AG2-582 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:42

Flint Run 500 kV

2075.0 MW Capacity / 2100.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is CPV Shay, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Monongahela Power Company.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $75,064,436 $174,887,472 = 0.43 AND ( $75,064,436 - $174,887,472 ) 2100.0 = $-47,535 per MW

General

The Project Developer has proposed a Natural Gas generating facility located in the Monongahela Power Company zone — Doddridge County, West Virginia. The installed facilities will have a total capability of 2100.0 MW with 2075.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-582
Project Name:
Flint Run 500 kV
Project Developer Name:
CPV Shay, LLC
State:
West Virginia
County:
Doddridge
Transmission Owner:
Monongahela Power Company
MFO:
2100.0
MWE:
2100.0
MWC:
2075.0
Fuel Type:
Natural Gas
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG2-582 will interconnect on the Monongahela Power Company transmission system as a direct connect at the Flint Run 500 kV substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-582 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-582Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$411,978$0$0
Other Scope$983,319$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$6,576,357$6,576,357$6,576,357
System Reliability Network Upgrades
Steady State Thermal & Voltage$68,488,079$68,488,079$68,488,079
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$76,459,733$75,064,436$75,064,436

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-582

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-582
Project ID: AG2-582
20% of cost allocation for Phase II Network Upgrades:(A) $15,012,887
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $17,488,747
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $0
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Expand the existing Flint Run substation by adding one (1) new circuit breaker with SCADA controls.

$3,096,089$2,969,685$273,075$129,668$6,468,517$6,468,517
(Pending)

Review and revise relay settings at Harrison substation.

$49,550$0$4,370$0$53,920$53,920
(Pending)

Review and revise relay settings at Belmont substation.

$49,550$0$4,370$0$53,920$53,920
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install revenue metering on AG2-582 terminal at the existing Flint Run substation.

$373,763$552,554$32,966$24,036$983,319$983,319
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Integrate Interconnection Facilities protection and controls to the transmission system.

$49,550$0$4,370$0$53,920$53,920
(Pending)

Construct one span of 500kV circuit from Flint Run substation to the Point of Change in Ownership outside the substation.

$270,524$49,452$23,860$14,222$358,058$358,058
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$7,971,654$7,971,654
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take 59 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

FE performed an analysis of its underlying transmission system <100 kV system. New Service Request Project AG2-582 did not contribute to any overloads on the FE transmission <100 kV system.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. FirstEnergy interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-582 was evaluated as a 2100.0 MW (2075.0 MW Capacity) injection in the APS area.

AG2-582 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 2100.0 MW (2100.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-017_SRT-A
BreakerAC151.9 %527.0B800.53
332.01
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-017_SRT-A
BreakerAC145.31 %527.0B765.78
332.01
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-016_SRT-A
BreakerAC151.9 %527.0B800.53
332.01
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-016_SRT-A
BreakerAC145.31 %527.0B765.78
332.01

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-017_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:151.9 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:800.53
MW Contribution:
332.01
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:176.72 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:931.34
MW Contribution:
338.25
Bus #Bus NameTypeMW Contribution
23562501BACKB
Solar/Wind Helper
0.425
970935AG2-582 GEN
50/50
332.009
23751201ROTHROCK
Solar/Wind Helper
0.336
23751101LEADS_P59
Solar/Wind Helper
1.38
LAGNLTFEXP_LAGN->PJM
CLTF
1.38
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.606
TVALTFEXP_TVA->PJM
CLTF
0.674
NYPJM->LTFIMP_NY
CLTF
0.508
LGEELTFEXP_LGEE->PJM
CLTF
0.656
WECLTFEXP_WEC->PJM
CLTF
0.368
CPLELTFEXP_CPLE->PJM
CLTF
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.701
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.422
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.72
MECLTFEXP_MEC->PJM
CLTF
1.523
SIGELTFEXP_SIGE->PJM
CLTF
0.049

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-017_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.31 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:765.78
MW Contribution:
332.01
IPD Plant:AG2-582
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.59 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:883.19
MW Contribution:
338.25
IPD Plant:AG2-582
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
332.009

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-016_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:151.9 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:800.53
MW Contribution:
332.01
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:176.72 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:931.34
MW Contribution:
338.25
Bus #Bus NameTypeMW Contribution
23562501BACKB
Solar/Wind Helper
0.425
970935AG2-582 GEN
50/50
332.009
23751201ROTHROCK
Solar/Wind Helper
0.336
23751101LEADS_P59
Solar/Wind Helper
1.38
LAGNLTFEXP_LAGN->PJM
CLTF
1.38
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.606
TVALTFEXP_TVA->PJM
CLTF
0.674
NYPJM->LTFIMP_NY
CLTF
0.508
LGEELTFEXP_LGEE->PJM
CLTF
0.656
WECLTFEXP_WEC->PJM
CLTF
0.368
CPLELTFEXP_CPLE->PJM
CLTF
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.701
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.422
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.72
MECLTFEXP_MEC->PJM
CLTF
1.523
SIGELTFEXP_SIGE->PJM
CLTF
0.049

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-016_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.31 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:765.78
MW Contribution:
332.01
IPD Plant:AG2-582
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.59 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:883.19
MW Contribution:
338.25
IPD Plant:AG2-582
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
332.009
CONTINGENCY 'AP_P2-3_MP-500-017_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
CONTINGENCY 'AP_P2-3_MP-500-016_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
235235 to 235100 ckt 1
235235 to 235100 ckt 2

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BARNET-01SHINNS 138.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC113.79 %268.0B304.97
83.88
GD2AP
01BARNET-01SHINNS 138.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC112.31 %268.0B300.99
84.09
GD2AP
01BARNET-01SHINNS 138.0 kV Ckt 1 line
AP_P2-3_MP-500-018_SRT-SL
BreakerAC112.31 %268.0B300.99
84.09
GD2AP
01BARNET-01SHINNS 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT4_SRT-SL
BreakerAC112.31 %268.0B300.99
84.09
GD2AP
01BARNET-01SHINNS 138.0 kV Ckt 1 line
AP_P2-3_MP-500-017_SRT-A
BreakerAC101.14 %268.0B271.06
72.7
GD2AP
01BARNET-01SHINNS 138.0 kV Ckt 1 line
AP_P2-3_MP-500-016_SRT-A
BreakerAC101.14 %268.0B271.06
72.7
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-3_PE-500-014_SRT-SL
BreakerAC155.12 %206.0B319.54
11.59
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT19_SRT-SL
BreakerAC151.46 %206.0B312.0
11.71
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-2
SingleAC140.5 %206.0B289.42
11.59
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-1
SingleAC136.99 %206.0B282.21
11.71
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT9_SRT-SL
BusAC110.26 %206.0B227.14
11.87
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT22_SRT-SL
BreakerAC110.26 %206.0B227.13
11.87
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-3_MP-138-206_SRT-A
BreakerAC108.81 %206.0B224.14
11.91
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT11_SRT-SL
BusAC104.91 %206.0B216.12
12.02
GD2AP
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC115.81 %268.0B310.36
83.88
GD2AP
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC114.32 %268.0B306.38
84.09
GD2AP
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT4_SRT-SL
BreakerAC114.32 %268.0B306.37
84.09
GD2AP
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
AP_P2-3_MP-500-018_SRT-SL
BreakerAC114.32 %268.0B306.37
84.09
GD2AP
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
AP_P2-3_MP-500-017_SRT-A
BreakerAC103.15 %268.0B276.43
72.7
GD2AP
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
AP_P2-3_MP-500-016_SRT-A
BreakerAC103.15 %268.0B276.43
72.7
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC110.45 %527.0B582.07
192.04
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_WP-500-DRT4_SRT-SL
BreakerAC109.38 %527.0B576.43
192.28
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-018_SRT-SL
BreakerAC109.38 %527.0B576.43
192.28
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC106.51 %527.0B561.28
204.03
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC102.1 %527.0B538.05
203.78
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_WP-500-DRT4_SRT-SL
BreakerAC101.24 %527.0B533.52
204.03
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC101.24 %527.0B533.52
204.03
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-018_SRT-SL
BreakerAC101.24 %527.0B533.52
204.03
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC110.45 %527.0B582.07
192.04
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-018_SRT-SL
BreakerAC109.38 %527.0B576.43
192.28
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_WP-500-DRT4_SRT-SL
BreakerAC109.38 %527.0B576.43
192.28
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC106.51 %527.0B561.28
204.03
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC102.1 %527.0B538.05
203.78
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC101.24 %527.0B533.52
204.03
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_WP-500-DRT4_SRT-SL
BreakerAC101.24 %527.0B533.52
204.03
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-018_SRT-SL
BreakerAC101.24 %527.0B533.52
204.03
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC139.19 %3792.0B5278.17
1217.29
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC139.17 %3792.0B5277.43
1217.29
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC138.98 %3792.0B5270.18
1216.01
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC138.45 %3792.0B5250.02
1217.29
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC138.41 %3792.0B5248.4
1217.29
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-2_MP-500-007_SRT-SL
BusAC105.54 %2811.0B2966.77
1251.92
GD2AP
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC120.94 %268.0B324.11
83.88
GD2AP
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC119.45 %268.0B320.12
84.09
GD2AP
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
AP_P2-3_MP-500-018_SRT-SL
BreakerAC119.45 %268.0B320.12
84.09
GD2AP
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT4_SRT-SL
BreakerAC119.45 %268.0B320.12
84.09
GD2AP
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
AP_P2-3_MP-500-017_SRT-A
BreakerAC108.26 %268.0B290.14
72.7
GD2AP
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
AP_P2-3_MP-500-016_SRT-A
BreakerAC108.26 %268.0B290.14
72.7
GD2AP
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
AP_P2-2_MP-138-013_SRT-A
BusAC104.58 %268.0B280.28
29.58
GD2AP
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC116.78 %268.0B312.97
77.71
GD2AP
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC115.68 %268.0B310.02
77.87
GD2AP
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
AP_P2-3_MP-500-018_SRT-SL
BreakerAC115.67 %268.0B310.01
77.87
GD2AP
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT4_SRT-SL
BreakerAC115.67 %268.0B310.01
77.87
GD2AP
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
AP_P2-3_MP-500-017_SRT-A
BreakerAC105.01 %268.0B281.43
66.98
GD2AP
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
AP_P2-3_MP-500-016_SRT-A
BreakerAC105.01 %268.0B281.43
66.98
GD2AP
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT6_SRT-SL
BreakerAC104.91 %3792.0B3978.38
814.39
GD2AP
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT9_SRT-SL
BreakerAC104.68 %3792.0B3969.31
815.66
GD2AP
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
AP_P1-2_MP-500-022_SRT-A
SingleAC104.34 %3792.0B3956.52
814.39
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC130.69 %3729.0B4873.53
238.72
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.24 %3729.0B4632.89
241.83
GD2AP
01MTZION-01BERYL 138.0 kV Ckt 1 line
AP_P2-3_PE-500-014_SRT-SL
BreakerAC143.1 %206.0B294.78
11.59
GD2AP
01MTZION-01BERYL 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT19_SRT-SL
BreakerAC139.44 %206.0B287.24
11.71
GD2AP
01MTZION-01BERYL 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-2
SingleAC130.67 %206.0B269.18
11.59
GD2AP
01MTZION-01BERYL 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-1
SingleAC127.17 %206.0B261.96
11.71
GD2AP
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC112.33 %268.0B301.04
83.88
GD2AP
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC110.84 %268.0B297.06
84.09
GD2AP
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT4_SRT-SL
BreakerAC110.84 %268.0B297.06
84.09
GD2AP
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
AP_P2-3_MP-500-018_SRT-SL
BreakerAC110.84 %268.0B297.06
84.09
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC132.01 %3792.0B5005.84
238.72
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.57 %3792.0B4761.71
241.83
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
PN_P1-1_PN-230-018_SRT-A
SingleAC121.66 %128.0B155.73
6.78
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
PN_P1-1_PN-230-017_SRT-A
SingleAC121.66 %128.0B155.73
6.78
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
PN_P2-3_PN-115-84A1_SRT-A
BreakerAC104.69 %128.0B134.0
8.18
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
PN_P2-3_PN-115-84D1_SRT-A
BreakerAC104.69 %128.0B134.0
8.18
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
PN_P2-2_PN-345-1154-W_SRT-A
BusAC104.14 %128.0B133.29
7.7

Details for 01BARNET-01SHINNS 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BARNET-01SHINNS 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.79 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:304.97
MW Contribution:
83.88
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
122.446
970935AG2-582 GEN
Adder
83.882
LAGNLTFEXP_LAGN->PJM
CLTF
0.983
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.576
TVALTFEXP_TVA->PJM
CLTF
0.49
NYPJM->LTFIMP_NY
CLTF
0.302
LGEELTFEXP_LGEE->PJM
CLTF
0.44
WECLTFEXP_WEC->PJM
CLTF
0.238
CPLELTFEXP_CPLE->PJM
CLTF
0.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.335
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.869
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.942
MECLTFEXP_MEC->PJM
CLTF
1.004
SIGELTFEXP_SIGE->PJM
CLTF
0.033

Details for 01BARNET-01SHINNS 138.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BARNET-01SHINNS 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.31 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:300.99
MW Contribution:
84.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
123.297
970935AG2-582 GEN
Adder
84.094
LAGNLTFEXP_LAGN->PJM
CLTF
0.966
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.653
TVALTFEXP_TVA->PJM
CLTF
0.483
NYPJM->LTFIMP_NY
CLTF
0.307
LGEELTFEXP_LGEE->PJM
CLTF
0.423
WECLTFEXP_WEC->PJM
CLTF
0.226
CPLELTFEXP_CPLE->PJM
CLTF
0.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.905
MECLTFEXP_MEC->PJM
CLTF
0.96
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for 01BARNET-01SHINNS 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-018_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BARNET-01SHINNS 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-018_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.31 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:300.99
MW Contribution:
84.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
123.297
970935AG2-582 GEN
Adder
84.094
LAGNLTFEXP_LAGN->PJM
CLTF
0.966
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.653
TVALTFEXP_TVA->PJM
CLTF
0.483
NYPJM->LTFIMP_NY
CLTF
0.307
LGEELTFEXP_LGEE->PJM
CLTF
0.423
WECLTFEXP_WEC->PJM
CLTF
0.226
CPLELTFEXP_CPLE->PJM
CLTF
0.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.905
MECLTFEXP_MEC->PJM
CLTF
0.96
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for 01BARNET-01SHINNS 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT4_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BARNET-01SHINNS 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT4_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.31 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:300.99
MW Contribution:
84.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
123.297
970935AG2-582 GEN
Adder
84.094
LAGNLTFEXP_LAGN->PJM
CLTF
0.966
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.653
TVALTFEXP_TVA->PJM
CLTF
0.483
NYPJM->LTFIMP_NY
CLTF
0.307
LGEELTFEXP_LGEE->PJM
CLTF
0.423
WECLTFEXP_WEC->PJM
CLTF
0.226
CPLELTFEXP_CPLE->PJM
CLTF
0.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.905
MECLTFEXP_MEC->PJM
CLTF
0.96
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for 01BARNET-01SHINNS 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-017_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BARNET-01SHINNS 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.14 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:271.06
MW Contribution:
72.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
127.584
970935AG2-582 GEN
Adder
72.703
LAGNLTFEXP_LAGN->PJM
CLTF
0.893
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.607
TVALTFEXP_TVA->PJM
CLTF
0.447
NYPJM->LTFIMP_NY
CLTF
0.282
LGEELTFEXP_LGEE->PJM
CLTF
0.391
WECLTFEXP_WEC->PJM
CLTF
0.208
CPLELTFEXP_CPLE->PJM
CLTF
0.092
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.571
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.762
MECLTFEXP_MEC->PJM
CLTF
0.886
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01BARNET-01SHINNS 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-016_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BARNET-01SHINNS 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.14 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:271.06
MW Contribution:
72.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
127.584
970935AG2-582 GEN
Adder
72.703
LAGNLTFEXP_LAGN->PJM
CLTF
0.893
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.607
TVALTFEXP_TVA->PJM
CLTF
0.447
NYPJM->LTFIMP_NY
CLTF
0.282
LGEELTFEXP_LGEE->PJM
CLTF
0.391
WECLTFEXP_WEC->PJM
CLTF
0.208
CPLELTFEXP_CPLE->PJM
CLTF
0.092
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.571
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.762
MECLTFEXP_MEC->PJM
CLTF
0.886
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-3_PE-500-014_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.12 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:319.54
MW Contribution:
11.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750501ELLIOTTS
Solar/Wind Harmer
0.971
23750701CROSSCHOOL
Solar/Wind Helper
3.116
970935AG2-582 GEN
Adder
11.589
970697AG2-448 GEN
Solar/Wind Harmer
25.379
238185AF2-356 C
Solar/Wind Harmer
24.308
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
TVALTFEXP_TVA->PJM
CLTF
0.155
NYPJM->LTFIMP_NY
CLTF
0.148
LGEELTFEXP_LGEE->PJM
CLTF
0.173
WECLTFEXP_WEC->PJM
CLTF
0.1
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.664
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.649
MECLTFEXP_MEC->PJM
CLTF
0.403
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT19_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT19_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:151.46 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:312.0
MW Contribution:
11.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750501ELLIOTTS
Solar/Wind Harmer
0.973
23750701CROSSCHOOL
Solar/Wind Helper
3.116
964991AG1-363 GEN
Solar/Wind Helper
1.775
970697AG2-448 GEN
Solar/Wind Harmer
25.381
238185AF2-356 C
Solar/Wind Harmer
24.311
970935AG2-582 GEN
Adder
11.711
LAGNLTFEXP_LAGN->PJM
CLTF
0.33
TVALTFEXP_TVA->PJM
CLTF
0.161
NYPJM->LTFIMP_NY
CLTF
0.145
LGEELTFEXP_LGEE->PJM
CLTF
0.176
WECLTFEXP_WEC->PJM
CLTF
0.102
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.736
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.047
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.669
MECLTFEXP_MEC->PJM
CLTF
0.413
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.5 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:289.42
MW Contribution:
11.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
11.589
23750701CROSSCHOOL
Solar/Wind Helper
3.116
970697AG2-448 GEN
Solar/Wind Harmer
20.86
238185AF2-356 C
Solar/Wind Harmer
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
TVALTFEXP_TVA->PJM
CLTF
0.155
NYPJM->LTFIMP_NY
CLTF
0.148
LGEELTFEXP_LGEE->PJM
CLTF
0.173
WECLTFEXP_WEC->PJM
CLTF
0.1
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.664
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.649
MECLTFEXP_MEC->PJM
CLTF
0.403
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.99 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:282.21
MW Contribution:
11.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
11.711
23750701CROSSCHOOL
Solar/Wind Helper
3.116
964991AG1-363 GEN
Solar/Wind Helper
1.775
970697AG2-448 GEN
Solar/Wind Harmer
20.861
238185AF2-356 C
Solar/Wind Harmer
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.33
TVALTFEXP_TVA->PJM
CLTF
0.161
NYPJM->LTFIMP_NY
CLTF
0.145
LGEELTFEXP_LGEE->PJM
CLTF
0.176
WECLTFEXP_WEC->PJM
CLTF
0.102
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.736
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.047
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.669
MECLTFEXP_MEC->PJM
CLTF
0.413
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT9_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT9_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.26 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:227.14
MW Contribution:
11.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750501ELLIOTTS
Solar/Wind Harmer
0.95
23750701CROSSCHOOL
Solar/Wind Helper
2.995
23751201ROTHROCK
Solar/Wind Harmer
0.889
970935AG2-582 GEN
Adder
11.874
970697AG2-448 GEN
Solar/Wind Harmer
25.785
238185AF2-356 C
Solar/Wind Harmer
24.708
LAGNLTFEXP_LAGN->PJM
CLTF
0.376
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.198
TVALTFEXP_TVA->PJM
CLTF
0.186
NYPJM->LTFIMP_NY
CLTF
0.189
LGEELTFEXP_LGEE->PJM
CLTF
0.169
WECLTFEXP_WEC->PJM
CLTF
0.094
CPLELTFEXP_CPLE->PJM
CLTF
0.009
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.828
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.604
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.74
MECLTFEXP_MEC->PJM
CLTF
0.394
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT22_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT22_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.26 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:227.13
MW Contribution:
11.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970697AG2-448 GEN
Solar/Wind Harmer
25.785
238185AF2-356 C
Solar/Wind Harmer
24.708
23751201ROTHROCK
Solar/Wind Harmer
0.889
970935AG2-582 GEN
Adder
11.874
23750501ELLIOTTS
Solar/Wind Harmer
0.95
23750701CROSSCHOOL
Solar/Wind Helper
2.995
LAGNLTFEXP_LAGN->PJM
CLTF
0.376
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.198
TVALTFEXP_TVA->PJM
CLTF
0.186
NYPJM->LTFIMP_NY
CLTF
0.189
LGEELTFEXP_LGEE->PJM
CLTF
0.169
WECLTFEXP_WEC->PJM
CLTF
0.094
CPLELTFEXP_CPLE->PJM
CLTF
0.009
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.828
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.604
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.74
MECLTFEXP_MEC->PJM
CLTF
0.394
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-3_MP-138-206_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-138-206_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.81 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:224.14
MW Contribution:
11.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970697AG2-448 GEN
Solar/Wind Harmer
25.786
238185AF2-356 C
Solar/Wind Harmer
24.709
23751201ROTHROCK
Solar/Wind Harmer
0.889
970935AG2-582 GEN
Adder
11.913
23750501ELLIOTTS
Solar/Wind Harmer
0.951
23750701CROSSCHOOL
Solar/Wind Helper
2.995
LAGNLTFEXP_LAGN->PJM
CLTF
0.379
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.203
TVALTFEXP_TVA->PJM
CLTF
0.188
NYPJM->LTFIMP_NY
CLTF
0.188
LGEELTFEXP_LGEE->PJM
CLTF
0.17
WECLTFEXP_WEC->PJM
CLTF
0.095
CPLELTFEXP_CPLE->PJM
CLTF
0.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.851
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.629
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.747
MECLTFEXP_MEC->PJM
CLTF
0.397
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT11_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT11_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.91 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:216.12
MW Contribution:
12.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750501ELLIOTTS
Solar/Wind Harmer
0.952
23750701CROSSCHOOL
Solar/Wind Helper
2.994
23751201ROTHROCK
Solar/Wind Harmer
0.89
970935AG2-582 GEN
Adder
12.023
970697AG2-448 GEN
Solar/Wind Harmer
25.788
238185AF2-356 C
Solar/Wind Harmer
24.712
LAGNLTFEXP_LAGN->PJM
CLTF
0.389
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.217
TVALTFEXP_TVA->PJM
CLTF
0.193
NYPJM->LTFIMP_NY
CLTF
0.185
LGEELTFEXP_LGEE->PJM
CLTF
0.173
WECLTFEXP_WEC->PJM
CLTF
0.097
CPLELTFEXP_CPLE->PJM
CLTF
0.016
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.916
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.7
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.765
MECLTFEXP_MEC->PJM
CLTF
0.405
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BRIDGP-01BARNET 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.81 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:310.36
MW Contribution:
83.88
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
122.446
970935AG2-582 GEN
Adder
83.882
LAGNLTFEXP_LAGN->PJM
CLTF
0.983
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.576
TVALTFEXP_TVA->PJM
CLTF
0.49
NYPJM->LTFIMP_NY
CLTF
0.302
LGEELTFEXP_LGEE->PJM
CLTF
0.44
WECLTFEXP_WEC->PJM
CLTF
0.238
CPLELTFEXP_CPLE->PJM
CLTF
0.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.335
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.869
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.942
MECLTFEXP_MEC->PJM
CLTF
1.004
SIGELTFEXP_SIGE->PJM
CLTF
0.033

Details for 01BRIDGP-01BARNET 138.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.32 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:306.38
MW Contribution:
84.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
123.297
970935AG2-582 GEN
Adder
84.094
LAGNLTFEXP_LAGN->PJM
CLTF
0.966
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.653
TVALTFEXP_TVA->PJM
CLTF
0.483
NYPJM->LTFIMP_NY
CLTF
0.307
LGEELTFEXP_LGEE->PJM
CLTF
0.423
WECLTFEXP_WEC->PJM
CLTF
0.226
CPLELTFEXP_CPLE->PJM
CLTF
0.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.905
MECLTFEXP_MEC->PJM
CLTF
0.96
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for 01BRIDGP-01BARNET 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT4_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT4_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.32 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:306.37
MW Contribution:
84.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
123.297
970935AG2-582 GEN
Adder
84.094
LAGNLTFEXP_LAGN->PJM
CLTF
0.966
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.653
TVALTFEXP_TVA->PJM
CLTF
0.483
NYPJM->LTFIMP_NY
CLTF
0.307
LGEELTFEXP_LGEE->PJM
CLTF
0.423
WECLTFEXP_WEC->PJM
CLTF
0.226
CPLELTFEXP_CPLE->PJM
CLTF
0.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.905
MECLTFEXP_MEC->PJM
CLTF
0.96
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for 01BRIDGP-01BARNET 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-018_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-018_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.32 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:306.37
MW Contribution:
84.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
123.297
970935AG2-582 GEN
Adder
84.094
LAGNLTFEXP_LAGN->PJM
CLTF
0.966
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.653
TVALTFEXP_TVA->PJM
CLTF
0.483
NYPJM->LTFIMP_NY
CLTF
0.307
LGEELTFEXP_LGEE->PJM
CLTF
0.423
WECLTFEXP_WEC->PJM
CLTF
0.226
CPLELTFEXP_CPLE->PJM
CLTF
0.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.905
MECLTFEXP_MEC->PJM
CLTF
0.96
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for 01BRIDGP-01BARNET 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-017_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.15 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:276.43
MW Contribution:
72.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
127.584
970935AG2-582 GEN
Adder
72.703
LAGNLTFEXP_LAGN->PJM
CLTF
0.893
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.607
TVALTFEXP_TVA->PJM
CLTF
0.447
NYPJM->LTFIMP_NY
CLTF
0.282
LGEELTFEXP_LGEE->PJM
CLTF
0.391
WECLTFEXP_WEC->PJM
CLTF
0.208
CPLELTFEXP_CPLE->PJM
CLTF
0.092
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.571
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.762
MECLTFEXP_MEC->PJM
CLTF
0.886
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01BRIDGP-01BARNET 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-016_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.15 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:276.43
MW Contribution:
72.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
127.584
970935AG2-582 GEN
Adder
72.703
LAGNLTFEXP_LAGN->PJM
CLTF
0.893
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.607
TVALTFEXP_TVA->PJM
CLTF
0.447
NYPJM->LTFIMP_NY
CLTF
0.282
LGEELTFEXP_LGEE->PJM
CLTF
0.391
WECLTFEXP_WEC->PJM
CLTF
0.208
CPLELTFEXP_CPLE->PJM
CLTF
0.092
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.571
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.762
MECLTFEXP_MEC->PJM
CLTF
0.886
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.45 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:582.07
MW Contribution:
192.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
192.043
LAGNLTFEXP_LAGN->PJM
CLTF
1.247
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.684
TVALTFEXP_TVA->PJM
CLTF
0.617
NYPJM->LTFIMP_NY
CLTF
0.409
LGEELTFEXP_LGEE->PJM
CLTF
0.566
WECLTFEXP_WEC->PJM
CLTF
0.311
CPLELTFEXP_CPLE->PJM
CLTF
0.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.401
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.535
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.458
MECLTFEXP_MEC->PJM
CLTF
1.304
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_WP-500-DRT4_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_WP-500-DRT4_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.38 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:576.43
MW Contribution:
192.28
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
192.277
LAGNLTFEXP_LAGN->PJM
CLTF
1.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.769
TVALTFEXP_TVA->PJM
CLTF
0.61
NYPJM->LTFIMP_NY
CLTF
0.414
LGEELTFEXP_LGEE->PJM
CLTF
0.547
WECLTFEXP_WEC->PJM
CLTF
0.298
CPLELTFEXP_CPLE->PJM
CLTF
0.103
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.896
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.418
MECLTFEXP_MEC->PJM
CLTF
1.255
SIGELTFEXP_SIGE->PJM
CLTF
0.041

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-018_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-018_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.38 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:576.43
MW Contribution:
192.28
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
192.277
LAGNLTFEXP_LAGN->PJM
CLTF
1.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.769
TVALTFEXP_TVA->PJM
CLTF
0.61
NYPJM->LTFIMP_NY
CLTF
0.414
LGEELTFEXP_LGEE->PJM
CLTF
0.547
WECLTFEXP_WEC->PJM
CLTF
0.298
CPLELTFEXP_CPLE->PJM
CLTF
0.103
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.896
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.418
MECLTFEXP_MEC->PJM
CLTF
1.255
SIGELTFEXP_SIGE->PJM
CLTF
0.041

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.51 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:561.28
MW Contribution:
204.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
204.029
LAGNLTFEXP_LAGN->PJM
CLTF
1.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.769
TVALTFEXP_TVA->PJM
CLTF
0.61
NYPJM->LTFIMP_NY
CLTF
0.414
LGEELTFEXP_LGEE->PJM
CLTF
0.547
WECLTFEXP_WEC->PJM
CLTF
0.298
CPLELTFEXP_CPLE->PJM
CLTF
0.103
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.896
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.418
MECLTFEXP_MEC->PJM
CLTF
1.255
SIGELTFEXP_SIGE->PJM
CLTF
0.041

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.1 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:538.05
MW Contribution:
203.78
IPD Plant:AG2-582
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
203.78

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_WP-500-DRT4_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_WP-500-DRT4_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.24 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:533.52
MW Contribution:
204.03
IPD Plant:AG2-582
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
204.029

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.24 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:533.52
MW Contribution:
204.03
IPD Plant:AG2-582
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
204.029

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-018_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-018_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.24 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:533.52
MW Contribution:
204.03
IPD Plant:AG2-582
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
204.029

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.45 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:582.07
MW Contribution:
192.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
192.043
LAGNLTFEXP_LAGN->PJM
CLTF
1.247
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.684
TVALTFEXP_TVA->PJM
CLTF
0.617
NYPJM->LTFIMP_NY
CLTF
0.409
LGEELTFEXP_LGEE->PJM
CLTF
0.566
WECLTFEXP_WEC->PJM
CLTF
0.311
CPLELTFEXP_CPLE->PJM
CLTF
0.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.401
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.535
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.458
MECLTFEXP_MEC->PJM
CLTF
1.304
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-018_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-018_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.38 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:576.43
MW Contribution:
192.28
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
192.277
LAGNLTFEXP_LAGN->PJM
CLTF
1.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.769
TVALTFEXP_TVA->PJM
CLTF
0.61
NYPJM->LTFIMP_NY
CLTF
0.414
LGEELTFEXP_LGEE->PJM
CLTF
0.547
WECLTFEXP_WEC->PJM
CLTF
0.298
CPLELTFEXP_CPLE->PJM
CLTF
0.103
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.896
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.418
MECLTFEXP_MEC->PJM
CLTF
1.255
SIGELTFEXP_SIGE->PJM
CLTF
0.041

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_WP-500-DRT4_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_WP-500-DRT4_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.38 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:576.43
MW Contribution:
192.28
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
192.277
LAGNLTFEXP_LAGN->PJM
CLTF
1.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.769
TVALTFEXP_TVA->PJM
CLTF
0.61
NYPJM->LTFIMP_NY
CLTF
0.414
LGEELTFEXP_LGEE->PJM
CLTF
0.547
WECLTFEXP_WEC->PJM
CLTF
0.298
CPLELTFEXP_CPLE->PJM
CLTF
0.103
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.896
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.418
MECLTFEXP_MEC->PJM
CLTF
1.255
SIGELTFEXP_SIGE->PJM
CLTF
0.041

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.51 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:561.28
MW Contribution:
204.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
204.029
LAGNLTFEXP_LAGN->PJM
CLTF
1.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.769
TVALTFEXP_TVA->PJM
CLTF
0.61
NYPJM->LTFIMP_NY
CLTF
0.414
LGEELTFEXP_LGEE->PJM
CLTF
0.547
WECLTFEXP_WEC->PJM
CLTF
0.298
CPLELTFEXP_CPLE->PJM
CLTF
0.103
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.896
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.418
MECLTFEXP_MEC->PJM
CLTF
1.255
SIGELTFEXP_SIGE->PJM
CLTF
0.041

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.1 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:538.05
MW Contribution:
203.78
IPD Plant:AG2-582
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
203.78

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.24 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:533.52
MW Contribution:
204.03
IPD Plant:AG2-582
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
204.029

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_WP-500-DRT4_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_WP-500-DRT4_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.24 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:533.52
MW Contribution:
204.03
IPD Plant:AG2-582
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
204.029

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-018_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-018_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.24 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:533.52
MW Contribution:
204.03
IPD Plant:AG2-582
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
204.029

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.19 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5278.17
MW Contribution:
1217.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
940611AE2-048 GEN
Solar/Wind Harmer
22.073
941391AE2-136 GEN
Solar/Wind Harmer
11.438
270291AC1-194 GEN
Solar/Wind Harmer
5.101
270459AD2-067 GEN
Solar/Wind Harmer
8.368
961821AG1-024 GEN
Solar/Wind Harmer
8.496
270432AC2-029 GEN
Solar/Wind Harmer
6.989
270263AC1-001 GEN
Solar/Wind Harmer
1.042
241955AC1-078 GEN
Solar/Wind Harmer
7.382
945631AF1-228 GEN
Solar/Wind Harmer
4.627
971985AH1-537 GEN
Solar/Wind Harmer
17.539
253338AC1-165 GEN
Solar/Wind Harmer
1.063
253343AC1-166 GEN
Solar/Wind Harmer
1.063
241973AD2-163_GEN1
Solar/Wind Harmer
1.941
241974AD2-163_GEN2
Solar/Wind Harmer
1.941
943861AF1-054 GEN
Solar/Wind Harmer
3.769
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
2.956
241972AD1-140 GEN
Solar/Wind Harmer
4.312
253406AD2-031_GEN
Solar/Wind Harmer
1.227
253433AC1-085 GEN1
Solar/Wind Harmer
5.075
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270223U2-072_GEN1
Solar/Wind Harmer
1.87
270224U2-072_GEN2
Solar/Wind Harmer
1.87
270227U2-072_GEN3
Solar/Wind Harmer
1.87
270228U2-072_GEN4
Solar/Wind Harmer
1.87
270231U2-072_GEN5
Solar/Wind Harmer
1.87
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
7.829
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
9.262
972165AH1-665 GEN
Solar/Wind Harmer
7.409
971029AG2-637 GEN
Solar/Wind Harmer
13.858
270543AE2-219 C
Solar/Wind Harmer
9.219
247536S-71 GEN
Solar/Wind Harmer
3.723
24729505KEY G4
Adder
5.966
958711AF2-162 GEN
Solar/Wind Harmer
0.93
945581AF1-223 GEN
Solar/Wind Harmer
4.167
270356AE2-297 GEN
Solar/Wind Harmer
4.233
961761AG1-017 GEN
Solar/Wind Harmer
0.393
964611AG1-324 GEN
Solar/Wind Harmer
3.579
270071AF1-092 GEN
Solar/Wind Harmer
13.725
970289AG2-191 GEN
Solar/Wind Harmer
1.738
963791AG1-232 GEN
Solar/Wind Harmer
12.295
959331AF2-224 GEN
Solar/Wind Harmer
9.086
247521TR3_G114
Solar/Wind Harmer
3.039
270191TR4_S_V150
Solar/Wind Harmer
2.712
965051AG1-369 GEN
Solar/Wind Harmer
4.516
965041AG1-368 GEN
Solar/Wind Harmer
9.035
339216AC1-074 GEN
Solar/Wind Harmer
1.512
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
35.004
970153AG2-106 GEN
Solar/Wind Harmer
15.264
270512AE1-227 GEN2
Solar/Wind Harmer
2.247
270330AC1-082 GEN2
Solar/Wind Harmer
0.49
270329AC1-082 GEN1
Solar/Wind Harmer
0.49
971191AH1-055 GEN
Solar/Wind Harmer
19.037
957541AF2-048 GEN
Solar/Wind Harmer
1.603
970879AG2-548 GEN
Solar/Wind Harmer
8.039
961921AG1-034 GEN
Solar/Wind Harmer
12.743
960801AF2-371 GEN
Solar/Wind Harmer
2.536
964871AG1-351 GEN
Solar/Wind Harmer
1.751
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
5.566
270287AF1-227 GEN3
Solar/Wind Harmer
2.059
942051AE2-217 GEN
Solar/Wind Harmer
17.671
253325AC1-069 GEN
Solar/Wind Harmer
1.025
270518AE2-148 GEN
Solar/Wind Harmer
11.818
270367AC2-061_GEN
Solar/Wind Harmer
3.046
253394AE2-221_GEN
Solar/Wind Harmer
4.334
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
35.004
970149AG2-104 GEN
Solar/Wind Harmer
21.615
970155AG2-107 GEN
Solar/Wind Harmer
15.264
270510AE1-227 GEN1
Solar/Wind Harmer
2.647
960001AF2-291 GEN
Solar/Wind Harmer
3.156
270331AC1-082 GEN3
Solar/Wind Harmer
0.491
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
6.054
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
2.653
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
270286AF1-227 GEN2
Solar/Wind Harmer
2.059
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
1.025
253398AE2-221_GEN2
Solar/Wind Harmer
4.334
253316AC1-085 GEN3
Solar/Wind Harmer
7.996
946171AF1-282 GEN
Solar/Wind Harmer
9.551
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
9.479
270391AF1-285 GEN3
Solar/Wind Harmer
1.145
270578AF1-285 GEN2
Solar/Wind Harmer
1.145
252510AF1-249 C
Solar/Wind Harmer
0.394
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
2.993
270485AE1-090_GEN
Solar/Wind Harmer
0.565
270222AC2-111 GEN
Solar/Wind Harmer
4.163
944031AF1-071 GEN
Solar/Wind Harmer
0.937
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
17.484
942081AE2-220 GEN
Solar/Wind Harmer
5.889
270209AC1-174_GEN
Solar/Wind Harmer
3.747
270437AC2-090 C
Solar/Wind Harmer
5.139
270239V3-007_GEN1
Solar/Wind Harmer
1.584
965651AG1-433 GEN
Solar/Wind Harmer
5.023
958861AF2-177 GEN
Solar/Wind Harmer
10.045
945371AF1-202 GEN
Solar/Wind Harmer
6.41
971995AH1-542 GEN
Solar/Wind Harmer
10.104
270005AE1-210 C O1
Solar/Wind Harmer
5.017
970825AG2-519 GEN
Solar/Wind Harmer
1.925
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
12.433
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
4.289
276903AD2-071 C
Solar/Wind Harmer
9.138
965011AG1-365 GEN
Solar/Wind Harmer
9.086
24728605AND G2
Adder
3.47
339221AD2-048_GEN
Solar/Wind Harmer
1.388
965421AG1-410 GEN
Solar/Wind Harmer
27.057
24639705ELKHART HY
Adder
0.138
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
940581AE2-045 GEN
Solar/Wind Harmer
5.47
971605AH1-302 GEN
Solar/Wind Harmer
4.677
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
927014AC1-188 GEN
Solar/Wind Harmer
1.603
270349AD2-093_GEN
Solar/Wind Harmer
3.664
270471AD2-092_GEN
Solar/Wind Harmer
3.664
270054AF2-122 C O1
Solar/Wind Harmer
3.288
971073AG2-665 GEN
Solar/Wind Harmer
8.039
970879AG2-548 GEN
Solar/Wind Harmer
1.168
946101AF1-275 GEN
Solar/Wind Harmer
1.513
270269AC2-059
Solar/Wind Harmer
9.305
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253383AE2-342_GEN
Solar/Wind Harmer
0.868
942861AE2-305 GEN
Solar/Wind Harmer
7.636
253415AE1-040 GEN
Solar/Wind Harmer
1.098
962581AG1-107 GEN
Solar/Wind Harmer
4.832
961491AF2-440 GEN
Solar/Wind Harmer
2.008
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
5.747
252509AD1-136 GEN
Solar/Wind Harmer
0.243
253349AC2-067 GEN
Solar/Wind Harmer
1.925
253400AC2-068 GEN
Solar/Wind Harmer
0.774
938701AE1-092 GEN
Solar/Wind Harmer
19.541
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
253378AE2-206_GEN
Solar/Wind Harmer
3.383
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
6.502
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
9.219
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
5.623
926881AC1-175 GEN
Solar/Wind Harmer
5.139
944541AF1-119 GEN
Solar/Wind Harmer
3.848
960971AF2-388 GEN
Solar/Wind Harmer
10.047
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
4.716
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
7.466
270599AE1-208 GEN
Solar/Wind Harmer
7.466
942221AE2-234 GEN
Solar/Wind Harmer
3.201
970291AG2-192 GEN
Solar/Wind Harmer
1.189
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
3.633
24699105WLD G1 C
Solar/Wind Harmer
3.591
270246TR4_N_V150
Solar/Wind Harmer
0.769
270247TR4_N_V136
Solar/Wind Harmer
0.769
970349AG2-230 GEN
Solar/Wind Harmer
13.564
945421AF1-207 GEN
Solar/Wind Harmer
12.67
957841AF2-078 GEN
Solar/Wind Harmer
5.454
247620Y3-023
Adder
0.413
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
253317AC1-085 GEN4
Solar/Wind Harmer
7.996
946181AF1-283 GEN
Solar/Wind Harmer
12.416
270186AC1-089 GEN
Solar/Wind Harmer
5.821
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
960071AF2-298 GEN
Solar/Wind Harmer
1.437
252507AC2-088 GEN
Solar/Wind Harmer
1.699
252519AF1-045_GEN
Solar/Wind Harmer
3.45
942871AE2-306 GEN
Solar/Wind Harmer
0.859
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
252524AE2-267 GEN
Solar/Wind Harmer
1.486
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
276820AF1-078_GEN
Solar/Wind Harmer
1.503
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
7.423
958171AF2-111 GEN
Solar/Wind Harmer
23.182
24379505HDWTR1G C
Solar/Wind Harmer
7.281
270240V3-007_GEN2
Solar/Wind Harmer
5.697
944531AF1-118 GEN
Solar/Wind Harmer
32.194
270004AE1-209 GEN
Solar/Wind Harmer
5.017
946031AF1-268 GEN
Solar/Wind Harmer
7.618
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
970825AG2-519 GEN
Solar/Wind Harmer
5.167
965461AG1-414 GEN
Solar/Wind Harmer
2.074
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.058
270043AE2-236 GEN
Solar/Wind Harmer
5.008
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
4.521
339243AC2-075 GEN1
Solar/Wind Harmer
0.41
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.17 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5277.43
MW Contribution:
1217.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
940611AE2-048 GEN
Solar/Wind Harmer
22.073
941391AE2-136 GEN
Solar/Wind Harmer
11.438
270291AC1-194 GEN
Solar/Wind Harmer
5.101
270459AD2-067 GEN
Solar/Wind Harmer
8.368
961821AG1-024 GEN
Solar/Wind Harmer
8.496
270432AC2-029 GEN
Solar/Wind Harmer
6.989
270263AC1-001 GEN
Solar/Wind Harmer
1.042
241955AC1-078 GEN
Solar/Wind Harmer
7.382
945631AF1-228 GEN
Solar/Wind Harmer
4.627
971985AH1-537 GEN
Solar/Wind Harmer
17.539
253338AC1-165 GEN
Solar/Wind Harmer
1.063
253343AC1-166 GEN
Solar/Wind Harmer
1.063
241973AD2-163_GEN1
Solar/Wind Harmer
1.941
241974AD2-163_GEN2
Solar/Wind Harmer
1.941
943861AF1-054 GEN
Solar/Wind Harmer
3.769
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
2.956
241972AD1-140 GEN
Solar/Wind Harmer
4.312
253406AD2-031_GEN
Solar/Wind Harmer
1.227
253433AC1-085 GEN1
Solar/Wind Harmer
5.075
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270223U2-072_GEN1
Solar/Wind Harmer
1.87
270224U2-072_GEN2
Solar/Wind Harmer
1.87
270227U2-072_GEN3
Solar/Wind Harmer
1.87
270228U2-072_GEN4
Solar/Wind Harmer
1.87
270231U2-072_GEN5
Solar/Wind Harmer
1.87
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
7.829
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
9.262
972165AH1-665 GEN
Solar/Wind Harmer
7.409
971029AG2-637 GEN
Solar/Wind Harmer
13.858
270543AE2-219 C
Solar/Wind Harmer
9.219
247536S-71 GEN
Solar/Wind Harmer
3.723
24729505KEY G4
Adder
5.966
958711AF2-162 GEN
Solar/Wind Harmer
0.93
945581AF1-223 GEN
Solar/Wind Harmer
4.167
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
35.004
970149AG2-104 GEN
Solar/Wind Harmer
21.615
970155AG2-107 GEN
Solar/Wind Harmer
15.264
270510AE1-227 GEN1
Solar/Wind Harmer
2.647
960001AF2-291 GEN
Solar/Wind Harmer
3.156
270331AC1-082 GEN3
Solar/Wind Harmer
0.491
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
6.054
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
2.653
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
270286AF1-227 GEN2
Solar/Wind Harmer
2.059
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
1.025
253398AE2-221_GEN2
Solar/Wind Harmer
4.334
253316AC1-085 GEN3
Solar/Wind Harmer
7.996
946171AF1-282 GEN
Solar/Wind Harmer
9.551
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
9.479
270391AF1-285 GEN3
Solar/Wind Harmer
1.145
270578AF1-285 GEN2
Solar/Wind Harmer
1.145
252510AF1-249 C
Solar/Wind Harmer
0.394
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
2.993
270485AE1-090_GEN
Solar/Wind Harmer
0.565
270222AC2-111 GEN
Solar/Wind Harmer
4.163
944031AF1-071 GEN
Solar/Wind Harmer
0.937
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
17.484
942081AE2-220 GEN
Solar/Wind Harmer
5.889
270209AC1-174_GEN
Solar/Wind Harmer
3.747
270437AC2-090 C
Solar/Wind Harmer
5.139
270239V3-007_GEN1
Solar/Wind Harmer
1.584
965651AG1-433 GEN
Solar/Wind Harmer
5.023
958861AF2-177 GEN
Solar/Wind Harmer
10.045
945371AF1-202 GEN
Solar/Wind Harmer
6.41
971995AH1-542 GEN
Solar/Wind Harmer
10.104
270005AE1-210 C O1
Solar/Wind Harmer
5.017
970825AG2-519 GEN
Solar/Wind Harmer
1.925
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
12.433
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
4.289
276903AD2-071 C
Solar/Wind Harmer
9.138
965011AG1-365 GEN
Solar/Wind Harmer
9.086
24728605AND G2
Adder
3.47
339221AD2-048_GEN
Solar/Wind Harmer
1.388
965421AG1-410 GEN
Solar/Wind Harmer
27.057
24639705ELKHART HY
Adder
0.138
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
940581AE2-045 GEN
Solar/Wind Harmer
5.47
971605AH1-302 GEN
Solar/Wind Harmer
4.677
270356AE2-297 GEN
Solar/Wind Harmer
4.233
961761AG1-017 GEN
Solar/Wind Harmer
0.393
964611AG1-324 GEN
Solar/Wind Harmer
3.579
270071AF1-092 GEN
Solar/Wind Harmer
13.725
970289AG2-191 GEN
Solar/Wind Harmer
1.738
963791AG1-232 GEN
Solar/Wind Harmer
12.295
959331AF2-224 GEN
Solar/Wind Harmer
9.086
247521TR3_G114
Solar/Wind Harmer
3.039
270191TR4_S_V150
Solar/Wind Harmer
2.712
965051AG1-369 GEN
Solar/Wind Harmer
4.516
965041AG1-368 GEN
Solar/Wind Harmer
9.035
339216AC1-074 GEN
Solar/Wind Harmer
1.512
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
927014AC1-188 GEN
Solar/Wind Harmer
1.603
270349AD2-093_GEN
Solar/Wind Harmer
3.664
270471AD2-092_GEN
Solar/Wind Harmer
3.664
270054AF2-122 C O1
Solar/Wind Harmer
3.288
971073AG2-665 GEN
Solar/Wind Harmer
8.039
970879AG2-548 GEN
Solar/Wind Harmer
1.168
946101AF1-275 GEN
Solar/Wind Harmer
1.513
270269AC2-059
Solar/Wind Harmer
9.305
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253383AE2-342_GEN
Solar/Wind Harmer
0.868
942861AE2-305 GEN
Solar/Wind Harmer
7.636
253415AE1-040 GEN
Solar/Wind Harmer
1.098
962581AG1-107 GEN
Solar/Wind Harmer
4.832
961491AF2-440 GEN
Solar/Wind Harmer
2.008
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
5.747
252509AD1-136 GEN
Solar/Wind Harmer
0.243
253349AC2-067 GEN
Solar/Wind Harmer
1.925
253400AC2-068 GEN
Solar/Wind Harmer
0.774
938701AE1-092 GEN
Solar/Wind Harmer
19.541
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
253378AE2-206_GEN
Solar/Wind Harmer
3.383
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
6.502
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
9.219
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
5.623
926881AC1-175 GEN
Solar/Wind Harmer
5.139
944541AF1-119 GEN
Solar/Wind Harmer
3.848
960971AF2-388 GEN
Solar/Wind Harmer
10.047
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
4.716
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
7.466
270599AE1-208 GEN
Solar/Wind Harmer
7.466
942221AE2-234 GEN
Solar/Wind Harmer
3.201
970291AG2-192 GEN
Solar/Wind Harmer
1.189
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
3.633
24699105WLD G1 C
Solar/Wind Harmer
3.591
270246TR4_N_V150
Solar/Wind Harmer
0.769
270247TR4_N_V136
Solar/Wind Harmer
0.769
970349AG2-230 GEN
Solar/Wind Harmer
13.564
945421AF1-207 GEN
Solar/Wind Harmer
12.67
957841AF2-078 GEN
Solar/Wind Harmer
5.454
247620Y3-023
Adder
0.413
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
35.004
970153AG2-106 GEN
Solar/Wind Harmer
15.264
270512AE1-227 GEN2
Solar/Wind Harmer
2.247
270330AC1-082 GEN2
Solar/Wind Harmer
0.49
270329AC1-082 GEN1
Solar/Wind Harmer
0.49
971191AH1-055 GEN
Solar/Wind Harmer
19.037
957541AF2-048 GEN
Solar/Wind Harmer
1.603
970879AG2-548 GEN
Solar/Wind Harmer
8.039
961921AG1-034 GEN
Solar/Wind Harmer
12.743
960801AF2-371 GEN
Solar/Wind Harmer
2.536
964871AG1-351 GEN
Solar/Wind Harmer
1.751
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
5.566
270287AF1-227 GEN3
Solar/Wind Harmer
2.059
942051AE2-217 GEN
Solar/Wind Harmer
17.671
253325AC1-069 GEN
Solar/Wind Harmer
1.025
270518AE2-148 GEN
Solar/Wind Harmer
11.818
270367AC2-061_GEN
Solar/Wind Harmer
3.046
253394AE2-221_GEN
Solar/Wind Harmer
4.334
253317AC1-085 GEN4
Solar/Wind Harmer
7.996
946181AF1-283 GEN
Solar/Wind Harmer
12.416
270186AC1-089 GEN
Solar/Wind Harmer
5.821
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
960071AF2-298 GEN
Solar/Wind Harmer
1.437
252507AC2-088 GEN
Solar/Wind Harmer
1.699
252519AF1-045_GEN
Solar/Wind Harmer
3.45
942871AE2-306 GEN
Solar/Wind Harmer
0.859
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
252524AE2-267 GEN
Solar/Wind Harmer
1.486
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
276820AF1-078_GEN
Solar/Wind Harmer
1.503
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
7.423
958171AF2-111 GEN
Solar/Wind Harmer
23.182
24379505HDWTR1G C
Solar/Wind Harmer
7.281
270240V3-007_GEN2
Solar/Wind Harmer
5.697
944531AF1-118 GEN
Solar/Wind Harmer
32.194
270004AE1-209 GEN
Solar/Wind Harmer
5.017
946031AF1-268 GEN
Solar/Wind Harmer
7.618
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
970825AG2-519 GEN
Solar/Wind Harmer
5.167
965461AG1-414 GEN
Solar/Wind Harmer
2.074
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.058
270043AE2-236 GEN
Solar/Wind Harmer
5.008
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
4.521
339243AC2-075 GEN1
Solar/Wind Harmer
0.41
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.98 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5270.18
MW Contribution:
1216.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.275
23684201S70BUS2
50/50
0.318
23562301OGROV1
50/50
2.457
962761AG1-125 GEN
Solar/Wind Harmer
35.283
970149AG2-104 GEN
Solar/Wind Harmer
21.787
970155AG2-107 GEN
Solar/Wind Harmer
15.385
270510AE1-227 GEN1
Solar/Wind Harmer
2.681
960001AF2-291 GEN
Solar/Wind Harmer
3.18
270331AC1-082 GEN3
Solar/Wind Harmer
0.495
971073AG2-665 GEN
Solar/Wind Harmer
1.178
270520AE2-214 GEN
Solar/Wind Harmer
6.11
270273AD2-016 GEN
Solar/Wind Harmer
2.676
972203AH1-686 GEN
Adder
2.316
972269AH1-719 GEN
Adder
2.296
24686505CER G6
Adder
8.307
270286AF1-227 GEN2
Solar/Wind Harmer
2.078
24723205RIVRG3
Adder
18.614
253333AC1-068 GEN
Solar/Wind Harmer
1.034
253398AE2-221_GEN2
Solar/Wind Harmer
4.371
253316AC1-085 GEN3
Solar/Wind Harmer
8.063
946171AF1-282 GEN
Solar/Wind Harmer
9.631
253370AE2-315 SEC1
Adder
1.924
253371AE2-315 SEC2
Adder
1.82
25326309TAIT D
Adder
1.052
270391AF1-285 GEN3
Solar/Wind Harmer
1.157
270578AF1-285 GEN2
Solar/Wind Harmer
1.157
252516AE2-318_GEN
Solar/Wind Harmer
9.558
252510AF1-249 C
Solar/Wind Harmer
0.397
25194608D.CRK4
Adder
1.565
25196808ZIMRHP
Adder
72.004
270317AD1-130_GEN
Solar/Wind Harmer
3.023
270485AE1-090_GEN
Solar/Wind Harmer
0.571
270222AC2-111 GEN
Solar/Wind Harmer
4.198
944031AF1-071 GEN
Solar/Wind Harmer
0.945
25196008MFTGT1
Adder
1.308
945681AF1-233 GEN
Solar/Wind Harmer
17.624
942081AE2-220 GEN
Solar/Wind Harmer
5.939
270209AC1-174_GEN
Solar/Wind Harmer
3.779
270437AC2-090 C
Solar/Wind Harmer
5.183
270239V3-007_GEN1
Solar/Wind Harmer
1.598
971995AH1-542 GEN
Solar/Wind Harmer
10.211
965651AG1-433 GEN
Solar/Wind Harmer
5.067
958861AF2-177 GEN
Solar/Wind Harmer
10.133
945371AF1-202 GEN
Solar/Wind Harmer
6.466
270005AE1-210 C O1
Solar/Wind Harmer
5.06
970825AG2-519 GEN
Solar/Wind Harmer
1.941
970091AG2-072 GEN
Adder
70.821
270594AE1-207 GEN
Solar/Wind Harmer
12.54
270032AE2-172
Solar/Wind Harmer
4.294
270024AE2-089 GEN
Solar/Wind Harmer
4.327
276903AD2-071 C
Solar/Wind Harmer
9.216
965011AG1-365 GEN
Solar/Wind Harmer
9.171
24728605AND G2
Adder
3.499
339221AD2-048_GEN
Solar/Wind Harmer
1.399
965421AG1-410 GEN
Solar/Wind Harmer
27.321
246936BC-WTG1
Solar/Wind Harmer
3.559
270489AE1-102 GEN1
Solar/Wind Harmer
1.183
24639705ELKHART HY
Adder
0.139
274773LINCOLN ;4U
Adder
7.587
274774LINCOLN ;5U
Adder
7.587
274751CRETE EC ;1U
Adder
7.403
274754CRETE EC ;4U
Adder
7.403
274723RIVER EC ;12
Adder
16.092
274812UNIV PK N;8U
Adder
4.493
274802UNIV PARK;5U
Adder
5.223
274732ELWOOD EC;7P
Adder
14.692
23583801GRNGAP
Solar/Wind Helper
4.95
316095T157 G97
Solar/Wind Helper
1.324
23546401DTGZ2-030
Solar/Wind Helper
0.076
238109AE1-109 GEN2
Solar/Wind Helper
0.087
237038AE2-054 C
Solar/Wind Helper
0.229
235067AD1-061 GEN
Solar/Wind Helper
0.374
237085AD2-009_GEN
Solar/Wind Helper
1.38
237002AB1-128_GEN
Solar/Wind Helper
0.373
23777801MSM_W1-116
Solar/Wind Helper
0.098
940611AE2-048 GEN
Solar/Wind Harmer
22.313
941391AE2-136 GEN
Solar/Wind Harmer
11.562
270291AC1-194 GEN
Solar/Wind Harmer
5.145
270459AD2-067 GEN
Solar/Wind Harmer
8.448
961821AG1-024 GEN
Solar/Wind Harmer
8.577
270432AC2-029 GEN
Solar/Wind Harmer
7.05
270263AC1-001 GEN
Solar/Wind Harmer
1.051
241955AC1-078 GEN
Solar/Wind Harmer
7.45
945631AF1-228 GEN
Solar/Wind Harmer
4.669
971985AH1-537 GEN
Solar/Wind Harmer
17.679
253338AC1-165 GEN
Solar/Wind Harmer
1.072
253343AC1-166 GEN
Solar/Wind Harmer
1.072
241973AD2-163_GEN1
Solar/Wind Harmer
1.959
241974AD2-163_GEN2
Solar/Wind Harmer
1.959
943861AF1-054 GEN
Solar/Wind Harmer
3.803
943851AF1-053 GEN
Solar/Wind Harmer
1.838
270340AC2-060 GEN
Solar/Wind Harmer
2.981
241972AD1-140 GEN
Solar/Wind Harmer
4.35
253406AD2-031_GEN
Solar/Wind Harmer
1.237
253433AC1-085 GEN1
Solar/Wind Harmer
5.118
253432AC1-085 GEN2
Solar/Wind Harmer
0.258
253372AE2-315 SEC3
Adder
1.82
253372AE2-315 SEC3
Adder
1.82
25306009OHH W.
Adder
2.761
270223U2-072_GEN1
Solar/Wind Harmer
1.888
270224U2-072_GEN2
Solar/Wind Harmer
1.888
270227U2-072_GEN3
Solar/Wind Harmer
1.888
270228U2-072_GEN4
Solar/Wind Harmer
1.888
270231U2-072_GEN5
Solar/Wind Harmer
1.888
270578AF1-285 GEN2
Solar/Wind Harmer
0.445
25196408WSDLE3
Adder
8.398
25196308WSDLE2
Adder
8.325
25196208WSDLE1
Adder
8.304
25196708WSDLE6
Adder
8.283
25196508WSDLE4
Adder
8.074
270302AB2-170 GEN
Solar/Wind Harmer
7.906
25196108MFTGT2
Adder
1.442
25196108MFTGT2
Adder
1.339
972163AH1-664 GEN
Solar/Wind Harmer
9.335
972165AH1-665 GEN
Solar/Wind Harmer
7.468
971029AG2-637 GEN
Solar/Wind Harmer
13.978
270543AE2-219 C
Solar/Wind Harmer
9.298
247536S-71 GEN
Solar/Wind Harmer
3.755
24729505KEY G4
Adder
6.019
958711AF2-162 GEN
Solar/Wind Harmer
0.938
945581AF1-223 GEN
Solar/Wind Harmer
4.203
270356AE2-297 GEN
Solar/Wind Harmer
4.269
961761AG1-017 GEN
Solar/Wind Harmer
0.396
964611AG1-324 GEN
Solar/Wind Harmer
3.61
270071AF1-092 GEN
Solar/Wind Harmer
13.847
970289AG2-191 GEN
Solar/Wind Harmer
1.753
963791AG1-232 GEN
Solar/Wind Harmer
12.407
959331AF2-224 GEN
Solar/Wind Harmer
9.171
247521TR3_G114
Solar/Wind Harmer
3.068
270191TR4_S_V150
Solar/Wind Harmer
2.738
965051AG1-369 GEN
Solar/Wind Harmer
4.559
965041AG1-368 GEN
Solar/Wind Harmer
9.12
339216AC1-074 GEN
Solar/Wind Harmer
1.524
957201AF2-014 GEN
Solar/Wind Harmer
4.127
270435AC2-044 GEN
Solar/Wind Harmer
1.82
274775LINCOLN ;6U
Adder
7.587
274776LINCOLN ;7U
Adder
7.587
274777LINCOLN ;8U
Adder
7.587
972037AH1-567 GEN1
Adder
0.164
972228AH1-698 GEN2
Adder
3.318
972227AH1-698 GEN1
Adder
2.336
274827FISK ;RP
Adder
6.949
274800UNIV PARK;3U
Adder
5.222
274801UNIV PARK;4U
Adder
5.222
274687WILL CNTY;4U
Adder
24.982
274687WILL CNTY;4U
Adder
24.982
941621AE2-160 GEN
Adder
2.939
274728ELWOOD EC;5P
Adder
14.692
274731ELWOOD EC;2P
Adder
14.692
274733ELWOOD EC;3P
Adder
14.692
274735ELWOOD EC;4P
Adder
11.662
238169AE2-226 GEN1
Solar/Wind Helper
0.593
238170AE2-226 GEN2
Solar/Wind Helper
0.593
23750701CROSSCHOOL
Solar/Wind Helper
1.115
23779801AA1-109
Solar/Wind Helper
0.164
3138216PACIFIC
Solar/Wind Helper
0.037
237030AB1-096 C
Solar/Wind Helper
0.057
237025AB1-124 C
Solar/Wind Helper
0.141
970935AG2-582 GEN
50/50
1216.009
23684101S70BUS1
50/50
0.312
23534401HANNIB
50/50
0.148
24318905MLG2
50/50
4.725
927014AC1-188 GEN
Solar/Wind Harmer
1.616
270349AD2-093_GEN
Solar/Wind Harmer
3.698
270471AD2-092_GEN
Solar/Wind Harmer
3.698
270054AF2-122 C O1
Solar/Wind Harmer
3.319
971073AG2-665 GEN
Solar/Wind Harmer
8.107
970879AG2-548 GEN
Solar/Wind Harmer
1.178
946101AF1-275 GEN
Solar/Wind Harmer
1.527
270269AC2-059
Solar/Wind Harmer
9.386
253383AE2-342_GEN
Solar/Wind Harmer
0.876
24723005RIVRG1
Adder
18.614
24723105RIVRG2
Adder
18.614
942861AE2-305 GEN
Solar/Wind Harmer
7.705
253415AE1-040 GEN
Solar/Wind Harmer
1.108
962581AG1-107 GEN
Solar/Wind Harmer
4.871
961491AF2-440 GEN
Solar/Wind Harmer
2.024
972159AH1-661 GEN
Adder
0.964
25326109MON D
Adder
1.264
253370AE2-315 SEC1
Adder
1.924
25322209TAIT E
Adder
9.36
25322209TAIT E
Adder
9.149
25183208HLCRTG
Solar/Wind Harmer
5.795
252509AD1-136 GEN
Solar/Wind Harmer
0.245
938701AE1-092 GEN
Solar/Wind Harmer
19.736
253349AC2-067 GEN
Solar/Wind Harmer
1.941
253400AC2-068 GEN
Solar/Wind Harmer
0.781
25194408D.CRK1
Adder
7.198
25194508D.CRK3
Adder
1.346
253378AE2-206_GEN
Solar/Wind Harmer
3.414
25326509SID D
Adder
1.244
270462AD2-086
Solar/Wind Harmer
6.566
24728805RICHG1
Adder
3.521
24728905RICHG2
Adder
3.521
970883AG2-550 GEN
Solar/Wind Harmer
9.298
970885AG2-551 GEN
Solar/Wind Harmer
2.162
270383AD1-128 GEN
Solar/Wind Harmer
5.671
926881AC1-175 GEN
Solar/Wind Harmer
5.183
944541AF1-119 GEN
Solar/Wind Harmer
3.882
960971AF2-388 GEN
Solar/Wind Harmer
10.135
247621Y3-024
Adder
0.223
270201AC2-176 GEN
Solar/Wind Harmer
4.757
964611AG1-324 GEN
Solar/Wind Harmer
0.484
270031AE2-169
Solar/Wind Harmer
7.53
270599AE1-208 GEN
Solar/Wind Harmer
7.53
942221AE2-234 GEN
Solar/Wind Harmer
3.23
970291AG2-192 GEN
Solar/Wind Harmer
1.199
970291AG2-192 GEN
Solar/Wind Harmer
0.386
24725505WLD G2 C
Solar/Wind Harmer
3.664
24699105WLD G1 C
Solar/Wind Harmer
3.622
270246TR4_N_V150
Solar/Wind Harmer
0.776
270247TR4_N_V136
Solar/Wind Harmer
0.776
970349AG2-230 GEN
Solar/Wind Harmer
13.685
246937BC-WTG2
Solar/Wind Harmer
3.559
247620Y3-023
Adder
0.416
274770LINCOLN ;1U
Adder
7.587
274771LINCOLN ;2U
Adder
7.587
274805UNIV PK N;1U
Adder
4.503
274808UNIV PK N;4U
Adder
4.473
316097T157 G90
Solar/Wind Helper
1.324
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
237061AD1-155 GEN
Solar/Wind Helper
1.5
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.231
237080AD1-060 GEN
Solar/Wind Helper
0.287
235062AE1-101 C1
Solar/Wind Helper
1.395
237006AB1-125 GEN
Solar/Wind Helper
0.106
316411AF1-147_GEN1
Solar/Wind Helper
0.753
945421AF1-207 GEN
Solar/Wind Harmer
3.67
23559001PLEAS1
50/50
11.275
23562401OGROV2
50/50
2.436
24318805MLG1
50/50
6.371
24721905FLATG4
Adder
23.616
962771AG1-126 GEN
Solar/Wind Harmer
35.283
970153AG2-106 GEN
Solar/Wind Harmer
15.385
270512AE1-227 GEN2
Solar/Wind Harmer
2.276
270330AC1-082 GEN2
Solar/Wind Harmer
0.494
270329AC1-082 GEN1
Solar/Wind Harmer
0.494
971191AH1-055 GEN
Solar/Wind Harmer
19.185
957541AF2-048 GEN
Solar/Wind Harmer
1.616
970879AG2-548 GEN
Solar/Wind Harmer
8.107
961921AG1-034 GEN
Solar/Wind Harmer
12.865
960801AF2-371 GEN
Solar/Wind Harmer
2.559
964871AG1-351 GEN
Solar/Wind Harmer
1.767
24686405CER G5
Adder
8.242
270284AF1-227 GEN1
Solar/Wind Harmer
5.618
270287AF1-227 GEN3
Solar/Wind Harmer
2.078
942051AE2-217 GEN
Solar/Wind Harmer
17.832
253325AC1-069 GEN
Solar/Wind Harmer
1.034
270518AE2-148 GEN
Solar/Wind Harmer
11.924
270367AC2-061_GEN
Solar/Wind Harmer
3.071
253394AE2-221_GEN
Solar/Wind Harmer
4.371
253317AC1-085 GEN4
Solar/Wind Harmer
8.063
946181AF1-283 GEN
Solar/Wind Harmer
12.52
270186AC1-089 GEN
Solar/Wind Harmer
5.868
253303V4-073 C
Solar/Wind Harmer
0.111
253370AE2-315 SEC1
Adder
1.924
253371AE2-315 SEC2
Adder
1.82
960071AF2-298 GEN
Solar/Wind Harmer
1.449
252507AC2-088 GEN
Solar/Wind Harmer
1.712
942871AE2-306 GEN
Solar/Wind Harmer
0.867
270391AF1-285 GEN3
Solar/Wind Harmer
0.445
252519AF1-045_GEN
Solar/Wind Harmer
3.479
252524AE2-267 GEN
Solar/Wind Harmer
1.499
25196608WSDLE5
Adder
8.158
25194608D.CRK4
Adder
1.565
276820AF1-078_GEN
Solar/Wind Harmer
1.517
25196008MFTGT1
Adder
1.267
972167AH1-666 GEN
Solar/Wind Harmer
7.482
958171AF2-111 GEN
Solar/Wind Harmer
23.368
24379505HDWTR1G C
Solar/Wind Harmer
7.343
270240V3-007_GEN2
Solar/Wind Harmer
5.745
944531AF1-118 GEN
Solar/Wind Harmer
32.478
270004AE1-209 GEN
Solar/Wind Harmer
5.06
946031AF1-268 GEN
Solar/Wind Harmer
7.684
962031AG1-047 GEN
Solar/Wind Harmer
2.799
957741AF2-068 GEN
Solar/Wind Harmer
13.884
970825AG2-519 GEN
Solar/Wind Harmer
5.212
965461AG1-414 GEN
Solar/Wind Harmer
2.092
970289AG2-191 GEN
Solar/Wind Harmer
0.708
247642Z2-115 C
Solar/Wind Harmer
0.059
270043AE2-236 GEN
Solar/Wind Harmer
5.054
965021AG1-366 GEN
Solar/Wind Harmer
2.133
971347AH1-153 GEN
Solar/Wind Harmer
4.562
24728705AND G3
Adder
7.317
24728505AND G1
Adder
3.499
958581AF2-149 GEN
Solar/Wind Harmer
3.901
971199AH1-059 GEN
Solar/Wind Harmer
1.914
339243AC2-075 GEN1
Solar/Wind Harmer
0.413
246938BC-WTG3
Solar/Wind Harmer
3.621
270491AE1-102 GEN2
Solar/Wind Harmer
1.183
274772LINCOLN ;3U
Adder
7.587
274752CRETE EC ;2U
Adder
7.403
274753CRETE EC ;3U
Adder
7.403
274724RIVER EC ;11
Adder
15.904
274814UNIV PK N;0U
Adder
4.532
274807UNIV PK N;3U
Adder
4.522
274811UNIV PK N;7U
Adder
4.493
274803UNIV PARK;6U
Adder
5.223
274826FISK ;BP
Adder
9.806
972038AH1-567 GEN2
Adder
0.327
972259AH1-714 GEN
Adder
17.082
274729ELWOOD EC;1P
Adder
14.692
274730ELWOOD EC;6P
Adder
14.692
274734ELWOOD EC;8P
Adder
14.692
964991AG1-363 GEN
Solar/Wind Helper
4.19
238152AF2-075_GEN
Solar/Wind Helper
0.604
238175AF1-290_GEN
Solar/Wind Helper
0.131
23777901MDS_W4-102
Solar/Wind Helper
0.149
238108AE1-109 GEN1
Solar/Wind Helper
0.087
238110AE1-109 GEN3
Solar/Wind Helper
0.087
237001AB1-127_GEN
Solar/Wind Helper
0.372
235063AE1-101 C2
Solar/Wind Helper
1.395
316415AF1-147_GEN2
Solar/Wind Helper
0.753
LAGNLTFEXP_LAGN->PJM
CLTF
13.935
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.915
TVALTFEXP_TVA->PJM
CLTF
6.925
NYPJM->LTFIMP_NY
CLTF
4.427
LGEELTFEXP_LGEE->PJM
CLTF
6.165
WECLTFEXP_WEC->PJM
CLTF
3.367
AG2-052LTFEXP_AG2-052->PJM
LTF
0.21
AH1-155LTFEXP_AH1-155->PJM
LTF
0.315
CPLELTFEXP_CPLE->PJM
CLTF
1.258
CBM West 2LTFEXP_CBM-W2->PJM
CBM
103.644
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.892
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.394
MECLTFEXP_MEC->PJM
CLTF
14.194
SIGELTFEXP_SIGE->PJM
CLTF
0.459

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.45 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5250.02
MW Contribution:
1217.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.141
970879AG2-548 GEN
Solar/Wind Harmer
1.168
270269AC2-059
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
942861AE2-305 GEN
Solar/Wind Harmer
5.328
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
938701AE1-092 GEN
Solar/Wind Harmer
10.602
971655AH1-328 GEN
Solar/Wind Harmer
2.343
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
960971AF2-388 GEN
Solar/Wind Harmer
3.762
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
270599AE1-208 GEN
Solar/Wind Harmer
5.858
971613AH1-306 GEN
Solar/Wind Harmer
3.066
942221AE2-234 GEN
Solar/Wind Harmer
2.563
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.04
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
972045AH1-571 GEN
Solar/Wind Harmer
1.309
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.711
965681AG1-436 GEN
Solar/Wind Harmer
7.827
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
971587AH1-292 GEN
Solar/Wind Harmer
4.565
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
971125AH1-004 GEN
Solar/Wind Harmer
2.48
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
276776AD2-060 GEN
Solar/Wind Harmer
0.661
958011AF2-095 GEN
Solar/Wind Harmer
8.924
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
958481AF2-142 GEN
Solar/Wind Harmer
9.241
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.221
944231AF1-091 GEN
Solar/Wind Harmer
14.169
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270291AC1-194 GEN
Solar/Wind Harmer
0
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
971985AH1-537 GEN
Solar/Wind Harmer
2.039
943861AF1-054 GEN
Solar/Wind Harmer
2.63
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
253406AD2-031_GEN
Solar/Wind Harmer
0.497
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
7.194
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
270543AE2-219 C
Solar/Wind Harmer
4.502
247536S-71 GEN
Solar/Wind Harmer
0.257
24729505KEY G4
Adder
5.966
945581AF1-223 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
270071AF1-092 GEN
Solar/Wind Harmer
12.235
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
959331AF2-224 GEN
Solar/Wind Harmer
4.437
247521TR3_G114
Solar/Wind Harmer
0.229
965051AG1-369 GEN
Solar/Wind Harmer
3.151
965041AG1-368 GEN
Solar/Wind Harmer
6.303
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270526AF1-158 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
270399AC1-101 GEN
Solar/Wind Harmer
1.959
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
970179AG2-119 GEN
Solar/Wind Harmer
5.512
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.152
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.441
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
971171AH1-044 GEN
Solar/Wind Harmer
2.06
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
970879AG2-548 GEN
Solar/Wind Harmer
5.141
961921AG1-034 GEN
Solar/Wind Harmer
6.223
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.329
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252507AC2-088 GEN
Solar/Wind Harmer
0.298
252519AF1-045_GEN
Solar/Wind Harmer
3.45
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
970191AG2-125 GEN
Solar/Wind Harmer
1.699
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
958171AF2-111 GEN
Solar/Wind Harmer
16.173
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
28.761
270004AE1-209 GEN
Solar/Wind Harmer
1.388
946031AF1-268 GEN
Solar/Wind Harmer
6.094
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.076
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
3.154
971199AH1-059 GEN
Solar/Wind Harmer
1.321
24690905MDL-1G C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.226
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24695305TIMB G C
Solar/Wind Harmer
0.532
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274887GEN-1.85
Solar/Wind Harmer
0.161
276843GEN-1.7
Solar/Wind Harmer
0.2
276806AD2-047 C O1
Solar/Wind Harmer
3.512
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
970707AG2-453 GEN
Solar/Wind Harmer
20.232
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
965091AG1-374 GEN
Solar/Wind Harmer
18.362
959611AF2-252 GEN
Solar/Wind Harmer
2.04
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
959091AF2-200 GEN
Solar/Wind Harmer
2.06
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
29.52
970149AG2-104 GEN
Solar/Wind Harmer
15.941
970155AG2-107 GEN
Solar/Wind Harmer
18.85
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
7.407
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
12.198
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970825AG2-519 GEN
Solar/Wind Harmer
2.272
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.119
965011AG1-365 GEN
Solar/Wind Harmer
6.339
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.17
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.183
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.272
24639705ELKHART HY
Adder
0.138
963741AG1-226 GEN
Solar/Wind Harmer
14.786
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.244
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.566
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.617
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.588
962781AG1-127 GEN
Solar/Wind Harmer
5.837
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.41 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5248.4
MW Contribution:
1217.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.141
970879AG2-548 GEN
Solar/Wind Harmer
1.168
270269AC2-059
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
942861AE2-305 GEN
Solar/Wind Harmer
5.328
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
938701AE1-092 GEN
Solar/Wind Harmer
10.602
971655AH1-328 GEN
Solar/Wind Harmer
2.343
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
960971AF2-388 GEN
Solar/Wind Harmer
3.762
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
270599AE1-208 GEN
Solar/Wind Harmer
5.858
971613AH1-306 GEN
Solar/Wind Harmer
3.066
942221AE2-234 GEN
Solar/Wind Harmer
2.563
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.04
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
972045AH1-571 GEN
Solar/Wind Harmer
1.309
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.711
965681AG1-436 GEN
Solar/Wind Harmer
7.827
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
971587AH1-292 GEN
Solar/Wind Harmer
4.565
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
971125AH1-004 GEN
Solar/Wind Harmer
2.48
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
276776AD2-060 GEN
Solar/Wind Harmer
0.661
958011AF2-095 GEN
Solar/Wind Harmer
8.924
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
958481AF2-142 GEN
Solar/Wind Harmer
9.241
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.221
944231AF1-091 GEN
Solar/Wind Harmer
14.169
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270291AC1-194 GEN
Solar/Wind Harmer
0
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
971985AH1-537 GEN
Solar/Wind Harmer
2.039
943861AF1-054 GEN
Solar/Wind Harmer
2.63
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
253406AD2-031_GEN
Solar/Wind Harmer
0.497
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
7.194
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
270543AE2-219 C
Solar/Wind Harmer
4.502
247536S-71 GEN
Solar/Wind Harmer
0.257
24729505KEY G4
Adder
5.966
945581AF1-223 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
270071AF1-092 GEN
Solar/Wind Harmer
12.235
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
959331AF2-224 GEN
Solar/Wind Harmer
4.437
247521TR3_G114
Solar/Wind Harmer
0.229
965051AG1-369 GEN
Solar/Wind Harmer
3.151
965041AG1-368 GEN
Solar/Wind Harmer
6.303
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270526AF1-158 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
270399AC1-101 GEN
Solar/Wind Harmer
1.959
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
970179AG2-119 GEN
Solar/Wind Harmer
5.512
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.152
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.441
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
971171AH1-044 GEN
Solar/Wind Harmer
2.06
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
29.52
970149AG2-104 GEN
Solar/Wind Harmer
15.941
970155AG2-107 GEN
Solar/Wind Harmer
18.85
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
7.407
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
12.198
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970825AG2-519 GEN
Solar/Wind Harmer
2.272
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.119
965011AG1-365 GEN
Solar/Wind Harmer
6.339
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.17
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.183
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.272
24639705ELKHART HY
Adder
0.138
963741AG1-226 GEN
Solar/Wind Harmer
14.786
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.244
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.566
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.617
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.588
962781AG1-127 GEN
Solar/Wind Harmer
5.837
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
970879AG2-548 GEN
Solar/Wind Harmer
5.141
961921AG1-034 GEN
Solar/Wind Harmer
6.223
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.329
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252507AC2-088 GEN
Solar/Wind Harmer
0.298
252519AF1-045_GEN
Solar/Wind Harmer
3.45
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
970191AG2-125 GEN
Solar/Wind Harmer
1.699
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
958171AF2-111 GEN
Solar/Wind Harmer
16.173
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
28.761
270004AE1-209 GEN
Solar/Wind Harmer
1.388
946031AF1-268 GEN
Solar/Wind Harmer
6.094
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.076
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
3.154
971199AH1-059 GEN
Solar/Wind Harmer
1.321
24690905MDL-1G C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.226
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24695305TIMB G C
Solar/Wind Harmer
0.532
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274887GEN-1.85
Solar/Wind Harmer
0.161
276843GEN-1.7
Solar/Wind Harmer
0.2
276806AD2-047 C O1
Solar/Wind Harmer
3.512
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
970707AG2-453 GEN
Solar/Wind Harmer
20.232
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
965091AG1-374 GEN
Solar/Wind Harmer
18.362
959611AF2-252 GEN
Solar/Wind Harmer
2.04
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
959091AF2-200 GEN
Solar/Wind Harmer
2.06
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-2_MP-500-007_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_MP-500-007_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.54 %
Rating:2811.0 MVA
Rating Type:B
MVA to Mitigate:2966.77
MW Contribution:
1251.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
10.505
23562401OGROV2
50/50
2.229
24289405MTG1
50/50
4.056
24721905FLATG4
Adder
17.845
970935AG2-582 GEN
50/50
1251.922
23684101S70BUS1
50/50
0.286
237068AA2-119 GEN
50/50
65.899
23534401HANNIB
50/50
0.114
243186AF1-051 GEN
50/50
4.567
23559101PLEAS2
50/50
10.505
23684201S70BUS2
50/50
0.292
23562301OGROV1
50/50
2.248
24289405MTG1
50/50
4.056
243186AF1-051 GEN
50/50
4.567
LAGNLTFEXP_LAGN->PJM
CLTF
10.273
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.285
TVALTFEXP_TVA->PJM
CLTF
5.135
NYPJM->LTFIMP_NY
CLTF
3.23
LGEELTFEXP_LGEE->PJM
CLTF
4.467
WECLTFEXP_WEC->PJM
CLTF
2.389
AG2-052LTFEXP_AG2-052->PJM
LTF
0.148
AH1-155LTFEXP_AH1-155->PJM
LTF
0.223
CPLELTFEXP_CPLE->PJM
CLTF
1.24
CBM West 2LTFEXP_CBM-W2->PJM
CBM
75.423
CBM West 1LTFEXP_CBM-W1->PJM
CBM
86.953
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.21
MECLTFEXP_MEC->PJM
CLTF
10.155
SIGELTFEXP_SIGE->PJM
CLTF
0.331

Details for 01GLENFL-01BRIDGP 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.94 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:324.11
MW Contribution:
83.88
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
122.446
970935AG2-582 GEN
Adder
83.882
LAGNLTFEXP_LAGN->PJM
CLTF
0.983
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.576
TVALTFEXP_TVA->PJM
CLTF
0.49
NYPJM->LTFIMP_NY
CLTF
0.302
LGEELTFEXP_LGEE->PJM
CLTF
0.44
WECLTFEXP_WEC->PJM
CLTF
0.238
CPLELTFEXP_CPLE->PJM
CLTF
0.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.335
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.869
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.942
MECLTFEXP_MEC->PJM
CLTF
1.004
SIGELTFEXP_SIGE->PJM
CLTF
0.033

Details for 01GLENFL-01BRIDGP 138.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.45 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:320.12
MW Contribution:
84.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
123.297
970935AG2-582 GEN
Adder
84.094
LAGNLTFEXP_LAGN->PJM
CLTF
0.966
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.653
TVALTFEXP_TVA->PJM
CLTF
0.483
NYPJM->LTFIMP_NY
CLTF
0.307
LGEELTFEXP_LGEE->PJM
CLTF
0.423
WECLTFEXP_WEC->PJM
CLTF
0.226
CPLELTFEXP_CPLE->PJM
CLTF
0.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.905
MECLTFEXP_MEC->PJM
CLTF
0.96
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for 01GLENFL-01BRIDGP 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-018_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-018_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.45 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:320.12
MW Contribution:
84.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
123.297
970935AG2-582 GEN
Adder
84.094
LAGNLTFEXP_LAGN->PJM
CLTF
0.966
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.653
TVALTFEXP_TVA->PJM
CLTF
0.483
NYPJM->LTFIMP_NY
CLTF
0.307
LGEELTFEXP_LGEE->PJM
CLTF
0.423
WECLTFEXP_WEC->PJM
CLTF
0.226
CPLELTFEXP_CPLE->PJM
CLTF
0.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.905
MECLTFEXP_MEC->PJM
CLTF
0.96
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for 01GLENFL-01BRIDGP 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT4_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT4_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.45 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:320.12
MW Contribution:
84.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
123.297
970935AG2-582 GEN
Adder
84.094
LAGNLTFEXP_LAGN->PJM
CLTF
0.966
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.653
TVALTFEXP_TVA->PJM
CLTF
0.483
NYPJM->LTFIMP_NY
CLTF
0.307
LGEELTFEXP_LGEE->PJM
CLTF
0.423
WECLTFEXP_WEC->PJM
CLTF
0.226
CPLELTFEXP_CPLE->PJM
CLTF
0.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.905
MECLTFEXP_MEC->PJM
CLTF
0.96
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for 01GLENFL-01BRIDGP 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-017_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.26 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:290.14
MW Contribution:
72.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
127.584
970935AG2-582 GEN
Adder
72.703
LAGNLTFEXP_LAGN->PJM
CLTF
0.893
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.607
TVALTFEXP_TVA->PJM
CLTF
0.447
NYPJM->LTFIMP_NY
CLTF
0.282
LGEELTFEXP_LGEE->PJM
CLTF
0.391
WECLTFEXP_WEC->PJM
CLTF
0.208
CPLELTFEXP_CPLE->PJM
CLTF
0.092
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.571
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.762
MECLTFEXP_MEC->PJM
CLTF
0.886
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01GLENFL-01BRIDGP 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-016_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.26 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:290.14
MW Contribution:
72.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
127.584
970935AG2-582 GEN
Adder
72.703
LAGNLTFEXP_LAGN->PJM
CLTF
0.893
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.607
TVALTFEXP_TVA->PJM
CLTF
0.447
NYPJM->LTFIMP_NY
CLTF
0.282
LGEELTFEXP_LGEE->PJM
CLTF
0.391
WECLTFEXP_WEC->PJM
CLTF
0.208
CPLELTFEXP_CPLE->PJM
CLTF
0.092
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.571
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.762
MECLTFEXP_MEC->PJM
CLTF
0.886
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01GLENFL-01BRIDGP 138.0 kV Ckt 1 line l/o AP_P2-2_MP-138-013_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_MP-138-013_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.58 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:280.28
MW Contribution:
29.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
194.29
970935AG2-582 GEN
Adder
29.582
LAGNLTFEXP_LAGN->PJM
CLTF
0.501
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.344
TVALTFEXP_TVA->PJM
CLTF
0.251
NYPJM->LTFIMP_NY
CLTF
0.166
LGEELTFEXP_LGEE->PJM
CLTF
0.218
WECLTFEXP_WEC->PJM
CLTF
0.116
CPLELTFEXP_CPLE->PJM
CLTF
0.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.677
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.281
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.989
MECLTFEXP_MEC->PJM
CLTF
0.494
SIGELTFEXP_SIGE->PJM
CLTF
0.016

Details for 01GLENFL-01MCALPN 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.78 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:312.97
MW Contribution:
77.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
115.459
970935AG2-582 GEN
Adder
77.712
LAGNLTFEXP_LAGN->PJM
CLTF
0.893
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.584
TVALTFEXP_TVA->PJM
CLTF
0.446
NYPJM->LTFIMP_NY
CLTF
0.277
LGEELTFEXP_LGEE->PJM
CLTF
0.393
WECLTFEXP_WEC->PJM
CLTF
0.211
CPLELTFEXP_CPLE->PJM
CLTF
0.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.599
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.811
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.761
MECLTFEXP_MEC->PJM
CLTF
0.894
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01GLENFL-01MCALPN 138.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.68 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:310.02
MW Contribution:
77.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
116.092
970935AG2-582 GEN
Adder
77.87
LAGNLTFEXP_LAGN->PJM
CLTF
0.881
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.642
TVALTFEXP_TVA->PJM
CLTF
0.441
NYPJM->LTFIMP_NY
CLTF
0.281
LGEELTFEXP_LGEE->PJM
CLTF
0.38
WECLTFEXP_WEC->PJM
CLTF
0.202
CPLELTFEXP_CPLE->PJM
CLTF
0.112
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.434
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.733
MECLTFEXP_MEC->PJM
CLTF
0.861
SIGELTFEXP_SIGE->PJM
CLTF
0.028

Details for 01GLENFL-01MCALPN 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-018_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-018_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:310.01
MW Contribution:
77.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
116.092
970935AG2-582 GEN
Adder
77.87
LAGNLTFEXP_LAGN->PJM
CLTF
0.881
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.642
TVALTFEXP_TVA->PJM
CLTF
0.441
NYPJM->LTFIMP_NY
CLTF
0.281
LGEELTFEXP_LGEE->PJM
CLTF
0.38
WECLTFEXP_WEC->PJM
CLTF
0.202
CPLELTFEXP_CPLE->PJM
CLTF
0.112
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.434
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.733
MECLTFEXP_MEC->PJM
CLTF
0.861
SIGELTFEXP_SIGE->PJM
CLTF
0.028

Details for 01GLENFL-01MCALPN 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT4_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT4_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:310.01
MW Contribution:
77.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
116.092
970935AG2-582 GEN
Adder
77.87
LAGNLTFEXP_LAGN->PJM
CLTF
0.881
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.642
TVALTFEXP_TVA->PJM
CLTF
0.441
NYPJM->LTFIMP_NY
CLTF
0.281
LGEELTFEXP_LGEE->PJM
CLTF
0.38
WECLTFEXP_WEC->PJM
CLTF
0.202
CPLELTFEXP_CPLE->PJM
CLTF
0.112
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.434
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.733
MECLTFEXP_MEC->PJM
CLTF
0.861
SIGELTFEXP_SIGE->PJM
CLTF
0.028

Details for 01GLENFL-01MCALPN 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-017_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.01 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:281.43
MW Contribution:
66.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
120.191
970935AG2-582 GEN
Adder
66.978
LAGNLTFEXP_LAGN->PJM
CLTF
0.811
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.598
TVALTFEXP_TVA->PJM
CLTF
0.407
NYPJM->LTFIMP_NY
CLTF
0.257
LGEELTFEXP_LGEE->PJM
CLTF
0.349
WECLTFEXP_WEC->PJM
CLTF
0.185
CPLELTFEXP_CPLE->PJM
CLTF
0.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.916
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.762
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.596
MECLTFEXP_MEC->PJM
CLTF
0.79
SIGELTFEXP_SIGE->PJM
CLTF
0.026

Details for 01GLENFL-01MCALPN 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-016_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.01 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:281.43
MW Contribution:
66.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
120.191
970935AG2-582 GEN
Adder
66.978
LAGNLTFEXP_LAGN->PJM
CLTF
0.811
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.598
TVALTFEXP_TVA->PJM
CLTF
0.407
NYPJM->LTFIMP_NY
CLTF
0.257
LGEELTFEXP_LGEE->PJM
CLTF
0.349
WECLTFEXP_WEC->PJM
CLTF
0.185
CPLELTFEXP_CPLE->PJM
CLTF
0.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.916
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.762
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.596
MECLTFEXP_MEC->PJM
CLTF
0.79
SIGELTFEXP_SIGE->PJM
CLTF
0.026

Details for 01HARRSN-01PRNTY 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT6_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT6_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.91 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:3978.38
MW Contribution:
814.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
7.032
23684201S70BUS2
50/50
0.195
23909102SAMMG7
Adder
26.243
241859AE2-194_GEN
Solar/Wind Harmer
13.402
23583801GRNGAP
Solar/Wind Helper
6.248
316095T157 G97
Solar/Wind Helper
1.648
23751101LEADS_P59
Solar/Wind Helper
2.386
23546401DTGZ2-030
Solar/Wind Helper
0.09
238185AF2-356 C
Solar/Wind Helper
2.426
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238120AE2-309 GEN
Solar/Wind Helper
0.474
238126S14_GEN_1
Solar/Wind Helper
0.741
3141196NOKESVL
Solar/Wind Helper
0.972
237085AD2-009_GEN
Solar/Wind Helper
1.368
237038AE2-054 C
Solar/Wind Helper
0.226
235067AD1-061 GEN
Solar/Wind Helper
0.37
237002AB1-128_GEN
Solar/Wind Helper
0.366
3132273ORANGE
Solar/Wind Helper
0.045
23558701HARRN3
50/50
18.426
23558601HARRN2
50/50
18.426
970935AG2-582 GEN
50/50
814.391
23684101S70BUS1
50/50
0.191
23909002SAMMG6
Adder
26.243
23908902SAMMG5
Adder
20.994
316097T157 G90
Solar/Wind Helper
1.648
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
237061AD1-155 GEN
Solar/Wind Helper
1.799
23585401KL_K28_T16
Solar/Wind Helper
1.429
23751201ROTHROCK
Solar/Wind Helper
0.827
235054AD2-180 GEN
Solar/Wind Helper
1.916
235531U2-073 GEN
Solar/Wind Helper
2.963
238117U2-030
Solar/Wind Helper
0.306
316411AF1-147_GEN1
Solar/Wind Helper
0.818
3132123MT JACKSON
Solar/Wind Helper
0.75
316006AB2-029 C
Solar/Wind Helper
0.114
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.23
237080AD1-060 GEN
Solar/Wind Helper
0.285
316045AC1-158 PL2
Solar/Wind Helper
4.086
23558501HARRN1
50/50
18.426
23559001PLEAS1
50/50
7.032
238152AF2-075_GEN
Solar/Wind Helper
0.713
23562501BACKB
Solar/Wind Helper
1.011
238108AE1-109 GEN1
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
964991AG1-363 GEN
Solar/Wind Helper
3.939
238127S14_GEN_2
Solar/Wind Helper
0.741
238175AF1-290_GEN
Solar/Wind Helper
0.141
316415AF1-147_GEN2
Solar/Wind Helper
0.818
23777901MDS_W4-102
Solar/Wind Helper
0.149
316447AC1-158 HLD
Solar/Wind Helper
2.81
316044AC1-158 PL1
Solar/Wind Helper
1.277
235063AE1-101 C2
Solar/Wind Helper
1.369
237001AB1-127_GEN
Solar/Wind Helper
0.364
316450AC1-158 RIC
Solar/Wind Helper
0.34
235062AE1-101 C1
Solar/Wind Helper
1.369
972001AH1-545 GEN
Solar/Wind Harmer
19.9
972229AH1-699 GEN
Adder
6.968
23750701CROSSCHOOL
Solar/Wind Helper
1.321
238169AE2-226 GEN1
Solar/Wind Helper
0.655
238170AE2-226 GEN2
Solar/Wind Helper
0.655
238118U2-030_1
Solar/Wind Helper
0.306
3138216PACIFIC
Solar/Wind Helper
0.04
315651AD1-115 GEN
Solar/Wind Helper
0.779
316164AC1-076 GEN
Solar/Wind Helper
1.091
3141426STAFORD
Solar/Wind Helper
0.05
226929AD2-058 GEN
Solar/Wind Helper
0.087
LAGNLTFEXP_LAGN->PJM
CLTF
6.196
TVALTFEXP_TVA->PJM
CLTF
3.004
NYPJM->LTFIMP_NY
CLTF
2.523
LGEELTFEXP_LGEE->PJM
CLTF
3.372
WECLTFEXP_WEC->PJM
CLTF
1.937
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.856
AG2-052LTFEXP_AG2-052->PJM
LTF
0.123
AH1-155LTFEXP_AH1-155->PJM
LTF
0.185
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.788
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.074
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.571
MECLTFEXP_MEC->PJM
CLTF
7.827
SIGELTFEXP_SIGE->PJM
CLTF
0.25

Details for 01HARRSN-01PRNTY 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT9_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT9_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.68 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:3969.31
MW Contribution:
815.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
7.048
23684201S70BUS2
50/50
0.196
23909102SAMMG7
Adder
26.425
23558501HARRN1
50/50
18.441
23559001PLEAS1
50/50
7.048
238152AF2-075_GEN
Solar/Wind Helper
0.715
23562501BACKB
Solar/Wind Helper
0.978
238108AE1-109 GEN1
Solar/Wind Helper
0.101
238110AE1-109 GEN3
Solar/Wind Helper
0.101
964991AG1-363 GEN
Solar/Wind Helper
3.958
238175AF1-290_GEN
Solar/Wind Helper
0.142
238127S14_GEN_2
Solar/Wind Helper
0.725
316415AF1-147_GEN2
Solar/Wind Helper
0.822
23777901MDS_W4-102
Solar/Wind Helper
0.15
316447AC1-158 HLD
Solar/Wind Helper
2.824
316044AC1-158 PL1
Solar/Wind Helper
1.284
235063AE1-101 C2
Solar/Wind Helper
1.371
237001AB1-127_GEN
Solar/Wind Helper
0.365
3147983MERCK5
Solar/Wind Helper
0.089
23558701HARRN3
50/50
18.441
23558601HARRN2
50/50
18.441
970935AG2-582 GEN
50/50
815.661
23684101S70BUS1
50/50
0.192
23909002SAMMG6
Adder
26.425
23908902SAMMG5
Adder
21.14
316097T157 G90
Solar/Wind Helper
1.656
238147AE2-230_GEN1
Solar/Wind Helper
0.501
238148AE2-230_GEN2
Solar/Wind Helper
0.501
238149AF1-291A_GEN
Solar/Wind Helper
0.143
237061AD1-155 GEN
Solar/Wind Helper
1.806
23585401KL_K28_T16
Solar/Wind Helper
1.387
235054AD2-180 GEN
Solar/Wind Helper
1.867
23751201ROTHROCK
Solar/Wind Helper
0.799
235531U2-073 GEN
Solar/Wind Helper
2.885
238117U2-030
Solar/Wind Helper
0.297
316411AF1-147_GEN1
Solar/Wind Helper
0.822
3132123MT JACKSON
Solar/Wind Helper
0.753
316006AB2-029 C
Solar/Wind Helper
0.115
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.23
237080AD1-060 GEN
Solar/Wind Helper
0.286
316045AC1-158 PL2
Solar/Wind Helper
4.107
316450AC1-158 RIC
Solar/Wind Helper
0.342
235062AE1-101 C1
Solar/Wind Helper
1.371
241859AE2-194_GEN
Solar/Wind Harmer
13.49
23583801GRNGAP
Solar/Wind Helper
6.278
316095T157 G97
Solar/Wind Helper
1.656
23751101LEADS_P59
Solar/Wind Helper
2.329
23546401DTGZ2-030
Solar/Wind Helper
0.09
238185AF2-356 C
Solar/Wind Helper
2.372
238109AE1-109 GEN2
Solar/Wind Helper
0.101
238120AE2-309 GEN
Solar/Wind Helper
0.464
238126S14_GEN_1
Solar/Wind Helper
0.725
3141196NOKESVL
Solar/Wind Helper
0.977
237038AE2-054 C
Solar/Wind Helper
0.227
237085AD2-009_GEN
Solar/Wind Helper
1.37
235067AD1-061 GEN
Solar/Wind Helper
0.371
237002AB1-128_GEN
Solar/Wind Helper
0.367
3132273ORANGE
Solar/Wind Helper
0.045
227287AC2-120 GEN
Solar/Wind Helper
0.303
972001AH1-545 GEN
Solar/Wind Harmer
20.03
972229AH1-699 GEN
Adder
7.018
23750701CROSSCHOOL
Solar/Wind Helper
1.3
238169AE2-226 GEN1
Solar/Wind Helper
0.658
238170AE2-226 GEN2
Solar/Wind Helper
0.658
238118U2-030_1
Solar/Wind Helper
0.297
3138216PACIFIC
Solar/Wind Helper
0.041
315651AD1-115 GEN
Solar/Wind Helper
0.783
316164AC1-076 GEN
Solar/Wind Helper
1.096
3141426STAFORD
Solar/Wind Helper
0.05
226929AD2-058 GEN
Solar/Wind Helper
0.088
LAGNLTFEXP_LAGN->PJM
CLTF
6.204
TVALTFEXP_TVA->PJM
CLTF
3.008
NYPJM->LTFIMP_NY
CLTF
2.521
LGEELTFEXP_LGEE->PJM
CLTF
3.379
WECLTFEXP_WEC->PJM
CLTF
1.942
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.865
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.185
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.882
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.078
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.59
MECLTFEXP_MEC->PJM
CLTF
7.845
SIGELTFEXP_SIGE->PJM
CLTF
0.25

Details for 01HARRSN-01PRNTY 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-022_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-022_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.34 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:3956.52
MW Contribution:
814.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23558701HARRN3
50/50
18.426
23558601HARRN2
50/50
18.426
970935AG2-582 GEN
50/50
814.391
23684101S70BUS1
50/50
0.191
23909002SAMMG6
Adder
26.243
23908902SAMMG5
Adder
20.994
316097T157 G90
Solar/Wind Helper
1.648
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
237061AD1-155 GEN
Solar/Wind Helper
1.799
23585401KL_K28_T16
Solar/Wind Helper
1.429
23751201ROTHROCK
Solar/Wind Helper
0.827
235054AD2-180 GEN
Solar/Wind Helper
1.916
235531U2-073 GEN
Solar/Wind Helper
2.963
238117U2-030
Solar/Wind Helper
0.306
316411AF1-147_GEN1
Solar/Wind Helper
0.818
3132123MT JACKSON
Solar/Wind Helper
0.75
316006AB2-029 C
Solar/Wind Helper
0.114
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.23
237080AD1-060 GEN
Solar/Wind Helper
0.285
316045AC1-158 PL2
Solar/Wind Helper
4.086
316450AC1-158 RIC
Solar/Wind Helper
0.34
235062AE1-101 C1
Solar/Wind Helper
1.369
23559101PLEAS2
50/50
7.032
23684201S70BUS2
50/50
0.195
23909102SAMMG7
Adder
26.243
241859AE2-194_GEN
Solar/Wind Harmer
9.028
23583801GRNGAP
Solar/Wind Helper
6.248
316095T157 G97
Solar/Wind Helper
1.648
23751101LEADS_P59
Solar/Wind Helper
2.386
23546401DTGZ2-030
Solar/Wind Helper
0.09
238185AF2-356 C
Solar/Wind Helper
2.426
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238120AE2-309 GEN
Solar/Wind Helper
0.474
238126S14_GEN_1
Solar/Wind Helper
0.741
3141196NOKESVL
Solar/Wind Helper
0.972
237085AD2-009_GEN
Solar/Wind Helper
1.368
237038AE2-054 C
Solar/Wind Helper
0.226
235067AD1-061 GEN
Solar/Wind Helper
0.37
237002AB1-128_GEN
Solar/Wind Helper
0.366
3132273ORANGE
Solar/Wind Helper
0.045
23558501HARRN1
50/50
18.426
23559001PLEAS1
50/50
7.032
238152AF2-075_GEN
Solar/Wind Helper
0.713
23562501BACKB
Solar/Wind Helper
1.011
238108AE1-109 GEN1
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
964991AG1-363 GEN
Solar/Wind Helper
3.939
238127S14_GEN_2
Solar/Wind Helper
0.741
238175AF1-290_GEN
Solar/Wind Helper
0.141
316415AF1-147_GEN2
Solar/Wind Helper
0.818
23777901MDS_W4-102
Solar/Wind Helper
0.149
316447AC1-158 HLD
Solar/Wind Helper
2.81
316044AC1-158 PL1
Solar/Wind Helper
1.277
235063AE1-101 C2
Solar/Wind Helper
1.369
237001AB1-127_GEN
Solar/Wind Helper
0.364
972001AH1-545 GEN
Solar/Wind Harmer
2.314
972229AH1-699 GEN
Adder
6.968
23750701CROSSCHOOL
Solar/Wind Helper
1.321
238169AE2-226 GEN1
Solar/Wind Helper
0.655
238170AE2-226 GEN2
Solar/Wind Helper
0.655
238118U2-030_1
Solar/Wind Helper
0.306
3138216PACIFIC
Solar/Wind Helper
0.04
315651AD1-115 GEN
Solar/Wind Helper
0.779
316164AC1-076 GEN
Solar/Wind Helper
1.091
3141426STAFORD
Solar/Wind Helper
0.05
226929AD2-058 GEN
Solar/Wind Helper
0.087
LAGNLTFEXP_LAGN->PJM
CLTF
6.196
TVALTFEXP_TVA->PJM
CLTF
3.004
NYPJM->LTFIMP_NY
CLTF
2.523
LGEELTFEXP_LGEE->PJM
CLTF
3.372
WECLTFEXP_WEC->PJM
CLTF
1.937
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.856
AG2-052LTFEXP_AG2-052->PJM
LTF
0.123
AH1-155LTFEXP_AH1-155->PJM
LTF
0.185
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.788
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.074
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.571
MECLTFEXP_MEC->PJM
CLTF
7.827
SIGELTFEXP_SIGE->PJM
CLTF
0.25

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.69 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4873.53
MW Contribution:
238.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.05
23559101PLEAS2
50/50
5.445
270122AB2-093 CT
50/50
4.1
962761AG1-125 GEN
Solar/Wind Harmer
40.867
970149AG2-104 GEN
Solar/Wind Harmer
25.235
970155AG2-107 GEN
Solar/Wind Harmer
17.82
270286AF1-227 GEN2
Solar/Wind Harmer
2.547
270520AE2-214 GEN
Solar/Wind Harmer
7.352
270391AF1-285 GEN3
Solar/Wind Harmer
1.427
270578AF1-285 GEN2
Solar/Wind Harmer
1.427
971995AH1-542 GEN
Solar/Wind Harmer
12.942
972269AH1-719 GEN
Adder
2.693
270317AD1-130_GEN
Solar/Wind Harmer
3.738
270485AE1-090_GEN
Solar/Wind Harmer
0.706
270510AE1-227 GEN1
Solar/Wind Harmer
2.885
253333AC1-068 GEN
Solar/Wind Harmer
1.205
241813AF1-122_GEN
Solar/Wind Harmer
6.22
971201AH1-060 GEN
Solar/Wind Harmer
1.944
270273AD2-016 GEN
Solar/Wind Harmer
3.042
241847AF2-150_GEN
Solar/Wind Harmer
4.61
246936BC-WTG1
Solar/Wind Harmer
4.329
270489AE1-102 GEN1
Solar/Wind Harmer
1.439
965421AG1-410 GEN
Solar/Wind Harmer
33.164
971073AG2-665 GEN
Solar/Wind Harmer
1.284
25326309TAIT D
Adder
1.207
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
270297AD1-101 GEN
Solar/Wind Harmer
2.226
965011AG1-365 GEN
Solar/Wind Harmer
10.939
270258AD1-119 GEN
Solar/Wind Harmer
2.219
253398AE2-221_GEN2
Solar/Wind Harmer
4.932
253316AC1-085 GEN3
Solar/Wind Harmer
9.041
946171AF1-282 GEN
Solar/Wind Harmer
10.799
965651AG1-433 GEN
Solar/Wind Harmer
5.866
270024AE2-089 GEN
Solar/Wind Harmer
5.027
958861AF2-177 GEN
Solar/Wind Harmer
11.712
960001AF2-291 GEN
Solar/Wind Harmer
3.236
24639705ELKHART HY
Adder
0.164
945371AF1-202 GEN
Solar/Wind Harmer
7.453
270216AD2-079_GEN
Solar/Wind Harmer
0.645
945111AF1-176 GEN
Solar/Wind Harmer
19.021
957891AF2-083 GEN
Solar/Wind Harmer
15.982
252516AE2-318_GEN
Solar/Wind Harmer
10.65
270449AD2-020 GEN
Solar/Wind Harmer
2.984
943021AE2-325 GEN
Solar/Wind Harmer
3.878
270222AC2-111 GEN
Solar/Wind Harmer
4.753
944031AF1-071 GEN
Solar/Wind Harmer
1.069
24441205WTRV SLR C
Solar/Wind Harmer
0.143
252510AF1-249 C
Solar/Wind Harmer
0.443
25194608D.CRK4
Adder
1.747
25196808ZIMRHP
Adder
79.955
23906502RICHG2&3
Adder
1.268
25196008MFTGT1
Adder
1.455
274751CRETE EC ;1U
Adder
8.571
274754CRETE EC ;4U
Adder
8.571
274723RIVER EC ;12
Adder
18.619
274773LINCOLN ;4U
Adder
8.764
274774LINCOLN ;5U
Adder
8.764
274812UNIV PK N;8U
Adder
5.194
274802UNIV PARK;5U
Adder
6.031
23920202STRYCT
Adder
1.44
274676JOLIET 29;8U
Adder
31.606
274732ELWOOD EC;7P
Adder
16.929
274674JOLIET 9 ;6U
Adder
15.855
23583801GRNGAP
Solar/Wind Helper
6.383
316095T157 G97
Solar/Wind Helper
1.71
972239AH1-704 GEN
50/50
3.095
270459AD2-067 GEN
Solar/Wind Harmer
10.428
961821AG1-024 GEN
Solar/Wind Harmer
10.588
241955AC1-078 GEN
Solar/Wind Harmer
8.918
241973AD2-163_GEN1
Solar/Wind Harmer
2.358
241974AD2-163_GEN2
Solar/Wind Harmer
2.358
940611AE2-048 GEN
Solar/Wind Harmer
26.008
941391AE2-136 GEN
Solar/Wind Harmer
13.477
270223U2-072_GEN1
Solar/Wind Harmer
2.33
270224U2-072_GEN2
Solar/Wind Harmer
2.33
270227U2-072_GEN3
Solar/Wind Harmer
2.33
270228U2-072_GEN4
Solar/Wind Harmer
2.33
270231U2-072_GEN5
Solar/Wind Harmer
2.33
270578AF1-285 GEN2
Solar/Wind Harmer
0.549
943861AF1-054 GEN
Solar/Wind Harmer
4.542
943851AF1-053 GEN
Solar/Wind Harmer
2.195
945631AF1-228 GEN
Solar/Wind Harmer
5.525
270302AB2-170 GEN
Solar/Wind Harmer
9.776
270432AC2-029 GEN
Solar/Wind Harmer
8.117
970179AG2-119 GEN
Solar/Wind Harmer
9.237
253338AC1-165 GEN
Solar/Wind Harmer
1.249
253343AC1-166 GEN
Solar/Wind Harmer
1.249
241972AD1-140 GEN
Solar/Wind Harmer
5.07
270263AC1-001 GEN
Solar/Wind Harmer
1.18
971567AH1-282 GEN
Solar/Wind Harmer
5.635
270377AD1-106 GEN
Solar/Wind Harmer
5.917
966831AG1-554 GEN
Solar/Wind Harmer
1.337
270291AC1-194 GEN
Solar/Wind Harmer
5.669
270340AC2-060 GEN
Solar/Wind Harmer
3.354
957201AF2-014 GEN
Solar/Wind Harmer
5.019
270435AC2-044 GEN
Solar/Wind Harmer
2.213
270007AE1-245 C
Solar/Wind Harmer
5.939
253372AE2-315 SEC3
Adder
2.081
253372AE2-315 SEC3
Adder
2.081
247521TR3_G114
Solar/Wind Harmer
3.687
270191TR4_S_V150
Solar/Wind Harmer
3.29
965051AG1-369 GEN
Solar/Wind Harmer
5.479
25306009OHH W.
Adder
3.158
965041AG1-368 GEN
Solar/Wind Harmer
10.944
959331AF2-224 GEN
Solar/Wind Harmer
10.939
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.18
963791AG1-232 GEN
Solar/Wind Harmer
14.614
253433AC1-085 GEN1
Solar/Wind Harmer
5.738
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
270071AF1-092 GEN
Solar/Wind Harmer
16.191
24729505KEY G4
Adder
6.997
945641AF1-229 GEN
Solar/Wind Harmer
3.912
970031AG2-029 GEN
Solar/Wind Harmer
26.913
958711AF2-162 GEN
Solar/Wind Harmer
1.086
945581AF1-223 GEN
Solar/Wind Harmer
4.845
971029AG2-637 GEN
Solar/Wind Harmer
16.005
270499AE1-146 GEN
Solar/Wind Harmer
2.679
270543AE2-219 C
Solar/Wind Harmer
10.668
247536S-71 GEN
Solar/Wind Harmer
4.316
961761AG1-017 GEN
Solar/Wind Harmer
0.456
964611AG1-324 GEN
Solar/Wind Harmer
4.154
971771AH1-392 GEN
Solar/Wind Harmer
9.58
944161AF1-084 GEN
Solar/Wind Harmer
2.352
25196408WSDLE3
Adder
9.385
25196308WSDLE2
Adder
9.303
25196208WSDLE1
Adder
9.28
25196708WSDLE6
Adder
9.256
25196508WSDLE4
Adder
9.023
25196108MFTGT2
Adder
1.604
25196108MFTGT2
Adder
1.489
274775LINCOLN ;6U
Adder
8.764
274776LINCOLN ;7U
Adder
8.764
274777LINCOLN ;8U
Adder
8.764
972037AH1-567 GEN1
Adder
0.189
274827FISK ;RP
Adder
8.022
274800UNIV PARK;3U
Adder
6.026
274801UNIV PARK;4U
Adder
6.026
972228AH1-698 GEN2
Adder
3.828
972227AH1-698 GEN1
Adder
2.695
274687WILL CNTY;4U
Adder
28.802
274687WILL CNTY;4U
Adder
28.802
274675JOLIET 29;7U
Adder
31.606
274675JOLIET 29;7U
Adder
30.477
274728ELWOOD EC;5P
Adder
16.929
274731ELWOOD EC;2P
Adder
16.929
274733ELWOOD EC;3P
Adder
16.929
270119AB2-067 GEN1
50/50
7.05
270120AB2-067 GEN2
50/50
7.05
24318905MLG2
50/50
7.451
270054AF2-122 C O1
Solar/Wind Harmer
4.054
270349AD2-093_GEN
Solar/Wind Harmer
4.513
270471AD2-092_GEN
Solar/Wind Harmer
4.513
946101AF1-275 GEN
Solar/Wind Harmer
1.838
253383AE2-342_GEN
Solar/Wind Harmer
1.057
938701AE1-092 GEN
Solar/Wind Harmer
24.428
942861AE2-305 GEN
Solar/Wind Harmer
9.201
270462AD2-086
Solar/Wind Harmer
8.12
972159AH1-661 GEN
Adder
1.163
241960AC2-195 GEN
Solar/Wind Harmer
3.204
270269AC2-059
Solar/Wind Harmer
10.672
253378AE2-206_GEN
Solar/Wind Harmer
4.074
25326509SID D
Adder
1.478
253415AE1-040 GEN
Solar/Wind Harmer
1.252
25326109MON D
Adder
1.457
246937BC-WTG2
Solar/Wind Harmer
4.329
971073AG2-665 GEN
Solar/Wind Harmer
8.835
970879AG2-548 GEN
Solar/Wind Harmer
1.284
25322209TAIT E
Adder
10.744
25322209TAIT E
Adder
10.502
942801AE2-298 GEN
Solar/Wind Harmer
1.666
247607V1-011 GEN
Solar/Wind Harmer
4.348
253370AE2-315 SEC1
Adder
2.2
270246TR4_N_V150
Solar/Wind Harmer
0.933
270247TR4_N_V136
Solar/Wind Harmer
0.933
247522W1-056 GEN
Solar/Wind Harmer
2.469
253349AC2-067 GEN
Solar/Wind Harmer
2.225
253400AC2-068 GEN
Solar/Wind Harmer
0.895
927014AC1-188 GEN
Solar/Wind Harmer
1.72
944231AF1-091 GEN
Solar/Wind Harmer
19.433
942221AE2-234 GEN
Solar/Wind Harmer
3.759
944541AF1-119 GEN
Solar/Wind Harmer
4.494
960971AF2-388 GEN
Solar/Wind Harmer
11.731
247620Y3-023
Adder
0.492
970349AG2-230 GEN
Solar/Wind Harmer
16.027
247621Y3-024
Adder
0.257
25183208HLCRTG
Solar/Wind Harmer
6.454
970883AG2-550 GEN
Solar/Wind Harmer
10.668
970885AG2-551 GEN
Solar/Wind Harmer
2.481
962581AG1-107 GEN
Solar/Wind Harmer
5.371
961491AF2-440 GEN
Solar/Wind Harmer
2.232
270201AC2-176 GEN
Solar/Wind Harmer
5.48
961051AF2-396 GEN
Solar/Wind Harmer
16.91
961051AF2-396 GEN
Solar/Wind Harmer
7.865
964611AG1-324 GEN
Solar/Wind Harmer
0.557
270031AE2-169
Solar/Wind Harmer
8.665
270599AE1-208 GEN
Solar/Wind Harmer
8.665
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.503
24728805RICHG1
Adder
3.989
24728905RICHG2
Adder
3.989
970935AG2-582 GEN
Adder
238.716
274770LINCOLN ;1U
Adder
8.764
274771LINCOLN ;2U
Adder
8.764
274805UNIV PK N;1U
Adder
5.205
274808UNIV PK N;4U
Adder
5.171
274674JOLIET 9 ;6U
Adder
0.246
316097T157 G90
Solar/Wind Helper
1.71
238147AE2-230_GEN1
Solar/Wind Helper
0.556
238148AE2-230_GEN2
Solar/Wind Helper
0.556
238149AF1-291A_GEN
Solar/Wind Helper
0.159
237061AD1-155 GEN
Solar/Wind Helper
1.974
235054AD2-180 GEN
Solar/Wind Helper
2.118
235531U2-073 GEN
Solar/Wind Helper
3.481
23585401KL_K28_T16
Solar/Wind Helper
1.534
235020AA1-095 C
Solar/Wind Helper
0.058
238117U2-030
Solar/Wind Helper
0.357
238221AF1-254 C O1
Solar/Wind Helper
0.297
237080AD1-060 GEN
Solar/Wind Helper
0.369
235062AE1-101 C1
Solar/Wind Helper
1.786
316411AF1-147_GEN1
Solar/Wind Helper
0.984
23751201ROTHROCK
Solar/Wind Helper
0.821
237006AB1-125 GEN
Solar/Wind Helper
0.132
316006AB2-029 C
Solar/Wind Helper
0.131
223401AF1-299 GEN
Solar/Wind Helper
0.389
223402AF1-300 C
Solar/Wind Helper
0.389
316045AC1-158 PL2
Solar/Wind Helper
4.643
316450AC1-158 RIC
Solar/Wind Helper
0.387
3132123MT JACKSON
Solar/Wind Helper
0.767
233930AB2-032 GEN
Solar/Wind Helper
0.389
233982AB2-133 GEN
Solar/Wind Helper
0.367
232424Y1-079 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.581
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.982
24318805MLG1
50/50
10
23559001PLEAS1
50/50
5.445
270051AF1-062 GEN
50/50
11.971
962771AG1-126 GEN
Solar/Wind Harmer
40.867
970153AG2-106 GEN
Solar/Wind Harmer
17.82
961921AG1-034 GEN
Solar/Wind Harmer
15.881
270284AF1-227 GEN1
Solar/Wind Harmer
6.884
270287AF1-227 GEN3
Solar/Wind Harmer
2.547
942051AE2-217 GEN
Solar/Wind Harmer
21.323
942871AE2-306 GEN
Solar/Wind Harmer
1.07
270391AF1-285 GEN3
Solar/Wind Harmer
0.549
960801AF2-371 GEN
Solar/Wind Harmer
2.983
964871AG1-351 GEN
Solar/Wind Harmer
2.06
270512AE1-227 GEN2
Solar/Wind Harmer
2.449
270518AE2-148 GEN
Solar/Wind Harmer
13.997
958581AF2-149 GEN
Solar/Wind Harmer
4.955
971199AH1-059 GEN
Solar/Wind Harmer
2.432
24721905FLATG4
Adder
23.444
253325AC1-069 GEN
Solar/Wind Harmer
1.205
970065AG2-057 GEN
Solar/Wind Harmer
0.972
276820AF1-078_GEN
Solar/Wind Harmer
1.81
270588AE1-091_GEN
Solar/Wind Harmer
12.281
961961AG1-039 GEN
Solar/Wind Harmer
3.18
246938BC-WTG3
Solar/Wind Harmer
4.404
270491AE1-102 GEN2
Solar/Wind Harmer
1.439
970879AG2-548 GEN
Solar/Wind Harmer
8.835
958091AF2-103 GEN
Solar/Wind Harmer
0.178
960071AF2-298 GEN
Solar/Wind Harmer
1.664
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
24695305TIMB G C
Solar/Wind Harmer
3.661
965021AG1-366 GEN
Solar/Wind Harmer
2.544
270044AE2-322 C
Solar/Wind Harmer
1.431
253394AE2-221_GEN
Solar/Wind Harmer
4.932
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270043AE2-236 GEN
Solar/Wind Harmer
5.961
944531AF1-118 GEN
Solar/Wind Harmer
37.819
253317AC1-085 GEN4
Solar/Wind Harmer
9.041
946181AF1-283 GEN
Solar/Wind Harmer
14.038
270063AE2-323 C
Solar/Wind Harmer
2.363
270541AE2-072 C
Solar/Wind Harmer
4.86
971191AH1-055 GEN
Solar/Wind Harmer
20.005
971347AH1-153 GEN
Solar/Wind Harmer
5.342
247643Z2-116 C
Solar/Wind Harmer
0.074
962031AG1-047 GEN
Solar/Wind Harmer
3.224
957741AF2-068 GEN
Solar/Wind Harmer
15.993
945111AF1-176 GEN
Solar/Wind Harmer
6.028
270505AE1-170 C O1
Solar/Wind Harmer
15.984
252519AF1-045_GEN
Solar/Wind Harmer
3.876
252524AE2-267 GEN
Solar/Wind Harmer
1.675
25196608WSDLE5
Adder
9.116
25194608D.CRK4
Adder
1.747
270367AC2-061_GEN
Solar/Wind Harmer
3.375
23906502RICHG2&3
Adder
1.268
23906402RICHG1
Adder
1.268
25196008MFTGT1
Adder
1.409
274752CRETE EC ;2U
Adder
8.571
274753CRETE EC ;3U
Adder
8.571
274724RIVER EC ;11
Adder
18.401
274772LINCOLN ;3U
Adder
8.764
274814UNIV PK N;0U
Adder
5.24
274807UNIV PK N;3U
Adder
5.228
274811UNIV PK N;7U
Adder
5.194
274803UNIV PARK;6U
Adder
6.031
274826FISK ;BP
Adder
11.319
274735ELWOOD EC;4P
Adder
16.929
23750701CROSSCHOOL
Solar/Wind Helper
1.591
238169AE2-226 GEN1
Solar/Wind Helper
0.777
238170AE2-226 GEN2
Solar/Wind Helper
0.777
238118U2-030_1
Solar/Wind Helper
0.357
3138216PACIFIC
Solar/Wind Helper
0.049
23779801AA1-109
Solar/Wind Helper
0.208
237030AB1-096 C
Solar/Wind Helper
0.071
237025AB1-124 C
Solar/Wind Helper
0.176
226929AD2-058 GEN
Solar/Wind Helper
0.108
3141426STAFORD
Solar/Wind Helper
0.058
315651AD1-115 GEN
Solar/Wind Helper
0.883
316164AC1-076 GEN
Solar/Wind Helper
1.232
23750501ELLIOTTS
Solar/Wind Helper
0.631
205917AD1-020 ES
Solar/Wind Helper
0.381
959381AF2-229 GEN
Solar/Wind Helper
0.368
20390526W1-045 C
Solar/Wind Helper
0.361
205943AE1-185 GEN
Solar/Wind Helper
0.521
205956AE1-196_GEN
Solar/Wind Helper
0.521
233915AB1-141 GEN
Solar/Wind Helper
0.514
233901CHERRYDALE C
Solar/Wind Helper
0.238
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
230434AG1-499 GEN
Solar/Wind Helper
0.234
228728W1-130C
Solar/Wind Helper
0.055
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.192
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.084
20675128HRM_W1-127
Solar/Wind Helper
0.03
972038AH1-567 GEN2
Adder
0.377
972259AH1-714 GEN
Adder
19.698
274676JOLIET 29;8U
Adder
30.477
274729ELWOOD EC;1P
Adder
16.929
274730ELWOOD EC;6P
Adder
16.929
274734ELWOOD EC;8P
Adder
16.929
274736ELWOOD EC;9P
Adder
16.929
964991AG1-363 GEN
Solar/Wind Helper
5.569
238108AE1-109 GEN1
Solar/Wind Helper
0.122
238110AE1-109 GEN3
Solar/Wind Helper
0.122
238152AF2-075_GEN
Solar/Wind Helper
0.794
238175AF1-290_GEN
Solar/Wind Helper
0.173
238127S14_GEN_2
Solar/Wind Helper
0.87
23777901MDS_W4-102
Solar/Wind Helper
0.192
235063AE1-101 C2
Solar/Wind Helper
1.786
237001AB1-127_GEN
Solar/Wind Helper
0.476
316415AF1-147_GEN2
Solar/Wind Helper
0.984
23562501BACKB
Solar/Wind Helper
1
316447AC1-158 HLD
Solar/Wind Helper
3.193
316044AC1-158 PL1
Solar/Wind Helper
1.451
237048AF1-022 C
Solar/Wind Helper
0.18
205916AD1-020 GEN
Solar/Wind Helper
1.77
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.521
233918AB1-142 GEN
Solar/Wind Helper
0.514
233944AB2-135 GEN
Solar/Wind Helper
0.603
232426Y1-080 FULL
Solar/Wind Helper
0.04
3147666LOUISA
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.21
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.518
232408W1-005 C
Solar/Wind Helper
0.518
316192AB2-158 GEN
Solar/Wind Helper
1.618
228729W2-030 C
Solar/Wind Helper
0.112
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.543
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.066
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674628WNG_W3-110
Solar/Wind Helper
0.09
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674928WA_W3-044
Solar/Wind Helper
0.099
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.573
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.151
232410W1-006 C
Solar/Wind Helper
0.518
232428Y3-058 C
Solar/Wind Helper
0.346
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.238
233954AC2-188 GEN
Solar/Wind Helper
0.238
966001AG1-469 GEN
Solar/Wind Helper
0.256
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.152
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.293
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
238109AE1-109 GEN2
Solar/Wind Helper
0.122
238185AF2-356 C
Solar/Wind Helper
2.787
23546401DTGZ2-030
Solar/Wind Helper
0.1
238120AE2-309 GEN
Solar/Wind Helper
0.557
238126S14_GEN_1
Solar/Wind Helper
0.87
237038AE2-054 C
Solar/Wind Helper
0.294
235067AD1-061 GEN
Solar/Wind Helper
0.481
237085AD2-009_GEN
Solar/Wind Helper
1.776
237002AB1-128_GEN
Solar/Wind Helper
0.477
3141196NOKESVL
Solar/Wind Helper
1.144
23777801MSM_W1-116
Solar/Wind Helper
0.123
226910AB2-157 C
Solar/Wind Helper
0.016
227287AC2-120 GEN
Solar/Wind Helper
0.377
23751101LEADS_P59
Solar/Wind Helper
1.984
3132273ORANGE
Solar/Wind Helper
0.049
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.297
233987AB2-037 GEN
Solar/Wind Helper
2.395
233933AB2-153 GEN
Solar/Wind Helper
0.238
232422X3-066 FULL
Solar/Wind Helper
0.117
232417X3-008 C
Solar/Wind Helper
0.238
233964AF2-378 GEN
Solar/Wind Helper
0.043
3147666LOUISA
Solar/Wind Helper
0.553
233923SMA
Solar/Wind Helper
0.769
233997TMININ_4.2
Solar/Wind Helper
0.21
232406W1-004 FULL
Solar/Wind Helper
0.518
232434Z2-077 GEN
Solar/Wind Helper
0.13
233950AC2-186 GEN
Solar/Wind Helper
0.119
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.117
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.313
966881AG1-559 GEN
Solar/Wind Helper
0.313
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
205941AD2-115 GEN
Solar/Wind Helper
0.499
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.138
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.777
211065PSPA IPP
Solar/Wind Helper
0.151
960841AF2-375 GEN
Solar/Wind Harmer
0.624
LAGNLTFEXP_LAGN->PJM
CLTF
14.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.226
TVALTFEXP_TVA->PJM
CLTF
7.078
NYPJM->LTFIMP_NY
CLTF
4.574
LGEELTFEXP_LGEE->PJM
CLTF
6.731
WECLTFEXP_WEC->PJM
CLTF
3.853
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.111
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.423
MECLTFEXP_MEC->PJM
CLTF
15.924
SIGELTFEXP_SIGE->PJM
CLTF
0.504

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.24 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4632.89
MW Contribution:
241.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
50/50
2.774
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.899
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
970179AG2-119 GEN
Solar/Wind Harmer
6.643
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.918
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971567AH1-282 GEN
Solar/Wind Harmer
5.517
959331AF2-224 GEN
Solar/Wind Harmer
5.044
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.193
24729505KEY G4
Adder
6.652
963791AG1-232 GEN
Solar/Wind Harmer
9.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
971985AH1-537 GEN
Solar/Wind Harmer
2.117
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
25196508WSDLE4
Adder
8.634
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
270543AE2-219 C
Solar/Wind Harmer
4.962
247536S-71 GEN
Solar/Wind Harmer
0.283
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
971771AH1-392 GEN
Solar/Wind Harmer
7.027
970289AG2-191 GEN
Solar/Wind Harmer
1.334
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
971549AH1-272 GEN
Solar/Wind Harmer
14.305
270119AB2-067 GEN1
50/50
6.887
270120AB2-067 GEN2
50/50
6.887
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.105
938701AE1-092 GEN
Solar/Wind Harmer
12.459
971655AH1-328 GEN
Solar/Wind Harmer
2.753
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
970935AG2-582 GEN
Adder
241.832
25326509SID D
Adder
1.398
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
970879AG2-548 GEN
Solar/Wind Harmer
1.228
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
246937BC-WTG2
Solar/Wind Harmer
0.292
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
960971AF2-388 GEN
Solar/Wind Harmer
4.179
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
25194408D.CRK1
Adder
7.692
25194508D.CRK3
Adder
1.438
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970885AG2-551 GEN
Solar/Wind Harmer
2.363
247621Y3-024
Adder
0.245
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270031AE2-169
Solar/Wind Harmer
3.884
270599AE1-208 GEN
Solar/Wind Harmer
6.473
270383AD1-128 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.273
247620Y3-023
Adder
0.465
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.374
24728805RICHG1
Adder
3.809
24728905RICHG2
Adder
3.809
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
965681AG1-436 GEN
Solar/Wind Harmer
8.747
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
274808UNIV PK N;4U
Adder
4.919
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.78
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
276776AD2-060 GEN
Solar/Wind Harmer
0.732
958011AF2-095 GEN
Solar/Wind Harmer
9.886
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
10.177
962691AG1-118 GEN
Solar/Wind Harmer
20.32
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
942111AE2-223 GEN
Solar/Wind Harmer
2.188
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235020AA1-095 C
Solar/Wind Helper
0.051
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
237061AD1-155 GEN
Solar/Wind Helper
1.703
238117U2-030
Solar/Wind Helper
0.315
238221AF1-254 C O1
Solar/Wind Helper
0.267
237080AD1-060 GEN
Solar/Wind Helper
0.332
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
316411AF1-147_GEN1
Solar/Wind Helper
0.865
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
223402AF1-300 C
Solar/Wind Helper
0.357
316006AB2-029 C
Solar/Wind Helper
0.114
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.113
232436AB1-176 C
Solar/Wind Helper
0.043
233946AB2-136 GEN
Solar/Wind Helper
0.553
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
316045AC1-158 PL2
Solar/Wind Helper
4.03
316450AC1-158 RIC
Solar/Wind Helper
0.336
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.059
219912AD2-042 GEN
Solar/Wind Helper
0.146
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.061
207459AE1-142 C O1
Solar/Wind Helper
0.282
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
24318805MLG1
50/50
9.823
23559001PLEAS1
50/50
5.39
270051AF1-062 GEN
50/50
11.411
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
961921AG1-034 GEN
Solar/Wind Harmer
7.349
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
14.139
24721905FLATG4
Adder
22.814
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
970191AG2-125 GEN
Solar/Wind Harmer
1.872
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
24695305TIMB G C
Solar/Wind Harmer
0.609
944531AF1-118 GEN
Solar/Wind Harmer
32.112
270043AE2-236 GEN
Solar/Wind Harmer
4.595
252519AF1-045_GEN
Solar/Wind Harmer
3.711
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
8.723
25194608D.CRK4
Adder
1.672
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
971347AH1-153 GEN
Solar/Wind Harmer
3.535
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.713
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
970289AG2-191 GEN
Solar/Wind Harmer
0.773
270505AE1-170 C O1
Solar/Wind Harmer
7.374
247642Z2-115 C
Solar/Wind Harmer
0.003
25196008MFTGT1
Adder
1.349
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
274753CRETE EC ;3U
Adder
8.15
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
274811UNIV PK N;7U
Adder
4.941
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
274887GEN-1.85
Solar/Wind Harmer
0.178
276843GEN-1.7
Solar/Wind Harmer
0.222
276806AD2-047 C O1
Solar/Wind Harmer
3.89
274826FISK ;BP
Adder
10.773
972038AH1-567 GEN2
Adder
0.359
972167AH1-666 GEN
Solar/Wind Harmer
5.491
24728705AND G3
Adder
7.891
24728505AND G1
Adder
3.773
270166AC1-044 GEN3
50/50
6.887
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
962761AG1-125 GEN
Solar/Wind Harmer
33.201
970149AG2-104 GEN
Solar/Wind Harmer
17.929
970155AG2-107 GEN
Solar/Wind Harmer
21.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.804
270273AD2-016 GEN
Solar/Wind Harmer
0.78
972269AH1-719 GEN
Adder
2.495
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965011AG1-365 GEN
Solar/Wind Harmer
7.206
960001AF2-291 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.09
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.054
25194608D.CRK4
Adder
1.672
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
276903AD2-071 C
Solar/Wind Harmer
7.818
25196008MFTGT1
Adder
1.393
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.046
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274754CRETE EC ;4U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
274812UNIV PK N;8U
Adder
4.941
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.093
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
939401AE1-172 GEN
Solar/Wind Harmer
5.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
971997AH1-543 GEN
Solar/Wind Harmer
3.554
962781AG1-127 GEN
Solar/Wind Harmer
6.441
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.202
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.427
316095T157 G97
Solar/Wind Helper
1.459
23583801GRNGAP
Solar/Wind Helper
5.433
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23546401DTGZ2-030
Solar/Wind Helper
0.086
238126S14_GEN_1
Solar/Wind Helper
0.769
237038AE2-054 C
Solar/Wind Helper
0.264
235067AD1-061 GEN
Solar/Wind Helper
0.432
237085AD2-009_GEN
Solar/Wind Helper
1.596
237002AB1-128_GEN
Solar/Wind Helper
0.43
23777801MSM_W1-116
Solar/Wind Helper
0.111
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.337
208835TUHI V3-051
Solar/Wind Helper
0.021
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
232406W1-004 FULL
Solar/Wind Helper
0.493
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.301
219612MATRIX C
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.481
20716928W4-060COL
Solar/Wind Helper
0.05
957471AF2-041 GEN
Solar/Wind Harmer
13.123
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.341
274776LINCOLN ;7U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972228AH1-698 GEN2
Adder
3.644
972227AH1-698 GEN1
Adder
2.566
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
274728ELWOOD EC;5P
Adder
16.119
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
274735ELWOOD EC;4P
Adder
16.119
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
970169AG2-114 GEN
Solar/Wind Harmer
6.772
971675AH1-338 GEN
Solar/Wind Harmer
2.63
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
971411AH1-196 GEN
Solar/Wind Harmer
10.113
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.07
23750701CROSSCHOOL
Solar/Wind Helper
1.401
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
959381AF2-229 GEN
Solar/Wind Helper
0.346
20390526W1-045 C
Solar/Wind Helper
0.339
23750501ELLIOTTS
Solar/Wind Helper
0.573
3141426STAFORD
Solar/Wind Helper
0.051
205943AE1-185 GEN
Solar/Wind Helper
0.494
205956AE1-196_GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
233901CHERRYDALE C
Solar/Wind Helper
0.226
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
18.754
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274676JOLIET 29;8U
Adder
29.018
274729ELWOOD EC;1P
Adder
16.119
274730ELWOOD EC;6P
Adder
16.119
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970193AG2-126 GEN
Solar/Wind Harmer
10.106
970571AG2-364 GEN
Solar/Wind Harmer
13.468
964991AG1-363 GEN
Solar/Wind Helper
4.979
238108AE1-109 GEN1
Solar/Wind Helper
0.107
238110AE1-109 GEN3
Solar/Wind Helper
0.107
238175AF1-290_GEN
Solar/Wind Helper
0.152
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
235063AE1-101 C2
Solar/Wind Helper
1.608
237001AB1-127_GEN
Solar/Wind Helper
0.428
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
23562501BACKB
Solar/Wind Helper
0.845
205916AD1-020 GEN
Solar/Wind Helper
1.664
208835TUHI V3-051
Solar/Wind Helper
0.021
205932AD2-116_GEN
Solar/Wind Helper
0.494
233918AB1-142 GEN
Solar/Wind Helper
0.488
233944AB2-135 GEN
Solar/Wind Helper
0.573
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
316447AC1-158 HLD
Solar/Wind Helper
2.771
316044AC1-158 PL1
Solar/Wind Helper
1.259
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
203975AE1-071-GEN
Solar/Wind Helper
2.421
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
959091AF2-200 GEN
Solar/Wind Harmer
8.748
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230434AG1-499 GEN
Solar/Wind Helper
0.223
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.075
219615MILLCREEK C
Solar/Wind Helper
0.026
20715028HAN_X4-015
Solar/Wind Helper
0.055
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.184
971171AH1-044 GEN
Solar/Wind Harmer
8.748
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
TVALTFEXP_TVA->PJM
CLTF
6.984
NYPJM->LTFIMP_NY
CLTF
4.644
LGEELTFEXP_LGEE->PJM
CLTF
6.478
WECLTFEXP_WEC->PJM
CLTF
3.676
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345
CPLELTFEXP_CPLE->PJM
CLTF
0.539
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
MECLTFEXP_MEC->PJM
CLTF
15.273
SIGELTFEXP_SIGE->PJM
CLTF
0.485

Details for 01MTZION-01BERYL 138.0 kV Ckt 1 line l/o AP_P2-3_PE-500-014_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01MTZION-01BERYL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.1 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:294.78
MW Contribution:
11.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750501ELLIOTTS
Solar/Wind Harmer
0.971
23750701CROSSCHOOL
Solar/Wind Helper
3.116
238185AF2-356 C
Solar/Wind Harmer
24.308
970935AG2-582 GEN
Adder
11.589
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
TVALTFEXP_TVA->PJM
CLTF
0.155
NYPJM->LTFIMP_NY
CLTF
0.148
LGEELTFEXP_LGEE->PJM
CLTF
0.173
WECLTFEXP_WEC->PJM
CLTF
0.1
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.664
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.649
MECLTFEXP_MEC->PJM
CLTF
0.403
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01MTZION-01BERYL 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT19_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01MTZION-01BERYL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT19_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.44 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:287.24
MW Contribution:
11.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750501ELLIOTTS
Solar/Wind Harmer
0.973
23750701CROSSCHOOL
Solar/Wind Helper
3.116
964991AG1-363 GEN
Solar/Wind Helper
1.775
238185AF2-356 C
Solar/Wind Harmer
24.311
970935AG2-582 GEN
Adder
11.711
LAGNLTFEXP_LAGN->PJM
CLTF
0.33
TVALTFEXP_TVA->PJM
CLTF
0.161
NYPJM->LTFIMP_NY
CLTF
0.145
LGEELTFEXP_LGEE->PJM
CLTF
0.176
WECLTFEXP_WEC->PJM
CLTF
0.102
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.736
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.047
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.669
MECLTFEXP_MEC->PJM
CLTF
0.413
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01MTZION-01BERYL 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01MTZION-01BERYL 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.67 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:269.18
MW Contribution:
11.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
11.589
23750701CROSSCHOOL
Solar/Wind Helper
3.116
238185AF2-356 C
Solar/Wind Harmer
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
TVALTFEXP_TVA->PJM
CLTF
0.155
NYPJM->LTFIMP_NY
CLTF
0.148
LGEELTFEXP_LGEE->PJM
CLTF
0.173
WECLTFEXP_WEC->PJM
CLTF
0.1
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.664
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.649
MECLTFEXP_MEC->PJM
CLTF
0.403
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01MTZION-01BERYL 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01MTZION-01BERYL 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.17 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:261.96
MW Contribution:
11.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
11.711
23750701CROSSCHOOL
Solar/Wind Helper
3.116
964991AG1-363 GEN
Solar/Wind Helper
1.775
238185AF2-356 C
Solar/Wind Harmer
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.33
TVALTFEXP_TVA->PJM
CLTF
0.161
NYPJM->LTFIMP_NY
CLTF
0.145
LGEELTFEXP_LGEE->PJM
CLTF
0.176
WECLTFEXP_WEC->PJM
CLTF
0.102
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.736
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.047
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.669
MECLTFEXP_MEC->PJM
CLTF
0.413
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01SHINNS-01PRNTY 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.33 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:301.04
MW Contribution:
83.88
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
122.446
970935AG2-582 GEN
Adder
83.882
LAGNLTFEXP_LAGN->PJM
CLTF
0.983
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.576
TVALTFEXP_TVA->PJM
CLTF
0.49
NYPJM->LTFIMP_NY
CLTF
0.302
LGEELTFEXP_LGEE->PJM
CLTF
0.44
WECLTFEXP_WEC->PJM
CLTF
0.238
CPLELTFEXP_CPLE->PJM
CLTF
0.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.335
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.869
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.942
MECLTFEXP_MEC->PJM
CLTF
1.004
SIGELTFEXP_SIGE->PJM
CLTF
0.033

Details for 01SHINNS-01PRNTY 138.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.84 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:297.06
MW Contribution:
84.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
123.297
970935AG2-582 GEN
Adder
84.094
LAGNLTFEXP_LAGN->PJM
CLTF
0.966
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.653
TVALTFEXP_TVA->PJM
CLTF
0.483
NYPJM->LTFIMP_NY
CLTF
0.307
LGEELTFEXP_LGEE->PJM
CLTF
0.423
WECLTFEXP_WEC->PJM
CLTF
0.226
CPLELTFEXP_CPLE->PJM
CLTF
0.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.905
MECLTFEXP_MEC->PJM
CLTF
0.96
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for 01SHINNS-01PRNTY 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT4_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT4_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.84 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:297.06
MW Contribution:
84.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
123.297
970935AG2-582 GEN
Adder
84.094
LAGNLTFEXP_LAGN->PJM
CLTF
0.966
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.653
TVALTFEXP_TVA->PJM
CLTF
0.483
NYPJM->LTFIMP_NY
CLTF
0.307
LGEELTFEXP_LGEE->PJM
CLTF
0.423
WECLTFEXP_WEC->PJM
CLTF
0.226
CPLELTFEXP_CPLE->PJM
CLTF
0.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.905
MECLTFEXP_MEC->PJM
CLTF
0.96
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for 01SHINNS-01PRNTY 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-018_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-018_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.84 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:297.06
MW Contribution:
84.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
237068AA2-119 GEN
50/50
123.297
970935AG2-582 GEN
Adder
84.094
LAGNLTFEXP_LAGN->PJM
CLTF
0.966
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.653
TVALTFEXP_TVA->PJM
CLTF
0.483
NYPJM->LTFIMP_NY
CLTF
0.307
LGEELTFEXP_LGEE->PJM
CLTF
0.423
WECLTFEXP_WEC->PJM
CLTF
0.226
CPLELTFEXP_CPLE->PJM
CLTF
0.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.905
MECLTFEXP_MEC->PJM
CLTF
0.96
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.01 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5005.84
MW Contribution:
238.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.05
23559101PLEAS2
50/50
5.445
270122AB2-093 CT
50/50
4.1
962761AG1-125 GEN
Solar/Wind Harmer
40.867
970149AG2-104 GEN
Solar/Wind Harmer
25.235
970155AG2-107 GEN
Solar/Wind Harmer
17.82
270286AF1-227 GEN2
Solar/Wind Harmer
2.547
270520AE2-214 GEN
Solar/Wind Harmer
7.352
270391AF1-285 GEN3
Solar/Wind Harmer
1.427
270578AF1-285 GEN2
Solar/Wind Harmer
1.427
971995AH1-542 GEN
Solar/Wind Harmer
12.942
972269AH1-719 GEN
Adder
2.693
270317AD1-130_GEN
Solar/Wind Harmer
3.738
270485AE1-090_GEN
Solar/Wind Harmer
0.706
270510AE1-227 GEN1
Solar/Wind Harmer
2.885
253333AC1-068 GEN
Solar/Wind Harmer
1.205
241813AF1-122_GEN
Solar/Wind Harmer
6.22
971201AH1-060 GEN
Solar/Wind Harmer
1.944
270273AD2-016 GEN
Solar/Wind Harmer
3.042
241847AF2-150_GEN
Solar/Wind Harmer
4.61
246936BC-WTG1
Solar/Wind Harmer
4.329
270489AE1-102 GEN1
Solar/Wind Harmer
1.439
965421AG1-410 GEN
Solar/Wind Harmer
33.164
971073AG2-665 GEN
Solar/Wind Harmer
1.284
25326309TAIT D
Adder
1.207
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
270297AD1-101 GEN
Solar/Wind Harmer
2.226
965011AG1-365 GEN
Solar/Wind Harmer
10.939
270258AD1-119 GEN
Solar/Wind Harmer
2.219
253398AE2-221_GEN2
Solar/Wind Harmer
4.932
253316AC1-085 GEN3
Solar/Wind Harmer
9.041
946171AF1-282 GEN
Solar/Wind Harmer
10.799
965651AG1-433 GEN
Solar/Wind Harmer
5.866
270024AE2-089 GEN
Solar/Wind Harmer
5.027
958861AF2-177 GEN
Solar/Wind Harmer
11.712
960001AF2-291 GEN
Solar/Wind Harmer
3.236
24639705ELKHART HY
Adder
0.164
945371AF1-202 GEN
Solar/Wind Harmer
7.453
270216AD2-079_GEN
Solar/Wind Harmer
0.645
945111AF1-176 GEN
Solar/Wind Harmer
19.021
957891AF2-083 GEN
Solar/Wind Harmer
15.982
252516AE2-318_GEN
Solar/Wind Harmer
10.65
270449AD2-020 GEN
Solar/Wind Harmer
2.984
943021AE2-325 GEN
Solar/Wind Harmer
3.878
270222AC2-111 GEN
Solar/Wind Harmer
4.753
944031AF1-071 GEN
Solar/Wind Harmer
1.069
24441205WTRV SLR C
Solar/Wind Harmer
0.143
252510AF1-249 C
Solar/Wind Harmer
0.443
25194608D.CRK4
Adder
1.747
25196808ZIMRHP
Adder
79.955
23906502RICHG2&3
Adder
1.268
25196008MFTGT1
Adder
1.455
274751CRETE EC ;1U
Adder
8.571
274754CRETE EC ;4U
Adder
8.571
274723RIVER EC ;12
Adder
18.619
274773LINCOLN ;4U
Adder
8.764
274774LINCOLN ;5U
Adder
8.764
274812UNIV PK N;8U
Adder
5.194
274802UNIV PARK;5U
Adder
6.031
23920202STRYCT
Adder
1.44
274676JOLIET 29;8U
Adder
31.606
274732ELWOOD EC;7P
Adder
16.929
274674JOLIET 9 ;6U
Adder
15.855
23583801GRNGAP
Solar/Wind Helper
6.383
316095T157 G97
Solar/Wind Helper
1.71
238109AE1-109 GEN2
Solar/Wind Helper
0.122
238185AF2-356 C
Solar/Wind Helper
2.787
23546401DTGZ2-030
Solar/Wind Helper
0.1
238120AE2-309 GEN
Solar/Wind Helper
0.557
238126S14_GEN_1
Solar/Wind Helper
0.87
237038AE2-054 C
Solar/Wind Helper
0.294
235067AD1-061 GEN
Solar/Wind Helper
0.481
237085AD2-009_GEN
Solar/Wind Helper
1.776
237002AB1-128_GEN
Solar/Wind Helper
0.477
3141196NOKESVL
Solar/Wind Helper
1.144
23777801MSM_W1-116
Solar/Wind Helper
0.123
226910AB2-157 C
Solar/Wind Helper
0.016
227287AC2-120 GEN
Solar/Wind Helper
0.377
23751101LEADS_P59
Solar/Wind Helper
1.984
3132273ORANGE
Solar/Wind Helper
0.049
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.297
233987AB2-037 GEN
Solar/Wind Helper
2.395
233933AB2-153 GEN
Solar/Wind Helper
0.238
232422X3-066 FULL
Solar/Wind Helper
0.117
232417X3-008 C
Solar/Wind Helper
0.238
233964AF2-378 GEN
Solar/Wind Helper
0.043
3147666LOUISA
Solar/Wind Helper
0.553
233923SMA
Solar/Wind Helper
0.769
233997TMININ_4.2
Solar/Wind Helper
0.21
232406W1-004 FULL
Solar/Wind Helper
0.518
232434Z2-077 GEN
Solar/Wind Helper
0.13
233950AC2-186 GEN
Solar/Wind Helper
0.119
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.117
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.313
966881AG1-559 GEN
Solar/Wind Helper
0.313
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
972239AH1-704 GEN
50/50
3.095
270459AD2-067 GEN
Solar/Wind Harmer
10.428
961821AG1-024 GEN
Solar/Wind Harmer
10.588
241955AC1-078 GEN
Solar/Wind Harmer
8.918
241973AD2-163_GEN1
Solar/Wind Harmer
2.358
241974AD2-163_GEN2
Solar/Wind Harmer
2.358
940611AE2-048 GEN
Solar/Wind Harmer
26.008
941391AE2-136 GEN
Solar/Wind Harmer
13.477
270223U2-072_GEN1
Solar/Wind Harmer
2.33
270224U2-072_GEN2
Solar/Wind Harmer
2.33
270227U2-072_GEN3
Solar/Wind Harmer
2.33
270228U2-072_GEN4
Solar/Wind Harmer
2.33
270231U2-072_GEN5
Solar/Wind Harmer
2.33
270578AF1-285 GEN2
Solar/Wind Harmer
0.549
943861AF1-054 GEN
Solar/Wind Harmer
4.542
943851AF1-053 GEN
Solar/Wind Harmer
2.195
945631AF1-228 GEN
Solar/Wind Harmer
5.525
270302AB2-170 GEN
Solar/Wind Harmer
9.776
270432AC2-029 GEN
Solar/Wind Harmer
8.117
970179AG2-119 GEN
Solar/Wind Harmer
9.237
253338AC1-165 GEN
Solar/Wind Harmer
1.249
253343AC1-166 GEN
Solar/Wind Harmer
1.249
241972AD1-140 GEN
Solar/Wind Harmer
5.07
270263AC1-001 GEN
Solar/Wind Harmer
1.18
971567AH1-282 GEN
Solar/Wind Harmer
5.635
270377AD1-106 GEN
Solar/Wind Harmer
5.917
966831AG1-554 GEN
Solar/Wind Harmer
1.337
270291AC1-194 GEN
Solar/Wind Harmer
5.669
270340AC2-060 GEN
Solar/Wind Harmer
3.354
957201AF2-014 GEN
Solar/Wind Harmer
5.019
270435AC2-044 GEN
Solar/Wind Harmer
2.213
270007AE1-245 C
Solar/Wind Harmer
5.939
253372AE2-315 SEC3
Adder
2.081
253372AE2-315 SEC3
Adder
2.081
247521TR3_G114
Solar/Wind Harmer
3.687
270191TR4_S_V150
Solar/Wind Harmer
3.29
965051AG1-369 GEN
Solar/Wind Harmer
5.479
25306009OHH W.
Adder
3.158
965041AG1-368 GEN
Solar/Wind Harmer
10.944
959331AF2-224 GEN
Solar/Wind Harmer
10.939
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.18
963791AG1-232 GEN
Solar/Wind Harmer
14.614
253433AC1-085 GEN1
Solar/Wind Harmer
5.738
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
270071AF1-092 GEN
Solar/Wind Harmer
16.191
24729505KEY G4
Adder
6.997
945641AF1-229 GEN
Solar/Wind Harmer
3.912
970031AG2-029 GEN
Solar/Wind Harmer
26.913
958711AF2-162 GEN
Solar/Wind Harmer
1.086
945581AF1-223 GEN
Solar/Wind Harmer
4.845
971029AG2-637 GEN
Solar/Wind Harmer
16.005
270499AE1-146 GEN
Solar/Wind Harmer
2.679
270543AE2-219 C
Solar/Wind Harmer
10.668
247536S-71 GEN
Solar/Wind Harmer
4.316
961761AG1-017 GEN
Solar/Wind Harmer
0.456
964611AG1-324 GEN
Solar/Wind Harmer
4.154
971771AH1-392 GEN
Solar/Wind Harmer
9.58
944161AF1-084 GEN
Solar/Wind Harmer
2.352
25196408WSDLE3
Adder
9.385
25196308WSDLE2
Adder
9.303
25196208WSDLE1
Adder
9.28
25196708WSDLE6
Adder
9.256
25196508WSDLE4
Adder
9.023
25196108MFTGT2
Adder
1.604
25196108MFTGT2
Adder
1.489
274775LINCOLN ;6U
Adder
8.764
274776LINCOLN ;7U
Adder
8.764
274777LINCOLN ;8U
Adder
8.764
972037AH1-567 GEN1
Adder
0.189
274827FISK ;RP
Adder
8.022
274800UNIV PARK;3U
Adder
6.026
274801UNIV PARK;4U
Adder
6.026
972228AH1-698 GEN2
Adder
3.828
972227AH1-698 GEN1
Adder
2.695
274687WILL CNTY;4U
Adder
28.802
274687WILL CNTY;4U
Adder
28.802
274675JOLIET 29;7U
Adder
31.606
274675JOLIET 29;7U
Adder
30.477
274728ELWOOD EC;5P
Adder
16.929
274731ELWOOD EC;2P
Adder
16.929
274733ELWOOD EC;3P
Adder
16.929
274735ELWOOD EC;4P
Adder
16.929
23750701CROSSCHOOL
Solar/Wind Helper
1.591
238169AE2-226 GEN1
Solar/Wind Helper
0.777
238170AE2-226 GEN2
Solar/Wind Helper
0.777
238118U2-030_1
Solar/Wind Helper
0.357
3138216PACIFIC
Solar/Wind Helper
0.049
23779801AA1-109
Solar/Wind Helper
0.208
237030AB1-096 C
Solar/Wind Helper
0.071
237025AB1-124 C
Solar/Wind Helper
0.176
226929AD2-058 GEN
Solar/Wind Helper
0.108
3141426STAFORD
Solar/Wind Helper
0.058
315651AD1-115 GEN
Solar/Wind Helper
0.883
316164AC1-076 GEN
Solar/Wind Helper
1.232
23750501ELLIOTTS
Solar/Wind Helper
0.631
205917AD1-020 ES
Solar/Wind Helper
0.381
959381AF2-229 GEN
Solar/Wind Helper
0.368
20390526W1-045 C
Solar/Wind Helper
0.361
205943AE1-185 GEN
Solar/Wind Helper
0.521
205941AD2-115 GEN
Solar/Wind Helper
0.499
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.138
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.777
211065PSPA IPP
Solar/Wind Helper
0.151
960841AF2-375 GEN
Solar/Wind Harmer
0.624
270119AB2-067 GEN1
50/50
7.05
270120AB2-067 GEN2
50/50
7.05
24318905MLG2
50/50
7.451
270054AF2-122 C O1
Solar/Wind Harmer
4.054
270349AD2-093_GEN
Solar/Wind Harmer
4.513
270471AD2-092_GEN
Solar/Wind Harmer
4.513
946101AF1-275 GEN
Solar/Wind Harmer
1.838
253383AE2-342_GEN
Solar/Wind Harmer
1.057
938701AE1-092 GEN
Solar/Wind Harmer
24.428
942861AE2-305 GEN
Solar/Wind Harmer
9.201
270462AD2-086
Solar/Wind Harmer
8.12
972159AH1-661 GEN
Adder
1.163
241960AC2-195 GEN
Solar/Wind Harmer
3.204
270269AC2-059
Solar/Wind Harmer
10.672
253378AE2-206_GEN
Solar/Wind Harmer
4.074
25326509SID D
Adder
1.478
253415AE1-040 GEN
Solar/Wind Harmer
1.252
25326109MON D
Adder
1.457
246937BC-WTG2
Solar/Wind Harmer
4.329
971073AG2-665 GEN
Solar/Wind Harmer
8.835
970879AG2-548 GEN
Solar/Wind Harmer
1.284
25322209TAIT E
Adder
10.744
25322209TAIT E
Adder
10.502
942801AE2-298 GEN
Solar/Wind Harmer
1.666
247607V1-011 GEN
Solar/Wind Harmer
4.348
253370AE2-315 SEC1
Adder
2.2
270246TR4_N_V150
Solar/Wind Harmer
0.933
270247TR4_N_V136
Solar/Wind Harmer
0.933
247522W1-056 GEN
Solar/Wind Harmer
2.469
253349AC2-067 GEN
Solar/Wind Harmer
2.225
253400AC2-068 GEN
Solar/Wind Harmer
0.895
927014AC1-188 GEN
Solar/Wind Harmer
1.72
944231AF1-091 GEN
Solar/Wind Harmer
19.433
942221AE2-234 GEN
Solar/Wind Harmer
3.759
944541AF1-119 GEN
Solar/Wind Harmer
4.494
960971AF2-388 GEN
Solar/Wind Harmer
11.731
247620Y3-023
Adder
0.492
970349AG2-230 GEN
Solar/Wind Harmer
16.027
247621Y3-024
Adder
0.257
25183208HLCRTG
Solar/Wind Harmer
6.454
970883AG2-550 GEN
Solar/Wind Harmer
10.668
970885AG2-551 GEN
Solar/Wind Harmer
2.481
962581AG1-107 GEN
Solar/Wind Harmer
5.371
961491AF2-440 GEN
Solar/Wind Harmer
2.232
270201AC2-176 GEN
Solar/Wind Harmer
5.48
961051AF2-396 GEN
Solar/Wind Harmer
16.91
961051AF2-396 GEN
Solar/Wind Harmer
7.865
964611AG1-324 GEN
Solar/Wind Harmer
0.557
270031AE2-169
Solar/Wind Harmer
8.665
270599AE1-208 GEN
Solar/Wind Harmer
8.665
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.503
24728805RICHG1
Adder
3.989
24728905RICHG2
Adder
3.989
970935AG2-582 GEN
Adder
238.716
274770LINCOLN ;1U
Adder
8.764
274771LINCOLN ;2U
Adder
8.764
274805UNIV PK N;1U
Adder
5.205
274808UNIV PK N;4U
Adder
5.171
274674JOLIET 9 ;6U
Adder
0.246
316097T157 G90
Solar/Wind Helper
1.71
238147AE2-230_GEN1
Solar/Wind Helper
0.556
238148AE2-230_GEN2
Solar/Wind Helper
0.556
238149AF1-291A_GEN
Solar/Wind Helper
0.159
237061AD1-155 GEN
Solar/Wind Helper
1.974
235054AD2-180 GEN
Solar/Wind Helper
2.118
235531U2-073 GEN
Solar/Wind Helper
3.481
23585401KL_K28_T16
Solar/Wind Helper
1.534
235020AA1-095 C
Solar/Wind Helper
0.058
238117U2-030
Solar/Wind Helper
0.357
238221AF1-254 C O1
Solar/Wind Helper
0.297
237080AD1-060 GEN
Solar/Wind Helper
0.369
235062AE1-101 C1
Solar/Wind Helper
1.786
316411AF1-147_GEN1
Solar/Wind Helper
0.984
23751201ROTHROCK
Solar/Wind Helper
0.821
237006AB1-125 GEN
Solar/Wind Helper
0.132
316006AB2-029 C
Solar/Wind Helper
0.131
223401AF1-299 GEN
Solar/Wind Helper
0.389
223402AF1-300 C
Solar/Wind Helper
0.389
316045AC1-158 PL2
Solar/Wind Helper
4.643
316450AC1-158 RIC
Solar/Wind Helper
0.387
3132123MT JACKSON
Solar/Wind Helper
0.767
233930AB2-032 GEN
Solar/Wind Helper
0.389
233982AB2-133 GEN
Solar/Wind Helper
0.367
232424Y1-079 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.581
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.982
232410W1-006 C
Solar/Wind Helper
0.518
232428Y3-058 C
Solar/Wind Helper
0.346
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.238
233954AC2-188 GEN
Solar/Wind Helper
0.238
966001AG1-469 GEN
Solar/Wind Helper
0.256
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.152
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
24318805MLG1
50/50
10
23559001PLEAS1
50/50
5.445
270051AF1-062 GEN
50/50
11.971
962771AG1-126 GEN
Solar/Wind Harmer
40.867
970153AG2-106 GEN
Solar/Wind Harmer
17.82
961921AG1-034 GEN
Solar/Wind Harmer
15.881
270284AF1-227 GEN1
Solar/Wind Harmer
6.884
270287AF1-227 GEN3
Solar/Wind Harmer
2.547
942051AE2-217 GEN
Solar/Wind Harmer
21.323
942871AE2-306 GEN
Solar/Wind Harmer
1.07
270391AF1-285 GEN3
Solar/Wind Harmer
0.549
960801AF2-371 GEN
Solar/Wind Harmer
2.983
964871AG1-351 GEN
Solar/Wind Harmer
2.06
270512AE1-227 GEN2
Solar/Wind Harmer
2.449
270518AE2-148 GEN
Solar/Wind Harmer
13.997
958581AF2-149 GEN
Solar/Wind Harmer
4.955
971199AH1-059 GEN
Solar/Wind Harmer
2.432
24721905FLATG4
Adder
23.444
253325AC1-069 GEN
Solar/Wind Harmer
1.205
970065AG2-057 GEN
Solar/Wind Harmer
0.972
276820AF1-078_GEN
Solar/Wind Harmer
1.81
270588AE1-091_GEN
Solar/Wind Harmer
12.281
961961AG1-039 GEN
Solar/Wind Harmer
3.18
246938BC-WTG3
Solar/Wind Harmer
4.404
270491AE1-102 GEN2
Solar/Wind Harmer
1.439
970879AG2-548 GEN
Solar/Wind Harmer
8.835
958091AF2-103 GEN
Solar/Wind Harmer
0.178
960071AF2-298 GEN
Solar/Wind Harmer
1.664
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
24695305TIMB G C
Solar/Wind Harmer
3.661
965021AG1-366 GEN
Solar/Wind Harmer
2.544
270044AE2-322 C
Solar/Wind Harmer
1.431
253394AE2-221_GEN
Solar/Wind Harmer
4.932
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270043AE2-236 GEN
Solar/Wind Harmer
5.961
944531AF1-118 GEN
Solar/Wind Harmer
37.819
253317AC1-085 GEN4
Solar/Wind Harmer
9.041
946181AF1-283 GEN
Solar/Wind Harmer
14.038
270063AE2-323 C
Solar/Wind Harmer
2.363
270541AE2-072 C
Solar/Wind Harmer
4.86
971191AH1-055 GEN
Solar/Wind Harmer
20.005
971347AH1-153 GEN
Solar/Wind Harmer
5.342
247643Z2-116 C
Solar/Wind Harmer
0.074
962031AG1-047 GEN
Solar/Wind Harmer
3.224
957741AF2-068 GEN
Solar/Wind Harmer
15.993
945111AF1-176 GEN
Solar/Wind Harmer
6.028
270505AE1-170 C O1
Solar/Wind Harmer
15.984
252519AF1-045_GEN
Solar/Wind Harmer
3.876
252524AE2-267 GEN
Solar/Wind Harmer
1.675
25196608WSDLE5
Adder
9.116
25194608D.CRK4
Adder
1.747
270367AC2-061_GEN
Solar/Wind Harmer
3.375
23906502RICHG2&3
Adder
1.268
23906402RICHG1
Adder
1.268
25196008MFTGT1
Adder
1.409
274752CRETE EC ;2U
Adder
8.571
274753CRETE EC ;3U
Adder
8.571
274724RIVER EC ;11
Adder
18.401
274772LINCOLN ;3U
Adder
8.764
274814UNIV PK N;0U
Adder
5.24
274807UNIV PK N;3U
Adder
5.228
274811UNIV PK N;7U
Adder
5.194
274803UNIV PARK;6U
Adder
6.031
274826FISK ;BP
Adder
11.319
972038AH1-567 GEN2
Adder
0.377
972259AH1-714 GEN
Adder
19.698
274676JOLIET 29;8U
Adder
30.477
274729ELWOOD EC;1P
Adder
16.929
274730ELWOOD EC;6P
Adder
16.929
274734ELWOOD EC;8P
Adder
16.929
274736ELWOOD EC;9P
Adder
16.929
964991AG1-363 GEN
Solar/Wind Helper
5.569
238108AE1-109 GEN1
Solar/Wind Helper
0.122
238110AE1-109 GEN3
Solar/Wind Helper
0.122
238152AF2-075_GEN
Solar/Wind Helper
0.794
238175AF1-290_GEN
Solar/Wind Helper
0.173
238127S14_GEN_2
Solar/Wind Helper
0.87
23777901MDS_W4-102
Solar/Wind Helper
0.192
235063AE1-101 C2
Solar/Wind Helper
1.786
237001AB1-127_GEN
Solar/Wind Helper
0.476
316415AF1-147_GEN2
Solar/Wind Helper
0.984
23562501BACKB
Solar/Wind Helper
1
316447AC1-158 HLD
Solar/Wind Helper
3.193
316044AC1-158 PL1
Solar/Wind Helper
1.451
237048AF1-022 C
Solar/Wind Helper
0.18
205916AD1-020 GEN
Solar/Wind Helper
1.77
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.521
233918AB1-142 GEN
Solar/Wind Helper
0.514
233944AB2-135 GEN
Solar/Wind Helper
0.603
232426Y1-080 FULL
Solar/Wind Helper
0.04
3147666LOUISA
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.21
205956AE1-196_GEN
Solar/Wind Helper
0.521
233915AB1-141 GEN
Solar/Wind Helper
0.514
233901CHERRYDALE C
Solar/Wind Helper
0.238
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
230434AG1-499 GEN
Solar/Wind Helper
0.234
228728W1-130C
Solar/Wind Helper
0.055
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.192
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.084
20675128HRM_W1-127
Solar/Wind Helper
0.03
219304NAMERICA C
Solar/Wind Helper
0.133
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.293
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.518
232408W1-005 C
Solar/Wind Helper
0.518
316192AB2-158 GEN
Solar/Wind Helper
1.618
228729W2-030 C
Solar/Wind Helper
0.112
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.543
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.066
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674628WNG_W3-110
Solar/Wind Helper
0.09
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674928WA_W3-044
Solar/Wind Helper
0.099
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.573
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.151
LAGNLTFEXP_LAGN->PJM
CLTF
14.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.226
TVALTFEXP_TVA->PJM
CLTF
7.078
NYPJM->LTFIMP_NY
CLTF
4.574
LGEELTFEXP_LGEE->PJM
CLTF
6.731
WECLTFEXP_WEC->PJM
CLTF
3.853
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.111
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.423
MECLTFEXP_MEC->PJM
CLTF
15.924
SIGELTFEXP_SIGE->PJM
CLTF
0.504

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.57 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4761.71
MW Contribution:
241.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
50/50
2.774
270459AD2-067 GEN
Solar/Wind Harmer
0
24318805MLG1
50/50
9.823
23559001PLEAS1
50/50
5.39
270051AF1-062 GEN
50/50
11.411
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
961921AG1-034 GEN
Solar/Wind Harmer
7.349
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
14.139
24721905FLATG4
Adder
22.814
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
970191AG2-125 GEN
Solar/Wind Harmer
1.872
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
24695305TIMB G C
Solar/Wind Harmer
0.609
944531AF1-118 GEN
Solar/Wind Harmer
32.112
270043AE2-236 GEN
Solar/Wind Harmer
4.595
252519AF1-045_GEN
Solar/Wind Harmer
3.711
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
8.723
25194608D.CRK4
Adder
1.672
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
971347AH1-153 GEN
Solar/Wind Harmer
3.535
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.713
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
970289AG2-191 GEN
Solar/Wind Harmer
0.773
270505AE1-170 C O1
Solar/Wind Harmer
7.374
247642Z2-115 C
Solar/Wind Harmer
0.003
25196008MFTGT1
Adder
1.349
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
274753CRETE EC ;3U
Adder
8.15
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
274811UNIV PK N;7U
Adder
4.941
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
274887GEN-1.85
Solar/Wind Harmer
0.178
276843GEN-1.7
Solar/Wind Harmer
0.222
276806AD2-047 C O1
Solar/Wind Harmer
3.89
274826FISK ;BP
Adder
10.773
972038AH1-567 GEN2
Adder
0.359
972167AH1-666 GEN
Solar/Wind Harmer
5.491
24728705AND G3
Adder
7.891
24728505AND G1
Adder
3.773
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
18.754
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274676JOLIET 29;8U
Adder
29.018
274729ELWOOD EC;1P
Adder
16.119
274730ELWOOD EC;6P
Adder
16.119
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970193AG2-126 GEN
Solar/Wind Harmer
10.106
970571AG2-364 GEN
Solar/Wind Harmer
13.468
964991AG1-363 GEN
Solar/Wind Helper
4.979
238108AE1-109 GEN1
Solar/Wind Helper
0.107
238110AE1-109 GEN3
Solar/Wind Helper
0.107
238175AF1-290_GEN
Solar/Wind Helper
0.152
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
235063AE1-101 C2
Solar/Wind Helper
1.608
237001AB1-127_GEN
Solar/Wind Helper
0.428
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
23562501BACKB
Solar/Wind Helper
0.845
205916AD1-020 GEN
Solar/Wind Helper
1.664
208835TUHI V3-051
Solar/Wind Helper
0.021
205932AD2-116_GEN
Solar/Wind Helper
0.494
233918AB1-142 GEN
Solar/Wind Helper
0.488
233944AB2-135 GEN
Solar/Wind Helper
0.573
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
316447AC1-158 HLD
Solar/Wind Helper
2.771
316044AC1-158 PL1
Solar/Wind Helper
1.259
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
270166AC1-044 GEN3
50/50
6.887
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
962761AG1-125 GEN
Solar/Wind Harmer
33.201
970149AG2-104 GEN
Solar/Wind Harmer
17.929
970155AG2-107 GEN
Solar/Wind Harmer
21.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.804
270273AD2-016 GEN
Solar/Wind Harmer
0.78
972269AH1-719 GEN
Adder
2.495
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965011AG1-365 GEN
Solar/Wind Harmer
7.206
960001AF2-291 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.09
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.054
25194608D.CRK4
Adder
1.672
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
276903AD2-071 C
Solar/Wind Harmer
7.818
25196008MFTGT1
Adder
1.393
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.046
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274754CRETE EC ;4U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
274812UNIV PK N;8U
Adder
4.941
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.093
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
939401AE1-172 GEN
Solar/Wind Harmer
5.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
971997AH1-543 GEN
Solar/Wind Harmer
3.554
962781AG1-127 GEN
Solar/Wind Harmer
6.441
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.202
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.427
316095T157 G97
Solar/Wind Helper
1.459
23583801GRNGAP
Solar/Wind Helper
5.433
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23546401DTGZ2-030
Solar/Wind Helper
0.086
238126S14_GEN_1
Solar/Wind Helper
0.769
237038AE2-054 C
Solar/Wind Helper
0.264
235067AD1-061 GEN
Solar/Wind Helper
0.432
237085AD2-009_GEN
Solar/Wind Helper
1.596
237002AB1-128_GEN
Solar/Wind Helper
0.43
23777801MSM_W1-116
Solar/Wind Helper
0.111
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
961821AG1-024 GEN
Solar/Wind Harmer
4.899
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
970179AG2-119 GEN
Solar/Wind Harmer
6.643
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.918
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971567AH1-282 GEN
Solar/Wind Harmer
5.517
959331AF2-224 GEN
Solar/Wind Harmer
5.044
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.193
24729505KEY G4
Adder
6.652
963791AG1-232 GEN
Solar/Wind Harmer
9.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
971985AH1-537 GEN
Solar/Wind Harmer
2.117
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
25196508WSDLE4
Adder
8.634
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
270543AE2-219 C
Solar/Wind Harmer
4.962
247536S-71 GEN
Solar/Wind Harmer
0.283
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
971771AH1-392 GEN
Solar/Wind Harmer
7.027
970289AG2-191 GEN
Solar/Wind Harmer
1.334
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
971549AH1-272 GEN
Solar/Wind Harmer
14.305
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.341
274776LINCOLN ;7U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972228AH1-698 GEN2
Adder
3.644
972227AH1-698 GEN1
Adder
2.566
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
274728ELWOOD EC;5P
Adder
16.119
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
274735ELWOOD EC;4P
Adder
16.119
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
970169AG2-114 GEN
Solar/Wind Harmer
6.772
971675AH1-338 GEN
Solar/Wind Harmer
2.63
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
971411AH1-196 GEN
Solar/Wind Harmer
10.113
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.07
23750701CROSSCHOOL
Solar/Wind Helper
1.401
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
959381AF2-229 GEN
Solar/Wind Helper
0.346
20390526W1-045 C
Solar/Wind Helper
0.339
270119AB2-067 GEN1
50/50
6.887
270120AB2-067 GEN2
50/50
6.887
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.105
938701AE1-092 GEN
Solar/Wind Harmer
12.459
971655AH1-328 GEN
Solar/Wind Harmer
2.753
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
970935AG2-582 GEN
Adder
241.832
25326509SID D
Adder
1.398
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
970879AG2-548 GEN
Solar/Wind Harmer
1.228
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
246937BC-WTG2
Solar/Wind Harmer
0.292
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
960971AF2-388 GEN
Solar/Wind Harmer
4.179
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
25194408D.CRK1
Adder
7.692
25194508D.CRK3
Adder
1.438
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970885AG2-551 GEN
Solar/Wind Harmer
2.363
247621Y3-024
Adder
0.245
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270031AE2-169
Solar/Wind Harmer
3.884
270599AE1-208 GEN
Solar/Wind Harmer
6.473
270383AD1-128 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.273
247620Y3-023
Adder
0.465
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.374
24728805RICHG1
Adder
3.809
24728905RICHG2
Adder
3.809
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
965681AG1-436 GEN
Solar/Wind Harmer
8.747
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
274808UNIV PK N;4U
Adder
4.919
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.78
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
276776AD2-060 GEN
Solar/Wind Harmer
0.732
958011AF2-095 GEN
Solar/Wind Harmer
9.886
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
10.177
962691AG1-118 GEN
Solar/Wind Harmer
20.32
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
942111AE2-223 GEN
Solar/Wind Harmer
2.188
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235020AA1-095 C
Solar/Wind Helper
0.051
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
237061AD1-155 GEN
Solar/Wind Helper
1.703
238117U2-030
Solar/Wind Helper
0.315
238221AF1-254 C O1
Solar/Wind Helper
0.267
237080AD1-060 GEN
Solar/Wind Helper
0.332
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
316411AF1-147_GEN1
Solar/Wind Helper
0.865
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
223402AF1-300 C
Solar/Wind Helper
0.357
316006AB2-029 C
Solar/Wind Helper
0.114
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
23750501ELLIOTTS
Solar/Wind Helper
0.573
3141426STAFORD
Solar/Wind Helper
0.051
205943AE1-185 GEN
Solar/Wind Helper
0.494
205956AE1-196_GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
233901CHERRYDALE C
Solar/Wind Helper
0.226
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230434AG1-499 GEN
Solar/Wind Helper
0.223
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.075
219615MILLCREEK C
Solar/Wind Helper
0.026
20715028HAN_X4-015
Solar/Wind Helper
0.055
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.184
971171AH1-044 GEN
Solar/Wind Harmer
8.748
232424Y1-079 C
Solar/Wind Helper
0.113
232436AB1-176 C
Solar/Wind Helper
0.043
233946AB2-136 GEN
Solar/Wind Helper
0.553
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
316045AC1-158 PL2
Solar/Wind Helper
4.03
316450AC1-158 RIC
Solar/Wind Helper
0.336
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.059
219912AD2-042 GEN
Solar/Wind Helper
0.146
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.061
207459AE1-142 C O1
Solar/Wind Helper
0.282
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
203975AE1-071-GEN
Solar/Wind Helper
2.421
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
959091AF2-200 GEN
Solar/Wind Harmer
8.748
227287AC2-120 GEN
Solar/Wind Helper
0.337
208835TUHI V3-051
Solar/Wind Helper
0.021
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
232406W1-004 FULL
Solar/Wind Helper
0.493
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.301
219612MATRIX C
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.481
20716928W4-060COL
Solar/Wind Helper
0.05
957471AF2-041 GEN
Solar/Wind Harmer
13.123
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
TVALTFEXP_TVA->PJM
CLTF
6.984
NYPJM->LTFIMP_NY
CLTF
4.644
LGEELTFEXP_LGEE->PJM
CLTF
6.478
WECLTFEXP_WEC->PJM
CLTF
3.676
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345
CPLELTFEXP_CPLE->PJM
CLTF
0.539
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
MECLTFEXP_MEC->PJM
CLTF
15.273
SIGELTFEXP_SIGE->PJM
CLTF
0.485

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o PN_P1-1_PN-230-018_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
PN_P1-1_PN-230-018_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.66 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:155.73
MW Contribution:
6.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
203859AF2-294 C
Solar/Wind Harmer
0.513
972191AH1-680 GEN
Adder
6.656
970935AG2-582 GEN
Adder
6.784
941421AE2-139 GEN
Solar/Wind Helper
2.971
20083926HOMER C3
Adder
15.349
20083826HOMER C2
Adder
14.498
20083726HOMER C1
Adder
9.087
200917MEHOOPANY_G
Solar/Wind Helper
1.991
LAGNLTFEXP_LAGN->PJM
CLTF
0.624
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.727
TVALTFEXP_TVA->PJM
CLTF
0.309
LGEELTFEXP_LGEE->PJM
CLTF
0.234
WECLTFEXP_WEC->PJM
CLTF
0.134
CPLELTFEXP_CPLE->PJM
CLTF
0.233
CBM NorthLTFEXP_CBM-N->PJM
CBM
17.816
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.354
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.356
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.182
MECLTFEXP_MEC->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o PN_P1-1_PN-230-017_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
PN_P1-1_PN-230-017_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.66 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:155.73
MW Contribution:
6.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
203859AF2-294 C
Solar/Wind Harmer
0.513
972191AH1-680 GEN
Adder
6.656
970935AG2-582 GEN
Adder
6.784
941421AE2-139 GEN
Solar/Wind Helper
2.971
20083926HOMER C3
Adder
15.349
20083826HOMER C2
Adder
14.498
20083726HOMER C1
Adder
9.087
200917MEHOOPANY_G
Solar/Wind Helper
1.991
LAGNLTFEXP_LAGN->PJM
CLTF
0.624
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.727
TVALTFEXP_TVA->PJM
CLTF
0.309
LGEELTFEXP_LGEE->PJM
CLTF
0.234
WECLTFEXP_WEC->PJM
CLTF
0.134
CPLELTFEXP_CPLE->PJM
CLTF
0.233
CBM NorthLTFEXP_CBM-N->PJM
CBM
17.816
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.354
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.356
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.182
MECLTFEXP_MEC->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o PN_P2-3_PN-115-84A1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-115-84A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.69 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:134.0
MW Contribution:
8.18
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
20398826ARMNA MT
Solar/Wind Helper
2.272
941421AE2-139 GEN
Solar/Wind Helper
3.566
203859AF2-294 C
Solar/Wind Harmer
0.75
972191AH1-680 GEN
Adder
7.967
970935AG2-582 GEN
Adder
8.182
20083926HOMER C3
Adder
18.903
20083826HOMER C2
Adder
17.856
20083726HOMER C1
Adder
11.181
200917MEHOOPANY_G
Solar/Wind Helper
2.406
LAGNLTFEXP_LAGN->PJM
CLTF
0.749
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.875
TVALTFEXP_TVA->PJM
CLTF
0.371
LGEELTFEXP_LGEE->PJM
CLTF
0.281
WECLTFEXP_WEC->PJM
CLTF
0.161
CPLELTFEXP_CPLE->PJM
CLTF
0.281
CBM NorthLTFEXP_CBM-N->PJM
CBM
19.554
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.226
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.419
MECLTFEXP_MEC->PJM
CLTF
0.689
SIGELTFEXP_SIGE->PJM
CLTF
0.021

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o PN_P2-3_PN-115-84D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-115-84D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.69 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:134.0
MW Contribution:
8.18
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
20398826ARMNA MT
Solar/Wind Helper
2.272
941421AE2-139 GEN
Solar/Wind Helper
3.566
203859AF2-294 C
Solar/Wind Harmer
0.75
972191AH1-680 GEN
Adder
7.967
970935AG2-582 GEN
Adder
8.182
20083926HOMER C3
Adder
18.903
20083826HOMER C2
Adder
17.856
20083726HOMER C1
Adder
11.181
200917MEHOOPANY_G
Solar/Wind Helper
2.406
LAGNLTFEXP_LAGN->PJM
CLTF
0.749
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.875
TVALTFEXP_TVA->PJM
CLTF
0.371
LGEELTFEXP_LGEE->PJM
CLTF
0.281
WECLTFEXP_WEC->PJM
CLTF
0.161
CPLELTFEXP_CPLE->PJM
CLTF
0.281
CBM NorthLTFEXP_CBM-N->PJM
CBM
19.554
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.226
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.419
MECLTFEXP_MEC->PJM
CLTF
0.689
SIGELTFEXP_SIGE->PJM
CLTF
0.021

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o PN_P2-2_PN-345-1154-W_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-345-1154-W_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.14 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:133.29
MW Contribution:
7.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
Adder
18.011
20083826HOMER C2
Adder
17.014
20083726HOMER C1
Adder
10.621
200917MEHOOPANY_G
Solar/Wind Helper
2.229
941421AE2-139 GEN
Solar/Wind Helper
3.345
20398826ARMNA MT
Solar/Wind Helper
1.624
203859AF2-294 C
Solar/Wind Harmer
0.816
972191AH1-680 GEN
Adder
7.471
970935AG2-582 GEN
Adder
7.698
LAGNLTFEXP_LAGN->PJM
CLTF
0.704
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.823
TVALTFEXP_TVA->PJM
CLTF
0.349
LGEELTFEXP_LGEE->PJM
CLTF
0.264
WECLTFEXP_WEC->PJM
CLTF
0.151
CPLELTFEXP_CPLE->PJM
CLTF
0.265
CBM NorthLTFEXP_CBM-N->PJM
CBM
19.942
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.908
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.02
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.333
MECLTFEXP_MEC->PJM
CLTF
0.647
SIGELTFEXP_SIGE->PJM
CLTF
0.02
CONTINGENCY 'AP_P2-3_MP-500-012_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1   /*01HARRSN     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235703 CKT 1   /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P2-3_MP-500-018_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1          /*01HARRSN     500.0 - 01FLINTRUN   500.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235111 CKT 1 /*01HARRSN     500.0 - 01 502 J     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235112 CKT 1 /*01HARRSN     500.0 - 01PRNTY      500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235111 CKT 1 /*01HARRSN     500.0 - 01 502 J     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235112 CKT 1 /*01HARRSN     500.0 - 01PRNTY      500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT4_SRT-SL'
 OPEN BRANCH FROM BUS 235107 TO BUS 235235 CKT 1                /*01HARRSN     500.0 - 01FLINTRUN   500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235111 CKT 1 /*01HARRSN     500.0 - 01 502 J     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235111 CKT 1 /*01HARRSN     500.0 - 01 502 J     500.0
END
CONTINGENCY 'AP_P2-3_MP-500-017_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
CONTINGENCY 'AP_P2-3_MP-500-016_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
CONTINGENCY 'AP_P2-3_PE-500-014_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235103 TO BUS 964990 CKT 1          /*01BLACKO     500.0 - AG1-363 TP   500.0
 REDUCE BUS 235103 SHUNT BY 50 PERCENT                          /*01BLACKO     500.0
 SET POSTCONTRATING 2771 BRANCH FROM BUS 235101 TO BUS 235103 CKT 1 /*01BEDNGT     500.0 - 01BLACKO     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235101 TO BUS 235103 CKT 1 /*01BEDNGT     500.0 - 01BLACKO     500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT19_SRT-SL'
 OPEN BRANCH FROM BUS 235108 TO BUS 964990 CKT 1                /*01HATFLD     500.0 - AG1-363 TP   500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235774 CKT 1 /*01HATFLD     500.0 - 01RONCO      500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235774 CKT 1 /*01HATFLD     500.0 - 01RONCO      500.0
END
CONTINGENCY 'AP_P1-2_PE-500-004_SRT-SL-2'
 DISCONNECT BRANCH FROM BUS 964990 TO BUS 235103 CKT 1   /*AG1-363 TP   500.0 - 01BLACKO     500.0
END
CONTINGENCY 'AP_P1-2_PE-500-004_SRT-SL-1'
 DISCONNECT BRANCH FROM BUS 235108 TO BUS 964990 CKT 1   /*01HATFLD     500.0 - AG1-363 TP   500.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT9_SRT-SL'
 OPEN BRANCH FROM BUS 235774 TO BUS 235108 CKT 1                /*01RONCO      500.0 - 01HATFLD     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235106 TO BUS 235774 CKT 1 /*01FMARTN     500.0 - 01RONCO      500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235106 TO BUS 235774 CKT 1 /*01FMARTN     500.0 - 01RONCO      500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT22_SRT-SL'
 OPEN BRANCH FROM BUS 235108 TO BUS 235774 CKT 1                /*01HATFLD     500.0 - 01RONCO      500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 964990 CKT 1 /*01HATFLD     500.0 - AG1-363 TP   500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 964990 CKT 1 /*01HATFLD     500.0 - AG1-363 TP   500.0
END
CONTINGENCY 'AP_P2-3_MP-138-206_SRT-A'
 DISCONNECT BRANCH FROM BUS 235106 TO BUS 235774 CKT 1   /*01FMARTN     500.0 - 01RONCO      500.0
 DISCONNECT BRANCH FROM BUS 235108 TO BUS 235774 CKT 1   /*01HATFLD     500.0 - 01RONCO      500.0
 DISCONNECT BRANCH FROM BUS 235755 TO BUS 235774 CKT 1   /*01RONCO1      18.0 - 01RONCO      500.0
 DISCONNECT BRANCH FROM BUS 235756 TO BUS 235774 CKT 1   /*01RONCO2      18.0 - 01RONCO      500.0
 DISCONNECT BRANCH FROM BUS 235757 TO BUS 235774 CKT 1   /*01RONCO3      18.0 - 01RONCO      500.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT11_SRT-SL'
 OPEN BRANCH FROM BUS 235774 TO BUS 235106 CKT 1                /*01RONCO      500.0 - 01FMARTN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235774 TO BUS 235108 CKT 1 /*01RONCO      500.0 - 01HATFLD     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235774 TO BUS 235108 CKT 1 /*01RONCO      500.0 - 01HATFLD     500.0
END
CONTINGENCY 'AEP_P4_#8975_05KAMMER 765_MM2_SRT-A'
 OPEN BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT7A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT10A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235111 TO BUS 235113 CKT 2                /*01 502 J     500.0 - 01 502JCT    138.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-2_MP-500-007_SRT-SL'
 SET POSTCONTRATING 2811 BRANCH FROM BUS 235235 TO BUS 235107 CKT 1 /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235111 CKT 1 /*01HARRSN     500.0 - 01 502 J     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235112 CKT 1 /*01HARRSN     500.0 - 01PRNTY      500.0
 SET PRECONTRATING 2179 BRANCH FROM BUS 235235 TO BUS 235107 CKT 1 /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235111 CKT 1 /*01HARRSN     500.0 - 01 502 J     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235112 CKT 1 /*01HARRSN     500.0 - 01PRNTY      500.0
END
CONTINGENCY 'AP_P2-2_MP-138-013_SRT-A'
 DISCONNECT BRANCH FROM BUS 235334 TO BUS 235349 CKT 1   /*01GLENFL     138.0 - 01HARR T     138.0
 DISCONNECT BRANCH FROM BUS 235334 TO BUS 235375 CKT 1   /*01GLENFL     138.0 - 01NATLCN     138.0
 DISCONNECT BRANCH FROM BUS 235334 TO BUS 235442 CKT 1   /*01GLENFL     138.0 - 01MCALPN     138.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT6_SRT-SL'
 OPEN BRANCH FROM BUS 235111 TO BUS 235107 CKT 1                /*01 502 J     500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT9_SRT-SL'
 OPEN BRANCH FROM BUS 235111 TO BUS 235107 CKT 1                /*01 502 J     500.0 - 01HARRSN     500.0
 OPEN BRANCH FROM BUS 235111 TO BUS 235113 CKT 2                /*01 502 J     500.0 - 01 502JCT    138.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-2_MP-500-022_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235111 CKT 1   /*01HARRSN     500.0 - 01 502 J     500.0
END
CONTINGENCY 'PN_P1-1_PN-230-018_SRT-A'
 REMOVE MACHINE 1 FROM BUS 203923   /*AA1-082 G2    23.0
END
CONTINGENCY 'PN_P1-1_PN-230-017_SRT-A'
 REMOVE MACHINE 1 FROM BUS 203922   /*AA1-082 G1    23.0
END
CONTINGENCY 'PN_P2-3_PN-115-84A1_SRT-A'
 DISCONNECT BRANCH FROM BUS 200929 TO BUS 200672 CKT 1   /*26MAINESBURG 115.0 - 26MANSFIEL   115.0
 DISCONNECT BRANCH FROM BUS 200930 TO BUS 200929 CKT 1   /*26MAINESBURG 345.0 - 26MAINESBURG 115.0
END
CONTINGENCY 'PN_P2-3_PN-115-84D1_SRT-A'
 DISCONNECT BRANCH FROM BUS 200929 TO BUS 200885 CKT 1   /*26MAINESBURG 115.0 - 26EVERT DR   115.0
 DISCONNECT BRANCH FROM BUS 200930 TO BUS 200929 CKT 1   /*26MAINESBURG 345.0 - 26MAINESBURG 115.0
END
CONTINGENCY 'PN_P2-2_PN-345-1154-W_SRT-A'
 DISCONNECT BRANCH FROM BUS 200930 TO BUS 200929 CKT 1   /*26MAINESBURG 345.0 - 26MAINESBURG 115.0
 REMOVE SWSHUNT FROM BUS 200930 BLOCK 1 STEP 1           /*26MAINESBURG 345.0
 REMOVE SWSHUNT FROM BUS 200930 BLOCK 2 STEP 1           /*26MAINESBURG 345.0
END
235473 to 235527 ckt 1
235550 to 237506 ckt 1
235306 to 235473 ckt 1
235235 to 235100 ckt 1
235235 to 235100 ckt 2
235235 to 235107 ckt 1
235334 to 235306 ckt 1
235334 to 235442 ckt 1
235107 to 235112 ckt 1
235117 to 235111 ckt 1
235492 to 235550 ckt 1
235527 to 235391 ckt 1
242925 to 235117 ckt 1
130836 to 200676 ckt 1

Winter Peak Analysis

The New Service Request AG2-582 was evaluated as a 2100.0 MW (2075.0 MW Capacity) injection in the APS area.

AG2-582 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 2100.0 MW (2100.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-017_SRT-A
BreakerAC127.75 %578.0B738.41
337.38
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-017_SRT-A
BreakerAC121.06 %578.0B699.7
337.38
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-016_SRT-A
BreakerAC127.75 %578.0B738.41
337.38
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-016_SRT-A
BreakerAC121.06 %578.0B699.7
337.38

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-017_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.75 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:738.41
MW Contribution:
337.38
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.77 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:830.99
MW Contribution:
344.06
Bus #Bus NameTypeMW Contribution
23751201ROTHROCK
Solar/Wind Helper
0.715
23562501BACKB
Solar/Wind Helper
0.971
23751101LEADS_P59
Solar/Wind Helper
2.129
970935AG2-582 GEN
50/50
337.38
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.285
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.468
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.928
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.76
NYPJM->LTFIMP_NY
CLTF
0.472
LGEELTFEXP_LGEE->PJM
CLTF
0.698
WECLTFEXP_WEC->PJM
CLTF
0.389
CPLELTFEXP_CPLE->PJM
CLTF
0.084
TVALTFEXP_TVA->PJM
CLTF
0.728
MECLTFEXP_MEC->PJM
CLTF
1.615
LAGNLTFEXP_LAGN->PJM
CLTF
1.486
SIGELTFEXP_SIGE->PJM
CLTF
0.052

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-017_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.06 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:699.7
MW Contribution:
337.38
IPD Plant:AG2-582
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.65 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:778.26
MW Contribution:
344.06
IPD Plant:AG2-582
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
337.38

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-016_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.75 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:738.41
MW Contribution:
337.38
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.77 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:830.99
MW Contribution:
344.06
Bus #Bus NameTypeMW Contribution
23751201ROTHROCK
Solar/Wind Helper
0.715
23562501BACKB
Solar/Wind Helper
0.971
23751101LEADS_P59
Solar/Wind Helper
2.129
970935AG2-582 GEN
50/50
337.38
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.285
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.468
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.928
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.76
NYPJM->LTFIMP_NY
CLTF
0.472
LGEELTFEXP_LGEE->PJM
CLTF
0.698
WECLTFEXP_WEC->PJM
CLTF
0.389
CPLELTFEXP_CPLE->PJM
CLTF
0.084
TVALTFEXP_TVA->PJM
CLTF
0.728
MECLTFEXP_MEC->PJM
CLTF
1.615
LAGNLTFEXP_LAGN->PJM
CLTF
1.486
SIGELTFEXP_SIGE->PJM
CLTF
0.052

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-016_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.06 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:699.7
MW Contribution:
337.38
IPD Plant:AG2-582
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.65 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:778.26
MW Contribution:
344.06
IPD Plant:AG2-582
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
337.38
CONTINGENCY 'AP_P2-3_MP-500-017_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
CONTINGENCY 'AP_P2-3_MP-500-016_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
235235 to 235100 ckt 1
235235 to 235100 ckt 2

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AG2-582 was evaluated as a 2100.0 MW injection

AG2-582 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 2100.0 MW (2100.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-017_SRT-A
BreakerAC108.98 %527.0B574.34
333.62
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-016_SRT-A
BreakerAC108.98 %527.0B574.34
333.62

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-017_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.98 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:574.34
MW Contribution:
333.62
IPD Plant:AG2-582
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.99 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:648.18
MW Contribution:
339.79
IPD Plant:AG2-582
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
333.623

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-016_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.98 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:574.34
MW Contribution:
333.62
IPD Plant:AG2-582
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.99 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:648.18
MW Contribution:
339.79
IPD Plant:AG2-582
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
333.623
CONTINGENCY 'AP_P2-3_MP-500-017_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
CONTINGENCY 'AP_P2-3_MP-500-016_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
235235 to 235100 ckt 1
235235 to 235100 ckt 2

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-017_SRT-A
BreakerAC133.09 %527.0B701.37
183.96
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-016_SRT-A
BreakerAC133.09 %527.0B701.37
183.96

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-017_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.09 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:701.37
MW Contribution:
183.96
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23751201ROTHROCK
Solar/Wind Helper
0.708
23562501BACKB
Solar/Wind Helper
0.96
23751101LEADS_P59
Solar/Wind Helper
2.061
970935AG2-582 GEN
50/50
183.962
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.85
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.012
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.203
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.61
NYPJM->LTFIMP_NY
CLTF
0.646
LGEELTFEXP_LGEE->PJM
CLTF
0.956
WECLTFEXP_WEC->PJM
CLTF
0.517
CPLELTFEXP_CPLE->PJM
CLTF
0.293
TVALTFEXP_TVA->PJM
CLTF
1.062
MECLTFEXP_MEC->PJM
CLTF
2.182
LAGNLTFEXP_LAGN->PJM
CLTF
2.165
SIGELTFEXP_SIGE->PJM
CLTF
0.071
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.994

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-016_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.09 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:701.37
MW Contribution:
183.96
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23751201ROTHROCK
Solar/Wind Helper
0.708
23562501BACKB
Solar/Wind Helper
0.96
23751101LEADS_P59
Solar/Wind Helper
2.061
970935AG2-582 GEN
50/50
183.962
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.85
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.012
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.203
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.61
NYPJM->LTFIMP_NY
CLTF
0.646
LGEELTFEXP_LGEE->PJM
CLTF
0.956
WECLTFEXP_WEC->PJM
CLTF
0.517
CPLELTFEXP_CPLE->PJM
CLTF
0.293
TVALTFEXP_TVA->PJM
CLTF
1.062
MECLTFEXP_MEC->PJM
CLTF
2.182
LAGNLTFEXP_LAGN->PJM
CLTF
2.165
SIGELTFEXP_SIGE->PJM
CLTF
0.071
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.994
CONTINGENCY 'AP_P2-3_MP-500-017_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
CONTINGENCY 'AP_P2-3_MP-500-016_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
235235 to 235100 ckt 1
235235 to 235100 ckt 2

Short Circuit Analysis

Short Circuit Analysis is complete and an overduty has been identified. TC2 project AG2-582 is contributing to the overduty in Glen Falls BarnetR406, which exceeds the >1% threshold per PJM Manual 14H 4.2.3.1.

An existing network upgrade, N4854, upgrades the overdutied breaker. AG2-582 is contingent on this upgrade.

 

Below is the duty impact analysis.

 

Bus Name

Bus Number

Project ID

Breaker Overdutied

Breaker Capacity (Amps)

Duty Percent With TC2 (%)

Duty Amps With TC2 (Amps)

Full Amps Contribution (Amps)

Reinforcement ID

Reinforcement Project Description

GLEN FALLS 138.kV

235334

AG2-582

BarnetR406

20189.2

173.91%

35111.3

231

N4854

Replace the Buckhannon 50, Barnetts Run 406, Oak Mound 4, No. 1 & No. 4 transf. and 138 kV Bust tie breakers with 63 kA, 3000 A units. Install 3 new foundations, 4 switches, cable trench, control cable and all associated facilities.

 

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

 

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 2, Cluster 73 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 73 projects.

This analysis is effectively a screening study to determine whether the addition of the Cluster 73 projects will meet the dynamics requirements of the NERC, FE-APS, and PJM reliability standards.

The load flow scenario for the analysis was based on the 2028 light load case, modified to include applicable projects. Cluster 73 projects have been dispatched online at maximum power output, with approximately unity power factors at the high side of the GSUs, 1.00 pu voltage at the generator terminals, and 1.05 pu voltage at the POI bus.

Cluster 73 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 168 contingencies were studied, each with a 20 second simulation time period (with 1.0 second initial run prior to any events). Studied faults included:

  1. Steady-state operation (Category P0);
  2. Three-phase faults with normal clearing time (Category P1);
  3. Single-phase faults with stuck breaker (Category P4);
  4. Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (Category P5);
  5. Single-phase to ground faults with normal clearing for common structure (Category P7).

Multiple-circuit tower line faults were identified for this study.

High Speed Reclosing (HSR) facilities were found in the vicinity of TC1 Cluster 73 projects.

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

For all of the fault contingencies tested on the 2028 light load case:

  1. Cluster 73 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  2. The system with Cluster 73 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.
  3. Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).
  4. No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

No mitigations were found to be required for TC2 Cluster 73.

Table 1: TC2 Cluster 73 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

73

AG2-582

Natural Gas

FirstEnergy (FE) transmission system,

APS zone

2100 MW

2100 MW

2075 MW

Flint Run 500 kV

 

Reactive Power Analysis

The reactive power capability of AG2-582 meets the 0.9 lagging and 0.95 leading PF requirement at the generator terminals.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

(No dependencies were identified)

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
NYISO
RTEP ID / TO ID
(Pending) / NYISO_CY17_13387
Title
East Sayre-North Waverly 115kV line upgrade - NYSEG (NYISO CY17 driven upgrade)
Description
North Waverly terminal equipment upgrades and a line reconductor of the NYSEG portion of the East Sayre – North Waverly 115kV line. (Install approximately twenty-six (26) new steel pole structures, one (1) 795 kcmil (26/7) ACSR conductor, and 36 Fiber OPGW). Final expected SUM ratings with both NYSEG & Penelec work complete = 218/251 MVA SN/SE. NYSEG uses LTE for Rate B, not STE like FirstEnergy. The projected in-service date for this project is in late 2026, but that timeframe may shift to complete the terminal equipment work at North Waverly. The final trip setting for the line will be updated during engineering and construction, but it must meet at least 176 MVA. Note: NYISO customers Q387, Q421, Q505 require an upgrade on the East Sayre-North Waverly 115 kV line as part of the CY17 study. NYSEG will complete work at North Waverly substation and the line reconductor/rebuild. FirstEnergy will complete work at East Sayre substation. Per NYISO, the rating that must be achieved for CY17 is 176/176/176 MVA Summer Normal/LTE/STE. NYSEG confirmed the new line ratings for the NYISO side (218/251/282 MVA Summer Normal/LTE/STE; 265/291/318 MVA Winter Normal/LTE/STE), but the East Sayre terminal needs to be upgraded since it is limiting. NYSEG uses LTE for Rate B, not STE like FirstEnergy.
Total Cost ($USD)
$10,525,000
Allocated Cost ($USD)
$0
Time Estimate
32 Months

Info

Note: AG2-582 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line(Any)

Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG2-582 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
APSn9735.0Replace 500/138 kV TR1 with (3) Single Phase 500/138 kV TRs at Flint Run.Cost Allocated$32,119,007N/A
APSn9733.0Replace 500/138 kV TR2 with (3) Single Phase 500/138 kV TRs at Flint Run.Cost Allocated$32,119,007N/A
APSn9737.0Replace 6 138 kV Disc Switches and 5 Breaker Leads at Flint RunCost Allocated$1,826,164N/A
APSn9736.0Replace 6 138 kV Disc Switches and 5 Breaker Leads at Flint RunCost Allocated$1,826,164N/A
APSn9738.0Replace SCCIR 3" Pipe A-frame closest to Disc SW A-39Cost Allocated$597,737N/A
APSn4854Glen Falls SS: Circuit Breaker ReplacementsContingent$0N/A
APSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Contingent$0N/A
AEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationContingent$0N/A
APSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Contingent$0N/A
APSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Contingent$0N/A
APSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardContingent$0N/A
PENELECn8471East Sayre-North Waverly 115kV line upgrade - FirstEnergy (NYISO CY17 driven upgrade)Contingent$0N/A
Grand Total:$68,488,079

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n4854
Type
Short Circuit
TO
APS
RTEP ID / TO ID
n4854
Title
Glen Falls SS: Circuit Breaker Replacements
Description
Glen Falls SS. Replace the Buckhannon 50, Barnetts Run 406, Oak Mound 4, No. 1 & No. 4 transf. and 138 kV Bust tie breakers with 63 kA, 3000 A units. Install 3 new foundations, 4 switches, cable trench, control cable and all all associated facilities. Replacements are driven by AA2-119 due to overduties identified in their SIS report.
Total Cost ($USD)
$1,920,000
Discounted Total Cost ($USD)
$1,920,000
Allocated Cost ($USD)
$0
Time Estimate
TBD

Contingent

Note: Based on PJM cost allocation criteria, AG2-582 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-582 may not have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.


System Reinforcement: n9735.0
Type
Load Flow
TO
APS
RTEP ID / TO ID
n9735.0 / TC2-APS-016.a
Title
Replace 500/138 kV TR1 with (3) Single Phase 500/138 kV TRs at Flint Run.
Description
Replace 500/138 kV TR1 at Flint Run. An assessment was made on reconfiguration/expansion options at Flint Run substation to accomodate the AG2-582 interconnection and any changes to address stuck breaker contingencies. Due to the substation location/space constraints, the Flint Run 500/138kV transformer replacements are the only option while still being able to accomodate the AG2-582 interconnection into the 500kV yard.
Total Cost ($USD)
$32,119,007
Discounted Total Cost ($USD)
$32,119,007
Allocated Cost ($USD)
$32,119,007
Time Estimate
80 Months

Contributor

FacilityContingency
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A548.0 MVA
(All)B688.0 MVA
(All)C727.0 MVA
WINA710.0 MVA
WINB790.0 MVA
WINC819.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582337.4 MW100.0%$32,119,007

System Reinforcement: n9733.0
Type
Load Flow
TO
APS
RTEP ID / TO ID
n9733.0 / TC2-APS-015.a
Title
Replace 500/138 kV TR2 with (3) Single Phase 500/138 kV TRs at Flint Run.
Description
Replace 500/138 kV TR2 at Flint Run. An assessment was made on reconfiguration/expansion options at Flint Run substation to accomodate the AG2-582 interconnection and any changes to address stuck breaker contingencies. Due to the substation location/space constraints, the Flint Run 500/138kV transformer replacements are the only option while still being able to accomodate the AG2-582 interconnection into the 500kV yard.
Total Cost ($USD)
$32,119,007
Discounted Total Cost ($USD)
$32,119,007
Allocated Cost ($USD)
$32,119,007
Time Estimate
80 Months

Contributor

FacilityContingency
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 2 transformer(Any)
Rating SetRating TypeRating Value
(All)A548.0 MVA
(All)B688.0 MVA
(All)C727.0 MVA
WINA710.0 MVA
WINB790.0 MVA
WINC819.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582337.4 MW100.0%$32,119,007

System Reinforcement: n9737.0
Type
Load Flow
TO
APS
RTEP ID / TO ID
n9737.0 / TC2-APS-016.b
Title
Replace 6 138 kV Disc Switches and 5 Breaker Leads at Flint Run
Description
Replace 6 138 kV Disc Switches and 5 Breaker Leads at Flint Run
Total Cost ($USD)
$1,826,164
Discounted Total Cost ($USD)
$1,826,164
Allocated Cost ($USD)
$1,826,164
Time Estimate
24 Months

Contributor

FacilityContingency
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A601.0 MVA
(All)B776.0 MVA
(All)C855.0 MVA
WINA795.0 MVA
WINB913.0 MVA
WINC976.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582337.4 MW100.0%$1,826,164

System Reinforcement: n9736.0
Type
Load Flow
TO
APS
RTEP ID / TO ID
n9736.0 / TC2-APS-015.b
Title
Replace 6 138 kV Disc Switches and 5 Breaker Leads at Flint Run
Description
Replace 6 138 kV Disc Switches and 5 Breaker Leads at Flint Run
Total Cost ($USD)
$1,826,164
Discounted Total Cost ($USD)
$1,826,164
Allocated Cost ($USD)
$1,826,164
Time Estimate
24 Months

Contributor

FacilityContingency
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 2 transformer(Any)
Rating SetRating TypeRating Value
(All)A747.0 MVA
(All)B900.0 MVA
(All)C1034.0 MVA
WINA907.0 MVA
WINB1054.0 MVA
WINC1212.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582337.4 MW100.0%$1,826,164

System Reinforcement: n9738.0
Type
Load Flow
TO
APS
RTEP ID / TO ID
n9738.0 / TC2-APS-016.c
Title
Replace SCCIR 3" Pipe A-frame closest to Disc SW A-39
Description
Replace SCCIR 3" Pipe A-frame closest to Disc SW A-39
Total Cost ($USD)
$597,737
Discounted Total Cost ($USD)
$597,737
Allocated Cost ($USD)
$597,737
Time Estimate
18 Months

Contributor

FacilityContingency
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A747.0 MVA
(All)B900.0 MVA
(All)C1034.0 MVA
WINA907.0 MVA
WINB1054.0 MVA
WINC1192.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582337.4 MW100.0%$597,737

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01GLENFL-01MCALPN 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01GLENFL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01BARNET 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01PRNTY-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BARNET-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
01MTZION-01BERYL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01GLENFL-01MCALPN 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01GLENFL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01BARNET 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01PRNTY-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BARNET-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
01MTZION-01BERYL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01GLENFL-01MCALPN 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01GLENFL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01BARNET 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01PRNTY-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BARNET-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
01MTZION-01BERYL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01GLENFL-01MCALPN 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01GLENFL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01BARNET 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01PRNTY-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BARNET-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
01MTZION-01BERYL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01GLENFL-01MCALPN 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01GLENFL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01BARNET 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01PRNTY-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BARNET-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
01MTZION-01BERYL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01GLENFL-01MCALPN 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01GLENFL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01BARNET 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01PRNTY-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BARNET-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
01MTZION-01BERYL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01GLENFL-01MCALPN 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01GLENFL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01BARNET 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01PRNTY-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BARNET-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
01MTZION-01BERYL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01GLENFL-01MCALPN 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01GLENFL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01BARNET 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01PRNTY-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BARNET-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
01MTZION-01BERYL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01GLENFL-01MCALPN 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01GLENFL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01BARNET 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01PRNTY-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BARNET-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
01MTZION-01BERYL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01GLENFL-01MCALPN 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01GLENFL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01BARNET 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01PRNTY-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BARNET-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
01MTZION-01BERYL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01GLENFL-01MCALPN 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01GLENFL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BRIDGP-01BARNET 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01PRNTY-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BARNET-01SHINNS 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
01MTZION-01BERYL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: s3191.1
Type
Load Flow
TO
APS
RTEP ID / TO ID
s3191.1 / APS-2023-056
Title
Harrison – Pruntytown 500 kV Misoperation Relays (Projected ISD by end of 2025)
Description
- Replace wave trap, line metering and relaying at Harrison Substation- - Replace wave trap, line metering and relaying at Pruntytown Substation
Cost Information
Time Estimate
Dec 31 2024

Not Contingent

Note: AG2-582 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AG2-582 is not contingent on this supplemental project as it is already in-service.

FacilityContingency
01HARRSN-01PRNTY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3573.0 MVA
(All)B4379.0 MVA
(All)C4973.0 MVA
WINA4050.0 MVA
WINB5194.0 MVA
WINC5640.0 MVA

System Reinforcement: n8471
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n8471
Title
East Sayre-North Waverly 115kV line upgrade - FirstEnergy (NYISO CY17 driven upgrade)
Description
East Sayre Substation: Replace one (1) 115 kV circuit breaker on North Waverly (NYSEG) terminal at East Sayre. Revise wiring for the North Waverly 115kV PR and BU line protection relays to utilize the redundant CT’s and trip coils on the new breaker. East Sayre – North Waverly 115kV line: Replace 3 pole wood Structure 141 due to NYSEG reconductor of East Sayre-North Waverly 115kV line. Enable load encroachment such that all protection elements will achieve the required loadability of 221/263/263/301 MVA (SN/SE/WN/WE) Note: NYISO customers Q387, Q421, Q505 require an upgrade on the East Sayre-North Waverly 115 kV line as part of the CY17 study. NYSEG will complete work at North Waverly substation and the line reconductor/rebuild. FirstEnergy will complete work at East Sayre substation. Per NYISO, the rating that must be achieved for CY17 is 176/176/176 MVA Summer Normal/LTE/STE. NYSEG confirmed the new line ratings for the NYISO side (218/251/282 MVA Summer Normal/LTE/STE; 265/291/318 MVA Winter Normal/LTE/STE), but the East Sayre terminal is still limiting. Once the scope of work and ratings at East Sayre are finalized, the expected line ratings will be updated. NYSEG uses LTE for Rate B, not STE like FirstEnergy.
Total Cost ($USD)
$1,417,388
Discounted Total Cost ($USD)
$1,417,388
Allocated Cost ($USD)
$0
Time Estimate
Nov 01 2027

Contingent

Note: Based on PJM cost allocation criteria, AG2-582 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-582 could receive cost allocation. Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A218.0 MVA
(All)B251.0 MVA
(All)C276.0 MVA
WINA263.0 MVA
WINB291.0 MVA
WINC312.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-582


AG2-582 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowAPSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationTopology-0.0%Contingent$0
Load FlowAPSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Topology-0.0%Contingent$0
Load FlowAPSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Topology-0.0%Contingent$0
Load FlowAPSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardTopology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-582 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-582 One Line Diagram

AG2-582 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.