AH1-725 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:16

Conastone 500 kV

500.0 MW Capacity / 500.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Cardinal Energy Storage East, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Baltimore Gas and Electric Company.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request meets the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposits refunded. See Readiness Deposit calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $8,741,862 $2,000,000 = 4.37 AND ( $8,741,862 - $2,000,000 ) 500.0 = $13,484 per MW

General

The Project Developer has proposed a Storage facility located in the Baltimore Gas and Electric Company zone — Harford County, Maryland. The installed facilities will have a total capability of 500.0 MW with 500.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-725
Project Name:
Conastone 500 kV
Project Developer Name:
Cardinal Energy Storage East, LLC
State:
Maryland
County:
Harford
Transmission Owner:
Baltimore Gas and Electric Company
MFO:
500.0
MWE:
500.0
MWC:
500.0
Battery Storage Specification:
30000.0 MWh, 6.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AH1-725 will interconnect on the Baltimore Gas and Electric Company transmission system at the Conastone 500 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-725 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-725Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$35,054,607$0$0
Other Scope$0$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$8,741,862$8,741,862$8,741,862
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$43,796,469$8,741,862$8,741,862

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-725

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-725
Project ID: AH1-725
20% of cost allocation for Phase II Network Upgrades:(A) $1,748,372
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $2,000,000
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $0
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install (1) 500 kV, 4000A, 63 kA circuit breaker at Conastone substation in position G along with maintenance disconnect switches, bus tubing, CCVT's, relaying upgrades, etc. as required.

$1,307,765$6,955,543$130,776$347,777$8,741,862$8,741,862
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install termination structures, terminations, gas insulated cables, arrestors, grounding and fiber and extend approximately 0.5-mile Gas Insulated Bus (GIB) from Conastone breaker position G to Project Developer provided location to be designated as Point of Change of Ownership (PCO).

$10,401,631$23,367,872$1,218,972$66,132$35,054,607$35,054,607
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$43,796,469$43,796,469
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 42 to 72 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

No impacts identified by Transmission Owner.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. BGE interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-725 was evaluated as a 500.0 MW (500.0 MW Capacity) injection in the BGE area.

AH1-725 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 500.0 MW (500.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019E_SRT-SL
BreakerAC127.16 %3098.0B3939.34
137.76
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P1-2_PE-500-3835T_SRT-A
SingleAC116.99 %3098.0B3624.44
137.55
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC111.62 %3098.0B3458.01
114.2
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK
BreakerAC103.85 %3098.0B3217.41
140.97
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
BG_P7_CNSTN_NWEST2_SRT-A
TowerAC102.61 %3098.0B3178.71
123.89
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
BreakerAC101.69 %3098.0B3150.34
142.64
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
DPL_P4_2_KEENEY-ROCK AT50_SRT-A
BreakerAC101.33 %2860.0B2897.9
200.32
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
PECO_P1-2_5025_SRT-A/* $ CHESCO $ PECO_P1-2_5025 $ L
SingleAC101.06 %2860.0B2890.26
200.32

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019E_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019E_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.16 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3939.34
MW Contribution:
137.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
2.052
200053ROCKSP 2
50/50
2.012
200054ROCKSP 3
50/50
2.076
200055ROCKSP 4
50/50
2.04
200203Y1-065-STG
50/50
5.649
200204Y1-065-CTG1
50/50
3.262
200205Y1-065-CTG2
50/50
3.262
3147043LAWRENC
Solar/Wind Helper
0.137
3147133PAMPLIN
Solar/Wind Helper
0.717
3147133PAMPLIN
Solar/Wind Helper
0.183
3147133PAMPLIN
Solar/Wind Helper
0.228
20334726NME_Y1-047
Adder
2.076
20390726Y2-042
Adder
2.289
23546401DTGZ2-030
Solar/Wind Helper
0.076
20486527WR_V4-052
Adder
0.887
20628028LAKEHURS
Adder
0.795
20633028GILCT9
Adder
23.779
20634528N27_Y2-018
Solar/Wind Harmer
0.225
20635828PARLN1&2
Adder
2.798
20635828PARLN1&2
Adder
6.178
20635928PARLN3&4
Adder
2.798
20635928PARLN3&4
Adder
6.178
20636028O CRK C1
Adder
5.914
20636128O CRK C2
Adder
5.392
20641628MLH_W1-032
Solar/Wind Harmer
0.245
20671828STAW2-080
Solar/Wind Harmer
0.088
20671928W4-073
Solar/Wind Harmer
0.363
20673628F1S_V4-069
Solar/Wind Harmer
0.15
20673728F2S_V4-070
Solar/Wind Harmer
0.15
20673828FLE_V3-070
Solar/Wind Harmer
0.389
20674128FR_U2-059
Solar/Wind Harmer
0.154
20674328GAR_V4-001
Solar/Wind Harmer
0.092
20674528F3S_W2-016
Solar/Wind Harmer
1.177
20674628WNG_W3-110
Solar/Wind Harmer
0.337
20674828DL_W4-046
Solar/Wind Harmer
0.541
20674928WA_W3-044
Solar/Wind Harmer
0.403
20675128HRM_W1-127
Solar/Wind Harmer
0.143
20675428EAM_W2-061
Solar/Wind Harmer
0.158
20675528CPH_W2-050
Solar/Wind Harmer
0.479
20675728RH_W2-091
Solar/Wind Harmer
0.506
20675828AU_W4-064
Solar/Wind Harmer
0.145
20675928HOL_W4-097
Solar/Wind Harmer
0.11
20676128MHD_W3-029
Solar/Wind Harmer
0.399
20676228FRD_X1-012
Solar/Wind Harmer
0.494
20676328BVR_Y1-020
Solar/Wind Harmer
0.277
20676428JCR_X2-075
Solar/Wind Harmer
0.285
20676728BRNX1-095
Solar/Wind Harmer
0.147
20714428HOW_X1-037
Solar/Wind Harmer
1.031
20714528FRN_Y2-051
Solar/Wind Harmer
0.246
20714828MDF_W3-079
Solar/Wind Harmer
0.255
20714928UPF_X1-085
Solar/Wind Harmer
0.34
20715028HAN_X4-015
Solar/Wind Harmer
0.25
20715228NPK_W1-113
Solar/Wind Harmer
0.359
20715728PEM_W1-119
Solar/Wind Harmer
0.447
20715828PEM_W1-120
Solar/Wind Harmer
0.447
20716028EGP_W2-019
Solar/Wind Harmer
0.388
20716228APLW2-078
Solar/Wind Harmer
0.737
20716428NHV_W2-082
Solar/Wind Harmer
1.489
20716928W4-060COL
Solar/Wind Harmer
0.593
20717128DIX_Z2-102
Solar/Wind Harmer
1.105
20720428HOL_W1-112
Solar/Wind Harmer
0.289
20720528MAN_W1-024
Solar/Wind Harmer
0.212
20720628TIN_W1-124
Solar/Wind Harmer
0.831
20720728JCB_W1-129
Solar/Wind Harmer
0.25
20720828JCB_W4-025
Solar/Wind Harmer
0.379
207408W3-077 C
Solar/Wind Harmer
0.425
207439AE1-081 C O1
Solar/Wind Harmer
0.05
213497CHSTR7-9
Adder
2.334
213497CHSTR7-9
Adder
2.334
213497CHSTR7-9
Adder
2.334
213535CROYDN11
Adder
8.623
213560DLW11-12
Adder
2.303
213560DLW11-12
Adder
2.303
213561DLWR9-10
Adder
3.011
213561DLWR9-10
Adder
2.303
213587EDDYSTN3
Adder
68.152
213589EDDYSTN4
Adder
68.158
213611FALLS1-3
Adder
2.97
213611FALLS1-3
Adder
2.97
213611FALLS1-3
Adder
2.97
213815MOSER1-3
Adder
2.994
213815MOSER1-3
Adder
2.994
213815MOSER1-3
Adder
2.994
213942SCHUYLKILL
Adder
2.315
213942SCHUYLKILL
Adder
3.027
213957STHWK3-4
Adder
2.314
213957STHWK3-4
Adder
2.314
213958STHWK5-6
Adder
2.314
213958STHWK5-6
Adder
2.314
214067T20SOLAR
Solar/Wind Harmer
0.212
214194N WALES4
Adder
0.716
217206BARNGR HS C
Solar/Wind Harmer
0.026
217208PARK ELE C
Solar/Wind Harmer
0.021
217209CENTRL HS C
Solar/Wind Harmer
0.037
217211CAMDEN ST C
Solar/Wind Harmer
0.02
217213AMBOY SO C
Solar/Wind Harmer
0.106
231907DC10
Adder
3.382
231917EM10
Adder
2.237
231918WEST 1
Adder
3.199
231919CHRIST1
Adder
4.207
231920CHRIST2
Adder
4.114
231940T-011
Adder
0.726
232404W1-003 C
Solar/Wind Harmer
0.973
232408W1-005 C
Solar/Wind Harmer
0.973
232410W1-006 C
Solar/Wind Harmer
0.973
232417X3-008 C
Solar/Wind Harmer
1.094
232426Y1-080 FULL
Solar/Wind Harmer
0.186
232428Y3-058 C
Solar/Wind Harmer
0.811
232813VAUGHN
Adder
0.572
232901NORTHST
Adder
8.101
232902EASTMUNI
Adder
12.659
232904IR4
Adder
78.673
232907VN8
Adder
29.221
232912OH NUG1
Adder
8.595
232913OH NUG2
Adder
8.48
232914OH NUG3
Adder
8.595
232915OH NUG4
Adder
8.537
232916OH NUG5
Adder
8.595
232917OH NUG6
Adder
8.556
232918OH NUG7
Adder
8.537
232919VN10
Adder
2.73
232920IR10
Adder
3.075
232921TASLEY2G
Adder
5.023
232926CRISFLD1
Adder
1.91
3137176SLIGO L2192
Solar/Wind Helper
0.965
3141426STAFORD
Solar/Wind Helper
0.062
3141906WESTMOR
Solar/Wind Helper
0.104
3142416OLDCHRC
Solar/Wind Helper
0.656
3142416OLDCHRC
Solar/Wind Helper
0.251
3142433PROV 92
Solar/Wind Helper
1.003
3142956BIRDNECK
Solar/Wind Helper
0.164
3143316POE
Solar/Wind Helper
0.969
3144356SAPONY
Solar/Wind Helper
0.429
3145506HICKORY
Solar/Wind Helper
0.972
3145506HICKORY
Solar/Wind Helper
0.583
3145506HICKORY
Solar/Wind Helper
0.146
3146386ELIZ CT
Solar/Wind Helper
0.241
3146776BUCKING
Solar/Wind Helper
0.93
3146776BUCKING
Solar/Wind Helper
0.075
3146776BUCKING
Solar/Wind Helper
0.084
3146776BUCKING
Solar/Wind Helper
0.093
209027LOR2_Q27
Solar/Wind Harmer
3.641
212266LOR1
Solar/Wind Harmer
0.965
217081WEATEXAS C
Solar/Wind Harmer
0.072
217083KRNY_132
Adder
7.71
217083KRNY_132
Adder
7.76
217086KRNY_131
Adder
7.776
217086KRNY_131
Adder
7.694
217146KRNY_1234
Adder
7.232
217146KRNY_1234
Adder
7.183
217147KRNY_1212
Adder
7.381
217147KRNY_1212
Adder
7.249
217167KRNY_14
Adder
7.76
217169METRODIV C
Solar/Wind Harmer
0.033
217186ESSEX_G9
Adder
3.295
217197RE CRAN C
Solar/Wind Harmer
0.448
217201HACKENSOLA C
Solar/Wind Harmer
0.061
217202FBANKSOLAR C
Solar/Wind Harmer
0.061
218418LINDEN_G5
Adder
14.336
218419LINDEN_G6
Adder
14.336
218428ETC SOLAR C
Solar/Wind Harmer
0.03
218438BLK ROCK C
Solar/Wind Harmer
0.114
218440SUMMTASSOC C
Solar/Wind Harmer
0.107
218449LINSOLAR C
Solar/Wind Harmer
0.84
218660EHAMPSOLAR C
Solar/Wind Harmer
0.148
219035LINDEN_G8
Adder
13.763
219036LINDEN_G7
Adder
13.962
219114HARTZY_C
Solar/Wind Harmer
0.698
219137THOSOLAR C
Solar/Wind Harmer
1.032
219236SOUTHERNHQ C
Solar/Wind Harmer
0.057
219249CENTRALDIV C
Solar/Wind Harmer
0.033
219272CLEANLIGHT C
Solar/Wind Harmer
0.155
219276PARKLANDSO C
Solar/Wind Harmer
0.386
219287REEVESEAST C
Solar/Wind Harmer
1.141
219291REEVESSOUT C
Solar/Wind Harmer
0.051
219348LDSOLAR C
Solar/Wind Harmer
0.504
219607WPEMNERT C
Solar/Wind Harmer
0.353
219610FLORENCE C
Solar/Wind Harmer
1.168
219612MATRIX C
Solar/Wind Harmer
0.153
219615MILLCREEK C
Solar/Wind Harmer
0.201
219620RIDERU C
Solar/Wind Harmer
0.047
219766PARADISE C
Solar/Wind Harmer
0.267
219817TRENTONSOL C
Solar/Wind Harmer
0.921
227927V4-067C
Solar/Wind Harmer
0.17
228200CARL#1CT
Adder
5.63
228201CARL#2CT
Adder
5.92
228206SHRMN CT
Adder
14.293
228251CARLLS#4
Adder
0.543
228260V4-054C
Solar/Wind Harmer
0.884
228307PCLP GT
Adder
10.382
228400MICK 1CT
Adder
10.117
228711V2-041C
Solar/Wind Harmer
0.518
316075AC2-137 C
Solar/Wind Helper
0.384
316077AC2-138 C
Solar/Wind Helper
0.241
20462827N BANGR8
Adder
0.6
228728W1-130C
Solar/Wind Harmer
0.57
228729W2-030 C
Solar/Wind Harmer
0.495
228732V1-021 C
Adder
0.163
3138133OCRAN
Solar/Wind Helper
0.076
3138133OCRAN
Solar/Wind Helper
0.151
3141766HARMONY
Solar/Wind Helper
0.05
3141783LANCAST
Solar/Wind Helper
0.151
3141783LANCAST
Solar/Wind Helper
0.101
3141813NORNECK
Solar/Wind Helper
0.255
3141913WHIT STONE
Solar/Wind Helper
0.252
3143226MDLTHAN
Solar/Wind Helper
0.25
3143873LANEXA
Solar/Wind Helper
0.151
3145273HOLLAND
Solar/Wind Helper
0.179
3146376EDENTON
Solar/Wind Helper
0.237
3146456SLIGO L269
Solar/Wind Helper
0.242
3146456SLIGO L269
Solar/Wind Helper
0.242
3146486SUNBURY
Solar/Wind Helper
0.241
3146486SUNBURY
Solar/Wind Helper
0.241
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.778
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.24
3146626S HERTFORD
Solar/Wind Helper
0.239
3146626S HERTFORD
Solar/Wind Helper
0.239
3146626S HERTFORD
Solar/Wind Helper
0.239
3146926FARMVIL
Solar/Wind Helper
0.139
3146926FARMVIL
Solar/Wind Helper
0.139
3147666LOUISA
Solar/Wind Helper
1.044
3147666LOUISA
Solar/Wind Helper
0.6
3147983MERCK5
Solar/Wind Helper
0.09
200034PCHBTM 2
50/50
16.353
200035PCHBTM 3
50/50
16.218
232406W1-004 FULL
Solar/Wind Harmer
0.973
232436AB1-176 C
Solar/Wind Harmer
0.222
200192DELTA CT1
50/50
1.567
200193DELTA CT2
50/50
1.567
200194DELTA CT3
50/50
1.567
200195DELTA ST
50/50
2.421
217194REDH C
Solar/Wind Harmer
0.411
3141726DUNNSVL
Solar/Wind Helper
1.019
3145663CRESWEL
Solar/Wind Helper
0.659
316034AC1-036 C
Solar/Wind Helper
0.238
316036AC1-147 C
Solar/Wind Helper
0.372
316059AD1-063 C
Solar/Wind Helper
0.254
316159AE1-175 C
Solar/Wind Helper
0.377
316240AF1-291 C
Solar/Wind Helper
0.334
316246AF1-032 C
Solar/Wind Helper
0.278
316258AE1-075 C
Solar/Wind Helper
0.335
316305AF2-043 C
Solar/Wind Helper
0.327
316315AB2-025 C
Solar/Wind Helper
0.366
316316AC1-027 C
Solar/Wind Helper
0.385
316317KELFORD C
Solar/Wind Helper
0.206
316382AG1-145 C
Solar/Wind Helper
0.335
316405AF2-144 C
Solar/Wind Helper
0.279
230415AB2-049 C
Solar/Wind Harmer
0.163
20742028HF_AC1-207
Solar/Wind Harmer
0.654
207454AA2-184 E
Solar/Wind Harmer
0.834
207459AE1-142 C O1
Solar/Wind Harmer
0.882
207471AF2-354 C
Solar/Wind Harmer
0.429
208835TUHI V3-051
Solar/Wind Harmer
0.044
208835TUHI V3-051
Solar/Wind Harmer
0.044
208909MACR G3
Adder
133.375
208923BUSO V4-027
Solar/Wind Harmer
0.248
209008PAXT IPP
Adder
1.603
209010PEIP 1
Adder
2.851
209010PEIP 1
Adder
0.418
209010PEIP 1
Adder
0.518
209018SUNBIPCT
Adder
5.784
209023WIENIPP1
Adder
8.797
209025WIENIPP3
Adder
4.303
209025WIENIPP3
Adder
4.391
209026WIENIPP4
Adder
4.347
209030FRFA O01
Adder
0.192
232424Y1-079 C
Solar/Wind Harmer
0.545
232899W1-062
Adder
9.354
232900DEMECSMY
Adder
8.973
232905CHERITON_25
Adder
2.387
218524CNTRALGAS1 C
Solar/Wind Harmer
0.308
218526CNTRALGAS2 C
Solar/Wind Harmer
0.309
226910AB2-157 C
Solar/Wind Helper
0.017
233901CHERRYDALE C
Solar/Wind Harmer
1.094
233939AC1-091 C
Solar/Wind Harmer
2.608
233940AF2-379 C
Solar/Wind Harmer
0.181
233970AC1-092 C
Solar/Wind Harmer
2.608
233971AC1-093 C
Solar/Wind Harmer
2.477
233972AC1-094 C
Solar/Wind Harmer
2.095
233973AC2-185 C
Solar/Wind Harmer
5.27
212507AE2-042_GEN
Solar/Wind Harmer
2.343
219727YARDVSOLFA C
Solar/Wind Harmer
0.761
219907AC1-030 C
Solar/Wind Harmer
0.118
3130156CHOWAN
Solar/Wind Helper
0.237
3130156CHOWAN
Solar/Wind Helper
0.237
3130156CHOWAN
Solar/Wind Helper
0.237
3145336SMITFLD
Solar/Wind Helper
0.979
3145336SMITFLD
Solar/Wind Helper
0.098
3148133STUARTS
Solar/Wind Helper
0.134
3141196NOKESVL
Solar/Wind Helper
1.133
3141873WAN 176
Solar/Wind Helper
0.05
3143526WINTERP
Solar/Wind Helper
1.301
3143526WINTERP
Solar/Wind Helper
1.301
316411AF1-147_GEN1
Solar/Wind Helper
0.98
316415AF1-147_GEN2
Solar/Wind Helper
0.98
316404AE1-155 C
Solar/Wind Helper
2.174
316017AA1-139 ULT1
Solar/Wind Helper
1.112
316018AA1-139 ULT2
Solar/Wind Helper
1.046
316181AB2-040 GEN
Solar/Wind Helper
1.651
316033AB2-134 GEN
Solar/Wind Helper
0.855
228754AB1-001 C
Solar/Wind Harmer
0.119
316388AE2-253 GEN
Solar/Wind Helper
0.927
228351V2-046C
Solar/Wind Harmer
1.732
205956AE1-196_GEN
Solar/Wind Harmer
0.58
217204WCALDSOLAR C
Solar/Wind Harmer
0.061
3148013FISHERV
Solar/Wind Helper
0.129
3148013FISHERV
Solar/Wind Helper
0.224
3145176PASQUOTANK
Solar/Wind Helper
0.149
3132123MT JACKSON
Solar/Wind Helper
0.716
3132273ORANGE
Solar/Wind Helper
0.052
3142543TWELFTH
Solar/Wind Helper
0.024
3144303KENBRDG
Solar/Wind Helper
0.181
238175AF1-290_GEN
Solar/Wind Helper
0.137
238169AE2-226 GEN1
Solar/Wind Helper
0.612
238170AE2-226 GEN2
Solar/Wind Helper
0.612
316005AA1-067
Solar/Wind Helper
0.256
233944AB2-135 GEN
Solar/Wind Harmer
5.063
233946AB2-136 GEN
Solar/Wind Harmer
3.878
316426AA2-053 GEN
Solar/Wind Helper
1.309
316190AA2-174 GEN
Solar/Wind Helper
0.015
233994AC2-023 GEN
Solar/Wind Harmer
2.612
315614AA2-178 GEN
Solar/Wind Helper
1.437
315816AE2-034 GEN
Solar/Wind Helper
1.078
316312AB1-027
Solar/Wind Helper
0.481
316011AB1-132 GEN
Solar/Wind Helper
2.467
316369SG1_INVT
Solar/Wind Helper
1.191
315651AD1-115 GEN
Solar/Wind Helper
0.909
316023GEN1_S
Solar/Wind Helper
0.888
316365GEN2_N
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.514
316463AE2-346 GEN
Solar/Wind Helper
0.212
315839AE2-212 C
Solar/Wind Helper
0.332
233984AB2-036 GEN
Solar/Wind Harmer
12.079
233982AB2-133 GEN
Solar/Wind Harmer
4.706
233915AB1-141 GEN
Solar/Wind Harmer
0.957
233918AB1-142 GEN
Solar/Wind Harmer
0.957
315821AE2-092 GEN
Solar/Wind Helper
2.125
316499AE2-029_GEN
Solar/Wind Helper
0.757
315671AE2-027_GEN
Solar/Wind Helper
1.998
233930AB2-032 GEN
Solar/Wind Harmer
0.805
233987AB2-037 GEN
Solar/Wind Harmer
11.072
315662AE1-191 GEN
Solar/Wind Helper
1.354
315666AE1-190 GEN
Solar/Wind Helper
0.338
319010AE1-072 C
Solar/Wind Helper
2.775
315697AD1-025 GEN
Solar/Wind Helper
2.824
316185AD1-033 GEN
Solar/Wind Helper
1.148
233933AB2-153 GEN
Solar/Wind Harmer
1.087
233955AB2-172 GEN
Solar/Wind Harmer
4.861
315773AC2-141 GEN
Solar/Wind Helper
5.274
316280AD1-041 GEN
Solar/Wind Helper
0.846
233935AB2-179 C
Solar/Wind Harmer
2.395
234041AC1-190 GEN
Solar/Wind Harmer
8.709
315732AD1-074 GEN1
Solar/Wind Helper
2.672
315733AD1-074 GEN2
Solar/Wind Helper
2.672
315735AD1-075 GEN1
Solar/Wind Helper
1.336
315737AD1-076 GEN
Solar/Wind Helper
2.285
316473AC1-191 GEN
Solar/Wind Helper
1.553
316478AD1-087 GEN
Solar/Wind Helper
1.116
316486AD2-202 GEN
Solar/Wind Helper
0.327
316447AC1-158 HLD
Solar/Wind Helper
3.315
316044AC1-158 PL1
Solar/Wind Helper
1.506
316045AC1-158 PL2
Solar/Wind Helper
4.82
316450AC1-158 RIC
Solar/Wind Helper
0.402
316468AD1-105 GEN
Solar/Wind Helper
1.246
316072AD1-144
Solar/Wind Helper
0.279
315687AD1-152 GEN
Solar/Wind Helper
1.202
316156AD2-030 GEN
Solar/Wind Helper
0.38
315785AD2-033 C
Solar/Wind Helper
2.641
316337AD2-073 GEN
Solar/Wind Helper
0.391
233968AD2-076_GEN
Solar/Wind Harmer
6.422
234012AE2-112_GEN
Solar/Wind Harmer
2.228
234014AF1-036_GEN
Solar/Wind Harmer
2.621
234015AF2-250 C
Solar/Wind Harmer
0.117
234036AF2-325 C
Solar/Wind Harmer
0.891
207522AF2-254 C
Solar/Wind Harmer
1.202
207528AF2-192 GEN
Solar/Wind Harmer
1.062
207484AF2-139 C O1
Solar/Wind Harmer
0.424
207510AF2-138 C
Solar/Wind Harmer
1.488
207518AF1-320_GEN
Solar/Wind Harmer
3.066
207442AE1-156 GEN
Solar/Wind Harmer
0.621
226929AD2-058 GEN
Solar/Wind Helper
0.119
207437AD2-070 GEN
Solar/Wind Harmer
0.253
209054AE2-059 GEN
Solar/Wind Harmer
1.322
313526AB2-022
Solar/Wind Helper
0.369
316313AB2-026
Solar/Wind Helper
0.372
207445AB1-138_GEN
Solar/Wind Harmer
0.484
209071AE2-133 GEN
Solar/Wind Harmer
1.314
209116AE2-175 GEN
Solar/Wind Harmer
3.423
209120AE2-241 GEN
Solar/Wind Harmer
2.617
209093AE2-110 GEN
Solar/Wind Harmer
1.978
3145513AHOSKIE
Solar/Wind Helper
0.231
3145513AHOSKIE
Solar/Wind Helper
0.104
233923SMA
Solar/Wind Harmer
3.556
230433AD2-135 GEN
Solar/Wind Harmer
0.087
230430AE1-229_GEN
Solar/Wind Harmer
24.623
219680HOPEWELLV C1
Solar/Wind Harmer
0.063
219686LUMSOLAR_N C
Solar/Wind Harmer
0.172
219688LUMSOLAR_S C
Solar/Wind Harmer
0.172
219908AB1-139 C
Solar/Wind Harmer
0.318
219904AC1-010 C
Solar/Wind Harmer
0.321
219906AC1-017 C
Solar/Wind Harmer
0.188
219623KINSLEYBEA C
Solar/Wind Harmer
0.364
219258KINSLEYDEP C
Solar/Wind Harmer
0.275
219304NAMERICA C
Solar/Wind Harmer
0.262
219921AF1-264
Solar/Wind Harmer
0.123
231902DC CT7
Adder
10.829
231906DC3 NUG
Adder
13.546
211065PSPA IPP
Solar/Wind Harmer
0.375
211065PSPA IPP
Solar/Wind Harmer
0.375
208862AG1-362 C
Solar/Wind Harmer
0.661
207530AG1-191 GEN
Solar/Wind Harmer
1.151
230511AF1-262
Solar/Wind Harmer
0.157
209130AF1-271A GEN
Solar/Wind Harmer
2.183
209142AF1-226 GEN
Solar/Wind Harmer
4.58
205932AD2-116_GEN
Solar/Wind Harmer
0.58
205941AD2-115 GEN
Solar/Wind Harmer
0.763
205943AE1-185 GEN
Solar/Wind Harmer
0.574
205967AE2-211_GEN
Solar/Wind Harmer
6.196
205951AE1-129_GEN
Solar/Wind Harmer
8.48
20464627HAM CT
Adder
1.901
20465427SHAW CT
Adder
3.226
20464827MOUNT CT
Adder
1.9
20464827MOUNT CT
Adder
1.958
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.888
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
209067AE2-060 GEN
Solar/Wind Harmer
1.124
209137AF2-361 C
Solar/Wind Harmer
2.171
3146206CASHIE
Solar/Wind Helper
0.232
3146206CASHIE
Solar/Wind Helper
0.232
3146206CASHIE
Solar/Wind Helper
0.232
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.137
3142666NORTHAMPTON
Solar/Wind Helper
0.229
316274AC1-208 GEN
Solar/Wind Helper
1.374
316349AD2-085 GEN
Solar/Wind Helper
1.112
3156021HOLLOMANSOL
Solar/Wind Helper
1.763
313506AB2-031 GEN
Solar/Wind Helper
1.045
316006AB2-029 C
Solar/Wind Helper
0.132
316322AB2-045
Solar/Wind Helper
0.26
316131AB2-060 GEN
Solar/Wind Helper
1.373
316192AB2-158 GEN
Solar/Wind Helper
1.757
316174AB2-169 GEN
Solar/Wind Helper
0.584
316087AB2-174 GEN
Solar/Wind Helper
1.612
316132AB2-190 GEN1
Solar/Wind Helper
1.416
316458AB2-190 GEN2
Solar/Wind Helper
1.416
316129AC1-054 GEN
Solar/Wind Helper
1.119
316210AC1-098 GEN
Solar/Wind Helper
1.823
316212AC1-099_GEN
Solar/Wind Helper
1.013
316375AC2-012 GEN
Solar/Wind Helper
0.642
316339AD2-160 GEN
Solar/Wind Helper
0.927
316164AC1-076 GEN
Solar/Wind Helper
1.284
20635028RRCT1&2
Adder
9.839
20635028RRCT1&2
Adder
9.687
20635128RRCT3&4
Adder
9.351
20635128RRCT3&4
Adder
8.157
316239AB2-077_GEN
Solar/Wind Helper
0.302
316238AB2-078_GEN
Solar/Wind Helper
0.302
316237AB2-079_GEN
Solar/Wind Helper
0.302
316140AB2-099
Solar/Wind Helper
0.088
316223AC1-118
Solar/Wind Helper
0.396
316294AC1-161 GEN
Solar/Wind Helper
4.482
315975AC1-164 GENB
Solar/Wind Helper
0.096
315976AC1-164 GENA
Solar/Wind Helper
3.236
316169AC1-164_GENC
Solar/Wind Helper
2.795
316381AD1-082 GEN
Solar/Wind Helper
1.267
316233AE1-074 FULL
Solar/Wind Helper
0.382
316236AE1-162_GEN
Solar/Wind Helper
0.33
315607AA1-063A GEN
Solar/Wind Helper
1.317
20465027TOLNA CT
Adder
2.298
20465027TOLNA CT
Adder
2.389
20465527S.RDG CT
Adder
2.202
20465527S.RDG CT
Adder
2.276
20466127PORT 5CT
Adder
22.184
20465127PORT CT
Adder
2.514
20465127PORT CT
Adder
3.337
230434AG1-499 GEN
Solar/Wind Harmer
0.497
233964AF2-378 GEN
Solar/Wind Harmer
0.124
3130546PLYMOUTH
Solar/Wind Helper
0.234
3145593CAROLNA
Solar/Wind Helper
0.228
3145593CAROLNA
Solar/Wind Helper
0.228
3145683EARLEYS
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.461
200200DELTA2 CT1
50/50
2.805
200201DELTA2 CT2
50/50
2.805
200202DELTA2 ST
50/50
4.75
207511W3-106 GEN
Solar/Wind Harmer
0.276
208972BECR K09
Solar/Wind Harmer
0.854
209029WAYMART-WD
Solar/Wind Harmer
2.083
230407AD2-065 C
Solar/Wind Harmer
0.113
232432Z2-076 GEN
Solar/Wind Harmer
0.128
232434Z2-077 GEN
Solar/Wind Harmer
0.243
233996TM1833_GEN
Solar/Wind Harmer
0.97
233997TMININ_4.2
Solar/Wind Harmer
0.97
233998TM1NIN_3.36
Solar/Wind Harmer
0.97
3130086AYDLETT
Solar/Wind Helper
0.969
3137643SOCKMAN
Solar/Wind Helper
0.915
3138216PACIFIC
Solar/Wind Helper
0.049
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.01
3142946ENON
Solar/Wind Helper
0.025
3142946ENON
Solar/Wind Helper
0.083
3144536CHRHLND
Solar/Wind Helper
0.037
3144873MCLAUGH
Solar/Wind Helper
0.006
3145783HORNRTN
Solar/Wind Helper
0.228
3145796HORNRTN
Solar/Wind Helper
0.682
3145796HORNRTN
Solar/Wind Helper
0.75
3145796HORNRTN
Solar/Wind Helper
0.227
3145796HORNRTN
Solar/Wind Helper
0.227
3145796HORNRTN
Solar/Wind Helper
0.909
3145796HORNRTN
Solar/Wind Helper
0.728
3145796HORNRTN
Solar/Wind Helper
0.091
3145823KELFORD
Solar/Wind Helper
0.229
3145823KELFORD
Solar/Wind Helper
0.229
3145893MURPHYS
Solar/Wind Helper
0.333
3145893MURPHYS
Solar/Wind Helper
0.418
3145893MURPHYS
Solar/Wind Helper
0.083
3145893MURPHYS
Solar/Wind Helper
0.232
3145893MURPHYS
Solar/Wind Helper
0.929
3145893MURPHYS
Solar/Wind Helper
0.232
3145893MURPHYS
Solar/Wind Helper
0.627
3145933PARMELE
Solar/Wind Helper
0.45
3145933PARMELE
Solar/Wind Helper
0.225
3145933PARMELE
Solar/Wind Helper
0.225
3145963POPLR C
Solar/Wind Helper
0.229
3145963POPLR C
Solar/Wind Helper
0.229
3146033SCOT NK
Solar/Wind Helper
0.908
3146043SEABORD
Solar/Wind Helper
0.231
3146173TUNIS
Solar/Wind Helper
0.231
3146173TUNIS
Solar/Wind Helper
0.231
3146173TUNIS
Solar/Wind Helper
0.231
3146173TUNIS
Solar/Wind Helper
0.231
3146263WOODLND
Solar/Wind Helper
0.23
3146263WOODLND
Solar/Wind Helper
0.23
315611Z1-036_GEN2
Solar/Wind Helper
1.309
315800Z1-036_GEN1
Solar/Wind Helper
1.309
316320Y1-086
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.368
942461AE2-259 GEN
Solar/Wind Helper
1.549
946281AF1-292 GEN
Solar/Wind Helper
0.232
946691AF1-333 GEN
Solar/Wind Harmer
0.778
946731AF1-337 GEN
Solar/Wind Harmer
0.778
946741AF1-338 GEN
Solar/Wind Harmer
0.778
946751AF1-339 GEN
Solar/Wind Harmer
0.778
959421AF2-233 GEN
Solar/Wind Harmer
0.777
959431AF2-234 GEN
Solar/Wind Harmer
1.553
959561AF2-247 GEN
Solar/Wind Harmer
0.407
961261AF2-417 GEN
Solar/Wind Harmer
0.817
961301AF2-421 GEN
Solar/Wind Harmer
0.816
961331AF2-424 GEN
Solar/Wind Harmer
0.793
961341AF2-425 GEN
Solar/Wind Harmer
0.793
961421AF2-433 GEN
Solar/Wind Harmer
0.791
961431AF2-434 GEN
Solar/Wind Harmer
0.791
961541AF2-445A GEN
Solar/Wind Harmer
2.616
961941AG1-037 GEN
Solar/Wind Helper
0.078
963071AG1-156 GEN
Solar/Wind Harmer
8.021
963151AG1-164 GEN
Solar/Wind Harmer
0.816
963161AG1-165 GEN
Solar/Wind Harmer
0.816
963391AG1-188 GEN
Solar/Wind Harmer
3.136
963401AG1-189 GEN
Solar/Wind Harmer
1.902
966871AG1-558 GEN
Solar/Wind Helper
0.343
966881AG1-559 GEN
Solar/Wind Helper
0.355
970025AG2-016 GEN
Solar/Wind Harmer
2.37
970095AG2-074 GEN
Solar/Wind Harmer
5.08
970453AG2-297 GEN
Solar/Wind Harmer
2.381
970597AG2-380 GEN
Solar/Wind Harmer
4.033
970695AG2-447 GEN
Solar/Wind Harmer
3.486
970997AG2-616 GEN
Solar/Wind Harmer
8.249
971007AG2-625 GEN
Solar/Wind Harmer
2.153
971009AG2-626 GEN
Solar/Wind Harmer
1.373
971189AH1-054 GEN
Solar/Wind Harmer
0.987
971195AH1-057 GEN
Solar/Wind Harmer
0.948
971519AH1-257 GEN
Solar/Wind Harmer
2.114
971521AH1-258 GEN
Solar/Wind Harmer
2.259
971667AH1-334 GEN
Solar/Wind Harmer
2.298
219221BRL12CT1
Adder
7.526
219222BRL12CT2
Adder
7.526
219223BRL12CT3
Adder
7.526
219224BRL12CT4
Adder
7.526
219918AC2-009 C
Solar/Wind Harmer
0.021
227287AC2-120 GEN
Solar/Wind Helper
0.415
316431W1029_GEN1
Solar/Wind Helper
0.972
316433W1029_GEN2
Solar/Wind Helper
0.972
316435W1029_GEN3
Solar/Wind Helper
0.972
924131AB2-057 GEN
Solar/Wind Harmer
0.858
957601AF2-054 GEN
Solar/Wind Helper
0.337
957831AF2-077 GEN
Solar/Wind Helper
0.336
957921AF2-086 GEN
Solar/Wind Harmer
0.769
963711AG1-223 GEN
Solar/Wind Harmer
1.236
964001AG1-254 GEN
Solar/Wind Harmer
6.266
964051AG1-259 GEN
Solar/Wind Harmer
1.041
964061AG1-260 GEN
Solar/Wind Harmer
1.041
964211AG1-282 GEN
Solar/Wind Helper
0.343
964851AG1-348 GEN
Solar/Wind Harmer
1.145
966001AG1-469 GEN
Solar/Wind Helper
0.277
966261AG1-495 GEN
Solar/Wind Harmer
2.938
966621AG1-532 GEN
Solar/Wind Helper
0.21
972141AH1-641 GEN
Solar/Wind Harmer
2.475
972177AH1-672 GEN
Solar/Wind Harmer
13.07
972221AH1-695 GEN
Adder
108.793
972233AH1-701 GEN
Adder
3.596
972237AH1-703 GEN
Adder
8.446
972251AH1-710 GEN
Adder
42.982
972275AH1-722 GEN
Adder
26.355
200917MEHOOPANY_G
Solar/Wind Harmer
3.089
972281AH1-725 GEN
50/50
137.759
233950AC2-186 GEN
Solar/Wind Harmer
0.547
233952AC2-187 GEN
Solar/Wind Harmer
1.093
233954AC2-188 GEN
Solar/Wind Harmer
1.093
972260AH1-715 GEN1
Adder
11.48
972261AH1-715 GEN2
Adder
13.365
238147AE2-230_GEN1
Solar/Wind Helper
0.422
238148AE2-230_GEN2
Solar/Wind Helper
0.422
238149AF1-291A_GEN
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.603
230422AE1-104_GEN1
Solar/Wind Harmer
28.972
230425AE1-104_GEN2
Solar/Wind Harmer
28.972
232422X3-066 FULL
Solar/Wind Harmer
0.242
234033AF1-007_GEN
Solar/Wind Harmer
36.192
316487AF1-042 GEN
Solar/Wind Helper
0.256
316484AD2-074 GEN
Solar/Wind Helper
0.489
219919AE1-041 FULL
Solar/Wind Harmer
0.034
219912AD2-042 GEN
Solar/Wind Harmer
0.675
219914AD2-027 C
Solar/Wind Harmer
0.509
207500AE2-000G1
Solar/Wind Harmer
26.357
207497AE2-000G2
Solar/Wind Harmer
26.357
207507AE2-000G3
Solar/Wind Harmer
26.357
207487AE2-000G4
Solar/Wind Harmer
26.357
217121ECCF
Adder
0.362
232910NRG_G1
Adder
8.38
G-007ALTFEXP_G-007A->PJM
CMTX
42.787
VTFLTFEXP_VFT->PJM
CMTX
113.065
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.043
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.9
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.7
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.489
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.882
CBM NorthLTFEXP_CBM-N->PJM
CBM
65.935
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-3835T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-3835T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.99 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3624.44
MW Contribution:
137.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
2.048
200053ROCKSP 2
50/50
2.008
200054ROCKSP 3
50/50
2.072
200055ROCKSP 4
50/50
2.036
200203Y1-065-STG
50/50
5.638
200204Y1-065-CTG1
50/50
3.255
200205Y1-065-CTG2
50/50
3.255
3147043LAWRENC
Solar/Wind Helper
0.137
3147133PAMPLIN
Solar/Wind Helper
0.715
3147133PAMPLIN
Solar/Wind Helper
0.182
3147133PAMPLIN
Solar/Wind Helper
0.228
20334726NME_Y1-047
Adder
2.07
20390726Y2-042
Adder
2.283
23546401DTGZ2-030
Solar/Wind Helper
0.076
20486527WR_V4-052
Adder
0.884
20628028LAKEHURS
Adder
0.793
20633028GILCT9
Adder
23.712
20635828PARLN1&2
Adder
2.791
20635828PARLN1&2
Adder
6.162
20635928PARLN3&4
Adder
2.791
20635928PARLN3&4
Adder
6.162
20636028O CRK C1
Adder
5.899
20636128O CRK C2
Adder
5.379
20714828MDF_W3-079
Solar/Wind Harmer
0.082
213497CHSTR7-9
Adder
2.328
213497CHSTR7-9
Adder
2.328
213497CHSTR7-9
Adder
2.328
213535CROYDN11
Adder
8.601
213560DLW11-12
Adder
2.297
213560DLW11-12
Adder
2.297
213561DLWR9-10
Adder
3.004
213561DLWR9-10
Adder
2.297
213587EDDYSTN3
Adder
67.984
213589EDDYSTN4
Adder
67.989
213611FALLS1-3
Adder
2.963
213611FALLS1-3
Adder
2.963
213611FALLS1-3
Adder
2.963
213815MOSER1-3
Adder
2.986
213815MOSER1-3
Adder
2.986
213815MOSER1-3
Adder
2.986
213942SCHUYLKILL
Adder
2.309
213942SCHUYLKILL
Adder
3.019
213957STHWK3-4
Adder
2.308
213957STHWK3-4
Adder
2.308
213958STHWK5-6
Adder
2.308
213958STHWK5-6
Adder
2.308
214194N WALES4
Adder
0.714
231907DC10
Adder
3.374
231917EM10
Adder
2.231
231918WEST 1
Adder
3.192
231919CHRIST1
Adder
4.197
231920CHRIST2
Adder
4.104
231940T-011
Adder
0.724
232404W1-003 C
Solar/Wind Harmer
0.627
232408W1-005 C
Solar/Wind Harmer
0.627
232410W1-006 C
Solar/Wind Harmer
0.627
232813VAUGHN
Adder
0.57
232901NORTHST
Adder
8.082
232902EASTMUNI
Adder
12.63
232904IR4
Adder
78.494
232907VN8
Adder
29.155
232912OH NUG1
Adder
8.575
232913OH NUG2
Adder
8.461
232914OH NUG3
Adder
8.575
232915OH NUG4
Adder
8.518
232916OH NUG5
Adder
8.575
232917OH NUG6
Adder
8.537
232918OH NUG7
Adder
8.518
232919VN10
Adder
2.724
232920IR10
Adder
3.068
232921TASLEY2G
Adder
5.012
232926CRISFLD1
Adder
1.906
23777901MDS_W4-102
Solar/Wind Helper
0.141
3137176SLIGO L2192
Solar/Wind Helper
0.962
3141426STAFORD
Solar/Wind Helper
0.062
3141906WESTMOR
Solar/Wind Helper
0.103
3142416OLDCHRC
Solar/Wind Helper
0.654
3142416OLDCHRC
Solar/Wind Helper
0.25
3142433PROV 92
Solar/Wind Helper
1
3142956BIRDNECK
Solar/Wind Helper
0.164
3143316POE
Solar/Wind Helper
0.966
3144356SAPONY
Solar/Wind Helper
0.428
3145506HICKORY
Solar/Wind Helper
0.97
3145506HICKORY
Solar/Wind Helper
0.582
3145506HICKORY
Solar/Wind Helper
0.145
3146386ELIZ CT
Solar/Wind Helper
0.241
3146776BUCKING
Solar/Wind Helper
0.928
3146776BUCKING
Solar/Wind Helper
0.075
3146776BUCKING
Solar/Wind Helper
0.083
3146776BUCKING
Solar/Wind Helper
0.093
209027LOR2_Q27
Solar/Wind Harmer
0
217083KRNY_132
Adder
7.69
217083KRNY_132
Adder
7.739
217086KRNY_131
Adder
7.755
217086KRNY_131
Adder
7.673
217146KRNY_1234
Adder
7.213
217146KRNY_1234
Adder
7.164
217147KRNY_1212
Adder
7.361
217147KRNY_1212
Adder
7.23
217167KRNY_14
Adder
7.739
217186ESSEX_G9
Adder
3.286
218418LINDEN_G5
Adder
14.298
218419LINDEN_G6
Adder
14.298
219035LINDEN_G8
Adder
13.726
219036LINDEN_G7
Adder
13.925
228200CARL#1CT
Adder
5.617
228201CARL#2CT
Adder
5.906
228206SHRMN CT
Adder
14.258
228251CARLLS#4
Adder
0.542
228307PCLP GT
Adder
10.356
228400MICK 1CT
Adder
10.092
235020AA1-095 C
Solar/Wind Helper
0.042
316075AC2-137 C
Solar/Wind Helper
0.383
316077AC2-138 C
Solar/Wind Helper
0.24
20462827N BANGR8
Adder
0.599
228732V1-021 C
Adder
0.163
3138133OCRAN
Solar/Wind Helper
0.075
3138133OCRAN
Solar/Wind Helper
0.151
3141766HARMONY
Solar/Wind Helper
0.05
3141783LANCAST
Solar/Wind Helper
0.151
3141783LANCAST
Solar/Wind Helper
0.101
3141813NORNECK
Solar/Wind Helper
0.255
3141913WHIT STONE
Solar/Wind Helper
0.251
3143226MDLTHAN
Solar/Wind Helper
0.249
3143873LANEXA
Solar/Wind Helper
0.15
3145273HOLLAND
Solar/Wind Helper
0.179
3146376EDENTON
Solar/Wind Helper
0.237
3146456SLIGO L269
Solar/Wind Helper
0.242
3146456SLIGO L269
Solar/Wind Helper
0.242
3146486SUNBURY
Solar/Wind Helper
0.24
3146486SUNBURY
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.239
3146516WINFALL
Solar/Wind Helper
0.239
3146516WINFALL
Solar/Wind Helper
0.776
3146516WINFALL
Solar/Wind Helper
0.239
3146516WINFALL
Solar/Wind Helper
0.239
3146516WINFALL
Solar/Wind Helper
0.239
3146626S HERTFORD
Solar/Wind Helper
0.239
3146626S HERTFORD
Solar/Wind Helper
0.239
3146626S HERTFORD
Solar/Wind Helper
0.239
3146926FARMVIL
Solar/Wind Helper
0.138
3146926FARMVIL
Solar/Wind Helper
0.138
3147666LOUISA
Solar/Wind Helper
1.041
3147666LOUISA
Solar/Wind Helper
0.599
3147983MERCK5
Solar/Wind Helper
0.09
200034PCHBTM 2
50/50
16.321
200035PCHBTM 3
50/50
16.185
232406W1-004 FULL
Solar/Wind Harmer
0.627
200192DELTA CT1
50/50
1.564
200193DELTA CT2
50/50
1.564
200194DELTA CT3
50/50
1.564
200195DELTA ST
50/50
2.416
3141726DUNNSVL
Solar/Wind Helper
1.017
3145663CRESWEL
Solar/Wind Helper
0.657
316034AC1-036 C
Solar/Wind Helper
0.237
316036AC1-147 C
Solar/Wind Helper
0.371
316059AD1-063 C
Solar/Wind Helper
0.253
316159AE1-175 C
Solar/Wind Helper
0.376
316240AF1-291 C
Solar/Wind Helper
0.333
316246AF1-032 C
Solar/Wind Helper
0.277
316258AE1-075 C
Solar/Wind Helper
0.334
316305AF2-043 C
Solar/Wind Helper
0.326
316315AB2-025 C
Solar/Wind Helper
0.365
316316AC1-027 C
Solar/Wind Helper
0.384
316317KELFORD C
Solar/Wind Helper
0.205
316382AG1-145 C
Solar/Wind Helper
0.334
316405AF2-144 C
Solar/Wind Helper
0.278
208909MACR G3
Adder
132.999
209008PAXT IPP
Adder
1.596
209010PEIP 1
Adder
2.843
209010PEIP 1
Adder
0.416
209010PEIP 1
Adder
0.517
209018SUNBIPCT
Adder
5.767
209023WIENIPP1
Adder
8.772
209025WIENIPP3
Adder
4.29
209025WIENIPP3
Adder
4.379
209026WIENIPP4
Adder
4.334
209030FRFA O01
Adder
0.191
232899W1-062
Adder
9.333
232900DEMECSMY
Adder
8.952
232905CHERITON_25
Adder
2.382
218524CNTRALGAS1 C
Solar/Wind Harmer
0.636
218526CNTRALGAS2 C
Solar/Wind Harmer
0.637
226910AB2-157 C
Solar/Wind Helper
0.017
233939AC1-091 C
Solar/Wind Harmer
1.751
233970AC1-092 C
Solar/Wind Harmer
1.751
233971AC1-093 C
Solar/Wind Harmer
1.751
233972AC1-094 C
Solar/Wind Harmer
1.751
233973AC2-185 C
Solar/Wind Harmer
1.751
212507AE2-042_GEN
Solar/Wind Harmer
0.479
3130156CHOWAN
Solar/Wind Helper
0.237
3130156CHOWAN
Solar/Wind Helper
0.237
3130156CHOWAN
Solar/Wind Helper
0.237
3145336SMITFLD
Solar/Wind Helper
0.977
3145336SMITFLD
Solar/Wind Helper
0.098
3148133STUARTS
Solar/Wind Helper
0.134
3141196NOKESVL
Solar/Wind Helper
1.13
3141873WAN 176
Solar/Wind Helper
0.05
3143526WINTERP
Solar/Wind Helper
1.298
3143526WINTERP
Solar/Wind Helper
1.298
316411AF1-147_GEN1
Solar/Wind Helper
0.977
316415AF1-147_GEN2
Solar/Wind Helper
0.977
316404AE1-155 C
Solar/Wind Helper
2.169
316017AA1-139 ULT1
Solar/Wind Helper
1.109
316018AA1-139 ULT2
Solar/Wind Helper
1.043
316181AB2-040 GEN
Solar/Wind Helper
1.646
316033AB2-134 GEN
Solar/Wind Helper
0.853
316388AE2-253 GEN
Solar/Wind Helper
0.924
205956AE1-196_GEN
Solar/Wind Harmer
0.024
3148013FISHERV
Solar/Wind Helper
0.128
3148013FISHERV
Solar/Wind Helper
0.224
3145176PASQUOTANK
Solar/Wind Helper
0.149
3132123MT JACKSON
Solar/Wind Helper
0.715
3132273ORANGE
Solar/Wind Helper
0.052
3142543TWELFTH
Solar/Wind Helper
0.024
3144303KENBRDG
Solar/Wind Helper
0.181
238175AF1-290_GEN
Solar/Wind Helper
0.138
238169AE2-226 GEN1
Solar/Wind Helper
0.616
238170AE2-226 GEN2
Solar/Wind Helper
0.616
316005AA1-067
Solar/Wind Helper
0.255
316426AA2-053 GEN
Solar/Wind Helper
1.305
316190AA2-174 GEN
Solar/Wind Helper
0.015
315614AA2-178 GEN
Solar/Wind Helper
1.434
315816AE2-034 GEN
Solar/Wind Helper
1.075
316312AB1-027
Solar/Wind Helper
0.48
316011AB1-132 GEN
Solar/Wind Helper
2.46
316369SG1_INVT
Solar/Wind Helper
1.187
315651AD1-115 GEN
Solar/Wind Helper
0.907
316023GEN1_S
Solar/Wind Helper
0.885
316365GEN2_N
Solar/Wind Helper
0.885
237061AD1-155 GEN
Solar/Wind Helper
1.511
316463AE2-346 GEN
Solar/Wind Helper
0.211
315839AE2-212 C
Solar/Wind Helper
0.331
233984AB2-036 GEN
Solar/Wind Harmer
7.033
233915AB1-141 GEN
Solar/Wind Harmer
0.246
233918AB1-142 GEN
Solar/Wind Harmer
0.246
315821AE2-092 GEN
Solar/Wind Helper
2.119
316499AE2-029_GEN
Solar/Wind Helper
0.755
315671AE2-027_GEN
Solar/Wind Helper
1.993
233930AB2-032 GEN
Solar/Wind Harmer
0.924
233987AB2-037 GEN
Solar/Wind Harmer
-0.001
315662AE1-191 GEN
Solar/Wind Helper
1.35
315666AE1-190 GEN
Solar/Wind Helper
0.338
319010AE1-072 C
Solar/Wind Helper
2.768
315697AD1-025 GEN
Solar/Wind Helper
2.817
316185AD1-033 GEN
Solar/Wind Helper
1.145
315773AC2-141 GEN
Solar/Wind Helper
5.26
316280AD1-041 GEN
Solar/Wind Helper
0.844
233935AB2-179 C
Solar/Wind Harmer
1.314
234041AC1-190 GEN
Solar/Wind Harmer
7.072
315732AD1-074 GEN1
Solar/Wind Helper
2.665
315733AD1-074 GEN2
Solar/Wind Helper
2.665
315735AD1-075 GEN1
Solar/Wind Helper
1.333
315737AD1-076 GEN
Solar/Wind Helper
2.279
316473AC1-191 GEN
Solar/Wind Helper
1.549
316478AD1-087 GEN
Solar/Wind Helper
1.113
316486AD2-202 GEN
Solar/Wind Helper
0.326
316447AC1-158 HLD
Solar/Wind Helper
3.306
316044AC1-158 PL1
Solar/Wind Helper
1.502
316045AC1-158 PL2
Solar/Wind Helper
4.808
316450AC1-158 RIC
Solar/Wind Helper
0.401
316468AD1-105 GEN
Solar/Wind Helper
1.243
316072AD1-144
Solar/Wind Helper
0.278
316156AD2-030 GEN
Solar/Wind Helper
0.379
315785AD2-033 C
Solar/Wind Helper
2.634
316337AD2-073 GEN
Solar/Wind Helper
0.39
233968AD2-076_GEN
Solar/Wind Harmer
2.247
234012AE2-112_GEN
Solar/Wind Harmer
2.247
234014AF1-036_GEN
Solar/Wind Harmer
2.247
207522AF2-254 C
Solar/Wind Harmer
0.775
207528AF2-192 GEN
Solar/Wind Harmer
0.598
207442AE1-156 GEN
Solar/Wind Harmer
0.049
226929AD2-058 GEN
Solar/Wind Helper
0.119
207437AD2-070 GEN
Solar/Wind Harmer
0.055
313526AB2-022
Solar/Wind Helper
0.368
316313AB2-026
Solar/Wind Helper
0.371
209120AE2-241 GEN
Solar/Wind Harmer
1.275
209093AE2-110 GEN
Solar/Wind Harmer
1.275
3145513AHOSKIE
Solar/Wind Helper
0.23
3145513AHOSKIE
Solar/Wind Helper
0.103
230430AE1-229_GEN
Solar/Wind Harmer
17.026
219304NAMERICA C
Solar/Wind Harmer
0.076
231902DC CT7
Adder
10.805
231906DC3 NUG
Adder
13.515
208862AG1-362 C
Solar/Wind Harmer
0.49
209130AF1-271A GEN
Solar/Wind Harmer
1.519
209142AF1-226 GEN
Solar/Wind Harmer
2.23
205932AD2-116_GEN
Solar/Wind Harmer
0.072
205941AD2-115 GEN
Solar/Wind Harmer
0.095
205943AE1-185 GEN
Solar/Wind Harmer
0.024
205967AE2-211_GEN
Solar/Wind Harmer
3.973
205951AE1-129_GEN
Solar/Wind Harmer
0.111
20465427SHAW CT
Adder
3.217
20464827MOUNT CT
Adder
1.879
20464827MOUNT CT
Adder
1.936
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.886
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3146206CASHIE
Solar/Wind Helper
0.232
3146206CASHIE
Solar/Wind Helper
0.232
3146206CASHIE
Solar/Wind Helper
0.232
3142666NORTHAMPTON
Solar/Wind Helper
0.228
3142666NORTHAMPTON
Solar/Wind Helper
0.228
3142666NORTHAMPTON
Solar/Wind Helper
0.228
3142666NORTHAMPTON
Solar/Wind Helper
0.137
3142666NORTHAMPTON
Solar/Wind Helper
0.228
316274AC1-208 GEN
Solar/Wind Helper
1.37
316349AD2-085 GEN
Solar/Wind Helper
1.109
3156021HOLLOMANSOL
Solar/Wind Helper
1.758
313506AB2-031 GEN
Solar/Wind Helper
1.042
316006AB2-029 C
Solar/Wind Helper
0.131
316322AB2-045
Solar/Wind Helper
0.259
316131AB2-060 GEN
Solar/Wind Helper
1.369
316192AB2-158 GEN
Solar/Wind Helper
1.752
316174AB2-169 GEN
Solar/Wind Helper
0.583
316087AB2-174 GEN
Solar/Wind Helper
1.607
316132AB2-190 GEN1
Solar/Wind Helper
1.413
316458AB2-190 GEN2
Solar/Wind Helper
1.413
316129AC1-054 GEN
Solar/Wind Helper
1.116
316210AC1-098 GEN
Solar/Wind Helper
1.818
316212AC1-099_GEN
Solar/Wind Helper
1.01
316375AC2-012 GEN
Solar/Wind Helper
0.64
316339AD2-160 GEN
Solar/Wind Helper
0.924
316164AC1-076 GEN
Solar/Wind Helper
1.281
20635028RRCT1&2
Adder
9.813
20635028RRCT1&2
Adder
9.662
20635128RRCT3&4
Adder
9.327
20635128RRCT3&4
Adder
8.136
316239AB2-077_GEN
Solar/Wind Helper
0.302
316238AB2-078_GEN
Solar/Wind Helper
0.302
316237AB2-079_GEN
Solar/Wind Helper
0.302
316140AB2-099
Solar/Wind Helper
0.088
316223AC1-118
Solar/Wind Helper
0.395
316294AC1-161 GEN
Solar/Wind Helper
4.47
315975AC1-164 GENB
Solar/Wind Helper
0.095
315976AC1-164 GENA
Solar/Wind Helper
3.228
316169AC1-164_GENC
Solar/Wind Helper
2.788
316381AD1-082 GEN
Solar/Wind Helper
1.264
316233AE1-074 FULL
Solar/Wind Helper
0.381
316236AE1-162_GEN
Solar/Wind Helper
0.329
315607AA1-063A GEN
Solar/Wind Helper
1.314
20465027TOLNA CT
Adder
2.278
20465027TOLNA CT
Adder
2.369
20465527S.RDG CT
Adder
2.194
20465527S.RDG CT
Adder
2.267
20466127PORT 5CT
Adder
22.122
20465127PORT CT
Adder
2.507
20465127PORT CT
Adder
3.327
3130546PLYMOUTH
Solar/Wind Helper
0.233
3145593CAROLNA
Solar/Wind Helper
0.228
3145593CAROLNA
Solar/Wind Helper
0.228
3145683EARLEYS
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.46
200200DELTA2 CT1
50/50
2.799
200201DELTA2 CT2
50/50
2.799
200202DELTA2 ST
50/50
4.74
232432Z2-076 GEN
Solar/Wind Harmer
0.013
232434Z2-077 GEN
Solar/Wind Harmer
0.04
3130086AYDLETT
Solar/Wind Helper
0.966
3137643SOCKMAN
Solar/Wind Helper
0.912
3138216PACIFIC
Solar/Wind Helper
0.049
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.01
3142946ENON
Solar/Wind Helper
0.025
3142946ENON
Solar/Wind Helper
0.083
3144536CHRHLND
Solar/Wind Helper
0.037
3144873MCLAUGH
Solar/Wind Helper
0.006
3145783HORNRTN
Solar/Wind Helper
0.227
3145796HORNRTN
Solar/Wind Helper
0.68
3145796HORNRTN
Solar/Wind Helper
0.748
3145796HORNRTN
Solar/Wind Helper
0.227
3145796HORNRTN
Solar/Wind Helper
0.227
3145796HORNRTN
Solar/Wind Helper
0.907
3145796HORNRTN
Solar/Wind Helper
0.726
3145796HORNRTN
Solar/Wind Helper
0.091
3145823KELFORD
Solar/Wind Helper
0.228
3145823KELFORD
Solar/Wind Helper
0.228
3145893MURPHYS
Solar/Wind Helper
0.332
3145893MURPHYS
Solar/Wind Helper
0.417
3145893MURPHYS
Solar/Wind Helper
0.083
3145893MURPHYS
Solar/Wind Helper
0.232
3145893MURPHYS
Solar/Wind Helper
0.927
3145893MURPHYS
Solar/Wind Helper
0.232
3145893MURPHYS
Solar/Wind Helper
0.625
3145933PARMELE
Solar/Wind Helper
0.449
3145933PARMELE
Solar/Wind Helper
0.224
3145933PARMELE
Solar/Wind Helper
0.224
3145963POPLR C
Solar/Wind Helper
0.228
3145963POPLR C
Solar/Wind Helper
0.228
3146033SCOT NK
Solar/Wind Helper
0.905
3146043SEABORD
Solar/Wind Helper
0.23
3146173TUNIS
Solar/Wind Helper
0.231
3146173TUNIS
Solar/Wind Helper
0.231
3146173TUNIS
Solar/Wind Helper
0.231
3146173TUNIS
Solar/Wind Helper
0.231
3146263WOODLND
Solar/Wind Helper
0.229
3146263WOODLND
Solar/Wind Helper
0.229
315611Z1-036_GEN2
Solar/Wind Helper
1.306
315800Z1-036_GEN1
Solar/Wind Helper
1.306
316320Y1-086
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.367
942461AE2-259 GEN
Solar/Wind Helper
1.545
946281AF1-292 GEN
Solar/Wind Helper
0.231
961541AF2-445A GEN
Solar/Wind Harmer
1.807
961941AG1-037 GEN
Solar/Wind Helper
0.078
963071AG1-156 GEN
Solar/Wind Harmer
6.123
963391AG1-188 GEN
Solar/Wind Harmer
1.527
963401AG1-189 GEN
Solar/Wind Harmer
0.938
966871AG1-558 GEN
Solar/Wind Helper
0.342
966881AG1-559 GEN
Solar/Wind Helper
0.354
970025AG2-016 GEN
Solar/Wind Harmer
1.528
970095AG2-074 GEN
Solar/Wind Harmer
4.061
970453AG2-297 GEN
Solar/Wind Harmer
2.193
970597AG2-380 GEN
Solar/Wind Harmer
4.024
970695AG2-447 GEN
Solar/Wind Harmer
2.427
970753AG2-477 GEN
Solar/Wind Harmer
0.06
970755AG2-478 GEN
Solar/Wind Harmer
0.059
970757AG2-479 GEN
Solar/Wind Harmer
0.61
970761AG2-481 GEN
Solar/Wind Harmer
0.614
970997AG2-616 GEN
Solar/Wind Harmer
6.191
971007AG2-625 GEN
Solar/Wind Harmer
1.387
971009AG2-626 GEN
Solar/Wind Harmer
0.885
971189AH1-054 GEN
Solar/Wind Harmer
0.636
971195AH1-057 GEN
Solar/Wind Harmer
0.607
971519AH1-257 GEN
Solar/Wind Harmer
1.362
971521AH1-258 GEN
Solar/Wind Harmer
1.456
971667AH1-334 GEN
Solar/Wind Harmer
1.481
219221BRL12CT1
Adder
7.507
219222BRL12CT2
Adder
7.507
219223BRL12CT3
Adder
7.507
219224BRL12CT4
Adder
7.507
227287AC2-120 GEN
Solar/Wind Helper
0.416
316431W1029_GEN1
Solar/Wind Helper
0.969
316433W1029_GEN2
Solar/Wind Helper
0.969
316435W1029_GEN3
Solar/Wind Helper
0.969
957601AF2-054 GEN
Solar/Wind Helper
0.336
957831AF2-077 GEN
Solar/Wind Helper
0.335
964001AG1-254 GEN
Solar/Wind Harmer
4.839
964211AG1-282 GEN
Solar/Wind Helper
0.343
966001AG1-469 GEN
Solar/Wind Helper
0.276
966261AG1-495 GEN
Solar/Wind Harmer
1.431
966621AG1-532 GEN
Solar/Wind Helper
0.209
972141AH1-641 GEN
Solar/Wind Harmer
1.34
972177AH1-672 GEN
Solar/Wind Harmer
9.886
972221AH1-695 GEN
Adder
108.273
972233AH1-701 GEN
Adder
3.587
972237AH1-703 GEN
Adder
8.423
972251AH1-710 GEN
Adder
42.883
972275AH1-722 GEN
Adder
26.286
200917MEHOOPANY_G
Solar/Wind Harmer
0.308
970767AG2-484 GEN
Solar/Wind Harmer
0.585
972281AH1-725 GEN
50/50
137.55
972260AH1-715 GEN1
Adder
11.449
972261AH1-715 GEN2
Adder
13.33
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238148AE2-230_GEN2
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
238152AF2-075_GEN
Solar/Wind Helper
0.602
230422AE1-104_GEN1
Solar/Wind Harmer
11.603
230425AE1-104_GEN2
Solar/Wind Harmer
11.603
232422X3-066 FULL
Solar/Wind Harmer
0.08
234033AF1-007_GEN
Solar/Wind Harmer
13.407
316487AF1-042 GEN
Solar/Wind Helper
0.255
316484AD2-074 GEN
Solar/Wind Helper
0.488
207500AE2-000G1
Solar/Wind Harmer
10.554
207497AE2-000G2
Solar/Wind Harmer
10.554
207507AE2-000G3
Solar/Wind Harmer
10.554
207487AE2-000G4
Solar/Wind Harmer
10.554
217121ECCF
Adder
0.362
232910NRG_G1
Adder
8.361
G-007ALTFEXP_G-007A->PJM
CMTX
42.674
VTFLTFEXP_VFT->PJM
CMTX
112.763
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.028
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.891
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.639
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.476
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.841
CBM NorthLTFEXP_CBM-N->PJM
CBM
65.754
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.62 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3458.01
MW Contribution:
114.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
1.686
200053ROCKSP 2
50/50
1.653
200054ROCKSP 3
50/50
1.705
200055ROCKSP 4
50/50
1.676
200203Y1-065-STG
50/50
4.64
200204Y1-065-CTG1
50/50
2.679
200205Y1-065-CTG2
50/50
2.679
20486527WR_V4-052
Adder
0.706
20628028LAKEHURS
Adder
0.647
20633028GILCT9
Adder
19.277
20634528N27_Y2-018
Solar/Wind Harmer
0.183
20635828PARLN1&2
Adder
2.275
20635828PARLN1&2
Adder
5.022
20635928PARLN3&4
Adder
2.275
20635928PARLN3&4
Adder
5.022
20636028O CRK C1
Adder
4.809
20636128O CRK C2
Adder
4.385
20641628MLH_W1-032
Solar/Wind Harmer
0.199
20671828STAW2-080
Solar/Wind Harmer
0.071
20671928W4-073
Solar/Wind Harmer
0.294
20673628F1S_V4-069
Solar/Wind Harmer
0.122
20673728F2S_V4-070
Solar/Wind Harmer
0.122
20673828FLE_V3-070
Solar/Wind Harmer
0.316
20674128FR_U2-059
Solar/Wind Harmer
0.125
20674328GAR_V4-001
Solar/Wind Harmer
0.075
20674528F3S_W2-016
Solar/Wind Harmer
0.955
20674628WNG_W3-110
Solar/Wind Harmer
0.274
20674828DL_W4-046
Solar/Wind Harmer
0.439
20674928WA_W3-044
Solar/Wind Harmer
0.327
20675128HRM_W1-127
Solar/Wind Harmer
0.116
20675428EAM_W2-061
Solar/Wind Harmer
0.128
20675528CPH_W2-050
Solar/Wind Harmer
0.389
20675728RH_W2-091
Solar/Wind Harmer
0.41
20675828AU_W4-064
Solar/Wind Harmer
0.117
20675928HOL_W4-097
Solar/Wind Harmer
0.089
20676128MHD_W3-029
Solar/Wind Harmer
0.324
20676228FRD_X1-012
Solar/Wind Harmer
0.401
20676328BVR_Y1-020
Solar/Wind Harmer
0.225
20676428JCR_X2-075
Solar/Wind Harmer
0.232
20676728BRNX1-095
Solar/Wind Harmer
0.12
20714428HOW_X1-037
Solar/Wind Harmer
0.838
20714528FRN_Y2-051
Solar/Wind Harmer
0.2
20714828MDF_W3-079
Solar/Wind Harmer
0.208
20714928UPF_X1-085
Solar/Wind Harmer
0.277
20715028HAN_X4-015
Solar/Wind Harmer
0.203
20715228NPK_W1-113
Solar/Wind Harmer
0.292
20715728PEM_W1-119
Solar/Wind Harmer
0.364
20715828PEM_W1-120
Solar/Wind Harmer
0.364
20716028EGP_W2-019
Solar/Wind Harmer
0.316
20716228APLW2-078
Solar/Wind Harmer
0.599
20716428NHV_W2-082
Solar/Wind Harmer
1.21
20716928W4-060COL
Solar/Wind Harmer
0.482
20717128DIX_Z2-102
Solar/Wind Harmer
0.899
20720428HOL_W1-112
Solar/Wind Harmer
0.235
20720528MAN_W1-024
Solar/Wind Harmer
0.172
20720628TIN_W1-124
Solar/Wind Harmer
0.675
20720728JCB_W1-129
Solar/Wind Harmer
0.203
20720828JCB_W4-025
Solar/Wind Harmer
0.308
207408W3-077 C
Solar/Wind Harmer
0.345
207439AE1-081 C O1
Solar/Wind Harmer
0.041
213497CHSTR7-9
Adder
1.892
213497CHSTR7-9
Adder
1.892
213497CHSTR7-9
Adder
1.892
213535CROYDN11
Adder
7.007
213560DLW11-12
Adder
1.869
213560DLW11-12
Adder
1.869
213561DLWR9-10
Adder
2.444
213561DLWR9-10
Adder
1.869
213587EDDYSTN3
Adder
55.24
213589EDDYSTN4
Adder
55.245
213611FALLS1-3
Adder
2.414
213611FALLS1-3
Adder
2.414
213611FALLS1-3
Adder
2.414
213815MOSER1-3
Adder
2.431
213815MOSER1-3
Adder
2.431
213815MOSER1-3
Adder
2.431
213942SCHUYLKILL
Adder
1.877
213942SCHUYLKILL
Adder
2.455
213957STHWK3-4
Adder
1.876
213957STHWK3-4
Adder
1.876
213958STHWK5-6
Adder
1.876
213958STHWK5-6
Adder
1.876
214067T20SOLAR
Solar/Wind Harmer
0.172
214194N WALES4
Adder
0.581
217206BARNGR HS C
Solar/Wind Harmer
0.021
217208PARK ELE C
Solar/Wind Harmer
0.017
217209CENTRL HS C
Solar/Wind Harmer
0.03
217211CAMDEN ST C
Solar/Wind Harmer
0.017
217213AMBOY SO C
Solar/Wind Harmer
0.086
231907DC10
Adder
2.752
231917EM10
Adder
1.817
231918WEST 1
Adder
2.599
231919CHRIST1
Adder
3.418
231920CHRIST2
Adder
3.342
231940T-011
Adder
0.591
232404W1-003 C
Solar/Wind Harmer
0.793
232408W1-005 C
Solar/Wind Harmer
0.793
232410W1-006 C
Solar/Wind Harmer
0.793
232417X3-008 C
Solar/Wind Harmer
0.891
232426Y1-080 FULL
Solar/Wind Harmer
0.151
232428Y3-058 C
Solar/Wind Harmer
0.66
232813VAUGHN
Adder
0.466
232901NORTHST
Adder
6.603
232902EASTMUNI
Adder
10.308
232904IR4
Adder
64.11
232907VN8
Adder
23.808
232912OH NUG1
Adder
7.003
232913OH NUG2
Adder
6.91
232914OH NUG3
Adder
7.003
232915OH NUG4
Adder
6.956
232916OH NUG5
Adder
7.003
232917OH NUG6
Adder
6.972
232918OH NUG7
Adder
6.956
232919VN10
Adder
2.225
232920IR10
Adder
2.506
232921TASLEY2G
Adder
4.093
232926CRISFLD1
Adder
1.556
3141426STAFORD
Solar/Wind Helper
0.053
209027LOR2_Q27
Solar/Wind Harmer
2.962
212266LOR1
Solar/Wind Harmer
0.785
217081WEATEXAS C
Solar/Wind Harmer
0.058
217083KRNY_132
Adder
6.265
217083KRNY_132
Adder
6.305
217086KRNY_131
Adder
6.318
217086KRNY_131
Adder
6.251
217146KRNY_1234
Adder
5.877
217146KRNY_1234
Adder
5.836
217147KRNY_1212
Adder
5.997
217147KRNY_1212
Adder
5.89
217167KRNY_14
Adder
6.305
217169METRODIV C
Solar/Wind Harmer
0.027
217186ESSEX_G9
Adder
2.678
217197RE CRAN C
Solar/Wind Harmer
0.364
217201HACKENSOLA C
Solar/Wind Harmer
0.05
217202FBANKSOLAR C
Solar/Wind Harmer
0.05
218418LINDEN_G5
Adder
11.65
218419LINDEN_G6
Adder
11.65
218428ETC SOLAR C
Solar/Wind Harmer
0.024
218438BLK ROCK C
Solar/Wind Harmer
0.092
218440SUMMTASSOC C
Solar/Wind Harmer
0.087
218449LINSOLAR C
Solar/Wind Harmer
0.682
218660EHAMPSOLAR C
Solar/Wind Harmer
0.121
219035LINDEN_G8
Adder
11.184
219036LINDEN_G7
Adder
11.346
219114HARTZY_C
Solar/Wind Harmer
0.567
219137THOSOLAR C
Solar/Wind Harmer
0.839
219236SOUTHERNHQ C
Solar/Wind Harmer
0.047
219249CENTRALDIV C
Solar/Wind Harmer
0.027
219272CLEANLIGHT C
Solar/Wind Harmer
0.126
219276PARKLANDSO C
Solar/Wind Harmer
0.313
219287REEVESEAST C
Solar/Wind Harmer
0.928
219291REEVESSOUT C
Solar/Wind Harmer
0.041
219348LDSOLAR C
Solar/Wind Harmer
0.41
219607WPEMNERT C
Solar/Wind Harmer
0.287
219610FLORENCE C
Solar/Wind Harmer
0.949
219612MATRIX C
Solar/Wind Harmer
0.125
219615MILLCREEK C
Solar/Wind Harmer
0.164
219620RIDERU C
Solar/Wind Harmer
0.038
219766PARADISE C
Solar/Wind Harmer
0.217
219817TRENTONSOL C
Solar/Wind Harmer
0.748
227927V4-067C
Solar/Wind Harmer
0.138
228200CARL#1CT
Adder
4.582
228201CARL#2CT
Adder
4.817
228206SHRMN CT
Adder
11.633
228251CARLLS#4
Adder
0.442
228260V4-054C
Solar/Wind Harmer
0.719
228307PCLP GT
Adder
8.443
228400MICK 1CT
Adder
8.225
228711V2-041C
Solar/Wind Harmer
0.421
20462827N BANGR8
Adder
0.487
228728W1-130C
Solar/Wind Harmer
0.464
228729W2-030 C
Solar/Wind Harmer
0.403
228732V1-021 C
Adder
0.133
200034PCHBTM 2
50/50
13.449
200035PCHBTM 3
50/50
13.333
232406W1-004 FULL
Solar/Wind Harmer
0.793
232436AB1-176 C
Solar/Wind Harmer
0.18
200192DELTA CT1
50/50
1.289
200193DELTA CT2
50/50
1.289
200194DELTA CT3
50/50
1.289
200195DELTA ST
50/50
1.991
217194REDH C
Solar/Wind Harmer
0.334
230415AB2-049 C
Solar/Wind Harmer
0.132
20742028HF_AC1-207
Solar/Wind Harmer
0.532
207454AA2-184 E
Solar/Wind Harmer
0.678
207459AE1-142 C O1
Solar/Wind Harmer
0.717
207471AF2-354 C
Solar/Wind Harmer
0.348
208909MACR G3
Adder
108.247
209008PAXT IPP
Adder
1.271
209010PEIP 1
Adder
2.322
209010PEIP 1
Adder
0.34
209010PEIP 1
Adder
0.422
209018SUNBIPCT
Adder
4.709
209023WIENIPP1
Adder
7.154
209025WIENIPP3
Adder
3.499
209025WIENIPP3
Adder
3.571
209026WIENIPP4
Adder
3.535
232424Y1-079 C
Solar/Wind Harmer
0.444
232899W1-062
Adder
7.624
232900DEMECSMY
Adder
7.313
232905CHERITON_25
Adder
1.945
218524CNTRALGAS1 C
Solar/Wind Harmer
0.251
218526CNTRALGAS2 C
Solar/Wind Harmer
0.251
226910AB2-157 C
Solar/Wind Helper
0.021
233901CHERRYDALE C
Solar/Wind Harmer
0.892
233939AC1-091 C
Solar/Wind Harmer
2.126
233940AF2-379 C
Solar/Wind Harmer
0.148
233970AC1-092 C
Solar/Wind Harmer
2.126
233971AC1-093 C
Solar/Wind Harmer
2.019
233972AC1-094 C
Solar/Wind Harmer
1.708
233973AC2-185 C
Solar/Wind Harmer
4.296
212507AE2-042_GEN
Solar/Wind Harmer
1.907
219727YARDVSOLFA C
Solar/Wind Harmer
0.619
219907AC1-030 C
Solar/Wind Harmer
0.095
3141196NOKESVL
Solar/Wind Helper
0.919
316411AF1-147_GEN1
Solar/Wind Helper
0.781
316415AF1-147_GEN2
Solar/Wind Helper
0.781
228754AB1-001 C
Solar/Wind Harmer
0.097
228351V2-046C
Solar/Wind Harmer
1.409
217204WCALDSOLAR C
Solar/Wind Harmer
0.05
233944AB2-135 GEN
Solar/Wind Harmer
4.119
233946AB2-136 GEN
Solar/Wind Harmer
3.159
233994AC2-023 GEN
Solar/Wind Harmer
2.128
233984AB2-036 GEN
Solar/Wind Harmer
9.832
233982AB2-133 GEN
Solar/Wind Harmer
3.828
233915AB1-141 GEN
Solar/Wind Harmer
0.778
233918AB1-142 GEN
Solar/Wind Harmer
0.778
233930AB2-032 GEN
Solar/Wind Harmer
0.655
233987AB2-037 GEN
Solar/Wind Harmer
9.02
233933AB2-153 GEN
Solar/Wind Harmer
0.884
233955AB2-172 GEN
Solar/Wind Harmer
3.959
233935AB2-179 C
Solar/Wind Harmer
1.945
234041AC1-190 GEN
Solar/Wind Harmer
7.094
316447AC1-158 HLD
Solar/Wind Helper
2.738
316044AC1-158 PL1
Solar/Wind Helper
1.244
316045AC1-158 PL2
Solar/Wind Helper
3.981
316450AC1-158 RIC
Solar/Wind Helper
0.332
233968AD2-076_GEN
Solar/Wind Harmer
5.226
234012AE2-112_GEN
Solar/Wind Harmer
1.813
234014AF1-036_GEN
Solar/Wind Harmer
2.133
234015AF2-250 C
Solar/Wind Harmer
0.095
234036AF2-325 C
Solar/Wind Harmer
0.726
207522AF2-254 C
Solar/Wind Harmer
0.977
207528AF2-192 GEN
Solar/Wind Harmer
0.862
207484AF2-139 C O1
Solar/Wind Harmer
0.344
207510AF2-138 C
Solar/Wind Harmer
1.208
207518AF1-320_GEN
Solar/Wind Harmer
2.488
207442AE1-156 GEN
Solar/Wind Harmer
0.504
226929AD2-058 GEN
Solar/Wind Helper
0.143
207437AD2-070 GEN
Solar/Wind Harmer
0.205
209054AE2-059 GEN
Solar/Wind Harmer
1.076
207445AB1-138_GEN
Solar/Wind Harmer
0.394
209071AE2-133 GEN
Solar/Wind Harmer
1.07
209116AE2-175 GEN
Solar/Wind Harmer
2.78
209120AE2-241 GEN
Solar/Wind Harmer
2.13
209093AE2-110 GEN
Solar/Wind Harmer
1.61
233923SMA
Solar/Wind Harmer
2.897
230433AD2-135 GEN
Solar/Wind Harmer
0.071
230430AE1-229_GEN
Solar/Wind Harmer
20.033
219680HOPEWELLV C1
Solar/Wind Harmer
0.052
219686LUMSOLAR_N C
Solar/Wind Harmer
0.14
219688LUMSOLAR_S C
Solar/Wind Harmer
0.14
219908AB1-139 C
Solar/Wind Harmer
0.258
219904AC1-010 C
Solar/Wind Harmer
0.261
219906AC1-017 C
Solar/Wind Harmer
0.153
219623KINSLEYBEA C
Solar/Wind Harmer
0.296
219258KINSLEYDEP C
Solar/Wind Harmer
0.224
219304NAMERICA C
Solar/Wind Harmer
0.213
219921AF1-264
Solar/Wind Harmer
0.1
231902DC CT7
Adder
8.813
231906DC3 NUG
Adder
11.024
211065PSPA IPP
Solar/Wind Harmer
0.305
211065PSPA IPP
Solar/Wind Harmer
0.305
208862AG1-362 C
Solar/Wind Harmer
0.523
207530AG1-191 GEN
Solar/Wind Harmer
0.935
230511AF1-262
Solar/Wind Harmer
0.128
209130AF1-271A GEN
Solar/Wind Harmer
1.778
209142AF1-226 GEN
Solar/Wind Harmer
3.728
205941AD2-115 GEN
Solar/Wind Harmer
0.611
20465427SHAW CT
Adder
2.62
209067AE2-060 GEN
Solar/Wind Harmer
0.909
209137AF2-361 C
Solar/Wind Harmer
1.757
316006AB2-029 C
Solar/Wind Helper
0.107
20635028RRCT1&2
Adder
7.997
20635028RRCT1&2
Adder
7.874
20635128RRCT3&4
Adder
7.6
20635128RRCT3&4
Adder
6.63
20465527S.RDG CT
Adder
1.753
20465527S.RDG CT
Adder
1.811
20466127PORT 5CT
Adder
18.01
20465127PORT CT
Adder
2.041
20465127PORT CT
Adder
2.708
230434AG1-499 GEN
Solar/Wind Harmer
0.404
233964AF2-378 GEN
Solar/Wind Harmer
0.101
200200DELTA2 CT1
50/50
2.307
200201DELTA2 CT2
50/50
2.307
200202DELTA2 ST
50/50
3.907
207511W3-106 GEN
Solar/Wind Harmer
0.224
208972BECR K09
Solar/Wind Harmer
0.695
209029WAYMART-WD
Solar/Wind Harmer
1.696
230407AD2-065 C
Solar/Wind Harmer
0.092
232432Z2-076 GEN
Solar/Wind Harmer
0.105
232434Z2-077 GEN
Solar/Wind Harmer
0.198
233996TM1833_GEN
Solar/Wind Harmer
0.79
233997TMININ_4.2
Solar/Wind Harmer
0.79
233998TM1NIN_3.36
Solar/Wind Harmer
0.79
3138216PACIFIC
Solar/Wind Helper
0.039
946691AF1-333 GEN
Solar/Wind Harmer
0.633
946731AF1-337 GEN
Solar/Wind Harmer
0.633
946741AF1-338 GEN
Solar/Wind Harmer
0.633
946751AF1-339 GEN
Solar/Wind Harmer
0.633
959421AF2-233 GEN
Solar/Wind Harmer
0.632
959431AF2-234 GEN
Solar/Wind Harmer
1.264
959561AF2-247 GEN
Solar/Wind Harmer
0.331
961261AF2-417 GEN
Solar/Wind Harmer
0.665
961301AF2-421 GEN
Solar/Wind Harmer
0.663
961331AF2-424 GEN
Solar/Wind Harmer
0.645
961341AF2-425 GEN
Solar/Wind Harmer
0.645
961421AF2-433 GEN
Solar/Wind Harmer
0.644
961431AF2-434 GEN
Solar/Wind Harmer
0.644
961541AF2-445A GEN
Solar/Wind Harmer
2.128
963071AG1-156 GEN
Solar/Wind Harmer
6.527
963151AG1-164 GEN
Solar/Wind Harmer
0.663
963161AG1-165 GEN
Solar/Wind Harmer
0.663
963391AG1-188 GEN
Solar/Wind Harmer
2.55
963401AG1-189 GEN
Solar/Wind Harmer
1.547
970025AG2-016 GEN
Solar/Wind Harmer
1.927
970095AG2-074 GEN
Solar/Wind Harmer
4.134
970453AG2-297 GEN
Solar/Wind Harmer
1.938
970597AG2-380 GEN
Solar/Wind Harmer
3.282
970695AG2-447 GEN
Solar/Wind Harmer
2.842
970997AG2-616 GEN
Solar/Wind Harmer
6.712
971007AG2-625 GEN
Solar/Wind Harmer
1.747
971009AG2-626 GEN
Solar/Wind Harmer
1.114
971189AH1-054 GEN
Solar/Wind Harmer
0.803
971195AH1-057 GEN
Solar/Wind Harmer
0.773
971519AH1-257 GEN
Solar/Wind Harmer
1.715
971521AH1-258 GEN
Solar/Wind Harmer
1.837
971667AH1-334 GEN
Solar/Wind Harmer
1.868
219221BRL12CT1
Adder
6.116
219222BRL12CT2
Adder
6.116
219223BRL12CT3
Adder
6.116
219224BRL12CT4
Adder
6.116
219918AC2-009 C
Solar/Wind Harmer
0.017
227287AC2-120 GEN
Solar/Wind Helper
0.516
924131AB2-057 GEN
Solar/Wind Harmer
0.698
957921AF2-086 GEN
Solar/Wind Harmer
0.626
963711AG1-223 GEN
Solar/Wind Harmer
1.005
964001AG1-254 GEN
Solar/Wind Harmer
5.098
964051AG1-259 GEN
Solar/Wind Harmer
0.848
964061AG1-260 GEN
Solar/Wind Harmer
0.848
964851AG1-348 GEN
Solar/Wind Harmer
0.929
966261AG1-495 GEN
Solar/Wind Harmer
2.384
972141AH1-641 GEN
Solar/Wind Harmer
2.013
972177AH1-672 GEN
Solar/Wind Harmer
10.65
972221AH1-695 GEN
Adder
86.06
972233AH1-701 GEN
Adder
2.923
972237AH1-703 GEN
Adder
6.863
972251AH1-710 GEN
Adder
35.054
972275AH1-722 GEN
Adder
21.418
972281AH1-725 GEN
50/50
114.199
233950AC2-186 GEN
Solar/Wind Harmer
0.445
233952AC2-187 GEN
Solar/Wind Harmer
0.891
233954AC2-188 GEN
Solar/Wind Harmer
0.891
972260AH1-715 GEN1
Adder
9.329
972261AH1-715 GEN2
Adder
10.861
230422AE1-104_GEN1
Solar/Wind Harmer
23.58
230425AE1-104_GEN2
Solar/Wind Harmer
23.58
232422X3-066 FULL
Solar/Wind Harmer
0.197
234033AF1-007_GEN
Solar/Wind Harmer
29.492
219919AE1-041 FULL
Solar/Wind Harmer
0.027
219912AD2-042 GEN
Solar/Wind Harmer
0.549
219914AD2-027 C
Solar/Wind Harmer
0.414
207500AE2-000G1
Solar/Wind Harmer
21.434
207497AE2-000G2
Solar/Wind Harmer
21.434
207507AE2-000G3
Solar/Wind Harmer
21.434
207487AE2-000G4
Solar/Wind Harmer
21.434
217121ECCF
Adder
0.295
232910NRG_G1
Adder
6.825
G-007ALTFEXP_G-007A->PJM
CMTX
34.775
VTFLTFEXP_VFT->PJM
CMTX
91.873
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.03
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.296
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.653
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.624
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
54.028
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.85 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3217.41
MW Contribution:
140.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
2.111
200053ROCKSP 2
50/50
2.07
200054ROCKSP 3
50/50
2.135
200055ROCKSP 4
50/50
2.099
200203Y1-065-STG
50/50
5.811
200204Y1-065-CTG1
50/50
3.355
200205Y1-065-CTG2
50/50
3.355
20486527WR_V4-052
Adder
0.577
20628028LAKEHURS
Adder
0.671
20633028GILCT9
Adder
17.75
20634528N27_Y2-018
Solar/Wind Harmer
0.17
20635828PARLN1&2
Adder
2.283
20635828PARLN1&2
Adder
5.042
20635928PARLN3&4
Adder
2.283
20635928PARLN3&4
Adder
5.042
20636028O CRK C1
Adder
5.027
20636128O CRK C2
Adder
4.583
20641628MLH_W1-032
Solar/Wind Harmer
0.203
20671828STAW2-080
Solar/Wind Harmer
0.069
20671928W4-073
Solar/Wind Harmer
0.271
20673628F1S_V4-069
Solar/Wind Harmer
0.12
20673728F2S_V4-070
Solar/Wind Harmer
0.12
20673828FLE_V3-070
Solar/Wind Harmer
0.313
20674128FR_U2-059
Solar/Wind Harmer
0.115
20674328GAR_V4-001
Solar/Wind Harmer
0.071
20674528F3S_W2-016
Solar/Wind Harmer
0.928
20674628WNG_W3-110
Solar/Wind Harmer
0.259
20674828DL_W4-046
Solar/Wind Harmer
0.411
20674928WA_W3-044
Solar/Wind Harmer
0.306
20675128HRM_W1-127
Solar/Wind Harmer
0.107
20675428EAM_W2-061
Solar/Wind Harmer
0.126
20675528CPH_W2-050
Solar/Wind Harmer
0.387
20675728RH_W2-091
Solar/Wind Harmer
0.38
20675828AU_W4-064
Solar/Wind Harmer
0.111
20675928HOL_W4-097
Solar/Wind Harmer
0.082
20676128MHD_W3-029
Solar/Wind Harmer
0.319
20676228FRD_X1-012
Solar/Wind Harmer
0.38
20676328BVR_Y1-020
Solar/Wind Harmer
0.213
20676428JCR_X2-075
Solar/Wind Harmer
0.228
20676728BRNX1-095
Solar/Wind Harmer
0.115
20714428HOW_X1-037
Solar/Wind Harmer
0.857
20714528FRN_Y2-051
Solar/Wind Harmer
0.206
20714828MDF_W3-079
Solar/Wind Harmer
0.214
20714928UPF_X1-085
Solar/Wind Harmer
0.288
20715028HAN_X4-015
Solar/Wind Harmer
0.213
20715228NPK_W1-113
Solar/Wind Harmer
0.297
20715728PEM_W1-119
Solar/Wind Harmer
0.381
20715828PEM_W1-120
Solar/Wind Harmer
0.381
20716028EGP_W2-019
Solar/Wind Harmer
0.331
20716228APLW2-078
Solar/Wind Harmer
0.611
20716428NHV_W2-082
Solar/Wind Harmer
1.269
20716928W4-060COL
Solar/Wind Harmer
0.487
20717128DIX_Z2-102
Solar/Wind Harmer
0.941
20720428HOL_W1-112
Solar/Wind Harmer
0.238
20720528MAN_W1-024
Solar/Wind Harmer
0.176
20720628TIN_W1-124
Solar/Wind Harmer
0.689
20720728JCB_W1-129
Solar/Wind Harmer
0.213
20720828JCB_W4-025
Solar/Wind Harmer
0.323
207408W3-077 C
Solar/Wind Harmer
0.319
207439AE1-081 C O1
Solar/Wind Harmer
0.039
213497CHSTR7-9
Adder
2.092
213497CHSTR7-9
Adder
2.092
213497CHSTR7-9
Adder
2.092
213535CROYDN11
Adder
7.454
213560DLW11-12
Adder
2.015
213560DLW11-12
Adder
2.015
213561DLWR9-10
Adder
2.635
213561DLWR9-10
Adder
2.015
213587EDDYSTN3
Adder
61.027
213589EDDYSTN4
Adder
61.041
213611FALLS1-3
Adder
2.544
213611FALLS1-3
Adder
2.544
213611FALLS1-3
Adder
2.544
213815MOSER1-3
Adder
2.587
213815MOSER1-3
Adder
2.587
213815MOSER1-3
Adder
2.587
213942SCHUYLKILL
Adder
2.047
213942SCHUYLKILL
Adder
2.677
213957STHWK3-4
Adder
2.044
213957STHWK3-4
Adder
2.044
213958STHWK5-6
Adder
2.044
213958STHWK5-6
Adder
2.044
214067T20SOLAR
Solar/Wind Harmer
0.182
214194N WALES4
Adder
0.609
217206BARNGR HS C
Solar/Wind Harmer
0.02
217208PARK ELE C
Solar/Wind Harmer
0.017
217209CENTRL HS C
Solar/Wind Harmer
0.03
217211CAMDEN ST C
Solar/Wind Harmer
0.016
217213AMBOY SO C
Solar/Wind Harmer
0.085
231907DC10
Adder
3.209
231917EM10
Adder
2.089
231918WEST 1
Adder
3.001
231919CHRIST1
Adder
3.943
231920CHRIST2
Adder
3.855
231940T-011
Adder
0.689
232404W1-003 C
Solar/Wind Harmer
0.924
232408W1-005 C
Solar/Wind Harmer
0.924
232410W1-006 C
Solar/Wind Harmer
0.924
232417X3-008 C
Solar/Wind Harmer
1.039
232426Y1-080 FULL
Solar/Wind Harmer
0.177
232428Y3-058 C
Solar/Wind Harmer
0.77
232813VAUGHN
Adder
0.543
232901NORTHST
Adder
7.688
232902EASTMUNI
Adder
12.032
232904IR4
Adder
74.738
232907VN8
Adder
27.777
232912OH NUG1
Adder
8.167
232913OH NUG2
Adder
8.058
232914OH NUG3
Adder
8.167
232915OH NUG4
Adder
8.113
232916OH NUG5
Adder
8.167
232917OH NUG6
Adder
8.131
232918OH NUG7
Adder
8.113
232919VN10
Adder
2.595
232920IR10
Adder
2.921
232921TASLEY2G
Adder
4.773
232926CRISFLD1
Adder
1.815
3141426STAFORD
Solar/Wind Helper
0.05
209027LOR2_Q27
Solar/Wind Harmer
2.477
212266LOR1
Solar/Wind Harmer
0.656
217081WEATEXAS C
Solar/Wind Harmer
0.057
217083KRNY_132
Adder
6.116
217083KRNY_132
Adder
6.155
217086KRNY_131
Adder
6.168
217086KRNY_131
Adder
6.103
217146KRNY_1234
Adder
5.737
217146KRNY_1234
Adder
5.697
217147KRNY_1212
Adder
5.854
217147KRNY_1212
Adder
5.75
217167KRNY_14
Adder
6.155
217169METRODIV C
Solar/Wind Harmer
0.026
217186ESSEX_G9
Adder
2.614
217197RE CRAN C
Solar/Wind Harmer
0.368
217201HACKENSOLA C
Solar/Wind Harmer
0.049
217202FBANKSOLAR C
Solar/Wind Harmer
0.049
218418LINDEN_G5
Adder
11.534
218419LINDEN_G6
Adder
11.534
218428ETC SOLAR C
Solar/Wind Harmer
0.024
218438BLK ROCK C
Solar/Wind Harmer
0.093
218440SUMMTASSOC C
Solar/Wind Harmer
0.086
218449LINSOLAR C
Solar/Wind Harmer
0.672
218660EHAMPSOLAR C
Solar/Wind Harmer
0.13
219035LINDEN_G8
Adder
11.018
219036LINDEN_G7
Adder
11.177
219114HARTZY_C
Solar/Wind Harmer
0.59
219137THOSOLAR C
Solar/Wind Harmer
0.911
219236SOUTHERNHQ C
Solar/Wind Harmer
0.05
219249CENTRALDIV C
Solar/Wind Harmer
0.027
219272CLEANLIGHT C
Solar/Wind Harmer
0.136
219276PARKLANDSO C
Solar/Wind Harmer
0.323
219287REEVESEAST C
Solar/Wind Harmer
0.998
219291REEVESSOUT C
Solar/Wind Harmer
0.045
219348LDSOLAR C
Solar/Wind Harmer
0.436
219607WPEMNERT C
Solar/Wind Harmer
0.305
219610FLORENCE C
Solar/Wind Harmer
1.01
219612MATRIX C
Solar/Wind Harmer
0.126
219615MILLCREEK C
Solar/Wind Harmer
0.175
219620RIDERU C
Solar/Wind Harmer
0.039
219766PARADISE C
Solar/Wind Harmer
0.235
219817TRENTONSOL C
Solar/Wind Harmer
0.767
227927V4-067C
Solar/Wind Harmer
0.151
228200CARL#1CT
Adder
5.032
228201CARL#2CT
Adder
5.291
228206SHRMN CT
Adder
12.794
228251CARLLS#4
Adder
0.485
228260V4-054C
Solar/Wind Harmer
0.79
228307PCLP GT
Adder
9.242
228400MICK 1CT
Adder
8.978
228711V2-041C
Solar/Wind Harmer
0.464
20462827N BANGR8
Adder
0.448
228728W1-130C
Solar/Wind Harmer
0.507
228729W2-030 C
Solar/Wind Harmer
0.439
228732V1-021 C
Adder
0.146
200034PCHBTM 2
50/50
17.072
200035PCHBTM 3
50/50
16.97
232406W1-004 FULL
Solar/Wind Harmer
0.924
232436AB1-176 C
Solar/Wind Harmer
0.211
200192DELTA CT1
50/50
1.637
200193DELTA CT2
50/50
1.637
200194DELTA CT3
50/50
1.637
200195DELTA ST
50/50
2.528
217194REDH C
Solar/Wind Harmer
0.326
230415AB2-049 C
Solar/Wind Harmer
0.145
20742028HF_AC1-207
Solar/Wind Harmer
0.541
207454AA2-184 E
Solar/Wind Harmer
0.692
207459AE1-142 C O1
Solar/Wind Harmer
0.745
207471AF2-354 C
Solar/Wind Harmer
0.325
208909MACR G3
Adder
98.632
209010PEIP 1
Adder
2.034
209010PEIP 1
Adder
0.298
209010PEIP 1
Adder
0.37
209023WIENIPP1
Adder
6.173
209025WIENIPP3
Adder
3.019
209025WIENIPP3
Adder
3.081
209026WIENIPP4
Adder
3.05
232424Y1-079 C
Solar/Wind Harmer
0.518
232899W1-062
Adder
8.876
232900DEMECSMY
Adder
8.514
232905CHERITON_25
Adder
2.269
218524CNTRALGAS1 C
Solar/Wind Harmer
0.25
218526CNTRALGAS2 C
Solar/Wind Harmer
0.25
226910AB2-157 C
Solar/Wind Helper
0.014
233901CHERRYDALE C
Solar/Wind Harmer
1.04
233939AC1-091 C
Solar/Wind Harmer
2.474
233940AF2-379 C
Solar/Wind Harmer
0.172
233970AC1-092 C
Solar/Wind Harmer
2.474
233971AC1-093 C
Solar/Wind Harmer
2.35
233972AC1-094 C
Solar/Wind Harmer
1.987
233973AC2-185 C
Solar/Wind Harmer
4.999
219727YARDVSOLFA C
Solar/Wind Harmer
0.641
219907AC1-030 C
Solar/Wind Harmer
0.103
3141196NOKESVL
Solar/Wind Helper
0.901
316411AF1-147_GEN1
Solar/Wind Helper
0.776
316415AF1-147_GEN2
Solar/Wind Helper
0.776
228754AB1-001 C
Solar/Wind Harmer
0.106
228351V2-046C
Solar/Wind Harmer
1.545
217204WCALDSOLAR C
Solar/Wind Harmer
0.048
233944AB2-135 GEN
Solar/Wind Harmer
4.805
233946AB2-136 GEN
Solar/Wind Harmer
3.686
233994AC2-023 GEN
Solar/Wind Harmer
2.482
233984AB2-036 GEN
Solar/Wind Harmer
11.477
233982AB2-133 GEN
Solar/Wind Harmer
4.466
233915AB1-141 GEN
Solar/Wind Harmer
0.908
233918AB1-142 GEN
Solar/Wind Harmer
0.908
233930AB2-032 GEN
Solar/Wind Harmer
0.764
233987AB2-037 GEN
Solar/Wind Harmer
10.537
233933AB2-153 GEN
Solar/Wind Harmer
1.032
233955AB2-172 GEN
Solar/Wind Harmer
4.62
233935AB2-179 C
Solar/Wind Harmer
2.269
234041AC1-190 GEN
Solar/Wind Harmer
8.277
233968AD2-076_GEN
Solar/Wind Harmer
6.099
234012AE2-112_GEN
Solar/Wind Harmer
2.116
234014AF1-036_GEN
Solar/Wind Harmer
2.489
234015AF2-250 C
Solar/Wind Harmer
0.111
234036AF2-325 C
Solar/Wind Harmer
0.847
207522AF2-254 C
Solar/Wind Harmer
1.024
207528AF2-192 GEN
Solar/Wind Harmer
0.85
207484AF2-139 C O1
Solar/Wind Harmer
0.318
207510AF2-138 C
Solar/Wind Harmer
1.145
207518AF1-320_GEN
Solar/Wind Harmer
2.303
207442AE1-156 GEN
Solar/Wind Harmer
0.497
226929AD2-058 GEN
Solar/Wind Helper
0.102
207437AD2-070 GEN
Solar/Wind Harmer
0.19
207445AB1-138_GEN
Solar/Wind Harmer
0.409
209116AE2-175 GEN
Solar/Wind Harmer
2.506
209120AE2-241 GEN
Solar/Wind Harmer
1.764
209093AE2-110 GEN
Solar/Wind Harmer
1.334
233923SMA
Solar/Wind Harmer
3.379
230433AD2-135 GEN
Solar/Wind Harmer
0.077
230430AE1-229_GEN
Solar/Wind Harmer
21.968
219680HOPEWELLV C1
Solar/Wind Harmer
0.053
219686LUMSOLAR_N C
Solar/Wind Harmer
0.15
219688LUMSOLAR_S C
Solar/Wind Harmer
0.15
219908AB1-139 C
Solar/Wind Harmer
0.257
219904AC1-010 C
Solar/Wind Harmer
0.282
219906AC1-017 C
Solar/Wind Harmer
0.163
219623KINSLEYBEA C
Solar/Wind Harmer
0.32
219258KINSLEYDEP C
Solar/Wind Harmer
0.242
219304NAMERICA C
Solar/Wind Harmer
0.226
219921AF1-264
Solar/Wind Harmer
0.108
231902DC CT7
Adder
10.276
231906DC3 NUG
Adder
12.854
211065PSPA IPP
Solar/Wind Harmer
0.271
211065PSPA IPP
Solar/Wind Harmer
0.271
207530AG1-191 GEN
Solar/Wind Harmer
0.884
230511AF1-262
Solar/Wind Harmer
0.14
209142AF1-226 GEN
Solar/Wind Harmer
3.088
205941AD2-115 GEN
Solar/Wind Harmer
0.512
20465427SHAW CT
Adder
2.407
20635028RRCT1&2
Adder
8.004
20635028RRCT1&2
Adder
7.881
20635128RRCT3&4
Adder
7.607
20635128RRCT3&4
Adder
6.636
20465527S.RDG CT
Adder
1.43
20465527S.RDG CT
Adder
1.478
20466127PORT 5CT
Adder
16.611
20465127PORT CT
Adder
1.882
20465127PORT CT
Adder
2.498
230434AG1-499 GEN
Solar/Wind Harmer
0.442
233964AF2-378 GEN
Solar/Wind Harmer
0.118
200200DELTA2 CT1
50/50
2.929
200201DELTA2 CT2
50/50
2.929
200202DELTA2 ST
50/50
4.96
207511W3-106 GEN
Solar/Wind Harmer
0.212
208972BECR K09
Solar/Wind Harmer
0.599
209029WAYMART-WD
Solar/Wind Harmer
1.486
230407AD2-065 C
Solar/Wind Harmer
0.1
232432Z2-076 GEN
Solar/Wind Harmer
0.122
232434Z2-077 GEN
Solar/Wind Harmer
0.231
233996TM1833_GEN
Solar/Wind Harmer
0.922
233997TMININ_4.2
Solar/Wind Harmer
0.922
233998TM1NIN_3.36
Solar/Wind Harmer
0.922
3138216PACIFIC
Solar/Wind Helper
0.039
959561AF2-247 GEN
Solar/Wind Harmer
0.348
961261AF2-417 GEN
Solar/Wind Harmer
0.59
961301AF2-421 GEN
Solar/Wind Harmer
0.572
961331AF2-424 GEN
Solar/Wind Harmer
0.535
961341AF2-425 GEN
Solar/Wind Harmer
0.535
961421AF2-433 GEN
Solar/Wind Harmer
0.533
961431AF2-434 GEN
Solar/Wind Harmer
0.533
961541AF2-445A GEN
Solar/Wind Harmer
1.779
963071AG1-156 GEN
Solar/Wind Harmer
5.669
963151AG1-164 GEN
Solar/Wind Harmer
0.572
963161AG1-165 GEN
Solar/Wind Harmer
0.572
963391AG1-188 GEN
Solar/Wind Harmer
2.657
963401AG1-189 GEN
Solar/Wind Harmer
1.614
970025AG2-016 GEN
Solar/Wind Harmer
2.009
970095AG2-074 GEN
Solar/Wind Harmer
3.59
970453AG2-297 GEN
Solar/Wind Harmer
2.136
970597AG2-380 GEN
Solar/Wind Harmer
3.83
970695AG2-447 GEN
Solar/Wind Harmer
3.307
970997AG2-616 GEN
Solar/Wind Harmer
7.363
971007AG2-625 GEN
Solar/Wind Harmer
1.627
971009AG2-626 GEN
Solar/Wind Harmer
1.038
971189AH1-054 GEN
Solar/Wind Harmer
0.836
971195AH1-057 GEN
Solar/Wind Harmer
0.901
971519AH1-257 GEN
Solar/Wind Harmer
1.596
971521AH1-258 GEN
Solar/Wind Harmer
1.866
971667AH1-334 GEN
Solar/Wind Harmer
1.941
219221BRL12CT1
Adder
6.508
219222BRL12CT2
Adder
6.508
219223BRL12CT3
Adder
6.508
219224BRL12CT4
Adder
6.508
219918AC2-009 C
Solar/Wind Harmer
0.018
227287AC2-120 GEN
Solar/Wind Helper
0.356
924131AB2-057 GEN
Solar/Wind Harmer
0.7
957921AF2-086 GEN
Solar/Wind Harmer
0.519
963711AG1-223 GEN
Solar/Wind Harmer
1.036
964001AG1-254 GEN
Solar/Wind Harmer
5.591
964851AG1-348 GEN
Solar/Wind Harmer
0.866
966261AG1-495 GEN
Solar/Wind Harmer
2.282
972141AH1-641 GEN
Solar/Wind Harmer
2.209
972177AH1-672 GEN
Solar/Wind Harmer
12.412
972233AH1-701 GEN
Adder
3.192
972237AH1-703 GEN
Adder
6.701
972251AH1-710 GEN
Adder
40.035
972275AH1-722 GEN
Adder
21.203
972281AH1-725 GEN
50/50
140.974
233950AC2-186 GEN
Solar/Wind Harmer
0.519
233952AC2-187 GEN
Solar/Wind Harmer
1.038
233954AC2-188 GEN
Solar/Wind Harmer
1.038
972260AH1-715 GEN1
Adder
9.236
972261AH1-715 GEN2
Adder
10.7
230422AE1-104_GEN1
Solar/Wind Harmer
25.798
230425AE1-104_GEN2
Solar/Wind Harmer
25.798
232422X3-066 FULL
Solar/Wind Harmer
0.23
234033AF1-007_GEN
Solar/Wind Harmer
34.381
219919AE1-041 FULL
Solar/Wind Harmer
0.027
219912AD2-042 GEN
Solar/Wind Harmer
0.592
219914AD2-027 C
Solar/Wind Harmer
0.446
207500AE2-000G1
Solar/Wind Harmer
22.403
207497AE2-000G2
Solar/Wind Harmer
22.403
207507AE2-000G3
Solar/Wind Harmer
22.403
207487AE2-000G4
Solar/Wind Harmer
22.403
217121ECCF
Adder
0.288
232910NRG_G1
Adder
7.954
G-007ALTFEXP_G-007A->PJM
CMTX
34.806
VTFLTFEXP_VFT->PJM
CMTX
89.976
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.123
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.379
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.987
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.93
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.138
CBM NorthLTFEXP_CBM-N->PJM
CBM
50.284
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o BG_P7_CNSTN_NWEST2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
BG_P7_CNSTN_NWEST2_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.61 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3178.71
MW Contribution:
123.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
1.556
200053ROCKSP 2
50/50
1.526
200054ROCKSP 3
50/50
1.575
200055ROCKSP 4
50/50
1.547
200203Y1-065-STG
50/50
4.285
200204Y1-065-CTG1
50/50
2.474
200205Y1-065-CTG2
50/50
2.474
20486527WR_V4-052
Adder
0.661
20628028LAKEHURS
Adder
0.592
20633028GILCT9
Adder
17.557
20634528N27_Y2-018
Solar/Wind Harmer
0.166
20635828PARLN1&2
Adder
2.077
20635828PARLN1&2
Adder
4.586
20635928PARLN3&4
Adder
2.077
20635928PARLN3&4
Adder
4.586
20636028O CRK C1
Adder
4.408
20636128O CRK C2
Adder
4.019
20641628MLH_W1-032
Solar/Wind Harmer
0.182
20671828STAW2-080
Solar/Wind Harmer
0.065
20671928W4-073
Solar/Wind Harmer
0.268
20673628F1S_V4-069
Solar/Wind Harmer
0.111
20673728F2S_V4-070
Solar/Wind Harmer
0.111
20673828FLE_V3-070
Solar/Wind Harmer
0.289
20674128FR_U2-059
Solar/Wind Harmer
0.114
20674328GAR_V4-001
Solar/Wind Harmer
0.068
20674528F3S_W2-016
Solar/Wind Harmer
0.872
20674628WNG_W3-110
Solar/Wind Harmer
0.249
20674828DL_W4-046
Solar/Wind Harmer
0.399
20674928WA_W3-044
Solar/Wind Harmer
0.298
20675128HRM_W1-127
Solar/Wind Harmer
0.105
20675428EAM_W2-061
Solar/Wind Harmer
0.117
20675528CPH_W2-050
Solar/Wind Harmer
0.356
20675728RH_W2-091
Solar/Wind Harmer
0.373
20675828AU_W4-064
Solar/Wind Harmer
0.107
20675928HOL_W4-097
Solar/Wind Harmer
0.081
20676128MHD_W3-029
Solar/Wind Harmer
0.295
20676228FRD_X1-012
Solar/Wind Harmer
0.365
20676328BVR_Y1-020
Solar/Wind Harmer
0.204
20676428JCR_X2-075
Solar/Wind Harmer
0.211
20676728BRNX1-095
Solar/Wind Harmer
0.109
20714428HOW_X1-037
Solar/Wind Harmer
0.767
20714528FRN_Y2-051
Solar/Wind Harmer
0.183
20714828MDF_W3-079
Solar/Wind Harmer
0.19
20714928UPF_X1-085
Solar/Wind Harmer
0.253
20715028HAN_X4-015
Solar/Wind Harmer
0.186
20715228NPK_W1-113
Solar/Wind Harmer
0.267
20715728PEM_W1-119
Solar/Wind Harmer
0.333
20715828PEM_W1-120
Solar/Wind Harmer
0.333
20716028EGP_W2-019
Solar/Wind Harmer
0.29
20716228APLW2-078
Solar/Wind Harmer
0.548
20716428NHV_W2-082
Solar/Wind Harmer
1.11
20716928W4-060COL
Solar/Wind Harmer
0.441
20717128DIX_Z2-102
Solar/Wind Harmer
0.824
20720428HOL_W1-112
Solar/Wind Harmer
0.214
20720528MAN_W1-024
Solar/Wind Harmer
0.158
20720628TIN_W1-124
Solar/Wind Harmer
0.618
20720728JCB_W1-129
Solar/Wind Harmer
0.186
20720828JCB_W4-025
Solar/Wind Harmer
0.283
207408W3-077 C
Solar/Wind Harmer
0.313
207439AE1-081 C O1
Solar/Wind Harmer
0.037
213497CHSTR7-9
Adder
1.754
213497CHSTR7-9
Adder
1.754
213497CHSTR7-9
Adder
1.754
213535CROYDN11
Adder
6.441
213560DLW11-12
Adder
1.724
213560DLW11-12
Adder
1.724
213561DLWR9-10
Adder
2.254
213561DLWR9-10
Adder
1.724
213587EDDYSTN3
Adder
51.233
213589EDDYSTN4
Adder
51.238
213611FALLS1-3
Adder
2.216
213611FALLS1-3
Adder
2.216
213611FALLS1-3
Adder
2.216
213815MOSER1-3
Adder
2.233
213815MOSER1-3
Adder
2.233
213815MOSER1-3
Adder
2.233
213942SCHUYLKILL
Adder
1.736
213942SCHUYLKILL
Adder
2.27
213957STHWK3-4
Adder
1.735
213957STHWK3-4
Adder
1.735
213958STHWK5-6
Adder
1.735
213958STHWK5-6
Adder
1.735
214067T20SOLAR
Solar/Wind Harmer
0.158
214194N WALES4
Adder
0.533
217206BARNGR HS C
Solar/Wind Harmer
0.019
217208PARK ELE C
Solar/Wind Harmer
0.016
217209CENTRL HS C
Solar/Wind Harmer
0.028
217211CAMDEN ST C
Solar/Wind Harmer
0.015
217213AMBOY SO C
Solar/Wind Harmer
0.078
231907DC10
Adder
2.556
231917EM10
Adder
1.69
231918WEST 1
Adder
2.418
231919CHRIST1
Adder
3.179
231920CHRIST2
Adder
3.109
231940T-011
Adder
0.548
232404W1-003 C
Solar/Wind Harmer
0.735
232408W1-005 C
Solar/Wind Harmer
0.735
232410W1-006 C
Solar/Wind Harmer
0.735
232417X3-008 C
Solar/Wind Harmer
0.826
232426Y1-080 FULL
Solar/Wind Harmer
0.14
232428Y3-058 C
Solar/Wind Harmer
0.612
232813VAUGHN
Adder
0.432
232901NORTHST
Adder
6.114
232902EASTMUNI
Adder
9.566
232904IR4
Adder
59.406
232907VN8
Adder
22.071
232912OH NUG1
Adder
6.491
232913OH NUG2
Adder
6.404
232914OH NUG3
Adder
6.491
232915OH NUG4
Adder
6.447
232916OH NUG5
Adder
6.491
232917OH NUG6
Adder
6.462
232918OH NUG7
Adder
6.447
232919VN10
Adder
2.062
232920IR10
Adder
2.322
232921TASLEY2G
Adder
3.793
232926CRISFLD1
Adder
1.442
209027LOR2_Q27
Solar/Wind Harmer
2.665
212266LOR1
Solar/Wind Harmer
0.706
217081WEATEXAS C
Solar/Wind Harmer
0.053
217083KRNY_132
Adder
5.71
217083KRNY_132
Adder
5.746
217086KRNY_131
Adder
5.758
217086KRNY_131
Adder
5.697
217146KRNY_1234
Adder
5.356
217146KRNY_1234
Adder
5.319
217147KRNY_1212
Adder
5.466
217147KRNY_1212
Adder
5.368
217167KRNY_14
Adder
5.746
217169METRODIV C
Solar/Wind Harmer
0.025
217186ESSEX_G9
Adder
2.44
217197RE CRAN C
Solar/Wind Harmer
0.333
217201HACKENSOLA C
Solar/Wind Harmer
0.045
217202FBANKSOLAR C
Solar/Wind Harmer
0.045
218418LINDEN_G5
Adder
10.628
218419LINDEN_G6
Adder
10.628
218428ETC SOLAR C
Solar/Wind Harmer
0.022
218438BLK ROCK C
Solar/Wind Harmer
0.084
218440SUMMTASSOC C
Solar/Wind Harmer
0.079
218449LINSOLAR C
Solar/Wind Harmer
0.622
218660EHAMPSOLAR C
Solar/Wind Harmer
0.111
219035LINDEN_G8
Adder
10.199
219036LINDEN_G7
Adder
10.347
219114HARTZY_C
Solar/Wind Harmer
0.52
219137THOSOLAR C
Solar/Wind Harmer
0.773
219236SOUTHERNHQ C
Solar/Wind Harmer
0.043
219249CENTRALDIV C
Solar/Wind Harmer
0.025
219272CLEANLIGHT C
Solar/Wind Harmer
0.116
219276PARKLANDSO C
Solar/Wind Harmer
0.287
219287REEVESEAST C
Solar/Wind Harmer
0.853
219291REEVESSOUT C
Solar/Wind Harmer
0.038
219348LDSOLAR C
Solar/Wind Harmer
0.377
219607WPEMNERT C
Solar/Wind Harmer
0.264
219610FLORENCE C
Solar/Wind Harmer
0.872
219612MATRIX C
Solar/Wind Harmer
0.114
219615MILLCREEK C
Solar/Wind Harmer
0.15
219620RIDERU C
Solar/Wind Harmer
0.035
219766PARADISE C
Solar/Wind Harmer
0.2
219817TRENTONSOL C
Solar/Wind Harmer
0.685
227927V4-067C
Solar/Wind Harmer
0.127
228200CARL#1CT
Adder
4.22
228201CARL#2CT
Adder
4.437
228206SHRMN CT
Adder
10.712
228251CARLLS#4
Adder
0.407
228260V4-054C
Solar/Wind Harmer
0.662
228307PCLP GT
Adder
7.78
228400MICK 1CT
Adder
7.579
228711V2-041C
Solar/Wind Harmer
0.388
20462827N BANGR8
Adder
0.443
228728W1-130C
Solar/Wind Harmer
0.427
228729W2-030 C
Solar/Wind Harmer
0.371
228732V1-021 C
Adder
0.122
200034PCHBTM 2
50/50
12.417
200035PCHBTM 3
50/50
12.143
232406W1-004 FULL
Solar/Wind Harmer
0.735
232436AB1-176 C
Solar/Wind Harmer
0.168
200058HUNTR101
50/50
1.547
200059HUNTR201
50/50
1.547
200060HUNTR301
50/50
1.547
200061HUNTR401
50/50
2.95
200192DELTA CT1
50/50
1.19
200193DELTA CT2
50/50
1.19
200194DELTA CT3
50/50
1.19
200195DELTA ST
50/50
1.838
217194REDH C
Solar/Wind Harmer
0.304
230415AB2-049 C
Solar/Wind Harmer
0.122
20742028HF_AC1-207
Solar/Wind Harmer
0.486
207454AA2-184 E
Solar/Wind Harmer
0.62
207459AE1-142 C O1
Solar/Wind Harmer
0.657
207471AF2-354 C
Solar/Wind Harmer
0.317
208835TUHI V3-051
Solar/Wind Harmer
0.038
208835TUHI V3-051
Solar/Wind Harmer
0.038
208909MACR G3
Adder
98.264
209008PAXT IPP
Adder
1.196
209010PEIP 1
Adder
2.097
209010PEIP 1
Adder
0.307
209010PEIP 1
Adder
0.381
209018SUNBIPCT
Adder
4.224
209023WIENIPP1
Adder
6.455
209025WIENIPP3
Adder
3.157
209025WIENIPP3
Adder
3.222
209026WIENIPP4
Adder
3.19
209030FRFA O01
Adder
0.166
232424Y1-079 C
Solar/Wind Harmer
0.412
232899W1-062
Adder
7.061
232900DEMECSMY
Adder
6.773
232905CHERITON_25
Adder
1.803
218524CNTRALGAS1 C
Solar/Wind Harmer
0.229
218526CNTRALGAS2 C
Solar/Wind Harmer
0.229
226910AB2-157 C
Solar/Wind Helper
0.017
233901CHERRYDALE C
Solar/Wind Harmer
0.826
233939AC1-091 C
Solar/Wind Harmer
1.969
233940AF2-379 C
Solar/Wind Harmer
0.137
233970AC1-092 C
Solar/Wind Harmer
1.969
233971AC1-093 C
Solar/Wind Harmer
1.869
233972AC1-094 C
Solar/Wind Harmer
1.581
233973AC2-185 C
Solar/Wind Harmer
3.977
212507AE2-042_GEN
Solar/Wind Harmer
1.712
219727YARDVSOLFA C
Solar/Wind Harmer
0.567
219907AC1-030 C
Solar/Wind Harmer
0.088
228754AB1-001 C
Solar/Wind Harmer
0.089
228351V2-046C
Solar/Wind Harmer
1.298
217204WCALDSOLAR C
Solar/Wind Harmer
0.045
233944AB2-135 GEN
Solar/Wind Harmer
3.829
233946AB2-136 GEN
Solar/Wind Harmer
2.93
233994AC2-023 GEN
Solar/Wind Harmer
1.972
233984AB2-036 GEN
Solar/Wind Harmer
9.131
233982AB2-133 GEN
Solar/Wind Harmer
3.56
233915AB1-141 GEN
Solar/Wind Harmer
0.724
233918AB1-142 GEN
Solar/Wind Harmer
0.724
233930AB2-032 GEN
Solar/Wind Harmer
0.609
233987AB2-037 GEN
Solar/Wind Harmer
8.365
233933AB2-153 GEN
Solar/Wind Harmer
0.822
233955AB2-172 GEN
Solar/Wind Harmer
3.672
233935AB2-179 C
Solar/Wind Harmer
1.815
234041AC1-190 GEN
Solar/Wind Harmer
6.579
233968AD2-076_GEN
Solar/Wind Harmer
4.857
234012AE2-112_GEN
Solar/Wind Harmer
1.685
234014AF1-036_GEN
Solar/Wind Harmer
1.982
234015AF2-250 C
Solar/Wind Harmer
0.088
234036AF2-325 C
Solar/Wind Harmer
0.673
207522AF2-254 C
Solar/Wind Harmer
0.896
207528AF2-192 GEN
Solar/Wind Harmer
0.787
207484AF2-139 C O1
Solar/Wind Harmer
0.313
207510AF2-138 C
Solar/Wind Harmer
1.1
207518AF1-320_GEN
Solar/Wind Harmer
2.263
207442AE1-156 GEN
Solar/Wind Harmer
0.46
226929AD2-058 GEN
Solar/Wind Helper
0.114
207437AD2-070 GEN
Solar/Wind Harmer
0.187
209054AE2-059 GEN
Solar/Wind Harmer
0.966
207445AB1-138_GEN
Solar/Wind Harmer
0.361
209071AE2-133 GEN
Solar/Wind Harmer
0.96
209116AE2-175 GEN
Solar/Wind Harmer
2.519
209120AE2-241 GEN
Solar/Wind Harmer
1.915
209093AE2-110 GEN
Solar/Wind Harmer
1.447
233923SMA
Solar/Wind Harmer
2.685
230433AD2-135 GEN
Solar/Wind Harmer
0.065
230430AE1-229_GEN
Solar/Wind Harmer
18.452
219680HOPEWELLV C1
Solar/Wind Harmer
0.047
219686LUMSOLAR_N C
Solar/Wind Harmer
0.128
219688LUMSOLAR_S C
Solar/Wind Harmer
0.128
219908AB1-139 C
Solar/Wind Harmer
0.236
219904AC1-010 C
Solar/Wind Harmer
0.24
219906AC1-017 C
Solar/Wind Harmer
0.141
219623KINSLEYBEA C
Solar/Wind Harmer
0.272
219258KINSLEYDEP C
Solar/Wind Harmer
0.206
219304NAMERICA C
Solar/Wind Harmer
0.195
219921AF1-264
Solar/Wind Harmer
0.092
231902DC CT7
Adder
8.186
231906DC3 NUG
Adder
10.24
211065PSPA IPP
Solar/Wind Harmer
0.276
211065PSPA IPP
Solar/Wind Harmer
0.276
208862AG1-362 C
Solar/Wind Harmer
0.496
207530AG1-191 GEN
Solar/Wind Harmer
0.851
230511AF1-262
Solar/Wind Harmer
0.118
209130AF1-271A GEN
Solar/Wind Harmer
1.594
209142AF1-226 GEN
Solar/Wind Harmer
3.351
205941AD2-115 GEN
Solar/Wind Harmer
0.567
20465427SHAW CT
Adder
2.379
20635028RRCT1&2
Adder
7.301
20635028RRCT1&2
Adder
7.189
20635128RRCT3&4
Adder
6.939
20635128RRCT3&4
Adder
6.053
20465527S.RDG CT
Adder
1.643
20465527S.RDG CT
Adder
1.698
20466127PORT 5CT
Adder
16.36
20465127PORT CT
Adder
1.855
20465127PORT CT
Adder
2.461
230434AG1-499 GEN
Solar/Wind Harmer
0.372
233964AF2-378 GEN
Solar/Wind Harmer
0.094
200200DELTA2 CT1
50/50
2.13
200201DELTA2 CT2
50/50
2.13
200202DELTA2 ST
50/50
3.607
207511W3-106 GEN
Solar/Wind Harmer
0.204
208972BECR K09
Solar/Wind Harmer
0.627
209029WAYMART-WD
Solar/Wind Harmer
1.532
230407AD2-065 C
Solar/Wind Harmer
0.084
232432Z2-076 GEN
Solar/Wind Harmer
0.097
232434Z2-077 GEN
Solar/Wind Harmer
0.184
233996TM1833_GEN
Solar/Wind Harmer
0.732
233997TMININ_4.2
Solar/Wind Harmer
0.732
233998TM1NIN_3.36
Solar/Wind Harmer
0.732
946691AF1-333 GEN
Solar/Wind Harmer
0.568
946731AF1-337 GEN
Solar/Wind Harmer
0.568
946741AF1-338 GEN
Solar/Wind Harmer
0.568
946751AF1-339 GEN
Solar/Wind Harmer
0.568
959421AF2-233 GEN
Solar/Wind Harmer
0.567
959431AF2-234 GEN
Solar/Wind Harmer
1.134
959561AF2-247 GEN
Solar/Wind Harmer
0.304
961261AF2-417 GEN
Solar/Wind Harmer
0.601
961301AF2-421 GEN
Solar/Wind Harmer
0.599
961331AF2-424 GEN
Solar/Wind Harmer
0.58
961341AF2-425 GEN
Solar/Wind Harmer
0.58
961421AF2-433 GEN
Solar/Wind Harmer
0.579
961431AF2-434 GEN
Solar/Wind Harmer
0.579
961541AF2-445A GEN
Solar/Wind Harmer
1.915
963071AG1-156 GEN
Solar/Wind Harmer
5.892
963151AG1-164 GEN
Solar/Wind Harmer
0.599
963161AG1-165 GEN
Solar/Wind Harmer
0.599
963391AG1-188 GEN
Solar/Wind Harmer
2.336
963401AG1-189 GEN
Solar/Wind Harmer
1.417
970025AG2-016 GEN
Solar/Wind Harmer
1.766
970095AG2-074 GEN
Solar/Wind Harmer
3.731
970453AG2-297 GEN
Solar/Wind Harmer
1.785
970597AG2-380 GEN
Solar/Wind Harmer
3.05
970695AG2-447 GEN
Solar/Wind Harmer
2.631
970997AG2-616 GEN
Solar/Wind Harmer
6.182
971007AG2-625 GEN
Solar/Wind Harmer
1.589
971009AG2-626 GEN
Solar/Wind Harmer
1.014
971189AH1-054 GEN
Solar/Wind Harmer
0.735
971195AH1-057 GEN
Solar/Wind Harmer
0.716
971519AH1-257 GEN
Solar/Wind Harmer
1.561
971521AH1-258 GEN
Solar/Wind Harmer
1.679
971667AH1-334 GEN
Solar/Wind Harmer
1.712
219221BRL12CT1
Adder
5.621
219222BRL12CT2
Adder
5.621
219223BRL12CT3
Adder
5.621
219224BRL12CT4
Adder
5.621
219918AC2-009 C
Solar/Wind Harmer
0.016
227287AC2-120 GEN
Solar/Wind Helper
0.405
924131AB2-057 GEN
Solar/Wind Harmer
0.637
957921AF2-086 GEN
Solar/Wind Harmer
0.563
963711AG1-223 GEN
Solar/Wind Harmer
0.92
964001AG1-254 GEN
Solar/Wind Harmer
4.696
964051AG1-259 GEN
Solar/Wind Harmer
0.761
964061AG1-260 GEN
Solar/Wind Harmer
0.761
964851AG1-348 GEN
Solar/Wind Harmer
0.845
966261AG1-495 GEN
Solar/Wind Harmer
2.174
972141AH1-641 GEN
Solar/Wind Harmer
1.855
972177AH1-672 GEN
Solar/Wind Harmer
9.868
972221AH1-695 GEN
Adder
80.797
972233AH1-701 GEN
Adder
2.694
972237AH1-703 GEN
Adder
6.255
972251AH1-710 GEN
Adder
32.338
972275AH1-722 GEN
Adder
19.539
972281AH1-725 GEN
50/50
123.888
233950AC2-186 GEN
Solar/Wind Harmer
0.413
233952AC2-187 GEN
Solar/Wind Harmer
0.826
233954AC2-188 GEN
Solar/Wind Harmer
0.826
972260AH1-715 GEN1
Adder
8.511
972261AH1-715 GEN2
Adder
9.904
230422AE1-104_GEN1
Solar/Wind Harmer
21.702
230425AE1-104_GEN2
Solar/Wind Harmer
21.702
232422X3-066 FULL
Solar/Wind Harmer
0.183
234033AF1-007_GEN
Solar/Wind Harmer
27.328
219919AE1-041 FULL
Solar/Wind Harmer
0.025
219912AD2-042 GEN
Solar/Wind Harmer
0.505
219914AD2-027 C
Solar/Wind Harmer
0.381
207500AE2-000G1
Solar/Wind Harmer
19.645
207497AE2-000G2
Solar/Wind Harmer
19.645
207507AE2-000G3
Solar/Wind Harmer
19.645
207487AE2-000G4
Solar/Wind Harmer
19.645
217121ECCF
Adder
0.268
232910NRG_G1
Adder
6.331
G-007ALTFEXP_G-007A->PJM
CMTX
31.752
VTFLTFEXP_VFT->PJM
CMTX
83.748
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.778
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.16
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.114
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.52
BlueGrassPJM->LTFIMP_BlueG
CLTF
7.862
CBM NorthLTFEXP_CBM-N->PJM
CBM
49.127
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.69 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3150.34
MW Contribution:
142.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
2.146
200053ROCKSP 2
50/50
2.104
200054ROCKSP 3
50/50
2.17
200055ROCKSP 4
50/50
2.133
200203Y1-065-STG
50/50
5.906
200204Y1-065-CTG1
50/50
3.41
200205Y1-065-CTG2
50/50
3.41
20486527WR_V4-052
Adder
0.575
20628028LAKEHURS
Adder
0.665
20633028GILCT9
Adder
17.624
20634528N27_Y2-018
Solar/Wind Harmer
0.169
20635828PARLN1&2
Adder
2.264
20635828PARLN1&2
Adder
4.999
20635928PARLN3&4
Adder
2.264
20635928PARLN3&4
Adder
4.999
20636028O CRK C1
Adder
4.982
20636128O CRK C2
Adder
4.542
20641628MLH_W1-032
Solar/Wind Harmer
0.201
20671828STAW2-080
Solar/Wind Harmer
0.069
20671928W4-073
Solar/Wind Harmer
0.269
20673628F1S_V4-069
Solar/Wind Harmer
0.119
20673728F2S_V4-070
Solar/Wind Harmer
0.119
20673828FLE_V3-070
Solar/Wind Harmer
0.31
20674128FR_U2-059
Solar/Wind Harmer
0.115
20674328GAR_V4-001
Solar/Wind Harmer
0.07
20674528F3S_W2-016
Solar/Wind Harmer
0.919
20674628WNG_W3-110
Solar/Wind Harmer
0.257
20674828DL_W4-046
Solar/Wind Harmer
0.408
20674928WA_W3-044
Solar/Wind Harmer
0.304
20675128HRM_W1-127
Solar/Wind Harmer
0.106
20675428EAM_W2-061
Solar/Wind Harmer
0.125
20675528CPH_W2-050
Solar/Wind Harmer
0.383
20675728RH_W2-091
Solar/Wind Harmer
0.377
20675828AU_W4-064
Solar/Wind Harmer
0.11
20675928HOL_W4-097
Solar/Wind Harmer
0.082
20676128MHD_W3-029
Solar/Wind Harmer
0.316
20676228FRD_X1-012
Solar/Wind Harmer
0.377
20676328BVR_Y1-020
Solar/Wind Harmer
0.211
20676428JCR_X2-075
Solar/Wind Harmer
0.226
20676728BRNX1-095
Solar/Wind Harmer
0.114
20714428HOW_X1-037
Solar/Wind Harmer
0.849
20714528FRN_Y2-051
Solar/Wind Harmer
0.205
20714828MDF_W3-079
Solar/Wind Harmer
0.212
20714928UPF_X1-085
Solar/Wind Harmer
0.285
20715028HAN_X4-015
Solar/Wind Harmer
0.211
20715228NPK_W1-113
Solar/Wind Harmer
0.295
20715728PEM_W1-119
Solar/Wind Harmer
0.377
20715828PEM_W1-120
Solar/Wind Harmer
0.377
20716028EGP_W2-019
Solar/Wind Harmer
0.328
20716228APLW2-078
Solar/Wind Harmer
0.606
20716428NHV_W2-082
Solar/Wind Harmer
1.256
20716928W4-060COL
Solar/Wind Harmer
0.483
20717128DIX_Z2-102
Solar/Wind Harmer
0.932
20720428HOL_W1-112
Solar/Wind Harmer
0.236
20720528MAN_W1-024
Solar/Wind Harmer
0.174
20720628TIN_W1-124
Solar/Wind Harmer
0.683
20720728JCB_W1-129
Solar/Wind Harmer
0.211
20720828JCB_W4-025
Solar/Wind Harmer
0.32
207408W3-077 C
Solar/Wind Harmer
0.317
207439AE1-081 C O1
Solar/Wind Harmer
0.038
213497CHSTR7-9
Adder
2.026
213497CHSTR7-9
Adder
2.026
213497CHSTR7-9
Adder
2.026
213535CROYDN11
Adder
7.346
213560DLW11-12
Adder
1.97
213560DLW11-12
Adder
1.97
213561DLWR9-10
Adder
2.576
213561DLWR9-10
Adder
1.97
213587EDDYSTN3
Adder
59.094
213589EDDYSTN4
Adder
59.105
213611FALLS1-3
Adder
2.508
213611FALLS1-3
Adder
2.508
213611FALLS1-3
Adder
2.508
213815MOSER1-3
Adder
2.537
213815MOSER1-3
Adder
2.537
213815MOSER1-3
Adder
2.537
213942SCHUYLKILL
Adder
1.989
213942SCHUYLKILL
Adder
2.602
213957STHWK3-4
Adder
1.988
213957STHWK3-4
Adder
1.988
213958STHWK5-6
Adder
1.988
213958STHWK5-6
Adder
1.988
214067T20SOLAR
Solar/Wind Harmer
0.179
214194N WALES4
Adder
0.6
217206BARNGR HS C
Solar/Wind Harmer
0.02
217208PARK ELE C
Solar/Wind Harmer
0.017
217209CENTRL HS C
Solar/Wind Harmer
0.029
217211CAMDEN ST C
Solar/Wind Harmer
0.016
217213AMBOY SO C
Solar/Wind Harmer
0.084
231907DC10
Adder
3.19
231911HR5
50/50
1.326
231912HR6
50/50
1.326
231913HR7
50/50
1.326
231914HR8
50/50
2.016
231917EM10
Adder
2.058
231918WEST 1
Adder
2.961
231919CHRIST1
Adder
3.889
231920CHRIST2
Adder
3.803
231940T-011
Adder
0.687
232404W1-003 C
Solar/Wind Harmer
0.921
232408W1-005 C
Solar/Wind Harmer
0.921
232410W1-006 C
Solar/Wind Harmer
0.921
232417X3-008 C
Solar/Wind Harmer
1.035
232426Y1-080 FULL
Solar/Wind Harmer
0.176
232428Y3-058 C
Solar/Wind Harmer
0.768
232616GEN FOOD
50/50
0.159
232813VAUGHN
Adder
0.541
232901NORTHST
Adder
7.669
232902EASTMUNI
Adder
11.979
232904IR4
Adder
74.501
232907VN8
50/50
29.37
232911NRG_G2
50/50
0.46
232912OH NUG1
50/50
8.637
232913OH NUG2
50/50
8.522
232914OH NUG3
50/50
8.637
232915OH NUG4
50/50
8.58
232916OH NUG5
50/50
8.637
232917OH NUG6
50/50
8.599
232918OH NUG7
50/50
8.58
232919VN10
50/50
2.744
232920IR10
Adder
2.912
232921TASLEY2G
50/50
5.048
232926CRISFLD1
50/50
1.919
3141426STAFORD
Solar/Wind Helper
0.049
209027LOR2_Q27
Solar/Wind Harmer
2.466
212266LOR1
Solar/Wind Harmer
0.654
217081WEATEXAS C
Solar/Wind Harmer
0.057
217083KRNY_132
Adder
6.066
217083KRNY_132
Adder
6.105
217086KRNY_131
Adder
6.118
217086KRNY_131
Adder
6.053
217146KRNY_1234
Adder
5.69
217146KRNY_1234
Adder
5.652
217147KRNY_1212
Adder
5.807
217147KRNY_1212
Adder
5.703
217167KRNY_14
Adder
6.105
217169METRODIV C
Solar/Wind Harmer
0.026
217186ESSEX_G9
Adder
2.593
217197RE CRAN C
Solar/Wind Harmer
0.365
217201HACKENSOLA C
Solar/Wind Harmer
0.048
217202FBANKSOLAR C
Solar/Wind Harmer
0.048
218418LINDEN_G5
Adder
11.436
218419LINDEN_G6
Adder
11.436
218428ETC SOLAR C
Solar/Wind Harmer
0.024
218438BLK ROCK C
Solar/Wind Harmer
0.092
218440SUMMTASSOC C
Solar/Wind Harmer
0.086
218449LINSOLAR C
Solar/Wind Harmer
0.666
218660EHAMPSOLAR C
Solar/Wind Harmer
0.128
219035LINDEN_G8
Adder
10.926
219036LINDEN_G7
Adder
11.085
219114HARTZY_C
Solar/Wind Harmer
0.583
219137THOSOLAR C
Solar/Wind Harmer
0.897
219236SOUTHERNHQ C
Solar/Wind Harmer
0.049
219249CENTRALDIV C
Solar/Wind Harmer
0.026
219272CLEANLIGHT C
Solar/Wind Harmer
0.134
219276PARKLANDSO C
Solar/Wind Harmer
0.319
219287REEVESEAST C
Solar/Wind Harmer
0.987
219291REEVESSOUT C
Solar/Wind Harmer
0.044
219348LDSOLAR C
Solar/Wind Harmer
0.43
219607WPEMNERT C
Solar/Wind Harmer
0.301
219610FLORENCE C
Solar/Wind Harmer
0.996
219612MATRIX C
Solar/Wind Harmer
0.125
219615MILLCREEK C
Solar/Wind Harmer
0.172
219620RIDERU C
Solar/Wind Harmer
0.038
219766PARADISE C
Solar/Wind Harmer
0.231
219817TRENTONSOL C
Solar/Wind Harmer
0.759
227927V4-067C
Solar/Wind Harmer
0.149
228200CARL#1CT
Adder
4.983
228201CARL#2CT
Adder
5.239
228206SHRMN CT
Adder
12.684
228251CARLLS#4
Adder
0.481
228260V4-054C
Solar/Wind Harmer
0.782
228307PCLP GT
Adder
9.126
228400MICK 1CT
Adder
8.855
228711V2-041C
Solar/Wind Harmer
0.46
233920W3-032A-CTG1
50/50
1.973
233921W3-032A-STG1
50/50
1.275
20462827N BANGR8
Adder
0.445
228728W1-130C
Solar/Wind Harmer
0.502
228729W2-030 C
Solar/Wind Harmer
0.436
228732V1-021 C
Adder
0.144
200034PCHBTM 2
50/50
17.405
200035PCHBTM 3
50/50
17.342
232406W1-004 FULL
Solar/Wind Harmer
0.921
232436AB1-176 C
Solar/Wind Harmer
0.209
200192DELTA CT1
50/50
1.669
200193DELTA CT2
50/50
1.669
200194DELTA CT3
50/50
1.669
200195DELTA ST
50/50
2.578
217194REDH C
Solar/Wind Harmer
0.323
230415AB2-049 C
Solar/Wind Harmer
0.143
20742028HF_AC1-207
Solar/Wind Harmer
0.536
207454AA2-184 E
Solar/Wind Harmer
0.686
207459AE1-142 C O1
Solar/Wind Harmer
0.738
207471AF2-354 C
Solar/Wind Harmer
0.323
208909MACR G3
Adder
97.98
209010PEIP 1
Adder
2.024
209010PEIP 1
Adder
0.296
209010PEIP 1
Adder
0.368
209023WIENIPP1
Adder
6.142
209025WIENIPP3
Adder
3.004
209025WIENIPP3
Adder
3.066
209026WIENIPP4
Adder
3.035
232424Y1-079 C
Solar/Wind Harmer
0.515
232899W1-062
Adder
8.852
232900DEMECSMY
Adder
8.49
232905CHERITON_25
50/50
2.399
218524CNTRALGAS1 C
Solar/Wind Harmer
0.247
218526CNTRALGAS2 C
Solar/Wind Harmer
0.248
226910AB2-157 C
Solar/Wind Helper
0.014
233901CHERRYDALE C
Solar/Wind Harmer
1.036
233939AC1-091 C
Solar/Wind Harmer
2.469
233940AF2-379 C
Solar/Wind Harmer
0.172
233970AC1-092 C
Solar/Wind Harmer
2.469
233971AC1-093 C
Solar/Wind Harmer
2.344
233972AC1-094 C
Solar/Wind Harmer
1.982
233973AC2-185 C
Solar/Wind Harmer
4.987
219727YARDVSOLFA C
Solar/Wind Harmer
0.634
219907AC1-030 C
Solar/Wind Harmer
0.101
316411AF1-147_GEN1
Solar/Wind Helper
0.765
316415AF1-147_GEN2
Solar/Wind Helper
0.765
228754AB1-001 C
Solar/Wind Harmer
0.105
228351V2-046C
Solar/Wind Harmer
1.528
217204WCALDSOLAR C
Solar/Wind Harmer
0.048
233944AB2-135 GEN
Solar/Wind Harmer
4.777
233946AB2-136 GEN
Solar/Wind Harmer
3.672
233994AC2-023 GEN
Solar/Wind Harmer
2.473
233984AB2-036 GEN
Solar/Wind Harmer
11.421
233982AB2-133 GEN
Solar/Wind Harmer
4.439
233915AB1-141 GEN
Solar/Wind Harmer
0.903
233918AB1-142 GEN
Solar/Wind Harmer
0.903
233930AB2-032 GEN
Solar/Wind Harmer
0.76
233987AB2-037 GEN
Solar/Wind Harmer
10.497
233933AB2-153 GEN
Solar/Wind Harmer
1.026
233955AB2-172 GEN
Solar/Wind Harmer
4.602
233935AB2-179 C
Solar/Wind Harmer
2.248
234041AC1-190 GEN
Solar/Wind Harmer
8.246
233968AD2-076_GEN
Solar/Wind Harmer
6.066
234012AE2-112_GEN
Solar/Wind Harmer
2.104
234014AF1-036_GEN
Solar/Wind Harmer
2.476
234015AF2-250 C
Solar/Wind Harmer
0.111
234036AF2-325 C
Solar/Wind Harmer
0.844
207522AF2-254 C
Solar/Wind Harmer
1.014
207528AF2-192 GEN
Solar/Wind Harmer
0.842
207484AF2-139 C O1
Solar/Wind Harmer
0.316
207510AF2-138 C
Solar/Wind Harmer
1.136
207518AF1-320_GEN
Solar/Wind Harmer
2.286
207442AE1-156 GEN
Solar/Wind Harmer
0.492
226929AD2-058 GEN
Solar/Wind Helper
0.1
207437AD2-070 GEN
Solar/Wind Harmer
0.188
207445AB1-138_GEN
Solar/Wind Harmer
0.405
209116AE2-175 GEN
Solar/Wind Harmer
2.49
209120AE2-241 GEN
Solar/Wind Harmer
1.758
209093AE2-110 GEN
Solar/Wind Harmer
1.328
233923SMA
Solar/Wind Harmer
3.368
230433AD2-135 GEN
Solar/Wind Harmer
0.077
230430AE1-229_GEN
Solar/Wind Harmer
21.736
219680HOPEWELLV C1
Solar/Wind Harmer
0.052
219686LUMSOLAR_N C
Solar/Wind Harmer
0.148
219688LUMSOLAR_S C
Solar/Wind Harmer
0.148
219908AB1-139 C
Solar/Wind Harmer
0.254
219904AC1-010 C
Solar/Wind Harmer
0.278
219906AC1-017 C
Solar/Wind Harmer
0.161
219623KINSLEYBEA C
Solar/Wind Harmer
0.316
219258KINSLEYDEP C
Solar/Wind Harmer
0.239
219304NAMERICA C
Solar/Wind Harmer
0.223
219921AF1-264
Solar/Wind Harmer
0.106
231902DC CT7
Adder
10.215
231906DC3 NUG
Adder
12.777
211065PSPA IPP
Solar/Wind Harmer
0.27
211065PSPA IPP
Solar/Wind Harmer
0.27
207530AG1-191 GEN
Solar/Wind Harmer
0.877
230511AF1-262
Solar/Wind Harmer
0.139
209142AF1-226 GEN
Solar/Wind Harmer
3.076
205941AD2-115 GEN
Solar/Wind Harmer
0.51
20465427SHAW CT
Adder
2.391
20635028RRCT1&2
Adder
7.936
20635028RRCT1&2
Adder
7.814
20635128RRCT3&4
Adder
7.542
20635128RRCT3&4
Adder
6.579
20465527S.RDG CT
Adder
1.426
20465527S.RDG CT
Adder
1.473
20466127PORT 5CT
Adder
16.497
20465127PORT CT
Adder
1.869
20465127PORT CT
Adder
2.48
230434AG1-499 GEN
Solar/Wind Harmer
0.437
233964AF2-378 GEN
Solar/Wind Harmer
0.117
234034AF2-060
50/50
1.727
200200DELTA2 CT1
50/50
2.986
200201DELTA2 CT2
50/50
2.986
200202DELTA2 ST
50/50
5.057
207511W3-106 GEN
Solar/Wind Harmer
0.211
208972BECR K09
Solar/Wind Harmer
0.596
209029WAYMART-WD
Solar/Wind Harmer
1.478
230407AD2-065 C
Solar/Wind Harmer
0.099
232432Z2-076 GEN
Solar/Wind Harmer
0.122
232434Z2-077 GEN
Solar/Wind Harmer
0.23
233996TM1833_GEN
Solar/Wind Harmer
0.918
233997TMININ_4.2
Solar/Wind Harmer
0.918
233998TM1NIN_3.36
Solar/Wind Harmer
0.918
3138216PACIFIC
Solar/Wind Helper
0.038
959561AF2-247 GEN
Solar/Wind Harmer
0.344
961261AF2-417 GEN
Solar/Wind Harmer
0.587
961301AF2-421 GEN
Solar/Wind Harmer
0.57
961331AF2-424 GEN
Solar/Wind Harmer
0.533
961341AF2-425 GEN
Solar/Wind Harmer
0.533
961421AF2-433 GEN
Solar/Wind Harmer
0.531
961431AF2-434 GEN
Solar/Wind Harmer
0.531
961541AF2-445A GEN
Solar/Wind Harmer
1.772
963071AG1-156 GEN
Solar/Wind Harmer
5.641
963151AG1-164 GEN
Solar/Wind Harmer
0.57
963161AG1-165 GEN
Solar/Wind Harmer
0.57
963391AG1-188 GEN
Solar/Wind Harmer
2.633
963401AG1-189 GEN
Solar/Wind Harmer
1.599
970025AG2-016 GEN
Solar/Wind Harmer
1.991
970095AG2-074 GEN
Solar/Wind Harmer
3.572
970453AG2-297 GEN
Solar/Wind Harmer
2.118
970597AG2-380 GEN
Solar/Wind Harmer
3.809
970695AG2-447 GEN
Solar/Wind Harmer
3.299
970997AG2-616 GEN
Solar/Wind Harmer
7.285
971007AG2-625 GEN
Solar/Wind Harmer
1.615
971009AG2-626 GEN
Solar/Wind Harmer
1.03
971189AH1-054 GEN
Solar/Wind Harmer
0.828
971195AH1-057 GEN
Solar/Wind Harmer
0.898
971519AH1-257 GEN
Solar/Wind Harmer
1.584
971521AH1-258 GEN
Solar/Wind Harmer
1.85
971667AH1-334 GEN
Solar/Wind Harmer
1.923
219221BRL12CT1
Adder
6.417
219222BRL12CT2
Adder
6.417
219223BRL12CT3
Adder
6.417
219224BRL12CT4
Adder
6.417
219918AC2-009 C
Solar/Wind Harmer
0.018
227287AC2-120 GEN
Solar/Wind Helper
0.351
924131AB2-057 GEN
Solar/Wind Harmer
0.693
957921AF2-086 GEN
Solar/Wind Harmer
0.517
963711AG1-223 GEN
Solar/Wind Harmer
1.026
964001AG1-254 GEN
Solar/Wind Harmer
5.529
964851AG1-348 GEN
Solar/Wind Harmer
0.859
966261AG1-495 GEN
Solar/Wind Harmer
2.262
972141AH1-641 GEN
Solar/Wind Harmer
2.186
972177AH1-672 GEN
Solar/Wind Harmer
12.374
972233AH1-701 GEN
Adder
3.149
972237AH1-703 GEN
Adder
6.647
972251AH1-710 GEN
Adder
39.968
972275AH1-722 GEN
Adder
21.024
972281AH1-725 GEN
50/50
142.643
233950AC2-186 GEN
Solar/Wind Harmer
0.517
233952AC2-187 GEN
Solar/Wind Harmer
1.035
233954AC2-188 GEN
Solar/Wind Harmer
1.035
972260AH1-715 GEN1
Adder
9.158
972261AH1-715 GEN2
Adder
10.611
230422AE1-104_GEN1
Solar/Wind Harmer
25.577
230425AE1-104_GEN2
Solar/Wind Harmer
25.577
232422X3-066 FULL
Solar/Wind Harmer
0.228
234033AF1-007_GEN
Solar/Wind Harmer
34.273
219919AE1-041 FULL
Solar/Wind Harmer
0.027
219912AD2-042 GEN
Solar/Wind Harmer
0.582
219914AD2-027 C
Solar/Wind Harmer
0.439
207500AE2-000G1
Solar/Wind Harmer
22.203
207497AE2-000G2
Solar/Wind Harmer
22.203
207507AE2-000G3
Solar/Wind Harmer
22.203
207487AE2-000G4
Solar/Wind Harmer
22.203
217121ECCF
Adder
0.285
232910NRG_G1
50/50
8.406
G-007ALTFEXP_G-007A->PJM
CMTX
34.511
VTFLTFEXP_VFT->PJM
CMTX
89.246
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.048
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.334
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.668
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.862
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.924
CBM NorthLTFEXP_CBM-N->PJM
CBM
50.042
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o DPL_P4_2_KEENEY-ROCK AT50_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
DPL_P4_2_KEENEY-ROCK AT50_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.33 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:2897.9
MW Contribution:
200.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
5.405
200053ROCKSP 2
50/50
5.299
200054ROCKSP 3
50/50
5.467
200055ROCKSP 4
50/50
5.373
200203Y1-065-STG
50/50
14.877
200204Y1-065-CTG1
50/50
8.591
200205Y1-065-CTG2
50/50
8.591
20671828STAW2-080
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.15
20673628F1S_V4-069
Solar/Wind Helper
0.054
20673728F2S_V4-070
Solar/Wind Helper
0.054
20673828FLE_V3-070
Solar/Wind Helper
0.156
20674128FR_U2-059
Solar/Wind Helper
0.007
20674328GAR_V4-001
Solar/Wind Helper
0.038
20674628WNG_W3-110
Solar/Wind Helper
0.153
20674828DL_W4-046
Solar/Wind Helper
0.013
20674928WA_W3-044
Solar/Wind Helper
0.166
20675128HRM_W1-127
Solar/Wind Helper
0.049
20675428EAM_W2-061
Solar/Wind Helper
0.029
20675528CPH_W2-050
Solar/Wind Helper
0.205
20675728RH_W2-091
Solar/Wind Helper
0.137
20675828AU_W4-064
Solar/Wind Helper
0.051
20675928HOL_W4-097
Solar/Wind Helper
0.084
20676128MHD_W3-029
Solar/Wind Helper
0.172
20676228FRD_X1-012
Solar/Wind Helper
0.157
20676328BVR_Y1-020
Solar/Wind Helper
0.046
20676428JCR_X2-075
Solar/Wind Helper
0.121
20676728BRNX1-095
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.104
20714828MDF_W3-079
Solar/Wind Helper
0.237
20714928UPF_X1-085
Solar/Wind Helper
0.009
20715028HAN_X4-015
Solar/Wind Helper
0.105
20715228NPK_W1-113
Solar/Wind Helper
0.142
20715728PEM_W1-119
Solar/Wind Helper
0.176
20715828PEM_W1-120
Solar/Wind Helper
0.176
20716028EGP_W2-019
Solar/Wind Helper
0.034
20716928W4-060COL
Solar/Wind Helper
0.093
20720528MAN_W1-024
Solar/Wind Helper
0.051
20720628TIN_W1-124
Solar/Wind Helper
0.344
20720728JCB_W1-129
Solar/Wind Helper
0.105
20720828JCB_W4-025
Solar/Wind Helper
0.116
207408W3-077 C
Solar/Wind Helper
0.141
207439AE1-081 C O1
Solar/Wind Helper
0.032
214067T20SOLAR
Solar/Wind Helper
0.021
217206BARNGR HS C
Solar/Wind Helper
0.011
217208PARK ELE C
Solar/Wind Helper
0.008
217209CENTRL HS C
Solar/Wind Helper
0.015
217211CAMDEN ST C
Solar/Wind Helper
0.008
217213AMBOY SO C
Solar/Wind Helper
0.052
224035CHALK U1
Adder
15.912
224035CHALK U1
Adder
15.912
224036CHALK U2
Adder
16.113
224036CHALK U2
Adder
16.113
224046MORGTU1
Adder
3.371
224046MORGTU1
Adder
52.902
224047MORGTU2
Adder
3.371
224047MORGTU2
Adder
52.902
224050MORGTCT3
Adder
5.092
224051MORGTCT4
Adder
5.092
224052MORGTCT5
Adder
5.092
224053MORGTCT6
Adder
5.092
232404W1-003 C
Solar/Wind Helper
0.889
232408W1-005 C
Solar/Wind Helper
0.889
232410W1-006 C
Solar/Wind Helper
0.889
232417X3-008 C
Solar/Wind Helper
0.407
232426Y1-080 FULL
Solar/Wind Helper
0.068
232428Y3-058 C
Solar/Wind Helper
0.593
209027LOR2_Q27
Solar/Wind Helper
1.54
212266LOR1
Solar/Wind Helper
0.449
217081WEATEXAS C
Solar/Wind Helper
0.022
217169METRODIV C
Solar/Wind Helper
0.007
217201HACKENSOLA C
Solar/Wind Helper
0.005
217202FBANKSOLAR C
Solar/Wind Helper
0.005
218428ETC SOLAR C
Solar/Wind Helper
0.009
218438BLK ROCK C
Solar/Wind Helper
0.05
218440SUMMTASSOC C
Solar/Wind Helper
0.03
218660EHAMPSOLAR C
Solar/Wind Helper
0.061
219236SOUTHERNHQ C
Solar/Wind Helper
0.01
219249CENTRALDIV C
Solar/Wind Helper
0.018
219272CLEANLIGHT C
Solar/Wind Helper
0.047
219276PARKLANDSO C
Solar/Wind Helper
0.165
219291REEVESSOUT C
Solar/Wind Helper
0.021
219348LDSOLAR C
Solar/Wind Helper
0.215
219607WPEMNERT C
Solar/Wind Helper
0.15
219612MATRIX C
Solar/Wind Helper
0.043
219615MILLCREEK C
Solar/Wind Helper
0.05
219620RIDERU C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.103
227024SMECOCT
Adder
7.665
227927V4-067C
Solar/Wind Helper
0.019
228728W1-130C
Solar/Wind Helper
0.099
228729W2-030 C
Solar/Wind Helper
0.202
200034PCHBTM 2
50/50
42.258
200035PCHBTM 3
50/50
-28.326
232406W1-004 FULL
Solar/Wind Helper
0.889
232436AB1-176 C
Solar/Wind Helper
0.077
200058HUNTR101
50/50
2.228
200059HUNTR201
50/50
2.228
200060HUNTR301
50/50
2.228
200061HUNTR401
50/50
4.248
200192DELTA CT1
50/50
4.048
200193DELTA CT2
50/50
4.048
200194DELTA CT3
50/50
4.048
200195DELTA ST
50/50
6.253
223402AF1-300 C
Solar/Wind Harmer
0.572
230415AB2-049 C
Solar/Wind Helper
0.056
20742028HF_AC1-207
Solar/Wind Helper
0.256
207454AA2-184 E
Solar/Wind Helper
0.563
207459AE1-142 C O1
Solar/Wind Helper
0.529
207471AF2-354 C
Solar/Wind Helper
0.285
232424Y1-079 C
Solar/Wind Helper
0.202
218524CNTRALGAS1 C
Solar/Wind Helper
0.289
218526CNTRALGAS2 C
Solar/Wind Helper
0.29
226910AB2-157 C
Solar/Wind Harmer
0.084
233901CHERRYDALE C
Solar/Wind Helper
0.408
233940AF2-379 C
Solar/Wind Helper
0.109
212507AE2-042_GEN
Solar/Wind Helper
2.248
219907AC1-030 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.048
217204WCALDSOLAR C
Solar/Wind Helper
0.005
233944AB2-135 GEN
Solar/Wind Helper
1.021
233946AB2-136 GEN
Solar/Wind Helper
0.996
233994AC2-023 GEN
Solar/Wind Helper
1.685
233982AB2-133 GEN
Solar/Wind Helper
0.621
233915AB1-141 GEN
Solar/Wind Helper
0.869
233918AB1-142 GEN
Solar/Wind Helper
0.869
233930AB2-032 GEN
Solar/Wind Helper
0.658
233987AB2-037 GEN
Solar/Wind Helper
4.103
233933AB2-153 GEN
Solar/Wind Helper
0.402
233935AB2-179 C
Solar/Wind Helper
2.16
234015AF2-250 C
Solar/Wind Helper
0.067
234036AF2-325 C
Solar/Wind Helper
0.074
207484AF2-139 C O1
Solar/Wind Helper
0.141
207510AF2-138 C
Solar/Wind Helper
0.139
207518AF1-320_GEN
Solar/Wind Helper
2.635
207442AE1-156 GEN
Solar/Wind Helper
0.585
207437AD2-070 GEN
Solar/Wind Helper
0.23
209054AE2-059 GEN
Solar/Wind Helper
0.115
207445AB1-138_GEN
Solar/Wind Helper
0.19
209071AE2-133 GEN
Solar/Wind Helper
0.114
209116AE2-175 GEN
Solar/Wind Helper
2.935
233923SMA
Solar/Wind Helper
1.318
230433AD2-135 GEN
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.006
219686LUMSOLAR_N C
Solar/Wind Helper
0.074
219688LUMSOLAR_S C
Solar/Wind Helper
0.074
219908AB1-139 C
Solar/Wind Helper
0.133
219904AC1-010 C
Solar/Wind Helper
0.114
219906AC1-017 C
Solar/Wind Helper
0.078
219623KINSLEYBEA C
Solar/Wind Helper
0.004
219258KINSLEYDEP C
Solar/Wind Helper
0.144
219304NAMERICA C
Solar/Wind Helper
0.246
219921AF1-264
Solar/Wind Helper
0.096
211065PSPA IPP
Solar/Wind Helper
0.247
211065PSPA IPP
Solar/Wind Helper
0.247
207530AG1-191 GEN
Solar/Wind Helper
0.113
230511AF1-262
Solar/Wind Helper
0.027
205941AD2-115 GEN
Solar/Wind Helper
0.643
230434AG1-499 GEN
Solar/Wind Helper
0.425
233964AF2-378 GEN
Solar/Wind Helper
0.073
224039CHALKCT1
Adder
1.72
224040CHALKCT2
Adder
2.523
224041CHALKCT3
Adder
8.219
224042CHALKCT4
Adder
8.219
224043CHALKCT5
Adder
10.417
224044CHALKCT6
Adder
10.417
200200DELTA2 CT1
50/50
7.244
200201DELTA2 CT2
50/50
7.244
200202DELTA2 ST
50/50
12.268
207511W3-106 GEN
Solar/Wind Helper
0.046
208972BECR K09
Solar/Wind Helper
0.502
209029WAYMART-WD
Solar/Wind Helper
1.257
223401AF1-299 GEN
Solar/Wind Harmer
0.572
230407AD2-065 C
Solar/Wind Helper
0.074
232432Z2-076 GEN
Solar/Wind Helper
0.117
232434Z2-077 GEN
Solar/Wind Helper
0.222
233996TM1833_GEN
Solar/Wind Helper
0.36
233997TMININ_4.2
Solar/Wind Helper
0.36
233998TM1NIN_3.36
Solar/Wind Helper
0.36
946691AF1-333 GEN
Solar/Wind Helper
0.629
946731AF1-337 GEN
Solar/Wind Helper
0.629
946741AF1-338 GEN
Solar/Wind Helper
0.629
946751AF1-339 GEN
Solar/Wind Helper
0.629
959421AF2-233 GEN
Solar/Wind Helper
0.627
959431AF2-234 GEN
Solar/Wind Helper
1.255
959561AF2-247 GEN
Solar/Wind Helper
0.039
961261AF2-417 GEN
Solar/Wind Helper
0.69
961301AF2-421 GEN
Solar/Wind Helper
0.684
961331AF2-424 GEN
Solar/Wind Helper
0.65
961341AF2-425 GEN
Solar/Wind Helper
0.65
961421AF2-433 GEN
Solar/Wind Helper
0.649
961431AF2-434 GEN
Solar/Wind Helper
0.649
963151AG1-164 GEN
Solar/Wind Helper
0.684
963161AG1-165 GEN
Solar/Wind Helper
0.684
219918AC2-009 C
Solar/Wind Helper
0.002
227287AC2-120 GEN
Solar/Wind Harmer
0.743
957921AF2-086 GEN
Solar/Wind Helper
0.641
963711AG1-223 GEN
Solar/Wind Helper
0.116
964051AG1-259 GEN
Solar/Wind Helper
0.094
964061AG1-260 GEN
Solar/Wind Helper
0.094
964851AG1-348 GEN
Solar/Wind Helper
0.106
220909PERRYG12
Adder
7.191
220910PERRYG34
Adder
14.383
220912PHIL G34
Adder
3.945
220913PHIL G12
Adder
3.998
220917WAGNERG1
Adder
16.544
220921WAGNR GT
Adder
1.718
970999AG2-617 GEN
Solar/Wind Harmer
5.702
971001AG2-618 GEN
Solar/Wind Harmer
3.313
220911PERRYG51
50/50
1.121
220923PERRY U6
50/50
0.902
226936AF1-003_GEN1
Solar/Wind Harmer
0.651
226937AF1-003_GEN2
Solar/Wind Harmer
0.651
226943AF1-005_GEN
Solar/Wind Harmer
1.301
972281AH1-725 GEN
50/50
200.318
233950AC2-186 GEN
Solar/Wind Helper
0.204
233952AC2-187 GEN
Solar/Wind Helper
0.407
233954AC2-188 GEN
Solar/Wind Helper
0.407
232422X3-066 FULL
Solar/Wind Helper
0.198
219919AE1-041 FULL
Solar/Wind Helper
0.007
219912AD2-042 GEN
Solar/Wind Helper
0.283
219914AD2-027 C
Solar/Wind Helper
0.216
NYPJM->LTFIMP_NY
CLTF
7.331
LGEELTFEXP_LGEE->PJM
CLTF
1.737
WECLTFEXP_WEC->PJM
CLTF
0.943
CPLELTFEXP_CPLE->PJM
CLTF
3.62
LAGNLTFEXP_LAGN->PJM
CLTF
5.509
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.367
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.229
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.454
TVALTFEXP_TVA->PJM
CLTF
2.767
MECLTFEXP_MEC->PJM
CLTF
4.239
SIGELTFEXP_SIGE->PJM
CLTF
0.133

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o PECO_P1-2_5025_SRT-A/* $ CHESCO $ PECO_P1-2_5025 $ L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
PECO_P1-2_5025_SRT-A/* $ CHESCO $ PECO_P1-2_5025 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.06 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:2890.26
MW Contribution:
200.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
5.405
200053ROCKSP 2
50/50
5.299
200054ROCKSP 3
50/50
5.467
200055ROCKSP 4
50/50
5.373
200203Y1-065-STG
50/50
14.877
200204Y1-065-CTG1
50/50
8.591
200205Y1-065-CTG2
50/50
8.591
20671828STAW2-080
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.15
20673628F1S_V4-069
Solar/Wind Helper
0.054
20673728F2S_V4-070
Solar/Wind Helper
0.054
20673828FLE_V3-070
Solar/Wind Helper
0.156
20674128FR_U2-059
Solar/Wind Helper
0.007
20674328GAR_V4-001
Solar/Wind Helper
0.038
20674628WNG_W3-110
Solar/Wind Helper
0.153
20674828DL_W4-046
Solar/Wind Helper
0.013
20674928WA_W3-044
Solar/Wind Helper
0.166
20675128HRM_W1-127
Solar/Wind Helper
0.049
20675428EAM_W2-061
Solar/Wind Helper
0.029
20675528CPH_W2-050
Solar/Wind Helper
0.205
20675728RH_W2-091
Solar/Wind Helper
0.137
20675828AU_W4-064
Solar/Wind Helper
0.051
20675928HOL_W4-097
Solar/Wind Helper
0.084
20676128MHD_W3-029
Solar/Wind Helper
0.172
20676228FRD_X1-012
Solar/Wind Helper
0.157
20676328BVR_Y1-020
Solar/Wind Helper
0.046
20676428JCR_X2-075
Solar/Wind Helper
0.121
20676728BRNX1-095
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.104
20714828MDF_W3-079
Solar/Wind Helper
0.237
20714928UPF_X1-085
Solar/Wind Helper
0.009
20715028HAN_X4-015
Solar/Wind Helper
0.105
20715228NPK_W1-113
Solar/Wind Helper
0.142
20715728PEM_W1-119
Solar/Wind Helper
0.176
20715828PEM_W1-120
Solar/Wind Helper
0.176
20716028EGP_W2-019
Solar/Wind Helper
0.034
20716928W4-060COL
Solar/Wind Helper
0.093
20720528MAN_W1-024
Solar/Wind Helper
0.051
20720628TIN_W1-124
Solar/Wind Helper
0.344
20720728JCB_W1-129
Solar/Wind Helper
0.105
20720828JCB_W4-025
Solar/Wind Helper
0.116
207408W3-077 C
Solar/Wind Helper
0.141
207439AE1-081 C O1
Solar/Wind Helper
0.032
214067T20SOLAR
Solar/Wind Helper
0.021
217206BARNGR HS C
Solar/Wind Helper
0.011
217208PARK ELE C
Solar/Wind Helper
0.008
217209CENTRL HS C
Solar/Wind Helper
0.015
217211CAMDEN ST C
Solar/Wind Helper
0.008
217213AMBOY SO C
Solar/Wind Helper
0.052
224035CHALK U1
Adder
15.912
224035CHALK U1
Adder
15.912
224036CHALK U2
Adder
16.113
224036CHALK U2
Adder
16.113
224046MORGTU1
Adder
3.371
224046MORGTU1
Adder
52.902
224047MORGTU2
Adder
3.371
224047MORGTU2
Adder
52.902
224050MORGTCT3
Adder
5.092
224051MORGTCT4
Adder
5.092
224052MORGTCT5
Adder
5.092
224053MORGTCT6
Adder
5.092
232404W1-003 C
Solar/Wind Helper
0.889
232408W1-005 C
Solar/Wind Helper
0.889
232410W1-006 C
Solar/Wind Helper
0.889
232417X3-008 C
Solar/Wind Helper
0.407
232426Y1-080 FULL
Solar/Wind Helper
0.068
232428Y3-058 C
Solar/Wind Helper
0.593
209027LOR2_Q27
Solar/Wind Helper
1.54
212266LOR1
Solar/Wind Helper
0.449
217081WEATEXAS C
Solar/Wind Helper
0.022
217169METRODIV C
Solar/Wind Helper
0.007
217201HACKENSOLA C
Solar/Wind Helper
0.005
217202FBANKSOLAR C
Solar/Wind Helper
0.005
218428ETC SOLAR C
Solar/Wind Helper
0.009
218438BLK ROCK C
Solar/Wind Helper
0.05
218440SUMMTASSOC C
Solar/Wind Helper
0.03
218660EHAMPSOLAR C
Solar/Wind Helper
0.061
219236SOUTHERNHQ C
Solar/Wind Helper
0.01
219249CENTRALDIV C
Solar/Wind Helper
0.018
219272CLEANLIGHT C
Solar/Wind Helper
0.047
219276PARKLANDSO C
Solar/Wind Helper
0.165
219291REEVESSOUT C
Solar/Wind Helper
0.021
219348LDSOLAR C
Solar/Wind Helper
0.215
219607WPEMNERT C
Solar/Wind Helper
0.15
219612MATRIX C
Solar/Wind Helper
0.043
219615MILLCREEK C
Solar/Wind Helper
0.05
219620RIDERU C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.103
227024SMECOCT
Adder
7.665
227927V4-067C
Solar/Wind Helper
0.019
228728W1-130C
Solar/Wind Helper
0.099
228729W2-030 C
Solar/Wind Helper
0.202
200034PCHBTM 2
50/50
42.258
200035PCHBTM 3
50/50
-28.326
232406W1-004 FULL
Solar/Wind Helper
0.889
232436AB1-176 C
Solar/Wind Helper
0.077
200058HUNTR101
50/50
2.228
200059HUNTR201
50/50
2.228
200060HUNTR301
50/50
2.228
200061HUNTR401
50/50
4.248
200192DELTA CT1
50/50
4.048
200193DELTA CT2
50/50
4.048
200194DELTA CT3
50/50
4.048
200195DELTA ST
50/50
6.253
230415AB2-049 C
Solar/Wind Helper
0.056
20742028HF_AC1-207
Solar/Wind Helper
0.256
207454AA2-184 E
Solar/Wind Helper
0.563
207459AE1-142 C O1
Solar/Wind Helper
0.529
207471AF2-354 C
Solar/Wind Helper
0.285
232424Y1-079 C
Solar/Wind Helper
0.202
218524CNTRALGAS1 C
Solar/Wind Helper
0.289
218526CNTRALGAS2 C
Solar/Wind Helper
0.29
233901CHERRYDALE C
Solar/Wind Helper
0.408
233940AF2-379 C
Solar/Wind Helper
0.109
212507AE2-042_GEN
Solar/Wind Helper
2.248
219907AC1-030 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.048
217204WCALDSOLAR C
Solar/Wind Helper
0.005
233944AB2-135 GEN
Solar/Wind Helper
1.022
233946AB2-136 GEN
Solar/Wind Helper
0.996
233994AC2-023 GEN
Solar/Wind Helper
1.685
233982AB2-133 GEN
Solar/Wind Helper
0.621
233915AB1-141 GEN
Solar/Wind Helper
0.869
233918AB1-142 GEN
Solar/Wind Helper
0.869
233930AB2-032 GEN
Solar/Wind Helper
0.658
233987AB2-037 GEN
Solar/Wind Helper
4.104
233933AB2-153 GEN
Solar/Wind Helper
0.402
233935AB2-179 C
Solar/Wind Helper
2.16
234015AF2-250 C
Solar/Wind Helper
0.067
234036AF2-325 C
Solar/Wind Helper
0.074
207484AF2-139 C O1
Solar/Wind Helper
0.141
207510AF2-138 C
Solar/Wind Helper
0.139
207518AF1-320_GEN
Solar/Wind Helper
2.635
207442AE1-156 GEN
Solar/Wind Helper
0.585
207437AD2-070 GEN
Solar/Wind Helper
0.23
209054AE2-059 GEN
Solar/Wind Helper
0.115
207445AB1-138_GEN
Solar/Wind Helper
0.19
209071AE2-133 GEN
Solar/Wind Helper
0.114
209116AE2-175 GEN
Solar/Wind Helper
2.935
233923SMA
Solar/Wind Helper
1.319
230433AD2-135 GEN
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.006
219686LUMSOLAR_N C
Solar/Wind Helper
0.074
219688LUMSOLAR_S C
Solar/Wind Helper
0.074
219908AB1-139 C
Solar/Wind Helper
0.133
219904AC1-010 C
Solar/Wind Helper
0.114
219906AC1-017 C
Solar/Wind Helper
0.078
219623KINSLEYBEA C
Solar/Wind Helper
0.004
219258KINSLEYDEP C
Solar/Wind Helper
0.144
219304NAMERICA C
Solar/Wind Helper
0.246
219921AF1-264
Solar/Wind Helper
0.096
211065PSPA IPP
Solar/Wind Helper
0.247
211065PSPA IPP
Solar/Wind Helper
0.247
207530AG1-191 GEN
Solar/Wind Helper
0.113
230511AF1-262
Solar/Wind Helper
0.027
205941AD2-115 GEN
Solar/Wind Helper
0.643
230434AG1-499 GEN
Solar/Wind Helper
0.425
233964AF2-378 GEN
Solar/Wind Helper
0.073
224039CHALKCT1
Adder
1.72
224040CHALKCT2
Adder
2.523
224041CHALKCT3
Adder
8.219
224042CHALKCT4
Adder
8.219
224043CHALKCT5
Adder
10.417
224044CHALKCT6
Adder
10.417
200200DELTA2 CT1
50/50
7.244
200201DELTA2 CT2
50/50
7.244
200202DELTA2 ST
50/50
12.268
207511W3-106 GEN
Solar/Wind Helper
0.046
208972BECR K09
Solar/Wind Helper
0.502
209029WAYMART-WD
Solar/Wind Helper
1.257
230407AD2-065 C
Solar/Wind Helper
0.074
232432Z2-076 GEN
Solar/Wind Helper
0.117
232434Z2-077 GEN
Solar/Wind Helper
0.222
233996TM1833_GEN
Solar/Wind Helper
0.36
233997TMININ_4.2
Solar/Wind Helper
0.36
233998TM1NIN_3.36
Solar/Wind Helper
0.36
946691AF1-333 GEN
Solar/Wind Helper
0.629
946731AF1-337 GEN
Solar/Wind Helper
0.629
946741AF1-338 GEN
Solar/Wind Helper
0.629
946751AF1-339 GEN
Solar/Wind Helper
0.629
959421AF2-233 GEN
Solar/Wind Helper
0.627
959431AF2-234 GEN
Solar/Wind Helper
1.255
959561AF2-247 GEN
Solar/Wind Helper
0.039
961261AF2-417 GEN
Solar/Wind Helper
0.69
961301AF2-421 GEN
Solar/Wind Helper
0.684
961331AF2-424 GEN
Solar/Wind Helper
0.65
961341AF2-425 GEN
Solar/Wind Helper
0.65
961421AF2-433 GEN
Solar/Wind Helper
0.649
961431AF2-434 GEN
Solar/Wind Helper
0.649
963151AG1-164 GEN
Solar/Wind Helper
0.684
963161AG1-165 GEN
Solar/Wind Helper
0.684
219918AC2-009 C
Solar/Wind Helper
0.002
957921AF2-086 GEN
Solar/Wind Helper
0.641
963711AG1-223 GEN
Solar/Wind Helper
0.116
964051AG1-259 GEN
Solar/Wind Helper
0.094
964061AG1-260 GEN
Solar/Wind Helper
0.094
964851AG1-348 GEN
Solar/Wind Helper
0.106
220909PERRYG12
Adder
7.191
220910PERRYG34
Adder
14.383
220912PHIL G34
Adder
3.945
220913PHIL G12
Adder
3.998
220917WAGNERG1
Adder
16.544
220921WAGNR GT
Adder
1.718
970999AG2-617 GEN
Solar/Wind Harmer
3.978
220911PERRYG51
50/50
1.121
220923PERRY U6
50/50
0.902
226936AF1-003_GEN1
Solar/Wind Harmer
0.475
226937AF1-003_GEN2
Solar/Wind Harmer
0.475
226943AF1-005_GEN
Solar/Wind Harmer
0.991
972281AH1-725 GEN
50/50
200.318
233950AC2-186 GEN
Solar/Wind Helper
0.204
233952AC2-187 GEN
Solar/Wind Helper
0.407
233954AC2-188 GEN
Solar/Wind Helper
0.407
232422X3-066 FULL
Solar/Wind Helper
0.198
219919AE1-041 FULL
Solar/Wind Helper
0.007
219912AD2-042 GEN
Solar/Wind Helper
0.283
219914AD2-027 C
Solar/Wind Helper
0.216
NYPJM->LTFIMP_NY
CLTF
7.331
LGEELTFEXP_LGEE->PJM
CLTF
1.737
WECLTFEXP_WEC->PJM
CLTF
0.943
CPLELTFEXP_CPLE->PJM
CLTF
3.62
LAGNLTFEXP_LAGN->PJM
CLTF
5.509
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.367
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.454
TVALTFEXP_TVA->PJM
CLTF
2.767
MECLTFEXP_MEC->PJM
CLTF
4.239
SIGELTFEXP_SIGE->PJM
CLTF
0.133
CONTINGENCY 'AP_P2-3_PE-500-019E_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 1          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 3          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1          /*CHAN         500.0 - 01DOUBS      500.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 2                  /*01DOUBS      500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 235098 CKT 1 /*01DOUBS      500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-2_PE-500-3835T_SRT-A'
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'PECO_P4_PEACH025_SRT-A
 TRIP BRANCH FROM BUS 200013 TO BUS 200066 CKT Z1   /*PCHBTM2N     500.0 - PCHBTM1N     500.0
 TRIP BRANCH FROM BUS 200013 TO BUS 214347 CKT Z1   /*PCHBTM2N     500.0 - PBN_EXP_BAY  500.0
 TRIP BRANCH FROM BUS 270095 TO BUS 200066 CKT 1    /*CHAN         500.0 - PCHBTM1N     500.0
END
CONTINGENCY 'BG_P7_CNSTN_NWEST2_SRT-A'
 OPEN BRANCH FROM BUS 220961 TO BUS 220963 CKT 1   /*NWEST326     230.0 - CONASTON     230.0
 OPEN BRANCH FROM BUS 220962 TO BUS 220963 CKT 1   /*NWEST311     230.0 - CONASTON     230.0
END
CONTINGENCY 'PECO_P4_PEACH035_SRT-A
 DISCONNECT BUS 213791                             /*MDDYRN07     230.0
 DISCONNECT BUS 213794                             /*MDYRN5-6      13.8
 DISCONNECT BUS 213795                             /*MDYRN7-8      13.8
 DISCONNECT BUS 213866                             /*PCHBTM       230.0
 DISCONNECT BUS 213867                             /*PCHBTM        35.0
 TRIP BRANCH FROM BUS 200066 TO BUS 270095 CKT 1   /*PCHBTM1N     500.0 - CHAN         500.0
END
CONTINGENCY 'DPL_P4_2_KEENEY-ROCK AT50_SRT-A'
 OPEN LINE FROM BUS 200010 TO BUS 200051 CIRCUIT 1   /*KEENEY       500.0 - ROCKSPGS     500.0
 OPEN LINE FROM BUS 200010 TO BUS 231003 CIRCUIT 1   /*KEENEY       500.0 - KEEN_230     230.0
END
CONTINGENCY 'PECO_P1-2_5025_SRT-A
 TRIP BRANCH FROM BUS 200010 TO BUS 200051 CKT 1   /*KEENEY       500.0 - ROCKSPGS     500.0
END
200004 to 200003 ckt 1
200064 to 214347 ckt 2

Winter Peak Analysis

The New Service Request AH1-725 was evaluated as a 500.0 MW (500.0 MW Capacity) injection in the BGE area.

AH1-725 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 500.0 MW (500.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P1-2_PE-500-3835T_SRT-A
SingleAC128.38 %3507.0B4502.35
134.83
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019E_SRT-W
BreakerAC128.11 %3507.0B4492.66
135.03
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC111.87 %3507.0B3923.45
112.06
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
SingleAC108.79 %3507.0B3815.35
138.63
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
BG_P7_CNSTN_NWEST2_SRT-A
TowerAC101.98 %3507.0B3576.36
121.86

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-3835T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-3835T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.38 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:4502.35
MW Contribution:
134.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
43.046
200053ROCKSP 2
50/50
43.046
200054ROCKSP 3
50/50
42.609
200055ROCKSP 4
50/50
42.609
200203Y1-065-STG
50/50
5.765
200204Y1-065-CTG1
50/50
3.63
200205Y1-065-CTG2
50/50
3.63
3147043LAWRENC
Solar/Wind Helper
0.202
3147133PAMPLIN
Solar/Wind Helper
1.053
3147133PAMPLIN
Solar/Wind Helper
0.268
3147133PAMPLIN
Solar/Wind Helper
0.335
23546401DTGZ2-030
Solar/Wind Helper
0.057
20676328BVR_Y1-020
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
23777901MDS_W4-102
Solar/Wind Helper
0.106
3137176SLIGO L2192
Solar/Wind Helper
1.413
3141426STAFORD
Solar/Wind Helper
0.09
3141906WESTMOR
Solar/Wind Helper
0.151
3142416OLDCHRC
Solar/Wind Helper
0.959
3142416OLDCHRC
Solar/Wind Helper
0.367
3142433PROV 92
Solar/Wind Helper
1.466
3142956BIRDNECK
Solar/Wind Helper
0.591
3143316POE
Solar/Wind Helper
1.418
3145506HICKORY
Solar/Wind Helper
1.424
3145506HICKORY
Solar/Wind Helper
0.854
3145506HICKORY
Solar/Wind Helper
0.214
3146386ELIZ CT
Solar/Wind Helper
0.354
3146776BUCKING
Solar/Wind Helper
1.365
3146776BUCKING
Solar/Wind Helper
0.111
3146776BUCKING
Solar/Wind Helper
0.123
3146776BUCKING
Solar/Wind Helper
0.137
209027LOR2_Q27
Solar/Wind Harmer
4.58
212266LOR1
Solar/Wind Harmer
1.25
217081WEATEXAS C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
235020AA1-095 C
Solar/Wind Helper
0.023
316075AC2-137 C
Solar/Wind Helper
0.118
316077AC2-138 C
Solar/Wind Helper
0.084
3138133OCRAN
Solar/Wind Helper
0.111
3138133OCRAN
Solar/Wind Helper
0.221
3141766HARMONY
Solar/Wind Helper
0.073
3141783LANCAST
Solar/Wind Helper
0.221
3141783LANCAST
Solar/Wind Helper
0.148
3141813NORNECK
Solar/Wind Helper
0.373
3141913WHIT STONE
Solar/Wind Helper
0.368
3143226MDLTHAN
Solar/Wind Helper
0.366
3143873LANEXA
Solar/Wind Helper
0.22
3145273HOLLAND
Solar/Wind Helper
0.263
3146376EDENTON
Solar/Wind Helper
0.348
3146456SLIGO L269
Solar/Wind Helper
0.355
3146456SLIGO L269
Solar/Wind Helper
0.355
3146486SUNBURY
Solar/Wind Helper
0.353
3146486SUNBURY
Solar/Wind Helper
0.353
3146516WINFALL
Solar/Wind Helper
0.352
3146516WINFALL
Solar/Wind Helper
0.352
3146516WINFALL
Solar/Wind Helper
1.14
3146516WINFALL
Solar/Wind Helper
0.352
3146516WINFALL
Solar/Wind Helper
0.352
3146516WINFALL
Solar/Wind Helper
0.352
3146626S HERTFORD
Solar/Wind Helper
0.351
3146626S HERTFORD
Solar/Wind Helper
0.351
3146626S HERTFORD
Solar/Wind Helper
0.351
3146843MT LREL
Solar/Wind Helper
0.323
3146843MT LREL
Solar/Wind Helper
0.323
3146926FARMVIL
Solar/Wind Helper
0.204
3146926FARMVIL
Solar/Wind Helper
0.204
3147666LOUISA
Solar/Wind Helper
1.524
3147666LOUISA
Solar/Wind Helper
0.876
3147983MERCK5
Solar/Wind Helper
0.133
200034PCHBTM 2
50/50
99.353
200035PCHBTM 3
50/50
16.372
200192DELTA CT1
50/50
1.504
200193DELTA CT2
50/50
1.504
200194DELTA CT3
50/50
1.504
200195DELTA ST
50/50
2.506
3141726DUNNSVL
Solar/Wind Helper
1.49
3145663CRESWEL
Solar/Wind Helper
0.966
316034AC1-036 C
Solar/Wind Helper
0.074
316036AC1-147 C
Solar/Wind Helper
0.115
316059AD1-063 C
Solar/Wind Helper
0.089
316159AE1-175 C
Solar/Wind Helper
0.116
316240AF1-291 C
Solar/Wind Helper
0.116
316246AF1-032 C
Solar/Wind Helper
0.086
316248AF1-058 C
Solar/Wind Helper
0.102
316258AE1-075 C
Solar/Wind Helper
0.103
316305AF2-043 C
Solar/Wind Helper
0.114
316314AB2-024 C
Solar/Wind Helper
0.118
316315AB2-025 C
Solar/Wind Helper
0.113
316316AC1-027 C
Solar/Wind Helper
0.101
316317KELFORD C
Solar/Wind Helper
0.125
316382AG1-145 C
Solar/Wind Helper
0.117
316405AF2-144 C
Solar/Wind Helper
0.097
208835TUHI V3-051
Solar/Wind Harmer
0.06
208835TUHI V3-051
Solar/Wind Harmer
0.06
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
226910AB2-157 C
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Harmer
0.195
233970AC1-092 C
Solar/Wind Harmer
0.195
233971AC1-093 C
Solar/Wind Harmer
0.185
233972AC1-094 C
Solar/Wind Harmer
0.156
233973AC2-185 C
Solar/Wind Harmer
0.394
219727YARDVSOLFA C
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Helper
0.348
3130156CHOWAN
Solar/Wind Helper
0.348
3130156CHOWAN
Solar/Wind Helper
0.348
3145336SMITFLD
Solar/Wind Helper
1.434
3145336SMITFLD
Solar/Wind Helper
0.143
3148133STUARTS
Solar/Wind Helper
0.198
3141196NOKESVL
Solar/Wind Helper
1.648
3147243WELCO
Solar/Wind Helper
0.199
3141873WAN 176
Solar/Wind Helper
0.073
3143526WINTERP
Solar/Wind Helper
1.904
3143526WINTERP
Solar/Wind Helper
1.904
316411AF1-147_GEN1
Solar/Wind Helper
0.339
316415AF1-147_GEN2
Solar/Wind Helper
0.339
316404AE1-155 C
Solar/Wind Helper
0.758
316017AA1-139 ULT1
Solar/Wind Helper
0.342
316018AA1-139 ULT2
Solar/Wind Helper
0.342
316181AB2-040 GEN
Solar/Wind Helper
0.433
316033AB2-134 GEN
Solar/Wind Helper
0.826
316388AE2-253 GEN
Solar/Wind Helper
0.286
3148013FISHERV
Solar/Wind Helper
0.189
3148013FISHERV
Solar/Wind Helper
0.33
3145176PASQUOTANK
Solar/Wind Helper
0.219
3132123MT JACKSON
Solar/Wind Helper
1.053
3132273ORANGE
Solar/Wind Helper
0.077
3142543TWELFTH
Solar/Wind Helper
0.035
3144303KENBRDG
Solar/Wind Helper
0.266
3147173SINAI
Solar/Wind Helper
0.319
3148463FAIRFLD
Solar/Wind Helper
0.316
238175AF1-290_GEN
Solar/Wind Helper
0.482
238169AE2-226 GEN1
Solar/Wind Helper
0.294
238170AE2-226 GEN2
Solar/Wind Helper
0.294
316203AE2-005 GEN
Solar/Wind Helper
0.767
316441AF1-014 GEN
Solar/Wind Helper
0.117
316494AC1-189 GEN
Solar/Wind Helper
0.42
315616AA1-038_C
Solar/Wind Helper
1.903
316005AA1-067
Solar/Wind Helper
0.079
316426AA2-053 GEN
Solar/Wind Helper
0.404
316190AA2-174 GEN
Solar/Wind Helper
0.027
316327AA2-057 GEN
Solar/Wind Helper
0.394
3156081AA2-088 GEN
Solar/Wind Helper
0.551
315614AA2-178 GEN
Solar/Wind Helper
0.444
315816AE2-034 GEN
Solar/Wind Helper
0.333
316312AB1-027
Solar/Wind Helper
0.148
316049AB1-081 GEN
Solar/Wind Helper
0.415
316011AB1-132 GEN
Solar/Wind Helper
0.648
316369SG1_INVT
Solar/Wind Helper
0.568
315651AD1-115 GEN
Solar/Wind Helper
0.948
237061AD1-155 GEN
Solar/Wind Helper
0.427
316463AE2-346 GEN
Solar/Wind Helper
0.065
315839AE2-212 C
Solar/Wind Helper
0.116
315821AE2-092 GEN
Solar/Wind Helper
0.744
316499AE2-029_GEN
Solar/Wind Helper
0.265
315671AE2-027_GEN
Solar/Wind Helper
0.697
23583801GRNGAP
Solar/Wind Helper
8.496
233987AB2-037 GEN
Solar/Wind Harmer
0
315662AE1-191 GEN
Solar/Wind Helper
0.472
315666AE1-190 GEN
Solar/Wind Helper
0.118
319010AE1-072 C
Solar/Wind Helper
0.855
316065AD1-022 GEN
Solar/Wind Helper
0.439
315697AD1-025 GEN
Solar/Wind Helper
0.87
316185AD1-033 GEN
Solar/Wind Helper
0.401
316280AD1-041 GEN
Solar/Wind Helper
0.295
316478AD1-087 GEN
Solar/Wind Helper
0.345
316486AD2-202 GEN
Solar/Wind Helper
0.101
316447AC1-158 HLD
Solar/Wind Helper
1.016
316044AC1-158 PL1
Solar/Wind Helper
0.462
316045AC1-158 PL2
Solar/Wind Helper
1.478
316450AC1-158 RIC
Solar/Wind Helper
0.123
316468AD1-105 GEN
Solar/Wind Helper
0.45
316072AD1-144
Solar/Wind Helper
0.086
315687AD1-152 GEN
Solar/Wind Helper
0.421
316156AD2-030 GEN
Solar/Wind Helper
0.117
315785AD2-033 C
Solar/Wind Helper
0.694
316337AD2-073 GEN
Solar/Wind Helper
0.12
233968AD2-076_GEN
Solar/Wind Harmer
0.48
234012AE2-112_GEN
Solar/Wind Harmer
0.166
234014AF1-036_GEN
Solar/Wind Harmer
0.196
234015AF2-250 C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.089
207528AF2-192 GEN
Solar/Wind Harmer
0.06
226929AD2-058 GEN
Solar/Wind Helper
0.04
313526AB2-022
Solar/Wind Helper
0.114
316313AB2-026
Solar/Wind Helper
0.115
209120AE2-241 GEN
Solar/Wind Harmer
0.146
209093AE2-110 GEN
Solar/Wind Harmer
0.146
3145513AHOSKIE
Solar/Wind Helper
0.339
3145513AHOSKIE
Solar/Wind Helper
0.339
230430AE1-229_GEN
Solar/Wind Harmer
1.387
219623KINSLEYBEA C
Solar/Wind Harmer
0
208862AG1-362 C
Solar/Wind Harmer
0.037
209130AF1-271A GEN
Solar/Wind Harmer
0.122
209142AF1-226 GEN
Solar/Wind Harmer
0.256
205967AE2-211_GEN
Solar/Wind Harmer
0.453
205951AE1-129_GEN
Solar/Wind Harmer
0.468
270494AE1-108_GEN
Solar/Wind Helper
0.777
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
1.307
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3146206CASHIE
Solar/Wind Helper
0.341
3146206CASHIE
Solar/Wind Helper
0.341
3146206CASHIE
Solar/Wind Helper
0.341
3142666NORTHAMPTON
Solar/Wind Helper
0.336
3142666NORTHAMPTON
Solar/Wind Helper
0.336
3142666NORTHAMPTON
Solar/Wind Helper
0.336
3142666NORTHAMPTON
Solar/Wind Helper
0.202
3142666NORTHAMPTON
Solar/Wind Helper
0.336
316349AD2-085 GEN
Solar/Wind Helper
0.291
3156021HOLLOMANSOL
Solar/Wind Helper
0.544
313506AB2-031 GEN
Solar/Wind Helper
0.323
316006AB2-029 C
Solar/Wind Helper
0.127
313527AB2-043 GEN
Solar/Wind Helper
0.265
316322AB2-045
Solar/Wind Helper
0.109
316359AB2-059 GEN
Solar/Wind Helper
0.519
316131AB2-060 GEN
Solar/Wind Helper
0.425
316192AB2-158 GEN
Solar/Wind Helper
0.539
316083AB2-161 GEN
Solar/Wind Helper
0.287
316174AB2-169 GEN
Solar/Wind Helper
0.398
316087AB2-174 GEN
Solar/Wind Helper
0.434
316132AB2-190 GEN1
Solar/Wind Helper
0.436
316458AB2-190 GEN2
Solar/Wind Helper
0.436
316375AC2-012 GEN
Solar/Wind Helper
0.676
316339AD2-160 GEN
Solar/Wind Helper
0.286
316239AB2-077_GEN
Solar/Wind Helper
0.106
316238AB2-078_GEN
Solar/Wind Helper
0.106
316237AB2-079_GEN
Solar/Wind Helper
0.106
316140AB2-099
Solar/Wind Helper
0.027
316223AC1-118
Solar/Wind Helper
0.122
315975AC1-164 GENB
Solar/Wind Helper
0.029
315976AC1-164 GENA
Solar/Wind Helper
0.996
316169AC1-164_GENC
Solar/Wind Helper
0.86
316381AD1-082 GEN
Solar/Wind Helper
0.39
316233AE1-074 FULL
Solar/Wind Helper
0.118
316236AE1-162_GEN
Solar/Wind Helper
0.115
315607AA1-063A GEN
Solar/Wind Helper
0.407
233964AF2-378 GEN
Solar/Wind Harmer
0
3130546PLYMOUTH
Solar/Wind Helper
0.343
3145543BTLEBRO
Solar/Wind Helper
0.258
3145543BTLEBRO
Solar/Wind Helper
0.323
3145543BTLEBRO
Solar/Wind Helper
0.323
3145543BTLEBRO
Solar/Wind Helper
0.323
3145593CAROLNA
Solar/Wind Helper
0.336
3145593CAROLNA
Solar/Wind Helper
0.336
3145683EARLEYS
Solar/Wind Helper
0.338
3145683EARLEYS
Solar/Wind Helper
0.338
3145683EARLEYS
Solar/Wind Helper
0.338
3145683EARLEYS
Solar/Wind Helper
0.677
200200DELTA2 CT1
50/50
2.837
200201DELTA2 CT2
50/50
2.837
200202DELTA2 ST
50/50
5.068
207511W3-106 GEN
Solar/Wind Harmer
0
208972BECR K09
Solar/Wind Harmer
1.195
209029WAYMART-WD
Solar/Wind Harmer
2.938
230407AD2-065 C
Solar/Wind Harmer
0
3130086AYDLETT
Solar/Wind Helper
1.419
3137643SOCKMAN
Solar/Wind Helper
1.344
3138216PACIFIC
Solar/Wind Helper
0.071
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.015
3138543CONSLDL
Solar/Wind Helper
0.214
3142946ENON
Solar/Wind Helper
0.037
3142946ENON
Solar/Wind Helper
0.122
3144536CHRHLND
Solar/Wind Helper
0.054
3144873MCLAUGH
Solar/Wind Helper
0.009
3145573BETHELC
Solar/Wind Helper
0.325
3145573BETHELC
Solar/Wind Helper
0.325
3145783HORNRTN
Solar/Wind Helper
0.335
3145796HORNRTN
Solar/Wind Helper
1.002
3145796HORNRTN
Solar/Wind Helper
1.102
3145796HORNRTN
Solar/Wind Helper
0.334
3145796HORNRTN
Solar/Wind Helper
0.334
3145796HORNRTN
Solar/Wind Helper
1.336
3145796HORNRTN
Solar/Wind Helper
1.069
3145796HORNRTN
Solar/Wind Helper
0.134
3145823KELFORD
Solar/Wind Helper
0.336
3145823KELFORD
Solar/Wind Helper
0.336
3145893MURPHYS
Solar/Wind Helper
1.091
3145893MURPHYS
Solar/Wind Helper
0.614
3145893MURPHYS
Solar/Wind Helper
0.273
3145893MURPHYS
Solar/Wind Helper
0.341
3145893MURPHYS
Solar/Wind Helper
1.364
3145893MURPHYS
Solar/Wind Helper
0.341
3145893MURPHYS
Solar/Wind Helper
0.921
3145933PARMELE
Solar/Wind Helper
0.662
3145933PARMELE
Solar/Wind Helper
0.331
3145933PARMELE
Solar/Wind Helper
0.331
3145963POPLR C
Solar/Wind Helper
0.336
3145963POPLR C
Solar/Wind Helper
0.336
3146033SCOT NK
Solar/Wind Helper
1.334
3146043SEABORD
Solar/Wind Helper
0.339
3146073TAR RVR
Solar/Wind Helper
0.325
3146083TARBORO
Solar/Wind Helper
0.325
3146083TARBORO
Solar/Wind Helper
0.325
3146173TUNIS
Solar/Wind Helper
0.34
3146173TUNIS
Solar/Wind Helper
0.34
3146173TUNIS
Solar/Wind Helper
0.34
3146173TUNIS
Solar/Wind Helper
0.34
3146233WITAKRS
Solar/Wind Helper
1.293
3146233WITAKRS
Solar/Wind Helper
0.221
3146263WOODLND
Solar/Wind Helper
0.338
3146263WOODLND
Solar/Wind Helper
0.338
315611Z1-036_GEN2
Solar/Wind Helper
2.541
315800Z1-036_GEN1
Solar/Wind Helper
2.541
316095T157 G97
Solar/Wind Helper
1.272
316097T157 G90
Solar/Wind Helper
1.272
316318V4-068
Solar/Wind Helper
0.026
316319Z2-044 C
Solar/Wind Helper
0.063
316320Y1-086
Solar/Wind Helper
0.114
316321Z2-027
Solar/Wind Helper
0.113
942461AE2-259 GEN
Solar/Wind Helper
0.542
944491AF1-114 GEN
Solar/Wind Helper
0.618
946281AF1-292 GEN
Solar/Wind Helper
0.081
961541AF2-445A GEN
Solar/Wind Harmer
0.146
961611AG1-000B GEN
Solar/Wind Helper
0.515
961671AG1-007 GEN
Solar/Wind Helper
0.049
961941AG1-037 GEN
Solar/Wind Helper
0.027
961951AG1-038 GEN
Solar/Wind Helper
0.268
963401AG1-189 GEN
Solar/Wind Harmer
0.107
966871AG1-558 GEN
Solar/Wind Helper
0.119
966881AG1-559 GEN
Solar/Wind Helper
0.123
970025AG2-016 GEN
Solar/Wind Harmer
0.176
970095AG2-074 GEN
Solar/Wind Harmer
0.284
970453AG2-297 GEN
Solar/Wind Harmer
0.178
970597AG2-380 GEN
Solar/Wind Harmer
3.915
970695AG2-447 GEN
Solar/Wind Harmer
0.197
970997AG2-616 GEN
Solar/Wind Harmer
0.465
971007AG2-625 GEN
Solar/Wind Harmer
0.16
971009AG2-626 GEN
Solar/Wind Harmer
0.102
971189AH1-054 GEN
Solar/Wind Harmer
0.073
971195AH1-057 GEN
Solar/Wind Harmer
0.071
971519AH1-257 GEN
Solar/Wind Harmer
0.157
971521AH1-258 GEN
Solar/Wind Harmer
0.168
971667AH1-334 GEN
Solar/Wind Harmer
0.171
219918AC2-009 C
Solar/Wind Harmer
0
316431W1029_GEN1
Solar/Wind Helper
1.883
316433W1029_GEN2
Solar/Wind Helper
1.883
316435W1029_GEN3
Solar/Wind Helper
1.883
940641AE2-051 GEN
Solar/Wind Helper
0.855
957601AF2-054 GEN
Solar/Wind Helper
0.117
957831AF2-077 GEN
Solar/Wind Helper
0.117
957971AF2-091 GEN
Solar/Wind Helper
0.21
964211AG1-282 GEN
Solar/Wind Helper
0.12
964441AG1-307 GEN
Solar/Wind Helper
0.473
966001AG1-469 GEN
Solar/Wind Helper
0.085
966621AG1-532 GEN
Solar/Wind Helper
0.073
972141AH1-641 GEN
Solar/Wind Harmer
0.139
972177AH1-672 GEN
Solar/Wind Harmer
0.738
972281AH1-725 GEN
50/50
134.827
233984AB2-036 GEN
Solar/Wind Harmer
0.902
234041AC1-190 GEN
Solar/Wind Harmer
0.492
315732AD1-074 GEN1
Solar/Wind Helper
0.825
315733AD1-074 GEN2
Solar/Wind Helper
0.825
315735AD1-075 GEN1
Solar/Wind Helper
0.413
315737AD1-076 GEN
Solar/Wind Helper
0.6
315773AC2-141 GEN
Solar/Wind Helper
1.381
316003AC1-222 GEN
Solar/Wind Helper
0.328
316023GEN1_S
Solar/Wind Helper
0.274
316118AC1-105 GEN
Solar/Wind Helper
0.263
316129AC1-054 GEN
Solar/Wind Helper
0.346
316164AC1-076 GEN
Solar/Wind Helper
0.394
316210AC1-098 GEN
Solar/Wind Helper
0.479
316212AC1-099_GEN
Solar/Wind Helper
0.266
316274AC1-208 GEN
Solar/Wind Helper
0.425
316294AC1-161 GEN
Solar/Wind Helper
1.381
316365GEN2_N
Solar/Wind Helper
0.274
316420AA1-050 GEN
Solar/Wind Helper
0.418
316473AC1-191 GEN
Solar/Wind Helper
0.477
227287AC2-120 GEN
Solar/Wind Helper
0.197
238147AE2-230_GEN1
Solar/Wind Helper
0.201
238148AE2-230_GEN2
Solar/Wind Helper
0.201
238149AF1-291A_GEN
Solar/Wind Helper
0.057
238152AF2-075_GEN
Solar/Wind Helper
0.287
230422AE1-104_GEN1
Solar/Wind Harmer
38.509
230425AE1-104_GEN2
Solar/Wind Harmer
38.509
234033AF1-007_GEN
Solar/Wind Harmer
48.189
316487AF1-042 GEN
Solar/Wind Helper
0.268
315833AF1-017_GEN
Solar/Wind Helper
0.228
316484AD2-074 GEN
Solar/Wind Helper
0.512
207500AE2-000G1
Solar/Wind Harmer
34.99
207497AE2-000G2
Solar/Wind Harmer
34.99
207507AE2-000G3
Solar/Wind Harmer
34.99
207487AE2-000G4
Solar/Wind Harmer
34.99
CBM NorthLTFEXP_CBM-N->PJM
CBM
63.083
G-007ALTFEXP_G-007A->PJM
CMTX
41.37
VFTLTFEXP_VFT->PJM
CMTX
109.253
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.343
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.082
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
18.051
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.78
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.788
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019E_SRT-W


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019E_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.11 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:4492.66
MW Contribution:
135.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
43.134
200053ROCKSP 2
50/50
43.134
200054ROCKSP 3
50/50
42.696
200055ROCKSP 4
50/50
42.696
200203Y1-065-STG
50/50
5.777
200204Y1-065-CTG1
50/50
3.637
200205Y1-065-CTG2
50/50
3.637
3147043LAWRENC
Solar/Wind Helper
0.202
3147133PAMPLIN
Solar/Wind Helper
1.056
3147133PAMPLIN
Solar/Wind Helper
0.269
3147133PAMPLIN
Solar/Wind Helper
0.336
23546401DTGZ2-030
Solar/Wind Helper
0.057
20676328BVR_Y1-020
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
23777901MDS_W4-102
Solar/Wind Helper
0.104
3137176SLIGO L2192
Solar/Wind Helper
1.417
3141426STAFORD
Solar/Wind Helper
0.09
3141906WESTMOR
Solar/Wind Helper
0.152
3142416OLDCHRC
Solar/Wind Helper
0.961
3142416OLDCHRC
Solar/Wind Helper
0.368
3142433PROV 92
Solar/Wind Helper
1.47
3142956BIRDNECK
Solar/Wind Helper
0.593
3143316POE
Solar/Wind Helper
1.422
3145506HICKORY
Solar/Wind Helper
1.427
3145506HICKORY
Solar/Wind Helper
0.856
3145506HICKORY
Solar/Wind Helper
0.214
3146386ELIZ CT
Solar/Wind Helper
0.354
3146776BUCKING
Solar/Wind Helper
1.369
3146776BUCKING
Solar/Wind Helper
0.111
3146776BUCKING
Solar/Wind Helper
0.123
3146776BUCKING
Solar/Wind Helper
0.137
209027LOR2_Q27
Solar/Wind Harmer
4.593
212266LOR1
Solar/Wind Harmer
1.254
217081WEATEXAS C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
235020AA1-095 C
Solar/Wind Helper
0.022
316075AC2-137 C
Solar/Wind Helper
0.118
316077AC2-138 C
Solar/Wind Helper
0.084
3138133OCRAN
Solar/Wind Helper
0.111
3138133OCRAN
Solar/Wind Helper
0.221
3141766HARMONY
Solar/Wind Helper
0.074
3141783LANCAST
Solar/Wind Helper
0.222
3141783LANCAST
Solar/Wind Helper
0.148
3141813NORNECK
Solar/Wind Helper
0.374
3141913WHIT STONE
Solar/Wind Helper
0.369
3143226MDLTHAN
Solar/Wind Helper
0.366
3143873LANEXA
Solar/Wind Helper
0.221
3145273HOLLAND
Solar/Wind Helper
0.264
3146376EDENTON
Solar/Wind Helper
0.349
3146456SLIGO L269
Solar/Wind Helper
0.356
3146456SLIGO L269
Solar/Wind Helper
0.356
3146486SUNBURY
Solar/Wind Helper
0.354
3146486SUNBURY
Solar/Wind Helper
0.354
3146516WINFALL
Solar/Wind Helper
0.353
3146516WINFALL
Solar/Wind Helper
0.353
3146516WINFALL
Solar/Wind Helper
1.143
3146516WINFALL
Solar/Wind Helper
0.353
3146516WINFALL
Solar/Wind Helper
0.353
3146516WINFALL
Solar/Wind Helper
0.353
3146626S HERTFORD
Solar/Wind Helper
0.352
3146626S HERTFORD
Solar/Wind Helper
0.352
3146626S HERTFORD
Solar/Wind Helper
0.352
3146843MT LREL
Solar/Wind Helper
0.324
3146843MT LREL
Solar/Wind Helper
0.324
3146926FARMVIL
Solar/Wind Helper
0.204
3146926FARMVIL
Solar/Wind Helper
0.204
3147666LOUISA
Solar/Wind Helper
1.528
3147666LOUISA
Solar/Wind Helper
0.879
3147983MERCK5
Solar/Wind Helper
0.133
200034PCHBTM 2
50/50
99.55
200035PCHBTM 3
50/50
16.404
200192DELTA CT1
50/50
1.507
200193DELTA CT2
50/50
1.507
200194DELTA CT3
50/50
1.507
200195DELTA ST
50/50
2.511
3141726DUNNSVL
Solar/Wind Helper
1.493
3145663CRESWEL
Solar/Wind Helper
0.969
316034AC1-036 C
Solar/Wind Helper
0.074
316036AC1-147 C
Solar/Wind Helper
0.115
316059AD1-063 C
Solar/Wind Helper
0.089
316159AE1-175 C
Solar/Wind Helper
0.116
316240AF1-291 C
Solar/Wind Helper
0.117
316246AF1-032 C
Solar/Wind Helper
0.086
316248AF1-058 C
Solar/Wind Helper
0.103
316258AE1-075 C
Solar/Wind Helper
0.103
316305AF2-043 C
Solar/Wind Helper
0.114
316314AB2-024 C
Solar/Wind Helper
0.118
316315AB2-025 C
Solar/Wind Helper
0.113
316316AC1-027 C
Solar/Wind Helper
0.101
316317KELFORD C
Solar/Wind Helper
0.125
316382AG1-145 C
Solar/Wind Helper
0.117
316405AF2-144 C
Solar/Wind Helper
0.098
208835TUHI V3-051
Solar/Wind Harmer
0.06
208835TUHI V3-051
Solar/Wind Harmer
0.06
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
226910AB2-157 C
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Harmer
0.195
233970AC1-092 C
Solar/Wind Harmer
0.195
233971AC1-093 C
Solar/Wind Harmer
0.185
233972AC1-094 C
Solar/Wind Harmer
0.157
233973AC2-185 C
Solar/Wind Harmer
0.394
219727YARDVSOLFA C
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Helper
0.349
3130156CHOWAN
Solar/Wind Helper
0.349
3130156CHOWAN
Solar/Wind Helper
0.349
3145336SMITFLD
Solar/Wind Helper
1.438
3145336SMITFLD
Solar/Wind Helper
0.144
3148133STUARTS
Solar/Wind Helper
0.198
3141196NOKESVL
Solar/Wind Helper
1.653
3147243WELCO
Solar/Wind Helper
0.2
3141873WAN 176
Solar/Wind Helper
0.074
3143526WINTERP
Solar/Wind Helper
1.908
3143526WINTERP
Solar/Wind Helper
1.908
316411AF1-147_GEN1
Solar/Wind Helper
0.34
316415AF1-147_GEN2
Solar/Wind Helper
0.34
316404AE1-155 C
Solar/Wind Helper
0.759
316017AA1-139 ULT1
Solar/Wind Helper
0.343
316018AA1-139 ULT2
Solar/Wind Helper
0.343
316181AB2-040 GEN
Solar/Wind Helper
0.435
316033AB2-134 GEN
Solar/Wind Helper
0.828
316388AE2-253 GEN
Solar/Wind Helper
0.286
3148013FISHERV
Solar/Wind Helper
0.19
3148013FISHERV
Solar/Wind Helper
0.331
3145176PASQUOTANK
Solar/Wind Helper
0.219
3132123MT JACKSON
Solar/Wind Helper
1.055
3132273ORANGE
Solar/Wind Helper
0.077
3142543TWELFTH
Solar/Wind Helper
0.035
3144303KENBRDG
Solar/Wind Helper
0.267
3147173SINAI
Solar/Wind Helper
0.32
3148463FAIRFLD
Solar/Wind Helper
0.316
238175AF1-290_GEN
Solar/Wind Helper
0.478
238169AE2-226 GEN1
Solar/Wind Helper
0.292
238170AE2-226 GEN2
Solar/Wind Helper
0.292
316203AE2-005 GEN
Solar/Wind Helper
0.769
316441AF1-014 GEN
Solar/Wind Helper
0.118
316494AC1-189 GEN
Solar/Wind Helper
0.421
315616AA1-038_C
Solar/Wind Helper
1.909
316005AA1-067
Solar/Wind Helper
0.079
316426AA2-053 GEN
Solar/Wind Helper
0.405
316190AA2-174 GEN
Solar/Wind Helper
0.027
316327AA2-057 GEN
Solar/Wind Helper
0.395
3156081AA2-088 GEN
Solar/Wind Helper
0.552
315614AA2-178 GEN
Solar/Wind Helper
0.445
315816AE2-034 GEN
Solar/Wind Helper
0.334
316312AB1-027
Solar/Wind Helper
0.148
316049AB1-081 GEN
Solar/Wind Helper
0.416
316011AB1-132 GEN
Solar/Wind Helper
0.65
316369SG1_INVT
Solar/Wind Helper
0.569
315651AD1-115 GEN
Solar/Wind Helper
0.95
237061AD1-155 GEN
Solar/Wind Helper
0.428
316463AE2-346 GEN
Solar/Wind Helper
0.066
315839AE2-212 C
Solar/Wind Helper
0.116
315821AE2-092 GEN
Solar/Wind Helper
0.746
316499AE2-029_GEN
Solar/Wind Helper
0.266
315671AE2-027_GEN
Solar/Wind Helper
0.699
23583801GRNGAP
Solar/Wind Helper
8.529
233987AB2-037 GEN
Solar/Wind Harmer
0
315662AE1-191 GEN
Solar/Wind Helper
0.473
315666AE1-190 GEN
Solar/Wind Helper
0.118
319010AE1-072 C
Solar/Wind Helper
0.858
316065AD1-022 GEN
Solar/Wind Helper
0.44
315697AD1-025 GEN
Solar/Wind Helper
0.872
316185AD1-033 GEN
Solar/Wind Helper
0.402
316280AD1-041 GEN
Solar/Wind Helper
0.296
316478AD1-087 GEN
Solar/Wind Helper
0.346
316486AD2-202 GEN
Solar/Wind Helper
0.101
316447AC1-158 HLD
Solar/Wind Helper
1.019
316044AC1-158 PL1
Solar/Wind Helper
0.463
316045AC1-158 PL2
Solar/Wind Helper
1.481
316450AC1-158 RIC
Solar/Wind Helper
0.123
316468AD1-105 GEN
Solar/Wind Helper
0.451
316072AD1-144
Solar/Wind Helper
0.086
315687AD1-152 GEN
Solar/Wind Helper
0.422
316156AD2-030 GEN
Solar/Wind Helper
0.117
315785AD2-033 C
Solar/Wind Helper
0.696
316337AD2-073 GEN
Solar/Wind Helper
0.12
233968AD2-076_GEN
Solar/Wind Harmer
0.481
234012AE2-112_GEN
Solar/Wind Harmer
0.167
234014AF1-036_GEN
Solar/Wind Harmer
0.196
234015AF2-250 C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.09
207528AF2-192 GEN
Solar/Wind Harmer
0.06
226929AD2-058 GEN
Solar/Wind Helper
0.04
313526AB2-022
Solar/Wind Helper
0.114
316313AB2-026
Solar/Wind Helper
0.115
209120AE2-241 GEN
Solar/Wind Harmer
0.147
209093AE2-110 GEN
Solar/Wind Harmer
0.147
3145513AHOSKIE
Solar/Wind Helper
0.34
3145513AHOSKIE
Solar/Wind Helper
0.34
230430AE1-229_GEN
Solar/Wind Harmer
1.391
219623KINSLEYBEA C
Solar/Wind Harmer
0
208862AG1-362 C
Solar/Wind Harmer
0.037
209130AF1-271A GEN
Solar/Wind Harmer
0.122
209142AF1-226 GEN
Solar/Wind Harmer
0.257
205967AE2-211_GEN
Solar/Wind Harmer
0.456
205951AE1-129_GEN
Solar/Wind Harmer
0.471
270494AE1-108_GEN
Solar/Wind Helper
0.78
3145746EVERETS
Solar/Wind Helper
0.329
3145746EVERETS
Solar/Wind Helper
0.329
3145746EVERETS
Solar/Wind Helper
0.329
3145746EVERETS
Solar/Wind Helper
0.329
3145746EVERETS
Solar/Wind Helper
1.31
3145746EVERETS
Solar/Wind Helper
0.329
3145746EVERETS
Solar/Wind Helper
0.329
3145746EVERETS
Solar/Wind Helper
0.329
3146206CASHIE
Solar/Wind Helper
0.342
3146206CASHIE
Solar/Wind Helper
0.342
3146206CASHIE
Solar/Wind Helper
0.342
3142666NORTHAMPTON
Solar/Wind Helper
0.337
3142666NORTHAMPTON
Solar/Wind Helper
0.337
3142666NORTHAMPTON
Solar/Wind Helper
0.337
3142666NORTHAMPTON
Solar/Wind Helper
0.202
3142666NORTHAMPTON
Solar/Wind Helper
0.337
316349AD2-085 GEN
Solar/Wind Helper
0.292
3156021HOLLOMANSOL
Solar/Wind Helper
0.546
313506AB2-031 GEN
Solar/Wind Helper
0.324
316006AB2-029 C
Solar/Wind Helper
0.128
313527AB2-043 GEN
Solar/Wind Helper
0.265
316322AB2-045
Solar/Wind Helper
0.109
316359AB2-059 GEN
Solar/Wind Helper
0.52
316131AB2-060 GEN
Solar/Wind Helper
0.426
316192AB2-158 GEN
Solar/Wind Helper
0.541
316083AB2-161 GEN
Solar/Wind Helper
0.288
316174AB2-169 GEN
Solar/Wind Helper
0.399
316087AB2-174 GEN
Solar/Wind Helper
0.435
316132AB2-190 GEN1
Solar/Wind Helper
0.437
316458AB2-190 GEN2
Solar/Wind Helper
0.437
316375AC2-012 GEN
Solar/Wind Helper
0.678
316339AD2-160 GEN
Solar/Wind Helper
0.286
316239AB2-077_GEN
Solar/Wind Helper
0.106
316238AB2-078_GEN
Solar/Wind Helper
0.106
316237AB2-079_GEN
Solar/Wind Helper
0.106
316140AB2-099
Solar/Wind Helper
0.027
316223AC1-118
Solar/Wind Helper
0.122
315975AC1-164 GENB
Solar/Wind Helper
0.03
315976AC1-164 GENA
Solar/Wind Helper
0.998
316169AC1-164_GENC
Solar/Wind Helper
0.862
316381AD1-082 GEN
Solar/Wind Helper
0.391
316233AE1-074 FULL
Solar/Wind Helper
0.118
316236AE1-162_GEN
Solar/Wind Helper
0.115
315607AA1-063A GEN
Solar/Wind Helper
0.408
233964AF2-378 GEN
Solar/Wind Harmer
0
3130546PLYMOUTH
Solar/Wind Helper
0.344
3145543BTLEBRO
Solar/Wind Helper
0.259
3145543BTLEBRO
Solar/Wind Helper
0.324
3145543BTLEBRO
Solar/Wind Helper
0.324
3145543BTLEBRO
Solar/Wind Helper
0.324
3145593CAROLNA
Solar/Wind Helper
0.336
3145593CAROLNA
Solar/Wind Helper
0.336
3145683EARLEYS
Solar/Wind Helper
0.339
3145683EARLEYS
Solar/Wind Helper
0.339
3145683EARLEYS
Solar/Wind Helper
0.339
3145683EARLEYS
Solar/Wind Helper
0.678
200200DELTA2 CT1
50/50
2.843
200201DELTA2 CT2
50/50
2.843
200202DELTA2 ST
50/50
5.078
207511W3-106 GEN
Solar/Wind Harmer
0
208972BECR K09
Solar/Wind Harmer
1.198
209029WAYMART-WD
Solar/Wind Harmer
2.946
230407AD2-065 C
Solar/Wind Harmer
0
3130086AYDLETT
Solar/Wind Helper
1.423
3137643SOCKMAN
Solar/Wind Helper
1.347
3138216PACIFIC
Solar/Wind Helper
0.071
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.015
3138543CONSLDL
Solar/Wind Helper
0.215
3142946ENON
Solar/Wind Helper
0.037
3142946ENON
Solar/Wind Helper
0.122
3144536CHRHLND
Solar/Wind Helper
0.054
3144873MCLAUGH
Solar/Wind Helper
0.009
3145573BETHELC
Solar/Wind Helper
0.326
3145573BETHELC
Solar/Wind Helper
0.326
3145783HORNRTN
Solar/Wind Helper
0.336
3145796HORNRTN
Solar/Wind Helper
1.005
3145796HORNRTN
Solar/Wind Helper
1.105
3145796HORNRTN
Solar/Wind Helper
0.335
3145796HORNRTN
Solar/Wind Helper
0.335
3145796HORNRTN
Solar/Wind Helper
1.34
3145796HORNRTN
Solar/Wind Helper
1.072
3145796HORNRTN
Solar/Wind Helper
0.134
3145823KELFORD
Solar/Wind Helper
0.337
3145823KELFORD
Solar/Wind Helper
0.337
3145893MURPHYS
Solar/Wind Helper
1.094
3145893MURPHYS
Solar/Wind Helper
0.615
3145893MURPHYS
Solar/Wind Helper
0.273
3145893MURPHYS
Solar/Wind Helper
0.342
3145893MURPHYS
Solar/Wind Helper
1.367
3145893MURPHYS
Solar/Wind Helper
0.342
3145893MURPHYS
Solar/Wind Helper
0.923
3145933PARMELE
Solar/Wind Helper
0.663
3145933PARMELE
Solar/Wind Helper
0.332
3145933PARMELE
Solar/Wind Helper
0.332
3145963POPLR C
Solar/Wind Helper
0.337
3145963POPLR C
Solar/Wind Helper
0.337
3146033SCOT NK
Solar/Wind Helper
1.337
3146043SEABORD
Solar/Wind Helper
0.339
3146073TAR RVR
Solar/Wind Helper
0.326
3146083TARBORO
Solar/Wind Helper
0.326
3146083TARBORO
Solar/Wind Helper
0.326
3146173TUNIS
Solar/Wind Helper
0.341
3146173TUNIS
Solar/Wind Helper
0.341
3146173TUNIS
Solar/Wind Helper
0.341
3146173TUNIS
Solar/Wind Helper
0.341
3146233WITAKRS
Solar/Wind Helper
1.297
3146233WITAKRS
Solar/Wind Helper
0.222
3146263WOODLND
Solar/Wind Helper
0.338
3146263WOODLND
Solar/Wind Helper
0.338
315611Z1-036_GEN2
Solar/Wind Helper
2.548
315800Z1-036_GEN1
Solar/Wind Helper
2.548
316095T157 G97
Solar/Wind Helper
1.277
316097T157 G90
Solar/Wind Helper
1.277
316318V4-068
Solar/Wind Helper
0.026
316319Z2-044 C
Solar/Wind Helper
0.063
316320Y1-086
Solar/Wind Helper
0.114
316321Z2-027
Solar/Wind Helper
0.114
942461AE2-259 GEN
Solar/Wind Helper
0.544
944491AF1-114 GEN
Solar/Wind Helper
0.619
946281AF1-292 GEN
Solar/Wind Helper
0.081
961541AF2-445A GEN
Solar/Wind Harmer
0.147
961611AG1-000B GEN
Solar/Wind Helper
0.516
961671AG1-007 GEN
Solar/Wind Helper
0.049
961941AG1-037 GEN
Solar/Wind Helper
0.027
961951AG1-038 GEN
Solar/Wind Helper
0.268
963401AG1-189 GEN
Solar/Wind Harmer
0.107
966871AG1-558 GEN
Solar/Wind Helper
0.12
966881AG1-559 GEN
Solar/Wind Helper
0.124
970025AG2-016 GEN
Solar/Wind Harmer
0.177
970095AG2-074 GEN
Solar/Wind Harmer
0.285
970453AG2-297 GEN
Solar/Wind Harmer
0.178
970597AG2-380 GEN
Solar/Wind Harmer
3.924
970695AG2-447 GEN
Solar/Wind Harmer
0.197
970997AG2-616 GEN
Solar/Wind Harmer
0.466
971007AG2-625 GEN
Solar/Wind Harmer
0.16
971009AG2-626 GEN
Solar/Wind Harmer
0.102
971189AH1-054 GEN
Solar/Wind Harmer
0.074
971195AH1-057 GEN
Solar/Wind Harmer
0.071
971519AH1-257 GEN
Solar/Wind Harmer
0.157
971521AH1-258 GEN
Solar/Wind Harmer
0.169
971667AH1-334 GEN
Solar/Wind Harmer
0.172
219918AC2-009 C
Solar/Wind Harmer
0
316431W1029_GEN1
Solar/Wind Helper
1.888
316433W1029_GEN2
Solar/Wind Helper
1.888
316435W1029_GEN3
Solar/Wind Helper
1.888
940641AE2-051 GEN
Solar/Wind Helper
0.857
957601AF2-054 GEN
Solar/Wind Helper
0.118
957831AF2-077 GEN
Solar/Wind Helper
0.117
957971AF2-091 GEN
Solar/Wind Helper
0.21
964211AG1-282 GEN
Solar/Wind Helper
0.12
964441AG1-307 GEN
Solar/Wind Helper
0.47
966001AG1-469 GEN
Solar/Wind Helper
0.085
966621AG1-532 GEN
Solar/Wind Helper
0.074
972141AH1-641 GEN
Solar/Wind Harmer
0.14
972177AH1-672 GEN
Solar/Wind Harmer
0.739
972281AH1-725 GEN
50/50
135.033
233984AB2-036 GEN
Solar/Wind Harmer
0.904
234041AC1-190 GEN
Solar/Wind Harmer
0.493
315732AD1-074 GEN1
Solar/Wind Helper
0.827
315733AD1-074 GEN2
Solar/Wind Helper
0.827
315735AD1-075 GEN1
Solar/Wind Helper
0.414
315737AD1-076 GEN
Solar/Wind Helper
0.601
315773AC2-141 GEN
Solar/Wind Helper
1.384
316003AC1-222 GEN
Solar/Wind Helper
0.329
316023GEN1_S
Solar/Wind Helper
0.275
316118AC1-105 GEN
Solar/Wind Helper
0.264
316129AC1-054 GEN
Solar/Wind Helper
0.347
316164AC1-076 GEN
Solar/Wind Helper
0.395
316210AC1-098 GEN
Solar/Wind Helper
0.48
316212AC1-099_GEN
Solar/Wind Helper
0.267
316274AC1-208 GEN
Solar/Wind Helper
0.426
316294AC1-161 GEN
Solar/Wind Helper
1.384
316365GEN2_N
Solar/Wind Helper
0.275
316420AA1-050 GEN
Solar/Wind Helper
0.419
316473AC1-191 GEN
Solar/Wind Helper
0.479
227287AC2-120 GEN
Solar/Wind Helper
0.196
238147AE2-230_GEN1
Solar/Wind Helper
0.201
238148AE2-230_GEN2
Solar/Wind Helper
0.201
238149AF1-291A_GEN
Solar/Wind Helper
0.058
238152AF2-075_GEN
Solar/Wind Helper
0.288
230422AE1-104_GEN1
Solar/Wind Harmer
38.604
230425AE1-104_GEN2
Solar/Wind Harmer
38.604
234033AF1-007_GEN
Solar/Wind Harmer
48.3
316487AF1-042 GEN
Solar/Wind Helper
0.268
315833AF1-017_GEN
Solar/Wind Helper
0.229
316484AD2-074 GEN
Solar/Wind Helper
0.513
207500AE2-000G1
Solar/Wind Harmer
35.08
207497AE2-000G2
Solar/Wind Harmer
35.08
207507AE2-000G3
Solar/Wind Harmer
35.08
207487AE2-000G4
Solar/Wind Harmer
35.08
CBM NorthLTFEXP_CBM-N->PJM
CBM
63.26
G-007ALTFEXP_G-007A->PJM
CMTX
41.48
VFTLTFEXP_VFT->PJM
CMTX
109.55
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.359
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.091
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
18.113
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.793
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.829
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.87 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:3923.45
MW Contribution:
112.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
35.469
200053ROCKSP 2
50/50
35.469
200054ROCKSP 3
50/50
35.108
200055ROCKSP 4
50/50
35.108
200203Y1-065-STG
50/50
4.75
200204Y1-065-CTG1
50/50
2.991
200205Y1-065-CTG2
50/50
2.991
20676328BVR_Y1-020
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
3141426STAFORD
Solar/Wind Helper
0.078
3141906WESTMOR
Solar/Wind Helper
0.128
209027LOR2_Q27
Solar/Wind Harmer
3.742
212266LOR1
Solar/Wind Harmer
1.022
217081WEATEXAS C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
316077AC2-138 C
Solar/Wind Helper
0.07
3141813NORNECK
Solar/Wind Helper
0.313
3147666LOUISA
Solar/Wind Helper
1.259
3147666LOUISA
Solar/Wind Helper
0.724
200034PCHBTM 2
50/50
81.968
200035PCHBTM 3
50/50
13.502
200192DELTA CT1
50/50
1.241
200193DELTA CT2
50/50
1.241
200194DELTA CT3
50/50
1.241
200195DELTA ST
50/50
2.067
3141726DUNNSVL
Solar/Wind Helper
1.249
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
226910AB2-157 C
Solar/Wind Helper
0.022
233939AC1-091 C
Solar/Wind Harmer
0.159
233970AC1-092 C
Solar/Wind Harmer
0.159
233971AC1-093 C
Solar/Wind Harmer
0.151
233972AC1-094 C
Solar/Wind Harmer
0.128
233973AC2-185 C
Solar/Wind Harmer
0.322
219727YARDVSOLFA C
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.338
316411AF1-147_GEN1
Solar/Wind Helper
0.271
316415AF1-147_GEN2
Solar/Wind Helper
0.271
3132273ORANGE
Solar/Wind Helper
0.063
315651AD1-115 GEN
Solar/Wind Helper
0.778
233987AB2-037 GEN
Solar/Wind Harmer
0
316447AC1-158 HLD
Solar/Wind Helper
0.84
316044AC1-158 PL1
Solar/Wind Helper
0.382
316045AC1-158 PL2
Solar/Wind Helper
1.221
316450AC1-158 RIC
Solar/Wind Helper
0.102
316468AD1-105 GEN
Solar/Wind Helper
0.379
316337AD2-073 GEN
Solar/Wind Helper
0.101
233968AD2-076_GEN
Solar/Wind Harmer
0.392
234012AE2-112_GEN
Solar/Wind Harmer
0.136
234014AF1-036_GEN
Solar/Wind Harmer
0.16
234015AF2-250 C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.073
207528AF2-192 GEN
Solar/Wind Harmer
0.049
226929AD2-058 GEN
Solar/Wind Helper
0.047
209120AE2-241 GEN
Solar/Wind Harmer
0.12
209093AE2-110 GEN
Solar/Wind Harmer
0.12
230430AE1-229_GEN
Solar/Wind Harmer
1.133
219623KINSLEYBEA C
Solar/Wind Harmer
0
208862AG1-362 C
Solar/Wind Harmer
0.029
209130AF1-271A GEN
Solar/Wind Harmer
0.1
209142AF1-226 GEN
Solar/Wind Harmer
0.209
316006AB2-029 C
Solar/Wind Helper
0.104
316192AB2-158 GEN
Solar/Wind Helper
0.445
316223AC1-118
Solar/Wind Helper
0.102
233964AF2-378 GEN
Solar/Wind Harmer
0
200200DELTA2 CT1
50/50
2.341
200201DELTA2 CT2
50/50
2.341
200202DELTA2 ST
50/50
4.182
207511W3-106 GEN
Solar/Wind Harmer
0
208972BECR K09
Solar/Wind Harmer
0.976
209029WAYMART-WD
Solar/Wind Harmer
2.403
230407AD2-065 C
Solar/Wind Harmer
0
3138216PACIFIC
Solar/Wind Helper
0.056
944491AF1-114 GEN
Solar/Wind Helper
0.524
961541AF2-445A GEN
Solar/Wind Harmer
0.119
963401AG1-189 GEN
Solar/Wind Harmer
0.087
966881AG1-559 GEN
Solar/Wind Helper
0.104
970025AG2-016 GEN
Solar/Wind Harmer
0.144
970095AG2-074 GEN
Solar/Wind Harmer
0.232
970453AG2-297 GEN
Solar/Wind Harmer
0.145
970597AG2-380 GEN
Solar/Wind Harmer
3.196
970695AG2-447 GEN
Solar/Wind Harmer
0.161
970997AG2-616 GEN
Solar/Wind Harmer
0.38
971007AG2-625 GEN
Solar/Wind Harmer
0.13
971009AG2-626 GEN
Solar/Wind Harmer
0.083
971189AH1-054 GEN
Solar/Wind Harmer
0.06
971195AH1-057 GEN
Solar/Wind Harmer
0.058
971519AH1-257 GEN
Solar/Wind Harmer
0.128
971521AH1-258 GEN
Solar/Wind Harmer
0.137
971667AH1-334 GEN
Solar/Wind Harmer
0.14
219918AC2-009 C
Solar/Wind Harmer
0
957971AF2-091 GEN
Solar/Wind Helper
0.178
964211AG1-282 GEN
Solar/Wind Helper
0.1
972141AH1-641 GEN
Solar/Wind Harmer
0.114
972177AH1-672 GEN
Solar/Wind Harmer
0.603
972281AH1-725 GEN
50/50
112.063
233984AB2-036 GEN
Solar/Wind Harmer
0.737
234041AC1-190 GEN
Solar/Wind Harmer
0.402
316164AC1-076 GEN
Solar/Wind Helper
0.325
227287AC2-120 GEN
Solar/Wind Helper
0.24
230422AE1-104_GEN1
Solar/Wind Harmer
31.452
230425AE1-104_GEN2
Solar/Wind Harmer
31.452
234033AF1-007_GEN
Solar/Wind Harmer
39.4
207500AE2-000G1
Solar/Wind Harmer
28.559
207497AE2-000G2
Solar/Wind Harmer
28.559
207507AE2-000G3
Solar/Wind Harmer
28.559
207487AE2-000G4
Solar/Wind Harmer
28.559
CBM NorthLTFEXP_CBM-N->PJM
CBM
51.929
G-007ALTFEXP_G-007A->PJM
CMTX
33.751
VFTLTFEXP_VFT->PJM
CMTX
89.117
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.279
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.447
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.767
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.864
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.936
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.79 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:3815.35
MW Contribution:
138.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
44.545
200053ROCKSP 2
50/50
44.545
200054ROCKSP 3
50/50
44.093
200055ROCKSP 4
50/50
44.093
200203Y1-065-STG
50/50
5.966
200204Y1-065-CTG1
50/50
3.756
200205Y1-065-CTG2
50/50
3.756
20676328BVR_Y1-020
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
3141426STAFORD
Solar/Wind Helper
0.073
217081WEATEXAS C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
200034PCHBTM 2
50/50
104.357
200035PCHBTM 3
50/50
17.262
200192DELTA CT1
50/50
1.58
200193DELTA CT2
50/50
1.58
200194DELTA CT3
50/50
1.58
200195DELTA ST
50/50
2.633
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
226910AB2-157 C
Solar/Wind Helper
0.015
233939AC1-091 C
Solar/Wind Harmer
0.186
233970AC1-092 C
Solar/Wind Harmer
0.186
233971AC1-093 C
Solar/Wind Harmer
0.176
233972AC1-094 C
Solar/Wind Harmer
0.149
233973AC2-185 C
Solar/Wind Harmer
0.375
219727YARDVSOLFA C
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.318
316411AF1-147_GEN1
Solar/Wind Helper
0.27
316415AF1-147_GEN2
Solar/Wind Helper
0.27
315651AD1-115 GEN
Solar/Wind Helper
0.762
233987AB2-037 GEN
Solar/Wind Harmer
0
316447AC1-158 HLD
Solar/Wind Helper
0.817
316044AC1-158 PL1
Solar/Wind Helper
0.372
316045AC1-158 PL2
Solar/Wind Helper
1.189
316450AC1-158 RIC
Solar/Wind Helper
0.099
233968AD2-076_GEN
Solar/Wind Harmer
0.458
234012AE2-112_GEN
Solar/Wind Harmer
0.159
234014AF1-036_GEN
Solar/Wind Harmer
0.187
234015AF2-250 C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.076
207528AF2-192 GEN
Solar/Wind Harmer
0.048
226929AD2-058 GEN
Solar/Wind Helper
0.034
230430AE1-229_GEN
Solar/Wind Harmer
1.243
219623KINSLEYBEA C
Solar/Wind Harmer
0
316006AB2-029 C
Solar/Wind Helper
0.102
233964AF2-378 GEN
Solar/Wind Harmer
0
200200DELTA2 CT1
50/50
2.981
200201DELTA2 CT2
50/50
2.981
200202DELTA2 ST
50/50
5.325
207511W3-106 GEN
Solar/Wind Harmer
0
208972BECR K09
Solar/Wind Harmer
0.835
209029WAYMART-WD
Solar/Wind Harmer
2.087
230407AD2-065 C
Solar/Wind Harmer
0
3138216PACIFIC
Solar/Wind Helper
0.056
963401AG1-189 GEN
Solar/Wind Harmer
0.091
970025AG2-016 GEN
Solar/Wind Harmer
0.15
970095AG2-074 GEN
Solar/Wind Harmer
0.2
970453AG2-297 GEN
Solar/Wind Harmer
0.16
970597AG2-380 GEN
Solar/Wind Harmer
3.737
970695AG2-447 GEN
Solar/Wind Harmer
0.188
970997AG2-616 GEN
Solar/Wind Harmer
0.417
971007AG2-625 GEN
Solar/Wind Harmer
0.121
971009AG2-626 GEN
Solar/Wind Harmer
0.077
971189AH1-054 GEN
Solar/Wind Harmer
0.062
971195AH1-057 GEN
Solar/Wind Harmer
0.068
971519AH1-257 GEN
Solar/Wind Harmer
0.118
971521AH1-258 GEN
Solar/Wind Harmer
0.139
971667AH1-334 GEN
Solar/Wind Harmer
0.145
219918AC2-009 C
Solar/Wind Harmer
0
972141AH1-641 GEN
Solar/Wind Harmer
0.125
972177AH1-672 GEN
Solar/Wind Harmer
0.704
972281AH1-725 GEN
50/50
138.626
233984AB2-036 GEN
Solar/Wind Harmer
0.862
234041AC1-190 GEN
Solar/Wind Harmer
0.47
316164AC1-076 GEN
Solar/Wind Helper
0.317
227287AC2-120 GEN
Solar/Wind Helper
0.168
230422AE1-104_GEN1
Solar/Wind Harmer
34.424
230425AE1-104_GEN2
Solar/Wind Harmer
34.424
234033AF1-007_GEN
Solar/Wind Harmer
46.015
207500AE2-000G1
Solar/Wind Harmer
29.823
207497AE2-000G2
Solar/Wind Harmer
29.823
207507AE2-000G3
Solar/Wind Harmer
29.823
207487AE2-000G4
Solar/Wind Harmer
29.823
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.024
G-007ALTFEXP_G-007A->PJM
CMTX
33.705
VFTLTFEXP_VFT->PJM
CMTX
87.012
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.392
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.542
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
15.191
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.189
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.945
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o BG_P7_CNSTN_NWEST2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
BG_P7_CNSTN_NWEST2_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.98 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:3576.36
MW Contribution:
121.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
32.729
200053ROCKSP 2
50/50
32.729
200054ROCKSP 3
50/50
32.397
200055ROCKSP 4
50/50
32.397
200203Y1-065-STG
50/50
4.383
200204Y1-065-CTG1
50/50
2.76
200205Y1-065-CTG2
50/50
2.76
20676328BVR_Y1-020
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
3141426STAFORD
Solar/Wind Helper
0.071
209027LOR2_Q27
Solar/Wind Harmer
3.36
212266LOR1
Solar/Wind Harmer
0.917
217081WEATEXAS C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
200034PCHBTM 2
50/50
75.618
200035PCHBTM 3
50/50
12.284
200058HUNTR101
50/50
1.508
200059HUNTR201
50/50
1.508
200060HUNTR301
50/50
1.508
200061HUNTR401
50/50
2.883
200192DELTA CT1
50/50
1.145
200193DELTA CT2
50/50
1.145
200194DELTA CT3
50/50
1.145
200195DELTA ST
50/50
1.907
208835TUHI V3-051
Solar/Wind Harmer
0.053
208835TUHI V3-051
Solar/Wind Harmer
0.053
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
226910AB2-157 C
Solar/Wind Helper
0.017
233939AC1-091 C
Solar/Wind Harmer
0.147
233970AC1-092 C
Solar/Wind Harmer
0.147
233971AC1-093 C
Solar/Wind Harmer
0.14
233972AC1-094 C
Solar/Wind Harmer
0.118
233973AC2-185 C
Solar/Wind Harmer
0.298
219727YARDVSOLFA C
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.253
316411AF1-147_GEN1
Solar/Wind Helper
0.256
316415AF1-147_GEN2
Solar/Wind Helper
0.256
233987AB2-037 GEN
Solar/Wind Harmer
0
233968AD2-076_GEN
Solar/Wind Harmer
0.364
234012AE2-112_GEN
Solar/Wind Harmer
0.126
234014AF1-036_GEN
Solar/Wind Harmer
0.148
234015AF2-250 C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.067
207528AF2-192 GEN
Solar/Wind Harmer
0.044
226929AD2-058 GEN
Solar/Wind Helper
0.038
209120AE2-241 GEN
Solar/Wind Harmer
0.107
209093AE2-110 GEN
Solar/Wind Harmer
0.107
230430AE1-229_GEN
Solar/Wind Harmer
1.042
219623KINSLEYBEA C
Solar/Wind Harmer
0
208862AG1-362 C
Solar/Wind Harmer
0.028
209130AF1-271A GEN
Solar/Wind Harmer
0.089
209142AF1-226 GEN
Solar/Wind Harmer
0.188
233964AF2-378 GEN
Solar/Wind Harmer
0
200200DELTA2 CT1
50/50
2.16
200201DELTA2 CT2
50/50
2.16
200202DELTA2 ST
50/50
3.858
207511W3-106 GEN
Solar/Wind Harmer
0
208972BECR K09
Solar/Wind Harmer
0.879
209029WAYMART-WD
Solar/Wind Harmer
2.166
230407AD2-065 C
Solar/Wind Harmer
0
3138216PACIFIC
Solar/Wind Helper
0.053
961541AF2-445A GEN
Solar/Wind Harmer
0.107
963401AG1-189 GEN
Solar/Wind Harmer
0.08
970025AG2-016 GEN
Solar/Wind Harmer
0.132
970095AG2-074 GEN
Solar/Wind Harmer
0.209
970453AG2-297 GEN
Solar/Wind Harmer
0.133
970597AG2-380 GEN
Solar/Wind Harmer
2.968
970695AG2-447 GEN
Solar/Wind Harmer
0.149
970997AG2-616 GEN
Solar/Wind Harmer
0.349
971007AG2-625 GEN
Solar/Wind Harmer
0.118
971009AG2-626 GEN
Solar/Wind Harmer
0.075
971189AH1-054 GEN
Solar/Wind Harmer
0.055
971195AH1-057 GEN
Solar/Wind Harmer
0.054
971519AH1-257 GEN
Solar/Wind Harmer
0.116
971521AH1-258 GEN
Solar/Wind Harmer
0.125
971667AH1-334 GEN
Solar/Wind Harmer
0.128
219918AC2-009 C
Solar/Wind Harmer
0
972141AH1-641 GEN
Solar/Wind Harmer
0.105
972177AH1-672 GEN
Solar/Wind Harmer
0.559
972281AH1-725 GEN
50/50
121.856
233984AB2-036 GEN
Solar/Wind Harmer
0.684
234041AC1-190 GEN
Solar/Wind Harmer
0.372
227287AC2-120 GEN
Solar/Wind Helper
0.19
230422AE1-104_GEN1
Solar/Wind Harmer
28.921
230425AE1-104_GEN2
Solar/Wind Harmer
28.921
234033AF1-007_GEN
Solar/Wind Harmer
36.484
207500AE2-000G1
Solar/Wind Harmer
26.146
207497AE2-000G2
Solar/Wind Harmer
26.146
207507AE2-000G3
Solar/Wind Harmer
26.146
207487AE2-000G4
Solar/Wind Harmer
26.146
CBM NorthLTFEXP_CBM-N->PJM
CBM
47.134
G-007ALTFEXP_G-007A->PJM
CMTX
30.778
VFTLTFEXP_VFT->PJM
CMTX
81.127
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.013
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.303
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.165
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.746
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.566
MDUPJM->LTFIMP_MDU
CLTF
0
CONTINGENCY 'AP_P1-2_PE-500-3835T_SRT-A'
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019E_SRT-W'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 1   /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 3   /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 2           /*01DOUBS      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'PECO_P1-2_5007_SRT-A
 TRIP BRANCH FROM BUS 200066 TO BUS 270095 CKT 1   /*PCHBTM1N     500.0 - CHAN         500.0
END
CONTINGENCY 'BG_P7_CNSTN_NWEST2_SRT-A'
 OPEN BRANCH FROM BUS 220961 TO BUS 220963 CKT 1   /*NWEST326     230.0 - CONASTON     230.0
 OPEN BRANCH FROM BUS 220962 TO BUS 220963 CKT 1   /*NWEST311     230.0 - CONASTON     230.0
END
200004 to 200003 ckt 1

Light Load Analysis

The New Service Request AH1-725 was evaluated as a 500.0 MW injection and 500.0 MW withdrawal in the BGE area.

AH1-725 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 500.0 MW (500.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary:

New Service Requests (projects) in PJM Transition Cycle 2, Cluster 90 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 90 projects.

This analysis is effectively a screening study to determine whether the addition of the Cluster 90 projects will meet the dynamics requirements of the NERC, BGE and PJM reliability standards.

The load flow scenario for the analysis was based on the RTEP 2028 summer peak load case, modified to include applicable projects. Cluster 90 projects have been dispatched online at maximum power output, with 1.0 pu voltage at the terminal bus.

Cluster 90 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 255 contingencies were studied, each with a 20 second simulation time period. Studied faults included:

  1. Steady-state operation (20 second run);
  2. Three-phase faults with normal clearing time (and with unsuccessful high-speed reclosing);
  3. Single-phase bus faults with normal clearing time;
  4. Single-phase faults with stuck breaker;
  5. Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure;
  6. Single-phase faults with loss of multiple-circuit tower line (and with unsuccessful high-speed reclosing).

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

For all of the fault contingencies tested on the 2028 peak load case:

  1. Cluster 90 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  2. The system with Cluster 90 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.
  3. Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).
  4. No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

AG2-617, AH1-261 and AH1-725 meet the 0.95 leading and lagging PF requirement.

AG2-617 exhibited voltage limit violations following several contingencies, although overall system stability was maintained. To improve performance, model tuning was performed. In the REPCA1 model, droop control was enabled by setting the VC flag to 0. In addition, the reactive current compensation gain, Kc, was increased from 0.04 pu to 0.2 pu. These changes kept the voltage within the acceptable range of 0.95 pu to 1.05 pu.

AH1-261 GEN exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. To improve its performance, model tuning was performed. In the REPCA1 model, the integral gain, Ki, was reduced from 0.25 pu to 0.0 pu. This adjustment improved reactive power recovery.

AH1-725 GEN exhibited voltage limit violations following several contingencies, although overall system stability was maintained. To improve performance, model tuning was performed. In the REPCA1 model, droop control was enabled by setting the VC flag to 0. This adjustment kept the voltage within the acceptable range of 0.95 pu to 1.05 pu.

The IPCMD and IQCMD states in the REGCA1 models of AG2-617, AH1-261, and AH1-725 showed erratic behavior for some contingencies in which AG2-617, AH1-261, and AH1-725 have been disconnected as part of the contingency event. Since the machine is disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause system instability.

No mitigations were found to be required.

Table 1: TC2 Cluster 90 Projects

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

90

AG2-617

Solar

BGE

55

55.0

33.0

Waugh Chapel 115 kV

AH1-261

Storage

BGE

135

135.0

135.0

Northeast - Riverside 230 kV

AH1-725

Storage

BGE

500

500

500

Conastone 500 kV

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AH1-725 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Analysis Complete - No Issues

Steady State Voltage Analysis complete, no voltage issues identified.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

(No dependencies were identified)

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AH1-725 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
BGEb3780.7Build new Batavia Road substation (Projected ISD 12/31/2028)Contingent$0N/A
BGEb3780.8Graceton 500 kV substation expansion (Projected ISD 12/31/2028)Contingent$0N/A
BGEb3780.9Graceton to Batavia Road 230 kV double circuit pole line (Projected ISD 12/31/2028)Contingent$0N/A
BGEb3780.13Batavia Road to Riverside 230 kV reconductorContingent$0N/A
PECOb3780.15Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV subContingent$0N/A
PECOb3780.17Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV sub (Transource)Contingent$0N/A
BGEb3800.34Rebuild 5012 (existing Peach Bottom-Conastone) (new Graceton-Conastone) 500 kV and cut into North Delta 500kV (Projected ISD 12/31/2030)Contingent$0N/A
PECOb3780.16Terminate new Cooper-North Delta 230 kV line (Transource Scope) at North Delta 230 kVContingent$0N/A
PECOb3800.45North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (PECO work).Contingent$0N/A
PECOb3780.14Reconfigure Cooper transmission feeds by establishing new Cooper-North Delta 230 kV line and rerouting existing transmissions lines by Cooper.Contingent$0N/A
PECOb3800.50North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (Transource work).Contingent$0N/A
PEPCOb3800.46North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (PECO work).Contingent$0N/A
PECOb3800.51North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (Transource work).Contingent$0N/A
PECOb3800.31Build new North Delta-High Ridge 500 kV line - PECO Portion (Projected ISD 12/1/2030)Contingent$0N/A
PECOb3800.35Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton PECO) 500 kV (Projected ISD 12/1/2030)Contingent$0N/A
PECOb3780.1Peach Bottom North upgrades – substation work (Projected ISD 12/31/2028)Contingent$0N/A
PECOb3800.52Reconfigure Peach Bottom North and South 500 kV yards (Projected ISD 12/1/2030)Contingent$0N/A
BGEb3800.36Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton BGE) 500 kV (Projected ISD 12/31/2030)Contingent$0N/A
PECOb3800.44North Delta termination for the North Delta-High Ridge 500 line (PECO work).Contingent$0N/A
BGEb3780.5Build Solley Road substation + Statcom (Projected ISD 12/31/2028)Contingent$0N/A
BGEb3780.6Build Granite substation + Statcom (Projected ISD 12/31/2028)Contingent$0N/A
PEPCOb3780.11Brighton Statcom and Capacitor (Projected ISD 12/31/2028)Contingent$0N/A
BGEb3800.37Replace terminal equipment limitations at Conastone 500 kV - on the (existing Peach Bottom-Conastone) or (new Graceton-Conastone) 500 kV line (Projected ISD 12/31/2030)Contingent$0N/A
PECOb3800.49North Delta 500 kV termination for the Calpine generator (Calpine/Transource work).Contingent$0N/A
PECOb3800.42Peach Bottom 500kV North bus upgrade (Projected ISD 12/1/2030)Contingent$0N/A
PECOb3800.47Build new Peach Bottom South-North Delta 500 kV line (Projected ISD 12/1/2030)Contingent$0N/A
BGEb3800.30High Ridge - Install two 500/230 kV transformers (Projected ISD 12/31/2030)Contingent$0N/A
BGEb3800.28High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) -Brighton side (Projected ISD 12/31/2030)Contingent$0N/A
BGEb3800.27High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) - Waugh Chapel side (Projected ISD 12/31/2030)Contingent$0N/A
BGEb3800.26Build High Ridge 500 kV substation - Three bay breaker and half configuration (Projected ISD 12/31/2030)Contingent$0N/A
BGEb3800.32Build new North Delta-High Ridge 500 kV line - BGE Portion (Projected ISD 12/31/2030)Contingent$0N/A
PECOb3800.48North Delta termination for the North Delta-High Ridge 500 line (Transource work).Contingent$0N/A
PECOb3737.47Build New North Delta 500 kV substation (Four bay breaker and half configuration)Contingent$0N/A
BGEb3800.29High Ridge termination for the North Delta-High Ridge 500 kV line (Projected ISD 12/31/2030)Contingent$0N/A
BGEb3800.33Replace terminal equipment limitations at Brighton 500 kV - on the existing Brighton-Waugh Chapel 500 kV (5053) or new Brighton-High Ridge 500 kV.Contingent$0N/A
PECOb3780.2Peach Bottom to Graceton (PECO Portion) – New 500kV LineContingent$0N/A
BGEb3780.4Peach Bottom to Graceton (BGE Portion) – New 500kV LineContingent$0N/A
Grand Total:$0

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b3780.7
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.7
Title
Build new Batavia Road substation (Projected ISD 12/31/2028)
Description
Build Batavia Road substation. Add 4 x 230kV breaker bays
Cost Information
Time Estimate
Dec 31 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.8
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.8
Title
Graceton 500 kV substation expansion (Projected ISD 12/31/2028)
Description
Add 3x 500 kV breaker bays, 2x 500/230 kV auto transformer, 1x 500 kV caps
Cost Information
Time Estimate
Dec 31 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.9
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.9
Title
Graceton to Batavia Road 230 kV double circuit pole line (Projected ISD 12/31/2028)
Description
Graceton to Batavia Road 230 kV double circuit pole line New rating: 1331 MVA SN/ 1594 MVA SE
Cost Information
Time Estimate
Dec 31 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.13
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.13
Title
Batavia Road to Riverside 230 kV reconductor
Description
Batavia Road to Riverside 230 kV reconductor New rating: 1941 MVA SN / 2181 MVA SE
Cost Information
Time Estimate
Dec 31 2027

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.15
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.15
Title
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV sub
Description
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV substation by rebuilding 5012 between new terminal at Peach Bottom South and North Delta on single circuit structures and terminating at North Delta.
Cost Information
Time Estimate
Apr 10 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.17
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.17
Title
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV sub (Transource)
Description
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV substation by rebuilding 5012 between new terminal at Peach Bottom South and North Delta on single circuit structures and terminating at North Delta (Transource Scope).
Cost Information
Time Estimate
May 31 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.34
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.34
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new Graceton-Conastone) 500 kV and cut into North Delta 500kV (Projected ISD 12/31/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new Graceton-Conastone) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Dec 31 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.16
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.16
Title
Terminate new Cooper-North Delta 230 kV line (Transource Scope) at North Delta 230 kV
Description
None
Cost Information
Time Estimate
Oct 15 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.45
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.45
Title
North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (PECO work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Jan 31 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.14
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.14
Title
Reconfigure Cooper transmission feeds by establishing new Cooper-North Delta 230 kV line and rerouting existing transmissions lines by Cooper.
Description
None
Cost Information
Time Estimate
Oct 23 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.50
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.50
Title
North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (Transource work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Jan 23 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.46
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3800.46
Title
North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (PECO work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Dec 11 2029

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.51
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.51
Title
North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (Transource work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
May 31 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.31
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.31
Title
Build new North Delta-High Ridge 500 kV line - PECO Portion (Projected ISD 12/1/2030)
Description
None
Cost Information
Time Estimate
Dec 15 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.35
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.35
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton PECO) 500 kV (Projected ISD 12/1/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton PECO) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Apr 10 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.1
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.1
Title
Peach Bottom North upgrades – substation work (Projected ISD 12/31/2028)
Description
Add 3x 500 kV breakers to form a breaker-and-a-half bay.
Cost Information
Time Estimate
Oct 15 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.52
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.52
Title
Reconfigure Peach Bottom North and South 500 kV yards (Projected ISD 12/1/2030)
Description
Reconfigure Peach Bottom North and South yards to allow for termination of 500 kV lines from Peach Bottom to North Delta. North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line.
Cost Information
Time Estimate
Dec 01 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.36
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.36
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton BGE) 500 kV (Projected ISD 12/31/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton BGE) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Dec 31 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.44
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.44
Title
North Delta termination for the North Delta-High Ridge 500 line (PECO work).
Description
None
Cost Information
Time Estimate
Dec 15 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.5
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.5
Title
Build Solley Road substation + Statcom (Projected ISD 12/31/2028)
Description
Build Solley Road substation + Statcom. New STATCOM rating: 350 MVAR Add 4x 230 kV breakers bays.
Cost Information
Time Estimate
Dec 31 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.6
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.6
Title
Build Granite substation + Statcom (Projected ISD 12/31/2028)
Description
Build Granite substation + Statcom. New STATCOM rating: 350 MVAR. Add 4x 230 kV breaker bays.
Cost Information
Time Estimate
Dec 31 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.11
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3780.11
Title
Brighton Statcom and Capacitor (Projected ISD 12/31/2028)
Description
Brighton Statcom and capacitor New STATCOM rating: 350 MVAR New capacitor rating: 350 MVAR
Cost Information
Time Estimate
Dec 31 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.37
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.37
Title
Replace terminal equipment limitations at Conastone 500 kV - on the (existing Peach Bottom-Conastone) or (new Graceton-Conastone) 500 kV line (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.49
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.49
Title
North Delta 500 kV termination for the Calpine generator (Calpine/Transource work).
Description
None
Cost Information
Time Estimate
Oct 06 2027

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.42
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.42
Title
Peach Bottom 500kV North bus upgrade (Projected ISD 12/1/2030)
Description
Peach Bottom 500kV North bus upgrade - Replace 11 – Instances of strain bus conductor used for breaker drops or CT drops, 7 – 500 kV disconnect switches, 7 – Free Standing CTs, 1 – 500 kV breaker, 2 – Breaker relays or meters.
Cost Information
Time Estimate
Dec 01 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.47
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.47
Title
Build new Peach Bottom South-North Delta 500 kV line (Projected ISD 12/1/2030)
Description
Build new Peach Bottom South-North Delta 500 kV line – cut in to Peach Bottom tie No. 1 and extending line to North Delta (~1.25 miles new ROW).
Cost Information
Time Estimate
Jan 14 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.30
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.30
Title
High Ridge - Install two 500/230 kV transformers (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.28
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.28
Title
High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) -Brighton side (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.27
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.27
Title
High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) - Waugh Chapel side (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.26
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.26
Title
Build High Ridge 500 kV substation - Three bay breaker and half configuration (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.32
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.32
Title
Build new North Delta-High Ridge 500 kV line - BGE Portion (Projected ISD 12/31/2030)
Description
Build new North Delta-High Ridge 500 kV line. (~59 miles)
Cost Information
Time Estimate
Dec 31 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.48
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.48
Title
North Delta termination for the North Delta-High Ridge 500 line (Transource work).
Description
None
Cost Information
Time Estimate
Dec 15 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3737.47
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3737.47
Title
Build New North Delta 500 kV substation (Four bay breaker and half configuration)
Description
Build New North Delta 500 kV substation (four bay breaker and half configuration) - the substation will include 12 - 500kV breakers and one 500/230 kV transformer, will allow the termination of six - 500 kV lines
Cost Information
Time Estimate
Oct 06 2027

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.29
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.29
Title
High Ridge termination for the North Delta-High Ridge 500 kV line (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.33
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.33
Title
Replace terminal equipment limitations at Brighton 500 kV - on the existing Brighton-Waugh Chapel 500 kV (5053) or new Brighton-High Ridge 500 kV.
Description
None
Cost Information
Time Estimate
Dec 31 2030

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.2
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.2
Title
Peach Bottom to Graceton (PECO Portion) – New 500kV Line
Description
Peach Bottom to Graceton (PECO Portion) – New 500kV Line. New rating: 4503 MVA SN/ 5022 MVA SE. This is a baseline identified for the announced Brandon Shores deactivation.
Cost Information
Time Estimate
Oct 23 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.4
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.4
Title
Peach Bottom to Graceton (BGE Portion) – New 500kV Line
Description
New rating: 4503 MVA SN/ 5022 MVA SE. This is a baseline identified for the announced Brandon Shores deactivation.
Cost Information
Time Estimate
Dec 31 2028

ContingentTopology Changing

Note 1: Although AH1-725 may not presently have cost responsibility for this upgrade, AH1-725 may need this upgrade in-service to be deliverable to the PJM system. If AH1-725 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-725


AH1-725 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowBGEb3780.7Build new Batavia Road substation (Projected ISD 12/31/2028)Topology-0.0%Contingent$0
Load FlowBGEb3780.8Graceton 500 kV substation expansion (Projected ISD 12/31/2028)Topology-0.0%Contingent$0
Load FlowBGEb3780.9Graceton to Batavia Road 230 kV double circuit pole line (Projected ISD 12/31/2028)Topology-0.0%Contingent$0
Load FlowBGEb3780.13Batavia Road to Riverside 230 kV reconductorTopology-0.0%Contingent$0
Load FlowPECOb3780.15Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV subTopology-0.0%Contingent$0
Load FlowPECOb3780.17Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV sub (Transource)Topology-0.0%Contingent$0
Load FlowBGEb3800.34Rebuild 5012 (existing Peach Bottom-Conastone) (new Graceton-Conastone) 500 kV and cut into North Delta 500kV (Projected ISD 12/31/2030)Topology-0.0%Contingent$0
Load FlowPECOb3780.16Terminate new Cooper-North Delta 230 kV line (Transource Scope) at North Delta 230 kVTopology-0.0%Contingent$0
Load FlowPECOb3800.45North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (PECO work).Topology-0.0%Contingent$0
Load FlowPECOb3780.14Reconfigure Cooper transmission feeds by establishing new Cooper-North Delta 230 kV line and rerouting existing transmissions lines by Cooper.Topology-0.0%Contingent$0
Load FlowPECOb3800.50North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (Transource work).Topology-0.0%Contingent$0
Load FlowPEPCOb3800.46North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (PECO work).Topology-0.0%Contingent$0
Load FlowPECOb3800.51North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (Transource work).Topology-0.0%Contingent$0
Load FlowPECOb3800.31Build new North Delta-High Ridge 500 kV line - PECO Portion (Projected ISD 12/1/2030)Topology-0.0%Contingent$0
Load FlowPECOb3800.35Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton PECO) 500 kV (Projected ISD 12/1/2030)Topology-0.0%Contingent$0
Load FlowPECOb3780.1Peach Bottom North upgrades – substation work (Projected ISD 12/31/2028)Topology-0.0%Contingent$0
Load FlowPECOb3800.52Reconfigure Peach Bottom North and South 500 kV yards (Projected ISD 12/1/2030)Topology-0.0%Contingent$0
Load FlowBGEb3800.36Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton BGE) 500 kV (Projected ISD 12/31/2030)Topology-0.0%Contingent$0
Load FlowPECOb3800.44North Delta termination for the North Delta-High Ridge 500 line (PECO work).Topology-0.0%Contingent$0
Load FlowBGEb3780.5Build Solley Road substation + Statcom (Projected ISD 12/31/2028)Topology-0.0%Contingent$0
Load FlowBGEb3780.6Build Granite substation + Statcom (Projected ISD 12/31/2028)Topology-0.0%Contingent$0
Load FlowPEPCOb3780.11Brighton Statcom and Capacitor (Projected ISD 12/31/2028)Topology-0.0%Contingent$0
Load FlowBGEb3800.37Replace terminal equipment limitations at Conastone 500 kV - on the (existing Peach Bottom-Conastone) or (new Graceton-Conastone) 500 kV line (Projected ISD 12/31/2030)Topology-0.0%Contingent$0
Load FlowPECOb3800.49North Delta 500 kV termination for the Calpine generator (Calpine/Transource work).Topology-0.0%Contingent$0
Load FlowPECOb3800.42Peach Bottom 500kV North bus upgrade (Projected ISD 12/1/2030)Topology-0.0%Contingent$0
Load FlowPECOb3800.47Build new Peach Bottom South-North Delta 500 kV line (Projected ISD 12/1/2030)Topology-0.0%Contingent$0
Load FlowBGEb3800.30High Ridge - Install two 500/230 kV transformers (Projected ISD 12/31/2030)Topology-0.0%Contingent$0
Load FlowBGEb3800.28High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) -Brighton side (Projected ISD 12/31/2030)Topology-0.0%Contingent$0
Load FlowBGEb3800.27High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) - Waugh Chapel side (Projected ISD 12/31/2030)Topology-0.0%Contingent$0
Load FlowBGEb3800.26Build High Ridge 500 kV substation - Three bay breaker and half configuration (Projected ISD 12/31/2030)Topology-0.0%Contingent$0
Load FlowBGEb3800.32Build new North Delta-High Ridge 500 kV line - BGE Portion (Projected ISD 12/31/2030)Topology-0.0%Contingent$0
Load FlowPECOb3800.48North Delta termination for the North Delta-High Ridge 500 line (Transource work).Topology-0.0%Contingent$0
Load FlowPECOb3737.47Build New North Delta 500 kV substation (Four bay breaker and half configuration)Topology-0.0%Contingent$0
Load FlowBGEb3800.29High Ridge termination for the North Delta-High Ridge 500 kV line (Projected ISD 12/31/2030)Topology-0.0%Contingent$0
Load FlowBGEb3800.33Replace terminal equipment limitations at Brighton 500 kV - on the existing Brighton-Waugh Chapel 500 kV (5053) or new Brighton-High Ridge 500 kV.Topology-0.0%Contingent$0
Load FlowPECOb3780.2Peach Bottom to Graceton (PECO Portion) – New 500kV LineTopology-0.0%Contingent$0
Load FlowBGEb3780.4Peach Bottom to Graceton (BGE Portion) – New 500kV LineTopology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-725 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-725 One Line Diagram

AH1-725 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.