AH1-721 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:29

Laurel-Cooper 161 kV

758.9507 MW Capacity / 786.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is East Kentucky Power Cooperative, Inc., and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is East Kentucky Power Cooperative, Inc..

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $91,867,999 $108,174,888 = 0.85 AND ( $91,867,999 - $108,174,888 ) 786.0 = $-20,747 per MW

General

The Project Developer has proposed a Natural Gas generating facility located in the East Kentucky Power Cooperative, Inc. zone — Not Specified County, Kentucky. The installed facilities will have a total capability of 786.0 MW with 758.9507 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-721
Project Name:
Laurel-Cooper 161 kV
Project Developer Name:
East Kentucky Power Cooperative, Inc.
State:
Kentucky
County:
Not Specified
Transmission Owner:
East Kentucky Power Cooperative, Inc.
MFO:
786.0
MWE:
786.0
MWC:
758.9507
Fuel Type:
Natural Gas
Basecase Study Year:
2028

Capacity Interconnection Rights (CIR) Transfer Details

This project intends to claim and transfer CIRs from the following Deactivation capacity generation resources. PJM performed a reliability analysis of the impacts to the system capability for the proposed transfer of CIRs from the Deactivation generation resources.

Unit NameStatusCIR ClaimedPOI Transfer
Cooper 1Future Deactivation116.0Yes

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AH1-721 will interconnect on the East Kentucky Power Cooperative, Inc. transmission system tapping the Laurel - Cooper 161 kV line .

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-721 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-721Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$1,600,832$0$0
Other Scope$0$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$21,583,244$21,583,244$21,583,244
Network Upgrades$8,243,486$8,243,486$8,243,486
System Reliability Network Upgrades
Steady State Thermal & Voltage$57,432,556$57,432,556$57,432,556
Transient Stability$508,152$508,152$508,152
Short Circuit$3,015,000$3,015,000$3,015,000
Transmission Owner Analysis
SubRegional$100,000$100,000$100,000
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$985,560$0$985,560
AFS - Non-PJM Violations$0$0$0
Total$93,468,831$90,882,438$91,867,999

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-721

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-721
Project ID: AH1-721
20% of cost allocation for Phase II Network Upgrades:(A) $18,176,488
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $10,211,658
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $7,964,830
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Loop the existing Cooper-Laurel Dam and Cooper-Denny 161 kV lines into the new East Cooper interconnection switching station.

$4,488,804$2,583,936$576,732$63,304$7,712,776$7,712,776
(Pending)

Revise remote end relay settings/relays at the existing Cooper substation.

$235,511$7,247$20,785$1,812$265,355$265,355
(Pending)

Revise remote end relay settings/relays at the existing Denny substation.

$235,511$7,247$20,785$1,812$265,355$265,355
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

East Cooper 161 kV Switching Station: Construct a new 161 kV switching station along the Cooper-Laurel Dam 161 kV line.

$10,006,398$9,726,108$1,665,769$184,969$21,583,244$21,583,244
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Three (3) 161 kV generator lead lines to include, but not limited to, installation of 161 kV breakers, line conductor from the GSU transformers to the bus position in the switchyard, and 161 kV metering equipment.

$852,139$611,771$123,287$13,635$1,600,832$1,600,832
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$31,427,562$31,427,562
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take 22 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

Transmission Owner Identified Network Impacts to Distribution Facilities

None


Transmission Owner Identified Network Impacts to Sub-Regional Facilities

The Transmission Owner identified network impacts to Sub-Regional facilities as follows:

Overloaded ElementContingencyRating [MVA]Final Cycle Loading %Contribution [MW]
243740 05MOREHE 69.0 - 243728 05HAYWAR 69.0 CKT 1 34541 34553_SRT-A
CONTINGENCY '34541 34553_SRT-A'  

  OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1                  /* 249581 08MELDAL 345.00 342838 7SPURLOCK 345.00

  OPEN BRANCH FROM BUS 253077 TO BUS 342838 CKT 1                  /* 253077 09STUART 345.00 342838 7SPURLOCK 345.00

END
48.0116.32 %5.61

Transmission Owner Identified System Reinforcements on Distribution Facilities

None


Transmission Owner Identified System Reinforcements on Sub-Regional Facilities
AH1-721 Transmission Owner Identified System Reinforcements Cost Breakdown:
TORTEP ID / TO IDTitleMW ImpactPercent AllocationAllocated Cost ($USD)
AEPn9794.0 / TC2-AEP-182Hayward - Morehead: Replace Sub conductor 4/0 CU at Hayward. Replace Sub cond 300 MCM CU 37 Str at Morehead.5.6 MW100.0%$100,000
Grand Total:$100,000
System Reinforcement
TORTEP ID / TO IDTitleTotal Cost
AEPn9794.0 / TC2-AEP-182Hayward - Morehead: Replace Sub conductor 4/0 CU at Hayward. Replace Sub cond 300 MCM CU 37 Str at Morehead.$100,000

Contributor

Description: Hayward - Morehead: Replace Sub conductor 4/0 CU at Hayward. Replace Sub cond 300 MCM CU 37 Str at Morehead.

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-7215.6 MW100.0%$100,000

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. EKPC interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-721 was evaluated as a 786.0 MW (758.9507 MW Capacity) injection in the EKPC area.

AH1-721 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 786.0 MW (786.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
AEP_P4_#9173_05BROADF 765_P_SRT-A
BreakerAC106.75 %392.0B418.48
22.11
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC103.15 %5523.0B5696.85
86.7
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC103.15 %5523.0B5696.85
86.7
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.46
86.7
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.46
86.7
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.16
86.7
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC102.09 %5523.0B5638.63
86.7
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC102.08 %5523.0B5637.94
86.7
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC300.71 %1180.0B3548.35
66.57
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC300.71 %1180.0B3548.35
66.57
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC300.69 %1180.0B3548.19
66.57
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC300.69 %1180.0B3548.19
66.57
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC300.69 %1180.0B3548.09
66.57
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC286.57 %1180.0B3381.47
66.57
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC286.54 %1180.0B3381.22
66.57
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC220.32 %1180.0B2599.75
59.85
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC220.32 %1180.0B2599.75
59.85
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC220.32 %1180.0B2599.75
59.85
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC220.3 %1180.0B2599.51
59.85
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC191.87 %1180.0B2264.12
52.94
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2114-535_SRT-A_SENS
TowerAC188.07 %1180.0B2219.28
50.71
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC184.05 %1180.0B2171.82
50.66
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P2-2: ALTAVISTA 138KV_SRT-A
BusAC183.75 %1180.0B2168.24
50.91
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Base Case
SingleAC180.03 %1180.0A2124.32
50.73
GD2AEP
05ELKGARDNSS-05SALTV1 138.0 kV Ckt 1 line
AEP_P4_#9173_05BROADF 765_P_SRT-A
BreakerAC100.83 %392.0B395.24
22.11
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC124.63 %4571.0B5696.85
86.7
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC124.63 %4571.0B5696.85
86.7
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.46
86.7
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.46
86.7
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.16
86.7
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC123.36 %4571.0B5638.63
86.7
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC123.34 %4571.0B5637.94
86.7
GD2AEP
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
AEP_P7-1_#10868___SRT-SL
TowerAC114.38 %361.0B412.91
18.66
GD2AEP
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
AEP_P4_#9173_05BROADF 765_P_SRT-A
BreakerAC113.39 %361.0B409.35
22.11
GD2AEP
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
AEP_P4_#1375_05BROADF 765_P2_SRT-A
BreakerAC103.51 %361.0B373.67
22.21
GD2AEP
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
AEP_P4_#11112_05J.FERR 765_A1_SRT-A
BreakerAC110.62 %296.0B327.42
15.55
GD2AEP
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
AEP_P4_#14149_05BROADF 765_Q2_SRT-A
BreakerAC103.73 %296.0B307.05
14.82
GD2AEP
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
AEP_P4_#2916_05J.FERR 765_A_SRT-A
BreakerAC103.45 %296.0B306.22
14.81
GD2AEP
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
AEP_P1-2_#2915_4_SRT-A
SingleAC103.16 %296.0B305.34
14.82
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#3149_05HANG R 765_B_SRT-A
BreakerAC143.94 %1540.0B2216.66
40.9
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC123.49 %1540.0B1901.76
38.37
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#1558_05BAKER 765_Q_SRT-A
BreakerAC121.58 %1540.0B1872.34
34.01
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#309_05HANG R 765_B2_SRT-A
BreakerAC121.32 %1540.0B1868.38
34.43
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#1560_05BAKER 765_Q2_SRT-A
BreakerAC121.04 %1540.0B1864.08
34.4
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#6156_05MARQUI 765_2_SRT-A
BusAC120.75 %1540.0B1859.53
40.88
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC108.24 %1540.0B1666.97
34.16
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
Base Case
SingleAC107.72 %1189.0A1280.85
33.6
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#6763_05BIERSR 345_2_SRT-A
BusAC106.64 %1540.0B1642.31
35.33
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#308_05CULLOD 765_1_SRT-A
BusAC106.58 %1540.0B1641.32
36.02
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P7-1_#11019___SRT-A-2
TowerAC106.15 %1540.0B1634.72
34.89
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
34569 34598 34524_SRT-A
TowerAC105.24 %1540.0B1620.65
35.2
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC104.94 %1540.0B1616.13
33.53
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT5_SRT-SL
BusAC103.91 %1540.0B1600.21
33.54
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#316_05AMOS 765_2_SRT-A
BusAC101.35 %1540.0B1560.82
33.6
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1014_SRT-A
BreakerAC145.54 %105.0B152.81
65.61
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1014_SRT-A
BreakerAC138.4 %105.0B145.32
69.62
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1024_SRT-A
BreakerAC130.4 %105.0B136.92
66.96
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1008_SRT-A
BreakerAC127.72 %105.0B134.1
78.93
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC127.72 %105.0B134.1
78.93
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1024_SRT-A
BreakerAC122.68 %105.0B128.81
71.05
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1008_SRT-A
BreakerAC121.08 %105.0B127.14
78.93
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC121.08 %105.0B127.14
78.93
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P4-6_COOP S42-1039_SRT-A_SENS
BreakerAC102.43 %105.0B107.55
66.37
GD2EKPC
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line
EKPC_P2-3_MAR W38-1014_SRT-A
BreakerAC105.07 %39.0B40.98
4.56
GD2EKPC
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line
EKPC_P2-3_SSHAD S11-1014_SRT-A
BreakerAC102.11 %39.0B39.82
7.98
GD2EKPC/LGEE
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
EKPC_P2-2_KU HODG 69_SRT-A
BusAC106.61 %50.0B53.3
8.93
GD2EKPC/LGEE
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
EKPC_P2-2_BARDIT-EBARD69_SRT-A
BusAC104.69 %50.0B52.34
6.87
GD2EKPC/LGEE
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
EKPC_P2-3_SSHAD S11-1014_SRT-A
BreakerAC101.27 %50.0B50.63
9.99
GD2EKPC/LGEE
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
EKPC_P2-3_SSHAD S11-1004_SRT-A-1
BreakerAC100.15 %50.0B50.07
9.66
GD2EKPC
2W LONDON-2W LONDON T 69.0 kV Ckt 1 line
EKPC_P2-3_TYNER E13-1014_SRT-A
BreakerAC122.46 %46.0B56.33
13.22
GD2EKPC
2W LONDON-2W LONDON T 69.0 kV Ckt 1 line
EKPC_P1-2_LAUR-PIT-TY161_SRT-A
SingleAC107.98 %46.0B49.67
15.07
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC196.67 %277.0B544.77
307.56
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC164.25 %277.0B454.97
307.56
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EXT_B-345-100_SRT-S
SingleAC132.74 %200.0B265.49
109.3
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EXT_B-345-100_SRT-S
SingleAC122.66 %200.0B245.32
109.3
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC118.86 %200.0B237.73
80.01
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Base Case
SingleAC118.22 %174.0A205.7
62.08
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Base Case
SingleAC112.72 %174.0A196.13
62.08
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1008_SRT-A
BreakerAC112.38 %200.0B224.75
93.41
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC112.38 %200.0B224.75
93.41
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1024_SRT-A
BreakerAC112.31 %200.0B224.62
94.16
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EXT_324100 7ALCALDE 345 324112 7PINEVILLE 345 1_SRT-S
SingleAC110.04 %200.0B220.08
69.79
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC109.9 %200.0B219.79
80.01
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1008_SRT-A
BreakerAC108.73 %200.0B217.47
93.41
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC108.73 %200.0B217.47
93.41
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1024_SRT-A
BreakerAC108.71 %200.0B217.42
94.16
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 1_SRT-A
TowerAC108.63 %200.0B217.26
78.63
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_PULASKI 161_SRT-A
BusAC107.71 %200.0B215.42
68.22
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 1_SRT-A
TowerAC105.12 %200.0B210.24
78.63
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EXT_324100 7ALCALDE 345 324112 7PINEVILLE 345 1_SRT-S
SingleAC105.0 %200.0B210.01
69.8
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_PULASKI 161_SRT-A
BusAC103.01 %200.0B206.03
68.22
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC103.42 %54.0B55.85
3.42
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC103.42 %54.0B55.85
3.42
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC103.0 %54.0B55.62
4.33
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
SingleAC102.16 %54.0B55.16
5.45
GD2AEP
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
AEP_P4_#11112_05J.FERR 765_A1_SRT-A
BreakerAC117.51 %296.0B347.84
15.55
GD2AEP
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
AEP_P4_#14149_05BROADF 765_Q2_SRT-A
BreakerAC110.63 %296.0B327.47
14.82
GD2AEP
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
AEP_P4_#2916_05J.FERR 765_A_SRT-A
BreakerAC110.35 %296.0B326.65
14.81
GD2AEP
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
AEP_P1-2_#2915_4_SRT-A
SingleAC107.09 %296.0B316.99
14.82
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC128.32 %210.0B269.47
301.88
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC127.46 %210.0B267.66
301.88
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
SingleAC100.53 %210.0B211.11
309.19

Details for 05CLNCHR-05LEBANO 138.0 kV Ckt 1 line l/o AEP_P4_#9173_05BROADF 765_P_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9173_05BROADF 765_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.75 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:418.48
MW Contribution:
22.11
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9173_05BROADF 765_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:99.63 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:390.54
MW Contribution:
21.37
Bus #Bus NameTypeMW Contribution
24689505VACITY
50/50
8.123
24290105CRG2H
50/50
1.678
971461AH1-227 GEN
Solar/Wind Harmer
6.703
972103AH1-617 GEN
Solar/Wind Harmer
16.971
960911AF2-382 GEN
Solar/Wind Harmer
4.56
972273AH1-721 GEN
Adder
22.105
24289905CRG1H
50/50
1.634
971225AH1-072 GEN
Solar/Wind Harmer
2.613
971227AH1-073 GEN
Solar/Wind Harmer
2.613
24290205CRG2L
50/50
1.406
970281AG2-184 GEN
Solar/Wind Harmer
17.82
962211AG1-066 GEN
Solar/Wind Harmer
1.732
24734705WLF1G3
Adder
3.889
24734805WLF1G4
Adder
3.889
24734905WLF1G5
Adder
3.889
24735105WLF2G1
Adder
3.527
971981AH1-535 GEN
Solar/Wind Harmer
4.339
24290005CRG1L
50/50
1.368
971687AH1-348 GEN
Solar/Wind Harmer
1.272
24735205WLF2G2
Adder
3.527
LAGNLTFEXP_LAGN->PJM
CLTF
3.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.116
TVALTFEXP_TVA->PJM
CLTF
2.094
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.781
WECLTFEXP_WEC->PJM
CLTF
0.258
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.01
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.216
MECLTFEXP_MEC->PJM
CLTF
1.538
SIGELTFEXP_SIGE->PJM
CLTF
0.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.786

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.15 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
86.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.34 MW.

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.15 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
86.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.34 MW.

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
86.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.34 MW.

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
86.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.34 MW.

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.16
MW Contribution:
86.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.34 MW.

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
86.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.34 MW.

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
86.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
316316AC1-027 C
Solar/Wind Helper
0.36
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.34 MW.

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.71 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.35
MW Contribution:
66.57
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.036
24728205BUCHG1
50/50
5.498
24289905CRG1H
50/50
0.856
270214AC2-123 GEN
Solar/Wind Harmer
3.436
971277AH1-098 GEN
Solar/Wind Harmer
5.696
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
970913AG2-568 GEN
Solar/Wind Harmer
6.824
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
316045AC1-158 PL2
Solar/Wind Helper
4.721
316450AC1-158 RIC
Solar/Wind Helper
0.393
966871AG1-558 GEN
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.471
316006AB2-029 C
Solar/Wind Helper
0.117
3143526WINTERP
Solar/Wind Helper
1.25
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316487AF1-042 GEN
Solar/Wind Helper
0.237
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316411AF1-147_GEN1
Solar/Wind Helper
0.762
316240AF1-291 C
Solar/Wind Helper
0.302
970823AG2-518 GEN
50/50
5.367
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
970563AG2-360 GEN
50/50
35.775
971881AH1-461 GEN
50/50
11.279
24689505VACITY
50/50
4.258
24290105CRG2H
50/50
0.879
24416005BYLLESBY
50/50
0.023
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
971329AH1-144 GEN
Solar/Wind Harmer
7.984
971313AH1-133 GEN
Solar/Wind Harmer
7.137
24734705WLF1G3
Adder
6.298
24734805WLF1G4
Adder
6.298
24734905WLF1G5
Adder
6.298
24735105WLF2G1
Adder
6.159
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
270400AC1-102 GEN
Solar/Wind Harmer
4.127
970281AG2-184 GEN
Solar/Wind Harmer
20.395
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
971981AH1-535 GEN
Solar/Wind Harmer
9.403
962211AG1-066 GEN
Solar/Wind Harmer
2.254
941621AE2-160 GEN
Adder
3.038
971061AG2-657 GEN
Solar/Wind Harmer
7.927
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274728ELWOOD EC;5P
Adder
10.589
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
274735ELWOOD EC;4P
Adder
10.589
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
316468AD1-105 GEN
Solar/Wind Helper
1.202
316164AC1-076 GEN
Solar/Wind Helper
1.187
3141426STAFORD
Solar/Wind Helper
0.054
316233AE1-074 FULL
Solar/Wind Helper
0.367
315651AD1-115 GEN
Solar/Wind Helper
0.81
3141813NORNECK
Solar/Wind Helper
0.236
3143873LANEXA
Solar/Wind Helper
0.14
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.232
957601AF2-054 GEN
Solar/Wind Helper
0.31
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
957831AF2-077 GEN
Solar/Wind Helper
0.303
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
270205AE1-176
50/50
0.003
24728305BUCHG2
50/50
5.498
24290005CRG1L
50/50
0.717
24735205WLF2G2
Adder
6.159
971687AH1-348 GEN
Solar/Wind Harmer
1.03
270336AE1-100 GEN
Solar/Wind Harmer
1.767
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
274732ELWOOD EC;7P
Adder
10.589
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
270494AE1-108_GEN
Solar/Wind Helper
3.46
316473AC1-191 GEN
Solar/Wind Helper
1.53
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316223AC1-118
Solar/Wind Helper
0.364
3141906WESTMOR
Solar/Wind Helper
0.095
316077AC2-138 C
Solar/Wind Helper
0.222
3142946ENON
Solar/Wind Helper
0.078
316484AD2-074 GEN
Solar/Wind Helper
0.452
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147312GRETNA
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
943031AE2-326 GEN
Solar/Wind Harmer
5.408
958121AF2-106 GEN
Solar/Wind Harmer
6.316
960911AF2-382 GEN
Solar/Wind Harmer
8.361
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
972273AH1-721 GEN
Adder
66.568
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274729ELWOOD EC;1P
Adder
10.589
274730ELWOOD EC;6P
Adder
10.589
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
316044AC1-158 PL1
Solar/Wind Helper
1.476
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
3143526WINTERP
Solar/Wind Helper
1.25
3143226MDLTHAN
Solar/Wind Helper
0.24
315975AC1-164 GENB
Solar/Wind Helper
0.091
316337AD2-073 GEN
Solar/Wind Helper
0.361
3142543TWELFTH
Solar/Wind Helper
0.023
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.944
316404AE1-155 C
Solar/Wind Helper
2.011
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
316415AF1-147_GEN2
Solar/Wind Helper
0.762
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
TVALTFEXP_TVA->PJM
CLTF
7.636
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.71 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.35
MW Contribution:
66.57
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
5.367
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
970563AG2-360 GEN
50/50
35.775
971881AH1-461 GEN
50/50
11.279
24689505VACITY
50/50
4.258
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
958121AF2-106 GEN
Solar/Wind Harmer
6.316
960911AF2-382 GEN
Solar/Wind Harmer
8.361
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
247619Y1-049
50/50
0.036
24728205BUCHG1
50/50
5.498
24289905CRG1H
50/50
0.856
270214AC2-123 GEN
Solar/Wind Harmer
3.436
971277AH1-098 GEN
Solar/Wind Harmer
5.696
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
970913AG2-568 GEN
Solar/Wind Harmer
6.824
24723105RIVRG2
Adder
16.666
24416005BYLLESBY
50/50
0.023
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
971329AH1-144 GEN
Solar/Wind Harmer
7.984
971313AH1-133 GEN
Solar/Wind Harmer
7.137
24734705WLF1G3
Adder
6.298
24734805WLF1G4
Adder
6.298
24734905WLF1G5
Adder
6.298
24735105WLF2G1
Adder
6.159
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
270400AC1-102 GEN
Solar/Wind Harmer
4.127
970281AG2-184 GEN
Solar/Wind Harmer
20.395
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
971981AH1-535 GEN
Solar/Wind Harmer
9.403
962211AG1-066 GEN
Solar/Wind Harmer
2.254
941621AE2-160 GEN
Adder
3.038
971061AG2-657 GEN
Solar/Wind Harmer
7.927
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274728ELWOOD EC;5P
Adder
10.589
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
274735ELWOOD EC;4P
Adder
10.589
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
316468AD1-105 GEN
Solar/Wind Helper
1.202
316164AC1-076 GEN
Solar/Wind Helper
1.187
3141426STAFORD
Solar/Wind Helper
0.054
316233AE1-074 FULL
Solar/Wind Helper
0.367
315651AD1-115 GEN
Solar/Wind Helper
0.81
3141813NORNECK
Solar/Wind Helper
0.236
3143873LANEXA
Solar/Wind Helper
0.14
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.232
957601AF2-054 GEN
Solar/Wind Helper
0.31
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
957831AF2-077 GEN
Solar/Wind Helper
0.303
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
270205AE1-176
50/50
0.003
24728305BUCHG2
50/50
5.498
24290005CRG1L
50/50
0.717
24735205WLF2G2
Adder
6.159
971687AH1-348 GEN
Solar/Wind Harmer
1.03
270336AE1-100 GEN
Solar/Wind Harmer
1.767
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
274732ELWOOD EC;7P
Adder
10.589
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
270494AE1-108_GEN
Solar/Wind Helper
3.46
316473AC1-191 GEN
Solar/Wind Helper
1.53
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316223AC1-118
Solar/Wind Helper
0.364
3141906WESTMOR
Solar/Wind Helper
0.095
316077AC2-138 C
Solar/Wind Helper
0.222
3142946ENON
Solar/Wind Helper
0.078
316484AD2-074 GEN
Solar/Wind Helper
0.452
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147312GRETNA
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
316045AC1-158 PL2
Solar/Wind Helper
4.721
316450AC1-158 RIC
Solar/Wind Helper
0.393
966871AG1-558 GEN
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.471
316006AB2-029 C
Solar/Wind Helper
0.117
3143526WINTERP
Solar/Wind Helper
1.25
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316487AF1-042 GEN
Solar/Wind Helper
0.237
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316411AF1-147_GEN1
Solar/Wind Helper
0.762
316240AF1-291 C
Solar/Wind Helper
0.302
972273AH1-721 GEN
Adder
66.568
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274729ELWOOD EC;1P
Adder
10.589
274730ELWOOD EC;6P
Adder
10.589
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
316044AC1-158 PL1
Solar/Wind Helper
1.476
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
3143526WINTERP
Solar/Wind Helper
1.25
3143226MDLTHAN
Solar/Wind Helper
0.24
315975AC1-164 GENB
Solar/Wind Helper
0.091
316337AD2-073 GEN
Solar/Wind Helper
0.361
3142543TWELFTH
Solar/Wind Helper
0.023
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.944
316404AE1-155 C
Solar/Wind Helper
2.011
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
316415AF1-147_GEN2
Solar/Wind Helper
0.762
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
TVALTFEXP_TVA->PJM
CLTF
7.636
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.69 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.19
MW Contribution:
66.57
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.036
24728205BUCHG1
50/50
5.498
24289905CRG1H
50/50
0.856
270214AC2-123 GEN
Solar/Wind Harmer
3.436
971277AH1-098 GEN
Solar/Wind Harmer
5.696
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24416005BYLLESBY
50/50
0.023
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
971329AH1-144 GEN
Solar/Wind Harmer
7.984
971313AH1-133 GEN
Solar/Wind Harmer
7.137
24734705WLF1G3
Adder
6.298
24734805WLF1G4
Adder
6.298
24734905WLF1G5
Adder
6.298
24735105WLF2G1
Adder
6.159
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
270400AC1-102 GEN
Solar/Wind Harmer
4.127
970281AG2-184 GEN
Solar/Wind Harmer
20.395
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
971981AH1-535 GEN
Solar/Wind Harmer
9.403
962211AG1-066 GEN
Solar/Wind Harmer
2.254
941621AE2-160 GEN
Adder
3.038
971061AG2-657 GEN
Solar/Wind Harmer
7.927
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274728ELWOOD EC;5P
Adder
10.589
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
274735ELWOOD EC;4P
Adder
10.589
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
316468AD1-105 GEN
Solar/Wind Helper
1.202
316164AC1-076 GEN
Solar/Wind Helper
1.187
3141426STAFORD
Solar/Wind Helper
0.054
316233AE1-074 FULL
Solar/Wind Helper
0.367
315651AD1-115 GEN
Solar/Wind Helper
0.81
3141813NORNECK
Solar/Wind Helper
0.236
3143873LANEXA
Solar/Wind Helper
0.14
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.232
957601AF2-054 GEN
Solar/Wind Helper
0.31
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
957831AF2-077 GEN
Solar/Wind Helper
0.303
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
270205AE1-176
50/50
0.003
24728305BUCHG2
50/50
5.498
24290005CRG1L
50/50
0.717
24735205WLF2G2
Adder
6.159
971687AH1-348 GEN
Solar/Wind Harmer
1.03
270336AE1-100 GEN
Solar/Wind Harmer
1.767
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
274732ELWOOD EC;7P
Adder
10.589
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
270494AE1-108_GEN
Solar/Wind Helper
3.46
316473AC1-191 GEN
Solar/Wind Helper
1.53
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316223AC1-118
Solar/Wind Helper
0.364
3141906WESTMOR
Solar/Wind Helper
0.095
316077AC2-138 C
Solar/Wind Helper
0.222
3142946ENON
Solar/Wind Helper
0.078
316484AD2-074 GEN
Solar/Wind Helper
0.452
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147312GRETNA
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
970823AG2-518 GEN
50/50
5.367
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
970563AG2-360 GEN
50/50
35.775
971881AH1-461 GEN
50/50
11.279
24689505VACITY
50/50
4.258
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
958121AF2-106 GEN
Solar/Wind Harmer
6.316
960911AF2-382 GEN
Solar/Wind Harmer
8.361
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
972273AH1-721 GEN
Adder
66.568
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274729ELWOOD EC;1P
Adder
10.589
274730ELWOOD EC;6P
Adder
10.589
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
316044AC1-158 PL1
Solar/Wind Helper
1.476
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
3143526WINTERP
Solar/Wind Helper
1.25
3143226MDLTHAN
Solar/Wind Helper
0.24
315975AC1-164 GENB
Solar/Wind Helper
0.091
316337AD2-073 GEN
Solar/Wind Helper
0.361
3142543TWELFTH
Solar/Wind Helper
0.023
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.944
316404AE1-155 C
Solar/Wind Helper
2.011
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
316415AF1-147_GEN2
Solar/Wind Helper
0.762
970913AG2-568 GEN
Solar/Wind Harmer
6.824
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
316045AC1-158 PL2
Solar/Wind Helper
4.721
316450AC1-158 RIC
Solar/Wind Helper
0.393
966871AG1-558 GEN
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.471
316006AB2-029 C
Solar/Wind Helper
0.117
3143526WINTERP
Solar/Wind Helper
1.25
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316487AF1-042 GEN
Solar/Wind Helper
0.237
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316411AF1-147_GEN1
Solar/Wind Helper
0.762
316240AF1-291 C
Solar/Wind Helper
0.302
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
TVALTFEXP_TVA->PJM
CLTF
7.636
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.69 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.19
MW Contribution:
66.57
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.023
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
971329AH1-144 GEN
Solar/Wind Harmer
7.984
971313AH1-133 GEN
Solar/Wind Harmer
7.137
24734705WLF1G3
Adder
6.298
24734805WLF1G4
Adder
6.298
24734905WLF1G5
Adder
6.298
24735105WLF2G1
Adder
6.159
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
270400AC1-102 GEN
Solar/Wind Harmer
4.127
970281AG2-184 GEN
Solar/Wind Harmer
20.395
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
971981AH1-535 GEN
Solar/Wind Harmer
9.403
962211AG1-066 GEN
Solar/Wind Harmer
2.254
941621AE2-160 GEN
Adder
3.038
971061AG2-657 GEN
Solar/Wind Harmer
7.927
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274728ELWOOD EC;5P
Adder
10.589
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
274735ELWOOD EC;4P
Adder
10.589
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
316468AD1-105 GEN
Solar/Wind Helper
1.202
316164AC1-076 GEN
Solar/Wind Helper
1.187
3141426STAFORD
Solar/Wind Helper
0.054
316233AE1-074 FULL
Solar/Wind Helper
0.367
315651AD1-115 GEN
Solar/Wind Helper
0.81
3141813NORNECK
Solar/Wind Helper
0.236
3143873LANEXA
Solar/Wind Helper
0.14
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.232
957601AF2-054 GEN
Solar/Wind Helper
0.31
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
957831AF2-077 GEN
Solar/Wind Helper
0.303
970823AG2-518 GEN
50/50
5.367
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
970563AG2-360 GEN
50/50
35.775
971881AH1-461 GEN
50/50
11.279
24689505VACITY
50/50
4.258
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
958121AF2-106 GEN
Solar/Wind Harmer
6.316
960911AF2-382 GEN
Solar/Wind Harmer
8.361
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
972273AH1-721 GEN
Adder
66.568
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274729ELWOOD EC;1P
Adder
10.589
274730ELWOOD EC;6P
Adder
10.589
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
316044AC1-158 PL1
Solar/Wind Helper
1.476
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
3143526WINTERP
Solar/Wind Helper
1.25
3143226MDLTHAN
Solar/Wind Helper
0.24
315975AC1-164 GENB
Solar/Wind Helper
0.091
316337AD2-073 GEN
Solar/Wind Helper
0.361
3142543TWELFTH
Solar/Wind Helper
0.023
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.944
316404AE1-155 C
Solar/Wind Helper
2.011
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
316415AF1-147_GEN2
Solar/Wind Helper
0.762
247619Y1-049
50/50
0.036
24728205BUCHG1
50/50
5.498
24289905CRG1H
50/50
0.856
270214AC2-123 GEN
Solar/Wind Harmer
3.436
971277AH1-098 GEN
Solar/Wind Harmer
5.696
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
970913AG2-568 GEN
Solar/Wind Harmer
6.824
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
316045AC1-158 PL2
Solar/Wind Helper
4.721
316450AC1-158 RIC
Solar/Wind Helper
0.393
966871AG1-558 GEN
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.471
316006AB2-029 C
Solar/Wind Helper
0.117
3143526WINTERP
Solar/Wind Helper
1.25
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316487AF1-042 GEN
Solar/Wind Helper
0.237
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316411AF1-147_GEN1
Solar/Wind Helper
0.762
316240AF1-291 C
Solar/Wind Helper
0.302
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
270205AE1-176
50/50
0.003
24728305BUCHG2
50/50
5.498
24290005CRG1L
50/50
0.717
24735205WLF2G2
Adder
6.159
971687AH1-348 GEN
Solar/Wind Harmer
1.03
270336AE1-100 GEN
Solar/Wind Harmer
1.767
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
274732ELWOOD EC;7P
Adder
10.589
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
270494AE1-108_GEN
Solar/Wind Helper
3.46
316473AC1-191 GEN
Solar/Wind Helper
1.53
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316223AC1-118
Solar/Wind Helper
0.364
3141906WESTMOR
Solar/Wind Helper
0.095
316077AC2-138 C
Solar/Wind Helper
0.222
3142946ENON
Solar/Wind Helper
0.078
316484AD2-074 GEN
Solar/Wind Helper
0.452
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147312GRETNA
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
TVALTFEXP_TVA->PJM
CLTF
7.636
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.69 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.09
MW Contribution:
66.57
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.023
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
971329AH1-144 GEN
Solar/Wind Harmer
7.984
971313AH1-133 GEN
Solar/Wind Harmer
7.137
24734705WLF1G3
Adder
6.298
24734805WLF1G4
Adder
6.298
24734905WLF1G5
Adder
6.298
24735105WLF2G1
Adder
6.159
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
270400AC1-102 GEN
Solar/Wind Harmer
4.127
970281AG2-184 GEN
Solar/Wind Harmer
20.395
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
971981AH1-535 GEN
Solar/Wind Harmer
9.403
962211AG1-066 GEN
Solar/Wind Harmer
2.254
941621AE2-160 GEN
Adder
3.038
971061AG2-657 GEN
Solar/Wind Harmer
7.927
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274728ELWOOD EC;5P
Adder
10.589
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
274735ELWOOD EC;4P
Adder
10.589
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
316468AD1-105 GEN
Solar/Wind Helper
1.202
316164AC1-076 GEN
Solar/Wind Helper
1.187
3141426STAFORD
Solar/Wind Helper
0.054
316233AE1-074 FULL
Solar/Wind Helper
0.367
315651AD1-115 GEN
Solar/Wind Helper
0.81
3141813NORNECK
Solar/Wind Helper
0.236
3143873LANEXA
Solar/Wind Helper
0.14
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.232
957601AF2-054 GEN
Solar/Wind Helper
0.31
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
957831AF2-077 GEN
Solar/Wind Helper
0.303
970823AG2-518 GEN
50/50
5.367
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
970563AG2-360 GEN
50/50
35.775
971881AH1-461 GEN
50/50
11.279
24689505VACITY
50/50
4.258
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
958121AF2-106 GEN
Solar/Wind Harmer
6.316
960911AF2-382 GEN
Solar/Wind Harmer
8.361
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
972273AH1-721 GEN
Adder
66.568
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274729ELWOOD EC;1P
Adder
10.589
274730ELWOOD EC;6P
Adder
10.589
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
247619Y1-049
50/50
0.036
24728205BUCHG1
50/50
5.498
24289905CRG1H
50/50
0.856
270214AC2-123 GEN
Solar/Wind Harmer
3.436
971277AH1-098 GEN
Solar/Wind Harmer
5.696
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
970913AG2-568 GEN
Solar/Wind Harmer
6.824
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
270205AE1-176
50/50
0.003
24728305BUCHG2
50/50
5.498
24290005CRG1L
50/50
0.717
24735205WLF2G2
Adder
6.159
971687AH1-348 GEN
Solar/Wind Harmer
1.03
270336AE1-100 GEN
Solar/Wind Harmer
1.767
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
274732ELWOOD EC;7P
Adder
10.589
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
270494AE1-108_GEN
Solar/Wind Helper
3.46
316473AC1-191 GEN
Solar/Wind Helper
1.53
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316223AC1-118
Solar/Wind Helper
0.364
3141906WESTMOR
Solar/Wind Helper
0.095
316077AC2-138 C
Solar/Wind Helper
0.222
3142946ENON
Solar/Wind Helper
0.078
316484AD2-074 GEN
Solar/Wind Helper
0.452
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147312GRETNA
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
316045AC1-158 PL2
Solar/Wind Helper
4.721
316450AC1-158 RIC
Solar/Wind Helper
0.393
966871AG1-558 GEN
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.471
316006AB2-029 C
Solar/Wind Helper
0.117
3143526WINTERP
Solar/Wind Helper
1.25
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316487AF1-042 GEN
Solar/Wind Helper
0.237
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316411AF1-147_GEN1
Solar/Wind Helper
0.762
316240AF1-291 C
Solar/Wind Helper
0.302
316447AC1-158 HLD
Solar/Wind Helper
3.247
316044AC1-158 PL1
Solar/Wind Helper
1.476
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
3143526WINTERP
Solar/Wind Helper
1.25
3143226MDLTHAN
Solar/Wind Helper
0.24
315975AC1-164 GENB
Solar/Wind Helper
0.091
316337AD2-073 GEN
Solar/Wind Helper
0.361
3142543TWELFTH
Solar/Wind Helper
0.023
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.944
316404AE1-155 C
Solar/Wind Helper
2.011
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
316415AF1-147_GEN2
Solar/Wind Helper
0.762
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
TVALTFEXP_TVA->PJM
CLTF
7.636
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:286.57 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3381.47
MW Contribution:
66.57
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.023
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
966391AG1-508 GEN
Solar/Wind Harmer
1.529
971331AH1-145 GEN
Solar/Wind Harmer
12.5
971329AH1-144 GEN
Solar/Wind Harmer
4.594
971313AH1-133 GEN
Solar/Wind Harmer
4.106
24734705WLF1G3
Adder
6.298
24734805WLF1G4
Adder
6.298
24734905WLF1G5
Adder
6.298
24735105WLF2G1
Adder
6.159
270069AE2-166 C O1
Solar/Wind Harmer
6.442
270399AC1-101 GEN
Solar/Wind Harmer
2.148
270400AC1-102 GEN
Solar/Wind Harmer
2.148
970281AG2-184 GEN
Solar/Wind Harmer
14.229
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
14.993
971981AH1-535 GEN
Solar/Wind Harmer
4.373
941621AE2-160 GEN
Adder
3.038
971061AG2-657 GEN
Solar/Wind Harmer
3.871
274728ELWOOD EC;5P
Adder
10.589
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
274735ELWOOD EC;4P
Adder
10.589
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
316468AD1-105 GEN
Solar/Wind Helper
1.202
316164AC1-076 GEN
Solar/Wind Helper
1.187
3141426STAFORD
Solar/Wind Helper
0.054
316233AE1-074 FULL
Solar/Wind Helper
0.367
315651AD1-115 GEN
Solar/Wind Helper
0.81
3141813NORNECK
Solar/Wind Helper
0.236
3143873LANEXA
Solar/Wind Helper
0.14
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.232
957601AF2-054 GEN
Solar/Wind Helper
0.31
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
957831AF2-077 GEN
Solar/Wind Helper
0.303
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
270205AE1-176
50/50
0.003
24728305BUCHG2
50/50
5.498
24290005CRG1L
50/50
0.717
24735205WLF2G2
Adder
6.159
971687AH1-348 GEN
Solar/Wind Harmer
0.719
971403AH1-188 GEN
Solar/Wind Harmer
9.797
944971AF1-162 GEN
Solar/Wind Harmer
6.718
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
274732ELWOOD EC;7P
Adder
10.589
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
270494AE1-108_GEN
Solar/Wind Helper
3.46
316473AC1-191 GEN
Solar/Wind Helper
1.53
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316223AC1-118
Solar/Wind Helper
0.364
3141906WESTMOR
Solar/Wind Helper
0.095
316077AC2-138 C
Solar/Wind Helper
0.222
3142946ENON
Solar/Wind Helper
0.078
316484AD2-074 GEN
Solar/Wind Helper
0.452
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147312GRETNA
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
970823AG2-518 GEN
50/50
5.367
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
970563AG2-360 GEN
50/50
35.775
971881AH1-461 GEN
50/50
11.279
24689505VACITY
50/50
4.258
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
958121AF2-106 GEN
Solar/Wind Harmer
0.001
960911AF2-382 GEN
Solar/Wind Harmer
5.833
270346AE1-212 GEN
Solar/Wind Harmer
6.792
971461AH1-227 GEN
Solar/Wind Harmer
3.708
972103AH1-617 GEN
Solar/Wind Harmer
13.552
270030AE2-140 GEN
Solar/Wind Harmer
13.376
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
274730ELWOOD EC;6P
Adder
10.589
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
316044AC1-158 PL1
Solar/Wind Helper
1.476
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
3143526WINTERP
Solar/Wind Helper
1.25
3143226MDLTHAN
Solar/Wind Helper
0.24
315975AC1-164 GENB
Solar/Wind Helper
0.091
316337AD2-073 GEN
Solar/Wind Helper
0.361
3142543TWELFTH
Solar/Wind Helper
0.023
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.944
316404AE1-155 C
Solar/Wind Helper
2.011
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
316415AF1-147_GEN2
Solar/Wind Helper
0.762
247619Y1-049
50/50
0.036
24728205BUCHG1
50/50
5.498
24289905CRG1H
50/50
0.856
971277AH1-098 GEN
Solar/Wind Harmer
3.974
270583AD2-179 GEN
Solar/Wind Harmer
9.711
971225AH1-072 GEN
Solar/Wind Harmer
1.446
971227AH1-073 GEN
Solar/Wind Harmer
1.446
970913AG2-568 GEN
Solar/Wind Harmer
5.608
24723105RIVRG2
Adder
16.666
316045AC1-158 PL2
Solar/Wind Helper
4.721
316450AC1-158 RIC
Solar/Wind Helper
0.393
966871AG1-558 GEN
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.471
316006AB2-029 C
Solar/Wind Helper
0.117
3143526WINTERP
Solar/Wind Helper
1.25
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316487AF1-042 GEN
Solar/Wind Helper
0.237
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316411AF1-147_GEN1
Solar/Wind Helper
0.762
316240AF1-291 C
Solar/Wind Helper
0.302
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
TVALTFEXP_TVA->PJM
CLTF
7.636
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:286.54 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3381.22
MW Contribution:
66.57
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.023
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
966391AG1-508 GEN
Solar/Wind Harmer
1.529
971331AH1-145 GEN
Solar/Wind Harmer
12.5
971329AH1-144 GEN
Solar/Wind Harmer
4.594
971313AH1-133 GEN
Solar/Wind Harmer
4.106
24734705WLF1G3
Adder
6.298
24734805WLF1G4
Adder
6.298
24734905WLF1G5
Adder
6.298
24735105WLF2G1
Adder
6.159
270069AE2-166 C O1
Solar/Wind Harmer
6.442
270399AC1-101 GEN
Solar/Wind Harmer
2.148
270400AC1-102 GEN
Solar/Wind Harmer
2.148
970281AG2-184 GEN
Solar/Wind Harmer
14.229
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
14.993
971981AH1-535 GEN
Solar/Wind Harmer
4.373
941621AE2-160 GEN
Adder
3.038
971061AG2-657 GEN
Solar/Wind Harmer
3.871
274728ELWOOD EC;5P
Adder
10.589
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
274735ELWOOD EC;4P
Adder
10.589
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
316468AD1-105 GEN
Solar/Wind Helper
1.202
316164AC1-076 GEN
Solar/Wind Helper
1.187
3141426STAFORD
Solar/Wind Helper
0.054
316233AE1-074 FULL
Solar/Wind Helper
0.367
315651AD1-115 GEN
Solar/Wind Helper
0.81
3141813NORNECK
Solar/Wind Helper
0.236
3143873LANEXA
Solar/Wind Helper
0.14
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.232
957601AF2-054 GEN
Solar/Wind Helper
0.31
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
957831AF2-077 GEN
Solar/Wind Helper
0.303
970823AG2-518 GEN
50/50
5.367
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
970563AG2-360 GEN
50/50
35.775
971881AH1-461 GEN
50/50
11.279
24689505VACITY
50/50
4.258
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
958121AF2-106 GEN
Solar/Wind Harmer
0.001
960911AF2-382 GEN
Solar/Wind Harmer
5.833
270346AE1-212 GEN
Solar/Wind Harmer
6.792
971461AH1-227 GEN
Solar/Wind Harmer
3.708
972103AH1-617 GEN
Solar/Wind Harmer
13.552
270030AE2-140 GEN
Solar/Wind Harmer
13.376
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
274730ELWOOD EC;6P
Adder
10.589
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
316044AC1-158 PL1
Solar/Wind Helper
1.476
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
3143526WINTERP
Solar/Wind Helper
1.25
3143226MDLTHAN
Solar/Wind Helper
0.24
315975AC1-164 GENB
Solar/Wind Helper
0.091
316337AD2-073 GEN
Solar/Wind Helper
0.361
3142543TWELFTH
Solar/Wind Helper
0.023
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.944
316404AE1-155 C
Solar/Wind Helper
2.011
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
316415AF1-147_GEN2
Solar/Wind Helper
0.762
247619Y1-049
50/50
0.036
24728205BUCHG1
50/50
5.498
24289905CRG1H
50/50
0.856
971277AH1-098 GEN
Solar/Wind Harmer
3.974
270583AD2-179 GEN
Solar/Wind Harmer
9.711
971225AH1-072 GEN
Solar/Wind Harmer
1.446
971227AH1-073 GEN
Solar/Wind Harmer
1.446
970913AG2-568 GEN
Solar/Wind Harmer
5.608
24723105RIVRG2
Adder
16.666
316045AC1-158 PL2
Solar/Wind Helper
4.721
316450AC1-158 RIC
Solar/Wind Helper
0.393
966871AG1-558 GEN
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.471
316006AB2-029 C
Solar/Wind Helper
0.117
3143526WINTERP
Solar/Wind Helper
1.25
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316487AF1-042 GEN
Solar/Wind Helper
0.237
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316411AF1-147_GEN1
Solar/Wind Helper
0.762
316240AF1-291 C
Solar/Wind Helper
0.302
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
270205AE1-176
50/50
0.003
24728305BUCHG2
50/50
5.498
24290005CRG1L
50/50
0.717
24735205WLF2G2
Adder
6.159
971687AH1-348 GEN
Solar/Wind Harmer
0.719
971403AH1-188 GEN
Solar/Wind Harmer
9.797
944971AF1-162 GEN
Solar/Wind Harmer
6.718
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
274732ELWOOD EC;7P
Adder
10.589
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
270494AE1-108_GEN
Solar/Wind Helper
3.46
316473AC1-191 GEN
Solar/Wind Helper
1.53
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316223AC1-118
Solar/Wind Helper
0.364
3141906WESTMOR
Solar/Wind Helper
0.095
316077AC2-138 C
Solar/Wind Helper
0.222
3142946ENON
Solar/Wind Helper
0.078
316484AD2-074 GEN
Solar/Wind Helper
0.452
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147312GRETNA
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
TVALTFEXP_TVA->PJM
CLTF
7.636
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:220.32 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2599.75
MW Contribution:
59.85
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
70.636
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 70.64 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:220.32 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2599.75
MW Contribution:
59.85
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
70.636
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 70.64 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:220.32 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2599.75
MW Contribution:
59.85
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
70.636
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 70.64 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:220.3 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2599.51
MW Contribution:
59.85
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
70.636
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 70.64 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:191.87 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2264.12
MW Contribution:
52.94
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
62.489
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 62.49 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2114-535_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2114-535_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:188.07 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2219.28
MW Contribution:
50.71
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
59.863
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 59.86 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:184.05 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2171.82
MW Contribution:
50.66
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
59.796
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 59.8 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P2-2: ALTAVISTA 138KV_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ALTAVISTA 138KV_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:183.75 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2168.24
MW Contribution:
50.91
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
60.094
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 60.09 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:180.03 %
Rating:1180.0 MVA
Rating Type:A
MVA to Mitigate:2124.32
MW Contribution:
50.73
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
59.878
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 59.88 MW.

Details for 05ELKGARDNSS-05SALTV1 138.0 kV Ckt 1 line l/o AEP_P4_#9173_05BROADF 765_P_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05ELKGARDNSS-05SALTV1 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9173_05BROADF 765_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.83 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:395.24
MW Contribution:
22.11
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05ELKGARDNSS-05SALTV1 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9173_05BROADF 765_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:93.78 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:367.63
MW Contribution:
21.37
Bus #Bus NameTypeMW Contribution
24689505VACITY
50/50
8.123
24290105CRG2H
50/50
1.678
971461AH1-227 GEN
Solar/Wind Harmer
6.703
972103AH1-617 GEN
Solar/Wind Harmer
16.971
960911AF2-382 GEN
Solar/Wind Harmer
4.56
972273AH1-721 GEN
Adder
22.105
24290205CRG2L
50/50
1.406
970281AG2-184 GEN
Solar/Wind Harmer
17.82
962211AG1-066 GEN
Solar/Wind Harmer
1.732
24734705WLF1G3
Adder
3.889
24734805WLF1G4
Adder
3.889
24734905WLF1G5
Adder
3.889
24735105WLF2G1
Adder
3.527
971981AH1-535 GEN
Solar/Wind Harmer
4.339
24289905CRG1H
50/50
1.634
971225AH1-072 GEN
Solar/Wind Harmer
2.613
971227AH1-073 GEN
Solar/Wind Harmer
2.613
24290005CRG1L
50/50
1.368
971687AH1-348 GEN
Solar/Wind Harmer
1.272
24735205WLF2G2
Adder
3.527
LAGNLTFEXP_LAGN->PJM
CLTF
3.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.116
TVALTFEXP_TVA->PJM
CLTF
2.094
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.781
WECLTFEXP_WEC->PJM
CLTF
0.258
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.01
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.216
MECLTFEXP_MEC->PJM
CLTF
1.538
SIGELTFEXP_SIGE->PJM
CLTF
0.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.786

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.63 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
86.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.34 MW.

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.63 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
86.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.34 MW.

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
86.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.34 MW.

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
86.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
24728205BUCHG1
50/50
8.141
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.34 MW.

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.16
MW Contribution:
86.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.34 MW.

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.36 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
86.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.34 MW.

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
86.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.34 MW.

Details for 05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line l/o AEP_P7-1_#10868___SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10868___SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:114.38 %
Rating:361.0 MVA
Rating Type:B
MVA to Mitigate:412.91
MW Contribution:
18.66
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10868___SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.79 %
Rating:361.0 MVA
Rating Type:B
MVA to Mitigate:378.29
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
24289905CRG1H
50/50
1.97
971225AH1-072 GEN
Solar/Wind Harmer
3.118
971227AH1-073 GEN
Solar/Wind Harmer
3.118
24290005CRG1L
50/50
1.649
24735205WLF2G2
50/50
6.012
971687AH1-348 GEN
Solar/Wind Harmer
1.515
24290205CRG2L
50/50
1.696
24734705WLF1G3
50/50
8.311
24734805WLF1G4
50/50
8.311
24734905WLF1G5
50/50
8.311
24735105WLF2G1
50/50
6.012
970281AG2-184 GEN
Solar/Wind Harmer
20.83
962211AG1-066 GEN
Solar/Wind Harmer
1.962
24689505VACITY
50/50
9.797
24290105CRG2H
50/50
2.023
971461AH1-227 GEN
Solar/Wind Harmer
7.997
972103AH1-617 GEN
Solar/Wind Harmer
19.838
960911AF2-382 GEN
Solar/Wind Harmer
5.402
972273AH1-721 GEN
Adder
18.659
LAGNLTFEXP_LAGN->PJM
CLTF
2.432
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.087
TVALTFEXP_TVA->PJM
CLTF
1.561
NYPJM->LTFIMP_NY
CLTF
0.229
LGEELTFEXP_LGEE->PJM
CLTF
0.588
WECLTFEXP_WEC->PJM
CLTF
0.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.385
MECLTFEXP_MEC->PJM
CLTF
1.053
SIGELTFEXP_SIGE->PJM
CLTF
0.041
CPLELTFEXP_CPLE->PJM
CLTF
0.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.928

Details for 05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line l/o AEP_P4_#9173_05BROADF 765_P_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9173_05BROADF 765_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.39 %
Rating:361.0 MVA
Rating Type:B
MVA to Mitigate:409.35
MW Contribution:
22.11
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9173_05BROADF 765_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.68 %
Rating:361.0 MVA
Rating Type:B
MVA to Mitigate:381.51
MW Contribution:
21.37
Bus #Bus NameTypeMW Contribution
24289905CRG1H
50/50
1.634
971225AH1-072 GEN
Solar/Wind Harmer
2.613
971227AH1-073 GEN
Solar/Wind Harmer
2.613
24290205CRG2L
50/50
1.406
970281AG2-184 GEN
Solar/Wind Harmer
17.82
962211AG1-066 GEN
Solar/Wind Harmer
1.732
24734705WLF1G3
Adder
3.889
24734805WLF1G4
Adder
3.889
24734905WLF1G5
Adder
3.889
24689505VACITY
50/50
8.123
24290105CRG2H
50/50
1.678
971461AH1-227 GEN
Solar/Wind Harmer
6.703
972103AH1-617 GEN
Solar/Wind Harmer
16.971
960911AF2-382 GEN
Solar/Wind Harmer
4.56
972273AH1-721 GEN
Adder
22.105
24735105WLF2G1
Adder
3.527
971981AH1-535 GEN
Solar/Wind Harmer
4.339
24290005CRG1L
50/50
1.368
971687AH1-348 GEN
Solar/Wind Harmer
1.272
24735205WLF2G2
Adder
3.527
LAGNLTFEXP_LAGN->PJM
CLTF
3.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.116
TVALTFEXP_TVA->PJM
CLTF
2.094
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.781
WECLTFEXP_WEC->PJM
CLTF
0.258
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.01
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.216
MECLTFEXP_MEC->PJM
CLTF
1.538
SIGELTFEXP_SIGE->PJM
CLTF
0.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.786

Details for 05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line l/o AEP_P4_#1375_05BROADF 765_P2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1375_05BROADF 765_P2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.51 %
Rating:361.0 MVA
Rating Type:B
MVA to Mitigate:373.67
MW Contribution:
22.21
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1375_05BROADF 765_P2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:98.24 %
Rating:361.0 MVA
Rating Type:B
MVA to Mitigate:354.65
MW Contribution:
21.47
Bus #Bus NameTypeMW Contribution
24689505VACITY
50/50
8.264
24290105CRG2H
50/50
1.707
971461AH1-227 GEN
Solar/Wind Harmer
6.818
972103AH1-617 GEN
Solar/Wind Harmer
17.167
960911AF2-382 GEN
Solar/Wind Harmer
4.814
972273AH1-721 GEN
Adder
22.206
24290205CRG2L
50/50
1.431
970281AG2-184 GEN
Solar/Wind Harmer
18.025
962211AG1-066 GEN
Solar/Wind Harmer
1.752
24734705WLF1G3
Adder
4.099
24734805WLF1G4
Adder
4.099
24734905WLF1G5
Adder
4.099
24735105WLF2G1
Adder
3.697
971981AH1-535 GEN
Solar/Wind Harmer
4.52
24289905CRG1H
50/50
1.662
971225AH1-072 GEN
Solar/Wind Harmer
2.658
971227AH1-073 GEN
Solar/Wind Harmer
2.658
24290005CRG1L
50/50
1.391
971687AH1-348 GEN
Solar/Wind Harmer
1.293
24735205WLF2G2
Adder
3.697
LAGNLTFEXP_LAGN->PJM
CLTF
3.417
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.928
TVALTFEXP_TVA->PJM
CLTF
2.181
NYPJM->LTFIMP_NY
CLTF
0.236
LGEELTFEXP_LGEE->PJM
CLTF
0.721
WECLTFEXP_WEC->PJM
CLTF
0.226
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.809
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.424
MECLTFEXP_MEC->PJM
CLTF
1.447
SIGELTFEXP_SIGE->PJM
CLTF
0.053
CPLELTFEXP_CPLE->PJM
CLTF
0.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.856

Details for 05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11112_05J.FERR 765_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.62 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:327.42
MW Contribution:
15.55
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11112_05J.FERR 765_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.49 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:309.28
MW Contribution:
15.08
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
33.379
24689505VACITY
50/50
3.467
24290105CRG2H
50/50
0.716
971461AH1-227 GEN
Solar/Wind Harmer
2.867
972273AH1-721 GEN
Adder
15.55
24290205CRG2L
50/50
0.6
24734705WLF1G3
Adder
4.417
24734805WLF1G4
Adder
4.417
24734905WLF1G5
Adder
4.417
24735105WLF2G1
Adder
3.651
24289905CRG1H
50/50
0.697
971225AH1-072 GEN
Solar/Wind Harmer
1.118
971227AH1-073 GEN
Solar/Wind Harmer
1.118
24290005CRG1L
50/50
0.584
24735205WLF2G2
Adder
3.651
971687AH1-348 GEN
Solar/Wind Harmer
0.543
LAGNLTFEXP_LAGN->PJM
CLTF
2.913
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.433
TVALTFEXP_TVA->PJM
CLTF
1.772
NYPJM->LTFIMP_NY
CLTF
0.199
LGEELTFEXP_LGEE->PJM
CLTF
0.644
WECLTFEXP_WEC->PJM
CLTF
0.249
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.741
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.09
MECLTFEXP_MEC->PJM
CLTF
1.418
SIGELTFEXP_SIGE->PJM
CLTF
0.049
CPLELTFEXP_CPLE->PJM
CLTF
0.364
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.839

Details for 05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line l/o AEP_P4_#14149_05BROADF 765_Q2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14149_05BROADF 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.73 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:307.05
MW Contribution:
14.82
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14149_05BROADF 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:93.45 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:276.62
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
0.598
24734705WLF1G3
Adder
4.382
24734805WLF1G4
Adder
4.382
24734905WLF1G5
Adder
4.382
24735105WLF2G1
Adder
3.603
970563AG2-360 GEN
50/50
33.396
24689505VACITY
50/50
3.456
24290105CRG2H
50/50
0.714
971461AH1-227 GEN
Solar/Wind Harmer
2.861
972273AH1-721 GEN
Adder
14.819
24289905CRG1H
50/50
0.695
971225AH1-072 GEN
Solar/Wind Harmer
1.115
971227AH1-073 GEN
Solar/Wind Harmer
1.115
24290005CRG1L
50/50
0.582
24735205WLF2G2
Adder
3.603
971687AH1-348 GEN
Solar/Wind Harmer
0.542
LAGNLTFEXP_LAGN->PJM
CLTF
2.473
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.74
TVALTFEXP_TVA->PJM
CLTF
1.556
NYPJM->LTFIMP_NY
CLTF
0.186
LGEELTFEXP_LGEE->PJM
CLTF
0.617
WECLTFEXP_WEC->PJM
CLTF
0.233
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.399
MECLTFEXP_MEC->PJM
CLTF
1.291
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.897

Details for 05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line l/o AEP_P4_#2916_05J.FERR 765_A_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2916_05J.FERR 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.45 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:306.22
MW Contribution:
14.81
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2916_05J.FERR 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:93.09 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:275.54
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
0.598
24734705WLF1G3
Adder
4.38
24734805WLF1G4
Adder
4.38
24734905WLF1G5
Adder
4.38
24735105WLF2G1
Adder
3.602
970563AG2-360 GEN
50/50
33.385
24689505VACITY
50/50
3.455
24290105CRG2H
50/50
0.714
971461AH1-227 GEN
Solar/Wind Harmer
2.859
972273AH1-721 GEN
Adder
14.808
24289905CRG1H
50/50
0.695
971225AH1-072 GEN
Solar/Wind Harmer
1.115
971227AH1-073 GEN
Solar/Wind Harmer
1.115
24290005CRG1L
50/50
0.582
24735205WLF2G2
Adder
3.602
971687AH1-348 GEN
Solar/Wind Harmer
0.541
LAGNLTFEXP_LAGN->PJM
CLTF
2.477
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.779
TVALTFEXP_TVA->PJM
CLTF
1.558
NYPJM->LTFIMP_NY
CLTF
0.186
LGEELTFEXP_LGEE->PJM
CLTF
0.615
WECLTFEXP_WEC->PJM
CLTF
0.232
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.16
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.402
MECLTFEXP_MEC->PJM
CLTF
1.288
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.899

Details for 05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line l/o AEP_P1-2_#2915_4_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#2915_4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.16 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:305.34
MW Contribution:
14.82
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#2915_4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:92.88 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:274.93
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
0.598
24734705WLF1G3
Adder
4.382
24734805WLF1G4
Adder
4.382
24734905WLF1G5
Adder
4.382
24735105WLF2G1
Adder
3.603
24290005CRG1L
50/50
0.582
24735205WLF2G2
Adder
3.603
971687AH1-348 GEN
Solar/Wind Harmer
0.378
970563AG2-360 GEN
50/50
33.396
24689505VACITY
50/50
3.456
24290105CRG2H
50/50
0.714
971461AH1-227 GEN
Solar/Wind Harmer
1.996
24289905CRG1H
50/50
0.695
971225AH1-072 GEN
Solar/Wind Harmer
0.778
971227AH1-073 GEN
Solar/Wind Harmer
0.778
972273AH1-721 GEN
Adder
14.819
LAGNLTFEXP_LAGN->PJM
CLTF
2.473
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.74
TVALTFEXP_TVA->PJM
CLTF
1.556
NYPJM->LTFIMP_NY
CLTF
0.186
LGEELTFEXP_LGEE->PJM
CLTF
0.617
WECLTFEXP_WEC->PJM
CLTF
0.233
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.399
MECLTFEXP_MEC->PJM
CLTF
1.291
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.897

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#3149_05HANG R 765_B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3149_05HANG R 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.94 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2216.66
MW Contribution:
40.9
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.51
24802706KYGER 1LP
50/50
2.645
24803506KYGER 5LP
50/50
2.583
971985AH1-537 GEN
Solar/Wind Harmer
56.698
253433AC1-085 GEN1
Solar/Wind Harmer
7.414
253432AC1-085 GEN2
Solar/Wind Harmer
0.373
270263AC1-001 GEN
Solar/Wind Harmer
1.45
25196408WSDLE3
Adder
11.623
270340AC2-060 GEN
Solar/Wind Harmer
3.884
253406AD2-031_GEN
Solar/Wind Harmer
1.593
25196108MFTGT2
Adder
1.88
25196108MFTGT2
Adder
1.746
972163AH1-664 GEN
Solar/Wind Harmer
12.044
972165AH1-665 GEN
Solar/Wind Harmer
9.636
339216AC1-074 GEN
Solar/Wind Harmer
1.864
270432AC2-029 GEN
Solar/Wind Harmer
7.644
253372AE2-315 SEC3
Adder
2.037
253372AE2-315 SEC3
Adder
2.037
25306009OHH W.
Adder
3.033
3429211JKCT 2G
Adder
10.852
241972AD1-140 GEN
Solar/Wind Harmer
4.019
253338AC1-165 GEN
Solar/Wind Harmer
0.945
253343AC1-166 GEN
Solar/Wind Harmer
0.945
270356AE2-297 GEN
Solar/Wind Harmer
3.987
971029AG2-637 GEN
Solar/Wind Harmer
12.539
270543AE2-219 C
Solar/Wind Harmer
7.986
247536S-71 GEN
Solar/Wind Harmer
3.092
964611AG1-324 GEN
Solar/Wind Harmer
2.831
961761AG1-017 GEN
Solar/Wind Harmer
0.309
945581AF1-223 GEN
Solar/Wind Harmer
3.114
945631AF1-228 GEN
Solar/Wind Harmer
3.07
958711AF2-162 GEN
Solar/Wind Harmer
0.655
943861AF1-054 GEN
Solar/Wind Harmer
2.451
943851AF1-053 GEN
Solar/Wind Harmer
1.184
970289AG2-191 GEN
Solar/Wind Harmer
1.202
24729505KEY G4
Adder
3.936
270291AC1-194 GEN
Solar/Wind Harmer
2.922
270444AC2-157 GEN1
Solar/Wind Harmer
3.091
270445AC2-157 GEN2
Solar/Wind Harmer
3.091
963791AG1-232 GEN
Solar/Wind Harmer
7.435
241955AC1-078 GEN
Solar/Wind Harmer
4.102
241973AD2-163_GEN1
Solar/Wind Harmer
1.085
241974AD2-163_GEN2
Solar/Wind Harmer
1.085
963841AG1-237 GEN
Solar/Wind Harmer
5.506
24386405FR-21G C
Solar/Wind Harmer
2.11
24387005FR-3G C
Solar/Wind Harmer
1.94
270071AF1-092 GEN
Solar/Wind Harmer
7.35
944221AF1-090 GEN
Solar/Wind Harmer
5.351
276763AC1-053 GEN1
Solar/Wind Harmer
1.897
276764AC1-053 GEN2
Solar/Wind Harmer
1.897
276668AB2-070 GEN1
Solar/Wind Harmer
1.062
276848AB2-070 GEN3
Solar/Wind Harmer
1.062
276849AB2-070 GEN2
Solar/Wind Harmer
1.062
946581AF1-322 GEN
Solar/Wind Harmer
4.858
24691005MDL-2G C
Solar/Wind Harmer
1.756
274731ELWOOD EC;2P
Adder
7.239
274733ELWOOD EC;3P
Adder
7.239
274735ELWOOD EC;4P
Adder
7.239
274728ELWOOD EC;5P
Adder
7.239
972228AH1-698 GEN2
Adder
1.631
972227AH1-698 GEN1
Adder
1.148
274800UNIV PARK;3U
Adder
2.561
274801UNIV PARK;4U
Adder
2.561
274675JOLIET 29;7U
Adder
13.475
274675JOLIET 29;7U
Adder
12.994
274687WILL CNTY;4U
Adder
12.271
274687WILL CNTY;4U
Adder
12.271
972037AH1-567 GEN1
Adder
0.08
274744AC1-111 GEN8
Adder
2.453
274746AC1-111 G10
Adder
2.453
274827FISK ;RP
Adder
3.404
972267AH1-718 GEN
Adder
1.824
24803406KYGER 5HP
50/50
4.427
24803206KYGER 4HP
50/50
4.417
253316AC1-085 GEN3
Solar/Wind Harmer
11.681
946171AF1-282 GEN
Solar/Wind Harmer
13.952
252516AE2-318_GEN
Solar/Wind Harmer
13.939
25196808ZIMRHP
Adder
103.883
270273AD2-016 GEN
Solar/Wind Harmer
3.628
252510AF1-249 C
Solar/Wind Harmer
0.552
25194608D.CRK4
Adder
2.171
253398AE2-221_GEN2
Solar/Wind Harmer
5.919
25196008MFTGT1
Adder
1.705
945681AF1-233 GEN
Solar/Wind Harmer
23.016
339221AD2-048_GEN
Solar/Wind Harmer
1.678
253370AE2-315 SEC1
Adder
2.154
253371AE2-315 SEC2
Adder
2.037
25326309TAIT D
Adder
1.136
270222AC2-111 GEN
Solar/Wind Harmer
4.57
944031AF1-071 GEN
Solar/Wind Harmer
1.028
943111AE2-339 GEN
Solar/Wind Harmer
0.888
3429421JKCT 10G
Adder
8.012
3429241JKCT 3G
Adder
10.994
253333AC1-068 GEN
Solar/Wind Harmer
0.911
942081AE2-220 GEN
Solar/Wind Harmer
5.25
270209AC1-174_GEN
Solar/Wind Harmer
3.341
270437AC2-090 C
Solar/Wind Harmer
4.582
270239V3-007_GEN1
Solar/Wind Harmer
1.413
339211AE2-254 GEN
Solar/Wind Harmer
1.157
270005AE1-210 C O1
Solar/Wind Harmer
4.08
24728605AND G2
Adder
2.824
970825AG2-519 GEN
Solar/Wind Harmer
1.543
971073AG2-665 GEN
Solar/Wind Harmer
0.808
945371AF1-202 GEN
Solar/Wind Harmer
4.791
970653AG2-424 GEN
Solar/Wind Harmer
3.289
276903AD2-071 C
Solar/Wind Harmer
6.734
958861AF2-177 GEN
Solar/Wind Harmer
7.226
270594AE1-207 GEN
Solar/Wind Harmer
8.954
270032AE2-172
Solar/Wind Harmer
3.066
270024AE2-089 GEN
Solar/Wind Harmer
3.071
965651AG1-433 GEN
Solar/Wind Harmer
3.54
339241AF1-083 GEN
Solar/Wind Harmer
1.047
964901AG1-354 GEN
Solar/Wind Harmer
8.68
970091AG2-072 GEN
Adder
41.08
963741AG1-226 GEN
Solar/Wind Harmer
23.222
24385905FR-11G C
Solar/Wind Harmer
4.077
24386605FR-22G C
Solar/Wind Harmer
2.11
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276621W2-048 GEN
Solar/Wind Harmer
2.997
276686W4-005 GEN3
Solar/Wind Harmer
1.451
24791305MDL-5G
Solar/Wind Harmer
1.145
274732ELWOOD EC;7P
Adder
7.239
274674JOLIET 9 ;6U
Adder
6.773
274676JOLIET 29;8U
Adder
13.475
274802UNIV PARK;5U
Adder
2.56
274745AC1-111 GEN9
Adder
2.453
274812UNIV PK N;8U
Adder
2.195
274682WAUKEGAN ;7U
Adder
7.875
274828WAUKEGAN ;BP
Adder
4.839
274761LEE CO EC;2U
Adder
4.074
274766LEE CO EC;7U
Adder
4.026
274723RIVER EC ;12
Adder
7.842
960001AF2-291 GEN
Solar/Wind Helper
1.495
270331AC1-082 GEN3
Solar/Wind Helper
0.169
235780M24_1
Solar/Wind Helper
0.532
24803006KYGER 3HP
50/50
4.478
24802806KYGER 2HP
50/50
4.462
24802906KYGER 2LP
50/50
2.619
25183008BIOENL
50/50
0.04
252509AD1-136 GEN
Solar/Wind Harmer
0.382
25183208HLCRTG
Solar/Wind Harmer
8.726
270269AC2-059
Solar/Wind Harmer
12.725
25194408D.CRK1
Adder
9.987
25194508D.CRK3
Adder
1.867
253415AE1-040 GEN
Solar/Wind Harmer
1.391
962581AG1-107 GEN
Solar/Wind Harmer
6.139
961491AF2-440 GEN
Solar/Wind Harmer
2.552
253370AE2-315 SEC1
Adder
2.154
972043AH1-570 GEN
Solar/Wind Harmer
2.668
972045AH1-571 GEN
Solar/Wind Harmer
2.134
25322209TAIT E
Adder
10.12
25322209TAIT E
Adder
9.892
253349AC2-067 GEN
Solar/Wind Harmer
2.068
253400AC2-068 GEN
Solar/Wind Harmer
0.832
25326109MON D
Adder
1.335
971125AH1-004 GEN
Solar/Wind Harmer
4.054
970107AG2-081 GEN
Solar/Wind Harmer
3.041
942891AE2-308 GEN
Solar/Wind Harmer
9.049
926881AC1-175 GEN
Solar/Wind Harmer
4.582
270383AD1-128 GEN
Solar/Wind Harmer
4.96
970883AG2-550 GEN
Solar/Wind Harmer
7.986
970885AG2-551 GEN
Solar/Wind Harmer
1.857
247621Y3-024
Adder
0.179
25326509SID D
Adder
0.961
964611AG1-324 GEN
Solar/Wind Harmer
0.38
270201AC2-176 GEN
Solar/Wind Harmer
3.708
964571AG1-320 GEN
Solar/Wind Harmer
5.837
971073AG2-665 GEN
Solar/Wind Harmer
5.557
970879AG2-548 GEN
Solar/Wind Harmer
0.808
24725505WLD G2 C
Solar/Wind Harmer
2.754
24699105WLD G1 C
Solar/Wind Harmer
2.722
253378AE2-206_GEN
Solar/Wind Harmer
2.463
270031AE2-169
Solar/Wind Harmer
5.579
270599AE1-208 GEN
Solar/Wind Harmer
5.579
944541AF1-119 GEN
Solar/Wind Harmer
2.712
960971AF2-388 GEN
Solar/Wind Harmer
7.079
942861AE2-305 GEN
Solar/Wind Harmer
4.965
970291AG2-192 GEN
Solar/Wind Harmer
0.823
970291AG2-192 GEN
Solar/Wind Harmer
0.265
942221AE2-234 GEN
Solar/Wind Harmer
2.13
339236AF1-050_GEN
Solar/Wind Harmer
1.062
945391AF1-204 GEN
Solar/Wind Harmer
7.777
339231AF1-038_GEN
Solar/Wind Harmer
1.01
927014AC1-188 GEN
Solar/Wind Harmer
0.86
964781AG1-341 GEN
Solar/Wind Harmer
5.607
253383AE2-342_GEN
Solar/Wind Harmer
0.463
970241AG2-163 GEN
Solar/Wind Harmer
12.901
971485AH1-239 GEN
Solar/Wind Harmer
3.962
24387305FR-4G C
Solar/Wind Harmer
2.492
966841AG1-555 GEN
Solar/Wind Harmer
1.232
966021AG1-471 GEN
Solar/Wind Harmer
2.631
276916AD2-100_GEN
Solar/Wind Harmer
10.179
276911AD2-131_GEN
Solar/Wind Harmer
2.057
276615X2-022 GEN
Solar/Wind Harmer
0.941
276838X2-022 GEN2
Solar/Wind Harmer
0.112
274880W4-005 GEN4
Solar/Wind Harmer
1.451
276174W4-005 GEN2
Solar/Wind Harmer
1.451
270180AB1-006 GEN1
Solar/Wind Harmer
3.414
24697605MDL-3G C
Solar/Wind Harmer
1.75
24755605MDL-5G
Solar/Wind Harmer
1.145
24697905MDL-4G C
Solar/Wind Harmer
1.089
270181AB1-006 GEN2
Solar/Wind Harmer
0.34
274674JOLIET 9 ;6U
Adder
6.773
274696ROCKY RD ;4P
Adder
4.997
274695ROCKY RD ;2P
Adder
4.881
274693ROCKY RD ;1P
Adder
4.833
274697ROCKY RD ;3P
Adder
1.326
274805UNIV PK N;1U
Adder
2.2
274808UNIV PK N;4U
Adder
2.186
274683WAUKEGAN ;8U
Adder
9.232
274683WAUKEGAN ;8U
Adder
7.782
274764LEE CO EC;5U
Adder
4.084
274765LEE CO EC;6U
Adder
4.084
274762LEE CO EC;3U
Adder
4.074
274763LEE CO EC;4U
Adder
4.036
237033AB1-150 GEN
Solar/Wind Helper
0.429
24803106KYGER 3LP
50/50
2.637
24803306KYGER 4LP
50/50
2.583
971191AH1-055 GEN
Solar/Wind Harmer
85.223
252507AC2-088 GEN
Solar/Wind Harmer
2.672
253317AC1-085 GEN4
Solar/Wind Harmer
11.681
946181AF1-283 GEN
Solar/Wind Harmer
18.138
252519AF1-045_GEN
Solar/Wind Harmer
5.073
25194608D.CRK4
Adder
2.171
252524AE2-267 GEN
Solar/Wind Harmer
2.074
25196608WSDLE5
Adder
11.291
958171AF2-111 GEN
Solar/Wind Harmer
32.8
253394AE2-221_GEN
Solar/Wind Harmer
5.919
270367AC2-061_GEN
Solar/Wind Harmer
3.968
270186AC1-089 GEN
Solar/Wind Harmer
7.496
972167AH1-666 GEN
Solar/Wind Harmer
9.813
25196008MFTGT1
Adder
1.652
339243AC2-075 GEN1
Solar/Wind Harmer
0.505
253303V4-073 C
Solar/Wind Harmer
0.125
253370AE2-315 SEC1
Adder
2.154
253371AE2-315 SEC2
Adder
2.037
960071AF2-298 GEN
Solar/Wind Harmer
1.548
3429391JKCT 9G
Adder
8.012
253325AC1-069 GEN
Solar/Wind Harmer
0.911
970093AG2-073 GEN
Solar/Wind Harmer
4.533
24379505HDWTR1G C
Solar/Wind Harmer
6.491
270240V3-007_GEN2
Solar/Wind Harmer
5.079
270518AE2-148 GEN
Solar/Wind Harmer
9.286
270004AE1-209 GEN
Solar/Wind Harmer
4.08
970455AG2-298 GEN
Solar/Wind Harmer
2.601
946031AF1-268 GEN
Solar/Wind Harmer
6.158
24728505AND G1
Adder
2.824
970825AG2-519 GEN
Solar/Wind Harmer
4.143
962031AG1-047 GEN
Solar/Wind Harmer
2.182
957741AF2-068 GEN
Solar/Wind Harmer
10.823
970879AG2-548 GEN
Solar/Wind Harmer
5.557
276820AF1-078_GEN
Solar/Wind Harmer
1.094
970653AG2-424 GEN
Solar/Wind Harmer
0.476
339206AE1-143 GEN
Solar/Wind Harmer
1.407
965461AG1-414 GEN
Solar/Wind Harmer
1.435
970289AG2-191 GEN
Solar/Wind Harmer
0.486
247642Z2-115 C
Solar/Wind Harmer
0.039
942051AE2-217 GEN
Solar/Wind Harmer
10.751
944531AF1-118 GEN
Solar/Wind Harmer
20.719
960801AF2-371 GEN
Solar/Wind Harmer
1.503
964871AG1-351 GEN
Solar/Wind Harmer
1.038
972273AH1-721 GEN
Adder
48.281
970193AG2-126 GEN
Solar/Wind Harmer
8.371
957541AF2-048 GEN
Solar/Wind Harmer
0.86
339255AE2-071 GEN
Solar/Wind Harmer
0.625
339250AF1-203 GEN
Solar/Wind Harmer
0.322
24386205FR-12G C
Solar/Wind Harmer
2.102
942481AE2-261 GEN
Solar/Wind Harmer
14.45
957381AF2-032 GEN
Solar/Wind Harmer
0.966
276785W4-005 GEN1
Solar/Wind Harmer
1.451
971993AH1-541 GEN
Solar/Wind Harmer
4.434
24690905MDL-1G C
Solar/Wind Harmer
3.811
274729ELWOOD EC;1P
Adder
7.239
274730ELWOOD EC;6P
Adder
7.239
274734ELWOOD EC;8P
Adder
7.239
274736ELWOOD EC;9P
Adder
7.239
972259AH1-714 GEN
Adder
8.385
972038AH1-567 GEN2
Adder
0.16
274676JOLIET 29;8U
Adder
12.994
274803UNIV PARK;6U
Adder
2.56
274826FISK ;BP
Adder
4.804
274814UNIV PK N;0U
Adder
2.215
274807UNIV PK N;3U
Adder
2.21
274811UNIV PK N;7U
Adder
2.195
274682WAUKEGAN ;7U
Adder
7.875
274760LEE CO EC;1U
Adder
4.074
274767LEE CO EC;8U
Adder
4.026
274724RIVER EC ;11
Adder
5.289
270330AC1-082 GEN2
Solar/Wind Helper
0.17
270329AC1-082 GEN1
Solar/Wind Helper
0.17
970781AG2-491 GEN
Solar/Wind Harmer
2.151
LAGNLTFEXP_LAGN->PJM
CLTF
5.53
TVALTFEXP_TVA->PJM
CLTF
2.623
NYPJM->LTFIMP_NY
CLTF
1.649
LGEELTFEXP_LGEE->PJM
CLTF
5.838
WECLTFEXP_WEC->PJM
CLTF
1.668
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.436
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.901
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CBM West 1LTFEXP_CBM-W1->PJM
CBM
67.865
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.827
MECLTFEXP_MEC->PJM
CLTF
7.138
SIGELTFEXP_SIGE->PJM
CLTF
0.35
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.263
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 48.28 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.49 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1901.76
MW Contribution:
38.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.088
24803206KYGER 4HP
50/50
4.079
252516AE2-318_GEN
Solar/Wind Harmer
10.884
25196808ZIMRHP
Adder
81.628
25194608D.CRK4
Adder
1.737
252510AF1-249 C
Solar/Wind Harmer
0.44
25196008MFTGT1
Adder
1.418
253316AC1-085 GEN3
Solar/Wind Harmer
8.517
946171AF1-282 GEN
Solar/Wind Harmer
10.173
253398AE2-221_GEN2
Solar/Wind Harmer
4.342
945681AF1-233 GEN
Solar/Wind Harmer
17.68
339221AD2-048_GEN
Solar/Wind Harmer
1.364
270273AD2-016 GEN
Solar/Wind Harmer
2.213
943111AE2-339 GEN
Solar/Wind Harmer
0.732
270222AC2-111 GEN
Solar/Wind Harmer
3.698
944031AF1-071 GEN
Solar/Wind Harmer
0.832
253370AE2-315 SEC1
Adder
1.629
253371AE2-315 SEC2
Adder
1.541
3429421JKCT 10G
Adder
6.632
970091AG2-072 GEN
Adder
60.833
25326309TAIT D
Adder
0.86
3429241JKCT 3G
Adder
9.168
339211AE2-254 GEN
Solar/Wind Harmer
1.029
942081AE2-220 GEN
Solar/Wind Harmer
4.355
270209AC1-174_GEN
Solar/Wind Harmer
2.771
270437AC2-090 C
Solar/Wind Harmer
3.8
270239V3-007_GEN1
Solar/Wind Harmer
1.172
970653AG2-424 GEN
Solar/Wind Harmer
3.113
24728605AND G2
Adder
2.452
270005AE1-210 C O1
Solar/Wind Harmer
3.373
970825AG2-519 GEN
Solar/Wind Harmer
1.27
339241AF1-083 GEN
Solar/Wind Harmer
0.988
253333AC1-068 GEN
Solar/Wind Harmer
0.611
945371AF1-202 GEN
Solar/Wind Harmer
3.908
964901AG1-354 GEN
Solar/Wind Harmer
8.361
276903AD2-071 C
Solar/Wind Harmer
5.516
958861AF2-177 GEN
Solar/Wind Harmer
5.856
270594AE1-207 GEN
Solar/Wind Harmer
7.241
270032AE2-172
Solar/Wind Harmer
2.48
270024AE2-089 GEN
Solar/Wind Harmer
2.452
965651AG1-433 GEN
Solar/Wind Harmer
2.858
963741AG1-226 GEN
Solar/Wind Harmer
20.834
965911AG1-460 GEN
Solar/Wind Harmer
0.634
276621W2-048 GEN
Solar/Wind Harmer
2.771
276686W4-005 GEN3
Solar/Wind Harmer
1.331
960001AF2-291 GEN
Solar/Wind Helper
1.708
270331AC1-082 GEN3
Solar/Wind Helper
0.192
235780M24_1
Solar/Wind Helper
0.478
24802606KYGER 1HP
50/50
4.165
24802706KYGER 1LP
50/50
2.442
24803506KYGER 5LP
50/50
2.385
971985AH1-537 GEN
Solar/Wind Harmer
50.232
25196408WSDLE3
Adder
9.326
25196108MFTGT2
Adder
1.564
25196108MFTGT2
Adder
1.452
253433AC1-085 GEN1
Solar/Wind Harmer
5.406
253432AC1-085 GEN2
Solar/Wind Harmer
0.272
972163AH1-664 GEN
Solar/Wind Harmer
9.279
972165AH1-665 GEN
Solar/Wind Harmer
7.424
339216AC1-074 GEN
Solar/Wind Harmer
1.517
253406AD2-031_GEN
Solar/Wind Harmer
1.147
270340AC2-060 GEN
Solar/Wind Harmer
2.587
270263AC1-001 GEN
Solar/Wind Harmer
0.87
253372AE2-315 SEC3
Adder
1.541
253372AE2-315 SEC3
Adder
1.541
25306009OHH W.
Adder
2.304
3429211JKCT 2G
Adder
9.05
270356AE2-297 GEN
Solar/Wind Harmer
3.35
971029AG2-637 GEN
Solar/Wind Harmer
10.129
241972AD1-140 GEN
Solar/Wind Harmer
2.94
270432AC2-029 GEN
Solar/Wind Harmer
4.54
270543AE2-219 C
Solar/Wind Harmer
6.457
270444AC2-157 GEN1
Solar/Wind Harmer
3.536
270445AC2-157 GEN2
Solar/Wind Harmer
3.536
247536S-71 GEN
Solar/Wind Harmer
2.502
964611AG1-324 GEN
Solar/Wind Harmer
2.301
961761AG1-017 GEN
Solar/Wind Harmer
0.25
253338AC1-165 GEN
Solar/Wind Harmer
0.633
253343AC1-166 GEN
Solar/Wind Harmer
0.633
945581AF1-223 GEN
Solar/Wind Harmer
2.541
958711AF2-162 GEN
Solar/Wind Harmer
0.529
970289AG2-191 GEN
Solar/Wind Harmer
0.966
24729505KEY G4
Adder
3.139
944221AF1-090 GEN
Solar/Wind Harmer
5.121
963841AG1-237 GEN
Solar/Wind Harmer
4.848
276763AC1-053 GEN1
Solar/Wind Harmer
1.744
276764AC1-053 GEN2
Solar/Wind Harmer
1.744
276668AB2-070 GEN1
Solar/Wind Harmer
0.974
276848AB2-070 GEN3
Solar/Wind Harmer
0.974
276849AB2-070 GEN2
Solar/Wind Harmer
0.974
943861AF1-054 GEN
Solar/Wind Harmer
1.665
943851AF1-053 GEN
Solar/Wind Harmer
0.805
24803006KYGER 3HP
50/50
4.136
24802806KYGER 2HP
50/50
4.121
24802906KYGER 2LP
50/50
2.418
25183008BIOENL
50/50
0.03
252509AD1-136 GEN
Solar/Wind Harmer
0.299
25183208HLCRTG
Solar/Wind Harmer
6.647
25194408D.CRK1
Adder
7.991
25194508D.CRK3
Adder
1.494
962581AG1-107 GEN
Solar/Wind Harmer
4.435
961491AF2-440 GEN
Solar/Wind Harmer
1.844
972043AH1-570 GEN
Solar/Wind Harmer
2.164
972045AH1-571 GEN
Solar/Wind Harmer
1.731
971125AH1-004 GEN
Solar/Wind Harmer
3.34
970107AG2-081 GEN
Solar/Wind Harmer
2.505
270269AC2-059
Solar/Wind Harmer
7.76
253415AE1-040 GEN
Solar/Wind Harmer
0.936
253370AE2-315 SEC1
Adder
1.629
25322209TAIT E
Adder
7.66
25322209TAIT E
Adder
7.488
253349AC2-067 GEN
Solar/Wind Harmer
1.584
253400AC2-068 GEN
Solar/Wind Harmer
0.637
25326109MON D
Adder
1.005
942891AE2-308 GEN
Solar/Wind Harmer
7.614
926881AC1-175 GEN
Solar/Wind Harmer
3.8
964571AG1-320 GEN
Solar/Wind Harmer
5.537
270383AD1-128 GEN
Solar/Wind Harmer
4.066
970883AG2-550 GEN
Solar/Wind Harmer
6.457
970885AG2-551 GEN
Solar/Wind Harmer
1.502
247621Y3-024
Adder
0.145
964611AG1-324 GEN
Solar/Wind Harmer
0.309
270201AC2-176 GEN
Solar/Wind Harmer
3.006
24725505WLD G2 C
Solar/Wind Harmer
2.27
24699105WLD G1 C
Solar/Wind Harmer
2.244
339236AF1-050_GEN
Solar/Wind Harmer
1.02
270031AE2-169
Solar/Wind Harmer
4.558
270599AE1-208 GEN
Solar/Wind Harmer
4.558
25326509SID D
Adder
0.702
339231AF1-038_GEN
Solar/Wind Harmer
0.965
945391AF1-204 GEN
Solar/Wind Harmer
7.373
944541AF1-119 GEN
Solar/Wind Harmer
2.19
960971AF2-388 GEN
Solar/Wind Harmer
5.716
964781AG1-341 GEN
Solar/Wind Harmer
5.52
970291AG2-192 GEN
Solar/Wind Harmer
0.661
970291AG2-192 GEN
Solar/Wind Harmer
0.213
253378AE2-206_GEN
Solar/Wind Harmer
1.774
971485AH1-239 GEN
Solar/Wind Harmer
3.886
942221AE2-234 GEN
Solar/Wind Harmer
1.69
966021AG1-471 GEN
Solar/Wind Harmer
2.588
970241AG2-163 GEN
Solar/Wind Harmer
11.574
276916AD2-100_GEN
Solar/Wind Harmer
9.604
276911AD2-131_GEN
Solar/Wind Harmer
1.941
276615X2-022 GEN
Solar/Wind Harmer
0.87
276838X2-022 GEN2
Solar/Wind Harmer
0.103
274880W4-005 GEN4
Solar/Wind Harmer
1.331
276174W4-005 GEN2
Solar/Wind Harmer
1.331
942861AE2-305 GEN
Solar/Wind Harmer
3.374
237033AB1-150 GEN
Solar/Wind Helper
0.386
24803106KYGER 3LP
50/50
2.435
24803306KYGER 4LP
50/50
2.385
971191AH1-055 GEN
Solar/Wind Harmer
71.732
252507AC2-088 GEN
Solar/Wind Harmer
2.093
252519AF1-045_GEN
Solar/Wind Harmer
3.961
252524AE2-267 GEN
Solar/Wind Harmer
1.664
25196608WSDLE5
Adder
9.059
25194608D.CRK4
Adder
1.737
25196008MFTGT1
Adder
1.374
253317AC1-085 GEN4
Solar/Wind Harmer
8.517
946181AF1-283 GEN
Solar/Wind Harmer
13.225
958171AF2-111 GEN
Solar/Wind Harmer
24.984
253394AE2-221_GEN
Solar/Wind Harmer
4.342
972167AH1-666 GEN
Solar/Wind Harmer
7.533
270367AC2-061_GEN
Solar/Wind Harmer
2.88
339243AC2-075 GEN1
Solar/Wind Harmer
0.411
270186AC1-089 GEN
Solar/Wind Harmer
5.474
253303V4-073 C
Solar/Wind Harmer
0.094
253370AE2-315 SEC1
Adder
1.629
253371AE2-315 SEC2
Adder
1.541
3429391JKCT 9G
Adder
6.632
960071AF2-298 GEN
Solar/Wind Harmer
1.175
970093AG2-073 GEN
Solar/Wind Harmer
3.861
970455AG2-298 GEN
Solar/Wind Harmer
2.419
24379505HDWTR1G C
Solar/Wind Harmer
5.384
270240V3-007_GEN2
Solar/Wind Harmer
4.212
970653AG2-424 GEN
Solar/Wind Harmer
0.45
24728505AND G1
Adder
2.452
270004AE1-209 GEN
Solar/Wind Harmer
3.373
339206AE1-143 GEN
Solar/Wind Harmer
1.311
946031AF1-268 GEN
Solar/Wind Harmer
5.055
970825AG2-519 GEN
Solar/Wind Harmer
3.411
962031AG1-047 GEN
Solar/Wind Harmer
1.769
957741AF2-068 GEN
Solar/Wind Harmer
8.774
253325AC1-069 GEN
Solar/Wind Harmer
0.611
972273AH1-721 GEN
Adder
45.289
970193AG2-126 GEN
Solar/Wind Harmer
7.936
270518AE2-148 GEN
Solar/Wind Harmer
6.377
339255AE2-071 GEN
Solar/Wind Harmer
0.613
339250AF1-203 GEN
Solar/Wind Harmer
0.316
965461AG1-414 GEN
Solar/Wind Harmer
1.153
970289AG2-191 GEN
Solar/Wind Harmer
0.39
276820AF1-078_GEN
Solar/Wind Harmer
0.788
247642Z2-115 C
Solar/Wind Harmer
0.031
944531AF1-118 GEN
Solar/Wind Harmer
16.445
942481AE2-261 GEN
Solar/Wind Harmer
13.577
957381AF2-032 GEN
Solar/Wind Harmer
0.906
276785W4-005 GEN1
Solar/Wind Harmer
1.331
971993AH1-541 GEN
Solar/Wind Harmer
4.067
270330AC1-082 GEN2
Solar/Wind Helper
0.193
270329AC1-082 GEN1
Solar/Wind Helper
0.193
LAGNLTFEXP_LAGN->PJM
CLTF
6.101
TVALTFEXP_TVA->PJM
CLTF
3.013
NYPJM->LTFIMP_NY
CLTF
1.477
LGEELTFEXP_LGEE->PJM
CLTF
5.581
WECLTFEXP_WEC->PJM
CLTF
1.413
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.272
AG2-052LTFEXP_AG2-052->PJM
LTF
0.09
AH1-155LTFEXP_AH1-155->PJM
LTF
0.135
CBM West 1LTFEXP_CBM-W1->PJM
CBM
57.337
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.776
MECLTFEXP_MEC->PJM
CLTF
6.502
SIGELTFEXP_SIGE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.85
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 45.29 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#1558_05BAKER 765_Q_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1558_05BAKER 765_Q_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.58 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1872.34
MW Contribution:
34.01
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1558_05BAKER 765_Q_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.08 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2295.78
MW Contribution:
35.52
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.206
24802706KYGER 1LP
50/50
2.466
24803506KYGER 5LP
50/50
2.408
971985AH1-537 GEN
Solar/Wind Harmer
50.38
25196408WSDLE3
Adder
9.236
253433AC1-085 GEN1
Solar/Wind Harmer
5.516
253432AC1-085 GEN2
Solar/Wind Harmer
0.278
25196108MFTGT2
Adder
1.524
25196108MFTGT2
Adder
1.415
253406AD2-031_GEN
Solar/Wind Harmer
1.174
972163AH1-664 GEN
Solar/Wind Harmer
9.177
972165AH1-665 GEN
Solar/Wind Harmer
7.342
270263AC1-001 GEN
Solar/Wind Harmer
0.943
270340AC2-060 GEN
Solar/Wind Harmer
2.713
339216AC1-074 GEN
Solar/Wind Harmer
1.469
253372AE2-315 SEC3
Adder
1.56
253372AE2-315 SEC3
Adder
1.56
25306009OHH W.
Adder
2.331
3429211JKCT 2G
Adder
8.597
270356AE2-297 GEN
Solar/Wind Harmer
3.32
270432AC2-029 GEN
Solar/Wind Harmer
4.963
971029AG2-637 GEN
Solar/Wind Harmer
10.225
241972AD1-140 GEN
Solar/Wind Harmer
3.018
270543AE2-219 C
Solar/Wind Harmer
6.542
24803006KYGER 3HP
50/50
4.176
24802806KYGER 2HP
50/50
4.16
24802906KYGER 2LP
50/50
2.442
25183008BIOENL
50/50
0.031
252509AD1-136 GEN
Solar/Wind Harmer
0.298
25183208HLCRTG
Solar/Wind Harmer
6.689
25194408D.CRK1
Adder
7.92
25194508D.CRK3
Adder
1.481
270269AC2-059
Solar/Wind Harmer
8.406
962581AG1-107 GEN
Solar/Wind Harmer
4.506
961491AF2-440 GEN
Solar/Wind Harmer
1.873
253415AE1-040 GEN
Solar/Wind Harmer
0.979
972043AH1-570 GEN
Solar/Wind Harmer
2.092
972045AH1-571 GEN
Solar/Wind Harmer
1.674
253370AE2-315 SEC1
Adder
1.65
971125AH1-004 GEN
Solar/Wind Harmer
3.204
970107AG2-081 GEN
Solar/Wind Harmer
2.403
25322209TAIT E
Adder
7.761
24803106KYGER 3LP
50/50
2.459
24803306KYGER 4LP
50/50
2.408
971191AH1-055 GEN
Solar/Wind Harmer
73.297
252507AC2-088 GEN
Solar/Wind Harmer
2.088
252519AF1-045_GEN
Solar/Wind Harmer
3.956
25194608D.CRK4
Adder
1.722
252524AE2-267 GEN
Solar/Wind Harmer
1.648
25196608WSDLE5
Adder
8.972
253317AC1-085 GEN4
Solar/Wind Harmer
8.691
946181AF1-283 GEN
Solar/Wind Harmer
13.495
958171AF2-111 GEN
Solar/Wind Harmer
24.929
25196008MFTGT1
Adder
1.339
253394AE2-221_GEN
Solar/Wind Harmer
4.427
972167AH1-666 GEN
Solar/Wind Harmer
7.467
270367AC2-061_GEN
Solar/Wind Harmer
2.92
270186AC1-089 GEN
Solar/Wind Harmer
5.527
339243AC2-075 GEN1
Solar/Wind Harmer
0.398
253303V4-073 C
Solar/Wind Harmer
0.095
253370AE2-315 SEC1
Adder
1.65
253371AE2-315 SEC2
Adder
1.56
960071AF2-298 GEN
Solar/Wind Harmer
1.19
3429391JKCT 9G
Adder
6.331
970093AG2-073 GEN
Solar/Wind Harmer
3.624
24379505HDWTR1G C
Solar/Wind Harmer
5.386
270240V3-007_GEN2
Solar/Wind Harmer
4.214
24728505AND G1
Adder
2.416
970455AG2-298 GEN
Solar/Wind Harmer
2.202
270004AE1-209 GEN
Solar/Wind Harmer
3.403
253325AC1-069 GEN
Solar/Wind Harmer
0.646
946031AF1-268 GEN
Solar/Wind Harmer
5.127
970825AG2-519 GEN
Solar/Wind Harmer
3.46
962031AG1-047 GEN
Solar/Wind Harmer
1.807
957741AF2-068 GEN
Solar/Wind Harmer
8.963
970653AG2-424 GEN
Solar/Wind Harmer
0.406
270518AE2-148 GEN
Solar/Wind Harmer
6.717
339206AE1-143 GEN
Solar/Wind Harmer
1.183
965461AG1-414 GEN
Solar/Wind Harmer
1.232
970289AG2-191 GEN
Solar/Wind Harmer
0.417
247642Z2-115 C
Solar/Wind Harmer
0.034
276820AF1-078_GEN
Solar/Wind Harmer
0.821
970193AG2-126 GEN
Solar/Wind Harmer
7.665
944531AF1-118 GEN
Solar/Wind Harmer
17.273
972273AH1-721 GEN
Adder
40.144
339255AE2-071 GEN
Solar/Wind Harmer
0.539
339250AF1-203 GEN
Solar/Wind Harmer
0.277
24386205FR-12G C
Solar/Wind Harmer
1.932
942481AE2-261 GEN
Solar/Wind Harmer
13.191
957381AF2-032 GEN
Solar/Wind Harmer
0.881
276785W4-005 GEN1
Solar/Wind Harmer
1.319
971993AH1-541 GEN
Solar/Wind Harmer
4.03
24690905MDL-1G C
Solar/Wind Harmer
3.492
970781AG2-491 GEN
Solar/Wind Harmer
4.35
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
247536S-71 GEN
Solar/Wind Harmer
2.544
253338AC1-165 GEN
Solar/Wind Harmer
0.67
253343AC1-166 GEN
Solar/Wind Harmer
0.67
964611AG1-324 GEN
Solar/Wind Harmer
2.347
961761AG1-017 GEN
Solar/Wind Harmer
0.256
945581AF1-223 GEN
Solar/Wind Harmer
2.597
270444AC2-157 GEN1
Solar/Wind Harmer
3.034
270445AC2-157 GEN2
Solar/Wind Harmer
3.034
970289AG2-191 GEN
Solar/Wind Harmer
1.032
958711AF2-162 GEN
Solar/Wind Harmer
0.546
24729505KEY G4
Adder
3.282
963841AG1-237 GEN
Solar/Wind Harmer
5.056
945631AF1-228 GEN
Solar/Wind Harmer
2.147
943861AF1-054 GEN
Solar/Wind Harmer
1.763
943851AF1-053 GEN
Solar/Wind Harmer
0.852
963791AG1-232 GEN
Solar/Wind Harmer
6.128
24386405FR-21G C
Solar/Wind Harmer
1.939
24387005FR-3G C
Solar/Wind Harmer
1.783
944221AF1-090 GEN
Solar/Wind Harmer
4.903
276763AC1-053 GEN1
Solar/Wind Harmer
1.725
276764AC1-053 GEN2
Solar/Wind Harmer
1.725
276668AB2-070 GEN1
Solar/Wind Harmer
0.965
276848AB2-070 GEN3
Solar/Wind Harmer
0.965
276849AB2-070 GEN2
Solar/Wind Harmer
0.965
946581AF1-322 GEN
Solar/Wind Harmer
4.451
24691005MDL-2G C
Solar/Wind Harmer
1.609
25322209TAIT E
Adder
7.587
253349AC2-067 GEN
Solar/Wind Harmer
1.601
253400AC2-068 GEN
Solar/Wind Harmer
0.644
25326109MON D
Adder
1.02
942891AE2-308 GEN
Solar/Wind Harmer
7.202
926881AC1-175 GEN
Solar/Wind Harmer
3.802
270383AD1-128 GEN
Solar/Wind Harmer
4.093
970883AG2-550 GEN
Solar/Wind Harmer
6.542
970885AG2-551 GEN
Solar/Wind Harmer
1.521
247621Y3-024
Adder
0.148
964571AG1-320 GEN
Solar/Wind Harmer
5.012
964611AG1-324 GEN
Solar/Wind Harmer
0.315
270201AC2-176 GEN
Solar/Wind Harmer
3.071
24725505WLD G2 C
Solar/Wind Harmer
2.34
24699105WLD G1 C
Solar/Wind Harmer
2.313
270031AE2-169
Solar/Wind Harmer
4.672
270599AE1-208 GEN
Solar/Wind Harmer
4.672
25326509SID D
Adder
0.727
970291AG2-192 GEN
Solar/Wind Harmer
0.706
970291AG2-192 GEN
Solar/Wind Harmer
0.227
944541AF1-119 GEN
Solar/Wind Harmer
2.261
960971AF2-388 GEN
Solar/Wind Harmer
5.903
253378AE2-206_GEN
Solar/Wind Harmer
1.848
945391AF1-204 GEN
Solar/Wind Harmer
7.122
942221AE2-234 GEN
Solar/Wind Harmer
1.774
339236AF1-050_GEN
Solar/Wind Harmer
0.907
970241AG2-163 GEN
Solar/Wind Harmer
11.839
339231AF1-038_GEN
Solar/Wind Harmer
0.852
942861AE2-305 GEN
Solar/Wind Harmer
3.571
964781AG1-341 GEN
Solar/Wind Harmer
4.844
24387305FR-4G C
Solar/Wind Harmer
2.29
966841AG1-555 GEN
Solar/Wind Harmer
1.132
276916AD2-100_GEN
Solar/Wind Harmer
9.299
276911AD2-131_GEN
Solar/Wind Harmer
1.879
276615X2-022 GEN
Solar/Wind Harmer
0.857
276838X2-022 GEN2
Solar/Wind Harmer
0.102
274880W4-005 GEN4
Solar/Wind Harmer
1.319
276174W4-005 GEN2
Solar/Wind Harmer
1.319
270180AB1-006 GEN1
Solar/Wind Harmer
3.129
24697605MDL-3G C
Solar/Wind Harmer
1.604
24755605MDL-5G
Solar/Wind Harmer
1.049
24697905MDL-4G C
Solar/Wind Harmer
0.998
270181AB1-006 GEN2
Solar/Wind Harmer
0.311
237033AB1-150 GEN
Solar/Wind Helper
0.389
24803406KYGER 5HP
50/50
4.128
24803206KYGER 4HP
50/50
4.118
252516AE2-318_GEN
Solar/Wind Harmer
10.869
25196808ZIMRHP
Adder
81.158
25194608D.CRK4
Adder
1.722
252510AF1-249 C
Solar/Wind Harmer
0.436
253316AC1-085 GEN3
Solar/Wind Harmer
8.691
946171AF1-282 GEN
Solar/Wind Harmer
10.381
25196008MFTGT1
Adder
1.383
253398AE2-221_GEN2
Solar/Wind Harmer
4.427
945681AF1-233 GEN
Solar/Wind Harmer
17.516
270273AD2-016 GEN
Solar/Wind Harmer
2.397
339221AD2-048_GEN
Solar/Wind Harmer
1.32
270222AC2-111 GEN
Solar/Wind Harmer
3.68
944031AF1-071 GEN
Solar/Wind Harmer
0.828
253370AE2-315 SEC1
Adder
1.65
253371AE2-315 SEC2
Adder
1.56
25326309TAIT D
Adder
0.871
943111AE2-339 GEN
Solar/Wind Harmer
0.702
3429421JKCT 10G
Adder
6.331
3429241JKCT 3G
Adder
8.71
942081AE2-220 GEN
Solar/Wind Harmer
4.357
270209AC1-174_GEN
Solar/Wind Harmer
2.772
270437AC2-090 C
Solar/Wind Harmer
3.802
270239V3-007_GEN1
Solar/Wind Harmer
1.172
24728605AND G2
Adder
2.416
339211AE2-254 GEN
Solar/Wind Harmer
0.948
270005AE1-210 C O1
Solar/Wind Harmer
3.403
253333AC1-068 GEN
Solar/Wind Harmer
0.646
970825AG2-519 GEN
Solar/Wind Harmer
1.289
970091AG2-072 GEN
Adder
45.609
970653AG2-424 GEN
Solar/Wind Harmer
2.807
276903AD2-071 C
Solar/Wind Harmer
5.743
945371AF1-202 GEN
Solar/Wind Harmer
3.996
270594AE1-207 GEN
Solar/Wind Harmer
7.628
270032AE2-172
Solar/Wind Harmer
2.612
958861AF2-177 GEN
Solar/Wind Harmer
6.026
270024AE2-089 GEN
Solar/Wind Harmer
2.54
965651AG1-433 GEN
Solar/Wind Harmer
2.952
339241AF1-083 GEN
Solar/Wind Harmer
0.886
972203AH1-686 GEN
Adder
1.224
964901AG1-354 GEN
Solar/Wind Harmer
7.42
963741AG1-226 GEN
Solar/Wind Harmer
21.31
24385905FR-11G C
Solar/Wind Harmer
3.747
24386605FR-22G C
Solar/Wind Harmer
1.939
965911AG1-460 GEN
Solar/Wind Harmer
0.616
276621W2-048 GEN
Solar/Wind Harmer
2.728
276686W4-005 GEN3
Solar/Wind Harmer
1.319
24791305MDL-5G
Solar/Wind Harmer
1.049
960001AF2-291 GEN
Solar/Wind Helper
1.672
270331AC1-082 GEN3
Solar/Wind Helper
0.186
235780M24_1
Solar/Wind Helper
0.482
LAGNLTFEXP_LAGN->PJM
CLTF
5.106
TVALTFEXP_TVA->PJM
CLTF
2.41
NYPJM->LTFIMP_NY
CLTF
1.475
LGEELTFEXP_LGEE->PJM
CLTF
5.052
WECLTFEXP_WEC->PJM
CLTF
1.492
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.65
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.296
AG2-052LTFEXP_AG2-052->PJM
LTF
0.097
AH1-155LTFEXP_AH1-155->PJM
LTF
0.146
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.717
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.398
MECLTFEXP_MEC->PJM
CLTF
6.442
SIGELTFEXP_SIGE->PJM
CLTF
0.309
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.237
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 40.14 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 41.93 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#309_05HANG R 765_B2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#309_05HANG R 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.32 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1868.38
MW Contribution:
34.43
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#309_05HANG R 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.69 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2289.82
MW Contribution:
35.86
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.127
24803206KYGER 4HP
50/50
4.117
252516AE2-318_GEN
Solar/Wind Harmer
10.863
25196808ZIMRHP
Adder
81.128
25194608D.CRK4
Adder
1.721
252510AF1-249 C
Solar/Wind Harmer
0.436
253316AC1-085 GEN3
Solar/Wind Harmer
8.685
946171AF1-282 GEN
Solar/Wind Harmer
10.373
25196008MFTGT1
Adder
1.382
253398AE2-221_GEN2
Solar/Wind Harmer
4.423
945681AF1-233 GEN
Solar/Wind Harmer
17.553
270273AD2-016 GEN
Solar/Wind Harmer
2.392
339221AD2-048_GEN
Solar/Wind Harmer
1.323
270222AC2-111 GEN
Solar/Wind Harmer
3.676
944031AF1-071 GEN
Solar/Wind Harmer
0.827
253370AE2-315 SEC1
Adder
1.648
253371AE2-315 SEC2
Adder
1.558
943111AE2-339 GEN
Solar/Wind Harmer
0.704
25326309TAIT D
Adder
0.87
3429421JKCT 10G
Adder
6.355
3429241JKCT 3G
Adder
8.749
942081AE2-220 GEN
Solar/Wind Harmer
4.35
270209AC1-174_GEN
Solar/Wind Harmer
2.768
270437AC2-090 C
Solar/Wind Harmer
3.796
270239V3-007_GEN1
Solar/Wind Harmer
1.17
339211AE2-254 GEN
Solar/Wind Harmer
0.954
24728605AND G2
Adder
2.415
270005AE1-210 C O1
Solar/Wind Harmer
3.398
253333AC1-068 GEN
Solar/Wind Harmer
0.644
970825AG2-519 GEN
Solar/Wind Harmer
1.287
970091AG2-072 GEN
Adder
45.51
970653AG2-424 GEN
Solar/Wind Harmer
2.823
276903AD2-071 C
Solar/Wind Harmer
5.733
24802606KYGER 1HP
50/50
4.205
24802706KYGER 1LP
50/50
2.465
24803506KYGER 5LP
50/50
2.408
971985AH1-537 GEN
Solar/Wind Harmer
50.362
25196408WSDLE3
Adder
9.229
253433AC1-085 GEN1
Solar/Wind Harmer
5.512
253432AC1-085 GEN2
Solar/Wind Harmer
0.277
25196108MFTGT2
Adder
1.523
25196108MFTGT2
Adder
1.414
972163AH1-664 GEN
Solar/Wind Harmer
9.198
972165AH1-665 GEN
Solar/Wind Harmer
7.358
253406AD2-031_GEN
Solar/Wind Harmer
1.174
270263AC1-001 GEN
Solar/Wind Harmer
0.941
270340AC2-060 GEN
Solar/Wind Harmer
2.71
339216AC1-074 GEN
Solar/Wind Harmer
1.472
253372AE2-315 SEC3
Adder
1.558
253372AE2-315 SEC3
Adder
1.558
25306009OHH W.
Adder
2.328
3429211JKCT 2G
Adder
8.636
270356AE2-297 GEN
Solar/Wind Harmer
3.317
270432AC2-029 GEN
Solar/Wind Harmer
4.949
971029AG2-637 GEN
Solar/Wind Harmer
10.209
241972AD1-140 GEN
Solar/Wind Harmer
3.011
270543AE2-219 C
Solar/Wind Harmer
6.531
247536S-71 GEN
Solar/Wind Harmer
2.539
253338AC1-165 GEN
Solar/Wind Harmer
0.668
253343AC1-166 GEN
Solar/Wind Harmer
0.668
24803106KYGER 3LP
50/50
2.459
24803306KYGER 4LP
50/50
2.408
971191AH1-055 GEN
Solar/Wind Harmer
73.271
252507AC2-088 GEN
Solar/Wind Harmer
2.087
252519AF1-045_GEN
Solar/Wind Harmer
3.954
25194608D.CRK4
Adder
1.721
252524AE2-267 GEN
Solar/Wind Harmer
1.647
25196608WSDLE5
Adder
8.965
253317AC1-085 GEN4
Solar/Wind Harmer
8.685
946181AF1-283 GEN
Solar/Wind Harmer
13.485
958171AF2-111 GEN
Solar/Wind Harmer
24.946
25196008MFTGT1
Adder
1.338
253394AE2-221_GEN
Solar/Wind Harmer
4.423
972167AH1-666 GEN
Solar/Wind Harmer
7.482
270367AC2-061_GEN
Solar/Wind Harmer
2.924
270186AC1-089 GEN
Solar/Wind Harmer
5.537
339243AC2-075 GEN1
Solar/Wind Harmer
0.399
253303V4-073 C
Solar/Wind Harmer
0.095
253370AE2-315 SEC1
Adder
1.648
253371AE2-315 SEC2
Adder
1.558
960071AF2-298 GEN
Solar/Wind Harmer
1.188
3429391JKCT 9G
Adder
6.355
970093AG2-073 GEN
Solar/Wind Harmer
3.645
24379505HDWTR1G C
Solar/Wind Harmer
5.379
270240V3-007_GEN2
Solar/Wind Harmer
4.208
970455AG2-298 GEN
Solar/Wind Harmer
2.212
24728505AND G1
Adder
2.415
270004AE1-209 GEN
Solar/Wind Harmer
3.398
253325AC1-069 GEN
Solar/Wind Harmer
0.644
946031AF1-268 GEN
Solar/Wind Harmer
5.118
970825AG2-519 GEN
Solar/Wind Harmer
3.455
962031AG1-047 GEN
Solar/Wind Harmer
1.803
957741AF2-068 GEN
Solar/Wind Harmer
8.946
970653AG2-424 GEN
Solar/Wind Harmer
0.408
339206AE1-143 GEN
Solar/Wind Harmer
1.192
270518AE2-148 GEN
Solar/Wind Harmer
6.693
965461AG1-414 GEN
Solar/Wind Harmer
1.229
970289AG2-191 GEN
Solar/Wind Harmer
0.416
247642Z2-115 C
Solar/Wind Harmer
0.034
276820AF1-078_GEN
Solar/Wind Harmer
0.818
970193AG2-126 GEN
Solar/Wind Harmer
7.659
944531AF1-118 GEN
Solar/Wind Harmer
17.224
972273AH1-721 GEN
Adder
40.637
339255AE2-071 GEN
Solar/Wind Harmer
0.544
339250AF1-203 GEN
Solar/Wind Harmer
0.28
24386205FR-12G C
Solar/Wind Harmer
1.927
942481AE2-261 GEN
Solar/Wind Harmer
13.196
957381AF2-032 GEN
Solar/Wind Harmer
0.881
276785W4-005 GEN1
Solar/Wind Harmer
1.319
971993AH1-541 GEN
Solar/Wind Harmer
4.029
24690905MDL-1G C
Solar/Wind Harmer
3.482
970781AG2-491 GEN
Solar/Wind Harmer
4.338
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
24803006KYGER 3HP
50/50
4.175
24802806KYGER 2HP
50/50
4.16
24802906KYGER 2LP
50/50
2.441
25183008BIOENL
50/50
0.031
252509AD1-136 GEN
Solar/Wind Harmer
0.298
25183208HLCRTG
Solar/Wind Harmer
6.685
25194408D.CRK1
Adder
7.915
25194508D.CRK3
Adder
1.48
270269AC2-059
Solar/Wind Harmer
8.388
962581AG1-107 GEN
Solar/Wind Harmer
4.512
961491AF2-440 GEN
Solar/Wind Harmer
1.875
253415AE1-040 GEN
Solar/Wind Harmer
0.978
972043AH1-570 GEN
Solar/Wind Harmer
2.098
972045AH1-571 GEN
Solar/Wind Harmer
1.678
253370AE2-315 SEC1
Adder
1.648
971125AH1-004 GEN
Solar/Wind Harmer
3.214
970107AG2-081 GEN
Solar/Wind Harmer
2.411
25322209TAIT E
Adder
7.75
25322209TAIT E
Adder
7.575
253349AC2-067 GEN
Solar/Wind Harmer
1.598
253400AC2-068 GEN
Solar/Wind Harmer
0.643
25326109MON D
Adder
1.019
942891AE2-308 GEN
Solar/Wind Harmer
7.237
926881AC1-175 GEN
Solar/Wind Harmer
3.796
270383AD1-128 GEN
Solar/Wind Harmer
4.087
970883AG2-550 GEN
Solar/Wind Harmer
6.531
970885AG2-551 GEN
Solar/Wind Harmer
1.519
964571AG1-320 GEN
Solar/Wind Harmer
5.034
247621Y3-024
Adder
0.147
964611AG1-324 GEN
Solar/Wind Harmer
0.314
270201AC2-176 GEN
Solar/Wind Harmer
3.065
24725505WLD G2 C
Solar/Wind Harmer
2.336
24699105WLD G1 C
Solar/Wind Harmer
2.309
270031AE2-169
Solar/Wind Harmer
4.663
270599AE1-208 GEN
Solar/Wind Harmer
4.663
25326509SID D
Adder
0.725
970291AG2-192 GEN
Solar/Wind Harmer
0.704
970291AG2-192 GEN
Solar/Wind Harmer
0.227
944541AF1-119 GEN
Solar/Wind Harmer
2.256
960971AF2-388 GEN
Solar/Wind Harmer
5.889
253378AE2-206_GEN
Solar/Wind Harmer
1.841
945391AF1-204 GEN
Solar/Wind Harmer
7.115
942221AE2-234 GEN
Solar/Wind Harmer
1.77
339236AF1-050_GEN
Solar/Wind Harmer
0.915
339231AF1-038_GEN
Solar/Wind Harmer
0.862
970241AG2-163 GEN
Solar/Wind Harmer
11.818
964781AG1-341 GEN
Solar/Wind Harmer
4.895
942861AE2-305 GEN
Solar/Wind Harmer
3.555
24387305FR-4G C
Solar/Wind Harmer
2.284
966841AG1-555 GEN
Solar/Wind Harmer
1.129
276916AD2-100_GEN
Solar/Wind Harmer
9.304
276911AD2-131_GEN
Solar/Wind Harmer
1.88
276615X2-022 GEN
Solar/Wind Harmer
0.857
276838X2-022 GEN2
Solar/Wind Harmer
0.102
274880W4-005 GEN4
Solar/Wind Harmer
1.319
276174W4-005 GEN2
Solar/Wind Harmer
1.319
270180AB1-006 GEN1
Solar/Wind Harmer
3.12
24697605MDL-3G C
Solar/Wind Harmer
1.599
24755605MDL-5G
Solar/Wind Harmer
1.046
24697905MDL-4G C
Solar/Wind Harmer
0.995
270181AB1-006 GEN2
Solar/Wind Harmer
0.31
237033AB1-150 GEN
Solar/Wind Helper
0.389
964611AG1-324 GEN
Solar/Wind Harmer
2.343
961761AG1-017 GEN
Solar/Wind Harmer
0.255
945581AF1-223 GEN
Solar/Wind Harmer
2.592
270444AC2-157 GEN1
Solar/Wind Harmer
3.031
270445AC2-157 GEN2
Solar/Wind Harmer
3.031
970289AG2-191 GEN
Solar/Wind Harmer
1.03
958711AF2-162 GEN
Solar/Wind Harmer
0.545
24729505KEY G4
Adder
3.273
963841AG1-237 GEN
Solar/Wind Harmer
5.045
945631AF1-228 GEN
Solar/Wind Harmer
2.136
943861AF1-054 GEN
Solar/Wind Harmer
1.755
943851AF1-053 GEN
Solar/Wind Harmer
0.848
963791AG1-232 GEN
Solar/Wind Harmer
6.108
24386405FR-21G C
Solar/Wind Harmer
1.934
24387005FR-3G C
Solar/Wind Harmer
1.779
944221AF1-090 GEN
Solar/Wind Harmer
4.906
276763AC1-053 GEN1
Solar/Wind Harmer
1.725
276764AC1-053 GEN2
Solar/Wind Harmer
1.725
276668AB2-070 GEN1
Solar/Wind Harmer
0.965
276848AB2-070 GEN3
Solar/Wind Harmer
0.965
276849AB2-070 GEN2
Solar/Wind Harmer
0.965
946581AF1-322 GEN
Solar/Wind Harmer
4.438
24691005MDL-2G C
Solar/Wind Harmer
1.604
945371AF1-202 GEN
Solar/Wind Harmer
3.988
270594AE1-207 GEN
Solar/Wind Harmer
7.612
270032AE2-172
Solar/Wind Harmer
2.607
958861AF2-177 GEN
Solar/Wind Harmer
6.012
270024AE2-089 GEN
Solar/Wind Harmer
2.534
965651AG1-433 GEN
Solar/Wind Harmer
2.945
339241AF1-083 GEN
Solar/Wind Harmer
0.893
972203AH1-686 GEN
Adder
1.213
964901AG1-354 GEN
Solar/Wind Harmer
7.489
963741AG1-226 GEN
Solar/Wind Harmer
21.272
24385905FR-11G C
Solar/Wind Harmer
3.737
24386605FR-22G C
Solar/Wind Harmer
1.934
965911AG1-460 GEN
Solar/Wind Harmer
0.616
276621W2-048 GEN
Solar/Wind Harmer
2.728
276686W4-005 GEN3
Solar/Wind Harmer
1.319
24791305MDL-5G
Solar/Wind Harmer
1.046
960001AF2-291 GEN
Solar/Wind Helper
1.673
270331AC1-082 GEN3
Solar/Wind Helper
0.186
235780M24_1
Solar/Wind Helper
0.482
LAGNLTFEXP_LAGN->PJM
CLTF
5.217
TVALTFEXP_TVA->PJM
CLTF
2.479
NYPJM->LTFIMP_NY
CLTF
1.479
LGEELTFEXP_LGEE->PJM
CLTF
5.06
WECLTFEXP_WEC->PJM
CLTF
1.491
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.262
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.6
AG2-052LTFEXP_AG2-052->PJM
LTF
0.097
AH1-155LTFEXP_AH1-155->PJM
LTF
0.145
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.663
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.617
MECLTFEXP_MEC->PJM
CLTF
6.459
SIGELTFEXP_SIGE->PJM
CLTF
0.31
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.694
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 40.64 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 42.34 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#1560_05BAKER 765_Q2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1560_05BAKER 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.04 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1864.08
MW Contribution:
34.4
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1560_05BAKER 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.55 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2287.64
MW Contribution:
35.84
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.458
24803306KYGER 4LP
50/50
2.407
971191AH1-055 GEN
Solar/Wind Harmer
73.235
252507AC2-088 GEN
Solar/Wind Harmer
2.085
252519AF1-045_GEN
Solar/Wind Harmer
3.95
25194608D.CRK4
Adder
1.719
252524AE2-267 GEN
Solar/Wind Harmer
1.646
25196608WSDLE5
Adder
8.957
253317AC1-085 GEN4
Solar/Wind Harmer
8.675
946181AF1-283 GEN
Solar/Wind Harmer
13.471
958171AF2-111 GEN
Solar/Wind Harmer
24.917
25196008MFTGT1
Adder
1.337
253394AE2-221_GEN
Solar/Wind Harmer
4.418
972167AH1-666 GEN
Solar/Wind Harmer
7.466
270367AC2-061_GEN
Solar/Wind Harmer
2.916
270186AC1-089 GEN
Solar/Wind Harmer
5.521
339243AC2-075 GEN1
Solar/Wind Harmer
0.398
253303V4-073 C
Solar/Wind Harmer
0.095
253370AE2-315 SEC1
Adder
1.646
253371AE2-315 SEC2
Adder
1.557
960071AF2-298 GEN
Solar/Wind Harmer
1.187
3429391JKCT 9G
Adder
6.347
970093AG2-073 GEN
Solar/Wind Harmer
3.638
24379505HDWTR1G C
Solar/Wind Harmer
5.374
270240V3-007_GEN2
Solar/Wind Harmer
4.204
970455AG2-298 GEN
Solar/Wind Harmer
2.21
24728505AND G1
Adder
2.412
270004AE1-209 GEN
Solar/Wind Harmer
3.395
253325AC1-069 GEN
Solar/Wind Harmer
0.643
946031AF1-268 GEN
Solar/Wind Harmer
5.113
970825AG2-519 GEN
Solar/Wind Harmer
3.451
962031AG1-047 GEN
Solar/Wind Harmer
1.802
957741AF2-068 GEN
Solar/Wind Harmer
8.938
970653AG2-424 GEN
Solar/Wind Harmer
0.408
339206AE1-143 GEN
Solar/Wind Harmer
1.191
270518AE2-148 GEN
Solar/Wind Harmer
6.685
965461AG1-414 GEN
Solar/Wind Harmer
1.228
970289AG2-191 GEN
Solar/Wind Harmer
0.415
247642Z2-115 C
Solar/Wind Harmer
0.034
276820AF1-078_GEN
Solar/Wind Harmer
0.817
970193AG2-126 GEN
Solar/Wind Harmer
7.653
944531AF1-118 GEN
Solar/Wind Harmer
17.208
972273AH1-721 GEN
Adder
40.6
339255AE2-071 GEN
Solar/Wind Harmer
0.544
339250AF1-203 GEN
Solar/Wind Harmer
0.28
24386205FR-12G C
Solar/Wind Harmer
1.925
942481AE2-261 GEN
Solar/Wind Harmer
13.188
957381AF2-032 GEN
Solar/Wind Harmer
0.881
276785W4-005 GEN1
Solar/Wind Harmer
1.318
971993AH1-541 GEN
Solar/Wind Harmer
4.027
24690905MDL-1G C
Solar/Wind Harmer
3.479
970781AG2-491 GEN
Solar/Wind Harmer
4.334
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
24803006KYGER 3HP
50/50
4.173
24802806KYGER 2HP
50/50
4.158
24802906KYGER 2LP
50/50
2.44
25183008BIOENL
50/50
0.031
252509AD1-136 GEN
Solar/Wind Harmer
0.298
25183208HLCRTG
Solar/Wind Harmer
6.678
25194408D.CRK1
Adder
7.907
25194508D.CRK3
Adder
1.478
270269AC2-059
Solar/Wind Harmer
8.376
962581AG1-107 GEN
Solar/Wind Harmer
4.499
961491AF2-440 GEN
Solar/Wind Harmer
1.87
253415AE1-040 GEN
Solar/Wind Harmer
0.977
972043AH1-570 GEN
Solar/Wind Harmer
2.094
972045AH1-571 GEN
Solar/Wind Harmer
1.675
253370AE2-315 SEC1
Adder
1.646
971125AH1-004 GEN
Solar/Wind Harmer
3.21
970107AG2-081 GEN
Solar/Wind Harmer
2.407
25322209TAIT E
Adder
7.741
25322209TAIT E
Adder
7.567
253349AC2-067 GEN
Solar/Wind Harmer
1.597
253400AC2-068 GEN
Solar/Wind Harmer
0.642
25326109MON D
Adder
1.017
942891AE2-308 GEN
Solar/Wind Harmer
7.225
926881AC1-175 GEN
Solar/Wind Harmer
3.793
270383AD1-128 GEN
Solar/Wind Harmer
4.083
970883AG2-550 GEN
Solar/Wind Harmer
6.525
970885AG2-551 GEN
Solar/Wind Harmer
1.517
964571AG1-320 GEN
Solar/Wind Harmer
5.03
247621Y3-024
Adder
0.147
964611AG1-324 GEN
Solar/Wind Harmer
0.314
270201AC2-176 GEN
Solar/Wind Harmer
3.062
24725505WLD G2 C
Solar/Wind Harmer
2.334
24699105WLD G1 C
Solar/Wind Harmer
2.307
270031AE2-169
Solar/Wind Harmer
4.658
270599AE1-208 GEN
Solar/Wind Harmer
4.658
25326509SID D
Adder
0.724
970291AG2-192 GEN
Solar/Wind Harmer
0.704
970291AG2-192 GEN
Solar/Wind Harmer
0.227
944541AF1-119 GEN
Solar/Wind Harmer
2.254
960971AF2-388 GEN
Solar/Wind Harmer
5.884
253378AE2-206_GEN
Solar/Wind Harmer
1.839
945391AF1-204 GEN
Solar/Wind Harmer
7.11
942221AE2-234 GEN
Solar/Wind Harmer
1.768
339236AF1-050_GEN
Solar/Wind Harmer
0.914
339231AF1-038_GEN
Solar/Wind Harmer
0.862
970241AG2-163 GEN
Solar/Wind Harmer
11.808
964781AG1-341 GEN
Solar/Wind Harmer
4.893
942861AE2-305 GEN
Solar/Wind Harmer
3.55
24387305FR-4G C
Solar/Wind Harmer
2.282
966841AG1-555 GEN
Solar/Wind Harmer
1.128
276916AD2-100_GEN
Solar/Wind Harmer
9.298
276911AD2-131_GEN
Solar/Wind Harmer
1.879
276615X2-022 GEN
Solar/Wind Harmer
0.856
276838X2-022 GEN2
Solar/Wind Harmer
0.102
274880W4-005 GEN4
Solar/Wind Harmer
1.318
276174W4-005 GEN2
Solar/Wind Harmer
1.318
270180AB1-006 GEN1
Solar/Wind Harmer
3.117
24697605MDL-3G C
Solar/Wind Harmer
1.598
24755605MDL-5G
Solar/Wind Harmer
1.045
24697905MDL-4G C
Solar/Wind Harmer
0.994
270181AB1-006 GEN2
Solar/Wind Harmer
0.31
237033AB1-150 GEN
Solar/Wind Helper
0.389
24803406KYGER 5HP
50/50
4.125
24803206KYGER 4HP
50/50
4.116
252516AE2-318_GEN
Solar/Wind Harmer
10.852
25196808ZIMRHP
Adder
81.048
25194608D.CRK4
Adder
1.719
252510AF1-249 C
Solar/Wind Harmer
0.436
253316AC1-085 GEN3
Solar/Wind Harmer
8.675
946171AF1-282 GEN
Solar/Wind Harmer
10.363
25196008MFTGT1
Adder
1.381
253398AE2-221_GEN2
Solar/Wind Harmer
4.418
945681AF1-233 GEN
Solar/Wind Harmer
17.515
270273AD2-016 GEN
Solar/Wind Harmer
2.389
339221AD2-048_GEN
Solar/Wind Harmer
1.321
270222AC2-111 GEN
Solar/Wind Harmer
3.672
944031AF1-071 GEN
Solar/Wind Harmer
0.826
253370AE2-315 SEC1
Adder
1.646
253371AE2-315 SEC2
Adder
1.557
24802606KYGER 1HP
50/50
4.203
24802706KYGER 1LP
50/50
2.464
24803506KYGER 5LP
50/50
2.407
971985AH1-537 GEN
Solar/Wind Harmer
50.336
25196408WSDLE3
Adder
9.22
253433AC1-085 GEN1
Solar/Wind Harmer
5.507
253432AC1-085 GEN2
Solar/Wind Harmer
0.277
25196108MFTGT2
Adder
1.522
25196108MFTGT2
Adder
1.413
253406AD2-031_GEN
Solar/Wind Harmer
1.172
972163AH1-664 GEN
Solar/Wind Harmer
9.178
972165AH1-665 GEN
Solar/Wind Harmer
7.342
270263AC1-001 GEN
Solar/Wind Harmer
0.94
270340AC2-060 GEN
Solar/Wind Harmer
2.706
339216AC1-074 GEN
Solar/Wind Harmer
1.47
253372AE2-315 SEC3
Adder
1.557
253372AE2-315 SEC3
Adder
1.557
25306009OHH W.
Adder
2.325
3429211JKCT 2G
Adder
8.623
270356AE2-297 GEN
Solar/Wind Harmer
3.314
270432AC2-029 GEN
Solar/Wind Harmer
4.942
971029AG2-637 GEN
Solar/Wind Harmer
10.199
241972AD1-140 GEN
Solar/Wind Harmer
3.007
270543AE2-219 C
Solar/Wind Harmer
6.525
247536S-71 GEN
Solar/Wind Harmer
2.537
253338AC1-165 GEN
Solar/Wind Harmer
0.667
253343AC1-166 GEN
Solar/Wind Harmer
0.667
964611AG1-324 GEN
Solar/Wind Harmer
2.341
961761AG1-017 GEN
Solar/Wind Harmer
0.255
945581AF1-223 GEN
Solar/Wind Harmer
2.59
270444AC2-157 GEN1
Solar/Wind Harmer
3.029
270445AC2-157 GEN2
Solar/Wind Harmer
3.029
970289AG2-191 GEN
Solar/Wind Harmer
1.029
958711AF2-162 GEN
Solar/Wind Harmer
0.545
24729505KEY G4
Adder
3.27
963841AG1-237 GEN
Solar/Wind Harmer
5.041
945631AF1-228 GEN
Solar/Wind Harmer
2.133
943861AF1-054 GEN
Solar/Wind Harmer
1.752
943851AF1-053 GEN
Solar/Wind Harmer
0.847
963791AG1-232 GEN
Solar/Wind Harmer
6.102
24386405FR-21G C
Solar/Wind Harmer
1.932
24387005FR-3G C
Solar/Wind Harmer
1.777
944221AF1-090 GEN
Solar/Wind Harmer
4.903
276763AC1-053 GEN1
Solar/Wind Harmer
1.724
276764AC1-053 GEN2
Solar/Wind Harmer
1.724
276668AB2-070 GEN1
Solar/Wind Harmer
0.964
276848AB2-070 GEN3
Solar/Wind Harmer
0.964
276849AB2-070 GEN2
Solar/Wind Harmer
0.964
946581AF1-322 GEN
Solar/Wind Harmer
4.434
24691005MDL-2G C
Solar/Wind Harmer
1.603
943111AE2-339 GEN
Solar/Wind Harmer
0.703
25326309TAIT D
Adder
0.869
3429421JKCT 10G
Adder
6.347
3429241JKCT 3G
Adder
8.736
942081AE2-220 GEN
Solar/Wind Harmer
4.346
270209AC1-174_GEN
Solar/Wind Harmer
2.766
270437AC2-090 C
Solar/Wind Harmer
3.793
270239V3-007_GEN1
Solar/Wind Harmer
1.169
339211AE2-254 GEN
Solar/Wind Harmer
0.953
24728605AND G2
Adder
2.412
270005AE1-210 C O1
Solar/Wind Harmer
3.395
253333AC1-068 GEN
Solar/Wind Harmer
0.643
970825AG2-519 GEN
Solar/Wind Harmer
1.285
970091AG2-072 GEN
Adder
45.472
970653AG2-424 GEN
Solar/Wind Harmer
2.821
276903AD2-071 C
Solar/Wind Harmer
5.727
945371AF1-202 GEN
Solar/Wind Harmer
3.984
270594AE1-207 GEN
Solar/Wind Harmer
7.604
270032AE2-172
Solar/Wind Harmer
2.604
958861AF2-177 GEN
Solar/Wind Harmer
6.007
270024AE2-089 GEN
Solar/Wind Harmer
2.531
965651AG1-433 GEN
Solar/Wind Harmer
2.942
339241AF1-083 GEN
Solar/Wind Harmer
0.892
972203AH1-686 GEN
Adder
1.212
964901AG1-354 GEN
Solar/Wind Harmer
7.485
963741AG1-226 GEN
Solar/Wind Harmer
21.254
24385905FR-11G C
Solar/Wind Harmer
3.734
24386605FR-22G C
Solar/Wind Harmer
1.932
965911AG1-460 GEN
Solar/Wind Harmer
0.615
276621W2-048 GEN
Solar/Wind Harmer
2.726
276686W4-005 GEN3
Solar/Wind Harmer
1.318
24791305MDL-5G
Solar/Wind Harmer
1.045
960001AF2-291 GEN
Solar/Wind Helper
1.677
270331AC1-082 GEN3
Solar/Wind Helper
0.186
235780M24_1
Solar/Wind Helper
0.483
LAGNLTFEXP_LAGN->PJM
CLTF
5.225
TVALTFEXP_TVA->PJM
CLTF
2.484
NYPJM->LTFIMP_NY
CLTF
1.475
LGEELTFEXP_LGEE->PJM
CLTF
5.055
WECLTFEXP_WEC->PJM
CLTF
1.49
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.592
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.256
AG2-052LTFEXP_AG2-052->PJM
LTF
0.097
AH1-155LTFEXP_AH1-155->PJM
LTF
0.145
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.621
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.627
MECLTFEXP_MEC->PJM
CLTF
6.456
SIGELTFEXP_SIGE->PJM
CLTF
0.31
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.702
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 40.6 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 42.3 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#6156_05MARQUI 765_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6156_05MARQUI 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:120.75 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1859.53
MW Contribution:
40.88
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.511
24802706KYGER 1LP
50/50
2.645
24803506KYGER 5LP
50/50
2.583
971985AH1-537 GEN
Solar/Wind Harmer
56.568
253433AC1-085 GEN1
Solar/Wind Harmer
7.375
253432AC1-085 GEN2
Solar/Wind Harmer
0.371
270263AC1-001 GEN
Solar/Wind Harmer
1.447
25196408WSDLE3
Adder
11.529
270340AC2-060 GEN
Solar/Wind Harmer
3.869
253406AD2-031_GEN
Solar/Wind Harmer
1.584
25196108MFTGT2
Adder
1.862
25196108MFTGT2
Adder
1.729
972163AH1-664 GEN
Solar/Wind Harmer
11.991
972165AH1-665 GEN
Solar/Wind Harmer
9.592
339216AC1-074 GEN
Solar/Wind Harmer
1.851
270432AC2-029 GEN
Solar/Wind Harmer
7.618
253372AE2-315 SEC3
Adder
2.021
253372AE2-315 SEC3
Adder
2.021
25306009OHH W.
Adder
3.008
3429211JKCT 2G
Adder
10.797
241972AD1-140 GEN
Solar/Wind Harmer
3.986
253338AC1-165 GEN
Solar/Wind Harmer
0.939
253343AC1-166 GEN
Solar/Wind Harmer
0.939
270356AE2-297 GEN
Solar/Wind Harmer
3.929
971029AG2-637 GEN
Solar/Wind Harmer
12.368
270543AE2-219 C
Solar/Wind Harmer
7.87
247536S-71 GEN
Solar/Wind Harmer
3.045
964611AG1-324 GEN
Solar/Wind Harmer
2.784
961761AG1-017 GEN
Solar/Wind Harmer
0.304
945581AF1-223 GEN
Solar/Wind Harmer
3.06
945631AF1-228 GEN
Solar/Wind Harmer
3.043
958711AF2-162 GEN
Solar/Wind Harmer
0.643
943861AF1-054 GEN
Solar/Wind Harmer
2.427
943851AF1-053 GEN
Solar/Wind Harmer
1.173
970289AG2-191 GEN
Solar/Wind Harmer
1.176
24729505KEY G4
Adder
3.861
270291AC1-194 GEN
Solar/Wind Harmer
2.916
241955AC1-078 GEN
Solar/Wind Harmer
4.064
241973AD2-163_GEN1
Solar/Wind Harmer
1.073
241974AD2-163_GEN2
Solar/Wind Harmer
1.073
963791AG1-232 GEN
Solar/Wind Harmer
7.287
270444AC2-157 GEN1
Solar/Wind Harmer
2.98
270445AC2-157 GEN2
Solar/Wind Harmer
2.98
963841AG1-237 GEN
Solar/Wind Harmer
5.337
24803006KYGER 3HP
50/50
4.479
24802806KYGER 2HP
50/50
4.462
24802906KYGER 2LP
50/50
2.619
25183008BIOENL
50/50
0.04
252509AD1-136 GEN
Solar/Wind Harmer
0.379
25183208HLCRTG
Solar/Wind Harmer
8.672
270269AC2-059
Solar/Wind Harmer
12.691
25194408D.CRK1
Adder
9.908
25194508D.CRK3
Adder
1.852
253415AE1-040 GEN
Solar/Wind Harmer
1.385
962581AG1-107 GEN
Solar/Wind Harmer
6.11
961491AF2-440 GEN
Solar/Wind Harmer
2.54
253370AE2-315 SEC1
Adder
2.137
972043AH1-570 GEN
Solar/Wind Harmer
2.652
972045AH1-571 GEN
Solar/Wind Harmer
2.122
25322209TAIT E
Adder
10.038
25322209TAIT E
Adder
9.812
253349AC2-067 GEN
Solar/Wind Harmer
2.05
253400AC2-068 GEN
Solar/Wind Harmer
0.824
971125AH1-004 GEN
Solar/Wind Harmer
4.03
970107AG2-081 GEN
Solar/Wind Harmer
3.023
25326109MON D
Adder
1.324
942891AE2-308 GEN
Solar/Wind Harmer
9.002
926881AC1-175 GEN
Solar/Wind Harmer
4.513
270383AD1-128 GEN
Solar/Wind Harmer
4.887
970883AG2-550 GEN
Solar/Wind Harmer
7.87
970885AG2-551 GEN
Solar/Wind Harmer
1.83
247621Y3-024
Adder
0.176
25326509SID D
Adder
0.951
964611AG1-324 GEN
Solar/Wind Harmer
0.374
270201AC2-176 GEN
Solar/Wind Harmer
3.648
964571AG1-320 GEN
Solar/Wind Harmer
5.767
971073AG2-665 GEN
Solar/Wind Harmer
5.548
970879AG2-548 GEN
Solar/Wind Harmer
0.806
24725505WLD G2 C
Solar/Wind Harmer
2.701
24699105WLD G1 C
Solar/Wind Harmer
2.67
253378AE2-206_GEN
Solar/Wind Harmer
2.436
270031AE2-169
Solar/Wind Harmer
5.48
270599AE1-208 GEN
Solar/Wind Harmer
5.48
944541AF1-119 GEN
Solar/Wind Harmer
2.663
960971AF2-388 GEN
Solar/Wind Harmer
6.95
942861AE2-305 GEN
Solar/Wind Harmer
4.917
970291AG2-192 GEN
Solar/Wind Harmer
0.805
970291AG2-192 GEN
Solar/Wind Harmer
0.259
942221AE2-234 GEN
Solar/Wind Harmer
2.089
339236AF1-050_GEN
Solar/Wind Harmer
1.055
339231AF1-038_GEN
Solar/Wind Harmer
1.008
927014AC1-188 GEN
Solar/Wind Harmer
0.859
945391AF1-204 GEN
Solar/Wind Harmer
7.563
964781AG1-341 GEN
Solar/Wind Harmer
5.576
253383AE2-342_GEN
Solar/Wind Harmer
0.458
970241AG2-163 GEN
Solar/Wind Harmer
12.517
971485AH1-239 GEN
Solar/Wind Harmer
3.96
966021AG1-471 GEN
Solar/Wind Harmer
2.631
24387305FR-4G C
Solar/Wind Harmer
2.413
966841AG1-555 GEN
Solar/Wind Harmer
1.193
276916AD2-100_GEN
Solar/Wind Harmer
9.913
276911AD2-131_GEN
Solar/Wind Harmer
2.003
276615X2-022 GEN
Solar/Wind Harmer
0.916
276838X2-022 GEN2
Solar/Wind Harmer
0.109
274880W4-005 GEN4
Solar/Wind Harmer
1.412
276174W4-005 GEN2
Solar/Wind Harmer
1.412
270180AB1-006 GEN1
Solar/Wind Harmer
3.305
24697605MDL-3G C
Solar/Wind Harmer
1.694
24755605MDL-5G
Solar/Wind Harmer
1.108
24697905MDL-4G C
Solar/Wind Harmer
1.055
270181AB1-006 GEN2
Solar/Wind Harmer
0.329
237033AB1-150 GEN
Solar/Wind Helper
0.424
24803406KYGER 5HP
50/50
4.427
24803206KYGER 4HP
50/50
4.417
253316AC1-085 GEN3
Solar/Wind Harmer
11.619
946171AF1-282 GEN
Solar/Wind Harmer
13.878
252516AE2-318_GEN
Solar/Wind Harmer
13.842
270273AD2-016 GEN
Solar/Wind Harmer
3.619
25196808ZIMRHP
Adder
103.16
252510AF1-249 C
Solar/Wind Harmer
0.548
25194608D.CRK4
Adder
2.154
253398AE2-221_GEN2
Solar/Wind Harmer
5.885
945681AF1-233 GEN
Solar/Wind Harmer
22.912
25196008MFTGT1
Adder
1.689
339221AD2-048_GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.137
253371AE2-315 SEC2
Adder
2.021
25326309TAIT D
Adder
1.127
270222AC2-111 GEN
Solar/Wind Harmer
4.52
944031AF1-071 GEN
Solar/Wind Harmer
1.017
943111AE2-339 GEN
Solar/Wind Harmer
0.883
3429421JKCT 10G
Adder
7.969
3429241JKCT 3G
Adder
10.939
253333AC1-068 GEN
Solar/Wind Harmer
0.905
942081AE2-220 GEN
Solar/Wind Harmer
5.172
270209AC1-174_GEN
Solar/Wind Harmer
3.291
270437AC2-090 C
Solar/Wind Harmer
4.513
270239V3-007_GEN1
Solar/Wind Harmer
1.391
339211AE2-254 GEN
Solar/Wind Harmer
1.15
270005AE1-210 C O1
Solar/Wind Harmer
4.013
970825AG2-519 GEN
Solar/Wind Harmer
1.517
24728605AND G2
Adder
2.773
971073AG2-665 GEN
Solar/Wind Harmer
0.806
970653AG2-424 GEN
Solar/Wind Harmer
3.256
945371AF1-202 GEN
Solar/Wind Harmer
4.707
276903AD2-071 C
Solar/Wind Harmer
6.601
958861AF2-177 GEN
Solar/Wind Harmer
7.096
270594AE1-207 GEN
Solar/Wind Harmer
8.773
270032AE2-172
Solar/Wind Harmer
3.005
270024AE2-089 GEN
Solar/Wind Harmer
3.017
965651AG1-433 GEN
Solar/Wind Harmer
3.475
339241AF1-083 GEN
Solar/Wind Harmer
1.04
964901AG1-354 GEN
Solar/Wind Harmer
8.626
970091AG2-072 GEN
Adder
38.834
963741AG1-226 GEN
Solar/Wind Harmer
22.53
24385905FR-11G C
Solar/Wind Harmer
3.949
24386605FR-22G C
Solar/Wind Harmer
2.043
965911AG1-460 GEN
Solar/Wind Harmer
0.657
276621W2-048 GEN
Solar/Wind Harmer
2.918
276686W4-005 GEN3
Solar/Wind Harmer
1.412
24791305MDL-5G
Solar/Wind Harmer
1.108
960001AF2-291 GEN
Solar/Wind Helper
1.492
270331AC1-082 GEN3
Solar/Wind Helper
0.168
235780M24_1
Solar/Wind Helper
0.525
270071AF1-092 GEN
Solar/Wind Harmer
7.165
944221AF1-090 GEN
Solar/Wind Harmer
5.212
24386405FR-21G C
Solar/Wind Harmer
2.043
24387005FR-3G C
Solar/Wind Harmer
1.879
276763AC1-053 GEN1
Solar/Wind Harmer
1.847
276764AC1-053 GEN2
Solar/Wind Harmer
1.847
276668AB2-070 GEN1
Solar/Wind Harmer
1.034
276848AB2-070 GEN3
Solar/Wind Harmer
1.034
276849AB2-070 GEN2
Solar/Wind Harmer
1.034
946581AF1-322 GEN
Solar/Wind Harmer
4.702
24691005MDL-2G C
Solar/Wind Harmer
1.699
24803106KYGER 3LP
50/50
2.637
24803306KYGER 4LP
50/50
2.583
971191AH1-055 GEN
Solar/Wind Harmer
85.195
252507AC2-088 GEN
Solar/Wind Harmer
2.655
253317AC1-085 GEN4
Solar/Wind Harmer
11.619
946181AF1-283 GEN
Solar/Wind Harmer
18.042
252519AF1-045_GEN
Solar/Wind Harmer
5.038
25194608D.CRK4
Adder
2.154
252524AE2-267 GEN
Solar/Wind Harmer
2.058
25196608WSDLE5
Adder
11.2
958171AF2-111 GEN
Solar/Wind Harmer
32.628
253394AE2-221_GEN
Solar/Wind Harmer
5.885
270367AC2-061_GEN
Solar/Wind Harmer
3.949
270186AC1-089 GEN
Solar/Wind Harmer
7.462
972167AH1-666 GEN
Solar/Wind Harmer
9.768
25196008MFTGT1
Adder
1.636
339243AC2-075 GEN1
Solar/Wind Harmer
0.501
253303V4-073 C
Solar/Wind Harmer
0.124
253370AE2-315 SEC1
Adder
2.137
253371AE2-315 SEC2
Adder
2.021
960071AF2-298 GEN
Solar/Wind Harmer
1.535
3429391JKCT 9G
Adder
7.969
253325AC1-069 GEN
Solar/Wind Harmer
0.905
970093AG2-073 GEN
Solar/Wind Harmer
4.511
24379505HDWTR1G C
Solar/Wind Harmer
6.394
270240V3-007_GEN2
Solar/Wind Harmer
5.003
270518AE2-148 GEN
Solar/Wind Harmer
9.208
970455AG2-298 GEN
Solar/Wind Harmer
2.574
270004AE1-209 GEN
Solar/Wind Harmer
4.013
946031AF1-268 GEN
Solar/Wind Harmer
6.057
970825AG2-519 GEN
Solar/Wind Harmer
4.074
24728505AND G1
Adder
2.773
962031AG1-047 GEN
Solar/Wind Harmer
2.146
957741AF2-068 GEN
Solar/Wind Harmer
10.645
970879AG2-548 GEN
Solar/Wind Harmer
5.548
276820AF1-078_GEN
Solar/Wind Harmer
1.082
970653AG2-424 GEN
Solar/Wind Harmer
0.471
339206AE1-143 GEN
Solar/Wind Harmer
1.398
965461AG1-414 GEN
Solar/Wind Harmer
1.404
970289AG2-191 GEN
Solar/Wind Harmer
0.475
247642Z2-115 C
Solar/Wind Harmer
0.038
942051AE2-217 GEN
Solar/Wind Harmer
10.648
960801AF2-371 GEN
Solar/Wind Harmer
1.494
964871AG1-351 GEN
Solar/Wind Harmer
1.032
944531AF1-118 GEN
Solar/Wind Harmer
20.315
972273AH1-721 GEN
Adder
48.249
957541AF2-048 GEN
Solar/Wind Harmer
0.859
970193AG2-126 GEN
Solar/Wind Harmer
8.141
339255AE2-071 GEN
Solar/Wind Harmer
0.622
339250AF1-203 GEN
Solar/Wind Harmer
0.32
24386205FR-12G C
Solar/Wind Harmer
2.036
942481AE2-261 GEN
Solar/Wind Harmer
14.072
957381AF2-032 GEN
Solar/Wind Harmer
0.94
276785W4-005 GEN1
Solar/Wind Harmer
1.412
971993AH1-541 GEN
Solar/Wind Harmer
4.315
24690905MDL-1G C
Solar/Wind Harmer
3.689
270330AC1-082 GEN2
Solar/Wind Helper
0.169
270329AC1-082 GEN1
Solar/Wind Helper
0.169
970781AG2-491 GEN
Solar/Wind Harmer
2.082
LAGNLTFEXP_LAGN->PJM
CLTF
5.54
TVALTFEXP_TVA->PJM
CLTF
2.651
NYPJM->LTFIMP_NY
CLTF
1.62
LGEELTFEXP_LGEE->PJM
CLTF
5.749
WECLTFEXP_WEC->PJM
CLTF
1.624
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.383
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.817
AG2-052LTFEXP_AG2-052->PJM
LTF
0.106
AH1-155LTFEXP_AH1-155->PJM
LTF
0.159
CBM West 1LTFEXP_CBM-W1->PJM
CBM
66.406
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.825
MECLTFEXP_MEC->PJM
CLTF
6.978
SIGELTFEXP_SIGE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.569
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 48.25 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.24 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1666.97
MW Contribution:
34.16
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.1 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2342.28
MW Contribution:
36.74
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.162
24802706KYGER 1LP
50/50
2.441
24803506KYGER 5LP
50/50
2.384
971985AH1-537 GEN
Solar/Wind Harmer
49.14
25196408WSDLE3
Adder
8.658
253433AC1-085 GEN1
Solar/Wind Harmer
5.134
253432AC1-085 GEN2
Solar/Wind Harmer
0.258
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
8.69
972165AH1-665 GEN
Solar/Wind Harmer
6.952
253406AD2-031_GEN
Solar/Wind Harmer
1.088
339216AC1-074 GEN
Solar/Wind Harmer
1.391
270340AC2-060 GEN
Solar/Wind Harmer
2.489
270263AC1-001 GEN
Solar/Wind Harmer
0.854
253372AE2-315 SEC3
Adder
1.443
253372AE2-315 SEC3
Adder
1.443
25306009OHH W.
Adder
2.158
3429211JKCT 2G
Adder
8.249
270356AE2-297 GEN
Solar/Wind Harmer
3.158
971029AG2-637 GEN
Solar/Wind Harmer
9.766
270432AC2-029 GEN
Solar/Wind Harmer
4.409
270543AE2-219 C
Solar/Wind Harmer
6.274
241972AD1-140 GEN
Solar/Wind Harmer
2.733
247536S-71 GEN
Solar/Wind Harmer
2.45
964611AG1-324 GEN
Solar/Wind Harmer
2.272
961761AG1-017 GEN
Solar/Wind Harmer
0.248
945581AF1-223 GEN
Solar/Wind Harmer
2.557
253338AC1-165 GEN
Solar/Wind Harmer
0.595
253343AC1-166 GEN
Solar/Wind Harmer
0.595
958711AF2-162 GEN
Solar/Wind Harmer
0.544
970289AG2-191 GEN
Solar/Wind Harmer
0.989
24729505KEY G4
Adder
3.305
270444AC2-157 GEN1
Solar/Wind Harmer
2.758
270445AC2-157 GEN2
Solar/Wind Harmer
2.758
963791AG1-232 GEN
Solar/Wind Harmer
6.09
963841AG1-237 GEN
Solar/Wind Harmer
4.776
944221AF1-090 GEN
Solar/Wind Harmer
4.74
24803406KYGER 5HP
50/50
4.085
24803206KYGER 4HP
50/50
4.076
252516AE2-318_GEN
Solar/Wind Harmer
10.186
25196808ZIMRHP
Adder
76.155
25194608D.CRK4
Adder
1.615
252510AF1-249 C
Solar/Wind Harmer
0.409
253316AC1-085 GEN3
Solar/Wind Harmer
8.089
946171AF1-282 GEN
Solar/Wind Harmer
9.662
25196008MFTGT1
Adder
1.298
253398AE2-221_GEN2
Solar/Wind Harmer
4.109
945681AF1-233 GEN
Solar/Wind Harmer
16.573
270273AD2-016 GEN
Solar/Wind Harmer
2.168
339221AD2-048_GEN
Solar/Wind Harmer
1.251
270222AC2-111 GEN
Solar/Wind Harmer
3.47
944031AF1-071 GEN
Solar/Wind Harmer
0.781
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.443
943111AE2-339 GEN
Solar/Wind Harmer
0.669
25326309TAIT D
Adder
0.804
3429421JKCT 10G
Adder
6.056
3429241JKCT 3G
Adder
8.358
942081AE2-220 GEN
Solar/Wind Harmer
4.197
270209AC1-174_GEN
Solar/Wind Harmer
2.67
270437AC2-090 C
Solar/Wind Harmer
3.662
270239V3-007_GEN1
Solar/Wind Harmer
1.129
339211AE2-254 GEN
Solar/Wind Harmer
0.919
270005AE1-210 C O1
Solar/Wind Harmer
3.304
24728605AND G2
Adder
2.296
970825AG2-519 GEN
Solar/Wind Harmer
1.247
945371AF1-202 GEN
Solar/Wind Harmer
3.934
970653AG2-424 GEN
Solar/Wind Harmer
2.709
276903AD2-071 C
Solar/Wind Harmer
5.501
253333AC1-068 GEN
Solar/Wind Harmer
0.574
958861AF2-177 GEN
Solar/Wind Harmer
5.973
270594AE1-207 GEN
Solar/Wind Harmer
7.326
270032AE2-172
Solar/Wind Harmer
2.509
965651AG1-433 GEN
Solar/Wind Harmer
2.937
270024AE2-089 GEN
Solar/Wind Harmer
2.481
339241AF1-083 GEN
Solar/Wind Harmer
0.868
970091AG2-072 GEN
Adder
38.983
964901AG1-354 GEN
Solar/Wind Harmer
7.327
963741AG1-226 GEN
Solar/Wind Harmer
20.113
960001AF2-291 GEN
Solar/Wind Helper
1.7
270331AC1-082 GEN3
Solar/Wind Helper
0.189
235780M24_1
Solar/Wind Helper
0.465
24803006KYGER 3HP
50/50
4.133
24802806KYGER 2HP
50/50
4.118
24802906KYGER 2LP
50/50
2.417
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.28
25183208HLCRTG
Solar/Wind Harmer
6.261
25194408D.CRK1
Adder
7.428
25194508D.CRK3
Adder
1.389
962581AG1-107 GEN
Solar/Wind Harmer
4.213
961491AF2-440 GEN
Solar/Wind Harmer
1.751
270269AC2-059
Solar/Wind Harmer
7.604
253415AE1-040 GEN
Solar/Wind Harmer
0.897
972043AH1-570 GEN
Solar/Wind Harmer
1.988
972045AH1-571 GEN
Solar/Wind Harmer
1.59
971125AH1-004 GEN
Solar/Wind Harmer
3.051
970107AG2-081 GEN
Solar/Wind Harmer
2.288
253370AE2-315 SEC1
Adder
1.526
25322209TAIT E
Adder
7.164
25322209TAIT E
Adder
7.003
253349AC2-067 GEN
Solar/Wind Harmer
1.485
253400AC2-068 GEN
Solar/Wind Harmer
0.597
25326109MON D
Adder
0.938
942891AE2-308 GEN
Solar/Wind Harmer
6.919
926881AC1-175 GEN
Solar/Wind Harmer
3.662
270383AD1-128 GEN
Solar/Wind Harmer
3.929
970883AG2-550 GEN
Solar/Wind Harmer
6.274
970885AG2-551 GEN
Solar/Wind Harmer
1.459
247621Y3-024
Adder
0.142
964571AG1-320 GEN
Solar/Wind Harmer
4.793
964611AG1-324 GEN
Solar/Wind Harmer
0.305
270201AC2-176 GEN
Solar/Wind Harmer
2.974
24725505WLD G2 C
Solar/Wind Harmer
2.243
24699105WLD G1 C
Solar/Wind Harmer
2.217
270031AE2-169
Solar/Wind Harmer
4.555
270599AE1-208 GEN
Solar/Wind Harmer
4.555
944541AF1-119 GEN
Solar/Wind Harmer
2.25
960971AF2-388 GEN
Solar/Wind Harmer
5.873
970291AG2-192 GEN
Solar/Wind Harmer
0.676
970291AG2-192 GEN
Solar/Wind Harmer
0.218
942221AE2-234 GEN
Solar/Wind Harmer
1.752
25326509SID D
Adder
0.658
339236AF1-050_GEN
Solar/Wind Harmer
0.894
945391AF1-204 GEN
Solar/Wind Harmer
6.702
339231AF1-038_GEN
Solar/Wind Harmer
0.854
253378AE2-206_GEN
Solar/Wind Harmer
1.655
964781AG1-341 GEN
Solar/Wind Harmer
4.826
970241AG2-163 GEN
Solar/Wind Harmer
11.174
237033AB1-150 GEN
Solar/Wind Helper
0.375
24803106KYGER 3LP
50/50
2.434
24803306KYGER 4LP
50/50
2.384
971191AH1-055 GEN
Solar/Wind Harmer
71.644
252507AC2-088 GEN
Solar/Wind Harmer
1.961
252519AF1-045_GEN
Solar/Wind Harmer
3.707
25194608D.CRK4
Adder
1.615
252524AE2-267 GEN
Solar/Wind Harmer
1.545
25196608WSDLE5
Adder
8.411
253317AC1-085 GEN4
Solar/Wind Harmer
8.089
946181AF1-283 GEN
Solar/Wind Harmer
12.561
958171AF2-111 GEN
Solar/Wind Harmer
23.452
25196008MFTGT1
Adder
1.257
253394AE2-221_GEN
Solar/Wind Harmer
4.109
972167AH1-666 GEN
Solar/Wind Harmer
7.062
270367AC2-061_GEN
Solar/Wind Harmer
2.733
270186AC1-089 GEN
Solar/Wind Harmer
5.183
339243AC2-075 GEN1
Solar/Wind Harmer
0.377
253303V4-073 C
Solar/Wind Harmer
0.088
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.443
3429391JKCT 9G
Adder
6.056
960071AF2-298 GEN
Solar/Wind Harmer
1.1
970093AG2-073 GEN
Solar/Wind Harmer
3.499
24379505HDWTR1G C
Solar/Wind Harmer
5.189
270240V3-007_GEN2
Solar/Wind Harmer
4.06
270004AE1-209 GEN
Solar/Wind Harmer
3.304
970455AG2-298 GEN
Solar/Wind Harmer
2.109
24728505AND G1
Adder
2.296
946031AF1-268 GEN
Solar/Wind Harmer
4.96
970825AG2-519 GEN
Solar/Wind Harmer
3.347
962031AG1-047 GEN
Solar/Wind Harmer
1.75
957741AF2-068 GEN
Solar/Wind Harmer
8.68
970653AG2-424 GEN
Solar/Wind Harmer
0.392
253325AC1-069 GEN
Solar/Wind Harmer
0.574
339206AE1-143 GEN
Solar/Wind Harmer
1.156
965461AG1-414 GEN
Solar/Wind Harmer
1.18
970289AG2-191 GEN
Solar/Wind Harmer
0.399
247642Z2-115 C
Solar/Wind Harmer
0.032
944531AF1-118 GEN
Solar/Wind Harmer
17.479
270518AE2-148 GEN
Solar/Wind Harmer
5.914
972273AH1-721 GEN
Adder
40.32
970193AG2-126 GEN
Solar/Wind Harmer
7.214
276820AF1-078_GEN
Solar/Wind Harmer
0.735
339255AE2-071 GEN
Solar/Wind Harmer
0.537
339250AF1-203 GEN
Solar/Wind Harmer
0.276
270330AC1-082 GEN2
Solar/Wind Helper
0.19
270329AC1-082 GEN1
Solar/Wind Helper
0.19
LAGNLTFEXP_LAGN->PJM
CLTF
5.572
TVALTFEXP_TVA->PJM
CLTF
2.7
NYPJM->LTFIMP_NY
CLTF
1.435
LGEELTFEXP_LGEE->PJM
CLTF
4.729
WECLTFEXP_WEC->PJM
CLTF
1.499
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.049
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.271
AG2-052LTFEXP_AG2-052->PJM
LTF
0.096
AH1-155LTFEXP_AH1-155->PJM
LTF
0.144
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.972
MECLTFEXP_MEC->PJM
CLTF
6.466
SIGELTFEXP_SIGE->PJM
CLTF
0.293
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.696
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 40.32 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 43.37 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.72 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1280.85
MW Contribution:
33.6
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.63 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1362.91
MW Contribution:
35.03
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.094
24803206KYGER 4HP
50/50
4.085
252516AE2-318_GEN
Solar/Wind Harmer
7.932
25196808ZIMRHP
Adder
75.812
25194608D.CRK4
Adder
1.604
252510AF1-249 C
Solar/Wind Harmer
0.051
253316AC1-085 GEN3
Solar/Wind Harmer
0
24802606KYGER 1HP
50/50
4.172
24802706KYGER 1LP
50/50
2.446
24803506KYGER 5LP
50/50
2.389
971985AH1-537 GEN
Solar/Wind Harmer
5.716
25196408WSDLE3
Adder
8.602
25196108MFTGT2
Adder
1.414
25196108MFTGT2
Adder
1.313
972163AH1-664 GEN
Solar/Wind Harmer
6.737
972165AH1-665 GEN
Solar/Wind Harmer
5.396
253406AD2-031_GEN
Solar/Wind Harmer
0.443
24803006KYGER 3HP
50/50
4.142
24802806KYGER 2HP
50/50
4.127
24802906KYGER 2LP
50/50
2.422
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.038
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.38
25194508D.CRK3
Adder
1.38
962581AG1-107 GEN
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.433
972045AH1-571 GEN
Solar/Wind Harmer
1.148
253370AE2-315 SEC1
Adder
1.526
971125AH1-004 GEN
Solar/Wind Harmer
2.112
970107AG2-081 GEN
Solar/Wind Harmer
1.584
25322209TAIT E
Adder
7.169
25322209TAIT E
Adder
7.008
25326109MON D
Adder
0.942
942891AE2-308 GEN
Solar/Wind Harmer
4.783
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.132
970885AG2-551 GEN
Solar/Wind Harmer
1.377
964571AG1-320 GEN
Solar/Wind Harmer
3.631
247621Y3-024
Adder
0.133
964611AG1-324 GEN
Solar/Wind Harmer
0.283
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.967
270599AE1-208 GEN
Solar/Wind Harmer
3.278
270263AC1-001 GEN
Solar/Wind Harmer
0.582
270340AC2-060 GEN
Solar/Wind Harmer
0.001
339216AC1-074 GEN
Solar/Wind Harmer
0.154
253372AE2-315 SEC3
Adder
1.444
253372AE2-315 SEC3
Adder
1.444
25306009OHH W.
Adder
2.154
3429211JKCT 2G
Adder
8.179
270356AE2-297 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.01
971029AG2-637 GEN
Solar/Wind Harmer
6.48
241972AD1-140 GEN
Solar/Wind Harmer
0.472
270543AE2-219 C
Solar/Wind Harmer
2.892
247536S-71 GEN
Solar/Wind Harmer
0.158
964611AG1-324 GEN
Solar/Wind Harmer
1.472
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.584
970289AG2-191 GEN
Solar/Wind Harmer
0.636
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
2.909
946171AF1-282 GEN
Solar/Wind Harmer
6.761
25196008MFTGT1
Adder
1.283
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
11.543
270273AD2-016 GEN
Solar/Wind Harmer
0.596
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.444
25326309TAIT D
Adder
0.805
3429421JKCT 10G
Adder
6.006
3429241JKCT 3G
Adder
8.287
970773AG2-487 GEN
Solar/Wind Harmer
0.807
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.158
24728605AND G2
Adder
2.173
253333AC1-068 GEN
Solar/Wind Harmer
0.004
270005AE1-210 C O1
Solar/Wind Harmer
0.848
970825AG2-519 GEN
Solar/Wind Harmer
1.367
970653AG2-424 GEN
Solar/Wind Harmer
1.845
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
3.979
270594AE1-207 GEN
Solar/Wind Harmer
3.893
270032AE2-172
Solar/Wind Harmer
2.318
958861AF2-177 GEN
Solar/Wind Harmer
1.487
970091AG2-072 GEN
Adder
37.335
270024AE2-089 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
0.985
964901AG1-354 GEN
Solar/Wind Harmer
4.987
960001AF2-291 GEN
Solar/Wind Helper
1.682
270331AC1-082 GEN3
Solar/Wind Helper
0.187
24803106KYGER 3LP
50/50
2.439
24803306KYGER 4LP
50/50
2.389
971191AH1-055 GEN
Solar/Wind Harmer
68.884
252507AC2-088 GEN
Solar/Wind Harmer
0.343
252519AF1-045_GEN
Solar/Wind Harmer
3.694
25194608D.CRK4
Adder
1.604
25196608WSDLE5
Adder
8.356
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.789
958171AF2-111 GEN
Solar/Wind Harmer
16.332
25196008MFTGT1
Adder
1.242
253394AE2-221_GEN
Solar/Wind Harmer
0.001
972167AH1-666 GEN
Solar/Wind Harmer
4.919
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.444
970191AG2-125 GEN
Solar/Wind Harmer
1.303
3429391JKCT 9G
Adder
6.006
970093AG2-073 GEN
Solar/Wind Harmer
3.867
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970455AG2-298 GEN
Solar/Wind Harmer
1.6
24728505AND G1
Adder
2.173
253325AC1-069 GEN
Solar/Wind Harmer
0.004
270004AE1-209 GEN
Solar/Wind Harmer
0.848
946031AF1-268 GEN
Solar/Wind Harmer
3.69
970825AG2-519 GEN
Solar/Wind Harmer
2.902
970653AG2-424 GEN
Solar/Wind Harmer
0.382
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.618
270518AE2-148 GEN
Solar/Wind Harmer
0.289
970289AG2-191 GEN
Solar/Wind Harmer
0.368
972273AH1-721 GEN
Adder
39.663
247642Z2-115 C
Solar/Wind Harmer
0.001
970193AG2-126 GEN
Solar/Wind Harmer
4.669
944531AF1-118 GEN
Solar/Wind Harmer
13.648
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270329AC1-082 GEN1
Solar/Wind Helper
0.188
25326509SID D
Adder
0.66
971613AH1-306 GEN
Solar/Wind Harmer
1.669
944541AF1-119 GEN
Solar/Wind Harmer
0.224
960971AF2-388 GEN
Solar/Wind Harmer
1.97
970291AG2-192 GEN
Solar/Wind Harmer
0.435
970291AG2-192 GEN
Solar/Wind Harmer
0.201
971587AH1-292 GEN
Solar/Wind Harmer
2.382
970329AG2-216 GEN
Solar/Wind Harmer
1.4
942221AE2-234 GEN
Solar/Wind Harmer
1.259
945391AF1-204 GEN
Solar/Wind Harmer
3.307
964781AG1-341 GEN
Solar/Wind Harmer
3.276
LAGNLTFEXP_LAGN->PJM
CLTF
5.22
TVALTFEXP_TVA->PJM
CLTF
2.571
NYPJM->LTFIMP_NY
CLTF
1.348
LGEELTFEXP_LGEE->PJM
CLTF
4.627
WECLTFEXP_WEC->PJM
CLTF
1.3
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.036
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.242
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.475
MECLTFEXP_MEC->PJM
CLTF
5.763
SIGELTFEXP_SIGE->PJM
CLTF
0.281
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.509
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 39.66 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 41.35 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#6763_05BIERSR 345_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6763_05BIERSR 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.64 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1642.31
MW Contribution:
35.33
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6763_05BIERSR 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:124.15 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1911.95
MW Contribution:
37.07
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.233
24802706KYGER 1LP
50/50
2.482
24803506KYGER 5LP
50/50
2.424
971985AH1-537 GEN
Solar/Wind Harmer
50.257
270263AC1-001 GEN
Solar/Wind Harmer
1.208
270340AC2-060 GEN
Solar/Wind Harmer
3.062
25196408WSDLE3
Adder
8.855
253433AC1-085 GEN1
Solar/Wind Harmer
5.315
253432AC1-085 GEN2
Solar/Wind Harmer
0.268
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
972163AH1-664 GEN
Solar/Wind Harmer
9.072
972165AH1-665 GEN
Solar/Wind Harmer
7.258
253406AD2-031_GEN
Solar/Wind Harmer
1.155
270432AC2-029 GEN
Solar/Wind Harmer
6.034
339216AC1-074 GEN
Solar/Wind Harmer
1.44
253372AE2-315 SEC3
Adder
1.457
253372AE2-315 SEC3
Adder
1.457
25306009OHH W.
Adder
2.176
3429211JKCT 2G
Adder
8.545
270356AE2-297 GEN
Solar/Wind Harmer
3.063
971029AG2-637 GEN
Solar/Wind Harmer
9.355
24803406KYGER 5HP
50/50
4.154
24803206KYGER 4HP
50/50
4.145
270273AD2-016 GEN
Solar/Wind Harmer
3.199
252516AE2-318_GEN
Solar/Wind Harmer
10.498
25196808ZIMRHP
Adder
78.483
252510AF1-249 C
Solar/Wind Harmer
0.42
25194608D.CRK4
Adder
1.654
253316AC1-085 GEN3
Solar/Wind Harmer
8.374
946171AF1-282 GEN
Solar/Wind Harmer
10.003
25196008MFTGT1
Adder
1.323
253398AE2-221_GEN2
Solar/Wind Harmer
4.227
945681AF1-233 GEN
Solar/Wind Harmer
17.298
339221AD2-048_GEN
Solar/Wind Harmer
1.297
943111AE2-339 GEN
Solar/Wind Harmer
0.692
270222AC2-111 GEN
Solar/Wind Harmer
3.448
944031AF1-071 GEN
Solar/Wind Harmer
0.776
253370AE2-315 SEC1
Adder
1.54
253371AE2-315 SEC2
Adder
1.457
3429421JKCT 10G
Adder
6.269
25326309TAIT D
Adder
0.808
3429241JKCT 3G
Adder
8.658
339211AE2-254 GEN
Solar/Wind Harmer
0.946
942081AE2-220 GEN
Solar/Wind Harmer
3.986
270209AC1-174_GEN
Solar/Wind Harmer
2.536
270437AC2-090 C
Solar/Wind Harmer
3.478
270239V3-007_GEN1
Solar/Wind Harmer
1.072
24728605AND G2
Adder
2.198
970653AG2-424 GEN
Solar/Wind Harmer
2.75
270005AE1-210 C O1
Solar/Wind Harmer
3.075
970825AG2-519 GEN
Solar/Wind Harmer
1.162
339241AF1-083 GEN
Solar/Wind Harmer
0.887
253333AC1-068 GEN
Solar/Wind Harmer
0.554
945371AF1-202 GEN
Solar/Wind Harmer
3.561
276903AD2-071 C
Solar/Wind Harmer
5.099
970091AG2-072 GEN
Adder
38.38
964901AG1-354 GEN
Solar/Wind Harmer
7.465
270594AE1-207 GEN
Solar/Wind Harmer
6.734
270032AE2-172
Solar/Wind Harmer
2.306
958861AF2-177 GEN
Solar/Wind Harmer
5.335
270024AE2-089 GEN
Solar/Wind Harmer
2.242
965651AG1-433 GEN
Solar/Wind Harmer
2.603
960001AF2-291 GEN
Solar/Wind Helper
1.623
270331AC1-082 GEN3
Solar/Wind Helper
0.176
24803106KYGER 3LP
50/50
2.475
24803306KYGER 4LP
50/50
2.424
971191AH1-055 GEN
Solar/Wind Harmer
74.07
252507AC2-088 GEN
Solar/Wind Harmer
2.029
252519AF1-045_GEN
Solar/Wind Harmer
3.821
25194608D.CRK4
Adder
1.654
252524AE2-267 GEN
Solar/Wind Harmer
1.581
25196608WSDLE5
Adder
8.602
253317AC1-085 GEN4
Solar/Wind Harmer
8.374
946181AF1-283 GEN
Solar/Wind Harmer
13.003
958171AF2-111 GEN
Solar/Wind Harmer
24.384
25196008MFTGT1
Adder
1.281
253394AE2-221_GEN
Solar/Wind Harmer
4.227
270367AC2-061_GEN
Solar/Wind Harmer
2.94
972167AH1-666 GEN
Solar/Wind Harmer
7.371
270186AC1-089 GEN
Solar/Wind Harmer
5.567
339243AC2-075 GEN1
Solar/Wind Harmer
0.39
253303V4-073 C
Solar/Wind Harmer
0.089
253370AE2-315 SEC1
Adder
1.54
253371AE2-315 SEC2
Adder
1.457
3429391JKCT 9G
Adder
6.269
960071AF2-298 GEN
Solar/Wind Harmer
1.104
970093AG2-073 GEN
Solar/Wind Harmer
3.624
24379505HDWTR1G C
Solar/Wind Harmer
4.928
270240V3-007_GEN2
Solar/Wind Harmer
3.856
970455AG2-298 GEN
Solar/Wind Harmer
2.145
24728505AND G1
Adder
2.198
970653AG2-424 GEN
Solar/Wind Harmer
0.398
270004AE1-209 GEN
Solar/Wind Harmer
3.075
946031AF1-268 GEN
Solar/Wind Harmer
4.625
339206AE1-143 GEN
Solar/Wind Harmer
1.182
970825AG2-519 GEN
Solar/Wind Harmer
3.119
962031AG1-047 GEN
Solar/Wind Harmer
1.621
957741AF2-068 GEN
Solar/Wind Harmer
8.043
253325AC1-069 GEN
Solar/Wind Harmer
0.554
972273AH1-721 GEN
Adder
41.705
965461AG1-414 GEN
Solar/Wind Harmer
1.079
970289AG2-191 GEN
Solar/Wind Harmer
0.365
339255AE2-071 GEN
Solar/Wind Harmer
0.546
339250AF1-203 GEN
Solar/Wind Harmer
0.281
247642Z2-115 C
Solar/Wind Harmer
0.029
270518AE2-148 GEN
Solar/Wind Harmer
5.413
970193AG2-126 GEN
Solar/Wind Harmer
6.708
276820AF1-078_GEN
Solar/Wind Harmer
0.71
270330AC1-082 GEN2
Solar/Wind Helper
0.177
270329AC1-082 GEN1
Solar/Wind Helper
0.177
24803006KYGER 3HP
50/50
4.203
24802806KYGER 2HP
50/50
4.187
24802906KYGER 2LP
50/50
2.458
25183008BIOENL
50/50
0.03
270269AC2-059
Solar/Wind Harmer
11.217
252509AD1-136 GEN
Solar/Wind Harmer
0.29
25183208HLCRTG
Solar/Wind Harmer
6.476
25194408D.CRK1
Adder
7.607
25194508D.CRK3
Adder
1.422
253415AE1-040 GEN
Solar/Wind Harmer
1.072
962581AG1-107 GEN
Solar/Wind Harmer
4.523
961491AF2-440 GEN
Solar/Wind Harmer
1.88
972043AH1-570 GEN
Solar/Wind Harmer
2.063
972045AH1-571 GEN
Solar/Wind Harmer
1.65
971125AH1-004 GEN
Solar/Wind Harmer
3.156
970107AG2-081 GEN
Solar/Wind Harmer
2.367
253370AE2-315 SEC1
Adder
1.54
25322209TAIT E
Adder
7.197
25322209TAIT E
Adder
7.035
253349AC2-067 GEN
Solar/Wind Harmer
1.487
253400AC2-068 GEN
Solar/Wind Harmer
0.598
942891AE2-308 GEN
Solar/Wind Harmer
7.164
25326109MON D
Adder
0.939
926881AC1-175 GEN
Solar/Wind Harmer
3.478
270383AD1-128 GEN
Solar/Wind Harmer
3.738
970883AG2-550 GEN
Solar/Wind Harmer
5.951
970885AG2-551 GEN
Solar/Wind Harmer
1.384
964571AG1-320 GEN
Solar/Wind Harmer
4.845
247621Y3-024
Adder
0.133
964611AG1-324 GEN
Solar/Wind Harmer
0.283
270201AC2-176 GEN
Solar/Wind Harmer
2.756
24725505WLD G2 C
Solar/Wind Harmer
2.089
24699105WLD G1 C
Solar/Wind Harmer
2.065
270031AE2-169
Solar/Wind Harmer
4.163
270599AE1-208 GEN
Solar/Wind Harmer
4.163
339236AF1-050_GEN
Solar/Wind Harmer
0.911
25326509SID D
Adder
0.639
339231AF1-038_GEN
Solar/Wind Harmer
0.877
944541AF1-119 GEN
Solar/Wind Harmer
1.995
960971AF2-388 GEN
Solar/Wind Harmer
5.207
970291AG2-192 GEN
Solar/Wind Harmer
0.618
970291AG2-192 GEN
Solar/Wind Harmer
0.199
964781AG1-341 GEN
Solar/Wind Harmer
4.908
945391AF1-204 GEN
Solar/Wind Harmer
6.233
253378AE2-206_GEN
Solar/Wind Harmer
1.598
942221AE2-234 GEN
Solar/Wind Harmer
1.546
971485AH1-239 GEN
Solar/Wind Harmer
3.529
966021AG1-471 GEN
Solar/Wind Harmer
2.352
241972AD1-140 GEN
Solar/Wind Harmer
2.699
270543AE2-219 C
Solar/Wind Harmer
5.951
247536S-71 GEN
Solar/Wind Harmer
2.301
964611AG1-324 GEN
Solar/Wind Harmer
2.109
961761AG1-017 GEN
Solar/Wind Harmer
0.229
253338AC1-165 GEN
Solar/Wind Harmer
0.575
253343AC1-166 GEN
Solar/Wind Harmer
0.575
945581AF1-223 GEN
Solar/Wind Harmer
2.315
958711AF2-162 GEN
Solar/Wind Harmer
0.482
970289AG2-191 GEN
Solar/Wind Harmer
0.904
270444AC2-157 GEN1
Solar/Wind Harmer
2.638
270445AC2-157 GEN2
Solar/Wind Harmer
2.638
24729505KEY G4
Adder
2.858
LAGNLTFEXP_LAGN->PJM
CLTF
5.453
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.294
TVALTFEXP_TVA->PJM
CLTF
2.722
NYPJM->LTFIMP_NY
CLTF
1.367
LGEELTFEXP_LGEE->PJM
CLTF
4.789
WECLTFEXP_WEC->PJM
CLTF
1.269
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.139
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.122
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.877
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.097
MECLTFEXP_MEC->PJM
CLTF
5.729
SIGELTFEXP_SIGE->PJM
CLTF
0.289
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.722
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 41.7 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 43.76 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#308_05CULLOD 765_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#308_05CULLOD 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.58 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1641.32
MW Contribution:
36.02
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#308_05CULLOD 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:120.05 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1848.71
MW Contribution:
37.49
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.104
24803206KYGER 4HP
50/50
4.094
252516AE2-318_GEN
Solar/Wind Harmer
10.415
25196808ZIMRHP
Adder
77.888
25194608D.CRK4
Adder
1.647
252510AF1-249 C
Solar/Wind Harmer
0.418
253316AC1-085 GEN3
Solar/Wind Harmer
8.32
946171AF1-282 GEN
Solar/Wind Harmer
9.938
25196008MFTGT1
Adder
1.321
253398AE2-221_GEN2
Solar/Wind Harmer
4.228
945681AF1-233 GEN
Solar/Wind Harmer
17.15
270273AD2-016 GEN
Solar/Wind Harmer
2.264
339221AD2-048_GEN
Solar/Wind Harmer
1.291
943111AE2-339 GEN
Solar/Wind Harmer
0.692
253370AE2-315 SEC1
Adder
1.567
253371AE2-315 SEC2
Adder
1.482
270222AC2-111 GEN
Solar/Wind Harmer
3.487
944031AF1-071 GEN
Solar/Wind Harmer
0.785
25326309TAIT D
Adder
0.826
3429421JKCT 10G
Adder
6.274
3429241JKCT 3G
Adder
8.674
942081AE2-220 GEN
Solar/Wind Harmer
4.085
270209AC1-174_GEN
Solar/Wind Harmer
2.599
270437AC2-090 C
Solar/Wind Harmer
3.565
270239V3-007_GEN1
Solar/Wind Harmer
1.099
339211AE2-254 GEN
Solar/Wind Harmer
0.956
24728605AND G2
Adder
2.264
270005AE1-210 C O1
Solar/Wind Harmer
3.176
970653AG2-424 GEN
Solar/Wind Harmer
2.799
253333AC1-068 GEN
Solar/Wind Harmer
0.604
970825AG2-519 GEN
Solar/Wind Harmer
1.201
339241AF1-083 GEN
Solar/Wind Harmer
0.903
276903AD2-071 C
Solar/Wind Harmer
5.316
945371AF1-202 GEN
Solar/Wind Harmer
3.708
970091AG2-072 GEN
Adder
40.26
270594AE1-207 GEN
Solar/Wind Harmer
7.041
270032AE2-172
Solar/Wind Harmer
2.411
958861AF2-177 GEN
Solar/Wind Harmer
5.577
24803106KYGER 3LP
50/50
2.445
24803306KYGER 4LP
50/50
2.394
971191AH1-055 GEN
Solar/Wind Harmer
72.303
252507AC2-088 GEN
Solar/Wind Harmer
2.004
252519AF1-045_GEN
Solar/Wind Harmer
3.791
25194608D.CRK4
Adder
1.647
252524AE2-267 GEN
Solar/Wind Harmer
1.576
25196608WSDLE5
Adder
8.577
253317AC1-085 GEN4
Solar/Wind Harmer
8.32
946181AF1-283 GEN
Solar/Wind Harmer
12.919
958171AF2-111 GEN
Solar/Wind Harmer
24.139
25196008MFTGT1
Adder
1.279
253394AE2-221_GEN
Solar/Wind Harmer
4.228
972167AH1-666 GEN
Solar/Wind Harmer
7.307
270367AC2-061_GEN
Solar/Wind Harmer
2.836
24803006KYGER 3HP
50/50
4.152
24802806KYGER 2HP
50/50
4.136
24802906KYGER 2LP
50/50
2.428
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.286
25183208HLCRTG
Solar/Wind Harmer
6.412
25194408D.CRK1
Adder
7.577
25194508D.CRK3
Adder
1.417
962581AG1-107 GEN
Solar/Wind Harmer
4.372
961491AF2-440 GEN
Solar/Wind Harmer
1.817
270269AC2-059
Solar/Wind Harmer
7.941
253415AE1-040 GEN
Solar/Wind Harmer
0.933
972043AH1-570 GEN
Solar/Wind Harmer
2.055
972045AH1-571 GEN
Solar/Wind Harmer
1.644
971125AH1-004 GEN
Solar/Wind Harmer
3.154
970107AG2-081 GEN
Solar/Wind Harmer
2.365
253370AE2-315 SEC1
Adder
1.567
25322209TAIT E
Adder
7.355
25322209TAIT E
Adder
7.19
253349AC2-067 GEN
Solar/Wind Harmer
1.516
253400AC2-068 GEN
Solar/Wind Harmer
0.61
25326109MON D
Adder
0.965
942891AE2-308 GEN
Solar/Wind Harmer
7.186
926881AC1-175 GEN
Solar/Wind Harmer
3.565
270383AD1-128 GEN
Solar/Wind Harmer
3.837
970883AG2-550 GEN
Solar/Wind Harmer
6.124
970885AG2-551 GEN
Solar/Wind Harmer
1.424
964571AG1-320 GEN
Solar/Wind Harmer
4.93
247621Y3-024
Adder
0.138
964611AG1-324 GEN
Solar/Wind Harmer
0.293
270201AC2-176 GEN
Solar/Wind Harmer
2.858
24725505WLD G2 C
Solar/Wind Harmer
2.172
24699105WLD G1 C
Solar/Wind Harmer
2.146
270031AE2-169
Solar/Wind Harmer
4.335
270599AE1-208 GEN
Solar/Wind Harmer
4.335
25326509SID D
Adder
0.676
339236AF1-050_GEN
Solar/Wind Harmer
0.931
970291AG2-192 GEN
Solar/Wind Harmer
0.649
970291AG2-192 GEN
Solar/Wind Harmer
0.209
944541AF1-119 GEN
Solar/Wind Harmer
2.09
960971AF2-388 GEN
Solar/Wind Harmer
5.455
339231AF1-038_GEN
Solar/Wind Harmer
0.897
253378AE2-206_GEN
Solar/Wind Harmer
1.709
964781AG1-341 GEN
Solar/Wind Harmer
5.034
945391AF1-204 GEN
Solar/Wind Harmer
6.561
942221AE2-234 GEN
Solar/Wind Harmer
1.631
971485AH1-239 GEN
Solar/Wind Harmer
3.621
966021AG1-471 GEN
Solar/Wind Harmer
2.415
970241AG2-163 GEN
Solar/Wind Harmer
10.778
237033AB1-150 GEN
Solar/Wind Helper
0.376
24802606KYGER 1HP
50/50
4.181
24802706KYGER 1LP
50/50
2.452
24803506KYGER 5LP
50/50
2.394
971985AH1-537 GEN
Solar/Wind Harmer
49.573
25196408WSDLE3
Adder
8.83
253433AC1-085 GEN1
Solar/Wind Harmer
5.281
253432AC1-085 GEN2
Solar/Wind Harmer
0.266
25196108MFTGT2
Adder
1.456
25196108MFTGT2
Adder
1.352
972163AH1-664 GEN
Solar/Wind Harmer
8.997
972165AH1-665 GEN
Solar/Wind Harmer
7.198
253406AD2-031_GEN
Solar/Wind Harmer
1.124
339216AC1-074 GEN
Solar/Wind Harmer
1.434
270340AC2-060 GEN
Solar/Wind Harmer
2.588
270263AC1-001 GEN
Solar/Wind Harmer
0.893
253372AE2-315 SEC3
Adder
1.482
253372AE2-315 SEC3
Adder
1.482
25306009OHH W.
Adder
2.212
3429211JKCT 2G
Adder
8.562
270356AE2-297 GEN
Solar/Wind Harmer
3.125
270432AC2-029 GEN
Solar/Wind Harmer
4.647
971029AG2-637 GEN
Solar/Wind Harmer
9.596
241972AD1-140 GEN
Solar/Wind Harmer
2.835
270543AE2-219 C
Solar/Wind Harmer
6.124
247536S-71 GEN
Solar/Wind Harmer
2.375
253338AC1-165 GEN
Solar/Wind Harmer
0.626
253343AC1-166 GEN
Solar/Wind Harmer
0.626
964611AG1-324 GEN
Solar/Wind Harmer
2.185
961761AG1-017 GEN
Solar/Wind Harmer
0.238
945581AF1-223 GEN
Solar/Wind Harmer
2.41
970289AG2-191 GEN
Solar/Wind Harmer
0.949
958711AF2-162 GEN
Solar/Wind Harmer
0.505
270444AC2-157 GEN1
Solar/Wind Harmer
2.766
270445AC2-157 GEN2
Solar/Wind Harmer
2.766
24729505KEY G4
Adder
3.017
964901AG1-354 GEN
Solar/Wind Harmer
7.63
270024AE2-089 GEN
Solar/Wind Harmer
2.348
965651AG1-433 GEN
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
19.4
960001AF2-291 GEN
Solar/Wind Helper
1.679
270331AC1-082 GEN3
Solar/Wind Helper
0.185
235780M24_1
Solar/Wind Helper
0.466
270186AC1-089 GEN
Solar/Wind Harmer
5.382
339243AC2-075 GEN1
Solar/Wind Harmer
0.388
253303V4-073 C
Solar/Wind Harmer
0.091
253370AE2-315 SEC1
Adder
1.567
253371AE2-315 SEC2
Adder
1.482
3429391JKCT 9G
Adder
6.274
960071AF2-298 GEN
Solar/Wind Harmer
1.127
970093AG2-073 GEN
Solar/Wind Harmer
3.641
24379505HDWTR1G C
Solar/Wind Harmer
5.05
270240V3-007_GEN2
Solar/Wind Harmer
3.951
970455AG2-298 GEN
Solar/Wind Harmer
2.176
24728505AND G1
Adder
2.264
270004AE1-209 GEN
Solar/Wind Harmer
3.176
970653AG2-424 GEN
Solar/Wind Harmer
0.405
253325AC1-069 GEN
Solar/Wind Harmer
0.604
946031AF1-268 GEN
Solar/Wind Harmer
4.781
970825AG2-519 GEN
Solar/Wind Harmer
3.226
339206AE1-143 GEN
Solar/Wind Harmer
1.202
962031AG1-047 GEN
Solar/Wind Harmer
1.681
957741AF2-068 GEN
Solar/Wind Harmer
8.342
270518AE2-148 GEN
Solar/Wind Harmer
6.232
972273AH1-721 GEN
Adder
42.523
965461AG1-414 GEN
Solar/Wind Harmer
1.132
970289AG2-191 GEN
Solar/Wind Harmer
0.383
247642Z2-115 C
Solar/Wind Harmer
0.031
339255AE2-071 GEN
Solar/Wind Harmer
0.56
339250AF1-203 GEN
Solar/Wind Harmer
0.288
276820AF1-078_GEN
Solar/Wind Harmer
0.759
970193AG2-126 GEN
Solar/Wind Harmer
7.062
944531AF1-118 GEN
Solar/Wind Harmer
15.85
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
5.772
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.344
TVALTFEXP_TVA->PJM
CLTF
2.874
NYPJM->LTFIMP_NY
CLTF
1.419
LGEELTFEXP_LGEE->PJM
CLTF
4.847
WECLTFEXP_WEC->PJM
CLTF
1.374
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.143
AG2-052LTFEXP_AG2-052->PJM
LTF
0.088
AH1-155LTFEXP_AH1-155->PJM
LTF
0.132
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.588
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.625
MECLTFEXP_MEC->PJM
CLTF
6.138
SIGELTFEXP_SIGE->PJM
CLTF
0.297
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.11
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 42.52 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 44.26 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P7-1_#11019___SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11019___SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.15 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1634.72
MW Contribution:
34.89
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.147
24802806KYGER 2HP
50/50
4.132
24802906KYGER 2LP
50/50
2.425
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.286
25183208HLCRTG
Solar/Wind Harmer
6.401
24803406KYGER 5HP
50/50
4.099
24803206KYGER 4HP
50/50
4.09
252516AE2-318_GEN
Solar/Wind Harmer
10.431
25196808ZIMRHP
Adder
78.006
25194608D.CRK4
Adder
1.659
252510AF1-249 C
Solar/Wind Harmer
0.42
253316AC1-085 GEN3
Solar/Wind Harmer
8.268
946171AF1-282 GEN
Solar/Wind Harmer
9.876
25196008MFTGT1
Adder
1.335
253398AE2-221_GEN2
Solar/Wind Harmer
4.207
945681AF1-233 GEN
Solar/Wind Harmer
16.945
270273AD2-016 GEN
Solar/Wind Harmer
2.226
339221AD2-048_GEN
Solar/Wind Harmer
1.278
270222AC2-111 GEN
Solar/Wind Harmer
3.666
944031AF1-071 GEN
Solar/Wind Harmer
0.825
253370AE2-315 SEC1
Adder
1.572
253371AE2-315 SEC2
Adder
1.486
943111AE2-339 GEN
Solar/Wind Harmer
0.683
942081AE2-220 GEN
Solar/Wind Harmer
4.877
270209AC1-174_GEN
Solar/Wind Harmer
3.103
270437AC2-090 C
Solar/Wind Harmer
4.256
270239V3-007_GEN1
Solar/Wind Harmer
1.312
25326309TAIT D
Adder
0.828
3429421JKCT 10G
Adder
6.186
965651AG1-433 GEN
Solar/Wind Harmer
3.967
958861AF2-177 GEN
Solar/Wind Harmer
7.933
945371AF1-202 GEN
Solar/Wind Harmer
5.062
270005AE1-210 C O1
Solar/Wind Harmer
3.962
3429241JKCT 3G
Adder
8.54
970825AG2-519 GEN
Solar/Wind Harmer
1.408
24728605AND G2
Adder
2.43
339211AE2-254 GEN
Solar/Wind Harmer
0.938
276903AD2-071 C
Solar/Wind Harmer
5.798
270594AE1-207 GEN
Solar/Wind Harmer
7.838
270032AE2-172
Solar/Wind Harmer
2.684
253333AC1-068 GEN
Solar/Wind Harmer
0.598
970653AG2-424 GEN
Solar/Wind Harmer
2.75
270024AE2-089 GEN
Solar/Wind Harmer
2.518
339241AF1-083 GEN
Solar/Wind Harmer
0.882
970091AG2-072 GEN
Adder
38.234
964901AG1-354 GEN
Solar/Wind Harmer
7.432
24802606KYGER 1HP
50/50
4.177
24802706KYGER 1LP
50/50
2.449
24803506KYGER 5LP
50/50
2.392
971985AH1-537 GEN
Solar/Wind Harmer
49.507
25196408WSDLE3
Adder
8.895
253433AC1-085 GEN1
Solar/Wind Harmer
5.248
253432AC1-085 GEN2
Solar/Wind Harmer
0.264
25196108MFTGT2
Adder
1.472
25196108MFTGT2
Adder
1.367
972163AH1-664 GEN
Solar/Wind Harmer
8.886
972165AH1-665 GEN
Solar/Wind Harmer
7.109
253406AD2-031_GEN
Solar/Wind Harmer
1.116
339216AC1-074 GEN
Solar/Wind Harmer
1.421
270340AC2-060 GEN
Solar/Wind Harmer
2.555
270263AC1-001 GEN
Solar/Wind Harmer
0.877
253372AE2-315 SEC3
Adder
1.486
253372AE2-315 SEC3
Adder
1.486
25306009OHH W.
Adder
2.227
270356AE2-297 GEN
Solar/Wind Harmer
3.397
24729505KEY G4
Adder
4.712
958711AF2-162 GEN
Solar/Wind Harmer
0.734
945581AF1-223 GEN
Solar/Wind Harmer
3.291
3429211JKCT 2G
Adder
8.429
971029AG2-637 GEN
Solar/Wind Harmer
10.454
270543AE2-219 C
Solar/Wind Harmer
6.73
270432AC2-029 GEN
Solar/Wind Harmer
4.565
247536S-71 GEN
Solar/Wind Harmer
2.631
964611AG1-324 GEN
Solar/Wind Harmer
2.484
241972AD1-140 GEN
Solar/Wind Harmer
2.83
961761AG1-017 GEN
Solar/Wind Harmer
0.268
253338AC1-165 GEN
Solar/Wind Harmer
0.62
253343AC1-166 GEN
Solar/Wind Harmer
0.62
970289AG2-191 GEN
Solar/Wind Harmer
1.03
270444AC2-157 GEN1
Solar/Wind Harmer
2.679
270445AC2-157 GEN2
Solar/Wind Harmer
2.679
960001AF2-291 GEN
Solar/Wind Helper
1.677
270331AC1-082 GEN3
Solar/Wind Helper
0.186
24803106KYGER 3LP
50/50
2.442
24803306KYGER 4LP
50/50
2.392
971191AH1-055 GEN
Solar/Wind Harmer
71.988
252507AC2-088 GEN
Solar/Wind Harmer
2.003
252519AF1-045_GEN
Solar/Wind Harmer
3.797
25194608D.CRK4
Adder
1.659
252524AE2-267 GEN
Solar/Wind Harmer
1.588
25196608WSDLE5
Adder
8.641
253317AC1-085 GEN4
Solar/Wind Harmer
8.268
946181AF1-283 GEN
Solar/Wind Harmer
12.839
25196008MFTGT1
Adder
1.293
958171AF2-111 GEN
Solar/Wind Harmer
23.953
253394AE2-221_GEN
Solar/Wind Harmer
4.207
972167AH1-666 GEN
Solar/Wind Harmer
7.221
270367AC2-061_GEN
Solar/Wind Harmer
2.804
270186AC1-089 GEN
Solar/Wind Harmer
5.313
339243AC2-075 GEN1
Solar/Wind Harmer
0.385
253303V4-073 C
Solar/Wind Harmer
0.091
253370AE2-315 SEC1
Adder
1.572
253371AE2-315 SEC2
Adder
1.486
24379505HDWTR1G C
Solar/Wind Harmer
6.03
270240V3-007_GEN2
Solar/Wind Harmer
4.718
960071AF2-298 GEN
Solar/Wind Harmer
1.133
3429391JKCT 9G
Adder
6.186
944531AF1-118 GEN
Solar/Wind Harmer
25.425
270004AE1-209 GEN
Solar/Wind Harmer
3.962
946031AF1-268 GEN
Solar/Wind Harmer
5.635
970093AG2-073 GEN
Solar/Wind Harmer
3.576
970825AG2-519 GEN
Solar/Wind Harmer
3.78
24728505AND G1
Adder
2.43
962031AG1-047 GEN
Solar/Wind Harmer
1.892
957741AF2-068 GEN
Solar/Wind Harmer
9.384
970455AG2-298 GEN
Solar/Wind Harmer
2.144
253325AC1-069 GEN
Solar/Wind Harmer
0.598
970653AG2-424 GEN
Solar/Wind Harmer
0.398
339206AE1-143 GEN
Solar/Wind Harmer
1.176
965461AG1-414 GEN
Solar/Wind Harmer
1.229
970289AG2-191 GEN
Solar/Wind Harmer
0.416
270518AE2-148 GEN
Solar/Wind Harmer
6.193
247642Z2-115 C
Solar/Wind Harmer
0.033
972273AH1-721 GEN
Adder
41.179
276820AF1-078_GEN
Solar/Wind Harmer
0.747
339255AE2-071 GEN
Solar/Wind Harmer
0.544
339250AF1-203 GEN
Solar/Wind Harmer
0.28
970193AG2-126 GEN
Solar/Wind Harmer
6.921
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
25194408D.CRK1
Adder
7.63
25194508D.CRK3
Adder
1.427
962581AG1-107 GEN
Solar/Wind Harmer
4.324
961491AF2-440 GEN
Solar/Wind Harmer
1.797
270269AC2-059
Solar/Wind Harmer
7.807
253415AE1-040 GEN
Solar/Wind Harmer
0.922
972043AH1-570 GEN
Solar/Wind Harmer
2.031
972045AH1-571 GEN
Solar/Wind Harmer
1.625
253370AE2-315 SEC1
Adder
1.572
971125AH1-004 GEN
Solar/Wind Harmer
3.116
970107AG2-081 GEN
Solar/Wind Harmer
2.337
926881AC1-175 GEN
Solar/Wind Harmer
4.256
25322209TAIT E
Adder
7.38
25322209TAIT E
Adder
7.214
253349AC2-067 GEN
Solar/Wind Harmer
1.537
253400AC2-068 GEN
Solar/Wind Harmer
0.618
25326109MON D
Adder
0.965
944541AF1-119 GEN
Solar/Wind Harmer
3.039
960971AF2-388 GEN
Solar/Wind Harmer
7.934
270383AD1-128 GEN
Solar/Wind Harmer
4.402
942891AE2-308 GEN
Solar/Wind Harmer
7.07
970883AG2-550 GEN
Solar/Wind Harmer
6.73
970885AG2-551 GEN
Solar/Wind Harmer
1.565
964611AG1-324 GEN
Solar/Wind Harmer
0.333
247621Y3-024
Adder
0.152
270201AC2-176 GEN
Solar/Wind Harmer
3.215
24725505WLD G2 C
Solar/Wind Harmer
2.387
24699105WLD G1 C
Solar/Wind Harmer
2.359
964571AG1-320 GEN
Solar/Wind Harmer
4.862
270031AE2-169
Solar/Wind Harmer
4.804
270599AE1-208 GEN
Solar/Wind Harmer
4.804
970291AG2-192 GEN
Solar/Wind Harmer
0.705
970291AG2-192 GEN
Solar/Wind Harmer
0.227
25326509SID D
Adder
0.666
339236AF1-050_GEN
Solar/Wind Harmer
0.907
339231AF1-038_GEN
Solar/Wind Harmer
0.869
942221AE2-234 GEN
Solar/Wind Harmer
1.672
253378AE2-206_GEN
Solar/Wind Harmer
1.682
945391AF1-204 GEN
Solar/Wind Harmer
6.43
964781AG1-341 GEN
Solar/Wind Harmer
4.886
971485AH1-239 GEN
Solar/Wind Harmer
3.491
966021AG1-471 GEN
Solar/Wind Harmer
2.326
LAGNLTFEXP_LAGN->PJM
CLTF
5.383
TVALTFEXP_TVA->PJM
CLTF
2.678
NYPJM->LTFIMP_NY
CLTF
1.353
LGEELTFEXP_LGEE->PJM
CLTF
4.807
WECLTFEXP_WEC->PJM
CLTF
1.252
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.209
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.121
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.356
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.982
MECLTFEXP_MEC->PJM
CLTF
5.697
SIGELTFEXP_SIGE->PJM
CLTF
0.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.183
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 41.18 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o 34569 34598 34524_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
34569 34598 34524_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.24 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1620.65
MW Contribution:
35.2
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
34569 34598 34524_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.92 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1862.17
MW Contribution:
36.75
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.18
24802706KYGER 1LP
50/50
2.451
24803506KYGER 5LP
50/50
2.394
25250008NTE_CT
50/50
1.874
25250108NTE_ST
50/50
1.428
24803106KYGER 3LP
50/50
2.444
24803306KYGER 4LP
50/50
2.394
971191AH1-055 GEN
Solar/Wind Harmer
72.075
252507AC2-088 GEN
Solar/Wind Harmer
2.075
252519AF1-045_GEN
Solar/Wind Harmer
4.054
252524AE2-267 GEN
Solar/Wind Harmer
1.74
25196608WSDLE5
Adder
9.473
25194608D.CRK4
Adder
1.804
25196008MFTGT1
Adder
1.342
958171AF2-111 GEN
Solar/Wind Harmer
24.038
253317AC1-085 GEN4
Solar/Wind Harmer
7.629
946181AF1-283 GEN
Solar/Wind Harmer
11.847
972167AH1-666 GEN
Solar/Wind Harmer
7.254
270367AC2-061_GEN
Solar/Wind Harmer
2.783
339243AC2-075 GEN1
Solar/Wind Harmer
0.389
270186AC1-089 GEN
Solar/Wind Harmer
5.237
253394AE2-221_GEN
Solar/Wind Harmer
3.688
3429391JKCT 9G
Adder
6.228
970093AG2-073 GEN
Solar/Wind Harmer
3.604
24379505HDWTR1G C
Solar/Wind Harmer
5.117
270240V3-007_GEN2
Solar/Wind Harmer
4.003
970455AG2-298 GEN
Solar/Wind Harmer
2.164
253303V4-073 C
Solar/Wind Harmer
0.069
253370AE2-315 SEC1
Adder
1.193
253371AE2-315 SEC2
Adder
1.129
24728505AND G1
Adder
2.269
960071AF2-298 GEN
Solar/Wind Harmer
0.884
270004AE1-209 GEN
Solar/Wind Harmer
3.191
946031AF1-268 GEN
Solar/Wind Harmer
4.773
24803006KYGER 3HP
50/50
4.151
24802806KYGER 2HP
50/50
4.136
24802906KYGER 2LP
50/50
2.427
252509AD1-136 GEN
Solar/Wind Harmer
0.296
25194408D.CRK1
Adder
8.3
25194508D.CRK3
Adder
1.552
25183208HLCRTG
Solar/Wind Harmer
6.57
962581AG1-107 GEN
Solar/Wind Harmer
4.143
961491AF2-440 GEN
Solar/Wind Harmer
1.722
270269AC2-059
Solar/Wind Harmer
7.653
972043AH1-570 GEN
Solar/Wind Harmer
2.049
972045AH1-571 GEN
Solar/Wind Harmer
1.639
971125AH1-004 GEN
Solar/Wind Harmer
3.142
970107AG2-081 GEN
Solar/Wind Harmer
2.356
253415AE1-040 GEN
Solar/Wind Harmer
0.85
942891AE2-308 GEN
Solar/Wind Harmer
7.124
926881AC1-175 GEN
Solar/Wind Harmer
3.612
270383AD1-128 GEN
Solar/Wind Harmer
3.829
253349AC2-067 GEN
Solar/Wind Harmer
1.237
253400AC2-068 GEN
Solar/Wind Harmer
0.497
970883AG2-550 GEN
Solar/Wind Harmer
6.014
970885AG2-551 GEN
Solar/Wind Harmer
1.399
964571AG1-320 GEN
Solar/Wind Harmer
4.901
253370AE2-315 SEC1
Adder
1.193
25322209TAIT E
Adder
5.625
25322209TAIT E
Adder
5.499
247621Y3-024
Adder
0.136
964611AG1-324 GEN
Solar/Wind Harmer
0.291
270201AC2-176 GEN
Solar/Wind Harmer
2.828
25326109MON D
Adder
0.721
24725505WLD G2 C
Solar/Wind Harmer
2.164
24699105WLD G1 C
Solar/Wind Harmer
2.139
270031AE2-169
Solar/Wind Harmer
4.312
270599AE1-208 GEN
Solar/Wind Harmer
4.312
339236AF1-050_GEN
Solar/Wind Harmer
0.916
944541AF1-119 GEN
Solar/Wind Harmer
2.077
960971AF2-388 GEN
Solar/Wind Harmer
5.423
970291AG2-192 GEN
Solar/Wind Harmer
0.642
970291AG2-192 GEN
Solar/Wind Harmer
0.207
339231AF1-038_GEN
Solar/Wind Harmer
0.877
964781AG1-341 GEN
Solar/Wind Harmer
4.932
945391AF1-204 GEN
Solar/Wind Harmer
6.434
942221AE2-234 GEN
Solar/Wind Harmer
1.6
971485AH1-239 GEN
Solar/Wind Harmer
3.524
966021AG1-471 GEN
Solar/Wind Harmer
2.348
24803406KYGER 5HP
50/50
4.103
24803206KYGER 4HP
50/50
4.094
252516AE2-318_GEN
Solar/Wind Harmer
11.138
25194608D.CRK4
Adder
1.804
252510AF1-249 C
Solar/Wind Harmer
0.456
25196808ZIMRHP
Adder
81.595
25196008MFTGT1
Adder
1.386
253316AC1-085 GEN3
Solar/Wind Harmer
7.629
946171AF1-282 GEN
Solar/Wind Harmer
9.113
945681AF1-233 GEN
Solar/Wind Harmer
17.022
339221AD2-048_GEN
Solar/Wind Harmer
1.291
270273AD2-016 GEN
Solar/Wind Harmer
2.182
253398AE2-221_GEN2
Solar/Wind Harmer
3.688
943111AE2-339 GEN
Solar/Wind Harmer
0.688
270222AC2-111 GEN
Solar/Wind Harmer
3.467
944031AF1-071 GEN
Solar/Wind Harmer
0.78
3429421JKCT 10G
Adder
6.228
3429241JKCT 3G
Adder
8.601
942081AE2-220 GEN
Solar/Wind Harmer
4.139
270209AC1-174_GEN
Solar/Wind Harmer
2.633
270437AC2-090 C
Solar/Wind Harmer
3.612
270239V3-007_GEN1
Solar/Wind Harmer
1.113
339211AE2-254 GEN
Solar/Wind Harmer
0.946
253370AE2-315 SEC1
Adder
1.193
253371AE2-315 SEC2
Adder
1.129
24728605AND G2
Adder
2.269
270005AE1-210 C O1
Solar/Wind Harmer
3.191
25326309TAIT D
Adder
0.632
970653AG2-424 GEN
Solar/Wind Harmer
2.774
970825AG2-519 GEN
Solar/Wind Harmer
1.201
339241AF1-083 GEN
Solar/Wind Harmer
0.89
945371AF1-202 GEN
Solar/Wind Harmer
3.703
276903AD2-071 C
Solar/Wind Harmer
5.286
253333AC1-068 GEN
Solar/Wind Harmer
0.546
270594AE1-207 GEN
Solar/Wind Harmer
6.982
270032AE2-172
Solar/Wind Harmer
2.391
958861AF2-177 GEN
Solar/Wind Harmer
5.553
970091AG2-072 GEN
Adder
38.889
964901AG1-354 GEN
Solar/Wind Harmer
7.5
965651AG1-433 GEN
Solar/Wind Harmer
2.711
270024AE2-089 GEN
Solar/Wind Harmer
2.306
960001AF2-291 GEN
Solar/Wind Helper
1.678
270331AC1-082 GEN3
Solar/Wind Helper
0.186
971985AH1-537 GEN
Solar/Wind Harmer
50.178
25196408WSDLE3
Adder
9.751
25196108MFTGT2
Adder
1.528
25196108MFTGT2
Adder
1.418
253433AC1-085 GEN1
Solar/Wind Harmer
4.843
253432AC1-085 GEN2
Solar/Wind Harmer
0.244
972163AH1-664 GEN
Solar/Wind Harmer
8.928
972165AH1-665 GEN
Solar/Wind Harmer
7.142
339216AC1-074 GEN
Solar/Wind Harmer
1.438
270263AC1-001 GEN
Solar/Wind Harmer
0.863
270340AC2-060 GEN
Solar/Wind Harmer
2.393
253406AD2-031_GEN
Solar/Wind Harmer
0.982
3429211JKCT 2G
Adder
8.489
270356AE2-297 GEN
Solar/Wind Harmer
3.167
270432AC2-029 GEN
Solar/Wind Harmer
4.421
971029AG2-637 GEN
Solar/Wind Harmer
9.394
25306009OHH W.
Adder
1.747
270543AE2-219 C
Solar/Wind Harmer
6.014
253372AE2-315 SEC3
Adder
1.129
253372AE2-315 SEC3
Adder
1.129
247536S-71 GEN
Solar/Wind Harmer
2.339
964611AG1-324 GEN
Solar/Wind Harmer
2.166
961761AG1-017 GEN
Solar/Wind Harmer
0.235
945581AF1-223 GEN
Solar/Wind Harmer
2.407
253338AC1-165 GEN
Solar/Wind Harmer
0.566
253343AC1-166 GEN
Solar/Wind Harmer
0.566
958711AF2-162 GEN
Solar/Wind Harmer
0.502
970289AG2-191 GEN
Solar/Wind Harmer
0.938
270444AC2-157 GEN1
Solar/Wind Harmer
2.7
270445AC2-157 GEN2
Solar/Wind Harmer
2.7
241972AD1-140 GEN
Solar/Wind Harmer
2.089
24729505KEY G4
Adder
2.983
970653AG2-424 GEN
Solar/Wind Harmer
0.401
970825AG2-519 GEN
Solar/Wind Harmer
3.224
339206AE1-143 GEN
Solar/Wind Harmer
1.186
962031AG1-047 GEN
Solar/Wind Harmer
1.663
957741AF2-068 GEN
Solar/Wind Harmer
8.252
253325AC1-069 GEN
Solar/Wind Harmer
0.546
972273AH1-721 GEN
Adder
41.552
965461AG1-414 GEN
Solar/Wind Harmer
1.12
970289AG2-191 GEN
Solar/Wind Harmer
0.379
247642Z2-115 C
Solar/Wind Harmer
0.03
339255AE2-071 GEN
Solar/Wind Harmer
0.549
339250AF1-203 GEN
Solar/Wind Harmer
0.283
970193AG2-126 GEN
Solar/Wind Harmer
6.925
944531AF1-118 GEN
Solar/Wind Harmer
15.636
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
5.472
TVALTFEXP_TVA->PJM
CLTF
2.709
NYPJM->LTFIMP_NY
CLTF
1.375
LGEELTFEXP_LGEE->PJM
CLTF
4.87
WECLTFEXP_WEC->PJM
CLTF
1.323
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.209
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.127
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.578
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.139
MECLTFEXP_MEC->PJM
CLTF
5.918
SIGELTFEXP_SIGE->PJM
CLTF
0.295
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.539
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 41.55 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 43.38 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.94 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1616.13
MW Contribution:
33.53
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:114.49 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1763.1
MW Contribution:
34.94
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.171
24802706KYGER 1LP
50/50
2.446
24803506KYGER 5LP
50/50
2.388
971985AH1-537 GEN
Solar/Wind Harmer
49.138
25196408WSDLE3
Adder
8.592
253433AC1-085 GEN1
Solar/Wind Harmer
5.144
253432AC1-085 GEN2
Solar/Wind Harmer
0.259
25196108MFTGT2
Adder
1.412
25196108MFTGT2
Adder
1.312
972163AH1-664 GEN
Solar/Wind Harmer
8.663
972165AH1-665 GEN
Solar/Wind Harmer
6.93
253406AD2-031_GEN
Solar/Wind Harmer
1.092
270263AC1-001 GEN
Solar/Wind Harmer
0.871
270340AC2-060 GEN
Solar/Wind Harmer
2.516
339216AC1-074 GEN
Solar/Wind Harmer
1.38
253372AE2-315 SEC3
Adder
1.442
253372AE2-315 SEC3
Adder
1.442
25306009OHH W.
Adder
2.151
3429211JKCT 2G
Adder
8.167
270356AE2-297 GEN
Solar/Wind Harmer
3.013
270432AC2-029 GEN
Solar/Wind Harmer
4.541
971029AG2-637 GEN
Solar/Wind Harmer
9.271
241972AD1-140 GEN
Solar/Wind Harmer
2.765
270543AE2-219 C
Solar/Wind Harmer
5.912
247536S-71 GEN
Solar/Wind Harmer
2.291
253338AC1-165 GEN
Solar/Wind Harmer
0.612
253343AC1-166 GEN
Solar/Wind Harmer
0.612
964611AG1-324 GEN
Solar/Wind Harmer
2.105
961761AG1-017 GEN
Solar/Wind Harmer
0.229
945581AF1-223 GEN
Solar/Wind Harmer
2.32
958711AF2-162 GEN
Solar/Wind Harmer
0.486
970289AG2-191 GEN
Solar/Wind Harmer
0.909
270444AC2-157 GEN1
Solar/Wind Harmer
2.592
270445AC2-157 GEN2
Solar/Wind Harmer
2.592
24729505KEY G4
Adder
2.902
24803106KYGER 3LP
50/50
2.439
24803306KYGER 4LP
50/50
2.388
971191AH1-055 GEN
Solar/Wind Harmer
71.816
252507AC2-088 GEN
Solar/Wind Harmer
1.953
252519AF1-045_GEN
Solar/Wind Harmer
3.69
25194608D.CRK4
Adder
1.602
252524AE2-267 GEN
Solar/Wind Harmer
1.534
25196608WSDLE5
Adder
8.347
253317AC1-085 GEN4
Solar/Wind Harmer
8.104
946181AF1-283 GEN
Solar/Wind Harmer
12.584
958171AF2-111 GEN
Solar/Wind Harmer
23.383
25196008MFTGT1
Adder
1.241
253394AE2-221_GEN
Solar/Wind Harmer
4.119
972167AH1-666 GEN
Solar/Wind Harmer
7.042
270367AC2-061_GEN
Solar/Wind Harmer
2.733
270186AC1-089 GEN
Solar/Wind Harmer
5.181
339243AC2-075 GEN1
Solar/Wind Harmer
0.374
253303V4-073 C
Solar/Wind Harmer
0.088
253370AE2-315 SEC1
Adder
1.524
253371AE2-315 SEC2
Adder
1.442
960071AF2-298 GEN
Solar/Wind Harmer
1.097
3429391JKCT 9G
Adder
5.997
970093AG2-073 GEN
Solar/Wind Harmer
3.458
24379505HDWTR1G C
Solar/Wind Harmer
4.872
270240V3-007_GEN2
Solar/Wind Harmer
3.812
970455AG2-298 GEN
Solar/Wind Harmer
2.061
24728505AND G1
Adder
2.168
253325AC1-069 GEN
Solar/Wind Harmer
0.59
270004AE1-209 GEN
Solar/Wind Harmer
3.058
946031AF1-268 GEN
Solar/Wind Harmer
4.604
970825AG2-519 GEN
Solar/Wind Harmer
3.105
970653AG2-424 GEN
Solar/Wind Harmer
0.382
962031AG1-047 GEN
Solar/Wind Harmer
1.62
957741AF2-068 GEN
Solar/Wind Harmer
8.036
339206AE1-143 GEN
Solar/Wind Harmer
1.13
270518AE2-148 GEN
Solar/Wind Harmer
6.093
965461AG1-414 GEN
Solar/Wind Harmer
1.085
970289AG2-191 GEN
Solar/Wind Harmer
0.367
972273AH1-721 GEN
Adder
39.573
276820AF1-078_GEN
Solar/Wind Harmer
0.74
247642Z2-115 C
Solar/Wind Harmer
0.029
970193AG2-126 GEN
Solar/Wind Harmer
6.675
339255AE2-071 GEN
Solar/Wind Harmer
0.521
339250AF1-203 GEN
Solar/Wind Harmer
0.268
944531AF1-118 GEN
Solar/Wind Harmer
15.239
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270329AC1-082 GEN1
Solar/Wind Helper
0.188
24803006KYGER 3HP
50/50
4.141
24802806KYGER 2HP
50/50
4.126
24802906KYGER 2LP
50/50
2.422
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.279
25183208HLCRTG
Solar/Wind Harmer
6.246
25194408D.CRK1
Adder
7.371
25194508D.CRK3
Adder
1.378
962581AG1-107 GEN
Solar/Wind Harmer
4.214
961491AF2-440 GEN
Solar/Wind Harmer
1.751
270269AC2-059
Solar/Wind Harmer
7.764
253415AE1-040 GEN
Solar/Wind Harmer
0.907
972043AH1-570 GEN
Solar/Wind Harmer
1.972
972045AH1-571 GEN
Solar/Wind Harmer
1.578
253370AE2-315 SEC1
Adder
1.524
971125AH1-004 GEN
Solar/Wind Harmer
3.022
970107AG2-081 GEN
Solar/Wind Harmer
2.267
25322209TAIT E
Adder
7.158
25322209TAIT E
Adder
6.998
253349AC2-067 GEN
Solar/Wind Harmer
1.474
253400AC2-068 GEN
Solar/Wind Harmer
0.593
25326109MON D
Adder
0.94
942891AE2-308 GEN
Solar/Wind Harmer
6.845
926881AC1-175 GEN
Solar/Wind Harmer
3.439
270383AD1-128 GEN
Solar/Wind Harmer
3.701
970883AG2-550 GEN
Solar/Wind Harmer
5.912
970885AG2-551 GEN
Solar/Wind Harmer
1.375
964571AG1-320 GEN
Solar/Wind Harmer
4.664
247621Y3-024
Adder
0.133
964611AG1-324 GEN
Solar/Wind Harmer
0.282
270201AC2-176 GEN
Solar/Wind Harmer
2.754
24725505WLD G2 C
Solar/Wind Harmer
2.084
24699105WLD G1 C
Solar/Wind Harmer
2.059
270031AE2-169
Solar/Wind Harmer
4.168
270599AE1-208 GEN
Solar/Wind Harmer
4.168
25326509SID D
Adder
0.658
944541AF1-119 GEN
Solar/Wind Harmer
2.011
960971AF2-388 GEN
Solar/Wind Harmer
5.248
339236AF1-050_GEN
Solar/Wind Harmer
0.871
970291AG2-192 GEN
Solar/Wind Harmer
0.622
970291AG2-192 GEN
Solar/Wind Harmer
0.2
253378AE2-206_GEN
Solar/Wind Harmer
1.666
339231AF1-038_GEN
Solar/Wind Harmer
0.834
942221AE2-234 GEN
Solar/Wind Harmer
1.568
945391AF1-204 GEN
Solar/Wind Harmer
6.202
964781AG1-341 GEN
Solar/Wind Harmer
4.685
24803406KYGER 5HP
50/50
4.093
24803206KYGER 4HP
50/50
4.084
252516AE2-318_GEN
Solar/Wind Harmer
10.14
25196808ZIMRHP
Adder
75.73
25194608D.CRK4
Adder
1.602
252510AF1-249 C
Solar/Wind Harmer
0.406
253316AC1-085 GEN3
Solar/Wind Harmer
8.104
946171AF1-282 GEN
Solar/Wind Harmer
9.68
25196008MFTGT1
Adder
1.281
253398AE2-221_GEN2
Solar/Wind Harmer
4.119
945681AF1-233 GEN
Solar/Wind Harmer
16.525
270273AD2-016 GEN
Solar/Wind Harmer
2.214
339221AD2-048_GEN
Solar/Wind Harmer
1.241
253370AE2-315 SEC1
Adder
1.524
253371AE2-315 SEC2
Adder
1.442
270222AC2-111 GEN
Solar/Wind Harmer
3.38
944031AF1-071 GEN
Solar/Wind Harmer
0.76
943111AE2-339 GEN
Solar/Wind Harmer
0.662
25326309TAIT D
Adder
0.804
3429421JKCT 10G
Adder
5.997
3429241JKCT 3G
Adder
8.274
942081AE2-220 GEN
Solar/Wind Harmer
3.941
270209AC1-174_GEN
Solar/Wind Harmer
2.508
270437AC2-090 C
Solar/Wind Harmer
3.439
270239V3-007_GEN1
Solar/Wind Harmer
1.06
339211AE2-254 GEN
Solar/Wind Harmer
0.904
24728605AND G2
Adder
2.168
253333AC1-068 GEN
Solar/Wind Harmer
0.59
270005AE1-210 C O1
Solar/Wind Harmer
3.058
970825AG2-519 GEN
Solar/Wind Harmer
1.156
970653AG2-424 GEN
Solar/Wind Harmer
2.64
945371AF1-202 GEN
Solar/Wind Harmer
3.569
339241AF1-083 GEN
Solar/Wind Harmer
0.848
276903AD2-071 C
Solar/Wind Harmer
5.097
270594AE1-207 GEN
Solar/Wind Harmer
6.753
270032AE2-172
Solar/Wind Harmer
2.313
958861AF2-177 GEN
Solar/Wind Harmer
5.366
970091AG2-072 GEN
Adder
37.252
270024AE2-089 GEN
Solar/Wind Harmer
2.261
965651AG1-433 GEN
Solar/Wind Harmer
2.624
964901AG1-354 GEN
Solar/Wind Harmer
7.132
960001AF2-291 GEN
Solar/Wind Helper
1.683
270331AC1-082 GEN3
Solar/Wind Helper
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
5.198
TVALTFEXP_TVA->PJM
CLTF
2.56
NYPJM->LTFIMP_NY
CLTF
1.355
LGEELTFEXP_LGEE->PJM
CLTF
4.619
WECLTFEXP_WEC->PJM
CLTF
1.296
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.041
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.249
AG2-052LTFEXP_AG2-052->PJM
LTF
0.083
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.966
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.434
MECLTFEXP_MEC->PJM
CLTF
5.745
SIGELTFEXP_SIGE->PJM
CLTF
0.281
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.364
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 39.57 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 41.25 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT5_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT5_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.91 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1600.21
MW Contribution:
33.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT5_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.35 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1745.55
MW Contribution:
34.96
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.142
24802806KYGER 2HP
50/50
4.126
24802906KYGER 2LP
50/50
2.422
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.279
25183208HLCRTG
Solar/Wind Harmer
6.247
25194408D.CRK1
Adder
7.373
25194508D.CRK3
Adder
1.378
962581AG1-107 GEN
Solar/Wind Harmer
4.215
961491AF2-440 GEN
Solar/Wind Harmer
1.752
270269AC2-059
Solar/Wind Harmer
7.766
253415AE1-040 GEN
Solar/Wind Harmer
0.908
972043AH1-570 GEN
Solar/Wind Harmer
1.973
972045AH1-571 GEN
Solar/Wind Harmer
1.578
253370AE2-315 SEC1
Adder
1.525
971125AH1-004 GEN
Solar/Wind Harmer
3.023
970107AG2-081 GEN
Solar/Wind Harmer
2.267
25322209TAIT E
Adder
7.161
25322209TAIT E
Adder
7
253349AC2-067 GEN
Solar/Wind Harmer
1.474
253400AC2-068 GEN
Solar/Wind Harmer
0.593
25326109MON D
Adder
0.94
942891AE2-308 GEN
Solar/Wind Harmer
6.847
926881AC1-175 GEN
Solar/Wind Harmer
3.44
270383AD1-128 GEN
Solar/Wind Harmer
3.703
970883AG2-550 GEN
Solar/Wind Harmer
5.914
970885AG2-551 GEN
Solar/Wind Harmer
1.375
964571AG1-320 GEN
Solar/Wind Harmer
4.665
247621Y3-024
Adder
0.133
24802606KYGER 1HP
50/50
4.171
24802706KYGER 1LP
50/50
2.446
24803506KYGER 5LP
50/50
2.389
971985AH1-537 GEN
Solar/Wind Harmer
49.142
25196408WSDLE3
Adder
8.594
253433AC1-085 GEN1
Solar/Wind Harmer
5.145
253432AC1-085 GEN2
Solar/Wind Harmer
0.259
25196108MFTGT2
Adder
1.413
25196108MFTGT2
Adder
1.312
972163AH1-664 GEN
Solar/Wind Harmer
8.665
972165AH1-665 GEN
Solar/Wind Harmer
6.932
253406AD2-031_GEN
Solar/Wind Harmer
1.092
270263AC1-001 GEN
Solar/Wind Harmer
0.871
270340AC2-060 GEN
Solar/Wind Harmer
2.517
339216AC1-074 GEN
Solar/Wind Harmer
1.38
253372AE2-315 SEC3
Adder
1.442
253372AE2-315 SEC3
Adder
1.442
25306009OHH W.
Adder
2.152
3429211JKCT 2G
Adder
8.17
270356AE2-297 GEN
Solar/Wind Harmer
3.014
270432AC2-029 GEN
Solar/Wind Harmer
4.543
971029AG2-637 GEN
Solar/Wind Harmer
9.275
241972AD1-140 GEN
Solar/Wind Harmer
2.767
270543AE2-219 C
Solar/Wind Harmer
5.914
247536S-71 GEN
Solar/Wind Harmer
2.292
253338AC1-165 GEN
Solar/Wind Harmer
0.612
253343AC1-166 GEN
Solar/Wind Harmer
0.612
964611AG1-324 GEN
Solar/Wind Harmer
2.106
961761AG1-017 GEN
Solar/Wind Harmer
0.229
945581AF1-223 GEN
Solar/Wind Harmer
2.321
958711AF2-162 GEN
Solar/Wind Harmer
0.486
970289AG2-191 GEN
Solar/Wind Harmer
0.909
270444AC2-157 GEN1
Solar/Wind Harmer
2.593
270445AC2-157 GEN2
Solar/Wind Harmer
2.593
24729505KEY G4
Adder
2.903
24803406KYGER 5HP
50/50
4.094
24803206KYGER 4HP
50/50
4.085
252516AE2-318_GEN
Solar/Wind Harmer
10.142
25196808ZIMRHP
Adder
75.748
25194608D.CRK4
Adder
1.603
252510AF1-249 C
Solar/Wind Harmer
0.406
253316AC1-085 GEN3
Solar/Wind Harmer
8.106
946171AF1-282 GEN
Solar/Wind Harmer
9.682
25196008MFTGT1
Adder
1.282
253398AE2-221_GEN2
Solar/Wind Harmer
4.12
945681AF1-233 GEN
Solar/Wind Harmer
16.529
270273AD2-016 GEN
Solar/Wind Harmer
2.214
339221AD2-048_GEN
Solar/Wind Harmer
1.241
253370AE2-315 SEC1
Adder
1.525
253371AE2-315 SEC2
Adder
1.442
270222AC2-111 GEN
Solar/Wind Harmer
3.381
944031AF1-071 GEN
Solar/Wind Harmer
0.761
943111AE2-339 GEN
Solar/Wind Harmer
0.663
25326309TAIT D
Adder
0.804
3429421JKCT 10G
Adder
5.999
3429241JKCT 3G
Adder
8.277
942081AE2-220 GEN
Solar/Wind Harmer
3.942
270209AC1-174_GEN
Solar/Wind Harmer
2.508
270437AC2-090 C
Solar/Wind Harmer
3.44
270239V3-007_GEN1
Solar/Wind Harmer
1.061
339211AE2-254 GEN
Solar/Wind Harmer
0.905
24728605AND G2
Adder
2.169
253333AC1-068 GEN
Solar/Wind Harmer
0.59
270005AE1-210 C O1
Solar/Wind Harmer
3.06
970825AG2-519 GEN
Solar/Wind Harmer
1.157
970653AG2-424 GEN
Solar/Wind Harmer
2.641
945371AF1-202 GEN
Solar/Wind Harmer
3.57
339241AF1-083 GEN
Solar/Wind Harmer
0.848
276903AD2-071 C
Solar/Wind Harmer
5.099
270594AE1-207 GEN
Solar/Wind Harmer
6.756
270032AE2-172
Solar/Wind Harmer
2.314
958861AF2-177 GEN
Solar/Wind Harmer
5.369
970091AG2-072 GEN
Adder
37.27
270024AE2-089 GEN
Solar/Wind Harmer
2.262
965651AG1-433 GEN
Solar/Wind Harmer
2.625
964901AG1-354 GEN
Solar/Wind Harmer
7.136
960001AF2-291 GEN
Solar/Wind Helper
1.683
270331AC1-082 GEN3
Solar/Wind Helper
0.187
24803106KYGER 3LP
50/50
2.439
24803306KYGER 4LP
50/50
2.389
971191AH1-055 GEN
Solar/Wind Harmer
71.821
252507AC2-088 GEN
Solar/Wind Harmer
1.953
252519AF1-045_GEN
Solar/Wind Harmer
3.691
25194608D.CRK4
Adder
1.603
252524AE2-267 GEN
Solar/Wind Harmer
1.534
25196608WSDLE5
Adder
8.349
253317AC1-085 GEN4
Solar/Wind Harmer
8.106
946181AF1-283 GEN
Solar/Wind Harmer
12.587
958171AF2-111 GEN
Solar/Wind Harmer
23.388
25196008MFTGT1
Adder
1.241
253394AE2-221_GEN
Solar/Wind Harmer
4.12
972167AH1-666 GEN
Solar/Wind Harmer
7.044
270367AC2-061_GEN
Solar/Wind Harmer
2.734
270186AC1-089 GEN
Solar/Wind Harmer
5.183
339243AC2-075 GEN1
Solar/Wind Harmer
0.374
253303V4-073 C
Solar/Wind Harmer
0.088
253370AE2-315 SEC1
Adder
1.525
253371AE2-315 SEC2
Adder
1.442
960071AF2-298 GEN
Solar/Wind Harmer
1.097
3429391JKCT 9G
Adder
5.999
970093AG2-073 GEN
Solar/Wind Harmer
3.46
24379505HDWTR1G C
Solar/Wind Harmer
4.874
270240V3-007_GEN2
Solar/Wind Harmer
3.813
970455AG2-298 GEN
Solar/Wind Harmer
2.061
24728505AND G1
Adder
2.169
253325AC1-069 GEN
Solar/Wind Harmer
0.59
270004AE1-209 GEN
Solar/Wind Harmer
3.06
946031AF1-268 GEN
Solar/Wind Harmer
4.606
970825AG2-519 GEN
Solar/Wind Harmer
3.106
970653AG2-424 GEN
Solar/Wind Harmer
0.382
962031AG1-047 GEN
Solar/Wind Harmer
1.621
957741AF2-068 GEN
Solar/Wind Harmer
8.04
339206AE1-143 GEN
Solar/Wind Harmer
1.131
270518AE2-148 GEN
Solar/Wind Harmer
6.095
965461AG1-414 GEN
Solar/Wind Harmer
1.085
970289AG2-191 GEN
Solar/Wind Harmer
0.367
972273AH1-721 GEN
Adder
39.592
276820AF1-078_GEN
Solar/Wind Harmer
0.741
247642Z2-115 C
Solar/Wind Harmer
0.029
970193AG2-126 GEN
Solar/Wind Harmer
6.679
339255AE2-071 GEN
Solar/Wind Harmer
0.522
339250AF1-203 GEN
Solar/Wind Harmer
0.269
944531AF1-118 GEN
Solar/Wind Harmer
15.247
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270329AC1-082 GEN1
Solar/Wind Helper
0.188
964611AG1-324 GEN
Solar/Wind Harmer
0.283
270201AC2-176 GEN
Solar/Wind Harmer
2.755
24725505WLD G2 C
Solar/Wind Harmer
2.085
24699105WLD G1 C
Solar/Wind Harmer
2.06
270031AE2-169
Solar/Wind Harmer
4.17
270599AE1-208 GEN
Solar/Wind Harmer
4.17
25326509SID D
Adder
0.658
944541AF1-119 GEN
Solar/Wind Harmer
2.012
960971AF2-388 GEN
Solar/Wind Harmer
5.251
339236AF1-050_GEN
Solar/Wind Harmer
0.871
970291AG2-192 GEN
Solar/Wind Harmer
0.622
970291AG2-192 GEN
Solar/Wind Harmer
0.2
253378AE2-206_GEN
Solar/Wind Harmer
1.667
339231AF1-038_GEN
Solar/Wind Harmer
0.835
942221AE2-234 GEN
Solar/Wind Harmer
1.569
945391AF1-204 GEN
Solar/Wind Harmer
6.205
964781AG1-341 GEN
Solar/Wind Harmer
4.687
LAGNLTFEXP_LAGN->PJM
CLTF
5.203
TVALTFEXP_TVA->PJM
CLTF
2.563
NYPJM->LTFIMP_NY
CLTF
1.353
LGEELTFEXP_LGEE->PJM
CLTF
4.621
WECLTFEXP_WEC->PJM
CLTF
1.297
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.248
AG2-052LTFEXP_AG2-052->PJM
LTF
0.083
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.443
MECLTFEXP_MEC->PJM
CLTF
5.749
SIGELTFEXP_SIGE->PJM
CLTF
0.281
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.395
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 39.59 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 41.27 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#316_05AMOS 765_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#316_05AMOS 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.35 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1560.82
MW Contribution:
33.6
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#316_05AMOS 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:116.21 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1789.67
MW Contribution:
35.35
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.141
24802706KYGER 1LP
50/50
2.428
24803506KYGER 5LP
50/50
2.371
971985AH1-537 GEN
Solar/Wind Harmer
48.849
25196408WSDLE3
Adder
8.575
253433AC1-085 GEN1
Solar/Wind Harmer
5.13
253432AC1-085 GEN2
Solar/Wind Harmer
0.258
25196108MFTGT2
Adder
1.411
25196108MFTGT2
Adder
1.31
972163AH1-664 GEN
Solar/Wind Harmer
8.638
972165AH1-665 GEN
Solar/Wind Harmer
6.911
253406AD2-031_GEN
Solar/Wind Harmer
1.088
270340AC2-060 GEN
Solar/Wind Harmer
2.501
270263AC1-001 GEN
Solar/Wind Harmer
0.862
339216AC1-074 GEN
Solar/Wind Harmer
1.378
253372AE2-315 SEC3
Adder
1.438
253372AE2-315 SEC3
Adder
1.438
25306009OHH W.
Adder
2.146
3429211JKCT 2G
Adder
8.16
270356AE2-297 GEN
Solar/Wind Harmer
3.016
270432AC2-029 GEN
Solar/Wind Harmer
4.502
971029AG2-637 GEN
Solar/Wind Harmer
9.279
241972AD1-140 GEN
Solar/Wind Harmer
2.76
270543AE2-219 C
Solar/Wind Harmer
5.919
247536S-71 GEN
Solar/Wind Harmer
2.295
253338AC1-165 GEN
Solar/Wind Harmer
0.61
253343AC1-166 GEN
Solar/Wind Harmer
0.61
964611AG1-324 GEN
Solar/Wind Harmer
2.11
961761AG1-017 GEN
Solar/Wind Harmer
0.23
945581AF1-223 GEN
Solar/Wind Harmer
2.326
958711AF2-162 GEN
Solar/Wind Harmer
0.487
970289AG2-191 GEN
Solar/Wind Harmer
0.913
270444AC2-157 GEN1
Solar/Wind Harmer
2.615
270445AC2-157 GEN2
Solar/Wind Harmer
2.615
24729505KEY G4
Adder
2.912
24803106KYGER 3LP
50/50
2.421
24803306KYGER 4LP
50/50
2.371
971191AH1-055 GEN
Solar/Wind Harmer
71.356
252507AC2-088 GEN
Solar/Wind Harmer
1.948
252519AF1-045_GEN
Solar/Wind Harmer
3.681
25194608D.CRK4
Adder
1.599
252524AE2-267 GEN
Solar/Wind Harmer
1.53
25196608WSDLE5
Adder
8.33
253317AC1-085 GEN4
Solar/Wind Harmer
8.083
946181AF1-283 GEN
Solar/Wind Harmer
12.551
958171AF2-111 GEN
Solar/Wind Harmer
23.332
25196008MFTGT1
Adder
1.239
253394AE2-221_GEN
Solar/Wind Harmer
4.108
972167AH1-666 GEN
Solar/Wind Harmer
7.022
270367AC2-061_GEN
Solar/Wind Harmer
2.716
270186AC1-089 GEN
Solar/Wind Harmer
5.151
339243AC2-075 GEN1
Solar/Wind Harmer
0.373
253303V4-073 C
Solar/Wind Harmer
0.088
253370AE2-315 SEC1
Adder
1.521
253371AE2-315 SEC2
Adder
1.438
960071AF2-298 GEN
Solar/Wind Harmer
1.095
3429391JKCT 9G
Adder
5.993
970093AG2-073 GEN
Solar/Wind Harmer
3.456
24379505HDWTR1G C
Solar/Wind Harmer
4.879
270240V3-007_GEN2
Solar/Wind Harmer
3.817
970455AG2-298 GEN
Solar/Wind Harmer
2.065
24728505AND G1
Adder
2.175
253325AC1-069 GEN
Solar/Wind Harmer
0.588
270004AE1-209 GEN
Solar/Wind Harmer
3.065
946031AF1-268 GEN
Solar/Wind Harmer
4.614
970825AG2-519 GEN
Solar/Wind Harmer
3.112
970653AG2-424 GEN
Solar/Wind Harmer
0.383
962031AG1-047 GEN
Solar/Wind Harmer
1.623
957741AF2-068 GEN
Solar/Wind Harmer
8.053
339206AE1-143 GEN
Solar/Wind Harmer
1.133
270518AE2-148 GEN
Solar/Wind Harmer
6.079
965461AG1-414 GEN
Solar/Wind Harmer
1.089
970289AG2-191 GEN
Solar/Wind Harmer
0.369
972273AH1-721 GEN
Adder
39.657
276820AF1-078_GEN
Solar/Wind Harmer
0.74
247642Z2-115 C
Solar/Wind Harmer
0.03
970193AG2-126 GEN
Solar/Wind Harmer
6.722
339255AE2-071 GEN
Solar/Wind Harmer
0.524
339250AF1-203 GEN
Solar/Wind Harmer
0.27
944531AF1-118 GEN
Solar/Wind Harmer
15.299
270330AC1-082 GEN2
Solar/Wind Helper
0.209
270329AC1-082 GEN1
Solar/Wind Helper
0.209
24803006KYGER 3HP
50/50
4.111
24802806KYGER 2HP
50/50
4.096
24802906KYGER 2LP
50/50
2.404
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.278
25183208HLCRTG
Solar/Wind Harmer
6.23
25194408D.CRK1
Adder
7.356
25194508D.CRK3
Adder
1.375
962581AG1-107 GEN
Solar/Wind Harmer
4.188
961491AF2-440 GEN
Solar/Wind Harmer
1.741
270269AC2-059
Solar/Wind Harmer
7.708
253415AE1-040 GEN
Solar/Wind Harmer
0.902
972043AH1-570 GEN
Solar/Wind Harmer
1.969
972045AH1-571 GEN
Solar/Wind Harmer
1.575
253370AE2-315 SEC1
Adder
1.521
971125AH1-004 GEN
Solar/Wind Harmer
3.019
970107AG2-081 GEN
Solar/Wind Harmer
2.264
25322209TAIT E
Adder
7.143
25322209TAIT E
Adder
6.983
253349AC2-067 GEN
Solar/Wind Harmer
1.471
253400AC2-068 GEN
Solar/Wind Harmer
0.592
25326109MON D
Adder
0.938
942891AE2-308 GEN
Solar/Wind Harmer
6.839
926881AC1-175 GEN
Solar/Wind Harmer
3.444
270383AD1-128 GEN
Solar/Wind Harmer
3.706
970883AG2-550 GEN
Solar/Wind Harmer
5.919
970885AG2-551 GEN
Solar/Wind Harmer
1.376
964571AG1-320 GEN
Solar/Wind Harmer
4.676
247621Y3-024
Adder
0.133
964611AG1-324 GEN
Solar/Wind Harmer
0.283
270201AC2-176 GEN
Solar/Wind Harmer
2.759
24725505WLD G2 C
Solar/Wind Harmer
2.091
24699105WLD G1 C
Solar/Wind Harmer
2.066
270031AE2-169
Solar/Wind Harmer
4.18
270599AE1-208 GEN
Solar/Wind Harmer
4.18
25326509SID D
Adder
0.657
944541AF1-119 GEN
Solar/Wind Harmer
2.017
960971AF2-388 GEN
Solar/Wind Harmer
5.265
339236AF1-050_GEN
Solar/Wind Harmer
0.874
970291AG2-192 GEN
Solar/Wind Harmer
0.625
970291AG2-192 GEN
Solar/Wind Harmer
0.201
253378AE2-206_GEN
Solar/Wind Harmer
1.665
339231AF1-038_GEN
Solar/Wind Harmer
0.837
942221AE2-234 GEN
Solar/Wind Harmer
1.574
945391AF1-204 GEN
Solar/Wind Harmer
6.245
964781AG1-341 GEN
Solar/Wind Harmer
4.704
237033AB1-150 GEN
Solar/Wind Helper
0.445
24803406KYGER 5HP
50/50
4.064
24803206KYGER 4HP
50/50
4.055
252516AE2-318_GEN
Solar/Wind Harmer
10.115
25196808ZIMRHP
Adder
75.568
25194608D.CRK4
Adder
1.599
252510AF1-249 C
Solar/Wind Harmer
0.405
253316AC1-085 GEN3
Solar/Wind Harmer
8.083
946171AF1-282 GEN
Solar/Wind Harmer
9.655
25196008MFTGT1
Adder
1.28
253398AE2-221_GEN2
Solar/Wind Harmer
4.108
945681AF1-233 GEN
Solar/Wind Harmer
16.478
270273AD2-016 GEN
Solar/Wind Harmer
2.198
339221AD2-048_GEN
Solar/Wind Harmer
1.239
253370AE2-315 SEC1
Adder
1.521
253371AE2-315 SEC2
Adder
1.438
270222AC2-111 GEN
Solar/Wind Harmer
3.377
944031AF1-071 GEN
Solar/Wind Harmer
0.76
943111AE2-339 GEN
Solar/Wind Harmer
0.662
25326309TAIT D
Adder
0.802
3429421JKCT 10G
Adder
5.993
3429241JKCT 3G
Adder
8.267
942081AE2-220 GEN
Solar/Wind Harmer
3.946
270209AC1-174_GEN
Solar/Wind Harmer
2.511
270437AC2-090 C
Solar/Wind Harmer
3.444
270239V3-007_GEN1
Solar/Wind Harmer
1.062
339211AE2-254 GEN
Solar/Wind Harmer
0.905
24728605AND G2
Adder
2.175
253333AC1-068 GEN
Solar/Wind Harmer
0.588
270005AE1-210 C O1
Solar/Wind Harmer
3.065
970825AG2-519 GEN
Solar/Wind Harmer
1.159
970653AG2-424 GEN
Solar/Wind Harmer
2.647
945371AF1-202 GEN
Solar/Wind Harmer
3.579
276903AD2-071 C
Solar/Wind Harmer
5.115
339241AF1-083 GEN
Solar/Wind Harmer
0.85
270594AE1-207 GEN
Solar/Wind Harmer
6.778
270032AE2-172
Solar/Wind Harmer
2.321
958861AF2-177 GEN
Solar/Wind Harmer
5.382
970091AG2-072 GEN
Adder
37.724
270024AE2-089 GEN
Solar/Wind Harmer
2.267
965651AG1-433 GEN
Solar/Wind Harmer
2.633
964901AG1-354 GEN
Solar/Wind Harmer
7.156
960001AF2-291 GEN
Solar/Wind Helper
1.773
270331AC1-082 GEN3
Solar/Wind Helper
0.208
235780M24_1
Solar/Wind Helper
0.552
LAGNLTFEXP_LAGN->PJM
CLTF
5.253
TVALTFEXP_TVA->PJM
CLTF
2.588
NYPJM->LTFIMP_NY
CLTF
1.332
LGEELTFEXP_LGEE->PJM
CLTF
4.629
WECLTFEXP_WEC->PJM
CLTF
1.307
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.235
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.126
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.217
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.528
MECLTFEXP_MEC->PJM
CLTF
5.794
SIGELTFEXP_SIGE->PJM
CLTF
0.282
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.728
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 39.66 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 41.73 MW.

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1014_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.54 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:152.81
MW Contribution:
65.61
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.41 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:153.73
MW Contribution:
65.62
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
Adder
65.607
339206AE1-143 GEN
Solar/Wind Helper
1.481
339255AE2-071 GEN
Solar/Wind Helper
0.178
339250AF1-203 GEN
Solar/Wind Helper
0.138
339231AF1-038_GEN
Solar/Wind Helper
2.349
339236AF1-050_GEN
Solar/Wind Helper
0.357
339241AF1-083 GEN
Solar/Wind Helper
0.422
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.109
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.404
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.004
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.215
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.666
G-007ALTFEXP_G-007A->PJM
CMTX
0.08
CPLELTFEXP_CPLE->PJM
CLTF
0.016
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.147
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1014_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.4 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:145.32
MW Contribution:
69.62
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.39 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:146.36
MW Contribution:
69.63
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
69.617

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1024_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.4 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:136.92
MW Contribution:
66.96
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.38 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:136.9
MW Contribution:
66.89
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
Adder
66.96
339255AE2-071 GEN
Solar/Wind Helper
0.164
339250AF1-203 GEN
Solar/Wind Helper
0.126
339231AF1-038_GEN
Solar/Wind Helper
1.418
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.058
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.242
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.121
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.043
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.785
G-007ALTFEXP_G-007A->PJM
CMTX
0.045
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.086
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1008_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.72 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:134.1
MW Contribution:
78.93
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.04 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:134.44
MW Contribution:
79.77
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
1.295
972273AH1-721 GEN
50/50
78.932
339206AE1-143 GEN
Solar/Wind Helper
1.359
339255AE2-071 GEN
Solar/Wind Helper
0.179
339250AF1-203 GEN
Solar/Wind Helper
0.138
339231AF1-038_GEN
Solar/Wind Helper
1.448
339236AF1-050_GEN
Solar/Wind Helper
0.39
339241AF1-083 GEN
Solar/Wind Helper
0.411
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.095
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.372
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.167
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.026
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.038
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.905
G-007ALTFEXP_G-007A->PJM
CMTX
0.062
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.117
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:127.72 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:134.1
MW Contribution:
78.93
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.06 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:134.46
MW Contribution:
79.77
Bus #Bus NameTypeMW Contribution
339231AF1-038_GEN
Solar/Wind Helper
1.448
339236AF1-050_GEN
Solar/Wind Helper
0.39
339241AF1-083 GEN
Solar/Wind Helper
0.411
3429031COOPER2 G
50/50
1.295
972273AH1-721 GEN
50/50
78.932
339206AE1-143 GEN
Solar/Wind Helper
1.359
339255AE2-071 GEN
Solar/Wind Helper
0.179
339250AF1-203 GEN
Solar/Wind Helper
0.138
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.095
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.372
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.167
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.026
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.038
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.905
G-007ALTFEXP_G-007A->PJM
CMTX
0.062
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.117
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1024_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.68 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:128.81
MW Contribution:
71.05
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.39 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:130.61
MW Contribution:
70.98
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.053

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1008_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.08 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:127.14
MW Contribution:
78.93
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.46 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:127.53
MW Contribution:
79.77
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
78.932

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.08 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:127.14
MW Contribution:
78.93
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.46 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:127.53
MW Contribution:
79.77
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
78.932

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P4-6_COOP S42-1039_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-6_COOP S42-1039_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.43 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:107.55
MW Contribution:
66.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
339241AF1-083 GEN
Solar/Wind Helper
0.405
972273AH1-721 GEN
Adder
66.368
339206AE1-143 GEN
Solar/Wind Helper
1.339
339255AE2-071 GEN
Solar/Wind Helper
0.177
339250AF1-203 GEN
Solar/Wind Helper
0.137
339231AF1-038_GEN
Solar/Wind Helper
1.427
339236AF1-050_GEN
Solar/Wind Helper
0.385
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.085
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.341
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.25
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.021
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.861
G-007ALTFEXP_G-007A->PJM
CMTX
0.093
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.18
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line l/o EKPC_P2-3_MAR W38-1014_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_MAR W38-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.07 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:40.98
MW Contribution:
4.56
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_MAR W38-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.72 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:43.57
MW Contribution:
5.47
Bus #Bus NameTypeMW Contribution
339206AE1-143 GEN
Solar/Wind Harmer
2.149
972273AH1-721 GEN
Adder
4.559
339236AF1-050_GEN
Solar/Wind Harmer
1.485
964781AG1-341 GEN
Solar/Wind Harmer
3.299
339241AF1-083 GEN
Solar/Wind Harmer
1.674
964901AG1-354 GEN
Solar/Wind Harmer
11.361
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.159
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.546
LAGNLTFEXP_LAGN->PJM
CLTF
0.439
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.403
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.323
VTFLTFEXP_VFT->PJM
CMTX
0.043
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.814
MECLTFEXP_MEC->PJM
CLTF
0.054
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
CPLELTFEXP_CPLE->PJM
CLTF
0.11
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.013
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.274

Details for 2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line l/o EKPC_P2-3_SSHAD S11-1014_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_SSHAD S11-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.11 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:39.82
MW Contribution:
7.98
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_SSHAD S11-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.7 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:41.22
MW Contribution:
9.25
Bus #Bus NameTypeMW Contribution
339206AE1-143 GEN
Solar/Wind Harmer
1.152
972273AH1-721 GEN
Adder
7.983
964901AG1-354 GEN
Solar/Wind Harmer
17.351
339241AF1-083 GEN
Solar/Wind Harmer
1.536
339236AF1-050_GEN
Solar/Wind Harmer
2.098
950011AG9-010
External Queue
4.951374053955078
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.554
LAGNLTFEXP_LAGN->PJM
CLTF
0.163
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.221
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.135
VTFLTFEXP_VFT->PJM
CMTX
0.037
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.276
G-007ALTFEXP_G-007A->PJM
CMTX
0.014
CPLELTFEXP_CPLE->PJM
CLTF
0.062
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.015
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.035
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line l/o EKPC_P2-2_KU HODG 69_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_KU HODG 69_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.61 %
Rating:50.0 MVA
Rating Type:B
MVA to Mitigate:53.3
MW Contribution:
8.93
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_KU HODG 69_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.98 %
Rating:50.0 MVA
Rating Type:B
MVA to Mitigate:56.99
MW Contribution:
10.58
Bus #Bus NameTypeMW Contribution
339206AE1-143 GEN
Solar/Wind Harmer
1.435
339241AF1-083 GEN
Solar/Wind Harmer
1.026
970653AG2-424 GEN
Solar/Wind Harmer
2.725
964901AG1-354 GEN
Solar/Wind Harmer
5.9
970653AG2-424 GEN
Solar/Wind Harmer
0.394
972273AH1-721 GEN
Adder
8.927
950011AG9-010
External Queue
10.121600151062012
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.151
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.505
LAGNLTFEXP_LAGN->PJM
CLTF
0.397
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.36
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.277
WECLTFEXP_WEC->PJM
CLTF
0.001
VTFLTFEXP_VFT->PJM
CMTX
0.039
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.027
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.693
MECLTFEXP_MEC->PJM
CLTF
0.078
G-007ALTFEXP_G-007A->PJM
CMTX
0.015
CPLELTFEXP_CPLE->PJM
CLTF
0.099
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.516

Details for 2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line l/o EKPC_P2-2_BARDIT-EBARD69_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_BARDIT-EBARD69_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.69 %
Rating:50.0 MVA
Rating Type:B
MVA to Mitigate:52.34
MW Contribution:
6.87
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_BARDIT-EBARD69_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.82 %
Rating:50.0 MVA
Rating Type:B
MVA to Mitigate:55.41
MW Contribution:
8.2
Bus #Bus NameTypeMW Contribution
339241AF1-083 GEN
Solar/Wind Harmer
0.794
964901AG1-354 GEN
Solar/Wind Harmer
4.299
339206AE1-143 GEN
Solar/Wind Harmer
1.181
972273AH1-721 GEN
Adder
6.868
950011AG9-010
External Queue
8.503388404846191
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.073
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.218
LAGNLTFEXP_LAGN->PJM
CLTF
0.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.269
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.212
WECLTFEXP_WEC->PJM
CLTF
0.003
VTFLTFEXP_VFT->PJM
CMTX
0.02
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.113
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.559
MECLTFEXP_MEC->PJM
CLTF
0.072
SIGELTFEXP_SIGE->PJM
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.008
CPLELTFEXP_CPLE->PJM
CLTF
0.073
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.002
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.274

Details for 2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line l/o EKPC_P2-3_SSHAD S11-1014_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_SSHAD S11-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.27 %
Rating:50.0 MVA
Rating Type:B
MVA to Mitigate:50.63
MW Contribution:
9.99
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_SSHAD S11-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.37 %
Rating:50.0 MVA
Rating Type:B
MVA to Mitigate:53.69
MW Contribution:
11.7
Bus #Bus NameTypeMW Contribution
339206AE1-143 GEN
Solar/Wind Harmer
1.75
339236AF1-050_GEN
Solar/Wind Harmer
1.414
972273AH1-721 GEN
Adder
9.995
339241AF1-083 GEN
Solar/Wind Harmer
1.378
964901AG1-354 GEN
Solar/Wind Harmer
11.694
950011AG9-010
External Queue
11.699796676635742
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.155
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.542
LAGNLTFEXP_LAGN->PJM
CLTF
0.244
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.261
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.177
VTFLTFEXP_VFT->PJM
CMTX
0.024
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.402
MECLTFEXP_MEC->PJM
CLTF
0.019
G-007ALTFEXP_G-007A->PJM
CMTX
0.009
CPLELTFEXP_CPLE->PJM
CLTF
0.072
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.003
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.732

Details for 2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line l/o EKPC_P2-3_SSHAD S11-1004_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_SSHAD S11-1004_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.15 %
Rating:50.0 MVA
Rating Type:B
MVA to Mitigate:50.07
MW Contribution:
9.66
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_SSHAD S11-1004_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.87 %
Rating:50.0 MVA
Rating Type:B
MVA to Mitigate:52.93
MW Contribution:
11.31
Bus #Bus NameTypeMW Contribution
339206AE1-143 GEN
Solar/Wind Harmer
1.747
972273AH1-721 GEN
Adder
9.665
339241AF1-083 GEN
Solar/Wind Harmer
1.375
964901AG1-354 GEN
Solar/Wind Harmer
11.664
339236AF1-050_GEN
Solar/Wind Harmer
1.41
950011AG9-010
External Queue
11.663920402526855
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.137
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.474
LAGNLTFEXP_LAGN->PJM
CLTF
0.207
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.227
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.151
NYPJM->LTFIMP_NY
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.017
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.338
MECLTFEXP_MEC->PJM
CLTF
0.012
G-007ALTFEXP_G-007A->PJM
CMTX
0.006
CPLELTFEXP_CPLE->PJM
CLTF
0.063
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.603

Details for 2W LONDON-2W LONDON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_TYNER E13-1014_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
2W LONDON-2W LONDON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_TYNER E13-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.46 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:56.33
MW Contribution:
13.22
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
2W LONDON-2W LONDON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_TYNER E13-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.21 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:60.82
MW Contribution:
15.68
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
Adder
15.555
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.023
LAGNLTFEXP_LAGN->PJM
CLTF
0.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.178
TVALTFEXP_TVA->PJM
CLTF
0.125
NYPJM->LTFIMP_NY
CLTF
0.001
WECLTFEXP_WEC->PJM
CLTF
0.003
VTFLTFEXP_VFT->PJM
CMTX
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.102
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.357
MECLTFEXP_MEC->PJM
CLTF
0.046
SIGELTFEXP_SIGE->PJM
CLTF
0.001
G-007ALTFEXP_G-007A->PJM
CMTX
0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.048
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.788
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 15.55 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 18.43 MW.

Details for 2W LONDON-2W LONDON T 69.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-PIT-TY161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
2W LONDON-2W LONDON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-PIT-TY161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.98 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:49.67
MW Contribution:
15.07
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
2W LONDON-2W LONDON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-PIT-TY161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.88 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:54.69
MW Contribution:
17.75
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.3
972273AH1-721 GEN
Adder
17.734
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.003
LAGNLTFEXP_LAGN->PJM
CLTF
0.22
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.205
TVALTFEXP_TVA->PJM
CLTF
0.149
NYPJM->LTFIMP_NY
CLTF
0.001
WECLTFEXP_WEC->PJM
CLTF
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.178
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.442
MECLTFEXP_MEC->PJM
CLTF
0.062
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.055
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.993
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 17.73 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 20.87 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:196.67 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:544.77
MW Contribution:
307.56
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
339241AF1-083 GEN
Solar/Wind Harmer
1.642
964901AG1-354 GEN
Solar/Wind Harmer
13.431
339211AE2-254 GEN
Solar/Wind Harmer
0.738
970653AG2-424 GEN
Solar/Wind Harmer
2.314
3429031COOPER2 G
50/50
5.924
972273AH1-721 GEN
50/50
363.261
339206AE1-143 GEN
Solar/Wind Harmer
2.391
339255AE2-071 GEN
Solar/Wind Harmer
1.036
339250AF1-203 GEN
Solar/Wind Harmer
0.533
970653AG2-424 GEN
Solar/Wind Harmer
0.335
3429451LAUREL 1G
50/50
1.17
971485AH1-239 GEN
Solar/Wind Harmer
12.338
966021AG1-471 GEN
Solar/Wind Harmer
8.255
339231AF1-038_GEN
Solar/Wind Harmer
2.312
339236AF1-050_GEN
Solar/Wind Harmer
1.637
964781AG1-341 GEN
Solar/Wind Harmer
8.957
950011AG9-010
External Queue
9.896462440490723
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
LAGNLTFEXP_LAGN->PJM
CLTF
1.46
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.515
TVALTFEXP_TVA->PJM
CLTF
1.072
NYPJM->LTFIMP_NY
CLTF
0.067
WECLTFEXP_WEC->PJM
CLTF
0.058
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.927
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.18
MECLTFEXP_MEC->PJM
CLTF
0.521
SIGELTFEXP_SIGE->PJM
CLTF
0.016
CPLELTFEXP_CPLE->PJM
CLTF
0.097
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.21
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 363.26 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:164.25 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:454.97
MW Contribution:
307.56
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
363.261
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 363.26 MW.

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EXT_B-345-100_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_B-345-100_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.74 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:265.49
MW Contribution:
109.3
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_B-345-100_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.27 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:278.53
MW Contribution:
115.62
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
128.701
3429031COOPER2 G
50/50
2.061
3429451LAUREL 1G
50/50
1.726
971485AH1-239 GEN
Solar/Wind Harmer
3.709
966021AG1-471 GEN
Solar/Wind Harmer
2.467
LAGNLTFEXP_LAGN->PJM
CLTF
0.859
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.485
TVALTFEXP_TVA->PJM
CLTF
0.599
NYPJM->LTFIMP_NY
CLTF
0.03
LGEELTFEXP_LGEE->PJM
CLTF
0.031
WECLTFEXP_WEC->PJM
CLTF
0.035
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.17
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.875
MECLTFEXP_MEC->PJM
CLTF
0.307
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
0.112
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.315
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 128.7 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 136.0 MW.

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EXT_B-345-100_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_B-345-100_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.66 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:245.32
MW Contribution:
109.3
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_B-345-100_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.08 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:258.17
MW Contribution:
115.62
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
128.701
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 128.7 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 136.0 MW.

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:118.86 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:237.73
MW Contribution:
80.01
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.589
339231AF1-038_GEN
Solar/Wind Harmer
0.92
971485AH1-239 GEN
Solar/Wind Harmer
3.63
966021AG1-471 GEN
Solar/Wind Harmer
2.413
972273AH1-721 GEN
50/50
93.946
3429031COOPER2 G
50/50
1.481
LAGNLTFEXP_LAGN->PJM
CLTF
0.612
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.3
TVALTFEXP_TVA->PJM
CLTF
0.42
NYPJM->LTFIMP_NY
CLTF
0.026
LGEELTFEXP_LGEE->PJM
CLTF
0.109
WECLTFEXP_WEC->PJM
CLTF
0.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.086
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.4
MECLTFEXP_MEC->PJM
CLTF
0.251
SIGELTFEXP_SIGE->PJM
CLTF
0.013
CPLELTFEXP_CPLE->PJM
CLTF
0.064
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.322
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 93.95 MW.

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.22 %
Rating:174.0 MVA
Rating Type:A
MVA to Mitigate:205.7
MW Contribution:
62.08
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.9 %
Rating:174.0 MVA
Rating Type:A
MVA to Mitigate:234.73
MW Contribution:
80.12
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.521
972273AH1-721 GEN
50/50
73.034
3429031COOPER2 G
50/50
1.164
LAGNLTFEXP_LAGN->PJM
CLTF
0.524
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.268
TVALTFEXP_TVA->PJM
CLTF
0.355
NYPJM->LTFIMP_NY
CLTF
0.022
LGEELTFEXP_LGEE->PJM
CLTF
0.118
WECLTFEXP_WEC->PJM
CLTF
0.029
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.97
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.209
MECLTFEXP_MEC->PJM
CLTF
0.219
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
0.058
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.89
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 73.03 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 94.08 MW.

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.72 %
Rating:174.0 MVA
Rating Type:A
MVA to Mitigate:196.13
MW Contribution:
62.08
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.64 %
Rating:174.0 MVA
Rating Type:A
MVA to Mitigate:222.09
MW Contribution:
80.12
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
73.034
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 73.03 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 94.08 MW.

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1008_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.38 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:224.75
MW Contribution:
93.41
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.71 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:269.42
MW Contribution:
130.27
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
93.413
3429031COOPER2 G
50/50
1.502
3429451LAUREL 1G
50/50
1.596
LAGNLTFEXP_LAGN->PJM
CLTF
0.311
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.178
TVALTFEXP_TVA->PJM
CLTF
0.205
NYPJM->LTFIMP_NY
CLTF
0.02
LGEELTFEXP_LGEE->PJM
CLTF
0.102
WECLTFEXP_WEC->PJM
CLTF
0.015
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.474
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.733
MECLTFEXP_MEC->PJM
CLTF
0.123
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
0.036
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.722

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.38 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:224.75
MW Contribution:
93.41
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:134.7 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:269.4
MW Contribution:
130.27
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
93.413
3429031COOPER2 G
50/50
1.502
3429451LAUREL 1G
50/50
1.596
LAGNLTFEXP_LAGN->PJM
CLTF
0.311
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.178
TVALTFEXP_TVA->PJM
CLTF
0.205
NYPJM->LTFIMP_NY
CLTF
0.02
LGEELTFEXP_LGEE->PJM
CLTF
0.102
WECLTFEXP_WEC->PJM
CLTF
0.015
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.474
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.733
MECLTFEXP_MEC->PJM
CLTF
0.123
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
0.036
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.722

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1024_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.31 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:224.62
MW Contribution:
94.16
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.39 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:268.79
MW Contribution:
131.28
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
94.163
3429031COOPER2 G
50/50
1.514
3429451LAUREL 1G
50/50
1.599
LAGNLTFEXP_LAGN->PJM
CLTF
0.306
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.18
TVALTFEXP_TVA->PJM
CLTF
0.202
NYPJM->LTFIMP_NY
CLTF
0.02
LGEELTFEXP_LGEE->PJM
CLTF
0.098
WECLTFEXP_WEC->PJM
CLTF
0.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.446
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.719
MECLTFEXP_MEC->PJM
CLTF
0.118
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
0.037
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.677

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EXT_324100 7ALCALDE 345 324112 7PINEVILLE 345 1_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_324100 7ALCALDE 345 324112 7PINEVILLE 345 1_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.04 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:220.08
MW Contribution:
69.79
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_324100 7ALCALDE 345 324112 7PINEVILLE 345 1_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.42 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:246.84
MW Contribution:
85.74
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.552
972273AH1-721 GEN
50/50
82.128
3429031COOPER2 G
50/50
1.31
LAGNLTFEXP_LAGN->PJM
CLTF
0.447
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.015
TVALTFEXP_TVA->PJM
CLTF
0.3
NYPJM->LTFIMP_NY
CLTF
0.034
LGEELTFEXP_LGEE->PJM
CLTF
0.248
WECLTFEXP_WEC->PJM
CLTF
0.043
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.006
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.435
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.167
MECLTFEXP_MEC->PJM
CLTF
0.263
SIGELTFEXP_SIGE->PJM
CLTF
0.018
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.994
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 82.13 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 100.71 MW.

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.9 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:219.79
MW Contribution:
80.01
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
93.946
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 93.95 MW.

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1008_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.73 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:217.47
MW Contribution:
93.41
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.59 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:261.17
MW Contribution:
130.27
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
93.413

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.73 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:217.47
MW Contribution:
93.41
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.59 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:261.17
MW Contribution:
130.27
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
93.413

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1024_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.71 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:217.42
MW Contribution:
94.16
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.2 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:260.41
MW Contribution:
131.28
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
94.163

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 1_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.63 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:217.26
MW Contribution:
78.63
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 1_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:127.9 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:255.79
MW Contribution:
107.11
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
92.659
3429031COOPER2 G
50/50
1.488
3429451LAUREL 1G
50/50
1.595
LAGNLTFEXP_LAGN->PJM
CLTF
0.291
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.164
TVALTFEXP_TVA->PJM
CLTF
0.19
NYPJM->LTFIMP_NY
CLTF
0.02
LGEELTFEXP_LGEE->PJM
CLTF
0.102
WECLTFEXP_WEC->PJM
CLTF
0.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.439
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.686
MECLTFEXP_MEC->PJM
CLTF
0.115
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
0.033
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.62
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 92.66 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 126.0 MW.

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_PULASKI 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_PULASKI 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.71 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:215.42
MW Contribution:
68.22
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_PULASKI 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:127.76 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:255.52
MW Contribution:
89.97
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.548
972273AH1-721 GEN
50/50
80.316
3429031COOPER2 G
50/50
1.284
LAGNLTFEXP_LAGN->PJM
CLTF
0.519
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.308
TVALTFEXP_TVA->PJM
CLTF
0.355
NYPJM->LTFIMP_NY
CLTF
0.02
LGEELTFEXP_LGEE->PJM
CLTF
0.089
WECLTFEXP_WEC->PJM
CLTF
0.025
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.82
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.182
MECLTFEXP_MEC->PJM
CLTF
0.2
SIGELTFEXP_SIGE->PJM
CLTF
0.01
CPLELTFEXP_CPLE->PJM
CLTF
0.07
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.734
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 80.32 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 105.72 MW.

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 1_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.12 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:210.24
MW Contribution:
78.63
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 1_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:123.59 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:247.18
MW Contribution:
107.12
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
92.659
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 92.66 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 126.0 MW.

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EXT_324100 7ALCALDE 345 324112 7PINEVILLE 345 1_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_324100 7ALCALDE 345 324112 7PINEVILLE 345 1_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.0 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:210.01
MW Contribution:
69.8
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_324100 7ALCALDE 345 324112 7PINEVILLE 345 1_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.62 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:231.24
MW Contribution:
85.74
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
82.128
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 82.13 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 100.71 MW.

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_PULASKI 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_PULASKI 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.01 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:206.03
MW Contribution:
68.22
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_PULASKI 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.92 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:237.84
MW Contribution:
89.97
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
80.316
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 80.32 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 105.72 MW.

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.42 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:55.85
MW Contribution:
3.42
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.32 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:80.63
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
35.691
971485AH1-239 GEN
Solar/Wind Harmer
36.927
972273AH1-721 GEN
Adder
3.421
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.003
LGEELTFEXP_LGEE->PJM
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.002
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.02
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.012
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.061
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.42 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:55.85
MW Contribution:
3.42
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:149.32 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:80.63
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
Adder
3.421
966021AG1-471 GEN
Solar/Wind Harmer
35.691
971485AH1-239 GEN
Solar/Wind Harmer
36.927
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.003
LGEELTFEXP_LGEE->PJM
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.002
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.02
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.012
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.061
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.0 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:55.62
MW Contribution:
4.33
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
35.596
971485AH1-239 GEN
Solar/Wind Harmer
36.81
972273AH1-721 GEN
Adder
4.333
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.004
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.024
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.035
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.044
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.004
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.16 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:55.16
MW Contribution:
5.45
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:148.65 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:80.27
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
Adder
5.447
966021AG1-471 GEN
Solar/Wind Harmer
27.66
971485AH1-239 GEN
Solar/Wind Harmer
31.89
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0
LGEELTFEXP_LGEE->PJM
CLTF
0.013
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.018
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.109
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11112_05J.FERR 765_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.51 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:347.84
MW Contribution:
15.55
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11112_05J.FERR 765_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.35 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:329.6
MW Contribution:
15.08
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
33.379
24689505VACITY
50/50
3.467
24290105CRG2H
50/50
0.716
971461AH1-227 GEN
Solar/Wind Harmer
2.867
972273AH1-721 GEN
Adder
15.55
24290205CRG2L
50/50
0.6
971313AH1-133 GEN
Solar/Wind Harmer
20.638
24734705WLF1G3
Adder
4.417
24734805WLF1G4
Adder
4.417
24734905WLF1G5
Adder
4.417
24735105WLF2G1
Adder
3.651
24290005CRG1L
50/50
0.584
24735205WLF2G2
Adder
3.651
971687AH1-348 GEN
Solar/Wind Harmer
0.543
24289905CRG1H
50/50
0.697
971225AH1-072 GEN
Solar/Wind Harmer
1.118
971227AH1-073 GEN
Solar/Wind Harmer
1.118
LAGNLTFEXP_LAGN->PJM
CLTF
2.913
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.433
TVALTFEXP_TVA->PJM
CLTF
1.772
NYPJM->LTFIMP_NY
CLTF
0.199
LGEELTFEXP_LGEE->PJM
CLTF
0.644
WECLTFEXP_WEC->PJM
CLTF
0.249
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.741
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.09
MECLTFEXP_MEC->PJM
CLTF
1.418
SIGELTFEXP_SIGE->PJM
CLTF
0.049
CPLELTFEXP_CPLE->PJM
CLTF
0.364
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.839

Details for AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line l/o AEP_P4_#14149_05BROADF 765_Q2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14149_05BROADF 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.63 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:327.47
MW Contribution:
14.82
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14149_05BROADF 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.33 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:296.98
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
33.396
24689505VACITY
50/50
3.456
24290105CRG2H
50/50
0.714
971461AH1-227 GEN
Solar/Wind Harmer
2.861
972273AH1-721 GEN
Adder
14.819
24289905CRG1H
50/50
0.695
971225AH1-072 GEN
Solar/Wind Harmer
1.115
971227AH1-073 GEN
Solar/Wind Harmer
1.115
24290205CRG2L
50/50
0.598
971313AH1-133 GEN
Solar/Wind Harmer
20.662
24734705WLF1G3
Adder
4.382
24734805WLF1G4
Adder
4.382
24734905WLF1G5
Adder
4.382
24735105WLF2G1
Adder
3.603
24290005CRG1L
50/50
0.582
24735205WLF2G2
Adder
3.603
971687AH1-348 GEN
Solar/Wind Harmer
0.542
LAGNLTFEXP_LAGN->PJM
CLTF
2.473
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.74
TVALTFEXP_TVA->PJM
CLTF
1.556
NYPJM->LTFIMP_NY
CLTF
0.186
LGEELTFEXP_LGEE->PJM
CLTF
0.617
WECLTFEXP_WEC->PJM
CLTF
0.233
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.399
MECLTFEXP_MEC->PJM
CLTF
1.291
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.897

Details for AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line l/o AEP_P4_#2916_05J.FERR 765_A_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2916_05J.FERR 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.35 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:326.65
MW Contribution:
14.81
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2916_05J.FERR 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:99.96 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:295.89
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
0.598
971313AH1-133 GEN
Solar/Wind Harmer
20.659
24734705WLF1G3
Adder
4.38
24734805WLF1G4
Adder
4.38
24734905WLF1G5
Adder
4.38
24735105WLF2G1
Adder
3.602
970563AG2-360 GEN
50/50
33.385
24689505VACITY
50/50
3.455
24290105CRG2H
50/50
0.714
971461AH1-227 GEN
Solar/Wind Harmer
2.859
972273AH1-721 GEN
Adder
14.808
24289905CRG1H
50/50
0.695
971225AH1-072 GEN
Solar/Wind Harmer
1.115
971227AH1-073 GEN
Solar/Wind Harmer
1.115
24290005CRG1L
50/50
0.582
24735205WLF2G2
Adder
3.602
971687AH1-348 GEN
Solar/Wind Harmer
0.541
LAGNLTFEXP_LAGN->PJM
CLTF
2.477
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.779
TVALTFEXP_TVA->PJM
CLTF
1.558
NYPJM->LTFIMP_NY
CLTF
0.186
LGEELTFEXP_LGEE->PJM
CLTF
0.615
WECLTFEXP_WEC->PJM
CLTF
0.232
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.16
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.402
MECLTFEXP_MEC->PJM
CLTF
1.288
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.899

Details for AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line l/o AEP_P1-2_#2915_4_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#2915_4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.09 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:316.99
MW Contribution:
14.82
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#2915_4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:96.8 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:286.52
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
24289905CRG1H
50/50
0.695
971225AH1-072 GEN
Solar/Wind Harmer
0.778
971227AH1-073 GEN
Solar/Wind Harmer
0.778
24290005CRG1L
50/50
0.582
24735205WLF2G2
Adder
3.603
971687AH1-348 GEN
Solar/Wind Harmer
0.378
24290205CRG2L
50/50
0.598
971313AH1-133 GEN
Solar/Wind Harmer
11.888
24734705WLF1G3
Adder
4.382
24734805WLF1G4
Adder
4.382
24734905WLF1G5
Adder
4.382
24735105WLF2G1
Adder
3.603
970563AG2-360 GEN
50/50
33.396
24689505VACITY
50/50
3.456
24290105CRG2H
50/50
0.714
971461AH1-227 GEN
Solar/Wind Harmer
1.996
972273AH1-721 GEN
Adder
14.819
LAGNLTFEXP_LAGN->PJM
CLTF
2.473
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.74
TVALTFEXP_TVA->PJM
CLTF
1.556
NYPJM->LTFIMP_NY
CLTF
0.186
LGEELTFEXP_LGEE->PJM
CLTF
0.617
WECLTFEXP_WEC->PJM
CLTF
0.233
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.399
MECLTFEXP_MEC->PJM
CLTF
1.291
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.897

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:128.32 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:269.47
MW Contribution:
301.88
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.014
972273AH1-721 GEN
50/50
301.88
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.081
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.275
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.01
GibsonPJM->LTFIMP_GIBSON
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.068
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.205
G-007ALTFEXP_G-007A->PJM
CMTX
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.007
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.047
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:127.46 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:267.66
MW Contribution:
301.88
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
301.88

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-LAUREL161_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.53 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:211.11
MW Contribution:
309.19
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:267.79 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:562.37
MW Contribution:
625.42
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
309.192
339206AE1-143 GEN
Solar/Wind Helper
2.546
339255AE2-071 GEN
Solar/Wind Helper
0.288
339250AF1-203 GEN
Solar/Wind Helper
0.222
3429451LAUREL 1G
50/50
1.074
339231AF1-038_GEN
Solar/Wind Helper
1.371
339236AF1-050_GEN
Solar/Wind Helper
0.739
339241AF1-083 GEN
Solar/Wind Helper
0.771
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.133
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.571
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.756
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.068
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.613
G-007ALTFEXP_G-007A->PJM
CMTX
0.281
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.568
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CONTINGENCY 'AEP_P4_#9173_05BROADF 765_P_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 290612 CKT Z1   /*05BAKER      765.0 - 05BAKER_RB   765.0
 OPEN BRANCH FROM BUS 242511 TO BUS 290422 CKT 6    /*05BROADF     765.0 - 05BROADFD6EQ   1.0
 OPEN BRANCH FROM BUS 242511 TO BUS 290613 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RB 765.0
 OPEN BRANCH FROM BUS 242518 TO BUS 290422 CKT 6    /*05BROADF     500.0 - 05BROADFD6EQ   1.0
 OPEN BRANCH FROM BUS 242518 TO BUS 360106 CKT 1    /*05BROADF     500.0 - 8SULLIVAN TN 500.0
 OPEN BRANCH FROM BUS 290422 TO BUS 290423 CKT 6    /*05BROADFD6EQ   1.0 - 05BROADFD T6  13.8
 OPEN BRANCH FROM BUS 290612 TO BUS 290613 CKT 1    /*05BAKER_RB   765.0 - 05BROADFR_RB 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 1           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 2           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1          /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 242508 TO BUS 237805 CKT 1 /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1          /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 242508 TO BUS 237805 CKT 1 /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2114-535_SRT-A_SENS'
 OPEN BRANCH FROM BUS 235110 TO BUS 289543 CKT 1   /*01MDWBRK     500.0 - 05YEAT       500.0
 OPEN BRANCH FROM BUS 314085 TO BUS 314110 CKT 1   /*6REMNGCT     230.0 - 6ELK RUN     230.0
 OPEN BRANCH FROM BUS 314110 TO BUS 314125 CKT 1   /*6ELK RUN     230.0 - 6VINTHIL     230.0
 OPEN BUS 314110                                   /*6ELK RUN     230.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'DVP_P2-2: ALTAVISTA 138KV_SRT-A'
 OPEN BUS 314348   /*2GRETN_1      69.0
 OPEN BUS 314667   /*4ALTVSTA     138.0
 OPEN BUS 314670   /*2ALTVSTA      69.0
 OPEN BUS 314680   /*2CHATHAM      69.0
 OPEN BUS 314685   /*2CHTM TP      69.0
 OPEN BUS 314698   /*2TAYLORS MIL  69.0
 OPEN BUS 314709   /*2GLADYS TAP   69.0
 OPEN BUS 314727   /*2CLIMAX DP    69.0
 OPEN BUS 314728   /*2CLMX TP      69.0
 OPEN BUS 314729   /*2GLADYS       69.0
 OPEN BUS 314730   /*3STONE MILL   69.0
 OPEN BUS 314731   /*2GRETNA       69.0
 OPEN BUS 314733   /*2GRNA DP      69.0
 OPEN BUS 314735   /*2ALTAVISTADP  69.0
 OPEN BUS 314736   /*2SHKO DP      69.0
 OPEN BUS 314738   /*2MT AIRY      69.0
 OPEN BUS 314739   /*2MT A TP      69.0
 OPEN BUS 316193   /*RENANTP       69.0
 OPEN BUS 316194   /*AC1-042 MAIN  69.0
 OPEN BUS 316195   /*AC1-042 COL   34.0
 OPEN BUS 316196   /*AC1-042 TERT  13.0
 OPEN BUS 316197   /*AC1-042 GEN    0.4
 OPEN BUS 316214   /*AC1-145 MAIN  69.0
 OPEN BUS 316215   /*AC1-145 COL2  34.5
 OPEN BUS 316216   /*AC1-145 COL1  34.5
 OPEN BUS 316217   /*AC1-145 GEN    0.6
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AEP_P7-1_#10868___SRT-SL'
 OPEN BRANCH FROM BUS 242533 TO BUS 242693 CKT 1   /*05ABINGD     138.0 - 05KEYWSS     138.0
 OPEN BRANCH FROM BUS 242566 TO BUS 290135 CKT 1   /*05BROADF     138.0 - 05SALTVL_BP  138.0
 OPEN BRANCH FROM BUS 242605 TO BUS 242665 CKT 1   /*05CLNCHR     138.0 - 05HANSON     138.0
 OPEN BRANCH FROM BUS 242665 TO BUS 242714 CKT 1   /*05HANSON     138.0 - 05MEADWV     138.0
 OPEN BRANCH FROM BUS 242692 TO BUS 242693 CKT 1   /*05KEYWOD     138.0 - 05KEYWSS     138.0
 OPEN BRANCH FROM BUS 242693 TO BUS 290135 CKT 1   /*05KEYWSS     138.0 - 05SALTVL_BP  138.0
 OPEN BRANCH FROM BUS 242714 TO BUS 242789 CKT 1   /*05MEADWV     138.0 - 05SALTV2     138.0
 OPEN BRANCH FROM BUS 242714 TO BUS 290185 CKT 2   /*05MEADWV     138.0 - 05MEADWVW2EQ 999.0
 OPEN BRANCH FROM BUS 242875 TO BUS 244241 CKT 1   /*05MEADWVW     69.0 - 05HILLMAN     69.0
 OPEN BRANCH FROM BUS 242875 TO BUS 244268 CKT 1   /*05MEADWVW     69.0 - 05MEDALLIN    69.0
 OPEN BRANCH FROM BUS 242875 TO BUS 290185 CKT 2   /*05MEADWVW     69.0 - 05MEADWVW2EQ 999.0
 OPEN BRANCH FROM BUS 290184 TO BUS 290185 CKT 2   /*05MEADWVW T2  13.1 - 05MEADWVW2EQ 999.0
END
CONTINGENCY 'AEP_P4_#1375_05BROADF 765_P2_SRT-A'
 OPEN BRANCH FROM BUS 242511 TO BUS 290422 CKT 6   /*05BROADF     765.0 - 05BROADFD6EQ   1.0
 OPEN BRANCH FROM BUS 242518 TO BUS 290422 CKT 6   /*05BROADF     500.0 - 05BROADFD6EQ   1.0
 OPEN BRANCH FROM BUS 242518 TO BUS 360106 CKT 1   /*05BROADF     500.0 - 8SULLIVAN TN 500.0
 OPEN BRANCH FROM BUS 290422 TO BUS 290423 CKT 6   /*05BROADFD6EQ   1.0 - 05BROADFD T6  13.8
END
CONTINGENCY 'AEP_P4_#11112_05J.FERR 765_A1_SRT-A'
 OPEN BRANCH FROM BUS 242511 TO BUS 290615 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290022 CKT 1    /*05J.FERR     765.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290615 CKT 1    /*05J.FERR     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242520 TO BUS 290022 CKT 1    /*05J.FERR     500.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1    /*05J.FERR     500.0 - 8ANTIOCH     500.0
 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB   /*05BROADF     138.0 - 05BROADX     138.0
 OPEN BRANCH FROM BUS 290022 TO BUS 290023 CKT 1    /*05J.FERR 1EQ   1.0 - 05J.FERR T1   13.8
END
CONTINGENCY 'AEP_P4_#14149_05BROADF 765_Q2_SRT-A'
 OPEN BRANCH FROM BUS 242511 TO BUS 290615 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290615 CKT 1    /*05J.FERR     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB   /*05BROADF     138.0 - 05BROADX     138.0
END
CONTINGENCY 'AEP_P4_#2916_05J.FERR 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242509 TO BUS 242545 CKT 1    /*05AXTON      765.0 - 05AXTONX     138.0
 OPEN BRANCH FROM BUS 242509 TO BUS 290609 CKT Z1   /*05AXTON      765.0 - 05AXTON_RJ   765.0
 OPEN BRANCH FROM BUS 242511 TO BUS 290615 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290609 CKT 1    /*05J.FERR     765.0 - 05AXTON_RJ   765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290615 CKT 1    /*05J.FERR     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242544 TO BUS 242545 CKT SR   /*05AXTON      138.0 - 05AXTONX     138.0
 OPEN BRANCH FROM BUS 242544 TO BUS 242545 CKT ZB   /*05AXTON      138.0 - 05AXTONX     138.0
 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB   /*05BROADF     138.0 - 05BROADX     138.0
END
CONTINGENCY 'AEP_P1-2_#2915_4_SRT-A'
 OPEN BRANCH FROM BUS 242511 TO BUS 290615 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290615 CKT 1    /*05J.FERR     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB   /*05BROADF     138.0 - 05BROADX     138.0
END
CONTINGENCY 'AEP_P4_#3149_05HANG R 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242924 TO BUS 242927 CKT 1   /*05HANG R     765.0 - 05MARQUI     765.0
 OPEN BRANCH FROM BUS 242927 TO BUS 242938 CKT 1   /*05MARQUI     765.0 - 05MARQUI     345.0
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290598 CKT Z1   /*05GRNTWN     765.0 - 05GREENTW_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290598 TO BUS 290599 CKT 1    /*05GREENTW_RJ 765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#1558_05BAKER 765_Q_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242513 CKT 1   /*05BAKER      765.0 - 05CULLOD     765.0
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P4_#309_05HANG R 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P4_#1560_05BAKER 765_Q2_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242523 CKT 1   /*05BAKER      765.0 - 05BAKER      345.0
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P2-2_#6156_05MARQUI 765_2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 242927 CKT 1   /*05HANG R     765.0 - 05MARQUI     765.0
 OPEN BRANCH FROM BUS 242927 TO BUS 242938 CKT 1   /*05MARQUI     765.0 - 05MARQUI     345.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P2-2_#6763_05BIERSR 345_2_SRT-A'
 OPEN BRANCH FROM BUS 243454 TO BUS 246888 CKT 1   /*05BIXBY      345.0 - 05BIERSR     345.0
END
CONTINGENCY 'AEP_P2-2_#308_05CULLOD 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242513 CKT 1   /*05BAKER      765.0 - 05CULLOD     765.0
END
CONTINGENCY 'AEP_P7-1_#11019___SRT-A-2'
 OPEN BRANCH FROM BUS 243225 TO BUS 243232 CKT 1   /*05KEYSTN     345.0 - 05SORENS     345.0
 OPEN BRANCH FROM BUS 944530 TO BUS 243232 CKT 2   /*AF1-118 TP   345.0 - 05SORENS     345.0
END
CONTINGENCY '34569 34598 34524_SRT-A'
 OPEN BRANCH FROM BUS 249566 TO BUS 249578 CKT 1   /*08FOSTER     345.0 - 08HILCRT     345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253006 CKT 1   /*08FOSTER     345.0 - 09BATH       345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253079 CKT 1   /*08FOSTER     345.0 - 09SUGRCK     345.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT14_SRT-SL'
 OPEN BRANCH FROM BUS 235109 TO BUS 235081 CKT 1                /*AB1-106 POI  500.0 - T-174  1     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT5_SRT-SL'
 OPEN BRANCH FROM BUS 235851 TO BUS 235850 CKT 1                /*01NTHLNV     500.0 - 01LONGVIEW   500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235111 TO BUS 235851 CKT 1 /*01 502 J     500.0 - 01NTHLNV     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235851 TO BUS 235106 CKT 1 /*01NTHLNV     500.0 - 01FMARTN     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235111 TO BUS 235851 CKT 1 /*01 502 J     500.0 - 01NTHLNV     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235851 TO BUS 235106 CKT 1 /*01NTHLNV     500.0 - 01FMARTN     500.0
END
CONTINGENCY 'AEP_P2-2_#316_05AMOS 765_2_SRT-A'
 OPEN BRANCH FROM BUS 242508 TO BUS 290927 CKT 5    /*05AMOS       765.0 - 05AMOS 5EQ     1.0
 OPEN BRANCH FROM BUS 242522 TO BUS 247504 CKT Z5   /*05AMOS       345.0 - 05AMOS_5_XFL 345.0
 OPEN BRANCH FROM BUS 247504 TO BUS 290927 CKT 5    /*05AMOS_5_XFL 345.0 - 05AMOS 5EQ     1.0
 OPEN BRANCH FROM BUS 290927 TO BUS 290928 CKT 5    /*05AMOS 5EQ     1.0 - 05AMOS T5     34.5
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1014_SRT-A'
 OPEN BRANCH FROM BUS 342742 TO BUS 342745 CKT 1   /*5JABEZ       161.0 - 5JABEZ T     161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342751 CKT 1   /*5JABEZ T     161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342799 CKT 1   /*5JABEZ T     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342748 TO BUS 342751 CKT 1   /*5JAMESTOWN   161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342751 TO BUS 342796 CKT 1   /*5JAMESTOWN T 161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342793 TO BUS 342796 CKT 1   /*5RUSSEL CO   161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342796 TO BUS 360448 CKT 1   /*5RUSSEL CO J 161.0 - 5WOLF CRK HP 161.0
 OPEN BUS 342715                                   /*5COOPER1     161.0
 OPEN BUS 342900                                   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1024_SRT-A'
 OPEN BRANCH FROM BUS 342115 TO BUS 342787 CKT 1   /*2PULASK CO    69.0 - 5PULASK CO   161.0
 OPEN BRANCH FROM BUS 342760 TO BUS 342790 CKT 1   /*5LIBERTY J   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342787 TO BUS 342790 CKT 1   /*5PULASK CO   161.0 - 5PULASK CO J 161.0
 OPEN BUS 342715                                   /*5COOPER1     161.0
 OPEN BUS 342900                                   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1008_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
 OPEN BUS 342900   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-2_COOPER 1 161_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
END
CONTINGENCY 'EKPC_P4-6_COOP S42-1039_SRT-A_SENS'
 OPEN BUS 342715   /*5COOPER1     161.0
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342900   /*1COOPER1 G    13.8
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-3_MAR W38-1014_SRT-A'
 OPEN BRANCH FROM BUS 341269 TO BUS 342703 CKT 1   /*2CASEY CO     69.0 - 5CASEY CO    161.0
 OPEN BRANCH FROM BUS 342703 TO BUS 342760 CKT 1   /*5CASEY CO    161.0 - 5LIBERTY J   161.0
 OPEN BRANCH FROM BUS 342703 TO BUS 342769 CKT 1   /*5CASEY CO    161.0 - 5MARION CO   161.0
 OPEN BRANCH FROM BUS 342770 TO BUS 342769 CKT 1   /*4MARION CO   138.0 - 5MARION CO   161.0
END
CONTINGENCY 'EKPC_P2-3_SSHAD S11-1014_SRT-A'
 OPEN BRANCH FROM BUS 964900 TO BUS 342814 CKT 1   /*AG1-354 TP   161.0 - 5SUMM SHADE  161.0
 OPEN BUS 361788                                   /*5SUM SHAD TP 161.0
END
CONTINGENCY 'EKPC_P2-2_KU HODG 69_SRT-A'
 OPEN BUS 341632   /*2HODGENVILLE  69.0
END
CONTINGENCY 'EKPC_P2-2_BARDIT-EBARD69_SRT-A'
 OPEN BUS 341407   /*2E BARDSTOWN  69.0
END
CONTINGENCY 'EKPC_P2-3_SSHAD S11-1004_SRT-A-1'
 OPEN BRANCH FROM BUS 341059 TO BUS 342694 CKT 1   /*2BARREN CO    69.0 - 5BARREN CO   161.0
 OPEN BRANCH FROM BUS 342694 TO BUS 342814 CKT 1   /*5BARREN CO   161.0 - 5SUMM SHADE  161.0
 OPEN BRANCH FROM BUS 361788 TO BUS 342814 CKT 1   /*5SUM SHAD TP 161.0 - 5SUMM SHADE  161.0
 OPEN BRANCH FROM BUS 964900 TO BUS 342814 CKT 1   /*AG1-354 TP   161.0 - 5SUMM SHADE  161.0
END
CONTINGENCY 'EKPC_P2-3_TYNER E13-1014_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BUS 342820                                   /*5TYNER       161.0
END
CONTINGENCY 'EKPC_P1-2_LAUR-PIT-TY161_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS'
 OPEN BRANCH FROM BUS 324130 TO BUS 972272 CKT 1   /*5ALCALDE     161.0 - AH1-721 TP   161.0
 OPEN BRANCH FROM BUS 324130 TO BUS 972272 CKT 2   /*5ALCALDE     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EXT_B-345-100_SRT-S'
 OPEN BRANCH FROM BUS 324100 TO BUS 324102 CKT 1   /*7ALCALDE     345.0 - 7BROWN NORTH 345.0
 OPEN BRANCH FROM BUS 324100 TO BUS 324112 CKT 1   /*7ALCALDE     345.0 - 7PINEVILLE   345.0
 OPEN BRANCH FROM BUS 324100 TO BUS 324130 CKT 1   /*7ALCALDE     345.0 - 5ALCALDE     161.0
END
CONTINGENCY 'EXT_324100 7ALCALDE 345 324112 7PINEVILLE 345 1_SRT-S'
 OPEN BRANCH FROM BUS 324100 TO BUS 324112 CKT 1   /*7ALCALDE     345.0 - 7PINEVILLE   345.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 1_SRT-A'
 OPEN BRANCH FROM BUS 342115 TO BUS 342787 CKT 1   /*2PULASK CO    69.0 - 5PULASK CO   161.0
 OPEN BRANCH FROM BUS 342715 TO BUS 342790 CKT 1   /*5COOPER1     161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342715 TO BUS 342799 CKT 1   /*5COOPER1     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342742 TO BUS 342745 CKT 1   /*5JABEZ       161.0 - 5JABEZ T     161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342751 CKT 1   /*5JABEZ T     161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342799 CKT 1   /*5JABEZ T     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342748 TO BUS 342751 CKT 1   /*5JAMESTOWN   161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342751 TO BUS 342796 CKT 1   /*5JAMESTOWN T 161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342760 TO BUS 342790 CKT 1   /*5LIBERTY J   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342787 TO BUS 342790 CKT 1   /*5PULASK CO   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342793 TO BUS 342796 CKT 1   /*5RUSSEL CO   161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342796 TO BUS 360448 CKT 1   /*5RUSSEL CO J 161.0 - 5WOLF CRK HP 161.0
END
CONTINGENCY 'EKPC_P2-2_PULASKI 161_SRT-A'
 OPEN BUS 342787   /*5PULASK CO   161.0
 OPEN BUS 342790   /*5PULASK CO J 161.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-210G_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-2_COOPER 2 161_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
END
CONTINGENCY 'EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A'
 DISCONNECT BRANCH FROM BUS 971484 TO BUS 342397 CKT 1   /*AH1-239 TP    69.0 - 2UPCHURCH T   69.0
END
CONTINGENCY 'EKPC_P1-2_COOP-LAUREL161_SRT-A-1'
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 1   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
242605 to 242700 ckt 1
290610 to 242512 ckt Z1
290614 to 242515 ckt 1
246766 to 242788 ckt 1
242514 to 290610 ckt 1
242700 to 246766 ckt 1
242788 to 971312 ckt 1
248005 to 242528 ckt 1
324531 to 342287 ckt 1
341563 to 342325 ckt 1
324736 to 341935 ckt 1
342451 to 342452 ckt 1
342718 to 324141 ckt 1
342757 to 342754 ckt 1
966020 to 342532 ckt 1
971312 to 242827 ckt 1
972272 to 342718 ckt 2

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
BreakerAC107.18 %2320.0B2486.65
42.66
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
SingleAC104.78 %2320.0B2430.97
42.66
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.13 %3393.4B4008.49
75.59
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC115.66 %3610.0B4175.28
75.96
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC115.4 %3610.0B4165.98
75.7
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC115.26 %3610.0B4160.96
75.59
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC114.94 %3610.0B4149.41
75.64
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC119.32 %5523.0B6590.12
85.57
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
BreakerAC117.27 %5523.0B6477.04
96.73
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC116.4 %5523.0B6428.58
96.73
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
BreakerAC112.72 %5523.0B6225.55
97.71
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC111.96 %5523.0B6183.32
81.4
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC109.18 %4558.0A4976.63
77.28
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC108.41 %5523.0B5987.66
94.18
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC107.46 %5523.0B5935.05
84.42
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.76 %5523.0B5896.19
94.18
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC105.86 %5523.0B5846.6
85.24
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10856___SRT-A
TowerAC101.88 %5523.0B5626.94
86.12
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC153.59 %1540.0B2365.35
37.22
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC141.94 %1540.0B2185.8
36.74
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#309_15_SRT-A
SingleAC133.27 %1540.0B2052.4
35.86
GD2EKPC
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC156.95 %63.0B98.88
119.87
IPDEKPC
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC155.54 %63.0B97.99
119.87
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC195.41 %63.0B123.11
108.32
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC188.75 %63.0B118.91
115.39
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC188.75 %63.0B118.91
115.39
IPDEKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC175.64 %63.0B110.66
108.32
IPDEKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC171.57 %63.0B108.09
115.39
IPDEKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC171.57 %63.0B108.09
115.39
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC195.24 %63.0B123.0
108.32
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC188.58 %63.0B118.8
115.39
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC188.56 %63.0B118.79
115.39
IPDEKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC175.47 %63.0B110.55
108.32
IPDEKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC171.39 %63.0B107.97
115.39
IPDEKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC171.39 %63.0B107.97
115.39
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC217.1 %76.0B165.0
86.37
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC199.45 %76.0B151.58
86.37
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC159.85 %76.0B121.49
65.58
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC159.47 %76.0B121.2
65.58
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC159.24 %76.0B121.02
65.35
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC153.38 %76.0B116.57
65.59
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC153.38 %76.0B116.57
65.59
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC153.14 %76.0B116.39
65.35
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC217.1 %76.0B165.0
86.37
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC199.45 %76.0B151.58
86.37
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC159.85 %76.0B121.49
65.58
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC159.47 %76.0B121.2
65.58
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC159.24 %76.0B121.02
65.35
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC153.38 %76.0B116.57
65.59
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC153.38 %76.0B116.57
65.59
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC153.14 %76.0B116.39
65.35
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC287.41 %46.0B132.21
108.32
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC277.36 %46.0B127.58
115.39
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC277.36 %46.0B127.58
115.39
IPDEKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC260.36 %46.0B119.76
108.32
IPDEKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC253.83 %46.0B116.76
115.39
IPDEKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC253.83 %46.0B116.76
115.39
GD2EKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC139.3 %66.0B91.94
88.41
GD2EKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC139.29 %66.0B91.93
88.41
IPDEKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC138.39 %66.0B91.34
88.41
IPDEKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC138.39 %66.0B91.34
88.41
GD2EKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC135.02 %66.0B89.11
91.64
IPDEKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC133.95 %66.0B88.41
91.64
GD2EKPC
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC128.12 %66.0B84.56
79.02
GD2EKPC
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC128.1 %66.0B84.55
79.02
IPDEKPC
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC127.54 %66.0B84.18
79.02
IPDEKPC
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC127.54 %66.0B84.18
79.02
GD2EKPC
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC126.79 %66.0B83.68
81.04
IPDEKPC
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC126.15 %66.0B83.26
81.04
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC132.95 %105.0B139.6
101.64
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC124.56 %105.0B130.79
101.64
GD2EKPC
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC110.23 %39.0B42.99
12.14
GD2EKPC
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line
EKPC_P2-2_SUMMSHADE 161 #2_SRT-A
BusAC107.29 %39.0B41.84
9.25
GD2EKPC
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line
EKPC_P2-3_SSHAD S11-1039_SRT-A
BreakerAC107.26 %39.0B41.83
9.25
GD2EKPC
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line
EKPC_P4-2_SSHAD S11-1004_SRT-A
BreakerAC107.26 %39.0B41.83
9.25
GD2EKPC
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC175.99 %63.0B110.88
119.87
IPDEKPC
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC174.58 %63.0B109.99
119.87
IPDEKPC
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC100.17 %63.0B63.11
71.39
IPDEKPC
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC100.01 %63.0B63.01
71.55
IPDEKPC
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC100.01 %63.0B63.01
71.55
GD2EKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC150.15 %105.0B157.66
138.07
IPDEKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC149.25 %105.0B156.71
138.07
GD2EKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC105.6 %105.0B110.88
83.81
GD2EKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC105.38 %105.0B110.65
83.81
GD2EKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC105.38 %105.0B110.65
83.81
IPDEKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC104.78 %105.0B110.02
83.81
IPDEKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC104.5 %105.0B109.72
83.81
IPDEKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC104.5 %105.0B109.72
83.81
GD2EKPC
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC191.94 %63.0B120.92
119.87
IPDEKPC
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC190.53 %63.0B120.04
119.87
GD2EKPC
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC126.73 %63.0B79.84
67.43
GD2EKPC
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC126.73 %63.0B79.84
67.43
GD2EKPC
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC126.61 %63.0B79.76
67.28
IPDEKPC
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC113.46 %63.0B71.48
71.39
IPDEKPC
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC113.23 %63.0B71.33
71.55
IPDEKPC
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC113.23 %63.0B71.33
71.55
GD2EKPC/LGEE
2LIBER CH T-2FARLEY KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC124.36 %76.0B94.51
119.87
IPDEKPC/LGEE
2LIBER CH T-2FARLEY KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC123.19 %76.0B93.62
119.87
GD2EKPC
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC162.76 %63.0B102.54
119.87
IPDEKPC
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC161.35 %63.0B101.65
119.87
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC304.78 %105.0B320.02
172.4
IPDEKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC239.94 %105.0B251.94
172.4
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC224.7 %105.0B235.93
129.5
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC224.32 %105.0B235.53
128.92
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC209.2 %105.0B219.66
129.5
IPDEKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC171.79 %105.0B180.38
129.5
IPDEKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC171.79 %105.0B180.38
129.5
IPDEKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC171.38 %105.0B179.95
128.92
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC206.75 %152.0B314.25
176.31
IPDEKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC168.71 %152.0B256.43
176.31
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC148.66 %152.0B225.97
133.55
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC148.4 %152.0B225.56
132.98
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC140.88 %152.0B214.14
133.55
IPDEKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC121.66 %152.0B184.92
133.55
IPDEKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC121.66 %152.0B184.92
133.55
IPDEKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC121.37 %152.0B184.48
132.98
GD2EKPC/LGEE
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC120.73 %50.0B60.36
17.01
GD2EKPC/LGEE
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC107.77 %50.0B53.89
15.95
GD2EKPC/LGEE
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
EKPC_P2-3_SSHAD S11-1044_SRT-A
BreakerAC106.27 %50.0B53.14
11.79
IPDEKPC
2W LONDON-2W LONDON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC119.43 %46.0B54.94
49.38
GD2EKPC
2W LONDON-2W LONDON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerAC115.94 %46.0B53.33
46.54
GD2EKPC
2WALNUT GROV-2MARETBURG T 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC105.22 %63.0B66.29
32.68
GD2DEO&K/EKPC
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line
34541 34553_SRT-A
TowerAC103.34 %284.0B293.48
28.7
GD2EKPC/LGEE
4MARION CO-4LEBANON 138.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC106.8 %220.0B234.95
92.29
GD2EKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC203.25 %152.0B308.94
169.18
IPDEKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC196.07 %152.0B298.03
169.18
GD2EKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC156.92 %152.0B238.52
128.98
GD2EKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC156.92 %152.0B238.52
128.98
GD2EKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC156.35 %152.0B237.66
127.91
IPDEKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC152.62 %152.0B231.98
128.98
IPDEKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC152.62 %152.0B231.98
128.98
IPDEKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC152.04 %152.0B231.1
127.9
GD2EKPC
5COOPER1-5PULASK CO J 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC117.56 %298.0B350.32
198.94
IPDEKPC
5COOPER1-5PULASK CO J 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC109.24 %298.0B325.52
198.94
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC173.44 %501.0B868.91
672.84
IPDEKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC168.91 %501.0B846.23
672.84
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC130.16 %501.0B652.09
524.74
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC130.15 %501.0B652.08
524.74
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC129.73 %501.0B649.97
522.06
IPDEKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC126.83 %501.0B635.42
524.74
IPDEKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC126.83 %501.0B635.42
524.74
IPDEKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC126.41 %501.0B633.29
522.06
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1014_SRT-A
BreakerAC258.0 %277.0B714.66
557.26
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1024_SRT-A
BreakerAC256.54 %277.0B710.6
558.31
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1008_SRT-A
BreakerAC256.41 %277.0B710.25
559.13
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC256.41 %277.0B710.25
559.13
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC254.83 %277.0B705.89
560.97
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC250.49 %277.0B693.86
354.92
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1024_SRT-A
BreakerAC250.48 %277.0B693.83
354.92
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC250.47 %277.0B693.79
354.92
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC250.35 %277.0B693.48
355.54
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC250.29 %277.0B693.3
355.23
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1014_SRT-A
BreakerAC249.4 %277.0B690.83
557.26
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1024_SRT-A
BreakerAC248.13 %277.0B687.31
558.31
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1008_SRT-A
BreakerAC247.82 %277.0B686.46
559.13
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC247.82 %277.0B686.46
559.13
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC247.66 %277.0B686.01
560.97
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC240.63 %277.0B666.55
355.54
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Base Case
SingleAC238.58 %219.0A522.49
307.93
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOP-LAURD 161_SRT-A
BusAC235.73 %277.0B652.99
355.69
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 1_SRT-A
TowerAC220.33 %277.0B610.32
421.34
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_PULASKI 161_SRT-A
BusAC216.21 %277.0B598.91
351.19
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC212.83 %277.0B589.54
354.92
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC212.83 %277.0B589.54
354.92
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC212.56 %277.0B588.79
355.22
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1014_SRT-A
BreakerAC212.56 %277.0B588.79
355.22
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC212.55 %277.0B588.75
355.54
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC212.55 %277.0B588.75
355.54
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 1_SRT-A
TowerAC210.18 %277.0B582.21
421.34
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Base Case
SingleAC209.11 %219.0A457.95
307.93
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOP-LAURD 161_SRT-A
BusAC198.41 %277.0B549.61
355.7
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_PULASKI 161_SRT-A
BusAC192.36 %277.0B532.84
351.2
GD2EKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC270.03 %109.0B294.34
282.81
GD2EKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC270.02 %109.0B294.33
282.81
GD2EKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC268.6 %109.0B292.78
281.0
IPDEKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC268.14 %109.0B292.27
282.81
IPDEKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC268.14 %109.0B292.27
282.81
IPDEKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC266.54 %109.0B290.53
281.0
GD2EKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC117.84 %109.0B128.44
72.46
IPDEKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC116.44 %109.0B126.92
72.46
GD2EKPC/LGEE
5GREEN HAL T-5DELVINTA 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC100.07 %251.0B251.17
319.05
GD2EKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC231.83 %152.0B352.38
307.31
IPDEKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC230.52 %152.0B350.39
307.31
GD2EKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC147.36 %152.0B223.99
188.26
GD2EKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC147.29 %152.0B223.88
188.02
GD2EKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC147.29 %152.0B223.88
188.02
IPDEKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC146.55 %152.0B222.75
188.26
IPDEKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC146.49 %152.0B222.67
188.02
IPDEKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC146.49 %152.0B222.67
188.02
GD2EKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_TYNER E13-1014_SRT-A
BreakerAC110.08 %152.0B167.33
45.84
GD2EKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P1-2_LAUR-PIT-TY161_SRT-A
SingleAC108.0 %152.0B164.15
50.15
IPDEKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_TYNER E13-1014_SRT-A
BreakerAC107.12 %152.0B162.83
48.64
IPDEKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P1-2_LAUR-PIT-TY161_SRT-A
SingleAC104.58 %152.0B158.96
50.14
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC238.63 %200.0B477.27
451.34
IPDEKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC236.15 %200.0B472.3
451.34
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC174.22 %200.0B348.43
289.39
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC173.62 %200.0B347.25
287.82
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC173.61 %200.0B347.23
287.82
IPDEKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC166.14 %200.0B332.29
289.39
IPDEKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC165.4 %200.0B330.79
287.82
IPDEKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC165.4 %200.0B330.79
287.82
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC414.2 %200.0B828.4
758.65
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC412.16 %200.0B824.32
758.65
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC301.0 %200.0B602.0
477.65
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC290.96 %200.0B581.91
477.65
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC289.82 %200.0B579.65
475.84
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC289.82 %200.0B579.65
475.84
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC175.49 %200.0B350.97
143.5
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC157.12 %200.0B314.25
143.5
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC156.49 %200.0B312.98
141.81
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC156.49 %200.0B312.98
141.81
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC129.84 %200.0B259.67
127.08
GD2EKPC
5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC106.57 %220.0B234.46
92.29
GD2EKPC/LGEE
5PITTSBURG-2PITTSBRG KU 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC117.41 %129.0B151.45
104.45
IPDEKPC/LGEE
5PITTSBURG-2PITTSBRG KU 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC116.73 %129.0B150.58
104.45
GD2EKPC
5PITTSBURG-5TYNER 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC131.41 %250.0B328.51
346.89
IPDEKPC
5PITTSBURG-5TYNER 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC128.63 %250.0B321.57
346.89
GD2EKPC
5TYNER-5GREEN HAL T 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC101.55 %250.0B253.88
319.05
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1445_ZIMMER_SRT-A
BreakerAC107.55 %1532.0B1647.65
88.65
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1449_ZIMMER_SRT-A
BreakerAC107.43 %1532.0B1645.79
88.63
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
34569 34598 34524_SRT-A
TowerAC106.98 %1532.0B1638.99
75.15
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1373_PORTUNION_SRT-A
BreakerAC106.14 %1532.0B1626.02
77.72
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1493_RED BANK_SRT-A
BreakerAC105.1 %1532.0B1610.06
77.24
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1487_RED BANK_SRT-A
BreakerAC105.05 %1532.0B1609.33
77.24
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A
TowerAC104.96 %1532.0B1608.02
77.26
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A
BusAC104.95 %1532.0B1607.79
77.25
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Base Case
SingleAC104.93 %1240.0A1301.17
73.77
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
EKPC_P2-2_MELD-SPUR 345_SRT-A
BusAC103.1 %1532.0B1579.46
88.87
GD2AEP/DVP
AE1-108 POI-4BREMO 138.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC178.27 %156.98B279.84
7.87
GD2EKPC
AE2-254 POI-2GARRARD CO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC118.85 %63.0B74.87
27.82
GD2EKPC
AE2-254 POI-2GARRARD CO 69.0 kV Ckt 1 line
EKPC_P2-3_MAR W38-1004_SRT-A
BreakerAC104.2 %63.0B65.65
20.36
GD2EKPC
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
EKPC_P2-2_TVA WAYNE 161_SRT-A
BusAC100.32 %54.0B54.17
10.3
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-DEN161_SRT-A-1
SingleAC188.88 %298.0B562.87
625.96
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-DEN161_SRT-A-1
SingleAC185.85 %298.0B553.84
625.96
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1014_SRT-A
BreakerAC136.15 %298.0B405.72
373.16
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC136.15 %298.0B405.71
373.15
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1014_SRT-A
BreakerAC136.14 %298.0B405.7
373.16
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC136.14 %298.0B405.7
373.16
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC136.07 %298.0B405.5
373.17
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC135.49 %298.0B403.77
373.15
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC132.76 %298.0B395.63
373.15
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC132.76 %298.0B395.63
373.15
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1014_SRT-A
BreakerAC132.76 %298.0B395.63
373.16
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC132.76 %298.0B395.61
373.16
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1014_SRT-A
BreakerAC132.76 %298.0B395.61
373.16
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC132.69 %298.0B395.41
373.17
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC110.99 %298.0B330.75
349.92
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC110.55 %298.0B329.44
349.92
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Base Case
SingleAC109.05 %267.0A291.18
326.77
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Base Case
SingleAC108.31 %267.0A289.19
326.77
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
SingleAC263.5 %210.0B553.35
625.42
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC205.12 %210.0B430.76
523.01
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC201.74 %210.0B423.66
523.01
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC177.18 %210.0B372.09
345.37
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-3_LAURL S50-1014_SRT-A
BreakerAC177.18 %210.0B372.08
345.38
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P4-5_LAURL S50-1014_SRT-A
BreakerAC177.18 %210.0B372.07
345.38
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC177.18 %210.0B372.07
345.38
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC177.09 %210.0B371.88
345.38
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC176.82 %210.0B371.32
345.37
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC174.36 %210.0B366.15
345.37
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC174.36 %210.0B366.15
345.37
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-3_LAURL S50-1014_SRT-A
BreakerAC174.35 %210.0B366.14
345.38
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P4-5_LAURL S50-1014_SRT-A
BreakerAC174.35 %210.0B366.13
345.38
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC174.35 %210.0B366.13
345.38
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC174.25 %210.0B365.94
345.38
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Base Case
SingleAC144.88 %186.0A269.48
302.44
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Base Case
SingleAC143.89 %186.0A267.63
302.44
GD2EKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC143.93 %210.0B302.26
282.81
GD2EKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC143.93 %210.0B302.25
282.81
GD2EKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC143.53 %210.0B301.42
281.0
IPDEKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC142.74 %210.0B299.75
282.81
IPDEKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC142.74 %210.0B299.75
282.81
IPDEKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC142.38 %210.0B299.0
281.0
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC254.75 %298.0B759.16
758.95
IPDEKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC254.75 %298.0B759.16
758.95
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC176.07 %298.0B524.69
477.95
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC175.36 %298.0B522.59
476.14
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC175.36 %298.0B522.58
476.14
IPDEKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC170.17 %298.0B507.11
477.95
IPDEKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC169.45 %298.0B504.96
476.14
IPDEKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC169.45 %298.0B504.96
476.14

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.18 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2486.65
MW Contribution:
42.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24735105WLF2G1
Adder
4.907
24734705WLF1G3
Adder
4.896
24734805WLF1G4
Adder
4.896
24734905WLF1G5
Adder
4.896
966391AG1-508 GEN
Solar/Wind Harmer
2.783
971981AH1-535 GEN
Solar/Wind Harmer
7.894
971313AH1-133 GEN
Solar/Wind Harmer
4.584
970281AG2-184 GEN
Solar/Wind Harmer
14.612
962211AG1-066 GEN
Solar/Wind Harmer
1.641
270399AC1-101 GEN
Solar/Wind Harmer
2.774
270400AC1-102 GEN
Solar/Wind Harmer
2.774
957241AF2-018 GEN
Solar/Wind Harmer
2.859
270053AF1-130 C
Solar/Wind Harmer
11.424
3429211JKCT 2G
Adder
6.347
339216AC1-074 GEN
Solar/Wind Harmer
0.857
972163AH1-664 GEN
Solar/Wind Harmer
4.973
972165AH1-665 GEN
Solar/Wind Harmer
3.979
24735205WLF2G2
Adder
4.907
24728305BUCHG2
Adder
3.63
971687AH1-348 GEN
Solar/Wind Harmer
0.746
971403AH1-188 GEN
Solar/Wind Harmer
9.183
944971AF1-162 GEN
Solar/Wind Harmer
4.503
24723205RIVRG3
Adder
11.612
270336AE1-100 GEN
Solar/Wind Harmer
1.01
972203AH1-686 GEN
Adder
1.34
964901AG1-354 GEN
Solar/Wind Harmer
8.649
339241AF1-083 GEN
Solar/Wind Harmer
0.951
24686505CER G6
Adder
4.748
339211AE2-254 GEN
Solar/Wind Harmer
0.852
970653AG2-424 GEN
Solar/Wind Harmer
2.669
3429241JKCT 3G
Adder
6.43
3429421JKCT 10G
Adder
4.482
970563AG2-360 GEN
50/50
26.903
943031AE2-326 GEN
Solar/Wind Harmer
3.912
962751AG1-124 GEN
Solar/Wind Harmer
9.059
960911AF2-382 GEN
Solar/Wind Harmer
5.846
971461AH1-227 GEN
Solar/Wind Harmer
3.852
972103AH1-617 GEN
Solar/Wind Harmer
13.916
270214AC2-123 GEN
Solar/Wind Harmer
2.486
971277AH1-098 GEN
Solar/Wind Harmer
3.312
24728205BUCHG1
Adder
3.63
971225AH1-072 GEN
Solar/Wind Harmer
1.502
971227AH1-073 GEN
Solar/Wind Harmer
1.502
24723005RIVRG1
Adder
11.612
24723105RIVRG2
Adder
11.612
966021AG1-471 GEN
Solar/Wind Harmer
3.282
971485AH1-239 GEN
Solar/Wind Harmer
4.84
339231AF1-038_GEN
Solar/Wind Harmer
1.081
964781AG1-341 GEN
Solar/Wind Harmer
6.17
339236AF1-050_GEN
Solar/Wind Harmer
1.045
942891AE2-308 GEN
Solar/Wind Harmer
5.443
964571AG1-320 GEN
Solar/Wind Harmer
4.43
971125AH1-004 GEN
Solar/Wind Harmer
2.108
970107AG2-081 GEN
Solar/Wind Harmer
1.581
972043AH1-570 GEN
Solar/Wind Harmer
1.293
972045AH1-571 GEN
Solar/Wind Harmer
1.034
276916AD2-100_GEN
Solar/Wind Harmer
10.169
276911AD2-131_GEN
Solar/Wind Harmer
2.055
276615X2-022 GEN
Solar/Wind Harmer
0.938
276838X2-022 GEN2
Solar/Wind Harmer
0.111
945391AF1-204 GEN
Solar/Wind Harmer
6.651
274880W4-005 GEN4
Solar/Wind Harmer
1.44
276174W4-005 GEN2
Solar/Wind Harmer
1.44
960611AF2-352 GEN
Solar/Wind Harmer
1.092
276158O29GEN2
Solar/Wind Harmer
2.347
276157O29GEN1
Solar/Wind Harmer
1.785
276645AC1-214 GEN1
Solar/Wind Harmer
0.626
942111AE2-223 GEN
Solar/Wind Harmer
3.832
274764LEE CO EC;5U
Adder
4.358
274765LEE CO EC;6U
Adder
4.358
274762LEE CO EC;3U
Adder
4.348
274763LEE CO EC;4U
Adder
4.307
970241AG2-163 GEN
Solar/Wind Harmer
11.68
938861AE1-114 GEN
Solar/Wind Harmer
3.826
972235AH1-702 GEN1
Adder
1.172
972236AH1-702 GEN2
Adder
1.019
971341AH1-150 GEN
Solar/Wind Harmer
9.281
971343AH1-151 GEN
Solar/Wind Harmer
9.281
252509AD1-136 GEN
Solar/Wind Harmer
0.119
274683WAUKEGAN ;8U
Adder
9.688
274683WAUKEGAN ;8U
Adder
8.167
25194408D.CRK1
Adder
3.476
25194508D.CRK3
Adder
0.65
274696ROCKY RD ;4P
Adder
5.236
274695ROCKY RD ;2P
Adder
5.115
274693ROCKY RD ;1P
Adder
5.064
274697ROCKY RD ;3P
Adder
1.389
24728805RICHG1
Adder
1.729
24728905RICHG2
Adder
1.729
274674JOLIET 9 ;6U
Adder
7.01
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
237061AD1-155 GEN
Solar/Wind Helper
0.84
972273AH1-721 GEN
Adder
50.356
339255AE2-071 GEN
Solar/Wind Harmer
0.685
339250AF1-203 GEN
Solar/Wind Harmer
0.353
339206AE1-143 GEN
Solar/Wind Harmer
1.218
24686405CER G5
Adder
4.71
970093AG2-073 GEN
Solar/Wind Harmer
2.932
970653AG2-424 GEN
Solar/Wind Harmer
0.386
270030AE2-140 GEN
Solar/Wind Harmer
10.987
970455AG2-298 GEN
Solar/Wind Harmer
1.905
3429391JKCT 9G
Adder
4.482
339243AC2-075 GEN1
Solar/Wind Harmer
0.232
972167AH1-666 GEN
Solar/Wind Harmer
3.959
958171AF2-111 GEN
Solar/Wind Harmer
12.218
942481AE2-261 GEN
Solar/Wind Harmer
14.451
957381AF2-032 GEN
Solar/Wind Harmer
0.966
970193AG2-126 GEN
Solar/Wind Harmer
7.158
276785W4-005 GEN1
Solar/Wind Harmer
1.44
971993AH1-541 GEN
Solar/Wind Harmer
4.402
965931AG1-462 GEN
Solar/Wind Harmer
12.097
971087AG2-675 GEN
Solar/Wind Harmer
1.765
270186AC1-089 GEN
Solar/Wind Harmer
2.883
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.771
24728505AND G1
Adder
1.803
965091AG1-374 GEN
Solar/Wind Harmer
14.092
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
1.869
274878BISHOP HL;2U
Solar/Wind Harmer
1.582
274851PROVIDENC;RU
Solar/Wind Harmer
1.332
274849CRESCENT ;1U
Solar/Wind Harmer
0.865
276603SUBLETTE C
Solar/Wind Harmer
0.49
274857EASY ROAD;U1
Solar/Wind Harmer
2.239
274760LEE CO EC;1U
Adder
4.348
274767LEE CO EC;8U
Adder
4.297
24721905FLATG4
Adder
9.452
270367AC2-061_GEN
Solar/Wind Harmer
1.479
970571AG2-364 GEN
Solar/Wind Harmer
9.291
959091AF2-200 GEN
Solar/Wind Harmer
9.281
252507AC2-088 GEN
Solar/Wind Harmer
0.831
274855GSG-6 ;RU
Solar/Wind Harmer
1.71
274850MENDOTA H;RU
Solar/Wind Harmer
1.189
276602WESTBROOK C
Solar/Wind Harmer
0.984
276799AD1-013 GEN
Solar/Wind Harmer
1.023
946671AF1-331 GEN
Solar/Wind Harmer
0.194
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
25196608WSDLE5
Adder
3.933
274729ELWOOD EC;1P
Adder
7.484
274730ELWOOD EC;6P
Adder
7.484
274734ELWOOD EC;8P
Adder
7.484
274736ELWOOD EC;9P
Adder
7.484
274676JOLIET 29;8U
Adder
5.57
3147983MERCK5
Solar/Wind Helper
0.108
316192AB2-158 GEN
Solar/Wind Helper
0.989
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
3146776BUCKING
Solar/Wind Helper
0.05
238152AF2-075_GEN
Solar/Wind Helper
0.306
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
1.456
316044AC1-158 PL1
Solar/Wind Helper
0.662
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
315975AC1-164 GENB
Solar/Wind Helper
0.044
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.173
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.959
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
316313AB2-026
Solar/Wind Helper
0.201
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.168
238147AE2-230_GEN1
Solar/Wind Helper
0.214
238148AE2-230_GEN2
Solar/Wind Helper
0.214
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316006AB2-029 C
Solar/Wind Helper
0.059
316312AB1-027
Solar/Wind Helper
0.234
316097T157 G90
Solar/Wind Helper
0.557
316045AC1-158 PL2
Solar/Wind Helper
2.117
316450AC1-158 RIC
Solar/Wind Helper
0.176
3143526WINTERP
Solar/Wind Helper
0.609
315976AC1-164 GENA
Solar/Wind Helper
1.499
316169AC1-164_GENC
Solar/Wind Helper
1.295
3142946ENON
Solar/Wind Helper
0.011
316487AF1-042 GEN
Solar/Wind Helper
0.113
276872AE1-163_GEN1
Solar/Wind Harmer
0.072
276876AE1-163_GEN2
Solar/Wind Harmer
0.072
270444AC2-157 GEN1
Solar/Wind Harmer
2.733
270445AC2-157 GEN2
Solar/Wind Harmer
2.733
944221AF1-090 GEN
Solar/Wind Harmer
5.329
276763AC1-053 GEN1
Solar/Wind Harmer
1.887
276764AC1-053 GEN2
Solar/Wind Harmer
1.887
276668AB2-070 GEN1
Solar/Wind Harmer
1.055
276848AB2-070 GEN3
Solar/Wind Harmer
1.055
276849AB2-070 GEN2
Solar/Wind Harmer
1.055
946321AF1-296 GEN
Solar/Wind Harmer
4.94
25196108MFTGT2
Adder
0.721
25196108MFTGT2
Adder
0.67
274853TWINGROVE;U1
Solar/Wind Harmer
3.384
274854TWINGROVE;U2
Solar/Wind Harmer
3.313
274877BISHOP HL;1U
Solar/Wind Harmer
1.582
276741O09 GEN1
Solar/Wind Harmer
1.676
972267AH1-718 GEN
Adder
1.953
276726Z2-087_GEN
Solar/Wind Harmer
3.696
959341AF2-225 GEN
Solar/Wind Harmer
7.012
971681AH1-341 GEN
Solar/Wind Harmer
7
274856ECOGROVE ;U1
Solar/Wind Harmer
1.571
276611AD2-172 GEN
Solar/Wind Harmer
1.192
276612AE2-035 GEN
Solar/Wind Harmer
1.192
274823ROCKFORD ;21
Adder
9.053
926823AC1-168 GEN
Solar/Wind Harmer
1.997
963841AG1-237 GEN
Solar/Wind Harmer
5.074
971171AH1-044 GEN
Solar/Wind Harmer
9.281
970169AG2-114 GEN
Solar/Wind Harmer
4.633
276861AD2-134 GEN
Solar/Wind Harmer
0.827
276863AD2-134 GEN
Solar/Wind Harmer
0.827
971675AH1-338 GEN
Solar/Wind Harmer
8.334
971411AH1-196 GEN
Solar/Wind Harmer
6.945
25196408WSDLE3
Adder
4.049
25196308WSDLE2
Adder
4.013
25196208WSDLE1
Adder
4.003
25196708WSDLE6
Adder
3.993
25196508WSDLE4
Adder
3.893
274744AC1-111 GEN8
Adder
2.557
274746AC1-111 G10
Adder
2.557
274728ELWOOD EC;5P
Adder
7.484
274731ELWOOD EC;2P
Adder
7.484
274733ELWOOD EC;3P
Adder
7.484
274735ELWOOD EC;4P
Adder
7.484
274675JOLIET 29;7U
Adder
13.963
274675JOLIET 29;7U
Adder
13.464
315616AA1-038_C
Solar/Wind Helper
1.809
3148463FAIRFLD
Solar/Wind Helper
0.399
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
315651AD1-115 GEN
Solar/Wind Helper
0.443
316258AE1-075 C
Solar/Wind Helper
0.181
316405AF2-144 C
Solar/Wind Helper
0.151
316164AC1-076 GEN
Solar/Wind Helper
0.62
316322AB2-045
Solar/Wind Helper
0.141
316468AD1-105 GEN
Solar/Wind Helper
0.59
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.113
276889AE2-281 GEN
Solar/Wind Harmer
0.021
958131AF2-107 GEN
Solar/Wind Harmer
2.667
943111AE2-339 GEN
Solar/Wind Harmer
0.467
943811AF1-049 GEN
Solar/Wind Harmer
1.99
339221AD2-048_GEN
Solar/Wind Harmer
0.786
970091AG2-072 GEN
Adder
38.065
945681AF1-233 GEN
Solar/Wind Harmer
9.341
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276621W2-048 GEN
Solar/Wind Harmer
2.987
276686W4-005 GEN3
Solar/Wind Harmer
1.44
25196008MFTGT1
Adder
0.654
24728605AND G2
Adder
1.803
274848CAMPGROVE;RU
Solar/Wind Harmer
3.029
276708O09 GEN2
Solar/Wind Harmer
1.676
276646AC1-214 GEN2
Solar/Wind Harmer
0.626
25196808ZIMRHP
Adder
35.505
276655WTG1_EQ
Solar/Wind Harmer
4.08
276656WTG2_EQ
Solar/Wind Harmer
0.54
939741AE1-205 GEN
Solar/Wind Harmer
9.349
274858EASY ROAD;U2
Solar/Wind Harmer
2.239
274761LEE CO EC;2U
Adder
4.348
274766LEE CO EC;7U
Adder
4.297
963741AG1-226 GEN
Solar/Wind Harmer
21.023
970819AG2-516 GEN
Solar/Wind Harmer
5.587
274822ROCKFORD ;11
Adder
9.119
970569AG2-363 GEN
Solar/Wind Harmer
13.937
957471AF2-041 GEN
Solar/Wind Harmer
13.921
959081AF2-199 GEN
Solar/Wind Harmer
4.64
971067AG2-660 GEN
Solar/Wind Harmer
1.079
274828WAUKEGAN ;BP
Adder
5.078
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
274745AC1-111 GEN9
Adder
2.557
274732ELWOOD EC;7P
Adder
7.484
274674JOLIET 9 ;6U
Adder
7.01
274676JOLIET 29;8U
Adder
13.963
3148013FISHERV
Solar/Wind Helper
0.287
316499AE2-029_GEN
Solar/Wind Helper
0.937
315821AE2-092 GEN
Solar/Wind Helper
1.831
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
23546401DTGZ2-030
Solar/Wind Helper
0.04
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.76
23583801GRNGAP
Solar/Wind Helper
2.128
316095T157 G97
Solar/Wind Helper
0.557
316075AC2-137 C
Solar/Wind Helper
0.18
316223AC1-118
Solar/Wind Helper
0.174
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.453
316077AC2-138 C
Solar/Wind Helper
0.106
316484AD2-074 GEN
Solar/Wind Helper
0.216
LAGNLTFEXP_LAGN->PJM
CLTF
11.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.097
TVALTFEXP_TVA->PJM
CLTF
6.216
NYPJM->LTFIMP_NY
CLTF
1.48
LGEELTFEXP_LGEE->PJM
CLTF
3.563
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.647
MECLTFEXP_MEC->PJM
CLTF
8.317
SIGELTFEXP_SIGE->PJM
CLTF
0.271
CPLELTFEXP_CPLE->PJM
CLTF
3.109
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.184
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 50.36 MW.

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2430.97
MW Contribution:
42.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24735105WLF2G1
50/50
5.207
24734705WLF1G3
50/50
5.196
24734805WLF1G4
50/50
5.196
24734905WLF1G5
50/50
5.196
966391AG1-508 GEN
Solar/Wind Harmer
0.87
971981AH1-535 GEN
Solar/Wind Harmer
3.671
971313AH1-133 GEN
Solar/Wind Harmer
2.637
970281AG2-184 GEN
Solar/Wind Harmer
10.194
270399AC1-101 GEN
Solar/Wind Harmer
1.444
270400AC1-102 GEN
Solar/Wind Harmer
1.444
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
10.049
3429211JKCT 2G
Adder
6.347
339216AC1-074 GEN
Solar/Wind Harmer
0.095
972163AH1-664 GEN
Solar/Wind Harmer
3.863
972165AH1-665 GEN
Solar/Wind Harmer
3.094
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
1.996
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.131
276848AB2-070 GEN3
Solar/Wind Harmer
0.13
276849AB2-070 GEN2
Solar/Wind Harmer
0.131
946321AF1-296 GEN
Solar/Wind Harmer
1.85
25196108MFTGT2
Adder
0.721
25196108MFTGT2
Adder
0.67
274854TWINGROVE;U2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.109
276741O09 GEN1
Solar/Wind Harmer
0.116
972267AH1-718 GEN
Adder
1.953
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.424
971681AH1-341 GEN
Solar/Wind Harmer
5.242
274856ECOGROVE ;U1
Solar/Wind Harmer
0.076
274823ROCKFORD ;21
Adder
9.053
926823AC1-168 GEN
Solar/Wind Harmer
0.551
963841AG1-237 GEN
Solar/Wind Harmer
1.404
971171AH1-044 GEN
Solar/Wind Harmer
6.475
970563AG2-360 GEN
50/50
26.903
24689505VACITY
50/50
3.164
943031AE2-326 GEN
Solar/Wind Harmer
3.912
962751AG1-124 GEN
Solar/Wind Harmer
6.205
960911AF2-382 GEN
Solar/Wind Harmer
4.078
971461AH1-227 GEN
Solar/Wind Harmer
2.687
972103AH1-617 GEN
Solar/Wind Harmer
9.709
972273AH1-721 GEN
Adder
50.356
24686405CER G5
Adder
4.71
970093AG2-073 GEN
Solar/Wind Harmer
3.273
970653AG2-424 GEN
Solar/Wind Harmer
0.386
270030AE2-140 GEN
Solar/Wind Harmer
7.666
970455AG2-298 GEN
Solar/Wind Harmer
1.477
3429391JKCT 9G
Adder
4.482
972167AH1-666 GEN
Solar/Wind Harmer
2.762
958171AF2-111 GEN
Solar/Wind Harmer
8.524
942481AE2-261 GEN
Solar/Wind Harmer
10.082
957381AF2-032 GEN
Solar/Wind Harmer
0.764
970193AG2-126 GEN
Solar/Wind Harmer
4.994
971993AH1-541 GEN
Solar/Wind Harmer
1.535
965931AG1-462 GEN
Solar/Wind Harmer
8.44
971087AG2-675 GEN
Solar/Wind Harmer
1.765
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.771
24728505AND G1
Adder
1.803
965091AG1-374 GEN
Solar/Wind Harmer
9.832
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.109
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.348
274767LEE CO EC;8U
Adder
4.297
24721905FLATG4
Adder
9.452
270367AC2-061_GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.482
959091AF2-200 GEN
Solar/Wind Harmer
6.475
252507AC2-088 GEN
Solar/Wind Harmer
0.146
274855GSG-6 ;RU
Solar/Wind Harmer
0.118
24735205WLF2G2
50/50
5.207
24728305BUCHG2
Adder
3.63
971687AH1-348 GEN
Solar/Wind Harmer
0.521
971403AH1-188 GEN
Solar/Wind Harmer
6.407
944971AF1-162 GEN
Solar/Wind Harmer
4.503
24723205RIVRG3
Adder
11.612
972203AH1-686 GEN
Adder
1.34
964901AG1-354 GEN
Solar/Wind Harmer
6.034
24686505CER G6
Adder
4.748
970653AG2-424 GEN
Solar/Wind Harmer
1.862
3429241JKCT 3G
Adder
6.43
3429421JKCT 10G
Adder
4.482
958131AF2-107 GEN
Solar/Wind Harmer
2.003
943811AF1-049 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
38.065
945681AF1-233 GEN
Solar/Wind Harmer
6.517
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276621W2-048 GEN
Solar/Wind Harmer
0.167
25196008MFTGT1
Adder
0.654
24728605AND G2
Adder
1.803
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.116
276646AC1-214 GEN2
Solar/Wind Harmer
0.128
25196808ZIMRHP
Adder
35.505
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.566
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.348
274766LEE CO EC;7U
Adder
4.297
963741AG1-226 GEN
Solar/Wind Harmer
7.714
970819AG2-516 GEN
Solar/Wind Harmer
3.898
274822ROCKFORD ;11
Adder
9.119
970569AG2-363 GEN
Solar/Wind Harmer
9.723
957471AF2-041 GEN
Solar/Wind Harmer
9.712
959081AF2-199 GEN
Solar/Wind Harmer
3.237
971067AG2-660 GEN
Solar/Wind Harmer
1.079
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.689
971277AH1-098 GEN
Solar/Wind Harmer
2.311
24728205BUCHG1
Adder
3.63
971225AH1-072 GEN
Solar/Wind Harmer
1.048
971227AH1-073 GEN
Solar/Wind Harmer
1.048
24723005RIVRG1
Adder
11.612
24723105RIVRG2
Adder
11.612
966021AG1-471 GEN
Solar/Wind Harmer
2.29
971485AH1-239 GEN
Solar/Wind Harmer
3.377
964781AG1-341 GEN
Solar/Wind Harmer
4.305
942891AE2-308 GEN
Solar/Wind Harmer
3.798
964571AG1-320 GEN
Solar/Wind Harmer
3.443
971125AH1-004 GEN
Solar/Wind Harmer
1.471
970107AG2-081 GEN
Solar/Wind Harmer
1.103
972043AH1-570 GEN
Solar/Wind Harmer
0.938
972045AH1-571 GEN
Solar/Wind Harmer
0.751
971587AH1-292 GEN
Solar/Wind Harmer
2.505
276916AD2-100_GEN
Solar/Wind Harmer
7.095
276911AD2-131_GEN
Solar/Wind Harmer
0.467
276615X2-022 GEN
Solar/Wind Harmer
0.035
276838X2-022 GEN2
Solar/Wind Harmer
0.188
945391AF1-204 GEN
Solar/Wind Harmer
3.538
960611AF2-352 GEN
Solar/Wind Harmer
1.092
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.528
276645AC1-214 GEN1
Solar/Wind Harmer
0.128
942111AE2-223 GEN
Solar/Wind Harmer
1.06
274764LEE CO EC;5U
Adder
4.358
970169AG2-114 GEN
Solar/Wind Harmer
3.232
276861AD2-134 GEN
Solar/Wind Harmer
0.058
276863AD2-134 GEN
Solar/Wind Harmer
0.058
274765LEE CO EC;6U
Adder
4.358
276882AE2-255 GEN
Solar/Wind Harmer
0.375
971675AH1-338 GEN
Solar/Wind Harmer
1.26
971411AH1-196 GEN
Solar/Wind Harmer
4.845
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
4.049
25196308WSDLE2
Adder
4.013
25196208WSDLE1
Adder
4.003
25196708WSDLE6
Adder
3.993
25196508WSDLE4
Adder
3.893
274744AC1-111 GEN8
Adder
2.557
274746AC1-111 G10
Adder
2.557
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.499
970833AG2-524 GEN
Solar/Wind Harmer
2.333
274728ELWOOD EC;5P
Adder
7.484
274731ELWOOD EC;2P
Adder
7.484
274733ELWOOD EC;3P
Adder
7.484
274735ELWOOD EC;4P
Adder
7.484
274675JOLIET 29;7U
Adder
13.963
274675JOLIET 29;7U
Adder
13.464
960591AF2-350 GEN
Solar/Wind Harmer
3.162
970289AG2-191 GEN
Solar/Wind Harmer
0.599
971611AH1-305 GEN
Solar/Wind Harmer
1.876
971985AH1-537 GEN
Solar/Wind Harmer
0.936
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
4.672
971609AH1-304 GEN
Solar/Wind Harmer
0.508
270543AE2-219 C
Solar/Wind Harmer
2.176
253406AD2-031_GEN
Solar/Wind Harmer
0.23
964611AG1-324 GEN
Solar/Wind Harmer
1.21
247536S-71 GEN
Solar/Wind Harmer
0.124
945581AF1-223 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
5.772
315616AA1-038_C
Solar/Wind Helper
1.809
3148463FAIRFLD
Solar/Wind Helper
0.399
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
315651AD1-115 GEN
Solar/Wind Helper
0.443
316258AE1-075 C
Solar/Wind Helper
0.181
316405AF2-144 C
Solar/Wind Helper
0.151
316164AC1-076 GEN
Solar/Wind Helper
0.62
316322AB2-045
Solar/Wind Helper
0.141
316468AD1-105 GEN
Solar/Wind Helper
0.59
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.113
274850MENDOTA H;RU
Solar/Wind Harmer
0.038
946671AF1-331 GEN
Solar/Wind Harmer
0.345
276868AE1-113 GEN
Solar/Wind Harmer
0.643
274879MINONK ;1U
Solar/Wind Harmer
0.134
24386205FR-12G C
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
1.674
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
25196608WSDLE5
Adder
3.933
274862TOP CROP ;2U
Solar/Wind Harmer
0.432
943121AE2-341 GEN
Solar/Wind Harmer
5.351
943591AF1-030 GEN
Solar/Wind Harmer
3.559
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.187
274729ELWOOD EC;1P
Adder
7.484
274730ELWOOD EC;6P
Adder
7.484
274734ELWOOD EC;8P
Adder
7.484
274736ELWOOD EC;9P
Adder
7.484
274676JOLIET 29;8U
Adder
3.003
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.354
274887GEN-1.85
Solar/Wind Harmer
0.082
276843GEN-1.7
Solar/Wind Harmer
0.102
276806AD2-047 C O1
Solar/Wind Harmer
1.792
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
4.107
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.347
970825AG2-519 GEN
Solar/Wind Harmer
2.365
270004AE1-209 GEN
Solar/Wind Harmer
0.68
946031AF1-268 GEN
Solar/Wind Harmer
2.979
964401AG1-302 GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
7.973
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.643
970191AG2-125 GEN
Solar/Wind Harmer
0.781
944531AF1-118 GEN
Solar/Wind Harmer
13.572
971347AH1-153 GEN
Solar/Wind Harmer
1.512
3147983MERCK5
Solar/Wind Helper
0.108
316192AB2-158 GEN
Solar/Wind Helper
0.989
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
3146776BUCKING
Solar/Wind Helper
0.05
238152AF2-075_GEN
Solar/Wind Helper
0.306
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
1.456
316044AC1-158 PL1
Solar/Wind Helper
0.662
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
315975AC1-164 GENB
Solar/Wind Helper
0.044
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.173
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.959
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
274762LEE CO EC;3U
Adder
4.348
274763LEE CO EC;4U
Adder
4.307
970241AG2-163 GEN
Solar/Wind Harmer
1.901
938861AE1-114 GEN
Solar/Wind Harmer
1.845
972235AH1-702 GEN1
Adder
1.172
972236AH1-702 GEN2
Adder
1.019
971341AH1-150 GEN
Solar/Wind Harmer
6.475
971343AH1-151 GEN
Solar/Wind Harmer
6.475
252509AD1-136 GEN
Solar/Wind Harmer
0.016
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.364
962691AG1-118 GEN
Solar/Wind Harmer
9.643
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.815
25183208HLCRTG
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
9.688
274683WAUKEGAN ;8U
Adder
8.167
25194408D.CRK1
Adder
3.476
25194508D.CRK3
Adder
0.65
274696ROCKY RD ;4P
Adder
5.236
274695ROCKY RD ;2P
Adder
5.115
274693ROCKY RD ;1P
Adder
5.064
274697ROCKY RD ;3P
Adder
1.389
958481AF2-142 GEN
Solar/Wind Harmer
4.795
24728805RICHG1
Adder
1.729
24728905RICHG2
Adder
1.729
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
7.01
276893AG1-478 C
Solar/Wind Harmer
0.212
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
7.927
274888KELLY CRK;1U
Solar/Wind Harmer
0.184
276776AD2-060 GEN
Solar/Wind Harmer
0.337
958011AF2-095 GEN
Solar/Wind Harmer
4.553
970941AG2-585 GEN
Solar/Wind Harmer
1.739
926881AC1-175 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.41
970291AG2-192 GEN
Solar/Wind Harmer
0.189
971613AH1-306 GEN
Solar/Wind Harmer
1.512
270383AD1-128 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.712
270599AE1-208 GEN
Solar/Wind Harmer
2.854
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
3.108
970885AG2-551 GEN
Solar/Wind Harmer
1.036
964611AG1-324 GEN
Solar/Wind Harmer
0.233
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.205
960971AF2-388 GEN
Solar/Wind Harmer
1.8
965681AG1-436 GEN
Solar/Wind Harmer
3.818
965791AG1-447 GEN
Solar/Wind Harmer
2.8
942221AE2-234 GEN
Solar/Wind Harmer
1.218
970349AG2-230 GEN
Solar/Wind Harmer
4.536
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
237061AD1-155 GEN
Solar/Wind Helper
0.84
316313AB2-026
Solar/Wind Helper
0.201
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.168
238147AE2-230_GEN1
Solar/Wind Helper
0.214
238148AE2-230_GEN2
Solar/Wind Helper
0.214
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316006AB2-029 C
Solar/Wind Helper
0.059
316312AB1-027
Solar/Wind Helper
0.234
316097T157 G90
Solar/Wind Helper
0.557
316045AC1-158 PL2
Solar/Wind Helper
2.117
316450AC1-158 RIC
Solar/Wind Helper
0.176
3143526WINTERP
Solar/Wind Helper
0.609
315976AC1-164 GENA
Solar/Wind Helper
1.499
316169AC1-164_GENC
Solar/Wind Helper
1.295
3142946ENON
Solar/Wind Helper
0.011
316487AF1-042 GEN
Solar/Wind Helper
0.113
962781AG1-127 GEN
Solar/Wind Harmer
3.062
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
0.568
276805AD2-038 GEN
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.024
252516AE2-318_GEN
Solar/Wind Harmer
3.594
274828WAUKEGAN ;BP
Adder
5.078
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
939401AE1-172 GEN
Solar/Wind Harmer
2.397
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.519
274745AC1-111 GEN9
Adder
2.557
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.484
274674JOLIET 9 ;6U
Adder
7.01
274676JOLIET 29;8U
Adder
13.963
276903AD2-071 C
Solar/Wind Harmer
3.542
941551AE2-152 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
3.159
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
2.314
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
3.938
270594AE1-207 GEN
Solar/Wind Harmer
3.528
270032AE2-172
Solar/Wind Harmer
2.1
970825AG2-519 GEN
Solar/Wind Harmer
1.115
270005AE1-210 C O1
Solar/Wind Harmer
0.68
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.068
958381AF2-132 GEN
Solar/Wind Harmer
0
253398AE2-221_GEN2
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.5
958861AF2-177 GEN
Solar/Wind Harmer
1.334
965651AG1-433 GEN
Solar/Wind Harmer
0.9
270024AE2-089 GEN
Solar/Wind Harmer
0
3148013FISHERV
Solar/Wind Helper
0.287
316499AE2-029_GEN
Solar/Wind Helper
0.937
315821AE2-092 GEN
Solar/Wind Helper
1.831
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
23546401DTGZ2-030
Solar/Wind Helper
0.04
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.76
23583801GRNGAP
Solar/Wind Helper
2.128
316095T157 G97
Solar/Wind Helper
0.557
316075AC2-137 C
Solar/Wind Helper
0.18
316223AC1-118
Solar/Wind Helper
0.174
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.453
316077AC2-138 C
Solar/Wind Helper
0.106
316484AD2-074 GEN
Solar/Wind Helper
0.216
LAGNLTFEXP_LAGN->PJM
CLTF
11.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.097
TVALTFEXP_TVA->PJM
CLTF
6.216
NYPJM->LTFIMP_NY
CLTF
1.48
LGEELTFEXP_LGEE->PJM
CLTF
3.563
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.647
MECLTFEXP_MEC->PJM
CLTF
8.317
SIGELTFEXP_SIGE->PJM
CLTF
0.271
CPLELTFEXP_CPLE->PJM
CLTF
3.109
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.184
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 50.36 MW.

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.13 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4008.49
MW Contribution:
75.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.795
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
971329AH1-144 GEN
Solar/Wind Harmer
6.744
966391AG1-508 GEN
Solar/Wind Harmer
1.991
270197AD1-017 GEN1
Solar/Wind Harmer
1.424
270069AE2-166 C O1
Solar/Wind Harmer
10.375
971313AH1-133 GEN
Solar/Wind Harmer
5.363
24734705WLF1G3
Adder
8.187
24734805WLF1G4
Adder
8.187
24734905WLF1G5
Adder
8.187
24735105WLF2G1
Adder
8.017
270399AC1-101 GEN
Solar/Wind Harmer
2.889
270400AC1-102 GEN
Solar/Wind Harmer
2.889
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
20.219
970281AG2-184 GEN
Solar/Wind Harmer
18.909
971981AH1-535 GEN
Solar/Wind Harmer
5.838
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.21
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.967
970563AG2-360 GEN
50/50
45.796
970417AG2-272 GEN
50/50
3.731
962751AG1-124 GEN
Solar/Wind Harmer
12.886
958121AF2-106 GEN
Solar/Wind Harmer
0.001
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.174
941801AE2-185 GEN
Solar/Wind Harmer
7.447
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.535
270030AE2-140 GEN
Solar/Wind Harmer
21.562
960911AF2-382 GEN
Solar/Wind Harmer
7.632
971461AH1-227 GEN
Solar/Wind Harmer
4.882
970223AG2-152 GEN
Solar/Wind Harmer
12.382
972103AH1-617 GEN
Solar/Wind Harmer
18.009
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.195
24684505SMG3
50/50
1.341
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.157
3147312GRETNA
Solar/Wind Harmer
0.047
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
958131AF2-107 GEN
Solar/Wind Harmer
5.335
24735205WLF2G2
Adder
8.017
971687AH1-348 GEN
Solar/Wind Harmer
0.947
971403AH1-188 GEN
Solar/Wind Harmer
13.142
944971AF1-162 GEN
Solar/Wind Harmer
9.06
24723205RIVRG3
Adder
22.932
24686505CER G6
Adder
9.865
972203AH1-686 GEN
Adder
2.702
964901AG1-354 GEN
Solar/Wind Harmer
10.795
960001AF2-291 GEN
Solar/Wind Harmer
0
3429241JKCT 3G
Adder
12.016
970653AG2-424 GEN
Solar/Wind Harmer
3.403
3429421JKCT 10G
Adder
8.393
945681AF1-233 GEN
Solar/Wind Harmer
12.766
970091AG2-072 GEN
Adder
73.941
316123AC1-075 GEN
Solar/Wind Harmer
0.164
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252516AE2-318_GEN
Solar/Wind Harmer
7.186
252510AF1-249 C
Solar/Wind Harmer
0.048
25194608D.CRK4
Adder
1.506
971073AG2-665 GEN
Solar/Wind Harmer
1.065
965911AG1-460 GEN
Solar/Wind Harmer
1.269
971061AG2-657 GEN
Solar/Wind Harmer
5.362
3429211JKCT 2G
Adder
11.861
339216AC1-074 GEN
Solar/Wind Harmer
0.182
972163AH1-664 GEN
Solar/Wind Harmer
7.559
972165AH1-665 GEN
Solar/Wind Harmer
6.054
971985AH1-537 GEN
Solar/Wind Harmer
2.009
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
944221AF1-090 GEN
Solar/Wind Harmer
3.75
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
25196508WSDLE4
Adder
7.759
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.247
276848AB2-070 GEN3
Solar/Wind Harmer
0.246
276849AB2-070 GEN2
Solar/Wind Harmer
0.247
270356AE2-297 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.464
963841AG1-237 GEN
Solar/Wind Harmer
2.696
946321AF1-296 GEN
Solar/Wind Harmer
3.479
274854TWINGROVE;U2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.498
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.206
276741O09 GEN1
Solar/Wind Harmer
0.218
972267AH1-718 GEN
Adder
3.684
971681AH1-341 GEN
Solar/Wind Harmer
9.907
274856ECOGROVE ;U1
Solar/Wind Harmer
0.144
926823AC1-168 GEN
Solar/Wind Harmer
1.044
970169AG2-114 GEN
Solar/Wind Harmer
6.143
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.132
971171AH1-044 GEN
Solar/Wind Harmer
12.26
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
970289AG2-191 GEN
Solar/Wind Harmer
1.163
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.387
971411AH1-196 GEN
Solar/Wind Harmer
9.181
270263AC1-001 GEN
Solar/Wind Harmer
0.61
970073AG2-061 GEN
Solar/Wind Harmer
2.033
971029AG2-637 GEN
Solar/Wind Harmer
9.145
270543AE2-219 C
Solar/Wind Harmer
4.252
274744AC1-111 GEN8
Adder
4.865
274746AC1-111 G10
Adder
4.865
24686405CER G5
Adder
9.787
972273AH1-721 GEN
Adder
89.23
24721905FLATG4
Adder
21.662
970093AG2-073 GEN
Solar/Wind Harmer
6.071
970653AG2-424 GEN
Solar/Wind Harmer
0.705
3429391JKCT 9G
Adder
8.393
971191AH1-055 GEN
Solar/Wind Harmer
18.034
970455AG2-298 GEN
Solar/Wind Harmer
2.725
972167AH1-666 GEN
Solar/Wind Harmer
5.413
958171AF2-111 GEN
Solar/Wind Harmer
16.661
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.292
25196008MFTGT1
Adder
1.251
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
970879AG2-548 GEN
Solar/Wind Harmer
4.688
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
9.542
942481AE2-261 GEN
Solar/Wind Harmer
18.979
957381AF2-032 GEN
Solar/Wind Harmer
1.438
24728705AND G3
Adder
7.274
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.219
971993AH1-541 GEN
Solar/Wind Harmer
2.902
253394AE2-221_GEN
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
15.863
971087AG2-675 GEN
Solar/Wind Harmer
3.318
965091AG1-374 GEN
Solar/Wind Harmer
18.636
959611AF2-252 GEN
Solar/Wind Harmer
2.071
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.206
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.213
274767LEE CO EC;8U
Adder
8.117
970571AG2-364 GEN
Solar/Wind Harmer
12.283
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.138
959091AF2-200 GEN
Solar/Wind Harmer
12.26
247642Z2-115 C
Solar/Wind Harmer
0.003
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970289AG2-191 GEN
Solar/Wind Harmer
0.673
946671AF1-331 GEN
Solar/Wind Harmer
0.653
270004AE1-209 GEN
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
4.603
276868AE1-113 GEN
Solar/Wind Harmer
1.222
274879MINONK ;1U
Solar/Wind Harmer
0.255
946031AF1-268 GEN
Solar/Wind Harmer
5.802
274682WAUKEGAN ;7U
Adder
15.687
274862TOP CROP ;2U
Solar/Wind Harmer
0.821
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.322
276621W2-048 GEN
Solar/Wind Harmer
0.315
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.798
253398AE2-221_GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.664
24385905FR-11G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.218
276646AC1-214 GEN2
Solar/Wind Harmer
0.242
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.518
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.213
274766LEE CO EC;7U
Adder
8.117
276903AD2-071 C
Solar/Wind Harmer
6.875
970819AG2-516 GEN
Solar/Wind Harmer
7.371
970569AG2-363 GEN
Solar/Wind Harmer
18.425
274822ROCKFORD ;11
Adder
17.258
957471AF2-041 GEN
Solar/Wind Harmer
18.391
959081AF2-199 GEN
Solar/Wind Harmer
6.13
971067AG2-660 GEN
Solar/Wind Harmer
2.043
270594AE1-207 GEN
Solar/Wind Harmer
6.854
270032AE2-172
Solar/Wind Harmer
4.08
971997AH1-543 GEN
Solar/Wind Harmer
3.207
270005AE1-210 C O1
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
2.169
276882AE2-255 GEN
Solar/Wind Harmer
0.713
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.81
939401AE1-172 GEN
Solar/Wind Harmer
4.564
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.988
274745AC1-111 GEN9
Adder
4.865
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.589
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
274676JOLIET 29;8U
Adder
26.611
941551AE2-152 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0.001
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.157
270583AD2-179 GEN
Solar/Wind Harmer
14.449
971277AH1-098 GEN
Solar/Wind Harmer
5.174
942671AE2-283 GEN
Solar/Wind Harmer
5.792
970913AG2-568 GEN
Solar/Wind Harmer
7.67
971225AH1-072 GEN
Solar/Wind Harmer
1.903
971227AH1-073 GEN
Solar/Wind Harmer
1.903
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
942751AE2-291 GEN
Solar/Wind Harmer
7.879
966021AG1-471 GEN
Solar/Wind Harmer
4.01
971485AH1-239 GEN
Solar/Wind Harmer
5.922
964781AG1-341 GEN
Solar/Wind Harmer
7.646
942891AE2-308 GEN
Solar/Wind Harmer
7.092
964571AG1-320 GEN
Solar/Wind Harmer
6.355
971125AH1-004 GEN
Solar/Wind Harmer
2.78
970107AG2-081 GEN
Solar/Wind Harmer
2.085
972043AH1-570 GEN
Solar/Wind Harmer
1.794
972045AH1-571 GEN
Solar/Wind Harmer
1.437
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
4.796
252509AD1-136 GEN
Solar/Wind Harmer
0.032
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
6.93
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
4.688
970879AG2-548 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
6.759
276916AD2-100_GEN
Solar/Wind Harmer
13.351
276911AD2-131_GEN
Solar/Wind Harmer
0.879
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.355
970241AG2-163 GEN
Solar/Wind Harmer
3.647
24728805RICHG1
Adder
3.383
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
8.571
960201AF2-311 GEN
Solar/Wind Harmer
5.7
960611AF2-352 GEN
Solar/Wind Harmer
2.071
942111AE2-223 GEN
Solar/Wind Harmer
2.011
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.996
276645AC1-214 GEN1
Solar/Wind Harmer
0.242
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.233
274765LEE CO EC;6U
Adder
8.233
274762LEE CO EC;3U
Adder
8.213
274763LEE CO EC;4U
Adder
8.136
938861AE1-114 GEN
Solar/Wind Harmer
3.487
270383AD1-128 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.217
972236AH1-702 GEN2
Adder
1.928
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
12.26
971343AH1-151 GEN
Solar/Wind Harmer
12.26
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.796
970291AG2-192 GEN
Solar/Wind Harmer
0.367
971613AH1-306 GEN
Solar/Wind Harmer
2.938
971611AH1-305 GEN
Solar/Wind Harmer
3.614
970833AG2-524 GEN
Solar/Wind Harmer
6.668
970833AG2-524 GEN
Solar/Wind Harmer
4.445
959141AF2-205 GEN
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
14.264
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
274735ELWOOD EC;4P
Adder
14.264
247536S-71 GEN
Solar/Wind Harmer
0.242
25306009OHH W.
Adder
2.5
971609AH1-304 GEN
Solar/Wind Harmer
0.988
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
964611AG1-324 GEN
Solar/Wind Harmer
2.357
958391AF2-133 GEN
Solar/Wind Harmer
0.001
960591AF2-350 GEN
Solar/Wind Harmer
6.035
945581AF1-223 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
3.297
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.089
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
18.303
958491AF2-143 GEN
Solar/Wind Harmer
9.149
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274696ROCKY RD ;4P
Adder
9.947
274695ROCKY RD ;2P
Adder
9.717
274693ROCKY RD ;1P
Adder
9.622
274697ROCKY RD ;3P
Adder
2.64
958481AF2-142 GEN
Solar/Wind Harmer
9.122
970883AG2-550 GEN
Solar/Wind Harmer
6.074
970885AG2-551 GEN
Solar/Wind Harmer
2.025
276893AG1-478 C
Solar/Wind Harmer
0.404
274674JOLIET 9 ;6U
Adder
13.36
270031AE2-169
Solar/Wind Harmer
3.328
270599AE1-208 GEN
Solar/Wind Harmer
5.547
276897AD1-100 C
Solar/Wind Harmer
15.124
964611AG1-324 GEN
Solar/Wind Harmer
0.453
274888KELLY CRK;1U
Solar/Wind Harmer
0.352
276776AD2-060 GEN
Solar/Wind Harmer
0.644
958011AF2-095 GEN
Solar/Wind Harmer
8.691
970941AG2-585 GEN
Solar/Wind Harmer
3.319
270201AC2-176 GEN
Solar/Wind Harmer
0
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.647
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
316450AC1-158 RIC
Solar/Wind Helper
0.337
971917AH1-482 GEN
Solar/Wind Harmer
7.838
945371AF1-202 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.23
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.295
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
943121AE2-341 GEN
Solar/Wind Harmer
10.182
943591AF1-030 GEN
Solar/Wind Harmer
6.771
274729ELWOOD EC;1P
Adder
14.264
274730ELWOOD EC;6P
Adder
14.264
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
19.749
274887GEN-1.85
Solar/Wind Harmer
0.157
276843GEN-1.7
Solar/Wind Harmer
0.195
276806AD2-047 C O1
Solar/Wind Harmer
3.42
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.046
970191AG2-125 GEN
Solar/Wind Harmer
1.552
964401AG1-302 GEN
Solar/Wind Harmer
0.001
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316447AC1-158 HLD
Solar/Wind Helper
2.777
316044AC1-158 PL1
Solar/Wind Helper
1.262
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
TVALTFEXP_TVA->PJM
CLTF
10.596
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
CPLELTFEXP_CPLE->PJM
CLTF
6.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 89.23 MW.

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.66 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4175.28
MW Contribution:
75.96
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.26
24684705SMG5
50/50
0.846
24684305SMG1
50/50
0.796
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.387
971329AH1-144 GEN
Solar/Wind Harmer
11.745
966391AG1-508 GEN
Solar/Wind Harmer
6.384
270197AD1-017 GEN1
Solar/Wind Harmer
2.542
270069AE2-166 C O1
Solar/Wind Harmer
14.894
971313AH1-133 GEN
Solar/Wind Harmer
9.348
24734705WLF1G3
Adder
8.213
24734805WLF1G4
Adder
8.213
24734905WLF1G5
Adder
8.213
24735105WLF2G1
Adder
8.042
270399AC1-101 GEN
Solar/Wind Harmer
5.575
270400AC1-102 GEN
Solar/Wind Harmer
5.575
941621AE2-160 GEN
Adder
4.304
957241AF2-018 GEN
Solar/Wind Harmer
5.778
270053AF1-130 C
Solar/Wind Harmer
23.086
970281AG2-184 GEN
Solar/Wind Harmer
27.213
971981AH1-535 GEN
Solar/Wind Harmer
12.593
962211AG1-066 GEN
Solar/Wind Harmer
3.011
971061AG2-657 GEN
Solar/Wind Harmer
11.048
3429211JKCT 2G
Adder
11.928
339216AC1-074 GEN
Solar/Wind Harmer
1.652
972163AH1-664 GEN
Solar/Wind Harmer
9.793
972165AH1-665 GEN
Solar/Wind Harmer
7.834
971985AH1-537 GEN
Solar/Wind Harmer
17.394
270444AC2-157 GEN1
Solar/Wind Harmer
5.263
270445AC2-157 GEN2
Solar/Wind Harmer
5.263
25196108MFTGT2
Adder
1.433
25196108MFTGT2
Adder
1.331
944221AF1-090 GEN
Solar/Wind Harmer
10.074
25196408WSDLE3
Adder
8.125
25196308WSDLE2
Adder
8.054
25196208WSDLE1
Adder
8.034
25196708WSDLE6
Adder
8.014
25196508WSDLE4
Adder
7.812
253433AC1-085 GEN1
Solar/Wind Harmer
4.849
253432AC1-085 GEN2
Solar/Wind Harmer
0.244
276763AC1-053 GEN1
Solar/Wind Harmer
3.586
276764AC1-053 GEN2
Solar/Wind Harmer
3.586
276668AB2-070 GEN1
Solar/Wind Harmer
2.006
276848AB2-070 GEN3
Solar/Wind Harmer
2.006
276849AB2-070 GEN2
Solar/Wind Harmer
2.006
270356AE2-297 GEN
Solar/Wind Harmer
4.168
253406AD2-031_GEN
Solar/Wind Harmer
1.153
270291AC1-194 GEN
Solar/Wind Harmer
4.567
963841AG1-237 GEN
Solar/Wind Harmer
9.807
946321AF1-296 GEN
Solar/Wind Harmer
9.347
274853TWINGROVE;U1
Solar/Wind Harmer
6.454
274854TWINGROVE;U2
Solar/Wind Harmer
6.319
270340AC2-060 GEN
Solar/Wind Harmer
2.703
276726Z2-087_GEN
Solar/Wind Harmer
7.058
959341AF2-225 GEN
Solar/Wind Harmer
13.389
972267AH1-718 GEN
Adder
3.707
274823ROCKFORD ;21
Adder
17.239
274744AC1-111 GEN8
Adder
4.896
274746AC1-111 G10
Adder
4.896
25306009OHH W.
Adder
2.518
274728ELWOOD EC;5P
Adder
14.355
274731ELWOOD EC;2P
Adder
14.355
274733ELWOOD EC;3P
Adder
14.355
274735ELWOOD EC;4P
Adder
14.355
253372AE2-315 SEC3
Adder
1.655
253372AE2-315 SEC3
Adder
1.655
274675JOLIET 29;7U
Adder
26.781
315616AA1-038_C
Solar/Wind Helper
3.299
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.846
316164AC1-076 GEN
Solar/Wind Helper
1.182
316258AE1-075 C
Solar/Wind Helper
0.321
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.093
238169AE2-226 GEN1
Solar/Wind Helper
0.546
238170AE2-226 GEN2
Solar/Wind Helper
0.546
3141426STAFORD
Solar/Wind Helper
0.049
24386405FR-21G C
Solar/Wind Harmer
2.921
24387005FR-3G C
Solar/Wind Harmer
2.686
970823AG2-518 GEN
50/50
8.391
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.212
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
15.01
970563AG2-360 GEN
50/50
45.925
970417AG2-272 GEN
50/50
3.737
962751AG1-124 GEN
Solar/Wind Harmer
18.829
958121AF2-106 GEN
Solar/Wind Harmer
9.417
943031AE2-326 GEN
Solar/Wind Harmer
6.794
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.813
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.976
270030AE2-140 GEN
Solar/Wind Harmer
30.957
270018AE2-047 C O1
Solar/Wind Harmer
1.823
960911AF2-382 GEN
Solar/Wind Harmer
10.976
270016AE1-250 BESS
Solar/Wind Harmer
3.251
971461AH1-227 GEN
Solar/Wind Harmer
7.023
970223AG2-152 GEN
Solar/Wind Harmer
17.677
972103AH1-617 GEN
Solar/Wind Harmer
25.917
24686405CER G5
Adder
9.839
270330AC1-082 GEN2
Solar/Wind Harmer
0.514
270329AC1-082 GEN1
Solar/Wind Harmer
0.514
972273AH1-721 GEN
Adder
89.66
24721905FLATG4
Adder
21.789
339255AE2-071 GEN
Solar/Wind Harmer
1.222
339250AF1-203 GEN
Solar/Wind Harmer
0.629
339206AE1-143 GEN
Solar/Wind Harmer
2.213
970093AG2-073 GEN
Solar/Wind Harmer
5.468
970653AG2-424 GEN
Solar/Wind Harmer
0.709
971191AH1-055 GEN
Solar/Wind Harmer
18.939
3429391JKCT 9G
Adder
8.441
970455AG2-298 GEN
Solar/Wind Harmer
3.536
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972167AH1-666 GEN
Solar/Wind Harmer
7.807
957541AF2-048 GEN
Solar/Wind Harmer
1.537
958171AF2-111 GEN
Solar/Wind Harmer
24.034
270186AC1-089 GEN
Solar/Wind Harmer
5.851
270367AC2-061_GEN
Solar/Wind Harmer
3.02
252507AC2-088 GEN
Solar/Wind Harmer
1.676
25196008MFTGT1
Adder
1.259
252519AF1-045_GEN
Solar/Wind Harmer
3.37
970879AG2-548 GEN
Solar/Wind Harmer
7.39
25194608D.CRK4
Adder
1.517
252524AE2-267 GEN
Solar/Wind Harmer
1.45
25196608WSDLE5
Adder
7.893
970193AG2-126 GEN
Solar/Wind Harmer
13.761
942481AE2-261 GEN
Solar/Wind Harmer
27.366
957381AF2-032 GEN
Solar/Wind Harmer
1.829
253317AC1-085 GEN4
Solar/Wind Harmer
7.64
946181AF1-283 GEN
Solar/Wind Harmer
11.863
24728705AND G3
Adder
7.32
24728505AND G1
Adder
3.5
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.18
270583AD2-179 GEN
Solar/Wind Harmer
20.746
270214AC2-123 GEN
Solar/Wind Harmer
4.317
971277AH1-098 GEN
Solar/Wind Harmer
7.43
942671AE2-283 GEN
Solar/Wind Harmer
8.669
270013AE1-250 PV
Solar/Wind Harmer
3.251
970913AG2-568 GEN
Solar/Wind Harmer
9.375
971225AH1-072 GEN
Solar/Wind Harmer
2.738
971227AH1-073 GEN
Solar/Wind Harmer
2.738
24723005RIVRG1
Adder
23.046
24723105RIVRG2
Adder
23.046
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.774
971485AH1-239 GEN
Solar/Wind Harmer
8.528
339231AF1-038_GEN
Solar/Wind Harmer
1.925
964781AG1-341 GEN
Solar/Wind Harmer
11.012
339236AF1-050_GEN
Solar/Wind Harmer
1.88
942891AE2-308 GEN
Solar/Wind Harmer
10.222
964571AG1-320 GEN
Solar/Wind Harmer
8.222
971125AH1-004 GEN
Solar/Wind Harmer
4.008
970107AG2-081 GEN
Solar/Wind Harmer
3.006
972043AH1-570 GEN
Solar/Wind Harmer
2.487
972045AH1-571 GEN
Solar/Wind Harmer
1.989
927014AC1-188 GEN
Solar/Wind Harmer
1.537
962581AG1-107 GEN
Solar/Wind Harmer
4.757
961491AF2-440 GEN
Solar/Wind Harmer
1.977
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.603
971073AG2-665 GEN
Solar/Wind Harmer
7.39
970879AG2-548 GEN
Solar/Wind Harmer
1.074
25194408D.CRK1
Adder
6.977
25194508D.CRK3
Adder
1.304
945391AF1-204 GEN
Solar/Wind Harmer
12.785
276916AD2-100_GEN
Solar/Wind Harmer
19.251
276911AD2-131_GEN
Solar/Wind Harmer
3.891
276615X2-022 GEN
Solar/Wind Harmer
1.781
276838X2-022 GEN2
Solar/Wind Harmer
0.212
274880W4-005 GEN4
Solar/Wind Harmer
2.739
276174W4-005 GEN2
Solar/Wind Harmer
2.739
970241AG2-163 GEN
Solar/Wind Harmer
22.546
24728805RICHG1
Adder
3.406
24728905RICHG2
Adder
3.406
960251AF2-316 GEN
Solar/Wind Harmer
13.508
960201AF2-311 GEN
Solar/Wind Harmer
9.005
960611AF2-352 GEN
Solar/Wind Harmer
2.083
942111AE2-223 GEN
Solar/Wind Harmer
7.317
274764LEE CO EC;5U
Adder
8.284
274765LEE CO EC;6U
Adder
8.284
274762LEE CO EC;3U
Adder
8.264
274763LEE CO EC;4U
Adder
8.186
972235AH1-702 GEN1
Adder
2.231
972236AH1-702 GEN2
Adder
1.94
274683WAUKEGAN ;8U
Adder
18.516
274683WAUKEGAN ;8U
Adder
15.608
274696ROCKY RD ;4P
Adder
10.01
274695ROCKY RD ;2P
Adder
9.779
274693ROCKY RD ;1P
Adder
9.683
274697ROCKY RD ;3P
Adder
2.656
253370AE2-315 SEC1
Adder
1.749
274674JOLIET 9 ;6U
Adder
13.445
3132123MT JACKSON
Solar/Wind Helper
1.393
966001AG1-469 GEN
Solar/Wind Helper
0.321
237061AD1-155 GEN
Solar/Wind Helper
1.655
316097T157 G90
Solar/Wind Helper
1.135
238147AE2-230_GEN1
Solar/Wind Helper
0.426
238148AE2-230_GEN2
Solar/Wind Helper
0.426
238149AF1-291A_GEN
Solar/Wind Helper
0.122
316006AB2-029 C
Solar/Wind Helper
0.114
316313AB2-026
Solar/Wind Helper
0.356
316045AC1-158 PL2
Solar/Wind Helper
4.058
316450AC1-158 RIC
Solar/Wind Helper
0.338
966871AG1-558 GEN
Solar/Wind Helper
0.307
316312AB1-027
Solar/Wind Helper
0.426
24387305FR-4G C
Solar/Wind Harmer
3.45
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.197
24684505SMG3
50/50
1.342
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.292
24728305BUCHG2
50/50
7.18
270173AC1-122 GEN
Solar/Wind Harmer
3.446
316217AC1-145 GEN
Solar/Wind Harmer
4.244
316197AC1-042 GEN
Solar/Wind Harmer
3.217
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.474
270336AE1-100 GEN
Solar/Wind Harmer
2.754
943811AF1-049 GEN
Solar/Wind Harmer
5.701
958131AF2-107 GEN
Solar/Wind Harmer
7.107
24735205WLF2G2
Adder
8.042
971687AH1-348 GEN
Solar/Wind Harmer
1.363
971403AH1-188 GEN
Solar/Wind Harmer
18.915
944971AF1-162 GEN
Solar/Wind Harmer
9.1
24723205RIVRG3
Adder
23.046
24686505CER G6
Adder
9.917
972203AH1-686 GEN
Adder
2.716
270331AC1-082 GEN3
Solar/Wind Harmer
0.515
339211AE2-254 GEN
Solar/Wind Harmer
1.567
964901AG1-354 GEN
Solar/Wind Harmer
15.55
960001AF2-291 GEN
Solar/Wind Harmer
3.133
339241AF1-083 GEN
Solar/Wind Harmer
1.722
3429241JKCT 3G
Adder
12.084
970653AG2-424 GEN
Solar/Wind Harmer
4.903
3429421JKCT 10G
Adder
8.441
943111AE2-339 GEN
Solar/Wind Harmer
0.887
339221AD2-048_GEN
Solar/Wind Harmer
1.518
945681AF1-233 GEN
Solar/Wind Harmer
18.414
970091AG2-072 GEN
Adder
74.384
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
71.001
25196008MFTGT1
Adder
1.3
252516AE2-318_GEN
Solar/Wind Harmer
9.259
252510AF1-249 C
Solar/Wind Harmer
0.385
971073AG2-665 GEN
Solar/Wind Harmer
1.074
25194608D.CRK4
Adder
1.517
965911AG1-460 GEN
Solar/Wind Harmer
1.277
253316AC1-085 GEN3
Solar/Wind Harmer
7.64
946171AF1-282 GEN
Solar/Wind Harmer
9.125
24728605AND G2
Adder
3.5
276621W2-048 GEN
Solar/Wind Harmer
5.671
276686W4-005 GEN3
Solar/Wind Harmer
2.739
963741AG1-226 GEN
Solar/Wind Harmer
40.583
253398AE2-221_GEN2
Solar/Wind Harmer
4.079
270222AC2-111 GEN
Solar/Wind Harmer
4.015
944031AF1-071 GEN
Solar/Wind Harmer
0.903
276655WTG1_EQ
Solar/Wind Harmer
7.791
276656WTG2_EQ
Solar/Wind Harmer
1.032
939741AE1-205 GEN
Solar/Wind Harmer
17.852
274761LEE CO EC;2U
Adder
8.264
274766LEE CO EC;7U
Adder
8.167
274822ROCKFORD ;11
Adder
17.365
274828WAUKEGAN ;BP
Adder
9.706
274682WAUKEGAN ;7U
Adder
15.786
274745AC1-111 GEN9
Adder
4.896
274732ELWOOD EC;7P
Adder
14.355
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
274674JOLIET 9 ;6U
Adder
13.445
274676JOLIET 29;8U
Adder
22.605
3148013FISHERV
Solar/Wind Helper
0.524
316499AE2-029_GEN
Solar/Wind Helper
1.728
315821AE2-092 GEN
Solar/Wind Helper
3.236
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.628
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.324
316095T157 G97
Solar/Wind Helper
1.135
966881AG1-559 GEN
Solar/Wind Helper
0.315
316473AC1-191 GEN
Solar/Wind Helper
1.393
24385905FR-11G C
Solar/Wind Harmer
5.645
24386605FR-22G C
Solar/Wind Harmer
2.921
276785W4-005 GEN1
Solar/Wind Harmer
2.739
971993AH1-541 GEN
Solar/Wind Harmer
8.371
253394AE2-221_GEN
Solar/Wind Harmer
4.079
965931AG1-462 GEN
Solar/Wind Harmer
22.875
971087AG2-675 GEN
Solar/Wind Harmer
3.338
965091AG1-374 GEN
Solar/Wind Harmer
26.876
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274760LEE CO EC;1U
Adder
8.264
274767LEE CO EC;8U
Adder
8.167
274682WAUKEGAN ;7U
Adder
15.786
274729ELWOOD EC;1P
Adder
14.355
274730ELWOOD EC;6P
Adder
14.355
274734ELWOOD EC;8P
Adder
14.355
274736ELWOOD EC;9P
Adder
14.355
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.852
3147666LOUISA
Solar/Wind Helper
1.093
238152AF2-075_GEN
Solar/Wind Helper
0.608
316447AC1-158 HLD
Solar/Wind Helper
2.79
316044AC1-158 PL1
Solar/Wind Helper
1.268
3142416OLDCHRC
Solar/Wind Helper
0.581
3142416OLDCHRC
Solar/Wind Helper
0.222
24386205FR-12G C
Solar/Wind Harmer
2.911
LAGNLTFEXP_LAGN->PJM
CLTF
20.349
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.582
TVALTFEXP_TVA->PJM
CLTF
10.64
NYPJM->LTFIMP_NY
CLTF
3.28
LGEELTFEXP_LGEE->PJM
CLTF
6.795
WECLTFEXP_WEC->PJM
CLTF
3.389
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.053
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.452
MECLTFEXP_MEC->PJM
CLTF
15.488
SIGELTFEXP_SIGE->PJM
CLTF
0.51
CPLELTFEXP_CPLE->PJM
CLTF
6.224
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.642
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 89.66 MW.

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.4 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4165.98
MW Contribution:
75.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.246
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.796
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.362
971329AH1-144 GEN
Solar/Wind Harmer
11.729
966391AG1-508 GEN
Solar/Wind Harmer
6.375
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
270069AE2-166 C O1
Solar/Wind Harmer
14.878
971313AH1-133 GEN
Solar/Wind Harmer
9.329
24734705WLF1G3
Adder
8.195
24734805WLF1G4
Adder
8.195
24734905WLF1G5
Adder
8.195
24735105WLF2G1
Adder
8.025
270399AC1-101 GEN
Solar/Wind Harmer
5.558
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.288
957241AF2-018 GEN
Solar/Wind Harmer
5.76
270053AF1-130 C
Solar/Wind Harmer
23.016
970281AG2-184 GEN
Solar/Wind Harmer
27.137
971981AH1-535 GEN
Solar/Wind Harmer
12.564
962211AG1-066 GEN
Solar/Wind Harmer
3.002
971061AG2-657 GEN
Solar/Wind Harmer
11.001
3429211JKCT 2G
Adder
11.881
339216AC1-074 GEN
Solar/Wind Harmer
1.645
972163AH1-664 GEN
Solar/Wind Harmer
9.75
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.311
270444AC2-157 GEN1
Solar/Wind Harmer
5.241
270445AC2-157 GEN2
Solar/Wind Harmer
5.241
25196108MFTGT2
Adder
1.427
25196108MFTGT2
Adder
1.325
944221AF1-090 GEN
Solar/Wind Harmer
10.032
25196408WSDLE3
Adder
8.087
25196308WSDLE2
Adder
8.016
25196208WSDLE1
Adder
7.996
25196708WSDLE6
Adder
7.976
25196508WSDLE4
Adder
7.775
253433AC1-085 GEN1
Solar/Wind Harmer
4.826
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
276668AB2-070 GEN1
Solar/Wind Harmer
1.998
276848AB2-070 GEN3
Solar/Wind Harmer
1.998
276849AB2-070 GEN2
Solar/Wind Harmer
1.998
270356AE2-297 GEN
Solar/Wind Harmer
4.149
253406AD2-031_GEN
Solar/Wind Harmer
1.147
963841AG1-237 GEN
Solar/Wind Harmer
9.765
270291AC1-194 GEN
Solar/Wind Harmer
4.541
946321AF1-296 GEN
Solar/Wind Harmer
9.308
274853TWINGROVE;U1
Solar/Wind Harmer
6.427
274854TWINGROVE;U2
Solar/Wind Harmer
6.292
270340AC2-060 GEN
Solar/Wind Harmer
2.689
276726Z2-087_GEN
Solar/Wind Harmer
7.027
959341AF2-225 GEN
Solar/Wind Harmer
13.331
972267AH1-718 GEN
Adder
3.691
274823ROCKFORD ;21
Adder
17.165
274744AC1-111 GEN8
Adder
4.874
274746AC1-111 G10
Adder
4.874
274728ELWOOD EC;5P
Adder
14.292
274731ELWOOD EC;2P
Adder
14.292
274733ELWOOD EC;3P
Adder
14.292
274735ELWOOD EC;4P
Adder
14.292
25306009OHH W.
Adder
2.505
274675JOLIET 29;7U
Adder
26.663
274675JOLIET 29;7U
Adder
7.65
315616AA1-038_C
Solar/Wind Helper
3.298
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.844
316164AC1-076 GEN
Solar/Wind Helper
1.178
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.09
24386405FR-21G C
Solar/Wind Harmer
2.093
24387005FR-3G C
Solar/Wind Harmer
1.925
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.164
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971277AH1-098 GEN
Solar/Wind Harmer
7.42
942671AE2-283 GEN
Solar/Wind Harmer
8.664
270013AE1-250 PV
Solar/Wind Harmer
3.249
970913AG2-568 GEN
Solar/Wind Harmer
9.345
971225AH1-072 GEN
Solar/Wind Harmer
2.731
971227AH1-073 GEN
Solar/Wind Harmer
2.731
24723005RIVRG1
Adder
22.967
24723105RIVRG2
Adder
22.967
942751AE2-291 GEN
Solar/Wind Harmer
10.376
966021AG1-471 GEN
Solar/Wind Harmer
5.755
971485AH1-239 GEN
Solar/Wind Harmer
8.501
339231AF1-038_GEN
Solar/Wind Harmer
1.919
964781AG1-341 GEN
Solar/Wind Harmer
10.975
339236AF1-050_GEN
Solar/Wind Harmer
1.873
942891AE2-308 GEN
Solar/Wind Harmer
10.182
964571AG1-320 GEN
Solar/Wind Harmer
8.191
971125AH1-004 GEN
Solar/Wind Harmer
3.992
970107AG2-081 GEN
Solar/Wind Harmer
2.994
972043AH1-570 GEN
Solar/Wind Harmer
2.477
972045AH1-571 GEN
Solar/Wind Harmer
1.981
927014AC1-188 GEN
Solar/Wind Harmer
1.529
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.577
971073AG2-665 GEN
Solar/Wind Harmer
7.349
970879AG2-548 GEN
Solar/Wind Harmer
1.068
25194408D.CRK1
Adder
6.944
25194508D.CRK3
Adder
1.298
945391AF1-204 GEN
Solar/Wind Harmer
12.73
276916AD2-100_GEN
Solar/Wind Harmer
19.171
276911AD2-131_GEN
Solar/Wind Harmer
3.875
276615X2-022 GEN
Solar/Wind Harmer
1.774
276838X2-022 GEN2
Solar/Wind Harmer
0.211
274880W4-005 GEN4
Solar/Wind Harmer
2.728
276174W4-005 GEN2
Solar/Wind Harmer
2.728
970241AG2-163 GEN
Solar/Wind Harmer
22.448
24728805RICHG1
Adder
3.39
24728905RICHG2
Adder
3.39
960251AF2-316 GEN
Solar/Wind Harmer
13.412
960201AF2-311 GEN
Solar/Wind Harmer
8.941
960611AF2-352 GEN
Solar/Wind Harmer
2.075
942111AE2-223 GEN
Solar/Wind Harmer
7.286
274764LEE CO EC;5U
Adder
8.248
274765LEE CO EC;6U
Adder
8.248
274762LEE CO EC;3U
Adder
8.229
274763LEE CO EC;4U
Adder
8.151
972235AH1-702 GEN1
Adder
2.222
972236AH1-702 GEN2
Adder
1.932
274683WAUKEGAN ;8U
Adder
18.436
274683WAUKEGAN ;8U
Adder
15.54
274696ROCKY RD ;4P
Adder
9.966
274695ROCKY RD ;2P
Adder
9.736
274693ROCKY RD ;1P
Adder
9.64
274697ROCKY RD ;3P
Adder
2.645
274674JOLIET 9 ;6U
Adder
13.386
3132123MT JACKSON
Solar/Wind Helper
1.391
966001AG1-469 GEN
Solar/Wind Helper
0.321
237061AD1-155 GEN
Solar/Wind Helper
1.65
316097T157 G90
Solar/Wind Helper
1.13
238147AE2-230_GEN1
Solar/Wind Helper
0.424
238148AE2-230_GEN2
Solar/Wind Helper
0.424
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.356
966871AG1-558 GEN
Solar/Wind Helper
0.307
316045AC1-158 PL2
Solar/Wind Helper
4.045
316450AC1-158 RIC
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.425
24387305FR-4G C
Solar/Wind Harmer
2.471
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.196
24684505SMG3
50/50
1.342
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.164
270173AC1-122 GEN
Solar/Wind Harmer
3.444
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
958131AF2-107 GEN
Solar/Wind Harmer
7.104
24735205WLF2G2
Adder
8.025
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.86
944971AF1-162 GEN
Solar/Wind Harmer
9.072
24723205RIVRG3
Adder
22.967
24686505CER G6
Adder
9.881
972203AH1-686 GEN
Adder
2.706
270331AC1-082 GEN3
Solar/Wind Harmer
0.513
964901AG1-354 GEN
Solar/Wind Harmer
15.496
339211AE2-254 GEN
Solar/Wind Harmer
1.561
339241AF1-083 GEN
Solar/Wind Harmer
1.716
960001AF2-291 GEN
Solar/Wind Harmer
3.117
3429241JKCT 3G
Adder
12.037
970653AG2-424 GEN
Solar/Wind Harmer
4.885
3429421JKCT 10G
Adder
8.408
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339221AD2-048_GEN
Solar/Wind Harmer
1.511
945681AF1-233 GEN
Solar/Wind Harmer
18.334
970091AG2-072 GEN
Adder
74.077
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.673
25196008MFTGT1
Adder
1.294
252516AE2-318_GEN
Solar/Wind Harmer
9.216
252510AF1-249 C
Solar/Wind Harmer
0.384
971073AG2-665 GEN
Solar/Wind Harmer
1.068
25194608D.CRK4
Adder
1.51
965911AG1-460 GEN
Solar/Wind Harmer
1.272
24728605AND G2
Adder
3.485
253316AC1-085 GEN3
Solar/Wind Harmer
7.603
946171AF1-282 GEN
Solar/Wind Harmer
9.081
276621W2-048 GEN
Solar/Wind Harmer
5.648
276686W4-005 GEN3
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
40.407
270222AC2-111 GEN
Solar/Wind Harmer
3.996
944031AF1-071 GEN
Solar/Wind Harmer
0.899
253398AE2-221_GEN2
Solar/Wind Harmer
4.059
276655WTG1_EQ
Solar/Wind Harmer
7.757
276656WTG2_EQ
Solar/Wind Harmer
1.027
939741AE1-205 GEN
Solar/Wind Harmer
17.775
274848CAMPGROVE;RU
Solar/Wind Harmer
5.733
274761LEE CO EC;2U
Adder
8.229
274766LEE CO EC;7U
Adder
8.132
274822ROCKFORD ;11
Adder
17.29
274828WAUKEGAN ;BP
Adder
9.664
274682WAUKEGAN ;7U
Adder
15.718
274745AC1-111 GEN9
Adder
4.874
274732ELWOOD EC;7P
Adder
14.292
274674JOLIET 9 ;6U
Adder
13.386
274676JOLIET 29;8U
Adder
26.663
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.232
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.627
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.304
316095T157 G97
Solar/Wind Helper
1.13
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.39
24385905FR-11G C
Solar/Wind Harmer
4.044
24386605FR-22G C
Solar/Wind Harmer
2.093
970823AG2-518 GEN
50/50
8.383
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.211
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.98
970563AG2-360 GEN
50/50
45.836
970417AG2-272 GEN
50/50
3.733
962751AG1-124 GEN
Solar/Wind Harmer
18.819
958121AF2-106 GEN
Solar/Wind Harmer
9.406
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.808
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270030AE2-140 GEN
Solar/Wind Harmer
30.922
270018AE2-047 C O1
Solar/Wind Harmer
1.821
960911AF2-382 GEN
Solar/Wind Harmer
10.95
270016AE1-250 BESS
Solar/Wind Harmer
3.249
971461AH1-227 GEN
Solar/Wind Harmer
7.006
970223AG2-152 GEN
Solar/Wind Harmer
17.663
972103AH1-617 GEN
Solar/Wind Harmer
25.844
24686405CER G5
Adder
9.803
270330AC1-082 GEN2
Solar/Wind Harmer
0.512
270329AC1-082 GEN1
Solar/Wind Harmer
0.512
972273AH1-721 GEN
Adder
89.361
24721905FLATG4
Adder
21.701
339255AE2-071 GEN
Solar/Wind Harmer
1.218
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.205
970093AG2-073 GEN
Solar/Wind Harmer
5.447
970653AG2-424 GEN
Solar/Wind Harmer
0.706
3429391JKCT 9G
Adder
8.408
971191AH1-055 GEN
Solar/Wind Harmer
18.847
970455AG2-298 GEN
Solar/Wind Harmer
3.522
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
972167AH1-666 GEN
Solar/Wind Harmer
7.773
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.928
270186AC1-089 GEN
Solar/Wind Harmer
5.824
270367AC2-061_GEN
Solar/Wind Harmer
3.006
252507AC2-088 GEN
Solar/Wind Harmer
1.668
25196008MFTGT1
Adder
1.253
252519AF1-045_GEN
Solar/Wind Harmer
3.354
970879AG2-548 GEN
Solar/Wind Harmer
7.349
25194608D.CRK4
Adder
1.51
252524AE2-267 GEN
Solar/Wind Harmer
1.443
25196608WSDLE5
Adder
7.856
970193AG2-126 GEN
Solar/Wind Harmer
13.702
942481AE2-261 GEN
Solar/Wind Harmer
27.253
957381AF2-032 GEN
Solar/Wind Harmer
1.822
24728705AND G3
Adder
7.288
24728505AND G1
Adder
3.485
253317AC1-085 GEN4
Solar/Wind Harmer
7.603
946181AF1-283 GEN
Solar/Wind Harmer
11.806
276785W4-005 GEN1
Solar/Wind Harmer
2.728
971993AH1-541 GEN
Solar/Wind Harmer
8.336
253394AE2-221_GEN
Solar/Wind Harmer
4.059
965931AG1-462 GEN
Solar/Wind Harmer
22.779
971087AG2-675 GEN
Solar/Wind Harmer
3.324
965091AG1-374 GEN
Solar/Wind Harmer
26.762
959611AF2-252 GEN
Solar/Wind Harmer
2.075
274760LEE CO EC;1U
Adder
8.229
274767LEE CO EC;8U
Adder
8.132
274682WAUKEGAN ;7U
Adder
15.718
274729ELWOOD EC;1P
Adder
14.292
274730ELWOOD EC;6P
Adder
14.292
274734ELWOOD EC;8P
Adder
14.292
274736ELWOOD EC;9P
Adder
14.292
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.847
3147666LOUISA
Solar/Wind Helper
1.09
238152AF2-075_GEN
Solar/Wind Helper
0.606
316447AC1-158 HLD
Solar/Wind Helper
2.781
316044AC1-158 PL1
Solar/Wind Helper
1.264
3142416OLDCHRC
Solar/Wind Helper
0.579
3142416OLDCHRC
Solar/Wind Helper
0.222
24386205FR-12G C
Solar/Wind Harmer
2.085
LAGNLTFEXP_LAGN->PJM
CLTF
20.287
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.539
TVALTFEXP_TVA->PJM
CLTF
10.609
NYPJM->LTFIMP_NY
CLTF
3.263
LGEELTFEXP_LGEE->PJM
CLTF
6.768
WECLTFEXP_WEC->PJM
CLTF
3.374
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.331
MECLTFEXP_MEC->PJM
CLTF
15.426
SIGELTFEXP_SIGE->PJM
CLTF
0.508
CPLELTFEXP_CPLE->PJM
CLTF
6.216
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.186
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 89.36 MW.

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.26 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4160.96
MW Contribution:
75.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.157
270583AD2-179 GEN
Solar/Wind Harmer
20.71
270214AC2-123 GEN
Solar/Wind Harmer
4.308
971277AH1-098 GEN
Solar/Wind Harmer
7.416
942671AE2-283 GEN
Solar/Wind Harmer
8.662
270013AE1-250 PV
Solar/Wind Harmer
3.247
970913AG2-568 GEN
Solar/Wind Harmer
9.332
971225AH1-072 GEN
Solar/Wind Harmer
2.728
971227AH1-073 GEN
Solar/Wind Harmer
2.728
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
942751AE2-291 GEN
Solar/Wind Harmer
10.374
966021AG1-471 GEN
Solar/Wind Harmer
5.747
971485AH1-239 GEN
Solar/Wind Harmer
8.488
339231AF1-038_GEN
Solar/Wind Harmer
1.916
964781AG1-341 GEN
Solar/Wind Harmer
10.959
339236AF1-050_GEN
Solar/Wind Harmer
1.871
942891AE2-308 GEN
Solar/Wind Harmer
10.165
964571AG1-320 GEN
Solar/Wind Harmer
8.178
971125AH1-004 GEN
Solar/Wind Harmer
3.985
970107AG2-081 GEN
Solar/Wind Harmer
2.988
972043AH1-570 GEN
Solar/Wind Harmer
2.472
972045AH1-571 GEN
Solar/Wind Harmer
1.978
927014AC1-188 GEN
Solar/Wind Harmer
1.526
962581AG1-107 GEN
Solar/Wind Harmer
4.724
961491AF2-440 GEN
Solar/Wind Harmer
1.963
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.565
25194408D.CRK1
Adder
6.93
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.33
970879AG2-548 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
12.706
276916AD2-100_GEN
Solar/Wind Harmer
19.136
276911AD2-131_GEN
Solar/Wind Harmer
3.867
276615X2-022 GEN
Solar/Wind Harmer
1.77
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.723
276174W4-005 GEN2
Solar/Wind Harmer
2.723
970241AG2-163 GEN
Solar/Wind Harmer
22.405
24728805RICHG1
Adder
3.383
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
13.37
960201AF2-311 GEN
Solar/Wind Harmer
8.913
960611AF2-352 GEN
Solar/Wind Harmer
2.071
942111AE2-223 GEN
Solar/Wind Harmer
7.272
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.795
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
971329AH1-144 GEN
Solar/Wind Harmer
11.722
966391AG1-508 GEN
Solar/Wind Harmer
6.371
270197AD1-017 GEN1
Solar/Wind Harmer
2.54
270069AE2-166 C O1
Solar/Wind Harmer
14.87
971313AH1-133 GEN
Solar/Wind Harmer
9.321
24734705WLF1G3
Adder
8.187
24734805WLF1G4
Adder
8.187
24734905WLF1G5
Adder
8.187
24735105WLF2G1
Adder
8.017
270399AC1-101 GEN
Solar/Wind Harmer
5.551
270400AC1-102 GEN
Solar/Wind Harmer
5.551
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
5.752
270053AF1-130 C
Solar/Wind Harmer
22.985
970281AG2-184 GEN
Solar/Wind Harmer
27.103
971981AH1-535 GEN
Solar/Wind Harmer
12.552
962211AG1-066 GEN
Solar/Wind Harmer
2.998
971061AG2-657 GEN
Solar/Wind Harmer
10.98
3429211JKCT 2G
Adder
11.861
339216AC1-074 GEN
Solar/Wind Harmer
1.642
972163AH1-664 GEN
Solar/Wind Harmer
9.732
972165AH1-665 GEN
Solar/Wind Harmer
7.785
971985AH1-537 GEN
Solar/Wind Harmer
17.275
270444AC2-157 GEN1
Solar/Wind Harmer
5.231
270445AC2-157 GEN2
Solar/Wind Harmer
5.231
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
944221AF1-090 GEN
Solar/Wind Harmer
10.014
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
25196508WSDLE4
Adder
7.759
253433AC1-085 GEN1
Solar/Wind Harmer
4.815
253432AC1-085 GEN2
Solar/Wind Harmer
0.242
276763AC1-053 GEN1
Solar/Wind Harmer
3.564
276764AC1-053 GEN2
Solar/Wind Harmer
3.564
276668AB2-070 GEN1
Solar/Wind Harmer
1.994
276848AB2-070 GEN3
Solar/Wind Harmer
1.994
276849AB2-070 GEN2
Solar/Wind Harmer
1.994
270356AE2-297 GEN
Solar/Wind Harmer
4.141
253406AD2-031_GEN
Solar/Wind Harmer
1.145
963841AG1-237 GEN
Solar/Wind Harmer
9.746
946321AF1-296 GEN
Solar/Wind Harmer
9.291
274853TWINGROVE;U1
Solar/Wind Harmer
6.415
274854TWINGROVE;U2
Solar/Wind Harmer
6.28
270291AC1-194 GEN
Solar/Wind Harmer
4.529
270340AC2-060 GEN
Solar/Wind Harmer
2.683
276726Z2-087_GEN
Solar/Wind Harmer
7.014
959341AF2-225 GEN
Solar/Wind Harmer
13.306
972267AH1-718 GEN
Adder
3.684
274823ROCKFORD ;21
Adder
17.132
274744AC1-111 GEN8
Adder
4.865
274746AC1-111 G10
Adder
4.865
274728ELWOOD EC;5P
Adder
14.264
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
274735ELWOOD EC;4P
Adder
14.264
25306009OHH W.
Adder
2.5
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
315616AA1-038_C
Solar/Wind Helper
3.297
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.089
24386405FR-21G C
Solar/Wind Harmer
2.088
24387005FR-3G C
Solar/Wind Harmer
1.921
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.195
24684505SMG3
50/50
1.341
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.157
270173AC1-122 GEN
Solar/Wind Harmer
3.443
316217AC1-145 GEN
Solar/Wind Harmer
4.241
316197AC1-042 GEN
Solar/Wind Harmer
3.215
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.466
270336AE1-100 GEN
Solar/Wind Harmer
2.749
943811AF1-049 GEN
Solar/Wind Harmer
5.692
958131AF2-107 GEN
Solar/Wind Harmer
7.102
24735205WLF2G2
Adder
8.017
971687AH1-348 GEN
Solar/Wind Harmer
1.358
971403AH1-188 GEN
Solar/Wind Harmer
18.836
944971AF1-162 GEN
Solar/Wind Harmer
9.06
24723205RIVRG3
Adder
22.932
24686505CER G6
Adder
9.865
972203AH1-686 GEN
Adder
2.702
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
964901AG1-354 GEN
Solar/Wind Harmer
15.473
339211AE2-254 GEN
Solar/Wind Harmer
1.559
339241AF1-083 GEN
Solar/Wind Harmer
1.713
960001AF2-291 GEN
Solar/Wind Harmer
3.11
3429241JKCT 3G
Adder
12.016
970653AG2-424 GEN
Solar/Wind Harmer
4.877
3429421JKCT 10G
Adder
8.393
943111AE2-339 GEN
Solar/Wind Harmer
0.882
339221AD2-048_GEN
Solar/Wind Harmer
1.508
945681AF1-233 GEN
Solar/Wind Harmer
18.298
970091AG2-072 GEN
Adder
73.941
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252516AE2-318_GEN
Solar/Wind Harmer
9.197
252510AF1-249 C
Solar/Wind Harmer
0.383
25194608D.CRK4
Adder
1.506
971073AG2-665 GEN
Solar/Wind Harmer
1.065
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
7.586
946171AF1-282 GEN
Solar/Wind Harmer
9.062
276621W2-048 GEN
Solar/Wind Harmer
5.637
276686W4-005 GEN3
Solar/Wind Harmer
2.723
963741AG1-226 GEN
Solar/Wind Harmer
40.329
270222AC2-111 GEN
Solar/Wind Harmer
3.988
944031AF1-071 GEN
Solar/Wind Harmer
0.897
253398AE2-221_GEN2
Solar/Wind Harmer
4.05
276655WTG1_EQ
Solar/Wind Harmer
7.743
276656WTG2_EQ
Solar/Wind Harmer
1.025
939741AE1-205 GEN
Solar/Wind Harmer
17.741
274848CAMPGROVE;RU
Solar/Wind Harmer
5.723
274761LEE CO EC;2U
Adder
8.213
274766LEE CO EC;7U
Adder
8.117
274822ROCKFORD ;11
Adder
17.258
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274745AC1-111 GEN9
Adder
4.865
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
274676JOLIET 29;8U
Adder
26.611
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.23
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.295
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
24385905FR-11G C
Solar/Wind Harmer
4.036
24386605FR-22G C
Solar/Wind Harmer
2.088
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.21
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.967
970563AG2-360 GEN
50/50
45.796
970417AG2-272 GEN
50/50
3.731
962751AG1-124 GEN
Solar/Wind Harmer
18.814
958121AF2-106 GEN
Solar/Wind Harmer
9.401
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.805
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.925
270030AE2-140 GEN
Solar/Wind Harmer
30.906
270018AE2-047 C O1
Solar/Wind Harmer
1.82
960911AF2-382 GEN
Solar/Wind Harmer
10.939
270016AE1-250 BESS
Solar/Wind Harmer
3.247
971461AH1-227 GEN
Solar/Wind Harmer
6.998
970223AG2-152 GEN
Solar/Wind Harmer
17.657
972103AH1-617 GEN
Solar/Wind Harmer
25.812
24686405CER G5
Adder
9.787
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
972273AH1-721 GEN
Adder
89.23
24721905FLATG4
Adder
21.662
339255AE2-071 GEN
Solar/Wind Harmer
1.216
339250AF1-203 GEN
Solar/Wind Harmer
0.626
339206AE1-143 GEN
Solar/Wind Harmer
2.202
970093AG2-073 GEN
Solar/Wind Harmer
5.438
970653AG2-424 GEN
Solar/Wind Harmer
0.705
3429391JKCT 9G
Adder
8.393
971191AH1-055 GEN
Solar/Wind Harmer
18.807
970455AG2-298 GEN
Solar/Wind Harmer
3.516
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
972167AH1-666 GEN
Solar/Wind Harmer
7.758
957541AF2-048 GEN
Solar/Wind Harmer
1.526
958171AF2-111 GEN
Solar/Wind Harmer
23.881
270186AC1-089 GEN
Solar/Wind Harmer
5.812
270367AC2-061_GEN
Solar/Wind Harmer
3
252507AC2-088 GEN
Solar/Wind Harmer
1.664
25196008MFTGT1
Adder
1.251
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
970879AG2-548 GEN
Solar/Wind Harmer
7.33
252524AE2-267 GEN
Solar/Wind Harmer
1.44
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
13.676
942481AE2-261 GEN
Solar/Wind Harmer
27.203
957381AF2-032 GEN
Solar/Wind Harmer
1.819
24728705AND G3
Adder
7.274
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
7.586
946181AF1-283 GEN
Solar/Wind Harmer
11.78
276785W4-005 GEN1
Solar/Wind Harmer
2.723
971993AH1-541 GEN
Solar/Wind Harmer
8.32
253394AE2-221_GEN
Solar/Wind Harmer
4.05
965931AG1-462 GEN
Solar/Wind Harmer
22.737
971087AG2-675 GEN
Solar/Wind Harmer
3.318
965091AG1-374 GEN
Solar/Wind Harmer
26.711
959611AF2-252 GEN
Solar/Wind Harmer
2.071
274760LEE CO EC;1U
Adder
8.213
274767LEE CO EC;8U
Adder
8.117
274682WAUKEGAN ;7U
Adder
15.687
274729ELWOOD EC;1P
Adder
14.264
274730ELWOOD EC;6P
Adder
14.264
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316447AC1-158 HLD
Solar/Wind Helper
2.777
316044AC1-158 PL1
Solar/Wind Helper
1.262
24386205FR-12G C
Solar/Wind Harmer
2.081
274764LEE CO EC;5U
Adder
8.233
274765LEE CO EC;6U
Adder
8.233
274762LEE CO EC;3U
Adder
8.213
274763LEE CO EC;4U
Adder
8.136
972235AH1-702 GEN1
Adder
2.217
972236AH1-702 GEN2
Adder
1.928
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274696ROCKY RD ;4P
Adder
9.947
274695ROCKY RD ;2P
Adder
9.717
274693ROCKY RD ;1P
Adder
9.622
274697ROCKY RD ;3P
Adder
2.64
274674JOLIET 9 ;6U
Adder
13.36
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.647
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
316450AC1-158 RIC
Solar/Wind Helper
0.337
24387305FR-4G C
Solar/Wind Harmer
2.467
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
TVALTFEXP_TVA->PJM
CLTF
10.596
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
CPLELTFEXP_CPLE->PJM
CLTF
6.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 89.23 MW.

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.94 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4149.41
MW Contribution:
75.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.244
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.796
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.357
971329AH1-144 GEN
Solar/Wind Harmer
11.725
966391AG1-508 GEN
Solar/Wind Harmer
6.373
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
270069AE2-166 C O1
Solar/Wind Harmer
14.876
971313AH1-133 GEN
Solar/Wind Harmer
9.325
24734705WLF1G3
Adder
8.191
24734805WLF1G4
Adder
8.191
24734905WLF1G5
Adder
8.191
24735105WLF2G1
Adder
8.021
270399AC1-101 GEN
Solar/Wind Harmer
5.554
270400AC1-102 GEN
Solar/Wind Harmer
5.554
941621AE2-160 GEN
Adder
4.283
957241AF2-018 GEN
Solar/Wind Harmer
5.755
270053AF1-130 C
Solar/Wind Harmer
22.996
970281AG2-184 GEN
Solar/Wind Harmer
27.117
971981AH1-535 GEN
Solar/Wind Harmer
12.558
962211AG1-066 GEN
Solar/Wind Harmer
3
971061AG2-657 GEN
Solar/Wind Harmer
10.986
3429211JKCT 2G
Adder
11.868
339216AC1-074 GEN
Solar/Wind Harmer
1.643
972163AH1-664 GEN
Solar/Wind Harmer
9.738
972165AH1-665 GEN
Solar/Wind Harmer
7.79
971985AH1-537 GEN
Solar/Wind Harmer
17.286
270444AC2-157 GEN1
Solar/Wind Harmer
5.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.235
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.323
944221AF1-090 GEN
Solar/Wind Harmer
10.021
25196408WSDLE3
Adder
8.076
25196308WSDLE2
Adder
8.005
25196208WSDLE1
Adder
7.985
25196708WSDLE6
Adder
7.965
25196508WSDLE4
Adder
7.765
253433AC1-085 GEN1
Solar/Wind Harmer
4.819
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.567
276764AC1-053 GEN2
Solar/Wind Harmer
3.567
276668AB2-070 GEN1
Solar/Wind Harmer
1.995
276848AB2-070 GEN3
Solar/Wind Harmer
1.995
276849AB2-070 GEN2
Solar/Wind Harmer
1.995
270356AE2-297 GEN
Solar/Wind Harmer
4.144
253406AD2-031_GEN
Solar/Wind Harmer
1.146
963841AG1-237 GEN
Solar/Wind Harmer
9.753
946321AF1-296 GEN
Solar/Wind Harmer
9.297
274853TWINGROVE;U1
Solar/Wind Harmer
6.419
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.16
270583AD2-179 GEN
Solar/Wind Harmer
20.716
270214AC2-123 GEN
Solar/Wind Harmer
4.31
971277AH1-098 GEN
Solar/Wind Harmer
7.418
942671AE2-283 GEN
Solar/Wind Harmer
8.665
270013AE1-250 PV
Solar/Wind Harmer
3.249
970913AG2-568 GEN
Solar/Wind Harmer
9.337
971225AH1-072 GEN
Solar/Wind Harmer
2.729
971227AH1-073 GEN
Solar/Wind Harmer
2.729
24723005RIVRG1
Adder
22.944
24723105RIVRG2
Adder
22.944
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.751
971485AH1-239 GEN
Solar/Wind Harmer
8.494
339231AF1-038_GEN
Solar/Wind Harmer
1.917
964781AG1-341 GEN
Solar/Wind Harmer
10.966
339236AF1-050_GEN
Solar/Wind Harmer
1.872
942891AE2-308 GEN
Solar/Wind Harmer
10.171
964571AG1-320 GEN
Solar/Wind Harmer
8.183
971125AH1-004 GEN
Solar/Wind Harmer
3.987
970107AG2-081 GEN
Solar/Wind Harmer
2.99
972043AH1-570 GEN
Solar/Wind Harmer
2.474
972045AH1-571 GEN
Solar/Wind Harmer
1.979
927014AC1-188 GEN
Solar/Wind Harmer
1.527
962581AG1-107 GEN
Solar/Wind Harmer
4.728
961491AF2-440 GEN
Solar/Wind Harmer
1.965
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.569
25194408D.CRK1
Adder
6.935
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.336
970879AG2-548 GEN
Solar/Wind Harmer
1.066
945391AF1-204 GEN
Solar/Wind Harmer
12.715
276916AD2-100_GEN
Solar/Wind Harmer
19.15
276911AD2-131_GEN
Solar/Wind Harmer
3.87
276615X2-022 GEN
Solar/Wind Harmer
1.772
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.725
276174W4-005 GEN2
Solar/Wind Harmer
2.725
970241AG2-163 GEN
Solar/Wind Harmer
22.421
24728805RICHG1
Adder
3.386
24728905RICHG2
Adder
3.386
960251AF2-316 GEN
Solar/Wind Harmer
13.38
960201AF2-311 GEN
Solar/Wind Harmer
8.92
960611AF2-352 GEN
Solar/Wind Harmer
2.072
942111AE2-223 GEN
Solar/Wind Harmer
7.277
274764LEE CO EC;5U
Adder
8.239
274765LEE CO EC;6U
Adder
8.239
274762LEE CO EC;3U
Adder
8.219
274763LEE CO EC;4U
Adder
8.142
972235AH1-702 GEN1
Adder
2.219
972236AH1-702 GEN2
Adder
1.93
274683WAUKEGAN ;8U
Adder
18.414
274683WAUKEGAN ;8U
Adder
15.522
274696ROCKY RD ;4P
Adder
9.954
274695ROCKY RD ;2P
Adder
9.725
274693ROCKY RD ;1P
Adder
9.629
274697ROCKY RD ;3P
Adder
2.642
274674JOLIET 9 ;6U
Adder
13.37
3132123MT JACKSON
Solar/Wind Helper
1.389
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.646
316097T157 G90
Solar/Wind Helper
1.127
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.036
316450AC1-158 RIC
Solar/Wind Helper
0.336
24387305FR-4G C
Solar/Wind Harmer
2.468
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.196
24684505SMG3
50/50
1.342
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.16
270173AC1-122 GEN
Solar/Wind Harmer
3.444
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
958131AF2-107 GEN
Solar/Wind Harmer
7.106
24735205WLF2G2
Adder
8.021
971687AH1-348 GEN
Solar/Wind Harmer
1.358
971403AH1-188 GEN
Solar/Wind Harmer
18.845
944971AF1-162 GEN
Solar/Wind Harmer
9.064
24723205RIVRG3
Adder
22.944
24686505CER G6
Adder
9.87
972203AH1-686 GEN
Adder
2.703
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
964901AG1-354 GEN
Solar/Wind Harmer
15.482
339211AE2-254 GEN
Solar/Wind Harmer
1.56
339241AF1-083 GEN
Solar/Wind Harmer
1.714
960001AF2-291 GEN
Solar/Wind Harmer
3.112
3429241JKCT 3G
Adder
12.024
970653AG2-424 GEN
Solar/Wind Harmer
4.88
3429421JKCT 10G
Adder
8.399
943111AE2-339 GEN
Solar/Wind Harmer
0.882
339221AD2-048_GEN
Solar/Wind Harmer
1.509
945681AF1-233 GEN
Solar/Wind Harmer
18.311
970091AG2-072 GEN
Adder
73.991
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
70.578
25196008MFTGT1
Adder
1.293
252516AE2-318_GEN
Solar/Wind Harmer
9.203
252510AF1-249 C
Solar/Wind Harmer
0.383
25194608D.CRK4
Adder
1.508
971073AG2-665 GEN
Solar/Wind Harmer
1.066
965911AG1-460 GEN
Solar/Wind Harmer
1.27
24728605AND G2
Adder
3.48
253316AC1-085 GEN3
Solar/Wind Harmer
7.592
946171AF1-282 GEN
Solar/Wind Harmer
9.068
276621W2-048 GEN
Solar/Wind Harmer
5.641
276686W4-005 GEN3
Solar/Wind Harmer
2.725
963741AG1-226 GEN
Solar/Wind Harmer
40.358
270222AC2-111 GEN
Solar/Wind Harmer
3.991
944031AF1-071 GEN
Solar/Wind Harmer
0.898
253398AE2-221_GEN2
Solar/Wind Harmer
4.053
276655WTG1_EQ
Solar/Wind Harmer
7.748
276656WTG2_EQ
Solar/Wind Harmer
1.026
939741AE1-205 GEN
Solar/Wind Harmer
17.754
274848CAMPGROVE;RU
Solar/Wind Harmer
5.727
274761LEE CO EC;2U
Adder
8.219
274766LEE CO EC;7U
Adder
8.123
274822ROCKFORD ;11
Adder
17.27
274828WAUKEGAN ;BP
Adder
9.652
274682WAUKEGAN ;7U
Adder
15.699
274745AC1-111 GEN9
Adder
4.868
274732ELWOOD EC;7P
Adder
14.275
274674JOLIET 9 ;6U
Adder
13.37
274676JOLIET 29;8U
Adder
26.631
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
315821AE2-092 GEN
Solar/Wind Helper
3.228
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.293
316095T157 G97
Solar/Wind Helper
1.127
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
24385905FR-11G C
Solar/Wind Harmer
4.039
24386605FR-22G C
Solar/Wind Harmer
2.09
274854TWINGROVE;U2
Solar/Wind Harmer
6.285
270291AC1-194 GEN
Solar/Wind Harmer
4.532
270340AC2-060 GEN
Solar/Wind Harmer
2.685
276726Z2-087_GEN
Solar/Wind Harmer
7.019
959341AF2-225 GEN
Solar/Wind Harmer
13.316
972267AH1-718 GEN
Adder
3.687
274823ROCKFORD ;21
Adder
17.145
274744AC1-111 GEN8
Adder
4.868
274746AC1-111 G10
Adder
4.868
274728ELWOOD EC;5P
Adder
14.275
274731ELWOOD EC;2P
Adder
14.275
274733ELWOOD EC;3P
Adder
14.275
274735ELWOOD EC;4P
Adder
14.275
25306009OHH W.
Adder
2.502
274675JOLIET 29;7U
Adder
26.631
274675JOLIET 29;7U
Adder
7.641
315616AA1-038_C
Solar/Wind Helper
3.296
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.842
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.266
316468AD1-105 GEN
Solar/Wind Helper
1.088
24386405FR-21G C
Solar/Wind Harmer
2.09
24387005FR-3G C
Solar/Wind Harmer
1.922
970823AG2-518 GEN
50/50
8.382
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.211
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.973
970563AG2-360 GEN
50/50
45.815
970417AG2-272 GEN
50/50
3.733
962751AG1-124 GEN
Solar/Wind Harmer
18.82
958121AF2-106 GEN
Solar/Wind Harmer
9.404
943031AE2-326 GEN
Solar/Wind Harmer
6.783
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.809
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.931
270030AE2-140 GEN
Solar/Wind Harmer
30.919
270018AE2-047 C O1
Solar/Wind Harmer
1.821
960911AF2-382 GEN
Solar/Wind Harmer
10.944
270016AE1-250 BESS
Solar/Wind Harmer
3.249
971461AH1-227 GEN
Solar/Wind Harmer
7.001
970223AG2-152 GEN
Solar/Wind Harmer
17.666
972103AH1-617 GEN
Solar/Wind Harmer
25.825
24686405CER G5
Adder
9.792
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
972273AH1-721 GEN
Adder
89.284
24721905FLATG4
Adder
21.675
339255AE2-071 GEN
Solar/Wind Harmer
1.217
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.203
970093AG2-073 GEN
Solar/Wind Harmer
5.442
970653AG2-424 GEN
Solar/Wind Harmer
0.706
3429391JKCT 9G
Adder
8.399
971191AH1-055 GEN
Solar/Wind Harmer
18.819
970455AG2-298 GEN
Solar/Wind Harmer
3.519
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
972167AH1-666 GEN
Solar/Wind Harmer
7.764
957541AF2-048 GEN
Solar/Wind Harmer
1.527
958171AF2-111 GEN
Solar/Wind Harmer
23.897
270186AC1-089 GEN
Solar/Wind Harmer
5.816
270367AC2-061_GEN
Solar/Wind Harmer
3.002
252507AC2-088 GEN
Solar/Wind Harmer
1.666
25196008MFTGT1
Adder
1.252
252519AF1-045_GEN
Solar/Wind Harmer
3.349
25194608D.CRK4
Adder
1.508
970879AG2-548 GEN
Solar/Wind Harmer
7.336
252524AE2-267 GEN
Solar/Wind Harmer
1.441
25196608WSDLE5
Adder
7.845
970193AG2-126 GEN
Solar/Wind Harmer
13.686
942481AE2-261 GEN
Solar/Wind Harmer
27.222
957381AF2-032 GEN
Solar/Wind Harmer
1.82
24728705AND G3
Adder
7.279
24728505AND G1
Adder
3.48
253317AC1-085 GEN4
Solar/Wind Harmer
7.592
946181AF1-283 GEN
Solar/Wind Harmer
11.789
276785W4-005 GEN1
Solar/Wind Harmer
2.725
971993AH1-541 GEN
Solar/Wind Harmer
8.326
253394AE2-221_GEN
Solar/Wind Harmer
4.053
965931AG1-462 GEN
Solar/Wind Harmer
22.754
971087AG2-675 GEN
Solar/Wind Harmer
3.32
965091AG1-374 GEN
Solar/Wind Harmer
26.73
959611AF2-252 GEN
Solar/Wind Harmer
2.072
274760LEE CO EC;1U
Adder
8.219
274767LEE CO EC;8U
Adder
8.123
274682WAUKEGAN ;7U
Adder
15.699
274729ELWOOD EC;1P
Adder
14.275
274730ELWOOD EC;6P
Adder
14.275
274734ELWOOD EC;8P
Adder
14.275
274736ELWOOD EC;9P
Adder
14.275
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.844
3147666LOUISA
Solar/Wind Helper
1.088
238152AF2-075_GEN
Solar/Wind Helper
0.604
316447AC1-158 HLD
Solar/Wind Helper
2.775
316044AC1-158 PL1
Solar/Wind Helper
1.261
24386205FR-12G C
Solar/Wind Harmer
2.082
LAGNLTFEXP_LAGN->PJM
CLTF
20.273
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.54
TVALTFEXP_TVA->PJM
CLTF
10.603
NYPJM->LTFIMP_NY
CLTF
3.251
LGEELTFEXP_LGEE->PJM
CLTF
6.761
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.367
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.302
MECLTFEXP_MEC->PJM
CLTF
15.41
SIGELTFEXP_SIGE->PJM
CLTF
0.508
CPLELTFEXP_CPLE->PJM
CLTF
6.22
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.073
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 89.28 MW.

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.32 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6590.12
MW Contribution:
85.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.938
957241AF2-018 GEN
Solar/Wind Harmer
7.557
270053AF1-130 C
Solar/Wind Harmer
30.195
270399AC1-101 GEN
Solar/Wind Harmer
7.142
270400AC1-102 GEN
Solar/Wind Harmer
7.142
941621AE2-160 GEN
Adder
5.016
970281AG2-184 GEN
Solar/Wind Harmer
31.268
971313AH1-133 GEN
Solar/Wind Harmer
8.781
962211AG1-066 GEN
Solar/Wind Harmer
3.415
24734705WLF1G3
Adder
7.988
24734805WLF1G4
Adder
7.988
24734905WLF1G5
Adder
7.988
971061AG2-657 GEN
Solar/Wind Harmer
12.335
24735105WLF2G1
Adder
7.848
966391AG1-508 GEN
Solar/Wind Harmer
4.607
971985AH1-537 GEN
Solar/Wind Harmer
23.357
971331AH1-145 GEN
Solar/Wind Harmer
11.822
971329AH1-144 GEN
Solar/Wind Harmer
7.552
270444AC2-157 GEN1
Solar/Wind Harmer
7.062
270445AC2-157 GEN2
Solar/Wind Harmer
7.062
971981AH1-535 GEN
Solar/Wind Harmer
12.497
24386405FR-21G C
Solar/Wind Harmer
5.279
24387005FR-3G C
Solar/Wind Harmer
4.855
963841AG1-237 GEN
Solar/Wind Harmer
13.411
946581AF1-322 GEN
Solar/Wind Harmer
12.536
24691005MDL-2G C
Solar/Wind Harmer
4.53
274775LINCOLN ;6U
Adder
7.555
274776LINCOLN ;7U
Adder
7.555
274777LINCOLN ;8U
Adder
7.555
944221AF1-090 GEN
Solar/Wind Harmer
13.317
276668AB2-070 GEN1
Solar/Wind Harmer
2.697
276848AB2-070 GEN3
Solar/Wind Harmer
2.697
276849AB2-070 GEN2
Solar/Wind Harmer
2.697
276763AC1-053 GEN1
Solar/Wind Harmer
4.814
276764AC1-053 GEN2
Solar/Wind Harmer
4.814
274853TWINGROVE;U1
Solar/Wind Harmer
8.769
274854TWINGROVE;U2
Solar/Wind Harmer
8.585
276726Z2-087_GEN
Solar/Wind Harmer
9.623
959341AF2-225 GEN
Solar/Wind Harmer
18.256
274863CRW1-WTG
Solar/Wind Harmer
6.788
243186AF1-051 GEN
50/50
13.022
24721705FLATG2
50/50
43.628
24723005RIVRG1
Adder
35.405
24723105RIVRG2
Adder
35.405
970913AG2-568 GEN
Solar/Wind Harmer
10.639
24728205BUCHG1
Adder
6.758
971225AH1-072 GEN
Solar/Wind Harmer
2.946
971227AH1-073 GEN
Solar/Wind Harmer
2.946
270214AC2-123 GEN
Solar/Wind Harmer
3.099
971277AH1-098 GEN
Solar/Wind Harmer
5.287
927014AC1-188 GEN
Solar/Wind Harmer
1.995
24387305FR-4G C
Solar/Wind Harmer
6.235
966841AG1-555 GEN
Solar/Wind Harmer
3.081
945391AF1-204 GEN
Solar/Wind Harmer
17.098
970241AG2-163 GEN
Solar/Wind Harmer
30.673
270180AB1-006 GEN1
Solar/Wind Harmer
8.812
24697605MDL-3G C
Solar/Wind Harmer
4.516
24755605MDL-5G
Solar/Wind Harmer
2.954
24697905MDL-4G C
Solar/Wind Harmer
2.811
270181AB1-006 GEN2
Solar/Wind Harmer
0.876
945421AF1-207 GEN
Solar/Wind Harmer
17.195
957841AF2-078 GEN
Solar/Wind Harmer
7.402
270583AD2-179 GEN
Solar/Wind Harmer
12.237
274770LINCOLN ;1U
Adder
7.555
274771LINCOLN ;2U
Adder
7.555
274880W4-005 GEN4
Solar/Wind Harmer
3.683
276174W4-005 GEN2
Solar/Wind Harmer
3.683
276916AD2-100_GEN
Solar/Wind Harmer
25.572
276911AD2-131_GEN
Solar/Wind Harmer
5.168
276615X2-022 GEN
Solar/Wind Harmer
2.385
276838X2-022 GEN2
Solar/Wind Harmer
0.283
960611AF2-352 GEN
Solar/Wind Harmer
2.831
942111AE2-223 GEN
Solar/Wind Harmer
9.977
276897AD1-100 C
Solar/Wind Harmer
56.428
962691AG1-118 GEN
Solar/Wind Harmer
36.394
274696ROCKY RD ;4P
Adder
13.825
274695ROCKY RD ;2P
Adder
13.506
274693ROCKY RD ;1P
Adder
13.373
274697ROCKY RD ;3P
Adder
3.669
274674JOLIET 9 ;6U
Adder
18.672
274683WAUKEGAN ;8U
Adder
25.548
274683WAUKEGAN ;8U
Adder
21.536
972235AH1-702 GEN1
Adder
3.053
972236AH1-702 GEN2
Adder
2.655
274764LEE CO EC;5U
Adder
11.292
274765LEE CO EC;6U
Adder
11.292
274762LEE CO EC;3U
Adder
11.266
274763LEE CO EC;4U
Adder
11.16
237043AE2-125 C
Solar/Wind Helper
0.181
23585401KL_K28_T16
Solar/Wind Helper
1.305
23751201ROTHROCK
Solar/Wind Helper
0.749
254304AE2-114 C
Solar/Wind Helper
0.216
254305AE2-115 C
Solar/Wind Helper
0.216
962101AG1-054 GEN
Solar/Wind Helper
0.644
235054AD2-180 GEN
Solar/Wind Helper
1.728
241967AE2-285_GEN
Solar/Wind Helper
0.629
241801AE1-079 GEN
Solar/Wind Helper
0.246
238117U2-030
Solar/Wind Helper
0.291
20083426SW_E13_K22
Solar/Wind Helper
0.055
235531U2-073 GEN
Solar/Wind Helper
2.761
946071AF1-272 GEN
Solar/Wind Helper
2.663
20088826HIGHLAND
Solar/Wind Helper
0.88
203818AF1-086 GEN
Solar/Wind Helper
1.65
203961AE2-224 GEN
Solar/Wind Helper
2.354
946381AF1-302 GEN
Solar/Wind Helper
0.217
203853AF1-134 C O1
Solar/Wind Helper
0.466
203946AE2-131 C
Solar/Wind Helper
0.461
203804AE2-113_GEN
Solar/Wind Helper
1.698
940863AE2-074 GEN
Solar/Wind Helper
0.444
203954AE2-126 C
Solar/Wind Helper
0.458
203835AF1-098 GEN
Solar/Wind Helper
1.78
24289405MTG1
50/50
11.749
243186AF1-051 GEN
50/50
13.022
24318705GVG2
50/50
12.071
24721805FLATG3
50/50
2.938
962761AG1-125 GEN
Solar/Wind Harmer
67.342
970149AG2-104 GEN
Solar/Wind Harmer
41.584
970155AG2-107 GEN
Solar/Wind Harmer
29.364
24723205RIVRG3
Adder
35.405
972203AH1-686 GEN
Adder
4.304
24686505CER G6
Adder
15.123
944971AF1-162 GEN
Solar/Wind Harmer
11.902
971403AH1-188 GEN
Solar/Wind Harmer
23.698
270331AC1-082 GEN3
Solar/Wind Harmer
0.791
960001AF2-291 GEN
Solar/Wind Harmer
4.817
24728305BUCHG2
Adder
6.758
971687AH1-348 GEN
Solar/Wind Harmer
1.473
24735205WLF2G2
Adder
7.848
970091AG2-072 GEN
Adder
102.767
24385905FR-11G C
Solar/Wind Harmer
10.201
24386605FR-22G C
Solar/Wind Harmer
5.279
963741AG1-226 GEN
Solar/Wind Harmer
55.212
24791305MDL-5G
Solar/Wind Harmer
2.954
24289405MTG1
50/50
11.749
24318705GVG2
50/50
12.071
24722005FLATG5
50/50
2.938
24721905FLATG4
50/50
53.66
962771AG1-126 GEN
Solar/Wind Harmer
67.342
970153AG2-106 GEN
Solar/Wind Harmer
29.364
24686405CER G5
Adder
15.004
270330AC1-082 GEN2
Solar/Wind Harmer
0.789
270329AC1-082 GEN1
Solar/Wind Harmer
0.789
960911AF2-382 GEN
Solar/Wind Harmer
11.34
972103AH1-617 GEN
Solar/Wind Harmer
29.779
274864CRW2-WTG
Solar/Wind Harmer
6.788
970169AG2-114 GEN
Solar/Wind Harmer
12.163
959141AF2-205 GEN
Solar/Wind Harmer
7.348
970833AG2-524 GEN
Solar/Wind Harmer
10.601
970833AG2-524 GEN
Solar/Wind Harmer
4.931
274744AC1-111 GEN8
Adder
6.785
274746AC1-111 G10
Adder
6.785
958391AF2-133 GEN
Solar/Wind Harmer
11.004
972228AH1-698 GEN2
Adder
4.493
972227AH1-698 GEN1
Adder
3.164
274728ELWOOD EC;5P
Adder
19.933
274731ELWOOD EC;2P
Adder
19.933
274733ELWOOD EC;3P
Adder
19.933
274735ELWOOD EC;4P
Adder
19.933
274675JOLIET 29;7U
Adder
37.198
274675JOLIET 29;7U
Adder
35.87
274687WILL CNTY;4U
Adder
33.865
274687WILL CNTY;4U
Adder
33.865
274823ROCKFORD ;21
Adder
23.605
274800UNIV PARK;3U
Adder
7.06
274801UNIV PARK;4U
Adder
7.06
274827FISK ;RP
Adder
9.392
972267AH1-718 GEN
Adder
5.041
23750501ELLIOTTS
Solar/Wind Helper
0.679
23652301WDPWR_K20
Solar/Wind Helper
0.146
241997AF1-093 GEN
Solar/Wind Helper
0.252
241985AE1-237 GEN
Solar/Wind Helper
0.246
241982AE2-343 S C
Solar/Wind Helper
0.221
23750701CROSSCHOOL
Solar/Wind Helper
1.209
203955AF1-039 C O1
Solar/Wind Helper
0.373
238118U2-030_1
Solar/Wind Helper
0.291
20089126CSLMN_L13
Solar/Wind Helper
0.591
20089226LOOKOUT
Solar/Wind Helper
0.59
20088926STNY CRK
Solar/Wind Helper
0.806
203940AF1-140 C
Solar/Wind Helper
0.388
20094526CT_V3-030
Solar/Wind Helper
0.462
20088626ARWF_N39
Solar/Wind Helper
1.182
203846AF2-130 C
Solar/Wind Helper
0.443
20334926Z1-069 C
Solar/Wind Helper
1.308
926823AC1-168 GEN
Solar/Wind Harmer
0.606
972207SS24-0001
Solar/Wind Harmer
26.861
274773LINCOLN ;4U
Adder
7.555
274774LINCOLN ;5U
Adder
7.555
276686W4-005 GEN3
Solar/Wind Harmer
3.683
276621W2-048 GEN
Solar/Wind Harmer
7.596
940581AE2-045 GEN
Solar/Wind Harmer
12.418
971605AH1-302 GEN
Solar/Wind Harmer
10.618
965911AG1-460 GEN
Solar/Wind Harmer
1.699
276655WTG1_EQ
Solar/Wind Harmer
10.623
276656WTG2_EQ
Solar/Wind Harmer
1.406
939741AE1-205 GEN
Solar/Wind Harmer
24.341
939401AE1-172 GEN
Solar/Wind Harmer
16.947
941551AE2-152 GEN
Solar/Wind Harmer
5.509
274871GR RIDGE ;2U
Solar/Wind Harmer
9.337
274847GR RIDGE ;BU
Solar/Wind Harmer
6.14
274745AC1-111 GEN9
Adder
6.785
971997AH1-543 GEN
Solar/Wind Harmer
19.104
274674JOLIET 9 ;6U
Adder
18.672
274732ELWOOD EC;7P
Adder
19.933
274682WAUKEGAN ;7U
Adder
21.789
274676JOLIET 29;8U
Adder
37.198
274828WAUKEGAN ;BP
Adder
13.392
274822ROCKFORD ;11
Adder
23.778
274761LEE CO EC;2U
Adder
11.266
274766LEE CO EC;7U
Adder
11.133
274802UNIV PARK;5U
Adder
6.986
238185AF2-356 C
Solar/Wind Helper
2.23
254303AC2-168 GEN
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.252
20089026BF_G21_K23
Solar/Wind Helper
0.468
20084626FORWARD
Solar/Wind Helper
0.35
238120AE2-309 GEN
Solar/Wind Helper
0.432
238126S14_GEN_1
Solar/Wind Helper
0.686
964201AG1-281 GEN
Solar/Wind Helper
0.472
23751101LEADS_P59
Solar/Wind Helper
1.885
20091526CHSTN_FL
Solar/Wind Helper
0.569
20090526Q36
Solar/Wind Helper
1
203952AE2-129 C
Solar/Wind Helper
0.461
203855AF2-088 C
Solar/Wind Helper
0.149
238109AE1-109 GEN2
Solar/Wind Helper
0.086
203830AF1-094 GEN
Solar/Wind Helper
0.449
203979AG1-198 GEN
Solar/Wind Helper
0.27
961971AG1-040 GEN
Solar/Wind Helper
0.447
203947AF1-006 C
Solar/Wind Helper
0.483
971461AH1-227 GEN
Solar/Wind Harmer
7.556
971191AH1-055 GEN
Solar/Wind Harmer
27.281
270346AE1-212 GEN
Solar/Wind Harmer
12.339
943031AE2-326 GEN
Solar/Wind Harmer
4.878
957541AF2-048 GEN
Solar/Wind Harmer
1.995
24386205FR-12G C
Solar/Wind Harmer
5.26
970193AG2-126 GEN
Solar/Wind Harmer
18.403
24690905MDL-1G C
Solar/Wind Harmer
9.836
970781AG2-491 GEN
Solar/Wind Harmer
12.252
958121AF2-106 GEN
Solar/Wind Harmer
5.546
274772LINCOLN ;3U
Adder
7.555
276785W4-005 GEN1
Solar/Wind Harmer
3.683
971993AH1-541 GEN
Solar/Wind Harmer
11.253
942481AE2-261 GEN
Solar/Wind Harmer
36.404
957381AF2-032 GEN
Solar/Wind Harmer
2.435
965091AG1-374 GEN
Solar/Wind Harmer
36.515
959611AF2-252 GEN
Solar/Wind Harmer
2.831
970707AG2-453 GEN
Solar/Wind Harmer
34.064
939351AE1-166 GEN
Solar/Wind Harmer
7.204
972259AH1-714 GEN
Adder
23.175
943121AE2-341 GEN
Solar/Wind Harmer
18.219
943591AF1-030 GEN
Solar/Wind Harmer
12.146
972273AH1-721 GEN
Adder
101.006
274729ELWOOD EC;1P
Adder
19.933
274730ELWOOD EC;6P
Adder
19.933
274734ELWOOD EC;8P
Adder
19.933
274736ELWOOD EC;9P
Adder
19.933
274682WAUKEGAN ;7U
Adder
21.789
274676JOLIET 29;8U
Adder
35.87
972038AH1-567 GEN2
Adder
0.442
274760LEE CO EC;1U
Adder
11.266
274767LEE CO EC;8U
Adder
11.133
274826FISK ;BP
Adder
13.253
237048AF1-022 C
Solar/Wind Helper
0.199
237046AF1-021 C
Solar/Wind Helper
0.345
235058AG1-386 C
Solar/Wind Helper
0.46
23562501BACKB
Solar/Wind Helper
0.911
202652Y1-033 WT C
Solar/Wind Helper
0.565
964991AG1-363 GEN
Solar/Wind Helper
3.718
238127S14_GEN_2
Solar/Wind Helper
0.686
20092526R32
Solar/Wind Helper
1.14
20303426NA_O38_P22
Solar/Wind Helper
0.969
203993AD2-133_GEN1
Solar/Wind Helper
1
203854AF2-039 C
Solar/Wind Helper
0.309
238108AE1-109 GEN1
Solar/Wind Helper
0.086
238110AE1-109 GEN3
Solar/Wind Helper
0.086
20398826ARMNA MT
Solar/Wind Helper
1.443
962511AG1-100 GEN
Solar/Wind Helper
0.445
941421AE2-139 GEN
Solar/Wind Helper
2.224
LAGNLTFEXP_LAGN->PJM
CLTF
23.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.518
TVALTFEXP_TVA->PJM
CLTF
11.786
NYPJM->LTFIMP_NY
CLTF
5.358
LGEELTFEXP_LGEE->PJM
CLTF
8.414
WECLTFEXP_WEC->PJM
CLTF
4.631
AG2-052LTFEXP_AG2-052->PJM
LTF
0.281
AH1-155LTFEXP_AH1-155->PJM
LTF
0.421
CBM West 1LTFEXP_CBM-W1->PJM
CBM
149.868
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.575
MECLTFEXP_MEC->PJM
CLTF
20.238
SIGELTFEXP_SIGE->PJM
CLTF
0.64
CPLELTFEXP_CPLE->PJM
CLTF
6.948
CBM West 2LTFEXP_CBM-W2->PJM
CBM
158.57
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 101.01 MW.

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.27 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6477.04
MW Contribution:
96.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
7.699
270053AF1-130 C
Solar/Wind Harmer
30.765
270399AC1-101 GEN
Solar/Wind Harmer
7.281
270400AC1-102 GEN
Solar/Wind Harmer
7.281
970281AG2-184 GEN
Solar/Wind Harmer
32.719
971985AH1-537 GEN
Solar/Wind Harmer
27.788
941621AE2-160 GEN
Adder
5.034
962211AG1-066 GEN
Solar/Wind Harmer
3.649
971313AH1-133 GEN
Solar/Wind Harmer
8.798
972163AH1-664 GEN
Solar/Wind Harmer
14.536
972165AH1-665 GEN
Solar/Wind Harmer
11.629
339216AC1-074 GEN
Solar/Wind Harmer
2.394
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
3429211JKCT 2G
Adder
16.597
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
25196508WSDLE4
Adder
12.037
24734705WLF1G3
Adder
8.159
24734805WLF1G4
Adder
8.159
24734905WLF1G5
Adder
8.159
253433AC1-085 GEN1
Solar/Wind Harmer
7.506
253432AC1-085 GEN2
Solar/Wind Harmer
0.378
270340AC2-060 GEN
Solar/Wind Harmer
4.256
253406AD2-031_GEN
Solar/Wind Harmer
1.796
270263AC1-001 GEN
Solar/Wind Harmer
1.464
270444AC2-157 GEN1
Solar/Wind Harmer
7.815
270445AC2-157 GEN2
Solar/Wind Harmer
7.815
270291AC1-194 GEN
Solar/Wind Harmer
7.123
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
6.333
971061AG2-657 GEN
Solar/Wind Harmer
12.288
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
2.562
963841AG1-237 GEN
Solar/Wind Harmer
14.713
971029AG2-637 GEN
Solar/Wind Harmer
20.191
24386405FR-21G C
Solar/Wind Harmer
5.776
24387005FR-3G C
Solar/Wind Harmer
5.313
270543AE2-219 C
Solar/Wind Harmer
13.404
946581AF1-322 GEN
Solar/Wind Harmer
13.675
24691005MDL-2G C
Solar/Wind Harmer
4.942
945581AF1-223 GEN
Solar/Wind Harmer
6.056
247536S-71 GEN
Solar/Wind Harmer
5.402
964611AG1-324 GEN
Solar/Wind Harmer
5.196
270432AC2-029 GEN
Solar/Wind Harmer
9.322
944221AF1-090 GEN
Solar/Wind Harmer
14.552
961761AG1-017 GEN
Solar/Wind Harmer
0.569
24729505KEY G4
Adder
8.55
274775LINCOLN ;6U
Adder
11.001
274776LINCOLN ;7U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
274744AC1-111 GEN8
Adder
7.28
274746AC1-111 G10
Adder
7.28
972267AH1-718 GEN
Adder
5.423
274728ELWOOD EC;5P
Adder
21.404
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
274735ELWOOD EC;4P
Adder
21.404
274823ROCKFORD ;21
Adder
25.367
972228AH1-698 GEN2
Adder
4.822
972227AH1-698 GEN1
Adder
3.396
23750501ELLIOTTS
Solar/Wind Helper
0.793
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
238118U2-030_1
Solar/Wind Helper
0.345
203955AF1-039 C O1
Solar/Wind Helper
0.435
20089126CSLMN_L13
Solar/Wind Helper
0.688
20089226LOOKOUT
Solar/Wind Helper
0.686
241997AF1-093 GEN
Solar/Wind Helper
0.282
241985AE1-237 GEN
Solar/Wind Helper
0.274
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
203940AF1-140 C
Solar/Wind Helper
0.45
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
203846AF2-130 C
Solar/Wind Helper
0.501
20334926Z1-069 C
Solar/Wind Helper
1.501
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
959431AF2-234 GEN
Solar/Wind Helper
1.007
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.504
209054AE2-059 GEN
Solar/Wind Helper
0.091
209027LOR2_Q27
Solar/Wind Helper
1.174
212266LOR1
Solar/Wind Helper
0.342
209029WAYMART-WD
Solar/Wind Helper
0.944
961261AF2-417 GEN
Solar/Wind Helper
0.499
20675128HRM_W1-127
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20676428JCR_X2-075
Solar/Wind Helper
0.074
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
20390526W1-045 C
Solar/Wind Helper
0.36
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.081
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.043
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.244
233901CHERRYDALE C
Solar/Wind Helper
0.242
233940AF2-379 C
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.07
205956AE1-196_GEN
Solar/Wind Helper
0.528
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
205917AD1-020 ES
Solar/Wind Helper
0.371
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
23779801AA1-109
Solar/Wind Helper
0.169
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
927014AC1-188 GEN
Solar/Wind Harmer
2.477
970913AG2-568 GEN
Solar/Wind Harmer
10.623
971225AH1-072 GEN
Solar/Wind Harmer
3.04
971227AH1-073 GEN
Solar/Wind Harmer
3.04
24728205BUCHG1
Adder
6.8
962581AG1-107 GEN
Solar/Wind Harmer
7.389
961491AF2-440 GEN
Solar/Wind Harmer
3.071
971073AG2-665 GEN
Solar/Wind Harmer
11.654
970879AG2-548 GEN
Solar/Wind Harmer
1.694
252509AD1-136 GEN
Solar/Wind Harmer
0.369
972043AH1-570 GEN
Solar/Wind Harmer
3.585
972045AH1-571 GEN
Solar/Wind Harmer
2.868
25183208HLCRTG
Solar/Wind Harmer
8.652
971125AH1-004 GEN
Solar/Wind Harmer
5.691
970107AG2-081 GEN
Solar/Wind Harmer
4.268
25194408D.CRK1
Adder
10.747
25194508D.CRK3
Adder
2.009
942891AE2-308 GEN
Solar/Wind Harmer
14.201
253415AE1-040 GEN
Solar/Wind Harmer
1.57
964571AG1-320 GEN
Solar/Wind Harmer
11.341
270269AC2-059
Solar/Wind Harmer
12.798
24728805RICHG1
Adder
5.185
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
18.959
926881AC1-175 GEN
Solar/Wind Harmer
7.589
253370AE2-315 SEC1
Adder
2.718
270383AD1-128 GEN
Solar/Wind Harmer
8.27
339231AF1-038_GEN
Solar/Wind Harmer
2.457
24725505WLD G2 C
Solar/Wind Harmer
5.381
24699105WLD G1 C
Solar/Wind Harmer
5.319
339236AF1-050_GEN
Solar/Wind Harmer
2.451
970241AG2-163 GEN
Solar/Wind Harmer
33.734
970291AG2-192 GEN
Solar/Wind Harmer
1.753
970291AG2-192 GEN
Solar/Wind Harmer
0.565
253349AC2-067 GEN
Solar/Wind Harmer
2.741
253400AC2-068 GEN
Solar/Wind Harmer
1.102
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
24387305FR-4G C
Solar/Wind Harmer
6.822
966841AG1-555 GEN
Solar/Wind Harmer
3.372
970883AG2-550 GEN
Solar/Wind Harmer
13.404
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
4.927
24755605MDL-5G
Solar/Wind Harmer
3.222
24697905MDL-4G C
Solar/Wind Harmer
3.067
270181AB1-006 GEN2
Solar/Wind Harmer
0.956
971485AH1-239 GEN
Solar/Wind Harmer
10.681
964781AG1-341 GEN
Solar/Wind Harmer
14.151
966021AG1-471 GEN
Solar/Wind Harmer
7.208
270031AE2-169
Solar/Wind Harmer
10.876
270599AE1-208 GEN
Solar/Wind Harmer
10.876
945421AF1-207 GEN
Solar/Wind Harmer
18.73
957841AF2-078 GEN
Solar/Wind Harmer
8.063
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
247621Y3-024
Adder
0.321
270201AC2-176 GEN
Solar/Wind Harmer
6.831
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
274696ROCKY RD ;4P
Adder
14.841
274695ROCKY RD ;2P
Adder
14.499
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
274765LEE CO EC;6U
Adder
12.144
274762LEE CO EC;3U
Adder
12.115
274763LEE CO EC;4U
Adder
12.001
274697ROCKY RD ;3P
Adder
3.939
972235AH1-702 GEN1
Adder
3.282
972236AH1-702 GEN2
Adder
2.854
274674JOLIET 9 ;6U
Adder
20.046
274683WAUKEGAN ;8U
Adder
27.432
23585401KL_K28_T16
Solar/Wind Helper
1.54
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
235054AD2-180 GEN
Solar/Wind Helper
2.046
238117U2-030
Solar/Wind Helper
0.345
235531U2-073 GEN
Solar/Wind Helper
3.281
962101AG1-054 GEN
Solar/Wind Helper
0.72
254304AE2-114 C
Solar/Wind Helper
0.241
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
241801AE1-079 GEN
Solar/Wind Helper
0.274
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
203961AE2-224 GEN
Solar/Wind Helper
2.731
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
203804AE2-113_GEN
Solar/Wind Helper
1.942
946751AF1-339 GEN
Solar/Wind Helper
0.504
961431AF2-434 GEN
Solar/Wind Helper
0.502
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
20674328GAR_V4-001
Solar/Wind Helper
0.025
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
207459AE1-142 C O1
Solar/Wind Helper
0.312
20720828JCB_W4-025
Solar/Wind Helper
0.068
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219906AC1-017 C
Solar/Wind Helper
0.045
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.159
219904AC1-010 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.028
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
234015AF2-250 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.592
233994AC2-023 GEN
Solar/Wind Helper
1.001
232428Y3-058 C
Solar/Wind Helper
0.352
234036AF2-325 C
Solar/Wind Helper
0.044
232424Y1-079 C
Solar/Wind Helper
0.121
232436AB1-176 C
Solar/Wind Helper
0.046
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.478
237080AD1-060 GEN
Solar/Wind Helper
0.299
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
223402AF1-300 C
Solar/Wind Helper
0.341
24289405MTG1
50/50
11.336
243186AF1-051 GEN
50/50
12.477
24318705GVG2
50/50
11.565
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
24686505CER G6
Adder
15.551
270331AC1-082 GEN3
Solar/Wind Harmer
0.844
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
5.223
971403AH1-188 GEN
Solar/Wind Harmer
23.963
962761AG1-125 GEN
Solar/Wind Harmer
54.553
970149AG2-104 GEN
Solar/Wind Harmer
33.686
970155AG2-107 GEN
Solar/Wind Harmer
23.787
971687AH1-348 GEN
Solar/Wind Harmer
1.522
24728305BUCHG2
Adder
6.8
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
945681AF1-233 GEN
Solar/Wind Harmer
27.387
339221AD2-048_GEN
Solar/Wind Harmer
2.202
25196808ZIMRHP
Adder
108.598
252516AE2-318_GEN
Solar/Wind Harmer
14.288
252510AF1-249 C
Solar/Wind Harmer
0.594
25196008MFTGT1
Adder
1.98
943111AE2-339 GEN
Solar/Wind Harmer
1.257
25194608D.CRK4
Adder
2.336
3429241JKCT 3G
Adder
16.815
3429421JKCT 10G
Adder
11.809
253316AC1-085 GEN3
Solar/Wind Harmer
11.825
946171AF1-282 GEN
Solar/Wind Harmer
14.124
339211AE2-254 GEN
Solar/Wind Harmer
2.115
24735205WLF2G2
Adder
8.041
253398AE2-221_GEN2
Solar/Wind Harmer
6.325
270222AC2-111 GEN
Solar/Wind Harmer
6.156
944031AF1-071 GEN
Solar/Wind Harmer
1.385
970653AG2-424 GEN
Solar/Wind Harmer
6.638
270273AD2-016 GEN
Solar/Wind Harmer
3.648
24728605AND G2
Adder
5.248
339241AF1-083 GEN
Solar/Wind Harmer
2.268
942081AE2-220 GEN
Solar/Wind Harmer
8.696
270209AC1-174_GEN
Solar/Wind Harmer
5.534
270437AC2-090 C
Solar/Wind Harmer
7.589
270239V3-007_GEN1
Solar/Wind Harmer
2.34
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
276903AD2-071 C
Solar/Wind Harmer
13.523
963741AG1-226 GEN
Solar/Wind Harmer
60.722
964901AG1-354 GEN
Solar/Wind Harmer
20.24
270594AE1-207 GEN
Solar/Wind Harmer
18.313
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
7.368
970825AG2-519 GEN
Solar/Wind Harmer
2.824
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
11.163
24386605FR-22G C
Solar/Wind Harmer
5.776
24791305MDL-5G
Solar/Wind Harmer
3.222
945371AF1-202 GEN
Solar/Wind Harmer
9.316
958861AF2-177 GEN
Solar/Wind Harmer
14.534
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
274745AC1-111 GEN9
Adder
7.28
274761LEE CO EC;2U
Adder
12.115
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274822ROCKFORD ;11
Adder
25.553
274674JOLIET 9 ;6U
Adder
20.046
238185AF2-356 C
Solar/Wind Helper
2.64
20089026BF_G21_K23
Solar/Wind Helper
0.545
238120AE2-309 GEN
Solar/Wind Helper
0.514
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
20084626FORWARD
Solar/Wind Helper
0.405
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
957921AF2-086 GEN
Solar/Wind Helper
0.497
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
23583801GRNGAP
Solar/Wind Helper
4.315
211065PSPA IPP
Solar/Wind Helper
0.169
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.004
207437AD2-070 GEN
Solar/Wind Helper
0.152
207511W3-106 GEN
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.089
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
217213AMBOY SO C
Solar/Wind Helper
0.031
205941AD2-115 GEN
Solar/Wind Helper
0.536
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
207454AA2-184 E
Solar/Wind Helper
0.335
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232406W1-004 FULL
Solar/Wind Helper
0.528
233950AC2-186 GEN
Solar/Wind Helper
0.121
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.463
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
232422X3-066 FULL
Solar/Wind Helper
0.119
233933AB2-153 GEN
Solar/Wind Helper
0.242
233935AB2-179 C
Solar/Wind Helper
1.32
235067AD1-061 GEN
Solar/Wind Helper
0.394
237038AE2-054 C
Solar/Wind Helper
0.24
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
23777801MSM_W1-116
Solar/Wind Helper
0.101
24289405MTG1
50/50
11.336
24318705GVG2
50/50
11.565
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
24686405CER G5
Adder
15.429
270330AC1-082 GEN2
Solar/Wind Harmer
0.842
270329AC1-082 GEN1
Solar/Wind Harmer
0.842
962771AG1-126 GEN
Solar/Wind Harmer
54.553
970153AG2-106 GEN
Solar/Wind Harmer
23.787
971191AH1-055 GEN
Solar/Wind Harmer
31.162
957541AF2-048 GEN
Solar/Wind Harmer
2.477
972103AH1-617 GEN
Solar/Wind Harmer
31.161
960911AF2-382 GEN
Solar/Wind Harmer
11.466
971461AH1-227 GEN
Solar/Wind Harmer
7.797
270367AC2-061_GEN
Solar/Wind Harmer
4.689
270186AC1-089 GEN
Solar/Wind Harmer
9.011
970879AG2-548 GEN
Solar/Wind Harmer
11.654
972167AH1-666 GEN
Solar/Wind Harmer
11.619
252507AC2-088 GEN
Solar/Wind Harmer
2.586
958171AF2-111 GEN
Solar/Wind Harmer
35.846
339243AC2-075 GEN1
Solar/Wind Harmer
0.648
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25196008MFTGT1
Adder
1.918
25194608D.CRK4
Adder
2.336
252524AE2-267 GEN
Solar/Wind Harmer
2.234
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
970093AG2-073 GEN
Solar/Wind Harmer
7.507
253317AC1-085 GEN4
Solar/Wind Harmer
11.825
946181AF1-283 GEN
Solar/Wind Harmer
18.362
253394AE2-221_GEN
Solar/Wind Harmer
6.325
970455AG2-298 GEN
Solar/Wind Harmer
4.865
970653AG2-424 GEN
Solar/Wind Harmer
0.96
339206AE1-143 GEN
Solar/Wind Harmer
2.932
972273AH1-721 GEN
Adder
114.179
24728705AND G3
Adder
10.976
24728505AND G1
Adder
5.248
970193AG2-126 GEN
Solar/Wind Harmer
20.406
24379505HDWTR1G C
Solar/Wind Harmer
10.752
270240V3-007_GEN2
Solar/Wind Harmer
8.412
253303V4-073 C
Solar/Wind Harmer
0.157
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
270346AE1-212 GEN
Solar/Wind Harmer
12.206
247642Z2-115 C
Solar/Wind Harmer
0.086
965461AG1-414 GEN
Solar/Wind Harmer
3.058
970289AG2-191 GEN
Solar/Wind Harmer
1.035
270004AE1-209 GEN
Solar/Wind Harmer
7.368
970825AG2-519 GEN
Solar/Wind Harmer
7.583
946031AF1-268 GEN
Solar/Wind Harmer
11.153
24386205FR-12G C
Solar/Wind Harmer
5.756
960071AF2-298 GEN
Solar/Wind Harmer
2.031
339255AE2-071 GEN
Solar/Wind Harmer
1.57
339250AF1-203 GEN
Solar/Wind Harmer
0.808
24690905MDL-1G C
Solar/Wind Harmer
10.73
970781AG2-491 GEN
Solar/Wind Harmer
13.365
962031AG1-047 GEN
Solar/Wind Harmer
4.019
274772LINCOLN ;3U
Adder
11.001
972259AH1-714 GEN
Adder
24.853
274760LEE CO EC;1U
Adder
12.115
274767LEE CO EC;8U
Adder
11.973
274729ELWOOD EC;1P
Adder
21.404
274730ELWOOD EC;6P
Adder
21.404
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
274682WAUKEGAN ;7U
Adder
7.239
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
235058AG1-386 C
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
1.078
964991AG1-363 GEN
Solar/Wind Helper
4.441
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203854AF2-039 C
Solar/Wind Helper
0.357
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
946731AF1-337 GEN
Solar/Wind Helper
0.504
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207518AF1-320_GEN
Solar/Wind Helper
1.73
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
203975AE1-071-GEN
Solar/Wind Helper
2.698
207484AF2-139 C O1
Solar/Wind Helper
0.093
20674928WA_W3-044
Solar/Wind Helper
0.108
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674628WNG_W3-110
Solar/Wind Helper
0.098
20676328BVR_Y1-020
Solar/Wind Helper
0.03
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.492
219908AB1-139 C
Solar/Wind Helper
0.08
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.069
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.058
228729W2-030 C
Solar/Wind Helper
0.117
233996TM1833_GEN
Solar/Wind Helper
0.214
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
232408W1-005 C
Solar/Wind Helper
0.528
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
233918AB1-142 GEN
Solar/Wind Helper
0.523
235063AE1-101 C2
Solar/Wind Helper
1.478
205916AD1-020 GEN
Solar/Wind Helper
1.727
237001AB1-127_GEN
Solar/Wind Helper
0.391
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
238175AF1-290_GEN
Solar/Wind Helper
0.127
957741AF2-068 GEN
Solar/Wind Harmer
8.281
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
TVALTFEXP_TVA->PJM
CLTF
12.563
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
WECLTFEXP_WEC->PJM
CLTF
4.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 114.18 MW.

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.4 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6428.58
MW Contribution:
96.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
970913AG2-568 GEN
Solar/Wind Harmer
8.731
971225AH1-072 GEN
Solar/Wind Harmer
2.121
971227AH1-073 GEN
Solar/Wind Harmer
2.121
24728205BUCHG1
Adder
6.8
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971073AG2-665 GEN
Solar/Wind Harmer
7.453
970879AG2-548 GEN
Solar/Wind Harmer
1.694
252509AD1-136 GEN
Solar/Wind Harmer
0.05
972043AH1-570 GEN
Solar/Wind Harmer
2.601
972045AH1-571 GEN
Solar/Wind Harmer
2.084
25183208HLCRTG
Solar/Wind Harmer
0.001
971125AH1-004 GEN
Solar/Wind Harmer
3.97
970107AG2-081 GEN
Solar/Wind Harmer
2.978
25194408D.CRK1
Adder
10.747
25194508D.CRK3
Adder
2.009
942891AE2-308 GEN
Solar/Wind Harmer
9.908
971587AH1-292 GEN
Solar/Wind Harmer
7.164
964571AG1-320 GEN
Solar/Wind Harmer
8.813
270269AC2-059
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
5.185
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
10.085
926881AC1-175 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
5.492
970291AG2-192 GEN
Solar/Wind Harmer
1.223
970291AG2-192 GEN
Solar/Wind Harmer
0.565
971613AH1-306 GEN
Solar/Wind Harmer
4.515
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.061
970883AG2-550 GEN
Solar/Wind Harmer
9.352
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971485AH1-239 GEN
Solar/Wind Harmer
7.452
964781AG1-341 GEN
Solar/Wind Harmer
9.873
966021AG1-471 GEN
Solar/Wind Harmer
5.029
270031AE2-169
Solar/Wind Harmer
5.121
270599AE1-208 GEN
Solar/Wind Harmer
8.535
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
247621Y3-024
Adder
0.321
270201AC2-176 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
19.462
276911AD2-131_GEN
Solar/Wind Harmer
1.282
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.431
276615X2-022 GEN
Solar/Wind Harmer
0.096
276838X2-022 GEN2
Solar/Wind Harmer
0.521
960611AF2-352 GEN
Solar/Wind Harmer
3.067
942111AE2-223 GEN
Solar/Wind Harmer
2.987
276645AC1-214 GEN1
Solar/Wind Harmer
0.358
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
22.743
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
958491AF2-143 GEN
Solar/Wind Harmer
13.642
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.467
958481AF2-142 GEN
Solar/Wind Harmer
13.633
962691AG1-118 GEN
Solar/Wind Harmer
27.261
971341AH1-150 GEN
Solar/Wind Harmer
18.173
971343AH1-151 GEN
Solar/Wind Harmer
18.173
938861AE1-114 GEN
Solar/Wind Harmer
5.149
274696ROCKY RD ;4P
Adder
14.841
274695ROCKY RD ;2P
Adder
14.499
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
274765LEE CO EC;6U
Adder
12.144
274762LEE CO EC;3U
Adder
12.115
274763LEE CO EC;4U
Adder
12.001
274697ROCKY RD ;3P
Adder
3.939
972235AH1-702 GEN1
Adder
3.282
972236AH1-702 GEN2
Adder
2.854
276893AG1-478 C
Solar/Wind Harmer
0.606
274674JOLIET 9 ;6U
Adder
20.046
942221AE2-234 GEN
Solar/Wind Harmer
3.648
274683WAUKEGAN ;8U
Adder
27.432
971277AH1-098 GEN
Solar/Wind Harmer
3.633
274888KELLY CRK;1U
Solar/Wind Harmer
0.529
276776AD2-060 GEN
Solar/Wind Harmer
0.968
958011AF2-095 GEN
Solar/Wind Harmer
13.073
970941AG2-585 GEN
Solar/Wind Harmer
4.993
23585401KL_K28_T16
Solar/Wind Helper
1.54
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
235054AD2-180 GEN
Solar/Wind Helper
2.046
238117U2-030
Solar/Wind Helper
0.345
235531U2-073 GEN
Solar/Wind Helper
3.281
962101AG1-054 GEN
Solar/Wind Helper
0.72
254304AE2-114 C
Solar/Wind Helper
0.241
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
241801AE1-079 GEN
Solar/Wind Helper
0.274
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
203961AE2-224 GEN
Solar/Wind Helper
2.731
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
27.062
270399AC1-101 GEN
Solar/Wind Harmer
3.79
270400AC1-102 GEN
Solar/Wind Harmer
3.79
970281AG2-184 GEN
Solar/Wind Harmer
22.827
971985AH1-537 GEN
Solar/Wind Harmer
3.231
941621AE2-160 GEN
Adder
5.034
971313AH1-133 GEN
Solar/Wind Harmer
5.062
972163AH1-664 GEN
Solar/Wind Harmer
11.291
972165AH1-665 GEN
Solar/Wind Harmer
9.043
339216AC1-074 GEN
Solar/Wind Harmer
0.266
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
3429211JKCT 2G
Adder
16.597
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
25196508WSDLE4
Adder
12.037
24734705WLF1G3
Adder
8.159
24734805WLF1G4
Adder
8.159
24734905WLF1G5
Adder
8.159
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.728
270263AC1-001 GEN
Solar/Wind Harmer
0.978
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
0.001
971061AG2-657 GEN
Solar/Wind Harmer
6.001
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
1.788
963841AG1-237 GEN
Solar/Wind Harmer
4.07
971029AG2-637 GEN
Solar/Wind Harmer
14.087
24386405FR-21G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
6.546
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.372
971609AH1-304 GEN
Solar/Wind Harmer
1.521
964611AG1-324 GEN
Solar/Wind Harmer
3.625
270432AC2-029 GEN
Solar/Wind Harmer
4.119
944221AF1-090 GEN
Solar/Wind Harmer
5.449
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.363
276848AB2-070 GEN3
Solar/Wind Harmer
0.362
24289405MTG1
50/50
11.336
24318705GVG2
50/50
11.565
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
24686405CER G5
Adder
15.429
962771AG1-126 GEN
Solar/Wind Harmer
46.005
970153AG2-106 GEN
Solar/Wind Harmer
29.378
971191AH1-055 GEN
Solar/Wind Harmer
29.882
972103AH1-617 GEN
Solar/Wind Harmer
21.74
960911AF2-382 GEN
Solar/Wind Harmer
7.999
971461AH1-227 GEN
Solar/Wind Harmer
5.44
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
7.453
972167AH1-666 GEN
Solar/Wind Harmer
8.106
252507AC2-088 GEN
Solar/Wind Harmer
0.453
958171AF2-111 GEN
Solar/Wind Harmer
25.009
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25196008MFTGT1
Adder
1.918
25194608D.CRK4
Adder
2.336
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
970093AG2-073 GEN
Solar/Wind Harmer
8.38
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
12.81
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
3.77
970653AG2-424 GEN
Solar/Wind Harmer
0.96
972273AH1-721 GEN
Adder
114.179
24728705AND G3
Adder
10.976
24728505AND G1
Adder
5.248
970193AG2-126 GEN
Solar/Wind Harmer
14.237
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
270346AE1-212 GEN
Solar/Wind Harmer
8.358
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.035
270004AE1-209 GEN
Solar/Wind Harmer
2.038
276849AB2-070 GEN2
Solar/Wind Harmer
0.363
971611AH1-305 GEN
Solar/Wind Harmer
5.499
959141AF2-205 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0
24729505KEY G4
Adder
8.55
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.649
966391AG1-508 GEN
Solar/Wind Harmer
1.42
970169AG2-114 GEN
Solar/Wind Harmer
9.156
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
241972AD1-140 GEN
Solar/Wind Harmer
0.996
274877BISHOP HL;1U
Solar/Wind Harmer
0.304
926823AC1-168 GEN
Solar/Wind Harmer
1.55
274775LINCOLN ;6U
Adder
11.001
274776LINCOLN ;7U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
970073AG2-061 GEN
Solar/Wind Harmer
3.032
276741O09 GEN1
Solar/Wind Harmer
0.321
970833AG2-524 GEN
Solar/Wind Harmer
10.003
970833AG2-524 GEN
Solar/Wind Harmer
6.669
274744AC1-111 GEN8
Adder
7.28
274746AC1-111 G10
Adder
7.28
276861AD2-134 GEN
Solar/Wind Harmer
0.162
276863AD2-134 GEN
Solar/Wind Harmer
0.162
971675AH1-338 GEN
Solar/Wind Harmer
3.544
971171AH1-044 GEN
Solar/Wind Harmer
18.173
971681AH1-341 GEN
Solar/Wind Harmer
14.63
972267AH1-718 GEN
Adder
5.423
946321AF1-296 GEN
Solar/Wind Harmer
5.088
274728ELWOOD EC;5P
Adder
21.404
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
274735ELWOOD EC;4P
Adder
21.404
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
274823ROCKFORD ;21
Adder
25.367
971411AH1-196 GEN
Solar/Wind Harmer
13.626
972228AH1-698 GEN2
Adder
4.822
972227AH1-698 GEN1
Adder
3.396
960591AF2-350 GEN
Solar/Wind Harmer
9.078
23750501ELLIOTTS
Solar/Wind Helper
0.793
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
238118U2-030_1
Solar/Wind Helper
0.345
203955AF1-039 C O1
Solar/Wind Helper
0.435
20089126CSLMN_L13
Solar/Wind Helper
0.688
20089226LOOKOUT
Solar/Wind Helper
0.686
241997AF1-093 GEN
Solar/Wind Helper
0.282
241985AE1-237 GEN
Solar/Wind Helper
0.274
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
203940AF1-140 C
Solar/Wind Helper
0.45
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
203846AF2-130 C
Solar/Wind Helper
0.501
20334926Z1-069 C
Solar/Wind Helper
1.501
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
959431AF2-234 GEN
Solar/Wind Helper
1.007
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.504
209054AE2-059 GEN
Solar/Wind Helper
0.091
209027LOR2_Q27
Solar/Wind Helper
1.174
212266LOR1
Solar/Wind Helper
0.342
209029WAYMART-WD
Solar/Wind Helper
0.944
961261AF2-417 GEN
Solar/Wind Helper
0.499
20675128HRM_W1-127
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20676428JCR_X2-075
Solar/Wind Helper
0.074
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.061
970191AG2-125 GEN
Solar/Wind Harmer
2.419
970825AG2-519 GEN
Solar/Wind Harmer
7.074
946031AF1-268 GEN
Solar/Wind Harmer
8.922
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.325
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.91
942481AE2-261 GEN
Solar/Wind Harmer
27.692
957381AF2-032 GEN
Solar/Wind Harmer
2.099
971993AH1-541 GEN
Solar/Wind Harmer
4.271
943031AE2-326 GEN
Solar/Wind Harmer
4.803
965091AG1-374 GEN
Solar/Wind Harmer
27.602
959611AF2-252 GEN
Solar/Wind Harmer
3.067
944531AF1-118 GEN
Solar/Wind Harmer
41.107
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.304
970571AG2-364 GEN
Solar/Wind Harmer
18.217
253325AC1-069 GEN
Solar/Wind Harmer
0.01
276868AE1-113 GEN
Solar/Wind Harmer
1.82
274879MINONK ;1U
Solar/Wind Harmer
0.38
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.001
970707AG2-453 GEN
Solar/Wind Harmer
29.702
943121AE2-341 GEN
Solar/Wind Harmer
15.239
943591AF1-030 GEN
Solar/Wind Harmer
10.134
274862TOP CROP ;2U
Solar/Wind Harmer
1.227
972259AH1-714 GEN
Adder
24.853
274855GSG-6 ;RU
Solar/Wind Harmer
0.332
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
946671AF1-331 GEN
Solar/Wind Harmer
0.969
959091AF2-200 GEN
Solar/Wind Harmer
18.173
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.115
274767LEE CO EC;8U
Adder
11.973
965931AG1-462 GEN
Solar/Wind Harmer
23.167
274729ELWOOD EC;1P
Adder
21.404
274730ELWOOD EC;6P
Adder
21.404
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
971087AG2-675 GEN
Solar/Wind Harmer
4.845
274682WAUKEGAN ;7U
Adder
7.239
274887GEN-1.85
Solar/Wind Harmer
0.236
276843GEN-1.7
Solar/Wind Harmer
0.294
276806AD2-047 C O1
Solar/Wind Harmer
5.144
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
235058AG1-386 C
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
1.078
964991AG1-363 GEN
Solar/Wind Helper
4.441
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203854AF2-039 C
Solar/Wind Helper
0.357
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
946731AF1-337 GEN
Solar/Wind Helper
0.504
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207518AF1-320_GEN
Solar/Wind Helper
1.73
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
203975AE1-071-GEN
Solar/Wind Helper
2.698
207484AF2-139 C O1
Solar/Wind Helper
0.093
20674928WA_W3-044
Solar/Wind Helper
0.108
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674628WNG_W3-110
Solar/Wind Helper
0.098
20676328BVR_Y1-020
Solar/Wind Helper
0.03
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676728BRNX1-095
Solar/Wind Helper
0.032
24289405MTG1
50/50
11.336
243186AF1-051 GEN
50/50
12.477
24318705GVG2
50/50
11.565
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
24686505CER G6
Adder
15.551
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
16.719
962761AG1-125 GEN
Solar/Wind Harmer
46.005
970149AG2-104 GEN
Solar/Wind Harmer
24.844
970155AG2-107 GEN
Solar/Wind Harmer
29.378
971687AH1-348 GEN
Solar/Wind Harmer
1.062
24728305BUCHG2
Adder
6.8
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
945681AF1-233 GEN
Solar/Wind Harmer
19.107
25196808ZIMRHP
Adder
108.598
252516AE2-318_GEN
Solar/Wind Harmer
11.165
252510AF1-249 C
Solar/Wind Harmer
0.075
25196008MFTGT1
Adder
1.98
25194608D.CRK4
Adder
2.336
3429241JKCT 3G
Adder
16.815
3429421JKCT 10G
Adder
11.809
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.854
24735205WLF2G2
Adder
8.041
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
4.631
970773AG2-487 GEN
Solar/Wind Harmer
1.693
270273AD2-016 GEN
Solar/Wind Harmer
0.98
24728605AND G2
Adder
5.248
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.957
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
276903AD2-071 C
Solar/Wind Harmer
10.535
963741AG1-226 GEN
Solar/Wind Harmer
22.28
964901AG1-354 GEN
Solar/Wind Harmer
14.121
270594AE1-207 GEN
Solar/Wind Harmer
10.536
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
2.038
970825AG2-519 GEN
Solar/Wind Harmer
3.334
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.02
965911AG1-460 GEN
Solar/Wind Harmer
1.852
965651AG1-433 GEN
Solar/Wind Harmer
2.715
276621W2-048 GEN
Solar/Wind Harmer
0.463
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.546
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.866
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.925
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.831
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.358
270055AF2-134 C O1
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
27.326
971997AH1-543 GEN
Solar/Wind Harmer
4.779
253333AC1-068 GEN
Solar/Wind Harmer
0.01
276882AE2-255 GEN
Solar/Wind Harmer
1.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
276805AD2-038 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.321
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.477
274861TOP CROP ;1U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.28
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
27.26
959081AF2-199 GEN
Solar/Wind Harmer
9.087
962781AG1-127 GEN
Solar/Wind Harmer
8.648
971067AG2-660 GEN
Solar/Wind Harmer
3.029
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.115
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274822ROCKFORD ;11
Adder
25.553
274674JOLIET 9 ;6U
Adder
20.046
970819AG2-516 GEN
Solar/Wind Harmer
10.9
238185AF2-356 C
Solar/Wind Helper
2.64
20089026BF_G21_K23
Solar/Wind Helper
0.545
238120AE2-309 GEN
Solar/Wind Helper
0.514
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
20084626FORWARD
Solar/Wind Helper
0.405
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
957921AF2-086 GEN
Solar/Wind Helper
0.497
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
23583801GRNGAP
Solar/Wind Helper
4.315
211065PSPA IPP
Solar/Wind Helper
0.169
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.004
207437AD2-070 GEN
Solar/Wind Helper
0.152
207511W3-106 GEN
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.089
217169METRODIV C
Solar/Wind Helper
0.004
959381AF2-229 GEN
Solar/Wind Helper
0.367
20390526W1-045 C
Solar/Wind Helper
0.36
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.081
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.043
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.244
233901CHERRYDALE C
Solar/Wind Helper
0.242
233940AF2-379 C
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.07
205956AE1-196_GEN
Solar/Wind Helper
0.528
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
205917AD1-020 ES
Solar/Wind Helper
0.371
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
23779801AA1-109
Solar/Wind Helper
0.169
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
203804AE2-113_GEN
Solar/Wind Helper
1.942
946751AF1-339 GEN
Solar/Wind Helper
0.504
961431AF2-434 GEN
Solar/Wind Helper
0.502
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
20674328GAR_V4-001
Solar/Wind Helper
0.025
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
207459AE1-142 C O1
Solar/Wind Helper
0.312
20720828JCB_W4-025
Solar/Wind Helper
0.068
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219906AC1-017 C
Solar/Wind Helper
0.045
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.159
219904AC1-010 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.028
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
234015AF2-250 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.592
233994AC2-023 GEN
Solar/Wind Helper
1.001
232428Y3-058 C
Solar/Wind Helper
0.352
234036AF2-325 C
Solar/Wind Helper
0.044
232424Y1-079 C
Solar/Wind Helper
0.121
232436AB1-176 C
Solar/Wind Helper
0.046
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.478
237080AD1-060 GEN
Solar/Wind Helper
0.299
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
223402AF1-300 C
Solar/Wind Helper
0.341
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
217213AMBOY SO C
Solar/Wind Helper
0.031
205941AD2-115 GEN
Solar/Wind Helper
0.536
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
207454AA2-184 E
Solar/Wind Helper
0.335
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232406W1-004 FULL
Solar/Wind Helper
0.528
233950AC2-186 GEN
Solar/Wind Helper
0.121
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.463
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
232422X3-066 FULL
Solar/Wind Helper
0.119
233933AB2-153 GEN
Solar/Wind Helper
0.242
233935AB2-179 C
Solar/Wind Helper
1.32
235067AD1-061 GEN
Solar/Wind Helper
0.394
237038AE2-054 C
Solar/Wind Helper
0.24
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
23777801MSM_W1-116
Solar/Wind Helper
0.101
970373AG2-245 GEN
Solar/Wind Harmer
16.807
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.492
219908AB1-139 C
Solar/Wind Helper
0.08
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.069
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.058
228729W2-030 C
Solar/Wind Helper
0.117
233996TM1833_GEN
Solar/Wind Helper
0.214
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
232408W1-005 C
Solar/Wind Helper
0.528
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
233918AB1-142 GEN
Solar/Wind Helper
0.523
235063AE1-101 C2
Solar/Wind Helper
1.478
205916AD1-020 GEN
Solar/Wind Helper
1.727
237001AB1-127_GEN
Solar/Wind Helper
0.391
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
238175AF1-290_GEN
Solar/Wind Helper
0.127
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
TVALTFEXP_TVA->PJM
CLTF
12.563
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
WECLTFEXP_WEC->PJM
CLTF
4.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 114.18 MW.

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#17219_05GUERNSEY 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.72 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6225.55
MW Contribution:
97.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.774
957241AF2-018 GEN
Solar/Wind Harmer
7.761
270053AF1-130 C
Solar/Wind Harmer
31.012
270399AC1-101 GEN
Solar/Wind Harmer
7.341
270400AC1-102 GEN
Solar/Wind Harmer
7.341
970281AG2-184 GEN
Solar/Wind Harmer
33.013
971985AH1-537 GEN
Solar/Wind Harmer
28.037
941621AE2-160 GEN
Adder
5.08
962211AG1-066 GEN
Solar/Wind Harmer
3.683
971313AH1-133 GEN
Solar/Wind Harmer
8.881
972163AH1-664 GEN
Solar/Wind Harmer
14.676
972165AH1-665 GEN
Solar/Wind Harmer
11.741
339216AC1-074 GEN
Solar/Wind Harmer
2.418
25196108MFTGT2
Adder
2.204
25196108MFTGT2
Adder
2.047
3429211JKCT 2G
Adder
16.761
25196408WSDLE3
Adder
12.643
25196308WSDLE2
Adder
12.533
243186AF1-051 GEN
50/50
12.548
24721705FLATG2
50/50
41.198
24723005RIVRG1
Adder
36.155
24723105RIVRG2
Adder
36.155
927014AC1-188 GEN
Solar/Wind Harmer
2.499
970913AG2-568 GEN
Solar/Wind Harmer
10.718
971225AH1-072 GEN
Solar/Wind Harmer
3.068
971227AH1-073 GEN
Solar/Wind Harmer
3.068
24728205BUCHG1
Adder
6.863
962581AG1-107 GEN
Solar/Wind Harmer
7.459
961491AF2-440 GEN
Solar/Wind Harmer
3.1
971073AG2-665 GEN
Solar/Wind Harmer
11.766
970879AG2-548 GEN
Solar/Wind Harmer
1.71
252509AD1-136 GEN
Solar/Wind Harmer
0.373
972043AH1-570 GEN
Solar/Wind Harmer
3.62
972045AH1-571 GEN
Solar/Wind Harmer
2.896
25183208HLCRTG
Solar/Wind Harmer
8.737
971125AH1-004 GEN
Solar/Wind Harmer
5.746
970107AG2-081 GEN
Solar/Wind Harmer
4.31
25194408D.CRK1
Adder
10.853
25194508D.CRK3
Adder
2.029
942891AE2-308 GEN
Solar/Wind Harmer
14.341
253415AE1-040 GEN
Solar/Wind Harmer
1.586
964571AG1-320 GEN
Solar/Wind Harmer
11.455
270269AC2-059
Solar/Wind Harmer
12.928
24728805RICHG1
Adder
5.238
24728905RICHG2
Adder
5.238
945391AF1-204 GEN
Solar/Wind Harmer
19.154
926881AC1-175 GEN
Solar/Wind Harmer
7.667
253370AE2-315 SEC1
Adder
2.746
270383AD1-128 GEN
Solar/Wind Harmer
8.356
339231AF1-038_GEN
Solar/Wind Harmer
2.483
24725505WLD G2 C
Solar/Wind Harmer
5.437
24699105WLD G1 C
Solar/Wind Harmer
5.374
339236AF1-050_GEN
Solar/Wind Harmer
2.477
970241AG2-163 GEN
Solar/Wind Harmer
34.084
970291AG2-192 GEN
Solar/Wind Harmer
1.771
970291AG2-192 GEN
Solar/Wind Harmer
0.57
253349AC2-067 GEN
Solar/Wind Harmer
2.769
253400AC2-068 GEN
Solar/Wind Harmer
1.114
25322209TAIT E
Adder
13.248
25322209TAIT E
Adder
12.95
24387305FR-4G C
Solar/Wind Harmer
6.894
966841AG1-555 GEN
Solar/Wind Harmer
3.407
970883AG2-550 GEN
Solar/Wind Harmer
13.544
970885AG2-551 GEN
Solar/Wind Harmer
3.15
270180AB1-006 GEN1
Solar/Wind Harmer
9.713
24697605MDL-3G C
Solar/Wind Harmer
4.978
24755605MDL-5G
Solar/Wind Harmer
3.256
24697905MDL-4G C
Solar/Wind Harmer
3.099
270181AB1-006 GEN2
Solar/Wind Harmer
0.966
971485AH1-239 GEN
Solar/Wind Harmer
10.793
964781AG1-341 GEN
Solar/Wind Harmer
14.3
966021AG1-471 GEN
Solar/Wind Harmer
7.284
270031AE2-169
Solar/Wind Harmer
10.99
270599AE1-208 GEN
Solar/Wind Harmer
10.99
945421AF1-207 GEN
Solar/Wind Harmer
18.926
957841AF2-078 GEN
Solar/Wind Harmer
8.147
25326109MON D
Adder
1.772
964611AG1-324 GEN
Solar/Wind Harmer
0.704
247621Y3-024
Adder
0.324
270201AC2-176 GEN
Solar/Wind Harmer
6.903
274770LINCOLN ;1U
Adder
11.119
274771LINCOLN ;2U
Adder
11.119
274696ROCKY RD ;4P
Adder
15.001
274695ROCKY RD ;2P
Adder
14.655
274693ROCKY RD ;1P
Adder
14.51
274764LEE CO EC;5U
Adder
12.274
274765LEE CO EC;6U
Adder
12.274
274762LEE CO EC;3U
Adder
12.246
274763LEE CO EC;4U
Adder
12.13
274697ROCKY RD ;3P
Adder
3.981
274674JOLIET 9 ;6U
Adder
20.261
972235AH1-702 GEN1
Adder
3.317
972236AH1-702 GEN2
Adder
2.884
23585401KL_K28_T16
Solar/Wind Helper
1.522
237043AE2-125 C
Solar/Wind Helper
0.207
23751201ROTHROCK
Solar/Wind Helper
0.874
235054AD2-180 GEN
Solar/Wind Helper
2.021
238117U2-030
Solar/Wind Helper
0.341
235531U2-073 GEN
Solar/Wind Helper
3.241
962101AG1-054 GEN
Solar/Wind Helper
0.711
254304AE2-114 C
Solar/Wind Helper
0.238
254305AE2-115 C
Solar/Wind Helper
0.238
20083426SW_E13_K22
Solar/Wind Helper
0.063
241967AE2-285_GEN
Solar/Wind Helper
0.691
241801AE1-079 GEN
Solar/Wind Helper
0.27
946071AF1-272 GEN
Solar/Wind Helper
3.032
20088826HIGHLAND
Solar/Wind Helper
1.005
203961AE2-224 GEN
Solar/Wind Helper
2.695
203818AF1-086 GEN
Solar/Wind Helper
1.876
203853AF1-134 C O1
Solar/Wind Helper
0.53
946381AF1-302 GEN
Solar/Wind Helper
0.245
203946AE2-131 C
Solar/Wind Helper
0.526
203954AE2-126 C
Solar/Wind Helper
0.519
940863AE2-074 GEN
Solar/Wind Helper
0.501
203804AE2-113_GEN
Solar/Wind Helper
1.916
946751AF1-339 GEN
Solar/Wind Helper
0.496
961431AF2-434 GEN
Solar/Wind Helper
0.495
316097T157 G90
Solar/Wind Helper
1.146
203835AF1-098 GEN
Solar/Wind Helper
1.948
207471AF2-354 C
Solar/Wind Helper
0.183
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.054
20674328GAR_V4-001
Solar/Wind Helper
0.024
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.15
20714828MDF_W3-079
Solar/Wind Helper
0.138
207459AE1-142 C O1
Solar/Wind Helper
0.307
20720828JCB_W4-025
Solar/Wind Helper
0.067
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.084
219304NAMERICA C
Solar/Wind Helper
0.138
219906AC1-017 C
Solar/Wind Helper
0.044
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.157
219904AC1-010 C
Solar/Wind Helper
0.063
228754AB1-001 C
Solar/Wind Helper
0.027
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.015
233952AC2-187 GEN
Solar/Wind Helper
0.239
233954AC2-188 GEN
Solar/Wind Helper
0.239
233994AC2-023 GEN
Solar/Wind Helper
0.986
232410W1-006 C
Solar/Wind Helper
0.52
232428Y3-058 C
Solar/Wind Helper
0.347
234015AF2-250 C
Solar/Wind Helper
0.039
233946AB2-136 GEN
Solar/Wind Helper
0.583
234036AF2-325 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.368
233930AB2-032 GEN
Solar/Wind Helper
0.39
232436AB1-176 C
Solar/Wind Helper
0.046
235062AE1-101 C1
Solar/Wind Helper
1.456
237080AD1-060 GEN
Solar/Wind Helper
0.295
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.235
237006AB1-125 GEN
Solar/Wind Helper
0.109
223401AF1-299 GEN
Solar/Wind Helper
0.336
223402AF1-300 C
Solar/Wind Helper
0.336
24289405MTG1
50/50
11.396
243186AF1-051 GEN
50/50
12.548
24318705GVG2
50/50
11.631
24721805FLATG3
50/50
2.774
972203AH1-686 GEN
Adder
4.442
24723205RIVRG3
Adder
36.155
24686505CER G6
Adder
15.668
270331AC1-082 GEN3
Solar/Wind Harmer
0.851
944971AF1-162 GEN
Solar/Wind Harmer
12.224
960001AF2-291 GEN
Solar/Wind Harmer
5.265
971403AH1-188 GEN
Solar/Wind Harmer
24.159
962761AG1-125 GEN
Solar/Wind Harmer
55.006
970149AG2-104 GEN
Solar/Wind Harmer
33.966
970155AG2-107 GEN
Solar/Wind Harmer
23.985
971687AH1-348 GEN
Solar/Wind Harmer
1.536
24728305BUCHG2
Adder
6.863
970091AG2-072 GEN
Adder
114.157
971073AG2-665 GEN
Solar/Wind Harmer
1.71
945681AF1-233 GEN
Solar/Wind Harmer
27.651
339221AD2-048_GEN
Solar/Wind Harmer
2.223
25196208WSDLE1
Adder
12.501
25196708WSDLE6
Adder
12.47
25196508WSDLE4
Adder
12.156
24734705WLF1G3
Adder
8.239
24734805WLF1G4
Adder
8.239
24734905WLF1G5
Adder
8.239
253433AC1-085 GEN1
Solar/Wind Harmer
7.58
253432AC1-085 GEN2
Solar/Wind Harmer
0.381
270340AC2-060 GEN
Solar/Wind Harmer
4.299
253406AD2-031_GEN
Solar/Wind Harmer
1.814
270263AC1-001 GEN
Solar/Wind Harmer
1.479
270444AC2-157 GEN1
Solar/Wind Harmer
7.893
270445AC2-157 GEN2
Solar/Wind Harmer
7.893
270291AC1-194 GEN
Solar/Wind Harmer
7.194
24735105WLF2G1
Adder
8.122
270356AE2-297 GEN
Solar/Wind Harmer
6.397
971061AG2-657 GEN
Solar/Wind Harmer
12.414
253372AE2-315 SEC3
Adder
2.597
253372AE2-315 SEC3
Adder
2.597
25306009OHH W.
Adder
3.946
970289AG2-191 GEN
Solar/Wind Harmer
2.589
963841AG1-237 GEN
Solar/Wind Harmer
14.866
971029AG2-637 GEN
Solar/Wind Harmer
20.401
24386405FR-21G C
Solar/Wind Harmer
5.837
24387005FR-3G C
Solar/Wind Harmer
5.368
270543AE2-219 C
Solar/Wind Harmer
13.544
946581AF1-322 GEN
Solar/Wind Harmer
13.818
24691005MDL-2G C
Solar/Wind Harmer
4.994
945581AF1-223 GEN
Solar/Wind Harmer
6.119
247536S-71 GEN
Solar/Wind Harmer
5.458
964611AG1-324 GEN
Solar/Wind Harmer
5.25
270432AC2-029 GEN
Solar/Wind Harmer
9.42
944221AF1-090 GEN
Solar/Wind Harmer
14.705
961761AG1-017 GEN
Solar/Wind Harmer
0.575
24729505KEY G4
Adder
8.64
274775LINCOLN ;6U
Adder
11.119
274776LINCOLN ;7U
Adder
11.119
274777LINCOLN ;8U
Adder
11.119
274744AC1-111 GEN8
Adder
7.358
274746AC1-111 G10
Adder
7.358
972267AH1-718 GEN
Adder
5.481
274731ELWOOD EC;2P
Adder
21.634
274733ELWOOD EC;3P
Adder
21.634
274735ELWOOD EC;4P
Adder
21.634
274728ELWOOD EC;5P
Adder
21.634
274823ROCKFORD ;21
Adder
25.64
972228AH1-698 GEN2
Adder
4.874
972227AH1-698 GEN1
Adder
3.432
23750501ELLIOTTS
Solar/Wind Helper
0.784
23652301WDPWR_K20
Solar/Wind Helper
0.167
23750701CROSSCHOOL
Solar/Wind Helper
1.42
238118U2-030_1
Solar/Wind Helper
0.341
203955AF1-039 C O1
Solar/Wind Helper
0.43
20089126CSLMN_L13
Solar/Wind Helper
0.68
20089226LOOKOUT
Solar/Wind Helper
0.678
241997AF1-093 GEN
Solar/Wind Helper
0.278
241985AE1-237 GEN
Solar/Wind Helper
0.27
241982AE2-343 S C
Solar/Wind Helper
0.243
20088926STNY CRK
Solar/Wind Helper
0.922
203940AF1-140 C
Solar/Wind Helper
0.444
20094526CT_V3-030
Solar/Wind Helper
0.527
20088626ARWF_N39
Solar/Wind Helper
1.354
203846AF2-130 C
Solar/Wind Helper
0.494
20334926Z1-069 C
Solar/Wind Helper
1.481
200917MEHOOPANY_G
Solar/Wind Helper
2.413
209067AE2-060 GEN
Solar/Wind Helper
0.091
959431AF2-234 GEN
Solar/Wind Helper
0.993
964051AG1-259 GEN
Solar/Wind Helper
0.074
964061AG1-260 GEN
Solar/Wind Helper
0.074
959421AF2-233 GEN
Solar/Wind Helper
0.497
209054AE2-059 GEN
Solar/Wind Helper
0.09
209027LOR2_Q27
Solar/Wind Helper
1.157
212266LOR1
Solar/Wind Helper
0.337
209029WAYMART-WD
Solar/Wind Helper
0.93
961261AF2-417 GEN
Solar/Wind Helper
0.492
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.068
20676428JCR_X2-075
Solar/Wind Helper
0.073
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.172
20675528CPH_W2-050
Solar/Wind Helper
0.121
20720628TIN_W1-124
Solar/Wind Helper
0.202
24289405MTG1
50/50
11.396
24318705GVG2
50/50
11.631
24722005FLATG5
50/50
2.774
24721905FLATG4
50/50
50.672
24686405CER G5
Adder
15.544
270330AC1-082 GEN2
Solar/Wind Harmer
0.849
270329AC1-082 GEN1
Solar/Wind Harmer
0.849
962771AG1-126 GEN
Solar/Wind Harmer
55.006
970153AG2-106 GEN
Solar/Wind Harmer
23.985
971191AH1-055 GEN
Solar/Wind Harmer
31.424
957541AF2-048 GEN
Solar/Wind Harmer
2.499
972103AH1-617 GEN
Solar/Wind Harmer
31.441
960911AF2-382 GEN
Solar/Wind Harmer
11.571
971461AH1-227 GEN
Solar/Wind Harmer
7.869
270367AC2-061_GEN
Solar/Wind Harmer
4.734
270186AC1-089 GEN
Solar/Wind Harmer
9.096
970879AG2-548 GEN
Solar/Wind Harmer
11.766
972167AH1-666 GEN
Solar/Wind Harmer
11.731
252507AC2-088 GEN
Solar/Wind Harmer
2.611
958171AF2-111 GEN
Solar/Wind Harmer
36.196
339243AC2-075 GEN1
Solar/Wind Harmer
0.655
252519AF1-045_GEN
Solar/Wind Harmer
5.251
25196008MFTGT1
Adder
1.936
25194608D.CRK4
Adder
2.359
252524AE2-267 GEN
Solar/Wind Harmer
2.256
25196608WSDLE5
Adder
12.281
3429391JKCT 9G
Adder
11.925
970093AG2-073 GEN
Solar/Wind Harmer
7.582
253317AC1-085 GEN4
Solar/Wind Harmer
11.942
946181AF1-283 GEN
Solar/Wind Harmer
18.543
253394AE2-221_GEN
Solar/Wind Harmer
6.388
970455AG2-298 GEN
Solar/Wind Harmer
4.914
970653AG2-424 GEN
Solar/Wind Harmer
0.97
339206AE1-143 GEN
Solar/Wind Harmer
2.962
972273AH1-721 GEN
Adder
115.342
24728705AND G3
Adder
11.088
24728505AND G1
Adder
5.301
970193AG2-126 GEN
Solar/Wind Harmer
20.616
24379505HDWTR1G C
Solar/Wind Harmer
10.862
270240V3-007_GEN2
Solar/Wind Harmer
8.498
253303V4-073 C
Solar/Wind Harmer
0.159
253370AE2-315 SEC1
Adder
2.746
253371AE2-315 SEC2
Adder
2.597
270346AE1-212 GEN
Solar/Wind Harmer
12.332
247642Z2-115 C
Solar/Wind Harmer
0.087
965461AG1-414 GEN
Solar/Wind Harmer
3.09
970289AG2-191 GEN
Solar/Wind Harmer
1.046
270004AE1-209 GEN
Solar/Wind Harmer
7.445
970825AG2-519 GEN
Solar/Wind Harmer
7.662
946031AF1-268 GEN
Solar/Wind Harmer
11.269
24386205FR-12G C
Solar/Wind Harmer
5.816
960071AF2-298 GEN
Solar/Wind Harmer
2.052
339255AE2-071 GEN
Solar/Wind Harmer
1.586
339250AF1-203 GEN
Solar/Wind Harmer
0.817
24690905MDL-1G C
Solar/Wind Harmer
10.842
970781AG2-491 GEN
Solar/Wind Harmer
13.505
962031AG1-047 GEN
Solar/Wind Harmer
4.061
274772LINCOLN ;3U
Adder
11.119
972259AH1-714 GEN
Adder
25.12
274760LEE CO EC;1U
Adder
12.246
274767LEE CO EC;8U
Adder
12.101
274729ELWOOD EC;1P
Adder
21.634
274730ELWOOD EC;6P
Adder
21.634
274734ELWOOD EC;8P
Adder
21.634
274736ELWOOD EC;9P
Adder
21.634
274682WAUKEGAN ;7U
Adder
23.647
237048AF1-022 C
Solar/Wind Helper
0.229
237046AF1-021 C
Solar/Wind Helper
0.396
235058AG1-386 C
Solar/Wind Helper
0.512
23562501BACKB
Solar/Wind Helper
1.065
964991AG1-363 GEN
Solar/Wind Helper
4.388
202652Y1-033 WT C
Solar/Wind Helper
0.652
238127S14_GEN_2
Solar/Wind Helper
0.805
20092526R32
Solar/Wind Helper
1.303
238108AE1-109 GEN1
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20303426NA_O38_P22
Solar/Wind Helper
1.11
203993AD2-133_GEN1
Solar/Wind Helper
1.142
25196808ZIMRHP
Adder
109.659
252516AE2-318_GEN
Solar/Wind Harmer
14.428
252510AF1-249 C
Solar/Wind Harmer
0.6
25196008MFTGT1
Adder
1.999
943111AE2-339 GEN
Solar/Wind Harmer
1.269
25194608D.CRK4
Adder
2.359
3429241JKCT 3G
Adder
16.981
3429421JKCT 10G
Adder
11.925
253316AC1-085 GEN3
Solar/Wind Harmer
11.942
946171AF1-282 GEN
Solar/Wind Harmer
14.264
339211AE2-254 GEN
Solar/Wind Harmer
2.136
24735205WLF2G2
Adder
8.122
253398AE2-221_GEN2
Solar/Wind Harmer
6.388
270222AC2-111 GEN
Solar/Wind Harmer
6.219
944031AF1-071 GEN
Solar/Wind Harmer
1.399
970653AG2-424 GEN
Solar/Wind Harmer
6.706
270273AD2-016 GEN
Solar/Wind Harmer
3.685
24728605AND G2
Adder
5.301
339241AF1-083 GEN
Solar/Wind Harmer
2.292
942081AE2-220 GEN
Solar/Wind Harmer
8.785
270209AC1-174_GEN
Solar/Wind Harmer
5.591
270437AC2-090 C
Solar/Wind Harmer
7.667
270239V3-007_GEN1
Solar/Wind Harmer
2.364
253370AE2-315 SEC1
Adder
2.746
253371AE2-315 SEC2
Adder
2.597
276903AD2-071 C
Solar/Wind Harmer
13.662
963741AG1-226 GEN
Solar/Wind Harmer
61.351
964901AG1-354 GEN
Solar/Wind Harmer
20.45
270594AE1-207 GEN
Solar/Wind Harmer
18.503
270032AE2-172
Solar/Wind Harmer
6.337
270005AE1-210 C O1
Solar/Wind Harmer
7.445
970825AG2-519 GEN
Solar/Wind Harmer
2.854
25326309TAIT D
Adder
1.488
24385905FR-11G C
Solar/Wind Harmer
11.279
24386605FR-22G C
Solar/Wind Harmer
5.837
24791305MDL-5G
Solar/Wind Harmer
3.256
945371AF1-202 GEN
Solar/Wind Harmer
9.414
958861AF2-177 GEN
Solar/Wind Harmer
14.687
274773LINCOLN ;4U
Adder
11.119
274774LINCOLN ;5U
Adder
11.119
274745AC1-111 GEN9
Adder
7.358
274761LEE CO EC;2U
Adder
12.246
274766LEE CO EC;7U
Adder
12.101
274732ELWOOD EC;7P
Adder
21.634
274822ROCKFORD ;11
Adder
25.827
274674JOLIET 9 ;6U
Adder
20.261
274682WAUKEGAN ;7U
Adder
11.397
238185AF2-356 C
Solar/Wind Helper
2.609
20089026BF_G21_K23
Solar/Wind Helper
0.538
238120AE2-309 GEN
Solar/Wind Helper
0.508
238126S14_GEN_1
Solar/Wind Helper
0.805
254303AC2-168 GEN
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.278
23751101LEADS_P59
Solar/Wind Helper
2.213
20084626FORWARD
Solar/Wind Helper
0.4
964201AG1-281 GEN
Solar/Wind Helper
0.541
20091526CHSTN_FL
Solar/Wind Helper
0.651
238109AE1-109 GEN2
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.142
203952AE2-129 C
Solar/Wind Helper
0.526
203855AF2-088 C
Solar/Wind Helper
0.169
209071AE2-133 GEN
Solar/Wind Helper
0.09
946691AF1-333 GEN
Solar/Wind Helper
0.496
946741AF1-338 GEN
Solar/Wind Helper
0.496
961421AF2-433 GEN
Solar/Wind Helper
0.495
957921AF2-086 GEN
Solar/Wind Helper
0.49
961331AF2-424 GEN
Solar/Wind Helper
0.495
208972BECR K09
Solar/Wind Helper
0.37
963161AG1-165 GEN
Solar/Wind Helper
0.492
203830AF1-094 GEN
Solar/Wind Helper
0.492
203979AG1-198 GEN
Solar/Wind Helper
0.295
316095T157 G97
Solar/Wind Helper
1.146
23583801GRNGAP
Solar/Wind Helper
4.253
211065PSPA IPP
Solar/Wind Helper
0.167
209116AE2-175 GEN
Solar/Wind Helper
1.956
961971AG1-040 GEN
Solar/Wind Helper
0.488
20674128FR_U2-059
Solar/Wind Helper
0.004
20671928W4-073
Solar/Wind Helper
0.097
207437AD2-070 GEN
Solar/Wind Helper
0.149
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.111
20715028HAN_X4-015
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.06
959381AF2-229 GEN
Solar/Wind Helper
0.361
20390526W1-045 C
Solar/Wind Helper
0.355
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.08
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.042
228728W1-130C
Solar/Wind Helper
0.056
230434AG1-499 GEN
Solar/Wind Helper
0.24
232432Z2-076 GEN
Solar/Wind Helper
0.069
233901CHERRYDALE C
Solar/Wind Helper
0.239
233940AF2-379 C
Solar/Wind Helper
0.064
205956AE1-196_GEN
Solar/Wind Helper
0.52
205943AE1-185 GEN
Solar/Wind Helper
0.52
233915AB1-141 GEN
Solar/Wind Helper
0.515
205917AD1-020 ES
Solar/Wind Helper
0.366
237025AB1-124 C
Solar/Wind Helper
0.145
237030AB1-096 C
Solar/Wind Helper
0.059
23779801AA1-109
Solar/Wind Helper
0.167
238169AE2-226 GEN1
Solar/Wind Helper
0.55
238170AE2-226 GEN2
Solar/Wind Helper
0.55
207511W3-106 GEN
Solar/Wind Helper
0.029
207510AF2-138 C
Solar/Wind Helper
0.088
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.349
20673728F2S_V4-070
Solar/Wind Helper
0.032
217213AMBOY SO C
Solar/Wind Helper
0.031
219249CENTRALDIV C
Solar/Wind Helper
0.011
205941AD2-115 GEN
Solar/Wind Helper
0.528
20716928W4-060COL
Solar/Wind Helper
0.055
219612MATRIX C
Solar/Wind Helper
0.025
207454AA2-184 E
Solar/Wind Helper
0.33
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.005
20715728PEM_W1-119
Solar/Wind Helper
0.101
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.12
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.524
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233950AC2-186 GEN
Solar/Wind Helper
0.119
232434Z2-077 GEN
Solar/Wind Helper
0.13
233923SMA
Solar/Wind Helper
0.772
233997TMININ_4.2
Solar/Wind Helper
0.21
232406W1-004 FULL
Solar/Wind Helper
0.52
232417X3-008 C
Solar/Wind Helper
0.239
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.442
233987AB2-037 GEN
Solar/Wind Helper
2.403
233933AB2-153 GEN
Solar/Wind Helper
0.238
232422X3-066 FULL
Solar/Wind Helper
0.117
233935AB2-179 C
Solar/Wind Helper
1.3
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
208835TUHI V3-051
Solar/Wind Helper
0.021
23777801MSM_W1-116
Solar/Wind Helper
0.099
203854AF2-039 C
Solar/Wind Helper
0.352
20398826ARMNA MT
Solar/Wind Helper
1.645
941421AE2-139 GEN
Solar/Wind Helper
2.555
209137AF2-361 C
Solar/Wind Helper
1.523
946731AF1-337 GEN
Solar/Wind Helper
0.496
212507AE2-042_GEN
Solar/Wind Helper
1.759
961341AF2-425 GEN
Solar/Wind Helper
0.495
961301AF2-421 GEN
Solar/Wind Helper
0.492
963151AG1-164 GEN
Solar/Wind Helper
0.492
211065PSPA IPP
Solar/Wind Helper
0.167
207518AF1-320_GEN
Solar/Wind Helper
1.705
20675728RH_W2-091
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.032
203975AE1-071-GEN
Solar/Wind Helper
2.659
207484AF2-139 C O1
Solar/Wind Helper
0.091
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
20674628WNG_W3-110
Solar/Wind Helper
0.097
20676328BVR_Y1-020
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.072
207439AE1-081 C O1
Solar/Wind Helper
0.02
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.485
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.172
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.083
20720528MAN_W1-024
Solar/Wind Helper
0.03
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714528FRN_Y2-051
Solar/Wind Helper
0.06
219276PARKLANDSO C
Solar/Wind Helper
0.095
20715828PEM_W1-120
Solar/Wind Helper
0.101
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.12
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.057
228729W2-030 C
Solar/Wind Helper
0.116
233996TM1833_GEN
Solar/Wind Helper
0.21
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.52
232408W1-005 C
Solar/Wind Helper
0.52
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.52
233944AB2-135 GEN
Solar/Wind Helper
0.605
233918AB1-142 GEN
Solar/Wind Helper
0.515
235063AE1-101 C2
Solar/Wind Helper
1.456
205916AD1-020 GEN
Solar/Wind Helper
1.701
237001AB1-127_GEN
Solar/Wind Helper
0.386
23777901MDS_W4-102
Solar/Wind Helper
0.149
208835TUHI V3-051
Solar/Wind Helper
0.021
238175AF1-290_GEN
Solar/Wind Helper
0.125
957741AF2-068 GEN
Solar/Wind Harmer
8.369
LAGNLTFEXP_LAGN->PJM
CLTF
25.015
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.459
TVALTFEXP_TVA->PJM
CLTF
12.705
NYPJM->LTFIMP_NY
CLTF
6.23
LGEELTFEXP_LGEE->PJM
CLTF
9.895
WECLTFEXP_WEC->PJM
CLTF
5.031
AG2-052LTFEXP_AG2-052->PJM
LTF
0.308
AH1-155LTFEXP_AH1-155->PJM
LTF
0.462
CBM West 1LTFEXP_CBM-W1->PJM
CBM
171.353
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.863
MECLTFEXP_MEC->PJM
CLTF
22.066
SIGELTFEXP_SIGE->PJM
CLTF
0.733
CPLELTFEXP_CPLE->PJM
CLTF
6.636
CBM West 2LTFEXP_CBM-W2->PJM
CBM
174.171
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 115.34 MW.

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.96 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6183.32
MW Contribution:
81.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
49.394
243186AF1-051 GEN
50/50
14.291
24723005RIVRG1
Adder
37.759
24723105RIVRG2
Adder
37.759
970913AG2-568 GEN
Solar/Wind Harmer
11.514
24728205BUCHG1
Adder
7.18
971225AH1-072 GEN
Solar/Wind Harmer
3.076
971227AH1-073 GEN
Solar/Wind Harmer
3.076
270214AC2-123 GEN
Solar/Wind Harmer
3.345
971277AH1-098 GEN
Solar/Wind Harmer
5.707
270583AD2-179 GEN
Solar/Wind Harmer
13.318
927014AC1-188 GEN
Solar/Wind Harmer
2.104
966021AG1-471 GEN
Solar/Wind Harmer
6.141
339231AF1-038_GEN
Solar/Wind Harmer
2.061
971485AH1-239 GEN
Solar/Wind Harmer
9.077
942891AE2-308 GEN
Solar/Wind Harmer
11.161
971073AG2-665 GEN
Solar/Wind Harmer
8.927
970879AG2-548 GEN
Solar/Wind Harmer
1.298
339236AF1-050_GEN
Solar/Wind Harmer
2.021
964781AG1-341 GEN
Solar/Wind Harmer
11.789
964571AG1-320 GEN
Solar/Wind Harmer
8.983
972043AH1-570 GEN
Solar/Wind Harmer
2.731
972045AH1-571 GEN
Solar/Wind Harmer
2.185
971125AH1-004 GEN
Solar/Wind Harmer
4.363
970107AG2-081 GEN
Solar/Wind Harmer
3.272
962581AG1-107 GEN
Solar/Wind Harmer
5.294
961491AF2-440 GEN
Solar/Wind Harmer
2.2
252509AD1-136 GEN
Solar/Wind Harmer
0.26
945391AF1-204 GEN
Solar/Wind Harmer
13.723
25183208HLCRTG
Solar/Wind Harmer
5.886
24721605FLATG1
50/50
3.326
957241AF2-018 GEN
Solar/Wind Harmer
8.033
270053AF1-130 C
Solar/Wind Harmer
32.096
270399AC1-101 GEN
Solar/Wind Harmer
7.582
270400AC1-102 GEN
Solar/Wind Harmer
7.582
941621AE2-160 GEN
Adder
5.453
971313AH1-133 GEN
Solar/Wind Harmer
9.358
970281AG2-184 GEN
Solar/Wind Harmer
32.451
971061AG2-657 GEN
Solar/Wind Harmer
13.518
24734705WLF1G3
Adder
8.32
24734805WLF1G4
Adder
8.32
24734905WLF1G5
Adder
8.32
962211AG1-066 GEN
Solar/Wind Harmer
3.487
966391AG1-508 GEN
Solar/Wind Harmer
4.969
24735105WLF2G1
Adder
8.13
971331AH1-145 GEN
Solar/Wind Harmer
12.844
971329AH1-144 GEN
Solar/Wind Harmer
8.204
971985AH1-537 GEN
Solar/Wind Harmer
23.127
971981AH1-535 GEN
Solar/Wind Harmer
12.746
270069AE2-166 C O1
Solar/Wind Harmer
10.572
3429211JKCT 2G
Adder
12.98
972163AH1-664 GEN
Solar/Wind Harmer
10.818
972165AH1-665 GEN
Solar/Wind Harmer
8.654
339216AC1-074 GEN
Solar/Wind Harmer
1.805
270444AC2-157 GEN1
Solar/Wind Harmer
5.93
270445AC2-157 GEN2
Solar/Wind Harmer
5.93
270291AC1-194 GEN
Solar/Wind Harmer
5.169
25196108MFTGT2
Adder
1.544
25196108MFTGT2
Adder
1.434
944221AF1-090 GEN
Solar/Wind Harmer
10.637
25196408WSDLE3
Adder
8.509
25196308WSDLE2
Adder
8.435
25196208WSDLE1
Adder
8.414
25196708WSDLE6
Adder
8.393
25196508WSDLE4
Adder
8.182
963841AG1-237 GEN
Solar/Wind Harmer
10.358
276763AC1-053 GEN1
Solar/Wind Harmer
3.74
276764AC1-053 GEN2
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
2.091
276848AB2-070 GEN3
Solar/Wind Harmer
2.091
276849AB2-070 GEN2
Solar/Wind Harmer
2.091
270356AE2-297 GEN
Solar/Wind Harmer
4.331
24386405FR-21G C
Solar/Wind Harmer
4.038
24387005FR-3G C
Solar/Wind Harmer
3.714
274853TWINGROVE;U1
Solar/Wind Harmer
6.662
274854TWINGROVE;U2
Solar/Wind Harmer
6.522
946581AF1-322 GEN
Solar/Wind Harmer
9.458
24691005MDL-2G C
Solar/Wind Harmer
3.418
270197AD1-017 GEN1
Solar/Wind Harmer
1.417
276726Z2-087_GEN
Solar/Wind Harmer
7.262
959341AF2-225 GEN
Solar/Wind Harmer
13.777
972267AH1-718 GEN
Adder
3.77
274823ROCKFORD ;21
Adder
17.467
274744AC1-111 GEN8
Adder
4.935
274746AC1-111 G10
Adder
4.935
274728ELWOOD EC;5P
Adder
14.442
274731ELWOOD EC;2P
Adder
14.442
274733ELWOOD EC;3P
Adder
14.442
274735ELWOOD EC;4P
Adder
14.442
274675JOLIET 29;7U
Adder
26.921
274675JOLIET 29;7U
Adder
15.118
23750501ELLIOTTS
Solar/Wind Helper
0.617
23652301WDPWR_K20
Solar/Wind Helper
0.134
241997AF1-093 GEN
Solar/Wind Helper
0.235
241985AE1-237 GEN
Solar/Wind Helper
0.229
241982AE2-343 S C
Solar/Wind Helper
0.206
203955AF1-039 C O1
Solar/Wind Helper
0.338
23750701CROSSCHOOL
Solar/Wind Helper
1.086
20089126CSLMN_L13
Solar/Wind Helper
0.537
20089226LOOKOUT
Solar/Wind Helper
0.536
238118U2-030_1
Solar/Wind Helper
0.261
24289405MTG1
50/50
12.684
24721805FLATG3
50/50
3.326
243186AF1-051 GEN
50/50
14.291
24318705GVG2
50/50
13.247
962761AG1-125 GEN
Solar/Wind Harmer
91.718
970149AG2-104 GEN
Solar/Wind Harmer
56.636
970155AG2-107 GEN
Solar/Wind Harmer
39.993
24723205RIVRG3
Adder
37.759
972203AH1-686 GEN
Adder
4.539
24686505CER G6
Adder
16.11
944971AF1-162 GEN
Solar/Wind Harmer
12.651
971403AH1-188 GEN
Solar/Wind Harmer
25.286
270331AC1-082 GEN3
Solar/Wind Harmer
0.847
960001AF2-291 GEN
Solar/Wind Harmer
5.171
24728305BUCHG2
Adder
7.18
971687AH1-348 GEN
Solar/Wind Harmer
1.537
24735205WLF2G2
Adder
8.13
270336AE1-100 GEN
Solar/Wind Harmer
2.029
970091AG2-072 GEN
Adder
90.254
943811AF1-049 GEN
Solar/Wind Harmer
4.254
339211AE2-254 GEN
Solar/Wind Harmer
1.701
339241AF1-083 GEN
Solar/Wind Harmer
1.857
971073AG2-665 GEN
Solar/Wind Harmer
1.298
964901AG1-354 GEN
Solar/Wind Harmer
16.708
3429241JKCT 3G
Adder
13.15
970653AG2-424 GEN
Solar/Wind Harmer
5.33
3429421JKCT 10G
Adder
9.153
943111AE2-339 GEN
Solar/Wind Harmer
0.965
339221AD2-048_GEN
Solar/Wind Harmer
1.667
945681AF1-233 GEN
Solar/Wind Harmer
20.299
25196008MFTGT1
Adder
1.401
25196808ZIMRHP
Adder
75.86
252516AE2-318_GEN
Solar/Wind Harmer
9.778
252510AF1-249 C
Solar/Wind Harmer
0.407
270173AC1-122 GEN
Solar/Wind Harmer
1.632
25194608D.CRK4
Adder
1.596
965911AG1-460 GEN
Solar/Wind Harmer
1.34
24728605AND G2
Adder
3.684
963741AG1-226 GEN
Solar/Wind Harmer
43.023
276621W2-048 GEN
Solar/Wind Harmer
5.925
276686W4-005 GEN3
Solar/Wind Harmer
2.856
24385905FR-11G C
Solar/Wind Harmer
7.803
24386605FR-22G C
Solar/Wind Harmer
4.038
24791305MDL-5G
Solar/Wind Harmer
2.228
270574AD1-017 GEN2
Solar/Wind Harmer
4.722
276655WTG1_EQ
Solar/Wind Harmer
8.017
276656WTG2_EQ
Solar/Wind Harmer
1.061
939741AE1-205 GEN
Solar/Wind Harmer
18.37
274761LEE CO EC;2U
Adder
8.393
274766LEE CO EC;7U
Adder
8.294
274822ROCKFORD ;11
Adder
17.595
274828WAUKEGAN ;BP
Adder
9.796
274682WAUKEGAN ;7U
Adder
15.93
274745AC1-111 GEN9
Adder
4.935
274732ELWOOD EC;7P
Adder
14.442
274674JOLIET 9 ;6U
Adder
13.524
274676JOLIET 29;8U
Adder
26.921
254303AC2-168 GEN
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.235
238185AF2-356 C
Solar/Wind Helper
2.008
20089026BF_G21_K23
Solar/Wind Helper
0.425
24289405MTG1
50/50
12.684
24722005FLATG5
50/50
3.326
24721905FLATG4
50/50
60.751
24318705GVG2
50/50
13.247
962771AG1-126 GEN
Solar/Wind Harmer
91.718
970153AG2-106 GEN
Solar/Wind Harmer
39.993
24686405CER G5
Adder
15.983
270330AC1-082 GEN2
Solar/Wind Harmer
0.845
270329AC1-082 GEN1
Solar/Wind Harmer
0.845
960911AF2-382 GEN
Solar/Wind Harmer
12.012
972103AH1-617 GEN
Solar/Wind Harmer
30.905
971461AH1-227 GEN
Solar/Wind Harmer
7.89
971191AH1-055 GEN
Solar/Wind Harmer
28.586
270346AE1-212 GEN
Solar/Wind Harmer
13.435
943031AE2-326 GEN
Solar/Wind Harmer
5.264
958121AF2-106 GEN
Solar/Wind Harmer
6.036
957541AF2-048 GEN
Solar/Wind Harmer
2.104
972273AH1-721 GEN
Adder
96.087
270030AE2-140 GEN
Solar/Wind Harmer
23
970093AG2-073 GEN
Solar/Wind Harmer
5.967
339206AE1-143 GEN
Solar/Wind Harmer
2.39
970879AG2-548 GEN
Solar/Wind Harmer
8.927
339255AE2-071 GEN
Solar/Wind Harmer
1.308
339250AF1-203 GEN
Solar/Wind Harmer
0.673
970653AG2-424 GEN
Solar/Wind Harmer
0.771
970455AG2-298 GEN
Solar/Wind Harmer
3.861
3429391JKCT 9G
Adder
9.153
270186AC1-089 GEN
Solar/Wind Harmer
6.641
339243AC2-075 GEN1
Solar/Wind Harmer
0.489
270367AC2-061_GEN
Solar/Wind Harmer
3.424
972167AH1-666 GEN
Solar/Wind Harmer
8.599
958171AF2-111 GEN
Solar/Wind Harmer
25.759
270018AE2-047 C O1
Solar/Wind Harmer
1.267
252507AC2-088 GEN
Solar/Wind Harmer
1.823
25196008MFTGT1
Adder
1.357
970193AG2-126 GEN
Solar/Wind Harmer
14.771
252519AF1-045_GEN
Solar/Wind Harmer
3.559
25194608D.CRK4
Adder
1.596
252524AE2-267 GEN
Solar/Wind Harmer
1.519
25196608WSDLE5
Adder
8.266
942481AE2-261 GEN
Solar/Wind Harmer
28.724
24728705AND G3
Adder
7.705
24728505AND G1
Adder
3.684
957381AF2-032 GEN
Solar/Wind Harmer
1.919
962751AG1-124 GEN
Solar/Wind Harmer
8.593
276785W4-005 GEN1
Solar/Wind Harmer
2.856
971993AH1-541 GEN
Solar/Wind Harmer
8.726
24386205FR-12G C
Solar/Wind Harmer
4.023
965091AG1-374 GEN
Solar/Wind Harmer
27.739
959611AF2-252 GEN
Solar/Wind Harmer
2.15
24690905MDL-1G C
Solar/Wind Harmer
7.42
970781AG2-491 GEN
Solar/Wind Harmer
9.243
274760LEE CO EC;1U
Adder
8.393
274767LEE CO EC;8U
Adder
8.294
274682WAUKEGAN ;7U
Adder
15.93
274729ELWOOD EC;1P
Adder
14.442
274730ELWOOD EC;6P
Adder
14.442
274734ELWOOD EC;8P
Adder
14.442
274736ELWOOD EC;9P
Adder
14.442
237048AF1-022 C
Solar/Wind Helper
0.181
237046AF1-021 C
Solar/Wind Helper
0.315
235058AG1-386 C
Solar/Wind Helper
0.425
202652Y1-033 WT C
Solar/Wind Helper
0.512
23562501BACKB
Solar/Wind Helper
0.816
964991AG1-363 GEN
Solar/Wind Helper
3.339
25194408D.CRK1
Adder
7.34
25194508D.CRK3
Adder
1.372
276916AD2-100_GEN
Solar/Wind Harmer
20.233
276911AD2-131_GEN
Solar/Wind Harmer
4.089
970241AG2-163 GEN
Solar/Wind Harmer
23.902
276615X2-022 GEN
Solar/Wind Harmer
1.861
276838X2-022 GEN2
Solar/Wind Harmer
0.221
274880W4-005 GEN4
Solar/Wind Harmer
2.856
276174W4-005 GEN2
Solar/Wind Harmer
2.856
24387305FR-4G C
Solar/Wind Harmer
4.769
966841AG1-555 GEN
Solar/Wind Harmer
2.357
960611AF2-352 GEN
Solar/Wind Harmer
2.15
270180AB1-006 GEN1
Solar/Wind Harmer
6.648
24697605MDL-3G C
Solar/Wind Harmer
3.407
24755605MDL-5G
Solar/Wind Harmer
2.228
24697905MDL-4G C
Solar/Wind Harmer
2.121
270181AB1-006 GEN2
Solar/Wind Harmer
0.661
942111AE2-223 GEN
Solar/Wind Harmer
7.529
24728805RICHG1
Adder
3.447
24728905RICHG2
Adder
3.447
274764LEE CO EC;5U
Adder
8.413
274765LEE CO EC;6U
Adder
8.413
274762LEE CO EC;3U
Adder
8.393
274763LEE CO EC;4U
Adder
8.314
972235AH1-702 GEN1
Adder
2.262
972236AH1-702 GEN2
Adder
1.967
274683WAUKEGAN ;8U
Adder
18.687
274683WAUKEGAN ;8U
Adder
15.753
274696ROCKY RD ;4P
Adder
10.103
274695ROCKY RD ;2P
Adder
9.87
274693ROCKY RD ;1P
Adder
9.773
274697ROCKY RD ;3P
Adder
2.681
274674JOLIET 9 ;6U
Adder
13.524
237043AE2-125 C
Solar/Wind Helper
0.166
254304AE2-114 C
Solar/Wind Helper
0.201
254305AE2-115 C
Solar/Wind Helper
0.201
962101AG1-054 GEN
Solar/Wind Helper
0.598
241967AE2-285_GEN
Solar/Wind Helper
0.586
241801AE1-079 GEN
Solar/Wind Helper
0.229
23585401KL_K28_T16
Solar/Wind Helper
1.176
23751201ROTHROCK
Solar/Wind Helper
0.671
235054AD2-180 GEN
Solar/Wind Helper
1.553
238117U2-030
Solar/Wind Helper
0.261
946071AF1-272 GEN
Solar/Wind Helper
2.433
20083426SW_E13_K22
Solar/Wind Helper
0.05
945421AF1-207 GEN
Solar/Wind Harmer
3.217
LAGNLTFEXP_LAGN->PJM
CLTF
21.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.819
TVALTFEXP_TVA->PJM
CLTF
11.07
NYPJM->LTFIMP_NY
CLTF
4.806
LGEELTFEXP_LGEE->PJM
CLTF
7.592
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.205
AH1-155LTFEXP_AH1-155->PJM
LTF
0.307
CBM West 1LTFEXP_CBM-W1->PJM
CBM
111.112
CBM South 1LTFEXP_CBM-S1->PJM
CBM
41.561
MECLTFEXP_MEC->PJM
CLTF
15.956
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
7.6
CBM West 2LTFEXP_CBM-W2->PJM
CBM
138.522
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 96.09 MW.

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.18 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4976.63
MW Contribution:
77.28
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.475
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
24.531
270399AC1-101 GEN
Solar/Wind Harmer
3.431
270400AC1-102 GEN
Solar/Wind Harmer
3.431
941621AE2-160 GEN
Adder
4.685
970281AG2-184 GEN
Solar/Wind Harmer
20.069
971313AH1-133 GEN
Solar/Wind Harmer
4.633
971061AG2-657 GEN
Solar/Wind Harmer
5.63
24734705WLF1G3
Adder
7.275
24734805WLF1G4
Adder
7.275
24734905WLF1G5
Adder
7.275
971985AH1-537 GEN
Solar/Wind Harmer
2.606
24735105WLF2G1
Adder
7.131
966391AG1-508 GEN
Solar/Wind Harmer
1.323
971331AH1-145 GEN
Solar/Wind Harmer
10.902
971329AH1-144 GEN
Solar/Wind Harmer
4.007
971981AH1-535 GEN
Solar/Wind Harmer
5.247
972163AH1-664 GEN
Solar/Wind Harmer
8.578
972165AH1-665 GEN
Solar/Wind Harmer
6.87
3429211JKCT 2G
Adder
12.836
339216AC1-074 GEN
Solar/Wind Harmer
0.202
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.606
25196108MFTGT2
Adder
1.492
24289405MTG1
50/50
10.896
24318705GVG2
50/50
10.829
24722005FLATG5
50/50
2.475
24721905FLATG4
50/50
45.211
24686405CER G5
Adder
13.963
971191AH1-055 GEN
Solar/Wind Harmer
25.524
960911AF2-382 GEN
Solar/Wind Harmer
7.256
972103AH1-617 GEN
Solar/Wind Harmer
19.113
971461AH1-227 GEN
Solar/Wind Harmer
4.836
270346AE1-212 GEN
Solar/Wind Harmer
7.826
943031AE2-326 GEN
Solar/Wind Harmer
4.478
970879AG2-548 GEN
Solar/Wind Harmer
5.846
958121AF2-106 GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
6.527
972167AH1-666 GEN
Solar/Wind Harmer
6.143
972273AH1-721 GEN
Adder
91.222
3429391JKCT 9G
Adder
9.095
970455AG2-298 GEN
Solar/Wind Harmer
2.913
958171AF2-111 GEN
Solar/Wind Harmer
18.695
252507AC2-088 GEN
Solar/Wind Harmer
0.336
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
9.098
25196308WSDLE2
Adder
9.019
25196208WSDLE1
Adder
8.997
25196708WSDLE6
Adder
8.974
25196508WSDLE4
Adder
8.748
253406AD2-031_GEN
Solar/Wind Harmer
0.516
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.692
270069AE2-166 C O1
Solar/Wind Harmer
6.22
270356AE2-297 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.926
963841AG1-237 GEN
Solar/Wind Harmer
2.866
24386405FR-21G C
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.257
276848AB2-070 GEN3
Solar/Wind Harmer
0.256
276849AB2-070 GEN2
Solar/Wind Harmer
0.257
970289AG2-191 GEN
Solar/Wind Harmer
1.233
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.69
274854TWINGROVE;U2
Solar/Wind Harmer
0
25306009OHH W.
Adder
2.654
253372AE2-315 SEC3
Adder
1.743
253372AE2-315 SEC3
Adder
1.743
270543AE2-219 C
Solar/Wind Harmer
4.484
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.721
247536S-71 GEN
Solar/Wind Harmer
0.254
971611AH1-305 GEN
Solar/Wind Harmer
3.778
946321AF1-296 GEN
Solar/Wind Harmer
3.554
274877BISHOP HL;1U
Solar/Wind Harmer
0.211
971609AH1-304 GEN
Solar/Wind Harmer
1.034
964611AG1-324 GEN
Solar/Wind Harmer
2.468
970169AG2-114 GEN
Solar/Wind Harmer
6.325
276741O09 GEN1
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.763
926823AC1-168 GEN
Solar/Wind Harmer
1.07
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.116
274856ECOGROVE ;U1
Solar/Wind Harmer
0.147
274823ROCKFORD ;21
Adder
17.485
971171AH1-044 GEN
Solar/Wind Harmer
12.516
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971675AH1-338 GEN
Solar/Wind Harmer
2.437
971411AH1-196 GEN
Solar/Wind Harmer
9.369
970073AG2-061 GEN
Solar/Wind Harmer
2.078
274744AC1-111 GEN8
Adder
4.965
274746AC1-111 G10
Adder
4.965
970833AG2-524 GEN
Solar/Wind Harmer
6.809
970833AG2-524 GEN
Solar/Wind Harmer
4.54
274728ELWOOD EC;5P
Adder
14.558
274731ELWOOD EC;2P
Adder
14.558
274733ELWOOD EC;3P
Adder
14.558
274735ELWOOD EC;4P
Adder
14.558
274675JOLIET 29;7U
Adder
27.142
960591AF2-350 GEN
Solar/Wind Harmer
6.155
23750501ELLIOTTS
Solar/Wind Helper
0.598
23652301WDPWR_K20
Solar/Wind Helper
0.127
970653AG2-424 GEN
Solar/Wind Harmer
0.745
25196008MFTGT1
Adder
1.411
252519AF1-045_GEN
Solar/Wind Harmer
3.801
25194608D.CRK4
Adder
1.702
25196608WSDLE5
Adder
8.838
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.158
962771AG1-126 GEN
Solar/Wind Harmer
27.311
970153AG2-106 GEN
Solar/Wind Harmer
17.44
253394AE2-221_GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
10.239
24728705AND G3
Adder
7.833
24728505AND G1
Adder
3.745
270030AE2-140 GEN
Solar/Wind Harmer
13.518
942481AE2-261 GEN
Solar/Wind Harmer
19.808
957381AF2-032 GEN
Solar/Wind Harmer
1.5
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.022
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.714
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.48
270004AE1-209 GEN
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
4.865
965091AG1-374 GEN
Solar/Wind Harmer
19.301
946031AF1-268 GEN
Solar/Wind Harmer
6.123
959611AF2-252 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
970191AG2-125 GEN
Solar/Wind Harmer
1.638
965931AG1-462 GEN
Solar/Wind Harmer
16.203
971087AG2-675 GEN
Solar/Wind Harmer
3.389
274878BISHOP HL;2U
Solar/Wind Harmer
0.211
276782AC1-033 GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.45
970571AG2-364 GEN
Solar/Wind Harmer
12.579
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.386
274767LEE CO EC;8U
Adder
8.287
959091AF2-200 GEN
Solar/Wind Harmer
12.516
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
946671AF1-331 GEN
Solar/Wind Harmer
0.666
276868AE1-113 GEN
Solar/Wind Harmer
1.25
274879MINONK ;1U
Solar/Wind Harmer
0.261
274682WAUKEGAN ;7U
Adder
16.004
274862TOP CROP ;2U
Solar/Wind Harmer
0.839
943121AE2-341 GEN
Solar/Wind Harmer
10.39
943591AF1-030 GEN
Solar/Wind Harmer
6.91
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
14.558
274730ELWOOD EC;6P
Adder
14.558
274734ELWOOD EC;8P
Adder
14.558
274736ELWOOD EC;9P
Adder
14.558
970707AG2-453 GEN
Solar/Wind Harmer
20.15
274887GEN-1.85
Solar/Wind Harmer
0.16
276843GEN-1.7
Solar/Wind Harmer
0.199
276806AD2-047 C O1
Solar/Wind Harmer
3.488
237048AF1-022 C
Solar/Wind Helper
0.175
237046AF1-021 C
Solar/Wind Helper
0.301
235058AG1-386 C
Solar/Wind Helper
0.387
23562501BACKB
Solar/Wind Helper
0.811
24289405MTG1
50/50
10.896
243186AF1-051 GEN
50/50
11.683
24318705GVG2
50/50
10.829
24721805FLATG3
50/50
2.475
24723205RIVRG3
Adder
32.69
972203AH1-686 GEN
Adder
3.965
24686505CER G6
Adder
14.074
944971AF1-162 GEN
Solar/Wind Harmer
10.992
971403AH1-188 GEN
Solar/Wind Harmer
15.251
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
6.196
971687AH1-348 GEN
Solar/Wind Harmer
0.943
24735205WLF2G2
Adder
7.131
971073AG2-665 GEN
Solar/Wind Harmer
1.329
970091AG2-072 GEN
Adder
86.562
945681AF1-233 GEN
Solar/Wind Harmer
14.491
3429241JKCT 3G
Adder
13.004
3429421JKCT 10G
Adder
9.095
970653AG2-424 GEN
Solar/Wind Harmer
3.596
964901AG1-354 GEN
Solar/Wind Harmer
11.126
25196808ZIMRHP
Adder
79.991
25196008MFTGT1
Adder
1.457
252516AE2-318_GEN
Solar/Wind Harmer
8.161
252510AF1-249 C
Solar/Wind Harmer
0.055
25194608D.CRK4
Adder
1.702
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.045
962761AG1-125 GEN
Solar/Wind Harmer
27.311
970149AG2-104 GEN
Solar/Wind Harmer
14.748
970155AG2-107 GEN
Solar/Wind Harmer
17.44
253398AE2-221_GEN2
Solar/Wind Harmer
0
24728605AND G2
Adder
3.745
970773AG2-487 GEN
Solar/Wind Harmer
1.199
963741AG1-226 GEN
Solar/Wind Harmer
15.765
965911AG1-460 GEN
Solar/Wind Harmer
1.325
943811AF1-049 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.832
276621W2-048 GEN
Solar/Wind Harmer
0.329
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.31
270594AE1-207 GEN
Solar/Wind Harmer
7.264
270032AE2-172
Solar/Wind Harmer
4.324
270273AD2-016 GEN
Solar/Wind Harmer
0.662
270005AE1-210 C O1
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
2.292
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.961
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.933
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.248
276708O09 GEN2
Solar/Wind Harmer
0.223
970569AG2-363 GEN
Solar/Wind Harmer
18.869
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.386
274766LEE CO EC;7U
Adder
8.287
25326309TAIT D
Adder
0.988
945371AF1-202 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
7.523
939401AE1-172 GEN
Solar/Wind Harmer
4.684
274822ROCKFORD ;11
Adder
17.613
957471AF2-041 GEN
Solar/Wind Harmer
18.774
959081AF2-199 GEN
Solar/Wind Harmer
6.258
971067AG2-660 GEN
Solar/Wind Harmer
2.086
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.135
971997AH1-543 GEN
Solar/Wind Harmer
3.283
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.729
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.929
274828WAUKEGAN ;BP
Adder
9.84
274682WAUKEGAN ;7U
Adder
16.004
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.692
276691AA1-018 GEN1
Solar/Wind Harmer
1.009
274745AC1-111 GEN9
Adder
4.965
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.558
274674JOLIET 9 ;6U
Adder
13.632
965651AG1-433 GEN
Solar/Wind Harmer
1.811
274676JOLIET 29;8U
Adder
9.572
238185AF2-356 C
Solar/Wind Helper
1.975
970373AG2-245 GEN
Solar/Wind Harmer
5.443
243186AF1-051 GEN
50/50
11.683
24721705FLATG2
50/50
36.759
24723005RIVRG1
Adder
32.69
24723105RIVRG2
Adder
32.69
970913AG2-568 GEN
Solar/Wind Harmer
8.105
24728205BUCHG1
Adder
6.196
971225AH1-072 GEN
Solar/Wind Harmer
1.885
971227AH1-073 GEN
Solar/Wind Harmer
1.885
971277AH1-098 GEN
Solar/Wind Harmer
3.388
971073AG2-665 GEN
Solar/Wind Harmer
5.846
970879AG2-548 GEN
Solar/Wind Harmer
1.329
270583AD2-179 GEN
Solar/Wind Harmer
7.872
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942891AE2-308 GEN
Solar/Wind Harmer
7.677
972043AH1-570 GEN
Solar/Wind Harmer
1.99
972045AH1-571 GEN
Solar/Wind Harmer
1.594
971125AH1-004 GEN
Solar/Wind Harmer
3.042
970107AG2-081 GEN
Solar/Wind Harmer
2.281
966021AG1-471 GEN
Solar/Wind Harmer
4.034
252509AD1-136 GEN
Solar/Wind Harmer
0.037
971485AH1-239 GEN
Solar/Wind Harmer
5.968
964571AG1-320 GEN
Solar/Wind Harmer
6.787
964781AG1-341 GEN
Solar/Wind Harmer
7.81
25183208HLCRTG
Solar/Wind Harmer
0
971587AH1-292 GEN
Solar/Wind Harmer
5.311
25194408D.CRK1
Adder
7.827
25194508D.CRK3
Adder
1.463
945391AF1-204 GEN
Solar/Wind Harmer
7.253
24728805RICHG1
Adder
3.656
24728905RICHG2
Adder
3.656
970241AG2-163 GEN
Solar/Wind Harmer
3.886
276916AD2-100_GEN
Solar/Wind Harmer
13.944
276911AD2-131_GEN
Solar/Wind Harmer
0.919
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.068
276838X2-022 GEN2
Solar/Wind Harmer
0.37
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.743
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.844
970291AG2-192 GEN
Solar/Wind Harmer
0.389
971613AH1-306 GEN
Solar/Wind Harmer
3.113
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
970883AG2-550 GEN
Solar/Wind Harmer
6.406
970885AG2-551 GEN
Solar/Wind Harmer
2.135
942111AE2-223 GEN
Solar/Wind Harmer
2.08
270031AE2-169
Solar/Wind Harmer
3.483
270599AE1-208 GEN
Solar/Wind Harmer
5.804
276645AC1-214 GEN1
Solar/Wind Harmer
0.248
964611AG1-324 GEN
Solar/Wind Harmer
0.475
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.019
247621Y3-024
Adder
0.218
270201AC2-176 GEN
Solar/Wind Harmer
0
25322209TAIT E
Adder
8.794
25322209TAIT E
Adder
8.596
274764LEE CO EC;5U
Adder
8.405
274765LEE CO EC;6U
Adder
8.405
274762LEE CO EC;3U
Adder
8.386
274763LEE CO EC;4U
Adder
8.307
938861AE1-114 GEN
Solar/Wind Harmer
3.56
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.263
972236AH1-702 GEN2
Adder
1.968
971341AH1-150 GEN
Solar/Wind Harmer
12.516
971343AH1-151 GEN
Solar/Wind Harmer
12.516
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.353
962691AG1-118 GEN
Solar/Wind Harmer
18.68
274683WAUKEGAN ;8U
Adder
18.772
274683WAUKEGAN ;8U
Adder
15.824
274696ROCKY RD ;4P
Adder
10.15
274695ROCKY RD ;2P
Adder
9.916
274693ROCKY RD ;1P
Adder
9.818
274697ROCKY RD ;3P
Adder
2.694
958481AF2-142 GEN
Solar/Wind Harmer
9.318
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
15.453
276893AG1-478 C
Solar/Wind Harmer
0.412
274674JOLIET 9 ;6U
Adder
13.632
944541AF1-119 GEN
Solar/Wind Harmer
0.412
960971AF2-388 GEN
Solar/Wind Harmer
3.621
274888KELLY CRK;1U
Solar/Wind Harmer
0.359
276776AD2-060 GEN
Solar/Wind Harmer
0.657
958011AF2-095 GEN
Solar/Wind Harmer
8.864
970941AG2-585 GEN
Solar/Wind Harmer
3.385
23585401KL_K28_T16
Solar/Wind Helper
1.157
237043AE2-125 C
Solar/Wind Helper
0.157
23751201ROTHROCK
Solar/Wind Helper
0.666
235054AD2-180 GEN
Solar/Wind Helper
1.531
LAGNLTFEXP_LAGN->PJM
CLTF
19.698
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23
TVALTFEXP_TVA->PJM
CLTF
10.208
NYPJM->LTFIMP_NY
CLTF
4.626
LGEELTFEXP_LGEE->PJM
CLTF
7.468
WECLTFEXP_WEC->PJM
CLTF
3.435
AG2-052LTFEXP_AG2-052->PJM
LTF
0.207
AH1-155LTFEXP_AH1-155->PJM
LTF
0.311
CBM West 1LTFEXP_CBM-W1->PJM
CBM
115.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.783
MECLTFEXP_MEC->PJM
CLTF
15.666
SIGELTFEXP_SIGE->PJM
CLTF
0.545
CPLELTFEXP_CPLE->PJM
CLTF
6.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.098
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 91.22 MW.

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.41 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5987.66
MW Contribution:
94.18
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
970913AG2-568 GEN
Solar/Wind Harmer
11.956
24728205BUCHG1
Adder
7.739
270214AC2-123 GEN
Solar/Wind Harmer
3.869
971225AH1-072 GEN
Solar/Wind Harmer
3.319
971227AH1-073 GEN
Solar/Wind Harmer
3.319
971277AH1-098 GEN
Solar/Wind Harmer
6.62
270583AD2-179 GEN
Solar/Wind Harmer
16.289
927014AC1-188 GEN
Solar/Wind Harmer
2.364
971073AG2-665 GEN
Solar/Wind Harmer
10.717
970879AG2-548 GEN
Solar/Wind Harmer
1.558
942891AE2-308 GEN
Solar/Wind Harmer
13.25
339231AF1-038_GEN
Solar/Wind Harmer
2.384
972043AH1-570 GEN
Solar/Wind Harmer
3.285
972045AH1-571 GEN
Solar/Wind Harmer
2.628
971125AH1-004 GEN
Solar/Wind Harmer
5.238
970107AG2-081 GEN
Solar/Wind Harmer
3.929
966021AG1-471 GEN
Solar/Wind Harmer
7.071
971485AH1-239 GEN
Solar/Wind Harmer
10.457
962581AG1-107 GEN
Solar/Wind Harmer
6.569
961491AF2-440 GEN
Solar/Wind Harmer
2.73
339236AF1-050_GEN
Solar/Wind Harmer
2.347
964781AG1-341 GEN
Solar/Wind Harmer
13.643
964571AG1-320 GEN
Solar/Wind Harmer
10.544
252509AD1-136 GEN
Solar/Wind Harmer
0.325
25183208HLCRTG
Solar/Wind Harmer
7.535
25194408D.CRK1
Adder
9.34
25194508D.CRK3
Adder
1.746
945391AF1-204 GEN
Solar/Wind Harmer
16.433
942671AE2-283 GEN
Solar/Wind Harmer
5.701
24728805RICHG1
Adder
4.399
24728905RICHG2
Adder
4.399
253415AE1-040 GEN
Solar/Wind Harmer
1.308
276916AD2-100_GEN
Solar/Wind Harmer
24.22
276911AD2-131_GEN
Solar/Wind Harmer
4.895
970241AG2-163 GEN
Solar/Wind Harmer
28.803
276615X2-022 GEN
Solar/Wind Harmer
2.236
276838X2-022 GEN2
Solar/Wind Harmer
0.266
926881AC1-175 GEN
Solar/Wind Harmer
6.354
274880W4-005 GEN4
Solar/Wind Harmer
3.438
276174W4-005 GEN2
Solar/Wind Harmer
3.438
24387305FR-4G C
Solar/Wind Harmer
5.77
966841AG1-555 GEN
Solar/Wind Harmer
2.852
24725505WLD G2 C
Solar/Wind Harmer
4.513
24699105WLD G1 C
Solar/Wind Harmer
4.461
270383AD1-128 GEN
Solar/Wind Harmer
6.909
970291AG2-192 GEN
Solar/Wind Harmer
1.461
970291AG2-192 GEN
Solar/Wind Harmer
0.47
253370AE2-315 SEC1
Adder
2.225
274764LEE CO EC;5U
Adder
10.23
274765LEE CO EC;6U
Adder
10.23
274762LEE CO EC;3U
Adder
10.206
274763LEE CO EC;4U
Adder
10.109
247621Y3-024
Adder
0.264
972235AH1-702 GEN1
Adder
2.754
972236AH1-702 GEN2
Adder
2.395
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274696ROCKY RD ;4P
Adder
12.353
274695ROCKY RD ;2P
Adder
12.068
274693ROCKY RD ;1P
Adder
11.949
274697ROCKY RD ;3P
Adder
3.278
274674JOLIET 9 ;6U
Adder
16.589
23585401KL_K28_T16
Solar/Wind Helper
1.275
235054AD2-180 GEN
Solar/Wind Helper
1.707
238117U2-030
Solar/Wind Helper
0.29
235531U2-073 GEN
Solar/Wind Helper
2.776
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
316097T157 G90
Solar/Wind Helper
1.102
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
203961AE2-224 GEN
Solar/Wind Helper
2.204
24289405MTG1
50/50
11.78
243186AF1-051 GEN
50/50
12.754
24318705GVG2
50/50
11.822
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24686505CER G6
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
26.012
270331AC1-082 GEN3
Solar/Wind Harmer
0.864
960001AF2-291 GEN
Solar/Wind Harmer
5.313
24728305BUCHG2
Adder
7.739
971687AH1-348 GEN
Solar/Wind Harmer
1.658
24735205WLF2G2
Adder
8.97
270336AE1-100 GEN
Solar/Wind Harmer
2.369
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
339211AE2-254 GEN
Solar/Wind Harmer
1.998
3429241JKCT 3G
Adder
15.659
270173AC1-122 GEN
Solar/Wind Harmer
2.206
3429421JKCT 10G
Adder
10.948
945681AF1-233 GEN
Solar/Wind Harmer
24.773
943111AE2-339 GEN
Solar/Wind Harmer
1.158
339221AD2-048_GEN
Solar/Wind Harmer
2.01
943811AF1-049 GEN
Solar/Wind Harmer
4.941
339241AF1-083 GEN
Solar/Wind Harmer
2.163
964901AG1-354 GEN
Solar/Wind Harmer
19.398
970653AG2-424 GEN
Solar/Wind Harmer
6.236
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252516AE2-318_GEN
Solar/Wind Harmer
12.45
252510AF1-249 C
Solar/Wind Harmer
0.517
25194608D.CRK4
Adder
2.03
253316AC1-085 GEN3
Solar/Wind Harmer
10.112
946171AF1-282 GEN
Solar/Wind Harmer
12.079
24728605AND G2
Adder
4.51
253398AE2-221_GEN2
Solar/Wind Harmer
5.329
962761AG1-125 GEN
Solar/Wind Harmer
38.013
970149AG2-104 GEN
Solar/Wind Harmer
23.473
970155AG2-107 GEN
Solar/Wind Harmer
16.575
270574AD1-017 GEN2
Solar/Wind Harmer
5.994
316217AC1-145 GEN
Solar/Wind Harmer
2.791
316197AC1-042 GEN
Solar/Wind Harmer
2.116
3147312GRETNA
Solar/Wind Harmer
-0.003
270222AC2-111 GEN
Solar/Wind Harmer
5.217
944031AF1-071 GEN
Solar/Wind Harmer
1.174
963741AG1-226 GEN
Solar/Wind Harmer
51.846
965911AG1-460 GEN
Solar/Wind Harmer
1.606
276621W2-048 GEN
Solar/Wind Harmer
7.12
942081AE2-220 GEN
Solar/Wind Harmer
7.281
270209AC1-174_GEN
Solar/Wind Harmer
4.633
270437AC2-090 C
Solar/Wind Harmer
6.354
270239V3-007_GEN1
Solar/Wind Harmer
1.959
276686W4-005 GEN3
Solar/Wind Harmer
3.438
24385905FR-11G C
Solar/Wind Harmer
9.442
24386605FR-22G C
Solar/Wind Harmer
4.886
276903AD2-071 C
Solar/Wind Harmer
11.325
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274761LEE CO EC;2U
Adder
10.206
274766LEE CO EC;7U
Adder
10.085
274822ROCKFORD ;11
Adder
21.436
25326309TAIT D
Adder
1.195
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
274745AC1-111 GEN9
Adder
6.042
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
274676JOLIET 29;8U
Adder
11.649
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
964201AG1-281 GEN
Solar/Wind Helper
0.442
270594AE1-207 GEN
Solar/Wind Harmer
12.561
270032AE2-172
Solar/Wind Harmer
4.302
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
8.236
270053AF1-130 C
Solar/Wind Harmer
32.909
270399AC1-101 GEN
Solar/Wind Harmer
7.81
270400AC1-102 GEN
Solar/Wind Harmer
7.81
971313AH1-133 GEN
Solar/Wind Harmer
10.201
941621AE2-160 GEN
Adder
5.641
966391AG1-508 GEN
Solar/Wind Harmer
5.744
970281AG2-184 GEN
Solar/Wind Harmer
34.819
971331AH1-145 GEN
Solar/Wind Harmer
15.307
971329AH1-144 GEN
Solar/Wind Harmer
9.777
24734705WLF1G3
Adder
9.154
24734805WLF1G4
Adder
9.154
24734905WLF1G5
Adder
9.154
962211AG1-066 GEN
Solar/Wind Harmer
3.81
24735105WLF2G1
Adder
8.97
971061AG2-657 GEN
Solar/Wind Harmer
14.005
971985AH1-537 GEN
Solar/Wind Harmer
26.103
971981AH1-535 GEN
Solar/Wind Harmer
14.155
270069AE2-166 C O1
Solar/Wind Harmer
12.483
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
13.172
972165AH1-665 GEN
Solar/Wind Harmer
10.538
339216AC1-074 GEN
Solar/Wind Harmer
2.182
270291AC1-194 GEN
Solar/Wind Harmer
6.437
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
270444AC2-157 GEN1
Solar/Wind Harmer
6.941
270445AC2-157 GEN2
Solar/Wind Harmer
6.941
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
25196508WSDLE4
Adder
10.442
253433AC1-085 GEN1
Solar/Wind Harmer
6.419
253432AC1-085 GEN2
Solar/Wind Harmer
0.323
253406AD2-031_GEN
Solar/Wind Harmer
1.524
270340AC2-060 GEN
Solar/Wind Harmer
3.588
270263AC1-001 GEN
Solar/Wind Harmer
1.236
270197AD1-017 GEN1
Solar/Wind Harmer
1.798
270356AE2-297 GEN
Solar/Wind Harmer
5.395
944221AF1-090 GEN
Solar/Wind Harmer
12.7
963841AG1-237 GEN
Solar/Wind Harmer
12.506
276763AC1-053 GEN1
Solar/Wind Harmer
4.5
276764AC1-053 GEN2
Solar/Wind Harmer
4.5
276668AB2-070 GEN1
Solar/Wind Harmer
2.517
276848AB2-070 GEN3
Solar/Wind Harmer
2.517
276849AB2-070 GEN2
Solar/Wind Harmer
2.517
24386405FR-21G C
Solar/Wind Harmer
4.886
24387005FR-3G C
Solar/Wind Harmer
4.493
970289AG2-191 GEN
Solar/Wind Harmer
2.135
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
972267AH1-718 GEN
Adder
4.579
274823ROCKFORD ;21
Adder
21.28
274744AC1-111 GEN8
Adder
6.042
274746AC1-111 G10
Adder
6.042
274728ELWOOD EC;5P
Adder
17.715
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
274735ELWOOD EC;4P
Adder
17.715
274675JOLIET 29;7U
Adder
33.032
23750501ELLIOTTS
Solar/Wind Helper
0.639
23750701CROSSCHOOL
Solar/Wind Helper
1.205
238118U2-030_1
Solar/Wind Helper
0.29
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089226LOOKOUT
Solar/Wind Helper
0.556
20088926STNY CRK
Solar/Wind Helper
0.752
203940AF1-140 C
Solar/Wind Helper
0.362
24289405MTG1
50/50
11.78
24318705GVG2
50/50
11.822
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
24686405CER G5
Adder
16.028
270330AC1-082 GEN2
Solar/Wind Harmer
0.862
270329AC1-082 GEN1
Solar/Wind Harmer
0.862
960911AF2-382 GEN
Solar/Wind Harmer
12.889
943031AE2-326 GEN
Solar/Wind Harmer
6.089
971461AH1-227 GEN
Solar/Wind Harmer
8.512
972103AH1-617 GEN
Solar/Wind Harmer
33.161
971191AH1-055 GEN
Solar/Wind Harmer
30.574
270346AE1-212 GEN
Solar/Wind Harmer
14.67
958121AF2-106 GEN
Solar/Wind Harmer
7.386
957541AF2-048 GEN
Solar/Wind Harmer
2.364
970879AG2-548 GEN
Solar/Wind Harmer
10.717
972273AH1-721 GEN
Adder
111.17
270030AE2-140 GEN
Solar/Wind Harmer
26.764
970093AG2-073 GEN
Solar/Wind Harmer
7.05
270186AC1-089 GEN
Solar/Wind Harmer
8.102
270367AC2-061_GEN
Solar/Wind Harmer
4.197
3429391JKCT 9G
Adder
10.948
972167AH1-666 GEN
Solar/Wind Harmer
10.503
962751AG1-124 GEN
Solar/Wind Harmer
11.766
339206AE1-143 GEN
Solar/Wind Harmer
2.789
339243AC2-075 GEN1
Solar/Wind Harmer
0.591
970455AG2-298 GEN
Solar/Wind Harmer
4.537
970653AG2-424 GEN
Solar/Wind Harmer
0.902
339255AE2-071 GEN
Solar/Wind Harmer
1.514
339250AF1-203 GEN
Solar/Wind Harmer
0.779
958171AF2-111 GEN
Solar/Wind Harmer
32.027
252507AC2-088 GEN
Solar/Wind Harmer
2.278
25196008MFTGT1
Adder
1.685
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
252524AE2-267 GEN
Solar/Wind Harmer
1.938
25196608WSDLE5
Adder
10.55
270018AE2-047 C O1
Solar/Wind Harmer
1.501
253317AC1-085 GEN4
Solar/Wind Harmer
10.112
946181AF1-283 GEN
Solar/Wind Harmer
15.702
970193AG2-126 GEN
Solar/Wind Harmer
17.687
24728705AND G3
Adder
9.433
24728505AND G1
Adder
4.51
253394AE2-221_GEN
Solar/Wind Harmer
5.329
962771AG1-126 GEN
Solar/Wind Harmer
38.013
970153AG2-106 GEN
Solar/Wind Harmer
16.575
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.453
942481AE2-261 GEN
Solar/Wind Harmer
34.409
957381AF2-032 GEN
Solar/Wind Harmer
2.3
24379505HDWTR1G C
Solar/Wind Harmer
9.002
270240V3-007_GEN2
Solar/Wind Harmer
7.043
276785W4-005 GEN1
Solar/Wind Harmer
3.438
971993AH1-541 GEN
Solar/Wind Harmer
10.504
24386205FR-12G C
Solar/Wind Harmer
4.868
247642Z2-115 C
Solar/Wind Harmer
0.072
965461AG1-414 GEN
Solar/Wind Harmer
2.547
970289AG2-191 GEN
Solar/Wind Harmer
0.862
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274760LEE CO EC;1U
Adder
10.206
274767LEE CO EC;8U
Adder
10.085
274682WAUKEGAN ;7U
Adder
19.478
274729ELWOOD EC;1P
Adder
17.715
274730ELWOOD EC;6P
Adder
17.715
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
964991AG1-363 GEN
Solar/Wind Helper
3.731
238127S14_GEN_2
Solar/Wind Helper
0.692
23562501BACKB
Solar/Wind Helper
0.87
202652Y1-033 WT C
Solar/Wind Helper
0.538
238108AE1-109 GEN1
Solar/Wind Helper
0.089
238110AE1-109 GEN3
Solar/Wind Helper
0.089
20092526R32
Solar/Wind Helper
1.061
235058AG1-386 C
Solar/Wind Helper
0.381
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
TVALTFEXP_TVA->PJM
CLTF
12.601
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
WECLTFEXP_WEC->PJM
CLTF
4.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657
CPLELTFEXP_CPLE->PJM
CLTF
7.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 111.17 MW.

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.46 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5935.05
MW Contribution:
84.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.32
243186AF1-051 GEN
50/50
12.373
24318705GVG2
50/50
11.469
24721805FLATG3
50/50
2.718
24723205RIVRG3
Adder
34.305
972203AH1-686 GEN
Adder
4.176
24686505CER G6
Adder
14.723
944971AF1-162 GEN
Solar/Wind Harmer
11.548
971403AH1-188 GEN
Solar/Wind Harmer
22.954
270331AC1-082 GEN3
Solar/Wind Harmer
0.78
960001AF2-291 GEN
Solar/Wind Harmer
4.782
962761AG1-125 GEN
Solar/Wind Harmer
51.105
970149AG2-104 GEN
Solar/Wind Harmer
31.557
970155AG2-107 GEN
Solar/Wind Harmer
22.284
24728305BUCHG2
Adder
6.531
971687AH1-348 GEN
Solar/Wind Harmer
1.432
24735205WLF2G2
Adder
7.594
970091AG2-072 GEN
Adder
98.735
339211AE2-254 GEN
Solar/Wind Harmer
1.806
3429241JKCT 3G
Adder
14.075
970653AG2-424 GEN
Solar/Wind Harmer
5.716
24721605FLATG1
50/50
2.718
957241AF2-018 GEN
Solar/Wind Harmer
7.332
270053AF1-130 C
Solar/Wind Harmer
29.298
270399AC1-101 GEN
Solar/Wind Harmer
6.93
270400AC1-102 GEN
Solar/Wind Harmer
6.93
941621AE2-160 GEN
Adder
4.867
970281AG2-184 GEN
Solar/Wind Harmer
30.484
971313AH1-133 GEN
Solar/Wind Harmer
8.48
962211AG1-066 GEN
Solar/Wind Harmer
3.344
24734705WLF1G3
Adder
7.73
24734805WLF1G4
Adder
7.73
24734905WLF1G5
Adder
7.73
971061AG2-657 GEN
Solar/Wind Harmer
11.954
971985AH1-537 GEN
Solar/Wind Harmer
23.681
24735105WLF2G1
Adder
7.594
966391AG1-508 GEN
Solar/Wind Harmer
4.439
971331AH1-145 GEN
Solar/Wind Harmer
11.397
971329AH1-144 GEN
Solar/Wind Harmer
7.28
971981AH1-535 GEN
Solar/Wind Harmer
12.094
270444AC2-157 GEN1
Solar/Wind Harmer
6.747
270445AC2-157 GEN2
Solar/Wind Harmer
6.747
3429211JKCT 2G
Adder
13.893
972163AH1-664 GEN
Solar/Wind Harmer
11.763
972165AH1-665 GEN
Solar/Wind Harmer
9.41
339216AC1-074 GEN
Solar/Wind Harmer
1.968
963841AG1-237 GEN
Solar/Wind Harmer
12.582
25196108MFTGT2
Adder
1.764
25196108MFTGT2
Adder
1.638
24386405FR-21G C
Solar/Wind Harmer
4.939
24387005FR-3G C
Solar/Wind Harmer
4.542
944221AF1-090 GEN
Solar/Wind Harmer
12.541
946581AF1-322 GEN
Solar/Wind Harmer
11.687
24691005MDL-2G C
Solar/Wind Harmer
4.223
276763AC1-053 GEN1
Solar/Wind Harmer
4.503
24289405MTG1
50/50
11.32
24318705GVG2
50/50
11.469
24722005FLATG5
50/50
2.718
24721905FLATG4
50/50
49.64
24686405CER G5
Adder
14.607
270330AC1-082 GEN2
Solar/Wind Harmer
0.779
270329AC1-082 GEN1
Solar/Wind Harmer
0.779
962771AG1-126 GEN
Solar/Wind Harmer
51.105
970153AG2-106 GEN
Solar/Wind Harmer
22.284
971191AH1-055 GEN
Solar/Wind Harmer
27.435
960911AF2-382 GEN
Solar/Wind Harmer
10.97
972103AH1-617 GEN
Solar/Wind Harmer
29.032
971461AH1-227 GEN
Solar/Wind Harmer
7.34
270346AE1-212 GEN
Solar/Wind Harmer
11.918
957541AF2-048 GEN
Solar/Wind Harmer
2.06
943031AE2-326 GEN
Solar/Wind Harmer
4.698
972273AH1-721 GEN
Adder
99.65
970093AG2-073 GEN
Solar/Wind Harmer
6.342
970455AG2-298 GEN
Solar/Wind Harmer
4.162
339206AE1-143 GEN
Solar/Wind Harmer
2.532
970653AG2-424 GEN
Solar/Wind Harmer
0.827
270186AC1-089 GEN
Solar/Wind Harmer
7.225
3429391JKCT 9G
Adder
9.84
270367AC2-061_GEN
Solar/Wind Harmer
3.742
958121AF2-106 GEN
Solar/Wind Harmer
5.343
339243AC2-075 GEN1
Solar/Wind Harmer
0.533
972167AH1-666 GEN
Solar/Wind Harmer
9.374
339255AE2-071 GEN
Solar/Wind Harmer
1.375
339250AF1-203 GEN
Solar/Wind Harmer
0.708
970193AG2-126 GEN
Solar/Wind Harmer
17.459
25196008MFTGT1
Adder
1.55
24386205FR-12G C
Solar/Wind Harmer
4.921
24728705AND G3
Adder
9.201
24728505AND G1
Adder
4.399
252507AC2-088 GEN
Solar/Wind Harmer
2.051
942481AE2-261 GEN
Solar/Wind Harmer
34.173
957381AF2-032 GEN
Solar/Wind Harmer
2.285
24690905MDL-1G C
Solar/Wind Harmer
9.169
970781AG2-491 GEN
Solar/Wind Harmer
11.422
958171AF2-111 GEN
Solar/Wind Harmer
28.524
276785W4-005 GEN1
Solar/Wind Harmer
3.443
971993AH1-541 GEN
Solar/Wind Harmer
10.521
247642Z2-115 C
Solar/Wind Harmer
0.073
965091AG1-374 GEN
Solar/Wind Harmer
33.954
970879AG2-548 GEN
Solar/Wind Harmer
9.054
959611AF2-252 GEN
Solar/Wind Harmer
2.632
965461AG1-414 GEN
Solar/Wind Harmer
2.564
970289AG2-191 GEN
Solar/Wind Harmer
0.868
25194608D.CRK4
Adder
1.843
274760LEE CO EC;1U
Adder
10.407
274767LEE CO EC;8U
Adder
10.284
25196608WSDLE5
Adder
9.576
274682WAUKEGAN ;7U
Adder
20.049
274772LINCOLN ;3U
Adder
9.41
972259AH1-714 GEN
Adder
21.265
274729ELWOOD EC;1P
Adder
18.315
274730ELWOOD EC;6P
Adder
18.315
274734ELWOOD EC;8P
Adder
18.315
274736ELWOOD EC;9P
Adder
18.315
237048AF1-022 C
Solar/Wind Helper
0.194
237046AF1-021 C
Solar/Wind Helper
0.336
235058AG1-386 C
Solar/Wind Helper
0.44
23562501BACKB
Solar/Wind Helper
0.897
964991AG1-363 GEN
Solar/Wind Helper
3.654
202652Y1-033 WT C
Solar/Wind Helper
0.551
238127S14_GEN_2
Solar/Wind Helper
0.674
20092526R32
Solar/Wind Helper
1.103
20303426NA_O38_P22
Solar/Wind Helper
0.938
203993AD2-133_GEN1
Solar/Wind Helper
0.966
238108AE1-109 GEN1
Solar/Wind Helper
0.084
238110AE1-109 GEN3
Solar/Wind Helper
0.084
203854AF2-039 C
Solar/Wind Helper
0.298
243186AF1-051 GEN
50/50
12.373
24721705FLATG2
50/50
40.36
24723005RIVRG1
Adder
34.305
24723105RIVRG2
Adder
34.305
970913AG2-568 GEN
Solar/Wind Harmer
10.293
24728205BUCHG1
Adder
6.531
971225AH1-072 GEN
Solar/Wind Harmer
2.862
971227AH1-073 GEN
Solar/Wind Harmer
2.862
927014AC1-188 GEN
Solar/Wind Harmer
2.06
270214AC2-123 GEN
Solar/Wind Harmer
2.985
971277AH1-098 GEN
Solar/Wind Harmer
5.094
942891AE2-308 GEN
Solar/Wind Harmer
11.926
964571AG1-320 GEN
Solar/Wind Harmer
9.728
339231AF1-038_GEN
Solar/Wind Harmer
2.148
972043AH1-570 GEN
Solar/Wind Harmer
2.957
972045AH1-571 GEN
Solar/Wind Harmer
2.366
971125AH1-004 GEN
Solar/Wind Harmer
4.718
970107AG2-081 GEN
Solar/Wind Harmer
3.539
270583AD2-179 GEN
Solar/Wind Harmer
11.79
966021AG1-471 GEN
Solar/Wind Harmer
6.353
339236AF1-050_GEN
Solar/Wind Harmer
2.134
971485AH1-239 GEN
Solar/Wind Harmer
9.407
964781AG1-341 GEN
Solar/Wind Harmer
12.396
945391AF1-204 GEN
Solar/Wind Harmer
16.22
962581AG1-107 GEN
Solar/Wind Harmer
5.847
961491AF2-440 GEN
Solar/Wind Harmer
2.43
970241AG2-163 GEN
Solar/Wind Harmer
28.851
24387305FR-4G C
Solar/Wind Harmer
5.833
966841AG1-555 GEN
Solar/Wind Harmer
2.883
252509AD1-136 GEN
Solar/Wind Harmer
0.293
276916AD2-100_GEN
Solar/Wind Harmer
24.022
276911AD2-131_GEN
Solar/Wind Harmer
4.855
270180AB1-006 GEN1
Solar/Wind Harmer
8.215
24697605MDL-3G C
Solar/Wind Harmer
4.21
24755605MDL-5G
Solar/Wind Harmer
2.754
24697905MDL-4G C
Solar/Wind Harmer
2.621
270181AB1-006 GEN2
Solar/Wind Harmer
0.817
276615X2-022 GEN
Solar/Wind Harmer
2.233
276838X2-022 GEN2
Solar/Wind Harmer
0.265
945421AF1-207 GEN
Solar/Wind Harmer
16.001
957841AF2-078 GEN
Solar/Wind Harmer
6.888
274880W4-005 GEN4
Solar/Wind Harmer
3.443
276174W4-005 GEN2
Solar/Wind Harmer
3.443
971073AG2-665 GEN
Solar/Wind Harmer
9.054
960611AF2-352 GEN
Solar/Wind Harmer
2.632
970879AG2-548 GEN
Solar/Wind Harmer
1.316
970291AG2-192 GEN
Solar/Wind Harmer
1.47
970291AG2-192 GEN
Solar/Wind Harmer
0.473
24725505WLD G2 C
Solar/Wind Harmer
4.494
24699105WLD G1 C
Solar/Wind Harmer
4.441
942111AE2-223 GEN
Solar/Wind Harmer
9.262
25194408D.CRK1
Adder
8.477
25194508D.CRK3
Adder
1.585
274764LEE CO EC;5U
Adder
10.431
274765LEE CO EC;6U
Adder
10.431
274762LEE CO EC;3U
Adder
10.407
274763LEE CO EC;4U
Adder
10.309
972235AH1-702 GEN1
Adder
2.817
972236AH1-702 GEN2
Adder
2.45
274696ROCKY RD ;4P
Adder
12.719
274695ROCKY RD ;2P
Adder
12.425
274693ROCKY RD ;1P
Adder
12.303
274697ROCKY RD ;3P
Adder
3.375
274683WAUKEGAN ;8U
Adder
23.51
274683WAUKEGAN ;8U
Adder
19.818
274770LINCOLN ;1U
Adder
9.41
274771LINCOLN ;2U
Adder
9.41
274674JOLIET 9 ;6U
Adder
16.682
237043AE2-125 C
Solar/Wind Helper
0.176
23585401KL_K28_T16
Solar/Wind Helper
1.282
23751201ROTHROCK
Solar/Wind Helper
0.737
235054AD2-180 GEN
Solar/Wind Helper
1.698
238117U2-030
Solar/Wind Helper
0.286
962101AG1-054 GEN
Solar/Wind Helper
0.612
254304AE2-114 C
Solar/Wind Helper
0.205
254305AE2-115 C
Solar/Wind Helper
0.205
241967AE2-285_GEN
Solar/Wind Helper
0.597
241801AE1-079 GEN
Solar/Wind Helper
0.233
235531U2-073 GEN
Solar/Wind Helper
2.712
20083426SW_E13_K22
Solar/Wind Helper
0.053
946071AF1-272 GEN
Solar/Wind Helper
2.571
20088826HIGHLAND
Solar/Wind Helper
0.851
203961AE2-224 GEN
Solar/Wind Helper
2.277
203818AF1-086 GEN
Solar/Wind Helper
1.591
203853AF1-134 C O1
Solar/Wind Helper
0.449
946381AF1-302 GEN
Solar/Wind Helper
0.208
203946AE2-131 C
Solar/Wind Helper
0.445
203954AE2-126 C
Solar/Wind Helper
0.44
203804AE2-113_GEN
Solar/Wind Helper
1.631
940863AE2-074 GEN
Solar/Wind Helper
0.426
276764AC1-053 GEN2
Solar/Wind Harmer
4.503
276668AB2-070 GEN1
Solar/Wind Harmer
2.521
276848AB2-070 GEN3
Solar/Wind Harmer
2.521
276849AB2-070 GEN2
Solar/Wind Harmer
2.521
270356AE2-297 GEN
Solar/Wind Harmer
5.225
274853TWINGROVE;U1
Solar/Wind Harmer
8.154
274854TWINGROVE;U2
Solar/Wind Harmer
7.983
970289AG2-191 GEN
Solar/Wind Harmer
2.148
276726Z2-087_GEN
Solar/Wind Harmer
8.934
959341AF2-225 GEN
Solar/Wind Harmer
16.948
972267AH1-718 GEN
Adder
4.661
274823ROCKFORD ;21
Adder
21.773
25196408WSDLE3
Adder
9.858
25196308WSDLE2
Adder
9.772
25196208WSDLE1
Adder
9.747
25196708WSDLE6
Adder
9.723
25196508WSDLE4
Adder
9.478
274744AC1-111 GEN8
Adder
6.235
274746AC1-111 G10
Adder
6.235
274775LINCOLN ;6U
Adder
9.41
274776LINCOLN ;7U
Adder
9.41
274777LINCOLN ;8U
Adder
9.41
274728ELWOOD EC;5P
Adder
18.315
274731ELWOOD EC;2P
Adder
18.315
274733ELWOOD EC;3P
Adder
18.315
274735ELWOOD EC;4P
Adder
18.315
23750501ELLIOTTS
Solar/Wind Helper
0.664
23652301WDPWR_K20
Solar/Wind Helper
0.142
23750701CROSSCHOOL
Solar/Wind Helper
1.189
203955AF1-039 C O1
Solar/Wind Helper
0.363
238118U2-030_1
Solar/Wind Helper
0.286
241997AF1-093 GEN
Solar/Wind Helper
0.24
241985AE1-237 GEN
Solar/Wind Helper
0.233
241982AE2-343 S C
Solar/Wind Helper
0.209
20089126CSLMN_L13
Solar/Wind Helper
0.575
20089226LOOKOUT
Solar/Wind Helper
0.573
20088926STNY CRK
Solar/Wind Helper
0.78
203940AF1-140 C
Solar/Wind Helper
0.376
20094526CT_V3-030
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.144
203846AF2-130 C
Solar/Wind Helper
0.423
959141AF2-205 GEN
Solar/Wind Harmer
1.763
339241AF1-083 GEN
Solar/Wind Harmer
1.965
3429421JKCT 10G
Adder
9.84
339221AD2-048_GEN
Solar/Wind Harmer
1.812
943111AE2-339 GEN
Solar/Wind Harmer
1.043
964901AG1-354 GEN
Solar/Wind Harmer
17.632
945681AF1-233 GEN
Solar/Wind Harmer
22.112
963741AG1-226 GEN
Solar/Wind Harmer
51.931
25196008MFTGT1
Adder
1.6
24385905FR-11G C
Solar/Wind Harmer
9.545
24386605FR-22G C
Solar/Wind Harmer
4.939
24728605AND G2
Adder
4.399
965911AG1-460 GEN
Solar/Wind Harmer
1.595
24791305MDL-5G
Solar/Wind Harmer
2.754
276621W2-048 GEN
Solar/Wind Harmer
7.111
276686W4-005 GEN3
Solar/Wind Harmer
3.443
25196808ZIMRHP
Adder
86.01
971073AG2-665 GEN
Solar/Wind Harmer
1.316
276903AD2-071 C
Solar/Wind Harmer
11.309
940581AE2-045 GEN
Solar/Wind Harmer
11.524
971605AH1-302 GEN
Solar/Wind Harmer
9.854
276655WTG1_EQ
Solar/Wind Harmer
9.862
276656WTG2_EQ
Solar/Wind Harmer
1.306
939741AE1-205 GEN
Solar/Wind Harmer
22.597
270594AE1-207 GEN
Solar/Wind Harmer
15.305
270032AE2-172
Solar/Wind Harmer
5.241
25194608D.CRK4
Adder
1.843
274761LEE CO EC;2U
Adder
10.407
274766LEE CO EC;7U
Adder
10.284
274822ROCKFORD ;11
Adder
21.932
274828WAUKEGAN ;BP
Adder
12.324
274745AC1-111 GEN9
Adder
6.235
274682WAUKEGAN ;7U
Adder
20.049
274773LINCOLN ;4U
Adder
9.41
274774LINCOLN ;5U
Adder
9.41
274732ELWOOD EC;7P
Adder
18.315
274674JOLIET 9 ;6U
Adder
17.154
238185AF2-356 C
Solar/Wind Helper
2.191
254303AC2-168 GEN
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.24
20089026BF_G21_K23
Solar/Wind Helper
0.455
238120AE2-309 GEN
Solar/Wind Helper
0.424
238126S14_GEN_1
Solar/Wind Helper
0.674
23751101LEADS_P59
Solar/Wind Helper
1.865
20084626FORWARD
Solar/Wind Helper
0.338
964201AG1-281 GEN
Solar/Wind Helper
0.457
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.966
238109AE1-109 GEN2
Solar/Wind Helper
0.084
203952AE2-129 C
Solar/Wind Helper
0.445
203855AF2-088 C
Solar/Wind Helper
0.143
LAGNLTFEXP_LAGN->PJM
CLTF
22.209
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.481
TVALTFEXP_TVA->PJM
CLTF
11.344
NYPJM->LTFIMP_NY
CLTF
5.206
LGEELTFEXP_LGEE->PJM
CLTF
8.318
WECLTFEXP_WEC->PJM
CLTF
4.274
AG2-052LTFEXP_AG2-052->PJM
LTF
0.26
AH1-155LTFEXP_AH1-155->PJM
LTF
0.389
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.12
MECLTFEXP_MEC->PJM
CLTF
18.91
SIGELTFEXP_SIGE->PJM
CLTF
0.622
CPLELTFEXP_CPLE->PJM
CLTF
6.634
CBM West 2LTFEXP_CBM-W2->PJM
CBM
151.558
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 99.65 MW.

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.76 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5896.19
MW Contribution:
94.18
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
970913AG2-568 GEN
Solar/Wind Harmer
9.827
24728205BUCHG1
Adder
7.739
971225AH1-072 GEN
Solar/Wind Harmer
2.315
971227AH1-073 GEN
Solar/Wind Harmer
2.315
971277AH1-098 GEN
Solar/Wind Harmer
4.618
270583AD2-179 GEN
Solar/Wind Harmer
11.364
971073AG2-665 GEN
Solar/Wind Harmer
6.854
970879AG2-548 GEN
Solar/Wind Harmer
1.558
942891AE2-308 GEN
Solar/Wind Harmer
9.244
972043AH1-570 GEN
Solar/Wind Harmer
2.384
972045AH1-571 GEN
Solar/Wind Harmer
1.91
971125AH1-004 GEN
Solar/Wind Harmer
3.655
970107AG2-081 GEN
Solar/Wind Harmer
2.741
966021AG1-471 GEN
Solar/Wind Harmer
4.933
971485AH1-239 GEN
Solar/Wind Harmer
7.296
962581AG1-107 GEN
Solar/Wind Harmer
0.002
964781AG1-341 GEN
Solar/Wind Harmer
9.518
964571AG1-320 GEN
Solar/Wind Harmer
8.194
252509AD1-136 GEN
Solar/Wind Harmer
0.044
25183208HLCRTG
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
6.363
25194408D.CRK1
Adder
9.34
25194508D.CRK3
Adder
1.746
945391AF1-204 GEN
Solar/Wind Harmer
8.741
942671AE2-283 GEN
Solar/Wind Harmer
3.812
24728805RICHG1
Adder
4.399
24728905RICHG2
Adder
4.399
276916AD2-100_GEN
Solar/Wind Harmer
16.897
276911AD2-131_GEN
Solar/Wind Harmer
1.113
970241AG2-163 GEN
Solar/Wind Harmer
4.689
276615X2-022 GEN
Solar/Wind Harmer
0.083
276838X2-022 GEN2
Solar/Wind Harmer
0.448
926881AC1-175 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.897
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
1.019
970291AG2-192 GEN
Solar/Wind Harmer
0.47
971613AH1-306 GEN
Solar/Wind Harmer
3.76
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.602
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
2.525
253370AE2-315 SEC1
Adder
2.225
970883AG2-550 GEN
Solar/Wind Harmer
7.744
970885AG2-551 GEN
Solar/Wind Harmer
2.581
276645AC1-214 GEN1
Solar/Wind Harmer
0.302
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.239
270031AE2-169
Solar/Wind Harmer
4.216
270599AE1-208 GEN
Solar/Wind Harmer
7.027
964611AG1-324 GEN
Solar/Wind Harmer
0.575
274764LEE CO EC;5U
Adder
10.23
274765LEE CO EC;6U
Adder
10.23
274762LEE CO EC;3U
Adder
10.206
274763LEE CO EC;4U
Adder
10.109
938861AE1-114 GEN
Solar/Wind Harmer
4.333
247621Y3-024
Adder
0.264
270201AC2-176 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.754
972236AH1-702 GEN2
Adder
2.395
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
15.232
971343AH1-151 GEN
Solar/Wind Harmer
15.232
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.378
962691AG1-118 GEN
Solar/Wind Harmer
22.733
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274696ROCKY RD ;4P
Adder
12.353
274695ROCKY RD ;2P
Adder
12.068
274693ROCKY RD ;1P
Adder
11.949
274697ROCKY RD ;3P
Adder
3.278
958481AF2-142 GEN
Solar/Wind Harmer
11.337
276897AD1-100 C
Solar/Wind Harmer
18.8
276893AG1-478 C
Solar/Wind Harmer
0.501
274674JOLIET 9 ;6U
Adder
16.589
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.437
276776AD2-060 GEN
Solar/Wind Harmer
0.799
958011AF2-095 GEN
Solar/Wind Harmer
10.787
23585401KL_K28_T16
Solar/Wind Helper
1.275
235054AD2-180 GEN
Solar/Wind Helper
1.707
238117U2-030
Solar/Wind Helper
0.29
235531U2-073 GEN
Solar/Wind Helper
2.776
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
28.948
270399AC1-101 GEN
Solar/Wind Harmer
4.065
270400AC1-102 GEN
Solar/Wind Harmer
4.065
971313AH1-133 GEN
Solar/Wind Harmer
5.869
941621AE2-160 GEN
Adder
5.641
966391AG1-508 GEN
Solar/Wind Harmer
1.796
970281AG2-184 GEN
Solar/Wind Harmer
24.292
971331AH1-145 GEN
Solar/Wind Harmer
15.307
971329AH1-144 GEN
Solar/Wind Harmer
5.625
24734705WLF1G3
Adder
9.154
24734805WLF1G4
Adder
9.154
24734905WLF1G5
Adder
9.154
24735105WLF2G1
Adder
8.97
971061AG2-657 GEN
Solar/Wind Harmer
6.84
971985AH1-537 GEN
Solar/Wind Harmer
3.035
971981AH1-535 GEN
Solar/Wind Harmer
6.584
270069AE2-166 C O1
Solar/Wind Harmer
8.709
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
10.231
972165AH1-665 GEN
Solar/Wind Harmer
8.194
339216AC1-074 GEN
Solar/Wind Harmer
0.242
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
25196508WSDLE4
Adder
10.442
253406AD2-031_GEN
Solar/Wind Harmer
0.618
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.825
270197AD1-017 GEN1
Solar/Wind Harmer
1.008
270356AE2-297 GEN
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.756
963841AG1-237 GEN
Solar/Wind Harmer
3.459
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
24386405FR-21G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.489
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
24289405MTG1
50/50
11.78
243186AF1-051 GEN
50/50
12.754
24318705GVG2
50/50
11.822
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24686505CER G6
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
18.148
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
7.739
971687AH1-348 GEN
Solar/Wind Harmer
1.157
24735205WLF2G2
Adder
8.97
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
3429241JKCT 3G
Adder
15.659
3429421JKCT 10G
Adder
10.948
945681AF1-233 GEN
Solar/Wind Harmer
17.283
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
964901AG1-354 GEN
Solar/Wind Harmer
13.534
970653AG2-424 GEN
Solar/Wind Harmer
4.351
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252516AE2-318_GEN
Solar/Wind Harmer
9.728
252510AF1-249 C
Solar/Wind Harmer
0.065
25194608D.CRK4
Adder
2.03
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.427
24728605AND G2
Adder
4.51
253398AE2-221_GEN2
Solar/Wind Harmer
0
962761AG1-125 GEN
Solar/Wind Harmer
32.057
970149AG2-104 GEN
Solar/Wind Harmer
17.311
970155AG2-107 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.031
970773AG2-487 GEN
Solar/Wind Harmer
1.442
963741AG1-226 GEN
Solar/Wind Harmer
19.023
965911AG1-460 GEN
Solar/Wind Harmer
1.606
276621W2-048 GEN
Solar/Wind Harmer
0.398
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.825
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.823
270594AE1-207 GEN
Solar/Wind Harmer
8.772
270032AE2-172
Solar/Wind Harmer
5.222
270005AE1-210 C O1
Solar/Wind Harmer
1.692
970825AG2-519 GEN
Solar/Wind Harmer
2.77
270273AD2-016 GEN
Solar/Wind Harmer
0.795
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
10.877
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.302
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.607
276708O09 GEN2
Solar/Wind Harmer
0.271
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
10.206
274766LEE CO EC;7U
Adder
10.085
970569AG2-363 GEN
Solar/Wind Harmer
22.948
970819AG2-516 GEN
Solar/Wind Harmer
9.157
274822ROCKFORD ;11
Adder
21.436
957471AF2-041 GEN
Solar/Wind Harmer
22.848
959081AF2-199 GEN
Solar/Wind Harmer
7.616
971067AG2-660 GEN
Solar/Wind Harmer
2.539
945371AF1-202 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.694
971997AH1-543 GEN
Solar/Wind Harmer
3.993
25326309TAIT D
Adder
1.195
276882AE2-255 GEN
Solar/Wind Harmer
0.887
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.865
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
7.216
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.228
274745AC1-111 GEN9
Adder
6.042
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
3.264
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
274676JOLIET 29;8U
Adder
11.649
270055AF2-134 C O1
Solar/Wind Harmer
0
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
964201AG1-281 GEN
Solar/Wind Helper
0.442
971029AG2-637 GEN
Solar/Wind Harmer
11.702
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.158
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
270543AE2-219 C
Solar/Wind Harmer
5.421
946321AF1-296 GEN
Solar/Wind Harmer
4.325
274877BISHOP HL;1U
Solar/Wind Harmer
0.257
247536S-71 GEN
Solar/Wind Harmer
0.307
971611AH1-305 GEN
Solar/Wind Harmer
4.575
970169AG2-114 GEN
Solar/Wind Harmer
7.684
276741O09 GEN1
Solar/Wind Harmer
0.271
972267AH1-718 GEN
Adder
4.579
971609AH1-304 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
2.987
926823AC1-168 GEN
Solar/Wind Harmer
1.302
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
12.311
274856ECOGROVE ;U1
Solar/Wind Harmer
0.178
274823ROCKFORD ;21
Adder
21.28
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.232
945581AF1-223 GEN
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.136
276863AD2-134 GEN
Solar/Wind Harmer
0.136
971675AH1-338 GEN
Solar/Wind Harmer
2.966
971411AH1-196 GEN
Solar/Wind Harmer
11.402
970073AG2-061 GEN
Solar/Wind Harmer
2.528
274744AC1-111 GEN8
Adder
6.042
274746AC1-111 G10
Adder
6.042
970833AG2-524 GEN
Solar/Wind Harmer
8.285
970833AG2-524 GEN
Solar/Wind Harmer
5.523
274728ELWOOD EC;5P
Adder
17.715
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
274735ELWOOD EC;4P
Adder
17.715
274675JOLIET 29;7U
Adder
33.032
960591AF2-350 GEN
Solar/Wind Harmer
7.491
23750501ELLIOTTS
Solar/Wind Helper
0.639
23750701CROSSCHOOL
Solar/Wind Helper
1.205
238118U2-030_1
Solar/Wind Helper
0.29
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089226LOOKOUT
Solar/Wind Helper
0.556
20088926STNY CRK
Solar/Wind Helper
0.752
203940AF1-140 C
Solar/Wind Helper
0.362
24289405MTG1
50/50
11.78
24318705GVG2
50/50
11.822
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
24686405CER G5
Adder
16.028
960911AF2-382 GEN
Solar/Wind Harmer
8.992
943031AE2-326 GEN
Solar/Wind Harmer
6.089
971461AH1-227 GEN
Solar/Wind Harmer
5.939
972103AH1-617 GEN
Solar/Wind Harmer
23.135
971191AH1-055 GEN
Solar/Wind Harmer
29.317
270346AE1-212 GEN
Solar/Wind Harmer
10.045
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
6.854
972273AH1-721 GEN
Adder
111.17
270030AE2-140 GEN
Solar/Wind Harmer
18.672
970093AG2-073 GEN
Solar/Wind Harmer
7.87
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
3429391JKCT 9G
Adder
10.948
972167AH1-666 GEN
Solar/Wind Harmer
7.327
962751AG1-124 GEN
Solar/Wind Harmer
8.058
970455AG2-298 GEN
Solar/Wind Harmer
3.516
970653AG2-424 GEN
Solar/Wind Harmer
0.902
958171AF2-111 GEN
Solar/Wind Harmer
22.344
252507AC2-088 GEN
Solar/Wind Harmer
0.399
25196008MFTGT1
Adder
1.685
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
25196608WSDLE5
Adder
10.55
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
10.955
970193AG2-126 GEN
Solar/Wind Harmer
12.34
24728705AND G3
Adder
9.433
24728505AND G1
Adder
4.51
253394AE2-221_GEN
Solar/Wind Harmer
0
962771AG1-126 GEN
Solar/Wind Harmer
32.057
970153AG2-106 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.122
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.901
942481AE2-261 GEN
Solar/Wind Harmer
24.006
957381AF2-032 GEN
Solar/Wind Harmer
1.818
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.664
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.862
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.832
270004AE1-209 GEN
Solar/Wind Harmer
1.692
965091AG1-374 GEN
Solar/Wind Harmer
23.422
959611AF2-252 GEN
Solar/Wind Harmer
2.602
970825AG2-519 GEN
Solar/Wind Harmer
5.878
946031AF1-268 GEN
Solar/Wind Harmer
7.4
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
965931AG1-462 GEN
Solar/Wind Harmer
19.72
971087AG2-675 GEN
Solar/Wind Harmer
4.124
3147123OTTER R
Solar/Wind Harmer
0.087
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.257
970191AG2-125 GEN
Solar/Wind Harmer
1.979
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
10.206
274767LEE CO EC;8U
Adder
10.085
970571AG2-364 GEN
Solar/Wind Harmer
15.299
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.443
959091AF2-200 GEN
Solar/Wind Harmer
15.232
274855GSG-6 ;RU
Solar/Wind Harmer
0.277
274850MENDOTA H;RU
Solar/Wind Harmer
0.088
946671AF1-331 GEN
Solar/Wind Harmer
0.811
276868AE1-113 GEN
Solar/Wind Harmer
1.52
274879MINONK ;1U
Solar/Wind Harmer
0.317
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
19.478
274862TOP CROP ;2U
Solar/Wind Harmer
1.021
943121AE2-341 GEN
Solar/Wind Harmer
12.644
943591AF1-030 GEN
Solar/Wind Harmer
8.409
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
17.715
274730ELWOOD EC;6P
Adder
17.715
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
970707AG2-453 GEN
Solar/Wind Harmer
24.521
274887GEN-1.85
Solar/Wind Harmer
0.195
276843GEN-1.7
Solar/Wind Harmer
0.242
276806AD2-047 C O1
Solar/Wind Harmer
4.245
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
964991AG1-363 GEN
Solar/Wind Helper
3.731
238127S14_GEN_2
Solar/Wind Helper
0.692
23562501BACKB
Solar/Wind Helper
0.87
202652Y1-033 WT C
Solar/Wind Helper
0.538
238108AE1-109 GEN1
Solar/Wind Helper
0.089
238110AE1-109 GEN3
Solar/Wind Helper
0.089
20092526R32
Solar/Wind Helper
1.061
235058AG1-386 C
Solar/Wind Helper
0.381
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
316097T157 G90
Solar/Wind Helper
1.102
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
203961AE2-224 GEN
Solar/Wind Helper
2.204
970941AG2-585 GEN
Solar/Wind Harmer
2.017
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
TVALTFEXP_TVA->PJM
CLTF
12.601
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
WECLTFEXP_WEC->PJM
CLTF
4.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657
CPLELTFEXP_CPLE->PJM
CLTF
7.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 111.17 MW.

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.86 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5846.6
MW Contribution:
85.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.749
24318705GVG2
50/50
11.694
24722005FLATG5
50/50
2.66
24721905FLATG4
50/50
48.595
270330AC1-082 GEN2
Solar/Wind Harmer
0.934
270329AC1-082 GEN1
Solar/Wind Harmer
0.934
24686405CER G5
Adder
16.065
971191AH1-055 GEN
Solar/Wind Harmer
33.049
960911AF2-382 GEN
Solar/Wind Harmer
11.685
957541AF2-048 GEN
Solar/Wind Harmer
2.439
972103AH1-617 GEN
Solar/Wind Harmer
30.771
971461AH1-227 GEN
Solar/Wind Harmer
7.779
270346AE1-212 GEN
Solar/Wind Harmer
13.204
943031AE2-326 GEN
Solar/Wind Harmer
5.037
24721605FLATG1
50/50
2.66
957241AF2-018 GEN
Solar/Wind Harmer
7.904
270053AF1-130 C
Solar/Wind Harmer
31.582
243186AF1-051 GEN
50/50
12.616
24721705FLATG2
50/50
39.51
24723005RIVRG1
Adder
36.981
24723105RIVRG2
Adder
36.981
970913AG2-568 GEN
Solar/Wind Harmer
11.393
24728205BUCHG1
Adder
6.959
927014AC1-188 GEN
Solar/Wind Harmer
2.439
971225AH1-072 GEN
Solar/Wind Harmer
3.033
971227AH1-073 GEN
Solar/Wind Harmer
3.033
270214AC2-123 GEN
Solar/Wind Harmer
3.2
971277AH1-098 GEN
Solar/Wind Harmer
5.471
971073AG2-665 GEN
Solar/Wind Harmer
10.456
970879AG2-548 GEN
Solar/Wind Harmer
1.52
270583AD2-179 GEN
Solar/Wind Harmer
12.855
962581AG1-107 GEN
Solar/Wind Harmer
6.12
961491AF2-440 GEN
Solar/Wind Harmer
2.543
942891AE2-308 GEN
Solar/Wind Harmer
12.112
972043AH1-570 GEN
Solar/Wind Harmer
3.018
972045AH1-571 GEN
Solar/Wind Harmer
2.414
971125AH1-004 GEN
Solar/Wind Harmer
4.793
970107AG2-081 GEN
Solar/Wind Harmer
3.595
339231AF1-038_GEN
Solar/Wind Harmer
2.155
966021AG1-471 GEN
Solar/Wind Harmer
6.374
971485AH1-239 GEN
Solar/Wind Harmer
9.429
252509AD1-136 GEN
Solar/Wind Harmer
0.301
339236AF1-050_GEN
Solar/Wind Harmer
2.122
964571AG1-320 GEN
Solar/Wind Harmer
9.57
964781AG1-341 GEN
Solar/Wind Harmer
12.309
25183208HLCRTG
Solar/Wind Harmer
6.902
25194408D.CRK1
Adder
8.538
25194508D.CRK3
Adder
1.596
945391AF1-204 GEN
Solar/Wind Harmer
14.618
24728805RICHG1
Adder
3.92
24728905RICHG2
Adder
3.92
253415AE1-040 GEN
Solar/Wind Harmer
1.157
276916AD2-100_GEN
Solar/Wind Harmer
21.377
276911AD2-131_GEN
Solar/Wind Harmer
4.32
970241AG2-163 GEN
Solar/Wind Harmer
25.444
926881AC1-175 GEN
Solar/Wind Harmer
5.627
276615X2-022 GEN
Solar/Wind Harmer
1.968
276838X2-022 GEN2
Solar/Wind Harmer
0.234
24725505WLD G2 C
Solar/Wind Harmer
3.981
24699105WLD G1 C
Solar/Wind Harmer
3.935
274880W4-005 GEN4
Solar/Wind Harmer
3.022
276174W4-005 GEN2
Solar/Wind Harmer
3.022
270383AD1-128 GEN
Solar/Wind Harmer
6.1
24387305FR-4G C
Solar/Wind Harmer
5.075
966841AG1-555 GEN
Solar/Wind Harmer
2.508
970291AG2-192 GEN
Solar/Wind Harmer
1.283
970291AG2-192 GEN
Solar/Wind Harmer
0.413
270180AB1-006 GEN1
Solar/Wind Harmer
7.075
253370AE2-315 SEC1
Adder
1.937
247621Y3-024
Adder
0.23
274764LEE CO EC;5U
Adder
8.891
274765LEE CO EC;6U
Adder
8.891
274762LEE CO EC;3U
Adder
8.871
274763LEE CO EC;4U
Adder
8.787
972235AH1-702 GEN1
Adder
2.391
972236AH1-702 GEN2
Adder
2.08
25322209TAIT E
Adder
9.19
25322209TAIT E
Adder
8.984
274683WAUKEGAN ;8U
Adder
19.789
274683WAUKEGAN ;8U
Adder
16.681
274696ROCKY RD ;4P
Adder
10.699
274695ROCKY RD ;2P
Adder
10.452
274693ROCKY RD ;1P
Adder
10.349
274697ROCKY RD ;3P
Adder
2.839
274674JOLIET 9 ;6U
Adder
14.342
237043AE2-125 C
Solar/Wind Helper
0.175
254304AE2-114 C
Solar/Wind Helper
0.213
254305AE2-115 C
Solar/Wind Helper
0.213
962101AG1-054 GEN
Solar/Wind Helper
0.63
241967AE2-285_GEN
Solar/Wind Helper
0.617
241801AE1-079 GEN
Solar/Wind Helper
0.241
23585401KL_K28_T16
Solar/Wind Helper
1.231
23751201ROTHROCK
Solar/Wind Helper
0.704
235054AD2-180 GEN
Solar/Wind Helper
1.627
946071AF1-272 GEN
Solar/Wind Helper
2.555
238117U2-030
Solar/Wind Helper
0.274
20083426SW_E13_K22
Solar/Wind Helper
0.053
20088826HIGHLAND
Solar/Wind Helper
0.842
235531U2-073 GEN
Solar/Wind Helper
2.597
203818AF1-086 GEN
Solar/Wind Helper
1.582
203961AE2-224 GEN
Solar/Wind Helper
2.25
946381AF1-302 GEN
Solar/Wind Helper
0.208
203853AF1-134 C O1
Solar/Wind Helper
0.446
203946AE2-131 C
Solar/Wind Helper
0.441
203804AE2-113_GEN
Solar/Wind Helper
1.63
24289405MTG1
50/50
11.749
243186AF1-051 GEN
50/50
12.616
24318705GVG2
50/50
11.694
24721805FLATG3
50/50
2.66
960001AF2-291 GEN
Solar/Wind Harmer
6.049
24723205RIVRG3
Adder
36.981
270331AC1-082 GEN3
Solar/Wind Harmer
0.937
24686505CER G6
Adder
16.193
972203AH1-686 GEN
Adder
4.427
944971AF1-162 GEN
Solar/Wind Harmer
12.449
971403AH1-188 GEN
Solar/Wind Harmer
24.722
24728305BUCHG2
Adder
6.959
971687AH1-348 GEN
Solar/Wind Harmer
1.517
24735205WLF2G2
Adder
7.967
971073AG2-665 GEN
Solar/Wind Harmer
1.52
970091AG2-072 GEN
Adder
94.28
945681AF1-233 GEN
Solar/Wind Harmer
22.855
3429241JKCT 3G
Adder
14.309
339221AD2-048_GEN
Solar/Wind Harmer
1.847
339211AE2-254 GEN
Solar/Wind Harmer
1.818
3429421JKCT 10G
Adder
9.999
943111AE2-339 GEN
Solar/Wind Harmer
1.059
339241AF1-083 GEN
Solar/Wind Harmer
1.958
970653AG2-424 GEN
Solar/Wind Harmer
5.656
964901AG1-354 GEN
Solar/Wind Harmer
17.533
25196808ZIMRHP
Adder
87.559
25196008MFTGT1
Adder
1.593
252516AE2-318_GEN
Solar/Wind Harmer
11.412
252510AF1-249 C
Solar/Wind Harmer
0.473
25194608D.CRK4
Adder
1.856
270336AE1-100 GEN
Solar/Wind Harmer
1.934
253316AC1-085 GEN3
Solar/Wind Harmer
9.117
946171AF1-282 GEN
Solar/Wind Harmer
10.89
943811AF1-049 GEN
Solar/Wind Harmer
4.052
24728605AND G2
Adder
4.021
253398AE2-221_GEN2
Solar/Wind Harmer
4.748
270222AC2-111 GEN
Solar/Wind Harmer
4.662
944031AF1-071 GEN
Solar/Wind Harmer
1.049
963741AG1-226 GEN
Solar/Wind Harmer
45.799
965911AG1-460 GEN
Solar/Wind Harmer
1.416
962761AG1-125 GEN
Solar/Wind Harmer
32.808
970149AG2-104 GEN
Solar/Wind Harmer
20.259
970155AG2-107 GEN
Solar/Wind Harmer
14.306
942081AE2-220 GEN
Solar/Wind Harmer
6.447
270209AC1-174_GEN
Solar/Wind Harmer
4.103
270437AC2-090 C
Solar/Wind Harmer
5.627
270239V3-007_GEN1
Solar/Wind Harmer
1.735
276621W2-048 GEN
Solar/Wind Harmer
6.266
276686W4-005 GEN3
Solar/Wind Harmer
3.022
24385905FR-11G C
Solar/Wind Harmer
8.303
24386605FR-22G C
Solar/Wind Harmer
4.297
276903AD2-071 C
Solar/Wind Harmer
9.98
270594AE1-207 GEN
Solar/Wind Harmer
13.398
270032AE2-172
Solar/Wind Harmer
4.588
270005AE1-210 C O1
Solar/Wind Harmer
5.379
270399AC1-101 GEN
Solar/Wind Harmer
7.458
270400AC1-102 GEN
Solar/Wind Harmer
7.458
941621AE2-160 GEN
Adder
5.547
970281AG2-184 GEN
Solar/Wind Harmer
32.31
971313AH1-133 GEN
Solar/Wind Harmer
9.046
971061AG2-657 GEN
Solar/Wind Harmer
13.699
971985AH1-537 GEN
Solar/Wind Harmer
26.806
962211AG1-066 GEN
Solar/Wind Harmer
3.513
24734705WLF1G3
Adder
8.136
24734805WLF1G4
Adder
8.136
24734905WLF1G5
Adder
8.136
24735105WLF2G1
Adder
7.967
966391AG1-508 GEN
Solar/Wind Harmer
4.767
971331AH1-145 GEN
Solar/Wind Harmer
12.423
971329AH1-144 GEN
Solar/Wind Harmer
7.935
971981AH1-535 GEN
Solar/Wind Harmer
12.575
972163AH1-664 GEN
Solar/Wind Harmer
12.156
972165AH1-665 GEN
Solar/Wind Harmer
9.725
3429211JKCT 2G
Adder
14.123
270291AC1-194 GEN
Solar/Wind Harmer
6.12
339216AC1-074 GEN
Solar/Wind Harmer
2.003
25196108MFTGT2
Adder
1.756
25196108MFTGT2
Adder
1.631
25196408WSDLE3
Adder
9.915
25196308WSDLE2
Adder
9.829
25196208WSDLE1
Adder
9.804
25196708WSDLE6
Adder
9.779
25196508WSDLE4
Adder
9.533
270444AC2-157 GEN1
Solar/Wind Harmer
6.262
270445AC2-157 GEN2
Solar/Wind Harmer
6.262
270069AE2-166 C O1
Solar/Wind Harmer
10.085
253433AC1-085 GEN1
Solar/Wind Harmer
5.787
253432AC1-085 GEN2
Solar/Wind Harmer
0.291
253406AD2-031_GEN
Solar/Wind Harmer
1.368
270340AC2-060 GEN
Solar/Wind Harmer
3.206
270263AC1-001 GEN
Solar/Wind Harmer
1.104
270356AE2-297 GEN
Solar/Wind Harmer
4.818
944221AF1-090 GEN
Solar/Wind Harmer
11.234
963841AG1-237 GEN
Solar/Wind Harmer
11.024
276763AC1-053 GEN1
Solar/Wind Harmer
3.957
276764AC1-053 GEN2
Solar/Wind Harmer
3.957
276668AB2-070 GEN1
Solar/Wind Harmer
2.213
276848AB2-070 GEN3
Solar/Wind Harmer
2.213
276849AB2-070 GEN2
Solar/Wind Harmer
2.213
24386405FR-21G C
Solar/Wind Harmer
4.297
24387005FR-3G C
Solar/Wind Harmer
3.952
970289AG2-191 GEN
Solar/Wind Harmer
1.875
25306009OHH W.
Adder
2.793
253372AE2-315 SEC3
Adder
1.832
253372AE2-315 SEC3
Adder
1.832
972267AH1-718 GEN
Adder
3.983
274823ROCKFORD ;21
Adder
18.472
274744AC1-111 GEN8
Adder
5.228
274746AC1-111 G10
Adder
5.228
274728ELWOOD EC;5P
Adder
15.317
274731ELWOOD EC;2P
Adder
15.317
274733ELWOOD EC;3P
Adder
15.317
274735ELWOOD EC;4P
Adder
15.317
274675JOLIET 29;7U
Adder
28.551
23750501ELLIOTTS
Solar/Wind Helper
0.647
253370AE2-315 SEC1
Adder
1.937
253371AE2-315 SEC2
Adder
1.832
274761LEE CO EC;2U
Adder
8.871
274766LEE CO EC;7U
Adder
8.766
274822ROCKFORD ;11
Adder
18.607
25326309TAIT D
Adder
1.032
274828WAUKEGAN ;BP
Adder
10.373
274682WAUKEGAN ;7U
Adder
16.869
274745AC1-111 GEN9
Adder
5.228
274732ELWOOD EC;7P
Adder
15.317
274674JOLIET 9 ;6U
Adder
14.342
274676JOLIET 29;8U
Adder
10.069
254303AC2-168 GEN
Solar/Wind Helper
0.154
241966AE1-183 GEN
Solar/Wind Helper
0.247
238185AF2-356 C
Solar/Wind Helper
2.102
20089026BF_G21_K23
Solar/Wind Helper
0.446
20084626FORWARD
Solar/Wind Helper
0.335
964201AG1-281 GEN
Solar/Wind Helper
0.452
238126S14_GEN_1
Solar/Wind Helper
0.645
20091526CHSTN_FL
Solar/Wind Helper
0.544
238120AE2-309 GEN
Solar/Wind Helper
0.406
20090526Q36
Solar/Wind Helper
0.956
203952AE2-129 C
Solar/Wind Helper
0.441
23652301WDPWR_K20
Solar/Wind Helper
0.14
241997AF1-093 GEN
Solar/Wind Helper
0.247
241985AE1-237 GEN
Solar/Wind Helper
0.241
241982AE2-343 S C
Solar/Wind Helper
0.216
203955AF1-039 C O1
Solar/Wind Helper
0.355
23750701CROSSCHOOL
Solar/Wind Helper
1.137
20089126CSLMN_L13
Solar/Wind Helper
0.564
20089226LOOKOUT
Solar/Wind Helper
0.562
238118U2-030_1
Solar/Wind Helper
0.274
20088926STNY CRK
Solar/Wind Helper
0.77
203940AF1-140 C
Solar/Wind Helper
0.371
20094526CT_V3-030
Solar/Wind Helper
0.443
203846AF2-130 C
Solar/Wind Helper
0.428
20088626ARWF_N39
Solar/Wind Helper
1.129
946581AF1-322 GEN
Solar/Wind Harmer
3.68
970879AG2-548 GEN
Solar/Wind Harmer
10.456
958121AF2-106 GEN
Solar/Wind Harmer
5.826
270186AC1-089 GEN
Solar/Wind Harmer
7.579
270367AC2-061_GEN
Solar/Wind Harmer
3.93
970093AG2-073 GEN
Solar/Wind Harmer
6.439
972167AH1-666 GEN
Solar/Wind Harmer
9.688
972273AH1-721 GEN
Adder
100.618
3429391JKCT 9G
Adder
9.999
339243AC2-075 GEN1
Solar/Wind Harmer
0.542
339206AE1-143 GEN
Solar/Wind Harmer
2.528
970455AG2-298 GEN
Solar/Wind Harmer
4.124
252507AC2-088 GEN
Solar/Wind Harmer
2.108
958171AF2-111 GEN
Solar/Wind Harmer
29.368
970653AG2-424 GEN
Solar/Wind Harmer
0.818
339255AE2-071 GEN
Solar/Wind Harmer
1.366
339250AF1-203 GEN
Solar/Wind Harmer
0.703
25196008MFTGT1
Adder
1.543
252519AF1-045_GEN
Solar/Wind Harmer
4.153
25194608D.CRK4
Adder
1.856
252524AE2-267 GEN
Solar/Wind Harmer
1.77
25196608WSDLE5
Adder
9.632
270030AE2-140 GEN
Solar/Wind Harmer
21.915
253317AC1-085 GEN4
Solar/Wind Harmer
9.117
946181AF1-283 GEN
Solar/Wind Harmer
14.157
970193AG2-126 GEN
Solar/Wind Harmer
15.734
24728705AND G3
Adder
8.411
24728505AND G1
Adder
4.021
253394AE2-221_GEN
Solar/Wind Harmer
4.748
942481AE2-261 GEN
Solar/Wind Harmer
30.351
957381AF2-032 GEN
Solar/Wind Harmer
2.028
962771AG1-126 GEN
Solar/Wind Harmer
32.808
970153AG2-106 GEN
Solar/Wind Harmer
14.306
24379505HDWTR1G C
Solar/Wind Harmer
7.972
270240V3-007_GEN2
Solar/Wind Harmer
6.237
276785W4-005 GEN1
Solar/Wind Harmer
3.022
971993AH1-541 GEN
Solar/Wind Harmer
9.233
24386205FR-12G C
Solar/Wind Harmer
4.281
247642Z2-115 C
Solar/Wind Harmer
0.063
965461AG1-414 GEN
Solar/Wind Harmer
2.238
970289AG2-191 GEN
Solar/Wind Harmer
0.757
270004AE1-209 GEN
Solar/Wind Harmer
5.379
24690905MDL-1G C
Solar/Wind Harmer
7.897
253370AE2-315 SEC1
Adder
1.937
253371AE2-315 SEC2
Adder
1.832
274760LEE CO EC;1U
Adder
8.871
274767LEE CO EC;8U
Adder
8.766
274682WAUKEGAN ;7U
Adder
16.869
274729ELWOOD EC;1P
Adder
15.317
274730ELWOOD EC;6P
Adder
15.317
274734ELWOOD EC;8P
Adder
15.317
274736ELWOOD EC;9P
Adder
15.317
237048AF1-022 C
Solar/Wind Helper
0.19
235058AG1-386 C
Solar/Wind Helper
0.455
237046AF1-021 C
Solar/Wind Helper
0.331
202652Y1-033 WT C
Solar/Wind Helper
0.537
23562501BACKB
Solar/Wind Helper
0.856
964991AG1-363 GEN
Solar/Wind Helper
3.486
20092526R32
Solar/Wind Helper
1.091
238127S14_GEN_2
Solar/Wind Helper
0.645
20303426NA_O38_P22
Solar/Wind Helper
0.926
203993AD2-133_GEN1
Solar/Wind Helper
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
21.601
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.934
TVALTFEXP_TVA->PJM
CLTF
11.244
NYPJM->LTFIMP_NY
CLTF
5.068
LGEELTFEXP_LGEE->PJM
CLTF
8.183
WECLTFEXP_WEC->PJM
CLTF
3.631
AG2-052LTFEXP_AG2-052->PJM
LTF
0.218
AH1-155LTFEXP_AH1-155->PJM
LTF
0.328
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
42.677
MECLTFEXP_MEC->PJM
CLTF
16.745
SIGELTFEXP_SIGE->PJM
CLTF
0.592
CPLELTFEXP_CPLE->PJM
CLTF
7.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
143.77
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 100.62 MW.

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10856___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10856___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.88 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5626.94
MW Contribution:
86.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.675
957241AF2-018 GEN
Solar/Wind Harmer
7.959
270053AF1-130 C
Solar/Wind Harmer
31.802
270399AC1-101 GEN
Solar/Wind Harmer
7.511
270400AC1-102 GEN
Solar/Wind Harmer
7.511
941621AE2-160 GEN
Adder
5.587
970281AG2-184 GEN
Solar/Wind Harmer
32.57
24289405MTG1
50/50
11.803
971313AH1-133 GEN
Solar/Wind Harmer
9.12
971061AG2-657 GEN
Solar/Wind Harmer
13.811
971985AH1-537 GEN
Solar/Wind Harmer
27.028
962211AG1-066 GEN
Solar/Wind Harmer
3.543
24734705WLF1G3
Adder
8.207
24734805WLF1G4
Adder
8.207
24734905WLF1G5
Adder
8.207
24735105WLF2G1
Adder
8.038
966391AG1-508 GEN
Solar/Wind Harmer
4.81
971331AH1-145 GEN
Solar/Wind Harmer
12.539
971329AH1-144 GEN
Solar/Wind Harmer
8.009
971981AH1-535 GEN
Solar/Wind Harmer
12.699
972163AH1-664 GEN
Solar/Wind Harmer
12.28
972165AH1-665 GEN
Solar/Wind Harmer
9.824
3429211JKCT 2G
Adder
14.268
270291AC1-194 GEN
Solar/Wind Harmer
6.183
339216AC1-074 GEN
Solar/Wind Harmer
2.024
25196108MFTGT2
Adder
1.775
25196108MFTGT2
Adder
1.648
25196408WSDLE3
Adder
10.024
25196308WSDLE2
Adder
9.937
25196208WSDLE1
Adder
9.912
25196708WSDLE6
Adder
9.887
25196508WSDLE4
Adder
9.638
270444AC2-157 GEN1
Solar/Wind Harmer
6.331
270445AC2-157 GEN2
Solar/Wind Harmer
6.331
270069AE2-166 C O1
Solar/Wind Harmer
10.196
253433AC1-085 GEN1
Solar/Wind Harmer
5.853
253432AC1-085 GEN2
Solar/Wind Harmer
0.295
253406AD2-031_GEN
Solar/Wind Harmer
1.384
270340AC2-060 GEN
Solar/Wind Harmer
3.244
270263AC1-001 GEN
Solar/Wind Harmer
1.117
243186AF1-051 GEN
50/50
12.678
24721705FLATG2
50/50
39.728
24723005RIVRG1
Adder
37.214
24723105RIVRG2
Adder
37.214
970913AG2-568 GEN
Solar/Wind Harmer
11.477
24728205BUCHG1
Adder
7.015
927014AC1-188 GEN
Solar/Wind Harmer
2.459
971225AH1-072 GEN
Solar/Wind Harmer
3.058
971227AH1-073 GEN
Solar/Wind Harmer
3.058
270214AC2-123 GEN
Solar/Wind Harmer
3.229
243186AF1-051 GEN
50/50
12.678
24318705GVG2
50/50
11.752
24721805FLATG3
50/50
2.675
960001AF2-291 GEN
Solar/Wind Harmer
6.087
24723205RIVRG3
Adder
37.214
270331AC1-082 GEN3
Solar/Wind Harmer
0.942
24686505CER G6
Adder
16.296
972203AH1-686 GEN
Adder
4.456
944971AF1-162 GEN
Solar/Wind Harmer
12.535
971403AH1-188 GEN
Solar/Wind Harmer
24.896
24728305BUCHG2
Adder
7.015
971687AH1-348 GEN
Solar/Wind Harmer
1.53
24735205WLF2G2
Adder
8.038
971073AG2-665 GEN
Solar/Wind Harmer
1.534
970091AG2-072 GEN
Adder
95.233
945681AF1-233 GEN
Solar/Wind Harmer
23.089
3429241JKCT 3G
Adder
14.456
339221AD2-048_GEN
Solar/Wind Harmer
1.866
339211AE2-254 GEN
Solar/Wind Harmer
1.837
3429421JKCT 10G
Adder
10.103
943111AE2-339 GEN
Solar/Wind Harmer
1.07
339241AF1-083 GEN
Solar/Wind Harmer
1.979
970653AG2-424 GEN
Solar/Wind Harmer
5.716
964901AG1-354 GEN
Solar/Wind Harmer
17.72
25196808ZIMRHP
Adder
88.501
25196008MFTGT1
Adder
1.61
252516AE2-318_GEN
Solar/Wind Harmer
11.536
252510AF1-249 C
Solar/Wind Harmer
0.479
25194608D.CRK4
Adder
1.876
270336AE1-100 GEN
Solar/Wind Harmer
1.956
253316AC1-085 GEN3
Solar/Wind Harmer
9.221
946171AF1-282 GEN
Solar/Wind Harmer
11.014
943811AF1-049 GEN
Solar/Wind Harmer
4.099
24728605AND G2
Adder
4.069
253398AE2-221_GEN2
Solar/Wind Harmer
4.804
270222AC2-111 GEN
Solar/Wind Harmer
4.717
944031AF1-071 GEN
Solar/Wind Harmer
1.061
963741AG1-226 GEN
Solar/Wind Harmer
46.357
965911AG1-460 GEN
Solar/Wind Harmer
1.434
962761AG1-125 GEN
Solar/Wind Harmer
33.21
970149AG2-104 GEN
Solar/Wind Harmer
20.507
970155AG2-107 GEN
Solar/Wind Harmer
14.481
942081AE2-220 GEN
Solar/Wind Harmer
6.527
270209AC1-174_GEN
Solar/Wind Harmer
4.153
270437AC2-090 C
Solar/Wind Harmer
5.696
270239V3-007_GEN1
Solar/Wind Harmer
1.756
276621W2-048 GEN
Solar/Wind Harmer
6.343
276686W4-005 GEN3
Solar/Wind Harmer
3.059
24385905FR-11G C
Solar/Wind Harmer
8.406
24386605FR-22G C
Solar/Wind Harmer
4.35
276903AD2-071 C
Solar/Wind Harmer
10.104
270594AE1-207 GEN
Solar/Wind Harmer
13.567
270032AE2-172
Solar/Wind Harmer
4.646
270005AE1-210 C O1
Solar/Wind Harmer
5.447
253370AE2-315 SEC1
Adder
1.962
253371AE2-315 SEC2
Adder
1.855
274761LEE CO EC;2U
Adder
8.986
274766LEE CO EC;7U
Adder
8.88
274822ROCKFORD ;11
Adder
18.851
25326309TAIT D
Adder
1.046
274828WAUKEGAN ;BP
Adder
10.51
274682WAUKEGAN ;7U
Adder
17.092
274745AC1-111 GEN9
Adder
5.298
274732ELWOOD EC;7P
Adder
15.521
274674JOLIET 9 ;6U
Adder
14.533
274676JOLIET 29;8U
Adder
10.203
254303AC2-168 GEN
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.244
238185AF2-356 C
Solar/Wind Helper
2.074
20089026BF_G21_K23
Solar/Wind Helper
0.44
20084626FORWARD
Solar/Wind Helper
0.33
964201AG1-281 GEN
Solar/Wind Helper
0.445
238126S14_GEN_1
Solar/Wind Helper
0.636
20091526CHSTN_FL
Solar/Wind Helper
0.536
238120AE2-309 GEN
Solar/Wind Helper
0.4
270356AE2-297 GEN
Solar/Wind Harmer
4.876
944221AF1-090 GEN
Solar/Wind Harmer
11.369
963841AG1-237 GEN
Solar/Wind Harmer
11.16
276763AC1-053 GEN1
Solar/Wind Harmer
4.006
276764AC1-053 GEN2
Solar/Wind Harmer
4.006
276668AB2-070 GEN1
Solar/Wind Harmer
2.24
276848AB2-070 GEN3
Solar/Wind Harmer
2.24
276849AB2-070 GEN2
Solar/Wind Harmer
2.24
24386405FR-21G C
Solar/Wind Harmer
4.35
24387005FR-3G C
Solar/Wind Harmer
4.001
970289AG2-191 GEN
Solar/Wind Harmer
1.899
25306009OHH W.
Adder
2.828
253372AE2-315 SEC3
Adder
1.855
253372AE2-315 SEC3
Adder
1.855
972267AH1-718 GEN
Adder
4.035
274823ROCKFORD ;21
Adder
18.714
274744AC1-111 GEN8
Adder
5.298
274746AC1-111 G10
Adder
5.298
274728ELWOOD EC;5P
Adder
15.521
274731ELWOOD EC;2P
Adder
15.521
274733ELWOOD EC;3P
Adder
15.521
274735ELWOOD EC;4P
Adder
15.521
274675JOLIET 29;7U
Adder
28.931
23750501ELLIOTTS
Solar/Wind Helper
0.639
23652301WDPWR_K20
Solar/Wind Helper
0.139
241997AF1-093 GEN
Solar/Wind Helper
0.244
241985AE1-237 GEN
Solar/Wind Helper
0.238
241982AE2-343 S C
Solar/Wind Helper
0.214
203955AF1-039 C O1
Solar/Wind Helper
0.35
23750701CROSSCHOOL
Solar/Wind Helper
1.122
20089126CSLMN_L13
Solar/Wind Helper
0.556
20089226LOOKOUT
Solar/Wind Helper
0.555
238118U2-030_1
Solar/Wind Helper
0.27
20088926STNY CRK
Solar/Wind Helper
0.759
203940AF1-140 C
Solar/Wind Helper
0.366
20094526CT_V3-030
Solar/Wind Helper
0.437
203846AF2-130 C
Solar/Wind Helper
0.422
20088626ARWF_N39
Solar/Wind Helper
1.113
946581AF1-322 GEN
Solar/Wind Harmer
3.726
971277AH1-098 GEN
Solar/Wind Harmer
5.52
971073AG2-665 GEN
Solar/Wind Harmer
10.556
970879AG2-548 GEN
Solar/Wind Harmer
1.534
270583AD2-179 GEN
Solar/Wind Harmer
12.98
962581AG1-107 GEN
Solar/Wind Harmer
6.183
961491AF2-440 GEN
Solar/Wind Harmer
2.569
942891AE2-308 GEN
Solar/Wind Harmer
12.236
972043AH1-570 GEN
Solar/Wind Harmer
3.049
972045AH1-571 GEN
Solar/Wind Harmer
2.439
971125AH1-004 GEN
Solar/Wind Harmer
4.843
970107AG2-081 GEN
Solar/Wind Harmer
3.632
339231AF1-038_GEN
Solar/Wind Harmer
2.178
966021AG1-471 GEN
Solar/Wind Harmer
6.442
971485AH1-239 GEN
Solar/Wind Harmer
9.528
252509AD1-136 GEN
Solar/Wind Harmer
0.304
339236AF1-050_GEN
Solar/Wind Harmer
2.145
964571AG1-320 GEN
Solar/Wind Harmer
9.672
964781AG1-341 GEN
Solar/Wind Harmer
12.441
25183208HLCRTG
Solar/Wind Harmer
6.977
25194408D.CRK1
Adder
8.632
25194508D.CRK3
Adder
1.614
945391AF1-204 GEN
Solar/Wind Harmer
14.791
24728805RICHG1
Adder
3.967
24728905RICHG2
Adder
3.967
253415AE1-040 GEN
Solar/Wind Harmer
1.171
276916AD2-100_GEN
Solar/Wind Harmer
21.637
276911AD2-131_GEN
Solar/Wind Harmer
4.373
970241AG2-163 GEN
Solar/Wind Harmer
25.754
926881AC1-175 GEN
Solar/Wind Harmer
5.696
276615X2-022 GEN
Solar/Wind Harmer
1.992
276838X2-022 GEN2
Solar/Wind Harmer
0.237
24725505WLD G2 C
Solar/Wind Harmer
4.03
24699105WLD G1 C
Solar/Wind Harmer
3.983
274880W4-005 GEN4
Solar/Wind Harmer
3.059
276174W4-005 GEN2
Solar/Wind Harmer
3.059
270383AD1-128 GEN
Solar/Wind Harmer
6.175
24387305FR-4G C
Solar/Wind Harmer
5.138
966841AG1-555 GEN
Solar/Wind Harmer
2.539
970291AG2-192 GEN
Solar/Wind Harmer
1.299
970291AG2-192 GEN
Solar/Wind Harmer
0.418
270180AB1-006 GEN1
Solar/Wind Harmer
7.164
253370AE2-315 SEC1
Adder
1.962
247621Y3-024
Adder
0.233
274764LEE CO EC;5U
Adder
9.007
274765LEE CO EC;6U
Adder
9.007
274762LEE CO EC;3U
Adder
8.986
274763LEE CO EC;4U
Adder
8.901
972235AH1-702 GEN1
Adder
2.423
972236AH1-702 GEN2
Adder
2.107
25322209TAIT E
Adder
9.312
25322209TAIT E
Adder
9.102
274683WAUKEGAN ;8U
Adder
20.05
274683WAUKEGAN ;8U
Adder
16.901
274696ROCKY RD ;4P
Adder
10.84
274695ROCKY RD ;2P
Adder
10.59
274693ROCKY RD ;1P
Adder
10.485
274697ROCKY RD ;3P
Adder
2.877
274674JOLIET 9 ;6U
Adder
14.533
237043AE2-125 C
Solar/Wind Helper
0.172
254304AE2-114 C
Solar/Wind Helper
0.21
254305AE2-115 C
Solar/Wind Helper
0.21
962101AG1-054 GEN
Solar/Wind Helper
0.622
241967AE2-285_GEN
Solar/Wind Helper
0.609
241801AE1-079 GEN
Solar/Wind Helper
0.238
23585401KL_K28_T16
Solar/Wind Helper
1.215
23751201ROTHROCK
Solar/Wind Helper
0.695
235054AD2-180 GEN
Solar/Wind Helper
1.606
946071AF1-272 GEN
Solar/Wind Helper
2.52
238117U2-030
Solar/Wind Helper
0.27
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.83
235531U2-073 GEN
Solar/Wind Helper
2.561
203818AF1-086 GEN
Solar/Wind Helper
1.56
203961AE2-224 GEN
Solar/Wind Helper
2.218
946381AF1-302 GEN
Solar/Wind Helper
0.205
24289405MTG1
50/50
11.803
24318705GVG2
50/50
11.752
24722005FLATG5
50/50
2.675
24721905FLATG4
50/50
48.862
270330AC1-082 GEN2
Solar/Wind Harmer
0.94
270329AC1-082 GEN1
Solar/Wind Harmer
0.94
24686405CER G5
Adder
16.168
971191AH1-055 GEN
Solar/Wind Harmer
33.281
960911AF2-382 GEN
Solar/Wind Harmer
11.778
957541AF2-048 GEN
Solar/Wind Harmer
2.459
972103AH1-617 GEN
Solar/Wind Harmer
31.019
971461AH1-227 GEN
Solar/Wind Harmer
7.843
270346AE1-212 GEN
Solar/Wind Harmer
13.316
943031AE2-326 GEN
Solar/Wind Harmer
5.082
970879AG2-548 GEN
Solar/Wind Harmer
10.556
958121AF2-106 GEN
Solar/Wind Harmer
5.883
270186AC1-089 GEN
Solar/Wind Harmer
7.655
270367AC2-061_GEN
Solar/Wind Harmer
3.969
970093AG2-073 GEN
Solar/Wind Harmer
6.505
972167AH1-666 GEN
Solar/Wind Harmer
9.788
972273AH1-721 GEN
Adder
101.651
3429391JKCT 9G
Adder
10.103
339243AC2-075 GEN1
Solar/Wind Harmer
0.548
339206AE1-143 GEN
Solar/Wind Harmer
2.555
970455AG2-298 GEN
Solar/Wind Harmer
4.167
252507AC2-088 GEN
Solar/Wind Harmer
2.13
958171AF2-111 GEN
Solar/Wind Harmer
29.678
970653AG2-424 GEN
Solar/Wind Harmer
0.827
339255AE2-071 GEN
Solar/Wind Harmer
1.381
339250AF1-203 GEN
Solar/Wind Harmer
0.711
25196008MFTGT1
Adder
1.56
252519AF1-045_GEN
Solar/Wind Harmer
4.199
25194608D.CRK4
Adder
1.876
252524AE2-267 GEN
Solar/Wind Harmer
1.789
25196608WSDLE5
Adder
9.738
270030AE2-140 GEN
Solar/Wind Harmer
22.165
253317AC1-085 GEN4
Solar/Wind Harmer
9.221
946181AF1-283 GEN
Solar/Wind Harmer
14.318
970193AG2-126 GEN
Solar/Wind Harmer
15.92
24728705AND G3
Adder
8.51
24728505AND G1
Adder
4.069
253394AE2-221_GEN
Solar/Wind Harmer
4.804
942481AE2-261 GEN
Solar/Wind Harmer
30.722
957381AF2-032 GEN
Solar/Wind Harmer
2.053
962771AG1-126 GEN
Solar/Wind Harmer
33.21
970153AG2-106 GEN
Solar/Wind Harmer
14.481
24379505HDWTR1G C
Solar/Wind Harmer
8.07
270240V3-007_GEN2
Solar/Wind Harmer
6.314
276785W4-005 GEN1
Solar/Wind Harmer
3.059
971993AH1-541 GEN
Solar/Wind Harmer
9.348
24386205FR-12G C
Solar/Wind Harmer
4.335
247642Z2-115 C
Solar/Wind Harmer
0.064
965461AG1-414 GEN
Solar/Wind Harmer
2.266
970289AG2-191 GEN
Solar/Wind Harmer
0.767
270004AE1-209 GEN
Solar/Wind Harmer
5.447
24690905MDL-1G C
Solar/Wind Harmer
7.997
253370AE2-315 SEC1
Adder
1.962
253371AE2-315 SEC2
Adder
1.855
274760LEE CO EC;1U
Adder
8.986
274767LEE CO EC;8U
Adder
8.88
274682WAUKEGAN ;7U
Adder
17.092
274729ELWOOD EC;1P
Adder
15.521
274730ELWOOD EC;6P
Adder
15.521
274734ELWOOD EC;8P
Adder
15.521
274736ELWOOD EC;9P
Adder
15.521
237048AF1-022 C
Solar/Wind Helper
0.188
235058AG1-386 C
Solar/Wind Helper
0.45
237046AF1-021 C
Solar/Wind Helper
0.327
202652Y1-033 WT C
Solar/Wind Helper
0.53
23562501BACKB
Solar/Wind Helper
0.844
964991AG1-363 GEN
Solar/Wind Helper
3.438
20092526R32
Solar/Wind Helper
1.076
238127S14_GEN_2
Solar/Wind Helper
0.636
20303426NA_O38_P22
Solar/Wind Helper
0.913
LAGNLTFEXP_LAGN->PJM
CLTF
21.853
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
11.37
NYPJM->LTFIMP_NY
CLTF
4.988
LGEELTFEXP_LGEE->PJM
CLTF
8.269
WECLTFEXP_WEC->PJM
CLTF
3.678
AG2-052LTFEXP_AG2-052->PJM
LTF
0.221
AH1-155LTFEXP_AH1-155->PJM
LTF
0.332
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.565
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.151
MECLTFEXP_MEC->PJM
CLTF
16.954
SIGELTFEXP_SIGE->PJM
CLTF
0.599
CPLELTFEXP_CPLE->PJM
CLTF
7.358
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.448
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 101.65 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.59 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2365.35
MW Contribution:
37.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.153
24802706KYGER 1LP
50/50
2.435
24803506KYGER 5LP
50/50
2.378
971985AH1-537 GEN
Solar/Wind Harmer
49.684
25196408WSDLE3
Adder
9.213
25196308WSDLE2
Adder
9.133
25196208WSDLE1
Adder
9.11
25196708WSDLE6
Adder
9.087
25196508WSDLE4
Adder
8.858
253433AC1-085 GEN1
Solar/Wind Harmer
5.417
253432AC1-085 GEN2
Solar/Wind Harmer
0.273
25196108MFTGT2
Adder
1.534
25196108MFTGT2
Adder
1.424
972163AH1-664 GEN
Solar/Wind Harmer
9.168
972165AH1-665 GEN
Solar/Wind Harmer
7.335
253406AD2-031_GEN
Solar/Wind Harmer
1.154
339216AC1-074 GEN
Solar/Wind Harmer
1.482
270340AC2-060 GEN
Solar/Wind Harmer
2.616
270263AC1-001 GEN
Solar/Wind Harmer
0.88
253372AE2-315 SEC3
Adder
1.561
253372AE2-315 SEC3
Adder
1.561
25306009OHH W.
Adder
2.343
270356AE2-297 GEN
Solar/Wind Harmer
3.599
3429211JKCT 2G
Adder
8.841
971029AG2-637 GEN
Solar/Wind Harmer
11.181
270543AE2-219 C
Solar/Wind Harmer
7.251
247536S-71 GEN
Solar/Wind Harmer
2.858
964611AG1-324 GEN
Solar/Wind Harmer
2.681
961761AG1-017 GEN
Solar/Wind Harmer
0.293
945581AF1-223 GEN
Solar/Wind Harmer
3.049
241972AD1-140 GEN
Solar/Wind Harmer
2.984
270432AC2-029 GEN
Solar/Wind Harmer
4.634
970289AG2-191 GEN
Solar/Wind Harmer
1.232
958711AF2-162 GEN
Solar/Wind Harmer
0.656
24729505KEY G4
Adder
4.046
253338AC1-165 GEN
Solar/Wind Harmer
0.663
253343AC1-166 GEN
Solar/Wind Harmer
0.663
270444AC2-157 GEN1
Solar/Wind Harmer
3.34
270445AC2-157 GEN2
Solar/Wind Harmer
3.34
963841AG1-237 GEN
Solar/Wind Harmer
6.259
24386405FR-21G C
Solar/Wind Harmer
2.437
24387005FR-3G C
Solar/Wind Harmer
2.241
963791AG1-232 GEN
Solar/Wind Harmer
7.617
946581AF1-322 GEN
Solar/Wind Harmer
5.719
24691005MDL-2G C
Solar/Wind Harmer
2.067
270071AF1-092 GEN
Solar/Wind Harmer
8.327
959141AF2-205 GEN
Solar/Wind Harmer
3.307
958391AF2-133 GEN
Solar/Wind Harmer
4.945
944221AF1-090 GEN
Solar/Wind Harmer
5.93
276668AB2-070 GEN1
Solar/Wind Harmer
1.199
276848AB2-070 GEN3
Solar/Wind Harmer
1.199
276849AB2-070 GEN2
Solar/Wind Harmer
1.199
276763AC1-053 GEN1
Solar/Wind Harmer
2.139
276764AC1-053 GEN2
Solar/Wind Harmer
2.139
274853TWINGROVE;U1
Solar/Wind Harmer
3.87
274775LINCOLN ;6U
Adder
4.436
274776LINCOLN ;7U
Adder
4.436
274777LINCOLN ;8U
Adder
4.436
972227AH1-698 GEN1
Adder
1.369
972228AH1-698 GEN2
Adder
1.944
274728ELWOOD EC;5P
Adder
8.613
274731ELWOOD EC;2P
Adder
8.614
274733ELWOOD EC;3P
Adder
8.614
274735ELWOOD EC;4P
Adder
8.614
274800UNIV PARK;3U
Adder
3.055
274801UNIV PARK;4U
Adder
3.055
972037AH1-567 GEN1
Adder
0.096
274827FISK ;RP
Adder
4.063
274687WILL CNTY;4U
Adder
14.622
274687WILL CNTY;4U
Adder
14.622
274675JOLIET 29;7U
Adder
16.054
274675JOLIET 29;7U
Adder
15.48
274744AC1-111 GEN8
Adder
2.918
274746AC1-111 G10
Adder
2.918
274854TWINGROVE;U2
Solar/Wind Harmer
0.363
24803006KYGER 3HP
50/50
4.125
24802806KYGER 2HP
50/50
4.108
24802906KYGER 2LP
50/50
2.412
25183008BIOENL
50/50
0.03
252509AD1-136 GEN
Solar/Wind Harmer
0.294
25183208HLCRTG
Solar/Wind Harmer
6.595
25194408D.CRK1
Adder
7.9
25194508D.CRK3
Adder
1.477
962581AG1-107 GEN
Solar/Wind Harmer
4.434
961491AF2-440 GEN
Solar/Wind Harmer
1.843
972043AH1-570 GEN
Solar/Wind Harmer
2.117
972045AH1-571 GEN
Solar/Wind Harmer
1.694
270269AC2-059
Solar/Wind Harmer
7.883
253415AE1-040 GEN
Solar/Wind Harmer
0.948
253370AE2-315 SEC1
Adder
1.651
971125AH1-004 GEN
Solar/Wind Harmer
3.263
970107AG2-081 GEN
Solar/Wind Harmer
2.447
24728805RICHG1
Adder
3.029
24728905RICHG2
Adder
3.029
25322209TAIT E
Adder
7.785
25322209TAIT E
Adder
7.61
253349AC2-067 GEN
Solar/Wind Harmer
1.622
253400AC2-068 GEN
Solar/Wind Harmer
0.652
25326109MON D
Adder
1.021
926881AC1-175 GEN
Solar/Wind Harmer
4.212
942891AE2-308 GEN
Solar/Wind Harmer
7.426
270383AD1-128 GEN
Solar/Wind Harmer
4.53
970883AG2-550 GEN
Solar/Wind Harmer
7.251
970885AG2-551 GEN
Solar/Wind Harmer
1.686
247621Y3-024
Adder
0.167
964611AG1-324 GEN
Solar/Wind Harmer
0.36
270201AC2-176 GEN
Solar/Wind Harmer
3.513
24725505WLD G2 C
Solar/Wind Harmer
2.705
24699105WLD G1 C
Solar/Wind Harmer
2.673
270031AE2-169
Solar/Wind Harmer
5.45
270599AE1-208 GEN
Solar/Wind Harmer
5.45
964571AG1-320 GEN
Solar/Wind Harmer
5.334
970291AG2-192 GEN
Solar/Wind Harmer
0.843
970291AG2-192 GEN
Solar/Wind Harmer
0.272
944541AF1-119 GEN
Solar/Wind Harmer
2.715
960971AF2-388 GEN
Solar/Wind Harmer
7.089
942221AE2-234 GEN
Solar/Wind Harmer
2.151
945391AF1-204 GEN
Solar/Wind Harmer
8.333
970241AG2-163 GEN
Solar/Wind Harmer
14.459
25326509SID D
Adder
0.751
24387305FR-4G C
Solar/Wind Harmer
2.878
966841AG1-555 GEN
Solar/Wind Harmer
1.422
270180AB1-006 GEN1
Solar/Wind Harmer
4.02
24697605MDL-3G C
Solar/Wind Harmer
2.06
24755605MDL-5G
Solar/Wind Harmer
1.347
24697905MDL-4G C
Solar/Wind Harmer
1.282
270181AB1-006 GEN2
Solar/Wind Harmer
0.4
945421AF1-207 GEN
Solar/Wind Harmer
7.8
957841AF2-078 GEN
Solar/Wind Harmer
3.358
339236AF1-050_GEN
Solar/Wind Harmer
0.993
274880W4-005 GEN4
Solar/Wind Harmer
1.638
276174W4-005 GEN2
Solar/Wind Harmer
1.638
276615X2-022 GEN
Solar/Wind Harmer
1.059
276838X2-022 GEN2
Solar/Wind Harmer
0.126
276916AD2-100_GEN
Solar/Wind Harmer
11.356
276911AD2-131_GEN
Solar/Wind Harmer
2.295
270535AF1-215 GEN1
Solar/Wind Harmer
2.441
270536AF1-215 GEN2
Solar/Wind Harmer
2.441
274770LINCOLN ;1U
Adder
4.436
274771LINCOLN ;2U
Adder
4.436
274674JOLIET 9 ;6U
Adder
8.063
274805UNIV PK N;1U
Adder
2.628
274808UNIV PK N;4U
Adder
2.611
274696ROCKY RD ;4P
Adder
5.933
274695ROCKY RD ;2P
Adder
5.796
274693ROCKY RD ;1P
Adder
5.739
274697ROCKY RD ;3P
Adder
1.575
237033AB1-150 GEN
Solar/Wind Helper
0.409
960611AF2-352 GEN
Solar/Wind Harmer
0.12
24803406KYGER 5HP
50/50
4.081
24803206KYGER 4HP
50/50
4.076
252516AE2-318_GEN
Solar/Wind Harmer
10.768
25196808ZIMRHP
Adder
80.577
25194608D.CRK4
Adder
1.717
252510AF1-249 C
Solar/Wind Harmer
0.435
253316AC1-085 GEN3
Solar/Wind Harmer
8.534
946171AF1-282 GEN
Solar/Wind Harmer
10.193
25196008MFTGT1
Adder
1.391
253398AE2-221_GEN2
Solar/Wind Harmer
4.361
945681AF1-233 GEN
Solar/Wind Harmer
17.478
339221AD2-048_GEN
Solar/Wind Harmer
1.333
270222AC2-111 GEN
Solar/Wind Harmer
3.827
944031AF1-071 GEN
Solar/Wind Harmer
0.861
270273AD2-016 GEN
Solar/Wind Harmer
2.247
253370AE2-315 SEC1
Adder
1.651
253371AE2-315 SEC2
Adder
1.561
943111AE2-339 GEN
Solar/Wind Harmer
0.715
25326309TAIT D
Adder
0.874
3429421JKCT 10G
Adder
6.485
3429241JKCT 3G
Adder
8.957
942081AE2-220 GEN
Solar/Wind Harmer
4.827
270209AC1-174_GEN
Solar/Wind Harmer
3.072
270437AC2-090 C
Solar/Wind Harmer
4.212
270239V3-007_GEN1
Solar/Wind Harmer
1.299
270005AE1-210 C O1
Solar/Wind Harmer
3.872
24728605AND G2
Adder
2.694
970825AG2-519 GEN
Solar/Wind Harmer
1.469
945371AF1-202 GEN
Solar/Wind Harmer
4.69
276903AD2-071 C
Solar/Wind Harmer
6.702
270594AE1-207 GEN
Solar/Wind Harmer
8.993
270032AE2-172
Solar/Wind Harmer
3.08
339211AE2-254 GEN
Solar/Wind Harmer
0.998
958861AF2-177 GEN
Solar/Wind Harmer
7.178
965651AG1-433 GEN
Solar/Wind Harmer
3.544
270024AE2-089 GEN
Solar/Wind Harmer
2.988
970653AG2-424 GEN
Solar/Wind Harmer
3.003
253333AC1-068 GEN
Solar/Wind Harmer
0.639
970091AG2-072 GEN
Adder
46.355
963741AG1-226 GEN
Solar/Wind Harmer
26.027
339241AF1-083 GEN
Solar/Wind Harmer
0.959
24385905FR-11G C
Solar/Wind Harmer
4.709
24386605FR-22G C
Solar/Wind Harmer
2.437
24791305MDL-5G
Solar/Wind Harmer
1.347
940581AE2-045 GEN
Solar/Wind Harmer
5.601
971605AH1-302 GEN
Solar/Wind Harmer
4.789
964861AG1-349 GEN
Solar/Wind Harmer
4.271
971917AH1-482 GEN
Solar/Wind Harmer
4.927
958381AF2-132 GEN
Solar/Wind Harmer
4.923
964901AG1-354 GEN
Solar/Wind Harmer
8.138
276686W4-005 GEN3
Solar/Wind Harmer
1.638
276621W2-048 GEN
Solar/Wind Harmer
3.373
965911AG1-460 GEN
Solar/Wind Harmer
0.754
270055AF2-134 C O1
Solar/Wind Harmer
1.627
274773LINCOLN ;4U
Adder
4.436
274774LINCOLN ;5U
Adder
4.436
274732ELWOOD EC;7P
Adder
8.613
274802UNIV PARK;5U
Adder
3.054
274674JOLIET 9 ;6U
Adder
8.063
274812UNIV PK N;8U
Adder
2.622
274723RIVER EC ;12
Adder
9.381
274751CRETE EC ;1U
Adder
4.313
274754CRETE EC ;4U
Adder
4.313
274676JOLIET 29;8U
Adder
16.054
274745AC1-111 GEN9
Adder
2.918
960001AF2-291 GEN
Solar/Wind Helper
1.729
270331AC1-082 GEN3
Solar/Wind Helper
0.194
235780M24_1
Solar/Wind Helper
0.507
24803106KYGER 3LP
50/50
2.429
24803306KYGER 4LP
50/50
2.378
971191AH1-055 GEN
Solar/Wind Harmer
71.613
252507AC2-088 GEN
Solar/Wind Harmer
2.061
252519AF1-045_GEN
Solar/Wind Harmer
3.919
25194608D.CRK4
Adder
1.717
252524AE2-267 GEN
Solar/Wind Harmer
1.644
25196608WSDLE5
Adder
8.95
253317AC1-085 GEN4
Solar/Wind Harmer
8.534
946181AF1-283 GEN
Solar/Wind Harmer
13.251
25196008MFTGT1
Adder
1.348
958171AF2-111 GEN
Solar/Wind Harmer
24.74
253394AE2-221_GEN
Solar/Wind Harmer
4.361
972167AH1-666 GEN
Solar/Wind Harmer
7.448
270367AC2-061_GEN
Solar/Wind Harmer
2.87
270186AC1-089 GEN
Solar/Wind Harmer
5.445
339243AC2-075 GEN1
Solar/Wind Harmer
0.401
253303V4-073 C
Solar/Wind Harmer
0.095
253370AE2-315 SEC1
Adder
1.651
253371AE2-315 SEC2
Adder
1.561
960071AF2-298 GEN
Solar/Wind Harmer
1.198
3429391JKCT 9G
Adder
6.485
24379505HDWTR1G C
Solar/Wind Harmer
5.968
270240V3-007_GEN2
Solar/Wind Harmer
4.669
970093AG2-073 GEN
Solar/Wind Harmer
3.762
270004AE1-209 GEN
Solar/Wind Harmer
3.872
24728705AND G3
Adder
5.634
24728505AND G1
Adder
2.694
946031AF1-268 GEN
Solar/Wind Harmer
5.828
970825AG2-519 GEN
Solar/Wind Harmer
3.944
962031AG1-047 GEN
Solar/Wind Harmer
2.067
957741AF2-068 GEN
Solar/Wind Harmer
10.253
970455AG2-298 GEN
Solar/Wind Harmer
2.327
965461AG1-414 GEN
Solar/Wind Harmer
1.471
970289AG2-191 GEN
Solar/Wind Harmer
0.498
247642Z2-115 C
Solar/Wind Harmer
0.041
970653AG2-424 GEN
Solar/Wind Harmer
0.434
944531AF1-118 GEN
Solar/Wind Harmer
21.518
253325AC1-069 GEN
Solar/Wind Harmer
0.639
970193AG2-126 GEN
Solar/Wind Harmer
8.969
339206AE1-143 GEN
Solar/Wind Harmer
1.271
24386205FR-12G C
Solar/Wind Harmer
2.428
24690905MDL-1G C
Solar/Wind Harmer
4.487
970781AG2-491 GEN
Solar/Wind Harmer
5.589
270518AE2-148 GEN
Solar/Wind Harmer
6.728
964401AG1-302 GEN
Solar/Wind Harmer
4.923
276785W4-005 GEN1
Solar/Wind Harmer
1.638
971993AH1-541 GEN
Solar/Wind Harmer
5.005
942481AE2-261 GEN
Solar/Wind Harmer
16.153
957381AF2-032 GEN
Solar/Wind Harmer
1.08
972273AH1-721 GEN
Adder
43.936
274772LINCOLN ;3U
Adder
4.436
972259AH1-714 GEN
Adder
10.006
274729ELWOOD EC;1P
Adder
8.614
274730ELWOOD EC;6P
Adder
8.613
274734ELWOOD EC;8P
Adder
8.613
274736ELWOOD EC;9P
Adder
8.613
274803UNIV PARK;6U
Adder
3.054
972038AH1-567 GEN2
Adder
0.191
274826FISK ;BP
Adder
5.733
274814UNIV PK N;0U
Adder
2.645
274807UNIV PK N;3U
Adder
2.64
274811UNIV PK N;7U
Adder
2.622
274724RIVER EC ;11
Adder
9.272
274752CRETE EC ;2U
Adder
4.313
274753CRETE EC ;3U
Adder
4.313
274676JOLIET 29;8U
Adder
15.48
274682WAUKEGAN ;7U
Adder
5.491
270330AC1-082 GEN2
Solar/Wind Helper
0.195
270329AC1-082 GEN1
Solar/Wind Helper
0.195
LAGNLTFEXP_LAGN->PJM
CLTF
6.674
TVALTFEXP_TVA->PJM
CLTF
3.152
NYPJM->LTFIMP_NY
CLTF
1.71
LGEELTFEXP_LGEE->PJM
CLTF
5.221
WECLTFEXP_WEC->PJM
CLTF
1.971
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.322
AG2-052LTFEXP_AG2-052->PJM
LTF
0.126
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
75.047
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.848
MECLTFEXP_MEC->PJM
CLTF
8.254
SIGELTFEXP_SIGE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.683
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 43.94 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.94 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2185.8
MW Contribution:
36.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.156
24802706KYGER 1LP
50/50
2.437
24803506KYGER 5LP
50/50
2.38
971985AH1-537 GEN
Solar/Wind Harmer
5.763
25196408WSDLE3
Adder
9.057
25196308WSDLE2
Adder
8.978
25196208WSDLE1
Adder
8.956
25196708WSDLE6
Adder
8.933
25196508WSDLE4
Adder
8.708
25196108MFTGT2
Adder
1.509
25196108MFTGT2
Adder
1.401
972163AH1-664 GEN
Solar/Wind Harmer
7.027
972165AH1-665 GEN
Solar/Wind Harmer
5.628
253406AD2-031_GEN
Solar/Wind Harmer
0.458
339216AC1-074 GEN
Solar/Wind Harmer
0.162
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.58
253372AE2-315 SEC3
Adder
1.514
253372AE2-315 SEC3
Adder
1.514
25306009OHH W.
Adder
2.27
270356AE2-297 GEN
Solar/Wind Harmer
0
3429211JKCT 2G
Adder
8.721
971029AG2-637 GEN
Solar/Wind Harmer
7.57
270543AE2-219 C
Solar/Wind Harmer
3.433
247536S-71 GEN
Solar/Wind Harmer
0.191
964611AG1-324 GEN
Solar/Wind Harmer
1.811
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.738
270432AC2-029 GEN
Solar/Wind Harmer
2.001
241972AD1-140 GEN
Solar/Wind Harmer
0.484
970289AG2-191 GEN
Solar/Wind Harmer
0.834
24729505KEY G4
Adder
3.899
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.68
24386405FR-21G C
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
5.053
270071AF1-092 GEN
Solar/Wind Harmer
7.11
971611AH1-305 GEN
Solar/Wind Harmer
2.204
959141AF2-205 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.16
958391AF2-133 GEN
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.144
276848AB2-070 GEN3
Solar/Wind Harmer
0.143
276849AB2-070 GEN2
Solar/Wind Harmer
0.144
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.806
970169AG2-114 GEN
Solar/Wind Harmer
3.591
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
4.277
274776LINCOLN ;7U
Adder
4.277
274777LINCOLN ;8U
Adder
4.277
926823AC1-168 GEN
Solar/Wind Harmer
0.6
972228AH1-698 GEN2
Adder
1.875
972227AH1-698 GEN1
Adder
1.321
970833AG2-524 GEN
Solar/Wind Harmer
3.884
970833AG2-524 GEN
Solar/Wind Harmer
2.589
960591AF2-350 GEN
Solar/Wind Harmer
3.53
274728ELWOOD EC;5P
Adder
8.311
274731ELWOOD EC;2P
Adder
8.311
274733ELWOOD EC;3P
Adder
8.311
274735ELWOOD EC;4P
Adder
8.311
274800UNIV PARK;3U
Adder
2.946
274801UNIV PARK;4U
Adder
2.946
970073AG2-061 GEN
Solar/Wind Harmer
1.175
972037AH1-567 GEN1
Adder
0.092
274827FISK ;RP
Adder
3.918
274675JOLIET 29;7U
Adder
15.488
274675JOLIET 29;7U
Adder
14.935
274687WILL CNTY;4U
Adder
14.106
274687WILL CNTY;4U
Adder
14.106
274877BISHOP HL;1U
Solar/Wind Harmer
0.117
274744AC1-111 GEN8
Adder
2.817
274746AC1-111 G10
Adder
2.817
276861AD2-134 GEN
Solar/Wind Harmer
0.062
276863AD2-134 GEN
Solar/Wind Harmer
0.062
971675AH1-338 GEN
Solar/Wind Harmer
1.363
971411AH1-196 GEN
Solar/Wind Harmer
5.237
971171AH1-044 GEN
Solar/Wind Harmer
6.982
960681AF2-359 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.123
274856ECOGROVE ;U1
Solar/Wind Harmer
0.081
971681AH1-341 GEN
Solar/Wind Harmer
5.605
946321AF1-296 GEN
Solar/Wind Harmer
1.935
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
3.411
970031AG2-029 GEN
Solar/Wind Harmer
1.822
959331AF2-224 GEN
Solar/Wind Harmer
2.262
965041AG1-368 GEN
Solar/Wind Harmer
3.099
247521TR3_G114
Solar/Wind Harmer
0.11
965051AG1-369 GEN
Solar/Wind Harmer
1.514
945631AF1-228 GEN
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
6.245
24803006KYGER 3HP
50/50
4.127
24802806KYGER 2HP
50/50
4.111
24802906KYGER 2LP
50/50
2.413
25183008BIOENL
50/50
0.03
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.768
25194508D.CRK3
Adder
1.452
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972043AH1-570 GEN
Solar/Wind Harmer
1.516
972045AH1-571 GEN
Solar/Wind Harmer
1.214
270269AC2-059
Solar/Wind Harmer
0
971125AH1-004 GEN
Solar/Wind Harmer
2.245
970107AG2-081 GEN
Solar/Wind Harmer
1.684
253370AE2-315 SEC1
Adder
1.601
24728805RICHG1
Adder
2.955
24728905RICHG2
Adder
2.955
25322209TAIT E
Adder
7.522
25322209TAIT E
Adder
7.353
25326109MON D
Adder
0.984
926881AC1-175 GEN
Solar/Wind Harmer
0
942891AE2-308 GEN
Solar/Wind Harmer
5.111
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.905
970885AG2-551 GEN
Solar/Wind Harmer
1.635
247621Y3-024
Adder
0.162
964611AG1-324 GEN
Solar/Wind Harmer
0.348
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
2.485
270599AE1-208 GEN
Solar/Wind Harmer
4.141
971613AH1-306 GEN
Solar/Wind Harmer
2.151
964571AG1-320 GEN
Solar/Wind Harmer
4.079
970291AG2-192 GEN
Solar/Wind Harmer
0.57
970291AG2-192 GEN
Solar/Wind Harmer
0.263
944541AF1-119 GEN
Solar/Wind Harmer
0.292
960971AF2-388 GEN
Solar/Wind Harmer
2.564
942221AE2-234 GEN
Solar/Wind Harmer
1.655
971587AH1-292 GEN
Solar/Wind Harmer
2.993
945391AF1-204 GEN
Solar/Wind Harmer
4.316
970241AG2-163 GEN
Solar/Wind Harmer
2.286
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.434
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
7.7
276911AD2-131_GEN
Solar/Wind Harmer
0.507
276615X2-022 GEN
Solar/Wind Harmer
0.038
276838X2-022 GEN2
Solar/Wind Harmer
0.206
25326509SID D
Adder
0.689
960611AF2-352 GEN
Solar/Wind Harmer
1.21
942111AE2-223 GEN
Solar/Wind Harmer
1.178
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
8.857
274770LINCOLN ;1U
Adder
4.277
274771LINCOLN ;2U
Adder
4.277
276901AD2-066 C O1
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.206
276776AD2-060 GEN
Solar/Wind Harmer
0.377
958011AF2-095 GEN
Solar/Wind Harmer
5.084
970941AG2-585 GEN
Solar/Wind Harmer
1.942
276893AG1-478 C
Solar/Wind Harmer
0.235
274674JOLIET 9 ;6U
Adder
7.779
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
5.287
958491AF2-143 GEN
Solar/Wind Harmer
5.287
276645AC1-214 GEN1
Solar/Wind Harmer
0.138
274805UNIV PK N;1U
Adder
2.533
274808UNIV PK N;4U
Adder
2.517
274696ROCKY RD ;4P
Adder
5.728
274695ROCKY RD ;2P
Adder
5.596
274693ROCKY RD ;1P
Adder
5.541
274697ROCKY RD ;3P
Adder
1.52
962691AG1-118 GEN
Solar/Wind Harmer
10.508
964781AG1-341 GEN
Solar/Wind Harmer
3.705
971341AH1-150 GEN
Solar/Wind Harmer
6.982
971343AH1-151 GEN
Solar/Wind Harmer
6.982
970349AG2-230 GEN
Solar/Wind Harmer
5.234
965681AG1-436 GEN
Solar/Wind Harmer
4.361
965791AG1-447 GEN
Solar/Wind Harmer
3.198
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.562
938861AE1-114 GEN
Solar/Wind Harmer
1.972
970329AG2-216 GEN
Solar/Wind Harmer
1.444
961051AF2-396 GEN
Solar/Wind Harmer
6.65
961051AF2-396 GEN
Solar/Wind Harmer
4.433
971485AH1-239 GEN
Solar/Wind Harmer
2.603
966021AG1-471 GEN
Solar/Wind Harmer
1.739
270246TR4_N_V150
Solar/Wind Harmer
0.019
270247TR4_N_V136
Solar/Wind Harmer
0.019
237033AB1-150 GEN
Solar/Wind Helper
0.401
24803106KYGER 3LP
50/50
2.43
24803306KYGER 4LP
50/50
2.38
971191AH1-055 GEN
Solar/Wind Harmer
68.684
252507AC2-088 GEN
Solar/Wind Harmer
0.357
252519AF1-045_GEN
Solar/Wind Harmer
3.858
25194608D.CRK4
Adder
1.689
25196608WSDLE5
Adder
8.798
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.081
25196008MFTGT1
Adder
1.326
958171AF2-111 GEN
Solar/Wind Harmer
17.024
253394AE2-221_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.127
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
970191AG2-125 GEN
Solar/Wind Harmer
1.385
3429391JKCT 9G
Adder
6.396
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
4.143
270004AE1-209 GEN
Solar/Wind Harmer
1.04
24728705AND G3
Adder
5.496
24728505AND G1
Adder
2.628
946031AF1-268 GEN
Solar/Wind Harmer
4.524
970825AG2-519 GEN
Solar/Wind Harmer
3.571
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.92
970455AG2-298 GEN
Solar/Wind Harmer
1.776
970289AG2-191 GEN
Solar/Wind Harmer
0.483
247642Z2-115 C
Solar/Wind Harmer
0.002
970653AG2-424 GEN
Solar/Wind Harmer
0.428
944531AF1-118 GEN
Solar/Wind Harmer
18.504
253325AC1-069 GEN
Solar/Wind Harmer
0.005
970193AG2-126 GEN
Solar/Wind Harmer
6.094
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.775
270518AE2-148 GEN
Solar/Wind Harmer
0.304
971993AH1-541 GEN
Solar/Wind Harmer
1.694
942481AE2-261 GEN
Solar/Wind Harmer
10.95
957381AF2-032 GEN
Solar/Wind Harmer
0.83
964401AG1-302 GEN
Solar/Wind Harmer
0
972273AH1-721 GEN
Adder
43.369
965091AG1-374 GEN
Solar/Wind Harmer
10.891
959611AF2-252 GEN
Solar/Wind Harmer
1.21
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
4.277
274887GEN-1.85
Solar/Wind Harmer
0.092
276843GEN-1.7
Solar/Wind Harmer
0.114
276806AD2-047 C O1
Solar/Wind Harmer
2.001
972259AH1-714 GEN
Adder
9.653
274729ELWOOD EC;1P
Adder
8.311
274730ELWOOD EC;6P
Adder
8.311
274734ELWOOD EC;8P
Adder
8.311
274736ELWOOD EC;9P
Adder
8.311
970707AG2-453 GEN
Solar/Wind Harmer
11.521
270043AE2-236 GEN
Solar/Wind Harmer
2.263
972038AH1-567 GEN2
Adder
0.184
970571AG2-364 GEN
Solar/Wind Harmer
7.05
274803UNIV PARK;6U
Adder
2.945
276868AE1-113 GEN
Solar/Wind Harmer
0.705
274879MINONK ;1U
Solar/Wind Harmer
0.147
274862TOP CROP ;2U
Solar/Wind Harmer
0.476
274826FISK ;BP
Adder
5.528
274676JOLIET 29;8U
Adder
14.935
274814UNIV PK N;0U
Adder
2.55
274807UNIV PK N;3U
Adder
2.544
274811UNIV PK N;7U
Adder
2.528
274724RIVER EC ;11
Adder
8.935
274752CRETE EC ;2U
Adder
4.155
274753CRETE EC ;3U
Adder
4.155
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.117
943121AE2-341 GEN
Solar/Wind Harmer
5.893
943591AF1-030 GEN
Solar/Wind Harmer
3.919
274682WAUKEGAN ;7U
Adder
5.301
946671AF1-331 GEN
Solar/Wind Harmer
0.373
274855GSG-6 ;RU
Solar/Wind Harmer
0.128
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
959091AF2-200 GEN
Solar/Wind Harmer
6.982
971347AH1-153 GEN
Solar/Wind Harmer
1.745
274857EASY ROAD;U1
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
8.801
971087AG2-675 GEN
Solar/Wind Harmer
1.841
270063AE2-323 C
Solar/Wind Harmer
0
270505AE1-170 C O1
Solar/Wind Harmer
3.511
945111AF1-176 GEN
Solar/Wind Harmer
2.708
965021AG1-366 GEN
Solar/Wind Harmer
1.077
270330AC1-082 GEN2
Solar/Wind Helper
0.194
270329AC1-082 GEN1
Solar/Wind Helper
0.194
24803406KYGER 5HP
50/50
4.083
24803206KYGER 4HP
50/50
4.079
252516AE2-318_GEN
Solar/Wind Harmer
8.283
25196808ZIMRHP
Adder
79.38
25194608D.CRK4
Adder
1.689
252510AF1-249 C
Solar/Wind Harmer
0.054
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.986
25196008MFTGT1
Adder
1.369
253398AE2-221_GEN2
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.031
270273AD2-016 GEN
Solar/Wind Harmer
0.594
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
25326309TAIT D
Adder
0.844
3429421JKCT 10G
Adder
6.396
970773AG2-487 GEN
Solar/Wind Harmer
0.939
3429241JKCT 3G
Adder
8.835
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.76
270005AE1-210 C O1
Solar/Wind Harmer
1.04
24728605AND G2
Adder
2.628
970825AG2-519 GEN
Solar/Wind Harmer
1.683
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
5.07
270594AE1-207 GEN
Solar/Wind Harmer
5.019
270032AE2-172
Solar/Wind Harmer
2.988
958861AF2-177 GEN
Solar/Wind Harmer
1.919
965651AG1-433 GEN
Solar/Wind Harmer
1.282
270024AE2-089 GEN
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
2.063
970091AG2-072 GEN
Adder
45.503
253333AC1-068 GEN
Solar/Wind Harmer
0.005
963741AG1-226 GEN
Solar/Wind Harmer
9.274
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
964901AG1-354 GEN
Solar/Wind Harmer
5.594
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.628
276621W2-048 GEN
Solar/Wind Harmer
0.183
965911AG1-460 GEN
Solar/Wind Harmer
0.732
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.756
958381AF2-132 GEN
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
5.074
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.536
939401AE1-172 GEN
Solar/Wind Harmer
2.672
941551AE2-152 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
4.277
274774LINCOLN ;5U
Adder
4.277
971997AH1-543 GEN
Solar/Wind Harmer
1.853
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.311
274674JOLIET 9 ;6U
Adder
7.779
276694AA1-018 GEN2
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
10.575
274802UNIV PARK;5U
Adder
2.945
276691AA1-018 GEN1
Solar/Wind Harmer
0.573
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.411
276646AC1-214 GEN2
Solar/Wind Harmer
0.138
274848CAMPGROVE;RU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
15.488
274812UNIV PK N;8U
Adder
2.528
274723RIVER EC ;12
Adder
9.04
274751CRETE EC ;1U
Adder
4.155
274754CRETE EC ;4U
Adder
4.155
274745AC1-111 GEN9
Adder
2.817
962781AG1-127 GEN
Solar/Wind Harmer
3.332
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
10.473
959081AF2-199 GEN
Solar/Wind Harmer
3.491
971067AG2-660 GEN
Solar/Wind Harmer
1.164
276708O09 GEN2
Solar/Wind Harmer
0.123
970819AG2-516 GEN
Solar/Wind Harmer
4.177
274858EASY ROAD;U2
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
5.58
945111AF1-176 GEN
Solar/Wind Harmer
5.962
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.73
965011AG1-365 GEN
Solar/Wind Harmer
3.232
960001AF2-291 GEN
Solar/Wind Helper
1.722
270331AC1-082 GEN3
Solar/Wind Helper
0.193
235780M24_1
Solar/Wind Helper
0.496
LAGNLTFEXP_LAGN->PJM
CLTF
6.552
TVALTFEXP_TVA->PJM
CLTF
3.106
NYPJM->LTFIMP_NY
CLTF
1.666
LGEELTFEXP_LGEE->PJM
CLTF
5.14
WECLTFEXP_WEC->PJM
CLTF
1.904
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.044
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.289
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.317
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.627
MECLTFEXP_MEC->PJM
CLTF
8.009
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.393
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 43.37 MW.

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#309_15_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#309_15_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.27 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2052.4
MW Contribution:
35.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.207
24802706KYGER 1LP
50/50
2.467
24803506KYGER 5LP
50/50
2.41
971985AH1-537 GEN
Solar/Wind Harmer
5.9
25196408WSDLE3
Adder
9.526
25196308WSDLE2
Adder
9.443
25196208WSDLE1
Adder
9.419
25196708WSDLE6
Adder
9.395
25196508WSDLE4
Adder
9.159
25196108MFTGT2
Adder
1.576
25196108MFTGT2
Adder
1.463
253406AD2-031_GEN
Solar/Wind Harmer
0.493
972163AH1-664 GEN
Solar/Wind Harmer
7.368
972165AH1-665 GEN
Solar/Wind Harmer
5.901
270263AC1-001 GEN
Solar/Wind Harmer
0.65
270340AC2-060 GEN
Solar/Wind Harmer
0.001
339216AC1-074 GEN
Solar/Wind Harmer
0.169
253372AE2-315 SEC3
Adder
1.623
253372AE2-315 SEC3
Adder
1.623
25306009OHH W.
Adder
2.424
3429211JKCT 2G
Adder
8.956
270356AE2-297 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.299
971029AG2-637 GEN
Solar/Wind Harmer
7.492
241972AD1-140 GEN
Solar/Wind Harmer
0.535
270543AE2-219 C
Solar/Wind Harmer
3.362
247536S-71 GEN
Solar/Wind Harmer
0.185
964611AG1-324 GEN
Solar/Wind Harmer
1.732
971609AH1-304 GEN
Solar/Wind Harmer
0.694
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.79
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
3.463
963841AG1-237 GEN
Solar/Wind Harmer
1.583
945631AF1-228 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.02
963791AG1-232 GEN
Solar/Wind Harmer
4.554
971611AH1-305 GEN
Solar/Wind Harmer
2.005
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.132
276848AB2-070 GEN3
Solar/Wind Harmer
0.132
276849AB2-070 GEN2
Solar/Wind Harmer
0.132
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
1.273
943851AF1-053 GEN
Solar/Wind Harmer
0.882
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.418
270071AF1-092 GEN
Solar/Wind Harmer
6.13
970169AG2-114 GEN
Solar/Wind Harmer
3.185
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.104
926823AC1-168 GEN
Solar/Wind Harmer
0.529
970073AG2-061 GEN
Solar/Wind Harmer
1.026
276741O09 GEN1
Solar/Wind Harmer
0.108
970833AG2-524 GEN
Solar/Wind Harmer
3.368
970833AG2-524 GEN
Solar/Wind Harmer
2.246
274728ELWOOD EC;5P
Adder
7.204
274731ELWOOD EC;2P
Adder
7.204
274733ELWOOD EC;3P
Adder
7.204
274735ELWOOD EC;4P
Adder
7.204
972227AH1-698 GEN1
Adder
1.143
972228AH1-698 GEN2
Adder
1.623
960591AF2-350 GEN
Solar/Wind Harmer
3.054
274675JOLIET 29;7U
Adder
13.407
274675JOLIET 29;7U
Adder
12.928
274687WILL CNTY;4U
Adder
12.208
274687WILL CNTY;4U
Adder
12.208
274800UNIV PARK;3U
Adder
2.547
274801UNIV PARK;4U
Adder
2.547
971681AH1-341 GEN
Solar/Wind Harmer
4.906
274744AC1-111 GEN8
Adder
2.441
274746AC1-111 G10
Adder
2.441
972267AH1-718 GEN
Adder
1.819
972037AH1-567 GEN1
Adder
0.08
276861AD2-134 GEN
Solar/Wind Harmer
0.054
276863AD2-134 GEN
Solar/Wind Harmer
0.054
971171AH1-044 GEN
Solar/Wind Harmer
6.093
971675AH1-338 GEN
Solar/Wind Harmer
1.188
946321AF1-296 GEN
Solar/Wind Harmer
1.706
274827FISK ;RP
Adder
3.386
274856ECOGROVE ;U1
Solar/Wind Harmer
0.071
971411AH1-196 GEN
Solar/Wind Harmer
4.564
24803006KYGER 3HP
50/50
4.179
24802806KYGER 2HP
50/50
4.162
24802906KYGER 2LP
50/50
2.443
25183008BIOENL
50/50
0.032
252509AD1-136 GEN
Solar/Wind Harmer
0.042
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
8.168
25194508D.CRK3
Adder
1.527
270269AC2-059
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972043AH1-570 GEN
Solar/Wind Harmer
1.575
972045AH1-571 GEN
Solar/Wind Harmer
1.262
253370AE2-315 SEC1
Adder
1.716
971125AH1-004 GEN
Solar/Wind Harmer
2.323
970107AG2-081 GEN
Solar/Wind Harmer
1.743
25322209TAIT E
Adder
8.074
25322209TAIT E
Adder
7.893
25326109MON D
Adder
1.062
24728805RICHG1
Adder
2.987
24728905RICHG2
Adder
2.987
942891AE2-308 GEN
Solar/Wind Harmer
5.239
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.803
970885AG2-551 GEN
Solar/Wind Harmer
1.601
247621Y3-024
Adder
0.156
964571AG1-320 GEN
Solar/Wind Harmer
4.114
964611AG1-324 GEN
Solar/Wind Harmer
0.333
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
2.045
270031AE2-169
Solar/Wind Harmer
2.337
270599AE1-208 GEN
Solar/Wind Harmer
3.895
970291AG2-192 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.25
971587AH1-292 GEN
Solar/Wind Harmer
3.03
25326509SID D
Adder
0.755
944541AF1-119 GEN
Solar/Wind Harmer
0.265
960971AF2-388 GEN
Solar/Wind Harmer
2.332
945391AF1-204 GEN
Solar/Wind Harmer
4.175
942221AE2-234 GEN
Solar/Wind Harmer
1.514
970329AG2-216 GEN
Solar/Wind Harmer
1.606
970241AG2-163 GEN
Solar/Wind Harmer
2.168
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.406
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
7.149
276911AD2-131_GEN
Solar/Wind Harmer
0.471
964781AG1-341 GEN
Solar/Wind Harmer
3.596
276615X2-022 GEN
Solar/Wind Harmer
0.035
276838X2-022 GEN2
Solar/Wind Harmer
0.19
942861AE2-305 GEN
Solar/Wind Harmer
2.579
960611AF2-352 GEN
Solar/Wind Harmer
1.092
942111AE2-223 GEN
Solar/Wind Harmer
1.058
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.122
971485AH1-239 GEN
Solar/Wind Harmer
2.492
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.619
966021AG1-471 GEN
Solar/Wind Harmer
1.662
276897AD1-100 C
Solar/Wind Harmer
7.68
958481AF2-142 GEN
Solar/Wind Harmer
4.605
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.494
276893AG1-478 C
Solar/Wind Harmer
0.204
274888KELLY CRK;1U
Solar/Wind Harmer
0.178
276776AD2-060 GEN
Solar/Wind Harmer
0.326
958011AF2-095 GEN
Solar/Wind Harmer
4.397
274674JOLIET 9 ;6U
Adder
6.739
970941AG2-585 GEN
Solar/Wind Harmer
1.679
971341AH1-150 GEN
Solar/Wind Harmer
6.093
971343AH1-151 GEN
Solar/Wind Harmer
6.093
938861AE1-114 GEN
Solar/Wind Harmer
1.726
962691AG1-118 GEN
Solar/Wind Harmer
9.136
24803106KYGER 3LP
50/50
2.46
24803306KYGER 4LP
50/50
2.41
971191AH1-055 GEN
Solar/Wind Harmer
70.432
252507AC2-088 GEN
Solar/Wind Harmer
0.376
252519AF1-045_GEN
Solar/Wind Harmer
4.074
25194608D.CRK4
Adder
1.776
25196608WSDLE5
Adder
9.253
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.717
958171AF2-111 GEN
Solar/Wind Harmer
17.947
25196008MFTGT1
Adder
1.385
253394AE2-221_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.382
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
970191AG2-125 GEN
Solar/Wind Harmer
1.47
3429391JKCT 9G
Adder
6.589
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
4.224
24728705AND G3
Adder
5.404
24728505AND G1
Adder
2.584
253325AC1-069 GEN
Solar/Wind Harmer
0.005
970455AG2-298 GEN
Solar/Wind Harmer
1.797
270004AE1-209 GEN
Solar/Wind Harmer
0.992
946031AF1-268 GEN
Solar/Wind Harmer
4.337
970825AG2-519 GEN
Solar/Wind Harmer
3.419
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.615
970653AG2-424 GEN
Solar/Wind Harmer
0.429
270518AE2-148 GEN
Solar/Wind Harmer
0.348
970289AG2-191 GEN
Solar/Wind Harmer
0.457
247642Z2-115 C
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
5.894
944531AF1-118 GEN
Solar/Wind Harmer
16.286
24386205FR-12G C
Solar/Wind Harmer
0
972273AH1-721 GEN
Adder
42.335
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.495
942481AE2-261 GEN
Solar/Wind Harmer
10.146
957381AF2-032 GEN
Solar/Wind Harmer
0.768
971993AH1-541 GEN
Solar/Wind Harmer
1.554
964401AG1-302 GEN
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
9.828
959611AF2-252 GEN
Solar/Wind Harmer
1.092
274878BISHOP HL;2U
Solar/Wind Harmer
0.104
276782AC1-033 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.202
942051AE2-217 GEN
Solar/Wind Harmer
5.57
276868AE1-113 GEN
Solar/Wind Harmer
0.616
274879MINONK ;1U
Solar/Wind Harmer
0.129
939351AE1-166 GEN
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.415
274729ELWOOD EC;1P
Adder
7.204
274730ELWOOD EC;6P
Adder
7.204
274734ELWOOD EC;8P
Adder
7.204
274736ELWOOD EC;9P
Adder
7.204
274887GEN-1.85
Solar/Wind Harmer
0.079
276843GEN-1.7
Solar/Wind Harmer
0.099
276806AD2-047 C O1
Solar/Wind Harmer
1.73
972259AH1-714 GEN
Adder
8.342
274676JOLIET 29;8U
Adder
12.928
972038AH1-567 GEN2
Adder
0.159
274803UNIV PARK;6U
Adder
2.546
274855GSG-6 ;RU
Solar/Wind Harmer
0.111
274850MENDOTA H;RU
Solar/Wind Harmer
0.035
946671AF1-331 GEN
Solar/Wind Harmer
0.325
959091AF2-200 GEN
Solar/Wind Harmer
6.093
274857EASY ROAD;U1
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
7.765
274760LEE CO EC;1U
Adder
4.061
274767LEE CO EC;8U
Adder
4.013
971087AG2-675 GEN
Solar/Wind Harmer
1.624
274826FISK ;BP
Adder
4.777
943121AE2-341 GEN
Solar/Wind Harmer
5.104
943591AF1-030 GEN
Solar/Wind Harmer
3.394
274682WAUKEGAN ;7U
Adder
7.839
970707AG2-453 GEN
Solar/Wind Harmer
9.937
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270329AC1-082 GEN1
Solar/Wind Helper
0.188
24803406KYGER 5HP
50/50
4.134
24803206KYGER 4HP
50/50
4.13
252516AE2-318_GEN
Solar/Wind Harmer
8.746
25196808ZIMRHP
Adder
83.622
25194608D.CRK4
Adder
1.776
252510AF1-249 C
Solar/Wind Harmer
0.057
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.475
25196008MFTGT1
Adder
1.43
253398AE2-221_GEN2
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.627
270273AD2-016 GEN
Solar/Wind Harmer
0.667
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
25326309TAIT D
Adder
0.906
3429421JKCT 10G
Adder
6.589
3429241JKCT 3G
Adder
9.074
970773AG2-487 GEN
Solar/Wind Harmer
0.935
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.658
24728605AND G2
Adder
2.584
253333AC1-068 GEN
Solar/Wind Harmer
0.005
270005AE1-210 C O1
Solar/Wind Harmer
0.992
970825AG2-519 GEN
Solar/Wind Harmer
1.611
970091AG2-072 GEN
Adder
49.338
276903AD2-071 C
Solar/Wind Harmer
4.853
970653AG2-424 GEN
Solar/Wind Harmer
2.069
270594AE1-207 GEN
Solar/Wind Harmer
4.771
270032AE2-172
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.758
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.166
963741AG1-226 GEN
Solar/Wind Harmer
8.794
972203AH1-686 GEN
Adder
1.223
964901AG1-354 GEN
Solar/Wind Harmer
5.49
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.679
276621W2-048 GEN
Solar/Wind Harmer
0.169
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.21
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.274
958381AF2-132 GEN
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.558
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.636
939401AE1-172 GEN
Solar/Wind Harmer
2.347
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.122
970569AG2-363 GEN
Solar/Wind Harmer
9.303
971997AH1-543 GEN
Solar/Wind Harmer
1.622
276882AE2-255 GEN
Solar/Wind Harmer
0.36
276805AD2-038 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.499
276708O09 GEN2
Solar/Wind Harmer
0.108
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.204
274674JOLIET 9 ;6U
Adder
6.739
274676JOLIET 29;8U
Adder
13.407
274802UNIV PARK;5U
Adder
2.546
274745AC1-111 GEN9
Adder
2.441
957471AF2-041 GEN
Solar/Wind Harmer
9.139
959081AF2-199 GEN
Solar/Wind Harmer
3.046
971067AG2-660 GEN
Solar/Wind Harmer
1.015
274872LEEDK;1U
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.061
274766LEE CO EC;7U
Adder
4.013
962781AG1-127 GEN
Solar/Wind Harmer
2.898
274682WAUKEGAN ;7U
Adder
7.839
274828WAUKEGAN ;BP
Adder
4.817
274822ROCKFORD ;11
Adder
2.437
970819AG2-516 GEN
Solar/Wind Harmer
3.649
960001AF2-291 GEN
Solar/Wind Helper
1.676
270331AC1-082 GEN3
Solar/Wind Helper
0.186
235780M24_1
Solar/Wind Helper
0.501
274764LEE CO EC;5U
Adder
4.07
274765LEE CO EC;6U
Adder
4.07
274762LEE CO EC;3U
Adder
4.061
274763LEE CO EC;4U
Adder
4.023
274696ROCKY RD ;4P
Adder
4.974
274695ROCKY RD ;2P
Adder
4.859
274693ROCKY RD ;1P
Adder
4.811
274697ROCKY RD ;3P
Adder
1.32
274683WAUKEGAN ;8U
Adder
9.19
274683WAUKEGAN ;8U
Adder
7.747
972235AH1-702 GEN1
Adder
1.099
972236AH1-702 GEN2
Adder
0.956
237033AB1-150 GEN
Solar/Wind Helper
0.404
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
TVALTFEXP_TVA->PJM
CLTF
2.665
NYPJM->LTFIMP_NY
CLTF
1.597
LGEELTFEXP_LGEE->PJM
CLTF
5.305
WECLTFEXP_WEC->PJM
CLTF
1.662
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.628
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.274
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.431
MECLTFEXP_MEC->PJM
CLTF
7.137
SIGELTFEXP_SIGE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.865
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 42.34 MW.

Details for 2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:156.95 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:98.88
MW Contribution:
119.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.605
972273AH1-721 GEN
50/50
119.868
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.163
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:155.54 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:97.99
MW Contribution:
119.87
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
119.868

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:195.41 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:123.11
MW Contribution:
108.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
108.32
966021AG1-471 GEN
Solar/Wind Harmer
4.016
971485AH1-239 GEN
Solar/Wind Harmer
5.342
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.066
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.203
LAGNLTFEXP_LAGN->PJM
CLTF
0.305
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.294
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.215
WECLTFEXP_WEC->PJM
CLTF
0.002
VTFLTFEXP_VFT->PJM
CMTX
0.045
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.073
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.565
MECLTFEXP_MEC->PJM
CLTF
0.06
G-007ALTFEXP_G-007A->PJM
CMTX
0.017
CPLELTFEXP_CPLE->PJM
CLTF
0.081
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.134

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:188.75 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:118.91
MW Contribution:
115.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.385
966021AG1-471 GEN
Solar/Wind Harmer
3.717
971485AH1-239 GEN
Solar/Wind Harmer
4.888
972273AH1-721 GEN
50/50
115.385
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.073
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
0.157
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.217
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VTFLTFEXP_VFT->PJM
CMTX
0.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.236
MECLTFEXP_MEC->PJM
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.022
CPLELTFEXP_CPLE->PJM
CLTF
0.061
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.374
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:188.75 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:118.91
MW Contribution:
115.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.385
3429451LAUREL 1G
50/50
0.385
966021AG1-471 GEN
Solar/Wind Harmer
3.717
971485AH1-239 GEN
Solar/Wind Harmer
4.888
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.073
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
0.157
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.217
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VTFLTFEXP_VFT->PJM
CMTX
0.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.236
MECLTFEXP_MEC->PJM
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.022
CPLELTFEXP_CPLE->PJM
CLTF
0.061
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.374
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.64 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:110.66
MW Contribution:
108.32
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
108.32

Details for [AH1-721] 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:171.57 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:108.09
MW Contribution:
115.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
115.385

Details for [AH1-721] 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:171.57 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:108.09
MW Contribution:
115.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
115.385

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:195.24 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:123.0
MW Contribution:
108.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
4.016
971485AH1-239 GEN
Solar/Wind Harmer
5.342
972273AH1-721 GEN
50/50
108.32
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.066
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.203
LAGNLTFEXP_LAGN->PJM
CLTF
0.305
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.294
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.215
WECLTFEXP_WEC->PJM
CLTF
0.002
VTFLTFEXP_VFT->PJM
CMTX
0.045
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.073
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.565
MECLTFEXP_MEC->PJM
CLTF
0.06
G-007ALTFEXP_G-007A->PJM
CMTX
0.017
CPLELTFEXP_CPLE->PJM
CLTF
0.081
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.134

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:188.58 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:118.8
MW Contribution:
115.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.385
3429451LAUREL 1G
50/50
0.385
966021AG1-471 GEN
Solar/Wind Harmer
3.717
971485AH1-239 GEN
Solar/Wind Harmer
4.888
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.073
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
0.157
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.217
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VTFLTFEXP_VFT->PJM
CMTX
0.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.236
MECLTFEXP_MEC->PJM
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.022
CPLELTFEXP_CPLE->PJM
CLTF
0.061
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.374
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:188.56 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:118.79
MW Contribution:
115.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.385
3429451LAUREL 1G
50/50
0.385
966021AG1-471 GEN
Solar/Wind Harmer
3.717
971485AH1-239 GEN
Solar/Wind Harmer
4.888
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.073
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
0.157
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.217
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VTFLTFEXP_VFT->PJM
CMTX
0.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.236
MECLTFEXP_MEC->PJM
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.022
CPLELTFEXP_CPLE->PJM
CLTF
0.061
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.374
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.47 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:110.55
MW Contribution:
108.32
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
108.32

Details for [AH1-721] 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:171.39 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:107.97
MW Contribution:
115.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
115.385

Details for [AH1-721] 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:171.39 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:107.97
MW Contribution:
115.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
115.385

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:217.1 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:165.0
MW Contribution:
86.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
101.945
3429031COOPER2 G
50/50
1.651
966021AG1-471 GEN
Solar/Wind Harmer
2.892
971485AH1-239 GEN
Solar/Wind Harmer
3.978
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.001
LAGNLTFEXP_LAGN->PJM
CLTF
0.444
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.227
TVALTFEXP_TVA->PJM
CLTF
0.317
NYPJM->LTFIMP_NY
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.018
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.951
MECLTFEXP_MEC->PJM
CLTF
0.157
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
0.053
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.169
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 101.94 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:199.45 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:151.58
MW Contribution:
86.37
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
101.945
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 101.94 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:159.85 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:121.49
MW Contribution:
65.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.247
3429031COOPER2 G
50/50
1.26
972273AH1-721 GEN
50/50
77.477
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.035
LAGNLTFEXP_LAGN->PJM
CLTF
0.303
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.155
TVALTFEXP_TVA->PJM
CLTF
0.22
NYPJM->LTFIMP_NY
CLTF
0.011
WECLTFEXP_WEC->PJM
CLTF
0.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.299
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.637
MECLTFEXP_MEC->PJM
CLTF
0.095
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.407
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.48 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:159.47 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:121.2
MW Contribution:
65.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
1.26
972273AH1-721 GEN
50/50
77.477
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.035
LAGNLTFEXP_LAGN->PJM
CLTF
0.303
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.155
TVALTFEXP_TVA->PJM
CLTF
0.22
NYPJM->LTFIMP_NY
CLTF
0.011
WECLTFEXP_WEC->PJM
CLTF
0.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.299
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.637
MECLTFEXP_MEC->PJM
CLTF
0.095
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.407
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.48 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:159.24 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:121.02
MW Contribution:
65.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
1.261
972273AH1-721 GEN
50/50
77.263
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.035
LAGNLTFEXP_LAGN->PJM
CLTF
0.303
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.155
TVALTFEXP_TVA->PJM
CLTF
0.22
NYPJM->LTFIMP_NY
CLTF
0.011
WECLTFEXP_WEC->PJM
CLTF
0.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.3
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.638
MECLTFEXP_MEC->PJM
CLTF
0.096
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.408
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.26 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:153.38 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:116.57
MW Contribution:
65.59
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
77.477
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.48 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:153.38 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:116.57
MW Contribution:
65.59
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
77.477
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.48 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:153.14 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:116.39
MW Contribution:
65.35
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
77.263
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.26 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:217.1 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:165.0
MW Contribution:
86.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
101.945
3429031COOPER2 G
50/50
1.651
966021AG1-471 GEN
Solar/Wind Harmer
2.892
971485AH1-239 GEN
Solar/Wind Harmer
3.978
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.001
LAGNLTFEXP_LAGN->PJM
CLTF
0.444
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.227
TVALTFEXP_TVA->PJM
CLTF
0.317
NYPJM->LTFIMP_NY
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.018
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.951
MECLTFEXP_MEC->PJM
CLTF
0.157
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
0.053
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.169
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 101.94 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:199.45 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:151.58
MW Contribution:
86.37
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
101.945
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 101.94 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:159.85 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:121.49
MW Contribution:
65.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.247
3429031COOPER2 G
50/50
1.26
972273AH1-721 GEN
50/50
77.477
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.035
LAGNLTFEXP_LAGN->PJM
CLTF
0.303
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.155
TVALTFEXP_TVA->PJM
CLTF
0.22
NYPJM->LTFIMP_NY
CLTF
0.011
WECLTFEXP_WEC->PJM
CLTF
0.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.299
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.637
MECLTFEXP_MEC->PJM
CLTF
0.095
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.407
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.48 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:159.47 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:121.2
MW Contribution:
65.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
1.26
972273AH1-721 GEN
50/50
77.477
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.035
LAGNLTFEXP_LAGN->PJM
CLTF
0.303
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.155
TVALTFEXP_TVA->PJM
CLTF
0.22
NYPJM->LTFIMP_NY
CLTF
0.011
WECLTFEXP_WEC->PJM
CLTF
0.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.299
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.637
MECLTFEXP_MEC->PJM
CLTF
0.095
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.407
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.48 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:159.24 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:121.02
MW Contribution:
65.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
1.261
972273AH1-721 GEN
50/50
77.263
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.035
LAGNLTFEXP_LAGN->PJM
CLTF
0.303
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.155
TVALTFEXP_TVA->PJM
CLTF
0.22
NYPJM->LTFIMP_NY
CLTF
0.011
WECLTFEXP_WEC->PJM
CLTF
0.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.3
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.638
MECLTFEXP_MEC->PJM
CLTF
0.096
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.408
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.26 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:153.38 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:116.57
MW Contribution:
65.59
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
77.477
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.48 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:153.38 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:116.57
MW Contribution:
65.59
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
77.477
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.48 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:153.14 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:116.39
MW Contribution:
65.35
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
77.263
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.26 MW.

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:287.41 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:132.21
MW Contribution:
108.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
4.016
971485AH1-239 GEN
Solar/Wind Harmer
5.342
972273AH1-721 GEN
50/50
108.32
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.066
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.203
LAGNLTFEXP_LAGN->PJM
CLTF
0.305
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.294
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.215
WECLTFEXP_WEC->PJM
CLTF
0.002
VTFLTFEXP_VFT->PJM
CMTX
0.045
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.073
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.565
MECLTFEXP_MEC->PJM
CLTF
0.06
G-007ALTFEXP_G-007A->PJM
CMTX
0.017
CPLELTFEXP_CPLE->PJM
CLTF
0.081
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.134

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:277.36 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:127.58
MW Contribution:
115.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.385
3429451LAUREL 1G
50/50
0.385
966021AG1-471 GEN
Solar/Wind Harmer
3.717
971485AH1-239 GEN
Solar/Wind Harmer
4.888
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.073
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
0.157
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.217
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VTFLTFEXP_VFT->PJM
CMTX
0.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.236
MECLTFEXP_MEC->PJM
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.022
CPLELTFEXP_CPLE->PJM
CLTF
0.061
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.374
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:277.36 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:127.58
MW Contribution:
115.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.385
3429451LAUREL 1G
50/50
0.385
966021AG1-471 GEN
Solar/Wind Harmer
3.717
971485AH1-239 GEN
Solar/Wind Harmer
4.888
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.073
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
0.157
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.217
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VTFLTFEXP_VFT->PJM
CMTX
0.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.236
MECLTFEXP_MEC->PJM
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.022
CPLELTFEXP_CPLE->PJM
CLTF
0.061
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.374
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:260.36 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:119.76
MW Contribution:
108.32
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
108.32

Details for [AH1-721] 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:253.83 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:116.76
MW Contribution:
115.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
115.385

Details for [AH1-721] 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:253.83 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:116.76
MW Contribution:
115.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
115.385

Details for 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:139.3 %
Rating:66.0 MVA
Rating Type:B
MVA to Mitigate:91.94
MW Contribution:
88.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
88.406
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.014
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.075
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LGEELTFEXP_LGEE->PJM
CLTF
0.006
VTFLTFEXP_VFT->PJM
CMTX
0.004
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.033
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.048
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.41
G-007ALTFEXP_G-007A->PJM
CMTX
0.001
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.01
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.29 %
Rating:66.0 MVA
Rating Type:B
MVA to Mitigate:91.93
MW Contribution:
88.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
88.406
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.014
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.075
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LGEELTFEXP_LGEE->PJM
CLTF
0.006
VTFLTFEXP_VFT->PJM
CMTX
0.004
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.033
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.048
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.41
G-007ALTFEXP_G-007A->PJM
CMTX
0.001
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.01
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:66.0 MVA
Rating Type:B
MVA to Mitigate:91.34
MW Contribution:
88.41
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
88.406

Details for [AH1-721] 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:66.0 MVA
Rating Type:B
MVA to Mitigate:91.34
MW Contribution:
88.41
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
88.406

Details for 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.02 %
Rating:66.0 MVA
Rating Type:B
MVA to Mitigate:89.11
MW Contribution:
91.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
91.641
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.014
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.078
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LGEELTFEXP_LGEE->PJM
CLTF
0.014
VTFLTFEXP_VFT->PJM
CMTX
0.005
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.059
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.499
G-007ALTFEXP_G-007A->PJM
CMTX
0.002
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.013
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.95 %
Rating:66.0 MVA
Rating Type:B
MVA to Mitigate:88.41
MW Contribution:
91.64
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
91.641

Details for 2DENNY-2WIBORG T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.12 %
Rating:66.0 MVA
Rating Type:B
MVA to Mitigate:84.56
MW Contribution:
79.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
79.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.087
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.052
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.076
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.154
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2DENNY-2WIBORG T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.1 %
Rating:66.0 MVA
Rating Type:B
MVA to Mitigate:84.55
MW Contribution:
79.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
79.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.087
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.052
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.076
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.154
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2DENNY-2WIBORG T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.54 %
Rating:66.0 MVA
Rating Type:B
MVA to Mitigate:84.18
MW Contribution:
79.02
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
79.021

Details for [AH1-721] 2DENNY-2WIBORG T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:127.54 %
Rating:66.0 MVA
Rating Type:B
MVA to Mitigate:84.18
MW Contribution:
79.02
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
79.021

Details for 2DENNY-2WIBORG T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.79 %
Rating:66.0 MVA
Rating Type:B
MVA to Mitigate:83.68
MW Contribution:
81.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
81.043
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.088
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.055
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.08
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.199
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2DENNY-2WIBORG T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.15 %
Rating:66.0 MVA
Rating Type:B
MVA to Mitigate:83.26
MW Contribution:
81.04
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
81.043

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.95 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:139.6
MW Contribution:
101.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.38
339231AF1-038_GEN
Solar/Wind Helper
1.495
339236AF1-050_GEN
Solar/Wind Helper
0.506
339241AF1-083 GEN
Solar/Wind Helper
0.51
3429031COOPER2 G
50/50
1.663
972273AH1-721 GEN
50/50
101.638
339206AE1-143 GEN
Solar/Wind Helper
1.637
339255AE2-071 GEN
Solar/Wind Helper
0.228
339250AF1-203 GEN
Solar/Wind Helper
0.176
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.114
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.459
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.165
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.046
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.067
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.259
G-007ALTFEXP_G-007A->PJM
CMTX
0.061
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.126
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.56 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:130.79
MW Contribution:
101.64
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
101.638

Details for 2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.23 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:42.99
MW Contribution:
12.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
Adder
14.338
339236AF1-050_GEN
Solar/Wind Harmer
1.037
964781AG1-341 GEN
Solar/Wind Harmer
2.583
339241AF1-083 GEN
Solar/Wind Harmer
0.958
964901AG1-354 GEN
Solar/Wind Harmer
7.982
950011AG9-010
External Queue
3.174992084503174
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.154
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.54
LAGNLTFEXP_LAGN->PJM
CLTF
0.355
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.354
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.267
VTFLTFEXP_VFT->PJM
CMTX
0.065
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.66
MECLTFEXP_MEC->PJM
CLTF
0.025
G-007ALTFEXP_G-007A->PJM
CMTX
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.099
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.032
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.892
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 14.34 MW.

Details for 2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line l/o EKPC_P2-2_SUMMSHADE 161 #2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_SUMMSHADE 161 #2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.29 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:41.84
MW Contribution:
9.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339206AE1-143 GEN
Solar/Wind Harmer
1.191
972273AH1-721 GEN
Adder
9.248
339236AF1-050_GEN
Solar/Wind Harmer
2.152
964901AG1-354 GEN
Solar/Wind Harmer
17.798
339241AF1-083 GEN
Solar/Wind Harmer
1.578
950011AG9-010
External Queue
5.105432987213135
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.139
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.503
LAGNLTFEXP_LAGN->PJM
CLTF
0.112
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.184
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.101
VTFLTFEXP_VFT->PJM
CMTX
0.031
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.118
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.186
G-007ALTFEXP_G-007A->PJM
CMTX
0.012
CPLELTFEXP_CPLE->PJM
CLTF
0.052
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.012
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line l/o EKPC_P2-3_SSHAD S11-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_SSHAD S11-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.26 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:41.83
MW Contribution:
9.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339206AE1-143 GEN
Solar/Wind Harmer
1.191
972273AH1-721 GEN
Adder
9.248
339236AF1-050_GEN
Solar/Wind Harmer
2.152
964901AG1-354 GEN
Solar/Wind Harmer
17.798
339241AF1-083 GEN
Solar/Wind Harmer
1.578
950011AG9-010
External Queue
5.105432987213135
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.139
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.503
LAGNLTFEXP_LAGN->PJM
CLTF
0.112
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.184
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.101
VTFLTFEXP_VFT->PJM
CMTX
0.031
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.118
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.186
G-007ALTFEXP_G-007A->PJM
CMTX
0.012
CPLELTFEXP_CPLE->PJM
CLTF
0.052
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.012
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-2_SSHAD S11-1004_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-2_SSHAD S11-1004_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.26 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:41.83
MW Contribution:
9.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
964901AG1-354 GEN
Solar/Wind Harmer
17.798
339241AF1-083 GEN
Solar/Wind Harmer
1.578
339206AE1-143 GEN
Solar/Wind Harmer
1.191
972273AH1-721 GEN
Adder
9.248
339236AF1-050_GEN
Solar/Wind Harmer
2.152
950011AG9-010
External Queue
5.105432987213135
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.139
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.503
LAGNLTFEXP_LAGN->PJM
CLTF
0.112
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.184
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.101
VTFLTFEXP_VFT->PJM
CMTX
0.031
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.118
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.186
G-007ALTFEXP_G-007A->PJM
CMTX
0.012
CPLELTFEXP_CPLE->PJM
CLTF
0.052
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.012
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:175.99 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:110.88
MW Contribution:
119.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.605
972273AH1-721 GEN
50/50
119.868
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.163
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:174.58 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:109.99
MW Contribution:
119.87
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
119.868

Details for [AH1-721] 2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.17 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:63.11
MW Contribution:
71.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.393

Details for [AH1-721] 2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.01 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:63.01
MW Contribution:
71.55
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.549

Details for [AH1-721] 2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.01 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:63.01
MW Contribution:
71.55
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.549

Details for 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:150.15 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:157.66
MW Contribution:
138.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.696
972273AH1-721 GEN
50/50
138.067
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.016
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.034
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.143
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:149.25 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:156.71
MW Contribution:
138.07
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
138.067

Details for 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.6 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:110.88
MW Contribution:
83.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
83.81
3429451LAUREL 1G
50/50
0.513
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.017
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.035
SIGELTFEXP_SIGE->PJM
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.38 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:110.65
MW Contribution:
83.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
83.815
3429451LAUREL 1G
50/50
0.513
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.017
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.036
SIGELTFEXP_SIGE->PJM
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.38 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:110.65
MW Contribution:
83.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
83.815
3429451LAUREL 1G
50/50
0.513
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.017
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.036
SIGELTFEXP_SIGE->PJM
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:110.02
MW Contribution:
83.81
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
83.81

Details for [AH1-721] 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.5 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:109.72
MW Contribution:
83.81
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
83.815

Details for [AH1-721] 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.5 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:109.72
MW Contribution:
83.81
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
83.815

Details for 2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:191.94 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:120.92
MW Contribution:
119.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.605
972273AH1-721 GEN
50/50
119.868
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.019
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.038
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.163
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:190.53 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:120.04
MW Contribution:
119.87
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
119.868

Details for 2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.73 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:79.84
MW Contribution:
67.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
Adder
67.427
3429451LAUREL 1G
50/50
0.441
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.02
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.028
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.041
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.068
SIGELTFEXP_SIGE->PJM
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.73 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:79.84
MW Contribution:
67.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
Adder
67.427
3429451LAUREL 1G
50/50
0.441
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.02
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.028
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.041
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.068
SIGELTFEXP_SIGE->PJM
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.61 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:79.76
MW Contribution:
67.28
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
Adder
67.28
3429451LAUREL 1G
50/50
0.441
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.02
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.028
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.041
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.066
SIGELTFEXP_SIGE->PJM
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.46 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:71.48
MW Contribution:
71.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.393

Details for [AH1-721] 2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.23 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:71.33
MW Contribution:
71.55
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.549

Details for [AH1-721] 2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.23 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:71.33
MW Contribution:
71.55
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.549

Details for 2LIBER CH T-2FARLEY KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LIBER CH T-2FARLEY KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:124.36 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:94.51
MW Contribution:
119.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.605
972273AH1-721 GEN
50/50
119.868
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.163
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2LIBER CH T-2FARLEY KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LIBER CH T-2FARLEY KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:123.19 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:93.62
MW Contribution:
119.87
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
119.868

Details for 2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:162.76 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:102.54
MW Contribution:
119.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.605
972273AH1-721 GEN
50/50
119.868
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.163
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:161.35 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:101.65
MW Contribution:
119.87
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
119.868

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:304.78 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:320.02
MW Contribution:
172.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
3.299
972273AH1-721 GEN
50/50
203.521
339206AE1-143 GEN
Solar/Wind Harmer
1.795
339255AE2-071 GEN
Solar/Wind Harmer
0.905
339250AF1-203 GEN
Solar/Wind Harmer
0.466
339231AF1-038_GEN
Solar/Wind Harmer
3.633
966021AG1-471 GEN
Solar/Wind Harmer
6.628
971485AH1-239 GEN
Solar/Wind Harmer
9.416
339236AF1-050_GEN
Solar/Wind Harmer
1.284
964781AG1-341 GEN
Solar/Wind Harmer
7.2
339241AF1-083 GEN
Solar/Wind Harmer
1.258
964901AG1-354 GEN
Solar/Wind Harmer
10.565
950011AG9-010
External Queue
7.339239120483398
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.42
TVALTFEXP_TVA->PJM
CLTF
0.87
NYPJM->LTFIMP_NY
CLTF
0.043
WECLTFEXP_WEC->PJM
CLTF
0.065
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.156
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.676
MECLTFEXP_MEC->PJM
CLTF
0.492
SIGELTFEXP_SIGE->PJM
CLTF
0.018
CPLELTFEXP_CPLE->PJM
CLTF
0.083
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.312
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 203.52 MW.

Details for [AH1-721] 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:239.94 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:251.94
MW Contribution:
172.4
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
203.521
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 203.52 MW.

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:224.7 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:235.93
MW Contribution:
129.5
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339241AF1-083 GEN
Solar/Wind Harmer
1.018
964901AG1-354 GEN
Solar/Wind Harmer
8.574
3429031COOPER2 G
50/50
2.491
972273AH1-721 GEN
50/50
153.021
339206AE1-143 GEN
Solar/Wind Harmer
1.449
339255AE2-071 GEN
Solar/Wind Harmer
0.748
339250AF1-203 GEN
Solar/Wind Harmer
0.385
3429451LAUREL 1G
50/50
0.475
339231AF1-038_GEN
Solar/Wind Harmer
3.215
966021AG1-471 GEN
Solar/Wind Harmer
5.438
971485AH1-239 GEN
Solar/Wind Harmer
7.73
339236AF1-050_GEN
Solar/Wind Harmer
1.042
964781AG1-341 GEN
Solar/Wind Harmer
5.858
950011AG9-010
External Queue
5.9790191650390625
LAGNLTFEXP_LAGN->PJM
CLTF
0.921
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.271
TVALTFEXP_TVA->PJM
CLTF
0.67
NYPJM->LTFIMP_NY
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.047
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.552
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.027
MECLTFEXP_MEC->PJM
CLTF
0.366
SIGELTFEXP_SIGE->PJM
CLTF
0.013
CPLELTFEXP_CPLE->PJM
CLTF
0.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.739
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 153.02 MW.

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:224.32 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:235.53
MW Contribution:
128.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
2.495
972273AH1-721 GEN
50/50
152.481
339206AE1-143 GEN
Solar/Wind Harmer
1.45
339255AE2-071 GEN
Solar/Wind Harmer
0.749
339250AF1-203 GEN
Solar/Wind Harmer
0.386
3429451LAUREL 1G
50/50
0.473
339231AF1-038_GEN
Solar/Wind Harmer
3.216
966021AG1-471 GEN
Solar/Wind Harmer
5.437
971485AH1-239 GEN
Solar/Wind Harmer
7.729
339236AF1-050_GEN
Solar/Wind Harmer
1.042
964781AG1-341 GEN
Solar/Wind Harmer
5.862
339241AF1-083 GEN
Solar/Wind Harmer
1.019
964901AG1-354 GEN
Solar/Wind Harmer
8.581
950011AG9-010
External Queue
5.9849534034729
LAGNLTFEXP_LAGN->PJM
CLTF
0.921
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.271
TVALTFEXP_TVA->PJM
CLTF
0.67
NYPJM->LTFIMP_NY
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.047
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.029
MECLTFEXP_MEC->PJM
CLTF
0.367
SIGELTFEXP_SIGE->PJM
CLTF
0.013
CPLELTFEXP_CPLE->PJM
CLTF
0.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.743
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 152.48 MW.

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:209.2 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:219.66
MW Contribution:
129.5
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.475
966021AG1-471 GEN
Solar/Wind Harmer
3.794
971485AH1-239 GEN
Solar/Wind Harmer
5.393
964781AG1-341 GEN
Solar/Wind Harmer
4.087
964901AG1-354 GEN
Solar/Wind Harmer
5.982
3429031COOPER2 G
50/50
2.491
972273AH1-721 GEN
50/50
153.021
950011AG9-010
External Queue
5.9790191650390625
LAGNLTFEXP_LAGN->PJM
CLTF
0.921
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.271
TVALTFEXP_TVA->PJM
CLTF
0.67
NYPJM->LTFIMP_NY
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.047
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.552
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.027
MECLTFEXP_MEC->PJM
CLTF
0.366
SIGELTFEXP_SIGE->PJM
CLTF
0.013
CPLELTFEXP_CPLE->PJM
CLTF
0.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.739
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 153.02 MW.

Details for [AH1-721] 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.79 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:180.38
MW Contribution:
129.5
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
153.021
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 153.02 MW.

Details for [AH1-721] 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:171.79 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:180.38
MW Contribution:
129.5
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
153.021
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 153.02 MW.

Details for [AH1-721] 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:171.38 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:179.95
MW Contribution:
128.92
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
152.481
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 152.48 MW.

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:206.75 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:314.25
MW Contribution:
176.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
3.373
972273AH1-721 GEN
50/50
208.136
339206AE1-143 GEN
Solar/Wind Harmer
1.745
339255AE2-071 GEN
Solar/Wind Harmer
0.713
339250AF1-203 GEN
Solar/Wind Harmer
0.367
339231AF1-038_GEN
Solar/Wind Harmer
2.641
966021AG1-471 GEN
Solar/Wind Harmer
5.827
971485AH1-239 GEN
Solar/Wind Harmer
8.211
339236AF1-050_GEN
Solar/Wind Harmer
1.109
964781AG1-341 GEN
Solar/Wind Harmer
5.665
339241AF1-083 GEN
Solar/Wind Harmer
1.166
964901AG1-354 GEN
Solar/Wind Harmer
9.029
950011AG9-010
External Queue
7.104459285736084
LAGNLTFEXP_LAGN->PJM
CLTF
0.92
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.248
TVALTFEXP_TVA->PJM
CLTF
0.659
NYPJM->LTFIMP_NY
CLTF
0.041
LGEELTFEXP_LGEE->PJM
CLTF
0.015
WECLTFEXP_WEC->PJM
CLTF
0.051
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.686
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.043
MECLTFEXP_MEC->PJM
CLTF
0.384
SIGELTFEXP_SIGE->PJM
CLTF
0.015
CPLELTFEXP_CPLE->PJM
CLTF
0.039
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.878
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 208.14 MW.

Details for [AH1-721] 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:168.71 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:256.43
MW Contribution:
176.31
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
208.136
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 208.14 MW.

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:148.66 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:225.97
MW Contribution:
133.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339241AF1-083 GEN
Solar/Wind Harmer
0.926
964901AG1-354 GEN
Solar/Wind Harmer
7.044
3429031COOPER2 G
50/50
2.568
972273AH1-721 GEN
50/50
157.799
339206AE1-143 GEN
Solar/Wind Harmer
1.4
339255AE2-071 GEN
Solar/Wind Harmer
0.556
339250AF1-203 GEN
Solar/Wind Harmer
0.286
3429451LAUREL 1G
50/50
0.5
339231AF1-038_GEN
Solar/Wind Harmer
2.224
966021AG1-471 GEN
Solar/Wind Harmer
4.64
971485AH1-239 GEN
Solar/Wind Harmer
6.53
339236AF1-050_GEN
Solar/Wind Harmer
0.867
950011AG9-010
External Queue
5.748615264892578
LAGNLTFEXP_LAGN->PJM
CLTF
0.628
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.099
TVALTFEXP_TVA->PJM
CLTF
0.459
NYPJM->LTFIMP_NY
CLTF
0.036
WECLTFEXP_WEC->PJM
CLTF
0.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.396
MECLTFEXP_MEC->PJM
CLTF
0.258
SIGELTFEXP_SIGE->PJM
CLTF
0.01
CPLELTFEXP_CPLE->PJM
CLTF
0.003
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.31
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 157.8 MW.

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:148.4 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:225.56
MW Contribution:
132.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
2.572
972273AH1-721 GEN
50/50
157.266
339206AE1-143 GEN
Solar/Wind Harmer
1.401
339255AE2-071 GEN
Solar/Wind Harmer
0.556
339250AF1-203 GEN
Solar/Wind Harmer
0.286
3429451LAUREL 1G
50/50
0.498
339231AF1-038_GEN
Solar/Wind Harmer
2.226
966021AG1-471 GEN
Solar/Wind Harmer
4.639
971485AH1-239 GEN
Solar/Wind Harmer
6.529
339236AF1-050_GEN
Solar/Wind Harmer
0.868
339241AF1-083 GEN
Solar/Wind Harmer
0.927
964901AG1-354 GEN
Solar/Wind Harmer
7.052
950011AG9-010
External Queue
5.7544779777526855
LAGNLTFEXP_LAGN->PJM
CLTF
0.629
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.099
TVALTFEXP_TVA->PJM
CLTF
0.459
NYPJM->LTFIMP_NY
CLTF
0.036
WECLTFEXP_WEC->PJM
CLTF
0.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.085
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.398
MECLTFEXP_MEC->PJM
CLTF
0.258
SIGELTFEXP_SIGE->PJM
CLTF
0.01
CPLELTFEXP_CPLE->PJM
CLTF
0.003
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.314
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 157.27 MW.

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.88 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:214.14
MW Contribution:
133.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
2.568
972273AH1-721 GEN
50/50
157.799
964901AG1-354 GEN
Solar/Wind Harmer
4.915
3429451LAUREL 1G
50/50
0.5
966021AG1-471 GEN
Solar/Wind Harmer
3.237
971485AH1-239 GEN
Solar/Wind Harmer
4.556
950011AG9-010
External Queue
5.748615264892578
LAGNLTFEXP_LAGN->PJM
CLTF
0.628
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.099
TVALTFEXP_TVA->PJM
CLTF
0.459
NYPJM->LTFIMP_NY
CLTF
0.036
WECLTFEXP_WEC->PJM
CLTF
0.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.396
MECLTFEXP_MEC->PJM
CLTF
0.258
SIGELTFEXP_SIGE->PJM
CLTF
0.01
CPLELTFEXP_CPLE->PJM
CLTF
0.003
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.31
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 157.8 MW.

Details for [AH1-721] 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.66 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:184.92
MW Contribution:
133.55
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
157.799
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 157.8 MW.

Details for [AH1-721] 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.66 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:184.92
MW Contribution:
133.55
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
157.799
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 157.8 MW.

Details for [AH1-721] 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:121.37 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:184.48
MW Contribution:
132.98
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
157.266
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 157.27 MW.

Details for 2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.73 %
Rating:50.0 MVA
Rating Type:B
MVA to Mitigate:60.36
MW Contribution:
17.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339241AF1-083 GEN
Solar/Wind Harmer
1.02
964901AG1-354 GEN
Solar/Wind Harmer
5.66
339206AE1-143 GEN
Solar/Wind Harmer
1.512
972273AH1-721 GEN
Adder
20.084
950011AG9-010
External Queue
10.66642951965332
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.149
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.501
LAGNLTFEXP_LAGN->PJM
CLTF
0.388
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.352
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.277
VTFLTFEXP_VFT->PJM
CMTX
0.029
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.699
MECLTFEXP_MEC->PJM
CLTF
0.068
G-007ALTFEXP_G-007A->PJM
CMTX
0.011
CPLELTFEXP_CPLE->PJM
CLTF
0.097
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.004
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.406
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 20.08 MW.

Details for 2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.77 %
Rating:50.0 MVA
Rating Type:B
MVA to Mitigate:53.89
MW Contribution:
15.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339206AE1-143 GEN
Solar/Wind Harmer
1.482
972273AH1-721 GEN
Adder
15.947
339241AF1-083 GEN
Solar/Wind Harmer
0.999
964901AG1-354 GEN
Solar/Wind Harmer
5.49
950011AG9-010
External Queue
10.550325393676758
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.152
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.513
LAGNLTFEXP_LAGN->PJM
CLTF
0.363
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.339
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.26
VTFLTFEXP_VFT->PJM
CMTX
0.034
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.643
MECLTFEXP_MEC->PJM
CLTF
0.057
G-007ALTFEXP_G-007A->PJM
CMTX
0.013
CPLELTFEXP_CPLE->PJM
CLTF
0.094
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.008
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.272

Details for 2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line l/o EKPC_P2-3_SSHAD S11-1044_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_SSHAD S11-1044_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.27 %
Rating:50.0 MVA
Rating Type:B
MVA to Mitigate:53.14
MW Contribution:
11.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339206AE1-143 GEN
Solar/Wind Harmer
1.777
972273AH1-721 GEN
Adder
11.792
339236AF1-050_GEN
Solar/Wind Harmer
1.446
339241AF1-083 GEN
Solar/Wind Harmer
1.404
964901AG1-354 GEN
Solar/Wind Harmer
11.955
950011AG9-010
External Queue
11.82680606842041
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.156
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.544
LAGNLTFEXP_LAGN->PJM
CLTF
0.237
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.259
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.173
VTFLTFEXP_VFT->PJM
CMTX
0.023
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.39
MECLTFEXP_MEC->PJM
CLTF
0.013
G-007ALTFEXP_G-007A->PJM
CMTX
0.009
CPLELTFEXP_CPLE->PJM
CLTF
0.072
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.003
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.694

Details for [AH1-721] 2W LONDON-2W LONDON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2W LONDON-2W LONDON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:119.43 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:54.94
MW Contribution:
49.38
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
49.38

Details for 2W LONDON-2W LONDON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2W LONDON-2W LONDON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.94 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:53.33
MW Contribution:
46.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
Adder
46.536
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.063
LAGNLTFEXP_LAGN->PJM
CLTF
0.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.131
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.064
VTFLTFEXP_VFT->PJM
CMTX
0.031
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.163
MECLTFEXP_MEC->PJM
CLTF
0.012
G-007ALTFEXP_G-007A->PJM
CMTX
0.012
CPLELTFEXP_CPLE->PJM
CLTF
0.037
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.016
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.326

Details for 2WALNUT GROV-2MARETBURG T 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2WALNUT GROV-2MARETBURG T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.22 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:66.29
MW Contribution:
32.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
Adder
38.581
LAGNLTFEXP_LAGN->PJM
CLTF
0.433
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.366
TVALTFEXP_TVA->PJM
CLTF
0.294
NYPJM->LTFIMP_NY
CLTF
0.002
WECLTFEXP_WEC->PJM
CLTF
0.014
VTFLTFEXP_VFT->PJM
CMTX
0.001
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.466
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.89
MECLTFEXP_MEC->PJM
CLTF
0.137
SIGELTFEXP_SIGE->PJM
CLTF
0.005
G-007ALTFEXP_G-007A->PJM
CMTX
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.099
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.04
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 38.58 MW.

Details for 4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o 34541 34553_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DEO&K/EKPC
Facility Description:
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line
Contingency Name:
34541 34553_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.34 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:293.48
MW Contribution:
28.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339216AC1-074 GEN
Solar/Wind Harmer
2.32
972163AH1-664 GEN
Solar/Wind Harmer
9.179
972165AH1-665 GEN
Solar/Wind Harmer
7.343
3429211JKCT 2G
Adder
7.531
3429631SPURLK3G
50/50
1.637
339243AC2-075 GEN1
Solar/Wind Harmer
0.628
972167AH1-666 GEN
Solar/Wind Harmer
7.475
958171AF2-111 GEN
Solar/Wind Harmer
22.606
3429391JKCT 9G
Adder
5.48
970093AG2-073 GEN
Solar/Wind Harmer
3.125
972273AH1-721 GEN
Adder
28.699
3429601SPURLK2G
50/50
3.119
972043AH1-570 GEN
Solar/Wind Harmer
2.368
972045AH1-571 GEN
Solar/Wind Harmer
1.895
971125AH1-004 GEN
Solar/Wind Harmer
3.354
970107AG2-081 GEN
Solar/Wind Harmer
2.516
942891AE2-308 GEN
Solar/Wind Harmer
6.384
3429571SPURLK1G
50/50
1.977
3429661SPURLK4G
50/50
1.637
339221AD2-048_GEN
Solar/Wind Harmer
1.665
945681AF1-233 GEN
Solar/Wind Harmer
17.523
943111AE2-339 GEN
Solar/Wind Harmer
0.697
3429421JKCT 10G
Adder
5.48
3429241JKCT 3G
Adder
7.63
339211AE2-254 GEN
Solar/Wind Harmer
0.72
950041AG9-017
External Queue
4.585055828094482
LAGNLTFEXP_LAGN->PJM
CLTF
1.667
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.501
TVALTFEXP_TVA->PJM
CLTF
1.037
NYPJM->LTFIMP_NY
CLTF
0.076
LGEELTFEXP_LGEE->PJM
CLTF
1.886
WECLTFEXP_WEC->PJM
CLTF
0.057
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.261
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.052
MECLTFEXP_MEC->PJM
CLTF
0.592
SIGELTFEXP_SIGE->PJM
CLTF
0.063
CPLELTFEXP_CPLE->PJM
CLTF
0.394
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.767

Details for 4MARION CO-4LEBANON 138.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
4MARION CO-4LEBANON 138.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.8 %
Rating:220.0 MVA
Rating Type:B
MVA to Mitigate:234.95
MW Contribution:
92.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339236AF1-050_GEN
Solar/Wind Harmer
2.932
339231AF1-038_GEN
Solar/Wind Harmer
1.786
971485AH1-239 GEN
Solar/Wind Harmer
5.85
966021AG1-471 GEN
Solar/Wind Harmer
3.94
3429031COOPER2 G
50/50
1.767
972273AH1-721 GEN
50/50
108.965
339206AE1-143 GEN
Solar/Wind Harmer
8.636
339255AE2-071 GEN
Solar/Wind Harmer
0.855
339250AF1-203 GEN
Solar/Wind Harmer
0.44
970653AG2-424 GEN
Solar/Wind Harmer
0.404
964781AG1-341 GEN
Solar/Wind Harmer
7.499
339241AF1-083 GEN
Solar/Wind Harmer
4.334
964901AG1-354 GEN
Solar/Wind Harmer
22.606
970653AG2-424 GEN
Solar/Wind Harmer
2.794
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.292
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.886
LAGNLTFEXP_LAGN->PJM
CLTF
1.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.121
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.892
NYPJM->LTFIMP_NY
CLTF
0.008
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.251
MECLTFEXP_MEC->PJM
CLTF
0.173
CPLELTFEXP_CPLE->PJM
CLTF
0.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.988
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 108.97 MW.

Details for 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:203.25 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:308.94
MW Contribution:
169.18
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
3.25
972273AH1-721 GEN
50/50
199.87
339206AE1-143 GEN
Solar/Wind Harmer
1.07
LAGNLTFEXP_LAGN->PJM
CLTF
0.571
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.185
TVALTFEXP_TVA->PJM
CLTF
0.416
NYPJM->LTFIMP_NY
CLTF
0.029
LGEELTFEXP_LGEE->PJM
CLTF
0.005
WECLTFEXP_WEC->PJM
CLTF
0.028
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.896
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.285
MECLTFEXP_MEC->PJM
CLTF
0.224
SIGELTFEXP_SIGE->PJM
CLTF
0.009
CPLELTFEXP_CPLE->PJM
CLTF
0.033
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.979
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 199.87 MW.

Details for [AH1-721] 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:196.07 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:298.03
MW Contribution:
169.18
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
199.87
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 199.87 MW.

Details for 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:156.92 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:238.52
MW Contribution:
128.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.491
3429031COOPER2 G
50/50
2.493
972273AH1-721 GEN
50/50
152.539
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.297
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.045
TVALTFEXP_TVA->PJM
CLTF
0.228
NYPJM->LTFIMP_NY
CLTF
0.024
WECLTFEXP_WEC->PJM
CLTF
0.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.329
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.677
MECLTFEXP_MEC->PJM
CLTF
0.106
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.504
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 152.54 MW.

Details for 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:156.92 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:238.52
MW Contribution:
128.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
2.493
972273AH1-721 GEN
50/50
152.539
3429451LAUREL 1G
50/50
0.491
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.297
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.045
TVALTFEXP_TVA->PJM
CLTF
0.228
NYPJM->LTFIMP_NY
CLTF
0.024
WECLTFEXP_WEC->PJM
CLTF
0.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.329
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.677
MECLTFEXP_MEC->PJM
CLTF
0.106
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.504
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 152.54 MW.

Details for 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:156.35 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:237.66
MW Contribution:
127.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
2.5
972273AH1-721 GEN
50/50
151.534
3429451LAUREL 1G
50/50
0.488
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.003
LAGNLTFEXP_LAGN->PJM
CLTF
0.299
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.045
TVALTFEXP_TVA->PJM
CLTF
0.229
NYPJM->LTFIMP_NY
CLTF
0.024
WECLTFEXP_WEC->PJM
CLTF
0.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.332
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.68
MECLTFEXP_MEC->PJM
CLTF
0.107
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.512
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 151.53 MW.

Details for [AH1-721] 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:152.62 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:231.98
MW Contribution:
128.98
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
152.539
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 152.54 MW.

Details for [AH1-721] 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:152.62 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:231.98
MW Contribution:
128.98
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
152.539
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 152.54 MW.

Details for [AH1-721] 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:152.04 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:231.1
MW Contribution:
127.9
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
151.534
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 151.53 MW.

Details for 5COOPER1-5PULASK CO J 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-5PULASK CO J 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.56 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:350.32
MW Contribution:
198.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339241AF1-083 GEN
Solar/Wind Helper
0.54
339211AE2-254 GEN
Solar/Wind Helper
0.369
3429031COOPER2 G
50/50
3.813
972273AH1-721 GEN
50/50
234.928
339206AE1-143 GEN
Solar/Wind Helper
2.396
966021AG1-471 GEN
Solar/Wind Harmer
4.284
971485AH1-239 GEN
Solar/Wind Harmer
5.755
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.203
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.641
LAGNLTFEXP_LAGN->PJM
CLTF
0.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.765
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.525
NYPJM->LTFIMP_NY
CLTF
0.001
VTFLTFEXP_VFT->PJM
CMTX
0.042
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.319
MECLTFEXP_MEC->PJM
CLTF
0.062
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
CPLELTFEXP_CPLE->PJM
CLTF
0.21
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.067
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 234.93 MW.

Details for [AH1-721] 5COOPER1-5PULASK CO J 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-5PULASK CO J 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.24 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:325.52
MW Contribution:
198.94
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
234.928
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 234.93 MW.

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:173.44 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:868.91
MW Contribution:
672.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
4.247
971485AH1-239 GEN
Solar/Wind Harmer
5.577
3429031COOPER2 G
50/50
10.929
972273AH1-721 GEN
50/50
672.839
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.13
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.415
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.029
NYPJM->LTFIMP_NY
CLTF
0.055
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.002
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.011
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.257
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:168.91 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:846.23
MW Contribution:
672.84
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
672.839

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.16 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:652.09
MW Contribution:
524.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
8.56
972273AH1-721 GEN
50/50
524.744
339206AE1-143 GEN
Solar/Wind Helper
1.401
3429451LAUREL 1G
50/50
1.777
339231AF1-038_GEN
Solar/Wind Helper
0.641
339236AF1-050_GEN
Solar/Wind Helper
0.378
339241AF1-083 GEN
Solar/Wind Helper
0.413
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.233
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.811
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.039
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.057
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.088
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.185
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.15 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:652.08
MW Contribution:
524.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
8.56
972273AH1-721 GEN
50/50
524.744
339206AE1-143 GEN
Solar/Wind Helper
1.401
339241AF1-083 GEN
Solar/Wind Helper
0.413
3429451LAUREL 1G
50/50
1.777
339231AF1-038_GEN
Solar/Wind Helper
0.641
339236AF1-050_GEN
Solar/Wind Helper
0.378
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.233
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.811
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.039
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.088
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.057
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.185
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:129.73 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:649.97
MW Contribution:
522.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339241AF1-083 GEN
Solar/Wind Helper
0.411
3429451LAUREL 1G
50/50
1.768
339231AF1-038_GEN
Solar/Wind Helper
0.638
339236AF1-050_GEN
Solar/Wind Helper
0.376
3429031COOPER2 G
50/50
8.579
972273AH1-721 GEN
50/50
522.06
339206AE1-143 GEN
Solar/Wind Helper
1.394
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.232
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.808
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.039
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.057
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.088
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.181
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.83 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:635.42
MW Contribution:
524.74
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
524.744

Details for [AH1-721] 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.83 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:635.42
MW Contribution:
524.74
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
524.744

Details for [AH1-721] 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:126.41 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:633.29
MW Contribution:
522.06
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
522.06

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:258.0 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:714.66
MW Contribution:
557.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
9.089
972273AH1-721 GEN
50/50
557.261
3429451LAUREL 1G
50/50
1.856
966021AG1-471 GEN
Solar/Wind Harmer
4.577
971485AH1-239 GEN
Solar/Wind Harmer
6.132
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.192
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.596
LAGNLTFEXP_LAGN->PJM
CLTF
0.138
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.156
NYPJM->LTFIMP_NY
CLTF
0.059
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.143
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.225
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:256.54 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:710.6
MW Contribution:
558.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.861
966021AG1-471 GEN
Solar/Wind Harmer
4.409
971485AH1-239 GEN
Solar/Wind Harmer
5.915
3429031COOPER2 G
50/50
9.106
972273AH1-721 GEN
50/50
558.314
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.186
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.577
LAGNLTFEXP_LAGN->PJM
CLTF
0.088
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.118
NYPJM->LTFIMP_NY
CLTF
0.06
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.011
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.176
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.119
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1008_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:256.41 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:710.25
MW Contribution:
559.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.864
966021AG1-471 GEN
Solar/Wind Harmer
4.417
971485AH1-239 GEN
Solar/Wind Harmer
5.921
3429031COOPER2 G
50/50
9.119
972273AH1-721 GEN
50/50
559.128
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.189
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.59
LAGNLTFEXP_LAGN->PJM
CLTF
0.083
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.115
NYPJM->LTFIMP_NY
CLTF
0.06
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.022
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.011
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.187
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.106
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:256.41 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:710.25
MW Contribution:
559.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
9.119
972273AH1-721 GEN
50/50
559.128
3429451LAUREL 1G
50/50
1.864
966021AG1-471 GEN
Solar/Wind Harmer
4.417
971485AH1-239 GEN
Solar/Wind Harmer
5.921
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.189
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.59
LAGNLTFEXP_LAGN->PJM
CLTF
0.083
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.115
NYPJM->LTFIMP_NY
CLTF
0.06
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.022
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.187
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.106
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:254.83 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:705.89
MW Contribution:
560.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.871
966021AG1-471 GEN
Solar/Wind Harmer
2.99
971485AH1-239 GEN
Solar/Wind Harmer
3.999
3429031COOPER2 G
50/50
9.149
972273AH1-721 GEN
50/50
560.965
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.187
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.586
LAGNLTFEXP_LAGN->PJM
CLTF
0.032
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.078
NYPJM->LTFIMP_NY
CLTF
0.06
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.015
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.23
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:250.49 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:693.86
MW Contribution:
354.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.113
966021AG1-471 GEN
Solar/Wind Harmer
9.329
971485AH1-239 GEN
Solar/Wind Harmer
13.192
339231AF1-038_GEN
Solar/Wind Harmer
2.843
339236AF1-050_GEN
Solar/Wind Harmer
1.903
964781AG1-341 GEN
Solar/Wind Harmer
10.425
339241AF1-083 GEN
Solar/Wind Harmer
1.907
964901AG1-354 GEN
Solar/Wind Harmer
15.617
970653AG2-424 GEN
Solar/Wind Harmer
2.723
3429031COOPER2 G
50/50
6.798
972273AH1-721 GEN
50/50
418.865
339206AE1-143 GEN
Solar/Wind Harmer
2.773
339255AE2-071 GEN
Solar/Wind Harmer
1.202
339250AF1-203 GEN
Solar/Wind Harmer
0.619
970653AG2-424 GEN
Solar/Wind Harmer
0.394
950011AG9-010
External Queue
11.361714363098145
LAGNLTFEXP_LAGN->PJM
CLTF
1.784
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.646
TVALTFEXP_TVA->PJM
CLTF
1.295
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.562
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.923
MECLTFEXP_MEC->PJM
CLTF
0.666
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
0.124
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.013
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 418.87 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:250.48 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:693.83
MW Contribution:
354.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
6.798
972273AH1-721 GEN
50/50
418.865
339206AE1-143 GEN
Solar/Wind Harmer
2.773
339255AE2-071 GEN
Solar/Wind Harmer
1.202
339250AF1-203 GEN
Solar/Wind Harmer
0.619
970653AG2-424 GEN
Solar/Wind Harmer
0.394
3429451LAUREL 1G
50/50
2.113
966021AG1-471 GEN
Solar/Wind Harmer
9.329
971485AH1-239 GEN
Solar/Wind Harmer
13.192
339231AF1-038_GEN
Solar/Wind Harmer
2.843
339236AF1-050_GEN
Solar/Wind Harmer
1.903
964781AG1-341 GEN
Solar/Wind Harmer
10.425
339241AF1-083 GEN
Solar/Wind Harmer
1.907
964901AG1-354 GEN
Solar/Wind Harmer
15.617
970653AG2-424 GEN
Solar/Wind Harmer
2.723
950011AG9-010
External Queue
11.361714363098145
LAGNLTFEXP_LAGN->PJM
CLTF
1.784
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.646
TVALTFEXP_TVA->PJM
CLTF
1.295
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.562
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.923
MECLTFEXP_MEC->PJM
CLTF
0.666
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
0.124
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.013
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 418.87 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:250.47 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:693.79
MW Contribution:
354.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
6.798
972273AH1-721 GEN
50/50
418.865
339206AE1-143 GEN
Solar/Wind Harmer
2.773
339255AE2-071 GEN
Solar/Wind Harmer
1.202
339250AF1-203 GEN
Solar/Wind Harmer
0.619
970653AG2-424 GEN
Solar/Wind Harmer
0.394
339241AF1-083 GEN
Solar/Wind Harmer
1.907
964901AG1-354 GEN
Solar/Wind Harmer
15.617
970653AG2-424 GEN
Solar/Wind Harmer
2.723
3429451LAUREL 1G
50/50
2.113
966021AG1-471 GEN
Solar/Wind Harmer
9.329
971485AH1-239 GEN
Solar/Wind Harmer
13.192
339231AF1-038_GEN
Solar/Wind Harmer
2.843
339236AF1-050_GEN
Solar/Wind Harmer
1.903
964781AG1-341 GEN
Solar/Wind Harmer
10.425
950011AG9-010
External Queue
11.361714363098145
LAGNLTFEXP_LAGN->PJM
CLTF
1.784
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.646
TVALTFEXP_TVA->PJM
CLTF
1.295
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.562
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.923
MECLTFEXP_MEC->PJM
CLTF
0.666
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
0.124
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.013
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 418.87 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:250.35 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:693.48
MW Contribution:
355.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
6.81
972273AH1-721 GEN
50/50
419.599
339206AE1-143 GEN
Solar/Wind Harmer
2.78
339255AE2-071 GEN
Solar/Wind Harmer
1.206
339250AF1-203 GEN
Solar/Wind Harmer
0.621
970653AG2-424 GEN
Solar/Wind Harmer
0.395
3429451LAUREL 1G
50/50
2.116
966021AG1-471 GEN
Solar/Wind Harmer
9.361
971485AH1-239 GEN
Solar/Wind Harmer
13.237
339231AF1-038_GEN
Solar/Wind Harmer
2.854
339236AF1-050_GEN
Solar/Wind Harmer
1.908
964781AG1-341 GEN
Solar/Wind Harmer
10.458
339241AF1-083 GEN
Solar/Wind Harmer
1.912
964901AG1-354 GEN
Solar/Wind Harmer
15.662
970653AG2-424 GEN
Solar/Wind Harmer
2.731
950011AG9-010
External Queue
11.39061164855957
LAGNLTFEXP_LAGN->PJM
CLTF
1.806
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.669
TVALTFEXP_TVA->PJM
CLTF
1.309
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.582
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.967
MECLTFEXP_MEC->PJM
CLTF
0.672
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
0.13
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.11
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 419.6 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:250.29 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:693.3
MW Contribution:
355.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339241AF1-083 GEN
Solar/Wind Harmer
1.91
964901AG1-354 GEN
Solar/Wind Harmer
15.642
970653AG2-424 GEN
Solar/Wind Harmer
2.728
3429031COOPER2 G
50/50
6.804
972273AH1-721 GEN
50/50
419.224
339206AE1-143 GEN
Solar/Wind Harmer
2.777
339255AE2-071 GEN
Solar/Wind Harmer
1.204
339250AF1-203 GEN
Solar/Wind Harmer
0.62
970653AG2-424 GEN
Solar/Wind Harmer
0.394
3429451LAUREL 1G
50/50
2.114
966021AG1-471 GEN
Solar/Wind Harmer
9.345
971485AH1-239 GEN
Solar/Wind Harmer
13.214
339231AF1-038_GEN
Solar/Wind Harmer
2.849
339236AF1-050_GEN
Solar/Wind Harmer
1.906
964781AG1-341 GEN
Solar/Wind Harmer
10.442
950011AG9-010
External Queue
11.37878131866455
LAGNLTFEXP_LAGN->PJM
CLTF
1.796
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.657
TVALTFEXP_TVA->PJM
CLTF
1.302
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.946
MECLTFEXP_MEC->PJM
CLTF
0.669
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
0.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.065
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 419.22 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:249.4 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:690.83
MW Contribution:
557.26
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
557.261

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:248.13 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:687.31
MW Contribution:
558.31
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
558.314

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1008_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:247.82 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:686.46
MW Contribution:
559.13
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
559.128

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:247.82 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:686.46
MW Contribution:
559.13
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
559.128

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:247.66 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:686.01
MW Contribution:
560.97
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
560.965

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:240.63 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:666.55
MW Contribution:
355.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.116
966021AG1-471 GEN
Solar/Wind Harmer
6.531
971485AH1-239 GEN
Solar/Wind Harmer
9.235
964781AG1-341 GEN
Solar/Wind Harmer
7.296
3429031COOPER2 G
50/50
6.81
972273AH1-721 GEN
50/50
419.599
970653AG2-424 GEN
Solar/Wind Harmer
0.395
964901AG1-354 GEN
Solar/Wind Harmer
10.927
970653AG2-424 GEN
Solar/Wind Harmer
1.905
950011AG9-010
External Queue
11.39061164855957
LAGNLTFEXP_LAGN->PJM
CLTF
1.806
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.669
TVALTFEXP_TVA->PJM
CLTF
1.309
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.582
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.967
MECLTFEXP_MEC->PJM
CLTF
0.672
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
0.13
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.11
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 419.6 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:238.58 %
Rating:219.0 MVA
Rating Type:A
MVA to Mitigate:522.49
MW Contribution:
307.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.172
966021AG1-471 GEN
Solar/Wind Harmer
5.566
971485AH1-239 GEN
Solar/Wind Harmer
7.867
964781AG1-341 GEN
Solar/Wind Harmer
6.207
3429031COOPER2 G
50/50
5.929
972273AH1-721 GEN
50/50
363.691
970653AG2-424 GEN
Solar/Wind Harmer
0.333
964901AG1-354 GEN
Solar/Wind Harmer
9.324
970653AG2-424 GEN
Solar/Wind Harmer
1.606
950011AG9-010
External Queue
9.8912935256958
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.03
LAGNLTFEXP_LAGN->PJM
CLTF
1.443
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.494
TVALTFEXP_TVA->PJM
CLTF
1.061
NYPJM->LTFIMP_NY
CLTF
0.066
WECLTFEXP_WEC->PJM
CLTF
0.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.912
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.14
MECLTFEXP_MEC->PJM
CLTF
0.52
SIGELTFEXP_SIGE->PJM
CLTF
0.016
CPLELTFEXP_CPLE->PJM
CLTF
0.092
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.133
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 363.69 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOP-LAURD 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOP-LAURD 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:235.73 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:652.99
MW Contribution:
355.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
6.813
972273AH1-721 GEN
50/50
419.775
339206AE1-143 GEN
Solar/Wind Harmer
2.784
339255AE2-071 GEN
Solar/Wind Harmer
1.208
339250AF1-203 GEN
Solar/Wind Harmer
0.622
970653AG2-424 GEN
Solar/Wind Harmer
0.396
966021AG1-471 GEN
Solar/Wind Harmer
9.372
971485AH1-239 GEN
Solar/Wind Harmer
13.253
339231AF1-038_GEN
Solar/Wind Harmer
2.858
339236AF1-050_GEN
Solar/Wind Harmer
1.912
964781AG1-341 GEN
Solar/Wind Harmer
10.479
339241AF1-083 GEN
Solar/Wind Harmer
1.916
964901AG1-354 GEN
Solar/Wind Harmer
15.693
970653AG2-424 GEN
Solar/Wind Harmer
2.741
950011AG9-010
External Queue
11.39061164855957
LAGNLTFEXP_LAGN->PJM
CLTF
1.847
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.729
TVALTFEXP_TVA->PJM
CLTF
1.329
NYPJM->LTFIMP_NY
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.874
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.043
MECLTFEXP_MEC->PJM
CLTF
0.706
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.152
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.38
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 419.77 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 1_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:220.33 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:610.32
MW Contribution:
421.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
8.115
972273AH1-721 GEN
50/50
497.808
3429451LAUREL 1G
50/50
1.658
966021AG1-471 GEN
Solar/Wind Harmer
5.649
971485AH1-239 GEN
Solar/Wind Harmer
7.689
339231AF1-038_GEN
Solar/Wind Harmer
1.23
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.167
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.5
LAGNLTFEXP_LAGN->PJM
CLTF
0.331
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.05
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.283
NYPJM->LTFIMP_NY
CLTF
0.058
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.001
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.638
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.896
MDUPJM->LTFIMP_MDU
CLTF
0
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 497.81 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_PULASKI 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_PULASKI 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:216.21 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:598.91
MW Contribution:
351.19
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
6.763
972273AH1-721 GEN
50/50
414.857
339255AE2-071 GEN
Solar/Wind Harmer
0.905
339250AF1-203 GEN
Solar/Wind Harmer
0.466
3429451LAUREL 1G
50/50
1.35
966021AG1-471 GEN
Solar/Wind Harmer
8.618
971485AH1-239 GEN
Solar/Wind Harmer
12.026
339231AF1-038_GEN
Solar/Wind Harmer
1.911
964781AG1-341 GEN
Solar/Wind Harmer
8.1
339236AF1-050_GEN
Solar/Wind Harmer
1.022
964901AG1-354 GEN
Solar/Wind Harmer
8.817
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.148
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.363
LAGNLTFEXP_LAGN->PJM
CLTF
1.468
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.747
TVALTFEXP_TVA->PJM
CLTF
1.1
NYPJM->LTFIMP_NY
CLTF
0.056
WECLTFEXP_WEC->PJM
CLTF
0.035
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.124
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.109
MECLTFEXP_MEC->PJM
CLTF
0.425
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
0.169
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.535
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 414.86 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:212.83 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:589.54
MW Contribution:
354.92
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
418.865
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 418.87 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:212.83 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:589.54
MW Contribution:
354.92
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
418.865
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 418.87 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:212.56 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:588.79
MW Contribution:
355.22
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
419.224
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 419.22 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:212.56 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:588.79
MW Contribution:
355.22
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
419.224
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 419.22 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:212.55 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:588.75
MW Contribution:
355.54
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
419.599
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 419.6 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:212.55 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:588.75
MW Contribution:
355.54
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
419.599
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 419.6 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 1_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:210.18 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:582.21
MW Contribution:
421.34
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
497.808
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 497.81 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:209.11 %
Rating:219.0 MVA
Rating Type:A
MVA to Mitigate:457.95
MW Contribution:
307.93
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
363.691
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 363.69 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOP-LAURD 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOP-LAURD 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:198.41 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:549.61
MW Contribution:
355.7
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
419.775
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 419.77 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_PULASKI 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_PULASKI 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:192.36 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:532.84
MW Contribution:
351.2
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
414.857
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 414.86 MW.

Details for 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:270.03 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:294.34
MW Contribution:
282.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
282.813
3429451LAUREL 1G
50/50
0.955
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.108
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.003
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.056
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.081
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.555
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:270.02 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:294.33
MW Contribution:
282.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
282.813
3429451LAUREL 1G
50/50
0.955
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.108
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.003
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.056
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.081
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.555
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:268.6 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:292.78
MW Contribution:
281.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
281.003
3429451LAUREL 1G
50/50
0.948
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.088
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.004
LGEELTFEXP_LGEE->PJM
CLTF
0.002
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.057
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.083
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.538
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:268.14 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:292.27
MW Contribution:
282.81
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
282.813

Details for [AH1-721] 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:268.14 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:292.27
MW Contribution:
282.81
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
282.813

Details for [AH1-721] 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:266.54 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:290.53
MW Contribution:
281.0
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
281.003

Details for 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.84 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:128.44
MW Contribution:
72.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
85.157
3429031COOPER2 G
50/50
1.352
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.015
LGEELTFEXP_LGEE->PJM
CLTF
0.083
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.062
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.068
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 85.16 MW.

Details for [AH1-721] 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:116.44 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:126.92
MW Contribution:
72.46
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
85.157
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 85.16 MW.

Details for 5GREEN HAL T-5DELVINTA 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5GREEN HAL T-5DELVINTA 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:100.07 %
Rating:251.0 MVA
Rating Type:B
MVA to Mitigate:251.17
MW Contribution:
319.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
319.051
3429451LAUREL 1G
50/50
1.609
LAGNLTFEXP_LAGN->PJM
CLTF
0.547
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.512
TVALTFEXP_TVA->PJM
CLTF
0.356
NYPJM->LTFIMP_NY
CLTF
0.006
LGEELTFEXP_LGEE->PJM
CLTF
0.053
WECLTFEXP_WEC->PJM
CLTF
0.019
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.61
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.149
MECLTFEXP_MEC->PJM
CLTF
0.174
SIGELTFEXP_SIGE->PJM
CLTF
0.007
CPLELTFEXP_CPLE->PJM
CLTF
0.135
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.602

Details for 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:231.83 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:352.38
MW Contribution:
307.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.55
972273AH1-721 GEN
50/50
307.315
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.003
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.024
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.014
LGEELTFEXP_LGEE->PJM
CLTF
0.001
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.054
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.079
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.269
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:230.52 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:350.39
MW Contribution:
307.31
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
307.315

Details for 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.36 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:223.99
MW Contribution:
188.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
188.258
3429451LAUREL 1G
50/50
1.148
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.012
LGEELTFEXP_LGEE->PJM
CLTF
0.002
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.044
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.035
SIGELTFEXP_SIGE->PJM
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.29 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:223.88
MW Contribution:
188.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
188.022
3429451LAUREL 1G
50/50
1.147
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.012
LGEELTFEXP_LGEE->PJM
CLTF
0.003
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.045
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.035
SIGELTFEXP_SIGE->PJM
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:147.29 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:223.88
MW Contribution:
188.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
188.022
3429451LAUREL 1G
50/50
1.147
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.012
LGEELTFEXP_LGEE->PJM
CLTF
0.003
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.045
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.035
SIGELTFEXP_SIGE->PJM
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.55 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:222.75
MW Contribution:
188.26
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
188.258

Details for [AH1-721] 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.49 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:222.67
MW Contribution:
188.02
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
188.022

Details for [AH1-721] 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:146.49 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:222.67
MW Contribution:
188.02
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
188.022

Details for 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_TYNER E13-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_TYNER E13-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.08 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:167.33
MW Contribution:
45.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
Adder
53.783
3429451LAUREL 1G
50/50
1.069
LAGNLTFEXP_LAGN->PJM
CLTF
0.185
TVALTFEXP_TVA->PJM
CLTF
0.134
NYPJM->LTFIMP_NY
CLTF
0.02
LGEELTFEXP_LGEE->PJM
CLTF
0.073
WECLTFEXP_WEC->PJM
CLTF
0.017
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.484
MECLTFEXP_MEC->PJM
CLTF
0.108
SIGELTFEXP_SIGE->PJM
CLTF
0.007
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.226
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 53.78 MW.

Details for 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P1-2_LAUR-PIT-TY161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P1-2_LAUR-PIT-TY161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.0 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:164.15
MW Contribution:
50.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.086
972273AH1-721 GEN
50/50
58.842
3429031COOPER2 G
50/50
0.924
LAGNLTFEXP_LAGN->PJM
CLTF
0.212
TVALTFEXP_TVA->PJM
CLTF
0.151
NYPJM->LTFIMP_NY
CLTF
0.02
LGEELTFEXP_LGEE->PJM
CLTF
0.079
WECLTFEXP_WEC->PJM
CLTF
0.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.006
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.604
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.544
MECLTFEXP_MEC->PJM
CLTF
0.119
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.371
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 58.84 MW.

Details for [AH1-721] 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_TYNER E13-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_TYNER E13-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.12 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:162.83
MW Contribution:
48.64
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
57.071
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 57.07 MW.

Details for [AH1-721] 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P1-2_LAUR-PIT-TY161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P1-2_LAUR-PIT-TY161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.58 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:158.96
MW Contribution:
50.14
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
58.842
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 58.84 MW.

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:238.63 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:477.27
MW Contribution:
451.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.276
972273AH1-721 GEN
50/50
451.337
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.044
LAGNLTFEXP_LAGN->PJM
CLTF
0.282
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.304
TVALTFEXP_TVA->PJM
CLTF
0.189
NYPJM->LTFIMP_NY
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.001
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.559
MECLTFEXP_MEC->PJM
CLTF
0.055
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.15

Details for [AH1-721] 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:236.15 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:472.3
MW Contribution:
451.34
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
451.337

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.22 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:348.43
MW Contribution:
289.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
289.391
3429451LAUREL 1G
50/50
1.73
966021AG1-471 GEN
Solar/Wind Harmer
3.031
971485AH1-239 GEN
Solar/Wind Harmer
4.128
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.01
LAGNLTFEXP_LAGN->PJM
CLTF
0.621
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.561
TVALTFEXP_TVA->PJM
CLTF
0.418
NYPJM->LTFIMP_NY
CLTF
0.006
WECLTFEXP_WEC->PJM
CLTF
0.017
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.537
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.261
MECLTFEXP_MEC->PJM
CLTF
0.179
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.149
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.8

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.62 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:347.25
MW Contribution:
287.82
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.724
966021AG1-471 GEN
Solar/Wind Harmer
3.013
971485AH1-239 GEN
Solar/Wind Harmer
4.111
972273AH1-721 GEN
50/50
287.817
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
0.629
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.556
TVALTFEXP_TVA->PJM
CLTF
0.423
NYPJM->LTFIMP_NY
CLTF
0.006
WECLTFEXP_WEC->PJM
CLTF
0.018
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.282
MECLTFEXP_MEC->PJM
CLTF
0.186
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
0.147
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.866

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:173.61 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:347.23
MW Contribution:
287.82
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
287.817
3429451LAUREL 1G
50/50
1.724
966021AG1-471 GEN
Solar/Wind Harmer
3.013
971485AH1-239 GEN
Solar/Wind Harmer
4.111
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
0.629
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.556
TVALTFEXP_TVA->PJM
CLTF
0.423
NYPJM->LTFIMP_NY
CLTF
0.006
WECLTFEXP_WEC->PJM
CLTF
0.018
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.282
MECLTFEXP_MEC->PJM
CLTF
0.186
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
0.147
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.866

Details for [AH1-721] 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.14 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:332.29
MW Contribution:
289.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
289.391

Details for [AH1-721] 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:165.4 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:330.79
MW Contribution:
287.82
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
287.817

Details for [AH1-721] 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.4 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:330.79
MW Contribution:
287.82
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
287.817

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:414.2 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:828.4
MW Contribution:
758.65
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
3.826
972273AH1-721 GEN
50/50
758.652
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.022
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.068
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.102
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:412.16 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:824.32
MW Contribution:
758.65
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
758.652

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:301.0 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:602.0
MW Contribution:
477.65
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.878
966021AG1-471 GEN
Solar/Wind Harmer
4.438
971485AH1-239 GEN
Solar/Wind Harmer
6.02
972273AH1-721 GEN
50/50
477.649
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.527
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.343
TVALTFEXP_TVA->PJM
CLTF
0.367
NYPJM->LTFIMP_NY
CLTF
0.018
WECLTFEXP_WEC->PJM
CLTF
0.016
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.105
MECLTFEXP_MEC->PJM
CLTF
0.163
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.082
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.451

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:290.96 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:581.91
MW Contribution:
477.65
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
477.649

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:289.82 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:579.65
MW Contribution:
475.84
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
475.84

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:289.82 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:579.65
MW Contribution:
475.84
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
475.84

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:175.49 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:350.97
MW Contribution:
143.5
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339241AF1-083 GEN
Solar/Wind Harmer
0.787
964901AG1-354 GEN
Solar/Wind Harmer
6.523
3429451LAUREL 1G
50/50
1.83
339231AF1-038_GEN
Solar/Wind Harmer
1.376
966021AG1-471 GEN
Solar/Wind Harmer
3.927
971485AH1-239 GEN
Solar/Wind Harmer
5.561
339236AF1-050_GEN
Solar/Wind Harmer
0.794
972273AH1-721 GEN
50/50
168.518
3429031COOPER2 G
50/50
2.659
339206AE1-143 GEN
Solar/Wind Harmer
1.133
339255AE2-071 GEN
Solar/Wind Harmer
0.515
339250AF1-203 GEN
Solar/Wind Harmer
0.265
LAGNLTFEXP_LAGN->PJM
CLTF
0.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.392
TVALTFEXP_TVA->PJM
CLTF
0.628
NYPJM->LTFIMP_NY
CLTF
0.039
LGEELTFEXP_LGEE->PJM
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.047
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.015
MECLTFEXP_MEC->PJM
CLTF
0.36
SIGELTFEXP_SIGE->PJM
CLTF
0.016
CPLELTFEXP_CPLE->PJM
CLTF
0.082
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.745
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 168.52 MW.

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:157.12 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:314.25
MW Contribution:
143.5
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
168.518
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 168.52 MW.

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:156.49 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:312.98
MW Contribution:
141.81
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
166.941
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 166.94 MW.

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:156.49 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:312.98
MW Contribution:
141.81
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
166.941
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 166.94 MW.

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.84 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:259.67
MW Contribution:
127.08
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
127.076

Details for 5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.57 %
Rating:220.0 MVA
Rating Type:B
MVA to Mitigate:234.46
MW Contribution:
92.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
1.767
972273AH1-721 GEN
50/50
108.965
339206AE1-143 GEN
Solar/Wind Harmer
8.636
339255AE2-071 GEN
Solar/Wind Harmer
0.855
339250AF1-203 GEN
Solar/Wind Harmer
0.44
970653AG2-424 GEN
Solar/Wind Harmer
0.404
339236AF1-050_GEN
Solar/Wind Harmer
2.932
339231AF1-038_GEN
Solar/Wind Harmer
1.786
971485AH1-239 GEN
Solar/Wind Harmer
5.85
966021AG1-471 GEN
Solar/Wind Harmer
3.94
964781AG1-341 GEN
Solar/Wind Harmer
7.499
339241AF1-083 GEN
Solar/Wind Harmer
4.334
964901AG1-354 GEN
Solar/Wind Harmer
22.606
970653AG2-424 GEN
Solar/Wind Harmer
2.794
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.292
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.886
LAGNLTFEXP_LAGN->PJM
CLTF
1.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.121
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.892
NYPJM->LTFIMP_NY
CLTF
0.008
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.251
MECLTFEXP_MEC->PJM
CLTF
0.173
CPLELTFEXP_CPLE->PJM
CLTF
0.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.988
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 108.97 MW.

Details for 5PITTSBURG-2PITTSBRG KU 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5PITTSBURG-2PITTSBRG KU 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:117.41 %
Rating:129.0 MVA
Rating Type:B
MVA to Mitigate:151.45
MW Contribution:
104.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
104.449
3429451LAUREL 1G
50/50
0.527
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.062
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.045
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.185
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5PITTSBURG-2PITTSBRG KU 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5PITTSBURG-2PITTSBRG KU 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:116.73 %
Rating:129.0 MVA
Rating Type:B
MVA to Mitigate:150.58
MW Contribution:
104.45
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
104.449

Details for 5PITTSBURG-5TYNER 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5PITTSBURG-5TYNER 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:131.41 %
Rating:250.0 MVA
Rating Type:B
MVA to Mitigate:328.51
MW Contribution:
346.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
346.888
3429451LAUREL 1G
50/50
1.75
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.002
LAGNLTFEXP_LAGN->PJM
CLTF
0.502
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.538
TVALTFEXP_TVA->PJM
CLTF
0.329
NYPJM->LTFIMP_NY
CLTF
0.003
LGEELTFEXP_LGEE->PJM
CLTF
0.002
WECLTFEXP_WEC->PJM
CLTF
0.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.301
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.016
MECLTFEXP_MEC->PJM
CLTF
0.131
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.146
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.212

Details for [AH1-721] 5PITTSBURG-5TYNER 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5PITTSBURG-5TYNER 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:128.63 %
Rating:250.0 MVA
Rating Type:B
MVA to Mitigate:321.57
MW Contribution:
346.89
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
346.888

Details for 5TYNER-5GREEN HAL T 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5TYNER-5GREEN HAL T 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:101.55 %
Rating:250.0 MVA
Rating Type:B
MVA to Mitigate:253.88
MW Contribution:
319.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
319.051
3429451LAUREL 1G
50/50
1.609
LAGNLTFEXP_LAGN->PJM
CLTF
0.547
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.512
TVALTFEXP_TVA->PJM
CLTF
0.356
NYPJM->LTFIMP_NY
CLTF
0.006
LGEELTFEXP_LGEE->PJM
CLTF
0.053
WECLTFEXP_WEC->PJM
CLTF
0.019
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.61
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.149
MECLTFEXP_MEC->PJM
CLTF
0.174
SIGELTFEXP_SIGE->PJM
CLTF
0.007
CPLELTFEXP_CPLE->PJM
CLTF
0.135
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.602

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1445_ZIMMER_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1445_ZIMMER_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.55 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1647.65
MW Contribution:
88.65
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
18.648
25197108MELDL2
50/50
1.268
971125AH1-004 GEN
Solar/Wind Harmer
11.529
970107AG2-081 GEN
Solar/Wind Harmer
8.647
972043AH1-570 GEN
Solar/Wind Harmer
7.199
972045AH1-571 GEN
Solar/Wind Harmer
5.759
942891AE2-308 GEN
Solar/Wind Harmer
25.15
3429661SPURLK4G
50/50
9.786
25197008MELDL1
50/50
1.25
3429571SPURLK1G
50/50
9.78
945681AF1-233 GEN
Solar/Wind Harmer
83.584
943111AE2-339 GEN
Solar/Wind Harmer
2.559
3429421JKCT 10G
Adder
24.087
339221AD2-048_GEN
Solar/Wind Harmer
4.286
3429241JKCT 3G
Adder
32.179
339211AE2-254 GEN
Solar/Wind Harmer
2.559
339241AF1-083 GEN
Solar/Wind Harmer
1.767
970653AG2-424 GEN
Solar/Wind Harmer
4.64
964901AG1-354 GEN
Solar/Wind Harmer
13.573
971687AH1-348 GEN
Solar/Wind Harmer
0.458
253398AE2-221_GEN2
Solar/Wind Helper
2.196
253333AC1-068 GEN
Solar/Wind Helper
0.827
972163AH1-664 GEN
Solar/Wind Harmer
43.025
972165AH1-665 GEN
Solar/Wind Harmer
34.42
339216AC1-074 GEN
Solar/Wind Harmer
4.856
3429211JKCT 2G
Adder
31.762
962211AG1-066 GEN
Solar/Wind Harmer
2.194
970281AG2-184 GEN
Solar/Wind Harmer
13.04
253338AC1-165 GEN
Solar/Wind Helper
0.798
253343AC1-166 GEN
Solar/Wind Helper
0.798
253406AD2-031_GEN
Solar/Wind Helper
0.685
945631AF1-228 GEN
Solar/Wind Helper
0.92
241972AD1-140 GEN
Solar/Wind Helper
1.755
3429631SPURLK3G
50/50
9.786
25197208MELDL3
50/50
1.258
958171AF2-111 GEN
Solar/Wind Harmer
128.735
972167AH1-666 GEN
Solar/Wind Harmer
35.72
339243AC2-075 GEN1
Solar/Wind Harmer
1.315
3429391JKCT 9G
Adder
24.087
970093AG2-073 GEN
Solar/Wind Harmer
12.282
972273AH1-721 GEN
Adder
104.619
339206AE1-143 GEN
Solar/Wind Harmer
2.513
970455AG2-298 GEN
Solar/Wind Harmer
3.9
970653AG2-424 GEN
Solar/Wind Harmer
0.671
270186AC1-089 GEN
Solar/Wind Harmer
5.472
339255AE2-071 GEN
Solar/Wind Harmer
0.94
339250AF1-203 GEN
Solar/Wind Harmer
0.484
972103AH1-617 GEN
Solar/Wind Harmer
12.419
971461AH1-227 GEN
Solar/Wind Harmer
2.266
253394AE2-221_GEN
Solar/Wind Helper
2.196
253325AC1-069 GEN
Solar/Wind Helper
0.827
252507AC2-088 GEN
Solar/Wind Helper
0.993
270518AE2-148 GEN
Solar/Wind Helper
6.125
339231AF1-038_GEN
Solar/Wind Harmer
1.929
339236AF1-050_GEN
Solar/Wind Harmer
1.676
966021AG1-471 GEN
Solar/Wind Harmer
4.849
971485AH1-239 GEN
Solar/Wind Harmer
7.098
964571AG1-320 GEN
Solar/Wind Harmer
7.24
964781AG1-341 GEN
Solar/Wind Harmer
8.124
971225AH1-072 GEN
Solar/Wind Harmer
0.883
971227AH1-073 GEN
Solar/Wind Harmer
0.883
25183208HLCRTG
Solar/Wind Helper
2.43
252509AD1-136 GEN
Solar/Wind Helper
0.142
253415AE1-040 GEN
Solar/Wind Helper
0.408
950051AG9-018
External Queue
23.236736297607422
950041AG9-017
External Queue
23.31861114501953
950011AG9-010
External Queue
6.1081342697143555
LAGNLTFEXP_LAGN->PJM
CLTF
6.1
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.899
TVALTFEXP_TVA->PJM
CLTF
3.738
NYPJM->LTFIMP_NY
CLTF
0.555
LGEELTFEXP_LGEE->PJM
CLTF
4.938
WECLTFEXP_WEC->PJM
CLTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.881
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.374
MECLTFEXP_MEC->PJM
CLTF
2.567
SIGELTFEXP_SIGE->PJM
CLTF
0.219
CPLELTFEXP_CPLE->PJM
CLTF
1.184
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.757
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 104.62 MW.

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1449_ZIMMER_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1449_ZIMMER_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.43 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1645.79
MW Contribution:
88.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429661SPURLK4G
50/50
9.787
25197008MELDL1
50/50
1.25
3429571SPURLK1G
50/50
9.78
945681AF1-233 GEN
Solar/Wind Harmer
83.589
943111AE2-339 GEN
Solar/Wind Harmer
2.559
3429421JKCT 10G
Adder
24.086
339221AD2-048_GEN
Solar/Wind Harmer
4.286
3429241JKCT 3G
Adder
32.178
339211AE2-254 GEN
Solar/Wind Harmer
2.559
339241AF1-083 GEN
Solar/Wind Harmer
1.767
970653AG2-424 GEN
Solar/Wind Harmer
4.638
964901AG1-354 GEN
Solar/Wind Harmer
13.568
971687AH1-348 GEN
Solar/Wind Harmer
0.458
253398AE2-221_GEN2
Solar/Wind Helper
2.194
972163AH1-664 GEN
Solar/Wind Harmer
43.027
972165AH1-665 GEN
Solar/Wind Harmer
34.422
339216AC1-074 GEN
Solar/Wind Harmer
4.855
3429211JKCT 2G
Adder
31.761
962211AG1-066 GEN
Solar/Wind Harmer
2.194
970281AG2-184 GEN
Solar/Wind Harmer
13.039
253338AC1-165 GEN
Solar/Wind Helper
0.797
253343AC1-166 GEN
Solar/Wind Helper
0.797
253406AD2-031_GEN
Solar/Wind Helper
0.683
945631AF1-228 GEN
Solar/Wind Helper
0.919
3429631SPURLK3G
50/50
9.787
25197208MELDL3
50/50
1.258
958171AF2-111 GEN
Solar/Wind Harmer
128.745
972167AH1-666 GEN
Solar/Wind Harmer
35.722
339243AC2-075 GEN1
Solar/Wind Harmer
1.315
3429391JKCT 9G
Adder
24.086
970093AG2-073 GEN
Solar/Wind Harmer
12.281
972273AH1-721 GEN
Adder
104.598
339206AE1-143 GEN
Solar/Wind Harmer
2.513
970455AG2-298 GEN
Solar/Wind Harmer
3.899
970653AG2-424 GEN
Solar/Wind Harmer
0.671
270186AC1-089 GEN
Solar/Wind Harmer
5.475
339255AE2-071 GEN
Solar/Wind Harmer
0.939
339250AF1-203 GEN
Solar/Wind Harmer
0.484
972103AH1-617 GEN
Solar/Wind Harmer
12.418
971461AH1-227 GEN
Solar/Wind Harmer
2.266
253394AE2-221_GEN
Solar/Wind Helper
2.194
253325AC1-069 GEN
Solar/Wind Helper
0.826
252507AC2-088 GEN
Solar/Wind Helper
0.996
270518AE2-148 GEN
Solar/Wind Helper
6.113
3429601SPURLK2G
50/50
18.65
25197108MELDL2
50/50
1.268
971125AH1-004 GEN
Solar/Wind Harmer
11.528
970107AG2-081 GEN
Solar/Wind Harmer
8.646
972043AH1-570 GEN
Solar/Wind Harmer
7.198
972045AH1-571 GEN
Solar/Wind Harmer
5.758
942891AE2-308 GEN
Solar/Wind Harmer
25.149
339231AF1-038_GEN
Solar/Wind Harmer
1.929
339236AF1-050_GEN
Solar/Wind Harmer
1.675
966021AG1-471 GEN
Solar/Wind Harmer
4.847
971485AH1-239 GEN
Solar/Wind Harmer
7.096
964571AG1-320 GEN
Solar/Wind Harmer
7.237
964781AG1-341 GEN
Solar/Wind Harmer
8.121
971225AH1-072 GEN
Solar/Wind Harmer
0.883
971227AH1-073 GEN
Solar/Wind Harmer
0.883
25183208HLCRTG
Solar/Wind Helper
2.425
252509AD1-136 GEN
Solar/Wind Helper
0.142
253415AE1-040 GEN
Solar/Wind Helper
0.407
253333AC1-068 GEN
Solar/Wind Helper
0.826
950051AG9-018
External Queue
23.243040084838867
950041AG9-017
External Queue
23.32491683959961
950011AG9-010
External Queue
6.111148357391357
LAGNLTFEXP_LAGN->PJM
CLTF
6.095
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.896
TVALTFEXP_TVA->PJM
CLTF
3.736
NYPJM->LTFIMP_NY
CLTF
0.554
LGEELTFEXP_LGEE->PJM
CLTF
4.934
WECLTFEXP_WEC->PJM
CLTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.856
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.363
MECLTFEXP_MEC->PJM
CLTF
2.563
SIGELTFEXP_SIGE->PJM
CLTF
0.219
CPLELTFEXP_CPLE->PJM
CLTF
1.183
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.719
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 104.6 MW.

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o 34569 34598 34524_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
34569 34598 34524_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.98 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1638.99
MW Contribution:
75.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
7.061
25197208MELDL3
50/50
0.562
958171AF2-111 GEN
Solar/Wind Harmer
93.601
972167AH1-666 GEN
Solar/Wind Harmer
26.206
339243AC2-075 GEN1
Solar/Wind Harmer
1.039
3429391JKCT 9G
Adder
18.489
970093AG2-073 GEN
Solar/Wind Harmer
9.666
972273AH1-721 GEN
Adder
88.699
339206AE1-143 GEN
Solar/Wind Harmer
2.228
970455AG2-298 GEN
Solar/Wind Harmer
3.621
970653AG2-424 GEN
Solar/Wind Harmer
0.639
25196008MFTGT1
Adder
1.024
3429601SPURLK2G
50/50
13.454
25197108MELDL2
50/50
0.567
972043AH1-570 GEN
Solar/Wind Harmer
5.598
972045AH1-571 GEN
Solar/Wind Harmer
4.479
971125AH1-004 GEN
Solar/Wind Harmer
8.94
970107AG2-081 GEN
Solar/Wind Harmer
6.705
942891AE2-308 GEN
Solar/Wind Harmer
19.644
339231AF1-038_GEN
Solar/Wind Harmer
1.696
964571AG1-320 GEN
Solar/Wind Harmer
7.187
339236AF1-050_GEN
Solar/Wind Harmer
1.554
966021AG1-471 GEN
Solar/Wind Harmer
4.35
971485AH1-239 GEN
Solar/Wind Harmer
6.405
964781AG1-341 GEN
Solar/Wind Harmer
7.81
25194408D.CRK1
Adder
5.134
25194508D.CRK3
Adder
0.96
25183208HLCRTG
Solar/Wind Helper
5.698
253415AE1-040 GEN
Solar/Wind Helper
0.679
252509AD1-136 GEN
Solar/Wind Helper
0.14
946101AF1-275 GEN
Solar/Wind Helper
0.373
253383AE2-342_GEN
Solar/Wind Helper
0.369
339255AE2-071 GEN
Solar/Wind Harmer
0.892
339250AF1-203 GEN
Solar/Wind Harmer
0.459
270186AC1-089 GEN
Solar/Wind Harmer
4.247
252524AE2-267 GEN
Solar/Wind Harmer
1.09
25196608WSDLE5
Adder
5.933
25194608D.CRK4
Adder
1.116
972103AH1-617 GEN
Solar/Wind Harmer
9.479
253394AE2-221_GEN
Solar/Wind Helper
3.664
253325AC1-069 GEN
Solar/Wind Helper
1.339
270518AE2-148 GEN
Solar/Wind Helper
9.686
252507AC2-088 GEN
Solar/Wind Helper
0.978
972163AH1-664 GEN
Solar/Wind Harmer
31.649
972165AH1-665 GEN
Solar/Wind Harmer
25.319
339216AC1-074 GEN
Solar/Wind Harmer
3.834
3429211JKCT 2G
Adder
24.533
25196108MFTGT2
Adder
1.166
25196108MFTGT2
Adder
1.082
962211AG1-066 GEN
Solar/Wind Harmer
1.711
25196408WSDLE3
Adder
6.108
25196308WSDLE2
Adder
6.055
25196208WSDLE1
Adder
6.04
25196708WSDLE6
Adder
6.025
25196508WSDLE4
Adder
5.873
970281AG2-184 GEN
Solar/Wind Harmer
9.952
253338AC1-165 GEN
Solar/Wind Helper
1.292
253343AC1-166 GEN
Solar/Wind Helper
1.292
253406AD2-031_GEN
Solar/Wind Helper
1.192
945631AF1-228 GEN
Solar/Wind Helper
1.431
241972AD1-140 GEN
Solar/Wind Helper
2.736
270340AC2-060 GEN
Solar/Wind Helper
1.34
241955AC1-078 GEN
Solar/Wind Helper
1.212
241973AD2-163_GEN1
Solar/Wind Helper
0.942
241974AD2-163_GEN2
Solar/Wind Helper
0.942
270263AC1-001 GEN
Solar/Wind Helper
0.509
960071AF2-298 GEN
Solar/Wind Helper
0.314
960801AF2-371 GEN
Solar/Wind Helper
0.52
964871AG1-351 GEN
Solar/Wind Helper
0.359
3429661SPURLK4G
50/50
7.061
3429571SPURLK1G
50/50
7.129
25197008MELDL1
50/50
0.559
945681AF1-233 GEN
Solar/Wind Harmer
61.342
943111AE2-339 GEN
Solar/Wind Harmer
1.979
3429421JKCT 10G
Adder
18.489
339221AD2-048_GEN
Solar/Wind Harmer
3.377
25196808ZIMRHP
Adder
160.518
3429241JKCT 3G
Adder
24.855
339211AE2-254 GEN
Solar/Wind Harmer
2.125
339241AF1-083 GEN
Solar/Wind Harmer
1.597
970653AG2-424 GEN
Solar/Wind Harmer
4.417
964901AG1-354 GEN
Solar/Wind Harmer
12.634
25196008MFTGT1
Adder
1.057
25194608D.CRK4
Adder
1.116
252510AF1-249 C
Solar/Wind Harmer
0.264
253398AE2-221_GEN2
Solar/Wind Helper
3.664
253333AC1-068 GEN
Solar/Wind Helper
1.339
270520AE2-214 GEN
Solar/Wind Helper
1.493
270273AD2-016 GEN
Solar/Wind Helper
1.381
950051AG9-018
External Queue
14.513641357421875
950041AG9-017
External Queue
14.800519943237305
LAGNLTFEXP_LAGN->PJM
CLTF
6.902
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.204
TVALTFEXP_TVA->PJM
CLTF
3.913
NYPJM->LTFIMP_NY
CLTF
0.774
LGEELTFEXP_LGEE->PJM
CLTF
5.705
WECLTFEXP_WEC->PJM
CLTF
0.798
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.766
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.666
MECLTFEXP_MEC->PJM
CLTF
4.442
SIGELTFEXP_SIGE->PJM
CLTF
0.296
CPLELTFEXP_CPLE->PJM
CLTF
0.903
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.135
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 88.7 MW.

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1373_PORTUNION_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1373_PORTUNION_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.14 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1626.02
MW Contribution:
77.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972163AH1-664 GEN
Solar/Wind Harmer
35.056
972165AH1-665 GEN
Solar/Wind Harmer
28.045
339216AC1-074 GEN
Solar/Wind Harmer
4.116
3429211JKCT 2G
Adder
26.54
962211AG1-066 GEN
Solar/Wind Harmer
1.83
970281AG2-184 GEN
Solar/Wind Harmer
10.689
25196108MFTGT2
Adder
0.729
25196108MFTGT2
Adder
0.677
253338AC1-165 GEN
Solar/Wind Helper
1.023
253343AC1-166 GEN
Solar/Wind Helper
1.023
253406AD2-031_GEN
Solar/Wind Helper
0.903
945631AF1-228 GEN
Solar/Wind Helper
1.078
270340AC2-060 GEN
Solar/Wind Helper
1.06
3429631SPURLK3G
50/50
7.899
25197208MELDL3
50/50
0.684
958171AF2-111 GEN
Solar/Wind Harmer
104.309
972167AH1-666 GEN
Solar/Wind Harmer
29.068
339243AC2-075 GEN1
Solar/Wind Harmer
1.115
3429391JKCT 9G
Adder
20.063
970093AG2-073 GEN
Solar/Wind Harmer
10.362
972273AH1-721 GEN
Adder
91.729
339206AE1-143 GEN
Solar/Wind Harmer
2.259
970455AG2-298 GEN
Solar/Wind Harmer
3.596
970653AG2-424 GEN
Solar/Wind Harmer
0.627
339255AE2-071 GEN
Solar/Wind Harmer
0.876
339250AF1-203 GEN
Solar/Wind Harmer
0.451
270186AC1-089 GEN
Solar/Wind Harmer
4.264
972103AH1-617 GEN
Solar/Wind Harmer
10.18
25196008MFTGT1
Adder
0.64
253394AE2-221_GEN
Solar/Wind Helper
2.845
253325AC1-069 GEN
Solar/Wind Helper
1.06
270518AE2-148 GEN
Solar/Wind Helper
7.005
252507AC2-088 GEN
Solar/Wind Helper
0.736
3429601SPURLK2G
50/50
15.051
25197108MELDL2
50/50
0.689
972043AH1-570 GEN
Solar/Wind Harmer
6.04
972045AH1-571 GEN
Solar/Wind Harmer
4.832
971125AH1-004 GEN
Solar/Wind Harmer
9.66
970107AG2-081 GEN
Solar/Wind Harmer
7.245
942891AE2-308 GEN
Solar/Wind Harmer
21.138
339231AF1-038_GEN
Solar/Wind Harmer
1.725
339236AF1-050_GEN
Solar/Wind Harmer
1.543
964571AG1-320 GEN
Solar/Wind Harmer
6.934
966021AG1-471 GEN
Solar/Wind Harmer
4.381
971485AH1-239 GEN
Solar/Wind Harmer
6.435
964781AG1-341 GEN
Solar/Wind Harmer
7.632
25183208HLCRTG
Solar/Wind Helper
2.949
253415AE1-040 GEN
Solar/Wind Helper
0.531
946101AF1-275 GEN
Solar/Wind Helper
0.294
252509AD1-136 GEN
Solar/Wind Helper
0.105
241972AD1-140 GEN
Solar/Wind Helper
1.838
241955AC1-078 GEN
Solar/Wind Helper
0.93
3429661SPURLK4G
50/50
7.899
3429571SPURLK1G
50/50
7.935
25197008MELDL1
50/50
0.68
25196808ZIMRHP
50/50
216.614
945681AF1-233 GEN
Solar/Wind Harmer
68.028
943111AE2-339 GEN
Solar/Wind Harmer
2.141
3429421JKCT 10G
Adder
20.063
339221AD2-048_GEN
Solar/Wind Harmer
3.624
3429241JKCT 3G
Adder
26.889
339211AE2-254 GEN
Solar/Wind Harmer
2.221
339241AF1-083 GEN
Solar/Wind Harmer
1.605
970653AG2-424 GEN
Solar/Wind Harmer
4.338
964901AG1-354 GEN
Solar/Wind Harmer
12.527
25196008MFTGT1
Adder
0.661
253398AE2-221_GEN2
Solar/Wind Helper
2.845
253333AC1-068 GEN
Solar/Wind Helper
1.06
270520AE2-214 GEN
Solar/Wind Helper
1.175
950051AG9-018
External Queue
17.4936466217041
950041AG9-017
External Queue
17.633872985839844
LAGNLTFEXP_LAGN->PJM
CLTF
6.318
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.215
TVALTFEXP_TVA->PJM
CLTF
3.686
NYPJM->LTFIMP_NY
CLTF
0.654
LGEELTFEXP_LGEE->PJM
CLTF
5.166
WECLTFEXP_WEC->PJM
CLTF
0.598
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.791
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.436
MECLTFEXP_MEC->PJM
CLTF
3.587
SIGELTFEXP_SIGE->PJM
CLTF
0.255
CPLELTFEXP_CPLE->PJM
CLTF
0.943
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.569
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 91.73 MW.

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1493_RED BANK_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1493_RED BANK_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.1 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1610.06
MW Contribution:
77.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
8.108
25197208MELDL3
50/50
0.73
958171AF2-111 GEN
Solar/Wind Harmer
106.911
972167AH1-666 GEN
Solar/Wind Harmer
29.739
339243AC2-075 GEN1
Solar/Wind Harmer
1.12
3429391JKCT 9G
Adder
20.338
970093AG2-073 GEN
Solar/Wind Harmer
10.451
972273AH1-721 GEN
Adder
91.159
339206AE1-143 GEN
Solar/Wind Harmer
2.226
970455AG2-298 GEN
Solar/Wind Harmer
3.514
970653AG2-424 GEN
Solar/Wind Harmer
0.61
270186AC1-089 GEN
Solar/Wind Harmer
4.706
339255AE2-071 GEN
Solar/Wind Harmer
0.852
339250AF1-203 GEN
Solar/Wind Harmer
0.439
972103AH1-617 GEN
Solar/Wind Harmer
10.304
253394AE2-221_GEN
Solar/Wind Helper
2.61
253325AC1-069 GEN
Solar/Wind Helper
0.979
252507AC2-088 GEN
Solar/Wind Helper
0.879
270518AE2-148 GEN
Solar/Wind Helper
5.932
3429601SPURLK2G
50/50
15.451
25197108MELDL2
50/50
0.736
971125AH1-004 GEN
Solar/Wind Harmer
9.765
970107AG2-081 GEN
Solar/Wind Harmer
7.323
972043AH1-570 GEN
Solar/Wind Harmer
6.102
972045AH1-571 GEN
Solar/Wind Harmer
4.881
942891AE2-308 GEN
Solar/Wind Harmer
21.351
339231AF1-038_GEN
Solar/Wind Harmer
1.702
339236AF1-050_GEN
Solar/Wind Harmer
1.508
964571AG1-320 GEN
Solar/Wind Harmer
6.69
966021AG1-471 GEN
Solar/Wind Harmer
4.307
971485AH1-239 GEN
Solar/Wind Harmer
6.318
964781AG1-341 GEN
Solar/Wind Harmer
7.405
25183208HLCRTG
Solar/Wind Helper
2.518
252509AD1-136 GEN
Solar/Wind Helper
0.126
253415AE1-040 GEN
Solar/Wind Helper
0.462
972163AH1-664 GEN
Solar/Wind Harmer
35.849
972165AH1-665 GEN
Solar/Wind Harmer
28.679
339216AC1-074 GEN
Solar/Wind Harmer
4.134
3429211JKCT 2G
Adder
26.87
962211AG1-066 GEN
Solar/Wind Harmer
1.846
970281AG2-184 GEN
Solar/Wind Harmer
10.819
253338AC1-165 GEN
Solar/Wind Helper
0.945
253343AC1-166 GEN
Solar/Wind Helper
0.945
253406AD2-031_GEN
Solar/Wind Helper
0.782
945631AF1-228 GEN
Solar/Wind Helper
0.945
3429661SPURLK4G
50/50
8.108
3429571SPURLK1G
50/50
8.127
25197008MELDL1
50/50
0.726
25196808ZIMRHP
50/50
235.792
945681AF1-233 GEN
Solar/Wind Harmer
69.595
943111AE2-339 GEN
Solar/Wind Harmer
2.166
3429421JKCT 10G
Adder
20.338
339221AD2-048_GEN
Solar/Wind Harmer
3.648
3429241JKCT 3G
Adder
27.222
339211AE2-254 GEN
Solar/Wind Harmer
2.216
339241AF1-083 GEN
Solar/Wind Harmer
1.576
970653AG2-424 GEN
Solar/Wind Harmer
4.218
964901AG1-354 GEN
Solar/Wind Harmer
12.23
253398AE2-221_GEN2
Solar/Wind Helper
2.61
253333AC1-068 GEN
Solar/Wind Helper
0.979
950051AG9-018
External Queue
18.441604614257812
950041AG9-017
External Queue
18.613412857055664
LAGNLTFEXP_LAGN->PJM
CLTF
5.925
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.129
TVALTFEXP_TVA->PJM
CLTF
3.509
NYPJM->LTFIMP_NY
CLTF
0.603
LGEELTFEXP_LGEE->PJM
CLTF
4.842
WECLTFEXP_WEC->PJM
CLTF
0.494
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.619
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.574
MECLTFEXP_MEC->PJM
CLTF
3.122
SIGELTFEXP_SIGE->PJM
CLTF
0.232
CPLELTFEXP_CPLE->PJM
CLTF
0.937
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.691
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 91.16 MW.

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1487_RED BANK_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1487_RED BANK_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.05 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1609.33
MW Contribution:
77.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
8.108
25197208MELDL3
50/50
0.73
958171AF2-111 GEN
Solar/Wind Harmer
106.91
972167AH1-666 GEN
Solar/Wind Harmer
29.739
339243AC2-075 GEN1
Solar/Wind Harmer
1.12
3429391JKCT 9G
Adder
20.338
970093AG2-073 GEN
Solar/Wind Harmer
10.451
972273AH1-721 GEN
Adder
91.159
339206AE1-143 GEN
Solar/Wind Harmer
2.226
970455AG2-298 GEN
Solar/Wind Harmer
3.514
970653AG2-424 GEN
Solar/Wind Harmer
0.61
270186AC1-089 GEN
Solar/Wind Harmer
4.707
339255AE2-071 GEN
Solar/Wind Harmer
0.852
339250AF1-203 GEN
Solar/Wind Harmer
0.439
972103AH1-617 GEN
Solar/Wind Harmer
10.304
253394AE2-221_GEN
Solar/Wind Helper
2.61
253325AC1-069 GEN
Solar/Wind Helper
0.979
252507AC2-088 GEN
Solar/Wind Helper
0.878
270518AE2-148 GEN
Solar/Wind Helper
5.933
3429601SPURLK2G
50/50
15.451
25197108MELDL2
50/50
0.736
971125AH1-004 GEN
Solar/Wind Harmer
9.765
970107AG2-081 GEN
Solar/Wind Harmer
7.323
972043AH1-570 GEN
Solar/Wind Harmer
6.102
972045AH1-571 GEN
Solar/Wind Harmer
4.881
942891AE2-308 GEN
Solar/Wind Harmer
21.351
339231AF1-038_GEN
Solar/Wind Harmer
1.702
339236AF1-050_GEN
Solar/Wind Harmer
1.508
964571AG1-320 GEN
Solar/Wind Harmer
6.69
966021AG1-471 GEN
Solar/Wind Harmer
4.307
971485AH1-239 GEN
Solar/Wind Harmer
6.318
964781AG1-341 GEN
Solar/Wind Harmer
7.405
25183208HLCRTG
Solar/Wind Helper
2.518
252509AD1-136 GEN
Solar/Wind Helper
0.125
253415AE1-040 GEN
Solar/Wind Helper
0.462
972163AH1-664 GEN
Solar/Wind Harmer
35.849
972165AH1-665 GEN
Solar/Wind Harmer
28.679
339216AC1-074 GEN
Solar/Wind Harmer
4.134
3429211JKCT 2G
Adder
26.87
962211AG1-066 GEN
Solar/Wind Harmer
1.846
970281AG2-184 GEN
Solar/Wind Harmer
10.819
253338AC1-165 GEN
Solar/Wind Helper
0.945
253343AC1-166 GEN
Solar/Wind Helper
0.945
253406AD2-031_GEN
Solar/Wind Helper
0.782
945631AF1-228 GEN
Solar/Wind Helper
0.945
3429661SPURLK4G
50/50
8.108
3429571SPURLK1G
50/50
8.127
25197008MELDL1
50/50
0.726
25196808ZIMRHP
50/50
235.774
945681AF1-233 GEN
Solar/Wind Harmer
69.594
943111AE2-339 GEN
Solar/Wind Harmer
2.166
3429421JKCT 10G
Adder
20.338
339221AD2-048_GEN
Solar/Wind Harmer
3.648
3429241JKCT 3G
Adder
27.222
339211AE2-254 GEN
Solar/Wind Harmer
2.216
339241AF1-083 GEN
Solar/Wind Harmer
1.576
970653AG2-424 GEN
Solar/Wind Harmer
4.218
964901AG1-354 GEN
Solar/Wind Harmer
12.23
253398AE2-221_GEN2
Solar/Wind Helper
2.61
253333AC1-068 GEN
Solar/Wind Helper
0.979
950051AG9-018
External Queue
18.441471099853516
950041AG9-017
External Queue
18.61345100402832
LAGNLTFEXP_LAGN->PJM
CLTF
5.925
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.129
TVALTFEXP_TVA->PJM
CLTF
3.509
NYPJM->LTFIMP_NY
CLTF
0.603
LGEELTFEXP_LGEE->PJM
CLTF
4.842
WECLTFEXP_WEC->PJM
CLTF
0.494
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.616
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.573
MECLTFEXP_MEC->PJM
CLTF
3.121
SIGELTFEXP_SIGE->PJM
CLTF
0.232
CPLELTFEXP_CPLE->PJM
CLTF
0.937
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.689
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 91.16 MW.

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.96 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1608.02
MW Contribution:
77.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972163AH1-664 GEN
Solar/Wind Harmer
35.852
972165AH1-665 GEN
Solar/Wind Harmer
28.681
339216AC1-074 GEN
Solar/Wind Harmer
4.135
3429211JKCT 2G
Adder
26.873
962211AG1-066 GEN
Solar/Wind Harmer
1.847
970281AG2-184 GEN
Solar/Wind Harmer
10.819
253338AC1-165 GEN
Solar/Wind Helper
0.945
253343AC1-166 GEN
Solar/Wind Helper
0.945
253406AD2-031_GEN
Solar/Wind Helper
0.782
945631AF1-228 GEN
Solar/Wind Helper
0.944
3429661SPURLK4G
50/50
8.109
3429571SPURLK1G
50/50
8.128
25197008MELDL1
50/50
0.726
25196808ZIMRHP
50/50
235.827
945681AF1-233 GEN
Solar/Wind Harmer
69.6
943111AE2-339 GEN
Solar/Wind Harmer
2.166
3429421JKCT 10G
Adder
20.341
339221AD2-048_GEN
Solar/Wind Harmer
3.648
3429241JKCT 3G
Adder
27.226
339211AE2-254 GEN
Solar/Wind Harmer
2.217
339241AF1-083 GEN
Solar/Wind Harmer
1.576
970653AG2-424 GEN
Solar/Wind Harmer
4.22
964901AG1-354 GEN
Solar/Wind Harmer
12.233
253398AE2-221_GEN2
Solar/Wind Helper
2.61
253333AC1-068 GEN
Solar/Wind Helper
0.979
3429631SPURLK3G
50/50
8.109
25197208MELDL3
50/50
0.73
958171AF2-111 GEN
Solar/Wind Harmer
106.917
972167AH1-666 GEN
Solar/Wind Harmer
29.741
339243AC2-075 GEN1
Solar/Wind Harmer
1.12
3429391JKCT 9G
Adder
20.341
970093AG2-073 GEN
Solar/Wind Harmer
10.453
972273AH1-721 GEN
Adder
91.178
339206AE1-143 GEN
Solar/Wind Harmer
2.227
970455AG2-298 GEN
Solar/Wind Harmer
3.515
970653AG2-424 GEN
Solar/Wind Harmer
0.61
270186AC1-089 GEN
Solar/Wind Harmer
4.707
339255AE2-071 GEN
Solar/Wind Harmer
0.853
339250AF1-203 GEN
Solar/Wind Harmer
0.439
972103AH1-617 GEN
Solar/Wind Harmer
10.304
253394AE2-221_GEN
Solar/Wind Helper
2.61
253325AC1-069 GEN
Solar/Wind Helper
0.979
252507AC2-088 GEN
Solar/Wind Helper
0.886
270518AE2-148 GEN
Solar/Wind Helper
5.931
3429601SPURLK2G
50/50
15.452
25197108MELDL2
50/50
0.736
971125AH1-004 GEN
Solar/Wind Harmer
9.766
970107AG2-081 GEN
Solar/Wind Harmer
7.324
972043AH1-570 GEN
Solar/Wind Harmer
6.103
972045AH1-571 GEN
Solar/Wind Harmer
4.882
942891AE2-308 GEN
Solar/Wind Harmer
21.354
339231AF1-038_GEN
Solar/Wind Harmer
1.703
339236AF1-050_GEN
Solar/Wind Harmer
1.508
964571AG1-320 GEN
Solar/Wind Harmer
6.692
966021AG1-471 GEN
Solar/Wind Harmer
4.308
971485AH1-239 GEN
Solar/Wind Harmer
6.32
964781AG1-341 GEN
Solar/Wind Harmer
7.407
25183208HLCRTG
Solar/Wind Helper
2.519
252509AD1-136 GEN
Solar/Wind Helper
0.127
253415AE1-040 GEN
Solar/Wind Helper
0.462
950051AG9-018
External Queue
18.440826416015625
950041AG9-017
External Queue
18.613161087036133
LAGNLTFEXP_LAGN->PJM
CLTF
5.927
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.129
TVALTFEXP_TVA->PJM
CLTF
3.51
NYPJM->LTFIMP_NY
CLTF
0.603
LGEELTFEXP_LGEE->PJM
CLTF
4.844
WECLTFEXP_WEC->PJM
CLTF
0.494
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.634
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.579
MECLTFEXP_MEC->PJM
CLTF
3.124
SIGELTFEXP_SIGE->PJM
CLTF
0.232
CPLELTFEXP_CPLE->PJM
CLTF
0.937
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.712
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 91.18 MW.

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.95 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1607.79
MW Contribution:
77.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
8.108
25197208MELDL3
50/50
0.73
958171AF2-111 GEN
Solar/Wind Harmer
106.907
972167AH1-666 GEN
Solar/Wind Harmer
29.739
339243AC2-075 GEN1
Solar/Wind Harmer
1.12
3429391JKCT 9G
Adder
20.338
970093AG2-073 GEN
Solar/Wind Harmer
10.451
972273AH1-721 GEN
Adder
91.166
339206AE1-143 GEN
Solar/Wind Harmer
2.226
970455AG2-298 GEN
Solar/Wind Harmer
3.514
970653AG2-424 GEN
Solar/Wind Harmer
0.61
270186AC1-089 GEN
Solar/Wind Harmer
4.707
339255AE2-071 GEN
Solar/Wind Harmer
0.852
339250AF1-203 GEN
Solar/Wind Harmer
0.439
972103AH1-617 GEN
Solar/Wind Harmer
10.305
253394AE2-221_GEN
Solar/Wind Helper
2.611
253325AC1-069 GEN
Solar/Wind Helper
0.979
252507AC2-088 GEN
Solar/Wind Helper
0.876
270518AE2-148 GEN
Solar/Wind Helper
5.934
3429601SPURLK2G
50/50
15.45
25197108MELDL2
50/50
0.736
971125AH1-004 GEN
Solar/Wind Harmer
9.765
970107AG2-081 GEN
Solar/Wind Harmer
7.324
972043AH1-570 GEN
Solar/Wind Harmer
6.102
972045AH1-571 GEN
Solar/Wind Harmer
4.882
942891AE2-308 GEN
Solar/Wind Harmer
21.351
339231AF1-038_GEN
Solar/Wind Harmer
1.702
339236AF1-050_GEN
Solar/Wind Harmer
1.508
964571AG1-320 GEN
Solar/Wind Harmer
6.691
966021AG1-471 GEN
Solar/Wind Harmer
4.307
971485AH1-239 GEN
Solar/Wind Harmer
6.319
964781AG1-341 GEN
Solar/Wind Harmer
7.406
972163AH1-664 GEN
Solar/Wind Harmer
35.848
972165AH1-665 GEN
Solar/Wind Harmer
28.679
339216AC1-074 GEN
Solar/Wind Harmer
4.134
3429211JKCT 2G
Adder
26.87
962211AG1-066 GEN
Solar/Wind Harmer
1.847
970281AG2-184 GEN
Solar/Wind Harmer
10.82
253338AC1-165 GEN
Solar/Wind Helper
0.945
253343AC1-166 GEN
Solar/Wind Helper
0.945
253406AD2-031_GEN
Solar/Wind Helper
0.782
945631AF1-228 GEN
Solar/Wind Helper
0.945
3429661SPURLK4G
50/50
8.108
3429571SPURLK1G
50/50
8.127
25197008MELDL1
50/50
0.726
25196808ZIMRHP
50/50
235.731
945681AF1-233 GEN
Solar/Wind Harmer
69.594
943111AE2-339 GEN
Solar/Wind Harmer
2.166
3429421JKCT 10G
Adder
20.338
339221AD2-048_GEN
Solar/Wind Harmer
3.648
3429241JKCT 3G
Adder
27.223
339211AE2-254 GEN
Solar/Wind Harmer
2.216
339241AF1-083 GEN
Solar/Wind Harmer
1.576
970653AG2-424 GEN
Solar/Wind Harmer
4.219
964901AG1-354 GEN
Solar/Wind Harmer
12.231
253398AE2-221_GEN2
Solar/Wind Helper
2.611
253333AC1-068 GEN
Solar/Wind Helper
0.979
25183208HLCRTG
Solar/Wind Helper
2.518
252509AD1-136 GEN
Solar/Wind Helper
0.125
253415AE1-040 GEN
Solar/Wind Helper
0.462
950051AG9-018
External Queue
18.440135955810547
950041AG9-017
External Queue
18.612449645996094
LAGNLTFEXP_LAGN->PJM
CLTF
5.926
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.131
TVALTFEXP_TVA->PJM
CLTF
3.509
NYPJM->LTFIMP_NY
CLTF
0.603
LGEELTFEXP_LGEE->PJM
CLTF
4.843
WECLTFEXP_WEC->PJM
CLTF
0.494
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.615
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.576
MECLTFEXP_MEC->PJM
CLTF
3.121
SIGELTFEXP_SIGE->PJM
CLTF
0.232
CPLELTFEXP_CPLE->PJM
CLTF
0.938
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.692
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 91.17 MW.

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.93 %
Rating:1240.0 MVA
Rating Type:A
MVA to Mitigate:1301.17
MW Contribution:
73.77
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972163AH1-664 GEN
Solar/Wind Harmer
25.864
972165AH1-665 GEN
Solar/Wind Harmer
20.714
339216AC1-074 GEN
Solar/Wind Harmer
0.434
3429211JKCT 2G
Adder
25.2
970281AG2-184 GEN
Solar/Wind Harmer
7.039
25196108MFTGT2
Adder
0.689
25196108MFTGT2
Adder
0.64
253338AC1-165 GEN
Solar/Wind Helper
1.016
253343AC1-166 GEN
Solar/Wind Helper
1.016
253406AD2-031_GEN
Solar/Wind Helper
0.85
945631AF1-228 GEN
Solar/Wind Helper
0.992
270340AC2-060 GEN
Solar/Wind Helper
0.994
3429601SPURLK2G
50/50
14.29
25197108MELDL2
50/50
0.548
972043AH1-570 GEN
Solar/Wind Harmer
4.163
972045AH1-571 GEN
Solar/Wind Harmer
3.336
971125AH1-004 GEN
Solar/Wind Harmer
6.399
970107AG2-081 GEN
Solar/Wind Harmer
4.799
942891AE2-308 GEN
Solar/Wind Harmer
14.003
964571AG1-320 GEN
Solar/Wind Harmer
5.122
966021AG1-471 GEN
Solar/Wind Harmer
2.901
971485AH1-239 GEN
Solar/Wind Harmer
4.261
964781AG1-341 GEN
Solar/Wind Harmer
5.057
25183208HLCRTG
Solar/Wind Helper
2.669
253415AE1-040 GEN
Solar/Wind Helper
0.5
252509AD1-136 GEN
Solar/Wind Helper
0.106
946101AF1-275 GEN
Solar/Wind Helper
0.279
3429661SPURLK4G
50/50
7.499
3429571SPURLK1G
50/50
7.535
25197008MELDL1
50/50
0.54
945681AF1-233 GEN
Solar/Wind Harmer
45.077
3429421JKCT 10G
Adder
19.05
3429241JKCT 3G
Adder
25.531
25196808ZIMRHP
Adder
146.641
970653AG2-424 GEN
Solar/Wind Harmer
2.876
964901AG1-354 GEN
Solar/Wind Harmer
8.3
25196008MFTGT1
Adder
0.625
253398AE2-221_GEN2
Solar/Wind Helper
2.816
253333AC1-068 GEN
Solar/Wind Helper
1.053
270520AE2-214 GEN
Solar/Wind Helper
1.117
3429631SPURLK3G
50/50
7.499
25197208MELDL3
50/50
0.543
958171AF2-111 GEN
Solar/Wind Harmer
69.096
972167AH1-666 GEN
Solar/Wind Harmer
19.261
3429391JKCT 9G
Adder
19.05
970093AG2-073 GEN
Solar/Wind Harmer
10.983
972273AH1-721 GEN
Adder
87.068
970455AG2-298 GEN
Solar/Wind Harmer
2.649
970653AG2-424 GEN
Solar/Wind Harmer
0.596
270186AC1-089 GEN
Solar/Wind Harmer
0
972103AH1-617 GEN
Solar/Wind Harmer
6.704
25196008MFTGT1
Adder
0.605
253394AE2-221_GEN
Solar/Wind Helper
2.816
253325AC1-069 GEN
Solar/Wind Helper
1.053
270518AE2-148 GEN
Solar/Wind Helper
6.196
252507AC2-088 GEN
Solar/Wind Helper
0.745
950051AG9-018
External Queue
16.602676391601562
950041AG9-017
External Queue
16.80695915222168
LAGNLTFEXP_LAGN->PJM
CLTF
5.986
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.932
TVALTFEXP_TVA->PJM
CLTF
3.49
NYPJM->LTFIMP_NY
CLTF
0.629
LGEELTFEXP_LGEE->PJM
CLTF
4.921
WECLTFEXP_WEC->PJM
CLTF
0.575
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.28
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.592
MECLTFEXP_MEC->PJM
CLTF
3.424
SIGELTFEXP_SIGE->PJM
CLTF
0.243
CPLELTFEXP_CPLE->PJM
CLTF
0.869
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.388
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 87.07 MW.

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o EKPC_P2-2_MELD-SPUR 345_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_MELD-SPUR 345_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.1 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1579.46
MW Contribution:
88.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
9.793
958171AF2-111 GEN
Solar/Wind Harmer
128.831
972167AH1-666 GEN
Solar/Wind Harmer
35.75
339243AC2-075 GEN1
Solar/Wind Harmer
1.316
3429391JKCT 9G
Adder
24.115
970093AG2-073 GEN
Solar/Wind Harmer
12.299
972273AH1-721 GEN
Adder
104.883
339206AE1-143 GEN
Solar/Wind Harmer
2.52
970455AG2-298 GEN
Solar/Wind Harmer
3.911
970653AG2-424 GEN
Solar/Wind Harmer
0.673
270186AC1-089 GEN
Solar/Wind Harmer
5.496
339255AE2-071 GEN
Solar/Wind Harmer
0.943
339250AF1-203 GEN
Solar/Wind Harmer
0.486
972103AH1-617 GEN
Solar/Wind Harmer
12.486
971461AH1-227 GEN
Solar/Wind Harmer
2.283
253394AE2-221_GEN
Solar/Wind Helper
2.188
253325AC1-069 GEN
Solar/Wind Helper
0.822
252507AC2-088 GEN
Solar/Wind Helper
0.99
270518AE2-148 GEN
Solar/Wind Helper
6.07
972163AH1-664 GEN
Solar/Wind Harmer
43.062
972165AH1-665 GEN
Solar/Wind Harmer
34.449
339216AC1-074 GEN
Solar/Wind Harmer
4.861
3429211JKCT 2G
Adder
31.801
962211AG1-066 GEN
Solar/Wind Harmer
2.202
970281AG2-184 GEN
Solar/Wind Harmer
13.111
253338AC1-165 GEN
Solar/Wind Helper
0.794
253343AC1-166 GEN
Solar/Wind Helper
0.794
253406AD2-031_GEN
Solar/Wind Helper
0.679
945631AF1-228 GEN
Solar/Wind Helper
0.912
3429661SPURLK4G
50/50
9.793
3429571SPURLK1G
50/50
9.787
945681AF1-233 GEN
Solar/Wind Harmer
83.653
943111AE2-339 GEN
Solar/Wind Harmer
2.562
3429421JKCT 10G
Adder
24.115
339221AD2-048_GEN
Solar/Wind Harmer
4.291
3429241JKCT 3G
Adder
32.219
339211AE2-254 GEN
Solar/Wind Harmer
2.564
339241AF1-083 GEN
Solar/Wind Harmer
1.773
970653AG2-424 GEN
Solar/Wind Harmer
4.655
964901AG1-354 GEN
Solar/Wind Harmer
13.62
971687AH1-348 GEN
Solar/Wind Harmer
0.461
253398AE2-221_GEN2
Solar/Wind Helper
2.188
253333AC1-068 GEN
Solar/Wind Helper
0.822
3429601SPURLK2G
50/50
18.661
971125AH1-004 GEN
Solar/Wind Harmer
11.542
970107AG2-081 GEN
Solar/Wind Harmer
8.656
972043AH1-570 GEN
Solar/Wind Harmer
7.207
972045AH1-571 GEN
Solar/Wind Harmer
5.765
942891AE2-308 GEN
Solar/Wind Harmer
25.183
339231AF1-038_GEN
Solar/Wind Harmer
1.935
339236AF1-050_GEN
Solar/Wind Harmer
1.681
966021AG1-471 GEN
Solar/Wind Harmer
4.866
971485AH1-239 GEN
Solar/Wind Harmer
7.124
964571AG1-320 GEN
Solar/Wind Harmer
7.265
964781AG1-341 GEN
Solar/Wind Harmer
8.157
971225AH1-072 GEN
Solar/Wind Harmer
0.89
971227AH1-073 GEN
Solar/Wind Harmer
0.89
25183208HLCRTG
Solar/Wind Helper
2.416
252509AD1-136 GEN
Solar/Wind Helper
0.141
950051AG9-018
External Queue
23.243040084838867
950041AG9-017
External Queue
23.32491683959961
950011AG9-010
External Queue
6.111148357391357
LAGNLTFEXP_LAGN->PJM
CLTF
6.165
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5
TVALTFEXP_TVA->PJM
CLTF
3.771
NYPJM->LTFIMP_NY
CLTF
0.532
LGEELTFEXP_LGEE->PJM
CLTF
4.958
WECLTFEXP_WEC->PJM
CLTF
0.339
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.357
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.494
MECLTFEXP_MEC->PJM
CLTF
2.621
SIGELTFEXP_SIGE->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
1.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.182
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 104.88 MW.

Details for AE1-108 POI-4BREMO 138.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
AE1-108 POI-4BREMO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:178.27 %
Rating:156.98 MVA
Rating Type:B
MVA to Mitigate:279.84
MW Contribution:
7.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274728ELWOOD EC;5P
Adder
1.266
274731ELWOOD EC;2P
Adder
1.266
274733ELWOOD EC;3P
Adder
1.266
274735ELWOOD EC;4P
Adder
1.266
274675JOLIET 29;7U
Adder
2.361
274675JOLIET 29;7U
Adder
2.277
942671AE2-283 GEN
Solar/Wind Harmer
1.407
24288905REUSENS
50/50
0.018
962751AG1-124 GEN
Solar/Wind Harmer
6.519
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.809
972273AH1-721 GEN
Adder
7.866
274729ELWOOD EC;1P
Adder
1.266
274730ELWOOD EC;6P
Adder
1.266
274734ELWOOD EC;8P
Adder
1.266
274736ELWOOD EC;9P
Adder
1.266
274676JOLIET 29;8U
Adder
2.277
270494AE1-108_GEN
Solar/Wind Harmer
9.502
958131AF2-107 GEN
Solar/Wind Harmer
9.389
3147312GRETNA
Solar/Wind Harmer
0.011
274732ELWOOD EC;7P
Adder
1.266
274676JOLIET 29;8U
Adder
2.361
315821AE2-092 GEN
Solar/Wind Helper
1.51
LAGNLTFEXP_LAGN->PJM
CLTF
1.739
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.914
TVALTFEXP_TVA->PJM
CLTF
0.915
NYPJM->LTFIMP_NY
CLTF
0.286
LGEELTFEXP_LGEE->PJM
CLTF
0.593
WECLTFEXP_WEC->PJM
CLTF
0.298
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.844
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.402
MECLTFEXP_MEC->PJM
CLTF
1.353
SIGELTFEXP_SIGE->PJM
CLTF
0.045
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.362

Details for AE2-254 POI-2GARRARD CO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AE2-254 POI-2GARRARD CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:118.85 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:74.87
MW Contribution:
27.82
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339211AE2-254 GEN
Solar/Wind Harmer
10.41
972273AH1-721 GEN
Adder
32.851
339231AF1-038_GEN
Solar/Wind Harmer
0.941
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.041
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.097
LAGNLTFEXP_LAGN->PJM
CLTF
0.361
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.27
TVALTFEXP_TVA->PJM
CLTF
0.255
NYPJM->LTFIMP_NY
CLTF
0.011
WECLTFEXP_WEC->PJM
CLTF
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.14
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.685
MECLTFEXP_MEC->PJM
CLTF
0.091
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.069
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.575
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 32.85 MW.

Details for AE2-254 POI-2GARRARD CO 69.0 kV Ckt 1 line l/o EKPC_P2-3_MAR W38-1004_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AE2-254 POI-2GARRARD CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_MAR W38-1004_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.2 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:65.65
MW Contribution:
20.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339206AE1-143 GEN
Solar/Wind Harmer
2.137
972273AH1-721 GEN
Adder
24.073
339231AF1-038_GEN
Solar/Wind Harmer
0.98
339211AE2-254 GEN
Solar/Wind Harmer
10.48
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.083
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.247
LAGNLTFEXP_LAGN->PJM
CLTF
0.263
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.278
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.195
NYPJM->LTFIMP_NY
CLTF
0.008
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.453
MECLTFEXP_MEC->PJM
CLTF
0.02
CPLELTFEXP_CPLE->PJM
CLTF
0.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.847
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 24.07 MW.

Details for AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line l/o EKPC_P2-2_TVA WAYNE 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_TVA WAYNE 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.32 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:54.17
MW Contribution:
10.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
Adder
10.297
971485AH1-239 GEN
Solar/Wind Harmer
29.16
966021AG1-471 GEN
Solar/Wind Harmer
16.565
339255AE2-071 GEN
Solar/Wind Helper
0.144
339250AF1-203 GEN
Solar/Wind Helper
0.111
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.028
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.108
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.036
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.004
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.216
G-007ALTFEXP_G-007A->PJM
CMTX
0.013
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.026
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-DEN161_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-DEN161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:188.88 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:562.87
MW Contribution:
625.96
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.104
966021AG1-471 GEN
Solar/Wind Harmer
2.141
971485AH1-239 GEN
Solar/Wind Harmer
2.726
339231AF1-038_GEN
Solar/Wind Helper
0.353
972273AH1-721 GEN
50/50
625.96
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.17
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.579
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.017
GibsonPJM->LTFIMP_GIBSON
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.145
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.459
G-007ALTFEXP_G-007A->PJM
CMTX
0.054
CPLELTFEXP_CPLE->PJM
CLTF
0.014
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.104
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-DEN161_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-DEN161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:185.85 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:553.84
MW Contribution:
625.96
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
625.96

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.15 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:405.72
MW Contribution:
373.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.882
966021AG1-471 GEN
Solar/Wind Harmer
2.749
971485AH1-239 GEN
Solar/Wind Harmer
3.667
972273AH1-721 GEN
50/50
373.157
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.119
LAGNLTFEXP_LAGN->PJM
CLTF
0.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.154
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.129
NYPJM->LTFIMP_NY
CLTF
0.007
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.342
MECLTFEXP_MEC->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
0.038
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.662

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:136.15 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:405.71
MW Contribution:
373.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
373.146
3429451LAUREL 1G
50/50
1.882
966021AG1-471 GEN
Solar/Wind Harmer
2.749
971485AH1-239 GEN
Solar/Wind Harmer
3.666
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.119
LAGNLTFEXP_LAGN->PJM
CLTF
0.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.154
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.129
NYPJM->LTFIMP_NY
CLTF
0.007
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.342
MECLTFEXP_MEC->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
0.038
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.661

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.14 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:405.7
MW Contribution:
373.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
373.157
3429451LAUREL 1G
50/50
1.882
966021AG1-471 GEN
Solar/Wind Harmer
2.749
971485AH1-239 GEN
Solar/Wind Harmer
3.667
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.119
LAGNLTFEXP_LAGN->PJM
CLTF
0.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.154
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.129
NYPJM->LTFIMP_NY
CLTF
0.007
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.342
MECLTFEXP_MEC->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
0.038
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.662

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:136.14 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:405.7
MW Contribution:
373.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
373.157
3429451LAUREL 1G
50/50
1.882
966021AG1-471 GEN
Solar/Wind Harmer
2.749
971485AH1-239 GEN
Solar/Wind Harmer
3.667
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.119
LAGNLTFEXP_LAGN->PJM
CLTF
0.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.154
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.129
NYPJM->LTFIMP_NY
CLTF
0.007
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.342
MECLTFEXP_MEC->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
0.038
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.662

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:136.07 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:405.5
MW Contribution:
373.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
373.165
3429451LAUREL 1G
50/50
1.882
966021AG1-471 GEN
Solar/Wind Harmer
2.75
971485AH1-239 GEN
Solar/Wind Harmer
3.667
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.119
LAGNLTFEXP_LAGN->PJM
CLTF
0.183
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.155
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.13
NYPJM->LTFIMP_NY
CLTF
0.007
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.343
MECLTFEXP_MEC->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
0.039
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.663

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.49 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:403.77
MW Contribution:
373.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.882
966021AG1-471 GEN
Solar/Wind Harmer
1.918
971485AH1-239 GEN
Solar/Wind Harmer
2.558
972273AH1-721 GEN
50/50
373.146
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.119
LAGNLTFEXP_LAGN->PJM
CLTF
0.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.154
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.129
NYPJM->LTFIMP_NY
CLTF
0.007
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.342
MECLTFEXP_MEC->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
0.038
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.661

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:132.76 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:395.63
MW Contribution:
373.15
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
373.146

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.76 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:395.63
MW Contribution:
373.15
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
373.146

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.76 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:395.63
MW Contribution:
373.16
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
373.157

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:132.76 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:395.61
MW Contribution:
373.16
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
373.157

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.76 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:395.61
MW Contribution:
373.16
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
373.157

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:132.69 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:395.41
MW Contribution:
373.17
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
373.165

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.99 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:330.75
MW Contribution:
349.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
349.922
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.031
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.102
LAGNLTFEXP_LAGN->PJM
CLTF
0.113
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.164
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.072
WECLTFEXP_WEC->PJM
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.099
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.018
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.18
MECLTFEXP_MEC->PJM
CLTF
0.017
G-007ALTFEXP_G-007A->PJM
CMTX
0.037
CPLELTFEXP_CPLE->PJM
CLTF
0.048
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.068
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.363

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.55 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:329.44
MW Contribution:
349.92
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
349.922

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.05 %
Rating:267.0 MVA
Rating Type:A
MVA to Mitigate:291.18
MW Contribution:
326.77
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
326.769
3429451LAUREL 1G
50/50
1.098
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.089
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.302
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.009
GibsonPJM->LTFIMP_GIBSON
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.076
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.239
G-007ALTFEXP_G-007A->PJM
CMTX
0.028
CPLELTFEXP_CPLE->PJM
CLTF
0.007
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.054
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.31 %
Rating:267.0 MVA
Rating Type:A
MVA to Mitigate:289.19
MW Contribution:
326.77
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
326.769

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-LAUREL161_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:263.5 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:553.35
MW Contribution:
625.42
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
625.42

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:205.12 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:430.76
MW Contribution:
523.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
523.015
339206AE1-143 GEN
Solar/Wind Helper
1.373
3429451LAUREL 1G
50/50
1.772
339231AF1-038_GEN
Solar/Wind Helper
0.629
339236AF1-050_GEN
Solar/Wind Helper
0.367
339241AF1-083 GEN
Solar/Wind Helper
0.403
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.162
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.59
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.359
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.856
G-007ALTFEXP_G-007A->PJM
CMTX
0.134
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.27
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:201.74 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:423.66
MW Contribution:
523.01
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
523.015

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:177.18 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:372.09
MW Contribution:
345.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
345.366
3429451LAUREL 1G
50/50
1.742
966021AG1-471 GEN
Solar/Wind Harmer
2.544
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.037
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.11
LAGNLTFEXP_LAGN->PJM
CLTF
0.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.143
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.12
NYPJM->LTFIMP_NY
CLTF
0.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.316
MECLTFEXP_MEC->PJM
CLTF
0.026
CPLELTFEXP_CPLE->PJM
CLTF
0.036
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.611

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-3_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-3_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:177.18 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:372.08
MW Contribution:
345.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.742
966021AG1-471 GEN
Solar/Wind Harmer
2.545
972273AH1-721 GEN
50/50
345.377
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.037
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.11
LAGNLTFEXP_LAGN->PJM
CLTF
0.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.143
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.12
NYPJM->LTFIMP_NY
CLTF
0.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.026
CPLELTFEXP_CPLE->PJM
CLTF
0.036
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.613

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P4-5_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P4-5_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:177.18 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:372.07
MW Contribution:
345.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.742
966021AG1-471 GEN
Solar/Wind Harmer
2.545
972273AH1-721 GEN
50/50
345.377
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.037
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.11
LAGNLTFEXP_LAGN->PJM
CLTF
0.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.143
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.12
NYPJM->LTFIMP_NY
CLTF
0.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.026
CPLELTFEXP_CPLE->PJM
CLTF
0.036
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.613

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:177.18 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:372.07
MW Contribution:
345.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
345.377
3429451LAUREL 1G
50/50
1.742
966021AG1-471 GEN
Solar/Wind Harmer
2.545
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.037
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.11
LAGNLTFEXP_LAGN->PJM
CLTF
0.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.143
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.12
NYPJM->LTFIMP_NY
CLTF
0.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.026
CPLELTFEXP_CPLE->PJM
CLTF
0.036
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.613

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:177.09 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:371.88
MW Contribution:
345.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.742
966021AG1-471 GEN
Solar/Wind Harmer
2.545
972273AH1-721 GEN
50/50
345.384
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.037
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.11
LAGNLTFEXP_LAGN->PJM
CLTF
0.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.143
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.12
NYPJM->LTFIMP_NY
CLTF
0.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.026
CPLELTFEXP_CPLE->PJM
CLTF
0.036
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.614

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:176.82 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:371.32
MW Contribution:
345.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.742
966021AG1-471 GEN
Solar/Wind Harmer
1.775
972273AH1-721 GEN
50/50
345.366
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.037
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.11
LAGNLTFEXP_LAGN->PJM
CLTF
0.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.143
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.12
NYPJM->LTFIMP_NY
CLTF
0.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.316
MECLTFEXP_MEC->PJM
CLTF
0.026
CPLELTFEXP_CPLE->PJM
CLTF
0.036
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.611

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:174.36 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:366.15
MW Contribution:
345.37
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
345.366

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:174.36 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:366.15
MW Contribution:
345.37
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
345.366

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-3_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-3_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.35 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:366.14
MW Contribution:
345.38
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
345.377

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P4-5_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P4-5_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.35 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:366.13
MW Contribution:
345.38
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
345.377

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:174.35 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:366.13
MW Contribution:
345.38
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
345.377

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:174.25 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:365.94
MW Contribution:
345.38
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
345.384

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:144.88 %
Rating:186.0 MVA
Rating Type:A
MVA to Mitigate:269.48
MW Contribution:
302.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
302.442
3429451LAUREL 1G
50/50
1.017
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.082
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.008
GibsonPJM->LTFIMP_GIBSON
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.222
G-007ALTFEXP_G-007A->PJM
CMTX
0.026
CPLELTFEXP_CPLE->PJM
CLTF
0.007
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.05
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.89 %
Rating:186.0 MVA
Rating Type:A
MVA to Mitigate:267.63
MW Contribution:
302.44
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
302.442

Details for AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:143.93 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:302.26
MW Contribution:
282.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
282.813
3429451LAUREL 1G
50/50
0.955
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.108
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.003
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.056
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.081
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.555
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.93 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:302.25
MW Contribution:
282.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.955
972273AH1-721 GEN
50/50
282.813
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.108
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.003
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.056
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.081
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.555
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.53 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:301.42
MW Contribution:
281.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.948
972273AH1-721 GEN
50/50
281.003
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.088
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.004
LGEELTFEXP_LGEE->PJM
CLTF
0.002
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.057
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.083
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.538
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:142.74 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:299.75
MW Contribution:
282.81
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
282.813

Details for [AH1-721] AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.74 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:299.75
MW Contribution:
282.81
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
282.813

Details for [AH1-721] AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.38 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:299.0
MW Contribution:
281.0
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
281.003

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:254.75 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:759.16
MW Contribution:
758.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
758.949
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:254.75 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:759.16
MW Contribution:
758.95
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
758.949

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:176.07 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:524.69
MW Contribution:
477.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
477.946
966021AG1-471 GEN
Solar/Wind Harmer
4.456
971485AH1-239 GEN
Solar/Wind Harmer
6.047
LAGNLTFEXP_LAGN->PJM
CLTF
0.595
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.445
TVALTFEXP_TVA->PJM
CLTF
0.401
WECLTFEXP_WEC->PJM
CLTF
0.029
VTFLTFEXP_VFT->PJM
CMTX
0.061
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.997
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.233
MECLTFEXP_MEC->PJM
CLTF
0.22
SIGELTFEXP_SIGE->PJM
CLTF
0.006
G-007ALTFEXP_G-007A->PJM
CMTX
0.023
CPLELTFEXP_CPLE->PJM
CLTF
0.119
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.032
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.906

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.36 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:522.59
MW Contribution:
476.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
4.424
971485AH1-239 GEN
Solar/Wind Harmer
6.011
972273AH1-721 GEN
50/50
476.137
LAGNLTFEXP_LAGN->PJM
CLTF
0.601
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.435
TVALTFEXP_TVA->PJM
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.005
WECLTFEXP_WEC->PJM
CLTF
0.03
VTFLTFEXP_VFT->PJM
CMTX
0.051
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.043
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.25
MECLTFEXP_MEC->PJM
CLTF
0.226
SIGELTFEXP_SIGE->PJM
CLTF
0.007
G-007ALTFEXP_G-007A->PJM
CMTX
0.019
CPLELTFEXP_CPLE->PJM
CLTF
0.116
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.967

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:175.36 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:522.58
MW Contribution:
476.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
476.137
966021AG1-471 GEN
Solar/Wind Harmer
4.424
971485AH1-239 GEN
Solar/Wind Harmer
6.011
LAGNLTFEXP_LAGN->PJM
CLTF
0.601
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.435
TVALTFEXP_TVA->PJM
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.005
WECLTFEXP_WEC->PJM
CLTF
0.03
VTFLTFEXP_VFT->PJM
CMTX
0.051
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.043
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.25
MECLTFEXP_MEC->PJM
CLTF
0.226
SIGELTFEXP_SIGE->PJM
CLTF
0.007
G-007ALTFEXP_G-007A->PJM
CMTX
0.019
CPLELTFEXP_CPLE->PJM
CLTF
0.116
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.967

Details for [AH1-721] AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:170.17 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:507.11
MW Contribution:
477.95
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
477.946

Details for [AH1-721] AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:169.45 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:504.96
MW Contribution:
476.14
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
476.137

Details for [AH1-721] AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:169.45 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:504.96
MW Contribution:
476.14
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
476.137
CONTINGENCY 'AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AEP_P4_#8075_05MARYSV 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#17219_05GUERNSEY 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 246751 CKT 1    /*05GUERNSEY   765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#10944___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242940 TO BUS 242947 CKT 1   /*05MUSKNG     345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'AEP_P7-1_#10856___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242528 TO BUS 242947 CKT 1   /*05SPORN      345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P1-2_#309_15_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1064_SRT-A'
 OPEN BRANCH FROM BUS 341392 TO BUS 342727 CKT 1   /*2DENNY        69.0 - 5DENNY       161.0
 OPEN BUS 342718                                   /*5COOPER2     161.0
 OPEN BUS 342903                                   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1039_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342900   /*1COOPER1 G    13.8
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-210G_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-2_COOPER 2 161_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 2_SRT-A-2'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-ELIHU161_SRT-A'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P2-2_ELIHU-COOP 161_SRT-A'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 2_SRT-A-1'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 1   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EKPC_P1-2_COOP 161 TIE_SRT-A'
 OPEN BRANCH FROM BUS 342715 TO BUS 342718 CKT 1   /*5COOPER1     161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P2-2_SUMMSHADE 161 #2_SRT-A'
 OPEN BUS 342814   /*5SUMM SHADE  161.0
END
CONTINGENCY 'EKPC_P2-3_SSHAD S11-1039_SRT-A'
 OPEN BRANCH FROM BUS 341059 TO BUS 342694 CKT 1   /*2BARREN CO    69.0 - 5BARREN CO   161.0
 OPEN BUS 342814                                   /*5SUMM SHADE  161.0
END
CONTINGENCY 'EKPC_P4-2_SSHAD S11-1004_SRT-A'
 OPEN BUS 342814   /*5SUMM SHADE  161.0
END
CONTINGENCY 'EKPC_P2-3_SSHAD S11-1044_SRT-A'
 OPEN BRANCH FROM BUS 964900 TO BUS 342814 CKT 1   /*AG1-354 TP   161.0 - 5SUMM SHADE  161.0
 OPEN BUS 342814                                   /*5SUMM SHADE  161.0
 OPEN BUS 361788                                   /*5SUM SHAD TP 161.0
END
CONTINGENCY '34541 34553_SRT-A'
 OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1   /*08MELDAL     345.0 - 7SPURLOCK    345.0
 OPEN BRANCH FROM BUS 253077 TO BUS 342838 CKT 1   /*09STUART     345.0 - 7SPURLOCK    345.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1014_SRT-A'
 OPEN BRANCH FROM BUS 342742 TO BUS 342745 CKT 1   /*5JABEZ       161.0 - 5JABEZ T     161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342751 CKT 1   /*5JABEZ T     161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342799 CKT 1   /*5JABEZ T     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342748 TO BUS 342751 CKT 1   /*5JAMESTOWN   161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342751 TO BUS 342796 CKT 1   /*5JAMESTOWN T 161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342793 TO BUS 342796 CKT 1   /*5RUSSEL CO   161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342796 TO BUS 360448 CKT 1   /*5RUSSEL CO J 161.0 - 5WOLF CRK HP 161.0
 OPEN BUS 342715                                   /*5COOPER1     161.0
 OPEN BUS 342900                                   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1024_SRT-A'
 OPEN BRANCH FROM BUS 342115 TO BUS 342787 CKT 1   /*2PULASK CO    69.0 - 5PULASK CO   161.0
 OPEN BRANCH FROM BUS 342760 TO BUS 342790 CKT 1   /*5LIBERTY J   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342787 TO BUS 342790 CKT 1   /*5PULASK CO   161.0 - 5PULASK CO J 161.0
 OPEN BUS 342715                                   /*5COOPER1     161.0
 OPEN BUS 342900                                   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1008_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
 OPEN BUS 342900   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-2_COOPER 1 161_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
 OPEN BUS 342754                                   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P2-3_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 341740 TO BUS 342754 CKT 1   /*2LAUREL CO    69.0 - 5LAUREL CO   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P7-1_LAURL 161 DBL_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P2-2_LAUR-LAURD161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P2-2_LAUREL CO 161_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P1-2_LAUR-L DAM161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P2-2_COOP-LAURD 161_SRT-A'
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 1_SRT-A'
 OPEN BRANCH FROM BUS 342115 TO BUS 342787 CKT 1   /*2PULASK CO    69.0 - 5PULASK CO   161.0
 OPEN BRANCH FROM BUS 342715 TO BUS 342790 CKT 1   /*5COOPER1     161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342715 TO BUS 342799 CKT 1   /*5COOPER1     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342742 TO BUS 342745 CKT 1   /*5JABEZ       161.0 - 5JABEZ T     161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342751 CKT 1   /*5JABEZ T     161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342799 CKT 1   /*5JABEZ T     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342748 TO BUS 342751 CKT 1   /*5JAMESTOWN   161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342751 TO BUS 342796 CKT 1   /*5JAMESTOWN T 161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342760 TO BUS 342790 CKT 1   /*5LIBERTY J   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342787 TO BUS 342790 CKT 1   /*5PULASK CO   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342793 TO BUS 342796 CKT 1   /*5RUSSEL CO   161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342796 TO BUS 360448 CKT 1   /*5RUSSEL CO J 161.0 - 5WOLF CRK HP 161.0
END
CONTINGENCY 'EKPC_P2-2_PULASKI 161_SRT-A'
 OPEN BUS 342787   /*5PULASK CO   161.0
 OPEN BUS 342790   /*5PULASK CO J 161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1014_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P2-3_TYNER E13-1014_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BUS 342820                                   /*5TYNER       161.0
END
CONTINGENCY 'EKPC_P1-2_LAUR-PIT-TY161_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'DEOK_P4_1445_ZIMMER_SRT-A'
 OPEN BRANCH FROM BUS 249570 TO BUS 249577 CKT 1   /*08P.UNON     345.0 - 08ZIMER      345.0
 OPEN BRANCH FROM BUS 249581 TO BUS 249577 CKT 1   /*08MELDAL     345.0 - 08ZIMER      345.0
END
CONTINGENCY 'DEOK_P4_1449_ZIMMER_SRT-A'
 OPEN BRANCH FROM BUS 249581 TO BUS 249577 CKT 1   /*08MELDAL     345.0 - 08ZIMER      345.0
END
CONTINGENCY '34569 34598 34524_SRT-A'
 OPEN BRANCH FROM BUS 249566 TO BUS 249578 CKT 1   /*08FOSTER     345.0 - 08HILCRT     345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253006 CKT 1   /*08FOSTER     345.0 - 09BATH       345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253079 CKT 1   /*08FOSTER     345.0 - 09SUGRCK     345.0
END
CONTINGENCY 'DEOK_P4_1373_PORTUNION_SRT-A'
 OPEN BRANCH FROM BUS 249570 TO BUS 249575 CKT 1   /*08P.UNON     345.0 - 08TERMNL     345.0
 OPEN BRANCH FROM BUS 249570 TO BUS 249577 CKT 1   /*08P.UNON     345.0 - 08ZIMER      345.0
END
CONTINGENCY 'DEOK_P4_1493_RED BANK_SRT-A'
 OPEN BRANCH FROM BUS 249571 TO BUS 250092 CKT 1   /*08REDBK1     345.0 - 08REDBK1     138.0
 OPEN BUS 249573                                   /*08SGROVE     345.0
END
CONTINGENCY 'DEOK_P4_1487_RED BANK_SRT-A'
 OPEN BRANCH FROM BUS 249571 TO BUS 250093 CKT 1   /*08REDBK1     345.0 - 08REDBK2     138.0
 OPEN BUS 249573                                   /*08SGROVE     345.0
END
CONTINGENCY 'DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A'
 OPEN BUS 249573   /*08SGROVE     345.0
 OPEN BUS 250079   /*08NWTWN1     138.0
END
CONTINGENCY 'DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A'
 OPEN BUS 249573   /*08SGROVE     345.0
END
CONTINGENCY 'EKPC_P2-2_MELD-SPUR 345_SRT-A'
 OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1   /*08MELDAL     345.0 - 7SPURLOCK    345.0
END
CONTINGENCY 'EKPC_P2-3_MAR W38-1004_SRT-A'
 OPEN BRANCH FROM BUS 342769 TO BUS 342775 CKT 1   /*5MARION CO   161.0 - 5MARION IP T 161.0
 OPEN BRANCH FROM BUS 342770 TO BUS 342769 CKT 1   /*4MARION CO   138.0 - 5MARION CO   161.0
 OPEN BRANCH FROM BUS 342772 TO BUS 342797 CKT 1   /*5MARION IP   161.0 - 5S MARION IT 161.0
 OPEN BRANCH FROM BUS 342775 TO BUS 342797 CKT 1   /*5MARION IP T 161.0 - 5S MARION IT 161.0
 OPEN BRANCH FROM BUS 342775 TO BUS 342805 CKT 1   /*5MARION IP T 161.0 - 5SALOMA  T   161.0
 OPEN BRANCH FROM BUS 342797 TO BUS 342798 CKT 1   /*5S MARION IT 161.0 - 5S MARION IP 161.0
 OPEN BRANCH FROM BUS 342802 TO BUS 342805 CKT 1   /*5SALOMA      161.0 - 5SALOMA  T   161.0
 OPEN BRANCH FROM BUS 342805 TO BUS 339237 CKT 1   /*5SALOMA  T   161.0 - AF1-083 TAP  161.0
END
CONTINGENCY 'EKPC_P2-2_TVA WAYNE 161_SRT-A'
 OPEN BRANCH FROM BUS 342823 TO BUS 360486 CKT 1   /*5WAYNE CO    161.0 - 5WAYNE CO KY 161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-DEN161_SRT-A-1'
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 2   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EKPC_P2-3_LAURL S50-1014_SRT-A'
 OPEN BRANCH FROM BUS 341740 TO BUS 342754 CKT 1   /*2LAUREL CO    69.0 - 5LAUREL CO   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-LAUREL161_SRT-A-1'
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 1   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
247977 to 242524 ckt 17
242519 to 314912 ckt 1
242516 to 242920 ckt 1
248005 to 242528 ckt 1
341038 to 341755 ckt 1
341206 to 341347 ckt 1
341347 to 341344 ckt 1
341344 to 342286 ckt 1
341344 to 342286 ckt 2
341392 to 341206 ckt 1
341392 to 341578 ckt 1
341392 to 342499 ckt 1
324531 to 342287 ckt 1
341563 to 342325 ckt 1
341722 to 342187 ckt 1
341740 to 324576 ckt 1
341740 to 341722 ckt 1
341755 to 324527 ckt 1
342187 to 341038 ckt 1
342287 to 324531 ckt 1
342286 to 342287 ckt 1
324736 to 341935 ckt 1
342451 to 342452 ckt 1
342472 to 341818 ckt 1
342559 to 250054 ckt 1
342770 to 324271 ckt 1
342715 to 341344 ckt 1
342715 to 342790 ckt 1
342718 to 342715 ckt 1
342718 to 324141 ckt 1
342727 to 341392 ckt 1
342736 to 324138 ckt 1
342754 to 341740 ckt 1
342754 to 342781 ckt 1
342757 to 342754 ckt 1
342769 to 342770 ckt 1
342781 to 324688 ckt 1
342781 to 342820 ckt 1
342820 to 342736 ckt 1
342838 to 253077 ckt 1
938820 to 314746 ckt 1
339207 to 341515 ckt 1
971484 to 342397 ckt 1
972272 to 342718 ckt 1
972272 to 342718 ckt 2
972272 to 342727 ckt 1
972272 to 342757 ckt 1

Winter Peak Analysis

The New Service Request AH1-721 was evaluated as a 786.0 MW (758.9507 MW Capacity) injection in the EKPC area.

AH1-721 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 786.0 MW (786.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-A_SENS
SingleAC193.15 %1180.0B2279.13
55.11
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 542T553_SRT-W_SENS
BreakerAC190.77 %1180.0B2251.03
55.22
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 553T564_SRT-W_SENS
BreakerAC189.72 %1180.0B2238.67
55.28
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC184.94 %1180.0B2182.25
63.94
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC165.38 %1180.0B1951.44
56.32
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2114-535_SRT-A_SENS
TowerAC163.2 %1180.0B1925.78
53.94
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC159.15 %1180.0B1877.92
53.89
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#10265_05LEESVI 138_1_SRT-A
BusAC158.85 %1180.0B1874.41
54.26
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Base Case
SingleAC154.52 %1180.0A1823.34
54.0
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1014_SRT-A
BreakerAC144.85 %141.0B204.24
72.09
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1008_SRT-A
BreakerAC139.93 %141.0B197.3
81.78
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC139.93 %141.0B197.3
81.78
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1024_SRT-A
BreakerAC125.68 %141.0B177.21
73.62
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC121.48 %141.0B171.29
81.78
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1008_SRT-A
BreakerAC121.48 %141.0B171.29
81.78
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC116.02 %141.0B163.58
91.78
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC116.02 %141.0B163.58
91.78
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P4-6_COOP S42-1039_SRT-A_SENS
BreakerAC114.28 %141.0B161.14
72.87
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC113.08 %141.0B159.44
91.78
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC113.08 %141.0B159.44
91.78
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC135.36 %305.0B412.85
320.96
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-DEN161_SRT-A-1
SingleAC116.37 %334.0B388.69
321.15
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-DEN161_SRT-A-1
SingleAC114.29 %334.0B381.74
321.15
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
SingleAC149.93 %258.0B386.82
319.61
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
SingleAC147.25 %258.0B379.91
319.61
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC111.35 %258.0B287.3
312.55
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC110.57 %258.0B285.27
312.55

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:193.15 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2279.13
MW Contribution:
55.11
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
64.636
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 64.64 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 542T553_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 542T553_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:190.77 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2251.03
MW Contribution:
55.22
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
64.781
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 64.78 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 553T564_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 553T564_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:189.72 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2238.67
MW Contribution:
55.28
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
64.845
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 64.84 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:184.94 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2182.25
MW Contribution:
63.94
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
75.009
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 75.01 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:165.38 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1951.44
MW Contribution:
56.32
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
66.074
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 66.07 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2114-535_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2114-535_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:163.2 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1925.78
MW Contribution:
53.94
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
63.283
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 63.28 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:159.15 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1877.92
MW Contribution:
53.89
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
63.221
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 63.22 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#10265_05LEESVI 138_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10265_05LEESVI 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:158.85 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1874.41
MW Contribution:
54.26
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
63.647
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 63.65 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:154.52 %
Rating:1180.0 MVA
Rating Type:A
MVA to Mitigate:1823.34
MW Contribution:
54.0
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
63.353
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 63.35 MW.

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1014_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.85 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:204.24
MW Contribution:
72.09
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.96 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:204.39
MW Contribution:
72.11
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
72.088

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1008_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.93 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:197.3
MW Contribution:
81.78
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.41 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:196.57
MW Contribution:
82.65
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
23.708
339241AF1-083 GEN
Solar/Wind Helper
0.187
339236AF1-050_GEN
Solar/Wind Helper
0.177
339206AE1-143 GEN
Solar/Wind Helper
0.38
972273AH1-721 GEN
50/50
81.779
339255AE2-071 GEN
Solar/Wind Helper
0.11
339231AF1-038_GEN
Solar/Wind Helper
0.658
339250AF1-203 GEN
Solar/Wind Helper
0.063
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.137
G-007ALTFEXP_G-007A->PJM
CMTX
0.072
VFTLTFEXP_VFT->PJM
CMTX
0.194
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.035
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.025
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.894
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.092
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.364
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:139.93 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:197.3
MW Contribution:
81.78
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:139.4 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:196.56
MW Contribution:
82.65
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
23.708
339241AF1-083 GEN
Solar/Wind Helper
0.187
339236AF1-050_GEN
Solar/Wind Helper
0.177
339206AE1-143 GEN
Solar/Wind Helper
0.38
972273AH1-721 GEN
50/50
81.779
339255AE2-071 GEN
Solar/Wind Helper
0.11
339231AF1-038_GEN
Solar/Wind Helper
0.658
339250AF1-203 GEN
Solar/Wind Helper
0.063
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.137
G-007ALTFEXP_G-007A->PJM
CMTX
0.072
VFTLTFEXP_VFT->PJM
CMTX
0.194
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.035
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.025
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.894
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.092
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.364
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1024_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.68 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:177.21
MW Contribution:
73.62
IPD Plant:AH1-721
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.85 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:176.04
MW Contribution:
73.55
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
73.623

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.48 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:171.29
MW Contribution:
81.78
IPD Plant:AH1-721
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:120.97 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:170.56
MW Contribution:
82.65
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
81.779

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1008_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.48 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:171.29
MW Contribution:
81.78
IPD Plant:AH1-721
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.97 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:170.56
MW Contribution:
82.65
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
81.779

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.02 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:163.58
MW Contribution:
91.78
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
339241AF1-083 GEN
Solar/Wind Helper
0.229
339236AF1-050_GEN
Solar/Wind Helper
0.227
339206AE1-143 GEN
Solar/Wind Helper
0.452
972273AH1-721 GEN
50/50
91.779
339255AE2-071 GEN
Solar/Wind Helper
0.138
339231AF1-038_GEN
Solar/Wind Helper
0.67
339250AF1-203 GEN
Solar/Wind Helper
0.079
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.168
G-007ALTFEXP_G-007A->PJM
CMTX
0.086
VFTLTFEXP_VFT->PJM
CMTX
0.231
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.045
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.215
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.107
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.436
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:116.02 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:163.58
MW Contribution:
91.78
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
339241AF1-083 GEN
Solar/Wind Helper
0.229
339236AF1-050_GEN
Solar/Wind Helper
0.227
339206AE1-143 GEN
Solar/Wind Helper
0.452
972273AH1-721 GEN
50/50
91.779
339255AE2-071 GEN
Solar/Wind Helper
0.138
339231AF1-038_GEN
Solar/Wind Helper
0.67
339250AF1-203 GEN
Solar/Wind Helper
0.079
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.168
G-007ALTFEXP_G-007A->PJM
CMTX
0.086
VFTLTFEXP_VFT->PJM
CMTX
0.231
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.045
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.215
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.107
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.436
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P4-6_COOP S42-1039_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-6_COOP S42-1039_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.28 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:161.14
MW Contribution:
72.87
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
72.867

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.08 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:159.44
MW Contribution:
91.78
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
91.779

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.08 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:159.44
MW Contribution:
91.78
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
91.779

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:135.36 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:412.85
MW Contribution:
320.96
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
108.527
970653AG2-424 GEN
Solar/Wind Harmer
0.339
3429451LAUREL 1G
50/50
1.173
971485AH1-239 GEN
Solar/Wind Harmer
0.72
966021AG1-471 GEN
Solar/Wind Harmer
0.482
964901AG1-354 GEN
Solar/Wind Harmer
0.786
964781AG1-341 GEN
Solar/Wind Harmer
0.524
972273AH1-721 GEN
50/50
376.735
970653AG2-424 GEN
Solar/Wind Harmer
0.136
950011AG9-010
External Queue
0.5764614939689636
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.054
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.187
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.684
NYPJM->LTFIMP_NY
CLTF
0.03
WECLTFEXP_WEC->PJM
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
0.158
TVALTFEXP_TVA->PJM
CLTF
1.063
MECLTFEXP_MEC->PJM
CLTF
0.626
LAGNLTFEXP_LAGN->PJM
CLTF
1.577
SIGELTFEXP_SIGE->PJM
CLTF
0.02
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.024
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 376.74 MW.

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-DEN161_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-DEN161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.37 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:388.69
MW Contribution:
321.15
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-DEN161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:177.79 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:593.8
MW Contribution:
648.08
Bus #Bus NameTypeMW Contribution
339241AF1-083 GEN
Solar/Wind Helper
0.354
339236AF1-050_GEN
Solar/Wind Helper
0.34
3429451LAUREL 1G
50/50
1.076
339206AE1-143 GEN
Solar/Wind Helper
0.719
972273AH1-721 GEN
50/50
321.147
339255AE2-071 GEN
Solar/Wind Helper
0.179
339231AF1-038_GEN
Solar/Wind Helper
0.629
339250AF1-203 GEN
Solar/Wind Helper
0.102
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.194
G-007ALTFEXP_G-007A->PJM
CMTX
0.098
VFTLTFEXP_VFT->PJM
CMTX
0.264
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.113
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.079
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.818
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.177
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.706
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-DEN161_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-DEN161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.29 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:381.74
MW Contribution:
321.15
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-DEN161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:176.36 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:589.03
MW Contribution:
648.08
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
321.147

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-LAUREL161_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:149.93 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:386.82
MW Contribution:
319.61
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:229.95 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:593.26
MW Contribution:
647.52
Bus #Bus NameTypeMW Contribution
339241AF1-083 GEN
Solar/Wind Helper
0.353
339236AF1-050_GEN
Solar/Wind Helper
0.338
3429451LAUREL 1G
50/50
1.071
339206AE1-143 GEN
Solar/Wind Helper
0.716
972273AH1-721 GEN
50/50
319.614
339255AE2-071 GEN
Solar/Wind Helper
0.178
339231AF1-038_GEN
Solar/Wind Helper
0.626
339250AF1-203 GEN
Solar/Wind Helper
0.102
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.193
G-007ALTFEXP_G-007A->PJM
CMTX
0.098
VFTLTFEXP_VFT->PJM
CMTX
0.263
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.113
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.078
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.81
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.176
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.703
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-LAUREL161_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:147.25 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:379.91
MW Contribution:
319.61
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:228.1 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:588.5
MW Contribution:
647.52
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
319.614

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.35 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:287.3
MW Contribution:
312.55
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.014
972273AH1-721 GEN
50/50
312.546
NYPJM->LTFIMP_NY
CLTF
0.001
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.003
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.236
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.088
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.295
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.277

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.57 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:285.27
MW Contribution:
312.55
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
312.546
CONTINGENCY 'DVP_P1-2: LN 553_SRT-A_SENS'
 OPEN BRANCH FROM BUS 314910 TO BUS 313378 CKT 1   /*8CUNINGHAM   500.0 - 8VONTAY      500.0
END
CONTINGENCY 'DVP_P4-2: 542T553_SRT-W_SENS'
 OPEN BRANCH FROM BUS 313378 TO BUS 314910 CKT 1                /*8VONTAY      500.0 - 8CUNINGHAM   500.0
 OPEN BUS 315217                                                /*1CUNINGB      18.0
 OPEN BUS 315218                                                /*1CUNINGC      18.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'DVP_P4-2: 553T564_SRT-W_SENS'
 OPEN BRANCH FROM BUS 313378 TO BUS 314910 CKT 1                /*8VONTAY      500.0 - 8CUNINGHAM   500.0
 OPEN BUS 315216                                                /*1CUNINGA      18.0
 OPEN BUS 315219                                                /*1CUNINGD      22.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2114-535_SRT-A_SENS'
 OPEN BRANCH FROM BUS 235110 TO BUS 289543 CKT 1   /*01MDWBRK     500.0 - 05YEAT       500.0
 OPEN BRANCH FROM BUS 314085 TO BUS 314110 CKT 1   /*6REMNGCT     230.0 - 6ELK RUN     230.0
 OPEN BRANCH FROM BUS 314110 TO BUS 314125 CKT 1   /*6ELK RUN     230.0 - 6VINTHIL     230.0
 OPEN BUS 314110                                   /*6ELK RUN     230.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'AEP_P2-2_#10265_05LEESVI 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242701 TO BUS 242802 CKT 1   /*05LEESVI     138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242701 TO BUS 247284 CKT 1   /*05LEESVI     138.0 - 05LEESVG      13.8
 OPEN BRANCH FROM BUS 242701 TO BUS 314667 CKT 1   /*05LEESVI     138.0 - 4ALTVSTA     138.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1014_SRT-A'
 OPEN BRANCH FROM BUS 342742 TO BUS 342745 CKT 1   /*5JABEZ       161.0 - 5JABEZ T     161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342751 CKT 1   /*5JABEZ T     161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342799 CKT 1   /*5JABEZ T     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342748 TO BUS 342751 CKT 1   /*5JAMESTOWN   161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342751 TO BUS 342796 CKT 1   /*5JAMESTOWN T 161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342793 TO BUS 342796 CKT 1   /*5RUSSEL CO   161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342796 TO BUS 360448 CKT 1   /*5RUSSEL CO J 161.0 - 5WOLF CRK HP 161.0
 OPEN BUS 342715                                   /*5COOPER1     161.0
 OPEN BUS 342900                                   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1008_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
 OPEN BUS 342900   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-2_COOPER 1 161_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1024_SRT-A'
 OPEN BRANCH FROM BUS 342115 TO BUS 342787 CKT 1   /*2PULASK CO    69.0 - 5PULASK CO   161.0
 OPEN BRANCH FROM BUS 342760 TO BUS 342790 CKT 1   /*5LIBERTY J   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342787 TO BUS 342790 CKT 1   /*5PULASK CO   161.0 - 5PULASK CO J 161.0
 OPEN BUS 342715                                   /*5COOPER1     161.0
 OPEN BUS 342900                                   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-3_COOP S42-210G_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-2_COOPER 2 161_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
END
CONTINGENCY 'EKPC_P4-6_COOP S42-1039_SRT-A_SENS'
 OPEN BUS 342715   /*5COOPER1     161.0
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342900   /*1COOPER1 G    13.8
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS'
 OPEN BRANCH FROM BUS 324130 TO BUS 972272 CKT 1   /*5ALCALDE     161.0 - AH1-721 TP   161.0
 OPEN BRANCH FROM BUS 324130 TO BUS 972272 CKT 2   /*5ALCALDE     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-DEN161_SRT-A-1'
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 2   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-LAUREL161_SRT-A-1'
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 1   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
290614 to 242515 ckt 1
324531 to 342287 ckt 1
342718 to 324141 ckt 1
972272 to 342718 ckt 1
972272 to 342718 ckt 2

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2EKPC
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC107.72 %86.0B92.64
124.15
IPDEKPC
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC106.69 %86.0B91.75
124.15
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC130.08 %86.0B111.87
112.16
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC126.92 %86.0B109.15
119.48
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC126.92 %86.0B109.15
119.48
IPDEKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC125.34 %86.0B107.79
112.16
IPDEKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC123.33 %86.0B106.06
119.48
IPDEKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC123.33 %86.0B106.06
119.48
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC129.82 %86.0B111.65
112.16
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC126.67 %86.0B108.93
119.48
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC126.67 %86.0B108.93
119.48
IPDEKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC125.09 %86.0B107.58
112.16
IPDEKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC123.08 %86.0B105.85
119.48
IPDEKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC123.08 %86.0B105.85
119.48
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC174.7 %89.0B155.48
90.12
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC134.08 %89.0B119.33
90.11
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC132.42 %89.0B117.85
68.43
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC132.09 %89.0B117.56
68.43
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC131.87 %89.0B117.37
68.19
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC101.73 %89.0B90.54
68.43
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC101.73 %89.0B90.54
68.43
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC101.47 %89.0B90.31
68.2
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC174.7 %89.0B155.48
90.12
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC134.08 %89.0B119.33
90.11
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC132.42 %89.0B117.85
68.43
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC132.09 %89.0B117.56
68.43
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC131.87 %89.0B117.37
68.19
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC101.73 %89.0B90.54
68.43
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC101.73 %89.0B90.54
68.43
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC101.47 %89.0B90.31
68.2
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC167.4 %76.0B127.23
112.16
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC162.95 %76.0B123.84
119.48
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC162.95 %76.0B123.84
119.48
IPDEKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC162.04 %76.0B123.15
112.16
IPDEKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC158.89 %76.0B120.76
119.48
IPDEKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC158.89 %76.0B120.76
119.48
GD2EKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC114.65 %89.0B102.03
91.56
GD2EKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC114.65 %89.0B102.03
91.56
IPDEKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC113.97 %89.0B101.43
91.56
IPDEKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC113.97 %89.0B101.43
91.56
GD2EKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC111.37 %89.0B99.12
94.91
IPDEKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC110.54 %89.0B98.38
94.91
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC145.11 %141.0B204.61
105.33
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC120.97 %141.0B170.57
105.33
GD2EKPC
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC123.96 %86.0B106.6
124.15
IPDEKPC
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC122.93 %86.0B105.72
124.15
GD2EKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC112.49 %141.0B158.61
142.99
IPDEKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC111.82 %141.0B157.67
142.99
GD2EKPC
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC140.21 %86.0B120.58
124.15
IPDEKPC
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC139.18 %86.0B119.7
124.15
GD2EKPC
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC111.61 %86.0B95.98
124.15
IPDEKPC
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC110.58 %86.0B95.1
124.15
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC147.57 %141.0B208.07
179.93
GD2EKPC
2SOMERSET KU-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC102.08 %177.0B180.69
90.03
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC121.68 %177.0B215.38
184.01
GD2EKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC173.49 %178.0B308.8
176.54
IPDEKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC136.28 %178.0B242.57
176.54
GD2EKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC133.66 %178.0B237.92
134.59
GD2EKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC133.66 %178.0B237.92
134.59
GD2EKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC133.16 %178.0B237.03
133.48
IPDEKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC105.34 %178.0B187.5
134.59
IPDEKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC105.34 %178.0B187.5
134.59
IPDEKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC104.75 %178.0B186.45
133.48
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC176.86 %501.0B886.08
697.68
IPDEKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC136.31 %501.0B682.92
697.68
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC133.86 %501.0B670.64
544.09
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC133.86 %501.0B670.63
544.09
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC133.4 %501.0B668.31
541.31
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EXT_324130 5ALCALDE 161 324141 5ELIHU 161 1_SRT-W
SingleAC101.89 %501.0B510.46
445.94
IPDEKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC101.61 %501.0B509.06
544.09
IPDEKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC101.61 %501.0B509.06
544.09
IPDEKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC101.09 %501.0B506.45
541.31
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1014_SRT-A
BreakerAC226.85 %305.0B691.9
577.84
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1024_SRT-A
BreakerAC224.52 %305.0B684.79
578.94
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1008_SRT-A
BreakerAC224.35 %305.0B684.28
579.78
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC224.35 %305.0B684.28
579.78
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC223.93 %305.0B682.98
581.69
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC184.26 %305.0B561.98
370.35
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC184.25 %305.0B561.97
370.35
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1024_SRT-A
BreakerAC184.25 %305.0B561.96
370.35
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC183.81 %305.0B560.61
371.0
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC183.8 %305.0B560.6
371.0
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC183.79 %305.0B560.55
370.67
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 1_SRT-A
TowerAC183.38 %305.0B559.3
439.65
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOP-LAURD 161_SRT-A
BusAC170.9 %305.0B521.26
371.18
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1014_SRT-A
BreakerAC170.36 %305.0B519.59
577.84
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1024_SRT-A
BreakerAC168.35 %305.0B513.46
578.94
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1008_SRT-A
BreakerAC168.05 %305.0B512.55
579.78
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC168.05 %305.0B512.55
579.78
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC167.7 %305.0B511.48
581.69
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_PULASKI 161_SRT-A
BusAC166.35 %305.0B507.37
366.44
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Base Case
SingleAC149.52 %279.0A417.15
321.34
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC134.04 %305.0B408.81
370.35
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC134.03 %305.0B408.8
370.35
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1024_SRT-A
BreakerAC134.03 %305.0B408.8
370.35
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC133.48 %305.0B407.13
370.67
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC133.43 %305.0B406.98
371.0
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC133.43 %305.0B406.98
371.0
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 1_SRT-A
TowerAC132.53 %305.0B404.22
516.21
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOP-LAURD 161_SRT-A
BusAC121.04 %305.0B369.16
435.35
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_PULASKI 161_SRT-A
BusAC118.88 %305.0B362.6
430.19
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Base Case
SingleAC102.47 %279.0A285.88
377.19
GD2EKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC277.0 %109.0B301.93
292.89
GD2EKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC277.0 %109.0B301.93
292.89
IPDEKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC275.1 %109.0B299.86
292.89
IPDEKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC275.1 %109.0B299.86
292.89
GD2EKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC274.73 %109.0B299.46
291.02
IPDEKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC272.88 %109.0B297.44
291.02
GD2EKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC118.37 %109.0B129.02
75.6
GD2EKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC109.59 %109.0B119.45
72.23
GD2EKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC204.8 %178.0B364.54
318.27
IPDEKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC203.68 %178.0B362.54
318.27
GD2EKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC131.4 %178.0B233.89
194.97
GD2EKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC131.29 %178.0B233.69
194.73
GD2EKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC131.29 %178.0B233.69
194.73
IPDEKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC130.69 %178.0B232.62
194.97
IPDEKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC130.58 %178.0B232.43
194.73
IPDEKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC130.58 %178.0B232.43
194.73
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC140.35 %351.0B492.62
467.38
IPDEKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC138.88 %351.0B487.47
467.38
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC256.09 %334.0B855.33
785.65
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC254.85 %334.0B851.21
785.65
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC180.81 %334.0B603.89
494.63
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC179.88 %334.0B600.79
492.75
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC179.88 %334.0B600.79
492.75
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC177.54 %334.0B593.0
494.63
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC176.6 %334.0B589.85
492.75
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC176.6 %334.0B589.85
492.75
GD2EKPC/LGEE
5PITTSBURG-2PITTSBRG KU 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC116.06 %143.0B165.96
108.17
IPDEKPC/LGEE
5PITTSBURG-2PITTSBRG KU 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC115.45 %143.0B165.09
108.17
GD2EKPC
5PITTSBURG-5TYNER 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC131.76 %250.0B329.4
359.2
IPDEKPC
5PITTSBURG-5TYNER 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC128.86 %250.0B322.16
359.2
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC123.52 %334.0B412.55
386.39
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC123.52 %334.0B412.55
386.39
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1014_SRT-A
BreakerAC123.51 %334.0B412.54
386.4
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1014_SRT-A
BreakerAC123.51 %334.0B412.53
386.4
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC123.51 %334.0B412.53
386.4
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC123.51 %334.0B412.52
386.41
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC122.25 %334.0B408.32
386.39
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC122.25 %334.0B408.32
386.39
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1014_SRT-A
BreakerAC122.25 %334.0B408.3
386.4
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC122.24 %334.0B408.28
386.4
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1014_SRT-A
BreakerAC122.24 %334.0B408.28
386.4
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC122.24 %334.0B408.27
386.41
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC106.58 %334.0B355.99
362.33
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC106.2 %334.0B354.72
362.33
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC198.38 %258.0B511.81
541.31
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC196.33 %258.0B506.53
541.31
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC147.91 %258.0B381.61
357.62
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC147.91 %258.0B381.61
357.62
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-3_LAURL S50-1014_SRT-A
BreakerAC147.9 %258.0B381.59
357.63
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P4-5_LAURL S50-1014_SRT-A
BreakerAC147.9 %258.0B381.58
357.63
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC147.9 %258.0B381.58
357.63
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC147.9 %258.0B381.57
357.64
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC146.47 %258.0B377.88
357.62
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC146.47 %258.0B377.88
357.62
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-3_LAURL S50-1014_SRT-A
BreakerAC146.46 %258.0B377.87
357.63
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P4-5_LAURL S50-1014_SRT-A
BreakerAC146.46 %258.0B377.85
357.63
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC146.46 %258.0B377.85
357.63
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC146.45 %258.0B377.84
357.64
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Base Case
SingleAC114.68 %250.0A286.7
313.13
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Base Case
SingleAC113.87 %250.0A284.66
313.13
GD2EKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC121.44 %258.0B313.33
292.89
GD2EKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC121.44 %258.0B313.32
292.89
GD2EKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC120.95 %258.0B312.04
291.02
IPDEKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC120.47 %258.0B310.81
292.89
IPDEKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC120.47 %258.0B310.81
292.89
IPDEKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC119.98 %258.0B309.55
291.02
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC235.3 %334.0B785.9
786.0
IPDEKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC235.3 %334.0B785.9
786.0
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC157.6 %334.0B526.37
494.98
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC156.77 %334.0B523.62
493.11
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC156.77 %334.0B523.61
493.11
IPDEKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC155.16 %334.0B518.23
494.98
IPDEKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC154.3 %334.0B515.37
493.11
IPDEKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC154.3 %334.0B515.37
493.11

Details for 2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:107.72 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:92.64
MW Contribution:
124.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.605
972273AH1-721 GEN
50/50
124.149
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.02
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.054
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.037
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.16
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:106.69 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:91.75
MW Contribution:
124.15
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
124.149

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.08 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:111.87
MW Contribution:
112.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
0.233
971485AH1-239 GEN
Solar/Wind Harmer
0.31
972273AH1-721 GEN
50/50
112.16
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.097
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.542
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.286
G-007ALTFEXP_G-007A->PJM
CMTX
0.011
VFTLTFEXP_VFT->PJM
CMTX
0.029
GibsonPJM->LTFIMP_GIBSON
CLTF
0
WECLTFEXP_WEC->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.078
TVALTFEXP_TVA->PJM
CLTF
0.208
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
MECLTFEXP_MEC->PJM
CLTF
0.058
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.207
LAGNLTFEXP_LAGN->PJM
CLTF
0.303
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.547

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:109.15
MW Contribution:
119.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.385
966021AG1-471 GEN
Solar/Wind Harmer
0.216
971485AH1-239 GEN
Solar/Wind Harmer
0.284
972273AH1-721 GEN
50/50
119.478
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.345
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.21
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
VFTLTFEXP_VFT->PJM
CMTX
0.044
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.059
TVALTFEXP_TVA->PJM
CLTF
0.108
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.239
LAGNLTFEXP_LAGN->PJM
CLTF
0.155
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.455

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:109.15
MW Contribution:
119.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.385
966021AG1-471 GEN
Solar/Wind Harmer
0.216
971485AH1-239 GEN
Solar/Wind Harmer
0.284
972273AH1-721 GEN
50/50
119.478
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.345
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.21
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
VFTLTFEXP_VFT->PJM
CMTX
0.044
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.059
TVALTFEXP_TVA->PJM
CLTF
0.108
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.239
LAGNLTFEXP_LAGN->PJM
CLTF
0.155
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.455

Details for [AH1-721] 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.34 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:107.79
MW Contribution:
112.16
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
112.16

Details for [AH1-721] 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:123.33 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:106.06
MW Contribution:
119.48
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
119.478

Details for [AH1-721] 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.33 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:106.06
MW Contribution:
119.48
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
119.478

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.82 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:111.65
MW Contribution:
112.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
0.233
971485AH1-239 GEN
Solar/Wind Harmer
0.31
972273AH1-721 GEN
50/50
112.16
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.097
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.542
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.286
G-007ALTFEXP_G-007A->PJM
CMTX
0.011
VFTLTFEXP_VFT->PJM
CMTX
0.029
GibsonPJM->LTFIMP_GIBSON
CLTF
0
WECLTFEXP_WEC->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.078
TVALTFEXP_TVA->PJM
CLTF
0.208
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
MECLTFEXP_MEC->PJM
CLTF
0.058
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.207
LAGNLTFEXP_LAGN->PJM
CLTF
0.303
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.547

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.67 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:108.93
MW Contribution:
119.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.385
966021AG1-471 GEN
Solar/Wind Harmer
0.216
971485AH1-239 GEN
Solar/Wind Harmer
0.284
972273AH1-721 GEN
50/50
119.478
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.345
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.21
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
VFTLTFEXP_VFT->PJM
CMTX
0.044
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.059
TVALTFEXP_TVA->PJM
CLTF
0.108
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.239
LAGNLTFEXP_LAGN->PJM
CLTF
0.155
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.455

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.67 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:108.93
MW Contribution:
119.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.385
966021AG1-471 GEN
Solar/Wind Harmer
0.216
971485AH1-239 GEN
Solar/Wind Harmer
0.284
972273AH1-721 GEN
50/50
119.478
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.345
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.21
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
VFTLTFEXP_VFT->PJM
CMTX
0.044
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.059
TVALTFEXP_TVA->PJM
CLTF
0.108
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.239
LAGNLTFEXP_LAGN->PJM
CLTF
0.155
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.455

Details for [AH1-721] 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.09 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:107.58
MW Contribution:
112.16
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
112.16

Details for [AH1-721] 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.08 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:105.85
MW Contribution:
119.48
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
119.478

Details for [AH1-721] 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:123.08 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:105.85
MW Contribution:
119.48
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
119.478

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:174.7 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:155.48
MW Contribution:
90.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
30.255
966021AG1-471 GEN
Solar/Wind Harmer
0.169
971485AH1-239 GEN
Solar/Wind Harmer
0.232
972273AH1-721 GEN
50/50
105.713
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.895
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.957
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.27
NYPJM->LTFIMP_NY
CLTF
0.004
WECLTFEXP_WEC->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
0.068
TVALTFEXP_TVA->PJM
CLTF
0.316
MECLTFEXP_MEC->PJM
CLTF
0.184
LAGNLTFEXP_LAGN->PJM
CLTF
0.475
SIGELTFEXP_SIGE->PJM
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.331
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 105.71 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:134.08 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:119.33
MW Contribution:
90.11
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
105.713
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 105.71 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.42 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:117.85
MW Contribution:
68.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.248
3429031COOPER2 G
50/50
23.083
972273AH1-721 GEN
50/50
80.337
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.518
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.536
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.186
NYPJM->LTFIMP_NY
CLTF
0.004
WECLTFEXP_WEC->PJM
CLTF
0.013
CPLELTFEXP_CPLE->PJM
CLTF
0.047
TVALTFEXP_TVA->PJM
CLTF
0.219
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
MECLTFEXP_MEC->PJM
CLTF
0.115
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.289
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 80.34 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:132.09 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:117.56
MW Contribution:
68.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
23.083
972273AH1-721 GEN
50/50
80.337
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.518
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.536
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.186
NYPJM->LTFIMP_NY
CLTF
0.004
WECLTFEXP_WEC->PJM
CLTF
0.013
CPLELTFEXP_CPLE->PJM
CLTF
0.047
TVALTFEXP_TVA->PJM
CLTF
0.219
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
MECLTFEXP_MEC->PJM
CLTF
0.115
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.289
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 80.34 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:131.87 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:117.37
MW Contribution:
68.19
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
23.11
972273AH1-721 GEN
50/50
80.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.519
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.538
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.643
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.186
NYPJM->LTFIMP_NY
CLTF
0.004
WECLTFEXP_WEC->PJM
CLTF
0.013
CPLELTFEXP_CPLE->PJM
CLTF
0.047
TVALTFEXP_TVA->PJM
CLTF
0.219
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
MECLTFEXP_MEC->PJM
CLTF
0.115
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
0.326
SIGELTFEXP_SIGE->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.289
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 80.12 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.73 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:90.54
MW Contribution:
68.43
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
80.337
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 80.34 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.73 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:90.54
MW Contribution:
68.43
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
80.337
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 80.34 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.47 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:90.31
MW Contribution:
68.2
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
80.116
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 80.12 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:174.7 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:155.48
MW Contribution:
90.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
30.255
966021AG1-471 GEN
Solar/Wind Harmer
0.169
971485AH1-239 GEN
Solar/Wind Harmer
0.232
972273AH1-721 GEN
50/50
105.713
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.895
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.957
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.27
NYPJM->LTFIMP_NY
CLTF
0.004
WECLTFEXP_WEC->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
0.068
TVALTFEXP_TVA->PJM
CLTF
0.316
MECLTFEXP_MEC->PJM
CLTF
0.184
LAGNLTFEXP_LAGN->PJM
CLTF
0.475
SIGELTFEXP_SIGE->PJM
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.331
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 105.71 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:134.08 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:119.33
MW Contribution:
90.11
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
105.713
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 105.71 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.42 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:117.85
MW Contribution:
68.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.248
3429031COOPER2 G
50/50
23.083
972273AH1-721 GEN
50/50
80.337
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.518
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.536
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.186
NYPJM->LTFIMP_NY
CLTF
0.004
WECLTFEXP_WEC->PJM
CLTF
0.013
CPLELTFEXP_CPLE->PJM
CLTF
0.047
TVALTFEXP_TVA->PJM
CLTF
0.219
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
MECLTFEXP_MEC->PJM
CLTF
0.115
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.289
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 80.34 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:132.09 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:117.56
MW Contribution:
68.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
23.083
972273AH1-721 GEN
50/50
80.337
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.518
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.536
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.186
NYPJM->LTFIMP_NY
CLTF
0.004
WECLTFEXP_WEC->PJM
CLTF
0.013
CPLELTFEXP_CPLE->PJM
CLTF
0.047
TVALTFEXP_TVA->PJM
CLTF
0.219
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
MECLTFEXP_MEC->PJM
CLTF
0.115
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.289
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 80.34 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:131.87 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:117.37
MW Contribution:
68.19
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
23.11
972273AH1-721 GEN
50/50
80.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.519
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.538
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.643
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.186
NYPJM->LTFIMP_NY
CLTF
0.004
WECLTFEXP_WEC->PJM
CLTF
0.013
CPLELTFEXP_CPLE->PJM
CLTF
0.047
TVALTFEXP_TVA->PJM
CLTF
0.219
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
MECLTFEXP_MEC->PJM
CLTF
0.115
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
0.326
SIGELTFEXP_SIGE->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.289
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 80.12 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.73 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:90.54
MW Contribution:
68.43
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
80.337
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 80.34 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.73 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:90.54
MW Contribution:
68.43
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
80.337
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 80.34 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.47 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:90.31
MW Contribution:
68.2
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
80.116
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 80.12 MW.

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.4 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:127.23
MW Contribution:
112.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
0.233
971485AH1-239 GEN
Solar/Wind Harmer
0.31
972273AH1-721 GEN
50/50
112.16
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.097
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.542
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.286
G-007ALTFEXP_G-007A->PJM
CMTX
0.011
VFTLTFEXP_VFT->PJM
CMTX
0.029
GibsonPJM->LTFIMP_GIBSON
CLTF
0
WECLTFEXP_WEC->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.078
TVALTFEXP_TVA->PJM
CLTF
0.208
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
MECLTFEXP_MEC->PJM
CLTF
0.058
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.207
LAGNLTFEXP_LAGN->PJM
CLTF
0.303
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.547

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:162.95 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:123.84
MW Contribution:
119.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.385
966021AG1-471 GEN
Solar/Wind Harmer
0.216
971485AH1-239 GEN
Solar/Wind Harmer
0.284
972273AH1-721 GEN
50/50
119.478
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.345
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.21
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
VFTLTFEXP_VFT->PJM
CMTX
0.044
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.059
TVALTFEXP_TVA->PJM
CLTF
0.108
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.239
LAGNLTFEXP_LAGN->PJM
CLTF
0.155
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.455

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:162.95 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:123.84
MW Contribution:
119.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.385
966021AG1-471 GEN
Solar/Wind Harmer
0.216
971485AH1-239 GEN
Solar/Wind Harmer
0.284
972273AH1-721 GEN
50/50
119.478
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.345
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.21
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
VFTLTFEXP_VFT->PJM
CMTX
0.044
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.059
TVALTFEXP_TVA->PJM
CLTF
0.108
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.239
LAGNLTFEXP_LAGN->PJM
CLTF
0.155
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.455

Details for [AH1-721] 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:162.04 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:123.15
MW Contribution:
112.16
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
112.16

Details for [AH1-721] 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:158.89 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:120.76
MW Contribution:
119.48
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
119.478

Details for [AH1-721] 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:158.89 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:120.76
MW Contribution:
119.48
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
119.478

Details for 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.65 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:102.03
MW Contribution:
91.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
91.561
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.012
G-007ALTFEXP_G-007A->PJM
CMTX
0.002
VFTLTFEXP_VFT->PJM
CMTX
0.006
LGEELTFEXP_LGEE->PJM
CLTF
0.008
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.047
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.033
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.409
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.014
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.074
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:114.65 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:102.03
MW Contribution:
91.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
91.561
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.012
G-007ALTFEXP_G-007A->PJM
CMTX
0.002
VFTLTFEXP_VFT->PJM
CMTX
0.006
LGEELTFEXP_LGEE->PJM
CLTF
0.008
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.047
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.033
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.409
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.014
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.074
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.97 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:101.43
MW Contribution:
91.56
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
91.561

Details for [AH1-721] 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.97 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:101.43
MW Contribution:
91.56
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
91.561

Details for 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.37 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:99.12
MW Contribution:
94.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
94.913
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.016
G-007ALTFEXP_G-007A->PJM
CMTX
0.003
VFTLTFEXP_VFT->PJM
CMTX
0.009
LGEELTFEXP_LGEE->PJM
CLTF
0.016
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.059
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.497
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.013
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.077
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.54 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:98.38
MW Contribution:
94.91
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
94.913

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.11 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:204.61
MW Contribution:
105.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.38
339206AE1-143 GEN
Solar/Wind Helper
0.457
3429031COOPER2 G
50/50
30.447
339241AF1-083 GEN
Solar/Wind Helper
0.231
339236AF1-050_GEN
Solar/Wind Helper
0.23
972273AH1-721 GEN
50/50
105.326
339255AE2-071 GEN
Solar/Wind Helper
0.14
339231AF1-038_GEN
Solar/Wind Helper
0.679
339250AF1-203 GEN
Solar/Wind Helper
0.08
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.165
G-007ALTFEXP_G-007A->PJM
CMTX
0.081
VFTLTFEXP_VFT->PJM
CMTX
0.217
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.062
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.043
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.237
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.109
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.445
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.97 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:170.57
MW Contribution:
105.33
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
105.326

Details for 2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:123.96 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:106.6
MW Contribution:
124.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.605
972273AH1-721 GEN
50/50
124.149
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.02
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.054
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.037
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.16
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:122.93 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:105.72
MW Contribution:
124.15
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
124.149

Details for 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:112.49 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:158.61
MW Contribution:
142.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.696
972273AH1-721 GEN
50/50
142.994
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.017
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.034
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.141
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:111.82 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:157.67
MW Contribution:
142.99
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
142.994

Details for 2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:140.21 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:120.58
MW Contribution:
124.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.605
972273AH1-721 GEN
50/50
124.149
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.02
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.054
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.037
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.16
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:139.18 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:119.7
MW Contribution:
124.15
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
124.149

Details for 2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:111.61 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:95.98
MW Contribution:
124.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.605
972273AH1-721 GEN
50/50
124.149
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.02
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.054
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.037
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.16
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:110.58 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:95.1
MW Contribution:
124.15
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
124.149

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:147.57 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:208.07
MW Contribution:
179.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
60.456
966021AG1-471 GEN
Solar/Wind Harmer
0.387
971485AH1-239 GEN
Solar/Wind Harmer
0.549
964901AG1-354 GEN
Solar/Wind Harmer
0.617
964781AG1-341 GEN
Solar/Wind Harmer
0.421
972273AH1-721 GEN
50/50
211.105
950011AG9-010
External Queue
0.42752620577812195
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.93
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.722
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.645
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.525
NYPJM->LTFIMP_NY
CLTF
0.02
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.078
CPLELTFEXP_CPLE->PJM
CLTF
0.121
TVALTFEXP_TVA->PJM
CLTF
0.853
MECLTFEXP_MEC->PJM
CLTF
0.56
LAGNLTFEXP_LAGN->PJM
CLTF
1.285
SIGELTFEXP_SIGE->PJM
CLTF
0.02
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.643
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 211.1 MW.

Details for 2SOMERSET KU-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET KU-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:177.0 MVA
Rating Type:B
MVA to Mitigate:180.69
MW Contribution:
90.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.322
339206AE1-143 GEN
Solar/Wind Helper
0.444
3429031COOPER2 G
50/50
26.05
339241AF1-083 GEN
Solar/Wind Helper
0.213
339236AF1-050_GEN
Solar/Wind Helper
0.196
972273AH1-721 GEN
50/50
90.028
339255AE2-071 GEN
Solar/Wind Helper
0.106
339231AF1-038_GEN
Solar/Wind Helper
0.488
339250AF1-203 GEN
Solar/Wind Helper
0.061
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.148
G-007ALTFEXP_G-007A->PJM
CMTX
0.075
VFTLTFEXP_VFT->PJM
CMTX
0.202
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.031
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.022
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.961
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.106
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.414
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:121.68 %
Rating:177.0 MVA
Rating Type:B
MVA to Mitigate:215.38
MW Contribution:
184.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
61.823
966021AG1-471 GEN
Solar/Wind Harmer
0.34
971485AH1-239 GEN
Solar/Wind Harmer
0.479
964901AG1-354 GEN
Solar/Wind Harmer
0.528
964781AG1-341 GEN
Solar/Wind Harmer
0.332
972273AH1-721 GEN
50/50
215.886
950011AG9-010
External Queue
0.4137878715991974
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.051
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.355
NYPJM->LTFIMP_NY
CLTF
0.018
LGEELTFEXP_LGEE->PJM
CLTF
0.033
WECLTFEXP_WEC->PJM
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
0.077
TVALTFEXP_TVA->PJM
CLTF
0.654
MECLTFEXP_MEC->PJM
CLTF
0.45
LAGNLTFEXP_LAGN->PJM
CLTF
0.992
SIGELTFEXP_SIGE->PJM
CLTF
0.017
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.401
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 215.89 MW.

Details for 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:173.49 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:308.8
MW Contribution:
176.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
59.555
972273AH1-721 GEN
50/50
207.269
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.458
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.346
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.315
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.274
NYPJM->LTFIMP_NY
CLTF
0.009
LGEELTFEXP_LGEE->PJM
CLTF
0.022
WECLTFEXP_WEC->PJM
CLTF
0.039
CPLELTFEXP_CPLE->PJM
CLTF
0.065
TVALTFEXP_TVA->PJM
CLTF
0.419
MECLTFEXP_MEC->PJM
CLTF
0.278
LAGNLTFEXP_LAGN->PJM
CLTF
0.632
SIGELTFEXP_SIGE->PJM
CLTF
0.011
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.255
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 207.27 MW.

Details for [AH1-721] 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:136.28 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:242.57
MW Contribution:
176.54
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
207.269
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 207.27 MW.

Details for 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.66 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:237.92
MW Contribution:
134.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.492
3429031COOPER2 G
50/50
45.681
972273AH1-721 GEN
50/50
158.182
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.728
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.787
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.707
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.112
NYPJM->LTFIMP_NY
CLTF
0.009
WECLTFEXP_WEC->PJM
CLTF
0.019
CPLELTFEXP_CPLE->PJM
CLTF
0.023
TVALTFEXP_TVA->PJM
CLTF
0.233
MECLTFEXP_MEC->PJM
CLTF
0.146
LAGNLTFEXP_LAGN->PJM
CLTF
0.343
SIGELTFEXP_SIGE->PJM
CLTF
0.005
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.174
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 158.18 MW.

Details for 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:133.66 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:237.92
MW Contribution:
134.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
45.681
3429451LAUREL 1G
50/50
0.492
972273AH1-721 GEN
50/50
158.182
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.728
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.787
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.707
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.112
NYPJM->LTFIMP_NY
CLTF
0.009
WECLTFEXP_WEC->PJM
CLTF
0.019
CPLELTFEXP_CPLE->PJM
CLTF
0.023
TVALTFEXP_TVA->PJM
CLTF
0.233
MECLTFEXP_MEC->PJM
CLTF
0.146
LAGNLTFEXP_LAGN->PJM
CLTF
0.343
SIGELTFEXP_SIGE->PJM
CLTF
0.005
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.174
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 158.18 MW.

Details for 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:133.16 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:237.03
MW Contribution:
133.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
45.812
3429451LAUREL 1G
50/50
0.489
972273AH1-721 GEN
50/50
157.142
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.733
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.795
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.71
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.113
NYPJM->LTFIMP_NY
CLTF
0.009
WECLTFEXP_WEC->PJM
CLTF
0.02
CPLELTFEXP_CPLE->PJM
CLTF
0.023
TVALTFEXP_TVA->PJM
CLTF
0.234
MECLTFEXP_MEC->PJM
CLTF
0.147
LAGNLTFEXP_LAGN->PJM
CLTF
0.344
SIGELTFEXP_SIGE->PJM
CLTF
0.005
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.173
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 157.14 MW.

Details for [AH1-721] 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.34 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:187.5
MW Contribution:
134.59
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
158.182
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 158.18 MW.

Details for [AH1-721] 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.34 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:187.5
MW Contribution:
134.59
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
158.182
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 158.18 MW.

Details for [AH1-721] 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.75 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:186.45
MW Contribution:
133.48
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
157.142
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 157.14 MW.

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:176.86 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:886.08
MW Contribution:
697.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
200.23
966021AG1-471 GEN
Solar/Wind Harmer
0.25
971485AH1-239 GEN
Solar/Wind Harmer
0.329
972273AH1-721 GEN
50/50
697.678
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.507
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.306
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.271
G-007ALTFEXP_G-007A->PJM
CMTX
0.031
VFTLTFEXP_VFT->PJM
CMTX
0.084
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.077
TVALTFEXP_TVA->PJM
CLTF
0.128
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
MECLTFEXP_MEC->PJM
CLTF
0.009
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.225
LAGNLTFEXP_LAGN->PJM
CLTF
0.191
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.488

Details for [AH1-721] 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:136.31 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:682.92
MW Contribution:
697.68
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
697.678

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.86 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:670.64
MW Contribution:
544.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.78
339206AE1-143 GEN
Solar/Wind Helper
0.388
3429031COOPER2 G
50/50
156.82
339241AF1-083 GEN
Solar/Wind Helper
0.185
339236AF1-050_GEN
Solar/Wind Helper
0.169
972273AH1-721 GEN
50/50
544.091
339231AF1-038_GEN
Solar/Wind Helper
0.289
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.056
G-007ALTFEXP_G-007A->PJM
CMTX
0.029
VFTLTFEXP_VFT->PJM
CMTX
0.077
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.041
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.028
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.973
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.187
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.669
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.235

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:133.86 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:670.63
MW Contribution:
544.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
156.82
339241AF1-083 GEN
Solar/Wind Helper
0.185
339236AF1-050_GEN
Solar/Wind Helper
0.169
3429451LAUREL 1G
50/50
1.78
339206AE1-143 GEN
Solar/Wind Helper
0.388
972273AH1-721 GEN
50/50
544.091
339231AF1-038_GEN
Solar/Wind Helper
0.289
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.056
G-007ALTFEXP_G-007A->PJM
CMTX
0.029
VFTLTFEXP_VFT->PJM
CMTX
0.077
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.041
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.028
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.973
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.187
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.669
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.235

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:133.4 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:668.31
MW Contribution:
541.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
157.168
339241AF1-083 GEN
Solar/Wind Helper
0.185
339236AF1-050_GEN
Solar/Wind Helper
0.168
3429451LAUREL 1G
50/50
1.771
339206AE1-143 GEN
Solar/Wind Helper
0.386
972273AH1-721 GEN
50/50
541.313
339231AF1-038_GEN
Solar/Wind Helper
0.287
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.056
G-007ALTFEXP_G-007A->PJM
CMTX
0.029
VFTLTFEXP_VFT->PJM
CMTX
0.077
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.041
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.028
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.968
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.186
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.665
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.234

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EXT_324130 5ALCALDE 161 324141 5ELIHU 161 1_SRT-W


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EXT_324130 5ALCALDE 161 324141 5ELIHU 161 1_SRT-W
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.89 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:510.46
MW Contribution:
445.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.48
339206AE1-143 GEN
Solar/Wind Helper
0.503
3429031COOPER2 G
50/50
128.503
339241AF1-083 GEN
Solar/Wind Helper
0.241
339236AF1-050_GEN
Solar/Wind Helper
0.221
972273AH1-721 GEN
50/50
445.944
339255AE2-071 GEN
Solar/Wind Helper
0.1
339231AF1-038_GEN
Solar/Wind Helper
0.221
339250AF1-203 GEN
Solar/Wind Helper
0.057
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.105
G-007ALTFEXP_G-007A->PJM
CMTX
0.052
VFTLTFEXP_VFT->PJM
CMTX
0.141
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.054
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.037
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.21
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.196
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.718
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.126

Details for [AH1-721] 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.61 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:509.06
MW Contribution:
544.09
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
544.091

Details for [AH1-721] 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.61 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:509.06
MW Contribution:
544.09
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
544.091

Details for [AH1-721] 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.09 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:506.45
MW Contribution:
541.31
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
541.313

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:226.85 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:691.9
MW Contribution:
577.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.86
966021AG1-471 GEN
Solar/Wind Harmer
0.269
971485AH1-239 GEN
Solar/Wind Harmer
0.36
3429031COOPER2 G
50/50
166.522
972273AH1-721 GEN
50/50
577.838
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.851
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.487
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.209
NYPJM->LTFIMP_NY
CLTF
0.009
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.052
TVALTFEXP_TVA->PJM
CLTF
0.224
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.141
MECLTFEXP_MEC->PJM
CLTF
0.024
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.438
LAGNLTFEXP_LAGN->PJM
CLTF
0.3
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.791

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:224.52 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:684.79
MW Contribution:
578.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.864
966021AG1-471 GEN
Solar/Wind Harmer
0.259
971485AH1-239 GEN
Solar/Wind Harmer
0.348
3429031COOPER2 G
50/50
166.839
972273AH1-721 GEN
50/50
578.937
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.661
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.392
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.167
NYPJM->LTFIMP_NY
CLTF
0.009
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.041
TVALTFEXP_TVA->PJM
CLTF
0.189
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.135
MECLTFEXP_MEC->PJM
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.418
LAGNLTFEXP_LAGN->PJM
CLTF
0.251
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.714

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1008_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:224.35 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:684.28
MW Contribution:
579.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.868
966021AG1-471 GEN
Solar/Wind Harmer
0.259
971485AH1-239 GEN
Solar/Wind Harmer
0.348
3429031COOPER2 G
50/50
167.08
972273AH1-721 GEN
50/50
579.78
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.616
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.379
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.169
NYPJM->LTFIMP_NY
CLTF
0.009
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.042
TVALTFEXP_TVA->PJM
CLTF
0.186
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.138
MECLTFEXP_MEC->PJM
CLTF
0.007
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.43
LAGNLTFEXP_LAGN->PJM
CLTF
0.246
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.728

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:224.35 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:684.28
MW Contribution:
579.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.868
966021AG1-471 GEN
Solar/Wind Harmer
0.259
971485AH1-239 GEN
Solar/Wind Harmer
0.348
3429031COOPER2 G
50/50
167.08
972273AH1-721 GEN
50/50
579.78
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.616
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.379
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.169
NYPJM->LTFIMP_NY
CLTF
0.009
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.042
TVALTFEXP_TVA->PJM
CLTF
0.186
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.138
MECLTFEXP_MEC->PJM
CLTF
0.007
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.43
LAGNLTFEXP_LAGN->PJM
CLTF
0.246
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.728

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:223.93 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:682.98
MW Contribution:
581.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.875
966021AG1-471 GEN
Solar/Wind Harmer
0.252
971485AH1-239 GEN
Solar/Wind Harmer
0.337
3429031COOPER2 G
50/50
167.628
972273AH1-721 GEN
50/50
581.687
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.39
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.279
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.134
NYPJM->LTFIMP_NY
CLTF
0.009
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.032
TVALTFEXP_TVA->PJM
CLTF
0.152
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.136
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.426
LAGNLTFEXP_LAGN->PJM
CLTF
0.196
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.674

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:184.26 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:561.98
MW Contribution:
370.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
124.571
970653AG2-424 GEN
Solar/Wind Harmer
0.398
3429451LAUREL 1G
50/50
2.116
966021AG1-471 GEN
Solar/Wind Harmer
0.544
971485AH1-239 GEN
Solar/Wind Harmer
0.77
964901AG1-354 GEN
Solar/Wind Harmer
0.914
964781AG1-341 GEN
Solar/Wind Harmer
0.61
972273AH1-721 GEN
50/50
434.378
970653AG2-424 GEN
Solar/Wind Harmer
0.16
950011AG9-010
External Queue
0.6617914438247681
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.868
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.761
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.921
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.833
NYPJM->LTFIMP_NY
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.191
TVALTFEXP_TVA->PJM
CLTF
1.281
MECLTFEXP_MEC->PJM
CLTF
0.784
LAGNLTFEXP_LAGN->PJM
CLTF
1.914
SIGELTFEXP_SIGE->PJM
CLTF
0.027
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.093
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 434.38 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.25 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:561.97
MW Contribution:
370.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.116
966021AG1-471 GEN
Solar/Wind Harmer
0.544
971485AH1-239 GEN
Solar/Wind Harmer
0.77
964901AG1-354 GEN
Solar/Wind Harmer
0.914
964781AG1-341 GEN
Solar/Wind Harmer
0.61
3429031COOPER2 G
50/50
124.571
970653AG2-424 GEN
Solar/Wind Harmer
0.398
972273AH1-721 GEN
50/50
434.378
970653AG2-424 GEN
Solar/Wind Harmer
0.16
950011AG9-010
External Queue
0.6617914438247681
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.868
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.761
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.921
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.833
NYPJM->LTFIMP_NY
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.191
TVALTFEXP_TVA->PJM
CLTF
1.281
MECLTFEXP_MEC->PJM
CLTF
0.784
LAGNLTFEXP_LAGN->PJM
CLTF
1.914
SIGELTFEXP_SIGE->PJM
CLTF
0.027
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.093
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 434.38 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.25 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:561.96
MW Contribution:
370.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.116
966021AG1-471 GEN
Solar/Wind Harmer
0.544
971485AH1-239 GEN
Solar/Wind Harmer
0.77
964901AG1-354 GEN
Solar/Wind Harmer
0.914
964781AG1-341 GEN
Solar/Wind Harmer
0.61
3429031COOPER2 G
50/50
124.571
970653AG2-424 GEN
Solar/Wind Harmer
0.398
972273AH1-721 GEN
50/50
434.378
970653AG2-424 GEN
Solar/Wind Harmer
0.16
950011AG9-010
External Queue
0.6617914438247681
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.868
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.761
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.921
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.833
NYPJM->LTFIMP_NY
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.191
TVALTFEXP_TVA->PJM
CLTF
1.281
MECLTFEXP_MEC->PJM
CLTF
0.784
LAGNLTFEXP_LAGN->PJM
CLTF
1.914
SIGELTFEXP_SIGE->PJM
CLTF
0.027
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.093
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 434.38 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:183.81 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:560.61
MW Contribution:
371.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.119
966021AG1-471 GEN
Solar/Wind Harmer
0.546
971485AH1-239 GEN
Solar/Wind Harmer
0.773
964901AG1-354 GEN
Solar/Wind Harmer
0.916
964781AG1-341 GEN
Solar/Wind Harmer
0.612
3429031COOPER2 G
50/50
124.788
970653AG2-424 GEN
Solar/Wind Harmer
0.399
972273AH1-721 GEN
50/50
435.138
970653AG2-424 GEN
Solar/Wind Harmer
0.161
950011AG9-010
External Queue
0.6634839773178101
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.891
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.857
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.964
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.856
NYPJM->LTFIMP_NY
CLTF
0.04
WECLTFEXP_WEC->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.198
TVALTFEXP_TVA->PJM
CLTF
1.295
MECLTFEXP_MEC->PJM
CLTF
0.79
LAGNLTFEXP_LAGN->PJM
CLTF
1.936
SIGELTFEXP_SIGE->PJM
CLTF
0.027
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.112
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 435.14 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:183.8 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:560.6
MW Contribution:
371.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.119
966021AG1-471 GEN
Solar/Wind Harmer
0.546
971485AH1-239 GEN
Solar/Wind Harmer
0.773
964901AG1-354 GEN
Solar/Wind Harmer
0.916
964781AG1-341 GEN
Solar/Wind Harmer
0.612
3429031COOPER2 G
50/50
124.788
970653AG2-424 GEN
Solar/Wind Harmer
0.399
972273AH1-721 GEN
50/50
435.138
970653AG2-424 GEN
Solar/Wind Harmer
0.161
950011AG9-010
External Queue
0.6634839773178101
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.891
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.857
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.964
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.856
NYPJM->LTFIMP_NY
CLTF
0.04
WECLTFEXP_WEC->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.198
TVALTFEXP_TVA->PJM
CLTF
1.295
MECLTFEXP_MEC->PJM
CLTF
0.79
LAGNLTFEXP_LAGN->PJM
CLTF
1.936
SIGELTFEXP_SIGE->PJM
CLTF
0.027
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.112
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 435.14 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:183.79 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:560.55
MW Contribution:
370.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
124.677
970653AG2-424 GEN
Solar/Wind Harmer
0.399
3429451LAUREL 1G
50/50
2.117
966021AG1-471 GEN
Solar/Wind Harmer
0.545
971485AH1-239 GEN
Solar/Wind Harmer
0.771
964901AG1-354 GEN
Solar/Wind Harmer
0.915
964781AG1-341 GEN
Solar/Wind Harmer
0.611
972273AH1-721 GEN
50/50
434.751
970653AG2-424 GEN
Solar/Wind Harmer
0.16
950011AG9-010
External Queue
0.6627915501594543
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.881
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.813
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.943
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.845
NYPJM->LTFIMP_NY
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.195
TVALTFEXP_TVA->PJM
CLTF
1.288
MECLTFEXP_MEC->PJM
CLTF
0.787
LAGNLTFEXP_LAGN->PJM
CLTF
1.925
SIGELTFEXP_SIGE->PJM
CLTF
0.027
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.102
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 434.75 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 1_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:183.38 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:559.3
MW Contribution:
439.65
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
148.683
3429451LAUREL 1G
50/50
1.661
966021AG1-471 GEN
Solar/Wind Harmer
0.331
971485AH1-239 GEN
Solar/Wind Harmer
0.45
972273AH1-721 GEN
50/50
516.214
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.251
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.856
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.859
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.268
NYPJM->LTFIMP_NY
CLTF
0.011
GibsonPJM->LTFIMP_GIBSON
CLTF
0
WECLTFEXP_WEC->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
0.065
TVALTFEXP_TVA->PJM
CLTF
0.339
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.12
MECLTFEXP_MEC->PJM
CLTF
0.112
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.354
LAGNLTFEXP_LAGN->PJM
CLTF
0.48
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.831
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 516.21 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOP-LAURD 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOP-LAURD 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:170.9 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:521.26
MW Contribution:
371.18
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
124.848
970653AG2-424 GEN
Solar/Wind Harmer
0.401
966021AG1-471 GEN
Solar/Wind Harmer
0.547
971485AH1-239 GEN
Solar/Wind Harmer
0.774
964901AG1-354 GEN
Solar/Wind Harmer
0.918
964781AG1-341 GEN
Solar/Wind Harmer
0.613
972273AH1-721 GEN
50/50
435.348
970653AG2-424 GEN
Solar/Wind Harmer
0.161
950011AG9-010
External Queue
0.6634839773178101
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.168
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.051
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.926
NYPJM->LTFIMP_NY
CLTF
0.026
WECLTFEXP_WEC->PJM
CLTF
0.112
CPLELTFEXP_CPLE->PJM
CLTF
0.223
TVALTFEXP_TVA->PJM
CLTF
1.318
MECLTFEXP_MEC->PJM
CLTF
0.828
LAGNLTFEXP_LAGN->PJM
CLTF
1.982
SIGELTFEXP_SIGE->PJM
CLTF
0.029
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.112
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 435.35 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:170.36 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:519.59
MW Contribution:
577.84
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
577.838

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:168.35 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:513.46
MW Contribution:
578.94
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
578.937

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1008_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:168.05 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:512.55
MW Contribution:
579.78
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
579.78

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:168.05 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:512.55
MW Contribution:
579.78
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
579.78

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:167.7 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:511.48
MW Contribution:
581.69
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
581.687

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_PULASKI 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_PULASKI 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:166.35 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:507.37
MW Contribution:
366.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
123.911
3429451LAUREL 1G
50/50
1.353
966021AG1-471 GEN
Solar/Wind Harmer
0.503
971485AH1-239 GEN
Solar/Wind Harmer
0.702
964781AG1-341 GEN
Solar/Wind Harmer
0.475
964901AG1-354 GEN
Solar/Wind Harmer
0.518
972273AH1-721 GEN
50/50
430.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.281
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.261
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.921
NYPJM->LTFIMP_NY
CLTF
0.018
WECLTFEXP_WEC->PJM
CLTF
0.058
CPLELTFEXP_CPLE->PJM
CLTF
0.233
TVALTFEXP_TVA->PJM
CLTF
1.094
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.109
MECLTFEXP_MEC->PJM
CLTF
0.533
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.243
LAGNLTFEXP_LAGN->PJM
CLTF
1.592
SIGELTFEXP_SIGE->PJM
CLTF
0.008
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.718
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 430.19 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:149.52 %
Rating:279.0 MVA
Rating Type:A
MVA to Mitigate:417.15
MW Contribution:
321.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.174
966021AG1-471 GEN
Solar/Wind Harmer
0.466
971485AH1-239 GEN
Solar/Wind Harmer
0.658
964901AG1-354 GEN
Solar/Wind Harmer
0.782
964781AG1-341 GEN
Solar/Wind Harmer
0.521
3429031COOPER2 G
50/50
108.652
970653AG2-424 GEN
Solar/Wind Harmer
0.337
972273AH1-721 GEN
50/50
377.185
970653AG2-424 GEN
Solar/Wind Harmer
0.135
950011AG9-010
External Queue
0.57616126537323
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.058
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.825
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.149
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.665
NYPJM->LTFIMP_NY
CLTF
0.029
WECLTFEXP_WEC->PJM
CLTF
0.081
CPLELTFEXP_CPLE->PJM
CLTF
0.154
TVALTFEXP_TVA->PJM
CLTF
1.052
MECLTFEXP_MEC->PJM
CLTF
0.625
LAGNLTFEXP_LAGN->PJM
CLTF
1.561
SIGELTFEXP_SIGE->PJM
CLTF
0.019
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.069
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 377.19 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.04 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:408.81
MW Contribution:
370.35
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
434.378
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 434.38 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:134.03 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:408.8
MW Contribution:
370.35
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
434.378
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 434.38 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.03 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:408.8
MW Contribution:
370.35
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
434.378
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 434.38 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:133.48 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:407.13
MW Contribution:
370.67
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
434.751
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 434.75 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:133.43 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:406.98
MW Contribution:
371.0
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
435.138
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 435.14 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.43 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:406.98
MW Contribution:
371.0
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
435.138
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 435.14 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 1_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:132.53 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:404.22
MW Contribution:
516.21
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
516.214

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOP-LAURD 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOP-LAURD 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.04 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:369.16
MW Contribution:
435.35
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
435.348

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_PULASKI 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_PULASKI 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.88 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:362.6
MW Contribution:
430.19
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
430.188

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.47 %
Rating:279.0 MVA
Rating Type:A
MVA to Mitigate:285.88
MW Contribution:
377.19
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
377.185

Details for 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:277.0 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:301.93
MW Contribution:
292.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.955
972273AH1-721 GEN
50/50
292.892
NYPJM->LTFIMP_NY
CLTF
0.003
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.081
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.056
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.555
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.108
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:277.0 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:301.93
MW Contribution:
292.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.955
972273AH1-721 GEN
50/50
292.892
NYPJM->LTFIMP_NY
CLTF
0.003
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.081
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.056
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.555
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.108
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:275.1 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:299.86
MW Contribution:
292.89
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
292.892

Details for [AH1-721] 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:275.1 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:299.86
MW Contribution:
292.89
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
292.892

Details for 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:274.73 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:299.46
MW Contribution:
291.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.948
972273AH1-721 GEN
50/50
291.021
NYPJM->LTFIMP_NY
CLTF
0.004
LGEELTFEXP_LGEE->PJM
CLTF
0.004
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.083
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.057
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.538
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.017
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.087
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:272.88 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:297.44
MW Contribution:
291.02
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
291.021

Details for 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:118.37 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:129.02
MW Contribution:
75.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
24.77
972273AH1-721 GEN
50/50
88.322
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.149
NYPJM->LTFIMP_NY
CLTF
0.006
LGEELTFEXP_LGEE->PJM
CLTF
0.093
WECLTFEXP_WEC->PJM
CLTF
0.005
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.052
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.036
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.025
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.004
MDUPJM->LTFIMP_MDU
CLTF
0
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 88.32 MW.

Details for 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P1-2_COOP 161 TIE_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.59 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:119.45
MW Contribution:
72.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.244
3429031COOPER2 G
50/50
20.254
972273AH1-721 GEN
50/50
72.231
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.002
LGEELTFEXP_LGEE->PJM
CLTF
0.071
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.091
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.063
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.559
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:204.8 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:364.54
MW Contribution:
318.27
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.55
972273AH1-721 GEN
50/50
318.27
NYPJM->LTFIMP_NY
CLTF
0.014
LGEELTFEXP_LGEE->PJM
CLTF
0.002
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.079
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.054
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.268
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.003
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.024
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:203.68 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:362.54
MW Contribution:
318.27
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
318.27

Details for 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.4 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:233.89
MW Contribution:
194.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.148
972273AH1-721 GEN
50/50
194.969
NYPJM->LTFIMP_NY
CLTF
0.012
LGEELTFEXP_LGEE->PJM
CLTF
0.002
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.044
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.034
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.29 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:233.69
MW Contribution:
194.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.147
972273AH1-721 GEN
50/50
194.726
NYPJM->LTFIMP_NY
CLTF
0.012
LGEELTFEXP_LGEE->PJM
CLTF
0.004
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.045
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.034
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:131.29 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:233.69
MW Contribution:
194.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.147
972273AH1-721 GEN
50/50
194.726
NYPJM->LTFIMP_NY
CLTF
0.012
LGEELTFEXP_LGEE->PJM
CLTF
0.004
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.045
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.034
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.69 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:232.62
MW Contribution:
194.97
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
194.969

Details for [AH1-721] 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.58 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:232.43
MW Contribution:
194.73
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
194.726

Details for [AH1-721] 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.58 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:232.43
MW Contribution:
194.73
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
194.726

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:140.35 %
Rating:351.0 MVA
Rating Type:B
MVA to Mitigate:492.62
MW Contribution:
467.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.276
972273AH1-721 GEN
50/50
467.377
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.07
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.539
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.287
NYPJM->LTFIMP_NY
CLTF
0.011
CPLELTFEXP_CPLE->PJM
CLTF
0.074
TVALTFEXP_TVA->PJM
CLTF
0.184
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.022
MECLTFEXP_MEC->PJM
CLTF
0.048
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.054
LAGNLTFEXP_LAGN->PJM
CLTF
0.273
SIGELTFEXP_SIGE->PJM
CLTF
0.001
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.306

Details for [AH1-721] 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:138.88 %
Rating:351.0 MVA
Rating Type:B
MVA to Mitigate:487.47
MW Contribution:
467.38
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
467.377

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:256.09 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:855.33
MW Contribution:
785.65
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
3.826
972273AH1-721 GEN
50/50
785.647
NYPJM->LTFIMP_NY
CLTF
0.025
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.026
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.016
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.116
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.025
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.078
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:254.85 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:851.21
MW Contribution:
785.65
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
785.647

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:180.81 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:603.89
MW Contribution:
494.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.878
966021AG1-471 GEN
Solar/Wind Harmer
0.258
971485AH1-239 GEN
Solar/Wind Harmer
0.35
972273AH1-721 GEN
50/50
494.626
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.533
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.356
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.047
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.325
NYPJM->LTFIMP_NY
CLTF
0.021
WECLTFEXP_WEC->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
0.076
TVALTFEXP_TVA->PJM
CLTF
0.349
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.008
MECLTFEXP_MEC->PJM
CLTF
0.157
LAGNLTFEXP_LAGN->PJM
CLTF
0.518
SIGELTFEXP_SIGE->PJM
CLTF
0.004
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.45

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.88 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:600.79
MW Contribution:
492.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.871
966021AG1-471 GEN
Solar/Wind Harmer
0.256
971485AH1-239 GEN
Solar/Wind Harmer
0.348
972273AH1-721 GEN
50/50
492.755
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.584
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.419
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.316
NYPJM->LTFIMP_NY
CLTF
0.022
WECLTFEXP_WEC->PJM
CLTF
0.015
CPLELTFEXP_CPLE->PJM
CLTF
0.073
TVALTFEXP_TVA->PJM
CLTF
0.352
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.002
MECLTFEXP_MEC->PJM
CLTF
0.164
LAGNLTFEXP_LAGN->PJM
CLTF
0.524
SIGELTFEXP_SIGE->PJM
CLTF
0.005
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.424

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:179.88 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:600.79
MW Contribution:
492.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.871
966021AG1-471 GEN
Solar/Wind Harmer
0.256
971485AH1-239 GEN
Solar/Wind Harmer
0.348
972273AH1-721 GEN
50/50
492.755
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.584
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.419
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.316
NYPJM->LTFIMP_NY
CLTF
0.022
WECLTFEXP_WEC->PJM
CLTF
0.015
CPLELTFEXP_CPLE->PJM
CLTF
0.073
TVALTFEXP_TVA->PJM
CLTF
0.352
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.002
MECLTFEXP_MEC->PJM
CLTF
0.164
LAGNLTFEXP_LAGN->PJM
CLTF
0.524
SIGELTFEXP_SIGE->PJM
CLTF
0.005
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.424

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:177.54 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:593.0
MW Contribution:
494.63
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
494.626

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:176.6 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:589.85
MW Contribution:
492.75
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
492.755

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:176.6 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:589.85
MW Contribution:
492.75
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
492.755

Details for 5PITTSBURG-2PITTSBRG KU 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5PITTSBURG-2PITTSBRG KU 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:116.06 %
Rating:143.0 MVA
Rating Type:B
MVA to Mitigate:165.96
MW Contribution:
108.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.527
972273AH1-721 GEN
50/50
108.174
NYPJM->LTFIMP_NY
CLTF
0.005
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.045
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.185
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.061
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5PITTSBURG-2PITTSBRG KU 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5PITTSBURG-2PITTSBRG KU 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:115.45 %
Rating:143.0 MVA
Rating Type:B
MVA to Mitigate:165.09
MW Contribution:
108.17
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
108.174

Details for 5PITTSBURG-5TYNER 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5PITTSBURG-5TYNER 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:131.76 %
Rating:250.0 MVA
Rating Type:B
MVA to Mitigate:329.4
MW Contribution:
359.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.749
972273AH1-721 GEN
50/50
359.203
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.119
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.992
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.52
NYPJM->LTFIMP_NY
CLTF
0.007
WECLTFEXP_WEC->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
0.139
TVALTFEXP_TVA->PJM
CLTF
0.323
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.006
MECLTFEXP_MEC->PJM
CLTF
0.124
LAGNLTFEXP_LAGN->PJM
CLTF
0.494
SIGELTFEXP_SIGE->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.441

Details for [AH1-721] 5PITTSBURG-5TYNER 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5PITTSBURG-5TYNER 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:128.86 %
Rating:250.0 MVA
Rating Type:B
MVA to Mitigate:322.16
MW Contribution:
359.2
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
359.203

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.52 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:412.55
MW Contribution:
386.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.882
966021AG1-471 GEN
Solar/Wind Harmer
0.16
971485AH1-239 GEN
Solar/Wind Harmer
0.213
972273AH1-721 GEN
50/50
386.389
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.312
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.134
NYPJM->LTFIMP_NY
CLTF
0.011
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.031
TVALTFEXP_TVA->PJM
CLTF
0.121
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
MECLTFEXP_MEC->PJM
CLTF
0.019
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
LAGNLTFEXP_LAGN->PJM
CLTF
0.171
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.315

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:123.52 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:412.55
MW Contribution:
386.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.882
966021AG1-471 GEN
Solar/Wind Harmer
0.16
971485AH1-239 GEN
Solar/Wind Harmer
0.213
972273AH1-721 GEN
50/50
386.389
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.312
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.134
NYPJM->LTFIMP_NY
CLTF
0.011
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.031
TVALTFEXP_TVA->PJM
CLTF
0.121
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
MECLTFEXP_MEC->PJM
CLTF
0.019
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
LAGNLTFEXP_LAGN->PJM
CLTF
0.171
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.315

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.51 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:412.54
MW Contribution:
386.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.882
966021AG1-471 GEN
Solar/Wind Harmer
0.16
971485AH1-239 GEN
Solar/Wind Harmer
0.213
972273AH1-721 GEN
50/50
386.401
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.312
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.135
NYPJM->LTFIMP_NY
CLTF
0.011
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.031
TVALTFEXP_TVA->PJM
CLTF
0.121
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
MECLTFEXP_MEC->PJM
CLTF
0.019
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
LAGNLTFEXP_LAGN->PJM
CLTF
0.171
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.316

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.51 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:412.53
MW Contribution:
386.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.882
966021AG1-471 GEN
Solar/Wind Harmer
0.16
971485AH1-239 GEN
Solar/Wind Harmer
0.213
972273AH1-721 GEN
50/50
386.401
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.312
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.135
NYPJM->LTFIMP_NY
CLTF
0.011
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.031
TVALTFEXP_TVA->PJM
CLTF
0.121
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
MECLTFEXP_MEC->PJM
CLTF
0.019
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
LAGNLTFEXP_LAGN->PJM
CLTF
0.171
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.316

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:123.51 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:412.53
MW Contribution:
386.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.882
966021AG1-471 GEN
Solar/Wind Harmer
0.16
971485AH1-239 GEN
Solar/Wind Harmer
0.213
972273AH1-721 GEN
50/50
386.401
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.312
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.135
NYPJM->LTFIMP_NY
CLTF
0.011
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.031
TVALTFEXP_TVA->PJM
CLTF
0.121
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
MECLTFEXP_MEC->PJM
CLTF
0.019
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
LAGNLTFEXP_LAGN->PJM
CLTF
0.171
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.316

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:123.51 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:412.52
MW Contribution:
386.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.882
966021AG1-471 GEN
Solar/Wind Harmer
0.16
971485AH1-239 GEN
Solar/Wind Harmer
0.213
972273AH1-721 GEN
50/50
386.409
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.574
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.313
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.135
NYPJM->LTFIMP_NY
CLTF
0.011
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.032
TVALTFEXP_TVA->PJM
CLTF
0.121
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
MECLTFEXP_MEC->PJM
CLTF
0.019
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
LAGNLTFEXP_LAGN->PJM
CLTF
0.171
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.316

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.25 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:408.32
MW Contribution:
386.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
386.389

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:122.25 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:408.32
MW Contribution:
386.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
386.389

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.25 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:408.3
MW Contribution:
386.4
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
386.401

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:122.24 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:408.28
MW Contribution:
386.4
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
386.401

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.24 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:408.28
MW Contribution:
386.4
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
386.401

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:122.24 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:408.27
MW Contribution:
386.41
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
386.409

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.58 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:355.99
MW Contribution:
362.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
362.326
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.026
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.263
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.159
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.141
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
VFTLTFEXP_VFT->PJM
CMTX
0.044
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.04
TVALTFEXP_TVA->PJM
CLTF
0.067
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.036
MECLTFEXP_MEC->PJM
CLTF
0.005
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.117
LAGNLTFEXP_LAGN->PJM
CLTF
0.099
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.253

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.2 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:354.72
MW Contribution:
362.33
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
362.326

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:198.38 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:511.81
MW Contribution:
541.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339241AF1-083 GEN
Solar/Wind Helper
0.185
339236AF1-050_GEN
Solar/Wind Helper
0.168
3429451LAUREL 1G
50/50
1.771
339206AE1-143 GEN
Solar/Wind Helper
0.386
972273AH1-721 GEN
50/50
541.313
339231AF1-038_GEN
Solar/Wind Helper
0.287
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.056
G-007ALTFEXP_G-007A->PJM
CMTX
0.029
VFTLTFEXP_VFT->PJM
CMTX
0.077
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.041
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.028
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.968
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.186
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.665
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.234

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:196.33 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:506.53
MW Contribution:
541.31
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
541.313

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:147.91 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:381.61
MW Contribution:
357.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.742
966021AG1-471 GEN
Solar/Wind Harmer
0.148
972273AH1-721 GEN
50/50
357.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.529
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.289
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.124
NYPJM->LTFIMP_NY
CLTF
0.01
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.029
TVALTFEXP_TVA->PJM
CLTF
0.112
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.04
MECLTFEXP_MEC->PJM
CLTF
0.017
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.121
LAGNLTFEXP_LAGN->PJM
CLTF
0.158
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.292

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:147.91 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:381.61
MW Contribution:
357.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.742
966021AG1-471 GEN
Solar/Wind Harmer
0.148
972273AH1-721 GEN
50/50
357.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.529
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.289
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.124
NYPJM->LTFIMP_NY
CLTF
0.01
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.029
TVALTFEXP_TVA->PJM
CLTF
0.112
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.04
MECLTFEXP_MEC->PJM
CLTF
0.017
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.121
LAGNLTFEXP_LAGN->PJM
CLTF
0.158
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.292

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-3_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-3_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.9 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:381.59
MW Contribution:
357.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.742
966021AG1-471 GEN
Solar/Wind Harmer
0.148
972273AH1-721 GEN
50/50
357.634
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.531
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.289
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.125
NYPJM->LTFIMP_NY
CLTF
0.01
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.029
TVALTFEXP_TVA->PJM
CLTF
0.112
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.04
MECLTFEXP_MEC->PJM
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.121
LAGNLTFEXP_LAGN->PJM
CLTF
0.158
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.292

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P4-5_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P4-5_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.9 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:381.58
MW Contribution:
357.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.742
966021AG1-471 GEN
Solar/Wind Harmer
0.148
972273AH1-721 GEN
50/50
357.634
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.531
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.289
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.125
NYPJM->LTFIMP_NY
CLTF
0.01
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.029
TVALTFEXP_TVA->PJM
CLTF
0.112
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.04
MECLTFEXP_MEC->PJM
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.121
LAGNLTFEXP_LAGN->PJM
CLTF
0.158
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.292

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:147.9 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:381.58
MW Contribution:
357.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.742
966021AG1-471 GEN
Solar/Wind Harmer
0.148
972273AH1-721 GEN
50/50
357.634
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.531
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.289
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.125
NYPJM->LTFIMP_NY
CLTF
0.01
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.029
TVALTFEXP_TVA->PJM
CLTF
0.112
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.04
MECLTFEXP_MEC->PJM
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.121
LAGNLTFEXP_LAGN->PJM
CLTF
0.158
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.292

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:147.9 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:381.57
MW Contribution:
357.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.742
966021AG1-471 GEN
Solar/Wind Harmer
0.148
972273AH1-721 GEN
50/50
357.642
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.532
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.29
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.125
NYPJM->LTFIMP_NY
CLTF
0.01
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.029
TVALTFEXP_TVA->PJM
CLTF
0.112
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.04
MECLTFEXP_MEC->PJM
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.121
LAGNLTFEXP_LAGN->PJM
CLTF
0.159
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.292

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:146.47 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:377.88
MW Contribution:
357.62
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
357.624

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:146.47 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:377.88
MW Contribution:
357.62
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
357.624

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-3_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-3_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.46 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:377.87
MW Contribution:
357.63
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
357.634

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P4-5_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P4-5_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.46 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:377.85
MW Contribution:
357.63
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
357.634

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:146.46 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:377.85
MW Contribution:
357.63
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
357.634

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:146.45 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:377.84
MW Contribution:
357.64
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
357.642

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.68 %
Rating:250.0 MVA
Rating Type:A
MVA to Mitigate:286.7
MW Contribution:
313.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.016
972273AH1-721 GEN
50/50
313.128
NYPJM->LTFIMP_NY
CLTF
0.001
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.004
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.252
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.089
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.3
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.259

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.87 %
Rating:250.0 MVA
Rating Type:A
MVA to Mitigate:284.66
MW Contribution:
313.13
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
313.128

Details for AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.44 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:313.33
MW Contribution:
292.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.955
972273AH1-721 GEN
50/50
292.892
NYPJM->LTFIMP_NY
CLTF
0.003
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.081
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.056
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.555
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.108
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.44 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:313.32
MW Contribution:
292.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.955
972273AH1-721 GEN
50/50
292.892
NYPJM->LTFIMP_NY
CLTF
0.003
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.081
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.056
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.555
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.108
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.95 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:312.04
MW Contribution:
291.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.948
972273AH1-721 GEN
50/50
291.021
NYPJM->LTFIMP_NY
CLTF
0.004
LGEELTFEXP_LGEE->PJM
CLTF
0.004
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.083
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.057
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.538
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.017
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.087
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:120.47 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:310.81
MW Contribution:
292.89
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
292.892

Details for [AH1-721] AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.47 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:310.81
MW Contribution:
292.89
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
292.892

Details for [AH1-721] AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.98 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:309.55
MW Contribution:
291.02
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
291.021

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:235.3 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:785.9
MW Contribution:
786.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
786

Details for [AH1-721] AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:235.3 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:785.9
MW Contribution:
786.0
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
786

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:157.6 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:526.37
MW Contribution:
494.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
0.259
971485AH1-239 GEN
Solar/Wind Harmer
0.352
972273AH1-721 GEN
50/50
494.979
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.032
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.099
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.878
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.194
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.442
G-007ALTFEXP_G-007A->PJM
CMTX
0.023
VFTLTFEXP_VFT->PJM
CMTX
0.061
WECLTFEXP_WEC->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
0.118
TVALTFEXP_TVA->PJM
CLTF
0.388
MECLTFEXP_MEC->PJM
CLTF
0.222
LAGNLTFEXP_LAGN->PJM
CLTF
0.597
SIGELTFEXP_SIGE->PJM
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.45

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:156.77 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:523.62
MW Contribution:
493.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
0.257
971485AH1-239 GEN
Solar/Wind Harmer
0.349
972273AH1-721 GEN
50/50
493.108
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.027
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.15
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.942
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.21
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.434
G-007ALTFEXP_G-007A->PJM
CMTX
0.02
VFTLTFEXP_VFT->PJM
CMTX
0.053
LGEELTFEXP_LGEE->PJM
CLTF
0.003
WECLTFEXP_WEC->PJM
CLTF
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.116
TVALTFEXP_TVA->PJM
CLTF
0.391
MECLTFEXP_MEC->PJM
CLTF
0.229
LAGNLTFEXP_LAGN->PJM
CLTF
0.603
SIGELTFEXP_SIGE->PJM
CLTF
0.007
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.424

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.77 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:523.61
MW Contribution:
493.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
0.257
971485AH1-239 GEN
Solar/Wind Harmer
0.349
972273AH1-721 GEN
50/50
493.108
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.027
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.15
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.942
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.21
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.434
G-007ALTFEXP_G-007A->PJM
CMTX
0.02
VFTLTFEXP_VFT->PJM
CMTX
0.053
LGEELTFEXP_LGEE->PJM
CLTF
0.003
WECLTFEXP_WEC->PJM
CLTF
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.116
TVALTFEXP_TVA->PJM
CLTF
0.391
MECLTFEXP_MEC->PJM
CLTF
0.229
LAGNLTFEXP_LAGN->PJM
CLTF
0.603
SIGELTFEXP_SIGE->PJM
CLTF
0.007
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.424

Details for [AH1-721] AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.16 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:518.23
MW Contribution:
494.98
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
494.979

Details for [AH1-721] AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:154.3 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:515.37
MW Contribution:
493.11
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
493.108

Details for [AH1-721] AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.3 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:515.37
MW Contribution:
493.11
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
493.108
CONTINGENCY 'EKPC_P2-3_COOP S42-1064_SRT-A'
 OPEN BRANCH FROM BUS 341392 TO BUS 342727 CKT 1   /*2DENNY        69.0 - 5DENNY       161.0
 OPEN BUS 342718                                   /*5COOPER2     161.0
 OPEN BUS 342903                                   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1039_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342900   /*1COOPER1 G    13.8
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-210G_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-2_COOPER 2 161_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 2_SRT-A-2'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-ELIHU161_SRT-A'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P2-2_ELIHU-COOP 161_SRT-A'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 2_SRT-A-1'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 1   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EKPC_P1-2_COOP 161 TIE_SRT-A'
 OPEN BRANCH FROM BUS 342715 TO BUS 342718 CKT 1   /*5COOPER1     161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EXT_324130 5ALCALDE 161 324141 5ELIHU 161 1_SRT-W'
 OPEN BRANCH FROM BUS 324130 TO BUS 324141 CKT 1   /*5ALCALDE     161.0 - 5ELIHU       161.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1014_SRT-A'
 OPEN BRANCH FROM BUS 342742 TO BUS 342745 CKT 1   /*5JABEZ       161.0 - 5JABEZ T     161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342751 CKT 1   /*5JABEZ T     161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342799 CKT 1   /*5JABEZ T     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342748 TO BUS 342751 CKT 1   /*5JAMESTOWN   161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342751 TO BUS 342796 CKT 1   /*5JAMESTOWN T 161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342793 TO BUS 342796 CKT 1   /*5RUSSEL CO   161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342796 TO BUS 360448 CKT 1   /*5RUSSEL CO J 161.0 - 5WOLF CRK HP 161.0
 OPEN BUS 342715                                   /*5COOPER1     161.0
 OPEN BUS 342900                                   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1024_SRT-A'
 OPEN BRANCH FROM BUS 342115 TO BUS 342787 CKT 1   /*2PULASK CO    69.0 - 5PULASK CO   161.0
 OPEN BRANCH FROM BUS 342760 TO BUS 342790 CKT 1   /*5LIBERTY J   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342787 TO BUS 342790 CKT 1   /*5PULASK CO   161.0 - 5PULASK CO J 161.0
 OPEN BUS 342715                                   /*5COOPER1     161.0
 OPEN BUS 342900                                   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1008_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
 OPEN BUS 342900   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-2_COOPER 1 161_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
END
CONTINGENCY 'EKPC_P7-1_LAURL 161 DBL_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
 OPEN BUS 342754                                   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P2-3_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 341740 TO BUS 342754 CKT 1   /*2LAUREL CO    69.0 - 5LAUREL CO   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P2-2_LAUR-LAURD161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P1-2_LAUR-L DAM161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P2-2_LAUREL CO 161_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 1_SRT-A'
 OPEN BRANCH FROM BUS 342115 TO BUS 342787 CKT 1   /*2PULASK CO    69.0 - 5PULASK CO   161.0
 OPEN BRANCH FROM BUS 342715 TO BUS 342790 CKT 1   /*5COOPER1     161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342715 TO BUS 342799 CKT 1   /*5COOPER1     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342742 TO BUS 342745 CKT 1   /*5JABEZ       161.0 - 5JABEZ T     161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342751 CKT 1   /*5JABEZ T     161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342799 CKT 1   /*5JABEZ T     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342748 TO BUS 342751 CKT 1   /*5JAMESTOWN   161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342751 TO BUS 342796 CKT 1   /*5JAMESTOWN T 161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342760 TO BUS 342790 CKT 1   /*5LIBERTY J   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342787 TO BUS 342790 CKT 1   /*5PULASK CO   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342793 TO BUS 342796 CKT 1   /*5RUSSEL CO   161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342796 TO BUS 360448 CKT 1   /*5RUSSEL CO J 161.0 - 5WOLF CRK HP 161.0
END
CONTINGENCY 'EKPC_P2-2_COOP-LAURD 161_SRT-A'
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P2-2_PULASKI 161_SRT-A'
 OPEN BUS 342787   /*5PULASK CO   161.0
 OPEN BUS 342790   /*5PULASK CO J 161.0
END
CONTINGENCY 'EKPC_P2-3_LAURL S50-1014_SRT-A'
 OPEN BRANCH FROM BUS 341740 TO BUS 342754 CKT 1   /*2LAUREL CO    69.0 - 5LAUREL CO   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1014_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
341038 to 341755 ckt 1
341206 to 341347 ckt 1
341347 to 341344 ckt 1
341344 to 342286 ckt 1
341344 to 342286 ckt 2
341392 to 341206 ckt 1
341392 to 341578 ckt 1
324531 to 342287 ckt 1
341722 to 342187 ckt 1
341740 to 324576 ckt 1
341740 to 341722 ckt 1
342187 to 341038 ckt 1
342287 to 324531 ckt 1
342287 to 342286 ckt 1
342286 to 342287 ckt 1
342715 to 341344 ckt 1
342718 to 342715 ckt 1
342718 to 324141 ckt 1
342727 to 341392 ckt 1
342754 to 341740 ckt 1
342754 to 342781 ckt 1
342757 to 342754 ckt 1
342781 to 324688 ckt 1
342781 to 342820 ckt 1
972272 to 342718 ckt 1
972272 to 342718 ckt 2
972272 to 342727 ckt 1
972272 to 342757 ckt 1

Light Load Analysis

The New Service Request AH1-721 was evaluated as a 786.0 MW injection

AH1-721 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 786.0 MW (786.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC173.68 %1180.0B2049.45
72.07
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC173.67 %1180.0B2049.35
72.07
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-L
BreakerAC173.35 %1180.0B2045.56
72.07
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC171.54 %1180.0B2024.13
72.07
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC138.39 %1180.0B1632.98
76.95
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
BreakerAC138.39 %1180.0B1632.98
76.95
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC136.83 %1180.0B1614.63
76.95
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC102.7 %1180.0B1211.91
72.07
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC102.7 %1180.0B1211.91
72.07
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC102.7 %1180.0B1211.81
72.07
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC126.88 %76.0B96.43
88.87
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC126.88 %76.0B96.43
88.87
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1008_SRT-A
BreakerAC123.87 %76.0B94.14
79.17
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC123.87 %76.0B94.14
79.17
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1024_SRT-A
BreakerAC111.12 %76.0B84.45
71.26
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC110.92 %76.0B84.3
88.87
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC110.92 %76.0B84.3
88.87
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1008_SRT-A
BreakerAC110.22 %76.0B83.77
79.17
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC110.22 %76.0B83.77
79.17
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1014_SRT-A
BreakerAC105.55 %76.0B80.22
69.83
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC153.06 %298.0B456.13
307.68
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC131.98 %298.0B393.29
307.68
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EXT_324100 7ALCALDE 345 324130 5ALCALDE 161 1_SRT-L
SingleAC102.05 %200.0B204.1
109.21
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EXT_B-345-100_SRT-L
SingleAC101.96 %200.0B203.92
109.17
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC112.11 %298.0B334.08
326.07
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC111.39 %298.0B331.94
326.07
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-DEN161_SRT-A-1
SingleAC108.39 %298.0B323.01
310.42
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-DEN161_SRT-A-1
SingleAC102.72 %298.0B306.11
310.42
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
SingleAC153.07 %210.0B321.45
308.94
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC147.23 %210.0B309.19
301.79
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC146.29 %210.0B307.21
301.79
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
SingleAC145.06 %210.0B304.63
308.94

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.68 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2049.45
MW Contribution:
72.07
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970417AG2-272 GEN
50/50
8.428
971507AH1-251 GEN
50/50
Charging
5.863
957191AF2-013 GEN
50/50
Charging
10.655
943031AE2-326 GEN
Solar/Wind Harmer
11.709
270069AE2-166 C O1
Solar/Wind Harmer
8.427
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
966881AG1-559 GEN
Solar/Wind Helper
0.447
316473AC1-191 GEN
Solar/Wind Helper
2.427
966871AG1-558 GEN
Solar/Wind Helper
0.436
315651AD1-115 GEN
Solar/Wind Helper
4.201
966001AG1-469 GEN
Solar/Wind Helper
0.423
316258AE1-075 C
Solar/Wind Helper
0.519
315975AC1-164 GENB
Solar/Wind Helper
0.061
316337AD2-073 GEN
Solar/Wind Helper
0.563
961951AG1-038 GEN
Solar/Wind Helper
1.258
315666AE1-190 GEN
Solar/Wind Helper
0.555
316382AG1-145 C
Solar/Wind Helper
0.541
315616AA1-038_C
Solar/Wind Helper
1.957
970563AG2-360 GEN
50/50
45.019
971881AH1-461 GEN
50/50
14.324
970119AG2-088 GEN
50/50
Charging
16.823
972273AH1-721 GEN
50/50
85.07
958121AF2-106 GEN
Solar/Wind Harmer
0
971277AH1-098 GEN
Solar/Wind Harmer
4.144
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971981AH1-535 GEN
Solar/Wind Harmer
7.212
270494AE1-108_GEN
Solar/Wind Helper
5.579
316450AC1-158 RIC
Solar/Wind Helper
0.616
316164AC1-076 GEN
Solar/Wind Helper
1.94
316468AD1-105 GEN
Solar/Wind Helper
2.225
316312AB1-027
Solar/Wind Helper
0.748
316075AC2-137 C
Solar/Wind Helper
0.581
316313AB2-026
Solar/Wind Helper
0.577
315976AC1-164 GENA
Solar/Wind Helper
2.054
316169AC1-164_GENC
Solar/Wind Helper
1.775
957971AF2-091 GEN
Solar/Wind Helper
0.971
316223AC1-118
Solar/Wind Helper
0.567
316203AE2-005 GEN
Solar/Wind Helper
3.616
316156AD2-030 GEN
Solar/Wind Helper
0.548
316159AE1-175 C
Solar/Wind Helper
0.538
970823AG2-518 GEN
50/50
19.371
316303AF2-085
50/50
Charging
2.243
970365AG2-240 GEN
50/50
Charging
1.246
316405AF2-144 C
50/50
Charging
1.174
270583AD2-179 GEN
Solar/Wind Harmer
12.447
971277AH1-098 GEN
Solar/Wind Harmer
4.558
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971329AH1-144 GEN
Solar/Wind Harmer
7.833
943811AF1-049 GEN
Solar/Wind Harmer
0
971461AH1-227 GEN
Solar/Wind Harmer
4.169
971687AH1-348 GEN
Solar/Wind Harmer
0.807
971403AH1-188 GEN
Solar/Wind Harmer
10.665
970281AG2-184 GEN
Solar/Wind Harmer
15.747
972103AH1-617 GEN
Solar/Wind Harmer
14.997
316447AC1-158 HLD
Solar/Wind Helper
5.08
316192AB2-158 GEN
Solar/Wind Helper
2.765
316006AB2-029 C
Solar/Wind Helper
0.541
316405AF2-144 C
Solar/Wind Helper
0.49
316077AC2-138 C
Solar/Wind Helper
0.394
316404AE1-155 C
Solar/Wind Helper
3.563
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.553
315662AE1-191 GEN
Solar/Wind Helper
2.22
957601AF2-054 GEN
Solar/Wind Helper
0.551
971543AH1-269 GEN
50/50
11.498
941621AE2-160 GEN
50/50
6.64
971531AH1-263 GEN
50/50
Charging
23.667
972293SS25-0014
50/50
Charging
57.012
963031AG1-152 GEN
50/50
Charging
10.85
971313AH1-133 GEN
Solar/Wind Harmer
6.407
270346AE1-212 GEN
Solar/Wind Harmer
8.186
960911AF2-382 GEN
Solar/Wind Harmer
6.617
270030AE2-140 GEN
Solar/Wind Harmer
17.484
970913AG2-568 GEN
Solar/Wind Harmer
5.92
971981AH1-535 GEN
Solar/Wind Harmer
6.611
316045AC1-158 PL2
Solar/Wind Helper
7.388
316044AC1-158 PL1
Solar/Wind Helper
2.309
316233AE1-074 FULL
Solar/Wind Helper
0.6
944491AF1-114 GEN
Solar/Wind Helper
2.856
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.227
316487AF1-042 GEN
Solar/Wind Helper
1.165
316059AD1-063 C
Solar/Wind Helper
0.418
316280AD1-041 GEN
Solar/Wind Helper
1.388
315821AE2-092 GEN
Solar/Wind Helper
3.827
270399AC1-101 GEN
Solar/Wind Harmer
1.686
270400AC1-102 GEN
Solar/Wind Harmer
1.686
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
NYPJM->LTFIMP_NY
CLTF
2.179
LGEELTFEXP_LGEE->PJM
CLTF
5.763
WECLTFEXP_WEC->PJM
CLTF
2.894
CPLELTFEXP_CPLE->PJM
CLTF
4.752
TVALTFEXP_TVA->PJM
CLTF
9.526
MECLTFEXP_MEC->PJM
CLTF
13.346
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 85.07 MW.

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.67 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2049.35
MW Contribution:
72.07
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
45.019
971881AH1-461 GEN
50/50
14.324
970119AG2-088 GEN
50/50
Charging
16.824
972273AH1-721 GEN
50/50
85.07
958121AF2-106 GEN
Solar/Wind Harmer
0
971277AH1-098 GEN
Solar/Wind Harmer
4.144
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971981AH1-535 GEN
Solar/Wind Harmer
7.212
270494AE1-108_GEN
Solar/Wind Helper
5.58
316450AC1-158 RIC
Solar/Wind Helper
0.616
316164AC1-076 GEN
Solar/Wind Helper
1.94
316468AD1-105 GEN
Solar/Wind Helper
2.225
316312AB1-027
Solar/Wind Helper
0.748
316075AC2-137 C
Solar/Wind Helper
0.581
316313AB2-026
Solar/Wind Helper
0.577
315976AC1-164 GENA
Solar/Wind Helper
2.054
316169AC1-164_GENC
Solar/Wind Helper
1.775
957971AF2-091 GEN
Solar/Wind Helper
0.971
316223AC1-118
Solar/Wind Helper
0.567
316203AE2-005 GEN
Solar/Wind Helper
3.616
316156AD2-030 GEN
Solar/Wind Helper
0.548
316159AE1-175 C
Solar/Wind Helper
0.538
971543AH1-269 GEN
50/50
11.498
941621AE2-160 GEN
50/50
6.64
971531AH1-263 GEN
50/50
Charging
23.667
972293SS25-0014
50/50
Charging
57.012
963031AG1-152 GEN
50/50
Charging
10.85
971313AH1-133 GEN
Solar/Wind Harmer
6.407
270346AE1-212 GEN
Solar/Wind Harmer
8.186
960911AF2-382 GEN
Solar/Wind Harmer
6.617
270030AE2-140 GEN
Solar/Wind Harmer
17.484
970913AG2-568 GEN
Solar/Wind Harmer
5.92
971981AH1-535 GEN
Solar/Wind Harmer
6.611
316045AC1-158 PL2
Solar/Wind Helper
7.388
316044AC1-158 PL1
Solar/Wind Helper
2.309
316233AE1-074 FULL
Solar/Wind Helper
0.6
944491AF1-114 GEN
Solar/Wind Helper
2.856
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.227
316487AF1-042 GEN
Solar/Wind Helper
1.165
316059AD1-063 C
Solar/Wind Helper
0.418
316280AD1-041 GEN
Solar/Wind Helper
1.388
315821AE2-092 GEN
Solar/Wind Helper
3.827
270399AC1-101 GEN
Solar/Wind Harmer
1.686
270400AC1-102 GEN
Solar/Wind Harmer
1.686
970823AG2-518 GEN
50/50
19.371
316303AF2-085
50/50
Charging
2.243
970365AG2-240 GEN
50/50
Charging
1.246
316405AF2-144 C
50/50
Charging
1.175
270583AD2-179 GEN
Solar/Wind Harmer
12.447
971277AH1-098 GEN
Solar/Wind Harmer
4.558
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971329AH1-144 GEN
Solar/Wind Harmer
7.833
943811AF1-049 GEN
Solar/Wind Harmer
0
971461AH1-227 GEN
Solar/Wind Harmer
4.169
971687AH1-348 GEN
Solar/Wind Harmer
0.807
971403AH1-188 GEN
Solar/Wind Harmer
10.665
970281AG2-184 GEN
Solar/Wind Harmer
15.747
972103AH1-617 GEN
Solar/Wind Harmer
14.997
316447AC1-158 HLD
Solar/Wind Helper
5.08
316192AB2-158 GEN
Solar/Wind Helper
2.765
316006AB2-029 C
Solar/Wind Helper
0.541
316405AF2-144 C
Solar/Wind Helper
0.49
316077AC2-138 C
Solar/Wind Helper
0.394
316404AE1-155 C
Solar/Wind Helper
3.563
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.554
315662AE1-191 GEN
Solar/Wind Helper
2.22
957601AF2-054 GEN
Solar/Wind Helper
0.551
970417AG2-272 GEN
50/50
8.428
971507AH1-251 GEN
50/50
Charging
5.863
957191AF2-013 GEN
50/50
Charging
10.655
943031AE2-326 GEN
Solar/Wind Harmer
11.709
270069AE2-166 C O1
Solar/Wind Harmer
8.427
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
966881AG1-559 GEN
Solar/Wind Helper
0.447
316473AC1-191 GEN
Solar/Wind Helper
2.427
966871AG1-558 GEN
Solar/Wind Helper
0.436
315651AD1-115 GEN
Solar/Wind Helper
4.201
966001AG1-469 GEN
Solar/Wind Helper
0.423
316258AE1-075 C
Solar/Wind Helper
0.519
315975AC1-164 GENB
Solar/Wind Helper
0.061
316337AD2-073 GEN
Solar/Wind Helper
0.563
961951AG1-038 GEN
Solar/Wind Helper
1.258
315666AE1-190 GEN
Solar/Wind Helper
0.555
315616AA1-038_C
Solar/Wind Helper
1.962
316382AG1-145 C
Solar/Wind Helper
0.541
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
NYPJM->LTFIMP_NY
CLTF
2.178
LGEELTFEXP_LGEE->PJM
CLTF
5.763
WECLTFEXP_WEC->PJM
CLTF
2.894
CPLELTFEXP_CPLE->PJM
CLTF
4.752
TVALTFEXP_TVA->PJM
CLTF
9.526
MECLTFEXP_MEC->PJM
CLTF
13.346
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 85.07 MW.

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-L
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.35 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2045.56
MW Contribution:
72.07
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
45.014
971881AH1-461 GEN
50/50
14.323
970119AG2-088 GEN
50/50
Charging
16.846
972273AH1-721 GEN
50/50
85.068
958121AF2-106 GEN
Solar/Wind Harmer
0
971277AH1-098 GEN
Solar/Wind Harmer
4.143
971331AH1-145 GEN
Solar/Wind Harmer
17.214
971981AH1-535 GEN
Solar/Wind Harmer
7.211
270494AE1-108_GEN
Solar/Wind Helper
5.59
971543AH1-269 GEN
50/50
11.496
941621AE2-160 GEN
50/50
6.64
971531AH1-263 GEN
50/50
Charging
23.682
972293SS25-0014
50/50
Charging
57.048
963031AG1-152 GEN
50/50
Charging
10.856
971313AH1-133 GEN
Solar/Wind Harmer
6.407
270346AE1-212 GEN
Solar/Wind Harmer
8.185
970823AG2-518 GEN
50/50
19.368
316303AF2-085
50/50
Charging
2.246
970365AG2-240 GEN
50/50
Charging
1.247
316405AF2-144 C
50/50
Charging
1.177
270583AD2-179 GEN
Solar/Wind Harmer
12.446
971277AH1-098 GEN
Solar/Wind Harmer
4.558
966391AG1-508 GEN
Solar/Wind Harmer
10.237
971329AH1-144 GEN
Solar/Wind Harmer
7.832
943811AF1-049 GEN
Solar/Wind Harmer
0
971461AH1-227 GEN
Solar/Wind Harmer
4.168
971687AH1-348 GEN
Solar/Wind Harmer
0.807
971403AH1-188 GEN
Solar/Wind Harmer
10.665
970281AG2-184 GEN
Solar/Wind Harmer
15.746
970417AG2-272 GEN
50/50
8.425
971507AH1-251 GEN
50/50
Charging
5.867
957191AF2-013 GEN
50/50
Charging
10.663
943031AE2-326 GEN
Solar/Wind Harmer
11.708
270069AE2-166 C O1
Solar/Wind Harmer
8.425
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
966881AG1-559 GEN
Solar/Wind Helper
0.447
316473AC1-191 GEN
Solar/Wind Helper
2.43
966871AG1-558 GEN
Solar/Wind Helper
0.437
315651AD1-115 GEN
Solar/Wind Helper
4.205
966001AG1-469 GEN
Solar/Wind Helper
0.424
316258AE1-075 C
Solar/Wind Helper
0.52
315975AC1-164 GENB
Solar/Wind Helper
0.061
316337AD2-073 GEN
Solar/Wind Helper
0.564
961951AG1-038 GEN
Solar/Wind Helper
1.26
315616AA1-038_C
Solar/Wind Helper
2.018
315666AE1-190 GEN
Solar/Wind Helper
0.556
316382AG1-145 C
Solar/Wind Helper
0.541
316450AC1-158 RIC
Solar/Wind Helper
0.616
316164AC1-076 GEN
Solar/Wind Helper
1.941
316468AD1-105 GEN
Solar/Wind Helper
2.227
316312AB1-027
Solar/Wind Helper
0.748
316075AC2-137 C
Solar/Wind Helper
0.582
316313AB2-026
Solar/Wind Helper
0.578
315976AC1-164 GENA
Solar/Wind Helper
2.057
316169AC1-164_GENC
Solar/Wind Helper
1.777
957971AF2-091 GEN
Solar/Wind Helper
0.972
316223AC1-118
Solar/Wind Helper
0.568
316203AE2-005 GEN
Solar/Wind Helper
3.62
316156AD2-030 GEN
Solar/Wind Helper
0.548
316159AE1-175 C
Solar/Wind Helper
0.538
972103AH1-617 GEN
Solar/Wind Harmer
14.996
316447AC1-158 HLD
Solar/Wind Helper
5.083
316192AB2-158 GEN
Solar/Wind Helper
2.769
316006AB2-029 C
Solar/Wind Helper
0.541
316405AF2-144 C
Solar/Wind Helper
0.491
316077AC2-138 C
Solar/Wind Helper
0.394
316404AE1-155 C
Solar/Wind Helper
3.567
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.554
315662AE1-191 GEN
Solar/Wind Helper
2.223
957601AF2-054 GEN
Solar/Wind Helper
0.551
960911AF2-382 GEN
Solar/Wind Harmer
6.616
270030AE2-140 GEN
Solar/Wind Harmer
17.478
970913AG2-568 GEN
Solar/Wind Harmer
5.92
971981AH1-535 GEN
Solar/Wind Harmer
6.61
316045AC1-158 PL2
Solar/Wind Helper
7.393
316044AC1-158 PL1
Solar/Wind Helper
2.31
316233AE1-074 FULL
Solar/Wind Helper
0.6
944491AF1-114 GEN
Solar/Wind Helper
2.859
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.229
316487AF1-042 GEN
Solar/Wind Helper
1.167
316059AD1-063 C
Solar/Wind Helper
0.419
315821AE2-092 GEN
Solar/Wind Helper
3.841
316280AD1-041 GEN
Solar/Wind Helper
1.389
270399AC1-101 GEN
Solar/Wind Harmer
1.686
270400AC1-102 GEN
Solar/Wind Harmer
1.686
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.9
CBM West 2LTFEXP_CBM-W2->PJM
CBM
114.999
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.017
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.652
NYPJM->LTFIMP_NY
CLTF
2.177
LGEELTFEXP_LGEE->PJM
CLTF
5.764
WECLTFEXP_WEC->PJM
CLTF
2.895
CPLELTFEXP_CPLE->PJM
CLTF
4.745
TVALTFEXP_TVA->PJM
CLTF
9.524
MECLTFEXP_MEC->PJM
CLTF
13.347
LAGNLTFEXP_LAGN->PJM
CLTF
17.991
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.478
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 85.07 MW.

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.54 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2024.13
MW Contribution:
72.07
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
45.019
971881AH1-461 GEN
50/50
14.324
970119AG2-088 GEN
50/50
Charging
16.823
972273AH1-721 GEN
50/50
85.07
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
17.216
270494AE1-108_GEN
Solar/Wind Helper
5.579
316164AC1-076 GEN
Solar/Wind Helper
1.94
316468AD1-105 GEN
Solar/Wind Helper
2.225
316075AC2-137 C
Solar/Wind Helper
0.581
316313AB2-026
Solar/Wind Helper
0.577
957971AF2-091 GEN
Solar/Wind Helper
0.971
316223AC1-118
Solar/Wind Helper
0.567
316203AE2-005 GEN
Solar/Wind Helper
3.616
316156AD2-030 GEN
Solar/Wind Helper
0.548
316159AE1-175 C
Solar/Wind Helper
0.538
944971AF1-162 GEN
Solar/Wind Harmer
2.093
971543AH1-269 GEN
50/50
11.498
941621AE2-160 GEN
50/50
6.64
971531AH1-263 GEN
50/50
Charging
23.667
972293SS25-0014
50/50
Charging
57.012
963031AG1-152 GEN
50/50
Charging
10.85
971313AH1-133 GEN
Solar/Wind Harmer
6.407
270346AE1-212 GEN
Solar/Wind Harmer
8.186
960911AF2-382 GEN
Solar/Wind Harmer
6.617
270030AE2-140 GEN
Solar/Wind Harmer
17.484
970913AG2-568 GEN
Solar/Wind Harmer
5.92
270399AC1-101 GEN
Solar/Wind Harmer
3.469
270400AC1-102 GEN
Solar/Wind Harmer
3.469
270053AF1-130 C
Solar/Wind Harmer
12.797
316233AE1-074 FULL
Solar/Wind Helper
0.6
944491AF1-114 GEN
Solar/Wind Helper
2.856
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.227
316487AF1-042 GEN
Solar/Wind Helper
1.165
316059AD1-063 C
Solar/Wind Helper
0.418
316280AD1-041 GEN
Solar/Wind Helper
1.388
315821AE2-092 GEN
Solar/Wind Helper
3.827
970823AG2-518 GEN
50/50
19.371
316303AF2-085
50/50
Charging
2.243
970365AG2-240 GEN
50/50
Charging
1.246
316405AF2-144 C
50/50
Charging
1.174
270583AD2-179 GEN
Solar/Wind Harmer
12.447
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971329AH1-144 GEN
Solar/Wind Harmer
7.833
943811AF1-049 GEN
Solar/Wind Harmer
0
971461AH1-227 GEN
Solar/Wind Harmer
4.169
971687AH1-348 GEN
Solar/Wind Harmer
0.807
971403AH1-188 GEN
Solar/Wind Harmer
10.665
970281AG2-184 GEN
Solar/Wind Harmer
15.747
972103AH1-617 GEN
Solar/Wind Harmer
14.997
316192AB2-158 GEN
Solar/Wind Helper
2.765
316006AB2-029 C
Solar/Wind Helper
0.541
316077AC2-138 C
Solar/Wind Helper
0.394
316404AE1-155 C
Solar/Wind Helper
3.563
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.553
315662AE1-191 GEN
Solar/Wind Helper
2.22
957601AF2-054 GEN
Solar/Wind Helper
0.551
970417AG2-272 GEN
50/50
8.428
971507AH1-251 GEN
50/50
Charging
5.863
957191AF2-013 GEN
50/50
Charging
10.655
943031AE2-326 GEN
Solar/Wind Harmer
11.709
270069AE2-166 C O1
Solar/Wind Harmer
8.427
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
957241AF2-018 GEN
Solar/Wind Harmer
0
316473AC1-191 GEN
Solar/Wind Helper
2.427
315651AD1-115 GEN
Solar/Wind Helper
4.201
966001AG1-469 GEN
Solar/Wind Helper
0.423
316258AE1-075 C
Solar/Wind Helper
0.519
316337AD2-073 GEN
Solar/Wind Helper
0.563
961951AG1-038 GEN
Solar/Wind Helper
1.258
315666AE1-190 GEN
Solar/Wind Helper
0.555
316382AG1-145 C
Solar/Wind Helper
0.541
315616AA1-038_C
Solar/Wind Helper
1.957
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
NYPJM->LTFIMP_NY
CLTF
2.179
LGEELTFEXP_LGEE->PJM
CLTF
5.763
WECLTFEXP_WEC->PJM
CLTF
2.894
CPLELTFEXP_CPLE->PJM
CLTF
4.752
TVALTFEXP_TVA->PJM
CLTF
9.526
MECLTFEXP_MEC->PJM
CLTF
13.346
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 85.07 MW.

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1632.98
MW Contribution:
76.95
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
37.854
971881AH1-461 GEN
50/50
11.944
972273AH1-721 GEN
50/50
76.948
971277AH1-098 GEN
Solar/Wind Harmer
3.312
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.165
316450AC1-158 RIC
Solar/Wind Helper
0.582
270494AE1-108_GEN
Solar/Wind Helper
4.816
316468AD1-105 GEN
Solar/Wind Helper
2.079
316164AC1-076 GEN
Solar/Wind Helper
1.745
316312AB1-027
Solar/Wind Helper
0.693
957971AF2-091 GEN
Solar/Wind Helper
0.919
944971AF1-162 GEN
Solar/Wind Harmer
10.409
971543AH1-269 GEN
50/50
8.594
941621AE2-160 GEN
50/50
5.904
971531AH1-263 GEN
50/50
Charging
22.363
972293SS25-0014
50/50
Charging
53.849
963031AG1-152 GEN
50/50
Charging
10.244
971313AH1-133 GEN
Solar/Wind Harmer
5.386
960911AF2-382 GEN
Solar/Wind Harmer
5.69
270346AE1-212 GEN
Solar/Wind Harmer
6.755
970913AG2-568 GEN
Solar/Wind Harmer
5.207
270399AC1-101 GEN
Solar/Wind Harmer
3.156
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270053AF1-130 C
Solar/Wind Harmer
11.711
316045AC1-158 PL2
Solar/Wind Helper
6.979
316044AC1-158 PL1
Solar/Wind Helper
2.181
944491AF1-114 GEN
Solar/Wind Helper
2.702
970823AG2-518 GEN
50/50
14.083
970365AG2-240 GEN
50/50
Charging
1.154
971277AH1-098 GEN
Solar/Wind Harmer
3.644
966391AG1-508 GEN
Solar/Wind Harmer
8.202
270583AD2-179 GEN
Solar/Wind Harmer
9.358
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971687AH1-348 GEN
Solar/Wind Harmer
0.705
971403AH1-188 GEN
Solar/Wind Harmer
9.621
970281AG2-184 GEN
Solar/Wind Harmer
14.006
972103AH1-617 GEN
Solar/Wind Harmer
13.339
316447AC1-158 HLD
Solar/Wind Helper
4.798
316006AB2-029 C
Solar/Wind Helper
0.504
970417AG2-272 GEN
50/50
6.326
971507AH1-251 GEN
50/50
Charging
5.466
957191AF2-013 GEN
50/50
Charging
10.139
943031AE2-326 GEN
Solar/Wind Harmer
9.448
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
270069AE2-166 C O1
Solar/Wind Harmer
6.316
957241AF2-018 GEN
Solar/Wind Harmer
0
966881AG1-559 GEN
Solar/Wind Helper
0.418
316473AC1-191 GEN
Solar/Wind Helper
2.25
966871AG1-558 GEN
Solar/Wind Helper
0.404
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
NYPJM->LTFIMP_NY
CLTF
2.2
LGEELTFEXP_LGEE->PJM
CLTF
5.464
WECLTFEXP_WEC->PJM
CLTF
2.768
CPLELTFEXP_CPLE->PJM
CLTF
3.423
TVALTFEXP_TVA->PJM
CLTF
8.341
MECLTFEXP_MEC->PJM
CLTF
12.527
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
SIGELTFEXP_SIGE->PJM
CLTF
0.412
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1632.98
MW Contribution:
76.95
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970417AG2-272 GEN
50/50
6.326
971507AH1-251 GEN
50/50
Charging
5.466
957191AF2-013 GEN
50/50
Charging
10.139
943031AE2-326 GEN
Solar/Wind Harmer
9.448
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
270069AE2-166 C O1
Solar/Wind Harmer
6.316
957241AF2-018 GEN
Solar/Wind Harmer
0
966881AG1-559 GEN
Solar/Wind Helper
0.418
316473AC1-191 GEN
Solar/Wind Helper
2.25
966871AG1-558 GEN
Solar/Wind Helper
0.404
970563AG2-360 GEN
50/50
37.854
971881AH1-461 GEN
50/50
11.944
972273AH1-721 GEN
50/50
76.948
971277AH1-098 GEN
Solar/Wind Harmer
3.312
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.165
316450AC1-158 RIC
Solar/Wind Helper
0.582
270494AE1-108_GEN
Solar/Wind Helper
4.816
316468AD1-105 GEN
Solar/Wind Helper
2.079
316164AC1-076 GEN
Solar/Wind Helper
1.745
316312AB1-027
Solar/Wind Helper
0.693
957971AF2-091 GEN
Solar/Wind Helper
0.919
944971AF1-162 GEN
Solar/Wind Harmer
10.409
970823AG2-518 GEN
50/50
14.083
970365AG2-240 GEN
50/50
Charging
1.154
971277AH1-098 GEN
Solar/Wind Harmer
3.644
966391AG1-508 GEN
Solar/Wind Harmer
8.202
270583AD2-179 GEN
Solar/Wind Harmer
9.358
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971687AH1-348 GEN
Solar/Wind Harmer
0.705
971403AH1-188 GEN
Solar/Wind Harmer
9.621
970281AG2-184 GEN
Solar/Wind Harmer
14.006
972103AH1-617 GEN
Solar/Wind Harmer
13.339
316447AC1-158 HLD
Solar/Wind Helper
4.798
316006AB2-029 C
Solar/Wind Helper
0.504
971543AH1-269 GEN
50/50
8.594
941621AE2-160 GEN
50/50
5.904
971531AH1-263 GEN
50/50
Charging
22.363
972293SS25-0014
50/50
Charging
53.849
963031AG1-152 GEN
50/50
Charging
10.244
971313AH1-133 GEN
Solar/Wind Harmer
5.386
960911AF2-382 GEN
Solar/Wind Harmer
5.69
270346AE1-212 GEN
Solar/Wind Harmer
6.755
970913AG2-568 GEN
Solar/Wind Harmer
5.207
270399AC1-101 GEN
Solar/Wind Harmer
3.156
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270053AF1-130 C
Solar/Wind Harmer
11.711
316045AC1-158 PL2
Solar/Wind Helper
6.979
316044AC1-158 PL1
Solar/Wind Helper
2.181
944491AF1-114 GEN
Solar/Wind Helper
2.702
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
NYPJM->LTFIMP_NY
CLTF
2.2
LGEELTFEXP_LGEE->PJM
CLTF
5.464
WECLTFEXP_WEC->PJM
CLTF
2.768
CPLELTFEXP_CPLE->PJM
CLTF
3.423
TVALTFEXP_TVA->PJM
CLTF
8.341
MECLTFEXP_MEC->PJM
CLTF
12.527
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
SIGELTFEXP_SIGE->PJM
CLTF
0.412
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.83 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1614.63
MW Contribution:
76.95
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
37.854
971881AH1-461 GEN
50/50
11.944
972273AH1-721 GEN
50/50
76.948
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.165
944971AF1-162 GEN
Solar/Wind Harmer
12.03
270494AE1-108_GEN
Solar/Wind Helper
4.816
316468AD1-105 GEN
Solar/Wind Helper
2.079
316164AC1-076 GEN
Solar/Wind Helper
1.745
957971AF2-091 GEN
Solar/Wind Helper
0.919
971543AH1-269 GEN
50/50
8.594
941621AE2-160 GEN
50/50
5.904
971531AH1-263 GEN
50/50
Charging
22.363
972293SS25-0014
50/50
Charging
53.849
963031AG1-152 GEN
50/50
Charging
10.244
971313AH1-133 GEN
Solar/Wind Harmer
5.386
960911AF2-382 GEN
Solar/Wind Harmer
5.69
270346AE1-212 GEN
Solar/Wind Harmer
6.755
970913AG2-568 GEN
Solar/Wind Harmer
5.207
270399AC1-101 GEN
Solar/Wind Harmer
3.156
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270053AF1-130 C
Solar/Wind Harmer
11.711
944491AF1-114 GEN
Solar/Wind Helper
2.702
270030AE2-140 GEN
Solar/Wind Harmer
3.161
970823AG2-518 GEN
50/50
14.083
970365AG2-240 GEN
50/50
Charging
1.154
966391AG1-508 GEN
Solar/Wind Harmer
8.202
270583AD2-179 GEN
Solar/Wind Harmer
9.358
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971687AH1-348 GEN
Solar/Wind Harmer
0.705
971403AH1-188 GEN
Solar/Wind Harmer
9.621
970281AG2-184 GEN
Solar/Wind Harmer
14.006
972103AH1-617 GEN
Solar/Wind Harmer
13.339
316006AB2-029 C
Solar/Wind Helper
0.504
970417AG2-272 GEN
50/50
6.326
971507AH1-251 GEN
50/50
Charging
5.466
957191AF2-013 GEN
50/50
Charging
10.139
943031AE2-326 GEN
Solar/Wind Harmer
9.448
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
270069AE2-166 C O1
Solar/Wind Harmer
6.316
957241AF2-018 GEN
Solar/Wind Harmer
0
316473AC1-191 GEN
Solar/Wind Helper
2.25
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
NYPJM->LTFIMP_NY
CLTF
2.2
LGEELTFEXP_LGEE->PJM
CLTF
5.464
WECLTFEXP_WEC->PJM
CLTF
2.768
CPLELTFEXP_CPLE->PJM
CLTF
3.423
TVALTFEXP_TVA->PJM
CLTF
8.341
MECLTFEXP_MEC->PJM
CLTF
12.527
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
SIGELTFEXP_SIGE->PJM
CLTF
0.412
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.7 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1211.91
MW Contribution:
72.07
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
85.07
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 85.07 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.7 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1211.91
MW Contribution:
72.07
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
85.07
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 85.07 MW.

Details for [AH1-721] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.7 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1211.81
MW Contribution:
72.07
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
85.07
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 85.07 MW.

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.88 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:96.43
MW Contribution:
88.87
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
88.874
339231AF1-038_GEN
Solar/Wind Helper
3.615
339255AE2-071 GEN
Solar/Wind Helper
0.743
339250AF1-203 GEN
Solar/Wind Helper
0.425
339206AE1-143 GEN
Solar/Wind Helper
2.431
339236AF1-050_GEN
Solar/Wind Helper
1.222
339241AF1-083 GEN
Solar/Wind Helper
1.23
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.333
G-007ALTFEXP_G-007A->PJM
CMTX
0.167
VFTLTFEXP_VFT->PJM
CMTX
0.449
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.045
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.033
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.129
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.088
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.378
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.88 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:96.43
MW Contribution:
88.87
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
88.874
339231AF1-038_GEN
Solar/Wind Helper
3.615
339255AE2-071 GEN
Solar/Wind Helper
0.743
339250AF1-203 GEN
Solar/Wind Helper
0.425
339206AE1-143 GEN
Solar/Wind Helper
2.431
339236AF1-050_GEN
Solar/Wind Helper
1.222
339241AF1-083 GEN
Solar/Wind Helper
1.23
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.333
G-007ALTFEXP_G-007A->PJM
CMTX
0.167
VFTLTFEXP_VFT->PJM
CMTX
0.449
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.045
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.033
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.129
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.088
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.378
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1008_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.87 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:94.14
MW Contribution:
79.17
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.51 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:92.35
MW Contribution:
80.03
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
79.173
339231AF1-038_GEN
Solar/Wind Helper
3.548
339255AE2-071 GEN
Solar/Wind Helper
0.591
339250AF1-203 GEN
Solar/Wind Helper
0.338
339206AE1-143 GEN
Solar/Wind Helper
2.044
339236AF1-050_GEN
Solar/Wind Helper
0.952
339241AF1-083 GEN
Solar/Wind Helper
1.005
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.273
G-007ALTFEXP_G-007A->PJM
CMTX
0.138
VFTLTFEXP_VFT->PJM
CMTX
0.372
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.015
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.824
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.077
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.317
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:123.87 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:94.14
MW Contribution:
79.17
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.51 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:92.35
MW Contribution:
80.03
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
79.173
339231AF1-038_GEN
Solar/Wind Helper
3.548
339255AE2-071 GEN
Solar/Wind Helper
0.591
339250AF1-203 GEN
Solar/Wind Helper
0.338
339206AE1-143 GEN
Solar/Wind Helper
2.044
339236AF1-050_GEN
Solar/Wind Helper
0.952
339241AF1-083 GEN
Solar/Wind Helper
1.005
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.273
G-007ALTFEXP_G-007A->PJM
CMTX
0.138
VFTLTFEXP_VFT->PJM
CMTX
0.372
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.015
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.824
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.077
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.317
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1024_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.12 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:84.45
MW Contribution:
71.26
IPD Plant:AH1-721
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.26 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:82.27
MW Contribution:
71.2
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.258

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.92 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:84.3
MW Contribution:
88.87
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
88.874

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.92 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:84.3
MW Contribution:
88.87
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
88.874

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1008_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.22 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:83.77
MW Contribution:
79.17
IPD Plant:AH1-721
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.91 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:82.01
MW Contribution:
80.03
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
79.173

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.22 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:83.77
MW Contribution:
79.17
IPD Plant:AH1-721
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.91 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:82.01
MW Contribution:
80.03
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
79.173

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1014_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.55 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:80.22
MW Contribution:
69.83
IPD Plant:AH1-721
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.75 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:78.85
MW Contribution:
69.88
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
69.835

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:153.06 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:456.13
MW Contribution:
307.68
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
363.396
971485AH1-239 GEN
Solar/Wind Harmer
7.898
966021AG1-471 GEN
Solar/Wind Harmer
5.284
964901AG1-354 GEN
Solar/Wind Harmer
8.603
964781AG1-341 GEN
Solar/Wind Harmer
6.731
964781AG1-341 GEN
Solar/Wind Harmer
3.702
970653AG2-424 GEN
Solar/Wind Harmer
1.484
970653AG2-424 GEN
Solar/Wind Harmer
0.839
950011AG9-010
External Queue
6.191452503204346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.363
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.527
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.887
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.67
NYPJM->LTFIMP_NY
CLTF
0.058
LGEELTFEXP_LGEE->PJM
CLTF
0.011
WECLTFEXP_WEC->PJM
CLTF
0.064
CPLELTFEXP_CPLE->PJM
CLTF
0.144
TVALTFEXP_TVA->PJM
CLTF
0.929
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
MECLTFEXP_MEC->PJM
CLTF
0.555
LAGNLTFEXP_LAGN->PJM
CLTF
1.49
SIGELTFEXP_SIGE->PJM
CLTF
0.018
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.372
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 363.4 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:131.98 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:393.29
MW Contribution:
307.68
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
363.396
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 363.4 MW.

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EXT_324100 7ALCALDE 345 324130 5ALCALDE 161 1_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_324100 7ALCALDE 345 324130 5ALCALDE 161 1_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.05 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:204.1
MW Contribution:
109.21
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_324100 7ALCALDE 345 324130 5ALCALDE 161 1_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.03 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:216.05
MW Contribution:
115.55
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
128.597
971485AH1-239 GEN
Solar/Wind Harmer
3.394
966021AG1-471 GEN
Solar/Wind Harmer
2.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.07
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.688
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.514
NYPJM->LTFIMP_NY
CLTF
0.039
LGEELTFEXP_LGEE->PJM
CLTF
0.065
WECLTFEXP_WEC->PJM
CLTF
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.118
TVALTFEXP_TVA->PJM
CLTF
0.525
MECLTFEXP_MEC->PJM
CLTF
0.287
LAGNLTFEXP_LAGN->PJM
CLTF
0.832
SIGELTFEXP_SIGE->PJM
CLTF
0.012
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.283
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 128.6 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 135.92 MW.

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EXT_B-345-100_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_B-345-100_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.96 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:203.92
MW Contribution:
109.17
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_B-345-100_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.96 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:215.92
MW Contribution:
115.48
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
128.551
971485AH1-239 GEN
Solar/Wind Harmer
3.392
966021AG1-471 GEN
Solar/Wind Harmer
2.256
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.195
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.683
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.507
NYPJM->LTFIMP_NY
CLTF
0.039
LGEELTFEXP_LGEE->PJM
CLTF
0.068
WECLTFEXP_WEC->PJM
CLTF
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.116
TVALTFEXP_TVA->PJM
CLTF
0.523
MECLTFEXP_MEC->PJM
CLTF
0.288
LAGNLTFEXP_LAGN->PJM
CLTF
0.829
SIGELTFEXP_SIGE->PJM
CLTF
0.012
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.217
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 128.55 MW.
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 135.84 MW.

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:112.11 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:334.08
MW Contribution:
326.07
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
326.066
NYPJM->LTFIMP_NY
CLTF
0.002
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.004
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.257
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.095
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.321
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.456

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.39 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:331.94
MW Contribution:
326.07
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
326.066

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-DEN161_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-DEN161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.39 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:323.01
MW Contribution:
310.42
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-DEN161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:215.14 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:641.11
MW Contribution:
625.79
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
310.417
339231AF1-038_GEN
Solar/Wind Helper
3.388
339255AE2-071 GEN
Solar/Wind Helper
0.963
339250AF1-203 GEN
Solar/Wind Helper
0.55
970653AG2-424 GEN
50/50
Charging
0.95
339206AE1-143 GEN
Solar/Wind Helper
3.873
339236AF1-050_GEN
Solar/Wind Helper
1.828
339241AF1-083 GEN
Solar/Wind Helper
1.908
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.402
G-007ALTFEXP_G-007A->PJM
CMTX
0.2
VFTLTFEXP_VFT->PJM
CMTX
0.538
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.089
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.064
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.711
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.634
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-DEN161_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-DEN161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.72 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:306.11
MW Contribution:
310.42
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-DEN161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:212.05 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:631.9
MW Contribution:
625.79
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
310.417

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-LAUREL161_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:153.07 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:321.45
MW Contribution:
308.94
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:305.0 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:640.49
MW Contribution:
625.25
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
308.935
339231AF1-038_GEN
Solar/Wind Helper
3.372
339255AE2-071 GEN
Solar/Wind Helper
0.958
339250AF1-203 GEN
Solar/Wind Helper
0.548
970653AG2-424 GEN
50/50
Charging
0.946
339206AE1-143 GEN
Solar/Wind Helper
3.854
339236AF1-050_GEN
Solar/Wind Helper
1.819
339241AF1-083 GEN
Solar/Wind Helper
1.899
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.4
G-007ALTFEXP_G-007A->PJM
CMTX
0.199
VFTLTFEXP_VFT->PJM
CMTX
0.535
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.088
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.064
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.703
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.631
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:147.23 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:309.19
MW Contribution:
301.79
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
301.791
NYPJM->LTFIMP_NY
CLTF
0.002
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.004
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.238
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.088
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.297
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.348

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:146.29 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:307.21
MW Contribution:
301.79
IPD Plant:AH1-721
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
301.791

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-LAUREL161_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.06 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:304.63
MW Contribution:
308.94
IPD Plant:AH1-721
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:300.62 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:631.29
MW Contribution:
625.25
IPD Plant:AH1-721
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
308.935
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 56602_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314856 TO BUS 314912 CKT 1   /*6LEXNGT2     230.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 547T566_SRT-L'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1                /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314901 TO BUS 314987 CKT 1                /*8BATH CO     500.0 - 8LEXINGTN SC 500.0
 OPEN BRANCH FROM BUS 314912 TO BUS 314987 CKT 1                /*8LEXNGTN     500.0 - 8LEXINGTN SC 500.0
 OPEN BUS 314987                                                /*8LEXINGTN SC 500.0
 SET POSTCONTRATING 3914 BRANCH FROM BUS 314901 TO BUS 314991 CKT 1 /*8BATH CO     500.0 - 8VALLEY SC   500.0
 SET PRECONTRATING 3880 BRANCH FROM BUS 314901 TO BUS 314991 CKT 1 /*8BATH CO     500.0 - 8VALLEY SC   500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-210G_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-2_COOPER 2 161_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1008_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
 OPEN BUS 342900   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-2_COOPER 1 161_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1024_SRT-A'
 OPEN BRANCH FROM BUS 342115 TO BUS 342787 CKT 1   /*2PULASK CO    69.0 - 5PULASK CO   161.0
 OPEN BRANCH FROM BUS 342760 TO BUS 342790 CKT 1   /*5LIBERTY J   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342787 TO BUS 342790 CKT 1   /*5PULASK CO   161.0 - 5PULASK CO J 161.0
 OPEN BUS 342715                                   /*5COOPER1     161.0
 OPEN BUS 342900                                   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1014_SRT-A'
 OPEN BRANCH FROM BUS 342742 TO BUS 342745 CKT 1   /*5JABEZ       161.0 - 5JABEZ T     161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342751 CKT 1   /*5JABEZ T     161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342799 CKT 1   /*5JABEZ T     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342748 TO BUS 342751 CKT 1   /*5JAMESTOWN   161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342751 TO BUS 342796 CKT 1   /*5JAMESTOWN T 161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342793 TO BUS 342796 CKT 1   /*5RUSSEL CO   161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342796 TO BUS 360448 CKT 1   /*5RUSSEL CO J 161.0 - 5WOLF CRK HP 161.0
 OPEN BUS 342715                                   /*5COOPER1     161.0
 OPEN BUS 342900                                   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS'
 OPEN BRANCH FROM BUS 324130 TO BUS 972272 CKT 1   /*5ALCALDE     161.0 - AH1-721 TP   161.0
 OPEN BRANCH FROM BUS 324130 TO BUS 972272 CKT 2   /*5ALCALDE     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EXT_324100 7ALCALDE 345 324130 5ALCALDE 161 1_SRT-L'
 OPEN BRANCH FROM BUS 324100 TO BUS 324130 CKT 1   /*7ALCALDE     345.0 - 5ALCALDE     161.0
END
CONTINGENCY 'EXT_B-345-100_SRT-L'
 OPEN BRANCH FROM BUS 324100 TO BUS 324102 CKT 1   /*7ALCALDE     345.0 - 7BROWN NORTH 345.0
 OPEN BRANCH FROM BUS 324100 TO BUS 324112 CKT 1   /*7ALCALDE     345.0 - 7PINEVILLE   345.0
 OPEN BRANCH FROM BUS 324100 TO BUS 324130 CKT 1   /*7ALCALDE     345.0 - 5ALCALDE     161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-DEN161_SRT-A-1'
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 2   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-LAUREL161_SRT-A-1'
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 1   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
290614 to 242515 ckt 1
324531 to 342287 ckt 1
342718 to 324141 ckt 1
342757 to 342754 ckt 1
972272 to 342718 ckt 1
972272 to 342718 ckt 2

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2EKPC
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC181.71 %63.0B114.48
120.25
IPDEKPC
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC181.27 %63.0B114.2
120.25
IPDEKPC
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC100.47 %63.0B63.3
71.76
IPDEKPC
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC100.47 %63.0B63.3
71.76
IPDEKPC
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC100.4 %63.0B63.25
71.61
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC185.76 %63.0B117.03
108.3
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC184.33 %63.0B116.13
115.39
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC184.33 %63.0B116.13
115.39
IPDEKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC169.45 %63.0B106.76
115.39
IPDEKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC169.45 %63.0B106.76
115.39
IPDEKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC167.2 %63.0B105.33
108.3
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC185.57 %63.0B116.91
108.3
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC184.13 %63.0B116.0
115.39
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC184.13 %63.0B116.0
115.39
IPDEKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC169.26 %63.0B106.63
115.39
IPDEKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC169.26 %63.0B106.63
115.39
IPDEKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC167.0 %63.0B105.21
108.3
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC164.36 %76.0B124.91
86.41
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC149.35 %76.0B113.51
86.41
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC123.42 %76.0B93.8
65.62
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC123.42 %76.0B93.8
65.62
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC123.12 %76.0B93.57
65.39
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC116.96 %76.0B88.89
65.62
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC116.96 %76.0B88.89
65.62
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC116.65 %76.0B88.66
65.39
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC164.36 %76.0B124.91
86.41
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC149.35 %76.0B113.51
86.41
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC123.42 %76.0B93.8
65.62
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC123.42 %76.0B93.8
65.62
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC123.12 %76.0B93.57
65.39
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC116.96 %76.0B88.89
65.62
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC116.96 %76.0B88.89
65.62
IPDEKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC116.65 %76.0B88.66
65.39
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC264.54 %46.0B121.69
108.3
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC262.5 %46.0B120.75
115.39
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC262.5 %46.0B120.75
115.39
IPDEKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC242.12 %46.0B111.38
115.39
IPDEKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC242.12 %46.0B111.38
115.39
IPDEKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC239.12 %46.0B110.0
108.3
GD2EKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC123.18 %76.0B93.62
91.71
GD2EKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC122.57 %76.0B93.15
88.46
GD2EKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC122.57 %76.0B93.15
88.46
IPDEKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC122.17 %76.0B92.85
91.71
IPDEKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC121.72 %76.0B92.51
88.46
IPDEKPC
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC121.72 %76.0B92.51
88.46
GD2EKPC
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC109.58 %76.0B83.28
81.07
GD2EKPC
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC109.11 %76.0B82.93
79.04
GD2EKPC
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC109.11 %76.0B82.93
79.04
IPDEKPC
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC109.03 %76.0B82.86
81.07
IPDEKPC
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC108.63 %76.0B82.56
79.04
IPDEKPC
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC108.63 %76.0B82.56
79.04
GD2EKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC139.56 %76.0B106.07
101.98
IPDEKPC/LGEE
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC123.42 %76.0B93.8
101.98
GD2EKPC
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC191.37 %63.0B120.56
120.25
IPDEKPC
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC190.92 %63.0B120.28
120.25
IPDEKPC
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC108.33 %63.0B68.25
71.76
IPDEKPC
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC108.33 %63.0B68.25
71.76
IPDEKPC
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC108.26 %63.0B68.2
71.61
GD2EKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC159.66 %92.0B146.89
137.13
IPDEKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC159.39 %92.0B146.64
137.13
GD2EKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC101.7 %92.0B93.57
83.22
GD2EKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC101.7 %92.0B93.57
83.22
GD2EKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC101.69 %92.0B93.56
83.22
IPDEKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC101.56 %92.0B93.44
83.22
IPDEKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC101.56 %92.0B93.44
83.22
IPDEKPC/LGEE
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC101.56 %92.0B93.43
83.22
GD2EKPC
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC199.44 %63.0B125.65
120.25
IPDEKPC
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC199.0 %63.0B125.37
120.25
IPDEKPC
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC115.54 %63.0B72.79
71.76
IPDEKPC
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC115.54 %63.0B72.79
71.76
IPDEKPC
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC115.46 %63.0B72.74
71.61
GD2EKPC/LGEE
2LIBER CH T-2FARLEY KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC147.71 %76.0B112.26
120.25
IPDEKPC/LGEE
2LIBER CH T-2FARLEY KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC147.34 %76.0B111.98
120.25
GD2EKPC
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC184.63 %63.0B116.32
120.25
IPDEKPC
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC184.19 %63.0B116.04
120.25
IPDEKPC
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC102.77 %63.0B64.74
71.76
IPDEKPC
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC102.77 %63.0B64.74
71.76
IPDEKPC
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC102.69 %63.0B64.7
71.61
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC341.22 %76.0B259.33
172.4
IPDEKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC278.09 %76.0B211.35
172.41
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC264.23 %76.0B200.82
129.48
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC263.53 %76.0B200.28
128.91
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC255.29 %76.0B194.02
129.48
IPDEKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC214.24 %76.0B162.82
129.48
IPDEKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC214.24 %76.0B162.82
129.48
IPDEKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC213.5 %76.0B162.26
128.91
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC165.17 %152.0B251.06
176.36
IPDEKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC139.25 %152.0B211.66
176.35
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC123.52 %152.0B187.75
133.58
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC123.52 %152.0B187.75
133.58
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC123.16 %152.0B187.2
133.01
IPDEKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC107.46 %152.0B163.34
133.58
IPDEKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC107.46 %152.0B163.34
133.58
IPDEKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC107.09 %152.0B162.77
133.01
IPDEKPC
2W LONDON-2W LONDON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC117.09 %46.0B53.86
49.57
GD2EKPC
2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC103.11 %74.0B76.3
81.07
GD2EKPC
2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC102.6 %74.0B75.93
79.04
GD2EKPC
2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC102.6 %74.0B75.93
79.04
IPDEKPC
2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC102.55 %74.0B75.89
81.07
IPDEKPC
2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC102.1 %74.0B75.56
79.04
IPDEKPC
2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC102.1 %74.0B75.56
79.04
GD2EKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC155.51 %152.0B236.37
169.3
IPDEKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC149.75 %152.0B227.62
169.3
GD2EKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC120.87 %152.0B183.73
129.07
GD2EKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC120.87 %152.0B183.73
129.07
GD2EKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC120.19 %152.0B182.69
128.0
IPDEKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC117.86 %152.0B179.14
129.07
IPDEKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC117.86 %152.0B179.14
129.07
IPDEKPC
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC117.15 %152.0B178.07
127.99
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC135.39 %501.0B678.29
673.7
IPDEKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC133.2 %501.0B667.32
673.7
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC104.89 %501.0B525.51
525.51
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC104.89 %501.0B525.51
525.51
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC104.35 %501.0B522.77
522.83
IPDEKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC103.17 %501.0B516.89
525.51
IPDEKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC103.17 %501.0B516.89
525.51
IPDEKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC102.63 %501.0B514.19
522.83
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1014_SRT-A
BreakerAC194.84 %298.0B580.62
557.87
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC194.82 %298.0B580.56
561.58
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC194.67 %298.0B580.13
559.74
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1008_SRT-A
BreakerAC194.67 %298.0B580.12
559.74
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1024_SRT-A
BreakerAC194.56 %298.0B579.8
558.92
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC191.01 %298.0B569.2
561.58
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1008_SRT-A
BreakerAC190.55 %298.0B567.85
559.74
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC190.55 %298.0B567.85
559.74
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1024_SRT-A
BreakerAC190.46 %298.0B567.57
558.92
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC188.48 %298.0B561.68
355.55
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC188.47 %298.0B561.64
354.93
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC188.47 %298.0B561.64
354.93
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1024_SRT-A
BreakerAC188.46 %298.0B561.62
354.93
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC188.26 %298.0B561.0
355.24
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC184.41 %298.0B549.53
355.55
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Base Case
SingleAC179.86 %249.0A447.86
308.02
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOP-LAURD 161_SRT-A
BusAC176.44 %298.0B525.79
355.83
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 1_SRT-A
TowerAC172.9 %298.0B515.25
421.75
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 1_SRT-A
TowerAC167.24 %298.0B498.38
421.76
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_PULASKI 161_SRT-A
BusAC165.51 %298.0B493.23
351.39
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC164.09 %298.0B489.0
354.93
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC163.96 %298.0B488.6
355.55
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC163.96 %298.0B488.6
355.55
IPDEKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Base Case
SingleAC159.19 %249.0A396.39
308.02
GD2EKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC269.81 %109.0B294.09
282.89
GD2EKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC269.81 %109.0B294.09
282.89
GD2EKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC269.37 %109.0B293.61
281.08
IPDEKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC269.07 %109.0B293.29
282.89
IPDEKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC269.07 %109.0B293.29
282.89
IPDEKPC
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC268.66 %109.0B292.84
281.08
GD2EKPC/LGEE
5GREEN HAL T-5DELVINTA 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC127.63 %251.0B320.34
318.94
IPDEKPC/LGEE
5GREEN HAL T-5DELVINTA 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC124.8 %251.0B313.25
318.94
GD2EKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC220.92 %152.0B335.8
306.95
IPDEKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC220.6 %152.0B335.31
306.95
GD2EKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC145.66 %152.0B221.41
187.98
GD2EKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC145.6 %152.0B221.32
187.75
GD2EKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC145.6 %152.0B221.32
187.75
IPDEKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC145.56 %152.0B221.25
187.98
IPDEKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC145.5 %152.0B221.16
187.75
IPDEKPC
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC145.5 %152.0B221.16
187.75
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC246.07 %200.0B492.15
451.43
IPDEKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC244.18 %200.0B488.36
451.43
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC168.26 %200.0B336.52
289.32
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC168.03 %200.0B336.06
287.75
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC168.03 %200.0B336.06
287.75
IPDEKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC161.61 %200.0B323.21
289.32
IPDEKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC161.38 %200.0B322.76
287.75
IPDEKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC161.38 %200.0B322.76
287.75
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC412.32 %200.0B824.63
758.38
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC412.08 %200.0B824.16
758.38
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC281.56 %200.0B563.12
477.31
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC281.23 %200.0B562.46
475.49
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC281.23 %200.0B562.46
475.49
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC274.83 %200.0B549.66
477.31
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC274.55 %200.0B549.1
475.49
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC274.55 %200.0B549.1
475.49
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EXT_324130 5ALCALDE 161 324141 5ELIHU 161 1_SRT-L
SingleAC141.4 %200.0B282.8
158.62
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC130.02 %200.0B260.03
143.35
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC129.29 %200.0B258.57
141.67
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC129.28 %200.0B258.56
141.67
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EXT_324130 5ALCALDE 161 324141 5ELIHU 161 1_SRT-L
SingleAC125.9 %200.0B251.79
158.63
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC118.9 %200.0B237.8
143.35
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC118.15 %200.0B236.29
141.67
IPDEKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC118.15 %200.0B236.29
141.67
GD2EKPC
5PITTSBURG-5TYNER 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC148.71 %250.0B371.77
346.81
IPDEKPC
5PITTSBURG-5TYNER 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC146.02 %250.0B365.04
346.81
GD2EKPC
5TYNER-5GREEN HAL T 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC128.66 %250.0B321.65
318.94
IPDEKPC
5TYNER-5GREEN HAL T 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC125.82 %250.0B314.55
318.94
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC138.88 %298.0B413.87
372.99
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC138.88 %298.0B413.86
372.99
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1024_SRT-A
BreakerAC138.88 %298.0B413.85
372.99
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC138.75 %298.0B413.46
372.97
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC138.75 %298.0B413.46
372.97
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC138.73 %298.0B413.42
372.98
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC136.54 %298.0B406.88
372.99
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC136.53 %298.0B406.87
372.99
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1024_SRT-A
BreakerAC136.53 %298.0B406.87
372.99
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC136.4 %298.0B406.48
372.97
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC136.4 %298.0B406.48
372.97
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC136.39 %298.0B406.43
372.98
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Base Case
SingleAC124.4 %267.0A332.13
326.68
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Base Case
SingleAC123.63 %267.0A330.09
326.68
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC117.12 %298.0B349.01
349.87
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC116.32 %298.0B346.62
349.87
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC248.98 %210.0B522.85
522.83
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC244.89 %210.0B514.27
522.83
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC181.36 %210.0B380.86
345.22
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC181.36 %210.0B380.86
345.22
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-3_LAURL S50-1024_SRT-A
BreakerAC181.36 %210.0B380.85
345.22
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC181.19 %210.0B380.49
345.2
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC181.19 %210.0B380.49
345.2
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC181.17 %210.0B380.45
345.21
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC179.31 %210.0B376.55
345.22
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC179.31 %210.0B376.55
345.22
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-3_LAURL S50-1024_SRT-A
BreakerAC179.31 %210.0B376.54
345.22
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC179.14 %210.0B376.19
345.2
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC179.14 %210.0B376.19
345.2
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC179.11 %210.0B376.14
345.21
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Base Case
SingleAC165.26 %186.0A307.38
302.36
IPDEKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Base Case
SingleAC164.24 %186.0A305.49
302.36
GD2EKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC140.57 %210.0B295.2
282.89
GD2EKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC140.57 %210.0B295.19
282.89
GD2EKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC140.27 %210.0B294.57
281.08
IPDEKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC140.19 %210.0B294.39
282.89
IPDEKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC140.19 %210.0B294.39
282.89
IPDEKPC
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC139.91 %210.0B293.81
281.08
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC254.67 %298.0B758.9
758.95
IPDEKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1064_SRT-A
BreakerDC254.67 %298.0B758.9
758.95
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC167.08 %298.0B497.9
477.87
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC166.87 %298.0B497.27
476.06
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC166.87 %298.0B497.27
476.06
IPDEKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC161.66 %298.0B481.75
477.87
IPDEKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC161.48 %298.0B481.21
476.06
IPDEKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC161.48 %298.0B481.21
476.06

Details for 2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:181.71 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:114.48
MW Contribution:
120.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
120.251
NYPJM->LTFIMP_NY
CLTF
0.009
LGEELTFEXP_LGEE->PJM
CLTF
0.008
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.038
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.167
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:181.27 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:114.2
MW Contribution:
120.25
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
120.251

Details for [AH1-721] 2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.47 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:63.3
MW Contribution:
71.76
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.764

Details for [AH1-721] 2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.47 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:63.3
MW Contribution:
71.76
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.764

Details for [AH1-721] 2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BACON CRK T-2LIBER CH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.4 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:63.25
MW Contribution:
71.61
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.608

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.76 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:117.03
MW Contribution:
108.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
108.3
966021AG1-471 GEN
Solar/Wind Harmer
2.567
971485AH1-239 GEN
Solar/Wind Harmer
3.414
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.055
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.071
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.541
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.306
G-007ALTFEXP_G-007A->PJM
CMTX
0.005
VFTLTFEXP_VFT->PJM
CMTX
0.013
NYPJM->LTFIMP_NY
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
WECLTFEXP_WEC->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.083
TVALTFEXP_TVA->PJM
CLTF
0.199
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
MECLTFEXP_MEC->PJM
CLTF
0.055
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.212
LAGNLTFEXP_LAGN->PJM
CLTF
0.297
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.811

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.33 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:116.13
MW Contribution:
115.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.389
966021AG1-471 GEN
Solar/Wind Harmer
2.376
971485AH1-239 GEN
Solar/Wind Harmer
3.126
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.259
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.228
G-007ALTFEXP_G-007A->PJM
CMTX
0.018
VFTLTFEXP_VFT->PJM
CMTX
0.048
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.064
TVALTFEXP_TVA->PJM
CLTF
0.111
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.238
LAGNLTFEXP_LAGN->PJM
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.315

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:184.33 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:116.13
MW Contribution:
115.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.389
966021AG1-471 GEN
Solar/Wind Harmer
2.376
971485AH1-239 GEN
Solar/Wind Harmer
3.126
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.259
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.228
G-007ALTFEXP_G-007A->PJM
CMTX
0.018
VFTLTFEXP_VFT->PJM
CMTX
0.048
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.064
TVALTFEXP_TVA->PJM
CLTF
0.111
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.238
LAGNLTFEXP_LAGN->PJM
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.315

Details for [AH1-721] 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:169.45 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:106.76
MW Contribution:
115.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
115.389

Details for [AH1-721] 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:169.45 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:106.76
MW Contribution:
115.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
115.389

Details for [AH1-721] 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.2 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:105.33
MW Contribution:
108.3
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
108.3

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.57 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:116.91
MW Contribution:
108.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
108.3
966021AG1-471 GEN
Solar/Wind Harmer
2.567
971485AH1-239 GEN
Solar/Wind Harmer
3.414
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.055
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.071
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.541
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.306
G-007ALTFEXP_G-007A->PJM
CMTX
0.005
VFTLTFEXP_VFT->PJM
CMTX
0.013
NYPJM->LTFIMP_NY
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
WECLTFEXP_WEC->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.083
TVALTFEXP_TVA->PJM
CLTF
0.199
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
MECLTFEXP_MEC->PJM
CLTF
0.055
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.212
LAGNLTFEXP_LAGN->PJM
CLTF
0.297
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.811

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.13 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:116.0
MW Contribution:
115.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.389
966021AG1-471 GEN
Solar/Wind Harmer
2.376
971485AH1-239 GEN
Solar/Wind Harmer
3.126
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.259
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.228
G-007ALTFEXP_G-007A->PJM
CMTX
0.018
VFTLTFEXP_VFT->PJM
CMTX
0.048
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.064
TVALTFEXP_TVA->PJM
CLTF
0.111
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.238
LAGNLTFEXP_LAGN->PJM
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.315

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:184.13 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:116.0
MW Contribution:
115.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.389
966021AG1-471 GEN
Solar/Wind Harmer
2.376
971485AH1-239 GEN
Solar/Wind Harmer
3.126
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.259
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.228
G-007ALTFEXP_G-007A->PJM
CMTX
0.018
VFTLTFEXP_VFT->PJM
CMTX
0.048
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.064
TVALTFEXP_TVA->PJM
CLTF
0.111
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.238
LAGNLTFEXP_LAGN->PJM
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.315

Details for [AH1-721] 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:169.26 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:106.63
MW Contribution:
115.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
115.389

Details for [AH1-721] 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:169.26 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:106.63
MW Contribution:
115.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
115.389

Details for [AH1-721] 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.0 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:105.21
MW Contribution:
108.3
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
108.3

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:164.36 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:124.91
MW Contribution:
86.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
102
966021AG1-471 GEN
Solar/Wind Harmer
1.852
971485AH1-239 GEN
Solar/Wind Harmer
2.547
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.752
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.895
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.28
NYPJM->LTFIMP_NY
CLTF
0.01
LGEELTFEXP_LGEE->PJM
CLTF
0.011
WECLTFEXP_WEC->PJM
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
0.069
TVALTFEXP_TVA->PJM
CLTF
0.285
MECLTFEXP_MEC->PJM
CLTF
0.17
LAGNLTFEXP_LAGN->PJM
CLTF
0.457
SIGELTFEXP_SIGE->PJM
CLTF
0.005
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.761
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.0 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:149.35 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:113.51
MW Contribution:
86.41
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
102
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.0 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.42 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:93.8
MW Contribution:
65.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
77.517
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.406
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.48
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.598
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.191
NYPJM->LTFIMP_NY
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.011
CPLELTFEXP_CPLE->PJM
CLTF
0.047
TVALTFEXP_TVA->PJM
CLTF
0.197
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
MECLTFEXP_MEC->PJM
CLTF
0.104
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.027
LAGNLTFEXP_LAGN->PJM
CLTF
0.311
SIGELTFEXP_SIGE->PJM
CLTF
0.002
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.51
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.52 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:123.42 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:93.8
MW Contribution:
65.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
77.517
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.406
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.48
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.598
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.191
NYPJM->LTFIMP_NY
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.011
CPLELTFEXP_CPLE->PJM
CLTF
0.047
TVALTFEXP_TVA->PJM
CLTF
0.197
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
MECLTFEXP_MEC->PJM
CLTF
0.104
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.027
LAGNLTFEXP_LAGN->PJM
CLTF
0.311
SIGELTFEXP_SIGE->PJM
CLTF
0.002
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.51
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.52 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:123.12 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:93.57
MW Contribution:
65.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
77.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.407
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.482
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.598
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.191
NYPJM->LTFIMP_NY
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.011
CPLELTFEXP_CPLE->PJM
CLTF
0.047
TVALTFEXP_TVA->PJM
CLTF
0.197
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
MECLTFEXP_MEC->PJM
CLTF
0.104
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.027
LAGNLTFEXP_LAGN->PJM
CLTF
0.311
SIGELTFEXP_SIGE->PJM
CLTF
0.002
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.509
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.3 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.96 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:88.89
MW Contribution:
65.62
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
77.517
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.52 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:116.96 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:88.89
MW Contribution:
65.62
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
77.517
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.52 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:116.65 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:88.66
MW Contribution:
65.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
77.303
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.3 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:164.36 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:124.91
MW Contribution:
86.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
102
966021AG1-471 GEN
Solar/Wind Harmer
1.852
971485AH1-239 GEN
Solar/Wind Harmer
2.547
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.752
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.895
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.28
NYPJM->LTFIMP_NY
CLTF
0.01
LGEELTFEXP_LGEE->PJM
CLTF
0.011
WECLTFEXP_WEC->PJM
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
0.069
TVALTFEXP_TVA->PJM
CLTF
0.285
MECLTFEXP_MEC->PJM
CLTF
0.17
LAGNLTFEXP_LAGN->PJM
CLTF
0.457
SIGELTFEXP_SIGE->PJM
CLTF
0.005
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.761
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.0 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:149.35 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:113.51
MW Contribution:
86.41
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
102
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 102.0 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.42 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:93.8
MW Contribution:
65.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
77.517
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.406
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.48
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.598
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.191
NYPJM->LTFIMP_NY
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.011
CPLELTFEXP_CPLE->PJM
CLTF
0.047
TVALTFEXP_TVA->PJM
CLTF
0.197
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
MECLTFEXP_MEC->PJM
CLTF
0.104
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.027
LAGNLTFEXP_LAGN->PJM
CLTF
0.311
SIGELTFEXP_SIGE->PJM
CLTF
0.002
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.51
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.52 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:123.42 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:93.8
MW Contribution:
65.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
77.517
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.406
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.48
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.598
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.191
NYPJM->LTFIMP_NY
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.011
CPLELTFEXP_CPLE->PJM
CLTF
0.047
TVALTFEXP_TVA->PJM
CLTF
0.197
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
MECLTFEXP_MEC->PJM
CLTF
0.104
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.027
LAGNLTFEXP_LAGN->PJM
CLTF
0.311
SIGELTFEXP_SIGE->PJM
CLTF
0.002
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.51
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.52 MW.

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:123.12 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:93.57
MW Contribution:
65.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
77.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.407
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.482
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.598
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.191
NYPJM->LTFIMP_NY
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.011
CPLELTFEXP_CPLE->PJM
CLTF
0.047
TVALTFEXP_TVA->PJM
CLTF
0.197
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
MECLTFEXP_MEC->PJM
CLTF
0.104
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.027
LAGNLTFEXP_LAGN->PJM
CLTF
0.311
SIGELTFEXP_SIGE->PJM
CLTF
0.002
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.509
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.3 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.96 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:88.89
MW Contribution:
65.62
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
77.517
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.52 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:116.96 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:88.89
MW Contribution:
65.62
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
77.517
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.52 MW.

Details for [AH1-721] 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:116.65 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:88.66
MW Contribution:
65.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
77.303
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 77.3 MW.

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:264.54 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:121.69
MW Contribution:
108.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
108.3
966021AG1-471 GEN
Solar/Wind Harmer
2.567
971485AH1-239 GEN
Solar/Wind Harmer
3.414
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.055
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.071
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.541
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.306
G-007ALTFEXP_G-007A->PJM
CMTX
0.005
VFTLTFEXP_VFT->PJM
CMTX
0.013
NYPJM->LTFIMP_NY
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
WECLTFEXP_WEC->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.083
TVALTFEXP_TVA->PJM
CLTF
0.199
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
MECLTFEXP_MEC->PJM
CLTF
0.055
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.212
LAGNLTFEXP_LAGN->PJM
CLTF
0.297
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.811

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:262.5 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:120.75
MW Contribution:
115.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.389
966021AG1-471 GEN
Solar/Wind Harmer
2.376
971485AH1-239 GEN
Solar/Wind Harmer
3.126
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.259
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.228
G-007ALTFEXP_G-007A->PJM
CMTX
0.018
VFTLTFEXP_VFT->PJM
CMTX
0.048
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.064
TVALTFEXP_TVA->PJM
CLTF
0.111
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.238
LAGNLTFEXP_LAGN->PJM
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.315

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:262.5 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:120.75
MW Contribution:
115.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.389
966021AG1-471 GEN
Solar/Wind Harmer
2.376
971485AH1-239 GEN
Solar/Wind Harmer
3.126
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.259
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.228
G-007ALTFEXP_G-007A->PJM
CMTX
0.018
VFTLTFEXP_VFT->PJM
CMTX
0.048
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.064
TVALTFEXP_TVA->PJM
CLTF
0.111
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.238
LAGNLTFEXP_LAGN->PJM
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.315

Details for [AH1-721] 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:242.12 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:111.38
MW Contribution:
115.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
115.389

Details for [AH1-721] 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:242.12 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:111.38
MW Contribution:
115.39
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
115.389

Details for [AH1-721] 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:239.12 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:110.0
MW Contribution:
108.3
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
108.3

Details for 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.18 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:93.62
MW Contribution:
91.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
91.71
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.05
G-007ALTFEXP_G-007A->PJM
CMTX
0.02
VFTLTFEXP_VFT->PJM
CMTX
0.053
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.038
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.48
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.009
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.065
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.57 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:93.15
MW Contribution:
88.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
88.464
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.039
G-007ALTFEXP_G-007A->PJM
CMTX
0.015
VFTLTFEXP_VFT->PJM
CMTX
0.042
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.044
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.395
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.065
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:122.57 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:93.15
MW Contribution:
88.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
88.464
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.039
G-007ALTFEXP_G-007A->PJM
CMTX
0.015
VFTLTFEXP_VFT->PJM
CMTX
0.042
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.044
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.395
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.065
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.17 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:92.85
MW Contribution:
91.71
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
91.71

Details for [AH1-721] 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.72 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:92.51
MW Contribution:
88.46
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
88.464

Details for [AH1-721] 2DENNY-2GREGORY R T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2GREGORY R T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.72 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:92.51
MW Contribution:
88.46
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
88.464

Details for 2DENNY-2WIBORG T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.58 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:83.28
MW Contribution:
81.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
81.068
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.073
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.08
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.055
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.196
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.002
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2DENNY-2WIBORG T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.11 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:82.93
MW Contribution:
79.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
79.039
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.075
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.052
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.002
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2DENNY-2WIBORG T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.11 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:82.93
MW Contribution:
79.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
79.039
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.075
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.052
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.002
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2DENNY-2WIBORG T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.03 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:82.86
MW Contribution:
81.07
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
81.068

Details for [AH1-721] 2DENNY-2WIBORG T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.63 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:82.56
MW Contribution:
79.04
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
79.039

Details for [AH1-721] 2DENNY-2WIBORG T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2WIBORG T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.63 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:82.56
MW Contribution:
79.04
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
79.039

Details for 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.56 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:106.07
MW Contribution:
101.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
101.981
339231AF1-038_GEN
Solar/Wind Helper
3.662
339255AE2-071 GEN
Solar/Wind Helper
0.75
339250AF1-203 GEN
Solar/Wind Helper
0.429
339206AE1-143 GEN
Solar/Wind Helper
2.461
339236AF1-050_GEN
Solar/Wind Helper
1.235
339241AF1-083 GEN
Solar/Wind Helper
1.245
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.347
G-007ALTFEXP_G-007A->PJM
CMTX
0.17
VFTLTFEXP_VFT->PJM
CMTX
0.457
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.041
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.143
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.089
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.381
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.42 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:93.8
MW Contribution:
101.98
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
101.981

Details for 2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:191.37 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:120.56
MW Contribution:
120.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
120.251
NYPJM->LTFIMP_NY
CLTF
0.009
LGEELTFEXP_LGEE->PJM
CLTF
0.008
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.038
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.167
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:190.92 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:120.28
MW Contribution:
120.25
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
120.251

Details for [AH1-721] 2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.33 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:68.25
MW Contribution:
71.76
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.764

Details for [AH1-721] 2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.33 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:68.25
MW Contribution:
71.76
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.764

Details for [AH1-721] 2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2KEAVY 2 T-2S CORBIN 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.26 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:68.2
MW Contribution:
71.61
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.608

Details for 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:159.66 %
Rating:92.0 MVA
Rating Type:B
MVA to Mitigate:146.89
MW Contribution:
137.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
137.129
NYPJM->LTFIMP_NY
CLTF
0.009
LGEELTFEXP_LGEE->PJM
CLTF
0.006
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.051
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.035
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.149
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:159.39 %
Rating:92.0 MVA
Rating Type:B
MVA to Mitigate:146.64
MW Contribution:
137.13
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
137.129

Details for 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.7 %
Rating:92.0 MVA
Rating Type:B
MVA to Mitigate:93.57
MW Contribution:
83.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
83.222
NYPJM->LTFIMP_NY
CLTF
0.009
LGEELTFEXP_LGEE->PJM
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.036
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.024
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.045
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.7 %
Rating:92.0 MVA
Rating Type:B
MVA to Mitigate:93.57
MW Contribution:
83.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
83.222
NYPJM->LTFIMP_NY
CLTF
0.009
LGEELTFEXP_LGEE->PJM
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.036
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.024
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.045
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.69 %
Rating:92.0 MVA
Rating Type:B
MVA to Mitigate:93.56
MW Contribution:
83.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
83.217
NYPJM->LTFIMP_NY
CLTF
0.009
LGEELTFEXP_LGEE->PJM
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.035
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.024
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.044
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.56 %
Rating:92.0 MVA
Rating Type:B
MVA to Mitigate:93.44
MW Contribution:
83.22
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
83.222

Details for [AH1-721] 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.56 %
Rating:92.0 MVA
Rating Type:B
MVA to Mitigate:93.44
MW Contribution:
83.22
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
83.222

Details for [AH1-721] 2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LAUREL CO-2HOPEWELL 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.56 %
Rating:92.0 MVA
Rating Type:B
MVA to Mitigate:93.43
MW Contribution:
83.22
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
83.217

Details for 2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:199.44 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:125.65
MW Contribution:
120.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
120.251
NYPJM->LTFIMP_NY
CLTF
0.009
LGEELTFEXP_LGEE->PJM
CLTF
0.008
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.038
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.167
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:199.0 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:125.37
MW Contribution:
120.25
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
120.251

Details for [AH1-721] 2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.54 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:72.79
MW Contribution:
71.76
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.764

Details for [AH1-721] 2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.54 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:72.79
MW Contribution:
71.76
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.764

Details for [AH1-721] 2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2LAUREL CO-2KEAVY 2 T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.46 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:72.74
MW Contribution:
71.61
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.608

Details for 2LIBER CH T-2FARLEY KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LIBER CH T-2FARLEY KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:147.71 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:112.26
MW Contribution:
120.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
120.251
NYPJM->LTFIMP_NY
CLTF
0.009
LGEELTFEXP_LGEE->PJM
CLTF
0.008
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.038
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.167
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2LIBER CH T-2FARLEY KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2LIBER CH T-2FARLEY KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:147.34 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:111.98
MW Contribution:
120.25
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
120.251

Details for 2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:184.63 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:116.32
MW Contribution:
120.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
120.251
NYPJM->LTFIMP_NY
CLTF
0.009
LGEELTFEXP_LGEE->PJM
CLTF
0.008
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.038
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.167
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:184.19 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:116.04
MW Contribution:
120.25
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
120.251

Details for [AH1-721] 2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.77 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:64.74
MW Contribution:
71.76
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.764

Details for [AH1-721] 2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.77 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:64.74
MW Contribution:
71.76
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.764

Details for [AH1-721] 2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2S CORBIN-2BACON CRK T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.69 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:64.7
MW Contribution:
71.61
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
71.608

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:341.22 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:259.33
MW Contribution:
172.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
203.526
966021AG1-471 GEN
Solar/Wind Harmer
4.239
971485AH1-239 GEN
Solar/Wind Harmer
6.022
964901AG1-354 GEN
Solar/Wind Harmer
6.758
964781AG1-341 GEN
Solar/Wind Harmer
5.402
964781AG1-341 GEN
Solar/Wind Harmer
2.971
950011AG9-010
External Queue
4.5946855545043945
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.351
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.435
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.396
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.511
NYPJM->LTFIMP_NY
CLTF
0.043
LGEELTFEXP_LGEE->PJM
CLTF
0.087
WECLTFEXP_WEC->PJM
CLTF
0.066
CPLELTFEXP_CPLE->PJM
CLTF
0.109
TVALTFEXP_TVA->PJM
CLTF
0.746
MECLTFEXP_MEC->PJM
CLTF
0.501
LAGNLTFEXP_LAGN->PJM
CLTF
1.215
SIGELTFEXP_SIGE->PJM
CLTF
0.018
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.513
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 203.53 MW.

Details for [AH1-721] 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:278.09 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:211.35
MW Contribution:
172.41
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
203.526
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 203.53 MW.

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:264.23 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:200.82
MW Contribution:
129.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
153
966021AG1-471 GEN
Solar/Wind Harmer
3.476
971485AH1-239 GEN
Solar/Wind Harmer
4.942
964901AG1-354 GEN
Solar/Wind Harmer
5.48
964781AG1-341 GEN
Solar/Wind Harmer
4.391
964781AG1-341 GEN
Solar/Wind Harmer
2.415
950011AG9-010
External Queue
3.741147518157959
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.637
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.769
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.783
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.327
NYPJM->LTFIMP_NY
CLTF
0.041
LGEELTFEXP_LGEE->PJM
CLTF
0.037
WECLTFEXP_WEC->PJM
CLTF
0.046
CPLELTFEXP_CPLE->PJM
CLTF
0.062
TVALTFEXP_TVA->PJM
CLTF
0.564
MECLTFEXP_MEC->PJM
CLTF
0.366
LAGNLTFEXP_LAGN->PJM
CLTF
0.913
SIGELTFEXP_SIGE->PJM
CLTF
0.013
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.995
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 153.0 MW.

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:263.53 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:200.28
MW Contribution:
128.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
152.46
966021AG1-471 GEN
Solar/Wind Harmer
3.476
971485AH1-239 GEN
Solar/Wind Harmer
4.941
964901AG1-354 GEN
Solar/Wind Harmer
5.485
964781AG1-341 GEN
Solar/Wind Harmer
4.395
964781AG1-341 GEN
Solar/Wind Harmer
2.417
950011AG9-010
External Queue
3.7449028491973877
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.773
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.785
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.327
NYPJM->LTFIMP_NY
CLTF
0.041
LGEELTFEXP_LGEE->PJM
CLTF
0.037
WECLTFEXP_WEC->PJM
CLTF
0.046
CPLELTFEXP_CPLE->PJM
CLTF
0.062
TVALTFEXP_TVA->PJM
CLTF
0.564
MECLTFEXP_MEC->PJM
CLTF
0.366
LAGNLTFEXP_LAGN->PJM
CLTF
0.914
SIGELTFEXP_SIGE->PJM
CLTF
0.013
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.994
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 152.46 MW.

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:255.29 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:194.02
MW Contribution:
129.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
153
966021AG1-471 GEN
Solar/Wind Harmer
3.476
971485AH1-239 GEN
Solar/Wind Harmer
4.942
964901AG1-354 GEN
Solar/Wind Harmer
5.48
950011AG9-010
External Queue
3.741147518157959
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.637
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.769
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.783
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.327
NYPJM->LTFIMP_NY
CLTF
0.041
LGEELTFEXP_LGEE->PJM
CLTF
0.037
WECLTFEXP_WEC->PJM
CLTF
0.046
CPLELTFEXP_CPLE->PJM
CLTF
0.062
TVALTFEXP_TVA->PJM
CLTF
0.564
MECLTFEXP_MEC->PJM
CLTF
0.366
LAGNLTFEXP_LAGN->PJM
CLTF
0.913
SIGELTFEXP_SIGE->PJM
CLTF
0.013
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.995
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 153.0 MW.

Details for [AH1-721] 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:214.24 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:162.82
MW Contribution:
129.48
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
153
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 153.0 MW.

Details for [AH1-721] 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:214.24 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:162.82
MW Contribution:
129.48
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
153
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 153.0 MW.

Details for [AH1-721] 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:213.5 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:162.26
MW Contribution:
128.91
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
152.46
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 152.46 MW.

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:165.17 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:251.06
MW Contribution:
176.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
208.195
966021AG1-471 GEN
Solar/Wind Harmer
3.729
971485AH1-239 GEN
Solar/Wind Harmer
5.255
964901AG1-354 GEN
Solar/Wind Harmer
5.781
964781AG1-341 GEN
Solar/Wind Harmer
4.255
964781AG1-341 GEN
Solar/Wind Harmer
2.34
950011AG9-010
External Queue
4.469371795654297
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.927
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.065
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.337
NYPJM->LTFIMP_NY
CLTF
0.037
LGEELTFEXP_LGEE->PJM
CLTF
0.086
WECLTFEXP_WEC->PJM
CLTF
0.054
CPLELTFEXP_CPLE->PJM
CLTF
0.066
TVALTFEXP_TVA->PJM
CLTF
0.57
MECLTFEXP_MEC->PJM
CLTF
0.401
LAGNLTFEXP_LAGN->PJM
CLTF
0.934
SIGELTFEXP_SIGE->PJM
CLTF
0.016
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.225
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 208.19 MW.

Details for [AH1-721] 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:139.25 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:211.66
MW Contribution:
176.35
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
208.195
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 208.19 MW.

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.52 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:187.75
MW Contribution:
133.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
157.831
966021AG1-471 GEN
Solar/Wind Harmer
2.968
971485AH1-239 GEN
Solar/Wind Harmer
4.178
964901AG1-354 GEN
Solar/Wind Harmer
4.508
950011AG9-010
External Queue
3.6185762882232666
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.215
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.405
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.153
NYPJM->LTFIMP_NY
CLTF
0.035
LGEELTFEXP_LGEE->PJM
CLTF
0.037
WECLTFEXP_WEC->PJM
CLTF
0.034
CPLELTFEXP_CPLE->PJM
CLTF
0.019
TVALTFEXP_TVA->PJM
CLTF
0.389
MECLTFEXP_MEC->PJM
CLTF
0.266
LAGNLTFEXP_LAGN->PJM
CLTF
0.633
SIGELTFEXP_SIGE->PJM
CLTF
0.01
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.708
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 157.83 MW.

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:123.52 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:187.75
MW Contribution:
133.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
157.831
966021AG1-471 GEN
Solar/Wind Harmer
2.968
971485AH1-239 GEN
Solar/Wind Harmer
4.178
964901AG1-354 GEN
Solar/Wind Harmer
4.508
950011AG9-010
External Queue
3.6185762882232666
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.215
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.405
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.153
NYPJM->LTFIMP_NY
CLTF
0.035
LGEELTFEXP_LGEE->PJM
CLTF
0.037
WECLTFEXP_WEC->PJM
CLTF
0.034
CPLELTFEXP_CPLE->PJM
CLTF
0.019
TVALTFEXP_TVA->PJM
CLTF
0.389
MECLTFEXP_MEC->PJM
CLTF
0.266
LAGNLTFEXP_LAGN->PJM
CLTF
0.633
SIGELTFEXP_SIGE->PJM
CLTF
0.01
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.708
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 157.83 MW.

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:123.16 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:187.2
MW Contribution:
133.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
157.298
966021AG1-471 GEN
Solar/Wind Harmer
2.968
971485AH1-239 GEN
Solar/Wind Harmer
4.177
964901AG1-354 GEN
Solar/Wind Harmer
4.512
950011AG9-010
External Queue
3.622286796569824
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.217
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.409
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.241
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.153
NYPJM->LTFIMP_NY
CLTF
0.035
LGEELTFEXP_LGEE->PJM
CLTF
0.037
WECLTFEXP_WEC->PJM
CLTF
0.034
CPLELTFEXP_CPLE->PJM
CLTF
0.019
TVALTFEXP_TVA->PJM
CLTF
0.389
MECLTFEXP_MEC->PJM
CLTF
0.266
LAGNLTFEXP_LAGN->PJM
CLTF
0.634
SIGELTFEXP_SIGE->PJM
CLTF
0.01
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.707
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 157.3 MW.

Details for [AH1-721] 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.46 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:163.34
MW Contribution:
133.58
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
157.831
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 157.83 MW.

Details for [AH1-721] 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.46 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:163.34
MW Contribution:
133.58
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
157.831
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 157.83 MW.

Details for [AH1-721] 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.09 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:162.77
MW Contribution:
133.01
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
157.298
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 157.3 MW.

Details for [AH1-721] 2W LONDON-2W LONDON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2W LONDON-2W LONDON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:117.09 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:53.86
MW Contribution:
49.57
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
49.571

Details for 2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.11 %
Rating:74.0 MVA
Rating Type:B
MVA to Mitigate:76.3
MW Contribution:
81.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
81.068
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.073
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.08
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.055
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.196
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.002
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.6 %
Rating:74.0 MVA
Rating Type:B
MVA to Mitigate:75.93
MW Contribution:
79.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
79.039
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.075
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.052
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.002
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.6 %
Rating:74.0 MVA
Rating Type:B
MVA to Mitigate:75.93
MW Contribution:
79.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
79.039
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.075
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.052
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.002
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.55 %
Rating:74.0 MVA
Rating Type:B
MVA to Mitigate:75.89
MW Contribution:
81.07
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
81.068

Details for [AH1-721] 2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.1 %
Rating:74.0 MVA
Rating Type:B
MVA to Mitigate:75.56
MW Contribution:
79.04
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
79.039

Details for [AH1-721] 2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
2WHITLEY CTY-2MCCREARY CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.1 %
Rating:74.0 MVA
Rating Type:B
MVA to Mitigate:75.56
MW Contribution:
79.04
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
79.039

Details for 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:155.51 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:236.37
MW Contribution:
169.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
200.006
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.214
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.251
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.198
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.275
NYPJM->LTFIMP_NY
CLTF
0.019
LGEELTFEXP_LGEE->PJM
CLTF
0.059
WECLTFEXP_WEC->PJM
CLTF
0.034
CPLELTFEXP_CPLE->PJM
CLTF
0.062
TVALTFEXP_TVA->PJM
CLTF
0.368
MECLTFEXP_MEC->PJM
CLTF
0.254
LAGNLTFEXP_LAGN->PJM
CLTF
0.603
SIGELTFEXP_SIGE->PJM
CLTF
0.01
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.402
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 200.01 MW.

Details for [AH1-721] 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:149.75 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:227.62
MW Contribution:
169.3
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
200.006
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 200.01 MW.

Details for 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.87 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:183.73
MW Contribution:
129.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
152.647
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.544
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.624
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.102
NYPJM->LTFIMP_NY
CLTF
0.016
LGEELTFEXP_LGEE->PJM
CLTF
0.012
WECLTFEXP_WEC->PJM
CLTF
0.015
CPLELTFEXP_CPLE->PJM
CLTF
0.018
TVALTFEXP_TVA->PJM
CLTF
0.197
MECLTFEXP_MEC->PJM
CLTF
0.127
LAGNLTFEXP_LAGN->PJM
CLTF
0.32
SIGELTFEXP_SIGE->PJM
CLTF
0.005
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.917
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 152.65 MW.

Details for 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:120.87 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:183.73
MW Contribution:
129.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
152.647
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.544
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.624
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.102
NYPJM->LTFIMP_NY
CLTF
0.016
LGEELTFEXP_LGEE->PJM
CLTF
0.012
WECLTFEXP_WEC->PJM
CLTF
0.015
CPLELTFEXP_CPLE->PJM
CLTF
0.018
TVALTFEXP_TVA->PJM
CLTF
0.197
MECLTFEXP_MEC->PJM
CLTF
0.127
LAGNLTFEXP_LAGN->PJM
CLTF
0.32
SIGELTFEXP_SIGE->PJM
CLTF
0.005
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.917
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 152.65 MW.

Details for 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.19 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:182.69
MW Contribution:
128.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
151.642
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.549
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.698
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.103
NYPJM->LTFIMP_NY
CLTF
0.017
LGEELTFEXP_LGEE->PJM
CLTF
0.013
WECLTFEXP_WEC->PJM
CLTF
0.015
CPLELTFEXP_CPLE->PJM
CLTF
0.018
TVALTFEXP_TVA->PJM
CLTF
0.198
MECLTFEXP_MEC->PJM
CLTF
0.128
LAGNLTFEXP_LAGN->PJM
CLTF
0.322
SIGELTFEXP_SIGE->PJM
CLTF
0.005
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.915
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 151.64 MW.

Details for [AH1-721] 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.86 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:179.14
MW Contribution:
129.07
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
152.647
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 152.65 MW.

Details for [AH1-721] 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:117.86 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:179.14
MW Contribution:
129.07
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
152.647
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 152.65 MW.

Details for [AH1-721] 5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-2COOPER 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.15 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:178.07
MW Contribution:
127.99
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
151.642
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 151.64 MW.

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:135.39 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:678.29
MW Contribution:
673.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
673.695
966021AG1-471 GEN
Solar/Wind Harmer
2.75
971485AH1-239 GEN
Solar/Wind Harmer
3.617
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.067
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.527
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.346
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.3
G-007ALTFEXP_G-007A->PJM
CMTX
0.04
VFTLTFEXP_VFT->PJM
CMTX
0.106
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.086
TVALTFEXP_TVA->PJM
CLTF
0.137
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.067
MECLTFEXP_MEC->PJM
CLTF
0.015
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.219
LAGNLTFEXP_LAGN->PJM
CLTF
0.195
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.503

Details for [AH1-721] 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:133.2 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:667.32
MW Contribution:
673.7
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
673.695

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.89 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:525.51
MW Contribution:
525.51
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
525.508
339231AF1-038_GEN
Solar/Wind Helper
1.557
339206AE1-143 GEN
Solar/Wind Helper
2.091
339236AF1-050_GEN
Solar/Wind Helper
0.911
339241AF1-083 GEN
Solar/Wind Helper
0.999
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.131
G-007ALTFEXP_G-007A->PJM
CMTX
0.065
VFTLTFEXP_VFT->PJM
CMTX
0.176
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.032
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.935
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.179
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.642
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.984

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.89 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:525.51
MW Contribution:
525.51
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
525.508
339231AF1-038_GEN
Solar/Wind Helper
1.557
339206AE1-143 GEN
Solar/Wind Helper
2.091
339236AF1-050_GEN
Solar/Wind Helper
0.911
339241AF1-083 GEN
Solar/Wind Helper
0.999
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.131
G-007ALTFEXP_G-007A->PJM
CMTX
0.065
VFTLTFEXP_VFT->PJM
CMTX
0.176
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.032
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.935
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.179
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.642
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.984

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.35 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:522.77
MW Contribution:
522.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
522.825
339231AF1-038_GEN
Solar/Wind Helper
1.549
339206AE1-143 GEN
Solar/Wind Helper
2.08
339236AF1-050_GEN
Solar/Wind Helper
0.907
339241AF1-083 GEN
Solar/Wind Helper
0.994
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.13
G-007ALTFEXP_G-007A->PJM
CMTX
0.065
VFTLTFEXP_VFT->PJM
CMTX
0.175
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.032
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.93
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.178
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.639
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.979

Details for [AH1-721] 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.17 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:516.89
MW Contribution:
525.51
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
525.508

Details for [AH1-721] 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.17 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:516.89
MW Contribution:
525.51
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
525.508

Details for [AH1-721] 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.63 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:514.19
MW Contribution:
522.83
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
522.825

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:194.84 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:580.62
MW Contribution:
557.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
557.866
966021AG1-471 GEN
Solar/Wind Harmer
2.95
971485AH1-239 GEN
Solar/Wind Harmer
3.955
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.678
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.44
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.201
NYPJM->LTFIMP_NY
CLTF
0.016
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.047
TVALTFEXP_TVA->PJM
CLTF
0.195
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.149
MECLTFEXP_MEC->PJM
CLTF
0.004
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.462
LAGNLTFEXP_LAGN->PJM
CLTF
0.273
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.98

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:194.82 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:580.56
MW Contribution:
561.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
561.582
966021AG1-471 GEN
Solar/Wind Harmer
2.765
971485AH1-239 GEN
Solar/Wind Harmer
3.7
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.208
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.118
NYPJM->LTFIMP_NY
CLTF
0.016
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.025
TVALTFEXP_TVA->PJM
CLTF
0.13
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.027
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.144
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.45
LAGNLTFEXP_LAGN->PJM
CLTF
0.17
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.364

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:194.67 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:580.13
MW Contribution:
559.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
559.737
966021AG1-471 GEN
Solar/Wind Harmer
2.848
971485AH1-239 GEN
Solar/Wind Harmer
3.821
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.433
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.337
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.155
NYPJM->LTFIMP_NY
CLTF
0.017
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.035
TVALTFEXP_TVA->PJM
CLTF
0.161
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.146
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.455
LAGNLTFEXP_LAGN->PJM
CLTF
0.219
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.65

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1008_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:194.67 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:580.12
MW Contribution:
559.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
559.737
966021AG1-471 GEN
Solar/Wind Harmer
2.848
971485AH1-239 GEN
Solar/Wind Harmer
3.821
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.433
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.337
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.155
NYPJM->LTFIMP_NY
CLTF
0.017
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.035
TVALTFEXP_TVA->PJM
CLTF
0.161
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.146
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.455
LAGNLTFEXP_LAGN->PJM
CLTF
0.219
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.65

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:194.56 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:579.8
MW Contribution:
558.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
558.919
966021AG1-471 GEN
Solar/Wind Harmer
2.843
971485AH1-239 GEN
Solar/Wind Harmer
3.817
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.475
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.347
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.152
NYPJM->LTFIMP_NY
CLTF
0.017
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.033
TVALTFEXP_TVA->PJM
CLTF
0.163
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.143
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.443
LAGNLTFEXP_LAGN->PJM
CLTF
0.223
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.575

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:191.01 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:569.2
MW Contribution:
561.58
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
561.582

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1008_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:190.55 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:567.85
MW Contribution:
559.74
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
559.737

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:190.55 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:567.85
MW Contribution:
559.74
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
559.737

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:190.46 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:567.57
MW Contribution:
558.92
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
558.919

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:188.48 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:561.68
MW Contribution:
355.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
419.607
966021AG1-471 GEN
Solar/Wind Harmer
5.987
971485AH1-239 GEN
Solar/Wind Harmer
8.466
964901AG1-354 GEN
Solar/Wind Harmer
10.018
964781AG1-341 GEN
Solar/Wind Harmer
7.846
964781AG1-341 GEN
Solar/Wind Harmer
4.315
970653AG2-424 GEN
Solar/Wind Harmer
1.747
970653AG2-424 GEN
Solar/Wind Harmer
0.987
950011AG9-010
External Queue
7.131826877593994
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.885
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.294
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.563
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.811
NYPJM->LTFIMP_NY
CLTF
0.081
LGEELTFEXP_LGEE->PJM
CLTF
0.075
WECLTFEXP_WEC->PJM
CLTF
0.081
CPLELTFEXP_CPLE->PJM
CLTF
0.171
TVALTFEXP_TVA->PJM
CLTF
1.127
MECLTFEXP_MEC->PJM
CLTF
0.686
LAGNLTFEXP_LAGN->PJM
CLTF
1.809
SIGELTFEXP_SIGE->PJM
CLTF
0.025
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.985
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 419.61 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:188.47 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:561.64
MW Contribution:
354.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
418.878
966021AG1-471 GEN
Solar/Wind Harmer
5.967
971485AH1-239 GEN
Solar/Wind Harmer
8.437
964901AG1-354 GEN
Solar/Wind Harmer
9.989
964781AG1-341 GEN
Solar/Wind Harmer
7.822
964781AG1-341 GEN
Solar/Wind Harmer
4.302
970653AG2-424 GEN
Solar/Wind Harmer
1.742
970653AG2-424 GEN
Solar/Wind Harmer
0.985
950011AG9-010
External Queue
7.1139235496521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.868
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.201
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.788
NYPJM->LTFIMP_NY
CLTF
0.081
LGEELTFEXP_LGEE->PJM
CLTF
0.075
WECLTFEXP_WEC->PJM
CLTF
0.081
CPLELTFEXP_CPLE->PJM
CLTF
0.165
TVALTFEXP_TVA->PJM
CLTF
1.113
MECLTFEXP_MEC->PJM
CLTF
0.681
LAGNLTFEXP_LAGN->PJM
CLTF
1.789
SIGELTFEXP_SIGE->PJM
CLTF
0.024
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.888
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 418.88 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:188.47 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:561.64
MW Contribution:
354.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
418.878
966021AG1-471 GEN
Solar/Wind Harmer
5.967
971485AH1-239 GEN
Solar/Wind Harmer
8.437
964901AG1-354 GEN
Solar/Wind Harmer
9.989
964781AG1-341 GEN
Solar/Wind Harmer
7.822
964781AG1-341 GEN
Solar/Wind Harmer
4.302
970653AG2-424 GEN
Solar/Wind Harmer
1.742
970653AG2-424 GEN
Solar/Wind Harmer
0.985
950011AG9-010
External Queue
7.1139235496521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.868
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.201
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.788
NYPJM->LTFIMP_NY
CLTF
0.081
LGEELTFEXP_LGEE->PJM
CLTF
0.075
WECLTFEXP_WEC->PJM
CLTF
0.081
CPLELTFEXP_CPLE->PJM
CLTF
0.165
TVALTFEXP_TVA->PJM
CLTF
1.113
MECLTFEXP_MEC->PJM
CLTF
0.681
LAGNLTFEXP_LAGN->PJM
CLTF
1.789
SIGELTFEXP_SIGE->PJM
CLTF
0.024
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.888
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 418.88 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:188.46 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:561.62
MW Contribution:
354.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
418.878
966021AG1-471 GEN
Solar/Wind Harmer
5.967
971485AH1-239 GEN
Solar/Wind Harmer
8.437
964901AG1-354 GEN
Solar/Wind Harmer
9.989
964781AG1-341 GEN
Solar/Wind Harmer
7.822
964781AG1-341 GEN
Solar/Wind Harmer
4.302
970653AG2-424 GEN
Solar/Wind Harmer
1.742
970653AG2-424 GEN
Solar/Wind Harmer
0.985
950011AG9-010
External Queue
7.1139235496521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.868
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.201
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.788
NYPJM->LTFIMP_NY
CLTF
0.081
LGEELTFEXP_LGEE->PJM
CLTF
0.075
WECLTFEXP_WEC->PJM
CLTF
0.081
CPLELTFEXP_CPLE->PJM
CLTF
0.165
TVALTFEXP_TVA->PJM
CLTF
1.113
MECLTFEXP_MEC->PJM
CLTF
0.681
LAGNLTFEXP_LAGN->PJM
CLTF
1.789
SIGELTFEXP_SIGE->PJM
CLTF
0.024
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.888
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 418.88 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:188.26 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:561.0
MW Contribution:
355.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
419.235
966021AG1-471 GEN
Solar/Wind Harmer
5.977
971485AH1-239 GEN
Solar/Wind Harmer
8.452
964901AG1-354 GEN
Solar/Wind Harmer
10.005
964781AG1-341 GEN
Solar/Wind Harmer
7.834
964781AG1-341 GEN
Solar/Wind Harmer
4.309
970653AG2-424 GEN
Solar/Wind Harmer
1.745
970653AG2-424 GEN
Solar/Wind Harmer
0.986
950011AG9-010
External Queue
7.124643802642822
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.878
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.25
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.543
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.8
NYPJM->LTFIMP_NY
CLTF
0.081
LGEELTFEXP_LGEE->PJM
CLTF
0.075
WECLTFEXP_WEC->PJM
CLTF
0.081
CPLELTFEXP_CPLE->PJM
CLTF
0.168
TVALTFEXP_TVA->PJM
CLTF
1.12
MECLTFEXP_MEC->PJM
CLTF
0.684
LAGNLTFEXP_LAGN->PJM
CLTF
1.799
SIGELTFEXP_SIGE->PJM
CLTF
0.024
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.935
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 419.24 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:184.41 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:549.53
MW Contribution:
355.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
419.607
966021AG1-471 GEN
Solar/Wind Harmer
5.987
971485AH1-239 GEN
Solar/Wind Harmer
8.466
964901AG1-354 GEN
Solar/Wind Harmer
10.018
970653AG2-424 GEN
Solar/Wind Harmer
1.747
970653AG2-424 GEN
Solar/Wind Harmer
0.987
950011AG9-010
External Queue
7.131826877593994
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.885
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.294
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.563
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.811
NYPJM->LTFIMP_NY
CLTF
0.081
LGEELTFEXP_LGEE->PJM
CLTF
0.075
WECLTFEXP_WEC->PJM
CLTF
0.081
CPLELTFEXP_CPLE->PJM
CLTF
0.171
TVALTFEXP_TVA->PJM
CLTF
1.127
MECLTFEXP_MEC->PJM
CLTF
0.686
LAGNLTFEXP_LAGN->PJM
CLTF
1.809
SIGELTFEXP_SIGE->PJM
CLTF
0.025
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.985
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 419.61 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.86 %
Rating:249.0 MVA
Rating Type:A
MVA to Mitigate:447.86
MW Contribution:
308.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
363.804
966021AG1-471 GEN
Solar/Wind Harmer
5.107
971485AH1-239 GEN
Solar/Wind Harmer
7.218
964901AG1-354 GEN
Solar/Wind Harmer
8.559
970653AG2-424 GEN
Solar/Wind Harmer
1.476
970653AG2-424 GEN
Solar/Wind Harmer
0.834
950011AG9-010
External Queue
6.188554286956787
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.314
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.413
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.841
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.64
NYPJM->LTFIMP_NY
CLTF
0.059
LGEELTFEXP_LGEE->PJM
CLTF
0.004
WECLTFEXP_WEC->PJM
CLTF
0.064
CPLELTFEXP_CPLE->PJM
CLTF
0.137
TVALTFEXP_TVA->PJM
CLTF
0.915
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.022
MECLTFEXP_MEC->PJM
CLTF
0.549
LAGNLTFEXP_LAGN->PJM
CLTF
1.468
SIGELTFEXP_SIGE->PJM
CLTF
0.017
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.637
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 363.8 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOP-LAURD 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOP-LAURD 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:176.44 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:525.79
MW Contribution:
355.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
419.944
966021AG1-471 GEN
Solar/Wind Harmer
6
971485AH1-239 GEN
Solar/Wind Harmer
8.485
964901AG1-354 GEN
Solar/Wind Harmer
10.054
964781AG1-341 GEN
Solar/Wind Harmer
7.877
964781AG1-341 GEN
Solar/Wind Harmer
4.332
970653AG2-424 GEN
Solar/Wind Harmer
1.759
970653AG2-424 GEN
Solar/Wind Harmer
0.994
950011AG9-010
External Queue
7.131826877593994
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.81
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.709
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.927
NYPJM->LTFIMP_NY
CLTF
0.057
LGEELTFEXP_LGEE->PJM
CLTF
0.102
WECLTFEXP_WEC->PJM
CLTF
0.096
CPLELTFEXP_CPLE->PJM
CLTF
0.213
TVALTFEXP_TVA->PJM
CLTF
1.165
MECLTFEXP_MEC->PJM
CLTF
0.751
LAGNLTFEXP_LAGN->PJM
CLTF
1.887
SIGELTFEXP_SIGE->PJM
CLTF
0.027
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.985
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 419.94 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 1_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:172.9 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:515.25
MW Contribution:
421.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
498.298
966021AG1-471 GEN
Solar/Wind Harmer
3.631
971485AH1-239 GEN
Solar/Wind Harmer
4.945
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.619
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.775
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.251
NYPJM->LTFIMP_NY
CLTF
0.024
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.056
TVALTFEXP_TVA->PJM
CLTF
0.296
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.132
MECLTFEXP_MEC->PJM
CLTF
0.081
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.392
LAGNLTFEXP_LAGN->PJM
CLTF
0.44
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.223
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 498.3 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 1_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:167.24 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:498.38
MW Contribution:
421.76
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
498.298
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 498.3 MW.

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_PULASKI 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_PULASKI 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:165.51 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:493.23
MW Contribution:
351.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
415.093
966021AG1-471 GEN
Solar/Wind Harmer
5.521
971485AH1-239 GEN
Solar/Wind Harmer
7.704
964781AG1-341 GEN
Solar/Wind Harmer
6.097
964901AG1-354 GEN
Solar/Wind Harmer
5.663
964781AG1-341 GEN
Solar/Wind Harmer
3.353
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.729
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.943
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.88
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.941
NYPJM->LTFIMP_NY
CLTF
0.04
WECLTFEXP_WEC->PJM
CLTF
0.046
CPLELTFEXP_CPLE->PJM
CLTF
0.231
TVALTFEXP_TVA->PJM
CLTF
0.97
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.132
MECLTFEXP_MEC->PJM
CLTF
0.478
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.312
LAGNLTFEXP_LAGN->PJM
CLTF
1.52
SIGELTFEXP_SIGE->PJM
CLTF
0.007
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
8.963
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 415.09 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:164.09 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:489.0
MW Contribution:
354.93
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
418.878
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 418.88 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:163.96 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:488.6
MW Contribution:
355.55
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
419.607
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 419.61 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:163.96 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:488.6
MW Contribution:
355.55
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
419.607
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 419.61 MW.

Details for [AH1-721] 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:159.19 %
Rating:249.0 MVA
Rating Type:A
MVA to Mitigate:396.39
MW Contribution:
308.02
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
363.804
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 363.8 MW.

Details for 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:269.81 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:294.09
MW Contribution:
282.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
282.892
NYPJM->LTFIMP_NY
CLTF
0.001
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.079
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.055
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.545
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.1
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:269.81 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:294.09
MW Contribution:
282.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
282.892
NYPJM->LTFIMP_NY
CLTF
0.001
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.079
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.055
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.545
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.1
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:269.37 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:293.61
MW Contribution:
281.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
281.078
NYPJM->LTFIMP_NY
CLTF
0.002
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.081
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.056
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.529
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.015
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.081
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:269.07 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:293.29
MW Contribution:
282.89
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
282.892

Details for [AH1-721] 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:269.07 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:293.29
MW Contribution:
282.89
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
282.892

Details for [AH1-721] 5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5DENNY-2DENNY 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:268.66 %
Rating:109.0 MVA
Rating Type:B
MVA to Mitigate:292.84
MW Contribution:
281.08
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
281.078

Details for 5GREEN HAL T-5DELVINTA 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5GREEN HAL T-5DELVINTA 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:127.63 %
Rating:251.0 MVA
Rating Type:B
MVA to Mitigate:320.34
MW Contribution:
318.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
318.937
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.294
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.277
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.032
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.475
NYPJM->LTFIMP_NY
CLTF
0.024
LGEELTFEXP_LGEE->PJM
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.009
CPLELTFEXP_CPLE->PJM
CLTF
0.119
TVALTFEXP_TVA->PJM
CLTF
0.321
MECLTFEXP_MEC->PJM
CLTF
0.132
LAGNLTFEXP_LAGN->PJM
CLTF
0.491
SIGELTFEXP_SIGE->PJM
CLTF
0.005
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.877

Details for [AH1-721] 5GREEN HAL T-5DELVINTA 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5GREEN HAL T-5DELVINTA 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:124.8 %
Rating:251.0 MVA
Rating Type:B
MVA to Mitigate:313.25
MW Contribution:
318.94
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
318.937

Details for 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:220.92 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:335.8
MW Contribution:
306.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
306.951
NYPJM->LTFIMP_NY
CLTF
0.018
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.083
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.057
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.287
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.007
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.037
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:220.6 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:335.31
MW Contribution:
306.95
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
306.951

Details for 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.66 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:221.41
MW Contribution:
187.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
187.983
NYPJM->LTFIMP_NY
CLTF
0.017
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.033
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.058
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.6 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:221.32
MW Contribution:
187.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
187.747
NYPJM->LTFIMP_NY
CLTF
0.017
LGEELTFEXP_LGEE->PJM
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.05
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.034
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.058
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:145.6 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:221.32
MW Contribution:
187.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
187.747
NYPJM->LTFIMP_NY
CLTF
0.017
LGEELTFEXP_LGEE->PJM
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.05
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.034
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.058
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.56 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:221.25
MW Contribution:
187.98
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
187.983

Details for [AH1-721] 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.5 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:221.16
MW Contribution:
187.75
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
187.747

Details for [AH1-721] 5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-2LAUREL CO 161.0/69.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:145.5 %
Rating:152.0 MVA
Rating Type:B
MVA to Mitigate:221.16
MW Contribution:
187.75
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
187.747

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:246.07 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:492.15
MW Contribution:
451.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
451.432
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.835
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.475
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.255
NYPJM->LTFIMP_NY
CLTF
0.024
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.061
TVALTFEXP_TVA->PJM
CLTF
0.163
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.034
MECLTFEXP_MEC->PJM
CLTF
0.016
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.093
LAGNLTFEXP_LAGN->PJM
CLTF
0.232
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.601

Details for [AH1-721] 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:244.18 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:488.36
MW Contribution:
451.43
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
451.432

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:168.26 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:336.52
MW Contribution:
289.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
289.322
966021AG1-471 GEN
Solar/Wind Harmer
1.93
971485AH1-239 GEN
Solar/Wind Harmer
2.627
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.249
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.483
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.14
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.533
NYPJM->LTFIMP_NY
CLTF
0.022
WECLTFEXP_WEC->PJM
CLTF
0.007
CPLELTFEXP_CPLE->PJM
CLTF
0.136
TVALTFEXP_TVA->PJM
CLTF
0.374
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
MECLTFEXP_MEC->PJM
CLTF
0.139
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.05
LAGNLTFEXP_LAGN->PJM
CLTF
0.568
SIGELTFEXP_SIGE->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.02

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:168.03 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:336.06
MW Contribution:
287.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
287.745
966021AG1-471 GEN
Solar/Wind Harmer
1.919
971485AH1-239 GEN
Solar/Wind Harmer
2.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.287
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.546
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.156
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.527
NYPJM->LTFIMP_NY
CLTF
0.023
WECLTFEXP_WEC->PJM
CLTF
0.009
CPLELTFEXP_CPLE->PJM
CLTF
0.134
TVALTFEXP_TVA->PJM
CLTF
0.377
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.022
MECLTFEXP_MEC->PJM
CLTF
0.146
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.035
LAGNLTFEXP_LAGN->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.004
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.928

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:168.03 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:336.06
MW Contribution:
287.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
287.745
966021AG1-471 GEN
Solar/Wind Harmer
1.919
971485AH1-239 GEN
Solar/Wind Harmer
2.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.287
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.546
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.156
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.527
NYPJM->LTFIMP_NY
CLTF
0.023
WECLTFEXP_WEC->PJM
CLTF
0.009
CPLELTFEXP_CPLE->PJM
CLTF
0.134
TVALTFEXP_TVA->PJM
CLTF
0.377
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.022
MECLTFEXP_MEC->PJM
CLTF
0.146
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.035
LAGNLTFEXP_LAGN->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.004
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.928

Details for [AH1-721] 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:161.61 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:323.21
MW Contribution:
289.32
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
289.322

Details for [AH1-721] 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:161.38 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:322.76
MW Contribution:
287.75
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
287.745

Details for [AH1-721] 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:161.38 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:322.76
MW Contribution:
287.75
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
287.745

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:412.32 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:824.63
MW Contribution:
758.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
758.383
NYPJM->LTFIMP_NY
CLTF
0.041
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.043
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.026
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.193
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.042
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.13
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:412.08 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:824.16
MW Contribution:
758.38
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
758.383

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:281.56 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:563.12
MW Contribution:
477.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
477.305
966021AG1-471 GEN
Solar/Wind Harmer
2.827
971485AH1-239 GEN
Solar/Wind Harmer
3.833
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.093
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.03
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.92
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.285
NYPJM->LTFIMP_NY
CLTF
0.04
WECLTFEXP_WEC->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.058
TVALTFEXP_TVA->PJM
CLTF
0.303
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
MECLTFEXP_MEC->PJM
CLTF
0.11
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.048
LAGNLTFEXP_LAGN->PJM
CLTF
0.459
SIGELTFEXP_SIGE->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.428

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:281.23 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:562.46
MW Contribution:
475.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
475.492
966021AG1-471 GEN
Solar/Wind Harmer
2.805
971485AH1-239 GEN
Solar/Wind Harmer
3.809
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.133
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.088
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.932
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.274
NYPJM->LTFIMP_NY
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
0.055
TVALTFEXP_TVA->PJM
CLTF
0.305
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
MECLTFEXP_MEC->PJM
CLTF
0.116
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.029
LAGNLTFEXP_LAGN->PJM
CLTF
0.463
SIGELTFEXP_SIGE->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.293

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:281.23 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:562.46
MW Contribution:
475.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
475.492
966021AG1-471 GEN
Solar/Wind Harmer
2.805
971485AH1-239 GEN
Solar/Wind Harmer
3.809
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.133
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.088
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.932
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.274
NYPJM->LTFIMP_NY
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
0.055
TVALTFEXP_TVA->PJM
CLTF
0.305
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
MECLTFEXP_MEC->PJM
CLTF
0.116
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.029
LAGNLTFEXP_LAGN->PJM
CLTF
0.463
SIGELTFEXP_SIGE->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.293

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:274.83 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:549.66
MW Contribution:
477.31
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
477.305

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:274.55 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:549.1
MW Contribution:
475.49
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
475.492

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:274.55 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:549.1
MW Contribution:
475.49
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
475.492

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EXT_324130 5ALCALDE 161 324141 5ELIHU 161 1_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_324130 5ALCALDE 161 324141 5ELIHU 161 1_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.4 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:282.8
MW Contribution:
158.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
186.809
966021AG1-471 GEN
Solar/Wind Harmer
3.152
971485AH1-239 GEN
Solar/Wind Harmer
4.466
964901AG1-354 GEN
Solar/Wind Harmer
5.108
950011AG9-010
External Queue
3.442777633666992
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.689
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.531
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.13
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.505
NYPJM->LTFIMP_NY
CLTF
0.056
LGEELTFEXP_LGEE->PJM
CLTF
0.115
WECLTFEXP_WEC->PJM
CLTF
0.049
CPLELTFEXP_CPLE->PJM
CLTF
0.105
TVALTFEXP_TVA->PJM
CLTF
0.652
MECLTFEXP_MEC->PJM
CLTF
0.405
LAGNLTFEXP_LAGN->PJM
CLTF
1.049
SIGELTFEXP_SIGE->PJM
CLTF
0.017
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.524
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 186.81 MW.

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:130.02 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:260.03
MW Contribution:
143.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
168.349
966021AG1-471 GEN
Solar/Wind Harmer
2.506
971485AH1-239 GEN
Solar/Wind Harmer
3.548
964901AG1-354 GEN
Solar/Wind Harmer
4.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.418
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.636
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.78
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.416
NYPJM->LTFIMP_NY
CLTF
0.049
LGEELTFEXP_LGEE->PJM
CLTF
0.12
WECLTFEXP_WEC->PJM
CLTF
0.041
CPLELTFEXP_CPLE->PJM
CLTF
0.085
TVALTFEXP_TVA->PJM
CLTF
0.538
MECLTFEXP_MEC->PJM
CLTF
0.34
LAGNLTFEXP_LAGN->PJM
CLTF
0.867
SIGELTFEXP_SIGE->PJM
CLTF
0.016
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.718
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 168.35 MW.

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.29 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:258.57
MW Contribution:
141.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
166.773
966021AG1-471 GEN
Solar/Wind Harmer
2.504
971485AH1-239 GEN
Solar/Wind Harmer
3.547
964901AG1-354 GEN
Solar/Wind Harmer
4.17
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.425
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.649
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.784
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.417
NYPJM->LTFIMP_NY
CLTF
0.049
LGEELTFEXP_LGEE->PJM
CLTF
0.12
WECLTFEXP_WEC->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
0.085
TVALTFEXP_TVA->PJM
CLTF
0.539
MECLTFEXP_MEC->PJM
CLTF
0.341
LAGNLTFEXP_LAGN->PJM
CLTF
0.869
SIGELTFEXP_SIGE->PJM
CLTF
0.016
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.715
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 166.77 MW.

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:129.28 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:258.56
MW Contribution:
141.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
166.773
966021AG1-471 GEN
Solar/Wind Harmer
2.504
971485AH1-239 GEN
Solar/Wind Harmer
3.547
964901AG1-354 GEN
Solar/Wind Harmer
4.17
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.425
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.649
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.784
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.417
NYPJM->LTFIMP_NY
CLTF
0.049
LGEELTFEXP_LGEE->PJM
CLTF
0.12
WECLTFEXP_WEC->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
0.085
TVALTFEXP_TVA->PJM
CLTF
0.539
MECLTFEXP_MEC->PJM
CLTF
0.341
LAGNLTFEXP_LAGN->PJM
CLTF
0.869
SIGELTFEXP_SIGE->PJM
CLTF
0.016
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.715
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 166.77 MW.

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EXT_324130 5ALCALDE 161 324141 5ELIHU 161 1_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_324130 5ALCALDE 161 324141 5ELIHU 161 1_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.9 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:251.79
MW Contribution:
158.63
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
186.809
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 186.81 MW.

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:118.9 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:237.8
MW Contribution:
143.35
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
168.349
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 168.35 MW.

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.15 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:236.29
MW Contribution:
141.67
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
166.773
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 166.77 MW.

Details for [AH1-721] 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.15 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:236.29
MW Contribution:
141.67
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
166.773
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 166.77 MW.

Details for 5PITTSBURG-5TYNER 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5PITTSBURG-5TYNER 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:148.71 %
Rating:250.0 MVA
Rating Type:B
MVA to Mitigate:371.77
MW Contribution:
346.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
346.812
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.006
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.898
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.926
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.503
NYPJM->LTFIMP_NY
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.131
TVALTFEXP_TVA->PJM
CLTF
0.301
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.019
MECLTFEXP_MEC->PJM
CLTF
0.091
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.033
LAGNLTFEXP_LAGN->PJM
CLTF
0.45
SIGELTFEXP_SIGE->PJM
CLTF
0.002
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.342

Details for [AH1-721] 5PITTSBURG-5TYNER 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5PITTSBURG-5TYNER 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:146.02 %
Rating:250.0 MVA
Rating Type:B
MVA to Mitigate:365.04
MW Contribution:
346.81
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
346.812

Details for 5TYNER-5GREEN HAL T 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5TYNER-5GREEN HAL T 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:128.66 %
Rating:250.0 MVA
Rating Type:B
MVA to Mitigate:321.65
MW Contribution:
318.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
318.937
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.294
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.277
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.032
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.475
NYPJM->LTFIMP_NY
CLTF
0.024
LGEELTFEXP_LGEE->PJM
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.009
CPLELTFEXP_CPLE->PJM
CLTF
0.119
TVALTFEXP_TVA->PJM
CLTF
0.321
MECLTFEXP_MEC->PJM
CLTF
0.132
LAGNLTFEXP_LAGN->PJM
CLTF
0.491
SIGELTFEXP_SIGE->PJM
CLTF
0.005
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.877

Details for [AH1-721] 5TYNER-5GREEN HAL T 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5TYNER-5GREEN HAL T 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:125.82 %
Rating:250.0 MVA
Rating Type:B
MVA to Mitigate:314.55
MW Contribution:
318.94
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
318.937

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.88 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:413.87
MW Contribution:
372.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
372.99
966021AG1-471 GEN
Solar/Wind Harmer
1.752
971485AH1-239 GEN
Solar/Wind Harmer
2.335
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.394
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.266
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.112
NYPJM->LTFIMP_NY
CLTF
0.02
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.022
TVALTFEXP_TVA->PJM
CLTF
0.104
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
0.142
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.636

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:138.88 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:413.86
MW Contribution:
372.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
372.99
966021AG1-471 GEN
Solar/Wind Harmer
1.752
971485AH1-239 GEN
Solar/Wind Harmer
2.335
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.394
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.266
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.112
NYPJM->LTFIMP_NY
CLTF
0.02
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.022
TVALTFEXP_TVA->PJM
CLTF
0.104
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
0.142
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.636

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.88 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:413.85
MW Contribution:
372.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
372.99
966021AG1-471 GEN
Solar/Wind Harmer
1.752
971485AH1-239 GEN
Solar/Wind Harmer
2.335
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.394
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.266
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.112
NYPJM->LTFIMP_NY
CLTF
0.02
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.022
TVALTFEXP_TVA->PJM
CLTF
0.104
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
0.142
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.636

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.75 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:413.46
MW Contribution:
372.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
372.971
966021AG1-471 GEN
Solar/Wind Harmer
1.751
971485AH1-239 GEN
Solar/Wind Harmer
2.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.392
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.265
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.111
NYPJM->LTFIMP_NY
CLTF
0.02
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.022
TVALTFEXP_TVA->PJM
CLTF
0.104
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
0.142
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.633

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:138.75 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:413.46
MW Contribution:
372.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
372.971
966021AG1-471 GEN
Solar/Wind Harmer
1.751
971485AH1-239 GEN
Solar/Wind Harmer
2.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.392
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.265
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.111
NYPJM->LTFIMP_NY
CLTF
0.02
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.022
TVALTFEXP_TVA->PJM
CLTF
0.104
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
0.142
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.633

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:138.73 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:413.42
MW Contribution:
372.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
372.982
966021AG1-471 GEN
Solar/Wind Harmer
1.752
971485AH1-239 GEN
Solar/Wind Harmer
2.335
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.266
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.111
NYPJM->LTFIMP_NY
CLTF
0.02
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.022
TVALTFEXP_TVA->PJM
CLTF
0.104
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
0.142
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.635

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.54 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:406.88
MW Contribution:
372.99
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
372.99

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:136.53 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:406.87
MW Contribution:
372.99
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
372.99

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.53 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:406.87
MW Contribution:
372.99
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
372.99

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.4 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:406.48
MW Contribution:
372.97
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
372.971

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:136.4 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:406.48
MW Contribution:
372.97
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
372.971

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:136.39 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:406.43
MW Contribution:
372.98
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
372.982

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.4 %
Rating:267.0 MVA
Rating Type:A
MVA to Mitigate:332.13
MW Contribution:
326.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
326.679
NYPJM->LTFIMP_NY
CLTF
0.001
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.004
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.273
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.096
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.324
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.344

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.63 %
Rating:267.0 MVA
Rating Type:A
MVA to Mitigate:330.09
MW Contribution:
326.68
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
326.679

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.12 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:349.01
MW Contribution:
349.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
349.871
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.274
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.18
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.156
G-007ALTFEXP_G-007A->PJM
CMTX
0.021
VFTLTFEXP_VFT->PJM
CMTX
0.055
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.045
TVALTFEXP_TVA->PJM
CLTF
0.071
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
MECLTFEXP_MEC->PJM
CLTF
0.008
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.114
LAGNLTFEXP_LAGN->PJM
CLTF
0.101
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.3

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:116.32 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:346.62
MW Contribution:
349.87
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
349.871

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:248.98 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:522.85
MW Contribution:
522.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
522.825
339231AF1-038_GEN
Solar/Wind Helper
1.549
339206AE1-143 GEN
Solar/Wind Helper
2.08
339236AF1-050_GEN
Solar/Wind Helper
0.907
339241AF1-083 GEN
Solar/Wind Helper
0.994
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.13
G-007ALTFEXP_G-007A->PJM
CMTX
0.065
VFTLTFEXP_VFT->PJM
CMTX
0.175
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.032
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.93
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.178
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.639
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.979

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:244.89 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:514.27
MW Contribution:
522.83
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
522.825

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:181.36 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:380.86
MW Contribution:
345.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
345.222
966021AG1-471 GEN
Solar/Wind Harmer
1.621
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.365
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.246
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.103
NYPJM->LTFIMP_NY
CLTF
0.018
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.02
TVALTFEXP_TVA->PJM
CLTF
0.096
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.048
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.147
LAGNLTFEXP_LAGN->PJM
CLTF
0.132
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.514

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:181.36 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:380.86
MW Contribution:
345.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
345.222
966021AG1-471 GEN
Solar/Wind Harmer
1.621
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.365
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.246
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.103
NYPJM->LTFIMP_NY
CLTF
0.018
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.02
TVALTFEXP_TVA->PJM
CLTF
0.096
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.048
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.147
LAGNLTFEXP_LAGN->PJM
CLTF
0.132
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.514

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-3_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-3_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:181.36 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:380.85
MW Contribution:
345.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
345.222
966021AG1-471 GEN
Solar/Wind Harmer
1.621
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.365
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.246
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.103
NYPJM->LTFIMP_NY
CLTF
0.018
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.02
TVALTFEXP_TVA->PJM
CLTF
0.096
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.048
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.147
LAGNLTFEXP_LAGN->PJM
CLTF
0.132
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.514

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:181.19 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:380.49
MW Contribution:
345.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
345.204
966021AG1-471 GEN
Solar/Wind Harmer
1.621
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.363
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.245
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.103
NYPJM->LTFIMP_NY
CLTF
0.018
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.02
TVALTFEXP_TVA->PJM
CLTF
0.096
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.048
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.147
LAGNLTFEXP_LAGN->PJM
CLTF
0.131
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.512

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:181.19 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:380.49
MW Contribution:
345.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
345.204
966021AG1-471 GEN
Solar/Wind Harmer
1.621
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.363
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.245
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.103
NYPJM->LTFIMP_NY
CLTF
0.018
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.02
TVALTFEXP_TVA->PJM
CLTF
0.096
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.048
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.147
LAGNLTFEXP_LAGN->PJM
CLTF
0.131
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.512

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:181.17 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:380.45
MW Contribution:
345.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
345.214
966021AG1-471 GEN
Solar/Wind Harmer
1.621
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.364
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.246
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.103
NYPJM->LTFIMP_NY
CLTF
0.018
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.02
TVALTFEXP_TVA->PJM
CLTF
0.096
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.048
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.147
LAGNLTFEXP_LAGN->PJM
CLTF
0.131
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.513

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.31 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:376.55
MW Contribution:
345.22
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
345.222

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:179.31 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:376.55
MW Contribution:
345.22
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
345.222

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-3_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-3_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.31 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:376.54
MW Contribution:
345.22
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
345.222

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.14 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:376.19
MW Contribution:
345.2
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
345.204

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:179.14 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:376.19
MW Contribution:
345.2
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
345.204

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:179.11 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:376.14
MW Contribution:
345.21
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
345.214

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:165.26 %
Rating:186.0 MVA
Rating Type:A
MVA to Mitigate:307.38
MW Contribution:
302.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
302.358
NYPJM->LTFIMP_NY
CLTF
0.001
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.004
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.253
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.089
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.3
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.244

Details for [AH1-721] AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:164.24 %
Rating:186.0 MVA
Rating Type:A
MVA to Mitigate:305.49
MW Contribution:
302.36
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
302.358

Details for AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.57 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:295.2
MW Contribution:
282.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
282.892
NYPJM->LTFIMP_NY
CLTF
0.001
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.079
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.055
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.545
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.1
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:140.57 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:295.19
MW Contribution:
282.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
282.892
NYPJM->LTFIMP_NY
CLTF
0.001
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.079
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.055
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.545
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.1
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.27 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:294.57
MW Contribution:
281.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
281.078
NYPJM->LTFIMP_NY
CLTF
0.002
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.081
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.056
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.529
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.015
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.081
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AH1-721] AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.19 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:294.39
MW Contribution:
282.89
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
282.892

Details for [AH1-721] AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:140.19 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:294.39
MW Contribution:
282.89
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
282.892

Details for [AH1-721] AH1-721 TP-5DENNY 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5DENNY 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.91 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:293.81
MW Contribution:
281.08
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
281.078

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:254.67 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:758.9
MW Contribution:
758.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
758.951

Details for [AH1-721] AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1064_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1064_SRT-A
Contingency Type:Breaker
DC|AC:DC
Final Cycle Loading:254.67 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:758.9
MW Contribution:
758.95
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
758.951

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.08 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:497.9
MW Contribution:
477.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
477.872
966021AG1-471 GEN
Solar/Wind Harmer
2.849
971485AH1-239 GEN
Solar/Wind Harmer
3.865
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.015
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.034
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.899
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.165
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.48
G-007ALTFEXP_G-007A->PJM
CMTX
0.014
VFTLTFEXP_VFT->PJM
CMTX
0.038
LGEELTFEXP_LGEE->PJM
CLTF
0.024
WECLTFEXP_WEC->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
0.129
TVALTFEXP_TVA->PJM
CLTF
0.368
MECLTFEXP_MEC->PJM
CLTF
0.218
LAGNLTFEXP_LAGN->PJM
CLTF
0.589
SIGELTFEXP_SIGE->PJM
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.428

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.87 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:497.27
MW Contribution:
476.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
476.059
966021AG1-471 GEN
Solar/Wind Harmer
2.828
971485AH1-239 GEN
Solar/Wind Harmer
3.842
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.957
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.177
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.469
G-007ALTFEXP_G-007A->PJM
CMTX
0.01
VFTLTFEXP_VFT->PJM
CMTX
0.025
LGEELTFEXP_LGEE->PJM
CLTF
0.031
WECLTFEXP_WEC->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
0.125
TVALTFEXP_TVA->PJM
CLTF
0.37
MECLTFEXP_MEC->PJM
CLTF
0.224
LAGNLTFEXP_LAGN->PJM
CLTF
0.594
SIGELTFEXP_SIGE->PJM
CLTF
0.007
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.293

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:166.87 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:497.27
MW Contribution:
476.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
476.059
966021AG1-471 GEN
Solar/Wind Harmer
2.828
971485AH1-239 GEN
Solar/Wind Harmer
3.842
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.957
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.177
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.469
G-007ALTFEXP_G-007A->PJM
CMTX
0.01
VFTLTFEXP_VFT->PJM
CMTX
0.025
LGEELTFEXP_LGEE->PJM
CLTF
0.031
WECLTFEXP_WEC->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
0.125
TVALTFEXP_TVA->PJM
CLTF
0.37
MECLTFEXP_MEC->PJM
CLTF
0.224
LAGNLTFEXP_LAGN->PJM
CLTF
0.594
SIGELTFEXP_SIGE->PJM
CLTF
0.007
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.293

Details for [AH1-721] AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:161.66 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:481.75
MW Contribution:
477.87
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
477.872

Details for [AH1-721] AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:161.48 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:481.21
MW Contribution:
476.06
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
476.059

Details for [AH1-721] AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:161.48 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:481.21
MW Contribution:
476.06
IPD Plant:AH1-721
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
PJM_IPD
476.059
CONTINGENCY 'EKPC_P2-3_COOP S42-1064_SRT-A'
 OPEN BRANCH FROM BUS 341392 TO BUS 342727 CKT 1   /*2DENNY        69.0 - 5DENNY       161.0
 OPEN BUS 342718                                   /*5COOPER2     161.0
 OPEN BUS 342903                                   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-210G_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-2_COOPER 2 161_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1039_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342900   /*1COOPER1 G    13.8
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 2_SRT-A-2'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-ELIHU161_SRT-A'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P2-2_ELIHU-COOP 161_SRT-A'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 2_SRT-A-1'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 1   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EKPC_P1-2_COOP 161 TIE_SRT-A'
 OPEN BRANCH FROM BUS 342715 TO BUS 342718 CKT 1   /*5COOPER1     161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1014_SRT-A'
 OPEN BRANCH FROM BUS 342742 TO BUS 342745 CKT 1   /*5JABEZ       161.0 - 5JABEZ T     161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342751 CKT 1   /*5JABEZ T     161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342799 CKT 1   /*5JABEZ T     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342748 TO BUS 342751 CKT 1   /*5JAMESTOWN   161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342751 TO BUS 342796 CKT 1   /*5JAMESTOWN T 161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342793 TO BUS 342796 CKT 1   /*5RUSSEL CO   161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342796 TO BUS 360448 CKT 1   /*5RUSSEL CO J 161.0 - 5WOLF CRK HP 161.0
 OPEN BUS 342715                                   /*5COOPER1     161.0
 OPEN BUS 342900                                   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-2_COOPER 1 161_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1008_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
 OPEN BUS 342900   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1024_SRT-A'
 OPEN BRANCH FROM BUS 342115 TO BUS 342787 CKT 1   /*2PULASK CO    69.0 - 5PULASK CO   161.0
 OPEN BRANCH FROM BUS 342760 TO BUS 342790 CKT 1   /*5LIBERTY J   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342787 TO BUS 342790 CKT 1   /*5PULASK CO   161.0 - 5PULASK CO J 161.0
 OPEN BUS 342715                                   /*5COOPER1     161.0
 OPEN BUS 342900                                   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-2_LAUR-LAURD161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
 OPEN BUS 342754                                   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P7-1_LAURL 161 DBL_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P2-3_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 341740 TO BUS 342754 CKT 1   /*2LAUREL CO    69.0 - 5LAUREL CO   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P2-2_LAUREL CO 161_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P1-2_LAUR-L DAM161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P2-2_COOP-LAURD 161_SRT-A'
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 1_SRT-A'
 OPEN BRANCH FROM BUS 342115 TO BUS 342787 CKT 1   /*2PULASK CO    69.0 - 5PULASK CO   161.0
 OPEN BRANCH FROM BUS 342715 TO BUS 342790 CKT 1   /*5COOPER1     161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342715 TO BUS 342799 CKT 1   /*5COOPER1     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342742 TO BUS 342745 CKT 1   /*5JABEZ       161.0 - 5JABEZ T     161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342751 CKT 1   /*5JABEZ T     161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342799 CKT 1   /*5JABEZ T     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342748 TO BUS 342751 CKT 1   /*5JAMESTOWN   161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342751 TO BUS 342796 CKT 1   /*5JAMESTOWN T 161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342760 TO BUS 342790 CKT 1   /*5LIBERTY J   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342787 TO BUS 342790 CKT 1   /*5PULASK CO   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342793 TO BUS 342796 CKT 1   /*5RUSSEL CO   161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342796 TO BUS 360448 CKT 1   /*5RUSSEL CO J 161.0 - 5WOLF CRK HP 161.0
END
CONTINGENCY 'EKPC_P2-2_PULASKI 161_SRT-A'
 OPEN BUS 342787   /*5PULASK CO   161.0
 OPEN BUS 342790   /*5PULASK CO J 161.0
END
CONTINGENCY 'EXT_324130 5ALCALDE 161 324141 5ELIHU 161 1_SRT-L'
 OPEN BRANCH FROM BUS 324130 TO BUS 324141 CKT 1   /*5ALCALDE     161.0 - 5ELIHU       161.0
END
341038 to 341755 ckt 1
341206 to 341347 ckt 1
341347 to 341344 ckt 1
341344 to 342286 ckt 1
341344 to 342286 ckt 2
341392 to 341206 ckt 1
341392 to 341578 ckt 1
341392 to 342499 ckt 1
324531 to 342287 ckt 1
341722 to 342187 ckt 1
341740 to 324576 ckt 1
341740 to 341722 ckt 1
341755 to 324527 ckt 1
342187 to 341038 ckt 1
342287 to 324531 ckt 1
342286 to 342287 ckt 1
342451 to 342452 ckt 1
342490 to 341845 ckt 1
342715 to 341344 ckt 1
342718 to 342715 ckt 1
342718 to 324141 ckt 1
342727 to 341392 ckt 1
342736 to 324138 ckt 1
342754 to 341740 ckt 1
342754 to 342781 ckt 1
342757 to 342754 ckt 1
342781 to 342820 ckt 1
342820 to 342736 ckt 1
972272 to 342718 ckt 1
972272 to 342718 ckt 2
972272 to 342727 ckt 1
972272 to 342757 ckt 1

Short Circuit Analysis

Short Circuit Analysis is complete and requires a cost allocation for this project. This project has been flagged as having a potential impact on the breakers at the Cooper substation, which exceeds the >1% threshold per PJM Manual 14H 4.2.3.1.

Reinforcements and duty impact analysis for TC2 Phase II is as following: 

Bus Name

Bus Number

Project ID

Breaker Overdutied

Breaker Capacity (Amps)

Duty Percent With TC2 (%)

Duty Amps With TC2 (Amps)

Full Amps Contribution (Amps)

Reinforcement ID

Reinforcement Project Description

COOPER 161. kV

 

 

 

 

 

 

 

 

342715

 

 

 

 

 

 

 

 

AH1-721

 

 

 

 

 

 

 

 

1064 DENNY

31500

137.36%

43269.2

20139.4

n9687.1

Cooper 161KV Breaker Replacement. Replace Breaker 1064 DENNY with 63kA Breaker.

1008 XFMR

40000

108.17%

43269.2

20139.4

n9687.2

Cooper 161KV Breaker Replacement. Replace Breaker 1008 XFMR with 63kA Breaker.

1014 WOLF CR

40000

108.17%

43269.2

20139.4

n9687.3

Cooper 161KV Breaker Replacement. Replace Breaker 1014 WOLF CR with 63kA Breaker.

1039 BUS

40000

108.17%

43269.2

20139.4

n9687.4

Cooper 161KV Breaker Replacement. Replace Breaker 1039 BUS with 63kA Breaker.

1054 LAUREL

40000

108.17%

43269.2

20139.4

n9687.5

Cooper 161KV Breaker Replacement. Replace Breaker 1054 LAUREL with 63kA Breaker.

1079 TRANSFR

40000

108.17%

43269.2

20139.4

n9687.6

Cooper 161KV Breaker Replacement. Replace Breaker 1079 TRANSFR with 63kA Breaker.

110G UNIT 1

40000

108.17%

43269.2

20139.4

n9687.7

Cooper 161KV Breaker Replacement. Replace Breaker 110G UNIT 1 with 63kA Breaker.

210G UNIT 2

40000

108.17%

43269.2

20139.4

n9687.8

Cooper 161KV Breaker Replacement. Replace Breaker 210G UNIT 2 with 63kA Breaker

1024 LIBERTY

39527.9

102.15%

40376.2

19487.5

n9687.9

Cooper 161KV Breaker Replacement. Replace Breaker 1024 LIBERTY with 63kA Breaker.

 

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests (projects) in PJM Transition Cycle 2, Cluster 79 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 79 projects.

This analysis is effectively a screening study to determine whether the addition of the Cluster 79 projects will meet the dynamics requirements of the NERC, EKPC and PJM reliability standards.

The load flow scenario for the analysis was based on the RTEP 2028 summer peak load and light load cases, modified to include applicable projects. Cluster 79 projects have been dispatched online at maximum power output and the voltage schedule set to achieve near unity power factor at the high side of the main transformer.

Cluster 79 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 245 contingencies were studied, each with a 20 second simulation time period. Studied faults included:

       a)       Steady-state operation;

       b)       Three-phase faults with normal clearing time;

       c)       Single-phase to ground bus faults with normal clearing time;

       d)       Single-phase to ground faults with delayed clearing due to a stuck breaker;

       e)       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure;

       f)       Single-phase faults with loss of multiple-circuit tower line.

       g)       Three-phase faults with normal clearing time and a failed high speed reclose attempt.

 

For all simulations, the Cluster 79 projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all of the fault contingencies tested on the 2028 summer peak load and light load cases:

       a)       Cluster 79 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with Cluster 79 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3%.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

AG2-424 meets the 0.95 leading and lagging PF requirement.

 

AH1-721 meets the 0.95 leading and 0.90 lagging PF requirement.

 

No mitigations were found to be required.

 

Table 1: TC2 Cluster 79 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

79

AG2-424

Solar

Storage

EKPC

63.25

63.25

34.95

Mognolia Summersville Tap 69 kV

AH1-721

Natural Gas

EKPC

786

786

758.9507

Laurel River Dam Cooper 161 kV

 

Reactive Power Analysis

The reactive power capability of AH1-721 meets the 0.95 leading and 0.90 lagging power factor at the generator terminals.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-150Grassy Falls 138kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-001Delano 138kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVPartially in Service - Under Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-101Johns Creek-Excel 138kV IEngineering & Procurement
AC1-102Johns Creek-Excel 138kV IIEngineering & Procurement
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVEngineering & Procurement
AC1-214Crescent RidgeIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-029Circleville 138kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-123Jacksons Ferry 138kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AC2-176Jay 138 kVIn Service
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVWithdrawn
AD1-128Modoc-Delaware 138 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-134Shady OaksPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVWithdrawn
AE1-040Greenfield 69 kVIn Service
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-143Marion County 161 kVUnder Construction
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterWithdrawn
AE1-175Light Foot 34.5 kVIn Service
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE2-005Harmony Village-Shackleford 115 kVSuspended
AE2-027Harrowgate-Locks 115kVSuspended
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-089Pennville-Adams 138 kVSuspended
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVEngineering & Procurement
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVUnder Construction
AE2-261Kincaid-Pana 345 kVEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-305Givens-Mechanicsburg 138 kVWithdrawn
AE2-308Three Forks-Dale 138 kVEngineering & Procurement
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVUnder Construction
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AE2-342Woodstock 69 kVSuspended
AF1-014Harmony Village-Shackleford 115 kVSuspended
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-038Sewellton Jct-Webbs Crossroads 69 kVUnder Construction
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-053Givens-Mechanicsburg 138 kVWithdrawn
AF1-054Givens-Mechanicsburg 138 kVWithdrawn
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-090Kincaid-PanaEngineering & Procurement
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVWithdrawn
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-147Poland Rd-Runway DP 230kVPartially in Service - Under Construction
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-228Beatty-Greene 345 kVUnder Construction
AF1-233Flemingsburg – Spurlock 138kVEngineering & Procurement
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVUnder Construction
AF1-331Twombley RoadEngineering & Procurement
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVWithdrawn
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-068Jay 138 kVEngineering & Procurement
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-085Midlothian 34.5 kVIn Service
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVEngineering & Procurement
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-177Sorenson-DeSoto #2 345 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-382Hurley 69 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVUnder Construction
AG1-017Jay 138 kVIn Service
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVUnder Construction
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-145Lightfoot 34.5 kVIn Service
AG1-152Remington CT 230 kVEngineering & Procurement
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Hodgenville-Stephensburg 69 kVEngineering & Procurement
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-460Kincaid-Pana 345 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-471Up Church-Wayne County 69 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-508Point Lookout 69 kVWithdrawn
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
AG2-061Dana 345 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Avon - Renaker 138 kVActive
AG2-088Midlothian 230 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-230Dumont 345 kVActive
AG2-240Old Church 34.5 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-272Berry Hill 138 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-401Losantville 345 kVActive
AG2-424Summersville - Magnolia 69 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-518Tech Drive 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run - Sundial 138 kVActive
AG2-585Kensignton 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-675Cordova 345 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Silver Lake - Cherry Valley 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-263Chancellor 115 kVActive
AH1-269Claytor 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-338New Sub S2354 138kVActive
AH1-341ESS-H445 3B 138kvActive
AH1-348Pound 34.5 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-461Buckhorn 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry - Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Millersburg 69 kVActive
AH1-571Millersburg 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-073Yankee 12.5kVIn Service
W2-048Brokaw-LanesvilleIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
Y1-049Wurno 34.5kVIn Service
Y3-024Bluff Point 12kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)Identified Impacts
AH1-721 System Reinforcements:
TOTrans Owner IDTitleAllocated Cost ($USD)
LGEETC2-LGEE-0003Replacing all terminal equipment at Elihu$985,560
LGEELGEE_TC1_15526Invalid - P2 contingency 69kV not monitored$0
LGEETC2-LGEE-0008Invalid - P2 contingency 69 kV not monitored$0
LGEETC2-LGEE-0006Invalid - P2 contingency 69 kV not monitored$0
LGEETC2-LGEE-0007Invalid - P2 contingency 69 kV not monitored$0
LGEETC2-LGEE-0012Invalid - P2 contingency 69 kV not monitored$0
LGEETC2-LGEE-0013Invalid - common mode contingency over 69 kV addressed by load shedding or generation redispatch$0
LGEETC2-LGEE-0015Invalid - common mode contingency over 69 kV addressed by load shedding or generation redispatch$0
Grand Total:$985,560

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / TC2-LGEE-0003
Title
Replacing all terminal equipment at Elihu
Description
Replacing all terminal equipment at Elihu LG&E/KU rating is 219/277 MVA SP & 335/368 MVA WP, flow would require replacement of all terminal equipment at Elihu. $1,000,000 24months
Total Cost ($USD)
$1,000,000
Allocated Cost ($USD)
$985,560
Time Estimate
0 to 24 Months

Contributor

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-239
8.5 MW1.4%$14,440
AH1-721
577.8 MW98.6%$985,560

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15526
Title
Invalid - P2 contingency 69kV not monitored
Description
Per the LG&E/KU Planning Guidelines, 69kV is not monitored for P2 contingencies.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / TC2-LGEE-0008
Title
Invalid - P2 contingency 69 kV not monitored
Description
Per LG&E/KU: LG&E/KU does not monitor the 69kV for this NERC Cont Cat
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2FARLEY KU-2LIBER CH T 69.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / TC2-LGEE-0006
Title
Invalid - P2 contingency 69 kV not monitored
Description
Per LG&E/KU: LG&E/KU does not monitor the 69kV for this NERC Cont Cat
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending)
Title
Replace 0.83 miles of 556 ACSR conductor in the Ferguson South to Somerset KU section of the Elihu to Somerset EKPC 69 kV line with 795 ACSR.
Description
Replace 0.83 miles of 556 ACSR conductor in the Ferguson South to Somerset KU section of the Elihu to Somerset EKPC 69 kV line with 795 ACSR.
Total Cost ($USD)
$2,335,038
Allocated Cost ($USD)
$0
Time Estimate
0 to 6 Months

Info

Note: AH1-721 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15519
Title
Invalid - P7 contingency 69kV not monitored by LGEE
Description
Invalid - P7 contingency 69kV not monitored by LGEE EKPC emergency rating is 143 MVA on the Somerset KU - Ferguston 69kV line.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line(Any)
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / TC2-LGEE-0007
Title
Invalid - P2 contingency 69 kV not monitored
Description
Per LG&E/KU: LG&E/KU does not monitor the 69kV for this NERC Cont Cat
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2HOPEWELL-2LAUREL CO 69.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / TC2-LGEE-0012
Title
Invalid - P2 contingency 69 kV not monitored
Description
Per LG&E/KU: LG&E/KU does not monitor the 69kV for this NERC Cont Cat
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2PITTSBRG KU-5PITTSBURG 69.0/161.0 kV Ckt 1 transformer(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / TC2-LGEE-0013
Title
Invalid - common mode contingency over 69 kV addressed by load shedding or generation redispatch
Description
LG&E/KU planning guidelines permit redispatch of generation or 5% load shedding to resolve overload for the contingency category
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
4LEBANON-4MARION CO 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / TC2-LGEE-0015
Title
Invalid - common mode contingency over 69 kV addressed by load shedding or generation redispatch
Description
LG&E/KU planning guidelines permit redispatch of generation or 5% load shedding to resolve overload for the contingency category
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5DELVINTA-5GREEN HAL T 161.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15524
Title
Load shedding of 10% PC load is allowed for P7 contingency
Description
Load shedding of 10% PC load is allowed for P7 contingency
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15525
Title
Load shedding of 10% PC load is allowed for P4 contingency
Description
Load shedding of 10% PC load is allowed for P4 contingency
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending)
Title
Load shedding of 10% PC load is allowed for P2 contingency
Description
Load shedding of 10% PC load is allowed for P2 contingency
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending)
Title
LGEE Summer 219/277 MVA & winter 335/335 MVA Rate A/Rate B
Description
LGEE Summer 219/277 MVA & winter 335/335 MVA Rate A/Rate B
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)No Impact
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Louisville Gas & Electric (LG&E)Study Pending
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AH1-721 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
EKPCn9743.0Cooper CCGT-Alcalde 161 kV Double-Circuit Line AdditionCost Allocated$19,567,493N/A
EKPCn8368.2Rebuild the Cooper-Elihu 161 kV line section using 1272 MCM ACSS conductor (4.2 miles)Cost Allocated$10,185,767N/A
AEPn9769.005CLOVRD_RJA 765.0 kV to 05CLOVRD 765.0 kV ckt Z1 - Upgrade/replace CBsCost Allocated$9,623,735N/A
OVECn9759.006KYGER 345.0 kV to 05SPORN 345.0 kV ckt 1 - Replace EquipmentCost Allocated$6,419,242N/A
AEPn9765.005CLNCHR 138.0 kV to 05LEBANO 138.0 kV ckt 1 - Rebuild Entrance SpanCost Allocated$1,284,708N/A
AEPn9764.005ELKGARDNSS 138.0 kV to 05SALTV1 138.0 kV ckt 1 - Reconductor entrance spanCost Allocated$1,284,708N/A
EKPCn9775.0Cooper-AH1-721 Tap (East Cooper) 161 kV Circuit #2 Rebuild (0.5 miles)Cost Allocated$1,215,000N/A
EKPCn9776.0Cooper-AH1-721 Tap (East Cooper) 161 kV Circuit #1 Rebuild (0.5 miles)Cost Allocated$1,215,000N/A
AEPn9771.005LEBANO 138.0 kV to 05ELKGARDNSS 138.0 kV ckt 1 - Rebuild/Reconductor Entrance SpanCost Allocated$1,014,628N/A
EKPCn7771.2Increase the maximum operating temperature of the Laurel County-Laurel Dam 161 kV line section 795 MCM conductor to 212 degrees F (~10.55 miles)Cost Allocated$1,002,320N/A
EKPCn9781.0Cooper-Elihu 161 kV Bus Conductor UpgradeCost Allocated$975,705N/A
EKPCn6834.1Rebuild the 4/0 ACSR Green County-Summersville 69 kV line section (4.2 miles) using 556 MCM ACSR.Cost Allocated$898,387N/A
AEPn9763.005J.FERR 765.0 kV to 05CLOVRD_RJA 765.0 kV ckt 1 - Replace WavetrapsCost Allocated$871,818N/A
AEPn9753.005KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag StudyCost Allocated$849,398N/A
EKPCn9688.0AH1-239 Tap (Clinton County)-Homestead New 69 kV Line (15 miles)Cost Allocated$508,152N/A
EKPCn7773.1Change the 69 kV current transformer settings associated with circuit breaker S7-654 from 600A to at least 800A.Cost Allocated$345,000N/A
EKPCn9687.1Cooper 161kV breaker replacements - Breaker 1064 DENNYCost Allocated$335,000N/A
EKPCn9687.2Cooper 161kV breaker replacements - Breaker 1008 XFMRCost Allocated$335,000N/A
EKPCn9687.3Cooper 161kV breaker replacements - Breaker 1014 WOLF CRCost Allocated$335,000N/A
EKPCn9687.4Cooper 161kV breaker replacements - Breaker 1039 BUSCost Allocated$335,000N/A
EKPCn9687.5Cooper 161kV breaker replacement - Breaker 1054 LAURELCost Allocated$335,000N/A
EKPCn9687.6Cooper 161kV breaker replacements - Breaker 1079 TRANSFCost Allocated$335,000N/A
EKPCn9687.7Cooper 161kV breaker replacements - Breaker 110G UNIT 1Cost Allocated$335,000N/A
EKPCn9687.8Cooper 161kV breaker replacements - Breaker 210G UNIT 2Cost Allocated$335,000N/A
EKPCn9687.9Cooper 161kV breaker replacements - Breaker 1024 LIBERTYCost Allocated$335,000N/A
EKPCn9687.10Cooper 161kV breaker replacements - Breaker 1044 ELIHUCost Allocated$330,163N/A
EKPCn9782.0West London Tap-West London 69 kV Conductor Maximum Operating Temperature IncreaseCost Allocated$135,000N/A
EKPCn9742.0Zula Junction N.O.-AG1-471 (Massingale Road) 69 kV Line Section Rebuild (0.6 miles)Cost Allocated$61,197N/A
EKPCn9780.0Cooper-Elihu 161 kV Relay UpgradeCost Allocated$54,206N/A
EKPCn7771.1Increase the maximum operating temperature of the Laurel County-Laurel Dam 161 kV line section 795 MCM conductor to 167 degrees F (~0.2 miles)Cost Allocated$34,734N/A
EKPCn8368.4Upgrade the existing 795 MCM ACSR jumpers at the Cooper substation associated with the Cooper-Elihu 161 kV line using bundled 500 MCM CU or equivalentCost Allocated$34,495N/A
EKPCn9778.0Increase the Zone 3 relay setting at Somerset substation associated with the Somerset-KU Ferguson South 69 kV line section to at least 205 MVA.Cost Allocated$10,000N/A
EKPCn9777.0Cooper-AH1-721 (East Cooper) Circuit #2 161 kV Zone 3 Setting UpgradeCost Allocated$10,000N/A
EKPCn8368.3Change the Zone 3 relay setting at Elihu substation associated with the line protection to at least 545 MVA LTE rating.Cost Allocated$9,856N/A
APSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardContingent$0N/A
APSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Contingent$0N/A
APSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Contingent$0N/A
APSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationContingent$0N/A
APSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Contingent$0N/A
AEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Contingent$0N/A
AEPb4068.1b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570Contingent$0N/A
AEPb3919.1Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yardContingent$0N/A
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0N/A
AEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0N/A
Dominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Contingent$0N/A
Dominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Contingent$0N/A
Dominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Contingent$0N/A
Dominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Contingent$0N/A
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0N/A
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0N/A
Dominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
AEPb4000.252Replace the wave trap and upgrade the relay at Joshua Falls 765kV substationContingent$0N/A
AEPb4000.251Replace the wave trap and upgrade the relay at Cloverdale 765kV substationContingent$0N/A
AEPs2572.3Rebuild ~21 miles of the 138KV line between Saltville and Tazewell stationsContingent$0N/A
OVECb3788.2Replace limiting station elements at Kyger CreekContingent$0N/A
AEPb3788.1Replace limiting station elements at Kyger CreekContingent$0N/A
Dominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Contingent$0N/A
Dominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Contingent$0N/A
Dominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Contingent$0N/A
EKPCn7773.4Replace the 1200A disconnects S7-653 and S7-655 at Somerset substation with 2000A equipment.Contingent$0N/A
EKPCn8368.5Cooper-Elihu 161 kV Current Transformer UpgradeContingent$0N/A
Grand Total:$60,955,712

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9688.0
Type
Stability
TO
EKPC
RTEP ID / TO ID
n9688.0 / EKPC-tc2-nu049
Title
AH1-239 Tap (Clinton County)-Homestead New 69 kV Line (15 miles)
Description
Construct approximately 15 miles of new 69 kV line from the AH1-239 POI substation (Clinton County) to the EKPC Homestead substation using 556.5 MCM ACSR conductor.
Total Cost ($USD)
$16,300,000
Discounted Total Cost ($USD)
$16,300,000
Allocated Cost ($USD)
$508,152
Time Estimate
Dec 31 2028

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

FacilityContingency
2UPCHURCH T-AH1-239 TP 69.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-239320.0 MW96.9%$15,791,848
AH1-72110.3 MW3.1%$508,152

System Reinforcement: n9687.1
Type
Short Circuit
TO
EKPC
RTEP ID / TO ID
n9687.1
Title
Cooper 161kV breaker replacements - Breaker 1064 DENNY
Description
Cooper 161kV breaker replacements - Breaker 1064 DENNY - replace with 63kA breaker
Total Cost ($USD)
$335,000
Discounted Total Cost ($USD)
$335,000
Allocated Cost ($USD)
$335,000
Time Estimate
Dec 01 2029

Contributor

Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AH1-721100.00%$335,000

System Reinforcement: n9687.2
Type
Short Circuit
TO
EKPC
RTEP ID / TO ID
n9687.2
Title
Cooper 161kV breaker replacements - Breaker 1008 XFMR
Description
Cooper 161kV breaker replacements - Breaker 1008 XFMR - replace with 63kA breaker
Total Cost ($USD)
$335,000
Discounted Total Cost ($USD)
$335,000
Allocated Cost ($USD)
$335,000
Time Estimate
Dec 01 2029

Contributor

Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AH1-721100.00%$335,000

System Reinforcement: n9687.3
Type
Short Circuit
TO
EKPC
RTEP ID / TO ID
n9687.3
Title
Cooper 161kV breaker replacements - Breaker 1014 WOLF CR
Description
Cooper 161kV breaker replacements - Breaker 1014 WOLF CR - replace with 63kA breaker
Total Cost ($USD)
$335,000
Discounted Total Cost ($USD)
$335,000
Allocated Cost ($USD)
$335,000
Time Estimate
Dec 01 2029

Contributor

Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AH1-721100.00%$335,000

System Reinforcement: n9687.4
Type
Short Circuit
TO
EKPC
RTEP ID / TO ID
n9687.4
Title
Cooper 161kV breaker replacements - Breaker 1039 BUS
Description
Cooper 161kV breaker replacements - Breaker 1039 BUS - replace with 63kA breaker
Total Cost ($USD)
$335,000
Discounted Total Cost ($USD)
$335,000
Allocated Cost ($USD)
$335,000
Time Estimate
Dec 01 2029

Contributor

Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AH1-721100.00%$335,000

System Reinforcement: n9687.5
Type
Short Circuit
TO
EKPC
RTEP ID / TO ID
n9687.5
Title
Cooper 161kV breaker replacement - Breaker 1054 LAUREL
Description
Cooper 161kV breaker replacements - Breaker 1054 LAUREL - replace with 63kA break
Total Cost ($USD)
$335,000
Discounted Total Cost ($USD)
$335,000
Allocated Cost ($USD)
$335,000
Time Estimate
Dec 01 2029

Contributor

Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AH1-721100.00%$335,000

System Reinforcement: n9687.6
Type
Short Circuit
TO
EKPC
RTEP ID / TO ID
n9687.6
Title
Cooper 161kV breaker replacements - Breaker 1079 TRANSF
Description
Cooper 161kV breaker replacements - 1079 TRANSFR - replace with 63kA breaker
Total Cost ($USD)
$335,000
Discounted Total Cost ($USD)
$335,000
Allocated Cost ($USD)
$335,000
Time Estimate
Dec 01 2029

Contributor

Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AH1-721100.00%$335,000

System Reinforcement: n9687.7
Type
Short Circuit
TO
EKPC
RTEP ID / TO ID
n9687.7
Title
Cooper 161kV breaker replacements - Breaker 110G UNIT 1
Description
Cooper 161kV breaker replacements - Breaker 110G UNIT 1 - replace with 63kA breaker
Total Cost ($USD)
$335,000
Discounted Total Cost ($USD)
$335,000
Allocated Cost ($USD)
$335,000
Time Estimate
Dec 01 2029

Contributor

Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AH1-721100.00%$335,000

System Reinforcement: n9687.8
Type
Short Circuit
TO
EKPC
RTEP ID / TO ID
n9687.8
Title
Cooper 161kV breaker replacements - Breaker 210G UNIT 2
Description
Cooper 161kV breaker replacements - Breaker 210G UNIT 2 - replace with 63kA breaker
Total Cost ($USD)
$335,000
Discounted Total Cost ($USD)
$335,000
Allocated Cost ($USD)
$335,000
Time Estimate
Dec 01 2029

Contributor

Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AH1-721100.00%$335,000

System Reinforcement: n9687.9
Type
Short Circuit
TO
EKPC
RTEP ID / TO ID
n9687.9
Title
Cooper 161kV breaker replacements - Breaker 1024 LIBERTY
Description
Cooper 161kV breaker replacements - Breaker 1024 LIBERTY - replace with 63kA breaker
Total Cost ($USD)
$335,000
Discounted Total Cost ($USD)
$335,000
Allocated Cost ($USD)
$335,000
Time Estimate
Dec 01 2029

Contributor

Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AH1-721100.00%$335,000

System Reinforcement: n9743.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9743.0 / EKPC-tc2-nu003
Title
Cooper CCGT-Alcalde 161 kV Double-Circuit Line Addition
Description
Construct a new double-circuit 161 kV line between EKPC's new Cooper CCGT substation and the LG&E/KU Alcalde substation (approximate length of 5 miles) using 1272 MCM ACSS conductor.
Total Cost ($USD)
$20,130,000
Discounted Total Cost ($USD)
$20,130,000
Allocated Cost ($USD)
$19,567,493
Time Estimate
22 to 36 Months

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

FacilityContingency
(Any)EKPC_P2-3_COOP S42-210G_SRT-A
No new ratings for this Flowgate.
(Any)EKPC_P2-3_COOP S42-1064_SRT-A
No new ratings for this Flowgate.
(Any)EKPC_P2-2_ELIHU-COOP 161_SRT-A
No new ratings for this Flowgate.
(Any)EKPC_P2-2_COOPER 2 161_SRT-A
No new ratings for this Flowgate.
(Any)EKPC_P7-1_COOP 161 DBL 1_SRT-A
No new ratings for this Flowgate.
(Any)EKPC_P2-3_COOP S42-1014_SRT-A
No new ratings for this Flowgate.
(Any)EKPC_P2-3_COOP S42-1039_SRT-A
No new ratings for this Flowgate.
(Any)EKPC_P2-3_COOP S42-1008_SRT-A
No new ratings for this Flowgate.
(Any)EKPC_P2-2_COOPER 1 161_SRT-A
No new ratings for this Flowgate.
(Any)EKPC_P2-3_COOP S42-1024_SRT-A
No new ratings for this Flowgate.
(Any)EKPC_P1-2_COOP-LAUREL161_SRT-A-1
No new ratings for this Flowgate.
(Any)EKPC_P1-2_COOP 161 TIE_SRT-A
No new ratings for this Flowgate.
(Any)EKPC_P1-2_COOP-ELIHU161_SRT-A
No new ratings for this Flowgate.
(Any)EKPC_P1-2_COOP-DEN161_SRT-A-1
No new ratings for this Flowgate.
(Any)EKPC_P2-2_COOP-LAURD 161_SRT-A
No new ratings for this Flowgate.
(Any)EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
No new ratings for this Flowgate.
(Any)EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
No new ratings for this Flowgate.
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 lineEKPC_P2-3_SSHAD S11-1044_SRT-A
No new ratings for this Flowgate.
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
5LAUREL CO-5LAUREL DAM 161.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-254 POI-2GARRARD CO 69.0 kV Ckt 1 lineEKPC_P2-3_MAR W38-1004_SRT-A
No new ratings for this Flowgate.
2MARETBURG T-2WALNUT GROV 69.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
5COOPER1-5COOPER2 161.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
5COOPER2-AH1-721 TP 161.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
5COOPER2-AH1-721 TP 161.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
2DENNY-5DENNY 69.0/161.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
2LAUREL CO-5LAUREL CO 69.0/161.0 kV Ckt 1 transformerEKPC_P1-2_LAUR-PIT-TY161_SRT-A
No new ratings for this Flowgate.
2LAUREL CO-5LAUREL CO 69.0/161.0 kV Ckt 1 transformerEKPC_P2-3_TYNER E13-1014_SRT-A
No new ratings for this Flowgate.
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-4243.1 MW0.0%$6,656
AH1-239260.5 MW2.8%$555,851
AH1-7219169.1 MW97.2%$19,567,493

System Reinforcement: n8368.2
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n8368.2 / EKPC-tc1-r0012b
Title
Rebuild the Cooper-Elihu 161 kV line section using 1272 MCM ACSS conductor (4.2 miles)
Description
Rebuild the Cooper-Elihu 161 kV line section using 1272 MCM ACSS conductor (4.2 miles).
Total Cost ($USD)
$10,335,000
Discounted Total Cost ($USD)
$10,335,000
Allocated Cost ($USD)
$10,185,767
Time Estimate
16 to 27 Months

Contributor

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A362.0 MVA
(All)B373.0 MVA
(All)C373.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-2398.5 MW1.4%$149,233
AH1-721577.8 MW98.6%$10,185,767

System Reinforcement: n9769.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9769.0 / AEP-TC2-19070
Title
05CLOVRD_RJA 765.0 kV to 05CLOVRD 765.0 kV ckt Z1 - Upgrade/replace CBs
Description
Upgrade/replace Cloverdale 765 kV, 4000 A CBs "CC" and "CC2" to 5000 A
Total Cost ($USD)
$25,000,000
Discounted Total Cost ($USD)
$25,000,000
Allocated Cost ($USD)
$9,623,735
Time Estimate
48 to 54 Months

Contributor

FacilityContingency
05CLOVRD-05CLOVRD_RJA 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07279.0 MW35.1%$8,763,492
AG2-184 Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
30.5 MW13.5%$3,387,027
AH1-617 Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
29.1 MW12.9%$3,225,746
AH1-72186.7 MW38.5%$9,623,735

System Reinforcement: n9759.0
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
n9759.0 / OVEC-TC2-19030
Title
06KYGER 345.0 kV to 05SPORN 345.0 kV ckt 1 - Replace Equipment
Description
Sag study Sporn - Kyger Creek line and replace section #25 OVEC element conductor 12.51 Miles At Sporn replace the following equipment: 2 - 2000 KCM AAC, 91-Str., AA1S1, AA1S2, AAS1, AAS2, KYGER CREEK #1 - PH A, KYGER CREEK #1 - PH B At Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB
Total Cost ($USD)
$38,180,000
Discounted Total Cost ($USD)
$38,180,000
Allocated Cost ($USD)
$6,419,242
Time Estimate
48 to 60 Months

Contributor

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1942.0 MVA
(All)B2837.0 MVA
LLA1942.0 MVA
LLB2837.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07246.4 MW20.9%$7,994,732
AH1-05571.6 MW32.3%$12,350,917
AH1-53749.7 MW22.4%$8,568,877
AH1-664 New AH1-664 swyd (Goddard - Plumville 138 kV) (EKPC): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-664, AH1-665
9.2 MW4.1%$1,581,182
AH1-665 New AH1-664 swyd (Goddard - Plumville 138 kV) (EKPC): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-664, AH1-665
7.3 MW3.3%$1,265,049
AH1-72137.2 MW16.8%$6,419,242

System Reinforcement: n9765.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9765.0 / AEP-TC2-19065
Title
05CLNCHR 138.0 kV to 05LEBANO 138.0 kV ckt 1 - Rebuild Entrance Span
Description
Rebuild/Reconductor entrance span from Clinch River - Str. 74-1 with 1590 ACSR. Rebuild/Reconductor entrance span from Str. 74-33 to Lebanon with 1590 ACSR. Replace station conductor at Clinch River and Lebanon
Total Cost ($USD)
$4,000,000
Discounted Total Cost ($USD)
$4,000,000
Allocated Cost ($USD)
$1,284,708
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A338.0 MVA
(All)B446.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-184 Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
17.8 MW25.9%$1,035,670
AH1-072 New AH1-072 swyd (Red Onion - VC5 69 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-072, AH1-073
2.6 MW3.8%$151,863
AH1-073 New AH1-072 swyd (Red Onion - VC5 69 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-072, AH1-073
2.6 MW3.8%$151,863
AH1-2276.7 MW9.7%$389,568
AH1-617 Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
17.0 MW24.7%$986,328
AH1-72122.1 MW32.1%$1,284,708

System Reinforcement: n9764.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9764.0 / AEP-TC2-19061
Title
05ELKGARDNSS 138.0 kV to 05SALTV1 138.0 kV ckt 1 - Reconductor entrance span
Description
Rebuild/Reconductor entrance span from Str 74-102 to Saltville with 1590 ACSR. Replace station conductor at Saltville 138 kV Station
Total Cost ($USD)
$4,000,000
Discounted Total Cost ($USD)
$4,000,000
Allocated Cost ($USD)
$1,284,708
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05SALTV1-05ELKGARDNSS 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A387.0 MVA
(All)B446.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-184 Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
17.8 MW25.9%$1,035,670
AH1-072 New AH1-072 swyd (Red Onion - VC5 69 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-072, AH1-073
2.6 MW3.8%$151,863
AH1-073 New AH1-072 swyd (Red Onion - VC5 69 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-072, AH1-073
2.6 MW3.8%$151,863
AH1-2276.7 MW9.7%$389,568
AH1-617 Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
17.0 MW24.7%$986,328
AH1-72122.1 MW32.1%$1,284,708

System Reinforcement: n9775.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9775.0 / EKPC-tc2-nu056
Title
Cooper-AH1-721 Tap (East Cooper) 161 kV Circuit #2 Rebuild (0.5 miles)
Description
Rebuild the Cooper-AH1-721 Tap (East Cooper) 161 kV Circuit #2 (formerly the Cooper-Denny line) line section (0.5 miles) using 954 ACSR conductor.
Total Cost ($USD)
$1,215,000
Discounted Total Cost ($USD)
$1,215,000
Allocated Cost ($USD)
$1,215,000
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
5COOPER2-AH1-721 TP 161.0 kV Ckt 2 line(Any)
Rating SetRating TypeRating Value
LLA268.0 MVA
LLB345.0 MVA
LLC390.0 MVA
SUMA268.0 MVA
SUMB345.0 MVA
SUMC390.0 MVA
WINA387.0 MVA
WINB399.0 MVA
WINC399.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-721625.4 MW100.0%$1,215,000

System Reinforcement: n9776.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9776.0 / EKPC-tc2-nu054
Title
Cooper-AH1-721 Tap (East Cooper) 161 kV Circuit #1 Rebuild (0.5 miles)
Description
Rebuild the Cooper-AH1-721 Tap (East Cooper) 161 kV Circuit #1 (formerly the Cooper-Laurel Dam line) line section (0.5 miles) using 954 ACSR conductor.
Total Cost ($USD)
$1,215,000
Discounted Total Cost ($USD)
$1,215,000
Allocated Cost ($USD)
$1,215,000
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
5COOPER2-AH1-721 TP 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA268.0 MVA
LLB345.0 MVA
LLC391.0 MVA
SUMA268.0 MVA
SUMB345.0 MVA
SUMC391.0 MVA
WINA417.0 MVA
WINB448.0 MVA
WINC448.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-721626.0 MW100.0%$1,215,000

System Reinforcement: n9771.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9771.0 / AEP-TC2-19073
Title
05LEBANO 138.0 kV to 05ELKGARDNSS 138.0 kV ckt 1 - Rebuild/Reconductor Entrance Span
Description
Rebuild/Reconductor entrance span from Str. 74-34 to Lebanon with 1590 ACSR. Replace station conductor at Lebanon
Total Cost ($USD)
$4,000,000
Discounted Total Cost ($USD)
$4,000,000
Allocated Cost ($USD)
$1,014,628
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A387.0 MVA
(All)B446.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-184 Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
20.8 MW28.3%$1,132,681
AH1-072 New AH1-072 swyd (Red Onion - VC5 69 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-072, AH1-073
3.1 MW4.2%$169,549
AH1-073 New AH1-072 swyd (Red Onion - VC5 69 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-072, AH1-073
3.1 MW4.2%$169,549
AH1-2278.0 MW10.9%$434,856
AH1-617 Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
19.8 MW27.0%$1,078,738
AH1-72118.7 MW25.4%$1,014,628

System Reinforcement: n7771.2
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n7771.2 / EKPC-tc1-r0014a
Title
Increase the maximum operating temperature of the Laurel County-Laurel Dam 161 kV line section 795 MCM conductor to 212 degrees F (~10.55 miles)
Description
Increase the maximum operating temperature of the Laurel County-Laurel Dam 161 kV line section 795 MCM conductor to 212 degrees F (~10.55 miles)
Total Cost ($USD)
$1,010,000
Discounted Total Cost ($USD)
$1,010,000
Allocated Cost ($USD)
$1,002,320
Time Estimate
18 to 24 Months

Contributor

FacilityContingency
5LAUREL CO-5LAUREL DAM 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A267.0 MVA
(All)B298.0 MVA
(All)C298.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-2396.0 MW0.8%$7,680
AH1-721785.6 MW99.2%$1,002,320

System Reinforcement: n9781.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9781.0 / EKPC-tc2-nu051
Title
Cooper-Elihu 161 kV Bus Conductor Upgrade
Description
Upgrade the 1.5" IPS aluminum bus conductor at Cooper Station associated with the Cooper-Elihu 161 kV line with at least 2" IPS aluminum bus conductor.
Total Cost ($USD)
$990,000
Discounted Total Cost ($USD)
$990,000
Allocated Cost ($USD)
$975,705
Time Estimate
12 to 15 Months

Contributor

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA408.0 MVA
LLB501.0 MVA
LLC501.0 MVA
SUMA408.0 MVA
SUMB501.0 MVA
SUMC501.0 MVA
WINA468.0 MVA
WINB501.0 MVA
WINC501.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-2398.5 MW1.4%$14,295
AH1-721577.8 MW98.6%$975,705

System Reinforcement: n6834.1
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n6834.1 / EKPC-tc1-r0001a
Title
Rebuild the 4/0 ACSR Green County-Summersville 69 kV line section (4.2 miles) using 556 MCM ACSR.
Description
Rebuild the 4/0 ACSR Green County-Summersville 69 kV line section (4.2 miles) using 556 MCM ACSR.
Total Cost ($USD)
$5,705,000
Discounted Total Cost ($USD)
$5,705,000
Allocated Cost ($USD)
$898,387
Time Estimate
18 to 24 Months

Contributor

FacilityContingency
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A57.0 MVA
(All)B63.0 MVA
(All)C63.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-2981.7 MW2.2%$127,897
AG2-42463.2 MW82.0%$4,678,715
AH1-72112.1 MW15.7%$898,387

System Reinforcement: n9763.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9763.0 / AEP-TC2-19060
Title
05J.FERR 765.0 kV to 05CLOVRD_RJA 765.0 kV ckt 1 - Replace Wavetraps
Description
Replace wave trap on 765 kV Cloverdale line. Replace/upgrade CB's B and B2 with 5000A CBs.
Total Cost ($USD)
$3,300,000
Discounted Total Cost ($USD)
$3,300,000
Allocated Cost ($USD)
$871,818
Time Estimate
48 to 54 Months

Contributor

FacilityContingency
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07279.0 MW24.1%$793,888
AG2-184 Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
30.5 MW9.3%$306,832
AG2-36055.2 MW16.8%$555,293
AG2-363 Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
28.6 MW8.7%$287,968
AG2-364 Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
19.1 MW5.8%$191,979
AH1-617 Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
29.1 MW8.9%$292,222
AH1-72186.7 MW26.4%$871,818

System Reinforcement: n9753.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9753.0 / AEP-TC2-18751
Title
05KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag Study
Description
Sag study Sporn - Kyger Creek line and at Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB, 2870 MCM ACSR (Bus), GCB AA, Wave Trap, Line Relay/CT, Meters, Switch 104, and Switch 10
Total Cost ($USD)
$5,052,000
Discounted Total Cost ($USD)
$5,052,000
Allocated Cost ($USD)
$849,398
Time Estimate
48 to 60 Months

Contributor

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1944.0 MVA
(All)B2825.0 MVA
(All)C2468.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07246.4 MW20.9%$1,057,868
AH1-05571.6 MW32.3%$1,634,281
AH1-53749.7 MW22.4%$1,133,839
AH1-664 New AH1-664 swyd (Goddard - Plumville 138 kV) (EKPC): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-664, AH1-665
9.2 MW4.1%$209,223
AH1-665 New AH1-664 swyd (Goddard - Plumville 138 kV) (EKPC): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-664, AH1-665
7.3 MW3.3%$167,392
AH1-72137.2 MW16.8%$849,398

System Reinforcement: n7773.1
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n7773.1 / EKPC-tc1-r0004b
Title
Change the 69 kV current transformer settings associated with circuit breaker S7-654 from 600A to at least 800A.
Description
Change the 69 kV current transformer settings associated with circuit breaker S7-654 from 600A to at least 800A.
Total Cost ($USD)
$345,000
Discounted Total Cost ($USD)
$345,000
Allocated Cost ($USD)
$345,000
Time Estimate
9 to 12 Months

Contributor

FacilityContingency
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A154.0 MVA
(All)B180.0 MVA
(All)C185.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-721179.9 MW100.0%$345,000

System Reinforcement: n9687.10
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9687.10 / EKPC-tc2-nu053
Title
Cooper 161kV breaker replacements - Breaker 1044 ELIHU
Description
Cooper 161kV breaker replacements - Breaker 1044 ELIHU - replace with 63kA breaker
Total Cost ($USD)
$335,000
Discounted Total Cost ($USD)
$335,000
Allocated Cost ($USD)
$330,163
Time Estimate
Dec 01 2029

Contributor

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA408.0 MVA
LLB545.0 MVA
LLC545.0 MVA
SUMA408.0 MVA
SUMB545.0 MVA
SUMC545.0 MVA
WINA529.0 MVA
WINB545.0 MVA
WINC545.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-2398.5 MW1.4%$4,837
AH1-721577.8 MW98.6%$330,163

System Reinforcement: n9782.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9782.0 / EKPC-tc2-nu050
Title
West London Tap-West London 69 kV Conductor Maximum Operating Temperature Increase
Description
Increase the maximum conductor operating temperature of the 266.8 MCM ACSR conductor (2.15 miles) in the West London-West London Tap (County Farm Road) 69 kV line section to 212 degrees F.
Total Cost ($USD)
$135,000
Discounted Total Cost ($USD)
$135,000
Allocated Cost ($USD)
$135,000
Time Estimate
12 to 21 Months

Contributor

FacilityContingency
2W LONDON-2W LONDON T 69.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA57.0 MVA
LLB63.0 MVA
LLC63.0 MVA
SUMA57.0 MVA
SUMB63.0 MVA
SUMC63.0 MVA
WINA82.0 MVA
WINB86.0 MVA
WINC86.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-72149.6 MW100.0%$135,000

System Reinforcement: n9742.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9742.0 / EKPC-tc2-nu034
Title
Zula Junction N.O.-AG1-471 (Massingale Road) 69 kV Line Section Rebuild (0.6 miles)
Description
Rebuild the Zula Junction N.O.-AG1-471 (Massingale Road) 69 kV line section (0.6 miles) using 556.5 ACSR conductor.
Total Cost ($USD)
$960,000
Discounted Total Cost ($USD)
$960,000
Allocated Cost ($USD)
$61,197
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
2ZULA J NO-AG1-471 TP 69.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A89.0 MVA
(All)B98.0 MVA
(All)C98.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-23980.0 MW93.6%$898,803
AH1-7215.4 MW6.4%$61,197

System Reinforcement: n9780.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9780.0 / EKPC-tc2-nu052
Title
Cooper-Elihu 161 kV Relay Upgrade
Description
Upgrade the relays at Cooper Station associated with the Cooper-Elihu 161 kV line to provide thermal capability of at least 2000A capability
Total Cost ($USD)
$55,000
Discounted Total Cost ($USD)
$55,000
Allocated Cost ($USD)
$54,206
Time Estimate
12 to 15 Months

Contributor

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA408.0 MVA
LLB517.0 MVA
LLC525.0 MVA
SUMA408.0 MVA
SUMB517.0 MVA
SUMC525.0 MVA
WINA544.0 MVA
WINB654.0 MVA
WINC660.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-2398.5 MW1.4%$794
AH1-721577.8 MW98.6%$54,206

System Reinforcement: n7771.1
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n7771.1 / r0013
Title
Increase the maximum operating temperature of the Laurel County-Laurel Dam 161 kV line section 795 MCM conductor to 167 degrees F (~0.2 miles)
Description
Total Cost ($USD)
$35,000
Discounted Total Cost ($USD)
$35,000
Allocated Cost ($USD)
$34,734
Time Estimate
9 to 12 Months

Contributor

FacilityContingency
5LAUREL CO-5LAUREL DAM 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A186.0 MVA
(All)B210.0 MVA
(All)C210.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-2396.0 MW0.8%$266
AH1-721785.6 MW99.2%$34,734

System Reinforcement: n8368.4
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n8368.4 / EKPC-tc1-r0012d
Title
Upgrade the existing 795 MCM ACSR jumpers at the Cooper substation associated with the Cooper-Elihu 161 kV line using bundled 500 MCM CU or equivalent
Description
Upgrade the existing 795 MCM ACSR jumpers at the Cooper substation associated with the Cooper-Elihu 161 kV line using bundled 500 MCM CU or equivalent
Total Cost ($USD)
$35,000
Discounted Total Cost ($USD)
$35,000
Allocated Cost ($USD)
$34,495
Time Estimate
9 to 12 Months

Contributor

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A344.0 MVA
(All)B383.0 MVA
(All)C390.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-2398.5 MW1.4%$505
AH1-721577.8 MW98.6%$34,495

System Reinforcement: n9778.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9778.0 / EKPC-tc2-nu047
Title
Increase the Zone 3 relay setting at Somerset substation associated with the Somerset-KU Ferguson South 69 kV line section to at least 205 MVA.
Description
Increase the Zone 3 relay setting at Somerset substation associated with the Somerset-KU Ferguson South 69 kV line section to at least 205 MVA.
Total Cost ($USD)
$10,000
Discounted Total Cost ($USD)
$10,000
Allocated Cost ($USD)
$10,000
Time Estimate
6 to 9 Months

Contributor

FacilityContingency
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA180.0 MVA
LLB230.0 MVA
LLC259.0 MVA
SUMA180.0 MVA
SUMB230.0 MVA
SUMC259.0 MVA
WINA190.0 MVA
WINB205.0 MVA
WINC207.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-721179.9 MW100.0%$10,000

System Reinforcement: n9777.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9777.0 / EKPC-tc2-nu055
Title
Cooper-AH1-721 (East Cooper) Circuit #2 161 kV Zone 3 Setting Upgrade
Description
Increase the Zone 3 relay setting at Cooper substation associated with the Cooper-AH1-721 (East Cooper) 161 kV Circuit #2 (formerly the Cooper-Denny line) to at least 387 MVA.
Total Cost ($USD)
$10,000
Discounted Total Cost ($USD)
$10,000
Allocated Cost ($USD)
$10,000
Time Estimate
9 to 12 Months

Contributor

FacilityContingency
5COOPER2-AH1-721 TP 161.0 kV Ckt 2 line(Any)
Rating SetRating TypeRating Value
LLA186.0 MVA
LLB210.0 MVA
LLC210.0 MVA
SUMA186.0 MVA
SUMB210.0 MVA
SUMC210.0 MVA
WINA343.0 MVA
WINB355.0 MVA
WINC355.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-721625.4 MW100.0%$10,000

System Reinforcement: n8368.3
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n8368.3 / EKPC-tc1-r0012c
Title
Change the Zone 3 relay setting at Elihu substation associated with the line protection to at least 545 MVA LTE rating.
Description
Change the Zone 3 relay setting at Elihu substation associated with the line protection to at least 545 MVA LTE rating.
Total Cost ($USD)
$10,000
Discounted Total Cost ($USD)
$10,000
Allocated Cost ($USD)
$9,856
Time Estimate
9 to 12 Months

Contributor

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A325.0 MVA
(All)B381.0 MVA
(All)C390.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-2398.5 MW1.4%$144
AH1-721577.8 MW98.6%$9,856

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4068.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4068.1 / AEP-TC2-18693
Title
b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570
Description
b4068.1 through b4068.49: Affected Transmission Owners: AEP / Dayton / ATSI The objective of this project is to construct multiple transmission lines to address Ohio area violations. The total distance covered by the lines is approximately 359.54 miles. The first transmission line ranges from the existing Greentown Substation in Howard County, Indiana to the new Teddy Substation in Clark County, Ohio, the line then branches north towards the existing Marysville Substation in Union County, Ohio, and east to the existing Beatty Substation in Franklin County, Ohio, and then extends to the existing Cole Substation in Franklin County, Ohio. The second transmission line extends from the existing Adkins Substation in Pickaway County, Ohio, to the new West Millersport Substation in Fairfield County, Ohio, then continues to the existing Conesville Substation in Coshocton County, Ohio before finally extending to the existing Guernsey Substation in Guernsey County, Ohio. There is a total of five transmission lines that extend between unnamed substations (Hayden - Cole 345 kV, Hyatt - Maliszewski 345 kV [double circuit], Roberts - Kenny 138 kV, Wilson - 5th Avenue 138 kV, West Millersport-Kirk 345 kV). This project will traverse 4 counties (Howard, Grant, Blackford, Jay) in Indiana, and 13 counties (Darke, Shelby, Champaign, Clark, Madison, Franklin, Delaware, Pickaway, Fairfield, Licking, Muskingum, Coshocton, Guernsey) in Ohio. This proposal has a total of 38 components, including 16 substation upgrade components, two greenfield substation components, eight greenfield transmission line components covering approximately 336.2 miles, and 12 transmission line upgrade components covering approximately 23.34 miles. b4068.28/b4068.49 is dependent on b3919.1 Baseline completion.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
08LONGBR-4BOONE CO 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3919.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3919.1
Title
Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yard
Description
Reconfigure Maliszewski 765 kV station from 2 breakers to a 6 breaker ring bus. Install a new 765/345 kV transformer. Establish new 345 kV breaker yard with 3 string breaker and a half to include a line exit to Hyatt and a line exit to Corridor. Loop the existing Hyatt - West Millersport 345 kV line into the new established 345 kV yard at the Maliszewski station.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
08LONGBR-4BOONE CO 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.252
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.252
Title
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Description
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4000.251
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.251
Title
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Description
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: s2572.3
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s2572.3
Title
Rebuild ~21 miles of the 138KV line between Saltville and Tazewell stations
Description
Rebuild ~21 miles of the 138KV line between Saltville and Tazewell stations
Cost Information
Time Estimate
Sep 02 2036

Contingent

Note: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA296.0 MVA
LLB413.0 MVA
SUMA296.0 MVA
SUMB413.0 MVA
WINA375.0 MVA
WINB464.0 MVA
05TAZEWE-AH1-133 TP 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA296.0 MVA
LLB413.0 MVA
SUMA296.0 MVA
SUMB413.0 MVA
WINA375.0 MVA
WINB464.0 MVA

System Reinforcement: b3788.2
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
b3788.2 / B3788.2
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace OVEC-owned breaker AA risers, bus work, and breaker AA disconnect switches at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Jun 01 2028

Contingent

Note: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B1540.0 MVA

System Reinforcement: b3788.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3788.1 / B3788.1
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace AEP-owned station takeoff riser and breaker BB risers at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Apr 03 2028

Contingent

Note: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B1540.0 MVA

System Reinforcement
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
(Pending) / DEOK_TC1_13706
Title
Line is 100% owned by EKPC. No DEOK upgrade required.
Description
Line is 100% owned by EKPC. No DEOK upgrade required.
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
08LONGBR-4BOONE CO 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc1-r0004a
Title
EKPC emergency rating is 143 MVA.
Description
EKPC emergency rating is 143 MVA. LG&E: SE rating is 105 MVA.
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A143.0 MVA
(All)B143.0 MVA
(All)C143.0 MVA

System Reinforcement: n7773.4
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n7773.4 / (Pending)
Title
Replace the 1200A disconnects S7-653 and S7-655 at Somerset substation with 2000A equipment.
Description
Replace the 1200A disconnects S7-653 and S7-655 at Somerset substation with 2000A equipment.
Total Cost ($USD)
$155,000
Discounted Total Cost ($USD)
$155,000
Allocated Cost ($USD)
$0
Time Estimate
9 to 12 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-721 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-721 could receive cost allocation. Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA180.0 MVA
LLB230.0 MVA
LLC259.0 MVA
SUMA180.0 MVA
SUMB230.0 MVA
SUMC259.0 MVA
WINA286.0 MVA
WINB286.0 MVA
WINC286.0 MVA

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc1-r0005a
Title
LGEE violation (non PJM area). EKPC emergency rating at 54 MVA The externa [...] Owner, LGEE, will not evaluate this violation until the impact study phase.
Description
LGEE violation (non PJM area). EKPC emergency rating at 54 MVA The external (i.e. Non-PJM) Transmission Owner, LGEE, will not evaluate this violation until the impact study phase.
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A49.0 MVA
(All)B54.0 MVA
(All)C54.0 MVA

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc1-r0012a
Title
LGE/KU is limiting this facility. EKPC emergency rating is 298 MVA.
Description
LGE/KU is limiting this facility (LGEE Summer 219/277 MVA & winter 335/335 MVA Rate A/Rate B). EKPC emergency rating is 298 MVA. LGEE AFS for TC1 has determined they will not require an reinforcement and thus EKPC existing 298 MVA Rate B is adequate as LGEE is the limiting element of the line.
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA267.0 MVA
SUMB298.0 MVA
SUMC298.0 MVA

System Reinforcement: n8368.5
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n8368.5 / EKPC-r0117d
Title
Cooper-Elihu 161 kV Current Transformer Upgrade
Description
Upgrade the 1200A current transformer at the Cooper substation associated with the Cooper-Elihu 161 kV line with a 2000A current transformer.
Total Cost ($USD)
$135,000
Discounted Total Cost ($USD)
$135,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 15 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-721 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-721 could receive cost allocation. Although AH1-721 may not presently have cost responsibility for this upgrade, AH1-721 may need this upgrade in-service to be deliverable to the PJM system. If AH1-721 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA359.0 MVA
LLB437.0 MVA
LLC476.0 MVA
SUMA359.0 MVA
SUMB437.0 MVA
SUMC476.0 MVA
WINA468.0 MVA
WINB501.0 MVA
WINC501.0 MVA

System Reinforcement: s3165.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
s3165.0 / s3165
Title
Construct a new 161/13.8 kV distribution substation and associated 0.25 mile 161 kV double circuit tap line.
Description
Construct a new 161/13.8 kV distribution substation and associated 0.25 mile 161 kV double circuit tap line. This new delivery point will tap the existing EKPC Marion County-Green County 161 kV transmission circuit approximately 2 mile southwest of the Marion County substation.
Cost Information
Time Estimate
Jul 26 2024

Not Contingent

Note: AH1-721 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-721 is not contingent on this supplemental project as it is already in-service.

FacilityContingency
5PITTSBURG-5TYNER 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A267.0 MVA
(All)B298.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-721


AH1-721 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
StabilityEKPCn9688.0 / EKPC-tc2-nu049AH1-239 Tap (Clinton County)-Homestead New 69 kV Line (15 miles)Topology10.3 MW3.1%Cost Allocated$508,152
Load FlowEKPCn9743.0 / EKPC-tc2-nu003Cooper CCGT-Alcalde 161 kV Double-Circuit Line AdditionTopology9169.1 MW97.2%Cost Allocated$19,567,493
Load FlowAPSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardTopology-0.0%Contingent$0
Load FlowAPSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Topology-0.0%Contingent$0
Load FlowAPSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Topology-0.0%Contingent$0
Load FlowAPSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationTopology-0.0%Contingent$0
Load FlowAPSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAEPb4068.1 / AEP-TC2-18693b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570Topology-0.0%Contingent$0
Load FlowAEPb3919.1Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yardTopology-0.0%Contingent$0
Load FlowDominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Topology-0.0%Contingent$0
Load FlowAEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Topology-0.0%Contingent$0
Load FlowDominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Topology-0.0%Contingent$0
Load FlowDominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Topology-0.0%Contingent$0
Load FlowDominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Topology-0.0%Contingent$0
Load FlowDominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Topology-0.0%Contingent$0
Load FlowDominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationTopology-0.0%Contingent$0
Load FlowDominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Topology-0.0%Contingent$0
Load FlowDominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Topology-0.0%Contingent$0
Load FlowDominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Topology-0.0%Contingent$0
Load FlowDominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Topology-0.0%Contingent$0
Load FlowDominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Topology-0.0%Contingent$0
Load FlowDominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$20,075,645
AH1-721 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-721 One Line Diagram

AH1-721 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.