AG2-447 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:51

Cedar Creek 138 kV VII

12.0 MW Capacity / 20.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Freepoint Solar LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Delmarva Power and Light Company.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request meets the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposits refunded. See Readiness Deposit calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $15,000,000 $0 = ∞ AND ( $15,000,000 - $0 ) 20.0 = $750,000 per MW

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the Delmarva Power and Light Company zone — New Castle County, Delaware. This project is an increase to the developer’s AC1-091/AC1-092/AC1-093/AC1-094/AC2-184/AC2-185 project(s), which will share the same Point of Interconnection. The AG2-447 project is a 20.0 MW uprate (12.0 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 134.25 MW with 55.3 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-447
Project Name:
Cedar Creek 138 kV VII
Project Developer Name:
Freepoint Solar LLC
State:
Delaware
County:
New Castle
Transmission Owner:
Delmarva Power and Light Company
MFO:
134.25
MWE:
20.0
MWC:
12.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Not Required

A Physical Interconnection Facilities Study is not required for this project.

Point of Interconnection

AG2-447 will interconnect with the Delmarva Power and Light Company transmission system at the Cedar Creek 138 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-447 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-447Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$0$0$0
Other Scope$0$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$0$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage$15,000,000$15,000,000$15,000,000
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$15,000,000$15,000,000$15,000,000

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-447

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-447
Project ID: AG2-447
20% of cost allocation for Phase II Network Upgrades:(A) $3,000,000
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $80,000
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $2,920,000
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

No TO Interconnection Facilities or Physical Network Upgrades are required for this project.

 



Transmission Owner Analysis

No impacts identified by Transmission Owner.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. DPL interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-447 was evaluated as a 20.0 MW (12.0 MW Capacity) injection in the DPL area.

AG2-447 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 134.25 MW (20.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DP&L
BRIDGEVL-TAYLOR 69.0 kV Ckt 1 line
DPL_P4_2_DP51_SRT-A
BreakerAC108.94 %64.0B69.72
0.65
GD2DP&L/PECO
CLAY_230-LINWOOD84 230.0 kV Ckt 1 line
PECO_P1-2_220-85_SRT-A/* $ DELCO $ PECO_P1-2_220-85 $ L
SingleAC108.56 %800.0B868.48
1.47
GD2AE/PECO
DELCOTAP-MCKLTON 230.0 kV Ckt 1 line
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
BreakerAC125.54 %637.0B799.67
1.0
GD2AE/PECO
DELCOTAP-MCKLTON 230.0 kV Ckt 1 line
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
BusAC125.54 %637.0B799.66
1.0
GD2AE/PECO
DELCOTAP-MCKLTON 230.0 kV Ckt 1 line
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
BreakerAC125.54 %637.0B799.66
1.0
GD2AE/PECO
DELCOTAP-MCKLTON 230.0 kV Ckt 1 line
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
BreakerAC125.49 %637.0B799.38
1.0
GD2DP&L
EDGEMR 5-CLAY_230 230.0 kV Ckt 1 line
PECO_P1-2_220-85_SRT-A/* $ DELCO $ PECO_P1-2_220-85 $ L
SingleAC104.67 %800.0B837.36
1.29
GD2DP&L/PECO
EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line
DPL_P4_2_DPEM231_SRT-A
BreakerAC105.87 %809.0B856.45
1.66
GD2DP&L/PECO
EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line
PECO_P1-2_220-84_SRT-A/* $ DELCO $ PECO_P1-2_220-84 $ L
SingleAC103.6 %809.0B838.11
1.41
GD2DP&L/PECO
EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line
PECO_P4_LINWO115_SRT-A/* $ DELCO $ PECO_P4_LINWO115 $ STBK
BreakerAC103.25 %809.0B835.32
1.95
GD2DP&L/PECO
EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line
DPL_P1_2_CKT 23015_SRT-A
SingleAC102.59 %809.0B829.93
1.29
GD2PECO
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
BreakerAC102.49 %1180.0B1209.36
1.71
GD2PECO
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
BusAC102.48 %1180.0B1209.3
1.71
GD2PECO
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
BreakerAC102.48 %1180.0B1209.29
1.71
GD2PECO
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
BreakerAC102.48 %1180.0B1209.25
1.71

Details for BRIDGEVL-TAYLOR 69.0 kV Ckt 1 line l/o DPL_P4_2_DP51_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DP&L
Facility Description:
BRIDGEVL-TAYLOR 69.0 kV Ckt 1 line
Contingency Name:
DPL_P4_2_DP51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.94 %
Rating:64.0 MVA
Rating Type:B
MVA to Mitigate:69.72
MW Contribution:
0.65
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DP&L
Facility Description:
BRIDGEVL-TAYLOR 69.0 kV Ckt 1 line
Contingency Name:
DPL_P4_2_DP51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.8 %
Rating:64.0 MVA
Rating Type:B
MVA to Mitigate:69.64
MW Contribution:
0.65
Bus #Bus NameTypeMW Contribution
232813VAUGHN
50/50
0.563
232432Z2-076 GEN
Solar/Wind Helper
0.038
233940AF2-379 C
Solar/Wind Helper
0.033
233901CHERRYDALE C
Solar/Wind Helper
0.115
232900DEMECSMY
Adder
3.705
233970AC1-092 C
Solar/Wind Harmer
0.487
232426Y1-080 FULL
Solar/Wind Helper
0.02
232404W1-003 C
Solar/Wind Helper
0.25
232408W1-005 C
Solar/Wind Helper
0.25
233996TM1833_GEN
Solar/Wind Helper
0.1
233998TM1NIN_3.36
Solar/Wind Helper
0.1
232910NRG_G1
50/50
5.385
233952AC2-187 GEN
Solar/Wind Harmer
1.591
233954AC2-188 GEN
Solar/Wind Harmer
1.591
233971AC1-093 C
Solar/Wind Harmer
0.463
234015AF2-250 C
Solar/Wind Helper
0.027
232428Y3-058 C
Solar/Wind Helper
0.205
233994AC2-023 GEN
Solar/Wind Helper
0.575
233946AB2-136 GEN
Solar/Wind Helper
0.284
232410W1-006 C
Solar/Wind Helper
0.25
234036AF2-325 C
Solar/Wind Helper
0.02
232911NRG_G2
50/50
0.294
233950AC2-186 GEN
Solar/Wind Harmer
0.795
233973AC2-185 C
Solar/Wind Harmer
0.984
970695AG2-447 GEN
Solar/Wind Harmer
0.651
233939AC1-091 C
Solar/Wind Harmer
0.487
233972AC1-094 C
Solar/Wind Harmer
0.391
232434Z2-077 GEN
Solar/Wind Helper
0.072
233964AF2-378 GEN
Solar/Wind Helper
0.021
232406W1-004 FULL
Solar/Wind Helper
0.25
233923SMA
Solar/Wind Helper
0.368
233997TMININ_4.2
Solar/Wind Helper
0.1
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.001
VTFLTFEXP_VFT->PJM
CMTX
0.038
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.001
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.001
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.005
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.003
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.017
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.017
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CLAY_230-LINWOOD84 230.0 kV Ckt 1 line l/o PECO_P1-2_220-85_SRT-A/* $ DELCO $ PECO_P1-2_220-85 $ L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DP&L/PECO
Facility Description:
CLAY_230-LINWOOD84 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_220-85_SRT-A/* $ DELCO $ PECO_P1-2_220-85 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.56 %
Rating:800.0 MVA
Rating Type:B
MVA to Mitigate:868.48
MW Contribution:
1.47
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DP&L/PECO
Facility Description:
CLAY_230-LINWOOD84 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_220-85_SRT-A/* $ DELCO $ PECO_P1-2_220-85 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.19 %
Rating:800.0 MVA
Rating Type:B
MVA to Mitigate:905.52
MW Contribution:
1.49
Bus #Bus NameTypeMW Contribution
231900EM5
50/50
11.61
231909HR2
50/50
2.479
231908HR1
50/50
2.429
231910HR3
50/50
2.429
232416X2-083
50/50
0.032
233930AB2-032 GEN
Solar/Wind Harmer
0.739
234014AF1-036_GEN
Solar/Wind Harmer
1.779
233984AB2-036 GEN
Solar/Wind Harmer
5.529
234041AC1-190 GEN
Solar/Wind Harmer
5.238
232926CRISFLD1
Adder
1.362
232410W1-006 C
Solar/Wind Harmer
0.446
232905CHERITON_25
Adder
1.696
232918OH NUG7
Adder
6.064
231940T-011
Adder
0.509
232910NRG_G1
Adder
5.875
233971AC1-093 C
Solar/Wind Harmer
1.06
219912AD2-042 GEN
Solar/Wind Helper
0.079
219904AC1-010 C
Solar/Wind Helper
0.031
231505HR4
50/50
4.966
231916EM3
50/50
1.705
231901EM4
50/50
3.378
231919CHRIST1
50/50
7.24
231920CHRIST2
50/50
7.079
231906DC3 NUG
50/50
12.728
231902DC CT7
50/50
10.175
231907DC10
50/50
3.178
233915AB1-141 GEN
Solar/Wind Harmer
0.197
233968AD2-076_GEN
Solar/Wind Harmer
1.779
970597AG2-380 GEN
Solar/Wind Harmer
3.186
971195AH1-057 GEN
Solar/Wind Harmer
0.432
232912OH NUG1
Adder
6.105
232913OH NUG2
Adder
6.023
232432Z2-076 GEN
Solar/Wind Harmer
0.009
232813VAUGHN
Adder
0.398
232920IR10
Adder
2.133
232904IR4
Adder
54.446
219258KINSLEYDEP C
Solar/Wind Helper
0.041
231917EM10
50/50
4.352
231918WEST 1
50/50
5.405
233918AB1-142 GEN
Solar/Wind Harmer
0.197
234012AE2-112_GEN
Solar/Wind Harmer
1.779
232902EASTMUNI
Adder
9.751
232919VN10
Adder
1.988
232404W1-003 C
Solar/Wind Harmer
0.446
232408W1-005 C
Solar/Wind Harmer
0.446
232917OH NUG6
Adder
6.078
232915OH NUG4
Adder
6.064
234033AF1-007_GEN
Solar/Wind Harmer
9.299
972177AH1-672 GEN
Solar/Wind Harmer
6.74
232900DEMECSMY
Adder
5.678
232901NORTHST
Adder
5.108
233970AC1-092 C
Solar/Wind Harmer
1.06
972251AH1-710 GEN
Adder
10.813
219766PARADISE C
Solar/Wind Helper
0.028
219907AC1-030 C
Solar/Wind Helper
0.017
231131BLOOM ENRGY
50/50
0.223
231915DC CT6
50/50
0.537
233935AB2-179 C
Solar/Wind Harmer
1.124
233987AB2-037 GEN
Solar/Wind Harmer
-0.001
232422X3-066 FULL
Solar/Wind Harmer
0.063
232907VN8
Adder
21.393
232406W1-004 FULL
Solar/Wind Harmer
0.446
232921TASLEY2G
Adder
3.568
232914OH NUG3
Adder
6.105
232916OH NUG5
Adder
6.105
232434Z2-077 GEN
Solar/Wind Harmer
0.028
233973AC2-185 C
Solar/Wind Harmer
1.06
970695AG2-447 GEN
Solar/Wind Harmer
1.469
233939AC1-091 C
Solar/Wind Harmer
1.06
233972AC1-094 C
Solar/Wind Harmer
1.06
219914AD2-027 C
Solar/Wind Helper
0.06
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
NYPJM->LTFIMP_NY
CLTF
0.965
LGEELTFEXP_LGEE->PJM
CLTF
0.057
WECLTFEXP_WEC->PJM
CLTF
0.028
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.978
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.381
MECLTFEXP_MEC->PJM
CLTF
0.135
SIGELTFEXP_SIGE->PJM
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.206
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.423
TVALTFEXP_TVA->PJM
CLTF
0.106
CPLELTFEXP_CPLE->PJM
CLTF
0.167
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.241

Details for DELCOTAP-MCKLTON 230.0 kV Ckt 1 line l/o PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AE/PECO
Facility Description:
DELCOTAP-MCKLTON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.54 %
Rating:637.0 MVA
Rating Type:B
MVA to Mitigate:799.67
MW Contribution:
1.0
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AE/PECO
Facility Description:
DELCOTAP-MCKLTON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.53 %
Rating:637.0 MVA
Rating Type:B
MVA to Mitigate:812.34
MW Contribution:
1.01
Bus #Bus NameTypeMW Contribution
231900EM5
50/50
6.808
231909HR2
50/50
1.373
231908HR1
50/50
1.37
231910HR3
50/50
1.37
232416X2-083
50/50
0.018
233930AB2-032 GEN
Solar/Wind Harmer
0.34
233982AB2-133 GEN
Solar/Wind Harmer
1.961
234014AF1-036_GEN
Solar/Wind Harmer
1.09
232436AB1-176 C
Solar/Wind Harmer
0.092
233984AB2-036 GEN
Solar/Wind Harmer
4.963
232424Y1-079 C
Solar/Wind Harmer
0.224
234041AC1-190 GEN
Solar/Wind Harmer
3.298
234036AF2-325 C
Solar/Wind Harmer
0.336
233946AB2-136 GEN
Solar/Wind Harmer
1.456
233994AC2-023 GEN
Solar/Wind Harmer
0.95
232428Y3-058 C
Solar/Wind Harmer
0.294
232926CRISFLD1
Adder
0.69
234015AF2-250 C
Solar/Wind Harmer
0.042
232410W1-006 C
Solar/Wind Harmer
0.35
232905CHERITON_25
Adder
0.858
232918OH NUG7
Adder
3.066
232910NRG_G1
Adder
2.973
231940T-011
Adder
0.256
233952AC2-187 GEN
Solar/Wind Harmer
0.376
233954AC2-188 GEN
Solar/Wind Harmer
0.376
233971AC1-093 C
Solar/Wind Harmer
0.714
219904AC1-010 C
Solar/Wind Helper
0.043
230511AF1-262
Solar/Wind Helper
0.01
219912AD2-042 GEN
Solar/Wind Helper
0.097
219906AC1-017 C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.066
219272CLEANLIGHT C
Solar/Wind Helper
0.013
230433AD2-135 GEN
Solar/Wind Helper
0.008
213893PHLISST1
50/50
5.367
231505HR4
50/50
2.912
231916EM3
50/50
0.944
231901EM4
50/50
1.905
231919CHRIST1
50/50
4.064
231920CHRIST2
50/50
3.974
231906DC3 NUG
Adder
6.37
231902DC CT7
Adder
5.092
231907DC10
Adder
1.59
233915AB1-141 GEN
Solar/Wind Harmer
0.404
233968AD2-076_GEN
Solar/Wind Harmer
2.671
970597AG2-380 GEN
Solar/Wind Harmer
1.677
233955AB2-172 GEN
Solar/Wind Harmer
1.844
233940AF2-379 C
Solar/Wind Harmer
0.066
971195AH1-057 GEN
Solar/Wind Harmer
0.341
233901CHERRYDALE C
Solar/Wind Harmer
0.393
232912OH NUG1
Adder
3.087
232913OH NUG2
Adder
3.046
232432Z2-076 GEN
Solar/Wind Harmer
0.045
232813VAUGHN
Adder
0.2
232920IR10
Adder
1.07
232904IR4
Adder
27.293
219258KINSLEYDEP C
Solar/Wind Helper
0.064
230434AG1-499 GEN
Solar/Wind Helper
0.17
228728W1-130C
Solar/Wind Helper
0.032
219615MILLCREEK C
Solar/Wind Helper
0.014
230407AD2-065 C
Solar/Wind Helper
0.02
213889PHLISCT2
50/50
3.714
231917EM10
50/50
2.41
231918WEST 1
50/50
3.002
233918AB1-142 GEN
Solar/Wind Harmer
0.404
234012AE2-112_GEN
Solar/Wind Harmer
0.927
233944AB2-135 GEN
Solar/Wind Harmer
2.051
232902EASTMUNI
Adder
5.07
232426Y1-080 FULL
Solar/Wind Harmer
0.069
232919VN10
Adder
1.014
233996TM1833_GEN
Solar/Wind Harmer
0.35
233998TM1NIN_3.36
Solar/Wind Harmer
0.35
232404W1-003 C
Solar/Wind Harmer
0.35
232408W1-005 C
Solar/Wind Harmer
0.35
232917OH NUG6
Adder
3.073
232915OH NUG4
Adder
3.066
234033AF1-007_GEN
Solar/Wind Harmer
12.555
972177AH1-672 GEN
Solar/Wind Harmer
4.432
232900DEMECSMY
Adder
2.76
232901NORTHST
Adder
2.475
233970AC1-092 C
Solar/Wind Harmer
0.751
219766PARADISE C
Solar/Wind Helper
0.039
219907AC1-030 C
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.058
213400COVANTA DELA
50/50
2.939
213890PHLISCT3
50/50
3.721
213888PHLISCT1
50/50
3.714
233935AB2-179 C
Solar/Wind Harmer
1.114
233933AB2-153 GEN
Solar/Wind Harmer
0.459
232422X3-066 FULL
Solar/Wind Harmer
0.1
233987AB2-037 GEN
Solar/Wind Harmer
4.518
232417X3-008 C
Solar/Wind Harmer
0.415
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.921
233923SMA
Solar/Wind Harmer
1.284
233997TMININ_4.2
Solar/Wind Harmer
0.35
232406W1-004 FULL
Solar/Wind Harmer
0.35
232921TASLEY2G
Adder
1.804
232914OH NUG3
Adder
3.087
232916OH NUG5
Adder
3.087
232434Z2-077 GEN
Solar/Wind Harmer
0.085
233950AC2-186 GEN
Solar/Wind Harmer
0.188
233973AC2-185 C
Solar/Wind Harmer
1.518
970695AG2-447 GEN
Solar/Wind Harmer
1.004
233939AC1-091 C
Solar/Wind Harmer
0.751
233972AC1-094 C
Solar/Wind Harmer
0.603
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.034
219914AD2-027 C
Solar/Wind Helper
0.075
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
230415AB2-049 C
Solar/Wind Helper
0.017
219291REEVESSOUT C
Solar/Wind Helper
0.006
NYPJM->LTFIMP_NY
CLTF
0.931
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.024
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.017
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.161
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.233
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for DELCOTAP-MCKLTON 230.0 kV Ckt 1 line l/o PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AE/PECO
Facility Description:
DELCOTAP-MCKLTON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:125.54 %
Rating:637.0 MVA
Rating Type:B
MVA to Mitigate:799.66
MW Contribution:
1.0
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AE/PECO
Facility Description:
DELCOTAP-MCKLTON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:127.53 %
Rating:637.0 MVA
Rating Type:B
MVA to Mitigate:812.34
MW Contribution:
1.01
Bus #Bus NameTypeMW Contribution
231900EM5
50/50
6.808
231909HR2
50/50
1.373
231908HR1
50/50
1.37
231910HR3
50/50
1.37
232416X2-083
50/50
0.018
233930AB2-032 GEN
Solar/Wind Harmer
0.34
233982AB2-133 GEN
Solar/Wind Harmer
1.961
234014AF1-036_GEN
Solar/Wind Harmer
1.09
232436AB1-176 C
Solar/Wind Harmer
0.092
233984AB2-036 GEN
Solar/Wind Harmer
4.963
232424Y1-079 C
Solar/Wind Harmer
0.224
234041AC1-190 GEN
Solar/Wind Harmer
3.298
234036AF2-325 C
Solar/Wind Harmer
0.336
233946AB2-136 GEN
Solar/Wind Harmer
1.456
233994AC2-023 GEN
Solar/Wind Harmer
0.95
232428Y3-058 C
Solar/Wind Harmer
0.294
232926CRISFLD1
Adder
0.69
234015AF2-250 C
Solar/Wind Harmer
0.042
232410W1-006 C
Solar/Wind Harmer
0.35
232905CHERITON_25
Adder
0.858
232918OH NUG7
Adder
3.066
232910NRG_G1
Adder
2.973
231940T-011
Adder
0.256
233952AC2-187 GEN
Solar/Wind Harmer
0.376
213893PHLISST1
50/50
5.367
231505HR4
50/50
2.912
231916EM3
50/50
0.944
231901EM4
50/50
1.905
231919CHRIST1
50/50
4.064
231920CHRIST2
50/50
3.974
231906DC3 NUG
Adder
6.37
231902DC CT7
Adder
5.092
231907DC10
Adder
1.59
233915AB1-141 GEN
Solar/Wind Harmer
0.404
233968AD2-076_GEN
Solar/Wind Harmer
2.671
970597AG2-380 GEN
Solar/Wind Harmer
1.677
233955AB2-172 GEN
Solar/Wind Harmer
1.844
233940AF2-379 C
Solar/Wind Harmer
0.066
971195AH1-057 GEN
Solar/Wind Harmer
0.341
233901CHERRYDALE C
Solar/Wind Harmer
0.393
232912OH NUG1
Adder
3.087
232913OH NUG2
Adder
3.046
232432Z2-076 GEN
Solar/Wind Harmer
0.045
232813VAUGHN
Adder
0.2
232920IR10
Adder
1.07
232904IR4
Adder
27.293
219258KINSLEYDEP C
Solar/Wind Helper
0.064
230434AG1-499 GEN
Solar/Wind Helper
0.17
228728W1-130C
Solar/Wind Helper
0.032
219615MILLCREEK C
Solar/Wind Helper
0.014
230407AD2-065 C
Solar/Wind Helper
0.02
213889PHLISCT2
50/50
3.714
231917EM10
50/50
2.41
231918WEST 1
50/50
3.002
233918AB1-142 GEN
Solar/Wind Harmer
0.404
234012AE2-112_GEN
Solar/Wind Harmer
0.927
233944AB2-135 GEN
Solar/Wind Harmer
2.051
232902EASTMUNI
Adder
5.07
232426Y1-080 FULL
Solar/Wind Harmer
0.069
232919VN10
Adder
1.014
233996TM1833_GEN
Solar/Wind Harmer
0.35
233998TM1NIN_3.36
Solar/Wind Harmer
0.35
232404W1-003 C
Solar/Wind Harmer
0.35
232408W1-005 C
Solar/Wind Harmer
0.35
232917OH NUG6
Adder
3.073
232915OH NUG4
Adder
3.066
234033AF1-007_GEN
Solar/Wind Harmer
12.555
972177AH1-672 GEN
Solar/Wind Harmer
4.432
232900DEMECSMY
Adder
2.76
232901NORTHST
Adder
2.475
233970AC1-092 C
Solar/Wind Harmer
0.751
219766PARADISE C
Solar/Wind Helper
0.039
219907AC1-030 C
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.058
233954AC2-188 GEN
Solar/Wind Harmer
0.376
233971AC1-093 C
Solar/Wind Harmer
0.714
219904AC1-010 C
Solar/Wind Helper
0.043
230511AF1-262
Solar/Wind Helper
0.01
219912AD2-042 GEN
Solar/Wind Helper
0.097
219906AC1-017 C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.066
219272CLEANLIGHT C
Solar/Wind Helper
0.013
230433AD2-135 GEN
Solar/Wind Helper
0.008
213400COVANTA DELA
50/50
2.939
213890PHLISCT3
50/50
3.721
213888PHLISCT1
50/50
3.714
233935AB2-179 C
Solar/Wind Harmer
1.114
233933AB2-153 GEN
Solar/Wind Harmer
0.459
232422X3-066 FULL
Solar/Wind Harmer
0.1
233987AB2-037 GEN
Solar/Wind Harmer
4.518
232417X3-008 C
Solar/Wind Harmer
0.415
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.921
233923SMA
Solar/Wind Harmer
1.284
233997TMININ_4.2
Solar/Wind Harmer
0.35
232406W1-004 FULL
Solar/Wind Harmer
0.35
232921TASLEY2G
Adder
1.804
232914OH NUG3
Adder
3.087
232916OH NUG5
Adder
3.087
232434Z2-077 GEN
Solar/Wind Harmer
0.085
233950AC2-186 GEN
Solar/Wind Harmer
0.188
233973AC2-185 C
Solar/Wind Harmer
1.518
970695AG2-447 GEN
Solar/Wind Harmer
1.004
233939AC1-091 C
Solar/Wind Harmer
0.751
233972AC1-094 C
Solar/Wind Harmer
0.603
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.034
219914AD2-027 C
Solar/Wind Helper
0.075
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
230415AB2-049 C
Solar/Wind Helper
0.017
219291REEVESSOUT C
Solar/Wind Helper
0.006
NYPJM->LTFIMP_NY
CLTF
0.931
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.024
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.017
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.233
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.161
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for DELCOTAP-MCKLTON 230.0 kV Ckt 1 line l/o PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AE/PECO
Facility Description:
DELCOTAP-MCKLTON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.54 %
Rating:637.0 MVA
Rating Type:B
MVA to Mitigate:799.66
MW Contribution:
1.0
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AE/PECO
Facility Description:
DELCOTAP-MCKLTON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.52 %
Rating:637.0 MVA
Rating Type:B
MVA to Mitigate:812.33
MW Contribution:
1.01
Bus #Bus NameTypeMW Contribution
231900EM5
50/50
6.808
231909HR2
50/50
1.373
231908HR1
50/50
1.37
231910HR3
50/50
1.37
232416X2-083
50/50
0.018
233930AB2-032 GEN
Solar/Wind Harmer
0.34
233982AB2-133 GEN
Solar/Wind Harmer
1.961
234014AF1-036_GEN
Solar/Wind Harmer
1.09
232436AB1-176 C
Solar/Wind Harmer
0.092
233984AB2-036 GEN
Solar/Wind Harmer
4.963
232424Y1-079 C
Solar/Wind Harmer
0.224
234041AC1-190 GEN
Solar/Wind Harmer
3.298
234036AF2-325 C
Solar/Wind Harmer
0.336
233946AB2-136 GEN
Solar/Wind Harmer
1.456
233994AC2-023 GEN
Solar/Wind Harmer
0.95
232428Y3-058 C
Solar/Wind Harmer
0.294
232926CRISFLD1
Adder
0.69
234015AF2-250 C
Solar/Wind Harmer
0.042
232410W1-006 C
Solar/Wind Harmer
0.35
232905CHERITON_25
Adder
0.858
232918OH NUG7
Adder
3.066
232910NRG_G1
Adder
2.973
231940T-011
Adder
0.256
213893PHLISST1
50/50
5.367
231505HR4
50/50
2.912
231916EM3
50/50
0.944
231901EM4
50/50
1.905
231919CHRIST1
50/50
4.064
231920CHRIST2
50/50
3.974
231906DC3 NUG
Adder
6.37
231902DC CT7
Adder
5.092
231907DC10
Adder
1.59
233915AB1-141 GEN
Solar/Wind Harmer
0.404
233968AD2-076_GEN
Solar/Wind Harmer
2.671
970597AG2-380 GEN
Solar/Wind Harmer
1.677
233955AB2-172 GEN
Solar/Wind Harmer
1.844
233940AF2-379 C
Solar/Wind Harmer
0.066
971195AH1-057 GEN
Solar/Wind Harmer
0.341
233901CHERRYDALE C
Solar/Wind Harmer
0.393
232912OH NUG1
Adder
3.087
232913OH NUG2
Adder
3.046
232432Z2-076 GEN
Solar/Wind Harmer
0.045
232813VAUGHN
Adder
0.2
232920IR10
Adder
1.07
232904IR4
Adder
27.293
219258KINSLEYDEP C
Solar/Wind Helper
0.064
230434AG1-499 GEN
Solar/Wind Helper
0.17
228728W1-130C
Solar/Wind Helper
0.032
219615MILLCREEK C
Solar/Wind Helper
0.014
230407AD2-065 C
Solar/Wind Helper
0.02
213889PHLISCT2
50/50
3.714
231917EM10
50/50
2.41
231918WEST 1
50/50
3.002
233918AB1-142 GEN
Solar/Wind Harmer
0.404
234012AE2-112_GEN
Solar/Wind Harmer
0.927
233944AB2-135 GEN
Solar/Wind Harmer
2.051
232902EASTMUNI
Adder
5.07
232426Y1-080 FULL
Solar/Wind Harmer
0.069
232919VN10
Adder
1.014
233996TM1833_GEN
Solar/Wind Harmer
0.35
233998TM1NIN_3.36
Solar/Wind Harmer
0.35
232404W1-003 C
Solar/Wind Harmer
0.35
232408W1-005 C
Solar/Wind Harmer
0.35
232917OH NUG6
Adder
3.073
232915OH NUG4
Adder
3.066
234033AF1-007_GEN
Solar/Wind Harmer
12.555
972177AH1-672 GEN
Solar/Wind Harmer
4.432
232900DEMECSMY
Adder
2.76
232901NORTHST
Adder
2.475
233970AC1-092 C
Solar/Wind Harmer
0.751
219766PARADISE C
Solar/Wind Helper
0.039
219907AC1-030 C
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.058
233952AC2-187 GEN
Solar/Wind Harmer
0.376
233954AC2-188 GEN
Solar/Wind Harmer
0.376
233971AC1-093 C
Solar/Wind Harmer
0.714
219904AC1-010 C
Solar/Wind Helper
0.043
230511AF1-262
Solar/Wind Helper
0.01
219912AD2-042 GEN
Solar/Wind Helper
0.097
219906AC1-017 C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.066
219272CLEANLIGHT C
Solar/Wind Helper
0.013
230433AD2-135 GEN
Solar/Wind Helper
0.008
233950AC2-186 GEN
Solar/Wind Harmer
0.188
233973AC2-185 C
Solar/Wind Harmer
1.518
970695AG2-447 GEN
Solar/Wind Harmer
1.004
233939AC1-091 C
Solar/Wind Harmer
0.751
233972AC1-094 C
Solar/Wind Harmer
0.603
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.034
219914AD2-027 C
Solar/Wind Helper
0.075
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
230415AB2-049 C
Solar/Wind Helper
0.017
219291REEVESSOUT C
Solar/Wind Helper
0.006
213400COVANTA DELA
50/50
2.939
213890PHLISCT3
50/50
3.721
213888PHLISCT1
50/50
3.714
233935AB2-179 C
Solar/Wind Harmer
1.114
233933AB2-153 GEN
Solar/Wind Harmer
0.459
232422X3-066 FULL
Solar/Wind Harmer
0.1
233987AB2-037 GEN
Solar/Wind Harmer
4.518
232417X3-008 C
Solar/Wind Harmer
0.415
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.921
233923SMA
Solar/Wind Harmer
1.284
233997TMININ_4.2
Solar/Wind Harmer
0.35
232406W1-004 FULL
Solar/Wind Harmer
0.35
232921TASLEY2G
Adder
1.804
232914OH NUG3
Adder
3.087
232916OH NUG5
Adder
3.087
232434Z2-077 GEN
Solar/Wind Harmer
0.085
NYPJM->LTFIMP_NY
CLTF
0.931
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.024
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.017
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.233
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.161
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for DELCOTAP-MCKLTON 230.0 kV Ckt 1 line l/o PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AE/PECO
Facility Description:
DELCOTAP-MCKLTON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.49 %
Rating:637.0 MVA
Rating Type:B
MVA to Mitigate:799.38
MW Contribution:
1.0
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AE/PECO
Facility Description:
DELCOTAP-MCKLTON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.48 %
Rating:637.0 MVA
Rating Type:B
MVA to Mitigate:812.05
MW Contribution:
1.01
Bus #Bus NameTypeMW Contribution
213893PHLISST1
50/50
5.376
231505HR4
50/50
2.91
231916EM3
50/50
0.944
231901EM4
50/50
1.904
231919CHRIST1
50/50
4.062
231920CHRIST2
50/50
3.972
231906DC3 NUG
Adder
6.367
231902DC CT7
Adder
5.09
231907DC10
Adder
1.589
233915AB1-141 GEN
Solar/Wind Harmer
0.404
233968AD2-076_GEN
Solar/Wind Harmer
2.669
970597AG2-380 GEN
Solar/Wind Harmer
1.676
233955AB2-172 GEN
Solar/Wind Harmer
1.844
233940AF2-379 C
Solar/Wind Harmer
0.066
971195AH1-057 GEN
Solar/Wind Harmer
0.341
233901CHERRYDALE C
Solar/Wind Harmer
0.393
232912OH NUG1
Adder
3.085
232913OH NUG2
Adder
3.044
232432Z2-076 GEN
Solar/Wind Harmer
0.045
232813VAUGHN
Adder
0.2
232920IR10
Adder
1.07
232904IR4
Adder
27.28
219258KINSLEYDEP C
Solar/Wind Helper
0.064
230434AG1-499 GEN
Solar/Wind Helper
0.17
228728W1-130C
Solar/Wind Helper
0.032
219615MILLCREEK C
Solar/Wind Helper
0.014
230407AD2-065 C
Solar/Wind Helper
0.02
213889PHLISCT2
50/50
3.708
231917EM10
50/50
2.409
231918WEST 1
50/50
3.001
233918AB1-142 GEN
Solar/Wind Harmer
0.404
234012AE2-112_GEN
Solar/Wind Harmer
0.926
233944AB2-135 GEN
Solar/Wind Harmer
2.05
232902EASTMUNI
Adder
5.068
232426Y1-080 FULL
Solar/Wind Harmer
0.069
232919VN10
Adder
1.013
233996TM1833_GEN
Solar/Wind Harmer
0.35
233998TM1NIN_3.36
Solar/Wind Harmer
0.35
232404W1-003 C
Solar/Wind Harmer
0.349
232408W1-005 C
Solar/Wind Harmer
0.349
232917OH NUG6
Adder
3.072
232915OH NUG4
Adder
3.065
234033AF1-007_GEN
Solar/Wind Harmer
12.55
972177AH1-672 GEN
Solar/Wind Harmer
4.43
232900DEMECSMY
Adder
2.758
232901NORTHST
Adder
2.474
233970AC1-092 C
Solar/Wind Harmer
0.751
219766PARADISE C
Solar/Wind Helper
0.039
219907AC1-030 C
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.058
231900EM5
50/50
6.804
231909HR2
50/50
1.372
231908HR1
50/50
1.369
231910HR3
50/50
1.369
232416X2-083
50/50
0.018
233930AB2-032 GEN
Solar/Wind Harmer
0.34
233982AB2-133 GEN
Solar/Wind Harmer
1.961
234014AF1-036_GEN
Solar/Wind Harmer
1.09
232436AB1-176 C
Solar/Wind Harmer
0.092
233984AB2-036 GEN
Solar/Wind Harmer
4.961
232424Y1-079 C
Solar/Wind Harmer
0.224
234041AC1-190 GEN
Solar/Wind Harmer
3.297
234036AF2-325 C
Solar/Wind Harmer
0.336
233946AB2-136 GEN
Solar/Wind Harmer
1.456
233994AC2-023 GEN
Solar/Wind Harmer
0.95
232428Y3-058 C
Solar/Wind Harmer
0.294
232926CRISFLD1
Adder
0.69
234015AF2-250 C
Solar/Wind Harmer
0.042
232410W1-006 C
Solar/Wind Harmer
0.349
232905CHERITON_25
Adder
0.857
232918OH NUG7
Adder
3.065
232910NRG_G1
Adder
2.972
231940T-011
Adder
0.256
233952AC2-187 GEN
Solar/Wind Harmer
0.376
233954AC2-188 GEN
Solar/Wind Harmer
0.376
233971AC1-093 C
Solar/Wind Harmer
0.713
219904AC1-010 C
Solar/Wind Helper
0.043
230511AF1-262
Solar/Wind Helper
0.01
219912AD2-042 GEN
Solar/Wind Helper
0.097
219906AC1-017 C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.066
219272CLEANLIGHT C
Solar/Wind Helper
0.013
230433AD2-135 GEN
Solar/Wind Helper
0.008
213400COVANTA DELA
50/50
2.939
213890PHLISCT3
50/50
3.727
213888PHLISCT1
50/50
3.708
233935AB2-179 C
Solar/Wind Harmer
1.113
233933AB2-153 GEN
Solar/Wind Harmer
0.459
232422X3-066 FULL
Solar/Wind Harmer
0.1
233987AB2-037 GEN
Solar/Wind Harmer
4.516
232417X3-008 C
Solar/Wind Harmer
0.415
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.916
233923SMA
Solar/Wind Harmer
1.284
233997TMININ_4.2
Solar/Wind Harmer
0.35
232406W1-004 FULL
Solar/Wind Harmer
0.349
232921TASLEY2G
Adder
1.804
232914OH NUG3
Adder
3.085
232916OH NUG5
Adder
3.085
232434Z2-077 GEN
Solar/Wind Harmer
0.085
233950AC2-186 GEN
Solar/Wind Harmer
0.188
233973AC2-185 C
Solar/Wind Harmer
1.517
970695AG2-447 GEN
Solar/Wind Harmer
1.004
233939AC1-091 C
Solar/Wind Harmer
0.751
233972AC1-094 C
Solar/Wind Harmer
0.603
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.034
219914AD2-027 C
Solar/Wind Helper
0.075
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
230415AB2-049 C
Solar/Wind Helper
0.017
219291REEVESSOUT C
Solar/Wind Helper
0.006
NYPJM->LTFIMP_NY
CLTF
0.931
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.024
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.017
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.161
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.233
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for EDGEMR 5-CLAY_230 230.0 kV Ckt 1 line l/o PECO_P1-2_220-85_SRT-A/* $ DELCO $ PECO_P1-2_220-85 $ L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DP&L
Facility Description:
EDGEMR 5-CLAY_230 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_220-85_SRT-A/* $ DELCO $ PECO_P1-2_220-85 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.67 %
Rating:800.0 MVA
Rating Type:B
MVA to Mitigate:837.36
MW Contribution:
1.29
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DP&L
Facility Description:
EDGEMR 5-CLAY_230 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_220-85_SRT-A/* $ DELCO $ PECO_P1-2_220-85 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.82 %
Rating:800.0 MVA
Rating Type:B
MVA to Mitigate:870.58
MW Contribution:
1.31
Bus #Bus NameTypeMW Contribution
231900EM5
50/50
11.61
231908HR1
50/50
1.78
231910HR3
50/50
1.78
232416X2-083
50/50
0.027
231909HR2
50/50
1.327
233930AB2-032 GEN
Solar/Wind Harmer
0.637
233984AB2-036 GEN
Solar/Wind Harmer
4.834
234014AF1-036_GEN
Solar/Wind Harmer
1.545
234041AC1-190 GEN
Solar/Wind Harmer
4.62
232926CRISFLD1
Adder
1.204
232410W1-006 C
Solar/Wind Harmer
0.394
232905CHERITON_25
Adder
1.499
232918OH NUG7
Adder
5.358
231940T-011
Adder
0.45
232910NRG_G1
Adder
5.125
233971AC1-093 C
Solar/Wind Harmer
0.933
231505HR4
50/50
4.966
231901EM4
50/50
2.477
231919CHRIST1
50/50
5.371
231920CHRIST2
50/50
5.252
231916EM3
50/50
0.913
231906DC3 NUG
50/50
10.439
231902DC CT7
50/50
8.345
231907DC10
50/50
2.606
233915AB1-141 GEN
Solar/Wind Harmer
0.17
233968AD2-076_GEN
Solar/Wind Harmer
1.545
970597AG2-380 GEN
Solar/Wind Harmer
2.767
971195AH1-057 GEN
Solar/Wind Harmer
0.382
232912OH NUG1
Adder
5.394
232913OH NUG2
Adder
5.322
232432Z2-076 GEN
Solar/Wind Harmer
0.008
232920IR10
Adder
1.884
232904IR4
Adder
48.087
232813VAUGHN
Adder
0.348
231918WEST 1
50/50
3.435
231917EM10
50/50
2.329
233918AB1-142 GEN
Solar/Wind Harmer
0.17
234012AE2-112_GEN
Solar/Wind Harmer
1.545
232902EASTMUNI
Adder
8.57
232919VN10
Adder
1.756
232404W1-003 C
Solar/Wind Harmer
0.394
232408W1-005 C
Solar/Wind Harmer
0.394
232917OH NUG6
Adder
5.37
232915OH NUG4
Adder
5.358
234033AF1-007_GEN
Solar/Wind Harmer
8.213
972177AH1-672 GEN
Solar/Wind Harmer
5.944
232901NORTHST
Adder
4.505
232900DEMECSMY
Adder
4.989
233970AC1-092 C
Solar/Wind Harmer
0.933
231131BLOOM ENRGY
50/50
0.182
231915DC CT6
50/50
0.44
233935AB2-179 C
Solar/Wind Harmer
0.943
233987AB2-037 GEN
Solar/Wind Harmer
-0.001
232422X3-066 FULL
Solar/Wind Harmer
0.055
232907VN8
Adder
18.917
232406W1-004 FULL
Solar/Wind Harmer
0.394
232921TASLEY2G
Adder
3.153
232914OH NUG3
Adder
5.394
232916OH NUG5
Adder
5.394
232434Z2-077 GEN
Solar/Wind Harmer
0.025
233973AC2-185 C
Solar/Wind Harmer
0.933
970695AG2-447 GEN
Solar/Wind Harmer
1.293
233939AC1-091 C
Solar/Wind Harmer
0.933
233972AC1-094 C
Solar/Wind Harmer
0.933
NYPJM->LTFIMP_NY
CLTF
0.85
LGEELTFEXP_LGEE->PJM
CLTF
0.057
WECLTFEXP_WEC->PJM
CLTF
0.029
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.005
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.374
MECLTFEXP_MEC->PJM
CLTF
0.136
SIGELTFEXP_SIGE->PJM
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.404
TVALTFEXP_TVA->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.159
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.228

Details for EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line l/o DPL_P4_2_DPEM231_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DP&L/PECO
Facility Description:
EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line
Contingency Name:
DPL_P4_2_DPEM231_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.87 %
Rating:809.0 MVA
Rating Type:B
MVA to Mitigate:856.45
MW Contribution:
1.66
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DP&L/PECO
Facility Description:
EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line
Contingency Name:
DPL_P4_2_DPEM231_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.17 %
Rating:809.0 MVA
Rating Type:B
MVA to Mitigate:891.29
MW Contribution:
1.68
Bus #Bus NameTypeMW Contribution
231505HR4
50/50
5.505
232912OH NUG1
50/50
5.182
232913OH NUG2
50/50
5.113
232920IR10
50/50
1.807
232904IR4
50/50
46.131
233968AD2-076_GEN
Solar/Wind Harmer
3.858
970597AG2-380 GEN
Solar/Wind Harmer
2.423
233915AB1-141 GEN
Solar/Wind Harmer
0.569
233955AB2-172 GEN
Solar/Wind Harmer
2.862
233940AF2-379 C
Solar/Wind Harmer
0.104
233901CHERRYDALE C
Solar/Wind Harmer
0.622
971195AH1-057 GEN
Solar/Wind Harmer
0.539
232432Z2-076 GEN
Solar/Wind Harmer
0.071
231906DC3 NUG
Adder
7.375
231902DC CT7
Adder
5.896
231907DC10
Adder
1.841
232813VAUGHN
Adder
0.309
231919CHRIST1
Adder
2.247
231920CHRIST2
Adder
2.197
232902EASTMUNI
50/50
8.155
232919VN10
50/50
1.686
232917OH NUG6
50/50
5.159
232915OH NUG4
50/50
5.147
234012AE2-112_GEN
Solar/Wind Harmer
1.339
233918AB1-142 GEN
Solar/Wind Harmer
0.569
232426Y1-080 FULL
Solar/Wind Harmer
0.108
233944AB2-135 GEN
Solar/Wind Harmer
2.918
233996TM1833_GEN
Solar/Wind Harmer
0.553
233998TM1NIN_3.36
Solar/Wind Harmer
0.553
232404W1-003 C
Solar/Wind Harmer
0.553
232408W1-005 C
Solar/Wind Harmer
0.553
234033AF1-007_GEN
Solar/Wind Harmer
19.999
972177AH1-672 GEN
Solar/Wind Harmer
7.065
231918WEST 1
Adder
1.731
232901NORTHST
Adder
4.056
232900DEMECSMY
Adder
4.46
233970AC1-092 C
Solar/Wind Harmer
1.241
231917EM10
Adder
0.874
231900EM5
50/50
12.87
232416X2-083
50/50
0.022
232926CRISFLD1
50/50
1.157
232905CHERITON_25
50/50
1.439
232918OH NUG7
50/50
5.147
231940T-011
50/50
0.431
233984AB2-036 GEN
Solar/Wind Harmer
7.348
232424Y1-079 C
Solar/Wind Harmer
0.33
234014AF1-036_GEN
Solar/Wind Harmer
1.575
232436AB1-176 C
Solar/Wind Harmer
0.132
233930AB2-032 GEN
Solar/Wind Harmer
0.479
234041AC1-190 GEN
Solar/Wind Harmer
5.123
234036AF2-325 C
Solar/Wind Harmer
0.523
233946AB2-136 GEN
Solar/Wind Harmer
2.271
233982AB2-133 GEN
Solar/Wind Harmer
2.752
233994AC2-023 GEN
Solar/Wind Harmer
1.497
232428Y3-058 C
Solar/Wind Harmer
0.463
232410W1-006 C
Solar/Wind Harmer
0.553
234015AF2-250 C
Solar/Wind Harmer
0.066
233952AC2-187 GEN
Solar/Wind Harmer
0.59
233954AC2-188 GEN
Solar/Wind Harmer
0.59
232910NRG_G1
Adder
4.521
233971AC1-093 C
Solar/Wind Harmer
1.179
232907VN8
50/50
18.205
233900O-025 C
50/50
0.038
232921TASLEY2G
50/50
3.029
232914OH NUG3
50/50
5.182
232916OH NUG5
50/50
5.182
234034AF2-060
50/50
1.036
231131BLOOM ENRGY
50/50
0.134
233987AB2-037 GEN
Solar/Wind Harmer
7.064
232422X3-066 FULL
Solar/Wind Harmer
0.144
233933AB2-153 GEN
Solar/Wind Harmer
0.647
232417X3-008 C
Solar/Wind Harmer
0.644
233964AF2-378 GEN
Solar/Wind Harmer
0.073
233935AB2-179 C
Solar/Wind Harmer
1.393
233923SMA
Solar/Wind Harmer
2.029
233997TMININ_4.2
Solar/Wind Harmer
0.553
232406W1-004 FULL
Solar/Wind Harmer
0.553
232434Z2-077 GEN
Solar/Wind Harmer
0.135
233950AC2-186 GEN
Solar/Wind Harmer
0.295
233973AC2-185 C
Solar/Wind Harmer
2.508
970695AG2-447 GEN
Solar/Wind Harmer
1.659
233939AC1-091 C
Solar/Wind Harmer
1.241
233972AC1-094 C
Solar/Wind Harmer
0.997
NYPJM->LTFIMP_NY
CLTF
0.768
LGEELTFEXP_LGEE->PJM
CLTF
0.062
WECLTFEXP_WEC->PJM
CLTF
0.031
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.118
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.394
MECLTFEXP_MEC->PJM
CLTF
0.147
SIGELTFEXP_SIGE->PJM
CLTF
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
0.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.41
TVALTFEXP_TVA->PJM
CLTF
0.108
CPLELTFEXP_CPLE->PJM
CLTF
0.16
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.307

Details for EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line l/o PECO_P1-2_220-84_SRT-A/* $ DELCO $ PECO_P1-2_220-84 $ L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DP&L/PECO
Facility Description:
EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_220-84_SRT-A/* $ DELCO $ PECO_P1-2_220-84 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.6 %
Rating:809.0 MVA
Rating Type:B
MVA to Mitigate:838.11
MW Contribution:
1.41
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DP&L/PECO
Facility Description:
EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_220-84_SRT-A/* $ DELCO $ PECO_P1-2_220-84 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.96 %
Rating:809.0 MVA
Rating Type:B
MVA to Mitigate:873.4
MW Contribution:
1.43
Bus #Bus NameTypeMW Contribution
231900EM5
50/50
11.435
231908HR1
50/50
2.266
231910HR3
50/50
2.266
231909HR2
50/50
2.217
232416X2-083
50/50
0.03
233930AB2-032 GEN
Solar/Wind Harmer
0.708
234014AF1-036_GEN
Solar/Wind Harmer
1.707
233984AB2-036 GEN
Solar/Wind Harmer
5.311
234041AC1-190 GEN
Solar/Wind Harmer
5.039
232926CRISFLD1
Adder
1.311
232410W1-006 C
Solar/Wind Harmer
0.43
232905CHERITON_25
Adder
1.632
232918OH NUG7
Adder
5.835
231940T-011
Adder
0.49
232910NRG_G1
Adder
5.64
233971AC1-093 C
Solar/Wind Harmer
1.02
219912AD2-042 GEN
Solar/Wind Helper
0.076
219904AC1-010 C
Solar/Wind Helper
0.03
231505HR4
50/50
4.891
231901EM4
50/50
3.152
231916EM3
50/50
1.525
231919CHRIST1
50/50
6.766
231920CHRIST2
50/50
6.616
231906DC3 NUG
50/50
12.091
231902DC CT7
50/50
9.666
231907DC10
50/50
3.018
233915AB1-141 GEN
Solar/Wind Harmer
0.188
233968AD2-076_GEN
Solar/Wind Harmer
1.707
970597AG2-380 GEN
Solar/Wind Harmer
3.057
971195AH1-057 GEN
Solar/Wind Harmer
0.416
232912OH NUG1
Adder
5.875
232913OH NUG2
Adder
5.796
232432Z2-076 GEN
Solar/Wind Harmer
0.009
232920IR10
Adder
2.053
232813VAUGHN
Adder
0.382
232904IR4
Adder
52.389
219258KINSLEYDEP C
Solar/Wind Helper
0.039
231917EM10
50/50
3.892
231918WEST 1
50/50
4.939
233918AB1-142 GEN
Solar/Wind Harmer
0.188
234012AE2-112_GEN
Solar/Wind Harmer
1.707
232902EASTMUNI
Adder
9.374
232919VN10
Adder
1.913
232404W1-003 C
Solar/Wind Harmer
0.43
232408W1-005 C
Solar/Wind Harmer
0.43
232917OH NUG6
Adder
5.849
232915OH NUG4
Adder
5.835
234033AF1-007_GEN
Solar/Wind Harmer
8.948
972177AH1-672 GEN
Solar/Wind Harmer
6.483
232900DEMECSMY
Adder
5.458
232901NORTHST
Adder
4.914
233970AC1-092 C
Solar/Wind Harmer
1.02
219766PARADISE C
Solar/Wind Helper
0.027
231131BLOOM ENRGY
50/50
0.212
231915DC CT6
50/50
0.51
233935AB2-179 C
Solar/Wind Harmer
1.072
233987AB2-037 GEN
Solar/Wind Harmer
-0.001
232422X3-066 FULL
Solar/Wind Harmer
0.061
232907VN8
Adder
20.589
232406W1-004 FULL
Solar/Wind Harmer
0.43
232921TASLEY2G
Adder
3.434
232914OH NUG3
Adder
5.875
232916OH NUG5
Adder
5.875
232434Z2-077 GEN
Solar/Wind Harmer
0.027
233973AC2-185 C
Solar/Wind Harmer
1.02
970695AG2-447 GEN
Solar/Wind Harmer
1.413
233939AC1-091 C
Solar/Wind Harmer
1.02
233972AC1-094 C
Solar/Wind Harmer
1.02
219914AD2-027 C
Solar/Wind Helper
0.058
NYPJM->LTFIMP_NY
CLTF
0.928
LGEELTFEXP_LGEE->PJM
CLTF
0.057
WECLTFEXP_WEC->PJM
CLTF
0.028
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.978
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.377
MECLTFEXP_MEC->PJM
CLTF
0.134
SIGELTFEXP_SIGE->PJM
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.204
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.415
TVALTFEXP_TVA->PJM
CLTF
0.104
CPLELTFEXP_CPLE->PJM
CLTF
0.164
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.229

Details for EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line l/o PECO_P4_LINWO115_SRT-A/* $ DELCO $ PECO_P4_LINWO115 $ STBK


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DP&L/PECO
Facility Description:
EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_LINWO115_SRT-A/* $ DELCO $ PECO_P4_LINWO115 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.25 %
Rating:809.0 MVA
Rating Type:B
MVA to Mitigate:835.32
MW Contribution:
1.95
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DP&L/PECO
Facility Description:
EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_LINWO115_SRT-A/* $ DELCO $ PECO_P4_LINWO115 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.5 %
Rating:809.0 MVA
Rating Type:B
MVA to Mitigate:869.71
MW Contribution:
1.97
Bus #Bus NameTypeMW Contribution
231505HR4
50/50
4.701
231901EM4
50/50
3.03
231916EM3
50/50
1.466
231919CHRIST1
50/50
6.505
231920CHRIST2
50/50
6.36
231906DC3 NUG
50/50
11.629
231902DC CT7
50/50
9.297
231907DC10
50/50
2.903
233915AB1-141 GEN
Solar/Wind Harmer
0.703
233968AD2-076_GEN
Solar/Wind Harmer
4.683
970597AG2-380 GEN
Solar/Wind Harmer
2.941
233955AB2-172 GEN
Solar/Wind Harmer
3.329
233940AF2-379 C
Solar/Wind Harmer
0.12
971195AH1-057 GEN
Solar/Wind Harmer
0.624
233901CHERRYDALE C
Solar/Wind Harmer
0.72
232912OH NUG1
Adder
5.652
232913OH NUG2
Adder
5.577
232432Z2-076 GEN
Solar/Wind Harmer
0.083
232920IR10
Adder
1.975
232813VAUGHN
Adder
0.368
232904IR4
Adder
50.408
219258KINSLEYDEP C
Solar/Wind Helper
0.038
231900EM5
50/50
10.99
231908HR1
50/50
2.178
231910HR3
50/50
2.178
231909HR2
50/50
2.131
232416X2-083
50/50
0.029
233930AB2-032 GEN
Solar/Wind Harmer
0.592
234014AF1-036_GEN
Solar/Wind Harmer
1.911
233982AB2-133 GEN
Solar/Wind Harmer
3.424
233984AB2-036 GEN
Solar/Wind Harmer
8.754
232436AB1-176 C
Solar/Wind Harmer
0.161
232424Y1-079 C
Solar/Wind Harmer
0.394
234041AC1-190 GEN
Solar/Wind Harmer
5.956
234036AF2-325 C
Solar/Wind Harmer
0.607
233946AB2-136 GEN
Solar/Wind Harmer
2.636
233994AC2-023 GEN
Solar/Wind Harmer
1.734
232428Y3-058 C
Solar/Wind Harmer
0.537
232926CRISFLD1
Adder
1.261
234015AF2-250 C
Solar/Wind Harmer
0.077
232410W1-006 C
Solar/Wind Harmer
0.64
232905CHERITON_25
Adder
1.57
232918OH NUG7
Adder
5.615
231940T-011
Adder
0.471
232910NRG_G1
Adder
5.427
233952AC2-187 GEN
Solar/Wind Harmer
0.694
233954AC2-188 GEN
Solar/Wind Harmer
0.694
233971AC1-093 C
Solar/Wind Harmer
1.385
219912AD2-042 GEN
Solar/Wind Helper
0.072
231917EM10
50/50
3.741
231918WEST 1
50/50
4.748
233918AB1-142 GEN
Solar/Wind Harmer
0.703
234012AE2-112_GEN
Solar/Wind Harmer
1.625
232902EASTMUNI
Adder
9.018
233944AB2-135 GEN
Solar/Wind Harmer
3.607
232426Y1-080 FULL
Solar/Wind Harmer
0.126
232919VN10
Adder
1.841
233996TM1833_GEN
Solar/Wind Harmer
0.64
233998TM1NIN_3.36
Solar/Wind Harmer
0.64
232404W1-003 C
Solar/Wind Harmer
0.64
232408W1-005 C
Solar/Wind Harmer
0.64
232917OH NUG6
Adder
5.627
232915OH NUG4
Adder
5.615
234033AF1-007_GEN
Solar/Wind Harmer
23.189
972177AH1-672 GEN
Solar/Wind Harmer
8.229
232900DEMECSMY
Adder
5.253
232901NORTHST
Adder
4.729
233970AC1-092 C
Solar/Wind Harmer
1.458
231131BLOOM ENRGY
50/50
0.204
231915DC CT6
50/50
0.49
233935AB2-179 C
Solar/Wind Harmer
1.875
233933AB2-153 GEN
Solar/Wind Harmer
0.799
233987AB2-037 GEN
Solar/Wind Harmer
8.044
232422X3-066 FULL
Solar/Wind Harmer
0.175
232417X3-008 C
Solar/Wind Harmer
0.749
233964AF2-378 GEN
Solar/Wind Harmer
0.084
232907VN8
Adder
19.808
233923SMA
Solar/Wind Harmer
2.348
233997TMININ_4.2
Solar/Wind Harmer
0.64
232406W1-004 FULL
Solar/Wind Harmer
0.64
232921TASLEY2G
Adder
3.304
232914OH NUG3
Adder
5.652
232916OH NUG5
Adder
5.652
232434Z2-077 GEN
Solar/Wind Harmer
0.157
233950AC2-186 GEN
Solar/Wind Harmer
0.347
233973AC2-185 C
Solar/Wind Harmer
2.946
970695AG2-447 GEN
Solar/Wind Harmer
1.949
233939AC1-091 C
Solar/Wind Harmer
1.458
233972AC1-094 C
Solar/Wind Harmer
1.171
219914AD2-027 C
Solar/Wind Helper
0.055
NYPJM->LTFIMP_NY
CLTF
0.881
LGEELTFEXP_LGEE->PJM
CLTF
0.065
WECLTFEXP_WEC->PJM
CLTF
0.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.171
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.422
MECLTFEXP_MEC->PJM
CLTF
0.155
SIGELTFEXP_SIGE->PJM
CLTF
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
0.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.446
TVALTFEXP_TVA->PJM
CLTF
0.116
CPLELTFEXP_CPLE->PJM
CLTF
0.175
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.394

Details for EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line l/o DPL_P1_2_CKT 23015_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DP&L/PECO
Facility Description:
EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line
Contingency Name:
DPL_P1_2_CKT 23015_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.59 %
Rating:809.0 MVA
Rating Type:B
MVA to Mitigate:829.93
MW Contribution:
1.29
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DP&L/PECO
Facility Description:
EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line
Contingency Name:
DPL_P1_2_CKT 23015_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.68 %
Rating:809.0 MVA
Rating Type:B
MVA to Mitigate:863.05
MW Contribution:
1.31
Bus #Bus NameTypeMW Contribution
231900EM5
50/50
11.51
231908HR1
50/50
1.795
231910HR3
50/50
1.795
232416X2-083
50/50
0.027
231909HR2
50/50
1.368
233930AB2-032 GEN
Solar/Wind Harmer
0.637
233984AB2-036 GEN
Solar/Wind Harmer
4.824
234014AF1-036_GEN
Solar/Wind Harmer
1.543
234041AC1-190 GEN
Solar/Wind Harmer
4.609
232926CRISFLD1
Adder
1.201
232410W1-006 C
Solar/Wind Harmer
0.393
232905CHERITON_25
Adder
1.495
232918OH NUG7
Adder
5.345
231940T-011
Adder
0.448
232910NRG_G1
Adder
5.115
233971AC1-093 C
Solar/Wind Harmer
0.931
231505HR4
50/50
4.923
231901EM4
50/50
2.496
231919CHRIST1
50/50
5.41
231920CHRIST2
50/50
5.29
231916EM3
50/50
0.941
231906DC3 NUG
50/50
10.454
231902DC CT7
50/50
8.357
231907DC10
50/50
2.61
233915AB1-141 GEN
Solar/Wind Harmer
0.169
233968AD2-076_GEN
Solar/Wind Harmer
1.543
970597AG2-380 GEN
Solar/Wind Harmer
2.763
971195AH1-057 GEN
Solar/Wind Harmer
0.381
232912OH NUG1
Adder
5.381
232913OH NUG2
Adder
5.309
232432Z2-076 GEN
Solar/Wind Harmer
0.008
232920IR10
Adder
1.879
232904IR4
Adder
47.965
232813VAUGHN
Adder
0.347
231918WEST 1
50/50
3.495
231917EM10
50/50
2.402
233918AB1-142 GEN
Solar/Wind Harmer
0.169
234012AE2-112_GEN
Solar/Wind Harmer
1.543
232902EASTMUNI
Adder
8.551
232919VN10
Adder
1.752
232404W1-003 C
Solar/Wind Harmer
0.393
232408W1-005 C
Solar/Wind Harmer
0.393
232917OH NUG6
Adder
5.357
232915OH NUG4
Adder
5.345
234033AF1-007_GEN
Solar/Wind Harmer
8.192
972177AH1-672 GEN
Solar/Wind Harmer
5.929
232901NORTHST
Adder
4.494
232900DEMECSMY
Adder
4.978
233970AC1-092 C
Solar/Wind Harmer
0.931
231131BLOOM ENRGY
50/50
0.182
231915DC CT6
50/50
0.441
233935AB2-179 C
Solar/Wind Harmer
0.943
233987AB2-037 GEN
Solar/Wind Harmer
-0.001
232422X3-066 FULL
Solar/Wind Harmer
0.055
232907VN8
Adder
18.868
232406W1-004 FULL
Solar/Wind Harmer
0.393
232921TASLEY2G
Adder
3.145
232914OH NUG3
Adder
5.381
232916OH NUG5
Adder
5.381
232434Z2-077 GEN
Solar/Wind Harmer
0.025
233973AC2-185 C
Solar/Wind Harmer
0.931
970695AG2-447 GEN
Solar/Wind Harmer
1.29
233939AC1-091 C
Solar/Wind Harmer
0.931
233972AC1-094 C
Solar/Wind Harmer
0.931
NYPJM->LTFIMP_NY
CLTF
0.848
LGEELTFEXP_LGEE->PJM
CLTF
0.057
WECLTFEXP_WEC->PJM
CLTF
0.029
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.372
MECLTFEXP_MEC->PJM
CLTF
0.135
SIGELTFEXP_SIGE->PJM
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.201
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.402
TVALTFEXP_TVA->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.158
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.223

Details for RICHMOND35-WANEETA3 230.0 kV Ckt 1 line l/o PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.49 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1209.36
MW Contribution:
1.71
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.95 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1273.83
MW Contribution:
1.73
Bus #Bus NameTypeMW Contribution
219229EAGLE PT ST
50/50
0.74
219231EAGLE PT CT2
50/50
1.461
230405GT2-CC
50/50
3.254
219224BRL12CT4
50/50
10.238
213536CROYDN12
50/50
1.292
213537CROYDN21
50/50
0.615
213538CROYDN22
50/50
0.615
213539CROYDN31
50/50
0.615
213540CROYDN32
50/50
0.603
219258KINSLEYDEP C
Solar/Wind Harmer
0.466
219137THOSOLAR C
Solar/Wind Harmer
1.626
219615MILLCREEK C
Solar/Wind Harmer
0.291
219610FLORENCE C
Solar/Wind Harmer
1.497
230434AG1-499 GEN
Solar/Wind Harmer
0.618
964001AG1-254 GEN
Solar/Wind Harmer
7.522
972141AH1-641 GEN
Solar/Wind Harmer
2.87
230430AE1-229_GEN
Solar/Wind Harmer
28.495
230407AD2-065 C
Solar/Wind Harmer
0.129
228728W1-130C
Solar/Wind Harmer
0.631
970453AG2-297 GEN
Solar/Wind Harmer
2.306
230422AE1-104_GEN1
Solar/Wind Harmer
28.004
230425AE1-104_GEN2
Solar/Wind Harmer
28.004
227927V4-067C
Solar/Wind Harmer
0.161
213611FALLS1-3
Adder
2.497
213611FALLS1-3
Adder
2.497
20720728JCB_W1-129
Solar/Wind Harmer
0.199
20715028HAN_X4-015
Solar/Wind Harmer
0.198
971189AH1-054 GEN
Solar/Wind Harmer
0.666
207487AE2-000G4
Solar/Wind Harmer
17.268
207497AE2-000G2
Solar/Wind Harmer
17.268
207500AE2-000G1
Solar/Wind Harmer
17.268
207507AE2-000G3
Solar/Wind Harmer
17.268
963401AG1-189 GEN
Solar/Wind Harmer
1.233
970025AG2-016 GEN
Solar/Wind Harmer
1.529
207445AB1-138_GEN
Solar/Wind Harmer
0.299
231919CHRIST1
Adder
2.298
231920CHRIST2
Adder
2.247
232904IR4
Adder
37.423
232920IR10
Adder
1.462
232432Z2-076 GEN
Solar/Wind Harmer
0.061
233901CHERRYDALE C
Solar/Wind Harmer
0.517
232912OH NUG1
Adder
4.062
232913OH NUG2
Adder
4.008
971195AH1-057 GEN
Solar/Wind Harmer
0.448
233940AF2-379 C
Solar/Wind Harmer
0.086
232813VAUGHN
Adder
0.269
233955AB2-172 GEN
Solar/Wind Harmer
2.266
231906DC3 NUG
Adder
6.26
231902DC CT7
Adder
5.004
231907DC10
Adder
1.563
233968AD2-076_GEN
Solar/Wind Harmer
2.871
970597AG2-380 GEN
Solar/Wind Harmer
1.803
233915AB1-141 GEN
Solar/Wind Harmer
0.422
20714428HOW_X1-037
Solar/Wind Harmer
0.482
20720628TIN_W1-124
Solar/Wind Harmer
0.386
971521AH1-258 GEN
Solar/Wind Harmer
0.973
20716228APLW2-078
Solar/Wind Harmer
0.296
219620RIDERU C
Solar/Wind Harmer
0.017
20635928PARLN3&4
Adder
2.175
218526CNTRALGAS2 C
Solar/Wind Harmer
0.099
213918RICHMD91
50/50
1.23
219267WHEELBRDEPTF
50/50
0.204
219230EAGLE PT CT1
50/50
1.462
219235Y2-105
50/50
0.528
228400MICK 1CT
50/50
14.896
219222BRL12CT2
50/50
10.238
213541CROYDN41
50/50
0.615
213618FORDAST1
50/50
2.931
213617FORDACT2
50/50
2.109
971525AH1-260 GEN
50/50
62.282
219766PARADISE C
Solar/Wind Harmer
0.477
219907AC1-030 C
Solar/Wind Harmer
0.197
219348LDSOLAR C
Solar/Wind Harmer
0.647
219686LUMSOLAR_N C
Solar/Wind Harmer
0.205
970997AG2-616 GEN
Solar/Wind Harmer
9.567
228260V4-054C
Solar/Wind Harmer
0.967
228206SHRMN CT
Adder
14.391
228732V1-021 C
Adder
0.158
228729W2-030 C
Solar/Wind Harmer
0.474
213611FALLS1-3
Adder
2.497
20716028EGP_W2-019
Solar/Wind Harmer
0.31
207522AF2-254 C
Solar/Wind Harmer
0.945
20717128DIX_Z2-102
Solar/Wind Harmer
0.859
20715828PEM_W1-120
Solar/Wind Harmer
0.342
972251AH1-710 GEN
Adder
26.009
219276PARKLANDSO C
Solar/Wind Harmer
0.249
231917EM10
Adder
1.278
231918WEST 1
Adder
1.709
963711AG1-223 GEN
Solar/Wind Harmer
0.68
20714528FRN_Y2-051
Solar/Wind Harmer
0.134
233970AC1-092 C
Solar/Wind Harmer
1.278
232901NORTHST
Adder
3.938
232900DEMECSMY
Adder
4.342
972177AH1-672 GEN
Solar/Wind Harmer
6.234
234033AF1-007_GEN
Solar/Wind Harmer
17.216
232917OH NUG6
Adder
4.044
232915OH NUG4
Adder
4.035
232404W1-003 C
Solar/Wind Harmer
0.46
232408W1-005 C
Solar/Wind Harmer
0.46
233996TM1833_GEN
Solar/Wind Harmer
0.458
233998TM1NIN_3.36
Solar/Wind Harmer
0.458
232919VN10
Adder
1.281
219126CAMDEN_CTG
50/50
1.475
219286CAMD CO RR
50/50
0.44
972233AH1-701 GEN
50/50
5.235
228307PCLP GT
50/50
14.42
213535CROYDN11
50/50
11.248
228201CARL#2CT
50/50
6.885
228200CARL#1CT
50/50
6.548
228251CARLLS#4
50/50
0.631
213619FORDBCT1
50/50
2.118
213620FORDBCT2
50/50
2.118
219912AD2-042 GEN
Solar/Wind Harmer
1.264
219904AC1-010 C
Solar/Wind Harmer
0.573
219906AC1-017 C
Solar/Wind Harmer
0.272
219272CLEANLIGHT C
Solar/Wind Harmer
0.201
219607WPEMNERT C
Solar/Wind Harmer
0.453
219304NAMERICA C
Solar/Wind Harmer
0.335
228351V2-046C
Solar/Wind Harmer
2.08
219287REEVESEAST C
Solar/Wind Harmer
1.363
230511AF1-262
Solar/Wind Harmer
0.181
230433AD2-135 GEN
Solar/Wind Harmer
0.096
228754AB1-001 C
Solar/Wind Harmer
0.115
214067T20SOLAR
Solar/Wind Harmer
0.178
20720828JCB_W4-025
Solar/Wind Harmer
0.302
20636128O CRK C2
Adder
3.533
207459AE1-142 C O1
Solar/Wind Harmer
0.543
20628028LAKEHURS
Adder
0.49
20714828MDF_W3-079
Solar/Wind Harmer
0.14
233971AC1-093 C
Solar/Wind Harmer
1.213
231940T-011
Adder
0.344
233952AC2-187 GEN
Solar/Wind Harmer
0.518
233954AC2-188 GEN
Solar/Wind Harmer
0.518
232918OH NUG7
Adder
4.035
232905CHERITON_25
Adder
1.128
232410W1-006 C
Solar/Wind Harmer
0.46
234015AF2-250 C
Solar/Wind Harmer
0.055
232926CRISFLD1
Adder
0.902
232428Y3-058 C
Solar/Wind Harmer
0.382
233994AC2-023 GEN
Solar/Wind Harmer
1.231
233946AB2-136 GEN
Solar/Wind Harmer
1.813
234036AF2-325 C
Solar/Wind Harmer
0.416
234041AC1-190 GEN
Solar/Wind Harmer
4.062
232910NRG_G1
Adder
3.914
233984AB2-036 GEN
Solar/Wind Harmer
5.464
232424Y1-079 C
Solar/Wind Harmer
0.246
234014AF1-036_GEN
Solar/Wind Harmer
1.172
232436AB1-176 C
Solar/Wind Harmer
0.099
233982AB2-133 GEN
Solar/Wind Harmer
2.079
233930AB2-032 GEN
Solar/Wind Harmer
0.356
217197RE CRAN C
Solar/Wind Harmer
0.202
218438BLK ROCK C
Solar/Wind Harmer
0.051
20641628MLH_W1-032
Solar/Wind Harmer
0.099
20742028HF_AC1-207
Solar/Wind Harmer
0.26
219817TRENTONSOL C
Solar/Wind Harmer
0.338
924131AB2-057 GEN
Solar/Wind Harmer
0.304
20635028RRCT1&2
Adder
3.214
20635128RRCT3&4
Adder
3.102
20635128RRCT3&4
Adder
2.706
232426Y1-080 FULL
Solar/Wind Harmer
0.087
232902EASTMUNI
Adder
5.803
234012AE2-112_GEN
Solar/Wind Harmer
0.996
233944AB2-135 GEN
Solar/Wind Harmer
2.261
233918AB1-142 GEN
Solar/Wind Harmer
0.422
20720428HOL_W1-112
Solar/Wind Harmer
0.122
20720528MAN_W1-024
Solar/Wind Harmer
0.086
20715228NPK_W1-113
Solar/Wind Harmer
0.144
219680HOPEWELLV C1
Solar/Wind Harmer
0.024
20635828PARLN1&2
Adder
2.175
20635028RRCT1&2
Adder
3.264
218524CNTRALGAS1 C
Solar/Wind Harmer
0.093
218440SUMMTASSOC C
Solar/Wind Harmer
0.032
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.094
219919AE1-041 FULL
Solar/Wind Harmer
0.01
213919RICHMD92
50/50
1.23
219124CAMDEN_STG
50/50
1.201
230406ST-CC
50/50
4.801
230404GT1-CC
50/50
3.243
213400COVANTA DELA
50/50
0.988
219221BRL12CT1
50/50
10.238
219223BRL12CT3
50/50
10.238
219924AG1-130 C
50/50
0.479
213542CROYDN42
50/50
0.615
213621FORDBST1
50/50
2.939
213616FORDACT1
50/50
2.109
219914AD2-027 C
Solar/Wind Harmer
0.954
219921AF1-264
Solar/Wind Harmer
0.211
219623KINSLEYBEA C
Solar/Wind Harmer
0.61
219236SOUTHERNHQ C
Solar/Wind Harmer
0.095
219688LUMSOLAR_S C
Solar/Wind Harmer
0.213
218660EHAMPSOLAR C
Solar/Wind Harmer
0.18
219291REEVESSOUT C
Solar/Wind Harmer
0.062
230415AB2-049 C
Solar/Wind Harmer
0.187
959561AF2-247 GEN
Solar/Wind Harmer
0.428
228711V2-041C
Solar/Wind Harmer
0.516
219114HARTZY_C
Solar/Wind Harmer
0.589
20716428NHV_W2-082
Solar/Wind Harmer
1.178
219727YARDVSOLFA C
Solar/Wind Harmer
0.596
20715728PEM_W1-119
Solar/Wind Harmer
0.342
20714928UPF_X1-085
Solar/Wind Harmer
0.228
20636028O CRK C1
Adder
3.875
963391AG1-188 GEN
Solar/Wind Harmer
2.02
971667AH1-334 GEN
Solar/Wind Harmer
1.441
233973AC2-185 C
Solar/Wind Harmer
2.581
970695AG2-447 GEN
Solar/Wind Harmer
1.707
233939AC1-091 C
Solar/Wind Harmer
1.278
233972AC1-094 C
Solar/Wind Harmer
1.026
232434Z2-077 GEN
Solar/Wind Harmer
0.115
233950AC2-186 GEN
Solar/Wind Harmer
0.259
232914OH NUG3
Adder
4.062
232916OH NUG5
Adder
4.062
232921TASLEY2G
Adder
2.374
232406W1-004 FULL
Solar/Wind Harmer
0.46
233923SMA
Solar/Wind Harmer
1.679
233997TMININ_4.2
Solar/Wind Harmer
0.458
232907VN8
Adder
13.709
233964AF2-378 GEN
Solar/Wind Harmer
0.058
232417X3-008 C
Solar/Wind Harmer
0.51
233987AB2-037 GEN
Solar/Wind Harmer
5.123
232422X3-066 FULL
Solar/Wind Harmer
0.108
233933AB2-153 GEN
Solar/Wind Harmer
0.48
207454AA2-184 E
Solar/Wind Harmer
0.387
233935AB2-179 C
Solar/Wind Harmer
0.985
219612MATRIX C
Solar/Wind Harmer
0.069
20716928W4-060COL
Solar/Wind Harmer
0.23
219918AC2-009 C
Solar/Wind Harmer
0.008
20635828PARLN1&2
Adder
0.985
20635928PARLN3&4
Adder
0.985
217213AMBOY SO C
Solar/Wind Harmer
0.031
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.585
VTFLTFEXP_VFT->PJM
CMTX
25.661
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.356
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.574
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.785
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.659
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
14.195
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.549
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for RICHMOND35-WANEETA3 230.0 kV Ckt 1 line l/o PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1209.3
MW Contribution:
1.71
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.96 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1273.88
MW Contribution:
1.73
Bus #Bus NameTypeMW Contribution
219229EAGLE PT ST
50/50
0.74
219231EAGLE PT CT2
50/50
1.461
230405GT2-CC
50/50
3.254
219224BRL12CT4
50/50
10.238
213536CROYDN12
50/50
1.292
213537CROYDN21
50/50
0.615
213538CROYDN22
50/50
0.615
213539CROYDN31
50/50
0.615
213540CROYDN32
50/50
0.603
219258KINSLEYDEP C
Solar/Wind Harmer
0.466
219137THOSOLAR C
Solar/Wind Harmer
1.626
219615MILLCREEK C
Solar/Wind Harmer
0.291
219610FLORENCE C
Solar/Wind Harmer
1.497
230434AG1-499 GEN
Solar/Wind Harmer
0.618
964001AG1-254 GEN
Solar/Wind Harmer
7.522
972141AH1-641 GEN
Solar/Wind Harmer
2.87
230430AE1-229_GEN
Solar/Wind Harmer
28.495
230407AD2-065 C
Solar/Wind Harmer
0.129
228728W1-130C
Solar/Wind Harmer
0.631
970453AG2-297 GEN
Solar/Wind Harmer
2.306
230422AE1-104_GEN1
Solar/Wind Harmer
28.004
230425AE1-104_GEN2
Solar/Wind Harmer
28.004
227927V4-067C
Solar/Wind Harmer
0.161
213611FALLS1-3
Adder
2.497
213611FALLS1-3
Adder
2.497
20720728JCB_W1-129
Solar/Wind Harmer
0.199
20715028HAN_X4-015
Solar/Wind Harmer
0.198
971189AH1-054 GEN
Solar/Wind Harmer
0.666
207487AE2-000G4
Solar/Wind Harmer
17.268
207497AE2-000G2
Solar/Wind Harmer
17.268
207500AE2-000G1
Solar/Wind Harmer
17.268
207507AE2-000G3
Solar/Wind Harmer
17.268
963401AG1-189 GEN
Solar/Wind Harmer
1.233
970025AG2-016 GEN
Solar/Wind Harmer
1.529
207445AB1-138_GEN
Solar/Wind Harmer
0.299
231919CHRIST1
Adder
2.298
231920CHRIST2
Adder
2.247
232904IR4
Adder
37.423
232920IR10
Adder
1.462
232432Z2-076 GEN
Solar/Wind Harmer
0.061
233901CHERRYDALE C
Solar/Wind Harmer
0.517
232912OH NUG1
Adder
4.062
232913OH NUG2
Adder
4.008
971195AH1-057 GEN
Solar/Wind Harmer
0.448
233940AF2-379 C
Solar/Wind Harmer
0.086
232813VAUGHN
Adder
0.269
233955AB2-172 GEN
Solar/Wind Harmer
2.266
231906DC3 NUG
Adder
6.26
231902DC CT7
Adder
5.004
231907DC10
Adder
1.563
233968AD2-076_GEN
Solar/Wind Harmer
2.871
970597AG2-380 GEN
Solar/Wind Harmer
1.803
233915AB1-141 GEN
Solar/Wind Harmer
0.422
20714428HOW_X1-037
Solar/Wind Harmer
0.482
20720628TIN_W1-124
Solar/Wind Harmer
0.386
971521AH1-258 GEN
Solar/Wind Harmer
0.973
20716228APLW2-078
Solar/Wind Harmer
0.296
213918RICHMD91
50/50
1.23
219267WHEELBRDEPTF
50/50
0.204
219230EAGLE PT CT1
50/50
1.462
219235Y2-105
50/50
0.528
228400MICK 1CT
50/50
14.896
219222BRL12CT2
50/50
10.238
213541CROYDN41
50/50
0.615
213618FORDAST1
50/50
2.931
213617FORDACT2
50/50
2.109
971525AH1-260 GEN
50/50
62.282
219766PARADISE C
Solar/Wind Harmer
0.477
219907AC1-030 C
Solar/Wind Harmer
0.197
219348LDSOLAR C
Solar/Wind Harmer
0.647
219686LUMSOLAR_N C
Solar/Wind Harmer
0.205
970997AG2-616 GEN
Solar/Wind Harmer
9.567
228260V4-054C
Solar/Wind Harmer
0.967
228206SHRMN CT
Adder
14.391
228732V1-021 C
Adder
0.158
228729W2-030 C
Solar/Wind Harmer
0.474
213611FALLS1-3
Adder
2.497
20716028EGP_W2-019
Solar/Wind Harmer
0.31
207522AF2-254 C
Solar/Wind Harmer
0.945
20717128DIX_Z2-102
Solar/Wind Harmer
0.859
20715828PEM_W1-120
Solar/Wind Harmer
0.342
972251AH1-710 GEN
Adder
26.009
219276PARKLANDSO C
Solar/Wind Harmer
0.249
231917EM10
Adder
1.278
231918WEST 1
Adder
1.709
963711AG1-223 GEN
Solar/Wind Harmer
0.68
20714528FRN_Y2-051
Solar/Wind Harmer
0.134
233970AC1-092 C
Solar/Wind Harmer
1.278
232901NORTHST
Adder
3.938
232900DEMECSMY
Adder
4.342
972177AH1-672 GEN
Solar/Wind Harmer
6.234
234033AF1-007_GEN
Solar/Wind Harmer
17.216
232917OH NUG6
Adder
4.044
232915OH NUG4
Adder
4.035
232404W1-003 C
Solar/Wind Harmer
0.46
232408W1-005 C
Solar/Wind Harmer
0.46
233996TM1833_GEN
Solar/Wind Harmer
0.458
233998TM1NIN_3.36
Solar/Wind Harmer
0.458
232919VN10
Adder
1.281
232426Y1-080 FULL
Solar/Wind Harmer
0.087
232902EASTMUNI
Adder
5.803
234012AE2-112_GEN
Solar/Wind Harmer
0.996
233944AB2-135 GEN
Solar/Wind Harmer
2.261
233918AB1-142 GEN
Solar/Wind Harmer
0.422
219620RIDERU C
Solar/Wind Harmer
0.017
20635928PARLN3&4
Adder
2.175
218526CNTRALGAS2 C
Solar/Wind Harmer
0.099
20720428HOL_W1-112
Solar/Wind Harmer
0.122
20720528MAN_W1-024
Solar/Wind Harmer
0.086
20715228NPK_W1-113
Solar/Wind Harmer
0.144
219680HOPEWELLV C1
Solar/Wind Harmer
0.024
20635828PARLN1&2
Adder
2.175
20635028RRCT1&2
Adder
3.264
218524CNTRALGAS1 C
Solar/Wind Harmer
0.093
218440SUMMTASSOC C
Solar/Wind Harmer
0.032
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.094
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219126CAMDEN_CTG
50/50
1.475
219286CAMD CO RR
50/50
0.44
972233AH1-701 GEN
50/50
5.235
228307PCLP GT
50/50
14.42
213535CROYDN11
50/50
11.248
228201CARL#2CT
50/50
6.885
228200CARL#1CT
50/50
6.548
228251CARLLS#4
50/50
0.631
213619FORDBCT1
50/50
2.118
213620FORDBCT2
50/50
2.118
219912AD2-042 GEN
Solar/Wind Harmer
1.264
219904AC1-010 C
Solar/Wind Harmer
0.573
219906AC1-017 C
Solar/Wind Harmer
0.272
219272CLEANLIGHT C
Solar/Wind Harmer
0.201
219607WPEMNERT C
Solar/Wind Harmer
0.453
219304NAMERICA C
Solar/Wind Harmer
0.335
228351V2-046C
Solar/Wind Harmer
2.08
219287REEVESEAST C
Solar/Wind Harmer
1.363
230511AF1-262
Solar/Wind Harmer
0.181
230433AD2-135 GEN
Solar/Wind Harmer
0.096
228754AB1-001 C
Solar/Wind Harmer
0.115
214067T20SOLAR
Solar/Wind Harmer
0.178
20720828JCB_W4-025
Solar/Wind Harmer
0.302
20636128O CRK C2
Adder
3.533
207459AE1-142 C O1
Solar/Wind Harmer
0.543
20628028LAKEHURS
Adder
0.49
20714828MDF_W3-079
Solar/Wind Harmer
0.14
233971AC1-093 C
Solar/Wind Harmer
1.213
231940T-011
Adder
0.344
233952AC2-187 GEN
Solar/Wind Harmer
0.518
233954AC2-188 GEN
Solar/Wind Harmer
0.518
232918OH NUG7
Adder
4.035
232905CHERITON_25
Adder
1.128
232410W1-006 C
Solar/Wind Harmer
0.46
234015AF2-250 C
Solar/Wind Harmer
0.055
232926CRISFLD1
Adder
0.902
232428Y3-058 C
Solar/Wind Harmer
0.382
233994AC2-023 GEN
Solar/Wind Harmer
1.231
233946AB2-136 GEN
Solar/Wind Harmer
1.813
234036AF2-325 C
Solar/Wind Harmer
0.416
234041AC1-190 GEN
Solar/Wind Harmer
4.062
232910NRG_G1
Adder
3.914
233984AB2-036 GEN
Solar/Wind Harmer
5.464
232424Y1-079 C
Solar/Wind Harmer
0.246
234014AF1-036_GEN
Solar/Wind Harmer
1.172
232436AB1-176 C
Solar/Wind Harmer
0.099
233982AB2-133 GEN
Solar/Wind Harmer
2.079
233930AB2-032 GEN
Solar/Wind Harmer
0.356
217197RE CRAN C
Solar/Wind Harmer
0.202
218438BLK ROCK C
Solar/Wind Harmer
0.051
20641628MLH_W1-032
Solar/Wind Harmer
0.099
20742028HF_AC1-207
Solar/Wind Harmer
0.26
219817TRENTONSOL C
Solar/Wind Harmer
0.338
924131AB2-057 GEN
Solar/Wind Harmer
0.304
20635028RRCT1&2
Adder
3.214
20635128RRCT3&4
Adder
3.102
20635128RRCT3&4
Adder
2.706
213919RICHMD92
50/50
1.23
219124CAMDEN_STG
50/50
1.201
230406ST-CC
50/50
4.801
230404GT1-CC
50/50
3.243
213400COVANTA DELA
50/50
0.988
219221BRL12CT1
50/50
10.238
219223BRL12CT3
50/50
10.238
219924AG1-130 C
50/50
0.479
213542CROYDN42
50/50
0.615
213621FORDBST1
50/50
2.939
213616FORDACT1
50/50
2.109
219914AD2-027 C
Solar/Wind Harmer
0.954
219921AF1-264
Solar/Wind Harmer
0.211
219623KINSLEYBEA C
Solar/Wind Harmer
0.61
219236SOUTHERNHQ C
Solar/Wind Harmer
0.095
219688LUMSOLAR_S C
Solar/Wind Harmer
0.213
218660EHAMPSOLAR C
Solar/Wind Harmer
0.18
219291REEVESSOUT C
Solar/Wind Harmer
0.062
230415AB2-049 C
Solar/Wind Harmer
0.187
959561AF2-247 GEN
Solar/Wind Harmer
0.428
228711V2-041C
Solar/Wind Harmer
0.516
219114HARTZY_C
Solar/Wind Harmer
0.589
20716428NHV_W2-082
Solar/Wind Harmer
1.178
219727YARDVSOLFA C
Solar/Wind Harmer
0.596
20715728PEM_W1-119
Solar/Wind Harmer
0.342
20714928UPF_X1-085
Solar/Wind Harmer
0.228
20636028O CRK C1
Adder
3.875
963391AG1-188 GEN
Solar/Wind Harmer
2.02
971667AH1-334 GEN
Solar/Wind Harmer
1.441
233973AC2-185 C
Solar/Wind Harmer
2.581
970695AG2-447 GEN
Solar/Wind Harmer
1.707
233939AC1-091 C
Solar/Wind Harmer
1.278
233972AC1-094 C
Solar/Wind Harmer
1.026
232434Z2-077 GEN
Solar/Wind Harmer
0.115
233950AC2-186 GEN
Solar/Wind Harmer
0.259
232914OH NUG3
Adder
4.062
232916OH NUG5
Adder
4.062
232921TASLEY2G
Adder
2.374
232406W1-004 FULL
Solar/Wind Harmer
0.46
233923SMA
Solar/Wind Harmer
1.679
233997TMININ_4.2
Solar/Wind Harmer
0.458
232907VN8
Adder
13.709
233964AF2-378 GEN
Solar/Wind Harmer
0.058
232417X3-008 C
Solar/Wind Harmer
0.51
233987AB2-037 GEN
Solar/Wind Harmer
5.123
232422X3-066 FULL
Solar/Wind Harmer
0.108
233933AB2-153 GEN
Solar/Wind Harmer
0.48
207454AA2-184 E
Solar/Wind Harmer
0.387
233935AB2-179 C
Solar/Wind Harmer
0.985
219612MATRIX C
Solar/Wind Harmer
0.069
20716928W4-060COL
Solar/Wind Harmer
0.23
219918AC2-009 C
Solar/Wind Harmer
0.008
20635828PARLN1&2
Adder
0.985
20635928PARLN3&4
Adder
0.985
217213AMBOY SO C
Solar/Wind Harmer
0.031
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.585
VTFLTFEXP_VFT->PJM
CMTX
25.661
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.356
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.574
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.659
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.785
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
14.195
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.549
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for RICHMOND35-WANEETA3 230.0 kV Ckt 1 line l/o PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1209.29
MW Contribution:
1.71
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.95 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1273.77
MW Contribution:
1.73
Bus #Bus NameTypeMW Contribution
219229EAGLE PT ST
50/50
0.74
219231EAGLE PT CT2
50/50
1.461
230405GT2-CC
50/50
3.254
219224BRL12CT4
50/50
10.238
213536CROYDN12
50/50
1.292
213537CROYDN21
50/50
0.615
213538CROYDN22
50/50
0.615
213539CROYDN31
50/50
0.615
213540CROYDN32
50/50
0.603
219258KINSLEYDEP C
Solar/Wind Harmer
0.466
219137THOSOLAR C
Solar/Wind Harmer
1.626
219615MILLCREEK C
Solar/Wind Harmer
0.291
219610FLORENCE C
Solar/Wind Harmer
1.497
230434AG1-499 GEN
Solar/Wind Harmer
0.618
964001AG1-254 GEN
Solar/Wind Harmer
7.522
972141AH1-641 GEN
Solar/Wind Harmer
2.87
230430AE1-229_GEN
Solar/Wind Harmer
28.495
230407AD2-065 C
Solar/Wind Harmer
0.129
228728W1-130C
Solar/Wind Harmer
0.631
970453AG2-297 GEN
Solar/Wind Harmer
2.306
230422AE1-104_GEN1
Solar/Wind Harmer
28.004
230425AE1-104_GEN2
Solar/Wind Harmer
28.004
227927V4-067C
Solar/Wind Harmer
0.161
213611FALLS1-3
Adder
2.497
213611FALLS1-3
Adder
2.497
20720728JCB_W1-129
Solar/Wind Harmer
0.199
20715028HAN_X4-015
Solar/Wind Harmer
0.198
971189AH1-054 GEN
Solar/Wind Harmer
0.666
207487AE2-000G4
Solar/Wind Harmer
17.268
207497AE2-000G2
Solar/Wind Harmer
17.268
207500AE2-000G1
Solar/Wind Harmer
17.268
207507AE2-000G3
Solar/Wind Harmer
17.268
963401AG1-189 GEN
Solar/Wind Harmer
1.233
970025AG2-016 GEN
Solar/Wind Harmer
1.529
207445AB1-138_GEN
Solar/Wind Harmer
0.299
231919CHRIST1
Adder
2.298
231920CHRIST2
Adder
2.247
232904IR4
Adder
37.423
232920IR10
Adder
1.462
232432Z2-076 GEN
Solar/Wind Harmer
0.061
233901CHERRYDALE C
Solar/Wind Harmer
0.517
232912OH NUG1
Adder
4.062
232913OH NUG2
Adder
4.008
971195AH1-057 GEN
Solar/Wind Harmer
0.448
233940AF2-379 C
Solar/Wind Harmer
0.086
232813VAUGHN
Adder
0.269
233955AB2-172 GEN
Solar/Wind Harmer
2.266
231906DC3 NUG
Adder
6.26
231902DC CT7
Adder
5.004
231907DC10
Adder
1.563
233968AD2-076_GEN
Solar/Wind Harmer
2.871
970597AG2-380 GEN
Solar/Wind Harmer
1.803
233915AB1-141 GEN
Solar/Wind Harmer
0.422
20714428HOW_X1-037
Solar/Wind Harmer
0.482
20720628TIN_W1-124
Solar/Wind Harmer
0.386
971521AH1-258 GEN
Solar/Wind Harmer
0.973
20716228APLW2-078
Solar/Wind Harmer
0.296
219620RIDERU C
Solar/Wind Harmer
0.017
20635928PARLN3&4
Adder
2.175
218526CNTRALGAS2 C
Solar/Wind Harmer
0.099
219126CAMDEN_CTG
50/50
1.475
219286CAMD CO RR
50/50
0.44
972233AH1-701 GEN
50/50
5.235
228307PCLP GT
50/50
14.42
213535CROYDN11
50/50
11.248
228201CARL#2CT
50/50
6.885
228200CARL#1CT
50/50
6.548
228251CARLLS#4
50/50
0.631
213619FORDBCT1
50/50
2.118
213620FORDBCT2
50/50
2.118
219912AD2-042 GEN
Solar/Wind Harmer
1.264
219904AC1-010 C
Solar/Wind Harmer
0.573
219906AC1-017 C
Solar/Wind Harmer
0.272
219272CLEANLIGHT C
Solar/Wind Harmer
0.201
219607WPEMNERT C
Solar/Wind Harmer
0.453
219304NAMERICA C
Solar/Wind Harmer
0.335
228351V2-046C
Solar/Wind Harmer
2.08
219287REEVESEAST C
Solar/Wind Harmer
1.363
230511AF1-262
Solar/Wind Harmer
0.181
230433AD2-135 GEN
Solar/Wind Harmer
0.096
228754AB1-001 C
Solar/Wind Harmer
0.115
214067T20SOLAR
Solar/Wind Harmer
0.178
20720828JCB_W4-025
Solar/Wind Harmer
0.302
20636128O CRK C2
Adder
3.533
207459AE1-142 C O1
Solar/Wind Harmer
0.543
20628028LAKEHURS
Adder
0.49
20714828MDF_W3-079
Solar/Wind Harmer
0.14
233971AC1-093 C
Solar/Wind Harmer
1.213
231940T-011
Adder
0.344
233952AC2-187 GEN
Solar/Wind Harmer
0.518
233954AC2-188 GEN
Solar/Wind Harmer
0.518
232918OH NUG7
Adder
4.035
232905CHERITON_25
Adder
1.128
232410W1-006 C
Solar/Wind Harmer
0.46
234015AF2-250 C
Solar/Wind Harmer
0.055
232926CRISFLD1
Adder
0.902
232428Y3-058 C
Solar/Wind Harmer
0.382
233994AC2-023 GEN
Solar/Wind Harmer
1.231
233946AB2-136 GEN
Solar/Wind Harmer
1.813
234036AF2-325 C
Solar/Wind Harmer
0.416
234041AC1-190 GEN
Solar/Wind Harmer
4.062
232910NRG_G1
Adder
3.914
233984AB2-036 GEN
Solar/Wind Harmer
5.464
232424Y1-079 C
Solar/Wind Harmer
0.246
234014AF1-036_GEN
Solar/Wind Harmer
1.172
232436AB1-176 C
Solar/Wind Harmer
0.099
233982AB2-133 GEN
Solar/Wind Harmer
2.079
233930AB2-032 GEN
Solar/Wind Harmer
0.356
217197RE CRAN C
Solar/Wind Harmer
0.202
218438BLK ROCK C
Solar/Wind Harmer
0.051
20641628MLH_W1-032
Solar/Wind Harmer
0.099
20742028HF_AC1-207
Solar/Wind Harmer
0.26
219817TRENTONSOL C
Solar/Wind Harmer
0.338
924131AB2-057 GEN
Solar/Wind Harmer
0.304
20635028RRCT1&2
Adder
3.214
20635128RRCT3&4
Adder
3.102
20635128RRCT3&4
Adder
2.706
213918RICHMD91
50/50
1.23
219267WHEELBRDEPTF
50/50
0.204
219230EAGLE PT CT1
50/50
1.462
219235Y2-105
50/50
0.528
228400MICK 1CT
50/50
14.896
219222BRL12CT2
50/50
10.238
213541CROYDN41
50/50
0.615
213618FORDAST1
50/50
2.931
213617FORDACT2
50/50
2.109
971525AH1-260 GEN
50/50
62.282
219766PARADISE C
Solar/Wind Harmer
0.477
219907AC1-030 C
Solar/Wind Harmer
0.197
219348LDSOLAR C
Solar/Wind Harmer
0.647
219686LUMSOLAR_N C
Solar/Wind Harmer
0.205
970997AG2-616 GEN
Solar/Wind Harmer
9.567
228260V4-054C
Solar/Wind Harmer
0.967
228206SHRMN CT
Adder
14.391
228732V1-021 C
Adder
0.158
228729W2-030 C
Solar/Wind Harmer
0.474
213611FALLS1-3
Adder
2.497
20716028EGP_W2-019
Solar/Wind Harmer
0.31
207522AF2-254 C
Solar/Wind Harmer
0.945
20717128DIX_Z2-102
Solar/Wind Harmer
0.859
20715828PEM_W1-120
Solar/Wind Harmer
0.342
972251AH1-710 GEN
Adder
26.009
219276PARKLANDSO C
Solar/Wind Harmer
0.249
231917EM10
Adder
1.278
231918WEST 1
Adder
1.709
963711AG1-223 GEN
Solar/Wind Harmer
0.68
20714528FRN_Y2-051
Solar/Wind Harmer
0.134
233970AC1-092 C
Solar/Wind Harmer
1.278
232901NORTHST
Adder
3.938
232900DEMECSMY
Adder
4.342
972177AH1-672 GEN
Solar/Wind Harmer
6.234
234033AF1-007_GEN
Solar/Wind Harmer
17.216
232917OH NUG6
Adder
4.044
232915OH NUG4
Adder
4.035
232404W1-003 C
Solar/Wind Harmer
0.46
232408W1-005 C
Solar/Wind Harmer
0.46
233996TM1833_GEN
Solar/Wind Harmer
0.458
233998TM1NIN_3.36
Solar/Wind Harmer
0.458
232919VN10
Adder
1.281
232426Y1-080 FULL
Solar/Wind Harmer
0.087
232902EASTMUNI
Adder
5.803
234012AE2-112_GEN
Solar/Wind Harmer
0.996
233944AB2-135 GEN
Solar/Wind Harmer
2.261
233918AB1-142 GEN
Solar/Wind Harmer
0.422
20720428HOL_W1-112
Solar/Wind Harmer
0.122
20720528MAN_W1-024
Solar/Wind Harmer
0.086
20715228NPK_W1-113
Solar/Wind Harmer
0.144
219680HOPEWELLV C1
Solar/Wind Harmer
0.024
20635828PARLN1&2
Adder
2.175
20635028RRCT1&2
Adder
3.264
218524CNTRALGAS1 C
Solar/Wind Harmer
0.093
218440SUMMTASSOC C
Solar/Wind Harmer
0.032
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.094
219919AE1-041 FULL
Solar/Wind Harmer
0.01
213919RICHMD92
50/50
1.23
219124CAMDEN_STG
50/50
1.201
230406ST-CC
50/50
4.801
230404GT1-CC
50/50
3.243
213400COVANTA DELA
50/50
0.988
219221BRL12CT1
50/50
10.238
219223BRL12CT3
50/50
10.238
219924AG1-130 C
50/50
0.479
213542CROYDN42
50/50
0.615
213621FORDBST1
50/50
2.939
213616FORDACT1
50/50
2.109
219914AD2-027 C
Solar/Wind Harmer
0.954
219921AF1-264
Solar/Wind Harmer
0.211
219623KINSLEYBEA C
Solar/Wind Harmer
0.61
219236SOUTHERNHQ C
Solar/Wind Harmer
0.095
219688LUMSOLAR_S C
Solar/Wind Harmer
0.213
218660EHAMPSOLAR C
Solar/Wind Harmer
0.18
219291REEVESSOUT C
Solar/Wind Harmer
0.062
230415AB2-049 C
Solar/Wind Harmer
0.187
959561AF2-247 GEN
Solar/Wind Harmer
0.428
228711V2-041C
Solar/Wind Harmer
0.516
219114HARTZY_C
Solar/Wind Harmer
0.589
20716428NHV_W2-082
Solar/Wind Harmer
1.178
219727YARDVSOLFA C
Solar/Wind Harmer
0.596
20715728PEM_W1-119
Solar/Wind Harmer
0.342
20714928UPF_X1-085
Solar/Wind Harmer
0.228
20636028O CRK C1
Adder
3.875
963391AG1-188 GEN
Solar/Wind Harmer
2.02
971667AH1-334 GEN
Solar/Wind Harmer
1.441
233973AC2-185 C
Solar/Wind Harmer
2.581
970695AG2-447 GEN
Solar/Wind Harmer
1.707
233939AC1-091 C
Solar/Wind Harmer
1.278
233972AC1-094 C
Solar/Wind Harmer
1.026
232434Z2-077 GEN
Solar/Wind Harmer
0.115
233950AC2-186 GEN
Solar/Wind Harmer
0.259
232914OH NUG3
Adder
4.062
232916OH NUG5
Adder
4.062
232921TASLEY2G
Adder
2.374
232406W1-004 FULL
Solar/Wind Harmer
0.46
233923SMA
Solar/Wind Harmer
1.679
233997TMININ_4.2
Solar/Wind Harmer
0.458
232907VN8
Adder
13.709
233964AF2-378 GEN
Solar/Wind Harmer
0.058
232417X3-008 C
Solar/Wind Harmer
0.51
233987AB2-037 GEN
Solar/Wind Harmer
5.123
232422X3-066 FULL
Solar/Wind Harmer
0.108
233933AB2-153 GEN
Solar/Wind Harmer
0.48
207454AA2-184 E
Solar/Wind Harmer
0.387
233935AB2-179 C
Solar/Wind Harmer
0.985
219612MATRIX C
Solar/Wind Harmer
0.069
20716928W4-060COL
Solar/Wind Harmer
0.23
219918AC2-009 C
Solar/Wind Harmer
0.008
20635828PARLN1&2
Adder
0.985
20635928PARLN3&4
Adder
0.985
217213AMBOY SO C
Solar/Wind Harmer
0.031
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.585
VTFLTFEXP_VFT->PJM
CMTX
25.661
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.356
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.574
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.659
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.785
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
14.195
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.549
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for RICHMOND35-WANEETA3 230.0 kV Ckt 1 line l/o PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1209.25
MW Contribution:
1.71
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.94 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1273.72
MW Contribution:
1.73
Bus #Bus NameTypeMW Contribution
219229EAGLE PT ST
50/50
0.74
219231EAGLE PT CT2
50/50
1.461
230405GT2-CC
50/50
3.254
219224BRL12CT4
50/50
10.238
213536CROYDN12
50/50
1.292
213537CROYDN21
50/50
0.615
213538CROYDN22
50/50
0.615
213539CROYDN31
50/50
0.615
213540CROYDN32
50/50
0.603
219258KINSLEYDEP C
Solar/Wind Harmer
0.466
219137THOSOLAR C
Solar/Wind Harmer
1.626
219615MILLCREEK C
Solar/Wind Harmer
0.291
219610FLORENCE C
Solar/Wind Harmer
1.497
230434AG1-499 GEN
Solar/Wind Harmer
0.618
964001AG1-254 GEN
Solar/Wind Harmer
7.522
972141AH1-641 GEN
Solar/Wind Harmer
2.87
230430AE1-229_GEN
Solar/Wind Harmer
28.496
230407AD2-065 C
Solar/Wind Harmer
0.129
228728W1-130C
Solar/Wind Harmer
0.631
970453AG2-297 GEN
Solar/Wind Harmer
2.306
230422AE1-104_GEN1
Solar/Wind Harmer
28.005
230425AE1-104_GEN2
Solar/Wind Harmer
28.005
227927V4-067C
Solar/Wind Harmer
0.161
213611FALLS1-3
Adder
2.497
213611FALLS1-3
Adder
2.497
20720728JCB_W1-129
Solar/Wind Harmer
0.199
20715028HAN_X4-015
Solar/Wind Harmer
0.198
971189AH1-054 GEN
Solar/Wind Harmer
0.666
207487AE2-000G4
Solar/Wind Harmer
17.268
207497AE2-000G2
Solar/Wind Harmer
17.268
207500AE2-000G1
Solar/Wind Harmer
17.268
207507AE2-000G3
Solar/Wind Harmer
17.268
963401AG1-189 GEN
Solar/Wind Harmer
1.233
970025AG2-016 GEN
Solar/Wind Harmer
1.529
207445AB1-138_GEN
Solar/Wind Harmer
0.299
231919CHRIST1
Adder
2.297
231920CHRIST2
Adder
2.246
232904IR4
Adder
37.42
232920IR10
Adder
1.462
232432Z2-076 GEN
Solar/Wind Harmer
0.061
233901CHERRYDALE C
Solar/Wind Harmer
0.517
232912OH NUG1
Adder
4.062
232913OH NUG2
Adder
4.008
971195AH1-057 GEN
Solar/Wind Harmer
0.448
233940AF2-379 C
Solar/Wind Harmer
0.086
232813VAUGHN
Adder
0.268
233955AB2-172 GEN
Solar/Wind Harmer
2.265
231906DC3 NUG
Adder
6.259
231902DC CT7
Adder
5.004
231907DC10
Adder
1.563
233968AD2-076_GEN
Solar/Wind Harmer
2.871
970597AG2-380 GEN
Solar/Wind Harmer
1.803
233915AB1-141 GEN
Solar/Wind Harmer
0.422
20714428HOW_X1-037
Solar/Wind Harmer
0.482
20720628TIN_W1-124
Solar/Wind Harmer
0.386
971521AH1-258 GEN
Solar/Wind Harmer
0.973
20716228APLW2-078
Solar/Wind Harmer
0.296
219620RIDERU C
Solar/Wind Harmer
0.017
20635928PARLN3&4
Adder
2.175
218526CNTRALGAS2 C
Solar/Wind Harmer
0.099
219126CAMDEN_CTG
50/50
1.475
219286CAMD CO RR
50/50
0.44
972233AH1-701 GEN
50/50
5.235
228307PCLP GT
50/50
14.421
213535CROYDN11
50/50
11.248
228201CARL#2CT
50/50
6.885
228200CARL#1CT
50/50
6.548
228251CARLLS#4
50/50
0.631
213619FORDBCT1
50/50
2.118
213620FORDBCT2
50/50
2.118
219912AD2-042 GEN
Solar/Wind Harmer
1.264
219904AC1-010 C
Solar/Wind Harmer
0.573
219906AC1-017 C
Solar/Wind Harmer
0.272
219272CLEANLIGHT C
Solar/Wind Harmer
0.201
219607WPEMNERT C
Solar/Wind Harmer
0.453
219304NAMERICA C
Solar/Wind Harmer
0.335
228351V2-046C
Solar/Wind Harmer
2.08
219287REEVESEAST C
Solar/Wind Harmer
1.363
230511AF1-262
Solar/Wind Harmer
0.181
230433AD2-135 GEN
Solar/Wind Harmer
0.096
228754AB1-001 C
Solar/Wind Harmer
0.115
214067T20SOLAR
Solar/Wind Harmer
0.178
20720828JCB_W4-025
Solar/Wind Harmer
0.302
20636128O CRK C2
Adder
3.533
207459AE1-142 C O1
Solar/Wind Harmer
0.543
20628028LAKEHURS
Adder
0.49
20714828MDF_W3-079
Solar/Wind Harmer
0.14
233971AC1-093 C
Solar/Wind Harmer
1.213
231940T-011
Adder
0.344
233952AC2-187 GEN
Solar/Wind Harmer
0.518
233954AC2-188 GEN
Solar/Wind Harmer
0.518
232410W1-006 C
Solar/Wind Harmer
0.46
232918OH NUG7
Adder
4.035
232905CHERITON_25
Adder
1.128
234015AF2-250 C
Solar/Wind Harmer
0.055
232926CRISFLD1
Adder
0.902
232428Y3-058 C
Solar/Wind Harmer
0.382
233994AC2-023 GEN
Solar/Wind Harmer
1.23
233946AB2-136 GEN
Solar/Wind Harmer
1.813
234036AF2-325 C
Solar/Wind Harmer
0.416
234041AC1-190 GEN
Solar/Wind Harmer
4.061
232910NRG_G1
Adder
3.913
233984AB2-036 GEN
Solar/Wind Harmer
5.463
232424Y1-079 C
Solar/Wind Harmer
0.246
234014AF1-036_GEN
Solar/Wind Harmer
1.172
232436AB1-176 C
Solar/Wind Harmer
0.099
233982AB2-133 GEN
Solar/Wind Harmer
2.079
233930AB2-032 GEN
Solar/Wind Harmer
0.355
217197RE CRAN C
Solar/Wind Harmer
0.202
218438BLK ROCK C
Solar/Wind Harmer
0.051
20641628MLH_W1-032
Solar/Wind Harmer
0.099
20742028HF_AC1-207
Solar/Wind Harmer
0.26
219817TRENTONSOL C
Solar/Wind Harmer
0.338
924131AB2-057 GEN
Solar/Wind Harmer
0.304
20635028RRCT1&2
Adder
3.214
20635128RRCT3&4
Adder
3.102
20635128RRCT3&4
Adder
2.706
213918RICHMD91
50/50
1.23
219267WHEELBRDEPTF
50/50
0.204
219230EAGLE PT CT1
50/50
1.462
219235Y2-105
50/50
0.528
228400MICK 1CT
50/50
14.897
219222BRL12CT2
50/50
10.238
213541CROYDN41
50/50
0.615
213618FORDAST1
50/50
2.931
213617FORDACT2
50/50
2.109
971525AH1-260 GEN
50/50
62.283
219766PARADISE C
Solar/Wind Harmer
0.477
219907AC1-030 C
Solar/Wind Harmer
0.197
219348LDSOLAR C
Solar/Wind Harmer
0.647
219686LUMSOLAR_N C
Solar/Wind Harmer
0.205
970997AG2-616 GEN
Solar/Wind Harmer
9.567
228260V4-054C
Solar/Wind Harmer
0.967
228206SHRMN CT
Adder
14.391
228732V1-021 C
Adder
0.158
228729W2-030 C
Solar/Wind Harmer
0.474
213611FALLS1-3
Adder
2.497
20716028EGP_W2-019
Solar/Wind Harmer
0.31
207522AF2-254 C
Solar/Wind Harmer
0.945
20717128DIX_Z2-102
Solar/Wind Harmer
0.859
20715828PEM_W1-120
Solar/Wind Harmer
0.342
972251AH1-710 GEN
Adder
26.008
219276PARKLANDSO C
Solar/Wind Harmer
0.249
231917EM10
Adder
1.278
231918WEST 1
Adder
1.709
963711AG1-223 GEN
Solar/Wind Harmer
0.68
20714528FRN_Y2-051
Solar/Wind Harmer
0.134
233970AC1-092 C
Solar/Wind Harmer
1.277
232901NORTHST
Adder
3.938
232900DEMECSMY
Adder
4.341
972177AH1-672 GEN
Solar/Wind Harmer
6.234
234033AF1-007_GEN
Solar/Wind Harmer
17.214
232404W1-003 C
Solar/Wind Harmer
0.46
232408W1-005 C
Solar/Wind Harmer
0.46
232917OH NUG6
Adder
4.044
232915OH NUG4
Adder
4.035
233996TM1833_GEN
Solar/Wind Harmer
0.458
233998TM1NIN_3.36
Solar/Wind Harmer
0.458
232919VN10
Adder
1.281
232426Y1-080 FULL
Solar/Wind Harmer
0.087
232902EASTMUNI
Adder
5.802
234012AE2-112_GEN
Solar/Wind Harmer
0.996
233944AB2-135 GEN
Solar/Wind Harmer
2.261
233918AB1-142 GEN
Solar/Wind Harmer
0.422
20720428HOL_W1-112
Solar/Wind Harmer
0.122
20720528MAN_W1-024
Solar/Wind Harmer
0.086
20715228NPK_W1-113
Solar/Wind Harmer
0.144
219680HOPEWELLV C1
Solar/Wind Harmer
0.024
20635828PARLN1&2
Adder
2.175
20635028RRCT1&2
Adder
3.264
218524CNTRALGAS1 C
Solar/Wind Harmer
0.093
218440SUMMTASSOC C
Solar/Wind Harmer
0.032
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.094
219919AE1-041 FULL
Solar/Wind Harmer
0.01
213919RICHMD92
50/50
1.23
219124CAMDEN_STG
50/50
1.201
230406ST-CC
50/50
4.801
230404GT1-CC
50/50
3.243
213400COVANTA DELA
50/50
0.988
219221BRL12CT1
50/50
10.238
219223BRL12CT3
50/50
10.238
219924AG1-130 C
50/50
0.479
213542CROYDN42
50/50
0.615
213621FORDBST1
50/50
2.939
213616FORDACT1
50/50
2.109
219914AD2-027 C
Solar/Wind Harmer
0.954
219921AF1-264
Solar/Wind Harmer
0.211
219623KINSLEYBEA C
Solar/Wind Harmer
0.61
219236SOUTHERNHQ C
Solar/Wind Harmer
0.095
219688LUMSOLAR_S C
Solar/Wind Harmer
0.213
218660EHAMPSOLAR C
Solar/Wind Harmer
0.18
219291REEVESSOUT C
Solar/Wind Harmer
0.062
230415AB2-049 C
Solar/Wind Harmer
0.187
959561AF2-247 GEN
Solar/Wind Harmer
0.428
228711V2-041C
Solar/Wind Harmer
0.516
219114HARTZY_C
Solar/Wind Harmer
0.589
20716428NHV_W2-082
Solar/Wind Harmer
1.178
219727YARDVSOLFA C
Solar/Wind Harmer
0.596
20715728PEM_W1-119
Solar/Wind Harmer
0.342
20714928UPF_X1-085
Solar/Wind Harmer
0.228
20636028O CRK C1
Adder
3.875
963391AG1-188 GEN
Solar/Wind Harmer
2.02
971667AH1-334 GEN
Solar/Wind Harmer
1.441
233973AC2-185 C
Solar/Wind Harmer
2.581
970695AG2-447 GEN
Solar/Wind Harmer
1.707
233939AC1-091 C
Solar/Wind Harmer
1.277
233972AC1-094 C
Solar/Wind Harmer
1.026
232434Z2-077 GEN
Solar/Wind Harmer
0.115
233950AC2-186 GEN
Solar/Wind Harmer
0.259
232406W1-004 FULL
Solar/Wind Harmer
0.46
232914OH NUG3
Adder
4.062
232916OH NUG5
Adder
4.062
232921TASLEY2G
Adder
2.374
233923SMA
Solar/Wind Harmer
1.679
233997TMININ_4.2
Solar/Wind Harmer
0.458
232907VN8
Adder
13.708
233964AF2-378 GEN
Solar/Wind Harmer
0.058
232417X3-008 C
Solar/Wind Harmer
0.51
233987AB2-037 GEN
Solar/Wind Harmer
5.123
232422X3-066 FULL
Solar/Wind Harmer
0.108
233933AB2-153 GEN
Solar/Wind Harmer
0.48
207454AA2-184 E
Solar/Wind Harmer
0.388
233935AB2-179 C
Solar/Wind Harmer
0.985
219612MATRIX C
Solar/Wind Harmer
0.069
20716928W4-060COL
Solar/Wind Harmer
0.23
219918AC2-009 C
Solar/Wind Harmer
0.008
20635828PARLN1&2
Adder
0.985
20635928PARLN3&4
Adder
0.985
217213AMBOY SO C
Solar/Wind Harmer
0.031
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.585
VTFLTFEXP_VFT->PJM
CMTX
25.662
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.356
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.574
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.786
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.659
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
14.195
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.55
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CONTINGENCY 'DPL_P4_2_DP51_SRT-A'
 DISCONNECT BRANCH FROM BUS 232114 TO BUS 232118 CKT 1   /*SHARNGTN     138.0 - NSEAFORD     138.0
 DISCONNECT BRANCH FROM BUS 232114 TO BUS 232137 CKT 1   /*SHARNGTN     138.0 - FARMVIEW     138.0
END
CONTINGENCY 'PECO_P1-2_220-85_SRT-A
 DISCONNECT BUS 214236   /*LINWOOD85    230.0
END
CONTINGENCY 'PECO_P4_CHICH045_SRT-A
 DISCONNECT BUS 213489   /*CHICHST1     230.0
 DISCONNECT BUS 213627   /*FOULK8       230.0
END
CONTINGENCY 'PECO_P2-2_CHI230B1_SRT-A
 DISCONNECT BUS 213489   /*CHICHST1     230.0
END
CONTINGENCY 'PECO_P4_CHICH195_SRT-A
 DISCONNECT BUS 213489   /*CHICHST1     230.0
 DISCONNECT BUS 214203   /*CHICHST1     138.0
 DISCONNECT BUS 214340   /*CHI9AB HS LD 230.0
END
CONTINGENCY 'PECO_P4_CHICH435_SRT-A
 DISCONNECT BUS 213489   /*CHICHST1     230.0
 DISCONNECT BUS 213750   /*LINWOOD43    230.0
 DISCONNECT BUS 214221   /*CHIREACT_43  230.0
END
CONTINGENCY 'DPL_P4_2_DPEM231_SRT-A'
 DISCONNECT BRANCH FROM BUS 231000 TO BUS 231001 CKT 1   /*CLAY_230     230.0 - EDGEMR 5     230.0
 DISCONNECT BRANCH FROM BUS 231001 TO BUS 231109 CKT 1   /*EDGEMR 5     230.0 - EDGEMR 4     138.0
END
CONTINGENCY 'PECO_P1-2_220-84_SRT-A
 DISCONNECT BUS 214235   /*LINWOOD84    230.0
END
CONTINGENCY 'PECO_P4_LINWO115_SRT-A
 DISCONNECT BUS 214216   /*POST97       230.0
 DISCONNECT BUS 214234   /*LINWOOD97    230.0
 DISCONNECT BUS 214235   /*LINWOOD84    230.0
END
CONTINGENCY 'DPL_P1_2_CKT 23015_SRT-A'
 OPEN LINE FROM BUS 231000 TO BUS 231001 CIRCUIT 1   /*CLAY_230     230.0 - EDGEMR 5     230.0
END
232245 to 232825 ckt 1
231000 to 214235 ckt 1
213559 to 228401 ckt 1
231001 to 231000 ckt 1
231001 to 214236 ckt 1
214277 to 214012 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC105.04 %4150.0B4359.2
4.68
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC105.01 %4150.0B4357.8
4.68
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC104.99 %4150.0B4357.18
4.68
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC104.65 %4150.0B4342.89
4.7
GD2PECO
CHIREACT_39-CHICHST2 230.0 kV Ckt 1 line
PECO_CBO_CHIC435_SRT-A/* $ DELCO $ PECO_CBO_CHIC435 $ K
BusAC101.34 %1622.0B1643.73
2.17
GD2PECO
CHIREACT_43-CHICHST1 230.0 kV Ckt 1 line
PECO_P4_POST475_SRT-A/* $ DELCO $ PECO_P4_POST475 $ STBK
BreakerAC101.18 %1770.0B1790.82
2.18
GD2PECO
CHIREACT_43-CHICHST1 230.0 kV Ckt 1 line
PECO_P4_POST785_SRT-A/* $ DELCO $ PECO_P4_POST785 $ STBK
BreakerAC101.17 %1770.0B1790.79
2.18
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019E_SRT-SL
BreakerAC127.16 %3098.0B3939.34
3.49
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P1-2_PE-500-3835T_SRT-A
SingleAC116.99 %3098.0B3624.44
2.43
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC111.62 %3098.0B3458.01
2.84
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK
BreakerAC103.85 %3098.0B3217.41
3.31
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
BG_P7_CNSTN_NWEST2_SRT-A
TowerAC102.61 %3098.0B3178.71
2.63
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
BreakerAC101.69 %3098.0B3150.34
3.3
GD2BGE/PECO
COOPER-GRACETON 230.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC109.26 %578.0B631.55
1.24
GD2BGE/PECO
COOPER-GRACETON 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC109.24 %578.0B631.4
1.24
GD2BGE/PECO
COOPER-GRACETON 230.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC109.22 %578.0B631.31
1.24
GD2BGE/PECO
COOPER-GRACETON 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC108.49 %578.0B627.1
1.22
GD2BGE/PECO
COOPER-GRACETON 230.0 kV Ckt 1 line
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
BreakerAC102.86 %578.0B594.52
1.25
GD2DP&L/PECO
EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line
DPL_P4_2_DPEM237_SRT-A
BreakerAC103.9 %809.0B840.56
1.88
GD2PECO
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line
PECO_P4_POST475_SRT-A/* $ DELCO $ PECO_P4_POST475 $ STBK
BreakerAC101.18 %1770.0B1790.82
2.18
GD2PECO
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line
PECO_P4_POST785_SRT-A/* $ DELCO $ PECO_P4_POST785 $ STBK
BreakerAC101.17 %1770.0B1790.79
2.18
GD2PECO
LINWOOD97-POST97 230.0 kV Ckt 1 line
PECO_CBO_CHIC435_SRT-A/* $ DELCO $ PECO_CBO_CHIC435 $ K
BusAC101.44 %1770.0B1795.44
2.17
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC117.62 %578.0B679.82
1.24
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC117.49 %578.0B679.08
1.24
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC117.45 %578.0B678.84
1.24
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC116.79 %578.0B675.02
1.22
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
BreakerAC111.0 %578.0B641.56
1.25
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC104.49 %578.0B603.92
0.86
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC117.62 %578.0B679.82
1.24
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC117.49 %578.0B679.08
1.24
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC117.45 %578.0B678.84
1.24
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC116.79 %578.0B675.02
1.22
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
BreakerAC111.0 %578.0B641.56
1.25
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC104.49 %578.0B603.92
0.86
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC133.22 %3486.0B4644.1
6.76
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC133.22 %3486.0B4644.06
6.76
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC133.16 %3486.0B4641.99
6.76
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC133.05 %3486.0B4638.14
6.78
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC120.33 %3486.0B4194.82
4.72
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
BreakerAC111.17 %3486.0B3875.5
6.84
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019E_SRT-SL
BreakerAC150.91 %3620.0B5462.93
6.24
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC145.49 %3620.0B5266.8
5.89
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK
BreakerAC140.01 %3620.0B5068.35
6.69
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
AP_P1-2_PE-500-3835T_SRT-A
SingleAC136.68 %3620.0B4947.73
4.35
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
BreakerAC134.7 %3620.0B4876.15
6.65
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
SingleAC126.49 %3620.0B4579.06
4.67
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_M_SRT-A
BreakerAC116.54 %3620.0B4218.81
3.96
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Base Case
SingleAC113.37 %2920.0A3310.31
3.23
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P2-2_NOTT230B_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B $ B
BusAC107.12 %3620.0B3877.79
5.03
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PL_04_P71_001014_SRT-A
TowerAC105.23 %3620.0B3809.42
4.69
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PL_05_P71_000906_SRT-A
TowerAC104.19 %3620.0B3771.64
4.66
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PL_04_P22_102290_SRT-A
BusAC103.6 %3620.0B3750.31
4.66
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC133.98 %2860.0B3831.94
7.0
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC133.98 %2860.0B3831.93
7.0
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC133.84 %2860.0B3827.78
6.99
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC133.82 %2860.0B3827.22
7.01
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
PECO_P1-2_5012_SRT-A
SingleAC121.88 %2860.0B3485.9
4.88
GD2PJM
PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z1 line
PECO_P4_PEACH255_SRT-A/* $ CHESCO $ PECO_P4_PEACH255 $ STBK
BreakerAC117.7 %2860.0B3366.11
6.59
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC115.07 %578.0B665.09
1.24
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC114.97 %578.0B664.51
1.24
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC114.92 %578.0B664.26
1.24
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC114.26 %578.0B660.41
1.22
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
BreakerAC108.46 %578.0B626.91
1.25
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC101.97 %578.0B589.37
0.86
GD2PECO
POST39-CHIREACT_39 230.0 kV Ckt 1 line
PECO_CBO_CHIC435_SRT-A/* $ DELCO $ PECO_CBO_CHIC435 $ K
BusAC101.34 %1622.0B1643.73
2.17

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.04 %
Rating:4150.0 MVA
Rating Type:B
MVA to Mitigate:4359.2
MW Contribution:
4.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
6.611
200195DELTA ST
50/50
3.37
200052ROCKSP 1
50/50
2.841
200053ROCKSP 2
50/50
2.785
232904IR4
Adder
105.562
232920IR10
Adder
4.126
232432Z2-076 GEN
Solar/Wind Harmer
0.172
233901CHERRYDALE C
Solar/Wind Harmer
1.468
232912OH NUG1
Adder
11.528
232913OH NUG2
Adder
11.375
233940AF2-379 C
Solar/Wind Harmer
0.243
971195AH1-057 GEN
Solar/Wind Harmer
1.272
233955AB2-172 GEN
Solar/Wind Harmer
6.513
232813VAUGHN
Adder
0.766
231906DC3 NUG
Adder
18.089
231902DC CT7
Adder
14.461
231907DC10
Adder
4.516
233968AD2-076_GEN
Solar/Wind Harmer
8.571
970597AG2-380 GEN
Solar/Wind Harmer
5.382
233915AB1-141 GEN
Solar/Wind Harmer
1.275
231919CHRIST1
Adder
5.581
231920CHRIST2
Adder
5.457
970453AG2-297 GEN
Solar/Wind Harmer
3.177
972141AH1-641 GEN
Solar/Wind Harmer
3.295
230422AE1-104_GEN1
Solar/Wind Harmer
38.61
230425AE1-104_GEN2
Solar/Wind Harmer
38.61
230430AE1-229_GEN
Solar/Wind Harmer
32.785
964001AG1-254 GEN
Solar/Wind Harmer
8.341
228728W1-130C
Solar/Wind Harmer
0.759
227927V4-067C
Solar/Wind Harmer
0.226
230407AD2-065 C
Solar/Wind Harmer
0.15
230434AG1-499 GEN
Solar/Wind Harmer
0.661
219137THOSOLAR C
Solar/Wind Harmer
1.369
219258KINSLEYDEP C
Solar/Wind Harmer
0.365
213942SCHUYLKILL
Adder
3.988
213942SCHUYLKILL
Adder
3.049
213957STHWK3-4
Adder
3.049
213957STHWK3-4
Adder
3.049
213561DLWR9-10
Adder
3.976
213561DLWR9-10
Adder
3.041
219615MILLCREEK C
Solar/Wind Harmer
0.267
219610FLORENCE C
Solar/Wind Harmer
1.547
219224BRL12CT4
Adder
9.97
213611FALLS1-3
Adder
3.931
213611FALLS1-3
Adder
3.931
20720728JCB_W1-129
Solar/Wind Harmer
0.331
20715028HAN_X4-015
Solar/Wind Harmer
0.331
207487AE2-000G4
Solar/Wind Harmer
34.936
207497AE2-000G2
Solar/Wind Harmer
34.936
207500AE2-000G1
Solar/Wind Harmer
34.936
207507AE2-000G3
Solar/Wind Harmer
34.936
963401AG1-189 GEN
Solar/Wind Harmer
2.521
970025AG2-016 GEN
Solar/Wind Harmer
3.141
200192DELTA CT1
50/50
2.181
200194DELTA CT3
50/50
2.181
200204Y1-065-CTG1
50/50
4.516
200054ROCKSP 3
50/50
2.874
232901NORTHST
Adder
10.881
233970AC1-092 C
Solar/Wind Harmer
3.505
234033AF1-007_GEN
Solar/Wind Harmer
48.561
232900DEMECSMY
Adder
12.045
972177AH1-672 GEN
Solar/Wind Harmer
17.537
232404W1-003 C
Solar/Wind Harmer
1.305
232408W1-005 C
Solar/Wind Harmer
1.305
232917OH NUG6
Adder
11.477
232915OH NUG4
Adder
11.452
233996TM1833_GEN
Solar/Wind Harmer
1.301
233998TM1NIN_3.36
Solar/Wind Harmer
1.301
232919VN10
Adder
3.661
232426Y1-080 FULL
Solar/Wind Harmer
0.249
232902EASTMUNI
Adder
16.941
234012AE2-112_GEN
Solar/Wind Harmer
2.974
972251AH1-710 GEN
Adder
57.798
233944AB2-135 GEN
Solar/Wind Harmer
6.752
233918AB1-142 GEN
Solar/Wind Harmer
1.275
231918WEST 1
Adder
4.242
231917EM10
Adder
2.965
228206SHRMN CT
Adder
19.057
228732V1-021 C
Adder
0.217
228260V4-054C
Solar/Wind Harmer
1.177
970997AG2-616 GEN
Solar/Wind Harmer
10.984
228729W2-030 C
Solar/Wind Harmer
0.659
228400MICK 1CT
Adder
13.439
213497CHSTR7-9
Adder
3.071
213497CHSTR7-9
Adder
3.071
219766PARADISE C
Solar/Wind Harmer
0.355
219686LUMSOLAR_N C
Solar/Wind Harmer
0.228
219907AC1-030 C
Solar/Wind Harmer
0.156
213958STHWK5-6
Adder
3.049
213560DLW11-12
Adder
3.041
219348LDSOLAR C
Solar/Wind Harmer
0.668
219222BRL12CT2
Adder
9.97
213611FALLS1-3
Adder
3.931
214194N WALES4
Adder
0.948
20716028EGP_W2-019
Solar/Wind Harmer
0.515
207522AF2-254 C
Solar/Wind Harmer
1.593
20717128DIX_Z2-102
Solar/Wind Harmer
1.465
20715828PEM_W1-120
Solar/Wind Harmer
0.592
963711AG1-223 GEN
Solar/Wind Harmer
1.636
20714528FRN_Y2-051
Solar/Wind Harmer
0.326
219276PARKLANDSO C
Solar/Wind Harmer
0.51
219680HOPEWELLV C1
Solar/Wind Harmer
0.084
20715228NPK_W1-113
Solar/Wind Harmer
0.474
20720528MAN_W1-024
Solar/Wind Harmer
0.28
20720428HOL_W1-112
Solar/Wind Harmer
0.381
20635828PARLN1&2
Adder
8.151
20635028RRCT1&2
Adder
12.975
218524CNTRALGAS1 C
Solar/Wind Harmer
0.406
218440SUMMTASSOC C
Solar/Wind Harmer
0.141
218428ETC SOLAR C
Solar/Wind Harmer
0.039
219908AB1-139 C
Solar/Wind Harmer
0.418
219919AE1-041 FULL
Solar/Wind Harmer
0.044
972275AH1-722 GEN
Adder
34.705
20673628F1S_V4-069
Solar/Wind Harmer
0.197
207528AF2-192 GEN
Solar/Wind Harmer
1.396
217209CENTRL HS C
Solar/Wind Harmer
0.049
217186ESSEX_G9
Adder
4.33
217121ECCF
Adder
0.476
217083KRNY_132
Adder
10.196
20671828STAW2-080
Solar/Wind Harmer
0.115
217208PARK ELE C
Solar/Wind Harmer
0.028
20676728BRNX1-095
Solar/Wind Harmer
0.193
966261AG1-495 GEN
Solar/Wind Harmer
3.838
207439AE1-081 C O1
Solar/Wind Harmer
0.065
20676328BVR_Y1-020
Solar/Wind Harmer
0.361
20674628WNG_W3-110
Solar/Wind Harmer
0.441
207530AG1-191 GEN
Solar/Wind Harmer
1.503
20676228FRD_X1-012
Solar/Wind Harmer
0.646
20675828AU_W4-064
Solar/Wind Harmer
0.189
20674928WA_W3-044
Solar/Wind Harmer
0.525
971519AH1-257 GEN
Solar/Wind Harmer
2.751
20675728RH_W2-091
Solar/Wind Harmer
0.658
207518AF1-320_GEN
Solar/Wind Harmer
3.988
207484AF2-139 C O1
Solar/Wind Harmer
0.551
20465127PORT CT
Adder
3.272
208909MACR G3
Adder
173.367
211065PSPA IPP
Solar/Wind Harmer
0.487
961301AF2-421 GEN
Solar/Wind Harmer
1.052
963151AG1-164 GEN
Solar/Wind Harmer
1.052
209023WIENIPP1
Adder
11.341
209025WIENIPP3
Adder
5.661
963071AG1-156 GEN
Solar/Wind Harmer
10.329
209010PEIP 1
Adder
0.666
961341AF2-425 GEN
Solar/Wind Harmer
1.016
212507AE2-042_GEN
Solar/Wind Harmer
2.994
946731AF1-337 GEN
Solar/Wind Harmer
0.993
209018SUNBIPCT
Adder
7.383
20465527S.RDG CT
Adder
2.722
209008PAXT IPP
Adder
1.814
209137AF2-361 C
Solar/Wind Harmer
2.564
205967AE2-211_GEN
Solar/Wind Harmer
5.78
941421AE2-139 GEN
Solar/Wind Harmer
2.746
20328326MANOR_T86
Adder
0.126
316415AF1-147_GEN2
Solar/Wind Helper
1.093
238175AF1-290_GEN
Solar/Wind Helper
0.162
316447AC1-158 HLD
Solar/Wind Helper
3.662
316044AC1-158 PL1
Solar/Wind Helper
1.664
3147666LOUISA
Solar/Wind Helper
1.16
316192AB2-158 GEN
Solar/Wind Helper
1.953
238152AF2-075_GEN
Solar/Wind Helper
0.704
316337AD2-073 GEN
Solar/Wind Helper
0.431
964211AG1-282 GEN
Solar/Wind Helper
0.38
3141726DUNNSVL
Solar/Wind Helper
1.127
316404AE1-155 C
Solar/Wind Helper
2.406
3142416OLDCHRC
Solar/Wind Helper
0.728
3142416OLDCHRC
Solar/Wind Helper
0.279
3138133OCRAN
Solar/Wind Helper
0.168
3141766HARMONY
Solar/Wind Helper
0.056
315662AE1-191 GEN
Solar/Wind Helper
1.504
316280AD1-041 GEN
Solar/Wind Helper
0.94
3143526WINTERP
Solar/Wind Helper
1.45
315975AC1-164 GENB
Solar/Wind Helper
0.106
3142433PROV 92
Solar/Wind Helper
1.115
3143226MDLTHAN
Solar/Wind Helper
0.279
3142543TWELFTH
Solar/Wind Helper
0.027
316132AB2-190 GEN1
Solar/Wind Helper
1.581
315671AE2-027_GEN
Solar/Wind Helper
2.231
316369SG1_INVT
Solar/Wind Helper
1.33
3145336SMITFLD
Solar/Wind Helper
1.096
315773AC2-141 GEN
Solar/Wind Helper
5.904
316381AD1-082 GEN
Solar/Wind Helper
1.419
316375AC2-012 GEN
Solar/Wind Helper
0.719
316036AC1-147 C
Solar/Wind Helper
0.417
316072AD1-144
Solar/Wind Helper
0.312
3146456SLIGO L269
Solar/Wind Helper
0.272
319010AE1-072 C
Solar/Wind Helper
3.113
23777901MDS_W4-102
Solar/Wind Helper
0.171
3146516WINFALL
Solar/Wind Helper
0.874
3146516WINFALL
Solar/Wind Helper
0.27
315611Z1-036_GEN2
Solar/Wind Helper
1.475
3130156CHOWAN
Solar/Wind Helper
0.268
315816AE2-034 GEN
Solar/Wind Helper
1.218
3145663CRESWEL
Solar/Wind Helper
0.744
3146776BUCKING
Solar/Wind Helper
0.106
315737AD1-076 GEN
Solar/Wind Helper
2.587
3146926FARMVIL
Solar/Wind Helper
0.158
316023GEN1_S
Solar/Wind Helper
1.006
3146206CASHIE
Solar/Wind Helper
0.263
3145893MURPHYS
Solar/Wind Helper
1.053
3146173TUNIS
Solar/Wind Helper
0.263
3147983MERCK5
Solar/Wind Helper
0.105
3156021HOLLOMANSOL
Solar/Wind Helper
2.001
3145683EARLEYS
Solar/Wind Helper
0.262
315607AA1-063A GEN
Solar/Wind Helper
1.497
316087AB2-174 GEN
Solar/Wind Helper
1.832
3146263WOODLND
Solar/Wind Helper
0.261
3145963POPLR C
Solar/Wind Helper
0.26
3145823KELFORD
Solar/Wind Helper
0.26
3145783HORNRTN
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.855
3145796HORNRTN
Solar/Wind Helper
0.259
316034AC1-036 C
Solar/Wind Helper
0.272
315785AD2-033 C
Solar/Wind Helper
3.019
316129AC1-054 GEN
Solar/Wind Helper
1.278
316131AB2-060 GEN
Solar/Wind Helper
1.571
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
316494AC1-189 GEN
Solar/Wind Helper
1.554
3146233WITAKRS
Solar/Wind Helper
1.009
961671AG1-007 GEN
Solar/Wind Helper
0.182
3146083TARBORO
Solar/Wind Helper
0.253
316359AB2-059 GEN
Solar/Wind Helper
1.926
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.202
238108AE1-109 GEN1
Solar/Wind Helper
0.094
238110AE1-109 GEN3
Solar/Wind Helper
0.094
964991AG1-363 GEN
Solar/Wind Helper
3.5
3147123OTTER R
Solar/Wind Helper
0.138
3147312GRETNA
Solar/Wind Helper
0.183
3146802CHATHAM
Solar/Wind Helper
0.172
270016AE1-250 BESS
Solar/Wind Helper
0.847
270018AE2-047 C O1
Solar/Wind Helper
0.792
200035PCHBTM 3
50/50
22.888
200201DELTA2 CT2
50/50
3.904
200034PCHBTM 2
50/50
22.757
200205Y1-065-CTG2
50/50
4.516
233971AC1-093 C
Solar/Wind Harmer
3.328
232899W1-062
Adder
12.558
232410W1-006 C
Solar/Wind Harmer
1.305
232918OH NUG7
Adder
11.452
232905CHERITON_25
Adder
3.202
232926CRISFLD1
Adder
2.562
231940T-011
Adder
0.973
234015AF2-250 C
Solar/Wind Harmer
0.157
232428Y3-058 C
Solar/Wind Harmer
1.087
233994AC2-023 GEN
Solar/Wind Harmer
3.502
233946AB2-136 GEN
Solar/Wind Harmer
5.198
234036AF2-325 C
Solar/Wind Harmer
1.194
233952AC2-187 GEN
Solar/Wind Harmer
1.466
233954AC2-188 GEN
Solar/Wind Harmer
1.466
234041AC1-190 GEN
Solar/Wind Harmer
11.671
232910NRG_G1
Adder
11.218
233984AB2-036 GEN
Solar/Wind Harmer
16.143
232424Y1-079 C
Solar/Wind Harmer
0.728
234014AF1-036_GEN
Solar/Wind Harmer
3.498
232436AB1-176 C
Solar/Wind Harmer
0.296
233930AB2-032 GEN
Solar/Wind Harmer
1.073
233982AB2-133 GEN
Solar/Wind Harmer
6.271
228201CARL#2CT
Adder
7.887
228200CARL#1CT
Adder
7.501
228251CARLLS#4
Adder
0.724
230433AD2-135 GEN
Solar/Wind Harmer
0.116
228351V2-046C
Solar/Wind Harmer
2.305
230511AF1-262
Solar/Wind Harmer
0.209
228754AB1-001 C
Solar/Wind Harmer
0.159
228307PCLP GT
Adder
13.804
972233AH1-701 GEN
Adder
4.777
219272CLEANLIGHT C
Solar/Wind Harmer
0.206
219904AC1-010 C
Solar/Wind Harmer
0.426
219287REEVESEAST C
Solar/Wind Harmer
1.516
213589EDDYSTN4
Adder
89.656
213587EDDYSTN3
Adder
89.65
219912AD2-042 GEN
Solar/Wind Harmer
0.895
219906AC1-017 C
Solar/Wind Harmer
0.249
213815MOSER1-3
Adder
3.966
213815MOSER1-3
Adder
3.966
219607WPEMNERT C
Solar/Wind Harmer
0.468
219304NAMERICA C
Solar/Wind Harmer
0.346
213535CROYDN11
Adder
11.421
214067T20SOLAR
Solar/Wind Harmer
0.281
20720828JCB_W4-025
Solar/Wind Harmer
0.503
20636128O CRK C2
Adder
7.147
207459AE1-142 C O1
Solar/Wind Harmer
1.168
20628028LAKEHURS
Adder
1.053
20714828MDF_W3-079
Solar/Wind Harmer
0.338
219817TRENTONSOL C
Solar/Wind Harmer
1.217
20641628MLH_W1-032
Solar/Wind Harmer
0.324
20742028HF_AC1-207
Solar/Wind Harmer
0.864
217197RE CRAN C
Solar/Wind Harmer
0.591
218438BLK ROCK C
Solar/Wind Harmer
0.15
924131AB2-057 GEN
Solar/Wind Harmer
1.132
20635028RRCT1&2
Adder
12.775
20635128RRCT3&4
Adder
12.332
20635128RRCT3&4
Adder
10.757
218418LINDEN_G5
Adder
18.878
218419LINDEN_G6
Adder
18.878
972260AH1-715 GEN1
Adder
15.117
20675428EAM_W2-061
Solar/Wind Harmer
0.207
219036LINDEN_G7
Adder
18.371
219035LINDEN_G8
Adder
18.109
972261AH1-715 GEN2
Adder
17.586
217081WEATEXAS C
Solar/Wind Harmer
0.094
217202FBANKSOLAR C
Solar/Wind Harmer
0.081
217201HACKENSOLA C
Solar/Wind Harmer
0.08
972237AH1-703 GEN
Adder
11.098
217206BARNGR HS C
Solar/Wind Harmer
0.034
217086KRNY_131
Adder
10.217
217083KRNY_132
Adder
10.131
217204WCALDSOLAR C
Solar/Wind Harmer
0.08
20674328GAR_V4-001
Solar/Wind Harmer
0.12
20674828DL_W4-046
Solar/Wind Harmer
0.705
207471AF2-354 C
Solar/Wind Harmer
0.559
20634528N27_Y2-018
Solar/Wind Harmer
0.294
20675928HOL_W4-097
Solar/Wind Harmer
0.142
20465127PORT CT
Adder
4.342
961541AF2-445A GEN
Solar/Wind Harmer
3.357
209010PEIP 1
Adder
3.664
209010PEIP 1
Adder
0.537
961431AF2-434 GEN
Solar/Wind Harmer
1.014
946751AF1-339 GEN
Solar/Wind Harmer
0.993
209130AF1-271A GEN
Solar/Wind Harmer
2.787
20465527S.RDG CT
Adder
2.634
316411AF1-147_GEN1
Solar/Wind Helper
1.093
316006AB2-029 C
Solar/Wind Helper
0.146
316045AC1-158 PL2
Solar/Wind Helper
5.325
316450AC1-158 RIC
Solar/Wind Helper
0.444
966001AG1-469 GEN
Solar/Wind Helper
0.309
238147AE2-230_GEN1
Solar/Wind Helper
0.493
238148AE2-230_GEN2
Solar/Wind Helper
0.493
238149AF1-291A_GEN
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.379
237061AD1-155 GEN
Solar/Wind Helper
1.762
316487AF1-042 GEN
Solar/Wind Helper
0.284
316312AB1-027
Solar/Wind Helper
0.535
315666AE1-190 GEN
Solar/Wind Helper
0.376
316156AD2-030 GEN
Solar/Wind Helper
0.422
3143526WINTERP
Solar/Wind Helper
1.45
315976AC1-164 GENA
Solar/Wind Helper
3.599
316169AC1-164_GENC
Solar/Wind Helper
3.109
3142946ENON
Solar/Wind Helper
0.028
316240AF1-291 C
Solar/Wind Helper
0.372
316033AB2-134 GEN
Solar/Wind Helper
0.955
316294AC1-161 GEN
Solar/Wind Helper
5.018
316313AB2-026
Solar/Wind Helper
0.418
316185AD1-033 GEN
Solar/Wind Helper
1.286
3145506HICKORY
Solar/Wind Helper
1.09
3145506HICKORY
Solar/Wind Helper
0.654
3145506HICKORY
Solar/Wind Helper
0.163
316349AD2-085 GEN
Solar/Wind Helper
1.247
316339AD2-160 GEN
Solar/Wind Helper
1.039
316388AE2-253 GEN
Solar/Wind Helper
1.039
235020AA1-095 C
Solar/Wind Helper
0.051
3137176SLIGO L2192
Solar/Wind Helper
1.082
3130086AYDLETT
Solar/Wind Helper
1.087
3146386ELIZ CT
Solar/Wind Helper
0.271
316431W1029_GEN1
Solar/Wind Helper
1.092
316433W1029_GEN2
Solar/Wind Helper
1.092
316435W1029_GEN3
Solar/Wind Helper
1.092
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.269
971189AH1-054 GEN
Solar/Wind Harmer
1.308
207445AB1-138_GEN
Solar/Wind Harmer
0.641
219620RIDERU C
Solar/Wind Harmer
0.062
20714428HOW_X1-037
Solar/Wind Harmer
1.363
20720628TIN_W1-124
Solar/Wind Harmer
1.098
20716228APLW2-078
Solar/Wind Harmer
0.975
971521AH1-258 GEN
Solar/Wind Harmer
2.985
20635928PARLN3&4
Adder
8.151
218526CNTRALGAS2 C
Solar/Wind Harmer
0.407
20675528CPH_W2-050
Solar/Wind Harmer
0.631
20673828FLE_V3-070
Solar/Wind Harmer
0.512
20676128MHD_W3-029
Solar/Wind Harmer
0.524
218449LINSOLAR C
Solar/Wind Harmer
1.105
20676428JCR_X2-075
Solar/Wind Harmer
0.375
217167KRNY_14
Adder
10.196
217086KRNY_131
Adder
10.109
217147KRNY_1212
Adder
9.698
217147KRNY_1212
Adder
9.525
217146KRNY_1234
Adder
9.503
217146KRNY_1234
Adder
9.438
964851AG1-348 GEN
Solar/Wind Harmer
1.491
971009AG2-626 GEN
Solar/Wind Harmer
1.788
207408W3-077 C
Solar/Wind Harmer
0.552
20675128HRM_W1-127
Solar/Wind Harmer
0.185
20462827N BANGR8
Adder
0.781
961261AF2-417 GEN
Solar/Wind Harmer
1.055
209026WIENIPP4
Adder
5.604
209027LOR2_Q27
Solar/Wind Harmer
4.673
212266LOR1
Solar/Wind Harmer
1.239
209029WAYMART-WD
Solar/Wind Harmer
2.676
209054AE2-059 GEN
Solar/Wind Harmer
1.689
959431AF2-234 GEN
Solar/Wind Harmer
1.982
964051AG1-259 GEN
Solar/Wind Harmer
1.329
964061AG1-260 GEN
Solar/Wind Harmer
1.329
959421AF2-233 GEN
Solar/Wind Harmer
0.991
20486527WR_V4-052
Adder
1.063
208862AG1-362 C
Solar/Wind Harmer
0.769
209067AE2-060 GEN
Solar/Wind Harmer
1.327
20390726Y2-042
Adder
2.772
200917MEHOOPANY_G
Solar/Wind Harmer
3.649
20334726NME_Y1-047
Adder
2.453
203926AA2-133 GEN
Adder
2.266
205951AE1-129_GEN
Solar/Wind Harmer
7.69
3138216PACIFIC
Solar/Wind Helper
0.054
3141426STAFORD
Solar/Wind Helper
0.066
315651AD1-115 GEN
Solar/Wind Helper
1.009
316164AC1-076 GEN
Solar/Wind Helper
1.421
238169AE2-226 GEN1
Solar/Wind Helper
0.722
238170AE2-226 GEN2
Solar/Wind Helper
0.722
316468AD1-105 GEN
Solar/Wind Helper
1.37
3141813NORNECK
Solar/Wind Helper
0.282
3141783LANCAST
Solar/Wind Helper
0.168
3141783LANCAST
Solar/Wind Helper
0.112
3138133OCRAN
Solar/Wind Helper
0.084
3141913WHIT STONE
Solar/Wind Helper
0.279
316059AD1-063 C
Solar/Wind Helper
0.282
3143873LANEXA
Solar/Wind Helper
0.167
957601AF2-054 GEN
Solar/Wind Helper
0.374
3141873WAN 176
Solar/Wind Helper
0.056
316233AE1-074 FULL
Solar/Wind Helper
0.426
957831AF2-077 GEN
Solar/Wind Helper
0.374
316382AG1-145 C
Solar/Wind Helper
0.373
316159AE1-175 C
Solar/Wind Helper
0.421
315697AD1-025 GEN
Solar/Wind Helper
3.155
315839AE2-212 C
Solar/Wind Helper
0.371
316236AE1-162_GEN
Solar/Wind Helper
0.369
3143316POE
Solar/Wind Helper
1.084
316258AE1-075 C
Solar/Wind Helper
0.376
316405AF2-144 C
Solar/Wind Helper
0.314
316316AC1-027 C
Solar/Wind Helper
0.431
316018AA1-139 ULT2
Solar/Wind Helper
1.173
313526AB2-022
Solar/Wind Helper
0.414
3146486SUNBURY
Solar/Wind Helper
0.271
3146486SUNBURY
Solar/Wind Helper
0.271
3145176PASQUOTANK
Solar/Wind Helper
0.168
315800Z1-036_GEN1
Solar/Wind Helper
1.475
3130156CHOWAN
Solar/Wind Helper
0.268
3130156CHOWAN
Solar/Wind Helper
0.268
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
316322AB2-045
Solar/Wind Helper
0.296
3130546PLYMOUTH
Solar/Wind Helper
0.264
315732AD1-074 GEN1
Solar/Wind Helper
3.025
315733AD1-074 GEN2
Solar/Wind Helper
3.025
3146206CASHIE
Solar/Wind Helper
0.263
3145893MURPHYS
Solar/Wind Helper
0.711
3145893MURPHYS
Solar/Wind Helper
0.263
316463AE2-346 GEN
Solar/Wind Helper
0.24
3145513AHOSKIE
Solar/Wind Helper
0.118
961941AG1-037 GEN
Solar/Wind Helper
0.088
3145513AHOSKIE
Solar/Wind Helper
0.262
946281AF1-292 GEN
Solar/Wind Helper
0.263
3146043SEABORD
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.523
3145683EARLEYS
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.262
3137643SOCKMAN
Solar/Wind Helper
1.041
316426AA2-053 GEN
Solar/Wind Helper
1.489
316174AB2-169 GEN
Solar/Wind Helper
0.665
316486AD2-202 GEN
Solar/Wind Helper
0.373
3148133STUARTS
Solar/Wind Helper
0.156
3148013FISHERV
Solar/Wind Helper
0.149
3145796HORNRTN
Solar/Wind Helper
0.829
3145796HORNRTN
Solar/Wind Helper
0.104
3144303KENBRDG
Solar/Wind Helper
0.207
3146033SCOT NK
Solar/Wind Helper
1.035
316210AC1-098 GEN
Solar/Wind Helper
2.082
316274AC1-208 GEN
Solar/Wind Helper
1.57
316238AB2-078_GEN
Solar/Wind Helper
0.346
316239AB2-077_GEN
Solar/Wind Helper
0.346
3145746EVERETS
Solar/Wind Helper
1.017
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
316327AA2-057 GEN
Solar/Wind Helper
1.457
226929AD2-058 GEN
Solar/Wind Helper
0.099
3145573BETHELC
Solar/Wind Helper
0.253
3145573BETHELC
Solar/Wind Helper
0.253
315616AA1-038_C
Solar/Wind Helper
1.138
3148463FAIRFLD
Solar/Wind Helper
0.251
3147173SINAI
Solar/Wind Helper
0.25
3147243WELCO
Solar/Wind Helper
0.156
270455AD2-022 GEN
Solar/Wind Helper
1.372
270457AD2-023 GEN
Solar/Wind Helper
0.904
270197AD1-017 GEN1
Solar/Wind Helper
1.224
3146626S HERTFORD
Solar/Wind Helper
0.269
3144356SAPONY
Solar/Wind Helper
0.483
316315AB2-025 C
Solar/Wind Helper
0.411
3132123MT JACKSON
Solar/Wind Helper
0.834
315614AA2-178 GEN
Solar/Wind Helper
1.624
3146776BUCKING
Solar/Wind Helper
1.059
3146776BUCKING
Solar/Wind Helper
0.086
316365GEN2_N
Solar/Wind Helper
1.006
3145893MURPHYS
Solar/Wind Helper
0.378
3145893MURPHYS
Solar/Wind Helper
0.474
3146173TUNIS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
316097T157 G90
Solar/Wind Helper
1.209
316140AB2-099
Solar/Wind Helper
0.1
313506AB2-031 GEN
Solar/Wind Helper
1.188
3147133PAMPLIN
Solar/Wind Helper
0.261
3147133PAMPLIN
Solar/Wind Helper
0.209
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.156
3145593CAROLNA
Solar/Wind Helper
0.26
3145593CAROLNA
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.777
3145933PARMELE
Solar/Wind Helper
0.514
3145933PARMELE
Solar/Wind Helper
0.257
316237AB2-079_GEN
Solar/Wind Helper
0.346
316005AA1-067
Solar/Wind Helper
0.293
315687AD1-152 GEN
Solar/Wind Helper
1.377
3146843MT LREL
Solar/Wind Helper
0.253
3146843MT LREL
Solar/Wind Helper
0.253
316049AB1-081 GEN
Solar/Wind Helper
1.54
316118AC1-105 GEN
Solar/Wind Helper
0.979
238221AF1-254 C O1
Solar/Wind Helper
0.248
316248AF1-058 C
Solar/Wind Helper
0.337
237080AD1-060 GEN
Solar/Wind Helper
0.298
270013AE1-250 PV
Solar/Wind Helper
0.847
200200DELTA2 CT1
50/50
3.904
200193DELTA CT2
50/50
2.181
200203Y1-065-STG
50/50
7.82
200055ROCKSP 4
50/50
2.824
233973AC2-185 C
Solar/Wind Harmer
7.08
970695AG2-447 GEN
Solar/Wind Harmer
4.684
233939AC1-091 C
Solar/Wind Harmer
3.505
233972AC1-094 C
Solar/Wind Harmer
2.814
233987AB2-037 GEN
Solar/Wind Harmer
14.844
232434Z2-077 GEN
Solar/Wind Harmer
0.326
232406W1-004 FULL
Solar/Wind Harmer
1.305
232914OH NUG3
Adder
11.528
232916OH NUG5
Adder
11.528
232921TASLEY2G
Adder
6.738
233923SMA
Solar/Wind Harmer
4.769
233997TMININ_4.2
Solar/Wind Harmer
1.301
232907VN8
Adder
39.184
233964AF2-378 GEN
Solar/Wind Harmer
0.166
233950AC2-186 GEN
Solar/Wind Harmer
0.733
232417X3-008 C
Solar/Wind Harmer
1.466
232422X3-066 FULL
Solar/Wind Harmer
0.323
233933AB2-153 GEN
Solar/Wind Harmer
1.449
233935AB2-179 C
Solar/Wind Harmer
3.169
228711V2-041C
Solar/Wind Harmer
0.691
230415AB2-049 C
Solar/Wind Harmer
0.217
219623KINSLEYBEA C
Solar/Wind Harmer
0.483
219291REEVESSOUT C
Solar/Wind Harmer
0.068
219921AF1-264
Solar/Wind Harmer
0.163
218660EHAMPSOLAR C
Solar/Wind Harmer
0.197
213497CHSTR7-9
Adder
3.071
219688LUMSOLAR_S C
Solar/Wind Harmer
0.228
219914AD2-027 C
Solar/Wind Harmer
0.675
219236SOUTHERNHQ C
Solar/Wind Harmer
0.076
213958STHWK5-6
Adder
3.049
213560DLW11-12
Adder
3.041
213815MOSER1-3
Adder
3.966
219221BRL12CT1
Adder
9.97
219223BRL12CT3
Adder
9.97
20716428NHV_W2-082
Solar/Wind Harmer
1.973
959561AF2-247 GEN
Solar/Wind Harmer
0.539
20715728PEM_W1-119
Solar/Wind Harmer
0.592
20636028O CRK C1
Adder
7.839
963391AG1-188 GEN
Solar/Wind Harmer
4.155
20714928UPF_X1-085
Solar/Wind Harmer
0.451
971667AH1-334 GEN
Solar/Wind Harmer
3.043
219114HARTZY_C
Solar/Wind Harmer
0.923
219727YARDVSOLFA C
Solar/Wind Harmer
1.007
219918AC2-009 C
Solar/Wind Harmer
0.028
207454AA2-184 E
Solar/Wind Harmer
1.102
219612MATRIX C
Solar/Wind Harmer
0.203
20716928W4-060COL
Solar/Wind Harmer
0.783
20635828PARLN1&2
Adder
3.692
20635928PARLN3&4
Adder
3.692
217213AMBOY SO C
Solar/Wind Harmer
0.139
219249CENTRALDIV C
Solar/Wind Harmer
0.044
207442AE1-156 GEN
Solar/Wind Harmer
0.816
20673728F2S_V4-070
Solar/Wind Harmer
0.197
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217169METRODIV C
Solar/Wind Harmer
0.044
217194REDH C
Solar/Wind Harmer
0.54
20674528F3S_W2-016
Solar/Wind Harmer
1.541
207510AF2-138 C
Solar/Wind Harmer
1.944
207511W3-106 GEN
Solar/Wind Harmer
0.361
971007AG2-625 GEN
Solar/Wind Harmer
2.804
207437AD2-070 GEN
Solar/Wind Harmer
0.328
20671928W4-073
Solar/Wind Harmer
0.471
20466127PORT 5CT
Adder
28.881
20674128FR_U2-059
Solar/Wind Harmer
0.201
20633028GILCT9
Adder
30.817
20465427SHAW CT
Adder
4.196
209116AE2-175 GEN
Solar/Wind Harmer
4.448
211065PSPA IPP
Solar/Wind Harmer
0.487
963161AG1-165 GEN
Solar/Wind Harmer
1.052
209025WIENIPP3
Adder
5.546
970095AG2-074 GEN
Solar/Wind Harmer
6.541
208972BECR K09
Solar/Wind Harmer
1.098
961331AF2-424 GEN
Solar/Wind Harmer
1.016
961421AF2-433 GEN
Solar/Wind Harmer
1.014
957921AF2-086 GEN
Solar/Wind Harmer
0.986
209142AF1-226 GEN
Solar/Wind Harmer
5.869
209093AE2-110 GEN
Solar/Wind Harmer
2.535
209120AE2-241 GEN
Solar/Wind Harmer
3.354
205941AD2-115 GEN
Solar/Wind Harmer
0.936
946691AF1-333 GEN
Solar/Wind Harmer
0.993
946741AF1-338 GEN
Solar/Wind Harmer
0.993
209071AE2-133 GEN
Solar/Wind Harmer
1.677
972221AH1-695 GEN
Adder
123.568
3141196NOKESVL
Solar/Wind Helper
1.257
3132273ORANGE
Solar/Wind Helper
0.058
3147666LOUISA
Solar/Wind Helper
0.667
966881AG1-559 GEN
Solar/Wind Helper
0.389
316223AC1-118
Solar/Wind Helper
0.435
3141906WESTMOR
Solar/Wind Helper
0.114
23546401DTGZ2-030
Solar/Wind Helper
0.089
316077AC2-138 C
Solar/Wind Helper
0.266
316473AC1-191 GEN
Solar/Wind Helper
1.72
316484AD2-074 GEN
Solar/Wind Helper
0.542
316075AC2-137 C
Solar/Wind Helper
0.426
3142946ENON
Solar/Wind Helper
0.093
316458AB2-190 GEN2
Solar/Wind Helper
1.581
3145336SMITFLD
Solar/Wind Helper
0.11
3144536CHRHLND
Solar/Wind Helper
0.041
3144873MCLAUGH
Solar/Wind Helper
0.007
3142956BIRDNECK
Solar/Wind Helper
0.184
316017AA1-139 ULT1
Solar/Wind Helper
1.247
3146456SLIGO L269
Solar/Wind Helper
0.272
316305AF2-043 C
Solar/Wind Helper
0.366
316246AF1-032 C
Solar/Wind Helper
0.311
316320Y1-086
Solar/Wind Helper
0.122
316321Z2-027
Solar/Wind Helper
0.413
3146516WINFALL
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.269
3145273HOLLAND
Solar/Wind Helper
0.202
3146376EDENTON
Solar/Wind Helper
0.268
3146776BUCKING
Solar/Wind Helper
0.095
315735AD1-075 GEN1
Solar/Wind Helper
1.513
3146926FARMVIL
Solar/Wind Helper
0.158
3146206CASHIE
Solar/Wind Helper
0.263
3145893MURPHYS
Solar/Wind Helper
0.094
3145893MURPHYS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
316095T157 G97
Solar/Wind Helper
1.209
315821AE2-092 GEN
Solar/Wind Helper
2.439
942461AE2-259 GEN
Solar/Wind Helper
1.765
966621AG1-532 GEN
Solar/Wind Helper
0.238
316499AE2-029_GEN
Solar/Wind Helper
0.88
3146263WOODLND
Solar/Wind Helper
0.261
316181AB2-040 GEN
Solar/Wind Helper
1.877
3147133PAMPLIN
Solar/Wind Helper
0.818
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3147043LAWRENC
Solar/Wind Helper
0.156
3145963POPLR C
Solar/Wind Helper
0.26
316190AA2-174 GEN
Solar/Wind Helper
0.018
316011AB1-132 GEN
Solar/Wind Helper
2.806
316317KELFORD C
Solar/Wind Helper
0.234
3145823KELFORD
Solar/Wind Helper
0.26
316478AD1-087 GEN
Solar/Wind Helper
1.273
3148013FISHERV
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
1.036
3145796HORNRTN
Solar/Wind Helper
0.259
316212AC1-099_GEN
Solar/Wind Helper
1.157
3145933PARMELE
Solar/Wind Helper
0.257
23583801GRNGAP
Solar/Wind Helper
4.397
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
270494AE1-108_GEN
Solar/Wind Helper
3.414
316420AA1-050 GEN
Solar/Wind Helper
1.459
3146233WITAKRS
Solar/Wind Helper
0.273
3146233WITAKRS
Solar/Wind Helper
0.172
3146073TAR RVR
Solar/Wind Helper
0.253
3146083TARBORO
Solar/Wind Helper
0.253
3138543CONSLDL
Solar/Wind Helper
0.167
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.252
238109AE1-109 GEN2
Solar/Wind Helper
0.094
316003AC1-222 GEN
Solar/Wind Helper
1.078
227287AC2-120 GEN
Solar/Wind Helper
0.335
226910AB2-157 C
Solar/Wind Helper
0.014
316222AC1-221 GEN
Solar/Wind Helper
1.39
316283AC2-100 C
Solar/Wind Helper
1.294
316123AC1-075 GEN
Solar/Wind Helper
1.47
237038AE2-054 C
Solar/Wind Helper
0.23
235067AD1-061 GEN
Solar/Wind Helper
0.375
316197AC1-042 GEN
Solar/Wind Helper
0.216
3147312GRETNA
Solar/Wind Helper
0.046
237085AD2-009_GEN
Solar/Wind Helper
1.36
237002AB1-128_GEN
Solar/Wind Helper
0.364
270173AC1-122 GEN
Solar/Wind Helper
1.533
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.981
VTFLTFEXP_VFT->PJM
CMTX
148.636
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.489
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.554
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.195
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.577
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
56.425
CBM NorthLTFEXP_CBM-N->PJM
CBM
83.076
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.01 %
Rating:4150.0 MVA
Rating Type:B
MVA to Mitigate:4357.8
MW Contribution:
4.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
2.181
200194DELTA CT3
50/50
2.181
200204Y1-065-CTG1
50/50
4.516
200054ROCKSP 3
50/50
2.874
232901NORTHST
Adder
10.881
233970AC1-092 C
Solar/Wind Harmer
3.505
234033AF1-007_GEN
Solar/Wind Harmer
48.561
232900DEMECSMY
Adder
12.045
972177AH1-672 GEN
Solar/Wind Harmer
17.537
232404W1-003 C
Solar/Wind Harmer
1.305
232408W1-005 C
Solar/Wind Harmer
1.305
232917OH NUG6
Adder
11.477
232915OH NUG4
Adder
11.452
233996TM1833_GEN
Solar/Wind Harmer
1.301
233998TM1NIN_3.36
Solar/Wind Harmer
1.301
232919VN10
Adder
3.661
200202DELTA2 ST
50/50
6.611
200195DELTA ST
50/50
3.37
200052ROCKSP 1
50/50
2.841
200053ROCKSP 2
50/50
2.785
232904IR4
Adder
105.562
200035PCHBTM 3
50/50
22.888
200201DELTA2 CT2
50/50
3.904
200034PCHBTM 2
50/50
22.757
200205Y1-065-CTG2
50/50
4.516
233971AC1-093 C
Solar/Wind Harmer
3.328
232899W1-062
Adder
12.558
232410W1-006 C
Solar/Wind Harmer
1.305
232918OH NUG7
Adder
11.452
232905CHERITON_25
Adder
3.202
232926CRISFLD1
Adder
2.562
231940T-011
Adder
0.973
234015AF2-250 C
Solar/Wind Harmer
0.157
232428Y3-058 C
Solar/Wind Harmer
1.087
233994AC2-023 GEN
Solar/Wind Harmer
3.502
233946AB2-136 GEN
Solar/Wind Harmer
5.198
234036AF2-325 C
Solar/Wind Harmer
1.194
233952AC2-187 GEN
Solar/Wind Harmer
1.466
233954AC2-188 GEN
Solar/Wind Harmer
1.466
234041AC1-190 GEN
Solar/Wind Harmer
11.671
232910NRG_G1
Adder
11.218
233984AB2-036 GEN
Solar/Wind Harmer
16.143
232424Y1-079 C
Solar/Wind Harmer
0.728
234014AF1-036_GEN
Solar/Wind Harmer
3.498
232436AB1-176 C
Solar/Wind Harmer
0.296
233930AB2-032 GEN
Solar/Wind Harmer
1.073
233982AB2-133 GEN
Solar/Wind Harmer
6.271
228201CARL#2CT
Adder
7.887
228200CARL#1CT
Adder
7.501
228251CARLLS#4
Adder
0.724
230433AD2-135 GEN
Solar/Wind Harmer
0.116
228351V2-046C
Solar/Wind Harmer
2.305
230511AF1-262
Solar/Wind Harmer
0.209
228754AB1-001 C
Solar/Wind Harmer
0.159
228307PCLP GT
Adder
13.804
972233AH1-701 GEN
Adder
4.777
219272CLEANLIGHT C
Solar/Wind Harmer
0.206
219904AC1-010 C
Solar/Wind Harmer
0.426
219287REEVESEAST C
Solar/Wind Harmer
1.516
213589EDDYSTN4
Adder
89.656
213587EDDYSTN3
Adder
89.65
219912AD2-042 GEN
Solar/Wind Harmer
0.895
219906AC1-017 C
Solar/Wind Harmer
0.249
213815MOSER1-3
Adder
3.966
213815MOSER1-3
Adder
3.966
219607WPEMNERT C
Solar/Wind Harmer
0.468
219304NAMERICA C
Solar/Wind Harmer
0.346
213535CROYDN11
Adder
11.421
214067T20SOLAR
Solar/Wind Harmer
0.281
20720828JCB_W4-025
Solar/Wind Harmer
0.503
20636128O CRK C2
Adder
7.147
207459AE1-142 C O1
Solar/Wind Harmer
1.168
232920IR10
Adder
4.126
232432Z2-076 GEN
Solar/Wind Harmer
0.172
233901CHERRYDALE C
Solar/Wind Harmer
1.468
232912OH NUG1
Adder
11.528
232913OH NUG2
Adder
11.375
233940AF2-379 C
Solar/Wind Harmer
0.243
971195AH1-057 GEN
Solar/Wind Harmer
1.272
233955AB2-172 GEN
Solar/Wind Harmer
6.513
232813VAUGHN
Adder
0.766
231906DC3 NUG
Adder
18.089
231902DC CT7
Adder
14.461
231907DC10
Adder
4.516
233968AD2-076_GEN
Solar/Wind Harmer
8.571
970597AG2-380 GEN
Solar/Wind Harmer
5.382
233915AB1-141 GEN
Solar/Wind Harmer
1.275
231919CHRIST1
Adder
5.581
231920CHRIST2
Adder
5.457
970453AG2-297 GEN
Solar/Wind Harmer
3.177
972141AH1-641 GEN
Solar/Wind Harmer
3.295
230422AE1-104_GEN1
Solar/Wind Harmer
38.61
230425AE1-104_GEN2
Solar/Wind Harmer
38.61
230430AE1-229_GEN
Solar/Wind Harmer
32.785
964001AG1-254 GEN
Solar/Wind Harmer
8.341
228728W1-130C
Solar/Wind Harmer
0.759
227927V4-067C
Solar/Wind Harmer
0.226
230407AD2-065 C
Solar/Wind Harmer
0.15
230434AG1-499 GEN
Solar/Wind Harmer
0.661
219137THOSOLAR C
Solar/Wind Harmer
1.369
219258KINSLEYDEP C
Solar/Wind Harmer
0.365
213942SCHUYLKILL
Adder
3.988
213942SCHUYLKILL
Adder
3.049
213957STHWK3-4
Adder
3.049
213957STHWK3-4
Adder
3.049
213561DLWR9-10
Adder
3.976
213561DLWR9-10
Adder
3.041
219615MILLCREEK C
Solar/Wind Harmer
0.267
219610FLORENCE C
Solar/Wind Harmer
1.547
219224BRL12CT4
Adder
9.97
213611FALLS1-3
Adder
3.931
213611FALLS1-3
Adder
3.931
20720728JCB_W1-129
Solar/Wind Harmer
0.331
20715028HAN_X4-015
Solar/Wind Harmer
0.331
207487AE2-000G4
Solar/Wind Harmer
34.936
207497AE2-000G2
Solar/Wind Harmer
34.936
207500AE2-000G1
Solar/Wind Harmer
34.936
207507AE2-000G3
Solar/Wind Harmer
34.936
963401AG1-189 GEN
Solar/Wind Harmer
2.521
970025AG2-016 GEN
Solar/Wind Harmer
3.141
971189AH1-054 GEN
Solar/Wind Harmer
1.308
207445AB1-138_GEN
Solar/Wind Harmer
0.641
219620RIDERU C
Solar/Wind Harmer
0.062
20714428HOW_X1-037
Solar/Wind Harmer
1.363
20720628TIN_W1-124
Solar/Wind Harmer
1.098
20716228APLW2-078
Solar/Wind Harmer
0.975
971521AH1-258 GEN
Solar/Wind Harmer
2.985
20635928PARLN3&4
Adder
8.151
218526CNTRALGAS2 C
Solar/Wind Harmer
0.407
20675528CPH_W2-050
Solar/Wind Harmer
0.631
20673828FLE_V3-070
Solar/Wind Harmer
0.512
20676128MHD_W3-029
Solar/Wind Harmer
0.524
218449LINSOLAR C
Solar/Wind Harmer
1.105
20676428JCR_X2-075
Solar/Wind Harmer
0.375
217167KRNY_14
Adder
10.196
217086KRNY_131
Adder
10.109
217147KRNY_1212
Adder
9.698
217147KRNY_1212
Adder
9.525
217146KRNY_1234
Adder
9.503
217146KRNY_1234
Adder
9.438
964851AG1-348 GEN
Solar/Wind Harmer
1.491
971009AG2-626 GEN
Solar/Wind Harmer
1.788
207408W3-077 C
Solar/Wind Harmer
0.552
20675128HRM_W1-127
Solar/Wind Harmer
0.185
20462827N BANGR8
Adder
0.781
961261AF2-417 GEN
Solar/Wind Harmer
1.055
209026WIENIPP4
Adder
5.604
209027LOR2_Q27
Solar/Wind Harmer
4.673
212266LOR1
Solar/Wind Harmer
1.239
209029WAYMART-WD
Solar/Wind Harmer
2.676
209054AE2-059 GEN
Solar/Wind Harmer
1.689
959431AF2-234 GEN
Solar/Wind Harmer
1.982
964051AG1-259 GEN
Solar/Wind Harmer
1.329
964061AG1-260 GEN
Solar/Wind Harmer
1.329
959421AF2-233 GEN
Solar/Wind Harmer
0.991
20486527WR_V4-052
Adder
1.063
208862AG1-362 C
Solar/Wind Harmer
0.769
209067AE2-060 GEN
Solar/Wind Harmer
1.327
20390726Y2-042
Adder
2.772
200917MEHOOPANY_G
Solar/Wind Harmer
3.649
20334726NME_Y1-047
Adder
2.453
203926AA2-133 GEN
Adder
2.266
205951AE1-129_GEN
Solar/Wind Harmer
7.69
3138216PACIFIC
Solar/Wind Helper
0.054
3141426STAFORD
Solar/Wind Helper
0.066
315651AD1-115 GEN
Solar/Wind Helper
1.009
316164AC1-076 GEN
Solar/Wind Helper
1.421
238169AE2-226 GEN1
Solar/Wind Helper
0.722
238170AE2-226 GEN2
Solar/Wind Helper
0.722
316468AD1-105 GEN
Solar/Wind Helper
1.37
3141813NORNECK
Solar/Wind Helper
0.282
3141783LANCAST
Solar/Wind Helper
0.168
3141783LANCAST
Solar/Wind Helper
0.112
3138133OCRAN
Solar/Wind Helper
0.084
3141913WHIT STONE
Solar/Wind Helper
0.279
316059AD1-063 C
Solar/Wind Helper
0.282
3143873LANEXA
Solar/Wind Helper
0.167
957601AF2-054 GEN
Solar/Wind Helper
0.374
3141873WAN 176
Solar/Wind Helper
0.056
316233AE1-074 FULL
Solar/Wind Helper
0.426
957831AF2-077 GEN
Solar/Wind Helper
0.374
316382AG1-145 C
Solar/Wind Helper
0.373
316159AE1-175 C
Solar/Wind Helper
0.421
315697AD1-025 GEN
Solar/Wind Helper
3.155
315839AE2-212 C
Solar/Wind Helper
0.371
316236AE1-162_GEN
Solar/Wind Helper
0.369
3143316POE
Solar/Wind Helper
1.084
316258AE1-075 C
Solar/Wind Helper
0.376
316405AF2-144 C
Solar/Wind Helper
0.314
316316AC1-027 C
Solar/Wind Helper
0.431
316018AA1-139 ULT2
Solar/Wind Helper
1.173
313526AB2-022
Solar/Wind Helper
0.414
20628028LAKEHURS
Adder
1.053
20714828MDF_W3-079
Solar/Wind Harmer
0.338
219817TRENTONSOL C
Solar/Wind Harmer
1.217
20641628MLH_W1-032
Solar/Wind Harmer
0.324
20742028HF_AC1-207
Solar/Wind Harmer
0.864
217197RE CRAN C
Solar/Wind Harmer
0.591
218438BLK ROCK C
Solar/Wind Harmer
0.15
924131AB2-057 GEN
Solar/Wind Harmer
1.132
20635028RRCT1&2
Adder
12.775
20635128RRCT3&4
Adder
12.332
20635128RRCT3&4
Adder
10.757
218418LINDEN_G5
Adder
18.878
218419LINDEN_G6
Adder
18.878
972260AH1-715 GEN1
Adder
15.117
20675428EAM_W2-061
Solar/Wind Harmer
0.207
219036LINDEN_G7
Adder
18.371
219035LINDEN_G8
Adder
18.109
972261AH1-715 GEN2
Adder
17.586
217081WEATEXAS C
Solar/Wind Harmer
0.094
217202FBANKSOLAR C
Solar/Wind Harmer
0.081
217201HACKENSOLA C
Solar/Wind Harmer
0.08
972237AH1-703 GEN
Adder
11.098
217206BARNGR HS C
Solar/Wind Harmer
0.034
217086KRNY_131
Adder
10.217
217083KRNY_132
Adder
10.131
217204WCALDSOLAR C
Solar/Wind Harmer
0.08
20674328GAR_V4-001
Solar/Wind Harmer
0.12
20674828DL_W4-046
Solar/Wind Harmer
0.705
207471AF2-354 C
Solar/Wind Harmer
0.559
20634528N27_Y2-018
Solar/Wind Harmer
0.294
20675928HOL_W4-097
Solar/Wind Harmer
0.142
20465127PORT CT
Adder
4.342
961541AF2-445A GEN
Solar/Wind Harmer
3.357
209010PEIP 1
Adder
3.664
209010PEIP 1
Adder
0.537
961431AF2-434 GEN
Solar/Wind Harmer
1.014
946751AF1-339 GEN
Solar/Wind Harmer
0.993
209130AF1-271A GEN
Solar/Wind Harmer
2.787
20465527S.RDG CT
Adder
2.634
316411AF1-147_GEN1
Solar/Wind Helper
1.093
316006AB2-029 C
Solar/Wind Helper
0.146
316045AC1-158 PL2
Solar/Wind Helper
5.325
316450AC1-158 RIC
Solar/Wind Helper
0.444
966001AG1-469 GEN
Solar/Wind Helper
0.309
238147AE2-230_GEN1
Solar/Wind Helper
0.493
238148AE2-230_GEN2
Solar/Wind Helper
0.493
238149AF1-291A_GEN
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.379
237061AD1-155 GEN
Solar/Wind Helper
1.762
316487AF1-042 GEN
Solar/Wind Helper
0.284
316312AB1-027
Solar/Wind Helper
0.535
315666AE1-190 GEN
Solar/Wind Helper
0.376
316156AD2-030 GEN
Solar/Wind Helper
0.422
3143526WINTERP
Solar/Wind Helper
1.45
315976AC1-164 GENA
Solar/Wind Helper
3.599
316169AC1-164_GENC
Solar/Wind Helper
3.109
3142946ENON
Solar/Wind Helper
0.028
316240AF1-291 C
Solar/Wind Helper
0.372
316033AB2-134 GEN
Solar/Wind Helper
0.955
316294AC1-161 GEN
Solar/Wind Helper
5.018
316313AB2-026
Solar/Wind Helper
0.418
316185AD1-033 GEN
Solar/Wind Helper
1.286
3145506HICKORY
Solar/Wind Helper
1.09
3145506HICKORY
Solar/Wind Helper
0.654
3145506HICKORY
Solar/Wind Helper
0.163
316349AD2-085 GEN
Solar/Wind Helper
1.247
316339AD2-160 GEN
Solar/Wind Helper
1.039
316388AE2-253 GEN
Solar/Wind Helper
1.039
235020AA1-095 C
Solar/Wind Helper
0.051
3137176SLIGO L2192
Solar/Wind Helper
1.082
3130086AYDLETT
Solar/Wind Helper
1.087
3146386ELIZ CT
Solar/Wind Helper
0.271
316431W1029_GEN1
Solar/Wind Helper
1.092
316433W1029_GEN2
Solar/Wind Helper
1.092
316435W1029_GEN3
Solar/Wind Helper
1.092
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.269
3146626S HERTFORD
Solar/Wind Helper
0.269
3144356SAPONY
Solar/Wind Helper
0.483
316315AB2-025 C
Solar/Wind Helper
0.411
232426Y1-080 FULL
Solar/Wind Harmer
0.249
232902EASTMUNI
Adder
16.941
234012AE2-112_GEN
Solar/Wind Harmer
2.974
972251AH1-710 GEN
Adder
57.798
233944AB2-135 GEN
Solar/Wind Harmer
6.752
233918AB1-142 GEN
Solar/Wind Harmer
1.275
231918WEST 1
Adder
4.242
231917EM10
Adder
2.965
228206SHRMN CT
Adder
19.057
228732V1-021 C
Adder
0.217
228260V4-054C
Solar/Wind Harmer
1.177
970997AG2-616 GEN
Solar/Wind Harmer
10.984
228729W2-030 C
Solar/Wind Harmer
0.659
228400MICK 1CT
Adder
13.439
213497CHSTR7-9
Adder
3.071
213497CHSTR7-9
Adder
3.071
219766PARADISE C
Solar/Wind Harmer
0.355
219686LUMSOLAR_N C
Solar/Wind Harmer
0.228
219907AC1-030 C
Solar/Wind Harmer
0.156
213958STHWK5-6
Adder
3.049
213560DLW11-12
Adder
3.041
219348LDSOLAR C
Solar/Wind Harmer
0.668
219222BRL12CT2
Adder
9.97
213611FALLS1-3
Adder
3.931
214194N WALES4
Adder
0.948
20716028EGP_W2-019
Solar/Wind Harmer
0.515
207522AF2-254 C
Solar/Wind Harmer
1.593
20717128DIX_Z2-102
Solar/Wind Harmer
1.465
20715828PEM_W1-120
Solar/Wind Harmer
0.592
963711AG1-223 GEN
Solar/Wind Harmer
1.636
20714528FRN_Y2-051
Solar/Wind Harmer
0.326
219276PARKLANDSO C
Solar/Wind Harmer
0.51
219680HOPEWELLV C1
Solar/Wind Harmer
0.084
20715228NPK_W1-113
Solar/Wind Harmer
0.474
20720528MAN_W1-024
Solar/Wind Harmer
0.28
20720428HOL_W1-112
Solar/Wind Harmer
0.381
20635828PARLN1&2
Adder
8.151
20635028RRCT1&2
Adder
12.975
218524CNTRALGAS1 C
Solar/Wind Harmer
0.406
218440SUMMTASSOC C
Solar/Wind Harmer
0.141
218428ETC SOLAR C
Solar/Wind Harmer
0.039
219908AB1-139 C
Solar/Wind Harmer
0.418
219919AE1-041 FULL
Solar/Wind Harmer
0.044
972275AH1-722 GEN
Adder
34.705
20673628F1S_V4-069
Solar/Wind Harmer
0.197
207528AF2-192 GEN
Solar/Wind Harmer
1.396
217209CENTRL HS C
Solar/Wind Harmer
0.049
217186ESSEX_G9
Adder
4.33
217121ECCF
Adder
0.476
217083KRNY_132
Adder
10.196
20671828STAW2-080
Solar/Wind Harmer
0.115
217208PARK ELE C
Solar/Wind Harmer
0.028
20676728BRNX1-095
Solar/Wind Harmer
0.193
966261AG1-495 GEN
Solar/Wind Harmer
3.838
207439AE1-081 C O1
Solar/Wind Harmer
0.065
20676328BVR_Y1-020
Solar/Wind Harmer
0.361
20674628WNG_W3-110
Solar/Wind Harmer
0.441
207530AG1-191 GEN
Solar/Wind Harmer
1.503
20676228FRD_X1-012
Solar/Wind Harmer
0.646
20675828AU_W4-064
Solar/Wind Harmer
0.189
20674928WA_W3-044
Solar/Wind Harmer
0.525
971519AH1-257 GEN
Solar/Wind Harmer
2.751
20675728RH_W2-091
Solar/Wind Harmer
0.658
207518AF1-320_GEN
Solar/Wind Harmer
3.988
207484AF2-139 C O1
Solar/Wind Harmer
0.551
20465127PORT CT
Adder
3.272
208909MACR G3
Adder
173.367
211065PSPA IPP
Solar/Wind Harmer
0.487
961301AF2-421 GEN
Solar/Wind Harmer
1.052
963151AG1-164 GEN
Solar/Wind Harmer
1.052
209023WIENIPP1
Adder
11.341
209025WIENIPP3
Adder
5.661
963071AG1-156 GEN
Solar/Wind Harmer
10.329
209010PEIP 1
Adder
0.666
961341AF2-425 GEN
Solar/Wind Harmer
1.016
212507AE2-042_GEN
Solar/Wind Harmer
2.994
946731AF1-337 GEN
Solar/Wind Harmer
0.993
209018SUNBIPCT
Adder
7.383
20465527S.RDG CT
Adder
2.722
209008PAXT IPP
Adder
1.814
209137AF2-361 C
Solar/Wind Harmer
2.564
205967AE2-211_GEN
Solar/Wind Harmer
5.78
941421AE2-139 GEN
Solar/Wind Harmer
2.746
20328326MANOR_T86
Adder
0.126
316415AF1-147_GEN2
Solar/Wind Helper
1.093
238175AF1-290_GEN
Solar/Wind Helper
0.162
316447AC1-158 HLD
Solar/Wind Helper
3.662
316044AC1-158 PL1
Solar/Wind Helper
1.664
3147666LOUISA
Solar/Wind Helper
1.16
316192AB2-158 GEN
Solar/Wind Helper
1.953
238152AF2-075_GEN
Solar/Wind Helper
0.704
316337AD2-073 GEN
Solar/Wind Helper
0.431
964211AG1-282 GEN
Solar/Wind Helper
0.38
3141726DUNNSVL
Solar/Wind Helper
1.127
316404AE1-155 C
Solar/Wind Helper
2.406
3142416OLDCHRC
Solar/Wind Helper
0.728
3142416OLDCHRC
Solar/Wind Helper
0.279
3138133OCRAN
Solar/Wind Helper
0.168
3141766HARMONY
Solar/Wind Helper
0.056
315662AE1-191 GEN
Solar/Wind Helper
1.504
316280AD1-041 GEN
Solar/Wind Helper
0.94
3143526WINTERP
Solar/Wind Helper
1.45
315975AC1-164 GENB
Solar/Wind Helper
0.106
3142433PROV 92
Solar/Wind Helper
1.115
3143226MDLTHAN
Solar/Wind Helper
0.279
3142543TWELFTH
Solar/Wind Helper
0.027
316132AB2-190 GEN1
Solar/Wind Helper
1.581
315671AE2-027_GEN
Solar/Wind Helper
2.231
316369SG1_INVT
Solar/Wind Helper
1.33
3145336SMITFLD
Solar/Wind Helper
1.096
315773AC2-141 GEN
Solar/Wind Helper
5.904
316381AD1-082 GEN
Solar/Wind Helper
1.419
316375AC2-012 GEN
Solar/Wind Helper
0.719
316036AC1-147 C
Solar/Wind Helper
0.417
316072AD1-144
Solar/Wind Helper
0.312
3146456SLIGO L269
Solar/Wind Helper
0.272
319010AE1-072 C
Solar/Wind Helper
3.113
23777901MDS_W4-102
Solar/Wind Helper
0.171
3146516WINFALL
Solar/Wind Helper
0.874
3146516WINFALL
Solar/Wind Helper
0.27
315611Z1-036_GEN2
Solar/Wind Helper
1.475
3130156CHOWAN
Solar/Wind Helper
0.268
315816AE2-034 GEN
Solar/Wind Helper
1.218
3145663CRESWEL
Solar/Wind Helper
0.744
3146776BUCKING
Solar/Wind Helper
0.106
315737AD1-076 GEN
Solar/Wind Helper
2.587
3146926FARMVIL
Solar/Wind Helper
0.158
316023GEN1_S
Solar/Wind Helper
1.006
3146206CASHIE
Solar/Wind Helper
0.263
3145893MURPHYS
Solar/Wind Helper
1.053
3146173TUNIS
Solar/Wind Helper
0.263
3147983MERCK5
Solar/Wind Helper
0.105
200200DELTA2 CT1
50/50
3.904
200193DELTA CT2
50/50
2.181
200203Y1-065-STG
50/50
7.82
200055ROCKSP 4
50/50
2.824
233973AC2-185 C
Solar/Wind Harmer
7.08
970695AG2-447 GEN
Solar/Wind Harmer
4.684
233939AC1-091 C
Solar/Wind Harmer
3.505
233972AC1-094 C
Solar/Wind Harmer
2.814
233987AB2-037 GEN
Solar/Wind Harmer
14.844
232434Z2-077 GEN
Solar/Wind Harmer
0.326
232406W1-004 FULL
Solar/Wind Harmer
1.305
232914OH NUG3
Adder
11.528
232916OH NUG5
Adder
11.528
232921TASLEY2G
Adder
6.738
233923SMA
Solar/Wind Harmer
4.769
233997TMININ_4.2
Solar/Wind Harmer
1.301
232907VN8
Adder
39.184
233964AF2-378 GEN
Solar/Wind Harmer
0.166
233950AC2-186 GEN
Solar/Wind Harmer
0.733
232417X3-008 C
Solar/Wind Harmer
1.466
232422X3-066 FULL
Solar/Wind Harmer
0.323
233933AB2-153 GEN
Solar/Wind Harmer
1.449
233935AB2-179 C
Solar/Wind Harmer
3.169
228711V2-041C
Solar/Wind Harmer
0.691
230415AB2-049 C
Solar/Wind Harmer
0.217
219623KINSLEYBEA C
Solar/Wind Harmer
0.483
219291REEVESSOUT C
Solar/Wind Harmer
0.068
219921AF1-264
Solar/Wind Harmer
0.163
218660EHAMPSOLAR C
Solar/Wind Harmer
0.197
213497CHSTR7-9
Adder
3.071
219688LUMSOLAR_S C
Solar/Wind Harmer
0.228
219914AD2-027 C
Solar/Wind Harmer
0.675
219236SOUTHERNHQ C
Solar/Wind Harmer
0.076
213958STHWK5-6
Adder
3.049
213560DLW11-12
Adder
3.041
213815MOSER1-3
Adder
3.966
219221BRL12CT1
Adder
9.97
219223BRL12CT3
Adder
9.97
20716428NHV_W2-082
Solar/Wind Harmer
1.973
959561AF2-247 GEN
Solar/Wind Harmer
0.539
20715728PEM_W1-119
Solar/Wind Harmer
0.592
20636028O CRK C1
Adder
7.839
963391AG1-188 GEN
Solar/Wind Harmer
4.155
20714928UPF_X1-085
Solar/Wind Harmer
0.451
971667AH1-334 GEN
Solar/Wind Harmer
3.043
219114HARTZY_C
Solar/Wind Harmer
0.923
219727YARDVSOLFA C
Solar/Wind Harmer
1.007
219918AC2-009 C
Solar/Wind Harmer
0.028
207454AA2-184 E
Solar/Wind Harmer
1.102
219612MATRIX C
Solar/Wind Harmer
0.203
20716928W4-060COL
Solar/Wind Harmer
0.783
20635828PARLN1&2
Adder
3.692
20635928PARLN3&4
Adder
3.692
3132123MT JACKSON
Solar/Wind Helper
0.834
315614AA2-178 GEN
Solar/Wind Helper
1.624
3146776BUCKING
Solar/Wind Helper
1.059
3146776BUCKING
Solar/Wind Helper
0.086
316365GEN2_N
Solar/Wind Helper
1.006
3145893MURPHYS
Solar/Wind Helper
0.378
3145893MURPHYS
Solar/Wind Helper
0.474
3146173TUNIS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
316097T157 G90
Solar/Wind Helper
1.209
316140AB2-099
Solar/Wind Helper
0.1
313506AB2-031 GEN
Solar/Wind Helper
1.188
3147133PAMPLIN
Solar/Wind Helper
0.261
3147133PAMPLIN
Solar/Wind Helper
0.209
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.156
3145593CAROLNA
Solar/Wind Helper
0.26
3145593CAROLNA
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.777
3145933PARMELE
Solar/Wind Helper
0.514
3145933PARMELE
Solar/Wind Helper
0.257
316237AB2-079_GEN
Solar/Wind Helper
0.346
316005AA1-067
Solar/Wind Helper
0.293
315687AD1-152 GEN
Solar/Wind Helper
1.377
3146843MT LREL
Solar/Wind Helper
0.253
3146843MT LREL
Solar/Wind Helper
0.253
316049AB1-081 GEN
Solar/Wind Helper
1.54
316118AC1-105 GEN
Solar/Wind Helper
0.979
238221AF1-254 C O1
Solar/Wind Helper
0.248
316248AF1-058 C
Solar/Wind Helper
0.337
237080AD1-060 GEN
Solar/Wind Helper
0.298
270013AE1-250 PV
Solar/Wind Helper
0.847
3146486SUNBURY
Solar/Wind Helper
0.271
3146486SUNBURY
Solar/Wind Helper
0.271
3145176PASQUOTANK
Solar/Wind Helper
0.168
315800Z1-036_GEN1
Solar/Wind Helper
1.475
3130156CHOWAN
Solar/Wind Helper
0.268
3130156CHOWAN
Solar/Wind Helper
0.268
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
316322AB2-045
Solar/Wind Helper
0.296
3130546PLYMOUTH
Solar/Wind Helper
0.264
315732AD1-074 GEN1
Solar/Wind Helper
3.025
315733AD1-074 GEN2
Solar/Wind Helper
3.025
3146206CASHIE
Solar/Wind Helper
0.263
3145893MURPHYS
Solar/Wind Helper
0.711
3145893MURPHYS
Solar/Wind Helper
0.263
316463AE2-346 GEN
Solar/Wind Helper
0.24
3145513AHOSKIE
Solar/Wind Helper
0.118
961941AG1-037 GEN
Solar/Wind Helper
0.088
3145513AHOSKIE
Solar/Wind Helper
0.262
946281AF1-292 GEN
Solar/Wind Helper
0.263
3146043SEABORD
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.523
3145683EARLEYS
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.262
3137643SOCKMAN
Solar/Wind Helper
1.041
316426AA2-053 GEN
Solar/Wind Helper
1.489
316174AB2-169 GEN
Solar/Wind Helper
0.665
316486AD2-202 GEN
Solar/Wind Helper
0.373
3148133STUARTS
Solar/Wind Helper
0.156
3148013FISHERV
Solar/Wind Helper
0.149
3145796HORNRTN
Solar/Wind Helper
0.829
3145796HORNRTN
Solar/Wind Helper
0.104
3144303KENBRDG
Solar/Wind Helper
0.207
3146033SCOT NK
Solar/Wind Helper
1.035
316210AC1-098 GEN
Solar/Wind Helper
2.082
316274AC1-208 GEN
Solar/Wind Helper
1.57
316238AB2-078_GEN
Solar/Wind Helper
0.346
316239AB2-077_GEN
Solar/Wind Helper
0.346
3145746EVERETS
Solar/Wind Helper
1.017
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
316327AA2-057 GEN
Solar/Wind Helper
1.457
226929AD2-058 GEN
Solar/Wind Helper
0.099
3145573BETHELC
Solar/Wind Helper
0.253
3145573BETHELC
Solar/Wind Helper
0.253
315616AA1-038_C
Solar/Wind Helper
1.138
3148463FAIRFLD
Solar/Wind Helper
0.251
3147173SINAI
Solar/Wind Helper
0.25
3147243WELCO
Solar/Wind Helper
0.156
270455AD2-022 GEN
Solar/Wind Helper
1.372
270457AD2-023 GEN
Solar/Wind Helper
0.904
270197AD1-017 GEN1
Solar/Wind Helper
1.224
3156021HOLLOMANSOL
Solar/Wind Helper
2.001
3145683EARLEYS
Solar/Wind Helper
0.262
315607AA1-063A GEN
Solar/Wind Helper
1.497
316087AB2-174 GEN
Solar/Wind Helper
1.832
3146263WOODLND
Solar/Wind Helper
0.261
3145963POPLR C
Solar/Wind Helper
0.26
3145823KELFORD
Solar/Wind Helper
0.26
3145783HORNRTN
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.855
3145796HORNRTN
Solar/Wind Helper
0.259
316034AC1-036 C
Solar/Wind Helper
0.272
315785AD2-033 C
Solar/Wind Helper
3.019
316129AC1-054 GEN
Solar/Wind Helper
1.278
316131AB2-060 GEN
Solar/Wind Helper
1.571
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
316494AC1-189 GEN
Solar/Wind Helper
1.554
3146233WITAKRS
Solar/Wind Helper
1.009
961671AG1-007 GEN
Solar/Wind Helper
0.182
3146083TARBORO
Solar/Wind Helper
0.253
316359AB2-059 GEN
Solar/Wind Helper
1.926
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.202
238108AE1-109 GEN1
Solar/Wind Helper
0.094
238110AE1-109 GEN3
Solar/Wind Helper
0.094
964991AG1-363 GEN
Solar/Wind Helper
3.5
3147123OTTER R
Solar/Wind Helper
0.138
3147312GRETNA
Solar/Wind Helper
0.183
3146802CHATHAM
Solar/Wind Helper
0.172
270016AE1-250 BESS
Solar/Wind Helper
0.847
270018AE2-047 C O1
Solar/Wind Helper
0.792
217213AMBOY SO C
Solar/Wind Harmer
0.139
219249CENTRALDIV C
Solar/Wind Harmer
0.044
207442AE1-156 GEN
Solar/Wind Harmer
0.816
20673728F2S_V4-070
Solar/Wind Harmer
0.197
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217169METRODIV C
Solar/Wind Harmer
0.044
217194REDH C
Solar/Wind Harmer
0.54
20674528F3S_W2-016
Solar/Wind Harmer
1.541
207510AF2-138 C
Solar/Wind Harmer
1.944
207511W3-106 GEN
Solar/Wind Harmer
0.361
971007AG2-625 GEN
Solar/Wind Harmer
2.804
207437AD2-070 GEN
Solar/Wind Harmer
0.328
20671928W4-073
Solar/Wind Harmer
0.471
20466127PORT 5CT
Adder
28.881
20674128FR_U2-059
Solar/Wind Harmer
0.201
20633028GILCT9
Adder
30.817
20465427SHAW CT
Adder
4.196
209116AE2-175 GEN
Solar/Wind Harmer
4.448
211065PSPA IPP
Solar/Wind Harmer
0.487
963161AG1-165 GEN
Solar/Wind Harmer
1.052
209025WIENIPP3
Adder
5.546
970095AG2-074 GEN
Solar/Wind Harmer
6.541
208972BECR K09
Solar/Wind Harmer
1.098
961331AF2-424 GEN
Solar/Wind Harmer
1.016
961421AF2-433 GEN
Solar/Wind Harmer
1.014
957921AF2-086 GEN
Solar/Wind Harmer
0.986
209142AF1-226 GEN
Solar/Wind Harmer
5.869
209093AE2-110 GEN
Solar/Wind Harmer
2.535
209120AE2-241 GEN
Solar/Wind Harmer
3.354
205941AD2-115 GEN
Solar/Wind Harmer
0.936
946691AF1-333 GEN
Solar/Wind Harmer
0.993
946741AF1-338 GEN
Solar/Wind Harmer
0.993
209071AE2-133 GEN
Solar/Wind Harmer
1.677
972221AH1-695 GEN
Adder
123.568
3141196NOKESVL
Solar/Wind Helper
1.257
3132273ORANGE
Solar/Wind Helper
0.058
3147666LOUISA
Solar/Wind Helper
0.667
966881AG1-559 GEN
Solar/Wind Helper
0.389
316223AC1-118
Solar/Wind Helper
0.435
3141906WESTMOR
Solar/Wind Helper
0.114
23546401DTGZ2-030
Solar/Wind Helper
0.089
316077AC2-138 C
Solar/Wind Helper
0.266
316473AC1-191 GEN
Solar/Wind Helper
1.72
316484AD2-074 GEN
Solar/Wind Helper
0.542
316075AC2-137 C
Solar/Wind Helper
0.426
3142946ENON
Solar/Wind Helper
0.093
316458AB2-190 GEN2
Solar/Wind Helper
1.581
3145336SMITFLD
Solar/Wind Helper
0.11
3144536CHRHLND
Solar/Wind Helper
0.041
3144873MCLAUGH
Solar/Wind Helper
0.007
3142956BIRDNECK
Solar/Wind Helper
0.184
316017AA1-139 ULT1
Solar/Wind Helper
1.247
3146456SLIGO L269
Solar/Wind Helper
0.272
316305AF2-043 C
Solar/Wind Helper
0.366
316246AF1-032 C
Solar/Wind Helper
0.311
316320Y1-086
Solar/Wind Helper
0.122
316321Z2-027
Solar/Wind Helper
0.413
3146516WINFALL
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.269
3145273HOLLAND
Solar/Wind Helper
0.202
3146376EDENTON
Solar/Wind Helper
0.268
3146776BUCKING
Solar/Wind Helper
0.095
315735AD1-075 GEN1
Solar/Wind Helper
1.513
3146926FARMVIL
Solar/Wind Helper
0.158
3146206CASHIE
Solar/Wind Helper
0.263
3145893MURPHYS
Solar/Wind Helper
0.094
3145893MURPHYS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
316095T157 G97
Solar/Wind Helper
1.209
315821AE2-092 GEN
Solar/Wind Helper
2.439
942461AE2-259 GEN
Solar/Wind Helper
1.765
966621AG1-532 GEN
Solar/Wind Helper
0.238
316499AE2-029_GEN
Solar/Wind Helper
0.88
3146263WOODLND
Solar/Wind Helper
0.261
316181AB2-040 GEN
Solar/Wind Helper
1.877
3147133PAMPLIN
Solar/Wind Helper
0.818
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3147043LAWRENC
Solar/Wind Helper
0.156
3145963POPLR C
Solar/Wind Helper
0.26
316190AA2-174 GEN
Solar/Wind Helper
0.018
316011AB1-132 GEN
Solar/Wind Helper
2.806
316317KELFORD C
Solar/Wind Helper
0.234
3145823KELFORD
Solar/Wind Helper
0.26
316478AD1-087 GEN
Solar/Wind Helper
1.273
3148013FISHERV
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
1.036
3145796HORNRTN
Solar/Wind Helper
0.259
316212AC1-099_GEN
Solar/Wind Helper
1.157
3145933PARMELE
Solar/Wind Helper
0.257
23583801GRNGAP
Solar/Wind Helper
4.397
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
270494AE1-108_GEN
Solar/Wind Helper
3.414
316420AA1-050 GEN
Solar/Wind Helper
1.459
3146233WITAKRS
Solar/Wind Helper
0.273
3146233WITAKRS
Solar/Wind Helper
0.172
3146073TAR RVR
Solar/Wind Helper
0.253
3146083TARBORO
Solar/Wind Helper
0.253
3138543CONSLDL
Solar/Wind Helper
0.167
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.252
238109AE1-109 GEN2
Solar/Wind Helper
0.094
316003AC1-222 GEN
Solar/Wind Helper
1.078
227287AC2-120 GEN
Solar/Wind Helper
0.335
226910AB2-157 C
Solar/Wind Helper
0.014
316222AC1-221 GEN
Solar/Wind Helper
1.39
316283AC2-100 C
Solar/Wind Helper
1.294
316123AC1-075 GEN
Solar/Wind Helper
1.47
237038AE2-054 C
Solar/Wind Helper
0.23
235067AD1-061 GEN
Solar/Wind Helper
0.375
316197AC1-042 GEN
Solar/Wind Helper
0.216
3147312GRETNA
Solar/Wind Helper
0.046
237085AD2-009_GEN
Solar/Wind Helper
1.36
237002AB1-128_GEN
Solar/Wind Helper
0.364
270173AC1-122 GEN
Solar/Wind Helper
1.533
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.981
VTFLTFEXP_VFT->PJM
CMTX
148.636
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.489
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.554
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.577
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.195
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
56.425
CBM NorthLTFEXP_CBM-N->PJM
CBM
83.076
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.99 %
Rating:4150.0 MVA
Rating Type:B
MVA to Mitigate:4357.18
MW Contribution:
4.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
22.891
200201DELTA2 CT2
50/50
3.904
200034PCHBTM 2
50/50
22.744
200205Y1-065-CTG2
50/50
4.513
233971AC1-093 C
Solar/Wind Harmer
3.326
232899W1-062
Adder
12.553
232410W1-006 C
Solar/Wind Harmer
1.304
232918OH NUG7
Adder
11.448
232905CHERITON_25
Adder
3.201
232926CRISFLD1
Adder
2.561
231940T-011
Adder
0.973
234015AF2-250 C
Solar/Wind Harmer
0.157
232428Y3-058 C
Solar/Wind Harmer
1.087
233994AC2-023 GEN
Solar/Wind Harmer
3.501
233946AB2-136 GEN
Solar/Wind Harmer
5.197
234036AF2-325 C
Solar/Wind Harmer
1.194
233952AC2-187 GEN
Solar/Wind Harmer
1.465
233954AC2-188 GEN
Solar/Wind Harmer
1.465
234041AC1-190 GEN
Solar/Wind Harmer
11.667
232910NRG_G1
Adder
11.214
233984AB2-036 GEN
Solar/Wind Harmer
16.137
232424Y1-079 C
Solar/Wind Harmer
0.728
234014AF1-036_GEN
Solar/Wind Harmer
3.497
232436AB1-176 C
Solar/Wind Harmer
0.296
233930AB2-032 GEN
Solar/Wind Harmer
1.073
233982AB2-133 GEN
Solar/Wind Harmer
6.269
228201CARL#2CT
Adder
7.885
228200CARL#1CT
Adder
7.5
228251CARLLS#4
Adder
0.723
230433AD2-135 GEN
Solar/Wind Harmer
0.116
228351V2-046C
Solar/Wind Harmer
2.305
230511AF1-262
Solar/Wind Harmer
0.209
228754AB1-001 C
Solar/Wind Harmer
0.159
228307PCLP GT
Adder
13.801
972233AH1-701 GEN
Adder
4.776
219272CLEANLIGHT C
Solar/Wind Harmer
0.206
219904AC1-010 C
Solar/Wind Harmer
0.426
219287REEVESEAST C
Solar/Wind Harmer
1.515
213589EDDYSTN4
Adder
89.642
213587EDDYSTN3
Adder
89.636
219912AD2-042 GEN
Solar/Wind Harmer
0.895
219906AC1-017 C
Solar/Wind Harmer
0.249
213815MOSER1-3
Adder
3.966
213815MOSER1-3
Adder
3.966
219607WPEMNERT C
Solar/Wind Harmer
0.468
219304NAMERICA C
Solar/Wind Harmer
0.346
213535CROYDN11
Adder
11.419
214067T20SOLAR
Solar/Wind Harmer
0.281
20720828JCB_W4-025
Solar/Wind Harmer
0.502
20636128O CRK C2
Adder
7.146
207459AE1-142 C O1
Solar/Wind Harmer
1.168
20628028LAKEHURS
Adder
1.053
20714828MDF_W3-079
Solar/Wind Harmer
0.338
219817TRENTONSOL C
Solar/Wind Harmer
1.217
20641628MLH_W1-032
Solar/Wind Harmer
0.324
20742028HF_AC1-207
Solar/Wind Harmer
0.864
217197RE CRAN C
Solar/Wind Harmer
0.591
218438BLK ROCK C
Solar/Wind Harmer
0.15
924131AB2-057 GEN
Solar/Wind Harmer
1.132
20635028RRCT1&2
Adder
12.774
20635128RRCT3&4
Adder
12.33
20635128RRCT3&4
Adder
10.756
218418LINDEN_G5
Adder
18.876
218419LINDEN_G6
Adder
18.876
972260AH1-715 GEN1
Adder
15.115
20675428EAM_W2-061
Solar/Wind Harmer
0.207
219036LINDEN_G7
Adder
18.369
219035LINDEN_G8
Adder
18.107
972261AH1-715 GEN2
Adder
17.584
217081WEATEXAS C
Solar/Wind Harmer
0.094
217202FBANKSOLAR C
Solar/Wind Harmer
0.081
217201HACKENSOLA C
Solar/Wind Harmer
0.08
972237AH1-703 GEN
Adder
11.097
217206BARNGR HS C
Solar/Wind Harmer
0.034
217086KRNY_131
Adder
10.216
217083KRNY_132
Adder
10.13
217204WCALDSOLAR C
Solar/Wind Harmer
0.08
20674328GAR_V4-001
Solar/Wind Harmer
0.12
20674828DL_W4-046
Solar/Wind Harmer
0.705
207471AF2-354 C
Solar/Wind Harmer
0.559
20634528N27_Y2-018
Solar/Wind Harmer
0.294
20675928HOL_W4-097
Solar/Wind Harmer
0.142
20465127PORT CT
Adder
4.342
961541AF2-445A GEN
Solar/Wind Harmer
3.357
209010PEIP 1
Adder
3.663
209010PEIP 1
Adder
0.537
961431AF2-434 GEN
Solar/Wind Harmer
1.014
946751AF1-339 GEN
Solar/Wind Harmer
0.993
209130AF1-271A GEN
Solar/Wind Harmer
2.787
20465527S.RDG CT
Adder
2.634
316411AF1-147_GEN1
Solar/Wind Helper
1.093
316006AB2-029 C
Solar/Wind Helper
0.146
316045AC1-158 PL2
Solar/Wind Helper
5.324
316450AC1-158 RIC
Solar/Wind Helper
0.444
966001AG1-469 GEN
Solar/Wind Helper
0.309
238147AE2-230_GEN1
Solar/Wind Helper
0.493
238148AE2-230_GEN2
Solar/Wind Helper
0.493
238149AF1-291A_GEN
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.379
237061AD1-155 GEN
Solar/Wind Helper
1.762
316487AF1-042 GEN
Solar/Wind Helper
0.284
316312AB1-027
Solar/Wind Helper
0.535
315666AE1-190 GEN
Solar/Wind Helper
0.376
316156AD2-030 GEN
Solar/Wind Helper
0.422
3143526WINTERP
Solar/Wind Helper
1.45
315976AC1-164 GENA
Solar/Wind Helper
3.598
316169AC1-164_GENC
Solar/Wind Helper
3.108
3142946ENON
Solar/Wind Helper
0.028
316240AF1-291 C
Solar/Wind Helper
0.372
316033AB2-134 GEN
Solar/Wind Helper
0.955
316294AC1-161 GEN
Solar/Wind Helper
5.017
316313AB2-026
Solar/Wind Helper
0.418
316185AD1-033 GEN
Solar/Wind Helper
1.286
3145506HICKORY
Solar/Wind Helper
1.09
3145506HICKORY
Solar/Wind Helper
0.654
3145506HICKORY
Solar/Wind Helper
0.163
316349AD2-085 GEN
Solar/Wind Helper
1.247
316339AD2-160 GEN
Solar/Wind Helper
1.039
316388AE2-253 GEN
Solar/Wind Helper
1.039
235020AA1-095 C
Solar/Wind Helper
0.051
3137176SLIGO L2192
Solar/Wind Helper
1.082
3130086AYDLETT
Solar/Wind Helper
1.087
3146386ELIZ CT
Solar/Wind Helper
0.271
316431W1029_GEN1
Solar/Wind Helper
1.092
316433W1029_GEN2
Solar/Wind Helper
1.092
316435W1029_GEN3
Solar/Wind Helper
1.092
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.269
3146626S HERTFORD
Solar/Wind Helper
0.269
3144356SAPONY
Solar/Wind Helper
0.483
316315AB2-025 C
Solar/Wind Helper
0.411
3132123MT JACKSON
Solar/Wind Helper
0.834
315614AA2-178 GEN
Solar/Wind Helper
1.624
3146776BUCKING
Solar/Wind Helper
1.059
3146776BUCKING
Solar/Wind Helper
0.086
316365GEN2_N
Solar/Wind Helper
1.006
3145893MURPHYS
Solar/Wind Helper
0.378
3145893MURPHYS
Solar/Wind Helper
0.474
3146173TUNIS
Solar/Wind Helper
0.262
3146173TUNIS
Solar/Wind Helper
0.262
316097T157 G90
Solar/Wind Helper
1.209
316140AB2-099
Solar/Wind Helper
0.1
313506AB2-031 GEN
Solar/Wind Helper
1.188
3147133PAMPLIN
Solar/Wind Helper
0.261
3147133PAMPLIN
Solar/Wind Helper
0.209
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.156
3145593CAROLNA
Solar/Wind Helper
0.26
3145593CAROLNA
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.777
3145933PARMELE
Solar/Wind Helper
0.514
3145933PARMELE
Solar/Wind Helper
0.257
316237AB2-079_GEN
Solar/Wind Helper
0.346
316005AA1-067
Solar/Wind Helper
0.293
315687AD1-152 GEN
Solar/Wind Helper
1.377
3146843MT LREL
Solar/Wind Helper
0.253
3146843MT LREL
Solar/Wind Helper
0.253
316049AB1-081 GEN
Solar/Wind Helper
1.54
316118AC1-105 GEN
Solar/Wind Helper
0.979
238221AF1-254 C O1
Solar/Wind Helper
0.248
316248AF1-058 C
Solar/Wind Helper
0.337
237080AD1-060 GEN
Solar/Wind Helper
0.298
270013AE1-250 PV
Solar/Wind Helper
0.847
200202DELTA2 ST
50/50
6.611
200195DELTA ST
50/50
3.37
200052ROCKSP 1
50/50
2.839
200053ROCKSP 2
50/50
2.784
232904IR4
Adder
105.525
232920IR10
Adder
4.124
232432Z2-076 GEN
Solar/Wind Harmer
0.172
233901CHERRYDALE C
Solar/Wind Harmer
1.467
232912OH NUG1
Adder
11.524
232913OH NUG2
Adder
11.371
233940AF2-379 C
Solar/Wind Harmer
0.243
971195AH1-057 GEN
Solar/Wind Harmer
1.272
233955AB2-172 GEN
Solar/Wind Harmer
6.511
232813VAUGHN
Adder
0.766
231906DC3 NUG
Adder
18.083
231902DC CT7
Adder
14.456
231907DC10
Adder
4.514
233968AD2-076_GEN
Solar/Wind Harmer
8.568
970597AG2-380 GEN
Solar/Wind Harmer
5.38
233915AB1-141 GEN
Solar/Wind Harmer
1.274
231919CHRIST1
Adder
5.58
231920CHRIST2
Adder
5.456
970453AG2-297 GEN
Solar/Wind Harmer
3.176
972141AH1-641 GEN
Solar/Wind Harmer
3.295
230422AE1-104_GEN1
Solar/Wind Harmer
38.601
230425AE1-104_GEN2
Solar/Wind Harmer
38.601
230430AE1-229_GEN
Solar/Wind Harmer
32.777
964001AG1-254 GEN
Solar/Wind Harmer
8.339
228728W1-130C
Solar/Wind Harmer
0.759
227927V4-067C
Solar/Wind Harmer
0.226
230407AD2-065 C
Solar/Wind Harmer
0.15
230434AG1-499 GEN
Solar/Wind Harmer
0.661
219137THOSOLAR C
Solar/Wind Harmer
1.369
219258KINSLEYDEP C
Solar/Wind Harmer
0.365
213942SCHUYLKILL
Adder
3.987
213942SCHUYLKILL
Adder
3.049
213957STHWK3-4
Adder
3.049
213957STHWK3-4
Adder
3.049
213561DLWR9-10
Adder
3.976
213561DLWR9-10
Adder
3.04
219615MILLCREEK C
Solar/Wind Harmer
0.267
219610FLORENCE C
Solar/Wind Harmer
1.547
219224BRL12CT4
Adder
9.969
213611FALLS1-3
Adder
3.931
213611FALLS1-3
Adder
3.931
20720728JCB_W1-129
Solar/Wind Harmer
0.331
20715028HAN_X4-015
Solar/Wind Harmer
0.331
207487AE2-000G4
Solar/Wind Harmer
34.93
207497AE2-000G2
Solar/Wind Harmer
34.93
207500AE2-000G1
Solar/Wind Harmer
34.93
207507AE2-000G3
Solar/Wind Harmer
34.93
963401AG1-189 GEN
Solar/Wind Harmer
2.52
970025AG2-016 GEN
Solar/Wind Harmer
3.14
971189AH1-054 GEN
Solar/Wind Harmer
1.307
207445AB1-138_GEN
Solar/Wind Harmer
0.641
219620RIDERU C
Solar/Wind Harmer
0.062
20714428HOW_X1-037
Solar/Wind Harmer
1.363
20720628TIN_W1-124
Solar/Wind Harmer
1.098
20716228APLW2-078
Solar/Wind Harmer
0.975
971521AH1-258 GEN
Solar/Wind Harmer
2.985
20635928PARLN3&4
Adder
8.15
218526CNTRALGAS2 C
Solar/Wind Harmer
0.407
20675528CPH_W2-050
Solar/Wind Harmer
0.631
20673828FLE_V3-070
Solar/Wind Harmer
0.512
20676128MHD_W3-029
Solar/Wind Harmer
0.524
218449LINSOLAR C
Solar/Wind Harmer
1.105
20676428JCR_X2-075
Solar/Wind Harmer
0.375
217167KRNY_14
Adder
10.195
217086KRNY_131
Adder
10.108
217147KRNY_1212
Adder
9.697
217147KRNY_1212
Adder
9.524
217146KRNY_1234
Adder
9.502
217146KRNY_1234
Adder
9.437
964851AG1-348 GEN
Solar/Wind Harmer
1.491
971009AG2-626 GEN
Solar/Wind Harmer
1.788
207408W3-077 C
Solar/Wind Harmer
0.552
20675128HRM_W1-127
Solar/Wind Harmer
0.185
20462827N BANGR8
Adder
0.781
961261AF2-417 GEN
Solar/Wind Harmer
1.055
209026WIENIPP4
Adder
5.603
209027LOR2_Q27
Solar/Wind Harmer
4.673
212266LOR1
Solar/Wind Harmer
1.239
209029WAYMART-WD
Solar/Wind Harmer
2.676
209054AE2-059 GEN
Solar/Wind Harmer
1.689
959431AF2-234 GEN
Solar/Wind Harmer
1.982
964051AG1-259 GEN
Solar/Wind Harmer
1.329
964061AG1-260 GEN
Solar/Wind Harmer
1.329
959421AF2-233 GEN
Solar/Wind Harmer
0.991
20486527WR_V4-052
Adder
1.063
208862AG1-362 C
Solar/Wind Harmer
0.769
209067AE2-060 GEN
Solar/Wind Harmer
1.327
20390726Y2-042
Adder
2.772
200917MEHOOPANY_G
Solar/Wind Harmer
3.649
20334726NME_Y1-047
Adder
2.453
205951AE1-129_GEN
Solar/Wind Harmer
7.691
203926AA2-133 GEN
Adder
2.266
3138216PACIFIC
Solar/Wind Helper
0.054
3141426STAFORD
Solar/Wind Helper
0.066
315651AD1-115 GEN
Solar/Wind Helper
1.009
316164AC1-076 GEN
Solar/Wind Helper
1.421
238169AE2-226 GEN1
Solar/Wind Helper
0.722
238170AE2-226 GEN2
Solar/Wind Helper
0.722
316468AD1-105 GEN
Solar/Wind Helper
1.37
3141813NORNECK
Solar/Wind Helper
0.282
3141783LANCAST
Solar/Wind Helper
0.168
3141783LANCAST
Solar/Wind Helper
0.112
3138133OCRAN
Solar/Wind Helper
0.084
3141913WHIT STONE
Solar/Wind Helper
0.279
316059AD1-063 C
Solar/Wind Helper
0.282
3143873LANEXA
Solar/Wind Helper
0.167
957601AF2-054 GEN
Solar/Wind Helper
0.374
3141873WAN 176
Solar/Wind Helper
0.056
316233AE1-074 FULL
Solar/Wind Helper
0.426
957831AF2-077 GEN
Solar/Wind Helper
0.374
316382AG1-145 C
Solar/Wind Helper
0.373
316159AE1-175 C
Solar/Wind Helper
0.421
315697AD1-025 GEN
Solar/Wind Helper
3.154
315839AE2-212 C
Solar/Wind Helper
0.371
316236AE1-162_GEN
Solar/Wind Helper
0.369
3143316POE
Solar/Wind Helper
1.084
316258AE1-075 C
Solar/Wind Helper
0.376
316405AF2-144 C
Solar/Wind Helper
0.314
316316AC1-027 C
Solar/Wind Helper
0.431
316018AA1-139 ULT2
Solar/Wind Helper
1.173
313526AB2-022
Solar/Wind Helper
0.414
3146486SUNBURY
Solar/Wind Helper
0.271
3146486SUNBURY
Solar/Wind Helper
0.271
3145176PASQUOTANK
Solar/Wind Helper
0.168
315800Z1-036_GEN1
Solar/Wind Helper
1.475
3130156CHOWAN
Solar/Wind Helper
0.268
3130156CHOWAN
Solar/Wind Helper
0.268
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
316322AB2-045
Solar/Wind Helper
0.296
3130546PLYMOUTH
Solar/Wind Helper
0.264
315732AD1-074 GEN1
Solar/Wind Helper
3.025
315733AD1-074 GEN2
Solar/Wind Helper
3.025
3146206CASHIE
Solar/Wind Helper
0.263
3145893MURPHYS
Solar/Wind Helper
0.711
3145893MURPHYS
Solar/Wind Helper
0.263
316463AE2-346 GEN
Solar/Wind Helper
0.24
3145513AHOSKIE
Solar/Wind Helper
0.117
961941AG1-037 GEN
Solar/Wind Helper
0.088
3145513AHOSKIE
Solar/Wind Helper
0.262
946281AF1-292 GEN
Solar/Wind Helper
0.263
3146043SEABORD
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.523
3145683EARLEYS
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.262
3137643SOCKMAN
Solar/Wind Helper
1.041
316426AA2-053 GEN
Solar/Wind Helper
1.489
316174AB2-169 GEN
Solar/Wind Helper
0.665
316486AD2-202 GEN
Solar/Wind Helper
0.373
3148133STUARTS
Solar/Wind Helper
0.156
3148013FISHERV
Solar/Wind Helper
0.149
3145796HORNRTN
Solar/Wind Helper
0.829
3145796HORNRTN
Solar/Wind Helper
0.104
3144303KENBRDG
Solar/Wind Helper
0.207
3146033SCOT NK
Solar/Wind Helper
1.034
316210AC1-098 GEN
Solar/Wind Helper
2.082
316274AC1-208 GEN
Solar/Wind Helper
1.57
316238AB2-078_GEN
Solar/Wind Helper
0.346
316239AB2-077_GEN
Solar/Wind Helper
0.346
3145746EVERETS
Solar/Wind Helper
1.017
3145746EVERETS
Solar/Wind Helper
0.255
3145746EVERETS
Solar/Wind Helper
0.255
3145746EVERETS
Solar/Wind Helper
0.255
316327AA2-057 GEN
Solar/Wind Helper
1.457
226929AD2-058 GEN
Solar/Wind Helper
0.099
3145573BETHELC
Solar/Wind Helper
0.253
3145573BETHELC
Solar/Wind Helper
0.253
315616AA1-038_C
Solar/Wind Helper
1.137
3148463FAIRFLD
Solar/Wind Helper
0.251
3147173SINAI
Solar/Wind Helper
0.25
3147243WELCO
Solar/Wind Helper
0.156
270455AD2-022 GEN
Solar/Wind Helper
1.372
270457AD2-023 GEN
Solar/Wind Helper
0.904
270197AD1-017 GEN1
Solar/Wind Helper
1.224
200192DELTA CT1
50/50
2.181
200194DELTA CT3
50/50
2.181
200204Y1-065-CTG1
50/50
4.513
200054ROCKSP 3
50/50
2.872
232901NORTHST
Adder
10.877
233970AC1-092 C
Solar/Wind Harmer
3.503
234033AF1-007_GEN
Solar/Wind Harmer
48.544
232900DEMECSMY
Adder
12.041
972177AH1-672 GEN
Solar/Wind Harmer
17.531
232404W1-003 C
Solar/Wind Harmer
1.304
232408W1-005 C
Solar/Wind Harmer
1.304
232917OH NUG6
Adder
11.473
232915OH NUG4
Adder
11.448
233996TM1833_GEN
Solar/Wind Harmer
1.3
233998TM1NIN_3.36
Solar/Wind Harmer
1.3
232919VN10
Adder
3.66
232426Y1-080 FULL
Solar/Wind Harmer
0.249
232902EASTMUNI
Adder
16.935
234012AE2-112_GEN
Solar/Wind Harmer
2.973
972251AH1-710 GEN
Adder
57.78
233944AB2-135 GEN
Solar/Wind Harmer
6.75
233918AB1-142 GEN
Solar/Wind Harmer
1.274
231918WEST 1
Adder
4.241
231917EM10
Adder
2.964
228206SHRMN CT
Adder
19.053
228732V1-021 C
Adder
0.217
228260V4-054C
Solar/Wind Harmer
1.177
970997AG2-616 GEN
Solar/Wind Harmer
10.982
228729W2-030 C
Solar/Wind Harmer
0.659
228400MICK 1CT
Adder
13.436
213497CHSTR7-9
Adder
3.07
213497CHSTR7-9
Adder
3.07
219766PARADISE C
Solar/Wind Harmer
0.355
219686LUMSOLAR_N C
Solar/Wind Harmer
0.228
219907AC1-030 C
Solar/Wind Harmer
0.156
213958STHWK5-6
Adder
3.049
213560DLW11-12
Adder
3.04
219348LDSOLAR C
Solar/Wind Harmer
0.668
219222BRL12CT2
Adder
9.969
213611FALLS1-3
Adder
3.931
214194N WALES4
Adder
0.948
20716028EGP_W2-019
Solar/Wind Harmer
0.515
207522AF2-254 C
Solar/Wind Harmer
1.592
20717128DIX_Z2-102
Solar/Wind Harmer
1.464
20715828PEM_W1-120
Solar/Wind Harmer
0.592
963711AG1-223 GEN
Solar/Wind Harmer
1.636
20714528FRN_Y2-051
Solar/Wind Harmer
0.326
219276PARKLANDSO C
Solar/Wind Harmer
0.51
219680HOPEWELLV C1
Solar/Wind Harmer
0.084
20715228NPK_W1-113
Solar/Wind Harmer
0.474
20720528MAN_W1-024
Solar/Wind Harmer
0.28
20720428HOL_W1-112
Solar/Wind Harmer
0.381
20635828PARLN1&2
Adder
8.15
20635028RRCT1&2
Adder
12.973
218524CNTRALGAS1 C
Solar/Wind Harmer
0.406
218440SUMMTASSOC C
Solar/Wind Harmer
0.141
218428ETC SOLAR C
Solar/Wind Harmer
0.039
219908AB1-139 C
Solar/Wind Harmer
0.418
219919AE1-041 FULL
Solar/Wind Harmer
0.044
972275AH1-722 GEN
Adder
34.701
20673628F1S_V4-069
Solar/Wind Harmer
0.197
207528AF2-192 GEN
Solar/Wind Harmer
1.396
217209CENTRL HS C
Solar/Wind Harmer
0.049
217186ESSEX_G9
Adder
4.329
217121ECCF
Adder
0.476
217083KRNY_132
Adder
10.195
20671828STAW2-080
Solar/Wind Harmer
0.115
217208PARK ELE C
Solar/Wind Harmer
0.028
20676728BRNX1-095
Solar/Wind Harmer
0.193
966261AG1-495 GEN
Solar/Wind Harmer
3.838
207439AE1-081 C O1
Solar/Wind Harmer
0.065
20676328BVR_Y1-020
Solar/Wind Harmer
0.361
20674628WNG_W3-110
Solar/Wind Harmer
0.441
207530AG1-191 GEN
Solar/Wind Harmer
1.503
20676228FRD_X1-012
Solar/Wind Harmer
0.646
20675828AU_W4-064
Solar/Wind Harmer
0.189
20674928WA_W3-044
Solar/Wind Harmer
0.525
971519AH1-257 GEN
Solar/Wind Harmer
2.751
20675728RH_W2-091
Solar/Wind Harmer
0.657
207518AF1-320_GEN
Solar/Wind Harmer
3.988
207484AF2-139 C O1
Solar/Wind Harmer
0.551
20465127PORT CT
Adder
3.272
208909MACR G3
Adder
173.357
211065PSPA IPP
Solar/Wind Harmer
0.487
961301AF2-421 GEN
Solar/Wind Harmer
1.052
963151AG1-164 GEN
Solar/Wind Harmer
1.052
209023WIENIPP1
Adder
11.34
209025WIENIPP3
Adder
5.661
963071AG1-156 GEN
Solar/Wind Harmer
10.328
209010PEIP 1
Adder
0.666
961341AF2-425 GEN
Solar/Wind Harmer
1.016
212507AE2-042_GEN
Solar/Wind Harmer
2.994
946731AF1-337 GEN
Solar/Wind Harmer
0.993
209018SUNBIPCT
Adder
7.383
20465527S.RDG CT
Adder
2.722
209008PAXT IPP
Adder
1.814
209137AF2-361 C
Solar/Wind Harmer
2.564
205967AE2-211_GEN
Solar/Wind Harmer
5.78
941421AE2-139 GEN
Solar/Wind Harmer
2.746
20328326MANOR_T86
Adder
0.126
316415AF1-147_GEN2
Solar/Wind Helper
1.093
238175AF1-290_GEN
Solar/Wind Helper
0.162
316447AC1-158 HLD
Solar/Wind Helper
3.661
316044AC1-158 PL1
Solar/Wind Helper
1.664
3147666LOUISA
Solar/Wind Helper
1.16
316192AB2-158 GEN
Solar/Wind Helper
1.952
238152AF2-075_GEN
Solar/Wind Helper
0.704
316337AD2-073 GEN
Solar/Wind Helper
0.431
964211AG1-282 GEN
Solar/Wind Helper
0.38
3141726DUNNSVL
Solar/Wind Helper
1.126
316404AE1-155 C
Solar/Wind Helper
2.405
3142416OLDCHRC
Solar/Wind Helper
0.728
3142416OLDCHRC
Solar/Wind Helper
0.279
3138133OCRAN
Solar/Wind Helper
0.168
3141766HARMONY
Solar/Wind Helper
0.056
315662AE1-191 GEN
Solar/Wind Helper
1.504
316280AD1-041 GEN
Solar/Wind Helper
0.94
3143526WINTERP
Solar/Wind Helper
1.45
315975AC1-164 GENB
Solar/Wind Helper
0.106
3142433PROV 92
Solar/Wind Helper
1.115
3143226MDLTHAN
Solar/Wind Helper
0.279
3142543TWELFTH
Solar/Wind Helper
0.027
316132AB2-190 GEN1
Solar/Wind Helper
1.581
315671AE2-027_GEN
Solar/Wind Helper
2.23
316369SG1_INVT
Solar/Wind Helper
1.33
3145336SMITFLD
Solar/Wind Helper
1.096
315773AC2-141 GEN
Solar/Wind Helper
5.904
316381AD1-082 GEN
Solar/Wind Helper
1.419
316375AC2-012 GEN
Solar/Wind Helper
0.719
316036AC1-147 C
Solar/Wind Helper
0.417
316072AD1-144
Solar/Wind Helper
0.312
3146456SLIGO L269
Solar/Wind Helper
0.272
319010AE1-072 C
Solar/Wind Helper
3.113
23777901MDS_W4-102
Solar/Wind Helper
0.171
3146516WINFALL
Solar/Wind Helper
0.874
3146516WINFALL
Solar/Wind Helper
0.27
315611Z1-036_GEN2
Solar/Wind Helper
1.475
3130156CHOWAN
Solar/Wind Helper
0.268
315816AE2-034 GEN
Solar/Wind Helper
1.218
3145663CRESWEL
Solar/Wind Helper
0.744
3146776BUCKING
Solar/Wind Helper
0.106
315737AD1-076 GEN
Solar/Wind Helper
2.587
3146926FARMVIL
Solar/Wind Helper
0.158
316023GEN1_S
Solar/Wind Helper
1.006
3146206CASHIE
Solar/Wind Helper
0.263
3145893MURPHYS
Solar/Wind Helper
1.053
3146173TUNIS
Solar/Wind Helper
0.262
3147983MERCK5
Solar/Wind Helper
0.105
3156021HOLLOMANSOL
Solar/Wind Helper
2
3145683EARLEYS
Solar/Wind Helper
0.262
315607AA1-063A GEN
Solar/Wind Helper
1.496
316087AB2-174 GEN
Solar/Wind Helper
1.831
3146263WOODLND
Solar/Wind Helper
0.261
3145963POPLR C
Solar/Wind Helper
0.26
3145823KELFORD
Solar/Wind Helper
0.26
3145783HORNRTN
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.855
3145796HORNRTN
Solar/Wind Helper
0.259
316034AC1-036 C
Solar/Wind Helper
0.272
315785AD2-033 C
Solar/Wind Helper
3.018
316129AC1-054 GEN
Solar/Wind Helper
1.278
316131AB2-060 GEN
Solar/Wind Helper
1.571
3145746EVERETS
Solar/Wind Helper
0.255
3145746EVERETS
Solar/Wind Helper
0.255
316494AC1-189 GEN
Solar/Wind Helper
1.554
3146233WITAKRS
Solar/Wind Helper
1.008
961671AG1-007 GEN
Solar/Wind Helper
0.182
3146083TARBORO
Solar/Wind Helper
0.253
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.202
316359AB2-059 GEN
Solar/Wind Helper
1.925
238108AE1-109 GEN1
Solar/Wind Helper
0.094
238110AE1-109 GEN3
Solar/Wind Helper
0.094
964991AG1-363 GEN
Solar/Wind Helper
3.499
3147123OTTER R
Solar/Wind Helper
0.138
3147312GRETNA
Solar/Wind Helper
0.183
3146802CHATHAM
Solar/Wind Helper
0.172
270016AE1-250 BESS
Solar/Wind Helper
0.847
270018AE2-047 C O1
Solar/Wind Helper
0.792
200200DELTA2 CT1
50/50
3.904
200193DELTA CT2
50/50
2.181
200203Y1-065-STG
50/50
7.816
200055ROCKSP 4
50/50
2.823
233973AC2-185 C
Solar/Wind Harmer
7.078
970695AG2-447 GEN
Solar/Wind Harmer
4.682
233939AC1-091 C
Solar/Wind Harmer
3.503
233972AC1-094 C
Solar/Wind Harmer
2.813
233987AB2-037 GEN
Solar/Wind Harmer
14.839
232434Z2-077 GEN
Solar/Wind Harmer
0.326
232406W1-004 FULL
Solar/Wind Harmer
1.304
232914OH NUG3
Adder
11.524
232916OH NUG5
Adder
11.524
232921TASLEY2G
Adder
6.735
233923SMA
Solar/Wind Harmer
4.768
233997TMININ_4.2
Solar/Wind Harmer
1.3
232907VN8
Adder
39.17
233964AF2-378 GEN
Solar/Wind Harmer
0.166
233950AC2-186 GEN
Solar/Wind Harmer
0.733
232417X3-008 C
Solar/Wind Harmer
1.465
232422X3-066 FULL
Solar/Wind Harmer
0.323
233933AB2-153 GEN
Solar/Wind Harmer
1.448
233935AB2-179 C
Solar/Wind Harmer
3.168
228711V2-041C
Solar/Wind Harmer
0.69
230415AB2-049 C
Solar/Wind Harmer
0.217
219623KINSLEYBEA C
Solar/Wind Harmer
0.483
219291REEVESSOUT C
Solar/Wind Harmer
0.068
219921AF1-264
Solar/Wind Harmer
0.163
218660EHAMPSOLAR C
Solar/Wind Harmer
0.197
213497CHSTR7-9
Adder
3.07
219688LUMSOLAR_S C
Solar/Wind Harmer
0.228
219914AD2-027 C
Solar/Wind Harmer
0.675
219236SOUTHERNHQ C
Solar/Wind Harmer
0.076
213958STHWK5-6
Adder
3.049
213560DLW11-12
Adder
3.04
213815MOSER1-3
Adder
3.966
219221BRL12CT1
Adder
9.969
219223BRL12CT3
Adder
9.969
20716428NHV_W2-082
Solar/Wind Harmer
1.973
959561AF2-247 GEN
Solar/Wind Harmer
0.539
20715728PEM_W1-119
Solar/Wind Harmer
0.592
20636028O CRK C1
Adder
7.838
963391AG1-188 GEN
Solar/Wind Harmer
4.154
20714928UPF_X1-085
Solar/Wind Harmer
0.45
971667AH1-334 GEN
Solar/Wind Harmer
3.043
219114HARTZY_C
Solar/Wind Harmer
0.923
219727YARDVSOLFA C
Solar/Wind Harmer
1.007
219918AC2-009 C
Solar/Wind Harmer
0.028
207454AA2-184 E
Solar/Wind Harmer
1.102
219612MATRIX C
Solar/Wind Harmer
0.202
20716928W4-060COL
Solar/Wind Harmer
0.783
20635828PARLN1&2
Adder
3.691
20635928PARLN3&4
Adder
3.691
217213AMBOY SO C
Solar/Wind Harmer
0.139
219249CENTRALDIV C
Solar/Wind Harmer
0.044
207442AE1-156 GEN
Solar/Wind Harmer
0.816
20673728F2S_V4-070
Solar/Wind Harmer
0.197
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217169METRODIV C
Solar/Wind Harmer
0.044
217194REDH C
Solar/Wind Harmer
0.54
20674528F3S_W2-016
Solar/Wind Harmer
1.541
207510AF2-138 C
Solar/Wind Harmer
1.944
207511W3-106 GEN
Solar/Wind Harmer
0.361
971007AG2-625 GEN
Solar/Wind Harmer
2.804
207437AD2-070 GEN
Solar/Wind Harmer
0.328
20671928W4-073
Solar/Wind Harmer
0.471
20466127PORT 5CT
Adder
28.879
20674128FR_U2-059
Solar/Wind Harmer
0.201
20633028GILCT9
Adder
30.815
20465427SHAW CT
Adder
4.196
209116AE2-175 GEN
Solar/Wind Harmer
4.448
211065PSPA IPP
Solar/Wind Harmer
0.487
963161AG1-165 GEN
Solar/Wind Harmer
1.052
209025WIENIPP3
Adder
5.546
970095AG2-074 GEN
Solar/Wind Harmer
6.541
208972BECR K09
Solar/Wind Harmer
1.098
961331AF2-424 GEN
Solar/Wind Harmer
1.016
961421AF2-433 GEN
Solar/Wind Harmer
1.014
957921AF2-086 GEN
Solar/Wind Harmer
0.986
209142AF1-226 GEN
Solar/Wind Harmer
5.869
209093AE2-110 GEN
Solar/Wind Harmer
2.535
209120AE2-241 GEN
Solar/Wind Harmer
3.354
205941AD2-115 GEN
Solar/Wind Harmer
0.936
946691AF1-333 GEN
Solar/Wind Harmer
0.993
946741AF1-338 GEN
Solar/Wind Harmer
0.993
209071AE2-133 GEN
Solar/Wind Harmer
1.677
972221AH1-695 GEN
Adder
123.573
3141196NOKESVL
Solar/Wind Helper
1.257
3132273ORANGE
Solar/Wind Helper
0.058
3147666LOUISA
Solar/Wind Helper
0.667
966881AG1-559 GEN
Solar/Wind Helper
0.389
316223AC1-118
Solar/Wind Helper
0.435
3141906WESTMOR
Solar/Wind Helper
0.114
23546401DTGZ2-030
Solar/Wind Helper
0.089
316077AC2-138 C
Solar/Wind Helper
0.266
316473AC1-191 GEN
Solar/Wind Helper
1.72
316484AD2-074 GEN
Solar/Wind Helper
0.542
316075AC2-137 C
Solar/Wind Helper
0.426
3142946ENON
Solar/Wind Helper
0.093
316458AB2-190 GEN2
Solar/Wind Helper
1.581
3145336SMITFLD
Solar/Wind Helper
0.11
3144536CHRHLND
Solar/Wind Helper
0.041
3144873MCLAUGH
Solar/Wind Helper
0.007
3142956BIRDNECK
Solar/Wind Helper
0.184
316017AA1-139 ULT1
Solar/Wind Helper
1.247
3146456SLIGO L269
Solar/Wind Helper
0.272
316305AF2-043 C
Solar/Wind Helper
0.366
316246AF1-032 C
Solar/Wind Helper
0.311
316320Y1-086
Solar/Wind Helper
0.122
316321Z2-027
Solar/Wind Helper
0.413
3146516WINFALL
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.269
3145273HOLLAND
Solar/Wind Helper
0.202
3146376EDENTON
Solar/Wind Helper
0.268
3146776BUCKING
Solar/Wind Helper
0.095
315735AD1-075 GEN1
Solar/Wind Helper
1.513
3146926FARMVIL
Solar/Wind Helper
0.158
3146206CASHIE
Solar/Wind Helper
0.263
3145893MURPHYS
Solar/Wind Helper
0.094
3145893MURPHYS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.262
316095T157 G97
Solar/Wind Helper
1.209
315821AE2-092 GEN
Solar/Wind Helper
2.438
942461AE2-259 GEN
Solar/Wind Helper
1.765
966621AG1-532 GEN
Solar/Wind Helper
0.238
316499AE2-029_GEN
Solar/Wind Helper
0.88
3146263WOODLND
Solar/Wind Helper
0.261
316181AB2-040 GEN
Solar/Wind Helper
1.876
3147133PAMPLIN
Solar/Wind Helper
0.818
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3147043LAWRENC
Solar/Wind Helper
0.156
316190AA2-174 GEN
Solar/Wind Helper
0.018
3145963POPLR C
Solar/Wind Helper
0.26
316011AB1-132 GEN
Solar/Wind Helper
2.806
316317KELFORD C
Solar/Wind Helper
0.234
3145823KELFORD
Solar/Wind Helper
0.26
316478AD1-087 GEN
Solar/Wind Helper
1.273
3148013FISHERV
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
1.036
3145796HORNRTN
Solar/Wind Helper
0.259
316212AC1-099_GEN
Solar/Wind Helper
1.156
3145933PARMELE
Solar/Wind Helper
0.257
23583801GRNGAP
Solar/Wind Helper
4.397
3145746EVERETS
Solar/Wind Helper
0.255
3145746EVERETS
Solar/Wind Helper
0.255
270494AE1-108_GEN
Solar/Wind Helper
3.413
316420AA1-050 GEN
Solar/Wind Helper
1.459
3146233WITAKRS
Solar/Wind Helper
0.273
3146233WITAKRS
Solar/Wind Helper
0.172
3146073TAR RVR
Solar/Wind Helper
0.253
3146083TARBORO
Solar/Wind Helper
0.253
3138543CONSLDL
Solar/Wind Helper
0.167
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.252
238109AE1-109 GEN2
Solar/Wind Helper
0.094
316003AC1-222 GEN
Solar/Wind Helper
1.078
227287AC2-120 GEN
Solar/Wind Helper
0.335
226910AB2-157 C
Solar/Wind Helper
0.014
316222AC1-221 GEN
Solar/Wind Helper
1.39
316283AC2-100 C
Solar/Wind Helper
1.294
316123AC1-075 GEN
Solar/Wind Helper
1.469
237038AE2-054 C
Solar/Wind Helper
0.23
235067AD1-061 GEN
Solar/Wind Helper
0.374
316197AC1-042 GEN
Solar/Wind Helper
0.216
3147312GRETNA
Solar/Wind Helper
0.046
237085AD2-009_GEN
Solar/Wind Helper
1.359
237002AB1-128_GEN
Solar/Wind Helper
0.364
270173AC1-122 GEN
Solar/Wind Helper
1.533
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.98
VTFLTFEXP_VFT->PJM
CMTX
148.621
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.489
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.553
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.193
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.574
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
56.418
CBM NorthLTFEXP_CBM-N->PJM
CBM
83.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.65 %
Rating:4150.0 MVA
Rating Type:B
MVA to Mitigate:4342.89
MW Contribution:
4.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
22.955
200201DELTA2 CT2
50/50
3.915
200034PCHBTM 2
50/50
22.824
200205Y1-065-CTG2
50/50
4.53
233971AC1-093 C
Solar/Wind Harmer
3.342
232899W1-062
Adder
12.612
232410W1-006 C
Solar/Wind Harmer
1.311
232918OH NUG7
Adder
11.502
232905CHERITON_25
Adder
3.216
232926CRISFLD1
Adder
2.573
231940T-011
Adder
0.978
234015AF2-250 C
Solar/Wind Harmer
0.158
232428Y3-058 C
Solar/Wind Harmer
1.092
233994AC2-023 GEN
Solar/Wind Harmer
3.518
233946AB2-136 GEN
Solar/Wind Harmer
5.221
234036AF2-325 C
Solar/Wind Harmer
1.2
233952AC2-187 GEN
Solar/Wind Harmer
1.472
233954AC2-188 GEN
Solar/Wind Harmer
1.472
234041AC1-190 GEN
Solar/Wind Harmer
11.722
232910NRG_G1
Adder
11.268
233984AB2-036 GEN
Solar/Wind Harmer
16.216
232424Y1-079 C
Solar/Wind Harmer
0.732
234014AF1-036_GEN
Solar/Wind Harmer
3.515
232436AB1-176 C
Solar/Wind Harmer
0.297
233930AB2-032 GEN
Solar/Wind Harmer
1.078
233982AB2-133 GEN
Solar/Wind Harmer
6.3
228201CARL#2CT
Adder
7.923
228200CARL#1CT
Adder
7.535
228251CARLLS#4
Adder
0.727
230433AD2-135 GEN
Solar/Wind Harmer
0.116
228351V2-046C
Solar/Wind Harmer
2.316
230511AF1-262
Solar/Wind Harmer
0.21
228754AB1-001 C
Solar/Wind Harmer
0.16
228307PCLP GT
Adder
13.868
972233AH1-701 GEN
Adder
4.799
219272CLEANLIGHT C
Solar/Wind Harmer
0.207
219904AC1-010 C
Solar/Wind Harmer
0.428
219287REEVESEAST C
Solar/Wind Harmer
1.523
213589EDDYSTN4
Adder
90.123
213587EDDYSTN3
Adder
90.117
219912AD2-042 GEN
Solar/Wind Harmer
0.899
219906AC1-017 C
Solar/Wind Harmer
0.251
213815MOSER1-3
Adder
3.985
213815MOSER1-3
Adder
3.985
219607WPEMNERT C
Solar/Wind Harmer
0.47
219304NAMERICA C
Solar/Wind Harmer
0.348
213535CROYDN11
Adder
11.476
214067T20SOLAR
Solar/Wind Harmer
0.282
20720828JCB_W4-025
Solar/Wind Harmer
0.505
20636128O CRK C2
Adder
7.18
207459AE1-142 C O1
Solar/Wind Harmer
1.173
20628028LAKEHURS
Adder
1.058
20714828MDF_W3-079
Solar/Wind Harmer
0.34
219817TRENTONSOL C
Solar/Wind Harmer
1.223
20641628MLH_W1-032
Solar/Wind Harmer
0.325
20742028HF_AC1-207
Solar/Wind Harmer
0.868
217197RE CRAN C
Solar/Wind Harmer
0.594
218438BLK ROCK C
Solar/Wind Harmer
0.151
924131AB2-057 GEN
Solar/Wind Harmer
1.138
20635028RRCT1&2
Adder
12.835
20635128RRCT3&4
Adder
12.39
20635128RRCT3&4
Adder
10.808
218418LINDEN_G5
Adder
18.967
218419LINDEN_G6
Adder
18.967
972260AH1-715 GEN1
Adder
15.188
20675428EAM_W2-061
Solar/Wind Harmer
0.208
219036LINDEN_G7
Adder
18.458
219035LINDEN_G8
Adder
18.195
972261AH1-715 GEN2
Adder
17.669
217081WEATEXAS C
Solar/Wind Harmer
0.095
217202FBANKSOLAR C
Solar/Wind Harmer
0.081
217201HACKENSOLA C
Solar/Wind Harmer
0.081
972237AH1-703 GEN
Adder
11.151
217206BARNGR HS C
Solar/Wind Harmer
0.034
217086KRNY_131
Adder
10.266
217083KRNY_132
Adder
10.179
217204WCALDSOLAR C
Solar/Wind Harmer
0.081
20674328GAR_V4-001
Solar/Wind Harmer
0.121
20674828DL_W4-046
Solar/Wind Harmer
0.708
207471AF2-354 C
Solar/Wind Harmer
0.561
20634528N27_Y2-018
Solar/Wind Harmer
0.295
20675928HOL_W4-097
Solar/Wind Harmer
0.143
20465127PORT CT
Adder
4.364
961541AF2-445A GEN
Solar/Wind Harmer
3.372
209010PEIP 1
Adder
3.68
209010PEIP 1
Adder
0.539
961431AF2-434 GEN
Solar/Wind Harmer
1.018
946751AF1-339 GEN
Solar/Wind Harmer
0.997
209130AF1-271A GEN
Solar/Wind Harmer
2.799
20465527S.RDG CT
Adder
2.657
316411AF1-147_GEN1
Solar/Wind Helper
1.095
316006AB2-029 C
Solar/Wind Helper
0.147
316045AC1-158 PL2
Solar/Wind Helper
5.337
316450AC1-158 RIC
Solar/Wind Helper
0.445
966001AG1-469 GEN
Solar/Wind Helper
0.31
238147AE2-230_GEN1
Solar/Wind Helper
0.494
238148AE2-230_GEN2
Solar/Wind Helper
0.494
238149AF1-291A_GEN
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.38
237061AD1-155 GEN
Solar/Wind Helper
1.767
316487AF1-042 GEN
Solar/Wind Helper
0.284
316312AB1-027
Solar/Wind Helper
0.536
315666AE1-190 GEN
Solar/Wind Helper
0.377
316156AD2-030 GEN
Solar/Wind Helper
0.423
3143526WINTERP
Solar/Wind Helper
1.454
315976AC1-164 GENA
Solar/Wind Helper
3.608
316169AC1-164_GENC
Solar/Wind Helper
3.117
3142946ENON
Solar/Wind Helper
0.028
316240AF1-291 C
Solar/Wind Helper
0.373
316033AB2-134 GEN
Solar/Wind Helper
0.957
316294AC1-161 GEN
Solar/Wind Helper
5.031
316313AB2-026
Solar/Wind Helper
0.419
316185AD1-033 GEN
Solar/Wind Helper
1.29
3145506HICKORY
Solar/Wind Helper
1.093
3145506HICKORY
Solar/Wind Helper
0.656
3145506HICKORY
Solar/Wind Helper
0.164
316349AD2-085 GEN
Solar/Wind Helper
1.251
316339AD2-160 GEN
Solar/Wind Helper
1.042
316388AE2-253 GEN
Solar/Wind Helper
1.042
235020AA1-095 C
Solar/Wind Helper
0.051
3137176SLIGO L2192
Solar/Wind Helper
1.085
3130086AYDLETT
Solar/Wind Helper
1.09
3146386ELIZ CT
Solar/Wind Helper
0.272
316431W1029_GEN1
Solar/Wind Helper
1.095
316433W1029_GEN2
Solar/Wind Helper
1.095
316435W1029_GEN3
Solar/Wind Helper
1.095
3146516WINFALL
Solar/Wind Helper
0.271
3146516WINFALL
Solar/Wind Helper
0.271
3146516WINFALL
Solar/Wind Helper
0.271
3146626S HERTFORD
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3144356SAPONY
Solar/Wind Helper
0.484
316315AB2-025 C
Solar/Wind Helper
0.413
3132123MT JACKSON
Solar/Wind Helper
0.837
315614AA2-178 GEN
Solar/Wind Helper
1.629
3146776BUCKING
Solar/Wind Helper
1.062
3146776BUCKING
Solar/Wind Helper
0.086
316365GEN2_N
Solar/Wind Helper
1.009
3145893MURPHYS
Solar/Wind Helper
0.379
3145893MURPHYS
Solar/Wind Helper
0.475
316097T157 G90
Solar/Wind Helper
1.213
3146173TUNIS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
316140AB2-099
Solar/Wind Helper
0.1
313506AB2-031 GEN
Solar/Wind Helper
1.192
3147133PAMPLIN
Solar/Wind Helper
0.261
3147133PAMPLIN
Solar/Wind Helper
0.209
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.157
3145593CAROLNA
Solar/Wind Helper
0.261
3145593CAROLNA
Solar/Wind Helper
0.261
3145796HORNRTN
Solar/Wind Helper
0.779
3145933PARMELE
Solar/Wind Helper
0.516
3145933PARMELE
Solar/Wind Helper
0.258
316237AB2-079_GEN
Solar/Wind Helper
0.347
316005AA1-067
Solar/Wind Helper
0.294
315687AD1-152 GEN
Solar/Wind Helper
1.381
3146843MT LREL
Solar/Wind Helper
0.254
3146843MT LREL
Solar/Wind Helper
0.254
316049AB1-081 GEN
Solar/Wind Helper
1.545
316118AC1-105 GEN
Solar/Wind Helper
0.982
238221AF1-254 C O1
Solar/Wind Helper
0.249
316248AF1-058 C
Solar/Wind Helper
0.338
237080AD1-060 GEN
Solar/Wind Helper
0.299
270013AE1-250 PV
Solar/Wind Helper
0.85
200202DELTA2 ST
50/50
6.63
200195DELTA ST
50/50
3.38
200052ROCKSP 1
50/50
2.85
200053ROCKSP 2
50/50
2.794
232904IR4
Adder
106.022
232920IR10
Adder
4.144
232432Z2-076 GEN
Solar/Wind Harmer
0.173
233901CHERRYDALE C
Solar/Wind Harmer
1.474
232912OH NUG1
Adder
11.579
232913OH NUG2
Adder
11.425
233940AF2-379 C
Solar/Wind Harmer
0.244
971195AH1-057 GEN
Solar/Wind Harmer
1.278
233955AB2-172 GEN
Solar/Wind Harmer
6.542
232813VAUGHN
Adder
0.769
231906DC3 NUG
Adder
18.172
231902DC CT7
Adder
14.527
231907DC10
Adder
4.537
233968AD2-076_GEN
Solar/Wind Harmer
8.611
970597AG2-380 GEN
Solar/Wind Harmer
5.407
233915AB1-141 GEN
Solar/Wind Harmer
1.281
231919CHRIST1
Adder
5.609
231920CHRIST2
Adder
5.484
970453AG2-297 GEN
Solar/Wind Harmer
3.191
972141AH1-641 GEN
Solar/Wind Harmer
3.31
230422AE1-104_GEN1
Solar/Wind Harmer
38.785
230425AE1-104_GEN2
Solar/Wind Harmer
38.785
230430AE1-229_GEN
Solar/Wind Harmer
32.935
964001AG1-254 GEN
Solar/Wind Harmer
8.379
228728W1-130C
Solar/Wind Harmer
0.763
227927V4-067C
Solar/Wind Harmer
0.227
230407AD2-065 C
Solar/Wind Harmer
0.151
230434AG1-499 GEN
Solar/Wind Harmer
0.664
219137THOSOLAR C
Solar/Wind Harmer
1.375
219258KINSLEYDEP C
Solar/Wind Harmer
0.367
213942SCHUYLKILL
Adder
4.008
213942SCHUYLKILL
Adder
3.065
213957STHWK3-4
Adder
3.065
213957STHWK3-4
Adder
3.065
213561DLWR9-10
Adder
3.996
213561DLWR9-10
Adder
3.056
219615MILLCREEK C
Solar/Wind Harmer
0.268
219610FLORENCE C
Solar/Wind Harmer
1.554
219224BRL12CT4
Adder
10.018
213611FALLS1-3
Adder
3.95
213611FALLS1-3
Adder
3.95
20720728JCB_W1-129
Solar/Wind Harmer
0.332
20715028HAN_X4-015
Solar/Wind Harmer
0.332
207487AE2-000G4
Solar/Wind Harmer
35.098
207497AE2-000G2
Solar/Wind Harmer
35.098
207500AE2-000G1
Solar/Wind Harmer
35.098
207507AE2-000G3
Solar/Wind Harmer
35.098
963401AG1-189 GEN
Solar/Wind Harmer
2.532
970025AG2-016 GEN
Solar/Wind Harmer
3.155
971189AH1-054 GEN
Solar/Wind Harmer
1.314
207445AB1-138_GEN
Solar/Wind Harmer
0.644
219620RIDERU C
Solar/Wind Harmer
0.062
20714428HOW_X1-037
Solar/Wind Harmer
1.37
20720628TIN_W1-124
Solar/Wind Harmer
1.103
20716228APLW2-078
Solar/Wind Harmer
0.979
971521AH1-258 GEN
Solar/Wind Harmer
2.999
20635928PARLN3&4
Adder
8.189
218526CNTRALGAS2 C
Solar/Wind Harmer
0.409
20675528CPH_W2-050
Solar/Wind Harmer
0.634
20673828FLE_V3-070
Solar/Wind Harmer
0.515
20676128MHD_W3-029
Solar/Wind Harmer
0.527
218449LINSOLAR C
Solar/Wind Harmer
1.11
20676428JCR_X2-075
Solar/Wind Harmer
0.377
217167KRNY_14
Adder
10.244
217086KRNY_131
Adder
10.157
217147KRNY_1212
Adder
9.744
217147KRNY_1212
Adder
9.57
217146KRNY_1234
Adder
9.548
217146KRNY_1234
Adder
9.483
964851AG1-348 GEN
Solar/Wind Harmer
1.499
971009AG2-626 GEN
Solar/Wind Harmer
1.797
207408W3-077 C
Solar/Wind Harmer
0.555
20675128HRM_W1-127
Solar/Wind Harmer
0.186
20462827N BANGR8
Adder
0.785
961261AF2-417 GEN
Solar/Wind Harmer
1.059
209026WIENIPP4
Adder
5.629
209027LOR2_Q27
Solar/Wind Harmer
4.694
212266LOR1
Solar/Wind Harmer
1.244
209029WAYMART-WD
Solar/Wind Harmer
2.688
209054AE2-059 GEN
Solar/Wind Harmer
1.696
959431AF2-234 GEN
Solar/Wind Harmer
1.991
964051AG1-259 GEN
Solar/Wind Harmer
1.335
964061AG1-260 GEN
Solar/Wind Harmer
1.335
959421AF2-233 GEN
Solar/Wind Harmer
0.995
20486527WR_V4-052
Adder
1.072
208862AG1-362 C
Solar/Wind Harmer
0.777
209067AE2-060 GEN
Solar/Wind Harmer
1.335
20390726Y2-042
Adder
2.782
200917MEHOOPANY_G
Solar/Wind Harmer
3.66
20334726NME_Y1-047
Adder
2.46
205951AE1-129_GEN
Solar/Wind Harmer
7.804
203926AA2-133 GEN
Adder
2.272
3138216PACIFIC
Solar/Wind Helper
0.054
3141426STAFORD
Solar/Wind Helper
0.066
315651AD1-115 GEN
Solar/Wind Helper
1.012
316164AC1-076 GEN
Solar/Wind Helper
1.425
238169AE2-226 GEN1
Solar/Wind Helper
0.724
238170AE2-226 GEN2
Solar/Wind Helper
0.724
316468AD1-105 GEN
Solar/Wind Helper
1.374
3141813NORNECK
Solar/Wind Helper
0.283
3141783LANCAST
Solar/Wind Helper
0.168
3141783LANCAST
Solar/Wind Helper
0.112
3138133OCRAN
Solar/Wind Helper
0.084
3141913WHIT STONE
Solar/Wind Helper
0.28
316059AD1-063 C
Solar/Wind Helper
0.283
3143873LANEXA
Solar/Wind Helper
0.168
957601AF2-054 GEN
Solar/Wind Helper
0.375
3141873WAN 176
Solar/Wind Helper
0.056
316233AE1-074 FULL
Solar/Wind Helper
0.427
957831AF2-077 GEN
Solar/Wind Helper
0.375
316382AG1-145 C
Solar/Wind Helper
0.374
316159AE1-175 C
Solar/Wind Helper
0.422
315697AD1-025 GEN
Solar/Wind Helper
3.163
315839AE2-212 C
Solar/Wind Helper
0.372
316236AE1-162_GEN
Solar/Wind Helper
0.37
3143316POE
Solar/Wind Helper
1.087
316258AE1-075 C
Solar/Wind Helper
0.377
316405AF2-144 C
Solar/Wind Helper
0.314
316316AC1-027 C
Solar/Wind Helper
0.433
316018AA1-139 ULT2
Solar/Wind Helper
1.177
313526AB2-022
Solar/Wind Helper
0.415
3146486SUNBURY
Solar/Wind Helper
0.272
3146486SUNBURY
Solar/Wind Helper
0.272
3145176PASQUOTANK
Solar/Wind Helper
0.168
315800Z1-036_GEN1
Solar/Wind Helper
1.479
3130156CHOWAN
Solar/Wind Helper
0.268
3130156CHOWAN
Solar/Wind Helper
0.268
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.008
316322AB2-045
Solar/Wind Helper
0.297
3130546PLYMOUTH
Solar/Wind Helper
0.265
315732AD1-074 GEN1
Solar/Wind Helper
3.034
315733AD1-074 GEN2
Solar/Wind Helper
3.034
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
0.713
3145893MURPHYS
Solar/Wind Helper
0.264
316463AE2-346 GEN
Solar/Wind Helper
0.241
3145513AHOSKIE
Solar/Wind Helper
0.118
961941AG1-037 GEN
Solar/Wind Helper
0.089
3145513AHOSKIE
Solar/Wind Helper
0.263
946281AF1-292 GEN
Solar/Wind Helper
0.264
3146043SEABORD
Solar/Wind Helper
0.263
3145683EARLEYS
Solar/Wind Helper
0.525
3145683EARLEYS
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.262
3137643SOCKMAN
Solar/Wind Helper
1.044
316426AA2-053 GEN
Solar/Wind Helper
1.494
316174AB2-169 GEN
Solar/Wind Helper
0.667
316486AD2-202 GEN
Solar/Wind Helper
0.374
3148133STUARTS
Solar/Wind Helper
0.156
3148013FISHERV
Solar/Wind Helper
0.15
3145796HORNRTN
Solar/Wind Helper
0.831
3145796HORNRTN
Solar/Wind Helper
0.104
3144303KENBRDG
Solar/Wind Helper
0.208
3146033SCOT NK
Solar/Wind Helper
1.038
316210AC1-098 GEN
Solar/Wind Helper
2.088
316274AC1-208 GEN
Solar/Wind Helper
1.575
316238AB2-078_GEN
Solar/Wind Helper
0.347
316239AB2-077_GEN
Solar/Wind Helper
0.347
3145746EVERETS
Solar/Wind Helper
1.02
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
316327AA2-057 GEN
Solar/Wind Helper
1.462
226929AD2-058 GEN
Solar/Wind Helper
0.099
3145573BETHELC
Solar/Wind Helper
0.254
3145573BETHELC
Solar/Wind Helper
0.254
315616AA1-038_C
Solar/Wind Helper
1.141
3148463FAIRFLD
Solar/Wind Helper
0.252
3147173SINAI
Solar/Wind Helper
0.251
3147243WELCO
Solar/Wind Helper
0.157
270455AD2-022 GEN
Solar/Wind Helper
1.377
270457AD2-023 GEN
Solar/Wind Helper
0.908
270197AD1-017 GEN1
Solar/Wind Helper
1.229
200192DELTA CT1
50/50
2.188
200194DELTA CT3
50/50
2.188
200204Y1-065-CTG1
50/50
4.53
200054ROCKSP 3
50/50
2.883
232901NORTHST
Adder
10.928
233970AC1-092 C
Solar/Wind Harmer
3.52
234033AF1-007_GEN
Solar/Wind Harmer
48.773
232900DEMECSMY
Adder
12.097
972177AH1-672 GEN
Solar/Wind Harmer
17.613
232404W1-003 C
Solar/Wind Harmer
1.311
232408W1-005 C
Solar/Wind Harmer
1.311
232917OH NUG6
Adder
11.527
232915OH NUG4
Adder
11.502
233996TM1833_GEN
Solar/Wind Harmer
1.306
233998TM1NIN_3.36
Solar/Wind Harmer
1.306
232919VN10
Adder
3.677
232426Y1-080 FULL
Solar/Wind Harmer
0.25
232902EASTMUNI
Adder
17.017
234012AE2-112_GEN
Solar/Wind Harmer
2.987
972251AH1-710 GEN
Adder
58.042
233944AB2-135 GEN
Solar/Wind Harmer
6.783
233918AB1-142 GEN
Solar/Wind Harmer
1.281
231918WEST 1
Adder
4.263
231917EM10
Adder
2.979
228206SHRMN CT
Adder
19.144
228732V1-021 C
Adder
0.218
228260V4-054C
Solar/Wind Harmer
1.183
970997AG2-616 GEN
Solar/Wind Harmer
11.034
228729W2-030 C
Solar/Wind Harmer
0.662
228400MICK 1CT
Adder
13.502
213497CHSTR7-9
Adder
3.087
213497CHSTR7-9
Adder
3.087
219766PARADISE C
Solar/Wind Harmer
0.356
219686LUMSOLAR_N C
Solar/Wind Harmer
0.229
219907AC1-030 C
Solar/Wind Harmer
0.156
213958STHWK5-6
Adder
3.065
213560DLW11-12
Adder
3.056
219348LDSOLAR C
Solar/Wind Harmer
0.671
219222BRL12CT2
Adder
10.018
213611FALLS1-3
Adder
3.95
214194N WALES4
Adder
0.952
20716028EGP_W2-019
Solar/Wind Harmer
0.517
207522AF2-254 C
Solar/Wind Harmer
1.6
20717128DIX_Z2-102
Solar/Wind Harmer
1.471
20715828PEM_W1-120
Solar/Wind Harmer
0.595
963711AG1-223 GEN
Solar/Wind Harmer
1.644
20714528FRN_Y2-051
Solar/Wind Harmer
0.328
219276PARKLANDSO C
Solar/Wind Harmer
0.512
219680HOPEWELLV C1
Solar/Wind Harmer
0.084
20715228NPK_W1-113
Solar/Wind Harmer
0.476
20720528MAN_W1-024
Solar/Wind Harmer
0.282
20720428HOL_W1-112
Solar/Wind Harmer
0.383
20635828PARLN1&2
Adder
8.189
20635028RRCT1&2
Adder
13.036
218524CNTRALGAS1 C
Solar/Wind Harmer
0.408
218440SUMMTASSOC C
Solar/Wind Harmer
0.141
218428ETC SOLAR C
Solar/Wind Harmer
0.04
219908AB1-139 C
Solar/Wind Harmer
0.42
219919AE1-041 FULL
Solar/Wind Harmer
0.045
972275AH1-722 GEN
Adder
34.869
20673628F1S_V4-069
Solar/Wind Harmer
0.198
207528AF2-192 GEN
Solar/Wind Harmer
1.403
217209CENTRL HS C
Solar/Wind Harmer
0.049
217186ESSEX_G9
Adder
4.35
217121ECCF
Adder
0.479
20671828STAW2-080
Solar/Wind Harmer
0.115
217083KRNY_132
Adder
10.244
217208PARK ELE C
Solar/Wind Harmer
0.028
20676728BRNX1-095
Solar/Wind Harmer
0.194
966261AG1-495 GEN
Solar/Wind Harmer
3.857
207439AE1-081 C O1
Solar/Wind Harmer
0.066
20676328BVR_Y1-020
Solar/Wind Harmer
0.363
20674628WNG_W3-110
Solar/Wind Harmer
0.443
207530AG1-191 GEN
Solar/Wind Harmer
1.51
20676228FRD_X1-012
Solar/Wind Harmer
0.649
20675828AU_W4-064
Solar/Wind Harmer
0.19
20674928WA_W3-044
Solar/Wind Harmer
0.528
971519AH1-257 GEN
Solar/Wind Harmer
2.765
20675728RH_W2-091
Solar/Wind Harmer
0.661
207518AF1-320_GEN
Solar/Wind Harmer
4.008
207484AF2-139 C O1
Solar/Wind Harmer
0.554
20465127PORT CT
Adder
3.288
208909MACR G3
Adder
174.223
211065PSPA IPP
Solar/Wind Harmer
0.489
961301AF2-421 GEN
Solar/Wind Harmer
1.057
963151AG1-164 GEN
Solar/Wind Harmer
1.057
209023WIENIPP1
Adder
11.393
209025WIENIPP3
Adder
5.687
963071AG1-156 GEN
Solar/Wind Harmer
10.376
209010PEIP 1
Adder
0.669
961341AF2-425 GEN
Solar/Wind Harmer
1.021
212507AE2-042_GEN
Solar/Wind Harmer
3.007
946731AF1-337 GEN
Solar/Wind Harmer
0.997
209018SUNBIPCT
Adder
7.415
20465527S.RDG CT
Adder
2.747
209008PAXT IPP
Adder
1.832
209137AF2-361 C
Solar/Wind Harmer
2.578
205967AE2-211_GEN
Solar/Wind Harmer
5.854
941421AE2-139 GEN
Solar/Wind Harmer
2.753
20328326MANOR_T86
Adder
0.126
316415AF1-147_GEN2
Solar/Wind Helper
1.095
238175AF1-290_GEN
Solar/Wind Helper
0.163
316447AC1-158 HLD
Solar/Wind Helper
3.67
316044AC1-158 PL1
Solar/Wind Helper
1.668
3147666LOUISA
Solar/Wind Helper
1.163
316192AB2-158 GEN
Solar/Wind Helper
1.957
238152AF2-075_GEN
Solar/Wind Helper
0.706
316337AD2-073 GEN
Solar/Wind Helper
0.432
964211AG1-282 GEN
Solar/Wind Helper
0.381
3141726DUNNSVL
Solar/Wind Helper
1.129
316404AE1-155 C
Solar/Wind Helper
2.412
3142416OLDCHRC
Solar/Wind Helper
0.73
3142416OLDCHRC
Solar/Wind Helper
0.28
3138133OCRAN
Solar/Wind Helper
0.168
3141766HARMONY
Solar/Wind Helper
0.056
315662AE1-191 GEN
Solar/Wind Helper
1.508
316280AD1-041 GEN
Solar/Wind Helper
0.942
3143526WINTERP
Solar/Wind Helper
1.454
315975AC1-164 GENB
Solar/Wind Helper
0.107
3142433PROV 92
Solar/Wind Helper
1.118
3143226MDLTHAN
Solar/Wind Helper
0.279
3142543TWELFTH
Solar/Wind Helper
0.027
316132AB2-190 GEN1
Solar/Wind Helper
1.585
315671AE2-027_GEN
Solar/Wind Helper
2.237
316369SG1_INVT
Solar/Wind Helper
1.333
3145336SMITFLD
Solar/Wind Helper
1.099
315773AC2-141 GEN
Solar/Wind Helper
5.92
316381AD1-082 GEN
Solar/Wind Helper
1.423
316375AC2-012 GEN
Solar/Wind Helper
0.721
316036AC1-147 C
Solar/Wind Helper
0.418
316072AD1-144
Solar/Wind Helper
0.313
3146456SLIGO L269
Solar/Wind Helper
0.273
319010AE1-072 C
Solar/Wind Helper
3.121
23777901MDS_W4-102
Solar/Wind Helper
0.171
3146516WINFALL
Solar/Wind Helper
0.877
3146516WINFALL
Solar/Wind Helper
0.271
315611Z1-036_GEN2
Solar/Wind Helper
1.479
3130156CHOWAN
Solar/Wind Helper
0.268
315816AE2-034 GEN
Solar/Wind Helper
1.221
3145663CRESWEL
Solar/Wind Helper
0.746
3146776BUCKING
Solar/Wind Helper
0.106
315737AD1-076 GEN
Solar/Wind Helper
2.594
3146926FARMVIL
Solar/Wind Helper
0.159
316023GEN1_S
Solar/Wind Helper
1.009
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
1.056
3147983MERCK5
Solar/Wind Helper
0.105
3146173TUNIS
Solar/Wind Helper
0.263
3156021HOLLOMANSOL
Solar/Wind Helper
2.006
3145683EARLEYS
Solar/Wind Helper
0.262
315607AA1-063A GEN
Solar/Wind Helper
1.501
316087AB2-174 GEN
Solar/Wind Helper
1.837
3146263WOODLND
Solar/Wind Helper
0.262
3145963POPLR C
Solar/Wind Helper
0.261
3145823KELFORD
Solar/Wind Helper
0.261
3145783HORNRTN
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.857
3145796HORNRTN
Solar/Wind Helper
0.26
316034AC1-036 C
Solar/Wind Helper
0.273
315785AD2-033 C
Solar/Wind Helper
3.028
316129AC1-054 GEN
Solar/Wind Helper
1.282
316131AB2-060 GEN
Solar/Wind Helper
1.576
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
316494AC1-189 GEN
Solar/Wind Helper
1.559
3146233WITAKRS
Solar/Wind Helper
1.012
961671AG1-007 GEN
Solar/Wind Helper
0.182
3146083TARBORO
Solar/Wind Helper
0.254
238108AE1-109 GEN1
Solar/Wind Helper
0.095
238110AE1-109 GEN3
Solar/Wind Helper
0.095
316359AB2-059 GEN
Solar/Wind Helper
1.932
3145543BTLEBRO
Solar/Wind Helper
0.253
3145543BTLEBRO
Solar/Wind Helper
0.202
964991AG1-363 GEN
Solar/Wind Helper
3.514
3147123OTTER R
Solar/Wind Helper
0.139
3147312GRETNA
Solar/Wind Helper
0.184
3146802CHATHAM
Solar/Wind Helper
0.172
270016AE1-250 BESS
Solar/Wind Helper
0.85
270018AE2-047 C O1
Solar/Wind Helper
0.795
200200DELTA2 CT1
50/50
3.915
200193DELTA CT2
50/50
2.188
200203Y1-065-STG
50/50
7.845
200055ROCKSP 4
50/50
2.833
233973AC2-185 C
Solar/Wind Harmer
7.11
970695AG2-447 GEN
Solar/Wind Harmer
4.704
233939AC1-091 C
Solar/Wind Harmer
3.52
233972AC1-094 C
Solar/Wind Harmer
2.826
233987AB2-037 GEN
Solar/Wind Harmer
14.909
232434Z2-077 GEN
Solar/Wind Harmer
0.328
232406W1-004 FULL
Solar/Wind Harmer
1.311
232914OH NUG3
Adder
11.579
232916OH NUG5
Adder
11.579
232921TASLEY2G
Adder
6.767
233923SMA
Solar/Wind Harmer
4.79
233997TMININ_4.2
Solar/Wind Harmer
1.306
232907VN8
Adder
39.356
233964AF2-378 GEN
Solar/Wind Harmer
0.167
233950AC2-186 GEN
Solar/Wind Harmer
0.736
232417X3-008 C
Solar/Wind Harmer
1.472
232422X3-066 FULL
Solar/Wind Harmer
0.324
233933AB2-153 GEN
Solar/Wind Harmer
1.455
233935AB2-179 C
Solar/Wind Harmer
3.185
228711V2-041C
Solar/Wind Harmer
0.694
230415AB2-049 C
Solar/Wind Harmer
0.218
219623KINSLEYBEA C
Solar/Wind Harmer
0.485
219291REEVESSOUT C
Solar/Wind Harmer
0.068
219921AF1-264
Solar/Wind Harmer
0.164
213497CHSTR7-9
Adder
3.087
218660EHAMPSOLAR C
Solar/Wind Harmer
0.198
219688LUMSOLAR_S C
Solar/Wind Harmer
0.229
219914AD2-027 C
Solar/Wind Harmer
0.678
219236SOUTHERNHQ C
Solar/Wind Harmer
0.076
213958STHWK5-6
Adder
3.065
213560DLW11-12
Adder
3.056
213815MOSER1-3
Adder
3.985
219221BRL12CT1
Adder
10.018
219223BRL12CT3
Adder
10.018
20716428NHV_W2-082
Solar/Wind Harmer
1.982
959561AF2-247 GEN
Solar/Wind Harmer
0.542
20715728PEM_W1-119
Solar/Wind Harmer
0.595
20636028O CRK C1
Adder
7.875
963391AG1-188 GEN
Solar/Wind Harmer
4.174
20714928UPF_X1-085
Solar/Wind Harmer
0.453
971667AH1-334 GEN
Solar/Wind Harmer
3.058
219114HARTZY_C
Solar/Wind Harmer
0.927
219727YARDVSOLFA C
Solar/Wind Harmer
1.012
219918AC2-009 C
Solar/Wind Harmer
0.029
207454AA2-184 E
Solar/Wind Harmer
1.107
219612MATRIX C
Solar/Wind Harmer
0.203
20716928W4-060COL
Solar/Wind Harmer
0.787
20635828PARLN1&2
Adder
3.709
20635928PARLN3&4
Adder
3.709
217213AMBOY SO C
Solar/Wind Harmer
0.14
219249CENTRALDIV C
Solar/Wind Harmer
0.044
207442AE1-156 GEN
Solar/Wind Harmer
0.82
20673728F2S_V4-070
Solar/Wind Harmer
0.198
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217169METRODIV C
Solar/Wind Harmer
0.044
217194REDH C
Solar/Wind Harmer
0.542
20674528F3S_W2-016
Solar/Wind Harmer
1.549
207510AF2-138 C
Solar/Wind Harmer
1.953
207511W3-106 GEN
Solar/Wind Harmer
0.362
971007AG2-625 GEN
Solar/Wind Harmer
2.818
207437AD2-070 GEN
Solar/Wind Harmer
0.33
20671928W4-073
Solar/Wind Harmer
0.474
20674128FR_U2-059
Solar/Wind Harmer
0.202
20466127PORT 5CT
Adder
29.023
20633028GILCT9
Adder
30.976
20465427SHAW CT
Adder
4.217
209116AE2-175 GEN
Solar/Wind Harmer
4.469
211065PSPA IPP
Solar/Wind Harmer
0.489
963161AG1-165 GEN
Solar/Wind Harmer
1.057
209025WIENIPP3
Adder
5.572
970095AG2-074 GEN
Solar/Wind Harmer
6.571
208972BECR K09
Solar/Wind Harmer
1.103
205941AD2-115 GEN
Solar/Wind Harmer
0.943
961331AF2-424 GEN
Solar/Wind Harmer
1.021
961421AF2-433 GEN
Solar/Wind Harmer
1.018
957921AF2-086 GEN
Solar/Wind Harmer
0.99
209142AF1-226 GEN
Solar/Wind Harmer
5.895
209093AE2-110 GEN
Solar/Wind Harmer
2.546
209120AE2-241 GEN
Solar/Wind Harmer
3.369
946691AF1-333 GEN
Solar/Wind Harmer
0.997
946741AF1-338 GEN
Solar/Wind Harmer
0.997
209071AE2-133 GEN
Solar/Wind Harmer
1.685
972221AH1-695 GEN
Adder
124.805
3141196NOKESVL
Solar/Wind Helper
1.26
3132273ORANGE
Solar/Wind Helper
0.059
3147666LOUISA
Solar/Wind Helper
0.669
966881AG1-559 GEN
Solar/Wind Helper
0.39
316223AC1-118
Solar/Wind Helper
0.436
3141906WESTMOR
Solar/Wind Helper
0.114
23546401DTGZ2-030
Solar/Wind Helper
0.089
316077AC2-138 C
Solar/Wind Helper
0.267
316473AC1-191 GEN
Solar/Wind Helper
1.724
316484AD2-074 GEN
Solar/Wind Helper
0.543
316075AC2-137 C
Solar/Wind Helper
0.427
3142946ENON
Solar/Wind Helper
0.093
316458AB2-190 GEN2
Solar/Wind Helper
1.585
3145336SMITFLD
Solar/Wind Helper
0.11
3144536CHRHLND
Solar/Wind Helper
0.041
3144873MCLAUGH
Solar/Wind Helper
0.007
3142956BIRDNECK
Solar/Wind Helper
0.184
316017AA1-139 ULT1
Solar/Wind Helper
1.25
3146456SLIGO L269
Solar/Wind Helper
0.273
316305AF2-043 C
Solar/Wind Helper
0.367
316246AF1-032 C
Solar/Wind Helper
0.312
316320Y1-086
Solar/Wind Helper
0.122
316321Z2-027
Solar/Wind Helper
0.415
3146516WINFALL
Solar/Wind Helper
0.271
3146626S HERTFORD
Solar/Wind Helper
0.27
3145273HOLLAND
Solar/Wind Helper
0.203
3146376EDENTON
Solar/Wind Helper
0.268
3146776BUCKING
Solar/Wind Helper
0.096
315735AD1-075 GEN1
Solar/Wind Helper
1.517
3146926FARMVIL
Solar/Wind Helper
0.159
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
0.095
3145893MURPHYS
Solar/Wind Helper
0.264
316095T157 G97
Solar/Wind Helper
1.213
3146173TUNIS
Solar/Wind Helper
0.263
315821AE2-092 GEN
Solar/Wind Helper
2.446
942461AE2-259 GEN
Solar/Wind Helper
1.771
966621AG1-532 GEN
Solar/Wind Helper
0.239
316499AE2-029_GEN
Solar/Wind Helper
0.883
3146263WOODLND
Solar/Wind Helper
0.262
316181AB2-040 GEN
Solar/Wind Helper
1.882
3147133PAMPLIN
Solar/Wind Helper
0.821
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3147043LAWRENC
Solar/Wind Helper
0.157
316190AA2-174 GEN
Solar/Wind Helper
0.018
3145963POPLR C
Solar/Wind Helper
0.261
316011AB1-132 GEN
Solar/Wind Helper
2.815
316317KELFORD C
Solar/Wind Helper
0.235
3145823KELFORD
Solar/Wind Helper
0.261
316478AD1-087 GEN
Solar/Wind Helper
1.276
3148013FISHERV
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
1.039
3145796HORNRTN
Solar/Wind Helper
0.26
316212AC1-099_GEN
Solar/Wind Helper
1.16
3145933PARMELE
Solar/Wind Helper
0.258
23583801GRNGAP
Solar/Wind Helper
4.412
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
270494AE1-108_GEN
Solar/Wind Helper
3.425
316420AA1-050 GEN
Solar/Wind Helper
1.464
3146233WITAKRS
Solar/Wind Helper
0.274
3146233WITAKRS
Solar/Wind Helper
0.173
3146073TAR RVR
Solar/Wind Helper
0.254
3146083TARBORO
Solar/Wind Helper
0.254
3138543CONSLDL
Solar/Wind Helper
0.168
238109AE1-109 GEN2
Solar/Wind Helper
0.095
3145543BTLEBRO
Solar/Wind Helper
0.253
3145543BTLEBRO
Solar/Wind Helper
0.253
316003AC1-222 GEN
Solar/Wind Helper
1.082
227287AC2-120 GEN
Solar/Wind Helper
0.335
316222AC1-221 GEN
Solar/Wind Helper
1.394
316283AC2-100 C
Solar/Wind Helper
1.299
226910AB2-157 C
Solar/Wind Helper
0.014
316123AC1-075 GEN
Solar/Wind Helper
1.475
237038AE2-054 C
Solar/Wind Helper
0.23
235067AD1-061 GEN
Solar/Wind Helper
0.375
316197AC1-042 GEN
Solar/Wind Helper
0.217
3147312GRETNA
Solar/Wind Helper
0.046
237085AD2-009_GEN
Solar/Wind Helper
1.363
237002AB1-128_GEN
Solar/Wind Helper
0.365
270173AC1-122 GEN
Solar/Wind Helper
1.539
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.003
VTFLTFEXP_VFT->PJM
CMTX
149.342
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.503
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.578
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.687
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.27
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
56.69
CBM NorthLTFEXP_CBM-N->PJM
CBM
83.409
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CHIREACT_39-CHICHST2 230.0 kV Ckt 1 line l/o PECO_CBO_CHIC435_SRT-A/* $ DELCO $ PECO_CBO_CHIC435 $ K


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
CHIREACT_39-CHICHST2 230.0 kV Ckt 1 line
Contingency Name:
PECO_CBO_CHIC435_SRT-A/* $ DELCO $ PECO_CBO_CHIC435 $ K
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.34 %
Rating:1622.0 MVA
Rating Type:B
MVA to Mitigate:1643.73
MW Contribution:
2.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213893PHLISST1
50/50
9.655
231505HR4
50/50
5.278
231916EM3
50/50
1.729
231901EM4
50/50
3.495
231919CHRIST1
50/50
7.479
231920CHRIST2
50/50
7.313
231906DC3 NUG
50/50
13.152
231902DC CT7
50/50
10.514
231907DC10
50/50
3.283
233915AB1-141 GEN
Solar/Wind Harmer
0.79
233968AD2-076_GEN
Solar/Wind Harmer
5.256
970597AG2-380 GEN
Solar/Wind Harmer
3.301
233955AB2-172 GEN
Solar/Wind Harmer
3.727
233940AF2-379 C
Solar/Wind Harmer
0.134
971195AH1-057 GEN
Solar/Wind Harmer
0.699
233901CHERRYDALE C
Solar/Wind Harmer
0.805
232912OH NUG1
Adder
6.323
232913OH NUG2
Adder
6.239
232432Z2-076 GEN
Solar/Wind Harmer
0.093
232920IR10
Adder
2.209
232813VAUGHN
Adder
0.411
232904IR4
Adder
56.366
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219615MILLCREEK C
Solar/Wind Helper
0.014
231900EM5
50/50
12.344
231909HR2
50/50
2.515
231908HR1
50/50
2.511
231910HR3
50/50
2.511
232416X2-083
50/50
0.033
233930AB2-032 GEN
Solar/Wind Harmer
0.665
234014AF1-036_GEN
Solar/Wind Harmer
2.145
233982AB2-133 GEN
Solar/Wind Harmer
3.845
233984AB2-036 GEN
Solar/Wind Harmer
9.819
232436AB1-176 C
Solar/Wind Harmer
0.181
232424Y1-079 C
Solar/Wind Harmer
0.442
234041AC1-190 GEN
Solar/Wind Harmer
6.669
234036AF2-325 C
Solar/Wind Harmer
0.68
233946AB2-136 GEN
Solar/Wind Harmer
2.951
233994AC2-023 GEN
Solar/Wind Harmer
1.94
232428Y3-058 C
Solar/Wind Harmer
0.6
232926CRISFLD1
Adder
1.411
234015AF2-250 C
Solar/Wind Harmer
0.086
232410W1-006 C
Solar/Wind Harmer
0.716
232905CHERITON_25
Adder
1.757
232918OH NUG7
Adder
6.281
231940T-011
Adder
0.527
232910NRG_G1
Adder
6.075
233952AC2-187 GEN
Solar/Wind Harmer
0.777
233954AC2-188 GEN
Solar/Wind Harmer
0.777
232899W1-062
Adder
6.114
233971AC1-093 C
Solar/Wind Harmer
1.544
219912AD2-042 GEN
Solar/Wind Helper
0.087
219904AC1-010 C
Solar/Wind Helper
0.035
219906AC1-017 C
Solar/Wind Helper
0.021
214067T20SOLAR
Solar/Wind Helper
0.006
219607WPEMNERT C
Solar/Wind Helper
0.039
219304NAMERICA C
Solar/Wind Helper
0.064
213889PHLISCT2
50/50
6.682
231917EM10
50/50
4.412
231918WEST 1
50/50
5.526
233918AB1-142 GEN
Solar/Wind Harmer
0.79
234012AE2-112_GEN
Solar/Wind Harmer
1.824
232902EASTMUNI
Adder
10.109
233944AB2-135 GEN
Solar/Wind Harmer
4.049
232426Y1-080 FULL
Solar/Wind Harmer
0.141
232919VN10
Adder
2.06
233996TM1833_GEN
Solar/Wind Harmer
0.717
233998TM1NIN_3.36
Solar/Wind Harmer
0.717
232404W1-003 C
Solar/Wind Harmer
0.716
232408W1-005 C
Solar/Wind Harmer
0.716
232917OH NUG6
Adder
6.295
232915OH NUG4
Adder
6.281
234033AF1-007_GEN
Solar/Wind Harmer
25.93
972177AH1-672 GEN
Solar/Wind Harmer
9.199
232900DEMECSMY
Adder
5.864
232901NORTHST
Adder
5.277
233970AC1-092 C
Solar/Wind Harmer
1.626
972251AH1-710 GEN
Adder
10.811
219766PARADISE C
Solar/Wind Helper
0.031
219907AC1-030 C
Solar/Wind Helper
0.019
219348LDSOLAR C
Solar/Wind Helper
0.056
213890PHLISCT3
50/50
6.693
213888PHLISCT1
50/50
6.682
231131BLOOM ENRGY
50/50
0.23
231915DC CT6
50/50
0.555
233935AB2-179 C
Solar/Wind Harmer
2.113
233933AB2-153 GEN
Solar/Wind Harmer
0.898
233987AB2-037 GEN
Solar/Wind Harmer
9.013
232422X3-066 FULL
Solar/Wind Harmer
0.197
232417X3-008 C
Solar/Wind Harmer
0.839
233964AF2-378 GEN
Solar/Wind Harmer
0.095
232907VN8
Adder
22.172
233923SMA
Solar/Wind Harmer
2.627
233997TMININ_4.2
Solar/Wind Harmer
0.717
232406W1-004 FULL
Solar/Wind Harmer
0.716
232921TASLEY2G
Adder
3.696
232914OH NUG3
Adder
6.323
232916OH NUG5
Adder
6.323
232434Z2-077 GEN
Solar/Wind Harmer
0.175
233950AC2-186 GEN
Solar/Wind Harmer
0.388
233973AC2-185 C
Solar/Wind Harmer
3.286
970695AG2-447 GEN
Solar/Wind Harmer
2.174
233939AC1-091 C
Solar/Wind Harmer
1.626
233972AC1-094 C
Solar/Wind Harmer
1.306
219914AD2-027 C
Solar/Wind Helper
0.067
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219921AF1-264
Solar/Wind Helper
0.027
219623KINSLEYBEA C
Solar/Wind Helper
0.001
NYPJM->LTFIMP_NY
CLTF
1.194
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.199
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.125
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.235
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.077
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.732
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CHIREACT_43-CHICHST1 230.0 kV Ckt 1 line l/o PECO_P4_POST475_SRT-A/* $ DELCO $ PECO_P4_POST475 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
CHIREACT_43-CHICHST1 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_POST475_SRT-A/* $ DELCO $ PECO_P4_POST475 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.18 %
Rating:1770.0 MVA
Rating Type:B
MVA to Mitigate:1790.82
MW Contribution:
2.18
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213889PHLISCT2
50/50
6.731
231917EM10
50/50
4.426
231918WEST 1
50/50
5.544
233918AB1-142 GEN
Solar/Wind Harmer
0.793
234012AE2-112_GEN
Solar/Wind Harmer
1.83
232902EASTMUNI
Adder
10.144
233944AB2-135 GEN
Solar/Wind Harmer
4.063
232426Y1-080 FULL
Solar/Wind Harmer
0.141
232919VN10
Adder
2.068
233996TM1833_GEN
Solar/Wind Harmer
0.719
233998TM1NIN_3.36
Solar/Wind Harmer
0.719
232404W1-003 C
Solar/Wind Harmer
0.718
232408W1-005 C
Solar/Wind Harmer
0.718
232917OH NUG6
Adder
6.318
232915OH NUG4
Adder
6.303
234033AF1-007_GEN
Solar/Wind Harmer
26.022
972177AH1-672 GEN
Solar/Wind Harmer
9.232
232900DEMECSMY
Adder
5.885
232901NORTHST
Adder
5.296
233970AC1-092 C
Solar/Wind Harmer
1.632
972251AH1-710 GEN
Adder
10.86
219766PARADISE C
Solar/Wind Helper
0.031
219907AC1-030 C
Solar/Wind Helper
0.019
219348LDSOLAR C
Solar/Wind Helper
0.056
231900EM5
50/50
12.386
231909HR2
50/50
2.523
231908HR1
50/50
2.519
231910HR3
50/50
2.519
232416X2-083
50/50
0.033
233930AB2-032 GEN
Solar/Wind Harmer
0.667
234014AF1-036_GEN
Solar/Wind Harmer
2.153
233982AB2-133 GEN
Solar/Wind Harmer
3.858
233984AB2-036 GEN
Solar/Wind Harmer
9.854
232436AB1-176 C
Solar/Wind Harmer
0.181
232424Y1-079 C
Solar/Wind Harmer
0.444
234041AC1-190 GEN
Solar/Wind Harmer
6.692
234036AF2-325 C
Solar/Wind Harmer
0.682
233946AB2-136 GEN
Solar/Wind Harmer
2.962
233994AC2-023 GEN
Solar/Wind Harmer
1.947
232428Y3-058 C
Solar/Wind Harmer
0.603
232926CRISFLD1
Adder
1.416
234015AF2-250 C
Solar/Wind Harmer
0.086
232410W1-006 C
Solar/Wind Harmer
0.718
232905CHERITON_25
Adder
1.763
232918OH NUG7
Adder
6.303
231940T-011
Adder
0.529
232910NRG_G1
Adder
6.097
233952AC2-187 GEN
Solar/Wind Harmer
0.779
233954AC2-188 GEN
Solar/Wind Harmer
0.779
232899W1-062
Adder
6.136
233971AC1-093 C
Solar/Wind Harmer
1.55
219912AD2-042 GEN
Solar/Wind Helper
0.087
219904AC1-010 C
Solar/Wind Helper
0.035
219906AC1-017 C
Solar/Wind Helper
0.021
214067T20SOLAR
Solar/Wind Helper
0.006
219607WPEMNERT C
Solar/Wind Helper
0.039
219304NAMERICA C
Solar/Wind Helper
0.064
213893PHLISST1
50/50
9.742
231505HR4
50/50
5.296
231916EM3
50/50
1.734
231901EM4
50/50
3.507
231919CHRIST1
50/50
7.504
231920CHRIST2
50/50
7.337
231906DC3 NUG
50/50
13.196
231902DC CT7
50/50
10.55
231907DC10
50/50
3.294
233915AB1-141 GEN
Solar/Wind Harmer
0.793
233968AD2-076_GEN
Solar/Wind Harmer
5.274
970597AG2-380 GEN
Solar/Wind Harmer
3.312
233955AB2-172 GEN
Solar/Wind Harmer
3.74
233940AF2-379 C
Solar/Wind Harmer
0.135
971195AH1-057 GEN
Solar/Wind Harmer
0.701
233901CHERRYDALE C
Solar/Wind Harmer
0.808
232912OH NUG1
Adder
6.346
232913OH NUG2
Adder
6.261
232432Z2-076 GEN
Solar/Wind Harmer
0.093
232920IR10
Adder
2.216
232813VAUGHN
Adder
0.413
232904IR4
Adder
56.566
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219615MILLCREEK C
Solar/Wind Helper
0.014
213890PHLISCT3
50/50
6.753
213888PHLISCT1
50/50
6.731
231131BLOOM ENRGY
50/50
0.231
231915DC CT6
50/50
0.557
233935AB2-179 C
Solar/Wind Harmer
2.12
233933AB2-153 GEN
Solar/Wind Harmer
0.901
233987AB2-037 GEN
Solar/Wind Harmer
9.044
232422X3-066 FULL
Solar/Wind Harmer
0.198
232417X3-008 C
Solar/Wind Harmer
0.842
233964AF2-378 GEN
Solar/Wind Harmer
0.095
232907VN8
Adder
22.251
233923SMA
Solar/Wind Harmer
2.637
233997TMININ_4.2
Solar/Wind Harmer
0.719
232406W1-004 FULL
Solar/Wind Harmer
0.718
232921TASLEY2G
Adder
3.709
232914OH NUG3
Adder
6.346
232916OH NUG5
Adder
6.346
232434Z2-077 GEN
Solar/Wind Harmer
0.176
233950AC2-186 GEN
Solar/Wind Harmer
0.39
233973AC2-185 C
Solar/Wind Harmer
3.298
970695AG2-447 GEN
Solar/Wind Harmer
2.181
233939AC1-091 C
Solar/Wind Harmer
1.632
233972AC1-094 C
Solar/Wind Harmer
1.311
219914AD2-027 C
Solar/Wind Helper
0.067
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219921AF1-264
Solar/Wind Helper
0.027
219623KINSLEYBEA C
Solar/Wind Helper
0.001
NYPJM->LTFIMP_NY
CLTF
1.198
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.201
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.127
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.237
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.086
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.738
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CHIREACT_43-CHICHST1 230.0 kV Ckt 1 line l/o PECO_P4_POST785_SRT-A/* $ DELCO $ PECO_P4_POST785 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
CHIREACT_43-CHICHST1 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_POST785_SRT-A/* $ DELCO $ PECO_P4_POST785 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.17 %
Rating:1770.0 MVA
Rating Type:B
MVA to Mitigate:1790.79
MW Contribution:
2.18
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213889PHLISCT2
50/50
6.731
231917EM10
50/50
4.426
231918WEST 1
50/50
5.544
233918AB1-142 GEN
Solar/Wind Harmer
0.793
234012AE2-112_GEN
Solar/Wind Harmer
1.83
232902EASTMUNI
Adder
10.144
233944AB2-135 GEN
Solar/Wind Harmer
4.063
232426Y1-080 FULL
Solar/Wind Harmer
0.141
232919VN10
Adder
2.068
233996TM1833_GEN
Solar/Wind Harmer
0.719
233998TM1NIN_3.36
Solar/Wind Harmer
0.719
232404W1-003 C
Solar/Wind Harmer
0.718
232408W1-005 C
Solar/Wind Harmer
0.718
232917OH NUG6
Adder
6.318
232915OH NUG4
Adder
6.303
234033AF1-007_GEN
Solar/Wind Harmer
26.022
972177AH1-672 GEN
Solar/Wind Harmer
9.232
232900DEMECSMY
Adder
5.885
232901NORTHST
Adder
5.296
233970AC1-092 C
Solar/Wind Harmer
1.632
972251AH1-710 GEN
Adder
10.86
219766PARADISE C
Solar/Wind Helper
0.031
231900EM5
50/50
12.386
231909HR2
50/50
2.523
231908HR1
50/50
2.519
231910HR3
50/50
2.519
232416X2-083
50/50
0.033
233930AB2-032 GEN
Solar/Wind Harmer
0.667
234014AF1-036_GEN
Solar/Wind Harmer
2.153
233982AB2-133 GEN
Solar/Wind Harmer
3.858
233984AB2-036 GEN
Solar/Wind Harmer
9.854
232436AB1-176 C
Solar/Wind Harmer
0.181
232424Y1-079 C
Solar/Wind Harmer
0.444
234041AC1-190 GEN
Solar/Wind Harmer
6.692
234036AF2-325 C
Solar/Wind Harmer
0.682
233946AB2-136 GEN
Solar/Wind Harmer
2.962
233994AC2-023 GEN
Solar/Wind Harmer
1.947
232428Y3-058 C
Solar/Wind Harmer
0.603
232926CRISFLD1
Adder
1.416
234015AF2-250 C
Solar/Wind Harmer
0.086
232410W1-006 C
Solar/Wind Harmer
0.718
232905CHERITON_25
Adder
1.763
232918OH NUG7
Adder
6.303
231940T-011
Adder
0.529
232910NRG_G1
Adder
6.097
233952AC2-187 GEN
Solar/Wind Harmer
0.779
233954AC2-188 GEN
Solar/Wind Harmer
0.779
232899W1-062
Adder
6.136
233971AC1-093 C
Solar/Wind Harmer
1.55
219912AD2-042 GEN
Solar/Wind Helper
0.087
219904AC1-010 C
Solar/Wind Helper
0.035
219906AC1-017 C
Solar/Wind Helper
0.021
214067T20SOLAR
Solar/Wind Helper
0.006
219607WPEMNERT C
Solar/Wind Helper
0.039
219304NAMERICA C
Solar/Wind Helper
0.064
213893PHLISST1
50/50
9.742
231505HR4
50/50
5.296
231916EM3
50/50
1.734
231901EM4
50/50
3.507
231919CHRIST1
50/50
7.504
231920CHRIST2
50/50
7.337
231906DC3 NUG
50/50
13.196
231902DC CT7
50/50
10.55
231907DC10
50/50
3.294
233915AB1-141 GEN
Solar/Wind Harmer
0.793
233968AD2-076_GEN
Solar/Wind Harmer
5.274
970597AG2-380 GEN
Solar/Wind Harmer
3.312
233955AB2-172 GEN
Solar/Wind Harmer
3.74
233940AF2-379 C
Solar/Wind Harmer
0.135
971195AH1-057 GEN
Solar/Wind Harmer
0.701
233901CHERRYDALE C
Solar/Wind Harmer
0.808
232912OH NUG1
Adder
6.346
232913OH NUG2
Adder
6.261
232432Z2-076 GEN
Solar/Wind Harmer
0.093
232920IR10
Adder
2.216
232813VAUGHN
Adder
0.413
232904IR4
Adder
56.566
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219615MILLCREEK C
Solar/Wind Helper
0.014
219907AC1-030 C
Solar/Wind Helper
0.019
219348LDSOLAR C
Solar/Wind Helper
0.056
213890PHLISCT3
50/50
6.753
213888PHLISCT1
50/50
6.731
231131BLOOM ENRGY
50/50
0.231
231915DC CT6
50/50
0.557
233935AB2-179 C
Solar/Wind Harmer
2.12
233933AB2-153 GEN
Solar/Wind Harmer
0.901
233987AB2-037 GEN
Solar/Wind Harmer
9.044
232422X3-066 FULL
Solar/Wind Harmer
0.198
232417X3-008 C
Solar/Wind Harmer
0.842
233964AF2-378 GEN
Solar/Wind Harmer
0.095
232907VN8
Adder
22.251
233923SMA
Solar/Wind Harmer
2.637
233997TMININ_4.2
Solar/Wind Harmer
0.719
232406W1-004 FULL
Solar/Wind Harmer
0.718
232921TASLEY2G
Adder
3.709
232914OH NUG3
Adder
6.346
232916OH NUG5
Adder
6.346
232434Z2-077 GEN
Solar/Wind Harmer
0.176
233950AC2-186 GEN
Solar/Wind Harmer
0.39
233973AC2-185 C
Solar/Wind Harmer
3.298
970695AG2-447 GEN
Solar/Wind Harmer
2.181
233939AC1-091 C
Solar/Wind Harmer
1.632
233972AC1-094 C
Solar/Wind Harmer
1.311
219914AD2-027 C
Solar/Wind Helper
0.067
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219921AF1-264
Solar/Wind Helper
0.027
219623KINSLEYBEA C
Solar/Wind Helper
0.001
NYPJM->LTFIMP_NY
CLTF
1.198
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.201
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.127
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.237
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.086
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.738
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019E_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019E_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.16 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3939.34
MW Contribution:
3.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200200DELTA2 CT1
50/50
2.805
200193DELTA CT2
50/50
1.567
200203Y1-065-STG
50/50
5.649
200055ROCKSP 4
50/50
2.04
233987AB2-037 GEN
Solar/Wind Harmer
11.072
200202DELTA2 ST
50/50
4.75
200195DELTA ST
50/50
2.421
200052ROCKSP 1
50/50
2.052
200053ROCKSP 2
50/50
2.012
232904IR4
Adder
78.673
233901CHERRYDALE C
Solar/Wind Harmer
1.094
232432Z2-076 GEN
Solar/Wind Harmer
0.128
232912OH NUG1
Adder
8.595
232913OH NUG2
Adder
8.48
232920IR10
Adder
3.075
233940AF2-379 C
Solar/Wind Harmer
0.181
971195AH1-057 GEN
Solar/Wind Harmer
0.948
233955AB2-172 GEN
Solar/Wind Harmer
4.861
232813VAUGHN
Adder
0.572
233968AD2-076_GEN
Solar/Wind Harmer
6.422
970597AG2-380 GEN
Solar/Wind Harmer
4.033
231906DC3 NUG
Adder
13.546
231902DC CT7
Adder
10.829
231907DC10
Adder
3.382
233915AB1-141 GEN
Solar/Wind Harmer
0.957
231919CHRIST1
Adder
4.207
231920CHRIST2
Adder
4.114
970453AG2-297 GEN
Solar/Wind Harmer
2.381
972141AH1-641 GEN
Solar/Wind Harmer
2.475
230430AE1-229_GEN
Solar/Wind Harmer
24.623
964001AG1-254 GEN
Solar/Wind Harmer
6.266
230422AE1-104_GEN1
Solar/Wind Harmer
28.972
230425AE1-104_GEN2
Solar/Wind Harmer
28.972
228728W1-130C
Solar/Wind Harmer
0.57
230434AG1-499 GEN
Solar/Wind Harmer
0.497
230407AD2-065 C
Solar/Wind Harmer
0.113
227927V4-067C
Solar/Wind Harmer
0.17
219137THOSOLAR C
Solar/Wind Harmer
1.032
219258KINSLEYDEP C
Solar/Wind Harmer
0.275
213942SCHUYLKILL
Adder
3.027
213942SCHUYLKILL
Adder
2.315
213957STHWK3-4
Adder
2.314
213957STHWK3-4
Adder
2.314
213561DLWR9-10
Adder
3.011
213561DLWR9-10
Adder
2.303
219615MILLCREEK C
Solar/Wind Harmer
0.201
219610FLORENCE C
Solar/Wind Harmer
1.168
219224BRL12CT4
Adder
7.526
213611FALLS1-3
Adder
2.97
213611FALLS1-3
Adder
2.97
20720728JCB_W1-129
Solar/Wind Harmer
0.25
20715028HAN_X4-015
Solar/Wind Harmer
0.25
207487AE2-000G4
Solar/Wind Harmer
26.357
207497AE2-000G2
Solar/Wind Harmer
26.357
207500AE2-000G1
Solar/Wind Harmer
26.357
207507AE2-000G3
Solar/Wind Harmer
26.357
963401AG1-189 GEN
Solar/Wind Harmer
1.902
970025AG2-016 GEN
Solar/Wind Harmer
2.37
971189AH1-054 GEN
Solar/Wind Harmer
0.987
207445AB1-138_GEN
Solar/Wind Harmer
0.484
219620RIDERU C
Solar/Wind Harmer
0.047
20714428HOW_X1-037
Solar/Wind Harmer
1.031
20720628TIN_W1-124
Solar/Wind Harmer
0.831
20716228APLW2-078
Solar/Wind Harmer
0.737
971521AH1-258 GEN
Solar/Wind Harmer
2.259
20635928PARLN3&4
Adder
6.178
218526CNTRALGAS2 C
Solar/Wind Harmer
0.309
20675528CPH_W2-050
Solar/Wind Harmer
0.479
20673828FLE_V3-070
Solar/Wind Harmer
0.389
20676128MHD_W3-029
Solar/Wind Harmer
0.399
218449LINSOLAR C
Solar/Wind Harmer
0.84
20676428JCR_X2-075
Solar/Wind Harmer
0.285
217167KRNY_14
Adder
7.76
217086KRNY_131
Adder
7.694
217147KRNY_1212
Adder
7.381
217147KRNY_1212
Adder
7.249
217146KRNY_1234
Adder
7.232
217146KRNY_1234
Adder
7.183
964851AG1-348 GEN
Solar/Wind Harmer
1.145
971009AG2-626 GEN
Solar/Wind Harmer
1.373
207408W3-077 C
Solar/Wind Harmer
0.425
20675128HRM_W1-127
Solar/Wind Harmer
0.143
20462827N BANGR8
Adder
0.6
961261AF2-417 GEN
Solar/Wind Harmer
0.817
209026WIENIPP4
Adder
4.347
20486527WR_V4-052
Adder
0.887
208862AG1-362 C
Solar/Wind Harmer
0.661
209027LOR2_Q27
Solar/Wind Harmer
3.641
212266LOR1
Solar/Wind Harmer
0.965
209029WAYMART-WD
Solar/Wind Harmer
2.083
209054AE2-059 GEN
Solar/Wind Harmer
1.322
959431AF2-234 GEN
Solar/Wind Harmer
1.553
964051AG1-259 GEN
Solar/Wind Harmer
1.041
964061AG1-260 GEN
Solar/Wind Harmer
1.041
959421AF2-233 GEN
Solar/Wind Harmer
0.777
209067AE2-060 GEN
Solar/Wind Harmer
1.124
209030FRFA O01
Adder
0.192
205951AE1-129_GEN
Solar/Wind Harmer
8.48
205956AE1-196_GEN
Solar/Wind Harmer
0.58
20465027TOLNA CT
Adder
2.389
205943AE1-185 GEN
Solar/Wind Harmer
0.574
20390726Y2-042
Adder
2.289
200917MEHOOPANY_G
Solar/Wind Harmer
3.089
20334726NME_Y1-047
Adder
2.076
20464627HAM CT
Adder
1.901
226929AD2-058 GEN
Solar/Wind Helper
0.119
3138216PACIFIC
Solar/Wind Helper
0.049
3141426STAFORD
Solar/Wind Helper
0.062
315651AD1-115 GEN
Solar/Wind Helper
0.909
316164AC1-076 GEN
Solar/Wind Helper
1.284
316468AD1-105 GEN
Solar/Wind Helper
1.246
3141813NORNECK
Solar/Wind Helper
0.255
3141783LANCAST
Solar/Wind Helper
0.151
3141783LANCAST
Solar/Wind Helper
0.101
3138133OCRAN
Solar/Wind Helper
0.076
3141913WHIT STONE
Solar/Wind Helper
0.252
316059AD1-063 C
Solar/Wind Helper
0.254
957601AF2-054 GEN
Solar/Wind Helper
0.337
3141873WAN 176
Solar/Wind Helper
0.05
3143873LANEXA
Solar/Wind Helper
0.151
316233AE1-074 FULL
Solar/Wind Helper
0.382
238169AE2-226 GEN1
Solar/Wind Helper
0.612
238170AE2-226 GEN2
Solar/Wind Helper
0.612
957831AF2-077 GEN
Solar/Wind Helper
0.336
316382AG1-145 C
Solar/Wind Helper
0.335
316159AE1-175 C
Solar/Wind Helper
0.377
315697AD1-025 GEN
Solar/Wind Helper
2.824
315839AE2-212 C
Solar/Wind Helper
0.332
316236AE1-162_GEN
Solar/Wind Helper
0.33
3143316POE
Solar/Wind Helper
0.969
316258AE1-075 C
Solar/Wind Helper
0.335
316405AF2-144 C
Solar/Wind Helper
0.279
316316AC1-027 C
Solar/Wind Helper
0.385
316018AA1-139 ULT2
Solar/Wind Helper
1.046
313526AB2-022
Solar/Wind Helper
0.369
3146486SUNBURY
Solar/Wind Helper
0.241
3146486SUNBURY
Solar/Wind Helper
0.241
3145176PASQUOTANK
Solar/Wind Helper
0.149
315800Z1-036_GEN1
Solar/Wind Helper
1.309
3130156CHOWAN
Solar/Wind Helper
0.237
3130156CHOWAN
Solar/Wind Helper
0.237
3130546PLYMOUTH
Solar/Wind Helper
0.234
315732AD1-074 GEN1
Solar/Wind Helper
2.672
315733AD1-074 GEN2
Solar/Wind Helper
2.672
316322AB2-045
Solar/Wind Helper
0.26
3146206CASHIE
Solar/Wind Helper
0.232
3145893MURPHYS
Solar/Wind Helper
0.627
3145893MURPHYS
Solar/Wind Helper
0.232
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.007
316463AE2-346 GEN
Solar/Wind Helper
0.212
3145513AHOSKIE
Solar/Wind Helper
0.104
961941AG1-037 GEN
Solar/Wind Helper
0.078
3145513AHOSKIE
Solar/Wind Helper
0.231
946281AF1-292 GEN
Solar/Wind Helper
0.232
3146043SEABORD
Solar/Wind Helper
0.231
3145683EARLEYS
Solar/Wind Helper
0.461
3145683EARLEYS
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.23
3137643SOCKMAN
Solar/Wind Helper
0.915
316426AA2-053 GEN
Solar/Wind Helper
1.309
316174AB2-169 GEN
Solar/Wind Helper
0.584
316486AD2-202 GEN
Solar/Wind Helper
0.327
3145796HORNRTN
Solar/Wind Helper
0.728
3145796HORNRTN
Solar/Wind Helper
0.091
3146033SCOT NK
Solar/Wind Helper
0.908
3144303KENBRDG
Solar/Wind Helper
0.181
316210AC1-098 GEN
Solar/Wind Helper
1.823
316274AC1-208 GEN
Solar/Wind Helper
1.374
316238AB2-078_GEN
Solar/Wind Helper
0.302
316239AB2-077_GEN
Solar/Wind Helper
0.302
3148133STUARTS
Solar/Wind Helper
0.134
3148013FISHERV
Solar/Wind Helper
0.129
3145746EVERETS
Solar/Wind Helper
0.888
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
972281AH1-725 GEN
50/50
137.759
200201DELTA2 CT2
50/50
2.805
200034PCHBTM 2
50/50
16.353
200035PCHBTM 3
50/50
16.218
200205Y1-065-CTG2
50/50
3.262
233971AC1-093 C
Solar/Wind Harmer
2.477
232410W1-006 C
Solar/Wind Harmer
0.973
232918OH NUG7
Adder
8.537
232905CHERITON_25
Adder
2.387
232926CRISFLD1
Adder
1.91
232428Y3-058 C
Solar/Wind Harmer
0.811
234015AF2-250 C
Solar/Wind Harmer
0.117
233994AC2-023 GEN
Solar/Wind Harmer
2.612
231940T-011
Adder
0.726
232899W1-062
Adder
9.354
233946AB2-136 GEN
Solar/Wind Harmer
3.878
234036AF2-325 C
Solar/Wind Harmer
0.891
234041AC1-190 GEN
Solar/Wind Harmer
8.709
233952AC2-187 GEN
Solar/Wind Harmer
1.093
233954AC2-188 GEN
Solar/Wind Harmer
1.093
232910NRG_G1
Adder
8.38
233984AB2-036 GEN
Solar/Wind Harmer
12.079
232424Y1-079 C
Solar/Wind Harmer
0.545
234014AF1-036_GEN
Solar/Wind Harmer
2.621
232436AB1-176 C
Solar/Wind Harmer
0.222
233930AB2-032 GEN
Solar/Wind Harmer
0.805
233982AB2-133 GEN
Solar/Wind Harmer
4.706
228201CARL#2CT
Adder
5.92
228200CARL#1CT
Adder
5.63
228251CARLLS#4
Adder
0.543
228351V2-046C
Solar/Wind Harmer
1.732
230433AD2-135 GEN
Solar/Wind Harmer
0.087
230511AF1-262
Solar/Wind Harmer
0.157
228307PCLP GT
Adder
10.382
228754AB1-001 C
Solar/Wind Harmer
0.119
972233AH1-701 GEN
Adder
3.596
213589EDDYSTN4
Adder
68.158
213587EDDYSTN3
Adder
68.152
219904AC1-010 C
Solar/Wind Harmer
0.321
219272CLEANLIGHT C
Solar/Wind Harmer
0.155
219912AD2-042 GEN
Solar/Wind Harmer
0.675
219287REEVESEAST C
Solar/Wind Harmer
1.141
219906AC1-017 C
Solar/Wind Harmer
0.188
213815MOSER1-3
Adder
2.994
213815MOSER1-3
Adder
2.994
219607WPEMNERT C
Solar/Wind Harmer
0.353
219304NAMERICA C
Solar/Wind Harmer
0.262
213535CROYDN11
Adder
8.623
214067T20SOLAR
Solar/Wind Harmer
0.212
20720828JCB_W4-025
Solar/Wind Harmer
0.379
20636128O CRK C2
Adder
5.392
207459AE1-142 C O1
Solar/Wind Harmer
0.882
20628028LAKEHURS
Adder
0.795
20714828MDF_W3-079
Solar/Wind Harmer
0.255
219817TRENTONSOL C
Solar/Wind Harmer
0.921
20641628MLH_W1-032
Solar/Wind Harmer
0.245
20742028HF_AC1-207
Solar/Wind Harmer
0.654
217197RE CRAN C
Solar/Wind Harmer
0.448
218438BLK ROCK C
Solar/Wind Harmer
0.114
924131AB2-057 GEN
Solar/Wind Harmer
0.858
20635028RRCT1&2
Adder
9.687
20635128RRCT3&4
Adder
9.351
20635128RRCT3&4
Adder
8.157
218418LINDEN_G5
Adder
14.336
218419LINDEN_G6
Adder
14.336
972260AH1-715 GEN1
Adder
11.48
20675428EAM_W2-061
Solar/Wind Harmer
0.158
219036LINDEN_G7
Adder
13.962
219035LINDEN_G8
Adder
13.763
972261AH1-715 GEN2
Adder
13.365
217081WEATEXAS C
Solar/Wind Harmer
0.072
217202FBANKSOLAR C
Solar/Wind Harmer
0.061
217201HACKENSOLA C
Solar/Wind Harmer
0.061
972237AH1-703 GEN
Adder
8.446
217206BARNGR HS C
Solar/Wind Harmer
0.026
217086KRNY_131
Adder
7.776
217083KRNY_132
Adder
7.71
217204WCALDSOLAR C
Solar/Wind Harmer
0.061
20674328GAR_V4-001
Solar/Wind Harmer
0.092
20674828DL_W4-046
Solar/Wind Harmer
0.541
207471AF2-354 C
Solar/Wind Harmer
0.429
20634528N27_Y2-018
Solar/Wind Harmer
0.225
20675928HOL_W4-097
Solar/Wind Harmer
0.11
20465127PORT CT
Adder
3.337
20465527S.RDG CT
Adder
2.202
961541AF2-445A GEN
Solar/Wind Harmer
2.616
209010PEIP 1
Adder
2.851
209010PEIP 1
Adder
0.418
961431AF2-434 GEN
Solar/Wind Harmer
0.791
946751AF1-339 GEN
Solar/Wind Harmer
0.778
209130AF1-271A GEN
Solar/Wind Harmer
2.183
20464827MOUNT CT
Adder
1.958
20464827MOUNT CT
Adder
1.9
316411AF1-147_GEN1
Solar/Wind Helper
0.98
316006AB2-029 C
Solar/Wind Helper
0.132
316045AC1-158 PL2
Solar/Wind Helper
4.82
316450AC1-158 RIC
Solar/Wind Helper
0.402
966001AG1-469 GEN
Solar/Wind Helper
0.277
966871AG1-558 GEN
Solar/Wind Helper
0.343
316487AF1-042 GEN
Solar/Wind Helper
0.256
316312AB1-027
Solar/Wind Helper
0.481
316156AD2-030 GEN
Solar/Wind Helper
0.38
315666AE1-190 GEN
Solar/Wind Helper
0.338
315976AC1-164 GENA
Solar/Wind Helper
3.236
316169AC1-164_GENC
Solar/Wind Helper
2.795
3143526WINTERP
Solar/Wind Helper
1.301
3142946ENON
Solar/Wind Helper
0.025
316240AF1-291 C
Solar/Wind Helper
0.334
316033AB2-134 GEN
Solar/Wind Helper
0.855
316294AC1-161 GEN
Solar/Wind Helper
4.482
238147AE2-230_GEN1
Solar/Wind Helper
0.422
238148AE2-230_GEN2
Solar/Wind Helper
0.422
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316313AB2-026
Solar/Wind Helper
0.372
316185AD1-033 GEN
Solar/Wind Helper
1.148
3145506HICKORY
Solar/Wind Helper
0.972
3145506HICKORY
Solar/Wind Helper
0.583
3145506HICKORY
Solar/Wind Helper
0.146
316349AD2-085 GEN
Solar/Wind Helper
1.112
316339AD2-160 GEN
Solar/Wind Helper
0.927
316388AE2-253 GEN
Solar/Wind Helper
0.927
3137176SLIGO L2192
Solar/Wind Helper
0.965
3130086AYDLETT
Solar/Wind Helper
0.969
237061AD1-155 GEN
Solar/Wind Helper
1.514
3146386ELIZ CT
Solar/Wind Helper
0.241
316431W1029_GEN1
Solar/Wind Helper
0.972
316433W1029_GEN2
Solar/Wind Helper
0.972
316435W1029_GEN3
Solar/Wind Helper
0.972
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.24
3146626S HERTFORD
Solar/Wind Helper
0.239
3146626S HERTFORD
Solar/Wind Helper
0.239
3144356SAPONY
Solar/Wind Helper
0.429
316315AB2-025 C
Solar/Wind Helper
0.366
315614AA2-178 GEN
Solar/Wind Helper
1.437
3146776BUCKING
Solar/Wind Helper
0.93
3146776BUCKING
Solar/Wind Helper
0.075
316365GEN2_N
Solar/Wind Helper
0.888
3145893MURPHYS
Solar/Wind Helper
0.333
3145893MURPHYS
Solar/Wind Helper
0.418
3146173TUNIS
Solar/Wind Helper
0.231
3146173TUNIS
Solar/Wind Helper
0.231
316140AB2-099
Solar/Wind Helper
0.088
313506AB2-031 GEN
Solar/Wind Helper
1.045
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.137
3132123MT JACKSON
Solar/Wind Helper
0.716
3145593CAROLNA
Solar/Wind Helper
0.228
3145593CAROLNA
Solar/Wind Helper
0.228
3147133PAMPLIN
Solar/Wind Helper
0.228
3147133PAMPLIN
Solar/Wind Helper
0.183
3145796HORNRTN
Solar/Wind Helper
0.682
3145933PARMELE
Solar/Wind Helper
0.45
3145933PARMELE
Solar/Wind Helper
0.225
316237AB2-079_GEN
Solar/Wind Helper
0.302
200192DELTA CT1
50/50
1.567
200194DELTA CT3
50/50
1.567
200204Y1-065-CTG1
50/50
3.262
200054ROCKSP 3
50/50
2.076
232901NORTHST
Adder
8.101
234033AF1-007_GEN
Solar/Wind Harmer
36.192
233970AC1-092 C
Solar/Wind Harmer
2.608
233996TM1833_GEN
Solar/Wind Harmer
0.97
233998TM1NIN_3.36
Solar/Wind Harmer
0.97
232404W1-003 C
Solar/Wind Harmer
0.973
232408W1-005 C
Solar/Wind Harmer
0.973
232917OH NUG6
Adder
8.556
232915OH NUG4
Adder
8.537
972177AH1-672 GEN
Solar/Wind Harmer
13.07
232919VN10
Adder
2.73
232426Y1-080 FULL
Solar/Wind Harmer
0.186
232900DEMECSMY
Adder
8.973
232902EASTMUNI
Adder
12.659
234012AE2-112_GEN
Solar/Wind Harmer
2.228
233944AB2-135 GEN
Solar/Wind Harmer
5.063
233918AB1-142 GEN
Solar/Wind Harmer
0.957
972251AH1-710 GEN
Adder
42.982
231918WEST 1
Adder
3.199
231917EM10
Adder
2.237
228206SHRMN CT
Adder
14.293
228732V1-021 C
Adder
0.163
228260V4-054C
Solar/Wind Harmer
0.884
970997AG2-616 GEN
Solar/Wind Harmer
8.249
228729W2-030 C
Solar/Wind Harmer
0.495
228400MICK 1CT
Adder
10.117
213497CHSTR7-9
Adder
2.334
213497CHSTR7-9
Adder
2.334
219766PARADISE C
Solar/Wind Harmer
0.267
213958STHWK5-6
Adder
2.314
219686LUMSOLAR_N C
Solar/Wind Harmer
0.172
219907AC1-030 C
Solar/Wind Harmer
0.118
213560DLW11-12
Adder
2.303
219348LDSOLAR C
Solar/Wind Harmer
0.504
219222BRL12CT2
Adder
7.526
213611FALLS1-3
Adder
2.97
214194N WALES4
Adder
0.716
20716028EGP_W2-019
Solar/Wind Harmer
0.388
207522AF2-254 C
Solar/Wind Harmer
1.202
20717128DIX_Z2-102
Solar/Wind Harmer
1.105
20715828PEM_W1-120
Solar/Wind Harmer
0.447
963711AG1-223 GEN
Solar/Wind Harmer
1.236
20714528FRN_Y2-051
Solar/Wind Harmer
0.246
219276PARKLANDSO C
Solar/Wind Harmer
0.386
219680HOPEWELLV C1
Solar/Wind Harmer
0.063
20715228NPK_W1-113
Solar/Wind Harmer
0.359
20720528MAN_W1-024
Solar/Wind Harmer
0.212
20720428HOL_W1-112
Solar/Wind Harmer
0.289
20635828PARLN1&2
Adder
6.178
20635028RRCT1&2
Adder
9.839
218524CNTRALGAS1 C
Solar/Wind Harmer
0.308
218440SUMMTASSOC C
Solar/Wind Harmer
0.107
218428ETC SOLAR C
Solar/Wind Harmer
0.03
219908AB1-139 C
Solar/Wind Harmer
0.318
219919AE1-041 FULL
Solar/Wind Harmer
0.034
972275AH1-722 GEN
Adder
26.355
20673628F1S_V4-069
Solar/Wind Harmer
0.15
207528AF2-192 GEN
Solar/Wind Harmer
1.062
217209CENTRL HS C
Solar/Wind Harmer
0.037
20671828STAW2-080
Solar/Wind Harmer
0.088
217186ESSEX_G9
Adder
3.295
217121ECCF
Adder
0.362
217083KRNY_132
Adder
7.76
217208PARK ELE C
Solar/Wind Harmer
0.021
20676728BRNX1-095
Solar/Wind Harmer
0.147
966261AG1-495 GEN
Solar/Wind Harmer
2.938
207439AE1-081 C O1
Solar/Wind Harmer
0.05
20676328BVR_Y1-020
Solar/Wind Harmer
0.277
207530AG1-191 GEN
Solar/Wind Harmer
1.151
20674628WNG_W3-110
Solar/Wind Harmer
0.337
20676228FRD_X1-012
Solar/Wind Harmer
0.494
20675828AU_W4-064
Solar/Wind Harmer
0.145
20674928WA_W3-044
Solar/Wind Harmer
0.403
971519AH1-257 GEN
Solar/Wind Harmer
2.114
20675728RH_W2-091
Solar/Wind Harmer
0.506
207518AF1-320_GEN
Solar/Wind Harmer
3.066
207484AF2-139 C O1
Solar/Wind Harmer
0.424
20465127PORT CT
Adder
2.514
208909MACR G3
Adder
133.375
211065PSPA IPP
Solar/Wind Harmer
0.375
961301AF2-421 GEN
Solar/Wind Harmer
0.816
963151AG1-164 GEN
Solar/Wind Harmer
0.816
209023WIENIPP1
Adder
8.797
209025WIENIPP3
Adder
4.391
20465527S.RDG CT
Adder
2.276
963071AG1-156 GEN
Solar/Wind Harmer
8.021
209010PEIP 1
Adder
0.518
961341AF2-425 GEN
Solar/Wind Harmer
0.793
212507AE2-042_GEN
Solar/Wind Harmer
2.343
946731AF1-337 GEN
Solar/Wind Harmer
0.778
209018SUNBIPCT
Adder
5.784
209008PAXT IPP
Adder
1.603
209137AF2-361 C
Solar/Wind Harmer
2.171
208835TUHI V3-051
Solar/Wind Harmer
0.044
205967AE2-211_GEN
Solar/Wind Harmer
6.196
205932AD2-116_GEN
Solar/Wind Harmer
0.58
20465027TOLNA CT
Adder
2.298
208923BUSO V4-027
Solar/Wind Harmer
0.248
316415AF1-147_GEN2
Solar/Wind Helper
0.98
316447AC1-158 HLD
Solar/Wind Helper
3.315
316044AC1-158 PL1
Solar/Wind Helper
1.506
3147666LOUISA
Solar/Wind Helper
1.044
316192AB2-158 GEN
Solar/Wind Helper
1.757
316337AD2-073 GEN
Solar/Wind Helper
0.391
964211AG1-282 GEN
Solar/Wind Helper
0.343
3141726DUNNSVL
Solar/Wind Helper
1.019
316404AE1-155 C
Solar/Wind Helper
2.174
238175AF1-290_GEN
Solar/Wind Helper
0.137
3142416OLDCHRC
Solar/Wind Helper
0.656
3142416OLDCHRC
Solar/Wind Helper
0.251
3138133OCRAN
Solar/Wind Helper
0.151
3141766HARMONY
Solar/Wind Helper
0.05
315662AE1-191 GEN
Solar/Wind Helper
1.354
316280AD1-041 GEN
Solar/Wind Helper
0.846
315975AC1-164 GENB
Solar/Wind Helper
0.096
3142433PROV 92
Solar/Wind Helper
1.003
3143526WINTERP
Solar/Wind Helper
1.301
3142543TWELFTH
Solar/Wind Helper
0.024
3143226MDLTHAN
Solar/Wind Helper
0.25
316132AB2-190 GEN1
Solar/Wind Helper
1.416
315671AE2-027_GEN
Solar/Wind Helper
1.998
316369SG1_INVT
Solar/Wind Helper
1.191
3145336SMITFLD
Solar/Wind Helper
0.979
315773AC2-141 GEN
Solar/Wind Helper
5.274
238152AF2-075_GEN
Solar/Wind Helper
0.603
316381AD1-082 GEN
Solar/Wind Helper
1.267
316375AC2-012 GEN
Solar/Wind Helper
0.642
316036AC1-147 C
Solar/Wind Helper
0.372
316072AD1-144
Solar/Wind Helper
0.279
3146456SLIGO L269
Solar/Wind Helper
0.242
319010AE1-072 C
Solar/Wind Helper
2.775
316005AA1-067
Solar/Wind Helper
0.256
315687AD1-152 GEN
Solar/Wind Helper
1.202
3146516WINFALL
Solar/Wind Helper
0.778
3146516WINFALL
Solar/Wind Helper
0.24
315611Z1-036_GEN2
Solar/Wind Helper
1.309
3130156CHOWAN
Solar/Wind Helper
0.237
315816AE2-034 GEN
Solar/Wind Helper
1.078
3145663CRESWEL
Solar/Wind Helper
0.659
315737AD1-076 GEN
Solar/Wind Helper
2.285
3146776BUCKING
Solar/Wind Helper
0.093
316023GEN1_S
Solar/Wind Helper
0.888
3146206CASHIE
Solar/Wind Helper
0.232
233973AC2-185 C
Solar/Wind Harmer
5.27
970695AG2-447 GEN
Solar/Wind Harmer
3.486
233939AC1-091 C
Solar/Wind Harmer
2.608
233972AC1-094 C
Solar/Wind Harmer
2.095
233923SMA
Solar/Wind Harmer
3.556
233997TMININ_4.2
Solar/Wind Harmer
0.97
232406W1-004 FULL
Solar/Wind Harmer
0.973
232434Z2-077 GEN
Solar/Wind Harmer
0.243
232907VN8
Adder
29.221
232914OH NUG3
Adder
8.595
232916OH NUG5
Adder
8.595
232921TASLEY2G
Adder
5.023
233964AF2-378 GEN
Solar/Wind Harmer
0.124
232417X3-008 C
Solar/Wind Harmer
1.094
233950AC2-186 GEN
Solar/Wind Harmer
0.547
232422X3-066 FULL
Solar/Wind Harmer
0.242
233933AB2-153 GEN
Solar/Wind Harmer
1.087
233935AB2-179 C
Solar/Wind Harmer
2.395
228711V2-041C
Solar/Wind Harmer
0.518
230415AB2-049 C
Solar/Wind Harmer
0.163
213497CHSTR7-9
Adder
2.334
219623KINSLEYBEA C
Solar/Wind Harmer
0.364
219921AF1-264
Solar/Wind Harmer
0.123
219291REEVESSOUT C
Solar/Wind Harmer
0.051
213958STHWK5-6
Adder
2.314
218660EHAMPSOLAR C
Solar/Wind Harmer
0.148
219914AD2-027 C
Solar/Wind Harmer
0.509
219688LUMSOLAR_S C
Solar/Wind Harmer
0.172
219236SOUTHERNHQ C
Solar/Wind Harmer
0.057
213560DLW11-12
Adder
2.303
213815MOSER1-3
Adder
2.994
219221BRL12CT1
Adder
7.526
219223BRL12CT3
Adder
7.526
959561AF2-247 GEN
Solar/Wind Harmer
0.407
20716428NHV_W2-082
Solar/Wind Harmer
1.489
20715728PEM_W1-119
Solar/Wind Harmer
0.447
20636028O CRK C1
Adder
5.914
963391AG1-188 GEN
Solar/Wind Harmer
3.136
20714928UPF_X1-085
Solar/Wind Harmer
0.34
971667AH1-334 GEN
Solar/Wind Harmer
2.298
219114HARTZY_C
Solar/Wind Harmer
0.698
219727YARDVSOLFA C
Solar/Wind Harmer
0.761
219918AC2-009 C
Solar/Wind Harmer
0.021
207454AA2-184 E
Solar/Wind Harmer
0.834
219612MATRIX C
Solar/Wind Harmer
0.153
20716928W4-060COL
Solar/Wind Harmer
0.593
20635828PARLN1&2
Adder
2.798
20635928PARLN3&4
Adder
2.798
217213AMBOY SO C
Solar/Wind Harmer
0.106
219249CENTRALDIV C
Solar/Wind Harmer
0.033
207442AE1-156 GEN
Solar/Wind Harmer
0.621
20673728F2S_V4-070
Solar/Wind Harmer
0.15
217211CAMDEN ST C
Solar/Wind Harmer
0.02
217169METRODIV C
Solar/Wind Harmer
0.033
217194REDH C
Solar/Wind Harmer
0.411
20674528F3S_W2-016
Solar/Wind Harmer
1.177
207510AF2-138 C
Solar/Wind Harmer
1.488
207511W3-106 GEN
Solar/Wind Harmer
0.276
971007AG2-625 GEN
Solar/Wind Harmer
2.153
207437AD2-070 GEN
Solar/Wind Harmer
0.253
20671928W4-073
Solar/Wind Harmer
0.363
20633028GILCT9
Adder
23.779
20674128FR_U2-059
Solar/Wind Harmer
0.154
20466127PORT 5CT
Adder
22.184
20465427SHAW CT
Adder
3.226
209116AE2-175 GEN
Solar/Wind Harmer
3.423
211065PSPA IPP
Solar/Wind Harmer
0.375
205941AD2-115 GEN
Solar/Wind Harmer
0.763
963161AG1-165 GEN
Solar/Wind Harmer
0.816
209025WIENIPP3
Adder
4.303
970095AG2-074 GEN
Solar/Wind Harmer
5.08
208972BECR K09
Solar/Wind Harmer
0.854
961331AF2-424 GEN
Solar/Wind Harmer
0.793
961421AF2-433 GEN
Solar/Wind Harmer
0.791
957921AF2-086 GEN
Solar/Wind Harmer
0.769
209142AF1-226 GEN
Solar/Wind Harmer
4.58
209093AE2-110 GEN
Solar/Wind Harmer
1.978
209120AE2-241 GEN
Solar/Wind Harmer
2.617
946691AF1-333 GEN
Solar/Wind Harmer
0.778
946741AF1-338 GEN
Solar/Wind Harmer
0.778
209071AE2-133 GEN
Solar/Wind Harmer
1.314
972221AH1-695 GEN
Adder
108.793
208835TUHI V3-051
Solar/Wind Harmer
0.044
227287AC2-120 GEN
Solar/Wind Helper
0.415
226910AB2-157 C
Solar/Wind Helper
0.017
3141196NOKESVL
Solar/Wind Helper
1.133
966881AG1-559 GEN
Solar/Wind Helper
0.355
3132273ORANGE
Solar/Wind Helper
0.052
3147666LOUISA
Solar/Wind Helper
0.6
316223AC1-118
Solar/Wind Helper
0.396
3141906WESTMOR
Solar/Wind Helper
0.104
316077AC2-138 C
Solar/Wind Helper
0.241
316473AC1-191 GEN
Solar/Wind Helper
1.553
316484AD2-074 GEN
Solar/Wind Helper
0.489
316075AC2-137 C
Solar/Wind Helper
0.384
3142946ENON
Solar/Wind Helper
0.083
316458AB2-190 GEN2
Solar/Wind Helper
1.416
3145336SMITFLD
Solar/Wind Helper
0.098
3144536CHRHLND
Solar/Wind Helper
0.037
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.164
23546401DTGZ2-030
Solar/Wind Helper
0.076
316017AA1-139 ULT1
Solar/Wind Helper
1.112
3146456SLIGO L269
Solar/Wind Helper
0.242
316305AF2-043 C
Solar/Wind Helper
0.327
316246AF1-032 C
Solar/Wind Helper
0.278
316320Y1-086
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.368
3146516WINFALL
Solar/Wind Helper
0.24
3146626S HERTFORD
Solar/Wind Helper
0.239
3145273HOLLAND
Solar/Wind Helper
0.179
3146376EDENTON
Solar/Wind Helper
0.237
315735AD1-075 GEN1
Solar/Wind Helper
1.336
3146776BUCKING
Solar/Wind Helper
0.084
3146206CASHIE
Solar/Wind Helper
0.232
3145893MURPHYS
Solar/Wind Helper
0.929
3146926FARMVIL
Solar/Wind Helper
0.139
3146173TUNIS
Solar/Wind Helper
0.231
3156021HOLLOMANSOL
Solar/Wind Helper
1.763
3145683EARLEYS
Solar/Wind Helper
0.23
315607AA1-063A GEN
Solar/Wind Helper
1.317
316087AB2-174 GEN
Solar/Wind Helper
1.612
3146263WOODLND
Solar/Wind Helper
0.23
3145963POPLR C
Solar/Wind Helper
0.229
3145823KELFORD
Solar/Wind Helper
0.229
3145783HORNRTN
Solar/Wind Helper
0.228
3145796HORNRTN
Solar/Wind Helper
0.75
3145796HORNRTN
Solar/Wind Helper
0.227
316034AC1-036 C
Solar/Wind Helper
0.238
315785AD2-033 C
Solar/Wind Helper
2.641
3147983MERCK5
Solar/Wind Helper
0.09
316129AC1-054 GEN
Solar/Wind Helper
1.119
316131AB2-060 GEN
Solar/Wind Helper
1.373
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145893MURPHYS
Solar/Wind Helper
0.083
3145893MURPHYS
Solar/Wind Helper
0.232
3146926FARMVIL
Solar/Wind Helper
0.139
3146173TUNIS
Solar/Wind Helper
0.231
966621AG1-532 GEN
Solar/Wind Helper
0.21
3146263WOODLND
Solar/Wind Helper
0.23
942461AE2-259 GEN
Solar/Wind Helper
1.549
316181AB2-040 GEN
Solar/Wind Helper
1.651
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3145963POPLR C
Solar/Wind Helper
0.229
3147043LAWRENC
Solar/Wind Helper
0.137
316190AA2-174 GEN
Solar/Wind Helper
0.015
316011AB1-132 GEN
Solar/Wind Helper
2.467
316317KELFORD C
Solar/Wind Helper
0.206
3145823KELFORD
Solar/Wind Helper
0.229
315821AE2-092 GEN
Solar/Wind Helper
2.125
3147133PAMPLIN
Solar/Wind Helper
0.717
316478AD1-087 GEN
Solar/Wind Helper
1.116
3145796HORNRTN
Solar/Wind Helper
0.909
3145796HORNRTN
Solar/Wind Helper
0.227
316212AC1-099_GEN
Solar/Wind Helper
1.013
3145933PARMELE
Solar/Wind Helper
0.225
316499AE2-029_GEN
Solar/Wind Helper
0.757
3148013FISHERV
Solar/Wind Helper
0.224
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.043
VTFLTFEXP_VFT->PJM
CMTX
113.065
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.489
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.9
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.7
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.882
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
42.787
CBM NorthLTFEXP_CBM-N->PJM
CBM
65.935
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-3835T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-3835T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.99 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3624.44
MW Contribution:
2.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
1.564
200194DELTA CT3
50/50
1.564
200204Y1-065-CTG1
50/50
3.255
200054ROCKSP 3
50/50
2.072
232901NORTHST
Adder
8.082
234033AF1-007_GEN
Solar/Wind Harmer
13.407
233970AC1-092 C
Solar/Wind Harmer
1.751
232404W1-003 C
Solar/Wind Harmer
0.627
232408W1-005 C
Solar/Wind Harmer
0.627
232917OH NUG6
Adder
8.537
232915OH NUG4
Adder
8.518
972177AH1-672 GEN
Solar/Wind Harmer
9.886
232919VN10
Adder
2.724
232900DEMECSMY
Adder
8.952
232902EASTMUNI
Adder
12.63
234012AE2-112_GEN
Solar/Wind Harmer
2.247
233918AB1-142 GEN
Solar/Wind Harmer
0.246
972251AH1-710 GEN
Adder
42.883
231918WEST 1
Adder
3.192
231917EM10
Adder
2.231
228206SHRMN CT
Adder
14.258
228732V1-021 C
Adder
0.163
970997AG2-616 GEN
Solar/Wind Harmer
6.191
228400MICK 1CT
Adder
10.092
213497CHSTR7-9
Adder
2.328
213497CHSTR7-9
Adder
2.328
213958STHWK5-6
Adder
2.308
213560DLW11-12
Adder
2.297
219222BRL12CT2
Adder
7.507
213611FALLS1-3
Adder
2.963
214194N WALES4
Adder
0.714
207522AF2-254 C
Solar/Wind Harmer
0.775
20635828PARLN1&2
Adder
6.162
20635028RRCT1&2
Adder
9.813
218524CNTRALGAS1 C
Solar/Wind Harmer
0.636
972275AH1-722 GEN
Adder
26.286
207528AF2-192 GEN
Solar/Wind Harmer
0.598
217186ESSEX_G9
Adder
3.286
217121ECCF
Adder
0.362
217083KRNY_132
Adder
7.739
966261AG1-495 GEN
Solar/Wind Harmer
1.431
971519AH1-257 GEN
Solar/Wind Harmer
1.362
20465127PORT CT
Adder
2.507
208909MACR G3
Adder
132.999
209023WIENIPP1
Adder
8.772
209025WIENIPP3
Adder
4.379
20465527S.RDG CT
Adder
2.267
963071AG1-156 GEN
Solar/Wind Harmer
6.123
209010PEIP 1
Adder
0.517
212507AE2-042_GEN
Solar/Wind Harmer
0.479
209018SUNBIPCT
Adder
5.767
970757AG2-479 GEN
Solar/Wind Harmer
0.61
209008PAXT IPP
Adder
1.596
205967AE2-211_GEN
Solar/Wind Harmer
3.973
205932AD2-116_GEN
Solar/Wind Harmer
0.072
970753AG2-477 GEN
Solar/Wind Harmer
0.06
20465027TOLNA CT
Adder
2.278
316415AF1-147_GEN2
Solar/Wind Helper
0.977
316447AC1-158 HLD
Solar/Wind Helper
3.306
316044AC1-158 PL1
Solar/Wind Helper
1.502
3147666LOUISA
Solar/Wind Helper
1.041
316192AB2-158 GEN
Solar/Wind Helper
1.752
316337AD2-073 GEN
Solar/Wind Helper
0.39
238175AF1-290_GEN
Solar/Wind Helper
0.138
964211AG1-282 GEN
Solar/Wind Helper
0.343
3141726DUNNSVL
Solar/Wind Helper
1.017
316404AE1-155 C
Solar/Wind Helper
2.169
3142416OLDCHRC
Solar/Wind Helper
0.654
3142416OLDCHRC
Solar/Wind Helper
0.25
3138133OCRAN
Solar/Wind Helper
0.151
3141766HARMONY
Solar/Wind Helper
0.05
315662AE1-191 GEN
Solar/Wind Helper
1.35
316280AD1-041 GEN
Solar/Wind Helper
0.844
315975AC1-164 GENB
Solar/Wind Helper
0.095
3142433PROV 92
Solar/Wind Helper
1
3143526WINTERP
Solar/Wind Helper
1.298
3142543TWELFTH
Solar/Wind Helper
0.024
3143226MDLTHAN
Solar/Wind Helper
0.249
316132AB2-190 GEN1
Solar/Wind Helper
1.413
315671AE2-027_GEN
Solar/Wind Helper
1.993
316369SG1_INVT
Solar/Wind Helper
1.187
3145336SMITFLD
Solar/Wind Helper
0.977
315773AC2-141 GEN
Solar/Wind Helper
5.26
238152AF2-075_GEN
Solar/Wind Helper
0.602
316381AD1-082 GEN
Solar/Wind Helper
1.264
316375AC2-012 GEN
Solar/Wind Helper
0.64
316036AC1-147 C
Solar/Wind Helper
0.371
316072AD1-144
Solar/Wind Helper
0.278
3146456SLIGO L269
Solar/Wind Helper
0.242
972281AH1-725 GEN
50/50
137.55
200201DELTA2 CT2
50/50
2.799
200034PCHBTM 2
50/50
16.321
200035PCHBTM 3
50/50
16.185
200205Y1-065-CTG2
50/50
3.255
233971AC1-093 C
Solar/Wind Harmer
1.751
232410W1-006 C
Solar/Wind Harmer
0.627
232918OH NUG7
Adder
8.518
232905CHERITON_25
Adder
2.382
232926CRISFLD1
Adder
1.906
231940T-011
Adder
0.724
232899W1-062
Adder
9.333
234041AC1-190 GEN
Solar/Wind Harmer
7.072
232910NRG_G1
Adder
8.361
233984AB2-036 GEN
Solar/Wind Harmer
7.033
234014AF1-036_GEN
Solar/Wind Harmer
2.247
233930AB2-032 GEN
Solar/Wind Harmer
0.924
228201CARL#2CT
Adder
5.906
228200CARL#1CT
Adder
5.617
228251CARLLS#4
Adder
0.542
228307PCLP GT
Adder
10.356
972233AH1-701 GEN
Adder
3.587
213589EDDYSTN4
Adder
67.989
213587EDDYSTN3
Adder
67.984
213815MOSER1-3
Adder
2.986
213815MOSER1-3
Adder
2.986
219304NAMERICA C
Solar/Wind Harmer
0.076
213535CROYDN11
Adder
8.601
20636128O CRK C2
Adder
5.379
20628028LAKEHURS
Adder
0.793
20714828MDF_W3-079
Solar/Wind Harmer
0.082
20635028RRCT1&2
Adder
9.662
20635128RRCT3&4
Adder
9.327
20635128RRCT3&4
Adder
8.136
218418LINDEN_G5
Adder
14.298
218419LINDEN_G6
Adder
14.298
972260AH1-715 GEN1
Adder
11.449
219036LINDEN_G7
Adder
13.925
219035LINDEN_G8
Adder
13.726
972261AH1-715 GEN2
Adder
13.33
972237AH1-703 GEN
Adder
8.423
217086KRNY_131
Adder
7.755
217083KRNY_132
Adder
7.69
20465127PORT CT
Adder
3.327
20465527S.RDG CT
Adder
2.194
961541AF2-445A GEN
Solar/Wind Harmer
1.807
209010PEIP 1
Adder
2.843
209010PEIP 1
Adder
0.416
970761AG2-481 GEN
Solar/Wind Harmer
0.614
209130AF1-271A GEN
Solar/Wind Harmer
1.519
20464827MOUNT CT
Adder
1.936
20464827MOUNT CT
Adder
1.879
316411AF1-147_GEN1
Solar/Wind Helper
0.977
200200DELTA2 CT1
50/50
2.799
200193DELTA CT2
50/50
1.564
200203Y1-065-STG
50/50
5.638
200055ROCKSP 4
50/50
2.036
233987AB2-037 GEN
Solar/Wind Harmer
-0.001
233973AC2-185 C
Solar/Wind Harmer
1.751
970695AG2-447 GEN
Solar/Wind Harmer
2.427
233939AC1-091 C
Solar/Wind Harmer
1.751
233972AC1-094 C
Solar/Wind Harmer
1.751
232406W1-004 FULL
Solar/Wind Harmer
0.627
232434Z2-077 GEN
Solar/Wind Harmer
0.04
232907VN8
Adder
29.155
232914OH NUG3
Adder
8.575
232916OH NUG5
Adder
8.575
232921TASLEY2G
Adder
5.012
232422X3-066 FULL
Solar/Wind Harmer
0.08
233935AB2-179 C
Solar/Wind Harmer
1.314
213497CHSTR7-9
Adder
2.328
213958STHWK5-6
Adder
2.308
213560DLW11-12
Adder
2.297
213815MOSER1-3
Adder
2.986
219221BRL12CT1
Adder
7.507
219223BRL12CT3
Adder
7.507
20636028O CRK C1
Adder
5.899
963391AG1-188 GEN
Solar/Wind Harmer
1.527
971667AH1-334 GEN
Solar/Wind Harmer
1.481
20635828PARLN1&2
Adder
2.791
20635928PARLN3&4
Adder
2.791
207442AE1-156 GEN
Solar/Wind Harmer
0.049
971007AG2-625 GEN
Solar/Wind Harmer
1.387
207437AD2-070 GEN
Solar/Wind Harmer
0.055
20633028GILCT9
Adder
23.712
20466127PORT 5CT
Adder
22.122
20465427SHAW CT
Adder
3.217
205941AD2-115 GEN
Solar/Wind Harmer
0.095
209025WIENIPP3
Adder
4.29
970095AG2-074 GEN
Solar/Wind Harmer
4.061
209142AF1-226 GEN
Solar/Wind Harmer
2.23
209093AE2-110 GEN
Solar/Wind Harmer
1.275
209120AE2-241 GEN
Solar/Wind Harmer
1.275
972221AH1-695 GEN
Adder
108.273
970767AG2-484 GEN
Solar/Wind Harmer
0.585
970755AG2-478 GEN
Solar/Wind Harmer
0.059
227287AC2-120 GEN
Solar/Wind Helper
0.416
226910AB2-157 C
Solar/Wind Helper
0.017
3141196NOKESVL
Solar/Wind Helper
1.13
966881AG1-559 GEN
Solar/Wind Helper
0.354
3132273ORANGE
Solar/Wind Helper
0.052
3147666LOUISA
Solar/Wind Helper
0.599
200202DELTA2 ST
50/50
4.74
200195DELTA ST
50/50
2.416
200052ROCKSP 1
50/50
2.048
200053ROCKSP 2
50/50
2.008
232904IR4
Adder
78.494
232432Z2-076 GEN
Solar/Wind Harmer
0.013
232912OH NUG1
Adder
8.575
232913OH NUG2
Adder
8.461
232920IR10
Adder
3.068
971195AH1-057 GEN
Solar/Wind Harmer
0.607
232813VAUGHN
Adder
0.57
233968AD2-076_GEN
Solar/Wind Harmer
2.247
970597AG2-380 GEN
Solar/Wind Harmer
4.024
231906DC3 NUG
Adder
13.515
231902DC CT7
Adder
10.805
231907DC10
Adder
3.374
233915AB1-141 GEN
Solar/Wind Harmer
0.246
231919CHRIST1
Adder
4.197
231920CHRIST2
Adder
4.104
970453AG2-297 GEN
Solar/Wind Harmer
2.193
972141AH1-641 GEN
Solar/Wind Harmer
1.34
230430AE1-229_GEN
Solar/Wind Harmer
17.026
964001AG1-254 GEN
Solar/Wind Harmer
4.839
230422AE1-104_GEN1
Solar/Wind Harmer
11.603
230425AE1-104_GEN2
Solar/Wind Harmer
11.603
213942SCHUYLKILL
Adder
3.019
213942SCHUYLKILL
Adder
2.309
213957STHWK3-4
Adder
2.308
213957STHWK3-4
Adder
2.308
213561DLWR9-10
Adder
3.004
213561DLWR9-10
Adder
2.297
219224BRL12CT4
Adder
7.507
213611FALLS1-3
Adder
2.963
213611FALLS1-3
Adder
2.963
207487AE2-000G4
Solar/Wind Harmer
10.554
207497AE2-000G2
Solar/Wind Harmer
10.554
207500AE2-000G1
Solar/Wind Harmer
10.554
207507AE2-000G3
Solar/Wind Harmer
10.554
963401AG1-189 GEN
Solar/Wind Harmer
0.938
970025AG2-016 GEN
Solar/Wind Harmer
1.528
971189AH1-054 GEN
Solar/Wind Harmer
0.636
971521AH1-258 GEN
Solar/Wind Harmer
1.456
20635928PARLN3&4
Adder
6.162
218526CNTRALGAS2 C
Solar/Wind Harmer
0.637
217167KRNY_14
Adder
7.739
217086KRNY_131
Adder
7.673
217147KRNY_1212
Adder
7.361
217147KRNY_1212
Adder
7.23
217146KRNY_1234
Adder
7.213
217146KRNY_1234
Adder
7.164
971009AG2-626 GEN
Solar/Wind Harmer
0.885
20462827N BANGR8
Adder
0.599
209026WIENIPP4
Adder
4.334
20486527WR_V4-052
Adder
0.884
208862AG1-362 C
Solar/Wind Harmer
0.49
209027LOR2_Q27
Solar/Wind Harmer
0
209030FRFA O01
Adder
0.191
205951AE1-129_GEN
Solar/Wind Harmer
0.111
205956AE1-196_GEN
Solar/Wind Harmer
0.024
20465027TOLNA CT
Adder
2.369
205943AE1-185 GEN
Solar/Wind Harmer
0.024
20390726Y2-042
Adder
2.283
200917MEHOOPANY_G
Solar/Wind Harmer
0.308
20334726NME_Y1-047
Adder
2.07
226929AD2-058 GEN
Solar/Wind Helper
0.119
3138216PACIFIC
Solar/Wind Helper
0.049
3141426STAFORD
Solar/Wind Helper
0.062
315651AD1-115 GEN
Solar/Wind Helper
0.907
316164AC1-076 GEN
Solar/Wind Helper
1.281
316468AD1-105 GEN
Solar/Wind Helper
1.243
3141813NORNECK
Solar/Wind Helper
0.255
238169AE2-226 GEN1
Solar/Wind Helper
0.616
238170AE2-226 GEN2
Solar/Wind Helper
0.616
3141783LANCAST
Solar/Wind Helper
0.151
3141783LANCAST
Solar/Wind Helper
0.101
3138133OCRAN
Solar/Wind Helper
0.075
3141913WHIT STONE
Solar/Wind Helper
0.251
316059AD1-063 C
Solar/Wind Helper
0.253
957601AF2-054 GEN
Solar/Wind Helper
0.336
3141873WAN 176
Solar/Wind Helper
0.05
3143873LANEXA
Solar/Wind Helper
0.15
316233AE1-074 FULL
Solar/Wind Helper
0.381
957831AF2-077 GEN
Solar/Wind Helper
0.335
316382AG1-145 C
Solar/Wind Helper
0.334
316159AE1-175 C
Solar/Wind Helper
0.376
315697AD1-025 GEN
Solar/Wind Helper
2.817
315839AE2-212 C
Solar/Wind Helper
0.331
316236AE1-162_GEN
Solar/Wind Helper
0.329
3143316POE
Solar/Wind Helper
0.966
316258AE1-075 C
Solar/Wind Helper
0.334
316405AF2-144 C
Solar/Wind Helper
0.278
316316AC1-027 C
Solar/Wind Helper
0.384
316018AA1-139 ULT2
Solar/Wind Helper
1.043
313526AB2-022
Solar/Wind Helper
0.368
3146486SUNBURY
Solar/Wind Helper
0.24
3146486SUNBURY
Solar/Wind Helper
0.24
3145176PASQUOTANK
Solar/Wind Helper
0.149
315800Z1-036_GEN1
Solar/Wind Helper
1.306
3130156CHOWAN
Solar/Wind Helper
0.237
3130156CHOWAN
Solar/Wind Helper
0.237
3130546PLYMOUTH
Solar/Wind Helper
0.233
315732AD1-074 GEN1
Solar/Wind Helper
2.665
315733AD1-074 GEN2
Solar/Wind Helper
2.665
316322AB2-045
Solar/Wind Helper
0.259
3146206CASHIE
Solar/Wind Helper
0.232
3145893MURPHYS
Solar/Wind Helper
0.625
3145893MURPHYS
Solar/Wind Helper
0.232
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.007
316463AE2-346 GEN
Solar/Wind Helper
0.211
3145513AHOSKIE
Solar/Wind Helper
0.103
961941AG1-037 GEN
Solar/Wind Helper
0.078
3145513AHOSKIE
Solar/Wind Helper
0.23
946281AF1-292 GEN
Solar/Wind Helper
0.231
3146043SEABORD
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.46
3145683EARLEYS
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.23
3137643SOCKMAN
Solar/Wind Helper
0.912
316426AA2-053 GEN
Solar/Wind Helper
1.305
316174AB2-169 GEN
Solar/Wind Helper
0.583
316486AD2-202 GEN
Solar/Wind Helper
0.326
3145796HORNRTN
Solar/Wind Helper
0.726
3145796HORNRTN
Solar/Wind Helper
0.091
3146033SCOT NK
Solar/Wind Helper
0.905
3144303KENBRDG
Solar/Wind Helper
0.181
316210AC1-098 GEN
Solar/Wind Helper
1.818
316274AC1-208 GEN
Solar/Wind Helper
1.37
316238AB2-078_GEN
Solar/Wind Helper
0.302
316239AB2-077_GEN
Solar/Wind Helper
0.302
3148133STUARTS
Solar/Wind Helper
0.134
3148013FISHERV
Solar/Wind Helper
0.128
3145746EVERETS
Solar/Wind Helper
0.886
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
319010AE1-072 C
Solar/Wind Helper
2.768
3146516WINFALL
Solar/Wind Helper
0.776
3146516WINFALL
Solar/Wind Helper
0.239
315611Z1-036_GEN2
Solar/Wind Helper
1.306
3130156CHOWAN
Solar/Wind Helper
0.237
315816AE2-034 GEN
Solar/Wind Helper
1.075
3145663CRESWEL
Solar/Wind Helper
0.657
315737AD1-076 GEN
Solar/Wind Helper
2.279
3146776BUCKING
Solar/Wind Helper
0.093
316023GEN1_S
Solar/Wind Helper
0.885
3146206CASHIE
Solar/Wind Helper
0.232
3145893MURPHYS
Solar/Wind Helper
0.927
3146926FARMVIL
Solar/Wind Helper
0.138
3146173TUNIS
Solar/Wind Helper
0.231
3156021HOLLOMANSOL
Solar/Wind Helper
1.758
3145683EARLEYS
Solar/Wind Helper
0.23
315607AA1-063A GEN
Solar/Wind Helper
1.314
316087AB2-174 GEN
Solar/Wind Helper
1.607
3146263WOODLND
Solar/Wind Helper
0.229
3145963POPLR C
Solar/Wind Helper
0.228
3145823KELFORD
Solar/Wind Helper
0.228
3145783HORNRTN
Solar/Wind Helper
0.227
3145796HORNRTN
Solar/Wind Helper
0.748
3145796HORNRTN
Solar/Wind Helper
0.227
316034AC1-036 C
Solar/Wind Helper
0.237
315785AD2-033 C
Solar/Wind Helper
2.634
3147983MERCK5
Solar/Wind Helper
0.09
316129AC1-054 GEN
Solar/Wind Helper
1.116
23777901MDS_W4-102
Solar/Wind Helper
0.141
316131AB2-060 GEN
Solar/Wind Helper
1.369
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
316006AB2-029 C
Solar/Wind Helper
0.131
316045AC1-158 PL2
Solar/Wind Helper
4.808
316450AC1-158 RIC
Solar/Wind Helper
0.401
966001AG1-469 GEN
Solar/Wind Helper
0.276
966871AG1-558 GEN
Solar/Wind Helper
0.342
316487AF1-042 GEN
Solar/Wind Helper
0.255
316312AB1-027
Solar/Wind Helper
0.48
315666AE1-190 GEN
Solar/Wind Helper
0.338
316156AD2-030 GEN
Solar/Wind Helper
0.379
315976AC1-164 GENA
Solar/Wind Helper
3.228
316169AC1-164_GENC
Solar/Wind Helper
2.788
3143526WINTERP
Solar/Wind Helper
1.298
3142946ENON
Solar/Wind Helper
0.025
316240AF1-291 C
Solar/Wind Helper
0.333
316033AB2-134 GEN
Solar/Wind Helper
0.853
316294AC1-161 GEN
Solar/Wind Helper
4.47
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238148AE2-230_GEN2
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.371
316185AD1-033 GEN
Solar/Wind Helper
1.145
3145506HICKORY
Solar/Wind Helper
0.97
3145506HICKORY
Solar/Wind Helper
0.582
3145506HICKORY
Solar/Wind Helper
0.145
316349AD2-085 GEN
Solar/Wind Helper
1.109
316339AD2-160 GEN
Solar/Wind Helper
0.924
316388AE2-253 GEN
Solar/Wind Helper
0.924
3137176SLIGO L2192
Solar/Wind Helper
0.962
3130086AYDLETT
Solar/Wind Helper
0.966
237061AD1-155 GEN
Solar/Wind Helper
1.511
3146386ELIZ CT
Solar/Wind Helper
0.241
316431W1029_GEN1
Solar/Wind Helper
0.969
316433W1029_GEN2
Solar/Wind Helper
0.969
316435W1029_GEN3
Solar/Wind Helper
0.969
3146516WINFALL
Solar/Wind Helper
0.239
3146516WINFALL
Solar/Wind Helper
0.239
3146516WINFALL
Solar/Wind Helper
0.239
3146626S HERTFORD
Solar/Wind Helper
0.239
3146626S HERTFORD
Solar/Wind Helper
0.239
3144356SAPONY
Solar/Wind Helper
0.428
316315AB2-025 C
Solar/Wind Helper
0.365
315614AA2-178 GEN
Solar/Wind Helper
1.434
3146776BUCKING
Solar/Wind Helper
0.928
3146776BUCKING
Solar/Wind Helper
0.075
316365GEN2_N
Solar/Wind Helper
0.885
3145893MURPHYS
Solar/Wind Helper
0.332
3145893MURPHYS
Solar/Wind Helper
0.417
3146173TUNIS
Solar/Wind Helper
0.231
3146173TUNIS
Solar/Wind Helper
0.231
316140AB2-099
Solar/Wind Helper
0.088
313506AB2-031 GEN
Solar/Wind Helper
1.042
3142666NORTHAMPTON
Solar/Wind Helper
0.228
3142666NORTHAMPTON
Solar/Wind Helper
0.228
3142666NORTHAMPTON
Solar/Wind Helper
0.228
3142666NORTHAMPTON
Solar/Wind Helper
0.137
3132123MT JACKSON
Solar/Wind Helper
0.715
3145593CAROLNA
Solar/Wind Helper
0.228
3145593CAROLNA
Solar/Wind Helper
0.228
3147133PAMPLIN
Solar/Wind Helper
0.228
3147133PAMPLIN
Solar/Wind Helper
0.182
3145796HORNRTN
Solar/Wind Helper
0.68
3145933PARMELE
Solar/Wind Helper
0.449
3145933PARMELE
Solar/Wind Helper
0.224
235020AA1-095 C
Solar/Wind Helper
0.042
316237AB2-079_GEN
Solar/Wind Helper
0.302
316005AA1-067
Solar/Wind Helper
0.255
316223AC1-118
Solar/Wind Helper
0.395
3141906WESTMOR
Solar/Wind Helper
0.103
316077AC2-138 C
Solar/Wind Helper
0.24
316473AC1-191 GEN
Solar/Wind Helper
1.549
316484AD2-074 GEN
Solar/Wind Helper
0.488
316075AC2-137 C
Solar/Wind Helper
0.383
3142946ENON
Solar/Wind Helper
0.083
316458AB2-190 GEN2
Solar/Wind Helper
1.413
3145336SMITFLD
Solar/Wind Helper
0.098
3144536CHRHLND
Solar/Wind Helper
0.037
23546401DTGZ2-030
Solar/Wind Helper
0.076
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.164
316017AA1-139 ULT1
Solar/Wind Helper
1.109
3146456SLIGO L269
Solar/Wind Helper
0.242
316305AF2-043 C
Solar/Wind Helper
0.326
316246AF1-032 C
Solar/Wind Helper
0.277
316320Y1-086
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.367
3146516WINFALL
Solar/Wind Helper
0.239
3146626S HERTFORD
Solar/Wind Helper
0.239
3145273HOLLAND
Solar/Wind Helper
0.179
3146376EDENTON
Solar/Wind Helper
0.237
315735AD1-075 GEN1
Solar/Wind Helper
1.333
3146776BUCKING
Solar/Wind Helper
0.083
3146206CASHIE
Solar/Wind Helper
0.232
3145893MURPHYS
Solar/Wind Helper
0.083
3145893MURPHYS
Solar/Wind Helper
0.232
3146926FARMVIL
Solar/Wind Helper
0.138
3146173TUNIS
Solar/Wind Helper
0.231
966621AG1-532 GEN
Solar/Wind Helper
0.209
3146263WOODLND
Solar/Wind Helper
0.229
942461AE2-259 GEN
Solar/Wind Helper
1.545
316181AB2-040 GEN
Solar/Wind Helper
1.646
3142666NORTHAMPTON
Solar/Wind Helper
0.228
3145963POPLR C
Solar/Wind Helper
0.228
3147043LAWRENC
Solar/Wind Helper
0.137
316190AA2-174 GEN
Solar/Wind Helper
0.015
316011AB1-132 GEN
Solar/Wind Helper
2.46
316317KELFORD C
Solar/Wind Helper
0.205
3145823KELFORD
Solar/Wind Helper
0.228
315821AE2-092 GEN
Solar/Wind Helper
2.119
3147133PAMPLIN
Solar/Wind Helper
0.715
316478AD1-087 GEN
Solar/Wind Helper
1.113
3145796HORNRTN
Solar/Wind Helper
0.907
3145796HORNRTN
Solar/Wind Helper
0.227
316212AC1-099_GEN
Solar/Wind Helper
1.01
3145933PARMELE
Solar/Wind Helper
0.224
316499AE2-029_GEN
Solar/Wind Helper
0.755
3148013FISHERV
Solar/Wind Helper
0.224
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.028
VTFLTFEXP_VFT->PJM
CMTX
112.763
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.476
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.891
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.639
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.841
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
42.674
CBM NorthLTFEXP_CBM-N->PJM
CBM
65.754
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.62 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3458.01
MW Contribution:
2.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
3.907
200195DELTA ST
50/50
1.991
200052ROCKSP 1
50/50
1.686
200053ROCKSP 2
50/50
1.653
232904IR4
Adder
64.11
232432Z2-076 GEN
Solar/Wind Harmer
0.105
232920IR10
Adder
2.506
233901CHERRYDALE C
Solar/Wind Harmer
0.892
232912OH NUG1
Adder
7.003
232913OH NUG2
Adder
6.91
233940AF2-379 C
Solar/Wind Harmer
0.148
971195AH1-057 GEN
Solar/Wind Harmer
0.773
233955AB2-172 GEN
Solar/Wind Harmer
3.959
232813VAUGHN
Adder
0.466
233968AD2-076_GEN
Solar/Wind Harmer
5.226
970597AG2-380 GEN
Solar/Wind Harmer
3.282
231906DC3 NUG
Adder
11.024
231902DC CT7
Adder
8.813
231907DC10
Adder
2.752
233915AB1-141 GEN
Solar/Wind Harmer
0.778
231919CHRIST1
Adder
3.418
231920CHRIST2
Adder
3.342
970453AG2-297 GEN
Solar/Wind Harmer
1.938
972141AH1-641 GEN
Solar/Wind Harmer
2.013
230430AE1-229_GEN
Solar/Wind Harmer
20.033
964001AG1-254 GEN
Solar/Wind Harmer
5.098
230422AE1-104_GEN1
Solar/Wind Harmer
23.58
230425AE1-104_GEN2
Solar/Wind Harmer
23.58
228728W1-130C
Solar/Wind Harmer
0.464
230434AG1-499 GEN
Solar/Wind Harmer
0.404
230407AD2-065 C
Solar/Wind Harmer
0.092
227927V4-067C
Solar/Wind Harmer
0.138
219137THOSOLAR C
Solar/Wind Harmer
0.839
219258KINSLEYDEP C
Solar/Wind Harmer
0.224
213942SCHUYLKILL
Adder
2.455
213942SCHUYLKILL
Adder
1.877
213957STHWK3-4
Adder
1.876
213957STHWK3-4
Adder
1.876
213561DLWR9-10
Adder
2.444
213561DLWR9-10
Adder
1.869
219615MILLCREEK C
Solar/Wind Harmer
0.164
219610FLORENCE C
Solar/Wind Harmer
0.949
219224BRL12CT4
Adder
6.116
213611FALLS1-3
Adder
2.414
213611FALLS1-3
Adder
2.414
20720728JCB_W1-129
Solar/Wind Harmer
0.203
20715028HAN_X4-015
Solar/Wind Harmer
0.203
207487AE2-000G4
Solar/Wind Harmer
21.434
207497AE2-000G2
Solar/Wind Harmer
21.434
207500AE2-000G1
Solar/Wind Harmer
21.434
207507AE2-000G3
Solar/Wind Harmer
21.434
963401AG1-189 GEN
Solar/Wind Harmer
1.547
970025AG2-016 GEN
Solar/Wind Harmer
1.927
971189AH1-054 GEN
Solar/Wind Harmer
0.803
207445AB1-138_GEN
Solar/Wind Harmer
0.394
219620RIDERU C
Solar/Wind Harmer
0.038
20714428HOW_X1-037
Solar/Wind Harmer
0.838
20720628TIN_W1-124
Solar/Wind Harmer
0.675
20716228APLW2-078
Solar/Wind Harmer
0.599
971521AH1-258 GEN
Solar/Wind Harmer
1.837
20635928PARLN3&4
Adder
5.022
218526CNTRALGAS2 C
Solar/Wind Harmer
0.251
20675528CPH_W2-050
Solar/Wind Harmer
0.389
20673828FLE_V3-070
Solar/Wind Harmer
0.316
20676128MHD_W3-029
Solar/Wind Harmer
0.324
218449LINSOLAR C
Solar/Wind Harmer
0.682
20676428JCR_X2-075
Solar/Wind Harmer
0.232
217167KRNY_14
Adder
6.305
217086KRNY_131
Adder
6.251
217147KRNY_1212
Adder
5.997
217147KRNY_1212
Adder
5.89
217146KRNY_1234
Adder
5.877
217146KRNY_1234
Adder
5.836
964851AG1-348 GEN
Solar/Wind Harmer
0.929
971009AG2-626 GEN
Solar/Wind Harmer
1.114
207408W3-077 C
Solar/Wind Harmer
0.345
20675128HRM_W1-127
Solar/Wind Harmer
0.116
20462827N BANGR8
Adder
0.487
961261AF2-417 GEN
Solar/Wind Harmer
0.665
209026WIENIPP4
Adder
3.535
209027LOR2_Q27
Solar/Wind Harmer
2.962
212266LOR1
Solar/Wind Harmer
0.785
20486527WR_V4-052
Adder
0.706
209029WAYMART-WD
Solar/Wind Harmer
1.696
209054AE2-059 GEN
Solar/Wind Harmer
1.076
208862AG1-362 C
Solar/Wind Harmer
0.523
959431AF2-234 GEN
Solar/Wind Harmer
1.264
964051AG1-259 GEN
Solar/Wind Harmer
0.848
964061AG1-260 GEN
Solar/Wind Harmer
0.848
959421AF2-233 GEN
Solar/Wind Harmer
0.632
209067AE2-060 GEN
Solar/Wind Harmer
0.909
226929AD2-058 GEN
Solar/Wind Helper
0.143
3141426STAFORD
Solar/Wind Helper
0.053
3138216PACIFIC
Solar/Wind Helper
0.039
200192DELTA CT1
50/50
1.289
200194DELTA CT3
50/50
1.289
200204Y1-065-CTG1
50/50
2.679
200054ROCKSP 3
50/50
1.705
232901NORTHST
Adder
6.603
233970AC1-092 C
Solar/Wind Harmer
2.126
234033AF1-007_GEN
Solar/Wind Harmer
29.492
233996TM1833_GEN
Solar/Wind Harmer
0.79
233998TM1NIN_3.36
Solar/Wind Harmer
0.79
232404W1-003 C
Solar/Wind Harmer
0.793
232408W1-005 C
Solar/Wind Harmer
0.793
232917OH NUG6
Adder
6.972
232915OH NUG4
Adder
6.956
972177AH1-672 GEN
Solar/Wind Harmer
10.65
232900DEMECSMY
Adder
7.313
232919VN10
Adder
2.225
232426Y1-080 FULL
Solar/Wind Harmer
0.151
232902EASTMUNI
Adder
10.308
234012AE2-112_GEN
Solar/Wind Harmer
1.813
233944AB2-135 GEN
Solar/Wind Harmer
4.119
233918AB1-142 GEN
Solar/Wind Harmer
0.778
972251AH1-710 GEN
Adder
35.054
231918WEST 1
Adder
2.599
231917EM10
Adder
1.817
228206SHRMN CT
Adder
11.633
228732V1-021 C
Adder
0.133
228260V4-054C
Solar/Wind Harmer
0.719
970997AG2-616 GEN
Solar/Wind Harmer
6.712
228729W2-030 C
Solar/Wind Harmer
0.403
228400MICK 1CT
Adder
8.225
213497CHSTR7-9
Adder
1.892
213497CHSTR7-9
Adder
1.892
219766PARADISE C
Solar/Wind Harmer
0.217
219686LUMSOLAR_N C
Solar/Wind Harmer
0.14
213958STHWK5-6
Adder
1.876
219907AC1-030 C
Solar/Wind Harmer
0.095
213560DLW11-12
Adder
1.869
219348LDSOLAR C
Solar/Wind Harmer
0.41
219222BRL12CT2
Adder
6.116
213611FALLS1-3
Adder
2.414
20716028EGP_W2-019
Solar/Wind Harmer
0.316
214194N WALES4
Adder
0.581
207522AF2-254 C
Solar/Wind Harmer
0.977
20717128DIX_Z2-102
Solar/Wind Harmer
0.899
20715828PEM_W1-120
Solar/Wind Harmer
0.364
963711AG1-223 GEN
Solar/Wind Harmer
1.005
20714528FRN_Y2-051
Solar/Wind Harmer
0.2
219276PARKLANDSO C
Solar/Wind Harmer
0.313
219680HOPEWELLV C1
Solar/Wind Harmer
0.052
20715228NPK_W1-113
Solar/Wind Harmer
0.292
20720528MAN_W1-024
Solar/Wind Harmer
0.172
20720428HOL_W1-112
Solar/Wind Harmer
0.235
20635828PARLN1&2
Adder
5.022
20635028RRCT1&2
Adder
7.997
218524CNTRALGAS1 C
Solar/Wind Harmer
0.251
218440SUMMTASSOC C
Solar/Wind Harmer
0.087
218428ETC SOLAR C
Solar/Wind Harmer
0.024
219908AB1-139 C
Solar/Wind Harmer
0.258
219919AE1-041 FULL
Solar/Wind Harmer
0.027
972275AH1-722 GEN
Adder
21.418
20673628F1S_V4-069
Solar/Wind Harmer
0.122
207528AF2-192 GEN
Solar/Wind Harmer
0.862
217209CENTRL HS C
Solar/Wind Harmer
0.03
20671828STAW2-080
Solar/Wind Harmer
0.071
217186ESSEX_G9
Adder
2.678
217121ECCF
Adder
0.295
217083KRNY_132
Adder
6.305
217208PARK ELE C
Solar/Wind Harmer
0.017
20676728BRNX1-095
Solar/Wind Harmer
0.12
966261AG1-495 GEN
Solar/Wind Harmer
2.384
207439AE1-081 C O1
Solar/Wind Harmer
0.041
20676328BVR_Y1-020
Solar/Wind Harmer
0.225
20674628WNG_W3-110
Solar/Wind Harmer
0.274
207530AG1-191 GEN
Solar/Wind Harmer
0.935
20676228FRD_X1-012
Solar/Wind Harmer
0.401
20675828AU_W4-064
Solar/Wind Harmer
0.117
20674928WA_W3-044
Solar/Wind Harmer
0.327
971519AH1-257 GEN
Solar/Wind Harmer
1.715
20675728RH_W2-091
Solar/Wind Harmer
0.41
207518AF1-320_GEN
Solar/Wind Harmer
2.488
207484AF2-139 C O1
Solar/Wind Harmer
0.344
20465127PORT CT
Adder
2.041
208909MACR G3
Adder
108.247
211065PSPA IPP
Solar/Wind Harmer
0.305
961301AF2-421 GEN
Solar/Wind Harmer
0.663
963151AG1-164 GEN
Solar/Wind Harmer
0.663
209023WIENIPP1
Adder
7.154
209025WIENIPP3
Adder
3.571
963071AG1-156 GEN
Solar/Wind Harmer
6.527
20465527S.RDG CT
Adder
1.811
209010PEIP 1
Adder
0.422
961341AF2-425 GEN
Solar/Wind Harmer
0.645
212507AE2-042_GEN
Solar/Wind Harmer
1.907
946731AF1-337 GEN
Solar/Wind Harmer
0.633
209018SUNBIPCT
Adder
4.709
209008PAXT IPP
Adder
1.271
209137AF2-361 C
Solar/Wind Harmer
1.757
316415AF1-147_GEN2
Solar/Wind Helper
0.781
316447AC1-158 HLD
Solar/Wind Helper
2.738
316044AC1-158 PL1
Solar/Wind Helper
1.244
200200DELTA2 CT1
50/50
2.307
200193DELTA CT2
50/50
1.289
200203Y1-065-STG
50/50
4.64
200055ROCKSP 4
50/50
1.676
233987AB2-037 GEN
Solar/Wind Harmer
9.02
233973AC2-185 C
Solar/Wind Harmer
4.296
970695AG2-447 GEN
Solar/Wind Harmer
2.842
233939AC1-091 C
Solar/Wind Harmer
2.126
233972AC1-094 C
Solar/Wind Harmer
1.708
232434Z2-077 GEN
Solar/Wind Harmer
0.198
233923SMA
Solar/Wind Harmer
2.897
233997TMININ_4.2
Solar/Wind Harmer
0.79
232406W1-004 FULL
Solar/Wind Harmer
0.793
232914OH NUG3
Adder
7.003
232916OH NUG5
Adder
7.003
232921TASLEY2G
Adder
4.093
232907VN8
Adder
23.808
233964AF2-378 GEN
Solar/Wind Harmer
0.101
232417X3-008 C
Solar/Wind Harmer
0.891
233950AC2-186 GEN
Solar/Wind Harmer
0.445
232422X3-066 FULL
Solar/Wind Harmer
0.197
233933AB2-153 GEN
Solar/Wind Harmer
0.884
233935AB2-179 C
Solar/Wind Harmer
1.945
228711V2-041C
Solar/Wind Harmer
0.421
230415AB2-049 C
Solar/Wind Harmer
0.132
213497CHSTR7-9
Adder
1.892
219623KINSLEYBEA C
Solar/Wind Harmer
0.296
219921AF1-264
Solar/Wind Harmer
0.1
219291REEVESSOUT C
Solar/Wind Harmer
0.041
218660EHAMPSOLAR C
Solar/Wind Harmer
0.121
219688LUMSOLAR_S C
Solar/Wind Harmer
0.14
219914AD2-027 C
Solar/Wind Harmer
0.414
213958STHWK5-6
Adder
1.876
219236SOUTHERNHQ C
Solar/Wind Harmer
0.047
213560DLW11-12
Adder
1.869
219221BRL12CT1
Adder
6.116
219223BRL12CT3
Adder
6.116
213815MOSER1-3
Adder
2.431
959561AF2-247 GEN
Solar/Wind Harmer
0.331
20716428NHV_W2-082
Solar/Wind Harmer
1.21
20715728PEM_W1-119
Solar/Wind Harmer
0.364
20636028O CRK C1
Adder
4.809
963391AG1-188 GEN
Solar/Wind Harmer
2.55
20714928UPF_X1-085
Solar/Wind Harmer
0.277
971667AH1-334 GEN
Solar/Wind Harmer
1.868
219114HARTZY_C
Solar/Wind Harmer
0.567
219727YARDVSOLFA C
Solar/Wind Harmer
0.619
219918AC2-009 C
Solar/Wind Harmer
0.017
207454AA2-184 E
Solar/Wind Harmer
0.678
219612MATRIX C
Solar/Wind Harmer
0.125
20716928W4-060COL
Solar/Wind Harmer
0.482
20635828PARLN1&2
Adder
2.275
20635928PARLN3&4
Adder
2.275
217213AMBOY SO C
Solar/Wind Harmer
0.086
219249CENTRALDIV C
Solar/Wind Harmer
0.027
207442AE1-156 GEN
Solar/Wind Harmer
0.504
20673728F2S_V4-070
Solar/Wind Harmer
0.122
972281AH1-725 GEN
50/50
114.199
200201DELTA2 CT2
50/50
2.307
200034PCHBTM 2
50/50
13.449
200035PCHBTM 3
50/50
13.333
200205Y1-065-CTG2
50/50
2.679
233971AC1-093 C
Solar/Wind Harmer
2.019
232410W1-006 C
Solar/Wind Harmer
0.793
232918OH NUG7
Adder
6.956
232905CHERITON_25
Adder
1.945
232926CRISFLD1
Adder
1.556
234015AF2-250 C
Solar/Wind Harmer
0.095
231940T-011
Adder
0.591
233994AC2-023 GEN
Solar/Wind Harmer
2.128
232428Y3-058 C
Solar/Wind Harmer
0.66
232899W1-062
Adder
7.624
233946AB2-136 GEN
Solar/Wind Harmer
3.159
234036AF2-325 C
Solar/Wind Harmer
0.726
234041AC1-190 GEN
Solar/Wind Harmer
7.094
233952AC2-187 GEN
Solar/Wind Harmer
0.891
233954AC2-188 GEN
Solar/Wind Harmer
0.891
232910NRG_G1
Adder
6.825
233984AB2-036 GEN
Solar/Wind Harmer
9.832
232424Y1-079 C
Solar/Wind Harmer
0.444
234014AF1-036_GEN
Solar/Wind Harmer
2.133
232436AB1-176 C
Solar/Wind Harmer
0.18
233930AB2-032 GEN
Solar/Wind Harmer
0.655
233982AB2-133 GEN
Solar/Wind Harmer
3.828
228201CARL#2CT
Adder
4.817
228200CARL#1CT
Adder
4.582
228251CARLLS#4
Adder
0.442
228351V2-046C
Solar/Wind Harmer
1.409
230433AD2-135 GEN
Solar/Wind Harmer
0.071
230511AF1-262
Solar/Wind Harmer
0.128
228307PCLP GT
Adder
8.443
228754AB1-001 C
Solar/Wind Harmer
0.097
972233AH1-701 GEN
Adder
2.923
213589EDDYSTN4
Adder
55.245
213587EDDYSTN3
Adder
55.24
219272CLEANLIGHT C
Solar/Wind Harmer
0.126
219904AC1-010 C
Solar/Wind Harmer
0.261
219287REEVESEAST C
Solar/Wind Harmer
0.928
219912AD2-042 GEN
Solar/Wind Harmer
0.549
219906AC1-017 C
Solar/Wind Harmer
0.153
219607WPEMNERT C
Solar/Wind Harmer
0.287
219304NAMERICA C
Solar/Wind Harmer
0.213
213535CROYDN11
Adder
7.007
213815MOSER1-3
Adder
2.431
213815MOSER1-3
Adder
2.431
214067T20SOLAR
Solar/Wind Harmer
0.172
20720828JCB_W4-025
Solar/Wind Harmer
0.308
20636128O CRK C2
Adder
4.385
207459AE1-142 C O1
Solar/Wind Harmer
0.717
20628028LAKEHURS
Adder
0.647
20714828MDF_W3-079
Solar/Wind Harmer
0.208
219817TRENTONSOL C
Solar/Wind Harmer
0.748
20641628MLH_W1-032
Solar/Wind Harmer
0.199
20742028HF_AC1-207
Solar/Wind Harmer
0.532
217197RE CRAN C
Solar/Wind Harmer
0.364
218438BLK ROCK C
Solar/Wind Harmer
0.092
924131AB2-057 GEN
Solar/Wind Harmer
0.698
20635028RRCT1&2
Adder
7.874
20635128RRCT3&4
Adder
7.6
20635128RRCT3&4
Adder
6.63
218418LINDEN_G5
Adder
11.65
218419LINDEN_G6
Adder
11.65
972260AH1-715 GEN1
Adder
9.329
20675428EAM_W2-061
Solar/Wind Harmer
0.128
219036LINDEN_G7
Adder
11.346
219035LINDEN_G8
Adder
11.184
972261AH1-715 GEN2
Adder
10.861
217081WEATEXAS C
Solar/Wind Harmer
0.058
217202FBANKSOLAR C
Solar/Wind Harmer
0.05
217201HACKENSOLA C
Solar/Wind Harmer
0.05
972237AH1-703 GEN
Adder
6.863
217206BARNGR HS C
Solar/Wind Harmer
0.021
217086KRNY_131
Adder
6.318
217083KRNY_132
Adder
6.265
217204WCALDSOLAR C
Solar/Wind Harmer
0.05
20674328GAR_V4-001
Solar/Wind Harmer
0.075
20674828DL_W4-046
Solar/Wind Harmer
0.439
207471AF2-354 C
Solar/Wind Harmer
0.348
20634528N27_Y2-018
Solar/Wind Harmer
0.183
20675928HOL_W4-097
Solar/Wind Harmer
0.089
20465127PORT CT
Adder
2.708
961541AF2-445A GEN
Solar/Wind Harmer
2.128
20465527S.RDG CT
Adder
1.753
209010PEIP 1
Adder
2.322
209010PEIP 1
Adder
0.34
961431AF2-434 GEN
Solar/Wind Harmer
0.644
946751AF1-339 GEN
Solar/Wind Harmer
0.633
209130AF1-271A GEN
Solar/Wind Harmer
1.778
316411AF1-147_GEN1
Solar/Wind Helper
0.781
316045AC1-158 PL2
Solar/Wind Helper
3.981
316006AB2-029 C
Solar/Wind Helper
0.107
316450AC1-158 RIC
Solar/Wind Helper
0.332
217211CAMDEN ST C
Solar/Wind Harmer
0.017
217169METRODIV C
Solar/Wind Harmer
0.027
217194REDH C
Solar/Wind Harmer
0.334
20674528F3S_W2-016
Solar/Wind Harmer
0.955
207510AF2-138 C
Solar/Wind Harmer
1.208
207511W3-106 GEN
Solar/Wind Harmer
0.224
971007AG2-625 GEN
Solar/Wind Harmer
1.747
207437AD2-070 GEN
Solar/Wind Harmer
0.205
20671928W4-073
Solar/Wind Harmer
0.294
20674128FR_U2-059
Solar/Wind Harmer
0.125
20633028GILCT9
Adder
19.277
20466127PORT 5CT
Adder
18.01
20465427SHAW CT
Adder
2.62
209116AE2-175 GEN
Solar/Wind Harmer
2.78
211065PSPA IPP
Solar/Wind Harmer
0.305
963161AG1-165 GEN
Solar/Wind Harmer
0.663
209025WIENIPP3
Adder
3.499
205941AD2-115 GEN
Solar/Wind Harmer
0.611
970095AG2-074 GEN
Solar/Wind Harmer
4.134
208972BECR K09
Solar/Wind Harmer
0.695
961331AF2-424 GEN
Solar/Wind Harmer
0.645
961421AF2-433 GEN
Solar/Wind Harmer
0.644
957921AF2-086 GEN
Solar/Wind Harmer
0.626
209142AF1-226 GEN
Solar/Wind Harmer
3.728
209093AE2-110 GEN
Solar/Wind Harmer
1.61
209120AE2-241 GEN
Solar/Wind Harmer
2.13
946691AF1-333 GEN
Solar/Wind Harmer
0.633
946741AF1-338 GEN
Solar/Wind Harmer
0.633
209071AE2-133 GEN
Solar/Wind Harmer
1.07
972221AH1-695 GEN
Adder
86.06
227287AC2-120 GEN
Solar/Wind Helper
0.516
226910AB2-157 C
Solar/Wind Helper
0.021
3141196NOKESVL
Solar/Wind Helper
0.919
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.03
VTFLTFEXP_VFT->PJM
CMTX
91.873
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.296
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.624
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.189
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.653
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
34.775
CBM NorthLTFEXP_CBM-N->PJM
CBM
54.028
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.85 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3217.41
MW Contribution:
3.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
140.974
200201DELTA2 CT2
50/50
2.929
200034PCHBTM 2
50/50
17.072
200035PCHBTM 3
50/50
16.97
200205Y1-065-CTG2
50/50
3.355
232410W1-006 C
Solar/Wind Harmer
0.924
232918OH NUG7
Adder
8.113
232905CHERITON_25
Adder
2.269
232926CRISFLD1
Adder
1.815
233994AC2-023 GEN
Solar/Wind Harmer
2.482
232428Y3-058 C
Solar/Wind Harmer
0.77
234015AF2-250 C
Solar/Wind Harmer
0.111
233946AB2-136 GEN
Solar/Wind Harmer
3.686
200202DELTA2 ST
50/50
4.96
200195DELTA ST
50/50
2.528
200052ROCKSP 1
50/50
2.111
200053ROCKSP 2
50/50
2.07
233901CHERRYDALE C
Solar/Wind Harmer
1.04
233940AF2-379 C
Solar/Wind Harmer
0.172
232912OH NUG1
Adder
8.167
232913OH NUG2
Adder
8.058
971195AH1-057 GEN
Solar/Wind Harmer
0.901
232432Z2-076 GEN
Solar/Wind Harmer
0.122
232904IR4
Adder
74.738
232920IR10
Adder
2.921
233955AB2-172 GEN
Solar/Wind Harmer
4.62
232813VAUGHN
Adder
0.543
233968AD2-076_GEN
Solar/Wind Harmer
6.099
970597AG2-380 GEN
Solar/Wind Harmer
3.83
231906DC3 NUG
Adder
12.854
231902DC CT7
Adder
10.276
231907DC10
Adder
3.209
233915AB1-141 GEN
Solar/Wind Harmer
0.908
231919CHRIST1
Adder
3.943
231920CHRIST2
Adder
3.855
970453AG2-297 GEN
Solar/Wind Harmer
2.136
972141AH1-641 GEN
Solar/Wind Harmer
2.209
230430AE1-229_GEN
Solar/Wind Harmer
21.968
964001AG1-254 GEN
Solar/Wind Harmer
5.591
230422AE1-104_GEN1
Solar/Wind Harmer
25.798
230425AE1-104_GEN2
Solar/Wind Harmer
25.798
228728W1-130C
Solar/Wind Harmer
0.507
230434AG1-499 GEN
Solar/Wind Harmer
0.442
230407AD2-065 C
Solar/Wind Harmer
0.1
227927V4-067C
Solar/Wind Harmer
0.151
219137THOSOLAR C
Solar/Wind Harmer
0.911
213942SCHUYLKILL
Adder
2.677
213942SCHUYLKILL
Adder
2.047
213957STHWK3-4
Adder
2.044
213957STHWK3-4
Adder
2.044
219258KINSLEYDEP C
Solar/Wind Harmer
0.242
213561DLWR9-10
Adder
2.635
213561DLWR9-10
Adder
2.015
219615MILLCREEK C
Solar/Wind Harmer
0.175
219610FLORENCE C
Solar/Wind Harmer
1.01
219224BRL12CT4
Adder
6.508
213611FALLS1-3
Adder
2.544
213611FALLS1-3
Adder
2.544
20720728JCB_W1-129
Solar/Wind Harmer
0.213
20715028HAN_X4-015
Solar/Wind Harmer
0.213
207487AE2-000G4
Solar/Wind Harmer
22.403
207497AE2-000G2
Solar/Wind Harmer
22.403
207500AE2-000G1
Solar/Wind Harmer
22.403
207507AE2-000G3
Solar/Wind Harmer
22.403
963401AG1-189 GEN
Solar/Wind Harmer
1.614
970025AG2-016 GEN
Solar/Wind Harmer
2.009
971189AH1-054 GEN
Solar/Wind Harmer
0.836
207445AB1-138_GEN
Solar/Wind Harmer
0.409
219620RIDERU C
Solar/Wind Harmer
0.039
20714428HOW_X1-037
Solar/Wind Harmer
0.857
20720628TIN_W1-124
Solar/Wind Harmer
0.689
20716228APLW2-078
Solar/Wind Harmer
0.611
971521AH1-258 GEN
Solar/Wind Harmer
1.866
20635928PARLN3&4
Adder
5.042
218526CNTRALGAS2 C
Solar/Wind Harmer
0.25
20675528CPH_W2-050
Solar/Wind Harmer
0.387
20673828FLE_V3-070
Solar/Wind Harmer
0.313
20676128MHD_W3-029
Solar/Wind Harmer
0.319
218449LINSOLAR C
Solar/Wind Harmer
0.672
20676428JCR_X2-075
Solar/Wind Harmer
0.228
217167KRNY_14
Adder
6.155
217086KRNY_131
Adder
6.103
217147KRNY_1212
Adder
5.854
217147KRNY_1212
Adder
5.75
217146KRNY_1234
Adder
5.737
217146KRNY_1234
Adder
5.697
964851AG1-348 GEN
Solar/Wind Harmer
0.866
971009AG2-626 GEN
Solar/Wind Harmer
1.038
207408W3-077 C
Solar/Wind Harmer
0.319
20675128HRM_W1-127
Solar/Wind Harmer
0.107
20462827N BANGR8
Adder
0.448
961261AF2-417 GEN
Solar/Wind Harmer
0.59
209026WIENIPP4
Adder
3.05
209029WAYMART-WD
Solar/Wind Harmer
1.486
209027LOR2_Q27
Solar/Wind Harmer
2.477
212266LOR1
Solar/Wind Harmer
0.656
20486527WR_V4-052
Adder
0.577
226929AD2-058 GEN
Solar/Wind Helper
0.102
3138216PACIFIC
Solar/Wind Helper
0.039
234036AF2-325 C
Solar/Wind Harmer
0.847
231940T-011
Adder
0.689
234041AC1-190 GEN
Solar/Wind Harmer
8.277
233971AC1-093 C
Solar/Wind Harmer
2.35
233952AC2-187 GEN
Solar/Wind Harmer
1.038
233954AC2-188 GEN
Solar/Wind Harmer
1.038
232899W1-062
Adder
8.876
233984AB2-036 GEN
Solar/Wind Harmer
11.477
232424Y1-079 C
Solar/Wind Harmer
0.518
232910NRG_G1
Adder
7.954
234014AF1-036_GEN
Solar/Wind Harmer
2.489
232436AB1-176 C
Solar/Wind Harmer
0.211
233930AB2-032 GEN
Solar/Wind Harmer
0.764
233982AB2-133 GEN
Solar/Wind Harmer
4.466
228251CARLLS#4
Adder
0.485
228201CARL#2CT
Adder
5.291
228200CARL#1CT
Adder
5.032
228351V2-046C
Solar/Wind Harmer
1.545
230511AF1-262
Solar/Wind Harmer
0.14
230433AD2-135 GEN
Solar/Wind Harmer
0.077
213589EDDYSTN4
Adder
61.041
213587EDDYSTN3
Adder
61.027
228307PCLP GT
Adder
9.242
228754AB1-001 C
Solar/Wind Harmer
0.106
972233AH1-701 GEN
Adder
3.192
219904AC1-010 C
Solar/Wind Harmer
0.282
219272CLEANLIGHT C
Solar/Wind Harmer
0.136
219912AD2-042 GEN
Solar/Wind Harmer
0.592
219287REEVESEAST C
Solar/Wind Harmer
0.998
219906AC1-017 C
Solar/Wind Harmer
0.163
219607WPEMNERT C
Solar/Wind Harmer
0.305
219304NAMERICA C
Solar/Wind Harmer
0.226
213815MOSER1-3
Adder
2.587
213815MOSER1-3
Adder
2.587
213535CROYDN11
Adder
7.454
214067T20SOLAR
Solar/Wind Harmer
0.182
20720828JCB_W4-025
Solar/Wind Harmer
0.323
20636128O CRK C2
Adder
4.583
207459AE1-142 C O1
Solar/Wind Harmer
0.745
20628028LAKEHURS
Adder
0.671
20714828MDF_W3-079
Solar/Wind Harmer
0.214
219817TRENTONSOL C
Solar/Wind Harmer
0.767
20641628MLH_W1-032
Solar/Wind Harmer
0.203
20742028HF_AC1-207
Solar/Wind Harmer
0.541
217197RE CRAN C
Solar/Wind Harmer
0.368
218438BLK ROCK C
Solar/Wind Harmer
0.093
924131AB2-057 GEN
Solar/Wind Harmer
0.7
20635028RRCT1&2
Adder
7.881
20635128RRCT3&4
Adder
7.607
20635128RRCT3&4
Adder
6.636
218418LINDEN_G5
Adder
11.534
218419LINDEN_G6
Adder
11.534
972260AH1-715 GEN1
Adder
9.236
20675428EAM_W2-061
Solar/Wind Harmer
0.126
219036LINDEN_G7
Adder
11.177
219035LINDEN_G8
Adder
11.018
972261AH1-715 GEN2
Adder
10.7
217081WEATEXAS C
Solar/Wind Harmer
0.057
217202FBANKSOLAR C
Solar/Wind Harmer
0.049
217201HACKENSOLA C
Solar/Wind Harmer
0.049
972237AH1-703 GEN
Adder
6.701
217206BARNGR HS C
Solar/Wind Harmer
0.02
217086KRNY_131
Adder
6.168
217083KRNY_132
Adder
6.116
217204WCALDSOLAR C
Solar/Wind Harmer
0.048
20674328GAR_V4-001
Solar/Wind Harmer
0.071
20674828DL_W4-046
Solar/Wind Harmer
0.411
207471AF2-354 C
Solar/Wind Harmer
0.325
20634528N27_Y2-018
Solar/Wind Harmer
0.17
20675928HOL_W4-097
Solar/Wind Harmer
0.082
20465127PORT CT
Adder
2.498
209010PEIP 1
Adder
2.034
209010PEIP 1
Adder
0.298
961541AF2-445A GEN
Solar/Wind Harmer
1.779
961431AF2-434 GEN
Solar/Wind Harmer
0.533
20465527S.RDG CT
Adder
1.43
316411AF1-147_GEN1
Solar/Wind Helper
0.776
200192DELTA CT1
50/50
1.637
200194DELTA CT3
50/50
1.637
200204Y1-065-CTG1
50/50
3.355
200054ROCKSP 3
50/50
2.135
233996TM1833_GEN
Solar/Wind Harmer
0.922
233998TM1NIN_3.36
Solar/Wind Harmer
0.922
232404W1-003 C
Solar/Wind Harmer
0.924
232408W1-005 C
Solar/Wind Harmer
0.924
232917OH NUG6
Adder
8.131
232915OH NUG4
Adder
8.113
232919VN10
Adder
2.595
232426Y1-080 FULL
Solar/Wind Harmer
0.177
234033AF1-007_GEN
Solar/Wind Harmer
34.381
972177AH1-672 GEN
Solar/Wind Harmer
12.412
232901NORTHST
Adder
7.688
232902EASTMUNI
Adder
12.032
233970AC1-092 C
Solar/Wind Harmer
2.474
232900DEMECSMY
Adder
8.514
234012AE2-112_GEN
Solar/Wind Harmer
2.116
233944AB2-135 GEN
Solar/Wind Harmer
4.805
233918AB1-142 GEN
Solar/Wind Harmer
0.908
231918WEST 1
Adder
3.001
972251AH1-710 GEN
Adder
40.035
231917EM10
Adder
2.089
228206SHRMN CT
Adder
12.794
228260V4-054C
Solar/Wind Harmer
0.79
228732V1-021 C
Adder
0.146
970997AG2-616 GEN
Solar/Wind Harmer
7.363
213497CHSTR7-9
Adder
2.092
213497CHSTR7-9
Adder
2.092
228729W2-030 C
Solar/Wind Harmer
0.439
228400MICK 1CT
Adder
8.978
213958STHWK5-6
Adder
2.044
219766PARADISE C
Solar/Wind Harmer
0.235
219686LUMSOLAR_N C
Solar/Wind Harmer
0.15
213560DLW11-12
Adder
2.015
219907AC1-030 C
Solar/Wind Harmer
0.103
219348LDSOLAR C
Solar/Wind Harmer
0.436
219222BRL12CT2
Adder
6.508
213611FALLS1-3
Adder
2.544
20716028EGP_W2-019
Solar/Wind Harmer
0.331
214194N WALES4
Adder
0.609
207522AF2-254 C
Solar/Wind Harmer
1.024
20717128DIX_Z2-102
Solar/Wind Harmer
0.941
20715828PEM_W1-120
Solar/Wind Harmer
0.381
963711AG1-223 GEN
Solar/Wind Harmer
1.036
20714528FRN_Y2-051
Solar/Wind Harmer
0.206
219276PARKLANDSO C
Solar/Wind Harmer
0.323
219680HOPEWELLV C1
Solar/Wind Harmer
0.053
20715228NPK_W1-113
Solar/Wind Harmer
0.297
20720528MAN_W1-024
Solar/Wind Harmer
0.176
20720428HOL_W1-112
Solar/Wind Harmer
0.238
20635828PARLN1&2
Adder
5.042
20635028RRCT1&2
Adder
8.004
218524CNTRALGAS1 C
Solar/Wind Harmer
0.25
218440SUMMTASSOC C
Solar/Wind Harmer
0.086
218428ETC SOLAR C
Solar/Wind Harmer
0.024
219908AB1-139 C
Solar/Wind Harmer
0.257
219919AE1-041 FULL
Solar/Wind Harmer
0.027
972275AH1-722 GEN
Adder
21.203
20673628F1S_V4-069
Solar/Wind Harmer
0.12
207528AF2-192 GEN
Solar/Wind Harmer
0.85
217209CENTRL HS C
Solar/Wind Harmer
0.03
217186ESSEX_G9
Adder
2.614
217121ECCF
Adder
0.288
217083KRNY_132
Adder
6.155
20671828STAW2-080
Solar/Wind Harmer
0.069
217208PARK ELE C
Solar/Wind Harmer
0.017
20676728BRNX1-095
Solar/Wind Harmer
0.115
966261AG1-495 GEN
Solar/Wind Harmer
2.282
207439AE1-081 C O1
Solar/Wind Harmer
0.039
20676328BVR_Y1-020
Solar/Wind Harmer
0.213
20674628WNG_W3-110
Solar/Wind Harmer
0.259
207530AG1-191 GEN
Solar/Wind Harmer
0.884
20676228FRD_X1-012
Solar/Wind Harmer
0.38
20675828AU_W4-064
Solar/Wind Harmer
0.111
20674928WA_W3-044
Solar/Wind Harmer
0.306
971519AH1-257 GEN
Solar/Wind Harmer
1.596
3141426STAFORD
Solar/Wind Helper
0.05
20675728RH_W2-091
Solar/Wind Harmer
0.38
207518AF1-320_GEN
Solar/Wind Harmer
2.303
207484AF2-139 C O1
Solar/Wind Harmer
0.318
20465127PORT CT
Adder
1.882
208909MACR G3
Adder
98.632
211065PSPA IPP
Solar/Wind Harmer
0.271
961301AF2-421 GEN
Solar/Wind Harmer
0.572
963151AG1-164 GEN
Solar/Wind Harmer
0.572
209023WIENIPP1
Adder
6.173
209025WIENIPP3
Adder
3.081
963071AG1-156 GEN
Solar/Wind Harmer
5.669
209010PEIP 1
Adder
0.37
961341AF2-425 GEN
Solar/Wind Harmer
0.535
20465527S.RDG CT
Adder
1.478
316415AF1-147_GEN2
Solar/Wind Helper
0.776
200200DELTA2 CT1
50/50
2.929
200193DELTA CT2
50/50
1.637
200203Y1-065-STG
50/50
5.811
200055ROCKSP 4
50/50
2.099
233987AB2-037 GEN
Solar/Wind Harmer
10.537
232907VN8
Adder
27.777
233923SMA
Solar/Wind Harmer
3.379
233997TMININ_4.2
Solar/Wind Harmer
0.922
232406W1-004 FULL
Solar/Wind Harmer
0.924
232914OH NUG3
Adder
8.167
232916OH NUG5
Adder
8.167
232921TASLEY2G
Adder
4.773
232434Z2-077 GEN
Solar/Wind Harmer
0.231
233964AF2-378 GEN
Solar/Wind Harmer
0.118
232417X3-008 C
Solar/Wind Harmer
1.039
233973AC2-185 C
Solar/Wind Harmer
4.999
970695AG2-447 GEN
Solar/Wind Harmer
3.307
233939AC1-091 C
Solar/Wind Harmer
2.474
233972AC1-094 C
Solar/Wind Harmer
1.987
233950AC2-186 GEN
Solar/Wind Harmer
0.519
232422X3-066 FULL
Solar/Wind Harmer
0.23
233933AB2-153 GEN
Solar/Wind Harmer
1.032
233935AB2-179 C
Solar/Wind Harmer
2.269
228711V2-041C
Solar/Wind Harmer
0.464
213497CHSTR7-9
Adder
2.092
230415AB2-049 C
Solar/Wind Harmer
0.145
213958STHWK5-6
Adder
2.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.32
219921AF1-264
Solar/Wind Harmer
0.108
219291REEVESSOUT C
Solar/Wind Harmer
0.045
218660EHAMPSOLAR C
Solar/Wind Harmer
0.13
219914AD2-027 C
Solar/Wind Harmer
0.446
219688LUMSOLAR_S C
Solar/Wind Harmer
0.15
213560DLW11-12
Adder
2.015
219236SOUTHERNHQ C
Solar/Wind Harmer
0.05
219221BRL12CT1
Adder
6.508
219223BRL12CT3
Adder
6.508
213815MOSER1-3
Adder
2.587
959561AF2-247 GEN
Solar/Wind Harmer
0.348
20716428NHV_W2-082
Solar/Wind Harmer
1.269
20715728PEM_W1-119
Solar/Wind Harmer
0.381
20636028O CRK C1
Adder
5.027
963391AG1-188 GEN
Solar/Wind Harmer
2.657
20714928UPF_X1-085
Solar/Wind Harmer
0.288
219114HARTZY_C
Solar/Wind Harmer
0.59
971667AH1-334 GEN
Solar/Wind Harmer
1.941
219727YARDVSOLFA C
Solar/Wind Harmer
0.641
219918AC2-009 C
Solar/Wind Harmer
0.018
207454AA2-184 E
Solar/Wind Harmer
0.692
219612MATRIX C
Solar/Wind Harmer
0.126
20716928W4-060COL
Solar/Wind Harmer
0.487
20635828PARLN1&2
Adder
2.283
20635928PARLN3&4
Adder
2.283
217213AMBOY SO C
Solar/Wind Harmer
0.085
219249CENTRALDIV C
Solar/Wind Harmer
0.027
207442AE1-156 GEN
Solar/Wind Harmer
0.497
20673728F2S_V4-070
Solar/Wind Harmer
0.12
217211CAMDEN ST C
Solar/Wind Harmer
0.016
217169METRODIV C
Solar/Wind Harmer
0.026
217194REDH C
Solar/Wind Harmer
0.326
20674528F3S_W2-016
Solar/Wind Harmer
0.928
207510AF2-138 C
Solar/Wind Harmer
1.145
207511W3-106 GEN
Solar/Wind Harmer
0.212
971007AG2-625 GEN
Solar/Wind Harmer
1.627
207437AD2-070 GEN
Solar/Wind Harmer
0.19
20671928W4-073
Solar/Wind Harmer
0.271
20466127PORT 5CT
Adder
16.611
20674128FR_U2-059
Solar/Wind Harmer
0.115
20633028GILCT9
Adder
17.75
20465427SHAW CT
Adder
2.407
209116AE2-175 GEN
Solar/Wind Harmer
2.506
211065PSPA IPP
Solar/Wind Harmer
0.271
963161AG1-165 GEN
Solar/Wind Harmer
0.572
209025WIENIPP3
Adder
3.019
970095AG2-074 GEN
Solar/Wind Harmer
3.59
208972BECR K09
Solar/Wind Harmer
0.599
205941AD2-115 GEN
Solar/Wind Harmer
0.512
961331AF2-424 GEN
Solar/Wind Harmer
0.535
961421AF2-433 GEN
Solar/Wind Harmer
0.533
957921AF2-086 GEN
Solar/Wind Harmer
0.519
209142AF1-226 GEN
Solar/Wind Harmer
3.088
209093AE2-110 GEN
Solar/Wind Harmer
1.334
209120AE2-241 GEN
Solar/Wind Harmer
1.764
227287AC2-120 GEN
Solar/Wind Helper
0.356
226910AB2-157 C
Solar/Wind Helper
0.014
3141196NOKESVL
Solar/Wind Helper
0.901
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.123
VTFLTFEXP_VFT->PJM
CMTX
89.976
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.379
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.93
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.138
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.987
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
34.806
CBM NorthLTFEXP_CBM-N->PJM
CBM
50.284
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o BG_P7_CNSTN_NWEST2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
BG_P7_CNSTN_NWEST2_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.61 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3178.71
MW Contribution:
2.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
123.888
200201DELTA2 CT2
50/50
2.13
200034PCHBTM 2
50/50
12.417
200205Y1-065-CTG2
50/50
2.474
200035PCHBTM 3
50/50
12.143
200061HUNTR401
50/50
2.95
232410W1-006 C
Solar/Wind Harmer
0.735
232918OH NUG7
Adder
6.447
232905CHERITON_25
Adder
1.803
232926CRISFLD1
Adder
1.442
233994AC2-023 GEN
Solar/Wind Harmer
1.972
232428Y3-058 C
Solar/Wind Harmer
0.612
234015AF2-250 C
Solar/Wind Harmer
0.088
231940T-011
Adder
0.548
233946AB2-136 GEN
Solar/Wind Harmer
2.93
234036AF2-325 C
Solar/Wind Harmer
0.673
234041AC1-190 GEN
Solar/Wind Harmer
6.579
233971AC1-093 C
Solar/Wind Harmer
1.869
232899W1-062
Adder
7.061
233952AC2-187 GEN
Solar/Wind Harmer
0.826
233954AC2-188 GEN
Solar/Wind Harmer
0.826
233984AB2-036 GEN
Solar/Wind Harmer
9.131
232910NRG_G1
Adder
6.331
232424Y1-079 C
Solar/Wind Harmer
0.412
234014AF1-036_GEN
Solar/Wind Harmer
1.982
232436AB1-176 C
Solar/Wind Harmer
0.168
233930AB2-032 GEN
Solar/Wind Harmer
0.609
233982AB2-133 GEN
Solar/Wind Harmer
3.56
228201CARL#2CT
Adder
4.437
228200CARL#1CT
Adder
4.22
228251CARLLS#4
Adder
0.407
228351V2-046C
Solar/Wind Harmer
1.298
230511AF1-262
Solar/Wind Harmer
0.118
230433AD2-135 GEN
Solar/Wind Harmer
0.065
228307PCLP GT
Adder
7.78
213589EDDYSTN4
Adder
51.238
213587EDDYSTN3
Adder
51.233
228754AB1-001 C
Solar/Wind Harmer
0.089
972233AH1-701 GEN
Adder
2.694
219904AC1-010 C
Solar/Wind Harmer
0.24
219272CLEANLIGHT C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.505
219287REEVESEAST C
Solar/Wind Harmer
0.853
219906AC1-017 C
Solar/Wind Harmer
0.141
219607WPEMNERT C
Solar/Wind Harmer
0.264
219304NAMERICA C
Solar/Wind Harmer
0.195
213535CROYDN11
Adder
6.441
213815MOSER1-3
Adder
2.233
213815MOSER1-3
Adder
2.233
214067T20SOLAR
Solar/Wind Harmer
0.158
20720828JCB_W4-025
Solar/Wind Harmer
0.283
20636128O CRK C2
Adder
4.019
207459AE1-142 C O1
Solar/Wind Harmer
0.657
20628028LAKEHURS
Adder
0.592
20714828MDF_W3-079
Solar/Wind Harmer
0.19
219817TRENTONSOL C
Solar/Wind Harmer
0.685
20641628MLH_W1-032
Solar/Wind Harmer
0.182
20742028HF_AC1-207
Solar/Wind Harmer
0.486
217197RE CRAN C
Solar/Wind Harmer
0.333
218438BLK ROCK C
Solar/Wind Harmer
0.084
924131AB2-057 GEN
Solar/Wind Harmer
0.637
20635028RRCT1&2
Adder
7.189
20635128RRCT3&4
Adder
6.939
20635128RRCT3&4
Adder
6.053
218418LINDEN_G5
Adder
10.628
218419LINDEN_G6
Adder
10.628
972260AH1-715 GEN1
Adder
8.511
20675428EAM_W2-061
Solar/Wind Harmer
0.117
219036LINDEN_G7
Adder
10.347
200202DELTA2 ST
50/50
3.607
200195DELTA ST
50/50
1.838
200052ROCKSP 1
50/50
1.556
200053ROCKSP 2
50/50
1.526
200059HUNTR201
50/50
1.547
200060HUNTR301
50/50
1.547
200058HUNTR101
50/50
1.547
233901CHERRYDALE C
Solar/Wind Harmer
0.826
233940AF2-379 C
Solar/Wind Harmer
0.137
232912OH NUG1
Adder
6.491
232913OH NUG2
Adder
6.404
232904IR4
Adder
59.406
971195AH1-057 GEN
Solar/Wind Harmer
0.716
232432Z2-076 GEN
Solar/Wind Harmer
0.097
232920IR10
Adder
2.322
233955AB2-172 GEN
Solar/Wind Harmer
3.672
232813VAUGHN
Adder
0.432
233968AD2-076_GEN
Solar/Wind Harmer
4.857
970597AG2-380 GEN
Solar/Wind Harmer
3.05
231906DC3 NUG
Adder
10.24
231902DC CT7
Adder
8.186
231907DC10
Adder
2.556
233915AB1-141 GEN
Solar/Wind Harmer
0.724
231919CHRIST1
Adder
3.179
231920CHRIST2
Adder
3.109
970453AG2-297 GEN
Solar/Wind Harmer
1.785
972141AH1-641 GEN
Solar/Wind Harmer
1.855
230430AE1-229_GEN
Solar/Wind Harmer
18.452
964001AG1-254 GEN
Solar/Wind Harmer
4.696
230422AE1-104_GEN1
Solar/Wind Harmer
21.702
230425AE1-104_GEN2
Solar/Wind Harmer
21.702
228728W1-130C
Solar/Wind Harmer
0.427
230434AG1-499 GEN
Solar/Wind Harmer
0.372
230407AD2-065 C
Solar/Wind Harmer
0.084
227927V4-067C
Solar/Wind Harmer
0.127
219137THOSOLAR C
Solar/Wind Harmer
0.773
200192DELTA CT1
50/50
1.19
200194DELTA CT3
50/50
1.19
200204Y1-065-CTG1
50/50
2.474
200054ROCKSP 3
50/50
1.575
233996TM1833_GEN
Solar/Wind Harmer
0.732
233998TM1NIN_3.36
Solar/Wind Harmer
0.732
232404W1-003 C
Solar/Wind Harmer
0.735
232408W1-005 C
Solar/Wind Harmer
0.735
232917OH NUG6
Adder
6.462
232915OH NUG4
Adder
6.447
234033AF1-007_GEN
Solar/Wind Harmer
27.328
232919VN10
Adder
2.062
232426Y1-080 FULL
Solar/Wind Harmer
0.14
232901NORTHST
Adder
6.114
972177AH1-672 GEN
Solar/Wind Harmer
9.868
233970AC1-092 C
Solar/Wind Harmer
1.969
232900DEMECSMY
Adder
6.773
232902EASTMUNI
Adder
9.566
234012AE2-112_GEN
Solar/Wind Harmer
1.685
233944AB2-135 GEN
Solar/Wind Harmer
3.829
233918AB1-142 GEN
Solar/Wind Harmer
0.724
972251AH1-710 GEN
Adder
32.338
231918WEST 1
Adder
2.418
231917EM10
Adder
1.69
228206SHRMN CT
Adder
10.712
228260V4-054C
Solar/Wind Harmer
0.662
228732V1-021 C
Adder
0.122
970997AG2-616 GEN
Solar/Wind Harmer
6.182
213497CHSTR7-9
Adder
1.754
213497CHSTR7-9
Adder
1.754
228729W2-030 C
Solar/Wind Harmer
0.371
228400MICK 1CT
Adder
7.579
213958STHWK5-6
Adder
1.735
219766PARADISE C
Solar/Wind Harmer
0.2
219686LUMSOLAR_N C
Solar/Wind Harmer
0.128
213560DLW11-12
Adder
1.724
219907AC1-030 C
Solar/Wind Harmer
0.088
219348LDSOLAR C
Solar/Wind Harmer
0.377
219222BRL12CT2
Adder
5.621
213611FALLS1-3
Adder
2.216
214194N WALES4
Adder
0.533
20716028EGP_W2-019
Solar/Wind Harmer
0.29
207522AF2-254 C
Solar/Wind Harmer
0.896
20717128DIX_Z2-102
Solar/Wind Harmer
0.824
20715828PEM_W1-120
Solar/Wind Harmer
0.333
963711AG1-223 GEN
Solar/Wind Harmer
0.92
20714528FRN_Y2-051
Solar/Wind Harmer
0.183
219276PARKLANDSO C
Solar/Wind Harmer
0.287
219680HOPEWELLV C1
Solar/Wind Harmer
0.047
20715228NPK_W1-113
Solar/Wind Harmer
0.267
20720528MAN_W1-024
Solar/Wind Harmer
0.158
20720428HOL_W1-112
Solar/Wind Harmer
0.214
20635828PARLN1&2
Adder
4.586
20635028RRCT1&2
Adder
7.301
218524CNTRALGAS1 C
Solar/Wind Harmer
0.229
218440SUMMTASSOC C
Solar/Wind Harmer
0.079
218428ETC SOLAR C
Solar/Wind Harmer
0.022
219258KINSLEYDEP C
Solar/Wind Harmer
0.206
213942SCHUYLKILL
Adder
2.27
213942SCHUYLKILL
Adder
1.736
213957STHWK3-4
Adder
1.735
213957STHWK3-4
Adder
1.735
213561DLWR9-10
Adder
2.254
213561DLWR9-10
Adder
1.724
219615MILLCREEK C
Solar/Wind Harmer
0.15
219610FLORENCE C
Solar/Wind Harmer
0.872
219224BRL12CT4
Adder
5.621
213611FALLS1-3
Adder
2.216
213611FALLS1-3
Adder
2.216
20720728JCB_W1-129
Solar/Wind Harmer
0.186
20715028HAN_X4-015
Solar/Wind Harmer
0.186
207487AE2-000G4
Solar/Wind Harmer
19.645
207497AE2-000G2
Solar/Wind Harmer
19.645
207500AE2-000G1
Solar/Wind Harmer
19.645
207507AE2-000G3
Solar/Wind Harmer
19.645
963401AG1-189 GEN
Solar/Wind Harmer
1.417
970025AG2-016 GEN
Solar/Wind Harmer
1.766
971189AH1-054 GEN
Solar/Wind Harmer
0.735
207445AB1-138_GEN
Solar/Wind Harmer
0.361
219620RIDERU C
Solar/Wind Harmer
0.035
20714428HOW_X1-037
Solar/Wind Harmer
0.767
20720628TIN_W1-124
Solar/Wind Harmer
0.618
20716228APLW2-078
Solar/Wind Harmer
0.548
971521AH1-258 GEN
Solar/Wind Harmer
1.679
20635928PARLN3&4
Adder
4.586
218526CNTRALGAS2 C
Solar/Wind Harmer
0.229
20675528CPH_W2-050
Solar/Wind Harmer
0.356
20673828FLE_V3-070
Solar/Wind Harmer
0.289
20676128MHD_W3-029
Solar/Wind Harmer
0.295
218449LINSOLAR C
Solar/Wind Harmer
0.622
20676428JCR_X2-075
Solar/Wind Harmer
0.211
217167KRNY_14
Adder
5.746
217086KRNY_131
Adder
5.697
217147KRNY_1212
Adder
5.466
217147KRNY_1212
Adder
5.368
217146KRNY_1234
Adder
5.356
217146KRNY_1234
Adder
5.319
964851AG1-348 GEN
Solar/Wind Harmer
0.845
971009AG2-626 GEN
Solar/Wind Harmer
1.014
207408W3-077 C
Solar/Wind Harmer
0.313
20675128HRM_W1-127
Solar/Wind Harmer
0.105
20462827N BANGR8
Adder
0.443
20486527WR_V4-052
Adder
0.661
961261AF2-417 GEN
Solar/Wind Harmer
0.601
208862AG1-362 C
Solar/Wind Harmer
0.496
209026WIENIPP4
Adder
3.19
209027LOR2_Q27
Solar/Wind Harmer
2.665
212266LOR1
Solar/Wind Harmer
0.706
209029WAYMART-WD
Solar/Wind Harmer
1.532
209030FRFA O01
Adder
0.166
209054AE2-059 GEN
Solar/Wind Harmer
0.966
959431AF2-234 GEN
Solar/Wind Harmer
1.134
964051AG1-259 GEN
Solar/Wind Harmer
0.761
964061AG1-260 GEN
Solar/Wind Harmer
0.761
959421AF2-233 GEN
Solar/Wind Harmer
0.567
226929AD2-058 GEN
Solar/Wind Helper
0.114
219908AB1-139 C
Solar/Wind Harmer
0.236
219919AE1-041 FULL
Solar/Wind Harmer
0.025
972275AH1-722 GEN
Adder
19.539
20673628F1S_V4-069
Solar/Wind Harmer
0.111
207528AF2-192 GEN
Solar/Wind Harmer
0.787
217209CENTRL HS C
Solar/Wind Harmer
0.028
20671828STAW2-080
Solar/Wind Harmer
0.065
217186ESSEX_G9
Adder
2.44
217121ECCF
Adder
0.268
217083KRNY_132
Adder
5.746
217208PARK ELE C
Solar/Wind Harmer
0.016
20676728BRNX1-095
Solar/Wind Harmer
0.109
966261AG1-495 GEN
Solar/Wind Harmer
2.174
207439AE1-081 C O1
Solar/Wind Harmer
0.037
20676328BVR_Y1-020
Solar/Wind Harmer
0.204
207530AG1-191 GEN
Solar/Wind Harmer
0.851
20674628WNG_W3-110
Solar/Wind Harmer
0.249
20676228FRD_X1-012
Solar/Wind Harmer
0.365
20675828AU_W4-064
Solar/Wind Harmer
0.107
20674928WA_W3-044
Solar/Wind Harmer
0.298
971519AH1-257 GEN
Solar/Wind Harmer
1.561
20675728RH_W2-091
Solar/Wind Harmer
0.373
207484AF2-139 C O1
Solar/Wind Harmer
0.313
207518AF1-320_GEN
Solar/Wind Harmer
2.263
20465127PORT CT
Adder
1.855
208909MACR G3
Adder
98.264
211065PSPA IPP
Solar/Wind Harmer
0.276
20465527S.RDG CT
Adder
1.698
961301AF2-421 GEN
Solar/Wind Harmer
0.599
963151AG1-164 GEN
Solar/Wind Harmer
0.599
209023WIENIPP1
Adder
6.455
209025WIENIPP3
Adder
3.222
963071AG1-156 GEN
Solar/Wind Harmer
5.892
209010PEIP 1
Adder
0.381
961341AF2-425 GEN
Solar/Wind Harmer
0.58
208835TUHI V3-051
Solar/Wind Harmer
0.038
212507AE2-042_GEN
Solar/Wind Harmer
1.712
946731AF1-337 GEN
Solar/Wind Harmer
0.568
200200DELTA2 CT1
50/50
2.13
200193DELTA CT2
50/50
1.19
200203Y1-065-STG
50/50
4.285
200055ROCKSP 4
50/50
1.547
233987AB2-037 GEN
Solar/Wind Harmer
8.365
232907VN8
Adder
22.071
233923SMA
Solar/Wind Harmer
2.685
233997TMININ_4.2
Solar/Wind Harmer
0.732
232406W1-004 FULL
Solar/Wind Harmer
0.735
232914OH NUG3
Adder
6.491
232916OH NUG5
Adder
6.491
232921TASLEY2G
Adder
3.793
232434Z2-077 GEN
Solar/Wind Harmer
0.184
233964AF2-378 GEN
Solar/Wind Harmer
0.094
232417X3-008 C
Solar/Wind Harmer
0.826
233973AC2-185 C
Solar/Wind Harmer
3.977
970695AG2-447 GEN
Solar/Wind Harmer
2.631
233939AC1-091 C
Solar/Wind Harmer
1.969
233972AC1-094 C
Solar/Wind Harmer
1.581
233950AC2-186 GEN
Solar/Wind Harmer
0.413
232422X3-066 FULL
Solar/Wind Harmer
0.183
233933AB2-153 GEN
Solar/Wind Harmer
0.822
233935AB2-179 C
Solar/Wind Harmer
1.815
228711V2-041C
Solar/Wind Harmer
0.388
230415AB2-049 C
Solar/Wind Harmer
0.122
209018SUNBIPCT
Adder
4.224
209008PAXT IPP
Adder
1.196
219035LINDEN_G8
Adder
10.199
972261AH1-715 GEN2
Adder
9.904
217081WEATEXAS C
Solar/Wind Harmer
0.053
217202FBANKSOLAR C
Solar/Wind Harmer
0.045
217201HACKENSOLA C
Solar/Wind Harmer
0.045
972237AH1-703 GEN
Adder
6.255
217206BARNGR HS C
Solar/Wind Harmer
0.019
217086KRNY_131
Adder
5.758
217083KRNY_132
Adder
5.71
217204WCALDSOLAR C
Solar/Wind Harmer
0.045
20674328GAR_V4-001
Solar/Wind Harmer
0.068
20674828DL_W4-046
Solar/Wind Harmer
0.399
207471AF2-354 C
Solar/Wind Harmer
0.317
20634528N27_Y2-018
Solar/Wind Harmer
0.166
20675928HOL_W4-097
Solar/Wind Harmer
0.081
20465127PORT CT
Adder
2.461
20465527S.RDG CT
Adder
1.643
961541AF2-445A GEN
Solar/Wind Harmer
1.915
209010PEIP 1
Adder
2.097
209010PEIP 1
Adder
0.307
961431AF2-434 GEN
Solar/Wind Harmer
0.579
946751AF1-339 GEN
Solar/Wind Harmer
0.568
209130AF1-271A GEN
Solar/Wind Harmer
1.594
213497CHSTR7-9
Adder
1.754
219623KINSLEYBEA C
Solar/Wind Harmer
0.272
213958STHWK5-6
Adder
1.735
219921AF1-264
Solar/Wind Harmer
0.092
219291REEVESSOUT C
Solar/Wind Harmer
0.038
218660EHAMPSOLAR C
Solar/Wind Harmer
0.111
219914AD2-027 C
Solar/Wind Harmer
0.381
219688LUMSOLAR_S C
Solar/Wind Harmer
0.128
213560DLW11-12
Adder
1.724
219236SOUTHERNHQ C
Solar/Wind Harmer
0.043
219221BRL12CT1
Adder
5.621
219223BRL12CT3
Adder
5.621
213815MOSER1-3
Adder
2.233
959561AF2-247 GEN
Solar/Wind Harmer
0.304
20716428NHV_W2-082
Solar/Wind Harmer
1.11
20715728PEM_W1-119
Solar/Wind Harmer
0.333
20636028O CRK C1
Adder
4.408
963391AG1-188 GEN
Solar/Wind Harmer
2.336
20714928UPF_X1-085
Solar/Wind Harmer
0.253
219114HARTZY_C
Solar/Wind Harmer
0.52
971667AH1-334 GEN
Solar/Wind Harmer
1.712
219727YARDVSOLFA C
Solar/Wind Harmer
0.567
219918AC2-009 C
Solar/Wind Harmer
0.016
207454AA2-184 E
Solar/Wind Harmer
0.62
219612MATRIX C
Solar/Wind Harmer
0.114
20716928W4-060COL
Solar/Wind Harmer
0.441
20635828PARLN1&2
Adder
2.077
20635928PARLN3&4
Adder
2.077
217213AMBOY SO C
Solar/Wind Harmer
0.078
219249CENTRALDIV C
Solar/Wind Harmer
0.025
207442AE1-156 GEN
Solar/Wind Harmer
0.46
20673728F2S_V4-070
Solar/Wind Harmer
0.111
217211CAMDEN ST C
Solar/Wind Harmer
0.015
217169METRODIV C
Solar/Wind Harmer
0.025
217194REDH C
Solar/Wind Harmer
0.304
20674528F3S_W2-016
Solar/Wind Harmer
0.872
207510AF2-138 C
Solar/Wind Harmer
1.1
207511W3-106 GEN
Solar/Wind Harmer
0.204
971007AG2-625 GEN
Solar/Wind Harmer
1.589
207437AD2-070 GEN
Solar/Wind Harmer
0.187
20633028GILCT9
Adder
17.557
20671928W4-073
Solar/Wind Harmer
0.268
20674128FR_U2-059
Solar/Wind Harmer
0.114
20466127PORT 5CT
Adder
16.36
20465427SHAW CT
Adder
2.379
209116AE2-175 GEN
Solar/Wind Harmer
2.519
211065PSPA IPP
Solar/Wind Harmer
0.276
205941AD2-115 GEN
Solar/Wind Harmer
0.567
963161AG1-165 GEN
Solar/Wind Harmer
0.599
209025WIENIPP3
Adder
3.157
970095AG2-074 GEN
Solar/Wind Harmer
3.731
208972BECR K09
Solar/Wind Harmer
0.627
961331AF2-424 GEN
Solar/Wind Harmer
0.58
961421AF2-433 GEN
Solar/Wind Harmer
0.579
957921AF2-086 GEN
Solar/Wind Harmer
0.563
209142AF1-226 GEN
Solar/Wind Harmer
3.351
209093AE2-110 GEN
Solar/Wind Harmer
1.447
209120AE2-241 GEN
Solar/Wind Harmer
1.915
208835TUHI V3-051
Solar/Wind Harmer
0.038
946691AF1-333 GEN
Solar/Wind Harmer
0.568
946741AF1-338 GEN
Solar/Wind Harmer
0.568
209071AE2-133 GEN
Solar/Wind Harmer
0.96
972221AH1-695 GEN
Adder
80.797
227287AC2-120 GEN
Solar/Wind Helper
0.405
226910AB2-157 C
Solar/Wind Helper
0.017
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.778
VTFLTFEXP_VFT->PJM
CMTX
83.748
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.16
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.52
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.114
BlueGrassPJM->LTFIMP_BlueG
CLTF
7.862
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
31.752
CBM NorthLTFEXP_CBM-N->PJM
CBM
49.127
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.69 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3150.34
MW Contribution:
3.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
142.643
200201DELTA2 CT2
50/50
2.986
200034PCHBTM 2
50/50
17.405
200035PCHBTM 3
50/50
17.342
200205Y1-065-CTG2
50/50
3.41
232918OH NUG7
50/50
8.58
232905CHERITON_25
50/50
2.399
232926CRISFLD1
50/50
1.919
232910NRG_G1
50/50
8.406
232410W1-006 C
Solar/Wind Harmer
0.921
234015AF2-250 C
Solar/Wind Harmer
0.111
233994AC2-023 GEN
Solar/Wind Harmer
2.473
232428Y3-058 C
Solar/Wind Harmer
0.768
231940T-011
Adder
0.687
233946AB2-136 GEN
Solar/Wind Harmer
3.672
233971AC1-093 C
Solar/Wind Harmer
2.344
234036AF2-325 C
Solar/Wind Harmer
0.844
234041AC1-190 GEN
Solar/Wind Harmer
8.246
232899W1-062
Adder
8.852
233952AC2-187 GEN
Solar/Wind Harmer
1.035
233954AC2-188 GEN
Solar/Wind Harmer
1.035
233984AB2-036 GEN
Solar/Wind Harmer
11.421
232424Y1-079 C
Solar/Wind Harmer
0.515
234014AF1-036_GEN
Solar/Wind Harmer
2.476
232436AB1-176 C
Solar/Wind Harmer
0.209
233930AB2-032 GEN
Solar/Wind Harmer
0.76
200202DELTA2 ST
50/50
5.057
200195DELTA ST
50/50
2.578
200052ROCKSP 1
50/50
2.146
200053ROCKSP 2
50/50
2.104
232912OH NUG1
50/50
8.637
232913OH NUG2
50/50
8.522
232616GEN FOOD
50/50
0.159
233901CHERRYDALE C
Solar/Wind Harmer
1.036
233940AF2-379 C
Solar/Wind Harmer
0.172
232904IR4
Adder
74.501
232920IR10
Adder
2.912
232432Z2-076 GEN
Solar/Wind Harmer
0.122
971195AH1-057 GEN
Solar/Wind Harmer
0.898
233955AB2-172 GEN
Solar/Wind Harmer
4.602
232813VAUGHN
Adder
0.541
233968AD2-076_GEN
Solar/Wind Harmer
6.066
970597AG2-380 GEN
Solar/Wind Harmer
3.809
231906DC3 NUG
Adder
12.777
231902DC CT7
Adder
10.215
231907DC10
Adder
3.19
233915AB1-141 GEN
Solar/Wind Harmer
0.903
231919CHRIST1
Adder
3.889
231920CHRIST2
Adder
3.803
970453AG2-297 GEN
Solar/Wind Harmer
2.118
972141AH1-641 GEN
Solar/Wind Harmer
2.186
230430AE1-229_GEN
Solar/Wind Harmer
21.736
964001AG1-254 GEN
Solar/Wind Harmer
5.529
230422AE1-104_GEN1
Solar/Wind Harmer
25.577
230425AE1-104_GEN2
Solar/Wind Harmer
25.577
228728W1-130C
Solar/Wind Harmer
0.502
227927V4-067C
Solar/Wind Harmer
0.149
230434AG1-499 GEN
Solar/Wind Harmer
0.437
230407AD2-065 C
Solar/Wind Harmer
0.099
219137THOSOLAR C
Solar/Wind Harmer
0.897
219258KINSLEYDEP C
Solar/Wind Harmer
0.239
213942SCHUYLKILL
Adder
2.602
213942SCHUYLKILL
Adder
1.989
213957STHWK3-4
Adder
1.988
213957STHWK3-4
Adder
1.988
213561DLWR9-10
Adder
2.576
213561DLWR9-10
Adder
1.97
200200DELTA2 CT1
50/50
2.986
200193DELTA CT2
50/50
1.669
200203Y1-065-STG
50/50
5.906
200055ROCKSP 4
50/50
2.133
231914HR8
50/50
2.016
231911HR5
50/50
1.326
232907VN8
50/50
29.37
232914OH NUG3
50/50
8.637
232916OH NUG5
50/50
8.637
232921TASLEY2G
50/50
5.048
234034AF2-060
50/50
1.727
233921W3-032A-STG1
50/50
1.275
232911NRG_G2
50/50
0.46
233987AB2-037 GEN
Solar/Wind Harmer
10.497
233923SMA
Solar/Wind Harmer
3.368
233997TMININ_4.2
Solar/Wind Harmer
0.918
232406W1-004 FULL
Solar/Wind Harmer
0.921
232434Z2-077 GEN
Solar/Wind Harmer
0.23
233973AC2-185 C
Solar/Wind Harmer
4.987
970695AG2-447 GEN
Solar/Wind Harmer
3.299
200192DELTA CT1
50/50
1.669
200194DELTA CT3
50/50
1.669
200204Y1-065-CTG1
50/50
3.41
200054ROCKSP 3
50/50
2.17
231912HR6
50/50
1.326
231913HR7
50/50
1.326
232917OH NUG6
50/50
8.599
232915OH NUG4
50/50
8.58
233920W3-032A-CTG1
50/50
1.973
232919VN10
50/50
2.744
233996TM1833_GEN
Solar/Wind Harmer
0.918
233998TM1NIN_3.36
Solar/Wind Harmer
0.918
232404W1-003 C
Solar/Wind Harmer
0.921
232408W1-005 C
Solar/Wind Harmer
0.921
234033AF1-007_GEN
Solar/Wind Harmer
34.273
232901NORTHST
Adder
7.669
232426Y1-080 FULL
Solar/Wind Harmer
0.176
972177AH1-672 GEN
Solar/Wind Harmer
12.374
233970AC1-092 C
Solar/Wind Harmer
2.469
232900DEMECSMY
Adder
8.49
232902EASTMUNI
Adder
11.979
234012AE2-112_GEN
Solar/Wind Harmer
2.104
233944AB2-135 GEN
Solar/Wind Harmer
4.777
233918AB1-142 GEN
Solar/Wind Harmer
0.903
972251AH1-710 GEN
Adder
39.968
231918WEST 1
Adder
2.961
231917EM10
Adder
2.058
228206SHRMN CT
Adder
12.684
228732V1-021 C
Adder
0.144
228260V4-054C
Solar/Wind Harmer
0.782
970997AG2-616 GEN
Solar/Wind Harmer
7.285
228729W2-030 C
Solar/Wind Harmer
0.436
228400MICK 1CT
Adder
8.855
213497CHSTR7-9
Adder
2.026
213497CHSTR7-9
Adder
2.026
219766PARADISE C
Solar/Wind Harmer
0.231
219686LUMSOLAR_N C
Solar/Wind Harmer
0.148
213958STHWK5-6
Adder
1.988
219907AC1-030 C
Solar/Wind Harmer
0.101
213560DLW11-12
Adder
1.97
219348LDSOLAR C
Solar/Wind Harmer
0.43
219222BRL12CT2
Adder
6.417
213611FALLS1-3
Adder
2.508
20716028EGP_W2-019
Solar/Wind Harmer
0.328
207522AF2-254 C
Solar/Wind Harmer
1.014
20717128DIX_Z2-102
Solar/Wind Harmer
0.932
20715828PEM_W1-120
Solar/Wind Harmer
0.377
214194N WALES4
Adder
0.6
963711AG1-223 GEN
Solar/Wind Harmer
1.026
20714528FRN_Y2-051
Solar/Wind Harmer
0.205
219276PARKLANDSO C
Solar/Wind Harmer
0.319
219680HOPEWELLV C1
Solar/Wind Harmer
0.052
20715228NPK_W1-113
Solar/Wind Harmer
0.295
20720528MAN_W1-024
Solar/Wind Harmer
0.174
20720428HOL_W1-112
Solar/Wind Harmer
0.236
20635828PARLN1&2
Adder
4.999
20635028RRCT1&2
Adder
7.936
218524CNTRALGAS1 C
Solar/Wind Harmer
0.247
218440SUMMTASSOC C
Solar/Wind Harmer
0.086
218428ETC SOLAR C
Solar/Wind Harmer
0.024
219908AB1-139 C
Solar/Wind Harmer
0.254
219919AE1-041 FULL
Solar/Wind Harmer
0.027
972275AH1-722 GEN
Adder
21.024
20673628F1S_V4-069
Solar/Wind Harmer
0.119
207528AF2-192 GEN
Solar/Wind Harmer
0.842
217209CENTRL HS C
Solar/Wind Harmer
0.029
217186ESSEX_G9
Adder
2.593
217121ECCF
Adder
0.285
217083KRNY_132
Adder
6.105
217208PARK ELE C
Solar/Wind Harmer
0.017
20671828STAW2-080
Solar/Wind Harmer
0.069
20676728BRNX1-095
Solar/Wind Harmer
0.114
966261AG1-495 GEN
Solar/Wind Harmer
2.262
207439AE1-081 C O1
Solar/Wind Harmer
0.038
20676328BVR_Y1-020
Solar/Wind Harmer
0.211
20674628WNG_W3-110
Solar/Wind Harmer
0.257
207530AG1-191 GEN
Solar/Wind Harmer
0.877
20676228FRD_X1-012
Solar/Wind Harmer
0.377
20675828AU_W4-064
Solar/Wind Harmer
0.11
20674928WA_W3-044
Solar/Wind Harmer
0.304
971519AH1-257 GEN
Solar/Wind Harmer
1.584
20675728RH_W2-091
Solar/Wind Harmer
0.377
207518AF1-320_GEN
Solar/Wind Harmer
2.286
207484AF2-139 C O1
Solar/Wind Harmer
0.316
20465127PORT CT
Adder
1.869
208909MACR G3
Adder
97.98
211065PSPA IPP
Solar/Wind Harmer
0.27
961301AF2-421 GEN
Solar/Wind Harmer
0.57
963151AG1-164 GEN
Solar/Wind Harmer
0.57
209023WIENIPP1
Adder
6.142
209025WIENIPP3
Adder
3.066
963071AG1-156 GEN
Solar/Wind Harmer
5.641
209010PEIP 1
Adder
0.368
961341AF2-425 GEN
Solar/Wind Harmer
0.533
20465527S.RDG CT
Adder
1.473
316415AF1-147_GEN2
Solar/Wind Helper
0.765
233982AB2-133 GEN
Solar/Wind Harmer
4.439
228201CARL#2CT
Adder
5.239
228200CARL#1CT
Adder
4.983
228251CARLLS#4
Adder
0.481
228351V2-046C
Solar/Wind Harmer
1.528
230433AD2-135 GEN
Solar/Wind Harmer
0.077
230511AF1-262
Solar/Wind Harmer
0.139
228307PCLP GT
Adder
9.126
228754AB1-001 C
Solar/Wind Harmer
0.105
972233AH1-701 GEN
Adder
3.149
213589EDDYSTN4
Adder
59.105
213587EDDYSTN3
Adder
59.094
219272CLEANLIGHT C
Solar/Wind Harmer
0.134
219904AC1-010 C
Solar/Wind Harmer
0.278
219287REEVESEAST C
Solar/Wind Harmer
0.987
219912AD2-042 GEN
Solar/Wind Harmer
0.582
219906AC1-017 C
Solar/Wind Harmer
0.161
219607WPEMNERT C
Solar/Wind Harmer
0.301
219304NAMERICA C
Solar/Wind Harmer
0.223
213535CROYDN11
Adder
7.346
213815MOSER1-3
Adder
2.537
213815MOSER1-3
Adder
2.537
214067T20SOLAR
Solar/Wind Harmer
0.179
20720828JCB_W4-025
Solar/Wind Harmer
0.32
20636128O CRK C2
Adder
4.542
207459AE1-142 C O1
Solar/Wind Harmer
0.738
20628028LAKEHURS
Adder
0.665
20714828MDF_W3-079
Solar/Wind Harmer
0.212
219817TRENTONSOL C
Solar/Wind Harmer
0.759
20641628MLH_W1-032
Solar/Wind Harmer
0.201
20742028HF_AC1-207
Solar/Wind Harmer
0.536
217197RE CRAN C
Solar/Wind Harmer
0.365
218438BLK ROCK C
Solar/Wind Harmer
0.092
924131AB2-057 GEN
Solar/Wind Harmer
0.693
20635028RRCT1&2
Adder
7.814
20635128RRCT3&4
Adder
7.542
20635128RRCT3&4
Adder
6.579
218418LINDEN_G5
Adder
11.436
218419LINDEN_G6
Adder
11.436
972260AH1-715 GEN1
Adder
9.158
219036LINDEN_G7
Adder
11.085
219035LINDEN_G8
Adder
10.926
972261AH1-715 GEN2
Adder
10.611
20675428EAM_W2-061
Solar/Wind Harmer
0.125
217081WEATEXAS C
Solar/Wind Harmer
0.057
217202FBANKSOLAR C
Solar/Wind Harmer
0.048
217201HACKENSOLA C
Solar/Wind Harmer
0.048
972237AH1-703 GEN
Adder
6.647
217206BARNGR HS C
Solar/Wind Harmer
0.02
217086KRNY_131
Adder
6.118
217083KRNY_132
Adder
6.066
217204WCALDSOLAR C
Solar/Wind Harmer
0.048
20674328GAR_V4-001
Solar/Wind Harmer
0.07
20674828DL_W4-046
Solar/Wind Harmer
0.408
207471AF2-354 C
Solar/Wind Harmer
0.323
20634528N27_Y2-018
Solar/Wind Harmer
0.169
20675928HOL_W4-097
Solar/Wind Harmer
0.082
20465127PORT CT
Adder
2.48
209010PEIP 1
Adder
2.024
209010PEIP 1
Adder
0.296
961541AF2-445A GEN
Solar/Wind Harmer
1.772
961431AF2-434 GEN
Solar/Wind Harmer
0.531
20465527S.RDG CT
Adder
1.426
316411AF1-147_GEN1
Solar/Wind Helper
0.765
219615MILLCREEK C
Solar/Wind Harmer
0.172
219610FLORENCE C
Solar/Wind Harmer
0.996
219224BRL12CT4
Adder
6.417
213611FALLS1-3
Adder
2.508
213611FALLS1-3
Adder
2.508
20720728JCB_W1-129
Solar/Wind Harmer
0.211
20715028HAN_X4-015
Solar/Wind Harmer
0.211
207487AE2-000G4
Solar/Wind Harmer
22.203
207497AE2-000G2
Solar/Wind Harmer
22.203
207500AE2-000G1
Solar/Wind Harmer
22.203
207507AE2-000G3
Solar/Wind Harmer
22.203
963401AG1-189 GEN
Solar/Wind Harmer
1.599
970025AG2-016 GEN
Solar/Wind Harmer
1.991
971189AH1-054 GEN
Solar/Wind Harmer
0.828
207445AB1-138_GEN
Solar/Wind Harmer
0.405
219620RIDERU C
Solar/Wind Harmer
0.038
20714428HOW_X1-037
Solar/Wind Harmer
0.849
20720628TIN_W1-124
Solar/Wind Harmer
0.683
20716228APLW2-078
Solar/Wind Harmer
0.606
971521AH1-258 GEN
Solar/Wind Harmer
1.85
20635928PARLN3&4
Adder
4.999
218526CNTRALGAS2 C
Solar/Wind Harmer
0.248
20675528CPH_W2-050
Solar/Wind Harmer
0.383
20673828FLE_V3-070
Solar/Wind Harmer
0.31
218449LINSOLAR C
Solar/Wind Harmer
0.666
20676128MHD_W3-029
Solar/Wind Harmer
0.316
20676428JCR_X2-075
Solar/Wind Harmer
0.226
217167KRNY_14
Adder
6.105
217086KRNY_131
Adder
6.053
217147KRNY_1212
Adder
5.807
217147KRNY_1212
Adder
5.703
217146KRNY_1234
Adder
5.69
217146KRNY_1234
Adder
5.652
964851AG1-348 GEN
Solar/Wind Harmer
0.859
971009AG2-626 GEN
Solar/Wind Harmer
1.03
207408W3-077 C
Solar/Wind Harmer
0.317
20675128HRM_W1-127
Solar/Wind Harmer
0.106
20462827N BANGR8
Adder
0.445
961261AF2-417 GEN
Solar/Wind Harmer
0.587
209026WIENIPP4
Adder
3.035
209029WAYMART-WD
Solar/Wind Harmer
1.478
209027LOR2_Q27
Solar/Wind Harmer
2.466
212266LOR1
Solar/Wind Harmer
0.654
20486527WR_V4-052
Adder
0.575
226929AD2-058 GEN
Solar/Wind Helper
0.1
3138216PACIFIC
Solar/Wind Helper
0.038
3141426STAFORD
Solar/Wind Helper
0.049
233939AC1-091 C
Solar/Wind Harmer
2.469
233972AC1-094 C
Solar/Wind Harmer
1.982
233964AF2-378 GEN
Solar/Wind Harmer
0.117
232417X3-008 C
Solar/Wind Harmer
1.035
233950AC2-186 GEN
Solar/Wind Harmer
0.517
232422X3-066 FULL
Solar/Wind Harmer
0.228
233933AB2-153 GEN
Solar/Wind Harmer
1.026
233935AB2-179 C
Solar/Wind Harmer
2.248
228711V2-041C
Solar/Wind Harmer
0.46
230415AB2-049 C
Solar/Wind Harmer
0.143
213497CHSTR7-9
Adder
2.026
219623KINSLEYBEA C
Solar/Wind Harmer
0.316
219921AF1-264
Solar/Wind Harmer
0.106
219291REEVESSOUT C
Solar/Wind Harmer
0.044
218660EHAMPSOLAR C
Solar/Wind Harmer
0.128
219688LUMSOLAR_S C
Solar/Wind Harmer
0.148
219914AD2-027 C
Solar/Wind Harmer
0.439
213958STHWK5-6
Adder
1.988
219236SOUTHERNHQ C
Solar/Wind Harmer
0.049
213560DLW11-12
Adder
1.97
219221BRL12CT1
Adder
6.417
219223BRL12CT3
Adder
6.417
213815MOSER1-3
Adder
2.537
959561AF2-247 GEN
Solar/Wind Harmer
0.344
20716428NHV_W2-082
Solar/Wind Harmer
1.256
20715728PEM_W1-119
Solar/Wind Harmer
0.377
20636028O CRK C1
Adder
4.982
963391AG1-188 GEN
Solar/Wind Harmer
2.633
20714928UPF_X1-085
Solar/Wind Harmer
0.285
971667AH1-334 GEN
Solar/Wind Harmer
1.923
219114HARTZY_C
Solar/Wind Harmer
0.583
219727YARDVSOLFA C
Solar/Wind Harmer
0.634
207454AA2-184 E
Solar/Wind Harmer
0.686
219918AC2-009 C
Solar/Wind Harmer
0.018
219612MATRIX C
Solar/Wind Harmer
0.125
20716928W4-060COL
Solar/Wind Harmer
0.483
20635828PARLN1&2
Adder
2.264
20635928PARLN3&4
Adder
2.264
217213AMBOY SO C
Solar/Wind Harmer
0.084
219249CENTRALDIV C
Solar/Wind Harmer
0.026
207442AE1-156 GEN
Solar/Wind Harmer
0.492
20673728F2S_V4-070
Solar/Wind Harmer
0.119
217211CAMDEN ST C
Solar/Wind Harmer
0.016
217169METRODIV C
Solar/Wind Harmer
0.026
217194REDH C
Solar/Wind Harmer
0.323
20674528F3S_W2-016
Solar/Wind Harmer
0.919
207510AF2-138 C
Solar/Wind Harmer
1.136
207511W3-106 GEN
Solar/Wind Harmer
0.211
971007AG2-625 GEN
Solar/Wind Harmer
1.615
207437AD2-070 GEN
Solar/Wind Harmer
0.188
20671928W4-073
Solar/Wind Harmer
0.269
20466127PORT 5CT
Adder
16.497
20674128FR_U2-059
Solar/Wind Harmer
0.115
20633028GILCT9
Adder
17.624
20465427SHAW CT
Adder
2.391
209116AE2-175 GEN
Solar/Wind Harmer
2.49
211065PSPA IPP
Solar/Wind Harmer
0.27
963161AG1-165 GEN
Solar/Wind Harmer
0.57
209025WIENIPP3
Adder
3.004
970095AG2-074 GEN
Solar/Wind Harmer
3.572
208972BECR K09
Solar/Wind Harmer
0.596
205941AD2-115 GEN
Solar/Wind Harmer
0.51
961331AF2-424 GEN
Solar/Wind Harmer
0.533
961421AF2-433 GEN
Solar/Wind Harmer
0.531
957921AF2-086 GEN
Solar/Wind Harmer
0.517
209142AF1-226 GEN
Solar/Wind Harmer
3.076
209093AE2-110 GEN
Solar/Wind Harmer
1.328
209120AE2-241 GEN
Solar/Wind Harmer
1.758
227287AC2-120 GEN
Solar/Wind Helper
0.351
226910AB2-157 C
Solar/Wind Helper
0.014
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.048
VTFLTFEXP_VFT->PJM
CMTX
89.246
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.334
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.862
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.924
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.668
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
34.511
CBM NorthLTFEXP_CBM-N->PJM
CBM
50.042
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for COOPER-GRACETON 230.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:BGE/PECO
Facility Description:
COOPER-GRACETON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.26 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:631.55
MW Contribution:
1.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.445
231917EM10
Adder
1.009
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233918AB1-142 GEN
Solar/Wind Harmer
0.407
233944AB2-135 GEN
Solar/Wind Harmer
2.121
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.99
232902EASTMUNI
Adder
4.962
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.028
233996TM1833_GEN
Solar/Wind Harmer
0.361
233998TM1NIN_3.36
Solar/Wind Harmer
0.361
232404W1-003 C
Solar/Wind Harmer
0.362
232408W1-005 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.184
232915OH NUG4
Adder
3.177
234033AF1-007_GEN
Solar/Wind Harmer
13.356
972177AH1-672 GEN
Solar/Wind Harmer
4.817
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.258
232901NORTHST
Adder
2.902
233970AC1-092 C
Solar/Wind Harmer
0.928
228400MICK 1CT
Adder
3.643
219766PARADISE C
Solar/Wind Harmer
0.096
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.861
228260V4-054C
Solar/Wind Harmer
0.303
228206SHRMN CT
Adder
4.833
219348LDSOLAR C
Solar/Wind Harmer
0.175
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.817
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
228729W2-030 C
Solar/Wind Harmer
0.165
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
20716028EGP_W2-019
Solar/Wind Harmer
0.124
207522AF2-254 C
Solar/Wind Harmer
0.384
20717128DIX_Z2-102
Solar/Wind Harmer
0.353
20715828PEM_W1-120
Solar/Wind Harmer
0.142
219276PARKLANDSO C
Solar/Wind Harmer
0.122
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.807
20635028RRCT1&2
Adder
2.861
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
972275AH1-722 GEN
Adder
7.526
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.302
208909MACR G3
Adder
32.163
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.552
213514CONOW1-2
50/50
0.552
231919CHRIST1
Adder
1.883
231920CHRIST2
Adder
1.841
233915AB1-141 GEN
Solar/Wind Harmer
0.407
233968AD2-076_GEN
Solar/Wind Harmer
2.659
970597AG2-380 GEN
Solar/Wind Harmer
1.67
231906DC3 NUG
Adder
5.531
231902DC CT7
Adder
4.422
231907DC10
Adder
1.381
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.99
213957STHWK3-4
Adder
0.99
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.85
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.353
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232912OH NUG1
Adder
3.198
232913OH NUG2
Adder
3.155
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.136
232904IR4
Adder
29.032
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
219137THOSOLAR C
Solar/Wind Harmer
0.376
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.189
230434AG1-499 GEN
Solar/Wind Harmer
0.174
972141AH1-641 GEN
Solar/Wind Harmer
0.858
230430AE1-229_GEN
Solar/Wind Harmer
8.531
219615MILLCREEK C
Solar/Wind Harmer
0.071
228728W1-130C
Solar/Wind Harmer
0.195
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219224BRL12CT4
Adder
2.608
230422AE1-104_GEN1
Solar/Wind Harmer
9.704
230425AE1-104_GEN2
Solar/Wind Harmer
9.704
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
207487AE2-000G4
Solar/Wind Harmer
8.265
207497AE2-000G2
Solar/Wind Harmer
8.265
207500AE2-000G1
Solar/Wind Harmer
8.265
207507AE2-000G3
Solar/Wind Harmer
8.265
971189AH1-054 GEN
Solar/Wind Harmer
0.31
963401AG1-189 GEN
Solar/Wind Harmer
0.595
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207445AB1-138_GEN
Solar/Wind Harmer
0.15
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.311
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20716228APLW2-078
Solar/Wind Harmer
0.222
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20635928PARLN3&4
Adder
1.807
20675528CPH_W2-050
Solar/Wind Harmer
0.14
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.112
20676128MHD_W3-029
Solar/Wind Harmer
0.114
233935AB2-179 C
Solar/Wind Harmer
1.159
213497CHSTR7-9
Adder
1.074
233933AB2-153 GEN
Solar/Wind Harmer
0.462
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.416
233987AB2-037 GEN
Solar/Wind Harmer
4.194
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.97
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.325
233997TMININ_4.2
Solar/Wind Harmer
0.361
232406W1-004 FULL
Solar/Wind Harmer
0.362
232914OH NUG3
Adder
3.198
232916OH NUG5
Adder
3.198
232921TASLEY2G
Adder
1.869
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.874
970695AG2-447 GEN
Solar/Wind Harmer
1.24
233939AC1-091 C
Solar/Wind Harmer
0.928
233972AC1-094 C
Solar/Wind Harmer
0.745
213815MOSER1-3
Adder
1.097
219914AD2-027 C
Solar/Wind Harmer
0.184
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.227
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20716428NHV_W2-082
Solar/Wind Harmer
0.476
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20636028O CRK C1
Adder
1.854
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963391AG1-188 GEN
Solar/Wind Harmer
0.98
971667AH1-334 GEN
Solar/Wind Harmer
0.715
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.251
219612MATRIX C
Solar/Wind Harmer
0.046
20716928W4-060COL
Solar/Wind Harmer
0.175
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
217213AMBOY SO C
Solar/Wind Harmer
0.03
219249CENTRALDIV C
Solar/Wind Harmer
0.009
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20673728F2S_V4-070
Solar/Wind Harmer
0.043
213508CON10-11
50/50
0.998
213508CON10-11
50/50
0.998
213518CONOW8-9
50/50
0.998
213518CONOW8-9
50/50
0.998
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.446
213587EDDYSTN3
Adder
31.419
233982AB2-133 GEN
Solar/Wind Harmer
2.006
233930AB2-032 GEN
Solar/Wind Harmer
0.342
232436AB1-176 C
Solar/Wind Harmer
0.092
234014AF1-036_GEN
Solar/Wind Harmer
1.085
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.868
232910NRG_G1
Adder
3.245
234041AC1-190 GEN
Solar/Wind Harmer
3.312
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.468
233952AC2-187 GEN
Solar/Wind Harmer
0.409
233954AC2-188 GEN
Solar/Wind Harmer
0.409
233994AC2-023 GEN
Solar/Wind Harmer
0.976
232428Y3-058 C
Solar/Wind Harmer
0.303
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.712
232410W1-006 C
Solar/Wind Harmer
0.362
232918OH NUG7
Adder
3.177
232905CHERITON_25
Adder
0.888
231940T-011
Adder
0.27
232899W1-062
Adder
3.396
233971AC1-093 C
Solar/Wind Harmer
0.881
972233AH1-701 GEN
Adder
1.292
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.244
228307PCLP GT
Adder
3.696
228351V2-046C
Solar/Wind Harmer
0.605
230511AF1-262
Solar/Wind Harmer
0.054
228201CARL#2CT
Adder
2.032
228200CARL#1CT
Adder
1.932
228251CARLLS#4
Adder
0.186
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
213535CROYDN11
Adder
3.004
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
219607WPEMNERT C
Solar/Wind Harmer
0.122
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.388
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.121
20636128O CRK C2
Adder
1.691
207459AE1-142 C O1
Solar/Wind Harmer
0.274
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20714828MDF_W3-079
Solar/Wind Harmer
0.078
20641628MLH_W1-032
Solar/Wind Harmer
0.073
217197RE CRAN C
Solar/Wind Harmer
0.135
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.196
924131AB2-057 GEN
Solar/Wind Harmer
0.253
20635028RRCT1&2
Adder
2.817
20635128RRCT3&4
Adder
2.719
20635128RRCT3&4
Adder
2.372
218418LINDEN_G5
Adder
4.094
218419LINDEN_G6
Adder
4.094
972260AH1-715 GEN1
Adder
3.278
20675428EAM_W2-061
Solar/Wind Harmer
0.045
223401AF1-299 GEN
Solar/Wind Helper
0.272
223402AF1-300 C
Solar/Wind Helper
0.272
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
VTFLTFEXP_VFT->PJM
CMTX
31.572
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.608
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.617
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.957
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.442
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.041
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for COOPER-GRACETON 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:BGE/PECO
Facility Description:
COOPER-GRACETON 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.24 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:631.4
MW Contribution:
1.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233918AB1-142 GEN
Solar/Wind Harmer
0.407
233944AB2-135 GEN
Solar/Wind Harmer
2.12
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.99
232902EASTMUNI
Adder
4.959
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.027
233996TM1833_GEN
Solar/Wind Harmer
0.361
233998TM1NIN_3.36
Solar/Wind Harmer
0.361
232404W1-003 C
Solar/Wind Harmer
0.362
232408W1-005 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.175
234033AF1-007_GEN
Solar/Wind Harmer
13.348
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233970AC1-092 C
Solar/Wind Harmer
0.927
228400MICK 1CT
Adder
3.642
219766PARADISE C
Solar/Wind Harmer
0.096
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.86
228260V4-054C
Solar/Wind Harmer
0.303
228206SHRMN CT
Adder
4.831
219348LDSOLAR C
Solar/Wind Harmer
0.175
213514CONOW1-2
50/50
0.552
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
233915AB1-141 GEN
Solar/Wind Harmer
0.407
233968AD2-076_GEN
Solar/Wind Harmer
2.658
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.42
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.849
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.353
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.135
232904IR4
Adder
29.017
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
219137THOSOLAR C
Solar/Wind Harmer
0.375
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.188
230434AG1-499 GEN
Solar/Wind Harmer
0.174
972141AH1-641 GEN
Solar/Wind Harmer
0.858
230430AE1-229_GEN
Solar/Wind Harmer
8.528
219615MILLCREEK C
Solar/Wind Harmer
0.071
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.552
233935AB2-179 C
Solar/Wind Harmer
1.159
213497CHSTR7-9
Adder
1.074
233933AB2-153 GEN
Solar/Wind Harmer
0.462
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.416
233987AB2-037 GEN
Solar/Wind Harmer
4.192
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.964
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.324
233997TMININ_4.2
Solar/Wind Harmer
0.361
232406W1-004 FULL
Solar/Wind Harmer
0.362
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
232921TASLEY2G
Adder
1.868
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.873
970695AG2-447 GEN
Solar/Wind Harmer
1.239
233939AC1-091 C
Solar/Wind Harmer
0.927
233972AC1-094 C
Solar/Wind Harmer
0.745
213815MOSER1-3
Adder
1.097
219914AD2-027 C
Solar/Wind Harmer
0.184
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.227
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20716428NHV_W2-082
Solar/Wind Harmer
0.476
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20636028O CRK C1
Adder
1.854
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963391AG1-188 GEN
Solar/Wind Harmer
0.98
971667AH1-334 GEN
Solar/Wind Harmer
0.715
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.251
219612MATRIX C
Solar/Wind Harmer
0.046
20716928W4-060COL
Solar/Wind Harmer
0.175
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
217213AMBOY SO C
Solar/Wind Harmer
0.03
219249CENTRALDIV C
Solar/Wind Harmer
0.009
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20673728F2S_V4-070
Solar/Wind Harmer
0.043
228728W1-130C
Solar/Wind Harmer
0.195
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219224BRL12CT4
Adder
2.608
230422AE1-104_GEN1
Solar/Wind Harmer
9.701
230425AE1-104_GEN2
Solar/Wind Harmer
9.701
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
207487AE2-000G4
Solar/Wind Harmer
8.262
207497AE2-000G2
Solar/Wind Harmer
8.262
207500AE2-000G1
Solar/Wind Harmer
8.262
207507AE2-000G3
Solar/Wind Harmer
8.262
971189AH1-054 GEN
Solar/Wind Harmer
0.31
963401AG1-189 GEN
Solar/Wind Harmer
0.595
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207445AB1-138_GEN
Solar/Wind Harmer
0.15
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.311
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20716228APLW2-078
Solar/Wind Harmer
0.221
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.14
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.112
20676128MHD_W3-029
Solar/Wind Harmer
0.114
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.809
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
228729W2-030 C
Solar/Wind Harmer
0.165
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
20716028EGP_W2-019
Solar/Wind Harmer
0.124
207522AF2-254 C
Solar/Wind Harmer
0.384
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715828PEM_W1-120
Solar/Wind Harmer
0.142
219276PARKLANDSO C
Solar/Wind Harmer
0.122
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.86
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
972275AH1-722 GEN
Adder
7.525
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.302
208909MACR G3
Adder
32.158
213508CON10-11
50/50
0.998
213508CON10-11
50/50
0.998
213518CONOW8-9
50/50
0.998
213518CONOW8-9
50/50
0.998
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.44
213587EDDYSTN3
Adder
31.412
233982AB2-133 GEN
Solar/Wind Harmer
2.006
233930AB2-032 GEN
Solar/Wind Harmer
0.342
232436AB1-176 C
Solar/Wind Harmer
0.092
234014AF1-036_GEN
Solar/Wind Harmer
1.085
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
232910NRG_G1
Adder
3.244
234041AC1-190 GEN
Solar/Wind Harmer
3.31
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.467
233952AC2-187 GEN
Solar/Wind Harmer
0.409
233954AC2-188 GEN
Solar/Wind Harmer
0.409
233994AC2-023 GEN
Solar/Wind Harmer
0.976
232428Y3-058 C
Solar/Wind Harmer
0.303
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.711
232410W1-006 C
Solar/Wind Harmer
0.362
232918OH NUG7
Adder
3.175
232905CHERITON_25
Adder
0.888
231940T-011
Adder
0.269
232899W1-062
Adder
3.395
233971AC1-093 C
Solar/Wind Harmer
0.88
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.244
228307PCLP GT
Adder
3.695
228351V2-046C
Solar/Wind Harmer
0.605
230511AF1-262
Solar/Wind Harmer
0.054
228201CARL#2CT
Adder
2.031
228200CARL#1CT
Adder
1.931
228251CARLLS#4
Adder
0.186
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
213535CROYDN11
Adder
3.003
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
219607WPEMNERT C
Solar/Wind Harmer
0.122
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.388
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.121
20636128O CRK C2
Adder
1.69
207459AE1-142 C O1
Solar/Wind Harmer
0.274
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20714828MDF_W3-079
Solar/Wind Harmer
0.078
20641628MLH_W1-032
Solar/Wind Harmer
0.073
217197RE CRAN C
Solar/Wind Harmer
0.135
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.196
924131AB2-057 GEN
Solar/Wind Harmer
0.252
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.719
20635128RRCT3&4
Adder
2.371
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
20675428EAM_W2-061
Solar/Wind Harmer
0.045
223401AF1-299 GEN
Solar/Wind Helper
0.272
223402AF1-300 C
Solar/Wind Helper
0.272
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
VTFLTFEXP_VFT->PJM
CMTX
31.565
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.608
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.956
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.616
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.439
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.039
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for COOPER-GRACETON 230.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:BGE/PECO
Facility Description:
COOPER-GRACETON 230.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.22 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:631.31
MW Contribution:
1.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.552
233935AB2-179 C
Solar/Wind Harmer
1.159
213497CHSTR7-9
Adder
1.074
233933AB2-153 GEN
Solar/Wind Harmer
0.462
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.416
233987AB2-037 GEN
Solar/Wind Harmer
4.192
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.964
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.324
233997TMININ_4.2
Solar/Wind Harmer
0.361
232406W1-004 FULL
Solar/Wind Harmer
0.362
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
232921TASLEY2G
Adder
1.868
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.873
970695AG2-447 GEN
Solar/Wind Harmer
1.239
233939AC1-091 C
Solar/Wind Harmer
0.927
233972AC1-094 C
Solar/Wind Harmer
0.745
213815MOSER1-3
Adder
1.097
219914AD2-027 C
Solar/Wind Harmer
0.184
213514CONOW1-2
50/50
0.552
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
233915AB1-141 GEN
Solar/Wind Harmer
0.407
233968AD2-076_GEN
Solar/Wind Harmer
2.658
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.42
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.849
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.353
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.135
232904IR4
Adder
29.017
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
219137THOSOLAR C
Solar/Wind Harmer
0.375
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.188
230434AG1-499 GEN
Solar/Wind Harmer
0.174
972141AH1-641 GEN
Solar/Wind Harmer
0.858
230430AE1-229_GEN
Solar/Wind Harmer
8.528
219615MILLCREEK C
Solar/Wind Harmer
0.071
228728W1-130C
Solar/Wind Harmer
0.195
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219224BRL12CT4
Adder
2.608
230422AE1-104_GEN1
Solar/Wind Harmer
9.701
230425AE1-104_GEN2
Solar/Wind Harmer
9.701
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
207487AE2-000G4
Solar/Wind Harmer
8.262
207497AE2-000G2
Solar/Wind Harmer
8.262
207500AE2-000G1
Solar/Wind Harmer
8.262
207507AE2-000G3
Solar/Wind Harmer
8.262
971189AH1-054 GEN
Solar/Wind Harmer
0.31
963401AG1-189 GEN
Solar/Wind Harmer
0.595
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207445AB1-138_GEN
Solar/Wind Harmer
0.15
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.311
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20716228APLW2-078
Solar/Wind Harmer
0.221
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.14
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.112
20676128MHD_W3-029
Solar/Wind Harmer
0.114
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.227
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20716428NHV_W2-082
Solar/Wind Harmer
0.476
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20636028O CRK C1
Adder
1.854
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963391AG1-188 GEN
Solar/Wind Harmer
0.98
971667AH1-334 GEN
Solar/Wind Harmer
0.715
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.251
219612MATRIX C
Solar/Wind Harmer
0.046
20716928W4-060COL
Solar/Wind Harmer
0.175
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
217213AMBOY SO C
Solar/Wind Harmer
0.03
219249CENTRALDIV C
Solar/Wind Harmer
0.009
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20673728F2S_V4-070
Solar/Wind Harmer
0.043
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233918AB1-142 GEN
Solar/Wind Harmer
0.407
233944AB2-135 GEN
Solar/Wind Harmer
2.12
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.99
232902EASTMUNI
Adder
4.959
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.027
233996TM1833_GEN
Solar/Wind Harmer
0.361
233998TM1NIN_3.36
Solar/Wind Harmer
0.361
232404W1-003 C
Solar/Wind Harmer
0.362
232408W1-005 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.175
234033AF1-007_GEN
Solar/Wind Harmer
13.348
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233970AC1-092 C
Solar/Wind Harmer
0.927
228400MICK 1CT
Adder
3.642
219766PARADISE C
Solar/Wind Harmer
0.096
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.86
228260V4-054C
Solar/Wind Harmer
0.303
228206SHRMN CT
Adder
4.831
219348LDSOLAR C
Solar/Wind Harmer
0.175
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.809
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
228729W2-030 C
Solar/Wind Harmer
0.165
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
20716028EGP_W2-019
Solar/Wind Harmer
0.124
207522AF2-254 C
Solar/Wind Harmer
0.384
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715828PEM_W1-120
Solar/Wind Harmer
0.142
219276PARKLANDSO C
Solar/Wind Harmer
0.122
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.86
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
213508CON10-11
50/50
0.998
213508CON10-11
50/50
0.998
213518CONOW8-9
50/50
0.998
213518CONOW8-9
50/50
0.998
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.44
213587EDDYSTN3
Adder
31.412
233982AB2-133 GEN
Solar/Wind Harmer
2.006
233930AB2-032 GEN
Solar/Wind Harmer
0.342
232436AB1-176 C
Solar/Wind Harmer
0.092
234014AF1-036_GEN
Solar/Wind Harmer
1.085
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
232910NRG_G1
Adder
3.244
234041AC1-190 GEN
Solar/Wind Harmer
3.31
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.467
233952AC2-187 GEN
Solar/Wind Harmer
0.409
233954AC2-188 GEN
Solar/Wind Harmer
0.409
233994AC2-023 GEN
Solar/Wind Harmer
0.976
232428Y3-058 C
Solar/Wind Harmer
0.303
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.711
232410W1-006 C
Solar/Wind Harmer
0.362
232918OH NUG7
Adder
3.175
232905CHERITON_25
Adder
0.888
231940T-011
Adder
0.269
232899W1-062
Adder
3.395
233971AC1-093 C
Solar/Wind Harmer
0.88
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.244
228307PCLP GT
Adder
3.695
228351V2-046C
Solar/Wind Harmer
0.605
230511AF1-262
Solar/Wind Harmer
0.054
228201CARL#2CT
Adder
2.031
228200CARL#1CT
Adder
1.931
228251CARLLS#4
Adder
0.186
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
213535CROYDN11
Adder
3.003
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
219607WPEMNERT C
Solar/Wind Harmer
0.122
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.388
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.121
20636128O CRK C2
Adder
1.69
207459AE1-142 C O1
Solar/Wind Harmer
0.274
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20714828MDF_W3-079
Solar/Wind Harmer
0.078
20641628MLH_W1-032
Solar/Wind Harmer
0.073
217197RE CRAN C
Solar/Wind Harmer
0.135
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.196
924131AB2-057 GEN
Solar/Wind Harmer
0.252
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.719
20635128RRCT3&4
Adder
2.371
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
20675428EAM_W2-061
Solar/Wind Harmer
0.045
223401AF1-299 GEN
Solar/Wind Helper
0.272
223402AF1-300 C
Solar/Wind Helper
0.272
972275AH1-722 GEN
Adder
7.525
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.302
208909MACR G3
Adder
32.158
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
VTFLTFEXP_VFT->PJM
CMTX
31.565
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.608
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.956
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.616
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.439
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.039
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for COOPER-GRACETON 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:BGE/PECO
Facility Description:
COOPER-GRACETON 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.49 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:627.1
MW Contribution:
1.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.548
231919CHRIST1
Adder
1.859
213515CONOW3-4
50/50
0.731
213516CONOW5-6
50/50
0.548
233935AB2-179 C
Solar/Wind Harmer
1.145
213497CHSTR7-9
Adder
1.06
233933AB2-153 GEN
Solar/Wind Harmer
0.456
232422X3-066 FULL
Solar/Wind Harmer
0.099
213958STHWK5-6
Adder
0.976
232417X3-008 C
Solar/Wind Harmer
0.411
233987AB2-037 GEN
Solar/Wind Harmer
4.137
233964AF2-378 GEN
Solar/Wind Harmer
0.046
232907VN8
Adder
10.819
233950AC2-186 GEN
Solar/Wind Harmer
0.202
233923SMA
Solar/Wind Harmer
1.306
233997TMININ_4.2
Solar/Wind Harmer
0.356
232406W1-004 FULL
Solar/Wind Harmer
0.357
232914OH NUG3
Adder
3.153
232916OH NUG5
Adder
3.153
232921TASLEY2G
Adder
1.843
232434Z2-077 GEN
Solar/Wind Harmer
0.089
213560DLW11-12
Adder
0.898
233973AC2-185 C
Solar/Wind Harmer
1.848
970695AG2-447 GEN
Solar/Wind Harmer
1.222
233939AC1-091 C
Solar/Wind Harmer
0.915
233972AC1-094 C
Solar/Wind Harmer
0.734
213815MOSER1-3
Adder
1.08
219914AD2-027 C
Solar/Wind Harmer
0.181
219921AF1-264
Solar/Wind Harmer
0.043
219623KINSLEYBEA C
Solar/Wind Harmer
0.128
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.055
228711V2-041C
Solar/Wind Harmer
0.172
219221BRL12CT1
Adder
2.568
219223BRL12CT3
Adder
2.568
219688LUMSOLAR_S C
Solar/Wind Harmer
0.058
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.05
959561AF2-247 GEN
Solar/Wind Harmer
0.135
219114HARTZY_C
Solar/Wind Harmer
0.224
219727YARDVSOLFA C
Solar/Wind Harmer
0.242
20716428NHV_W2-082
Solar/Wind Harmer
0.468
20715728PEM_W1-119
Solar/Wind Harmer
0.14
20636028O CRK C1
Adder
1.823
20714928UPF_X1-085
Solar/Wind Harmer
0.105
963391AG1-188 GEN
Solar/Wind Harmer
0.964
971667AH1-334 GEN
Solar/Wind Harmer
0.703
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.247
219612MATRIX C
Solar/Wind Harmer
0.045
20716928W4-060COL
Solar/Wind Harmer
0.172
20635828PARLN1&2
Adder
0.803
20635928PARLN3&4
Adder
0.803
217213AMBOY SO C
Solar/Wind Harmer
0.03
208835TUHI V3-051
Solar/Wind Helper
0.01
231920CHRIST2
Adder
1.818
233915AB1-141 GEN
Solar/Wind Harmer
0.402
233968AD2-076_GEN
Solar/Wind Harmer
2.624
970597AG2-380 GEN
Solar/Wind Harmer
1.648
231906DC3 NUG
Adder
5.458
231902DC CT7
Adder
4.364
231907DC10
Adder
1.363
213942SCHUYLKILL
Adder
1.288
213942SCHUYLKILL
Adder
0.985
213957STHWK3-4
Adder
0.976
213957STHWK3-4
Adder
0.976
232813VAUGHN
Adder
0.216
233955AB2-172 GEN
Solar/Wind Harmer
1.825
233940AF2-379 C
Solar/Wind Harmer
0.067
971195AH1-057 GEN
Solar/Wind Harmer
0.349
233901CHERRYDALE C
Solar/Wind Harmer
0.402
232912OH NUG1
Adder
3.153
232913OH NUG2
Adder
3.111
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.12
232904IR4
Adder
28.628
213561DLWR9-10
Adder
1.175
213561DLWR9-10
Adder
0.898
219137THOSOLAR C
Solar/Wind Harmer
0.37
219258KINSLEYDEP C
Solar/Wind Harmer
0.098
964001AG1-254 GEN
Solar/Wind Harmer
2.156
230434AG1-499 GEN
Solar/Wind Harmer
0.171
972141AH1-641 GEN
Solar/Wind Harmer
0.845
230430AE1-229_GEN
Solar/Wind Harmer
8.401
219615MILLCREEK C
Solar/Wind Harmer
0.07
228728W1-130C
Solar/Wind Harmer
0.192
230407AD2-065 C
Solar/Wind Harmer
0.038
970453AG2-297 GEN
Solar/Wind Harmer
0.788
219610FLORENCE C
Solar/Wind Harmer
0.398
219224BRL12CT4
Adder
2.568
230422AE1-104_GEN1
Solar/Wind Harmer
9.553
230425AE1-104_GEN2
Solar/Wind Harmer
9.553
227927V4-067C
Solar/Wind Harmer
0.056
213611FALLS1-3
Adder
0.999
213611FALLS1-3
Adder
0.999
20720728JCB_W1-129
Solar/Wind Harmer
0.079
20715028HAN_X4-015
Solar/Wind Harmer
0.079
207487AE2-000G4
Solar/Wind Harmer
8.126
207497AE2-000G2
Solar/Wind Harmer
8.126
207500AE2-000G1
Solar/Wind Harmer
8.126
207507AE2-000G3
Solar/Wind Harmer
8.126
971189AH1-054 GEN
Solar/Wind Harmer
0.305
963401AG1-189 GEN
Solar/Wind Harmer
0.585
970025AG2-016 GEN
Solar/Wind Harmer
0.729
207445AB1-138_GEN
Solar/Wind Harmer
0.148
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.306
20720628TIN_W1-124
Solar/Wind Harmer
0.246
20716228APLW2-078
Solar/Wind Harmer
0.218
971521AH1-258 GEN
Solar/Wind Harmer
0.663
20635928PARLN3&4
Adder
1.774
20675528CPH_W2-050
Solar/Wind Harmer
0.137
218526CNTRALGAS2 C
Solar/Wind Harmer
0.088
20673828FLE_V3-070
Solar/Wind Harmer
0.11
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213516CONOW5-6
50/50
0.731
213517CONOW7
50/50
0.731
213589EDDYSTN4
Adder
31.045
213587EDDYSTN3
Adder
31.018
233982AB2-133 GEN
Solar/Wind Harmer
1.981
233930AB2-032 GEN
Solar/Wind Harmer
0.338
232436AB1-176 C
Solar/Wind Harmer
0.091
234014AF1-036_GEN
Solar/Wind Harmer
1.071
232424Y1-079 C
Solar/Wind Harmer
0.218
233984AB2-036 GEN
Solar/Wind Harmer
4.803
232910NRG_G1
Adder
3.201
234041AC1-190 GEN
Solar/Wind Harmer
3.267
234036AF2-325 C
Solar/Wind Harmer
0.333
233946AB2-136 GEN
Solar/Wind Harmer
1.448
233952AC2-187 GEN
Solar/Wind Harmer
0.404
233954AC2-188 GEN
Solar/Wind Harmer
0.404
233994AC2-023 GEN
Solar/Wind Harmer
0.963
232428Y3-058 C
Solar/Wind Harmer
0.299
234015AF2-250 C
Solar/Wind Harmer
0.043
232926CRISFLD1
Adder
0.702
232410W1-006 C
Solar/Wind Harmer
0.357
232918OH NUG7
Adder
3.132
232905CHERITON_25
Adder
0.876
231940T-011
Adder
0.266
232899W1-062
Adder
3.349
233971AC1-093 C
Solar/Wind Harmer
0.868
972233AH1-701 GEN
Adder
1.272
213815MOSER1-3
Adder
1.08
213815MOSER1-3
Adder
1.08
219904AC1-010 C
Solar/Wind Harmer
0.114
219912AD2-042 GEN
Solar/Wind Harmer
0.24
228307PCLP GT
Adder
3.641
228351V2-046C
Solar/Wind Harmer
0.596
230511AF1-262
Solar/Wind Harmer
0.053
228201CARL#2CT
Adder
2
228200CARL#1CT
Adder
1.903
228251CARLLS#4
Adder
0.184
219906AC1-017 C
Solar/Wind Harmer
0.065
230433AD2-135 GEN
Solar/Wind Harmer
0.029
213535CROYDN11
Adder
2.957
219272CLEANLIGHT C
Solar/Wind Harmer
0.052
219607WPEMNERT C
Solar/Wind Harmer
0.12
219304NAMERICA C
Solar/Wind Harmer
0.089
219287REEVESEAST C
Solar/Wind Harmer
0.382
228754AB1-001 C
Solar/Wind Harmer
0.039
214067T20SOLAR
Solar/Wind Harmer
0.071
20720828JCB_W4-025
Solar/Wind Harmer
0.119
20636128O CRK C2
Adder
1.662
207459AE1-142 C O1
Solar/Wind Harmer
0.269
20628028LAKEHURS
Adder
0.243
219817TRENTONSOL C
Solar/Wind Harmer
0.28
20714828MDF_W3-079
Solar/Wind Harmer
0.077
20641628MLH_W1-032
Solar/Wind Harmer
0.072
217197RE CRAN C
Solar/Wind Harmer
0.133
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.192
924131AB2-057 GEN
Solar/Wind Harmer
0.248
20635028RRCT1&2
Adder
2.766
20635128RRCT3&4
Adder
2.67
20635128RRCT3&4
Adder
2.329
223401AF1-299 GEN
Solar/Wind Helper
0.284
223402AF1-300 C
Solar/Wind Helper
0.284
213514CONOW1-2
50/50
0.731
213515CONOW3-4
50/50
0.731
231918WEST 1
Adder
1.427
231917EM10
Adder
0.996
213497CHSTR7-9
Adder
1.06
213497CHSTR7-9
Adder
1.06
233918AB1-142 GEN
Solar/Wind Harmer
0.402
233944AB2-135 GEN
Solar/Wind Harmer
2.094
234012AE2-112_GEN
Solar/Wind Harmer
0.91
213958STHWK5-6
Adder
0.976
232902EASTMUNI
Adder
4.895
232426Y1-080 FULL
Solar/Wind Harmer
0.069
232919VN10
Adder
1.013
233996TM1833_GEN
Solar/Wind Harmer
0.356
233998TM1NIN_3.36
Solar/Wind Harmer
0.356
232404W1-003 C
Solar/Wind Harmer
0.357
232408W1-005 C
Solar/Wind Harmer
0.357
232917OH NUG6
Adder
3.139
232915OH NUG4
Adder
3.132
234033AF1-007_GEN
Solar/Wind Harmer
13.17
972177AH1-672 GEN
Solar/Wind Harmer
4.75
213560DLW11-12
Adder
0.898
232900DEMECSMY
Adder
3.212
232901NORTHST
Adder
2.861
233970AC1-092 C
Solar/Wind Harmer
0.915
228400MICK 1CT
Adder
3.589
219766PARADISE C
Solar/Wind Harmer
0.095
219907AC1-030 C
Solar/Wind Harmer
0.041
970997AG2-616 GEN
Solar/Wind Harmer
2.818
228260V4-054C
Solar/Wind Harmer
0.299
228206SHRMN CT
Adder
4.758
219348LDSOLAR C
Solar/Wind Harmer
0.172
219222BRL12CT2
Adder
2.568
228732V1-021 C
Adder
0.054
972251AH1-710 GEN
Adder
13.604
219686LUMSOLAR_N C
Solar/Wind Harmer
0.057
228729W2-030 C
Solar/Wind Harmer
0.163
214194N WALES4
Adder
0.241
213611FALLS1-3
Adder
0.999
20716028EGP_W2-019
Solar/Wind Harmer
0.122
207522AF2-254 C
Solar/Wind Harmer
0.378
20717128DIX_Z2-102
Solar/Wind Harmer
0.347
20715828PEM_W1-120
Solar/Wind Harmer
0.14
219276PARKLANDSO C
Solar/Wind Harmer
0.12
963711AG1-223 GEN
Solar/Wind Harmer
0.373
20714528FRN_Y2-051
Solar/Wind Harmer
0.074
219680HOPEWELLV C1
Solar/Wind Harmer
0.019
20715228NPK_W1-113
Solar/Wind Harmer
0.106
20720528MAN_W1-024
Solar/Wind Harmer
0.062
20720428HOL_W1-112
Solar/Wind Harmer
0.084
20635828PARLN1&2
Adder
1.774
20635028RRCT1&2
Adder
2.809
218524CNTRALGAS1 C
Solar/Wind Harmer
0.087
218440SUMMTASSOC C
Solar/Wind Harmer
0.03
218428ETC SOLAR C
Solar/Wind Harmer
0.008
219908AB1-139 C
Solar/Wind Harmer
0.09
219919AE1-041 FULL
Solar/Wind Harmer
0.01
208909MACR G3
Adder
31.435
208835TUHI V3-051
Solar/Wind Helper
0.01
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.015
VTFLTFEXP_VFT->PJM
CMTX
30.969
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.819
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.553
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.863
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.215
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.757
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for COOPER-GRACETON 230.0 kV Ckt 1 line l/o PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:BGE/PECO
Facility Description:
COOPER-GRACETON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.86 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:594.52
MW Contribution:
1.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.553
231919CHRIST1
Adder
1.889
231920CHRIST2
Adder
1.847
233915AB1-141 GEN
Solar/Wind Harmer
0.408
233968AD2-076_GEN
Solar/Wind Harmer
2.668
970597AG2-380 GEN
Solar/Wind Harmer
1.675
231906DC3 NUG
Adder
5.55
231902DC CT7
Adder
4.437
231907DC10
Adder
1.386
213942SCHUYLKILL
Adder
1.31
213942SCHUYLKILL
Adder
1.002
213957STHWK3-4
Adder
0.993
213957STHWK3-4
Adder
0.993
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.857
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.355
233901CHERRYDALE C
Solar/Wind Harmer
0.409
232912OH NUG1
Adder
3.21
232913OH NUG2
Adder
3.167
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.14
232904IR4
Adder
29.142
213561DLWR9-10
Adder
1.197
213561DLWR9-10
Adder
0.915
219137THOSOLAR C
Solar/Wind Harmer
0.377
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.199
230434AG1-499 GEN
Solar/Wind Harmer
0.175
972141AH1-641 GEN
Solar/Wind Harmer
0.862
230430AE1-229_GEN
Solar/Wind Harmer
8.569
219615MILLCREEK C
Solar/Wind Harmer
0.071
228728W1-130C
Solar/Wind Harmer
0.196
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.804
219610FLORENCE C
Solar/Wind Harmer
0.407
219224BRL12CT4
Adder
2.621
230422AE1-104_GEN1
Solar/Wind Harmer
9.749
230425AE1-104_GEN2
Solar/Wind Harmer
9.749
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.02
213611FALLS1-3
Adder
1.02
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
207487AE2-000G4
Solar/Wind Harmer
8.308
207497AE2-000G2
Solar/Wind Harmer
8.308
207500AE2-000G1
Solar/Wind Harmer
8.308
207507AE2-000G3
Solar/Wind Harmer
8.308
971189AH1-054 GEN
Solar/Wind Harmer
0.311
963401AG1-189 GEN
Solar/Wind Harmer
0.598
970025AG2-016 GEN
Solar/Wind Harmer
0.745
207445AB1-138_GEN
Solar/Wind Harmer
0.151
213508CON10-11
50/50
0.999
213508CON10-11
50/50
0.999
213518CONOW8-9
50/50
0.999
213518CONOW8-9
50/50
0.999
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.555
213587EDDYSTN3
Adder
31.528
233982AB2-133 GEN
Solar/Wind Harmer
2.013
233930AB2-032 GEN
Solar/Wind Harmer
0.344
232436AB1-176 C
Solar/Wind Harmer
0.093
234014AF1-036_GEN
Solar/Wind Harmer
1.089
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.885
232910NRG_G1
Adder
3.257
234041AC1-190 GEN
Solar/Wind Harmer
3.324
234036AF2-325 C
Solar/Wind Harmer
0.339
233946AB2-136 GEN
Solar/Wind Harmer
1.474
233952AC2-187 GEN
Solar/Wind Harmer
0.411
233954AC2-188 GEN
Solar/Wind Harmer
0.411
233994AC2-023 GEN
Solar/Wind Harmer
0.98
232428Y3-058 C
Solar/Wind Harmer
0.304
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.714
232410W1-006 C
Solar/Wind Harmer
0.363
232905CHERITON_25
Adder
0.892
232918OH NUG7
Adder
3.188
231940T-011
Adder
0.271
232899W1-062
Adder
3.409
233971AC1-093 C
Solar/Wind Harmer
0.884
972233AH1-701 GEN
Adder
1.297
213815MOSER1-3
Adder
1.102
213815MOSER1-3
Adder
1.102
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.245
228307PCLP GT
Adder
3.713
228351V2-046C
Solar/Wind Harmer
0.608
230511AF1-262
Solar/Wind Harmer
0.055
228201CARL#2CT
Adder
2.041
228200CARL#1CT
Adder
1.941
228251CARLLS#4
Adder
0.187
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
213535CROYDN11
Adder
3.018
219272CLEANLIGHT C
Solar/Wind Harmer
0.054
219607WPEMNERT C
Solar/Wind Harmer
0.123
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.39
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.122
20636128O CRK C2
Adder
1.7
207459AE1-142 C O1
Solar/Wind Harmer
0.276
20628028LAKEHURS
Adder
0.248
219817TRENTONSOL C
Solar/Wind Harmer
0.287
20714828MDF_W3-079
Solar/Wind Harmer
0.079
20641628MLH_W1-032
Solar/Wind Harmer
0.074
217197RE CRAN C
Solar/Wind Harmer
0.136
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.197
924131AB2-057 GEN
Solar/Wind Harmer
0.254
20635028RRCT1&2
Adder
2.834
20635128RRCT3&4
Adder
2.736
20635128RRCT3&4
Adder
2.386
218418LINDEN_G5
Adder
4.119
218419LINDEN_G6
Adder
4.119
972260AH1-715 GEN1
Adder
3.299
20675428EAM_W2-061
Solar/Wind Harmer
0.045
219036LINDEN_G7
Adder
3.972
219035LINDEN_G8
Adder
3.916
972261AH1-715 GEN2
Adder
3.803
223401AF1-299 GEN
Solar/Wind Helper
0.271
223402AF1-300 C
Solar/Wind Helper
0.271
219620RIDERU C
Solar/Wind Harmer
0.015
20714428HOW_X1-037
Solar/Wind Harmer
0.313
20720628TIN_W1-124
Solar/Wind Harmer
0.252
20716228APLW2-078
Solar/Wind Harmer
0.223
971521AH1-258 GEN
Solar/Wind Harmer
0.679
20635928PARLN3&4
Adder
1.817
20675528CPH_W2-050
Solar/Wind Harmer
0.141
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.113
20676128MHD_W3-029
Solar/Wind Harmer
0.114
20676428JCR_X2-075
Solar/Wind Harmer
0.081
218449LINSOLAR C
Solar/Wind Harmer
0.239
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.553
233935AB2-179 C
Solar/Wind Harmer
1.163
213497CHSTR7-9
Adder
1.078
233933AB2-153 GEN
Solar/Wind Harmer
0.464
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.993
232417X3-008 C
Solar/Wind Harmer
0.418
233987AB2-037 GEN
Solar/Wind Harmer
4.21
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
11.01
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.33
233997TMININ_4.2
Solar/Wind Harmer
0.363
232406W1-004 FULL
Solar/Wind Harmer
0.363
232921TASLEY2G
Adder
1.876
232914OH NUG3
Adder
3.21
232916OH NUG5
Adder
3.21
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.915
233973AC2-185 C
Solar/Wind Harmer
1.882
970695AG2-447 GEN
Solar/Wind Harmer
1.245
233939AC1-091 C
Solar/Wind Harmer
0.931
233972AC1-094 C
Solar/Wind Harmer
0.748
213815MOSER1-3
Adder
1.102
219914AD2-027 C
Solar/Wind Harmer
0.185
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.131
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.176
219221BRL12CT1
Adder
2.621
219223BRL12CT3
Adder
2.621
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.018
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.228
219727YARDVSOLFA C
Solar/Wind Harmer
0.247
20716428NHV_W2-082
Solar/Wind Harmer
0.478
20715728PEM_W1-119
Solar/Wind Harmer
0.143
20636028O CRK C1
Adder
1.864
20714928UPF_X1-085
Solar/Wind Harmer
0.108
963391AG1-188 GEN
Solar/Wind Harmer
0.985
971667AH1-334 GEN
Solar/Wind Harmer
0.719
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.252
219612MATRIX C
Solar/Wind Harmer
0.047
20716928W4-060COL
Solar/Wind Harmer
0.176
20635828PARLN1&2
Adder
0.823
20635928PARLN3&4
Adder
0.823
217213AMBOY SO C
Solar/Wind Harmer
0.031
219249CENTRALDIV C
Solar/Wind Harmer
0.01
207442AE1-156 GEN
Solar/Wind Harmer
0.178
20673728F2S_V4-070
Solar/Wind Harmer
0.043
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.45
231917EM10
Adder
1.012
213497CHSTR7-9
Adder
1.078
213497CHSTR7-9
Adder
1.078
233918AB1-142 GEN
Solar/Wind Harmer
0.408
233944AB2-135 GEN
Solar/Wind Harmer
2.129
234012AE2-112_GEN
Solar/Wind Harmer
0.926
213958STHWK5-6
Adder
0.993
232902EASTMUNI
Adder
4.98
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.031
233996TM1833_GEN
Solar/Wind Harmer
0.363
233998TM1NIN_3.36
Solar/Wind Harmer
0.363
232404W1-003 C
Solar/Wind Harmer
0.363
232408W1-005 C
Solar/Wind Harmer
0.363
232917OH NUG6
Adder
3.196
232915OH NUG4
Adder
3.188
234033AF1-007_GEN
Solar/Wind Harmer
13.406
972177AH1-672 GEN
Solar/Wind Harmer
4.835
213560DLW11-12
Adder
0.915
232900DEMECSMY
Adder
3.27
232901NORTHST
Adder
2.913
233970AC1-092 C
Solar/Wind Harmer
0.931
228400MICK 1CT
Adder
3.659
219766PARADISE C
Solar/Wind Harmer
0.097
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.874
228260V4-054C
Solar/Wind Harmer
0.305
228206SHRMN CT
Adder
4.855
219348LDSOLAR C
Solar/Wind Harmer
0.176
219222BRL12CT2
Adder
2.621
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.879
219686LUMSOLAR_N C
Solar/Wind Harmer
0.059
228729W2-030 C
Solar/Wind Harmer
0.166
214194N WALES4
Adder
0.246
213611FALLS1-3
Adder
1.02
20716028EGP_W2-019
Solar/Wind Harmer
0.125
207522AF2-254 C
Solar/Wind Harmer
0.386
20717128DIX_Z2-102
Solar/Wind Harmer
0.354
20715828PEM_W1-120
Solar/Wind Harmer
0.143
219276PARKLANDSO C
Solar/Wind Harmer
0.123
963711AG1-223 GEN
Solar/Wind Harmer
0.381
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.817
20635028RRCT1&2
Adder
2.878
218524CNTRALGAS1 C
Solar/Wind Harmer
0.09
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.092
219919AE1-041 FULL
Solar/Wind Harmer
0.01
972275AH1-722 GEN
Adder
7.573
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.304
208909MACR G3
Adder
32.417
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.015
VTFLTFEXP_VFT->PJM
CMTX
31.773
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.822
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.872
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.56
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.517
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.197
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line l/o DPL_P4_2_DPEM237_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DP&L/PECO
Facility Description:
EDGEMR 5-LINWOOD85 230.0 kV Ckt 1 line
Contingency Name:
DPL_P4_2_DPEM237_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.9 %
Rating:809.0 MVA
Rating Type:B
MVA to Mitigate:840.56
MW Contribution:
1.88
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
231900EM5
50/50
11.568
231908HR1
50/50
1.808
231910HR3
50/50
1.808
232416X2-083
50/50
0.027
231909HR2
50/50
1.381
233930AB2-032 GEN
Solar/Wind Harmer
0.561
233984AB2-036 GEN
Solar/Wind Harmer
8.373
234014AF1-036_GEN
Solar/Wind Harmer
1.819
232424Y1-079 C
Solar/Wind Harmer
0.377
232436AB1-176 C
Solar/Wind Harmer
0.153
233982AB2-133 GEN
Solar/Wind Harmer
3.237
234041AC1-190 GEN
Solar/Wind Harmer
5.741
234036AF2-325 C
Solar/Wind Harmer
0.586
233946AB2-136 GEN
Solar/Wind Harmer
2.542
233994AC2-023 GEN
Solar/Wind Harmer
1.674
232428Y3-058 C
Solar/Wind Harmer
0.518
232926CRISFLD1
Adder
1.218
234015AF2-250 C
Solar/Wind Harmer
0.074
232410W1-006 C
Solar/Wind Harmer
0.618
232905CHERITON_25
Adder
1.516
232918OH NUG7
Adder
5.422
231940T-011
Adder
0.455
232910NRG_G1
Adder
5.191
233952AC2-187 GEN
Solar/Wind Harmer
0.668
233954AC2-188 GEN
Solar/Wind Harmer
0.668
232899W1-062
Adder
5.275
233971AC1-093 C
Solar/Wind Harmer
1.336
231901EM4
50/50
2.517
231919CHRIST1
50/50
5.451
231920CHRIST2
50/50
5.33
231916EM3
50/50
0.949
231906DC3 NUG
50/50
10.582
231902DC CT7
50/50
8.46
231907DC10
50/50
2.642
233915AB1-141 GEN
Solar/Wind Harmer
0.666
233968AD2-076_GEN
Solar/Wind Harmer
4.456
970597AG2-380 GEN
Solar/Wind Harmer
2.798
233955AB2-172 GEN
Solar/Wind Harmer
3.208
233940AF2-379 C
Solar/Wind Harmer
0.116
971195AH1-057 GEN
Solar/Wind Harmer
0.603
233901CHERRYDALE C
Solar/Wind Harmer
0.695
232912OH NUG1
Adder
5.459
232913OH NUG2
Adder
5.386
232432Z2-076 GEN
Solar/Wind Harmer
0.08
232920IR10
Adder
1.907
232904IR4
Adder
48.682
232813VAUGHN
Adder
0.352
231918WEST 1
50/50
3.526
231917EM10
50/50
2.423
233918AB1-142 GEN
Solar/Wind Harmer
0.666
234012AE2-112_GEN
Solar/Wind Harmer
1.546
232902EASTMUNI
Adder
8.664
233944AB2-135 GEN
Solar/Wind Harmer
3.417
232426Y1-080 FULL
Solar/Wind Harmer
0.121
232919VN10
Adder
1.777
233996TM1833_GEN
Solar/Wind Harmer
0.619
233998TM1NIN_3.36
Solar/Wind Harmer
0.619
232404W1-003 C
Solar/Wind Harmer
0.618
232408W1-005 C
Solar/Wind Harmer
0.618
232917OH NUG6
Adder
5.434
232915OH NUG4
Adder
5.422
234033AF1-007_GEN
Solar/Wind Harmer
22.395
972177AH1-672 GEN
Solar/Wind Harmer
7.94
232901NORTHST
Adder
4.568
232900DEMECSMY
Adder
5.06
233970AC1-092 C
Solar/Wind Harmer
1.407
231131BLOOM ENRGY
50/50
0.184
231915DC CT6
50/50
0.446
233935AB2-179 C
Solar/Wind Harmer
1.735
233987AB2-037 GEN
Solar/Wind Harmer
7.791
233933AB2-153 GEN
Solar/Wind Harmer
0.757
232422X3-066 FULL
Solar/Wind Harmer
0.167
232417X3-008 C
Solar/Wind Harmer
0.722
233964AF2-378 GEN
Solar/Wind Harmer
0.081
232907VN8
Adder
19.133
233923SMA
Solar/Wind Harmer
2.268
233997TMININ_4.2
Solar/Wind Harmer
0.619
232406W1-004 FULL
Solar/Wind Harmer
0.618
232921TASLEY2G
Adder
3.191
232914OH NUG3
Adder
5.459
232916OH NUG5
Adder
5.459
232434Z2-077 GEN
Solar/Wind Harmer
0.152
233950AC2-186 GEN
Solar/Wind Harmer
0.334
233973AC2-185 C
Solar/Wind Harmer
2.843
970695AG2-447 GEN
Solar/Wind Harmer
1.881
233939AC1-091 C
Solar/Wind Harmer
1.407
233972AC1-094 C
Solar/Wind Harmer
1.13
NYPJM->LTFIMP_NY
CLTF
0.756
LGEELTFEXP_LGEE->PJM
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.025
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.9
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.32
MECLTFEXP_MEC->PJM
CLTF
0.118
SIGELTFEXP_SIGE->PJM
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.175
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.359
TVALTFEXP_TVA->PJM
CLTF
0.088
CPLELTFEXP_CPLE->PJM
CLTF
0.145
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.061

Details for LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line l/o PECO_P4_POST475_SRT-A/* $ DELCO $ PECO_P4_POST475 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_POST475_SRT-A/* $ DELCO $ PECO_P4_POST475 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.18 %
Rating:1770.0 MVA
Rating Type:B
MVA to Mitigate:1790.82
MW Contribution:
2.18
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213889PHLISCT2
50/50
6.731
231917EM10
50/50
4.426
231918WEST 1
50/50
5.544
233918AB1-142 GEN
Solar/Wind Harmer
0.793
234012AE2-112_GEN
Solar/Wind Harmer
1.83
232902EASTMUNI
Adder
10.144
233944AB2-135 GEN
Solar/Wind Harmer
4.063
232426Y1-080 FULL
Solar/Wind Harmer
0.141
232919VN10
Adder
2.068
233996TM1833_GEN
Solar/Wind Harmer
0.719
233998TM1NIN_3.36
Solar/Wind Harmer
0.719
232404W1-003 C
Solar/Wind Harmer
0.718
232408W1-005 C
Solar/Wind Harmer
0.718
232917OH NUG6
Adder
6.318
232915OH NUG4
Adder
6.303
234033AF1-007_GEN
Solar/Wind Harmer
26.022
972177AH1-672 GEN
Solar/Wind Harmer
9.232
232900DEMECSMY
Adder
5.885
232901NORTHST
Adder
5.296
233970AC1-092 C
Solar/Wind Harmer
1.632
972251AH1-710 GEN
Adder
10.86
219766PARADISE C
Solar/Wind Helper
0.031
219907AC1-030 C
Solar/Wind Helper
0.019
219348LDSOLAR C
Solar/Wind Helper
0.056
231900EM5
50/50
12.386
231909HR2
50/50
2.523
231908HR1
50/50
2.519
231910HR3
50/50
2.519
232416X2-083
50/50
0.033
233930AB2-032 GEN
Solar/Wind Harmer
0.667
234014AF1-036_GEN
Solar/Wind Harmer
2.153
233982AB2-133 GEN
Solar/Wind Harmer
3.858
233984AB2-036 GEN
Solar/Wind Harmer
9.854
232436AB1-176 C
Solar/Wind Harmer
0.181
232424Y1-079 C
Solar/Wind Harmer
0.444
234041AC1-190 GEN
Solar/Wind Harmer
6.692
234036AF2-325 C
Solar/Wind Harmer
0.682
233946AB2-136 GEN
Solar/Wind Harmer
2.962
233994AC2-023 GEN
Solar/Wind Harmer
1.947
232428Y3-058 C
Solar/Wind Harmer
0.603
232926CRISFLD1
Adder
1.416
234015AF2-250 C
Solar/Wind Harmer
0.086
232410W1-006 C
Solar/Wind Harmer
0.718
232905CHERITON_25
Adder
1.763
232918OH NUG7
Adder
6.303
231940T-011
Adder
0.529
232910NRG_G1
Adder
6.097
233952AC2-187 GEN
Solar/Wind Harmer
0.779
233954AC2-188 GEN
Solar/Wind Harmer
0.779
232899W1-062
Adder
6.136
233971AC1-093 C
Solar/Wind Harmer
1.55
219912AD2-042 GEN
Solar/Wind Helper
0.087
219904AC1-010 C
Solar/Wind Helper
0.035
219906AC1-017 C
Solar/Wind Helper
0.021
214067T20SOLAR
Solar/Wind Helper
0.006
219607WPEMNERT C
Solar/Wind Helper
0.039
219304NAMERICA C
Solar/Wind Helper
0.064
213893PHLISST1
50/50
9.742
231505HR4
50/50
5.296
231916EM3
50/50
1.734
231901EM4
50/50
3.507
231919CHRIST1
50/50
7.504
231920CHRIST2
50/50
7.337
231906DC3 NUG
50/50
13.196
231902DC CT7
50/50
10.55
231907DC10
50/50
3.294
233915AB1-141 GEN
Solar/Wind Harmer
0.793
233968AD2-076_GEN
Solar/Wind Harmer
5.274
970597AG2-380 GEN
Solar/Wind Harmer
3.312
233955AB2-172 GEN
Solar/Wind Harmer
3.74
233940AF2-379 C
Solar/Wind Harmer
0.135
971195AH1-057 GEN
Solar/Wind Harmer
0.701
233901CHERRYDALE C
Solar/Wind Harmer
0.808
232912OH NUG1
Adder
6.346
232913OH NUG2
Adder
6.261
232432Z2-076 GEN
Solar/Wind Harmer
0.093
232920IR10
Adder
2.216
232813VAUGHN
Adder
0.413
232904IR4
Adder
56.566
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219615MILLCREEK C
Solar/Wind Helper
0.014
213890PHLISCT3
50/50
6.753
213888PHLISCT1
50/50
6.731
231131BLOOM ENRGY
50/50
0.231
231915DC CT6
50/50
0.557
233935AB2-179 C
Solar/Wind Harmer
2.12
233933AB2-153 GEN
Solar/Wind Harmer
0.901
233987AB2-037 GEN
Solar/Wind Harmer
9.044
232422X3-066 FULL
Solar/Wind Harmer
0.198
232417X3-008 C
Solar/Wind Harmer
0.842
233964AF2-378 GEN
Solar/Wind Harmer
0.095
232907VN8
Adder
22.251
233923SMA
Solar/Wind Harmer
2.637
233997TMININ_4.2
Solar/Wind Harmer
0.719
232406W1-004 FULL
Solar/Wind Harmer
0.718
232921TASLEY2G
Adder
3.709
232914OH NUG3
Adder
6.346
232916OH NUG5
Adder
6.346
232434Z2-077 GEN
Solar/Wind Harmer
0.176
233950AC2-186 GEN
Solar/Wind Harmer
0.39
233973AC2-185 C
Solar/Wind Harmer
3.298
970695AG2-447 GEN
Solar/Wind Harmer
2.181
233939AC1-091 C
Solar/Wind Harmer
1.632
233972AC1-094 C
Solar/Wind Harmer
1.311
219914AD2-027 C
Solar/Wind Helper
0.067
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219921AF1-264
Solar/Wind Helper
0.027
219623KINSLEYBEA C
Solar/Wind Helper
0.001
NYPJM->LTFIMP_NY
CLTF
1.198
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.201
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.127
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.237
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.738
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.086
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line l/o PECO_P4_POST785_SRT-A/* $ DELCO $ PECO_P4_POST785 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_POST785_SRT-A/* $ DELCO $ PECO_P4_POST785 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.17 %
Rating:1770.0 MVA
Rating Type:B
MVA to Mitigate:1790.79
MW Contribution:
2.18
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
231900EM5
50/50
12.386
231909HR2
50/50
2.523
231908HR1
50/50
2.519
231910HR3
50/50
2.519
232416X2-083
50/50
0.033
233930AB2-032 GEN
Solar/Wind Harmer
0.667
234014AF1-036_GEN
Solar/Wind Harmer
2.153
233982AB2-133 GEN
Solar/Wind Harmer
3.858
233984AB2-036 GEN
Solar/Wind Harmer
9.854
232436AB1-176 C
Solar/Wind Harmer
0.181
232424Y1-079 C
Solar/Wind Harmer
0.444
213893PHLISST1
50/50
9.742
231505HR4
50/50
5.296
231916EM3
50/50
1.734
231901EM4
50/50
3.507
231919CHRIST1
50/50
7.504
231920CHRIST2
50/50
7.337
231906DC3 NUG
50/50
13.196
231902DC CT7
50/50
10.55
231907DC10
50/50
3.294
233915AB1-141 GEN
Solar/Wind Harmer
0.793
233968AD2-076_GEN
Solar/Wind Harmer
5.274
970597AG2-380 GEN
Solar/Wind Harmer
3.312
233955AB2-172 GEN
Solar/Wind Harmer
3.74
233940AF2-379 C
Solar/Wind Harmer
0.135
971195AH1-057 GEN
Solar/Wind Harmer
0.701
233901CHERRYDALE C
Solar/Wind Harmer
0.808
232912OH NUG1
Adder
6.346
232913OH NUG2
Adder
6.261
232432Z2-076 GEN
Solar/Wind Harmer
0.093
232920IR10
Adder
2.216
232813VAUGHN
Adder
0.413
232904IR4
Adder
56.566
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219615MILLCREEK C
Solar/Wind Helper
0.014
234041AC1-190 GEN
Solar/Wind Harmer
6.692
234036AF2-325 C
Solar/Wind Harmer
0.682
233946AB2-136 GEN
Solar/Wind Harmer
2.962
233994AC2-023 GEN
Solar/Wind Harmer
1.947
232428Y3-058 C
Solar/Wind Harmer
0.603
232926CRISFLD1
Adder
1.416
234015AF2-250 C
Solar/Wind Harmer
0.086
232410W1-006 C
Solar/Wind Harmer
0.718
232905CHERITON_25
Adder
1.763
232918OH NUG7
Adder
6.303
231940T-011
Adder
0.529
232910NRG_G1
Adder
6.097
233952AC2-187 GEN
Solar/Wind Harmer
0.779
233954AC2-188 GEN
Solar/Wind Harmer
0.779
232899W1-062
Adder
6.136
233971AC1-093 C
Solar/Wind Harmer
1.55
219912AD2-042 GEN
Solar/Wind Helper
0.087
219904AC1-010 C
Solar/Wind Helper
0.035
219906AC1-017 C
Solar/Wind Helper
0.021
214067T20SOLAR
Solar/Wind Helper
0.006
219607WPEMNERT C
Solar/Wind Helper
0.039
219304NAMERICA C
Solar/Wind Helper
0.064
213889PHLISCT2
50/50
6.731
231917EM10
50/50
4.426
231918WEST 1
50/50
5.544
233918AB1-142 GEN
Solar/Wind Harmer
0.793
234012AE2-112_GEN
Solar/Wind Harmer
1.83
232902EASTMUNI
Adder
10.144
233944AB2-135 GEN
Solar/Wind Harmer
4.063
232426Y1-080 FULL
Solar/Wind Harmer
0.141
232919VN10
Adder
2.068
233996TM1833_GEN
Solar/Wind Harmer
0.719
233998TM1NIN_3.36
Solar/Wind Harmer
0.719
232404W1-003 C
Solar/Wind Harmer
0.718
232408W1-005 C
Solar/Wind Harmer
0.718
232917OH NUG6
Adder
6.318
232915OH NUG4
Adder
6.303
234033AF1-007_GEN
Solar/Wind Harmer
26.022
972177AH1-672 GEN
Solar/Wind Harmer
9.232
232900DEMECSMY
Adder
5.885
232901NORTHST
Adder
5.296
233970AC1-092 C
Solar/Wind Harmer
1.632
972251AH1-710 GEN
Adder
10.86
219766PARADISE C
Solar/Wind Helper
0.031
219907AC1-030 C
Solar/Wind Helper
0.019
219348LDSOLAR C
Solar/Wind Helper
0.056
213890PHLISCT3
50/50
6.753
213888PHLISCT1
50/50
6.731
231131BLOOM ENRGY
50/50
0.231
231915DC CT6
50/50
0.557
233935AB2-179 C
Solar/Wind Harmer
2.12
233933AB2-153 GEN
Solar/Wind Harmer
0.901
233987AB2-037 GEN
Solar/Wind Harmer
9.044
232422X3-066 FULL
Solar/Wind Harmer
0.198
232417X3-008 C
Solar/Wind Harmer
0.842
233964AF2-378 GEN
Solar/Wind Harmer
0.095
232907VN8
Adder
22.251
233923SMA
Solar/Wind Harmer
2.637
233997TMININ_4.2
Solar/Wind Harmer
0.719
232406W1-004 FULL
Solar/Wind Harmer
0.718
232921TASLEY2G
Adder
3.709
232914OH NUG3
Adder
6.346
232916OH NUG5
Adder
6.346
232434Z2-077 GEN
Solar/Wind Harmer
0.176
233950AC2-186 GEN
Solar/Wind Harmer
0.39
233973AC2-185 C
Solar/Wind Harmer
3.298
970695AG2-447 GEN
Solar/Wind Harmer
2.181
233939AC1-091 C
Solar/Wind Harmer
1.632
233972AC1-094 C
Solar/Wind Harmer
1.311
219914AD2-027 C
Solar/Wind Helper
0.067
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219921AF1-264
Solar/Wind Helper
0.027
219623KINSLEYBEA C
Solar/Wind Helper
0.001
NYPJM->LTFIMP_NY
CLTF
1.198
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.201
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.127
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.237
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.738
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.086
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for LINWOOD97-POST97 230.0 kV Ckt 1 line l/o PECO_CBO_CHIC435_SRT-A/* $ DELCO $ PECO_CBO_CHIC435 $ K


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
LINWOOD97-POST97 230.0 kV Ckt 1 line
Contingency Name:
PECO_CBO_CHIC435_SRT-A/* $ DELCO $ PECO_CBO_CHIC435 $ K
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.44 %
Rating:1770.0 MVA
Rating Type:B
MVA to Mitigate:1795.44
MW Contribution:
2.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213893PHLISST1
50/50
9.655
231505HR4
50/50
5.278
231916EM3
50/50
1.729
231901EM4
50/50
3.495
231919CHRIST1
50/50
7.479
231920CHRIST2
50/50
7.313
231906DC3 NUG
50/50
13.152
231902DC CT7
50/50
10.514
231907DC10
50/50
3.283
233915AB1-141 GEN
Solar/Wind Harmer
0.79
233968AD2-076_GEN
Solar/Wind Harmer
5.256
970597AG2-380 GEN
Solar/Wind Harmer
3.301
233955AB2-172 GEN
Solar/Wind Harmer
3.727
233940AF2-379 C
Solar/Wind Harmer
0.134
971195AH1-057 GEN
Solar/Wind Harmer
0.699
233901CHERRYDALE C
Solar/Wind Harmer
0.805
232912OH NUG1
Adder
6.323
232913OH NUG2
Adder
6.239
232432Z2-076 GEN
Solar/Wind Harmer
0.093
232920IR10
Adder
2.209
232813VAUGHN
Adder
0.411
232904IR4
Adder
56.366
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219615MILLCREEK C
Solar/Wind Helper
0.014
231900EM5
50/50
12.344
231909HR2
50/50
2.515
231908HR1
50/50
2.511
231910HR3
50/50
2.511
232416X2-083
50/50
0.033
233930AB2-032 GEN
Solar/Wind Harmer
0.665
234014AF1-036_GEN
Solar/Wind Harmer
2.145
233982AB2-133 GEN
Solar/Wind Harmer
3.845
233984AB2-036 GEN
Solar/Wind Harmer
9.819
232436AB1-176 C
Solar/Wind Harmer
0.181
232424Y1-079 C
Solar/Wind Harmer
0.442
234041AC1-190 GEN
Solar/Wind Harmer
6.669
234036AF2-325 C
Solar/Wind Harmer
0.68
233946AB2-136 GEN
Solar/Wind Harmer
2.951
233994AC2-023 GEN
Solar/Wind Harmer
1.94
232428Y3-058 C
Solar/Wind Harmer
0.6
232926CRISFLD1
Adder
1.411
234015AF2-250 C
Solar/Wind Harmer
0.086
232410W1-006 C
Solar/Wind Harmer
0.716
232905CHERITON_25
Adder
1.757
232918OH NUG7
Adder
6.281
231940T-011
Adder
0.527
232910NRG_G1
Adder
6.075
233952AC2-187 GEN
Solar/Wind Harmer
0.777
233954AC2-188 GEN
Solar/Wind Harmer
0.777
232899W1-062
Adder
6.114
233971AC1-093 C
Solar/Wind Harmer
1.544
219912AD2-042 GEN
Solar/Wind Helper
0.087
219904AC1-010 C
Solar/Wind Helper
0.035
219906AC1-017 C
Solar/Wind Helper
0.021
214067T20SOLAR
Solar/Wind Helper
0.006
219607WPEMNERT C
Solar/Wind Helper
0.039
219304NAMERICA C
Solar/Wind Helper
0.064
213889PHLISCT2
50/50
6.682
231917EM10
50/50
4.412
231918WEST 1
50/50
5.526
233918AB1-142 GEN
Solar/Wind Harmer
0.79
234012AE2-112_GEN
Solar/Wind Harmer
1.824
232902EASTMUNI
Adder
10.109
233944AB2-135 GEN
Solar/Wind Harmer
4.049
232426Y1-080 FULL
Solar/Wind Harmer
0.141
232919VN10
Adder
2.06
233996TM1833_GEN
Solar/Wind Harmer
0.717
233998TM1NIN_3.36
Solar/Wind Harmer
0.717
232404W1-003 C
Solar/Wind Harmer
0.716
232408W1-005 C
Solar/Wind Harmer
0.716
232917OH NUG6
Adder
6.295
232915OH NUG4
Adder
6.281
234033AF1-007_GEN
Solar/Wind Harmer
25.93
972177AH1-672 GEN
Solar/Wind Harmer
9.199
232900DEMECSMY
Adder
5.864
232901NORTHST
Adder
5.277
233970AC1-092 C
Solar/Wind Harmer
1.626
972251AH1-710 GEN
Adder
10.811
219766PARADISE C
Solar/Wind Helper
0.031
219907AC1-030 C
Solar/Wind Helper
0.019
219348LDSOLAR C
Solar/Wind Helper
0.056
213890PHLISCT3
50/50
6.693
213888PHLISCT1
50/50
6.682
231131BLOOM ENRGY
50/50
0.23
231915DC CT6
50/50
0.555
233935AB2-179 C
Solar/Wind Harmer
2.113
233933AB2-153 GEN
Solar/Wind Harmer
0.898
233987AB2-037 GEN
Solar/Wind Harmer
9.013
232422X3-066 FULL
Solar/Wind Harmer
0.197
232417X3-008 C
Solar/Wind Harmer
0.839
233964AF2-378 GEN
Solar/Wind Harmer
0.095
232907VN8
Adder
22.172
233923SMA
Solar/Wind Harmer
2.627
233997TMININ_4.2
Solar/Wind Harmer
0.717
232406W1-004 FULL
Solar/Wind Harmer
0.716
232921TASLEY2G
Adder
3.696
232914OH NUG3
Adder
6.323
232916OH NUG5
Adder
6.323
232434Z2-077 GEN
Solar/Wind Harmer
0.175
233950AC2-186 GEN
Solar/Wind Harmer
0.388
233973AC2-185 C
Solar/Wind Harmer
3.286
970695AG2-447 GEN
Solar/Wind Harmer
2.174
233939AC1-091 C
Solar/Wind Harmer
1.626
233972AC1-094 C
Solar/Wind Harmer
1.306
219914AD2-027 C
Solar/Wind Helper
0.067
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219921AF1-264
Solar/Wind Helper
0.027
219623KINSLEYBEA C
Solar/Wind Helper
0.001
NYPJM->LTFIMP_NY
CLTF
1.194
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.199
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.125
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.235
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.077
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.732
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.62 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:679.82
MW Contribution:
1.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233918AB1-142 GEN
Solar/Wind Harmer
0.407
233944AB2-135 GEN
Solar/Wind Harmer
2.12
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.99
232902EASTMUNI
Adder
4.959
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.027
233996TM1833_GEN
Solar/Wind Harmer
0.361
233998TM1NIN_3.36
Solar/Wind Harmer
0.361
232404W1-003 C
Solar/Wind Harmer
0.362
232408W1-005 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.175
234033AF1-007_GEN
Solar/Wind Harmer
13.348
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233970AC1-092 C
Solar/Wind Harmer
0.927
228400MICK 1CT
Adder
3.642
219766PARADISE C
Solar/Wind Harmer
0.096
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.86
228260V4-054C
Solar/Wind Harmer
0.303
228206SHRMN CT
Adder
4.831
219348LDSOLAR C
Solar/Wind Harmer
0.175
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.809
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
228729W2-030 C
Solar/Wind Harmer
0.165
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
20716028EGP_W2-019
Solar/Wind Harmer
0.124
207522AF2-254 C
Solar/Wind Harmer
0.384
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715828PEM_W1-120
Solar/Wind Harmer
0.142
219276PARKLANDSO C
Solar/Wind Harmer
0.122
963711AG1-223 GEN
Solar/Wind Harmer
0.379
213514CONOW1-2
50/50
0.552
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
233915AB1-141 GEN
Solar/Wind Harmer
0.407
233968AD2-076_GEN
Solar/Wind Harmer
2.658
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.42
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.849
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.353
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.135
232904IR4
Adder
29.017
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
219137THOSOLAR C
Solar/Wind Harmer
0.375
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.188
230434AG1-499 GEN
Solar/Wind Harmer
0.174
972141AH1-641 GEN
Solar/Wind Harmer
0.858
230430AE1-229_GEN
Solar/Wind Harmer
8.528
219615MILLCREEK C
Solar/Wind Harmer
0.071
228728W1-130C
Solar/Wind Harmer
0.195
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219224BRL12CT4
Adder
2.608
230422AE1-104_GEN1
Solar/Wind Harmer
9.701
230425AE1-104_GEN2
Solar/Wind Harmer
9.701
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
207487AE2-000G4
Solar/Wind Harmer
8.262
207497AE2-000G2
Solar/Wind Harmer
8.262
207500AE2-000G1
Solar/Wind Harmer
8.262
207507AE2-000G3
Solar/Wind Harmer
8.262
971189AH1-054 GEN
Solar/Wind Harmer
0.31
963401AG1-189 GEN
Solar/Wind Harmer
0.595
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207445AB1-138_GEN
Solar/Wind Harmer
0.15
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.311
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20716228APLW2-078
Solar/Wind Harmer
0.221
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.14
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.112
20676128MHD_W3-029
Solar/Wind Harmer
0.114
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.86
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
972275AH1-722 GEN
Adder
7.525
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.302
208909MACR G3
Adder
32.158
213508CON10-11
50/50
0.998
213508CON10-11
50/50
0.998
213518CONOW8-9
50/50
0.998
213518CONOW8-9
50/50
0.998
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.44
213587EDDYSTN3
Adder
31.412
233982AB2-133 GEN
Solar/Wind Harmer
2.006
233930AB2-032 GEN
Solar/Wind Harmer
0.342
232436AB1-176 C
Solar/Wind Harmer
0.092
234014AF1-036_GEN
Solar/Wind Harmer
1.085
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
232910NRG_G1
Adder
3.244
234041AC1-190 GEN
Solar/Wind Harmer
3.31
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.467
233952AC2-187 GEN
Solar/Wind Harmer
0.409
233954AC2-188 GEN
Solar/Wind Harmer
0.409
233994AC2-023 GEN
Solar/Wind Harmer
0.976
232428Y3-058 C
Solar/Wind Harmer
0.303
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.711
232410W1-006 C
Solar/Wind Harmer
0.362
232918OH NUG7
Adder
3.175
232905CHERITON_25
Adder
0.888
231940T-011
Adder
0.269
232899W1-062
Adder
3.395
233971AC1-093 C
Solar/Wind Harmer
0.88
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.244
228307PCLP GT
Adder
3.695
228351V2-046C
Solar/Wind Harmer
0.605
230511AF1-262
Solar/Wind Harmer
0.054
228201CARL#2CT
Adder
2.031
228200CARL#1CT
Adder
1.931
228251CARLLS#4
Adder
0.186
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
213535CROYDN11
Adder
3.003
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
219607WPEMNERT C
Solar/Wind Harmer
0.122
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.388
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.121
20636128O CRK C2
Adder
1.69
207459AE1-142 C O1
Solar/Wind Harmer
0.274
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20714828MDF_W3-079
Solar/Wind Harmer
0.078
20641628MLH_W1-032
Solar/Wind Harmer
0.073
217197RE CRAN C
Solar/Wind Harmer
0.135
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.196
924131AB2-057 GEN
Solar/Wind Harmer
0.252
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.719
20635128RRCT3&4
Adder
2.371
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
20675428EAM_W2-061
Solar/Wind Harmer
0.045
223401AF1-299 GEN
Solar/Wind Helper
0.272
223402AF1-300 C
Solar/Wind Helper
0.272
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.552
233935AB2-179 C
Solar/Wind Harmer
1.159
213497CHSTR7-9
Adder
1.074
233933AB2-153 GEN
Solar/Wind Harmer
0.462
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.416
233987AB2-037 GEN
Solar/Wind Harmer
4.192
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.964
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.324
233997TMININ_4.2
Solar/Wind Harmer
0.361
232406W1-004 FULL
Solar/Wind Harmer
0.362
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
232921TASLEY2G
Adder
1.868
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.873
970695AG2-447 GEN
Solar/Wind Harmer
1.239
233939AC1-091 C
Solar/Wind Harmer
0.927
233972AC1-094 C
Solar/Wind Harmer
0.745
213815MOSER1-3
Adder
1.097
219914AD2-027 C
Solar/Wind Harmer
0.184
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.227
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20716428NHV_W2-082
Solar/Wind Harmer
0.476
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20636028O CRK C1
Adder
1.854
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963391AG1-188 GEN
Solar/Wind Harmer
0.98
971667AH1-334 GEN
Solar/Wind Harmer
0.715
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.251
219612MATRIX C
Solar/Wind Harmer
0.046
20716928W4-060COL
Solar/Wind Harmer
0.175
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
217213AMBOY SO C
Solar/Wind Harmer
0.03
219249CENTRALDIV C
Solar/Wind Harmer
0.009
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20673728F2S_V4-070
Solar/Wind Harmer
0.043
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
VTFLTFEXP_VFT->PJM
CMTX
31.565
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.608
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.956
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.616
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.439
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.039
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.49 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:679.08
MW Contribution:
1.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.552
231919CHRIST1
Adder
1.883
231920CHRIST2
Adder
1.841
233915AB1-141 GEN
Solar/Wind Harmer
0.407
233968AD2-076_GEN
Solar/Wind Harmer
2.659
970597AG2-380 GEN
Solar/Wind Harmer
1.67
231906DC3 NUG
Adder
5.531
231902DC CT7
Adder
4.422
231907DC10
Adder
1.381
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.99
213957STHWK3-4
Adder
0.99
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.445
231917EM10
Adder
1.009
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233918AB1-142 GEN
Solar/Wind Harmer
0.407
233944AB2-135 GEN
Solar/Wind Harmer
2.121
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.99
232902EASTMUNI
Adder
4.962
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.028
233996TM1833_GEN
Solar/Wind Harmer
0.361
233998TM1NIN_3.36
Solar/Wind Harmer
0.361
232404W1-003 C
Solar/Wind Harmer
0.362
232408W1-005 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.184
232915OH NUG4
Adder
3.177
234033AF1-007_GEN
Solar/Wind Harmer
13.356
972177AH1-672 GEN
Solar/Wind Harmer
4.817
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.258
232901NORTHST
Adder
2.902
233970AC1-092 C
Solar/Wind Harmer
0.928
228400MICK 1CT
Adder
3.643
219766PARADISE C
Solar/Wind Harmer
0.096
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.861
228260V4-054C
Solar/Wind Harmer
0.303
228206SHRMN CT
Adder
4.833
219348LDSOLAR C
Solar/Wind Harmer
0.175
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.817
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
228729W2-030 C
Solar/Wind Harmer
0.165
214194N WALES4
Adder
0.245
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.85
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.353
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232912OH NUG1
Adder
3.198
232913OH NUG2
Adder
3.155
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.136
232904IR4
Adder
29.032
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
219137THOSOLAR C
Solar/Wind Harmer
0.376
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.189
230434AG1-499 GEN
Solar/Wind Harmer
0.174
972141AH1-641 GEN
Solar/Wind Harmer
0.858
230430AE1-229_GEN
Solar/Wind Harmer
8.531
219615MILLCREEK C
Solar/Wind Harmer
0.071
228728W1-130C
Solar/Wind Harmer
0.195
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219224BRL12CT4
Adder
2.608
230422AE1-104_GEN1
Solar/Wind Harmer
9.704
230425AE1-104_GEN2
Solar/Wind Harmer
9.704
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
207487AE2-000G4
Solar/Wind Harmer
8.265
207497AE2-000G2
Solar/Wind Harmer
8.265
207500AE2-000G1
Solar/Wind Harmer
8.265
207507AE2-000G3
Solar/Wind Harmer
8.265
971189AH1-054 GEN
Solar/Wind Harmer
0.31
963401AG1-189 GEN
Solar/Wind Harmer
0.595
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207445AB1-138_GEN
Solar/Wind Harmer
0.15
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.311
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20716228APLW2-078
Solar/Wind Harmer
0.222
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20635928PARLN3&4
Adder
1.807
20675528CPH_W2-050
Solar/Wind Harmer
0.14
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.112
20676128MHD_W3-029
Solar/Wind Harmer
0.114
213611FALLS1-3
Adder
1.015
20716028EGP_W2-019
Solar/Wind Harmer
0.124
207522AF2-254 C
Solar/Wind Harmer
0.384
20717128DIX_Z2-102
Solar/Wind Harmer
0.353
20715828PEM_W1-120
Solar/Wind Harmer
0.142
219276PARKLANDSO C
Solar/Wind Harmer
0.122
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.807
20635028RRCT1&2
Adder
2.861
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
972275AH1-722 GEN
Adder
7.526
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.302
208909MACR G3
Adder
32.163
213508CON10-11
50/50
0.998
213508CON10-11
50/50
0.998
213518CONOW8-9
50/50
0.998
213518CONOW8-9
50/50
0.998
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.446
213587EDDYSTN3
Adder
31.419
233982AB2-133 GEN
Solar/Wind Harmer
2.006
233930AB2-032 GEN
Solar/Wind Harmer
0.342
232436AB1-176 C
Solar/Wind Harmer
0.092
234014AF1-036_GEN
Solar/Wind Harmer
1.085
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.868
232910NRG_G1
Adder
3.245
234041AC1-190 GEN
Solar/Wind Harmer
3.312
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.468
233952AC2-187 GEN
Solar/Wind Harmer
0.409
233954AC2-188 GEN
Solar/Wind Harmer
0.409
233994AC2-023 GEN
Solar/Wind Harmer
0.976
232428Y3-058 C
Solar/Wind Harmer
0.303
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.712
232410W1-006 C
Solar/Wind Harmer
0.362
232918OH NUG7
Adder
3.177
232905CHERITON_25
Adder
0.888
231940T-011
Adder
0.27
232899W1-062
Adder
3.396
233971AC1-093 C
Solar/Wind Harmer
0.881
972233AH1-701 GEN
Adder
1.292
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.244
228307PCLP GT
Adder
3.696
228351V2-046C
Solar/Wind Harmer
0.605
230511AF1-262
Solar/Wind Harmer
0.054
228201CARL#2CT
Adder
2.032
228200CARL#1CT
Adder
1.932
228251CARLLS#4
Adder
0.186
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
213535CROYDN11
Adder
3.004
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
219607WPEMNERT C
Solar/Wind Harmer
0.122
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.388
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.121
20636128O CRK C2
Adder
1.691
207459AE1-142 C O1
Solar/Wind Harmer
0.274
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20714828MDF_W3-079
Solar/Wind Harmer
0.078
20641628MLH_W1-032
Solar/Wind Harmer
0.073
217197RE CRAN C
Solar/Wind Harmer
0.135
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.196
924131AB2-057 GEN
Solar/Wind Harmer
0.253
20635028RRCT1&2
Adder
2.817
20635128RRCT3&4
Adder
2.719
20635128RRCT3&4
Adder
2.372
218418LINDEN_G5
Adder
4.094
218419LINDEN_G6
Adder
4.094
972260AH1-715 GEN1
Adder
3.278
20675428EAM_W2-061
Solar/Wind Harmer
0.045
223401AF1-299 GEN
Solar/Wind Helper
0.272
223402AF1-300 C
Solar/Wind Helper
0.272
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.552
233935AB2-179 C
Solar/Wind Harmer
1.159
213497CHSTR7-9
Adder
1.074
233933AB2-153 GEN
Solar/Wind Harmer
0.462
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.416
233987AB2-037 GEN
Solar/Wind Harmer
4.194
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.97
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.325
233997TMININ_4.2
Solar/Wind Harmer
0.361
232406W1-004 FULL
Solar/Wind Harmer
0.362
232914OH NUG3
Adder
3.198
232916OH NUG5
Adder
3.198
232921TASLEY2G
Adder
1.869
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.874
970695AG2-447 GEN
Solar/Wind Harmer
1.24
233939AC1-091 C
Solar/Wind Harmer
0.928
233972AC1-094 C
Solar/Wind Harmer
0.745
213815MOSER1-3
Adder
1.097
219914AD2-027 C
Solar/Wind Harmer
0.184
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.227
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20716428NHV_W2-082
Solar/Wind Harmer
0.476
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20636028O CRK C1
Adder
1.854
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963391AG1-188 GEN
Solar/Wind Harmer
0.98
971667AH1-334 GEN
Solar/Wind Harmer
0.715
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.251
219612MATRIX C
Solar/Wind Harmer
0.046
20716928W4-060COL
Solar/Wind Harmer
0.175
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
217213AMBOY SO C
Solar/Wind Harmer
0.03
219249CENTRALDIV C
Solar/Wind Harmer
0.009
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20673728F2S_V4-070
Solar/Wind Harmer
0.043
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
VTFLTFEXP_VFT->PJM
CMTX
31.572
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.608
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.957
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.617
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.442
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.041
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.45 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:678.84
MW Contribution:
1.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.552
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
233915AB1-141 GEN
Solar/Wind Harmer
0.407
233968AD2-076_GEN
Solar/Wind Harmer
2.658
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.42
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.219
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233918AB1-142 GEN
Solar/Wind Harmer
0.407
233944AB2-135 GEN
Solar/Wind Harmer
2.12
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.99
232902EASTMUNI
Adder
4.959
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.027
233996TM1833_GEN
Solar/Wind Harmer
0.361
233998TM1NIN_3.36
Solar/Wind Harmer
0.361
232404W1-003 C
Solar/Wind Harmer
0.362
232408W1-005 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.175
234033AF1-007_GEN
Solar/Wind Harmer
13.348
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233970AC1-092 C
Solar/Wind Harmer
0.927
228400MICK 1CT
Adder
3.642
219766PARADISE C
Solar/Wind Harmer
0.096
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.86
228260V4-054C
Solar/Wind Harmer
0.303
228206SHRMN CT
Adder
4.831
219348LDSOLAR C
Solar/Wind Harmer
0.175
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.809
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
228729W2-030 C
Solar/Wind Harmer
0.165
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
20716028EGP_W2-019
Solar/Wind Harmer
0.124
207522AF2-254 C
Solar/Wind Harmer
0.384
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715828PEM_W1-120
Solar/Wind Harmer
0.142
219276PARKLANDSO C
Solar/Wind Harmer
0.122
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.86
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
972275AH1-722 GEN
Adder
7.525
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.302
208909MACR G3
Adder
32.158
213508CON10-11
50/50
0.998
213508CON10-11
50/50
0.998
213518CONOW8-9
50/50
0.998
213518CONOW8-9
50/50
0.998
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.44
213587EDDYSTN3
Adder
31.412
233982AB2-133 GEN
Solar/Wind Harmer
2.006
233930AB2-032 GEN
Solar/Wind Harmer
0.342
232436AB1-176 C
Solar/Wind Harmer
0.092
234014AF1-036_GEN
Solar/Wind Harmer
1.085
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
232910NRG_G1
Adder
3.244
234041AC1-190 GEN
Solar/Wind Harmer
3.31
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.467
233952AC2-187 GEN
Solar/Wind Harmer
0.409
233954AC2-188 GEN
Solar/Wind Harmer
0.409
233994AC2-023 GEN
Solar/Wind Harmer
0.976
232428Y3-058 C
Solar/Wind Harmer
0.303
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.711
232410W1-006 C
Solar/Wind Harmer
0.362
232918OH NUG7
Adder
3.175
232905CHERITON_25
Adder
0.888
231940T-011
Adder
0.269
232899W1-062
Adder
3.395
233971AC1-093 C
Solar/Wind Harmer
0.88
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.244
228307PCLP GT
Adder
3.695
228351V2-046C
Solar/Wind Harmer
0.605
230511AF1-262
Solar/Wind Harmer
0.054
228201CARL#2CT
Adder
2.031
228200CARL#1CT
Adder
1.931
228251CARLLS#4
Adder
0.186
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
233955AB2-172 GEN
Solar/Wind Harmer
1.849
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.353
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.135
232904IR4
Adder
29.017
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
219137THOSOLAR C
Solar/Wind Harmer
0.375
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.188
230434AG1-499 GEN
Solar/Wind Harmer
0.174
972141AH1-641 GEN
Solar/Wind Harmer
0.858
230430AE1-229_GEN
Solar/Wind Harmer
8.528
219615MILLCREEK C
Solar/Wind Harmer
0.071
228728W1-130C
Solar/Wind Harmer
0.195
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219224BRL12CT4
Adder
2.608
230422AE1-104_GEN1
Solar/Wind Harmer
9.701
230425AE1-104_GEN2
Solar/Wind Harmer
9.701
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
207487AE2-000G4
Solar/Wind Harmer
8.262
207497AE2-000G2
Solar/Wind Harmer
8.262
207500AE2-000G1
Solar/Wind Harmer
8.262
207507AE2-000G3
Solar/Wind Harmer
8.262
971189AH1-054 GEN
Solar/Wind Harmer
0.31
963401AG1-189 GEN
Solar/Wind Harmer
0.595
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207445AB1-138_GEN
Solar/Wind Harmer
0.15
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.311
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20716228APLW2-078
Solar/Wind Harmer
0.221
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.14
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.112
20676128MHD_W3-029
Solar/Wind Harmer
0.114
213535CROYDN11
Adder
3.003
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
219607WPEMNERT C
Solar/Wind Harmer
0.122
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.388
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.121
20636128O CRK C2
Adder
1.69
207459AE1-142 C O1
Solar/Wind Harmer
0.274
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20714828MDF_W3-079
Solar/Wind Harmer
0.078
20641628MLH_W1-032
Solar/Wind Harmer
0.073
217197RE CRAN C
Solar/Wind Harmer
0.135
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.196
924131AB2-057 GEN
Solar/Wind Harmer
0.252
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.719
20635128RRCT3&4
Adder
2.371
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
20675428EAM_W2-061
Solar/Wind Harmer
0.045
223401AF1-299 GEN
Solar/Wind Helper
0.272
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.552
233935AB2-179 C
Solar/Wind Harmer
1.159
213497CHSTR7-9
Adder
1.074
233933AB2-153 GEN
Solar/Wind Harmer
0.462
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.416
233987AB2-037 GEN
Solar/Wind Harmer
4.192
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.964
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.324
233997TMININ_4.2
Solar/Wind Harmer
0.361
232406W1-004 FULL
Solar/Wind Harmer
0.362
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
232921TASLEY2G
Adder
1.868
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.873
970695AG2-447 GEN
Solar/Wind Harmer
1.239
233939AC1-091 C
Solar/Wind Harmer
0.927
233972AC1-094 C
Solar/Wind Harmer
0.745
213815MOSER1-3
Adder
1.097
219914AD2-027 C
Solar/Wind Harmer
0.184
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.227
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20716428NHV_W2-082
Solar/Wind Harmer
0.476
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20636028O CRK C1
Adder
1.854
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963391AG1-188 GEN
Solar/Wind Harmer
0.98
971667AH1-334 GEN
Solar/Wind Harmer
0.715
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.251
219612MATRIX C
Solar/Wind Harmer
0.046
20716928W4-060COL
Solar/Wind Harmer
0.175
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
217213AMBOY SO C
Solar/Wind Harmer
0.03
219249CENTRALDIV C
Solar/Wind Harmer
0.009
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.272
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
VTFLTFEXP_VFT->PJM
CMTX
31.565
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.608
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.616
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.956
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.439
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.039
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.79 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:675.02
MW Contribution:
1.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.548
231919CHRIST1
Adder
1.859
231920CHRIST2
Adder
1.818
233915AB1-141 GEN
Solar/Wind Harmer
0.402
233968AD2-076_GEN
Solar/Wind Harmer
2.624
970597AG2-380 GEN
Solar/Wind Harmer
1.648
231906DC3 NUG
Adder
5.458
231902DC CT7
Adder
4.364
231907DC10
Adder
1.363
213942SCHUYLKILL
Adder
1.288
213942SCHUYLKILL
Adder
0.985
213957STHWK3-4
Adder
0.976
213957STHWK3-4
Adder
0.976
232813VAUGHN
Adder
0.216
233955AB2-172 GEN
Solar/Wind Harmer
1.825
233940AF2-379 C
Solar/Wind Harmer
0.067
971195AH1-057 GEN
Solar/Wind Harmer
0.349
233901CHERRYDALE C
Solar/Wind Harmer
0.402
232912OH NUG1
Adder
3.153
232913OH NUG2
Adder
3.111
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.12
232904IR4
Adder
28.628
213515CONOW3-4
50/50
0.731
213516CONOW5-6
50/50
0.548
233935AB2-179 C
Solar/Wind Harmer
1.145
213497CHSTR7-9
Adder
1.06
233933AB2-153 GEN
Solar/Wind Harmer
0.456
232422X3-066 FULL
Solar/Wind Harmer
0.099
213958STHWK5-6
Adder
0.976
232417X3-008 C
Solar/Wind Harmer
0.411
213561DLWR9-10
Adder
1.175
213561DLWR9-10
Adder
0.898
219137THOSOLAR C
Solar/Wind Harmer
0.37
219258KINSLEYDEP C
Solar/Wind Harmer
0.098
964001AG1-254 GEN
Solar/Wind Harmer
2.156
230434AG1-499 GEN
Solar/Wind Harmer
0.171
972141AH1-641 GEN
Solar/Wind Harmer
0.845
230430AE1-229_GEN
Solar/Wind Harmer
8.401
219615MILLCREEK C
Solar/Wind Harmer
0.07
228728W1-130C
Solar/Wind Harmer
0.192
230407AD2-065 C
Solar/Wind Harmer
0.038
970453AG2-297 GEN
Solar/Wind Harmer
0.788
219610FLORENCE C
Solar/Wind Harmer
0.398
219224BRL12CT4
Adder
2.568
233987AB2-037 GEN
Solar/Wind Harmer
4.137
233964AF2-378 GEN
Solar/Wind Harmer
0.046
232907VN8
Adder
10.819
233950AC2-186 GEN
Solar/Wind Harmer
0.202
233923SMA
Solar/Wind Harmer
1.306
233997TMININ_4.2
Solar/Wind Harmer
0.356
232406W1-004 FULL
Solar/Wind Harmer
0.357
232914OH NUG3
Adder
3.153
232916OH NUG5
Adder
3.153
232921TASLEY2G
Adder
1.843
232434Z2-077 GEN
Solar/Wind Harmer
0.089
213560DLW11-12
Adder
0.898
233973AC2-185 C
Solar/Wind Harmer
1.848
970695AG2-447 GEN
Solar/Wind Harmer
1.222
233939AC1-091 C
Solar/Wind Harmer
0.915
233972AC1-094 C
Solar/Wind Harmer
0.734
213815MOSER1-3
Adder
1.08
219914AD2-027 C
Solar/Wind Harmer
0.181
219921AF1-264
Solar/Wind Harmer
0.043
219623KINSLEYBEA C
Solar/Wind Harmer
0.128
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.055
228711V2-041C
Solar/Wind Harmer
0.172
219221BRL12CT1
Adder
2.568
219223BRL12CT3
Adder
2.568
219688LUMSOLAR_S C
Solar/Wind Harmer
0.058
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.05
959561AF2-247 GEN
Solar/Wind Harmer
0.135
219114HARTZY_C
Solar/Wind Harmer
0.224
219727YARDVSOLFA C
Solar/Wind Harmer
0.242
20716428NHV_W2-082
Solar/Wind Harmer
0.468
20715728PEM_W1-119
Solar/Wind Harmer
0.14
20636028O CRK C1
Adder
1.823
20714928UPF_X1-085
Solar/Wind Harmer
0.105
963391AG1-188 GEN
Solar/Wind Harmer
0.964
971667AH1-334 GEN
Solar/Wind Harmer
0.703
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.247
219612MATRIX C
Solar/Wind Harmer
0.045
20716928W4-060COL
Solar/Wind Harmer
0.172
20635828PARLN1&2
Adder
0.803
20635928PARLN3&4
Adder
0.803
217213AMBOY SO C
Solar/Wind Harmer
0.03
208835TUHI V3-051
Solar/Wind Helper
0.01
230422AE1-104_GEN1
Solar/Wind Harmer
9.553
230425AE1-104_GEN2
Solar/Wind Harmer
9.553
227927V4-067C
Solar/Wind Harmer
0.056
213611FALLS1-3
Adder
0.999
213611FALLS1-3
Adder
0.999
20720728JCB_W1-129
Solar/Wind Harmer
0.079
20715028HAN_X4-015
Solar/Wind Harmer
0.079
207487AE2-000G4
Solar/Wind Harmer
8.126
207497AE2-000G2
Solar/Wind Harmer
8.126
207500AE2-000G1
Solar/Wind Harmer
8.126
207507AE2-000G3
Solar/Wind Harmer
8.126
971189AH1-054 GEN
Solar/Wind Harmer
0.305
963401AG1-189 GEN
Solar/Wind Harmer
0.585
970025AG2-016 GEN
Solar/Wind Harmer
0.729
207445AB1-138_GEN
Solar/Wind Harmer
0.148
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.306
20720628TIN_W1-124
Solar/Wind Harmer
0.246
20716228APLW2-078
Solar/Wind Harmer
0.218
971521AH1-258 GEN
Solar/Wind Harmer
0.663
20635928PARLN3&4
Adder
1.774
20675528CPH_W2-050
Solar/Wind Harmer
0.137
218526CNTRALGAS2 C
Solar/Wind Harmer
0.088
20673828FLE_V3-070
Solar/Wind Harmer
0.11
213514CONOW1-2
50/50
0.731
213515CONOW3-4
50/50
0.731
231918WEST 1
Adder
1.427
231917EM10
Adder
0.996
213497CHSTR7-9
Adder
1.06
213497CHSTR7-9
Adder
1.06
233918AB1-142 GEN
Solar/Wind Harmer
0.402
233944AB2-135 GEN
Solar/Wind Harmer
2.094
234012AE2-112_GEN
Solar/Wind Harmer
0.91
213958STHWK5-6
Adder
0.976
232902EASTMUNI
Adder
4.895
232426Y1-080 FULL
Solar/Wind Harmer
0.069
232919VN10
Adder
1.013
233996TM1833_GEN
Solar/Wind Harmer
0.356
233998TM1NIN_3.36
Solar/Wind Harmer
0.356
232404W1-003 C
Solar/Wind Harmer
0.357
232408W1-005 C
Solar/Wind Harmer
0.357
232917OH NUG6
Adder
3.139
232915OH NUG4
Adder
3.132
234033AF1-007_GEN
Solar/Wind Harmer
13.17
972177AH1-672 GEN
Solar/Wind Harmer
4.75
213560DLW11-12
Adder
0.898
232900DEMECSMY
Adder
3.212
232901NORTHST
Adder
2.861
233970AC1-092 C
Solar/Wind Harmer
0.915
228400MICK 1CT
Adder
3.589
219766PARADISE C
Solar/Wind Harmer
0.095
219907AC1-030 C
Solar/Wind Harmer
0.041
970997AG2-616 GEN
Solar/Wind Harmer
2.818
228260V4-054C
Solar/Wind Harmer
0.299
228206SHRMN CT
Adder
4.758
219348LDSOLAR C
Solar/Wind Harmer
0.172
219222BRL12CT2
Adder
2.568
228732V1-021 C
Adder
0.054
972251AH1-710 GEN
Adder
13.604
219686LUMSOLAR_N C
Solar/Wind Harmer
0.057
228729W2-030 C
Solar/Wind Harmer
0.163
214194N WALES4
Adder
0.241
213611FALLS1-3
Adder
0.999
20716028EGP_W2-019
Solar/Wind Harmer
0.122
207522AF2-254 C
Solar/Wind Harmer
0.378
20717128DIX_Z2-102
Solar/Wind Harmer
0.347
20715828PEM_W1-120
Solar/Wind Harmer
0.14
219276PARKLANDSO C
Solar/Wind Harmer
0.12
963711AG1-223 GEN
Solar/Wind Harmer
0.373
20714528FRN_Y2-051
Solar/Wind Harmer
0.074
219680HOPEWELLV C1
Solar/Wind Harmer
0.019
20715228NPK_W1-113
Solar/Wind Harmer
0.106
20720528MAN_W1-024
Solar/Wind Harmer
0.062
20720428HOL_W1-112
Solar/Wind Harmer
0.084
20635828PARLN1&2
Adder
1.774
20635028RRCT1&2
Adder
2.809
218524CNTRALGAS1 C
Solar/Wind Harmer
0.087
218440SUMMTASSOC C
Solar/Wind Harmer
0.03
218428ETC SOLAR C
Solar/Wind Harmer
0.008
219908AB1-139 C
Solar/Wind Harmer
0.09
219919AE1-041 FULL
Solar/Wind Harmer
0.01
208909MACR G3
Adder
31.435
208835TUHI V3-051
Solar/Wind Helper
0.01
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213516CONOW5-6
50/50
0.731
213517CONOW7
50/50
0.731
213589EDDYSTN4
Adder
31.045
213587EDDYSTN3
Adder
31.018
233982AB2-133 GEN
Solar/Wind Harmer
1.981
233930AB2-032 GEN
Solar/Wind Harmer
0.338
232436AB1-176 C
Solar/Wind Harmer
0.091
234014AF1-036_GEN
Solar/Wind Harmer
1.071
232424Y1-079 C
Solar/Wind Harmer
0.218
233984AB2-036 GEN
Solar/Wind Harmer
4.803
232910NRG_G1
Adder
3.201
234041AC1-190 GEN
Solar/Wind Harmer
3.267
234036AF2-325 C
Solar/Wind Harmer
0.333
233946AB2-136 GEN
Solar/Wind Harmer
1.448
233952AC2-187 GEN
Solar/Wind Harmer
0.404
233954AC2-188 GEN
Solar/Wind Harmer
0.404
233994AC2-023 GEN
Solar/Wind Harmer
0.963
232428Y3-058 C
Solar/Wind Harmer
0.299
234015AF2-250 C
Solar/Wind Harmer
0.043
232926CRISFLD1
Adder
0.702
232410W1-006 C
Solar/Wind Harmer
0.357
232918OH NUG7
Adder
3.132
232905CHERITON_25
Adder
0.876
231940T-011
Adder
0.266
232899W1-062
Adder
3.349
233971AC1-093 C
Solar/Wind Harmer
0.868
972233AH1-701 GEN
Adder
1.272
213815MOSER1-3
Adder
1.08
213815MOSER1-3
Adder
1.08
219904AC1-010 C
Solar/Wind Harmer
0.114
219912AD2-042 GEN
Solar/Wind Harmer
0.24
228307PCLP GT
Adder
3.641
228351V2-046C
Solar/Wind Harmer
0.596
230511AF1-262
Solar/Wind Harmer
0.053
228201CARL#2CT
Adder
2
228200CARL#1CT
Adder
1.903
228251CARLLS#4
Adder
0.184
219906AC1-017 C
Solar/Wind Harmer
0.065
230433AD2-135 GEN
Solar/Wind Harmer
0.029
213535CROYDN11
Adder
2.957
219272CLEANLIGHT C
Solar/Wind Harmer
0.052
219607WPEMNERT C
Solar/Wind Harmer
0.12
219304NAMERICA C
Solar/Wind Harmer
0.089
219287REEVESEAST C
Solar/Wind Harmer
0.382
228754AB1-001 C
Solar/Wind Harmer
0.039
214067T20SOLAR
Solar/Wind Harmer
0.071
20720828JCB_W4-025
Solar/Wind Harmer
0.119
20636128O CRK C2
Adder
1.662
207459AE1-142 C O1
Solar/Wind Harmer
0.269
20628028LAKEHURS
Adder
0.243
219817TRENTONSOL C
Solar/Wind Harmer
0.28
20714828MDF_W3-079
Solar/Wind Harmer
0.077
20641628MLH_W1-032
Solar/Wind Harmer
0.072
217197RE CRAN C
Solar/Wind Harmer
0.133
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.192
924131AB2-057 GEN
Solar/Wind Harmer
0.248
20635028RRCT1&2
Adder
2.766
20635128RRCT3&4
Adder
2.67
20635128RRCT3&4
Adder
2.329
223401AF1-299 GEN
Solar/Wind Helper
0.284
223402AF1-300 C
Solar/Wind Helper
0.284
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.015
VTFLTFEXP_VFT->PJM
CMTX
30.969
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.819
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.863
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.553
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.215
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.757
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.0 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:641.56
MW Contribution:
1.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.553
231919CHRIST1
Adder
1.889
231920CHRIST2
Adder
1.847
233915AB1-141 GEN
Solar/Wind Harmer
0.408
233968AD2-076_GEN
Solar/Wind Harmer
2.668
970597AG2-380 GEN
Solar/Wind Harmer
1.675
231906DC3 NUG
Adder
5.55
231902DC CT7
Adder
4.437
231907DC10
Adder
1.386
213942SCHUYLKILL
Adder
1.31
213942SCHUYLKILL
Adder
1.002
213957STHWK3-4
Adder
0.993
213957STHWK3-4
Adder
0.993
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.857
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.355
233901CHERRYDALE C
Solar/Wind Harmer
0.409
232912OH NUG1
Adder
3.21
232913OH NUG2
Adder
3.167
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.14
232904IR4
Adder
29.142
213561DLWR9-10
Adder
1.197
213561DLWR9-10
Adder
0.915
219137THOSOLAR C
Solar/Wind Harmer
0.377
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.199
230434AG1-499 GEN
Solar/Wind Harmer
0.175
972141AH1-641 GEN
Solar/Wind Harmer
0.862
230430AE1-229_GEN
Solar/Wind Harmer
8.569
219615MILLCREEK C
Solar/Wind Harmer
0.071
228728W1-130C
Solar/Wind Harmer
0.196
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.804
219610FLORENCE C
Solar/Wind Harmer
0.407
219224BRL12CT4
Adder
2.621
230422AE1-104_GEN1
Solar/Wind Harmer
9.749
230425AE1-104_GEN2
Solar/Wind Harmer
9.749
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.02
213611FALLS1-3
Adder
1.02
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
207487AE2-000G4
Solar/Wind Harmer
8.308
207497AE2-000G2
Solar/Wind Harmer
8.308
207500AE2-000G1
Solar/Wind Harmer
8.308
207507AE2-000G3
Solar/Wind Harmer
8.308
971189AH1-054 GEN
Solar/Wind Harmer
0.311
963401AG1-189 GEN
Solar/Wind Harmer
0.598
970025AG2-016 GEN
Solar/Wind Harmer
0.745
207445AB1-138_GEN
Solar/Wind Harmer
0.151
219620RIDERU C
Solar/Wind Harmer
0.015
20714428HOW_X1-037
Solar/Wind Harmer
0.313
20720628TIN_W1-124
Solar/Wind Harmer
0.252
20716228APLW2-078
Solar/Wind Harmer
0.223
971521AH1-258 GEN
Solar/Wind Harmer
0.679
20635928PARLN3&4
Adder
1.817
20675528CPH_W2-050
Solar/Wind Harmer
0.141
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.113
20676128MHD_W3-029
Solar/Wind Harmer
0.114
20676428JCR_X2-075
Solar/Wind Harmer
0.081
218449LINSOLAR C
Solar/Wind Harmer
0.239
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.45
231917EM10
Adder
1.012
213497CHSTR7-9
Adder
1.078
213497CHSTR7-9
Adder
1.078
233918AB1-142 GEN
Solar/Wind Harmer
0.408
233944AB2-135 GEN
Solar/Wind Harmer
2.129
234012AE2-112_GEN
Solar/Wind Harmer
0.926
213958STHWK5-6
Adder
0.993
232902EASTMUNI
Adder
4.98
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.031
233996TM1833_GEN
Solar/Wind Harmer
0.363
233998TM1NIN_3.36
Solar/Wind Harmer
0.363
232404W1-003 C
Solar/Wind Harmer
0.363
232408W1-005 C
Solar/Wind Harmer
0.363
232917OH NUG6
Adder
3.196
232915OH NUG4
Adder
3.188
234033AF1-007_GEN
Solar/Wind Harmer
13.406
972177AH1-672 GEN
Solar/Wind Harmer
4.835
213560DLW11-12
Adder
0.915
232900DEMECSMY
Adder
3.27
232901NORTHST
Adder
2.913
233970AC1-092 C
Solar/Wind Harmer
0.931
228400MICK 1CT
Adder
3.659
219766PARADISE C
Solar/Wind Harmer
0.097
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.874
228260V4-054C
Solar/Wind Harmer
0.305
228206SHRMN CT
Adder
4.855
219348LDSOLAR C
Solar/Wind Harmer
0.176
219222BRL12CT2
Adder
2.621
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.879
219686LUMSOLAR_N C
Solar/Wind Harmer
0.059
228729W2-030 C
Solar/Wind Harmer
0.166
214194N WALES4
Adder
0.246
213611FALLS1-3
Adder
1.02
20716028EGP_W2-019
Solar/Wind Harmer
0.125
207522AF2-254 C
Solar/Wind Harmer
0.386
20717128DIX_Z2-102
Solar/Wind Harmer
0.354
20715828PEM_W1-120
Solar/Wind Harmer
0.143
219276PARKLANDSO C
Solar/Wind Harmer
0.123
963711AG1-223 GEN
Solar/Wind Harmer
0.381
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.817
20635028RRCT1&2
Adder
2.878
218524CNTRALGAS1 C
Solar/Wind Harmer
0.09
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.092
219919AE1-041 FULL
Solar/Wind Harmer
0.01
972275AH1-722 GEN
Adder
7.573
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.304
208909MACR G3
Adder
32.417
213508CON10-11
50/50
0.999
213508CON10-11
50/50
0.999
213518CONOW8-9
50/50
0.999
213518CONOW8-9
50/50
0.999
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.555
213587EDDYSTN3
Adder
31.528
233982AB2-133 GEN
Solar/Wind Harmer
2.013
233930AB2-032 GEN
Solar/Wind Harmer
0.344
232436AB1-176 C
Solar/Wind Harmer
0.093
234014AF1-036_GEN
Solar/Wind Harmer
1.089
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.885
232910NRG_G1
Adder
3.257
234041AC1-190 GEN
Solar/Wind Harmer
3.324
234036AF2-325 C
Solar/Wind Harmer
0.339
233946AB2-136 GEN
Solar/Wind Harmer
1.474
233952AC2-187 GEN
Solar/Wind Harmer
0.411
233954AC2-188 GEN
Solar/Wind Harmer
0.411
233994AC2-023 GEN
Solar/Wind Harmer
0.98
232428Y3-058 C
Solar/Wind Harmer
0.304
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.714
232410W1-006 C
Solar/Wind Harmer
0.363
232905CHERITON_25
Adder
0.892
232918OH NUG7
Adder
3.188
231940T-011
Adder
0.271
232899W1-062
Adder
3.409
233971AC1-093 C
Solar/Wind Harmer
0.884
972233AH1-701 GEN
Adder
1.297
213815MOSER1-3
Adder
1.102
213815MOSER1-3
Adder
1.102
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.245
228307PCLP GT
Adder
3.713
228351V2-046C
Solar/Wind Harmer
0.608
230511AF1-262
Solar/Wind Harmer
0.055
228201CARL#2CT
Adder
2.041
228200CARL#1CT
Adder
1.941
228251CARLLS#4
Adder
0.187
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
213535CROYDN11
Adder
3.018
219272CLEANLIGHT C
Solar/Wind Harmer
0.054
219607WPEMNERT C
Solar/Wind Harmer
0.123
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.39
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.122
20636128O CRK C2
Adder
1.7
207459AE1-142 C O1
Solar/Wind Harmer
0.276
20628028LAKEHURS
Adder
0.248
219817TRENTONSOL C
Solar/Wind Harmer
0.287
20714828MDF_W3-079
Solar/Wind Harmer
0.079
20641628MLH_W1-032
Solar/Wind Harmer
0.074
217197RE CRAN C
Solar/Wind Harmer
0.136
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.197
924131AB2-057 GEN
Solar/Wind Harmer
0.254
20635028RRCT1&2
Adder
2.834
20635128RRCT3&4
Adder
2.736
20635128RRCT3&4
Adder
2.386
218418LINDEN_G5
Adder
4.119
218419LINDEN_G6
Adder
4.119
972260AH1-715 GEN1
Adder
3.299
20675428EAM_W2-061
Solar/Wind Harmer
0.045
219036LINDEN_G7
Adder
3.972
219035LINDEN_G8
Adder
3.916
972261AH1-715 GEN2
Adder
3.803
223401AF1-299 GEN
Solar/Wind Helper
0.271
223402AF1-300 C
Solar/Wind Helper
0.271
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.553
233935AB2-179 C
Solar/Wind Harmer
1.163
213497CHSTR7-9
Adder
1.078
233933AB2-153 GEN
Solar/Wind Harmer
0.464
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.993
232417X3-008 C
Solar/Wind Harmer
0.418
233987AB2-037 GEN
Solar/Wind Harmer
4.21
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
11.01
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.33
233997TMININ_4.2
Solar/Wind Harmer
0.363
232406W1-004 FULL
Solar/Wind Harmer
0.363
232921TASLEY2G
Adder
1.876
232914OH NUG3
Adder
3.21
232916OH NUG5
Adder
3.21
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.915
233973AC2-185 C
Solar/Wind Harmer
1.882
970695AG2-447 GEN
Solar/Wind Harmer
1.245
233939AC1-091 C
Solar/Wind Harmer
0.931
233972AC1-094 C
Solar/Wind Harmer
0.748
213815MOSER1-3
Adder
1.102
219914AD2-027 C
Solar/Wind Harmer
0.185
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.131
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.176
219221BRL12CT1
Adder
2.621
219223BRL12CT3
Adder
2.621
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.018
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.228
219727YARDVSOLFA C
Solar/Wind Harmer
0.247
20716428NHV_W2-082
Solar/Wind Harmer
0.478
20715728PEM_W1-119
Solar/Wind Harmer
0.143
20636028O CRK C1
Adder
1.864
20714928UPF_X1-085
Solar/Wind Harmer
0.108
963391AG1-188 GEN
Solar/Wind Harmer
0.985
971667AH1-334 GEN
Solar/Wind Harmer
0.719
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.252
219612MATRIX C
Solar/Wind Harmer
0.047
20716928W4-060COL
Solar/Wind Harmer
0.176
20635828PARLN1&2
Adder
0.823
20635928PARLN3&4
Adder
0.823
217213AMBOY SO C
Solar/Wind Harmer
0.031
219249CENTRALDIV C
Solar/Wind Harmer
0.01
207442AE1-156 GEN
Solar/Wind Harmer
0.178
20673728F2S_V4-070
Solar/Wind Harmer
0.043
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.015
VTFLTFEXP_VFT->PJM
CMTX
31.773
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.822
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.56
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.872
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.517
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.197
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.49 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:603.92
MW Contribution:
0.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.552
213893PHLISST1
50/50
1.346
231916EM3
50/50
0.419
231919CHRIST1
50/50
1.997
231920CHRIST2
50/50
1.953
231901EM4
50/50
0.845
213740LIBE_ST1
50/50
1.073
231505HR4
50/50
0.884
233915AB1-141 GEN
Solar/Wind Harmer
0.105
233968AD2-076_GEN
Solar/Wind Harmer
0.932
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.42
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.219
971195AH1-057 GEN
Solar/Wind Harmer
0.226
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
232432Z2-076 GEN
Solar/Wind Harmer
0.005
232920IR10
Adder
1.135
232904IR4
Adder
29.017
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
964001AG1-254 GEN
Solar/Wind Harmer
1.694
972141AH1-641 GEN
Solar/Wind Harmer
0.466
230430AE1-229_GEN
Solar/Wind Harmer
5.911
970453AG2-297 GEN
Solar/Wind Harmer
0.739
219224BRL12CT4
Adder
2.608
230422AE1-104_GEN1
Solar/Wind Harmer
3.894
230425AE1-104_GEN2
Solar/Wind Harmer
3.894
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
207487AE2-000G4
Solar/Wind Harmer
3.317
207497AE2-000G2
Solar/Wind Harmer
3.317
207500AE2-000G1
Solar/Wind Harmer
3.317
207507AE2-000G3
Solar/Wind Harmer
3.317
971189AH1-054 GEN
Solar/Wind Harmer
0.2
963401AG1-189 GEN
Solar/Wind Harmer
0.294
970025AG2-016 GEN
Solar/Wind Harmer
0.479
971521AH1-258 GEN
Solar/Wind Harmer
0.436
20635928PARLN3&4
Adder
1.806
218526CNTRALGAS2 C
Solar/Wind Harmer
0.186
213508CON10-11
50/50
0.998
213508CON10-11
50/50
0.998
213518CONOW8-9
50/50
0.998
213518CONOW8-9
50/50
0.998
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
231909HR2
50/50
0.61
231908HR1
50/50
0.607
231910HR3
50/50
0.607
213589EDDYSTN4
Adder
31.44
213587EDDYSTN3
Adder
31.412
233930AB2-032 GEN
Solar/Wind Harmer
0.394
234014AF1-036_GEN
Solar/Wind Harmer
0.932
233984AB2-036 GEN
Solar/Wind Harmer
2.839
232910NRG_G1
Adder
3.244
234041AC1-190 GEN
Solar/Wind Harmer
2.694
232926CRISFLD1
Adder
0.711
232410W1-006 C
Solar/Wind Harmer
0.234
232918OH NUG7
Adder
3.175
232905CHERITON_25
Adder
0.888
231940T-011
Adder
0.269
232899W1-062
Adder
3.395
233971AC1-093 C
Solar/Wind Harmer
0.624
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228307PCLP GT
Adder
3.695
228201CARL#2CT
Adder
2.031
228200CARL#1CT
Adder
1.931
228251CARLLS#4
Adder
0.186
213535CROYDN11
Adder
3.003
219304NAMERICA C
Solar/Wind Harmer
0.027
20636128O CRK C2
Adder
1.69
20628028LAKEHURS
Adder
0.247
20714828MDF_W3-079
Solar/Wind Harmer
0.025
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.719
20635128RRCT3&4
Adder
2.371
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
223401AF1-299 GEN
Solar/Wind Helper
0.272
223402AF1-300 C
Solar/Wind Helper
0.272
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
50/50
1.533
213889PHLISCT2
50/50
0.933
231917EM10
50/50
1.07
213738LIBE_CT1
50/50
0.777
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233918AB1-142 GEN
Solar/Wind Harmer
0.105
234012AE2-112_GEN
Solar/Wind Harmer
0.932
213958STHWK5-6
Adder
0.99
232902EASTMUNI
Adder
4.959
232919VN10
Adder
1.027
232404W1-003 C
Solar/Wind Harmer
0.234
232408W1-005 C
Solar/Wind Harmer
0.234
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.175
234033AF1-007_GEN
Solar/Wind Harmer
4.956
972177AH1-672 GEN
Solar/Wind Harmer
3.65
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233970AC1-092 C
Solar/Wind Harmer
0.624
228400MICK 1CT
Adder
3.642
970997AG2-616 GEN
Solar/Wind Harmer
2.152
228206SHRMN CT
Adder
4.831
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.809
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
207522AF2-254 C
Solar/Wind Harmer
0.248
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.86
218524CNTRALGAS1 C
Solar/Wind Harmer
0.184
972275AH1-722 GEN
Adder
7.525
207528AF2-192 GEN
Solar/Wind Harmer
0.171
208909MACR G3
Adder
32.158
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.552
213890PHLISCT3
50/50
0.933
213888PHLISCT1
50/50
0.933
213739LIBE_CT2
50/50
0.777
233935AB2-179 C
Solar/Wind Harmer
0.637
213497CHSTR7-9
Adder
1.074
232422X3-066 FULL
Solar/Wind Harmer
0.034
213958STHWK5-6
Adder
0.99
233987AB2-037 GEN
Solar/Wind Harmer
0
232907VN8
Adder
10.964
232406W1-004 FULL
Solar/Wind Harmer
0.234
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
232921TASLEY2G
Adder
1.868
232434Z2-077 GEN
Solar/Wind Harmer
0.015
213560DLW11-12
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
0.624
970695AG2-447 GEN
Solar/Wind Harmer
0.865
233939AC1-091 C
Solar/Wind Harmer
0.624
233972AC1-094 C
Solar/Wind Harmer
0.624
213815MOSER1-3
Adder
1.097
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
20636028O CRK C1
Adder
1.854
963391AG1-188 GEN
Solar/Wind Harmer
0.479
971667AH1-334 GEN
Solar/Wind Harmer
0.462
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
207442AE1-156 GEN
Solar/Wind Harmer
0.014
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
VTFLTFEXP_VFT->PJM
CMTX
31.565
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.608
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.616
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.956
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.439
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.039
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.62 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:679.82
MW Contribution:
1.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233918AB1-142 GEN
Solar/Wind Harmer
0.407
233944AB2-135 GEN
Solar/Wind Harmer
2.12
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.99
232902EASTMUNI
Adder
4.959
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.027
233996TM1833_GEN
Solar/Wind Harmer
0.361
233998TM1NIN_3.36
Solar/Wind Harmer
0.361
232404W1-003 C
Solar/Wind Harmer
0.362
232408W1-005 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.175
234033AF1-007_GEN
Solar/Wind Harmer
13.348
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
213514CONOW1-2
50/50
0.552
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
233915AB1-141 GEN
Solar/Wind Harmer
0.407
233968AD2-076_GEN
Solar/Wind Harmer
2.658
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.42
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.849
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.353
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.135
232904IR4
Adder
29.017
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
219137THOSOLAR C
Solar/Wind Harmer
0.375
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.188
230434AG1-499 GEN
Solar/Wind Harmer
0.174
972141AH1-641 GEN
Solar/Wind Harmer
0.858
230430AE1-229_GEN
Solar/Wind Harmer
8.528
219615MILLCREEK C
Solar/Wind Harmer
0.071
228728W1-130C
Solar/Wind Harmer
0.195
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219224BRL12CT4
Adder
2.608
230422AE1-104_GEN1
Solar/Wind Harmer
9.701
230425AE1-104_GEN2
Solar/Wind Harmer
9.701
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
207487AE2-000G4
Solar/Wind Harmer
8.262
207497AE2-000G2
Solar/Wind Harmer
8.262
207500AE2-000G1
Solar/Wind Harmer
8.262
207507AE2-000G3
Solar/Wind Harmer
8.262
971189AH1-054 GEN
Solar/Wind Harmer
0.31
963401AG1-189 GEN
Solar/Wind Harmer
0.595
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207445AB1-138_GEN
Solar/Wind Harmer
0.15
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.311
20720628TIN_W1-124
Solar/Wind Harmer
0.25
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233970AC1-092 C
Solar/Wind Harmer
0.927
228400MICK 1CT
Adder
3.642
219766PARADISE C
Solar/Wind Harmer
0.096
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.86
228260V4-054C
Solar/Wind Harmer
0.303
228206SHRMN CT
Adder
4.831
219348LDSOLAR C
Solar/Wind Harmer
0.175
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.809
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
228729W2-030 C
Solar/Wind Harmer
0.165
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
20716028EGP_W2-019
Solar/Wind Harmer
0.124
207522AF2-254 C
Solar/Wind Harmer
0.384
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715828PEM_W1-120
Solar/Wind Harmer
0.142
219276PARKLANDSO C
Solar/Wind Harmer
0.122
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.86
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
972275AH1-722 GEN
Adder
7.525
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.302
208909MACR G3
Adder
32.158
20716228APLW2-078
Solar/Wind Harmer
0.221
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.14
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.112
20676128MHD_W3-029
Solar/Wind Harmer
0.114
213508CON10-11
50/50
0.998
213508CON10-11
50/50
0.998
213518CONOW8-9
50/50
0.998
213518CONOW8-9
50/50
0.998
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.44
213587EDDYSTN3
Adder
31.412
233982AB2-133 GEN
Solar/Wind Harmer
2.006
233930AB2-032 GEN
Solar/Wind Harmer
0.342
232436AB1-176 C
Solar/Wind Harmer
0.092
234014AF1-036_GEN
Solar/Wind Harmer
1.085
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
232910NRG_G1
Adder
3.244
234041AC1-190 GEN
Solar/Wind Harmer
3.31
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.467
233952AC2-187 GEN
Solar/Wind Harmer
0.409
233954AC2-188 GEN
Solar/Wind Harmer
0.409
233994AC2-023 GEN
Solar/Wind Harmer
0.976
232428Y3-058 C
Solar/Wind Harmer
0.303
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.711
232410W1-006 C
Solar/Wind Harmer
0.362
232918OH NUG7
Adder
3.175
232905CHERITON_25
Adder
0.888
231940T-011
Adder
0.269
232899W1-062
Adder
3.395
233971AC1-093 C
Solar/Wind Harmer
0.88
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.244
228307PCLP GT
Adder
3.695
228351V2-046C
Solar/Wind Harmer
0.605
230511AF1-262
Solar/Wind Harmer
0.054
228201CARL#2CT
Adder
2.031
228200CARL#1CT
Adder
1.931
228251CARLLS#4
Adder
0.186
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
213535CROYDN11
Adder
3.003
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
219607WPEMNERT C
Solar/Wind Harmer
0.122
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.388
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.121
20636128O CRK C2
Adder
1.69
207459AE1-142 C O1
Solar/Wind Harmer
0.274
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20714828MDF_W3-079
Solar/Wind Harmer
0.078
20641628MLH_W1-032
Solar/Wind Harmer
0.073
217197RE CRAN C
Solar/Wind Harmer
0.135
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.196
924131AB2-057 GEN
Solar/Wind Harmer
0.252
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.719
20635128RRCT3&4
Adder
2.371
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
20675428EAM_W2-061
Solar/Wind Harmer
0.045
223401AF1-299 GEN
Solar/Wind Helper
0.272
223402AF1-300 C
Solar/Wind Helper
0.272
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.552
233935AB2-179 C
Solar/Wind Harmer
1.159
213497CHSTR7-9
Adder
1.074
233933AB2-153 GEN
Solar/Wind Harmer
0.462
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.416
233987AB2-037 GEN
Solar/Wind Harmer
4.192
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.964
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.324
233997TMININ_4.2
Solar/Wind Harmer
0.361
232406W1-004 FULL
Solar/Wind Harmer
0.362
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
232921TASLEY2G
Adder
1.868
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.873
970695AG2-447 GEN
Solar/Wind Harmer
1.239
233939AC1-091 C
Solar/Wind Harmer
0.927
233972AC1-094 C
Solar/Wind Harmer
0.745
213815MOSER1-3
Adder
1.097
219914AD2-027 C
Solar/Wind Harmer
0.184
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.227
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20716428NHV_W2-082
Solar/Wind Harmer
0.476
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20636028O CRK C1
Adder
1.854
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963391AG1-188 GEN
Solar/Wind Harmer
0.98
971667AH1-334 GEN
Solar/Wind Harmer
0.715
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.251
219612MATRIX C
Solar/Wind Harmer
0.046
20716928W4-060COL
Solar/Wind Harmer
0.175
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
217213AMBOY SO C
Solar/Wind Harmer
0.03
219249CENTRALDIV C
Solar/Wind Harmer
0.009
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20673728F2S_V4-070
Solar/Wind Harmer
0.043
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
VTFLTFEXP_VFT->PJM
CMTX
31.565
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.608
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.956
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.616
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.439
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.039
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.49 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:679.08
MW Contribution:
1.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.445
231917EM10
Adder
1.009
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233918AB1-142 GEN
Solar/Wind Harmer
0.407
233944AB2-135 GEN
Solar/Wind Harmer
2.121
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213514CONOW1-2
50/50
0.552
231919CHRIST1
Adder
1.883
231920CHRIST2
Adder
1.841
233915AB1-141 GEN
Solar/Wind Harmer
0.407
233968AD2-076_GEN
Solar/Wind Harmer
2.659
970597AG2-380 GEN
Solar/Wind Harmer
1.67
231906DC3 NUG
Adder
5.531
231902DC CT7
Adder
4.422
231907DC10
Adder
1.381
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.99
213957STHWK3-4
Adder
0.99
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.85
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.353
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232912OH NUG1
Adder
3.198
232913OH NUG2
Adder
3.155
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.136
232904IR4
Adder
29.032
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
219137THOSOLAR C
Solar/Wind Harmer
0.376
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.189
230434AG1-499 GEN
Solar/Wind Harmer
0.174
972141AH1-641 GEN
Solar/Wind Harmer
0.858
230430AE1-229_GEN
Solar/Wind Harmer
8.531
219615MILLCREEK C
Solar/Wind Harmer
0.071
228728W1-130C
Solar/Wind Harmer
0.195
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219224BRL12CT4
Adder
2.608
230422AE1-104_GEN1
Solar/Wind Harmer
9.704
230425AE1-104_GEN2
Solar/Wind Harmer
9.704
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
207487AE2-000G4
Solar/Wind Harmer
8.265
207497AE2-000G2
Solar/Wind Harmer
8.265
207500AE2-000G1
Solar/Wind Harmer
8.265
207507AE2-000G3
Solar/Wind Harmer
8.265
971189AH1-054 GEN
Solar/Wind Harmer
0.31
963401AG1-189 GEN
Solar/Wind Harmer
0.595
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207445AB1-138_GEN
Solar/Wind Harmer
0.15
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.311
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20716228APLW2-078
Solar/Wind Harmer
0.222
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20635928PARLN3&4
Adder
1.807
20675528CPH_W2-050
Solar/Wind Harmer
0.14
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.112
20676128MHD_W3-029
Solar/Wind Harmer
0.114
213958STHWK5-6
Adder
0.99
232902EASTMUNI
Adder
4.962
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.028
233996TM1833_GEN
Solar/Wind Harmer
0.361
233998TM1NIN_3.36
Solar/Wind Harmer
0.361
232404W1-003 C
Solar/Wind Harmer
0.362
232408W1-005 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.184
232915OH NUG4
Adder
3.177
234033AF1-007_GEN
Solar/Wind Harmer
13.356
972177AH1-672 GEN
Solar/Wind Harmer
4.817
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.258
232901NORTHST
Adder
2.902
233970AC1-092 C
Solar/Wind Harmer
0.928
228400MICK 1CT
Adder
3.643
219766PARADISE C
Solar/Wind Harmer
0.096
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.861
228260V4-054C
Solar/Wind Harmer
0.303
228206SHRMN CT
Adder
4.833
219348LDSOLAR C
Solar/Wind Harmer
0.175
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.817
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
228729W2-030 C
Solar/Wind Harmer
0.165
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
20716028EGP_W2-019
Solar/Wind Harmer
0.124
207522AF2-254 C
Solar/Wind Harmer
0.384
20717128DIX_Z2-102
Solar/Wind Harmer
0.353
20715828PEM_W1-120
Solar/Wind Harmer
0.142
219276PARKLANDSO C
Solar/Wind Harmer
0.122
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.807
20635028RRCT1&2
Adder
2.861
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
972275AH1-722 GEN
Adder
7.526
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.302
208909MACR G3
Adder
32.163
213508CON10-11
50/50
0.998
213508CON10-11
50/50
0.998
213518CONOW8-9
50/50
0.998
213518CONOW8-9
50/50
0.998
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.446
213587EDDYSTN3
Adder
31.419
233982AB2-133 GEN
Solar/Wind Harmer
2.006
233930AB2-032 GEN
Solar/Wind Harmer
0.342
232436AB1-176 C
Solar/Wind Harmer
0.092
234014AF1-036_GEN
Solar/Wind Harmer
1.085
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.868
232910NRG_G1
Adder
3.245
234041AC1-190 GEN
Solar/Wind Harmer
3.312
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.468
233952AC2-187 GEN
Solar/Wind Harmer
0.409
233954AC2-188 GEN
Solar/Wind Harmer
0.409
233994AC2-023 GEN
Solar/Wind Harmer
0.976
232428Y3-058 C
Solar/Wind Harmer
0.303
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.712
232410W1-006 C
Solar/Wind Harmer
0.362
232918OH NUG7
Adder
3.177
232905CHERITON_25
Adder
0.888
231940T-011
Adder
0.27
232899W1-062
Adder
3.396
233971AC1-093 C
Solar/Wind Harmer
0.881
972233AH1-701 GEN
Adder
1.292
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.244
228307PCLP GT
Adder
3.696
228351V2-046C
Solar/Wind Harmer
0.605
230511AF1-262
Solar/Wind Harmer
0.054
228201CARL#2CT
Adder
2.032
228200CARL#1CT
Adder
1.932
228251CARLLS#4
Adder
0.186
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
213535CROYDN11
Adder
3.004
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
219607WPEMNERT C
Solar/Wind Harmer
0.122
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.388
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.121
20636128O CRK C2
Adder
1.691
207459AE1-142 C O1
Solar/Wind Harmer
0.274
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20714828MDF_W3-079
Solar/Wind Harmer
0.078
20641628MLH_W1-032
Solar/Wind Harmer
0.073
217197RE CRAN C
Solar/Wind Harmer
0.135
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.196
924131AB2-057 GEN
Solar/Wind Harmer
0.253
20635028RRCT1&2
Adder
2.817
20635128RRCT3&4
Adder
2.719
20635128RRCT3&4
Adder
2.372
218418LINDEN_G5
Adder
4.094
218419LINDEN_G6
Adder
4.094
972260AH1-715 GEN1
Adder
3.278
20675428EAM_W2-061
Solar/Wind Harmer
0.045
223401AF1-299 GEN
Solar/Wind Helper
0.272
223402AF1-300 C
Solar/Wind Helper
0.272
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.552
233935AB2-179 C
Solar/Wind Harmer
1.159
213497CHSTR7-9
Adder
1.074
233933AB2-153 GEN
Solar/Wind Harmer
0.462
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.416
233987AB2-037 GEN
Solar/Wind Harmer
4.194
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.97
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.325
233997TMININ_4.2
Solar/Wind Harmer
0.361
232406W1-004 FULL
Solar/Wind Harmer
0.362
232914OH NUG3
Adder
3.198
232916OH NUG5
Adder
3.198
232921TASLEY2G
Adder
1.869
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.874
970695AG2-447 GEN
Solar/Wind Harmer
1.24
233939AC1-091 C
Solar/Wind Harmer
0.928
233972AC1-094 C
Solar/Wind Harmer
0.745
213815MOSER1-3
Adder
1.097
219914AD2-027 C
Solar/Wind Harmer
0.184
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.227
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20716428NHV_W2-082
Solar/Wind Harmer
0.476
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20636028O CRK C1
Adder
1.854
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963391AG1-188 GEN
Solar/Wind Harmer
0.98
971667AH1-334 GEN
Solar/Wind Harmer
0.715
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.251
219612MATRIX C
Solar/Wind Harmer
0.046
20716928W4-060COL
Solar/Wind Harmer
0.175
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
217213AMBOY SO C
Solar/Wind Harmer
0.03
219249CENTRALDIV C
Solar/Wind Harmer
0.009
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20673728F2S_V4-070
Solar/Wind Harmer
0.043
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
VTFLTFEXP_VFT->PJM
CMTX
31.572
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.608
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.617
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.957
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.442
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.041
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.45 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:678.84
MW Contribution:
1.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233918AB1-142 GEN
Solar/Wind Harmer
0.407
233944AB2-135 GEN
Solar/Wind Harmer
2.12
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.99
232902EASTMUNI
Adder
4.959
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.027
233996TM1833_GEN
Solar/Wind Harmer
0.361
233998TM1NIN_3.36
Solar/Wind Harmer
0.361
232404W1-003 C
Solar/Wind Harmer
0.362
232408W1-005 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.175
234033AF1-007_GEN
Solar/Wind Harmer
13.348
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233970AC1-092 C
Solar/Wind Harmer
0.927
228400MICK 1CT
Adder
3.642
219766PARADISE C
Solar/Wind Harmer
0.096
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.86
228260V4-054C
Solar/Wind Harmer
0.303
228206SHRMN CT
Adder
4.831
219348LDSOLAR C
Solar/Wind Harmer
0.175
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.809
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
228729W2-030 C
Solar/Wind Harmer
0.165
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
20716028EGP_W2-019
Solar/Wind Harmer
0.124
207522AF2-254 C
Solar/Wind Harmer
0.384
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715828PEM_W1-120
Solar/Wind Harmer
0.142
219276PARKLANDSO C
Solar/Wind Harmer
0.122
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.86
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
213514CONOW1-2
50/50
0.552
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
233915AB1-141 GEN
Solar/Wind Harmer
0.407
233968AD2-076_GEN
Solar/Wind Harmer
2.658
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.42
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.849
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.353
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.135
232904IR4
Adder
29.017
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.552
233935AB2-179 C
Solar/Wind Harmer
1.159
213497CHSTR7-9
Adder
1.074
233933AB2-153 GEN
Solar/Wind Harmer
0.462
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.416
233987AB2-037 GEN
Solar/Wind Harmer
4.192
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.964
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.324
233997TMININ_4.2
Solar/Wind Harmer
0.361
232406W1-004 FULL
Solar/Wind Harmer
0.362
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
232921TASLEY2G
Adder
1.868
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.873
970695AG2-447 GEN
Solar/Wind Harmer
1.239
233939AC1-091 C
Solar/Wind Harmer
0.927
233972AC1-094 C
Solar/Wind Harmer
0.745
213815MOSER1-3
Adder
1.097
219914AD2-027 C
Solar/Wind Harmer
0.184
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.227
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20716428NHV_W2-082
Solar/Wind Harmer
0.476
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20636028O CRK C1
Adder
1.854
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963391AG1-188 GEN
Solar/Wind Harmer
0.98
971667AH1-334 GEN
Solar/Wind Harmer
0.715
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.251
219612MATRIX C
Solar/Wind Harmer
0.046
20716928W4-060COL
Solar/Wind Harmer
0.175
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
217213AMBOY SO C
Solar/Wind Harmer
0.03
219249CENTRALDIV C
Solar/Wind Harmer
0.009
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20673728F2S_V4-070
Solar/Wind Harmer
0.043
219137THOSOLAR C
Solar/Wind Harmer
0.375
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.188
230434AG1-499 GEN
Solar/Wind Harmer
0.174
972141AH1-641 GEN
Solar/Wind Harmer
0.858
230430AE1-229_GEN
Solar/Wind Harmer
8.528
219615MILLCREEK C
Solar/Wind Harmer
0.071
228728W1-130C
Solar/Wind Harmer
0.195
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219224BRL12CT4
Adder
2.608
230422AE1-104_GEN1
Solar/Wind Harmer
9.701
230425AE1-104_GEN2
Solar/Wind Harmer
9.701
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
207487AE2-000G4
Solar/Wind Harmer
8.262
207497AE2-000G2
Solar/Wind Harmer
8.262
207500AE2-000G1
Solar/Wind Harmer
8.262
207507AE2-000G3
Solar/Wind Harmer
8.262
971189AH1-054 GEN
Solar/Wind Harmer
0.31
963401AG1-189 GEN
Solar/Wind Harmer
0.595
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207445AB1-138_GEN
Solar/Wind Harmer
0.15
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.311
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20716228APLW2-078
Solar/Wind Harmer
0.221
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.14
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.112
20676128MHD_W3-029
Solar/Wind Harmer
0.114
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
213508CON10-11
50/50
0.998
213508CON10-11
50/50
0.998
213518CONOW8-9
50/50
0.998
213518CONOW8-9
50/50
0.998
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.44
213587EDDYSTN3
Adder
31.412
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
972275AH1-722 GEN
Adder
7.525
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.302
208909MACR G3
Adder
32.158
233982AB2-133 GEN
Solar/Wind Harmer
2.006
233930AB2-032 GEN
Solar/Wind Harmer
0.342
232436AB1-176 C
Solar/Wind Harmer
0.092
234014AF1-036_GEN
Solar/Wind Harmer
1.085
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
232910NRG_G1
Adder
3.244
234041AC1-190 GEN
Solar/Wind Harmer
3.31
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.467
233952AC2-187 GEN
Solar/Wind Harmer
0.409
233954AC2-188 GEN
Solar/Wind Harmer
0.409
233994AC2-023 GEN
Solar/Wind Harmer
0.976
232428Y3-058 C
Solar/Wind Harmer
0.303
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.711
232410W1-006 C
Solar/Wind Harmer
0.362
232918OH NUG7
Adder
3.175
232905CHERITON_25
Adder
0.888
231940T-011
Adder
0.269
232899W1-062
Adder
3.395
233971AC1-093 C
Solar/Wind Harmer
0.88
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.244
228307PCLP GT
Adder
3.695
228351V2-046C
Solar/Wind Harmer
0.605
230511AF1-262
Solar/Wind Harmer
0.054
228201CARL#2CT
Adder
2.031
228200CARL#1CT
Adder
1.931
228251CARLLS#4
Adder
0.186
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
213535CROYDN11
Adder
3.003
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
219607WPEMNERT C
Solar/Wind Harmer
0.122
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.388
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.121
20636128O CRK C2
Adder
1.69
207459AE1-142 C O1
Solar/Wind Harmer
0.274
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20714828MDF_W3-079
Solar/Wind Harmer
0.078
20641628MLH_W1-032
Solar/Wind Harmer
0.073
217197RE CRAN C
Solar/Wind Harmer
0.135
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.196
924131AB2-057 GEN
Solar/Wind Harmer
0.252
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.719
20635128RRCT3&4
Adder
2.371
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
20675428EAM_W2-061
Solar/Wind Harmer
0.045
223401AF1-299 GEN
Solar/Wind Helper
0.272
223402AF1-300 C
Solar/Wind Helper
0.272
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
VTFLTFEXP_VFT->PJM
CMTX
31.565
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.608
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.956
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.616
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.439
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.039
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.79 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:675.02
MW Contribution:
1.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213515CONOW3-4
50/50
0.731
213516CONOW5-6
50/50
0.548
233935AB2-179 C
Solar/Wind Harmer
1.145
213497CHSTR7-9
Adder
1.06
233933AB2-153 GEN
Solar/Wind Harmer
0.456
232422X3-066 FULL
Solar/Wind Harmer
0.099
213958STHWK5-6
Adder
0.976
232417X3-008 C
Solar/Wind Harmer
0.411
233987AB2-037 GEN
Solar/Wind Harmer
4.137
233964AF2-378 GEN
Solar/Wind Harmer
0.046
232907VN8
Adder
10.819
233950AC2-186 GEN
Solar/Wind Harmer
0.202
233923SMA
Solar/Wind Harmer
1.306
233997TMININ_4.2
Solar/Wind Harmer
0.356
232406W1-004 FULL
Solar/Wind Harmer
0.357
232914OH NUG3
Adder
3.153
232916OH NUG5
Adder
3.153
232921TASLEY2G
Adder
1.843
232434Z2-077 GEN
Solar/Wind Harmer
0.089
213560DLW11-12
Adder
0.898
233973AC2-185 C
Solar/Wind Harmer
1.848
970695AG2-447 GEN
Solar/Wind Harmer
1.222
233939AC1-091 C
Solar/Wind Harmer
0.915
233972AC1-094 C
Solar/Wind Harmer
0.734
213815MOSER1-3
Adder
1.08
219914AD2-027 C
Solar/Wind Harmer
0.181
219921AF1-264
Solar/Wind Harmer
0.043
219623KINSLEYBEA C
Solar/Wind Harmer
0.128
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.055
228711V2-041C
Solar/Wind Harmer
0.172
219221BRL12CT1
Adder
2.568
219223BRL12CT3
Adder
2.568
219688LUMSOLAR_S C
Solar/Wind Harmer
0.058
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.05
959561AF2-247 GEN
Solar/Wind Harmer
0.135
219114HARTZY_C
Solar/Wind Harmer
0.224
219727YARDVSOLFA C
Solar/Wind Harmer
0.242
20716428NHV_W2-082
Solar/Wind Harmer
0.468
20715728PEM_W1-119
Solar/Wind Harmer
0.14
20636028O CRK C1
Adder
1.823
20714928UPF_X1-085
Solar/Wind Harmer
0.105
963391AG1-188 GEN
Solar/Wind Harmer
0.964
971667AH1-334 GEN
Solar/Wind Harmer
0.703
213514CONOW1-2
50/50
0.548
231919CHRIST1
Adder
1.859
231920CHRIST2
Adder
1.818
233915AB1-141 GEN
Solar/Wind Harmer
0.402
233968AD2-076_GEN
Solar/Wind Harmer
2.624
970597AG2-380 GEN
Solar/Wind Harmer
1.648
231906DC3 NUG
Adder
5.458
231902DC CT7
Adder
4.364
231907DC10
Adder
1.363
213942SCHUYLKILL
Adder
1.288
213942SCHUYLKILL
Adder
0.985
213957STHWK3-4
Adder
0.976
213957STHWK3-4
Adder
0.976
232813VAUGHN
Adder
0.216
233955AB2-172 GEN
Solar/Wind Harmer
1.825
233940AF2-379 C
Solar/Wind Harmer
0.067
971195AH1-057 GEN
Solar/Wind Harmer
0.349
233901CHERRYDALE C
Solar/Wind Harmer
0.402
232912OH NUG1
Adder
3.153
232913OH NUG2
Adder
3.111
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.12
232904IR4
Adder
28.628
213561DLWR9-10
Adder
1.175
213561DLWR9-10
Adder
0.898
219137THOSOLAR C
Solar/Wind Harmer
0.37
219258KINSLEYDEP C
Solar/Wind Harmer
0.098
964001AG1-254 GEN
Solar/Wind Harmer
2.156
230434AG1-499 GEN
Solar/Wind Harmer
0.171
972141AH1-641 GEN
Solar/Wind Harmer
0.845
230430AE1-229_GEN
Solar/Wind Harmer
8.401
219615MILLCREEK C
Solar/Wind Harmer
0.07
228728W1-130C
Solar/Wind Harmer
0.192
230407AD2-065 C
Solar/Wind Harmer
0.038
970453AG2-297 GEN
Solar/Wind Harmer
0.788
219610FLORENCE C
Solar/Wind Harmer
0.398
219224BRL12CT4
Adder
2.568
230422AE1-104_GEN1
Solar/Wind Harmer
9.553
230425AE1-104_GEN2
Solar/Wind Harmer
9.553
227927V4-067C
Solar/Wind Harmer
0.056
213611FALLS1-3
Adder
0.999
213611FALLS1-3
Adder
0.999
20720728JCB_W1-129
Solar/Wind Harmer
0.079
20715028HAN_X4-015
Solar/Wind Harmer
0.079
207487AE2-000G4
Solar/Wind Harmer
8.126
207497AE2-000G2
Solar/Wind Harmer
8.126
207500AE2-000G1
Solar/Wind Harmer
8.126
207507AE2-000G3
Solar/Wind Harmer
8.126
971189AH1-054 GEN
Solar/Wind Harmer
0.305
963401AG1-189 GEN
Solar/Wind Harmer
0.585
970025AG2-016 GEN
Solar/Wind Harmer
0.729
207445AB1-138_GEN
Solar/Wind Harmer
0.148
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.306
20720628TIN_W1-124
Solar/Wind Harmer
0.246
20716228APLW2-078
Solar/Wind Harmer
0.218
971521AH1-258 GEN
Solar/Wind Harmer
0.663
20635928PARLN3&4
Adder
1.774
20675528CPH_W2-050
Solar/Wind Harmer
0.137
218526CNTRALGAS2 C
Solar/Wind Harmer
0.088
20673828FLE_V3-070
Solar/Wind Harmer
0.11
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.247
219612MATRIX C
Solar/Wind Harmer
0.045
20716928W4-060COL
Solar/Wind Harmer
0.172
20635828PARLN1&2
Adder
0.803
20635928PARLN3&4
Adder
0.803
217213AMBOY SO C
Solar/Wind Harmer
0.03
208835TUHI V3-051
Solar/Wind Helper
0.01
213514CONOW1-2
50/50
0.731
213515CONOW3-4
50/50
0.731
231918WEST 1
Adder
1.427
231917EM10
Adder
0.996
213497CHSTR7-9
Adder
1.06
213497CHSTR7-9
Adder
1.06
233918AB1-142 GEN
Solar/Wind Harmer
0.402
233944AB2-135 GEN
Solar/Wind Harmer
2.094
234012AE2-112_GEN
Solar/Wind Harmer
0.91
213958STHWK5-6
Adder
0.976
232902EASTMUNI
Adder
4.895
232426Y1-080 FULL
Solar/Wind Harmer
0.069
232919VN10
Adder
1.013
233996TM1833_GEN
Solar/Wind Harmer
0.356
233998TM1NIN_3.36
Solar/Wind Harmer
0.356
232404W1-003 C
Solar/Wind Harmer
0.357
232408W1-005 C
Solar/Wind Harmer
0.357
232917OH NUG6
Adder
3.139
232915OH NUG4
Adder
3.132
234033AF1-007_GEN
Solar/Wind Harmer
13.17
972177AH1-672 GEN
Solar/Wind Harmer
4.75
213560DLW11-12
Adder
0.898
232900DEMECSMY
Adder
3.212
232901NORTHST
Adder
2.861
233970AC1-092 C
Solar/Wind Harmer
0.915
228400MICK 1CT
Adder
3.589
219766PARADISE C
Solar/Wind Harmer
0.095
219907AC1-030 C
Solar/Wind Harmer
0.041
970997AG2-616 GEN
Solar/Wind Harmer
2.818
228260V4-054C
Solar/Wind Harmer
0.299
228206SHRMN CT
Adder
4.758
219348LDSOLAR C
Solar/Wind Harmer
0.172
219222BRL12CT2
Adder
2.568
228732V1-021 C
Adder
0.054
972251AH1-710 GEN
Adder
13.604
219686LUMSOLAR_N C
Solar/Wind Harmer
0.057
228729W2-030 C
Solar/Wind Harmer
0.163
214194N WALES4
Adder
0.241
213611FALLS1-3
Adder
0.999
20716028EGP_W2-019
Solar/Wind Harmer
0.122
207522AF2-254 C
Solar/Wind Harmer
0.378
20717128DIX_Z2-102
Solar/Wind Harmer
0.347
20715828PEM_W1-120
Solar/Wind Harmer
0.14
219276PARKLANDSO C
Solar/Wind Harmer
0.12
963711AG1-223 GEN
Solar/Wind Harmer
0.373
20714528FRN_Y2-051
Solar/Wind Harmer
0.074
219680HOPEWELLV C1
Solar/Wind Harmer
0.019
20715228NPK_W1-113
Solar/Wind Harmer
0.106
20720528MAN_W1-024
Solar/Wind Harmer
0.062
20720428HOL_W1-112
Solar/Wind Harmer
0.084
20635828PARLN1&2
Adder
1.774
20635028RRCT1&2
Adder
2.809
218524CNTRALGAS1 C
Solar/Wind Harmer
0.087
218440SUMMTASSOC C
Solar/Wind Harmer
0.03
218428ETC SOLAR C
Solar/Wind Harmer
0.008
219908AB1-139 C
Solar/Wind Harmer
0.09
219919AE1-041 FULL
Solar/Wind Harmer
0.01
208909MACR G3
Adder
31.435
208835TUHI V3-051
Solar/Wind Helper
0.01
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213516CONOW5-6
50/50
0.731
213517CONOW7
50/50
0.731
213589EDDYSTN4
Adder
31.045
213587EDDYSTN3
Adder
31.018
233982AB2-133 GEN
Solar/Wind Harmer
1.981
233930AB2-032 GEN
Solar/Wind Harmer
0.338
232436AB1-176 C
Solar/Wind Harmer
0.091
234014AF1-036_GEN
Solar/Wind Harmer
1.071
232424Y1-079 C
Solar/Wind Harmer
0.218
233984AB2-036 GEN
Solar/Wind Harmer
4.803
232910NRG_G1
Adder
3.201
234041AC1-190 GEN
Solar/Wind Harmer
3.267
234036AF2-325 C
Solar/Wind Harmer
0.333
233946AB2-136 GEN
Solar/Wind Harmer
1.448
233952AC2-187 GEN
Solar/Wind Harmer
0.404
233954AC2-188 GEN
Solar/Wind Harmer
0.404
233994AC2-023 GEN
Solar/Wind Harmer
0.963
232428Y3-058 C
Solar/Wind Harmer
0.299
234015AF2-250 C
Solar/Wind Harmer
0.043
232926CRISFLD1
Adder
0.702
232410W1-006 C
Solar/Wind Harmer
0.357
232918OH NUG7
Adder
3.132
232905CHERITON_25
Adder
0.876
231940T-011
Adder
0.266
232899W1-062
Adder
3.349
233971AC1-093 C
Solar/Wind Harmer
0.868
972233AH1-701 GEN
Adder
1.272
213815MOSER1-3
Adder
1.08
213815MOSER1-3
Adder
1.08
219904AC1-010 C
Solar/Wind Harmer
0.114
219912AD2-042 GEN
Solar/Wind Harmer
0.24
228307PCLP GT
Adder
3.641
228351V2-046C
Solar/Wind Harmer
0.596
230511AF1-262
Solar/Wind Harmer
0.053
228201CARL#2CT
Adder
2
228200CARL#1CT
Adder
1.903
228251CARLLS#4
Adder
0.184
219906AC1-017 C
Solar/Wind Harmer
0.065
230433AD2-135 GEN
Solar/Wind Harmer
0.029
213535CROYDN11
Adder
2.957
219272CLEANLIGHT C
Solar/Wind Harmer
0.052
219607WPEMNERT C
Solar/Wind Harmer
0.12
219304NAMERICA C
Solar/Wind Harmer
0.089
219287REEVESEAST C
Solar/Wind Harmer
0.382
228754AB1-001 C
Solar/Wind Harmer
0.039
214067T20SOLAR
Solar/Wind Harmer
0.071
20720828JCB_W4-025
Solar/Wind Harmer
0.119
20636128O CRK C2
Adder
1.662
207459AE1-142 C O1
Solar/Wind Harmer
0.269
20628028LAKEHURS
Adder
0.243
219817TRENTONSOL C
Solar/Wind Harmer
0.28
20714828MDF_W3-079
Solar/Wind Harmer
0.077
20641628MLH_W1-032
Solar/Wind Harmer
0.072
217197RE CRAN C
Solar/Wind Harmer
0.133
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.192
924131AB2-057 GEN
Solar/Wind Harmer
0.248
20635028RRCT1&2
Adder
2.766
20635128RRCT3&4
Adder
2.67
20635128RRCT3&4
Adder
2.329
223401AF1-299 GEN
Solar/Wind Helper
0.284
223402AF1-300 C
Solar/Wind Helper
0.284
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.015
VTFLTFEXP_VFT->PJM
CMTX
30.969
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.819
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.553
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.863
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.215
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.757
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.0 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:641.56
MW Contribution:
1.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.553
231919CHRIST1
Adder
1.889
231920CHRIST2
Adder
1.847
233915AB1-141 GEN
Solar/Wind Harmer
0.408
233968AD2-076_GEN
Solar/Wind Harmer
2.668
970597AG2-380 GEN
Solar/Wind Harmer
1.675
231906DC3 NUG
Adder
5.55
231902DC CT7
Adder
4.437
231907DC10
Adder
1.386
213942SCHUYLKILL
Adder
1.31
213942SCHUYLKILL
Adder
1.002
213957STHWK3-4
Adder
0.993
213957STHWK3-4
Adder
0.993
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.857
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.355
233901CHERRYDALE C
Solar/Wind Harmer
0.409
232912OH NUG1
Adder
3.21
232913OH NUG2
Adder
3.167
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.14
232904IR4
Adder
29.142
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.45
231917EM10
Adder
1.012
213497CHSTR7-9
Adder
1.078
213497CHSTR7-9
Adder
1.078
233918AB1-142 GEN
Solar/Wind Harmer
0.408
233944AB2-135 GEN
Solar/Wind Harmer
2.129
234012AE2-112_GEN
Solar/Wind Harmer
0.926
213958STHWK5-6
Adder
0.993
232902EASTMUNI
Adder
4.98
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.031
233996TM1833_GEN
Solar/Wind Harmer
0.363
233998TM1NIN_3.36
Solar/Wind Harmer
0.363
232404W1-003 C
Solar/Wind Harmer
0.363
213508CON10-11
50/50
0.999
213508CON10-11
50/50
0.999
213518CONOW8-9
50/50
0.999
232408W1-005 C
Solar/Wind Harmer
0.363
232917OH NUG6
Adder
3.196
232915OH NUG4
Adder
3.188
234033AF1-007_GEN
Solar/Wind Harmer
13.406
972177AH1-672 GEN
Solar/Wind Harmer
4.835
213560DLW11-12
Adder
0.915
232900DEMECSMY
Adder
3.27
232901NORTHST
Adder
2.913
233970AC1-092 C
Solar/Wind Harmer
0.931
228400MICK 1CT
Adder
3.659
219766PARADISE C
Solar/Wind Harmer
0.097
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.874
228260V4-054C
Solar/Wind Harmer
0.305
228206SHRMN CT
Adder
4.855
219348LDSOLAR C
Solar/Wind Harmer
0.176
219222BRL12CT2
Adder
2.621
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.879
219686LUMSOLAR_N C
Solar/Wind Harmer
0.059
228729W2-030 C
Solar/Wind Harmer
0.166
214194N WALES4
Adder
0.246
213611FALLS1-3
Adder
1.02
20716028EGP_W2-019
Solar/Wind Harmer
0.125
207522AF2-254 C
Solar/Wind Harmer
0.386
20717128DIX_Z2-102
Solar/Wind Harmer
0.354
20715828PEM_W1-120
Solar/Wind Harmer
0.143
219276PARKLANDSO C
Solar/Wind Harmer
0.123
963711AG1-223 GEN
Solar/Wind Harmer
0.381
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.817
20635028RRCT1&2
Adder
2.878
218524CNTRALGAS1 C
Solar/Wind Harmer
0.09
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.092
219919AE1-041 FULL
Solar/Wind Harmer
0.01
972275AH1-722 GEN
Adder
7.573
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.304
208909MACR G3
Adder
32.417
213561DLWR9-10
Adder
1.197
213561DLWR9-10
Adder
0.915
219137THOSOLAR C
Solar/Wind Harmer
0.377
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.199
230434AG1-499 GEN
Solar/Wind Harmer
0.175
972141AH1-641 GEN
Solar/Wind Harmer
0.862
230430AE1-229_GEN
Solar/Wind Harmer
8.569
219615MILLCREEK C
Solar/Wind Harmer
0.071
228728W1-130C
Solar/Wind Harmer
0.196
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.804
219610FLORENCE C
Solar/Wind Harmer
0.407
219224BRL12CT4
Adder
2.621
230422AE1-104_GEN1
Solar/Wind Harmer
9.749
230425AE1-104_GEN2
Solar/Wind Harmer
9.749
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.02
213611FALLS1-3
Adder
1.02
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
207487AE2-000G4
Solar/Wind Harmer
8.308
207497AE2-000G2
Solar/Wind Harmer
8.308
207500AE2-000G1
Solar/Wind Harmer
8.308
207507AE2-000G3
Solar/Wind Harmer
8.308
971189AH1-054 GEN
Solar/Wind Harmer
0.311
963401AG1-189 GEN
Solar/Wind Harmer
0.598
970025AG2-016 GEN
Solar/Wind Harmer
0.745
207445AB1-138_GEN
Solar/Wind Harmer
0.151
219620RIDERU C
Solar/Wind Harmer
0.015
20714428HOW_X1-037
Solar/Wind Harmer
0.313
20720628TIN_W1-124
Solar/Wind Harmer
0.252
20716228APLW2-078
Solar/Wind Harmer
0.223
971521AH1-258 GEN
Solar/Wind Harmer
0.679
20635928PARLN3&4
Adder
1.817
20675528CPH_W2-050
Solar/Wind Harmer
0.141
213518CONOW8-9
50/50
0.999
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.555
213587EDDYSTN3
Adder
31.528
233982AB2-133 GEN
Solar/Wind Harmer
2.013
233930AB2-032 GEN
Solar/Wind Harmer
0.344
232436AB1-176 C
Solar/Wind Harmer
0.093
234014AF1-036_GEN
Solar/Wind Harmer
1.089
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.885
232910NRG_G1
Adder
3.257
234041AC1-190 GEN
Solar/Wind Harmer
3.324
234036AF2-325 C
Solar/Wind Harmer
0.339
233946AB2-136 GEN
Solar/Wind Harmer
1.474
233952AC2-187 GEN
Solar/Wind Harmer
0.411
233954AC2-188 GEN
Solar/Wind Harmer
0.411
233994AC2-023 GEN
Solar/Wind Harmer
0.98
232428Y3-058 C
Solar/Wind Harmer
0.304
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.714
232410W1-006 C
Solar/Wind Harmer
0.363
232905CHERITON_25
Adder
0.892
232918OH NUG7
Adder
3.188
231940T-011
Adder
0.271
232899W1-062
Adder
3.409
233971AC1-093 C
Solar/Wind Harmer
0.884
972233AH1-701 GEN
Adder
1.297
213815MOSER1-3
Adder
1.102
213815MOSER1-3
Adder
1.102
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.245
228307PCLP GT
Adder
3.713
228351V2-046C
Solar/Wind Harmer
0.608
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.553
233935AB2-179 C
Solar/Wind Harmer
1.163
213497CHSTR7-9
Adder
1.078
233933AB2-153 GEN
Solar/Wind Harmer
0.464
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.993
232417X3-008 C
Solar/Wind Harmer
0.418
233987AB2-037 GEN
Solar/Wind Harmer
4.21
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
11.01
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.33
233997TMININ_4.2
Solar/Wind Harmer
0.363
232406W1-004 FULL
Solar/Wind Harmer
0.363
232921TASLEY2G
Adder
1.876
232914OH NUG3
Adder
3.21
232916OH NUG5
Adder
3.21
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.915
233973AC2-185 C
Solar/Wind Harmer
1.882
970695AG2-447 GEN
Solar/Wind Harmer
1.245
233939AC1-091 C
Solar/Wind Harmer
0.931
233972AC1-094 C
Solar/Wind Harmer
0.748
213815MOSER1-3
Adder
1.102
219914AD2-027 C
Solar/Wind Harmer
0.185
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.131
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.176
219221BRL12CT1
Adder
2.621
219223BRL12CT3
Adder
2.621
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.018
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.228
219727YARDVSOLFA C
Solar/Wind Harmer
0.247
20716428NHV_W2-082
Solar/Wind Harmer
0.478
20715728PEM_W1-119
Solar/Wind Harmer
0.143
20636028O CRK C1
Adder
1.864
20714928UPF_X1-085
Solar/Wind Harmer
0.108
963391AG1-188 GEN
Solar/Wind Harmer
0.985
971667AH1-334 GEN
Solar/Wind Harmer
0.719
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.252
219612MATRIX C
Solar/Wind Harmer
0.047
20716928W4-060COL
Solar/Wind Harmer
0.176
20635828PARLN1&2
Adder
0.823
20635928PARLN3&4
Adder
0.823
217213AMBOY SO C
Solar/Wind Harmer
0.031
219249CENTRALDIV C
Solar/Wind Harmer
0.01
207442AE1-156 GEN
Solar/Wind Harmer
0.178
20673728F2S_V4-070
Solar/Wind Harmer
0.043
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.113
20676128MHD_W3-029
Solar/Wind Harmer
0.114
20676428JCR_X2-075
Solar/Wind Harmer
0.081
218449LINSOLAR C
Solar/Wind Harmer
0.239
230511AF1-262
Solar/Wind Harmer
0.055
228201CARL#2CT
Adder
2.041
228200CARL#1CT
Adder
1.941
228251CARLLS#4
Adder
0.187
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
213535CROYDN11
Adder
3.018
219272CLEANLIGHT C
Solar/Wind Harmer
0.054
219607WPEMNERT C
Solar/Wind Harmer
0.123
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.39
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.122
20636128O CRK C2
Adder
1.7
207459AE1-142 C O1
Solar/Wind Harmer
0.276
20628028LAKEHURS
Adder
0.248
219817TRENTONSOL C
Solar/Wind Harmer
0.287
20714828MDF_W3-079
Solar/Wind Harmer
0.079
20641628MLH_W1-032
Solar/Wind Harmer
0.074
217197RE CRAN C
Solar/Wind Harmer
0.136
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.197
924131AB2-057 GEN
Solar/Wind Harmer
0.254
20635028RRCT1&2
Adder
2.834
20635128RRCT3&4
Adder
2.736
20635128RRCT3&4
Adder
2.386
218418LINDEN_G5
Adder
4.119
218419LINDEN_G6
Adder
4.119
972260AH1-715 GEN1
Adder
3.299
20675428EAM_W2-061
Solar/Wind Harmer
0.045
219036LINDEN_G7
Adder
3.972
219035LINDEN_G8
Adder
3.916
972261AH1-715 GEN2
Adder
3.803
223401AF1-299 GEN
Solar/Wind Helper
0.271
223402AF1-300 C
Solar/Wind Helper
0.271
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.015
VTFLTFEXP_VFT->PJM
CMTX
31.773
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.822
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.872
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.56
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.517
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.197
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.49 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:603.92
MW Contribution:
0.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.552
213893PHLISST1
50/50
1.346
231916EM3
50/50
0.419
231919CHRIST1
50/50
1.997
231920CHRIST2
50/50
1.953
231901EM4
50/50
0.845
213740LIBE_ST1
50/50
1.073
231505HR4
50/50
0.884
233915AB1-141 GEN
Solar/Wind Harmer
0.105
233968AD2-076_GEN
Solar/Wind Harmer
0.932
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.42
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.219
971195AH1-057 GEN
Solar/Wind Harmer
0.226
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
232432Z2-076 GEN
Solar/Wind Harmer
0.005
232920IR10
Adder
1.135
232904IR4
Adder
29.017
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
964001AG1-254 GEN
Solar/Wind Harmer
1.694
972141AH1-641 GEN
Solar/Wind Harmer
0.466
230430AE1-229_GEN
Solar/Wind Harmer
5.911
970453AG2-297 GEN
Solar/Wind Harmer
0.739
219224BRL12CT4
Adder
2.608
230422AE1-104_GEN1
Solar/Wind Harmer
3.894
230425AE1-104_GEN2
Solar/Wind Harmer
3.894
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
207487AE2-000G4
Solar/Wind Harmer
3.317
207497AE2-000G2
Solar/Wind Harmer
3.317
207500AE2-000G1
Solar/Wind Harmer
3.317
207507AE2-000G3
Solar/Wind Harmer
3.317
971189AH1-054 GEN
Solar/Wind Harmer
0.2
963401AG1-189 GEN
Solar/Wind Harmer
0.294
970025AG2-016 GEN
Solar/Wind Harmer
0.479
971521AH1-258 GEN
Solar/Wind Harmer
0.436
20635928PARLN3&4
Adder
1.806
218526CNTRALGAS2 C
Solar/Wind Harmer
0.186
213508CON10-11
50/50
0.998
213508CON10-11
50/50
0.998
213518CONOW8-9
50/50
0.998
213518CONOW8-9
50/50
0.998
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
231909HR2
50/50
0.61
231908HR1
50/50
0.607
231910HR3
50/50
0.607
213589EDDYSTN4
Adder
31.44
213587EDDYSTN3
Adder
31.412
233930AB2-032 GEN
Solar/Wind Harmer
0.394
234014AF1-036_GEN
Solar/Wind Harmer
0.932
233984AB2-036 GEN
Solar/Wind Harmer
2.839
232910NRG_G1
Adder
3.244
234041AC1-190 GEN
Solar/Wind Harmer
2.694
232926CRISFLD1
Adder
0.711
232410W1-006 C
Solar/Wind Harmer
0.234
232918OH NUG7
Adder
3.175
232905CHERITON_25
Adder
0.888
231940T-011
Adder
0.269
232899W1-062
Adder
3.395
233971AC1-093 C
Solar/Wind Harmer
0.624
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228307PCLP GT
Adder
3.695
228201CARL#2CT
Adder
2.031
228200CARL#1CT
Adder
1.931
228251CARLLS#4
Adder
0.186
213535CROYDN11
Adder
3.003
219304NAMERICA C
Solar/Wind Harmer
0.027
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
50/50
1.533
213889PHLISCT2
50/50
0.933
231917EM10
50/50
1.07
213738LIBE_CT1
50/50
0.777
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233918AB1-142 GEN
Solar/Wind Harmer
0.105
234012AE2-112_GEN
Solar/Wind Harmer
0.932
213958STHWK5-6
Adder
0.99
232902EASTMUNI
Adder
4.959
232919VN10
Adder
1.027
232404W1-003 C
Solar/Wind Harmer
0.234
232408W1-005 C
Solar/Wind Harmer
0.234
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.175
234033AF1-007_GEN
Solar/Wind Harmer
4.956
972177AH1-672 GEN
Solar/Wind Harmer
3.65
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233970AC1-092 C
Solar/Wind Harmer
0.624
228400MICK 1CT
Adder
3.642
970997AG2-616 GEN
Solar/Wind Harmer
2.152
228206SHRMN CT
Adder
4.831
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.809
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
207522AF2-254 C
Solar/Wind Harmer
0.248
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.86
218524CNTRALGAS1 C
Solar/Wind Harmer
0.184
972275AH1-722 GEN
Adder
7.525
207528AF2-192 GEN
Solar/Wind Harmer
0.171
208909MACR G3
Adder
32.158
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.552
213890PHLISCT3
50/50
0.933
213888PHLISCT1
50/50
0.933
213739LIBE_CT2
50/50
0.777
233935AB2-179 C
Solar/Wind Harmer
0.637
213497CHSTR7-9
Adder
1.074
232422X3-066 FULL
Solar/Wind Harmer
0.034
213958STHWK5-6
Adder
0.99
233987AB2-037 GEN
Solar/Wind Harmer
0
232907VN8
Adder
10.964
232406W1-004 FULL
Solar/Wind Harmer
0.234
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
232921TASLEY2G
Adder
1.868
232434Z2-077 GEN
Solar/Wind Harmer
0.015
213560DLW11-12
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
0.624
970695AG2-447 GEN
Solar/Wind Harmer
0.865
233939AC1-091 C
Solar/Wind Harmer
0.624
233972AC1-094 C
Solar/Wind Harmer
0.624
213815MOSER1-3
Adder
1.097
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
20636028O CRK C1
Adder
1.854
963391AG1-188 GEN
Solar/Wind Harmer
0.479
971667AH1-334 GEN
Solar/Wind Harmer
0.462
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
207442AE1-156 GEN
Solar/Wind Harmer
0.014
20636128O CRK C2
Adder
1.69
20628028LAKEHURS
Adder
0.247
20714828MDF_W3-079
Solar/Wind Harmer
0.025
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.719
20635128RRCT3&4
Adder
2.371
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
223401AF1-299 GEN
Solar/Wind Helper
0.272
223402AF1-300 C
Solar/Wind Helper
0.272
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
VTFLTFEXP_VFT->PJM
CMTX
31.565
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.608
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.616
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.956
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.439
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.039
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.22 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:4644.1
MW Contribution:
6.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200200DELTA2 CT1
50/50
6.893
200193DELTA CT2
50/50
3.851
200203Y1-065-STG
50/50
13.408
200055ROCKSP 4
50/50
4.842
233987AB2-037 GEN
Solar/Wind Harmer
21.579
232907VN8
Adder
56.823
233923SMA
Solar/Wind Harmer
6.912
233997TMININ_4.2
Solar/Wind Harmer
1.885
232406W1-004 FULL
Solar/Wind Harmer
1.891
232914OH NUG3
Adder
16.706
232916OH NUG5
Adder
16.706
232921TASLEY2G
Adder
9.764
232434Z2-077 GEN
Solar/Wind Harmer
0.473
233964AF2-378 GEN
Solar/Wind Harmer
0.241
232417X3-008 C
Solar/Wind Harmer
2.124
233973AC2-185 C
Solar/Wind Harmer
10.224
970695AG2-447 GEN
Solar/Wind Harmer
6.764
200202DELTA2 ST
50/50
11.673
200195DELTA ST
50/50
5.95
200052ROCKSP 1
50/50
4.871
200053ROCKSP 2
50/50
4.775
233901CHERRYDALE C
Solar/Wind Harmer
2.127
232912OH NUG1
Adder
16.706
232913OH NUG2
Adder
16.483
233940AF2-379 C
Solar/Wind Harmer
0.353
232904IR4
Adder
152.888
232432Z2-076 GEN
Solar/Wind Harmer
0.249
971195AH1-057 GEN
Solar/Wind Harmer
1.843
232920IR10
Adder
5.976
233955AB2-172 GEN
Solar/Wind Harmer
9.442
232813VAUGHN
Adder
1.107
233968AD2-076_GEN
Solar/Wind Harmer
12.392
970597AG2-380 GEN
Solar/Wind Harmer
7.782
231906DC3 NUG
Adder
26.105
231902DC CT7
Adder
20.869
231907DC10
Adder
6.517
233915AB1-141 GEN
Solar/Wind Harmer
1.84
231919CHRIST1
Adder
7.82
231920CHRIST2
Adder
7.647
970453AG2-297 GEN
Solar/Wind Harmer
4.023
972141AH1-641 GEN
Solar/Wind Harmer
4.122
230430AE1-229_GEN
Solar/Wind Harmer
40.959
964001AG1-254 GEN
Solar/Wind Harmer
10.423
230422AE1-104_GEN1
Solar/Wind Harmer
48.023
230425AE1-104_GEN2
Solar/Wind Harmer
48.023
228728W1-130C
Solar/Wind Harmer
0.942
230434AG1-499 GEN
Solar/Wind Harmer
0.818
230407AD2-065 C
Solar/Wind Harmer
0.185
227927V4-067C
Solar/Wind Harmer
0.279
219137THOSOLAR C
Solar/Wind Harmer
1.666
219258KINSLEYDEP C
Solar/Wind Harmer
0.441
213942SCHUYLKILL
Adder
4.854
213942SCHUYLKILL
Adder
3.712
213957STHWK3-4
Adder
3.704
213957STHWK3-4
Adder
3.704
213561DLWR9-10
Adder
4.719
213561DLWR9-10
Adder
3.609
219615MILLCREEK C
Solar/Wind Harmer
0.311
219610FLORENCE C
Solar/Wind Harmer
1.784
219224BRL12CT4
Adder
11.498
213611FALLS1-3
Adder
4.418
213611FALLS1-3
Adder
4.418
20720728JCB_W1-129
Solar/Wind Harmer
0.368
20715028HAN_X4-015
Solar/Wind Harmer
0.368
207487AE2-000G4
Solar/Wind Harmer
38.529
207497AE2-000G2
Solar/Wind Harmer
38.529
207500AE2-000G1
Solar/Wind Harmer
38.529
207507AE2-000G3
Solar/Wind Harmer
38.529
963401AG1-189 GEN
Solar/Wind Harmer
2.766
970025AG2-016 GEN
Solar/Wind Harmer
3.437
971189AH1-054 GEN
Solar/Wind Harmer
1.429
207445AB1-138_GEN
Solar/Wind Harmer
0.693
219620RIDERU C
Solar/Wind Harmer
0.064
20714428HOW_X1-037
Solar/Wind Harmer
1.414
20720628TIN_W1-124
Solar/Wind Harmer
1.133
20716228APLW2-078
Solar/Wind Harmer
1.003
971521AH1-258 GEN
Solar/Wind Harmer
3.04
20635928PARLN3&4
Adder
8.013
218526CNTRALGAS2 C
Solar/Wind Harmer
0.393
20675528CPH_W2-050
Solar/Wind Harmer
0.6
20673828FLE_V3-070
Solar/Wind Harmer
0.481
218449LINSOLAR C
Solar/Wind Harmer
1.025
20676128MHD_W3-029
Solar/Wind Harmer
0.485
20676428JCR_X2-075
Solar/Wind Harmer
0.345
217167KRNY_14
Adder
9.191
217086KRNY_131
Adder
9.113
217147KRNY_1212
Adder
8.742
217147KRNY_1212
Adder
8.586
217146KRNY_1234
Adder
8.566
217146KRNY_1234
Adder
8.508
964851AG1-348 GEN
Solar/Wind Harmer
1.14
971009AG2-626 GEN
Solar/Wind Harmer
1.365
207408W3-077 C
Solar/Wind Harmer
0.414
200192DELTA CT1
50/50
3.851
200194DELTA CT3
50/50
3.851
200204Y1-065-CTG1
50/50
7.742
200054ROCKSP 3
50/50
4.927
233996TM1833_GEN
Solar/Wind Harmer
1.885
233998TM1NIN_3.36
Solar/Wind Harmer
1.885
232404W1-003 C
Solar/Wind Harmer
1.891
232408W1-005 C
Solar/Wind Harmer
1.891
232917OH NUG6
Adder
16.632
232915OH NUG4
Adder
16.595
234033AF1-007_GEN
Solar/Wind Harmer
70.332
232919VN10
Adder
5.307
232901NORTHST
Adder
15.731
232426Y1-080 FULL
Solar/Wind Harmer
0.361
972177AH1-672 GEN
Solar/Wind Harmer
25.383
233970AC1-092 C
Solar/Wind Harmer
5.061
232900DEMECSMY
Adder
17.402
232902EASTMUNI
Adder
24.554
234012AE2-112_GEN
Solar/Wind Harmer
4.299
233944AB2-135 GEN
Solar/Wind Harmer
9.744
233918AB1-142 GEN
Solar/Wind Harmer
1.84
972251AH1-710 GEN
Adder
80.133
231918WEST 1
Adder
5.957
231917EM10
Adder
4.123
228206SHRMN CT
Adder
24.016
228732V1-021 C
Adder
0.272
228260V4-054C
Solar/Wind Harmer
1.477
970997AG2-616 GEN
Solar/Wind Harmer
13.739
213497CHSTR7-9
Adder
3.862
213497CHSTR7-9
Adder
3.862
228729W2-030 C
Solar/Wind Harmer
0.814
228400MICK 1CT
Adder
16.558
213958STHWK5-6
Adder
3.704
219766PARADISE C
Solar/Wind Harmer
0.425
219686LUMSOLAR_N C
Solar/Wind Harmer
0.271
213560DLW11-12
Adder
3.609
219907AC1-030 C
Solar/Wind Harmer
0.184
219348LDSOLAR C
Solar/Wind Harmer
0.771
219222BRL12CT2
Adder
11.498
213611FALLS1-3
Adder
4.418
20716028EGP_W2-019
Solar/Wind Harmer
0.573
207522AF2-254 C
Solar/Wind Harmer
1.768
214194N WALES4
Adder
1.05
20717128DIX_Z2-102
Solar/Wind Harmer
1.624
20715828PEM_W1-120
Solar/Wind Harmer
0.656
963711AG1-223 GEN
Solar/Wind Harmer
1.734
20714528FRN_Y2-051
Solar/Wind Harmer
0.345
219276PARKLANDSO C
Solar/Wind Harmer
0.538
219680HOPEWELLV C1
Solar/Wind Harmer
0.087
20715228NPK_W1-113
Solar/Wind Harmer
0.488
20720528MAN_W1-024
Solar/Wind Harmer
0.288
20720428HOL_W1-112
Solar/Wind Harmer
0.387
20635828PARLN1&2
Adder
8.013
20635028RRCT1&2
Adder
12.64
218524CNTRALGAS1 C
Solar/Wind Harmer
0.39
218440SUMMTASSOC C
Solar/Wind Harmer
0.135
218428ETC SOLAR C
Solar/Wind Harmer
0.038
219908AB1-139 C
Solar/Wind Harmer
0.399
219919AE1-041 FULL
Solar/Wind Harmer
0.042
972275AH1-722 GEN
Adder
32.699
20673628F1S_V4-069
Solar/Wind Harmer
0.182
207528AF2-192 GEN
Solar/Wind Harmer
1.293
217209CENTRL HS C
Solar/Wind Harmer
0.045
217186ESSEX_G9
Adder
3.904
217121ECCF
Adder
0.429
217083KRNY_132
Adder
9.191
217208PARK ELE C
Solar/Wind Harmer
0.025
20671828STAW2-080
Solar/Wind Harmer
0.103
20676728BRNX1-095
Solar/Wind Harmer
0.166
966261AG1-495 GEN
Solar/Wind Harmer
3.222
207439AE1-081 C O1
Solar/Wind Harmer
0.054
20676328BVR_Y1-020
Solar/Wind Harmer
0.296
20674628WNG_W3-110
Solar/Wind Harmer
0.359
20676228FRD_X1-012
Solar/Wind Harmer
0.523
207530AG1-191 GEN
Solar/Wind Harmer
1.213
20675828AU_W4-064
Solar/Wind Harmer
0.152
20674928WA_W3-044
Solar/Wind Harmer
0.407
971519AH1-257 GEN
Solar/Wind Harmer
2.093
20675728RH_W2-091
Solar/Wind Harmer
0.493
207518AF1-320_GEN
Solar/Wind Harmer
2.977
207484AF2-139 C O1
Solar/Wind Harmer
0.409
20465127PORT CT
Adder
2.415
208909MACR G3
Adder
122.298
211065PSPA IPP
Solar/Wind Harmer
0.315
209010PEIP 1
Adder
0.401
963071AG1-156 GEN
Solar/Wind Harmer
5.996
961301AF2-421 GEN
Solar/Wind Harmer
0.593
963151AG1-164 GEN
Solar/Wind Harmer
0.593
209023WIENIPP1
Adder
6.397
209025WIENIPP3
Adder
3.193
316415AF1-147_GEN2
Solar/Wind Helper
0.819
238175AF1-290_GEN
Solar/Wind Helper
0.128
316447AC1-158 HLD
Solar/Wind Helper
2.856
316044AC1-158 PL1
Solar/Wind Helper
1.298
3147666LOUISA
Solar/Wind Helper
0.921
316192AB2-158 GEN
Solar/Wind Helper
1.55
238152AF2-075_GEN
Solar/Wind Helper
0.567
23777901MDS_W4-102
Solar/Wind Helper
0.144
316337AD2-073 GEN
Solar/Wind Helper
0.346
964211AG1-282 GEN
Solar/Wind Helper
0.306
3141726DUNNSVL
Solar/Wind Helper
0.908
316404AE1-155 C
Solar/Wind Helper
1.941
3142416OLDCHRC
Solar/Wind Helper
0.589
3142416OLDCHRC
Solar/Wind Helper
0.226
3138133OCRAN
Solar/Wind Helper
0.136
3143526WINTERP
Solar/Wind Helper
1.176
3141766HARMONY
Solar/Wind Helper
0.045
315662AE1-191 GEN
Solar/Wind Helper
1.219
316280AD1-041 GEN
Solar/Wind Helper
0.762
315975AC1-164 GENB
Solar/Wind Helper
0.086
3143226MDLTHAN
Solar/Wind Helper
0.226
3142433PROV 92
Solar/Wind Helper
0.904
3142543TWELFTH
Solar/Wind Helper
0.022
316132AB2-190 GEN1
Solar/Wind Helper
1.289
315671AE2-027_GEN
Solar/Wind Helper
1.819
316369SG1_INVT
Solar/Wind Helper
1.086
3145336SMITFLD
Solar/Wind Helper
0.897
315773AC2-141 GEN
Solar/Wind Helper
4.837
316381AD1-082 GEN
Solar/Wind Helper
1.164
316375AC2-012 GEN
Solar/Wind Helper
0.59
316036AC1-147 C
Solar/Wind Helper
0.342
316072AD1-144
Solar/Wind Helper
0.256
3146456SLIGO L269
Solar/Wind Helper
0.224
319010AE1-072 C
Solar/Wind Helper
2.561
3146516WINFALL
Solar/Wind Helper
0.722
3146516WINFALL
Solar/Wind Helper
0.223
200035PCHBTM 3
50/50
40.545
200201DELTA2 CT2
50/50
6.893
200034PCHBTM 2
50/50
40.156
200205Y1-065-CTG2
50/50
7.742
232926CRISFLD1
Adder
3.713
232410W1-006 C
Solar/Wind Harmer
1.891
232918OH NUG7
Adder
16.595
232905CHERITON_25
Adder
4.641
232428Y3-058 C
Solar/Wind Harmer
1.575
234015AF2-250 C
Solar/Wind Harmer
0.227
233994AC2-023 GEN
Solar/Wind Harmer
5.076
231940T-011
Adder
1.41
233946AB2-136 GEN
Solar/Wind Harmer
7.536
234036AF2-325 C
Solar/Wind Harmer
1.732
234041AC1-190 GEN
Solar/Wind Harmer
16.918
233971AC1-093 C
Solar/Wind Harmer
4.806
232899W1-062
Adder
18.143
233952AC2-187 GEN
Solar/Wind Harmer
2.12
233954AC2-188 GEN
Solar/Wind Harmer
2.12
233984AB2-036 GEN
Solar/Wind Harmer
23.374
232910NRG_G1
Adder
16.207
232424Y1-079 C
Solar/Wind Harmer
1.054
234014AF1-036_GEN
Solar/Wind Harmer
5.058
232436AB1-176 C
Solar/Wind Harmer
0.427
233930AB2-032 GEN
Solar/Wind Harmer
1.549
233982AB2-133 GEN
Solar/Wind Harmer
9.047
228251CARLLS#4
Adder
0.908
228201CARL#2CT
Adder
9.896
228200CARL#1CT
Adder
9.412
228351V2-046C
Solar/Wind Harmer
2.879
230511AF1-262
Solar/Wind Harmer
0.261
230433AD2-135 GEN
Solar/Wind Harmer
0.144
228307PCLP GT
Adder
17.145
213589EDDYSTN4
Adder
112.532
213587EDDYSTN3
Adder
112.486
228754AB1-001 C
Solar/Wind Harmer
0.196
972233AH1-701 GEN
Adder
5.893
219904AC1-010 C
Solar/Wind Harmer
0.511
219272CLEANLIGHT C
Solar/Wind Harmer
0.246
219912AD2-042 GEN
Solar/Wind Harmer
1.067
219287REEVESEAST C
Solar/Wind Harmer
1.8
219906AC1-017 C
Solar/Wind Harmer
0.29
219607WPEMNERT C
Solar/Wind Harmer
0.539
219304NAMERICA C
Solar/Wind Harmer
0.4
213815MOSER1-3
Adder
4.565
213815MOSER1-3
Adder
4.565
213535CROYDN11
Adder
13.157
214067T20SOLAR
Solar/Wind Harmer
0.316
20720828JCB_W4-025
Solar/Wind Harmer
0.559
20636128O CRK C2
Adder
7.882
207459AE1-142 C O1
Solar/Wind Harmer
1.266
20628028LAKEHURS
Adder
1.137
20714828MDF_W3-079
Solar/Wind Harmer
0.358
219817TRENTONSOL C
Solar/Wind Harmer
1.268
20641628MLH_W1-032
Solar/Wind Harmer
0.334
20742028HF_AC1-207
Solar/Wind Harmer
0.885
217197RE CRAN C
Solar/Wind Harmer
0.594
218438BLK ROCK C
Solar/Wind Harmer
0.151
924131AB2-057 GEN
Solar/Wind Harmer
1.109
20635028RRCT1&2
Adder
12.446
20635128RRCT3&4
Adder
12.014
20635128RRCT3&4
Adder
10.48
218418LINDEN_G5
Adder
17.787
218419LINDEN_G6
Adder
17.787
972260AH1-715 GEN1
Adder
14.243
219036LINDEN_G7
Adder
17.049
219035LINDEN_G8
Adder
16.806
972261AH1-715 GEN2
Adder
16.32
20675428EAM_W2-061
Solar/Wind Harmer
0.192
217081WEATEXAS C
Solar/Wind Harmer
0.087
217202FBANKSOLAR C
Solar/Wind Harmer
0.074
217201HACKENSOLA C
Solar/Wind Harmer
0.073
972237AH1-703 GEN
Adder
10.013
217206BARNGR HS C
Solar/Wind Harmer
0.03
217086KRNY_131
Adder
9.21
217083KRNY_132
Adder
9.132
217204WCALDSOLAR C
Solar/Wind Harmer
0.072
20674328GAR_V4-001
Solar/Wind Harmer
0.097
20674828DL_W4-046
Solar/Wind Harmer
0.549
207471AF2-354 C
Solar/Wind Harmer
0.433
20634528N27_Y2-018
Solar/Wind Harmer
0.224
20675928HOL_W4-097
Solar/Wind Harmer
0.106
20465127PORT CT
Adder
3.204
209010PEIP 1
Adder
2.204
209010PEIP 1
Adder
0.323
316411AF1-147_GEN1
Solar/Wind Helper
0.819
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.153
316450AC1-158 RIC
Solar/Wind Helper
0.346
966001AG1-469 GEN
Solar/Wind Helper
0.246
238147AE2-230_GEN1
Solar/Wind Helper
0.397
238148AE2-230_GEN2
Solar/Wind Helper
0.397
238149AF1-291A_GEN
Solar/Wind Helper
0.113
235020AA1-095 C
Solar/Wind Helper
0.043
237061AD1-155 GEN
Solar/Wind Helper
1.429
966871AG1-558 GEN
Solar/Wind Helper
0.306
316487AF1-042 GEN
Solar/Wind Helper
0.229
316312AB1-027
Solar/Wind Helper
0.432
3143526WINTERP
Solar/Wind Helper
1.176
315976AC1-164 GENA
Solar/Wind Helper
2.917
316169AC1-164_GENC
Solar/Wind Helper
2.52
315666AE1-190 GEN
Solar/Wind Helper
0.305
316156AD2-030 GEN
Solar/Wind Helper
0.342
3142946ENON
Solar/Wind Helper
0.023
316240AF1-291 C
Solar/Wind Helper
0.303
316033AB2-134 GEN
Solar/Wind Helper
0.779
316313AB2-026
Solar/Wind Helper
0.343
316294AC1-161 GEN
Solar/Wind Helper
4.111
316185AD1-033 GEN
Solar/Wind Helper
1.056
3145506HICKORY
Solar/Wind Helper
0.895
3145506HICKORY
Solar/Wind Helper
0.537
3145506HICKORY
Solar/Wind Helper
0.134
316349AD2-085 GEN
Solar/Wind Helper
1.025
316339AD2-160 GEN
Solar/Wind Helper
0.854
316388AE2-253 GEN
Solar/Wind Helper
0.854
3137176SLIGO L2192
Solar/Wind Helper
0.89
3130086AYDLETT
Solar/Wind Helper
0.894
3146386ELIZ CT
Solar/Wind Helper
0.223
316431W1029_GEN1
Solar/Wind Helper
0.902
316433W1029_GEN2
Solar/Wind Helper
0.902
316435W1029_GEN3
Solar/Wind Helper
0.902
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
238221AF1-254 C O1
Solar/Wind Helper
0.22
3146626S HERTFORD
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3144356SAPONY
Solar/Wind Helper
0.399
316315AB2-025 C
Solar/Wind Helper
0.34
20675128HRM_W1-127
Solar/Wind Harmer
0.136
20462827N BANGR8
Adder
0.568
961261AF2-417 GEN
Solar/Wind Harmer
0.67
209029WAYMART-WD
Solar/Wind Harmer
1.61
209026WIENIPP4
Adder
3.161
3138216PACIFIC
Solar/Wind Helper
0.041
238169AE2-226 GEN1
Solar/Wind Helper
0.573
238170AE2-226 GEN2
Solar/Wind Helper
0.573
315651AD1-115 GEN
Solar/Wind Helper
0.788
3141426STAFORD
Solar/Wind Helper
0.051
316164AC1-076 GEN
Solar/Wind Helper
1.112
316468AD1-105 GEN
Solar/Wind Helper
1.097
3141813NORNECK
Solar/Wind Helper
0.227
3141783LANCAST
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.09
3138133OCRAN
Solar/Wind Helper
0.068
3141913WHIT STONE
Solar/Wind Helper
0.226
316233AE1-074 FULL
Solar/Wind Helper
0.345
316059AD1-063 C
Solar/Wind Helper
0.229
3143873LANEXA
Solar/Wind Helper
0.136
957601AF2-054 GEN
Solar/Wind Helper
0.303
3141873WAN 176
Solar/Wind Helper
0.045
957831AF2-077 GEN
Solar/Wind Helper
0.304
316382AG1-145 C
Solar/Wind Helper
0.304
316159AE1-175 C
Solar/Wind Helper
0.343
315697AD1-025 GEN
Solar/Wind Helper
2.575
315839AE2-212 C
Solar/Wind Helper
0.303
316236AE1-162_GEN
Solar/Wind Helper
0.302
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.257
3143316POE
Solar/Wind Helper
0.888
316316AC1-027 C
Solar/Wind Helper
0.354
316018AA1-139 ULT2
Solar/Wind Helper
0.965
313526AB2-022
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.223
3146486SUNBURY
Solar/Wind Helper
0.223
3145176PASQUOTANK
Solar/Wind Helper
0.138
233939AC1-091 C
Solar/Wind Harmer
5.061
233972AC1-094 C
Solar/Wind Harmer
4.064
233950AC2-186 GEN
Solar/Wind Harmer
1.06
232422X3-066 FULL
Solar/Wind Harmer
0.466
233933AB2-153 GEN
Solar/Wind Harmer
2.091
233935AB2-179 C
Solar/Wind Harmer
4.545
228711V2-041C
Solar/Wind Harmer
0.871
230415AB2-049 C
Solar/Wind Harmer
0.269
213497CHSTR7-9
Adder
3.862
219623KINSLEYBEA C
Solar/Wind Harmer
0.583
213958STHWK5-6
Adder
3.704
219921AF1-264
Solar/Wind Harmer
0.196
219291REEVESSOUT C
Solar/Wind Harmer
0.081
218660EHAMPSOLAR C
Solar/Wind Harmer
0.235
219914AD2-027 C
Solar/Wind Harmer
0.805
219688LUMSOLAR_S C
Solar/Wind Harmer
0.271
213560DLW11-12
Adder
3.609
219236SOUTHERNHQ C
Solar/Wind Harmer
0.089
219221BRL12CT1
Adder
11.498
219223BRL12CT3
Adder
11.498
213815MOSER1-3
Adder
4.565
959561AF2-247 GEN
Solar/Wind Harmer
0.603
20716428NHV_W2-082
Solar/Wind Harmer
2.192
20715728PEM_W1-119
Solar/Wind Harmer
0.656
20636028O CRK C1
Adder
8.645
963391AG1-188 GEN
Solar/Wind Harmer
4.545
20714928UPF_X1-085
Solar/Wind Harmer
0.49
219114HARTZY_C
Solar/Wind Harmer
1.002
971667AH1-334 GEN
Solar/Wind Harmer
3.298
219727YARDVSOLFA C
Solar/Wind Harmer
1.084
219918AC2-009 C
Solar/Wind Harmer
0.029
207454AA2-184 E
Solar/Wind Harmer
1.137
219612MATRIX C
Solar/Wind Harmer
0.204
20716928W4-060COL
Solar/Wind Harmer
0.784
20635828PARLN1&2
Adder
3.63
20635928PARLN3&4
Adder
3.63
217213AMBOY SO C
Solar/Wind Harmer
0.132
219249CENTRALDIV C
Solar/Wind Harmer
0.041
207442AE1-156 GEN
Solar/Wind Harmer
0.756
20673728F2S_V4-070
Solar/Wind Harmer
0.182
217211CAMDEN ST C
Solar/Wind Harmer
0.024
217169METRODIV C
Solar/Wind Harmer
0.039
217194REDH C
Solar/Wind Harmer
0.486
20674528F3S_W2-016
Solar/Wind Harmer
1.358
207510AF2-138 C
Solar/Wind Harmer
1.581
207511W3-106 GEN
Solar/Wind Harmer
0.293
971007AG2-625 GEN
Solar/Wind Harmer
2.14
207437AD2-070 GEN
Solar/Wind Harmer
0.243
20466127PORT 5CT
Adder
21.35
20671928W4-073
Solar/Wind Harmer
0.345
20674128FR_U2-059
Solar/Wind Harmer
0.147
20633028GILCT9
Adder
22.394
20465427SHAW CT
Adder
3.06
209116AE2-175 GEN
Solar/Wind Harmer
3.018
211065PSPA IPP
Solar/Wind Harmer
0.315
970095AG2-074 GEN
Solar/Wind Harmer
3.797
963161AG1-165 GEN
Solar/Wind Harmer
0.593
209025WIENIPP3
Adder
3.128
208972BECR K09
Solar/Wind Harmer
0.618
3141196NOKESVL
Solar/Wind Helper
0.957
3132273ORANGE
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.529
966881AG1-559 GEN
Solar/Wind Helper
0.309
23546401DTGZ2-030
Solar/Wind Helper
0.072
316223AC1-118
Solar/Wind Helper
0.348
3141906WESTMOR
Solar/Wind Helper
0.091
316077AC2-138 C
Solar/Wind Helper
0.214
316473AC1-191 GEN
Solar/Wind Helper
1.387
316484AD2-074 GEN
Solar/Wind Helper
0.438
316075AC2-137 C
Solar/Wind Helper
0.345
3142946ENON
Solar/Wind Helper
0.075
316458AB2-190 GEN2
Solar/Wind Helper
1.289
3145336SMITFLD
Solar/Wind Helper
0.09
3144536CHRHLND
Solar/Wind Helper
0.034
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.151
316017AA1-139 ULT1
Solar/Wind Helper
1.025
3146456SLIGO L269
Solar/Wind Helper
0.224
316305AF2-043 C
Solar/Wind Helper
0.301
316246AF1-032 C
Solar/Wind Helper
0.256
316320Y1-086
Solar/Wind Helper
0.1
316321Z2-027
Solar/Wind Helper
0.341
3146516WINFALL
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3145273HOLLAND
Solar/Wind Helper
0.167
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.425
VTFLTFEXP_VFT->PJM
CMTX
135.388
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.24
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.798
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.944
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.424
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
54.971
CBM NorthLTFEXP_CBM-N->PJM
CBM
62.973
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.22 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:4644.06
MW Contribution:
6.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
3.851
200194DELTA CT3
50/50
3.851
200204Y1-065-CTG1
50/50
7.742
200054ROCKSP 3
50/50
4.927
233996TM1833_GEN
Solar/Wind Harmer
1.885
233998TM1NIN_3.36
Solar/Wind Harmer
1.885
232404W1-003 C
Solar/Wind Harmer
1.891
232408W1-005 C
Solar/Wind Harmer
1.891
232917OH NUG6
Adder
16.632
232915OH NUG4
Adder
16.595
234033AF1-007_GEN
Solar/Wind Harmer
70.332
232919VN10
Adder
5.307
232901NORTHST
Adder
15.731
232426Y1-080 FULL
Solar/Wind Harmer
0.361
972177AH1-672 GEN
Solar/Wind Harmer
25.383
233970AC1-092 C
Solar/Wind Harmer
5.061
232900DEMECSMY
Adder
17.402
232902EASTMUNI
Adder
24.554
234012AE2-112_GEN
Solar/Wind Harmer
4.299
233944AB2-135 GEN
Solar/Wind Harmer
9.744
233918AB1-142 GEN
Solar/Wind Harmer
1.84
972251AH1-710 GEN
Adder
80.133
231918WEST 1
Adder
5.957
231917EM10
Adder
4.123
228206SHRMN CT
Adder
24.016
228732V1-021 C
Adder
0.272
228260V4-054C
Solar/Wind Harmer
1.477
970997AG2-616 GEN
Solar/Wind Harmer
13.739
213497CHSTR7-9
Adder
3.862
213497CHSTR7-9
Adder
3.862
228729W2-030 C
Solar/Wind Harmer
0.814
228400MICK 1CT
Adder
16.558
213958STHWK5-6
Adder
3.704
219766PARADISE C
Solar/Wind Harmer
0.425
219686LUMSOLAR_N C
Solar/Wind Harmer
0.271
213560DLW11-12
Adder
3.609
219907AC1-030 C
Solar/Wind Harmer
0.184
219348LDSOLAR C
Solar/Wind Harmer
0.771
219222BRL12CT2
Adder
11.498
213611FALLS1-3
Adder
4.418
20716028EGP_W2-019
Solar/Wind Harmer
0.573
207522AF2-254 C
Solar/Wind Harmer
1.768
214194N WALES4
Adder
1.05
20717128DIX_Z2-102
Solar/Wind Harmer
1.624
20715828PEM_W1-120
Solar/Wind Harmer
0.656
963711AG1-223 GEN
Solar/Wind Harmer
1.734
20714528FRN_Y2-051
Solar/Wind Harmer
0.345
219276PARKLANDSO C
Solar/Wind Harmer
0.538
219680HOPEWELLV C1
Solar/Wind Harmer
0.087
20715228NPK_W1-113
Solar/Wind Harmer
0.488
20720528MAN_W1-024
Solar/Wind Harmer
0.288
20720428HOL_W1-112
Solar/Wind Harmer
0.387
20635828PARLN1&2
Adder
8.013
20635028RRCT1&2
Adder
12.64
218524CNTRALGAS1 C
Solar/Wind Harmer
0.39
218440SUMMTASSOC C
Solar/Wind Harmer
0.135
218428ETC SOLAR C
Solar/Wind Harmer
0.038
219908AB1-139 C
Solar/Wind Harmer
0.399
219919AE1-041 FULL
Solar/Wind Harmer
0.042
972275AH1-722 GEN
Adder
32.699
20673628F1S_V4-069
Solar/Wind Harmer
0.182
207528AF2-192 GEN
Solar/Wind Harmer
1.293
217209CENTRL HS C
Solar/Wind Harmer
0.045
217186ESSEX_G9
Adder
3.904
217121ECCF
Adder
0.429
217083KRNY_132
Adder
9.191
217208PARK ELE C
Solar/Wind Harmer
0.025
20671828STAW2-080
Solar/Wind Harmer
0.103
20676728BRNX1-095
Solar/Wind Harmer
0.166
966261AG1-495 GEN
Solar/Wind Harmer
3.222
207439AE1-081 C O1
Solar/Wind Harmer
0.054
20676328BVR_Y1-020
Solar/Wind Harmer
0.296
20674628WNG_W3-110
Solar/Wind Harmer
0.359
20676228FRD_X1-012
Solar/Wind Harmer
0.523
207530AG1-191 GEN
Solar/Wind Harmer
1.213
20675828AU_W4-064
Solar/Wind Harmer
0.152
20674928WA_W3-044
Solar/Wind Harmer
0.407
971519AH1-257 GEN
Solar/Wind Harmer
2.093
20675728RH_W2-091
Solar/Wind Harmer
0.493
207518AF1-320_GEN
Solar/Wind Harmer
2.977
207484AF2-139 C O1
Solar/Wind Harmer
0.409
20465127PORT CT
Adder
2.415
208909MACR G3
Adder
122.298
211065PSPA IPP
Solar/Wind Harmer
0.315
209010PEIP 1
Adder
0.401
963071AG1-156 GEN
Solar/Wind Harmer
5.996
200035PCHBTM 3
50/50
40.545
200201DELTA2 CT2
50/50
6.893
200034PCHBTM 2
50/50
40.156
200205Y1-065-CTG2
50/50
7.742
232926CRISFLD1
Adder
3.713
232410W1-006 C
Solar/Wind Harmer
1.891
232918OH NUG7
Adder
16.595
232905CHERITON_25
Adder
4.641
232428Y3-058 C
Solar/Wind Harmer
1.575
234015AF2-250 C
Solar/Wind Harmer
0.227
233994AC2-023 GEN
Solar/Wind Harmer
5.076
231940T-011
Adder
1.41
233946AB2-136 GEN
Solar/Wind Harmer
7.536
234036AF2-325 C
Solar/Wind Harmer
1.732
234041AC1-190 GEN
Solar/Wind Harmer
16.918
233971AC1-093 C
Solar/Wind Harmer
4.806
232899W1-062
Adder
18.143
233952AC2-187 GEN
Solar/Wind Harmer
2.12
233954AC2-188 GEN
Solar/Wind Harmer
2.12
233984AB2-036 GEN
Solar/Wind Harmer
23.374
232910NRG_G1
Adder
16.207
232424Y1-079 C
Solar/Wind Harmer
1.054
234014AF1-036_GEN
Solar/Wind Harmer
5.058
232436AB1-176 C
Solar/Wind Harmer
0.427
233930AB2-032 GEN
Solar/Wind Harmer
1.549
233982AB2-133 GEN
Solar/Wind Harmer
9.047
228251CARLLS#4
Adder
0.908
228201CARL#2CT
Adder
9.896
228200CARL#1CT
Adder
9.412
228351V2-046C
Solar/Wind Harmer
2.879
230511AF1-262
Solar/Wind Harmer
0.261
230433AD2-135 GEN
Solar/Wind Harmer
0.144
228307PCLP GT
Adder
17.145
213589EDDYSTN4
Adder
112.532
213587EDDYSTN3
Adder
112.486
228754AB1-001 C
Solar/Wind Harmer
0.196
972233AH1-701 GEN
Adder
5.893
219904AC1-010 C
Solar/Wind Harmer
0.511
219272CLEANLIGHT C
Solar/Wind Harmer
0.246
219912AD2-042 GEN
Solar/Wind Harmer
1.067
219287REEVESEAST C
Solar/Wind Harmer
1.8
219906AC1-017 C
Solar/Wind Harmer
0.29
219607WPEMNERT C
Solar/Wind Harmer
0.539
219304NAMERICA C
Solar/Wind Harmer
0.4
213815MOSER1-3
Adder
4.565
213815MOSER1-3
Adder
4.565
213535CROYDN11
Adder
13.157
214067T20SOLAR
Solar/Wind Harmer
0.316
20720828JCB_W4-025
Solar/Wind Harmer
0.559
20636128O CRK C2
Adder
7.882
207459AE1-142 C O1
Solar/Wind Harmer
1.266
20628028LAKEHURS
Adder
1.137
20714828MDF_W3-079
Solar/Wind Harmer
0.358
219817TRENTONSOL C
Solar/Wind Harmer
1.268
20641628MLH_W1-032
Solar/Wind Harmer
0.334
20742028HF_AC1-207
Solar/Wind Harmer
0.885
217197RE CRAN C
Solar/Wind Harmer
0.594
218438BLK ROCK C
Solar/Wind Harmer
0.151
924131AB2-057 GEN
Solar/Wind Harmer
1.109
20635028RRCT1&2
Adder
12.446
20635128RRCT3&4
Adder
12.014
20635128RRCT3&4
Adder
10.48
218418LINDEN_G5
Adder
17.787
218419LINDEN_G6
Adder
17.787
972260AH1-715 GEN1
Adder
14.243
219036LINDEN_G7
Adder
17.049
219035LINDEN_G8
Adder
16.806
972261AH1-715 GEN2
Adder
16.32
20675428EAM_W2-061
Solar/Wind Harmer
0.192
217081WEATEXAS C
Solar/Wind Harmer
0.087
217202FBANKSOLAR C
Solar/Wind Harmer
0.074
217201HACKENSOLA C
Solar/Wind Harmer
0.073
972237AH1-703 GEN
Adder
10.013
217206BARNGR HS C
Solar/Wind Harmer
0.03
217086KRNY_131
Adder
9.21
217083KRNY_132
Adder
9.132
217204WCALDSOLAR C
Solar/Wind Harmer
0.072
20674328GAR_V4-001
Solar/Wind Harmer
0.097
20674828DL_W4-046
Solar/Wind Harmer
0.549
207471AF2-354 C
Solar/Wind Harmer
0.433
20634528N27_Y2-018
Solar/Wind Harmer
0.224
20675928HOL_W4-097
Solar/Wind Harmer
0.106
20465127PORT CT
Adder
3.204
209010PEIP 1
Adder
2.204
209010PEIP 1
Adder
0.323
316411AF1-147_GEN1
Solar/Wind Helper
0.819
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.153
316450AC1-158 RIC
Solar/Wind Helper
0.346
966001AG1-469 GEN
Solar/Wind Helper
0.246
238147AE2-230_GEN1
Solar/Wind Helper
0.397
238148AE2-230_GEN2
Solar/Wind Helper
0.397
238149AF1-291A_GEN
Solar/Wind Helper
0.113
235020AA1-095 C
Solar/Wind Helper
0.043
237061AD1-155 GEN
Solar/Wind Helper
1.429
966871AG1-558 GEN
Solar/Wind Helper
0.306
316487AF1-042 GEN
Solar/Wind Helper
0.229
316312AB1-027
Solar/Wind Helper
0.432
3143526WINTERP
Solar/Wind Helper
1.176
315976AC1-164 GENA
Solar/Wind Helper
2.917
316169AC1-164_GENC
Solar/Wind Helper
2.52
315666AE1-190 GEN
Solar/Wind Helper
0.305
316156AD2-030 GEN
Solar/Wind Helper
0.342
3142946ENON
Solar/Wind Helper
0.023
316240AF1-291 C
Solar/Wind Helper
0.303
316033AB2-134 GEN
Solar/Wind Helper
0.779
316313AB2-026
Solar/Wind Helper
0.343
316294AC1-161 GEN
Solar/Wind Helper
4.111
316185AD1-033 GEN
Solar/Wind Helper
1.056
3145506HICKORY
Solar/Wind Helper
0.895
3145506HICKORY
Solar/Wind Helper
0.537
3145506HICKORY
Solar/Wind Helper
0.134
316349AD2-085 GEN
Solar/Wind Helper
1.025
316339AD2-160 GEN
Solar/Wind Helper
0.854
316388AE2-253 GEN
Solar/Wind Helper
0.854
3137176SLIGO L2192
Solar/Wind Helper
0.89
3130086AYDLETT
Solar/Wind Helper
0.894
3146386ELIZ CT
Solar/Wind Helper
0.223
316431W1029_GEN1
Solar/Wind Helper
0.902
316433W1029_GEN2
Solar/Wind Helper
0.902
316435W1029_GEN3
Solar/Wind Helper
0.902
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
238221AF1-254 C O1
Solar/Wind Helper
0.22
3146626S HERTFORD
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3144356SAPONY
Solar/Wind Helper
0.399
316315AB2-025 C
Solar/Wind Helper
0.34
961301AF2-421 GEN
Solar/Wind Harmer
0.593
963151AG1-164 GEN
Solar/Wind Harmer
0.593
209023WIENIPP1
Adder
6.397
209025WIENIPP3
Adder
3.193
316415AF1-147_GEN2
Solar/Wind Helper
0.819
238175AF1-290_GEN
Solar/Wind Helper
0.128
316447AC1-158 HLD
Solar/Wind Helper
2.856
316044AC1-158 PL1
Solar/Wind Helper
1.298
3147666LOUISA
Solar/Wind Helper
0.921
316192AB2-158 GEN
Solar/Wind Helper
1.55
238152AF2-075_GEN
Solar/Wind Helper
0.567
23777901MDS_W4-102
Solar/Wind Helper
0.144
316337AD2-073 GEN
Solar/Wind Helper
0.346
964211AG1-282 GEN
Solar/Wind Helper
0.306
3141726DUNNSVL
Solar/Wind Helper
0.908
316404AE1-155 C
Solar/Wind Helper
1.941
3142416OLDCHRC
Solar/Wind Helper
0.589
3142416OLDCHRC
Solar/Wind Helper
0.226
3138133OCRAN
Solar/Wind Helper
0.136
3143526WINTERP
Solar/Wind Helper
1.176
3141766HARMONY
Solar/Wind Helper
0.045
315662AE1-191 GEN
Solar/Wind Helper
1.219
316280AD1-041 GEN
Solar/Wind Helper
0.762
315975AC1-164 GENB
Solar/Wind Helper
0.086
3143226MDLTHAN
Solar/Wind Helper
0.226
3142433PROV 92
Solar/Wind Helper
0.904
3142543TWELFTH
Solar/Wind Helper
0.022
316132AB2-190 GEN1
Solar/Wind Helper
1.289
315671AE2-027_GEN
Solar/Wind Helper
1.819
316369SG1_INVT
Solar/Wind Helper
1.086
3145336SMITFLD
Solar/Wind Helper
0.897
315773AC2-141 GEN
Solar/Wind Helper
4.837
316381AD1-082 GEN
Solar/Wind Helper
1.164
316375AC2-012 GEN
Solar/Wind Helper
0.59
316036AC1-147 C
Solar/Wind Helper
0.342
316072AD1-144
Solar/Wind Helper
0.256
3146456SLIGO L269
Solar/Wind Helper
0.224
319010AE1-072 C
Solar/Wind Helper
2.561
3146516WINFALL
Solar/Wind Helper
0.722
3146516WINFALL
Solar/Wind Helper
0.223
200202DELTA2 ST
50/50
11.673
200195DELTA ST
50/50
5.95
200052ROCKSP 1
50/50
4.871
200053ROCKSP 2
50/50
4.775
233901CHERRYDALE C
Solar/Wind Harmer
2.127
232912OH NUG1
Adder
16.706
232913OH NUG2
Adder
16.483
233940AF2-379 C
Solar/Wind Harmer
0.353
232904IR4
Adder
152.888
232432Z2-076 GEN
Solar/Wind Harmer
0.249
971195AH1-057 GEN
Solar/Wind Harmer
1.843
232920IR10
Adder
5.976
233955AB2-172 GEN
Solar/Wind Harmer
9.442
232813VAUGHN
Adder
1.107
233968AD2-076_GEN
Solar/Wind Harmer
12.392
970597AG2-380 GEN
Solar/Wind Harmer
7.782
231906DC3 NUG
Adder
26.105
231902DC CT7
Adder
20.869
231907DC10
Adder
6.517
233915AB1-141 GEN
Solar/Wind Harmer
1.84
231919CHRIST1
Adder
7.82
231920CHRIST2
Adder
7.647
970453AG2-297 GEN
Solar/Wind Harmer
4.023
972141AH1-641 GEN
Solar/Wind Harmer
4.122
230430AE1-229_GEN
Solar/Wind Harmer
40.959
964001AG1-254 GEN
Solar/Wind Harmer
10.423
230422AE1-104_GEN1
Solar/Wind Harmer
48.023
230425AE1-104_GEN2
Solar/Wind Harmer
48.023
228728W1-130C
Solar/Wind Harmer
0.942
230434AG1-499 GEN
Solar/Wind Harmer
0.818
230407AD2-065 C
Solar/Wind Harmer
0.185
227927V4-067C
Solar/Wind Harmer
0.279
219137THOSOLAR C
Solar/Wind Harmer
1.666
219258KINSLEYDEP C
Solar/Wind Harmer
0.441
213942SCHUYLKILL
Adder
4.854
213942SCHUYLKILL
Adder
3.712
213957STHWK3-4
Adder
3.704
213957STHWK3-4
Adder
3.704
213561DLWR9-10
Adder
4.719
213561DLWR9-10
Adder
3.609
219615MILLCREEK C
Solar/Wind Harmer
0.311
219610FLORENCE C
Solar/Wind Harmer
1.784
219224BRL12CT4
Adder
11.498
213611FALLS1-3
Adder
4.418
213611FALLS1-3
Adder
4.418
20720728JCB_W1-129
Solar/Wind Harmer
0.368
20715028HAN_X4-015
Solar/Wind Harmer
0.368
207487AE2-000G4
Solar/Wind Harmer
38.529
207497AE2-000G2
Solar/Wind Harmer
38.529
207500AE2-000G1
Solar/Wind Harmer
38.529
207507AE2-000G3
Solar/Wind Harmer
38.529
963401AG1-189 GEN
Solar/Wind Harmer
2.766
970025AG2-016 GEN
Solar/Wind Harmer
3.437
971189AH1-054 GEN
Solar/Wind Harmer
1.429
207445AB1-138_GEN
Solar/Wind Harmer
0.693
219620RIDERU C
Solar/Wind Harmer
0.064
20714428HOW_X1-037
Solar/Wind Harmer
1.414
20720628TIN_W1-124
Solar/Wind Harmer
1.133
20716228APLW2-078
Solar/Wind Harmer
1.003
971521AH1-258 GEN
Solar/Wind Harmer
3.04
20635928PARLN3&4
Adder
8.013
218526CNTRALGAS2 C
Solar/Wind Harmer
0.393
20675528CPH_W2-050
Solar/Wind Harmer
0.6
20673828FLE_V3-070
Solar/Wind Harmer
0.481
218449LINSOLAR C
Solar/Wind Harmer
1.025
20676128MHD_W3-029
Solar/Wind Harmer
0.485
20676428JCR_X2-075
Solar/Wind Harmer
0.345
217167KRNY_14
Adder
9.191
217086KRNY_131
Adder
9.113
217147KRNY_1212
Adder
8.742
217147KRNY_1212
Adder
8.586
217146KRNY_1234
Adder
8.566
217146KRNY_1234
Adder
8.508
964851AG1-348 GEN
Solar/Wind Harmer
1.14
971009AG2-626 GEN
Solar/Wind Harmer
1.365
207408W3-077 C
Solar/Wind Harmer
0.414
20675128HRM_W1-127
Solar/Wind Harmer
0.136
20462827N BANGR8
Adder
0.568
961261AF2-417 GEN
Solar/Wind Harmer
0.67
209029WAYMART-WD
Solar/Wind Harmer
1.61
209026WIENIPP4
Adder
3.161
3138216PACIFIC
Solar/Wind Helper
0.041
238169AE2-226 GEN1
Solar/Wind Helper
0.573
238170AE2-226 GEN2
Solar/Wind Helper
0.573
315651AD1-115 GEN
Solar/Wind Helper
0.788
3141426STAFORD
Solar/Wind Helper
0.051
316164AC1-076 GEN
Solar/Wind Helper
1.112
316468AD1-105 GEN
Solar/Wind Helper
1.097
3141813NORNECK
Solar/Wind Helper
0.227
3141783LANCAST
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.09
3138133OCRAN
Solar/Wind Helper
0.068
3141913WHIT STONE
Solar/Wind Helper
0.226
316233AE1-074 FULL
Solar/Wind Helper
0.345
316059AD1-063 C
Solar/Wind Helper
0.229
3143873LANEXA
Solar/Wind Helper
0.136
957601AF2-054 GEN
Solar/Wind Helper
0.303
3141873WAN 176
Solar/Wind Helper
0.045
957831AF2-077 GEN
Solar/Wind Helper
0.304
316382AG1-145 C
Solar/Wind Helper
0.304
316159AE1-175 C
Solar/Wind Helper
0.343
315697AD1-025 GEN
Solar/Wind Helper
2.575
315839AE2-212 C
Solar/Wind Helper
0.303
316236AE1-162_GEN
Solar/Wind Helper
0.302
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.257
3143316POE
Solar/Wind Helper
0.888
316316AC1-027 C
Solar/Wind Helper
0.354
316018AA1-139 ULT2
Solar/Wind Helper
0.965
313526AB2-022
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.223
3146486SUNBURY
Solar/Wind Helper
0.223
3145176PASQUOTANK
Solar/Wind Helper
0.138
200200DELTA2 CT1
50/50
6.893
200193DELTA CT2
50/50
3.851
200203Y1-065-STG
50/50
13.408
200055ROCKSP 4
50/50
4.842
233987AB2-037 GEN
Solar/Wind Harmer
21.579
232907VN8
Adder
56.823
233923SMA
Solar/Wind Harmer
6.912
233997TMININ_4.2
Solar/Wind Harmer
1.885
232406W1-004 FULL
Solar/Wind Harmer
1.891
232914OH NUG3
Adder
16.706
232916OH NUG5
Adder
16.706
232921TASLEY2G
Adder
9.764
232434Z2-077 GEN
Solar/Wind Harmer
0.473
233964AF2-378 GEN
Solar/Wind Harmer
0.241
232417X3-008 C
Solar/Wind Harmer
2.124
233973AC2-185 C
Solar/Wind Harmer
10.224
970695AG2-447 GEN
Solar/Wind Harmer
6.764
233939AC1-091 C
Solar/Wind Harmer
5.061
233972AC1-094 C
Solar/Wind Harmer
4.064
233950AC2-186 GEN
Solar/Wind Harmer
1.06
232422X3-066 FULL
Solar/Wind Harmer
0.466
233933AB2-153 GEN
Solar/Wind Harmer
2.091
233935AB2-179 C
Solar/Wind Harmer
4.545
228711V2-041C
Solar/Wind Harmer
0.871
230415AB2-049 C
Solar/Wind Harmer
0.269
213497CHSTR7-9
Adder
3.862
219623KINSLEYBEA C
Solar/Wind Harmer
0.583
213958STHWK5-6
Adder
3.704
219921AF1-264
Solar/Wind Harmer
0.196
219291REEVESSOUT C
Solar/Wind Harmer
0.081
218660EHAMPSOLAR C
Solar/Wind Harmer
0.235
219914AD2-027 C
Solar/Wind Harmer
0.805
219688LUMSOLAR_S C
Solar/Wind Harmer
0.271
213560DLW11-12
Adder
3.609
219236SOUTHERNHQ C
Solar/Wind Harmer
0.089
219221BRL12CT1
Adder
11.498
219223BRL12CT3
Adder
11.498
213815MOSER1-3
Adder
4.565
959561AF2-247 GEN
Solar/Wind Harmer
0.603
20716428NHV_W2-082
Solar/Wind Harmer
2.192
20715728PEM_W1-119
Solar/Wind Harmer
0.656
20636028O CRK C1
Adder
8.645
963391AG1-188 GEN
Solar/Wind Harmer
4.545
20714928UPF_X1-085
Solar/Wind Harmer
0.49
219114HARTZY_C
Solar/Wind Harmer
1.002
971667AH1-334 GEN
Solar/Wind Harmer
3.298
219727YARDVSOLFA C
Solar/Wind Harmer
1.084
219918AC2-009 C
Solar/Wind Harmer
0.029
207454AA2-184 E
Solar/Wind Harmer
1.137
219612MATRIX C
Solar/Wind Harmer
0.204
20716928W4-060COL
Solar/Wind Harmer
0.784
20635828PARLN1&2
Adder
3.63
20635928PARLN3&4
Adder
3.63
217213AMBOY SO C
Solar/Wind Harmer
0.132
219249CENTRALDIV C
Solar/Wind Harmer
0.041
207442AE1-156 GEN
Solar/Wind Harmer
0.756
20673728F2S_V4-070
Solar/Wind Harmer
0.182
217211CAMDEN ST C
Solar/Wind Harmer
0.024
217169METRODIV C
Solar/Wind Harmer
0.039
217194REDH C
Solar/Wind Harmer
0.486
20674528F3S_W2-016
Solar/Wind Harmer
1.358
207510AF2-138 C
Solar/Wind Harmer
1.581
207511W3-106 GEN
Solar/Wind Harmer
0.293
971007AG2-625 GEN
Solar/Wind Harmer
2.14
207437AD2-070 GEN
Solar/Wind Harmer
0.243
20466127PORT 5CT
Adder
21.35
20671928W4-073
Solar/Wind Harmer
0.345
20674128FR_U2-059
Solar/Wind Harmer
0.147
20633028GILCT9
Adder
22.394
20465427SHAW CT
Adder
3.06
209116AE2-175 GEN
Solar/Wind Harmer
3.018
211065PSPA IPP
Solar/Wind Harmer
0.315
970095AG2-074 GEN
Solar/Wind Harmer
3.797
963161AG1-165 GEN
Solar/Wind Harmer
0.593
209025WIENIPP3
Adder
3.128
208972BECR K09
Solar/Wind Harmer
0.618
3141196NOKESVL
Solar/Wind Helper
0.957
3132273ORANGE
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.529
966881AG1-559 GEN
Solar/Wind Helper
0.309
23546401DTGZ2-030
Solar/Wind Helper
0.072
316223AC1-118
Solar/Wind Helper
0.348
3141906WESTMOR
Solar/Wind Helper
0.091
316077AC2-138 C
Solar/Wind Helper
0.214
316473AC1-191 GEN
Solar/Wind Helper
1.387
316484AD2-074 GEN
Solar/Wind Helper
0.438
316075AC2-137 C
Solar/Wind Helper
0.345
3142946ENON
Solar/Wind Helper
0.075
316458AB2-190 GEN2
Solar/Wind Helper
1.289
3145336SMITFLD
Solar/Wind Helper
0.09
3144536CHRHLND
Solar/Wind Helper
0.034
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.151
316017AA1-139 ULT1
Solar/Wind Helper
1.025
3146456SLIGO L269
Solar/Wind Helper
0.224
316305AF2-043 C
Solar/Wind Helper
0.301
316246AF1-032 C
Solar/Wind Helper
0.256
316320Y1-086
Solar/Wind Helper
0.1
316321Z2-027
Solar/Wind Helper
0.341
3146516WINFALL
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3145273HOLLAND
Solar/Wind Helper
0.167
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.425
VTFLTFEXP_VFT->PJM
CMTX
135.388
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.24
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.798
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.944
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.424
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
54.971
CBM NorthLTFEXP_CBM-N->PJM
CBM
62.973
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.16 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:4641.99
MW Contribution:
6.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
40.556
200201DELTA2 CT2
50/50
6.895
200034PCHBTM 2
50/50
40.112
200205Y1-065-CTG2
50/50
7.734
232926CRISFLD1
Adder
3.71
232410W1-006 C
Solar/Wind Harmer
1.889
232918OH NUG7
Adder
16.581
232905CHERITON_25
Adder
4.637
232428Y3-058 C
Solar/Wind Harmer
1.574
234015AF2-250 C
Solar/Wind Harmer
0.227
233994AC2-023 GEN
Solar/Wind Harmer
5.072
231940T-011
Adder
1.409
233946AB2-136 GEN
Solar/Wind Harmer
7.529
234036AF2-325 C
Solar/Wind Harmer
1.73
234041AC1-190 GEN
Solar/Wind Harmer
16.904
233971AC1-093 C
Solar/Wind Harmer
4.802
232899W1-062
Adder
18.128
233952AC2-187 GEN
Solar/Wind Harmer
2.119
233954AC2-188 GEN
Solar/Wind Harmer
2.119
233984AB2-036 GEN
Solar/Wind Harmer
23.356
232910NRG_G1
Adder
16.194
232424Y1-079 C
Solar/Wind Harmer
1.053
234014AF1-036_GEN
Solar/Wind Harmer
5.054
232436AB1-176 C
Solar/Wind Harmer
0.427
233930AB2-032 GEN
Solar/Wind Harmer
1.548
233982AB2-133 GEN
Solar/Wind Harmer
9.04
228251CARLLS#4
Adder
0.907
228201CARL#2CT
Adder
9.89
228200CARL#1CT
Adder
9.406
228351V2-046C
Solar/Wind Harmer
2.877
230511AF1-262
Solar/Wind Harmer
0.261
230433AD2-135 GEN
Solar/Wind Harmer
0.144
228307PCLP GT
Adder
17.135
213589EDDYSTN4
Adder
112.484
213587EDDYSTN3
Adder
112.438
228754AB1-001 C
Solar/Wind Harmer
0.196
972233AH1-701 GEN
Adder
5.89
219904AC1-010 C
Solar/Wind Harmer
0.511
219272CLEANLIGHT C
Solar/Wind Harmer
0.246
219912AD2-042 GEN
Solar/Wind Harmer
1.067
219287REEVESEAST C
Solar/Wind Harmer
1.799
219906AC1-017 C
Solar/Wind Harmer
0.29
219607WPEMNERT C
Solar/Wind Harmer
0.539
219304NAMERICA C
Solar/Wind Harmer
0.399
213815MOSER1-3
Adder
4.564
200192DELTA CT1
50/50
3.853
200194DELTA CT3
50/50
3.853
200204Y1-065-CTG1
50/50
7.734
200054ROCKSP 3
50/50
4.922
233996TM1833_GEN
Solar/Wind Harmer
1.884
233998TM1NIN_3.36
Solar/Wind Harmer
1.884
232404W1-003 C
Solar/Wind Harmer
1.889
232408W1-005 C
Solar/Wind Harmer
1.889
232917OH NUG6
Adder
16.619
232915OH NUG4
Adder
16.581
234033AF1-007_GEN
Solar/Wind Harmer
70.275
232919VN10
Adder
5.302
232901NORTHST
Adder
15.719
232426Y1-080 FULL
Solar/Wind Harmer
0.361
972177AH1-672 GEN
Solar/Wind Harmer
25.363
233970AC1-092 C
Solar/Wind Harmer
5.057
232900DEMECSMY
Adder
17.388
232902EASTMUNI
Adder
24.534
234012AE2-112_GEN
Solar/Wind Harmer
4.296
233944AB2-135 GEN
Solar/Wind Harmer
9.736
233918AB1-142 GEN
Solar/Wind Harmer
1.839
972251AH1-710 GEN
Adder
80.071
231918WEST 1
Adder
5.953
231917EM10
Adder
4.121
228206SHRMN CT
Adder
24.001
228732V1-021 C
Adder
0.272
228260V4-054C
Solar/Wind Harmer
1.476
970997AG2-616 GEN
Solar/Wind Harmer
13.731
213497CHSTR7-9
Adder
3.861
213497CHSTR7-9
Adder
3.861
228729W2-030 C
Solar/Wind Harmer
0.813
228400MICK 1CT
Adder
16.549
213958STHWK5-6
Adder
3.702
219766PARADISE C
Solar/Wind Harmer
0.425
219686LUMSOLAR_N C
Solar/Wind Harmer
0.271
213560DLW11-12
Adder
3.607
219907AC1-030 C
Solar/Wind Harmer
0.184
219348LDSOLAR C
Solar/Wind Harmer
0.77
219222BRL12CT2
Adder
11.493
213611FALLS1-3
Adder
4.416
20716028EGP_W2-019
Solar/Wind Harmer
0.572
207522AF2-254 C
Solar/Wind Harmer
1.767
214194N WALES4
Adder
1.05
20717128DIX_Z2-102
Solar/Wind Harmer
1.623
20715828PEM_W1-120
Solar/Wind Harmer
0.655
963711AG1-223 GEN
Solar/Wind Harmer
1.733
20714528FRN_Y2-051
Solar/Wind Harmer
0.345
219276PARKLANDSO C
Solar/Wind Harmer
0.537
219680HOPEWELLV C1
Solar/Wind Harmer
0.087
20715228NPK_W1-113
Solar/Wind Harmer
0.488
20720528MAN_W1-024
Solar/Wind Harmer
0.288
20720428HOL_W1-112
Solar/Wind Harmer
0.387
20635828PARLN1&2
Adder
8.01
20635028RRCT1&2
Adder
12.635
218524CNTRALGAS1 C
Solar/Wind Harmer
0.39
218440SUMMTASSOC C
Solar/Wind Harmer
0.135
218428ETC SOLAR C
Solar/Wind Harmer
0.038
219908AB1-139 C
Solar/Wind Harmer
0.399
219919AE1-041 FULL
Solar/Wind Harmer
0.042
972275AH1-722 GEN
Adder
32.686
20673628F1S_V4-069
Solar/Wind Harmer
0.182
207528AF2-192 GEN
Solar/Wind Harmer
1.292
217209CENTRL HS C
Solar/Wind Harmer
0.045
217186ESSEX_G9
Adder
3.903
217121ECCF
Adder
0.429
217083KRNY_132
Adder
9.187
217208PARK ELE C
Solar/Wind Harmer
0.025
20671828STAW2-080
Solar/Wind Harmer
0.103
20676728BRNX1-095
Solar/Wind Harmer
0.166
213815MOSER1-3
Adder
4.564
213535CROYDN11
Adder
13.151
214067T20SOLAR
Solar/Wind Harmer
0.316
20720828JCB_W4-025
Solar/Wind Harmer
0.558
20636128O CRK C2
Adder
7.878
207459AE1-142 C O1
Solar/Wind Harmer
1.266
20628028LAKEHURS
Adder
1.137
20714828MDF_W3-079
Solar/Wind Harmer
0.358
219817TRENTONSOL C
Solar/Wind Harmer
1.268
20641628MLH_W1-032
Solar/Wind Harmer
0.334
20742028HF_AC1-207
Solar/Wind Harmer
0.884
217197RE CRAN C
Solar/Wind Harmer
0.594
218438BLK ROCK C
Solar/Wind Harmer
0.151
924131AB2-057 GEN
Solar/Wind Harmer
1.109
20635028RRCT1&2
Adder
12.441
20635128RRCT3&4
Adder
12.009
20635128RRCT3&4
Adder
10.475
218418LINDEN_G5
Adder
17.78
218419LINDEN_G6
Adder
17.78
972260AH1-715 GEN1
Adder
14.237
219036LINDEN_G7
Adder
17.043
219035LINDEN_G8
Adder
16.799
972261AH1-715 GEN2
Adder
16.314
20675428EAM_W2-061
Solar/Wind Harmer
0.192
217081WEATEXAS C
Solar/Wind Harmer
0.087
217202FBANKSOLAR C
Solar/Wind Harmer
0.074
217201HACKENSOLA C
Solar/Wind Harmer
0.073
972237AH1-703 GEN
Adder
10.01
217206BARNGR HS C
Solar/Wind Harmer
0.03
217086KRNY_131
Adder
9.207
217083KRNY_132
Adder
9.129
217204WCALDSOLAR C
Solar/Wind Harmer
0.072
20674328GAR_V4-001
Solar/Wind Harmer
0.097
20674828DL_W4-046
Solar/Wind Harmer
0.548
207471AF2-354 C
Solar/Wind Harmer
0.433
20634528N27_Y2-018
Solar/Wind Harmer
0.224
20675928HOL_W4-097
Solar/Wind Harmer
0.106
20465127PORT CT
Adder
3.203
209010PEIP 1
Adder
2.203
209010PEIP 1
Adder
0.323
316411AF1-147_GEN1
Solar/Wind Helper
0.819
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.152
316450AC1-158 RIC
Solar/Wind Helper
0.346
966001AG1-469 GEN
Solar/Wind Helper
0.246
238147AE2-230_GEN1
Solar/Wind Helper
0.397
238148AE2-230_GEN2
Solar/Wind Helper
0.397
238149AF1-291A_GEN
Solar/Wind Helper
0.113
235020AA1-095 C
Solar/Wind Helper
0.043
237061AD1-155 GEN
Solar/Wind Helper
1.429
966871AG1-558 GEN
Solar/Wind Helper
0.306
316487AF1-042 GEN
Solar/Wind Helper
0.229
316312AB1-027
Solar/Wind Helper
0.432
3143526WINTERP
Solar/Wind Helper
1.175
315976AC1-164 GENA
Solar/Wind Helper
2.916
316169AC1-164_GENC
Solar/Wind Helper
2.519
315666AE1-190 GEN
Solar/Wind Helper
0.305
316156AD2-030 GEN
Solar/Wind Helper
0.342
3142946ENON
Solar/Wind Helper
0.023
316240AF1-291 C
Solar/Wind Helper
0.303
316033AB2-134 GEN
Solar/Wind Helper
0.779
316313AB2-026
Solar/Wind Helper
0.343
316294AC1-161 GEN
Solar/Wind Helper
4.109
316185AD1-033 GEN
Solar/Wind Helper
1.056
3145506HICKORY
Solar/Wind Helper
0.895
3145506HICKORY
Solar/Wind Helper
0.537
3145506HICKORY
Solar/Wind Helper
0.134
316349AD2-085 GEN
Solar/Wind Helper
1.025
316339AD2-160 GEN
Solar/Wind Helper
0.854
316388AE2-253 GEN
Solar/Wind Helper
0.854
3137176SLIGO L2192
Solar/Wind Helper
0.89
3130086AYDLETT
Solar/Wind Helper
0.894
3146386ELIZ CT
Solar/Wind Helper
0.223
316431W1029_GEN1
Solar/Wind Helper
0.901
316433W1029_GEN2
Solar/Wind Helper
0.901
316435W1029_GEN3
Solar/Wind Helper
0.901
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3144356SAPONY
Solar/Wind Helper
0.399
238221AF1-254 C O1
Solar/Wind Helper
0.22
316315AB2-025 C
Solar/Wind Helper
0.34
200202DELTA2 ST
50/50
11.676
200195DELTA ST
50/50
5.952
200052ROCKSP 1
50/50
4.865
200053ROCKSP 2
50/50
4.77
233901CHERRYDALE C
Solar/Wind Harmer
2.126
232912OH NUG1
Adder
16.693
232913OH NUG2
Adder
16.47
233940AF2-379 C
Solar/Wind Harmer
0.352
232904IR4
Adder
152.764
232432Z2-076 GEN
Solar/Wind Harmer
0.249
971195AH1-057 GEN
Solar/Wind Harmer
1.842
232920IR10
Adder
5.971
233955AB2-172 GEN
Solar/Wind Harmer
9.434
232813VAUGHN
Adder
1.106
233968AD2-076_GEN
Solar/Wind Harmer
12.382
970597AG2-380 GEN
Solar/Wind Harmer
7.775
231906DC3 NUG
Adder
26.084
231902DC CT7
Adder
20.853
231907DC10
Adder
6.512
233915AB1-141 GEN
Solar/Wind Harmer
1.839
231919CHRIST1
Adder
7.815
231920CHRIST2
Adder
7.641
970453AG2-297 GEN
Solar/Wind Harmer
4.02
972141AH1-641 GEN
Solar/Wind Harmer
4.119
230430AE1-229_GEN
Solar/Wind Harmer
40.934
964001AG1-254 GEN
Solar/Wind Harmer
10.417
230422AE1-104_GEN1
Solar/Wind Harmer
47.994
230425AE1-104_GEN2
Solar/Wind Harmer
47.994
228728W1-130C
Solar/Wind Harmer
0.941
230434AG1-499 GEN
Solar/Wind Harmer
0.818
230407AD2-065 C
Solar/Wind Harmer
0.185
227927V4-067C
Solar/Wind Harmer
0.279
219137THOSOLAR C
Solar/Wind Harmer
1.665
219258KINSLEYDEP C
Solar/Wind Harmer
0.44
213942SCHUYLKILL
Adder
4.852
213942SCHUYLKILL
Adder
3.71
213957STHWK3-4
Adder
3.702
213957STHWK3-4
Adder
3.702
213561DLWR9-10
Adder
4.717
213561DLWR9-10
Adder
3.607
219615MILLCREEK C
Solar/Wind Harmer
0.31
219610FLORENCE C
Solar/Wind Harmer
1.783
219224BRL12CT4
Adder
11.493
213611FALLS1-3
Adder
4.416
213611FALLS1-3
Adder
4.416
20720728JCB_W1-129
Solar/Wind Harmer
0.368
20715028HAN_X4-015
Solar/Wind Harmer
0.368
207487AE2-000G4
Solar/Wind Harmer
38.509
207497AE2-000G2
Solar/Wind Harmer
38.509
207500AE2-000G1
Solar/Wind Harmer
38.509
207507AE2-000G3
Solar/Wind Harmer
38.509
963401AG1-189 GEN
Solar/Wind Harmer
2.764
970025AG2-016 GEN
Solar/Wind Harmer
3.436
971189AH1-054 GEN
Solar/Wind Harmer
1.428
207445AB1-138_GEN
Solar/Wind Harmer
0.692
219620RIDERU C
Solar/Wind Harmer
0.064
20714428HOW_X1-037
Solar/Wind Harmer
1.413
20720628TIN_W1-124
Solar/Wind Harmer
1.133
20716228APLW2-078
Solar/Wind Harmer
1.002
971521AH1-258 GEN
Solar/Wind Harmer
3.038
20635928PARLN3&4
Adder
8.01
218526CNTRALGAS2 C
Solar/Wind Harmer
0.392
20675528CPH_W2-050
Solar/Wind Harmer
0.6
20673828FLE_V3-070
Solar/Wind Harmer
0.48
218449LINSOLAR C
Solar/Wind Harmer
1.025
20676128MHD_W3-029
Solar/Wind Harmer
0.485
20676428JCR_X2-075
Solar/Wind Harmer
0.345
217167KRNY_14
Adder
9.187
217086KRNY_131
Adder
9.109
217147KRNY_1212
Adder
8.739
217147KRNY_1212
Adder
8.583
217146KRNY_1234
Adder
8.563
217146KRNY_1234
Adder
8.505
964851AG1-348 GEN
Solar/Wind Harmer
1.14
971009AG2-626 GEN
Solar/Wind Harmer
1.365
207408W3-077 C
Solar/Wind Harmer
0.414
20675128HRM_W1-127
Solar/Wind Harmer
0.136
20462827N BANGR8
Adder
0.568
961261AF2-417 GEN
Solar/Wind Harmer
0.669
209029WAYMART-WD
Solar/Wind Harmer
1.609
209026WIENIPP4
Adder
3.16
3138216PACIFIC
Solar/Wind Helper
0.041
238169AE2-226 GEN1
Solar/Wind Helper
0.572
238170AE2-226 GEN2
Solar/Wind Helper
0.572
315651AD1-115 GEN
Solar/Wind Helper
0.787
3141426STAFORD
Solar/Wind Helper
0.051
316164AC1-076 GEN
Solar/Wind Helper
1.112
316468AD1-105 GEN
Solar/Wind Helper
1.096
3141813NORNECK
Solar/Wind Helper
0.227
3141783LANCAST
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.09
3138133OCRAN
Solar/Wind Helper
0.068
3141913WHIT STONE
Solar/Wind Helper
0.226
316233AE1-074 FULL
Solar/Wind Helper
0.345
316059AD1-063 C
Solar/Wind Helper
0.228
3143873LANEXA
Solar/Wind Helper
0.136
957601AF2-054 GEN
Solar/Wind Helper
0.303
3141873WAN 176
Solar/Wind Helper
0.045
957831AF2-077 GEN
Solar/Wind Helper
0.304
316382AG1-145 C
Solar/Wind Helper
0.304
316159AE1-175 C
Solar/Wind Helper
0.342
315697AD1-025 GEN
Solar/Wind Helper
2.574
315839AE2-212 C
Solar/Wind Helper
0.303
316236AE1-162_GEN
Solar/Wind Helper
0.302
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.257
3143316POE
Solar/Wind Helper
0.888
316316AC1-027 C
Solar/Wind Helper
0.354
316018AA1-139 ULT2
Solar/Wind Helper
0.964
313526AB2-022
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.223
3146486SUNBURY
Solar/Wind Helper
0.223
3145176PASQUOTANK
Solar/Wind Helper
0.138
966261AG1-495 GEN
Solar/Wind Harmer
3.221
207439AE1-081 C O1
Solar/Wind Harmer
0.054
20676328BVR_Y1-020
Solar/Wind Harmer
0.296
20674628WNG_W3-110
Solar/Wind Harmer
0.359
20676228FRD_X1-012
Solar/Wind Harmer
0.523
207530AG1-191 GEN
Solar/Wind Harmer
1.213
20675828AU_W4-064
Solar/Wind Harmer
0.152
20674928WA_W3-044
Solar/Wind Harmer
0.407
971519AH1-257 GEN
Solar/Wind Harmer
2.092
20675728RH_W2-091
Solar/Wind Harmer
0.493
207518AF1-320_GEN
Solar/Wind Harmer
2.976
207484AF2-139 C O1
Solar/Wind Harmer
0.409
20465127PORT CT
Adder
2.414
208909MACR G3
Adder
122.265
211065PSPA IPP
Solar/Wind Harmer
0.315
209010PEIP 1
Adder
0.401
963071AG1-156 GEN
Solar/Wind Harmer
5.994
961301AF2-421 GEN
Solar/Wind Harmer
0.593
963151AG1-164 GEN
Solar/Wind Harmer
0.593
209023WIENIPP1
Adder
6.395
209025WIENIPP3
Adder
3.192
316415AF1-147_GEN2
Solar/Wind Helper
0.819
238175AF1-290_GEN
Solar/Wind Helper
0.127
316447AC1-158 HLD
Solar/Wind Helper
2.855
316044AC1-158 PL1
Solar/Wind Helper
1.297
3147666LOUISA
Solar/Wind Helper
0.92
316192AB2-158 GEN
Solar/Wind Helper
1.55
238152AF2-075_GEN
Solar/Wind Helper
0.567
23777901MDS_W4-102
Solar/Wind Helper
0.144
316337AD2-073 GEN
Solar/Wind Helper
0.346
964211AG1-282 GEN
Solar/Wind Helper
0.306
3141726DUNNSVL
Solar/Wind Helper
0.907
316404AE1-155 C
Solar/Wind Helper
1.94
3142416OLDCHRC
Solar/Wind Helper
0.589
3142416OLDCHRC
Solar/Wind Helper
0.225
3138133OCRAN
Solar/Wind Helper
0.136
3143526WINTERP
Solar/Wind Helper
1.175
3141766HARMONY
Solar/Wind Helper
0.045
315662AE1-191 GEN
Solar/Wind Helper
1.218
316280AD1-041 GEN
Solar/Wind Helper
0.761
315975AC1-164 GENB
Solar/Wind Helper
0.086
3143226MDLTHAN
Solar/Wind Helper
0.226
3142433PROV 92
Solar/Wind Helper
0.904
3142543TWELFTH
Solar/Wind Helper
0.022
316132AB2-190 GEN1
Solar/Wind Helper
1.289
315671AE2-027_GEN
Solar/Wind Helper
1.818
316369SG1_INVT
Solar/Wind Helper
1.085
3145336SMITFLD
Solar/Wind Helper
0.897
315773AC2-141 GEN
Solar/Wind Helper
4.835
316381AD1-082 GEN
Solar/Wind Helper
1.164
316375AC2-012 GEN
Solar/Wind Helper
0.59
316036AC1-147 C
Solar/Wind Helper
0.342
316072AD1-144
Solar/Wind Helper
0.256
3146456SLIGO L269
Solar/Wind Helper
0.224
319010AE1-072 C
Solar/Wind Helper
2.56
3146516WINFALL
Solar/Wind Helper
0.722
3146516WINFALL
Solar/Wind Helper
0.223
200200DELTA2 CT1
50/50
6.895
200193DELTA CT2
50/50
3.853
200203Y1-065-STG
50/50
13.394
200055ROCKSP 4
50/50
4.837
233987AB2-037 GEN
Solar/Wind Harmer
21.561
232907VN8
Adder
56.777
233923SMA
Solar/Wind Harmer
6.906
233997TMININ_4.2
Solar/Wind Harmer
1.884
232406W1-004 FULL
Solar/Wind Harmer
1.889
232914OH NUG3
Adder
16.693
232916OH NUG5
Adder
16.693
232921TASLEY2G
Adder
9.756
232434Z2-077 GEN
Solar/Wind Harmer
0.472
233964AF2-378 GEN
Solar/Wind Harmer
0.241
232417X3-008 C
Solar/Wind Harmer
2.123
233973AC2-185 C
Solar/Wind Harmer
10.216
970695AG2-447 GEN
Solar/Wind Harmer
6.758
233939AC1-091 C
Solar/Wind Harmer
5.057
233972AC1-094 C
Solar/Wind Harmer
4.061
233950AC2-186 GEN
Solar/Wind Harmer
1.059
232422X3-066 FULL
Solar/Wind Harmer
0.466
233933AB2-153 GEN
Solar/Wind Harmer
2.09
233935AB2-179 C
Solar/Wind Harmer
4.541
228711V2-041C
Solar/Wind Harmer
0.87
230415AB2-049 C
Solar/Wind Harmer
0.269
213497CHSTR7-9
Adder
3.861
219623KINSLEYBEA C
Solar/Wind Harmer
0.583
213958STHWK5-6
Adder
3.702
219921AF1-264
Solar/Wind Harmer
0.196
219291REEVESSOUT C
Solar/Wind Harmer
0.081
218660EHAMPSOLAR C
Solar/Wind Harmer
0.234
219914AD2-027 C
Solar/Wind Harmer
0.804
219688LUMSOLAR_S C
Solar/Wind Harmer
0.27
213560DLW11-12
Adder
3.607
219236SOUTHERNHQ C
Solar/Wind Harmer
0.089
219221BRL12CT1
Adder
11.493
219223BRL12CT3
Adder
11.493
213815MOSER1-3
Adder
4.564
959561AF2-247 GEN
Solar/Wind Harmer
0.602
20716428NHV_W2-082
Solar/Wind Harmer
2.191
20715728PEM_W1-119
Solar/Wind Harmer
0.655
20636028O CRK C1
Adder
8.641
963391AG1-188 GEN
Solar/Wind Harmer
4.542
20714928UPF_X1-085
Solar/Wind Harmer
0.49
219114HARTZY_C
Solar/Wind Harmer
1.002
971667AH1-334 GEN
Solar/Wind Harmer
3.296
219727YARDVSOLFA C
Solar/Wind Harmer
1.083
219918AC2-009 C
Solar/Wind Harmer
0.029
207454AA2-184 E
Solar/Wind Harmer
1.136
219612MATRIX C
Solar/Wind Harmer
0.203
20716928W4-060COL
Solar/Wind Harmer
0.784
20635828PARLN1&2
Adder
3.628
20635928PARLN3&4
Adder
3.628
217213AMBOY SO C
Solar/Wind Harmer
0.132
219249CENTRALDIV C
Solar/Wind Harmer
0.041
207442AE1-156 GEN
Solar/Wind Harmer
0.755
20673728F2S_V4-070
Solar/Wind Harmer
0.182
217211CAMDEN ST C
Solar/Wind Harmer
0.024
217169METRODIV C
Solar/Wind Harmer
0.039
217194REDH C
Solar/Wind Harmer
0.486
20674528F3S_W2-016
Solar/Wind Harmer
1.357
207510AF2-138 C
Solar/Wind Harmer
1.581
207511W3-106 GEN
Solar/Wind Harmer
0.293
971007AG2-625 GEN
Solar/Wind Harmer
2.14
207437AD2-070 GEN
Solar/Wind Harmer
0.243
20466127PORT 5CT
Adder
21.343
20671928W4-073
Solar/Wind Harmer
0.345
20674128FR_U2-059
Solar/Wind Harmer
0.147
20633028GILCT9
Adder
22.387
20465427SHAW CT
Adder
3.059
209116AE2-175 GEN
Solar/Wind Harmer
3.017
211065PSPA IPP
Solar/Wind Harmer
0.315
970095AG2-074 GEN
Solar/Wind Harmer
3.796
963161AG1-165 GEN
Solar/Wind Harmer
0.593
209025WIENIPP3
Adder
3.128
208972BECR K09
Solar/Wind Harmer
0.618
3141196NOKESVL
Solar/Wind Helper
0.956
3132273ORANGE
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.529
966881AG1-559 GEN
Solar/Wind Helper
0.309
23546401DTGZ2-030
Solar/Wind Helper
0.072
316223AC1-118
Solar/Wind Helper
0.348
3141906WESTMOR
Solar/Wind Helper
0.091
316077AC2-138 C
Solar/Wind Helper
0.214
316473AC1-191 GEN
Solar/Wind Helper
1.386
316484AD2-074 GEN
Solar/Wind Helper
0.438
316075AC2-137 C
Solar/Wind Helper
0.345
3142946ENON
Solar/Wind Helper
0.075
316458AB2-190 GEN2
Solar/Wind Helper
1.289
3145336SMITFLD
Solar/Wind Helper
0.09
3144536CHRHLND
Solar/Wind Helper
0.034
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.151
316017AA1-139 ULT1
Solar/Wind Helper
1.025
3146456SLIGO L269
Solar/Wind Helper
0.224
316305AF2-043 C
Solar/Wind Helper
0.301
316246AF1-032 C
Solar/Wind Helper
0.256
316320Y1-086
Solar/Wind Helper
0.1
316321Z2-027
Solar/Wind Helper
0.341
3146516WINFALL
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3145273HOLLAND
Solar/Wind Helper
0.167
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.422
VTFLTFEXP_VFT->PJM
CMTX
135.337
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.796
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.239
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.415
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.937
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
54.948
CBM NorthLTFEXP_CBM-N->PJM
CBM
62.953
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.05 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:4638.14
MW Contribution:
6.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
40.582
200201DELTA2 CT2
50/50
6.899
200034PCHBTM 2
50/50
40.193
200205Y1-065-CTG2
50/50
7.75
232926CRISFLD1
Adder
3.719
232410W1-006 C
Solar/Wind Harmer
1.894
232918OH NUG7
Adder
16.622
232905CHERITON_25
Adder
4.648
232428Y3-058 C
Solar/Wind Harmer
1.578
234015AF2-250 C
Solar/Wind Harmer
0.228
233994AC2-023 GEN
Solar/Wind Harmer
5.084
231940T-011
Adder
1.412
233946AB2-136 GEN
Solar/Wind Harmer
7.548
234036AF2-325 C
Solar/Wind Harmer
1.734
234041AC1-190 GEN
Solar/Wind Harmer
16.946
233971AC1-093 C
Solar/Wind Harmer
4.813
232899W1-062
Adder
18.173
233952AC2-187 GEN
Solar/Wind Harmer
2.124
233954AC2-188 GEN
Solar/Wind Harmer
2.124
233984AB2-036 GEN
Solar/Wind Harmer
23.415
232910NRG_G1
Adder
16.235
232424Y1-079 C
Solar/Wind Harmer
1.056
234014AF1-036_GEN
Solar/Wind Harmer
5.067
232436AB1-176 C
Solar/Wind Harmer
0.428
200202DELTA2 ST
50/50
11.684
200195DELTA ST
50/50
5.956
200052ROCKSP 1
50/50
4.876
200053ROCKSP 2
50/50
4.78
200192DELTA CT1
50/50
3.855
200194DELTA CT3
50/50
3.855
233930AB2-032 GEN
Solar/Wind Harmer
1.552
233982AB2-133 GEN
Solar/Wind Harmer
9.063
228251CARLLS#4
Adder
0.91
228201CARL#2CT
Adder
9.916
228200CARL#1CT
Adder
9.431
228351V2-046C
Solar/Wind Harmer
2.884
230511AF1-262
Solar/Wind Harmer
0.261
230433AD2-135 GEN
Solar/Wind Harmer
0.144
228307PCLP GT
Adder
17.18
213589EDDYSTN4
Adder
112.788
213587EDDYSTN3
Adder
112.742
228754AB1-001 C
Solar/Wind Harmer
0.196
972233AH1-701 GEN
Adder
5.905
219904AC1-010 C
Solar/Wind Harmer
0.512
219272CLEANLIGHT C
Solar/Wind Harmer
0.246
219912AD2-042 GEN
Solar/Wind Harmer
1.07
219287REEVESEAST C
Solar/Wind Harmer
1.804
219906AC1-017 C
Solar/Wind Harmer
0.291
219607WPEMNERT C
Solar/Wind Harmer
0.541
219304NAMERICA C
Solar/Wind Harmer
0.4
213815MOSER1-3
Adder
4.575
213815MOSER1-3
Adder
4.575
213535CROYDN11
Adder
13.187
214067T20SOLAR
Solar/Wind Harmer
0.316
20720828JCB_W4-025
Solar/Wind Harmer
0.56
20636128O CRK C2
Adder
7.9
207459AE1-142 C O1
Solar/Wind Harmer
1.269
20628028LAKEHURS
Adder
1.14
20714828MDF_W3-079
Solar/Wind Harmer
0.359
219817TRENTONSOL C
Solar/Wind Harmer
1.272
20641628MLH_W1-032
Solar/Wind Harmer
0.335
20742028HF_AC1-207
Solar/Wind Harmer
0.887
217197RE CRAN C
Solar/Wind Harmer
0.596
218438BLK ROCK C
Solar/Wind Harmer
0.151
924131AB2-057 GEN
Solar/Wind Harmer
1.112
20635028RRCT1&2
Adder
12.479
20635128RRCT3&4
Adder
12.046
20635128RRCT3&4
Adder
10.507
218418LINDEN_G5
Adder
17.836
218419LINDEN_G6
Adder
17.836
972260AH1-715 GEN1
Adder
14.282
219036LINDEN_G7
Adder
17.097
219035LINDEN_G8
Adder
16.853
972261AH1-715 GEN2
Adder
16.366
20675428EAM_W2-061
Solar/Wind Harmer
0.192
217081WEATEXAS C
Solar/Wind Harmer
0.087
217202FBANKSOLAR C
Solar/Wind Harmer
0.074
217201HACKENSOLA C
Solar/Wind Harmer
0.073
972237AH1-703 GEN
Adder
10.042
217206BARNGR HS C
Solar/Wind Harmer
0.031
217086KRNY_131
Adder
9.237
217083KRNY_132
Adder
9.159
217204WCALDSOLAR C
Solar/Wind Harmer
0.072
20674328GAR_V4-001
Solar/Wind Harmer
0.097
20674828DL_W4-046
Solar/Wind Harmer
0.551
207471AF2-354 C
Solar/Wind Harmer
0.435
20634528N27_Y2-018
Solar/Wind Harmer
0.225
20675928HOL_W4-097
Solar/Wind Harmer
0.106
20465127PORT CT
Adder
3.216
209010PEIP 1
Adder
2.213
209010PEIP 1
Adder
0.324
316411AF1-147_GEN1
Solar/Wind Helper
0.82
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.16
316450AC1-158 RIC
Solar/Wind Helper
0.347
966001AG1-469 GEN
Solar/Wind Helper
0.247
238147AE2-230_GEN1
Solar/Wind Helper
0.398
238148AE2-230_GEN2
Solar/Wind Helper
0.398
238149AF1-291A_GEN
Solar/Wind Helper
0.114
235020AA1-095 C
Solar/Wind Helper
0.043
237061AD1-155 GEN
Solar/Wind Helper
1.432
966871AG1-558 GEN
Solar/Wind Helper
0.306
316487AF1-042 GEN
Solar/Wind Helper
0.229
316312AB1-027
Solar/Wind Helper
0.433
3143526WINTERP
Solar/Wind Helper
1.178
315666AE1-190 GEN
Solar/Wind Helper
0.305
316156AD2-030 GEN
Solar/Wind Helper
0.342
315976AC1-164 GENA
Solar/Wind Helper
2.922
316169AC1-164_GENC
Solar/Wind Helper
2.525
3142946ENON
Solar/Wind Helper
0.023
316240AF1-291 C
Solar/Wind Helper
0.304
316033AB2-134 GEN
Solar/Wind Helper
0.781
316313AB2-026
Solar/Wind Helper
0.343
316294AC1-161 GEN
Solar/Wind Helper
4.118
316185AD1-033 GEN
Solar/Wind Helper
1.058
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.538
3145506HICKORY
Solar/Wind Helper
0.134
316349AD2-085 GEN
Solar/Wind Helper
1.027
316339AD2-160 GEN
Solar/Wind Helper
0.856
316388AE2-253 GEN
Solar/Wind Helper
0.856
3137176SLIGO L2192
Solar/Wind Helper
0.892
3130086AYDLETT
Solar/Wind Helper
0.896
3146386ELIZ CT
Solar/Wind Helper
0.224
316431W1029_GEN1
Solar/Wind Helper
0.903
316433W1029_GEN2
Solar/Wind Helper
0.903
316435W1029_GEN3
Solar/Wind Helper
0.903
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3144356SAPONY
Solar/Wind Helper
0.4
316315AB2-025 C
Solar/Wind Helper
0.341
3146626S HERTFORD
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
200200DELTA2 CT1
50/50
6.899
200193DELTA CT2
50/50
3.855
200203Y1-065-STG
50/50
13.421
200055ROCKSP 4
50/50
4.847
233987AB2-037 GEN
Solar/Wind Harmer
21.615
232907VN8
Adder
56.917
233923SMA
Solar/Wind Harmer
6.923
233997TMININ_4.2
Solar/Wind Harmer
1.888
232406W1-004 FULL
Solar/Wind Harmer
1.894
232914OH NUG3
Adder
16.734
232916OH NUG5
Adder
16.734
232921TASLEY2G
Adder
9.78
232434Z2-077 GEN
Solar/Wind Harmer
0.473
233964AF2-378 GEN
Solar/Wind Harmer
0.241
232417X3-008 C
Solar/Wind Harmer
2.128
233973AC2-185 C
Solar/Wind Harmer
10.241
970695AG2-447 GEN
Solar/Wind Harmer
6.775
233939AC1-091 C
Solar/Wind Harmer
5.069
233972AC1-094 C
Solar/Wind Harmer
4.071
233950AC2-186 GEN
Solar/Wind Harmer
1.062
232422X3-066 FULL
Solar/Wind Harmer
0.467
233933AB2-153 GEN
Solar/Wind Harmer
2.095
233935AB2-179 C
Solar/Wind Harmer
4.553
228711V2-041C
Solar/Wind Harmer
0.872
230415AB2-049 C
Solar/Wind Harmer
0.269
213497CHSTR7-9
Adder
3.871
219623KINSLEYBEA C
Solar/Wind Harmer
0.584
213958STHWK5-6
Adder
3.712
219921AF1-264
Solar/Wind Harmer
0.196
219291REEVESSOUT C
Solar/Wind Harmer
0.081
218660EHAMPSOLAR C
Solar/Wind Harmer
0.235
219914AD2-027 C
Solar/Wind Harmer
0.807
219688LUMSOLAR_S C
Solar/Wind Harmer
0.271
213560DLW11-12
Adder
3.617
219236SOUTHERNHQ C
Solar/Wind Harmer
0.09
219221BRL12CT1
Adder
11.524
219223BRL12CT3
Adder
11.524
213815MOSER1-3
Adder
4.575
959561AF2-247 GEN
Solar/Wind Harmer
0.604
20716428NHV_W2-082
Solar/Wind Harmer
2.197
20715728PEM_W1-119
Solar/Wind Harmer
0.657
20636028O CRK C1
Adder
8.665
963391AG1-188 GEN
Solar/Wind Harmer
4.555
20714928UPF_X1-085
Solar/Wind Harmer
0.491
219114HARTZY_C
Solar/Wind Harmer
1.005
971667AH1-334 GEN
Solar/Wind Harmer
3.305
219727YARDVSOLFA C
Solar/Wind Harmer
1.086
219918AC2-009 C
Solar/Wind Harmer
0.029
207454AA2-184 E
Solar/Wind Harmer
1.14
219612MATRIX C
Solar/Wind Harmer
0.204
20716928W4-060COL
Solar/Wind Harmer
0.786
20635828PARLN1&2
Adder
3.639
20635928PARLN3&4
Adder
3.639
217213AMBOY SO C
Solar/Wind Harmer
0.133
219249CENTRALDIV C
Solar/Wind Harmer
0.041
207442AE1-156 GEN
Solar/Wind Harmer
0.758
20673728F2S_V4-070
Solar/Wind Harmer
0.183
217211CAMDEN ST C
Solar/Wind Harmer
0.025
217169METRODIV C
Solar/Wind Harmer
0.039
217194REDH C
Solar/Wind Harmer
0.487
20674528F3S_W2-016
Solar/Wind Harmer
1.362
207510AF2-138 C
Solar/Wind Harmer
1.587
207511W3-106 GEN
Solar/Wind Harmer
0.294
971007AG2-625 GEN
Solar/Wind Harmer
2.148
207437AD2-070 GEN
Solar/Wind Harmer
0.244
20466127PORT 5CT
Adder
21.427
20671928W4-073
Solar/Wind Harmer
0.347
20674128FR_U2-059
Solar/Wind Harmer
0.147
20633028GILCT9
Adder
22.481
20465427SHAW CT
Adder
3.071
209116AE2-175 GEN
Solar/Wind Harmer
3.03
211065PSPA IPP
Solar/Wind Harmer
0.316
970095AG2-074 GEN
Solar/Wind Harmer
3.814
963161AG1-165 GEN
Solar/Wind Harmer
0.596
209025WIENIPP3
Adder
3.142
208972BECR K09
Solar/Wind Harmer
0.62
3141196NOKESVL
Solar/Wind Helper
0.958
3132273ORANGE
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
966881AG1-559 GEN
Solar/Wind Helper
0.31
23546401DTGZ2-030
Solar/Wind Helper
0.072
316223AC1-118
Solar/Wind Helper
0.349
3141906WESTMOR
Solar/Wind Helper
0.091
316077AC2-138 C
Solar/Wind Helper
0.215
316473AC1-191 GEN
Solar/Wind Helper
1.389
316484AD2-074 GEN
Solar/Wind Helper
0.439
316075AC2-137 C
Solar/Wind Helper
0.346
3142946ENON
Solar/Wind Helper
0.076
316458AB2-190 GEN2
Solar/Wind Helper
1.291
3145336SMITFLD
Solar/Wind Helper
0.09
3144536CHRHLND
Solar/Wind Helper
0.034
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.151
316017AA1-139 ULT1
Solar/Wind Helper
1.027
3146456SLIGO L269
Solar/Wind Helper
0.224
316305AF2-043 C
Solar/Wind Helper
0.302
316246AF1-032 C
Solar/Wind Helper
0.257
316320Y1-086
Solar/Wind Helper
0.101
316321Z2-027
Solar/Wind Helper
0.342
3146516WINFALL
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3145273HOLLAND
Solar/Wind Helper
0.167
233901CHERRYDALE C
Solar/Wind Harmer
2.131
232912OH NUG1
Adder
16.734
232913OH NUG2
Adder
16.511
233940AF2-379 C
Solar/Wind Harmer
0.353
232904IR4
Adder
153.14
232432Z2-076 GEN
Solar/Wind Harmer
0.25
971195AH1-057 GEN
Solar/Wind Harmer
1.846
232920IR10
Adder
5.986
233955AB2-172 GEN
Solar/Wind Harmer
9.457
232813VAUGHN
Adder
1.109
233968AD2-076_GEN
Solar/Wind Harmer
12.414
970597AG2-380 GEN
Solar/Wind Harmer
7.795
231906DC3 NUG
Adder
26.15
231902DC CT7
Adder
20.906
231907DC10
Adder
6.528
233915AB1-141 GEN
Solar/Wind Harmer
1.844
231919CHRIST1
Adder
7.835
231920CHRIST2
Adder
7.661
970453AG2-297 GEN
Solar/Wind Harmer
4.03
972141AH1-641 GEN
Solar/Wind Harmer
4.13
230430AE1-229_GEN
Solar/Wind Harmer
41.041
964001AG1-254 GEN
Solar/Wind Harmer
10.444
230422AE1-104_GEN1
Solar/Wind Harmer
48.119
230425AE1-104_GEN2
Solar/Wind Harmer
48.119
228728W1-130C
Solar/Wind Harmer
0.944
230434AG1-499 GEN
Solar/Wind Harmer
0.82
230407AD2-065 C
Solar/Wind Harmer
0.186
227927V4-067C
Solar/Wind Harmer
0.28
219137THOSOLAR C
Solar/Wind Harmer
1.669
219258KINSLEYDEP C
Solar/Wind Harmer
0.442
213942SCHUYLKILL
Adder
4.865
213942SCHUYLKILL
Adder
3.72
213957STHWK3-4
Adder
3.712
213957STHWK3-4
Adder
3.712
213561DLWR9-10
Adder
4.73
213561DLWR9-10
Adder
3.617
219615MILLCREEK C
Solar/Wind Harmer
0.311
219610FLORENCE C
Solar/Wind Harmer
1.788
219224BRL12CT4
Adder
11.524
213611FALLS1-3
Adder
4.428
213611FALLS1-3
Adder
4.428
20720728JCB_W1-129
Solar/Wind Harmer
0.369
20715028HAN_X4-015
Solar/Wind Harmer
0.369
207487AE2-000G4
Solar/Wind Harmer
38.617
207497AE2-000G2
Solar/Wind Harmer
38.617
207500AE2-000G1
Solar/Wind Harmer
38.617
207507AE2-000G3
Solar/Wind Harmer
38.617
963401AG1-189 GEN
Solar/Wind Harmer
2.772
970025AG2-016 GEN
Solar/Wind Harmer
3.445
971189AH1-054 GEN
Solar/Wind Harmer
1.432
207445AB1-138_GEN
Solar/Wind Harmer
0.694
219620RIDERU C
Solar/Wind Harmer
0.064
20714428HOW_X1-037
Solar/Wind Harmer
1.417
20720628TIN_W1-124
Solar/Wind Harmer
1.136
20716228APLW2-078
Solar/Wind Harmer
1.005
971521AH1-258 GEN
Solar/Wind Harmer
3.047
20635928PARLN3&4
Adder
8.034
218526CNTRALGAS2 C
Solar/Wind Harmer
0.394
20675528CPH_W2-050
Solar/Wind Harmer
0.602
20673828FLE_V3-070
Solar/Wind Harmer
0.482
218449LINSOLAR C
Solar/Wind Harmer
1.028
20676128MHD_W3-029
Solar/Wind Harmer
0.487
20676428JCR_X2-075
Solar/Wind Harmer
0.346
217167KRNY_14
Adder
9.217
217086KRNY_131
Adder
9.139
217147KRNY_1212
Adder
8.767
217147KRNY_1212
Adder
8.611
217146KRNY_1234
Adder
8.591
217146KRNY_1234
Adder
8.532
964851AG1-348 GEN
Solar/Wind Harmer
1.144
971009AG2-626 GEN
Solar/Wind Harmer
1.37
207408W3-077 C
Solar/Wind Harmer
0.415
20675128HRM_W1-127
Solar/Wind Harmer
0.136
20462827N BANGR8
Adder
0.57
961261AF2-417 GEN
Solar/Wind Harmer
0.672
209029WAYMART-WD
Solar/Wind Harmer
1.616
209026WIENIPP4
Adder
3.175
3138216PACIFIC
Solar/Wind Helper
0.041
238169AE2-226 GEN1
Solar/Wind Helper
0.574
238170AE2-226 GEN2
Solar/Wind Helper
0.574
315651AD1-115 GEN
Solar/Wind Helper
0.789
316164AC1-076 GEN
Solar/Wind Helper
1.114
3141426STAFORD
Solar/Wind Helper
0.051
316468AD1-105 GEN
Solar/Wind Helper
1.099
3141813NORNECK
Solar/Wind Helper
0.227
3141783LANCAST
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.091
3138133OCRAN
Solar/Wind Helper
0.068
3141913WHIT STONE
Solar/Wind Helper
0.227
316233AE1-074 FULL
Solar/Wind Helper
0.346
316059AD1-063 C
Solar/Wind Helper
0.229
957601AF2-054 GEN
Solar/Wind Helper
0.304
3143873LANEXA
Solar/Wind Helper
0.136
3141873WAN 176
Solar/Wind Helper
0.045
957831AF2-077 GEN
Solar/Wind Helper
0.304
316382AG1-145 C
Solar/Wind Helper
0.304
316159AE1-175 C
Solar/Wind Helper
0.343
315697AD1-025 GEN
Solar/Wind Helper
2.58
315839AE2-212 C
Solar/Wind Helper
0.304
316236AE1-162_GEN
Solar/Wind Helper
0.303
316258AE1-075 C
Solar/Wind Helper
0.309
316405AF2-144 C
Solar/Wind Helper
0.257
3143316POE
Solar/Wind Helper
0.89
316316AC1-027 C
Solar/Wind Helper
0.355
316018AA1-139 ULT2
Solar/Wind Helper
0.967
313526AB2-022
Solar/Wind Helper
0.342
3146486SUNBURY
Solar/Wind Helper
0.224
3146486SUNBURY
Solar/Wind Helper
0.224
3145176PASQUOTANK
Solar/Wind Helper
0.139
315800Z1-036_GEN1
Solar/Wind Helper
1.226
238221AF1-254 C O1
Solar/Wind Helper
0.22
3132123MT JACKSON
Solar/Wind Helper
0.698
200204Y1-065-CTG1
50/50
7.75
200054ROCKSP 3
50/50
4.932
233996TM1833_GEN
Solar/Wind Harmer
1.888
233998TM1NIN_3.36
Solar/Wind Harmer
1.888
232404W1-003 C
Solar/Wind Harmer
1.894
232408W1-005 C
Solar/Wind Harmer
1.894
232917OH NUG6
Adder
16.66
232915OH NUG4
Adder
16.622
234033AF1-007_GEN
Solar/Wind Harmer
70.448
232919VN10
Adder
5.316
232901NORTHST
Adder
15.757
232426Y1-080 FULL
Solar/Wind Harmer
0.362
972177AH1-672 GEN
Solar/Wind Harmer
25.425
233970AC1-092 C
Solar/Wind Harmer
5.069
232900DEMECSMY
Adder
17.431
232902EASTMUNI
Adder
24.596
234012AE2-112_GEN
Solar/Wind Harmer
4.307
233944AB2-135 GEN
Solar/Wind Harmer
9.761
233918AB1-142 GEN
Solar/Wind Harmer
1.844
972251AH1-710 GEN
Adder
80.267
231918WEST 1
Adder
5.968
231917EM10
Adder
4.131
228206SHRMN CT
Adder
24.063
228732V1-021 C
Adder
0.273
228260V4-054C
Solar/Wind Harmer
1.48
970997AG2-616 GEN
Solar/Wind Harmer
13.766
213497CHSTR7-9
Adder
3.871
213497CHSTR7-9
Adder
3.871
228729W2-030 C
Solar/Wind Harmer
0.815
228400MICK 1CT
Adder
16.592
213958STHWK5-6
Adder
3.712
219766PARADISE C
Solar/Wind Harmer
0.426
219686LUMSOLAR_N C
Solar/Wind Harmer
0.271
213560DLW11-12
Adder
3.617
219907AC1-030 C
Solar/Wind Harmer
0.184
219348LDSOLAR C
Solar/Wind Harmer
0.772
219222BRL12CT2
Adder
11.524
213611FALLS1-3
Adder
4.428
20716028EGP_W2-019
Solar/Wind Harmer
0.574
207522AF2-254 C
Solar/Wind Harmer
1.772
214194N WALES4
Adder
1.052
20717128DIX_Z2-102
Solar/Wind Harmer
1.628
20715828PEM_W1-120
Solar/Wind Harmer
0.657
963711AG1-223 GEN
Solar/Wind Harmer
1.738
20714528FRN_Y2-051
Solar/Wind Harmer
0.346
219276PARKLANDSO C
Solar/Wind Harmer
0.539
219680HOPEWELLV C1
Solar/Wind Harmer
0.087
20715228NPK_W1-113
Solar/Wind Harmer
0.489
20720528MAN_W1-024
Solar/Wind Harmer
0.289
20720428HOL_W1-112
Solar/Wind Harmer
0.388
20635828PARLN1&2
Adder
8.034
20635028RRCT1&2
Adder
12.674
218524CNTRALGAS1 C
Solar/Wind Harmer
0.391
218440SUMMTASSOC C
Solar/Wind Harmer
0.135
218428ETC SOLAR C
Solar/Wind Harmer
0.038
219908AB1-139 C
Solar/Wind Harmer
0.4
219919AE1-041 FULL
Solar/Wind Harmer
0.042
972275AH1-722 GEN
Adder
32.789
20673628F1S_V4-069
Solar/Wind Harmer
0.183
207528AF2-192 GEN
Solar/Wind Harmer
1.296
217209CENTRL HS C
Solar/Wind Harmer
0.045
217186ESSEX_G9
Adder
3.916
217121ECCF
Adder
0.431
217083KRNY_132
Adder
9.217
217208PARK ELE C
Solar/Wind Harmer
0.025
20671828STAW2-080
Solar/Wind Harmer
0.103
20676728BRNX1-095
Solar/Wind Harmer
0.167
966261AG1-495 GEN
Solar/Wind Harmer
3.233
207439AE1-081 C O1
Solar/Wind Harmer
0.054
20676328BVR_Y1-020
Solar/Wind Harmer
0.297
20674628WNG_W3-110
Solar/Wind Harmer
0.36
20676228FRD_X1-012
Solar/Wind Harmer
0.525
207530AG1-191 GEN
Solar/Wind Harmer
1.217
20675828AU_W4-064
Solar/Wind Harmer
0.152
20674928WA_W3-044
Solar/Wind Harmer
0.409
971519AH1-257 GEN
Solar/Wind Harmer
2.1
20675728RH_W2-091
Solar/Wind Harmer
0.495
207518AF1-320_GEN
Solar/Wind Harmer
2.988
207484AF2-139 C O1
Solar/Wind Harmer
0.41
20465127PORT CT
Adder
2.423
208909MACR G3
Adder
122.768
211065PSPA IPP
Solar/Wind Harmer
0.316
209010PEIP 1
Adder
0.402
963071AG1-156 GEN
Solar/Wind Harmer
6.022
961301AF2-421 GEN
Solar/Wind Harmer
0.596
963151AG1-164 GEN
Solar/Wind Harmer
0.596
209023WIENIPP1
Adder
6.425
209025WIENIPP3
Adder
3.207
316415AF1-147_GEN2
Solar/Wind Helper
0.82
238175AF1-290_GEN
Solar/Wind Helper
0.128
316447AC1-158 HLD
Solar/Wind Helper
2.861
316044AC1-158 PL1
Solar/Wind Helper
1.3
3147666LOUISA
Solar/Wind Helper
0.922
316192AB2-158 GEN
Solar/Wind Helper
1.553
238152AF2-075_GEN
Solar/Wind Helper
0.568
23777901MDS_W4-102
Solar/Wind Helper
0.144
316337AD2-073 GEN
Solar/Wind Helper
0.347
964211AG1-282 GEN
Solar/Wind Helper
0.306
3141726DUNNSVL
Solar/Wind Helper
0.909
316404AE1-155 C
Solar/Wind Helper
1.944
3142416OLDCHRC
Solar/Wind Helper
0.59
3142416OLDCHRC
Solar/Wind Helper
0.226
3138133OCRAN
Solar/Wind Helper
0.136
3143526WINTERP
Solar/Wind Helper
1.178
3141766HARMONY
Solar/Wind Helper
0.045
315662AE1-191 GEN
Solar/Wind Helper
1.221
316280AD1-041 GEN
Solar/Wind Helper
0.763
315975AC1-164 GENB
Solar/Wind Helper
0.086
3143226MDLTHAN
Solar/Wind Helper
0.226
3142433PROV 92
Solar/Wind Helper
0.905
3142543TWELFTH
Solar/Wind Helper
0.022
316132AB2-190 GEN1
Solar/Wind Helper
1.291
315671AE2-027_GEN
Solar/Wind Helper
1.822
316369SG1_INVT
Solar/Wind Helper
1.087
3145336SMITFLD
Solar/Wind Helper
0.899
315773AC2-141 GEN
Solar/Wind Helper
4.846
316381AD1-082 GEN
Solar/Wind Helper
1.166
316375AC2-012 GEN
Solar/Wind Helper
0.591
316036AC1-147 C
Solar/Wind Helper
0.343
316072AD1-144
Solar/Wind Helper
0.257
3146456SLIGO L269
Solar/Wind Helper
0.224
319010AE1-072 C
Solar/Wind Helper
2.565
3146516WINFALL
Solar/Wind Helper
0.724
3146516WINFALL
Solar/Wind Helper
0.223
315611Z1-036_GEN2
Solar/Wind Helper
1.226
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.437
VTFLTFEXP_VFT->PJM
CMTX
135.774
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.247
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.811
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.985
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.485
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
55.116
CBM NorthLTFEXP_CBM-N->PJM
CBM
63.156
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.33 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:4194.82
MW Contribution:
4.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
3.851
200194DELTA CT3
50/50
3.851
200204Y1-065-CTG1
50/50
7.742
200054ROCKSP 3
50/50
4.927
232404W1-003 C
Solar/Wind Harmer
1.221
232408W1-005 C
Solar/Wind Harmer
1.221
232917OH NUG6
Adder
16.632
232915OH NUG4
Adder
16.595
234033AF1-007_GEN
Solar/Wind Harmer
26.113
232919VN10
Adder
5.307
232901NORTHST
Adder
15.731
972177AH1-672 GEN
Solar/Wind Harmer
19.244
233970AC1-092 C
Solar/Wind Harmer
3.406
232900DEMECSMY
Adder
17.402
232902EASTMUNI
Adder
24.554
234012AE2-112_GEN
Solar/Wind Harmer
4.345
233918AB1-142 GEN
Solar/Wind Harmer
0.474
972251AH1-710 GEN
Adder
80.133
231918WEST 1
Adder
5.957
231917EM10
Adder
4.123
228206SHRMN CT
Adder
24.016
228732V1-021 C
Adder
0.272
970997AG2-616 GEN
Solar/Wind Harmer
10.336
213497CHSTR7-9
Adder
3.862
213497CHSTR7-9
Adder
3.862
228400MICK 1CT
Adder
16.558
213958STHWK5-6
Adder
3.704
213560DLW11-12
Adder
3.609
219222BRL12CT2
Adder
11.498
213611FALLS1-3
Adder
4.418
207522AF2-254 C
Solar/Wind Harmer
1.142
214194N WALES4
Adder
1.05
20635828PARLN1&2
Adder
8.013
20635028RRCT1&2
Adder
12.64
218524CNTRALGAS1 C
Solar/Wind Harmer
0.807
972275AH1-722 GEN
Adder
32.699
207528AF2-192 GEN
Solar/Wind Harmer
0.73
217186ESSEX_G9
Adder
3.904
217121ECCF
Adder
0.429
217083KRNY_132
Adder
9.191
966261AG1-495 GEN
Solar/Wind Harmer
1.574
971519AH1-257 GEN
Solar/Wind Harmer
1.352
20465127PORT CT
Adder
2.415
208909MACR G3
Adder
122.298
209010PEIP 1
Adder
0.401
963071AG1-156 GEN
Solar/Wind Harmer
4.59
209023WIENIPP1
Adder
6.397
209025WIENIPP3
Adder
3.193
316415AF1-147_GEN2
Solar/Wind Helper
0.819
238175AF1-290_GEN
Solar/Wind Helper
0.128
316447AC1-158 HLD
Solar/Wind Helper
2.856
316044AC1-158 PL1
Solar/Wind Helper
1.298
3147666LOUISA
Solar/Wind Helper
0.921
316192AB2-158 GEN
Solar/Wind Helper
1.55
238152AF2-075_GEN
Solar/Wind Helper
0.567
23777901MDS_W4-102
Solar/Wind Helper
0.144
316337AD2-073 GEN
Solar/Wind Helper
0.346
964211AG1-282 GEN
Solar/Wind Helper
0.306
3141726DUNNSVL
Solar/Wind Helper
0.908
316404AE1-155 C
Solar/Wind Helper
1.941
3142416OLDCHRC
Solar/Wind Helper
0.589
3142416OLDCHRC
Solar/Wind Helper
0.226
3138133OCRAN
Solar/Wind Helper
0.136
3143526WINTERP
Solar/Wind Helper
1.176
3141766HARMONY
Solar/Wind Helper
0.045
315662AE1-191 GEN
Solar/Wind Helper
1.219
316280AD1-041 GEN
Solar/Wind Helper
0.762
315975AC1-164 GENB
Solar/Wind Helper
0.086
3143226MDLTHAN
Solar/Wind Helper
0.226
3142433PROV 92
Solar/Wind Helper
0.904
3142543TWELFTH
Solar/Wind Helper
0.022
316132AB2-190 GEN1
Solar/Wind Helper
1.289
315671AE2-027_GEN
Solar/Wind Helper
1.819
316369SG1_INVT
Solar/Wind Helper
1.086
3145336SMITFLD
Solar/Wind Helper
0.897
315773AC2-141 GEN
Solar/Wind Helper
4.837
316381AD1-082 GEN
Solar/Wind Helper
1.164
316375AC2-012 GEN
Solar/Wind Helper
0.59
316036AC1-147 C
Solar/Wind Helper
0.342
316072AD1-144
Solar/Wind Helper
0.256
3146456SLIGO L269
Solar/Wind Helper
0.224
319010AE1-072 C
Solar/Wind Helper
2.561
3146516WINFALL
Solar/Wind Helper
0.722
3146516WINFALL
Solar/Wind Helper
0.223
200035PCHBTM 3
50/50
40.545
200201DELTA2 CT2
50/50
6.893
200034PCHBTM 2
50/50
40.156
200205Y1-065-CTG2
50/50
7.742
232926CRISFLD1
Adder
3.713
232410W1-006 C
Solar/Wind Harmer
1.221
232918OH NUG7
Adder
16.595
232905CHERITON_25
Adder
4.641
231940T-011
Adder
1.41
234041AC1-190 GEN
Solar/Wind Harmer
13.77
233971AC1-093 C
Solar/Wind Harmer
3.406
232899W1-062
Adder
18.143
233984AB2-036 GEN
Solar/Wind Harmer
13.642
232910NRG_G1
Adder
16.207
234014AF1-036_GEN
Solar/Wind Harmer
4.345
233930AB2-032 GEN
Solar/Wind Harmer
1.782
228251CARLLS#4
Adder
0.908
228201CARL#2CT
Adder
9.896
228200CARL#1CT
Adder
9.412
228307PCLP GT
Adder
17.145
213589EDDYSTN4
Adder
112.532
213587EDDYSTN3
Adder
112.486
972233AH1-701 GEN
Adder
5.893
219304NAMERICA C
Solar/Wind Harmer
0.117
213815MOSER1-3
Adder
4.565
213815MOSER1-3
Adder
4.565
213535CROYDN11
Adder
13.157
20636128O CRK C2
Adder
7.882
20628028LAKEHURS
Adder
1.137
20714828MDF_W3-079
Solar/Wind Harmer
0.115
20635028RRCT1&2
Adder
12.446
20635128RRCT3&4
Adder
12.014
20635128RRCT3&4
Adder
10.48
218418LINDEN_G5
Adder
17.787
218419LINDEN_G6
Adder
17.787
972260AH1-715 GEN1
Adder
14.243
219036LINDEN_G7
Adder
17.049
219035LINDEN_G8
Adder
16.806
972261AH1-715 GEN2
Adder
16.32
972237AH1-703 GEN
Adder
10.013
217086KRNY_131
Adder
9.21
217083KRNY_132
Adder
9.132
20465127PORT CT
Adder
3.204
209010PEIP 1
Adder
2.204
209010PEIP 1
Adder
0.323
316411AF1-147_GEN1
Solar/Wind Helper
0.819
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.153
316450AC1-158 RIC
Solar/Wind Helper
0.346
966001AG1-469 GEN
Solar/Wind Helper
0.246
238147AE2-230_GEN1
Solar/Wind Helper
0.397
238148AE2-230_GEN2
Solar/Wind Helper
0.397
238149AF1-291A_GEN
Solar/Wind Helper
0.113
235020AA1-095 C
Solar/Wind Helper
0.043
237061AD1-155 GEN
Solar/Wind Helper
1.429
966871AG1-558 GEN
Solar/Wind Helper
0.306
316487AF1-042 GEN
Solar/Wind Helper
0.229
316312AB1-027
Solar/Wind Helper
0.432
3143526WINTERP
Solar/Wind Helper
1.176
315976AC1-164 GENA
Solar/Wind Helper
2.917
316169AC1-164_GENC
Solar/Wind Helper
2.52
315666AE1-190 GEN
Solar/Wind Helper
0.305
316156AD2-030 GEN
Solar/Wind Helper
0.342
3142946ENON
Solar/Wind Helper
0.023
316240AF1-291 C
Solar/Wind Helper
0.303
316033AB2-134 GEN
Solar/Wind Helper
0.779
316313AB2-026
Solar/Wind Helper
0.343
316294AC1-161 GEN
Solar/Wind Helper
4.111
316185AD1-033 GEN
Solar/Wind Helper
1.056
3145506HICKORY
Solar/Wind Helper
0.895
3145506HICKORY
Solar/Wind Helper
0.537
3145506HICKORY
Solar/Wind Helper
0.134
316349AD2-085 GEN
Solar/Wind Helper
1.025
316339AD2-160 GEN
Solar/Wind Helper
0.854
316388AE2-253 GEN
Solar/Wind Helper
0.854
3137176SLIGO L2192
Solar/Wind Helper
0.89
3130086AYDLETT
Solar/Wind Helper
0.894
3146386ELIZ CT
Solar/Wind Helper
0.223
316431W1029_GEN1
Solar/Wind Helper
0.902
316433W1029_GEN2
Solar/Wind Helper
0.902
316435W1029_GEN3
Solar/Wind Helper
0.902
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
238221AF1-254 C O1
Solar/Wind Helper
0.22
3146626S HERTFORD
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3144356SAPONY
Solar/Wind Helper
0.399
316315AB2-025 C
Solar/Wind Helper
0.34
200200DELTA2 CT1
50/50
6.893
200193DELTA CT2
50/50
3.851
200203Y1-065-STG
50/50
13.408
200055ROCKSP 4
50/50
4.842
233987AB2-037 GEN
Solar/Wind Harmer
-0.003
232907VN8
Adder
56.823
232406W1-004 FULL
Solar/Wind Harmer
1.221
232914OH NUG3
Adder
16.706
232916OH NUG5
Adder
16.706
232921TASLEY2G
Adder
9.764
232434Z2-077 GEN
Solar/Wind Harmer
0.079
233973AC2-185 C
Solar/Wind Harmer
3.406
970695AG2-447 GEN
Solar/Wind Harmer
4.719
233939AC1-091 C
Solar/Wind Harmer
3.406
233972AC1-094 C
Solar/Wind Harmer
3.406
232422X3-066 FULL
Solar/Wind Harmer
0.155
233935AB2-179 C
Solar/Wind Harmer
2.5
213497CHSTR7-9
Adder
3.862
213958STHWK5-6
Adder
3.704
213560DLW11-12
Adder
3.609
219221BRL12CT1
Adder
11.498
219223BRL12CT3
Adder
11.498
213815MOSER1-3
Adder
4.565
20636028O CRK C1
Adder
8.645
963391AG1-188 GEN
Solar/Wind Harmer
2.219
971667AH1-334 GEN
Solar/Wind Harmer
2.131
20635828PARLN1&2
Adder
3.63
20635928PARLN3&4
Adder
3.63
207442AE1-156 GEN
Solar/Wind Harmer
0.06
971007AG2-625 GEN
Solar/Wind Harmer
1.383
207437AD2-070 GEN
Solar/Wind Harmer
0.053
20466127PORT 5CT
Adder
21.35
20633028GILCT9
Adder
22.394
20465427SHAW CT
Adder
3.06
970095AG2-074 GEN
Solar/Wind Harmer
3.044
209025WIENIPP3
Adder
3.128
3141196NOKESVL
Solar/Wind Helper
0.957
3132273ORANGE
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.529
966881AG1-559 GEN
Solar/Wind Helper
0.309
23546401DTGZ2-030
Solar/Wind Helper
0.072
316223AC1-118
Solar/Wind Helper
0.348
3141906WESTMOR
Solar/Wind Helper
0.091
316077AC2-138 C
Solar/Wind Helper
0.214
316473AC1-191 GEN
Solar/Wind Helper
1.387
316484AD2-074 GEN
Solar/Wind Helper
0.438
316075AC2-137 C
Solar/Wind Helper
0.345
3142946ENON
Solar/Wind Helper
0.075
316458AB2-190 GEN2
Solar/Wind Helper
1.289
3145336SMITFLD
Solar/Wind Helper
0.09
3144536CHRHLND
Solar/Wind Helper
0.034
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.151
316017AA1-139 ULT1
Solar/Wind Helper
1.025
3146456SLIGO L269
Solar/Wind Helper
0.224
316305AF2-043 C
Solar/Wind Helper
0.301
316246AF1-032 C
Solar/Wind Helper
0.256
316320Y1-086
Solar/Wind Helper
0.1
316321Z2-027
Solar/Wind Helper
0.341
3146516WINFALL
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3145273HOLLAND
Solar/Wind Helper
0.167
200202DELTA2 ST
50/50
11.673
200195DELTA ST
50/50
5.95
200052ROCKSP 1
50/50
4.871
200053ROCKSP 2
50/50
4.775
232912OH NUG1
Adder
16.706
232913OH NUG2
Adder
16.483
232904IR4
Adder
152.888
232432Z2-076 GEN
Solar/Wind Harmer
0.025
971195AH1-057 GEN
Solar/Wind Harmer
1.182
232920IR10
Adder
5.976
232813VAUGHN
Adder
1.107
233968AD2-076_GEN
Solar/Wind Harmer
4.345
970597AG2-380 GEN
Solar/Wind Harmer
7.782
231906DC3 NUG
Adder
26.105
231902DC CT7
Adder
20.869
231907DC10
Adder
6.517
233915AB1-141 GEN
Solar/Wind Harmer
0.474
231919CHRIST1
Adder
7.82
231920CHRIST2
Adder
7.647
970453AG2-297 GEN
Solar/Wind Harmer
3.713
972141AH1-641 GEN
Solar/Wind Harmer
2.237
230430AE1-229_GEN
Solar/Wind Harmer
28.391
964001AG1-254 GEN
Solar/Wind Harmer
8.069
230422AE1-104_GEN1
Solar/Wind Harmer
19.279
230425AE1-104_GEN2
Solar/Wind Harmer
19.279
213942SCHUYLKILL
Adder
4.854
213942SCHUYLKILL
Adder
3.712
213957STHWK3-4
Adder
3.704
213957STHWK3-4
Adder
3.704
213561DLWR9-10
Adder
4.719
213561DLWR9-10
Adder
3.609
219224BRL12CT4
Adder
11.498
213611FALLS1-3
Adder
4.418
213611FALLS1-3
Adder
4.418
207487AE2-000G4
Solar/Wind Harmer
15.467
207497AE2-000G2
Solar/Wind Harmer
15.467
207500AE2-000G1
Solar/Wind Harmer
15.467
207507AE2-000G3
Solar/Wind Harmer
15.467
963401AG1-189 GEN
Solar/Wind Harmer
1.367
970025AG2-016 GEN
Solar/Wind Harmer
2.221
971189AH1-054 GEN
Solar/Wind Harmer
0.923
971521AH1-258 GEN
Solar/Wind Harmer
1.964
20635928PARLN3&4
Adder
8.013
218526CNTRALGAS2 C
Solar/Wind Harmer
0.812
217167KRNY_14
Adder
9.191
217086KRNY_131
Adder
9.113
217147KRNY_1212
Adder
8.742
217147KRNY_1212
Adder
8.586
217146KRNY_1234
Adder
8.566
217146KRNY_1234
Adder
8.508
971009AG2-626 GEN
Solar/Wind Harmer
0.882
20462827N BANGR8
Adder
0.568
209026WIENIPP4
Adder
3.161
3138216PACIFIC
Solar/Wind Helper
0.041
238169AE2-226 GEN1
Solar/Wind Helper
0.573
238170AE2-226 GEN2
Solar/Wind Helper
0.573
315651AD1-115 GEN
Solar/Wind Helper
0.788
3141426STAFORD
Solar/Wind Helper
0.051
316164AC1-076 GEN
Solar/Wind Helper
1.112
316468AD1-105 GEN
Solar/Wind Helper
1.097
3141813NORNECK
Solar/Wind Helper
0.227
3141783LANCAST
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.09
3138133OCRAN
Solar/Wind Helper
0.068
3141913WHIT STONE
Solar/Wind Helper
0.226
316233AE1-074 FULL
Solar/Wind Helper
0.345
316059AD1-063 C
Solar/Wind Helper
0.229
3143873LANEXA
Solar/Wind Helper
0.136
957601AF2-054 GEN
Solar/Wind Helper
0.303
3141873WAN 176
Solar/Wind Helper
0.045
957831AF2-077 GEN
Solar/Wind Helper
0.304
316382AG1-145 C
Solar/Wind Helper
0.304
316159AE1-175 C
Solar/Wind Helper
0.343
315697AD1-025 GEN
Solar/Wind Helper
2.575
315839AE2-212 C
Solar/Wind Helper
0.303
316236AE1-162_GEN
Solar/Wind Helper
0.302
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.257
3143316POE
Solar/Wind Helper
0.888
316316AC1-027 C
Solar/Wind Helper
0.354
316018AA1-139 ULT2
Solar/Wind Helper
0.965
313526AB2-022
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.223
3146486SUNBURY
Solar/Wind Helper
0.223
3145176PASQUOTANK
Solar/Wind Helper
0.138
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.425
VTFLTFEXP_VFT->PJM
CMTX
135.388
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.798
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.24
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.424
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.944
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
54.971
CBM NorthLTFEXP_CBM-N->PJM
CBM
62.973
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.17 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:3875.5
MW Contribution:
6.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
4.909
200053ROCKSP 2
50/50
4.813
233901CHERRYDALE C
Solar/Wind Harmer
2.15
232912OH NUG1
Adder
16.886
232913OH NUG2
Adder
16.661
233940AF2-379 C
Solar/Wind Harmer
0.356
232904IR4
Adder
154.535
232432Z2-076 GEN
Solar/Wind Harmer
0.252
971195AH1-057 GEN
Solar/Wind Harmer
1.863
232920IR10
Adder
6.04
233955AB2-172 GEN
Solar/Wind Harmer
9.543
232813VAUGHN
Adder
1.119
233968AD2-076_GEN
Solar/Wind Harmer
12.527
970597AG2-380 GEN
Solar/Wind Harmer
7.866
231906DC3 NUG
Adder
26.39
231902DC CT7
Adder
21.097
231907DC10
Adder
6.588
233915AB1-141 GEN
Solar/Wind Harmer
1.861
231919CHRIST1
Adder
7.91
231920CHRIST2
Adder
7.735
970453AG2-297 GEN
Solar/Wind Harmer
4.075
972141AH1-641 GEN
Solar/Wind Harmer
4.176
230430AE1-229_GEN
Solar/Wind Harmer
41.503
964001AG1-254 GEN
Solar/Wind Harmer
10.561
230422AE1-104_GEN1
Solar/Wind Harmer
48.665
230425AE1-104_GEN2
Solar/Wind Harmer
48.665
228728W1-130C
Solar/Wind Harmer
0.954
230434AG1-499 GEN
Solar/Wind Harmer
0.829
230407AD2-065 C
Solar/Wind Harmer
0.188
227927V4-067C
Solar/Wind Harmer
0.283
200204Y1-065-CTG1
50/50
7.804
200054ROCKSP 3
50/50
4.966
233996TM1833_GEN
Solar/Wind Harmer
1.905
233998TM1NIN_3.36
Solar/Wind Harmer
1.905
232404W1-003 C
Solar/Wind Harmer
1.911
232408W1-005 C
Solar/Wind Harmer
1.911
232917OH NUG6
Adder
16.811
232915OH NUG4
Adder
16.774
234033AF1-007_GEN
Solar/Wind Harmer
71.09
232919VN10
Adder
5.364
232901NORTHST
Adder
15.901
232426Y1-080 FULL
Solar/Wind Harmer
0.365
972177AH1-672 GEN
Solar/Wind Harmer
25.657
233970AC1-092 C
Solar/Wind Harmer
5.116
232900DEMECSMY
Adder
17.59
232902EASTMUNI
Adder
24.819
234012AE2-112_GEN
Solar/Wind Harmer
4.346
233944AB2-135 GEN
Solar/Wind Harmer
9.85
233918AB1-142 GEN
Solar/Wind Harmer
1.861
972251AH1-710 GEN
Adder
81.045
231918WEST 1
Adder
6.025
231917EM10
Adder
4.171
228206SHRMN CT
Adder
24.331
228732V1-021 C
Adder
0.276
228260V4-054C
Solar/Wind Harmer
1.497
970997AG2-616 GEN
Solar/Wind Harmer
13.921
213497CHSTR7-9
Adder
3.914
213497CHSTR7-9
Adder
3.914
228729W2-030 C
Solar/Wind Harmer
0.825
228400MICK 1CT
Adder
16.783
213958STHWK5-6
Adder
3.756
219766PARADISE C
Solar/Wind Harmer
0.431
219686LUMSOLAR_N C
Solar/Wind Harmer
0.275
219137THOSOLAR C
Solar/Wind Harmer
1.689
219258KINSLEYDEP C
Solar/Wind Harmer
0.447
213942SCHUYLKILL
Adder
4.922
213942SCHUYLKILL
Adder
3.764
213957STHWK3-4
Adder
3.756
213957STHWK3-4
Adder
3.756
213561DLWR9-10
Adder
4.787
213561DLWR9-10
Adder
3.661
219615MILLCREEK C
Solar/Wind Harmer
0.315
219610FLORENCE C
Solar/Wind Harmer
1.81
219224BRL12CT4
Adder
11.669
213611FALLS1-3
Adder
4.486
213611FALLS1-3
Adder
4.486
20720728JCB_W1-129
Solar/Wind Harmer
0.374
20715028HAN_X4-015
Solar/Wind Harmer
0.373
207487AE2-000G4
Solar/Wind Harmer
39.134
207497AE2-000G2
Solar/Wind Harmer
39.134
207500AE2-000G1
Solar/Wind Harmer
39.134
207507AE2-000G3
Solar/Wind Harmer
39.134
963401AG1-189 GEN
Solar/Wind Harmer
2.809
970025AG2-016 GEN
Solar/Wind Harmer
3.492
971189AH1-054 GEN
Solar/Wind Harmer
1.452
207445AB1-138_GEN
Solar/Wind Harmer
0.704
219620RIDERU C
Solar/Wind Harmer
0.065
20714428HOW_X1-037
Solar/Wind Harmer
1.438
20720628TIN_W1-124
Solar/Wind Harmer
1.153
20716228APLW2-078
Solar/Wind Harmer
1.02
971521AH1-258 GEN
Solar/Wind Harmer
3.093
20635928PARLN3&4
Adder
8.16
218526CNTRALGAS2 C
Solar/Wind Harmer
0.4
20675528CPH_W2-050
Solar/Wind Harmer
0.611
20673828FLE_V3-070
Solar/Wind Harmer
0.49
218449LINSOLAR C
Solar/Wind Harmer
1.045
20676128MHD_W3-029
Solar/Wind Harmer
0.495
20676428JCR_X2-075
Solar/Wind Harmer
0.352
217167KRNY_14
Adder
9.379
217086KRNY_131
Adder
9.299
217147KRNY_1212
Adder
8.921
217147KRNY_1212
Adder
8.762
217146KRNY_1234
Adder
8.742
217146KRNY_1234
Adder
8.682
964851AG1-348 GEN
Solar/Wind Harmer
1.169
971009AG2-626 GEN
Solar/Wind Harmer
1.4
207408W3-077 C
Solar/Wind Harmer
0.425
20675128HRM_W1-127
Solar/Wind Harmer
0.139
20462827N BANGR8
Adder
0.583
961261AF2-417 GEN
Solar/Wind Harmer
0.692
209029WAYMART-WD
Solar/Wind Harmer
1.667
209026WIENIPP4
Adder
3.278
3138216PACIFIC
Solar/Wind Helper
0.039
238169AE2-226 GEN1
Solar/Wind Helper
0.549
238170AE2-226 GEN2
Solar/Wind Helper
0.549
315651AD1-115 GEN
Solar/Wind Helper
0.756
3141426STAFORD
Solar/Wind Helper
0.049
316164AC1-076 GEN
Solar/Wind Helper
1.067
213560DLW11-12
Adder
3.661
219907AC1-030 C
Solar/Wind Harmer
0.186
219348LDSOLAR C
Solar/Wind Harmer
0.782
219222BRL12CT2
Adder
11.669
213611FALLS1-3
Adder
4.486
20716028EGP_W2-019
Solar/Wind Harmer
0.581
207522AF2-254 C
Solar/Wind Harmer
1.796
214194N WALES4
Adder
1.066
20717128DIX_Z2-102
Solar/Wind Harmer
1.649
20715828PEM_W1-120
Solar/Wind Harmer
0.666
963711AG1-223 GEN
Solar/Wind Harmer
1.763
20714528FRN_Y2-051
Solar/Wind Harmer
0.351
219276PARKLANDSO C
Solar/Wind Harmer
0.547
219680HOPEWELLV C1
Solar/Wind Harmer
0.088
20715228NPK_W1-113
Solar/Wind Harmer
0.496
20720528MAN_W1-024
Solar/Wind Harmer
0.293
20720428HOL_W1-112
Solar/Wind Harmer
0.393
20635828PARLN1&2
Adder
8.16
20635028RRCT1&2
Adder
12.874
218524CNTRALGAS1 C
Solar/Wind Harmer
0.397
218440SUMMTASSOC C
Solar/Wind Harmer
0.137
218428ETC SOLAR C
Solar/Wind Harmer
0.038
219908AB1-139 C
Solar/Wind Harmer
0.406
219919AE1-041 FULL
Solar/Wind Harmer
0.043
972275AH1-722 GEN
Adder
33.331
20673628F1S_V4-069
Solar/Wind Harmer
0.186
207528AF2-192 GEN
Solar/Wind Harmer
1.318
217209CENTRL HS C
Solar/Wind Harmer
0.046
217186ESSEX_G9
Adder
3.984
217121ECCF
Adder
0.438
217083KRNY_132
Adder
9.379
217208PARK ELE C
Solar/Wind Harmer
0.026
20671828STAW2-080
Solar/Wind Harmer
0.105
20676728BRNX1-095
Solar/Wind Harmer
0.17
966261AG1-495 GEN
Solar/Wind Harmer
3.294
207439AE1-081 C O1
Solar/Wind Harmer
0.055
20676328BVR_Y1-020
Solar/Wind Harmer
0.303
20674628WNG_W3-110
Solar/Wind Harmer
0.367
20676228FRD_X1-012
Solar/Wind Harmer
0.535
207530AG1-191 GEN
Solar/Wind Harmer
1.242
20675828AU_W4-064
Solar/Wind Harmer
0.155
20674928WA_W3-044
Solar/Wind Harmer
0.417
971519AH1-257 GEN
Solar/Wind Harmer
2.146
20675728RH_W2-091
Solar/Wind Harmer
0.505
207518AF1-320_GEN
Solar/Wind Harmer
3.054
207484AF2-139 C O1
Solar/Wind Harmer
0.419
20465127PORT CT
Adder
2.478
208909MACR G3
Adder
125.696
211065PSPA IPP
Solar/Wind Harmer
0.325
209010PEIP 1
Adder
0.415
963071AG1-156 GEN
Solar/Wind Harmer
6.215
961301AF2-421 GEN
Solar/Wind Harmer
0.615
963151AG1-164 GEN
Solar/Wind Harmer
0.615
209023WIENIPP1
Adder
6.634
209025WIENIPP3
Adder
3.312
316415AF1-147_GEN2
Solar/Wind Helper
0.787
238175AF1-290_GEN
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
2.741
316044AC1-158 PL1
Solar/Wind Helper
1.245
200035PCHBTM 3
50/50
40.849
200034PCHBTM 2
50/50
40.459
200205Y1-065-CTG2
50/50
7.804
232926CRISFLD1
Adder
3.753
232410W1-006 C
Solar/Wind Harmer
1.911
232918OH NUG7
Adder
16.774
232905CHERITON_25
Adder
4.691
232428Y3-058 C
Solar/Wind Harmer
1.592
234015AF2-250 C
Solar/Wind Harmer
0.23
233994AC2-023 GEN
Solar/Wind Harmer
5.131
231940T-011
Adder
1.425
233946AB2-136 GEN
Solar/Wind Harmer
7.617
234036AF2-325 C
Solar/Wind Harmer
1.75
234041AC1-190 GEN
Solar/Wind Harmer
17.1
233971AC1-093 C
Solar/Wind Harmer
4.857
232899W1-062
Adder
18.339
233952AC2-187 GEN
Solar/Wind Harmer
2.143
233954AC2-188 GEN
Solar/Wind Harmer
2.143
233984AB2-036 GEN
Solar/Wind Harmer
23.628
232910NRG_G1
Adder
16.383
232424Y1-079 C
Solar/Wind Harmer
1.066
234014AF1-036_GEN
Solar/Wind Harmer
5.113
232436AB1-176 C
Solar/Wind Harmer
0.432
233930AB2-032 GEN
Solar/Wind Harmer
1.566
233982AB2-133 GEN
Solar/Wind Harmer
9.146
228251CARLLS#4
Adder
0.92
228201CARL#2CT
Adder
10.027
228200CARL#1CT
Adder
9.536
228351V2-046C
Solar/Wind Harmer
2.917
230511AF1-262
Solar/Wind Harmer
0.264
230433AD2-135 GEN
Solar/Wind Harmer
0.146
228307PCLP GT
Adder
17.375
213589EDDYSTN4
Adder
114.051
213587EDDYSTN3
Adder
114.005
228754AB1-001 C
Solar/Wind Harmer
0.198
972233AH1-701 GEN
Adder
5.973
219904AC1-010 C
Solar/Wind Harmer
0.518
219272CLEANLIGHT C
Solar/Wind Harmer
0.249
219912AD2-042 GEN
Solar/Wind Harmer
1.082
219287REEVESEAST C
Solar/Wind Harmer
1.826
219906AC1-017 C
Solar/Wind Harmer
0.295
219607WPEMNERT C
Solar/Wind Harmer
0.547
219304NAMERICA C
Solar/Wind Harmer
0.405
213815MOSER1-3
Adder
4.633
213815MOSER1-3
Adder
4.633
213535CROYDN11
Adder
13.353
214067T20SOLAR
Solar/Wind Harmer
0.321
20720828JCB_W4-025
Solar/Wind Harmer
0.567
20636128O CRK C2
Adder
8.006
207459AE1-142 C O1
Solar/Wind Harmer
1.287
20628028LAKEHURS
Adder
1.156
20714828MDF_W3-079
Solar/Wind Harmer
0.364
219817TRENTONSOL C
Solar/Wind Harmer
1.29
20641628MLH_W1-032
Solar/Wind Harmer
0.34
20742028HF_AC1-207
Solar/Wind Harmer
0.9
217197RE CRAN C
Solar/Wind Harmer
0.605
218438BLK ROCK C
Solar/Wind Harmer
0.153
924131AB2-057 GEN
Solar/Wind Harmer
1.13
20635028RRCT1&2
Adder
12.676
20635128RRCT3&4
Adder
12.236
20635128RRCT3&4
Adder
10.674
218418LINDEN_G5
Adder
18.131
218419LINDEN_G6
Adder
18.131
972260AH1-715 GEN1
Adder
14.518
219036LINDEN_G7
Adder
17.385
219035LINDEN_G8
Adder
17.137
972261AH1-715 GEN2
Adder
16.642
20675428EAM_W2-061
Solar/Wind Harmer
0.196
217081WEATEXAS C
Solar/Wind Harmer
0.088
217202FBANKSOLAR C
Solar/Wind Harmer
0.075
217201HACKENSOLA C
Solar/Wind Harmer
0.074
972237AH1-703 GEN
Adder
10.218
217206BARNGR HS C
Solar/Wind Harmer
0.031
217086KRNY_131
Adder
9.399
217083KRNY_132
Adder
9.319
217204WCALDSOLAR C
Solar/Wind Harmer
0.073
20674328GAR_V4-001
Solar/Wind Harmer
0.099
200203Y1-065-STG
50/50
13.515
200055ROCKSP 4
50/50
4.881
233987AB2-037 GEN
Solar/Wind Harmer
21.811
232907VN8
Adder
57.434
233923SMA
Solar/Wind Harmer
6.986
233997TMININ_4.2
Solar/Wind Harmer
1.905
232406W1-004 FULL
Solar/Wind Harmer
1.911
232914OH NUG3
Adder
16.886
232916OH NUG5
Adder
16.886
232921TASLEY2G
Adder
9.869
232434Z2-077 GEN
Solar/Wind Harmer
0.478
233964AF2-378 GEN
Solar/Wind Harmer
0.244
232417X3-008 C
Solar/Wind Harmer
2.147
233973AC2-185 C
Solar/Wind Harmer
10.335
970695AG2-447 GEN
Solar/Wind Harmer
6.837
233939AC1-091 C
Solar/Wind Harmer
5.116
233972AC1-094 C
Solar/Wind Harmer
4.108
233950AC2-186 GEN
Solar/Wind Harmer
1.072
232422X3-066 FULL
Solar/Wind Harmer
0.471
233933AB2-153 GEN
Solar/Wind Harmer
2.114
233935AB2-179 C
Solar/Wind Harmer
4.596
228711V2-041C
Solar/Wind Harmer
0.882
230415AB2-049 C
Solar/Wind Harmer
0.272
213497CHSTR7-9
Adder
3.914
219623KINSLEYBEA C
Solar/Wind Harmer
0.591
213958STHWK5-6
Adder
3.756
219921AF1-264
Solar/Wind Harmer
0.199
219291REEVESSOUT C
Solar/Wind Harmer
0.082
218660EHAMPSOLAR C
Solar/Wind Harmer
0.238
219914AD2-027 C
Solar/Wind Harmer
0.816
219688LUMSOLAR_S C
Solar/Wind Harmer
0.274
213560DLW11-12
Adder
3.661
219236SOUTHERNHQ C
Solar/Wind Harmer
0.091
219221BRL12CT1
Adder
11.669
219223BRL12CT3
Adder
11.669
213815MOSER1-3
Adder
4.633
959561AF2-247 GEN
Solar/Wind Harmer
0.612
20716428NHV_W2-082
Solar/Wind Harmer
2.226
20715728PEM_W1-119
Solar/Wind Harmer
0.666
20636028O CRK C1
Adder
8.781
963391AG1-188 GEN
Solar/Wind Harmer
4.617
20714928UPF_X1-085
Solar/Wind Harmer
0.498
219114HARTZY_C
Solar/Wind Harmer
1.018
971667AH1-334 GEN
Solar/Wind Harmer
3.351
219727YARDVSOLFA C
Solar/Wind Harmer
1.101
219918AC2-009 C
Solar/Wind Harmer
0.03
207454AA2-184 E
Solar/Wind Harmer
1.156
219612MATRIX C
Solar/Wind Harmer
0.207
20716928W4-060COL
Solar/Wind Harmer
0.798
20635828PARLN1&2
Adder
3.696
20635928PARLN3&4
Adder
3.696
217213AMBOY SO C
Solar/Wind Harmer
0.135
219249CENTRALDIV C
Solar/Wind Harmer
0.042
20674828DL_W4-046
Solar/Wind Harmer
0.562
207471AF2-354 C
Solar/Wind Harmer
0.444
20634528N27_Y2-018
Solar/Wind Harmer
0.23
20675928HOL_W4-097
Solar/Wind Harmer
0.108
20465127PORT CT
Adder
3.289
209010PEIP 1
Adder
2.283
209010PEIP 1
Adder
0.334
316411AF1-147_GEN1
Solar/Wind Helper
0.787
316006AB2-029 C
Solar/Wind Helper
0.108
316045AC1-158 PL2
Solar/Wind Helper
3.985
316450AC1-158 RIC
Solar/Wind Helper
0.332
207442AE1-156 GEN
Solar/Wind Harmer
0.771
20673728F2S_V4-070
Solar/Wind Harmer
0.186
217211CAMDEN ST C
Solar/Wind Harmer
0.025
217169METRODIV C
Solar/Wind Harmer
0.04
217194REDH C
Solar/Wind Harmer
0.496
20674528F3S_W2-016
Solar/Wind Harmer
1.386
207510AF2-138 C
Solar/Wind Harmer
1.618
207511W3-106 GEN
Solar/Wind Harmer
0.3
971007AG2-625 GEN
Solar/Wind Harmer
2.194
207437AD2-070 GEN
Solar/Wind Harmer
0.25
20466127PORT 5CT
Adder
21.911
20671928W4-073
Solar/Wind Harmer
0.354
20674128FR_U2-059
Solar/Wind Harmer
0.151
20633028GILCT9
Adder
22.995
20465427SHAW CT
Adder
3.143
209116AE2-175 GEN
Solar/Wind Harmer
3.106
211065PSPA IPP
Solar/Wind Harmer
0.325
970095AG2-074 GEN
Solar/Wind Harmer
3.936
963161AG1-165 GEN
Solar/Wind Harmer
0.615
209025WIENIPP3
Adder
3.245
208972BECR K09
Solar/Wind Harmer
0.641
3141196NOKESVL
Solar/Wind Helper
0.919
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.18
VTFLTFEXP_VFT->PJM
CMTX
138.123
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.562
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.091
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.329
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.209
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
55.987
CBM NorthLTFEXP_CBM-N->PJM
CBM
65.052
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019E_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019E_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.91 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:5462.93
MW Contribution:
6.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
9.518
200195DELTA ST
50/50
4.852
200052ROCKSP 1
50/50
4.043
200053ROCKSP 2
50/50
3.963
232904IR4
Adder
140.512
232920IR10
Adder
5.492
232432Z2-076 GEN
Solar/Wind Harmer
0.229
233901CHERRYDALE C
Solar/Wind Harmer
1.954
232912OH NUG1
Adder
15.343
232913OH NUG2
Adder
15.138
233940AF2-379 C
Solar/Wind Harmer
0.324
971195AH1-057 GEN
Solar/Wind Harmer
1.693
233955AB2-172 GEN
Solar/Wind Harmer
8.661
232813VAUGHN
Adder
1.017
231906DC3 NUG
Adder
23.95
231902DC CT7
Adder
19.147
231907DC10
Adder
5.979
233968AD2-076_GEN
Solar/Wind Harmer
11.349
970597AG2-380 GEN
Solar/Wind Harmer
7.126
233915AB1-141 GEN
Solar/Wind Harmer
1.685
231919CHRIST1
Adder
7.292
231920CHRIST2
Adder
7.13
970453AG2-297 GEN
Solar/Wind Harmer
4.089
972141AH1-641 GEN
Solar/Wind Harmer
4.222
230422AE1-104_GEN1
Solar/Wind Harmer
49.478
230425AE1-104_GEN2
Solar/Wind Harmer
49.478
230430AE1-229_GEN
Solar/Wind Harmer
41.994
964001AG1-254 GEN
Solar/Wind Harmer
10.68
228728W1-130C
Solar/Wind Harmer
0.971
227927V4-067C
Solar/Wind Harmer
0.29
230407AD2-065 C
Solar/Wind Harmer
0.192
230434AG1-499 GEN
Solar/Wind Harmer
0.844
219137THOSOLAR C
Solar/Wind Harmer
1.737
219258KINSLEYDEP C
Solar/Wind Harmer
0.463
213942SCHUYLKILL
Adder
5.014
213942SCHUYLKILL
Adder
3.835
213957STHWK3-4
Adder
3.834
213957STHWK3-4
Adder
3.834
219615MILLCREEK C
Solar/Wind Harmer
0.335
213561DLWR9-10
Adder
4.99
213561DLWR9-10
Adder
3.816
219610FLORENCE C
Solar/Wind Harmer
1.941
219224BRL12CT4
Adder
12.513
213611FALLS1-3
Adder
4.906
213611FALLS1-3
Adder
4.906
20720728JCB_W1-129
Solar/Wind Harmer
0.413
20715028HAN_X4-015
Solar/Wind Harmer
0.413
207487AE2-000G4
Solar/Wind Harmer
43.606
207497AE2-000G2
Solar/Wind Harmer
43.606
207500AE2-000G1
Solar/Wind Harmer
43.606
207507AE2-000G3
Solar/Wind Harmer
43.606
963401AG1-189 GEN
Solar/Wind Harmer
3.143
970025AG2-016 GEN
Solar/Wind Harmer
3.914
971189AH1-054 GEN
Solar/Wind Harmer
1.629
207445AB1-138_GEN
Solar/Wind Harmer
0.797
219620RIDERU C
Solar/Wind Harmer
0.076
20714428HOW_X1-037
Solar/Wind Harmer
1.681
20720628TIN_W1-124
Solar/Wind Harmer
1.353
20716228APLW2-078
Solar/Wind Harmer
1.2
971521AH1-258 GEN
Solar/Wind Harmer
3.667
20635928PARLN3&4
Adder
9.946
218526CNTRALGAS2 C
Solar/Wind Harmer
0.495
20675528CPH_W2-050
Solar/Wind Harmer
0.764
20673828FLE_V3-070
Solar/Wind Harmer
0.619
218449LINSOLAR C
Solar/Wind Harmer
1.334
20676128MHD_W3-029
Solar/Wind Harmer
0.632
20676428JCR_X2-075
Solar/Wind Harmer
0.452
217167KRNY_14
Adder
12.245
217086KRNY_131
Adder
12.141
217147KRNY_1212
Adder
11.647
217147KRNY_1212
Adder
11.439
217146KRNY_1234
Adder
11.413
217146KRNY_1234
Adder
11.335
964851AG1-348 GEN
Solar/Wind Harmer
1.74
971009AG2-626 GEN
Solar/Wind Harmer
2.086
207408W3-077 C
Solar/Wind Harmer
0.642
20675128HRM_W1-127
Solar/Wind Harmer
0.215
20462827N BANGR8
Adder
0.904
961261AF2-417 GEN
Solar/Wind Harmer
1.2
209026WIENIPP4
Adder
6.296
209029WAYMART-WD
Solar/Wind Harmer
3.021
209027LOR2_Q27
Solar/Wind Harmer
5.166
212266LOR1
Solar/Wind Harmer
1.369
209054AE2-059 GEN
Solar/Wind Harmer
1.841
959431AF2-234 GEN
Solar/Wind Harmer
2.152
964051AG1-259 GEN
Solar/Wind Harmer
1.443
964061AG1-260 GEN
Solar/Wind Harmer
1.443
959421AF2-233 GEN
Solar/Wind Harmer
1.076
20486527WR_V4-052
Adder
1.044
208862AG1-362 C
Solar/Wind Harmer
0.705
20390726Y2-042
Adder
2.941
209067AE2-060 GEN
Solar/Wind Harmer
1.216
200917MEHOOPANY_G
Solar/Wind Harmer
3.765
20334726NME_Y1-047
Adder
2.531
203926AA2-133 GEN
Adder
2.289
226929AD2-058 GEN
Solar/Wind Helper
0.145
3138216PACIFIC
Solar/Wind Helper
0.054
3141426STAFORD
Solar/Wind Helper
0.07
315651AD1-115 GEN
Solar/Wind Helper
1.04
316164AC1-076 GEN
Solar/Wind Helper
1.472
316468AD1-105 GEN
Solar/Wind Helper
1.452
3141813NORNECK
Solar/Wind Helper
0.299
3141783LANCAST
Solar/Wind Helper
0.178
3141783LANCAST
Solar/Wind Helper
0.119
3138133OCRAN
Solar/Wind Helper
0.089
3141913WHIT STONE
Solar/Wind Helper
0.296
316059AD1-063 C
Solar/Wind Helper
0.299
957601AF2-054 GEN
Solar/Wind Helper
0.396
3141873WAN 176
Solar/Wind Helper
0.059
3143873LANEXA
Solar/Wind Helper
0.177
316233AE1-074 FULL
Solar/Wind Helper
0.45
957831AF2-077 GEN
Solar/Wind Helper
0.396
238169AE2-226 GEN1
Solar/Wind Helper
0.718
238170AE2-226 GEN2
Solar/Wind Helper
0.718
316382AG1-145 C
Solar/Wind Helper
0.395
316159AE1-175 C
Solar/Wind Helper
0.446
315697AD1-025 GEN
Solar/Wind Helper
3.344
315839AE2-212 C
Solar/Wind Helper
0.393
316236AE1-162_GEN
Solar/Wind Helper
0.392
3143316POE
Solar/Wind Helper
1.15
316316AC1-027 C
Solar/Wind Helper
0.458
316258AE1-075 C
Solar/Wind Helper
0.398
316405AF2-144 C
Solar/Wind Helper
0.331
316018AA1-139 ULT2
Solar/Wind Helper
1.246
313526AB2-022
Solar/Wind Helper
0.44
3146486SUNBURY
Solar/Wind Helper
0.288
3146486SUNBURY
Solar/Wind Helper
0.288
3145176PASQUOTANK
Solar/Wind Helper
0.178
315800Z1-036_GEN1
Solar/Wind Helper
1.569
200192DELTA CT1
50/50
3.14
200194DELTA CT3
50/50
3.14
200204Y1-065-CTG1
50/50
6.426
200054ROCKSP 3
50/50
4.089
232901NORTHST
Adder
14.493
233970AC1-092 C
Solar/Wind Harmer
4.668
234033AF1-007_GEN
Solar/Wind Harmer
64.639
232900DEMECSMY
Adder
16.032
972177AH1-672 GEN
Solar/Wind Harmer
23.34
232404W1-003 C
Solar/Wind Harmer
1.737
232408W1-005 C
Solar/Wind Harmer
1.737
232917OH NUG6
Adder
15.275
232915OH NUG4
Adder
15.24
233996TM1833_GEN
Solar/Wind Harmer
1.731
233998TM1NIN_3.36
Solar/Wind Harmer
1.731
232919VN10
Adder
4.87
232426Y1-080 FULL
Solar/Wind Harmer
0.331
232902EASTMUNI
Adder
22.499
234012AE2-112_GEN
Solar/Wind Harmer
3.937
233944AB2-135 GEN
Solar/Wind Harmer
8.93
972251AH1-710 GEN
Adder
76.383
233918AB1-142 GEN
Solar/Wind Harmer
1.685
231918WEST 1
Adder
5.544
231917EM10
Adder
3.863
228206SHRMN CT
Adder
24.494
228732V1-021 C
Adder
0.279
228260V4-054C
Solar/Wind Harmer
1.51
970997AG2-616 GEN
Solar/Wind Harmer
14.073
228729W2-030 C
Solar/Wind Harmer
0.843
228400MICK 1CT
Adder
17.12
219686LUMSOLAR_N C
Solar/Wind Harmer
0.289
219766PARADISE C
Solar/Wind Harmer
0.449
213497CHSTR7-9
Adder
3.882
213497CHSTR7-9
Adder
3.882
219907AC1-030 C
Solar/Wind Harmer
0.196
213958STHWK5-6
Adder
3.834
213560DLW11-12
Adder
3.816
219348LDSOLAR C
Solar/Wind Harmer
0.839
219222BRL12CT2
Adder
12.513
20716028EGP_W2-019
Solar/Wind Harmer
0.643
213611FALLS1-3
Adder
4.906
207522AF2-254 C
Solar/Wind Harmer
1.989
20717128DIX_Z2-102
Solar/Wind Harmer
1.829
20715828PEM_W1-120
Solar/Wind Harmer
0.74
214194N WALES4
Adder
1.176
963711AG1-223 GEN
Solar/Wind Harmer
2.026
20714528FRN_Y2-051
Solar/Wind Harmer
0.404
219276PARKLANDSO C
Solar/Wind Harmer
0.629
20715228NPK_W1-113
Solar/Wind Harmer
0.584
20720528MAN_W1-024
Solar/Wind Harmer
0.345
219680HOPEWELLV C1
Solar/Wind Harmer
0.103
20720428HOL_W1-112
Solar/Wind Harmer
0.468
20635828PARLN1&2
Adder
9.946
20635028RRCT1&2
Adder
15.806
218524CNTRALGAS1 C
Solar/Wind Harmer
0.494
218440SUMMTASSOC C
Solar/Wind Harmer
0.171
218428ETC SOLAR C
Solar/Wind Harmer
0.048
219908AB1-139 C
Solar/Wind Harmer
0.508
219919AE1-041 FULL
Solar/Wind Harmer
0.054
972275AH1-722 GEN
Adder
42.015
20673628F1S_V4-069
Solar/Wind Harmer
0.238
207528AF2-192 GEN
Solar/Wind Harmer
1.682
217209CENTRL HS C
Solar/Wind Harmer
0.059
217186ESSEX_G9
Adder
5.2
217121ECCF
Adder
0.572
217083KRNY_132
Adder
12.245
217208PARK ELE C
Solar/Wind Harmer
0.033
20671828STAW2-080
Solar/Wind Harmer
0.138
20676728BRNX1-095
Solar/Wind Harmer
0.23
966261AG1-495 GEN
Solar/Wind Harmer
4.539
207439AE1-081 C O1
Solar/Wind Harmer
0.077
20676328BVR_Y1-020
Solar/Wind Harmer
0.427
20674628WNG_W3-110
Solar/Wind Harmer
0.52
20676228FRD_X1-012
Solar/Wind Harmer
0.761
207530AG1-191 GEN
Solar/Wind Harmer
1.769
20675828AU_W4-064
Solar/Wind Harmer
0.222
20674928WA_W3-044
Solar/Wind Harmer
0.614
971519AH1-257 GEN
Solar/Wind Harmer
3.206
20675728RH_W2-091
Solar/Wind Harmer
0.764
207518AF1-320_GEN
Solar/Wind Harmer
4.635
207484AF2-139 C O1
Solar/Wind Harmer
0.639
20465127PORT CT
Adder
3.8
208909MACR G3
Adder
200.108
211065PSPA IPP
Solar/Wind Harmer
0.556
961301AF2-421 GEN
Solar/Wind Harmer
1.182
963151AG1-164 GEN
Solar/Wind Harmer
1.182
209023WIENIPP1
Adder
12.742
209025WIENIPP3
Adder
6.36
963071AG1-156 GEN
Solar/Wind Harmer
11.632
209010PEIP 1
Adder
0.752
961341AF2-425 GEN
Solar/Wind Harmer
1.119
212507AE2-042_GEN
Solar/Wind Harmer
3.264
946731AF1-337 GEN
Solar/Wind Harmer
1.079
209018SUNBIPCT
Adder
8.014
20465527S.RDG CT
Adder
2.667
209137AF2-361 C
Solar/Wind Harmer
2.349
209008PAXT IPP
Adder
1.516
941421AE2-139 GEN
Solar/Wind Harmer
2.714
20328326MANOR_T86
Adder
0.124
316415AF1-147_GEN2
Solar/Wind Helper
1.087
316447AC1-158 HLD
Solar/Wind Helper
3.79
316044AC1-158 PL1
Solar/Wind Helper
1.722
3147666LOUISA
Solar/Wind Helper
1.21
316192AB2-158 GEN
Solar/Wind Helper
2.036
316337AD2-073 GEN
Solar/Wind Helper
0.457
964211AG1-282 GEN
Solar/Wind Helper
0.402
3141726DUNNSVL
Solar/Wind Helper
1.194
316404AE1-155 C
Solar/Wind Helper
2.55
3142416OLDCHRC
Solar/Wind Helper
0.77
3142416OLDCHRC
Solar/Wind Helper
0.295
3138133OCRAN
Solar/Wind Helper
0.178
238175AF1-290_GEN
Solar/Wind Helper
0.16
3141766HARMONY
Solar/Wind Helper
0.059
315662AE1-191 GEN
Solar/Wind Helper
1.593
316280AD1-041 GEN
Solar/Wind Helper
0.996
315975AC1-164 GENB
Solar/Wind Helper
0.113
3142433PROV 92
Solar/Wind Helper
1.181
3143526WINTERP
Solar/Wind Helper
1.533
3142543TWELFTH
Solar/Wind Helper
0.028
3143226MDLTHAN
Solar/Wind Helper
0.294
316132AB2-190 GEN1
Solar/Wind Helper
1.675
315671AE2-027_GEN
Solar/Wind Helper
2.364
316369SG1_INVT
Solar/Wind Helper
1.409
3145336SMITFLD
Solar/Wind Helper
1.162
315773AC2-141 GEN
Solar/Wind Helper
6.262
316381AD1-082 GEN
Solar/Wind Helper
1.506
316375AC2-012 GEN
Solar/Wind Helper
0.763
316036AC1-147 C
Solar/Wind Helper
0.442
316072AD1-144
Solar/Wind Helper
0.331
3146456SLIGO L269
Solar/Wind Helper
0.289
319010AE1-072 C
Solar/Wind Helper
3.305
238152AF2-075_GEN
Solar/Wind Helper
0.709
3146516WINFALL
Solar/Wind Helper
0.929
3146516WINFALL
Solar/Wind Helper
0.287
315611Z1-036_GEN2
Solar/Wind Helper
1.569
3130156CHOWAN
Solar/Wind Helper
0.285
315816AE2-034 GEN
Solar/Wind Helper
1.297
3145663CRESWEL
Solar/Wind Helper
0.793
315737AD1-076 GEN
Solar/Wind Helper
2.758
316023GEN1_S
Solar/Wind Helper
1.073
3146206CASHIE
Solar/Wind Helper
0.281
3145893MURPHYS
Solar/Wind Helper
1.123
3146776BUCKING
Solar/Wind Helper
0.112
3146173TUNIS
Solar/Wind Helper
0.28
3146926FARMVIL
Solar/Wind Helper
0.168
3156021HOLLOMANSOL
Solar/Wind Helper
2.135
3145683EARLEYS
Solar/Wind Helper
0.279
315607AA1-063A GEN
Solar/Wind Helper
1.598
316087AB2-174 GEN
Solar/Wind Helper
1.955
3146263WOODLND
Solar/Wind Helper
0.279
3145963POPLR C
Solar/Wind Helper
0.278
200201DELTA2 CT2
50/50
5.62
200034PCHBTM 2
50/50
32.756
200035PCHBTM 3
50/50
32.261
200205Y1-065-CTG2
50/50
6.426
233971AC1-093 C
Solar/Wind Harmer
4.432
232899W1-062
Adder
16.714
232410W1-006 C
Solar/Wind Harmer
1.737
232918OH NUG7
Adder
15.24
232905CHERITON_25
Adder
4.262
232926CRISFLD1
Adder
3.409
231940T-011
Adder
1.295
234015AF2-250 C
Solar/Wind Harmer
0.209
232428Y3-058 C
Solar/Wind Harmer
1.447
233994AC2-023 GEN
Solar/Wind Harmer
4.66
233946AB2-136 GEN
Solar/Wind Harmer
6.914
234036AF2-325 C
Solar/Wind Harmer
1.589
233952AC2-187 GEN
Solar/Wind Harmer
1.949
233954AC2-188 GEN
Solar/Wind Harmer
1.949
234041AC1-190 GEN
Solar/Wind Harmer
15.52
232910NRG_G1
Adder
14.893
233984AB2-036 GEN
Solar/Wind Harmer
21.408
232424Y1-079 C
Solar/Wind Harmer
0.966
234014AF1-036_GEN
Solar/Wind Harmer
4.632
232436AB1-176 C
Solar/Wind Harmer
0.392
233930AB2-032 GEN
Solar/Wind Harmer
1.418
233982AB2-133 GEN
Solar/Wind Harmer
8.287
228251CARLLS#4
Adder
0.928
228201CARL#2CT
Adder
10.119
228200CARL#1CT
Adder
9.623
230433AD2-135 GEN
Solar/Wind Harmer
0.148
228351V2-046C
Solar/Wind Harmer
2.951
230511AF1-262
Solar/Wind Harmer
0.268
228754AB1-001 C
Solar/Wind Harmer
0.203
228307PCLP GT
Adder
17.631
972233AH1-701 GEN
Adder
6.088
219272CLEANLIGHT C
Solar/Wind Harmer
0.261
219287REEVESEAST C
Solar/Wind Harmer
1.918
219904AC1-010 C
Solar/Wind Harmer
0.539
213589EDDYSTN4
Adder
113.261
213587EDDYSTN3
Adder
113.248
219912AD2-042 GEN
Solar/Wind Harmer
1.13
219906AC1-017 C
Solar/Wind Harmer
0.314
219607WPEMNERT C
Solar/Wind Harmer
0.587
219304NAMERICA C
Solar/Wind Harmer
0.435
213535CROYDN11
Adder
14.326
213815MOSER1-3
Adder
4.95
213815MOSER1-3
Adder
4.95
214067T20SOLAR
Solar/Wind Harmer
0.351
20720828JCB_W4-025
Solar/Wind Harmer
0.628
20636128O CRK C2
Adder
8.921
207459AE1-142 C O1
Solar/Wind Harmer
1.453
20628028LAKEHURS
Adder
1.309
20714828MDF_W3-079
Solar/Wind Harmer
0.418
219817TRENTONSOL C
Solar/Wind Harmer
1.5
20641628MLH_W1-032
Solar/Wind Harmer
0.399
20742028HF_AC1-207
Solar/Wind Harmer
1.063
217197RE CRAN C
Solar/Wind Harmer
0.724
218438BLK ROCK C
Solar/Wind Harmer
0.184
924131AB2-057 GEN
Solar/Wind Harmer
1.381
20635028RRCT1&2
Adder
15.563
20635128RRCT3&4
Adder
15.022
20635128RRCT3&4
Adder
13.104
218418LINDEN_G5
Adder
22.854
218419LINDEN_G6
Adder
22.854
972260AH1-715 GEN1
Adder
18.301
219036LINDEN_G7
Adder
22.179
219035LINDEN_G8
Adder
21.863
972261AH1-715 GEN2
Adder
21.231
20675428EAM_W2-061
Solar/Wind Harmer
0.25
217081WEATEXAS C
Solar/Wind Harmer
0.114
217202FBANKSOLAR C
Solar/Wind Harmer
0.097
217201HACKENSOLA C
Solar/Wind Harmer
0.097
972237AH1-703 GEN
Adder
13.331
217206BARNGR HS C
Solar/Wind Harmer
0.041
217086KRNY_131
Adder
12.271
217083KRNY_132
Adder
12.167
217204WCALDSOLAR C
Solar/Wind Harmer
0.096
20674328GAR_V4-001
Solar/Wind Harmer
0.141
20674828DL_W4-046
Solar/Wind Harmer
0.825
207471AF2-354 C
Solar/Wind Harmer
0.653
20634528N27_Y2-018
Solar/Wind Harmer
0.343
20675928HOL_W4-097
Solar/Wind Harmer
0.165
20465127PORT CT
Adder
5.043
209010PEIP 1
Adder
4.136
209010PEIP 1
Adder
0.606
961541AF2-445A GEN
Solar/Wind Harmer
3.712
961431AF2-434 GEN
Solar/Wind Harmer
1.116
946751AF1-339 GEN
Solar/Wind Harmer
1.079
209130AF1-271A GEN
Solar/Wind Harmer
3.025
20465527S.RDG CT
Adder
2.58
223401AF1-299 GEN
Solar/Wind Helper
0.532
223402AF1-300 C
Solar/Wind Helper
0.532
316411AF1-147_GEN1
Solar/Wind Helper
1.087
316006AB2-029 C
Solar/Wind Helper
0.149
316045AC1-158 PL2
Solar/Wind Helper
5.511
316450AC1-158 RIC
Solar/Wind Helper
0.459
966001AG1-469 GEN
Solar/Wind Helper
0.321
966871AG1-558 GEN
Solar/Wind Helper
0.402
316487AF1-042 GEN
Solar/Wind Helper
0.301
316312AB1-027
Solar/Wind Helper
0.566
316156AD2-030 GEN
Solar/Wind Helper
0.447
315666AE1-190 GEN
Solar/Wind Helper
0.398
315976AC1-164 GENA
Solar/Wind Helper
3.81
316169AC1-164_GENC
Solar/Wind Helper
3.291
3143526WINTERP
Solar/Wind Helper
1.533
3142946ENON
Solar/Wind Helper
0.03
316240AF1-291 C
Solar/Wind Helper
0.394
316033AB2-134 GEN
Solar/Wind Helper
1.012
316294AC1-161 GEN
Solar/Wind Helper
5.321
316185AD1-033 GEN
Solar/Wind Helper
1.365
316313AB2-026
Solar/Wind Helper
0.442
3145506HICKORY
Solar/Wind Helper
1.157
3145506HICKORY
Solar/Wind Helper
0.694
3145506HICKORY
Solar/Wind Helper
0.173
316349AD2-085 GEN
Solar/Wind Helper
1.324
316339AD2-160 GEN
Solar/Wind Helper
1.103
316388AE2-253 GEN
Solar/Wind Helper
1.103
3137176SLIGO L2192
Solar/Wind Helper
1.149
3130086AYDLETT
Solar/Wind Helper
1.154
3146386ELIZ CT
Solar/Wind Helper
0.288
316431W1029_GEN1
Solar/Wind Helper
1.161
316433W1029_GEN2
Solar/Wind Helper
1.161
316435W1029_GEN3
Solar/Wind Helper
1.161
238147AE2-230_GEN1
Solar/Wind Helper
0.497
238148AE2-230_GEN2
Solar/Wind Helper
0.497
238149AF1-291A_GEN
Solar/Wind Helper
0.142
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.287
3146626S HERTFORD
Solar/Wind Helper
0.286
3146626S HERTFORD
Solar/Wind Helper
0.286
3144356SAPONY
Solar/Wind Helper
0.513
316315AB2-025 C
Solar/Wind Helper
0.437
237061AD1-155 GEN
Solar/Wind Helper
1.79
315614AA2-178 GEN
Solar/Wind Helper
1.73
316365GEN2_N
Solar/Wind Helper
1.073
3145893MURPHYS
Solar/Wind Helper
0.403
3145893MURPHYS
Solar/Wind Helper
0.506
3146776BUCKING
Solar/Wind Helper
1.123
3146776BUCKING
Solar/Wind Helper
0.091
3146173TUNIS
Solar/Wind Helper
0.28
3146173TUNIS
Solar/Wind Helper
0.28
316140AB2-099
Solar/Wind Helper
0.107
313506AB2-031 GEN
Solar/Wind Helper
1.269
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.167
3145593CAROLNA
Solar/Wind Helper
0.278
3145593CAROLNA
Solar/Wind Helper
0.278
3147133PAMPLIN
Solar/Wind Helper
0.278
200200DELTA2 CT1
50/50
5.62
200193DELTA CT2
50/50
3.14
200203Y1-065-STG
50/50
11.128
200055ROCKSP 4
50/50
4.019
233973AC2-185 C
Solar/Wind Harmer
9.43
970695AG2-447 GEN
Solar/Wind Harmer
6.238
233939AC1-091 C
Solar/Wind Harmer
4.668
233972AC1-094 C
Solar/Wind Harmer
3.748
233987AB2-037 GEN
Solar/Wind Harmer
19.759
232434Z2-077 GEN
Solar/Wind Harmer
0.434
232406W1-004 FULL
Solar/Wind Harmer
1.737
232914OH NUG3
Adder
15.343
232916OH NUG5
Adder
15.343
232921TASLEY2G
Adder
8.967
233923SMA
Solar/Wind Harmer
6.347
233997TMININ_4.2
Solar/Wind Harmer
1.731
232907VN8
Adder
52.14
233964AF2-378 GEN
Solar/Wind Harmer
0.221
233950AC2-186 GEN
Solar/Wind Harmer
0.975
232417X3-008 C
Solar/Wind Harmer
1.949
232422X3-066 FULL
Solar/Wind Harmer
0.427
233933AB2-153 GEN
Solar/Wind Harmer
1.915
233935AB2-179 C
Solar/Wind Harmer
4.154
228711V2-041C
Solar/Wind Harmer
0.888
230415AB2-049 C
Solar/Wind Harmer
0.277
219623KINSLEYBEA C
Solar/Wind Harmer
0.612
219291REEVESSOUT C
Solar/Wind Harmer
0.086
219921AF1-264
Solar/Wind Harmer
0.206
218660EHAMPSOLAR C
Solar/Wind Harmer
0.249
213497CHSTR7-9
Adder
3.882
219688LUMSOLAR_S C
Solar/Wind Harmer
0.288
219914AD2-027 C
Solar/Wind Harmer
0.852
219236SOUTHERNHQ C
Solar/Wind Harmer
0.096
213958STHWK5-6
Adder
3.834
213560DLW11-12
Adder
3.816
219221BRL12CT1
Adder
12.513
219223BRL12CT3
Adder
12.513
213815MOSER1-3
Adder
4.95
20716428NHV_W2-082
Solar/Wind Harmer
2.464
959561AF2-247 GEN
Solar/Wind Harmer
0.673
20715728PEM_W1-119
Solar/Wind Harmer
0.74
20636028O CRK C1
Adder
9.784
963391AG1-188 GEN
Solar/Wind Harmer
5.177
20714928UPF_X1-085
Solar/Wind Harmer
0.561
971667AH1-334 GEN
Solar/Wind Harmer
3.784
219114HARTZY_C
Solar/Wind Harmer
1.146
219727YARDVSOLFA C
Solar/Wind Harmer
1.248
207454AA2-184 E
Solar/Wind Harmer
1.357
219918AC2-009 C
Solar/Wind Harmer
0.035
219612MATRIX C
Solar/Wind Harmer
0.248
20716928W4-060COL
Solar/Wind Harmer
0.959
20635828PARLN1&2
Adder
4.505
20635928PARLN3&4
Adder
4.505
217213AMBOY SO C
Solar/Wind Harmer
0.169
219249CENTRALDIV C
Solar/Wind Harmer
0.053
207442AE1-156 GEN
Solar/Wind Harmer
0.984
20673728F2S_V4-070
Solar/Wind Harmer
0.238
217211CAMDEN ST C
Solar/Wind Harmer
0.032
217169METRODIV C
Solar/Wind Harmer
0.052
217194REDH C
Solar/Wind Harmer
0.648
20674528F3S_W2-016
Solar/Wind Harmer
1.838
207510AF2-138 C
Solar/Wind Harmer
2.292
207511W3-106 GEN
Solar/Wind Harmer
0.425
971007AG2-625 GEN
Solar/Wind Harmer
3.271
207437AD2-070 GEN
Solar/Wind Harmer
0.381
20466127PORT 5CT
Adder
33.565
20671928W4-073
Solar/Wind Harmer
0.546
20674128FR_U2-059
Solar/Wind Harmer
0.232
20633028GILCT9
Adder
35.572
20465427SHAW CT
Adder
4.868
209116AE2-175 GEN
Solar/Wind Harmer
5.114
211065PSPA IPP
Solar/Wind Harmer
0.556
963161AG1-165 GEN
Solar/Wind Harmer
1.182
209025WIENIPP3
Adder
6.232
970095AG2-074 GEN
Solar/Wind Harmer
7.367
208972BECR K09
Solar/Wind Harmer
1.232
961331AF2-424 GEN
Solar/Wind Harmer
1.119
961421AF2-433 GEN
Solar/Wind Harmer
1.116
957921AF2-086 GEN
Solar/Wind Harmer
1.085
209142AF1-226 GEN
Solar/Wind Harmer
6.458
209093AE2-110 GEN
Solar/Wind Harmer
2.789
209120AE2-241 GEN
Solar/Wind Harmer
3.69
946691AF1-333 GEN
Solar/Wind Harmer
1.079
946741AF1-338 GEN
Solar/Wind Harmer
1.079
209071AE2-133 GEN
Solar/Wind Harmer
1.821
205941AD2-115 GEN
Solar/Wind Harmer
0.964
972221AH1-695 GEN
Adder
101.532
226910AB2-157 C
Solar/Wind Helper
0.021
227287AC2-120 GEN
Solar/Wind Helper
0.513
3141196NOKESVL
Solar/Wind Helper
1.272
966881AG1-559 GEN
Solar/Wind Helper
0.411
3132273ORANGE
Solar/Wind Helper
0.061
3147666LOUISA
Solar/Wind Helper
0.695
316223AC1-118
Solar/Wind Helper
0.461
3141906WESTMOR
Solar/Wind Helper
0.121
316077AC2-138 C
Solar/Wind Helper
0.282
316473AC1-191 GEN
Solar/Wind Helper
1.82
316484AD2-074 GEN
Solar/Wind Helper
0.575
316075AC2-137 C
Solar/Wind Helper
0.451
3142946ENON
Solar/Wind Helper
0.098
316458AB2-190 GEN2
Solar/Wind Helper
1.675
3145336SMITFLD
Solar/Wind Helper
0.116
3144536CHRHLND
Solar/Wind Helper
0.044
3144873MCLAUGH
Solar/Wind Helper
0.007
3142956BIRDNECK
Solar/Wind Helper
0.195
316017AA1-139 ULT1
Solar/Wind Helper
1.323
3146456SLIGO L269
Solar/Wind Helper
0.289
316305AF2-043 C
Solar/Wind Helper
0.389
316246AF1-032 C
Solar/Wind Helper
0.331
316320Y1-086
Solar/Wind Helper
0.129
316321Z2-027
Solar/Wind Helper
0.439
23546401DTGZ2-030
Solar/Wind Helper
0.09
3146516WINFALL
Solar/Wind Helper
0.287
3146626S HERTFORD
Solar/Wind Helper
0.286
3145273HOLLAND
Solar/Wind Helper
0.215
3146376EDENTON
Solar/Wind Helper
0.285
315735AD1-075 GEN1
Solar/Wind Helper
1.613
3146206CASHIE
Solar/Wind Helper
0.281
3145893MURPHYS
Solar/Wind Helper
0.101
3145893MURPHYS
Solar/Wind Helper
0.281
3146776BUCKING
Solar/Wind Helper
0.101
3146173TUNIS
Solar/Wind Helper
0.28
3146926FARMVIL
Solar/Wind Helper
0.168
966621AG1-532 GEN
Solar/Wind Helper
0.254
3146263WOODLND
Solar/Wind Helper
0.279
316181AB2-040 GEN
Solar/Wind Helper
2.004
942461AE2-259 GEN
Solar/Wind Helper
1.878
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3145963POPLR C
Solar/Wind Helper
0.278
316190AA2-174 GEN
Solar/Wind Helper
0.019
3147043LAWRENC
Solar/Wind Helper
0.167
316011AB1-132 GEN
Solar/Wind Helper
2.999
316317KELFORD C
Solar/Wind Helper
0.25
3145823KELFORD
Solar/Wind Helper
0.278
3147133PAMPLIN
Solar/Wind Helper
0.872
315821AE2-092 GEN
Solar/Wind Helper
2.579
316478AD1-087 GEN
Solar/Wind Helper
1.359
3145796HORNRTN
Solar/Wind Helper
1.108
3145796HORNRTN
Solar/Wind Helper
0.277
316212AC1-099_GEN
Solar/Wind Helper
1.238
3145933PARMELE
Solar/Wind Helper
0.275
316499AE2-029_GEN
Solar/Wind Helper
0.923
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3148013FISHERV
Solar/Wind Helper
0.274
316420AA1-050 GEN
Solar/Wind Helper
1.566
3146233WITAKRS
Solar/Wind Helper
0.293
3146233WITAKRS
Solar/Wind Helper
0.185
3146073TAR RVR
Solar/Wind Helper
0.272
3146083TARBORO
Solar/Wind Helper
0.272
3138543CONSLDL
Solar/Wind Helper
0.179
270494AE1-108_GEN
Solar/Wind Helper
3.639
3145543BTLEBRO
Solar/Wind Helper
0.271
3145543BTLEBRO
Solar/Wind Helper
0.271
316095T157 G97
Solar/Wind Helper
1.231
316003AC1-222 GEN
Solar/Wind Helper
1.16
23583801GRNGAP
Solar/Wind Helper
4.532
316222AC1-221 GEN
Solar/Wind Helper
1.502
316283AC2-100 C
Solar/Wind Helper
1.399
316123AC1-075 GEN
Solar/Wind Helper
1.588
238109AE1-109 GEN2
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.235
3147312GRETNA
Solar/Wind Helper
0.05
23777801MSM_W1-116
Solar/Wind Helper
0.106
237038AE2-054 C
Solar/Wind Helper
0.243
270173AC1-122 GEN
Solar/Wind Helper
1.674
235067AD1-061 GEN
Solar/Wind Helper
0.395
943811AF1-049 GEN
Solar/Wind Helper
1.492
237085AD2-009_GEN
Solar/Wind Helper
1.436
237002AB1-128_GEN
Solar/Wind Helper
0.388
270336AE1-100 GEN
Solar/Wind Helper
1.039
238120AE2-309 GEN
Solar/Wind Helper
0.408
238126S14_GEN_1
Solar/Wind Helper
0.637
238185AF2-356 C
Solar/Wind Helper
1.927
3130156CHOWAN
Solar/Wind Helper
0.285
3130156CHOWAN
Solar/Wind Helper
0.285
3130546PLYMOUTH
Solar/Wind Helper
0.282
315732AD1-074 GEN1
Solar/Wind Helper
3.225
315733AD1-074 GEN2
Solar/Wind Helper
3.225
3146206CASHIE
Solar/Wind Helper
0.281
3145893MURPHYS
Solar/Wind Helper
0.758
3145893MURPHYS
Solar/Wind Helper
0.281
316322AB2-045
Solar/Wind Helper
0.314
316463AE2-346 GEN
Solar/Wind Helper
0.256
3145513AHOSKIE
Solar/Wind Helper
0.125
961941AG1-037 GEN
Solar/Wind Helper
0.094
3145513AHOSKIE
Solar/Wind Helper
0.28
3138266HYDRAULIC
Solar/Wind Helper
0.013
3138266HYDRAULIC
Solar/Wind Helper
0.008
946281AF1-292 GEN
Solar/Wind Helper
0.281
3146043SEABORD
Solar/Wind Helper
0.28
3145683EARLEYS
Solar/Wind Helper
0.559
3145683EARLEYS
Solar/Wind Helper
0.279
3145683EARLEYS
Solar/Wind Helper
0.279
3137643SOCKMAN
Solar/Wind Helper
1.112
316426AA2-053 GEN
Solar/Wind Helper
1.591
316174AB2-169 GEN
Solar/Wind Helper
0.711
316486AD2-202 GEN
Solar/Wind Helper
0.398
3145796HORNRTN
Solar/Wind Helper
0.886
3145796HORNRTN
Solar/Wind Helper
0.111
3146033SCOT NK
Solar/Wind Helper
1.107
3144303KENBRDG
Solar/Wind Helper
0.221
316210AC1-098 GEN
Solar/Wind Helper
2.228
316274AC1-208 GEN
Solar/Wind Helper
1.681
316238AB2-078_GEN
Solar/Wind Helper
0.37
316239AB2-077_GEN
Solar/Wind Helper
0.37
3145746EVERETS
Solar/Wind Helper
1.09
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3148133STUARTS
Solar/Wind Helper
0.164
3148013FISHERV
Solar/Wind Helper
0.157
316327AA2-057 GEN
Solar/Wind Helper
1.562
3145573BETHELC
Solar/Wind Helper
0.272
3145573BETHELC
Solar/Wind Helper
0.272
3147173SINAI
Solar/Wind Helper
0.268
3147243WELCO
Solar/Wind Helper
0.168
315616AA1-038_C
Solar/Wind Helper
1.207
3148463FAIRFLD
Solar/Wind Helper
0.266
270455AD2-022 GEN
Solar/Wind Helper
1.49
270457AD2-023 GEN
Solar/Wind Helper
0.982
23779801AA1-109
Solar/Wind Helper
0.183
270197AD1-017 GEN1
Solar/Wind Helper
1.336
23750701CROSSCHOOL
Solar/Wind Helper
1.107
237030AB1-096 C
Solar/Wind Helper
0.058
237025AB1-124 C
Solar/Wind Helper
0.143
238118U2-030_1
Solar/Wind Helper
0.261
3145823KELFORD
Solar/Wind Helper
0.278
3145783HORNRTN
Solar/Wind Helper
0.277
3145796HORNRTN
Solar/Wind Helper
0.914
3145796HORNRTN
Solar/Wind Helper
0.277
316034AC1-036 C
Solar/Wind Helper
0.29
315785AD2-033 C
Solar/Wind Helper
3.223
316129AC1-054 GEN
Solar/Wind Helper
1.367
23777901MDS_W4-102
Solar/Wind Helper
0.173
316131AB2-060 GEN
Solar/Wind Helper
1.68
3147983MERCK5
Solar/Wind Helper
0.11
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
316494AC1-189 GEN
Solar/Wind Helper
1.667
3146233WITAKRS
Solar/Wind Helper
1.082
961671AG1-007 GEN
Solar/Wind Helper
0.195
3146083TARBORO
Solar/Wind Helper
0.272
3145543BTLEBRO
Solar/Wind Helper
0.271
3145543BTLEBRO
Solar/Wind Helper
0.217
316359AB2-059 GEN
Solar/Wind Helper
2.068
238108AE1-109 GEN1
Solar/Wind Helper
0.095
238110AE1-109 GEN3
Solar/Wind Helper
0.095
3147123OTTER R
Solar/Wind Helper
0.15
270016AE1-250 BESS
Solar/Wind Helper
0.924
3147312GRETNA
Solar/Wind Helper
0.199
3146802CHATHAM
Solar/Wind Helper
0.187
270018AE2-047 C O1
Solar/Wind Helper
0.867
964991AG1-363 GEN
Solar/Wind Helper
3.563
237001AB1-127_GEN
Solar/Wind Helper
0.385
235063AE1-101 C2
Solar/Wind Helper
1.421
958121AF2-106 GEN
Solar/Wind Helper
1.718
238127S14_GEN_2
Solar/Wind Helper
0.637
3147133PAMPLIN
Solar/Wind Helper
0.222
3145796HORNRTN
Solar/Wind Helper
0.831
3132123MT JACKSON
Solar/Wind Helper
0.866
3145933PARMELE
Solar/Wind Helper
0.55
3145933PARMELE
Solar/Wind Helper
0.275
316237AB2-079_GEN
Solar/Wind Helper
0.37
235020AA1-095 C
Solar/Wind Helper
0.051
316005AA1-067
Solar/Wind Helper
0.314
315687AD1-152 GEN
Solar/Wind Helper
1.474
3146843MT LREL
Solar/Wind Helper
0.271
3146843MT LREL
Solar/Wind Helper
0.271
316049AB1-081 GEN
Solar/Wind Helper
1.654
316118AC1-105 GEN
Solar/Wind Helper
1.051
316248AF1-058 C
Solar/Wind Helper
0.362
316097T157 G90
Solar/Wind Helper
1.231
238221AF1-254 C O1
Solar/Wind Helper
0.258
237080AD1-060 GEN
Solar/Wind Helper
0.312
270013AE1-250 PV
Solar/Wind Helper
0.924
235062AE1-101 C1
Solar/Wind Helper
1.421
270214AC2-123 GEN
Solar/Wind Helper
0.81
237006AB1-125 GEN
Solar/Wind Helper
0.107
235531U2-073 GEN
Solar/Wind Helper
2.561
235054AD2-180 GEN
Solar/Wind Helper
1.52
238117U2-030
Solar/Wind Helper
0.261
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.524
VTFLTFEXP_VFT->PJM
CMTX
178.849
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.231
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.833
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
24.665
BlueGrassPJM->LTFIMP_BlueG
CLTF
16.299
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
68.737
CBM NorthLTFEXP_CBM-N->PJM
CBM
95.237
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.49 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:5266.8
MW Contribution:
5.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200200DELTA2 CT1
50/50
5.349
200193DELTA CT2
50/50
2.989
200203Y1-065-STG
50/50
10.579
200055ROCKSP 4
50/50
3.821
233973AC2-185 C
Solar/Wind Harmer
8.9
970695AG2-447 GEN
Solar/Wind Harmer
5.888
233939AC1-091 C
Solar/Wind Harmer
4.406
233972AC1-094 C
Solar/Wind Harmer
3.538
232434Z2-077 GEN
Solar/Wind Harmer
0.41
233987AB2-037 GEN
Solar/Wind Harmer
18.643
232406W1-004 FULL
Solar/Wind Harmer
1.639
232914OH NUG3
Adder
14.478
232916OH NUG5
Adder
14.478
232921TASLEY2G
Adder
8.461
233923SMA
Solar/Wind Harmer
5.989
233997TMININ_4.2
Solar/Wind Harmer
1.633
232907VN8
Adder
49.197
233964AF2-378 GEN
Solar/Wind Harmer
0.209
233950AC2-186 GEN
Solar/Wind Harmer
0.92
200202DELTA2 ST
50/50
9.059
200195DELTA ST
50/50
4.618
200052ROCKSP 1
50/50
3.843
200053ROCKSP 2
50/50
3.768
232904IR4
Adder
132.596
232920IR10
Adder
5.182
232432Z2-076 GEN
Solar/Wind Harmer
0.216
233901CHERRYDALE C
Solar/Wind Harmer
1.843
232912OH NUG1
Adder
14.478
232913OH NUG2
Adder
14.285
233940AF2-379 C
Solar/Wind Harmer
0.305
971195AH1-057 GEN
Solar/Wind Harmer
1.597
233955AB2-172 GEN
Solar/Wind Harmer
8.171
232813VAUGHN
Adder
0.96
231906DC3 NUG
Adder
22.579
231902DC CT7
Adder
18.051
231907DC10
Adder
5.637
233968AD2-076_GEN
Solar/Wind Harmer
10.698
970597AG2-380 GEN
Solar/Wind Harmer
6.718
233915AB1-141 GEN
Solar/Wind Harmer
1.588
231919CHRIST1
Adder
6.863
231920CHRIST2
Adder
6.711
970453AG2-297 GEN
Solar/Wind Harmer
3.848
230422AE1-104_GEN1
Solar/Wind Harmer
46.549
230425AE1-104_GEN2
Solar/Wind Harmer
46.549
972141AH1-641 GEN
Solar/Wind Harmer
3.971
230430AE1-229_GEN
Solar/Wind Harmer
39.5
964001AG1-254 GEN
Solar/Wind Harmer
10.045
228728W1-130C
Solar/Wind Harmer
0.913
227927V4-067C
Solar/Wind Harmer
0.272
230407AD2-065 C
Solar/Wind Harmer
0.18
230434AG1-499 GEN
Solar/Wind Harmer
0.794
219137THOSOLAR C
Solar/Wind Harmer
1.632
200192DELTA CT1
50/50
2.989
200194DELTA CT3
50/50
2.989
200204Y1-065-CTG1
50/50
6.109
200054ROCKSP 3
50/50
3.888
232901NORTHST
Adder
13.679
233970AC1-092 C
Solar/Wind Harmer
4.406
234033AF1-007_GEN
Solar/Wind Harmer
60.997
232900DEMECSMY
Adder
15.13
972177AH1-672 GEN
Solar/Wind Harmer
22.025
232404W1-003 C
Solar/Wind Harmer
1.639
232408W1-005 C
Solar/Wind Harmer
1.639
232917OH NUG6
Adder
14.413
232915OH NUG4
Adder
14.381
233996TM1833_GEN
Solar/Wind Harmer
1.633
233998TM1NIN_3.36
Solar/Wind Harmer
1.633
232919VN10
Adder
4.595
232426Y1-080 FULL
Solar/Wind Harmer
0.313
232902EASTMUNI
Adder
21.221
234012AE2-112_GEN
Solar/Wind Harmer
3.712
972251AH1-710 GEN
Adder
72.075
233944AB2-135 GEN
Solar/Wind Harmer
8.417
233918AB1-142 GEN
Solar/Wind Harmer
1.588
231918WEST 1
Adder
5.218
231917EM10
Adder
3.635
228206SHRMN CT
Adder
23.049
228732V1-021 C
Adder
0.263
228260V4-054C
Solar/Wind Harmer
1.421
970997AG2-616 GEN
Solar/Wind Harmer
13.238
228729W2-030 C
Solar/Wind Harmer
0.793
228400MICK 1CT
Adder
16.092
219686LUMSOLAR_N C
Solar/Wind Harmer
0.271
219766PARADISE C
Solar/Wind Harmer
0.421
213497CHSTR7-9
Adder
3.642
213497CHSTR7-9
Adder
3.642
219907AC1-030 C
Solar/Wind Harmer
0.184
213958STHWK5-6
Adder
3.596
213560DLW11-12
Adder
3.58
219348LDSOLAR C
Solar/Wind Harmer
0.787
219222BRL12CT2
Adder
11.748
20716028EGP_W2-019
Solar/Wind Harmer
0.604
213611FALLS1-3
Adder
4.604
207522AF2-254 C
Solar/Wind Harmer
1.867
20717128DIX_Z2-102
Solar/Wind Harmer
1.717
20715828PEM_W1-120
Solar/Wind Harmer
0.694
214194N WALES4
Adder
1.103
963711AG1-223 GEN
Solar/Wind Harmer
1.9
20714528FRN_Y2-051
Solar/Wind Harmer
0.379
219276PARKLANDSO C
Solar/Wind Harmer
0.59
20715228NPK_W1-113
Solar/Wind Harmer
0.547
20720528MAN_W1-024
Solar/Wind Harmer
0.323
219680HOPEWELLV C1
Solar/Wind Harmer
0.097
20720428HOL_W1-112
Solar/Wind Harmer
0.439
20635828PARLN1&2
Adder
9.318
20635028RRCT1&2
Adder
14.806
218524CNTRALGAS1 C
Solar/Wind Harmer
0.462
218440SUMMTASSOC C
Solar/Wind Harmer
0.16
218428ETC SOLAR C
Solar/Wind Harmer
0.045
219908AB1-139 C
Solar/Wind Harmer
0.475
219919AE1-041 FULL
Solar/Wind Harmer
0.05
972275AH1-722 GEN
Adder
39.333
20673628F1S_V4-069
Solar/Wind Harmer
0.222
207528AF2-192 GEN
Solar/Wind Harmer
1.574
217209CENTRL HS C
Solar/Wind Harmer
0.055
217186ESSEX_G9
Adder
4.865
217121ECCF
Adder
0.535
217083KRNY_132
Adder
11.455
217208PARK ELE C
Solar/Wind Harmer
0.031
20671828STAW2-080
Solar/Wind Harmer
0.129
20676728BRNX1-095
Solar/Wind Harmer
0.215
966261AG1-495 GEN
Solar/Wind Harmer
4.238
207439AE1-081 C O1
Solar/Wind Harmer
0.072
20676328BVR_Y1-020
Solar/Wind Harmer
0.398
20674628WNG_W3-110
Solar/Wind Harmer
0.485
219258KINSLEYDEP C
Solar/Wind Harmer
0.435
213942SCHUYLKILL
Adder
4.704
213942SCHUYLKILL
Adder
3.597
213957STHWK3-4
Adder
3.596
213957STHWK3-4
Adder
3.596
219615MILLCREEK C
Solar/Wind Harmer
0.315
213561DLWR9-10
Adder
4.682
213561DLWR9-10
Adder
3.58
219610FLORENCE C
Solar/Wind Harmer
1.822
219224BRL12CT4
Adder
11.748
20720728JCB_W1-129
Solar/Wind Harmer
0.388
20715028HAN_X4-015
Solar/Wind Harmer
0.388
213611FALLS1-3
Adder
4.604
213611FALLS1-3
Adder
4.604
207487AE2-000G4
Solar/Wind Harmer
40.932
207497AE2-000G2
Solar/Wind Harmer
40.932
207500AE2-000G1
Solar/Wind Harmer
40.932
207507AE2-000G3
Solar/Wind Harmer
40.932
963401AG1-189 GEN
Solar/Wind Harmer
2.95
970025AG2-016 GEN
Solar/Wind Harmer
3.673
971189AH1-054 GEN
Solar/Wind Harmer
1.528
207445AB1-138_GEN
Solar/Wind Harmer
0.748
219620RIDERU C
Solar/Wind Harmer
0.071
20714428HOW_X1-037
Solar/Wind Harmer
1.576
20720628TIN_W1-124
Solar/Wind Harmer
1.268
20716228APLW2-078
Solar/Wind Harmer
1.125
971521AH1-258 GEN
Solar/Wind Harmer
3.437
20635928PARLN3&4
Adder
9.318
218526CNTRALGAS2 C
Solar/Wind Harmer
0.464
20675528CPH_W2-050
Solar/Wind Harmer
0.715
20673828FLE_V3-070
Solar/Wind Harmer
0.579
218449LINSOLAR C
Solar/Wind Harmer
1.248
20676128MHD_W3-029
Solar/Wind Harmer
0.591
20676428JCR_X2-075
Solar/Wind Harmer
0.423
217167KRNY_14
Adder
11.455
217086KRNY_131
Adder
11.358
217147KRNY_1212
Adder
10.896
217147KRNY_1212
Adder
10.701
217146KRNY_1234
Adder
10.677
217146KRNY_1234
Adder
10.604
964851AG1-348 GEN
Solar/Wind Harmer
1.623
971009AG2-626 GEN
Solar/Wind Harmer
1.946
207408W3-077 C
Solar/Wind Harmer
0.599
20462827N BANGR8
Adder
0.843
20675128HRM_W1-127
Solar/Wind Harmer
0.2
961261AF2-417 GEN
Solar/Wind Harmer
1.117
209026WIENIPP4
Adder
5.855
20676228FRD_X1-012
Solar/Wind Harmer
0.711
207530AG1-191 GEN
Solar/Wind Harmer
1.651
20675828AU_W4-064
Solar/Wind Harmer
0.208
20674928WA_W3-044
Solar/Wind Harmer
0.573
971519AH1-257 GEN
Solar/Wind Harmer
2.99
20675728RH_W2-091
Solar/Wind Harmer
0.713
207518AF1-320_GEN
Solar/Wind Harmer
4.321
20465127PORT CT
Adder
3.543
207484AF2-139 C O1
Solar/Wind Harmer
0.596
208909MACR G3
Adder
186.471
211065PSPA IPP
Solar/Wind Harmer
0.518
961301AF2-421 GEN
Solar/Wind Harmer
1.099
963151AG1-164 GEN
Solar/Wind Harmer
1.099
209023WIENIPP1
Adder
11.85
209025WIENIPP3
Adder
5.915
963071AG1-156 GEN
Solar/Wind Harmer
10.821
209010PEIP 1
Adder
0.7
961341AF2-425 GEN
Solar/Wind Harmer
1.038
212507AE2-042_GEN
Solar/Wind Harmer
3.028
946731AF1-337 GEN
Solar/Wind Harmer
1
209018SUNBIPCT
Adder
7.431
20465527S.RDG CT
Adder
2.415
209137AF2-361 C
Solar/Wind Harmer
2.125
209008PAXT IPP
Adder
1.337
316415AF1-147_GEN2
Solar/Wind Helper
0.979
316447AC1-158 HLD
Solar/Wind Helper
3.477
316044AC1-158 PL1
Solar/Wind Helper
1.58
316337AD2-073 GEN
Solar/Wind Helper
0.423
3147666LOUISA
Solar/Wind Helper
1.111
316192AB2-158 GEN
Solar/Wind Helper
1.869
200201DELTA2 CT2
50/50
5.349
200034PCHBTM 2
50/50
31.177
200035PCHBTM 3
50/50
30.692
200205Y1-065-CTG2
50/50
6.109
233971AC1-093 C
Solar/Wind Harmer
4.183
232899W1-062
Adder
15.774
232410W1-006 C
Solar/Wind Harmer
1.639
232918OH NUG7
Adder
14.381
232905CHERITON_25
Adder
4.022
232926CRISFLD1
Adder
3.217
231940T-011
Adder
1.222
234015AF2-250 C
Solar/Wind Harmer
0.197
232428Y3-058 C
Solar/Wind Harmer
1.365
233994AC2-023 GEN
Solar/Wind Harmer
4.397
233946AB2-136 GEN
Solar/Wind Harmer
6.523
234036AF2-325 C
Solar/Wind Harmer
1.499
233952AC2-187 GEN
Solar/Wind Harmer
1.839
233954AC2-188 GEN
Solar/Wind Harmer
1.839
234041AC1-190 GEN
Solar/Wind Harmer
14.642
232910NRG_G1
Adder
14.048
233984AB2-036 GEN
Solar/Wind Harmer
20.187
232424Y1-079 C
Solar/Wind Harmer
0.911
234014AF1-036_GEN
Solar/Wind Harmer
4.367
232436AB1-176 C
Solar/Wind Harmer
0.369
233930AB2-032 GEN
Solar/Wind Harmer
1.337
233982AB2-133 GEN
Solar/Wind Harmer
7.809
228251CARLLS#4
Adder
0.873
228201CARL#2CT
Adder
9.519
228200CARL#1CT
Adder
9.054
230433AD2-135 GEN
Solar/Wind Harmer
0.139
228351V2-046C
Solar/Wind Harmer
2.776
230511AF1-262
Solar/Wind Harmer
0.252
228754AB1-001 C
Solar/Wind Harmer
0.191
228307PCLP GT
Adder
16.578
972233AH1-701 GEN
Adder
5.723
219272CLEANLIGHT C
Solar/Wind Harmer
0.245
219287REEVESEAST C
Solar/Wind Harmer
1.802
219904AC1-010 C
Solar/Wind Harmer
0.506
213589EDDYSTN4
Adder
106.245
213587EDDYSTN3
Adder
106.232
219912AD2-042 GEN
Solar/Wind Harmer
1.062
219906AC1-017 C
Solar/Wind Harmer
0.294
219607WPEMNERT C
Solar/Wind Harmer
0.551
219304NAMERICA C
Solar/Wind Harmer
0.408
213535CROYDN11
Adder
13.448
213815MOSER1-3
Adder
4.644
213815MOSER1-3
Adder
4.644
20720828JCB_W4-025
Solar/Wind Harmer
0.589
214067T20SOLAR
Solar/Wind Harmer
0.329
20636128O CRK C2
Adder
8.374
207459AE1-142 C O1
Solar/Wind Harmer
1.363
20628028LAKEHURS
Adder
1.228
20714828MDF_W3-079
Solar/Wind Harmer
0.393
219817TRENTONSOL C
Solar/Wind Harmer
1.407
20641628MLH_W1-032
Solar/Wind Harmer
0.374
20742028HF_AC1-207
Solar/Wind Harmer
0.997
217197RE CRAN C
Solar/Wind Harmer
0.679
218438BLK ROCK C
Solar/Wind Harmer
0.172
924131AB2-057 GEN
Solar/Wind Harmer
1.293
20635028RRCT1&2
Adder
14.578
20635128RRCT3&4
Adder
14.072
20635128RRCT3&4
Adder
12.275
218418LINDEN_G5
Adder
21.396
218419LINDEN_G6
Adder
21.396
972260AH1-715 GEN1
Adder
17.133
219036LINDEN_G7
Adder
20.759
219035LINDEN_G8
Adder
20.463
972261AH1-715 GEN2
Adder
19.871
20675428EAM_W2-061
Solar/Wind Harmer
0.234
217081WEATEXAS C
Solar/Wind Harmer
0.106
217202FBANKSOLAR C
Solar/Wind Harmer
0.091
217201HACKENSOLA C
Solar/Wind Harmer
0.09
972237AH1-703 GEN
Adder
12.471
217206BARNGR HS C
Solar/Wind Harmer
0.038
217086KRNY_131
Adder
11.48
217083KRNY_132
Adder
11.382
217204WCALDSOLAR C
Solar/Wind Harmer
0.09
20674328GAR_V4-001
Solar/Wind Harmer
0.132
20674828DL_W4-046
Solar/Wind Harmer
0.769
207471AF2-354 C
Solar/Wind Harmer
0.609
20634528N27_Y2-018
Solar/Wind Harmer
0.319
20675928HOL_W4-097
Solar/Wind Harmer
0.154
20465127PORT CT
Adder
4.701
209010PEIP 1
Adder
3.849
209010PEIP 1
Adder
0.564
961541AF2-445A GEN
Solar/Wind Harmer
3.447
961431AF2-434 GEN
Solar/Wind Harmer
1.036
946751AF1-339 GEN
Solar/Wind Harmer
1
209130AF1-271A GEN
Solar/Wind Harmer
2.805
20465527S.RDG CT
Adder
2.337
223401AF1-299 GEN
Solar/Wind Helper
0.612
223402AF1-300 C
Solar/Wind Helper
0.612
316411AF1-147_GEN1
Solar/Wind Helper
0.979
316006AB2-029 C
Solar/Wind Helper
0.136
316045AC1-158 PL2
Solar/Wind Helper
5.056
316450AC1-158 RIC
Solar/Wind Helper
0.421
966871AG1-558 GEN
Solar/Wind Helper
0.371
316487AF1-042 GEN
Solar/Wind Helper
0.278
966001AG1-469 GEN
Solar/Wind Helper
0.294
316312AB1-027
Solar/Wind Helper
0.523
316156AD2-030 GEN
Solar/Wind Helper
0.413
315666AE1-190 GEN
Solar/Wind Helper
0.368
315976AC1-164 GENA
Solar/Wind Helper
3.518
316169AC1-164_GENC
Solar/Wind Helper
3.039
3142946ENON
Solar/Wind Helper
0.027
3143526WINTERP
Solar/Wind Helper
1.413
316240AF1-291 C
Solar/Wind Helper
0.364
316033AB2-134 GEN
Solar/Wind Helper
0.933
316294AC1-161 GEN
Solar/Wind Helper
4.906
316185AD1-033 GEN
Solar/Wind Helper
1.258
232417X3-008 C
Solar/Wind Harmer
1.839
232422X3-066 FULL
Solar/Wind Harmer
0.403
233933AB2-153 GEN
Solar/Wind Harmer
1.805
233935AB2-179 C
Solar/Wind Harmer
3.909
228711V2-041C
Solar/Wind Harmer
0.835
230415AB2-049 C
Solar/Wind Harmer
0.261
219623KINSLEYBEA C
Solar/Wind Harmer
0.575
219291REEVESSOUT C
Solar/Wind Harmer
0.081
219921AF1-264
Solar/Wind Harmer
0.194
218660EHAMPSOLAR C
Solar/Wind Harmer
0.234
219688LUMSOLAR_S C
Solar/Wind Harmer
0.271
213497CHSTR7-9
Adder
3.642
219914AD2-027 C
Solar/Wind Harmer
0.801
219236SOUTHERNHQ C
Solar/Wind Harmer
0.09
213958STHWK5-6
Adder
3.596
213560DLW11-12
Adder
3.58
219221BRL12CT1
Adder
11.748
219223BRL12CT3
Adder
11.748
213815MOSER1-3
Adder
4.644
20716428NHV_W2-082
Solar/Wind Harmer
2.313
959561AF2-247 GEN
Solar/Wind Harmer
0.631
20715728PEM_W1-119
Solar/Wind Harmer
0.694
20636028O CRK C1
Adder
9.184
963391AG1-188 GEN
Solar/Wind Harmer
4.858
20714928UPF_X1-085
Solar/Wind Harmer
0.526
971667AH1-334 GEN
Solar/Wind Harmer
3.551
219114HARTZY_C
Solar/Wind Harmer
1.075
219727YARDVSOLFA C
Solar/Wind Harmer
1.17
207454AA2-184 E
Solar/Wind Harmer
1.272
219918AC2-009 C
Solar/Wind Harmer
0.033
219612MATRIX C
Solar/Wind Harmer
0.232
20716928W4-060COL
Solar/Wind Harmer
0.899
20635828PARLN1&2
Adder
4.221
20635928PARLN3&4
Adder
4.221
217213AMBOY SO C
Solar/Wind Harmer
0.158
219249CENTRALDIV C
Solar/Wind Harmer
0.05
207442AE1-156 GEN
Solar/Wind Harmer
0.92
20673728F2S_V4-070
Solar/Wind Harmer
0.222
217211CAMDEN ST C
Solar/Wind Harmer
0.03
217169METRODIV C
Solar/Wind Harmer
0.049
217194REDH C
Solar/Wind Harmer
0.606
20674528F3S_W2-016
Solar/Wind Harmer
1.718
207510AF2-138 C
Solar/Wind Harmer
2.14
207511W3-106 GEN
Solar/Wind Harmer
0.397
971007AG2-625 GEN
Solar/Wind Harmer
3.05
207437AD2-070 GEN
Solar/Wind Harmer
0.355
20466127PORT 5CT
Adder
31.299
20671928W4-073
Solar/Wind Harmer
0.509
20674128FR_U2-059
Solar/Wind Harmer
0.217
20633028GILCT9
Adder
33.129
20465427SHAW CT
Adder
4.539
209116AE2-175 GEN
Solar/Wind Harmer
4.765
211065PSPA IPP
Solar/Wind Harmer
0.518
963161AG1-165 GEN
Solar/Wind Harmer
1.099
209025WIENIPP3
Adder
5.796
970095AG2-074 GEN
Solar/Wind Harmer
6.853
208972BECR K09
Solar/Wind Harmer
1.145
961331AF2-424 GEN
Solar/Wind Harmer
1.038
961421AF2-433 GEN
Solar/Wind Harmer
1.036
957921AF2-086 GEN
Solar/Wind Harmer
1.007
209142AF1-226 GEN
Solar/Wind Harmer
5.995
209093AE2-110 GEN
Solar/Wind Harmer
2.589
209120AE2-241 GEN
Solar/Wind Harmer
3.426
946691AF1-333 GEN
Solar/Wind Harmer
1
946741AF1-338 GEN
Solar/Wind Harmer
1
209071AE2-133 GEN
Solar/Wind Harmer
1.688
205941AD2-115 GEN
Solar/Wind Harmer
0.881
972221AH1-695 GEN
Adder
89.251
226910AB2-157 C
Solar/Wind Helper
0.024
227287AC2-120 GEN
Solar/Wind Helper
0.568
3141196NOKESVL
Solar/Wind Helper
1.155
966881AG1-559 GEN
Solar/Wind Helper
0.381
316223AC1-118
Solar/Wind Helper
0.428
3141906WESTMOR
Solar/Wind Helper
0.112
3147666LOUISA
Solar/Wind Helper
0.639
3132273ORANGE
Solar/Wind Helper
0.055
316077AC2-138 C
Solar/Wind Helper
0.261
316473AC1-191 GEN
Solar/Wind Helper
1.682
316484AD2-074 GEN
Solar/Wind Helper
0.531
316075AC2-137 C
Solar/Wind Helper
0.417
3142946ENON
Solar/Wind Helper
0.091
316458AB2-190 GEN2
Solar/Wind Helper
1.545
3145336SMITFLD
Solar/Wind Helper
0.107
3144536CHRHLND
Solar/Wind Helper
0.04
3144873MCLAUGH
Solar/Wind Helper
0.007
3142956BIRDNECK
Solar/Wind Helper
0.18
316017AA1-139 ULT1
Solar/Wind Helper
1.22
3146456SLIGO L269
Solar/Wind Helper
0.266
316305AF2-043 C
Solar/Wind Helper
0.359
316246AF1-032 C
Solar/Wind Helper
0.305
316320Y1-086
Solar/Wind Helper
0.119
316321Z2-027
Solar/Wind Helper
0.405
3146516WINFALL
Solar/Wind Helper
0.264
3146626S HERTFORD
Solar/Wind Helper
0.264
3145273HOLLAND
Solar/Wind Helper
0.198
3146376EDENTON
Solar/Wind Helper
0.262
315735AD1-075 GEN1
Solar/Wind Helper
1.485
3146206CASHIE
Solar/Wind Helper
0.259
3145893MURPHYS
Solar/Wind Helper
0.093
3145893MURPHYS
Solar/Wind Helper
0.258
3146173TUNIS
Solar/Wind Helper
0.258
3146776BUCKING
Solar/Wind Helper
0.093
966621AG1-532 GEN
Solar/Wind Helper
0.234
3146926FARMVIL
Solar/Wind Helper
0.154
23546401DTGZ2-030
Solar/Wind Helper
0.081
3146263WOODLND
Solar/Wind Helper
0.257
316181AB2-040 GEN
Solar/Wind Helper
1.843
3142666NORTHAMPTON
Solar/Wind Helper
0.256
3145963POPLR C
Solar/Wind Helper
0.256
316011AB1-132 GEN
Solar/Wind Helper
2.758
942461AE2-259 GEN
Solar/Wind Helper
1.724
316190AA2-174 GEN
Solar/Wind Helper
0.017
316317KELFORD C
Solar/Wind Helper
0.23
3145823KELFORD
Solar/Wind Helper
0.256
3147043LAWRENC
Solar/Wind Helper
0.153
3147133PAMPLIN
Solar/Wind Helper
0.8
316478AD1-087 GEN
Solar/Wind Helper
1.249
3145796HORNRTN
Solar/Wind Helper
1.019
3145796HORNRTN
Solar/Wind Helper
0.255
315821AE2-092 GEN
Solar/Wind Helper
2.356
316212AC1-099_GEN
Solar/Wind Helper
1.138
3145933PARMELE
Solar/Wind Helper
0.253
3145746EVERETS
Solar/Wind Helper
0.252
3145746EVERETS
Solar/Wind Helper
0.252
316420AA1-050 GEN
Solar/Wind Helper
1.439
3146233WITAKRS
Solar/Wind Helper
0.269
3146233WITAKRS
Solar/Wind Helper
0.17
3146073TAR RVR
Solar/Wind Helper
0.25
3146083TARBORO
Solar/Wind Helper
0.25
3138543CONSLDL
Solar/Wind Helper
0.165
209029WAYMART-WD
Solar/Wind Harmer
2.811
209027LOR2_Q27
Solar/Wind Harmer
4.798
212266LOR1
Solar/Wind Harmer
1.272
209054AE2-059 GEN
Solar/Wind Harmer
1.708
959431AF2-234 GEN
Solar/Wind Harmer
1.995
964051AG1-259 GEN
Solar/Wind Harmer
1.338
964061AG1-260 GEN
Solar/Wind Harmer
1.338
959421AF2-233 GEN
Solar/Wind Harmer
0.998
20486527WR_V4-052
Adder
0.947
208862AG1-362 C
Solar/Wind Harmer
0.63
20390726Y2-042
Adder
2.722
209067AE2-060 GEN
Solar/Wind Harmer
1.1
200917MEHOOPANY_G
Solar/Wind Harmer
3.476
20334726NME_Y1-047
Adder
2.337
203926AA2-133 GEN
Adder
2.109
226929AD2-058 GEN
Solar/Wind Helper
0.158
3141426STAFORD
Solar/Wind Helper
0.066
3138216PACIFIC
Solar/Wind Helper
0.049
316164AC1-076 GEN
Solar/Wind Helper
1.35
315651AD1-115 GEN
Solar/Wind Helper
0.951
316468AD1-105 GEN
Solar/Wind Helper
1.346
3141813NORNECK
Solar/Wind Helper
0.277
3141783LANCAST
Solar/Wind Helper
0.164
3141783LANCAST
Solar/Wind Helper
0.11
3138133OCRAN
Solar/Wind Helper
0.082
3141913WHIT STONE
Solar/Wind Helper
0.274
316059AD1-063 C
Solar/Wind Helper
0.276
957601AF2-054 GEN
Solar/Wind Helper
0.366
3141873WAN 176
Solar/Wind Helper
0.055
3143873LANEXA
Solar/Wind Helper
0.164
316233AE1-074 FULL
Solar/Wind Helper
0.415
957831AF2-077 GEN
Solar/Wind Helper
0.366
316382AG1-145 C
Solar/Wind Helper
0.365
316159AE1-175 C
Solar/Wind Helper
0.411
315697AD1-025 GEN
Solar/Wind Helper
3.084
315839AE2-212 C
Solar/Wind Helper
0.363
316236AE1-162_GEN
Solar/Wind Helper
0.361
3143316POE
Solar/Wind Helper
1.06
316316AC1-027 C
Solar/Wind Helper
0.422
316018AA1-139 ULT2
Solar/Wind Helper
1.148
316258AE1-075 C
Solar/Wind Helper
0.366
316405AF2-144 C
Solar/Wind Helper
0.305
313526AB2-022
Solar/Wind Helper
0.405
3146486SUNBURY
Solar/Wind Helper
0.265
3146486SUNBURY
Solar/Wind Helper
0.265
3145176PASQUOTANK
Solar/Wind Helper
0.164
315800Z1-036_GEN1
Solar/Wind Helper
1.446
3130156CHOWAN
Solar/Wind Helper
0.262
3130156CHOWAN
Solar/Wind Helper
0.262
238169AE2-226 GEN1
Solar/Wind Helper
0.638
238170AE2-226 GEN2
Solar/Wind Helper
0.638
3130546PLYMOUTH
Solar/Wind Helper
0.26
315732AD1-074 GEN1
Solar/Wind Helper
2.969
315733AD1-074 GEN2
Solar/Wind Helper
2.969
3146206CASHIE
Solar/Wind Helper
0.259
3145893MURPHYS
Solar/Wind Helper
0.698
3145893MURPHYS
Solar/Wind Helper
0.258
316463AE2-346 GEN
Solar/Wind Helper
0.236
3145513AHOSKIE
Solar/Wind Helper
0.115
961941AG1-037 GEN
Solar/Wind Helper
0.087
3145513AHOSKIE
Solar/Wind Helper
0.257
316322AB2-045
Solar/Wind Helper
0.288
946281AF1-292 GEN
Solar/Wind Helper
0.258
3146043SEABORD
Solar/Wind Helper
0.257
3145683EARLEYS
Solar/Wind Helper
0.514
3145683EARLEYS
Solar/Wind Helper
0.257
3145683EARLEYS
Solar/Wind Helper
0.257
3137643SOCKMAN
Solar/Wind Helper
1.023
316426AA2-053 GEN
Solar/Wind Helper
1.463
316174AB2-169 GEN
Solar/Wind Helper
0.654
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
316486AD2-202 GEN
Solar/Wind Helper
0.366
3145796HORNRTN
Solar/Wind Helper
0.815
3145796HORNRTN
Solar/Wind Helper
0.102
3146033SCOT NK
Solar/Wind Helper
1.018
3144303KENBRDG
Solar/Wind Helper
0.203
316210AC1-098 GEN
Solar/Wind Helper
2.049
316274AC1-208 GEN
Solar/Wind Helper
1.545
316238AB2-078_GEN
Solar/Wind Helper
0.34
316239AB2-077_GEN
Solar/Wind Helper
0.34
3145746EVERETS
Solar/Wind Helper
1.002
3145746EVERETS
Solar/Wind Helper
0.252
3145746EVERETS
Solar/Wind Helper
0.252
3145746EVERETS
Solar/Wind Helper
0.252
316327AA2-057 GEN
Solar/Wind Helper
1.436
3145573BETHELC
Solar/Wind Helper
0.25
3145573BETHELC
Solar/Wind Helper
0.25
3148133STUARTS
Solar/Wind Helper
0.149
3148013FISHERV
Solar/Wind Helper
0.143
3147173SINAI
Solar/Wind Helper
0.246
3147243WELCO
Solar/Wind Helper
0.154
315616AA1-038_C
Solar/Wind Helper
1.098
3148463FAIRFLD
Solar/Wind Helper
0.242
23779801AA1-109
Solar/Wind Helper
0.172
270455AD2-022 GEN
Solar/Wind Helper
1.365
270457AD2-023 GEN
Solar/Wind Helper
0.899
270197AD1-017 GEN1
Solar/Wind Helper
1.22
964211AG1-282 GEN
Solar/Wind Helper
0.372
3141726DUNNSVL
Solar/Wind Helper
1.105
316404AE1-155 C
Solar/Wind Helper
2.359
3138133OCRAN
Solar/Wind Helper
0.164
3142416OLDCHRC
Solar/Wind Helper
0.711
3142416OLDCHRC
Solar/Wind Helper
0.273
3141766HARMONY
Solar/Wind Helper
0.055
315662AE1-191 GEN
Solar/Wind Helper
1.472
316280AD1-041 GEN
Solar/Wind Helper
0.92
3142433PROV 92
Solar/Wind Helper
1.09
315975AC1-164 GENB
Solar/Wind Helper
0.104
3142543TWELFTH
Solar/Wind Helper
0.026
3143526WINTERP
Solar/Wind Helper
1.413
3143226MDLTHAN
Solar/Wind Helper
0.271
316132AB2-190 GEN1
Solar/Wind Helper
1.545
315671AE2-027_GEN
Solar/Wind Helper
2.18
316369SG1_INVT
Solar/Wind Helper
1.3
3145336SMITFLD
Solar/Wind Helper
1.072
315773AC2-141 GEN
Solar/Wind Helper
5.773
316381AD1-082 GEN
Solar/Wind Helper
1.388
316375AC2-012 GEN
Solar/Wind Helper
0.703
316036AC1-147 C
Solar/Wind Helper
0.408
316072AD1-144
Solar/Wind Helper
0.306
3146456SLIGO L269
Solar/Wind Helper
0.266
319010AE1-072 C
Solar/Wind Helper
3.046
3146516WINFALL
Solar/Wind Helper
0.856
3146516WINFALL
Solar/Wind Helper
0.264
315611Z1-036_GEN2
Solar/Wind Helper
1.446
3130156CHOWAN
Solar/Wind Helper
0.262
238175AF1-290_GEN
Solar/Wind Helper
0.141
315816AE2-034 GEN
Solar/Wind Helper
1.195
3145663CRESWEL
Solar/Wind Helper
0.73
315737AD1-076 GEN
Solar/Wind Helper
2.539
3146206CASHIE
Solar/Wind Helper
0.259
316023GEN1_S
Solar/Wind Helper
0.987
3145893MURPHYS
Solar/Wind Helper
1.034
3146173TUNIS
Solar/Wind Helper
0.258
3156021HOLLOMANSOL
Solar/Wind Helper
1.965
3146776BUCKING
Solar/Wind Helper
0.103
3145683EARLEYS
Solar/Wind Helper
0.257
315607AA1-063A GEN
Solar/Wind Helper
1.47
3146926FARMVIL
Solar/Wind Helper
0.154
3146263WOODLND
Solar/Wind Helper
0.257
316087AB2-174 GEN
Solar/Wind Helper
1.799
238152AF2-075_GEN
Solar/Wind Helper
0.633
3145963POPLR C
Solar/Wind Helper
0.256
3145823KELFORD
Solar/Wind Helper
0.256
3145783HORNRTN
Solar/Wind Helper
0.255
3145796HORNRTN
Solar/Wind Helper
0.841
3145796HORNRTN
Solar/Wind Helper
0.255
316034AC1-036 C
Solar/Wind Helper
0.266
315785AD2-033 C
Solar/Wind Helper
2.96
316129AC1-054 GEN
Solar/Wind Helper
1.256
316131AB2-060 GEN
Solar/Wind Helper
1.543
3145746EVERETS
Solar/Wind Helper
0.252
3145746EVERETS
Solar/Wind Helper
0.252
316494AC1-189 GEN
Solar/Wind Helper
1.532
3146233WITAKRS
Solar/Wind Helper
0.994
961671AG1-007 GEN
Solar/Wind Helper
0.179
3146083TARBORO
Solar/Wind Helper
0.25
3147983MERCK5
Solar/Wind Helper
0.099
316359AB2-059 GEN
Solar/Wind Helper
1.9
3145543BTLEBRO
Solar/Wind Helper
0.249
3145543BTLEBRO
Solar/Wind Helper
0.199
23777901MDS_W4-102
Solar/Wind Helper
0.154
3147123OTTER R
Solar/Wind Helper
0.137
270016AE1-250 BESS
Solar/Wind Helper
0.844
3147312GRETNA
Solar/Wind Helper
0.182
3146802CHATHAM
Solar/Wind Helper
0.171
238108AE1-109 GEN1
Solar/Wind Helper
0.084
238110AE1-109 GEN3
Solar/Wind Helper
0.084
270018AE2-047 C O1
Solar/Wind Helper
0.792
3145506HICKORY
Solar/Wind Helper
1.066
3145506HICKORY
Solar/Wind Helper
0.64
3145506HICKORY
Solar/Wind Helper
0.16
316349AD2-085 GEN
Solar/Wind Helper
1.22
316339AD2-160 GEN
Solar/Wind Helper
1.017
316388AE2-253 GEN
Solar/Wind Helper
1.017
3137176SLIGO L2192
Solar/Wind Helper
1.059
316313AB2-026
Solar/Wind Helper
0.406
3130086AYDLETT
Solar/Wind Helper
1.064
3146386ELIZ CT
Solar/Wind Helper
0.265
316431W1029_GEN1
Solar/Wind Helper
1.07
316433W1029_GEN2
Solar/Wind Helper
1.07
316435W1029_GEN3
Solar/Wind Helper
1.07
3146516WINFALL
Solar/Wind Helper
0.264
3146516WINFALL
Solar/Wind Helper
0.264
3146516WINFALL
Solar/Wind Helper
0.264
3146626S HERTFORD
Solar/Wind Helper
0.264
3146626S HERTFORD
Solar/Wind Helper
0.264
3144356SAPONY
Solar/Wind Helper
0.473
316315AB2-025 C
Solar/Wind Helper
0.403
315614AA2-178 GEN
Solar/Wind Helper
1.593
316365GEN2_N
Solar/Wind Helper
0.987
3145893MURPHYS
Solar/Wind Helper
0.371
3145893MURPHYS
Solar/Wind Helper
0.465
3146173TUNIS
Solar/Wind Helper
0.258
3146173TUNIS
Solar/Wind Helper
0.258
316140AB2-099
Solar/Wind Helper
0.098
3146776BUCKING
Solar/Wind Helper
1.029
3146776BUCKING
Solar/Wind Helper
0.083
313506AB2-031 GEN
Solar/Wind Helper
1.167
238147AE2-230_GEN1
Solar/Wind Helper
0.443
238148AE2-230_GEN2
Solar/Wind Helper
0.443
238149AF1-291A_GEN
Solar/Wind Helper
0.127
3142666NORTHAMPTON
Solar/Wind Helper
0.256
3142666NORTHAMPTON
Solar/Wind Helper
0.256
3142666NORTHAMPTON
Solar/Wind Helper
0.256
3142666NORTHAMPTON
Solar/Wind Helper
0.154
237061AD1-155 GEN
Solar/Wind Helper
1.604
3145593CAROLNA
Solar/Wind Helper
0.256
3145593CAROLNA
Solar/Wind Helper
0.256
3147133PAMPLIN
Solar/Wind Helper
0.255
3147133PAMPLIN
Solar/Wind Helper
0.204
3145796HORNRTN
Solar/Wind Helper
0.764
3145933PARMELE
Solar/Wind Helper
0.506
3145933PARMELE
Solar/Wind Helper
0.253
316237AB2-079_GEN
Solar/Wind Helper
0.34
316005AA1-067
Solar/Wind Helper
0.288
315687AD1-152 GEN
Solar/Wind Helper
1.354
3132123MT JACKSON
Solar/Wind Helper
0.782
3146843MT LREL
Solar/Wind Helper
0.249
3146843MT LREL
Solar/Wind Helper
0.249
316049AB1-081 GEN
Solar/Wind Helper
1.52
316118AC1-105 GEN
Solar/Wind Helper
0.964
316248AF1-058 C
Solar/Wind Helper
0.332
235020AA1-095 C
Solar/Wind Helper
0.046
316097T157 G90
Solar/Wind Helper
1.092
238221AF1-254 C O1
Solar/Wind Helper
0.231
270013AE1-250 PV
Solar/Wind Helper
0.844
237080AD1-060 GEN
Solar/Wind Helper
0.28
3148013FISHERV
Solar/Wind Helper
0.249
3145543BTLEBRO
Solar/Wind Helper
0.249
3145543BTLEBRO
Solar/Wind Helper
0.249
316499AE2-029_GEN
Solar/Wind Helper
0.837
270494AE1-108_GEN
Solar/Wind Helper
3.328
316003AC1-222 GEN
Solar/Wind Helper
1.064
316222AC1-221 GEN
Solar/Wind Helper
1.377
316283AC2-100 C
Solar/Wind Helper
1.283
316123AC1-075 GEN
Solar/Wind Helper
1.454
316095T157 G97
Solar/Wind Helper
1.092
23583801GRNGAP
Solar/Wind Helper
4.045
23777801MSM_W1-116
Solar/Wind Helper
0.1
316197AC1-042 GEN
Solar/Wind Helper
0.215
3147312GRETNA
Solar/Wind Helper
0.045
270173AC1-122 GEN
Solar/Wind Helper
1.527
238109AE1-109 GEN2
Solar/Wind Helper
0.084
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.974
VTFLTFEXP_VFT->PJM
CMTX
167.343
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.505
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.761
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.838
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.469
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
64.386
CBM NorthLTFEXP_CBM-N->PJM
CBM
88.776
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.01 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:5068.35
MW Contribution:
6.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
11.158
200195DELTA ST
50/50
5.688
200052ROCKSP 1
50/50
4.679
200053ROCKSP 2
50/50
4.587
232904IR4
Adder
150.952
232920IR10
Adder
5.9
232432Z2-076 GEN
Solar/Wind Harmer
0.246
233901CHERRYDALE C
Solar/Wind Harmer
2.1
232912OH NUG1
Adder
16.488
232913OH NUG2
Adder
16.268
233940AF2-379 C
Solar/Wind Harmer
0.348
971195AH1-057 GEN
Solar/Wind Harmer
1.819
233955AB2-172 GEN
Solar/Wind Harmer
9.311
232813VAUGHN
Adder
1.092
233968AD2-076_GEN
Solar/Wind Harmer
12.195
970597AG2-380 GEN
Solar/Wind Harmer
7.658
231906DC3 NUG
Adder
25.712
231902DC CT7
Adder
20.555
231907DC10
Adder
6.419
233915AB1-141 GEN
Solar/Wind Harmer
1.81
231919CHRIST1
Adder
7.728
231920CHRIST2
Adder
7.557
970453AG2-297 GEN
Solar/Wind Harmer
4.121
972141AH1-641 GEN
Solar/Wind Harmer
4.232
230430AE1-229_GEN
Solar/Wind Harmer
42.068
964001AG1-254 GEN
Solar/Wind Harmer
10.701
230422AE1-104_GEN1
Solar/Wind Harmer
49.451
230425AE1-104_GEN2
Solar/Wind Harmer
49.451
228728W1-130C
Solar/Wind Harmer
0.97
230434AG1-499 GEN
Solar/Wind Harmer
0.842
230407AD2-065 C
Solar/Wind Harmer
0.191
227927V4-067C
Solar/Wind Harmer
0.288
200192DELTA CT1
50/50
3.682
200194DELTA CT3
50/50
3.682
200204Y1-065-CTG1
50/50
7.437
200054ROCKSP 3
50/50
4.733
232901NORTHST
Adder
15.553
233970AC1-092 C
Solar/Wind Harmer
5.006
234033AF1-007_GEN
Solar/Wind Harmer
69.442
232404W1-003 C
Solar/Wind Harmer
1.866
232408W1-005 C
Solar/Wind Harmer
1.866
232917OH NUG6
Adder
16.415
232915OH NUG4
Adder
16.378
233996TM1833_GEN
Solar/Wind Harmer
1.86
233998TM1NIN_3.36
Solar/Wind Harmer
1.86
972177AH1-672 GEN
Solar/Wind Harmer
25.067
232919VN10
Adder
5.235
232900DEMECSMY
Adder
17.201
232426Y1-080 FULL
Solar/Wind Harmer
0.356
232902EASTMUNI
Adder
24.193
234012AE2-112_GEN
Solar/Wind Harmer
4.231
233944AB2-135 GEN
Solar/Wind Harmer
9.589
233918AB1-142 GEN
Solar/Wind Harmer
1.81
972251AH1-710 GEN
Adder
80.304
231918WEST 1
Adder
5.882
231917EM10
Adder
4.08
228206SHRMN CT
Adder
24.633
228732V1-021 C
Adder
0.28
228260V4-054C
Solar/Wind Harmer
1.516
970997AG2-616 GEN
Solar/Wind Harmer
14.106
228729W2-030 C
Solar/Wind Harmer
0.84
228400MICK 1CT
Adder
17.044
213497CHSTR7-9
Adder
3.911
213497CHSTR7-9
Adder
3.911
219766PARADISE C
Solar/Wind Harmer
0.441
219686LUMSOLAR_N C
Solar/Wind Harmer
0.282
213958STHWK5-6
Adder
3.797
219907AC1-030 C
Solar/Wind Harmer
0.191
213560DLW11-12
Adder
3.736
219348LDSOLAR C
Solar/Wind Harmer
0.809
219222BRL12CT2
Adder
12.074
213611FALLS1-3
Adder
4.677
20716028EGP_W2-019
Solar/Wind Harmer
0.61
207522AF2-254 C
Solar/Wind Harmer
1.885
20717128DIX_Z2-102
Solar/Wind Harmer
1.732
20715828PEM_W1-120
Solar/Wind Harmer
0.7
214194N WALES4
Adder
1.114
963711AG1-223 GEN
Solar/Wind Harmer
1.878
20714528FRN_Y2-051
Solar/Wind Harmer
0.374
219276PARKLANDSO C
Solar/Wind Harmer
0.582
219680HOPEWELLV C1
Solar/Wind Harmer
0.095
20715228NPK_W1-113
Solar/Wind Harmer
0.534
20720528MAN_W1-024
Solar/Wind Harmer
0.315
20720428HOL_W1-112
Solar/Wind Harmer
0.425
20635828PARLN1&2
Adder
8.905
20635028RRCT1&2
Adder
14.092
218524CNTRALGAS1 C
Solar/Wind Harmer
0.437
218440SUMMTASSOC C
Solar/Wind Harmer
0.151
218428ETC SOLAR C
Solar/Wind Harmer
0.042
219908AB1-139 C
Solar/Wind Harmer
0.448
219919AE1-041 FULL
Solar/Wind Harmer
0.048
972275AH1-722 GEN
Adder
36.889
200201DELTA2 CT2
50/50
6.589
200034PCHBTM 2
50/50
38.39
200035PCHBTM 3
50/50
38.06
200205Y1-065-CTG2
50/50
7.437
233971AC1-093 C
Solar/Wind Harmer
4.753
232410W1-006 C
Solar/Wind Harmer
1.866
232918OH NUG7
Adder
16.378
232905CHERITON_25
Adder
4.58
232926CRISFLD1
Adder
3.664
234015AF2-250 C
Solar/Wind Harmer
0.224
232428Y3-058 C
Solar/Wind Harmer
1.555
231940T-011
Adder
1.392
233994AC2-023 GEN
Solar/Wind Harmer
5.009
232899W1-062
Adder
17.933
233946AB2-136 GEN
Solar/Wind Harmer
7.433
234036AF2-325 C
Solar/Wind Harmer
1.708
234041AC1-190 GEN
Solar/Wind Harmer
16.684
233952AC2-187 GEN
Solar/Wind Harmer
2.093
233954AC2-188 GEN
Solar/Wind Harmer
2.093
232910NRG_G1
Adder
15.988
233984AB2-036 GEN
Solar/Wind Harmer
23.015
232424Y1-079 C
Solar/Wind Harmer
1.038
234014AF1-036_GEN
Solar/Wind Harmer
4.978
232436AB1-176 C
Solar/Wind Harmer
0.421
233930AB2-032 GEN
Solar/Wind Harmer
1.524
233982AB2-133 GEN
Solar/Wind Harmer
8.899
228251CARLLS#4
Adder
0.932
228201CARL#2CT
Adder
10.156
228200CARL#1CT
Adder
9.66
228351V2-046C
Solar/Wind Harmer
2.956
230433AD2-135 GEN
Solar/Wind Harmer
0.148
230511AF1-262
Solar/Wind Harmer
0.268
228307PCLP GT
Adder
17.618
228754AB1-001 C
Solar/Wind Harmer
0.202
972233AH1-701 GEN
Adder
6.064
213589EDDYSTN4
Adder
113.991
213587EDDYSTN3
Adder
113.958
219272CLEANLIGHT C
Solar/Wind Harmer
0.256
219904AC1-010 C
Solar/Wind Harmer
0.53
219287REEVESEAST C
Solar/Wind Harmer
1.876
219912AD2-042 GEN
Solar/Wind Harmer
1.108
219906AC1-017 C
Solar/Wind Harmer
0.304
219607WPEMNERT C
Solar/Wind Harmer
0.566
219304NAMERICA C
Solar/Wind Harmer
0.42
213535CROYDN11
Adder
13.816
213815MOSER1-3
Adder
4.773
213815MOSER1-3
Adder
4.773
214067T20SOLAR
Solar/Wind Harmer
0.334
20720828JCB_W4-025
Solar/Wind Harmer
0.595
20636128O CRK C2
Adder
8.425
207459AE1-142 C O1
Solar/Wind Harmer
1.361
20628028LAKEHURS
Adder
1.224
20714828MDF_W3-079
Solar/Wind Harmer
0.388
219817TRENTONSOL C
Solar/Wind Harmer
1.38
20641628MLH_W1-032
Solar/Wind Harmer
0.365
20742028HF_AC1-207
Solar/Wind Harmer
0.97
217197RE CRAN C
Solar/Wind Harmer
0.655
218438BLK ROCK C
Solar/Wind Harmer
0.166
924131AB2-057 GEN
Solar/Wind Harmer
1.234
20635028RRCT1&2
Adder
13.875
20635128RRCT3&4
Adder
13.393
20635128RRCT3&4
Adder
11.683
218418LINDEN_G5
Adder
20.066
218419LINDEN_G6
Adder
20.066
972260AH1-715 GEN1
Adder
16.068
219036LINDEN_G7
Adder
19.339
219035LINDEN_G8
Adder
19.063
972261AH1-715 GEN2
Adder
18.513
20675428EAM_W2-061
Solar/Wind Harmer
0.218
217081WEATEXAS C
Solar/Wind Harmer
0.099
217202FBANKSOLAR C
Solar/Wind Harmer
0.084
217201HACKENSOLA C
Solar/Wind Harmer
0.083
972237AH1-703 GEN
Adder
11.476
217206BARNGR HS C
Solar/Wind Harmer
0.035
219137THOSOLAR C
Solar/Wind Harmer
1.719
219258KINSLEYDEP C
Solar/Wind Harmer
0.456
213942SCHUYLKILL
Adder
4.971
213942SCHUYLKILL
Adder
3.801
213957STHWK3-4
Adder
3.797
213957STHWK3-4
Adder
3.797
213561DLWR9-10
Adder
4.885
213561DLWR9-10
Adder
3.736
219615MILLCREEK C
Solar/Wind Harmer
0.325
219610FLORENCE C
Solar/Wind Harmer
1.873
219224BRL12CT4
Adder
12.074
213611FALLS1-3
Adder
4.677
213611FALLS1-3
Adder
4.677
20720728JCB_W1-129
Solar/Wind Harmer
0.392
20715028HAN_X4-015
Solar/Wind Harmer
0.392
207487AE2-000G4
Solar/Wind Harmer
41.181
207497AE2-000G2
Solar/Wind Harmer
41.181
207500AE2-000G1
Solar/Wind Harmer
41.181
207507AE2-000G3
Solar/Wind Harmer
41.181
963401AG1-189 GEN
Solar/Wind Harmer
2.961
970025AG2-016 GEN
Solar/Wind Harmer
3.683
971189AH1-054 GEN
Solar/Wind Harmer
1.531
207445AB1-138_GEN
Solar/Wind Harmer
0.745
219620RIDERU C
Solar/Wind Harmer
0.07
20714428HOW_X1-037
Solar/Wind Harmer
1.542
20720628TIN_W1-124
Solar/Wind Harmer
1.238
20716228APLW2-078
Solar/Wind Harmer
1.097
971521AH1-258 GEN
Solar/Wind Harmer
3.337
20635928PARLN3&4
Adder
8.905
218526CNTRALGAS2 C
Solar/Wind Harmer
0.439
20675528CPH_W2-050
Solar/Wind Harmer
0.673
20673828FLE_V3-070
Solar/Wind Harmer
0.542
218449LINSOLAR C
Solar/Wind Harmer
1.163
20676128MHD_W3-029
Solar/Wind Harmer
0.55
20676428JCR_X2-075
Solar/Wind Harmer
0.392
217167KRNY_14
Adder
10.537
217086KRNY_131
Adder
10.447
217147KRNY_1212
Adder
10.022
217147KRNY_1212
Adder
9.843
217146KRNY_1234
Adder
9.821
217146KRNY_1234
Adder
9.754
964851AG1-348 GEN
Solar/Wind Harmer
1.391
971009AG2-626 GEN
Solar/Wind Harmer
1.667
207408W3-077 C
Solar/Wind Harmer
0.509
20675128HRM_W1-127
Solar/Wind Harmer
0.168
20462827N BANGR8
Adder
0.708
961261AF2-417 GEN
Solar/Wind Harmer
0.886
209029WAYMART-WD
Solar/Wind Harmer
2.183
209026WIENIPP4
Adder
4.436
209027LOR2_Q27
Solar/Wind Harmer
3.43
212266LOR1
Solar/Wind Harmer
0.909
209054AE2-059 GEN
Solar/Wind Harmer
1.158
959431AF2-234 GEN
Solar/Wind Harmer
1.328
964051AG1-259 GEN
Solar/Wind Harmer
0.891
964061AG1-260 GEN
Solar/Wind Harmer
0.891
959421AF2-233 GEN
Solar/Wind Harmer
0.664
226929AD2-058 GEN
Solar/Wind Helper
0.12
3141426STAFORD
Solar/Wind Helper
0.056
3138216PACIFIC
Solar/Wind Helper
0.042
316164AC1-076 GEN
Solar/Wind Helper
1.186
315651AD1-115 GEN
Solar/Wind Helper
0.837
20673628F1S_V4-069
Solar/Wind Harmer
0.207
207528AF2-192 GEN
Solar/Wind Harmer
1.466
217209CENTRL HS C
Solar/Wind Harmer
0.051
217186ESSEX_G9
Adder
4.476
217121ECCF
Adder
0.492
217083KRNY_132
Adder
10.537
217208PARK ELE C
Solar/Wind Harmer
0.029
20671828STAW2-080
Solar/Wind Harmer
0.118
20676728BRNX1-095
Solar/Wind Harmer
0.194
966261AG1-495 GEN
Solar/Wind Harmer
3.783
207439AE1-081 C O1
Solar/Wind Harmer
0.064
20676328BVR_Y1-020
Solar/Wind Harmer
0.352
20674628WNG_W3-110
Solar/Wind Harmer
0.427
20676228FRD_X1-012
Solar/Wind Harmer
0.624
207530AG1-191 GEN
Solar/Wind Harmer
1.449
20675828AU_W4-064
Solar/Wind Harmer
0.182
20674928WA_W3-044
Solar/Wind Harmer
0.494
971519AH1-257 GEN
Solar/Wind Harmer
2.558
20675728RH_W2-091
Solar/Wind Harmer
0.606
207518AF1-320_GEN
Solar/Wind Harmer
3.668
207484AF2-139 C O1
Solar/Wind Harmer
0.504
20465127PORT CT
Adder
2.992
208909MACR G3
Adder
154.549
211065PSPA IPP
Solar/Wind Harmer
0.414
963071AG1-156 GEN
Solar/Wind Harmer
8.288
209010PEIP 1
Adder
0.543
961301AF2-421 GEN
Solar/Wind Harmer
0.832
963151AG1-164 GEN
Solar/Wind Harmer
0.832
209023WIENIPP1
Adder
8.977
209025WIENIPP3
Adder
4.481
961341AF2-425 GEN
Solar/Wind Harmer
0.73
212507AE2-042_GEN
Solar/Wind Harmer
2.052
946731AF1-337 GEN
Solar/Wind Harmer
0.669
209018SUNBIPCT
Adder
4.947
316415AF1-147_GEN2
Solar/Wind Helper
0.856
316447AC1-158 HLD
Solar/Wind Helper
3.049
316044AC1-158 PL1
Solar/Wind Helper
1.386
3147666LOUISA
Solar/Wind Helper
0.982
316192AB2-158 GEN
Solar/Wind Helper
1.653
316337AD2-073 GEN
Solar/Wind Helper
0.373
964211AG1-282 GEN
Solar/Wind Helper
0.329
3141726DUNNSVL
Solar/Wind Helper
0.977
316404AE1-155 C
Solar/Wind Helper
2.087
3142416OLDCHRC
Solar/Wind Helper
0.631
3142416OLDCHRC
Solar/Wind Helper
0.242
3138133OCRAN
Solar/Wind Helper
0.146
3141766HARMONY
Solar/Wind Helper
0.048
217086KRNY_131
Adder
10.559
217083KRNY_132
Adder
10.47
217204WCALDSOLAR C
Solar/Wind Harmer
0.082
20674328GAR_V4-001
Solar/Wind Harmer
0.116
20674828DL_W4-046
Solar/Wind Harmer
0.665
207471AF2-354 C
Solar/Wind Harmer
0.525
20634528N27_Y2-018
Solar/Wind Harmer
0.274
20675928HOL_W4-097
Solar/Wind Harmer
0.13
20465127PORT CT
Adder
3.97
209010PEIP 1
Adder
2.989
209010PEIP 1
Adder
0.438
961541AF2-445A GEN
Solar/Wind Harmer
2.465
961431AF2-434 GEN
Solar/Wind Harmer
0.727
946751AF1-339 GEN
Solar/Wind Harmer
0.669
209130AF1-271A GEN
Solar/Wind Harmer
1.867
223401AF1-299 GEN
Solar/Wind Helper
0.484
223402AF1-300 C
Solar/Wind Helper
0.484
316411AF1-147_GEN1
Solar/Wind Helper
0.856
316006AB2-029 C
Solar/Wind Helper
0.12
316045AC1-158 PL2
Solar/Wind Helper
4.434
316450AC1-158 RIC
Solar/Wind Helper
0.37
966001AG1-469 GEN
Solar/Wind Helper
0.261
966871AG1-558 GEN
Solar/Wind Helper
0.329
316487AF1-042 GEN
Solar/Wind Helper
0.246
316312AB1-027
Solar/Wind Helper
0.464
315666AE1-190 GEN
Solar/Wind Helper
0.327
316156AD2-030 GEN
Solar/Wind Helper
0.367
315976AC1-164 GENA
Solar/Wind Helper
3.126
316169AC1-164_GENC
Solar/Wind Helper
2.7
3142946ENON
Solar/Wind Helper
0.024
3143526WINTERP
Solar/Wind Helper
1.257
316240AF1-291 C
Solar/Wind Helper
0.324
316033AB2-134 GEN
Solar/Wind Helper
0.833
316294AC1-161 GEN
Solar/Wind Helper
4.388
316185AD1-033 GEN
Solar/Wind Helper
1.127
3145506HICKORY
Solar/Wind Helper
0.955
3145506HICKORY
Solar/Wind Helper
0.573
3145506HICKORY
Solar/Wind Helper
0.143
316349AD2-085 GEN
Solar/Wind Helper
1.094
316339AD2-160 GEN
Solar/Wind Helper
0.911
316388AE2-253 GEN
Solar/Wind Helper
0.911
316313AB2-026
Solar/Wind Helper
0.365
3137176SLIGO L2192
Solar/Wind Helper
0.949
3130086AYDLETT
Solar/Wind Helper
0.954
3146386ELIZ CT
Solar/Wind Helper
0.238
316431W1029_GEN1
Solar/Wind Helper
0.961
316433W1029_GEN2
Solar/Wind Helper
0.961
316435W1029_GEN3
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
3146626S HERTFORD
Solar/Wind Helper
0.237
3146626S HERTFORD
Solar/Wind Helper
0.237
3144356SAPONY
Solar/Wind Helper
0.425
316315AB2-025 C
Solar/Wind Helper
0.362
315614AA2-178 GEN
Solar/Wind Helper
1.439
238147AE2-230_GEN1
Solar/Wind Helper
0.406
238148AE2-230_GEN2
Solar/Wind Helper
0.406
238149AF1-291A_GEN
Solar/Wind Helper
0.116
237061AD1-155 GEN
Solar/Wind Helper
1.469
316365GEN2_N
Solar/Wind Helper
0.894
3145893MURPHYS
Solar/Wind Helper
0.336
3145893MURPHYS
Solar/Wind Helper
0.422
3146173TUNIS
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
3146776BUCKING
Solar/Wind Helper
0.935
3146776BUCKING
Solar/Wind Helper
0.076
316140AB2-099
Solar/Wind Helper
0.089
313506AB2-031 GEN
Solar/Wind Helper
1.061
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.14
3145593CAROLNA
Solar/Wind Helper
0.233
3145593CAROLNA
Solar/Wind Helper
0.233
3147133PAMPLIN
Solar/Wind Helper
0.232
3147133PAMPLIN
Solar/Wind Helper
0.186
3145796HORNRTN
Solar/Wind Helper
0.696
3145933PARMELE
Solar/Wind Helper
0.462
3145933PARMELE
Solar/Wind Helper
0.231
316237AB2-079_GEN
Solar/Wind Helper
0.311
316005AA1-067
Solar/Wind Helper
0.264
3132123MT JACKSON
Solar/Wind Helper
0.721
235020AA1-095 C
Solar/Wind Helper
0.043
315687AD1-152 GEN
Solar/Wind Helper
1.24
3146843MT LREL
Solar/Wind Helper
0.229
3146843MT LREL
Solar/Wind Helper
0.229
316049AB1-081 GEN
Solar/Wind Helper
1.397
316118AC1-105 GEN
Solar/Wind Helper
0.888
316248AF1-058 C
Solar/Wind Helper
0.306
237006AB1-125 GEN
Solar/Wind Helper
0.106
238221AF1-254 C O1
Solar/Wind Helper
0.222
316097T157 G90
Solar/Wind Helper
1.03
316468AD1-105 GEN
Solar/Wind Helper
1.184
3141813NORNECK
Solar/Wind Helper
0.244
3141783LANCAST
Solar/Wind Helper
0.146
3141783LANCAST
Solar/Wind Helper
0.097
3138133OCRAN
Solar/Wind Helper
0.073
3141913WHIT STONE
Solar/Wind Helper
0.243
316059AD1-063 C
Solar/Wind Helper
0.245
957601AF2-054 GEN
Solar/Wind Helper
0.325
3141873WAN 176
Solar/Wind Helper
0.048
3143873LANEXA
Solar/Wind Helper
0.145
316233AE1-074 FULL
Solar/Wind Helper
0.369
957831AF2-077 GEN
Solar/Wind Helper
0.325
316382AG1-145 C
Solar/Wind Helper
0.325
316159AE1-175 C
Solar/Wind Helper
0.366
315697AD1-025 GEN
Solar/Wind Helper
2.753
315839AE2-212 C
Solar/Wind Helper
0.324
316236AE1-162_GEN
Solar/Wind Helper
0.323
3143316POE
Solar/Wind Helper
0.948
316316AC1-027 C
Solar/Wind Helper
0.378
316258AE1-075 C
Solar/Wind Helper
0.328
316405AF2-144 C
Solar/Wind Helper
0.273
316018AA1-139 ULT2
Solar/Wind Helper
1.029
238169AE2-226 GEN1
Solar/Wind Helper
0.583
238170AE2-226 GEN2
Solar/Wind Helper
0.583
313526AB2-022
Solar/Wind Helper
0.364
3146486SUNBURY
Solar/Wind Helper
0.238
3146486SUNBURY
Solar/Wind Helper
0.238
3145176PASQUOTANK
Solar/Wind Helper
0.147
315800Z1-036_GEN1
Solar/Wind Helper
1.302
3130156CHOWAN
Solar/Wind Helper
0.236
3130156CHOWAN
Solar/Wind Helper
0.236
3130546PLYMOUTH
Solar/Wind Helper
0.235
315732AD1-074 GEN1
Solar/Wind Helper
2.687
315733AD1-074 GEN2
Solar/Wind Helper
2.687
3146206CASHIE
Solar/Wind Helper
0.234
3145893MURPHYS
Solar/Wind Helper
0.632
3145893MURPHYS
Solar/Wind Helper
0.234
316322AB2-045
Solar/Wind Helper
0.261
316463AE2-346 GEN
Solar/Wind Helper
0.214
3145513AHOSKIE
Solar/Wind Helper
0.105
961941AG1-037 GEN
Solar/Wind Helper
0.079
3145513AHOSKIE
Solar/Wind Helper
0.234
946281AF1-292 GEN
Solar/Wind Helper
0.234
3146043SEABORD
Solar/Wind Helper
0.233
3145683EARLEYS
Solar/Wind Helper
0.467
3145683EARLEYS
Solar/Wind Helper
0.233
3145683EARLEYS
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.007
3137643SOCKMAN
Solar/Wind Helper
0.93
316426AA2-053 GEN
Solar/Wind Helper
1.331
316174AB2-169 GEN
Solar/Wind Helper
0.595
316486AD2-202 GEN
Solar/Wind Helper
0.333
3145796HORNRTN
Solar/Wind Helper
0.743
3145796HORNRTN
Solar/Wind Helper
0.093
3146033SCOT NK
Solar/Wind Helper
0.927
3144303KENBRDG
Solar/Wind Helper
0.185
316210AC1-098 GEN
Solar/Wind Helper
1.87
316274AC1-208 GEN
Solar/Wind Helper
1.411
23779801AA1-109
Solar/Wind Helper
0.167
316238AB2-078_GEN
Solar/Wind Helper
0.311
316239AB2-077_GEN
Solar/Wind Helper
0.311
3145746EVERETS
Solar/Wind Helper
0.917
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
316327AA2-057 GEN
Solar/Wind Helper
1.315
3148133STUARTS
Solar/Wind Helper
0.138
3148013FISHERV
Solar/Wind Helper
0.132
315662AE1-191 GEN
Solar/Wind Helper
1.307
316280AD1-041 GEN
Solar/Wind Helper
0.817
3142433PROV 92
Solar/Wind Helper
0.969
315975AC1-164 GENB
Solar/Wind Helper
0.092
3143526WINTERP
Solar/Wind Helper
1.257
3142543TWELFTH
Solar/Wind Helper
0.023
3143226MDLTHAN
Solar/Wind Helper
0.242
316132AB2-190 GEN1
Solar/Wind Helper
1.378
315671AE2-027_GEN
Solar/Wind Helper
1.945
316369SG1_INVT
Solar/Wind Helper
1.16
3145336SMITFLD
Solar/Wind Helper
0.958
315773AC2-141 GEN
Solar/Wind Helper
5.163
238175AF1-290_GEN
Solar/Wind Helper
0.129
316381AD1-082 GEN
Solar/Wind Helper
1.242
316375AC2-012 GEN
Solar/Wind Helper
0.63
316036AC1-147 C
Solar/Wind Helper
0.365
316072AD1-144
Solar/Wind Helper
0.274
3146456SLIGO L269
Solar/Wind Helper
0.239
319010AE1-072 C
Solar/Wind Helper
2.731
3146516WINFALL
Solar/Wind Helper
0.769
3146516WINFALL
Solar/Wind Helper
0.238
315611Z1-036_GEN2
Solar/Wind Helper
1.302
3130156CHOWAN
Solar/Wind Helper
0.236
315816AE2-034 GEN
Solar/Wind Helper
1.079
3145663CRESWEL
Solar/Wind Helper
0.659
238152AF2-075_GEN
Solar/Wind Helper
0.58
315737AD1-076 GEN
Solar/Wind Helper
2.298
316023GEN1_S
Solar/Wind Helper
0.894
3146206CASHIE
Solar/Wind Helper
0.234
3145893MURPHYS
Solar/Wind Helper
0.937
3146173TUNIS
Solar/Wind Helper
0.234
3146776BUCKING
Solar/Wind Helper
0.093
3156021HOLLOMANSOL
Solar/Wind Helper
1.783
3146926FARMVIL
Solar/Wind Helper
0.14
3145683EARLEYS
Solar/Wind Helper
0.233
315607AA1-063A GEN
Solar/Wind Helper
1.335
316087AB2-174 GEN
Solar/Wind Helper
1.634
3146263WOODLND
Solar/Wind Helper
0.233
3145963POPLR C
Solar/Wind Helper
0.233
3145823KELFORD
Solar/Wind Helper
0.233
3145783HORNRTN
Solar/Wind Helper
0.232
3145796HORNRTN
Solar/Wind Helper
0.766
3145796HORNRTN
Solar/Wind Helper
0.232
316034AC1-036 C
Solar/Wind Helper
0.243
315785AD2-033 C
Solar/Wind Helper
2.702
23777901MDS_W4-102
Solar/Wind Helper
0.145
316129AC1-054 GEN
Solar/Wind Helper
1.147
316131AB2-060 GEN
Solar/Wind Helper
1.41
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
316494AC1-189 GEN
Solar/Wind Helper
1.404
3147983MERCK5
Solar/Wind Helper
0.092
3146233WITAKRS
Solar/Wind Helper
0.912
961671AG1-007 GEN
Solar/Wind Helper
0.165
3146083TARBORO
Solar/Wind Helper
0.229
316359AB2-059 GEN
Solar/Wind Helper
1.746
3145543BTLEBRO
Solar/Wind Helper
0.229
3145543BTLEBRO
Solar/Wind Helper
0.183
200200DELTA2 CT1
50/50
6.589
200193DELTA CT2
50/50
3.682
200203Y1-065-STG
50/50
12.879
200055ROCKSP 4
50/50
4.651
233987AB2-037 GEN
Solar/Wind Harmer
21.269
233973AC2-185 C
Solar/Wind Harmer
10.113
970695AG2-447 GEN
Solar/Wind Harmer
6.69
233939AC1-091 C
Solar/Wind Harmer
5.006
233972AC1-094 C
Solar/Wind Harmer
4.02
232434Z2-077 GEN
Solar/Wind Harmer
0.467
232406W1-004 FULL
Solar/Wind Harmer
1.866
232914OH NUG3
Adder
16.488
232916OH NUG5
Adder
16.488
232921TASLEY2G
Adder
9.636
233923SMA
Solar/Wind Harmer
6.821
233997TMININ_4.2
Solar/Wind Harmer
1.86
232907VN8
Adder
56.056
233964AF2-378 GEN
Solar/Wind Harmer
0.238
232417X3-008 C
Solar/Wind Harmer
2.095
233950AC2-186 GEN
Solar/Wind Harmer
1.047
232422X3-066 FULL
Solar/Wind Harmer
0.459
233933AB2-153 GEN
Solar/Wind Harmer
2.057
233935AB2-179 C
Solar/Wind Harmer
4.455
228711V2-041C
Solar/Wind Harmer
0.893
230415AB2-049 C
Solar/Wind Harmer
0.277
213497CHSTR7-9
Adder
3.911
219623KINSLEYBEA C
Solar/Wind Harmer
0.604
219921AF1-264
Solar/Wind Harmer
0.203
219291REEVESSOUT C
Solar/Wind Harmer
0.084
218660EHAMPSOLAR C
Solar/Wind Harmer
0.244
213958STHWK5-6
Adder
3.797
219688LUMSOLAR_S C
Solar/Wind Harmer
0.282
219914AD2-027 C
Solar/Wind Harmer
0.836
219236SOUTHERNHQ C
Solar/Wind Harmer
0.093
213560DLW11-12
Adder
3.736
219221BRL12CT1
Adder
12.074
219223BRL12CT3
Adder
12.074
213815MOSER1-3
Adder
4.773
959561AF2-247 GEN
Solar/Wind Harmer
0.64
20716428NHV_W2-082
Solar/Wind Harmer
2.336
20715728PEM_W1-119
Solar/Wind Harmer
0.7
20636028O CRK C1
Adder
9.24
963391AG1-188 GEN
Solar/Wind Harmer
4.87
20714928UPF_X1-085
Solar/Wind Harmer
0.526
971667AH1-334 GEN
Solar/Wind Harmer
3.545
219114HARTZY_C
Solar/Wind Harmer
1.074
219727YARDVSOLFA C
Solar/Wind Harmer
1.165
207454AA2-184 E
Solar/Wind Harmer
1.242
219918AC2-009 C
Solar/Wind Harmer
0.032
219612MATRIX C
Solar/Wind Harmer
0.224
20716928W4-060COL
Solar/Wind Harmer
0.866
20635828PARLN1&2
Adder
4.033
20635928PARLN3&4
Adder
4.033
217213AMBOY SO C
Solar/Wind Harmer
0.149
219249CENTRALDIV C
Solar/Wind Harmer
0.046
207442AE1-156 GEN
Solar/Wind Harmer
0.857
20673728F2S_V4-070
Solar/Wind Harmer
0.207
217211CAMDEN ST C
Solar/Wind Harmer
0.028
217169METRODIV C
Solar/Wind Harmer
0.045
217194REDH C
Solar/Wind Harmer
0.557
20674528F3S_W2-016
Solar/Wind Harmer
1.565
207510AF2-138 C
Solar/Wind Harmer
1.884
207511W3-106 GEN
Solar/Wind Harmer
0.35
971007AG2-625 GEN
Solar/Wind Harmer
2.614
207437AD2-070 GEN
Solar/Wind Harmer
0.3
20466127PORT 5CT
Adder
26.45
20671928W4-073
Solar/Wind Harmer
0.428
20674128FR_U2-059
Solar/Wind Harmer
0.182
20465427SHAW CT
Adder
3.814
20633028GILCT9
Adder
27.819
209116AE2-175 GEN
Solar/Wind Harmer
3.885
211065PSPA IPP
Solar/Wind Harmer
0.414
970095AG2-074 GEN
Solar/Wind Harmer
5.249
963161AG1-165 GEN
Solar/Wind Harmer
0.832
209025WIENIPP3
Adder
4.39
208972BECR K09
Solar/Wind Harmer
0.867
961331AF2-424 GEN
Solar/Wind Harmer
0.73
961421AF2-433 GEN
Solar/Wind Harmer
0.727
957921AF2-086 GEN
Solar/Wind Harmer
0.707
209142AF1-226 GEN
Solar/Wind Harmer
4.21
209093AE2-110 GEN
Solar/Wind Harmer
1.818
209120AE2-241 GEN
Solar/Wind Harmer
2.406
946691AF1-333 GEN
Solar/Wind Harmer
0.669
946741AF1-338 GEN
Solar/Wind Harmer
0.669
209071AE2-133 GEN
Solar/Wind Harmer
1.124
205941AD2-115 GEN
Solar/Wind Harmer
0.583
226910AB2-157 C
Solar/Wind Helper
0.018
227287AC2-120 GEN
Solar/Wind Helper
0.426
3141196NOKESVL
Solar/Wind Helper
1.01
966881AG1-559 GEN
Solar/Wind Helper
0.334
316223AC1-118
Solar/Wind Helper
0.376
3141906WESTMOR
Solar/Wind Helper
0.098
3132273ORANGE
Solar/Wind Helper
0.049
3147666LOUISA
Solar/Wind Helper
0.565
316077AC2-138 C
Solar/Wind Helper
0.231
316473AC1-191 GEN
Solar/Wind Helper
1.489
316484AD2-074 GEN
Solar/Wind Helper
0.47
316075AC2-137 C
Solar/Wind Helper
0.37
3142946ENON
Solar/Wind Helper
0.081
316458AB2-190 GEN2
Solar/Wind Helper
1.378
3145336SMITFLD
Solar/Wind Helper
0.096
3144536CHRHLND
Solar/Wind Helper
0.036
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.161
316017AA1-139 ULT1
Solar/Wind Helper
1.093
3146456SLIGO L269
Solar/Wind Helper
0.239
316305AF2-043 C
Solar/Wind Helper
0.321
316246AF1-032 C
Solar/Wind Helper
0.273
316320Y1-086
Solar/Wind Helper
0.107
316321Z2-027
Solar/Wind Helper
0.363
3146516WINFALL
Solar/Wind Helper
0.238
3146626S HERTFORD
Solar/Wind Helper
0.237
3145273HOLLAND
Solar/Wind Helper
0.178
3146376EDENTON
Solar/Wind Helper
0.236
23546401DTGZ2-030
Solar/Wind Helper
0.074
315735AD1-075 GEN1
Solar/Wind Helper
1.344
3146206CASHIE
Solar/Wind Helper
0.234
3145893MURPHYS
Solar/Wind Helper
0.084
3145893MURPHYS
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
3146776BUCKING
Solar/Wind Helper
0.084
966621AG1-532 GEN
Solar/Wind Helper
0.212
3146926FARMVIL
Solar/Wind Helper
0.14
3146263WOODLND
Solar/Wind Helper
0.233
316181AB2-040 GEN
Solar/Wind Helper
1.675
942461AE2-259 GEN
Solar/Wind Helper
1.569
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3145963POPLR C
Solar/Wind Helper
0.233
316011AB1-132 GEN
Solar/Wind Helper
2.509
316190AA2-174 GEN
Solar/Wind Helper
0.016
3147043LAWRENC
Solar/Wind Helper
0.14
316317KELFORD C
Solar/Wind Helper
0.21
3145823KELFORD
Solar/Wind Helper
0.233
3147133PAMPLIN
Solar/Wind Helper
0.729
316478AD1-087 GEN
Solar/Wind Helper
1.138
3145796HORNRTN
Solar/Wind Helper
0.928
3145796HORNRTN
Solar/Wind Helper
0.232
315821AE2-092 GEN
Solar/Wind Helper
2.154
316212AC1-099_GEN
Solar/Wind Helper
1.039
3145933PARMELE
Solar/Wind Helper
0.231
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
316420AA1-050 GEN
Solar/Wind Helper
1.319
3148013FISHERV
Solar/Wind Helper
0.229
23777801MSM_W1-116
Solar/Wind Helper
0.099
3146233WITAKRS
Solar/Wind Helper
0.247
3146233WITAKRS
Solar/Wind Helper
0.156
3146073TAR RVR
Solar/Wind Helper
0.229
3146083TARBORO
Solar/Wind Helper
0.229
316499AE2-029_GEN
Solar/Wind Helper
0.772
3138543CONSLDL
Solar/Wind Helper
0.151
3145543BTLEBRO
Solar/Wind Helper
0.229
3145543BTLEBRO
Solar/Wind Helper
0.229
270494AE1-108_GEN
Solar/Wind Helper
3.067
316003AC1-222 GEN
Solar/Wind Helper
0.984
316095T157 G97
Solar/Wind Helper
1.03
316222AC1-221 GEN
Solar/Wind Helper
1.283
316283AC2-100 C
Solar/Wind Helper
1.195
23583801GRNGAP
Solar/Wind Helper
3.821
3145573BETHELC
Solar/Wind Helper
0.229
3145573BETHELC
Solar/Wind Helper
0.229
3147173SINAI
Solar/Wind Helper
0.227
3147243WELCO
Solar/Wind Helper
0.142
237030AB1-096 C
Solar/Wind Helper
0.058
237025AB1-124 C
Solar/Wind Helper
0.142
315616AA1-038_C
Solar/Wind Helper
1.022
3148463FAIRFLD
Solar/Wind Helper
0.225
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.656
VTFLTFEXP_VFT->PJM
CMTX
154.628
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.362
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.876
BlueGrassPJM->LTFIMP_BlueG
CLTF
15.187
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.841
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
61.282
CBM NorthLTFEXP_CBM-N->PJM
CBM
75.829
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-3835T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-3835T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.68 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:4947.73
MW Contribution:
4.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
3.14
200194DELTA CT3
50/50
3.14
200204Y1-065-CTG1
50/50
6.424
200054ROCKSP 3
50/50
4.089
232901NORTHST
Adder
14.489
233970AC1-092 C
Solar/Wind Harmer
3.14
234033AF1-007_GEN
Solar/Wind Harmer
23.992
232900DEMECSMY
Adder
16.028
972177AH1-672 GEN
Solar/Wind Harmer
17.69
232404W1-003 C
Solar/Wind Harmer
1.121
232408W1-005 C
Solar/Wind Harmer
1.121
232917OH NUG6
Adder
15.27
232915OH NUG4
Adder
15.236
232919VN10
Adder
4.869
232902EASTMUNI
Adder
22.492
234012AE2-112_GEN
Solar/Wind Harmer
3.978
972251AH1-710 GEN
Adder
76.361
233918AB1-142 GEN
Solar/Wind Harmer
0.434
231918WEST 1
Adder
5.542
231917EM10
Adder
3.862
228206SHRMN CT
Adder
24.486
228732V1-021 C
Adder
0.279
970997AG2-616 GEN
Solar/Wind Harmer
10.584
228400MICK 1CT
Adder
17.114
213497CHSTR7-9
Adder
3.881
213497CHSTR7-9
Adder
3.881
213958STHWK5-6
Adder
3.833
213560DLW11-12
Adder
3.815
219222BRL12CT2
Adder
12.509
213611FALLS1-3
Adder
4.905
207522AF2-254 C
Solar/Wind Harmer
1.285
214194N WALES4
Adder
1.176
20635828PARLN1&2
Adder
9.943
20635028RRCT1&2
Adder
15.8
218524CNTRALGAS1 C
Solar/Wind Harmer
1.021
972275AH1-722 GEN
Adder
41.999
207528AF2-192 GEN
Solar/Wind Harmer
0.95
217186ESSEX_G9
Adder
5.198
217121ECCF
Adder
0.572
217083KRNY_132
Adder
12.24
966261AG1-495 GEN
Solar/Wind Harmer
2.216
971519AH1-257 GEN
Solar/Wind Harmer
2.071
20465127PORT CT
Adder
3.798
208909MACR G3
Adder
200.022
209023WIENIPP1
Adder
12.736
209025WIENIPP3
Adder
6.357
963071AG1-156 GEN
Solar/Wind Harmer
8.9
209010PEIP 1
Adder
0.752
212507AE2-042_GEN
Solar/Wind Harmer
0.669
209018SUNBIPCT
Adder
8.01
970757AG2-479 GEN
Solar/Wind Harmer
0.848
20465527S.RDG CT
Adder
2.665
209008PAXT IPP
Adder
1.515
941421AE2-139 GEN
Solar/Wind Harmer
0
20328326MANOR_T86
Adder
0.124
316415AF1-147_GEN2
Solar/Wind Helper
1.087
316447AC1-158 HLD
Solar/Wind Helper
3.788
316044AC1-158 PL1
Solar/Wind Helper
1.721
3147666LOUISA
Solar/Wind Helper
1.209
316192AB2-158 GEN
Solar/Wind Helper
2.035
316337AD2-073 GEN
Solar/Wind Helper
0.457
964211AG1-282 GEN
Solar/Wind Helper
0.402
3141726DUNNSVL
Solar/Wind Helper
1.194
316404AE1-155 C
Solar/Wind Helper
2.549
238175AF1-290_GEN
Solar/Wind Helper
0.16
3142416OLDCHRC
Solar/Wind Helper
0.77
3142416OLDCHRC
Solar/Wind Helper
0.295
3138133OCRAN
Solar/Wind Helper
0.178
3141766HARMONY
Solar/Wind Helper
0.059
315662AE1-191 GEN
Solar/Wind Helper
1.593
316280AD1-041 GEN
Solar/Wind Helper
0.995
315975AC1-164 GENB
Solar/Wind Helper
0.113
3142433PROV 92
Solar/Wind Helper
1.18
3143526WINTERP
Solar/Wind Helper
1.532
3142543TWELFTH
Solar/Wind Helper
0.028
3143226MDLTHAN
Solar/Wind Helper
0.294
316132AB2-190 GEN1
Solar/Wind Helper
1.674
315671AE2-027_GEN
Solar/Wind Helper
2.363
316369SG1_INVT
Solar/Wind Helper
1.409
3145336SMITFLD
Solar/Wind Helper
1.162
315773AC2-141 GEN
Solar/Wind Helper
6.258
316381AD1-082 GEN
Solar/Wind Helper
1.505
316375AC2-012 GEN
Solar/Wind Helper
0.763
316036AC1-147 C
Solar/Wind Helper
0.442
316072AD1-144
Solar/Wind Helper
0.331
3146456SLIGO L269
Solar/Wind Helper
0.289
319010AE1-072 C
Solar/Wind Helper
3.303
238152AF2-075_GEN
Solar/Wind Helper
0.709
3146516WINFALL
Solar/Wind Helper
0.929
3146516WINFALL
Solar/Wind Helper
0.287
315611Z1-036_GEN2
Solar/Wind Helper
1.569
3130156CHOWAN
Solar/Wind Helper
0.285
315816AE2-034 GEN
Solar/Wind Helper
1.297
3145663CRESWEL
Solar/Wind Helper
0.792
315737AD1-076 GEN
Solar/Wind Helper
2.757
316023GEN1_S
Solar/Wind Helper
1.072
3146206CASHIE
Solar/Wind Helper
0.281
3145893MURPHYS
Solar/Wind Helper
1.123
3146776BUCKING
Solar/Wind Helper
0.112
3146173TUNIS
Solar/Wind Helper
0.28
3146926FARMVIL
Solar/Wind Helper
0.168
3156021HOLLOMANSOL
Solar/Wind Helper
2.134
3145683EARLEYS
Solar/Wind Helper
0.279
315607AA1-063A GEN
Solar/Wind Helper
1.597
316087AB2-174 GEN
Solar/Wind Helper
1.954
3146263WOODLND
Solar/Wind Helper
0.279
3145963POPLR C
Solar/Wind Helper
0.278
3145823KELFORD
Solar/Wind Helper
0.278
3145783HORNRTN
Solar/Wind Helper
0.277
3145796HORNRTN
Solar/Wind Helper
0.914
3145796HORNRTN
Solar/Wind Helper
0.277
23777901MDS_W4-102
Solar/Wind Helper
0.174
316034AC1-036 C
Solar/Wind Helper
0.29
315785AD2-033 C
Solar/Wind Helper
3.221
316129AC1-054 GEN
Solar/Wind Helper
1.366
316131AB2-060 GEN
Solar/Wind Helper
1.679
3147983MERCK5
Solar/Wind Helper
0.11
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
316494AC1-189 GEN
Solar/Wind Helper
1.666
3146233WITAKRS
Solar/Wind Helper
1.082
961671AG1-007 GEN
Solar/Wind Helper
0.195
3146083TARBORO
Solar/Wind Helper
0.272
316359AB2-059 GEN
Solar/Wind Helper
2.067
3145543BTLEBRO
Solar/Wind Helper
0.271
3145543BTLEBRO
Solar/Wind Helper
0.217
238108AE1-109 GEN1
Solar/Wind Helper
0.095
238110AE1-109 GEN3
Solar/Wind Helper
0.095
3147123OTTER R
Solar/Wind Helper
0.15
270016AE1-250 BESS
Solar/Wind Helper
0.923
3147312GRETNA
Solar/Wind Helper
0.199
3146802CHATHAM
Solar/Wind Helper
0.187
270018AE2-047 C O1
Solar/Wind Helper
0.867
964991AG1-363 GEN
Solar/Wind Helper
3.56
237001AB1-127_GEN
Solar/Wind Helper
0.387
235063AE1-101 C2
Solar/Wind Helper
1.427
958121AF2-106 GEN
Solar/Wind Helper
1.717
238127S14_GEN_2
Solar/Wind Helper
0.637
200201DELTA2 CT2
50/50
5.619
200034PCHBTM 2
50/50
32.749
200035PCHBTM 3
50/50
32.254
200205Y1-065-CTG2
50/50
6.424
233971AC1-093 C
Solar/Wind Harmer
3.14
232899W1-062
Adder
16.71
232410W1-006 C
Solar/Wind Harmer
1.121
232918OH NUG7
Adder
15.236
232905CHERITON_25
Adder
4.261
232926CRISFLD1
Adder
3.408
231940T-011
Adder
1.295
234041AC1-190 GEN
Solar/Wind Harmer
12.629
232910NRG_G1
Adder
14.889
233984AB2-036 GEN
Solar/Wind Harmer
12.49
234014AF1-036_GEN
Solar/Wind Harmer
3.978
233930AB2-032 GEN
Solar/Wind Harmer
1.631
228251CARLLS#4
Adder
0.928
228201CARL#2CT
Adder
10.115
228200CARL#1CT
Adder
9.62
228307PCLP GT
Adder
17.625
972233AH1-701 GEN
Adder
6.086
213589EDDYSTN4
Adder
113.222
213587EDDYSTN3
Adder
113.209
219304NAMERICA C
Solar/Wind Harmer
0.127
213535CROYDN11
Adder
14.321
213815MOSER1-3
Adder
4.948
213815MOSER1-3
Adder
4.948
20636128O CRK C2
Adder
8.918
20628028LAKEHURS
Adder
1.308
20714828MDF_W3-079
Solar/Wind Harmer
0.134
20635028RRCT1&2
Adder
15.557
20635128RRCT3&4
Adder
15.017
20635128RRCT3&4
Adder
13.099
218418LINDEN_G5
Adder
22.846
218419LINDEN_G6
Adder
22.846
972260AH1-715 GEN1
Adder
18.294
219036LINDEN_G7
Adder
22.171
219035LINDEN_G8
Adder
21.855
972261AH1-715 GEN2
Adder
21.223
972237AH1-703 GEN
Adder
13.326
217086KRNY_131
Adder
12.266
217083KRNY_132
Adder
12.162
20465127PORT CT
Adder
5.04
209010PEIP 1
Adder
4.134
209010PEIP 1
Adder
0.606
961541AF2-445A GEN
Solar/Wind Harmer
2.571
970761AG2-481 GEN
Solar/Wind Harmer
0.858
209130AF1-271A GEN
Solar/Wind Harmer
2.109
20465527S.RDG CT
Adder
2.578
223401AF1-299 GEN
Solar/Wind Helper
0.532
223402AF1-300 C
Solar/Wind Helper
0.532
316411AF1-147_GEN1
Solar/Wind Helper
1.087
316006AB2-029 C
Solar/Wind Helper
0.149
316045AC1-158 PL2
Solar/Wind Helper
5.508
316450AC1-158 RIC
Solar/Wind Helper
0.459
966001AG1-469 GEN
Solar/Wind Helper
0.321
966871AG1-558 GEN
Solar/Wind Helper
0.401
316487AF1-042 GEN
Solar/Wind Helper
0.3
316312AB1-027
Solar/Wind Helper
0.566
315666AE1-190 GEN
Solar/Wind Helper
0.398
316156AD2-030 GEN
Solar/Wind Helper
0.447
315976AC1-164 GENA
Solar/Wind Helper
3.808
316169AC1-164_GENC
Solar/Wind Helper
3.29
3143526WINTERP
Solar/Wind Helper
1.532
3142946ENON
Solar/Wind Helper
0.03
316240AF1-291 C
Solar/Wind Helper
0.394
316033AB2-134 GEN
Solar/Wind Helper
1.012
316294AC1-161 GEN
Solar/Wind Helper
5.319
316185AD1-033 GEN
Solar/Wind Helper
1.364
316313AB2-026
Solar/Wind Helper
0.442
3145506HICKORY
Solar/Wind Helper
1.156
3145506HICKORY
Solar/Wind Helper
0.694
3145506HICKORY
Solar/Wind Helper
0.173
316349AD2-085 GEN
Solar/Wind Helper
1.323
316339AD2-160 GEN
Solar/Wind Helper
1.103
316388AE2-253 GEN
Solar/Wind Helper
1.103
3137176SLIGO L2192
Solar/Wind Helper
1.148
3130086AYDLETT
Solar/Wind Helper
1.154
3146386ELIZ CT
Solar/Wind Helper
0.288
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238148AE2-230_GEN2
Solar/Wind Helper
0.496
238149AF1-291A_GEN
Solar/Wind Helper
0.142
316431W1029_GEN1
Solar/Wind Helper
1.16
316433W1029_GEN2
Solar/Wind Helper
1.16
316435W1029_GEN3
Solar/Wind Helper
1.16
200202DELTA2 ST
50/50
9.516
200195DELTA ST
50/50
4.851
200052ROCKSP 1
50/50
4.042
200053ROCKSP 2
50/50
3.962
232904IR4
Adder
140.471
232920IR10
Adder
5.49
232432Z2-076 GEN
Solar/Wind Harmer
0.023
232912OH NUG1
Adder
15.338
232913OH NUG2
Adder
15.134
971195AH1-057 GEN
Solar/Wind Harmer
1.085
232813VAUGHN
Adder
1.017
231906DC3 NUG
Adder
23.943
231902DC CT7
Adder
19.141
231907DC10
Adder
5.977
233968AD2-076_GEN
Solar/Wind Harmer
3.978
970597AG2-380 GEN
Solar/Wind Harmer
7.124
233915AB1-141 GEN
Solar/Wind Harmer
0.434
231919CHRIST1
Adder
7.29
231920CHRIST2
Adder
7.128
970453AG2-297 GEN
Solar/Wind Harmer
3.773
972141AH1-641 GEN
Solar/Wind Harmer
2.29
230422AE1-104_GEN1
Solar/Wind Harmer
19.857
230425AE1-104_GEN2
Solar/Wind Harmer
19.857
230430AE1-229_GEN
Solar/Wind Harmer
29.099
964001AG1-254 GEN
Solar/Wind Harmer
8.266
213942SCHUYLKILL
Adder
5.013
213942SCHUYLKILL
Adder
3.833
213957STHWK3-4
Adder
3.833
213957STHWK3-4
Adder
3.833
213561DLWR9-10
Adder
4.989
213561DLWR9-10
Adder
3.815
219224BRL12CT4
Adder
12.509
213611FALLS1-3
Adder
4.905
213611FALLS1-3
Adder
4.905
207487AE2-000G4
Solar/Wind Harmer
17.499
207497AE2-000G2
Solar/Wind Harmer
17.499
207500AE2-000G1
Solar/Wind Harmer
17.499
207507AE2-000G3
Solar/Wind Harmer
17.499
963401AG1-189 GEN
Solar/Wind Harmer
1.552
970025AG2-016 GEN
Solar/Wind Harmer
2.528
971189AH1-054 GEN
Solar/Wind Harmer
1.052
971521AH1-258 GEN
Solar/Wind Harmer
2.369
20635928PARLN3&4
Adder
9.943
218526CNTRALGAS2 C
Solar/Wind Harmer
1.024
217167KRNY_14
Adder
12.24
217086KRNY_131
Adder
12.136
217147KRNY_1212
Adder
11.643
217147KRNY_1212
Adder
11.435
217146KRNY_1234
Adder
11.409
217146KRNY_1234
Adder
11.331
971009AG2-626 GEN
Solar/Wind Harmer
1.347
20462827N BANGR8
Adder
0.904
209026WIENIPP4
Adder
6.293
209027LOR2_Q27
Solar/Wind Harmer
0
20486527WR_V4-052
Adder
1.044
208862AG1-362 C
Solar/Wind Harmer
0.524
20390726Y2-042
Adder
2.94
200917MEHOOPANY_G
Solar/Wind Harmer
0.376
20334726NME_Y1-047
Adder
2.53
203926AA2-133 GEN
Adder
2.288
226929AD2-058 GEN
Solar/Wind Helper
0.145
3138216PACIFIC
Solar/Wind Helper
0.054
3141426STAFORD
Solar/Wind Helper
0.07
315651AD1-115 GEN
Solar/Wind Helper
1.039
316164AC1-076 GEN
Solar/Wind Helper
1.471
316468AD1-105 GEN
Solar/Wind Helper
1.451
3141813NORNECK
Solar/Wind Helper
0.299
3141783LANCAST
Solar/Wind Helper
0.178
3141783LANCAST
Solar/Wind Helper
0.118
3138133OCRAN
Solar/Wind Helper
0.089
3141913WHIT STONE
Solar/Wind Helper
0.296
316059AD1-063 C
Solar/Wind Helper
0.299
957601AF2-054 GEN
Solar/Wind Helper
0.396
3141873WAN 176
Solar/Wind Helper
0.059
3143873LANEXA
Solar/Wind Helper
0.177
316233AE1-074 FULL
Solar/Wind Helper
0.45
238169AE2-226 GEN1
Solar/Wind Helper
0.719
238170AE2-226 GEN2
Solar/Wind Helper
0.719
957831AF2-077 GEN
Solar/Wind Helper
0.396
316382AG1-145 C
Solar/Wind Helper
0.395
316159AE1-175 C
Solar/Wind Helper
0.446
315697AD1-025 GEN
Solar/Wind Helper
3.342
315839AE2-212 C
Solar/Wind Helper
0.393
316236AE1-162_GEN
Solar/Wind Helper
0.391
3143316POE
Solar/Wind Helper
1.149
316316AC1-027 C
Solar/Wind Helper
0.458
316258AE1-075 C
Solar/Wind Helper
0.398
316405AF2-144 C
Solar/Wind Helper
0.331
316018AA1-139 ULT2
Solar/Wind Helper
1.245
313526AB2-022
Solar/Wind Helper
0.439
3146486SUNBURY
Solar/Wind Helper
0.288
3146486SUNBURY
Solar/Wind Helper
0.288
3145176PASQUOTANK
Solar/Wind Helper
0.178
315800Z1-036_GEN1
Solar/Wind Helper
1.569
3130156CHOWAN
Solar/Wind Helper
0.285
3130156CHOWAN
Solar/Wind Helper
0.285
3130546PLYMOUTH
Solar/Wind Helper
0.282
315732AD1-074 GEN1
Solar/Wind Helper
3.224
315733AD1-074 GEN2
Solar/Wind Helper
3.224
3146206CASHIE
Solar/Wind Helper
0.281
3145893MURPHYS
Solar/Wind Helper
0.758
3145893MURPHYS
Solar/Wind Helper
0.281
316322AB2-045
Solar/Wind Helper
0.314
316463AE2-346 GEN
Solar/Wind Helper
0.256
3145513AHOSKIE
Solar/Wind Helper
0.125
961941AG1-037 GEN
Solar/Wind Helper
0.094
3145513AHOSKIE
Solar/Wind Helper
0.28
3138266HYDRAULIC
Solar/Wind Helper
0.013
3138266HYDRAULIC
Solar/Wind Helper
0.008
946281AF1-292 GEN
Solar/Wind Helper
0.281
3146043SEABORD
Solar/Wind Helper
0.279
3145683EARLEYS
Solar/Wind Helper
0.558
3145683EARLEYS
Solar/Wind Helper
0.279
3145683EARLEYS
Solar/Wind Helper
0.279
3137643SOCKMAN
Solar/Wind Helper
1.111
316426AA2-053 GEN
Solar/Wind Helper
1.59
316174AB2-169 GEN
Solar/Wind Helper
0.71
316486AD2-202 GEN
Solar/Wind Helper
0.398
3145796HORNRTN
Solar/Wind Helper
0.886
3145796HORNRTN
Solar/Wind Helper
0.111
3146033SCOT NK
Solar/Wind Helper
1.106
3144303KENBRDG
Solar/Wind Helper
0.221
316210AC1-098 GEN
Solar/Wind Helper
2.227
316274AC1-208 GEN
Solar/Wind Helper
1.68
316238AB2-078_GEN
Solar/Wind Helper
0.37
316239AB2-077_GEN
Solar/Wind Helper
0.37
3145746EVERETS
Solar/Wind Helper
1.089
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3148133STUARTS
Solar/Wind Helper
0.164
3148013FISHERV
Solar/Wind Helper
0.157
316327AA2-057 GEN
Solar/Wind Helper
1.561
3145573BETHELC
Solar/Wind Helper
0.272
3145573BETHELC
Solar/Wind Helper
0.272
3147173SINAI
Solar/Wind Helper
0.268
3147243WELCO
Solar/Wind Helper
0.168
315616AA1-038_C
Solar/Wind Helper
1.206
3148463FAIRFLD
Solar/Wind Helper
0.266
270455AD2-022 GEN
Solar/Wind Helper
1.489
270457AD2-023 GEN
Solar/Wind Helper
0.981
23779801AA1-109
Solar/Wind Helper
0.184
270197AD1-017 GEN1
Solar/Wind Helper
1.335
23750701CROSSCHOOL
Solar/Wind Helper
1.106
237030AB1-096 C
Solar/Wind Helper
0.059
237025AB1-124 C
Solar/Wind Helper
0.144
238118U2-030_1
Solar/Wind Helper
0.261
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.287
3146626S HERTFORD
Solar/Wind Helper
0.286
3146626S HERTFORD
Solar/Wind Helper
0.286
3144356SAPONY
Solar/Wind Helper
0.513
316315AB2-025 C
Solar/Wind Helper
0.437
237061AD1-155 GEN
Solar/Wind Helper
1.789
315614AA2-178 GEN
Solar/Wind Helper
1.729
316365GEN2_N
Solar/Wind Helper
1.072
3145893MURPHYS
Solar/Wind Helper
0.403
3145893MURPHYS
Solar/Wind Helper
0.505
3146776BUCKING
Solar/Wind Helper
1.122
3146776BUCKING
Solar/Wind Helper
0.091
3146173TUNIS
Solar/Wind Helper
0.28
3146173TUNIS
Solar/Wind Helper
0.28
316140AB2-099
Solar/Wind Helper
0.107
313506AB2-031 GEN
Solar/Wind Helper
1.268
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.167
3145593CAROLNA
Solar/Wind Helper
0.278
3145593CAROLNA
Solar/Wind Helper
0.278
3147133PAMPLIN
Solar/Wind Helper
0.277
3147133PAMPLIN
Solar/Wind Helper
0.222
3145796HORNRTN
Solar/Wind Helper
0.831
3132123MT JACKSON
Solar/Wind Helper
0.865
235020AA1-095 C
Solar/Wind Helper
0.052
3145933PARMELE
Solar/Wind Helper
0.55
3145933PARMELE
Solar/Wind Helper
0.275
316237AB2-079_GEN
Solar/Wind Helper
0.37
316005AA1-067
Solar/Wind Helper
0.314
315687AD1-152 GEN
Solar/Wind Helper
1.474
3146843MT LREL
Solar/Wind Helper
0.271
3146843MT LREL
Solar/Wind Helper
0.271
316049AB1-081 GEN
Solar/Wind Helper
1.653
316118AC1-105 GEN
Solar/Wind Helper
1.05
316248AF1-058 C
Solar/Wind Helper
0.362
316097T157 G90
Solar/Wind Helper
1.23
238221AF1-254 C O1
Solar/Wind Helper
0.259
237080AD1-060 GEN
Solar/Wind Helper
0.314
270013AE1-250 PV
Solar/Wind Helper
0.923
235062AE1-101 C1
Solar/Wind Helper
1.427
270214AC2-123 GEN
Solar/Wind Helper
0.81
237006AB1-125 GEN
Solar/Wind Helper
0.108
235531U2-073 GEN
Solar/Wind Helper
2.561
235054AD2-180 GEN
Solar/Wind Helper
1.519
238117U2-030
Solar/Wind Helper
0.261
200200DELTA2 CT1
50/50
5.619
200193DELTA CT2
50/50
3.14
200203Y1-065-STG
50/50
11.126
200055ROCKSP 4
50/50
4.018
233973AC2-185 C
Solar/Wind Harmer
3.14
970695AG2-447 GEN
Solar/Wind Harmer
4.351
233939AC1-091 C
Solar/Wind Harmer
3.14
233972AC1-094 C
Solar/Wind Harmer
3.14
233987AB2-037 GEN
Solar/Wind Harmer
-0.002
232434Z2-077 GEN
Solar/Wind Harmer
0.072
232406W1-004 FULL
Solar/Wind Harmer
1.121
232914OH NUG3
Adder
15.338
232916OH NUG5
Adder
15.338
232921TASLEY2G
Adder
8.964
232907VN8
Adder
52.124
232422X3-066 FULL
Solar/Wind Harmer
0.142
233935AB2-179 C
Solar/Wind Harmer
2.284
213497CHSTR7-9
Adder
3.881
213958STHWK5-6
Adder
3.833
213560DLW11-12
Adder
3.815
219221BRL12CT1
Adder
12.509
219223BRL12CT3
Adder
12.509
213815MOSER1-3
Adder
4.948
20636028O CRK C1
Adder
9.781
963391AG1-188 GEN
Solar/Wind Harmer
2.527
971667AH1-334 GEN
Solar/Wind Harmer
2.444
20635828PARLN1&2
Adder
4.503
20635928PARLN3&4
Adder
4.503
207442AE1-156 GEN
Solar/Wind Harmer
0.078
971007AG2-625 GEN
Solar/Wind Harmer
2.113
207437AD2-070 GEN
Solar/Wind Harmer
0.082
20466127PORT 5CT
Adder
33.551
20633028GILCT9
Adder
35.557
20465427SHAW CT
Adder
4.866
209025WIENIPP3
Adder
6.229
970095AG2-074 GEN
Solar/Wind Harmer
5.903
209142AF1-226 GEN
Solar/Wind Harmer
3.152
209093AE2-110 GEN
Solar/Wind Harmer
1.801
209120AE2-241 GEN
Solar/Wind Harmer
1.801
205941AD2-115 GEN
Solar/Wind Harmer
0.12
970767AG2-484 GEN
Solar/Wind Harmer
0.635
972221AH1-695 GEN
Adder
101.413
226910AB2-157 C
Solar/Wind Helper
0.021
227287AC2-120 GEN
Solar/Wind Helper
0.514
3141196NOKESVL
Solar/Wind Helper
1.271
966881AG1-559 GEN
Solar/Wind Helper
0.411
3132273ORANGE
Solar/Wind Helper
0.061
3147666LOUISA
Solar/Wind Helper
0.695
316223AC1-118
Solar/Wind Helper
0.461
3141906WESTMOR
Solar/Wind Helper
0.121
316077AC2-138 C
Solar/Wind Helper
0.282
316473AC1-191 GEN
Solar/Wind Helper
1.819
316484AD2-074 GEN
Solar/Wind Helper
0.574
316075AC2-137 C
Solar/Wind Helper
0.451
3142946ENON
Solar/Wind Helper
0.098
316458AB2-190 GEN2
Solar/Wind Helper
1.674
3145336SMITFLD
Solar/Wind Helper
0.116
3144536CHRHLND
Solar/Wind Helper
0.044
3144873MCLAUGH
Solar/Wind Helper
0.007
3142956BIRDNECK
Solar/Wind Helper
0.195
316017AA1-139 ULT1
Solar/Wind Helper
1.323
3146456SLIGO L269
Solar/Wind Helper
0.289
316305AF2-043 C
Solar/Wind Helper
0.389
316246AF1-032 C
Solar/Wind Helper
0.33
316320Y1-086
Solar/Wind Helper
0.129
316321Z2-027
Solar/Wind Helper
0.439
23546401DTGZ2-030
Solar/Wind Helper
0.09
3146516WINFALL
Solar/Wind Helper
0.287
3146626S HERTFORD
Solar/Wind Helper
0.286
3145273HOLLAND
Solar/Wind Helper
0.215
3146376EDENTON
Solar/Wind Helper
0.285
315735AD1-075 GEN1
Solar/Wind Helper
1.612
3146206CASHIE
Solar/Wind Helper
0.281
3145893MURPHYS
Solar/Wind Helper
0.101
3145893MURPHYS
Solar/Wind Helper
0.281
3146776BUCKING
Solar/Wind Helper
0.101
3146173TUNIS
Solar/Wind Helper
0.28
3146926FARMVIL
Solar/Wind Helper
0.168
966621AG1-532 GEN
Solar/Wind Helper
0.254
3146263WOODLND
Solar/Wind Helper
0.279
316181AB2-040 GEN
Solar/Wind Helper
2.003
942461AE2-259 GEN
Solar/Wind Helper
1.877
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3145963POPLR C
Solar/Wind Helper
0.278
316190AA2-174 GEN
Solar/Wind Helper
0.019
3147043LAWRENC
Solar/Wind Helper
0.167
316011AB1-132 GEN
Solar/Wind Helper
2.997
316317KELFORD C
Solar/Wind Helper
0.25
3145823KELFORD
Solar/Wind Helper
0.278
3147133PAMPLIN
Solar/Wind Helper
0.871
315821AE2-092 GEN
Solar/Wind Helper
2.577
316478AD1-087 GEN
Solar/Wind Helper
1.358
3145796HORNRTN
Solar/Wind Helper
1.107
3145796HORNRTN
Solar/Wind Helper
0.277
316212AC1-099_GEN
Solar/Wind Helper
1.237
3145933PARMELE
Solar/Wind Helper
0.275
316499AE2-029_GEN
Solar/Wind Helper
0.922
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3148013FISHERV
Solar/Wind Helper
0.274
316420AA1-050 GEN
Solar/Wind Helper
1.565
3146233WITAKRS
Solar/Wind Helper
0.292
3146233WITAKRS
Solar/Wind Helper
0.185
3146073TAR RVR
Solar/Wind Helper
0.272
3146083TARBORO
Solar/Wind Helper
0.272
3138543CONSLDL
Solar/Wind Helper
0.179
270494AE1-108_GEN
Solar/Wind Helper
3.637
3145543BTLEBRO
Solar/Wind Helper
0.271
3145543BTLEBRO
Solar/Wind Helper
0.271
316095T157 G97
Solar/Wind Helper
1.23
316003AC1-222 GEN
Solar/Wind Helper
1.159
23583801GRNGAP
Solar/Wind Helper
4.529
316222AC1-221 GEN
Solar/Wind Helper
1.501
316283AC2-100 C
Solar/Wind Helper
1.398
316123AC1-075 GEN
Solar/Wind Helper
1.587
238109AE1-109 GEN2
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.235
3147312GRETNA
Solar/Wind Helper
0.05
23777801MSM_W1-116
Solar/Wind Helper
0.107
237038AE2-054 C
Solar/Wind Helper
0.244
235067AD1-061 GEN
Solar/Wind Helper
0.397
270173AC1-122 GEN
Solar/Wind Helper
1.673
943811AF1-049 GEN
Solar/Wind Helper
1.491
237002AB1-128_GEN
Solar/Wind Helper
0.39
237085AD2-009_GEN
Solar/Wind Helper
1.441
270336AE1-100 GEN
Solar/Wind Helper
1.038
238120AE2-309 GEN
Solar/Wind Helper
0.408
238126S14_GEN_1
Solar/Wind Helper
0.637
238185AF2-356 C
Solar/Wind Helper
1.926
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.521
VTFLTFEXP_VFT->PJM
CMTX
178.78
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.228
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.831
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
24.651
BlueGrassPJM->LTFIMP_BlueG
CLTF
16.29
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
68.711
CBM NorthLTFEXP_CBM-N->PJM
CBM
95.196
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.7 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:4876.15
MW Contribution:
6.65
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
3.784
200194DELTA CT3
50/50
3.784
200204Y1-065-CTG1
50/50
7.611
200054ROCKSP 3
50/50
4.844
231912HR6
50/50
2.689
231913HR7
50/50
2.689
233920W3-032A-CTG1
50/50
3.977
232901NORTHST
50/50
16.404
232917OH NUG6
50/50
17.289
232915OH NUG4
50/50
17.251
232900DEMECSMY
50/50
18.135
233970AC1-092 C
Solar/Wind Harmer
4.977
234033AF1-007_GEN
Solar/Wind Harmer
68.948
232404W1-003 C
Solar/Wind Harmer
1.852
232408W1-005 C
Solar/Wind Harmer
1.852
233996TM1833_GEN
Solar/Wind Harmer
1.847
233998TM1NIN_3.36
Solar/Wind Harmer
1.847
972177AH1-672 GEN
Solar/Wind Harmer
24.89
232919VN10
Adder
5.194
232426Y1-080 FULL
Solar/Wind Harmer
0.353
232902EASTMUNI
Adder
23.97
234012AE2-112_GEN
Solar/Wind Harmer
4.184
233944AB2-135 GEN
Solar/Wind Harmer
9.48
233918AB1-142 GEN
Solar/Wind Harmer
1.788
972251AH1-710 GEN
Adder
79.924
231918WEST 1
Adder
5.736
231917EM10
Adder
3.965
228206SHRMN CT
Adder
24.208
228732V1-021 C
Adder
0.275
228260V4-054C
Solar/Wind Harmer
1.487
970997AG2-616 GEN
Solar/Wind Harmer
13.813
228729W2-030 C
Solar/Wind Harmer
0.825
228400MICK 1CT
Adder
16.591
219686LUMSOLAR_N C
Solar/Wind Harmer
0.276
219766PARADISE C
Solar/Wind Harmer
0.428
213497CHSTR7-9
Adder
3.683
213497CHSTR7-9
Adder
3.683
219907AC1-030 C
Solar/Wind Harmer
0.186
213958STHWK5-6
Adder
3.599
213560DLW11-12
Adder
3.573
219348LDSOLAR C
Solar/Wind Harmer
0.787
219222BRL12CT2
Adder
11.738
20716028EGP_W2-019
Solar/Wind Harmer
0.597
207522AF2-254 C
Solar/Wind Harmer
1.846
213611FALLS1-3
Adder
4.544
20717128DIX_Z2-102
Solar/Wind Harmer
1.696
20715828PEM_W1-120
Solar/Wind Harmer
0.685
214194N WALES4
Adder
1.078
963711AG1-223 GEN
Solar/Wind Harmer
1.842
20714528FRN_Y2-051
Solar/Wind Harmer
0.367
219276PARKLANDSO C
Solar/Wind Harmer
0.569
20715228NPK_W1-113
Solar/Wind Harmer
0.524
20720528MAN_W1-024
Solar/Wind Harmer
0.309
219680HOPEWELLV C1
Solar/Wind Harmer
0.092
20720428HOL_W1-112
Solar/Wind Harmer
0.417
20635828PARLN1&2
Adder
8.735
20635028RRCT1&2
Adder
13.824
218524CNTRALGAS1 C
Solar/Wind Harmer
0.429
218440SUMMTASSOC C
Solar/Wind Harmer
0.148
218428ETC SOLAR C
Solar/Wind Harmer
0.041
219908AB1-139 C
Solar/Wind Harmer
0.439
219919AE1-041 FULL
Solar/Wind Harmer
0.047
972275AH1-722 GEN
Adder
36.179
20673628F1S_V4-069
Solar/Wind Harmer
0.203
207528AF2-192 GEN
Solar/Wind Harmer
1.435
217209CENTRL HS C
Solar/Wind Harmer
0.05
217186ESSEX_G9
Adder
4.391
217121ECCF
Adder
0.483
217083KRNY_132
Adder
10.338
217208PARK ELE C
Solar/Wind Harmer
0.028
20671828STAW2-080
Solar/Wind Harmer
0.116
20676728BRNX1-095
Solar/Wind Harmer
0.19
966261AG1-495 GEN
Solar/Wind Harmer
3.703
207439AE1-081 C O1
Solar/Wind Harmer
0.062
20676328BVR_Y1-020
Solar/Wind Harmer
0.345
20674628WNG_W3-110
Solar/Wind Harmer
0.419
20676228FRD_X1-012
Solar/Wind Harmer
0.613
207530AG1-191 GEN
Solar/Wind Harmer
1.422
20675828AU_W4-064
Solar/Wind Harmer
0.178
20674928WA_W3-044
Solar/Wind Harmer
0.485
971519AH1-257 GEN
Solar/Wind Harmer
2.51
20675728RH_W2-091
Solar/Wind Harmer
0.595
207518AF1-320_GEN
Solar/Wind Harmer
3.599
207484AF2-139 C O1
Solar/Wind Harmer
0.495
20465127PORT CT
Adder
2.937
208909MACR G3
Adder
151.771
211065PSPA IPP
Solar/Wind Harmer
0.407
963071AG1-156 GEN
Solar/Wind Harmer
8.156
209010PEIP 1
Adder
0.535
961301AF2-421 GEN
Solar/Wind Harmer
0.819
963151AG1-164 GEN
Solar/Wind Harmer
0.819
209023WIENIPP1
Adder
8.833
209025WIENIPP3
Adder
4.409
961341AF2-425 GEN
Solar/Wind Harmer
0.719
212507AE2-042_GEN
Solar/Wind Harmer
2.023
946731AF1-337 GEN
Solar/Wind Harmer
0.66
209018SUNBIPCT
Adder
4.879
316415AF1-147_GEN2
Solar/Wind Helper
0.827
316447AC1-158 HLD
Solar/Wind Helper
2.942
316044AC1-158 PL1
Solar/Wind Helper
1.337
3147666LOUISA
Solar/Wind Helper
0.947
316192AB2-158 GEN
Solar/Wind Helper
1.594
316337AD2-073 GEN
Solar/Wind Helper
0.36
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.942
316404AE1-155 C
Solar/Wind Helper
2.013
3142416OLDCHRC
Solar/Wind Helper
0.609
3142416OLDCHRC
Solar/Wind Helper
0.233
3138133OCRAN
Solar/Wind Helper
0.14
200202DELTA2 ST
50/50
11.469
200195DELTA ST
50/50
5.846
200052ROCKSP 1
50/50
4.788
200053ROCKSP 2
50/50
4.695
232616GEN FOOD
50/50
0.321
232904IR4
50/50
159.039
232920IR10
50/50
6.216
232912OH NUG1
50/50
17.366
232913OH NUG2
50/50
17.135
232432Z2-076 GEN
Solar/Wind Harmer
0.245
233901CHERRYDALE C
Solar/Wind Harmer
2.084
233940AF2-379 C
Solar/Wind Harmer
0.345
971195AH1-057 GEN
Solar/Wind Harmer
1.806
233955AB2-172 GEN
Solar/Wind Harmer
9.235
232813VAUGHN
Adder
1.083
233968AD2-076_GEN
Solar/Wind Harmer
12.06
970597AG2-380 GEN
Solar/Wind Harmer
7.573
231906DC3 NUG
Adder
25.408
231902DC CT7
Adder
20.312
231907DC10
Adder
6.343
233915AB1-141 GEN
Solar/Wind Harmer
1.788
231919CHRIST1
Adder
7.534
231920CHRIST2
Adder
7.366
970453AG2-297 GEN
Solar/Wind Harmer
4.055
230422AE1-104_GEN1
Solar/Wind Harmer
48.602
230425AE1-104_GEN2
Solar/Wind Harmer
48.602
972141AH1-641 GEN
Solar/Wind Harmer
4.144
230430AE1-229_GEN
Solar/Wind Harmer
41.196
964001AG1-254 GEN
Solar/Wind Harmer
10.469
228728W1-130C
Solar/Wind Harmer
0.95
227927V4-067C
Solar/Wind Harmer
0.283
230407AD2-065 C
Solar/Wind Harmer
0.187
230434AG1-499 GEN
Solar/Wind Harmer
0.823
219137THOSOLAR C
Solar/Wind Harmer
1.669
219258KINSLEYDEP C
Solar/Wind Harmer
0.443
213942SCHUYLKILL
Adder
4.707
213942SCHUYLKILL
Adder
3.6
213957STHWK3-4
Adder
3.599
213957STHWK3-4
Adder
3.599
219615MILLCREEK C
Solar/Wind Harmer
0.316
213561DLWR9-10
Adder
4.673
213561DLWR9-10
Adder
3.573
219610FLORENCE C
Solar/Wind Harmer
1.821
219224BRL12CT4
Adder
11.738
20720728JCB_W1-129
Solar/Wind Harmer
0.384
20715028HAN_X4-015
Solar/Wind Harmer
0.384
213611FALLS1-3
Adder
4.544
213611FALLS1-3
Adder
4.544
207487AE2-000G4
Solar/Wind Harmer
40.407
207497AE2-000G2
Solar/Wind Harmer
40.407
207500AE2-000G1
Solar/Wind Harmer
40.407
207507AE2-000G3
Solar/Wind Harmer
40.407
963401AG1-189 GEN
Solar/Wind Harmer
2.905
970025AG2-016 GEN
Solar/Wind Harmer
3.613
971189AH1-054 GEN
Solar/Wind Harmer
1.501
207445AB1-138_GEN
Solar/Wind Harmer
0.731
219620RIDERU C
Solar/Wind Harmer
0.068
20714428HOW_X1-037
Solar/Wind Harmer
1.513
20720628TIN_W1-124
Solar/Wind Harmer
1.215
20716228APLW2-078
Solar/Wind Harmer
1.076
971521AH1-258 GEN
Solar/Wind Harmer
3.273
20635928PARLN3&4
Adder
8.735
218526CNTRALGAS2 C
Solar/Wind Harmer
0.431
20675528CPH_W2-050
Solar/Wind Harmer
0.659
20673828FLE_V3-070
Solar/Wind Harmer
0.531
218449LINSOLAR C
Solar/Wind Harmer
1.141
20676128MHD_W3-029
Solar/Wind Harmer
0.539
20676428JCR_X2-075
Solar/Wind Harmer
0.384
217167KRNY_14
Adder
10.338
217086KRNY_131
Adder
10.25
217147KRNY_1212
Adder
9.833
217147KRNY_1212
Adder
9.658
217146KRNY_1234
Adder
9.636
217146KRNY_1234
Adder
9.57
964851AG1-348 GEN
Solar/Wind Harmer
1.366
971009AG2-626 GEN
Solar/Wind Harmer
1.636
207408W3-077 C
Solar/Wind Harmer
0.499
20675128HRM_W1-127
Solar/Wind Harmer
0.165
20462827N BANGR8
Adder
0.695
961261AF2-417 GEN
Solar/Wind Harmer
0.872
209029WAYMART-WD
Solar/Wind Harmer
2.149
209026WIENIPP4
Adder
4.365
209027LOR2_Q27
Solar/Wind Harmer
3.378
212266LOR1
Solar/Wind Harmer
0.895
209054AE2-059 GEN
Solar/Wind Harmer
1.141
959431AF2-234 GEN
Solar/Wind Harmer
1.31
964051AG1-259 GEN
Solar/Wind Harmer
0.878
964061AG1-260 GEN
Solar/Wind Harmer
0.878
959421AF2-233 GEN
Solar/Wind Harmer
0.655
226929AD2-058 GEN
Solar/Wind Helper
0.116
3141426STAFORD
Solar/Wind Helper
0.054
3138216PACIFIC
Solar/Wind Helper
0.041
316164AC1-076 GEN
Solar/Wind Helper
1.145
315651AD1-115 GEN
Solar/Wind Helper
0.807
316468AD1-105 GEN
Solar/Wind Helper
1.142
3141813NORNECK
Solar/Wind Helper
0.236
3141783LANCAST
Solar/Wind Helper
0.141
3141783LANCAST
Solar/Wind Helper
0.094
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.234
316059AD1-063 C
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.314
3141873WAN 176
Solar/Wind Helper
0.047
3143873LANEXA
Solar/Wind Helper
0.14
316233AE1-074 FULL
Solar/Wind Helper
0.356
957831AF2-077 GEN
Solar/Wind Helper
0.314
316382AG1-145 C
Solar/Wind Helper
0.313
316159AE1-175 C
Solar/Wind Helper
0.353
315697AD1-025 GEN
Solar/Wind Helper
2.655
315839AE2-212 C
Solar/Wind Helper
0.312
316236AE1-162_GEN
Solar/Wind Helper
0.311
3143316POE
Solar/Wind Helper
0.914
316316AC1-027 C
Solar/Wind Helper
0.364
316258AE1-075 C
Solar/Wind Helper
0.316
316405AF2-144 C
Solar/Wind Helper
0.264
316018AA1-139 ULT2
Solar/Wind Helper
0.992
238169AE2-226 GEN1
Solar/Wind Helper
0.562
238170AE2-226 GEN2
Solar/Wind Helper
0.562
313526AB2-022
Solar/Wind Helper
0.351
3146486SUNBURY
Solar/Wind Helper
0.229
3146486SUNBURY
Solar/Wind Helper
0.229
3145176PASQUOTANK
Solar/Wind Helper
0.142
315800Z1-036_GEN1
Solar/Wind Helper
1.255
3130156CHOWAN
Solar/Wind Helper
0.228
3130156CHOWAN
Solar/Wind Helper
0.228
3130546PLYMOUTH
Solar/Wind Helper
0.226
315732AD1-074 GEN1
Solar/Wind Helper
2.59
315733AD1-074 GEN2
Solar/Wind Helper
2.59
3146206CASHIE
Solar/Wind Helper
0.226
3145893MURPHYS
Solar/Wind Helper
0.609
3145893MURPHYS
Solar/Wind Helper
0.226
316322AB2-045
Solar/Wind Helper
0.252
316463AE2-346 GEN
Solar/Wind Helper
0.206
3145513AHOSKIE
Solar/Wind Helper
0.101
961941AG1-037 GEN
Solar/Wind Helper
0.076
3145513AHOSKIE
Solar/Wind Helper
0.225
946281AF1-292 GEN
Solar/Wind Helper
0.226
3146043SEABORD
Solar/Wind Helper
0.225
3145683EARLEYS
Solar/Wind Helper
0.45
3145683EARLEYS
Solar/Wind Helper
0.225
3145683EARLEYS
Solar/Wind Helper
0.225
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.006
3137643SOCKMAN
Solar/Wind Helper
0.896
316426AA2-053 GEN
Solar/Wind Helper
1.283
316174AB2-169 GEN
Solar/Wind Helper
0.574
316486AD2-202 GEN
Solar/Wind Helper
0.321
3145796HORNRTN
Solar/Wind Helper
0.716
3145796HORNRTN
Solar/Wind Helper
0.089
3146033SCOT NK
Solar/Wind Helper
0.894
3144303KENBRDG
Solar/Wind Helper
0.178
200201DELTA2 CT2
50/50
6.772
200034PCHBTM 2
50/50
39.455
200035PCHBTM 3
50/50
39.25
200205Y1-065-CTG2
50/50
7.611
232918OH NUG7
50/50
17.251
232905CHERITON_25
50/50
4.824
232926CRISFLD1
50/50
3.859
232899W1-062
50/50
18.906
231940T-011
50/50
1.466
232910NRG_G1
50/50
16.819
233971AC1-093 C
Solar/Wind Harmer
4.726
232410W1-006 C
Solar/Wind Harmer
1.852
234015AF2-250 C
Solar/Wind Harmer
0.223
232428Y3-058 C
Solar/Wind Harmer
1.543
233994AC2-023 GEN
Solar/Wind Harmer
4.971
233946AB2-136 GEN
Solar/Wind Harmer
7.373
234036AF2-325 C
Solar/Wind Harmer
1.694
234041AC1-190 GEN
Solar/Wind Harmer
16.548
233952AC2-187 GEN
Solar/Wind Harmer
2.078
233954AC2-188 GEN
Solar/Wind Harmer
2.078
3141766HARMONY
Solar/Wind Helper
0.047
315662AE1-191 GEN
Solar/Wind Helper
1.261
316280AD1-041 GEN
Solar/Wind Helper
0.788
3142433PROV 92
Solar/Wind Helper
0.934
315975AC1-164 GENB
Solar/Wind Helper
0.089
3143526WINTERP
Solar/Wind Helper
1.213
3142543TWELFTH
Solar/Wind Helper
0.022
3143226MDLTHAN
Solar/Wind Helper
0.233
316132AB2-190 GEN1
Solar/Wind Helper
1.329
315671AE2-027_GEN
Solar/Wind Helper
1.876
316369SG1_INVT
Solar/Wind Helper
1.119
3145336SMITFLD
Solar/Wind Helper
0.924
315773AC2-141 GEN
Solar/Wind Helper
4.98
238175AF1-290_GEN
Solar/Wind Helper
0.124
316381AD1-082 GEN
Solar/Wind Helper
1.198
316375AC2-012 GEN
Solar/Wind Helper
0.607
316036AC1-147 C
Solar/Wind Helper
0.352
316072AD1-144
Solar/Wind Helper
0.264
3146456SLIGO L269
Solar/Wind Helper
0.23
319010AE1-072 C
Solar/Wind Helper
2.633
3146516WINFALL
Solar/Wind Helper
0.742
3146516WINFALL
Solar/Wind Helper
0.229
315611Z1-036_GEN2
Solar/Wind Helper
1.255
3130156CHOWAN
Solar/Wind Helper
0.228
315816AE2-034 GEN
Solar/Wind Helper
1.04
3145663CRESWEL
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.559
315737AD1-076 GEN
Solar/Wind Helper
2.215
316023GEN1_S
Solar/Wind Helper
0.862
3146206CASHIE
Solar/Wind Helper
0.226
3145893MURPHYS
Solar/Wind Helper
0.903
3146173TUNIS
Solar/Wind Helper
0.225
3146776BUCKING
Solar/Wind Helper
0.09
3156021HOLLOMANSOL
Solar/Wind Helper
1.719
3146926FARMVIL
Solar/Wind Helper
0.135
3145683EARLEYS
Solar/Wind Helper
0.225
315607AA1-063A GEN
Solar/Wind Helper
1.287
316087AB2-174 GEN
Solar/Wind Helper
1.575
3146263WOODLND
Solar/Wind Helper
0.225
3145963POPLR C
Solar/Wind Helper
0.224
3145823KELFORD
Solar/Wind Helper
0.224
3145783HORNRTN
Solar/Wind Helper
0.224
3145796HORNRTN
Solar/Wind Helper
0.738
3145796HORNRTN
Solar/Wind Helper
0.224
316034AC1-036 C
Solar/Wind Helper
0.234
315785AD2-033 C
Solar/Wind Helper
2.605
23777901MDS_W4-102
Solar/Wind Helper
0.14
316129AC1-054 GEN
Solar/Wind Helper
1.106
233984AB2-036 GEN
Solar/Wind Harmer
22.782
232424Y1-079 C
Solar/Wind Harmer
1.027
234014AF1-036_GEN
Solar/Wind Harmer
4.923
232436AB1-176 C
Solar/Wind Harmer
0.416
233930AB2-032 GEN
Solar/Wind Harmer
1.505
233982AB2-133 GEN
Solar/Wind Harmer
8.791
228251CARLLS#4
Adder
0.914
228201CARL#2CT
Adder
9.961
228200CARL#1CT
Adder
9.473
230433AD2-135 GEN
Solar/Wind Harmer
0.145
228351V2-046C
Solar/Wind Harmer
2.892
230511AF1-262
Solar/Wind Harmer
0.262
228754AB1-001 C
Solar/Wind Harmer
0.199
228307PCLP GT
Adder
17.187
972233AH1-701 GEN
Adder
5.906
219272CLEANLIGHT C
Solar/Wind Harmer
0.25
219287REEVESEAST C
Solar/Wind Harmer
1.833
219904AC1-010 C
Solar/Wind Harmer
0.514
219912AD2-042 GEN
Solar/Wind Harmer
1.075
213589EDDYSTN4
Adder
107.242
213587EDDYSTN3
Adder
107.22
219906AC1-017 C
Solar/Wind Harmer
0.295
219607WPEMNERT C
Solar/Wind Harmer
0.551
219304NAMERICA C
Solar/Wind Harmer
0.408
213535CROYDN11
Adder
13.421
213815MOSER1-3
Adder
4.592
213815MOSER1-3
Adder
4.592
20720828JCB_W4-025
Solar/Wind Harmer
0.583
214067T20SOLAR
Solar/Wind Harmer
0.325
20636128O CRK C2
Adder
8.267
207459AE1-142 C O1
Solar/Wind Harmer
1.335
20628028LAKEHURS
Adder
1.2
20714828MDF_W3-079
Solar/Wind Harmer
0.38
219817TRENTONSOL C
Solar/Wind Harmer
1.35
20641628MLH_W1-032
Solar/Wind Harmer
0.358
20742028HF_AC1-207
Solar/Wind Harmer
0.951
217197RE CRAN C
Solar/Wind Harmer
0.641
218438BLK ROCK C
Solar/Wind Harmer
0.163
924131AB2-057 GEN
Solar/Wind Harmer
1.209
20635028RRCT1&2
Adder
13.611
20635128RRCT3&4
Adder
13.138
20635128RRCT3&4
Adder
11.461
218418LINDEN_G5
Adder
19.68
218419LINDEN_G6
Adder
19.68
972260AH1-715 GEN1
Adder
15.759
219036LINDEN_G7
Adder
18.97
219035LINDEN_G8
Adder
18.699
972261AH1-715 GEN2
Adder
18.159
20675428EAM_W2-061
Solar/Wind Harmer
0.213
217081WEATEXAS C
Solar/Wind Harmer
0.097
217202FBANKSOLAR C
Solar/Wind Harmer
0.082
217201HACKENSOLA C
Solar/Wind Harmer
0.082
972237AH1-703 GEN
Adder
11.259
217206BARNGR HS C
Solar/Wind Harmer
0.034
217086KRNY_131
Adder
10.36
217083KRNY_132
Adder
10.272
217204WCALDSOLAR C
Solar/Wind Harmer
0.081
20674328GAR_V4-001
Solar/Wind Harmer
0.113
20674828DL_W4-046
Solar/Wind Harmer
0.652
207471AF2-354 C
Solar/Wind Harmer
0.515
20634528N27_Y2-018
Solar/Wind Harmer
0.269
20675928HOL_W4-097
Solar/Wind Harmer
0.128
20465127PORT CT
Adder
3.898
209010PEIP 1
Adder
2.942
209010PEIP 1
Adder
0.431
961541AF2-445A GEN
Solar/Wind Harmer
2.427
961431AF2-434 GEN
Solar/Wind Harmer
0.717
946751AF1-339 GEN
Solar/Wind Harmer
0.66
209130AF1-271A GEN
Solar/Wind Harmer
1.841
223401AF1-299 GEN
Solar/Wind Helper
0.473
223402AF1-300 C
Solar/Wind Helper
0.473
316411AF1-147_GEN1
Solar/Wind Helper
0.827
316006AB2-029 C
Solar/Wind Helper
0.115
316045AC1-158 PL2
Solar/Wind Helper
4.279
316450AC1-158 RIC
Solar/Wind Helper
0.357
966001AG1-469 GEN
Solar/Wind Helper
0.252
966871AG1-558 GEN
Solar/Wind Helper
0.317
316487AF1-042 GEN
Solar/Wind Helper
0.237
316312AB1-027
Solar/Wind Helper
0.447
315666AE1-190 GEN
Solar/Wind Helper
0.315
316156AD2-030 GEN
Solar/Wind Helper
0.354
315976AC1-164 GENA
Solar/Wind Helper
3.015
316169AC1-164_GENC
Solar/Wind Helper
2.604
3142946ENON
Solar/Wind Helper
0.023
3143526WINTERP
Solar/Wind Helper
1.213
316240AF1-291 C
Solar/Wind Helper
0.313
316033AB2-134 GEN
Solar/Wind Helper
0.803
316294AC1-161 GEN
Solar/Wind Helper
4.232
316185AD1-033 GEN
Solar/Wind Helper
1.087
3145506HICKORY
Solar/Wind Helper
0.921
3145506HICKORY
Solar/Wind Helper
0.553
3145506HICKORY
Solar/Wind Helper
0.138
316210AC1-098 GEN
Solar/Wind Helper
1.802
316274AC1-208 GEN
Solar/Wind Helper
1.36
316349AD2-085 GEN
Solar/Wind Helper
1.055
316313AB2-026
Solar/Wind Helper
0.351
316339AD2-160 GEN
Solar/Wind Helper
0.879
316388AE2-253 GEN
Solar/Wind Helper
0.879
3137176SLIGO L2192
Solar/Wind Helper
0.915
3130086AYDLETT
Solar/Wind Helper
0.92
3146386ELIZ CT
Solar/Wind Helper
0.23
316431W1029_GEN1
Solar/Wind Helper
0.926
316433W1029_GEN2
Solar/Wind Helper
0.926
316435W1029_GEN3
Solar/Wind Helper
0.926
3146516WINFALL
Solar/Wind Helper
0.229
3146516WINFALL
Solar/Wind Helper
0.229
3146516WINFALL
Solar/Wind Helper
0.229
3146626S HERTFORD
Solar/Wind Helper
0.229
3146626S HERTFORD
Solar/Wind Helper
0.229
3144356SAPONY
Solar/Wind Helper
0.41
316315AB2-025 C
Solar/Wind Helper
0.349
315614AA2-178 GEN
Solar/Wind Helper
1.387
238147AE2-230_GEN1
Solar/Wind Helper
0.391
238148AE2-230_GEN2
Solar/Wind Helper
0.391
238149AF1-291A_GEN
Solar/Wind Helper
0.112
237061AD1-155 GEN
Solar/Wind Helper
1.416
316365GEN2_N
Solar/Wind Helper
0.862
3145893MURPHYS
Solar/Wind Helper
0.324
3145893MURPHYS
Solar/Wind Helper
0.406
3146173TUNIS
Solar/Wind Helper
0.225
3146173TUNIS
Solar/Wind Helper
0.225
3146776BUCKING
Solar/Wind Helper
0.901
3146776BUCKING
Solar/Wind Helper
0.073
316140AB2-099
Solar/Wind Helper
0.086
313506AB2-031 GEN
Solar/Wind Helper
1.022
3142666NORTHAMPTON
Solar/Wind Helper
0.224
3142666NORTHAMPTON
Solar/Wind Helper
0.224
3142666NORTHAMPTON
Solar/Wind Helper
0.224
3142666NORTHAMPTON
Solar/Wind Helper
0.135
3145593CAROLNA
Solar/Wind Helper
0.224
3145593CAROLNA
Solar/Wind Helper
0.224
3147133PAMPLIN
Solar/Wind Helper
0.224
3147133PAMPLIN
Solar/Wind Helper
0.179
3145796HORNRTN
Solar/Wind Helper
0.671
3145933PARMELE
Solar/Wind Helper
0.445
3145933PARMELE
Solar/Wind Helper
0.223
200200DELTA2 CT1
50/50
6.772
200193DELTA CT2
50/50
3.784
200203Y1-065-STG
50/50
13.181
200055ROCKSP 4
50/50
4.76
231914HR8
50/50
4.087
231911HR5
50/50
2.689
233921W3-032A-STG1
50/50
2.57
232914OH NUG3
50/50
17.366
232916OH NUG5
50/50
17.366
232921TASLEY2G
50/50
10.15
234034AF2-060
50/50
3.473
233900O-025 C
50/50
0.127
232911NRG_G2
50/50
0.92
233973AC2-185 C
Solar/Wind Harmer
10.055
970695AG2-447 GEN
Solar/Wind Harmer
6.652
233939AC1-091 C
Solar/Wind Harmer
4.977
233972AC1-094 C
Solar/Wind Harmer
3.997
233987AB2-037 GEN
Solar/Wind Harmer
21.095
232434Z2-077 GEN
Solar/Wind Harmer
0.463
232406W1-004 FULL
Solar/Wind Harmer
1.852
233923SMA
Solar/Wind Harmer
6.771
233997TMININ_4.2
Solar/Wind Harmer
1.847
232907VN8
Adder
55.622
233964AF2-378 GEN
Solar/Wind Harmer
0.236
232417X3-008 C
Solar/Wind Harmer
2.078
233950AC2-186 GEN
Solar/Wind Harmer
1.039
232422X3-066 FULL
Solar/Wind Harmer
0.454
233933AB2-153 GEN
Solar/Wind Harmer
2.032
233935AB2-179 C
Solar/Wind Harmer
4.378
228711V2-041C
Solar/Wind Harmer
0.878
230415AB2-049 C
Solar/Wind Harmer
0.271
219623KINSLEYBEA C
Solar/Wind Harmer
0.587
219291REEVESSOUT C
Solar/Wind Harmer
0.082
218660EHAMPSOLAR C
Solar/Wind Harmer
0.239
219921AF1-264
Solar/Wind Harmer
0.197
219688LUMSOLAR_S C
Solar/Wind Harmer
0.275
213497CHSTR7-9
Adder
3.683
219914AD2-027 C
Solar/Wind Harmer
0.81
219236SOUTHERNHQ C
Solar/Wind Harmer
0.09
213958STHWK5-6
Adder
3.599
213560DLW11-12
Adder
3.573
219221BRL12CT1
Adder
11.738
219223BRL12CT3
Adder
11.738
213815MOSER1-3
Adder
4.592
20716428NHV_W2-082
Solar/Wind Harmer
2.288
20715728PEM_W1-119
Solar/Wind Harmer
0.685
959561AF2-247 GEN
Solar/Wind Harmer
0.623
20636028O CRK C1
Adder
9.066
963391AG1-188 GEN
Solar/Wind Harmer
4.777
20714928UPF_X1-085
Solar/Wind Harmer
0.515
971667AH1-334 GEN
Solar/Wind Harmer
3.476
219114HARTZY_C
Solar/Wind Harmer
1.048
219727YARDVSOLFA C
Solar/Wind Harmer
1.137
207454AA2-184 E
Solar/Wind Harmer
1.219
219918AC2-009 C
Solar/Wind Harmer
0.031
219612MATRIX C
Solar/Wind Harmer
0.22
20716928W4-060COL
Solar/Wind Harmer
0.849
20635828PARLN1&2
Adder
3.957
20635928PARLN3&4
Adder
3.957
217213AMBOY SO C
Solar/Wind Harmer
0.146
219249CENTRALDIV C
Solar/Wind Harmer
0.046
207442AE1-156 GEN
Solar/Wind Harmer
0.839
20673728F2S_V4-070
Solar/Wind Harmer
0.203
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217169METRODIV C
Solar/Wind Harmer
0.044
217194REDH C
Solar/Wind Harmer
0.547
20674528F3S_W2-016
Solar/Wind Harmer
1.531
207510AF2-138 C
Solar/Wind Harmer
1.848
207511W3-106 GEN
Solar/Wind Harmer
0.343
971007AG2-625 GEN
Solar/Wind Harmer
2.565
207437AD2-070 GEN
Solar/Wind Harmer
0.294
20466127PORT 5CT
Adder
25.97
20671928W4-073
Solar/Wind Harmer
0.42
20674128FR_U2-059
Solar/Wind Harmer
0.179
20465427SHAW CT
Adder
3.745
20633028GILCT9
Adder
27.292
209116AE2-175 GEN
Solar/Wind Harmer
3.818
211065PSPA IPP
Solar/Wind Harmer
0.407
970095AG2-074 GEN
Solar/Wind Harmer
5.165
963161AG1-165 GEN
Solar/Wind Harmer
0.819
209025WIENIPP3
Adder
4.32
208972BECR K09
Solar/Wind Harmer
0.853
961331AF2-424 GEN
Solar/Wind Harmer
0.719
961421AF2-433 GEN
Solar/Wind Harmer
0.717
957921AF2-086 GEN
Solar/Wind Harmer
0.697
209142AF1-226 GEN
Solar/Wind Harmer
4.148
209093AE2-110 GEN
Solar/Wind Harmer
1.791
209120AE2-241 GEN
Solar/Wind Harmer
2.37
946691AF1-333 GEN
Solar/Wind Harmer
0.66
946741AF1-338 GEN
Solar/Wind Harmer
0.66
209071AE2-133 GEN
Solar/Wind Harmer
1.108
205941AD2-115 GEN
Solar/Wind Harmer
0.572
226910AB2-157 C
Solar/Wind Helper
0.017
227287AC2-120 GEN
Solar/Wind Helper
0.412
3141196NOKESVL
Solar/Wind Helper
0.975
966881AG1-559 GEN
Solar/Wind Helper
0.323
316223AC1-118
Solar/Wind Helper
0.363
3141906WESTMOR
Solar/Wind Helper
0.095
3132273ORANGE
Solar/Wind Helper
0.047
3147666LOUISA
Solar/Wind Helper
0.545
316077AC2-138 C
Solar/Wind Helper
0.222
316473AC1-191 GEN
Solar/Wind Helper
1.437
316484AD2-074 GEN
Solar/Wind Helper
0.454
316075AC2-137 C
Solar/Wind Helper
0.357
3142946ENON
Solar/Wind Helper
0.078
316458AB2-190 GEN2
Solar/Wind Helper
1.329
3145336SMITFLD
Solar/Wind Helper
0.092
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.155
316017AA1-139 ULT1
Solar/Wind Helper
1.054
3146456SLIGO L269
Solar/Wind Helper
0.23
316305AF2-043 C
Solar/Wind Helper
0.31
316246AF1-032 C
Solar/Wind Helper
0.263
316320Y1-086
Solar/Wind Helper
0.103
316321Z2-027
Solar/Wind Helper
0.35
3146516WINFALL
Solar/Wind Helper
0.229
3146626S HERTFORD
Solar/Wind Helper
0.229
3145273HOLLAND
Solar/Wind Helper
0.172
3146376EDENTON
Solar/Wind Helper
0.228
23546401DTGZ2-030
Solar/Wind Helper
0.071
315735AD1-075 GEN1
Solar/Wind Helper
1.296
3146206CASHIE
Solar/Wind Helper
0.226
3145893MURPHYS
Solar/Wind Helper
0.081
3145893MURPHYS
Solar/Wind Helper
0.226
3146173TUNIS
Solar/Wind Helper
0.225
3146776BUCKING
Solar/Wind Helper
0.081
966621AG1-532 GEN
Solar/Wind Helper
0.205
3146926FARMVIL
Solar/Wind Helper
0.135
3146263WOODLND
Solar/Wind Helper
0.225
316181AB2-040 GEN
Solar/Wind Helper
1.615
942461AE2-259 GEN
Solar/Wind Helper
1.512
3142666NORTHAMPTON
Solar/Wind Helper
0.224
3145963POPLR C
Solar/Wind Helper
0.224
316011AB1-132 GEN
Solar/Wind Helper
2.418
316190AA2-174 GEN
Solar/Wind Helper
0.015
316317KELFORD C
Solar/Wind Helper
0.202
3145823KELFORD
Solar/Wind Helper
0.224
3147043LAWRENC
Solar/Wind Helper
0.134
3147133PAMPLIN
Solar/Wind Helper
0.703
316478AD1-087 GEN
Solar/Wind Helper
1.097
3145796HORNRTN
Solar/Wind Helper
0.895
3145796HORNRTN
Solar/Wind Helper
0.224
315821AE2-092 GEN
Solar/Wind Helper
2.076
316212AC1-099_GEN
Solar/Wind Helper
1.001
3145933PARMELE
Solar/Wind Helper
0.223
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.447
VTFLTFEXP_VFT->PJM
CMTX
151.705
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.236
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.686
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.598
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.958
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
60.116
CBM NorthLTFEXP_CBM-N->PJM
CBM
74.656
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.49 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:4579.06
MW Contribution:
4.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
3.68
200194DELTA CT3
50/50
3.68
200204Y1-065-CTG1
50/50
7.433
200054ROCKSP 3
50/50
4.731
232901NORTHST
Adder
15.552
233970AC1-092 C
Solar/Wind Harmer
3.368
234033AF1-007_GEN
Solar/Wind Harmer
25.781
232404W1-003 C
Solar/Wind Harmer
1.205
232408W1-005 C
Solar/Wind Harmer
1.205
232917OH NUG6
Adder
16.414
232915OH NUG4
Adder
16.378
972177AH1-672 GEN
Solar/Wind Harmer
19.003
232919VN10
Adder
5.235
232900DEMECSMY
Adder
17.2
232902EASTMUNI
Adder
24.192
234012AE2-112_GEN
Solar/Wind Harmer
4.276
233918AB1-142 GEN
Solar/Wind Harmer
0.466
972251AH1-710 GEN
Adder
80.305
231918WEST 1
Adder
5.882
231917EM10
Adder
4.081
228206SHRMN CT
Adder
24.638
228732V1-021 C
Adder
0.28
970997AG2-616 GEN
Solar/Wind Harmer
10.615
228400MICK 1CT
Adder
17.049
213497CHSTR7-9
Adder
3.913
213497CHSTR7-9
Adder
3.913
213958STHWK5-6
Adder
3.799
213560DLW11-12
Adder
3.738
219222BRL12CT2
Adder
12.079
213611FALLS1-3
Adder
4.679
207522AF2-254 C
Solar/Wind Harmer
1.218
214194N WALES4
Adder
1.114
20635828PARLN1&2
Adder
8.909
20635028RRCT1&2
Adder
14.099
218524CNTRALGAS1 C
Solar/Wind Harmer
0.905
972275AH1-722 GEN
Adder
36.909
207528AF2-192 GEN
Solar/Wind Harmer
0.828
217186ESSEX_G9
Adder
4.478
217121ECCF
Adder
0.493
217083KRNY_132
Adder
10.543
966261AG1-495 GEN
Solar/Wind Harmer
1.849
971519AH1-257 GEN
Solar/Wind Harmer
1.654
20465127PORT CT
Adder
2.994
208909MACR G3
Adder
154.656
963071AG1-156 GEN
Solar/Wind Harmer
6.349
209010PEIP 1
Adder
0.544
209023WIENIPP1
Adder
8.983
209025WIENIPP3
Adder
4.484
212507AE2-042_GEN
Solar/Wind Harmer
0.421
209018SUNBIPCT
Adder
4.951
970757AG2-479 GEN
Solar/Wind Harmer
0.524
316415AF1-147_GEN2
Solar/Wind Helper
0.857
316447AC1-158 HLD
Solar/Wind Helper
3.051
316044AC1-158 PL1
Solar/Wind Helper
1.386
3147666LOUISA
Solar/Wind Helper
0.982
316192AB2-158 GEN
Solar/Wind Helper
1.654
316337AD2-073 GEN
Solar/Wind Helper
0.373
964211AG1-282 GEN
Solar/Wind Helper
0.329
3141726DUNNSVL
Solar/Wind Helper
0.977
316404AE1-155 C
Solar/Wind Helper
2.088
3142416OLDCHRC
Solar/Wind Helper
0.632
3142416OLDCHRC
Solar/Wind Helper
0.242
3138133OCRAN
Solar/Wind Helper
0.146
3141766HARMONY
Solar/Wind Helper
0.048
315662AE1-191 GEN
Solar/Wind Helper
1.308
316280AD1-041 GEN
Solar/Wind Helper
0.817
3142433PROV 92
Solar/Wind Helper
0.969
315975AC1-164 GENB
Solar/Wind Helper
0.093
3143526WINTERP
Solar/Wind Helper
1.258
3142543TWELFTH
Solar/Wind Helper
0.023
3143226MDLTHAN
Solar/Wind Helper
0.242
316132AB2-190 GEN1
Solar/Wind Helper
1.379
315671AE2-027_GEN
Solar/Wind Helper
1.946
316369SG1_INVT
Solar/Wind Helper
1.161
3145336SMITFLD
Solar/Wind Helper
0.959
315773AC2-141 GEN
Solar/Wind Helper
5.166
238175AF1-290_GEN
Solar/Wind Helper
0.129
316381AD1-082 GEN
Solar/Wind Helper
1.243
316375AC2-012 GEN
Solar/Wind Helper
0.63
316036AC1-147 C
Solar/Wind Helper
0.365
316072AD1-144
Solar/Wind Helper
0.274
3146456SLIGO L269
Solar/Wind Helper
0.239
319010AE1-072 C
Solar/Wind Helper
2.732
3146516WINFALL
Solar/Wind Helper
0.77
3146516WINFALL
Solar/Wind Helper
0.238
315611Z1-036_GEN2
Solar/Wind Helper
1.302
3130156CHOWAN
Solar/Wind Helper
0.236
315816AE2-034 GEN
Solar/Wind Helper
1.079
3145663CRESWEL
Solar/Wind Helper
0.659
238152AF2-075_GEN
Solar/Wind Helper
0.58
315737AD1-076 GEN
Solar/Wind Helper
2.299
316023GEN1_S
Solar/Wind Helper
0.895
3146206CASHIE
Solar/Wind Helper
0.234
3145893MURPHYS
Solar/Wind Helper
0.937
3146173TUNIS
Solar/Wind Helper
0.234
3146776BUCKING
Solar/Wind Helper
0.094
3156021HOLLOMANSOL
Solar/Wind Helper
1.783
3146926FARMVIL
Solar/Wind Helper
0.14
3145683EARLEYS
Solar/Wind Helper
0.233
315607AA1-063A GEN
Solar/Wind Helper
1.335
316087AB2-174 GEN
Solar/Wind Helper
1.635
3146263WOODLND
Solar/Wind Helper
0.233
3145963POPLR C
Solar/Wind Helper
0.233
3145823KELFORD
Solar/Wind Helper
0.233
3145783HORNRTN
Solar/Wind Helper
0.232
3145796HORNRTN
Solar/Wind Helper
0.766
3145796HORNRTN
Solar/Wind Helper
0.232
316034AC1-036 C
Solar/Wind Helper
0.243
315785AD2-033 C
Solar/Wind Helper
2.703
23777901MDS_W4-102
Solar/Wind Helper
0.146
316129AC1-054 GEN
Solar/Wind Helper
1.148
316131AB2-060 GEN
Solar/Wind Helper
1.411
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
316494AC1-189 GEN
Solar/Wind Helper
1.404
3147983MERCK5
Solar/Wind Helper
0.092
3146233WITAKRS
Solar/Wind Helper
0.913
961671AG1-007 GEN
Solar/Wind Helper
0.165
3146083TARBORO
Solar/Wind Helper
0.229
316359AB2-059 GEN
Solar/Wind Helper
1.747
3145543BTLEBRO
Solar/Wind Helper
0.229
3145543BTLEBRO
Solar/Wind Helper
0.183
200202DELTA2 ST
50/50
11.153
200195DELTA ST
50/50
5.685
200052ROCKSP 1
50/50
4.677
200053ROCKSP 2
50/50
4.585
232904IR4
Adder
150.945
232920IR10
Adder
5.899
232432Z2-076 GEN
Solar/Wind Harmer
0.024
232912OH NUG1
Adder
16.488
232913OH NUG2
Adder
16.268
971195AH1-057 GEN
Solar/Wind Harmer
1.166
232813VAUGHN
Adder
1.092
233968AD2-076_GEN
Solar/Wind Harmer
4.276
970597AG2-380 GEN
Solar/Wind Harmer
7.658
231906DC3 NUG
Adder
25.711
231902DC CT7
Adder
20.555
231907DC10
Adder
6.419
233915AB1-141 GEN
Solar/Wind Harmer
0.466
231919CHRIST1
Adder
7.729
231920CHRIST2
Adder
7.557
970453AG2-297 GEN
Solar/Wind Harmer
3.805
972141AH1-641 GEN
Solar/Wind Harmer
2.297
230430AE1-229_GEN
Solar/Wind Harmer
29.168
964001AG1-254 GEN
Solar/Wind Harmer
8.287
230422AE1-104_GEN1
Solar/Wind Harmer
19.857
230425AE1-104_GEN2
Solar/Wind Harmer
19.857
213942SCHUYLKILL
Adder
4.974
213942SCHUYLKILL
Adder
3.803
213957STHWK3-4
Adder
3.799
213957STHWK3-4
Adder
3.799
213561DLWR9-10
Adder
4.888
213561DLWR9-10
Adder
3.738
219224BRL12CT4
Adder
12.079
213611FALLS1-3
Adder
4.679
213611FALLS1-3
Adder
4.679
207487AE2-000G4
Solar/Wind Harmer
16.538
207497AE2-000G2
Solar/Wind Harmer
16.538
207500AE2-000G1
Solar/Wind Harmer
16.538
207507AE2-000G3
Solar/Wind Harmer
16.538
963401AG1-189 GEN
Solar/Wind Harmer
1.464
970025AG2-016 GEN
Solar/Wind Harmer
2.381
971189AH1-054 GEN
Solar/Wind Harmer
0.99
971521AH1-258 GEN
Solar/Wind Harmer
2.157
20635928PARLN3&4
Adder
8.909
218526CNTRALGAS2 C
Solar/Wind Harmer
0.909
217167KRNY_14
Adder
10.543
217086KRNY_131
Adder
10.453
217147KRNY_1212
Adder
10.028
217147KRNY_1212
Adder
9.849
217146KRNY_1234
Adder
9.827
217146KRNY_1234
Adder
9.76
971009AG2-626 GEN
Solar/Wind Harmer
1.078
20462827N BANGR8
Adder
0.708
209026WIENIPP4
Adder
4.439
209027LOR2_Q27
Solar/Wind Harmer
0
226929AD2-058 GEN
Solar/Wind Helper
0.12
3141426STAFORD
Solar/Wind Helper
0.056
3138216PACIFIC
Solar/Wind Helper
0.042
316164AC1-076 GEN
Solar/Wind Helper
1.187
315651AD1-115 GEN
Solar/Wind Helper
0.837
316468AD1-105 GEN
Solar/Wind Helper
1.184
3141813NORNECK
Solar/Wind Helper
0.245
3141783LANCAST
Solar/Wind Helper
0.146
3141783LANCAST
Solar/Wind Helper
0.097
3138133OCRAN
Solar/Wind Helper
0.073
3141913WHIT STONE
Solar/Wind Helper
0.243
316059AD1-063 C
Solar/Wind Helper
0.245
957601AF2-054 GEN
Solar/Wind Helper
0.325
3141873WAN 176
Solar/Wind Helper
0.048
3143873LANEXA
Solar/Wind Helper
0.145
316233AE1-074 FULL
Solar/Wind Helper
0.37
957831AF2-077 GEN
Solar/Wind Helper
0.326
316382AG1-145 C
Solar/Wind Helper
0.325
316159AE1-175 C
Solar/Wind Helper
0.367
315697AD1-025 GEN
Solar/Wind Helper
2.754
315839AE2-212 C
Solar/Wind Helper
0.324
316236AE1-162_GEN
Solar/Wind Helper
0.323
3143316POE
Solar/Wind Helper
0.949
316316AC1-027 C
Solar/Wind Helper
0.378
316258AE1-075 C
Solar/Wind Helper
0.328
316405AF2-144 C
Solar/Wind Helper
0.273
316018AA1-139 ULT2
Solar/Wind Helper
1.029
238169AE2-226 GEN1
Solar/Wind Helper
0.583
238170AE2-226 GEN2
Solar/Wind Helper
0.583
313526AB2-022
Solar/Wind Helper
0.364
3146486SUNBURY
Solar/Wind Helper
0.238
3146486SUNBURY
Solar/Wind Helper
0.238
3145176PASQUOTANK
Solar/Wind Helper
0.148
315800Z1-036_GEN1
Solar/Wind Helper
1.302
3130156CHOWAN
Solar/Wind Helper
0.236
3130156CHOWAN
Solar/Wind Helper
0.236
3130546PLYMOUTH
Solar/Wind Helper
0.235
315732AD1-074 GEN1
Solar/Wind Helper
2.688
315733AD1-074 GEN2
Solar/Wind Helper
2.688
3146206CASHIE
Solar/Wind Helper
0.234
3145893MURPHYS
Solar/Wind Helper
0.632
3145893MURPHYS
Solar/Wind Helper
0.234
316322AB2-045
Solar/Wind Helper
0.262
316463AE2-346 GEN
Solar/Wind Helper
0.214
3145513AHOSKIE
Solar/Wind Helper
0.105
961941AG1-037 GEN
Solar/Wind Helper
0.079
3145513AHOSKIE
Solar/Wind Helper
0.234
946281AF1-292 GEN
Solar/Wind Helper
0.235
3146043SEABORD
Solar/Wind Helper
0.234
3145683EARLEYS
Solar/Wind Helper
0.467
3145683EARLEYS
Solar/Wind Helper
0.233
3145683EARLEYS
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.007
3137643SOCKMAN
Solar/Wind Helper
0.93
316426AA2-053 GEN
Solar/Wind Helper
1.331
316174AB2-169 GEN
Solar/Wind Helper
0.595
316486AD2-202 GEN
Solar/Wind Helper
0.333
3145796HORNRTN
Solar/Wind Helper
0.743
3145796HORNRTN
Solar/Wind Helper
0.093
3146033SCOT NK
Solar/Wind Helper
0.928
3144303KENBRDG
Solar/Wind Helper
0.185
316210AC1-098 GEN
Solar/Wind Helper
1.871
316274AC1-208 GEN
Solar/Wind Helper
1.412
23779801AA1-109
Solar/Wind Helper
0.167
316238AB2-078_GEN
Solar/Wind Helper
0.311
316239AB2-077_GEN
Solar/Wind Helper
0.311
3145746EVERETS
Solar/Wind Helper
0.917
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
316327AA2-057 GEN
Solar/Wind Helper
1.316
3148133STUARTS
Solar/Wind Helper
0.138
3148013FISHERV
Solar/Wind Helper
0.132
3145573BETHELC
Solar/Wind Helper
0.229
3145573BETHELC
Solar/Wind Helper
0.229
3147173SINAI
Solar/Wind Helper
0.227
3147243WELCO
Solar/Wind Helper
0.142
237030AB1-096 C
Solar/Wind Helper
0.058
237025AB1-124 C
Solar/Wind Helper
0.142
315616AA1-038_C
Solar/Wind Helper
1.022
3148463FAIRFLD
Solar/Wind Helper
0.225
200201DELTA2 CT2
50/50
6.586
200034PCHBTM 2
50/50
38.371
200035PCHBTM 3
50/50
38.112
200205Y1-065-CTG2
50/50
7.433
233971AC1-093 C
Solar/Wind Harmer
3.368
232410W1-006 C
Solar/Wind Harmer
1.205
232918OH NUG7
Adder
16.378
232905CHERITON_25
Adder
4.58
232926CRISFLD1
Adder
3.664
231940T-011
Adder
1.392
232899W1-062
Adder
17.932
234041AC1-190 GEN
Solar/Wind Harmer
13.58
232910NRG_G1
Adder
15.987
233984AB2-036 GEN
Solar/Wind Harmer
13.432
234014AF1-036_GEN
Solar/Wind Harmer
4.276
233930AB2-032 GEN
Solar/Wind Harmer
1.752
228251CARLLS#4
Adder
0.932
228201CARL#2CT
Adder
10.159
228200CARL#1CT
Adder
9.662
228307PCLP GT
Adder
17.623
972233AH1-701 GEN
Adder
6.066
213589EDDYSTN4
Adder
114.049
213587EDDYSTN3
Adder
114.017
219304NAMERICA C
Solar/Wind Harmer
0.123
213535CROYDN11
Adder
13.823
213815MOSER1-3
Adder
4.777
213815MOSER1-3
Adder
4.777
20636128O CRK C2
Adder
8.428
20628028LAKEHURS
Adder
1.224
20714828MDF_W3-079
Solar/Wind Harmer
0.125
20635028RRCT1&2
Adder
13.882
20635128RRCT3&4
Adder
13.4
20635128RRCT3&4
Adder
11.689
218418LINDEN_G5
Adder
20.077
218419LINDEN_G6
Adder
20.077
972260AH1-715 GEN1
Adder
16.077
219036LINDEN_G7
Adder
19.35
219035LINDEN_G8
Adder
19.074
972261AH1-715 GEN2
Adder
18.523
972237AH1-703 GEN
Adder
11.483
217086KRNY_131
Adder
10.565
217083KRNY_132
Adder
10.476
20465127PORT CT
Adder
3.973
209010PEIP 1
Adder
2.991
209010PEIP 1
Adder
0.438
961541AF2-445A GEN
Solar/Wind Harmer
1.709
970761AG2-481 GEN
Solar/Wind Harmer
0.54
209130AF1-271A GEN
Solar/Wind Harmer
1.304
223401AF1-299 GEN
Solar/Wind Helper
0.484
223402AF1-300 C
Solar/Wind Helper
0.484
316411AF1-147_GEN1
Solar/Wind Helper
0.857
316006AB2-029 C
Solar/Wind Helper
0.12
316045AC1-158 PL2
Solar/Wind Helper
4.436
316450AC1-158 RIC
Solar/Wind Helper
0.37
966001AG1-469 GEN
Solar/Wind Helper
0.262
966871AG1-558 GEN
Solar/Wind Helper
0.329
316487AF1-042 GEN
Solar/Wind Helper
0.246
316312AB1-027
Solar/Wind Helper
0.464
316156AD2-030 GEN
Solar/Wind Helper
0.367
315666AE1-190 GEN
Solar/Wind Helper
0.327
315976AC1-164 GENA
Solar/Wind Helper
3.127
316169AC1-164_GENC
Solar/Wind Helper
2.701
3142946ENON
Solar/Wind Helper
0.024
3143526WINTERP
Solar/Wind Helper
1.258
316240AF1-291 C
Solar/Wind Helper
0.325
316033AB2-134 GEN
Solar/Wind Helper
0.833
316294AC1-161 GEN
Solar/Wind Helper
4.39
316185AD1-033 GEN
Solar/Wind Helper
1.127
3145506HICKORY
Solar/Wind Helper
0.955
3145506HICKORY
Solar/Wind Helper
0.573
3145506HICKORY
Solar/Wind Helper
0.143
316349AD2-085 GEN
Solar/Wind Helper
1.094
316313AB2-026
Solar/Wind Helper
0.365
316339AD2-160 GEN
Solar/Wind Helper
0.912
316388AE2-253 GEN
Solar/Wind Helper
0.912
3137176SLIGO L2192
Solar/Wind Helper
0.95
3130086AYDLETT
Solar/Wind Helper
0.954
3146386ELIZ CT
Solar/Wind Helper
0.238
316431W1029_GEN1
Solar/Wind Helper
0.961
316433W1029_GEN2
Solar/Wind Helper
0.961
316435W1029_GEN3
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
3146626S HERTFORD
Solar/Wind Helper
0.237
3146626S HERTFORD
Solar/Wind Helper
0.237
3144356SAPONY
Solar/Wind Helper
0.425
316315AB2-025 C
Solar/Wind Helper
0.362
315614AA2-178 GEN
Solar/Wind Helper
1.439
238147AE2-230_GEN1
Solar/Wind Helper
0.406
238148AE2-230_GEN2
Solar/Wind Helper
0.406
238149AF1-291A_GEN
Solar/Wind Helper
0.116
237061AD1-155 GEN
Solar/Wind Helper
1.469
316365GEN2_N
Solar/Wind Helper
0.895
3145893MURPHYS
Solar/Wind Helper
0.336
3145893MURPHYS
Solar/Wind Helper
0.422
3146173TUNIS
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
3146776BUCKING
Solar/Wind Helper
0.935
3146776BUCKING
Solar/Wind Helper
0.076
316140AB2-099
Solar/Wind Helper
0.089
313506AB2-031 GEN
Solar/Wind Helper
1.061
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.14
3145593CAROLNA
Solar/Wind Helper
0.233
3145593CAROLNA
Solar/Wind Helper
0.233
3147133PAMPLIN
Solar/Wind Helper
0.232
3147133PAMPLIN
Solar/Wind Helper
0.186
3145796HORNRTN
Solar/Wind Helper
0.696
3145933PARMELE
Solar/Wind Helper
0.462
3145933PARMELE
Solar/Wind Helper
0.231
316237AB2-079_GEN
Solar/Wind Helper
0.311
3132123MT JACKSON
Solar/Wind Helper
0.721
316005AA1-067
Solar/Wind Helper
0.264
235020AA1-095 C
Solar/Wind Helper
0.043
315687AD1-152 GEN
Solar/Wind Helper
1.241
3146843MT LREL
Solar/Wind Helper
0.229
3146843MT LREL
Solar/Wind Helper
0.229
316049AB1-081 GEN
Solar/Wind Helper
1.397
316118AC1-105 GEN
Solar/Wind Helper
0.888
316248AF1-058 C
Solar/Wind Helper
0.306
237006AB1-125 GEN
Solar/Wind Helper
0.106
238221AF1-254 C O1
Solar/Wind Helper
0.222
316097T157 G90
Solar/Wind Helper
1.031
200200DELTA2 CT1
50/50
6.586
200193DELTA CT2
50/50
3.68
200203Y1-065-STG
50/50
12.873
200055ROCKSP 4
50/50
4.649
233987AB2-037 GEN
Solar/Wind Harmer
-0.003
233973AC2-185 C
Solar/Wind Harmer
3.368
970695AG2-447 GEN
Solar/Wind Harmer
4.668
233939AC1-091 C
Solar/Wind Harmer
3.368
233972AC1-094 C
Solar/Wind Harmer
3.368
232434Z2-077 GEN
Solar/Wind Harmer
0.078
232406W1-004 FULL
Solar/Wind Harmer
1.205
232914OH NUG3
Adder
16.488
232916OH NUG5
Adder
16.488
232921TASLEY2G
Adder
9.636
232907VN8
Adder
56.053
232422X3-066 FULL
Solar/Wind Harmer
0.153
233935AB2-179 C
Solar/Wind Harmer
2.45
213497CHSTR7-9
Adder
3.913
213958STHWK5-6
Adder
3.799
213560DLW11-12
Adder
3.738
219221BRL12CT1
Adder
12.079
219223BRL12CT3
Adder
12.079
213815MOSER1-3
Adder
4.777
20636028O CRK C1
Adder
9.244
963391AG1-188 GEN
Solar/Wind Harmer
2.379
971667AH1-334 GEN
Solar/Wind Harmer
2.291
20635828PARLN1&2
Adder
4.035
20635928PARLN3&4
Adder
4.035
207442AE1-156 GEN
Solar/Wind Harmer
0.068
971007AG2-625 GEN
Solar/Wind Harmer
1.69
207437AD2-070 GEN
Solar/Wind Harmer
0.065
20466127PORT 5CT
Adder
26.468
20465427SHAW CT
Adder
3.816
20633028GILCT9
Adder
27.838
970095AG2-074 GEN
Solar/Wind Harmer
4.211
209025WIENIPP3
Adder
4.394
209142AF1-226 GEN
Solar/Wind Harmer
2.058
209093AE2-110 GEN
Solar/Wind Harmer
1.176
209120AE2-241 GEN
Solar/Wind Harmer
1.176
205941AD2-115 GEN
Solar/Wind Harmer
0.073
226910AB2-157 C
Solar/Wind Helper
0.018
227287AC2-120 GEN
Solar/Wind Helper
0.426
3141196NOKESVL
Solar/Wind Helper
1.011
966881AG1-559 GEN
Solar/Wind Helper
0.334
316223AC1-118
Solar/Wind Helper
0.376
3141906WESTMOR
Solar/Wind Helper
0.099
3132273ORANGE
Solar/Wind Helper
0.049
3147666LOUISA
Solar/Wind Helper
0.565
316077AC2-138 C
Solar/Wind Helper
0.231
316473AC1-191 GEN
Solar/Wind Helper
1.49
316484AD2-074 GEN
Solar/Wind Helper
0.471
316075AC2-137 C
Solar/Wind Helper
0.37
3142946ENON
Solar/Wind Helper
0.081
316458AB2-190 GEN2
Solar/Wind Helper
1.379
3145336SMITFLD
Solar/Wind Helper
0.096
3144536CHRHLND
Solar/Wind Helper
0.036
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.161
316017AA1-139 ULT1
Solar/Wind Helper
1.094
3146456SLIGO L269
Solar/Wind Helper
0.239
316305AF2-043 C
Solar/Wind Helper
0.322
316246AF1-032 C
Solar/Wind Helper
0.273
316320Y1-086
Solar/Wind Helper
0.107
316321Z2-027
Solar/Wind Helper
0.363
3146516WINFALL
Solar/Wind Helper
0.238
3146626S HERTFORD
Solar/Wind Helper
0.237
3145273HOLLAND
Solar/Wind Helper
0.178
3146376EDENTON
Solar/Wind Helper
0.236
23546401DTGZ2-030
Solar/Wind Helper
0.074
315735AD1-075 GEN1
Solar/Wind Helper
1.344
3146206CASHIE
Solar/Wind Helper
0.234
3145893MURPHYS
Solar/Wind Helper
0.084
3145893MURPHYS
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
3146776BUCKING
Solar/Wind Helper
0.084
966621AG1-532 GEN
Solar/Wind Helper
0.212
3146926FARMVIL
Solar/Wind Helper
0.14
3146263WOODLND
Solar/Wind Helper
0.233
316181AB2-040 GEN
Solar/Wind Helper
1.676
942461AE2-259 GEN
Solar/Wind Helper
1.569
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3145963POPLR C
Solar/Wind Helper
0.233
316011AB1-132 GEN
Solar/Wind Helper
2.51
316190AA2-174 GEN
Solar/Wind Helper
0.016
316317KELFORD C
Solar/Wind Helper
0.21
3145823KELFORD
Solar/Wind Helper
0.233
3147043LAWRENC
Solar/Wind Helper
0.14
3147133PAMPLIN
Solar/Wind Helper
0.729
316478AD1-087 GEN
Solar/Wind Helper
1.138
3145796HORNRTN
Solar/Wind Helper
0.929
3145796HORNRTN
Solar/Wind Helper
0.232
315821AE2-092 GEN
Solar/Wind Helper
2.155
316212AC1-099_GEN
Solar/Wind Helper
1.039
3145933PARMELE
Solar/Wind Helper
0.231
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
316420AA1-050 GEN
Solar/Wind Helper
1.32
3148013FISHERV
Solar/Wind Helper
0.23
23777801MSM_W1-116
Solar/Wind Helper
0.099
3146233WITAKRS
Solar/Wind Helper
0.247
3146233WITAKRS
Solar/Wind Helper
0.156
316499AE2-029_GEN
Solar/Wind Helper
0.773
3146073TAR RVR
Solar/Wind Helper
0.229
3146083TARBORO
Solar/Wind Helper
0.229
3138543CONSLDL
Solar/Wind Helper
0.151
3145543BTLEBRO
Solar/Wind Helper
0.229
3145543BTLEBRO
Solar/Wind Helper
0.229
270494AE1-108_GEN
Solar/Wind Helper
3.068
316003AC1-222 GEN
Solar/Wind Helper
0.985
316095T157 G97
Solar/Wind Helper
1.031
316222AC1-221 GEN
Solar/Wind Helper
1.283
316283AC2-100 C
Solar/Wind Helper
1.196
23583801GRNGAP
Solar/Wind Helper
3.822
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.659
VTFLTFEXP_VFT->PJM
CMTX
154.716
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.363
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.877
BlueGrassPJM->LTFIMP_BlueG
CLTF
15.193
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.85
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
61.314
CBM NorthLTFEXP_CBM-N->PJM
CBM
75.878
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_M_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.54 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:4218.81
MW Contribution:
3.96
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200200DELTA2 CT1
50/50
3.757
200193DELTA CT2
50/50
2.099
200203Y1-065-STG
50/50
7.384
200055ROCKSP 4
50/50
2.667
233973AC2-185 C
Solar/Wind Harmer
5.984
970695AG2-447 GEN
Solar/Wind Harmer
3.958
233939AC1-091 C
Solar/Wind Harmer
2.962
233972AC1-094 C
Solar/Wind Harmer
2.378
232434Z2-077 GEN
Solar/Wind Harmer
0.275
232406W1-004 FULL
Solar/Wind Harmer
1.1
232914OH NUG3
Adder
9.718
232916OH NUG5
Adder
9.718
232921TASLEY2G
Adder
5.68
233987AB2-037 GEN
Solar/Wind Harmer
12.509
233923SMA
Solar/Wind Harmer
4.02
233997TMININ_4.2
Solar/Wind Harmer
1.096
232907VN8
Adder
33.013
233950AC2-186 GEN
Solar/Wind Harmer
0.617
233964AF2-378 GEN
Solar/Wind Harmer
0.14
232417X3-008 C
Solar/Wind Harmer
1.233
232422X3-066 FULL
Solar/Wind Harmer
0.269
233933AB2-153 GEN
Solar/Wind Harmer
1.203
233935AB2-179 C
Solar/Wind Harmer
2.584
228711V2-041C
Solar/Wind Harmer
0.553
230415AB2-049 C
Solar/Wind Harmer
0.172
219623KINSLEYBEA C
Solar/Wind Harmer
0.377
219291REEVESSOUT C
Solar/Wind Harmer
0.053
218660EHAMPSOLAR C
Solar/Wind Harmer
0.154
219921AF1-264
Solar/Wind Harmer
0.127
219688LUMSOLAR_S C
Solar/Wind Harmer
0.178
219914AD2-027 C
Solar/Wind Harmer
0.524
213497CHSTR7-9
Adder
2.365
219236SOUTHERNHQ C
Solar/Wind Harmer
0.059
213958STHWK5-6
Adder
2.334
219221BRL12CT1
Adder
7.676
219223BRL12CT3
Adder
7.676
213560DLW11-12
Adder
2.328
213815MOSER1-3
Adder
3.015
20716428NHV_W2-082
Solar/Wind Harmer
1.512
20715728PEM_W1-119
Solar/Wind Harmer
0.454
20636028O CRK C1
Adder
6.006
959561AF2-247 GEN
Solar/Wind Harmer
0.412
963391AG1-188 GEN
Solar/Wind Harmer
3.175
20714928UPF_X1-085
Solar/Wind Harmer
0.343
971667AH1-334 GEN
Solar/Wind Harmer
2.318
219114HARTZY_C
Solar/Wind Harmer
0.7
219727YARDVSOLFA C
Solar/Wind Harmer
0.762
207454AA2-184 E
Solar/Wind Harmer
0.828
219918AC2-009 C
Solar/Wind Harmer
0.021
219612MATRIX C
Solar/Wind Harmer
0.151
20716928W4-060COL
Solar/Wind Harmer
0.583
20635828PARLN1&2
Adder
2.735
20635928PARLN3&4
Adder
2.735
217213AMBOY SO C
Solar/Wind Harmer
0.102
219249CENTRALDIV C
Solar/Wind Harmer
0.032
207442AE1-156 GEN
Solar/Wind Harmer
0.593
20673728F2S_V4-070
Solar/Wind Harmer
0.143
217211CAMDEN ST C
Solar/Wind Harmer
0.019
217169METRODIV C
Solar/Wind Harmer
0.032
217194REDH C
Solar/Wind Harmer
0.39
20674528F3S_W2-016
Solar/Wind Harmer
1.099
207511W3-106 GEN
Solar/Wind Harmer
0.254
207510AF2-138 C
Solar/Wind Harmer
1.367
971007AG2-625 GEN
Solar/Wind Harmer
1.937
20466127PORT 5CT
Adder
19.892
207437AD2-070 GEN
Solar/Wind Harmer
0.224
20671928W4-073
Solar/Wind Harmer
0.322
20674128FR_U2-059
Solar/Wind Harmer
0.137
20465427SHAW CT
Adder
2.889
20633028GILCT9
Adder
20.866
209116AE2-175 GEN
Solar/Wind Harmer
3.024
211065PSPA IPP
Solar/Wind Harmer
0.328
963161AG1-165 GEN
Solar/Wind Harmer
0.699
209025WIENIPP3
Adder
3.688
970095AG2-074 GEN
Solar/Wind Harmer
4.377
208972BECR K09
Solar/Wind Harmer
0.732
961331AF2-424 GEN
Solar/Wind Harmer
0.661
961421AF2-433 GEN
Solar/Wind Harmer
0.659
957921AF2-086 GEN
Solar/Wind Harmer
0.641
209142AF1-226 GEN
Solar/Wind Harmer
3.816
209093AE2-110 GEN
Solar/Wind Harmer
1.648
209120AE2-241 GEN
Solar/Wind Harmer
2.181
946691AF1-333 GEN
Solar/Wind Harmer
0.637
946741AF1-338 GEN
Solar/Wind Harmer
0.637
209071AE2-133 GEN
Solar/Wind Harmer
1.075
205941AD2-115 GEN
Solar/Wind Harmer
0.496
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.486
208835TUHI V3-051
Solar/Wind Helper
0.022
200202DELTA2 ST
50/50
6.362
200195DELTA ST
50/50
3.243
200052ROCKSP 1
50/50
2.683
200053ROCKSP 2
50/50
2.63
232904IR4
Adder
89.03
232920IR10
Adder
3.479
232432Z2-076 GEN
Solar/Wind Harmer
0.145
233901CHERRYDALE C
Solar/Wind Harmer
1.237
232912OH NUG1
Adder
9.718
232913OH NUG2
Adder
9.588
233940AF2-379 C
Solar/Wind Harmer
0.205
971195AH1-057 GEN
Solar/Wind Harmer
1.072
233955AB2-172 GEN
Solar/Wind Harmer
5.479
232813VAUGHN
Adder
0.643
231906DC3 NUG
Adder
15.08
231902DC CT7
Adder
12.055
231907DC10
Adder
3.765
233968AD2-076_GEN
Solar/Wind Harmer
7.142
970597AG2-380 GEN
Solar/Wind Harmer
4.485
233915AB1-141 GEN
Solar/Wind Harmer
1.059
231919CHRIST1
Adder
4.54
231920CHRIST2
Adder
4.439
970453AG2-297 GEN
Solar/Wind Harmer
2.549
230422AE1-104_GEN1
Solar/Wind Harmer
30.772
230425AE1-104_GEN2
Solar/Wind Harmer
30.772
972141AH1-641 GEN
Solar/Wind Harmer
2.622
230430AE1-229_GEN
Solar/Wind Harmer
26.078
964001AG1-254 GEN
Solar/Wind Harmer
6.629
228728W1-130C
Solar/Wind Harmer
0.603
227927V4-067C
Solar/Wind Harmer
0.18
230407AD2-065 C
Solar/Wind Harmer
0.119
230434AG1-499 GEN
Solar/Wind Harmer
0.523
219137THOSOLAR C
Solar/Wind Harmer
1.071
219258KINSLEYDEP C
Solar/Wind Harmer
0.285
219615MILLCREEK C
Solar/Wind Harmer
0.206
213957STHWK3-4
Adder
2.334
213957STHWK3-4
Adder
2.334
219610FLORENCE C
Solar/Wind Harmer
1.191
219224BRL12CT4
Adder
7.676
213942SCHUYLKILL
Adder
3.052
213942SCHUYLKILL
Adder
2.334
213561DLWR9-10
Adder
3.044
213561DLWR9-10
Adder
2.328
20720728JCB_W1-129
Solar/Wind Harmer
0.254
20715028HAN_X4-015
Solar/Wind Harmer
0.254
207487AE2-000G4
Solar/Wind Harmer
26.768
207497AE2-000G2
Solar/Wind Harmer
26.768
207500AE2-000G1
Solar/Wind Harmer
26.768
207507AE2-000G3
Solar/Wind Harmer
26.768
213611FALLS1-3
Adder
3.001
213611FALLS1-3
Adder
3.001
963401AG1-189 GEN
Solar/Wind Harmer
1.928
970025AG2-016 GEN
Solar/Wind Harmer
2.4
971189AH1-054 GEN
Solar/Wind Harmer
0.998
207445AB1-138_GEN
Solar/Wind Harmer
0.488
20714428HOW_X1-037
Solar/Wind Harmer
1.025
219620RIDERU C
Solar/Wind Harmer
0.046
20720628TIN_W1-124
Solar/Wind Harmer
0.825
20716228APLW2-078
Solar/Wind Harmer
0.732
971521AH1-258 GEN
Solar/Wind Harmer
2.234
20635928PARLN3&4
Adder
6.039
218526CNTRALGAS2 C
Solar/Wind Harmer
0.3
20675528CPH_W2-050
Solar/Wind Harmer
0.461
20673828FLE_V3-070
Solar/Wind Harmer
0.373
218449LINSOLAR C
Solar/Wind Harmer
0.806
20676128MHD_W3-029
Solar/Wind Harmer
0.381
20676428JCR_X2-075
Solar/Wind Harmer
0.272
217167KRNY_14
Adder
7.38
217086KRNY_131
Adder
7.317
217147KRNY_1212
Adder
7.02
217147KRNY_1212
Adder
6.894
217146KRNY_1234
Adder
6.879
217146KRNY_1234
Adder
6.832
964851AG1-348 GEN
Solar/Wind Harmer
1.031
971009AG2-626 GEN
Solar/Wind Harmer
1.236
207408W3-077 C
Solar/Wind Harmer
0.379
20462827N BANGR8
Adder
0.534
20675128HRM_W1-127
Solar/Wind Harmer
0.127
961261AF2-417 GEN
Solar/Wind Harmer
0.714
209026WIENIPP4
Adder
3.726
209029WAYMART-WD
Solar/Wind Harmer
1.804
209027LOR2_Q27
Solar/Wind Harmer
3.052
212266LOR1
Solar/Wind Harmer
0.809
209054AE2-059 GEN
Solar/Wind Harmer
1.088
959431AF2-234 GEN
Solar/Wind Harmer
1.27
964051AG1-259 GEN
Solar/Wind Harmer
0.852
964061AG1-260 GEN
Solar/Wind Harmer
0.852
959421AF2-233 GEN
Solar/Wind Harmer
0.635
226929AD2-058 GEN
Solar/Wind Helper
0.133
3141426STAFORD
Solar/Wind Helper
0.05
200192DELTA CT1
50/50
2.099
200194DELTA CT3
50/50
2.099
200204Y1-065-CTG1
50/50
4.264
200054ROCKSP 3
50/50
2.714
233970AC1-092 C
Solar/Wind Harmer
2.962
232901NORTHST
Adder
9.195
232900DEMECSMY
Adder
10.163
234033AF1-007_GEN
Solar/Wind Harmer
40.956
972177AH1-672 GEN
Solar/Wind Harmer
14.788
232404W1-003 C
Solar/Wind Harmer
1.1
232408W1-005 C
Solar/Wind Harmer
1.1
200201DELTA2 CT2
50/50
3.757
200034PCHBTM 2
50/50
21.89
200035PCHBTM 3
50/50
21.288
200205Y1-065-CTG2
50/50
4.264
233971AC1-093 C
Solar/Wind Harmer
2.812
232899W1-062
Adder
10.596
232410W1-006 C
Solar/Wind Harmer
1.1
232918OH NUG7
Adder
9.653
232905CHERITON_25
Adder
2.699
232926CRISFLD1
Adder
2.159
231940T-011
Adder
0.821
234015AF2-250 C
Solar/Wind Harmer
0.132
232428Y3-058 C
Solar/Wind Harmer
0.916
233994AC2-023 GEN
Solar/Wind Harmer
2.951
233946AB2-136 GEN
Solar/Wind Harmer
4.375
233952AC2-187 GEN
Solar/Wind Harmer
1.234
233954AC2-188 GEN
Solar/Wind Harmer
1.234
234036AF2-325 C
Solar/Wind Harmer
1.005
234041AC1-190 GEN
Solar/Wind Harmer
9.819
232910NRG_G1
Adder
9.408
233984AB2-036 GEN
Solar/Wind Harmer
13.498
232424Y1-079 C
Solar/Wind Harmer
0.609
234014AF1-036_GEN
Solar/Wind Harmer
2.915
232436AB1-176 C
Solar/Wind Harmer
0.246
233930AB2-032 GEN
Solar/Wind Harmer
0.891
233982AB2-133 GEN
Solar/Wind Harmer
5.204
228201CARL#2CT
Adder
6.292
228200CARL#1CT
Adder
5.984
228251CARLLS#4
Adder
0.577
230433AD2-135 GEN
Solar/Wind Harmer
0.092
230511AF1-262
Solar/Wind Harmer
0.166
228351V2-046C
Solar/Wind Harmer
1.832
228754AB1-001 C
Solar/Wind Harmer
0.126
228307PCLP GT
Adder
10.92
972233AH1-701 GEN
Adder
3.765
219272CLEANLIGHT C
Solar/Wind Harmer
0.161
219287REEVESEAST C
Solar/Wind Harmer
1.183
219904AC1-010 C
Solar/Wind Harmer
0.332
219912AD2-042 GEN
Solar/Wind Harmer
0.695
213589EDDYSTN4
Adder
68.955
213587EDDYSTN3
Adder
68.948
219906AC1-017 C
Solar/Wind Harmer
0.192
219607WPEMNERT C
Solar/Wind Harmer
0.36
219304NAMERICA C
Solar/Wind Harmer
0.267
213535CROYDN11
Adder
8.783
213815MOSER1-3
Adder
3.015
213815MOSER1-3
Adder
3.015
20720828JCB_W4-025
Solar/Wind Harmer
0.385
20636128O CRK C2
Adder
5.476
214067T20SOLAR
Solar/Wind Harmer
0.214
207459AE1-142 C O1
Solar/Wind Harmer
0.89
20628028LAKEHURS
Adder
0.802
20714828MDF_W3-079
Solar/Wind Harmer
0.256
219817TRENTONSOL C
Solar/Wind Harmer
0.914
20641628MLH_W1-032
Solar/Wind Harmer
0.243
20742028HF_AC1-207
Solar/Wind Harmer
0.648
217197RE CRAN C
Solar/Wind Harmer
0.44
218438BLK ROCK C
Solar/Wind Harmer
0.112
924131AB2-057 GEN
Solar/Wind Harmer
0.838
20635028RRCT1&2
Adder
9.441
20635128RRCT3&4
Adder
9.113
20635128RRCT3&4
Adder
7.949
218418LINDEN_G5
Adder
13.824
218419LINDEN_G6
Adder
13.824
972260AH1-715 GEN1
Adder
11.069
219036LINDEN_G7
Adder
13.399
219035LINDEN_G8
Adder
13.208
972261AH1-715 GEN2
Adder
12.826
20675428EAM_W2-061
Solar/Wind Harmer
0.151
217081WEATEXAS C
Solar/Wind Harmer
0.069
217202FBANKSOLAR C
Solar/Wind Harmer
0.059
217201HACKENSOLA C
Solar/Wind Harmer
0.058
972237AH1-703 GEN
Adder
8.035
217206BARNGR HS C
Solar/Wind Harmer
0.024
217086KRNY_131
Adder
7.396
217083KRNY_132
Adder
7.333
217204WCALDSOLAR C
Solar/Wind Harmer
0.058
20674328GAR_V4-001
Solar/Wind Harmer
0.084
20674828DL_W4-046
Solar/Wind Harmer
0.489
207471AF2-354 C
Solar/Wind Harmer
0.387
20634528N27_Y2-018
Solar/Wind Harmer
0.203
20465127PORT CT
Adder
2.983
20675928HOL_W4-097
Solar/Wind Harmer
0.097
209010PEIP 1
Adder
2.47
209010PEIP 1
Adder
0.362
961541AF2-445A GEN
Solar/Wind Harmer
2.192
961431AF2-434 GEN
Solar/Wind Harmer
0.659
946751AF1-339 GEN
Solar/Wind Harmer
0.637
209130AF1-271A GEN
Solar/Wind Harmer
1.786
223401AF1-299 GEN
Solar/Wind Helper
0.718
223402AF1-300 C
Solar/Wind Helper
0.718
232917OH NUG6
Adder
9.675
232915OH NUG4
Adder
9.653
233996TM1833_GEN
Solar/Wind Harmer
1.096
233998TM1NIN_3.36
Solar/Wind Harmer
1.096
232919VN10
Adder
3.083
232426Y1-080 FULL
Solar/Wind Harmer
0.21
232902EASTMUNI
Adder
14.21
972251AH1-710 GEN
Adder
48.401
234012AE2-112_GEN
Solar/Wind Harmer
2.478
233944AB2-135 GEN
Solar/Wind Harmer
5.614
233918AB1-142 GEN
Solar/Wind Harmer
1.059
231918WEST 1
Adder
3.451
231917EM10
Adder
2.4
228206SHRMN CT
Adder
15.254
228732V1-021 C
Adder
0.174
228260V4-054C
Solar/Wind Harmer
0.939
970997AG2-616 GEN
Solar/Wind Harmer
8.74
228729W2-030 C
Solar/Wind Harmer
0.524
228400MICK 1CT
Adder
10.582
219686LUMSOLAR_N C
Solar/Wind Harmer
0.178
219766PARADISE C
Solar/Wind Harmer
0.276
213497CHSTR7-9
Adder
2.365
213497CHSTR7-9
Adder
2.365
219907AC1-030 C
Solar/Wind Harmer
0.121
213958STHWK5-6
Adder
2.334
219348LDSOLAR C
Solar/Wind Harmer
0.514
219222BRL12CT2
Adder
7.676
213560DLW11-12
Adder
2.328
20716028EGP_W2-019
Solar/Wind Harmer
0.395
207522AF2-254 C
Solar/Wind Harmer
1.221
20717128DIX_Z2-102
Solar/Wind Harmer
1.122
20715828PEM_W1-120
Solar/Wind Harmer
0.454
213611FALLS1-3
Adder
3.001
214194N WALES4
Adder
0.715
963711AG1-223 GEN
Solar/Wind Harmer
1.238
20714528FRN_Y2-051
Solar/Wind Harmer
0.247
219276PARKLANDSO C
Solar/Wind Harmer
0.384
20715228NPK_W1-113
Solar/Wind Harmer
0.356
20720528MAN_W1-024
Solar/Wind Harmer
0.21
219680HOPEWELLV C1
Solar/Wind Harmer
0.063
20720428HOL_W1-112
Solar/Wind Harmer
0.285
20635828PARLN1&2
Adder
6.039
20635028RRCT1&2
Adder
9.589
218524CNTRALGAS1 C
Solar/Wind Harmer
0.299
218440SUMMTASSOC C
Solar/Wind Harmer
0.103
218428ETC SOLAR C
Solar/Wind Harmer
0.029
219908AB1-139 C
Solar/Wind Harmer
0.307
219919AE1-041 FULL
Solar/Wind Harmer
0.033
972275AH1-722 GEN
Adder
25.413
20673628F1S_V4-069
Solar/Wind Harmer
0.143
207528AF2-192 GEN
Solar/Wind Harmer
1.014
217209CENTRL HS C
Solar/Wind Harmer
0.036
217186ESSEX_G9
Adder
3.134
217121ECCF
Adder
0.345
217083KRNY_132
Adder
7.38
217208PARK ELE C
Solar/Wind Harmer
0.02
20671828STAW2-080
Solar/Wind Harmer
0.083
20676728BRNX1-095
Solar/Wind Harmer
0.138
966261AG1-495 GEN
Solar/Wind Harmer
2.703
207439AE1-081 C O1
Solar/Wind Harmer
0.046
20676328BVR_Y1-020
Solar/Wind Harmer
0.255
20674628WNG_W3-110
Solar/Wind Harmer
0.31
20676228FRD_X1-012
Solar/Wind Harmer
0.455
207530AG1-191 GEN
Solar/Wind Harmer
1.053
20675828AU_W4-064
Solar/Wind Harmer
0.133
20674928WA_W3-044
Solar/Wind Harmer
0.364
971519AH1-257 GEN
Solar/Wind Harmer
1.897
20675728RH_W2-091
Solar/Wind Harmer
0.452
207518AF1-320_GEN
Solar/Wind Harmer
2.738
20465127PORT CT
Adder
2.248
207484AF2-139 C O1
Solar/Wind Harmer
0.376
208909MACR G3
Adder
118.084
211065PSPA IPP
Solar/Wind Harmer
0.328
961301AF2-421 GEN
Solar/Wind Harmer
0.699
963151AG1-164 GEN
Solar/Wind Harmer
0.699
209023WIENIPP1
Adder
7.541
209025WIENIPP3
Adder
3.764
963071AG1-156 GEN
Solar/Wind Harmer
6.911
209010PEIP 1
Adder
0.449
961341AF2-425 GEN
Solar/Wind Harmer
0.661
212507AE2-042_GEN
Solar/Wind Harmer
1.928
946731AF1-337 GEN
Solar/Wind Harmer
0.637
209018SUNBIPCT
Adder
4.731
208835TUHI V3-051
Solar/Wind Helper
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.146
VTFLTFEXP_VFT->PJM
CMTX
107.886
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.401
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.032
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.452
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.432
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
41.698
CBM NorthLTFEXP_CBM-N->PJM
CBM
58.927
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.37 %
Rating:2920.0 MVA
Rating Type:A
MVA to Mitigate:3310.31
MW Contribution:
3.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
7.401
200195DELTA ST
50/50
3.772
200052ROCKSP 1
50/50
3.122
200053ROCKSP 2
50/50
3.061
232904IR4
Adder
104.156
232920IR10
Adder
4.071
232432Z2-076 GEN
Solar/Wind Harmer
0.017
232912OH NUG1
Adder
11.372
232913OH NUG2
Adder
11.22
971195AH1-057 GEN
Solar/Wind Harmer
0.804
232813VAUGHN
Adder
0.753
231906DC3 NUG
Adder
17.692
231902DC CT7
Adder
14.144
231907DC10
Adder
4.417
233968AD2-076_GEN
Solar/Wind Harmer
2.939
970597AG2-380 GEN
Solar/Wind Harmer
5.264
233915AB1-141 GEN
Solar/Wind Harmer
0.32
231919CHRIST1
Adder
5.34
231920CHRIST2
Adder
5.221
970453AG2-297 GEN
Solar/Wind Harmer
2.736
230422AE1-104_GEN1
Solar/Wind Harmer
14.354
230425AE1-104_GEN2
Solar/Wind Harmer
14.354
972141AH1-641 GEN
Solar/Wind Harmer
1.655
230430AE1-229_GEN
Solar/Wind Harmer
21.028
964001AG1-254 GEN
Solar/Wind Harmer
5.972
213942SCHUYLKILL
Adder
3.576
213942SCHUYLKILL
Adder
2.735
213957STHWK3-4
Adder
2.734
213957STHWK3-4
Adder
2.734
213561DLWR9-10
Adder
3.554
213561DLWR9-10
Adder
2.717
219224BRL12CT4
Adder
8.911
213611FALLS1-3
Adder
3.48
213611FALLS1-3
Adder
3.48
207487AE2-000G4
Solar/Wind Harmer
12.416
207497AE2-000G2
Solar/Wind Harmer
12.416
207500AE2-000G1
Solar/Wind Harmer
12.416
207507AE2-000G3
Solar/Wind Harmer
12.416
963401AG1-189 GEN
Solar/Wind Harmer
1.101
970025AG2-016 GEN
Solar/Wind Harmer
1.792
971189AH1-054 GEN
Solar/Wind Harmer
0.745
971521AH1-258 GEN
Solar/Wind Harmer
1.661
20635928PARLN3&4
Adder
6.939
218526CNTRALGAS2 C
Solar/Wind Harmer
0.712
217167KRNY_14
Adder
8.439
217086KRNY_131
Adder
8.367
217147KRNY_1212
Adder
8.027
217147KRNY_1212
Adder
7.884
217146KRNY_1234
Adder
7.866
217146KRNY_1234
Adder
7.812
971009AG2-626 GEN
Solar/Wind Harmer
0.908
20462827N BANGR8
Adder
0.606
209026WIENIPP4
Adder
4.108
209027LOR2_Q27
Solar/Wind Harmer
0
20486527WR_V4-052
Adder
0.596
226929AD2-058 GEN
Solar/Wind Helper
0.114
200192DELTA CT1
50/50
2.442
200194DELTA CT3
50/50
2.442
200204Y1-065-CTG1
50/50
4.963
200054ROCKSP 3
50/50
3.158
232901NORTHST
Adder
10.748
233970AC1-092 C
Solar/Wind Harmer
2.329
234033AF1-007_GEN
Solar/Wind Harmer
17.79
232900DEMECSMY
Adder
11.884
972177AH1-672 GEN
Solar/Wind Harmer
13.116
232404W1-003 C
Solar/Wind Harmer
0.831
232408W1-005 C
Solar/Wind Harmer
0.831
232917OH NUG6
Adder
11.321
232915OH NUG4
Adder
11.296
232919VN10
Adder
3.609
232902EASTMUNI
Adder
16.653
234012AE2-112_GEN
Solar/Wind Harmer
2.939
972251AH1-710 GEN
Adder
56.355
233918AB1-142 GEN
Solar/Wind Harmer
0.32
231918WEST 1
Adder
4.06
231917EM10
Adder
2.824
228206SHRMN CT
Adder
17.736
228732V1-021 C
Adder
0.202
970997AG2-616 GEN
Solar/Wind Harmer
7.65
228400MICK 1CT
Adder
12.321
213497CHSTR7-9
Adder
2.779
213497CHSTR7-9
Adder
2.779
213958STHWK5-6
Adder
2.734
213560DLW11-12
Adder
2.717
219222BRL12CT2
Adder
8.911
213611FALLS1-3
Adder
3.48
207522AF2-254 C
Solar/Wind Harmer
0.912
214194N WALES4
Adder
0.831
20635828PARLN1&2
Adder
6.939
20635028RRCT1&2
Adder
11.012
218524CNTRALGAS1 C
Solar/Wind Harmer
0.71
972275AH1-722 GEN
Adder
29.134
207528AF2-192 GEN
Solar/Wind Harmer
0.657
217186ESSEX_G9
Adder
3.584
217121ECCF
Adder
0.394
217083KRNY_132
Adder
8.439
966261AG1-495 GEN
Solar/Wind Harmer
1.51
971519AH1-257 GEN
Solar/Wind Harmer
1.394
20465127PORT CT
Adder
2.549
208909MACR G3
Adder
133.592
209023WIENIPP1
Adder
8.313
209025WIENIPP3
Adder
4.15
963071AG1-156 GEN
Solar/Wind Harmer
5.821
209010PEIP 1
Adder
0.493
212507AE2-042_GEN
Solar/Wind Harmer
0.425
209018SUNBIPCT
Adder
5.068
970757AG2-479 GEN
Solar/Wind Harmer
0.537
20465527S.RDG CT
Adder
1.516
200201DELTA2 CT2
50/50
4.37
200034PCHBTM 2
50/50
25.466
200035PCHBTM 3
50/50
24.778
200205Y1-065-CTG2
50/50
4.963
233971AC1-093 C
Solar/Wind Harmer
2.329
232899W1-062
Adder
12.389
232410W1-006 C
Solar/Wind Harmer
0.831
232918OH NUG7
Adder
11.296
232905CHERITON_25
Adder
3.159
232926CRISFLD1
Adder
2.527
231940T-011
Adder
0.96
234041AC1-190 GEN
Solar/Wind Harmer
9.358
232910NRG_G1
Adder
11.021
233984AB2-036 GEN
Solar/Wind Harmer
9.239
234014AF1-036_GEN
Solar/Wind Harmer
2.939
233930AB2-032 GEN
Solar/Wind Harmer
1.204
228251CARLLS#4
Adder
0.671
228201CARL#2CT
Adder
7.318
228200CARL#1CT
Adder
6.96
228307PCLP GT
Adder
12.712
972233AH1-701 GEN
Adder
4.383
213589EDDYSTN4
Adder
81.033
213587EDDYSTN3
Adder
81.02
219304NAMERICA C
Solar/Wind Harmer
0.091
213535CROYDN11
Adder
10.198
213815MOSER1-3
Adder
3.51
213815MOSER1-3
Adder
3.51
20636128O CRK C2
Adder
6.328
20628028LAKEHURS
Adder
0.925
20714828MDF_W3-079
Solar/Wind Harmer
0.095
20635028RRCT1&2
Adder
10.843
20635128RRCT3&4
Adder
10.466
20635128RRCT3&4
Adder
9.13
218418LINDEN_G5
Adder
15.848
218419LINDEN_G6
Adder
15.848
972260AH1-715 GEN1
Adder
12.69
219036LINDEN_G7
Adder
15.347
219035LINDEN_G8
Adder
15.128
972261AH1-715 GEN2
Adder
14.691
972237AH1-703 GEN
Adder
9.189
217086KRNY_131
Adder
8.457
217083KRNY_132
Adder
8.385
20465127PORT CT
Adder
3.383
209010PEIP 1
Adder
2.71
209010PEIP 1
Adder
0.397
961541AF2-445A GEN
Solar/Wind Harmer
1.654
970761AG2-481 GEN
Solar/Wind Harmer
0.545
209130AF1-271A GEN
Solar/Wind Harmer
1.335
20465527S.RDG CT
Adder
1.467
223401AF1-299 GEN
Solar/Wind Helper
0.595
223402AF1-300 C
Solar/Wind Helper
0.595
200200DELTA2 CT1
50/50
4.37
200193DELTA CT2
50/50
2.442
200203Y1-065-STG
50/50
8.594
200055ROCKSP 4
50/50
3.104
233973AC2-185 C
Solar/Wind Harmer
2.329
970695AG2-447 GEN
Solar/Wind Harmer
3.227
233939AC1-091 C
Solar/Wind Harmer
2.329
233972AC1-094 C
Solar/Wind Harmer
2.329
233987AB2-037 GEN
Solar/Wind Harmer
-0.002
232434Z2-077 GEN
Solar/Wind Harmer
0.054
232406W1-004 FULL
Solar/Wind Harmer
0.831
232914OH NUG3
Adder
11.372
232916OH NUG5
Adder
11.372
232921TASLEY2G
Adder
6.646
232907VN8
Adder
38.641
232422X3-066 FULL
Solar/Wind Harmer
0.105
233935AB2-179 C
Solar/Wind Harmer
1.677
213497CHSTR7-9
Adder
2.779
213958STHWK5-6
Adder
2.734
213560DLW11-12
Adder
2.717
219221BRL12CT1
Adder
8.911
219223BRL12CT3
Adder
8.911
213815MOSER1-3
Adder
3.51
20636028O CRK C1
Adder
6.94
963391AG1-188 GEN
Solar/Wind Harmer
1.791
971667AH1-334 GEN
Solar/Wind Harmer
1.73
20635828PARLN1&2
Adder
3.143
20635928PARLN3&4
Adder
3.143
207442AE1-156 GEN
Solar/Wind Harmer
0.054
971007AG2-625 GEN
Solar/Wind Harmer
1.423
20466127PORT 5CT
Adder
22.534
207437AD2-070 GEN
Solar/Wind Harmer
0.055
20465427SHAW CT
Adder
3.263
20633028GILCT9
Adder
23.749
209025WIENIPP3
Adder
4.066
970095AG2-074 GEN
Solar/Wind Harmer
3.861
209142AF1-226 GEN
Solar/Wind Harmer
2.02
209093AE2-110 GEN
Solar/Wind Harmer
1.154
209120AE2-241 GEN
Solar/Wind Harmer
1.154
205941AD2-115 GEN
Solar/Wind Harmer
0.072
226910AB2-157 C
Solar/Wind Helper
0.017
227287AC2-120 GEN
Solar/Wind Helper
0.413
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.145
VTFLTFEXP_VFT->PJM
CMTX
123.44
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.451
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.477
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.832
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.33
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
47.889
CBM NorthLTFEXP_CBM-N->PJM
CBM
63.218
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P2-2_NOTT230B_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B $ B


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_NOTT230B_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.12 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:3877.79
MW Contribution:
5.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200201DELTA2 CT2
50/50
4.435
200034PCHBTM 2
50/50
25.851
200035PCHBTM 3
50/50
25.177
200205Y1-065-CTG2
50/50
5.082
233946AB2-136 GEN
Solar/Wind Harmer
5.612
234036AF2-325 C
Solar/Wind Harmer
1.29
234041AC1-190 GEN
Solar/Wind Harmer
12.605
233994AC2-023 GEN
Solar/Wind Harmer
3.777
232926CRISFLD1
Adder
2.762
232428Y3-058 C
Solar/Wind Harmer
1.172
232410W1-006 C
Solar/Wind Harmer
1.407
232918OH NUG7
Adder
12.345
232905CHERITON_25
Adder
3.452
234015AF2-250 C
Solar/Wind Harmer
0.169
231940T-011
Adder
1.049
233984AB2-036 GEN
Solar/Wind Harmer
17.513
232424Y1-079 C
Solar/Wind Harmer
0.79
233952AC2-187 GEN
Solar/Wind Harmer
1.58
233954AC2-188 GEN
Solar/Wind Harmer
1.58
234014AF1-036_GEN
Solar/Wind Harmer
3.802
232436AB1-176 C
Solar/Wind Harmer
0.322
232910NRG_G1
Adder
12.119
232899W1-062
Adder
13.496
233971AC1-093 C
Solar/Wind Harmer
3.57
233930AB2-032 GEN
Solar/Wind Harmer
1.168
233982AB2-133 GEN
Solar/Wind Harmer
6.828
213589EDDYSTN4
Adder
92.75
213587EDDYSTN3
Adder
92.725
228201CARL#2CT
Adder
7.979
228200CARL#1CT
Adder
7.588
228251CARLLS#4
Adder
0.732
228351V2-046C
Solar/Wind Harmer
2.33
230511AF1-262
Solar/Wind Harmer
0.211
230433AD2-135 GEN
Solar/Wind Harmer
0.117
228307PCLP GT
Adder
13.942
972233AH1-701 GEN
Adder
4.815
228754AB1-001 C
Solar/Wind Harmer
0.159
219904AC1-010 C
Solar/Wind Harmer
0.425
200192DELTA CT1
50/50
2.478
200194DELTA CT3
50/50
2.478
200204Y1-065-CTG1
50/50
5.082
200054ROCKSP 3
50/50
3.234
232426Y1-080 FULL
Solar/Wind Harmer
0.269
232919VN10
Adder
3.951
232902EASTMUNI
Adder
18.342
233996TM1833_GEN
Solar/Wind Harmer
1.402
233998TM1NIN_3.36
Solar/Wind Harmer
1.402
232404W1-003 C
Solar/Wind Harmer
1.407
232408W1-005 C
Solar/Wind Harmer
1.407
232917OH NUG6
Adder
12.373
232915OH NUG4
Adder
12.345
234033AF1-007_GEN
Solar/Wind Harmer
52.304
972177AH1-672 GEN
Solar/Wind Harmer
18.882
234012AE2-112_GEN
Solar/Wind Harmer
3.232
232901NORTHST
Adder
11.685
232900DEMECSMY
Adder
12.945
233970AC1-092 C
Solar/Wind Harmer
3.76
233918AB1-142 GEN
Solar/Wind Harmer
1.388
233944AB2-135 GEN
Solar/Wind Harmer
7.341
231918WEST 1
Adder
4.589
231917EM10
Adder
3.193
972251AH1-710 GEN
Adder
60.551
228206SHRMN CT
Adder
19.293
213497CHSTR7-9
Adder
3.178
200200DELTA2 CT1
50/50
4.435
200193DELTA CT2
50/50
2.478
200203Y1-065-STG
50/50
8.801
200055ROCKSP 4
50/50
3.179
233987AB2-037 GEN
Solar/Wind Harmer
16.045
232907VN8
Adder
42.282
233964AF2-378 GEN
Solar/Wind Harmer
0.18
232417X3-008 C
Solar/Wind Harmer
1.583
233923SMA
Solar/Wind Harmer
5.142
233997TMININ_4.2
Solar/Wind Harmer
1.402
232406W1-004 FULL
Solar/Wind Harmer
1.407
232914OH NUG3
Adder
12.428
232916OH NUG5
Adder
12.428
232921TASLEY2G
Adder
7.263
232434Z2-077 GEN
Solar/Wind Harmer
0.352
233950AC2-186 GEN
Solar/Wind Harmer
0.79
232422X3-066 FULL
Solar/Wind Harmer
0.351
233973AC2-185 C
Solar/Wind Harmer
7.595
970695AG2-447 GEN
Solar/Wind Harmer
5.025
233939AC1-091 C
Solar/Wind Harmer
3.76
233972AC1-094 C
Solar/Wind Harmer
3.019
233933AB2-153 GEN
Solar/Wind Harmer
1.577
233935AB2-179 C
Solar/Wind Harmer
3.486
228711V2-041C
Solar/Wind Harmer
0.699
213497CHSTR7-9
Adder
3.178
230415AB2-049 C
Solar/Wind Harmer
0.218
213958STHWK5-6
Adder
3.094
219623KINSLEYBEA C
Solar/Wind Harmer
0.483
219921AF1-264
Solar/Wind Harmer
0.163
219291REEVESSOUT C
Solar/Wind Harmer
0.067
219914AD2-027 C
Solar/Wind Harmer
0.672
218660EHAMPSOLAR C
Solar/Wind Harmer
0.195
213560DLW11-12
Adder
3.04
219688LUMSOLAR_S C
Solar/Wind Harmer
0.226
219236SOUTHERNHQ C
Solar/Wind Harmer
0.075
219221BRL12CT1
Adder
9.781
219223BRL12CT3
Adder
9.781
213815MOSER1-3
Adder
3.886
959561AF2-247 GEN
Solar/Wind Harmer
0.522
20716428NHV_W2-082
Solar/Wind Harmer
1.902
20715728PEM_W1-119
Solar/Wind Harmer
0.57
20636028O CRK C1
Adder
7.531
963391AG1-188 GEN
Solar/Wind Harmer
3.979
20714928UPF_X1-085
Solar/Wind Harmer
0.431
219114HARTZY_C
Solar/Wind Harmer
0.884
971667AH1-334 GEN
Solar/Wind Harmer
2.905
219727YARDVSOLFA C
Solar/Wind Harmer
0.96
219918AC2-009 C
Solar/Wind Harmer
0.027
207454AA2-184 E
Solar/Wind Harmer
1.032
219612MATRIX C
Solar/Wind Harmer
0.188
20716928W4-060COL
Solar/Wind Harmer
0.726
20635828PARLN1&2
Adder
3.399
20635928PARLN3&4
Adder
3.399
217213AMBOY SO C
Solar/Wind Harmer
0.127
219249CENTRALDIV C
Solar/Wind Harmer
0.04
207442AE1-156 GEN
Solar/Wind Harmer
0.735
20673728F2S_V4-070
Solar/Wind Harmer
0.178
217211CAMDEN ST C
Solar/Wind Harmer
0.024
217169METRODIV C
Solar/Wind Harmer
0.039
217194REDH C
Solar/Wind Harmer
0.482
20674528F3S_W2-016
Solar/Wind Harmer
1.362
207510AF2-138 C
Solar/Wind Harmer
1.675
207511W3-106 GEN
Solar/Wind Harmer
0.311
971007AG2-625 GEN
Solar/Wind Harmer
2.366
20466127PORT 5CT
Adder
24.184
207437AD2-070 GEN
Solar/Wind Harmer
0.274
20671928W4-073
Solar/Wind Harmer
0.392
20674128FR_U2-059
Solar/Wind Harmer
0.167
20465427SHAW CT
Adder
3.501
20633028GILCT9
Adder
25.478
209116AE2-175 GEN
Solar/Wind Harmer
3.644
211065PSPA IPP
Solar/Wind Harmer
0.394
963161AG1-165 GEN
Solar/Wind Harmer
0.823
209025WIENIPP3
Adder
4.341
970095AG2-074 GEN
Solar/Wind Harmer
5.146
208972BECR K09
Solar/Wind Harmer
0.857
961331AF2-424 GEN
Solar/Wind Harmer
0.763
961421AF2-433 GEN
Solar/Wind Harmer
0.76
957921AF2-086 GEN
Solar/Wind Harmer
0.739
209142AF1-226 GEN
Solar/Wind Harmer
4.401
209093AE2-110 GEN
Solar/Wind Harmer
1.901
209120AE2-241 GEN
Solar/Wind Harmer
2.515
946691AF1-333 GEN
Solar/Wind Harmer
0.725
946741AF1-338 GEN
Solar/Wind Harmer
0.725
209071AE2-133 GEN
Solar/Wind Harmer
1.223
205941AD2-115 GEN
Solar/Wind Harmer
0.608
226910AB2-157 C
Solar/Wind Helper
0.019
200202DELTA2 ST
50/50
7.511
200195DELTA ST
50/50
3.829
200052ROCKSP 1
50/50
3.197
200053ROCKSP 2
50/50
3.135
233955AB2-172 GEN
Solar/Wind Harmer
7.035
233940AF2-379 C
Solar/Wind Harmer
0.262
233901CHERRYDALE C
Solar/Wind Harmer
1.582
232912OH NUG1
Adder
12.428
232913OH NUG2
Adder
12.262
971195AH1-057 GEN
Solar/Wind Harmer
1.371
232432Z2-076 GEN
Solar/Wind Harmer
0.186
232920IR10
Adder
4.444
232904IR4
Adder
113.698
233968AD2-076_GEN
Solar/Wind Harmer
9.315
970597AG2-380 GEN
Solar/Wind Harmer
5.85
232813VAUGHN
Adder
0.827
233915AB1-141 GEN
Solar/Wind Harmer
1.388
231906DC3 NUG
Adder
19.617
231902DC CT7
Adder
15.683
231907DC10
Adder
4.897
231919CHRIST1
Adder
6.026
231920CHRIST2
Adder
5.892
970453AG2-297 GEN
Solar/Wind Harmer
3.221
972141AH1-641 GEN
Solar/Wind Harmer
3.332
964001AG1-254 GEN
Solar/Wind Harmer
8.434
230430AE1-229_GEN
Solar/Wind Harmer
33.13
230422AE1-104_GEN1
Solar/Wind Harmer
38.875
230425AE1-104_GEN2
Solar/Wind Harmer
38.875
228728W1-130C
Solar/Wind Harmer
0.765
230434AG1-499 GEN
Solar/Wind Harmer
0.666
230407AD2-065 C
Solar/Wind Harmer
0.151
227927V4-067C
Solar/Wind Harmer
0.227
213942SCHUYLKILL
Adder
4.052
213942SCHUYLKILL
Adder
3.099
219137THOSOLAR C
Solar/Wind Harmer
1.374
213957STHWK3-4
Adder
3.094
213957STHWK3-4
Adder
3.094
219258KINSLEYDEP C
Solar/Wind Harmer
0.365
213561DLWR9-10
Adder
3.975
213561DLWR9-10
Adder
3.04
219615MILLCREEK C
Solar/Wind Harmer
0.263
219610FLORENCE C
Solar/Wind Harmer
1.517
219224BRL12CT4
Adder
9.781
213611FALLS1-3
Adder
3.817
213611FALLS1-3
Adder
3.817
20720728JCB_W1-129
Solar/Wind Harmer
0.319
20715028HAN_X4-015
Solar/Wind Harmer
0.319
207487AE2-000G4
Solar/Wind Harmer
33.561
207497AE2-000G2
Solar/Wind Harmer
33.561
207500AE2-000G1
Solar/Wind Harmer
33.561
207507AE2-000G3
Solar/Wind Harmer
33.561
963401AG1-189 GEN
Solar/Wind Harmer
2.417
970025AG2-016 GEN
Solar/Wind Harmer
3.009
971189AH1-054 GEN
Solar/Wind Harmer
1.252
207445AB1-138_GEN
Solar/Wind Harmer
0.611
219620RIDERU C
Solar/Wind Harmer
0.058
20714428HOW_X1-037
Solar/Wind Harmer
1.28
20720628TIN_W1-124
Solar/Wind Harmer
1.029
20716228APLW2-078
Solar/Wind Harmer
0.912
971521AH1-258 GEN
Solar/Wind Harmer
2.784
20635928PARLN3&4
Adder
7.505
218526CNTRALGAS2 C
Solar/Wind Harmer
0.372
20675528CPH_W2-050
Solar/Wind Harmer
0.574
20673828FLE_V3-070
Solar/Wind Harmer
0.464
218449LINSOLAR C
Solar/Wind Harmer
0.997
20676128MHD_W3-029
Solar/Wind Harmer
0.472
20676428JCR_X2-075
Solar/Wind Harmer
0.337
217167KRNY_14
Adder
9.106
217086KRNY_131
Adder
9.029
217147KRNY_1212
Adder
8.661
217147KRNY_1212
Adder
8.507
217146KRNY_1234
Adder
8.487
217146KRNY_1234
Adder
8.429
964851AG1-348 GEN
Solar/Wind Harmer
1.259
971009AG2-626 GEN
Solar/Wind Harmer
1.509
207408W3-077 C
Solar/Wind Harmer
0.463
20675128HRM_W1-127
Solar/Wind Harmer
0.154
20462827N BANGR8
Adder
0.65
961261AF2-417 GEN
Solar/Wind Harmer
0.847
209026WIENIPP4
Adder
4.386
209029WAYMART-WD
Solar/Wind Harmer
2.117
209027LOR2_Q27
Solar/Wind Harmer
3.539
212266LOR1
Solar/Wind Harmer
0.938
209054AE2-059 GEN
Solar/Wind Harmer
1.243
959431AF2-234 GEN
Solar/Wind Harmer
1.445
964051AG1-259 GEN
Solar/Wind Harmer
0.969
964061AG1-260 GEN
Solar/Wind Harmer
0.969
959421AF2-233 GEN
Solar/Wind Harmer
0.723
20486527WR_V4-052
Adder
0.618
226929AD2-058 GEN
Solar/Wind Helper
0.123
219272CLEANLIGHT C
Solar/Wind Harmer
0.204
219912AD2-042 GEN
Solar/Wind Harmer
0.891
219287REEVESEAST C
Solar/Wind Harmer
1.501
219906AC1-017 C
Solar/Wind Harmer
0.246
219607WPEMNERT C
Solar/Wind Harmer
0.459
219304NAMERICA C
Solar/Wind Harmer
0.34
213535CROYDN11
Adder
11.202
213815MOSER1-3
Adder
3.886
213815MOSER1-3
Adder
3.886
214067T20SOLAR
Solar/Wind Harmer
0.273
20720828JCB_W4-025
Solar/Wind Harmer
0.485
20636128O CRK C2
Adder
6.866
207459AE1-142 C O1
Solar/Wind Harmer
1.115
20628028LAKEHURS
Adder
1.004
20714828MDF_W3-079
Solar/Wind Harmer
0.32
219817TRENTONSOL C
Solar/Wind Harmer
1.146
20641628MLH_W1-032
Solar/Wind Harmer
0.303
20742028HF_AC1-207
Solar/Wind Harmer
0.808
217197RE CRAN C
Solar/Wind Harmer
0.549
218438BLK ROCK C
Solar/Wind Harmer
0.139
924131AB2-057 GEN
Solar/Wind Harmer
1.042
20635028RRCT1&2
Adder
11.725
20635128RRCT3&4
Adder
11.318
20635128RRCT3&4
Adder
9.872
218418LINDEN_G5
Adder
17.125
218419LINDEN_G6
Adder
17.125
972260AH1-715 GEN1
Adder
13.713
219036LINDEN_G7
Adder
16.576
219035LINDEN_G8
Adder
16.339
972261AH1-715 GEN2
Adder
15.867
20675428EAM_W2-061
Solar/Wind Harmer
0.187
217081WEATEXAS C
Solar/Wind Harmer
0.085
217202FBANKSOLAR C
Solar/Wind Harmer
0.072
217201HACKENSOLA C
Solar/Wind Harmer
0.072
972237AH1-703 GEN
Adder
9.915
217206BARNGR HS C
Solar/Wind Harmer
0.03
217086KRNY_131
Adder
9.125
217083KRNY_132
Adder
9.048
217204WCALDSOLAR C
Solar/Wind Harmer
0.071
20674328GAR_V4-001
Solar/Wind Harmer
0.103
20674828DL_W4-046
Solar/Wind Harmer
0.598
207471AF2-354 C
Solar/Wind Harmer
0.473
20634528N27_Y2-018
Solar/Wind Harmer
0.248
20675928HOL_W4-097
Solar/Wind Harmer
0.119
20465127PORT CT
Adder
3.631
209010PEIP 1
Adder
2.898
209010PEIP 1
Adder
0.424
961541AF2-445A GEN
Solar/Wind Harmer
2.543
961431AF2-434 GEN
Solar/Wind Harmer
0.76
946751AF1-339 GEN
Solar/Wind Harmer
0.725
209130AF1-271A GEN
Solar/Wind Harmer
2.032
20465527S.RDG CT
Adder
1.52
223401AF1-299 GEN
Solar/Wind Helper
0.702
223402AF1-300 C
Solar/Wind Helper
0.702
213497CHSTR7-9
Adder
3.178
228260V4-054C
Solar/Wind Harmer
1.191
228732V1-021 C
Adder
0.219
970997AG2-616 GEN
Solar/Wind Harmer
11.105
228729W2-030 C
Solar/Wind Harmer
0.662
228400MICK 1CT
Adder
13.542
213958STHWK5-6
Adder
3.094
219766PARADISE C
Solar/Wind Harmer
0.354
219686LUMSOLAR_N C
Solar/Wind Harmer
0.226
213560DLW11-12
Adder
3.04
219907AC1-030 C
Solar/Wind Harmer
0.154
219348LDSOLAR C
Solar/Wind Harmer
0.656
219222BRL12CT2
Adder
9.781
213611FALLS1-3
Adder
3.817
20716028EGP_W2-019
Solar/Wind Harmer
0.497
214194N WALES4
Adder
0.913
207522AF2-254 C
Solar/Wind Harmer
1.535
20717128DIX_Z2-102
Solar/Wind Harmer
1.411
20715828PEM_W1-120
Solar/Wind Harmer
0.57
963711AG1-223 GEN
Solar/Wind Harmer
1.549
20714528FRN_Y2-051
Solar/Wind Harmer
0.309
219276PARKLANDSO C
Solar/Wind Harmer
0.482
219680HOPEWELLV C1
Solar/Wind Harmer
0.079
20715228NPK_W1-113
Solar/Wind Harmer
0.444
20720528MAN_W1-024
Solar/Wind Harmer
0.262
20720428HOL_W1-112
Solar/Wind Harmer
0.355
20635828PARLN1&2
Adder
7.505
20635028RRCT1&2
Adder
11.908
218524CNTRALGAS1 C
Solar/Wind Harmer
0.371
218440SUMMTASSOC C
Solar/Wind Harmer
0.128
218428ETC SOLAR C
Solar/Wind Harmer
0.036
219908AB1-139 C
Solar/Wind Harmer
0.381
219919AE1-041 FULL
Solar/Wind Harmer
0.04
972275AH1-722 GEN
Adder
31.482
20673628F1S_V4-069
Solar/Wind Harmer
0.178
207528AF2-192 GEN
Solar/Wind Harmer
1.257
217209CENTRL HS C
Solar/Wind Harmer
0.044
217186ESSEX_G9
Adder
3.868
217121ECCF
Adder
0.425
217083KRNY_132
Adder
9.106
217208PARK ELE C
Solar/Wind Harmer
0.025
20671828STAW2-080
Solar/Wind Harmer
0.102
20676728BRNX1-095
Solar/Wind Harmer
0.169
966261AG1-495 GEN
Solar/Wind Harmer
3.335
207439AE1-081 C O1
Solar/Wind Harmer
0.057
20676328BVR_Y1-020
Solar/Wind Harmer
0.312
20674628WNG_W3-110
Solar/Wind Harmer
0.38
20676228FRD_X1-012
Solar/Wind Harmer
0.556
207530AG1-191 GEN
Solar/Wind Harmer
1.291
20675828AU_W4-064
Solar/Wind Harmer
0.162
20674928WA_W3-044
Solar/Wind Harmer
0.445
971519AH1-257 GEN
Solar/Wind Harmer
2.317
20675728RH_W2-091
Solar/Wind Harmer
0.551
207518AF1-320_GEN
Solar/Wind Harmer
3.34
20465127PORT CT
Adder
2.736
207484AF2-139 C O1
Solar/Wind Harmer
0.46
208909MACR G3
Adder
143.189
211065PSPA IPP
Solar/Wind Harmer
0.394
961301AF2-421 GEN
Solar/Wind Harmer
0.823
963151AG1-164 GEN
Solar/Wind Harmer
0.823
209023WIENIPP1
Adder
8.875
209025WIENIPP3
Adder
4.43
963071AG1-156 GEN
Solar/Wind Harmer
8.125
209010PEIP 1
Adder
0.527
961341AF2-425 GEN
Solar/Wind Harmer
0.763
212507AE2-042_GEN
Solar/Wind Harmer
2.203
946731AF1-337 GEN
Solar/Wind Harmer
0.725
209018SUNBIPCT
Adder
5.383
20465527S.RDG CT
Adder
1.571
208835TUHI V3-051
Solar/Wind Helper
0.021
227287AC2-120 GEN
Solar/Wind Helper
0.447
208835TUHI V3-051
Solar/Wind Helper
0.021
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.462
VTFLTFEXP_VFT->PJM
CMTX
133.231
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.637
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.729
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
17.523
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.619
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
51.785
CBM NorthLTFEXP_CBM-N->PJM
CBM
68.166
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PL_04_P71_001014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PL_04_P71_001014_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.23 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:3809.42
MW Contribution:
4.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
7.421
200195DELTA ST
50/50
3.783
200052ROCKSP 1
50/50
3.136
200053ROCKSP 2
50/50
3.075
232904IR4
Adder
105.649
232920IR10
Adder
4.129
232432Z2-076 GEN
Solar/Wind Harmer
0.172
233901CHERRYDALE C
Solar/Wind Harmer
1.469
232912OH NUG1
Adder
11.534
232913OH NUG2
Adder
11.38
233940AF2-379 C
Solar/Wind Harmer
0.243
971195AH1-057 GEN
Solar/Wind Harmer
1.272
233955AB2-172 GEN
Solar/Wind Harmer
6.507
232813VAUGHN
Adder
0.764
231906DC3 NUG
Adder
17.944
231902DC CT7
Adder
14.345
231907DC10
Adder
4.48
233968AD2-076_GEN
Solar/Wind Harmer
8.501
970597AG2-380 GEN
Solar/Wind Harmer
5.338
233915AB1-141 GEN
Solar/Wind Harmer
1.261
231919CHRIST1
Adder
5.425
231920CHRIST2
Adder
5.305
970453AG2-297 GEN
Solar/Wind Harmer
3.034
230422AE1-104_GEN1
Solar/Wind Harmer
36.639
230425AE1-104_GEN2
Solar/Wind Harmer
36.639
972141AH1-641 GEN
Solar/Wind Harmer
3.125
230430AE1-229_GEN
Solar/Wind Harmer
31.08
964001AG1-254 GEN
Solar/Wind Harmer
7.902
228728W1-130C
Solar/Wind Harmer
0.718
227927V4-067C
Solar/Wind Harmer
0.214
230407AD2-065 C
Solar/Wind Harmer
0.142
230434AG1-499 GEN
Solar/Wind Harmer
0.624
219137THOSOLAR C
Solar/Wind Harmer
1.28
219258KINSLEYDEP C
Solar/Wind Harmer
0.34
213942SCHUYLKILL
Adder
3.671
213942SCHUYLKILL
Adder
2.807
213957STHWK3-4
Adder
2.807
213957STHWK3-4
Adder
2.807
219615MILLCREEK C
Solar/Wind Harmer
0.246
213561DLWR9-10
Adder
3.655
213561DLWR9-10
Adder
2.795
219610FLORENCE C
Solar/Wind Harmer
1.424
219224BRL12CT4
Adder
9.177
20720728JCB_W1-129
Solar/Wind Harmer
0.303
20715028HAN_X4-015
Solar/Wind Harmer
0.303
213611FALLS1-3
Adder
3.59
213611FALLS1-3
Adder
3.59
207487AE2-000G4
Solar/Wind Harmer
31.924
207497AE2-000G2
Solar/Wind Harmer
31.924
207500AE2-000G1
Solar/Wind Harmer
31.924
207507AE2-000G3
Solar/Wind Harmer
31.924
963401AG1-189 GEN
Solar/Wind Harmer
2.3
970025AG2-016 GEN
Solar/Wind Harmer
2.863
971189AH1-054 GEN
Solar/Wind Harmer
1.191
207445AB1-138_GEN
Solar/Wind Harmer
0.582
219620RIDERU C
Solar/Wind Harmer
0.055
20714428HOW_X1-037
Solar/Wind Harmer
1.224
20720628TIN_W1-124
Solar/Wind Harmer
0.984
20716228APLW2-078
Solar/Wind Harmer
0.873
971521AH1-258 GEN
Solar/Wind Harmer
2.666
20635928PARLN3&4
Adder
7.209
218526CNTRALGAS2 C
Solar/Wind Harmer
0.358
20675528CPH_W2-050
Solar/Wind Harmer
0.552
20673828FLE_V3-070
Solar/Wind Harmer
0.447
218449LINSOLAR C
Solar/Wind Harmer
0.962
20676128MHD_W3-029
Solar/Wind Harmer
0.456
20676428JCR_X2-075
Solar/Wind Harmer
0.326
217167KRNY_14
Adder
8.809
217086KRNY_131
Adder
8.734
217147KRNY_1212
Adder
8.379
217147KRNY_1212
Adder
8.229
217146KRNY_1234
Adder
8.211
217146KRNY_1234
Adder
8.155
964851AG1-348 GEN
Solar/Wind Harmer
1.239
971009AG2-626 GEN
Solar/Wind Harmer
1.485
207408W3-077 C
Solar/Wind Harmer
0.457
20675128HRM_W1-127
Solar/Wind Harmer
0.152
20462827N BANGR8
Adder
0.642
961261AF2-417 GEN
Solar/Wind Harmer
0.833
209026WIENIPP4
Adder
4.329
209029WAYMART-WD
Solar/Wind Harmer
2.08
200201DELTA2 CT2
50/50
4.382
200034PCHBTM 2
50/50
25.537
200035PCHBTM 3
50/50
24.86
200205Y1-065-CTG2
50/50
4.985
233971AC1-093 C
Solar/Wind Harmer
3.335
232899W1-062
Adder
12.57
232410W1-006 C
Solar/Wind Harmer
1.305
232918OH NUG7
Adder
11.457
232905CHERITON_25
Adder
3.204
232926CRISFLD1
Adder
2.563
231940T-011
Adder
0.974
234015AF2-250 C
Solar/Wind Harmer
0.157
232428Y3-058 C
Solar/Wind Harmer
1.087
233994AC2-023 GEN
Solar/Wind Harmer
3.503
233946AB2-136 GEN
Solar/Wind Harmer
5.195
233952AC2-187 GEN
Solar/Wind Harmer
1.465
233954AC2-188 GEN
Solar/Wind Harmer
1.465
234036AF2-325 C
Solar/Wind Harmer
1.194
234041AC1-190 GEN
Solar/Wind Harmer
11.66
232910NRG_G1
Adder
11.179
233984AB2-036 GEN
Solar/Wind Harmer
16.053
232424Y1-079 C
Solar/Wind Harmer
0.724
234014AF1-036_GEN
Solar/Wind Harmer
3.47
232436AB1-176 C
Solar/Wind Harmer
0.293
233930AB2-032 GEN
Solar/Wind Harmer
1.061
233982AB2-133 GEN
Solar/Wind Harmer
6.2
228251CARLLS#4
Adder
0.688
228201CARL#2CT
Adder
7.495
228200CARL#1CT
Adder
7.128
230433AD2-135 GEN
Solar/Wind Harmer
0.11
228351V2-046C
Solar/Wind Harmer
2.184
230511AF1-262
Solar/Wind Harmer
0.198
228754AB1-001 C
Solar/Wind Harmer
0.15
228307PCLP GT
Adder
13.029
972233AH1-701 GEN
Adder
4.494
219272CLEANLIGHT C
Solar/Wind Harmer
0.192
219287REEVESEAST C
Solar/Wind Harmer
1.412
219904AC1-010 C
Solar/Wind Harmer
0.396
219912AD2-042 GEN
Solar/Wind Harmer
0.831
213589EDDYSTN4
Adder
82.978
213587EDDYSTN3
Adder
82.967
219906AC1-017 C
Solar/Wind Harmer
0.23
219607WPEMNERT C
Solar/Wind Harmer
0.431
219304NAMERICA C
Solar/Wind Harmer
0.319
213535CROYDN11
Adder
10.504
213815MOSER1-3
Adder
3.619
213815MOSER1-3
Adder
3.619
20720828JCB_W4-025
Solar/Wind Harmer
0.46
214067T20SOLAR
Solar/Wind Harmer
0.257
20636128O CRK C2
Adder
6.531
207459AE1-142 C O1
Solar/Wind Harmer
1.062
20628028LAKEHURS
Adder
0.956
20714828MDF_W3-079
Solar/Wind Harmer
0.305
219817TRENTONSOL C
Solar/Wind Harmer
1.092
20641628MLH_W1-032
Solar/Wind Harmer
0.29
20742028HF_AC1-207
Solar/Wind Harmer
0.773
217197RE CRAN C
Solar/Wind Harmer
0.526
218438BLK ROCK C
Solar/Wind Harmer
0.133
924131AB2-057 GEN
Solar/Wind Harmer
1
20635028RRCT1&2
Adder
11.271
20635128RRCT3&4
Adder
10.88
20635128RRCT3&4
Adder
9.49
218418LINDEN_G5
Adder
16.503
218419LINDEN_G6
Adder
16.503
972260AH1-715 GEN1
Adder
13.215
219036LINDEN_G7
Adder
15.995
219035LINDEN_G8
Adder
15.767
972261AH1-715 GEN2
Adder
15.311
20675428EAM_W2-061
Solar/Wind Harmer
0.18
217081WEATEXAS C
Solar/Wind Harmer
0.082
217202FBANKSOLAR C
Solar/Wind Harmer
0.07
217201HACKENSOLA C
Solar/Wind Harmer
0.069
972237AH1-703 GEN
Adder
9.591
217206BARNGR HS C
Solar/Wind Harmer
0.029
217086KRNY_131
Adder
8.828
217083KRNY_132
Adder
8.753
217204WCALDSOLAR C
Solar/Wind Harmer
0.069
20674328GAR_V4-001
Solar/Wind Harmer
0.101
20674828DL_W4-046
Solar/Wind Harmer
0.588
207471AF2-354 C
Solar/Wind Harmer
0.465
20634528N27_Y2-018
Solar/Wind Harmer
0.244
20675928HOL_W4-097
Solar/Wind Harmer
0.117
20465127PORT CT
Adder
3.578
209010PEIP 1
Adder
2.848
209010PEIP 1
Adder
0.417
961541AF2-445A GEN
Solar/Wind Harmer
2.513
961431AF2-434 GEN
Solar/Wind Harmer
0.751
20465527S.RDG CT
Adder
1.984
946751AF1-339 GEN
Solar/Wind Harmer
0.717
209130AF1-271A GEN
Solar/Wind Harmer
2.009
223401AF1-299 GEN
Solar/Wind Helper
0.631
223402AF1-300 C
Solar/Wind Helper
0.631
200192DELTA CT1
50/50
2.449
200194DELTA CT3
50/50
2.449
200204Y1-065-CTG1
50/50
4.985
200054ROCKSP 3
50/50
3.173
232901NORTHST
Adder
10.904
233970AC1-092 C
Solar/Wind Harmer
3.512
232900DEMECSMY
Adder
12.056
234033AF1-007_GEN
Solar/Wind Harmer
48.601
972177AH1-672 GEN
Solar/Wind Harmer
17.548
232404W1-003 C
Solar/Wind Harmer
1.305
232408W1-005 C
Solar/Wind Harmer
1.305
232917OH NUG6
Adder
11.483
232915OH NUG4
Adder
11.457
233996TM1833_GEN
Solar/Wind Harmer
1.301
233998TM1NIN_3.36
Solar/Wind Harmer
1.301
232919VN10
Adder
3.66
232426Y1-080 FULL
Solar/Wind Harmer
0.249
232902EASTMUNI
Adder
16.888
234012AE2-112_GEN
Solar/Wind Harmer
2.949
972251AH1-710 GEN
Adder
57.346
233944AB2-135 GEN
Solar/Wind Harmer
6.685
233918AB1-142 GEN
Solar/Wind Harmer
1.261
231918WEST 1
Adder
4.124
231917EM10
Adder
2.87
228206SHRMN CT
Adder
18.159
228732V1-021 C
Adder
0.207
228260V4-054C
Solar/Wind Harmer
1.119
970997AG2-616 GEN
Solar/Wind Harmer
10.417
228729W2-030 C
Solar/Wind Harmer
0.624
228400MICK 1CT
Adder
12.634
219686LUMSOLAR_N C
Solar/Wind Harmer
0.212
219766PARADISE C
Solar/Wind Harmer
0.33
213497CHSTR7-9
Adder
2.845
213497CHSTR7-9
Adder
2.845
219907AC1-030 C
Solar/Wind Harmer
0.144
213958STHWK5-6
Adder
2.807
213560DLW11-12
Adder
2.795
219348LDSOLAR C
Solar/Wind Harmer
0.615
219222BRL12CT2
Adder
9.177
20716028EGP_W2-019
Solar/Wind Harmer
0.471
207522AF2-254 C
Solar/Wind Harmer
1.457
213611FALLS1-3
Adder
3.59
20717128DIX_Z2-102
Solar/Wind Harmer
1.339
20715828PEM_W1-120
Solar/Wind Harmer
0.541
214194N WALES4
Adder
0.859
963711AG1-223 GEN
Solar/Wind Harmer
1.478
20714528FRN_Y2-051
Solar/Wind Harmer
0.294
219276PARKLANDSO C
Solar/Wind Harmer
0.458
20715228NPK_W1-113
Solar/Wind Harmer
0.425
20720528MAN_W1-024
Solar/Wind Harmer
0.251
219680HOPEWELLV C1
Solar/Wind Harmer
0.075
20720428HOL_W1-112
Solar/Wind Harmer
0.34
20635828PARLN1&2
Adder
7.209
20635028RRCT1&2
Adder
11.447
218524CNTRALGAS1 C
Solar/Wind Harmer
0.357
218440SUMMTASSOC C
Solar/Wind Harmer
0.124
218428ETC SOLAR C
Solar/Wind Harmer
0.035
219908AB1-139 C
Solar/Wind Harmer
0.367
219919AE1-041 FULL
Solar/Wind Harmer
0.039
972275AH1-722 GEN
Adder
30.338
20673628F1S_V4-069
Solar/Wind Harmer
0.171
207528AF2-192 GEN
Solar/Wind Harmer
1.214
217209CENTRL HS C
Solar/Wind Harmer
0.042
217186ESSEX_G9
Adder
3.741
217121ECCF
Adder
0.412
217083KRNY_132
Adder
8.809
217208PARK ELE C
Solar/Wind Harmer
0.024
20671828STAW2-080
Solar/Wind Harmer
0.099
20676728BRNX1-095
Solar/Wind Harmer
0.165
966261AG1-495 GEN
Solar/Wind Harmer
3.255
207439AE1-081 C O1
Solar/Wind Harmer
0.055
20676328BVR_Y1-020
Solar/Wind Harmer
0.305
20674628WNG_W3-110
Solar/Wind Harmer
0.371
20676228FRD_X1-012
Solar/Wind Harmer
0.543
207530AG1-191 GEN
Solar/Wind Harmer
1.263
20675828AU_W4-064
Solar/Wind Harmer
0.158
20674928WA_W3-044
Solar/Wind Harmer
0.438
971519AH1-257 GEN
Solar/Wind Harmer
2.282
20675728RH_W2-091
Solar/Wind Harmer
0.544
207518AF1-320_GEN
Solar/Wind Harmer
3.296
207484AF2-139 C O1
Solar/Wind Harmer
0.455
20465127PORT CT
Adder
2.696
208909MACR G3
Adder
141.49
209027LOR2_Q27
Solar/Wind Harmer
3.497
212266LOR1
Solar/Wind Harmer
0.927
20486527WR_V4-052
Adder
0.793
209054AE2-059 GEN
Solar/Wind Harmer
1.228
208862AG1-362 C
Solar/Wind Harmer
0.591
959431AF2-234 GEN
Solar/Wind Harmer
1.429
964051AG1-259 GEN
Solar/Wind Harmer
0.958
964061AG1-260 GEN
Solar/Wind Harmer
0.958
959421AF2-233 GEN
Solar/Wind Harmer
0.715
226929AD2-058 GEN
Solar/Wind Helper
0.117
211065PSPA IPP
Solar/Wind Harmer
0.389
961301AF2-421 GEN
Solar/Wind Harmer
0.812
963151AG1-164 GEN
Solar/Wind Harmer
0.812
209023WIENIPP1
Adder
8.76
209025WIENIPP3
Adder
4.373
963071AG1-156 GEN
Solar/Wind Harmer
8.001
209010PEIP 1
Adder
0.518
961341AF2-425 GEN
Solar/Wind Harmer
0.754
20465527S.RDG CT
Adder
2.051
212507AE2-042_GEN
Solar/Wind Harmer
2.178
946731AF1-337 GEN
Solar/Wind Harmer
0.717
209018SUNBIPCT
Adder
5.322
208835TUHI V3-051
Solar/Wind Helper
0.023
200200DELTA2 CT1
50/50
4.382
200193DELTA CT2
50/50
2.449
200203Y1-065-STG
50/50
8.633
200055ROCKSP 4
50/50
3.118
233973AC2-185 C
Solar/Wind Harmer
7.095
970695AG2-447 GEN
Solar/Wind Harmer
4.694
233939AC1-091 C
Solar/Wind Harmer
3.512
233972AC1-094 C
Solar/Wind Harmer
2.82
232434Z2-077 GEN
Solar/Wind Harmer
0.327
233987AB2-037 GEN
Solar/Wind Harmer
14.851
232406W1-004 FULL
Solar/Wind Harmer
1.305
232914OH NUG3
Adder
11.534
232916OH NUG5
Adder
11.534
232921TASLEY2G
Adder
6.741
233923SMA
Solar/Wind Harmer
4.771
233997TMININ_4.2
Solar/Wind Harmer
1.301
232907VN8
Adder
39.19
233964AF2-378 GEN
Solar/Wind Harmer
0.166
233950AC2-186 GEN
Solar/Wind Harmer
0.732
232417X3-008 C
Solar/Wind Harmer
1.464
232422X3-066 FULL
Solar/Wind Harmer
0.32
233933AB2-153 GEN
Solar/Wind Harmer
1.433
233935AB2-179 C
Solar/Wind Harmer
3.091
228711V2-041C
Solar/Wind Harmer
0.658
230415AB2-049 C
Solar/Wind Harmer
0.205
219623KINSLEYBEA C
Solar/Wind Harmer
0.451
219291REEVESSOUT C
Solar/Wind Harmer
0.063
218660EHAMPSOLAR C
Solar/Wind Harmer
0.184
219921AF1-264
Solar/Wind Harmer
0.152
219688LUMSOLAR_S C
Solar/Wind Harmer
0.212
213497CHSTR7-9
Adder
2.845
219914AD2-027 C
Solar/Wind Harmer
0.627
219236SOUTHERNHQ C
Solar/Wind Harmer
0.07
213958STHWK5-6
Adder
2.807
213560DLW11-12
Adder
2.795
219221BRL12CT1
Adder
9.177
219223BRL12CT3
Adder
9.177
213815MOSER1-3
Adder
3.619
20716428NHV_W2-082
Solar/Wind Harmer
1.805
20715728PEM_W1-119
Solar/Wind Harmer
0.541
959561AF2-247 GEN
Solar/Wind Harmer
0.492
20636028O CRK C1
Adder
7.163
963391AG1-188 GEN
Solar/Wind Harmer
3.787
20714928UPF_X1-085
Solar/Wind Harmer
0.41
971667AH1-334 GEN
Solar/Wind Harmer
2.766
219114HARTZY_C
Solar/Wind Harmer
0.836
219727YARDVSOLFA C
Solar/Wind Harmer
0.91
207454AA2-184 E
Solar/Wind Harmer
0.988
219918AC2-009 C
Solar/Wind Harmer
0.025
219612MATRIX C
Solar/Wind Harmer
0.18
20716928W4-060COL
Solar/Wind Harmer
0.696
20635828PARLN1&2
Adder
3.265
20635928PARLN3&4
Adder
3.265
217213AMBOY SO C
Solar/Wind Harmer
0.122
219249CENTRALDIV C
Solar/Wind Harmer
0.038
207442AE1-156 GEN
Solar/Wind Harmer
0.71
20673728F2S_V4-070
Solar/Wind Harmer
0.171
217211CAMDEN ST C
Solar/Wind Harmer
0.023
217169METRODIV C
Solar/Wind Harmer
0.038
217194REDH C
Solar/Wind Harmer
0.466
20674528F3S_W2-016
Solar/Wind Harmer
1.322
207510AF2-138 C
Solar/Wind Harmer
1.637
207511W3-106 GEN
Solar/Wind Harmer
0.304
971007AG2-625 GEN
Solar/Wind Harmer
2.328
207437AD2-070 GEN
Solar/Wind Harmer
0.271
20466127PORT 5CT
Adder
23.797
20671928W4-073
Solar/Wind Harmer
0.388
20674128FR_U2-059
Solar/Wind Harmer
0.165
20633028GILCT9
Adder
25.303
20465427SHAW CT
Adder
3.442
209116AE2-175 GEN
Solar/Wind Harmer
3.595
211065PSPA IPP
Solar/Wind Harmer
0.389
963161AG1-165 GEN
Solar/Wind Harmer
0.812
209025WIENIPP3
Adder
4.284
970095AG2-074 GEN
Solar/Wind Harmer
5.068
208972BECR K09
Solar/Wind Harmer
0.844
961331AF2-424 GEN
Solar/Wind Harmer
0.754
961421AF2-433 GEN
Solar/Wind Harmer
0.751
957921AF2-086 GEN
Solar/Wind Harmer
0.73
209142AF1-226 GEN
Solar/Wind Harmer
4.349
209093AE2-110 GEN
Solar/Wind Harmer
1.878
209120AE2-241 GEN
Solar/Wind Harmer
2.485
205941AD2-115 GEN
Solar/Wind Harmer
0.676
946691AF1-333 GEN
Solar/Wind Harmer
0.717
946741AF1-338 GEN
Solar/Wind Harmer
0.717
209071AE2-133 GEN
Solar/Wind Harmer
1.209
226910AB2-157 C
Solar/Wind Helper
0.018
227287AC2-120 GEN
Solar/Wind Helper
0.427
208835TUHI V3-051
Solar/Wind Helper
0.023
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.265
VTFLTFEXP_VFT->PJM
CMTX
128.779
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.521
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.566
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.109
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.753
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
49.782
CBM NorthLTFEXP_CBM-N->PJM
CBM
66.182
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PL_05_P71_000906_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PL_05_P71_000906_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.19 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:3771.64
MW Contribution:
4.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200201DELTA2 CT2
50/50
4.356
200034PCHBTM 2
50/50
25.385
200035PCHBTM 3
50/50
24.719
200205Y1-065-CTG2
50/50
4.954
233971AC1-093 C
Solar/Wind Harmer
3.308
232899W1-062
Adder
12.467
232410W1-006 C
Solar/Wind Harmer
1.295
232918OH NUG7
Adder
11.362
232905CHERITON_25
Adder
3.177
232926CRISFLD1
Adder
2.541
231940T-011
Adder
0.966
234015AF2-250 C
Solar/Wind Harmer
0.156
232428Y3-058 C
Solar/Wind Harmer
1.078
233994AC2-023 GEN
Solar/Wind Harmer
3.474
233946AB2-136 GEN
Solar/Wind Harmer
5.151
233952AC2-187 GEN
Solar/Wind Harmer
1.453
233954AC2-188 GEN
Solar/Wind Harmer
1.453
234036AF2-325 C
Solar/Wind Harmer
1.183
234041AC1-190 GEN
Solar/Wind Harmer
11.561
232910NRG_G1
Adder
11.082
233984AB2-036 GEN
Solar/Wind Harmer
15.908
232424Y1-079 C
Solar/Wind Harmer
0.717
234014AF1-036_GEN
Solar/Wind Harmer
3.437
232436AB1-176 C
Solar/Wind Harmer
0.29
233930AB2-032 GEN
Solar/Wind Harmer
1.051
233982AB2-133 GEN
Solar/Wind Harmer
6.14
228251CARLLS#4
Adder
0.683
228201CARL#2CT
Adder
7.443
228200CARL#1CT
Adder
7.079
230433AD2-135 GEN
Solar/Wind Harmer
0.109
228351V2-046C
Solar/Wind Harmer
2.168
230511AF1-262
Solar/Wind Harmer
0.197
228754AB1-001 C
Solar/Wind Harmer
0.149
228307PCLP GT
Adder
12.936
972233AH1-701 GEN
Adder
4.462
219272CLEANLIGHT C
Solar/Wind Harmer
0.191
219287REEVESEAST C
Solar/Wind Harmer
1.403
219904AC1-010 C
Solar/Wind Harmer
0.394
219912AD2-042 GEN
Solar/Wind Harmer
0.825
213589EDDYSTN4
Adder
82.148
213587EDDYSTN3
Adder
82.138
219906AC1-017 C
Solar/Wind Harmer
0.229
219607WPEMNERT C
Solar/Wind Harmer
0.428
219304NAMERICA C
Solar/Wind Harmer
0.317
213535CROYDN11
Adder
10.435
213815MOSER1-3
Adder
3.593
213815MOSER1-3
Adder
3.593
20720828JCB_W4-025
Solar/Wind Harmer
0.457
214067T20SOLAR
Solar/Wind Harmer
0.255
20636128O CRK C2
Adder
6.497
207459AE1-142 C O1
Solar/Wind Harmer
1.056
20628028LAKEHURS
Adder
0.952
20714828MDF_W3-079
Solar/Wind Harmer
0.304
219817TRENTONSOL C
Solar/Wind Harmer
1.087
20641628MLH_W1-032
Solar/Wind Harmer
0.289
20742028HF_AC1-207
Solar/Wind Harmer
0.77
217197RE CRAN C
Solar/Wind Harmer
0.523
218438BLK ROCK C
Solar/Wind Harmer
0.133
924131AB2-057 GEN
Solar/Wind Harmer
0.996
20635028RRCT1&2
Adder
11.229
20635128RRCT3&4
Adder
10.839
20635128RRCT3&4
Adder
9.455
218418LINDEN_G5
Adder
16.449
218419LINDEN_G6
Adder
16.449
972260AH1-715 GEN1
Adder
13.171
219036LINDEN_G7
Adder
15.946
219035LINDEN_G8
Adder
15.719
972261AH1-715 GEN2
Adder
15.265
20675428EAM_W2-061
Solar/Wind Harmer
0.18
217081WEATEXAS C
Solar/Wind Harmer
0.082
217202FBANKSOLAR C
Solar/Wind Harmer
0.07
217201HACKENSOLA C
Solar/Wind Harmer
0.069
972237AH1-703 GEN
Adder
9.566
217206BARNGR HS C
Solar/Wind Harmer
0.029
217086KRNY_131
Adder
8.805
217083KRNY_132
Adder
8.73
217204WCALDSOLAR C
Solar/Wind Harmer
0.069
20674328GAR_V4-001
Solar/Wind Harmer
0.101
20674828DL_W4-046
Solar/Wind Harmer
0.587
207471AF2-354 C
Solar/Wind Harmer
0.465
20634528N27_Y2-018
Solar/Wind Harmer
0.244
20675928HOL_W4-097
Solar/Wind Harmer
0.117
20465127PORT CT
Adder
3.576
209010PEIP 1
Adder
2.868
209010PEIP 1
Adder
0.42
961541AF2-445A GEN
Solar/Wind Harmer
2.543
961431AF2-434 GEN
Solar/Wind Harmer
0.762
946751AF1-339 GEN
Solar/Wind Harmer
0.73
209130AF1-271A GEN
Solar/Wind Harmer
2.045
20465527S.RDG CT
Adder
1.876
223401AF1-299 GEN
Solar/Wind Helper
0.683
223402AF1-300 C
Solar/Wind Helper
0.683
200202DELTA2 ST
50/50
7.377
200195DELTA ST
50/50
3.76
200052ROCKSP 1
50/50
3.117
200053ROCKSP 2
50/50
3.056
232904IR4
Adder
104.776
232920IR10
Adder
4.095
232432Z2-076 GEN
Solar/Wind Harmer
0.171
233901CHERRYDALE C
Solar/Wind Harmer
1.456
232912OH NUG1
Adder
11.438
232913OH NUG2
Adder
11.285
233940AF2-379 C
Solar/Wind Harmer
0.241
971195AH1-057 GEN
Solar/Wind Harmer
1.262
233955AB2-172 GEN
Solar/Wind Harmer
6.451
232813VAUGHN
Adder
0.757
231906DC3 NUG
Adder
17.779
231902DC CT7
Adder
14.214
231907DC10
Adder
4.439
233968AD2-076_GEN
Solar/Wind Harmer
8.422
970597AG2-380 GEN
Solar/Wind Harmer
5.288
233915AB1-141 GEN
Solar/Wind Harmer
1.249
231919CHRIST1
Adder
5.371
231920CHRIST2
Adder
5.251
970453AG2-297 GEN
Solar/Wind Harmer
3.013
230422AE1-104_GEN1
Solar/Wind Harmer
36.397
230425AE1-104_GEN2
Solar/Wind Harmer
36.397
972141AH1-641 GEN
Solar/Wind Harmer
3.103
230430AE1-229_GEN
Solar/Wind Harmer
30.864
964001AG1-254 GEN
Solar/Wind Harmer
7.847
228728W1-130C
Solar/Wind Harmer
0.714
227927V4-067C
Solar/Wind Harmer
0.213
230407AD2-065 C
Solar/Wind Harmer
0.141
230434AG1-499 GEN
Solar/Wind Harmer
0.62
219137THOSOLAR C
Solar/Wind Harmer
1.27
219258KINSLEYDEP C
Solar/Wind Harmer
0.338
219615MILLCREEK C
Solar/Wind Harmer
0.245
213957STHWK3-4
Adder
2.781
213957STHWK3-4
Adder
2.781
213942SCHUYLKILL
Adder
3.637
213942SCHUYLKILL
Adder
2.781
219610FLORENCE C
Solar/Wind Harmer
1.414
219224BRL12CT4
Adder
9.118
213561DLWR9-10
Adder
3.625
213561DLWR9-10
Adder
2.772
20720728JCB_W1-129
Solar/Wind Harmer
0.301
20715028HAN_X4-015
Solar/Wind Harmer
0.301
213611FALLS1-3
Adder
3.567
213611FALLS1-3
Adder
3.567
207487AE2-000G4
Solar/Wind Harmer
31.757
207497AE2-000G2
Solar/Wind Harmer
31.757
207500AE2-000G1
Solar/Wind Harmer
31.757
207507AE2-000G3
Solar/Wind Harmer
31.757
963401AG1-189 GEN
Solar/Wind Harmer
2.288
970025AG2-016 GEN
Solar/Wind Harmer
2.848
971189AH1-054 GEN
Solar/Wind Harmer
1.185
207445AB1-138_GEN
Solar/Wind Harmer
0.579
219620RIDERU C
Solar/Wind Harmer
0.055
20714428HOW_X1-037
Solar/Wind Harmer
1.218
20720628TIN_W1-124
Solar/Wind Harmer
0.98
20716228APLW2-078
Solar/Wind Harmer
0.869
971521AH1-258 GEN
Solar/Wind Harmer
2.655
20635928PARLN3&4
Adder
7.181
218526CNTRALGAS2 C
Solar/Wind Harmer
0.357
20675528CPH_W2-050
Solar/Wind Harmer
0.55
20673828FLE_V3-070
Solar/Wind Harmer
0.445
218449LINSOLAR C
Solar/Wind Harmer
0.959
20676128MHD_W3-029
Solar/Wind Harmer
0.454
20676428JCR_X2-075
Solar/Wind Harmer
0.325
217167KRNY_14
Adder
8.786
217086KRNY_131
Adder
8.711
217147KRNY_1212
Adder
8.357
217147KRNY_1212
Adder
8.208
217146KRNY_1234
Adder
8.189
217146KRNY_1234
Adder
8.133
964851AG1-348 GEN
Solar/Wind Harmer
1.237
971009AG2-626 GEN
Solar/Wind Harmer
1.483
207408W3-077 C
Solar/Wind Harmer
0.456
20675128HRM_W1-127
Solar/Wind Harmer
0.152
20462827N BANGR8
Adder
0.641
961261AF2-417 GEN
Solar/Wind Harmer
0.837
209026WIENIPP4
Adder
4.362
209029WAYMART-WD
Solar/Wind Harmer
2.095
209027LOR2_Q27
Solar/Wind Harmer
3.54
212266LOR1
Solar/Wind Harmer
0.938
209054AE2-059 GEN
Solar/Wind Harmer
1.249
959431AF2-234 GEN
Solar/Wind Harmer
1.454
964051AG1-259 GEN
Solar/Wind Harmer
0.975
964061AG1-260 GEN
Solar/Wind Harmer
0.975
959421AF2-233 GEN
Solar/Wind Harmer
0.727
20486527WR_V4-052
Adder
0.756
208862AG1-362 C
Solar/Wind Harmer
0.529
226929AD2-058 GEN
Solar/Wind Helper
0.121
200192DELTA CT1
50/50
2.434
200194DELTA CT3
50/50
2.434
200204Y1-065-CTG1
50/50
4.954
200054ROCKSP 3
50/50
3.153
233970AC1-092 C
Solar/Wind Harmer
3.484
232901NORTHST
Adder
10.817
232900DEMECSMY
Adder
11.959
234033AF1-007_GEN
Solar/Wind Harmer
48.199
972177AH1-672 GEN
Solar/Wind Harmer
17.404
232404W1-003 C
Solar/Wind Harmer
1.295
232408W1-005 C
Solar/Wind Harmer
1.295
232917OH NUG6
Adder
11.387
232915OH NUG4
Adder
11.362
233996TM1833_GEN
Solar/Wind Harmer
1.29
233998TM1NIN_3.36
Solar/Wind Harmer
1.29
232919VN10
Adder
3.629
232426Y1-080 FULL
Solar/Wind Harmer
0.247
232902EASTMUNI
Adder
16.739
972251AH1-710 GEN
Adder
56.95
234012AE2-112_GEN
Solar/Wind Harmer
2.922
233944AB2-135 GEN
Solar/Wind Harmer
6.622
233918AB1-142 GEN
Solar/Wind Harmer
1.249
231918WEST 1
Adder
4.082
231917EM10
Adder
2.841
228206SHRMN CT
Adder
18.037
228732V1-021 C
Adder
0.205
228260V4-054C
Solar/Wind Harmer
1.111
970997AG2-616 GEN
Solar/Wind Harmer
10.344
228729W2-030 C
Solar/Wind Harmer
0.62
228400MICK 1CT
Adder
12.543
219686LUMSOLAR_N C
Solar/Wind Harmer
0.211
219766PARADISE C
Solar/Wind Harmer
0.328
213497CHSTR7-9
Adder
2.817
213497CHSTR7-9
Adder
2.817
219907AC1-030 C
Solar/Wind Harmer
0.143
213958STHWK5-6
Adder
2.781
219348LDSOLAR C
Solar/Wind Harmer
0.611
219222BRL12CT2
Adder
9.118
213560DLW11-12
Adder
2.772
20716028EGP_W2-019
Solar/Wind Harmer
0.468
207522AF2-254 C
Solar/Wind Harmer
1.449
20717128DIX_Z2-102
Solar/Wind Harmer
1.332
213611FALLS1-3
Adder
3.567
20715828PEM_W1-120
Solar/Wind Harmer
0.538
214194N WALES4
Adder
0.853
963711AG1-223 GEN
Solar/Wind Harmer
1.471
20714528FRN_Y2-051
Solar/Wind Harmer
0.293
219276PARKLANDSO C
Solar/Wind Harmer
0.456
20715228NPK_W1-113
Solar/Wind Harmer
0.423
20720528MAN_W1-024
Solar/Wind Harmer
0.25
219680HOPEWELLV C1
Solar/Wind Harmer
0.075
20720428HOL_W1-112
Solar/Wind Harmer
0.339
20635828PARLN1&2
Adder
7.181
20635028RRCT1&2
Adder
11.405
218524CNTRALGAS1 C
Solar/Wind Harmer
0.356
218440SUMMTASSOC C
Solar/Wind Harmer
0.123
218428ETC SOLAR C
Solar/Wind Harmer
0.034
219908AB1-139 C
Solar/Wind Harmer
0.366
219919AE1-041 FULL
Solar/Wind Harmer
0.039
972275AH1-722 GEN
Adder
30.239
20673628F1S_V4-069
Solar/Wind Harmer
0.171
207528AF2-192 GEN
Solar/Wind Harmer
1.21
217209CENTRL HS C
Solar/Wind Harmer
0.042
217186ESSEX_G9
Adder
3.732
217121ECCF
Adder
0.41
217083KRNY_132
Adder
8.786
217208PARK ELE C
Solar/Wind Harmer
0.024
20671828STAW2-080
Solar/Wind Harmer
0.099
20676728BRNX1-095
Solar/Wind Harmer
0.164
966261AG1-495 GEN
Solar/Wind Harmer
3.245
207439AE1-081 C O1
Solar/Wind Harmer
0.055
20676328BVR_Y1-020
Solar/Wind Harmer
0.304
20674628WNG_W3-110
Solar/Wind Harmer
0.371
20676228FRD_X1-012
Solar/Wind Harmer
0.543
207530AG1-191 GEN
Solar/Wind Harmer
1.261
20675828AU_W4-064
Solar/Wind Harmer
0.158
20674928WA_W3-044
Solar/Wind Harmer
0.437
971519AH1-257 GEN
Solar/Wind Harmer
2.279
20675728RH_W2-091
Solar/Wind Harmer
0.543
207518AF1-320_GEN
Solar/Wind Harmer
3.291
207484AF2-139 C O1
Solar/Wind Harmer
0.454
20465127PORT CT
Adder
2.695
208909MACR G3
Adder
141.493
211065PSPA IPP
Solar/Wind Harmer
0.39
961301AF2-421 GEN
Solar/Wind Harmer
0.819
963151AG1-164 GEN
Solar/Wind Harmer
0.819
209023WIENIPP1
Adder
8.828
209025WIENIPP3
Adder
4.407
963071AG1-156 GEN
Solar/Wind Harmer
8.062
209010PEIP 1
Adder
0.522
961341AF2-425 GEN
Solar/Wind Harmer
0.764
212507AE2-042_GEN
Solar/Wind Harmer
2.213
946731AF1-337 GEN
Solar/Wind Harmer
0.73
209018SUNBIPCT
Adder
5.417
20465527S.RDG CT
Adder
1.939
200200DELTA2 CT1
50/50
4.356
200193DELTA CT2
50/50
2.434
200203Y1-065-STG
50/50
8.58
200055ROCKSP 4
50/50
3.099
233973AC2-185 C
Solar/Wind Harmer
7.039
970695AG2-447 GEN
Solar/Wind Harmer
4.656
233939AC1-091 C
Solar/Wind Harmer
3.484
233972AC1-094 C
Solar/Wind Harmer
2.798
232434Z2-077 GEN
Solar/Wind Harmer
0.324
233987AB2-037 GEN
Solar/Wind Harmer
14.725
232406W1-004 FULL
Solar/Wind Harmer
1.295
232914OH NUG3
Adder
11.438
232916OH NUG5
Adder
11.438
232921TASLEY2G
Adder
6.685
233923SMA
Solar/Wind Harmer
4.732
233997TMININ_4.2
Solar/Wind Harmer
1.29
232907VN8
Adder
38.859
233964AF2-378 GEN
Solar/Wind Harmer
0.165
233950AC2-186 GEN
Solar/Wind Harmer
0.726
232417X3-008 C
Solar/Wind Harmer
1.452
232422X3-066 FULL
Solar/Wind Harmer
0.317
233933AB2-153 GEN
Solar/Wind Harmer
1.419
233935AB2-179 C
Solar/Wind Harmer
3.057
228711V2-041C
Solar/Wind Harmer
0.654
230415AB2-049 C
Solar/Wind Harmer
0.204
219623KINSLEYBEA C
Solar/Wind Harmer
0.448
219291REEVESSOUT C
Solar/Wind Harmer
0.063
218660EHAMPSOLAR C
Solar/Wind Harmer
0.182
219921AF1-264
Solar/Wind Harmer
0.151
219688LUMSOLAR_S C
Solar/Wind Harmer
0.211
219914AD2-027 C
Solar/Wind Harmer
0.622
213497CHSTR7-9
Adder
2.817
219236SOUTHERNHQ C
Solar/Wind Harmer
0.07
213958STHWK5-6
Adder
2.781
219221BRL12CT1
Adder
9.118
219223BRL12CT3
Adder
9.118
213560DLW11-12
Adder
2.772
213815MOSER1-3
Adder
3.593
20716428NHV_W2-082
Solar/Wind Harmer
1.795
20715728PEM_W1-119
Solar/Wind Harmer
0.538
20636028O CRK C1
Adder
7.126
959561AF2-247 GEN
Solar/Wind Harmer
0.489
963391AG1-188 GEN
Solar/Wind Harmer
3.767
20714928UPF_X1-085
Solar/Wind Harmer
0.408
971667AH1-334 GEN
Solar/Wind Harmer
2.752
219114HARTZY_C
Solar/Wind Harmer
0.832
219727YARDVSOLFA C
Solar/Wind Harmer
0.905
207454AA2-184 E
Solar/Wind Harmer
0.983
219918AC2-009 C
Solar/Wind Harmer
0.025
219612MATRIX C
Solar/Wind Harmer
0.179
20716928W4-060COL
Solar/Wind Harmer
0.693
20635828PARLN1&2
Adder
3.253
20635928PARLN3&4
Adder
3.253
217213AMBOY SO C
Solar/Wind Harmer
0.121
219249CENTRALDIV C
Solar/Wind Harmer
0.038
207442AE1-156 GEN
Solar/Wind Harmer
0.707
20673728F2S_V4-070
Solar/Wind Harmer
0.171
217211CAMDEN ST C
Solar/Wind Harmer
0.023
217169METRODIV C
Solar/Wind Harmer
0.038
217194REDH C
Solar/Wind Harmer
0.465
20674528F3S_W2-016
Solar/Wind Harmer
1.317
207510AF2-138 C
Solar/Wind Harmer
1.635
207511W3-106 GEN
Solar/Wind Harmer
0.303
971007AG2-625 GEN
Solar/Wind Harmer
2.325
207437AD2-070 GEN
Solar/Wind Harmer
0.27
20466127PORT 5CT
Adder
23.789
20671928W4-073
Solar/Wind Harmer
0.387
20674128FR_U2-059
Solar/Wind Harmer
0.165
20633028GILCT9
Adder
25.259
20465427SHAW CT
Adder
3.444
209116AE2-175 GEN
Solar/Wind Harmer
3.601
211065PSPA IPP
Solar/Wind Harmer
0.39
963161AG1-165 GEN
Solar/Wind Harmer
0.819
209025WIENIPP3
Adder
4.317
970095AG2-074 GEN
Solar/Wind Harmer
5.106
208972BECR K09
Solar/Wind Harmer
0.851
961331AF2-424 GEN
Solar/Wind Harmer
0.764
961421AF2-433 GEN
Solar/Wind Harmer
0.762
957921AF2-086 GEN
Solar/Wind Harmer
0.74
209142AF1-226 GEN
Solar/Wind Harmer
4.408
209093AE2-110 GEN
Solar/Wind Harmer
1.904
209120AE2-241 GEN
Solar/Wind Harmer
2.519
205941AD2-115 GEN
Solar/Wind Harmer
0.678
946691AF1-333 GEN
Solar/Wind Harmer
0.73
946741AF1-338 GEN
Solar/Wind Harmer
0.73
209071AE2-133 GEN
Solar/Wind Harmer
1.231
226910AB2-157 C
Solar/Wind Helper
0.019
227287AC2-120 GEN
Solar/Wind Helper
0.44
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.341
VTFLTFEXP_VFT->PJM
CMTX
128.422
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.563
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.605
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.947
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.231
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
49.597
CBM NorthLTFEXP_CBM-N->PJM
CBM
66.353
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PL_04_P22_102290_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PL_04_P22_102290_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.6 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:3750.31
MW Contribution:
4.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
7.427
200195DELTA ST
50/50
3.786
200052ROCKSP 1
50/50
3.135
200053ROCKSP 2
50/50
3.074
232904IR4
Adder
104.911
232920IR10
Adder
4.1
232432Z2-076 GEN
Solar/Wind Harmer
0.171
233901CHERRYDALE C
Solar/Wind Harmer
1.458
232912OH NUG1
Adder
11.454
232913OH NUG2
Adder
11.301
233940AF2-379 C
Solar/Wind Harmer
0.242
971195AH1-057 GEN
Solar/Wind Harmer
1.264
233955AB2-172 GEN
Solar/Wind Harmer
6.462
232813VAUGHN
Adder
0.759
231906DC3 NUG
Adder
17.818
231902DC CT7
Adder
14.245
231907DC10
Adder
4.448
233968AD2-076_GEN
Solar/Wind Harmer
8.443
970597AG2-380 GEN
Solar/Wind Harmer
5.301
233915AB1-141 GEN
Solar/Wind Harmer
1.252
231919CHRIST1
Adder
5.38
231920CHRIST2
Adder
5.26
970453AG2-297 GEN
Solar/Wind Harmer
2.995
230422AE1-104_GEN1
Solar/Wind Harmer
36.14
230425AE1-104_GEN2
Solar/Wind Harmer
36.14
972141AH1-641 GEN
Solar/Wind Harmer
3.083
230430AE1-229_GEN
Solar/Wind Harmer
30.656
964001AG1-254 GEN
Solar/Wind Harmer
7.794
228728W1-130C
Solar/Wind Harmer
0.708
227927V4-067C
Solar/Wind Harmer
0.211
230407AD2-065 C
Solar/Wind Harmer
0.14
230434AG1-499 GEN
Solar/Wind Harmer
0.615
219137THOSOLAR C
Solar/Wind Harmer
1.26
219258KINSLEYDEP C
Solar/Wind Harmer
0.335
213942SCHUYLKILL
Adder
3.612
213942SCHUYLKILL
Adder
2.762
213957STHWK3-4
Adder
2.762
213957STHWK3-4
Adder
2.762
219615MILLCREEK C
Solar/Wind Harmer
0.242
213561DLWR9-10
Adder
3.592
213561DLWR9-10
Adder
2.747
219610FLORENCE C
Solar/Wind Harmer
1.399
219224BRL12CT4
Adder
9.019
20720728JCB_W1-129
Solar/Wind Harmer
0.297
20715028HAN_X4-015
Solar/Wind Harmer
0.297
213611FALLS1-3
Adder
3.524
213611FALLS1-3
Adder
3.524
207487AE2-000G4
Solar/Wind Harmer
31.35
207497AE2-000G2
Solar/Wind Harmer
31.35
207500AE2-000G1
Solar/Wind Harmer
31.35
207507AE2-000G3
Solar/Wind Harmer
31.35
963401AG1-189 GEN
Solar/Wind Harmer
2.258
970025AG2-016 GEN
Solar/Wind Harmer
2.811
971189AH1-054 GEN
Solar/Wind Harmer
1.169
207445AB1-138_GEN
Solar/Wind Harmer
0.571
219620RIDERU C
Solar/Wind Harmer
0.054
20714428HOW_X1-037
Solar/Wind Harmer
1.199
20720628TIN_W1-124
Solar/Wind Harmer
0.964
20716228APLW2-078
Solar/Wind Harmer
0.855
971521AH1-258 GEN
Solar/Wind Harmer
2.61
20635928PARLN3&4
Adder
7.047
218526CNTRALGAS2 C
Solar/Wind Harmer
0.35
20675528CPH_W2-050
Solar/Wind Harmer
0.537
20673828FLE_V3-070
Solar/Wind Harmer
0.434
218449LINSOLAR C
Solar/Wind Harmer
0.938
20676128MHD_W3-029
Solar/Wind Harmer
0.443
20676428JCR_X2-075
Solar/Wind Harmer
0.316
217167KRNY_14
Adder
8.575
217086KRNY_131
Adder
8.502
217147KRNY_1212
Adder
8.156
217147KRNY_1212
Adder
8.01
217146KRNY_1234
Adder
7.992
217146KRNY_1234
Adder
7.938
964851AG1-348 GEN
Solar/Wind Harmer
1.185
971009AG2-626 GEN
Solar/Wind Harmer
1.42
207408W3-077 C
Solar/Wind Harmer
0.435
20462827N BANGR8
Adder
0.613
20675128HRM_W1-127
Solar/Wind Harmer
0.145
961261AF2-417 GEN
Solar/Wind Harmer
0.807
209026WIENIPP4
Adder
4.193
209029WAYMART-WD
Solar/Wind Harmer
2.022
209027LOR2_Q27
Solar/Wind Harmer
3.393
212266LOR1
Solar/Wind Harmer
0.899
209054AE2-059 GEN
Solar/Wind Harmer
1.196
959431AF2-234 GEN
Solar/Wind Harmer
1.392
964051AG1-259 GEN
Solar/Wind Harmer
0.933
964061AG1-260 GEN
Solar/Wind Harmer
0.933
959421AF2-233 GEN
Solar/Wind Harmer
0.696
226929AD2-058 GEN
Solar/Wind Helper
0.115
200201DELTA2 CT2
50/50
4.386
200034PCHBTM 2
50/50
25.558
200035PCHBTM 3
50/50
24.877
200205Y1-065-CTG2
50/50
4.983
233971AC1-093 C
Solar/Wind Harmer
3.311
232899W1-062
Adder
12.48
232410W1-006 C
Solar/Wind Harmer
1.296
232918OH NUG7
Adder
11.377
232905CHERITON_25
Adder
3.182
232926CRISFLD1
Adder
2.545
231940T-011
Adder
0.967
234015AF2-250 C
Solar/Wind Harmer
0.156
232428Y3-058 C
Solar/Wind Harmer
1.08
233994AC2-023 GEN
Solar/Wind Harmer
3.479
233946AB2-136 GEN
Solar/Wind Harmer
5.159
234036AF2-325 C
Solar/Wind Harmer
1.185
233952AC2-187 GEN
Solar/Wind Harmer
1.455
233954AC2-188 GEN
Solar/Wind Harmer
1.455
234041AC1-190 GEN
Solar/Wind Harmer
11.58
232910NRG_G1
Adder
11.1
233984AB2-036 GEN
Solar/Wind Harmer
15.943
232424Y1-079 C
Solar/Wind Harmer
0.719
234014AF1-036_GEN
Solar/Wind Harmer
3.446
232436AB1-176 C
Solar/Wind Harmer
0.291
233930AB2-032 GEN
Solar/Wind Harmer
1.054
233982AB2-133 GEN
Solar/Wind Harmer
6.157
228251CARLLS#4
Adder
0.678
228201CARL#2CT
Adder
7.394
228200CARL#1CT
Adder
7.033
230433AD2-135 GEN
Solar/Wind Harmer
0.108
228351V2-046C
Solar/Wind Harmer
2.154
230511AF1-262
Solar/Wind Harmer
0.195
228754AB1-001 C
Solar/Wind Harmer
0.148
228307PCLP GT
Adder
12.846
972233AH1-701 GEN
Adder
4.43
219272CLEANLIGHT C
Solar/Wind Harmer
0.189
219287REEVESEAST C
Solar/Wind Harmer
1.39
219904AC1-010 C
Solar/Wind Harmer
0.39
213589EDDYSTN4
Adder
81.805
213587EDDYSTN3
Adder
81.794
219912AD2-042 GEN
Solar/Wind Harmer
0.818
219906AC1-017 C
Solar/Wind Harmer
0.226
219607WPEMNERT C
Solar/Wind Harmer
0.423
219304NAMERICA C
Solar/Wind Harmer
0.313
213535CROYDN11
Adder
10.321
213815MOSER1-3
Adder
3.555
213815MOSER1-3
Adder
3.555
20720828JCB_W4-025
Solar/Wind Harmer
0.451
214067T20SOLAR
Solar/Wind Harmer
0.252
20636128O CRK C2
Adder
6.414
207459AE1-142 C O1
Solar/Wind Harmer
1.042
20628028LAKEHURS
Adder
0.938
20714828MDF_W3-079
Solar/Wind Harmer
0.299
219817TRENTONSOL C
Solar/Wind Harmer
1.07
20641628MLH_W1-032
Solar/Wind Harmer
0.284
20742028HF_AC1-207
Solar/Wind Harmer
0.757
217197RE CRAN C
Solar/Wind Harmer
0.514
218438BLK ROCK C
Solar/Wind Harmer
0.13
924131AB2-057 GEN
Solar/Wind Harmer
0.978
20635028RRCT1&2
Adder
11.013
20635128RRCT3&4
Adder
10.631
20635128RRCT3&4
Adder
9.273
218418LINDEN_G5
Adder
16.104
218419LINDEN_G6
Adder
16.104
972260AH1-715 GEN1
Adder
12.895
219036LINDEN_G7
Adder
15.595
219035LINDEN_G8
Adder
15.372
972261AH1-715 GEN2
Adder
14.928
20675428EAM_W2-061
Solar/Wind Harmer
0.175
217081WEATEXAS C
Solar/Wind Harmer
0.08
217202FBANKSOLAR C
Solar/Wind Harmer
0.068
217201HACKENSOLA C
Solar/Wind Harmer
0.068
972237AH1-703 GEN
Adder
9.336
217206BARNGR HS C
Solar/Wind Harmer
0.028
217086KRNY_131
Adder
8.593
217083KRNY_132
Adder
8.52
217204WCALDSOLAR C
Solar/Wind Harmer
0.067
20674328GAR_V4-001
Solar/Wind Harmer
0.097
20674828DL_W4-046
Solar/Wind Harmer
0.563
207471AF2-354 C
Solar/Wind Harmer
0.445
20634528N27_Y2-018
Solar/Wind Harmer
0.233
20465127PORT CT
Adder
3.425
20675928HOL_W4-097
Solar/Wind Harmer
0.111
209010PEIP 1
Adder
2.769
209010PEIP 1
Adder
0.406
961541AF2-445A GEN
Solar/Wind Harmer
2.438
961431AF2-434 GEN
Solar/Wind Harmer
0.73
946751AF1-339 GEN
Solar/Wind Harmer
0.698
209130AF1-271A GEN
Solar/Wind Harmer
1.957
223401AF1-299 GEN
Solar/Wind Helper
0.609
223402AF1-300 C
Solar/Wind Helper
0.609
200192DELTA CT1
50/50
2.451
200194DELTA CT3
50/50
2.451
200204Y1-065-CTG1
50/50
4.983
200054ROCKSP 3
50/50
3.172
232901NORTHST
Adder
10.827
233970AC1-092 C
Solar/Wind Harmer
3.487
234033AF1-007_GEN
Solar/Wind Harmer
48.262
232900DEMECSMY
Adder
11.971
972177AH1-672 GEN
Solar/Wind Harmer
17.425
232404W1-003 C
Solar/Wind Harmer
1.296
232408W1-005 C
Solar/Wind Harmer
1.296
232917OH NUG6
Adder
11.403
232915OH NUG4
Adder
11.377
233996TM1833_GEN
Solar/Wind Harmer
1.292
233998TM1NIN_3.36
Solar/Wind Harmer
1.292
232919VN10
Adder
3.635
232426Y1-080 FULL
Solar/Wind Harmer
0.247
232902EASTMUNI
Adder
16.772
234012AE2-112_GEN
Solar/Wind Harmer
2.929
972251AH1-710 GEN
Adder
56.833
233944AB2-135 GEN
Solar/Wind Harmer
6.639
233918AB1-142 GEN
Solar/Wind Harmer
1.252
231918WEST 1
Adder
4.09
231917EM10
Adder
2.845
228206SHRMN CT
Adder
17.921
228732V1-021 C
Adder
0.204
228260V4-054C
Solar/Wind Harmer
1.104
970997AG2-616 GEN
Solar/Wind Harmer
10.275
228729W2-030 C
Solar/Wind Harmer
0.615
228400MICK 1CT
Adder
12.452
219686LUMSOLAR_N C
Solar/Wind Harmer
0.209
219766PARADISE C
Solar/Wind Harmer
0.325
213497CHSTR7-9
Adder
2.805
213497CHSTR7-9
Adder
2.805
219907AC1-030 C
Solar/Wind Harmer
0.142
213958STHWK5-6
Adder
2.762
213560DLW11-12
Adder
2.747
219348LDSOLAR C
Solar/Wind Harmer
0.604
219222BRL12CT2
Adder
9.019
20716028EGP_W2-019
Solar/Wind Harmer
0.463
207522AF2-254 C
Solar/Wind Harmer
1.43
213611FALLS1-3
Adder
3.524
20717128DIX_Z2-102
Solar/Wind Harmer
1.315
20715828PEM_W1-120
Solar/Wind Harmer
0.532
214194N WALES4
Adder
0.841
963711AG1-223 GEN
Solar/Wind Harmer
1.449
20714528FRN_Y2-051
Solar/Wind Harmer
0.289
219276PARKLANDSO C
Solar/Wind Harmer
0.449
20715228NPK_W1-113
Solar/Wind Harmer
0.416
20720528MAN_W1-024
Solar/Wind Harmer
0.246
219680HOPEWELLV C1
Solar/Wind Harmer
0.074
20720428HOL_W1-112
Solar/Wind Harmer
0.333
20635828PARLN1&2
Adder
7.047
20635028RRCT1&2
Adder
11.185
218524CNTRALGAS1 C
Solar/Wind Harmer
0.349
218440SUMMTASSOC C
Solar/Wind Harmer
0.121
218428ETC SOLAR C
Solar/Wind Harmer
0.034
219908AB1-139 C
Solar/Wind Harmer
0.358
219919AE1-041 FULL
Solar/Wind Harmer
0.038
972275AH1-722 GEN
Adder
29.605
20673628F1S_V4-069
Solar/Wind Harmer
0.167
207528AF2-192 GEN
Solar/Wind Harmer
1.179
217209CENTRL HS C
Solar/Wind Harmer
0.041
217186ESSEX_G9
Adder
3.642
217121ECCF
Adder
0.401
217083KRNY_132
Adder
8.575
217208PARK ELE C
Solar/Wind Harmer
0.023
20671828STAW2-080
Solar/Wind Harmer
0.096
20676728BRNX1-095
Solar/Wind Harmer
0.159
966261AG1-495 GEN
Solar/Wind Harmer
3.119
207439AE1-081 C O1
Solar/Wind Harmer
0.053
20676328BVR_Y1-020
Solar/Wind Harmer
0.294
20674628WNG_W3-110
Solar/Wind Harmer
0.358
20676228FRD_X1-012
Solar/Wind Harmer
0.524
20675828AU_W4-064
Solar/Wind Harmer
0.153
207530AG1-191 GEN
Solar/Wind Harmer
1.213
20674928WA_W3-044
Solar/Wind Harmer
0.419
971519AH1-257 GEN
Solar/Wind Harmer
2.178
207518AF1-320_GEN
Solar/Wind Harmer
3.142
20675728RH_W2-091
Solar/Wind Harmer
0.518
20465127PORT CT
Adder
2.581
207484AF2-139 C O1
Solar/Wind Harmer
0.431
208909MACR G3
Adder
135.411
211065PSPA IPP
Solar/Wind Harmer
0.375
961301AF2-421 GEN
Solar/Wind Harmer
0.787
963151AG1-164 GEN
Solar/Wind Harmer
0.787
209023WIENIPP1
Adder
8.486
209025WIENIPP3
Adder
4.236
963071AG1-156 GEN
Solar/Wind Harmer
7.764
209010PEIP 1
Adder
0.503
961341AF2-425 GEN
Solar/Wind Harmer
0.732
212507AE2-042_GEN
Solar/Wind Harmer
2.12
946731AF1-337 GEN
Solar/Wind Harmer
0.698
209018SUNBIPCT
Adder
5.184
200200DELTA2 CT1
50/50
4.386
200193DELTA CT2
50/50
2.451
200203Y1-065-STG
50/50
8.63
200055ROCKSP 4
50/50
3.117
233973AC2-185 C
Solar/Wind Harmer
7.044
970695AG2-447 GEN
Solar/Wind Harmer
4.66
233939AC1-091 C
Solar/Wind Harmer
3.487
233972AC1-094 C
Solar/Wind Harmer
2.8
232434Z2-077 GEN
Solar/Wind Harmer
0.324
233987AB2-037 GEN
Solar/Wind Harmer
14.75
232406W1-004 FULL
Solar/Wind Harmer
1.296
232914OH NUG3
Adder
11.454
232916OH NUG5
Adder
11.454
232921TASLEY2G
Adder
6.694
233923SMA
Solar/Wind Harmer
4.738
233997TMININ_4.2
Solar/Wind Harmer
1.292
232907VN8
Adder
38.919
233964AF2-378 GEN
Solar/Wind Harmer
0.165
233950AC2-186 GEN
Solar/Wind Harmer
0.727
232417X3-008 C
Solar/Wind Harmer
1.454
232422X3-066 FULL
Solar/Wind Harmer
0.318
233933AB2-153 GEN
Solar/Wind Harmer
1.423
233935AB2-179 C
Solar/Wind Harmer
3.07
228711V2-041C
Solar/Wind Harmer
0.65
230415AB2-049 C
Solar/Wind Harmer
0.202
219623KINSLEYBEA C
Solar/Wind Harmer
0.444
219291REEVESSOUT C
Solar/Wind Harmer
0.062
218660EHAMPSOLAR C
Solar/Wind Harmer
0.181
219921AF1-264
Solar/Wind Harmer
0.15
219688LUMSOLAR_S C
Solar/Wind Harmer
0.209
213497CHSTR7-9
Adder
2.805
219914AD2-027 C
Solar/Wind Harmer
0.617
219236SOUTHERNHQ C
Solar/Wind Harmer
0.069
213958STHWK5-6
Adder
2.762
213560DLW11-12
Adder
2.747
219221BRL12CT1
Adder
9.019
219223BRL12CT3
Adder
9.019
213815MOSER1-3
Adder
3.555
20716428NHV_W2-082
Solar/Wind Harmer
1.772
20715728PEM_W1-119
Solar/Wind Harmer
0.532
959561AF2-247 GEN
Solar/Wind Harmer
0.483
20636028O CRK C1
Adder
7.034
963391AG1-188 GEN
Solar/Wind Harmer
3.718
20714928UPF_X1-085
Solar/Wind Harmer
0.402
971667AH1-334 GEN
Solar/Wind Harmer
2.714
219114HARTZY_C
Solar/Wind Harmer
0.82
219727YARDVSOLFA C
Solar/Wind Harmer
0.893
207454AA2-184 E
Solar/Wind Harmer
0.967
219918AC2-009 C
Solar/Wind Harmer
0.025
219612MATRIX C
Solar/Wind Harmer
0.176
20716928W4-060COL
Solar/Wind Harmer
0.681
20635828PARLN1&2
Adder
3.192
20635928PARLN3&4
Adder
3.192
217213AMBOY SO C
Solar/Wind Harmer
0.119
219249CENTRALDIV C
Solar/Wind Harmer
0.037
207442AE1-156 GEN
Solar/Wind Harmer
0.69
20673728F2S_V4-070
Solar/Wind Harmer
0.167
217211CAMDEN ST C
Solar/Wind Harmer
0.023
217169METRODIV C
Solar/Wind Harmer
0.037
217194REDH C
Solar/Wind Harmer
0.454
20674528F3S_W2-016
Solar/Wind Harmer
1.273
207511W3-106 GEN
Solar/Wind Harmer
0.293
207510AF2-138 C
Solar/Wind Harmer
1.577
971007AG2-625 GEN
Solar/Wind Harmer
2.226
20466127PORT 5CT
Adder
22.85
207437AD2-070 GEN
Solar/Wind Harmer
0.257
20465427SHAW CT
Adder
3.313
20671928W4-073
Solar/Wind Harmer
0.368
20674128FR_U2-059
Solar/Wind Harmer
0.157
20633028GILCT9
Adder
23.798
209116AE2-175 GEN
Solar/Wind Harmer
3.463
211065PSPA IPP
Solar/Wind Harmer
0.375
963161AG1-165 GEN
Solar/Wind Harmer
0.787
209025WIENIPP3
Adder
4.15
970095AG2-074 GEN
Solar/Wind Harmer
4.917
208972BECR K09
Solar/Wind Harmer
0.82
961331AF2-424 GEN
Solar/Wind Harmer
0.732
961421AF2-433 GEN
Solar/Wind Harmer
0.73
957921AF2-086 GEN
Solar/Wind Harmer
0.71
209142AF1-226 GEN
Solar/Wind Harmer
4.226
209093AE2-110 GEN
Solar/Wind Harmer
1.825
209120AE2-241 GEN
Solar/Wind Harmer
2.415
946691AF1-333 GEN
Solar/Wind Harmer
0.698
946741AF1-338 GEN
Solar/Wind Harmer
0.698
209071AE2-133 GEN
Solar/Wind Harmer
1.178
205941AD2-115 GEN
Solar/Wind Harmer
0.506
226910AB2-157 C
Solar/Wind Helper
0.018
227287AC2-120 GEN
Solar/Wind Helper
0.417
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.168
VTFLTFEXP_VFT->PJM
CMTX
125.427
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.464
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.489
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.87
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.391
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
48.643
CBM NorthLTFEXP_CBM-N->PJM
CBM
64.461
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o BGE_P4_GRACETON_51_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.98 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:3831.94
MW Contribution:
7.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
5.467
200194DELTA CT3
50/50
5.467
200204Y1-065-CTG1
50/50
10.599
200054ROCKSP 3
50/50
6.746
231912HR6
50/50
2.885
231913HR7
50/50
2.885
233920W3-032A-CTG1
50/50
4.189
232901NORTHST
50/50
17.278
232917OH NUG6
50/50
18.199
232915OH NUG4
50/50
18.158
233970AC1-092 C
Solar/Wind Harmer
5.239
234033AF1-007_GEN
Solar/Wind Harmer
72.584
232404W1-003 C
Solar/Wind Harmer
1.95
232408W1-005 C
Solar/Wind Harmer
1.95
233996TM1833_GEN
Solar/Wind Harmer
1.944
233998TM1NIN_3.36
Solar/Wind Harmer
1.944
972177AH1-672 GEN
Solar/Wind Harmer
26.189
232900DEMECSMY
Adder
17.968
232919VN10
Adder
5.464
232426Y1-080 FULL
Solar/Wind Harmer
0.372
232902EASTMUNI
Adder
25.121
234012AE2-112_GEN
Solar/Wind Harmer
4.35
233944AB2-135 GEN
Solar/Wind Harmer
9.825
200202DELTA2 ST
50/50
16.568
200195DELTA ST
50/50
8.445
200052ROCKSP 1
50/50
6.668
200053ROCKSP 2
50/50
6.538
232616GEN FOOD
50/50
0.339
232904IR4
50/50
167.426
232920IR10
50/50
6.543
232912OH NUG1
50/50
18.28
232913OH NUG2
50/50
18.037
232432Z2-076 GEN
Solar/Wind Harmer
0.257
233901CHERRYDALE C
Solar/Wind Harmer
2.194
233940AF2-379 C
Solar/Wind Harmer
0.363
971195AH1-057 GEN
Solar/Wind Harmer
1.9
233955AB2-172 GEN
Solar/Wind Harmer
9.705
232813VAUGHN
Adder
1.135
233968AD2-076_GEN
Solar/Wind Harmer
12.54
970597AG2-380 GEN
Solar/Wind Harmer
7.874
231906DC3 NUG
Adder
26.227
231902DC CT7
Adder
20.967
231907DC10
Adder
6.548
233915AB1-141 GEN
Solar/Wind Harmer
1.852
231919CHRIST1
Adder
7.005
231920CHRIST2
Adder
6.849
970453AG2-297 GEN
Solar/Wind Harmer
3.222
230422AE1-104_GEN1
Solar/Wind Harmer
37.16
230425AE1-104_GEN2
Solar/Wind Harmer
37.16
972141AH1-641 GEN
Solar/Wind Harmer
3.086
227927V4-067C
Solar/Wind Harmer
0.213
230430AE1-229_GEN
Solar/Wind Harmer
30.611
964001AG1-254 GEN
Solar/Wind Harmer
7.709
228728W1-130C
Solar/Wind Harmer
0.702
230407AD2-065 C
Solar/Wind Harmer
0.136
230434AG1-499 GEN
Solar/Wind Harmer
0.588
219137THOSOLAR C
Solar/Wind Harmer
1.066
219258KINSLEYDEP C
Solar/Wind Harmer
0.274
207487AE2-000G4
Solar/Wind Harmer
24.242
207497AE2-000G2
Solar/Wind Harmer
24.242
207500AE2-000G1
Solar/Wind Harmer
24.242
207507AE2-000G3
Solar/Wind Harmer
24.242
20720728JCB_W1-129
Solar/Wind Harmer
0.226
20715028HAN_X4-015
Solar/Wind Harmer
0.226
963401AG1-189 GEN
Solar/Wind Harmer
1.719
219615MILLCREEK C
Solar/Wind Harmer
0.178
970025AG2-016 GEN
Solar/Wind Harmer
2.124
219610FLORENCE C
Solar/Wind Harmer
1.016
219224BRL12CT4
Adder
6.546
971189AH1-054 GEN
Solar/Wind Harmer
0.87
207445AB1-138_GEN
Solar/Wind Harmer
0.415
213611FALLS1-3
Adder
2.31
213611FALLS1-3
Adder
2.31
213942SCHUYLKILL
Adder
2.293
213942SCHUYLKILL
Adder
1.754
213957STHWK3-4
Adder
1.753
213957STHWK3-4
Adder
1.753
233918AB1-142 GEN
Solar/Wind Harmer
1.852
972251AH1-710 GEN
Adder
79.377
231918WEST 1
Adder
5.37
231917EM10
Adder
3.587
228206SHRMN CT
Adder
18.904
228732V1-021 C
Adder
0.214
228260V4-054C
Solar/Wind Harmer
1.13
228729W2-030 C
Solar/Wind Harmer
0.621
970997AG2-616 GEN
Solar/Wind Harmer
10.285
228400MICK 1CT
Adder
11.306
219686LUMSOLAR_N C
Solar/Wind Harmer
0.179
219766PARADISE C
Solar/Wind Harmer
0.258
219907AC1-030 C
Solar/Wind Harmer
0.107
213497CHSTR7-9
Adder
2.061
213497CHSTR7-9
Adder
2.061
20716028EGP_W2-019
Solar/Wind Harmer
0.352
207522AF2-254 C
Solar/Wind Harmer
1.087
20717128DIX_Z2-102
Solar/Wind Harmer
0.998
20715828PEM_W1-120
Solar/Wind Harmer
0.403
219348LDSOLAR C
Solar/Wind Harmer
0.439
219222BRL12CT2
Adder
6.546
963711AG1-223 GEN
Solar/Wind Harmer
1.005
20714528FRN_Y2-051
Solar/Wind Harmer
0.2
213611FALLS1-3
Adder
2.31
213958STHWK5-6
Adder
1.753
213560DLW11-12
Adder
1.672
20720528MAN_W1-024
Solar/Wind Harmer
0.157
20715228NPK_W1-113
Solar/Wind Harmer
0.265
219276PARKLANDSO C
Solar/Wind Harmer
0.278
20720428HOL_W1-112
Solar/Wind Harmer
0.208
219680HOPEWELLV C1
Solar/Wind Harmer
0.043
20635828PARLN1&2
Adder
4.068
20635028RRCT1&2
Adder
6.303
218524CNTRALGAS1 C
Solar/Wind Harmer
0.186
218440SUMMTASSOC C
Solar/Wind Harmer
0.064
218428ETC SOLAR C
Solar/Wind Harmer
0.018
219908AB1-139 C
Solar/Wind Harmer
0.188
219919AE1-041 FULL
Solar/Wind Harmer
0.02
972275AH1-722 GEN
Adder
15.212
20714428HOW_X1-037
Solar/Wind Harmer
0.788
20720628TIN_W1-124
Solar/Wind Harmer
0.628
213561DLWR9-10
Adder
2.187
213561DLWR9-10
Adder
1.672
20716228APLW2-078
Solar/Wind Harmer
0.544
971521AH1-258 GEN
Solar/Wind Harmer
1.646
219620RIDERU C
Solar/Wind Harmer
0.032
20635928PARLN3&4
Adder
4.068
218526CNTRALGAS2 C
Solar/Wind Harmer
0.187
200201DELTA2 CT2
50/50
9.784
200034PCHBTM 2
50/50
56.95
200205Y1-065-CTG2
50/50
10.599
232918OH NUG7
50/50
18.158
232905CHERITON_25
50/50
5.078
232926CRISFLD1
50/50
4.062
232910NRG_G1
50/50
17.584
200035PCHBTM 3
50/50
-13.738
233971AC1-093 C
Solar/Wind Harmer
4.975
232410W1-006 C
Solar/Wind Harmer
1.95
234015AF2-250 C
Solar/Wind Harmer
0.234
231940T-011
Adder
1.454
232428Y3-058 C
Solar/Wind Harmer
1.624
233994AC2-023 GEN
Solar/Wind Harmer
5.231
232899W1-062
Adder
18.733
233946AB2-136 GEN
Solar/Wind Harmer
7.752
234036AF2-325 C
Solar/Wind Harmer
1.781
234041AC1-190 GEN
Solar/Wind Harmer
17.392
233952AC2-187 GEN
Solar/Wind Harmer
2.182
233954AC2-188 GEN
Solar/Wind Harmer
2.182
233984AB2-036 GEN
Solar/Wind Harmer
23.788
232424Y1-079 C
Solar/Wind Harmer
1.072
234014AF1-036_GEN
Solar/Wind Harmer
5.118
232436AB1-176 C
Solar/Wind Harmer
0.432
233930AB2-032 GEN
Solar/Wind Harmer
1.559
233982AB2-133 GEN
Solar/Wind Harmer
9.093
228251CARLLS#4
Adder
0.695
228201CARL#2CT
Adder
7.569
228200CARL#1CT
Adder
7.199
230433AD2-135 GEN
Solar/Wind Harmer
0.109
228754AB1-001 C
Solar/Wind Harmer
0.149
230511AF1-262
Solar/Wind Harmer
0.194
228351V2-046C
Solar/Wind Harmer
2.126
228307PCLP GT
Adder
12.171
972233AH1-701 GEN
Adder
4.052
219272CLEANLIGHT C
Solar/Wind Harmer
0.162
219287REEVESEAST C
Solar/Wind Harmer
1.191
219904AC1-010 C
Solar/Wind Harmer
0.31
219912AD2-042 GEN
Solar/Wind Harmer
0.627
20636128O CRK C2
Adder
4.96
20720828JCB_W4-025
Solar/Wind Harmer
0.344
219906AC1-017 C
Solar/Wind Harmer
0.167
213589EDDYSTN4
Adder
59.196
213587EDDYSTN3
Adder
59.104
219607WPEMNERT C
Solar/Wind Harmer
0.307
219304NAMERICA C
Solar/Wind Harmer
0.227
207459AE1-142 C O1
Solar/Wind Harmer
0.769
213535CROYDN11
Adder
7.313
20628028LAKEHURS
Adder
0.682
20714828MDF_W3-079
Solar/Wind Harmer
0.207
214067T20SOLAR
Solar/Wind Harmer
0.165
20641628MLH_W1-032
Solar/Wind Harmer
0.183
20742028HF_AC1-207
Solar/Wind Harmer
0.478
219817TRENTONSOL C
Solar/Wind Harmer
0.636
217197RE CRAN C
Solar/Wind Harmer
0.294
218438BLK ROCK C
Solar/Wind Harmer
0.074
20635028RRCT1&2
Adder
6.206
20635128RRCT3&4
Adder
5.991
20635128RRCT3&4
Adder
5.226
924131AB2-057 GEN
Solar/Wind Harmer
0.535
218418LINDEN_G5
Adder
8.275
218419LINDEN_G6
Adder
8.275
972260AH1-715 GEN1
Adder
6.626
200200DELTA2 CT1
50/50
9.784
200193DELTA CT2
50/50
5.467
200203Y1-065-STG
50/50
18.356
200055ROCKSP 4
50/50
6.629
231914HR8
50/50
4.385
231911HR5
50/50
2.885
233921W3-032A-STG1
50/50
2.707
232914OH NUG3
50/50
18.28
232916OH NUG5
50/50
18.28
232921TASLEY2G
50/50
10.684
234034AF2-060
50/50
3.656
232911NRG_G2
50/50
0.962
233987AB2-037 GEN
Solar/Wind Harmer
22.246
233973AC2-185 C
Solar/Wind Harmer
10.585
970695AG2-447 GEN
Solar/Wind Harmer
7.002
233939AC1-091 C
Solar/Wind Harmer
5.239
233972AC1-094 C
Solar/Wind Harmer
4.207
232434Z2-077 GEN
Solar/Wind Harmer
0.488
232406W1-004 FULL
Solar/Wind Harmer
1.95
233923SMA
Solar/Wind Harmer
7.127
233997TMININ_4.2
Solar/Wind Harmer
1.944
232907VN8
Adder
58.549
233964AF2-378 GEN
Solar/Wind Harmer
0.248
232417X3-008 C
Solar/Wind Harmer
2.184
233950AC2-186 GEN
Solar/Wind Harmer
1.091
232422X3-066 FULL
Solar/Wind Harmer
0.471
233933AB2-153 GEN
Solar/Wind Harmer
2.104
233935AB2-179 C
Solar/Wind Harmer
4.434
228711V2-041C
Solar/Wind Harmer
0.688
230415AB2-049 C
Solar/Wind Harmer
0.199
219291REEVESSOUT C
Solar/Wind Harmer
0.054
218660EHAMPSOLAR C
Solar/Wind Harmer
0.155
219688LUMSOLAR_S C
Solar/Wind Harmer
0.176
219623KINSLEYBEA C
Solar/Wind Harmer
0.368
219921AF1-264
Solar/Wind Harmer
0.121
219914AD2-027 C
Solar/Wind Harmer
0.473
219236SOUTHERNHQ C
Solar/Wind Harmer
0.052
20636028O CRK C1
Adder
5.439
213497CHSTR7-9
Adder
2.061
20716428NHV_W2-082
Solar/Wind Harmer
1.349
20715728PEM_W1-119
Solar/Wind Harmer
0.403
963391AG1-188 GEN
Solar/Wind Harmer
2.804
219221BRL12CT1
Adder
6.546
219223BRL12CT3
Adder
6.546
971667AH1-334 GEN
Solar/Wind Harmer
1.991
20714928UPF_X1-085
Solar/Wind Harmer
0.291
959561AF2-247 GEN
Solar/Wind Harmer
0.332
213958STHWK5-6
Adder
1.753
219114HARTZY_C
Solar/Wind Harmer
0.535
219727YARDVSOLFA C
Solar/Wind Harmer
0.573
207454AA2-184 E
Solar/Wind Harmer
0.63
213560DLW11-12
Adder
1.672
20716928W4-060COL
Solar/Wind Harmer
0.412
219918AC2-009 C
Solar/Wind Harmer
0.014
219612MATRIX C
Solar/Wind Harmer
0.101
20635828PARLN1&2
Adder
1.842
20635928PARLN3&4
Adder
1.842
217213AMBOY SO C
Solar/Wind Harmer
0.062
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.327
VTFLTFEXP_VFT->PJM
CMTX
60.398
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.044
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.998
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.185
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.478
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
27.411
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.817
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.98 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:3831.93
MW Contribution:
7.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
5.467
200194DELTA CT3
50/50
5.467
200204Y1-065-CTG1
50/50
10.599
200054ROCKSP 3
50/50
6.746
231912HR6
50/50
2.885
231913HR7
50/50
2.885
233920W3-032A-CTG1
50/50
4.189
232901NORTHST
50/50
17.278
232917OH NUG6
50/50
18.199
232915OH NUG4
50/50
18.158
233970AC1-092 C
Solar/Wind Harmer
5.239
234033AF1-007_GEN
Solar/Wind Harmer
72.584
232404W1-003 C
Solar/Wind Harmer
1.95
232408W1-005 C
Solar/Wind Harmer
1.95
233996TM1833_GEN
Solar/Wind Harmer
1.944
233998TM1NIN_3.36
Solar/Wind Harmer
1.944
972177AH1-672 GEN
Solar/Wind Harmer
26.189
232900DEMECSMY
Adder
17.968
232919VN10
Adder
5.464
232426Y1-080 FULL
Solar/Wind Harmer
0.372
232902EASTMUNI
Adder
25.121
234012AE2-112_GEN
Solar/Wind Harmer
4.35
233944AB2-135 GEN
Solar/Wind Harmer
9.825
233918AB1-142 GEN
Solar/Wind Harmer
1.852
972251AH1-710 GEN
Adder
79.377
200202DELTA2 ST
50/50
16.568
200195DELTA ST
50/50
8.445
200052ROCKSP 1
50/50
6.668
200053ROCKSP 2
50/50
6.538
232616GEN FOOD
50/50
0.339
232904IR4
50/50
167.426
232920IR10
50/50
6.543
232912OH NUG1
50/50
18.28
232913OH NUG2
50/50
18.037
232432Z2-076 GEN
Solar/Wind Harmer
0.257
233901CHERRYDALE C
Solar/Wind Harmer
2.194
233940AF2-379 C
Solar/Wind Harmer
0.363
971195AH1-057 GEN
Solar/Wind Harmer
1.9
233955AB2-172 GEN
Solar/Wind Harmer
9.705
232813VAUGHN
Adder
1.135
233968AD2-076_GEN
Solar/Wind Harmer
12.54
970597AG2-380 GEN
Solar/Wind Harmer
7.874
231906DC3 NUG
Adder
26.227
231902DC CT7
Adder
20.967
231907DC10
Adder
6.548
233915AB1-141 GEN
Solar/Wind Harmer
1.852
231919CHRIST1
Adder
7.005
231920CHRIST2
Adder
6.849
970453AG2-297 GEN
Solar/Wind Harmer
3.222
230422AE1-104_GEN1
Solar/Wind Harmer
37.16
230425AE1-104_GEN2
Solar/Wind Harmer
37.16
972141AH1-641 GEN
Solar/Wind Harmer
3.086
227927V4-067C
Solar/Wind Harmer
0.213
230430AE1-229_GEN
Solar/Wind Harmer
30.611
964001AG1-254 GEN
Solar/Wind Harmer
7.709
228728W1-130C
Solar/Wind Harmer
0.702
230407AD2-065 C
Solar/Wind Harmer
0.136
230434AG1-499 GEN
Solar/Wind Harmer
0.588
219137THOSOLAR C
Solar/Wind Harmer
1.066
219258KINSLEYDEP C
Solar/Wind Harmer
0.274
207487AE2-000G4
Solar/Wind Harmer
24.242
207497AE2-000G2
Solar/Wind Harmer
24.242
207500AE2-000G1
Solar/Wind Harmer
24.242
207507AE2-000G3
Solar/Wind Harmer
24.242
20720728JCB_W1-129
Solar/Wind Harmer
0.226
20715028HAN_X4-015
Solar/Wind Harmer
0.226
963401AG1-189 GEN
Solar/Wind Harmer
1.719
219615MILLCREEK C
Solar/Wind Harmer
0.178
970025AG2-016 GEN
Solar/Wind Harmer
2.124
219610FLORENCE C
Solar/Wind Harmer
1.016
219224BRL12CT4
Adder
6.546
971189AH1-054 GEN
Solar/Wind Harmer
0.87
207445AB1-138_GEN
Solar/Wind Harmer
0.415
213611FALLS1-3
Adder
2.31
213611FALLS1-3
Adder
2.31
213942SCHUYLKILL
Adder
2.293
213942SCHUYLKILL
Adder
1.754
213957STHWK3-4
Adder
1.753
213957STHWK3-4
Adder
1.753
20714428HOW_X1-037
Solar/Wind Harmer
0.788
20720628TIN_W1-124
Solar/Wind Harmer
0.628
213561DLWR9-10
Adder
2.187
213561DLWR9-10
Adder
1.672
20716228APLW2-078
Solar/Wind Harmer
0.544
971521AH1-258 GEN
Solar/Wind Harmer
1.646
219620RIDERU C
Solar/Wind Harmer
0.032
20635928PARLN3&4
Adder
4.068
218526CNTRALGAS2 C
Solar/Wind Harmer
0.187
200201DELTA2 CT2
50/50
9.784
200034PCHBTM 2
50/50
56.95
200205Y1-065-CTG2
50/50
10.599
232918OH NUG7
50/50
18.158
232905CHERITON_25
50/50
5.078
232926CRISFLD1
50/50
4.062
232910NRG_G1
50/50
17.584
200035PCHBTM 3
50/50
-13.738
233971AC1-093 C
Solar/Wind Harmer
4.975
232410W1-006 C
Solar/Wind Harmer
1.95
234015AF2-250 C
Solar/Wind Harmer
0.234
231940T-011
Adder
1.454
232428Y3-058 C
Solar/Wind Harmer
1.624
233994AC2-023 GEN
Solar/Wind Harmer
5.231
232899W1-062
Adder
18.733
233946AB2-136 GEN
Solar/Wind Harmer
7.752
234036AF2-325 C
Solar/Wind Harmer
1.781
234041AC1-190 GEN
Solar/Wind Harmer
17.392
233952AC2-187 GEN
Solar/Wind Harmer
2.182
233954AC2-188 GEN
Solar/Wind Harmer
2.182
233984AB2-036 GEN
Solar/Wind Harmer
23.788
232424Y1-079 C
Solar/Wind Harmer
1.072
234014AF1-036_GEN
Solar/Wind Harmer
5.118
232436AB1-176 C
Solar/Wind Harmer
0.432
233930AB2-032 GEN
Solar/Wind Harmer
1.559
233982AB2-133 GEN
Solar/Wind Harmer
9.093
228251CARLLS#4
Adder
0.695
228201CARL#2CT
Adder
7.569
228200CARL#1CT
Adder
7.199
231918WEST 1
Adder
5.37
231917EM10
Adder
3.587
228206SHRMN CT
Adder
18.904
228732V1-021 C
Adder
0.214
228260V4-054C
Solar/Wind Harmer
1.13
228729W2-030 C
Solar/Wind Harmer
0.621
970997AG2-616 GEN
Solar/Wind Harmer
10.285
228400MICK 1CT
Adder
11.306
219686LUMSOLAR_N C
Solar/Wind Harmer
0.179
219766PARADISE C
Solar/Wind Harmer
0.258
219907AC1-030 C
Solar/Wind Harmer
0.107
213497CHSTR7-9
Adder
2.061
213497CHSTR7-9
Adder
2.061
20716028EGP_W2-019
Solar/Wind Harmer
0.352
207522AF2-254 C
Solar/Wind Harmer
1.087
20717128DIX_Z2-102
Solar/Wind Harmer
0.998
20715828PEM_W1-120
Solar/Wind Harmer
0.403
219348LDSOLAR C
Solar/Wind Harmer
0.439
219222BRL12CT2
Adder
6.546
963711AG1-223 GEN
Solar/Wind Harmer
1.005
20714528FRN_Y2-051
Solar/Wind Harmer
0.2
213611FALLS1-3
Adder
2.31
213958STHWK5-6
Adder
1.753
213560DLW11-12
Adder
1.672
20720528MAN_W1-024
Solar/Wind Harmer
0.157
20715228NPK_W1-113
Solar/Wind Harmer
0.265
219276PARKLANDSO C
Solar/Wind Harmer
0.278
230433AD2-135 GEN
Solar/Wind Harmer
0.109
228754AB1-001 C
Solar/Wind Harmer
0.149
230511AF1-262
Solar/Wind Harmer
0.194
228351V2-046C
Solar/Wind Harmer
2.126
228307PCLP GT
Adder
12.171
972233AH1-701 GEN
Adder
4.052
219272CLEANLIGHT C
Solar/Wind Harmer
0.162
219287REEVESEAST C
Solar/Wind Harmer
1.191
219904AC1-010 C
Solar/Wind Harmer
0.31
219912AD2-042 GEN
Solar/Wind Harmer
0.627
20636128O CRK C2
Adder
4.96
20720828JCB_W4-025
Solar/Wind Harmer
0.344
219906AC1-017 C
Solar/Wind Harmer
0.167
213589EDDYSTN4
Adder
59.196
213587EDDYSTN3
Adder
59.104
219607WPEMNERT C
Solar/Wind Harmer
0.307
219304NAMERICA C
Solar/Wind Harmer
0.227
207459AE1-142 C O1
Solar/Wind Harmer
0.769
213535CROYDN11
Adder
7.313
20628028LAKEHURS
Adder
0.682
20714828MDF_W3-079
Solar/Wind Harmer
0.207
214067T20SOLAR
Solar/Wind Harmer
0.165
20641628MLH_W1-032
Solar/Wind Harmer
0.183
20742028HF_AC1-207
Solar/Wind Harmer
0.478
219817TRENTONSOL C
Solar/Wind Harmer
0.636
217197RE CRAN C
Solar/Wind Harmer
0.294
218438BLK ROCK C
Solar/Wind Harmer
0.074
20635028RRCT1&2
Adder
6.206
20635128RRCT3&4
Adder
5.991
20635128RRCT3&4
Adder
5.226
924131AB2-057 GEN
Solar/Wind Harmer
0.535
218418LINDEN_G5
Adder
8.275
218419LINDEN_G6
Adder
8.275
972260AH1-715 GEN1
Adder
6.626
200200DELTA2 CT1
50/50
9.784
200193DELTA CT2
50/50
5.467
200203Y1-065-STG
50/50
18.356
200055ROCKSP 4
50/50
6.629
231914HR8
50/50
4.385
231911HR5
50/50
2.885
233921W3-032A-STG1
50/50
2.707
232914OH NUG3
50/50
18.28
232916OH NUG5
50/50
18.28
232921TASLEY2G
50/50
10.684
234034AF2-060
50/50
3.656
232911NRG_G2
50/50
0.962
233987AB2-037 GEN
Solar/Wind Harmer
22.246
233973AC2-185 C
Solar/Wind Harmer
10.585
970695AG2-447 GEN
Solar/Wind Harmer
7.002
233939AC1-091 C
Solar/Wind Harmer
5.239
233972AC1-094 C
Solar/Wind Harmer
4.207
232434Z2-077 GEN
Solar/Wind Harmer
0.488
232406W1-004 FULL
Solar/Wind Harmer
1.95
233923SMA
Solar/Wind Harmer
7.127
233997TMININ_4.2
Solar/Wind Harmer
1.944
232907VN8
Adder
58.549
233964AF2-378 GEN
Solar/Wind Harmer
0.248
232417X3-008 C
Solar/Wind Harmer
2.184
233950AC2-186 GEN
Solar/Wind Harmer
1.091
232422X3-066 FULL
Solar/Wind Harmer
0.471
233933AB2-153 GEN
Solar/Wind Harmer
2.104
233935AB2-179 C
Solar/Wind Harmer
4.434
228711V2-041C
Solar/Wind Harmer
0.688
230415AB2-049 C
Solar/Wind Harmer
0.199
219291REEVESSOUT C
Solar/Wind Harmer
0.054
218660EHAMPSOLAR C
Solar/Wind Harmer
0.155
219688LUMSOLAR_S C
Solar/Wind Harmer
0.176
219623KINSLEYBEA C
Solar/Wind Harmer
0.368
219921AF1-264
Solar/Wind Harmer
0.121
219914AD2-027 C
Solar/Wind Harmer
0.473
219236SOUTHERNHQ C
Solar/Wind Harmer
0.052
20636028O CRK C1
Adder
5.439
213497CHSTR7-9
Adder
2.061
20716428NHV_W2-082
Solar/Wind Harmer
1.349
20715728PEM_W1-119
Solar/Wind Harmer
0.403
963391AG1-188 GEN
Solar/Wind Harmer
2.804
219221BRL12CT1
Adder
6.546
219223BRL12CT3
Adder
6.546
971667AH1-334 GEN
Solar/Wind Harmer
1.991
20714928UPF_X1-085
Solar/Wind Harmer
0.291
959561AF2-247 GEN
Solar/Wind Harmer
0.332
213958STHWK5-6
Adder
1.753
219114HARTZY_C
Solar/Wind Harmer
0.535
219727YARDVSOLFA C
Solar/Wind Harmer
0.573
207454AA2-184 E
Solar/Wind Harmer
0.63
213560DLW11-12
Adder
1.672
20716928W4-060COL
Solar/Wind Harmer
0.412
219918AC2-009 C
Solar/Wind Harmer
0.014
219612MATRIX C
Solar/Wind Harmer
0.101
20635828PARLN1&2
Adder
1.842
20635928PARLN3&4
Adder
1.842
217213AMBOY SO C
Solar/Wind Harmer
0.062
20720428HOL_W1-112
Solar/Wind Harmer
0.208
219680HOPEWELLV C1
Solar/Wind Harmer
0.043
20635828PARLN1&2
Adder
4.068
20635028RRCT1&2
Adder
6.303
218524CNTRALGAS1 C
Solar/Wind Harmer
0.186
218440SUMMTASSOC C
Solar/Wind Harmer
0.064
218428ETC SOLAR C
Solar/Wind Harmer
0.018
219908AB1-139 C
Solar/Wind Harmer
0.188
219919AE1-041 FULL
Solar/Wind Harmer
0.02
972275AH1-722 GEN
Adder
15.212
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.327
VTFLTFEXP_VFT->PJM
CMTX
60.398
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.044
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.998
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.185
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.478
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
27.411
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.817
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.84 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:3827.78
MW Contribution:
6.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
16.575
200195DELTA ST
50/50
8.449
200052ROCKSP 1
50/50
6.657
200053ROCKSP 2
50/50
6.526
232616GEN FOOD
50/50
0.338
232904IR4
50/50
167.133
232920IR10
50/50
6.531
232912OH NUG1
50/50
18.248
232913OH NUG2
50/50
18.005
232432Z2-076 GEN
Solar/Wind Harmer
0.257
233901CHERRYDALE C
Solar/Wind Harmer
2.19
233940AF2-379 C
Solar/Wind Harmer
0.363
971195AH1-057 GEN
Solar/Wind Harmer
1.897
233955AB2-172 GEN
Solar/Wind Harmer
9.688
232813VAUGHN
Adder
1.133
233968AD2-076_GEN
Solar/Wind Harmer
12.518
970597AG2-380 GEN
Solar/Wind Harmer
7.86
231906DC3 NUG
Adder
26.181
231902DC CT7
Adder
20.93
231907DC10
Adder
6.536
233915AB1-141 GEN
Solar/Wind Harmer
1.848
231919CHRIST1
Adder
6.993
231920CHRIST2
Adder
6.837
970453AG2-297 GEN
Solar/Wind Harmer
3.217
230422AE1-104_GEN1
Solar/Wind Harmer
37.094
230425AE1-104_GEN2
Solar/Wind Harmer
37.094
972141AH1-641 GEN
Solar/Wind Harmer
3.08
227927V4-067C
Solar/Wind Harmer
0.212
230430AE1-229_GEN
Solar/Wind Harmer
30.557
964001AG1-254 GEN
Solar/Wind Harmer
7.695
228728W1-130C
Solar/Wind Harmer
0.701
230407AD2-065 C
Solar/Wind Harmer
0.136
230434AG1-499 GEN
Solar/Wind Harmer
0.587
219137THOSOLAR C
Solar/Wind Harmer
1.064
219258KINSLEYDEP C
Solar/Wind Harmer
0.273
207487AE2-000G4
Solar/Wind Harmer
24.199
207497AE2-000G2
Solar/Wind Harmer
24.199
207500AE2-000G1
Solar/Wind Harmer
24.199
207507AE2-000G3
Solar/Wind Harmer
24.199
20720728JCB_W1-129
Solar/Wind Harmer
0.226
20715028HAN_X4-015
Solar/Wind Harmer
0.226
963401AG1-189 GEN
Solar/Wind Harmer
1.716
219615MILLCREEK C
Solar/Wind Harmer
0.178
970025AG2-016 GEN
Solar/Wind Harmer
2.12
219610FLORENCE C
Solar/Wind Harmer
1.014
219224BRL12CT4
Adder
6.534
971189AH1-054 GEN
Solar/Wind Harmer
0.868
207445AB1-138_GEN
Solar/Wind Harmer
0.415
213611FALLS1-3
Adder
2.305
213611FALLS1-3
Adder
2.305
213942SCHUYLKILL
Adder
2.289
213942SCHUYLKILL
Adder
1.751
213957STHWK3-4
Adder
1.75
213957STHWK3-4
Adder
1.75
20714428HOW_X1-037
Solar/Wind Harmer
0.787
20720628TIN_W1-124
Solar/Wind Harmer
0.627
213561DLWR9-10
Adder
2.183
213561DLWR9-10
Adder
1.669
20716228APLW2-078
Solar/Wind Harmer
0.543
971521AH1-258 GEN
Solar/Wind Harmer
1.643
219620RIDERU C
Solar/Wind Harmer
0.032
20635928PARLN3&4
Adder
4.06
218526CNTRALGAS2 C
Solar/Wind Harmer
0.187
200201DELTA2 CT2
50/50
9.788
200034PCHBTM 2
50/50
56.851
200205Y1-065-CTG2
50/50
10.581
232918OH NUG7
50/50
18.127
232905CHERITON_25
50/50
5.069
232926CRISFLD1
50/50
4.055
232910NRG_G1
50/50
17.553
200035PCHBTM 3
50/50
-13.716
233971AC1-093 C
Solar/Wind Harmer
4.966
232410W1-006 C
Solar/Wind Harmer
1.946
234015AF2-250 C
Solar/Wind Harmer
0.234
231940T-011
Adder
1.451
232428Y3-058 C
Solar/Wind Harmer
1.621
233994AC2-023 GEN
Solar/Wind Harmer
5.222
232899W1-062
Adder
18.7
233946AB2-136 GEN
Solar/Wind Harmer
7.739
234036AF2-325 C
Solar/Wind Harmer
1.778
234041AC1-190 GEN
Solar/Wind Harmer
17.361
233952AC2-187 GEN
Solar/Wind Harmer
2.178
233954AC2-188 GEN
Solar/Wind Harmer
2.178
233984AB2-036 GEN
Solar/Wind Harmer
23.747
232424Y1-079 C
Solar/Wind Harmer
1.07
234014AF1-036_GEN
Solar/Wind Harmer
5.109
232436AB1-176 C
Solar/Wind Harmer
0.431
233930AB2-032 GEN
Solar/Wind Harmer
1.556
233982AB2-133 GEN
Solar/Wind Harmer
9.077
228251CARLLS#4
Adder
0.693
228201CARL#2CT
Adder
7.555
228200CARL#1CT
Adder
7.186
230433AD2-135 GEN
Solar/Wind Harmer
0.108
228754AB1-001 C
Solar/Wind Harmer
0.148
230511AF1-262
Solar/Wind Harmer
0.194
228351V2-046C
Solar/Wind Harmer
2.122
228307PCLP GT
Adder
12.15
972233AH1-701 GEN
Adder
4.045
219272CLEANLIGHT C
Solar/Wind Harmer
0.161
219287REEVESEAST C
Solar/Wind Harmer
1.188
219904AC1-010 C
Solar/Wind Harmer
0.309
219912AD2-042 GEN
Solar/Wind Harmer
0.626
20636128O CRK C2
Adder
4.951
20720828JCB_W4-025
Solar/Wind Harmer
0.343
219906AC1-017 C
Solar/Wind Harmer
0.167
213589EDDYSTN4
Adder
59.089
213587EDDYSTN3
Adder
58.997
219607WPEMNERT C
Solar/Wind Harmer
0.307
219304NAMERICA C
Solar/Wind Harmer
0.227
207459AE1-142 C O1
Solar/Wind Harmer
0.767
213535CROYDN11
Adder
7.3
20628028LAKEHURS
Adder
0.681
20714828MDF_W3-079
Solar/Wind Harmer
0.207
214067T20SOLAR
Solar/Wind Harmer
0.165
20641628MLH_W1-032
Solar/Wind Harmer
0.183
20742028HF_AC1-207
Solar/Wind Harmer
0.478
219817TRENTONSOL C
Solar/Wind Harmer
0.635
217197RE CRAN C
Solar/Wind Harmer
0.293
218438BLK ROCK C
Solar/Wind Harmer
0.074
20635028RRCT1&2
Adder
6.195
20635128RRCT3&4
Adder
5.98
20635128RRCT3&4
Adder
5.216
924131AB2-057 GEN
Solar/Wind Harmer
0.534
218418LINDEN_G5
Adder
8.26
218419LINDEN_G6
Adder
8.26
972260AH1-715 GEN1
Adder
6.614
200200DELTA2 CT1
50/50
9.788
200193DELTA CT2
50/50
5.469
200203Y1-065-STG
50/50
18.324
200055ROCKSP 4
50/50
6.618
231914HR8
50/50
4.378
231911HR5
50/50
2.88
233921W3-032A-STG1
50/50
2.702
232914OH NUG3
50/50
18.248
232916OH NUG5
50/50
18.248
232921TASLEY2G
50/50
10.665
234034AF2-060
50/50
3.65
232911NRG_G2
50/50
0.96
233987AB2-037 GEN
Solar/Wind Harmer
22.207
233973AC2-185 C
Solar/Wind Harmer
10.566
970695AG2-447 GEN
Solar/Wind Harmer
6.99
233939AC1-091 C
Solar/Wind Harmer
5.23
233972AC1-094 C
Solar/Wind Harmer
4.2
232434Z2-077 GEN
Solar/Wind Harmer
0.487
232406W1-004 FULL
Solar/Wind Harmer
1.946
233923SMA
Solar/Wind Harmer
7.114
233997TMININ_4.2
Solar/Wind Harmer
1.94
232907VN8
Adder
58.446
233964AF2-378 GEN
Solar/Wind Harmer
0.248
232417X3-008 C
Solar/Wind Harmer
2.18
233950AC2-186 GEN
Solar/Wind Harmer
1.089
232422X3-066 FULL
Solar/Wind Harmer
0.47
233933AB2-153 GEN
Solar/Wind Harmer
2.1
233935AB2-179 C
Solar/Wind Harmer
4.426
228711V2-041C
Solar/Wind Harmer
0.686
230415AB2-049 C
Solar/Wind Harmer
0.199
219291REEVESSOUT C
Solar/Wind Harmer
0.054
218660EHAMPSOLAR C
Solar/Wind Harmer
0.155
219688LUMSOLAR_S C
Solar/Wind Harmer
0.175
219623KINSLEYBEA C
Solar/Wind Harmer
0.367
219921AF1-264
Solar/Wind Harmer
0.121
219914AD2-027 C
Solar/Wind Harmer
0.472
219236SOUTHERNHQ C
Solar/Wind Harmer
0.052
20636028O CRK C1
Adder
5.43
213497CHSTR7-9
Adder
2.057
20716428NHV_W2-082
Solar/Wind Harmer
1.346
20715728PEM_W1-119
Solar/Wind Harmer
0.402
963391AG1-188 GEN
Solar/Wind Harmer
2.799
219221BRL12CT1
Adder
6.534
219223BRL12CT3
Adder
6.534
971667AH1-334 GEN
Solar/Wind Harmer
1.987
20714928UPF_X1-085
Solar/Wind Harmer
0.291
959561AF2-247 GEN
Solar/Wind Harmer
0.332
213958STHWK5-6
Adder
1.75
219114HARTZY_C
Solar/Wind Harmer
0.534
219727YARDVSOLFA C
Solar/Wind Harmer
0.572
207454AA2-184 E
Solar/Wind Harmer
0.629
213560DLW11-12
Adder
1.669
20716928W4-060COL
Solar/Wind Harmer
0.411
219918AC2-009 C
Solar/Wind Harmer
0.014
219612MATRIX C
Solar/Wind Harmer
0.1
20635828PARLN1&2
Adder
1.839
20635928PARLN3&4
Adder
1.839
217213AMBOY SO C
Solar/Wind Harmer
0.062
200192DELTA CT1
50/50
5.469
200194DELTA CT3
50/50
5.469
200204Y1-065-CTG1
50/50
10.581
200054ROCKSP 3
50/50
6.734
231912HR6
50/50
2.88
231913HR7
50/50
2.88
233920W3-032A-CTG1
50/50
4.182
232901NORTHST
50/50
17.248
232917OH NUG6
50/50
18.167
232915OH NUG4
50/50
18.127
233970AC1-092 C
Solar/Wind Harmer
5.23
234033AF1-007_GEN
Solar/Wind Harmer
72.457
232404W1-003 C
Solar/Wind Harmer
1.946
232408W1-005 C
Solar/Wind Harmer
1.946
233996TM1833_GEN
Solar/Wind Harmer
1.94
233998TM1NIN_3.36
Solar/Wind Harmer
1.94
972177AH1-672 GEN
Solar/Wind Harmer
26.143
232900DEMECSMY
Adder
17.937
232919VN10
Adder
5.455
232426Y1-080 FULL
Solar/Wind Harmer
0.371
232902EASTMUNI
Adder
25.077
234012AE2-112_GEN
Solar/Wind Harmer
4.343
233944AB2-135 GEN
Solar/Wind Harmer
9.808
233918AB1-142 GEN
Solar/Wind Harmer
1.848
972251AH1-710 GEN
Adder
79.238
231918WEST 1
Adder
5.361
231917EM10
Adder
3.58
228206SHRMN CT
Adder
18.871
228732V1-021 C
Adder
0.214
228260V4-054C
Solar/Wind Harmer
1.128
228729W2-030 C
Solar/Wind Harmer
0.62
970997AG2-616 GEN
Solar/Wind Harmer
10.267
228400MICK 1CT
Adder
11.286
219686LUMSOLAR_N C
Solar/Wind Harmer
0.179
219766PARADISE C
Solar/Wind Harmer
0.257
219907AC1-030 C
Solar/Wind Harmer
0.107
213497CHSTR7-9
Adder
2.057
213497CHSTR7-9
Adder
2.057
20716028EGP_W2-019
Solar/Wind Harmer
0.352
207522AF2-254 C
Solar/Wind Harmer
1.085
20717128DIX_Z2-102
Solar/Wind Harmer
0.996
20715828PEM_W1-120
Solar/Wind Harmer
0.402
219348LDSOLAR C
Solar/Wind Harmer
0.438
219222BRL12CT2
Adder
6.534
963711AG1-223 GEN
Solar/Wind Harmer
1.003
20714528FRN_Y2-051
Solar/Wind Harmer
0.2
213611FALLS1-3
Adder
2.305
213958STHWK5-6
Adder
1.75
213560DLW11-12
Adder
1.669
20720528MAN_W1-024
Solar/Wind Harmer
0.157
20715228NPK_W1-113
Solar/Wind Harmer
0.264
219276PARKLANDSO C
Solar/Wind Harmer
0.277
20720428HOL_W1-112
Solar/Wind Harmer
0.208
219680HOPEWELLV C1
Solar/Wind Harmer
0.043
20635828PARLN1&2
Adder
4.06
20635028RRCT1&2
Adder
6.292
218524CNTRALGAS1 C
Solar/Wind Harmer
0.186
218440SUMMTASSOC C
Solar/Wind Harmer
0.064
218428ETC SOLAR C
Solar/Wind Harmer
0.018
219908AB1-139 C
Solar/Wind Harmer
0.188
219919AE1-041 FULL
Solar/Wind Harmer
0.02
972275AH1-722 GEN
Adder
15.184
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.322
VTFLTFEXP_VFT->PJM
CMTX
60.285
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.995
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.464
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.164
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
27.361
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.772
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.82 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:3827.22
MW Contribution:
7.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
16.573
200195DELTA ST
50/50
8.448
200201DELTA2 CT2
50/50
9.786
200034PCHBTM 2
50/50
56.966
200205Y1-065-CTG2
50/50
10.603
232918OH NUG7
50/50
18.171
232905CHERITON_25
50/50
5.081
232926CRISFLD1
50/50
4.065
232910NRG_G1
50/50
17.597
200035PCHBTM 3
50/50
-13.723
233971AC1-093 C
Solar/Wind Harmer
4.978
232410W1-006 C
Solar/Wind Harmer
1.951
234015AF2-250 C
Solar/Wind Harmer
0.234
231940T-011
Adder
1.455
232428Y3-058 C
Solar/Wind Harmer
1.625
233994AC2-023 GEN
Solar/Wind Harmer
5.234
232899W1-062
Adder
18.746
233946AB2-136 GEN
Solar/Wind Harmer
7.758
234036AF2-325 C
Solar/Wind Harmer
1.782
234041AC1-190 GEN
Solar/Wind Harmer
17.404
233952AC2-187 GEN
Solar/Wind Harmer
2.183
233954AC2-188 GEN
Solar/Wind Harmer
2.183
233984AB2-036 GEN
Solar/Wind Harmer
23.806
232424Y1-079 C
Solar/Wind Harmer
1.073
234014AF1-036_GEN
Solar/Wind Harmer
5.122
232436AB1-176 C
Solar/Wind Harmer
0.432
233930AB2-032 GEN
Solar/Wind Harmer
1.56
233982AB2-133 GEN
Solar/Wind Harmer
9.1
228251CARLLS#4
Adder
0.695
228201CARL#2CT
Adder
7.577
228200CARL#1CT
Adder
7.207
230433AD2-135 GEN
Solar/Wind Harmer
0.109
228754AB1-001 C
Solar/Wind Harmer
0.149
230511AF1-262
Solar/Wind Harmer
0.194
228351V2-046C
Solar/Wind Harmer
2.128
228307PCLP GT
Adder
12.186
972233AH1-701 GEN
Adder
4.058
219272CLEANLIGHT C
Solar/Wind Harmer
0.162
219287REEVESEAST C
Solar/Wind Harmer
1.192
219904AC1-010 C
Solar/Wind Harmer
0.31
219912AD2-042 GEN
Solar/Wind Harmer
0.628
20636128O CRK C2
Adder
4.967
200200DELTA2 CT1
50/50
9.786
200193DELTA CT2
50/50
5.468
200203Y1-065-STG
50/50
18.362
200055ROCKSP 4
50/50
6.631
231914HR8
50/50
4.388
231911HR5
50/50
2.887
233921W3-032A-STG1
50/50
2.709
232914OH NUG3
50/50
18.293
232916OH NUG5
50/50
18.293
232921TASLEY2G
50/50
10.691
234034AF2-060
50/50
3.659
232911NRG_G2
50/50
0.962
233987AB2-037 GEN
Solar/Wind Harmer
22.261
233973AC2-185 C
Solar/Wind Harmer
10.592
970695AG2-447 GEN
Solar/Wind Harmer
7.007
233939AC1-091 C
Solar/Wind Harmer
5.243
233972AC1-094 C
Solar/Wind Harmer
4.21
232434Z2-077 GEN
Solar/Wind Harmer
0.488
232406W1-004 FULL
Solar/Wind Harmer
1.951
233923SMA
Solar/Wind Harmer
7.132
233997TMININ_4.2
Solar/Wind Harmer
1.945
232907VN8
Adder
58.589
233964AF2-378 GEN
Solar/Wind Harmer
0.248
232417X3-008 C
Solar/Wind Harmer
2.185
233950AC2-186 GEN
Solar/Wind Harmer
1.092
232422X3-066 FULL
Solar/Wind Harmer
0.472
233933AB2-153 GEN
Solar/Wind Harmer
2.106
233935AB2-179 C
Solar/Wind Harmer
4.437
228711V2-041C
Solar/Wind Harmer
0.688
230415AB2-049 C
Solar/Wind Harmer
0.199
219291REEVESSOUT C
Solar/Wind Harmer
0.054
218660EHAMPSOLAR C
Solar/Wind Harmer
0.155
219688LUMSOLAR_S C
Solar/Wind Harmer
0.176
219623KINSLEYBEA C
Solar/Wind Harmer
0.368
219921AF1-264
Solar/Wind Harmer
0.121
219914AD2-027 C
Solar/Wind Harmer
0.474
219236SOUTHERNHQ C
Solar/Wind Harmer
0.052
20636028O CRK C1
Adder
5.448
213497CHSTR7-9
Adder
2.065
20716428NHV_W2-082
Solar/Wind Harmer
1.351
20715728PEM_W1-119
Solar/Wind Harmer
0.403
963391AG1-188 GEN
Solar/Wind Harmer
2.809
219221BRL12CT1
Adder
6.557
219223BRL12CT3
Adder
6.557
971667AH1-334 GEN
Solar/Wind Harmer
1.994
20714928UPF_X1-085
Solar/Wind Harmer
0.292
959561AF2-247 GEN
Solar/Wind Harmer
0.333
213958STHWK5-6
Adder
1.757
219114HARTZY_C
Solar/Wind Harmer
0.536
219727YARDVSOLFA C
Solar/Wind Harmer
0.574
207454AA2-184 E
Solar/Wind Harmer
0.631
213560DLW11-12
Adder
1.676
20716928W4-060COL
Solar/Wind Harmer
0.412
219918AC2-009 C
Solar/Wind Harmer
0.014
219612MATRIX C
Solar/Wind Harmer
0.101
20635828PARLN1&2
Adder
1.847
20635928PARLN3&4
Adder
1.847
217213AMBOY SO C
Solar/Wind Harmer
0.062
200192DELTA CT1
50/50
5.468
200194DELTA CT3
50/50
5.468
200204Y1-065-CTG1
50/50
10.603
200054ROCKSP 3
50/50
6.748
231912HR6
50/50
2.887
231913HR7
50/50
2.887
233920W3-032A-CTG1
50/50
4.192
232901NORTHST
50/50
17.29
232917OH NUG6
50/50
18.212
232915OH NUG4
50/50
18.171
233970AC1-092 C
Solar/Wind Harmer
5.243
234033AF1-007_GEN
Solar/Wind Harmer
72.634
232404W1-003 C
Solar/Wind Harmer
1.951
232408W1-005 C
Solar/Wind Harmer
1.951
233996TM1833_GEN
Solar/Wind Harmer
1.945
233998TM1NIN_3.36
Solar/Wind Harmer
1.945
972177AH1-672 GEN
Solar/Wind Harmer
26.207
232900DEMECSMY
Adder
17.981
232919VN10
Adder
5.468
232426Y1-080 FULL
Solar/Wind Harmer
0.372
232902EASTMUNI
Adder
25.139
234012AE2-112_GEN
Solar/Wind Harmer
4.354
233944AB2-135 GEN
Solar/Wind Harmer
9.832
233918AB1-142 GEN
Solar/Wind Harmer
1.853
972251AH1-710 GEN
Adder
79.434
231918WEST 1
Adder
5.375
231917EM10
Adder
3.59
228206SHRMN CT
Adder
18.924
228732V1-021 C
Adder
0.214
228260V4-054C
Solar/Wind Harmer
1.132
228729W2-030 C
Solar/Wind Harmer
0.622
970997AG2-616 GEN
Solar/Wind Harmer
10.297
228400MICK 1CT
Adder
11.321
219686LUMSOLAR_N C
Solar/Wind Harmer
0.179
219766PARADISE C
Solar/Wind Harmer
0.258
219907AC1-030 C
Solar/Wind Harmer
0.107
213497CHSTR7-9
Adder
2.065
213497CHSTR7-9
Adder
2.065
20716028EGP_W2-019
Solar/Wind Harmer
0.353
207522AF2-254 C
Solar/Wind Harmer
1.089
200052ROCKSP 1
50/50
6.67
200053ROCKSP 2
50/50
6.54
232616GEN FOOD
50/50
0.339
232904IR4
50/50
167.541
232920IR10
50/50
6.547
232912OH NUG1
50/50
18.293
232913OH NUG2
50/50
18.049
232432Z2-076 GEN
Solar/Wind Harmer
0.258
233901CHERRYDALE C
Solar/Wind Harmer
2.195
233940AF2-379 C
Solar/Wind Harmer
0.364
971195AH1-057 GEN
Solar/Wind Harmer
1.901
233955AB2-172 GEN
Solar/Wind Harmer
9.711
232813VAUGHN
Adder
1.135
233968AD2-076_GEN
Solar/Wind Harmer
12.549
970597AG2-380 GEN
Solar/Wind Harmer
7.88
231906DC3 NUG
Adder
26.246
231902DC CT7
Adder
20.982
231907DC10
Adder
6.552
233915AB1-141 GEN
Solar/Wind Harmer
1.853
231919CHRIST1
Adder
7.011
231920CHRIST2
Adder
6.856
970453AG2-297 GEN
Solar/Wind Harmer
3.226
230422AE1-104_GEN1
Solar/Wind Harmer
37.201
230425AE1-104_GEN2
Solar/Wind Harmer
37.201
972141AH1-641 GEN
Solar/Wind Harmer
3.089
227927V4-067C
Solar/Wind Harmer
0.213
230430AE1-229_GEN
Solar/Wind Harmer
30.647
964001AG1-254 GEN
Solar/Wind Harmer
7.718
228728W1-130C
Solar/Wind Harmer
0.703
230407AD2-065 C
Solar/Wind Harmer
0.136
230434AG1-499 GEN
Solar/Wind Harmer
0.589
219137THOSOLAR C
Solar/Wind Harmer
1.068
219258KINSLEYDEP C
Solar/Wind Harmer
0.274
207487AE2-000G4
Solar/Wind Harmer
24.28
207497AE2-000G2
Solar/Wind Harmer
24.28
207500AE2-000G1
Solar/Wind Harmer
24.28
207507AE2-000G3
Solar/Wind Harmer
24.28
20720728JCB_W1-129
Solar/Wind Harmer
0.227
20715028HAN_X4-015
Solar/Wind Harmer
0.227
963401AG1-189 GEN
Solar/Wind Harmer
1.722
219615MILLCREEK C
Solar/Wind Harmer
0.179
970025AG2-016 GEN
Solar/Wind Harmer
2.127
219610FLORENCE C
Solar/Wind Harmer
1.017
219224BRL12CT4
Adder
6.557
971189AH1-054 GEN
Solar/Wind Harmer
0.871
207445AB1-138_GEN
Solar/Wind Harmer
0.416
213611FALLS1-3
Adder
2.314
213611FALLS1-3
Adder
2.314
213942SCHUYLKILL
Adder
2.298
213942SCHUYLKILL
Adder
1.757
213957STHWK3-4
Adder
1.757
213957STHWK3-4
Adder
1.757
20714428HOW_X1-037
Solar/Wind Harmer
0.79
20720628TIN_W1-124
Solar/Wind Harmer
0.629
213561DLWR9-10
Adder
2.191
213561DLWR9-10
Adder
1.676
20716228APLW2-078
Solar/Wind Harmer
0.545
971521AH1-258 GEN
Solar/Wind Harmer
1.649
219620RIDERU C
Solar/Wind Harmer
0.032
20635928PARLN3&4
Adder
4.077
218526CNTRALGAS2 C
Solar/Wind Harmer
0.187
20717128DIX_Z2-102
Solar/Wind Harmer
0.999
20715828PEM_W1-120
Solar/Wind Harmer
0.403
219348LDSOLAR C
Solar/Wind Harmer
0.439
219222BRL12CT2
Adder
6.557
963711AG1-223 GEN
Solar/Wind Harmer
1.007
20714528FRN_Y2-051
Solar/Wind Harmer
0.201
213611FALLS1-3
Adder
2.314
213958STHWK5-6
Adder
1.757
213560DLW11-12
Adder
1.676
20720528MAN_W1-024
Solar/Wind Harmer
0.158
20715228NPK_W1-113
Solar/Wind Harmer
0.265
219276PARKLANDSO C
Solar/Wind Harmer
0.278
20720428HOL_W1-112
Solar/Wind Harmer
0.208
219680HOPEWELLV C1
Solar/Wind Harmer
0.043
20635828PARLN1&2
Adder
4.077
20635028RRCT1&2
Adder
6.318
218524CNTRALGAS1 C
Solar/Wind Harmer
0.187
218440SUMMTASSOC C
Solar/Wind Harmer
0.065
218428ETC SOLAR C
Solar/Wind Harmer
0.018
219908AB1-139 C
Solar/Wind Harmer
0.188
219919AE1-041 FULL
Solar/Wind Harmer
0.02
972275AH1-722 GEN
Adder
15.251
20720828JCB_W4-025
Solar/Wind Harmer
0.344
219906AC1-017 C
Solar/Wind Harmer
0.167
213589EDDYSTN4
Adder
59.306
213587EDDYSTN3
Adder
59.213
219607WPEMNERT C
Solar/Wind Harmer
0.308
219304NAMERICA C
Solar/Wind Harmer
0.228
207459AE1-142 C O1
Solar/Wind Harmer
0.77
213535CROYDN11
Adder
7.326
20628028LAKEHURS
Adder
0.683
20714828MDF_W3-079
Solar/Wind Harmer
0.208
214067T20SOLAR
Solar/Wind Harmer
0.165
20641628MLH_W1-032
Solar/Wind Harmer
0.184
20742028HF_AC1-207
Solar/Wind Harmer
0.479
219817TRENTONSOL C
Solar/Wind Harmer
0.637
217197RE CRAN C
Solar/Wind Harmer
0.294
218438BLK ROCK C
Solar/Wind Harmer
0.075
20635028RRCT1&2
Adder
6.22
20635128RRCT3&4
Adder
6.004
20635128RRCT3&4
Adder
5.238
924131AB2-057 GEN
Solar/Wind Harmer
0.536
218418LINDEN_G5
Adder
8.296
218419LINDEN_G6
Adder
8.296
972260AH1-715 GEN1
Adder
6.643
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.332
VTFLTFEXP_VFT->PJM
CMTX
60.563
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.049
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.001
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.211
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.495
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
27.474
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.896
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o PECO_P1-2_5012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.88 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:3485.9
MW Contribution:
4.88
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
5.467
200194DELTA CT3
50/50
5.467
200204Y1-065-CTG1
50/50
10.599
200054ROCKSP 3
50/50
6.746
231912HR6
50/50
2.885
231913HR7
50/50
2.885
233920W3-032A-CTG1
50/50
4.189
232901NORTHST
50/50
17.278
232917OH NUG6
50/50
18.199
200202DELTA2 ST
50/50
16.568
200195DELTA ST
50/50
8.445
200052ROCKSP 1
50/50
6.668
200053ROCKSP 2
50/50
6.538
232616GEN FOOD
50/50
0.339
232904IR4
50/50
167.426
232920IR10
50/50
6.543
232912OH NUG1
50/50
18.28
232913OH NUG2
50/50
18.037
232432Z2-076 GEN
Solar/Wind Harmer
0.026
971195AH1-057 GEN
Solar/Wind Harmer
1.218
232813VAUGHN
Adder
1.135
233968AD2-076_GEN
Solar/Wind Harmer
4.396
970597AG2-380 GEN
Solar/Wind Harmer
7.874
231906DC3 NUG
Adder
26.227
231902DC CT7
Adder
20.967
231907DC10
Adder
6.548
233915AB1-141 GEN
Solar/Wind Harmer
0.477
231919CHRIST1
Adder
7.005
231920CHRIST2
Adder
6.849
970453AG2-297 GEN
Solar/Wind Harmer
2.974
230422AE1-104_GEN1
Solar/Wind Harmer
14.918
230425AE1-104_GEN2
Solar/Wind Harmer
14.918
972141AH1-641 GEN
Solar/Wind Harmer
1.674
230430AE1-229_GEN
Solar/Wind Harmer
21.218
964001AG1-254 GEN
Solar/Wind Harmer
5.968
207487AE2-000G4
Solar/Wind Harmer
9.732
207497AE2-000G2
Solar/Wind Harmer
9.732
207500AE2-000G1
Solar/Wind Harmer
9.732
232915OH NUG4
50/50
18.158
233970AC1-092 C
Solar/Wind Harmer
3.526
234033AF1-007_GEN
Solar/Wind Harmer
26.949
232404W1-003 C
Solar/Wind Harmer
1.259
232408W1-005 C
Solar/Wind Harmer
1.259
972177AH1-672 GEN
Solar/Wind Harmer
19.855
232900DEMECSMY
Adder
17.968
232919VN10
Adder
5.464
232902EASTMUNI
Adder
25.121
234012AE2-112_GEN
Solar/Wind Harmer
4.396
233918AB1-142 GEN
Solar/Wind Harmer
0.477
972251AH1-710 GEN
Adder
79.377
231918WEST 1
Adder
5.37
231917EM10
Adder
3.587
228206SHRMN CT
Adder
18.904
228732V1-021 C
Adder
0.214
970997AG2-616 GEN
Solar/Wind Harmer
7.738
228400MICK 1CT
Adder
11.306
213497CHSTR7-9
Adder
2.061
213497CHSTR7-9
Adder
2.061
207522AF2-254 C
Solar/Wind Harmer
0.703
219222BRL12CT2
Adder
6.546
213611FALLS1-3
Adder
2.31
213958STHWK5-6
Adder
1.753
213560DLW11-12
Adder
1.672
20635828PARLN1&2
Adder
4.068
20635028RRCT1&2
Adder
6.303
218524CNTRALGAS1 C
Solar/Wind Harmer
0.385
972275AH1-722 GEN
Adder
15.212
200201DELTA2 CT2
50/50
9.784
200034PCHBTM 2
50/50
56.95
200205Y1-065-CTG2
50/50
10.599
232918OH NUG7
50/50
18.158
232905CHERITON_25
50/50
5.078
232926CRISFLD1
50/50
4.062
232910NRG_G1
50/50
17.584
200035PCHBTM 3
50/50
-13.738
233971AC1-093 C
Solar/Wind Harmer
3.526
207507AE2-000G3
Solar/Wind Harmer
9.732
963401AG1-189 GEN
Solar/Wind Harmer
0.85
970025AG2-016 GEN
Solar/Wind Harmer
1.372
219224BRL12CT4
Adder
6.546
971189AH1-054 GEN
Solar/Wind Harmer
0.562
213611FALLS1-3
Adder
2.31
213611FALLS1-3
Adder
2.31
213942SCHUYLKILL
Adder
2.293
213942SCHUYLKILL
Adder
1.754
213957STHWK3-4
Adder
1.753
213957STHWK3-4
Adder
1.753
213561DLWR9-10
Adder
2.187
213561DLWR9-10
Adder
1.672
971521AH1-258 GEN
Solar/Wind Harmer
1.063
20635928PARLN3&4
Adder
4.068
218526CNTRALGAS2 C
Solar/Wind Harmer
0.387
200200DELTA2 CT1
50/50
9.784
200193DELTA CT2
50/50
5.467
200203Y1-065-STG
50/50
18.356
200055ROCKSP 4
50/50
6.629
231914HR8
50/50
4.385
231911HR5
50/50
2.885
233921W3-032A-STG1
50/50
2.707
232914OH NUG3
50/50
18.28
232916OH NUG5
50/50
18.28
232921TASLEY2G
50/50
10.684
234034AF2-060
50/50
3.656
232911NRG_G2
50/50
0.962
233987AB2-037 GEN
Solar/Wind Harmer
-0.003
233973AC2-185 C
Solar/Wind Harmer
3.526
970695AG2-447 GEN
Solar/Wind Harmer
4.885
233939AC1-091 C
Solar/Wind Harmer
3.526
233972AC1-094 C
Solar/Wind Harmer
3.526
232434Z2-077 GEN
Solar/Wind Harmer
0.081
232406W1-004 FULL
Solar/Wind Harmer
1.259
232907VN8
Adder
58.549
232422X3-066 FULL
Solar/Wind Harmer
0.157
233935AB2-179 C
Solar/Wind Harmer
2.439
232410W1-006 C
Solar/Wind Harmer
1.259
231940T-011
Adder
1.454
232899W1-062
Adder
18.733
234041AC1-190 GEN
Solar/Wind Harmer
14.156
233984AB2-036 GEN
Solar/Wind Harmer
13.883
234014AF1-036_GEN
Solar/Wind Harmer
4.396
233930AB2-032 GEN
Solar/Wind Harmer
1.792
228251CARLLS#4
Adder
0.695
228201CARL#2CT
Adder
7.569
228200CARL#1CT
Adder
7.199
228307PCLP GT
Adder
12.171
972233AH1-701 GEN
Adder
4.052
20636128O CRK C2
Adder
4.96
213589EDDYSTN4
Adder
59.196
213587EDDYSTN3
Adder
59.104
219304NAMERICA C
Solar/Wind Harmer
0.067
213535CROYDN11
Adder
7.313
20628028LAKEHURS
Adder
0.682
20714828MDF_W3-079
Solar/Wind Harmer
0.067
20635028RRCT1&2
Adder
6.206
20635128RRCT3&4
Adder
5.991
20635128RRCT3&4
Adder
5.226
218418LINDEN_G5
Adder
8.275
218419LINDEN_G6
Adder
8.275
972260AH1-715 GEN1
Adder
6.626
20636028O CRK C1
Adder
5.439
213497CHSTR7-9
Adder
2.061
963391AG1-188 GEN
Solar/Wind Harmer
1.37
219221BRL12CT1
Adder
6.546
219223BRL12CT3
Adder
6.546
971667AH1-334 GEN
Solar/Wind Harmer
1.286
213958STHWK5-6
Adder
1.753
213560DLW11-12
Adder
1.672
20635828PARLN1&2
Adder
1.842
20635928PARLN3&4
Adder
1.842
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.327
VTFLTFEXP_VFT->PJM
CMTX
60.398
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.998
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.044
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.185
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.478
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
27.411
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.817
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z1 line l/o PECO_P4_PEACH255_SRT-A/* $ CHESCO $ PECO_P4_PEACH255 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z1 line
Contingency Name:
PECO_P4_PEACH255_SRT-A/* $ CHESCO $ PECO_P4_PEACH255 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.7 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:3366.11
MW Contribution:
6.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
5.606
200053ROCKSP 2
50/50
5.496
232616GEN FOOD
50/50
0.319
232904IR4
50/50
157.523
200204Y1-065-CTG1
50/50
8.911
200054ROCKSP 3
50/50
5.671
231912HR6
50/50
2.693
231913HR7
50/50
2.693
233920W3-032A-CTG1
50/50
3.941
232901NORTHST
50/50
16.255
232917OH NUG6
50/50
17.122
232915OH NUG4
50/50
17.084
232900DEMECSMY
50/50
17.951
232919VN10
50/50
5.456
233970AC1-092 C
Solar/Wind Harmer
4.931
234033AF1-007_GEN
Solar/Wind Harmer
68.291
232404W1-003 C
Solar/Wind Harmer
1.835
232408W1-005 C
Solar/Wind Harmer
1.835
233996TM1833_GEN
Solar/Wind Harmer
1.829
233998TM1NIN_3.36
Solar/Wind Harmer
1.829
972177AH1-672 GEN
Solar/Wind Harmer
24.646
232426Y1-080 FULL
Solar/Wind Harmer
0.35
232902EASTMUNI
Adder
23.674
234012AE2-112_GEN
Solar/Wind Harmer
4.113
233944AB2-135 GEN
Solar/Wind Harmer
9.301
233918AB1-142 GEN
Solar/Wind Harmer
1.753
972251AH1-710 GEN
Adder
76.732
231918WEST 1
Adder
5.321
231917EM10
Adder
3.612
228206SHRMN CT
Adder
20.518
228732V1-021 C
Adder
0.233
228260V4-054C
Solar/Wind Harmer
1.243
970997AG2-616 GEN
Solar/Wind Harmer
11.432
228729W2-030 C
Solar/Wind Harmer
0.688
228400MICK 1CT
Adder
13.159
219686LUMSOLAR_N C
Solar/Wind Harmer
0.214
219766PARADISE C
Solar/Wind Harmer
0.321
219907AC1-030 C
Solar/Wind Harmer
0.137
213497CHSTR7-9
Adder
2.674
213497CHSTR7-9
Adder
2.674
20716028EGP_W2-019
Solar/Wind Harmer
0.448
207522AF2-254 C
Solar/Wind Harmer
1.384
20717128DIX_Z2-102
Solar/Wind Harmer
1.272
20715828PEM_W1-120
Solar/Wind Harmer
0.514
219348LDSOLAR C
Solar/Wind Harmer
0.573
219222BRL12CT2
Adder
8.544
213958STHWK5-6
Adder
2.467
213611FALLS1-3
Adder
3.189
963711AG1-223 GEN
Solar/Wind Harmer
1.345
20714528FRN_Y2-051
Solar/Wind Harmer
0.268
213560DLW11-12
Adder
2.41
20720528MAN_W1-024
Solar/Wind Harmer
0.22
20715228NPK_W1-113
Solar/Wind Harmer
0.372
219276PARKLANDSO C
Solar/Wind Harmer
0.396
20720428HOL_W1-112
Solar/Wind Harmer
0.295
219680HOPEWELLV C1
Solar/Wind Harmer
0.063
20635828PARLN1&2
Adder
6.048
20635028RRCT1&2
Adder
9.508
218524CNTRALGAS1 C
Solar/Wind Harmer
0.29
218440SUMMTASSOC C
Solar/Wind Harmer
0.1
218428ETC SOLAR C
Solar/Wind Harmer
0.028
219908AB1-139 C
Solar/Wind Harmer
0.296
219919AE1-041 FULL
Solar/Wind Harmer
0.031
972275AH1-722 GEN
Adder
24.289
217209CENTRL HS C
Solar/Wind Harmer
0.033
20673628F1S_V4-069
Solar/Wind Harmer
0.131
207528AF2-192 GEN
Solar/Wind Harmer
0.931
217186ESSEX_G9
Adder
2.897
217121ECCF
Adder
0.319
217083KRNY_132
Adder
6.819
217208PARK ELE C
Solar/Wind Harmer
0.019
214194N WALES4
Adder
0.581
20671828STAW2-080
Solar/Wind Harmer
0.075
20676728BRNX1-095
Solar/Wind Harmer
0.124
207439AE1-081 C O1
Solar/Wind Harmer
0.04
966261AG1-495 GEN
Solar/Wind Harmer
2.328
20676328BVR_Y1-020
Solar/Wind Harmer
0.221
20674628WNG_W3-110
Solar/Wind Harmer
0.268
20676228FRD_X1-012
Solar/Wind Harmer
0.392
207530AG1-191 GEN
Solar/Wind Harmer
0.906
20675828AU_W4-064
Solar/Wind Harmer
0.114
20674928WA_W3-044
Solar/Wind Harmer
0.304
971519AH1-257 GEN
Solar/Wind Harmer
1.565
20675728RH_W2-091
Solar/Wind Harmer
0.369
207518AF1-320_GEN
Solar/Wind Harmer
2.23
20465127PORT CT
Adder
1.817
207484AF2-139 C O1
Solar/Wind Harmer
0.305
208909MACR G3
Adder
92.554
211065PSPA IPP
Solar/Wind Harmer
0.245
232920IR10
50/50
6.156
232912OH NUG1
50/50
17.199
232913OH NUG2
50/50
16.97
232813VAUGHN
50/50
1.135
232432Z2-076 GEN
Solar/Wind Harmer
0.242
233901CHERRYDALE C
Solar/Wind Harmer
2.064
233940AF2-379 C
Solar/Wind Harmer
0.342
971195AH1-057 GEN
Solar/Wind Harmer
1.788
233955AB2-172 GEN
Solar/Wind Harmer
9.136
233968AD2-076_GEN
Solar/Wind Harmer
11.855
970597AG2-380 GEN
Solar/Wind Harmer
7.444
231906DC3 NUG
Adder
24.876
231902DC CT7
Adder
19.887
231907DC10
Adder
6.21
233915AB1-141 GEN
Solar/Wind Harmer
1.753
231919CHRIST1
Adder
6.963
231920CHRIST2
Adder
6.809
970453AG2-297 GEN
Solar/Wind Harmer
3.467
230422AE1-104_GEN1
Solar/Wind Harmer
40.798
230425AE1-104_GEN2
Solar/Wind Harmer
40.798
972141AH1-641 GEN
Solar/Wind Harmer
3.43
230430AE1-229_GEN
Solar/Wind Harmer
34.063
227927V4-067C
Solar/Wind Harmer
0.236
964001AG1-254 GEN
Solar/Wind Harmer
8.616
228728W1-130C
Solar/Wind Harmer
0.784
230407AD2-065 C
Solar/Wind Harmer
0.153
230434AG1-499 GEN
Solar/Wind Harmer
0.668
219137THOSOLAR C
Solar/Wind Harmer
1.285
219258KINSLEYDEP C
Solar/Wind Harmer
0.336
219615MILLCREEK C
Solar/Wind Harmer
0.231
207487AE2-000G4
Solar/Wind Harmer
30.588
207497AE2-000G2
Solar/Wind Harmer
30.588
207500AE2-000G1
Solar/Wind Harmer
30.588
207507AE2-000G3
Solar/Wind Harmer
30.588
20720728JCB_W1-129
Solar/Wind Harmer
0.288
20715028HAN_X4-015
Solar/Wind Harmer
0.288
219610FLORENCE C
Solar/Wind Harmer
1.325
219224BRL12CT4
Adder
8.544
963401AG1-189 GEN
Solar/Wind Harmer
2.187
970025AG2-016 GEN
Solar/Wind Harmer
2.713
971189AH1-054 GEN
Solar/Wind Harmer
1.12
207445AB1-138_GEN
Solar/Wind Harmer
0.542
213942SCHUYLKILL
Adder
3.227
213942SCHUYLKILL
Adder
2.467
213957STHWK3-4
Adder
2.467
213957STHWK3-4
Adder
2.467
213611FALLS1-3
Adder
3.189
213611FALLS1-3
Adder
3.189
213561DLWR9-10
Adder
3.151
213561DLWR9-10
Adder
2.41
20714428HOW_X1-037
Solar/Wind Harmer
1.087
20720628TIN_W1-124
Solar/Wind Harmer
0.87
20716228APLW2-078
Solar/Wind Harmer
0.764
971521AH1-258 GEN
Solar/Wind Harmer
2.323
219620RIDERU C
Solar/Wind Harmer
0.047
20635928PARLN3&4
Adder
6.048
218526CNTRALGAS2 C
Solar/Wind Harmer
0.291
218449LINSOLAR C
Solar/Wind Harmer
0.761
20675528CPH_W2-050
Solar/Wind Harmer
0.427
20673828FLE_V3-070
Solar/Wind Harmer
0.344
20676128MHD_W3-029
Solar/Wind Harmer
0.35
20676428JCR_X2-075
Solar/Wind Harmer
0.249
217167KRNY_14
Adder
6.819
217086KRNY_131
Adder
6.762
217147KRNY_1212
Adder
6.486
217147KRNY_1212
Adder
6.371
217146KRNY_1234
Adder
6.356
217146KRNY_1234
Adder
6.313
964851AG1-348 GEN
Solar/Wind Harmer
0.853
971009AG2-626 GEN
Solar/Wind Harmer
1.022
207408W3-077 C
Solar/Wind Harmer
0.31
20675128HRM_W1-127
Solar/Wind Harmer
0.102
20462827N BANGR8
Adder
0.427
961261AF2-417 GEN
Solar/Wind Harmer
0.534
200203Y1-065-STG
50/50
15.433
200055ROCKSP 4
50/50
5.573
231914HR8
50/50
4.093
231911HR5
50/50
2.693
233921W3-032A-STG1
50/50
2.547
232914OH NUG3
50/50
17.199
232916OH NUG5
50/50
17.199
232921TASLEY2G
50/50
10.052
234034AF2-060
50/50
3.44
233900O-025 C
50/50
0.125
232907VN8
50/50
58.449
232911NRG_G2
50/50
0.907
233973AC2-185 C
Solar/Wind Harmer
9.961
200034PCHBTM 2
50/50
47.255
200205Y1-065-CTG2
50/50
8.911
232918OH NUG7
50/50
17.084
232905CHERITON_25
50/50
4.777
232926CRISFLD1
50/50
3.822
231940T-011
50/50
1.452
232899W1-062
50/50
18.715
232910NRG_G1
50/50
16.591
233971AC1-093 C
Solar/Wind Harmer
4.682
232410W1-006 C
Solar/Wind Harmer
1.835
234015AF2-250 C
Solar/Wind Harmer
0.22
232428Y3-058 C
Solar/Wind Harmer
1.528
233994AC2-023 GEN
Solar/Wind Harmer
4.922
233946AB2-136 GEN
Solar/Wind Harmer
7.297
234036AF2-325 C
Solar/Wind Harmer
1.676
234041AC1-190 GEN
Solar/Wind Harmer
16.372
233952AC2-187 GEN
Solar/Wind Harmer
2.055
233954AC2-188 GEN
Solar/Wind Harmer
2.055
970695AG2-447 GEN
Solar/Wind Harmer
6.59
233939AC1-091 C
Solar/Wind Harmer
4.931
233972AC1-094 C
Solar/Wind Harmer
3.96
233987AB2-037 GEN
Solar/Wind Harmer
20.91
232434Z2-077 GEN
Solar/Wind Harmer
0.459
232406W1-004 FULL
Solar/Wind Harmer
1.835
233923SMA
Solar/Wind Harmer
6.705
233997TMININ_4.2
Solar/Wind Harmer
1.829
233964AF2-378 GEN
Solar/Wind Harmer
0.233
232417X3-008 C
Solar/Wind Harmer
2.056
233950AC2-186 GEN
Solar/Wind Harmer
1.027
232422X3-066 FULL
Solar/Wind Harmer
0.446
233933AB2-153 GEN
Solar/Wind Harmer
1.993
233935AB2-179 C
Solar/Wind Harmer
4.237
228711V2-041C
Solar/Wind Harmer
0.745
230415AB2-049 C
Solar/Wind Harmer
0.223
219291REEVESSOUT C
Solar/Wind Harmer
0.064
218660EHAMPSOLAR C
Solar/Wind Harmer
0.186
219688LUMSOLAR_S C
Solar/Wind Harmer
0.212
219623KINSLEYBEA C
Solar/Wind Harmer
0.448
219921AF1-264
Solar/Wind Harmer
0.149
219914AD2-027 C
Solar/Wind Harmer
0.6
219236SOUTHERNHQ C
Solar/Wind Harmer
0.067
213497CHSTR7-9
Adder
2.674
20636028O CRK C1
Adder
6.863
20716428NHV_W2-082
Solar/Wind Harmer
1.716
20715728PEM_W1-119
Solar/Wind Harmer
0.514
219221BRL12CT1
Adder
8.544
219223BRL12CT3
Adder
8.544
963391AG1-188 GEN
Solar/Wind Harmer
3.585
971667AH1-334 GEN
Solar/Wind Harmer
2.583
20714928UPF_X1-085
Solar/Wind Harmer
0.38
959561AF2-247 GEN
Solar/Wind Harmer
0.447
213958STHWK5-6
Adder
2.467
213560DLW11-12
Adder
2.41
219114HARTZY_C
Solar/Wind Harmer
0.741
219727YARDVSOLFA C
Solar/Wind Harmer
0.8
233984AB2-036 GEN
Solar/Wind Harmer
22.451
232424Y1-079 C
Solar/Wind Harmer
1.012
234014AF1-036_GEN
Solar/Wind Harmer
4.839
232436AB1-176 C
Solar/Wind Harmer
0.409
233930AB2-032 GEN
Solar/Wind Harmer
1.476
233982AB2-133 GEN
Solar/Wind Harmer
8.615
228251CARLLS#4
Adder
0.764
228201CARL#2CT
Adder
8.327
228200CARL#1CT
Adder
7.92
230433AD2-135 GEN
Solar/Wind Harmer
0.12
228754AB1-001 C
Solar/Wind Harmer
0.165
230511AF1-262
Solar/Wind Harmer
0.217
228351V2-046C
Solar/Wind Harmer
2.378
228307PCLP GT
Adder
13.88
972233AH1-701 GEN
Adder
4.699
219272CLEANLIGHT C
Solar/Wind Harmer
0.194
219287REEVESEAST C
Solar/Wind Harmer
1.426
219904AC1-010 C
Solar/Wind Harmer
0.385
219912AD2-042 GEN
Solar/Wind Harmer
0.795
213589EDDYSTN4
Adder
77.452
213587EDDYSTN3
Adder
77.39
219906AC1-017 C
Solar/Wind Harmer
0.216
20636128O CRK C2
Adder
6.258
20720828JCB_W4-025
Solar/Wind Harmer
0.437
219607WPEMNERT C
Solar/Wind Harmer
0.401
219304NAMERICA C
Solar/Wind Harmer
0.297
213535CROYDN11
Adder
9.671
207459AE1-142 C O1
Solar/Wind Harmer
0.995
20628028LAKEHURS
Adder
0.889
214067T20SOLAR
Solar/Wind Harmer
0.228
20714828MDF_W3-079
Solar/Wind Harmer
0.278
20641628MLH_W1-032
Solar/Wind Harmer
0.255
20742028HF_AC1-207
Solar/Wind Harmer
0.675
219817TRENTONSOL C
Solar/Wind Harmer
0.929
217197RE CRAN C
Solar/Wind Harmer
0.439
218438BLK ROCK C
Solar/Wind Harmer
0.111
20635028RRCT1&2
Adder
9.362
20635128RRCT3&4
Adder
9.037
20635128RRCT3&4
Adder
7.883
924131AB2-057 GEN
Solar/Wind Harmer
0.821
218418LINDEN_G5
Adder
13.212
218419LINDEN_G6
Adder
13.212
972260AH1-715 GEN1
Adder
10.58
219036LINDEN_G7
Adder
12.66
219035LINDEN_G8
Adder
12.48
972261AH1-715 GEN2
Adder
12.119
217081WEATEXAS C
Solar/Wind Harmer
0.064
217202FBANKSOLAR C
Solar/Wind Harmer
0.055
20675428EAM_W2-061
Solar/Wind Harmer
0.138
217201HACKENSOLA C
Solar/Wind Harmer
0.054
972237AH1-703 GEN
Adder
7.43
217206BARNGR HS C
Solar/Wind Harmer
0.023
217086KRNY_131
Adder
6.834
217083KRNY_132
Adder
6.776
217204WCALDSOLAR C
Solar/Wind Harmer
0.053
213815MOSER1-3
Adder
2.391
213815MOSER1-3
Adder
2.391
20674328GAR_V4-001
Solar/Wind Harmer
0.072
20674828DL_W4-046
Solar/Wind Harmer
0.41
207471AF2-354 C
Solar/Wind Harmer
0.323
20634528N27_Y2-018
Solar/Wind Harmer
0.168
20465127PORT CT
Adder
2.411
20675928HOL_W4-097
Solar/Wind Harmer
0.079
223401AF1-299 GEN
Solar/Wind Helper
0.35
223402AF1-300 C
Solar/Wind Helper
0.35
207454AA2-184 E
Solar/Wind Harmer
0.873
219918AC2-009 C
Solar/Wind Harmer
0.021
20716928W4-060COL
Solar/Wind Harmer
0.596
219612MATRIX C
Solar/Wind Harmer
0.15
20635828PARLN1&2
Adder
2.739
20635928PARLN3&4
Adder
2.739
217213AMBOY SO C
Solar/Wind Harmer
0.098
219249CENTRALDIV C
Solar/Wind Harmer
0.03
217211CAMDEN ST C
Solar/Wind Harmer
0.018
207442AE1-156 GEN
Solar/Wind Harmer
0.544
20673728F2S_V4-070
Solar/Wind Harmer
0.131
217169METRODIV C
Solar/Wind Harmer
0.029
217194REDH C
Solar/Wind Harmer
0.361
213815MOSER1-3
Adder
2.391
20674528F3S_W2-016
Solar/Wind Harmer
0.97
207511W3-106 GEN
Solar/Wind Harmer
0.219
207510AF2-138 C
Solar/Wind Harmer
1.181
971007AG2-625 GEN
Solar/Wind Harmer
1.602
20466127PORT 5CT
Adder
16.112
207437AD2-070 GEN
Solar/Wind Harmer
0.181
20671928W4-073
Solar/Wind Harmer
0.259
20465427SHAW CT
Adder
2.326
20674128FR_U2-059
Solar/Wind Harmer
0.11
20633028GILCT9
Adder
16.799
209116AE2-175 GEN
Solar/Wind Harmer
2.317
211065PSPA IPP
Solar/Wind Harmer
0.245
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.755
VTFLTFEXP_VFT->PJM
CMTX
100.535
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.235
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.265
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.171
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
15.286
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
41.35
CBM NorthLTFEXP_CBM-N->PJM
CBM
47.408
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.07 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:665.09
MW Contribution:
1.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.552
233935AB2-179 C
Solar/Wind Harmer
1.159
213497CHSTR7-9
Adder
1.074
233933AB2-153 GEN
Solar/Wind Harmer
0.462
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.416
233987AB2-037 GEN
Solar/Wind Harmer
4.192
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.964
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.324
233997TMININ_4.2
Solar/Wind Harmer
0.361
232406W1-004 FULL
Solar/Wind Harmer
0.362
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
232921TASLEY2G
Adder
1.868
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.873
970695AG2-447 GEN
Solar/Wind Harmer
1.239
233939AC1-091 C
Solar/Wind Harmer
0.927
233972AC1-094 C
Solar/Wind Harmer
0.745
213815MOSER1-3
Adder
1.097
219914AD2-027 C
Solar/Wind Harmer
0.184
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.227
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20716428NHV_W2-082
Solar/Wind Harmer
0.476
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20636028O CRK C1
Adder
1.854
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963391AG1-188 GEN
Solar/Wind Harmer
0.98
971667AH1-334 GEN
Solar/Wind Harmer
0.715
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.251
219612MATRIX C
Solar/Wind Harmer
0.046
20716928W4-060COL
Solar/Wind Harmer
0.175
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
217213AMBOY SO C
Solar/Wind Harmer
0.03
219249CENTRALDIV C
Solar/Wind Harmer
0.009
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20673728F2S_V4-070
Solar/Wind Harmer
0.043
213514CONOW1-2
50/50
0.552
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
233915AB1-141 GEN
Solar/Wind Harmer
0.407
233968AD2-076_GEN
Solar/Wind Harmer
2.658
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.42
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.849
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.353
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.135
232904IR4
Adder
29.017
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
219137THOSOLAR C
Solar/Wind Harmer
0.375
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.188
230434AG1-499 GEN
Solar/Wind Harmer
0.174
972141AH1-641 GEN
Solar/Wind Harmer
0.858
230430AE1-229_GEN
Solar/Wind Harmer
8.528
219615MILLCREEK C
Solar/Wind Harmer
0.071
228728W1-130C
Solar/Wind Harmer
0.195
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219224BRL12CT4
Adder
2.608
230422AE1-104_GEN1
Solar/Wind Harmer
9.701
230425AE1-104_GEN2
Solar/Wind Harmer
9.701
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
207487AE2-000G4
Solar/Wind Harmer
8.262
207497AE2-000G2
Solar/Wind Harmer
8.262
207500AE2-000G1
Solar/Wind Harmer
8.262
207507AE2-000G3
Solar/Wind Harmer
8.262
971189AH1-054 GEN
Solar/Wind Harmer
0.31
963401AG1-189 GEN
Solar/Wind Harmer
0.595
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207445AB1-138_GEN
Solar/Wind Harmer
0.15
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.311
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20716228APLW2-078
Solar/Wind Harmer
0.221
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.14
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.112
20676128MHD_W3-029
Solar/Wind Harmer
0.114
213508CON10-11
50/50
0.998
213508CON10-11
50/50
0.998
213518CONOW8-9
50/50
0.998
213518CONOW8-9
50/50
0.998
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.44
213587EDDYSTN3
Adder
31.412
233982AB2-133 GEN
Solar/Wind Harmer
2.006
233930AB2-032 GEN
Solar/Wind Harmer
0.342
232436AB1-176 C
Solar/Wind Harmer
0.092
234014AF1-036_GEN
Solar/Wind Harmer
1.085
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
232910NRG_G1
Adder
3.244
234041AC1-190 GEN
Solar/Wind Harmer
3.31
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.467
233952AC2-187 GEN
Solar/Wind Harmer
0.409
233954AC2-188 GEN
Solar/Wind Harmer
0.409
233994AC2-023 GEN
Solar/Wind Harmer
0.976
232428Y3-058 C
Solar/Wind Harmer
0.303
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.711
232410W1-006 C
Solar/Wind Harmer
0.362
232918OH NUG7
Adder
3.175
232905CHERITON_25
Adder
0.888
231940T-011
Adder
0.269
232899W1-062
Adder
3.395
233971AC1-093 C
Solar/Wind Harmer
0.88
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.244
228307PCLP GT
Adder
3.695
228351V2-046C
Solar/Wind Harmer
0.605
230511AF1-262
Solar/Wind Harmer
0.054
228201CARL#2CT
Adder
2.031
228200CARL#1CT
Adder
1.931
228251CARLLS#4
Adder
0.186
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
213535CROYDN11
Adder
3.003
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
219607WPEMNERT C
Solar/Wind Harmer
0.122
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.388
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.121
20636128O CRK C2
Adder
1.69
207459AE1-142 C O1
Solar/Wind Harmer
0.274
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20714828MDF_W3-079
Solar/Wind Harmer
0.078
20641628MLH_W1-032
Solar/Wind Harmer
0.073
217197RE CRAN C
Solar/Wind Harmer
0.135
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.196
924131AB2-057 GEN
Solar/Wind Harmer
0.252
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.719
20635128RRCT3&4
Adder
2.371
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
20675428EAM_W2-061
Solar/Wind Harmer
0.045
223401AF1-299 GEN
Solar/Wind Helper
0.272
223402AF1-300 C
Solar/Wind Helper
0.272
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233918AB1-142 GEN
Solar/Wind Harmer
0.407
233944AB2-135 GEN
Solar/Wind Harmer
2.12
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.99
232902EASTMUNI
Adder
4.959
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.027
233996TM1833_GEN
Solar/Wind Harmer
0.361
233998TM1NIN_3.36
Solar/Wind Harmer
0.361
232404W1-003 C
Solar/Wind Harmer
0.362
232408W1-005 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.175
234033AF1-007_GEN
Solar/Wind Harmer
13.348
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233970AC1-092 C
Solar/Wind Harmer
0.927
228400MICK 1CT
Adder
3.642
219766PARADISE C
Solar/Wind Harmer
0.096
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.86
228260V4-054C
Solar/Wind Harmer
0.303
228206SHRMN CT
Adder
4.831
219348LDSOLAR C
Solar/Wind Harmer
0.175
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.809
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
228729W2-030 C
Solar/Wind Harmer
0.165
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
20716028EGP_W2-019
Solar/Wind Harmer
0.124
207522AF2-254 C
Solar/Wind Harmer
0.384
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715828PEM_W1-120
Solar/Wind Harmer
0.142
219276PARKLANDSO C
Solar/Wind Harmer
0.122
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.86
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
972275AH1-722 GEN
Adder
7.525
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.302
208909MACR G3
Adder
32.158
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
VTFLTFEXP_VFT->PJM
CMTX
31.565
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.608
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.956
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.616
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.439
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.039
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.97 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:664.51
MW Contribution:
1.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
207487AE2-000G4
Solar/Wind Harmer
8.265
207497AE2-000G2
Solar/Wind Harmer
8.265
207500AE2-000G1
Solar/Wind Harmer
8.265
207507AE2-000G3
Solar/Wind Harmer
8.265
971189AH1-054 GEN
Solar/Wind Harmer
0.31
963401AG1-189 GEN
Solar/Wind Harmer
0.595
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207445AB1-138_GEN
Solar/Wind Harmer
0.15
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.311
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20716228APLW2-078
Solar/Wind Harmer
0.222
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20635928PARLN3&4
Adder
1.807
20675528CPH_W2-050
Solar/Wind Harmer
0.14
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.112
20676128MHD_W3-029
Solar/Wind Harmer
0.114
207522AF2-254 C
Solar/Wind Harmer
0.384
20717128DIX_Z2-102
Solar/Wind Harmer
0.353
20715828PEM_W1-120
Solar/Wind Harmer
0.142
219276PARKLANDSO C
Solar/Wind Harmer
0.122
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.807
20635028RRCT1&2
Adder
2.861
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
972275AH1-722 GEN
Adder
7.526
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.302
208909MACR G3
Adder
32.163
20636128O CRK C2
Adder
1.691
207459AE1-142 C O1
Solar/Wind Harmer
0.274
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20714828MDF_W3-079
Solar/Wind Harmer
0.078
20641628MLH_W1-032
Solar/Wind Harmer
0.073
217197RE CRAN C
Solar/Wind Harmer
0.135
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.196
924131AB2-057 GEN
Solar/Wind Harmer
0.253
20635028RRCT1&2
Adder
2.817
20635128RRCT3&4
Adder
2.719
20635128RRCT3&4
Adder
2.372
218418LINDEN_G5
Adder
4.094
218419LINDEN_G6
Adder
4.094
972260AH1-715 GEN1
Adder
3.278
20675428EAM_W2-061
Solar/Wind Harmer
0.045
223401AF1-299 GEN
Solar/Wind Helper
0.272
223402AF1-300 C
Solar/Wind Helper
0.272
20716428NHV_W2-082
Solar/Wind Harmer
0.476
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20636028O CRK C1
Adder
1.854
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963391AG1-188 GEN
Solar/Wind Harmer
0.98
971667AH1-334 GEN
Solar/Wind Harmer
0.715
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.251
219612MATRIX C
Solar/Wind Harmer
0.046
20716928W4-060COL
Solar/Wind Harmer
0.175
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
217213AMBOY SO C
Solar/Wind Harmer
0.03
219249CENTRALDIV C
Solar/Wind Harmer
0.009
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20673728F2S_V4-070
Solar/Wind Harmer
0.043
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.552
233935AB2-179 C
Solar/Wind Harmer
1.159
213514CONOW1-2
50/50
0.552
231919CHRIST1
Adder
1.883
231920CHRIST2
Adder
1.841
233915AB1-141 GEN
Solar/Wind Harmer
0.407
233968AD2-076_GEN
Solar/Wind Harmer
2.659
970597AG2-380 GEN
Solar/Wind Harmer
1.67
231906DC3 NUG
Adder
5.531
231902DC CT7
Adder
4.422
231907DC10
Adder
1.381
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.99
213957STHWK3-4
Adder
0.99
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.85
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.353
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232912OH NUG1
Adder
3.198
232913OH NUG2
Adder
3.155
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.136
232904IR4
Adder
29.032
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
219137THOSOLAR C
Solar/Wind Harmer
0.376
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.189
230434AG1-499 GEN
Solar/Wind Harmer
0.174
972141AH1-641 GEN
Solar/Wind Harmer
0.858
230430AE1-229_GEN
Solar/Wind Harmer
8.531
219615MILLCREEK C
Solar/Wind Harmer
0.071
228728W1-130C
Solar/Wind Harmer
0.195
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219224BRL12CT4
Adder
2.608
230422AE1-104_GEN1
Solar/Wind Harmer
9.704
230425AE1-104_GEN2
Solar/Wind Harmer
9.704
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
213508CON10-11
50/50
0.998
213508CON10-11
50/50
0.998
213518CONOW8-9
50/50
0.998
213518CONOW8-9
50/50
0.998
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.446
213587EDDYSTN3
Adder
31.419
233982AB2-133 GEN
Solar/Wind Harmer
2.006
233930AB2-032 GEN
Solar/Wind Harmer
0.342
232436AB1-176 C
Solar/Wind Harmer
0.092
234014AF1-036_GEN
Solar/Wind Harmer
1.085
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.868
232910NRG_G1
Adder
3.245
234041AC1-190 GEN
Solar/Wind Harmer
3.312
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.468
233952AC2-187 GEN
Solar/Wind Harmer
0.409
233954AC2-188 GEN
Solar/Wind Harmer
0.409
233994AC2-023 GEN
Solar/Wind Harmer
0.976
232428Y3-058 C
Solar/Wind Harmer
0.303
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.712
232410W1-006 C
Solar/Wind Harmer
0.362
232918OH NUG7
Adder
3.177
232905CHERITON_25
Adder
0.888
231940T-011
Adder
0.27
232899W1-062
Adder
3.396
233971AC1-093 C
Solar/Wind Harmer
0.881
972233AH1-701 GEN
Adder
1.292
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.244
228307PCLP GT
Adder
3.696
228351V2-046C
Solar/Wind Harmer
0.605
230511AF1-262
Solar/Wind Harmer
0.054
228201CARL#2CT
Adder
2.032
228200CARL#1CT
Adder
1.932
228251CARLLS#4
Adder
0.186
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
213535CROYDN11
Adder
3.004
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
219607WPEMNERT C
Solar/Wind Harmer
0.122
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.388
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.121
213497CHSTR7-9
Adder
1.074
233933AB2-153 GEN
Solar/Wind Harmer
0.462
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.416
233987AB2-037 GEN
Solar/Wind Harmer
4.194
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.97
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.325
233997TMININ_4.2
Solar/Wind Harmer
0.361
232406W1-004 FULL
Solar/Wind Harmer
0.362
232914OH NUG3
Adder
3.198
232916OH NUG5
Adder
3.198
232921TASLEY2G
Adder
1.869
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.874
970695AG2-447 GEN
Solar/Wind Harmer
1.24
233939AC1-091 C
Solar/Wind Harmer
0.928
233972AC1-094 C
Solar/Wind Harmer
0.745
213815MOSER1-3
Adder
1.097
219914AD2-027 C
Solar/Wind Harmer
0.184
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.227
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.445
231917EM10
Adder
1.009
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233918AB1-142 GEN
Solar/Wind Harmer
0.407
233944AB2-135 GEN
Solar/Wind Harmer
2.121
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.99
232902EASTMUNI
Adder
4.962
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.028
233996TM1833_GEN
Solar/Wind Harmer
0.361
233998TM1NIN_3.36
Solar/Wind Harmer
0.361
232404W1-003 C
Solar/Wind Harmer
0.362
232408W1-005 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.184
232915OH NUG4
Adder
3.177
234033AF1-007_GEN
Solar/Wind Harmer
13.356
972177AH1-672 GEN
Solar/Wind Harmer
4.817
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.258
232901NORTHST
Adder
2.902
233970AC1-092 C
Solar/Wind Harmer
0.928
228400MICK 1CT
Adder
3.643
219766PARADISE C
Solar/Wind Harmer
0.096
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.861
228260V4-054C
Solar/Wind Harmer
0.303
228206SHRMN CT
Adder
4.833
219348LDSOLAR C
Solar/Wind Harmer
0.175
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.817
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
228729W2-030 C
Solar/Wind Harmer
0.165
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
20716028EGP_W2-019
Solar/Wind Harmer
0.124
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
VTFLTFEXP_VFT->PJM
CMTX
31.572
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.608
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.617
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.957
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.442
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.041
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.92 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:664.26
MW Contribution:
1.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.552
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
233915AB1-141 GEN
Solar/Wind Harmer
0.407
233968AD2-076_GEN
Solar/Wind Harmer
2.658
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.42
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.849
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.353
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.135
232904IR4
Adder
29.017
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
219137THOSOLAR C
Solar/Wind Harmer
0.375
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.188
230434AG1-499 GEN
Solar/Wind Harmer
0.174
972141AH1-641 GEN
Solar/Wind Harmer
0.858
230430AE1-229_GEN
Solar/Wind Harmer
8.528
219615MILLCREEK C
Solar/Wind Harmer
0.071
228728W1-130C
Solar/Wind Harmer
0.195
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219224BRL12CT4
Adder
2.608
230422AE1-104_GEN1
Solar/Wind Harmer
9.701
230425AE1-104_GEN2
Solar/Wind Harmer
9.701
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
207487AE2-000G4
Solar/Wind Harmer
8.262
207497AE2-000G2
Solar/Wind Harmer
8.262
207500AE2-000G1
Solar/Wind Harmer
8.262
207507AE2-000G3
Solar/Wind Harmer
8.262
971189AH1-054 GEN
Solar/Wind Harmer
0.31
963401AG1-189 GEN
Solar/Wind Harmer
0.595
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207445AB1-138_GEN
Solar/Wind Harmer
0.15
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.311
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20716228APLW2-078
Solar/Wind Harmer
0.221
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.14
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.112
20676128MHD_W3-029
Solar/Wind Harmer
0.114
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233918AB1-142 GEN
Solar/Wind Harmer
0.407
233944AB2-135 GEN
Solar/Wind Harmer
2.12
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.99
232902EASTMUNI
Adder
4.959
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.027
233996TM1833_GEN
Solar/Wind Harmer
0.361
233998TM1NIN_3.36
Solar/Wind Harmer
0.361
232404W1-003 C
Solar/Wind Harmer
0.362
232408W1-005 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.175
234033AF1-007_GEN
Solar/Wind Harmer
13.348
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233970AC1-092 C
Solar/Wind Harmer
0.927
228400MICK 1CT
Adder
3.642
219766PARADISE C
Solar/Wind Harmer
0.096
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.86
228260V4-054C
Solar/Wind Harmer
0.303
228206SHRMN CT
Adder
4.831
219348LDSOLAR C
Solar/Wind Harmer
0.175
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.809
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
228729W2-030 C
Solar/Wind Harmer
0.165
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
20716028EGP_W2-019
Solar/Wind Harmer
0.124
207522AF2-254 C
Solar/Wind Harmer
0.384
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715828PEM_W1-120
Solar/Wind Harmer
0.142
219276PARKLANDSO C
Solar/Wind Harmer
0.122
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
213508CON10-11
50/50
0.998
213508CON10-11
50/50
0.998
213518CONOW8-9
50/50
0.998
213518CONOW8-9
50/50
0.998
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.44
213587EDDYSTN3
Adder
31.412
233982AB2-133 GEN
Solar/Wind Harmer
2.006
233930AB2-032 GEN
Solar/Wind Harmer
0.342
232436AB1-176 C
Solar/Wind Harmer
0.092
234014AF1-036_GEN
Solar/Wind Harmer
1.085
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
232910NRG_G1
Adder
3.244
234041AC1-190 GEN
Solar/Wind Harmer
3.31
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.467
233952AC2-187 GEN
Solar/Wind Harmer
0.409
233954AC2-188 GEN
Solar/Wind Harmer
0.409
233994AC2-023 GEN
Solar/Wind Harmer
0.976
232428Y3-058 C
Solar/Wind Harmer
0.303
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.711
232410W1-006 C
Solar/Wind Harmer
0.362
232918OH NUG7
Adder
3.175
232905CHERITON_25
Adder
0.888
231940T-011
Adder
0.269
232899W1-062
Adder
3.395
233971AC1-093 C
Solar/Wind Harmer
0.88
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.244
228307PCLP GT
Adder
3.695
228351V2-046C
Solar/Wind Harmer
0.605
230511AF1-262
Solar/Wind Harmer
0.054
228201CARL#2CT
Adder
2.031
228200CARL#1CT
Adder
1.931
228251CARLLS#4
Adder
0.186
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
213535CROYDN11
Adder
3.003
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
219607WPEMNERT C
Solar/Wind Harmer
0.122
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.388
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.121
20636128O CRK C2
Adder
1.69
207459AE1-142 C O1
Solar/Wind Harmer
0.274
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20714828MDF_W3-079
Solar/Wind Harmer
0.078
20641628MLH_W1-032
Solar/Wind Harmer
0.073
217197RE CRAN C
Solar/Wind Harmer
0.135
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.196
924131AB2-057 GEN
Solar/Wind Harmer
0.252
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.719
20635128RRCT3&4
Adder
2.371
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
20675428EAM_W2-061
Solar/Wind Harmer
0.045
223401AF1-299 GEN
Solar/Wind Helper
0.272
223402AF1-300 C
Solar/Wind Helper
0.272
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.86
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
972275AH1-722 GEN
Adder
7.525
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.302
208909MACR G3
Adder
32.158
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.552
233935AB2-179 C
Solar/Wind Harmer
1.159
213497CHSTR7-9
Adder
1.074
233933AB2-153 GEN
Solar/Wind Harmer
0.462
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.416
233987AB2-037 GEN
Solar/Wind Harmer
4.192
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
10.964
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.324
233997TMININ_4.2
Solar/Wind Harmer
0.361
232406W1-004 FULL
Solar/Wind Harmer
0.362
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
232921TASLEY2G
Adder
1.868
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.873
970695AG2-447 GEN
Solar/Wind Harmer
1.239
233939AC1-091 C
Solar/Wind Harmer
0.927
233972AC1-094 C
Solar/Wind Harmer
0.745
213815MOSER1-3
Adder
1.097
219914AD2-027 C
Solar/Wind Harmer
0.184
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.227
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20716428NHV_W2-082
Solar/Wind Harmer
0.476
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20636028O CRK C1
Adder
1.854
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963391AG1-188 GEN
Solar/Wind Harmer
0.98
971667AH1-334 GEN
Solar/Wind Harmer
0.715
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.251
219612MATRIX C
Solar/Wind Harmer
0.046
20716928W4-060COL
Solar/Wind Harmer
0.175
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
217213AMBOY SO C
Solar/Wind Harmer
0.03
219249CENTRALDIV C
Solar/Wind Harmer
0.009
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20673728F2S_V4-070
Solar/Wind Harmer
0.043
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
VTFLTFEXP_VFT->PJM
CMTX
31.565
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.608
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.616
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.956
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.439
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.039
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.26 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:660.41
MW Contribution:
1.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.548
231919CHRIST1
Adder
1.859
231920CHRIST2
Adder
1.818
233915AB1-141 GEN
Solar/Wind Harmer
0.402
233968AD2-076_GEN
Solar/Wind Harmer
2.624
970597AG2-380 GEN
Solar/Wind Harmer
1.648
231906DC3 NUG
Adder
5.458
231902DC CT7
Adder
4.364
231907DC10
Adder
1.363
213942SCHUYLKILL
Adder
1.288
213942SCHUYLKILL
Adder
0.985
213957STHWK3-4
Adder
0.976
213957STHWK3-4
Adder
0.976
232813VAUGHN
Adder
0.216
233955AB2-172 GEN
Solar/Wind Harmer
1.825
233940AF2-379 C
Solar/Wind Harmer
0.067
971195AH1-057 GEN
Solar/Wind Harmer
0.349
233901CHERRYDALE C
Solar/Wind Harmer
0.402
232912OH NUG1
Adder
3.153
232913OH NUG2
Adder
3.111
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.12
232904IR4
Adder
28.628
213561DLWR9-10
Adder
1.175
213561DLWR9-10
Adder
0.898
219137THOSOLAR C
Solar/Wind Harmer
0.37
219258KINSLEYDEP C
Solar/Wind Harmer
0.098
964001AG1-254 GEN
Solar/Wind Harmer
2.156
230434AG1-499 GEN
Solar/Wind Harmer
0.171
972141AH1-641 GEN
Solar/Wind Harmer
0.845
230430AE1-229_GEN
Solar/Wind Harmer
8.401
219615MILLCREEK C
Solar/Wind Harmer
0.07
228728W1-130C
Solar/Wind Harmer
0.192
230407AD2-065 C
Solar/Wind Harmer
0.038
970453AG2-297 GEN
Solar/Wind Harmer
0.788
219610FLORENCE C
Solar/Wind Harmer
0.398
219224BRL12CT4
Adder
2.568
230422AE1-104_GEN1
Solar/Wind Harmer
9.553
230425AE1-104_GEN2
Solar/Wind Harmer
9.553
227927V4-067C
Solar/Wind Harmer
0.056
213611FALLS1-3
Adder
0.999
213611FALLS1-3
Adder
0.999
20720728JCB_W1-129
Solar/Wind Harmer
0.079
20715028HAN_X4-015
Solar/Wind Harmer
0.079
207487AE2-000G4
Solar/Wind Harmer
8.126
207497AE2-000G2
Solar/Wind Harmer
8.126
207500AE2-000G1
Solar/Wind Harmer
8.126
207507AE2-000G3
Solar/Wind Harmer
8.126
971189AH1-054 GEN
Solar/Wind Harmer
0.305
963401AG1-189 GEN
Solar/Wind Harmer
0.585
970025AG2-016 GEN
Solar/Wind Harmer
0.729
207445AB1-138_GEN
Solar/Wind Harmer
0.148
219620RIDERU C
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0.306
20720628TIN_W1-124
Solar/Wind Harmer
0.246
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213516CONOW5-6
50/50
0.731
213517CONOW7
50/50
0.731
213589EDDYSTN4
Adder
31.045
213587EDDYSTN3
Adder
31.018
233982AB2-133 GEN
Solar/Wind Harmer
1.981
233930AB2-032 GEN
Solar/Wind Harmer
0.338
232436AB1-176 C
Solar/Wind Harmer
0.091
234014AF1-036_GEN
Solar/Wind Harmer
1.071
232424Y1-079 C
Solar/Wind Harmer
0.218
233984AB2-036 GEN
Solar/Wind Harmer
4.803
232910NRG_G1
Adder
3.201
234041AC1-190 GEN
Solar/Wind Harmer
3.267
234036AF2-325 C
Solar/Wind Harmer
0.333
233946AB2-136 GEN
Solar/Wind Harmer
1.448
233952AC2-187 GEN
Solar/Wind Harmer
0.404
233954AC2-188 GEN
Solar/Wind Harmer
0.404
233994AC2-023 GEN
Solar/Wind Harmer
0.963
232428Y3-058 C
Solar/Wind Harmer
0.299
234015AF2-250 C
Solar/Wind Harmer
0.043
232926CRISFLD1
Adder
0.702
232410W1-006 C
Solar/Wind Harmer
0.357
232918OH NUG7
Adder
3.132
232905CHERITON_25
Adder
0.876
231940T-011
Adder
0.266
232899W1-062
Adder
3.349
233971AC1-093 C
Solar/Wind Harmer
0.868
972233AH1-701 GEN
Adder
1.272
213815MOSER1-3
Adder
1.08
213815MOSER1-3
Adder
1.08
219904AC1-010 C
Solar/Wind Harmer
0.114
219912AD2-042 GEN
Solar/Wind Harmer
0.24
228307PCLP GT
Adder
3.641
228351V2-046C
Solar/Wind Harmer
0.596
230511AF1-262
Solar/Wind Harmer
0.053
228201CARL#2CT
Adder
2
228200CARL#1CT
Adder
1.903
228251CARLLS#4
Adder
0.184
219906AC1-017 C
Solar/Wind Harmer
0.065
230433AD2-135 GEN
Solar/Wind Harmer
0.029
213535CROYDN11
Adder
2.957
219272CLEANLIGHT C
Solar/Wind Harmer
0.052
219607WPEMNERT C
Solar/Wind Harmer
0.12
219304NAMERICA C
Solar/Wind Harmer
0.089
219287REEVESEAST C
Solar/Wind Harmer
0.382
228754AB1-001 C
Solar/Wind Harmer
0.039
20716228APLW2-078
Solar/Wind Harmer
0.218
971521AH1-258 GEN
Solar/Wind Harmer
0.663
20635928PARLN3&4
Adder
1.774
20675528CPH_W2-050
Solar/Wind Harmer
0.137
218526CNTRALGAS2 C
Solar/Wind Harmer
0.088
20673828FLE_V3-070
Solar/Wind Harmer
0.11
213514CONOW1-2
50/50
0.731
213515CONOW3-4
50/50
0.731
231918WEST 1
Adder
1.427
231917EM10
Adder
0.996
213497CHSTR7-9
Adder
1.06
213497CHSTR7-9
Adder
1.06
233918AB1-142 GEN
Solar/Wind Harmer
0.402
233944AB2-135 GEN
Solar/Wind Harmer
2.094
234012AE2-112_GEN
Solar/Wind Harmer
0.91
213958STHWK5-6
Adder
0.976
232902EASTMUNI
Adder
4.895
232426Y1-080 FULL
Solar/Wind Harmer
0.069
232919VN10
Adder
1.013
233996TM1833_GEN
Solar/Wind Harmer
0.356
233998TM1NIN_3.36
Solar/Wind Harmer
0.356
232404W1-003 C
Solar/Wind Harmer
0.357
232408W1-005 C
Solar/Wind Harmer
0.357
232917OH NUG6
Adder
3.139
232915OH NUG4
Adder
3.132
234033AF1-007_GEN
Solar/Wind Harmer
13.17
972177AH1-672 GEN
Solar/Wind Harmer
4.75
213560DLW11-12
Adder
0.898
232900DEMECSMY
Adder
3.212
232901NORTHST
Adder
2.861
233970AC1-092 C
Solar/Wind Harmer
0.915
228400MICK 1CT
Adder
3.589
219766PARADISE C
Solar/Wind Harmer
0.095
219907AC1-030 C
Solar/Wind Harmer
0.041
970997AG2-616 GEN
Solar/Wind Harmer
2.818
228260V4-054C
Solar/Wind Harmer
0.299
228206SHRMN CT
Adder
4.758
219348LDSOLAR C
Solar/Wind Harmer
0.172
219222BRL12CT2
Adder
2.568
228732V1-021 C
Adder
0.054
972251AH1-710 GEN
Adder
13.604
219686LUMSOLAR_N C
Solar/Wind Harmer
0.057
228729W2-030 C
Solar/Wind Harmer
0.163
214194N WALES4
Adder
0.241
213611FALLS1-3
Adder
0.999
20716028EGP_W2-019
Solar/Wind Harmer
0.122
207522AF2-254 C
Solar/Wind Harmer
0.378
20717128DIX_Z2-102
Solar/Wind Harmer
0.347
20715828PEM_W1-120
Solar/Wind Harmer
0.14
219276PARKLANDSO C
Solar/Wind Harmer
0.12
963711AG1-223 GEN
Solar/Wind Harmer
0.373
20714528FRN_Y2-051
Solar/Wind Harmer
0.074
219680HOPEWELLV C1
Solar/Wind Harmer
0.019
20715228NPK_W1-113
Solar/Wind Harmer
0.106
20720528MAN_W1-024
Solar/Wind Harmer
0.062
20720428HOL_W1-112
Solar/Wind Harmer
0.084
20635828PARLN1&2
Adder
1.774
20635028RRCT1&2
Adder
2.809
218524CNTRALGAS1 C
Solar/Wind Harmer
0.087
218440SUMMTASSOC C
Solar/Wind Harmer
0.03
218428ETC SOLAR C
Solar/Wind Harmer
0.008
219908AB1-139 C
Solar/Wind Harmer
0.09
219919AE1-041 FULL
Solar/Wind Harmer
0.01
208909MACR G3
Adder
31.435
208835TUHI V3-051
Solar/Wind Helper
0.01
213515CONOW3-4
50/50
0.731
213516CONOW5-6
50/50
0.548
233935AB2-179 C
Solar/Wind Harmer
1.145
213497CHSTR7-9
Adder
1.06
233933AB2-153 GEN
Solar/Wind Harmer
0.456
232422X3-066 FULL
Solar/Wind Harmer
0.099
213958STHWK5-6
Adder
0.976
232417X3-008 C
Solar/Wind Harmer
0.411
233987AB2-037 GEN
Solar/Wind Harmer
4.137
233964AF2-378 GEN
Solar/Wind Harmer
0.046
232907VN8
Adder
10.819
233950AC2-186 GEN
Solar/Wind Harmer
0.202
233923SMA
Solar/Wind Harmer
1.306
233997TMININ_4.2
Solar/Wind Harmer
0.356
232406W1-004 FULL
Solar/Wind Harmer
0.357
232914OH NUG3
Adder
3.153
232916OH NUG5
Adder
3.153
232921TASLEY2G
Adder
1.843
232434Z2-077 GEN
Solar/Wind Harmer
0.089
213560DLW11-12
Adder
0.898
233973AC2-185 C
Solar/Wind Harmer
1.848
970695AG2-447 GEN
Solar/Wind Harmer
1.222
233939AC1-091 C
Solar/Wind Harmer
0.915
233972AC1-094 C
Solar/Wind Harmer
0.734
213815MOSER1-3
Adder
1.08
219914AD2-027 C
Solar/Wind Harmer
0.181
219921AF1-264
Solar/Wind Harmer
0.043
219623KINSLEYBEA C
Solar/Wind Harmer
0.128
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.055
228711V2-041C
Solar/Wind Harmer
0.172
219221BRL12CT1
Adder
2.568
219223BRL12CT3
Adder
2.568
219688LUMSOLAR_S C
Solar/Wind Harmer
0.058
219291REEVESSOUT C
Solar/Wind Harmer
0.017
218660EHAMPSOLAR C
Solar/Wind Harmer
0.05
959561AF2-247 GEN
Solar/Wind Harmer
0.135
219114HARTZY_C
Solar/Wind Harmer
0.224
219727YARDVSOLFA C
Solar/Wind Harmer
0.242
20716428NHV_W2-082
Solar/Wind Harmer
0.468
20715728PEM_W1-119
Solar/Wind Harmer
0.14
20636028O CRK C1
Adder
1.823
20714928UPF_X1-085
Solar/Wind Harmer
0.105
963391AG1-188 GEN
Solar/Wind Harmer
0.964
971667AH1-334 GEN
Solar/Wind Harmer
0.703
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.247
219612MATRIX C
Solar/Wind Harmer
0.045
20716928W4-060COL
Solar/Wind Harmer
0.172
20635828PARLN1&2
Adder
0.803
20635928PARLN3&4
Adder
0.803
217213AMBOY SO C
Solar/Wind Harmer
0.03
208835TUHI V3-051
Solar/Wind Helper
0.01
214067T20SOLAR
Solar/Wind Harmer
0.071
20720828JCB_W4-025
Solar/Wind Harmer
0.119
20636128O CRK C2
Adder
1.662
207459AE1-142 C O1
Solar/Wind Harmer
0.269
20628028LAKEHURS
Adder
0.243
219817TRENTONSOL C
Solar/Wind Harmer
0.28
20714828MDF_W3-079
Solar/Wind Harmer
0.077
20641628MLH_W1-032
Solar/Wind Harmer
0.072
217197RE CRAN C
Solar/Wind Harmer
0.133
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.192
924131AB2-057 GEN
Solar/Wind Harmer
0.248
20635028RRCT1&2
Adder
2.766
20635128RRCT3&4
Adder
2.67
20635128RRCT3&4
Adder
2.329
223401AF1-299 GEN
Solar/Wind Helper
0.284
223402AF1-300 C
Solar/Wind Helper
0.284
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.015
VTFLTFEXP_VFT->PJM
CMTX
30.969
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.819
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.863
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.553
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.215
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.757
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:626.91
MW Contribution:
1.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.553
233935AB2-179 C
Solar/Wind Harmer
1.163
213497CHSTR7-9
Adder
1.078
233933AB2-153 GEN
Solar/Wind Harmer
0.464
232422X3-066 FULL
Solar/Wind Harmer
0.101
213958STHWK5-6
Adder
0.993
232417X3-008 C
Solar/Wind Harmer
0.418
233987AB2-037 GEN
Solar/Wind Harmer
4.21
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232907VN8
Adder
11.01
233950AC2-186 GEN
Solar/Wind Harmer
0.205
233923SMA
Solar/Wind Harmer
1.33
233997TMININ_4.2
Solar/Wind Harmer
0.363
232406W1-004 FULL
Solar/Wind Harmer
0.363
232921TASLEY2G
Adder
1.876
232914OH NUG3
Adder
3.21
232916OH NUG5
Adder
3.21
232434Z2-077 GEN
Solar/Wind Harmer
0.09
213560DLW11-12
Adder
0.915
233973AC2-185 C
Solar/Wind Harmer
1.882
970695AG2-447 GEN
Solar/Wind Harmer
1.245
233939AC1-091 C
Solar/Wind Harmer
0.931
233972AC1-094 C
Solar/Wind Harmer
0.748
213815MOSER1-3
Adder
1.102
219914AD2-027 C
Solar/Wind Harmer
0.185
219921AF1-264
Solar/Wind Harmer
0.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.131
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230415AB2-049 C
Solar/Wind Harmer
0.056
228711V2-041C
Solar/Wind Harmer
0.176
219221BRL12CT1
Adder
2.621
219223BRL12CT3
Adder
2.621
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
219291REEVESSOUT C
Solar/Wind Harmer
0.018
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
959561AF2-247 GEN
Solar/Wind Harmer
0.137
219114HARTZY_C
Solar/Wind Harmer
0.228
219727YARDVSOLFA C
Solar/Wind Harmer
0.247
20716428NHV_W2-082
Solar/Wind Harmer
0.478
20715728PEM_W1-119
Solar/Wind Harmer
0.143
20636028O CRK C1
Adder
1.864
20714928UPF_X1-085
Solar/Wind Harmer
0.108
963391AG1-188 GEN
Solar/Wind Harmer
0.985
971667AH1-334 GEN
Solar/Wind Harmer
0.719
219918AC2-009 C
Solar/Wind Harmer
0.007
207454AA2-184 E
Solar/Wind Harmer
0.252
219612MATRIX C
Solar/Wind Harmer
0.047
20716928W4-060COL
Solar/Wind Harmer
0.176
20635828PARLN1&2
Adder
0.823
20635928PARLN3&4
Adder
0.823
217213AMBOY SO C
Solar/Wind Harmer
0.031
213514CONOW1-2
50/50
0.553
231919CHRIST1
Adder
1.889
231920CHRIST2
Adder
1.847
233915AB1-141 GEN
Solar/Wind Harmer
0.408
233968AD2-076_GEN
Solar/Wind Harmer
2.668
970597AG2-380 GEN
Solar/Wind Harmer
1.675
231906DC3 NUG
Adder
5.55
231902DC CT7
Adder
4.437
231907DC10
Adder
1.386
213942SCHUYLKILL
Adder
1.31
213942SCHUYLKILL
Adder
1.002
213957STHWK3-4
Adder
0.993
213957STHWK3-4
Adder
0.993
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.857
233940AF2-379 C
Solar/Wind Harmer
0.068
971195AH1-057 GEN
Solar/Wind Harmer
0.355
233901CHERRYDALE C
Solar/Wind Harmer
0.409
232912OH NUG1
Adder
3.21
232913OH NUG2
Adder
3.167
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.14
232904IR4
Adder
29.142
213561DLWR9-10
Adder
1.197
213561DLWR9-10
Adder
0.915
219137THOSOLAR C
Solar/Wind Harmer
0.377
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
964001AG1-254 GEN
Solar/Wind Harmer
2.199
230434AG1-499 GEN
Solar/Wind Harmer
0.175
972141AH1-641 GEN
Solar/Wind Harmer
0.862
230430AE1-229_GEN
Solar/Wind Harmer
8.569
219615MILLCREEK C
Solar/Wind Harmer
0.071
228728W1-130C
Solar/Wind Harmer
0.196
230407AD2-065 C
Solar/Wind Harmer
0.039
970453AG2-297 GEN
Solar/Wind Harmer
0.804
219610FLORENCE C
Solar/Wind Harmer
0.407
219224BRL12CT4
Adder
2.621
230422AE1-104_GEN1
Solar/Wind Harmer
9.749
230425AE1-104_GEN2
Solar/Wind Harmer
9.749
227927V4-067C
Solar/Wind Harmer
0.057
213611FALLS1-3
Adder
1.02
213611FALLS1-3
Adder
1.02
20720728JCB_W1-129
Solar/Wind Harmer
0.08
20715028HAN_X4-015
Solar/Wind Harmer
0.08
207487AE2-000G4
Solar/Wind Harmer
8.308
207497AE2-000G2
Solar/Wind Harmer
8.308
207500AE2-000G1
Solar/Wind Harmer
8.308
207507AE2-000G3
Solar/Wind Harmer
8.308
971189AH1-054 GEN
Solar/Wind Harmer
0.311
963401AG1-189 GEN
Solar/Wind Harmer
0.598
970025AG2-016 GEN
Solar/Wind Harmer
0.745
207445AB1-138_GEN
Solar/Wind Harmer
0.151
219620RIDERU C
Solar/Wind Harmer
0.015
20714428HOW_X1-037
Solar/Wind Harmer
0.313
20720628TIN_W1-124
Solar/Wind Harmer
0.252
20716228APLW2-078
Solar/Wind Harmer
0.223
971521AH1-258 GEN
Solar/Wind Harmer
0.679
20635928PARLN3&4
Adder
1.817
20675528CPH_W2-050
Solar/Wind Harmer
0.141
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
20673828FLE_V3-070
Solar/Wind Harmer
0.113
20676128MHD_W3-029
Solar/Wind Harmer
0.114
20676428JCR_X2-075
Solar/Wind Harmer
0.081
218449LINSOLAR C
Solar/Wind Harmer
0.239
213508CON10-11
50/50
0.999
213508CON10-11
50/50
0.999
213518CONOW8-9
50/50
0.999
213518CONOW8-9
50/50
0.999
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
213589EDDYSTN4
Adder
31.555
213587EDDYSTN3
Adder
31.528
233982AB2-133 GEN
Solar/Wind Harmer
2.013
233930AB2-032 GEN
Solar/Wind Harmer
0.344
232436AB1-176 C
Solar/Wind Harmer
0.093
234014AF1-036_GEN
Solar/Wind Harmer
1.089
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.885
232910NRG_G1
Adder
3.257
234041AC1-190 GEN
Solar/Wind Harmer
3.324
234036AF2-325 C
Solar/Wind Harmer
0.339
233946AB2-136 GEN
Solar/Wind Harmer
1.474
233952AC2-187 GEN
Solar/Wind Harmer
0.411
233954AC2-188 GEN
Solar/Wind Harmer
0.411
233994AC2-023 GEN
Solar/Wind Harmer
0.98
232428Y3-058 C
Solar/Wind Harmer
0.304
234015AF2-250 C
Solar/Wind Harmer
0.044
232926CRISFLD1
Adder
0.714
232410W1-006 C
Solar/Wind Harmer
0.363
232905CHERITON_25
Adder
0.892
232918OH NUG7
Adder
3.188
231940T-011
Adder
0.271
232899W1-062
Adder
3.409
233971AC1-093 C
Solar/Wind Harmer
0.884
972233AH1-701 GEN
Adder
1.297
213815MOSER1-3
Adder
1.102
213815MOSER1-3
Adder
1.102
219904AC1-010 C
Solar/Wind Harmer
0.116
219912AD2-042 GEN
Solar/Wind Harmer
0.245
228307PCLP GT
Adder
3.713
228351V2-046C
Solar/Wind Harmer
0.608
230511AF1-262
Solar/Wind Harmer
0.055
228201CARL#2CT
Adder
2.041
228200CARL#1CT
Adder
1.941
228251CARLLS#4
Adder
0.187
219906AC1-017 C
Solar/Wind Harmer
0.066
230433AD2-135 GEN
Solar/Wind Harmer
0.03
213535CROYDN11
Adder
3.018
219272CLEANLIGHT C
Solar/Wind Harmer
0.054
219607WPEMNERT C
Solar/Wind Harmer
0.123
219304NAMERICA C
Solar/Wind Harmer
0.091
219287REEVESEAST C
Solar/Wind Harmer
0.39
228754AB1-001 C
Solar/Wind Harmer
0.04
214067T20SOLAR
Solar/Wind Harmer
0.073
20720828JCB_W4-025
Solar/Wind Harmer
0.122
20636128O CRK C2
Adder
1.7
207459AE1-142 C O1
Solar/Wind Harmer
0.276
20628028LAKEHURS
Adder
0.248
219817TRENTONSOL C
Solar/Wind Harmer
0.287
20714828MDF_W3-079
Solar/Wind Harmer
0.079
20641628MLH_W1-032
Solar/Wind Harmer
0.074
217197RE CRAN C
Solar/Wind Harmer
0.136
218438BLK ROCK C
Solar/Wind Harmer
0.034
20742028HF_AC1-207
Solar/Wind Harmer
0.197
924131AB2-057 GEN
Solar/Wind Harmer
0.254
20635028RRCT1&2
Adder
2.834
20635128RRCT3&4
Adder
2.736
20635128RRCT3&4
Adder
2.386
218418LINDEN_G5
Adder
4.119
218419LINDEN_G6
Adder
4.119
972260AH1-715 GEN1
Adder
3.299
20675428EAM_W2-061
Solar/Wind Harmer
0.045
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
Adder
1.45
231917EM10
Adder
1.012
213497CHSTR7-9
Adder
1.078
213497CHSTR7-9
Adder
1.078
233918AB1-142 GEN
Solar/Wind Harmer
0.408
233944AB2-135 GEN
Solar/Wind Harmer
2.129
234012AE2-112_GEN
Solar/Wind Harmer
0.926
213958STHWK5-6
Adder
0.993
232902EASTMUNI
Adder
4.98
232426Y1-080 FULL
Solar/Wind Harmer
0.07
232919VN10
Adder
1.031
233996TM1833_GEN
Solar/Wind Harmer
0.363
233998TM1NIN_3.36
Solar/Wind Harmer
0.363
232404W1-003 C
Solar/Wind Harmer
0.363
232408W1-005 C
Solar/Wind Harmer
0.363
232917OH NUG6
Adder
3.196
232915OH NUG4
Adder
3.188
234033AF1-007_GEN
Solar/Wind Harmer
13.406
972177AH1-672 GEN
Solar/Wind Harmer
4.835
213560DLW11-12
Adder
0.915
232900DEMECSMY
Adder
3.27
232901NORTHST
Adder
2.913
233970AC1-092 C
Solar/Wind Harmer
0.931
228400MICK 1CT
Adder
3.659
219766PARADISE C
Solar/Wind Harmer
0.097
219907AC1-030 C
Solar/Wind Harmer
0.042
970997AG2-616 GEN
Solar/Wind Harmer
2.874
228260V4-054C
Solar/Wind Harmer
0.305
228206SHRMN CT
Adder
4.855
219348LDSOLAR C
Solar/Wind Harmer
0.176
219222BRL12CT2
Adder
2.621
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.879
219686LUMSOLAR_N C
Solar/Wind Harmer
0.059
228729W2-030 C
Solar/Wind Harmer
0.166
214194N WALES4
Adder
0.246
213611FALLS1-3
Adder
1.02
20716028EGP_W2-019
Solar/Wind Harmer
0.125
207522AF2-254 C
Solar/Wind Harmer
0.386
20717128DIX_Z2-102
Solar/Wind Harmer
0.354
20715828PEM_W1-120
Solar/Wind Harmer
0.143
219276PARKLANDSO C
Solar/Wind Harmer
0.123
963711AG1-223 GEN
Solar/Wind Harmer
0.381
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.108
20720528MAN_W1-024
Solar/Wind Harmer
0.064
20720428HOL_W1-112
Solar/Wind Harmer
0.086
20635828PARLN1&2
Adder
1.817
20635028RRCT1&2
Adder
2.878
218524CNTRALGAS1 C
Solar/Wind Harmer
0.09
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
218428ETC SOLAR C
Solar/Wind Harmer
0.009
219908AB1-139 C
Solar/Wind Harmer
0.092
219919AE1-041 FULL
Solar/Wind Harmer
0.01
972275AH1-722 GEN
Adder
7.573
20673628F1S_V4-069
Solar/Wind Harmer
0.043
207528AF2-192 GEN
Solar/Wind Harmer
0.304
208909MACR G3
Adder
32.417
219036LINDEN_G7
Adder
3.972
219035LINDEN_G8
Adder
3.916
972261AH1-715 GEN2
Adder
3.803
223401AF1-299 GEN
Solar/Wind Helper
0.271
223402AF1-300 C
Solar/Wind Helper
0.271
219249CENTRALDIV C
Solar/Wind Harmer
0.01
207442AE1-156 GEN
Solar/Wind Harmer
0.178
20673728F2S_V4-070
Solar/Wind Harmer
0.043
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.015
VTFLTFEXP_VFT->PJM
CMTX
31.773
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.822
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.872
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.56
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.517
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.197
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.97 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:589.37
MW Contribution:
0.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213514CONOW1-2
50/50
0.552
213893PHLISST1
50/50
1.346
231916EM3
50/50
0.419
231919CHRIST1
50/50
1.997
231920CHRIST2
50/50
1.953
231901EM4
50/50
0.845
213740LIBE_ST1
50/50
1.073
231505HR4
50/50
0.884
233915AB1-141 GEN
Solar/Wind Harmer
0.105
233968AD2-076_GEN
Solar/Wind Harmer
0.932
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.42
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.219
971195AH1-057 GEN
Solar/Wind Harmer
0.226
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
232432Z2-076 GEN
Solar/Wind Harmer
0.005
232920IR10
Adder
1.135
232904IR4
Adder
29.017
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
964001AG1-254 GEN
Solar/Wind Harmer
1.694
972141AH1-641 GEN
Solar/Wind Harmer
0.466
230430AE1-229_GEN
Solar/Wind Harmer
5.911
970453AG2-297 GEN
Solar/Wind Harmer
0.739
219224BRL12CT4
Adder
2.608
230422AE1-104_GEN1
Solar/Wind Harmer
3.894
230425AE1-104_GEN2
Solar/Wind Harmer
3.894
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
207487AE2-000G4
Solar/Wind Harmer
3.317
207497AE2-000G2
Solar/Wind Harmer
3.317
207500AE2-000G1
Solar/Wind Harmer
3.317
207507AE2-000G3
Solar/Wind Harmer
3.317
971189AH1-054 GEN
Solar/Wind Harmer
0.2
963401AG1-189 GEN
Solar/Wind Harmer
0.294
970025AG2-016 GEN
Solar/Wind Harmer
0.479
971521AH1-258 GEN
Solar/Wind Harmer
0.436
20635928PARLN3&4
Adder
1.806
218526CNTRALGAS2 C
Solar/Wind Harmer
0.186
213514CONOW1-2
50/50
0.737
213515CONOW3-4
50/50
0.737
231918WEST 1
50/50
1.533
213889PHLISCT2
50/50
0.933
231917EM10
50/50
1.07
213738LIBE_CT1
50/50
0.777
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233918AB1-142 GEN
Solar/Wind Harmer
0.105
234012AE2-112_GEN
Solar/Wind Harmer
0.932
213958STHWK5-6
Adder
0.99
232902EASTMUNI
Adder
4.959
232919VN10
Adder
1.027
232404W1-003 C
Solar/Wind Harmer
0.234
232408W1-005 C
Solar/Wind Harmer
0.234
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.175
234033AF1-007_GEN
Solar/Wind Harmer
4.956
972177AH1-672 GEN
Solar/Wind Harmer
3.65
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233970AC1-092 C
Solar/Wind Harmer
0.624
228400MICK 1CT
Adder
3.642
970997AG2-616 GEN
Solar/Wind Harmer
2.152
228206SHRMN CT
Adder
4.831
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
972251AH1-710 GEN
Adder
13.809
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
207522AF2-254 C
Solar/Wind Harmer
0.248
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.86
218524CNTRALGAS1 C
Solar/Wind Harmer
0.184
972275AH1-722 GEN
Adder
7.525
207528AF2-192 GEN
Solar/Wind Harmer
0.171
208909MACR G3
Adder
32.158
213515CONOW3-4
50/50
0.737
213516CONOW5-6
50/50
0.552
213890PHLISCT3
50/50
0.933
213888PHLISCT1
50/50
0.933
213739LIBE_CT2
50/50
0.777
233935AB2-179 C
Solar/Wind Harmer
0.637
213497CHSTR7-9
Adder
1.074
232422X3-066 FULL
Solar/Wind Harmer
0.034
213958STHWK5-6
Adder
0.99
233987AB2-037 GEN
Solar/Wind Harmer
0
232907VN8
Adder
10.964
232406W1-004 FULL
Solar/Wind Harmer
0.234
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
232921TASLEY2G
Adder
1.868
232434Z2-077 GEN
Solar/Wind Harmer
0.015
213560DLW11-12
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
0.624
970695AG2-447 GEN
Solar/Wind Harmer
0.865
233939AC1-091 C
Solar/Wind Harmer
0.624
233972AC1-094 C
Solar/Wind Harmer
0.624
213815MOSER1-3
Adder
1.097
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
20636028O CRK C1
Adder
1.854
963391AG1-188 GEN
Solar/Wind Harmer
0.479
971667AH1-334 GEN
Solar/Wind Harmer
0.462
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
207442AE1-156 GEN
Solar/Wind Harmer
0.014
213508CON10-11
50/50
0.998
213508CON10-11
50/50
0.998
213518CONOW8-9
50/50
0.998
213518CONOW8-9
50/50
0.998
213516CONOW5-6
50/50
0.737
213517CONOW7
50/50
0.737
231909HR2
50/50
0.61
231908HR1
50/50
0.607
231910HR3
50/50
0.607
213589EDDYSTN4
Adder
31.44
213587EDDYSTN3
Adder
31.412
233930AB2-032 GEN
Solar/Wind Harmer
0.394
234014AF1-036_GEN
Solar/Wind Harmer
0.932
233984AB2-036 GEN
Solar/Wind Harmer
2.839
232910NRG_G1
Adder
3.244
234041AC1-190 GEN
Solar/Wind Harmer
2.694
232926CRISFLD1
Adder
0.711
232410W1-006 C
Solar/Wind Harmer
0.234
232918OH NUG7
Adder
3.175
232905CHERITON_25
Adder
0.888
231940T-011
Adder
0.269
232899W1-062
Adder
3.395
233971AC1-093 C
Solar/Wind Harmer
0.624
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228307PCLP GT
Adder
3.695
228201CARL#2CT
Adder
2.031
228200CARL#1CT
Adder
1.931
228251CARLLS#4
Adder
0.186
213535CROYDN11
Adder
3.003
219304NAMERICA C
Solar/Wind Harmer
0.027
20636128O CRK C2
Adder
1.69
20628028LAKEHURS
Adder
0.247
20714828MDF_W3-079
Solar/Wind Harmer
0.025
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.719
20635128RRCT3&4
Adder
2.371
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
223401AF1-299 GEN
Solar/Wind Helper
0.272
223402AF1-300 C
Solar/Wind Helper
0.272
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
VTFLTFEXP_VFT->PJM
CMTX
31.565
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.608
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.616
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.956
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
12.439
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.039
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for POST39-CHIREACT_39 230.0 kV Ckt 1 line l/o PECO_CBO_CHIC435_SRT-A/* $ DELCO $ PECO_CBO_CHIC435 $ K


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PECO
Facility Description:
POST39-CHIREACT_39 230.0 kV Ckt 1 line
Contingency Name:
PECO_CBO_CHIC435_SRT-A/* $ DELCO $ PECO_CBO_CHIC435 $ K
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.34 %
Rating:1622.0 MVA
Rating Type:B
MVA to Mitigate:1643.73
MW Contribution:
2.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
213893PHLISST1
50/50
9.655
231505HR4
50/50
5.278
231916EM3
50/50
1.729
231901EM4
50/50
3.495
231919CHRIST1
50/50
7.479
231920CHRIST2
50/50
7.313
231906DC3 NUG
50/50
13.152
231902DC CT7
50/50
10.514
231907DC10
50/50
3.283
233915AB1-141 GEN
Solar/Wind Harmer
0.79
233968AD2-076_GEN
Solar/Wind Harmer
5.256
970597AG2-380 GEN
Solar/Wind Harmer
3.301
233955AB2-172 GEN
Solar/Wind Harmer
3.727
233940AF2-379 C
Solar/Wind Harmer
0.134
971195AH1-057 GEN
Solar/Wind Harmer
0.699
233901CHERRYDALE C
Solar/Wind Harmer
0.805
232912OH NUG1
Adder
6.323
232913OH NUG2
Adder
6.239
232432Z2-076 GEN
Solar/Wind Harmer
0.093
232920IR10
Adder
2.209
232813VAUGHN
Adder
0.411
232904IR4
Adder
56.366
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219615MILLCREEK C
Solar/Wind Helper
0.014
231900EM5
50/50
12.344
231909HR2
50/50
2.515
231908HR1
50/50
2.511
231910HR3
50/50
2.511
232416X2-083
50/50
0.033
233930AB2-032 GEN
Solar/Wind Harmer
0.665
234014AF1-036_GEN
Solar/Wind Harmer
2.145
233982AB2-133 GEN
Solar/Wind Harmer
3.845
233984AB2-036 GEN
Solar/Wind Harmer
9.819
232436AB1-176 C
Solar/Wind Harmer
0.181
232424Y1-079 C
Solar/Wind Harmer
0.442
234041AC1-190 GEN
Solar/Wind Harmer
6.669
234036AF2-325 C
Solar/Wind Harmer
0.68
233946AB2-136 GEN
Solar/Wind Harmer
2.951
233994AC2-023 GEN
Solar/Wind Harmer
1.94
232428Y3-058 C
Solar/Wind Harmer
0.6
232926CRISFLD1
Adder
1.411
234015AF2-250 C
Solar/Wind Harmer
0.086
232410W1-006 C
Solar/Wind Harmer
0.716
232905CHERITON_25
Adder
1.757
232918OH NUG7
Adder
6.281
231940T-011
Adder
0.527
232910NRG_G1
Adder
6.075
233952AC2-187 GEN
Solar/Wind Harmer
0.777
233954AC2-188 GEN
Solar/Wind Harmer
0.777
232899W1-062
Adder
6.114
233971AC1-093 C
Solar/Wind Harmer
1.544
219912AD2-042 GEN
Solar/Wind Helper
0.087
219904AC1-010 C
Solar/Wind Helper
0.035
219906AC1-017 C
Solar/Wind Helper
0.021
214067T20SOLAR
Solar/Wind Helper
0.006
219607WPEMNERT C
Solar/Wind Helper
0.039
219304NAMERICA C
Solar/Wind Helper
0.064
213889PHLISCT2
50/50
6.682
231917EM10
50/50
4.412
231918WEST 1
50/50
5.526
233918AB1-142 GEN
Solar/Wind Harmer
0.79
234012AE2-112_GEN
Solar/Wind Harmer
1.824
232902EASTMUNI
Adder
10.109
233944AB2-135 GEN
Solar/Wind Harmer
4.049
232426Y1-080 FULL
Solar/Wind Harmer
0.141
232919VN10
Adder
2.06
233996TM1833_GEN
Solar/Wind Harmer
0.717
233998TM1NIN_3.36
Solar/Wind Harmer
0.717
232404W1-003 C
Solar/Wind Harmer
0.716
232408W1-005 C
Solar/Wind Harmer
0.716
232917OH NUG6
Adder
6.295
232915OH NUG4
Adder
6.281
234033AF1-007_GEN
Solar/Wind Harmer
25.93
972177AH1-672 GEN
Solar/Wind Harmer
9.199
232900DEMECSMY
Adder
5.864
232901NORTHST
Adder
5.277
233970AC1-092 C
Solar/Wind Harmer
1.626
972251AH1-710 GEN
Adder
10.811
219766PARADISE C
Solar/Wind Helper
0.031
219907AC1-030 C
Solar/Wind Helper
0.019
219348LDSOLAR C
Solar/Wind Helper
0.056
213890PHLISCT3
50/50
6.693
213888PHLISCT1
50/50
6.682
231131BLOOM ENRGY
50/50
0.23
231915DC CT6
50/50
0.555
233935AB2-179 C
Solar/Wind Harmer
2.113
233933AB2-153 GEN
Solar/Wind Harmer
0.898
233987AB2-037 GEN
Solar/Wind Harmer
9.013
232422X3-066 FULL
Solar/Wind Harmer
0.197
232417X3-008 C
Solar/Wind Harmer
0.839
233964AF2-378 GEN
Solar/Wind Harmer
0.095
232907VN8
Adder
22.172
233923SMA
Solar/Wind Harmer
2.627
233997TMININ_4.2
Solar/Wind Harmer
0.717
232406W1-004 FULL
Solar/Wind Harmer
0.716
232921TASLEY2G
Adder
3.696
232914OH NUG3
Adder
6.323
232916OH NUG5
Adder
6.323
232434Z2-077 GEN
Solar/Wind Harmer
0.175
233950AC2-186 GEN
Solar/Wind Harmer
0.388
233973AC2-185 C
Solar/Wind Harmer
3.286
970695AG2-447 GEN
Solar/Wind Harmer
2.174
233939AC1-091 C
Solar/Wind Harmer
1.626
233972AC1-094 C
Solar/Wind Harmer
1.306
219914AD2-027 C
Solar/Wind Helper
0.067
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219921AF1-264
Solar/Wind Helper
0.027
219623KINSLEYBEA C
Solar/Wind Helper
0.001
NYPJM->LTFIMP_NY
CLTF
1.194
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.199
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.125
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.235
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.732
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.077
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CONTINGENCY 'PJM_500_BG_P4_5_CNSTN_C_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 200064 CKT 1    /*CNASTONE     500.0 - PCHBTM1S     500.0
 OPEN BRANCH FROM BUS 200004 TO BUS 200100 CKT ZC   /*CNASTONE     500.0 - CNASTCAP     500.0
END
CONTINGENCY 'BGE_P4_GRACETON_51_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 200064 CKT 1   /*CNASTONE     500.0 - PCHBTM1S     500.0
END
CONTINGENCY 'PECO_P4_PEACH235_SRT-A
 TRIP BRANCH FROM BUS 200064 TO BUS 200004 CKT 1    /*PCHBTM1S     500.0 - CNASTONE     500.0
 TRIP BRANCH FROM BUS 200064 TO BUS 200065 CKT Z1   /*PCHBTM1S     500.0 - PCHBTM2S     500.0
END
CONTINGENCY 'PJM_500_BG_P4_5_CNSTN_B_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 200064 CKT 1   /*CNASTONE     500.0 - PCHBTM1S     500.0
 OPEN BRANCH FROM BUS 200004 TO BUS 220963 CKT 2   /*CNASTONE     500.0 - CONASTON     230.0
END
CONTINGENCY 'PECO_CBO_CHIC435_SRT-A
 TRIP BRANCH FROM BUS 213489 TO BUS 214221 CKT 1   /*CHICHST1     230.0 - CHIREACT_43  230.0
END
CONTINGENCY 'PECO_P4_POST475_SRT-A
 DISCONNECT BUS 214216   /*POST97       230.0
 DISCONNECT BUS 214234   /*LINWOOD97    230.0
 DISCONNECT BUS 214290   /*POST1T       230.0
END
CONTINGENCY 'PECO_P4_POST785_SRT-A
 DISCONNECT BUS 214216   /*POST97       230.0
 DISCONNECT BUS 214234   /*LINWOOD97    230.0
 DISCONNECT BUS 214288   /*POST2T       230.0
END
CONTINGENCY 'AP_P2-3_PE-500-019E_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 1          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 3          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1          /*CHAN         500.0 - 01DOUBS      500.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 2                  /*01DOUBS      500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 235098 CKT 1 /*01DOUBS      500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-2_PE-500-3835T_SRT-A'
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'PECO_P4_PEACH025_SRT-A
 TRIP BRANCH FROM BUS 200013 TO BUS 200066 CKT Z1   /*PCHBTM2N     500.0 - PCHBTM1N     500.0
 TRIP BRANCH FROM BUS 200013 TO BUS 214347 CKT Z1   /*PCHBTM2N     500.0 - PBN_EXP_BAY  500.0
 TRIP BRANCH FROM BUS 270095 TO BUS 200066 CKT 1    /*CHAN         500.0 - PCHBTM1N     500.0
END
CONTINGENCY 'BG_P7_CNSTN_NWEST2_SRT-A'
 OPEN BRANCH FROM BUS 220961 TO BUS 220963 CKT 1   /*NWEST326     230.0 - CONASTON     230.0
 OPEN BRANCH FROM BUS 220962 TO BUS 220963 CKT 1   /*NWEST311     230.0 - CONASTON     230.0
END
CONTINGENCY 'PECO_P4_PEACH035_SRT-A
 DISCONNECT BUS 213791                             /*MDDYRN07     230.0
 DISCONNECT BUS 213794                             /*MDYRN5-6      13.8
 DISCONNECT BUS 213795                             /*MDYRN7-8      13.8
 DISCONNECT BUS 213866                             /*PCHBTM       230.0
 DISCONNECT BUS 213867                             /*PCHBTM        35.0
 TRIP BRANCH FROM BUS 200066 TO BUS 270095 CKT 1   /*PCHBTM1N     500.0 - CHAN         500.0
END
CONTINGENCY 'PECO_P4_PEACH245_SRT-A
 DISCONNECT BUS 200122                             /*DELTA        500.0
 DISCONNECT BUS 200192                             /*DELTA CT1     13.8
 DISCONNECT BUS 200193                             /*DELTA CT2     13.8
 DISCONNECT BUS 200194                             /*DELTA CT3     13.8
 DISCONNECT BUS 200195                             /*DELTA ST      18.0
 DISCONNECT BUS 200199                             /*DELTA2 POI   500.0
 DISCONNECT BUS 200200                             /*DELTA2 CT1    18.0
 DISCONNECT BUS 200201                             /*DELTA2 CT2    18.0
 DISCONNECT BUS 200202                             /*DELTA2 ST     19.5
 TRIP BRANCH FROM BUS 200064 TO BUS 200004 CKT 1   /*PCHBTM1S     500.0 - CNASTONE     500.0
END
CONTINGENCY 'DPL_P4_2_DPEM237_SRT-A'
 DISCONNECT BRANCH FROM BUS 231001 TO BUS 231000 CKT 1   /*EDGEMR 5     230.0 - CLAY_230     230.0
 DISCONNECT BUS 231505                                   /*HR4           18.0
END
CONTINGENCY 'PECO_P1-2_5012_SRT-A'
 TRIP BRANCH FROM BUS 200064 TO BUS 200004 CKT 1   /*PCHBTM1S     500.0 - CNASTONE     500.0
END
CONTINGENCY 'PECO_P1-2_5007_SRT-A
 TRIP BRANCH FROM BUS 200066 TO BUS 270095 CKT 1   /*PCHBTM1N     500.0 - CHAN         500.0
END
CONTINGENCY 'PJM_500_BG_P4_5_CNSTN_M_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 200026 CKT 1    /*CNASTONE     500.0 - HUNTERTN     500.0
 OPEN BRANCH FROM BUS 200004 TO BUS 200100 CKT ZC   /*CNASTONE     500.0 - CNASTCAP     500.0
END
CONTINGENCY 'PECO_P2-2_NOTT230B_SRT-A
 DISCONNECT BUS 213844   /*NOTTNGHM     230.0
END
CONTINGENCY 'PL_04_P71_001014_SRT-A'
 DISCONNECT BRANCH FROM BUS 208045 TO BUS 208078 CKT 3   /*LAUS         230.0 - SAKR         230.0
 DISCONNECT BRANCH FROM BUS 208045 TO BUS 208078 CKT 4   /*LAUS         230.0 - SAKR         230.0
END
CONTINGENCY 'PL_05_P71_000906_SRT-A'
 DISCONNECT BRANCH FROM BUS 208019 TO BUS 208020 CKT 1   /*MANO         230.0 - MANO TR3     230.0
 DISCONNECT BRANCH FROM BUS 208019 TO BUS 208021 CKT 1   /*MANO         230.0 - MANO TR4     230.0
 DISCONNECT BRANCH FROM BUS 208066 TO BUS 208914 CKT 1   /*SAHA0102     230.0 - SAHA 34       13.8
 DISCONNECT BRANCH FROM BUS 208066 TO BUS 208915 CKT 1   /*SAHA0102     230.0 - SAHA 567      13.8
 DISCONNECT BRANCH FROM BUS 208067 TO BUS 208916 CKT 1   /*SAHA0304     230.0 - SAHA8910      13.8
 DISCONNECT BRANCH FROM BUS 208067 TO BUS 208917 CKT 1   /*SAHA0304     230.0 - SAHA1112      13.8
 DISCONNECT BRANCH FROM BUS 208070 TO BUS 208019 CKT 1   /*SAHA12TP     230.0 - MANO         230.0
 DISCONNECT BRANCH FROM BUS 208070 TO BUS 208048 CKT 1   /*SAHA12TP     230.0 - OTCR         230.0
 DISCONNECT BRANCH FROM BUS 208070 TO BUS 208066 CKT 1   /*SAHA12TP     230.0 - SAHA0102     230.0
 DISCONNECT BRANCH FROM BUS 208071 TO BUS 208019 CKT 1   /*SAHA34TP     230.0 - MANO         230.0
 DISCONNECT BRANCH FROM BUS 208071 TO BUS 208067 CKT 1   /*SAHA34TP     230.0 - SAHA0304     230.0
 DISCONNECT BRANCH FROM BUS 208071 TO BUS 220964 CKT 1   /*SAHA34TP     230.0 - GRACETON     230.0
END
CONTINGENCY 'PL_04_P22_102290_SRT-A'
 DISCONNECT BRANCH FROM BUS 200099 TO BUS 208045 CKT 3   /*LAUS         500.0 - LAUS         230.0
END
CONTINGENCY 'PECO_P4_PEACH255_SRT-A
 DISCONNECT BUS 200122                              /*DELTA        500.0
 DISCONNECT BUS 200192                              /*DELTA CT1     13.8
 DISCONNECT BUS 200193                              /*DELTA CT2     13.8
 DISCONNECT BUS 200194                              /*DELTA CT3     13.8
 DISCONNECT BUS 200195                              /*DELTA ST      18.0
 DISCONNECT BUS 200199                              /*DELTA2 POI   500.0
 DISCONNECT BUS 200200                              /*DELTA2 CT1    18.0
 DISCONNECT BUS 200201                              /*DELTA2 CT2    18.0
 DISCONNECT BUS 200202                              /*DELTA2 ST     19.5
 TRIP BRANCH FROM BUS 200064 TO BUS 200065 CKT Z2   /*PCHBTM1S     500.0 - PCHBTM2S     500.0
 TRIP BRANCH FROM BUS 214347 TO BUS 200064 CKT 2    /*PBN_EXP_BAY  500.0 - PCHBTM1S     500.0
END
270095 to 235105 ckt 1
214220 to 213490 ckt 1
214221 to 213489 ckt 1
200004 to 200003 ckt 1
214084 to 220964 ckt 1
231001 to 214236 ckt 1
213750 to 214221 ckt 1
214234 to 214216 ckt 1
213844 to 213846 ckt 1
213846 to 213869 ckt 1
200066 to 270095 ckt 1
200064 to 200004 ckt 1
200064 to 214347 ckt 2
200065 to 200064 ckt Z1
213869 to 214087 ckt 1
214287 to 214220 ckt 1

Winter Peak Analysis

The New Service Request AG2-447 was evaluated as a 20.0 MW (12.0 MW Capacity) injection in the DPL area.

AG2-447 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 134.25 MW (20.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P1-2_PE-500-3835T_SRT-A
SingleAC128.38 %3507.0B4502.35
0.2
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019E_SRT-W
BreakerAC128.11 %3507.0B4492.66
0.2
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC111.87 %3507.0B3923.45
0.16
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
SingleAC108.79 %3507.0B3815.35
0.19
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
BG_P7_CNSTN_NWEST2_SRT-A
TowerAC101.98 %3507.0B3576.36
0.15

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-3835T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-3835T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.38 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:4502.35
MW Contribution:
0.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
43.046
200053ROCKSP 2
50/50
43.046
200054ROCKSP 3
50/50
42.609
200055ROCKSP 4
50/50
42.609
200203Y1-065-STG
50/50
5.765
200204Y1-065-CTG1
50/50
3.63
200205Y1-065-CTG2
50/50
3.63
3147043LAWRENC
Solar/Wind Helper
0.202
3147133PAMPLIN
Solar/Wind Helper
1.053
3147133PAMPLIN
Solar/Wind Helper
0.268
3147133PAMPLIN
Solar/Wind Helper
0.335
23546401DTGZ2-030
Solar/Wind Helper
0.057
20676328BVR_Y1-020
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
23777901MDS_W4-102
Solar/Wind Helper
0.106
3137176SLIGO L2192
Solar/Wind Helper
1.413
3141426STAFORD
Solar/Wind Helper
0.09
3141906WESTMOR
Solar/Wind Helper
0.151
3142416OLDCHRC
Solar/Wind Helper
0.959
3142416OLDCHRC
Solar/Wind Helper
0.367
3142433PROV 92
Solar/Wind Helper
1.466
3142956BIRDNECK
Solar/Wind Helper
0.591
3143316POE
Solar/Wind Helper
1.418
3145506HICKORY
Solar/Wind Helper
1.424
3145506HICKORY
Solar/Wind Helper
0.854
3145506HICKORY
Solar/Wind Helper
0.214
3146386ELIZ CT
Solar/Wind Helper
0.354
3146776BUCKING
Solar/Wind Helper
1.365
3146776BUCKING
Solar/Wind Helper
0.111
3146776BUCKING
Solar/Wind Helper
0.123
3146776BUCKING
Solar/Wind Helper
0.137
209027LOR2_Q27
Solar/Wind Harmer
4.58
212266LOR1
Solar/Wind Harmer
1.25
217081WEATEXAS C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
235020AA1-095 C
Solar/Wind Helper
0.023
316075AC2-137 C
Solar/Wind Helper
0.118
316077AC2-138 C
Solar/Wind Helper
0.084
3138133OCRAN
Solar/Wind Helper
0.111
3138133OCRAN
Solar/Wind Helper
0.221
3141766HARMONY
Solar/Wind Helper
0.073
3141783LANCAST
Solar/Wind Helper
0.221
3141783LANCAST
Solar/Wind Helper
0.148
3141813NORNECK
Solar/Wind Helper
0.373
3141913WHIT STONE
Solar/Wind Helper
0.368
3143226MDLTHAN
Solar/Wind Helper
0.366
3143873LANEXA
Solar/Wind Helper
0.22
3145273HOLLAND
Solar/Wind Helper
0.263
3146376EDENTON
Solar/Wind Helper
0.348
3146456SLIGO L269
Solar/Wind Helper
0.355
3146456SLIGO L269
Solar/Wind Helper
0.355
3146486SUNBURY
Solar/Wind Helper
0.353
3146486SUNBURY
Solar/Wind Helper
0.353
3146516WINFALL
Solar/Wind Helper
0.352
3146516WINFALL
Solar/Wind Helper
0.352
3146516WINFALL
Solar/Wind Helper
1.14
3146516WINFALL
Solar/Wind Helper
0.352
3146516WINFALL
Solar/Wind Helper
0.352
3146516WINFALL
Solar/Wind Helper
0.352
3146626S HERTFORD
Solar/Wind Helper
0.351
3146626S HERTFORD
Solar/Wind Helper
0.351
3146626S HERTFORD
Solar/Wind Helper
0.351
3146843MT LREL
Solar/Wind Helper
0.323
3146843MT LREL
Solar/Wind Helper
0.323
3146926FARMVIL
Solar/Wind Helper
0.204
3146926FARMVIL
Solar/Wind Helper
0.204
3147666LOUISA
Solar/Wind Helper
1.524
3147666LOUISA
Solar/Wind Helper
0.876
3147983MERCK5
Solar/Wind Helper
0.133
200034PCHBTM 2
50/50
99.353
200035PCHBTM 3
50/50
16.372
200192DELTA CT1
50/50
1.504
200193DELTA CT2
50/50
1.504
200194DELTA CT3
50/50
1.504
200195DELTA ST
50/50
2.506
3141726DUNNSVL
Solar/Wind Helper
1.49
3145663CRESWEL
Solar/Wind Helper
0.966
316034AC1-036 C
Solar/Wind Helper
0.074
316036AC1-147 C
Solar/Wind Helper
0.115
316059AD1-063 C
Solar/Wind Helper
0.089
316159AE1-175 C
Solar/Wind Helper
0.116
316240AF1-291 C
Solar/Wind Helper
0.116
316246AF1-032 C
Solar/Wind Helper
0.086
316248AF1-058 C
Solar/Wind Helper
0.102
316258AE1-075 C
Solar/Wind Helper
0.103
316305AF2-043 C
Solar/Wind Helper
0.114
316314AB2-024 C
Solar/Wind Helper
0.118
316315AB2-025 C
Solar/Wind Helper
0.113
316316AC1-027 C
Solar/Wind Helper
0.101
316317KELFORD C
Solar/Wind Helper
0.125
316382AG1-145 C
Solar/Wind Helper
0.117
316405AF2-144 C
Solar/Wind Helper
0.097
208835TUHI V3-051
Solar/Wind Harmer
0.06
208835TUHI V3-051
Solar/Wind Harmer
0.06
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
226910AB2-157 C
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Harmer
0.195
233970AC1-092 C
Solar/Wind Harmer
0.195
233971AC1-093 C
Solar/Wind Harmer
0.185
233972AC1-094 C
Solar/Wind Harmer
0.156
233973AC2-185 C
Solar/Wind Harmer
0.394
219727YARDVSOLFA C
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Helper
0.348
3130156CHOWAN
Solar/Wind Helper
0.348
3130156CHOWAN
Solar/Wind Helper
0.348
3145336SMITFLD
Solar/Wind Helper
1.434
3145336SMITFLD
Solar/Wind Helper
0.143
3148133STUARTS
Solar/Wind Helper
0.198
3141196NOKESVL
Solar/Wind Helper
1.648
3147243WELCO
Solar/Wind Helper
0.199
3141873WAN 176
Solar/Wind Helper
0.073
3143526WINTERP
Solar/Wind Helper
1.904
3143526WINTERP
Solar/Wind Helper
1.904
316411AF1-147_GEN1
Solar/Wind Helper
0.339
316415AF1-147_GEN2
Solar/Wind Helper
0.339
316404AE1-155 C
Solar/Wind Helper
0.758
316017AA1-139 ULT1
Solar/Wind Helper
0.342
316018AA1-139 ULT2
Solar/Wind Helper
0.342
316181AB2-040 GEN
Solar/Wind Helper
0.433
316033AB2-134 GEN
Solar/Wind Helper
0.826
316388AE2-253 GEN
Solar/Wind Helper
0.286
3148013FISHERV
Solar/Wind Helper
0.189
3148013FISHERV
Solar/Wind Helper
0.33
3145176PASQUOTANK
Solar/Wind Helper
0.219
3132123MT JACKSON
Solar/Wind Helper
1.053
3132273ORANGE
Solar/Wind Helper
0.077
3142543TWELFTH
Solar/Wind Helper
0.035
3144303KENBRDG
Solar/Wind Helper
0.266
3147173SINAI
Solar/Wind Helper
0.319
3148463FAIRFLD
Solar/Wind Helper
0.316
238175AF1-290_GEN
Solar/Wind Helper
0.482
238169AE2-226 GEN1
Solar/Wind Helper
0.294
238170AE2-226 GEN2
Solar/Wind Helper
0.294
316203AE2-005 GEN
Solar/Wind Helper
0.767
316441AF1-014 GEN
Solar/Wind Helper
0.117
316494AC1-189 GEN
Solar/Wind Helper
0.42
315616AA1-038_C
Solar/Wind Helper
1.903
316005AA1-067
Solar/Wind Helper
0.079
316426AA2-053 GEN
Solar/Wind Helper
0.404
316190AA2-174 GEN
Solar/Wind Helper
0.027
316327AA2-057 GEN
Solar/Wind Helper
0.394
3156081AA2-088 GEN
Solar/Wind Helper
0.551
315614AA2-178 GEN
Solar/Wind Helper
0.444
315816AE2-034 GEN
Solar/Wind Helper
0.333
316312AB1-027
Solar/Wind Helper
0.148
316049AB1-081 GEN
Solar/Wind Helper
0.415
316011AB1-132 GEN
Solar/Wind Helper
0.648
316369SG1_INVT
Solar/Wind Helper
0.568
315651AD1-115 GEN
Solar/Wind Helper
0.948
237061AD1-155 GEN
Solar/Wind Helper
0.427
316463AE2-346 GEN
Solar/Wind Helper
0.065
315839AE2-212 C
Solar/Wind Helper
0.116
315821AE2-092 GEN
Solar/Wind Helper
0.744
316499AE2-029_GEN
Solar/Wind Helper
0.265
315671AE2-027_GEN
Solar/Wind Helper
0.697
23583801GRNGAP
Solar/Wind Helper
8.496
233987AB2-037 GEN
Solar/Wind Harmer
0
315662AE1-191 GEN
Solar/Wind Helper
0.472
315666AE1-190 GEN
Solar/Wind Helper
0.118
319010AE1-072 C
Solar/Wind Helper
0.855
316065AD1-022 GEN
Solar/Wind Helper
0.439
315697AD1-025 GEN
Solar/Wind Helper
0.87
316185AD1-033 GEN
Solar/Wind Helper
0.401
316280AD1-041 GEN
Solar/Wind Helper
0.295
316478AD1-087 GEN
Solar/Wind Helper
0.345
316486AD2-202 GEN
Solar/Wind Helper
0.101
316447AC1-158 HLD
Solar/Wind Helper
1.016
316044AC1-158 PL1
Solar/Wind Helper
0.462
316045AC1-158 PL2
Solar/Wind Helper
1.478
316450AC1-158 RIC
Solar/Wind Helper
0.123
316468AD1-105 GEN
Solar/Wind Helper
0.45
316072AD1-144
Solar/Wind Helper
0.086
315687AD1-152 GEN
Solar/Wind Helper
0.421
316156AD2-030 GEN
Solar/Wind Helper
0.117
315785AD2-033 C
Solar/Wind Helper
0.694
316337AD2-073 GEN
Solar/Wind Helper
0.12
233968AD2-076_GEN
Solar/Wind Harmer
0.48
234012AE2-112_GEN
Solar/Wind Harmer
0.166
234014AF1-036_GEN
Solar/Wind Harmer
0.196
234015AF2-250 C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.089
207528AF2-192 GEN
Solar/Wind Harmer
0.06
226929AD2-058 GEN
Solar/Wind Helper
0.04
313526AB2-022
Solar/Wind Helper
0.114
316313AB2-026
Solar/Wind Helper
0.115
209120AE2-241 GEN
Solar/Wind Harmer
0.146
209093AE2-110 GEN
Solar/Wind Harmer
0.146
3145513AHOSKIE
Solar/Wind Helper
0.339
3145513AHOSKIE
Solar/Wind Helper
0.339
230430AE1-229_GEN
Solar/Wind Harmer
1.387
219623KINSLEYBEA C
Solar/Wind Harmer
0
208862AG1-362 C
Solar/Wind Harmer
0.037
209130AF1-271A GEN
Solar/Wind Harmer
0.122
209142AF1-226 GEN
Solar/Wind Harmer
0.256
205967AE2-211_GEN
Solar/Wind Harmer
0.453
205951AE1-129_GEN
Solar/Wind Harmer
0.468
270494AE1-108_GEN
Solar/Wind Helper
0.777
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
1.307
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3146206CASHIE
Solar/Wind Helper
0.341
3146206CASHIE
Solar/Wind Helper
0.341
3146206CASHIE
Solar/Wind Helper
0.341
3142666NORTHAMPTON
Solar/Wind Helper
0.336
3142666NORTHAMPTON
Solar/Wind Helper
0.336
3142666NORTHAMPTON
Solar/Wind Helper
0.336
3142666NORTHAMPTON
Solar/Wind Helper
0.202
3142666NORTHAMPTON
Solar/Wind Helper
0.336
316349AD2-085 GEN
Solar/Wind Helper
0.291
3156021HOLLOMANSOL
Solar/Wind Helper
0.544
313506AB2-031 GEN
Solar/Wind Helper
0.323
316006AB2-029 C
Solar/Wind Helper
0.127
313527AB2-043 GEN
Solar/Wind Helper
0.265
316322AB2-045
Solar/Wind Helper
0.109
316359AB2-059 GEN
Solar/Wind Helper
0.519
316131AB2-060 GEN
Solar/Wind Helper
0.425
316192AB2-158 GEN
Solar/Wind Helper
0.539
316083AB2-161 GEN
Solar/Wind Helper
0.287
316174AB2-169 GEN
Solar/Wind Helper
0.398
316087AB2-174 GEN
Solar/Wind Helper
0.434
316132AB2-190 GEN1
Solar/Wind Helper
0.436
316458AB2-190 GEN2
Solar/Wind Helper
0.436
316375AC2-012 GEN
Solar/Wind Helper
0.676
316339AD2-160 GEN
Solar/Wind Helper
0.286
316239AB2-077_GEN
Solar/Wind Helper
0.106
316238AB2-078_GEN
Solar/Wind Helper
0.106
316237AB2-079_GEN
Solar/Wind Helper
0.106
316140AB2-099
Solar/Wind Helper
0.027
316223AC1-118
Solar/Wind Helper
0.122
315975AC1-164 GENB
Solar/Wind Helper
0.029
315976AC1-164 GENA
Solar/Wind Helper
0.996
316169AC1-164_GENC
Solar/Wind Helper
0.86
316381AD1-082 GEN
Solar/Wind Helper
0.39
316233AE1-074 FULL
Solar/Wind Helper
0.118
316236AE1-162_GEN
Solar/Wind Helper
0.115
315607AA1-063A GEN
Solar/Wind Helper
0.407
233964AF2-378 GEN
Solar/Wind Harmer
0
3130546PLYMOUTH
Solar/Wind Helper
0.343
3145543BTLEBRO
Solar/Wind Helper
0.258
3145543BTLEBRO
Solar/Wind Helper
0.323
3145543BTLEBRO
Solar/Wind Helper
0.323
3145543BTLEBRO
Solar/Wind Helper
0.323
3145593CAROLNA
Solar/Wind Helper
0.336
3145593CAROLNA
Solar/Wind Helper
0.336
3145683EARLEYS
Solar/Wind Helper
0.338
3145683EARLEYS
Solar/Wind Helper
0.338
3145683EARLEYS
Solar/Wind Helper
0.338
3145683EARLEYS
Solar/Wind Helper
0.677
200200DELTA2 CT1
50/50
2.837
200201DELTA2 CT2
50/50
2.837
200202DELTA2 ST
50/50
5.068
207511W3-106 GEN
Solar/Wind Harmer
0
208972BECR K09
Solar/Wind Harmer
1.195
209029WAYMART-WD
Solar/Wind Harmer
2.938
230407AD2-065 C
Solar/Wind Harmer
0
3130086AYDLETT
Solar/Wind Helper
1.419
3137643SOCKMAN
Solar/Wind Helper
1.344
3138216PACIFIC
Solar/Wind Helper
0.071
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.015
3138543CONSLDL
Solar/Wind Helper
0.214
3142946ENON
Solar/Wind Helper
0.037
3142946ENON
Solar/Wind Helper
0.122
3144536CHRHLND
Solar/Wind Helper
0.054
3144873MCLAUGH
Solar/Wind Helper
0.009
3145573BETHELC
Solar/Wind Helper
0.325
3145573BETHELC
Solar/Wind Helper
0.325
3145783HORNRTN
Solar/Wind Helper
0.335
3145796HORNRTN
Solar/Wind Helper
1.002
3145796HORNRTN
Solar/Wind Helper
1.102
3145796HORNRTN
Solar/Wind Helper
0.334
3145796HORNRTN
Solar/Wind Helper
0.334
3145796HORNRTN
Solar/Wind Helper
1.336
3145796HORNRTN
Solar/Wind Helper
1.069
3145796HORNRTN
Solar/Wind Helper
0.134
3145823KELFORD
Solar/Wind Helper
0.336
3145823KELFORD
Solar/Wind Helper
0.336
3145893MURPHYS
Solar/Wind Helper
1.091
3145893MURPHYS
Solar/Wind Helper
0.614
3145893MURPHYS
Solar/Wind Helper
0.273
3145893MURPHYS
Solar/Wind Helper
0.341
3145893MURPHYS
Solar/Wind Helper
1.364
3145893MURPHYS
Solar/Wind Helper
0.341
3145893MURPHYS
Solar/Wind Helper
0.921
3145933PARMELE
Solar/Wind Helper
0.662
3145933PARMELE
Solar/Wind Helper
0.331
3145933PARMELE
Solar/Wind Helper
0.331
3145963POPLR C
Solar/Wind Helper
0.336
3145963POPLR C
Solar/Wind Helper
0.336
3146033SCOT NK
Solar/Wind Helper
1.334
3146043SEABORD
Solar/Wind Helper
0.339
3146073TAR RVR
Solar/Wind Helper
0.325
3146083TARBORO
Solar/Wind Helper
0.325
3146083TARBORO
Solar/Wind Helper
0.325
3146173TUNIS
Solar/Wind Helper
0.34
3146173TUNIS
Solar/Wind Helper
0.34
3146173TUNIS
Solar/Wind Helper
0.34
3146173TUNIS
Solar/Wind Helper
0.34
3146233WITAKRS
Solar/Wind Helper
1.293
3146233WITAKRS
Solar/Wind Helper
0.221
3146263WOODLND
Solar/Wind Helper
0.338
3146263WOODLND
Solar/Wind Helper
0.338
315611Z1-036_GEN2
Solar/Wind Helper
2.541
315800Z1-036_GEN1
Solar/Wind Helper
2.541
316095T157 G97
Solar/Wind Helper
1.272
316097T157 G90
Solar/Wind Helper
1.272
316318V4-068
Solar/Wind Helper
0.026
316319Z2-044 C
Solar/Wind Helper
0.063
316320Y1-086
Solar/Wind Helper
0.114
316321Z2-027
Solar/Wind Helper
0.113
942461AE2-259 GEN
Solar/Wind Helper
0.542
944491AF1-114 GEN
Solar/Wind Helper
0.618
946281AF1-292 GEN
Solar/Wind Helper
0.081
961541AF2-445A GEN
Solar/Wind Harmer
0.146
961611AG1-000B GEN
Solar/Wind Helper
0.515
961671AG1-007 GEN
Solar/Wind Helper
0.049
961941AG1-037 GEN
Solar/Wind Helper
0.027
961951AG1-038 GEN
Solar/Wind Helper
0.268
963401AG1-189 GEN
Solar/Wind Harmer
0.107
966871AG1-558 GEN
Solar/Wind Helper
0.119
966881AG1-559 GEN
Solar/Wind Helper
0.123
970025AG2-016 GEN
Solar/Wind Harmer
0.176
970095AG2-074 GEN
Solar/Wind Harmer
0.284
970453AG2-297 GEN
Solar/Wind Harmer
0.178
970597AG2-380 GEN
Solar/Wind Harmer
3.915
970695AG2-447 GEN
Solar/Wind Harmer
0.197
970997AG2-616 GEN
Solar/Wind Harmer
0.465
971007AG2-625 GEN
Solar/Wind Harmer
0.16
971009AG2-626 GEN
Solar/Wind Harmer
0.102
971189AH1-054 GEN
Solar/Wind Harmer
0.073
971195AH1-057 GEN
Solar/Wind Harmer
0.071
971519AH1-257 GEN
Solar/Wind Harmer
0.157
971521AH1-258 GEN
Solar/Wind Harmer
0.168
971667AH1-334 GEN
Solar/Wind Harmer
0.171
219918AC2-009 C
Solar/Wind Harmer
0
316431W1029_GEN1
Solar/Wind Helper
1.883
316433W1029_GEN2
Solar/Wind Helper
1.883
316435W1029_GEN3
Solar/Wind Helper
1.883
940641AE2-051 GEN
Solar/Wind Helper
0.855
957601AF2-054 GEN
Solar/Wind Helper
0.117
957831AF2-077 GEN
Solar/Wind Helper
0.117
957971AF2-091 GEN
Solar/Wind Helper
0.21
964211AG1-282 GEN
Solar/Wind Helper
0.12
964441AG1-307 GEN
Solar/Wind Helper
0.473
966001AG1-469 GEN
Solar/Wind Helper
0.085
966621AG1-532 GEN
Solar/Wind Helper
0.073
972141AH1-641 GEN
Solar/Wind Harmer
0.139
972177AH1-672 GEN
Solar/Wind Harmer
0.738
972281AH1-725 GEN
50/50
134.827
233984AB2-036 GEN
Solar/Wind Harmer
0.902
234041AC1-190 GEN
Solar/Wind Harmer
0.492
315732AD1-074 GEN1
Solar/Wind Helper
0.825
315733AD1-074 GEN2
Solar/Wind Helper
0.825
315735AD1-075 GEN1
Solar/Wind Helper
0.413
315737AD1-076 GEN
Solar/Wind Helper
0.6
315773AC2-141 GEN
Solar/Wind Helper
1.381
316003AC1-222 GEN
Solar/Wind Helper
0.328
316023GEN1_S
Solar/Wind Helper
0.274
316118AC1-105 GEN
Solar/Wind Helper
0.263
316129AC1-054 GEN
Solar/Wind Helper
0.346
316164AC1-076 GEN
Solar/Wind Helper
0.394
316210AC1-098 GEN
Solar/Wind Helper
0.479
316212AC1-099_GEN
Solar/Wind Helper
0.266
316274AC1-208 GEN
Solar/Wind Helper
0.425
316294AC1-161 GEN
Solar/Wind Helper
1.381
316365GEN2_N
Solar/Wind Helper
0.274
316420AA1-050 GEN
Solar/Wind Helper
0.418
316473AC1-191 GEN
Solar/Wind Helper
0.477
227287AC2-120 GEN
Solar/Wind Helper
0.197
238147AE2-230_GEN1
Solar/Wind Helper
0.201
238148AE2-230_GEN2
Solar/Wind Helper
0.201
238149AF1-291A_GEN
Solar/Wind Helper
0.057
238152AF2-075_GEN
Solar/Wind Helper
0.287
230422AE1-104_GEN1
Solar/Wind Harmer
38.509
230425AE1-104_GEN2
Solar/Wind Harmer
38.509
234033AF1-007_GEN
Solar/Wind Harmer
48.189
316487AF1-042 GEN
Solar/Wind Helper
0.268
315833AF1-017_GEN
Solar/Wind Helper
0.228
316484AD2-074 GEN
Solar/Wind Helper
0.512
207500AE2-000G1
Solar/Wind Harmer
34.99
207497AE2-000G2
Solar/Wind Harmer
34.99
207507AE2-000G3
Solar/Wind Harmer
34.99
207487AE2-000G4
Solar/Wind Harmer
34.99
CBM NorthLTFEXP_CBM-N->PJM
CBM
63.083
G-007ALTFEXP_G-007A->PJM
CMTX
41.37
VFTLTFEXP_VFT->PJM
CMTX
109.253
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.343
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.082
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
18.051
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.78
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.788
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019E_SRT-W


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019E_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.11 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:4492.66
MW Contribution:
0.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
43.134
200053ROCKSP 2
50/50
43.134
200054ROCKSP 3
50/50
42.696
200055ROCKSP 4
50/50
42.696
200203Y1-065-STG
50/50
5.777
200204Y1-065-CTG1
50/50
3.637
200205Y1-065-CTG2
50/50
3.637
3147043LAWRENC
Solar/Wind Helper
0.202
3147133PAMPLIN
Solar/Wind Helper
1.056
3147133PAMPLIN
Solar/Wind Helper
0.269
3147133PAMPLIN
Solar/Wind Helper
0.336
23546401DTGZ2-030
Solar/Wind Helper
0.057
20676328BVR_Y1-020
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
23777901MDS_W4-102
Solar/Wind Helper
0.104
3137176SLIGO L2192
Solar/Wind Helper
1.417
3141426STAFORD
Solar/Wind Helper
0.09
3141906WESTMOR
Solar/Wind Helper
0.152
3142416OLDCHRC
Solar/Wind Helper
0.961
3142416OLDCHRC
Solar/Wind Helper
0.368
3142433PROV 92
Solar/Wind Helper
1.47
3142956BIRDNECK
Solar/Wind Helper
0.593
3143316POE
Solar/Wind Helper
1.422
3145506HICKORY
Solar/Wind Helper
1.427
3145506HICKORY
Solar/Wind Helper
0.856
3145506HICKORY
Solar/Wind Helper
0.214
3146386ELIZ CT
Solar/Wind Helper
0.354
3146776BUCKING
Solar/Wind Helper
1.369
3146776BUCKING
Solar/Wind Helper
0.111
3146776BUCKING
Solar/Wind Helper
0.123
3146776BUCKING
Solar/Wind Helper
0.137
209027LOR2_Q27
Solar/Wind Harmer
4.593
212266LOR1
Solar/Wind Harmer
1.254
217081WEATEXAS C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
235020AA1-095 C
Solar/Wind Helper
0.022
316075AC2-137 C
Solar/Wind Helper
0.118
316077AC2-138 C
Solar/Wind Helper
0.084
3138133OCRAN
Solar/Wind Helper
0.111
3138133OCRAN
Solar/Wind Helper
0.221
3141766HARMONY
Solar/Wind Helper
0.074
3141783LANCAST
Solar/Wind Helper
0.222
3141783LANCAST
Solar/Wind Helper
0.148
3141813NORNECK
Solar/Wind Helper
0.374
3141913WHIT STONE
Solar/Wind Helper
0.369
3143226MDLTHAN
Solar/Wind Helper
0.366
3143873LANEXA
Solar/Wind Helper
0.221
3145273HOLLAND
Solar/Wind Helper
0.264
3146376EDENTON
Solar/Wind Helper
0.349
3146456SLIGO L269
Solar/Wind Helper
0.356
3146456SLIGO L269
Solar/Wind Helper
0.356
3146486SUNBURY
Solar/Wind Helper
0.354
3146486SUNBURY
Solar/Wind Helper
0.354
3146516WINFALL
Solar/Wind Helper
0.353
3146516WINFALL
Solar/Wind Helper
0.353
3146516WINFALL
Solar/Wind Helper
1.143
3146516WINFALL
Solar/Wind Helper
0.353
3146516WINFALL
Solar/Wind Helper
0.353
3146516WINFALL
Solar/Wind Helper
0.353
3146626S HERTFORD
Solar/Wind Helper
0.352
3146626S HERTFORD
Solar/Wind Helper
0.352
3146626S HERTFORD
Solar/Wind Helper
0.352
3146843MT LREL
Solar/Wind Helper
0.324
3146843MT LREL
Solar/Wind Helper
0.324
3146926FARMVIL
Solar/Wind Helper
0.204
3146926FARMVIL
Solar/Wind Helper
0.204
3147666LOUISA
Solar/Wind Helper
1.528
3147666LOUISA
Solar/Wind Helper
0.879
3147983MERCK5
Solar/Wind Helper
0.133
200034PCHBTM 2
50/50
99.55
200035PCHBTM 3
50/50
16.404
200192DELTA CT1
50/50
1.507
200193DELTA CT2
50/50
1.507
200194DELTA CT3
50/50
1.507
200195DELTA ST
50/50
2.511
3141726DUNNSVL
Solar/Wind Helper
1.493
3145663CRESWEL
Solar/Wind Helper
0.969
316034AC1-036 C
Solar/Wind Helper
0.074
316036AC1-147 C
Solar/Wind Helper
0.115
316059AD1-063 C
Solar/Wind Helper
0.089
316159AE1-175 C
Solar/Wind Helper
0.116
316240AF1-291 C
Solar/Wind Helper
0.117
316246AF1-032 C
Solar/Wind Helper
0.086
316248AF1-058 C
Solar/Wind Helper
0.103
316258AE1-075 C
Solar/Wind Helper
0.103
316305AF2-043 C
Solar/Wind Helper
0.114
316314AB2-024 C
Solar/Wind Helper
0.118
316315AB2-025 C
Solar/Wind Helper
0.113
316316AC1-027 C
Solar/Wind Helper
0.101
316317KELFORD C
Solar/Wind Helper
0.125
316382AG1-145 C
Solar/Wind Helper
0.117
316405AF2-144 C
Solar/Wind Helper
0.098
208835TUHI V3-051
Solar/Wind Harmer
0.06
208835TUHI V3-051
Solar/Wind Harmer
0.06
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
226910AB2-157 C
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Harmer
0.195
233970AC1-092 C
Solar/Wind Harmer
0.195
233971AC1-093 C
Solar/Wind Harmer
0.185
233972AC1-094 C
Solar/Wind Harmer
0.157
233973AC2-185 C
Solar/Wind Harmer
0.394
219727YARDVSOLFA C
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Helper
0.349
3130156CHOWAN
Solar/Wind Helper
0.349
3130156CHOWAN
Solar/Wind Helper
0.349
3145336SMITFLD
Solar/Wind Helper
1.438
3145336SMITFLD
Solar/Wind Helper
0.144
3148133STUARTS
Solar/Wind Helper
0.198
3141196NOKESVL
Solar/Wind Helper
1.653
3147243WELCO
Solar/Wind Helper
0.2
3141873WAN 176
Solar/Wind Helper
0.074
3143526WINTERP
Solar/Wind Helper
1.908
3143526WINTERP
Solar/Wind Helper
1.908
316411AF1-147_GEN1
Solar/Wind Helper
0.34
316415AF1-147_GEN2
Solar/Wind Helper
0.34
316404AE1-155 C
Solar/Wind Helper
0.759
316017AA1-139 ULT1
Solar/Wind Helper
0.343
316018AA1-139 ULT2
Solar/Wind Helper
0.343
316181AB2-040 GEN
Solar/Wind Helper
0.435
316033AB2-134 GEN
Solar/Wind Helper
0.828
316388AE2-253 GEN
Solar/Wind Helper
0.286
3148013FISHERV
Solar/Wind Helper
0.19
3148013FISHERV
Solar/Wind Helper
0.331
3145176PASQUOTANK
Solar/Wind Helper
0.219
3132123MT JACKSON
Solar/Wind Helper
1.055
3132273ORANGE
Solar/Wind Helper
0.077
3142543TWELFTH
Solar/Wind Helper
0.035
3144303KENBRDG
Solar/Wind Helper
0.267
3147173SINAI
Solar/Wind Helper
0.32
3148463FAIRFLD
Solar/Wind Helper
0.316
238175AF1-290_GEN
Solar/Wind Helper
0.478
238169AE2-226 GEN1
Solar/Wind Helper
0.292
238170AE2-226 GEN2
Solar/Wind Helper
0.292
316203AE2-005 GEN
Solar/Wind Helper
0.769
316441AF1-014 GEN
Solar/Wind Helper
0.118
316494AC1-189 GEN
Solar/Wind Helper
0.421
315616AA1-038_C
Solar/Wind Helper
1.909
316005AA1-067
Solar/Wind Helper
0.079
316426AA2-053 GEN
Solar/Wind Helper
0.405
316190AA2-174 GEN
Solar/Wind Helper
0.027
316327AA2-057 GEN
Solar/Wind Helper
0.395
3156081AA2-088 GEN
Solar/Wind Helper
0.552
315614AA2-178 GEN
Solar/Wind Helper
0.445
315816AE2-034 GEN
Solar/Wind Helper
0.334
316312AB1-027
Solar/Wind Helper
0.148
316049AB1-081 GEN
Solar/Wind Helper
0.416
316011AB1-132 GEN
Solar/Wind Helper
0.65
316369SG1_INVT
Solar/Wind Helper
0.569
315651AD1-115 GEN
Solar/Wind Helper
0.95
237061AD1-155 GEN
Solar/Wind Helper
0.428
316463AE2-346 GEN
Solar/Wind Helper
0.066
315839AE2-212 C
Solar/Wind Helper
0.116
315821AE2-092 GEN
Solar/Wind Helper
0.746
316499AE2-029_GEN
Solar/Wind Helper
0.266
315671AE2-027_GEN
Solar/Wind Helper
0.699
23583801GRNGAP
Solar/Wind Helper
8.529
233987AB2-037 GEN
Solar/Wind Harmer
0
315662AE1-191 GEN
Solar/Wind Helper
0.473
315666AE1-190 GEN
Solar/Wind Helper
0.118
319010AE1-072 C
Solar/Wind Helper
0.858
316065AD1-022 GEN
Solar/Wind Helper
0.44
315697AD1-025 GEN
Solar/Wind Helper
0.872
316185AD1-033 GEN
Solar/Wind Helper
0.402
316280AD1-041 GEN
Solar/Wind Helper
0.296
316478AD1-087 GEN
Solar/Wind Helper
0.346
316486AD2-202 GEN
Solar/Wind Helper
0.101
316447AC1-158 HLD
Solar/Wind Helper
1.019
316044AC1-158 PL1
Solar/Wind Helper
0.463
316045AC1-158 PL2
Solar/Wind Helper
1.481
316450AC1-158 RIC
Solar/Wind Helper
0.123
316468AD1-105 GEN
Solar/Wind Helper
0.451
316072AD1-144
Solar/Wind Helper
0.086
315687AD1-152 GEN
Solar/Wind Helper
0.422
316156AD2-030 GEN
Solar/Wind Helper
0.117
315785AD2-033 C
Solar/Wind Helper
0.696
316337AD2-073 GEN
Solar/Wind Helper
0.12
233968AD2-076_GEN
Solar/Wind Harmer
0.481
234012AE2-112_GEN
Solar/Wind Harmer
0.167
234014AF1-036_GEN
Solar/Wind Harmer
0.196
234015AF2-250 C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.09
207528AF2-192 GEN
Solar/Wind Harmer
0.06
226929AD2-058 GEN
Solar/Wind Helper
0.04
313526AB2-022
Solar/Wind Helper
0.114
316313AB2-026
Solar/Wind Helper
0.115
209120AE2-241 GEN
Solar/Wind Harmer
0.147
209093AE2-110 GEN
Solar/Wind Harmer
0.147
3145513AHOSKIE
Solar/Wind Helper
0.34
3145513AHOSKIE
Solar/Wind Helper
0.34
230430AE1-229_GEN
Solar/Wind Harmer
1.391
219623KINSLEYBEA C
Solar/Wind Harmer
0
208862AG1-362 C
Solar/Wind Harmer
0.037
209130AF1-271A GEN
Solar/Wind Harmer
0.122
209142AF1-226 GEN
Solar/Wind Harmer
0.257
205967AE2-211_GEN
Solar/Wind Harmer
0.456
205951AE1-129_GEN
Solar/Wind Harmer
0.471
270494AE1-108_GEN
Solar/Wind Helper
0.78
3145746EVERETS
Solar/Wind Helper
0.329
3145746EVERETS
Solar/Wind Helper
0.329
3145746EVERETS
Solar/Wind Helper
0.329
3145746EVERETS
Solar/Wind Helper
0.329
3145746EVERETS
Solar/Wind Helper
1.31
3145746EVERETS
Solar/Wind Helper
0.329
3145746EVERETS
Solar/Wind Helper
0.329
3145746EVERETS
Solar/Wind Helper
0.329
3146206CASHIE
Solar/Wind Helper
0.342
3146206CASHIE
Solar/Wind Helper
0.342
3146206CASHIE
Solar/Wind Helper
0.342
3142666NORTHAMPTON
Solar/Wind Helper
0.337
3142666NORTHAMPTON
Solar/Wind Helper
0.337
3142666NORTHAMPTON
Solar/Wind Helper
0.337
3142666NORTHAMPTON
Solar/Wind Helper
0.202
3142666NORTHAMPTON
Solar/Wind Helper
0.337
316349AD2-085 GEN
Solar/Wind Helper
0.292
3156021HOLLOMANSOL
Solar/Wind Helper
0.546
313506AB2-031 GEN
Solar/Wind Helper
0.324
316006AB2-029 C
Solar/Wind Helper
0.128
313527AB2-043 GEN
Solar/Wind Helper
0.265
316322AB2-045
Solar/Wind Helper
0.109
316359AB2-059 GEN
Solar/Wind Helper
0.52
316131AB2-060 GEN
Solar/Wind Helper
0.426
316192AB2-158 GEN
Solar/Wind Helper
0.541
316083AB2-161 GEN
Solar/Wind Helper
0.288
316174AB2-169 GEN
Solar/Wind Helper
0.399
316087AB2-174 GEN
Solar/Wind Helper
0.435
316132AB2-190 GEN1
Solar/Wind Helper
0.437
316458AB2-190 GEN2
Solar/Wind Helper
0.437
316375AC2-012 GEN
Solar/Wind Helper
0.678
316339AD2-160 GEN
Solar/Wind Helper
0.286
316239AB2-077_GEN
Solar/Wind Helper
0.106
316238AB2-078_GEN
Solar/Wind Helper
0.106
316237AB2-079_GEN
Solar/Wind Helper
0.106
316140AB2-099
Solar/Wind Helper
0.027
316223AC1-118
Solar/Wind Helper
0.122
315975AC1-164 GENB
Solar/Wind Helper
0.03
315976AC1-164 GENA
Solar/Wind Helper
0.998
316169AC1-164_GENC
Solar/Wind Helper
0.862
316381AD1-082 GEN
Solar/Wind Helper
0.391
316233AE1-074 FULL
Solar/Wind Helper
0.118
316236AE1-162_GEN
Solar/Wind Helper
0.115
315607AA1-063A GEN
Solar/Wind Helper
0.408
233964AF2-378 GEN
Solar/Wind Harmer
0
3130546PLYMOUTH
Solar/Wind Helper
0.344
3145543BTLEBRO
Solar/Wind Helper
0.259
3145543BTLEBRO
Solar/Wind Helper
0.324
3145543BTLEBRO
Solar/Wind Helper
0.324
3145543BTLEBRO
Solar/Wind Helper
0.324
3145593CAROLNA
Solar/Wind Helper
0.336
3145593CAROLNA
Solar/Wind Helper
0.336
3145683EARLEYS
Solar/Wind Helper
0.339
3145683EARLEYS
Solar/Wind Helper
0.339
3145683EARLEYS
Solar/Wind Helper
0.339
3145683EARLEYS
Solar/Wind Helper
0.678
200200DELTA2 CT1
50/50
2.843
200201DELTA2 CT2
50/50
2.843
200202DELTA2 ST
50/50
5.078
207511W3-106 GEN
Solar/Wind Harmer
0
208972BECR K09
Solar/Wind Harmer
1.198
209029WAYMART-WD
Solar/Wind Harmer
2.946
230407AD2-065 C
Solar/Wind Harmer
0
3130086AYDLETT
Solar/Wind Helper
1.423
3137643SOCKMAN
Solar/Wind Helper
1.347
3138216PACIFIC
Solar/Wind Helper
0.071
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.015
3138543CONSLDL
Solar/Wind Helper
0.215
3142946ENON
Solar/Wind Helper
0.037
3142946ENON
Solar/Wind Helper
0.122
3144536CHRHLND
Solar/Wind Helper
0.054
3144873MCLAUGH
Solar/Wind Helper
0.009
3145573BETHELC
Solar/Wind Helper
0.326
3145573BETHELC
Solar/Wind Helper
0.326
3145783HORNRTN
Solar/Wind Helper
0.336
3145796HORNRTN
Solar/Wind Helper
1.005
3145796HORNRTN
Solar/Wind Helper
1.105
3145796HORNRTN
Solar/Wind Helper
0.335
3145796HORNRTN
Solar/Wind Helper
0.335
3145796HORNRTN
Solar/Wind Helper
1.34
3145796HORNRTN
Solar/Wind Helper
1.072
3145796HORNRTN
Solar/Wind Helper
0.134
3145823KELFORD
Solar/Wind Helper
0.337
3145823KELFORD
Solar/Wind Helper
0.337
3145893MURPHYS
Solar/Wind Helper
1.094
3145893MURPHYS
Solar/Wind Helper
0.615
3145893MURPHYS
Solar/Wind Helper
0.273
3145893MURPHYS
Solar/Wind Helper
0.342
3145893MURPHYS
Solar/Wind Helper
1.367
3145893MURPHYS
Solar/Wind Helper
0.342
3145893MURPHYS
Solar/Wind Helper
0.923
3145933PARMELE
Solar/Wind Helper
0.663
3145933PARMELE
Solar/Wind Helper
0.332
3145933PARMELE
Solar/Wind Helper
0.332
3145963POPLR C
Solar/Wind Helper
0.337
3145963POPLR C
Solar/Wind Helper
0.337
3146033SCOT NK
Solar/Wind Helper
1.337
3146043SEABORD
Solar/Wind Helper
0.339
3146073TAR RVR
Solar/Wind Helper
0.326
3146083TARBORO
Solar/Wind Helper
0.326
3146083TARBORO
Solar/Wind Helper
0.326
3146173TUNIS
Solar/Wind Helper
0.341
3146173TUNIS
Solar/Wind Helper
0.341
3146173TUNIS
Solar/Wind Helper
0.341
3146173TUNIS
Solar/Wind Helper
0.341
3146233WITAKRS
Solar/Wind Helper
1.297
3146233WITAKRS
Solar/Wind Helper
0.222
3146263WOODLND
Solar/Wind Helper
0.338
3146263WOODLND
Solar/Wind Helper
0.338
315611Z1-036_GEN2
Solar/Wind Helper
2.548
315800Z1-036_GEN1
Solar/Wind Helper
2.548
316095T157 G97
Solar/Wind Helper
1.277
316097T157 G90
Solar/Wind Helper
1.277
316318V4-068
Solar/Wind Helper
0.026
316319Z2-044 C
Solar/Wind Helper
0.063
316320Y1-086
Solar/Wind Helper
0.114
316321Z2-027
Solar/Wind Helper
0.114
942461AE2-259 GEN
Solar/Wind Helper
0.544
944491AF1-114 GEN
Solar/Wind Helper
0.619
946281AF1-292 GEN
Solar/Wind Helper
0.081
961541AF2-445A GEN
Solar/Wind Harmer
0.147
961611AG1-000B GEN
Solar/Wind Helper
0.516
961671AG1-007 GEN
Solar/Wind Helper
0.049
961941AG1-037 GEN
Solar/Wind Helper
0.027
961951AG1-038 GEN
Solar/Wind Helper
0.268
963401AG1-189 GEN
Solar/Wind Harmer
0.107
966871AG1-558 GEN
Solar/Wind Helper
0.12
966881AG1-559 GEN
Solar/Wind Helper
0.124
970025AG2-016 GEN
Solar/Wind Harmer
0.177
970095AG2-074 GEN
Solar/Wind Harmer
0.285
970453AG2-297 GEN
Solar/Wind Harmer
0.178
970597AG2-380 GEN
Solar/Wind Harmer
3.924
970695AG2-447 GEN
Solar/Wind Harmer
0.197
970997AG2-616 GEN
Solar/Wind Harmer
0.466
971007AG2-625 GEN
Solar/Wind Harmer
0.16
971009AG2-626 GEN
Solar/Wind Harmer
0.102
971189AH1-054 GEN
Solar/Wind Harmer
0.074
971195AH1-057 GEN
Solar/Wind Harmer
0.071
971519AH1-257 GEN
Solar/Wind Harmer
0.157
971521AH1-258 GEN
Solar/Wind Harmer
0.169
971667AH1-334 GEN
Solar/Wind Harmer
0.172
219918AC2-009 C
Solar/Wind Harmer
0
316431W1029_GEN1
Solar/Wind Helper
1.888
316433W1029_GEN2
Solar/Wind Helper
1.888
316435W1029_GEN3
Solar/Wind Helper
1.888
940641AE2-051 GEN
Solar/Wind Helper
0.857
957601AF2-054 GEN
Solar/Wind Helper
0.118
957831AF2-077 GEN
Solar/Wind Helper
0.117
957971AF2-091 GEN
Solar/Wind Helper
0.21
964211AG1-282 GEN
Solar/Wind Helper
0.12
964441AG1-307 GEN
Solar/Wind Helper
0.47
966001AG1-469 GEN
Solar/Wind Helper
0.085
966621AG1-532 GEN
Solar/Wind Helper
0.074
972141AH1-641 GEN
Solar/Wind Harmer
0.14
972177AH1-672 GEN
Solar/Wind Harmer
0.739
972281AH1-725 GEN
50/50
135.033
233984AB2-036 GEN
Solar/Wind Harmer
0.904
234041AC1-190 GEN
Solar/Wind Harmer
0.493
315732AD1-074 GEN1
Solar/Wind Helper
0.827
315733AD1-074 GEN2
Solar/Wind Helper
0.827
315735AD1-075 GEN1
Solar/Wind Helper
0.414
315737AD1-076 GEN
Solar/Wind Helper
0.601
315773AC2-141 GEN
Solar/Wind Helper
1.384
316003AC1-222 GEN
Solar/Wind Helper
0.329
316023GEN1_S
Solar/Wind Helper
0.275
316118AC1-105 GEN
Solar/Wind Helper
0.264
316129AC1-054 GEN
Solar/Wind Helper
0.347
316164AC1-076 GEN
Solar/Wind Helper
0.395
316210AC1-098 GEN
Solar/Wind Helper
0.48
316212AC1-099_GEN
Solar/Wind Helper
0.267
316274AC1-208 GEN
Solar/Wind Helper
0.426
316294AC1-161 GEN
Solar/Wind Helper
1.384
316365GEN2_N
Solar/Wind Helper
0.275
316420AA1-050 GEN
Solar/Wind Helper
0.419
316473AC1-191 GEN
Solar/Wind Helper
0.479
227287AC2-120 GEN
Solar/Wind Helper
0.196
238147AE2-230_GEN1
Solar/Wind Helper
0.201
238148AE2-230_GEN2
Solar/Wind Helper
0.201
238149AF1-291A_GEN
Solar/Wind Helper
0.058
238152AF2-075_GEN
Solar/Wind Helper
0.288
230422AE1-104_GEN1
Solar/Wind Harmer
38.604
230425AE1-104_GEN2
Solar/Wind Harmer
38.604
234033AF1-007_GEN
Solar/Wind Harmer
48.3
316487AF1-042 GEN
Solar/Wind Helper
0.268
315833AF1-017_GEN
Solar/Wind Helper
0.229
316484AD2-074 GEN
Solar/Wind Helper
0.513
207500AE2-000G1
Solar/Wind Harmer
35.08
207497AE2-000G2
Solar/Wind Harmer
35.08
207507AE2-000G3
Solar/Wind Harmer
35.08
207487AE2-000G4
Solar/Wind Harmer
35.08
CBM NorthLTFEXP_CBM-N->PJM
CBM
63.26
G-007ALTFEXP_G-007A->PJM
CMTX
41.48
VFTLTFEXP_VFT->PJM
CMTX
109.55
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.359
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.091
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
18.113
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.793
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.829
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.87 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:3923.45
MW Contribution:
0.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
35.469
200053ROCKSP 2
50/50
35.469
200054ROCKSP 3
50/50
35.108
200055ROCKSP 4
50/50
35.108
200203Y1-065-STG
50/50
4.75
200204Y1-065-CTG1
50/50
2.991
200205Y1-065-CTG2
50/50
2.991
20676328BVR_Y1-020
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
3141426STAFORD
Solar/Wind Helper
0.078
3141906WESTMOR
Solar/Wind Helper
0.128
209027LOR2_Q27
Solar/Wind Harmer
3.742
212266LOR1
Solar/Wind Harmer
1.022
217081WEATEXAS C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
316077AC2-138 C
Solar/Wind Helper
0.07
3141813NORNECK
Solar/Wind Helper
0.313
3147666LOUISA
Solar/Wind Helper
1.259
3147666LOUISA
Solar/Wind Helper
0.724
200034PCHBTM 2
50/50
81.968
200035PCHBTM 3
50/50
13.502
200192DELTA CT1
50/50
1.241
200193DELTA CT2
50/50
1.241
200194DELTA CT3
50/50
1.241
200195DELTA ST
50/50
2.067
3141726DUNNSVL
Solar/Wind Helper
1.249
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
226910AB2-157 C
Solar/Wind Helper
0.022
233939AC1-091 C
Solar/Wind Harmer
0.159
233970AC1-092 C
Solar/Wind Harmer
0.159
233971AC1-093 C
Solar/Wind Harmer
0.151
233972AC1-094 C
Solar/Wind Harmer
0.128
233973AC2-185 C
Solar/Wind Harmer
0.322
219727YARDVSOLFA C
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.338
316411AF1-147_GEN1
Solar/Wind Helper
0.271
316415AF1-147_GEN2
Solar/Wind Helper
0.271
3132273ORANGE
Solar/Wind Helper
0.063
315651AD1-115 GEN
Solar/Wind Helper
0.778
233987AB2-037 GEN
Solar/Wind Harmer
0
316447AC1-158 HLD
Solar/Wind Helper
0.84
316044AC1-158 PL1
Solar/Wind Helper
0.382
316045AC1-158 PL2
Solar/Wind Helper
1.221
316450AC1-158 RIC
Solar/Wind Helper
0.102
316468AD1-105 GEN
Solar/Wind Helper
0.379
316337AD2-073 GEN
Solar/Wind Helper
0.101
233968AD2-076_GEN
Solar/Wind Harmer
0.392
234012AE2-112_GEN
Solar/Wind Harmer
0.136
234014AF1-036_GEN
Solar/Wind Harmer
0.16
234015AF2-250 C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.073
207528AF2-192 GEN
Solar/Wind Harmer
0.049
226929AD2-058 GEN
Solar/Wind Helper
0.047
209120AE2-241 GEN
Solar/Wind Harmer
0.12
209093AE2-110 GEN
Solar/Wind Harmer
0.12
230430AE1-229_GEN
Solar/Wind Harmer
1.133
219623KINSLEYBEA C
Solar/Wind Harmer
0
208862AG1-362 C
Solar/Wind Harmer
0.029
209130AF1-271A GEN
Solar/Wind Harmer
0.1
209142AF1-226 GEN
Solar/Wind Harmer
0.209
316006AB2-029 C
Solar/Wind Helper
0.104
316192AB2-158 GEN
Solar/Wind Helper
0.445
316223AC1-118
Solar/Wind Helper
0.102
233964AF2-378 GEN
Solar/Wind Harmer
0
200200DELTA2 CT1
50/50
2.341
200201DELTA2 CT2
50/50
2.341
200202DELTA2 ST
50/50
4.182
207511W3-106 GEN
Solar/Wind Harmer
0
208972BECR K09
Solar/Wind Harmer
0.976
209029WAYMART-WD
Solar/Wind Harmer
2.403
230407AD2-065 C
Solar/Wind Harmer
0
3138216PACIFIC
Solar/Wind Helper
0.056
944491AF1-114 GEN
Solar/Wind Helper
0.524
961541AF2-445A GEN
Solar/Wind Harmer
0.119
963401AG1-189 GEN
Solar/Wind Harmer
0.087
966881AG1-559 GEN
Solar/Wind Helper
0.104
970025AG2-016 GEN
Solar/Wind Harmer
0.144
970095AG2-074 GEN
Solar/Wind Harmer
0.232
970453AG2-297 GEN
Solar/Wind Harmer
0.145
970597AG2-380 GEN
Solar/Wind Harmer
3.196
970695AG2-447 GEN
Solar/Wind Harmer
0.161
970997AG2-616 GEN
Solar/Wind Harmer
0.38
971007AG2-625 GEN
Solar/Wind Harmer
0.13
971009AG2-626 GEN
Solar/Wind Harmer
0.083
971189AH1-054 GEN
Solar/Wind Harmer
0.06
971195AH1-057 GEN
Solar/Wind Harmer
0.058
971519AH1-257 GEN
Solar/Wind Harmer
0.128
971521AH1-258 GEN
Solar/Wind Harmer
0.137
971667AH1-334 GEN
Solar/Wind Harmer
0.14
219918AC2-009 C
Solar/Wind Harmer
0
957971AF2-091 GEN
Solar/Wind Helper
0.178
964211AG1-282 GEN
Solar/Wind Helper
0.1
972141AH1-641 GEN
Solar/Wind Harmer
0.114
972177AH1-672 GEN
Solar/Wind Harmer
0.603
972281AH1-725 GEN
50/50
112.063
233984AB2-036 GEN
Solar/Wind Harmer
0.737
234041AC1-190 GEN
Solar/Wind Harmer
0.402
316164AC1-076 GEN
Solar/Wind Helper
0.325
227287AC2-120 GEN
Solar/Wind Helper
0.24
230422AE1-104_GEN1
Solar/Wind Harmer
31.452
230425AE1-104_GEN2
Solar/Wind Harmer
31.452
234033AF1-007_GEN
Solar/Wind Harmer
39.4
207500AE2-000G1
Solar/Wind Harmer
28.559
207497AE2-000G2
Solar/Wind Harmer
28.559
207507AE2-000G3
Solar/Wind Harmer
28.559
207487AE2-000G4
Solar/Wind Harmer
28.559
CBM NorthLTFEXP_CBM-N->PJM
CBM
51.929
G-007ALTFEXP_G-007A->PJM
CMTX
33.751
VFTLTFEXP_VFT->PJM
CMTX
89.117
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.279
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.447
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.767
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.864
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.936
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.79 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:3815.35
MW Contribution:
0.19
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
44.545
200053ROCKSP 2
50/50
44.545
200054ROCKSP 3
50/50
44.093
200055ROCKSP 4
50/50
44.093
200203Y1-065-STG
50/50
5.966
200204Y1-065-CTG1
50/50
3.756
200205Y1-065-CTG2
50/50
3.756
20676328BVR_Y1-020
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
3141426STAFORD
Solar/Wind Helper
0.073
217081WEATEXAS C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
200034PCHBTM 2
50/50
104.357
200035PCHBTM 3
50/50
17.262
200192DELTA CT1
50/50
1.58
200193DELTA CT2
50/50
1.58
200194DELTA CT3
50/50
1.58
200195DELTA ST
50/50
2.633
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
226910AB2-157 C
Solar/Wind Helper
0.015
233939AC1-091 C
Solar/Wind Harmer
0.186
233970AC1-092 C
Solar/Wind Harmer
0.186
233971AC1-093 C
Solar/Wind Harmer
0.176
233972AC1-094 C
Solar/Wind Harmer
0.149
233973AC2-185 C
Solar/Wind Harmer
0.375
219727YARDVSOLFA C
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.318
316411AF1-147_GEN1
Solar/Wind Helper
0.27
316415AF1-147_GEN2
Solar/Wind Helper
0.27
315651AD1-115 GEN
Solar/Wind Helper
0.762
233987AB2-037 GEN
Solar/Wind Harmer
0
316447AC1-158 HLD
Solar/Wind Helper
0.817
316044AC1-158 PL1
Solar/Wind Helper
0.372
316045AC1-158 PL2
Solar/Wind Helper
1.189
316450AC1-158 RIC
Solar/Wind Helper
0.099
233968AD2-076_GEN
Solar/Wind Harmer
0.458
234012AE2-112_GEN
Solar/Wind Harmer
0.159
234014AF1-036_GEN
Solar/Wind Harmer
0.187
234015AF2-250 C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.076
207528AF2-192 GEN
Solar/Wind Harmer
0.048
226929AD2-058 GEN
Solar/Wind Helper
0.034
230430AE1-229_GEN
Solar/Wind Harmer
1.243
219623KINSLEYBEA C
Solar/Wind Harmer
0
316006AB2-029 C
Solar/Wind Helper
0.102
233964AF2-378 GEN
Solar/Wind Harmer
0
200200DELTA2 CT1
50/50
2.981
200201DELTA2 CT2
50/50
2.981
200202DELTA2 ST
50/50
5.325
207511W3-106 GEN
Solar/Wind Harmer
0
208972BECR K09
Solar/Wind Harmer
0.835
209029WAYMART-WD
Solar/Wind Harmer
2.087
230407AD2-065 C
Solar/Wind Harmer
0
3138216PACIFIC
Solar/Wind Helper
0.056
963401AG1-189 GEN
Solar/Wind Harmer
0.091
970025AG2-016 GEN
Solar/Wind Harmer
0.15
970095AG2-074 GEN
Solar/Wind Harmer
0.2
970453AG2-297 GEN
Solar/Wind Harmer
0.16
970597AG2-380 GEN
Solar/Wind Harmer
3.737
970695AG2-447 GEN
Solar/Wind Harmer
0.188
970997AG2-616 GEN
Solar/Wind Harmer
0.417
971007AG2-625 GEN
Solar/Wind Harmer
0.121
971009AG2-626 GEN
Solar/Wind Harmer
0.077
971189AH1-054 GEN
Solar/Wind Harmer
0.062
971195AH1-057 GEN
Solar/Wind Harmer
0.068
971519AH1-257 GEN
Solar/Wind Harmer
0.118
971521AH1-258 GEN
Solar/Wind Harmer
0.139
971667AH1-334 GEN
Solar/Wind Harmer
0.145
219918AC2-009 C
Solar/Wind Harmer
0
972141AH1-641 GEN
Solar/Wind Harmer
0.125
972177AH1-672 GEN
Solar/Wind Harmer
0.704
972281AH1-725 GEN
50/50
138.626
233984AB2-036 GEN
Solar/Wind Harmer
0.862
234041AC1-190 GEN
Solar/Wind Harmer
0.47
316164AC1-076 GEN
Solar/Wind Helper
0.317
227287AC2-120 GEN
Solar/Wind Helper
0.168
230422AE1-104_GEN1
Solar/Wind Harmer
34.424
230425AE1-104_GEN2
Solar/Wind Harmer
34.424
234033AF1-007_GEN
Solar/Wind Harmer
46.015
207500AE2-000G1
Solar/Wind Harmer
29.823
207497AE2-000G2
Solar/Wind Harmer
29.823
207507AE2-000G3
Solar/Wind Harmer
29.823
207487AE2-000G4
Solar/Wind Harmer
29.823
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.024
G-007ALTFEXP_G-007A->PJM
CMTX
33.705
VFTLTFEXP_VFT->PJM
CMTX
87.012
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.392
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.542
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
15.191
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.189
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.945
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o BG_P7_CNSTN_NWEST2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
BG_P7_CNSTN_NWEST2_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.98 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:3576.36
MW Contribution:
0.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
32.729
200053ROCKSP 2
50/50
32.729
200054ROCKSP 3
50/50
32.397
200055ROCKSP 4
50/50
32.397
200203Y1-065-STG
50/50
4.383
200204Y1-065-CTG1
50/50
2.76
200205Y1-065-CTG2
50/50
2.76
20676328BVR_Y1-020
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
3141426STAFORD
Solar/Wind Helper
0.071
209027LOR2_Q27
Solar/Wind Harmer
3.36
212266LOR1
Solar/Wind Harmer
0.917
217081WEATEXAS C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
200034PCHBTM 2
50/50
75.618
200035PCHBTM 3
50/50
12.284
200058HUNTR101
50/50
1.508
200059HUNTR201
50/50
1.508
200060HUNTR301
50/50
1.508
200061HUNTR401
50/50
2.883
200192DELTA CT1
50/50
1.145
200193DELTA CT2
50/50
1.145
200194DELTA CT3
50/50
1.145
200195DELTA ST
50/50
1.907
208835TUHI V3-051
Solar/Wind Harmer
0.053
208835TUHI V3-051
Solar/Wind Harmer
0.053
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
226910AB2-157 C
Solar/Wind Helper
0.017
233939AC1-091 C
Solar/Wind Harmer
0.147
233970AC1-092 C
Solar/Wind Harmer
0.147
233971AC1-093 C
Solar/Wind Harmer
0.14
233972AC1-094 C
Solar/Wind Harmer
0.118
233973AC2-185 C
Solar/Wind Harmer
0.298
219727YARDVSOLFA C
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.253
316411AF1-147_GEN1
Solar/Wind Helper
0.256
316415AF1-147_GEN2
Solar/Wind Helper
0.256
233987AB2-037 GEN
Solar/Wind Harmer
0
233968AD2-076_GEN
Solar/Wind Harmer
0.364
234012AE2-112_GEN
Solar/Wind Harmer
0.126
234014AF1-036_GEN
Solar/Wind Harmer
0.148
234015AF2-250 C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.067
207528AF2-192 GEN
Solar/Wind Harmer
0.044
226929AD2-058 GEN
Solar/Wind Helper
0.038
209120AE2-241 GEN
Solar/Wind Harmer
0.107
209093AE2-110 GEN
Solar/Wind Harmer
0.107
230430AE1-229_GEN
Solar/Wind Harmer
1.042
219623KINSLEYBEA C
Solar/Wind Harmer
0
208862AG1-362 C
Solar/Wind Harmer
0.028
209130AF1-271A GEN
Solar/Wind Harmer
0.089
209142AF1-226 GEN
Solar/Wind Harmer
0.188
233964AF2-378 GEN
Solar/Wind Harmer
0
200200DELTA2 CT1
50/50
2.16
200201DELTA2 CT2
50/50
2.16
200202DELTA2 ST
50/50
3.858
207511W3-106 GEN
Solar/Wind Harmer
0
208972BECR K09
Solar/Wind Harmer
0.879
209029WAYMART-WD
Solar/Wind Harmer
2.166
230407AD2-065 C
Solar/Wind Harmer
0
3138216PACIFIC
Solar/Wind Helper
0.053
961541AF2-445A GEN
Solar/Wind Harmer
0.107
963401AG1-189 GEN
Solar/Wind Harmer
0.08
970025AG2-016 GEN
Solar/Wind Harmer
0.132
970095AG2-074 GEN
Solar/Wind Harmer
0.209
970453AG2-297 GEN
Solar/Wind Harmer
0.133
970597AG2-380 GEN
Solar/Wind Harmer
2.968
970695AG2-447 GEN
Solar/Wind Harmer
0.149
970997AG2-616 GEN
Solar/Wind Harmer
0.349
971007AG2-625 GEN
Solar/Wind Harmer
0.118
971009AG2-626 GEN
Solar/Wind Harmer
0.075
971189AH1-054 GEN
Solar/Wind Harmer
0.055
971195AH1-057 GEN
Solar/Wind Harmer
0.054
971519AH1-257 GEN
Solar/Wind Harmer
0.116
971521AH1-258 GEN
Solar/Wind Harmer
0.125
971667AH1-334 GEN
Solar/Wind Harmer
0.128
219918AC2-009 C
Solar/Wind Harmer
0
972141AH1-641 GEN
Solar/Wind Harmer
0.105
972177AH1-672 GEN
Solar/Wind Harmer
0.559
972281AH1-725 GEN
50/50
121.856
233984AB2-036 GEN
Solar/Wind Harmer
0.684
234041AC1-190 GEN
Solar/Wind Harmer
0.372
227287AC2-120 GEN
Solar/Wind Helper
0.19
230422AE1-104_GEN1
Solar/Wind Harmer
28.921
230425AE1-104_GEN2
Solar/Wind Harmer
28.921
234033AF1-007_GEN
Solar/Wind Harmer
36.484
207500AE2-000G1
Solar/Wind Harmer
26.146
207497AE2-000G2
Solar/Wind Harmer
26.146
207507AE2-000G3
Solar/Wind Harmer
26.146
207487AE2-000G4
Solar/Wind Harmer
26.146
CBM NorthLTFEXP_CBM-N->PJM
CBM
47.134
G-007ALTFEXP_G-007A->PJM
CMTX
30.778
VFTLTFEXP_VFT->PJM
CMTX
81.127
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.013
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.303
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.165
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.746
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.566
MDUPJM->LTFIMP_MDU
CLTF
0
CONTINGENCY 'AP_P1-2_PE-500-3835T_SRT-A'
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019E_SRT-W'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 1   /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 3   /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 2           /*01DOUBS      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'PECO_P1-2_5007_SRT-A
 TRIP BRANCH FROM BUS 200066 TO BUS 270095 CKT 1   /*PCHBTM1N     500.0 - CHAN         500.0
END
CONTINGENCY 'BG_P7_CNSTN_NWEST2_SRT-A'
 OPEN BRANCH FROM BUS 220961 TO BUS 220963 CKT 1   /*NWEST326     230.0 - CONASTON     230.0
 OPEN BRANCH FROM BUS 220962 TO BUS 220963 CKT 1   /*NWEST311     230.0 - CONASTON     230.0
END
200004 to 200003 ckt 1

Light Load Analysis

The New Service Request AG2-447 was evaluated as a 20.0 MW injection

AG2-447 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 134.25 MW (20.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary:

New Service Requests (projects) in PJM Transition Cycle 2, Cluster 86 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 86 projects.

This analysis is effectively a screening study to determine whether the addition of the cluster 86 projects will meet the dynamics requirements of the NERC, DPL and PJM reliability standards.

The load flow scenario for the analysis was based on the RTEP 2028 summer peak load case, modified to include applicable projects. Cluster 86 projects have been dispatched online at maximum power output, with 1.0 voltage at the terminal bus.

Cluster 86 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 127 contingencies were studied, each with a 20 second simulation time period. Studied faults included:

  1. Steady-state operation (20 second run);
  2. Three-phase faults with normal clearing time;
  3. Single-phase bus faults with normal clearing time;
  4. Single-phase faults with stuck breaker;
  5. Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure;

No relevant tower faults or single-phase bus faults were identified for this study.

For generator interconnection studies, Category P3 and P6 contingencies will be evaluated on an as-needed basis.

Prior outage scenarios will not be considered for this study.

Stations at which the faults listed above will be applied are:

  • Carville 138 kV (AG2-380/AF1-036/AE2-112/AD2-076 POI)
  • Wye Mills 138 kV
  • Pondtown 138 kV (AB2-032/AB2-153 POI)
  • Cedar Creek 138 kV (AG2-447/AC1-091/AC1-092/AC1-093/AC1-094/AC2 184/AC2-185 POI)
  • Cedar Creek 230 kV
  • Clayton 138 kV (W1-062 POI)
  • Farmview 138 kV (AH1-672 POI)
  • Milford 138 kV
  • South Harrington 138 kV

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

For all of the fault contingencies tested on the 2028 peak load case:

  1. Cluster 86 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  2. The system with Cluster 86 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes,
  3. Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus),
  4. No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

AG2-380, AG2-447, and AH1-672 meet the 0.95 leading and lagging PF requirement.

AH1-672 exhibited slow reactive power recovery following several contingencies (P1.22 and P1.23), though system stability was not compromised. To improve performance, model tuning was conducted. In the REPCA1 model, the reactive current compensation gain, Kc, was increased from 0.0 pu to 0.07 pu. This change improved reactive power recovery.

The IPCMD and IQCMD states in the REGCA1 model of AG2-447 GEN, and AH1-672 GEN showed erratic behavior for some contingencies in which these generators have been disconnected as part of the contingency event. Since the machine is disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

For several contingencies (P1.23, P1.24, P1.25, and P4.47), the W1-062/DEMEC NUG units were tripping when dispatched at their Pmax. This behavior was also observed even after turning off all queue projects in Cluster 86, indicating that the issue is related to the W1-062/DEMEC NUG units themselves. To avoid tripping, the generator output of these units was reduced from Pmax = 52 MW to Pgen = 45 MW.

For several contingencies (e.g., P1.30), following fault clearing the system exhibits small, damped oscillations as the excitation and voltage control systems stabilize the voltage. The voltage settles to its steady-state value within a few seconds, indicating stable system behavior. These oscillations do not impact the overall stability of the system.

High voltage spikes occurred in the simulations immediately after fault clearing for some of the contingencies studied (i.e., fault where spike is observed]). The voltage spike is a known artifact of the WECC generic renewable models as stated in the WECC Solar Plant Dynamic Model Guidelines: “It should be noted that generic dynamic models for inverter-based generator tend to produce a short-duration (a cycle or shorter) voltage spike at fault inception and clearing. These spikes should be ignored in most cases, as they do not represent the performance of actual hardware. They are simply a consequence of the model’s limited bandwidth, integration time step, and the way current injection models interface with the network solution.”

No mitigations were found to be required.

Table 1: TC2 Cluster 86 Projects

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

86

AG2-380

Storage

DPL

106.00

20.00

20.00

Carville 138 kV IV Substation

AG2-447

Solar

DPL

134.25

20.00

12.00

Cedar Creek 138 kV VII Substation

AH1-672

Solar

DPL

75.00

75.00

48.90

Farmview 138 kV Substation

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AG2-447 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-032Church-Wye Mills 138 kVIn Service
AB2-036Church - Oil City 138kVSuspended
AB2-037Keeney-Steele 230kVPartially in Service - Under Construction
AB2-049Gloucester Township 12kVIn Service
AB2-057Brunswick 26kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVIn Service
AB2-153Church-Wye Mills 138 kVIn Service
AB2-172Todd 69kVIn Service
AB2-179Townsend 138kVIn Service
AC1-010Gloucester 26kVPartially in Service - Under Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-091Cedar Creek 138kV ISuspended
AC1-092Cedar Creek 138kV IISuspended
AC1-093Cedar Creek 138kV IIISuspended
AC1-094Cedar Creek 138kV IVSuspended
AC1-190East New Market 69kVSuspended
AC2-009Pennington 13 kVIn Service
AC2-023Hebron 69kVSuspended
AC2-185Cedar Creek 138kV IISuspended
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD2-027Camden Switch 26 kVIn Service
AD2-042Camden Switch 26 kV IIIn Service
AD2-065Atco 12 kVIn Service
AD2-076Carville 138 kVWithdrawn
AD2-135Williamstown 12kVPartially in Service - Under Construction
AE1-041Edison 4kVIn Service
AE1-104BL England 138 kVSuspended
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE2-112Carville 138 kV IIWithdrawn
AF1-007Indian River 230 kV ISuspended
AF1-036Carville 138 kV IIIWithdrawn
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF2-060Wattsville 12 kVSuspended
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-254Cookstown-New Lisbon 34.5 kVWithdrawn
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AG1-130Burlington 26 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG2-016Oyster Creek-Whitings 34.5 kVActive
AG2-297Cumberland 230 kVActive
AG2-380Carville 138 kV IVActive
AG2-616Churchtown - Upper Pittsgrove 138 kVActive
AH1-054Upton-Whitings 34.5 kVActive
AH1-057Edgewood 12.47 kVActive
AH1-258Belford - Keansburg 34.5 kVActive
AH1-260New Freedom - Monroe 230 kVActive
AH1-334Lakehurst - Whitings 34.5 kVActive
AH1-641Churchtown - Upper Pittsgrove 138kVActive
AH1-672Farmview 138 kVActive
AH1-701Valero 69 kVActive
AH1-710Salem 500kVActive
V1-021Cape May County 12kVIn Service
V2-041Clayville 12kVIn Service
V2-046Pilesgrove Township 12kVIn Service
V4-054Fairfield Township 12kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
X2-083Newark 12kVIn Service
X3-008Todd 69kVIn Service
X3-066Church Hill 69kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y2-105Eagle Point 230kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG2-447 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
DPLn9774.0Rebuild BRIDGEVL 69.0 kV to TAYLOR 69.0 kV ckt 1 to achieve 70 MVA minimumCost Allocated$15,000,000N/A
Grand Total:$15,000,000

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9774.0
Type
Load Flow
TO
DPL
RTEP ID / TO ID
n9774.0 / (Pending)
Title
Rebuild BRIDGEVL 69.0 kV to TAYLOR 69.0 kV ckt 1 to achieve 70 MVA minimum
Description
Rebuild line with new conductor
Total Cost ($USD)
$15,000,000
Discounted Total Cost ($USD)
$15,000,000
Allocated Cost ($USD)
$15,000,000
Time Estimate
36 to 60 Months

Aggregate Contributor

FacilityContingency
BRIDGEVL-TAYLOR 69.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA82.0 MVA
SUMB93.0 MVA
SUMC107.0 MVA
WINA96.0 MVA
WINB105.0 MVA
WINC121.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-4470.7 MW100.0%$15,000,000

System Reinforcement: b3780.7
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.7
Title
Build new Batavia Road substation (Projected ISD 12/31/2028)
Description
Build Batavia Road substation. Add 4 x 230kV breaker bays
Cost Information
Time Estimate
Dec 31 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.8
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.8
Title
Graceton 500 kV substation expansion (Projected ISD 12/31/2028)
Description
Add 3x 500 kV breaker bays, 2x 500/230 kV auto transformer, 1x 500 kV caps
Cost Information
Time Estimate
Dec 31 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.9
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.9
Title
Graceton to Batavia Road 230 kV double circuit pole line (Projected ISD 12/31/2028)
Description
Graceton to Batavia Road 230 kV double circuit pole line New rating: 1331 MVA SN/ 1594 MVA SE
Cost Information
Time Estimate
Dec 31 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.5
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.5
Title
Build Solley Road substation + Statcom (Projected ISD 12/31/2028)
Description
Build Solley Road substation + Statcom. New STATCOM rating: 350 MVAR Add 4x 230 kV breakers bays.
Cost Information
Time Estimate
Dec 31 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.13
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.13
Title
Batavia Road to Riverside 230 kV reconductor
Description
Batavia Road to Riverside 230 kV reconductor New rating: 1941 MVA SN / 2181 MVA SE
Cost Information
Time Estimate
Dec 31 2027

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.11
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3780.11
Title
Brighton Statcom and Capacitor (Projected ISD 12/31/2028)
Description
Brighton Statcom and capacitor New STATCOM rating: 350 MVAR New capacitor rating: 350 MVAR
Cost Information
Time Estimate
Dec 31 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.15
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.15
Title
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV sub
Description
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV substation by rebuilding 5012 between new terminal at Peach Bottom South and North Delta on single circuit structures and terminating at North Delta.
Cost Information
Time Estimate
Apr 10 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.17
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.17
Title
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV sub (Transource)
Description
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV substation by rebuilding 5012 between new terminal at Peach Bottom South and North Delta on single circuit structures and terminating at North Delta (Transource Scope).
Cost Information
Time Estimate
May 31 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.1
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.1
Title
Peach Bottom North upgrades – substation work (Projected ISD 12/31/2028)
Description
Add 3x 500 kV breakers to form a breaker-and-a-half bay.
Cost Information
Time Estimate
Oct 15 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.14
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.14
Title
Reconfigure Cooper transmission feeds by establishing new Cooper-North Delta 230 kV line and rerouting existing transmissions lines by Cooper.
Description
None
Cost Information
Time Estimate
Oct 23 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.16
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.16
Title
Terminate new Cooper-North Delta 230 kV line (Transource Scope) at North Delta 230 kV
Description
None
Cost Information
Time Estimate
Oct 15 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.6
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.6
Title
Build Granite substation + Statcom (Projected ISD 12/31/2028)
Description
Build Granite substation + Statcom. New STATCOM rating: 350 MVAR. Add 4x 230 kV breaker bays.
Cost Information
Time Estimate
Dec 31 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.37
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.37
Title
Replace terminal equipment limitations at Conastone 500 kV - on the (existing Peach Bottom-Conastone) or (new Graceton-Conastone) 500 kV line (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.34
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.34
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new Graceton-Conastone) 500 kV and cut into North Delta 500kV (Projected ISD 12/31/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new Graceton-Conastone) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.35
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.35
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton PECO) 500 kV (Projected ISD 12/1/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton PECO) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Apr 10 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.36
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.36
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton BGE) 500 kV (Projected ISD 12/31/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton BGE) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.52
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.52
Title
Reconfigure Peach Bottom North and South 500 kV yards (Projected ISD 12/1/2030)
Description
Reconfigure Peach Bottom North and South yards to allow for termination of 500 kV lines from Peach Bottom to North Delta. North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line.
Cost Information
Time Estimate
Dec 01 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.45
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.45
Title
North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (PECO work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Jan 31 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.50
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.50
Title
North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (Transource work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Jan 23 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.46
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3800.46
Title
North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (PECO work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Dec 11 2029

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.48
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.48
Title
North Delta termination for the North Delta-High Ridge 500 line (Transource work).
Description
None
Cost Information
Time Estimate
Dec 15 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.51
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.51
Title
North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (Transource work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
May 31 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.44
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.44
Title
North Delta termination for the North Delta-High Ridge 500 line (PECO work).
Description
None
Cost Information
Time Estimate
Dec 15 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.31
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.31
Title
Build new North Delta-High Ridge 500 kV line - PECO Portion (Projected ISD 12/1/2030)
Description
None
Cost Information
Time Estimate
Dec 15 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.29
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.29
Title
High Ridge termination for the North Delta-High Ridge 500 kV line (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.27
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.27
Title
High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) - Waugh Chapel side (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.28
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.28
Title
High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) -Brighton side (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.26
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.26
Title
Build High Ridge 500 kV substation - Three bay breaker and half configuration (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.32
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.32
Title
Build new North Delta-High Ridge 500 kV line - BGE Portion (Projected ISD 12/31/2030)
Description
Build new North Delta-High Ridge 500 kV line. (~59 miles)
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.30
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.30
Title
High Ridge - Install two 500/230 kV transformers (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.47
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.47
Title
Build new Peach Bottom South-North Delta 500 kV line (Projected ISD 12/1/2030)
Description
Build new Peach Bottom South-North Delta 500 kV line – cut in to Peach Bottom tie No. 1 and extending line to North Delta (~1.25 miles new ROW).
Cost Information
Time Estimate
Jan 14 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.42
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.42
Title
Peach Bottom 500kV North bus upgrade (Projected ISD 12/1/2030)
Description
Peach Bottom 500kV North bus upgrade - Replace 11 – Instances of strain bus conductor used for breaker drops or CT drops, 7 – 500 kV disconnect switches, 7 – Free Standing CTs, 1 – 500 kV breaker, 2 – Breaker relays or meters.
Cost Information
Time Estimate
Dec 01 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.49
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.49
Title
North Delta 500 kV termination for the Calpine generator (Calpine/Transource work).
Description
None
Cost Information
Time Estimate
Oct 06 2027

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3737.47
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3737.47
Title
Build New North Delta 500 kV substation (Four bay breaker and half configuration)
Description
Build New North Delta 500 kV substation (four bay breaker and half configuration) - the substation will include 12 - 500kV breakers and one 500/230 kV transformer, will allow the termination of six - 500 kV lines
Cost Information
Time Estimate
Oct 06 2027

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.33
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.33
Title
Replace terminal equipment limitations at Brighton 500 kV - on the existing Brighton-Waugh Chapel 500 kV (5053) or new Brighton-High Ridge 500 kV.
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.2
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.2
Title
Peach Bottom to Graceton (PECO Portion) – New 500kV Line
Description
Peach Bottom to Graceton (PECO Portion) – New 500kV Line. New rating: 4503 MVA SN/ 5022 MVA SE. This is a baseline identified for the announced Brandon Shores deactivation.
Cost Information
Time Estimate
Oct 23 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.4
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.4
Title
Peach Bottom to Graceton (BGE Portion) – New 500kV Line
Description
New rating: 4503 MVA SN/ 5022 MVA SE. This is a baseline identified for the announced Brandon Shores deactivation.
Cost Information
Time Estimate
Dec 31 2028

Not ContingentTopology Changing

Note 1: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CHICHST1-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHICHST2-CHIREACT_39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
LINWOOD43-CHIREACT_43 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
POST97-LINWOOD97 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CHIREACT_39-POST39 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3867.1
Type
Load Flow
TO
AEC
RTEP ID / TO ID
b3867.1
Title
Upgrade a circuit switcher at Mickleton substation.
Description
Upgrade a circuit switcher at Mickleton substation.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
DELCOTAP-MCKLTON 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA678.0 MVA
SUMB796.0 MVA

System Reinforcement
Type
Load Flow
TO
PECO
RTEP ID / TO ID
(Pending) / New Ratings
Title
Line rating higher on PECO side: 830/925/923/1052 MVA SN/SE/WN/WE.
Description
PECO ratings for this facility, which include from the Delco Tap to the NJ state line are: 830/925/923/1052 MVA SN/SE/WN/WE. Relay and Communication upgrades may require new fiber optic installation. The cost and scope will be further evaluated during the Phase 2 Interconnection Facilities Study.
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
DELCOTAP-MCKLTON 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A830.0 MVA
(All)B925.0 MVA

System Reinforcement
Type
Load Flow
TO
PECO
RTEP ID / TO ID
(Pending)
Title
PECO Ratings: 731/885 MVA (SN/SE)
Description
PECO Ratings: 731/885 MVA (SN/SE)
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 1 Months

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
LINWOOD84-CLAY_230 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A731.0 MVA
(All)B885.0 MVA
LINWOOD85-EDGEMR 5 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A731.0 MVA
(All)B885.0 MVA

System Reinforcement: b4004.1
Type
Load Flow
TO
DPL
RTEP ID / TO ID
b4004.1
Title
Upgrade terminal equipment at Claymont substation
Description
Upgrade existing 1590 ACSR stranded bus at Claymont substation to increase the rating on the Claymont – Linwood 230 kV circuit SUM: 654/809/900 // WP: 753/911/1017 // LL: 659/809/919
Cost Information
Time Estimate
May 31 2030

Not Contingent

Note: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
LINWOOD84-CLAY_230 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA659.0 MVA
LLB809.0 MVA
LLC919.0 MVA
SUMA654.0 MVA
SUMB809.0 MVA
SUMC900.0 MVA
WINA753.0 MVA
WINB911.0 MVA
WINC1017.0 MVA

System Reinforcement
Type
Load Flow
TO
DPL
RTEP ID / TO ID
(Pending) / PE-2025-008 (Supplemental)
Title
DPL 230 kV Supplemental Upgrades
Description
Rebuild the entire 7.1 miles of the 23015 Claymont-Edgemoor 230kV line and the DPL sections of the 220-84 Claymont-Linwood 230kV line (1 mile) and 220-85 Edgemoor-Linwood 230kV line (8.1 miles). Replace breakers, disconnects, relays and bus sections at Claymont and Edgemoor substations. Note: Developer is responsible for costs if supplemental upgrades are cancelled.
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-447 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-447 could receive cost allocation. Although AG2-447 may not presently have cost responsibility for this upgrade, AG2-447 is a potential Aggregate Pool Contributor.

FacilityContingency
LINWOOD84-CLAY_230 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1098.0 MVA
LLB1195.0 MVA
SUMA1098.0 MVA
SUMB1195.0 MVA
WINA1150.0 MVA
WINB1195.0 MVA
LINWOOD85-EDGEMR 5 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1044.0 MVA
LLB1310.0 MVA
SUMA1044.0 MVA
SUMB1310.0 MVA
WINA1362.0 MVA
WINB1590.0 MVA
CLAY_230-EDGEMR 5 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1009.0 MVA
LLB1195.0 MVA
SUMA1009.0 MVA
SUMB1195.0 MVA
WINA1195.0 MVA
WINB1195.0 MVA

System Reinforcement: b3907.2
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3907.2
Title
Rebuild Richmond - Waneeta 230 kV line
Description
Richmond to Waneeta 230kV Line: Rebuild entire 0.95 miles of existing UGT, and rebuild entire 2.23 miles of existing OHT
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
WANEETA3-RICHMOND35 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1245.0 MVA
(All)B1543.0 MVA
WINA1535.0 MVA
WINB1754.0 MVA

System Reinforcement: n9787.0
Type
Load Flow
TO
PECO
RTEP ID / TO ID
n9787.0 / PECO_TC2_PH2_Chichester
Title
New bus tie at Chichester
Description
At Chichester, create a new bus tie facility through the installation of two new 230kV circuit breakers and associated disconnects /relaying on the 230kV Chichester #1 bus, splitting the bus in two. One bus will connect to the 220-43 Chichester – Linwood line, the 220-04 Chichester – Foulk line, and the #3 distribution transformer. The other bus will connect to the 220-36 Chichester – Eddystone line, the 230/138kV 9A/9B transformers, and to the existing bus tie / #2 bus. Perform bus relaying upgrades.
Total Cost ($USD)
$3,500,000
Discounted Total Cost ($USD)
$3,500,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-447 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-447 could receive cost allocation. Although AG2-447 may not presently have cost responsibility for this upgrade, AG2-447 is a potential Aggregate Pool Contributor.

FacilityContingency
(Any)PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
No new ratings for this Flowgate.
(Any)PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
No new ratings for this Flowgate.
(Any)PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
No new ratings for this Flowgate.
(Any)PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-447


AG2-447 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-447 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-447 One Line Diagram

AG2-447 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.