AF1-125 Final System Impact Study (Retool 2) Report

v2.00 released 2026-05-14 11:48

Harper 230 kV

249.3 MW Capacity / 820.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia), and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.

The AF1-125 Final System Impact Study (Retool 1) Report is available for download here.

Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed a Offshore Wind generating facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — City of Chesapeake County, Virginia. The installed facilities will have a total capability of 820.0 MW with 249.3 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AF1-125
Project Name:
Harper 230 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
State:
Virginia
County:
City of Chesapeake
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
820.0
MWE:
820.0
MWC:
249.3
Fuel Type:
Offshore Wind
Basecase Study Year:
2027

Physical Interconnection Facility Study

Reviewed

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AF1-123, AF1-124 and AF1-125 will interconnect on the Dominion transmission system at the Harpers 230 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AF1-125 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AF1-125Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$7,308,561$7,308,561
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$98,140,632$98,140,632
Network Upgrades$151,928,890$151,928,890
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$65,028,562$65,028,562
Transient Stability$29,053,510$29,053,510
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0
AFS - Non-PJM Violations$0 **$0 **
Total$351,460,156$351,460,156

* Contributes to calculation for Security. See Security Requirement Section of this report for additional detail.

** This value reflects the results at the time of the report posting and it is subject to change. AFS – Non-PJM Violations are not subject to Security. For latest AFS – Non-PJM Violations, please refer to the latest Affected System Study Report for your project.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF1-125

Security has been calculated for the AF1-125 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF1-125
Project(s): AF1-125
Final Agreement Security (A): $351,460,156
Portion of Costs Already Paid (B): $263,813,495
Revised Net Security (C): A − B = $87,646,661
Security on Hand with PJM (D): $277,790,154
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

The New Service Request Project will interconnect with the Dominion transmission system via a new Harpers switching station that connects at Fentress 230/500 kV substation. The required work for the interconnection of the New Service Request Project to the Dominion Transmission System is detailed in the following tables.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n8317.1

Expand Fentress 500 kV and 230 kV substations to terminate three new 230 kV lines from Harpers Road substation and connect them to Fentress 500 kV

$32,089,434$188,729,124$3,121,660$2,604,178$226,544,396$75,514,799 (See Note 1)
n8317.2

Construct three (3) overhead 230kV transmission lines that will start at the existing Fentress Substation and terminate at the new Harpers Road Substation, located approximately 14.3 miles away

$87,809,759$122,418,217$7,002,882$12,011,417$229,242,275$76,414,092 (See Note 1)
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n8317.3

Build new 230 kV Harpers Road switching station to terminate nine offshore wind export cables for AF1-123/124/125 and consolidate to three overhead 230 kV transmission lines to go to Fentress Substation

$54,931,535$211,895,213$9,823,673$17,771,475$294,421,896$98,140,632 (See Note 1)
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install 230 kV backbone structures and foundations within the fence of the Interconnection Substation, to terminate the Project Developer’s generator lead lines. Line conductor from the backbone structure to the bus position in the switchyard of the interconnection substation.

$497,960$6,185,453$105,765$519,383$7,308,561$7,308,561

Based on the scope of work for the Interconnection Facilities, it is expected to take 10 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

It is estimated to take 10 months to complete this work upon execution of the Generator Interconnection Agreement (GIA).This estimated time to complete is dependent on major equipment lead times. These preliminary cost estimates are based on typical engineering costs. A more detailed engineering cost estimates are normally done when the Project Developer provides an exact site plan location for the generation substation during a future study phase.  As shown in the one line diagram, this Interconnection Request is sharing the Point of Interconnection (POI) and Interconnection Facilities with one or more other Interconnection Requests. Should other requests withdraw from Transition Cycle 1, the cost allocation for Transmission Owner Interconnection Facilities, Stand Alone Network Upgrades, and applicable Network Upgrades identified in the study report will be updated for the remaining project(s). Refer to the one line for other Interconnection Requests at this POI. 


Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.
 
Remote Terminal Work: During Phase 2 of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2027 load flow model and the results were verified by Dominion.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The wind generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Wind speed (meters/second) - (Required)
  • Wind direction (decimal degrees from true north) - (Required)
  • Ambient air temperature (Fahrenheit) - (Required)
  • Air Pressure (Hectopascals) - (Required)
  • Humidity (Percent) - (Accepted, not required)
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AF1-125 was evaluated as a 820.0 MW (249.3 MW Capacity) injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC141.99 %812.0C1152.9944.79
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC133.67 %663.64B887.0715.18
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 217_SRT-A
SingleAC112.85 %663.64B748.9212.81
GD1DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: H2T557_SRT-S
BreakerAC132.13 %1065.0C1407.21116.3
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P4-2: 224022-1_SRT-S
BreakerAC145.91 %830.0C1211.01221.77
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P4-2: 224022-2_SRT-S
BreakerAC145.75 %830.0C1209.69221.56
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P1-2: LN 271_SRT-A
SingleAC107.49 %678.68B729.563.02
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P1-2: LN 2240_SRT-A
SingleAC104.51 %678.68B709.2763.05
GD1DVP
6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: H2T574_SRT-S_SENS
BreakerAC134.99 %1031.0C1391.7369.2
GD1DVP
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
DVP_P4-2: 2110T2128_SRT-A
BreakerAC122.86 %830.0C1019.7127.07
GD1DVP
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
DVP_P4-2: 212822_SRT-S
BreakerAC120.29 %830.0C998.4157.15
GD1DVP
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
DVP_P4-2: 269T2128_SRT-S
BreakerAC116.98 %830.0C970.97147.89
GD1DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 56372_SRT-S
BreakerAC113.54 %1056.8C1199.8655.37
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC106.13 %3940.0C4181.52228.68
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC104.17 %3940.0C4104.33207.66
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H1T567_SRT-A
BreakerAC103.4 %3940.0C4073.91232.75
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC108.99 %3940.0C4294.13234.92
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC104.84 %3940.0C4130.73237.26
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S_SENS
BreakerAC102.96 %3940.0C4056.64220.8
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S_SENS
SingleAC101.85 %3220.44B3279.9765.2
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC102.49 %3144.0C3222.37245.73
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC102.39 %3144.0C3219.08247.32
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC102.39 %3144.0C3219.08247.32
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC102.38 %3144.0C3218.92247.32

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.99 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1152.99
MW Contribution:44.79
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.71 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1061.35
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944641AF1-129 C
50/50
138.059138.059
316240AF1-291 C
50/50
2.8082.808
925332AB2-190 E
50/50
4.8614.861
935162AD1-151 E
50/50
6.1926.192
927226AC1-216 E
Adder
4.2082352941176473.577
924814AB2-134 E
Adder
6.8941176470588245.86
939191AE1-149 C
50/50
7.6817.681
3143316POE
50/50
1.2311.231
316381AD1-082 C
50/50
0.7750.775
943461AF1-017 C
Adder
0.6317647058823530.537
942342AE2-247 E
Adder
0.96470588235294120.82
936666AD2-085 E
Adder
2.62823529411764722.234
932596AC2-079 E
Adder
4.2658823529411763.626
316311AC2-079 C
Adder
2.61529411764705882.223
941591AE2-156 C
Adder
5.6635294117647064.814
944601AF1-125 C
Adder
13.61647058823529511.574
944591AF1-124 C
Adder
13.87882352941176711.797
919152AA1-139 E1
Adder
1.27058823529411781.08
938532AE1-072 E
Adder
2.8635294117647062.434
3146326AYDLETT TAP
Adder
0.424705882352941160.361
917122Z2-027 E
Adder
0.435294117647058830.37
901082W1-029 E
Adder
10.5541176470588248.971
938771AE1-103 C
Adder
1.1282352941176470.959
3145413WATKINS
Adder
0.271764705882352960.231
920692AA2-178 E
Adder
1.45294117647058841.235
920042AA2-088 E OP
Adder
4.2552941176470593.617
934511AD1-075 C
Adder
3.0564705882352942.598
934521AD1-076 C
Adder
4.443.774
960081AF2-299 C
Adder
0.90588235294117650.77
966622AG1-532 E
Adder
0.452941176470588240.385
3145723EMPORIA
Adder
0.205882352941176460.175
926072AC1-086 E
Adder
4.4364705882352943.771
923573AB1-173 E OP
Adder
1.50588235294117641.28
919692AA2-053 E OP
Adder
1.7835294117647061.516
944011AF1-069 C
Adder
5.5494117647058824.717
926206AC1-098 E
Adder
1.4682352941176471.248
963041AG1-153 C
Adder
2.32823529411764741.979
925785AC1-054 E
Adder
1.32352941176470581.125
922923AB1-081 E OP
Adder
1.45294117647058841.235
316263AC1-034 C
Adder
2.5882352941176472.2
962562AG1-105 E
Adder
1.93058823529411771.641
964791AG1-342 C
Adder
1.1482352941176470.976
3150801HOPHCF4
50/50
2.5532.553
3150731STONECA
50/50
4.7614.761
940432AE2-027 E
Adder
3.68588235294117663.133
935161AD1-151 C
50/50
9.2889.288
934012AD1-025 E
Adder
5.4482352941176474.631
942341AE2-247 C
Adder
0.69882352941176470.594
316349AD2-085 C
Adder
1.61058823529411771.369
943462AF1-017 E
Adder
1.03058823529411760.876
935112AD1-144 E
Adder
0.315294117647058840.268
932046AC2-012 E
Adder
4.1552941176470593.532
944582AF1-123 E
Adder
31.66823529411764726.918
944592AF1-124 E
Adder
31.78352941176470427.016
958161AF2-110 C
Adder
0.50941176470588230.433
958162AF2-110 E
Adder
0.81058823529411760.689
919153AA1-139 E2
Adder
1.27058823529411781.08
938531AE1-072 C
Adder
5.49411764705882364.67
913392Y1-086 E
Adder
0.70470588235294120.599
923832AB2-022 E
Adder
0.397647058823529460.338
938772AE1-103 E
Adder
1.55882352941176471.325
916042Z1-036 E
Adder
9.7517647058823538.289
3145393UNCAMP
Adder
2.362.006
939411AE1-173 C
Adder
35.0670588235294129.807
934512AD1-075 E
Adder
1.5552941176470591.322
934502AD1-074 E
Adder
6.222352941176475.289
933981AD1-022 C
Adder
3.22705882352941182.743
924516AB2-100 E1
Adder
1.5282352941176471.299
900672V4-068 E
Adder
0.14235294117647060.121
918512AA1-065 E OP
Adder
2.12470588235294141.806
960082AF2-299 E
Adder
0.60352941176470590.513
966621AG1-532 C
Adder
0.67999999999999990.578
946281AF1-292 C
Adder
0.74941176470588230.637
926071AC1-086 C
Adder
9.7470588235294138.285
3137643SOCKMAN
Adder
0.315294117647058840.268
963042AG1-153 E
Adder
3.4917647058823532.968
918532AA1-067 E
Adder
0.269411764705882350.229
919710AA2-057 E
Adder
1.58117647058823541.344
927021AC1-189 C
Adder
3.2094117647058832.728
964241AG1-285 C
Adder
4.1952941176470593.566
924022AB2-043 E O1
Adder
1.73764705882352951.477
924152AB2-059 E OP
Adder
2.0588235294117651.75
924302AB2-077 E O1
Adder
0.448235294117647070.381
962561AG1-105 C
Adder
2.89529411764705862.461
3150781HOPHCF2
50/50
1.6821.682
3150791HOPHCF3
50/50
1.6821.682
3150771HOPHCF1
50/50
1.6821.682
940431AE2-027 C
Adder
5.5282352941176474.699
942001AE2-212 C
50/50
2.3882.388
942002AE2-212 E
50/50
1.5921.592
316132AB2-190 C
50/50
2.4992.499
961611AG1-000B C
Adder
7.286.188
939192AE1-149 E
50/50
5.125.12
939312AE1-162 E
Adder
0.54941176470588240.467
926662AC1-147 E
Adder
0.420.357
916192Z1-068 E
Adder
0.58588235294117650.498
934065AD1-033 E
Adder
1.53411764705882361.304
944581AF1-123 C
Adder
13.82941176470588311.755
941101AE2-104 C
Adder
1.2482352941176471.061
957492AF2-043 E
Adder
0.4717647058823530.401
937226AE2-253 E
Adder
1.80588235294117651.535
923852AB2-025 E
50/50
0.7170.717
940541AE2-040 C
50/50
1.7731.773
940482AE2-033 E
50/50
6.6116.611
940481AE2-033 C
50/50
9.8069.806
939412AE1-173 E
Adder
23.37764705882352719.871
934501AD1-074 C
Adder
12.22470588235294110.391
3150651CHESTF6
50/50
25.13725.137
946262AF1-291 E
50/50
1.8721.872
3150761HOPPOLC
50/50
1.0581.058
934576AD1-082 E
50/50
2.7072.707
316084AB2-161 E
50/50
3.3973.397
316083AB2-161 C
50/50
0.340.34
3145256KINGFORK
Adder
0.33882352941176470.288
925522AC1-027 E
Adder
0.380.323
944602AF1-125 E
Adder
31.17176470588235326.496
941102AE2-104 E
Adder
1.98470588235294131.687
3145506HICKORY
Adder
0.6682352941176470.568
943612AF1-032 E
Adder
0.30705882352941180.261
957871AF2-081 C
Adder
3.10588235294117652.64
957872AF2-081 E
Adder
1.33058823529411761.131
316315AB2-025 C
50/50
0.2520.252
940492AE2-034 E
Adder
1.08941176470588250.926
3145946PLYMOUTH TP
Adder
0.116470588235294130.099
934522AD1-076 E
Adder
2.2623529411764711.923
933982AD1-022 E
Adder
1.75647058823529421.493
943172AE2-346 E
Adder
0.238823529411764740.203
946282AF1-292 E
Adder
0.50.425
918492AA1-063AE OP
Adder
1.7070588235294121.451
917332KELFORD E
Adder
0.65058823529411770.553
925122AB2-169 E
Adder
2.1235294117647061.805
944012AF1-069 E
Adder
2.1552941176470591.832
932632AC2-084 E
Adder
1.2988235294117651.104
926214AC1-099 E
Adder
0.484705882352941150.412
316274AC1-208 C
Adder
3.6705882352941183.12
927146AC1-208 E
Adder
1.62941176470588231.385
917512Z2-088 E OP1
Adder
1.88000000000000011.598
917342Z2-044 E
Adder
0.235294117647058850.2
934622AD1-088 E
Adder
1.53176470588235311.302
964242AG1-285 E
Adder
2.7964705882352942.377
937482AD2-202 E
Adder
0.36941176470588240.314
934612AD1-087 E
Adder
1.26235294117647071.073
3151311EDGECMA
Adder
6.0682352941176485.158
924162AB2-060 E OP
Adder
1.41882352941176461.206
964792AG1-342 E
Adder
0.76588235294117660.651
924517AB2-100 E2
Adder
1.5282352941176471.299
316141AB2-099 E
Adder
0.098823529411764710.084
961941AG1-037 C
Adder
0.198823529411764730.169
961942AG1-037 E
Adder
0.132941176470588230.113
316088AB2-174 E
Adder
3.04352941176470632.587
923263AB1-132 E OP
Adder
2.8364705882352942.411
923994AB2-040_E
Adder
2.8235294117647062.4
941032AE2-094 E
Adder
7.6070588235294126.466
941031AE2-094 C
Adder
16.9847058823529414.437
934321AD1-056 C
Adder
2.642.244
934332AD1-057 E
Adder
0.76705882352941180.652
934322AD1-056 E
Adder
1.4317647058823531.217
934331AD1-057 C
Adder
1.47294117647058821.252
927022AC1-189 E
Adder
1.59882352941176481.359
957481AF2-042 C
Adder
19.4705882352941216.55
957482AF2-042 E
Adder
12.9811.033
961672AG1-007 E
Adder
0.204705882352941150.174
961671AG1-007 C
Adder
0.36235294117647060.308
934621AD1-088 C
Adder
3.18117647058823572.704
925595AC1-034 E
Adder
1.95294117647058821.66
924322AB2-079 E O1
Adder
0.448235294117647070.381
924312AB2-078 E O1
Adder
0.448235294117647070.381
935172AD1-152 E
Adder
1.86235294117647051.583
926274AC1-105 E
Adder
0.860.731
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.0758.075
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.5166.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.081.08
LAGNLTFEXP_LAGN->PJM
CLTF
2.3232.323
NYPJM->LTFIMP_NY
CLTF
0.4640.464
LGEELTFEXP_LGEE->PJM
CLTF
0.3190.319
WECLTFEXP_WEC->PJM
CLTF
0.1690.169
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.8981.898
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.93631.936
CPLELTFEXP_CPLE->PJM
CLTF
3.9843.984
TVALTFEXP_TVA->PJM
CLTF
1.811.81
O66PJM->LTFIMP_O-066
CMTX_NF
6.2766.276
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9850.985
SIGELTFEXP_SIGE->PJM
CLTF
0.0650.065

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.67 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:887.07
MW Contribution:15.18
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.35 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:918.17
MW Contribution:14.6
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150801HOPHCF4
80/20
2.5772.577
3150731STONECA
80/20
4.8074.807
935161AD1-151 C
80/20
9.5159.515
3151171GRAVELC
80/20
0.3880.388
3151221GRAVEL6
80/20
1.141.14
3150781HOPHCF2
80/20
1.6981.698
3150791HOPHCF3
80/20
1.6981.698
3150771HOPHCF1
80/20
1.6981.698
940431AE2-027 C
80/20
5.4285.428
942001AE2-212 C
80/20
2.3582.358
316132AB2-190 C
80/20
2.552.55
316369AC1-216 C
80/20
0.90.9
961611AG1-000B C
80/20
7.6267.626
316236AE1-162 C
80/20
0.1440.144
944581AF1-123 C
Adder
15.41882352941176613.106
941101AE2-104 C
80/20
1.3111.311
940541AE2-040 C
80/20
1.6761.676
940481AE2-033 C
80/20
9.2759.275
3156083AA2-088SOLA
80/20
0.4240.424
934501AD1-074 C
Adder
12.4576470588235310.589
961941AG1-037 C
Adder
0.196470588235294150.167
3156073AA1-063SOLA
80/20
0.570.57
316181AB2-040 GEN
80/20
0.5530.553
313506AB1-173 C OP
80/20
0.4910.491
3156063AA2-053SOLA
80/20
0.6110.611
3151371ROSEMS1
80/20
0.5510.551
3151361ROSEMG1
80/20
0.8890.889
3151381ROSEMG2
80/20
0.4160.416
3151281ROARAP4
80/20
0.5360.536
941031AE2-094 C
80/20
14.70614.706
934321AD1-056 C
Adder
2.50705882352941162.131
934331AD1-057 C
Adder
1.39882352941176481.189
957481AF2-042 C
Adder
16.9176470588235314.38
961671AG1-007 C
Adder
0.34588235294117650.294
934621AD1-088 C
Adder
2.76235294117647052.348
3150651CHESTF6
80/20
25.04225.042
3150761HOPPOLC
80/20
1.0681.068
316083AB2-161 C
80/20
0.340.34
933291AC2-141 C
Adder
9.0470588235294127.69
957871AF2-081 C
Adder
3.42823529411764752.914
316315AB2-025 C
80/20
0.2380.238
3151151S HAMPT1
80/20
0.5930.593
940641AE2-051 C
80/20
6.3516.351
316336AC2-165 C
Adder
-2.925882352941177-2.487
316087AB2-174 C
80/20
0.5210.521
3152431Z1-086 GT3
80/20
3.8323.832
3152421Z1-086 GT2
80/20
3.8323.832
316274AC1-208 C
Adder
3.50823529411764762.982
3151051BRUNSWICKS1
80/20
6.1926.192
3151311EDGECMA
Adder
5.7282352941176474.869
944641AF1-129 C
80/20
137.537137.537
316240AF1-291 C
80/20
2.7922.792
316033AB2-134 GEN
80/20
1.1791.179
934011AD1-025 C
80/20
1.4591.459
939191AE1-149 C
80/20
7.67.6
3151191GRAVEL3
80/20
1.1271.127
3151161SURRY 1
80/20
11.09811.098
3151211GRAVEL5
80/20
1.1271.127
316381AD1-082 C
80/20
0.7760.776
943461AF1-017 C
80/20
0.6470.647
316311AC2-079 C
80/20
2.6862.686
941591AE2-156 C
Adder
6.2764705882352945.335
944601AF1-125 C
Adder
15.18117647058823612.904
944591AF1-124 C
Adder
15.47294117647058813.152
938771AE1-103 C
80/20
1.1561.156
934511AD1-075 C
Adder
3.1141176470588232.647
934521AD1-076 C
Adder
4.5247058823529423.846
316365AB2-100 C1
80/20
0.4810.481
960081AF2-299 C
80/20
0.8560.856
3151391GASTONA
80/20
1.3541.354
316011AB1-132 C OP
80/20
1.0341.034
944011AF1-069 C
80/20
4.8054.805
3152441Z1-086 ST
80/20
6.6726.672
963041AG1-153 C
Adder
2.0188235294117651.716
3151021BRUNSWICKG1
80/20
2.9812.981
3151041BRUNSWICKG3
80/20
2.9812.981
316263AC1-034 C
Adder
2.44235294117647062.076
3151201GRAVEL4
80/20
1.1421.142
942341AE2-247 C
80/20
0.7150.715
316349AD2-085 C
80/20
1.6511.651
958161AF2-110 C
80/20
0.5350.535
938531AE1-072 C
Adder
6.04588235294117655.139
939411AE1-173 C
80/20
32.73632.736
933981AD1-022 C
Adder
3.26941176470588252.779
316023AB2-100 C2
80/20
0.4810.481
966621AG1-532 C
80/20
0.6420.642
946281AF1-292 C
80/20
0.7080.708
926071AC1-086 C
80/20
9.3179.317
3151411GASTONB
80/20
1.3541.354
3137643SOCKMAN
80/20
0.30.3
3151261ROARAP2
80/20
0.5670.567
3147043LAWRENC
80/20
0.1270.127
3152411Z1-086 GT1
80/20
3.8333.833
3151031BRUNSWICKG2
80/20
2.9812.981
927021AC1-189 C
Adder
3.0858823529411772.623
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.8996.899
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.7315.731
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.9380.938
LAGNLTFEXP_LAGN->PJM
CLTF
2.0572.057
NYPJM->LTFIMP_NY
CLTF
0.4310.431
LGEELTFEXP_LGEE->PJM
CLTF
0.2740.274
WECLTFEXP_WEC->PJM
CLTF
0.1450.145
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7131.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.64628.646
CPLELTFEXP_CPLE->PJM
CLTF
3.5953.595
TVALTFEXP_TVA->PJM
CLTF
1.6011.601
SIGELTFEXP_SIGE->PJM
CLTF
0.0560.056

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.85 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:748.92
MW Contribution:12.81
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.04 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:710.36
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150781HOPHCF2
80/20
2.052.05
3150791HOPHCF3
80/20
2.052.05
3150771HOPHCF1
80/20
2.052.05
940431AE2-027 C
80/20
6.666.66
942001AE2-212 C
80/20
2.8572.857
316132AB2-190 C
80/20
2.9822.982
316369AC1-216 C
80/20
1.0251.025
961611AG1-000B C
80/20
8.238.23
316236AE1-162 C
80/20
0.1430.143
316375AC2-012 C
80/20
0.4130.413
944581AF1-123 C
Adder
13.0152941176470611.063
941101AE2-104 C
80/20
1.2091.209
940541AE2-040 C
80/20
1.7111.711
940481AE2-033 C
80/20
9.4279.427
940491AE2-034 C
80/20
0.370.37
3156083AA2-088SOLA
80/20
0.3880.388
934501AD1-074 C
80/20
11.00411.004
3156021HOLLOMANSOL
80/20
0.6320.632
961941AG1-037 C
80/20
0.1780.178
943171AE2-346 C
80/20
0.0790.079
3156073AA1-063SOLA
80/20
0.5230.523
316181AB2-040 GEN
80/20
0.520.52
3150651CHESTF6
80/20
31.16731.167
3150761HOPPOLC
80/20
1.2891.289
316083AB2-161 C
80/20
0.3740.374
316072AD1-144 C
80/20
0.0920.092
316305AF2-043 C
80/20
0.1080.108
957871AF2-081 C
Adder
2.91294117647058842.476
316315AB2-025 C
80/20
0.2430.243
3151151S HAMPT1
80/20
0.5450.545
316087AB2-174 C
80/20
0.4920.492
932631AC2-084 C
80/20
0.3490.349
316274AC1-208 C
80/20
3.1613.161
944641AF1-129 C
80/20
171.179171.179
316240AF1-291 C
80/20
3.4573.457
316033AB2-134 GEN
80/20
1.3431.343
934011AD1-025 C
80/20
1.6611.661
939191AE1-149 C
80/20
8.6748.674
3151191GRAVEL3
80/20
1.1871.187
3151161SURRY 1
80/20
11.68311.683
3151211GRAVEL5
80/20
1.1871.187
316381AD1-082 C
80/20
0.8530.853
943461AF1-017 C
80/20
0.6550.655
316311AC2-079 C
80/20
2.6932.693
941591AE2-156 C
Adder
5.457647058823534.639
944601AF1-125 C
Adder
12.8152941176470610.893
944591AF1-124 C
Adder
13.0623529411764711.103
938771AE1-103 C
80/20
1.0631.063
934511AD1-075 C
80/20
2.7512.751
934521AD1-076 C
80/20
3.9963.996
316365AB2-100 C1
80/20
0.4730.473
316318V4-068 C
80/20
0.0290.029
960081AF2-299 C
80/20
0.8180.818
3151391GASTONA
80/20
1.2821.282
316011AB1-132 C OP
80/20
0.9790.979
316210AC1-098 C
80/20
0.3280.328
3150801HOPHCF4
80/20
3.1113.111
3150731STONECA
80/20
5.8035.803
935161AD1-151 C
80/20
10.99910.999
3151171GRAVELC
80/20
0.4080.408
3151221GRAVEL6
80/20
1.2011.201
3151201GRAVEL4
80/20
1.2021.202
942341AE2-247 C
80/20
0.7240.724
316349AD2-085 C
80/20
1.6711.671
958161AF2-110 C
80/20
0.4930.493
316246AF1-032 C
80/20
0.0890.089
938531AE1-072 C
Adder
5.1458823529411764.374
315614AA2-178 C
80/20
0.5030.503
939411AE1-173 C
Adder
24.56823529411764520.883
933981AD1-022 C
80/20
2.92.9
316023AB2-100 C2
80/20
0.4730.473
316140AB2-099 C
80/20
0.0340.034
966621AG1-532 C
80/20
0.6130.613
946281AF1-292 C
80/20
0.6770.677
926071AC1-086 C
80/20
8.8218.821
3151411GASTONB
80/20
1.2821.282
316317KELFORD C
80/20
0.1250.125
3137643SOCKMAN
80/20
0.2790.279
3151261ROARAP2
80/20
0.5210.521
3147043LAWRENC
80/20
0.1170.117
316212AC1-099 C
80/20
0.110.11
313506AB1-173 C OP
80/20
0.4620.462
3156063AA2-053SOLA
80/20
0.560.56
3151371ROSEMS1
80/20
0.5190.519
3151361ROSEMG1
80/20
0.8370.837
3151381ROSEMG2
80/20
0.3920.392
3151281ROARAP4
80/20
0.4930.493
934321AD1-056 C
80/20
2.2852.285
934331AD1-057 C
80/20
1.2741.274
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.844.84
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.2794.279
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.6820.682
LAGNLTFEXP_LAGN->PJM
CLTF
1.5581.558
NYPJM->LTFIMP_NY
CLTF
0.3360.336
LGEELTFEXP_LGEE->PJM
CLTF
0.1940.194
WECLTFEXP_WEC->PJM
CLTF
0.1020.102
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3561.356
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.36622.366
CPLELTFEXP_CPLE->PJM
CLTF
2.8462.846
TVALTFEXP_TVA->PJM
CLTF
1.211.21
SIGELTFEXP_SIGE->PJM
CLTF
0.040.04

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: H2T557_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.13 %
Rating:1065.0 MVA
Rating Type:C
MVA to Mitigate:1407.21
MW Contribution:116.3
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: H2T557_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.15 %
Rating:1065.0 MVA
Rating Type:C
MVA to Mitigate:1780.14
MW Contribution:134.71
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150481FOUR RIVERF
50/50
4.9634.963
3150451FOUR RIVERC
50/50
5.0385.038
927042AC1-191 E
50/50
7.1137.113
3150691DARBY 3
50/50
3.2743.274
3150601CHESTF5
Adder
70.6552941176470660.057
944641AF1-129 C
Adder
111.9952941176470695.196
316240AF1-291 C
Adder
2.32117647058823541.973
925332AB2-190 E
Adder
8.1470588235294116.925
935162AD1-151 E
Adder
10.7000000000000019.095
316233AE1-074 C
Adder
2.40235294117647062.042
3150501FOURRIVERG
50/50
6.2856.285
927226AC1-216 E
Adder
7.5517647058823536.419
924814AB2-134 E
Adder
12.37058823529411810.515
962962AG1-145 E
Adder
1.38941176470588231.181
939191AE1-149 C
Adder
10.0305882352941188.526
940551AE2-041 C
Adder
7.1435294117647066.072
3143316POE
Adder
1.24941176470588241.062
934146AD1-041 E
Adder
3.52588235294117652.997
957832AF2-077 E
Adder
1.33764705882352941.137
957601AF2-054 C
Adder
2.07411764705882361.763
943461AF1-017 C
Adder
1.13294117647058810.963
942342AE2-247 E
Adder
1.7282352941176471.469
936666AD2-085 E
Adder
4.7117647058823534.005
932596AC2-079 E
Adder
7.8070588235294126.636
316311AC2-079 C
Adder
4.7847058823529424.067
941591AE2-156 C
Adder
14.40941176470588112.248
944601AF1-125 C
Adder
35.35882352941176530.055
944591AF1-124 C
Adder
36.0430.634
919152AA1-139 E1
Adder
3.21764705882352952.735
938532AE1-072 E
Adder
7.2011764705882366.121
3146326AYDLETT TAP
Adder
1.06588235294117650.906
917122Z2-027 E
Adder
1.04588235294117650.889
901082W1-029 E
Adder
24.7470588235294121.035
938771AE1-103 C
Adder
2.24235294117647041.906
3145413WATKINS
Adder
0.51529411764705880.438
920692AA2-178 E
Adder
3.0352941176470592.58
920042AA2-088 E OP
Adder
7.6305882352941186.486
934511AD1-075 C
Adder
6.0917647058823535.178
934521AD1-076 C
Adder
8.8494117647058837.522
939246AE1-155 E
Adder
8.3858823529411777.128
958261AF2-120 C
Adder
6.0223529411764715.119
964212AG1-282 E
Adder
1.30235294117647071.107
960081AF2-299 C
Adder
1.2552941176470591.067
966622AG1-532 E
Adder
0.62705882352941180.533
3145723EMPORIA
Adder
0.289411764705882370.246
926072AC1-086 E
Adder
6.4505882352941175.483
923573AB1-173 E OP
Adder
2.1847058823529411.857
944011AF1-069 C
Adder
7.0176470588235295.965
957972AF2-091 E
Adder
2.29411764705882341.95
966881AG1-559 C
Adder
2.03647058823529431.731
926412AC1-112 E
50/50
1.5121.512
930122AB1-027 E
50/50
1.8591.859
3150701DARBY 4
50/50
3.2783.278
3150681DARBY 2
50/50
3.2633.263
3150671DARBY 1
50/50
3.2593.259
316169AC1-164 GEN
Adder
43.8917647058823537.308
3150731STONECA
Adder
7.29647058823529456.202
940432AE2-027 E
Adder
9.0447058823529417.688
935161AD1-151 C
Adder
16.05058823529411813.643
934012AD1-025 E
Adder
9.777647058823538.311
939612AE1-191 E
Adder
5.6423529411764714.796
934781AD1-105 C
50/50
1.5491.549
957602AF2-054 E
Adder
1.38235294117647081.175
942341AE2-247 C
Adder
1.25176470588235311.064
316349AD2-085 C
Adder
2.8882352941176472.455
943462AF1-017 E
Adder
1.8482352941176471.571
935112AD1-144 E
Adder
0.77529411764705890.659
932046AC2-012 E
Adder
10.5517647058823528.969
944582AF1-123 E
Adder
82.2352941176470769.9
944592AF1-124 E
Adder
82.532941176470670.153
958161AF2-110 C
Adder
1.09647058823529430.932
958162AF2-110 E
Adder
1.74470588235294131.483
919153AA1-139 E2
Adder
3.21764705882352952.735
938531AE1-072 C
Adder
13.81411764705882611.742
913392Y1-086 E
Adder
1.71647058823529421.459
923832AB2-022 E
Adder
0.96823529411764710.823
938772AE1-103 E
Adder
3.09647058823529432.632
916042Z1-036 E
Adder
21.6647058823529418.415
3145393UNCAMP
Adder
4.6082352941176473.917
939411AE1-173 C
Adder
60.99529411764705651.846
934512AD1-075 E
Adder
3.10117647058823562.636
934502AD1-074 E
Adder
12.40352941176470510.543
933981AD1-022 C
Adder
6.2894117647058835.346
924516AB2-100 E1
Adder
2.0282352941176471.724
958262AF2-120 E
Adder
4.0152941176470593.413
966661AG1-536 C
Adder
5.184.403
900672V4-068 E
Adder
0.25294117647058820.215
918512AA1-065 E OP
Adder
3.88823529411764753.305
940642AE2-051 E
Adder
7.3317647058823536.232
960082AF2-299 E
Adder
0.83647058823529410.711
966621AG1-532 C
Adder
0.94117647058823540.8
946281AF1-292 C
Adder
1.03882352941176470.883
926071AC1-086 C
Adder
14.17176470588235312.046
963612AG1-210 E
Adder
0.95647058823529410.813
316078AC2-138 E
Adder
0.89294117647058820.759
957971AF2-091 C
Adder
1.66117647058823531.412
944491AF1-114 C
Adder
4.88705882352941154.154
939261AE1-157 C
Adder
9.7317647058823548.272
966882AG1-559 E
Adder
1.02588235294117650.872
315052AA1-145 CT2
50/50
6.5666.566
315051AA1-145 CT1
50/50
6.5696.569
3150461FOUR RIVERD
50/50
4.0644.064
3150471FOUR RIVERE
50/50
4.0644.064
3142296MT RD221
50/50
0.1860.186
966872AG1-558 E
50/50
1.7921.792
927041AC1-191 C
50/50
14.27914.279
966871AG1-558 C
50/50
3.5563.556
316004AC1-112 C
50/50
0.4420.442
3142366NRTHEST
50/50
0.2420.242
3138116ELKO L286
Adder
1.61294117647058831.371
316076AC2-137 E
Adder
1.54705882352941181.315
3150831SPRUNCA
Adder
10.1282352941176488.609
3150841SPRUNCB
Adder
10.1282352941176488.609
940431AE2-027 C
Adder
13.56705882352941311.532
942001AE2-212 C
Adder
2.1905882352941181.862
942002AE2-212 E
Adder
1.46000000000000021.241
923842AB2-024 E
Adder
1.81529411764705871.543
961611AG1-000B C
Adder
14.80117647058823512.581
939192AE1-149 E
Adder
6.6870588235294125.684
934392AD1-063 E
Adder
1.0717647058823530.911
316157AD2-030 E
Adder
1.1635294117647060.989
939312AE1-162 E
Adder
1.24705882352941181.06
926662AC1-147 E
Adder
1.06705882352941180.907
916192Z1-068 E
Adder
1.50117647058823531.276
934065AD1-033 E
Adder
3.9752941176470593.379
944581AF1-123 C
Adder
35.91176470588235530.525
941101AE2-104 C
Adder
2.68823529411764732.285
957492AF2-043 E
Adder
1.12941176470588230.96
937226AE2-253 E
Adder
4.6070588235294123.916
923852AB2-025 E
Adder
0.86235294117647050.733
940541AE2-040 C
Adder
2.13058823529411741.811
940482AE2-033 E
Adder
8.0388235294117656.833
940481AE2-033 C
Adder
11.9247058823529410.136
943741AF1-042 C
Adder
2.81529411764705852.393
943742AF1-042 E
Adder
4.5941176470588233.905
939412AE1-173 E
Adder
40.66352941176470634.564
934501AD1-074 C
Adder
24.36705882352941220.712
962861AG1-135 C
Adder
5.8517647058823544.974
962862AG1-135 E
Adder
3.9011764705882353.316
924517AB2-100 E2
Adder
2.0282352941176471.724
966662AG1-536 E
Adder
6.9611764705882355.917
964211AG1-282 C
Adder
1.95411764705882351.661
316141AB2-099 E
Adder
0.176470588235294130.15
961941AG1-037 C
Adder
0.352941176470588260.3
961942AG1-037 E
Adder
0.235294117647058850.2
316088AB2-174 E
Adder
4.3517647058823533.699
923263AB1-132 E OP
Adder
4.1247058823529413.506
923994AB2-040_E
Adder
4.0952941176470593.481
3141813NORNECK
Adder
0.84941176470588230.722
963611AG1-210 C
Adder
0.63764705882352950.542
941032AE2-094 E
Adder
10.4941176470588248.92
941031AE2-094 C
Adder
23.43176470588235519.917
944492AF1-114 E
Adder
6.7482352941176475.736
3150431FOUR RIVERA
50/50
4.1244.124
3150441FOUR RIVERB
50/50
4.1244.124
316312AB1-027 C
50/50
0.7090.709
944631AF1-128 C
Adder
44.20941176470588437.578
926785AC1-164_E
Adder
19.72000000000000216.762
3150651CHESTF6
Adder
20.39176470588235217.333
946262AF1-291 E
Adder
1.54705882352941181.315
938552AE1-074 E
Adder
1.21058823529411751.029
316160AE1-175 E
Adder
1.14588235294117660.974
3130536PAPERMILL
Adder
6.6941176470588245.69
943471AF1-018 C
Adder
7.1435294117647066.072
925865AC1-065 E
Adder
16.6414.144
939602AE1-190 E
Adder
1.41058823529411771.199
3150921YORKTN3
Adder
107.5905882352941291.452
934576AD1-082 E
Adder
3.94470588235294173.353
316084AB2-161 E
Adder
4.9517647058823524.209
934782AD1-105 E
50/50
6.4256.425
3145256KINGFORK
Adder
0.83411764705882350.709
925522AC1-027 E
Adder
0.97294117647058820.827
933292AC2-141 E
Adder
10.1388235294117658.618
926755AC1-161 E
Adder
10.1388235294117658.618
933291AC2-141 C
Adder
23.7529411764705920.19
944602AF1-125 E
Adder
80.9447058823529368.803
941102AE2-104 E
Adder
4.2741176470588243.633
3145506HICKORY
Adder
1.7235294117647061.465
943612AF1-032 E
Adder
0.73411764705882350.624
957871AF2-081 C
Adder
7.8682352941176476.688
957872AF2-081 E
Adder
3.3717647058823532.866
936592AD2-074 E
Adder
8.7800000000000017.463
961951AG1-038 C
Adder
3.1117647058823532.645
961952AG1-038 E
Adder
4.297647058823533.653
936591AD2-074 C
Adder
5.3811764705882354.574
940492AE2-034 E
Adder
2.2764705882352941.935
3145946PLYMOUTH TP
Adder
0.234117647058823540.199
934522AD1-076 E
Adder
4.5105882352941183.834
933982AD1-022 E
Adder
3.4235294117647062.91
940641AE2-051 C
Adder
10.9988235294117669.349
943172AE2-346 E
Adder
0.42235294117647060.359
946282AF1-292 E
Adder
0.69294117647058820.589
918492AA1-063AE OP
Adder
2.78000000000000022.363
936582AD2-073 E
Adder
0.99294117647058820.844
926472AC1-118 E
Adder
0.95294117647058830.81
939262AE1-157 E
Adder
5.2788235294117654.487
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.3964.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0520.052
MECLTFEXP_MEC->PJM
CLTF
0.2980.298
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.1280.128
LAGNLTFEXP_LAGN->PJM
CLTF
2.0762.076
NYPJM->LTFIMP_NY
CLTF
0.8060.806
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.6452.645
CBM South 2LTFEXP_CBM-S2->PJM
CBM
41.47141.471
CPLELTFEXP_CPLE->PJM
CLTF
5.5585.558
TVALTFEXP_TVA->PJM
CLTF
1.5691.569
O66PJM->LTFIMP_O-066
CMTX_NF
10.11910.119
G-007PJM->LTFIMP_G-007
CMTX_NF
1.5811.581
SIGELTFEXP_SIGE->PJM
CLTF
0.0090.009

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P4-2: 224022-1_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 224022-1_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.91 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1211.01
MW Contribution:221.77
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944602AF1-125 E
50/50
154.345154.345
3145506HICKORY
50/50
3.183.18
957871AF2-081 C
50/50
12.76912.769
957872AF2-081 E
50/50
5.4725.472
944582AF1-123 E
50/50
156.806156.806
944592AF1-124 E
50/50
157.374157.374
316388AE2-253 GEN
50/50
2.6482.648
316017AA1-139 ULT1
50/50
1.3821.382
919153AA1-139 E2
50/50
5.2215.221
938531AE1-072 C
50/50
21.15821.158
913392Y1-086 E
50/50
1.9491.949
923832AB2-022 E
50/50
1.11.1
916042Z1-036 E
Adder
10.5388235294117658.958
944601AF1-125 C
50/50
67.42367.423
944591AF1-124 C
50/50
68.72168.721
316018AA1-139 ULT2
50/50
1.3821.382
919152AA1-139 E1
50/50
5.2215.221
938532AE1-072 E
50/50
11.02911.029
3146326AYDLETT TAP
50/50
1.5961.596
917122Z2-027 E
50/50
0.9950.995
901082W1-029 E
Adder
11.6788235294117649.927
944581AF1-123 C
50/50
68.47768.477
937226AE2-253 E
50/50
7.8747.874
313526AB2-022 C
50/50
0.3340.334
316320Y1-086 C
50/50
0.1950.195
316321Z2-027 C
50/50
0.2690.269
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0780.078
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.8761.876
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.8560.856
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.1890.189
LAGNLTFEXP_LAGN->PJM
CLTF
0.2510.251
LGEELTFEXP_LGEE->PJM
CLTF
0.0670.067
WECLTFEXP_WEC->PJM
CLTF
0.0370.037
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.110.11
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.1422.142
G-007ALTFEXP_G-007A->PJM
CMTX
0.1340.134
CPLELTFEXP_CPLE->PJM
CLTF
0.2290.229
TVALTFEXP_TVA->PJM
CLTF
0.1990.199
VTFLTFEXP_VFT->PJM
CMTX
0.3620.362
SIGELTFEXP_SIGE->PJM
CLTF
0.0120.012

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P4-2: 224022-2_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 224022-2_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.75 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1209.69
MW Contribution:221.56
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944602AF1-125 E
50/50
154.201154.201
3145506HICKORY
50/50
3.1773.177
957871AF2-081 C
50/50
12.75612.756
957872AF2-081 E
50/50
5.4675.467
944582AF1-123 E
50/50
156.659156.659
944592AF1-124 E
50/50
157.227157.227
316388AE2-253 GEN
50/50
2.6452.645
316017AA1-139 ULT1
50/50
1.3811.381
919153AA1-139 E2
50/50
5.2165.216
938531AE1-072 C
50/50
21.13621.136
913392Y1-086 E
50/50
1.9471.947
923832AB2-022 E
50/50
1.0991.099
916042Z1-036 E
Adder
10.5223529411764728.944
944601AF1-125 C
50/50
67.3667.36
944591AF1-124 C
50/50
68.65768.657
316018AA1-139 ULT2
50/50
1.3811.381
919152AA1-139 E1
50/50
5.2165.216
938532AE1-072 E
50/50
11.01811.018
3146326AYDLETT TAP
50/50
1.5941.594
917122Z2-027 E
50/50
0.9940.994
901082W1-029 E
Adder
11.6588235294117669.91
944581AF1-123 C
50/50
68.41368.413
937226AE2-253 E
50/50
7.8667.866
313526AB2-022 C
50/50
0.3340.334
316320Y1-086 C
50/50
0.1950.195
316321Z2-027 C
50/50
0.2690.269
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0790.079
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.8761.876
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.8550.855
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.1880.188
LAGNLTFEXP_LAGN->PJM
CLTF
0.2510.251
LGEELTFEXP_LGEE->PJM
CLTF
0.0670.067
WECLTFEXP_WEC->PJM
CLTF
0.0370.037
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.1090.109
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.1392.139
G-007ALTFEXP_G-007A->PJM
CMTX
0.1340.134
CPLELTFEXP_CPLE->PJM
CLTF
0.2280.228
TVALTFEXP_TVA->PJM
CLTF
0.1990.199
VTFLTFEXP_VFT->PJM
CMTX
0.3620.362
SIGELTFEXP_SIGE->PJM
CLTF
0.0120.012

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 271_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 271_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.49 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:729.5
MW Contribution:63.02
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957871AF2-081 C
80/20
11.88711.887
944601AF1-125 C
80/20
63.0263.02
944591AF1-124 C
80/20
64.23364.233
316018AA1-139 ULT2
80/20
1.2871.287
3156056W1-029WIND
80/20
0.2510.251
316388AE2-253 GEN
80/20
2.4682.468
316017AA1-139 ULT1
80/20
1.2871.287
938531AE1-072 C
80/20
19.67219.672
3156116Z1-036WIND
80/20
0.2150.215
316185AD1-033 C
80/20
1.7471.747
944581AF1-123 C
80/20
64.00664.006
313526AB2-022 C
80/20
0.3080.308
316320Y1-086 C
80/20
0.180.18
316321Z2-027 C
80/20
0.2470.247
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0720.072
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.6591.659
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.7490.749
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.1660.166
LAGNLTFEXP_LAGN->PJM
CLTF
0.2190.219
LGEELTFEXP_LGEE->PJM
CLTF
0.0590.059
WECLTFEXP_WEC->PJM
CLTF
0.0330.033
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0890.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.8161.816
G-007ALTFEXP_G-007A->PJM
CMTX
0.1240.124
CPLELTFEXP_CPLE->PJM
CLTF
0.1870.187
TVALTFEXP_TVA->PJM
CLTF
0.1740.174
VTFLTFEXP_VFT->PJM
CMTX
0.3330.333
SIGELTFEXP_SIGE->PJM
CLTF
0.0110.011

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2240_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2240_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.51 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:709.27
MW Contribution:63.05
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957871AF2-081 C
80/20
11.89411.894
944601AF1-125 C
80/20
63.05263.052
944591AF1-124 C
80/20
64.26664.266
316018AA1-139 ULT2
80/20
1.2881.288
3156056W1-029WIND
80/20
0.2510.251
316388AE2-253 GEN
80/20
2.4692.469
316017AA1-139 ULT1
80/20
1.2881.288
938531AE1-072 C
80/20
19.68519.685
3156116Z1-036WIND
80/20
0.2160.216
944581AF1-123 C
80/20
64.03864.038
313526AB2-022 C
80/20
0.3080.308
316320Y1-086 C
80/20
0.180.18
316321Z2-027 C
80/20
0.2470.247
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0880.088
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.8721.872
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.8320.832
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.1860.186
LAGNLTFEXP_LAGN->PJM
CLTF
0.2410.241
LGEELTFEXP_LGEE->PJM
CLTF
0.0670.067
WECLTFEXP_WEC->PJM
CLTF
0.0370.037
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0950.095
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.9451.945
G-007ALTFEXP_G-007A->PJM
CMTX
0.1540.154
CPLELTFEXP_CPLE->PJM
CLTF
0.1990.199
TVALTFEXP_TVA->PJM
CLTF
0.1910.191
VTFLTFEXP_VFT->PJM
CMTX
0.4150.415
SIGELTFEXP_SIGE->PJM
CLTF
0.0120.012

Details for 6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: H2T574_SRT-S_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.99 %
Rating:1031.0 MVA
Rating Type:C
MVA to Mitigate:1391.73
MW Contribution:69.2
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150431FOUR RIVERA
50/50
3.823.82
3150441FOUR RIVERB
50/50
3.823.82
944631AF1-128 C
Adder
26.61176470588235422.62
926785AC1-164_E
Adder
12.38352941176470510.526
3150651CHESTF6
Adder
11.81411764705882410.042
946262AF1-291 E
Adder
0.89529411764705890.761
938552AE1-074 E
Adder
0.66705882352941170.567
316160AE1-175 E
Adder
0.71882352941176480.611
3130536PAPERMILL
Adder
4.4917647058823533.818
943471AF1-018 C
Adder
4.8258823529411774.102
925865AC1-065 E
Adder
11.2164705882352949.534
939602AE1-190 E
Adder
0.95764705882352940.814
3150921YORKTN3
Adder
67.1576470588235357.084
934576AD1-082 E
Adder
2.3047058823529411.959
316084AB2-161 E
Adder
2.89176470588235322.458
934782AD1-105 E
50/50
4.8864.886
3145256KINGFORK
Adder
0.49882352941176470.424
925522AC1-027 E
Adder
0.57882352941176470.492
933292AC2-141 E
Adder
6.0694117647058825.159
926755AC1-161 E
Adder
6.0694117647058825.159
933291AC2-141 C
Adder
14.21882352941176512.086
944602AF1-125 E
Adder
48.1588235294117740.935
941102AE2-104 E
Adder
2.53411764705882362.154
3145506HICKORY
Adder
1.02470588235294110.871
943612AF1-032 E
Adder
0.43647058823529410.371
957871AF2-081 C
Adder
4.6800000000000013.978
957872AF2-081 E
Adder
2.00588235294117641.705
936592AD2-074 E
Adder
6.6858823529411765.683
961951AG1-038 C
Adder
2.37058823529411772.015
961952AG1-038 E
Adder
3.27294117647058822.782
936591AD2-074 C
Adder
4.0976470588235293.483
936582AD2-073 E
Adder
0.880.748
926472AC1-118 E
Adder
0.93294117647058830.793
3150391LDYSMT3
50/50
10.19310.193
3150411LDYSMT5
50/50
10.24410.244
939262AE1-157 E
50/50
14.45514.455
926412AC1-112 E
Adder
0.90235294117647060.767
930122AB1-027 E
Adder
1.10941176470588230.943
316169AC1-164 GEN
Adder
27.56470588235294323.43
3150731STONECA
Adder
4.3176470588235293.67
940432AE2-027 E
Adder
5.2776470588235294.486
935161AD1-151 C
Adder
9.5447058823529418.113
934012AD1-025 E
Adder
5.82352941176470654.95
939612AE1-191 E
Adder
3.8317647058823533.257
934781AD1-105 C
50/50
1.1781.178
957602AF2-054 E
Adder
0.94823529411764720.806
942341AE2-247 C
Adder
0.73764705882352940.627
316349AD2-085 C
Adder
1.70235294117647061.447
943462AF1-017 E
Adder
1.08941176470588250.926
935112AD1-144 E
Adder
0.46352941176470590.394
932046AC2-012 E
Adder
6.28352941176470655.341
944582AF1-123 E
Adder
48.92705882352941441.588
944592AF1-124 E
Adder
49.10352941176470441.738
958161AF2-110 C
Adder
0.65058823529411770.553
958162AF2-110 E
Adder
1.0352941176470590.88
919153AA1-139 E2
Adder
1.91411764705882351.627
938531AE1-072 C
Adder
8.2164705882352946.984
913392Y1-086 E
Adder
1.020.867
923832AB2-022 E
Adder
0.57647058823529410.49
958262AF2-120 E
Adder
3.15764705882352952.684
966661AG1-536 C
Adder
4.0741176470588243.463
963612AG1-210 E
Adder
0.77411764705882360.658
316078AC2-138 E
Adder
0.72235294117647060.614
957971AF2-091 C
Adder
2.08705882352941161.774
944491AF1-114 C
Adder
6.13764705882352955.217
3150331BIRCHWDA
50/50
33.12333.123
939261AE1-157 C
50/50
26.64926.649
966882AG1-559 E
50/50
2.1092.109
3150481FOUR RIVERF
50/50
4.5984.598
3150451FOUR RIVERC
50/50
4.6684.668
927042AC1-191 E
50/50
4.3364.336
3150601CHESTF5
Adder
42.53058823529412536.151
944641AF1-129 C
Adder
64.8858823529411855.153
316240AF1-291 C
Adder
1.34352941176470591.142
925332AB2-190 E
Adder
4.8388235294117664.113
935162AD1-151 E
Adder
6.3635294117647065.409
316233AE1-074 C
Adder
1.32470588235294121.126
3150501FOURRIVERG
50/50
4.5754.575
927226AC1-216 E
Adder
4.497647058823533.823
924814AB2-134 E
Adder
7.3670588235294126.262
962962AG1-145 E
Adder
0.87058823529411770.74
939191AE1-149 C
Adder
5.8258823529411774.952
940551AE2-041 C
Adder
4.8258823529411774.102
3143316POE
Adder
0.71411764705882350.607
934146AD1-041 E
Adder
2.3952941176470592.036
957832AF2-077 E
Adder
0.87647058823529410.745
957601AF2-054 C
Adder
1.42235294117647081.209
943461AF1-017 C
Adder
0.66705882352941170.567
942342AE2-247 E
Adder
1.01882352941176470.866
936666AD2-085 E
Adder
2.7764705882352942.36
932596AC2-079 E
Adder
4.6035294117647063.913
316311AC2-079 C
Adder
2.82235294117647052.399
941591AE2-156 C
Adder
8.587.293
944601AF1-125 C
Adder
21.0376470588235317.882
944591AF1-124 C
Adder
21.4423529411764718.226
919152AA1-139 E1
Adder
1.91411764705882351.627
938532AE1-072 E
Adder
4.2835294117647063.641
3146326AYDLETT TAP
Adder
0.63411764705882360.539
917122Z2-027 E
Adder
0.62117647058823530.528
939246AE1-155 E
Adder
6.5952941176470595.606
958261AF2-120 C
Adder
4.7364705882352944.026
964212AG1-282 E
Adder
1.02941176470588250.875
957972AF2-091 E
Adder
2.8811764705882352.449
3150381LDYSMT2
50/50
9.9319.931
966881AG1-559 C
50/50
4.1864.186
315052AA1-145 CT2
50/50
6.0836.083
315051AA1-145 CT1
50/50
6.0866.086
3150461FOUR RIVERD
50/50
3.7653.765
3150471FOUR RIVERE
50/50
3.7653.765
3142296MT RD221
50/50
0.1070.107
966872AG1-558 E
50/50
1.0921.092
927041AC1-191 C
50/50
8.7048.704
966871AG1-558 C
50/50
2.1682.168
3138116ELKO L286
Adder
0.98705882352941180.839
316076AC2-137 E
Adder
0.94588235294117650.804
3150831SPRUNCA
Adder
5.78235294117647054.915
3150841SPRUNCB
Adder
5.78235294117647054.915
940431AE2-027 C
Adder
7.917647058823536.73
942001AE2-212 C
Adder
1.26117647058823531.072
942002AE2-212 E
Adder
0.84117647058823530.715
923842AB2-024 E
Adder
1.21529411764705891.033
961611AG1-000B C
Adder
8.8552941176470597.527
939192AE1-149 E
Adder
3.88470588235294123.302
934392AD1-063 E
Adder
0.72352941176470590.615
316157AD2-030 E
Adder
0.79764705882352950.678
939312AE1-162 E
Adder
0.74588235294117660.634
926662AC1-147 E
Adder
0.63529411764705890.54
916192Z1-068 E
Adder
0.89294117647058820.759
934065AD1-033 E
Adder
2.36588235294117682.011
944581AF1-123 C
Adder
21.36588235294117818.161
941101AE2-104 C
Adder
1.59411764705882361.355
957492AF2-043 E
Adder
0.67176470588235290.571
937226AE2-253 E
Adder
2.742.329
943741AF1-042 C
Adder
2.1447058823529411.823
943742AF1-042 E
Adder
3.4988235294117652.974
962861AG1-135 C
Adder
4.5670588235294123.882
962862AG1-135 E
Adder
3.04470588235294142.588
966662AG1-536 E
Adder
5.4752941176470594.654
964211AG1-282 C
Adder
1.54470588235294121.313
3141813NORNECK
Adder
0.68705882352941170.584
963611AG1-210 C
Adder
0.51647058823529410.439
944492AF1-114 E
Adder
8.4752941176470587.204
957191AF2-013 C
Adder
15.57176470588235313.236
3141316ARNOLDS
50/50
0.2260.226
3150371LDYSMT1
50/50
9.8049.804
3150401LDYSMT4
50/50
10.21210.212
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.7883.788
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.7974.797
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.6820.682
LAGNLTFEXP_LAGN->PJM
CLTF
1.8271.827
NYPJM->LTFIMP_NY
CLTF
0.920.92
LGEELTFEXP_LGEE->PJM
CLTF
0.1870.187
WECLTFEXP_WEC->PJM
CLTF
0.0880.088
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6281.628
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.18327.183
CPLELTFEXP_CPLE->PJM
CLTF
3.4193.419
TVALTFEXP_TVA->PJM
CLTF
1.4341.434
O66PJM->LTFIMP_O-066
CMTX_NF
12.34612.346
G-007PJM->LTFIMP_G-007
CMTX_NF
1.9371.937
SIGELTFEXP_SIGE->PJM
CLTF
0.040.04

Details for 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2110T2128_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2110T2128_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.86 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1019.7
MW Contribution:127.07
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2110T2128_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.8 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:844.93
MW Contribution:76.07
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944602AF1-125 E
50/50
88.43888.438
3145506HICKORY
50/50
1.8381.838
957871AF2-081 C
50/50
7.5937.593
957872AF2-081 E
50/50
3.2543.254
944582AF1-123 E
50/50
89.84889.848
944592AF1-124 E
50/50
90.17490.174
316388AE2-253 GEN
50/50
1.5561.556
316017AA1-139 ULT1
50/50
0.8220.822
919153AA1-139 E2
50/50
3.1053.105
938531AE1-072 C
50/50
12.75712.757
913392Y1-086 E
50/50
1.2751.275
923832AB2-022 E
50/50
0.720.72
916042Z1-036 E
Adder
9.4541176470588238.036
944601AF1-125 C
50/50
38.63338.633
944591AF1-124 C
50/50
39.37639.376
316018AA1-139 ULT2
50/50
0.8220.822
919152AA1-139 E1
50/50
3.1053.105
938532AE1-072 E
50/50
6.656.65
3146326AYDLETT TAP
50/50
0.9670.967
917122Z2-027 E
Adder
0.68941176470588230.586
901082W1-029 E
Adder
10.9882352941176479.34
316185AD1-033 C
50/50
1.5071.507
934065AD1-033 E
50/50
6.1486.148
944581AF1-123 C
50/50
39.23739.237
937226AE2-253 E
50/50
4.6274.627
313526AB2-022 C
50/50
0.2190.219
316320Y1-086 C
50/50
0.1280.128
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0290.029
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.2612.261
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.1721.172
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.240.24
LAGNLTFEXP_LAGN->PJM
CLTF
0.3650.365
LGEELTFEXP_LGEE->PJM
CLTF
0.0820.082
WECLTFEXP_WEC->PJM
CLTF
0.0450.045
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.2270.227
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.8453.845
G-007ALTFEXP_G-007A->PJM
CMTX
0.0330.033
CPLELTFEXP_CPLE->PJM
CLTF
0.4750.475
TVALTFEXP_TVA->PJM
CLTF
0.2870.287
VTFLTFEXP_VFT->PJM
CMTX
0.0910.091
SIGELTFEXP_SIGE->PJM
CLTF
0.0150.015

Details for 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P4-2: 212822_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 212822_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.29 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:998.4
MW Contribution:157.15
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944602AF1-125 E
50/50
109.375109.375
3145506HICKORY
50/50
2.2562.256
957871AF2-081 C
50/50
9.0969.096
957872AF2-081 E
50/50
3.8983.898
944582AF1-123 E
50/50
111.119111.119
944592AF1-124 E
50/50
111.521111.521
316388AE2-253 GEN
50/50
1.8831.883
316017AA1-139 ULT1
50/50
0.9850.985
919153AA1-139 E2
50/50
3.723.72
938531AE1-072 C
50/50
15.10215.102
913392Y1-086 E
50/50
1.4081.408
923832AB2-022 E
50/50
0.7950.795
944601AF1-125 C
50/50
47.77847.778
944591AF1-124 C
50/50
48.69848.698
316018AA1-139 ULT2
50/50
0.9850.985
919152AA1-139 E1
50/50
3.723.72
938532AE1-072 E
50/50
7.8727.872
3146326AYDLETT TAP
50/50
1.141.14
917122Z2-027 E
Adder
0.72470588235294120.616
316185AD1-033 C
50/50
1.7831.783
934065AD1-033 E
50/50
7.2747.274
944581AF1-123 C
50/50
48.52648.526
937226AE2-253 E
50/50
5.65.6
313526AB2-022 C
50/50
0.2410.241
316320Y1-086 C
50/50
0.1410.141
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0430.043
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4081.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.6750.675
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.1450.145
LAGNLTFEXP_LAGN->PJM
CLTF
0.2030.203
LGEELTFEXP_LGEE->PJM
CLTF
0.0510.051
WECLTFEXP_WEC->PJM
CLTF
0.0280.028
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.1020.102
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.8891.889
G-007ALTFEXP_G-007A->PJM
CMTX
0.070.07
CPLELTFEXP_CPLE->PJM
CLTF
0.2140.214
TVALTFEXP_TVA->PJM
CLTF
0.160.16
VTFLTFEXP_VFT->PJM
CMTX
0.190.19
SIGELTFEXP_SIGE->PJM
CLTF
0.0090.009

Details for 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P4-2: 269T2128_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 269T2128_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.98 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:970.97
MW Contribution:147.89
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944602AF1-125 E
50/50
102.93102.93
3145506HICKORY
50/50
2.0612.061
957871AF2-081 C
50/50
7.4647.464
957872AF2-081 E
50/50
3.1993.199
944582AF1-123 E
50/50
104.572104.572
944592AF1-124 E
50/50
104.95104.95
316388AE2-253 GEN
50/50
1.6181.618
316017AA1-139 ULT1
50/50
0.8080.808
919153AA1-139 E2
50/50
3.0523.052
938531AE1-072 C
50/50
11.17211.172
913392Y1-086 E
Adder
1.04352941176470580.887
923832AB2-022 E
Adder
0.58941176470588240.501
944601AF1-125 C
50/50
44.96344.963
944591AF1-124 C
50/50
45.82945.829
316018AA1-139 ULT2
50/50
0.8080.808
919152AA1-139 E1
50/50
3.0523.052
938532AE1-072 E
50/50
5.8245.824
3146326AYDLETT TAP
50/50
0.8630.863
917122Z2-027 E
Adder
0.52941176470588240.45
316185AD1-033 C
50/50
1.7111.711
934065AD1-033 E
50/50
6.9816.981
944581AF1-123 C
50/50
45.66745.667
937226AE2-253 E
50/50
4.8124.812
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0590.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.321.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.5930.593
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.1320.132
LAGNLTFEXP_LAGN->PJM
CLTF
0.1730.173
LGEELTFEXP_LGEE->PJM
CLTF
0.0470.047
WECLTFEXP_WEC->PJM
CLTF
0.0260.026
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.070.07
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.4241.424
G-007ALTFEXP_G-007A->PJM
CMTX
0.1020.102
CPLELTFEXP_CPLE->PJM
CLTF
0.1470.147
TVALTFEXP_TVA->PJM
CLTF
0.1370.137
VTFLTFEXP_VFT->PJM
CMTX
0.2740.274
SIGELTFEXP_SIGE->PJM
CLTF
0.0090.009

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.54 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1199.86
MW Contribution:55.37
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.15 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1216.93
MW Contribution:55.94
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
925522AC1-027 E
Adder
0.430588235294117660.366
933292AC2-141 E
Adder
6.3529411764705895.4
926755AC1-161 E
Adder
6.3529411764705895.4
933291AC2-141 C
Adder
14.88235294117647112.65
944602AF1-125 E
Adder
38.536470588235332.756
3145506HICKORY
Adder
0.80470588235294130.684
957871AF2-081 C
Adder
3.47411764705882352.953
957872AF2-081 E
Adder
1.48941176470588241.266
940641AE2-051 C
50/50
14.85114.851
944012AF1-069 E
50/50
4.4634.463
3152431Z1-086 GT3
50/50
8.9728.972
3152421Z1-086 GT2
50/50
8.9728.972
3151051BRUNSWICKS1
50/50
14.35614.356
934622AD1-088 E
50/50
2.6942.694
3151531CLOVER1
50/50
7.797.79
964242AG1-285 E
Adder
3.99647058823529383.397
937482AD2-202 E
50/50
0.6470.647
934612AD1-087 E
50/50
2.212.21
934611AD1-087 C
50/50
0.7660.766
924162AB2-060 E OP
Adder
1.4435294117647061.227
961792AG1-021 E
Adder
0.50117647058823530.426
3138533PONTONDP
Adder
0.217647058823529420.185
964792AG1-342 E
Adder
0.95647058823529410.813
927255AC1-221 E
Adder
1.70117647058823531.446
932763AC2-100 E
Adder
1.14235294117647060.971
932046AC2-012 E
Adder
4.4317647058823533.767
944582AF1-123 E
Adder
39.15058823529411633.278
944592AF1-124 E
Adder
39.2929411764705933.399
919153AA1-139 E2
Adder
1.42117647058823531.208
938531AE1-072 C
Adder
5.95529411764705955.062
913392Y1-086 E
Adder
0.66235294117647060.563
923832AB2-022 E
Adder
0.374117647058823550.318
939411AE1-173 C
50/50
67.01167.011
940642AE2-051 E
50/50
9.9019.901
966621AG1-532 C
Adder
-1.14-0.969
946281AF1-292 C
Adder
-1.2576470588235293-1.069
3137643SOCKMAN
Adder
-0.34352941176470586-0.292
3152411Z1-086 GT1
50/50
8.9758.975
3151031BRUNSWICKG2
50/50
6.916.91
963042AG1-153 E
50/50
7.0227.022
3151541CLOVER2
50/50
7.7177.717
964241AG1-285 C
Adder
5.9952941176470595.096
937481AD2-202 C
50/50
0.2220.222
924022AB2-043 E O1
Adder
1.75058823529411781.488
3147223TWITTYS
Adder
0.42235294117647060.359
959312AF2-222 E
Adder
4.8764705882352944.145
924302AB2-077 E O1
Adder
0.45058823529411770.383
958212AF2-115 E
Adder
0.62588235294117660.532
962561AG1-105 C
Adder
3.50352941176470622.978
944641AF1-129 C
Adder
-99.89764705882352-84.913
316240AF1-291 C
Adder
-2.2705882352941176-1.93
941591AE2-156 C
Adder
6.1035294117647065.188
944601AF1-125 C
Adder
16.8341176470588214.309
944591AF1-124 C
Adder
17.15764705882352814.584
919152AA1-139 E1
Adder
1.42117647058823531.208
938532AE1-072 E
Adder
3.1047058823529412.639
3146326AYDLETT TAP
Adder
0.455294117647058850.387
3145723EMPORIA
Adder
-0.3270588235294118-0.278
944011AF1-069 C
50/50
11.48911.489
3152441Z1-086 ST
50/50
15.62215.622
963041AG1-153 C
50/50
4.6824.682
3151021BRUNSWICKG1
50/50
6.916.91
3151041BRUNSWICKG3
50/50
6.916.91
959311AF2-222 C
Adder
7.2776470588235296.186
936261AD2-033 C
Adder
4.3352941176470593.685
3147133PAMPLIN
Adder
0.377647058823529450.321
961791AG1-021 C
Adder
0.58823529411764710.5
942462AE2-259 E
Adder
2.21764705882352951.885
962562AG1-105 E
Adder
2.3352941176470591.985
964791AG1-342 C
Adder
1.43529411764705881.22
927264AC1-222 E
Adder
1.781.513
942001AE2-212 C
Adder
-2.8705882352941177-2.44
926662AC1-147 E
Adder
0.448235294117647070.381
916192Z1-068 E
Adder
0.6682352941176470.568
934065AD1-033 E
Adder
1.87294117647058831.592
944581AF1-123 C
Adder
17.0976470588235314.533
937226AE2-253 E
Adder
2.081.768
939412AE1-173 E
50/50
44.67444.674
941032AE2-094 E
50/50
15.74915.749
941031AE2-094 C
50/50
35.16335.163
934321AD1-056 C
Adder
-2.142352941176471-1.821
934331AD1-057 C
Adder
-1.1952941176470588-1.016
957481AF2-042 C
50/50
35.70935.709
957482AF2-042 E
50/50
23.80623.806
934621AD1-088 C
50/50
5.5965.596
925612AC1-036 E
Adder
0.381176470588235340.324
924322AB2-079 E O1
Adder
0.45058823529411770.383
924312AB2-078 E O1
Adder
0.45058823529411770.383
936262AD2-033 E
Adder
2.89058823529411772.457
946301AF1-294 C
Adder
1.2082352941176471.027
946302AF1-294 E
Adder
1.02352941176470580.87
958211AF2-115 C
Adder
0.73529411764705890.625
942461AE2-259 C
Adder
3.32588235294117632.827
935172AD1-152 E
Adder
3.1047058823529412.639
926274AC1-105 E
Adder
1.15529411764705880.982
943902AF1-058 E
Adder
0.58823529411764710.5
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.10812.108
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4868.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4991.499
LAGNLTFEXP_LAGN->PJM
CLTF
2.9182.918
NYPJM->LTFIMP_NY
CLTF
0.4470.447
LGEELTFEXP_LGEE->PJM
CLTF
0.4670.467
WECLTFEXP_WEC->PJM
CLTF
0.2490.249
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9681.968
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.24536.245
CPLELTFEXP_CPLE->PJM
CLTF
4.1284.128
TVALTFEXP_TVA->PJM
CLTF
2.2832.283
O66PJM->LTFIMP_O-066
CMTX_NF
6.1826.182
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9710.971
SIGELTFEXP_SIGE->PJM
CLTF
0.0920.092

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.13 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4181.52
MW Contribution:228.68
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.66 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4635.61
MW Contribution:230.14
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
942341AE2-247 C
Adder
2.11764705882352941.8
316349AD2-085 C
Adder
4.8858823529411764.153
943462AF1-017 E
Adder
3.12588235294117662.657
935112AD1-144 E
Adder
1.38117647058823521.174
932046AC2-012 E
50/50
20.04320.043
944582AF1-123 E
50/50
161.69161.69
944592AF1-124 E
50/50
162.275162.275
958161AF2-110 C
Adder
2.04352941176470631.737
958162AF2-110 E
Adder
3.24941176470588242.762
316388AE2-253 GEN
50/50
3.0473.047
316017AA1-139 ULT1
50/50
1.6761.676
919153AA1-139 E2
50/50
6.336.33
938531AE1-072 C
50/50
27.18327.183
913392Y1-086 E
50/50
3.383.38
923832AB2-022 E
50/50
1.9081.908
938772AE1-103 E
Adder
6.0023529411764715.102
916042Z1-036 E
Adder
43.3141176470588236.817
3145393UNCAMP
Adder
9.0117647058823537.66
939411AE1-173 C
50/50
158.79158.79
934512AD1-075 E
Adder
6.3941176470588235.435
934502AD1-074 E
Adder
25.5776470588235321.741
933981AD1-022 C
Adder
13.02235294117647211.069
924516AB2-100 E1
Adder
4.23058823529411753.596
900672V4-068 E
Adder
0.52352941176470590.445
918512AA1-065 E OP
Adder
8.1470588235294116.925
940642AE2-051 E
50/50
20.9220.92
960082AF2-299 E
Adder
1.80588235294117651.535
966621AG1-532 C
Adder
2.0317647058823531.727
946281AF1-292 C
Adder
2.24235294117647041.906
926071AC1-086 C
Adder
30.4329411764705925.868
3137643SOCKMAN
Adder
1.03058823529411760.876
3152411Z1-086 GT1
50/50
18.60518.605
3151031BRUNSWICKG2
50/50
14.45814.458
963042AG1-153 E
50/50
14.69214.692
918532AA1-067 E
Adder
1.02823529411764710.874
919710AA2-057 E
Adder
5.6458823529411774.799
927021AC1-189 C
Adder
12.02000000000000110.217
964241AG1-285 C
Adder
17.9658823529411815.271
924022AB2-043 E O1
Adder
7.1670588235294126.092
924152AB2-059 E OP
Adder
7.4317647058823546.317
3147223TWITTYS
Adder
1.2588235294117651.07
3150921YORKTN3
Adder
152.65647058823532129.758
934576AD1-082 E
Adder
5.7482352941176484.886
316084AB2-161 E
Adder
7.2141176470588236.132
3145256KINGFORK
Adder
1.48823529411764691.265
3151101ELIZAR3
50/50
4.9744.974
3151081ELIZAR1
50/50
4.9124.912
3151091ELIZAR2
50/50
4.8264.826
925522AC1-027 E
50/50
1.8771.877
916191Z1-068 C
50/50
0.0680.068
933292AC2-141 E
50/50
20.76320.763
926755AC1-161 E
50/50
20.76320.763
316294AC1-161 C
50/50
7.9487.948
933291AC2-141 C
50/50
48.6448.64
944602AF1-125 E
50/50
159.152159.152
941102AE2-104 E
Adder
7.966.766
3145506HICKORY
50/50
3.3883.388
943612AF1-032 E
Adder
1.40823529411764731.197
957871AF2-081 C
50/50
15.47915.479
957872AF2-081 E
50/50
6.6346.634
316315AB2-025 C
50/50
0.6050.605
940492AE2-034 E
Adder
4.6305882352941183.936
3145946PLYMOUTH TP
Adder
0.48235294117647060.41
934522AD1-076 E
Adder
9.3011764705882357.906
933982AD1-022 E
Adder
7.0894117647058836.026
940641AE2-051 C
50/50
31.3831.38
943172AE2-346 E
Adder
0.88941176470588230.756
946282AF1-292 E
Adder
1.49529411764705871.271
918492AA1-063AE OP
Adder
5.9423529411764715.051
917332KELFORD E
Adder
2.39764705882352922.038
925122AB2-169 E
Adder
8.4305882352941197.166
944012AF1-069 E
50/50
9.0749.074
932632AC2-084 E
Adder
4.6458823529411763.949
926214AC1-099 E
Adder
1.73647058823529421.476
3152431Z1-086 GT3
50/50
18.59918.599
3152421Z1-086 GT2
50/50
18.59918.599
316274AC1-208 C
Adder
12.93882352941176410.998
927146AC1-208 E
Adder
5.74470588235294164.883
3151051BRUNSWICKS1
50/50
30.03530.035
917512Z2-088 E OP1
Adder
6.9717647058823535.926
917342Z2-044 E
Adder
0.84705882352941180.72
934622AD1-088 E
Adder
6.6576470588235295.659
964242AG1-285 E
Adder
11.97764705882352810.181
937482AD2-202 E
Adder
1.57764705882352941.341
934612AD1-087 E
Adder
5.3905882352941184.582
3151311EDGECMA
Adder
21.84705882352941218.57
924162AB2-060 E OP
Adder
5.8752941176470594.994
964792AG1-342 E
Adder
3.1905882352941182.712
959312AF2-222 E
Adder
14.53882352941176512.358
924302AB2-077 E O1
Adder
1.84705882352941191.57
962561AG1-105 C
Adder
12.04705882352941210.24
939191AE1-149 C
Adder
13.15411764705882411.181
3143316POE
Adder
1.71764705882352931.46
943461AF1-017 C
Adder
1.91529411764705881.628
942342AE2-247 E
Adder
2.92470588235294172.486
936666AD2-085 E
Adder
7.9705882352941196.775
932596AC2-079 E
Adder
13.36941176470588411.364
316311AC2-079 C
Adder
8.1941176470588236.965
316036AC1-147 C
50/50
0.5640.564
941591AE2-156 C
50/50
27.4127.41
316316AC1-027 C
50/50
0.4870.487
944601AF1-125 C
50/50
69.52369.523
944591AF1-124 C
50/50
70.86170.861
316018AA1-139 ULT2
50/50
1.6761.676
919152AA1-139 E1
50/50
6.336.33
938532AE1-072 E
50/50
14.1714.17
3146326AYDLETT TAP
50/50
2.0962.096
917122Z2-027 E
Adder
2.061.751
901082W1-029 E
Adder
48.63529411764706441.34
938771AE1-103 C
Adder
4.3470588235294113.695
3145413WATKINS
Adder
1.02235294117647070.869
920692AA2-178 E
Adder
6.1741176470588245.248
920042AA2-088 E OP
Adder
15.59882352941176513.259
934511AD1-075 C
Adder
12.56117647058823510.677
934521AD1-076 C
Adder
18.24823529411764515.511
960081AF2-299 C
Adder
2.70823529411764732.302
966622AG1-532 E
Adder
1.35411764705882361.151
3145723EMPORIA
Adder
0.62470588235294120.531
926072AC1-086 E
Adder
13.85058823529411711.773
923573AB1-173 E OP
Adder
4.7517647058823534.039
919692AA2-053 E OP
Adder
6.1282352941176475.209
944011AF1-069 C
50/50
23.35723.357
926206AC1-098 E
Adder
5.25647058823529444.468
3152441Z1-086 ST
50/50
32.38632.386
963041AG1-153 C
50/50
9.7959.795
3151021BRUNSWICKG1
50/50
14.45814.458
3151041BRUNSWICKG3
50/50
14.45814.458
925785AC1-054 E
Adder
4.8741176470588234.143
922923AB1-081 E OP
Adder
5.2458823529411764.459
316263AC1-034 C
Adder
9.344705882352947.943
959311AF2-222 C
Adder
21.718.445
936261AD2-033 C
Adder
6.71764705882352955.71
962562AG1-105 E
Adder
8.0317647058823526.827
964791AG1-342 C
Adder
4.7858823529411764.068
961611AG1-000B C
Adder
19.52941176470588416.6
939192AE1-149 E
Adder
8.7694117647058827.454
939312AE1-162 E
Adder
1.95882352941176491.665
3150981CHESPKA
50/50
0.6670.667
316375AC2-012 C
50/50
2.0662.066
926662AC1-147 E
50/50
2.0262.026
3150991CHESPKB
50/50
1.1051.105
916192Z1-068 E
50/50
2.92.9
316185AD1-033 C
50/50
1.9111.911
934065AD1-033 E
50/50
7.7977.797
944581AF1-123 C
50/50
70.6170.61
941101AE2-104 C
Adder
5.00705882352941254.256
957492AF2-043 E
Adder
2.16705882352941171.842
937226AE2-253 E
50/50
9.0629.062
313526AB2-022 C
50/50
0.5790.579
316320Y1-086 C
50/50
0.3390.339
923852AB2-025 E
50/50
1.7231.723
940541AE2-040 C
Adder
4.263.621
940482AE2-033 E
Adder
16.1613.736
940481AE2-033 C
Adder
23.97176470588235420.376
939412AE1-173 E
50/50
105.86105.86
934501AD1-074 C
Adder
50.2447058823529442.708
924517AB2-100 E2
Adder
4.23058823529411753.596
316141AB2-099 E
Adder
0.370588235294117660.315
961941AG1-037 C
Adder
0.74117647058823530.63
961942AG1-037 E
Adder
0.494117647058823550.42
316088AB2-174 E
Adder
9.4435294117647068.027
923263AB1-132 E OP
Adder
8.8564705882352937.528
923994AB2-040_E
Adder
8.9094117647058837.573
941032AE2-094 E
50/50
32.01732.017
941031AE2-094 C
50/50
71.48571.485
934321AD1-056 C
Adder
8.927.582
934332AD1-057 E
Adder
2.5917647058823532.203
934322AD1-056 E
Adder
4.8388235294117664.113
934331AD1-057 C
Adder
4.9764705882352954.23
927022AC1-189 E
Adder
5.9882352941176475.09
957481AF2-042 C
50/50
83.22783.227
957482AF2-042 E
50/50
55.48555.485
961672AG1-007 E
Adder
0.75529411764705890.642
961671AG1-007 C
Adder
1.33294117647058831.133
934621AD1-088 C
Adder
13.82823529411764711.754
925595AC1-034 E
Adder
7.0494117647058835.992
925612AC1-036 E
Adder
1.13647058823529410.966
924322AB2-079 E O1
Adder
1.84705882352941191.57
924312AB2-078 E O1
Adder
1.84705882352941191.57
935172AD1-152 E
Adder
7.9105882352941186.724
926274AC1-105 E
Adder
3.63.06
943902AF1-058 E
Adder
1.71882352941176491.461
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.88834.888
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.38927.389
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.6044.604
LAGNLTFEXP_LAGN->PJM
CLTF
9.689.68
NYPJM->LTFIMP_NY
CLTF
2.172.17
LGEELTFEXP_LGEE->PJM
CLTF
1.3891.389
WECLTFEXP_WEC->PJM
CLTF
0.7290.729
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6337.633
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.923129.923
CPLELTFEXP_CPLE->PJM
CLTF
16.01716.017
TVALTFEXP_TVA->PJM
CLTF
7.5637.563
O66PJM->LTFIMP_O-066
CMTX_NF
29.52729.527
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6364.636
SIGELTFEXP_SIGE->PJM
CLTF
0.2790.279

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.17 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4104.33
MW Contribution:207.66
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150921YORKTN3
Adder
64.9600000000000155.216
934576AD1-082 E
Adder
5.4388235294117654.623
316084AB2-161 E
Adder
6.8258823529411765.802
3145256KINGFORK
Adder
1.35529411764705881.152
3151101ELIZAR3
50/50
4.524.52
3151081ELIZAR1
50/50
4.4634.463
3151091ELIZAR2
50/50
4.3854.385
925522AC1-027 E
50/50
1.7051.705
916191Z1-068 C
50/50
0.0610.061
933292AC2-141 E
50/50
18.61818.618
926755AC1-161 E
50/50
18.61818.618
316294AC1-161 C
50/50
7.1277.127
933291AC2-141 C
50/50
43.61643.616
944602AF1-125 E
50/50
144.526144.526
941102AE2-104 E
Adder
7.3058823529411766.21
3145506HICKORY
50/50
3.0783.078
943612AF1-032 E
Adder
1.28470588235294141.092
957871AF2-081 C
50/50
14.0814.08
957872AF2-081 E
50/50
6.0346.034
316315AB2-025 C
50/50
0.5820.582
940492AE2-034 E
Adder
4.2752941176470593.634
3145946PLYMOUTH TP
Adder
0.44705882352941180.38
934522AD1-076 E
Adder
8.6200000000000017.327
933982AD1-022 E
Adder
6.582352941176475.595
940641AE2-051 C
50/50
29.73129.731
943172AE2-346 E
Adder
0.8317647058823530.707
946282AF1-292 E
Adder
1.4270588235294121.213
918492AA1-063AE OP
Adder
5.6035294117647064.763
917332KELFORD E
Adder
2.25058823529411761.913
925122AB2-169 E
Adder
7.8694117647058836.689
944012AF1-069 E
50/50
8.6848.684
932632AC2-084 E
Adder
4.3905882352941183.732
926214AC1-099 E
Adder
1.64117647058823551.395
3152431Z1-086 GT3
50/50
17.80617.806
3152421Z1-086 GT2
50/50
17.80617.806
316274AC1-208 C
Adder
12.25411764705882510.416
927146AC1-208 E
Adder
5.44117647058823554.625
3151051BRUNSWICKS1
50/50
28.7628.76
917512Z2-088 E OP1
Adder
6.5941176470588245.605
917342Z2-044 E
Adder
0.80352941176470590.683
934622AD1-088 E
Adder
6.4094117647058835.448
961611AG1-000B C
Adder
18.02352941176470615.32
939192AE1-149 E
Adder
8.424705882352947.161
939312AE1-162 E
Adder
1.79058823529411781.522
316375AC2-012 C
50/50
1.8781.878
926662AC1-147 E
Adder
1.84117647058823521.565
916192Z1-068 E
50/50
2.6352.635
316185AD1-033 C
50/50
1.7361.736
934065AD1-033 E
50/50
7.0817.081
944581AF1-123 C
50/50
64.12164.121
941101AE2-104 C
Adder
4.5952941176470593.906
957492AF2-043 E
Adder
1.97647058823529421.68
937226AE2-253 E
50/50
8.2398.239
923852AB2-025 E
50/50
1.6571.657
940541AE2-040 C
50/50
4.0974.097
940482AE2-033 E
50/50
15.52815.528
940481AE2-033 C
50/50
23.03323.033
939412AE1-173 E
50/50
99.43599.435
934501AD1-074 C
Adder
46.5682352941176539.583
924517AB2-100 E2
Adder
4.042352941176473.436
316141AB2-099 E
Adder
0.347058823529411750.295
961941AG1-037 C
Adder
0.69294117647058820.589
961942AG1-037 E
Adder
0.462352941176470630.393
316088AB2-174 E
Adder
8.997647058823537.648
923263AB1-132 E OP
Adder
8.4105882352941177.149
923994AB2-040_E
Adder
8.487.208
941032AE2-094 E
50/50
30.64130.641
941031AE2-094 C
50/50
68.41468.414
934321AD1-056 C
Adder
8.477647058823537.206
934332AD1-057 E
Adder
2.46235294117647062.093
934322AD1-056 E
Adder
4.59882352941176453.909
934331AD1-057 C
Adder
4.72941176470588154.02
927022AC1-189 E
Adder
5.6541176470588244.806
957481AF2-042 C
50/50
79.94679.946
957482AF2-042 E
50/50
53.29753.297
961672AG1-007 E
Adder
0.71529411764705890.608
961671AG1-007 C
Adder
1.26235294117647071.073
934621AD1-088 C
Adder
13.31176470588235211.315
925595AC1-034 E
Adder
6.702352941176475.697
925612AC1-036 E
Adder
1.09882352941176480.934
924322AB2-079 E O1
Adder
1.77764705882352941.511
924312AB2-078 E O1
Adder
1.77764705882352941.511
936262AD2-033 E
Adder
10.6635294117647069.064
935172AD1-152 E
Adder
7.6094117647058826.468
926274AC1-105 E
Adder
3.4682352941176472.948
943902AF1-058 E
Adder
1.65647058823529411.408
3151531CLOVER1
50/50
18.24518.245
964242AG1-285 E
Adder
11.549.809
937482AD2-202 E
50/50
1.5171.517
934612AD1-087 E
50/50
5.1825.182
934611AD1-087 C
50/50
1.7961.796
3151311EDGECMA
Adder
20.7705882352941217.655
924162AB2-060 E OP
Adder
5.6588235294117644.81
964792AG1-342 E
Adder
3.07411764705882362.613
942341AE2-247 C
Adder
1.9647058823529411.67
316349AD2-085 C
Adder
4.5341176470588243.854
943462AF1-017 E
Adder
2.90117647058823552.466
935112AD1-144 E
Adder
1.2588235294117651.07
932046AC2-012 E
50/50
18.21618.216
944582AF1-123 E
50/50
146.831146.831
944592AF1-124 E
50/50
147.363147.363
958161AF2-110 C
Adder
1.8752941176470591.594
958162AF2-110 E
Adder
2.98235294117647072.535
316388AE2-253 GEN
50/50
2.7712.771
316017AA1-139 ULT1
50/50
1.5241.524
919153AA1-139 E2
50/50
5.7585.758
938531AE1-072 C
50/50
24.73924.739
913392Y1-086 E
Adder
3.08235294117647072.62
923832AB2-022 E
Adder
1.74000000000000021.479
938772AE1-103 E
Adder
5.5529411764705884.72
916042Z1-036 E
Adder
39.78705882352941433.819
3145393UNCAMP
Adder
8.3505882352941197.098
939411AE1-173 C
50/50
149.153149.153
934512AD1-075 E
Adder
5.9258823529411765.037
934502AD1-074 E
Adder
23.70588235294117420.15
933981AD1-022 C
Adder
12.09058823529411710.277
924516AB2-100 E1
Adder
4.042352941176473.436
900672V4-068 E
Adder
0.490588235294117660.417
918512AA1-065 E OP
Adder
7.6023529411764716.462
940642AE2-051 E
50/50
19.82119.821
960082AF2-299 E
Adder
1.7247058823529411.466
966621AG1-532 C
Adder
1.94000000000000021.649
946281AF1-292 C
Adder
2.14117647058823521.82
926071AC1-086 C
Adder
28.90117647058823624.566
3137643SOCKMAN
Adder
0.97882352941176460.832
3152411Z1-086 GT1
50/50
17.81217.812
3151031BRUNSWICKG2
50/50
13.84413.844
963042AG1-153 E
50/50
14.06814.068
918532AA1-067 E
Adder
0.96823529411764710.823
919710AA2-057 E
Adder
5.3541176470588244.551
927021AC1-189 C
Adder
11.3505882352941179.648
3151541CLOVER2
50/50
18.07518.075
964241AG1-285 C
Adder
17.3105882352941214.714
937481AD2-202 C
50/50
0.5210.521
924022AB2-043 E O1
Adder
6.95.865
924152AB2-059 E OP
Adder
7.0658823529411776.006
3147223TWITTYS
Adder
1.21764705882352931.035
959312AF2-222 E
Adder
14.06705882352941311.957
924302AB2-077 E O1
Adder
1.77764705882352941.511
962561AG1-105 C
Adder
11.6047058823529429.864
939191AE1-149 C
Adder
12.63647058823529410.741
3143316POE
Adder
1.67647058823529421.425
943461AF1-017 C
Adder
1.77764705882352941.511
942342AE2-247 E
Adder
2.71411764705882372.307
936666AD2-085 E
Adder
7.397647058823536.288
932596AC2-079 E
Adder
12.38941176470588310.531
316311AC2-079 C
Adder
7.5929411764705886.454
941591AE2-156 C
50/50
24.9124.91
316316AC1-027 C
50/50
0.4430.443
944601AF1-125 C
50/50
63.13463.134
944591AF1-124 C
50/50
64.34964.349
316018AA1-139 ULT2
50/50
1.5241.524
919152AA1-139 E1
50/50
5.7585.758
938532AE1-072 E
50/50
12.89612.896
3146326AYDLETT TAP
50/50
1.9081.908
917122Z2-027 E
Adder
1.88117647058823521.599
901082W1-029 E
Adder
44.4776470588235337.806
938771AE1-103 C
Adder
4.0211764705882363.418
3145413WATKINS
Adder
0.94941176470588240.807
920692AA2-178 E
Adder
5.74.845
920042AA2-088 E OP
Adder
14.57411764705882412.388
934511AD1-075 C
Adder
11.6423529411764739.896
934521AD1-076 C
Adder
16.9129411764705914.376
960081AF2-299 C
Adder
2.58705882352941162.199
966622AG1-532 E
Adder
1.29294117647058831.099
3145723EMPORIA
Adder
0.59647058823529410.507
926072AC1-086 E
Adder
13.15411764705882411.181
923573AB1-173 E OP
Adder
4.5223529411764713.844
919692AA2-053 E OP
Adder
5.797647058823534.928
944011AF1-069 C
50/50
22.35322.353
926206AC1-098 E
Adder
4.9670588235294124.222
3152441Z1-086 ST
50/50
31.00631.006
963041AG1-153 C
50/50
9.3799.379
3151021BRUNSWICKG1
50/50
13.84413.844
3151041BRUNSWICKG3
50/50
13.84413.844
925785AC1-054 E
Adder
4.65176470588235353.954
922923AB1-081 E OP
Adder
4.9882352941176474.24
316263AC1-034 C
Adder
8.8847058823529417.552
959311AF2-222 C
Adder
20.9952941176470617.846
936261AD2-033 C
Adder
15.9952941176470613.596
962562AG1-105 E
Adder
7.7364705882352946.576
964791AG1-342 C
Adder
4.6105882352941173.919
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.99436.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.67827.678
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.7584.758
LAGNLTFEXP_LAGN->PJM
CLTF
9.6549.654
NYPJM->LTFIMP_NY
CLTF
2.22.2
LGEELTFEXP_LGEE->PJM
CLTF
1.4681.468
WECLTFEXP_WEC->PJM
CLTF
0.7690.769
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.3487.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
126.03126.03
CPLELTFEXP_CPLE->PJM
CLTF
15.41515.415
TVALTFEXP_TVA->PJM
CLTF
7.567.56
O66PJM->LTFIMP_O-066
CMTX_NF
30.16830.168
G-007PJM->LTFIMP_G-007
CMTX_NF
4.7394.739
SIGELTFEXP_SIGE->PJM
CLTF
0.2910.291

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T567_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T567_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.4 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4073.91
MW Contribution:232.75
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150921YORKTN3
Adder
148.4764705882353126.205
934576AD1-082 E
Adder
5.5282352941176474.699
316084AB2-161 E
Adder
6.937647058823535.897
3145256KINGFORK
Adder
1.49058823529411751.267
3151101ELIZAR3
50/50
5.0455.045
3151081ELIZAR1
50/50
4.9824.982
3151091ELIZAR2
50/50
4.8954.895
925522AC1-027 E
50/50
1.9061.906
916191Z1-068 C
50/50
0.0690.069
933292AC2-141 E
50/50
21.46921.469
942341AE2-247 C
Adder
2.09411764705882361.78
316349AD2-085 C
Adder
4.8305882352941174.106
943462AF1-017 E
Adder
3.09058823529411742.627
935112AD1-144 E
Adder
1.3835294117647061.176
932046AC2-012 E
50/50
20.31420.314
944582AF1-123 E
50/50
164.574164.574
944592AF1-124 E
50/50
165.171165.171
958161AF2-110 C
Adder
2.0517647058823531.744
958162AF2-110 E
Adder
3.2635294117647062.774
316388AE2-253 GEN
50/50
3.0993.099
316017AA1-139 ULT1
50/50
1.7031.703
919153AA1-139 E2
50/50
6.4346.434
938531AE1-072 C
50/50
27.61527.615
913392Y1-086 E
Adder
3.42705882352941152.913
923832AB2-022 E
Adder
1.93411764705882351.644
938772AE1-103 E
Adder
6.0094117647058825.108
916042Z1-036 E
Adder
43.71058823529412537.154
3145393UNCAMP
Adder
9.017647058823537.665
939411AE1-173 C
50/50
160.299160.299
934512AD1-075 E
Adder
6.422352941176475.459
934502AD1-074 E
Adder
25.6882352941176521.835
933981AD1-022 C
Adder
13.06588235294117711.106
924516AB2-100 E1
Adder
4.1635294117647063.539
900672V4-068 E
Adder
0.52235294117647060.444
918512AA1-065 E OP
Adder
8.1494117647058816.927
940642AE2-051 E
50/50
21.07921.079
960082AF2-299 E
Adder
1.78117647058823541.514
966621AG1-532 C
Adder
2.00352941176470621.703
946281AF1-292 C
Adder
2.21058823529411751.879
926071AC1-086 C
Adder
30.1129411764705925.596
3137643SOCKMAN
Adder
1.02117647058823540.868
3152411Z1-086 GT1
50/50
18.63118.631
3151031BRUNSWICKG2
50/50
14.47314.473
963042AG1-153 E
50/50
14.70814.708
918532AA1-067 E
Adder
1.02588235294117650.872
919710AA2-057 E
Adder
5.6082352941176474.767
927021AC1-189 C
Adder
11.97411764705882410.178
964241AG1-285 C
Adder
17.77647058823529515.11
924022AB2-043 E O1
Adder
7.0847058823529416.022
924152AB2-059 E OP
Adder
7.3811764705882366.274
3147223TWITTYS
Adder
1.241.054
959312AF2-222 E
Adder
14.30117647058823712.156
924302AB2-077 E O1
Adder
1.82588235294117651.552
962561AG1-105 C
Adder
11.92235294117647210.134
3143316POE
Adder
1.61411764705882371.372
3152331SURRY 2
50/50
39.09539.095
943461AF1-017 C
Adder
1.89411764705882371.61
942342AE2-247 E
Adder
2.89058823529411772.457
936666AD2-085 E
Adder
7.8811764705882356.699
932596AC2-079 E
Adder
13.2447058823529411.258
316311AC2-079 C
Adder
8.117647058823536.9
941591AE2-156 C
50/50
27.78727.787
316316AC1-027 C
50/50
0.4950.495
944601AF1-125 C
50/50
70.76370.763
944591AF1-124 C
50/50
72.12672.126
316018AA1-139 ULT2
50/50
1.7031.703
919152AA1-139 E1
50/50
6.4346.434
938532AE1-072 E
50/50
14.39614.396
3146326AYDLETT TAP
50/50
2.1292.129
917122Z2-027 E
Adder
2.08705882352941161.774
901082W1-029 E
Adder
49.1811764705882441.804
938771AE1-103 C
Adder
4.3517647058823533.699
3145413WATKINS
Adder
1.02235294117647070.869
920692AA2-178 E
Adder
6.2129411764705885.281
920042AA2-088 E OP
Adder
15.5623529411764713.228
934511AD1-075 C
Adder
12.6152941176470610.723
934521AD1-076 C
Adder
18.32705882352941315.578
960081AF2-299 C
Adder
2.6705882352941182.27
966622AG1-532 E
Adder
1.3352941176470591.135
3145723EMPORIA
Adder
0.61647058823529410.524
926072AC1-086 E
Adder
13.70588235294117811.65
923573AB1-173 E OP
Adder
4.6976470588235293.993
919692AA2-053 E OP
Adder
6.08588235294117655.173
944011AF1-069 C
50/50
23.40523.405
926206AC1-098 E
Adder
5.2270588235294114.443
3152441Z1-086 ST
50/50
32.43132.431
963041AG1-153 C
50/50
9.8059.805
3151021BRUNSWICKG1
50/50
14.47314.473
3151041BRUNSWICKG3
50/50
14.47314.473
925785AC1-054 E
Adder
4.8317647058823534.107
922923AB1-081 E OP
Adder
5.2094117647058834.428
316263AC1-034 C
Adder
9.287.888
959311AF2-222 C
Adder
21.34470588235294418.143
936261AD2-033 C
Adder
5.8058823529411764.935
962562AG1-105 E
Adder
7.9482352941176486.756
964791AG1-342 C
Adder
4.737647058823534.027
961611AG1-000B C
Adder
18.65882352941176615.86
939312AE1-162 E
Adder
1.93058823529411771.641
316375AC2-012 C
50/50
2.0942.094
926662AC1-147 E
Adder
2.05411764705882361.746
3150991CHESPKB
50/50
1.121.12
916192Z1-068 E
50/50
2.9452.945
316185AD1-033 C
50/50
1.9451.945
934065AD1-033 E
50/50
7.9347.934
944581AF1-123 C
50/50
71.8771.87
941101AE2-104 C
Adder
5.0270588235294114.273
957492AF2-043 E
Adder
2.18823529411764731.86
937226AE2-253 E
50/50
9.2149.214
923852AB2-025 E
Adder
1.6847058823529411.432
940541AE2-040 C
Adder
4.16470588235294153.54
940482AE2-033 E
Adder
15.81058823529411813.439
940481AE2-033 C
Adder
23.45176470588235419.934
939412AE1-173 E
50/50
106.866106.866
934501AD1-074 C
Adder
50.4623529411764742.893
924517AB2-100 E2
Adder
4.1635294117647063.539
316141AB2-099 E
Adder
0.36941176470588240.314
961941AG1-037 C
Adder
0.740.629
961942AG1-037 E
Adder
0.49294117647058820.419
316088AB2-174 E
Adder
9.3282352941176477.929
923263AB1-132 E OP
Adder
8.7635294117647067.449
923994AB2-040_E
Adder
8.8082352941176477.487
941032AE2-094 E
50/50
32.08232.082
941031AE2-094 C
50/50
71.63171.631
934321AD1-056 C
Adder
8.844705882352947.518
934332AD1-057 E
Adder
2.56941176470588272.184
934322AD1-056 E
Adder
4.797647058823534.078
934331AD1-057 C
Adder
4.9341176470588244.194
927022AC1-189 E
Adder
5.9647058823529415.07
957481AF2-042 C
Adder
82.8776470588235370.446
957482AF2-042 E
Adder
55.2517647058823546.964
961672AG1-007 E
Adder
0.7517647058823530.639
961671AG1-007 C
Adder
1.32588235294117651.127
934621AD1-088 C
Adder
13.7211.662
925595AC1-034 E
Adder
7.0011764705882355.951
925612AC1-036 E
Adder
1.11882352941176480.951
924322AB2-079 E O1
Adder
1.82588235294117651.552
924312AB2-078 E O1
Adder
1.82588235294117651.552
935172AD1-152 E
Adder
7.8611764705882366.682
926274AC1-105 E
Adder
3.5647058823529413.03
943902AF1-058 E
Adder
1.70235294117647061.447
926755AC1-161 E
50/50
21.46921.469
316294AC1-161 C
50/50
8.2198.219
933291AC2-141 C
50/50
50.29350.293
944602AF1-125 E
50/50
161.991161.991
941102AE2-104 E
Adder
7.99294117647058756.794
3145506HICKORY
50/50
3.4483.448
943612AF1-032 E
Adder
1.42235294117647081.209
957871AF2-081 C
50/50
15.73315.733
957872AF2-081 E
50/50
6.7436.743
940492AE2-034 E
Adder
4.663.961
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
934522AD1-076 E
Adder
9.3411764705882367.94
933982AD1-022 E
Adder
7.11294117647058856.046
940641AE2-051 C
50/50
31.61831.618
943172AE2-346 E
Adder
0.88823529411764710.755
946282AF1-292 E
Adder
1.47411764705882351.253
918492AA1-063AE OP
Adder
5.9070588235294125.021
917332KELFORD E
Adder
2.39058823529411772.032
925122AB2-169 E
Adder
8.4411764705882367.175
944012AF1-069 E
50/50
9.0929.092
932632AC2-084 E
Adder
4.623.927
926214AC1-099 E
Adder
1.72705882352941181.468
3152431Z1-086 GT3
50/50
18.62518.625
3152421Z1-086 GT2
50/50
18.62518.625
316274AC1-208 C
Adder
12.85294117647058910.925
927146AC1-208 E
Adder
5.7070588235294124.851
3151051BRUNSWICKS1
50/50
30.06830.068
917512Z2-088 E OP1
Adder
6.9388235294117645.898
917342Z2-044 E
Adder
0.84117647058823530.715
934622AD1-088 E
Adder
6.6058823529411775.615
964242AG1-285 E
Adder
11.85176470588235310.074
937482AD2-202 E
Adder
1.56941176470588251.334
934612AD1-087 E
Adder
5.3611764705882364.557
3151311EDGECMA
Adder
21.6952941176470618.441
924162AB2-060 E OP
Adder
5.8058823529411764.935
964792AG1-342 E
Adder
3.1588235294117652.685
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.34332.343
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.24226.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.3444.344
LAGNLTFEXP_LAGN->PJM
CLTF
9.3599.359
NYPJM->LTFIMP_NY
CLTF
2.0052.005
LGEELTFEXP_LGEE->PJM
CLTF
1.2871.287
WECLTFEXP_WEC->PJM
CLTF
0.6770.677
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.5637.563
CBM South 2LTFEXP_CBM-S2->PJM
CBM
128.067128.067
CPLELTFEXP_CPLE->PJM
CLTF
15.87115.871
TVALTFEXP_TVA->PJM
CLTF
7.2977.297
O66PJM->LTFIMP_O-066
CMTX_NF
27.12727.127
G-007PJM->LTFIMP_G-007
CMTX_NF
4.2584.258
SIGELTFEXP_SIGE->PJM
CLTF
0.2610.261

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.99 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4294.13
MW Contribution:234.92
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150731STONECA
Adder
10.1976470588235298.668
3150651CHESTF6
Adder
27.96823529411764823.773
946262AF1-291 E
Adder
2.17647058823529441.85
938552AE1-074 E
50/50
2.1052.105
3150921YORKTN3
Adder
175.7670588235294149.402
934576AD1-082 E
Adder
6.9458823529411775.904
316084AB2-161 E
Adder
8.717647058823537.41
3145256KINGFORK
Adder
1.5952941176470591.356
3151101ELIZAR3
50/50
5.1725.172
3151081ELIZAR1
50/50
5.1085.108
3151091ELIZAR2
50/50
5.0195.019
925522AC1-027 E
50/50
1.9431.943
916191Z1-068 C
50/50
0.070.07
933292AC2-141 E
50/50
20.7620.76
926755AC1-161 E
50/50
20.7620.76
316294AC1-161 C
50/50
7.9477.947
933291AC2-141 C
50/50
48.63248.632
944602AF1-125 E
50/50
163.5163.5
941102AE2-104 E
Adder
8.4494117647058827.182
3145506HICKORY
50/50
3.4833.483
943612AF1-032 E
Adder
1.4682352941176471.248
957871AF2-081 C
Adder
15.93294117647058713.543
957872AF2-081 E
Adder
6.8282352941176485.804
316315AB2-025 C
50/50
0.650.65
940492AE2-034 E
Adder
4.84.08
3145946PLYMOUTH TP
Adder
0.50.425
934522AD1-076 E
Adder
9.6458823529411778.199
933982AD1-022 E
Adder
7.3576470588235296.254
938562AE1-075 E
Adder
1.64117647058823551.395
940641AE2-051 C
50/50
29.19229.192
943172AE2-346 E
Adder
0.92823529411764720.789
946282AF1-292 E
Adder
1.58588235294117651.348
918492AA1-063AE OP
Adder
6.2388235294117655.303
316336AC2-165 C
Adder
14.85411764705882312.626
944012AF1-069 E
50/50
8.3958.395
3152431Z1-086 GT3
50/50
17.32217.322
3152421Z1-086 GT2
50/50
17.32217.322
3151051BRUNSWICKS1
50/50
28.05928.059
934622AD1-088 E
Adder
6.9164705882352945.879
937482AD2-202 E
Adder
1.58941176470588231.351
934612AD1-087 E
Adder
5.42823529411764754.614
3150831SPRUNCA
Adder
14.05529411764705811.947
3150841SPRUNCB
Adder
14.05529411764705811.947
940431AE2-027 C
Adder
19.56823529411764516.633
942001AE2-212 C
Adder
3.34588235294117632.844
942002AE2-212 E
Adder
2.23058823529411751.896
961611AG1-000B C
Adder
24.2858823529411820.643
939192AE1-149 E
Adder
11.2529411764705879.565
939312AE1-162 E
Adder
2.22705882352941181.893
316375AC2-012 C
50/50
2.1542.154
926662AC1-147 E
Adder
2.1117647058823531.795
916192Z1-068 E
50/50
3.0013.001
316185AD1-033 C
50/50
1.9651.965
934065AD1-033 E
50/50
8.0198.019
944581AF1-123 C
50/50
72.53972.539
941101AE2-104 C
Adder
5.3141176470588244.517
957492AF2-043 E
Adder
2.25882352941176471.92
937226AE2-253 E
Adder
9.322352941176477.924
923852AB2-025 E
50/50
1.8511.851
940541AE2-040 C
50/50
4.5764.576
940482AE2-033 E
50/50
17.33217.332
940481AE2-033 C
50/50
25.70925.709
939412AE1-173 E
50/50
100.688100.688
934501AD1-074 C
Adder
52.1070588235294144.291
958502AF2-144 E
Adder
1.89058823529411771.607
923862AB2-026 E
Adder
1.9247058823529411.636
924517AB2-100 E2
Adder
4.4917647058823533.818
316141AB2-099 E
Adder
0.38705882352941180.329
961941AG1-037 C
Adder
0.77294117647058820.657
961942AG1-037 E
Adder
0.51529411764705880.438
316088AB2-174 E
Adder
9.988.483
923263AB1-132 E OP
Adder
9.3023529411764717.907
923994AB2-040_E
Adder
9.4011764705882357.991
941032AE2-094 E
50/50
29.62229.622
941031AE2-094 C
50/50
66.13866.138
957481AF2-042 C
Adder
82.7976470588235370.378
957482AF2-042 E
Adder
55.1988235294117646.919
934621AD1-088 C
Adder
14.36470588235294312.21
940432AE2-027 E
Adder
13.04588235294117711.089
935161AD1-151 C
Adder
24.22470588235294320.591
934012AD1-025 E
Adder
15.07294117647058812.812
942341AE2-247 C
Adder
2.362.006
316349AD2-085 C
Adder
5.4458823529411764.629
943462AF1-017 E
Adder
3.48470588235294132.962
935112AD1-144 E
Adder
1.48117647058823531.259
932046AC2-012 E
50/50
20.89320.893
944582AF1-123 E
50/50
166.107166.107
944592AF1-124 E
50/50
166.709166.709
958161AF2-110 C
Adder
2.16823529411764731.843
958162AF2-110 E
Adder
3.4494117647058822.932
919153AA1-139 E2
Adder
6.5152941176470595.538
938531AE1-072 C
Adder
27.99411764705882523.795
913392Y1-086 E
Adder
3.48941176470588272.966
923832AB2-022 E
Adder
1.96941176470588241.674
938772AE1-103 E
Adder
6.3458823529411775.394
916042Z1-036 E
Adder
44.8811764705882438.149
3145393UNCAMP
Adder
9.5200000000000018.092
939411AE1-173 C
50/50
151.032151.032
934512AD1-075 E
Adder
6.6317647058823535.637
934502AD1-074 E
Adder
26.5247058823529422.546
933981AD1-022 C
Adder
13.5152941176470611.488
924516AB2-100 E1
Adder
4.4917647058823533.818
900672V4-068 E
Adder
0.54941176470588240.467
918512AA1-065 E OP
Adder
0.250588235294117670.213
940642AE2-051 E
50/50
19.46119.461
960082AF2-299 E
Adder
1.91529411764705881.628
966621AG1-532 C
Adder
2.15411764705882371.831
946281AF1-292 C
Adder
2.37764705882352922.021
933502AC2-165 E
Adder
11.189.503
926071AC1-086 C
Adder
31.96588235294117627.171
3137643SOCKMAN
Adder
1.08470588235294120.922
3152411Z1-086 GT1
50/50
17.32817.328
3151031BRUNSWICKG2
50/50
13.50613.506
963042AG1-153 E
50/50
13.72513.725
944641AF1-129 C
Adder
153.60588235294117130.565
316240AF1-291 C
Adder
3.2635294117647062.774
925332AB2-190 E
Adder
12.07529411764705810.264
935162AD1-151 E
Adder
16.1505882352941213.728
316233AE1-074 C
50/50
4.1784.178
927226AC1-216 E
Adder
11.6423529411764739.896
924814AB2-134 E
Adder
19.07058823529411716.21
939191AE1-149 C
Adder
16.88000000000000314.348
3143316POE
50/50
2.1752.175
943461AF1-017 C
Adder
2.1352941176470591.815
942342AE2-247 E
Adder
3.262.771
936666AD2-085 E
Adder
8.8858823529411777.553
932596AC2-079 E
Adder
14.80823529411764712.587
316311AC2-079 C
Adder
9.0764705882352947.715
941591AE2-156 C
50/50
28.55328.553
316316AC1-027 C
50/50
0.5040.504
944601AF1-125 C
50/50
71.42271.422
944591AF1-124 C
50/50
72.79772.797
919152AA1-139 E1
Adder
6.5152941176470595.538
938532AE1-072 E
Adder
14.59294117647058912.404
3146326AYDLETT TAP
Adder
2.161.836
917122Z2-027 E
Adder
2.12941176470588231.81
901082W1-029 E
Adder
50.41764705882352642.855
938771AE1-103 C
Adder
4.5952941176470593.906
3145413WATKINS
Adder
1.07882352941176470.917
920692AA2-178 E
Adder
6.45.44
920042AA2-088 E OP
Adder
16.40941176470588313.948
934511AD1-075 C
Adder
13.02705882352941211.073
934521AD1-076 C
Adder
18.92352941176470816.085
960081AF2-299 C
Adder
2.87294117647058832.442
966622AG1-532 E
Adder
1.43647058823529421.221
3145723EMPORIA
Adder
0.66117647058823540.562
926072AC1-086 E
Adder
14.54823529411764812.366
923573AB1-173 E OP
Adder
5.0141176470588234.262
944011AF1-069 C
50/50
21.6121.61
3152441Z1-086 ST
50/50
30.16230.162
963041AG1-153 C
50/50
9.159.15
3151021BRUNSWICKG1
50/50
13.50613.506
3151041BRUNSWICKG3
50/50
13.50613.506
316303AF2-085
50/50
6.8996.899
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.00241.002
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.98729.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.2215.221
LAGNLTFEXP_LAGN->PJM
CLTF
10.36610.366
NYPJM->LTFIMP_NY
CLTF
2.7212.721
LGEELTFEXP_LGEE->PJM
CLTF
1.6421.642
WECLTFEXP_WEC->PJM
CLTF
0.8540.854
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6737.673
CBM South 2LTFEXP_CBM-S2->PJM
CBM
132.286132.286
CPLELTFEXP_CPLE->PJM
CLTF
16.09616.096
TVALTFEXP_TVA->PJM
CLTF
8.1488.148
O66PJM->LTFIMP_O-066
CMTX_NF
37.46537.465
G-007PJM->LTFIMP_G-007
CMTX_NF
5.8875.887
SIGELTFEXP_SIGE->PJM
CLTF
0.3220.322

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.84 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4130.73
MW Contribution:237.26
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.16 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4734.49
MW Contribution:242.98
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944641AF1-129 C
Adder
134.3435294117647114.192
316240AF1-291 C
Adder
3.0047058823529412.554
925332AB2-190 E
Adder
11.5164705882352939.789
935162AD1-151 E
Adder
15.4776470588235313.156
316233AE1-074 C
50/50
3.8433.843
927226AC1-216 E
Adder
11.2188235294117659.536
924814AB2-134 E
Adder
18.37647058823529315.62
962962AG1-145 E
Adder
2.0305882352941181.726
939191AE1-149 C
Adder
16.1694117647058813.744
3143316POE
Adder
2.0705882352941181.76
943461AF1-017 C
Adder
2.1105882352941181.794
942342AE2-247 E
Adder
3.22235294117647042.739
936666AD2-085 E
Adder
8.7835294117647067.466
932596AC2-079 E
Adder
14.6612.461
316311AC2-079 C
Adder
8.9858823529411777.638
941591AE2-156 C
50/50
28.7728.77
316316AC1-027 C
50/50
0.5090.509
944601AF1-125 C
50/50
72.13372.133
944591AF1-124 C
50/50
73.52173.521
919152AA1-139 E1
Adder
6.57294117647058855.587
938532AE1-072 E
Adder
14.7176470588235312.51
3146326AYDLETT TAP
Adder
2.17764705882352951.851
917122Z2-027 E
Adder
2.1435294117647061.822
901082W1-029 E
Adder
50.6800000000000143.078
938771AE1-103 C
Adder
4.582352941176473.895
3145413WATKINS
Adder
1.07411764705882360.913
920692AA2-178 E
Adder
6.4035294117647065.443
920042AA2-088 E OP
Adder
16.29647058823529413.852
934511AD1-075 C
Adder
13.00823529411764811.057
934521AD1-076 C
Adder
18.8976470588235316.063
960081AF2-299 C
Adder
2.822.397
966622AG1-532 E
Adder
1.41058823529411771.199
3145723EMPORIA
Adder
0.65058823529411770.553
926072AC1-086 E
Adder
14.32823529411764712.179
923573AB1-173 E OP
Adder
4.9341176470588244.194
919692AA2-053 E OP
Adder
6.3423529411764715.391
944011AF1-069 C
50/50
21.50921.509
3152441Z1-086 ST
50/50
29.99829.998
3150731STONECA
Adder
9.5694117647058838.134
940432AE2-027 E
Adder
12.12235294117647110.304
935161AD1-151 C
Adder
23.2152941176470619.733
934012AD1-025 E
Adder
14.52470588235294212.346
942341AE2-247 C
Adder
2.33294117647058831.983
316349AD2-085 C
Adder
5.3835294117647054.576
943462AF1-017 E
Adder
3.44470588235294132.928
935112AD1-144 E
Adder
1.48470588235294131.262
932046AC2-012 E
50/50
21.04921.049
944582AF1-123 E
50/50
167.759167.759
944592AF1-124 E
50/50
168.367168.367
958161AF2-110 C
Adder
2.16941176470588241.844
958162AF2-110 E
Adder
3.45058823529411772.933
316388AE2-253 GEN
50/50
3.1643.164
919153AA1-139 E2
Adder
6.57294117647058855.587
938531AE1-072 C
Adder
28.2329411764705923.998
913392Y1-086 E
Adder
3.51411764705882362.987
923832AB2-022 E
Adder
1.98352941176470581.686
938772AE1-103 E
Adder
6.3270588235294125.378
916042Z1-036 E
Adder
45.0211764705882438.268
3145393UNCAMP
Adder
9.4858823529411778.063
939411AE1-173 C
50/50
151.38151.38
934512AD1-075 E
Adder
6.622352941176475.629
934502AD1-074 E
Adder
26.48705882352941322.514
933981AD1-022 C
Adder
13.48352941176470711.461
924516AB2-100 E1
Adder
4.4035294117647063.743
900672V4-068 E
Adder
0.54588235294117650.464
918512AA1-065 E OP
Adder
8.4305882352941197.166
940642AE2-051 E
50/50
19.46619.466
960082AF2-299 E
Adder
1.88000000000000011.598
966621AG1-532 C
Adder
2.11529411764705881.798
946281AF1-292 C
Adder
2.33411764705882341.984
926071AC1-086 C
Adder
31.48235294117647226.76
3137643SOCKMAN
Adder
1.06823529411764720.908
3152411Z1-086 GT1
50/50
17.23317.233
3151031BRUNSWICKG2
50/50
13.42813.428
963042AG1-153 E
50/50
13.64513.645
964241AG1-285 C
Adder
18.8416.014
946262AF1-291 E
Adder
2.00235294117647071.702
938552AE1-074 E
50/50
1.9361.936
316160AE1-175 E
Adder
1.67529411764705881.424
3150921YORKTN3
Adder
176.88117647058823150.349
934576AD1-082 E
Adder
6.7411764705882365.73
316084AB2-161 E
Adder
8.467.191
3145256KINGFORK
Adder
1.61.36
3151101ELIZAR3
50/50
5.2135.213
3151081ELIZAR1
50/50
5.1485.148
3151091ELIZAR2
50/50
5.0595.059
925522AC1-027 E
50/50
1.961.96
916191Z1-068 C
50/50
0.0710.071
933292AC2-141 E
50/50
21.18321.183
926755AC1-161 E
50/50
21.18321.183
316294AC1-161 C
50/50
8.1098.109
933291AC2-141 C
50/50
49.62549.625
944602AF1-125 E
50/50
165.126165.126
941102AE2-104 E
Adder
8.4505882352941187.183
3145506HICKORY
50/50
3.5173.517
943612AF1-032 E
Adder
1.4764705882352941.255
957871AF2-081 C
Adder
16.07411764705882413.663
957872AF2-081 E
Adder
6.88823529411764755.855
940492AE2-034 E
Adder
4.8023529411764714.082
3145946PLYMOUTH TP
Adder
0.50.425
934522AD1-076 E
Adder
9.6317647058823528.187
933982AD1-022 E
Adder
7.346.239
938562AE1-075 E
Adder
1.53176470588235311.302
940641AE2-051 C
50/50
29.19929.199
943172AE2-346 E
Adder
0.92117647058823540.783
946282AF1-292 E
Adder
1.5564705882352941.323
918492AA1-063AE OP
Adder
6.1705882352941185.245
917332KELFORD E
Adder
2.4741176470588242.103
925122AB2-169 E
Adder
8.6764705882352937.375
944012AF1-069 E
50/50
8.3568.356
3152431Z1-086 GT3
50/50
17.22717.227
3152421Z1-086 GT2
50/50
17.22717.227
3151051BRUNSWICKS1
50/50
27.89627.896
934622AD1-088 E
Adder
6.8105882352941185.789
964242AG1-285 E
Adder
12.5610.676
937482AD2-202 E
Adder
1.5682352941176471.333
934612AD1-087 E
Adder
5.3588235294117644.555
963041AG1-153 C
50/50
9.0979.097
3151021BRUNSWICKG1
50/50
13.42813.428
3151041BRUNSWICKG3
50/50
13.42813.428
3150831SPRUNCA
Adder
12.67882352941176410.777
3150841SPRUNCB
Adder
12.67882352941176410.777
940431AE2-027 C
Adder
18.18352941176470615.456
942001AE2-212 C
Adder
3.1211764705882352.653
942002AE2-212 E
Adder
2.0811764705882351.769
961611AG1-000B C
Adder
23.7620.196
939192AE1-149 E
Adder
10.7800000000000019.163
939312AE1-162 E
Adder
2.21058823529411751.879
316375AC2-012 C
50/50
2.172.17
926662AC1-147 E
Adder
2.12823529411764721.809
916192Z1-068 E
50/50
3.0273.027
316185AD1-033 C
50/50
1.9851.985
934065AD1-033 E
50/50
8.0978.097
944581AF1-123 C
50/50
73.26173.261
941101AE2-104 C
Adder
5.3152941176470594.518
957492AF2-043 E
Adder
2.2717647058823531.931
937226AE2-253 E
50/50
9.4079.407
923852AB2-025 E
Adder
1.80470588235294121.534
940541AE2-040 C
Adder
4.4623529411764713.793
940482AE2-033 E
Adder
16.9129411764705914.376
940481AE2-033 C
Adder
25.0882352941176521.325
939412AE1-173 E
50/50
100.92100.92
934501AD1-074 C
Adder
52.03294117647059444.228
958502AF2-144 E
Adder
1.76470588235294111.5
923862AB2-026 E
Adder
1.7964705882352941.527
924517AB2-100 E2
Adder
4.4035294117647063.743
316141AB2-099 E
Adder
0.38352941176470590.326
961941AG1-037 C
Adder
0.76823529411764710.653
961942AG1-037 E
Adder
0.51176470588235290.435
316088AB2-174 E
Adder
9.8129411764705888.341
923263AB1-132 E OP
Adder
9.162352941176477.788
923994AB2-040_E
Adder
9.2505882352941197.863
941032AE2-094 E
50/50
29.48329.483
941031AE2-094 C
50/50
65.82865.828
957481AF2-042 C
Adder
81.8317647058823669.557
957482AF2-042 E
Adder
54.5552941176470646.372
934621AD1-088 C
Adder
14.14588235294117512.024
316303AF2-085
50/50
6.4766.476
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.34537.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.31928.319
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8474.847
LAGNLTFEXP_LAGN->PJM
CLTF
9.8929.892
NYPJM->LTFIMP_NY
CLTF
2.5392.539
LGEELTFEXP_LGEE->PJM
CLTF
1.4991.499
WECLTFEXP_WEC->PJM
CLTF
0.780.78
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.547.54
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.173129.173
CPLELTFEXP_CPLE->PJM
CLTF
15.81915.819
TVALTFEXP_TVA->PJM
CLTF
7.767.76
O66PJM->LTFIMP_O-066
CMTX_NF
34.77734.777
G-007PJM->LTFIMP_G-007
CMTX_NF
5.4635.463
SIGELTFEXP_SIGE->PJM
CLTF
0.2970.297

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.96 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4056.64
MW Contribution:220.8
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940432AE2-027 E
Adder
11.99411764705882410.195
935161AD1-151 C
Adder
22.3418.989
934012AD1-025 E
Adder
13.92352941176470811.835
942341AE2-247 C
Adder
2.21058823529411751.879
316349AD2-085 C
Adder
5.09882352941176454.334
943462AF1-017 E
Adder
3.2623529411764712.773
935112AD1-144 E
Adder
1.3882352941176471.18
932046AC2-012 E
50/50
19.61519.615
944582AF1-123 E
50/50
156.119156.119
944592AF1-124 E
50/50
156.684156.684
958161AF2-110 C
Adder
2.03529411764705871.73
958162AF2-110 E
Adder
3.2376470588235292.752
919153AA1-139 E2
Adder
6.1235294117647065.205
938531AE1-072 C
Adder
26.31411764705882622.367
913392Y1-086 E
Adder
3.282.788
923832AB2-022 E
Adder
1.8517647058823531.574
938772AE1-103 E
Adder
5.9670588235294125.072
916042Z1-036 E
Adder
42.2247058823529435.891
3145393UNCAMP
Adder
8.9552941176470597.612
939411AE1-173 C
50/50
143.648143.648
934512AD1-075 E
Adder
6.2470588235294125.31
934502AD1-074 E
Adder
24.98705882352941321.239
933981AD1-022 C
Adder
12.73411764705882410.824
924516AB2-100 E1
Adder
4.2411764705882353.605
900672V4-068 E
Adder
0.51764705882352950.44
940642AE2-051 E
50/50
18.57518.575
960082AF2-299 E
Adder
1.81058823529411761.539
966621AG1-532 C
Adder
2.03647058823529431.731
946281AF1-292 C
Adder
2.24823529411764731.911
933502AC2-165 E
Adder
10.5564705882352968.973
926071AC1-086 C
Adder
30.19411764705882525.665
3137643SOCKMAN
Adder
1.02470588235294110.871
3152411Z1-086 GT1
50/50
16.57316.573
3151031BRUNSWICKG2
50/50
12.91612.916
963042AG1-153 E
50/50
13.12513.125
964241AG1-285 C
Adder
12.04352941176470710.237
944641AF1-129 C
Adder
140.53529411764706119.455
316240AF1-291 C
Adder
2.99294117647058842.544
925332AB2-190 E
Adder
11.1200000000000019.452
935162AD1-151 E
Adder
14.89411764705882412.66
316233AE1-074 C
50/50
3.8973.897
927226AC1-216 E
Adder
10.7541176470588239.141
924814AB2-134 E
Adder
17.61647058823529514.974
939191AE1-149 C
Adder
15.69529411764705913.341
3143316POE
50/50
2.0282.028
943461AF1-017 C
Adder
2.01.7
942342AE2-247 E
Adder
3.0517647058823532.594
936666AD2-085 E
Adder
8.327.072
932596AC2-079 E
Adder
13.86941176470588211.789
316311AC2-079 C
Adder
8.5011764705882367.226
941591AE2-156 C
50/50
26.80726.807
316316AC1-027 C
50/50
0.4740.474
944601AF1-125 C
50/50
67.12767.127
944591AF1-124 C
50/50
68.4268.42
919152AA1-139 E1
Adder
6.1235294117647065.205
938532AE1-072 E
Adder
13.7176470588235311.66
3146326AYDLETT TAP
Adder
2.02941176470588271.725
917122Z2-027 E
Adder
2.00235294117647071.702
901082W1-029 E
Adder
47.440.29
938771AE1-103 C
Adder
4.3211764705882353.673
3145413WATKINS
Adder
1.0152941176470590.863
920692AA2-178 E
Adder
6.0258823529411775.122
920042AA2-088 E OP
Adder
15.46470588235294113.145
934511AD1-075 C
Adder
12.27176470588235310.431
934521AD1-076 C
Adder
17.82705882352941315.153
960081AF2-299 C
Adder
2.7152941176470592.308
966622AG1-532 E
Adder
1.35764705882352941.154
3145723EMPORIA
Adder
0.62588235294117660.532
926072AC1-086 E
Adder
13.7423529411764711.681
923573AB1-173 E OP
Adder
4.744.029
944011AF1-069 C
50/50
20.67620.676
3152441Z1-086 ST
50/50
28.84928.849
963041AG1-153 C
50/50
8.758.75
3151021BRUNSWICKG1
50/50
12.91612.916
3151041BRUNSWICKG3
50/50
12.91612.916
3150831SPRUNCA
Adder
12.87647058823529510.945
3150841SPRUNCB
Adder
12.87647058823529510.945
940431AE2-027 C
Adder
17.9905882352941215.292
942001AE2-212 C
Adder
3.08941176470588232.626
942002AE2-212 E
Adder
2.0588235294117651.75
961611AG1-000B C
Adder
22.53529411764706219.155
939192AE1-149 E
Adder
10.4635294117647078.894
939312AE1-162 E
Adder
2.07764705882352941.766
316375AC2-012 C
50/50
2.0222.022
926662AC1-147 E
Adder
1.98235294117647071.685
916192Z1-068 E
50/50
2.8192.819
316185AD1-033 C
50/50
1.8471.847
934065AD1-033 E
50/50
7.5367.536
944581AF1-123 C
50/50
68.17868.178
941101AE2-104 C
Adder
4.9894117647058824.241
957492AF2-043 E
Adder
2.12235294117647081.804
937226AE2-253 E
Adder
8.7623529411764727.448
923852AB2-025 E
50/50
1.7471.747
940541AE2-040 C
50/50
4.3194.319
940482AE2-033 E
50/50
16.3616.36
940481AE2-033 C
50/50
24.26824.268
939412AE1-173 E
50/50
95.76595.765
934501AD1-074 C
Adder
49.0858823529411841.723
958502AF2-144 E
Adder
1.78705882352941181.519
923862AB2-026 E
Adder
1.81882352941176471.546
924517AB2-100 E2
Adder
4.2411764705882353.605
316088AB2-174 E
Adder
9.4352941176470598.02
923263AB1-132 E OP
Adder
8.7870588235294127.469
923994AB2-040_E
Adder
8.8870588235294117.554
3150651CHESTF6
Adder
25.5882352941176521.75
946262AF1-291 E
Adder
1.99529411764705891.696
938552AE1-074 E
50/50
1.9631.963
3150921YORKTN3
Adder
163.19176470588235138.713
934576AD1-082 E
Adder
6.4764705882352945.505
316084AB2-161 E
Adder
8.1282352941176486.909
3145256KINGFORK
Adder
1.49529411764705871.271
3151101ELIZAR3
50/50
4.8574.857
3151081ELIZAR1
50/50
4.7964.796
3151091ELIZAR2
50/50
4.7134.713
925522AC1-027 E
50/50
1.8261.826
916191Z1-068 C
50/50
0.0660.066
933292AC2-141 E
50/50
19.5219.52
926755AC1-161 E
50/50
19.5219.52
316294AC1-161 C
50/50
7.4737.473
933291AC2-141 C
50/50
45.72845.728
944602AF1-125 E
50/50
153.669153.669
941102AE2-104 E
Adder
7.9317647058823536.742
3145506HICKORY
50/50
3.2743.274
943612AF1-032 E
Adder
1.38000000000000011.173
957871AF2-081 C
Adder
14.97647058823529412.73
957872AF2-081 E
Adder
6.4188235294117665.456
316315AB2-025 C
50/50
0.6130.613
940492AE2-034 E
Adder
4.5188235294117653.841
3145946PLYMOUTH TP
Adder
0.47058823529411770.4
934522AD1-076 E
Adder
9.0858823529411777.723
933982AD1-022 E
Adder
6.9329411764705885.893
938562AE1-075 E
Adder
1.55058823529411781.318
940641AE2-051 C
50/50
27.86227.862
946282AF1-292 E
Adder
1.49882352941176471.274
918492AA1-063AE OP
Adder
5.8905882352941185.007
316336AC2-165 C
Adder
14.02588235294117811.922
944012AF1-069 E
50/50
8.0328.032
3152431Z1-086 GT3
50/50
16.56716.567
3152421Z1-086 GT2
50/50
16.56716.567
3151051BRUNSWICKS1
50/50
26.83226.832
934622AD1-088 E
Adder
6.5941176470588245.605
937482AD2-202 E
Adder
1.5152941176470591.288
934612AD1-087 E
Adder
5.17764705882352954.401
941032AE2-094 E
50/50
28.34228.342
941031AE2-094 C
50/50
63.2863.28
957481AF2-042 C
Adder
79.0188235294117667.166
957482AF2-042 E
Adder
52.67882352941176544.777
934621AD1-088 C
Adder
13.69411764705882511.64
316303AF2-085
50/50
6.5326.532
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.98737.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.12228.122
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8684.868
LAGNLTFEXP_LAGN->PJM
CLTF
9.7559.755
NYPJM->LTFIMP_NY
CLTF
2.5532.553
LGEELTFEXP_LGEE->PJM
CLTF
1.5241.524
WECLTFEXP_WEC->PJM
CLTF
0.7920.792
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.2837.283
CBM South 2LTFEXP_CBM-S2->PJM
CBM
125.379125.379
CPLELTFEXP_CPLE->PJM
CLTF
15.2815.28
TVALTFEXP_TVA->PJM
CLTF
7.6637.663
O66PJM->LTFIMP_O-066
CMTX_NF
35.08335.083
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5125.512
SIGELTFEXP_SIGE->PJM
CLTF
0.30.3

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.85 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3279.97
MW Contribution:65.2
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944631AF1-128 C
Adder
48.040.8
3150651CHESTF6
Adder
24.50588235294117520.83
943471AF1-018 C
Adder
7.9588235294117656.765
3150921YORKTN3
Adder
157.0388235294118133.483
316083AB2-161 C
80/20
0.7870.787
316072AD1-144 C
80/20
0.4020.402
3151101ELIZAR3
80/20
4.7154.715
3151081ELIZAR1
80/20
4.6564.656
3150601CHESTF5
Adder
76.7117647058823665.205
944641AF1-129 C
Adder
134.59058823529412114.402
316240AF1-291 C
Adder
2.86941176470588262.439
316233AE1-074 C
80/20
3.7763.776
939191AE1-149 C
80/20
15.16215.162
940551AE2-041 C
Adder
7.9588235294117656.765
3151161SURRY 1
80/20
33.88933.889
3151211GRAVEL5
80/20
3.4433.443
316381AD1-082 C
80/20
1.7951.795
957601AF2-054 C
Adder
2.37764705882352922.021
3152331SURRY 2
80/20
34.47934.479
943461AF1-017 C
80/20
1.9381.938
316311AC2-079 C
80/20
8.2428.242
316036AC1-147 C
80/20
0.5360.536
941591AE2-156 C
80/20
26.02126.021
316316AC1-027 C
80/20
0.460.46
944601AF1-125 C
80/20
65.265.2
944591AF1-124 C
80/20
66.45566.455
316018AA1-139 ULT2
80/20
1.5751.575
3156056W1-029WIND
80/20
1.1231.123
938771AE1-103 C
80/20
4.24.2
934511AD1-075 C
Adder
11.94117647058823610.15
934521AD1-076 C
Adder
17.34705882352941214.745
316365AB2-100 C1
80/20
1.3721.372
960081AF2-299 C
Adder
2.64941176470588242.252
944011AF1-069 C
80/20
20.29620.296
3152441Z1-086 ST
80/20
28.31528.315
963041AG1-153 C
80/20
8.5888.588
3151021BRUNSWICKG1
80/20
12.67612.676
3151041BRUNSWICKG3
80/20
12.67612.676
316263AC1-034 C
Adder
8.8741176470588247.543
959311AF2-222 C
Adder
23.07176470588235519.611
936261AD2-033 C
Adder
17.57529411764705814.939
961791AG1-021 C
Adder
2.35764705882352972.004
964791AG1-342 C
Adder
4.6788235294117653.977
3150851SPRUNCC
80/20
0.2220.222
316169AC1-164 GEN
Adder
44.9588235294117738.215
3150731STONECA
Adder
8.9505882352941187.608
935161AD1-151 C
Adder
21.46588235294117618.246
3151221GRAVEL6
80/20
3.4833.483
3151201GRAVEL4
80/20
3.4873.487
942341AE2-247 C
80/20
2.1432.143
316349AD2-085 C
80/20
4.9434.943
958161AF2-110 C
80/20
1.9761.976
316246AF1-032 C
80/20
0.4130.413
316388AE2-253 GEN
80/20
2.8622.862
316017AA1-139 ULT1
80/20
1.5751.575
938531AE1-072 C
80/20
25.56125.561
3156116Z1-036WIND
80/20
0.9440.944
939411AE1-173 C
80/20
140.502140.502
933981AD1-022 C
Adder
12.39411764705882410.535
316258AE1-075 C
80/20
0.5030.503
316023AB2-100 C2
80/20
1.3721.372
966621AG1-532 C
Adder
1.9870588235294121.689
946281AF1-292 C
Adder
2.19294117647058861.864
926071AC1-086 C
Adder
29.4425.024
3137643SOCKMAN
Adder
1.00.85
3152411Z1-086 GT1
80/20
16.26616.266
3151031BRUNSWICKG2
80/20
12.67612.676
927021AC1-189 C
Adder
11.4094117647058839.698
3151541CLOVER2
80/20
17.7117.71
964241AG1-285 C
Adder
17.89058823529411815.207
937481AD2-202 C
80/20
0.5110.511
962561AG1-105 C
Adder
11.8176470588235310.045
3150831SPRUNCA
80/20
12.34712.347
3150841SPRUNCB
80/20
12.34712.347
3150861SPRUNCD
80/20
0.2220.222
940431AE2-027 C
Adder
17.26588235294117614.676
942001AE2-212 C
80/20
2.9732.973
961611AG1-000B C
Adder
21.72352941176470518.465
316236AE1-162 C
80/20
0.4930.493
3150981CHESPKA
80/20
0.6340.634
316375AC2-012 C
80/20
1.9631.963
3150991CHESPKB
80/20
1.051.05
316185AD1-033 C
80/20
1.7941.794
944581AF1-123 C
80/20
66.2266.22
941101AE2-104 C
80/20
4.8434.843
313526AB2-022 C
80/20
0.5460.546
316320Y1-086 C
80/20
0.3190.319
316321Z2-027 C
80/20
0.5270.527
940541AE2-040 C
80/20
4.2084.208
940481AE2-033 C
80/20
23.64823.648
943741AF1-042 C
Adder
3.01647058823529422.564
934501AD1-074 C
Adder
47.763529411764740.599
962861AG1-135 C
Adder
6.1588235294117655.235
316405AF2-144 C
80/20
0.4280.428
961941AG1-037 C
Adder
0.71058823529411760.604
941031AE2-094 C
80/20
62.11762.117
934321AD1-056 C
Adder
8.5376470588235297.257
934331AD1-057 C
Adder
4.7623529411764714.048
957481AF2-042 C
80/20
77.49977.499
961671AG1-007 C
Adder
1.26588235294117671.076
934621AD1-088 C
80/20
13.42613.426
946301AF1-294 C
Adder
4.8470588235294124.12
958211AF2-115 C
Adder
2.94705882352941152.505
942461AE2-259 C
Adder
12.70588235294117810.8
3151091ELIZAR2
80/20
4.5754.575
916191Z1-068 C
80/20
0.0640.064
316294AC1-161 C
80/20
7.267.26
933291AC2-141 C
80/20
44.42644.426
316305AF2-043 C
80/20
0.5050.505
957871AF2-081 C
80/20
14.54714.547
316315AB2-025 C
80/20
0.5980.598
961951AG1-038 C
Adder
3.3341176470588242.834
936591AD2-074 C
Adder
5.7647058823529424.9
3151151S HAMPT1
80/20
2.1352.135
316313AB2-026 C
80/20
0.5480.548
940641AE2-051 C
80/20
27.30727.307
316336AC2-165 C
Adder
13.69411764705882511.64
3152431Z1-086 GT3
80/20
16.26116.261
3152421Z1-086 GT2
80/20
16.26116.261
316274AC1-208 C
Adder
12.4023529411764710.542
3151051BRUNSWICKS1
80/20
26.33526.335
3151531CLOVER1
80/20
17.87717.877
934611AD1-087 C
80/20
1.761.76
3151311EDGECMA
Adder
20.74352941176470817.632
3138533PONTONDP
Adder
0.87294117647058820.742
316303AF2-085
80/20
6.3826.382
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.6437.64
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.68227.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8064.806
LAGNLTFEXP_LAGN->PJM
CLTF
9.5879.587
NYPJM->LTFIMP_NY
CLTF
2.4692.469
LGEELTFEXP_LGEE->PJM
CLTF
1.5071.507
WECLTFEXP_WEC->PJM
CLTF
0.7840.784
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1347.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.889122.889
CPLELTFEXP_CPLE->PJM
CLTF
14.96614.966
TVALTFEXP_TVA->PJM
CLTF
7.5327.532
SIGELTFEXP_SIGE->PJM
CLTF
0.2960.296

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.49 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3222.37
MW Contribution:245.73
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.18 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3432.65
MW Contribution:246.71
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316160AE1-175 E
Adder
1.12470588235294120.956
3150921YORKTN3
50/50
162.48162.48
934576AD1-082 E
Adder
4.4847058823529413.812
316084AB2-161 E
Adder
5.6282352941176474.784
3145256KINGFORK
50/50
1.5181.518
316072AD1-144 C
50/50
0.4210.421
3151101ELIZAR3
50/50
5.3035.303
3151081ELIZAR1
50/50
5.2375.237
3151091ELIZAR2
50/50
5.1465.146
925522AC1-027 E
50/50
2.0032.003
916191Z1-068 C
50/50
0.0720.072
933292AC2-141 E
50/50
24.4824.48
926755AC1-161 E
50/50
24.4824.48
316294AC1-161 C
50/50
9.3719.371
933291AC2-141 C
50/50
57.34757.347
944602AF1-125 E
50/50
171.025171.025
941102AE2-104 E
50/50
7.8957.895
3145506HICKORY
50/50
3.633.63
943612AF1-032 E
50/50
1.4511.451
316305AF2-043 C
50/50
0.5470.547
957871AF2-081 C
50/50
16.44116.441
957872AF2-081 E
50/50
7.0467.046
940492AE2-034 E
50/50
4.4344.434
3145946PLYMOUTH TP
Adder
0.451764705882352960.384
934522AD1-076 E
Adder
8.667.361
933982AD1-022 E
Adder
6.5129411764705885.536
940641AE2-051 C
50/50
24.20324.203
943172AE2-346 E
Adder
0.76823529411764710.653
946282AF1-292 E
Adder
1.05882352941176470.9
918492AA1-063AE OP
Adder
4.80941176470588254.088
917332KELFORD E
Adder
2.01647058823529421.714
925122AB2-169 E
Adder
7.4694117647058836.349
944012AF1-069 E
50/50
6.346.34
932632AC2-084 E
Adder
3.71882352941176463.161
926214AC1-099 E
Adder
1.38941176470588231.181
316274AC1-208 C
Adder
10.168.636
927146AC1-208 E
Adder
4.5117647058823533.835
917512Z2-088 E OP1
Adder
5.58588235294117654.748
917342Z2-044 E
Adder
0.65529411764705890.557
934622AD1-088 E
Adder
4.70470588235294153.999
964242AG1-285 E
Adder
8.5011764705882367.226
937482AD2-202 E
Adder
1.1129411764705880.946
934612AD1-087 E
Adder
3.80117647058823543.231
3151311EDGECMA
Adder
16.76352941176470814.249
924162AB2-060 E OP
Adder
4.1870588235294123.559
964792AG1-342 E
Adder
2.2623529411764711.923
927255AC1-221 E
Adder
3.5270588235294122.998
932763AC2-100 E
Adder
2.3941176470588242.035
935161AD1-151 C
Adder
9.2600000000000027.871
934012AD1-025 E
Adder
8.837647058823537.512
3144216WINCHST
50/50
0.1770.177
942341AE2-247 C
Adder
1.93764705882352951.647
316349AD2-085 C
Adder
4.4694117647058833.799
943462AF1-017 E
Adder
2.86000000000000032.431
935112AD1-144 E
50/50
1.4091.409
932046AC2-012 E
50/50
21.31821.318
944582AF1-123 E
50/50
173.752173.752
944592AF1-124 E
50/50
174.381174.381
958161AF2-110 C
50/50
2.0262.026
958162AF2-110 E
50/50
3.2233.223
316246AF1-032 C
50/50
0.4470.447
316388AE2-253 GEN
50/50
3.2483.248
316017AA1-139 ULT1
50/50
1.781.78
919153AA1-139 E2
50/50
6.7236.723
938531AE1-072 C
50/50
28.76728.767
913392Y1-086 E
50/50
3.5213.521
923832AB2-022 E
50/50
1.9881.988
938772AE1-103 E
50/50
5.6365.636
916042Z1-036 E
50/50
42.96342.963
3156116Z1-036WIND
50/50
0.9890.989
3145393UNCAMP
Adder
8.367.106
315614AA2-178 C
50/50
2.2542.254
939411AE1-173 C
50/50
132.376132.376
934512AD1-075 E
Adder
5.95411764705882355.061
934502AD1-074 E
Adder
23.81647058823529420.244
933981AD1-022 C
Adder
11.96352941176470710.169
924516AB2-100 E1
Adder
2.92235294117647062.484
900672V4-068 E
Adder
0.452941176470588240.385
918512AA1-065 E OP
Adder
7.1905882352941186.112
940642AE2-051 E
50/50
16.13516.135
960082AF2-299 E
Adder
1.27882352941176471.087
966621AG1-532 C
Adder
1.43882352941176481.223
946281AF1-292 C
Adder
1.58823529411764721.35
926071AC1-086 C
Adder
22.77647058823529519.36
3137643SOCKMAN
Adder
0.77882352941176480.662
963042AG1-153 E
Adder
10.2835294117647068.741
918532AA1-067 E
Adder
0.85764705882352940.729
919710AA2-057 E
Adder
4.43.74
927021AC1-189 C
Adder
9.768.296
964241AG1-285 C
Adder
12.75176470588235310.839
924022AB2-043 E O1
Adder
5.1070588235294124.341
924152AB2-059 E OP
Adder
5.70470588235294154.849
3147223TWITTYS
Adder
0.89647058823529410.762
959312AF2-222 E
Adder
10.3552941176470598.802
924302AB2-077 E O1
Adder
1.3164705882352941.119
962561AG1-105 C
Adder
8.5494117647058847.267
927226AC1-216 E
Adder
6.8258823529411765.802
924814AB2-134 E
Adder
11.1823529411764729.505
962962AG1-145 E
Adder
1.36235294117647051.158
939191AE1-149 C
Adder
8.8411764705882367.515
957832AF2-077 E
Adder
1.38000000000000011.173
3152331SURRY 2
50/50
52.22952.229
943461AF1-017 C
Adder
1.75294117647058821.49
942342AE2-247 E
Adder
2.6752941176470592.274
936666AD2-085 E
Adder
7.2929411764705886.199
932596AC2-079 E
Adder
12.36705882352941210.512
316311AC2-079 C
Adder
7.586.443
316036AC1-147 C
50/50
0.60.6
941591AE2-156 C
50/50
29.1829.18
316316AC1-027 C
50/50
0.520.52
944601AF1-125 C
50/50
74.70974.709
944591AF1-124 C
50/50
76.14876.148
316018AA1-139 ULT2
50/50
1.781.78
919152AA1-139 E1
50/50
6.7236.723
938532AE1-072 E
50/50
14.99614.996
3146326AYDLETT TAP
50/50
2.2162.216
917122Z2-027 E
50/50
2.1312.131
901082W1-029 E
50/50
49.64949.649
3156056W1-029WIND
50/50
1.211.21
938771AE1-103 C
50/50
4.0814.081
3145413WATKINS
Adder
0.93058823529411770.791
920692AA2-178 E
50/50
5.9125.912
920042AA2-088 E OP
Adder
13.60117647058823611.561
934511AD1-075 C
Adder
11.6964705882352959.942
934521AD1-076 C
Adder
16.99176470588235314.443
960081AF2-299 C
Adder
1.91882352941176481.631
966622AG1-532 E
Adder
0.95882352941176460.815
3145723EMPORIA
Adder
0.44705882352941180.38
926072AC1-086 E
Adder
10.3658823529411768.811
923573AB1-173 E OP
Adder
3.50352941176470622.978
919692AA2-053 E OP
Adder
4.8294117647058834.105
944011AF1-069 C
50/50
16.3216.32
926206AC1-098 E
Adder
4.2070588235294123.576
963041AG1-153 C
Adder
6.8564705882352955.828
925785AC1-054 E
Adder
3.63176470588235353.087
922923AB1-081 E OP
Adder
4.0270588235294123.423
316263AC1-034 C
Adder
7.1729411764705896.097
959311AF2-222 C
Adder
15.45647058823529513.138
936261AD2-033 C
Adder
11.82117647058823610.048
962562AG1-105 E
Adder
5.74.845
964791AG1-342 C
Adder
3.39411764705882352.885
961611AG1-000B C
Adder
17.5717647058823514.936
939192AE1-149 E
Adder
5.8941176470588235.01
939312AE1-162 E
50/50
1.9371.937
316236AE1-162 C
50/50
0.4750.475
3150981CHESPKA
50/50
0.7090.709
316375AC2-012 C
50/50
2.1982.198
926662AC1-147 E
50/50
2.1552.155
3150991CHESPKB
50/50
1.1761.176
916192Z1-068 E
50/50
3.0983.098
316185AD1-033 C
50/50
2.0522.052
934065AD1-033 E
50/50
8.3718.371
944581AF1-123 C
50/50
75.87875.878
941101AE2-104 C
50/50
4.9664.966
957492AF2-043 E
50/50
2.2332.233
937226AE2-253 E
50/50
9.6579.657
313526AB2-022 C
50/50
0.6030.603
316320Y1-086 C
50/50
0.3530.353
316321Z2-027 C
50/50
0.5770.577
923852AB2-025 E
Adder
1.06941176470588250.909
940541AE2-040 C
Adder
2.6435294117647062.247
940482AE2-033 E
Adder
10.1729411764705898.647
940481AE2-033 C
Adder
15.09058823529411912.827
940491AE2-034 C
50/50
1.6591.659
939412AE1-173 E
50/50
88.25188.251
934501AD1-074 C
Adder
46.7858823529411839.768
924517AB2-100 E2
Adder
2.92235294117647062.484
316141AB2-099 E
Adder
0.320.272
961941AG1-037 C
Adder
0.640.544
961942AG1-037 E
Adder
0.427058823529411770.363
316088AB2-174 E
Adder
6.877647058823535.846
923263AB1-132 E OP
Adder
6.6282352941176485.634
923994AB2-040_E
Adder
6.5694117647058825.584
941032AE2-094 E
50/50
22.37122.371
941031AE2-094 C
50/50
49.94849.948
934321AD1-056 C
Adder
6.7670588235294115.752
934332AD1-057 E
Adder
1.96588235294117661.671
934322AD1-056 E
Adder
3.6705882352941183.12
934331AD1-057 C
Adder
3.7752941176470593.209
927022AC1-189 E
Adder
4.86235294117647054.133
957481AF2-042 C
Adder
58.59176470588235549.803
957482AF2-042 E
Adder
39.0611764705882433.202
961672AG1-007 E
Adder
0.59882352941176480.509
961671AG1-007 C
Adder
1.05647058823529430.898
934621AD1-088 C
Adder
9.7717647058823538.306
925595AC1-034 E
Adder
5.4105882352941184.599
925612AC1-036 E
Adder
0.80823529411764720.687
924322AB2-079 E O1
Adder
1.3164705882352941.119
924312AB2-078 E O1
Adder
1.3164705882352941.119
936262AD2-033 E
Adder
7.8811764705882356.699
935172AD1-152 E
Adder
5.5847058823529414.747
926274AC1-105 E
Adder
2.5482352941176472.166
943902AF1-058 E
Adder
1.21411764705882351.032
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.74418.744
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.28317.283
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.712.71
LAGNLTFEXP_LAGN->PJM
CLTF
6.3446.344
NYPJM->LTFIMP_NY
CLTF
1.4491.449
LGEELTFEXP_LGEE->PJM
CLTF
0.760.76
WECLTFEXP_WEC->PJM
CLTF
0.3980.398
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.515.51
CBM South 2LTFEXP_CBM-S2->PJM
CBM
91.70491.704
CPLELTFEXP_CPLE->PJM
CLTF
11.56611.566
TVALTFEXP_TVA->PJM
CLTF
4.9264.926
O66PJM->LTFIMP_O-066
CMTX_NF
19.32919.329
G-007PJM->LTFIMP_G-007
CMTX_NF
3.0313.031
SIGELTFEXP_SIGE->PJM
CLTF
0.160.16

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.39 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3219.08
MW Contribution:247.32
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935161AD1-151 C
Adder
13.97176470588235211.876
934012AD1-025 E
Adder
9.3823529411764717.975
3144216WINCHST
50/50
0.180.18
942341AE2-247 C
Adder
2.00470588235294131.704
316349AD2-085 C
Adder
4.6258823529411773.932
943462AF1-017 E
Adder
2.962.516
935112AD1-144 E
50/50
1.4291.429
932046AC2-012 E
50/50
21.49421.494
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
958161AF2-110 C
50/50
2.0612.061
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
316017AA1-139 ULT1
50/50
1.7931.793
919153AA1-139 E2
50/50
6.7746.774
938531AE1-072 C
50/50
28.99428.994
913392Y1-086 E
50/50
3.5543.554
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
3156116Z1-036WIND
50/50
1.0021.002
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
939411AE1-173 C
50/50
131.454131.454
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
933981AD1-022 C
Adder
12.2223529411764710.389
924516AB2-100 E1
Adder
3.19529411764705932.716
900672V4-068 E
Adder
0.46705882352941180.397
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
960082AF2-299 E
Adder
1.37411764705882341.168
966621AG1-532 C
Adder
1.54588235294117651.314
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
3137643SOCKMAN
Adder
0.820.697
963042AG1-153 E
Adder
10.1470588235294118.625
918532AA1-067 E
Adder
0.87882352941176480.747
919710AA2-057 E
Adder
4.5505882352941183.868
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924022AB2-043 E O1
Adder
5.1847058823529414.407
924152AB2-059 E OP
Adder
5.8823529411764715
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
924302AB2-077 E O1
Adder
1.3364705882352941.136
962561AG1-105 C
Adder
8.6352941176470587.34
935162AD1-151 E
Adder
9.3141176470588247.917
927226AC1-216 E
Adder
7.2470588235294126.16
924814AB2-134 E
Adder
11.87058823529411810.09
962962AG1-145 E
Adder
1.40705882352941171.196
939191AE1-149 C
Adder
9.8705882352941188.39
3143316POE
Adder
1.15647058823529410.983
957832AF2-077 E
Adder
1.4235294117647061.21
3152331SURRY 2
50/50
52.46452.464
943461AF1-017 C
Adder
1.81411764705882361.542
942342AE2-247 E
Adder
2.76823529411764732.353
936666AD2-085 E
Adder
7.5470588235294126.415
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
316036AC1-147 C
50/50
0.6050.605
941591AE2-156 C
50/50
29.41729.417
316316AC1-027 C
50/50
0.5240.524
944601AF1-125 C
50/50
75.19275.192
944591AF1-124 C
50/50
76.6476.64
316018AA1-139 ULT2
50/50
1.7931.793
919152AA1-139 E1
50/50
6.7746.774
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
901082W1-029 E
50/50
50.20950.209
3156056W1-029WIND
50/50
1.2241.224
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
920692AA2-178 E
50/50
6.0146.014
920042AA2-088 E OP
Adder
14.01647058823529311.914
934511AD1-075 C
Adder
11.92941176470588310.14
934521AD1-076 C
Adder
17.32941176470588514.73
960081AF2-299 C
Adder
2.061.751
966622AG1-532 E
Adder
1.03058823529411760.876
3145723EMPORIA
Adder
0.47882352941176470.407
926072AC1-086 E
Adder
11.0094117647058839.358
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
944011AF1-069 C
Adder
16.07529411764705813.664
926206AC1-098 E
Adder
4.3541176470588243.701
963041AG1-153 C
Adder
6.7647058823529415.75
925785AC1-054 E
Adder
3.7423529411764713.181
922923AB1-081 E OP
Adder
4.1529411764705883.53
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
936261AD2-033 C
Adder
12.05176470588235410.244
962562AG1-105 E
Adder
5.75647058823529444.893
964791AG1-342 C
Adder
3.42470588235294132.911
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
934576AD1-082 E
Adder
4.8152941176470594.093
316084AB2-161 E
Adder
6.0435294117647055.137
3145256KINGFORK
50/50
1.5391.539
316072AD1-144 C
50/50
0.4270.427
3151101ELIZAR3
50/50
5.3455.345
3151081ELIZAR1
50/50
5.2785.278
3151091ELIZAR2
50/50
5.1875.187
925522AC1-027 E
50/50
2.0192.019
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
926755AC1-161 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
933291AC2-141 C
50/50
57.45157.451
944602AF1-125 E
50/50
172.13172.13
941102AE2-104 E
50/50
8.0328.032
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
316305AF2-043 C
50/50
0.5530.553
957871AF2-081 C
50/50
16.56416.564
957872AF2-081 E
50/50
7.0997.099
940492AE2-034 E
50/50
4.514.51
3145946PLYMOUTH TP
Adder
0.460.391
934522AD1-076 E
Adder
8.832941176470597.508
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
943172AE2-346 E
Adder
0.79058823529411770.672
946282AF1-292 E
Adder
1.13647058823529410.966
918492AA1-063AE OP
Adder
5.04.25
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
944012AF1-069 E
Adder
6.24470588235294165.308
932632AC2-084 E
Adder
3.8494117647058823.272
926214AC1-099 E
Adder
1.43882352941176481.223
316274AC1-208 C
Adder
10.5388235294117658.958
927146AC1-208 E
Adder
4.6800000000000013.978
917512Z2-088 E OP1
Adder
5.7423529411764714.881
917342Z2-044 E
Adder
0.6764705882352940.575
934622AD1-088 E
Adder
4.7082352941176474.002
964242AG1-285 E
Adder
8.5717647058823537.286
937482AD2-202 E
Adder
1.11058823529411770.944
934612AD1-087 E
Adder
3.79294117647058873.224
3151311EDGECMA
Adder
17.2952941176470614.701
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
927255AC1-221 E
Adder
2.40941176470588262.048
961611AG1-000B C
Adder
18.24117647058823615.505
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
316236AE1-162 C
50/50
0.4850.485
3150981CHESPKA
50/50
0.7150.715
316375AC2-012 C
50/50
2.2162.216
926662AC1-147 E
50/50
2.1732.173
3150991CHESPKB
50/50
1.1851.185
916192Z1-068 E
50/50
3.1213.121
316185AD1-033 C
50/50
2.0652.065
934065AD1-033 E
50/50
8.4268.426
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
957492AF2-043 E
50/50
2.2562.256
937226AE2-253 E
50/50
9.7279.727
313526AB2-022 C
50/50
0.6090.609
316320Y1-086 C
50/50
0.3560.356
316321Z2-027 C
50/50
0.5830.583
923852AB2-025 E
Adder
1.22235294117647041.039
940541AE2-040 C
Adder
3.02117647058823562.568
940482AE2-033 E
Adder
11.5564705882352949.823
940481AE2-033 C
Adder
17.1423529411764714.571
940491AE2-034 C
50/50
1.6871.687
939412AE1-173 E
50/50
87.63687.636
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
316141AB2-099 E
Adder
0.32941176470588240.28
961941AG1-037 C
Adder
0.65882352941176480.56
961942AG1-037 E
Adder
0.43882352941176470.373
316088AB2-174 E
Adder
7.3223529411764716.224
923263AB1-132 E OP
Adder
7.045.984
923994AB2-040_E
Adder
6.96705882352941155.922
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934321AD1-056 C
Adder
7.0682352941176476.008
934332AD1-057 E
Adder
2.05294117647058851.745
934322AD1-056 E
Adder
3.83411764705882343.259
934331AD1-057 C
Adder
3.94352941176470573.352
927022AC1-189 E
Adder
4.9929411764705884.244
957481AF2-042 C
Adder
58.3200000000000149.572
957482AF2-042 E
Adder
38.8833.048
961672AG1-007 E
Adder
0.61647058823529410.524
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
925595AC1-034 E
Adder
5.5800000000000014.743
925612AC1-036 E
Adder
0.81882352941176460.696
924322AB2-079 E O1
Adder
1.3364705882352941.136
924312AB2-078 E O1
Adder
1.3364705882352941.136
936262AD2-033 E
Adder
8.0352941176470596.83
935172AD1-152 E
Adder
5.5800000000000014.743
926274AC1-105 E
Adder
2.56470588235294142.18
943902AF1-058 E
Adder
1.21882352941176491.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.39 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3219.08
MW Contribution:247.32
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935161AD1-151 C
Adder
13.97176470588235211.876
934012AD1-025 E
Adder
9.3823529411764717.975
3144216WINCHST
50/50
0.180.18
942341AE2-247 C
Adder
2.00470588235294131.704
316349AD2-085 C
Adder
4.6258823529411773.932
943462AF1-017 E
Adder
2.962.516
935112AD1-144 E
50/50
1.4291.429
932046AC2-012 E
50/50
21.49421.494
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
958161AF2-110 C
50/50
2.0612.061
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
316017AA1-139 ULT1
50/50
1.7931.793
919153AA1-139 E2
50/50
6.7746.774
938531AE1-072 C
50/50
28.99428.994
913392Y1-086 E
50/50
3.5543.554
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
3156116Z1-036WIND
50/50
1.0021.002
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
939411AE1-173 C
50/50
131.454131.454
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
933981AD1-022 C
Adder
12.2223529411764710.389
924516AB2-100 E1
Adder
3.19529411764705932.716
900672V4-068 E
Adder
0.46705882352941180.397
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
960082AF2-299 E
Adder
1.37411764705882341.168
966621AG1-532 C
Adder
1.54588235294117651.314
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
3137643SOCKMAN
Adder
0.820.697
963042AG1-153 E
Adder
10.1470588235294118.625
918532AA1-067 E
Adder
0.87882352941176480.747
919710AA2-057 E
Adder
4.5505882352941183.868
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924022AB2-043 E O1
Adder
5.1847058823529414.407
924152AB2-059 E OP
Adder
5.8823529411764715
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
924302AB2-077 E O1
Adder
1.3364705882352941.136
962561AG1-105 C
Adder
8.6352941176470587.34
935162AD1-151 E
Adder
9.3141176470588247.917
927226AC1-216 E
Adder
7.2470588235294126.16
924814AB2-134 E
Adder
11.87058823529411810.09
962962AG1-145 E
Adder
1.40705882352941171.196
939191AE1-149 C
Adder
9.8705882352941188.39
3143316POE
Adder
1.15647058823529410.983
957832AF2-077 E
Adder
1.4235294117647061.21
3152331SURRY 2
50/50
52.46452.464
943461AF1-017 C
Adder
1.81411764705882361.542
942342AE2-247 E
Adder
2.76823529411764732.353
936666AD2-085 E
Adder
7.5470588235294126.415
932596AC2-079 E
Adder
12.76823529411764610.853
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
934576AD1-082 E
Adder
4.8152941176470594.093
316084AB2-161 E
Adder
6.0435294117647055.137
3145256KINGFORK
50/50
1.5391.539
316072AD1-144 C
50/50
0.4270.427
3151101ELIZAR3
50/50
5.3455.345
3151081ELIZAR1
50/50
5.2785.278
3151091ELIZAR2
50/50
5.1875.187
925522AC1-027 E
50/50
2.0192.019
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
926755AC1-161 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
933291AC2-141 C
50/50
57.45157.451
944602AF1-125 E
50/50
172.13172.13
941102AE2-104 E
50/50
8.0328.032
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
316305AF2-043 C
50/50
0.5530.553
957871AF2-081 C
50/50
16.56416.564
957872AF2-081 E
50/50
7.0997.099
940492AE2-034 E
50/50
4.514.51
3145946PLYMOUTH TP
Adder
0.460.391
934522AD1-076 E
Adder
8.832941176470597.508
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
943172AE2-346 E
Adder
0.79058823529411770.672
946282AF1-292 E
Adder
1.13647058823529410.966
918492AA1-063AE OP
Adder
5.04.25
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
944012AF1-069 E
Adder
6.24470588235294165.308
932632AC2-084 E
Adder
3.8494117647058823.272
926214AC1-099 E
Adder
1.43882352941176481.223
316274AC1-208 C
Adder
10.5388235294117658.958
927146AC1-208 E
Adder
4.6800000000000013.978
917512Z2-088 E OP1
Adder
5.7423529411764714.881
917342Z2-044 E
Adder
0.6764705882352940.575
934622AD1-088 E
Adder
4.7082352941176474.002
964242AG1-285 E
Adder
8.5717647058823537.286
937482AD2-202 E
Adder
1.11058823529411770.944
934612AD1-087 E
Adder
3.79294117647058873.224
3151311EDGECMA
Adder
17.2952941176470614.701
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
927255AC1-221 E
Adder
2.40941176470588262.048
961611AG1-000B C
Adder
18.24117647058823615.505
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
316236AE1-162 C
50/50
0.4850.485
3150981CHESPKA
50/50
0.7150.715
316375AC2-012 C
50/50
2.2162.216
926662AC1-147 E
50/50
2.1732.173
3150991CHESPKB
50/50
1.1851.185
916192Z1-068 E
50/50
3.1213.121
316185AD1-033 C
50/50
2.0652.065
934065AD1-033 E
50/50
8.4268.426
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
957492AF2-043 E
50/50
2.2562.256
937226AE2-253 E
50/50
9.7279.727
313526AB2-022 C
50/50
0.6090.609
316320Y1-086 C
50/50
0.3560.356
316321Z2-027 C
50/50
0.5830.583
923852AB2-025 E
Adder
1.22235294117647041.039
940541AE2-040 C
Adder
3.02117647058823562.568
940482AE2-033 E
Adder
11.5564705882352949.823
940481AE2-033 C
Adder
17.1423529411764714.571
940491AE2-034 C
50/50
1.6871.687
939412AE1-173 E
50/50
87.63687.636
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
316141AB2-099 E
Adder
0.32941176470588240.28
961941AG1-037 C
Adder
0.65882352941176480.56
961942AG1-037 E
Adder
0.43882352941176470.373
316088AB2-174 E
Adder
7.3223529411764716.224
923263AB1-132 E OP
Adder
7.045.984
923994AB2-040_E
Adder
6.96705882352941155.922
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934321AD1-056 C
Adder
7.0682352941176476.008
934332AD1-057 E
Adder
2.05294117647058851.745
934322AD1-056 E
Adder
3.83411764705882343.259
934331AD1-057 C
Adder
3.94352941176470573.352
927022AC1-189 E
Adder
4.9929411764705884.244
957481AF2-042 C
Adder
58.3200000000000149.572
957482AF2-042 E
Adder
38.8833.048
961672AG1-007 E
Adder
0.61647058823529410.524
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
925595AC1-034 E
Adder
5.5800000000000014.743
925612AC1-036 E
Adder
0.81882352941176460.696
924322AB2-079 E O1
Adder
1.3364705882352941.136
924312AB2-078 E O1
Adder
1.3364705882352941.136
936262AD2-033 E
Adder
8.0352941176470596.83
935172AD1-152 E
Adder
5.5800000000000014.743
926274AC1-105 E
Adder
2.56470588235294142.18
943902AF1-058 E
Adder
1.21882352941176491.036
316311AC2-079 C
Adder
7.8258823529411776.652
316036AC1-147 C
50/50
0.6050.605
941591AE2-156 C
50/50
29.41729.417
316316AC1-027 C
50/50
0.5240.524
944601AF1-125 C
50/50
75.19275.192
944591AF1-124 C
50/50
76.6476.64
316018AA1-139 ULT2
50/50
1.7931.793
919152AA1-139 E1
50/50
6.7746.774
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
901082W1-029 E
50/50
50.20950.209
3156056W1-029WIND
50/50
1.2241.224
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
920692AA2-178 E
50/50
6.0146.014
920042AA2-088 E OP
Adder
14.01647058823529311.914
934511AD1-075 C
Adder
11.92941176470588310.14
934521AD1-076 C
Adder
17.32941176470588514.73
960081AF2-299 C
Adder
2.061.751
966622AG1-532 E
Adder
1.03058823529411760.876
3145723EMPORIA
Adder
0.47882352941176470.407
926072AC1-086 E
Adder
11.0094117647058839.358
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
944011AF1-069 C
Adder
16.07529411764705813.664
926206AC1-098 E
Adder
4.3541176470588243.701
963041AG1-153 C
Adder
6.7647058823529415.75
925785AC1-054 E
Adder
3.7423529411764713.181
922923AB1-081 E OP
Adder
4.1529411764705883.53
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
936261AD2-033 C
Adder
12.05176470588235410.244
962562AG1-105 E
Adder
5.75647058823529444.893
964791AG1-342 C
Adder
3.42470588235294132.911
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.38 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3218.92
MW Contribution:247.32
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.16 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3432.06
MW Contribution:249.01
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
934576AD1-082 E
Adder
4.8152941176470594.093
316084AB2-161 E
Adder
6.0435294117647055.137
3145256KINGFORK
50/50
1.5391.539
316072AD1-144 C
50/50
0.4270.427
3151101ELIZAR3
50/50
5.3455.345
3151081ELIZAR1
50/50
5.2785.278
3151091ELIZAR2
50/50
5.1875.187
925522AC1-027 E
50/50
2.0192.019
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
926755AC1-161 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
933291AC2-141 C
50/50
57.45157.451
944602AF1-125 E
50/50
172.13172.13
941102AE2-104 E
50/50
8.0328.032
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
316305AF2-043 C
50/50
0.5530.553
957871AF2-081 C
50/50
16.56416.564
957872AF2-081 E
50/50
7.0997.099
940492AE2-034 E
50/50
4.514.51
3145946PLYMOUTH TP
Adder
0.460.391
934522AD1-076 E
Adder
8.832941176470597.508
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
943172AE2-346 E
Adder
0.79058823529411770.672
946282AF1-292 E
Adder
1.13647058823529410.966
918492AA1-063AE OP
Adder
5.04.25
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
944012AF1-069 E
Adder
6.24470588235294165.308
932632AC2-084 E
Adder
3.8494117647058823.272
926214AC1-099 E
Adder
1.43882352941176481.223
316274AC1-208 C
Adder
10.5388235294117658.958
927146AC1-208 E
Adder
4.6800000000000013.978
917512Z2-088 E OP1
Adder
5.7423529411764714.881
917342Z2-044 E
Adder
0.6764705882352940.575
934622AD1-088 E
Adder
4.7082352941176474.002
964242AG1-285 E
Adder
8.5717647058823537.286
937482AD2-202 E
Adder
1.11058823529411770.944
934612AD1-087 E
Adder
3.79294117647058873.224
3151311EDGECMA
Adder
17.2952941176470614.701
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
927255AC1-221 E
Adder
2.40941176470588262.048
935161AD1-151 C
Adder
13.97176470588235211.876
934012AD1-025 E
Adder
9.3823529411764717.975
3144216WINCHST
50/50
0.180.18
942341AE2-247 C
Adder
2.00470588235294131.704
316349AD2-085 C
Adder
4.6258823529411773.932
943462AF1-017 E
Adder
2.962.516
935112AD1-144 E
50/50
1.4291.429
932046AC2-012 E
50/50
21.49421.494
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
958161AF2-110 C
50/50
2.0612.061
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
316017AA1-139 ULT1
50/50
1.7931.793
919153AA1-139 E2
50/50
6.7746.774
938531AE1-072 C
50/50
28.99428.994
913392Y1-086 E
50/50
3.5543.554
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
3156116Z1-036WIND
50/50
1.0021.002
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
939411AE1-173 C
50/50
131.454131.454
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
933981AD1-022 C
Adder
12.2223529411764710.389
924516AB2-100 E1
Adder
3.19529411764705932.716
900672V4-068 E
Adder
0.46705882352941180.397
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
960082AF2-299 E
Adder
1.37411764705882341.168
966621AG1-532 C
Adder
1.54588235294117651.314
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
3137643SOCKMAN
Adder
0.820.697
963042AG1-153 E
Adder
10.1470588235294118.625
918532AA1-067 E
Adder
0.87882352941176480.747
919710AA2-057 E
Adder
4.5505882352941183.868
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924022AB2-043 E O1
Adder
5.1847058823529414.407
924152AB2-059 E OP
Adder
5.8823529411764715
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
924302AB2-077 E O1
Adder
1.3364705882352941.136
962561AG1-105 C
Adder
8.6352941176470587.34
935162AD1-151 E
Adder
9.3141176470588247.917
927226AC1-216 E
Adder
7.2470588235294126.16
924814AB2-134 E
Adder
11.87058823529411810.09
962962AG1-145 E
Adder
1.40705882352941171.196
939191AE1-149 C
Adder
9.8705882352941188.39
3143316POE
Adder
1.15647058823529410.983
957832AF2-077 E
Adder
1.4235294117647061.21
3152331SURRY 2
50/50
52.46452.464
943461AF1-017 C
Adder
1.81411764705882361.542
942342AE2-247 E
Adder
2.76823529411764732.353
936666AD2-085 E
Adder
7.5470588235294126.415
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
316036AC1-147 C
50/50
0.6050.605
941591AE2-156 C
50/50
29.41729.417
316316AC1-027 C
50/50
0.5240.524
944601AF1-125 C
50/50
75.19275.192
944591AF1-124 C
50/50
76.6476.64
316018AA1-139 ULT2
50/50
1.7931.793
919152AA1-139 E1
50/50
6.7746.774
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
901082W1-029 E
50/50
50.20950.209
3156056W1-029WIND
50/50
1.2241.224
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
920692AA2-178 E
50/50
6.0146.014
920042AA2-088 E OP
Adder
14.01647058823529311.914
934511AD1-075 C
Adder
11.92941176470588310.14
934521AD1-076 C
Adder
17.32941176470588514.73
960081AF2-299 C
Adder
2.061.751
966622AG1-532 E
Adder
1.03058823529411760.876
3145723EMPORIA
Adder
0.47882352941176470.407
926072AC1-086 E
Adder
11.0094117647058839.358
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
944011AF1-069 C
Adder
16.07529411764705813.664
926206AC1-098 E
Adder
4.3541176470588243.701
963041AG1-153 C
Adder
6.7647058823529415.75
925785AC1-054 E
Adder
3.7423529411764713.181
922923AB1-081 E OP
Adder
4.1529411764705883.53
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
936261AD2-033 C
Adder
12.05176470588235410.244
962562AG1-105 E
Adder
5.75647058823529444.893
964791AG1-342 C
Adder
3.42470588235294132.911
961611AG1-000B C
Adder
18.24117647058823615.505
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
316236AE1-162 C
50/50
0.4850.485
3150981CHESPKA
50/50
0.7150.715
316375AC2-012 C
50/50
2.2162.216
926662AC1-147 E
50/50
2.1732.173
3150991CHESPKB
50/50
1.1851.185
916192Z1-068 E
50/50
3.1213.121
316185AD1-033 C
50/50
2.0652.065
934065AD1-033 E
50/50
8.4268.426
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
957492AF2-043 E
50/50
2.2562.256
937226AE2-253 E
50/50
9.7279.727
313526AB2-022 C
50/50
0.6090.609
316320Y1-086 C
50/50
0.3560.356
316321Z2-027 C
50/50
0.5830.583
923852AB2-025 E
Adder
1.22235294117647041.039
940541AE2-040 C
Adder
3.02117647058823562.568
940482AE2-033 E
Adder
11.5564705882352949.823
940481AE2-033 C
Adder
17.1423529411764714.571
940491AE2-034 C
50/50
1.6871.687
939412AE1-173 E
50/50
87.63687.636
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
316141AB2-099 E
Adder
0.32941176470588240.28
961941AG1-037 C
Adder
0.65882352941176480.56
961942AG1-037 E
Adder
0.43882352941176470.373
316088AB2-174 E
Adder
7.3223529411764716.224
923263AB1-132 E OP
Adder
7.045.984
923994AB2-040_E
Adder
6.96705882352941155.922
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934321AD1-056 C
Adder
7.0682352941176476.008
934332AD1-057 E
Adder
2.05294117647058851.745
934322AD1-056 E
Adder
3.83411764705882343.259
934331AD1-057 C
Adder
3.94352941176470573.352
927022AC1-189 E
Adder
4.9929411764705884.244
957481AF2-042 C
Adder
58.3200000000000149.572
957482AF2-042 E
Adder
38.8833.048
961672AG1-007 E
Adder
0.61647058823529410.524
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
925595AC1-034 E
Adder
5.5800000000000014.743
925612AC1-036 E
Adder
0.81882352941176460.696
924322AB2-079 E O1
Adder
1.3364705882352941.136
924312AB2-078 E O1
Adder
1.3364705882352941.136
936262AD2-033 E
Adder
8.0352941176470596.83
935172AD1-152 E
Adder
5.5800000000000014.743
926274AC1-105 E
Adder
2.56470588235294142.18
943902AF1-058 E
Adder
1.21882352941176491.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 217_SRT-A'
 OPEN BRANCH FROM BUS 314225 TO BUS 314227 CKT 1   /*6CHARCTY     230.0 - 6LAKESIDE    230.0
 OPEN BRANCH FROM BUS 314225 TO BUS 314260 CKT 1   /*6CHARCTY     230.0 - 6VARINA      230.0
 OPEN BRANCH FROM BUS 314260 TO BUS 314287 CKT 1   /*6VARINA      230.0 - 6CHESTF B    230.0
 OPEN BUS 314225                                   /*6CHARCTY     230.0
 OPEN BUS 314260                                   /*6VARINA      230.0
END
CONTINGENCY 'DVP_P4-2: H2T557_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 224022-1_SRT-S'
 OPEN BRANCH FROM BUS 314466 TO BUS 314909 CKT 1                /*6FENTRES     230.0 - 8FENTRES     500.0
 OPEN BRANCH FROM BUS 314466 TO BUS 316171 CKT 1                /*6FENTRES     230.0 - 6POCATY      230.0
 OPEN BUS 314655                                                /*6FENTR_2     230.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES     500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES     500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P4-2: 224022-2_SRT-S'
 OPEN BRANCH FROM BUS 314466 TO BUS 314909 CKT 2                /*6FENTRES     230.0 - 8FENTRES     500.0
 OPEN BRANCH FROM BUS 314466 TO BUS 316171 CKT 1                /*6FENTRES     230.0 - 6POCATY      230.0
 OPEN BUS 313889                                                /*6FENTRES_STC 230.0
 OPEN BUS 314654                                                /*6FENTR_1     230.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES     500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES     500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 271_SRT-A'
 OPEN BRANCH FROM BUS 314481 TO BUS 316171 CKT 1   /*6LANDSTN     230.0 - 6POCATY      230.0
END
CONTINGENCY 'DVP_P1-2: LN 2240_SRT-A'
 OPEN BRANCH FROM BUS 314466 TO BUS 316171 CKT 1   /*6FENTRES     230.0 - 6POCATY      230.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
END
CONTINGENCY 'DVP_P4-2: 2110T2128_SRT-A'
 OPEN BRANCH FROM BUS 314466 TO BUS 314508 CKT 1   /*6FENTRES     230.0 - 6THRASHER    230.0
 OPEN BRANCH FROM BUS 314480 TO BUS 314508 CKT 1   /*6HUNTSMN     230.0 - 6THRASHER    230.0
 OPEN BRANCH FROM BUS 314480 TO BUS 314537 CKT 1   /*6HUNTSMN     230.0 - 6SUFFOLK     230.0
 OPEN BUS 314480                                   /*6HUNTSMN     230.0
END
CONTINGENCY 'DVP_P4-2: 212822_SRT-S'
 OPEN BRANCH FROM BUS 314466 TO BUS 314508 CKT 1                /*6FENTRES     230.0 - 6THRASHER    230.0
 OPEN BRANCH FROM BUS 314466 TO BUS 314909 CKT 1                /*6FENTRES     230.0 - 8FENTRES     500.0
 OPEN BUS 314655                                                /*6FENTR_2     230.0
 SET POSTCONTRATING 1166 BRANCH FROM BUS 314480 TO BUS 314508 CKT 1 /*6HUNTSMN     230.0 - 6THRASHER    230.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES     500.0 - 8YADKIN      500.0
 SET PRECONTRATING 1051 BRANCH FROM BUS 314480 TO BUS 314508 CKT 1 /*6HUNTSMN     230.0 - 6THRASHER    230.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES     500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P4-2: 269T2128_SRT-S'
 OPEN BRANCH FROM BUS 314466 TO BUS 314508 CKT 1                /*6FENTRES     230.0 - 6THRASHER    230.0
 OPEN BRANCH FROM BUS 314466 TO BUS 314645 CKT 1                /*6FENTRES     230.0 - 6SLIGO L269  230.0
 OPEN BRANCH FROM BUS 314645 TO BUS 938530 CKT 1                /*6SLIGO L269  230.0 - AE1-072 TP   230.0
 SET POSTCONTRATING 1166 BRANCH FROM BUS 314480 TO BUS 314508 CKT 1 /*6HUNTSMN     230.0 - 6THRASHER    230.0
 SET PRECONTRATING 1051 BRANCH FROM BUS 314480 TO BUS 314508 CKT 1 /*6HUNTSMN     230.0 - 6THRASHER    230.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A'
 OPEN BRANCH FROM BUS 314218 TO BUS 314196 CKT 1   /*6ELMONT      230.0 - 6LADYSMITH   230.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1   /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T567_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1   /*6CHCKAHM     230.0 - 8CHCKAHM     500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
314287 to 314276 ckt 1
314218 to 314908 ckt 1
314466 to 314508 ckt 1
314196 to 314911 ckt 1
316171 to 314481 ckt 1
314902 to 314282 ckt 2
314902 to 314914 ckt 1
314914 to 314918 ckt 1
314924 to 314903 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC107.9 %1123.3B1212.0520.38
GD1DVP
6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC101.4 %1123.3B1139.0120.38
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC113.32 %3940.0C4464.92202.01
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.39 %3220.44B3329.5461.0
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC104.31 %3637.0C3793.65271.17
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC111.58 %4070.2B4541.4778.98
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC111.48 %5011.0C5586.06259.68
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC100.74 %4070.2B4100.4868.22
GD1DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: 545T552_SRT-S
BreakerAC107.93 %3940.0C4252.56134.24
GD1DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC100.26 %3220.44B3228.8939.2
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
SingleAC102.3 %1058.16B1082.5218.27
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC119.4 %3220.44B3845.2867.91
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC117.79 %3940.0C4640.88225.81
GD1DVP
8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line
DVP_P4-2: H3T539_SRT-A
BreakerAC106.41 %3532.0C3758.495.45
GD1DVP
8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line
DVP_P4-2: H1T539_SRT-S
BreakerAC105.89 %3532.0C3739.9195.27
GD1DVP
8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line
DVP_P1-2: LN 539_SRT-A
SingleAC101.44 %3220.44B3266.7528.43
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC111.63 %3220.44B3595.0931.55
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
SingleAC110.86 %3220.44B3570.0533.57
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC110.14 %3940.0C4339.53109.68
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC116.71 %3220.44B3758.5640.27
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC113.93 %3220.44B3669.1350.49
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC111.88 %3940.0C4408.08139.43
GD1DVP
8OX-8CLIFTON 500.0 kV Ckt 1 line
DVP_P7-1: LN 2101-569_SRT-S
TowerAC105.43 %3144.0C3314.5695.98
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC120.93 %3220.44B3894.3339.3
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC119.78 %3220.44B3857.5749.45
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC117.54 %3940.0C4631.24137.23

Details for 6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.9 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1212.05
MW Contribution:20.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940431AE2-027 C
Adder
7.5435294117647066.412
316075AC2-137 C
80/20
0.2450.245
3150641CHESTS8
80/20
1.2141.214
3150611CHESTG7
80/20
2.3972.397
3150801HOPHCF4
80/20
2.1822.182
3150681DARBY 2
80/20
1.8091.809
3150671DARBY 1
80/20
1.8071.807
961611AG1-000B C
Adder
8.3835294117647077.126
942001AE2-212 C
Adder
1.22235294117647041.039
3150831SPRUNCA
80/20
5.5985.598
3150841SPRUNCB
80/20
5.5985.598
941101AE2-104 C
Adder
1.55058823529411781.318
944581AF1-123 C
Adder
20.69529411764706217.591
927041AC1-191 C
80/20
7.557.55
966871AG1-558 C
80/20
1.881.88
316169AC1-164 GEN
80/20
24.58124.581
3150771HOPHCF1
80/20
1.4371.437
3150731STONECA
Adder
4.0823529411764713.47
935161AD1-151 C
Adder
9.0317647058823527.677
316312AB1-027 C
80/20
0.3940.394
3150701DARBY 4
80/20
1.8171.817
3142366NRTHEST
80/20
0.1340.134
316349AD2-085 C
Adder
1.65294117647058841.405
942341AE2-247 C
Adder
0.71647058823529410.609
958161AF2-110 C
Adder
0.63294117647058830.538
938531AE1-072 C
Adder
8.06.8
315051AA1-145 CT1
80/20
8.6838.683
3150451FOUR RIVERC
80/20
6.666.66
940551AE2-041 C
Adder
3.70470588235294153.149
3150601CHESTF5
80/20
39.41539.415
3150631CHESTG8
80/20
2.3582.358
3150621CHESTS7
80/20
1.11.1
3143096IRON208
80/20
0.2880.288
3150781HOPHCF2
80/20
1.4371.437
316004AC1-112 C
80/20
0.2460.246
3150691DARBY 3
80/20
1.8151.815
939191AE1-149 C
Adder
5.63882352941176554.793
944641AF1-129 C
80/20
62.43662.436
316240AF1-291 C
80/20
1.2941.294
943461AF1-017 C
Adder
0.64823529411764710.551
316311AC2-079 C
Adder
2.74117647058823532.33
941591AE2-156 C
Adder
8.3011764705882357.056
944591AF1-124 C
Adder
20.76941176470588217.654
944601AF1-125 C
Adder
20.37647058823529617.32
316233AE1-074 C
Adder
1.31411764705882361.117
3142296MT RD221
80/20
0.1030.103
957601AF2-054 C
Adder
1.060.901
943471AF1-018 C
Adder
3.70470588235294153.149
944631AF1-128 C
80/20
24.66324.663
3150921YORKTN3
Adder
60.82117647058823551.698
3150791HOPHCF3
80/20
1.4371.437
3150651CHESTF6
80/20
11.36811.368
3150851SPRUNCC
80/20
0.10.1
3150861SPRUNCD
80/20
0.10.1
957871AF2-081 C
Adder
4.5541176470588243.871
933291AC2-141 C
Adder
13.77294117647058911.707
3150481FOUR RIVERF
80/20
6.566.56
3150461FOUR RIVERD
80/20
5.3725.372
3150471FOUR RIVERE
80/20
5.3725.372
3150441FOUR RIVERB
80/20
5.4515.451
315052AA1-145 CT2
80/20
8.6788.678
3150431FOUR RIVERA
80/20
5.4515.451
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.18619.186
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.3311.33
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.2052.205
LAGNLTFEXP_LAGN->PJM
CLTF
3.6223.622
NYPJM->LTFIMP_NY
CLTF
1.1351.135
LGEELTFEXP_LGEE->PJM
CLTF
0.7730.773
WECLTFEXP_WEC->PJM
CLTF
0.3950.395
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9991.999
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.12437.124
CPLELTFEXP_CPLE->PJM
CLTF
4.1874.187
TVALTFEXP_TVA->PJM
CLTF
2.9092.909
SIGELTFEXP_SIGE->PJM
CLTF
0.1430.143

Details for 6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.4 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1139.01
MW Contribution:20.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940551AE2-041 C
Adder
3.70470588235294153.149
3150601CHESTF5
80/20
39.41539.415
3150631CHESTG8
80/20
2.3582.358
3150621CHESTS7
80/20
1.11.1
3143096IRON208
80/20
0.2880.288
3150781HOPHCF2
80/20
1.4371.437
316004AC1-112 C
80/20
0.2460.246
3150691DARBY 3
80/20
1.8151.815
939191AE1-149 C
Adder
5.63882352941176554.793
944641AF1-129 C
80/20
62.43662.436
316240AF1-291 C
80/20
1.2941.294
943461AF1-017 C
Adder
0.64823529411764710.551
316311AC2-079 C
Adder
2.74117647058823532.33
941591AE2-156 C
Adder
8.3011764705882357.056
944591AF1-124 C
Adder
20.76941176470588217.654
944601AF1-125 C
Adder
20.37647058823529617.32
316233AE1-074 C
Adder
1.31411764705882361.117
3142296MT RD221
80/20
0.1030.103
957601AF2-054 C
Adder
1.060.901
966881AG1-559 C
80/20
7.7447.744
943471AF1-018 C
Adder
3.70470588235294153.149
944631AF1-128 C
80/20
24.66324.663
3150921YORKTN3
Adder
60.82117647058823551.698
3150791HOPHCF3
80/20
1.4371.437
3150651CHESTF6
80/20
11.36811.368
3150851SPRUNCC
80/20
0.10.1
3150861SPRUNCD
80/20
0.10.1
957871AF2-081 C
Adder
4.5541176470588243.871
940431AE2-027 C
Adder
7.5435294117647066.412
316075AC2-137 C
80/20
0.2450.245
3150641CHESTS8
80/20
1.2141.214
3150611CHESTG7
80/20
2.3972.397
3150801HOPHCF4
80/20
2.1822.182
3150681DARBY 2
80/20
1.8091.809
3150671DARBY 1
80/20
1.8071.807
961611AG1-000B C
Adder
8.3835294117647077.126
942001AE2-212 C
Adder
1.22235294117647041.039
3150831SPRUNCA
80/20
5.5985.598
3150841SPRUNCB
80/20
5.5985.598
941101AE2-104 C
Adder
1.55058823529411781.318
944581AF1-123 C
Adder
20.69529411764706217.591
927041AC1-191 C
80/20
7.557.55
966871AG1-558 C
80/20
1.881.88
933291AC2-141 C
Adder
13.77294117647058911.707
3150481FOUR RIVERF
80/20
6.566.56
3150461FOUR RIVERD
80/20
5.3725.372
3150471FOUR RIVERE
80/20
5.3725.372
3150441FOUR RIVERB
80/20
5.4515.451
315052AA1-145 CT2
80/20
8.6788.678
3150431FOUR RIVERA
80/20
5.4515.451
316169AC1-164 GEN
80/20
24.58124.581
3150771HOPHCF1
80/20
1.4371.437
3150731STONECA
Adder
4.0823529411764713.47
935161AD1-151 C
Adder
9.0317647058823527.677
316312AB1-027 C
80/20
0.3940.394
3150701DARBY 4
80/20
1.8171.817
3142366NRTHEST
80/20
0.1340.134
316349AD2-085 C
Adder
1.65294117647058841.405
942341AE2-247 C
Adder
0.71647058823529410.609
958161AF2-110 C
Adder
0.63294117647058830.538
938531AE1-072 C
Adder
8.06.8
315051AA1-145 CT1
80/20
8.6838.683
3150451FOUR RIVERC
80/20
6.666.66
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.18619.186
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.3311.33
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.2052.205
LAGNLTFEXP_LAGN->PJM
CLTF
3.6223.622
NYPJM->LTFIMP_NY
CLTF
1.1351.135
LGEELTFEXP_LGEE->PJM
CLTF
0.7730.773
WECLTFEXP_WEC->PJM
CLTF
0.3950.395
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9991.999
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.12437.124
CPLELTFEXP_CPLE->PJM
CLTF
4.1874.187
TVALTFEXP_TVA->PJM
CLTF
2.9092.909
SIGELTFEXP_SIGE->PJM
CLTF
0.1430.143

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.32 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4464.92
MW Contribution:202.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
939191AE1-149 C
Adder
12.10588235294117610.29
936666AD2-085 E
Adder
7.1317647058823546.062
942342AE2-247 E
Adder
2.61647058823529432.224
943461AF1-017 C
Adder
1.71411764705882371.457
3143316POE
Adder
1.6082352941176471.367
932596AC2-079 E
Adder
11.94588235294117610.154
316311AC2-079 C
Adder
7.3223529411764716.224
941591AE2-156 C
50/50
24.00724.007
3151101ELIZAR3
50/50
4.3424.342
944591AF1-124 C
50/50
62.59862.598
944601AF1-125 C
50/50
61.41561.415
919152AA1-139 E1
50/50
5.535.53
938532AE1-072 E
50/50
12.39212.392
3146326AYDLETT TAP
50/50
1.8341.834
917122Z2-027 E
Adder
1.81294117647058831.541
901082W1-029 E
Adder
42.9564705882352936.513
938771AE1-103 C
Adder
3.8941176470588243.31
3145413WATKINS
Adder
0.92117647058823540.783
920692AA2-178 E
Adder
5.5388235294117654.708
934521AD1-076 C
Adder
16.4752941176470614.004
934511AD1-075 C
Adder
11.3411764705882369.64
920042AA2-088 E OP
Adder
14.1647058823529412.04
960081AF2-299 C
Adder
2.4988235294117652.124
966622AG1-532 E
Adder
1.24941176470588241.062
926072AC1-086 E
Adder
12.85176470588235310.924
3145723EMPORIA
Adder
0.57647058823529410.49
923573AB1-173 E OP
Adder
4.3858823529411773.728
919692AA2-053 E OP
Adder
5.65176470588235354.804
944011AF1-069 C
50/50
21.78821.788
926206AC1-098 E
Adder
4.8835294117647064.151
3152421Z1-086 GT2
50/50
17.33717.337
3152441Z1-086 ST
50/50
30.18730.187
3152411Z1-086 GT1
50/50
17.34217.342
963041AG1-153 C
50/50
9.1739.173
3151051BRUNSWICKS1
50/50
28.03428.034
3151041BRUNSWICKG3
50/50
13.49413.494
925785AC1-054 E
Adder
4.5188235294117653.841
316263AC1-034 C
Adder
8.8505882352941177.523
922923AB1-081 E OP
Adder
4.9682352941176474.223
937481AD2-202 C
50/50
0.5150.515
962562AG1-105 E
Adder
7.41411764705882356.302
964791AG1-342 C
Adder
4.4517647058823523.784
927264AC1-222 E
Adder
5.0905882352941184.327
939192AE1-149 E
Adder
8.0705882352941176.86
939312AE1-162 E
Adder
1.72117647058823551.463
316375AC2-012 C
50/50
1.8031.803
926662AC1-147 E
Adder
1.77411764705882361.508
3151081ELIZAR1
50/50
4.2884.288
916192Z1-068 E
50/50
2.5342.534
916191Z1-068 C
50/50
0.0590.059
957492AF2-043 E
Adder
1.9105882352941181.624
941101AE2-104 C
Adder
4.4388235294117653.773
934065AD1-033 E
50/50
6.7926.792
316185AD1-033 C
50/50
1.6591.659
937226AE2-253 E
50/50
7.9097.909
944581AF1-123 C
50/50
62.37662.376
316294AC1-161 C
50/50
6.8696.869
940541AE2-040 C
50/50
3.9673.967
923852AB2-025 E
50/50
1.6041.604
940481AE2-033 C
50/50
22.31122.311
940482AE2-033 E
50/50
15.04115.041
934501AD1-074 C
Adder
45.3647058823529438.56
939412AE1-173 E
50/50
96.49596.495
924517AB2-100 E2
Adder
3.9282352941176473.339
961942AG1-037 E
Adder
0.451764705882352960.384
316141AB2-099 E
Adder
0.33882352941176470.288
961941AG1-037 C
Adder
0.6764705882352940.575
923263AB1-132 E OP
Adder
8.217647058823536.985
316088AB2-174 E
Adder
8.7141176470588247.407
923994AB2-040_E
Adder
8.2247058823529416.991
941031AE2-094 C
50/50
66.68466.684
941032AE2-094 E
50/50
29.86629.866
3151021BRUNSWICKG1
50/50
13.49413.494
3151031BRUNSWICKG2
50/50
13.49413.494
934331AD1-057 C
Adder
4.6741176470588233.973
934322AD1-056 E
Adder
4.5447058823529413.863
934332AD1-057 E
Adder
2.43411764705882352.069
934321AD1-056 C
Adder
8.3788235294117657.122
927022AC1-189 E
Adder
5.6070588235294124.766
961672AG1-007 E
Adder
0.71058823529411760.604
961671AG1-007 C
Adder
1.25411764705882361.066
957482AF2-042 E
50/50
52.68252.682
957481AF2-042 C
50/50
79.02379.023
925595AC1-034 E
Adder
6.6764705882352945.675
934621AD1-088 C
50/50
13.2613.26
3151531CLOVER1
50/50
18.02218.022
3151541CLOVER2
50/50
17.85317.853
935172AD1-152 E
Adder
7.5717647058823536.436
924322AB2-079 E O1
Adder
1.6447058823529411.398
924312AB2-078 E O1
Adder
1.6447058823529411.398
926274AC1-105 E
Adder
3.4082352941176472.897
943902AF1-058 E
Adder
1.65529411764705881.407
3150921YORKTN3
Adder
124.22470588235294105.591
934576AD1-082 E
Adder
5.2247058823529414.441
316084AB2-161 E
Adder
6.5576470588235295.574
3145256KINGFORK
Adder
1.30823529411764721.112
925522AC1-027 E
50/50
1.641.64
316316AC1-027 C
50/50
0.4240.424
943612AF1-032 E
Adder
1.24117647058823531.055
941102AE2-104 E
Adder
7.0576470588235295.999
3145506HICKORY
50/50
2.9532.953
944602AF1-125 E
50/50
140.592140.592
957872AF2-081 E
50/50
5.7955.795
957871AF2-081 C
50/50
13.52313.523
316017AA1-139 ULT1
50/50
1.4591.459
316018AA1-139 ULT2
50/50
1.4591.459
933292AC2-141 E
50/50
18.00718.007
933291AC2-141 C
50/50
42.18342.183
926755AC1-161 E
50/50
18.00718.007
940492AE2-034 E
Adder
4.1541176470588243.531
316315AB2-025 C
50/50
0.5620.562
3145946PLYMOUTH TP
Adder
0.435294117647058830.37
934522AD1-076 E
Adder
8.397647058823537.138
933982AD1-022 E
Adder
6.417647058823535.455
943172AE2-346 E
Adder
0.81176470588235290.69
940641AE2-051 C
50/50
28.87528.875
918492AA1-063AE OP
Adder
5.4552941176470594.637
925122AB2-169 E
Adder
7.7223529411764716.564
917332KELFORD E
Adder
2.2035294117647061.873
946282AF1-292 E
Adder
1.37882352941176461.172
944012AF1-069 E
50/50
8.4648.464
932632AC2-084 E
Adder
4.3164705882352943.669
926214AC1-099 E
Adder
1.61294117647058831.371
3152431Z1-086 GT3
50/50
17.33717.337
316274AC1-208 C
Adder
12.05058823529411810.243
927146AC1-208 E
Adder
5.3517647058823544.549
917512Z2-088 E OP1
Adder
6.54705882352941255.565
917342Z2-044 E
Adder
0.79764705882352950.678
3151311EDGECMA
Adder
20.6976470588235317.593
934622AD1-088 E
50/50
6.3856.385
934611AD1-087 C
50/50
1.7741.774
937482AD2-202 E
50/50
1.5031.503
934612AD1-087 E
50/50
5.1365.136
924162AB2-060 E OP
Adder
5.2141176470588244.432
964242AG1-285 E
Adder
9.9188235294117648.431
964792AG1-342 E
Adder
2.9682352941176472.523
927255AC1-221 E
Adder
4.84941176470588254.122
932763AC2-100 E
Adder
3.2952941176470592.801
935112AD1-144 E
Adder
1.21411764705882351.032
943462AF1-017 E
Adder
2.7964705882352942.377
316349AD2-085 C
Adder
4.3705882352941173.715
942341AE2-247 C
Adder
1.89411764705882371.61
932046AC2-012 E
50/50
17.5517.55
3151091ELIZAR2
50/50
4.2124.212
958161AF2-110 C
Adder
1.8117647058823531.54
958162AF2-110 E
Adder
2.8811764705882352.449
316388AE2-253 GEN
50/50
2.652.65
944582AF1-123 E
50/50
142.834142.834
944592AF1-124 E
50/50
143.351143.351
919153AA1-139 E2
50/50
5.535.53
938531AE1-072 C
50/50
23.77123.771
923832AB2-022 E
Adder
1.67529411764705881.424
913392Y1-086 E
Adder
2.9682352941176472.523
938772AE1-103 E
Adder
5.3788235294117654.572
916042Z1-036 E
Adder
38.52941176470588432.75
3145393UNCAMP
Adder
8.0941176470588236.88
934502AD1-074 E
Adder
23.0929411764705919.629
934512AD1-075 E
Adder
5.7729411764705894.907
939411AE1-173 C
50/50
144.742144.742
933981AD1-022 C
Adder
11.78823529411764610.02
900672V4-068 E
Adder
0.47764705882352950.406
918512AA1-065 E OP
Adder
7.42823529411764756.314
924516AB2-100 E1
Adder
3.9282352941176473.339
940642AE2-051 E
50/50
19.2519.25
966621AG1-532 C
Adder
1.87411764705882341.593
960082AF2-299 E
Adder
1.66588235294117641.416
946281AF1-292 C
Adder
2.0682352941176471.758
926071AC1-086 C
Adder
28.2376470588235324.002
3137643SOCKMAN
Adder
0.95176470588235310.809
963042AG1-153 E
50/50
13.7613.76
918532AA1-067 E
Adder
0.95764705882352940.814
927021AC1-189 C
Adder
11.2564705882352949.568
919710AA2-057 E
Adder
5.2964705882352944.502
924152AB2-059 E OP
Adder
7.0388235294117655.983
924022AB2-043 E O1
Adder
6.3552941176470595.402
924302AB2-077 E O1
Adder
1.6447058823529411.398
964241AG1-285 C
Adder
14.8776470588235312.646
962561AG1-105 C
Adder
11.1211764705882359.453
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.25255.252
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.53435.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.5866.586
LAGNLTFEXP_LAGN->PJM
CLTF
11.79711.797
NYPJM->LTFIMP_NY
CLTF
2.5842.584
LGEELTFEXP_LGEE->PJM
CLTF
2.1892.189
WECLTFEXP_WEC->PJM
CLTF
1.1371.137
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6257.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
136.078136.078
CPLELTFEXP_CPLE->PJM
CLTF
15.98515.985
TVALTFEXP_TVA->PJM
CLTF
9.3529.352
O66PJM->LTFIMP_O-066
CMTX_NF
36.00236.002
G-007PJM->LTFIMP_G-007
CMTX_NF
5.665.66
SIGELTFEXP_SIGE->PJM
CLTF
0.4160.416

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.39 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3329.54
MW Contribution:61.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940431AE2-027 C
Adder
11.395294117647069.686
961611AG1-000B C
Adder
17.0670588235294114.507
942001AE2-212 C
Adder
2.11411764705882371.797
316072AD1-144 C
80/20
0.3590.359
316375AC2-012 C
80/20
1.7911.791
3151081ELIZAR1
80/20
4.2584.258
916191Z1-068 C
80/20
0.0580.058
941101AE2-104 C
80/20
4.4074.407
316185AD1-033 C
80/20
1.6481.648
944581AF1-123 C
80/20
61.95761.957
316294AC1-161 C
80/20
6.8246.824
3156116Z1-036WIND
80/20
0.8770.877
315614AA2-178 C
80/20
2.0912.091
940491AE2-034 C
80/20
1.5381.538
940541AE2-040 C
80/20
3.9443.944
940481AE2-033 C
80/20
22.18122.181
934501AD1-074 C
80/20
45.0845.08
3156083AA2-088SOLA
80/20
1.4051.405
316365AB2-100 C1
80/20
1.2911.291
943171AE2-346 C
80/20
0.2980.298
961941AG1-037 C
80/20
0.6730.673
3151391GASTONA
80/20
4.0664.066
3151411GASTONB
80/20
4.0664.066
316181AB2-040 GEN
80/20
1.6831.683
941031AE2-094 C
80/20
66.45566.455
3147043LAWRENC
80/20
0.3980.398
3151021BRUNSWICKG1
80/20
13.44613.446
3151031BRUNSWICKG2
80/20
13.44613.446
934331AD1-057 C
Adder
4.6482352941176473.951
934321AD1-056 C
Adder
8.332941176470597.083
961671AG1-007 C
Adder
1.2482352941176471.061
957481AF2-042 C
80/20
78.71578.715
934621AD1-088 C
80/20
13.20613.206
3151531CLOVER1
80/20
17.9517.95
3151541CLOVER2
80/20
17.78117.781
958211AF2-115 C
Adder
2.28235294117647051.94
946301AF1-294 C
Adder
3.75411764705882333.191
935161AD1-151 C
Adder
15.27058823529411812.98
316349AD2-085 C
80/20
4.3374.337
942341AE2-247 C
80/20
1.881.88
3150991CHESPKB
80/20
0.9580.958
3151091ELIZAR2
80/20
4.1834.183
316246AF1-032 C
80/20
0.3780.378
958161AF2-110 C
80/20
1.7981.798
316388AE2-253 GEN
80/20
2.6322.632
938531AE1-072 C
80/20
23.60823.608
316320Y1-086 C
80/20
0.2940.294
939411AE1-173 C
80/20
144.1144.1
933981AD1-022 C
80/20
11.71411.714
316318V4-068 C
80/20
0.1070.107
3156021HOLLOMANSOL
80/20
2.4482.448
316174AB2-169_C
80/20
1.3931.393
966621AG1-532 C
80/20
1.8631.863
946281AF1-292 C
80/20
2.0562.056
316011AB1-132 C OP
80/20
3.1053.105
926071AC1-086 C
80/20
28.07728.077
313506AB1-173 C OP
80/20
1.4941.494
3156063AA2-053SOLA
80/20
1.9981.998
3151371ROSEMS1
80/20
1.681.68
3137643SOCKMAN
80/20
0.9470.947
3151281ROARAP4
80/20
1.7351.735
316210AC1-098 C
80/20
1.251.25
927021AC1-189 C
Adder
11.1952941176470599.516
935171AD1-152 C
80/20
1.8271.827
964241AG1-285 C
Adder
14.80352941176470712.583
962561AG1-105 C
Adder
11.0694117647058839.409
936161AD2-022 C
Adder
9.455294117647068.037
939191AE1-149 C
Adder
11.99058823529411710.192
943461AF1-017 C
80/20
1.7011.701
316311AC2-079 C
80/20
7.2667.266
3150981CHESPKA
80/20
0.5780.578
316036AC1-147 C
80/20
0.4890.489
941591AE2-156 C
80/20
23.83823.838
3151101ELIZAR3
80/20
4.3114.311
316305AF2-043 C
80/20
0.4630.463
944591AF1-124 C
80/20
62.17762.177
944601AF1-125 C
80/20
61.00261.002
316321Z2-027 C
80/20
0.4860.486
3156056W1-029WIND
80/20
1.0361.036
938771AE1-103 C
80/20
3.8693.869
3151151S HAMPT1
80/20
1.9741.974
934521AD1-076 C
80/20
16.37216.372
934511AD1-075 C
80/20
11.2711.27
3156073AA1-063SOLA
80/20
1.8611.861
960081AF2-299 C
80/20
2.4842.484
316087AB2-174 C
80/20
1.561.56
3151381ROSEMG2
80/20
1.271.27
3151361ROSEMG1
80/20
2.7122.712
3151261ROARAP2
80/20
1.8341.834
944011AF1-069 C
80/20
21.71321.713
316212AC1-099 C
80/20
0.4180.418
3152421Z1-086 GT2
80/20
17.27717.277
3152441Z1-086 ST
80/20
30.08230.082
3152411Z1-086 GT1
80/20
17.28217.282
963041AG1-153 C
80/20
9.1419.141
3151051BRUNSWICKS1
80/20
27.93527.935
3151041BRUNSWICKG3
80/20
13.44613.446
316263AC1-034 C
Adder
8.8035294117647057.483
937481AD2-202 C
80/20
0.5130.513
936261AD2-033 C
Adder
14.72470588235294112.516
959311AF2-222 C
Adder
18.28823529411764815.545
964791AG1-342 C
Adder
4.4317647058823533.767
961791AG1-021 C
Adder
1.82588235294117651.552
936171AD2-023 C
Adder
5.5152941176470584.688
3150921YORKTN3
Adder
127.84235294117647108.666
3152331SURRY 2
80/20
30.82730.827
316316AC1-027 C
80/20
0.4210.421
957871AF2-081 C
80/20
13.4313.43
316017AA1-139 ULT1
80/20
1.4491.449
316018AA1-139 ULT2
80/20
1.4491.449
933291AC2-141 C
80/20
41.90441.904
313526AB2-022 C
80/20
0.5040.504
316315AB2-025 C
80/20
0.5580.558
3152921DOMTR78
80/20
1.8181.818
316023AB2-100 C2
80/20
1.2911.291
316140AB2-099 C
80/20
0.1280.128
940641AE2-051 C
80/20
28.76428.764
316317KELFORD C
80/20
0.4760.476
932631AC2-084 C
80/20
1.3311.331
3152431Z1-086 GT3
80/20
17.27717.277
316274AC1-208 C
80/20
11.98411.984
316129AC1-054 C
80/20
1.5891.589
3151311EDGECMA
Adder
20.58941176470588317.501
934611AD1-087 C
80/20
1.7671.767
3138533PONTONDP
Adder
0.6764705882352940.575
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.0655.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.38335.383
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.566.56
LAGNLTFEXP_LAGN->PJM
CLTF
11.74411.744
NYPJM->LTFIMP_NY
CLTF
2.5592.559
LGEELTFEXP_LGEE->PJM
CLTF
2.182.18
WECLTFEXP_WEC->PJM
CLTF
1.1331.133
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.597.59
CBM South 2LTFEXP_CBM-S2->PJM
CBM
135.46135.46
CPLELTFEXP_CPLE->PJM
CLTF
15.91315.913
TVALTFEXP_TVA->PJM
CLTF
9.319.31
SIGELTFEXP_SIGE->PJM
CLTF
0.4150.415

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.31 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:3793.65
MW Contribution:271.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
963611AG1-210 C
Adder
0.93294117647058830.793
3141813NORNECK
Adder
1.24235294117647071.056
966662AG1-536 E
Adder
10.6329411764705889.038
962861AG1-135 C
Adder
8.9694117647058827.624
962862AG1-135 E
Adder
5.985.083
943741AF1-042 C
Adder
4.3658823529411773.711
943742AF1-042 E
Adder
7.1235294117647056.055
934392AD1-063 E
Adder
1.69764705882352951.443
923842AB2-024 E
Adder
2.84000000000000032.414
316076AC2-137 E
Adder
1.77294117647058821.507
3138116ELKO L286
Adder
1.84941176470588251.572
961611AG1-000B C
Adder
25.22588235294117721.442
939192AE1-149 E
Adder
9.628.177
939312AE1-162 E
50/50
2.4312.431
316072AD1-144 C
50/50
0.4940.494
316375AC2-012 C
50/50
2.4382.438
316078AC2-138 E
Adder
1.30588235294117671.11
963612AG1-210 E
Adder
1.39882352941176481.189
966661AG1-536 C
Adder
7.9129411764705886.726
958262AF2-120 E
Adder
6.1329411764705885.213
939612AE1-191 E
Adder
8.9247058823529427.586
316169AC1-164 GEN
50/50
65.01265.012
316159AE1-175 C
50/50
0.7040.704
935161AD1-151 C
Adder
22.94117647058823619.5
934012AD1-025 E
Adder
14.63647058823529612.441
3151161SURRY 1
50/50
40.01540.015
935112AD1-144 E
50/50
1.661.66
943462AF1-017 E
Adder
3.55294117647058853.02
316349AD2-085 C
Adder
5.5541176470588244.721
942341AE2-247 C
Adder
2.40705882352941152.046
3150991CHESPKB
50/50
1.3041.304
932046AC2-012 E
50/50
23.72823.728
3151091ELIZAR2
50/50
5.6915.691
316246AF1-032 C
50/50
0.5030.503
958161AF2-110 C
50/50
2.3482.348
958162AF2-110 E
50/50
3.7353.735
316388AE2-253 GEN
50/50
3.5313.531
944582AF1-123 E
50/50
191.735191.735
944592AF1-124 E
50/50
192.429192.429
919153AA1-139 E2
50/50
7.3487.348
938531AE1-072 C
50/50
31.50731.507
923832AB2-022 E
50/50
2.1962.196
913392Y1-086 E
50/50
3.893.89
316320Y1-086 C
50/50
0.3880.388
938772AE1-103 E
Adder
6.6011764705882355.611
916042Z1-036 E
50/50
48.46248.462
3145393UNCAMP
Adder
9.815294117647068.343
934502AD1-074 E
Adder
27.4094117647058823.298
934512AD1-075 E
Adder
6.8529411764705895.825
939411AE1-173 C
50/50
144.69144.69
933981AD1-022 C
Adder
13.8411.764
900672V4-068 E
Adder
0.53882352941176470.458
918512AA1-065 E OP
Adder
8.4494117647058827.182
924516AB2-100 E1
Adder
3.87764705882352923.296
940642AE2-051 E
50/50
17.58317.583
966621AG1-532 C
Adder
1.84588235294117651.569
960082AF2-299 E
Adder
1.01882352941176470.866
946281AF1-292 C
Adder
2.03764705882352941.732
926071AC1-086 C
Adder
28.7023529411764724.397
3137643SOCKMAN
Adder
0.96588235294117640.821
963042AG1-153 E
Adder
11.4941176470588249.77
957602AF2-054 E
Adder
2.24117647058823531.905
926662AC1-147 E
50/50
2.3992.399
3151081ELIZAR1
50/50
5.7935.793
916192Z1-068 E
50/50
3.4083.408
916191Z1-068 C
50/50
0.0790.079
957492AF2-043 E
50/50
2.5222.522
941101AE2-104 C
50/50
5.7555.755
934065AD1-033 E
50/50
9.1079.107
316185AD1-033 C
50/50
2.2242.224
937226AE2-253 E
50/50
10.53510.535
944581AF1-123 C
50/50
83.73183.731
316294AC1-161 C
50/50
9.6819.681
3156116Z1-036WIND
50/50
1.1111.111
940541AE2-040 C
Adder
3.79058823529411763.222
923852AB2-025 E
Adder
1.53294117647058831.303
940481AE2-033 C
Adder
21.4117647058823518.2
940482AE2-033 E
Adder
14.43529411764705912.27
934501AD1-074 C
Adder
53.8447058823529445.768
939412AE1-173 E
50/50
96.4696.46
924517AB2-100 E2
Adder
3.87764705882352923.296
961942AG1-037 E
Adder
0.50470588235294120.429
316141AB2-099 E
Adder
0.37882352941176470.322
961941AG1-037 C
Adder
0.75764705882352950.644
923263AB1-132 E OP
Adder
8.3529411764705897.1
316088AB2-174 E
Adder
8.6929411764705897.389
923994AB2-040_E
Adder
8.2482352941176477.011
941031AE2-094 C
Adder
55.5058823529411847.18
941032AE2-094 E
Adder
24.8621.131
957831AF2-077 C
50/50
0.570.57
316157AD2-030 E
Adder
1.88588235294117661.603
964211AG1-282 C
Adder
2.87176470588235282.441
936592AD2-074 E
Adder
13.61411764705882311.572
936591AD2-074 C
Adder
8.3435294117647067.092
961952AG1-038 E
Adder
6.66352941176470555.664
961951AG1-038 C
Adder
4.8258823529411774.102
939602AE1-190 E
Adder
2.23058823529411751.896
925865AC1-065 E
Adder
25.8294117647058821.955
943471AF1-018 C
Adder
11.3211764705882359.623
3130536PAPERMILL
Adder
10.4988235294117648.924
926785AC1-164_E
50/50
29.20829.208
316160AE1-175 E
50/50
2.1482.148
944631AF1-128 C
Adder
50.1435294117647142.622
3150921YORKTN3
50/50
222.183222.183
3144216WINCHST
50/50
0.2410.241
316236AE1-162 C
50/50
0.5940.594
934576AD1-082 E
Adder
6.4070588235294125.446
316084AB2-161 E
Adder
8.0411764705882356.835
3145256KINGFORK
50/50
1.7881.788
3152331SURRY 2
50/50
52.5452.54
925522AC1-027 E
50/50
2.2062.206
316316AC1-027 C
50/50
0.5710.571
943612AF1-032 E
50/50
1.6391.639
941102AE2-104 E
50/50
9.159.15
3145506HICKORY
50/50
3.9493.949
944602AF1-125 E
50/50
188.725188.725
957872AF2-081 E
50/50
7.7017.701
957871AF2-081 C
50/50
17.9717.97
316017AA1-139 ULT1
50/50
1.9391.939
316018AA1-139 ULT2
50/50
1.9391.939
933292AC2-141 E
50/50
25.37725.377
933291AC2-141 C
50/50
59.4559.45
926755AC1-161 E
50/50
25.37725.377
313526AB2-022 C
50/50
0.6650.665
940492AE2-034 E
Adder
5.057647058823534.299
3145946PLYMOUTH TP
Adder
0.51882352941176470.441
934522AD1-076 E
Adder
9.9670588235294128.472
933982AD1-022 E
Adder
7.5341176470588246.404
943172AE2-346 E
Adder
0.90941176470588240.773
940641AE2-051 C
50/50
26.37426.374
918492AA1-063AE OP
Adder
5.82352941176470654.95
925122AB2-169 E
Adder
8.6941176470588237.39
917332KELFORD E
Adder
2.42.04
944012AF1-069 E
Adder
7.04588235294117655.989
939246AE1-155 E
Adder
12.80941176470588310.888
958261AF2-120 C
Adder
9.1988235294117657.819
934146AD1-041 E
Adder
5.5776470588235294.741
940551AE2-041 C
Adder
11.3211764705882359.623
962962AG1-145 E
50/50
2.6032.603
316382AG1-145 C
50/50
0.6360.636
3150601CHESTF5
Adder
80.1388235294117768.118
925332AB2-190 E
Adder
11.1811764705882369.504
935162AD1-151 E
Adder
15.29411764705882413
927226AC1-216 E
Adder
11.3047058823529419.609
924814AB2-134 E
Adder
18.51882352941176515.741
939191AE1-149 C
Adder
14.42941176470588312.265
936666AD2-085 E
Adder
9.0611764705882357.702
942342AE2-247 E
Adder
3.3247058823529412.826
943461AF1-017 C
Adder
2.17764705882352951.851
932596AC2-079 E
Adder
15.21999999999999912.937
316311AC2-079 C
Adder
9.3282352941176477.929
3150981CHESPKA
50/50
0.7870.787
316036AC1-147 C
50/50
0.6650.665
941591AE2-156 C
50/50
32.45632.456
3151101ELIZAR3
50/50
5.8665.866
316305AF2-043 C
50/50
0.6160.616
944591AF1-124 C
50/50
84.02984.029
944601AF1-125 C
50/50
82.44182.441
919152AA1-139 E1
50/50
7.3487.348
938532AE1-072 E
50/50
16.42416.424
3146326AYDLETT TAP
50/50
2.4292.429
917122Z2-027 E
50/50
2.3642.364
316321Z2-027 C
50/50
0.6380.638
3156056W1-029WIND
50/50
1.351.35
901082W1-029 E
50/50
55.655.6
938771AE1-103 C
Adder
4.7799999999999994.063
3145413WATKINS
Adder
1.09647058823529430.932
920692AA2-178 E
Adder
6.7435294117647065.732
934521AD1-076 C
Adder
19.5552941176470616.622
934511AD1-075 C
Adder
13.46117647058823511.442
920042AA2-088 E OP
Adder
16.1705882352941213.745
960081AF2-299 C
Adder
2.46117647058823552.092
926072AC1-086 E
Adder
13.06352941176470511.104
3145723EMPORIA
Adder
0.57058823529411760.485
923573AB1-173 E OP
Adder
4.3988235294117643.739
919692AA2-053 E OP
Adder
5.8800000000000014.998
944011AF1-069 C
Adder
18.13647058823529415.416
963041AG1-153 C
Adder
7.662352941176476.513
957832AF2-077 E
50/50
2.4692.469
957601AF2-054 C
Adder
3.36117647058823542.857
964212AG1-282 E
Adder
1.91529411764705881.628
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.41628.416
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.24623.246
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.853.85
LAGNLTFEXP_LAGN->PJM
CLTF
8.2678.267
NYPJM->LTFIMP_NY
CLTF
2.0382.038
LGEELTFEXP_LGEE->PJM
CLTF
1.1621.162
WECLTFEXP_WEC->PJM
CLTF
0.5990.599
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.5566.556
CBM South 2LTFEXP_CBM-S2->PJM
CBM
111.34111.34
CPLELTFEXP_CPLE->PJM
CLTF
13.75813.758
TVALTFEXP_TVA->PJM
CLTF
6.4816.481
O66PJM->LTFIMP_O-066
CMTX_NF
27.4327.43
G-007PJM->LTFIMP_G-007
CMTX_NF
4.3044.304
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.58 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4541.47
MW Contribution:78.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
963611AG1-210 C
Adder
0.95764705882352940.814
962861AG1-135 C
Adder
9.3188235294117667.921
943741AF1-042 C
Adder
4.5552941176470593.872
940431AE2-027 C
Adder
22.58000000000000219.193
316075AC2-137 C
80/20
0.6870.687
3150641CHESTS8
80/20
3.5113.511
3150611CHESTG7
80/20
6.9316.931
3150801HOPHCF4
80/20
6.5586.558
316369AC1-216 C
80/20
2.8462.846
3150681DARBY 2
80/20
4.5764.576
3150671DARBY 1
80/20
4.574.57
961611AG1-000B C
80/20
28.34928.349
942001AE2-212 C
Adder
3.73882352941176473.178
3150831SPRUNCA
Adder
15.78000000000000113.413
3150841SPRUNCB
Adder
15.78000000000000113.413
941101AE2-104 C
Adder
5.8423529411764714.966
944581AF1-123 C
Adder
80.2141176470588368.182
316294AC1-161 C
80/20
8.8498.849
940541AE2-040 C
Adder
4.5529411764705883.87
940481AE2-033 C
Adder
25.6411764705882421.795
934501AD1-074 C
Adder
56.2176470588235347.785
961941AG1-037 C
Adder
0.82117647058823530.698
941031AE2-094 C
Adder
59.24117647058823650.355
934331AD1-057 C
Adder
5.3847058823529414.577
934321AD1-056 C
Adder
9.6541176470588248.206
961671AG1-007 C
Adder
1.44941176470588241.232
957481AF2-042 C
Adder
77.7682352941176466.103
927041AC1-191 C
Adder
16.39529411764705813.936
966871AG1-558 C
Adder
4.0835294117647063.471
934621AD1-088 C
Adder
13.69294117647058911.639
964211AG1-282 C
Adder
2.9811764705882352.534
958261AF2-120 C
Adder
9.5447058823529418.113
940551AE2-041 C
Adder
12.16117647058823610.337
316382AG1-145 C
80/20
0.6420.642
3150601CHESTF5
80/20
113.981113.981
3150631CHESTG8
80/20
6.826.82
3150621CHESTS7
80/20
3.1823.182
3143096IRON208
80/20
0.7870.787
3150781HOPHCF2
80/20
4.324.32
3150761HOPPOLC
80/20
2.7172.717
316132AB2-190 C
80/20
7.3677.367
316004AC1-112 C
80/20
0.5960.596
3150691DARBY 3
80/20
4.5924.592
939191AE1-149 C
Adder
18.60588235294117615.815
944641AF1-129 C
Adder
179.8423529411765152.866
316240AF1-291 C
Adder
3.78000000000000023.213
943461AF1-017 C
Adder
2.34941176470588251.997
316311AC2-079 C
Adder
9.984705882352948.487
941591AE2-156 C
Adder
31.64823529411764726.901
944591AF1-124 C
Adder
80.4988235294117868.424
944601AF1-125 C
Adder
78.9788235294117767.132
938771AE1-103 C
Adder
4.9788235294117654.232
934521AD1-076 C
Adder
20.41647058823529517.354
934511AD1-075 C
Adder
14.05411764705882411.946
316233AE1-074 C
Adder
4.08588235294117653.473
3142296MT RD221
80/20
0.2170.217
960081AF2-299 C
Adder
2.92.465
944011AF1-069 C
Adder
19.35647058823529316.453
963041AG1-153 C
Adder
8.3011764705882357.056
316263AC1-034 C
Adder
10.102352941176478.587
936261AD2-033 C
Adder
18.25529411764705815.517
957601AF2-054 C
Adder
3.56235294117647073.028
966661AG1-536 C
Adder
8.2105882352941186.979
316169AC1-164 GEN
80/20
73.90473.904
316159AE1-175 C
80/20
0.7120.712
3150771HOPHCF1
80/20
4.324.32
3150731STONECA
80/20
12.27512.275
935161AD1-151 C
80/20
28.71928.719
316312AB1-027 C
80/20
0.9570.957
3150701DARBY 4
80/20
4.5974.597
3151161SURRY 1
80/20
43.78843.788
3142366NRTHEST
80/20
0.330.33
316349AD2-085 C
Adder
5.9917647058823535.093
942341AE2-247 C
Adder
2.5964705882352942.207
958161AF2-110 C
Adder
2.38352941176470572.026
938531AE1-072 C
Adder
30.76823529411764526.153
939411AE1-173 C
Adder
145.74235294117648123.881
933981AD1-022 C
Adder
14.54588235294117712.364
966621AG1-532 C
Adder
2.1752941176470591.849
946281AF1-292 C
Adder
2.40117647058823552.041
926071AC1-086 C
Adder
32.9752941176470628.029
3137643SOCKMAN
Adder
1.1117647058823530.945
927021AC1-189 C
Adder
13.13058823529411811.161
964241AG1-285 C
Adder
17.71058823529411815.054
936591AD2-074 C
Adder
8.7058823529411787.4
961951AG1-038 C
Adder
5.035294117647064.28
943471AF1-018 C
Adder
12.16117647058823610.337
944631AF1-128 C
80/20
71.31971.319
3150921YORKTN3
80/20
215.99215.99
3144216WINCHST
80/20
0.2370.237
3150791HOPHCF3
80/20
4.324.32
934011AD1-025 C
80/20
4.6114.611
316033AB2-134 GEN
80/20
3.7293.729
3151191GRAVEL3
80/20
4.4484.448
3151221GRAVEL6
80/20
4.54.5
3151201GRAVEL4
80/20
4.5054.505
3150651CHESTF6
Adder
32.7447058823529427.833
3152331SURRY 2
80/20
45.81645.816
957871AF2-081 C
Adder
17.51647058823529314.889
933291AC2-141 C
80/20
54.34454.344
940641AE2-051 C
Adder
26.97529411764705622.929
316274AC1-208 C
Adder
14.04588235294117711.939
3151311EDGECMA
Adder
23.6270588235294120.083
316336AC2-165 C
Adder
13.90823529411764711.822
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.27284.272
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.64648.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
9.5619.561
LAGNLTFEXP_LAGN->PJM
CLTF
15.45715.457
NYPJM->LTFIMP_NY
CLTF
4.1344.134
LGEELTFEXP_LGEE->PJM
CLTF
3.3563.356
WECLTFEXP_WEC->PJM
CLTF
1.7261.726
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.4058.405
CBM South 2LTFEXP_CBM-S2->PJM
CBM
156.686156.686
CPLELTFEXP_CPLE->PJM
CLTF
17.60717.607
TVALTFEXP_TVA->PJM
CLTF
12.412.4
SIGELTFEXP_SIGE->PJM
CLTF
0.620.62

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.48 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5586.06
MW Contribution:259.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934146AD1-041 E
Adder
6.0129411764705885.111
940551AE2-041 C
Adder
12.15411764705882410.331
962962AG1-145 E
50/50
2.6282.628
316382AG1-145 C
50/50
0.6420.642
3150601CHESTF5
50/50
113.923113.923
3150631CHESTG8
50/50
6.8166.816
3150621CHESTS7
50/50
3.183.18
925332AB2-190 E
Adder
14.35882352941176512.205
935162AD1-151 E
Adder
19.1376470588235316.267
927226AC1-216 E
Adder
13.74117647058823411.68
924814AB2-134 E
Adder
22.5082352941176519.132
316004AC1-112 C
50/50
0.5960.596
3150691DARBY 3
50/50
4.5894.589
939191AE1-149 C
Adder
18.59882352941176415.809
944641AF1-129 C
Adder
179.7623529411765152.798
316240AF1-291 C
Adder
3.7788235294117653.212
936666AD2-085 E
Adder
9.7729411764705898.307
942342AE2-247 E
Adder
3.58470588235294143.047
943461AF1-017 C
Adder
2.34941176470588251.997
3143316POE
Adder
2.31058823529411761.964
932596AC2-079 E
Adder
16.2847058823529413.842
316311AC2-079 C
Adder
9.9811764705882358.484
941591AE2-156 C
Adder
31.63647058823529426.891
944591AF1-124 C
Adder
80.4682352941176568.398
944601AF1-125 C
Adder
78.9482352941176467.106
919152AA1-139 E1
Adder
7.166.086
938532AE1-072 E
Adder
16.0329411764705913.628
3146326AYDLETT TAP
Adder
2.3717647058823532.016
917122Z2-027 E
Adder
2.3352941176470591.985
901082W1-029 E
Adder
55.2529411764705946.965
938771AE1-103 C
Adder
4.9776470588235294.231
3145413WATKINS
Adder
1.15882352941176480.985
920692AA2-178 E
Adder
6.9352941176470585.895
934521AD1-076 C
Adder
20.41176470588235517.35
934511AD1-075 C
Adder
14.05058823529411811.943
316233AE1-074 C
Adder
4.08588235294117653.473
920042AA2-088 E OP
Adder
17.4414.824
3142296MT RD221
50/50
0.2170.217
960081AF2-299 C
Adder
2.92.465
966622AG1-532 E
Adder
1.45058823529411771.233
926072AC1-086 E
Adder
15.0047058823529412.754
3145723EMPORIA
Adder
0.66941176470588230.569
923573AB1-173 E OP
Adder
5.11176470588235254.345
919692AA2-053 E OP
Adder
6.6552941176470595.657
944011AF1-069 C
Adder
19.35294117647058716.45
963041AG1-153 C
Adder
8.37.055
927042AC1-191 E
Adder
8.1611764705882366.937
957832AF2-077 E
Adder
2.49294117647058842.119
957601AF2-054 C
Adder
3.56117647058823563.027
936592AD2-074 E
Adder
14.19411764705882312.065
936591AD2-074 C
Adder
8.77.395
961952AG1-038 E
Adder
6.9482352941176475.906
961951AG1-038 C
Adder
5.0317647058823534.277
939602AE1-190 E
Adder
2.40470588235294122.044
925865AC1-065 E
Adder
28.22117647058823723.988
943471AF1-018 C
Adder
12.15411764705882410.331
3130536PAPERMILL
Adder
11.342352941176479.641
926785AC1-164_E
50/50
33.18433.184
316160AE1-175 E
50/50
2.1682.168
944631AF1-128 C
50/50
71.28371.283
3150921YORKTN3
Adder
215.8894117647059183.506
3150651CHESTF6
Adder
32.7305882352941227.821
946262AF1-291 E
Adder
2.5188235294117652.141
934576AD1-082 E
Adder
7.6470588235294126.5
316084AB2-161 E
Adder
9.597647058823538.158
3145256KINGFORK
Adder
1.78823529411764711.52
3152331SURRY 2
50/50
45.79645.796
925522AC1-027 E
Adder
2.14588235294117661.824
943612AF1-032 E
Adder
1.61764705882352941.375
941102AE2-104 E
Adder
9.2858823529411767.893
3145506HICKORY
Adder
3.83058823529411763.256
944602AF1-125 E
Adder
180.73058823529414153.621
957872AF2-081 E
Adder
7.50470588235294046.379
957871AF2-081 C
Adder
17.5105882352941214.884
933292AC2-141 E
Adder
23.1894117647058819.711
933291AC2-141 C
Adder
54.3223529411764746.174
926755AC1-161 E
Adder
23.1894117647058819.711
940492AE2-034 E
Adder
5.2011764705882364.421
3145946PLYMOUTH TP
Adder
0.540.459
934522AD1-076 E
Adder
10.4035294117647078.843
938552AE1-074 E
Adder
2.05764705882352941.749
933982AD1-022 E
Adder
7.9164705882352956.729
943172AE2-346 E
Adder
0.98588235294117640.838
943741AF1-042 C
Adder
4.5517647058823533.869
943742AF1-042 E
Adder
7.42705882352941156.313
934392AD1-063 E
Adder
1.8235294117647061.55
923842AB2-024 E
Adder
3.07294117647058852.612
940431AE2-027 C
Adder
22.57058823529411719.185
316075AC2-137 C
50/50
0.6870.687
316076AC2-137 E
50/50
2.4242.424
3138116ELKO L286
50/50
2.5282.528
3150641CHESTS8
50/50
3.5093.509
3150611CHESTG7
50/50
6.9276.927
3150681DARBY 2
50/50
4.5734.573
3150671DARBY 1
50/50
4.5674.567
961611AG1-000B C
Adder
28.33647058823529424.086
939192AE1-149 E
Adder
12.39882352941176410.539
939312AE1-162 E
Adder
2.54117647058823562.16
942002AE2-212 E
Adder
2.49058823529411782.117
942001AE2-212 C
Adder
3.73647058823529443.176
3150831SPRUNCA
Adder
15.77411764705882313.408
3150841SPRUNCB
Adder
15.77411764705882313.408
926662AC1-147 E
Adder
2.34000000000000031.989
916192Z1-068 E
Adder
3.3141176470588242.817
957492AF2-043 E
Adder
2.48941176470588272.116
941101AE2-104 C
Adder
5.8411764705882354.965
934065AD1-033 E
Adder
8.8270588235294137.503
937226AE2-253 E
Adder
10.2482352941176478.711
944581AF1-123 C
Adder
80.1835294117647168.156
940541AE2-040 C
Adder
4.5517647058823533.869
923852AB2-025 E
Adder
1.84117647058823521.565
940481AE2-033 C
Adder
25.63411764705882621.789
940482AE2-033 E
Adder
17.28117647058823514.689
934501AD1-074 C
Adder
56.2023529411764747.772
939412AE1-173 E
Adder
97.132941176470682.563
924517AB2-100 E2
Adder
4.5505882352941183.868
961942AG1-037 E
Adder
0.54705882352941180.465
316141AB2-099 E
Adder
0.410588235294117640.349
961941AG1-037 C
Adder
0.82117647058823530.698
923263AB1-132 E OP
Adder
9.595294117647068.156
316088AB2-174 E
Adder
10.1435294117647078.622
923994AB2-040_E
Adder
9.5835294117647068.146
941031AE2-094 C
Adder
59.2294117647058850.345
941032AE2-094 E
Adder
26.52705882352941222.548
957481AF2-042 C
Adder
70.616470588235360.024
927041AC1-191 C
Adder
16.38352941176470513.926
966871AG1-558 C
Adder
4.083.468
966872AG1-558 E
Adder
2.0552941176470591.747
316157AD2-030 E
Adder
1.99764705882352931.698
939612AE1-191 E
Adder
9.628.177
316169AC1-164 GEN
50/50
73.86273.862
940432AE2-027 E
Adder
15.04705882352941212.79
316159AE1-175 C
50/50
0.7110.711
3150731STONECA
Adder
12.26941176470588210.429
935161AD1-151 C
Adder
28.70588235294117424.4
934012AD1-025 E
Adder
17.78941176470588215.121
930122AB1-027 E
50/50
2.5162.516
926412AC1-112 E
50/50
2.0462.046
316312AB1-027 C
50/50
0.9560.956
3150701DARBY 4
50/50
4.5944.594
3142366NRTHEST
50/50
0.330.33
935112AD1-144 E
Adder
1.66000000000000011.411
943462AF1-017 E
Adder
3.8317647058823533.257
316349AD2-085 C
Adder
5.9894117647058835.091
942341AE2-247 C
Adder
2.5964705882352942.207
932046AC2-012 E
Adder
23.15176470588235319.679
958161AF2-110 C
Adder
2.38352941176470572.026
958162AF2-110 E
Adder
3.79058823529411763.222
944582AF1-123 E
Adder
183.61176470588234156.07
944592AF1-124 E
Adder
184.2764705882353156.635
919153AA1-139 E2
Adder
7.166.086
938531AE1-072 C
Adder
30.75647058823529526.143
923832AB2-022 E
Adder
2.16117647058823531.837
913392Y1-086 E
Adder
3.8282352941176473.254
938772AE1-103 E
Adder
6.8741176470588235.843
916042Z1-036 E
Adder
48.916470588235341.579
3145393UNCAMP
Adder
10.2788235294117658.737
934502AD1-074 E
Adder
28.60941176470588624.318
934512AD1-075 E
Adder
7.1529411764705896.08
939411AE1-173 C
Adder
145.69882352941175123.844
933981AD1-022 C
Adder
14.54117647058823512.36
900672V4-068 E
Adder
0.58235294117647060.495
918512AA1-065 E OP
Adder
9.0517647058823547.694
924516AB2-100 E1
Adder
4.5505882352941183.868
940642AE2-051 E
Adder
17.97882352941176615.282
966621AG1-532 C
Adder
2.1752941176470591.849
960082AF2-299 E
Adder
1.93294117647058841.643
946281AF1-292 C
Adder
2.40117647058823552.041
926071AC1-086 C
Adder
32.9682352941176528.023
3137643SOCKMAN
Adder
1.1117647058823530.945
963042AG1-153 E
Adder
12.44941176470588410.582
957602AF2-054 E
Adder
2.37411764705882342.018
940641AE2-051 C
Adder
26.96705882352941322.922
918492AA1-063AE OP
Adder
6.5082352941176485.532
925122AB2-169 E
Adder
9.3470588235294127.945
917332KELFORD E
Adder
2.63882352941176462.243
946282AF1-292 E
Adder
1.61.36
944012AF1-069 E
Adder
7.5176470588235296.39
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.33484.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.67448.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
9.5679.567
LAGNLTFEXP_LAGN->PJM
CLTF
15.46415.464
NYPJM->LTFIMP_NY
CLTF
4.1384.138
LGEELTFEXP_LGEE->PJM
CLTF
3.3583.358
WECLTFEXP_WEC->PJM
CLTF
1.7271.727
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.4068.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
156.721156.721
CPLELTFEXP_CPLE->PJM
CLTF
17.60917.609
TVALTFEXP_TVA->PJM
CLTF
12.40612.406
O66PJM->LTFIMP_O-066
CMTX_NF
58.60758.607
G-007PJM->LTFIMP_G-007
CMTX_NF
9.2239.223
SIGELTFEXP_SIGE->PJM
CLTF
0.620.62

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.74 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4100.48
MW Contribution:68.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
958261AF2-120 C
Adder
8.16.885
940551AE2-041 C
Adder
10.3670588235294128.812
316382AG1-145 C
80/20
0.5540.554
3150601CHESTF5
80/20
92.29692.296
3150631CHESTG8
80/20
5.5225.522
3150621CHESTS7
80/20
2.5762.576
316004AC1-112 C
80/20
0.5060.506
3151171GRAVELC
80/20
1.2921.292
939191AE1-149 C
Adder
15.33294117647058713.033
944641AF1-129 C
Adder
143.61529411764707122.073
316240AF1-291 C
Adder
3.02705882352941162.573
943461AF1-017 C
Adder
1.99058823529411751.692
316311AC2-079 C
Adder
8.4682352941176487.198
3150981CHESPKA
80/20
0.6610.661
316036AC1-147 C
80/20
0.5590.559
941591AE2-156 C
80/20
27.25627.256
3151101ELIZAR3
80/20
4.9194.919
316305AF2-043 C
80/20
0.5230.523
944591AF1-124 C
80/20
69.53869.538
944601AF1-125 C
80/20
68.22568.225
316321Z2-027 C
80/20
0.5420.542
938771AE1-103 C
Adder
4.2458823529411773.609
934521AD1-076 C
Adder
17.4447058823529414.828
934511AD1-075 C
Adder
12.00823529411764810.207
3142296MT RD221
80/20
0.180.18
960081AF2-299 C
Adder
2.4235294117647062.06
944011AF1-069 C
Adder
16.40117647058823613.941
963041AG1-153 C
Adder
7.0223529411764725.969
316263AC1-034 C
Adder
8.5517647058823547.269
957601AF2-054 C
Adder
3.03647058823529432.581
963611AG1-210 C
Adder
0.81058823529411760.689
962861AG1-135 C
Adder
7.9105882352941186.724
943741AF1-042 C
Adder
3.87058823529411773.29
940431AE2-027 C
Adder
18.18117647058823715.454
316075AC2-137 C
80/20
0.5730.573
3150641CHESTS8
80/20
2.8432.843
3150611CHESTG7
80/20
5.6125.612
316369AC1-216 C
80/20
2.3642.364
961611AG1-000B C
80/20
23.84623.846
942001AE2-212 C
Adder
3.01764705882352932.565
3150831SPRUNCA
Adder
10.6141176470588259.022
3150841SPRUNCB
Adder
10.6141176470588259.022
316072AD1-144 C
80/20
0.4250.425
316375AC2-012 C
80/20
2.0492.049
3151081ELIZAR1
80/20
4.8584.858
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
55
316185AD1-033 C
80/20
1.8591.859
944581AF1-123 C
80/20
69.29269.292
316294AC1-161 C
80/20
7.7077.707
940541AE2-040 C
Adder
3.7941176470588243.225
940481AE2-033 C
Adder
21.37647058823529618.17
934501AD1-074 C
Adder
48.0341176470588340.829
961941AG1-037 C
Adder
0.69764705882352940.593
941031AE2-094 C
Adder
50.196470588235342.667
934331AD1-057 C
Adder
4.5482352941176483.866
934321AD1-056 C
Adder
8.1541176470588246.931
961671AG1-007 C
Adder
1.22941176470588221.045
957481AF2-042 C
Adder
64.7188235294117655.011
927041AC1-191 C
Adder
13.58823529411764911.55
966871AG1-558 C
Adder
3.3847058823529412.877
934621AD1-088 C
Adder
11.2658823529411789.576
3152191CUNINGD
80/20
17.70617.706
957831AF2-077 C
80/20
0.4940.494
964211AG1-282 C
Adder
2.5270588235294122.148
936591AD2-074 C
Adder
7.3964705882352946.287
961951AG1-038 C
Adder
4.277647058823533.636
943471AF1-018 C
Adder
10.3670588235294128.812
944631AF1-128 C
80/20
57.75157.751
3150921YORKTN3
80/20
186.63186.63
3144216WINCHST
80/20
0.2040.204
934011AD1-025 C
80/20
3.8313.831
316033AB2-134 GEN
80/20
3.0983.098
3151191GRAVEL3
80/20
3.7583.758
3151221GRAVEL6
80/20
3.8023.802
3151201GRAVEL4
80/20
3.8063.806
3151211GRAVEL5
80/20
3.7583.758
316236AE1-162 C
80/20
0.5280.528
3150651CHESTF6
Adder
26.14823529411764722.226
3152331SURRY 2
80/20
40.26840.268
316316AC1-027 C
80/20
0.4790.479
957871AF2-081 C
80/20
15.09215.092
316017AA1-139 ULT1
80/20
1.6281.628
316018AA1-139 ULT2
80/20
1.6281.628
933291AC2-141 C
80/20
47.32947.329
313526AB2-022 C
80/20
0.5630.563
940641AE2-051 C
Adder
23.00823529411764719.557
316274AC1-208 C
Adder
11.86588235294117810.086
3151311EDGECMA
Adder
20.00352941176470617.003
3152161CUNINGA
80/20
7.9167.916
3152181CUNINGC
80/20
7.9167.916
3152171CUNINGB
80/20
7.9167.916
966661AG1-536 C
Adder
6.96705882352941155.922
316169AC1-164 GEN
80/20
63.00863.008
316159AE1-175 C
80/20
0.6130.613
3150731STONECA
Adder
9.9858823529411778.488
935161AD1-151 C
80/20
23.75423.754
316312AB1-027 C
80/20
0.8120.812
3151161SURRY 1
80/20
36.99436.994
316349AD2-085 C
Adder
5.0752941176470594.314
942341AE2-247 C
Adder
2.21.87
3150991CHESPKB
80/20
1.0961.096
3151091ELIZAR2
80/20
4.7734.773
316246AF1-032 C
80/20
0.4270.427
958161AF2-110 C
80/20
2.042.04
316388AE2-253 GEN
80/20
2.9612.961
938531AE1-072 C
80/20
26.50226.502
316320Y1-086 C
80/20
0.3290.329
939411AE1-173 C
Adder
124.68470588235294105.982
933981AD1-022 C
Adder
12.41647058823529510.554
966621AG1-532 C
Adder
1.81764705882352941.545
946281AF1-292 C
Adder
2.00588235294117641.705
926071AC1-086 C
Adder
27.76352941176470823.599
3137643SOCKMAN
Adder
0.93411764705882360.794
927021AC1-189 C
Adder
11.1482352941176499.476
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.17274.172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.32542.325
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.3698.369
LAGNLTFEXP_LAGN->PJM
CLTF
13.38813.388
NYPJM->LTFIMP_NY
CLTF
3.5973.597
LGEELTFEXP_LGEE->PJM
CLTF
2.952.95
WECLTFEXP_WEC->PJM
CLTF
1.5171.517
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1467.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
133.887133.887
CPLELTFEXP_CPLE->PJM
CLTF
14.96914.969
TVALTFEXP_TVA->PJM
CLTF
10.74810.748
SIGELTFEXP_SIGE->PJM
CLTF
0.5440.544

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.93 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4252.56
MW Contribution:134.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934146AD1-041 E
Adder
3.17647058823529442.7
940551AE2-041 C
Adder
6.3964705882352955.437
962962AG1-145 E
Adder
1.34588235294117631.144
3150601CHESTF5
Adder
59.7211764705882350.763
925332AB2-190 E
Adder
7.537647058823536.407
935162AD1-151 E
Adder
10.0317647058823528.527
927226AC1-216 E
Adder
7.19176470588235356.113
924814AB2-134 E
Adder
11.78117647058823510.014
316004AC1-112 C
50/50
0.3130.313
3150691DARBY 3
50/50
2.4352.435
939191AE1-149 C
Adder
9.8564705882352958.378
944641AF1-129 C
Adder
95.9141176470588381.527
316240AF1-291 C
Adder
2.01647058823529421.714
936666AD2-085 E
Adder
5.11411764705882454.347
942342AE2-247 E
Adder
1.87647058823529411.595
943461AF1-017 C
Adder
1.22941176470588221.045
3143316POE
Adder
1.23411764705882351.049
932596AC2-079 E
Adder
8.517647058823537.24
316311AC2-079 C
Adder
5.2200000000000014.437
941591AE2-156 C
Adder
16.3729411764705913.917
944591AF1-124 C
Adder
41.5988235294117735.359
962861AG1-135 C
Adder
5.1564705882352944.383
962862AG1-135 E
Adder
3.43764705882352972.922
943741AF1-042 C
Adder
2.4964705882352942.122
943742AF1-042 E
Adder
4.07294117647058853.462
934392AD1-063 E
Adder
0.960.816
923842AB2-024 E
Adder
1.61176470588235321.37
940431AE2-027 C
Adder
12.02823529411764810.224
316075AC2-137 C
50/50
0.3570.357
316076AC2-137 E
50/50
1.2591.259
3138116ELKO L286
50/50
1.3131.313
3150681DARBY 2
50/50
2.4262.426
3150671DARBY 1
50/50
2.4232.423
961611AG1-000B C
Adder
14.76705882352941212.552
939192AE1-149 E
Adder
6.5717647058823535.586
939312AE1-162 E
Adder
1.31882352941176471.121
942002AE2-212 E
Adder
1.33058823529411761.131
942001AE2-212 C
Adder
1.99647058823529421.697
3150831SPRUNCA
Adder
8.5294117647058827.25
3150841SPRUNCB
Adder
8.5294117647058827.25
926662AC1-147 E
Adder
1.2117647058823531.03
916192Z1-068 E
Adder
1.71529411764705891.458
957492AF2-043 E
Adder
1.29176470588235311.098
941101AE2-104 C
Adder
3.04235294117647072.586
934065AD1-033 E
Adder
4.5682352941176473.883
937226AE2-253 E
Adder
5.30941176470588254.513
944581AF1-123 C
Adder
41.45176470588235435.234
940541AE2-040 C
Adder
2.442.074
923852AB2-025 E
Adder
0.98705882352941180.839
940481AE2-033 C
Adder
13.74117647058823411.68
940482AE2-033 E
Adder
9.2635294117647067.874
934501AD1-074 C
Adder
29.5529411764705925.12
939412AE1-173 E
Adder
51.40235294117647443.692
924517AB2-100 E2
Adder
2.4388235294117652.073
961942AG1-037 E
Adder
0.290588235294117650.247
316141AB2-099 E
Adder
0.217647058823529420.185
961941AG1-037 C
Adder
0.435294117647058830.37
316088AB2-174 E
Adder
5.4517647058823534.634
923994AB2-040_E
Adder
1.6270588235294121.383
941031AE2-094 C
Adder
31.94588235294117627.154
941032AE2-094 E
Adder
14.3082352941176512.162
927041AC1-191 C
Adder
9.0164705882352937.664
966871AG1-558 C
Adder
2.24588235294117671.909
966872AG1-558 E
Adder
1.1317647058823530.962
958502AF2-144 E
Adder
1.0117647058823530.86
923862AB2-026 E
Adder
1.02941176470588250.875
316157AD2-030 E
Adder
1.05647058823529430.898
226896D-009
Adder
-1.4576470588235295-1.239
939612AE1-191 E
Adder
5.0823529411764714.32
316169AC1-164 GEN
Adder
37.8729411764705932.192
940432AE2-027 E
Adder
8.0188235294117656.816
3150731STONECA
Adder
6.46823529411764755.498
935161AD1-151 C
Adder
15.04823529411764812.791
934012AD1-025 E
Adder
9.3117647058823547.915
930122AB1-027 E
50/50
1.3221.322
926412AC1-112 E
50/50
1.0751.075
316312AB1-027 C
50/50
0.5020.502
3150701DARBY 4
50/50
2.4382.438
3142366NRTHEST
50/50
0.1760.176
935112AD1-144 E
Adder
0.86117647058823530.732
943462AF1-017 E
Adder
2.00588235294117641.705
316349AD2-085 C
Adder
3.13411764705882372.664
942341AE2-247 C
Adder
1.35882352941176481.155
932046AC2-012 E
Adder
11.9823529411764710.185
958161AF2-110 C
Adder
1.24117647058823531.055
958162AF2-110 E
Adder
1.97411764705882351.678
944582AF1-123 E
Adder
94.9280.682
944592AF1-124 E
Adder
95.2635294117647180.974
919153AA1-139 E2
Adder
3.71058823529411753.154
938531AE1-072 C
Adder
15.94470588235294213.553
923832AB2-022 E
Adder
1.12235294117647060.954
913392Y1-086 E
Adder
1.9870588235294121.689
938772AE1-103 E
Adder
3.60352941176470633.063
916042Z1-036 E
Adder
25.53647058823529321.706
3145393UNCAMP
Adder
5.3964705882352944.587
934502AD1-074 E
Adder
15.04470588235294112.788
934512AD1-075 E
Adder
3.76117647058823533.197
939411AE1-173 C
Adder
77.103529411764765.538
933981AD1-022 C
Adder
7.6564705882352946.508
900672V4-068 E
Adder
0.308235294117647050.262
918512AA1-065 E OP
Adder
4.7847058823529424.067
924516AB2-100 E1
Adder
2.4388235294117652.073
940642AE2-051 E
Adder
9.5882352941176498.15
966621AG1-532 C
Adder
1.17058823529411770.995
960082AF2-299 E
Adder
1.040.884
946281AF1-292 C
Adder
1.29176470588235311.098
963042AG1-153 E
Adder
6.7294117647058825.72
933502AC2-165 E
Adder
6.177647058823535.251
315051AA1-145 CT1
50/50
4.7834.783
3150451FOUR RIVERC
50/50
3.6693.669
3152261N ANNA2
50/50
28.62228.622
957602AF2-054 E
Adder
1.2552941176470591.067
966882AG1-559 E
50/50
1.1551.155
226704AOCX4-046 E
Adder
-2.8423529411764705-2.416
939261AE1-157 C
Adder
13.28588235294117611.293
936592AD2-074 E
Adder
7.7847058823529426.617
936591AD2-074 C
Adder
4.7717647058823534.056
961952AG1-038 E
Adder
3.81058823529411763.239
961951AG1-038 C
Adder
2.7588235294117652.345
939602AE1-190 E
Adder
1.27058823529411781.08
925865AC1-065 E
Adder
14.8929411764705912.659
943471AF1-018 C
Adder
6.3964705882352955.437
3130536PAPERMILL
Adder
5.95411764705882355.061
926785AC1-164_E
Adder
17.0152941176470614.463
316160AE1-175 E
Adder
1.11058823529411770.944
944631AF1-128 C
Adder
37.3682352941176531.763
3150921YORKTN3
Adder
110.8188235294117694.196
3150651CHESTF6
Adder
17.46352941176470714.844
946262AF1-291 E
Adder
1.34470588235294121.143
934576AD1-082 E
Adder
4.0317647058823533.427
316084AB2-161 E
Adder
5.06000000000000054.301
3145256KINGFORK
Adder
0.92823529411764720.789
925522AC1-027 E
Adder
1.11058823529411770.944
943612AF1-032 E
Adder
0.840.714
941102AE2-104 E
Adder
4.8364705882352944.111
3145506HICKORY
Adder
1.98352941176470581.686
944602AF1-125 E
Adder
93.4294117647058979.415
957872AF2-081 E
Adder
3.88941176470588263.306
957871AF2-081 C
Adder
9.0741176470588247.713
933292AC2-141 E
Adder
11.89764705882352810.113
933291AC2-141 C
Adder
27.87176470588235223.691
926755AC1-161 E
Adder
11.89764705882352810.113
940492AE2-034 E
Adder
2.72588235294117662.317
3145946PLYMOUTH TP
Adder
0.283529411764705860.241
934522AD1-076 E
Adder
5.4705882352941194.65
938552AE1-074 E
Adder
1.13294117647058810.963
933982AD1-022 E
Adder
4.1682352941176483.543
943172AE2-346 E
Adder
0.52235294117647060.444
940641AE2-051 C
Adder
14.38235294117647112.225
918492AA1-063AE OP
Adder
3.47058823529411782.95
946282AF1-292 E
Adder
0.86117647058823530.732
944012AF1-069 E
Adder
4.0552941176470593.447
938562AE1-075 E
Adder
0.87764705882352940.746
316336AC2-165 C
Adder
8.2082352941176486.977
3150481FOUR RIVERF
50/50
3.6143.614
3150461FOUR RIVERD
50/50
2.9592.959
3150471FOUR RIVERE
50/50
2.9592.959
3150441FOUR RIVERB
50/50
3.0033.003
315052AA1-145 CT2
50/50
4.7814.781
3150431FOUR RIVERA
50/50
3.0033.003
3152251N ANNA1
50/50
28.6128.61
939262AE1-157 E
Adder
7.2070588235294136.126
944601AF1-125 C
Adder
40.81294117647059534.691
919152AA1-139 E1
Adder
3.71058823529411753.154
938532AE1-072 E
Adder
8.3117647058823547.065
3146326AYDLETT TAP
Adder
1.22941176470588221.045
917122Z2-027 E
Adder
1.21294117647058821.031
901082W1-029 E
Adder
28.74235294117647424.431
938771AE1-103 C
Adder
2.60941176470588232.218
3145413WATKINS
Adder
0.60941176470588240.518
920692AA2-178 E
Adder
3.6352941176470593.09
934521AD1-076 C
Adder
10.7329411764705889.123
934511AD1-075 C
Adder
7.38823529411764756.28
316233AE1-074 C
Adder
2.25058823529411761.913
920042AA2-088 E OP
Adder
9.2247058823529417.841
3142296MT RD221
50/50
0.1170.117
960081AF2-299 C
Adder
1.56117647058823541.327
966622AG1-532 E
Adder
0.780.663
3145723EMPORIA
Adder
0.360.306
944011AF1-069 C
Adder
10.437647058823538.872
963041AG1-153 C
Adder
4.4858823529411773.813
927042AC1-191 E
Adder
4.4917647058823533.818
957832AF2-077 E
Adder
1.29764705882352941.103
957601AF2-054 C
Adder
1.8835294117647061.601
966881AG1-559 C
50/50
2.2942.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.34851.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.44428.444
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.7125.712
LAGNLTFEXP_LAGN->PJM
CLTF
8.98.9
NYPJM->LTFIMP_NY
CLTF
3.113.11
LGEELTFEXP_LGEE->PJM
CLTF
2.0262.026
WECLTFEXP_WEC->PJM
CLTF
1.0481.048
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.6074.607
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.84786.847
CPLELTFEXP_CPLE->PJM
CLTF
9.659.65
TVALTFEXP_TVA->PJM
CLTF
7.1437.143
O66PJM->LTFIMP_O-066
CMTX_NF
44.79944.799
G-007PJM->LTFIMP_G-007
CMTX_NF
7.0597.059
SIGELTFEXP_SIGE->PJM
CLTF
0.3720.372

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.26 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3228.89
MW Contribution:39.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
958261AF2-120 C
Adder
5.2200000000000014.437
940551AE2-041 C
Adder
6.2364705882352955.301
3150601CHESTF5
80/20
57.83757.837
3150631CHESTG8
80/20
3.4613.461
3150621CHESTS7
80/20
1.6141.614
3143096IRON208
80/20
0.4040.404
316004AC1-112 C
80/20
0.3050.305
3150691DARBY 3
80/20
2.3622.362
939191AE1-149 C
Adder
9.4788235294117668.057
944641AF1-129 C
Adder
92.5282352941176578.649
316240AF1-291 C
Adder
1.94470588235294131.653
943461AF1-017 C
Adder
1.18117647058823531.004
316311AC2-079 C
Adder
5.0141176470588234.262
941591AE2-156 C
Adder
15.7305882352941213.371
944591AF1-124 C
Adder
39.9505882352941233.958
944601AF1-125 C
Adder
39.1964705882352933.317
938771AE1-103 C
Adder
2.5011764705882352.126
934521AD1-076 C
Adder
10.2717647058823538.731
934511AD1-075 C
Adder
7.0705882352941176.01
316233AE1-074 C
Adder
2.1552941176470591.832
3142296MT RD221
80/20
0.1140.114
960081AF2-299 C
Adder
1.48823529411764691.265
944011AF1-069 C
Adder
9.9305882352941198.441
963041AG1-153 C
Adder
4.2658823529411763.626
957601AF2-054 C
Adder
1.83764705882352961.562
966881AG1-559 C
80/20
2.2882.288
3150381LDYSMT2
80/20
4.3034.303
3150411LDYSMT5
80/20
4.4394.439
963611AG1-210 C
Adder
0.53882352941176470.458
962861AG1-135 C
Adder
5.0788235294117654.317
943741AF1-042 C
Adder
2.45411764705882352.086
940431AE2-027 C
Adder
11.5988235294117659.859
316075AC2-137 C
80/20
0.3470.347
3150641CHESTS8
80/20
1.7811.781
3150611CHESTG7
80/20
3.5173.517
3150681DARBY 2
80/20
2.3542.354
3150671DARBY 1
80/20
2.3512.351
961611AG1-000B C
Adder
14.23176470588235412.097
942001AE2-212 C
Adder
1.92117647058823531.633
3150831SPRUNCA
Adder
8.2188235294117656.986
3150841SPRUNCB
80/20
8.2198.219
941101AE2-104 C
Adder
2.92000000000000042.482
944581AF1-123 C
Adder
39.80941176470588533.838
940541AE2-040 C
Adder
2.33294117647058831.983
940481AE2-033 C
Adder
13.13529411764705811.165
934501AD1-074 C
Adder
28.28352941176470724.041
961941AG1-037 C
Adder
0.41529411764705880.353
941031AE2-094 C
Adder
30.39411764705882425.835
957481AF2-042 C
Adder
40.39647058823529634.337
927041AC1-191 C
80/20
8.8178.817
966871AG1-558 C
80/20
2.1962.196
934621AD1-088 C
Adder
7.1611764705882356.087
3150391LDYSMT3
80/20
4.4174.417
3150401LDYSMT4
80/20
4.4254.425
3150371LDYSMT1
80/20
4.2494.249
964211AG1-282 C
Adder
1.65294117647058841.405
936591AD2-074 C
Adder
4.6894117647058823.986
961951AG1-038 C
Adder
2.7117647058823532.305
943471AF1-018 C
Adder
6.2364705882352955.301
944631AF1-128 C
80/20
36.1936.19
3150921YORKTN3
Adder
107.0694117647058991.009
3150651CHESTF6
Adder
16.84705882352941214.32
3150851SPRUNCC
80/20
0.1470.147
3150861SPRUNCD
80/20
0.1470.147
957871AF2-081 C
Adder
8.7129411764705887.406
933291AC2-141 C
Adder
26.7822.763
940641AE2-051 C
Adder
13.71529411764705811.658
316336AC2-165 C
Adder
7.7411764705882356.58
3150481FOUR RIVERF
80/20
3.5533.553
3150461FOUR RIVERD
80/20
2.9092.909
3150471FOUR RIVERE
80/20
2.9092.909
3150441FOUR RIVERB
80/20
2.9522.952
315052AA1-145 CT2
80/20
4.74.7
3150431FOUR RIVERA
80/20
2.9522.952
3152251N ANNA1
80/20
26.07926.079
966661AG1-536 C
Adder
4.4905882352941183.817
316169AC1-164 GEN
80/20
36.80636.806
3150731STONECA
Adder
6.2458823529411775.309
935161AD1-151 C
Adder
14.5176470588235312.34
316312AB1-027 C
80/20
0.4890.489
3150701DARBY 4
80/20
2.3652.365
3142366NRTHEST
80/20
0.1710.171
316349AD2-085 C
Adder
3.0105882352941182.559
942341AE2-247 C
Adder
1.30470588235294121.109
958161AF2-110 C
Adder
1.19176470588235281.013
938531AE1-072 C
Adder
15.30823529411764713.012
939411AE1-173 C
Adder
73.6611764705882562.612
933981AD1-022 C
Adder
7.3258823529411776.227
966621AG1-532 C
Adder
1.1164705882352940.949
946281AF1-292 C
Adder
1.23176470588235291.047
926071AC1-086 C
Adder
16.83294117647058714.308
3137643SOCKMAN
Adder
0.56941176470588240.484
315051AA1-145 CT1
80/20
4.7034.703
3150451FOUR RIVERC
80/20
3.6073.607
3152261N ANNA2
80/20
26.0926.09
939261AE1-157 C
80/20
13.3213.32
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.86545.865
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.97725.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.1595.159
LAGNLTFEXP_LAGN->PJM
CLTF
8.1928.192
NYPJM->LTFIMP_NY
CLTF
2.8322.832
LGEELTFEXP_LGEE->PJM
CLTF
1.8211.821
WECLTFEXP_WEC->PJM
CLTF
0.9380.938
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.3484.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.51781.517
CPLELTFEXP_CPLE->PJM
CLTF
9.1099.109
TVALTFEXP_TVA->PJM
CLTF
6.5746.574
SIGELTFEXP_SIGE->PJM
CLTF
0.3350.335

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.3 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1082.52
MW Contribution:18.27
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316375AC2-012 C
80/20
0.5120.512
3151081ELIZAR1
80/20
1.2251.225
916191Z1-068 C
80/20
0.0170.017
941101AE2-104 C
Adder
1.23294117647058821.048
316185AD1-033 C
80/20
0.4830.483
944581AF1-123 C
80/20
18.55418.554
316294AC1-161 C
80/20
2.1022.102
3156116Z1-036WIND
80/20
0.260.26
315614AA2-178 C
80/20
0.6260.626
940491AE2-034 C
80/20
0.460.46
940541AE2-040 C
80/20
1.21.2
940481AE2-033 C
80/20
6.7556.755
934501AD1-074 C
80/20
13.58913.589
3156083AA2-088SOLA
80/20
0.4170.417
316365AB2-100 C1
80/20
0.3950.395
943171AE2-346 C
80/20
0.090.09
961941AG1-037 C
80/20
0.2040.204
3151391GASTONA
80/20
1.2541.254
3151411GASTONB
80/20
1.2541.254
316181AB2-040 GEN
80/20
0.5130.513
941031AE2-094 C
80/20
26.65326.653
3151021BRUNSWICKG1
80/20
5.3085.308
3151031BRUNSWICKG2
80/20
5.3085.308
934331AD1-057 C
80/20
1.4711.471
934321AD1-056 C
80/20
2.6372.637
961671AG1-007 C
Adder
0.398823529411764740.339
957481AF2-042 C
80/20
28.07228.072
934621AD1-088 C
80/20
4.3734.373
3151531CLOVER1
80/20
6.2476.247
3151541CLOVER2
80/20
6.1886.188
316283AC2-100 C
80/20
0.5020.502
938821AE1-108 C
Adder
-4.681176470588236-3.979
316349AD2-085 C
Adder
1.08823529411764720.925
942341AE2-247 C
Adder
0.4717647058823530.401
3150991CHESPKB
80/20
0.2740.274
3151091ELIZAR2
80/20
1.2031.203
316246AF1-032 C
80/20
0.1090.109
958161AF2-110 C
Adder
0.50352941176470590.428
316388AE2-253 GEN
80/20
0.7730.773
938531AE1-072 C
80/20
6.9356.935
316320Y1-086 C
80/20
0.0860.086
939411AE1-173 C
80/20
53.71753.717
933981AD1-022 C
80/20
3.5393.539
316318V4-068 C
80/20
0.0320.032
3156021HOLLOMANSOL
80/20
0.7440.744
316174AB2-169_C
80/20
0.4290.429
966621AG1-532 C
80/20
0.5650.565
946281AF1-292 C
80/20
0.6230.623
316011AB1-132 C OP
80/20
0.9580.958
926071AC1-086 C
80/20
8.6598.659
313506AB1-173 C OP
80/20
0.4550.455
3156063AA2-053SOLA
80/20
0.6120.612
943461AF1-017 C
Adder
0.427058823529411770.363
316311AC2-079 C
Adder
1.8517647058823531.574
3150981CHESPKA
80/20
0.1650.165
316036AC1-147 C
80/20
0.140.14
941591AE2-156 C
80/20
6.8286.828
3151101ELIZAR3
80/20
1.241.24
316305AF2-043 C
80/20
0.1340.134
944591AF1-124 C
80/20
18.6218.62
944601AF1-125 C
80/20
18.26818.268
316321Z2-027 C
80/20
0.1430.143
3156056W1-029WIND
80/20
0.3040.304
938771AE1-103 C
Adder
1.1117647058823530.945
934521AD1-076 C
80/20
4.9354.935
934511AD1-075 C
80/20
3.3973.397
3156073AA1-063SOLA
80/20
0.5640.564
960081AF2-299 C
80/20
0.7530.753
316087AB2-174 C
80/20
0.4750.475
3151381ROSEMG2
80/20
0.3930.393
3151361ROSEMG1
80/20
0.840.84
3151261ROARAP2
80/20
0.5630.563
944011AF1-069 C
80/20
8.7098.709
316212AC1-099 C
80/20
0.130.13
3152421Z1-086 GT2
80/20
6.8556.855
3152441Z1-086 ST
80/20
11.93511.935
3152411Z1-086 GT1
80/20
6.8566.856
963041AG1-153 C
80/20
3.6093.609
3151051BRUNSWICKS1
80/20
11.02811.028
3151041BRUNSWICKG3
80/20
5.3085.308
316327AA2-057 C
80/20
0.5450.545
316263AC1-034 C
Adder
2.8352941176470592.41
937481AD2-202 C
80/20
0.1780.178
3151591KERR 2
80/20
0.460.46
964791AG1-342 C
Adder
1.35764705882352941.154
316248AF1-058 C
80/20
0.130.13
936171AD2-023 C
Adder
1.81764705882352941.545
316316AC1-027 C
80/20
0.1220.122
957871AF2-081 C
80/20
3.9453.945
316017AA1-139 ULT1
80/20
0.4260.426
316018AA1-139 ULT2
80/20
0.4260.426
933291AC2-141 C
80/20
12.90812.908
313526AB2-022 C
80/20
0.1480.148
316315AB2-025 C
80/20
0.170.17
3152921DOMTR78
80/20
0.5530.553
316023AB2-100 C2
80/20
0.3950.395
316140AB2-099 C
80/20
0.0390.039
940641AE2-051 C
80/20
11.28211.282
316317KELFORD C
80/20
0.1460.146
932631AC2-084 C
80/20
0.4150.415
3152431Z1-086 GT3
80/20
6.8556.855
316274AC1-208 C
80/20
3.7453.745
316129AC1-054 C
80/20
0.4920.492
3151311EDGECMA
Adder
6.6317647058823535.637
934611AD1-087 C
80/20
0.6150.615
3151611KERR 4
80/20
0.460.46
3151631KERR 6
80/20
0.460.46
3151641KERR 7
80/20
0.460.46
3151621KERR 5
80/20
0.460.46
316336AC2-165 C
Adder
-10.934117647058825-9.294
316222AC1-221 C
80/20
0.6220.622
941011AE2-092 C
Adder
-4.542352941176471-3.861
3151371ROSEMS1
80/20
0.520.52
3137643SOCKMAN
80/20
0.290.29
3151281ROARAP4
80/20
0.5320.532
316210AC1-098 C
80/20
0.390.39
927021AC1-189 C
Adder
3.55058823529411743.018
3151601KERR 3
80/20
0.460.46
3151581KERR 1
80/20
0.1640.164
935171AD1-152 C
80/20
0.6280.628
964241AG1-285 C
Adder
3.8988235294117653.314
962561AG1-105 C
Adder
3.34823529411764742.846
936161AD2-022 C
Adder
3.11647058823529432.649
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.11814.118
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.08110.081
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.7671.767
LAGNLTFEXP_LAGN->PJM
CLTF
3.483.48
NYPJM->LTFIMP_NY
CLTF
0.5550.555
LGEELTFEXP_LGEE->PJM
CLTF
0.550.55
WECLTFEXP_WEC->PJM
CLTF
0.2910.291
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5692.569
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.4944.49
CPLELTFEXP_CPLE->PJM
CLTF
5.3885.388
TVALTFEXP_TVA->PJM
CLTF
2.7252.725
SIGELTFEXP_SIGE->PJM
CLTF
0.1080.108

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.4 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3845.28
MW Contribution:67.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940431AE2-027 C
Adder
18.39647058823529615.637
961611AG1-000B C
Adder
22.90588235294117719.47
942001AE2-212 C
80/20
3.1513.151
3150831SPRUNCA
80/20
13.15813.158
3150841SPRUNCB
80/20
13.15813.158
316072AD1-144 C
80/20
0.4180.418
316375AC2-012 C
80/20
2.0322.032
3151081ELIZAR1
80/20
4.824.82
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
5.0455.045
316185AD1-033 C
80/20
1.8511.851
944581AF1-123 C
80/20
68.97668.976
316294AC1-161 C
80/20
7.5057.505
3156116Z1-036WIND
80/20
0.9810.981
940541AE2-040 C
80/20
4.3564.356
940481AE2-033 C
80/20
24.49624.496
934501AD1-074 C
Adder
50.0317647058823542.527
316365AB2-100 C1
80/20
1.4231.423
961941AG1-037 C
Adder
0.74470588235294120.633
941031AE2-094 C
80/20
63.15563.155
3151021BRUNSWICKG1
80/20
12.91412.914
3151031BRUNSWICKG2
80/20
12.91412.914
934331AD1-057 C
Adder
5.04588235294117654.289
934321AD1-056 C
Adder
9.0458823529411777.689
961671AG1-007 C
Adder
1.34941176470588231.147
957481AF2-042 C
80/20
80.37380.373
934621AD1-088 C
80/20
14.01914.019
3151531CLOVER1
80/20
18.57418.574
3151541CLOVER2
80/20
18.39918.399
316258AE1-075 C
80/20
0.5130.513
958211AF2-115 C
Adder
3.0058823529411772.555
946301AF1-294 C
Adder
4.9423529411764714.201
942461AE2-259 C
Adder
12.99058823529411711.042
316169AC1-164 GEN
Adder
49.0282352941176541.674
3150731STONECA
Adder
9.5788235294117648.142
935161AD1-151 C
Adder
22.80117647058823519.381
3151161SURRY 1
80/20
35.54335.543
316381AD1-082 C
80/20
1.8751.875
316083AB2-161 C
80/20
0.8230.823
316349AD2-085 C
80/20
5.1625.162
942341AE2-247 C
80/20
2.2382.238
3150991CHESPKB
80/20
1.0871.087
3151091ELIZAR2
80/20
4.7364.736
316246AF1-032 C
80/20
0.4280.428
958161AF2-110 C
80/20
2.0582.058
316388AE2-253 GEN
80/20
2.9552.955
938531AE1-072 C
80/20
26.49826.498
316320Y1-086 C
80/20
0.330.33
939411AE1-173 C
80/20
143.49143.49
933981AD1-022 C
Adder
12.98823529411764711.04
966621AG1-532 C
Adder
2.06235294117647071.753
946281AF1-292 C
Adder
2.2752941176470591.934
926071AC1-086 C
Adder
30.83882352941176626.213
3137643SOCKMAN
Adder
1.04352941176470580.887
927021AC1-189 C
Adder
12.14117647058823710.32
964241AG1-285 C
Adder
17.31176470588235414.715
962561AG1-105 C
Adder
12.25882352941176610.42
940551AE2-041 C
Adder
8.4917647058823537.218
3150601CHESTF5
Adder
83.0647058823529570.605
939191AE1-149 C
80/20
15.94215.942
944641AF1-129 C
Adder
144.29529411764705122.651
316240AF1-291 C
Adder
3.0682352941176472.608
943461AF1-017 C
80/20
2.0242.024
316311AC2-079 C
80/20
8.6058.605
3150981CHESPKA
80/20
0.6560.656
316036AC1-147 C
80/20
0.5540.554
941591AE2-156 C
80/20
27.03327.033
3151101ELIZAR3
80/20
4.8814.881
316305AF2-043 C
80/20
0.5240.524
944591AF1-124 C
80/20
69.22169.221
944601AF1-125 C
80/20
67.91467.914
316321Z2-027 C
80/20
0.5460.546
3156056W1-029WIND
80/20
1.1641.164
938771AE1-103 C
80/20
4.3814.381
934521AD1-076 C
Adder
18.1705882352941215.445
934511AD1-075 C
Adder
12.50823529411764710.632
316233AE1-074 C
80/20
3.9163.916
960081AF2-299 C
Adder
2.74941176470588242.337
944011AF1-069 C
80/20
20.63520.635
3152421Z1-086 GT2
80/20
16.53816.538
3152441Z1-086 ST
80/20
28.79528.795
3152411Z1-086 GT1
80/20
16.54216.542
963041AG1-153 C
80/20
8.7798.779
3151051BRUNSWICKS1
80/20
26.8326.83
3151041BRUNSWICKG3
80/20
12.91412.914
316263AC1-034 C
Adder
9.488.058
936261AD2-033 C
Adder
17.81058823529411615.139
316313AB2-026 C
80/20
0.5590.559
959311AF2-222 C
Adder
22.66470588235294419.265
964791AG1-342 C
Adder
4.884.148
961791AG1-021 C
Adder
2.40470588235294122.044
957601AF2-054 C
Adder
2.53058823529411742.151
943471AF1-018 C
Adder
8.4917647058823537.218
944631AF1-128 C
Adder
51.9752941176470644.179
3150921YORKTN3
Adder
165.5670588235294140.732
3151191GRAVEL3
80/20
3.6113.611
3151221GRAVEL6
80/20
3.6533.653
3151201GRAVEL4
80/20
3.6573.657
3151211GRAVEL5
80/20
3.6113.611
316236AE1-162 C
80/20
0.5140.514
3150651CHESTF6
Adder
26.27176470588235422.331
3150851SPRUNCC
80/20
0.2360.236
3150861SPRUNCD
80/20
0.2360.236
3152331SURRY 2
80/20
35.95635.956
316316AC1-027 C
80/20
0.4760.476
957871AF2-081 C
80/20
15.07515.075
316017AA1-139 ULT1
80/20
1.6261.626
316018AA1-139 ULT2
80/20
1.6261.626
933291AC2-141 C
80/20
46.08646.086
313526AB2-022 C
80/20
0.5650.565
316315AB2-025 C
80/20
0.6170.617
316023AB2-100 C2
80/20
1.4231.423
940641AE2-051 C
80/20
27.74527.745
3152431Z1-086 GT3
80/20
16.53816.538
316274AC1-208 C
Adder
13.08588235294117711.123
3151311EDGECMA
Adder
22.1658823529411818.841
316405AF2-144 C
80/20
0.4360.436
3138533PONTONDP
Adder
0.89058823529411770.757
316336AC2-165 C
Adder
14.04941176470588411.942
316303AF2-085
80/20
6.4786.478
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.12565.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.22440.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6237.623
LAGNLTFEXP_LAGN->PJM
CLTF
13.13513.135
NYPJM->LTFIMP_NY
CLTF
3.1863.186
LGEELTFEXP_LGEE->PJM
CLTF
2.5932.593
WECLTFEXP_WEC->PJM
CLTF
1.3381.338
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.9747.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
144.491144.491
CPLELTFEXP_CPLE->PJM
CLTF
16.71416.714
TVALTFEXP_TVA->PJM
CLTF
10.46710.467
SIGELTFEXP_SIGE->PJM
CLTF
0.4870.487

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.79 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4640.88
MW Contribution:225.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
925332AB2-190 E
Adder
11.5352941176470599.805
935162AD1-151 E
Adder
15.43176470588235513.117
927226AC1-216 E
Adder
11.1270588235294129.458
924814AB2-134 E
Adder
18.2270588235294115.493
939191AE1-149 C
Adder
16.1494117647058813.727
944641AF1-129 C
Adder
146.62823529411764124.634
316240AF1-291 C
Adder
3.11647058823529432.649
936666AD2-085 E
Adder
8.5211764705882367.243
942342AE2-247 E
Adder
3.12588235294117662.657
943461AF1-017 C
Adder
2.0482352941176471.741
3143316POE
50/50
2.082.08
932596AC2-079 E
Adder
14.20352941176470712.073
316311AC2-079 C
Adder
8.7047058823529427.399
941591AE2-156 C
50/50
27.33727.337
3151101ELIZAR3
50/50
4.9364.936
944591AF1-124 C
50/50
69.97569.975
944601AF1-125 C
50/50
68.65368.653
919152AA1-139 E1
Adder
6.2317647058823535.297
938532AE1-072 E
Adder
13.96470588235294111.87
3146326AYDLETT TAP
Adder
2.06705882352941161.757
917122Z2-027 E
Adder
2.04352941176470631.737
901082W1-029 E
Adder
48.43294117647058541.168
938771AE1-103 C
Adder
4.4282352941176473.764
3145413WATKINS
Adder
1.04117647058823540.885
920692AA2-178 E
Adder
6.19058823529411755.262
934521AD1-076 C
Adder
18.35647058823529315.603
934511AD1-075 C
Adder
12.6352941176470610.74
316233AE1-074 C
50/50
3.9613.961
920042AA2-088 E OP
Adder
15.88941176470588313.506
960081AF2-299 C
Adder
2.7741176470588242.358
966622AG1-532 E
Adder
1.3870588235294121.179
926072AC1-086 E
Adder
14.16705882352941312.042
3145723EMPORIA
Adder
0.640.544
923573AB1-173 E OP
Adder
4.8588235294117644.13
919692AA2-053 E OP
Adder
6.2482352941176475.311
944011AF1-069 C
50/50
20.76920.769
3152421Z1-086 GT2
50/50
16.64616.646
3152441Z1-086 ST
50/50
28.98428.984
3152411Z1-086 GT1
50/50
16.65116.651
963041AG1-153 C
50/50
8.8378.837
3151051BRUNSWICKS1
50/50
27.00627.006
3151041BRUNSWICKG3
50/50
12.99912.999
940431AE2-027 C
Adder
18.6823529411764715.88
961611AG1-000B C
Adder
23.2270588235294119.743
939192AE1-149 E
Adder
10.7658823529411769.151
939312AE1-162 E
Adder
2.13058823529411741.811
942002AE2-212 E
Adder
2.13058823529411741.811
942001AE2-212 C
Adder
3.19647058823529442.717
3150831SPRUNCA
Adder
13.36352941176470611.359
3150841SPRUNCB
Adder
13.36352941176470611.359
316375AC2-012 C
50/50
2.0552.055
926662AC1-147 E
Adder
2.02235294117647071.719
3151081ELIZAR1
50/50
4.8744.874
916192Z1-068 E
50/50
2.8712.871
916191Z1-068 C
50/50
0.0670.067
957492AF2-043 E
Adder
2.16705882352941171.842
941101AE2-104 C
Adder
5.1011764705882364.336
934065AD1-033 E
50/50
7.6627.662
316185AD1-033 C
50/50
1.8711.871
937226AE2-253 E
Adder
8.9129411764705877.576
944581AF1-123 C
50/50
69.72769.727
316294AC1-161 C
50/50
7.5867.586
940541AE2-040 C
50/50
4.3984.398
923852AB2-025 E
50/50
1.7791.779
940481AE2-033 C
50/50
24.72924.729
940482AE2-033 E
50/50
16.67116.671
934501AD1-074 C
Adder
50.5435294117647142.962
939412AE1-173 E
50/50
96.42796.427
924517AB2-100 E2
Adder
4.3447058823529413.693
961942AG1-037 E
Adder
0.50117647058823530.426
316141AB2-099 E
Adder
0.37647058823529410.32
961941AG1-037 C
Adder
0.7517647058823530.639
923263AB1-132 E OP
Adder
9.0588235294117647.7
316088AB2-174 E
Adder
9.6611764705882348.212
923994AB2-040_E
Adder
9.1117647058823537.745
941031AE2-094 C
50/50
63.56663.566
941032AE2-094 E
50/50
28.4728.47
3151021BRUNSWICKG1
50/50
12.99912.999
3151031BRUNSWICKG2
50/50
12.99912.999
957482AF2-042 E
Adder
53.94941176470588645.857
957481AF2-042 C
Adder
80.9247058823529468.786
934621AD1-088 C
Adder
14.11647058823529511.999
958502AF2-144 E
Adder
1.81.53
923862AB2-026 E
Adder
1.8317647058823531.557
3150921YORKTN3
Adder
168.0623529411765142.853
3150651CHESTF6
Adder
26.6976470588235322.693
946262AF1-291 E
Adder
2.07764705882352941.766
934576AD1-082 E
Adder
6.6517647058823535.654
316084AB2-161 E
Adder
8.3482352941176477.096
3145256KINGFORK
Adder
1.52941176470588251.3
925522AC1-027 E
50/50
1.8591.859
316316AC1-027 C
50/50
0.4810.481
943612AF1-032 E
Adder
1.40941176470588241.198
941102AE2-104 E
Adder
8.1105882352941186.894
3145506HICKORY
50/50
3.3283.328
944602AF1-125 E
50/50
157.162157.162
957872AF2-081 E
Adder
6.53176470588235255.552
957871AF2-081 C
Adder
15.24000000000000212.954
933292AC2-141 E
50/50
19.88619.886
933291AC2-141 C
50/50
46.58646.586
926755AC1-161 E
50/50
19.88619.886
940492AE2-034 E
Adder
4.6423529411764713.946
316315AB2-025 C
50/50
0.6230.623
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
934522AD1-076 E
Adder
9.3564705882352957.953
938552AE1-074 E
50/50
1.9951.995
933982AD1-022 E
Adder
7.1423529411764716.071
943172AE2-346 E
Adder
0.90235294117647060.767
940641AE2-051 C
50/50
27.94427.944
918492AA1-063AE OP
Adder
6.065.151
946282AF1-292 E
Adder
1.53058823529411761.301
944012AF1-069 E
50/50
8.0688.068
3152431Z1-086 GT3
50/50
16.64616.646
934622AD1-088 E
Adder
6.79647058823529455.777
937482AD2-202 E
Adder
1.561.326
934612AD1-087 E
Adder
5.3305882352941174.531
938562AE1-075 E
Adder
1.56235294117647071.328
316336AC2-165 C
Adder
11.2529411764705879.565
940432AE2-027 E
Adder
12.45529411764705910.587
3150731STONECA
Adder
9.735294117647068.275
935161AD1-151 C
Adder
23.14823529411764719.676
934012AD1-025 E
Adder
14.40588235294117712.245
935112AD1-144 E
Adder
1.42000000000000021.207
943462AF1-017 E
Adder
3.34117647058823542.84
316349AD2-085 C
Adder
5.2223529411764714.439
942341AE2-247 C
Adder
2.2635294117647061.924
932046AC2-012 E
50/50
20.00120.001
3151091ELIZAR2
50/50
4.7894.789
958161AF2-110 C
Adder
2.0811764705882351.769
958162AF2-110 E
Adder
3.31058823529411762.814
944582AF1-123 E
50/50
159.668159.668
944592AF1-124 E
50/50
160.246160.246
919153AA1-139 E2
Adder
6.2317647058823535.297
938531AE1-072 C
Adder
26.78823529411764822.77
923832AB2-022 E
Adder
1.8882352941176471.605
913392Y1-086 E
Adder
3.3447058823529412.843
938772AE1-103 E
Adder
6.115294117647065.198
916042Z1-036 E
Adder
43.2517647058823636.764
3145393UNCAMP
Adder
9.1811764705882367.804
934502AD1-074 E
Adder
25.72941176470588321.87
934512AD1-075 E
Adder
6.4317647058823535.467
939411AE1-173 C
50/50
144.64144.64
933981AD1-022 C
Adder
13.12117647058823711.153
900672V4-068 E
Adder
0.53294117647058830.453
918512AA1-065 E OP
Adder
8.2458823529411777.009
924516AB2-100 E1
Adder
4.3447058823529413.693
940642AE2-051 E
50/50
18.62918.629
966621AG1-532 C
Adder
2.0811764705882351.769
960082AF2-299 E
Adder
1.84941176470588251.572
946281AF1-292 C
Adder
2.2964705882352941.952
926071AC1-086 C
Adder
31.12823529411764826.459
3137643SOCKMAN
Adder
1.05294117647058830.895
963042AG1-153 E
50/50
13.25613.256
316303AF2-085
50/50
6.5316.531
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.46965.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.49440.494
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6697.669
LAGNLTFEXP_LAGN->PJM
CLTF
13.22813.228
NYPJM->LTFIMP_NY
CLTF
3.2313.231
LGEELTFEXP_LGEE->PJM
CLTF
2.6092.609
WECLTFEXP_WEC->PJM
CLTF
1.3461.346
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.0368.036
CBM South 2LTFEXP_CBM-S2->PJM
CBM
145.599145.599
CPLELTFEXP_CPLE->PJM
CLTF
16.84316.843
TVALTFEXP_TVA->PJM
CLTF
10.54210.542
O66PJM->LTFIMP_O-066
CMTX_NF
45.24145.241
G-007PJM->LTFIMP_G-007
CMTX_NF
7.1157.115
SIGELTFEXP_SIGE->PJM
CLTF
0.490.49

Details for 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: H3T539_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H3T539_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.41 %
Rating:3532.0 MVA
Rating Type:C
MVA to Mitigate:3758.4
MW Contribution:95.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940431AE2-027 C
Adder
8.392941176470597.134
939192AE1-149 E
Adder
4.6529411764705893.955
942002AE2-212 E
Adder
0.93647058823529420.796
942001AE2-212 C
Adder
1.40470588235294121.194
3150831SPRUNCA
Adder
5.9811764705882355.084
3150841SPRUNCB
Adder
5.9811764705882355.084
926662AC1-147 E
Adder
0.860.731
944581AF1-123 C
Adder
29.47294117647058825.052
939412AE1-173 E
Adder
37.8611764705882432.182
941031AE2-094 C
Adder
24.10352941176470820.488
941032AE2-094 E
Adder
10.7952941176470589.176
958502AF2-144 E
Adder
0.79058823529411770.672
923862AB2-026 E
Adder
0.80470588235294130.684
316192AB2-158 C
50/50
1.8041.804
3151801S ANNAS2
50/50
1.0421.042
3151791S ANNAG2
50/50
2.0282.028
3151771S ANNAG1
50/50
2.0282.028
3151781S ANNAS1
50/50
1.0421.042
966001AG1-469 C
50/50
1.6461.646
926740AC1-158 E2
50/50
17.30117.301
925672AC1-043 E
50/50
12.45212.452
3150301M RUN C
50/50
5.6625.662
3150281M RUN A
50/50
5.6655.665
3150221REMNGT2
50/50
5.0565.056
316411AF1-147_GEN1
Adder
-4.564705882352941-3.88
940432AE2-027 E
Adder
5.5952941176470594.756
3150731STONECA
Adder
4.46823529411764753.798
932046AC2-012 E
Adder
8.5035294117647067.228
944582AF1-123 E
Adder
67.4905882352941157.367
944592AF1-124 E
Adder
67.7341176470588257.574
939411AE1-173 C
Adder
56.79058823529411648.272
940642AE2-051 E
Adder
7.1458823529411766.074
3152261N ANNA2
50/50
28.11228.112
925022AB2-158 E
50/50
4.7944.794
316044AC1-158 C1
50/50
6.6156.615
926486AC1-120 E
50/50
4.0694.069
934861AD1-115 C
50/50
3.8163.816
939222AE1-153 E
50/50
11.58111.581
923892AB2-029 E
50/50
2.5092.509
3150291M RUN B
50/50
5.625.62
963031AG1-152 C
50/50
8.228.22
316415AF1-147_GEN2
Adder
-4.564705882352941-3.88
3150651CHESTF6
Adder
12.12823529411764610.309
946262AF1-291 E
Adder
0.93647058823529420.796
944602AF1-125 E
Adder
66.4305882352941256.466
933292AC2-141 E
Adder
8.4282352941176477.164
933291AC2-141 C
Adder
19.74352941176470516.782
926755AC1-161 E
Adder
8.4282352941176477.164
938552AE1-074 E
Adder
0.82588235294117640.702
940641AE2-051 C
Adder
10.7188235294117669.111
944012AF1-069 E
Adder
3.062.601
938562AE1-075 E
Adder
0.68588235294117650.583
3152251N ANNA1
50/50
28.128.1
926004AC1-076_E
50/50
4.5534.553
316254AC1-120 C
50/50
7.97.9
316257AC1-043 C
50/50
7.6327.632
934862AD1-115 E
50/50
6.2266.226
316267AC1-143 C
50/50
8.4218.421
926615AC1-143 E
50/50
3.8433.843
3150211REMNGT1
50/50
5.0095.009
3150231REMNGT3
50/50
5.6895.689
925332AB2-190 E
Adder
5.2282352941176474.444
939191AE1-149 C
Adder
6.97999999999999955.933
944641AF1-129 C
Adder
66.6117647058823556.62
316240AF1-291 C
Adder
1.40470588235294121.194
3143316POE
Adder
0.88235294117647060.75
941591AE2-156 C
Adder
11.6200000000000019.877
944591AF1-124 C
Adder
29.5776470588235325.141
944601AF1-125 C
Adder
29.01882352941176524.666
316233AE1-074 C
Adder
1.63882352941176481.393
944011AF1-069 C
Adder
7.8752941176470596.694
966002AG1-469 E
50/50
0.8230.823
316045AC1-158 C2
50/50
6.6156.615
926739AC1-158 E1
50/50
17.30117.301
316164AC1-076_C
50/50
0.7950.795
316170AC1-121 C
50/50
2.7132.713
926502AC1-121 E
50/50
1.2771.277
939221AE1-153 C
50/50
17.37117.371
316006AB2-029 C
50/50
0.2550.255
3150241REMNGT4
50/50
5.0775.077
963032AG1-152 E
50/50
12.3312.33
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.67939.679
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.88221.882
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.4114.411
LAGNLTFEXP_LAGN->PJM
CLTF
6.8256.825
NYPJM->LTFIMP_NY
CLTF
2.8362.836
LGEELTFEXP_LGEE->PJM
CLTF
1.5711.571
WECLTFEXP_WEC->PJM
CLTF
0.8110.811
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.4753.475
CBM South 2LTFEXP_CBM-S2->PJM
CBM
65.85665.856
CPLELTFEXP_CPLE->PJM
CLTF
7.2777.277
TVALTFEXP_TVA->PJM
CLTF
5.4825.482
O66PJM->LTFIMP_O-066
CMTX_NF
40.65740.657
G-007PJM->LTFIMP_G-007
CMTX_NF
6.4046.404
SIGELTFEXP_SIGE->PJM
CLTF
0.2880.288

Details for 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T539_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T539_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.89 %
Rating:3532.0 MVA
Rating Type:C
MVA to Mitigate:3739.91
MW Contribution:95.27
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940431AE2-027 C
Adder
8.3764705882352957.12
939192AE1-149 E
Adder
4.6435294117647063.947
942002AE2-212 E
Adder
0.93411764705882360.794
942001AE2-212 C
Adder
1.40235294117647061.192
3150831SPRUNCA
Adder
5.9694117647058835.074
3150841SPRUNCB
Adder
5.9694117647058835.074
944581AF1-123 C
Adder
29.4152941176470625.003
939412AE1-173 E
Adder
37.7882352941176532.12
941031AE2-094 C
Adder
24.0576470588235320.449
941032AE2-094 E
Adder
10.775294117647069.159
958502AF2-144 E
Adder
0.78941176470588240.671
923862AB2-026 E
Adder
0.80352941176470590.683
316192AB2-158 C
50/50
1.8011.801
3151801S ANNAS2
50/50
1.0411.041
3151791S ANNAG2
50/50
2.0262.026
3151771S ANNAG1
50/50
2.0262.026
3151781S ANNAS1
50/50
1.0411.041
966001AG1-469 C
50/50
1.6441.644
926740AC1-158 E2
50/50
17.27317.273
925672AC1-043 E
50/50
12.43912.439
3150301M RUN C
50/50
5.6595.659
3150281M RUN A
50/50
5.6625.662
3150221REMNGT2
50/50
5.0545.054
316411AF1-147_GEN1
Adder
-4.552941176470588-3.87
940432AE2-027 E
Adder
5.5835294117647064.746
3150731STONECA
Adder
4.4588235294117653.79
944582AF1-123 E
Adder
67.3588235294117757.255
944592AF1-124 E
Adder
67.6035294117647157.463
939411AE1-173 C
Adder
56.6811764705882448.179
940642AE2-051 E
Adder
7.1317647058823546.062
3152261N ANNA2
50/50
28.06128.061
925022AB2-158 E
50/50
4.7874.787
316044AC1-158 C1
50/50
6.6046.604
926486AC1-120 E
50/50
4.0644.064
934861AD1-115 C
50/50
3.8123.812
939222AE1-153 E
50/50
11.57311.573
923892AB2-029 E
50/50
2.5082.508
3150291M RUN B
50/50
5.6175.617
963031AG1-152 C
50/50
8.2178.217
316415AF1-147_GEN2
Adder
-4.552941176470588-3.87
3150651CHESTF6
Adder
12.10470588235294210.289
946262AF1-291 E
Adder
0.93411764705882360.794
944602AF1-125 E
Adder
66.3023529411764756.357
933292AC2-141 E
Adder
8.4117647058823537.15
933291AC2-141 C
Adder
19.7047058823529416.749
926755AC1-161 E
Adder
8.4117647058823537.15
938552AE1-074 E
Adder
0.82470588235294120.701
940641AE2-051 C
Adder
10.6976470588235299.093
944012AF1-069 E
Adder
3.05411764705882362.596
938562AE1-075 E
Adder
0.68470588235294120.582
3152251N ANNA1
50/50
28.04928.049
926004AC1-076_E
50/50
4.5464.546
316254AC1-120 C
50/50
7.897.89
316257AC1-043 C
50/50
7.6247.624
934862AD1-115 E
50/50
6.2196.219
316267AC1-143 C
50/50
8.4158.415
926615AC1-143 E
50/50
3.843.84
3150211REMNGT1
50/50
5.0075.007
3150231REMNGT3
50/50
5.6875.687
925332AB2-190 E
Adder
5.21764705882352954.435
939191AE1-149 C
Adder
6.9658823529411775.921
944641AF1-129 C
Adder
66.4811764705882456.509
316240AF1-291 C
Adder
1.40235294117647061.192
3143316POE
Adder
0.880.748
941591AE2-156 C
Adder
11.5976470588235319.858
944591AF1-124 C
Adder
29.5225.092
944601AF1-125 C
Adder
28.9623529411764724.618
316233AE1-074 C
Adder
1.63647058823529411.391
944011AF1-069 C
Adder
7.8611764705882366.682
966002AG1-469 E
50/50
0.8220.822
316045AC1-158 C2
50/50
6.6046.604
926739AC1-158 E1
50/50
17.27317.273
316164AC1-076_C
50/50
0.7940.794
316170AC1-121 C
50/50
2.712.71
926502AC1-121 E
50/50
1.2751.275
939221AE1-153 C
50/50
17.35917.359
316006AB2-029 C
50/50
0.2540.254
3150241REMNGT4
50/50
5.0755.075
963032AG1-152 E
50/50
12.32512.325
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.59339.593
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.83721.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.4014.401
LAGNLTFEXP_LAGN->PJM
CLTF
6.8116.811
NYPJM->LTFIMP_NY
CLTF
2.8312.831
LGEELTFEXP_LGEE->PJM
CLTF
1.5681.568
WECLTFEXP_WEC->PJM
CLTF
0.8090.809
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.4683.468
CBM South 2LTFEXP_CBM-S2->PJM
CBM
65.72665.726
CPLELTFEXP_CPLE->PJM
CLTF
7.2637.263
TVALTFEXP_TVA->PJM
CLTF
5.4715.471
O66PJM->LTFIMP_O-066
CMTX_NF
40.58140.581
G-007PJM->LTFIMP_G-007
CMTX_NF
6.3926.392
SIGELTFEXP_SIGE->PJM
CLTF
0.2870.287

Details for 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 539_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 539_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.44 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3266.75
MW Contribution:28.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940431AE2-027 C
Adder
8.2211764705882376.988
942001AE2-212 C
Adder
1.37647058823529411.17
3150831SPRUNCA
80/20
5.865.86
3150841SPRUNCB
80/20
5.865.86
944581AF1-123 C
Adder
28.8729411764705924.542
316294AC1-161 C
80/20
3.153.15
941031AE2-094 C
Adder
23.6220.077
316192AB2-158 C
80/20
1.7771.777
3151801S ANNAS2
80/20
1.0291.029
3151791S ANNAG2
80/20
2.0032.003
3151771S ANNAG1
80/20
2.0032.003
3151781S ANNAS1
80/20
1.0291.029
3151761LOISA E
80/20
4.3884.388
966001AG1-469 C
80/20
1.6251.625
208900BRIS G1
80/20
-3.13-3.13
939191AE1-149 C
Adder
6.837647058823535.812
944641AF1-129 C
Adder
65.252941176470655.465
316240AF1-291 C
Adder
1.37647058823529411.17
944591AF1-124 C
Adder
28.97647058823529424.63
944601AF1-125 C
Adder
28.4282352941176524.164
316233AE1-074 C
80/20
1.6061.606
944011AF1-069 C
Adder
7.71764705882352956.56
3151751LOISA D
80/20
2.1522.152
3151731LOISA B
80/20
2.1522.152
316045AC1-158 C2
80/20
6.5026.502
316164AC1-076_C
80/20
0.7820.782
316170AC1-121 C
80/20
2.6782.678
939221AE1-153 C
80/20
17.24817.248
316006AB2-029 C
80/20
0.2530.253
3150241REMNGT4
80/20
5.0575.057
3150651CHESTF6
Adder
11.88117647058823510.099
3150851SPRUNCC
80/20
0.1050.105
3150861SPRUNCD
80/20
0.1050.105
933291AC2-141 C
80/20
19.34119.341
940641AE2-051 C
80/20
10.50310.503
3152251N ANNA1
80/20
27.56627.566
3151721LOISA A
80/20
2.1412.141
316254AC1-120 C
80/20
7.7987.798
316257AC1-043 C
80/20
7.5467.546
316267AC1-143 C
80/20
8.3628.362
3150211REMNGT1
80/20
4.994.99
3150231REMNGT3
80/20
5.6665.666
208901BRIS G2
80/20
-3.703-3.703
3150301M RUN C
80/20
5.635.63
3150281M RUN A
80/20
5.6335.633
3150221REMNGT2
80/20
5.0365.036
316411AF1-147_GEN1
Adder
-4.444705882352942-3.778
3150731STONECA
Adder
4.3764705882352953.72
939411AE1-173 C
80/20
55.64555.645
3152261N ANNA2
80/20
27.57827.578
3151741LOISA C
80/20
2.1522.152
316044AC1-158 C1
80/20
6.5026.502
934861AD1-115 C
80/20
3.7733.773
3150291M RUN B
80/20
5.5895.589
963031AG1-152 C
80/20
8.1888.188
316415AF1-147_GEN2
Adder
-4.444705882352942-3.778
316303AF2-085
80/20
2.4722.472
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.78338.783
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.40921.409
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.3134.313
LAGNLTFEXP_LAGN->PJM
CLTF
6.6796.679
NYPJM->LTFIMP_NY
CLTF
2.7812.781
LGEELTFEXP_LGEE->PJM
CLTF
1.5361.536
WECLTFEXP_WEC->PJM
CLTF
0.7930.793
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.4043.404
CBM South 2LTFEXP_CBM-S2->PJM
CBM
64.50164.501
CPLELTFEXP_CPLE->PJM
CLTF
7.1287.128
TVALTFEXP_TVA->PJM
CLTF
5.3665.366
SIGELTFEXP_SIGE->PJM
CLTF
0.2810.281

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.63 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3595.09
MW Contribution:31.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
942001AE2-212 C
Adder
1.40235294117647061.192
941101AE2-104 C
Adder
2.35411764705882342.001
944581AF1-123 C
Adder
32.0470588235294127.24
940541AE2-040 C
80/20
2.2982.298
940481AE2-033 C
80/20
12.91312.913
934501AD1-074 C
Adder
24.38588235294117720.728
316365AB2-100 C1
80/20
0.7450.745
961941AG1-037 C
Adder
0.37294117647058830.317
941031AE2-094 C
80/20
37.11337.113
3147043LAWRENC
80/20
0.240.24
3151021BRUNSWICKG1
80/20
7.5577.557
3151031BRUNSWICKG2
80/20
7.5577.557
934331AD1-057 C
Adder
2.6258823529411772.232
934321AD1-056 C
Adder
4.7070588235294134.001
961671AG1-007 C
Adder
0.69647058823529410.592
957481AF2-042 C
80/20
47.06247.062
934621AD1-088 C
80/20
8.2538.253
3151531CLOVER1
80/20
10.82910.829
3151541CLOVER2
80/20
10.72710.727
316258AE1-075 C
80/20
0.320.32
958211AF2-115 C
80/20
1.7961.796
946301AF1-294 C
80/20
2.9542.954
942461AE2-259 C
80/20
7.9867.986
316192AB2-158 C
80/20
4.3254.325
3151801S ANNAS2
80/20
1.6761.676
3151791S ANNAG2
80/20
3.2623.262
3151771S ANNAG1
80/20
3.2623.262
3151781S ANNAS1
80/20
1.6761.676
3151761LOISA E
80/20
6.8276.827
966001AG1-469 C
80/20
2.3822.382
208900BRIS G1
80/20
-2.405-2.405
208901BRIS G2
80/20
-2.846-2.846
316349AD2-085 C
Adder
2.3964705882352942.037
939191AE1-149 C
Adder
7.2929411764705886.199
943461AF1-017 C
Adder
0.94000000000000010.799
316311AC2-079 C
Adder
3.99647058823529383.397
941591AE2-156 C
Adder
12.43294117647058910.568
944591AF1-124 C
Adder
32.1611764705882427.337
944601AF1-125 C
Adder
31.55411764705882826.821
938771AE1-103 C
Adder
2.10235294117647081.787
934521AD1-076 C
Adder
8.8564705882352937.528
934511AD1-075 C
Adder
6.0964705882352945.182
316233AE1-074 C
80/20
2.0672.067
960081AF2-299 C
80/20
1.4551.455
316087AB2-174 C
80/20
0.9080.908
944011AF1-069 C
80/20
12.12612.126
3152421Z1-086 GT2
80/20
9.699.69
3152441Z1-086 ST
80/20
16.87216.872
3152411Z1-086 GT1
80/20
9.6939.693
963041AG1-153 C
80/20
5.1375.137
3151051BRUNSWICKS1
80/20
15.69915.699
3151041BRUNSWICKG3
80/20
7.5577.557
316263AC1-034 C
Adder
4.9470588235294124.205
937481AD2-202 C
80/20
0.3090.309
316239AB2-077 C O1
80/20
0.2590.259
936261AD2-033 C
80/20
10.37510.375
316313AB2-026 C
80/20
0.3480.348
959311AF2-222 C
80/20
13.30313.303
964791AG1-342 C
Adder
2.77294117647058872.357
961791AG1-021 C
80/20
1.4371.437
3151751LOISA D
80/20
3.3493.349
3151731LOISA B
80/20
3.3493.349
316045AC1-158 C2
80/20
18.51718.517
316164AC1-076_C
80/20
1.0891.089
316170AC1-121 C
80/20
2.952.95
957871AF2-081 C
Adder
7.0094117647058835.958
933291AC2-141 C
Adder
21.0423529411764717.886
316315AB2-025 C
80/20
0.3250.325
316023AB2-100 C2
80/20
0.7450.745
940641AE2-051 C
80/20
15.75815.758
3152431Z1-086 GT3
80/20
9.699.69
316274AC1-208 C
Adder
6.785.763
3151311EDGECMA
Adder
11.569.826
934611AD1-087 C
80/20
1.0661.066
313527AB2-043 C
80/20
0.4090.409
316237AB2-079 C O1
80/20
0.2590.259
316131AB2-060 C
80/20
1.1781.178
316405AF2-144 C
80/20
0.2720.272
942341AE2-247 C
Adder
1.03882352941176470.883
958161AF2-110 C
Adder
0.96117647058823530.817
938531AE1-072 C
Adder
12.33529411764705810.485
939411AE1-173 C
80/20
78.11378.113
933981AD1-022 C
Adder
6.3599999999999995.406
966621AG1-532 C
80/20
1.0911.091
946281AF1-292 C
80/20
1.2041.204
926071AC1-086 C
Adder
15.98823529411764713.59
3137643SOCKMAN
Adder
0.54588235294117650.464
927021AC1-189 C
Adder
6.225.287
935171AD1-152 C
80/20
1.0991.099
316238AB2-078 C O1
80/20
0.2590.259
964241AG1-285 C
80/20
9.9749.974
316034AC1-036 C
80/20
0.1860.186
962561AG1-105 C
Adder
6.9729411764705885.927
3144293JTRSVLE
80/20
0.3290.329
3152261N ANNA2
80/20
103.963103.963
3151741LOISA C
80/20
3.3493.349
316044AC1-158 C1
80/20
18.51718.517
934861AD1-115 C
80/20
3.3063.306
3138533PONTONDP
80/20
0.5320.532
316336AC2-165 C
80/20
8.8748.874
3152251N ANNA1
80/20
103.92103.92
3151721LOISA A
80/20
3.3313.331
316254AC1-120 C
80/20
8.5918.591
316257AC1-043 C
80/20
6.6126.612
316303AF2-085
80/20
3.8763.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.20919.209
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.12316.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.6672.667
LAGNLTFEXP_LAGN->PJM
CLTF
5.7055.705
NYPJM->LTFIMP_NY
CLTF
2.292.29
LGEELTFEXP_LGEE->PJM
CLTF
0.8350.835
WECLTFEXP_WEC->PJM
CLTF
0.4130.413
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2194.219
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.82173.821
CPLELTFEXP_CPLE->PJM
CLTF
8.8538.853
TVALTFEXP_TVA->PJM
CLTF
4.5224.522
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.86 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3570.05
MW Contribution:33.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940431AE2-027 C
Adder
8.3129411764705887.066
961611AG1-000B C
Adder
10.3129411764705888.766
942001AE2-212 C
Adder
1.49882352941176471.274
3150831SPRUNCA
Adder
6.1623529411764715.238
3150841SPRUNCB
Adder
6.1623529411764715.238
941101AE2-104 C
Adder
2.50470588235294132.129
944581AF1-123 C
Adder
34.0988235294117728.984
940541AE2-040 C
80/20
2.4262.426
940481AE2-033 C
80/20
13.63113.631
934501AD1-074 C
Adder
25.86823529411764621.988
316365AB2-100 C1
80/20
0.7870.787
939191AE1-149 C
Adder
7.7752941176470596.609
944641AF1-129 C
Adder
63.6988235294117654.144
316240AF1-291 C
Adder
1.37882352941176461.172
943461AF1-017 C
Adder
1.00.85
316311AC2-079 C
Adder
4.2541176470588233.616
941591AE2-156 C
Adder
13.23882352941176611.253
944591AF1-124 C
Adder
34.2229.087
944601AF1-125 C
Adder
33.5741176470588328.538
938771AE1-103 C
Adder
2.2329411764705881.898
934521AD1-076 C
Adder
9.3952941176470587.986
934511AD1-075 C
Adder
6.46705882352941155.497
316233AE1-074 C
80/20
2.1822.182
960081AF2-299 C
80/20
1.5351.535
316087AB2-174 C
80/20
0.9580.958
944011AF1-069 C
80/20
12.71412.714
3152421Z1-086 GT2
80/20
10.16110.161
961941AG1-037 C
Adder
0.39411764705882360.335
316181AB2-040 GEN
80/20
1.0311.031
941031AE2-094 C
80/20
38.91138.911
3147043LAWRENC
80/20
0.2530.253
3151021BRUNSWICKG1
80/20
7.9247.924
3151031BRUNSWICKG2
80/20
7.9247.924
934331AD1-057 C
Adder
2.7741176470588242.358
934321AD1-056 C
Adder
4.9729411764705894.227
961671AG1-007 C
Adder
0.73647058823529410.626
957481AF2-042 C
80/20
49.31549.315
934621AD1-088 C
80/20
8.6418.641
3151531CLOVER1
80/20
11.34911.349
3151541CLOVER2
80/20
11.24311.243
316258AE1-075 C
80/20
0.3330.333
958211AF2-115 C
80/20
1.8751.875
946301AF1-294 C
80/20
3.0833.083
942461AE2-259 C
Adder
8.3117647058823547.065
316192AB2-158 C
80/20
4.2764.276
3151801S ANNAS2
80/20
1.5631.563
3151791S ANNAG2
80/20
3.0413.041
3151771S ANNAG1
80/20
3.0413.041
3151781S ANNAS1
80/20
1.5631.563
3151761LOISA E
80/20
6.316.31
966001AG1-469 C
80/20
1.9821.982
208900BRIS G1
80/20
-2.414-2.414
208901BRIS G2
80/20
-2.857-2.857
316349AD2-085 C
Adder
2.5505882352941182.168
942341AE2-247 C
Adder
1.10588235294117650.94
958161AF2-110 C
Adder
1.02235294117647070.869
938531AE1-072 C
Adder
13.12352941176470511.155
939411AE1-173 C
80/20
82.26382.263
933981AD1-022 C
Adder
6.7447058823529415.733
966621AG1-532 C
80/20
1.1511.151
946281AF1-292 C
80/20
1.2711.271
926071AC1-086 C
Adder
16.8929411764705914.359
313506AB1-173 C OP
80/20
0.9150.915
3137643SOCKMAN
Adder
0.57647058823529410.49
927021AC1-189 C
Adder
6.5788235294117645.592
935171AD1-152 C
80/20
1.1531.153
316238AB2-078 C O1
80/20
0.2720.272
964241AG1-285 C
80/20
10.44910.449
316034AC1-036 C
80/20
0.1950.195
962561AG1-105 C
Adder
7.3152941176470596.218
3144293JTRSVLE
80/20
0.3440.344
3152261N ANNA2
80/20
106.999106.999
3151741LOISA C
80/20
3.0953.095
3152441Z1-086 ST
80/20
17.69217.692
3152411Z1-086 GT1
80/20
10.16410.164
963041AG1-153 C
80/20
5.3875.387
3151051BRUNSWICKS1
80/20
16.46316.463
3151041BRUNSWICKG3
80/20
7.9247.924
316263AC1-034 C
Adder
5.2270588235294114.443
937481AD2-202 C
80/20
0.3240.324
316239AB2-077 C O1
80/20
0.2720.272
936261AD2-033 C
80/20
10.85610.856
316313AB2-026 C
80/20
0.3630.363
959311AF2-222 C
80/20
13.90913.909
964791AG1-342 C
Adder
2.9105882352941182.474
961791AG1-021 C
80/20
1.51.5
3151751LOISA D
80/20
3.0953.095
3151731LOISA B
80/20
3.0953.095
3150651CHESTF6
Adder
11.5976470588235319.858
957871AF2-081 C
Adder
7.4588235294117656.34
933291AC2-141 C
Adder
22.41294117647058619.051
316315AB2-025 C
80/20
0.3440.344
316023AB2-100 C2
80/20
0.7870.787
940641AE2-051 C
80/20
16.55416.554
3152431Z1-086 GT3
80/20
10.16110.161
316274AC1-208 C
Adder
7.1635294117647066.089
3151311EDGECMA
Adder
12.21411764705882410.382
934611AD1-087 C
80/20
1.1171.117
313527AB2-043 C
80/20
0.4290.429
316237AB2-079 C O1
80/20
0.2720.272
316131AB2-060 C
80/20
1.2351.235
316405AF2-144 C
80/20
0.2830.283
3138533PONTONDP
80/20
0.5550.555
316336AC2-165 C
80/20
9.2269.226
3152251N ANNA1
80/20
106.954106.954
3151721LOISA A
80/20
3.0793.079
316303AF2-085
80/20
4.064.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.24822.248
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.65817.658
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.9882.988
LAGNLTFEXP_LAGN->PJM
CLTF
6.1746.174
NYPJM->LTFIMP_NY
CLTF
2.2912.291
LGEELTFEXP_LGEE->PJM
CLTF
0.9480.948
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4574.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
78.26878.268
CPLELTFEXP_CPLE->PJM
CLTF
9.3529.352
TVALTFEXP_TVA->PJM
CLTF
4.8954.895
SIGELTFEXP_SIGE->PJM
CLTF
0.1860.186

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.14 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4339.53
MW Contribution:109.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
939191AE1-149 C
Adder
7.7200000000000016.562
936666AD2-085 E
Adder
4.1329411764705883.513
942342AE2-247 E
Adder
1.5164705882352941.289
943461AF1-017 C
Adder
0.99294117647058820.844
3143316POE
Adder
1.04235294117647070.886
932596AC2-079 E
Adder
6.8929411764705895.859
316311AC2-079 C
Adder
4.2247058823529413.591
941591AE2-156 C
Adder
13.14823529411764711.176
944591AF1-124 C
Adder
33.9870588235294128.889
944601AF1-125 C
Adder
33.3447058823529428.343
919152AA1-139 E1
Adder
3.02941176470588272.575
938532AE1-072 E
Adder
6.7941176470588245.775
3146326AYDLETT TAP
Adder
1.00588235294117640.855
917122Z2-027 E
Adder
1.00.85
901082W1-029 E
Adder
23.76705882352941420.202
938771AE1-103 C
Adder
2.21764705882352951.885
3145413WATKINS
Adder
0.52941176470588240.45
920692AA2-178 E
Adder
3.1141176470588232.647
934521AD1-076 C
Adder
9.3258823529411777.927
934511AD1-075 C
Adder
6.425.457
316233AE1-074 C
Adder
2.17058823529411751.845
920042AA2-088 E OP
Adder
8.226.987
960081AF2-299 C
Adder
1.52470588235294141.296
966622AG1-532 E
Adder
0.76235294117647070.648
926072AC1-086 E
Adder
7.6341176470588236.489
3145723EMPORIA
Adder
0.350588235294117640.298
923573AB1-173 E OP
Adder
2.6529411764705882.255
919692AA2-053 E OP
Adder
3.36117647058823542.857
944011AF1-069 C
50/50
12.65212.652
926206AC1-098 E
Adder
2.86705882352941142.437
963041AG1-153 C
Adder
5.3588235294117644.555
925785AC1-054 E
Adder
2.79764705882352962.378
316263AC1-034 C
Adder
5.1835294117647064.406
922923AB1-081 E OP
Adder
2.9105882352941182.474
936261AD2-033 C
Adder
10.782352941176479.165
962562AG1-105 E
Adder
4.842352941176474.116
959311AF2-222 C
Adder
13.8152941176470611.743
964791AG1-342 C
Adder
2.88941176470588262.456
961791AG1-021 C
Adder
1.48941176470588241.266
3147133PAMPLIN
Adder
0.82352941176470580.7
942462AE2-259 E
Adder
5.5047058823529414.679
927264AC1-222 E
Adder
3.20470588235294152.724
924032AB2-045 E
Adder
1.08588235294117650.923
3151751LOISA D
50/50
3.1063.106
3151731LOISA B
50/50
3.1063.106
966002AG1-469 E
50/50
1.0031.003
316045AC1-158 C2
50/50
19.56819.568
926739AC1-158 E1
50/50
51.18251.182
939192AE1-149 E
Adder
5.1470588235294124.375
939312AE1-162 E
Adder
0.97647058823529410.83
942002AE2-212 E
Adder
0.99176470588235290.843
942001AE2-212 C
Adder
1.48705882352941181.264
3150831SPRUNCA
Adder
6.117647058823535.2
3150841SPRUNCB
Adder
6.117647058823535.2
926662AC1-147 E
Adder
0.97176470588235290.826
916192Z1-068 E
Adder
1.38588235294117631.178
957492AF2-043 E
Adder
1.05294117647058830.895
941101AE2-104 C
Adder
2.48705882352941152.114
934065AD1-033 E
Adder
3.70941176470588243.153
937226AE2-253 E
Adder
4.3282352941176473.679
944581AF1-123 C
Adder
33.8670588235294128.787
940541AE2-040 C
Adder
2.4117647058823532.05
923852AB2-025 E
Adder
0.97529411764705880.829
940481AE2-033 C
Adder
13.54823529411764811.516
940482AE2-033 E
Adder
9.1341176470588247.764
934501AD1-074 C
Adder
25.6821.828
939412AE1-173 E
Adder
54.5505882352941246.368
924517AB2-100 E2
Adder
2.36470588235294082.01
961942AG1-037 E
Adder
0.26117647058823530.222
316141AB2-099 E
Adder
0.195294117647058840.166
961941AG1-037 C
Adder
0.391764705882352960.333
923263AB1-132 E OP
Adder
4.8811764705882354.149
316088AB2-174 E
Adder
5.2858823529411774.493
923994AB2-040_E
Adder
4.9741176470588234.228
941031AE2-094 C
50/50
38.72138.721
941032AE2-094 E
50/50
17.34217.342
934331AD1-057 C
Adder
2.75294117647058822.34
934322AD1-056 E
Adder
2.6764705882352942.275
934332AD1-057 E
Adder
1.43411764705882371.219
934321AD1-056 C
Adder
4.9352941176470594.195
927022AC1-189 E
Adder
3.25058823529411762.763
961672AG1-007 E
Adder
0.414117647058823530.352
961671AG1-007 C
Adder
0.73058823529411760.621
957482AF2-042 E
Adder
32.6894117647058927.786
957481AF2-042 C
Adder
49.0341176470588341.679
925595AC1-034 E
Adder
3.91058823529411773.324
934621AD1-088 C
Adder
8.5905882352941177.302
935172AD1-152 E
Adder
4.7270588235294114.018
924322AB2-079 E O1
Adder
1.10588235294117650.94
924312AB2-078 E O1
Adder
1.10588235294117650.94
936262AD2-033 E
Adder
7.1882352941176476.11
958502AF2-144 E
Adder
1.15294117647058810.98
923862AB2-026 E
Adder
1.17294117647058820.997
925612AC1-036 E
Adder
0.7117647058823530.605
926274AC1-105 E
Adder
2.1788235294117651.852
958211AF2-115 C
Adder
1.86235294117647051.583
946301AF1-294 C
Adder
3.06235294117647072.603
946302AF1-294 E
Adder
2.59294117647058852.204
943902AF1-058 E
Adder
1.04352941176470580.887
942461AE2-259 C
Adder
8.257647058823537.019
316192AB2-158 C
50/50
4.2784.278
3151801S ANNAS2
50/50
1.5681.568
3151791S ANNAG2
50/50
3.0513.051
3151771S ANNAG1
50/50
3.0513.051
3151781S ANNAS1
50/50
1.5681.568
3151761LOISA E
50/50
6.3326.332
966001AG1-469 C
50/50
2.0062.006
926740AC1-158 E2
50/50
51.18251.182
208900BRIS G1
50/50
-2.489-2.489
208901BRIS G2
50/50
-2.946-2.946
935112AD1-144 E
Adder
0.67176470588235290.571
943462AF1-017 E
Adder
1.621.377
316349AD2-085 C
Adder
2.53294117647058852.153
942341AE2-247 C
Adder
1.09764705882352940.933
932046AC2-012 E
Adder
9.6164705882352938.174
958161AF2-110 C
Adder
1.0152941176470590.863
958162AF2-110 E
Adder
1.61411764705882371.372
944582AF1-123 E
Adder
77.5517647058823565.919
944592AF1-124 E
Adder
77.8317647058823566.157
919153AA1-139 E2
Adder
3.02941176470588272.575
938531AE1-072 C
Adder
13.03294117647058811.078
923832AB2-022 E
Adder
0.92235294117647060.784
913392Y1-086 E
Adder
1.63411764705882371.389
938772AE1-103 E
Adder
3.0611764705882352.602
916042Z1-036 E
Adder
21.48117647058823518.259
3145393UNCAMP
Adder
4.622352941176473.929
934502AD1-074 E
Adder
13.07176470588235311.111
934512AD1-075 E
Adder
3.26823529411764732.778
939411AE1-173 C
Adder
81.8247058823529469.551
933981AD1-022 C
Adder
6.6952941176470595.691
900672V4-068 E
Adder
0.276470588235294130.235
918512AA1-065 E OP
Adder
4.2588235294117653.62
924516AB2-100 E1
Adder
2.36470588235294082.01
940642AE2-051 E
50/50
10.98110.981
966621AG1-532 C
Adder
1.1435294117647060.972
960082AF2-299 E
Adder
1.01647058823529420.864
946281AF1-292 C
Adder
1.26235294117647071.073
926071AC1-086 C
Adder
16.77411764705882314.258
3137643SOCKMAN
Adder
0.57294117647058830.487
963042AG1-153 E
Adder
8.0388235294117656.833
918532AA1-067 E
Adder
0.55176470588235290.469
927021AC1-189 C
Adder
6.5247058823529425.546
919710AA2-057 E
Adder
3.1117647058823532.645
924152AB2-059 E OP
Adder
4.122352941176473.504
924022AB2-043 E O1
Adder
4.2929411764705883.649
924302AB2-077 E O1
Adder
1.10588235294117650.94
964241AG1-285 C
Adder
10.3776470588235298.821
3147223TWITTYS
Adder
0.78941176470588240.671
962561AG1-105 C
Adder
7.2635294117647076.174
959312AF2-222 E
Adder
9.2564705882352957.868
958212AF2-115 E
Adder
1.58588235294117651.348
933502AC2-165 E
Adder
6.9070588235294135.871
3152261N ANNA2
50/50
106.886106.886
925022AB2-158 E
50/50
11.37311.373
3151741LOISA C
50/50
3.1063.106
316044AC1-158 C1
50/50
19.56819.568
934576AD1-082 E
Adder
3.19882352941176462.719
316084AB2-161 E
Adder
4.0141176470588233.412
3145256KINGFORK
Adder
0.72352941176470590.615
925522AC1-027 E
Adder
0.89764705882352950.763
943612AF1-032 E
Adder
0.68470588235294120.582
941102AE2-104 E
Adder
3.9541176470588243.361
3145506HICKORY
Adder
1.61411764705882371.372
944602AF1-125 E
Adder
76.3341176470588364.884
957872AF2-081 E
Adder
3.17411764705882372.698
957871AF2-081 C
Adder
7.4070588235294126.296
933292AC2-141 E
Adder
9.502352941176478.077
933291AC2-141 C
Adder
22.2618.921
926755AC1-161 E
Adder
9.502352941176478.077
940492AE2-034 E
Adder
2.3364705882352941.986
3145946PLYMOUTH TP
Adder
0.245882352941176470.209
934522AD1-076 E
Adder
4.7541176470588244.041
938552AE1-074 E
Adder
1.09294117647058830.929
933982AD1-022 E
Adder
3.6447058823529413.098
943172AE2-346 E
Adder
0.46941176470588240.399
940641AE2-051 C
50/50
16.47216.472
918492AA1-063AE OP
Adder
3.22705882352941182.743
925122AB2-169 E
Adder
4.4105882352941183.749
917332KELFORD E
Adder
1.281.088
946282AF1-292 E
Adder
0.84117647058823530.715
944012AF1-069 E
50/50
4.9154.915
932632AC2-084 E
Adder
2.53411764705882362.154
926214AC1-099 E
Adder
0.94705882352941180.805
316274AC1-208 C
Adder
7.1094117647058826.043
927146AC1-208 E
Adder
3.1564705882352942.683
917512Z2-088 E OP1
Adder
3.8047058823529413.234
917342Z2-044 E
Adder
0.46823529411764710.398
3151311EDGECMA
Adder
12.11411764705882510.297
934622AD1-088 E
Adder
4.1364705882352943.516
937482AD2-202 E
Adder
0.94117647058823540.8
934612AD1-087 E
Adder
3.2152941176470592.733
924162AB2-060 E OP
Adder
3.54470588235294143.013
964242AG1-285 E
Adder
6.9188235294117655.881
938562AE1-075 E
Adder
1.00.85
964792AG1-342 E
Adder
1.92588235294117661.637
961792AG1-021 E
Adder
1.26941176470588221.079
3138533PONTONDP
Adder
0.55176470588235290.469
316336AC2-165 C
Adder
9.177647058823537.801
927255AC1-221 E
Adder
2.9588235294117652.515
932763AC2-100 E
Adder
2.00588235294117641.705
3152251N ANNA1
50/50
106.841106.841
3151721LOISA A
50/50
3.093.09
316303AF2-085
50/50
4.0434.043
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.05120.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.83616.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7842.784
LAGNLTFEXP_LAGN->PJM
CLTF
5.9595.959
NYPJM->LTFIMP_NY
CLTF
2.3732.373
LGEELTFEXP_LGEE->PJM
CLTF
0.8720.872
WECLTFEXP_WEC->PJM
CLTF
0.4310.431
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4084.408
CBM South 2LTFEXP_CBM-S2->PJM
CBM
77.11777.117
CPLELTFEXP_CPLE->PJM
CLTF
9.2519.251
TVALTFEXP_TVA->PJM
CLTF
4.7224.722
O66PJM->LTFIMP_O-066
CMTX_NF
32.20632.206
G-007PJM->LTFIMP_G-007
CMTX_NF
5.0575.057
SIGELTFEXP_SIGE->PJM
CLTF
0.1730.173

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.71 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3758.56
MW Contribution:40.27
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940431AE2-027 C
Adder
10.6976470588235299.093
961611AG1-000B C
Adder
13.19882352941176511.219
942001AE2-212 C
Adder
1.8635294117647061.584
3150831SPRUNCA
Adder
7.7905882352941186.622
3150841SPRUNCB
Adder
7.7905882352941186.622
316072AD1-144 C
80/20
0.2460.246
316375AC2-012 C
80/20
1.2021.202
3151081ELIZAR1
80/20
2.8512.851
916191Z1-068 C
80/20
0.0390.039
941101AE2-104 C
80/20
3.0013.001
316185AD1-033 C
80/20
1.0971.097
944581AF1-123 C
80/20
40.90340.903
316294AC1-161 C
80/20
4.4154.415
940541AE2-040 C
80/20
2.7232.723
940481AE2-033 C
80/20
15.30215.302
934501AD1-074 C
Adder
30.18352941176470625.656
316365AB2-100 C1
80/20
0.8850.885
961941AG1-037 C
Adder
0.454117647058823570.386
316181AB2-040 GEN
80/20
1.1581.158
941031AE2-094 C
80/20
41.10641.106
3147043LAWRENC
80/20
0.2810.281
3151021BRUNSWICKG1
80/20
8.3898.389
3151031BRUNSWICKG2
80/20
8.3898.389
934331AD1-057 C
Adder
3.11764705882352942.65
934321AD1-056 C
Adder
5.5882352941176484.75
961671AG1-007 C
Adder
0.82941176470588230.705
957481AF2-042 C
80/20
52.44752.447
934621AD1-088 C
80/20
9.29.2
3151531CLOVER1
80/20
12.09912.099
3151541CLOVER2
80/20
11.98511.985
316258AE1-075 C
80/20
0.3530.353
958211AF2-115 C
Adder
2.0152941176470591.713
946301AF1-294 C
Adder
3.3141176470588242.817
942461AE2-259 C
Adder
8.8929411764705887.559
316192AB2-158 C
80/20
3.5593.559
3151801S ANNAS2
80/20
1.2181.218
3151791S ANNAG2
80/20
2.372.37
3151771S ANNAG1
80/20
2.372.37
3151781S ANNAS1
80/20
1.2181.218
3151761LOISA E
80/20
4.8664.866
966001AG1-469 C
Adder
1.43764705882352951.222
208900BRIS G1
80/20
-2.56-2.56
208901BRIS G2
80/20
-3.03-3.03
3150731STONECA
Adder
5.4352941176470594.62
935161AD1-151 C
Adder
13.03882352941176511.083
316381AD1-082 C
80/20
1.1161.116
316083AB2-161 C
80/20
0.4890.489
316349AD2-085 C
80/20
3.0713.071
942341AE2-247 C
80/20
1.3311.331
3150991CHESPKB
80/20
0.6430.643
3151091ELIZAR2
80/20
2.8012.801
316246AF1-032 C
80/20
0.2540.254
958161AF2-110 C
80/20
1.2251.225
316388AE2-253 GEN
80/20
1.7531.753
938531AE1-072 C
80/20
15.7315.73
316320Y1-086 C
80/20
0.1960.196
939411AE1-173 C
80/20
90.4790.47
933981AD1-022 C
Adder
7.84941176470588256.672
966621AG1-532 C
80/20
1.2891.289
946281AF1-292 C
80/20
1.4231.423
926071AC1-086 C
Adder
19.07647058823529616.215
313506AB1-173 C OP
80/20
1.0281.028
3137643SOCKMAN
Adder
0.64823529411764710.551
927021AC1-189 C
Adder
7.4435294117647066.327
935171AD1-152 C
80/20
1.2331.233
964241AG1-285 C
Adder
11.3035294117647079.608
962561AG1-105 C
Adder
7.9117647058823526.725
3152261N ANNA2
80/20
92.75992.759
3151741LOISA C
80/20
2.3872.387
3150601CHESTF5
Adder
45.29058823529411638.497
939191AE1-149 C
80/20
9.4869.486
944641AF1-129 C
Adder
83.2882352941176570.795
316240AF1-291 C
Adder
1.78117647058823541.514
943461AF1-017 C
80/20
1.2041.204
316311AC2-079 C
80/20
5.125.12
3150981CHESPKA
80/20
0.3880.388
316036AC1-147 C
80/20
0.3280.328
941591AE2-156 C
80/20
15.98415.984
3151101ELIZAR3
80/20
2.8872.887
316305AF2-043 C
80/20
0.3110.311
944591AF1-124 C
80/20
41.04941.049
944601AF1-125 C
80/20
40.27340.273
316321Z2-027 C
80/20
0.3250.325
3156056W1-029WIND
80/20
0.6930.693
938771AE1-103 C
80/20
2.6332.633
934521AD1-076 C
Adder
10.9623529411764719.318
934511AD1-075 C
Adder
7.54588235294117656.414
316233AE1-074 C
80/20
2.4792.479
960081AF2-299 C
80/20
1.7191.719
316087AB2-174 C
80/20
1.0751.075
944011AF1-069 C
80/20
13.43113.431
3152421Z1-086 GT2
80/20
10.7510.75
3152441Z1-086 ST
80/20
18.71718.717
3152411Z1-086 GT1
80/20
10.75310.753
963041AG1-153 C
80/20
5.7035.703
3151051BRUNSWICKS1
80/20
17.42917.429
3151041BRUNSWICKG3
80/20
8.3898.389
316263AC1-034 C
Adder
5.8505882352941184.973
937481AD2-202 C
80/20
0.3460.346
936261AD2-033 C
Adder
11.7211764705882359.963
316313AB2-026 C
80/20
0.3850.385
959311AF2-222 C
Adder
14.9976470588235312.748
964791AG1-342 C
Adder
3.14588235294117662.674
961791AG1-021 C
Adder
1.61176470588235321.37
3151751LOISA D
80/20
2.3872.387
3151731LOISA B
80/20
2.3872.387
944631AF1-128 C
Adder
28.33882352941176624.088
3150921YORKTN3
Adder
92.4352941176470578.57
3150651CHESTF6
Adder
15.16470588235294212.89
3150851SPRUNCC
80/20
0.140.14
3150861SPRUNCD
80/20
0.140.14
316316AC1-027 C
80/20
0.2820.282
957871AF2-081 C
80/20
8.9458.945
316017AA1-139 ULT1
80/20
0.9650.965
316018AA1-139 ULT2
80/20
0.9650.965
933291AC2-141 C
80/20
27.11427.114
313526AB2-022 C
80/20
0.3360.336
316315AB2-025 C
80/20
0.3860.386
316023AB2-100 C2
80/20
0.8850.885
940641AE2-051 C
80/20
17.817.8
3152431Z1-086 GT3
80/20
10.7510.75
316274AC1-208 C
Adder
8.077647058823536.866
3151311EDGECMA
Adder
13.67647058823529511.625
934611AD1-087 C
80/20
1.1911.191
316405AF2-144 C
80/20
0.30.3
3138533PONTONDP
Adder
0.59764705882352940.508
316336AC2-165 C
80/20
9.7879.787
3152251N ANNA1
80/20
92.7292.72
3151721LOISA A
80/20
2.3742.374
316303AF2-085
80/20
4.3034.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.18225.182
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.8619.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.3753.375
LAGNLTFEXP_LAGN->PJM
CLTF
6.9186.918
NYPJM->LTFIMP_NY
CLTF
2.4542.454
LGEELTFEXP_LGEE->PJM
CLTF
1.0841.084
WECLTFEXP_WEC->PJM
CLTF
0.5370.537
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.8954.895
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.42786.427
CPLELTFEXP_CPLE->PJM
CLTF
10.2710.27
TVALTFEXP_TVA->PJM
CLTF
5.5015.501
SIGELTFEXP_SIGE->PJM
CLTF
0.2110.211

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.93 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3669.13
MW Contribution:50.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
963611AG1-210 C
Adder
0.68235294117647060.58
962861AG1-135 C
Adder
6.3647058823529425.41
943741AF1-042 C
Adder
3.06352941176470632.604
940431AE2-027 C
80/20
14.61614.616
3150801HOPHCF4
80/20
4.1494.149
961611AG1-000B C
Adder
17.92352941176470415.235
942001AE2-212 C
80/20
2.4472.447
3150831SPRUNCA
80/20
10.42510.425
3150841SPRUNCB
80/20
10.42510.425
316375AC2-012 C
80/20
1.521.52
3151081ELIZAR1
80/20
3.6013.601
941101AE2-104 C
Adder
3.75764705882352963.194
944581AF1-123 C
80/20
51.27751.277
316294AC1-161 C
80/20
5.5975.597
940541AE2-040 C
Adder
3.10117647058823562.636
940481AE2-033 C
Adder
17.43882352941176714.823
934501AD1-074 C
Adder
36.4552941176470630.987
961941AG1-037 C
Adder
0.53764705882352950.457
941031AE2-094 C
80/20
42.24742.247
934331AD1-057 C
Adder
3.5635294117647063.029
934321AD1-056 C
Adder
6.3870588235294125.429
961671AG1-007 C
Adder
0.95176470588235310.809
957481AF2-042 C
Adder
54.6470588235294146.45
927041AC1-191 C
Adder
10.2870588235294128.744
966871AG1-558 C
Adder
2.56235294117647072.178
934621AD1-088 C
Adder
9.6105882352941188.169
958211AF2-115 C
Adder
2.14705882352941171.825
946301AF1-294 C
Adder
3.5305882352941183.001
942461AE2-259 C
Adder
9.4035294117647077.993
964211AG1-282 C
Adder
2.07882352941176451.767
966661AG1-536 C
Adder
5.6341176470588234.789
316169AC1-164 GEN
Adder
43.66588235294117537.116
3150771HOPHCF1
80/20
2.7332.733
3150731STONECA
80/20
7.7657.765
935161AD1-151 C
Adder
18.16235294117647215.438
3142366NRTHEST
80/20
0.2040.204
316349AD2-085 C
Adder
3.87058823529411773.29
942341AE2-247 C
Adder
1.67764705882352931.426
3150991CHESPKB
80/20
0.8130.813
3151091ELIZAR2
80/20
3.5383.538
958161AF2-110 C
Adder
1.53294117647058831.303
938531AE1-072 C
Adder
19.70000000000000316.745
939411AE1-173 C
80/20
99.71499.714
933981AD1-022 C
Adder
9.4470588235294128.03
966621AG1-532 C
Adder
1.46470588235294131.245
946281AF1-292 C
Adder
1.61647058823529431.374
926071AC1-086 C
Adder
21.9611764705882418.667
3137643SOCKMAN
Adder
0.74235294117647070.631
927021AC1-189 C
Adder
8.6023529411764727.312
964241AG1-285 C
Adder
12.1610.336
962561AG1-105 C
Adder
8.5058823529411767.23
3152261N ANNA2
80/20
56.72156.721
934861AD1-115 C
Adder
-3.06-2.601
939261AE1-157 C
Adder
14.10235294117647211.987
958261AF2-120 C
Adder
6.5505882352941175.568
940551AE2-041 C
Adder
7.6152941176470596.473
3150601CHESTF5
Adder
70.4105882352941159.849
3143096IRON208
80/20
0.4940.494
3150781HOPHCF2
80/20
2.7332.733
3150761HOPPOLC
80/20
1.7191.719
939191AE1-149 C
80/20
12.15312.153
944641AF1-129 C
80/20
115.84115.84
316240AF1-291 C
80/20
2.4442.444
943461AF1-017 C
Adder
1.51764705882352961.29
316311AC2-079 C
Adder
6.4458823529411775.479
941591AE2-156 C
80/20
20.20920.209
3151101ELIZAR3
80/20
3.6473.647
944591AF1-124 C
80/20
51.4651.46
944601AF1-125 C
80/20
50.48850.488
938771AE1-103 C
Adder
3.22705882352941182.743
934521AD1-076 C
Adder
13.2411.254
934511AD1-075 C
Adder
9.1141176470588237.747
316233AE1-074 C
80/20
2.8742.874
960081AF2-299 C
Adder
1.95294117647058821.66
944011AF1-069 C
80/20
13.80413.804
963041AG1-153 C
Adder
5.8858823529411765.003
316263AC1-034 C
Adder
6.6529411764705895.655
936261AD2-033 C
Adder
12.57294117647058810.687
959311AF2-222 C
Adder
16.0552941176470613.647
964791AG1-342 C
Adder
3.38000000000000032.873
961791AG1-021 C
Adder
1.71764705882352931.46
957601AF2-054 C
Adder
2.26000000000000021.921
966881AG1-559 C
Adder
2.45176470588235332.084
936591AD2-074 C
Adder
5.8552941176470594.977
961951AG1-038 C
Adder
3.3858823529411772.878
943471AF1-018 C
Adder
7.6152941176470596.473
944631AF1-128 C
Adder
44.0564705882352937.448
3150921YORKTN3
Adder
133.0105882352941113.059
3150791HOPHCF3
80/20
2.7332.733
3150651CHESTF6
80/20
21.09121.091
3150851SPRUNCC
80/20
0.1870.187
3150861SPRUNCD
80/20
0.1870.187
3152331SURRY 2
80/20
27.86527.865
957871AF2-081 C
Adder
11.2117647058823529.53
933291AC2-141 C
80/20
34.37234.372
940641AE2-051 C
80/20
18.8818.88
316274AC1-208 C
Adder
9.2835294117647067.891
3151311EDGECMA
Adder
15.55647058823529613.223
3138533PONTONDP
Adder
0.63647058823529420.541
316336AC2-165 C
Adder
10.1788235294117648.652
3152251N ANNA1
80/20
56.69756.697
316254AC1-120 C
Adder
-6.376470588235295-5.42
316257AC1-043 C
Adder
-6.121176470588236-5.203
316303AF2-085
80/20
4.4474.447
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.72830.728
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.33523.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.0414.041
LAGNLTFEXP_LAGN->PJM
CLTF
8.0268.026
NYPJM->LTFIMP_NY
CLTF
2.72.7
LGEELTFEXP_LGEE->PJM
CLTF
1.331.33
WECLTFEXP_WEC->PJM
CLTF
0.6540.654
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.4135.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69496.694
CPLELTFEXP_CPLE->PJM
CLTF
11.35211.352
TVALTFEXP_TVA->PJM
CLTF
6.4156.415
SIGELTFEXP_SIGE->PJM
CLTF
0.2560.256

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.88 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4408.08
MW Contribution:139.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935162AD1-151 E
Adder
4.4752941176470593.804
927226AC1-216 E
Adder
6.6694117647058825.669
924814AB2-134 E
Adder
10.9235294117647069.285
939191AE1-149 C
Adder
10.0011764705882348.501
944641AF1-129 C
Adder
88.4505882352941375.183
316240AF1-291 C
Adder
1.88941176470588261.606
936666AD2-085 E
Adder
5.2764705882352954.485
942342AE2-247 E
Adder
1.93529411764705881.645
943461AF1-017 C
Adder
1.26823529411764711.078
3143316POE
Adder
1.30941176470588231.113
932596AC2-079 E
Adder
8.7952941176470587.476
316311AC2-079 C
Adder
5.3905882352941184.582
941591AE2-156 C
Adder
16.83647058823529414.311
944591AF1-124 C
Adder
43.2058823529411836.725
944601AF1-125 C
Adder
42.3894117647058836.031
919152AA1-139 E1
Adder
3.8505882352941183.273
938532AE1-072 E
Adder
8.6305882352941187.336
3146326AYDLETT TAP
Adder
1.27764705882352961.086
917122Z2-027 E
Adder
1.26588235294117671.076
901082W1-029 E
Adder
30.02588235294117425.522
938771AE1-103 C
Adder
2.7670588235294122.352
3145413WATKINS
Adder
0.65411764705882360.556
920692AA2-178 E
Adder
3.86941176470588263.289
934521AD1-076 C
Adder
11.5105882352941199.784
934511AD1-075 C
Adder
7.9235294117647066.735
316233AE1-074 C
50/50
2.5912.591
920042AA2-088 E OP
Adder
10.0447058823529418.538
960081AF2-299 C
Adder
1.7964705882352941.527
966622AG1-532 E
Adder
0.89882352941176480.764
926072AC1-086 E
Adder
9.0847058823529427.722
3145723EMPORIA
Adder
0.414117647058823530.352
923573AB1-173 E OP
Adder
3.1364705882352942.666
919692AA2-053 E OP
Adder
4.00705882352941253.406
944011AF1-069 C
50/50
13.92113.921
3152421Z1-086 GT2
50/50
11.14611.146
3152441Z1-086 ST
50/50
19.40819.408
3152411Z1-086 GT1
50/50
11.14911.149
963041AG1-153 C
50/50
5.9155.915
3151051BRUNSWICKS1
50/50
18.07518.075
3151041BRUNSWICKG3
50/50
8.78.7
925785AC1-054 E
Adder
3.24941176470588242.762
936261AD2-033 C
Adder
12.2210.387
959311AF2-222 C
Adder
15.63529411764705813.29
961791AG1-021 C
Adder
1.68117647058823551.429
3147133PAMPLIN
Adder
0.92823529411764720.789
942462AE2-259 E
Adder
6.1800000000000015.253
3151731LOISA B
50/50
2.4192.419
966002AG1-469 E
Adder
0.73058823529411760.621
940431AE2-027 C
Adder
11.3411764705882369.64
961611AG1-000B C
Adder
13.98823529411764911.89
939192AE1-149 E
Adder
6.6670588235294125.667
939312AE1-162 E
Adder
1.29647058823529431.102
942002AE2-212 E
Adder
1.31294117647058851.116
942001AE2-212 C
Adder
1.96941176470588241.674
3150831SPRUNCA
Adder
8.2435294117647067.007
3150841SPRUNCB
Adder
8.2435294117647067.007
926662AC1-147 E
Adder
1.24470588235294131.058
916192Z1-068 E
Adder
1.77058823529411761.505
957492AF2-043 E
Adder
1.341.139
941101AE2-104 C
Adder
3.1588235294117652.685
934065AD1-033 E
Adder
4.7282352941176474.019
937226AE2-253 E
Adder
5.5047058823529414.679
944581AF1-123 C
Adder
43.0529411764705936.595
940541AE2-040 C
Adder
2.84470588235294162.418
923852AB2-025 E
Adder
1.15058823529411770.978
940481AE2-033 C
Adder
15.98588235294117513.588
940482AE2-033 E
Adder
10.777647058823539.161
934501AD1-074 C
Adder
31.6952941176470626.941
939412AE1-173 E
50/50
62.82462.824
924517AB2-100 E2
Adder
2.82.38
961942AG1-037 E
Adder
0.317647058823529450.27
3150651CHESTF6
Adder
16.10470588235294213.689
946262AF1-291 E
Adder
1.261.071
934576AD1-082 E
Adder
4.1188235294117653.501
316084AB2-161 E
Adder
5.1694117647058834.394
3145256KINGFORK
Adder
0.93882352941176480.798
925522AC1-027 E
Adder
1.14588235294117660.974
943612AF1-032 E
Adder
0.87058823529411770.74
941102AE2-104 E
Adder
5.0223529411764714.269
3145506HICKORY
Adder
2.05411764705882361.746
944602AF1-125 E
Adder
97.0388235294117782.483
957872AF2-081 E
Adder
4.0352941176470593.43
957871AF2-081 C
Adder
9.4164705882352948.004
933292AC2-141 E
Adder
12.19411764705882510.365
933291AC2-141 C
Adder
28.56588235294117724.281
926755AC1-161 E
Adder
12.19411764705882510.365
940492AE2-034 E
Adder
2.90235294117647062.467
3145946PLYMOUTH TP
Adder
0.30352941176470590.258
934522AD1-076 E
Adder
5.8670588235294124.987
938552AE1-074 E
50/50
1.3051.305
933982AD1-022 E
Adder
4.4858823529411773.813
943172AE2-346 E
Adder
0.5717647058823530.486
940641AE2-051 C
50/50
18.48718.487
918492AA1-063AE OP
Adder
3.87294117647058833.292
917332KELFORD E
Adder
1.54588235294117651.314
946282AF1-292 E
Adder
0.99176470588235290.843
944012AF1-069 E
50/50
5.4085.408
3152431Z1-086 GT3
50/50
11.14611.146
934622AD1-088 E
Adder
4.6035294117647063.913
937482AD2-202 E
Adder
1.04941176470588250.892
934612AD1-087 E
Adder
3.5835294117647063.046
924162AB2-060 E OP
Adder
4.0294117647058823.425
964242AG1-285 E
Adder
7.8564705882352946.678
938562AE1-075 E
Adder
1.1082352941176470.942
961792AG1-021 E
Adder
1.4317647058823531.217
3138533PONTONDP
Adder
0.62235294117647070.529
316336AC2-165 C
Adder
10.1788235294117648.652
3152251N ANNA1
50/50
93.18793.187
316141AB2-099 E
Adder
0.237647058823529430.202
961941AG1-037 C
Adder
0.476470588235294150.405
923263AB1-132 E OP
Adder
5.80941176470588254.938
316088AB2-174 E
Adder
6.242352941176475.306
923994AB2-040_E
Adder
5.8811764705882354.999
941031AE2-094 C
50/50
42.60742.607
941032AE2-094 E
50/50
19.08319.083
3151021BRUNSWICKG1
50/50
8.78.7
3151031BRUNSWICKG2
50/50
8.78.7
957482AF2-042 E
Adder
36.31529411764705630.868
957481AF2-042 C
Adder
54.4729411764705946.302
934621AD1-088 C
Adder
9.5599999999999998.126
935172AD1-152 E
Adder
5.2941176470588234.5
924322AB2-079 E O1
Adder
1.25764705882352931.069
924312AB2-078 E O1
Adder
1.25764705882352931.069
936262AD2-033 E
Adder
8.1458823529411776.924
958502AF2-144 E
Adder
1.2764705882352941.085
923862AB2-026 E
Adder
1.31.105
925612AC1-036 E
Adder
0.80588235294117660.685
958211AF2-115 C
Adder
2.1011764705882351.786
946301AF1-294 C
Adder
3.45529411764705862.937
946302AF1-294 E
Adder
2.9258823529411772.487
942461AE2-259 C
Adder
9.2705882352941187.88
316192AB2-158 C
50/50
3.5873.587
3151801S ANNAS2
50/50
1.2331.233
3151791S ANNAG2
50/50
2.42.4
3151771S ANNAG1
50/50
2.42.4
3151781S ANNAS1
50/50
1.2331.233
3151761LOISA E
50/50
4.9314.931
966001AG1-469 C
Adder
1.46235294117647091.243
208900BRIS G1
50/50
-2.742-2.742
208901BRIS G2
50/50
-3.245-3.245
940432AE2-027 E
Adder
7.5611764705882356.427
935161AD1-151 C
Adder
13.84941176470588311.772
934012AD1-025 E
Adder
8.6341176470588247.339
935112AD1-144 E
Adder
0.8717647058823530.741
943462AF1-017 E
Adder
2.06941176470588231.759
316349AD2-085 C
Adder
3.23411764705882382.749
942341AE2-247 C
Adder
1.40235294117647061.192
932046AC2-012 E
Adder
12.31647058823529410.469
958161AF2-110 C
Adder
1.28941176470588251.096
958162AF2-110 E
Adder
2.0505882352941181.743
944582AF1-123 E
Adder
98.5858823529411883.798
944592AF1-124 E
Adder
98.9435294117647184.102
919153AA1-139 E2
Adder
3.8505882352941183.273
938531AE1-072 C
Adder
16.55647058823529614.073
923832AB2-022 E
Adder
1.1682352941176470.993
913392Y1-086 E
Adder
2.0705882352941181.76
938772AE1-103 E
Adder
3.8211764705882363.248
916042Z1-036 E
Adder
26.91882352941176422.881
3145393UNCAMP
Adder
5.7482352941176484.886
934502AD1-074 E
Adder
16.13411764705882613.714
934512AD1-075 E
Adder
4.0341176470588243.429
939411AE1-173 C
50/50
94.23794.237
933981AD1-022 C
Adder
8.247.004
900672V4-068 E
Adder
0.33764705882352940.287
918512AA1-065 E OP
Adder
5.2011764705882364.421
924516AB2-100 E1
Adder
2.82.38
940642AE2-051 E
50/50
12.32512.325
966621AG1-532 C
Adder
1.34705882352941191.145
960082AF2-299 E
Adder
1.19764705882352951.018
946281AF1-292 C
Adder
1.48705882352941181.264
926071AC1-086 C
Adder
19.96117647058823516.967
3137643SOCKMAN
Adder
0.67882352941176470.577
963042AG1-153 E
50/50
8.8728.872
924022AB2-043 E O1
Adder
4.8811764705882354.149
924302AB2-077 E O1
Adder
1.25764705882352931.069
964241AG1-285 C
Adder
11.78352941176470610.016
3147223TWITTYS
Adder
0.89294117647058820.759
959312AF2-222 E
Adder
10.4764705882352948.905
958212AF2-115 E
Adder
1.78941176470588231.521
933502AC2-165 E
Adder
7.6611764705882356.512
3152261N ANNA2
50/50
93.22693.226
925022AB2-158 E
50/50
9.5359.535
3151741LOISA C
50/50
2.4192.419
316303AF2-085
50/50
4.464.46
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.02528.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.37921.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.6863.686
LAGNLTFEXP_LAGN->PJM
CLTF
7.3867.386
NYPJM->LTFIMP_NY
CLTF
2.6122.612
LGEELTFEXP_LGEE->PJM
CLTF
1.1951.195
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.1255.125
CBM South 2LTFEXP_CBM-S2->PJM
CBM
90.8190.81
CPLELTFEXP_CPLE->PJM
CLTF
10.7510.75
TVALTFEXP_TVA->PJM
CLTF
5.8785.878
O66PJM->LTFIMP_O-066
CMTX_NF
35.46935.469
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5685.568
SIGELTFEXP_SIGE->PJM
CLTF
0.2320.232

Details for 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8OX-8CLIFTON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2101-569_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.43 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3314.56
MW Contribution:95.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316078AC2-138 E
Adder
0.71764705882352940.61
963612AG1-210 E
Adder
0.76823529411764710.653
966661AG1-536 C
Adder
4.0682352941176473.458
958262AF2-120 E
Adder
3.15294117647058862.68
939612AE1-191 E
Adder
3.99529411764705873.396
316169AC1-164 GEN
Adder
27.6552941176470623.507
940432AE2-027 E
Adder
5.8152941176470594.943
3150731STONECA
Adder
4.6788235294117653.977
935161AD1-151 C
Adder
10.8658823529411789.236
934012AD1-025 E
Adder
6.725.712
930122AB1-027 E
Adder
0.95294117647058830.81
926412AC1-112 E
Adder
0.77529411764705890.659
935112AD1-144 E
Adder
0.61764705882352940.525
943462AF1-017 E
Adder
1.43647058823529421.221
316349AD2-085 C
Adder
2.24588235294117671.909
942341AE2-247 C
Adder
0.97294117647058820.827
932046AC2-012 E
Adder
8.5752941176470587.289
958161AF2-110 C
Adder
0.88705882352941180.754
958162AF2-110 E
Adder
1.4117647058823531.2
944582AF1-123 E
Adder
67.8623529411764757.683
944592AF1-124 E
Adder
68.1082352941176557.892
919153AA1-139 E2
Adder
2.6505882352941182.253
938531AE1-072 C
Adder
11.3870588235294139.679
923832AB2-022 E
Adder
0.80.68
913392Y1-086 E
Adder
1.41764705882352951.205
939411AE1-173 C
Adder
55.50470588235294447.179
940642AE2-051 E
Adder
6.9188235294117655.881
3152261N ANNA2
50/50
23.22323.223
957602AF2-054 E
Adder
0.99411764705882360.845
925022AB2-158 E
Adder
3.342.839
316044AC1-158 C1
50/50
4.244.24
926486AC1-120 E
Adder
2.38235294117647062.025
966882AG1-559 E
50/50
0.9590.959
316415AF1-147_GEN2
Adder
-5.709411764705882-4.853
939261AE1-157 C
50/50
11.34411.344
3150091POSSM6B
50/50
3.7073.707
3150331BIRCHWDA
Adder
28.4352941176470624.17
944491AF1-114 C
Adder
5.6352941176470594.79
957971AF2-091 C
Adder
1.91529411764705881.628
963611AG1-210 C
Adder
0.51294117647058820.436
3141813NORNECK
Adder
0.68235294117647060.58
966662AG1-536 E
Adder
5.4670588235294124.647
962861AG1-135 C
Adder
4.57294117647058853.887
962862AG1-135 E
Adder
3.0482352941176472.591
943741AF1-042 C
Adder
2.16470588235294151.84
943742AF1-042 E
Adder
3.5317647058823533.002
934392AD1-063 E
Adder
0.75058823529411770.638
923842AB2-024 E
Adder
1.25176470588235311.064
940431AE2-027 C
Adder
8.722352941176477.414
316076AC2-137 E
Adder
0.91529411764705890.778
3138116ELKO L286
Adder
0.9552941176470590.812
961611AG1-000B C
Adder
10.6435294117647079.047
939192AE1-149 E
Adder
4.7364705882352944.026
939312AE1-162 E
Adder
0.94823529411764720.806
942002AE2-212 E
Adder
0.96117647058823530.817
942001AE2-212 C
Adder
1.44117647058823551.225
3150831SPRUNCA
Adder
6.19058823529411755.262
3150841SPRUNCB
Adder
6.19058823529411755.262
926662AC1-147 E
Adder
0.86705882352941180.737
916192Z1-068 E
Adder
1.22705882352941181.043
957492AF2-043 E
Adder
0.92352941176470590.785
941101AE2-104 C
Adder
2.17411764705882371.848
934065AD1-033 E
Adder
3.2670588235294122.777
937226AE2-253 E
Adder
3.79294117647058873.224
944581AF1-123 C
Adder
29.6352941176470625.19
940541AE2-040 C
Adder
1.7482352941176471.486
923852AB2-025 E
Adder
0.70705882352941170.601
939412AE1-173 E
Adder
37.00235294117647631.452
941031AE2-094 C
Adder
7.7070588235294126.551
927041AC1-191 C
Adder
6.8811764705882365.849
966871AG1-558 C
Adder
1.71411764705882371.457
966872AG1-558 E
Adder
0.86352941176470590.734
316157AD2-030 E
Adder
0.83647058823529410.711
926740AC1-158 E2
50/50
11.0911.09
316411AF1-147_GEN1
Adder
-5.709411764705882-4.853
3150391LDYSMT3
50/50
3.9183.918
3150401LDYSMT4
50/50
3.9253.925
3150371LDYSMT1
50/50
3.7683.768
3150081POSSM6A
50/50
3.7073.707
957191AF2-013 C
Adder
13.7647058823529411.7
944492AF1-114 E
Adder
7.7811764705882356.614
964211AG1-282 C
Adder
1.53411764705882361.304
936592AD2-074 E
Adder
6.7505882352941185.738
936591AD2-074 C
Adder
4.13764705882352953.517
961952AG1-038 E
Adder
3.30470588235294162.809
961951AG1-038 C
Adder
2.3929411764705882.034
939602AE1-190 E
Adder
0.99882352941176470.849
925865AC1-065 E
Adder
11.6529411764705889.905
943471AF1-018 C
Adder
5.002352941176474.252
3130536PAPERMILL
Adder
4.6305882352941183.936
926785AC1-164_E
Adder
12.42470588235294210.561
316160AE1-175 E
Adder
0.80823529411764720.687
944631AF1-128 C
Adder
27.14823529411764723.076
3150921YORKTN3
Adder
80.576470588235368.49
3150651CHESTF6
Adder
12.60823529411764810.717
946262AF1-291 E
Adder
0.97058823529411760.825
934576AD1-082 E
Adder
2.8988235294117652.464
316084AB2-161 E
Adder
3.63882352941176463.093
3145256KINGFORK
Adder
0.66470588235294110.565
925522AC1-027 E
Adder
0.79411764705882360.675
943612AF1-032 E
Adder
0.60.51
941102AE2-104 E
Adder
3.4564705882352942.938
3145506HICKORY
Adder
1.41764705882352951.205
944602AF1-125 E
Adder
66.7976470588235356.778
957872AF2-081 E
Adder
2.77764705882352962.361
957871AF2-081 C
Adder
6.4823529411764715.51
933292AC2-141 E
Adder
8.4905882352941177.217
933291AC2-141 C
Adder
19.89058823529411816.907
926755AC1-161 E
Adder
8.4905882352941177.217
938552AE1-074 E
Adder
0.82823529411764710.704
940641AE2-051 C
Adder
10.3776470588235298.821
3152251N ANNA1
50/50
23.21323.213
934782AD1-105 E
Adder
3.91411764705882353.327
926004AC1-076_E
Adder
2.9364705882352942.496
316254AC1-120 C
Adder
4.6235294117647063.93
939262AE1-157 E
50/50
6.1536.153
926472AC1-118 E
Adder
0.89058823529411770.757
936582AD2-073 E
Adder
0.85411764705882350.726
939246AE1-155 E
Adder
6.58588235294117655.598
958261AF2-120 C
Adder
4.72941176470588154.02
934146AD1-041 E
Adder
2.49764705882352982.123
940551AE2-041 C
Adder
5.002352941176474.252
962962AG1-145 E
Adder
0.980.833
3150601CHESTF5
Adder
43.3882352941176536.88
925332AB2-190 E
Adder
5.4447058823529424.628
935162AD1-151 E
Adder
7.24470588235294166.158
927226AC1-216 E
Adder
5.19058823529411754.412
924814AB2-134 E
Adder
8.5035294117647067.228
939191AE1-149 C
Adder
7.1058823529411776.04
944641AF1-129 C
Adder
69.2494117647058858.862
316240AF1-291 C
Adder
1.4552941176470591.237
936666AD2-085 E
Adder
3.66470588235294153.115
942342AE2-247 E
Adder
1.34470588235294121.143
943461AF1-017 C
Adder
0.88117647058823530.749
3143316POE
Adder
0.89058823529411770.757
932596AC2-079 E
Adder
6.1011764705882365.186
316311AC2-079 C
Adder
3.73882352941176473.178
941591AE2-156 C
Adder
11.7164705882352949.959
944591AF1-124 C
Adder
29.74117647058823625.28
944601AF1-125 C
Adder
29.17882352941176524.802
919152AA1-139 E1
Adder
2.6505882352941182.253
938532AE1-072 E
Adder
5.9364705882352945.046
3146326AYDLETT TAP
Adder
0.87882352941176480.747
917122Z2-027 E
Adder
0.86470588235294120.735
901082W1-029 E
Adder
20.48235294117647217.41
316233AE1-074 C
Adder
1.6435294117647061.397
927042AC1-191 E
Adder
3.42823529411764752.914
957832AF2-077 E
Adder
0.98235294117647050.835
957601AF2-054 C
Adder
1.49058823529411751.267
316045AC1-158 C2
50/50
4.244.24
926739AC1-158 E1
50/50
11.0911.09
316170AC1-121 C
Adder
1.58823529411764721.35
926502AC1-121 E
Adder
0.74705882352941180.635
966881AG1-559 C
50/50
1.9031.903
3150381LDYSMT2
50/50
3.8173.817
3150411LDYSMT5
50/50
3.9383.938
3150181POSSMC2
50/50
0.8240.824
3150071POSSM 5
Adder
89.4835294117647276.061
3150101POSSM6S
50/50
5.7795.779
957972AF2-091 E
Adder
2.64588235294117662.249
964212AG1-282 E
Adder
1.02235294117647070.869
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.0499.049
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.51310.513
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5641.564
LAGNLTFEXP_LAGN->PJM
CLTF
3.8863.886
NYPJM->LTFIMP_NY
CLTF
1.9611.961
LGEELTFEXP_LGEE->PJM
CLTF
0.4830.483
WECLTFEXP_WEC->PJM
CLTF
0.2130.213
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.9592.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
52.10752.107
CPLELTFEXP_CPLE->PJM
CLTF
6.2066.206
TVALTFEXP_TVA->PJM
CLTF
3.123.12
O66PJM->LTFIMP_O-066
CMTX_NF
25.38725.387
G-007PJM->LTFIMP_G-007
CMTX_NF
3.9723.972
SIGELTFEXP_SIGE->PJM
CLTF
0.0980.098

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.93 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3894.33
MW Contribution:39.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940431AE2-027 C
Adder
10.4682352941176488.898
961611AG1-000B C
Adder
12.91058823529411910.974
942001AE2-212 C
Adder
1.82117647058823541.548
3150831SPRUNCA
Adder
7.6235294117647066.48
3150841SPRUNCB
Adder
7.6235294117647066.48
316375AC2-012 C
80/20
1.1731.173
3151081ELIZAR1
80/20
2.7822.782
916191Z1-068 C
80/20
0.0380.038
941101AE2-104 C
80/20
2.9282.928
316185AD1-033 C
80/20
1.071.07
944581AF1-123 C
80/20
39.90939.909
316294AC1-161 C
80/20
4.314.31
940541AE2-040 C
80/20
2.652.65
940481AE2-033 C
80/20
14.89114.891
934501AD1-074 C
Adder
29.40470588235294324.994
316365AB2-100 C1
80/20
0.8620.862
961941AG1-037 C
Adder
0.44235294117647060.376
941031AE2-094 C
80/20
39.89839.898
3147043LAWRENC
80/20
0.2730.273
3151021BRUNSWICKG1
80/20
8.1438.143
3151031BRUNSWICKG2
80/20
8.1438.143
934331AD1-057 C
Adder
3.0305882352941182.576
934321AD1-056 C
Adder
5.4329411764705894.618
961671AG1-007 C
Adder
0.80588235294117660.685
957481AF2-042 C
80/20
51.00351.003
934621AD1-088 C
80/20
8.9588.958
3151531CLOVER1
80/20
11.76811.768
3151541CLOVER2
80/20
11.65811.658
316258AE1-075 C
80/20
0.3460.346
958211AF2-115 C
Adder
1.97411764705882351.678
946301AF1-294 C
Adder
3.2458823529411762.759
942461AE2-259 C
Adder
8.7329411764705887.423
316192AB2-158 C
80/20
3.6253.625
3151801S ANNAS2
80/20
1.3621.362
3151791S ANNAG2
80/20
2.6512.651
3151771S ANNAG1
80/20
2.6512.651
3151781S ANNAS1
80/20
1.3621.362
3151761LOISA E
80/20
5.5225.522
966001AG1-469 C
80/20
1.9591.959
208900BRIS G1
80/20
-2.628-2.628
208901BRIS G2
80/20
-3.11-3.11
3150731STONECA
Adder
5.3258823529411774.527
935161AD1-151 C
Adder
12.7647058823529410.85
316381AD1-082 C
80/20
1.0891.089
316083AB2-161 C
80/20
0.4780.478
316349AD2-085 C
80/20
2.9972.997
942341AE2-247 C
80/20
1.2991.299
3150991CHESPKB
80/20
0.6270.627
3151091ELIZAR2
80/20
2.7332.733
316246AF1-032 C
80/20
0.2480.248
958161AF2-110 C
80/20
1.1951.195
316388AE2-253 GEN
80/20
1.711.71
938531AE1-072 C
80/20
15.34615.346
316320Y1-086 C
80/20
0.1920.192
939411AE1-173 C
80/20
87.96287.962
933981AD1-022 C
Adder
7.6458823529411766.499
966621AG1-532 C
80/20
1.2551.255
946281AF1-292 C
80/20
1.3851.385
926071AC1-086 C
Adder
18.5623529411764715.778
3137643SOCKMAN
Adder
0.6317647058823530.537
927021AC1-189 C
Adder
7.2364705882352946.151
935171AD1-152 C
80/20
1.1991.199
964241AG1-285 C
Adder
11.0294117647058829.375
962561AG1-105 C
Adder
7.70470588235294156.549
3152261N ANNA2
80/20
89.07389.073
3151741LOISA C
80/20
2.7082.708
316044AC1-158 C1
80/20
19.41819.418
934861AD1-115 C
Adder
2.8482352941176472.421
939191AE1-149 C
80/20
9.2629.262
944641AF1-129 C
Adder
81.5517647058823669.319
316240AF1-291 C
Adder
1.7435294117647061.482
943461AF1-017 C
80/20
1.1751.175
316311AC2-079 C
80/20
4.9964.996
3150981CHESPKA
80/20
0.3780.378
316036AC1-147 C
80/20
0.320.32
941591AE2-156 C
80/20
15.615.6
3151101ELIZAR3
80/20
2.8172.817
316305AF2-043 C
80/20
0.3030.303
944591AF1-124 C
80/20
40.05140.051
944601AF1-125 C
80/20
39.29539.295
316321Z2-027 C
80/20
0.3170.317
3156056W1-029WIND
80/20
0.6760.676
938771AE1-103 C
80/20
2.5672.567
934521AD1-076 C
Adder
10.6788235294117659.077
934511AD1-075 C
Adder
7.3517647058823536.249
316233AE1-074 C
80/20
2.4172.417
960081AF2-299 C
80/20
1.6731.673
316087AB2-174 C
80/20
1.0461.046
944011AF1-069 C
80/20
13.03613.036
3152421Z1-086 GT2
80/20
10.43410.434
3152441Z1-086 ST
80/20
18.16818.168
3152411Z1-086 GT1
80/20
10.43710.437
963041AG1-153 C
80/20
5.5365.536
3151051BRUNSWICKS1
80/20
16.91816.918
3151041BRUNSWICKG3
80/20
8.1438.143
316263AC1-034 C
Adder
5.6858823529411774.833
937481AD2-202 C
80/20
0.3360.336
936261AD2-033 C
Adder
11.4505882352941189.733
316313AB2-026 C
80/20
0.3770.377
959311AF2-222 C
Adder
14.6623529411764712.463
964791AG1-342 C
Adder
3.06352941176470632.604
961791AG1-021 C
Adder
1.57882352941176471.342
3151751LOISA D
80/20
2.7082.708
3151731LOISA B
80/20
2.7082.708
316045AC1-158 C2
80/20
19.41819.418
316164AC1-076_C
80/20
1.1141.114
316170AC1-121 C
80/20
2.7242.724
3150921YORKTN3
Adder
90.5694117647058876.984
3150651CHESTF6
Adder
14.84823529411764812.621
3150851SPRUNCC
80/20
0.1370.137
3150861SPRUNCD
80/20
0.1370.137
316316AC1-027 C
80/20
0.2750.275
957871AF2-081 C
80/20
8.7288.728
316017AA1-139 ULT1
80/20
0.9420.942
316018AA1-139 ULT2
80/20
0.9420.942
933291AC2-141 C
80/20
26.46526.465
313526AB2-022 C
80/20
0.3280.328
316315AB2-025 C
80/20
0.3750.375
316023AB2-100 C2
80/20
0.8620.862
940641AE2-051 C
80/20
17.2917.29
3152431Z1-086 GT3
80/20
10.43410.434
316274AC1-208 C
Adder
7.857647058823536.679
3151311EDGECMA
Adder
13.28823529411764811.295
934611AD1-087 C
80/20
1.1591.159
316405AF2-144 C
80/20
0.2940.294
3138533PONTONDP
Adder
0.58470588235294120.497
316336AC2-165 C
80/20
9.6099.609
3152251N ANNA1
80/20
89.03589.035
3151721LOISA A
80/20
2.6942.694
316254AC1-120 C
80/20
7.9327.932
316257AC1-043 C
Adder
5.697647058823534.843
316303AF2-085
80/20
4.1844.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.96121.961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.49718.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.0623.062
LAGNLTFEXP_LAGN->PJM
CLTF
6.5316.531
NYPJM->LTFIMP_NY
CLTF
2.5322.532
LGEELTFEXP_LGEE->PJM
CLTF
0.9710.971
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.744.74
CBM South 2LTFEXP_CBM-S2->PJM
CBM
83.40383.403
CPLELTFEXP_CPLE->PJM
CLTF
9.9459.945
TVALTFEXP_TVA->PJM
CLTF
5.1955.195
SIGELTFEXP_SIGE->PJM
CLTF
0.1910.191

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.78 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3857.57
MW Contribution:49.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
963611AG1-210 C
Adder
0.66705882352941170.567
962861AG1-135 C
Adder
6.222352941176475.289
943741AF1-042 C
Adder
2.9964705882352942.547
940431AE2-027 C
80/20
14.31814.318
3150801HOPHCF4
80/20
4.0644.064
961611AG1-000B C
Adder
17.55647058823529614.923
942001AE2-212 C
80/20
2.3972.397
3150831SPRUNCA
80/20
10.21910.219
3150841SPRUNCB
80/20
10.21910.219
316375AC2-012 C
80/20
1.4881.488
3151081ELIZAR1
80/20
3.5273.527
941101AE2-104 C
Adder
3.683.128
944581AF1-123 C
80/20
50.22150.221
316294AC1-161 C
80/20
5.4825.482
940541AE2-040 C
Adder
3.03764705882352942.582
940481AE2-033 C
Adder
17.08117647058823614.519
934501AD1-074 C
Adder
35.6976470588235330.343
961941AG1-037 C
Adder
0.52705882352941180.448
941031AE2-094 C
80/20
41.37341.373
934331AD1-057 C
Adder
3.4882352941176472.965
934321AD1-056 C
Adder
6.2529411764705895.315
961671AG1-007 C
Adder
0.9317647058823530.792
957481AF2-042 C
Adder
53.64117647058823545.595
927041AC1-191 C
Adder
10.0729411764705888.562
966871AG1-558 C
Adder
2.50941176470588222.133
934621AD1-088 C
Adder
9.4482352941176488.031
958211AF2-115 C
Adder
2.12470588235294141.806
946301AF1-294 C
Adder
3.4941176470588242.97
942461AE2-259 C
Adder
9.347.939
316192AB2-158 C
80/20
2.1182.118
964211AG1-282 C
Adder
2.0317647058823531.727
966661AG1-536 C
Adder
5.5082352941176484.682
316169AC1-164 GEN
Adder
42.77176470588235436.356
3150771HOPHCF1
80/20
2.6772.677
3150731STONECA
80/20
7.6067.606
935161AD1-151 C
Adder
17.79176470588235415.123
3142366NRTHEST
80/20
0.20.2
316349AD2-085 C
Adder
3.79058823529411763.222
942341AE2-247 C
Adder
1.64235294117647061.396
3150991CHESPKB
80/20
0.7960.796
3151091ELIZAR2
80/20
3.4653.465
958161AF2-110 C
Adder
1.50117647058823531.276
938531AE1-072 C
Adder
19.2929411764705916.399
939411AE1-173 C
80/20
97.64897.648
933981AD1-022 C
Adder
9.2505882352941197.863
966621AG1-532 C
Adder
1.43529411764705881.22
946281AF1-292 C
Adder
1.58470588235294121.347
926071AC1-086 C
Adder
21.50823529411764718.282
3137643SOCKMAN
Adder
0.72705882352941180.618
927021AC1-189 C
Adder
8.4188235294117647.156
964241AG1-285 C
Adder
11.97764705882352810.181
962561AG1-105 C
Adder
8.3588235294117657.105
3152261N ANNA2
80/20
55.34655.346
316044AC1-158 C1
80/20
14.96214.962
939261AE1-157 C
Adder
13.77647058823529511.71
958261AF2-120 C
Adder
6.4035294117647065.443
940551AE2-041 C
Adder
7.4541176470588246.336
3150601CHESTF5
Adder
68.9811764705882458.634
3143096IRON208
80/20
0.4840.484
3150781HOPHCF2
80/20
2.6772.677
3150761HOPPOLC
80/20
1.6841.684
939191AE1-149 C
80/20
11.90511.905
944641AF1-129 C
80/20
113.49113.49
316240AF1-291 C
80/20
2.3942.394
943461AF1-017 C
Adder
1.48588235294117641.263
316311AC2-079 C
Adder
6.3129411764705885.366
941591AE2-156 C
80/20
19.79319.793
3151101ELIZAR3
80/20
3.5723.572
944591AF1-124 C
80/20
50.39950.399
944601AF1-125 C
80/20
49.44749.447
938771AE1-103 C
Adder
3.162.686
934521AD1-076 C
Adder
12.96470588235294111.02
934511AD1-075 C
Adder
8.9247058823529427.586
316233AE1-074 C
80/20
2.8192.819
960081AF2-299 C
Adder
1.91411764705882351.627
944011AF1-069 C
80/20
13.51813.518
963041AG1-153 C
Adder
5.7647058823529424.9
316263AC1-034 C
Adder
6.5105882352941185.534
936261AD2-033 C
Adder
12.4023529411764710.542
959311AF2-222 C
Adder
15.85294117647058913.475
964791AG1-342 C
Adder
3.32117647058823542.823
961791AG1-021 C
Adder
1.70000000000000021.445
957601AF2-054 C
Adder
2.2117647058823531.88
316045AC1-158 C2
80/20
14.96214.962
316164AC1-076_C
80/20
0.9930.993
966881AG1-559 C
Adder
2.3964705882352942.037
936591AD2-074 C
Adder
5.7258823529411764.867
961951AG1-038 C
Adder
3.3117647058823532.815
943471AF1-018 C
Adder
7.4541176470588246.336
944631AF1-128 C
Adder
43.1623529411764736.688
3150921YORKTN3
Adder
130.26705882352942110.727
3150791HOPHCF3
80/20
2.6772.677
3150651CHESTF6
80/20
20.66420.664
3150851SPRUNCC
80/20
0.1830.183
3150861SPRUNCD
80/20
0.1830.183
3152331SURRY 2
80/20
27.29427.294
957871AF2-081 C
Adder
10.989.333
933291AC2-141 C
80/20
33.66433.664
940641AE2-051 C
80/20
18.48818.488
316274AC1-208 C
Adder
9.0917647058823537.728
3151311EDGECMA
Adder
15.22352941176470512.94
3138533PONTONDP
Adder
0.62941176470588240.535
316336AC2-165 C
Adder
10.1094117647058828.593
3152251N ANNA1
80/20
55.32355.323
316303AF2-085
80/20
4.3634.363
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.65727.657
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.08222.082
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.7473.747
LAGNLTFEXP_LAGN->PJM
CLTF
7.6777.677
NYPJM->LTFIMP_NY
CLTF
2.8062.806
LGEELTFEXP_LGEE->PJM
CLTF
1.2221.222
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.2865.286
CBM South 2LTFEXP_CBM-S2->PJM
CBM
94.17394.173
CPLELTFEXP_CPLE->PJM
CLTF
11.08811.088
TVALTFEXP_TVA->PJM
CLTF
6.1396.139
SIGELTFEXP_SIGE->PJM
CLTF
0.2370.237

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.54 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4631.24
MW Contribution:137.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
925332AB2-190 E
Adder
6.8164705882352945.794
935162AD1-151 E
Adder
9.1294117647058827.76
927226AC1-216 E
Adder
6.5917647058823535.603
924814AB2-134 E
Adder
10.7988235294117659.179
939191AE1-149 C
Adder
9.8529411764705898.375
944641AF1-129 C
Adder
87.4717647058823574.351
316240AF1-291 C
Adder
1.86705882352941191.587
936666AD2-085 E
Adder
5.195294117647064.416
942342AE2-247 E
Adder
1.90588235294117661.62
943461AF1-017 C
Adder
1.2482352941176471.061
3143316POE
Adder
1.28823529411764711.095
932596AC2-079 E
Adder
8.6588235294117667.36
316311AC2-079 C
Adder
5.3070588235294124.511
941591AE2-156 C
Adder
16.57647058823529614.09
944591AF1-124 C
Adder
42.5247058823529436.146
944601AF1-125 C
Adder
41.7211764705882435.463
919152AA1-139 E1
Adder
3.78941176470588253.221
938532AE1-072 E
Adder
8.4941176470588247.22
3146326AYDLETT TAP
Adder
1.25764705882352931.069
917122Z2-027 E
Adder
1.24470588235294131.058
901082W1-029 E
Adder
29.54000000000000325.109
938771AE1-103 C
Adder
2.72117647058823582.313
3145413WATKINS
Adder
0.64235294117647070.546
920692AA2-178 E
Adder
3.8023529411764713.232
934521AD1-076 C
Adder
11.3094117647058829.613
934511AD1-075 C
Adder
7.7847058823529426.617
316233AE1-074 C
Adder
2.5458823529411772.164
920042AA2-088 E OP
Adder
9.8670588235294128.387
960081AF2-299 C
Adder
1.76235294117647071.498
966622AG1-532 E
Adder
0.88117647058823530.749
926072AC1-086 E
Adder
8.9094117647058837.573
3145723EMPORIA
Adder
0.405882352941176470.345
923573AB1-173 E OP
Adder
3.07647058823529432.615
919692AA2-053 E OP
Adder
3.93176470588235333.342
944011AF1-069 C
50/50
13.59813.598
926206AC1-098 E
Adder
3.35647058823529452.853
963041AG1-153 C
Adder
5.7788235294117654.912
925785AC1-054 E
Adder
3.18705882352941172.709
936261AD2-033 C
Adder
12.02117647058823610.218
962562AG1-105 E
Adder
5.3929411764705884.584
959311AF2-222 C
Adder
15.39294117647058813.084
961791AG1-021 C
Adder
1.65764705882352951.409
3147133PAMPLIN
Adder
0.91529411764705890.778
942462AE2-259 E
Adder
6.1105882352941175.194
3151751LOISA D
50/50
2.7452.745
3151731LOISA B
50/50
2.7452.745
966002AG1-469 E
50/50
0.9930.993
316045AC1-158 C2
50/50
19.48619.486
926739AC1-158 E1
50/50
50.96750.967
316164AC1-076_C
50/50
1.1311.131
316170AC1-121 C
50/50
2.7692.769
926502AC1-121 E
50/50
1.3031.303
940431AE2-027 C
Adder
11.2058823529411789.525
3150651CHESTF6
Adder
15.92588235294117813.537
946262AF1-291 E
Adder
1.24470588235294131.058
934576AD1-082 E
Adder
4.0564705882352943.448
316084AB2-161 E
Adder
5.0917647058823544.328
3145256KINGFORK
Adder
0.92470588235294130.786
925522AC1-027 E
Adder
1.1282352941176470.959
943612AF1-032 E
Adder
0.85764705882352940.729
941102AE2-104 E
Adder
4.9423529411764714.201
3145506HICKORY
Adder
2.02235294117647071.719
944602AF1-125 E
Adder
95.5082352941176581.182
957872AF2-081 E
Adder
3.9717647058823533.376
957871AF2-081 C
Adder
9.2670588235294127.877
933292AC2-141 E
Adder
12.0070588235294110.206
933291AC2-141 C
Adder
28.12941176470588223.91
926755AC1-161 E
Adder
12.0070588235294110.206
940492AE2-034 E
Adder
2.85176470588235282.424
3145946PLYMOUTH TP
Adder
0.29882352941176470.254
934522AD1-076 E
Adder
5.7635294117647064.899
938552AE1-074 E
Adder
1.28235294117647071.09
933982AD1-022 E
Adder
4.4070588235294123.746
943172AE2-346 E
Adder
0.56117647058823530.477
940641AE2-051 C
50/50
18.07818.078
918492AA1-063AE OP
Adder
3.80117647058823543.231
925122AB2-169 E
Adder
5.2764705882352954.485
917332KELFORD E
Adder
1.51764705882352961.29
946282AF1-292 E
Adder
0.97294117647058820.827
944012AF1-069 E
50/50
5.2835.283
932632AC2-084 E
Adder
2.96705882352941152.522
926214AC1-099 E
Adder
1.1082352941176470.942
316274AC1-208 C
Adder
8.2905882352941187.047
927146AC1-208 E
Adder
3.68117647058823533.129
934622AD1-088 E
Adder
4.5117647058823533.835
937482AD2-202 E
Adder
1.02705882352941180.873
934612AD1-087 E
Adder
3.50941176470588272.983
924162AB2-060 E OP
Adder
3.95764705882352933.364
964242AG1-285 E
Adder
7.7211764705882356.563
938562AE1-075 E
Adder
1.0917647058823530.928
961792AG1-021 E
Adder
1.4117647058823531.2
961611AG1-000B C
Adder
13.8152941176470611.743
939192AE1-149 E
Adder
6.5694117647058825.584
939312AE1-162 E
Adder
1.27764705882352961.086
942002AE2-212 E
Adder
1.2952941176470591.101
942001AE2-212 C
Adder
1.94235294117647061.651
3150831SPRUNCA
Adder
8.1435294117647056.922
3150841SPRUNCB
Adder
8.1435294117647056.922
926662AC1-147 E
Adder
1.22588235294117661.042
916192Z1-068 E
Adder
1.74235294117647071.481
957492AF2-043 E
Adder
1.31882352941176471.121
941101AE2-104 C
Adder
3.10941176470588232.643
934065AD1-033 E
Adder
4.6541176470588243.956
937226AE2-253 E
Adder
5.4188235294117654.606
944581AF1-123 C
Adder
42.37411764705882436.018
940541AE2-040 C
Adder
2.78823529411764742.37
923852AB2-025 E
Adder
1.1282352941176470.959
940481AE2-033 C
Adder
15.6752941176470613.324
940482AE2-033 E
Adder
10.5670588235294118.982
934501AD1-074 C
Adder
31.13882352941176626.468
939412AE1-173 E
Adder
61.5211764705882452.293
924517AB2-100 E2
Adder
2.74588235294117672.334
961942AG1-037 E
Adder
0.311764705882352940.265
316141AB2-099 E
Adder
0.234117647058823540.199
961941AG1-037 C
Adder
0.46705882352941180.397
923263AB1-132 E OP
Adder
5.697647058823534.843
316088AB2-174 E
Adder
6.1235294117647065.205
923994AB2-040_E
Adder
5.76941176470588254.904
941031AE2-094 C
50/50
41.61841.618
941032AE2-094 E
50/50
18.6418.64
957482AF2-042 E
Adder
35.55176470588235630.219
957481AF2-042 C
Adder
53.3270588235294245.328
934621AD1-088 C
Adder
9.3717647058823547.966
935172AD1-152 E
Adder
5.1847058823529414.407
924322AB2-079 E O1
Adder
1.23529411764705891.05
924312AB2-078 E O1
Adder
1.23529411764705891.05
936262AD2-033 E
Adder
8.0141176470588256.812
958502AF2-144 E
Adder
1.2588235294117651.07
923862AB2-026 E
Adder
1.28117647058823541.089
925612AC1-036 E
Adder
0.79294117647058830.674
958211AF2-115 C
Adder
2.0717647058823531.761
946301AF1-294 C
Adder
3.4070588235294122.896
946302AF1-294 E
Adder
2.88470588235294122.452
942461AE2-259 C
Adder
9.1658823529411777.791
316192AB2-158 C
50/50
3.6573.657
3151801S ANNAS2
50/50
1.381.38
3151791S ANNAG2
50/50
2.6852.685
3151771S ANNAG1
50/50
2.6852.685
3151781S ANNAS1
50/50
1.381.38
3151761LOISA E
50/50
5.5965.596
966001AG1-469 C
50/50
1.9871.987
926740AC1-158 E2
50/50
50.96750.967
925672AC1-043 E
Adder
9.4635294117647078.044
208900BRIS G1
50/50
-2.836-2.836
208901BRIS G2
50/50
-3.356-3.356
940432AE2-027 E
Adder
7.4705882352941186.35
3150731STONECA
Adder
0.92705882352941180.788
935161AD1-151 C
Adder
13.69411764705882511.64
934012AD1-025 E
Adder
8.5352941176470597.255
935112AD1-144 E
Adder
0.85764705882352940.729
943462AF1-017 E
Adder
2.03764705882352941.732
316349AD2-085 C
Adder
3.1835294117647062.706
942341AE2-247 C
Adder
1.38000000000000011.173
932046AC2-012 E
Adder
12.12705882352941210.308
958161AF2-110 C
Adder
1.26823529411764711.078
958162AF2-110 E
Adder
2.01764705882352931.715
944582AF1-123 E
Adder
97.0317647058823782.477
944592AF1-124 E
Adder
97.3823529411764882.775
3138533PONTONDP
Adder
0.61411764705882350.522
316336AC2-165 C
Adder
10.0588235294117668.55
3152251N ANNA1
50/50
89.57189.571
3151721LOISA A
50/50
2.7312.731
926004AC1-076_E
50/50
6.486.48
316254AC1-120 C
50/50
8.0618.061
316257AC1-043 C
Adder
5.84.93
934862AD1-115 E
Adder
4.73176470588235354.022
919153AA1-139 E2
Adder
3.78941176470588253.221
938531AE1-072 C
Adder
16.29411764705882213.85
923832AB2-022 E
Adder
1.14941176470588240.977
913392Y1-086 E
Adder
2.03647058823529431.731
938772AE1-103 E
Adder
3.75764705882352963.194
916042Z1-036 E
Adder
26.4694117647058822.499
3145393UNCAMP
Adder
5.65176470588235354.804
934502AD1-074 E
Adder
15.85176470588235313.474
934512AD1-075 E
Adder
3.96235294117647063.368
939411AE1-173 C
Adder
92.2811764705882478.439
933981AD1-022 C
Adder
8.0941176470588236.88
900672V4-068 E
Adder
0.33058823529411770.281
918512AA1-065 E OP
Adder
5.1070588235294124.341
924516AB2-100 E1
Adder
2.74588235294117672.334
940642AE2-051 E
50/50
12.05212.052
966621AG1-532 C
Adder
1.32117647058823541.123
960082AF2-299 E
Adder
1.17529411764705880.999
946281AF1-292 C
Adder
1.45882352941176461.24
926071AC1-086 C
Adder
19.57647058823529616.64
3137643SOCKMAN
Adder
0.66588235294117650.566
963042AG1-153 E
Adder
8.6682352941176477.368
924022AB2-043 E O1
Adder
4.7941176470588244.075
924302AB2-077 E O1
Adder
1.23529411764705891.05
964241AG1-285 C
Adder
11.5811764705882349.844
3147223TWITTYS
Adder
0.87882352941176480.747
962561AG1-105 C
Adder
8.0894117647058836.876
959312AF2-222 E
Adder
10.3129411764705888.766
958212AF2-115 E
Adder
1.76470588235294111.5
933502AC2-165 E
Adder
7.5705882352941176.435
3152261N ANNA2
50/50
89.60889.608
925022AB2-158 E
50/50
9.7219.721
3151741LOISA C
50/50
2.7452.745
316044AC1-158 C1
50/50
19.48619.486
926486AC1-120 E
50/50
4.1534.153
934861AD1-115 C
Adder
2.92.465
316303AF2-085
50/50
4.3644.364
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.22125.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.23820.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.4183.418
LAGNLTFEXP_LAGN->PJM
CLTF
7.0687.068
NYPJM->LTFIMP_NY
CLTF
2.7142.714
LGEELTFEXP_LGEE->PJM
CLTF
1.0981.098
WECLTFEXP_WEC->PJM
CLTF
0.5410.541
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.0035.003
CBM South 2LTFEXP_CBM-S2->PJM
CBM
88.42988.429
CPLELTFEXP_CPLE->PJM
CLTF
10.49610.496
TVALTFEXP_TVA->PJM
CLTF
5.6275.627
O66PJM->LTFIMP_O-066
CMTX_NF
36.7236.72
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7645.764
SIGELTFEXP_SIGE->PJM
CLTF
0.2140.214
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 545T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314916 CKT 1                /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H3T539_SRT-A'
 OPEN BRANCH FROM BUS 314130 TO BUS 314900 CKT 2   /*6BRISTER     230.0 - 8BRISTER     500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314919 CKT 1   /*8BRISTER     500.0 - 8OX          500.0
END
CONTINGENCY 'DVP_P4-2: H1T539_SRT-S'
 OPEN BRANCH FROM BUS 314130 TO BUS 314900 CKT 1                /*6BRISTER     230.0 - 8BRISTER     500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314919 CKT 1                /*8BRISTER     500.0 - 8OX          500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 539_SRT-A'
 OPEN BRANCH FROM BUS 314900 TO BUS 314919 CKT 1   /*8BRISTER     500.0 - 8OX          500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 568T575_SRT-A'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1   /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1   /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P7-1: LN 2101-569_SRT-S'
 OPEN BRANCH FROM BUS 313712 TO BUS 313716 CKT 1                /*6VINTHIL TP  230.0 - 6VINTHIL DP  230.0
 OPEN BRANCH FROM BUS 313712 TO BUS 314119 CKT 1                /*6VINTHIL TP  230.0 - 6NOKESVL     230.0
 OPEN BRANCH FROM BUS 313712 TO BUS 314125 CKT 1                /*6VINTHIL TP  230.0 - 6VINTHIL     230.0
 OPEN BRANCH FROM BUS 314119 TO BUS 314130 CKT 1                /*6NOKESVL     230.0 - 6BRISTER     230.0
 OPEN BRANCH FROM BUS 314913 TO BUS 314916 CKT 1                /*8LOUDOUN     500.0 - 8MORRSVL     500.0
 OPEN BUS 313712                                                /*6VINTHIL TP  230.0
 OPEN BUS 313716                                                /*6VINTHIL DP  230.0
 OPEN BUS 314119                                                /*6NOKESVL     230.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
314212 to 314150 ckt 1
314150 to 939260 ckt 1
314902 to 314914 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314911 to 314922 ckt 1
314914 to 314322 ckt 1
314914 to 314918 ckt 1
314916 to 314913 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314919 to 314904 ckt 1
314934 to 314916 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 567_SRT-A
OPAC117.56 %934.92B1099.1187.98
GD1DVP
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
OPAC119.65 %663.64B794.0547.33
GD1DVP
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC103.25 %984.18B1016.2148.69
GD1DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
DVP_P1-2: LN 557_SRT-S
OPAC108.08 %879.84B950.8978.65
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Base Case
OPAC120.66 %678.68A818.89161.31
GD1DVP
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
OPAC110.61 %663.64B734.0447.27
GD1DVP
6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 2 transformer
DVP_P1-2: LN 574_SRT-S_SENS
OPAC103.88 %889.43B923.9745.9
GD1DVP
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
OPAC117.46 %678.68B797.1663.39
GD1DVP
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC103.2 %984.18B1015.6848.69
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Base Case
OPAC104.13 %3220.44A3353.36166.38
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC136.2 %2442.12B3326.15257.42
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC115.81 %4070.2B4713.58247.5
GD1DVP
8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
OPAC113.6 %3220.44B3658.55158.22
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
OPAC126.34 %1058.16B1336.8861.92
GD1DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC106.0 %2442.12B2588.61147.82
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
OPAC105.29 %3220.44B3390.96137.93

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 567_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.56 %
Rating:934.92 MVA
Rating Type:B
MVA to Mitigate:1099.11
MW Contribution:87.98
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:123.89 %
Rating:934.92 MVA
Rating Type:B
MVA to Mitigate:1158.26
MW Contribution:89.42
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316240AF1-291 C
Adder
1.21647058823529421.034
944641AF1-129 C
Adder
58.0164705882352949.314
924814AB2-134 E
Adder
9.155294117647067.782
919152AA1-139 E1
Adder
2.4294117647058822.065
942342AE2-247 E
Adder
1.22588235294117661.042
316280AD1-041 C
50/50
0.9810.981
920042AA2-088 E OP
Adder
5.4247058823529414.611
934511AD1-075 C
Adder
4.4458823529411773.779
934521AD1-076 C
Adder
6.4588235294117655.49
939246AE1-155 E
50/50
9.7559.755
919692AA2-053 E OP
Adder
1.9247058823529411.636
957972AF2-091 E
Adder
2.38117647058823542.024
3150831SPRUNCA
Adder
4.643.944
3150841SPRUNCB
Adder
4.643.944
939412AE1-173 E
Adder
28.724.395
926662AC1-147 E
Adder
0.80941176470588230.688
916192Z1-068 E
Adder
1.13647058823529410.966
316076AC2-137 E
50/50
1.5851.585
957492AF2-043 E
Adder
0.85647058823529410.728
923852AB2-025 E
Adder
0.53647058823529410.456
923842AB2-024 E
50/50
2.2272.227
940642AE2-051 E
Adder
5.0282352941176474.274
919153AA1-139 E2
Adder
2.4294117647058822.065
943462AF1-017 E
Adder
1.31058823529411781.114
942341AE2-247 C
Adder
0.88823529411764710.755
316382AG1-145 C
50/50
0.3770.377
926412AC1-112 E
Adder
0.95058823529411770.808
958162AF2-110 E
Adder
1.29411764705882361.1
924516AB2-100 E1
Adder
1.31411764705882361.117
934512AD1-075 E
Adder
2.2635294117647061.924
934502AD1-074 E
Adder
9.0529411764705887.695
918512AA1-065 E OP
Adder
2.78823529411764742.37
963612AG1-210 E
Adder
1.11764705882352940.95
942002AE2-212 E
Adder
0.79294117647058830.674
940431AE2-027 C
Adder
8.0564705882352946.848
944581AF1-123 C
Adder
27.16823529411764723.093
941101AE2-104 C
Adder
1.99529411764705891.696
934392AD1-063 E
50/50
1.2811.281
943742AF1-042 E
50/50
5.3215.321
962862AG1-135 E
50/50
4.5334.533
966662AG1-536 E
50/50
8.0978.097
316141AB2-099 E
Adder
0.124705882352941180.106
944492AF1-114 E
Adder
7.0035294117647065.953
933292AC2-141 E
Adder
7.7070588235294126.551
946262AF1-291 E
Adder
0.81058823529411760.689
3150651CHESTF6
Adder
10.5635294117647058.979
944602AF1-125 E
Adder
61.2352941176470652.05
3145506HICKORY
Adder
1.3035294117647061.108
934576AD1-082 E
Adder
2.622.227
957871AF2-081 C
Adder
5.94117647058823555.05
943612AF1-032 E
Adder
0.5564705882352940.473
3130536PAPERMILL
50/50
8.178.17
939602AE1-190 E
50/50
1.6071.607
3150731STONECA
Adder
5.1505882352941184.378
932046AC2-012 E
Adder
8.0047058823529426.804
935161AD1-151 C
Adder
11.755294117647069.992
938531AE1-072 C
Adder
10.4258823529411768.862
958161AF2-110 C
Adder
0.81411764705882350.692
316059AD1-063 C
50/50
0.3140.314
3145393UNCAMP
Adder
3.34588235294117632.844
933981AD1-022 C
Adder
4.5705882352941173.885
900672V4-068 E
Adder
0.178823529411764710.152
942001AE2-212 C
Adder
1.18941176470588221.011
939192AE1-149 E
Adder
4.2529411764705883.615
934065AD1-033 E
Adder
3.0082352941176472.557
939312AE1-162 E
Adder
0.95764705882352940.814
937226AE2-253 E
Adder
3.48117647058823552.959
924517AB2-100 E2
Adder
1.31411764705882361.117
934501AD1-074 C
Adder
17.7847058823529415.117
943741AF1-042 C
50/50
3.2613.261
962861AG1-135 C
50/50
6.7996.799
3141813NORNECK
Adder
0.99176470588235290.843
961611AG1-000B C
Adder
11.3023529411764719.607
3138116ELKO L286
50/50
1.6531.653
940541AE2-040 C
Adder
1.32705882352941161.128
940482AE2-033 E
Adder
5.0317647058823534.277
940481AE2-033 C
Adder
7.4635294117647066.344
963611AG1-210 C
Adder
0.74470588235294120.633
923263AB1-132 E OP
Adder
2.76588235294117672.351
935162AD1-151 E
Adder
7.837647058823536.662
938532AE1-072 E
Adder
5.4352941176470594.62
3146326AYDLETT TAP
Adder
0.80352941176470590.683
943461AF1-017 C
Adder
0.80352941176470590.683
316311AC2-079 C
Adder
3.4117647058823532.9
932596AC2-079 E
Adder
5.5670588235294124.732
917122Z2-027 E
Adder
0.78588235294117660.668
957832AF2-077 E
Adder
1.39411764705882371.185
940551AE2-041 C
50/50
8.5438.543
920692AA2-178 E
Adder
2.23411764705882381.899
939611AE1-191 C
50/50
1.5481.548
940492AE2-034 E
Adder
1.67529411764705881.424
934522AD1-076 E
Adder
3.2917647058823532.798
936591AD2-074 C
50/50
6.2326.232
943172AE2-346 E
Adder
0.30.255
918492AA1-063AE OP
Adder
1.9235294117647061.635
917332KELFORD E
Adder
0.78588235294117660.668
925122AB2-169 E
Adder
2.8305882352941182.406
3143316POE
Adder
0.72470588235294120.616
939191AE1-149 C
Adder
6.3788235294117655.422
316159AE1-175 C
50/50
0.4180.418
901082W1-029 E
Adder
18.5929411764705915.804
3141843SHACKLE
50/50
0.6030.603
316201AC1-065 C
50/50
1.8491.849
934146AD1-041 E
50/50
4.0174.017
957601AF2-054 C
50/50
2.372.37
316404AE1-155 C
50/50
2.3762.376
958261AF2-120 C
50/50
7.0057.005
939411AE1-173 C
Adder
43.0494117647058836.592
940432AE2-027 E
Adder
5.3717647058823534.566
934012AD1-025 E
Adder
7.2364705882352946.151
913392Y1-086 E
Adder
1.29176470588235311.098
939612AE1-191 E
50/50
6.4276.427
957602AF2-054 E
50/50
1.581.58
966661AG1-536 C
50/50
6.0266.026
958262AF2-120 E
50/50
4.674.67
316078AC2-138 E
Adder
1.04235294117647070.886
944491AF1-114 C
Adder
5.0717647058823534.311
926755AC1-161 E
Adder
7.7070588235294126.551
933291AC2-141 C
Adder
18.0552941176470615.347
925522AC1-027 E
Adder
0.73647058823529410.626
944631AF1-128 C
Adder
38.5941176470588232.805
957872AF2-081 E
Adder
2.5458823529411772.164
3145256KINGFORK
Adder
0.64941176470588250.552
3150921YORKTN3
Adder
101.5176470588235486.29
316160AE1-175 E
50/50
1.2681.268
941102AE2-104 E
Adder
3.1717647058823532.696
936592AD2-074 E
50/50
10.16810.168
316157AD2-030 E
50/50
1.331.33
964211AG1-282 C
50/50
2.3232.323
961941AG1-037 C
Adder
0.250588235294117670.213
961942AG1-037 E
Adder
0.167058823529411760.142
957191AF2-013 C
Adder
8.1011764705882366.886
941591AE2-156 C
Adder
10.929411764705889.29
925332AB2-190 E
Adder
5.91411764705882355.027
944591AF1-124 C
Adder
27.26470588235294223.175
944601AF1-125 C
Adder
26.7494117647058822.737
927226AC1-216 E
Adder
5.5894117647058834.751
3150601CHESTF5
Adder
61.6852.428
936666AD2-085 E
Adder
3.34117647058823542.84
962962AG1-145 E
50/50
1.5371.537
938771AE1-103 C
Adder
1.63411764705882371.389
316156AD2-030 C
50/50
0.4250.425
3145413WATKINS
Adder
0.371764705882352940.316
964212AG1-282 E
50/50
1.5491.549
926072AC1-086 E
Adder
4.3247058823529423.676
316075AC2-137 C
50/50
0.4510.451
925865AC1-065 E
50/50
18.90818.908
939601AE1-190 C
50/50
0.3840.384
961951AG1-038 C
50/50
3.6043.604
961952AG1-038 E
50/50
4.9774.977
936582AD2-073 E
Adder
1.1482352941176470.976
944582AF1-123 E
Adder
62.2117647058823652.88
944592AF1-124 E
Adder
62.43647058823529553.071
935112AD1-144 E
Adder
0.60235294117647060.512
316349AD2-085 C
Adder
2.0482352941176471.741
930122AB1-027 E
Adder
1.1682352941176470.993
316169AC1-164 GEN
50/50
59.62859.628
923832AB2-022 E
Adder
0.72941176470588230.62
316314AB2-024 C
50/50
0.3640.364
938772AE1-103 E
Adder
2.25764705882352961.919
916042Z1-036 E
Adder
16.12117647058823513.703
926071AC1-086 C
Adder
9.502352941176478.077
957971AF2-091 C
Adder
1.7247058823529411.466
940641AE2-051 C
Adder
7.5435294117647066.412
316084AB2-161 E
Adder
3.2882352941176472.795
926785AC1-164_E
50/50
26.78926.789
943471AF1-018 C
50/50
8.5438.543
3145946PLYMOUTH TP
Adder
0.171764705882352930.146
933982AD1-022 E
Adder
2.48823529411764752.115
926472AC1-118 E
Adder
1.07411764705882360.913
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.0931.093
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.8973.897
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.4280.428
LAGNLTFEXP_LAGN->PJM
CLTF
1.6451.645
NYPJM->LTFIMP_NY
CLTF
0.5590.559
LGEELTFEXP_LGEE->PJM
CLTF
0.0680.068
WECLTFEXP_WEC->PJM
CLTF
0.0320.032
G-007PJM->LTFIMP_G-007
CMTX_NF
1.1231.123
SIGELTFEXP_SIGE->PJM
CLTF
0.0210.021
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.8251.825
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.11329.113
CPLELTFEXP_CPLE->PJM
CLTF
3.8353.835
TVALTFEXP_TVA->PJM
CLTF
1.2591.259
O66PJM->LTFIMP_O-066
CMTX_NF
7.1797.179

Details for 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:119.65 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:794.05
MW Contribution:47.33
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:118.19 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:784.36
MW Contribution:45.66
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
924814AB2-134 E
50/50
7.137.13
3150641CHESTS8
50/50
2.4652.465
919152AA1-139 E1
Adder
1.30470588235294121.109
942342AE2-247 E
Adder
0.68588235294117650.583
939246AE1-155 E
Adder
3.80823529411764743.237
316132AB2-190 C
50/50
2.5252.525
919153AA1-139 E2
Adder
1.30470588235294121.109
943462AF1-017 E
Adder
0.73294117647058820.623
942341AE2-247 C
Adder
0.49647058823529410.422
958162AF2-110 E
Adder
0.70235294117647060.597
963612AG1-210 E
Adder
0.43294117647058820.368
940431AE2-027 C
Adder
3.98470588235294133.387
3150771HOPHCF1
50/50
1.6511.651
944581AF1-123 C
Adder
14.61529411764705912.423
941101AE2-104 C
Adder
1.08235294117647070.92
934392AD1-063 E
Adder
0.50823529411764710.432
943742AF1-042 E
Adder
2.09647058823529431.782
962862AG1-135 E
Adder
1.77411764705882361.508
966662AG1-536 E
Adder
3.16117647058823532.687
3150731STONECA
50/50
4.6744.674
932046AC2-012 E
Adder
4.42705882352941153.763
935161AD1-151 C
50/50
9.4829.482
938531AE1-072 C
Adder
5.5941176470588234.755
958161AF2-110 C
Adder
0.44117647058823530.375
3145393UNCAMP
Adder
1.761.496
939192AE1-149 E
Adder
2.56235294117647072.178
3150781HOPHCF2
50/50
1.6511.651
934065AD1-033 E
Adder
1.62117647058823521.378
939312AE1-162 E
Adder
0.60.51
937226AE2-253 E
Adder
1.86941176470588231.589
943741AF1-042 C
Adder
1.28470588235294141.092
962861AG1-135 C
Adder
2.66117647058823532.262
3141813NORNECK
Adder
0.38352941176470590.326
961611AG1-000B C
Adder
7.877647058823536.696
3138116ELKO L286
Adder
0.55176470588235290.469
963611AG1-210 C
Adder
0.288235294117647030.245
935162AD1-151 E
50/50
6.3216.321
938532AE1-072 E
Adder
2.9164705882352942.479
3146326AYDLETT TAP
Adder
0.431764705882352940.367
943461AF1-017 C
Adder
0.44941176470588240.382
316311AC2-079 C
Adder
1.90117647058823551.616
932596AC2-079 E
Adder
3.10117647058823562.636
917122Z2-027 E
Adder
0.420.357
957832AF2-077 E
Adder
0.61529411764705890.523
940551AE2-041 C
Adder
3.3882352941176472.88
933292AC2-141 E
Adder
3.96117647058823553.367
944602AF1-125 E
Adder
32.9423529411764728.001
3145506HICKORY
Adder
0.70117647058823530.596
934576AD1-082 E
Adder
1.53176470588235311.302
957871AF2-081 C
Adder
3.1905882352941182.712
943612AF1-032 E
Adder
0.30.255
3130536PAPERMILL
Adder
3.2082352941176472.727
939602AE1-190 E
Adder
0.64823529411764710.551
936591AD2-074 C
Adder
2.4564705882352942.088
939191AE1-149 C
Adder
3.84235294117647053.266
934011AD1-025 C
50/50
1.4651.465
316033AB2-134 GEN
50/50
1.1851.185
901082W1-029 E
Adder
9.9247058823529428.436
934146AD1-041 E
Adder
1.621.377
957601AF2-054 C
Adder
0.96117647058823530.817
958261AF2-120 C
Adder
2.73529411764705932.325
940432AE2-027 E
Adder
2.65647058823529442.258
934012AD1-025 E
50/50
5.6355.635
913392Y1-086 E
Adder
0.6917647058823530.588
939612AE1-191 E
Adder
2.5917647058823532.203
957602AF2-054 E
Adder
0.64117647058823530.545
966661AG1-536 C
Adder
2.35294117647058832
958262AF2-120 E
Adder
1.8235294117647061.55
316078AC2-138 E
Adder
0.40352941176470590.343
926755AC1-161 E
Adder
3.96117647058823553.367
933291AC2-141 C
Adder
9.287.888
3150761HOPPOLC
50/50
1.0381.038
925522AC1-027 E
Adder
0.402352941176470640.342
944631AF1-128 C
50/50
49.90849.908
957872AF2-081 E
Adder
1.36705882352941171.162
3145256KINGFORK
Adder
0.360.306
3150921YORKTN3
Adder
49.1152941176470641.748
316160AE1-175 E
Adder
0.54352941176470590.462
941102AE2-104 E
Adder
1.72117647058823551.463
936592AD2-074 E
Adder
4.00705882352941253.406
3150801HOPHCF4
50/50
2.5062.506
3150791HOPHCF3
50/50
1.6511.651
926662AC1-147 E
Adder
0.44705882352941180.38
916192Z1-068 E
Adder
0.620.527
316369AC1-216 C
50/50
0.9040.904
316076AC2-137 E
Adder
0.52823529411764710.449
957492AF2-043 E
Adder
0.46117647058823530.392
923842AB2-024 E
Adder
0.87294117647058820.742
316157AD2-030 E
Adder
0.53882352941176470.458
964211AG1-282 C
Adder
0.89529411764705890.761
941591AE2-156 C
Adder
6.0388235294117655.133
925332AB2-190 E
50/50
4.9124.912
944591AF1-124 C
Adder
14.66705882352941312.467
944601AF1-125 C
Adder
14.39058823529411812.232
927226AC1-216 E
50/50
4.3534.353
3150601CHESTF5
50/50
79.76279.762
936666AD2-085 E
Adder
1.86823529411764721.588
962962AG1-145 E
Adder
0.65882352941176480.56
938771AE1-103 C
Adder
0.86470588235294120.735
964212AG1-282 E
Adder
0.59647058823529410.507
3150621CHESTS7
50/50
2.2342.234
3150611CHESTG7
50/50
4.8674.867
925865AC1-065 E
Adder
7.5929411764705886.454
961951AG1-038 C
Adder
1.42000000000000021.207
961952AG1-038 E
Adder
1.96117647058823531.667
936582AD2-073 E
Adder
0.43647058823529410.371
944582AF1-123 E
Adder
33.4682352941176528.448
944592AF1-124 E
Adder
33.5894117647058828.551
3150631CHESTG8
50/50
4.7894.789
935112AD1-144 E
Adder
0.33411764705882350.284
316349AD2-085 C
Adder
1.14470588235294120.973
316169AC1-164 GEN
50/50
22.41822.418
923832AB2-022 E
Adder
0.39058823529411770.332
938772AE1-103 E
Adder
1.19411764705882351.015
916042Z1-036 E
Adder
8.517647058823537.24
316084AB2-161 E
Adder
1.92235294117647061.634
926785AC1-164_E
50/50
10.07210.072
943471AF1-018 C
Adder
3.3882352941176472.88
926472AC1-118 E
Adder
0.40352941176470590.343
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.4860.486
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.7321.732
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.1910.191
LAGNLTFEXP_LAGN->PJM
CLTF
0.7290.729
NYPJM->LTFIMP_NY
CLTF
0.280.28
LGEELTFEXP_LGEE->PJM
CLTF
0.0310.031
WECLTFEXP_WEC->PJM
CLTF
0.0140.014
G-007PJM->LTFIMP_G-007
CMTX_NF
0.5680.568
SIGELTFEXP_SIGE->PJM
CLTF
0.010.01
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.8090.809
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.85612.856
CPLELTFEXP_CPLE->PJM
CLTF
1.71.7
TVALTFEXP_TVA->PJM
CLTF
0.5590.559
O66PJM->LTFIMP_O-066
CMTX_NF
3.6293.629

Details for 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.25 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1016.21
MW Contribution:48.69
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.15 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:985.63
MW Contribution:45.0
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150731STONECA
50/50
4.5124.512
932046AC2-012 E
Adder
4.4823529411764713.81
961611AG1-000B C
Adder
7.342352941176476.241
940541AE2-040 C
Adder
1.56117647058823541.327
940482AE2-033 E
Adder
5.8329411764705884.958
940481AE2-033 C
Adder
8.6517647058823537.354
923263AB1-132 E OP
Adder
2.582.193
924312AB2-078 E O1
Adder
0.41176470588235290.35
935162AD1-151 E
50/50
6.0156.015
938532AE1-072 E
Adder
3.07058823529411742.61
3146326AYDLETT TAP
Adder
0.455294117647058850.387
943461AF1-017 C
Adder
0.61882352941176480.526
316311AC2-079 C
Adder
2.5717647058823532.186
932596AC2-079 E
Adder
4.1964705882352953.567
917122Z2-027 E
Adder
0.457647058823529460.389
920692AA2-178 E
Adder
1.4552941176470591.237
966622AG1-532 E
Adder
0.408235294117647030.347
922923AB1-081 E OP
Adder
1.321.122
933292AC2-141 E
Adder
3.78588235294117673.218
946262AF1-291 E
50/50
1.6321.632
3150651CHESTF6
50/50
21.89721.897
944602AF1-125 E
Adder
33.8847058823529428.802
3145506HICKORY
Adder
0.72352941176470590.615
934576AD1-082 E
50/50
2.5582.558
957871AF2-081 C
Adder
3.34117647058823542.84
943612AF1-032 E
Adder
0.320.272
940492AE2-034 E
Adder
1.09058823529411760.927
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
918492AA1-063AE OP
Adder
1.59411764705882361.355
937482AD2-202 E
Adder
0.32588235294117650.277
917332KELFORD E
Adder
0.61411764705882350.522
925122AB2-169 E
Adder
2.04352941176470631.737
316274AC1-208 C
Adder
3.3788235294117652.872
917342Z2-044 E
Adder
0.215294117647058830.183
3151311EDGECMA
Adder
5.5117647058823534.685
3143316POE
50/50
1.0861.086
939191AE1-149 C
50/50
7.1377.137
901082W1-029 E
Adder
10.9870588235294139.339
926206AC1-098 E
Adder
1.35999999999999991.156
939411AE1-173 C
Adder
31.5352941176470626.805
940432AE2-027 E
Adder
4.6964705882352943.992
934012AD1-025 E
Adder
5.3364705882352944.536
913392Y1-086 E
Adder
0.74470588235294120.633
3137643SOCKMAN
Adder
0.288235294117647030.245
316240AF1-291 C
50/50
2.4482.448
944641AF1-129 C
50/50
120.262120.262
924814AB2-134 E
Adder
6.7529411764705885.74
316381AD1-082 C
50/50
0.7330.733
919152AA1-139 E1
Adder
1.36588235294117651.161
942342AE2-247 E
Adder
0.94470588235294130.803
920042AA2-088 E OP
Adder
4.0811764705882353.469
934511AD1-075 C
Adder
3.01411764705882362.562
934521AD1-076 C
Adder
4.377647058823533.721
3145723EMPORIA
Adder
0.185882352941176470.158
923573AB1-173 E OP
Adder
1.36823529411764721.163
919692AA2-053 E OP
Adder
1.64941176470588241.402
925785AC1-054 E
Adder
1.2082352941176471.027
316263AC1-034 C
Adder
2.3517647058823531.999
926755AC1-161 E
Adder
3.78588235294117673.218
933291AC2-141 C
Adder
8.8694117647058827.539
3150761HOPPOLC
50/50
1.0021.002
925522AC1-027 E
Adder
0.410588235294117640.349
957872AF2-081 E
Adder
1.4317647058823531.217
3145256KINGFORK
Adder
0.357647058823529430.304
941102AE2-104 E
Adder
2.0188235294117651.716
964242AG1-285 E
Adder
2.5717647058823532.186
926214AC1-099 E
Adder
0.44941176470588240.382
932632AC2-084 E
Adder
1.20235294117647061.022
924162AB2-060 E OP
Adder
1.3117647058823531.115
942001AE2-212 C
50/50
2.1112.111
939192AE1-149 E
50/50
4.7584.758
3150781HOPHCF2
50/50
1.5941.594
934065AD1-033 E
Adder
1.6670588235294121.417
939312AE1-162 E
Adder
0.5717647058823530.486
937226AE2-253 E
Adder
1.9482352941176471.656
924517AB2-100 E2
Adder
1.36823529411764721.163
934501AD1-074 C
Adder
12.05529411764705810.247
957482AF2-042 E
Adder
11.3435294117647069.642
934621AD1-088 C
Adder
2.86941176470588262.439
935172AD1-152 E
Adder
1.6435294117647061.397
961671AG1-007 C
Adder
0.332941176470588240.283
3150831SPRUNCA
Adder
2.6776470588235292.276
3150841SPRUNCB
Adder
2.6776470588235292.276
939412AE1-173 E
Adder
21.0235294117647117.87
941032AE2-094 E
Adder
6.3247058823529425.376
941031AE2-094 C
Adder
14.12000000000000112.002
3150801HOPHCF4
50/50
2.4192.419
3150791HOPHCF3
50/50
1.5941.594
926662AC1-147 E
Adder
0.452941176470588240.385
916192Z1-068 E
Adder
0.63294117647058830.538
957492AF2-043 E
Adder
0.49294117647058820.419
923852AB2-025 E
Adder
0.6317647058823530.537
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
934321AD1-056 C
Adder
2.3988235294117652.039
934331AD1-057 C
Adder
1.33882352941176451.138
934332AD1-057 E
Adder
0.69647058823529410.592
934322AD1-056 E
Adder
1.30117647058823541.106
927022AC1-189 E
Adder
1.48235294117647071.26
925595AC1-034 E
Adder
1.77411764705882361.508
944011AF1-069 C
Adder
4.6141176470588243.922
941591AE2-156 C
Adder
6.1141176470588245.197
925332AB2-190 E
50/50
4.6914.691
944591AF1-124 C
Adder
15.08705882352941312.824
944601AF1-125 C
Adder
14.80235294117647312.582
927226AC1-216 E
Adder
4.122352941176473.504
936666AD2-085 E
Adder
2.5752941176470592.189
963041AG1-153 C
Adder
1.9482352941176471.656
938771AE1-103 C
Adder
1.11764705882352940.95
3145413WATKINS
Adder
0.26470588235294120.225
960081AF2-299 C
Adder
0.81647058823529410.694
926072AC1-086 E
Adder
4.0352941176470593.43
944012AF1-069 E
Adder
1.7917647058823531.523
946282AF1-292 E
Adder
0.45058823529411770.383
917512Z2-088 E OP1
Adder
1.73411764705882351.474
944582AF1-123 E
Adder
34.4258823529411829.262
944592AF1-124 E
Adder
34.55058823529411429.368
935112AD1-144 E
Adder
0.33176470588235290.282
316349AD2-085 C
Adder
1.57882352941176471.342
923832AB2-022 E
Adder
0.421176470588235260.358
963042AG1-153 E
Adder
2.92235294117647062.484
938772AE1-103 E
Adder
1.5435294117647061.312
916042Z1-036 E
Adder
9.9682352941176488.473
946281AF1-292 C
Adder
0.67529411764705880.574
960082AF2-299 E
Adder
0.54470588235294130.463
926071AC1-086 C
Adder
8.8647058823529427.535
964241AG1-285 C
Adder
3.85882352941176483.28
927021AC1-189 C
Adder
2.97529411764705862.529
924152AB2-059 E OP
Adder
1.87058823529411791.59
942002AE2-212 E
50/50
1.4081.408
940431AE2-027 C
Adder
7.0447058823529425.988
3150771HOPHCF1
50/50
1.5941.594
944581AF1-123 C
Adder
15.03411764705882412.779
941101AE2-104 C
Adder
1.26941176470588221.079
957481AF2-042 C
Adder
17.0152941176470614.463
316088AB2-174 E
Adder
2.7588235294117652.345
316141AB2-099 E
Adder
0.095294117647058830.081
923994AB2-040_E
Adder
2.56588235294117652.181
924322AB2-079 E O1
Adder
0.41176470588235290.35
961672AG1-007 E
Adder
0.188235294117647060.16
940642AE2-051 E
Adder
4.0635294117647063.454
316132AB2-190 C
50/50
2.4122.412
919153AA1-139 E2
Adder
1.36588235294117651.161
943462AF1-017 E
Adder
1.00941176470588250.858
942341AE2-247 C
Adder
0.68470588235294120.582
958162AF2-110 E
Adder
0.82470588235294120.701
924516AB2-100 E1
Adder
1.36823529411764721.163
934512AD1-075 E
Adder
1.53411764705882361.304
934502AD1-074 E
Adder
6.1364705882352945.216
966621AG1-532 C
Adder
0.61294117647058830.521
918512AA1-065 E OP
Adder
2.04235294117647071.736
924022AB2-043 E O1
Adder
1.60117647058823541.361
918532AA1-067 E
Adder
0.251764705882352950.214
940641AE2-051 C
Adder
6.0952941176470595.181
316084AB2-161 E
50/50
3.213.21
316083AB2-161 C
50/50
0.3210.321
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
933982AD1-022 E
Adder
1.721.462
934622AD1-088 E
Adder
1.38117647058823521.174
934612AD1-087 E
Adder
1.1117647058823530.945
927146AC1-208 E
Adder
1.51.275
935161AD1-151 C
50/50
9.0229.022
938531AE1-072 C
Adder
5.8905882352941185.007
958161AF2-110 C
Adder
0.51764705882352950.44
3145393UNCAMP
Adder
2.3247058823529411.976
933981AD1-022 C
Adder
3.162.686
900672V4-068 E
Adder
0.136470588235294120.116
924302AB2-077 E O1
Adder
0.41176470588235290.35
919710AA2-057 E
Adder
1.44823529411764731.231
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
NYPJM->LTFIMP_NY
CLTF
0.4360.436
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
WECLTFEXP_WEC->PJM
CLTF
0.140.14
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
TVALTFEXP_TVA->PJM
CLTF
1.561.56
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.08 %
Rating:879.84 MVA
Rating Type:B
MVA to Mitigate:950.89
MW Contribution:78.65
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:132.69 %
Rating:879.84 MVA
Rating Type:B
MVA to Mitigate:1167.49
MW Contribution:88.24
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944011AF1-069 C
Adder
4.7458823529411774.034
941591AE2-156 C
Adder
9.744705882352948.283
3150831SPRUNCA
Adder
6.84941176470588255.822
3150841SPRUNCB
Adder
6.84941176470588255.822
939412AE1-173 E
Adder
27.4976470588235323.373
941032AE2-094 E
Adder
7.0964705882352946.032
941031AE2-094 C
Adder
15.84470588235294213.468
926662AC1-147 E
Adder
0.72117647058823530.613
916192Z1-068 E
Adder
1.0152941176470590.863
933292AC2-141 E
Adder
6.8564705882352955.828
946262AF1-291 E
Adder
1.04588235294117650.889
3150651CHESTF6
Adder
13.78941176470588211.721
944602AF1-125 E
Adder
54.7376470588235346.527
3145506HICKORY
Adder
1.16588235294117660.991
934576AD1-082 E
Adder
2.6682352941176472.268
957871AF2-081 C
Adder
5.3211764705882354.523
938552AE1-074 E
Adder
0.81882352941176460.696
926755AC1-161 E
Adder
6.8564705882352955.828
933291AC2-141 C
Adder
16.0623529411764713.653
925522AC1-027 E
Adder
0.65764705882352950.559
944631AF1-128 C
Adder
29.89647058823529225.412
957872AF2-081 E
Adder
2.281.938
3145256KINGFORK
Adder
0.56470588235294120.48
3150921YORKTN3
Adder
72.7576470588235461.844
316160AE1-175 E
Adder
0.77529411764705890.659
316312AB1-027 C
50/50
0.4790.479
941102AE2-104 E
Adder
2.89058823529411772.457
315052AA1-145 CT2
50/50
4.444.44
936592AD2-074 E
Adder
5.9376470588235295.047
934782AD1-105 E
50/50
4.3454.345
316240AF1-291 C
Adder
1.56941176470588251.334
944641AF1-129 C
Adder
75.7352941176470664.375
924814AB2-134 E
Adder
8.3647058823529427.11
919152AA1-139 E1
Adder
2.1752941176470591.849
942342AE2-247 E
Adder
1.16941176470588240.994
920042AA2-088 E OP
Adder
5.164.386
934511AD1-075 C
Adder
4.1188235294117653.501
934521AD1-076 C
Adder
5.9847058823529415.087
3145723EMPORIA
Adder
0.195294117647058840.166
939246AE1-155 E
Adder
5.6705882352941184.82
923573AB1-173 E OP
Adder
1.4764705882352941.255
957972AF2-091 E
Adder
1.5517647058823531.319
944582AF1-123 E
Adder
55.6105882352941247.269
944592AF1-124 E
Adder
55.81176470588235447.44
935112AD1-144 E
Adder
0.52352941176470590.445
316349AD2-085 C
Adder
1.95294117647058821.66
930122AB1-027 E
50/50
1.2571.257
316169AC1-164 GEN
Adder
29.68117647058823425.229
923832AB2-022 E
Adder
0.65529411764705890.557
938772AE1-103 E
Adder
2.09411764705882361.78
916042Z1-036 E
Adder
14.65058823529411712.453
966882AG1-559 E
Adder
0.69411764705882350.59
939261AE1-157 C
Adder
6.5811764705882365.594
946281AF1-292 C
Adder
0.70235294117647060.597
960082AF2-299 E
Adder
0.56588235294117650.481
926071AC1-086 C
Adder
9.5835294117647068.146
957971AF2-091 C
Adder
1.12352941176470590.955
316076AC2-137 E
Adder
1.04588235294117650.889
957492AF2-043 E
Adder
0.76352941176470590.649
923852AB2-025 E
Adder
0.58235294117647060.495
966872AG1-558 E
50/50
1.2121.212
966871AG1-558 C
50/50
2.4052.405
923842AB2-024 E
Adder
1.2282352941176471.044
316157AD2-030 E
Adder
0.78705882352941180.669
964211AG1-282 C
Adder
1.32117647058823541.123
961941AG1-037 C
Adder
0.238823529411764740.203
961942AG1-037 E
Adder
0.158823529411764720.135
940642AE2-051 E
Adder
4.9588235294117654.215
3150681DARBY 2
50/50
2.2072.207
919153AA1-139 E2
Adder
2.1752941176470591.849
943462AF1-017 E
Adder
1.24941176470588241.062
942341AE2-247 C
Adder
0.84705882352941180.72
926412AC1-112 E
50/50
1.0221.022
958162AF2-110 E
Adder
1.181.003
924516AB2-100 E1
Adder
1.3717647058823531.166
934512AD1-075 E
Adder
2.09647058823529431.782
934502AD1-074 E
Adder
8.3882352941176477.13
966621AG1-532 C
Adder
0.63647058823529420.541
918512AA1-065 E OP
Adder
2.62941176470588232.235
963612AG1-210 E
Adder
0.64705882352941180.55
934781AD1-105 C
50/50
1.0481.048
316233AE1-074 C
Adder
1.62470588235294121.381
935162AD1-151 E
Adder
7.235294117647066.15
3150691DARBY 3
50/50
2.2142.214
938532AE1-072 E
Adder
4.8694117647058834.139
3146326AYDLETT TAP
Adder
0.720.612
943461AF1-017 C
Adder
0.76588235294117660.651
316311AC2-079 C
Adder
3.2352941176470592.75
932596AC2-079 E
Adder
5.284.488
917122Z2-027 E
Adder
0.70705882352941170.601
957832AF2-077 E
Adder
0.90470588235294120.769
3150481FOUR RIVERF
50/50
3.3563.356
315051AA1-145 CT1
50/50
4.4424.442
927042AC1-191 E
50/50
4.814.81
940551AE2-041 C
Adder
4.8305882352941174.106
920692AA2-178 E
Adder
2.05294117647058851.745
966622AG1-532 E
Adder
0.424705882352941160.361
3150731STONECA
Adder
4.9341176470588244.194
932046AC2-012 E
Adder
7.1352941176470596.065
935161AD1-151 C
Adder
10.8541176470588259.226
3150701DARBY 4
50/50
2.2172.217
938531AE1-072 C
Adder
9.3411764705882367.94
958161AF2-110 C
Adder
0.74235294117647070.631
3145393UNCAMP
Adder
3.11647058823529432.649
942002AE2-212 E
Adder
0.98705882352941180.839
940431AE2-027 C
Adder
9.175294117647067.799
944581AF1-123 C
Adder
24.2847058823529420.642
941101AE2-104 C
Adder
1.81764705882352941.545
3150461FOUR RIVERD
50/50
2.7482.748
934392AD1-063 E
Adder
0.72470588235294120.616
943742AF1-042 E
Adder
3.10705882352941172.641
962862AG1-135 E
Adder
2.63764705882352952.242
966662AG1-536 E
Adder
4.7070588235294134.001
316088AB2-174 E
Adder
2.94235294117647062.501
316141AB2-099 E
Adder
0.118823529411764720.101
923994AB2-040_E
Adder
2.76941176470588252.354
944492AF1-114 E
Adder
4.5635294117647063.879
943612AF1-032 E
Adder
0.49647058823529410.422
3150441FOUR RIVERB
50/50
2.7882.788
3130536PAPERMILL
Adder
4.5270588235294123.848
939602AE1-190 E
Adder
0.95411764705882360.811
940492AE2-034 E
Adder
1.53882352941176471.308
934522AD1-076 E
Adder
3.0505882352941182.593
936591AD2-074 C
Adder
3.63882352941176463.093
943172AE2-346 E
Adder
0.28588235294117650.243
918492AA1-063AE OP
Adder
1.88000000000000011.598
933981AD1-022 C
Adder
4.2529411764705883.615
900672V4-068 E
Adder
0.170588235294117650.145
942001AE2-212 C
Adder
1.48117647058823531.259
939192AE1-149 E
Adder
4.5223529411764713.844
934065AD1-033 E
Adder
2.68823529411764732.285
939312AE1-162 E
Adder
0.84352941176470590.717
937226AE2-253 E
Adder
3.1152941176470592.648
3142296MT RD221
50/50
0.1260.126
316004AC1-112 C
50/50
0.2990.299
3150471FOUR RIVERE
50/50
2.7482.748
924517AB2-100 E2
Adder
1.3717647058823531.166
934501AD1-074 C
Adder
16.4776470588235314.006
943741AF1-042 C
Adder
1.90352941176470611.618
962861AG1-135 C
Adder
3.9564705882352943.363
3141813NORNECK
Adder
0.57411764705882350.488
3150501FOURRIVERG
50/50
4.254.25
3142366NRTHEST
50/50
0.1640.164
961611AG1-000B C
Adder
10.0094117647058818.508
3138116ELKO L286
Adder
1.09058823529411760.927
940541AE2-040 C
Adder
1.44117647058823551.225
940482AE2-033 E
Adder
5.4364705882352954.621
940481AE2-033 C
Adder
8.0647058823529436.855
927041AC1-191 C
50/50
9.6569.656
963611AG1-210 C
Adder
0.431764705882352940.367
923263AB1-132 E OP
Adder
2.78941176470588252.371
3143316POE
Adder
0.84470588235294120.718
939191AE1-149 C
Adder
6.78235294117647055.765
901082W1-029 E
Adder
16.73529411764705814.225
934146AD1-041 E
Adder
2.38470588235294122.027
957601AF2-054 C
Adder
1.40235294117647061.192
958261AF2-120 C
Adder
4.07294117647058853.462
939411AE1-173 C
Adder
41.24705882352941435.06
940432AE2-027 E
Adder
6.1164705882352945.199
934012AD1-025 E
Adder
6.6117647058823535.62
3150671DARBY 1
50/50
2.2042.204
913392Y1-086 E
Adder
1.160.986
3150451FOUR RIVERC
50/50
3.4073.407
939612AE1-191 E
Adder
3.8152941176470593.243
957602AF2-054 E
Adder
0.93529411764705890.795
966661AG1-536 C
Adder
3.50352941176470622.978
958262AF2-120 E
Adder
2.7152941176470592.308
316078AC2-138 E
Adder
0.60352941176470590.513
944491AF1-114 C
Adder
3.30470588235294162.809
925332AB2-190 E
Adder
5.5094117647058834.683
944591AF1-124 C
Adder
24.37176470588235620.716
944601AF1-125 C
Adder
23.9117647058823520.325
927226AC1-216 E
Adder
5.1070588235294124.341
3150601CHESTF5
Adder
47.7840.613
936666AD2-085 E
Adder
3.18705882352941172.709
962962AG1-145 E
Adder
0.94000000000000010.799
938771AE1-103 C
Adder
1.5164705882352941.289
3145413WATKINS
Adder
0.348235294117647030.296
966881AG1-559 C
Adder
1.37764705882352941.171
960081AF2-299 C
Adder
0.84823529411764710.721
964212AG1-282 E
Adder
0.88117647058823530.749
926072AC1-086 E
Adder
4.36235294117647053.708
3150431FOUR RIVERA
50/50
2.7882.788
925865AC1-065 E
Adder
11.2529411764705879.565
939262AE1-157 E
Adder
3.56941176470588233.034
961951AG1-038 C
Adder
2.1047058823529411.789
961952AG1-038 E
Adder
2.9058823529411772.47
946282AF1-292 E
Adder
0.46823529411764710.398
936582AD2-073 E
Adder
0.67176470588235290.571
940641AE2-051 C
Adder
7.4376470588235296.322
316084AB2-161 E
Adder
3.34823529411764742.846
926785AC1-164_E
Adder
13.3352941176470611.335
943471AF1-018 C
Adder
4.8305882352941174.106
3145946PLYMOUTH TP
Adder
0.158823529411764720.135
933982AD1-022 E
Adder
2.3152941176470591.968
926472AC1-118 E
Adder
0.64470588235294120.548
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.9732.973
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0350.035
MECLTFEXP_MEC->PJM
CLTF
0.2010.201
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0870.087
LAGNLTFEXP_LAGN->PJM
CLTF
1.4041.404
NYPJM->LTFIMP_NY
CLTF
0.5450.545
G-007PJM->LTFIMP_G-007
CMTX_NF
1.0691.069
SIGELTFEXP_SIGE->PJM
CLTF
0.0060.006
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7881.788
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.04428.044
CPLELTFEXP_CPLE->PJM
CLTF
3.7593.759
TVALTFEXP_TVA->PJM
CLTF
1.0611.061
O66PJM->LTFIMP_O-066
CMTX_NF
6.8436.843

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:120.66 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:818.89
MW Contribution:161.31
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
313526AB2-022 C
50/50
0.2360.236
938532AE1-072 E
50/50
7.9377.937
3146326AYDLETT TAP
50/50
1.1471.147
917122Z2-027 E
Adder
0.69411764705882350.59
944602AF1-125 E
50/50
112.268112.268
3145506HICKORY
50/50
2.3082.308
957871AF2-081 C
50/50
9.2149.214
919152AA1-139 E1
50/50
3.7683.768
316018AA1-139 ULT2
50/50
0.9980.998
957872AF2-081 E
50/50
3.9493.949
934065AD1-033 E
50/50
4.1134.113
937226AE2-253 E
50/50
5.6955.695
944591AF1-124 C
50/50
49.98749.987
944601AF1-125 C
50/50
49.04249.042
944582AF1-123 E
50/50
114.059114.059
944592AF1-124 E
50/50
114.472114.472
923832AB2-022 E
50/50
0.7780.778
944581AF1-123 C
50/50
49.8149.81
316185AD1-033 C
50/50
1.0081.008
316320Y1-086 C
50/50
0.1380.138
316388AE2-253 GEN
50/50
1.9151.915
919153AA1-139 E2
50/50
3.7683.768
316017AA1-139 ULT1
50/50
0.9980.998
938531AE1-072 C
50/50
15.22515.225
913392Y1-086 E
50/50
1.3781.378
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0560.056
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.1121.112
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.4850.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.110.11
LAGNLTFEXP_LAGN->PJM
CLTF
0.1390.139
LGEELTFEXP_LGEE->PJM
CLTF
0.040.04
WECLTFEXP_WEC->PJM
CLTF
0.0220.022
VTFLTFEXP_VFT->PJM
CMTX
0.2650.265
SIGELTFEXP_SIGE->PJM
CLTF
0.0070.007
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0480.048
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.0581.058
G-007ALTFEXP_G-007A->PJM
CMTX
0.0980.098
CPLELTFEXP_CPLE->PJM
CLTF
0.0990.099
TVALTFEXP_TVA->PJM
CLTF
0.1110.111

Details for 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:110.61 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:734.04
MW Contribution:47.27
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:110.43 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:732.86
MW Contribution:45.6
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150731STONECA
Adder
4.6705882352941183.97
932046AC2-012 E
Adder
4.4211764705882353.758
935161AD1-151 C
Adder
9.475294117647068.054
938531AE1-072 C
Adder
5.58588235294117654.748
958161AF2-110 C
Adder
0.44117647058823530.375
3145393UNCAMP
Adder
1.75764705882352961.494
961611AG1-000B C
Adder
7.8705882352941186.69
3138116ELKO L286
Adder
0.55058823529411770.468
963611AG1-210 C
Adder
0.288235294117647030.245
935162AD1-151 E
Adder
6.3164705882352945.369
938532AE1-072 E
Adder
2.91176470588235332.475
3146326AYDLETT TAP
Adder
0.430588235294117660.366
943461AF1-017 C
Adder
0.448235294117647070.381
316311AC2-079 C
Adder
1.89882352941176481.614
932596AC2-079 E
Adder
3.09764705882352942.633
917122Z2-027 E
Adder
0.420.357
957832AF2-077 E
Adder
0.61529411764705890.523
940551AE2-041 C
Adder
3.3847058823529412.877
933292AC2-141 E
Adder
3.9564705882352943.363
944602AF1-125 E
Adder
32.8976470588235327.963
3145506HICKORY
Adder
0.70.595
934576AD1-082 E
Adder
1.52941176470588251.3
957871AF2-081 C
Adder
3.18588235294117662.708
943612AF1-032 E
Adder
0.30.255
3130536PAPERMILL
Adder
3.20588235294117662.725
939602AE1-190 E
Adder
0.64705882352941180.55
936591AD2-074 C
Adder
2.45411764705882352.086
3143096IRON208
50/50
1.1521.152
939191AE1-149 C
Adder
3.83764705882352963.262
901082W1-029 E
Adder
9.9105882352941178.424
934146AD1-041 E
Adder
1.61882352941176461.376
957601AF2-054 C
Adder
0.960.816
958261AF2-120 C
Adder
2.7317647058823532.322
940432AE2-027 E
Adder
2.6529411764705882.255
934012AD1-025 E
Adder
5.6305882352941174.786
913392Y1-086 E
Adder
0.69058823529411760.587
939612AE1-191 E
Adder
2.58941176470588232.201
957602AF2-054 E
Adder
0.640.544
966661AG1-536 C
Adder
2.35058823529411761.998
958262AF2-120 E
Adder
1.82117647058823541.548
316078AC2-138 E
Adder
0.40352941176470590.343
924814AB2-134 E
Adder
7.1247058823529416.056
3150641CHESTS8
50/50
2.4642.464
919152AA1-139 E1
Adder
1.30235294117647071.107
942342AE2-247 E
Adder
0.68470588235294120.582
939246AE1-155 E
Adder
3.8047058823529413.234
926755AC1-161 E
Adder
3.9564705882352943.363
933291AC2-141 C
Adder
9.2670588235294127.877
925522AC1-027 E
Adder
0.401176470588235360.341
944631AF1-128 C
50/50
49.89149.891
957872AF2-081 E
Adder
1.36588235294117651.161
3145256KINGFORK
Adder
0.35882352941176470.305
3150921YORKTN3
Adder
49.06352941176470541.704
316160AE1-175 E
Adder
0.54235294117647060.461
941102AE2-104 E
Adder
1.71882352941176491.461
936592AD2-074 E
Adder
4.0035294117647063.403
939192AE1-149 E
Adder
2.55882352941176452.175
3150781HOPHCF2
50/50
1.651.65
934065AD1-033 E
Adder
1.61882352941176461.376
939312AE1-162 E
Adder
0.60.51
937226AE2-253 E
Adder
1.86705882352941191.587
943741AF1-042 C
Adder
1.28352941176470581.091
962861AG1-135 C
Adder
2.65764705882352952.259
3141813NORNECK
Adder
0.38352941176470590.326
3150801HOPHCF4
50/50
2.5042.504
3150791HOPHCF3
50/50
1.651.65
926662AC1-147 E
Adder
0.44705882352941180.38
916192Z1-068 E
Adder
0.61882352941176480.526
316076AC2-137 E
Adder
0.52823529411764710.449
957492AF2-043 E
Adder
0.46117647058823530.392
923842AB2-024 E
Adder
0.8717647058823530.741
316157AD2-030 E
Adder
0.53882352941176470.458
964211AG1-282 C
Adder
0.89411764705882360.76
941591AE2-156 C
Adder
6.0305882352941185.126
925332AB2-190 E
Adder
4.9082352941176474.172
944591AF1-124 C
Adder
14.64823529411764712.451
944601AF1-125 C
Adder
14.37058823529411812.215
927226AC1-216 E
Adder
4.34941176470588253.697
3150601CHESTF5
50/50
79.73479.734
936666AD2-085 E
Adder
1.86588235294117651.586
962962AG1-145 E
Adder
0.65764705882352950.559
938771AE1-103 C
Adder
0.86352941176470590.734
964212AG1-282 E
Adder
0.59647058823529410.507
3150621CHESTS7
50/50
2.2332.233
3150611CHESTG7
50/50
4.8654.865
925865AC1-065 E
Adder
7.5847058823529416.447
961951AG1-038 C
Adder
1.41882352941176461.206
961952AG1-038 E
Adder
1.961.666
936582AD2-073 E
Adder
0.43647058823529410.371
944582AF1-123 E
Adder
33.4223529411764728.409
944592AF1-124 E
Adder
33.5435294117647128.512
3150631CHESTG8
50/50
4.7884.788
935112AD1-144 E
Adder
0.332941176470588240.283
316349AD2-085 C
Adder
1.1435294117647060.972
316169AC1-164 GEN
Adder
22.40117647058823619.041
923832AB2-022 E
Adder
0.38941176470588240.331
938772AE1-103 E
Adder
1.19294117647058821.014
916042Z1-036 E
Adder
8.5047058823529427.229
940431AE2-027 C
Adder
3.9788235294117653.382
3150771HOPHCF1
50/50
1.651.65
944581AF1-123 C
Adder
14.5952941176470612.406
941101AE2-104 C
Adder
1.08117647058823540.919
934392AD1-063 E
Adder
0.50823529411764710.432
943742AF1-042 E
Adder
2.09529411764705881.781
962862AG1-135 E
Adder
1.7717647058823531.506
966662AG1-536 E
Adder
3.1588235294117652.685
919153AA1-139 E2
Adder
1.30235294117647071.107
943462AF1-017 E
Adder
0.7317647058823530.622
942341AE2-247 C
Adder
0.495294117647058830.421
958162AF2-110 E
Adder
0.70117647058823530.596
963612AG1-210 E
Adder
0.431764705882352940.367
316084AB2-161 E
Adder
1.921.632
926785AC1-164_E
Adder
10.0635294117647078.554
943471AF1-018 C
Adder
3.3847058823529412.877
926472AC1-118 E
Adder
0.402352941176470640.342
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.3540.354
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.6811.681
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.1790.179
LAGNLTFEXP_LAGN->PJM
CLTF
0.7160.716
NYPJM->LTFIMP_NY
CLTF
0.2840.284
LGEELTFEXP_LGEE->PJM
CLTF
0.0270.027
WECLTFEXP_WEC->PJM
CLTF
0.0120.012
G-007PJM->LTFIMP_G-007
CMTX_NF
0.5760.576
SIGELTFEXP_SIGE->PJM
CLTF
0.0090.009
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.8060.806
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.77712.777
CPLELTFEXP_CPLE->PJM
CLTF
1.6931.693
TVALTFEXP_TVA->PJM
CLTF
0.5480.548
O66PJM->LTFIMP_O-066
CMTX_NF
3.6813.681

Details for 6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 574_SRT-S_SENS
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.88 %
Rating:889.43 MVA
Rating Type:B
MVA to Mitigate:923.97
MW Contribution:45.9
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961611AG1-000B C
Adder
5.8729411764705884.992
3138116ELKO L286
Adder
0.65411764705882360.556
927041AC1-191 C
50/50
5.7735.773
316233AE1-074 C
Adder
0.87882352941176480.747
935162AD1-151 E
Adder
4.2200000000000013.587
938532AE1-072 E
Adder
2.84117647058823542.415
3146326AYDLETT TAP
Adder
0.420.357
943461AF1-017 C
Adder
0.44235294117647060.376
316311AC2-079 C
Adder
1.8717647058823531.591
932596AC2-079 E
Adder
3.05411764705882362.596
917122Z2-027 E
Adder
0.41176470588235290.35
957832AF2-077 E
Adder
0.58117647058823530.494
3150481FOUR RIVERF
50/50
3.0493.049
315051AA1-145 CT1
50/50
4.0364.036
927042AC1-191 E
50/50
2.8762.876
940551AE2-041 C
Adder
3.20117647058823532.721
3150381LDYSMT2
50/50
6.5876.587
3143316POE
Adder
0.47411764705882360.403
939191AE1-149 C
Adder
3.86470588235294173.285
316240AF1-291 C
Adder
0.89058823529411770.757
944641AF1-129 C
Adder
43.036470588235336.581
924814AB2-134 E
Adder
4.88705882352941154.154
919152AA1-139 E1
Adder
1.26941176470588221.079
942342AE2-247 E
Adder
0.67529411764705880.574
939246AE1-155 E
Adder
4.3741176470588233.718
957972AF2-091 E
Adder
1.9117647058823531.625
938552AE1-074 E
Adder
0.44235294117647060.376
926755AC1-161 E
Adder
4.0258823529411773.422
933291AC2-141 C
Adder
9.4305882352941198.016
925522AC1-027 E
Adder
0.38352941176470590.326
944631AF1-128 C
Adder
17.6505882352941215.003
957872AF2-081 E
Adder
1.33058823529411761.131
3145256KINGFORK
Adder
0.33176470588235290.282
3150921YORKTN3
Adder
44.5435294117647137.862
316160AE1-175 E
Adder
0.476470588235294150.405
941102AE2-104 E
Adder
1.68117647058823551.429
315052AA1-145 CT2
50/50
4.0344.034
936592AD2-074 E
Adder
4.4352941176470593.77
3150411LDYSMT5
50/50
6.7946.794
934782AD1-105 E
50/50
3.2413.241
941591AE2-156 C
Adder
5.69058823529411754.837
925332AB2-190 E
Adder
3.2094117647058832.728
944591AF1-124 C
Adder
14.2223529411764712.089
944601AF1-125 C
Adder
13.95294117647058811.86
927226AC1-216 E
Adder
2.9835294117647062.536
3150601CHESTF5
Adder
28.20941176470588423.978
936666AD2-085 E
Adder
1.84117647058823521.565
962962AG1-145 E
Adder
0.57764705882352940.491
966881AG1-559 C
50/50
2.7772.777
964212AG1-282 E
Adder
0.68352941176470580.581
3150431FOUR RIVERA
50/50
2.5342.534
925865AC1-065 E
Adder
7.446.324
939262AE1-157 E
50/50
9.5879.587
961951AG1-038 C
Adder
1.57176470588235321.336
961952AG1-038 E
Adder
2.17058823529411751.845
936582AD2-073 E
Adder
0.58352941176470590.496
3150831SPRUNCA
Adder
3.83529411764705853.26
3150841SPRUNCB
Adder
3.83529411764705853.26
926662AC1-147 E
Adder
0.421176470588235260.358
916192Z1-068 E
Adder
0.59294117647058830.504
316076AC2-137 E
Adder
0.62823529411764710.534
957492AF2-043 E
Adder
0.44588235294117650.379
966872AG1-558 E
50/50
0.7240.724
966871AG1-558 C
50/50
1.4381.438
923842AB2-024 E
Adder
0.80588235294117660.685
316157AD2-030 E
Adder
0.52941176470588240.45
964211AG1-282 C
Adder
1.02470588235294110.871
957191AF2-013 C
Adder
10.3282352941176478.779
3141316ARNOLDS
50/50
0.150.15
944582AF1-123 E
Adder
32.4505882352941227.583
944592AF1-124 E
Adder
32.5682352941176527.683
935112AD1-144 E
Adder
0.30705882352941180.261
316349AD2-085 C
Adder
1.1282352941176470.959
930122AB1-027 E
Adder
0.73529411764705890.625
316169AC1-164 GEN
Adder
18.2823529411764715.54
923832AB2-022 E
Adder
0.38235294117647060.325
966882AG1-559 E
50/50
1.3991.399
939261AE1-157 C
50/50
17.67517.675
3150391LDYSMT3
50/50
6.7616.761
957971AF2-091 C
Adder
1.3835294117647061.176
934146AD1-041 E
Adder
1.58823529411764721.35
957601AF2-054 C
Adder
0.9435294117647060.802
3150401LDYSMT4
50/50
6.7736.773
958261AF2-120 C
Adder
3.14117647058823522.67
933292AC2-141 E
Adder
4.0258823529411773.422
946262AF1-291 E
Adder
0.59411764705882350.505
3150651CHESTF6
Adder
7.8352941176470596.66
944602AF1-125 E
Adder
31.9423529411764727.151
3145506HICKORY
Adder
0.67999999999999990.578
934576AD1-082 E
Adder
1.5282352941176471.299
957871AF2-081 C
Adder
3.1047058823529412.639
943612AF1-032 E
Adder
0.289411764705882370.246
3150441FOUR RIVERB
50/50
2.5342.534
3130536PAPERMILL
Adder
2.9788235294117652.532
939602AE1-190 E
Adder
0.63529411764705890.54
936591AD2-074 C
Adder
2.71764705882352952.31
942002AE2-212 E
Adder
0.55764705882352940.474
940431AE2-027 C
Adder
5.2517647058823544.464
944581AF1-123 C
Adder
14.17176470588235312.046
941101AE2-104 C
Adder
1.05764705882352940.899
3150461FOUR RIVERD
50/50
2.4972.497
934392AD1-063 E
Adder
0.480.408
943742AF1-042 E
Adder
2.321.972
962862AG1-135 E
Adder
2.021.717
966662AG1-536 E
Adder
3.63176470588235353.087
944492AF1-114 E
Adder
5.6211764705882354.778
919153AA1-139 E2
Adder
1.26941176470588221.079
943462AF1-017 E
Adder
0.72235294117647060.614
942341AE2-247 C
Adder
0.48941176470588230.416
926412AC1-112 E
Adder
0.59882352941176480.509
958162AF2-110 E
Adder
0.68588235294117650.583
963612AG1-210 E
Adder
0.51294117647058820.436
934781AD1-105 C
50/50
0.7810.781
316084AB2-161 E
Adder
1.91764705882352931.63
926785AC1-164_E
Adder
8.2141176470588246.982
943471AF1-018 C
Adder
3.20117647058823532.721
926472AC1-118 E
Adder
0.61882352941176480.526
3150371LDYSMT1
50/50
6.5036.503
963611AG1-210 C
Adder
0.34235294117647060.291
3150731STONECA
Adder
2.8635294117647062.434
932046AC2-012 E
Adder
4.1682352941176483.543
935161AD1-151 C
Adder
6.3305882352941185.381
938531AE1-072 C
Adder
5.4494117647058824.632
958161AF2-110 C
Adder
0.431764705882352940.367
942001AE2-212 C
Adder
0.83647058823529410.711
939192AE1-149 E
Adder
2.57647058823529432.19
934065AD1-033 E
Adder
1.56941176470588251.334
939312AE1-162 E
Adder
0.494117647058823550.42
937226AE2-253 E
Adder
1.81764705882352941.545
3142296MT RD221
50/50
0.0710.071
3150471FOUR RIVERE
50/50
2.4972.497
943741AF1-042 C
Adder
1.42235294117647081.209
962861AG1-135 C
Adder
3.02941176470588272.575
3141813NORNECK
Adder
0.456470588235294130.388
3150501FOURRIVERG
50/50
3.0343.034
940432AE2-027 E
Adder
3.50117647058823562.976
934012AD1-025 E
Adder
3.86235294117647053.283
913392Y1-086 E
Adder
0.6764705882352940.575
3150451FOUR RIVERC
50/50
3.0963.096
939612AE1-191 E
Adder
2.54117647058823562.16
957602AF2-054 E
Adder
0.62941176470588240.535
966661AG1-536 C
Adder
2.7023529411764712.297
958262AF2-120 E
Adder
2.09411764705882361.78
316078AC2-138 E
Adder
0.47882352941176470.407
944491AF1-114 C
Adder
4.0705882352941173.46
3150331BIRCHWDA
50/50
21.96921.969
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.5122.512
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.1823.182
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.4520.452
LAGNLTFEXP_LAGN->PJM
CLTF
1.2121.212
NYPJM->LTFIMP_NY
CLTF
0.610.61
LGEELTFEXP_LGEE->PJM
CLTF
0.1240.124
WECLTFEXP_WEC->PJM
CLTF
0.0580.058
G-007PJM->LTFIMP_G-007
CMTX_NF
1.2851.285
SIGELTFEXP_SIGE->PJM
CLTF
0.0270.027
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.081.08
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.02918.029
CPLELTFEXP_CPLE->PJM
CLTF
2.2672.267
TVALTFEXP_TVA->PJM
CLTF
0.9510.951
O66PJM->LTFIMP_O-066
CMTX_NF
8.1888.188

Details for 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.46 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:797.16
MW Contribution:63.39
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.99 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:766.86
MW Contribution:59.57
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316240AF1-291 C
Adder
1.30470588235294121.109
944641AF1-129 C
Adder
63.01529411764706653.563
924814AB2-134 E
Adder
6.5788235294117645.592
919152AA1-139 E1
Adder
1.75411764705882381.491
942342AE2-247 E
Adder
0.94705882352941180.805
920042AA2-088 E OP
Adder
4.1788235294117653.552
934511AD1-075 C
Adder
3.3364705882352942.836
934521AD1-076 C
Adder
4.8470588235294124.12
939246AE1-155 E
Adder
4.423.757
3150861SPRUNCD
50/50
0.1930.193
942002AE2-212 E
Adder
0.82117647058823530.698
940431AE2-027 C
Adder
8.0694117647058836.859
944581AF1-123 C
Adder
19.5729411764705916.637
941101AE2-104 C
Adder
1.4682352941176471.248
934392AD1-063 E
Adder
0.60.51
943742AF1-042 E
Adder
2.45411764705882352.086
962862AG1-135 E
Adder
2.06235294117647071.753
966662AG1-536 E
Adder
3.6694117647058833.119
316141AB2-099 E
Adder
0.096470588235294130.082
3150731STONECA
Adder
3.82941176470588253.255
932046AC2-012 E
Adder
5.74352941176470564.882
935161AD1-151 C
Adder
8.5094117647058837.233
3150701DARBY 4
50/50
5.1675.167
938531AE1-072 C
Adder
7.5329411764705886.403
958161AF2-110 C
Adder
0.59882352941176480.509
3145393UNCAMP
Adder
2.522.142
933981AD1-022 C
Adder
3.44588235294117642.929
900672V4-068 E
Adder
0.13882352941176470.118
942001AE2-212 C
Adder
1.23176470588235291.047
939192AE1-149 E
Adder
3.68588235294117663.133
934065AD1-033 E
Adder
2.16705882352941171.842
939312AE1-162 E
Adder
0.67411764705882350.573
937226AE2-253 E
Adder
2.5117647058823532.135
924517AB2-100 E2
Adder
1.11411764705882340.947
934501AD1-074 C
Adder
13.34588235294117611.344
943741AF1-042 C
Adder
1.5035294117647061.278
962861AG1-135 C
Adder
3.09411764705882362.63
3141813NORNECK
Adder
0.44235294117647060.376
3142366NRTHEST
50/50
0.4150.415
961611AG1-000B C
Adder
7.94235294117647156.751
3138116ELKO L286
50/50
1.6051.605
940541AE2-040 C
Adder
1.1717647058823530.996
940482AE2-033 E
Adder
4.4188235294117653.756
940481AE2-033 C
Adder
6.5541176470588235.571
963611AG1-210 C
Adder
0.33176470588235290.282
935162AD1-151 E
Adder
5.6729411764705884.822
3150691DARBY 3
50/50
5.1615.161
938532AE1-072 E
Adder
3.9270588235294123.338
3146326AYDLETT TAP
Adder
0.58117647058823530.494
943461AF1-017 C
Adder
0.620.527
316311AC2-079 C
Adder
2.622.227
932596AC2-079 E
Adder
4.2752941176470593.634
917122Z2-027 E
Adder
0.57058823529411760.485
957832AF2-077 E
Adder
0.74235294117647070.631
940551AE2-041 C
Adder
4.0035294117647063.403
920692AA2-178 E
Adder
1.66000000000000011.411
966622AG1-532 E
Adder
0.343529411764705860.292
933292AC2-141 E
Adder
5.5482352941176484.716
946262AF1-291 E
Adder
0.86941176470588230.739
3150651CHESTF6
Adder
11.472941176470599.752
944602AF1-125 E
Adder
44.11647058823529537.499
3145506HICKORY
Adder
0.93882352941176480.798
934576AD1-082 E
Adder
2.16941176470588241.844
957871AF2-081 C
Adder
4.2894117647058823.646
943612AF1-032 E
Adder
0.40.34
3130536PAPERMILL
Adder
3.7670588235294123.202
939602AE1-190 E
Adder
0.79058823529411770.672
940492AE2-034 E
Adder
1.24588235294117641.059
934522AD1-076 E
Adder
2.47058823529411782.1
936591AD2-074 C
Adder
2.8741176470588242.443
943172AE2-346 E
Adder
0.231764705882352960.197
3143316POE
Adder
0.69294117647058820.589
939191AE1-149 C
Adder
5.5294117647058834.7
901082W1-029 E
Adder
13.50705882352941211.481
934146AD1-041 E
Adder
1.97529411764705891.679
957601AF2-054 C
Adder
1.15294117647058810.98
958261AF2-120 C
Adder
3.17411764705882372.698
3150851SPRUNCC
50/50
0.1930.193
939411AE1-173 C
Adder
32.84941176470588427.922
940432AE2-027 E
Adder
5.3800000000000014.573
934012AD1-025 E
Adder
5.1988235294117644.419
3150671DARBY 1
50/50
5.1375.137
913392Y1-086 E
Adder
0.93647058823529420.796
939612AE1-191 E
Adder
3.16117647058823532.687
957602AF2-054 E
Adder
0.76823529411764710.653
966661AG1-536 C
Adder
2.7305882352941182.321
958262AF2-120 E
Adder
2.1164705882352941.799
316078AC2-138 E
Adder
0.46470588235294120.395
926755AC1-161 E
Adder
5.5482352941176484.716
933291AC2-141 C
Adder
12.9976470588235311.048
925522AC1-027 E
Adder
0.52941176470588240.45
944631AF1-128 C
Adder
21.0152941176470617.863
957872AF2-081 E
Adder
1.83882352941176471.563
3145256KINGFORK
Adder
0.455294117647058850.387
3150921YORKTN3
Adder
59.65411764705882550.706
316160AE1-175 E
Adder
0.64705882352941180.55
941102AE2-104 E
Adder
2.33411764705882341.984
936592AD2-074 E
Adder
4.6894117647058823.986
3150831SPRUNCA
50/50
10.71910.719
3150841SPRUNCB
50/50
10.71910.719
939412AE1-173 E
Adder
21.918.615
926662AC1-147 E
Adder
0.580.493
916192Z1-068 E
Adder
0.81764705882352940.695
316076AC2-137 E
50/50
1.5391.539
957492AF2-043 E
Adder
0.61647058823529410.524
923852AB2-025 E
Adder
0.47411764705882360.403
923842AB2-024 E
Adder
1.02235294117647070.869
316157AD2-030 E
Adder
0.64705882352941180.55
964211AG1-282 C
Adder
1.02941176470588250.875
961941AG1-037 C
Adder
0.192941176470588250.164
961942AG1-037 E
Adder
0.129411764705882370.11
941591AE2-156 C
Adder
7.8423529411764716.666
925332AB2-190 E
Adder
4.3082352941176473.662
944591AF1-124 C
Adder
19.64235294117647316.696
944601AF1-125 C
Adder
19.27176470588235416.381
927226AC1-216 E
Adder
4.0164705882352943.414
3150601CHESTF5
Adder
33.5858823529411828.548
936666AD2-085 E
Adder
2.5811764705882352.194
962962AG1-145 E
Adder
0.78470588235294130.667
938771AE1-103 C
Adder
1.22588235294117661.042
3145413WATKINS
Adder
0.28235294117647060.24
960081AF2-299 C
Adder
0.68823529411764710.585
964212AG1-282 E
Adder
0.68588235294117650.583
316075AC2-137 C
50/50
0.4380.438
925865AC1-065 E
Adder
9.377647058823537.971
961951AG1-038 C
Adder
1.66235294117647061.413
961952AG1-038 E
Adder
2.2952941176470591.951
946282AF1-292 E
Adder
0.380.323
936582AD2-073 E
Adder
0.494117647058823550.42
944582AF1-123 E
Adder
44.8238.097
944592AF1-124 E
Adder
44.9823529411764738.235
935112AD1-144 E
Adder
0.42235294117647060.359
316349AD2-085 C
Adder
1.58235294117647051.345
316169AC1-164 GEN
50/50
25.43925.439
923832AB2-022 E
Adder
0.52823529411764710.449
938772AE1-103 E
Adder
1.69294117647058841.439
916042Z1-036 E
Adder
11.8376470588235310.062
946281AF1-292 C
Adder
0.56941176470588240.484
960082AF2-299 E
Adder
0.458823529411764740.39
940642AE2-051 E
Adder
3.9294117647058823.34
3150681DARBY 2
50/50
5.1435.143
919153AA1-139 E2
Adder
1.75411764705882381.491
943462AF1-017 E
Adder
1.0117647058823530.86
942341AE2-247 C
Adder
0.68588235294117650.583
958162AF2-110 E
Adder
0.95294117647058830.81
924516AB2-100 E1
Adder
1.11411764705882340.947
934512AD1-075 E
Adder
1.69882352941176461.444
934502AD1-074 E
Adder
6.7941176470588245.775
966621AG1-532 C
Adder
0.51647058823529410.439
918512AA1-065 E OP
Adder
2.1329411764705881.813
963612AG1-210 E
Adder
0.49764705882352940.423
940641AE2-051 C
Adder
5.8941176470588235.01
316084AB2-161 E
Adder
2.7223529411764712.314
926785AC1-164_E
50/50
11.42911.429
943471AF1-018 C
Adder
4.0035294117647063.403
3145946PLYMOUTH TP
Adder
0.128235294117647060.109
933982AD1-022 E
Adder
1.87647058823529411.595
926472AC1-118 E
Adder
0.448235294117647070.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.4653.465
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.1394.139
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.590.59
LAGNLTFEXP_LAGN->PJM
CLTF
1.5871.587
NYPJM->LTFIMP_NY
CLTF
0.4630.463
LGEELTFEXP_LGEE->PJM
CLTF
0.150.15
WECLTFEXP_WEC->PJM
CLTF
0.0770.077
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9570.957
SIGELTFEXP_SIGE->PJM
CLTF
0.0340.034
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.5041.504
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.58824.588
CPLELTFEXP_CPLE->PJM
CLTF
3.1573.157
TVALTFEXP_TVA->PJM
CLTF
1.2281.228
O66PJM->LTFIMP_O-066
CMTX_NF
6.1076.107

Details for 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.2 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1015.68
MW Contribution:48.69
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.1 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:985.14
MW Contribution:45.0
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961611AG1-000B C
Adder
7.342352941176476.241
940541AE2-040 C
Adder
1.56117647058823541.327
940482AE2-033 E
Adder
5.8329411764705884.958
940481AE2-033 C
Adder
8.6517647058823537.354
923263AB1-132 E OP
Adder
2.582.193
924312AB2-078 E O1
Adder
0.41176470588235290.35
935162AD1-151 E
50/50
6.0156.015
938532AE1-072 E
Adder
3.07058823529411742.61
3146326AYDLETT TAP
Adder
0.455294117647058850.387
943461AF1-017 C
Adder
0.61882352941176480.526
316311AC2-079 C
Adder
2.5717647058823532.186
932596AC2-079 E
Adder
4.1964705882352953.567
917122Z2-027 E
Adder
0.457647058823529460.389
920692AA2-178 E
Adder
1.4552941176470591.237
966622AG1-532 E
Adder
0.408235294117647030.347
922923AB1-081 E OP
Adder
1.321.122
933292AC2-141 E
Adder
3.78588235294117673.218
946262AF1-291 E
50/50
1.6321.632
3150651CHESTF6
50/50
21.89721.897
944602AF1-125 E
Adder
33.8847058823529428.802
3145506HICKORY
Adder
0.72352941176470590.615
934576AD1-082 E
50/50
2.5582.558
957871AF2-081 C
Adder
3.34117647058823542.84
943612AF1-032 E
Adder
0.320.272
940492AE2-034 E
Adder
1.09058823529411760.927
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
918492AA1-063AE OP
Adder
1.59411764705882361.355
937482AD2-202 E
Adder
0.32588235294117650.277
917332KELFORD E
Adder
0.61411764705882350.522
925122AB2-169 E
Adder
2.04352941176470631.737
316274AC1-208 C
Adder
3.3788235294117652.872
917342Z2-044 E
Adder
0.215294117647058830.183
3151311EDGECMA
Adder
5.5117647058823534.685
3143316POE
50/50
1.0861.086
939191AE1-149 C
50/50
7.1377.137
901082W1-029 E
Adder
10.9870588235294139.339
926206AC1-098 E
Adder
1.35999999999999991.156
316240AF1-291 C
50/50
2.4482.448
944641AF1-129 C
50/50
120.262120.262
924814AB2-134 E
Adder
6.7529411764705885.74
316381AD1-082 C
50/50
0.7330.733
919152AA1-139 E1
Adder
1.36588235294117651.161
942342AE2-247 E
Adder
0.94470588235294130.803
920042AA2-088 E OP
Adder
4.0811764705882353.469
934511AD1-075 C
Adder
3.01411764705882362.562
934521AD1-076 C
Adder
4.377647058823533.721
3145723EMPORIA
Adder
0.185882352941176470.158
923573AB1-173 E OP
Adder
1.36823529411764721.163
919692AA2-053 E OP
Adder
1.64941176470588241.402
925785AC1-054 E
Adder
1.2082352941176471.027
316263AC1-034 C
Adder
2.3517647058823531.999
926755AC1-161 E
Adder
3.78588235294117673.218
933291AC2-141 C
Adder
8.8694117647058827.539
3150761HOPPOLC
50/50
1.0021.002
925522AC1-027 E
Adder
0.410588235294117640.349
957872AF2-081 E
Adder
1.4317647058823531.217
3145256KINGFORK
Adder
0.357647058823529430.304
941102AE2-104 E
Adder
2.0188235294117651.716
964242AG1-285 E
Adder
2.5717647058823532.186
926214AC1-099 E
Adder
0.44941176470588240.382
932632AC2-084 E
Adder
1.20235294117647061.022
924162AB2-060 E OP
Adder
1.3117647058823531.115
942001AE2-212 C
50/50
2.1112.111
939192AE1-149 E
50/50
4.7584.758
3150781HOPHCF2
50/50
1.5941.594
934065AD1-033 E
Adder
1.6670588235294121.417
939312AE1-162 E
Adder
0.5717647058823530.486
937226AE2-253 E
Adder
1.9482352941176471.656
924517AB2-100 E2
Adder
1.36823529411764721.163
934501AD1-074 C
Adder
12.05529411764705810.247
957482AF2-042 E
Adder
11.3435294117647069.642
934621AD1-088 C
Adder
2.86941176470588262.439
935172AD1-152 E
Adder
1.6435294117647061.397
961671AG1-007 C
Adder
0.332941176470588240.283
3150831SPRUNCA
Adder
2.6776470588235292.276
3150841SPRUNCB
Adder
2.6776470588235292.276
939412AE1-173 E
Adder
21.0235294117647117.87
941032AE2-094 E
Adder
6.3247058823529425.376
941031AE2-094 C
Adder
14.12000000000000112.002
3150801HOPHCF4
50/50
2.4192.419
3150791HOPHCF3
50/50
1.5941.594
926662AC1-147 E
Adder
0.452941176470588240.385
916192Z1-068 E
Adder
0.63294117647058830.538
957492AF2-043 E
Adder
0.49294117647058820.419
923852AB2-025 E
Adder
0.6317647058823530.537
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
934321AD1-056 C
Adder
2.3988235294117652.039
934331AD1-057 C
Adder
1.33882352941176451.138
934332AD1-057 E
Adder
0.69647058823529410.592
934322AD1-056 E
Adder
1.30117647058823541.106
927022AC1-189 E
Adder
1.48235294117647071.26
925595AC1-034 E
Adder
1.77411764705882361.508
944011AF1-069 C
Adder
4.6141176470588243.922
941591AE2-156 C
Adder
6.1141176470588245.197
925332AB2-190 E
50/50
4.6914.691
944591AF1-124 C
Adder
15.08705882352941312.824
944601AF1-125 C
Adder
14.80235294117647312.582
927226AC1-216 E
Adder
4.122352941176473.504
936666AD2-085 E
Adder
2.5752941176470592.189
963041AG1-153 C
Adder
1.9482352941176471.656
938771AE1-103 C
Adder
1.11764705882352940.95
3145413WATKINS
Adder
0.26470588235294120.225
960081AF2-299 C
Adder
0.81647058823529410.694
926072AC1-086 E
Adder
4.0352941176470593.43
944012AF1-069 E
Adder
1.7917647058823531.523
946282AF1-292 E
Adder
0.45058823529411770.383
917512Z2-088 E OP1
Adder
1.73411764705882351.474
944582AF1-123 E
Adder
34.4258823529411829.262
944592AF1-124 E
Adder
34.55058823529411429.368
935112AD1-144 E
Adder
0.33176470588235290.282
316349AD2-085 C
Adder
1.57882352941176471.342
923832AB2-022 E
Adder
0.421176470588235260.358
963042AG1-153 E
Adder
2.92235294117647062.484
938772AE1-103 E
Adder
1.5435294117647061.312
916042Z1-036 E
Adder
9.9682352941176488.473
946281AF1-292 C
Adder
0.67529411764705880.574
960082AF2-299 E
Adder
0.54470588235294130.463
926071AC1-086 C
Adder
8.8647058823529427.535
964241AG1-285 C
Adder
3.85882352941176483.28
927021AC1-189 C
Adder
2.97529411764705862.529
924152AB2-059 E OP
Adder
1.87058823529411791.59
942002AE2-212 E
50/50
1.4081.408
940431AE2-027 C
Adder
7.0447058823529425.988
3150771HOPHCF1
50/50
1.5941.594
944581AF1-123 C
Adder
15.03411764705882412.779
941101AE2-104 C
Adder
1.26941176470588221.079
957481AF2-042 C
Adder
17.0152941176470614.463
316088AB2-174 E
Adder
2.7588235294117652.345
316141AB2-099 E
Adder
0.095294117647058830.081
923994AB2-040_E
Adder
2.56588235294117652.181
924322AB2-079 E O1
Adder
0.41176470588235290.35
961672AG1-007 E
Adder
0.188235294117647060.16
940642AE2-051 E
Adder
4.0635294117647063.454
316132AB2-190 C
50/50
2.4122.412
919153AA1-139 E2
Adder
1.36588235294117651.161
943462AF1-017 E
Adder
1.00941176470588250.858
942341AE2-247 C
Adder
0.68470588235294120.582
958162AF2-110 E
Adder
0.82470588235294120.701
924516AB2-100 E1
Adder
1.36823529411764721.163
934512AD1-075 E
Adder
1.53411764705882361.304
934502AD1-074 E
Adder
6.1364705882352945.216
966621AG1-532 C
Adder
0.61294117647058830.521
918512AA1-065 E OP
Adder
2.04235294117647071.736
924022AB2-043 E O1
Adder
1.60117647058823541.361
918532AA1-067 E
Adder
0.251764705882352950.214
940641AE2-051 C
Adder
6.0952941176470595.181
316084AB2-161 E
50/50
3.213.21
316083AB2-161 C
50/50
0.3210.321
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
933982AD1-022 E
Adder
1.721.462
934622AD1-088 E
Adder
1.38117647058823521.174
934612AD1-087 E
Adder
1.1117647058823530.945
927146AC1-208 E
Adder
1.51.275
3150731STONECA
50/50
4.5124.512
932046AC2-012 E
Adder
4.4823529411764713.81
935161AD1-151 C
50/50
9.0229.022
938531AE1-072 C
Adder
5.8905882352941185.007
958161AF2-110 C
Adder
0.51764705882352950.44
3145393UNCAMP
Adder
2.3247058823529411.976
933981AD1-022 C
Adder
3.162.686
900672V4-068 E
Adder
0.136470588235294120.116
924302AB2-077 E O1
Adder
0.41176470588235290.35
939411AE1-173 C
Adder
31.5352941176470626.805
940432AE2-027 E
Adder
4.6964705882352943.992
934012AD1-025 E
Adder
5.3364705882352944.536
913392Y1-086 E
Adder
0.74470588235294120.633
3137643SOCKMAN
Adder
0.288235294117647030.245
919710AA2-057 E
Adder
1.44823529411764731.231
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
NYPJM->LTFIMP_NY
CLTF
0.4360.436
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
WECLTFEXP_WEC->PJM
CLTF
0.140.14
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
TVALTFEXP_TVA->PJM
CLTF
1.561.56
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.13 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3353.36
MW Contribution:166.38
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3493.11
MW Contribution:161.87
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
932046AC2-012 E
50/50
14.50114.501
316017AA1-139 ULT1
50/50
1.2231.223
938531AE1-072 C
50/50
19.84719.847
958161AF2-110 C
Adder
1.49647058823529421.272
3152411Z1-086 GT1
50/50
15.81615.816
3152421Z1-086 GT2
50/50
15.81115.811
3145393UNCAMP
Adder
6.7635294117647065.749
933981AD1-022 C
Adder
9.8917647058823528.408
900672V4-068 E
Adder
0.402352941176470640.342
924302AB2-077 E O1
Adder
1.52117647058823541.293
316375AC2-012 C
50/50
1.4951.495
961611AG1-000B C
Adder
13.21058823529411611.229
313526AB2-022 C
50/50
0.4240.424
940541AE2-040 C
50/50
3.4343.434
940482AE2-033 E
50/50
13.01513.015
940481AE2-033 C
50/50
19.30519.305
923263AB1-132 E OP
Adder
7.0270588235294125.973
925612AC1-036 E
Adder
0.93294117647058830.793
924312AB2-078 E O1
Adder
1.52117647058823541.293
926274AC1-105 E
Adder
2.9882352941176472.54
938532AE1-072 E
50/50
10.34610.346
3146326AYDLETT TAP
50/50
1.5311.531
943461AF1-017 C
Adder
1.40235294117647061.192
316311AC2-079 C
Adder
5.9964705882352955.097
932596AC2-079 E
Adder
9.7835294117647078.316
3152431Z1-086 GT3
50/50
15.81115.811
3152441Z1-086 ST
50/50
27.53227.532
917122Z2-027 E
50/50
1.5121.512
920692AA2-178 E
Adder
4.6352941176470593.94
966622AG1-532 E
50/50
1.0851.085
3147133PAMPLIN
Adder
0.89882352941176480.764
922923AB1-081 E OP
Adder
4.20470588235294153.574
927264AC1-222 E
Adder
4.3282352941176473.679
933292AC2-141 E
50/50
14.89414.894
316294AC1-161 C
50/50
5.7015.701
944602AF1-125 E
50/50
115.795115.795
916191Z1-068 C
50/50
0.0490.049
3145506HICKORY
50/50
2.4672.467
934576AD1-082 E
Adder
4.1988235294117653.569
957871AF2-081 C
50/50
11.29311.293
943612AF1-032 E
Adder
1.02823529411764710.874
940492AE2-034 E
Adder
3.4764705882352942.955
934522AD1-076 E
Adder
7.045.984
943172AE2-346 E
Adder
0.68588235294117650.583
918492AA1-063AE OP
Adder
4.65058823529411753.953
937482AD2-202 E
50/50
1.3221.322
917332KELFORD E
Adder
1.8635294117647061.584
925122AB2-169 E
Adder
6.4858823529411775.513
316274AC1-208 C
Adder
10.255294117647068.717
961792AG1-021 E
Adder
1.38941176470588231.181
917342Z2-044 E
Adder
0.6764705882352940.575
3151311EDGECMA
Adder
17.50705882352941214.881
3143316POE
Adder
1.30823529411764721.112
939191AE1-149 C
Adder
9.5941176470588238.155
901082W1-029 E
Adder
35.7705882352941230.405
316365AB2-100 C1
50/50
1.1231.123
926206AC1-098 E
Adder
4.1470588235294123.525
935171AD1-152 C
50/50
1.6091.609
964791AG1-342 C
Adder
3.96470588235294133.37
939411AE1-173 C
50/50
128.665128.665
913392Y1-086 E
50/50
2.4762.476
3137643SOCKMAN
Adder
0.81882352941176460.696
937481AD2-202 C
50/50
0.4540.454
919710AA2-057 E
Adder
4.49411764705882363.82
919152AA1-139 E1
50/50
4.6184.618
316018AA1-139 ULT2
50/50
1.2231.223
942342AE2-247 E
Adder
2.141.819
920042AA2-088 E OP
Adder
11.94941176470588210.157
934511AD1-075 C
Adder
9.507058823529418.081
934521AD1-076 C
Adder
13.81176470588235411.74
3145723EMPORIA
50/50
0.50.5
923573AB1-173 E OP
Adder
3.78941176470588253.221
919692AA2-053 E OP
Adder
4.8352941176470594.11
925785AC1-054 E
Adder
3.94000000000000043.349
959311AF2-222 C
Adder
17.79058823529411615.122
316263AC1-034 C
Adder
7.4894117647058826.366
926755AC1-161 E
50/50
14.89414.894
933291AC2-141 C
50/50
34.8934.89
925522AC1-027 E
50/50
1.3621.362
957872AF2-081 E
50/50
4.844.84
3145256KINGFORK
Adder
1.06588235294117650.906
3150921YORKTN3
Adder
6.2929411764705885.349
941102AE2-104 E
Adder
5.8305882352941184.956
316087AB2-174 C
50/50
1.3621.362
964242AG1-285 E
50/50
9.9189.918
926214AC1-099 E
Adder
1.36941176470588231.164
932632AC2-084 E
Adder
3.66588235294117663.116
924162AB2-060 E OP
Adder
4.8364705882352944.111
964792AG1-342 E
Adder
2.6435294117647062.247
932763AC2-100 E
Adder
2.80941176470588252.388
939192AE1-149 E
Adder
6.3964705882352955.437
934065AD1-033 E
50/50
5.6715.671
939312AE1-162 E
Adder
1.37058823529411771.165
937226AE2-253 E
50/50
6.6066.606
316321Z2-027 C
50/50
0.410.41
3151031BRUNSWICKG2
50/50
12.28212.282
924517AB2-100 E2
50/50
3.3843.384
934501AD1-074 C
Adder
38.0305882352941232.326
957482AF2-042 E
50/50
46.62746.627
934621AD1-088 C
50/50
11.53711.537
935172AD1-152 E
50/50
6.6176.617
946301AF1-294 C
Adder
3.3517647058823532.849
961671AG1-007 C
Adder
1.05882352941176470.9
939412AE1-173 E
50/50
85.77785.777
941032AE2-094 E
50/50
27.25927.259
941031AE2-094 C
50/50
60.86460.864
926662AC1-147 E
Adder
1.46588235294117641.246
916192Z1-068 E
50/50
2.1052.105
957492AF2-043 E
Adder
1.58117647058823541.344
923852AB2-025 E
50/50
1.3891.389
3151051BRUNSWICKS1
50/50
25.51625.516
961941AG1-037 C
Adder
0.5717647058823530.486
961942AG1-037 E
Adder
0.381176470588235340.324
936262AD2-033 E
Adder
9.0082352941176477.657
958211AF2-115 C
Adder
2.03764705882352941.732
934321AD1-056 C
Adder
7.126.052
934331AD1-057 C
Adder
3.9717647058823533.376
934332AD1-057 E
Adder
2.0682352941176471.758
934322AD1-056 E
Adder
3.86117647058823543.282
927022AC1-189 E
Adder
4.7282352941176474.019
925595AC1-034 E
Adder
5.65058823529411754.803
944011AF1-069 C
50/50
19.88619.886
3151091ELIZAR2
50/50
3.4943.494
3151081ELIZAR1
50/50
3.5563.556
941591AE2-156 C
50/50
19.83519.835
944591AF1-124 C
50/50
51.55751.557
944601AF1-125 C
50/50
50.58350.583
316316AC1-027 C
50/50
0.3530.353
936666AD2-085 E
Adder
5.8329411764705884.958
963041AG1-153 C
50/50
8.3218.321
938771AE1-103 C
Adder
3.24823529411764732.761
3145413WATKINS
Adder
0.7717647058823530.656
960081AF2-299 C
50/50
2.1712.171
926072AC1-086 E
Adder
10.9894117647058819.341
3151531CLOVER1
50/50
15.90415.904
936261AD2-033 C
Adder
13.51176470588235311.485
961791AG1-021 C
Adder
1.63058823529411771.386
962562AG1-105 E
Adder
6.6470588235294125.65
944012AF1-069 E
50/50
7.7257.725
316315AB2-025 C
50/50
0.4880.488
946282AF1-292 E
50/50
1.1981.198
3138533PONTONDP
Adder
0.60352941176470590.513
917512Z2-088 E OP1
Adder
5.5247058823529414.696
3151101ELIZAR3
50/50
3.6013.601
944582AF1-123 E
50/50
117.641117.641
944592AF1-124 E
50/50
118.067118.067
935112AD1-144 E
Adder
0.98941176470588230.841
316349AD2-085 C
Adder
3.5752941176470593.039
923832AB2-022 E
50/50
1.3981.398
963042AG1-153 E
50/50
12.48112.481
938772AE1-103 E
Adder
4.4858823529411773.813
916042Z1-036 E
Adder
32.1705882352941227.345
316023AB2-100 C2
50/50
1.1231.123
946281AF1-292 C
50/50
1.7971.797
960082AF2-299 E
50/50
1.4471.447
926071AC1-086 C
Adder
24.1447058823529420.523
3151541CLOVER2
50/50
15.75715.757
964241AG1-285 C
50/50
14.87614.876
958212AF2-115 E
Adder
1.73647058823529421.476
927021AC1-189 C
Adder
9.4905882352941178.067
962561AG1-105 C
Adder
9.9705882352941188.475
924152AB2-059 E OP
Adder
5.9564705882352945.063
944581AF1-123 C
50/50
51.37451.374
316185AD1-033 C
50/50
1.391.39
941101AE2-104 C
Adder
3.66705882352941173.117
316320Y1-086 C
50/50
0.2480.248
3151041BRUNSWICKG3
50/50
12.28212.282
3151021BRUNSWICKG1
50/50
12.28212.282
957481AF2-042 C
50/50
69.9469.94
316088AB2-174 E
50/50
7.5427.542
316141AB2-099 E
Adder
0.28588235294117650.243
923994AB2-040_E
Adder
7.1047058823529416.039
924322AB2-079 E O1
Adder
1.52117647058823541.293
946302AF1-294 E
Adder
2.83882352941176472.413
961672AG1-007 E
Adder
0.60.51
943902AF1-058 E
Adder
1.42941176470588241.215
940642AE2-051 E
50/50
17.4117.41
316388AE2-253 GEN
50/50
2.2212.221
919153AA1-139 E2
50/50
4.6184.618
943462AF1-017 E
Adder
2.2870588235294121.944
942341AE2-247 C
Adder
1.54941176470588231.317
958162AF2-110 E
Adder
2.38000000000000032.023
924516AB2-100 E1
50/50
3.3843.384
934512AD1-075 E
Adder
4.844.114
934502AD1-074 E
Adder
19.3616.456
966621AG1-532 C
50/50
1.6281.628
918512AA1-065 E OP
Adder
6.2505882352941175.313
3147223TWITTYS
Adder
1.03411764705882360.879
959312AF2-222 E
Adder
11.9210.132
924022AB2-043 E O1
Adder
5.9035294117647065.018
918532AA1-067 E
Adder
0.80588235294117660.685
940641AE2-051 C
50/50
26.11526.115
316084AB2-161 E
Adder
5.26941176470588254.479
3145946PLYMOUTH TP
Adder
0.364705882352941160.31
933982AD1-022 E
Adder
5.3847058823529414.577
934622AD1-088 E
50/50
5.5555.555
934611AD1-087 C
50/50
1.5661.566
934612AD1-087 E
50/50
4.5174.517
927146AC1-208 E
Adder
4.5541176470588243.871
927255AC1-221 E
Adder
4.1411764705882363.52
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.47229.472
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.8122.81
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.8563.856
LAGNLTFEXP_LAGN->PJM
CLTF
8.048.04
NYPJM->LTFIMP_NY
CLTF
1.6611.661
LGEELTFEXP_LGEE->PJM
CLTF
1.1651.165
WECLTFEXP_WEC->PJM
CLTF
0.6140.614
G-007PJM->LTFIMP_G-007
CMTX_NF
3.5513.551
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.3016.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
107.493107.493
CPLELTFEXP_CPLE->PJM
CLTF
13.22113.221
TVALTFEXP_TVA->PJM
CLTF
6.2796.279
O66PJM->LTFIMP_O-066
CMTX_NF
22.61622.616

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:136.2 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3326.15
MW Contribution:257.42
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:145.97 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3564.81
MW Contribution:259.27
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944011AF1-069 C
Adder
17.03647058823529314.481
3151091ELIZAR2
50/50
5.4685.468
3151081ELIZAR1
50/50
5.5655.565
941591AE2-156 C
50/50
31.07431.074
925332AB2-190 E
Adder
10.335294117647068.785
944591AF1-124 C
50/50
79.76979.769
944601AF1-125 C
50/50
78.26278.262
316316AC1-027 C
50/50
0.550.55
927226AC1-216 E
Adder
10.5317647058823528.952
3150601CHESTF5
Adder
72.936470588235361.996
936666AD2-085 E
Adder
8.5588235294117647.275
962962AG1-145 E
50/50
2.4882.488
963041AG1-153 C
Adder
7.1717647058823536.096
938771AE1-103 C
Adder
4.5305882352941173.851
3145413WATKINS
Adder
1.03764705882352940.882
960081AF2-299 C
Adder
2.3023529411764711.957
964212AG1-282 E
Adder
1.84352941176470591.567
926072AC1-086 E
Adder
12.19176470588235310.363
933292AC2-141 E
50/50
24.37824.378
316294AC1-161 C
50/50
9.3329.332
944602AF1-125 E
50/50
179.158179.158
916191Z1-068 C
50/50
0.0760.076
3145506HICKORY
50/50
3.8083.808
934576AD1-082 E
Adder
5.9741176470588245.078
957871AF2-081 C
50/50
17.30217.302
943612AF1-032 E
50/50
1.5651.565
3130536PAPERMILL
Adder
9.9929411764705888.494
939602AE1-190 E
Adder
2.1164705882352941.799
940492AE2-034 E
Adder
4.8058823529411764.085
934522AD1-076 E
Adder
9.4435294117647068.027
936591AD2-074 C
Adder
7.8788235294117656.697
943172AE2-346 E
Adder
0.85647058823529410.728
918492AA1-063AE OP
Adder
5.464705882352944.645
917332KELFORD E
Adder
2.25294117647058821.915
925122AB2-169 E
Adder
8.1847058823529426.957
926755AC1-161 E
50/50
24.37824.378
933291AC2-141 C
50/50
57.10857.108
925522AC1-027 E
50/50
2.1192.119
944631AF1-128 C
Adder
31.06000000000000226.401
3151161SURRY 1
50/50
37.9237.92
957872AF2-081 E
50/50
7.4157.415
3145256KINGFORK
50/50
1.7041.704
3150921YORKTN3
50/50
212.818212.818
316305AF2-043 C
50/50
0.590.59
316160AE1-175 E
50/50
2.0532.053
941102AE2-104 E
50/50
8.7058.705
936592AD2-074 E
Adder
12.85529411764705910.927
926214AC1-099 E
Adder
1.56235294117647071.328
932632AC2-084 E
Adder
4.183.553
939412AE1-173 E
50/50
91.51291.512
941032AE2-094 E
Adder
23.3529411764705919.85
941031AE2-094 C
Adder
52.14117647058823544.32
926662AC1-147 E
50/50
2.2972.297
916192Z1-068 E
50/50
3.2743.274
316076AC2-137 E
Adder
1.64117647058823551.395
957492AF2-043 E
50/50
2.4072.407
923852AB2-025 E
Adder
1.42470588235294131.211
923842AB2-024 E
Adder
2.7035294117647062.298
316157AD2-030 E
Adder
1.7917647058823531.523
964211AG1-282 C
Adder
2.76588235294117672.351
961941AG1-037 C
Adder
0.71294117647058820.606
961942AG1-037 E
Adder
0.475294117647058870.404
940642AE2-051 E
50/50
16.6416.64
316388AE2-253 GEN
50/50
3.4133.413
919153AA1-139 E2
50/50
7.0757.075
943462AF1-017 E
Adder
3.35647058823529452.853
942341AE2-247 C
Adder
2.2741176470588241.933
316246AF1-032 C
50/50
0.4820.482
316382AG1-145 C
50/50
0.610.61
958162AF2-110 E
50/50
3.5543.554
924516AB2-100 E1
Adder
3.61411764705882373.072
934512AD1-075 E
Adder
6.4917647058823525.518
934502AD1-074 E
Adder
25.96941176470588522.074
966621AG1-532 C
Adder
1.72705882352941181.468
918512AA1-065 E OP
Adder
7.9635294117647066.769
963612AG1-210 E
Adder
1.35529411764705881.152
918532AA1-067 E
Adder
0.94588235294117650.804
3152331SURRY 2
50/50
50.93450.934
935162AD1-151 E
Adder
14.19058823529411712.062
938532AE1-072 E
50/50
15.80515.805
3146326AYDLETT TAP
50/50
2.3362.336
943461AF1-017 C
Adder
2.05764705882352941.749
316311AC2-079 C
Adder
8.827.497
932596AC2-079 E
Adder
14.39058823529411812.232
917122Z2-027 E
50/50
2.2672.267
3156056W1-029WIND
50/50
1.2961.296
957832AF2-077 E
50/50
2.3562.356
940551AE2-041 C
Adder
10.7682352941176489.153
920692AA2-178 E
Adder
6.4070588235294125.446
966622AG1-532 E
Adder
1.1517647058823530.979
316036AC1-147 C
50/50
0.6390.639
924814AB2-134 E
Adder
17.2517647058823514.664
919152AA1-139 E1
50/50
7.0757.075
316018AA1-139 ULT2
50/50
1.8731.873
942342AE2-247 E
Adder
3.142.669
920042AA2-088 E OP
Adder
15.25058823529411712.963
934511AD1-075 C
Adder
12.75411764705882310.841
934521AD1-076 C
Adder
18.52705882352941215.748
3145723EMPORIA
Adder
0.53411764705882360.454
939246AE1-155 E
Adder
12.06941176470588310.259
923573AB1-173 E OP
Adder
4.1152941176470593.498
919692AA2-053 E OP
Adder
5.50588235294117644.68
3151101ELIZAR3
50/50
5.6365.636
944582AF1-123 E
50/50
182.015182.015
944592AF1-124 E
50/50
182.674182.674
3144216WINCHST
50/50
0.2310.231
935112AD1-144 E
50/50
1.5821.582
316349AD2-085 C
Adder
5.2458823529411764.459
316169AC1-164 GEN
50/50
61.5761.57
923832AB2-022 E
50/50
2.1082.108
963042AG1-153 E
Adder
10.757647058823539.144
938772AE1-103 E
Adder
6.257647058823535.319
916042Z1-036 E
50/50
46.21946.219
946281AF1-292 C
Adder
1.90588235294117661.62
960082AF2-299 E
Adder
1.53529411764705871.305
926071AC1-086 C
Adder
26.78823529411764822.77
932046AC2-012 E
50/50
22.72422.724
935161AD1-151 C
Adder
21.28588235294117618.093
316017AA1-139 ULT1
50/50
1.8731.873
938531AE1-072 C
50/50
30.31830.318
958161AF2-110 C
50/50
2.2342.234
3145393UNCAMP
Adder
9.2964705882352947.902
933981AD1-022 C
Adder
13.0952941176470611.131
900672V4-068 E
Adder
0.50705882352941180.431
3150981CHESPKA
50/50
0.7560.756
944581AF1-123 C
50/50
79.48679.486
316185AD1-033 C
50/50
2.1522.152
941101AE2-104 C
50/50
5.4755.475
316320Y1-086 C
50/50
0.3740.374
934392AD1-063 E
Adder
1.61529411764705881.373
943742AF1-042 E
Adder
6.7258823529411765.717
962862AG1-135 E
Adder
5.63764705882352954.792
966662AG1-536 E
Adder
10.0188235294117658.516
316088AB2-174 E
Adder
8.1305882352941186.911
316141AB2-099 E
Adder
0.35647058823529410.303
923994AB2-040_E
Adder
7.7152941176470586.558
316375AC2-012 C
50/50
2.3432.343
316236AE1-162 C
50/50
0.5660.566
961611AG1-000B C
Adder
23.74470588235294220.183
3138116ELKO L286
Adder
1.71058823529411771.454
313526AB2-022 C
50/50
0.640.64
940541AE2-040 C
Adder
3.5223529411764712.994
940482AE2-033 E
Adder
13.4152941176470611.403
940481AE2-033 C
Adder
19.89882352941176816.914
957831AF2-077 C
50/50
0.5460.546
963611AG1-210 C
Adder
0.90352941176470590.768
923263AB1-132 E OP
Adder
7.79647058823529456.627
939192AE1-149 E
Adder
8.8705882352941187.54
3150991CHESPKB
50/50
1.2531.253
934065AD1-033 E
50/50
8.788.78
939312AE1-162 E
50/50
2.3092.309
937226AE2-253 E
50/50
10.1510.15
316321Z2-027 C
50/50
0.6140.614
924517AB2-100 E2
Adder
3.61411764705882373.072
934501AD1-074 C
Adder
51.01411764705882543.362
943741AF1-042 C
Adder
4.122352941176473.504
962861AG1-135 C
Adder
8.4564705882352957.188
3141813NORNECK
Adder
1.20352941176470571.023
939191AE1-149 C
Adder
13.30705882352941111.311
316159AE1-175 C
50/50
0.6760.676
901082W1-029 E
50/50
53.16253.162
934146AD1-041 E
Adder
5.2917647058823534.498
957601AF2-054 C
Adder
3.1929411764705882.714
958261AF2-120 C
Adder
8.6682352941176477.368
926206AC1-098 E
Adder
4.72941176470588154.02
939411AE1-173 C
50/50
137.269137.269
934012AD1-025 E
Adder
13.63529411764705811.59
913392Y1-086 E
50/50
3.7343.734
939612AE1-191 E
Adder
8.4670588235294127.197
3156116Z1-036WIND
50/50
1.0631.063
957602AF2-054 E
Adder
2.12823529411764721.809
966661AG1-536 C
Adder
7.4564705882352956.338
958262AF2-120 E
Adder
5.7788235294117654.912
316078AC2-138 E
Adder
1.26470588235294111.075
3137643SOCKMAN
Adder
0.90352941176470590.768
944012AF1-069 E
Adder
6.6188235294117655.626
925865AC1-065 E
Adder
24.48470588235294420.812
961951AG1-038 C
Adder
4.5564705882352943.873
961952AG1-038 E
Adder
6.2929411764705885.349
946282AF1-292 E
Adder
1.27058823529411781.08
940641AE2-051 C
50/50
24.9624.96
316084AB2-161 E
Adder
7.497647058823536.373
316072AD1-144 C
50/50
0.4730.473
926785AC1-164_E
50/50
27.66227.662
943471AF1-018 C
Adder
10.7682352941176489.153
3145946PLYMOUTH TP
Adder
0.491764705882352940.418
933982AD1-022 E
Adder
7.1294117647058826.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.55415.554
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.85316.853
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.4842.484
LAGNLTFEXP_LAGN->PJM
CLTF
6.3726.372
NYPJM->LTFIMP_NY
CLTF
1.6271.627
LGEELTFEXP_LGEE->PJM
CLTF
0.6520.652
WECLTFEXP_WEC->PJM
CLTF
0.3380.338
G-007PJM->LTFIMP_G-007
CMTX_NF
3.3653.365
SIGELTFEXP_SIGE->PJM
CLTF
0.1430.143
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.8765.876
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69696.696
CPLELTFEXP_CPLE->PJM
CLTF
12.33712.337
TVALTFEXP_TVA->PJM
CLTF
4.9324.932
O66PJM->LTFIMP_O-066
CMTX_NF
21.46821.468

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.81 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4713.58
MW Contribution:247.5
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:137.16 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5582.72
MW Contribution:259.78
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938552AE1-074 E
Adder
1.90000000000000011.615
944011AF1-069 C
Adder
18.02352941176470615.32
941591AE2-156 C
Adder
30.2317647058823525.697
925332AB2-190 E
Adder
13.54588235294117611.514
944591AF1-124 C
Adder
76.6964705882352965.192
944601AF1-125 C
Adder
75.2470588235294163.96
927226AC1-216 E
Adder
12.9976470588235311.048
3150601CHESTF5
50/50
107.532107.532
936666AD2-085 E
Adder
9.244705882352947.858
962962AG1-145 E
50/50
2.5352.535
963041AG1-153 C
Adder
7.67882352941176556.527
938771AE1-103 C
Adder
4.6882352941176473.985
3145413WATKINS
Adder
1.08705882352941190.924
960081AF2-299 C
Adder
2.6764705882352942.275
964212AG1-282 E
Adder
2.01294117647058851.711
3150831SPRUNCA
Adder
14.5823529411764712.395
3150841SPRUNCB
Adder
14.5823529411764712.395
939412AE1-173 E
Adder
91.772941176470678.007
941032AE2-094 E
Adder
24.70588235294117821
941031AE2-094 C
Adder
55.1635294117647146.889
926662AC1-147 E
Adder
2.2364705882352941.901
916192Z1-068 E
Adder
3.16941176470588242.694
316076AC2-137 E
50/50
2.32.3
957492AF2-043 E
Adder
2.37058823529411772.015
923852AB2-025 E
Adder
1.7117647058823531.455
966872AG1-558 E
Adder
1.88235294117647081.6
966871AG1-558 C
Adder
3.73647058823529443.176
923842AB2-024 E
Adder
2.99058823529411732.542
316157AD2-030 E
Adder
1.94470588235294131.653
964211AG1-282 C
Adder
3.02000000000000052.567
961941AG1-037 C
Adder
0.76117647058823530.647
961942AG1-037 E
Adder
0.50705882352941180.431
933292AC2-141 E
50/50
22.27722.277
316294AC1-161 C
50/50
8.5288.528
946262AF1-291 E
Adder
2.34117647058823541.99
3150651CHESTF6
Adder
30.4035294117647125.843
944602AF1-125 E
Adder
172.25764705882355146.419
3145506HICKORY
Adder
3.66705882352941173.117
934576AD1-082 E
Adder
7.1941176470588246.115
957871AF2-081 C
Adder
16.73529411764705814.225
943612AF1-032 E
Adder
1.54117647058823541.31
3130536PAPERMILL
Adder
11.0400000000000019.384
939602AE1-190 E
Adder
2.33764705882352961.987
940492AE2-034 E
Adder
4.8823529411764714.15
934522AD1-076 E
Adder
9.7164705882352948.259
936591AD2-074 C
Adder
8.5505882352941187.268
943172AE2-346 E
Adder
0.91294117647058830.776
918492AA1-063AE OP
Adder
6.0129411764705885.111
917332KELFORD E
Adder
2.43058823529411772.066
925122AB2-169 E
Adder
8.6200000000000017.327
316233AE1-074 C
Adder
3.7705882352941183.205
3152331SURRY 2
50/50
44.51344.513
935162AD1-151 E
Adder
18.0752941176470615.364
3150691DARBY 3
50/50
4.2724.272
938532AE1-072 E
Adder
15.31411764705882413.017
3146326AYDLETT TAP
Adder
2.26588235294117621.926
926755AC1-161 E
50/50
22.27722.277
933291AC2-141 C
50/50
52.18752.187
925522AC1-027 E
Adder
2.05294117647058851.745
944631AF1-128 C
50/50
67.28467.284
957872AF2-081 E
Adder
7.1717647058823536.096
3145256KINGFORK
Adder
1.70470588235294131.449
3150921YORKTN3
50/50
208.205208.205
316160AE1-175 E
50/50
2.0922.092
316312AB1-027 C
50/50
0.8920.892
941102AE2-104 E
Adder
8.815294117647067.493
936592AD2-074 E
Adder
13.95176470588235211.859
316240AF1-291 C
Adder
3.5117647058823532.985
944641AF1-129 C
Adder
166.98352941176472141.936
924814AB2-134 E
Adder
21.28941176470588218.096
3150641CHESTS8
50/50
3.3243.324
919152AA1-139 E1
Adder
6.8435294117647065.817
942342AE2-247 E
Adder
3.39176470588235322.883
920042AA2-088 E OP
Adder
16.25647058823529513.818
934511AD1-075 C
Adder
13.12352941176470511.155
934521AD1-076 C
Adder
19.0647058823529416.205
3145723EMPORIA
Adder
0.61764705882352940.525
939246AE1-155 E
Adder
13.111.135
923573AB1-173 E OP
Adder
4.7082352941176474.002
944582AF1-123 E
Adder
175.0035294117647148.753
944592AF1-124 E
Adder
175.63764705882355149.292
3150631CHESTG8
50/50
6.4576.457
3144216WINCHST
50/50
0.2290.229
935112AD1-144 E
Adder
1.58235294117647051.345
316349AD2-085 C
Adder
5.6658823529411774.816
930122AB1-027 E
50/50
2.342.34
316169AC1-164 GEN
50/50
71.02671.026
923832AB2-022 E
Adder
2.0588235294117651.75
963042AG1-153 E
Adder
11.517647058823539.79
938772AE1-103 E
Adder
6.4741176470588245.503
916042Z1-036 E
Adder
46.2035294117647139.273
946281AF1-292 C
Adder
2.2152941176470591.883
960082AF2-299 E
Adder
1.78470588235294111.517
926071AC1-086 C
Adder
8.492941176470597.219
940642AE2-051 E
Adder
16.92588235294117614.387
3150681DARBY 2
50/50
4.2574.257
919153AA1-139 E2
Adder
6.8435294117647065.817
943462AF1-017 E
Adder
3.62470588235294143.081
942341AE2-247 C
Adder
2.4552941176470592.087
316382AG1-145 C
50/50
0.6220.622
926412AC1-112 E
50/50
1.9031.903
958162AF2-110 E
Adder
3.5988235294117653.059
924516AB2-100 E1
Adder
4.20352941176470553.573
934512AD1-075 E
Adder
6.685.678
934502AD1-074 E
Adder
26.72117647058823722.713
966621AG1-532 C
Adder
2.00705882352941161.706
918512AA1-065 E OP
Adder
8.397647058823537.138
963612AG1-210 E
Adder
1.47058823529411781.25
943461AF1-017 C
Adder
2.2223529411764711.889
316311AC2-079 C
Adder
9.4458823529411768.029
932596AC2-079 E
Adder
15.41176470588235313.1
917122Z2-027 E
Adder
2.22117647058823531.888
957832AF2-077 E
Adder
2.41411764705882352.052
927042AC1-191 E
Adder
7.4741176470588236.353
940551AE2-041 C
Adder
11.82823529411764710.054
920692AA2-178 E
Adder
6.5094117647058835.533
966622AG1-532 E
Adder
1.33882352941176451.138
3150731STONECA
Adder
11.5258823529411789.797
932046AC2-012 E
Adder
22.12352941176470718.805
935161AD1-151 C
Adder
27.11411764705882623.047
3150701DARBY 4
50/50
4.2774.277
938531AE1-072 C
Adder
29.3776470588235324.971
958161AF2-110 C
Adder
2.2623529411764711.923
3145393UNCAMP
Adder
9.664705882352948.215
933981AD1-022 C
Adder
13.55882352941176611.525
900672V4-068 E
Adder
0.54235294117647060.461
942002AE2-212 E
Adder
2.31764705882352961.97
940431AE2-027 C
Adder
21.05411764705882417.896
944581AF1-123 C
Adder
76.4247058823529464.961
941101AE2-104 C
Adder
5.5447058823529414.713
934392AD1-063 E
Adder
1.77411764705882361.508
943742AF1-042 E
Adder
7.3000000000000016.205
962862AG1-135 E
Adder
6.1188235294117645.201
966662AG1-536 E
Adder
10.8741176470588249.243
316088AB2-174 E
Adder
9.3494117647058837.947
316141AB2-099 E
Adder
0.380.323
923994AB2-040_E
Adder
8.8282352941176477.504
942001AE2-212 C
Adder
3.4764705882352942.955
939192AE1-149 E
Adder
11.6211764705882359.878
934065AD1-033 E
Adder
8.4505882352941187.183
939312AE1-162 E
Adder
2.4211764705882352.058
937226AE2-253 E
Adder
9.88.33
316004AC1-112 C
50/50
0.5560.556
924517AB2-100 E2
Adder
4.20352941176470553.573
934501AD1-074 C
Adder
52.4929411764705944.619
943741AF1-042 C
Adder
4.4741176470588243.803
962861AG1-135 C
Adder
9.177647058823537.801
3141813NORNECK
Adder
1.30588235294117671.11
961611AG1-000B C
Adder
26.9129411764705922.876
3138116ELKO L286
50/50
2.3992.399
940541AE2-040 C
Adder
4.2317647058823533.597
940482AE2-033 E
Adder
16.0529411764705913.645
940481AE2-033 C
Adder
23.8117647058823520.24
927041AC1-191 C
Adder
15.00352941176470612.753
963611AG1-210 C
Adder
0.980.833
3143316POE
Adder
2.15411764705882371.831
939191AE1-149 C
Adder
17.43176470588235514.817
316159AE1-175 C
50/50
0.6890.689
901082W1-029 E
Adder
52.4682352941176544.598
934146AD1-041 E
Adder
5.8435294117647054.967
957601AF2-054 C
Adder
3.4647058823529412.945
958261AF2-120 C
Adder
9.4070588235294137.996
939411AE1-173 C
Adder
137.65882352941176117.01
940432AE2-027 E
Adder
14.03647058823529311.931
934012AD1-025 E
Adder
16.82705882352941314.303
913392Y1-086 E
Adder
3.6470588235294123.1
939612AE1-191 E
Adder
9.3494117647058837.947
957602AF2-054 E
Adder
2.31058823529411761.964
966661AG1-536 C
Adder
8.0929411764705876.879
958262AF2-120 E
Adder
6.2717647058823545.331
316078AC2-138 E
Adder
1.37294117647058831.167
944012AF1-069 E
Adder
7.0023529411764715.952
3150621CHESTS7
50/50
3.0123.012
3150611CHESTG7
50/50
6.5626.562
316075AC2-137 C
50/50
0.6540.654
925865AC1-065 E
Adder
27.3976470588235323.288
961951AG1-038 C
Adder
4.9458823529411764.204
961952AG1-038 E
Adder
6.8294117647058825.805
946282AF1-292 E
Adder
1.47764705882352951.256
940641AE2-051 C
Adder
25.38941176470588321.581
316084AB2-161 E
Adder
9.0294117647058827.675
926785AC1-164_E
50/50
31.9131.91
943471AF1-018 C
Adder
11.82823529411764710.054
3145946PLYMOUTH TP
Adder
0.50470588235294120.429
933982AD1-022 E
Adder
7.3811764705882366.274
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.3345.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.55730.557
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.5435.543
LAGNLTFEXP_LAGN->PJM
CLTF
10.28110.281
NYPJM->LTFIMP_NY
CLTF
3.1153.115
LGEELTFEXP_LGEE->PJM
CLTF
1.8191.819
WECLTFEXP_WEC->PJM
CLTF
0.9390.939
G-007PJM->LTFIMP_G-007
CMTX_NF
6.8256.825
SIGELTFEXP_SIGE->PJM
CLTF
0.3490.349
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.017.01
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.912122.912
CPLELTFEXP_CPLE->PJM
CLTF
14.714.7
TVALTFEXP_TVA->PJM
CLTF
8.1358.135
O66PJM->LTFIMP_O-066
CMTX_NF
43.443.4

Details for 8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.6 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3658.55
MW Contribution:158.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3142366NRTHEST
50/50
0.2360.236
961611AG1-000B C
Adder
18.15411764705882215.431
3138116ELKO L286
Adder
1.75647058823529421.493
940541AE2-040 C
Adder
2.73647058823529442.326
940482AE2-033 E
Adder
10.3694117647058828.814
940481AE2-033 C
Adder
15.38117647058823513.074
927041AC1-191 C
50/50
12.81112.811
3150371LDYSMT1
50/50
6.9556.955
963611AG1-210 C
Adder
0.78823529411764710.67
316233AE1-074 C
Adder
2.6270588235294122.233
935162AD1-151 E
Adder
12.49647058823529410.622
3150691DARBY 3
50/50
3.2613.261
938532AE1-072 E
Adder
9.7941176470588228.325
3146326AYDLETT TAP
Adder
1.44941176470588241.232
943461AF1-017 C
Adder
1.4552941176470591.237
316311AC2-079 C
Adder
6.1752941176470585.249
932596AC2-079 E
Adder
10.0764705882352948.565
917122Z2-027 E
Adder
1.42117647058823531.208
957832AF2-077 E
Adder
1.67882352941176481.427
3150481FOUR RIVERF
50/50
5.3255.325
315051AA1-145 CT1
50/50
7.0497.049
927042AC1-191 E
50/50
6.3816.381
940551AE2-041 C
Adder
8.5917647058823537.303
920692AA2-178 E
Adder
4.1576470588235293.534
966622AG1-532 E
Adder
0.85529411764705890.727
3150381LDYSMT2
50/50
7.0467.046
933292AC2-141 E
Adder
14.11411764705882511.997
946262AF1-291 E
Adder
1.67294117647058821.422
3150651CHESTF6
Adder
21.86235294117646818.583
944602AF1-125 E
Adder
110.112941176470693.596
3145506HICKORY
Adder
2.3435294117647061.992
934576AD1-082 E
Adder
4.8176470588235294.095
3143316POE
Adder
1.46235294117647091.243
939191AE1-149 C
Adder
11.85294117647058710.075
901082W1-029 E
Adder
33.6023529411764728.562
934146AD1-041 E
Adder
4.2517647058823533.614
957601AF2-054 C
Adder
2.5211764705882352.143
3150401LDYSMT4
50/50
7.2457.245
958261AF2-120 C
Adder
7.4223529411764716.309
316240AF1-291 C
Adder
2.5105882352941182.134
944641AF1-129 C
Adder
120.07411764705883102.063
924814AB2-134 E
Adder
14.62588235294117712.432
919152AA1-139 E1
Adder
4.3764705882352953.72
942342AE2-247 E
Adder
2.22117647058823531.888
920042AA2-088 E OP
Adder
10.4070588235294138.846
934511AD1-075 C
Adder
8.3752941176470597.119
934521AD1-076 C
Adder
12.16705882352941310.342
3145723EMPORIA
Adder
0.39411764705882360.335
939246AE1-155 E
Adder
10.3364705882352948.786
923573AB1-173 E OP
Adder
3.00235294117647072.552
957972AF2-091 E
Adder
3.1105882352941182.644
938552AE1-074 E
Adder
1.32352941176470581.125
926755AC1-161 E
Adder
14.11411764705882511.997
933291AC2-141 C
Adder
33.06352941176470528.104
925522AC1-027 E
Adder
1.3152941176470591.118
944631AF1-128 C
Adder
48.5670588235294141.282
957872AF2-081 E
Adder
4.58588235294117653.898
3145256KINGFORK
Adder
1.10588235294117650.94
3150921YORKTN3
Adder
139.0764705882353118.215
316160AE1-175 E
Adder
1.4270588235294121.213
316312AB1-027 C
50/50
0.6940.694
941102AE2-104 E
Adder
5.69058823529411754.837
315052AA1-145 CT2
50/50
7.0467.046
938562AE1-075 E
Adder
0.92941176470588240.79
936592AD2-074 E
Adder
10.7858823529411769.168
3150411LDYSMT5
50/50
7.2687.268
934782AD1-105 E
Adder
6.1211764705882365.203
942001AE2-212 C
Adder
2.4364705882352942.071
939192AE1-149 E
Adder
7.9023529411764716.717
934065AD1-033 E
Adder
5.4035294117647064.593
939312AE1-162 E
Adder
1.5964705882352941.357
937226AE2-253 E
Adder
6.2658823529411765.326
3142296MT RD221
50/50
0.1630.163
316004AC1-112 C
50/50
0.4320.432
3150471FOUR RIVERE
50/50
4.3614.361
3150831SPRUNCA
Adder
10.5929411764705879.004
3150841SPRUNCB
Adder
10.5929411764705879.004
939412AE1-173 E
Adder
56.8788235294117748.347
941032AE2-094 E
Adder
15.02823529411764612.774
941031AE2-094 C
Adder
33.5552941176470628.522
926662AC1-147 E
Adder
1.43647058823529421.221
916192Z1-068 E
Adder
2.0305882352941181.726
316076AC2-137 E
Adder
1.6835294117647061.431
957492AF2-043 E
Adder
1.52235294117647071.294
923852AB2-025 E
Adder
1.10705882352941170.941
944011AF1-069 C
Adder
10.9635294117647079.319
941591AE2-156 C
Adder
19.41529411764705816.503
925332AB2-190 E
Adder
9.4164705882352948.004
944591AF1-124 C
Adder
49.02705882352941641.673
944601AF1-125 C
Adder
48.1011764705882440.886
927226AC1-216 E
Adder
8.9282352941176487.589
3150601CHESTF5
Adder
77.6188235294117765.976
936666AD2-085 E
Adder
6.0552941176470595.147
962962AG1-145 E
Adder
1.73058823529411781.471
938771AE1-103 C
Adder
3.0152941176470592.563
3145413WATKINS
Adder
0.69764705882352940.593
966881AG1-559 C
50/50
3.5873.587
960081AF2-299 C
Adder
1.71058823529411771.454
964212AG1-282 E
Adder
1.59882352941176481.359
944012AF1-069 E
Adder
4.2588235294117653.62
3150431FOUR RIVERA
50/50
4.4254.425
925865AC1-065 E
Adder
19.93176470588235516.942
939262AE1-157 E
50/50
11.49311.493
961951AG1-038 C
Adder
3.8235294117647063.25
961952AG1-038 E
Adder
5.2788235294117654.487
946282AF1-292 E
Adder
0.9435294117647060.802
936582AD2-073 E
Adder
1.24588235294117641.059
966872AG1-558 E
50/50
1.6071.607
966871AG1-558 C
50/50
3.1913.191
923842AB2-024 E
Adder
2.16941176470588241.844
923862AB2-026 E
Adder
1.09058823529411760.927
316157AD2-030 E
Adder
1.4152941176470591.203
964211AG1-282 C
Adder
2.3988235294117652.039
961941AG1-037 C
Adder
0.485882352941176430.413
961942AG1-037 E
Adder
0.32352941176470590.275
944582AF1-123 E
Adder
111.8694117647058995.089
944592AF1-124 E
Adder
112.2741176470588395.433
935112AD1-144 E
Adder
1.02705882352941180.873
316349AD2-085 C
Adder
3.71176470588235263.155
930122AB1-027 E
50/50
1.821.82
316169AC1-164 GEN
Adder
50.7141176470588243.107
923832AB2-022 E
Adder
1.31764705882352961.12
938772AE1-103 E
Adder
4.16470588235294153.54
916042Z1-036 E
Adder
29.55058823529411825.118
966882AG1-559 E
50/50
1.8071.807
939261AE1-157 C
50/50
21.18921.189
946281AF1-292 C
Adder
1.4152941176470591.203
960082AF2-299 E
Adder
1.140.969
3150391LDYSMT3
50/50
7.2317.231
926071AC1-086 C
Adder
1.16117647058823530.987
957971AF2-091 C
Adder
2.25294117647058821.915
957871AF2-081 C
Adder
10.7011764705882359.096
943612AF1-032 E
Adder
0.98941176470588230.841
3150441FOUR RIVERB
50/50
4.4254.425
3130536PAPERMILL
Adder
8.0105882352941196.809
939602AE1-190 E
Adder
1.70117647058823531.446
940492AE2-034 E
Adder
3.11882352941176462.651
934522AD1-076 E
Adder
6.2011764705882355.271
936591AD2-074 C
Adder
6.6105882352941175.619
943172AE2-346 E
Adder
0.58235294117647060.495
918492AA1-063AE OP
Adder
3.83529411764705853.26
925122AB2-169 E
Adder
5.48117647058823554.659
942002AE2-212 E
Adder
1.62470588235294121.381
940431AE2-027 C
Adder
14.94470588235294212.703
944581AF1-123 C
Adder
48.8541176470588341.526
941101AE2-104 C
Adder
3.57882352941176453.042
3150461FOUR RIVERD
50/50
4.3614.361
934392AD1-063 E
Adder
1.28823529411764711.095
943742AF1-042 E
Adder
5.6435294117647064.797
962862AG1-135 E
Adder
4.8047058823529414.084
966662AG1-536 E
Adder
8.587.293
316088AB2-174 E
Adder
5.9647058823529415.07
316141AB2-099 E
Adder
0.242352941176470580.206
923994AB2-040_E
Adder
5.6294117647058834.785
944492AF1-114 E
Adder
9.1505882352941177.778
940642AE2-051 E
Adder
10.3694117647058828.814
919153AA1-139 E2
Adder
4.3764705882352953.72
943462AF1-017 E
Adder
2.37411764705882342.018
942341AE2-247 C
Adder
1.6082352941176471.367
926412AC1-112 E
50/50
1.481.48
958162AF2-110 E
Adder
2.3235294117647061.975
924516AB2-100 E1
Adder
2.69764705882352952.293
934512AD1-075 E
Adder
4.2635294117647063.624
934502AD1-074 E
Adder
17.05411764705882414.496
966621AG1-532 C
Adder
1.28235294117647071.09
918512AA1-065 E OP
Adder
5.3564705882352944.553
963612AG1-210 E
Adder
1.18235294117647041.005
940641AE2-051 C
Adder
15.55529411764705813.222
316084AB2-161 E
Adder
6.0470588235294125.14
926785AC1-164_E
Adder
22.7847058823529419.367
943471AF1-018 C
Adder
8.5917647058823537.303
3145946PLYMOUTH TP
Adder
0.32235294117647060.274
933982AD1-022 E
Adder
4.7105882352941174.004
926472AC1-118 E
Adder
1.221.037
3150731STONECA
Adder
8.157647058823536.934
932046AC2-012 E
Adder
14.21176470588235412.08
935161AD1-151 C
Adder
18.74470588235294215.933
3150701DARBY 4
50/50
3.2653.265
938531AE1-072 C
Adder
18.7870588235294115.969
958161AF2-110 C
Adder
1.46000000000000021.241
3145393UNCAMP
Adder
6.2117647058823535.28
933981AD1-022 C
Adder
8.6517647058823537.354
900672V4-068 E
Adder
0.34588235294117650.294
958502AF2-144 E
Adder
1.0717647058823530.911
924517AB2-100 E2
Adder
2.69764705882352952.293
934501AD1-074 C
Adder
33.50117647058823428.476
943741AF1-042 C
Adder
3.4588235294117652.94
962861AG1-135 C
Adder
7.2058823529411776.125
3141813NORNECK
Adder
1.05058823529411760.893
939411AE1-173 C
Adder
85.3176470588235272.52
940432AE2-027 E
Adder
9.9623529411764718.468
934012AD1-025 E
Adder
11.569.826
913392Y1-086 E
Adder
2.33294117647058831.983
3150451FOUR RIVERC
50/50
5.4065.406
939612AE1-191 E
Adder
6.8023529411764715.782
957602AF2-054 E
Adder
1.68117647058823551.429
966661AG1-536 C
Adder
6.3847058823529415.427
958262AF2-120 E
Adder
4.9482352941176484.206
316078AC2-138 E
Adder
1.10352941176470590.938
944491AF1-114 C
Adder
6.6258823529411775.632
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.54824.548
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.76217.762
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.1253.125
LAGNLTFEXP_LAGN->PJM
CLTF
6.0826.082
NYPJM->LTFIMP_NY
CLTF
2.4212.421
LGEELTFEXP_LGEE->PJM
CLTF
1.011.01
WECLTFEXP_WEC->PJM
CLTF
0.5150.515
G-007PJM->LTFIMP_G-007
CMTX_NF
5.2915.291
SIGELTFEXP_SIGE->PJM
CLTF
0.1960.196
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.3184.318
CBM South 2LTFEXP_CBM-S2->PJM
CBM
75.17775.177
CPLELTFEXP_CPLE->PJM
CLTF
9.069.06
TVALTFEXP_TVA->PJM
CLTF
4.8114.811
O66PJM->LTFIMP_O-066
CMTX_NF
33.64633.646

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.34 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1336.88
MW Contribution:61.92
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:127.16 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1345.51
MW Contribution:60.09
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926755AC1-161 E
Adder
5.7376470588235294.877
933291AC2-141 C
Adder
13.44235294117647211.426
925522AC1-027 E
Adder
0.50.425
957872AF2-081 E
Adder
1.79882352941176471.529
3145256KINGFORK
Adder
0.367058823529411770.312
941102AE2-104 E
Adder
2.06588235294117651.756
919152AA1-139 E1
Adder
1.71529411764705891.458
942342AE2-247 E
Adder
0.69411764705882350.59
920042AA2-088 E OP
Adder
4.3847058823529413.727
934511AD1-075 C
Adder
3.55411764705882363.021
934521AD1-076 C
Adder
5.1635294117647064.389
3145723EMPORIA
Adder
0.18470588235294120.157
923573AB1-173 E OP
Adder
1.40588235294117661.195
919692AA2-053 E OP
Adder
1.80705882352941181.536
925785AC1-054 E
Adder
1.47764705882352951.256
959311AF2-222 C
Adder
5.57411764705882454.738
316263AC1-034 C
Adder
2.91411764705882352.477
944582AF1-123 E
Adder
43.7823529411764837.215
944592AF1-124 E
Adder
43.9411764705882437.35
935112AD1-144 E
Adder
0.339999999999999970.289
316349AD2-085 C
Adder
1.15882352941176480.985
923832AB2-022 E
Adder
0.51764705882352950.44
963042AG1-153 E
50/50
5.5095.509
939412AE1-173 E
50/50
36.75136.751
941032AE2-094 E
50/50
12.16712.167
941031AE2-094 C
50/50
27.16527.165
926662AC1-147 E
Adder
0.53176470588235290.452
916192Z1-068 E
Adder
0.77294117647058820.657
957492AF2-043 E
Adder
0.57529411764705880.489
923852AB2-025 E
Adder
0.50705882352941180.431
3151051BRUNSWICKS1
50/50
11.26311.263
961941AG1-037 C
Adder
0.212941176470588240.181
961942AG1-037 E
Adder
0.14235294117647060.121
936262AD2-033 E
Adder
2.8247058823529412.401
934321AD1-056 C
Adder
2.72588235294117662.317
934331AD1-057 C
Adder
1.52117647058823541.293
934332AD1-057 E
Adder
0.7917647058823530.673
934322AD1-056 E
Adder
1.47882352941176461.257
927022AC1-189 E
Adder
1.8235294117647061.55
925595AC1-034 E
Adder
2.19764705882352951.868
940642AE2-051 E
50/50
7.6927.692
919153AA1-139 E2
Adder
1.71529411764705891.458
943462AF1-017 E
Adder
0.74117647058823530.63
942341AE2-247 C
Adder
0.50235294117647060.427
958162AF2-110 E
Adder
0.84352941176470590.717
924516AB2-100 E1
Adder
1.25176470588235311.064
934512AD1-075 E
Adder
1.80941176470588251.538
934502AD1-074 E
Adder
7.237647058823536.152
966621AG1-532 C
Adder
0.60117647058823530.511
918512AA1-065 E OP
Adder
2.34000000000000031.989
3147223TWITTYS
Adder
0.332941176470588240.283
959312AF2-222 E
Adder
3.73411764705882383.174
924022AB2-043 E O1
Adder
2.11764705882352941.8
918532AA1-067 E
Adder
0.30941176470588240.263
936161AD2-022 C
Adder
3.0882352941176472.625
938532AE1-072 E
Adder
3.84235294117647053.266
3146326AYDLETT TAP
Adder
0.56823529411764710.483
943461AF1-017 C
Adder
0.454117647058823570.386
316311AC2-079 C
Adder
1.9682352941176471.673
932596AC2-079 E
Adder
3.2117647058823532.73
3152431Z1-086 GT3
50/50
7.0047.004
944581AF1-123 C
Adder
19.11999999999999716.252
941101AE2-104 C
Adder
1.31.105
3151041BRUNSWICKG3
50/50
5.4215.421
3151021BRUNSWICKG1
50/50
5.4215.421
957481AF2-042 C
Adder
28.3424.089
316088AB2-174 E
Adder
2.7941176470588242.375
316141AB2-099 E
Adder
0.107058823529411760.091
923994AB2-040_E
Adder
2.63647058823529432.241
924322AB2-079 E O1
Adder
0.54823529411764720.466
961672AG1-007 E
Adder
0.232941176470588260.198
943902AF1-058 E
Adder
0.55294117647058830.47
933292AC2-141 E
Adder
5.7376470588235294.877
944602AF1-125 E
Adder
43.0952941176470636.631
3145506HICKORY
Adder
0.91764705882352950.78
957871AF2-081 C
Adder
4.1964705882352953.567
943612AF1-032 E
Adder
0.374117647058823550.318
940492AE2-034 E
Adder
1.2952941176470591.101
934522AD1-076 E
Adder
2.6317647058823532.237
943172AE2-346 E
Adder
0.255294117647058840.217
918492AA1-063AE OP
Adder
1.72705882352941181.468
937482AD2-202 E
Adder
0.52588235294117650.447
917332KELFORD E
Adder
0.70117647058823530.596
925122AB2-169 E
Adder
2.4564705882352942.088
316274AC1-208 C
Adder
3.8952941176470593.311
917342Z2-044 E
Adder
0.26117647058823530.222
3151311EDGECMA
Adder
6.8129411764705895.791
941011AE2-092 C
Adder
-4.452941176470588-3.785
932046AC2-012 E
Adder
5.2588235294117654.47
938531AE1-072 C
Adder
7.3705882352941176.265
958161AF2-110 C
Adder
0.53058823529411770.451
3152411Z1-086 GT1
50/50
7.0067.006
3152421Z1-086 GT2
50/50
7.0047.004
3145393UNCAMP
Adder
2.44352941176470572.077
933981AD1-022 C
Adder
3.73.145
900672V4-068 E
Adder
0.149411764705882360.127
924302AB2-077 E O1
Adder
0.54823529411764720.466
934065AD1-033 E
Adder
2.10705882352941171.791
939312AE1-162 E
Adder
0.41294117647058820.351
937226AE2-253 E
Adder
2.4552941176470592.087
3151031BRUNSWICKG2
50/50
5.4215.421
924517AB2-100 E2
Adder
1.25176470588235311.064
934501AD1-074 C
Adder
14.2176470588235312.085
957482AF2-042 E
Adder
18.89411764705882416.06
934621AD1-088 C
Adder
4.3611764705882353.707
935172AD1-152 E
Adder
2.6258823529411772.232
961671AG1-007 C
Adder
0.410588235294117640.349
936162AD2-022 E
Adder
1.85294117647058831.575
940541AE2-040 C
Adder
1.25411764705882361.066
940482AE2-033 E
Adder
4.7611764705882354.047
940481AE2-033 C
Adder
7.0611764705882366.002
923263AB1-132 E OP
Adder
2.6305882352941182.236
925612AC1-036 E
Adder
0.30.255
924312AB2-078 E O1
Adder
0.54823529411764720.466
926274AC1-105 E
Adder
1.13764705882352950.967
938821AE1-108 C
Adder
-4.716470588235294-4.009
3152441Z1-086 ST
50/50
12.19612.196
917122Z2-027 E
Adder
0.55999999999999990.476
920692AA2-178 E
Adder
1.72705882352941181.468
966622AG1-532 E
Adder
0.40.34
922923AB1-081 E OP
Adder
1.63529411764705881.39
927264AC1-222 E
Adder
1.66470588235294131.415
901082W1-029 E
Adder
13.19764705882352911.218
926206AC1-098 E
Adder
1.57411764705882361.338
964791AG1-342 C
Adder
1.48470588235294131.262
939411AE1-173 C
50/50
55.12655.126
913392Y1-086 E
Adder
0.91764705882352950.78
3137643SOCKMAN
Adder
0.30470588235294120.259
919710AA2-057 E
Adder
1.72588235294117661.467
964242AG1-285 E
Adder
3.57647058823529433.04
926214AC1-099 E
Adder
0.520.442
932632AC2-084 E
Adder
1.3917647058823531.183
924162AB2-060 E OP
Adder
1.71764705882352931.46
964792AG1-342 E
Adder
0.99058823529411770.842
932763AC2-100 E
Adder
1.12117647058823520.953
944011AF1-069 C
50/50
8.8768.876
941591AE2-156 C
Adder
7.202352941176476.122
944591AF1-124 C
Adder
19.18823529411764616.31
944601AF1-125 C
Adder
18.82588235294117516.002
936666AD2-085 E
Adder
1.89058823529411771.607
963041AG1-153 C
50/50
3.6733.673
938771AE1-103 C
Adder
1.16941176470588240.994
3145413WATKINS
Adder
0.279999999999999970.238
960081AF2-299 C
Adder
0.80117647058823540.681
926072AC1-086 E
Adder
4.11294117647058853.496
936261AD2-033 C
Adder
4.2364705882352943.601
962562AG1-105 E
Adder
2.4729411764705882.102
936171AD2-023 C
Adder
1.80117647058823521.531
944012AF1-069 E
50/50
3.4483.448
946282AF1-292 E
Adder
0.44235294117647060.376
917512Z2-088 E OP1
Adder
2.1352941176470591.815
938772AE1-103 E
Adder
1.61529411764705881.373
916042Z1-036 E
Adder
11.93411764705882510.144
946281AF1-292 C
Adder
0.66352941176470580.564
960082AF2-299 E
Adder
0.53411764705882360.454
926071AC1-086 C
Adder
9.037647058823537.682
964241AG1-285 C
Adder
5.3647058823529414.56
927021AC1-189 C
Adder
3.66117647058823573.112
962561AG1-105 C
Adder
3.70941176470588243.153
924152AB2-059 E OP
Adder
2.31764705882352961.97
936172AD2-023 E
Adder
0.97764705882352940.831
940641AE2-051 C
50/50
11.53811.538
316336AC2-165 C
Adder
-10.758823529411764-9.145
3145946PLYMOUTH TP
Adder
0.136470588235294120.116
933982AD1-022 E
Adder
2.01411764705882361.712
934622AD1-088 E
Adder
2.11.785
934612AD1-087 E
Adder
1.79882352941176471.529
927146AC1-208 E
Adder
1.72941176470588241.47
927255AC1-221 E
Adder
1.65176470588235281.404
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.53211.532
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.0379.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5141.514
LAGNLTFEXP_LAGN->PJM
CLTF
3.2073.207
NYPJM->LTFIMP_NY
CLTF
0.5140.514
LGEELTFEXP_LGEE->PJM
CLTF
0.4480.448
WECLTFEXP_WEC->PJM
CLTF
0.2390.239
G-007PJM->LTFIMP_G-007
CMTX_NF
1.0921.092
SIGELTFEXP_SIGE->PJM
CLTF
0.0910.091
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5712.571
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.69643.696
CPLELTFEXP_CPLE->PJM
CLTF
5.3965.396
TVALTFEXP_TVA->PJM
CLTF
2.4942.494
O66PJM->LTFIMP_O-066
CMTX_NF
6.9576.957

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.0 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2588.61
MW Contribution:147.82
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.54 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2748.4
MW Contribution:152.19
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
919152AA1-139 E1
50/50
3.8823.882
316018AA1-139 ULT2
50/50
1.0281.028
920042AA2-088 E OP
Adder
7.3835294117647066.276
934511AD1-075 C
Adder
6.2764705882352945.335
934521AD1-076 C
Adder
9.1176470588235297.75
3145723EMPORIA
Adder
0.352941176470588260.3
923573AB1-173 E OP
Adder
2.65411764705882322.256
919692AA2-053 E OP
Adder
3.30000000000000032.805
925785AC1-054 E
Adder
2.882.448
944581AF1-123 C
50/50
45.64445.644
316185AD1-033 C
50/50
1.2261.226
3151041BRUNSWICKG3
50/50
9.6689.668
3151021BRUNSWICKG1
50/50
9.6689.668
957481AF2-042 C
50/50
55.26355.263
932046AC2-012 E
50/50
12.1712.17
316017AA1-139 ULT1
50/50
1.0281.028
938531AE1-072 C
50/50
16.39816.398
3152411Z1-086 GT1
50/50
12.45512.455
3152421Z1-086 GT2
50/50
12.4512.45
3145393UNCAMP
Adder
3.8517647058823533.274
933981AD1-022 C
Adder
6.4741176470588245.503
900672V4-068 E
Adder
0.254117647058823560.216
924302AB2-077 E O1
Adder
1.18705882352941171.009
934065AD1-033 E
50/50
5.0045.004
937226AE2-253 E
50/50
5.6435.643
3151031BRUNSWICKG2
50/50
9.6689.668
924517AB2-100 E2
Adder
2.3717647058823532.016
316375AC2-012 C
50/50
1.2551.255
940541AE2-040 C
Adder
2.4364705882352942.071
940482AE2-033 E
Adder
9.2211764705882357.838
940481AE2-033 C
Adder
13.6776470588235311.626
923263AB1-132 E OP
Adder
4.8517647058823534.124
925612AC1-036 E
Adder
0.74705882352941180.635
924312AB2-078 E O1
Adder
1.18705882352941171.009
926274AC1-105 E
Adder
2.3364705882352941.986
938532AE1-072 E
50/50
8.5488.548
3146326AYDLETT TAP
Adder
1.25647058823529421.068
3152431Z1-086 GT3
50/50
12.4512.45
3152441Z1-086 ST
50/50
21.68121.681
917122Z2-027 E
Adder
1.1117647058823530.945
920692AA2-178 E
Adder
3.0870588235294122.624
966622AG1-532 E
Adder
0.76941176470588240.654
3147133PAMPLIN
Adder
0.740.629
922923AB1-081 E OP
Adder
2.9811764705882352.534
927264AC1-222 E
Adder
3.3870588235294122.879
933292AC2-141 E
50/50
37.13537.135
316294AC1-161 C
50/50
14.21614.216
944602AF1-125 E
50/50
102.879102.879
916191Z1-068 C
50/50
0.0420.042
3145506HICKORY
50/50
2.1612.161
957871AF2-081 C
50/50
9.4939.493
940492AE2-034 E
Adder
2.3152941176470591.968
934522AD1-076 E
Adder
4.6470588235294123.95
943172AE2-346 E
Adder
0.440.374
918492AA1-063AE OP
Adder
3.0882352941176472.625
937482AD2-202 E
50/50
1.0431.043
917332KELFORD E
Adder
1.2282352941176471.044
925122AB2-169 E
Adder
4.3388235294117653.688
316274AC1-208 C
Adder
7.0835294117647066.021
961792AG1-021 E
Adder
1.13294117647058810.963
917342Z2-044 E
Adder
0.475294117647058870.404
3151311EDGECMA
Adder
12.4152941176470610.553
3143316POE
Adder
0.80823529411764720.687
901082W1-029 E
Adder
23.54352941176470520.012
957601AF2-054 C
Adder
-1.2505882352941176-1.063
926206AC1-098 E
Adder
2.8317647058823532.407
942462AE2-259 E
Adder
4.3564705882352943.703
964791AG1-342 C
Adder
3.09882352941176452.634
939411AE1-173 C
50/50
86.92186.921
913392Y1-086 E
Adder
1.8917647058823531.608
3137643SOCKMAN
Adder
0.56941176470588240.484
937481AD2-202 C
50/50
0.3590.359
919710AA2-057 E
Adder
3.1364705882352942.666
959311AF2-222 C
Adder
14.27882352941176512.137
316263AC1-034 C
Adder
5.31058823529411854.514
926755AC1-161 E
50/50
37.13537.135
933291AC2-141 C
50/50
86.99486.994
925522AC1-027 E
50/50
1.1581.158
957872AF2-081 E
50/50
4.0684.068
964242AG1-285 E
Adder
7.846.664
926214AC1-099 E
Adder
0.93529411764705890.795
932632AC2-084 E
Adder
2.50352941176470622.128
924162AB2-060 E OP
Adder
3.78117647058823543.214
964792AG1-342 E
Adder
2.06588235294117651.756
932763AC2-100 E
Adder
2.1788235294117651.852
934501AD1-074 C
Adder
25.10470588235294221.339
957482AF2-042 E
50/50
36.84236.842
934621AD1-088 C
50/50
9.1619.161
935172AD1-152 E
Adder
5.2058823529411774.425
946301AF1-294 C
Adder
2.73529411764705932.325
942461AE2-259 C
Adder
6.5341176470588245.554
961671AG1-007 C
Adder
0.73882352941176480.628
939412AE1-173 E
50/50
57.94757.947
941032AE2-094 E
50/50
21.48321.483
941031AE2-094 C
50/50
47.96747.967
926662AC1-147 E
Adder
1.23058823529411781.046
916192Z1-068 E
50/50
1.7941.794
923852AB2-025 E
Adder
0.98588235294117640.838
3151051BRUNSWICKS1
50/50
20.08620.086
961941AG1-037 C
Adder
0.367058823529411770.312
961942AG1-037 E
Adder
0.244705882352941160.208
936262AD2-033 E
Adder
7.1529411764705896.08
958211AF2-115 C
Adder
1.6635294117647061.414
934321AD1-056 C
Adder
4.99411764705882364.245
934331AD1-057 C
Adder
2.78588235294117632.368
934332AD1-057 E
Adder
1.45058823529411771.233
934322AD1-056 E
Adder
2.70941176470588242.303
927022AC1-189 E
Adder
3.25764705882352962.769
925595AC1-034 E
Adder
4.00588235294117643.405
944011AF1-069 C
50/50
15.67315.673
3151091ELIZAR2
50/50
2.9782.978
3151081ELIZAR1
50/50
3.033.03
941591AE2-156 C
50/50
16.7516.75
944591AF1-124 C
50/50
45.80645.806
944601AF1-125 C
50/50
44.94144.941
316316AC1-027 C
50/50
0.3010.301
963041AG1-153 C
50/50
6.556.55
938771AE1-103 C
Adder
1.81647058823529431.544
3145413WATKINS
Adder
0.451764705882352960.384
960081AF2-299 C
Adder
1.541.309
926072AC1-086 E
Adder
7.5870588235294126.449
3151531CLOVER1
50/50
12.55212.552
936261AD2-033 C
Adder
10.7294117647058829.12
961791AG1-021 C
Adder
1.33058823529411761.131
962562AG1-105 E
Adder
5.1941176470588244.415
944012AF1-069 E
50/50
6.0886.088
946282AF1-292 E
Adder
0.84941176470588230.722
3138533PONTONDP
Adder
0.49294117647058820.419
917512Z2-088 E OP1
Adder
3.83294117647058833.258
3151101ELIZAR3
50/50
3.0693.069
944582AF1-123 E
50/50
104.52104.52
944592AF1-124 E
50/50
104.898104.898
923832AB2-022 E
Adder
1.06823529411764720.908
963042AG1-153 E
50/50
9.8259.825
938772AE1-103 E
Adder
2.50941176470588222.133
916042Z1-036 E
Adder
21.67647058823529718.425
946281AF1-292 C
Adder
1.27411764705882361.083
960082AF2-299 E
Adder
1.02588235294117650.872
926071AC1-086 C
Adder
16.6705882352941214.17
3151541CLOVER2
50/50
12.43612.436
964241AG1-285 C
Adder
11.7588235294117649.995
958212AF2-115 E
Adder
1.41647058823529411.204
927021AC1-189 C
Adder
6.5388235294117655.558
962561AG1-105 C
Adder
7.7917647058823536.623
924152AB2-059 E OP
Adder
4.2235294117647063.59
316088AB2-174 E
Adder
5.3035294117647064.508
316141AB2-099 E
Adder
0.183529411764705890.156
923994AB2-040_E
Adder
4.9776470588235294.231
924322AB2-079 E O1
Adder
1.18705882352941171.009
946302AF1-294 E
Adder
2.3164705882352941.969
961672AG1-007 E
Adder
0.41882352941176470.356
943902AF1-058 E
Adder
1.11882352941176480.951
940642AE2-051 E
50/50
17.64717.647
316388AE2-253 GEN
50/50
1.8981.898
919153AA1-139 E2
50/50
3.8823.882
924516AB2-100 E1
Adder
2.3717647058823532.016
934512AD1-075 E
Adder
3.19529411764705932.716
934502AD1-074 E
Adder
12.7810.863
966621AG1-532 C
Adder
1.15411764705882350.981
918512AA1-065 E OP
Adder
3.98941176470588273.391
3147223TWITTYS
Adder
0.82823529411764710.704
959312AF2-222 E
Adder
9.5670588235294118.132
924022AB2-043 E O1
Adder
4.6082352941176473.917
918532AA1-067 E
Adder
0.54705882352941180.465
940641AE2-051 C
50/50
26.4726.47
3145946PLYMOUTH TP
Adder
0.24117647058823530.205
933982AD1-022 E
Adder
3.52470588235294142.996
934622AD1-088 E
50/50
4.4114.411
934611AD1-087 C
50/50
1.2361.236
934612AD1-087 E
50/50
3.5653.565
927146AC1-208 E
Adder
3.14470588235294152.673
927255AC1-221 E
Adder
3.2152941176470592.733
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.52724.527
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.91517.915
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.1033.103
LAGNLTFEXP_LAGN->PJM
CLTF
6.2356.235
NYPJM->LTFIMP_NY
CLTF
0.9860.986
LGEELTFEXP_LGEE->PJM
CLTF
0.950.95
WECLTFEXP_WEC->PJM
CLTF
0.5060.506
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1242.124
SIGELTFEXP_SIGE->PJM
CLTF
0.1890.189
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.7574.757
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.65881.658
CPLELTFEXP_CPLE->PJM
CLTF
9.989.98
TVALTFEXP_TVA->PJM
CLTF
4.8674.867
O66PJM->LTFIMP_O-066
CMTX_NF
13.52713.527

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.29 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3390.96
MW Contribution:137.93
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:138.84 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4471.41
MW Contribution:162.64
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316044AC1-158 C1
50/50
15.00715.007
933292AC2-141 E
Adder
12.22823529411764710.394
946262AF1-291 E
Adder
1.36823529411764721.163
3150651CHESTF6
Adder
17.73411764705882415.074
944602AF1-125 E
Adder
95.9941176470588381.595
3145506HICKORY
Adder
2.04352941176470631.737
934576AD1-082 E
Adder
4.1482352941176473.526
957871AF2-081 C
Adder
9.347.939
3152251N ANNA1
50/50
47.25147.251
316192AB2-158 C
50/50
1.8991.899
938552AE1-074 E
50/50
1.2191.219
926755AC1-161 E
Adder
12.22823529411764710.394
933291AC2-141 C
Adder
28.64705882352941324.35
925522AC1-027 E
Adder
1.1435294117647060.972
944631AF1-128 C
Adder
37.24352941176470531.657
957872AF2-081 E
Adder
4.0035294117647063.403
3145256KINGFORK
Adder
0.94941176470588240.807
3150921YORKTN3
Adder
111.6988235294117794.944
316160AE1-175 E
Adder
1.10705882352941170.941
941102AE2-104 E
Adder
4.9623529411764714.218
938562AE1-075 E
Adder
0.92941176470588240.79
936592AD2-074 E
Adder
8.1388235294117656.918
944011AF1-069 C
Adder
11.3364705882352949.636
941591AE2-156 C
Adder
16.84235294117647214.316
925332AB2-190 E
Adder
7.6305882352941186.486
944591AF1-124 C
Adder
42.74117647058823636.33
944601AF1-125 C
Adder
41.9329411764705935.643
927226AC1-216 E
Adder
7.2941176470588246.2
3150601CHESTF5
Adder
59.5223529411764750.594
936666AD2-085 E
Adder
5.2529411764705884.465
962962AG1-145 E
Adder
1.34235294117647071.141
963041AG1-153 C
Adder
4.8047058823529414.084
938771AE1-103 C
Adder
2.66470588235294152.265
3145413WATKINS
Adder
0.62117647058823530.528
966881AG1-559 C
Adder
2.14941176470588241.827
316170AC1-121 C
Adder
2.1788235294117651.852
3150831SPRUNCA
50/50
8.7958.795
3150841SPRUNCB
50/50
8.7958.795
939412AE1-173 E
50/50
55.04655.046
941032AE2-094 E
Adder
15.53882352941176513.208
941031AE2-094 C
Adder
34.69411764705882529.49
926662AC1-147 E
Adder
1.24588235294117641.059
916192Z1-068 E
Adder
1.76588235294117651.501
316076AC2-137 E
Adder
1.23411764705882351.049
957492AF2-043 E
Adder
1.32705882352941161.128
923852AB2-025 E
Adder
1.0352941176470590.88
966872AG1-558 E
Adder
1.10705882352941170.941
966871AG1-558 C
Adder
2.1964705882352941.867
923842AB2-024 E
Adder
1.62470588235294121.381
923862AB2-026 E
Adder
1.08941176470588250.926
316157AD2-030 E
Adder
1.07647058823529430.915
943612AF1-032 E
Adder
0.86235294117647050.733
3130536PAPERMILL
Adder
6.0070588235294125.106
939602AE1-190 E
Adder
1.29058823529411761.097
940492AE2-034 E
Adder
2.7635294117647062.349
936591AD2-074 C
Adder
4.9882352941176474.24
316164AC1-076_C
50/50
1.0121.012
940642AE2-051 E
50/50
10.40710.407
919153AA1-139 E2
Adder
3.823.247
943462AF1-017 E
Adder
2.061.751
942341AE2-247 C
Adder
1.39529411764705881.186
926412AC1-112 E
Adder
1.03294117647058830.878
958162AF2-110 E
Adder
2.02588235294117651.722
924516AB2-100 E1
Adder
2.50705882352941162.131
934502AD1-074 E
Adder
15.18117647058823612.904
926739AC1-158 E1
50/50
39.12239.122
316233AE1-074 C
50/50
2.4192.419
935162AD1-151 E
Adder
10.1647058823529428.64
938532AE1-072 E
Adder
8.5517647058823547.269
3146326AYDLETT TAP
Adder
1.26470588235294111.075
943461AF1-017 C
Adder
1.26235294117647071.073
316311AC2-079 C
Adder
5.3611764705882364.557
932596AC2-079 E
Adder
8.7482352941176477.436
917122Z2-027 E
Adder
1.24470588235294131.058
957832AF2-077 E
Adder
1.31411764705882361.117
927042AC1-191 E
Adder
4.3941176470588243.735
940551AE2-041 C
Adder
6.4717647058823545.501
920692AA2-178 E
Adder
3.6835294117647063.131
316240AF1-291 C
Adder
2.05294117647058851.745
944641AF1-129 C
Adder
97.3976470588235282.788
924814AB2-134 E
Adder
11.94705882352941210.155
919152AA1-139 E1
Adder
3.823.247
942342AE2-247 E
Adder
1.92705882352941171.638
926502AC1-121 E
Adder
1.02470588235294110.871
920042AA2-088 E OP
Adder
9.3552941176470597.952
934511AD1-075 C
Adder
3.1717647058823532.696
934521AD1-076 C
Adder
10.8305882352941179.206
939246AE1-155 E
Adder
7.7800000000000016.613
925022AB2-158 E
50/50
5.0315.031
944582AF1-123 E
Adder
97.5247058823529582.896
944592AF1-124 E
Adder
97.8776470588235383.196
935112AD1-144 E
Adder
0.88235294117647060.75
316349AD2-085 C
Adder
3.222.737
930122AB1-027 E
Adder
1.27058823529411781.08
316169AC1-164 GEN
Adder
37.0447058823529431.488
923832AB2-022 E
Adder
1.1517647058823530.979
963042AG1-153 E
Adder
7.2070588235294136.126
938772AE1-103 E
Adder
3.67882352941176463.127
916042Z1-036 E
Adder
26.0235294117647122.12
966882AG1-559 E
Adder
1.08235294117647070.92
939261AE1-157 C
Adder
12.43411764705882510.569
3150731STONECA
Adder
6.53294117647058855.553
932046AC2-012 E
Adder
12.32588235294117710.477
935161AD1-151 C
Adder
15.24705882352941312.96
938531AE1-072 C
Adder
16.40352941176470513.943
958161AF2-110 C
Adder
1.27411764705882361.083
3145393UNCAMP
Adder
5.5035294117647064.678
926486AC1-120 E
Adder
3.26823529411764732.778
3152261N ANNA2
50/50
47.2747.27
3150861SPRUNCD
50/50
0.1580.158
942002AE2-212 E
Adder
1.36705882352941171.162
940431AE2-027 C
Adder
12.27647058823529510.435
944581AF1-123 C
Adder
42.58941176470588636.201
941101AE2-104 C
Adder
3.1211764705882352.653
934392AD1-063 E
Adder
0.97058823529411760.825
943742AF1-042 E
Adder
4.2588235294117653.62
962862AG1-135 E
Adder
3.6188235294117653.076
966662AG1-536 E
Adder
6.4588235294117655.49
926740AC1-158 E2
50/50
39.12239.122
942001AE2-212 C
Adder
2.0505882352941181.743
939192AE1-149 E
Adder
6.7682352941176475.753
934065AD1-033 E
Adder
4.7094117647058834.003
939312AE1-162 E
Adder
1.3482352941176471.146
937226AE2-253 E
Adder
5.4670588235294124.647
958502AF2-144 E
Adder
1.07058823529411760.91
924517AB2-100 E2
Adder
2.50705882352941162.131
934501AD1-074 C
Adder
29.82235294117647225.349
943741AF1-042 C
Adder
2.61058823529411742.219
962861AG1-135 C
Adder
5.42823529411764754.614
961611AG1-000B C
Adder
15.01294117647058712.761
3138116ELKO L286
Adder
1.28705882352941181.094
940541AE2-040 C
Adder
2.562.176
940482AE2-033 E
Adder
9.6941176470588258.24
940481AE2-033 C
Adder
14.37882352941176512.222
927041AC1-191 C
Adder
8.827.497
3143316POE
Adder
1.28352941176470581.091
939191AE1-149 C
Adder
10.152941176470598.63
901082W1-029 E
Adder
29.42941176470588325.015
934146AD1-041 E
Adder
3.22588235294117662.742
957601AF2-054 C
Adder
1.91764705882352931.63
958261AF2-120 C
Adder
5.5870588235294124.749
3150851SPRUNCC
50/50
0.1580.158
939411AE1-173 C
50/50
82.56982.569
940432AE2-027 E
Adder
8.1835294117647066.956
934012AD1-025 E
Adder
9.442352941176478.026
913392Y1-086 E
Adder
2.041.734
939612AE1-191 E
Adder
5.162352941176474.388
957602AF2-054 E
Adder
1.27882352941176471.087
966661AG1-536 C
Adder
4.8058823529411764.085
958262AF2-120 E
Adder
3.7247058823529413.166
316045AC1-158 C2
50/50
15.00715.007
944012AF1-069 E
Adder
4.4035294117647063.743
925865AC1-065 E
Adder
15.09882352941176512.834
316254AC1-120 C
Adder
6.3435294117647065.392
939262AE1-157 E
Adder
6.7447058823529415.733
961951AG1-038 C
Adder
2.88470588235294122.452
961952AG1-038 E
Adder
3.98470588235294133.387
926004AC1-076_E
50/50
5.7785.778
940641AE2-051 C
50/50
15.61115.611
316084AB2-161 E
Adder
5.2058823529411774.425
926785AC1-164_E
Adder
16.64352941176470714.147
943471AF1-018 C
Adder
6.4717647058823545.501
3145946PLYMOUTH TP
Adder
0.287058823529411760.244
316303AF2-085
50/50
3.7313.731
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.2045.204
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.39910.399
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.3051.305
LAGNLTFEXP_LAGN->PJM
CLTF
4.1614.161
NYPJM->LTFIMP_NY
CLTF
1.9221.922
LGEELTFEXP_LGEE->PJM
CLTF
0.310.31
WECLTFEXP_WEC->PJM
CLTF
0.1350.135
G-007PJM->LTFIMP_G-007
CMTX_NF
3.9253.925
SIGELTFEXP_SIGE->PJM
CLTF
0.0740.074
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.9713.971
CBM South 2LTFEXP_CBM-S2->PJM
CBM
66.04366.043
CPLELTFEXP_CPLE->PJM
CLTF
8.348.34
TVALTFEXP_TVA->PJM
CLTF
3.2553.255
O66PJM->LTFIMP_O-066
CMTX_NF
25.06225.062
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
314214 to 314903 ckt 1
314286 to 314309 ckt 1
314287 to 314260 ckt 1
314218 to 314908 ckt 2
314466 to 314508 ckt 1
314309 to 314338 ckt 1
314196 to 314911 ckt 2
314236 to 314218 ckt 1
314260 to 314225 ckt 1
314902 to 314914 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314911 to 313483 ckt 1
314914 to 314322 ckt 1
314923 to 314924 ckt 1
314934 to 314916 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6FENT1-8FENTRES 230.0/500.0 kV Ckt 1 transformer
DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 3_SRT-A
OPAC112.51 %1130.82B1272.24410.0
GD1DVP
6FENT1-8FENTRES 230.0/500.0 kV Ckt 2 transformer
DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 1_SRT-A
OPAC112.51 %1130.82B1272.24410.0
GD1DVP
6FENT1-8FENTRES 230.0/500.0 kV Ckt 3 transformer
DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 1_SRT-A
OPAC112.51 %1130.82B1272.24410.0
GD1DVP
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
OPAC128.71 %1123.3B1445.8267.02
GD1DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S-1
OPAC111.78 %1058.16B1182.7663.16
GD1DVP
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
DVP_P1-2: LN 588_SRT-A
OPAC160.69 %678.68B1090.54236.24
GD1DVP
6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
OPAC121.31 %1123.3B1362.6567.02
GD1DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
OPAC103.49 %4070.2B4212.31158.45
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Base Case
OPAC104.09 %2442.12A2541.99212.48
GD1DVP
8FENTRES-6FENTRES 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 588_SRT-A
OPAC117.03 %1115.59B1305.6412.54
GD1DVP
8FENTRES-6FENTRES 500.0/230.0 kV Ckt 2 transformer
DVP_P1-2: LN 588_SRT-A
OPAC116.88 %1103.28B1289.51407.46
GD1DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
OPAC103.53 %4070.2B4213.9161.52
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Base Case
OPAC104.94 %3220.44A3379.54118.48

Details for 6FENT1-8FENTRES 230.0/500.0 kV Ckt 1 transformer l/o DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 3_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FENT1-8FENTRES 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 3_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.51 %
Rating:1130.82 MVA
Rating Type:B
MVA to Mitigate:1272.24
MW Contribution:410.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944591AF1-124 C
50/50
127.05127.05
944601AF1-125 C
50/50
124.65124.65
944602AF1-125 E
50/50
285.35285.35
944592AF1-124 E
50/50
290.95290.95
944582AF1-123 E
50/50
289.9289.9
944581AF1-123 C
50/50
126.6126.6

Details for 6FENT1-8FENTRES 230.0/500.0 kV Ckt 2 transformer l/o DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FENT1-8FENTRES 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 1_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.51 %
Rating:1130.82 MVA
Rating Type:B
MVA to Mitigate:1272.24
MW Contribution:410.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944591AF1-124 C
50/50
127.05127.05
944601AF1-125 C
50/50
124.65124.65
944602AF1-125 E
50/50
285.35285.35
944592AF1-124 E
50/50
290.95290.95
944582AF1-123 E
50/50
289.9289.9
944581AF1-123 C
50/50
126.6126.6

Details for 6FENT1-8FENTRES 230.0/500.0 kV Ckt 3 transformer l/o DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FENT1-8FENTRES 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 1_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.51 %
Rating:1130.82 MVA
Rating Type:B
MVA to Mitigate:1272.24
MW Contribution:410.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944591AF1-124 C
50/50
127.05127.05
944601AF1-125 C
50/50
124.65124.65
944602AF1-125 E
50/50
285.35285.35
944592AF1-124 E
50/50
290.95290.95
944582AF1-123 E
50/50
289.9289.9
944581AF1-123 C
50/50
126.6126.6

Details for 6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:128.71 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1445.82
MW Contribution:67.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
39.4152941176470633.503
3150431FOUR RIVERA
50/50
5.4515.451
925332AB2-190 E
Adder
4.577647058823533.891
927226AC1-216 E
Adder
4.25647058823529443.618
936666AD2-085 E
Adder
2.6964705882352942.292
962962AG1-145 E
Adder
0.78352941176470590.666
944591AF1-124 C
Adder
20.76941176470588217.654
944601AF1-125 C
Adder
20.37647058823529617.32
941591AE2-156 C
Adder
8.3011764705882357.056
3150461FOUR RIVERD
50/50
5.3725.372
3150651CHESTF6
Adder
11.3682352941176489.663
946262AF1-291 E
Adder
0.86352941176470590.734
934576AD1-082 E
Adder
2.2329411764705881.898
933292AC2-141 E
Adder
5.8788235294117654.997
944602AF1-125 E
Adder
46.6470588235294139.65
957871AF2-081 C
Adder
4.5541176470588243.871
3145506HICKORY
Adder
0.99647058823529410.847
943612AF1-032 E
Adder
0.42352941176470590.36
3130536PAPERMILL
Adder
3.4952941176470592.971
939602AE1-190 E
Adder
0.72705882352941180.618
944631AF1-128 C
Adder
24.66235294117647220.963
315052AA1-145 CT2
50/50
8.6788.678
3150471FOUR RIVERE
50/50
5.3725.372
934782AD1-105 E
Adder
2.55647058823529432.173
938552AE1-074 E
Adder
0.66235294117647060.563
316160AE1-175 E
Adder
0.64588235294117660.549
933291AC2-141 C
Adder
13.77294117647058911.707
926755AC1-161 E
Adder
5.8788235294117654.997
957872AF2-081 E
Adder
1.9517647058823531.659
925522AC1-027 E
Adder
0.56117647058823530.477
941102AE2-104 E
Adder
2.46470588235294132.095
3145256KINGFORK
Adder
0.480.408
3150921YORKTN3
Adder
60.82117647058823551.698
316076AC2-137 E
Adder
0.86352941176470590.734
966872AG1-558 E
50/50
0.9470.947
966871AG1-558 C
50/50
1.881.88
3150831SPRUNCA
Adder
5.5988235294117654.759
3150841SPRUNCB
Adder
5.5988235294117654.759
916192Z1-068 E
Adder
0.86588235294117640.736
926662AC1-147 E
Adder
0.61411764705882350.522
957492AF2-043 E
Adder
0.6517647058823530.554
923842AB2-024 E
Adder
0.94941176470588240.807
316157AD2-030 E
Adder
0.59529411764705890.506
316169AC1-164 GEN
Adder
24.58000000000000220.893
930122AB1-027 E
50/50
1.0381.038
316349AD2-085 C
Adder
1.65294117647058841.405
944592AF1-124 E
Adder
47.5623529411764740.428
944582AF1-123 E
Adder
47.3905882352941240.282
923832AB2-022 E
Adder
0.56235294117647060.478
935112AD1-144 E
Adder
0.44470588235294120.378
926412AC1-112 E
50/50
0.8440.844
3150441FOUR RIVERB
50/50
5.4515.451
943462AF1-017 E
Adder
1.05764705882352940.899
942341AE2-247 C
Adder
0.71647058823529410.609
919153AA1-139 E2
Adder
1.86235294117647051.583
958162AF2-110 E
Adder
1.00588235294117640.855
3150691DARBY 3
50/50
1.8151.815
927042AC1-191 E
50/50
3.7613.761
316233AE1-074 C
Adder
1.31411764705882361.117
935162AD1-151 E
Adder
6.0211764705882365.118
943461AF1-017 C
Adder
0.64823529411764710.551
316311AC2-079 C
Adder
2.74117647058823532.33
932596AC2-079 E
Adder
4.4717647058823533.801
917122Z2-027 E
Adder
0.60705882352941180.516
3146326AYDLETT TAP
Adder
0.61764705882352940.525
938532AE1-072 E
Adder
4.1705882352941183.545
940551AE2-041 C
Adder
3.70470588235294153.149
957832AF2-077 E
Adder
0.72117647058823530.613
316004AC1-112 C
50/50
0.2460.246
3142296MT RD221
50/50
0.1030.103
944641AF1-129 C
Adder
62.4352941176470653.07
316240AF1-291 C
Adder
1.29411764705882361.1
924814AB2-134 E
Adder
6.9717647058823535.926
942342AE2-247 E
Adder
0.98941176470588230.841
919152AA1-139 E1
Adder
1.86235294117647051.583
3150671DARBY 1
50/50
1.8071.807
942001AE2-212 C
Adder
1.22235294117647041.039
939192AE1-149 E
Adder
3.75882352941176473.195
937226AE2-253 E
Adder
2.66588235294117662.266
934065AD1-033 E
Adder
2.29764705882352961.953
939312AE1-162 E
Adder
0.7117647058823530.605
3150681DARBY 2
50/50
1.8091.809
942002AE2-212 E
Adder
0.81529411764705880.693
940431AE2-027 C
Adder
7.5435294117647066.412
944581AF1-123 C
Adder
20.69529411764706217.591
941101AE2-104 C
Adder
1.55058823529411781.318
934392AD1-063 E
Adder
0.55529411764705880.472
3150701DARBY 4
50/50
1.8171.817
3142366NRTHEST
50/50
0.1340.134
315051AA1-145 CT1
50/50
8.6838.683
3150481FOUR RIVERF
50/50
6.566.56
3150731STONECA
Adder
4.0823529411764713.47
935161AD1-151 C
Adder
9.0317647058823527.677
938531AE1-072 C
Adder
8.06.8
932046AC2-012 E
Adder
6.0788235294117655.167
958161AF2-110 C
Adder
0.63294117647058830.538
3138116ELKO L286
Adder
0.90117647058823540.766
927041AC1-191 C
50/50
7.557.55
961611AG1-000B C
Adder
8.3835294117647077.126
316312AB1-027 C
50/50
0.3940.394
3150451FOUR RIVERC
50/50
6.666.66
940432AE2-027 E
Adder
5.0282352941176474.274
934012AD1-025 E
Adder
5.5105882352941184.684
913392Y1-086 E
Adder
0.99529411764705880.846
939612AE1-191 E
Adder
2.9070588235294122.471
957602AF2-054 E
Adder
0.70705882352941170.601
926785AC1-164_E
Adder
11.0435294117647079.387
316084AB2-161 E
Adder
2.8023529411764712.382
943471AF1-018 C
Adder
3.70470588235294153.149
3143316POE
Adder
0.69882352941176470.594
939191AE1-149 C
Adder
5.63882352941176554.793
901082W1-029 E
Adder
14.38705882352941112.229
934146AD1-041 E
Adder
1.81647058823529431.544
957601AF2-054 C
Adder
1.060.901
925865AC1-065 E
Adder
8.6211764705882357.328
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.18619.186
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.3311.33
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.2052.205
LAGNLTFEXP_LAGN->PJM
CLTF
3.6223.622
NYPJM->LTFIMP_NY
CLTF
1.1351.135
LGEELTFEXP_LGEE->PJM
CLTF
0.7730.773
WECLTFEXP_WEC->PJM
CLTF
0.3950.395
G-007PJM->LTFIMP_G-007
CMTX_NF
2.5152.515
SIGELTFEXP_SIGE->PJM
CLTF
0.1430.143
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9991.999
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.12437.124
CPLELTFEXP_CPLE->PJM
CLTF
4.1874.187
TVALTFEXP_TVA->PJM
CLTF
2.9092.909
O66PJM->LTFIMP_O-066
CMTX_NF
15.98515.985

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.78 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1182.76
MW Contribution:63.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
39.4470588235294233.53
924032AB2-045 E
Adder
0.94941176470588240.807
961791AG1-021 C
Adder
0.97294117647058820.827
936261AD2-033 C
Adder
6.5000000000000015.525
925332AB2-190 E
Adder
4.5752941176470593.889
963041AG1-153 C
Adder
2.2623529411764711.923
960081AF2-299 C
Adder
0.8517647058823530.724
944011AF1-069 C
Adder
5.2235294117647074.44
926072AC1-086 E
Adder
4.2364705882352943.601
927226AC1-216 E
Adder
4.20352941176470553.573
3145413WATKINS
Adder
0.30941176470588240.263
936666AD2-085 E
Adder
2.6835294117647062.281
962962AG1-145 E
Adder
0.65529411764705890.557
938771AE1-103 C
Adder
1.3117647058823531.115
944591AF1-124 C
Adder
19.5717647058823516.636
944601AF1-125 C
Adder
19.2023529411764716.322
941591AE2-156 C
Adder
7.8529411764705886.675
3150861SPRUNCD
50/50
0.1690.169
316405AF2-144 C
50/50
0.4340.434
3150651CHESTF6
Adder
11.96588235294117610.171
946262AF1-291 E
Adder
0.91058823529411770.774
941011AE2-092 C
Adder
6.9470588235294125.905
961792AG1-021 E
Adder
0.82823529411764710.704
937482AD2-202 E
Adder
0.456470588235294130.388
934576AD1-082 E
Adder
2.2917647058823531.948
918492AA1-063AE OP
Adder
1.8117647058823531.54
933292AC2-141 E
Adder
2.30588235294117631.96
940492AE2-034 E
Adder
1.33882352941176451.138
944602AF1-125 E
Adder
43.9588235294117737.365
957871AF2-081 C
Adder
4.3329411764705883.683
3145506HICKORY
Adder
0.94470588235294130.803
943612AF1-032 E
Adder
0.405882352941176470.345
3130536PAPERMILL
Adder
3.0341176470588242.579
939602AE1-190 E
Adder
0.6517647058823530.554
944631AF1-128 C
Adder
24.6823529411764720.98
3150851SPRUNCC
50/50
0.1690.169
938552AE1-074 E
50/50
1.8811.881
938562AE1-075 E
50/50
1.5421.542
964242AG1-285 E
Adder
4.0211764705882363.418
924162AB2-060 E OP
Adder
2.0117647058823531.71
316160AE1-175 E
Adder
0.54117647058823540.46
933291AC2-141 C
Adder
12.51176470588235310.635
957872AF2-081 E
Adder
1.85647058823529431.578
925522AC1-027 E
Adder
0.53176470588235290.452
941102AE2-104 E
Adder
2.39764705882352922.038
3145256KINGFORK
Adder
0.455294117647058850.387
3150921YORKTN3
Adder
52.8152941176470644.893
316076AC2-137 E
Adder
0.73529411764705890.625
966872AG1-558 E
Adder
0.64352941176470590.547
966871AG1-558 C
Adder
1.27764705882352961.086
3150831SPRUNCA
50/50
9.4469.446
3150841SPRUNCB
50/50
9.4469.446
316258AE1-075 C
50/50
0.5110.511
923862AB2-026 E
50/50
1.8081.808
941012AE2-092 E
Adder
4.6305882352941183.936
958211AF2-115 C
Adder
1.21529411764705891.033
936262AD2-033 E
Adder
4.3329411764705883.683
923852AB2-025 E
Adder
0.54941176470588240.467
941032AE2-094 E
Adder
7.166.086
941031AE2-094 C
Adder
15.98588235294117513.588
939412AE1-173 E
Adder
24.89294117647058621.159
916192Z1-068 E
Adder
0.820.697
926662AC1-147 E
Adder
0.58117647058823530.494
957492AF2-043 E
Adder
0.62470588235294120.531
923842AB2-024 E
Adder
0.82235294117647050.699
316157AD2-030 E
Adder
0.53411764705882360.454
316169AC1-164 GEN
Adder
19.79647058823529816.827
930122AB1-027 E
Adder
0.69529411764705880.591
958212AF2-115 E
Adder
1.0352941176470590.88
964241AG1-285 C
Adder
6.0305882352941185.126
963042AG1-153 E
Adder
3.39411764705882352.885
946281AF1-292 C
Adder
0.70588235294117650.6
960082AF2-299 E
Adder
0.56823529411764710.483
926071AC1-086 C
Adder
9.3082352941176477.912
316349AD2-085 C
Adder
1.6447058823529411.398
938772AE1-103 E
Adder
1.8117647058823531.54
916042Z1-036 E
Adder
12.43647058823529310.571
944592AF1-124 E
Adder
44.82117647058823538.098
944582AF1-123 E
Adder
44.6637.961
923832AB2-022 E
Adder
0.53882352941176470.458
935112AD1-144 E
Adder
0.42235294117647060.359
926412AC1-112 E
Adder
0.56470588235294120.48
959312AF2-222 E
Adder
5.71764705882352954.86
3147223TWITTYS
Adder
0.48235294117647060.41
924022AB2-043 E O1
Adder
2.4235294117647062.06
924516AB2-100 E1
Adder
1.32117647058823541.123
966621AG1-532 C
Adder
0.63882352941176480.543
940642AE2-051 E
Adder
4.67764705882352953.976
943462AF1-017 E
Adder
1.0517647058823530.894
942341AE2-247 C
Adder
0.71294117647058820.606
919153AA1-139 E2
Adder
1.7717647058823531.506
958162AF2-110 E
Adder
0.97882352941176460.832
927042AC1-191 E
Adder
2.55411764705882362.171
316233AE1-074 C
50/50
3.7333.733
3147133PAMPLIN
Adder
0.54941176470588240.467
966622AG1-532 E
Adder
0.42588235294117650.362
935162AD1-151 E
Adder
5.9847058823529415.087
943461AF1-017 C
Adder
0.64470588235294120.548
316311AC2-079 C
Adder
2.71999999999999982.312
932596AC2-079 E
Adder
4.4376470588235293.772
920692AA2-178 E
Adder
1.78588235294117651.518
917122Z2-027 E
Adder
0.58470588235294120.497
3146326AYDLETT TAP
Adder
0.58823529411764710.5
938532AE1-072 E
Adder
3.9729411764705883.377
940551AE2-041 C
Adder
3.25058823529411762.763
957832AF2-077 E
Adder
0.63529411764705890.54
944641AF1-129 C
Adder
65.7211764705882355.863
316240AF1-291 C
Adder
1.36588235294117651.161
959311AF2-222 C
Adder
8.5341176470588237.254
3145723EMPORIA
Adder
0.196470588235294150.167
923573AB1-173 E OP
Adder
1.47764705882352951.256
919692AA2-053 E OP
Adder
1.86823529411764721.588
924814AB2-134 E
Adder
6.8847058823529425.852
920042AA2-088 E OP
Adder
4.724.012
942342AE2-247 E
Adder
0.98470588235294120.837
919152AA1-139 E1
Adder
1.7717647058823531.506
958502AF2-144 E
50/50
1.7771.777
938822AE1-108 E
Adder
4.0211764705882363.418
942001AE2-212 C
Adder
1.3035294117647061.108
942461AE2-259 C
Adder
5.83647058823529454.961
946301AF1-294 C
Adder
1.99882352941176491.699
939192AE1-149 E
Adder
3.93176470588235333.342
934621AD1-088 C
Adder
4.3294117647058833.68
957482AF2-042 E
Adder
15.4776470588235313.156
924517AB2-100 E2
Adder
1.32117647058823541.123
937226AE2-253 E
Adder
2.53176470588235342.152
934065AD1-033 E
Adder
2.1752941176470591.849
939312AE1-162 E
Adder
0.67999999999999990.578
942002AE2-212 E
Adder
0.86941176470588230.739
946302AF1-294 E
Adder
1.69294117647058841.439
940431AE2-027 C
Adder
7.9682352941176476.773
924322AB2-079 E O1
Adder
0.62117647058823530.528
957481AF2-042 C
Adder
23.21647058823529619.734
316088AB2-174 E
Adder
2.94705882352941152.505
923994AB2-040_E
Adder
2.76941176470588252.354
944581AF1-123 C
Adder
19.50352941176470616.578
941101AE2-104 C
Adder
1.50823529411764711.282
934392AD1-063 E
Adder
0.487058823529411770.414
3150731STONECA
Adder
4.1494117647058823.527
924302AB2-077 E O1
Adder
0.62117647058823530.528
935161AD1-151 C
Adder
8.9764705882352947.63
900672V4-068 E
Adder
0.157647058823529420.134
3145393UNCAMP
Adder
2.72117647058823582.313
938531AE1-072 C
Adder
7.6223529411764716.479
932046AC2-012 E
Adder
5.7529411764705884.89
958161AF2-110 C
Adder
0.61529411764705890.523
3138116ELKO L286
Adder
0.76588235294117660.651
927041AC1-191 C
Adder
5.1282352941176474.359
938821AE1-108 C
Adder
8.4270588235294127.163
925612AC1-036 E
Adder
0.435294117647058830.37
924312AB2-078 E O1
Adder
0.62117647058823530.528
940541AE2-040 C
Adder
1.35764705882352941.154
940481AE2-033 C
Adder
7.6223529411764716.479
940482AE2-033 E
Adder
5.13882352941176554.368
923263AB1-132 E OP
Adder
2.70941176470588242.303
961611AG1-000B C
Adder
8.1152941176470596.898
933502AC2-165 E
50/50
10.19910.199
940432AE2-027 E
Adder
5.3129411764705894.516
3137643SOCKMAN
Adder
0.317647058823529450.27
939411AE1-173 C
Adder
37.3388235294117631.738
934012AD1-025 E
Adder
5.44117647058823554.625
913392Y1-086 E
Adder
0.9552941176470590.812
939612AE1-191 E
Adder
2.6082352941176472.217
957602AF2-054 E
Adder
0.63529411764705890.54
926785AC1-164_E
Adder
8.8941176470588247.56
316336AC2-165 C
50/50
13.55213.552
934622AD1-088 E
Adder
2.08470588235294141.772
934612AD1-087 E
Adder
1.55882352941176471.325
316084AB2-161 E
Adder
2.8764705882352942.445
940641AE2-051 C
Adder
7.0152941176470595.963
943471AF1-018 C
Adder
3.25058823529411762.763
3143096IRON208
50/50
0.330.33
316313AB2-026 C
50/50
0.5570.557
3143316POE
Adder
0.75647058823529410.643
942462AE2-259 E
Adder
3.8917647058823533.308
939191AE1-149 C
Adder
5.8976470588235295.013
901082W1-029 E
Adder
13.8976470588235311.813
934146AD1-041 E
Adder
1.63058823529411771.386
957601AF2-054 C
Adder
0.95294117647058830.81
3138533PONTONDP
Adder
0.360.306
946282AF1-292 E
Adder
0.47058823529411770.4
944012AF1-069 E
Adder
2.02941176470588271.725
925865AC1-065 E
Adder
7.73058823529411756.571
316303AF2-085
50/50
7.0277.027
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.08118.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.29711.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1322.132
LAGNLTFEXP_LAGN->PJM
CLTF
3.6953.695
NYPJM->LTFIMP_NY
CLTF
0.9630.963
LGEELTFEXP_LGEE->PJM
CLTF
0.7270.727
WECLTFEXP_WEC->PJM
CLTF
0.3730.373
G-007PJM->LTFIMP_G-007
CMTX_NF
2.112.11
SIGELTFEXP_SIGE->PJM
CLTF
0.1370.137
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.2422.242
CBM South 2LTFEXP_CBM-S2->PJM
CBM
40.62940.629
CPLELTFEXP_CPLE->PJM
CLTF
4.6984.698
TVALTFEXP_TVA->PJM
CLTF
2.952.95
O66PJM->LTFIMP_O-066
CMTX_NF
13.41813.418

Details for 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 588_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:160.69 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1090.54
MW Contribution:236.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944591AF1-124 C
50/50
73.20773.207
944601AF1-125 C
50/50
71.82471.824
934522AD1-076 E
Adder
2.3517647058823531.999
940492AE2-034 E
Adder
1.45294117647058841.235
944602AF1-125 E
50/50
164.42164.42
957871AF2-081 C
50/50
13.97813.978
3145506HICKORY
50/50
3.3893.389
957872AF2-081 E
50/50
5.9915.991
316018AA1-139 ULT2
50/50
1.5081.508
916042Z1-036 E
50/50
17.00117.001
944592AF1-124 E
50/50
167.647167.647
944582AF1-123 E
50/50
167.042167.042
923832AB2-022 E
50/50
1.3181.318
934502AD1-074 E
Adder
6.46823529411764755.498
934512AD1-075 E
Adder
1.61647058823529431.374
316320Y1-086 C
50/50
0.2330.233
919153AA1-139 E2
50/50
5.7165.716
316388AE2-253 GEN
50/50
2.8572.857
920692AA2-178 E
Adder
1.93647058823529421.646
917122Z2-027 E
50/50
1.2581.258
3146326AYDLETT TAP
50/50
1.7791.779
938532AE1-072 E
50/50
12.23212.232
3156056W1-029WIND
50/50
0.4810.481
934521AD1-076 C
Adder
4.6141176470588243.922
934511AD1-075 C
Adder
3.17647058823529442.7
316321Z2-027 C
50/50
0.340.34
919152AA1-139 E1
50/50
5.7165.716
934501AD1-074 C
Adder
12.70470588235294210.799
3156116Z1-036WIND
50/50
0.390.39
937226AE2-253 E
50/50
8.5248.524
934065AD1-033 E
50/50
10.2610.26
944581AF1-123 C
50/50
72.94872.948
316185AD1-033 C
50/50
2.5062.506
933981AD1-022 C
Adder
2.84588235294117682.419
938531AE1-072 C
50/50
23.46523.465
913392Y1-086 E
50/50
2.3352.335
933982AD1-022 E
Adder
1.54941176470588231.317
3145946PLYMOUTH TP
Adder
0.127058823529411780.108
313526AB2-022 C
50/50
0.3990.399
316017AA1-139 ULT1
50/50
1.5081.508
901082W1-029 E
50/50
19.78819.788
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.0861.086
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.7620.762
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.1350.135
LAGNLTFEXP_LAGN->PJM
CLTF
0.2620.262
NYPJM->LTFIMP_NY
CLTF
0.0440.044
LGEELTFEXP_LGEE->PJM
CLTF
0.0420.042
WECLTFEXP_WEC->PJM
CLTF
0.0220.022
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0960.096
SIGELTFEXP_SIGE->PJM
CLTF
0.0080.008
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.2290.229
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.53.5
CPLELTFEXP_CPLE->PJM
CLTF
0.480.48
TVALTFEXP_TVA->PJM
CLTF
0.2050.205
O66PJM->LTFIMP_O-066
CMTX_NF
0.6090.609

Details for 6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:121.31 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1362.65
MW Contribution:67.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
39.4152941176470633.503
3150431FOUR RIVERA
50/50
5.4515.451
966881AG1-559 C
50/50
7.7447.744
925332AB2-190 E
Adder
4.577647058823533.891
927226AC1-216 E
Adder
4.25647058823529443.618
936666AD2-085 E
Adder
2.6964705882352942.292
962962AG1-145 E
Adder
0.78352941176470590.666
944591AF1-124 C
Adder
20.76941176470588217.654
944601AF1-125 C
Adder
20.37647058823529617.32
941591AE2-156 C
Adder
8.3011764705882357.056
3150461FOUR RIVERD
50/50
5.3725.372
3150651CHESTF6
Adder
11.3682352941176489.663
946262AF1-291 E
Adder
0.86352941176470590.734
934576AD1-082 E
Adder
2.2329411764705881.898
933292AC2-141 E
Adder
5.8788235294117654.997
944602AF1-125 E
Adder
46.6470588235294139.65
957871AF2-081 C
Adder
4.5541176470588243.871
3145506HICKORY
Adder
0.99647058823529410.847
943612AF1-032 E
Adder
0.42352941176470590.36
3130536PAPERMILL
Adder
3.4952941176470592.971
939602AE1-190 E
Adder
0.72705882352941180.618
944631AF1-128 C
Adder
24.66235294117647220.963
315052AA1-145 CT2
50/50
8.6788.678
3150471FOUR RIVERE
50/50
5.3725.372
934782AD1-105 E
Adder
2.55647058823529432.173
938552AE1-074 E
Adder
0.66235294117647060.563
316160AE1-175 E
Adder
0.64588235294117660.549
933291AC2-141 C
Adder
13.77294117647058911.707
926755AC1-161 E
Adder
5.8788235294117654.997
957872AF2-081 E
Adder
1.9517647058823531.659
925522AC1-027 E
Adder
0.56117647058823530.477
941102AE2-104 E
Adder
2.46470588235294132.095
3145256KINGFORK
Adder
0.480.408
3150921YORKTN3
Adder
60.82117647058823551.698
316076AC2-137 E
Adder
0.86352941176470590.734
966872AG1-558 E
50/50
0.9470.947
966871AG1-558 C
50/50
1.881.88
3150831SPRUNCA
Adder
5.5988235294117654.759
3150841SPRUNCB
Adder
5.5988235294117654.759
916192Z1-068 E
Adder
0.86588235294117640.736
926662AC1-147 E
Adder
0.61411764705882350.522
957492AF2-043 E
Adder
0.6517647058823530.554
923842AB2-024 E
Adder
0.94941176470588240.807
316157AD2-030 E
Adder
0.59529411764705890.506
316169AC1-164 GEN
Adder
24.58000000000000220.893
930122AB1-027 E
50/50
1.0381.038
966882AG1-559 E
50/50
3.9013.901
316349AD2-085 C
Adder
1.65294117647058841.405
944592AF1-124 E
Adder
47.5623529411764740.428
944582AF1-123 E
Adder
47.3905882352941240.282
935112AD1-144 E
Adder
0.44470588235294120.378
926412AC1-112 E
50/50
0.8440.844
3150441FOUR RIVERB
50/50
5.4515.451
943462AF1-017 E
Adder
1.05764705882352940.899
942341AE2-247 C
Adder
0.71647058823529410.609
919153AA1-139 E2
Adder
1.86235294117647051.583
958162AF2-110 E
Adder
1.00588235294117640.855
3150691DARBY 3
50/50
1.8151.815
927042AC1-191 E
50/50
3.7613.761
316233AE1-074 C
Adder
1.31411764705882361.117
935162AD1-151 E
Adder
6.0211764705882365.118
943461AF1-017 C
Adder
0.64823529411764710.551
316311AC2-079 C
Adder
2.74117647058823532.33
932596AC2-079 E
Adder
4.4717647058823533.801
3146326AYDLETT TAP
Adder
0.61764705882352940.525
938532AE1-072 E
Adder
4.1705882352941183.545
940551AE2-041 C
Adder
3.70470588235294153.149
957832AF2-077 E
Adder
0.72117647058823530.613
316004AC1-112 C
50/50
0.2460.246
3142296MT RD221
50/50
0.1030.103
944641AF1-129 C
Adder
62.4352941176470653.07
316240AF1-291 C
Adder
1.29411764705882361.1
924814AB2-134 E
Adder
6.9717647058823535.926
942342AE2-247 E
Adder
0.98941176470588230.841
919152AA1-139 E1
Adder
1.86235294117647051.583
3150671DARBY 1
50/50
1.8071.807
942001AE2-212 C
Adder
1.22235294117647041.039
939192AE1-149 E
Adder
3.75882352941176473.195
937226AE2-253 E
Adder
2.66588235294117662.266
934065AD1-033 E
Adder
2.29764705882352961.953
939312AE1-162 E
Adder
0.7117647058823530.605
3150681DARBY 2
50/50
1.8091.809
942002AE2-212 E
Adder
0.81529411764705880.693
940431AE2-027 C
Adder
7.5435294117647066.412
944581AF1-123 C
Adder
20.69529411764706217.591
941101AE2-104 C
Adder
1.55058823529411781.318
934392AD1-063 E
Adder
0.55529411764705880.472
3150701DARBY 4
50/50
1.8171.817
3142366NRTHEST
50/50
0.1340.134
315051AA1-145 CT1
50/50
8.6838.683
3150481FOUR RIVERF
50/50
6.566.56
3150731STONECA
Adder
4.0823529411764713.47
935161AD1-151 C
Adder
9.0317647058823527.677
938531AE1-072 C
Adder
8.06.8
932046AC2-012 E
Adder
6.0788235294117655.167
958161AF2-110 C
Adder
0.63294117647058830.538
3138116ELKO L286
Adder
0.90117647058823540.766
927041AC1-191 C
50/50
7.557.55
961611AG1-000B C
Adder
8.3835294117647077.126
316312AB1-027 C
50/50
0.3940.394
3150451FOUR RIVERC
50/50
6.666.66
940432AE2-027 E
Adder
5.0282352941176474.274
934012AD1-025 E
Adder
5.5105882352941184.684
939612AE1-191 E
Adder
2.9070588235294122.471
957602AF2-054 E
Adder
0.70705882352941170.601
926785AC1-164_E
Adder
11.0435294117647079.387
316084AB2-161 E
Adder
2.8023529411764712.382
943471AF1-018 C
Adder
3.70470588235294153.149
3143316POE
Adder
0.69882352941176470.594
939191AE1-149 C
Adder
5.63882352941176554.793
934146AD1-041 E
Adder
1.81647058823529431.544
957601AF2-054 C
Adder
1.060.901
925865AC1-065 E
Adder
8.6211764705882357.328
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.18619.186
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.3311.33
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.2052.205
LAGNLTFEXP_LAGN->PJM
CLTF
3.6223.622
NYPJM->LTFIMP_NY
CLTF
1.1351.135
LGEELTFEXP_LGEE->PJM
CLTF
0.7730.773
WECLTFEXP_WEC->PJM
CLTF
0.3950.395
G-007PJM->LTFIMP_G-007
CMTX_NF
2.5152.515
SIGELTFEXP_SIGE->PJM
CLTF
0.1430.143
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9991.999
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.12437.124
CPLELTFEXP_CPLE->PJM
CLTF
4.1874.187
TVALTFEXP_TVA->PJM
CLTF
2.9092.909
O66PJM->LTFIMP_O-066
CMTX_NF
15.98515.985

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.49 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4212.31
MW Contribution:158.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
964212AG1-282 E
Adder
1.4117647058823531.2
3150601CHESTF5
Adder
70.2058823529411759.675
3150431FOUR RIVERA
50/50
3.5273.527
966881AG1-559 C
50/50
2.7662.766
925332AB2-190 E
Adder
8.8811764705882377.549
963041AG1-153 C
Adder
5.3364705882352944.536
944011AF1-069 C
Adder
12.49058823529411910.617
927226AC1-216 E
Adder
8.4752941176470587.204
3145413WATKINS
Adder
0.71529411764705890.608
936666AD2-085 E
Adder
6.03294117647058855.128
962962AG1-145 E
Adder
1.5835294117647061.346
938771AE1-103 C
Adder
3.06470588235294142.605
944591AF1-124 C
Adder
49.141.735
944601AF1-125 C
Adder
48.17294117647059440.947
941591AE2-156 C
Adder
19.3216.422
936591AD2-074 C
Adder
5.9258823529411765.037
3150461FOUR RIVERD
50/50
3.4763.476
3150651CHESTF6
Adder
20.5870588235294117.499
946262AF1-291 E
Adder
1.58588235294117651.348
934576AD1-082 E
Adder
4.7623529411764714.048
933292AC2-141 E
Adder
14.03647058823529311.931
940492AE2-034 E
Adder
3.1905882352941182.712
944602AF1-125 E
Adder
110.2776470588235393.736
957871AF2-081 C
Adder
10.6988235294117659.094
3145506HICKORY
Adder
2.34000000000000031.989
943612AF1-032 E
Adder
0.99058823529411770.842
3130536PAPERMILL
Adder
7.1317647058823546.062
939602AE1-190 E
Adder
1.5282352941176471.299
936592AD2-074 E
Adder
9.6694117647058818.219
944631AF1-128 C
Adder
43.9294117647058937.34
315052AA1-145 CT2
50/50
5.6165.616
3150471FOUR RIVERE
50/50
3.4763.476
938552AE1-074 E
Adder
1.35529411764705881.152
3150411LDYSMT5
50/50
5.4185.418
316160AE1-175 E
Adder
1.30705882352941181.111
933291AC2-141 C
Adder
32.8811764705882427.949
926755AC1-161 E
Adder
14.03647058823529311.931
957872AF2-081 E
Adder
4.5847058823529413.897
925522AC1-027 E
Adder
1.31058823529411781.114
941102AE2-104 E
Adder
5.6988235294117654.844
3145256KINGFORK
Adder
1.09411764705882360.93
3150921YORKTN3
Adder
130.66235294117647111.063
964211AG1-282 C
Adder
2.11764705882352941.8
316076AC2-137 E
Adder
1.47529411764705891.254
966872AG1-558 E
Adder
1.341.139
966871AG1-558 C
Adder
2.662.261
3150831SPRUNCA
Adder
10.0964705882352958.582
3150841SPRUNCB
Adder
10.0964705882352958.582
3150391LDYSMT3
50/50
5.3915.391
316045AC1-158 C2
50/50
7.3677.367
316044AC1-158 C1
50/50
7.3677.367
923852AB2-025 E
Adder
1.16941176470588240.994
941032AE2-094 E
Adder
17.12117647058823514.553
941031AE2-094 C
Adder
38.2270588235294232.493
939412AE1-173 E
Adder
61.3576470588235452.154
916192Z1-068 E
Adder
2.0235294117647061.72
926662AC1-147 E
Adder
1.42941176470588241.215
957492AF2-043 E
Adder
1.52352941176470581.295
923842AB2-024 E
Adder
1.92941176470588241.64
316157AD2-030 E
Adder
1.27411764705882361.083
963612AG1-210 E
Adder
1.04352941176470580.887
926412AC1-112 E
50/50
1.2521.252
3150441FOUR RIVERB
50/50
3.5273.527
3152261N ANNA2
50/50
40.26240.262
940642AE2-051 E
Adder
11.4905882352941179.767
934502AD1-074 E
Adder
8.9670588235294127.622
943462AF1-017 E
Adder
2.36588235294117682.011
942341AE2-247 C
Adder
1.60235294117647081.362
919153AA1-139 E2
Adder
4.3752941176470593.719
958162AF2-110 E
Adder
2.3270588235294121.978
927042AC1-191 E
Adder
5.3188235294117654.521
316233AE1-074 C
Adder
2.69176470588235262.288
3150381LDYSMT2
50/50
5.2525.252
926739AC1-158 E1
50/50
19.2719.27
935162AD1-151 E
Adder
11.82117647058823610.048
943461AF1-017 C
Adder
1.44941176470588241.232
316311AC2-079 C
Adder
6.1564705882352945.233
932596AC2-079 E
Adder
10.0458823529411768.539
920692AA2-178 E
Adder
4.2541176470588233.616
917122Z2-027 E
Adder
1.4282352941176471.214
3146326AYDLETT TAP
Adder
1.44941176470588241.232
938532AE1-072 E
Adder
9.7976470588235298.328
940551AE2-041 C
Adder
7.67764705882352956.526
957832AF2-077 E
Adder
1.54588235294117651.314
939246AE1-155 E
Adder
9.2517647058823537.864
316004AC1-112 C
50/50
0.3640.364
3142296MT RD221
50/50
0.1350.135
944641AF1-129 C
Adder
113.0705882352941296.11
316240AF1-291 C
Adder
2.37882352941176432.022
924814AB2-134 E
Adder
13.88352941176470711.801
920042AA2-088 E OP
Adder
10.782352941176479.165
942342AE2-247 E
Adder
2.2129411764705881.881
919152AA1-139 E1
Adder
4.3752941176470593.719
943741AF1-042 C
Adder
3.10117647058823562.636
962861AG1-135 C
Adder
6.4529411764705885.485
3141813NORNECK
Adder
0.92588235294117650.787
3152251N ANNA1
50/50
40.24640.246
942001AE2-212 C
Adder
2.35882352941176482.005
939192AE1-149 E
Adder
7.7682352941176476.603
316169AC1-164 GEN
Adder
44.39529411764705537.736
930122AB1-027 E
50/50
1.5391.539
966882AG1-559 E
50/50
1.3931.393
939261AE1-157 C
50/50
16.15516.155
963042AG1-153 E
Adder
8.0047058823529426.804
316349AD2-085 C
Adder
3.6976470588235293.143
938772AE1-103 E
Adder
4.2317647058823533.597
916042Z1-036 E
Adder
29.97176470588235425.476
944592AF1-124 E
Adder
112.4411764705882595.575
944582AF1-123 E
Adder
112.0352941176470795.23
923832AB2-022 E
Adder
1.32117647058823541.123
935112AD1-144 E
Adder
1.0152941176470590.863
943742AF1-042 E
Adder
5.05882352941176454.3
962862AG1-135 E
Adder
4.3023529411764713.657
966662AG1-536 E
Adder
7.686.528
3150401LDYSMT4
50/50
5.4015.401
942002AE2-212 E
Adder
1.57294117647058831.337
940431AE2-027 C
Adder
14.21058823529411812.079
944581AF1-123 C
Adder
48.9258823529411841.587
941101AE2-104 C
Adder
3.58470588235294143.047
3150701DARBY 4
50/50
2.8532.853
3142366NRTHEST
50/50
0.2060.206
315051AA1-145 CT1
50/50
5.6195.619
3150481FOUR RIVERF
50/50
4.2454.245
3150731STONECA
Adder
7.6200000000000016.477
935161AD1-151 C
Adder
17.7317647058823515.072
3145393UNCAMP
Adder
6.3329411764705885.383
938531AE1-072 C
Adder
18.79411764705882215.975
932046AC2-012 E
Adder
14.1412.019
958161AF2-110 C
Adder
1.46235294117647091.243
934392AD1-063 E
Adder
1.1517647058823530.979
963611AG1-210 C
Adder
0.69529411764705880.591
3138116ELKO L286
Adder
1.53882352941176471.308
927041AC1-191 C
Adder
10.6788235294117659.077
3150371LDYSMT1
50/50
5.1855.185
926740AC1-158 E2
50/50
19.2719.27
940541AE2-040 C
Adder
2.89058823529411772.457
940481AE2-033 C
Adder
16.25647058823529513.818
940482AE2-033 E
Adder
10.969.316
961611AG1-000B C
Adder
17.4070588235294114.796
934501AD1-074 C
Adder
34.51411764705882529.337
937226AE2-253 E
Adder
6.265.321
934065AD1-033 E
Adder
5.3894117647058834.581
939312AE1-162 E
Adder
1.5552941176470591.322
958261AF2-120 C
Adder
6.6447058823529415.648
3143316POE
Adder
1.4635294117647061.244
939191AE1-149 C
Adder
11.6529411764705889.905
901082W1-029 E
Adder
33.8176470588235328.745
934146AD1-041 E
Adder
3.8211764705882363.248
957601AF2-054 C
Adder
2.2717647058823531.931
958262AF2-120 E
Adder
4.4294117647058833.765
966661AG1-536 C
Adder
5.7152941176470584.858
316078AC2-138 E
Adder
0.97411764705882350.828
316312AB1-027 C
50/50
0.5850.585
3150451FOUR RIVERC
50/50
4.314.31
940432AE2-027 E
Adder
9.4729411764705888.052
939411AE1-173 C
Adder
92.0364705882352978.231
934012AD1-025 E
Adder
10.9729411764705889.327
913392Y1-086 E
Adder
2.34117647058823541.99
939612AE1-191 E
Adder
6.1141176470588245.197
957602AF2-054 E
Adder
1.51411764705882361.287
961952AG1-038 E
Adder
4.7329411764705884.023
961951AG1-038 C
Adder
3.42705882352941152.913
939262AE1-157 E
50/50
8.7638.763
944012AF1-069 E
Adder
4.8517647058823534.124
925865AC1-065 E
Adder
17.8870588235294115.204
926785AC1-164_E
Adder
19.94588235294117616.954
926004AC1-076_E
Adder
4.277647058823533.636
316084AB2-161 E
Adder
5.9764705882352945.08
940641AE2-051 C
Adder
17.23529411764705814.65
3145946PLYMOUTH TP
Adder
0.33176470588235290.282
943471AF1-018 C
Adder
7.67764705882352956.526
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.06830.068
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.37922.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.9143.914
LAGNLTFEXP_LAGN->PJM
CLTF
7.6467.646
NYPJM->LTFIMP_NY
CLTF
2.722.72
LGEELTFEXP_LGEE->PJM
CLTF
1.3021.302
WECLTFEXP_WEC->PJM
CLTF
0.640.64
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7495.749
SIGELTFEXP_SIGE->PJM
CLTF
0.2490.249
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.0355.035
CBM South 2LTFEXP_CBM-S2->PJM
CBM
90.48890.488
CPLELTFEXP_CPLE->PJM
CLTF
10.55810.558
TVALTFEXP_TVA->PJM
CLTF
6.1246.124
O66PJM->LTFIMP_O-066
CMTX_NF
36.64136.641

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.09 %
Rating:2442.12 MVA
Rating Type:A
MVA to Mitigate:2541.99
MW Contribution:212.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
964212AG1-282 E
Adder
1.6847058823529411.432
3150601CHESTF5
Adder
66.756.695
925332AB2-190 E
Adder
8.8411764705882367.515
963041AG1-153 C
Adder
4.884.148
960081AF2-299 C
Adder
1.69647058823529421.442
944011AF1-069 C
Adder
11.532941176470599.803
926072AC1-086 E
Adder
9.1682352941176477.793
927226AC1-216 E
Adder
8.9599999999999997.616
3145413WATKINS
Adder
0.82235294117647050.699
936666AD2-085 E
Adder
6.9317647058823545.892
962962AG1-145 E
50/50
2.2212.221
938771AE1-103 C
Adder
3.62470588235294143.081
944591AF1-124 C
50/50
65.84465.844
944601AF1-125 C
50/50
64.664.6
3151101ELIZAR3
50/50
4.6014.601
941591AE2-156 C
50/50
25.46125.461
936591AD2-074 C
Adder
7.2670588235294116.177
316274AC1-208 C
Adder
8.6647058823529427.365
934576AD1-082 E
Adder
4.80941176470588254.088
918492AA1-063AE OP
Adder
4.17764705882352953.551
917332KELFORD E
Adder
1.74000000000000021.479
925122AB2-169 E
Adder
6.3976470588235295.438
943172AE2-346 E
Adder
0.66705882352941170.567
934522AD1-076 E
Adder
7.48117647058823556.359
933292AC2-141 E
50/50
20.21420.214
940492AE2-034 E
Adder
3.8317647058823533.257
944602AF1-125 E
50/50
147.882147.882
957871AF2-081 C
50/50
14.02714.027
3145506HICKORY
50/50
3.0893.089
943612AF1-032 E
Adder
1.2764705882352941.085
3130536PAPERMILL
50/50
9.1469.146
939602AE1-190 E
Adder
1.9247058823529411.636
936592AD2-074 E
Adder
11.85764705882353110.079
944631AF1-128 C
Adder
41.73529411764706535.475
926214AC1-099 E
Adder
1.18705882352941171.009
932632AC2-084 E
Adder
3.17764705882352952.701
316160AE1-175 E
50/50
1.8321.832
933291AC2-141 C
50/50
47.35447.354
926755AC1-161 E
50/50
20.21420.214
957872AF2-081 E
50/50
6.0126.012
316018AA1-139 ULT2
50/50
1.5131.513
925522AC1-027 E
50/50
1.7291.729
941102AE2-104 E
Adder
7.0717647058823536.011
3145256KINGFORK
50/50
1.4051.405
3150921YORKTN3
50/50
185.501185.501
964211AG1-282 C
Adder
2.5270588235294122.148
316076AC2-137 E
Adder
1.53647058823529431.306
923852AB2-025 E
Adder
1.040.884
941032AE2-094 E
Adder
15.80941176470588313.438
941031AE2-094 C
Adder
35.2988235294117730.004
934321AD1-056 C
Adder
2.15411764705882371.831
927022AC1-189 E
Adder
4.1023529411764713.487
939412AE1-173 E
Adder
67.656470588235357.508
961942AG1-037 E
Adder
0.370588235294117660.315
961941AG1-037 C
Adder
0.55529411764705880.472
916192Z1-068 E
50/50
2.672.67
3151081ELIZAR1
50/50
4.5444.544
926662AC1-147 E
50/50
1.8821.882
957492AF2-043 E
Adder
1.9635294117647061.669
923842AB2-024 E
50/50
2.4762.476
316157AD2-030 E
Adder
1.6270588235294121.383
316169AC1-164 GEN
50/50
57.50657.506
963042AG1-153 E
Adder
7.3188235294117656.221
946281AF1-292 C
Adder
1.40470588235294121.194
960082AF2-299 E
Adder
1.13058823529411770.961
926071AC1-086 C
Adder
20.14470588235294517.123
927021AC1-189 C
Adder
8.235294117647067
316349AD2-085 C
Adder
4.2482352941176483.611
938772AE1-103 E
Adder
5.00588235294117644.255
916042Z1-036 E
Adder
37.13529411764706431.565
944592AF1-124 E
50/50
150.785150.785
944582AF1-123 E
50/50
150.24150.24
923832AB2-022 E
Adder
1.7070588235294121.451
963612AG1-210 E
Adder
1.23058823529411781.046
924516AB2-100 E1
Adder
2.6788235294117652.277
966621AG1-532 C
Adder
1.27294117647058851.082
940642AE2-051 E
Adder
11.79999999999999910.03
918532AA1-067 E
Adder
0.72588235294117650.617
918512AA1-065 E OP
Adder
6.2364705882352955.301
934502AD1-074 E
Adder
20.57176470588235517.486
934512AD1-075 E
Adder
5.1435294117647064.372
943462AF1-017 E
Adder
2.71882352941176462.311
942341AE2-247 C
Adder
1.84117647058823521.565
316159AE1-175 C
50/50
0.6010.601
919153AA1-139 E2
50/50
5.7365.736
316388AE2-253 GEN
50/50
2.7582.758
958162AF2-110 E
Adder
2.8870588235294122.454
966622AG1-532 E
Adder
0.84823529411764710.721
935162AD1-151 E
Adder
12.10588235294117610.29
943461AF1-017 C
Adder
1.66588235294117641.416
316311AC2-079 C
Adder
7.1458823529411766.074
932596AC2-079 E
Adder
11.6588235294117669.91
920692AA2-178 E
Adder
5.1082352941176474.342
3152331SURRY 2
50/50
43.89143.891
917122Z2-027 E
Adder
1.83411764705882341.559
3146326AYDLETT TAP
50/50
1.8931.893
938532AE1-072 E
50/50
12.8112.81
940551AE2-041 C
Adder
9.8305882352941178.356
957832AF2-077 E
50/50
2.0912.091
939246AE1-155 E
Adder
11.1941176470588259.515
3145723EMPORIA
Adder
0.39411764705882360.335
923573AB1-173 E OP
Adder
3.06235294117647072.603
919692AA2-053 E OP
Adder
4.1705882352941183.545
924814AB2-134 E
Adder
14.67647058823529312.475
920042AA2-088 E OP
Adder
11.93294117647058910.143
934521AD1-076 C
Adder
14.67647058823529312.475
934511AD1-075 C
Adder
10.102352941176478.587
942342AE2-247 E
Adder
2.54235294117647072.161
919152AA1-139 E1
50/50
5.7365.736
316036AC1-147 C
50/50
0.5220.522
943741AF1-042 C
Adder
3.8023529411764713.232
962861AG1-135 C
Adder
7.8329411764705896.658
3141813NORNECK
Adder
1.09294117647058830.929
939192AE1-149 E
Adder
7.1047058823529416.039
924517AB2-100 E2
Adder
2.6788235294117652.277
934501AD1-074 C
Adder
40.41176470588235534.35
937226AE2-253 E
50/50
8.238.23
934065AD1-033 E
50/50
7.137.13
939312AE1-162 E
Adder
1.9235294117647061.635
3151091ELIZAR2
50/50
4.4644.464
935112AD1-144 E
50/50
1.3041.304
316314AB2-024 C
50/50
0.4030.403
943742AF1-042 E
Adder
6.20470588235294155.274
962862AG1-135 E
Adder
5.2211764705882354.438
966662AG1-536 E
Adder
9.2917647058823527.898
940431AE2-027 C
Adder
10.9364705882352939.296
316088AB2-174 E
Adder
6.03294117647058855.128
923994AB2-040_E
Adder
5.7423529411764714.881
316141AB2-099 E
Adder
0.27764705882352940.236
316294AC1-161 C
50/50
7.7117.711
944581AF1-123 C
50/50
65.6165.61
316185AD1-033 C
50/50
1.7411.741
916191Z1-068 C
50/50
0.0620.062
941101AE2-104 C
Adder
4.4482352941176473.781
934392AD1-063 E
50/50
1.4751.475
3150731STONECA
Adder
6.8694117647058835.839
935161AD1-151 C
Adder
18.1615.436
900672V4-068 E
Adder
0.395294117647058850.336
933981AD1-022 C
Adder
10.3435294117647068.792
3145393UNCAMP
Adder
7.4105882352941186.299
938531AE1-072 C
50/50
24.57324.573
932046AC2-012 E
50/50
18.61318.613
958161AF2-110 C
Adder
1.81529411764705871.543
963611AG1-210 C
Adder
0.820.697
3138116ELKO L286
Adder
1.60117647058823541.361
940541AE2-040 C
Adder
2.5717647058823532.186
940481AE2-033 C
Adder
14.5623529411764712.378
940482AE2-033 E
Adder
9.817647058823538.345
923263AB1-132 E OP
Adder
5.86235294117647054.983
316375AC2-012 C
50/50
1.9131.913
961611AG1-000B C
Adder
20.0529411764705917.045
316072AD1-144 C
50/50
0.3890.389
316059AD1-063 C
50/50
0.360.36
957831AF2-077 C
50/50
0.4830.483
958262AF2-120 E
Adder
5.3588235294117644.555
966661AG1-536 C
Adder
6.91529411764705955.878
316078AC2-138 E
Adder
1.1482352941176470.976
940432AE2-027 E
Adder
7.2905882352941186.197
919710AA2-057 E
Adder
3.71882352941176463.161
3137643SOCKMAN
Adder
0.6764705882352940.575
939411AE1-173 C
Adder
101.4858823529411986.263
926472AC1-118 E
Adder
1.13411764705882350.964
926785AC1-164_E
50/50
25.83625.836
927146AC1-208 E
Adder
3.8470588235294123.27
316084AB2-161 E
Adder
6.0352941176470595.13
940641AE2-051 C
Adder
17.715.045
933982AD1-022 E
Adder
5.6317647058823534.787
3145946PLYMOUTH TP
Adder
0.38941176470588240.331
316017AA1-139 ULT1
50/50
1.5131.513
943471AF1-018 C
Adder
9.8305882352941178.356
958261AF2-120 C
Adder
8.0388235294117656.833
3143316POE
Adder
1.19294117647058821.014
939191AE1-149 C
Adder
10.6576470588235289.059
926206AC1-098 E
Adder
3.5952941176470593.056
316382AG1-145 C
50/50
0.5420.542
901082W1-029 E
Adder
43.0176470588235336.565
3150981CHESPKA
50/50
0.6170.617
934146AD1-041 E
Adder
4.8129411764705894.091
957601AF2-054 C
Adder
2.92.465
934012AD1-025 E
Adder
11.69.86
913392Y1-086 E
Adder
3.0235294117647062.57
3150991CHESPKB
50/50
1.0231.023
939612AE1-191 E
Adder
7.76.545
957602AF2-054 E
Adder
1.93294117647058841.643
961952AG1-038 E
Adder
5.8035294117647064.933
961951AG1-038 C
Adder
4.20352941176470553.573
936582AD2-073 E
Adder
1.23176470588235291.047
946282AF1-292 E
Adder
0.93647058823529420.796
944012AF1-069 E
Adder
4.47999999999999953.808
917512Z2-088 E OP1
Adder
4.702352941176473.997
316316AC1-027 C
50/50
0.4470.447
3144216WINCHST
50/50
0.20.2
925865AC1-065 E
Adder
22.29058823529411618.947
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.05913.059
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.06213.062
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.9921.992
LAGNLTFEXP_LAGN->PJM
CLTF
4.854.85
NYPJM->LTFIMP_NY
CLTF
1.3121.312
LGEELTFEXP_LGEE->PJM
CLTF
0.5530.553
WECLTFEXP_WEC->PJM
CLTF
0.2830.283
G-007PJM->LTFIMP_G-007
CMTX_NF
2.7242.724
SIGELTFEXP_SIGE->PJM
CLTF
0.1170.117
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.274.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
70.8670.86
CPLELTFEXP_CPLE->PJM
CLTF
8.9638.963
TVALTFEXP_TVA->PJM
CLTF
3.7783.778
O66PJM->LTFIMP_O-066
CMTX_NF
17.37617.376

Details for 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 588_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8FENTRES-6FENTRES 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 588_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.03 %
Rating:1115.59 MVA
Rating Type:B
MVA to Mitigate:1305.6
MW Contribution:412.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944591AF1-124 C
50/50
127.837127.837
944601AF1-125 C
50/50
125.423125.423
944602AF1-125 E
50/50
287.119287.119
944592AF1-124 E
50/50
292.753292.753
944582AF1-123 E
50/50
291.697291.697
944581AF1-123 C
50/50
127.385127.385

Details for 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 588_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8FENTRES-6FENTRES 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 588_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:116.88 %
Rating:1103.28 MVA
Rating Type:B
MVA to Mitigate:1289.51
MW Contribution:407.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944591AF1-124 C
50/50
126.263126.263
944601AF1-125 C
50/50
123.877123.877
944602AF1-125 E
50/50
283.581283.581
944592AF1-124 E
50/50
289.147289.147
944582AF1-123 E
50/50
288.103288.103
944581AF1-123 C
50/50
125.815125.815

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.53 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4213.9
MW Contribution:161.52
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
964212AG1-282 E
Adder
1.44470588235294131.228
3150601CHESTF5
Adder
71.6458823529411960.899
3150431FOUR RIVERA
50/50
3.613.61
966881AG1-559 C
50/50
2.8382.838
925332AB2-190 E
Adder
9.057647058823537.699
963041AG1-153 C
Adder
5.4305882352941184.616
944011AF1-069 C
Adder
12.71176470588235210.805
927226AC1-216 E
Adder
8.6447058823529417.348
3145413WATKINS
Adder
0.72823529411764710.619
936666AD2-085 E
Adder
6.1494117647058835.227
962962AG1-145 E
Adder
1.61647058823529431.374
938771AE1-103 C
Adder
3.12235294117647082.654
944591AF1-124 C
Adder
50.0517647058823542.544
944601AF1-125 C
Adder
49.1058823529411841.74
941591AE2-156 C
Adder
19.6952941176470616.741
936591AD2-074 C
Adder
6.0611764705882365.152
3150461FOUR RIVERD
50/50
3.5573.557
3150651CHESTF6
Adder
20.99647058823529717.847
946262AF1-291 E
Adder
1.61764705882352941.375
934576AD1-082 E
Adder
4.8541176470588244.126
934522AD1-076 E
Adder
6.5094117647058835.533
933292AC2-141 E
Adder
14.30941176470588312.163
940492AE2-034 E
Adder
3.25176470588235272.764
944602AF1-125 E
Adder
112.412941176470695.551
957871AF2-081 C
Adder
10.904705882352949.269
3145506HICKORY
Adder
2.38470588235294122.027
943612AF1-032 E
Adder
1.00941176470588250.858
3130536PAPERMILL
Adder
7.2870588235294126.194
939602AE1-190 E
Adder
1.56117647058823541.327
936592AD2-074 E
Adder
9.8894117647058838.406
944631AF1-128 C
Adder
44.8294117647058838.105
315052AA1-145 CT2
50/50
5.7475.747
3150471FOUR RIVERE
50/50
3.5573.557
934782AD1-105 E
Adder
2.9682352941176472.523
938552AE1-074 E
Adder
1.38000000000000011.173
3150411LDYSMT5
50/50
5.5725.572
316160AE1-175 E
Adder
1.33411764705882341.134
933291AC2-141 C
Adder
33.5211764705882428.493
926755AC1-161 E
Adder
14.30941176470588312.163
957872AF2-081 E
Adder
4.6741176470588233.973
925522AC1-027 E
Adder
1.3364705882352941.136
941102AE2-104 E
Adder
5.80941176470588254.938
3145256KINGFORK
Adder
1.11529411764705880.948
3150921YORKTN3
Adder
133.3164705882353113.319
964211AG1-282 C
Adder
2.16705882352941171.842
316076AC2-137 E
Adder
1.50588235294117641.28
966872AG1-558 E
Adder
1.36941176470588231.164
966871AG1-558 C
Adder
2.71882352941176462.311
3150831SPRUNCA
Adder
10.2905882352941188.747
3150841SPRUNCB
Adder
10.2905882352941188.747
3150391LDYSMT3
50/50
5.5445.544
923852AB2-025 E
Adder
1.19058823529411771.012
941032AE2-094 E
Adder
17.42588235294117614.812
941031AE2-094 C
Adder
38.9070588235294133.071
939412AE1-173 E
Adder
62.4952941176470653.121
916192Z1-068 E
Adder
2.0635294117647061.754
926662AC1-147 E
Adder
1.45764705882352951.239
957492AF2-043 E
Adder
1.55294117647058831.32
923842AB2-024 E
Adder
1.97176470588235291.676
316157AD2-030 E
Adder
1.30235294117647071.107
963612AG1-210 E
Adder
1.06823529411764720.908
926412AC1-112 E
50/50
1.2791.279
3150441FOUR RIVERB
50/50
3.613.61
3152261N ANNA2
50/50
40.89340.893
924516AB2-100 E1
Adder
2.91411764705882352.477
940642AE2-051 E
Adder
11.7000000000000019.945
934502AD1-074 E
Adder
17.90117647058823615.216
934512AD1-075 E
Adder
4.4752941176470593.804
943462AF1-017 E
Adder
2.4117647058823532.05
942341AE2-247 C
Adder
1.63294117647058811.388
919153AA1-139 E2
Adder
4.463.791
958162AF2-110 E
Adder
2.3717647058823532.016
927042AC1-191 E
Adder
5.4376470588235294.622
316233AE1-074 C
Adder
2.73882352941176472.328
3150381LDYSMT2
50/50
5.4025.402
935162AD1-151 E
Adder
12.0576470588235310.249
943461AF1-017 C
Adder
1.47764705882352951.256
316311AC2-079 C
Adder
6.2752941176470595.334
932596AC2-079 E
Adder
10.2388235294117648.703
920692AA2-178 E
Adder
4.3352941176470593.685
917122Z2-027 E
Adder
1.4552941176470591.237
3146326AYDLETT TAP
Adder
1.47764705882352951.256
938532AE1-072 E
Adder
9.9870588235294138.489
940551AE2-041 C
Adder
7.8435294117647066.667
957832AF2-077 E
Adder
1.57882352941176471.342
939246AE1-155 E
Adder
9.4658823529411768.046
316004AC1-112 C
50/50
0.3720.372
3142296MT RD221
50/50
0.1380.138
944641AF1-129 C
Adder
115.3152941176470698.018
316240AF1-291 C
Adder
2.42588235294117642.062
924814AB2-134 E
Adder
14.1612.036
920042AA2-088 E OP
Adder
10.9811764705882359.334
934521AD1-076 C
Adder
12.77058823529411810.855
934511AD1-075 C
Adder
8.7917647058823527.473
942342AE2-247 E
Adder
2.2552941176470591.917
919152AA1-139 E1
Adder
4.463.791
943741AF1-042 C
Adder
3.1717647058823532.696
962861AG1-135 C
Adder
6.6023529411764715.612
3141813NORNECK
Adder
0.94823529411764720.806
3152251N ANNA1
50/50
40.87840.878
942001AE2-212 C
Adder
2.40588235294117642.045
939192AE1-149 E
Adder
7.9200000000000016.732
924517AB2-100 E2
Adder
2.91411764705882352.477
934501AD1-074 C
Adder
35.1647058823529429.89
937226AE2-253 E
Adder
6.3811764705882365.424
934065AD1-033 E
Adder
5.49411764705882364.67
939312AE1-162 E
Adder
1.58588235294117651.348
316169AC1-164 GEN
Adder
45.3376470588235338.537
930122AB1-027 E
50/50
1.5721.572
966882AG1-559 E
50/50
1.431.43
939261AE1-157 C
50/50
16.59116.591
963042AG1-153 E
Adder
8.1447058823529416.923
316349AD2-085 C
Adder
3.7682352941176473.203
938772AE1-103 E
Adder
4.3117647058823533.665
916042Z1-036 E
Adder
30.54352941176470525.962
944592AF1-124 E
Adder
114.6297.427
944582AF1-123 E
Adder
114.2058823529411997.075
923832AB2-022 E
Adder
1.34705882352941191.145
935112AD1-144 E
Adder
1.0352941176470590.88
943742AF1-042 E
Adder
5.1741176470588234.398
962862AG1-135 E
Adder
4.40117647058823553.741
966662AG1-536 E
Adder
7.857647058823536.679
3150401LDYSMT4
50/50
5.5555.555
942002AE2-212 E
Adder
1.60352941176470591.363
940431AE2-027 C
Adder
14.49176470588235312.318
944581AF1-123 C
Adder
49.87411764705882442.393
941101AE2-104 C
Adder
3.65411764705882373.106
934392AD1-063 E
Adder
1.17647058823529421
3150701DARBY 4
50/50
2.9132.913
3142366NRTHEST
50/50
0.2110.211
315051AA1-145 CT1
50/50
5.755.75
3150481FOUR RIVERF
50/50
4.3444.344
3150731STONECA
Adder
7.7717647058823536.606
935161AD1-151 C
Adder
18.08588235294117715.373
3145393UNCAMP
Adder
6.4517647058823535.484
938531AE1-072 C
Adder
19.15764705882352816.284
932046AC2-012 E
Adder
14.41411764705882512.252
958161AF2-110 C
Adder
1.49058823529411751.267
963611AG1-210 C
Adder
0.7117647058823530.605
3138116ELKO L286
Adder
1.57058823529411761.335
927041AC1-191 C
Adder
10.915294117647069.278
3150371LDYSMT1
50/50
5.3335.333
940541AE2-040 C
Adder
2.94352941176470572.502
940481AE2-033 C
Adder
16.55647058823529614.073
940482AE2-033 E
Adder
11.1611764705882369.487
961611AG1-000B C
Adder
17.75176470588235515.089
926785AC1-164_E
Adder
20.36941176470588417.314
316084AB2-161 E
Adder
6.0929411764705895.179
940641AE2-051 C
Adder
17.55058823529411814.918
3145946PLYMOUTH TP
Adder
0.33764705882352940.287
958261AF2-120 C
Adder
6.7976470588235295.778
3143316POE
Adder
1.4917647058823531.268
939191AE1-149 C
Adder
11.8810.098
901082W1-029 E
Adder
34.4682352941176529.298
934146AD1-041 E
Adder
3.9035294117647063.318
957601AF2-054 C
Adder
2.321.972
958262AF2-120 E
Adder
4.53176470588235253.852
966661AG1-536 C
Adder
5.8482352941176474.971
316078AC2-138 E
Adder
0.99647058823529410.847
316312AB1-027 C
50/50
0.5970.597
3150451FOUR RIVERC
50/50
4.414.41
940432AE2-027 E
Adder
9.6611764705882348.212
939411AE1-173 C
Adder
93.7423529411764679.681
934012AD1-025 E
Adder
11.1917647058823539.513
913392Y1-086 E
Adder
2.38588235294117632.028
939612AE1-191 E
Adder
6.2458823529411775.309
957602AF2-054 E
Adder
1.54705882352941181.315
961952AG1-038 E
Adder
4.8411764705882364.115
961951AG1-038 C
Adder
3.50588235294117642.98
939262AE1-157 E
50/50
8.9998.999
944012AF1-069 E
Adder
4.9388235294117654.198
925865AC1-065 E
Adder
18.27411764705882315.533
943471AF1-018 C
Adder
7.8435294117647066.667
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.55931.559
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.04923.049
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.0634.063
LAGNLTFEXP_LAGN->PJM
CLTF
7.8427.842
NYPJM->LTFIMP_NY
CLTF
2.6672.667
LGEELTFEXP_LGEE->PJM
CLTF
1.3551.355
WECLTFEXP_WEC->PJM
CLTF
0.6690.669
G-007PJM->LTFIMP_G-007
CMTX_NF
5.6455.645
SIGELTFEXP_SIGE->PJM
CLTF
0.2590.259
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.1265.126
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.18992.189
CPLELTFEXP_CPLE->PJM
CLTF
10.74810.748
TVALTFEXP_TVA->PJM
CLTF
6.2796.279
O66PJM->LTFIMP_O-066
CMTX_NF
35.97435.974

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.94 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3379.54
MW Contribution:118.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
48.65647058823529441.358
925332AB2-190 E
Adder
6.3717647058823535.416
963041AG1-153 C
50/50
4.3484.348
944011AF1-069 C
50/50
10.20810.208
927226AC1-216 E
Adder
6.1082352941176475.192
3145413WATKINS
Adder
0.54117647058823540.46
936666AD2-085 E
Adder
4.5011764705882353.826
962962AG1-145 E
Adder
1.10235294117647080.937
938771AE1-103 C
Adder
2.30941176470588251.963
944591AF1-124 C
50/50
36.71436.714
944601AF1-125 C
50/50
36.02136.021
3151101ELIZAR3
50/50
2.5992.599
941591AE2-156 C
Adder
14.39882352941176612.239
3150861SPRUNCD
50/50
0.1320.132
3150651CHESTF6
Adder
14.8105882352941212.589
946262AF1-291 E
Adder
1.14588235294117660.974
3151021BRUNSWICKG1
50/50
6.3966.396
934576AD1-082 E
Adder
3.5411764705882353.01
933292AC2-141 E
50/50
10.44910.449
944602AF1-125 E
50/50
82.45882.458
957871AF2-081 C
Adder
7.9988235294117666.799
3145506HICKORY
Adder
1.7482352941176471.486
943612AF1-032 E
Adder
0.740.629
944631AF1-128 C
Adder
30.4447058823529425.878
3150851SPRUNCC
50/50
0.1320.132
938552AE1-074 E
50/50
1.0491.049
938562AE1-075 E
Adder
0.82470588235294120.701
3151031BRUNSWICKG2
50/50
6.3966.396
316160AE1-175 E
Adder
0.90941176470588240.773
933291AC2-141 C
50/50
24.47824.478
926755AC1-161 E
50/50
10.44910.449
957872AF2-081 E
Adder
3.42823529411764752.914
925522AC1-027 E
Adder
0.97764705882352940.831
941102AE2-104 E
Adder
4.2623529411764713.623
3145256KINGFORK
Adder
0.81058823529411760.689
3150921YORKTN3
Adder
92.9023529411764778.967
316076AC2-137 E
Adder
0.99176470588235290.843
3150831SPRUNCA
50/50
7.377.37
3150841SPRUNCB
50/50
7.377.37
923862AB2-026 E
Adder
0.96705882352941170.822
316045AC1-158 C2
50/50
14.72914.729
316044AC1-158 C1
50/50
14.72914.729
923852AB2-025 E
Adder
0.90941176470588240.773
3151051BRUNSWICKS1
50/50
13.28713.287
941032AE2-094 E
50/50
13.99213.992
941031AE2-094 C
50/50
31.24231.242
939412AE1-173 E
50/50
48.51748.517
916192Z1-068 E
Adder
1.51058823529411781.284
3151081ELIZAR1
50/50
2.5662.566
926662AC1-147 E
Adder
1.06470588235294120.905
957492AF2-043 E
Adder
1.13882352941176480.968
316169AC1-164 GEN
Adder
29.7105882352941225.254
925022AB2-158 E
50/50
4.8864.886
963042AG1-153 E
50/50
6.5226.522
316349AD2-085 C
Adder
2.7588235294117652.345
938772AE1-103 E
Adder
3.18941176470588242.711
916042Z1-036 E
Adder
22.54588235294117719.164
944592AF1-124 E
50/50
84.07784.077
944582AF1-123 E
50/50
83.77383.773
923832AB2-022 E
Adder
0.98941176470588230.841
3151091ELIZAR2
50/50
2.5212.521
935112AD1-144 E
Adder
0.75294117647058820.64
3152261N ANNA2
50/50
47.5747.57
924516AB2-100 E1
Adder
2.21882352941176461.886
940642AE2-051 E
50/50
9.2539.253
943462AF1-017 E
Adder
1.76470588235294111.5
942341AE2-247 C
Adder
1.19529411764705881.016
919153AA1-139 E2
Adder
3.27058823529411762.78
958162AF2-110 E
Adder
1.74000000000000021.479
316233AE1-074 C
50/50
2.0822.082
926739AC1-158 E1
50/50
38.52538.525
3152411Z1-086 GT1
50/50
8.198.19
3152441Z1-086 ST
50/50
14.25614.256
935162AD1-151 E
Adder
8.4988235294117667.224
943461AF1-017 C
Adder
1.08235294117647070.92
316311AC2-079 C
Adder
4.5952941176470593.906
932596AC2-079 E
Adder
7.497647058823536.373
917122Z2-027 E
Adder
1.06941176470588250.909
3146326AYDLETT TAP
Adder
1.08470588235294120.922
938532AE1-072 E
Adder
7.3270588235294126.228
957832AF2-077 E
Adder
1.07764705882352940.916
944641AF1-129 C
Adder
81.343529411764769.142
316240AF1-291 C
Adder
1.721.462
924814AB2-134 E
Adder
10.004705882352948.504
942342AE2-247 E
Adder
1.65176470588235281.404
919152AA1-139 E1
Adder
3.27058823529411762.78
958502AF2-144 E
Adder
0.95058823529411770.808
3152251N ANNA1
50/50
47.55247.552
316192AB2-158 C
50/50
1.8381.838
942001AE2-212 C
50/50
1.7341.734
939192AE1-149 E
50/50
5.7625.762
924517AB2-100 E2
Adder
2.21882352941176461.886
937226AE2-253 E
Adder
4.6788235294117653.977
934065AD1-033 E
Adder
4.0258823529411773.422
939312AE1-162 E
Adder
1.14235294117647060.971
942002AE2-212 E
50/50
1.1561.156
940431AE2-027 C
Adder
10.2917647058823528.748
957481AF2-042 C
Adder
12.04117647058823510.235
316294AC1-161 C
50/50
3.9863.986
944581AF1-123 C
50/50
36.58436.584
941101AE2-104 C
Adder
2.68117647058823532.279
3150731STONECA
Adder
5.4305882352941184.616
3152421Z1-086 GT2
50/50
8.1888.188
935161AD1-151 C
Adder
12.74823529411764710.836
3145393UNCAMP
Adder
4.7823529411764714.065
938531AE1-072 C
Adder
14.05529411764705811.947
932046AC2-012 E
Adder
10.5364705882352958.956
958161AF2-110 C
Adder
1.09411764705882360.93
3138116ELKO L286
Adder
1.03411764705882360.879
926740AC1-158 E2
50/50
38.52538.525
940541AE2-040 C
Adder
2.24941176470588241.912
940481AE2-033 C
Adder
12.64705882352941110.75
940482AE2-033 E
Adder
8.5258823529411767.247
3152431Z1-086 GT3
50/50
8.1888.188
961611AG1-000B C
Adder
12.62823529411764810.734
940432AE2-027 E
Adder
6.8611764705882355.832
939411AE1-173 C
50/50
72.77672.776
934012AD1-025 E
Adder
7.9070588235294126.721
913392Y1-086 E
Adder
1.75294117647058821.49
926785AC1-164_E
Adder
13.34823529411764811.346
926004AC1-076_E
50/50
4.684.68
316084AB2-161 E
Adder
4.4435294117647063.777
940641AE2-051 C
50/50
13.8813.88
316164AC1-076_C
50/50
0.8170.817
3143316POE
50/50
1.1011.101
939191AE1-149 C
50/50
8.6438.643
3151041BRUNSWICKG3
50/50
6.3966.396
901082W1-029 E
Adder
25.35058823529411521.548
944012AF1-069 E
50/50
3.9663.966
316303AF2-085
50/50
3.2933.293
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.47618.476
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.62115.621
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.5882.588
LAGNLTFEXP_LAGN->PJM
CLTF
5.5035.503
NYPJM->LTFIMP_NY
CLTF
2.0512.051
LGEELTFEXP_LGEE->PJM
CLTF
0.8310.831
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
G-007PJM->LTFIMP_G-007
CMTX_NF
4.2794.279
SIGELTFEXP_SIGE->PJM
CLTF
0.1630.163
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.9113.911
CBM South 2LTFEXP_CBM-S2->PJM
CBM
69.2669.26
CPLELTFEXP_CPLE->PJM
CLTF
8.2058.205
TVALTFEXP_TVA->PJM
CLTF
4.3954.395
O66PJM->LTFIMP_O-066
CMTX_NF
27.29527.295
CONTINGENCY 'DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 3_SRT-A'
 OPEN BRANCH FROM BUS 314909 TO BUS 314960 CKT 3   /*8FENTRES     500.0 - 6FENT1       230.0
END
CONTINGENCY 'DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 1_SRT-A'
 OPEN BRANCH FROM BUS 314909 TO BUS 314960 CKT 1   /*8FENTRES     500.0 - 6FENT1       230.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A'
 OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1   /*8FENTRES     500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
314960 to 314909 ckt 1
314960 to 314909 ckt 2
314960 to 314909 ckt 3
314212 to 314150 ckt 1
314322 to 314914 ckt 1
316171 to 314481 ckt 1
314150 to 939260 ckt 1
314905 to 314900 ckt 1
314903 to 314908 ckt 1
314909 to 314466 ckt 1
314909 to 314466 ckt 2
314911 to 314905 ckt 1
314934 to 314916 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AF1-125 was evaluated as a 820.0 MW injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC113.52 %678.68B770.4633.33
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC106.87 %678.68B725.2936.58
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC113.06 %678.68B767.333.33
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC106.41 %678.68B722.1636.58
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P1-2: LN 271_SRT-A
SingleAC111.0 %678.68B753.35165.69
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P1-2: LN 2240_SRT-A
SingleAC111.0 %678.68B753.33165.69

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.52 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:770.46
MW Contribution:33.33
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.06 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:814.81
MW Contribution:37.37
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.0258.025
3150651CHESTF6
80/20
3.3173.317
3150831SPRUNCA
80/20
1.4311.431
3150841SPRUNCB
80/20
1.4311.431
3156056W1-029WIND
80/20
0.5460.546
3156116Z1-036WIND
80/20
0.9860.986
901082W1-029 E
80/20
3.6623.662
916042Z1-036 E
80/20
6.626.62
916192Z1-068 E
80/20
0.2130.213
941032AE2-094 E
80/20
11.86611.866
944012AF1-069 E
80/20
3.8773.877
961942AG1-037 E
80/20
0.0860.086
963041AG1-153 C
80/20
1.7621.762
963042AG1-153 E
80/20
2.6422.642
916191Z1-068 C
80/20
0.030.03
961611AG1-000B C
80/20
1.5261.526
940541AE2-040 C
80/20
0.8680.868
941591AE2-156 C
80/20
5.0815.081
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
80/20
10.29210.292
944582AF1-123 E
80/20
23.56823.568
944591AF1-124 C
80/20
10.32910.329
944592AF1-124 E
80/20
23.65323.653
944601AF1-125 C
80/20
10.13310.133
944602AF1-125 E
80/20
23.19823.198
944631AF1-128 C
80/20
20.96620.966
944641AF1-129 C
80/20
30.36730.367
961612AG1-000B E
80/20
2.2892.289
316303AF2-085
80/20
1.8321.832
958502AF2-144 E
Adder
2.8294117647058822.405
943573AF1-028 BT
80/20
15.77615.776

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.87 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:725.29
MW Contribution:36.58
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.49 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:777.05
MW Contribution:38.72
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.4243.424
3150831SPRUNCA
80/20
1.4991.499
3150841SPRUNCB
80/20
1.4991.499
3151311EDGECMA
80/20
2.4292.429
3156056W1-029WIND
80/20
0.6050.605
3156116Z1-036WIND
80/20
1.11.1
901082W1-029 E
80/20
4.0534.053
916042Z1-036 E
80/20
7.3857.385
916192Z1-068 E
80/20
0.2340.234
941032AE2-094 E
80/20
14.50614.506
944012AF1-069 E
80/20
4.744.74
961942AG1-037 E
80/20
0.0980.098
963041AG1-153 C
80/20
2.1352.135
963042AG1-153 E
80/20
3.2023.202
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5981.598
940541AE2-040 C
80/20
1.0031.003
941591AE2-156 C
80/20
5.5525.552
943571AF1-028 C
Adder
-12.025882352941176-10.222
944581AF1-123 C
80/20
11.29511.295
944582AF1-123 E
80/20
25.86425.864
944591AF1-124 C
80/20
11.33511.335
944592AF1-124 E
80/20
25.95725.957
944601AF1-125 C
80/20
11.12111.121
944602AF1-125 E
80/20
25.45825.458
944641AF1-129 C
80/20
31.34631.346
961602AG1-000A E
80/20
1.8891.889
961612AG1-000B E
80/20
2.3972.397
316303AF2-085
80/20
2.1022.102
958502AF2-144 E
Adder
3.01882352941176452.566
943573AF1-028 BT
80/20
12.02612.026

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.06 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:767.3
MW Contribution:33.33
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.58 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:811.58
MW Contribution:37.37
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.0258.025
3150651CHESTF6
80/20
3.3173.317
3150831SPRUNCA
80/20
1.4311.431
3150841SPRUNCB
80/20
1.4311.431
3156056W1-029WIND
80/20
0.5460.546
3156116Z1-036WIND
80/20
0.9860.986
901082W1-029 E
80/20
3.6623.662
916042Z1-036 E
80/20
6.626.62
916192Z1-068 E
80/20
0.2130.213
941032AE2-094 E
80/20
11.86611.866
944012AF1-069 E
80/20
3.8773.877
961942AG1-037 E
80/20
0.0860.086
963041AG1-153 C
80/20
1.7621.762
963042AG1-153 E
80/20
2.6422.642
916191Z1-068 C
80/20
0.030.03
961611AG1-000B C
80/20
1.5261.526
940541AE2-040 C
80/20
0.8680.868
941591AE2-156 C
80/20
5.0815.081
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
80/20
10.29210.292
944582AF1-123 E
80/20
23.56823.568
944591AF1-124 C
80/20
10.32910.329
944592AF1-124 E
80/20
23.65323.653
944601AF1-125 C
80/20
10.13310.133
944602AF1-125 E
80/20
23.19823.198
944631AF1-128 C
80/20
20.96620.966
944641AF1-129 C
80/20
30.36730.367
961612AG1-000B E
80/20
2.2892.289
316303AF2-085
80/20
1.8321.832
958502AF2-144 E
Adder
2.8294117647058822.405
943573AF1-028 BT
80/20
15.77615.776

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.41 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:722.16
MW Contribution:36.58
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.03 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:773.88
MW Contribution:38.72
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.4243.424
3150831SPRUNCA
80/20
1.4991.499
3150841SPRUNCB
80/20
1.4991.499
3151311EDGECMA
80/20
2.4292.429
3156056W1-029WIND
80/20
0.6050.605
3156116Z1-036WIND
80/20
1.11.1
901082W1-029 E
80/20
4.0534.053
916042Z1-036 E
80/20
7.3857.385
916192Z1-068 E
80/20
0.2340.234
941032AE2-094 E
80/20
14.50614.506
944012AF1-069 E
80/20
4.744.74
961942AG1-037 E
80/20
0.0980.098
963041AG1-153 C
80/20
2.1352.135
963042AG1-153 E
80/20
3.2023.202
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5981.598
940541AE2-040 C
80/20
1.0031.003
941591AE2-156 C
80/20
5.5525.552
943571AF1-028 C
Adder
-12.025882352941176-10.222
944581AF1-123 C
80/20
11.29511.295
944582AF1-123 E
80/20
25.86425.864
944591AF1-124 C
80/20
11.33511.335
944592AF1-124 E
80/20
25.95725.957
944601AF1-125 C
80/20
11.12111.121
944602AF1-125 E
80/20
25.45825.458
944641AF1-129 C
80/20
31.34631.346
961602AG1-000A E
80/20
1.8891.889
961612AG1-000B E
80/20
2.3972.397
316303AF2-085
80/20
2.1022.102
958502AF2-144 E
Adder
3.01882352941176452.566
943573AF1-028 BT
80/20
12.02612.026

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 271_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 271_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.0 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:753.35
MW Contribution:165.69
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3156056W1-029WIND
80/20
0.6120.612
3156116Z1-036WIND
80/20
1.1111.111
901082W1-029 E
80/20
4.1024.102
916042Z1-036 E
80/20
7.4627.462
944581AF1-123 C
80/20
51.16351.163
944582AF1-123 E
80/20
117.157117.157
944591AF1-124 C
80/20
51.34451.344
944592AF1-124 E
80/20
117.581117.581
944601AF1-125 C
80/20
50.37550.375
944602AF1-125 E
80/20
115.318115.318
941593AE2-156 BT
80/20
18.68818.688
961613AG1-000B BT
80/20
4.8344.834

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2240_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2240_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.0 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:753.33
MW Contribution:165.69
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3156056W1-029WIND
80/20
0.6120.612
3156116Z1-036WIND
80/20
1.1111.111
901082W1-029 E
80/20
4.1024.102
916042Z1-036 E
80/20
7.4627.462
944581AF1-123 C
80/20
51.16351.163
944582AF1-123 E
80/20
117.157117.157
944591AF1-124 C
80/20
51.34451.344
944592AF1-124 E
80/20
117.581117.581
944601AF1-125 C
80/20
50.37550.375
944602AF1-125 E
80/20
115.318115.318
941593AE2-156 BT
80/20
18.68818.688
961613AG1-000B BT
80/20
4.8344.834
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 271_SRT-A'
 OPEN BRANCH FROM BUS 314481 TO BUS 316171 CKT 1   /*6LANDSTN     230.0 - 6POCATY      230.0
END
CONTINGENCY 'DVP_P1-2: LN 2240_SRT-A'
 OPEN BRANCH FROM BUS 314466 TO BUS 316171 CKT 1   /*6FENTRES     230.0 - 6POCATY      230.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314466 to 314508 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
DVP_P1-2: LN 2193_SRT-A
SingleAC112.33 %134.42B151.06.89
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC110.03 %661.76B728.1534.2
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC101.32 %661.76B670.535.68
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P1-2: LN 588_SRT-A
SingleAC155.94 %678.68B1058.33373.01
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC111.3 %661.76B736.5134.2
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC102.58 %661.76B678.8335.68
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC108.36 %661.76B717.0734.2

Details for 3BREMO-3FORK UNION 115.0 kV Ckt 2 line l/o DVP_P1-2: LN 2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
Contingency Name:
DVP_P1-2: LN 2193_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.33 %
Rating:134.42 MVA
Rating Type:B
MVA to Mitigate:151.0
MW Contribution:6.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944581AF1-123 C
Adder
2.12705882352941171.808
944582AF1-123 E
Adder
4.8705882352941174.14
944591AF1-124 C
Adder
2.13411764705882371.814
944592AF1-124 E
Adder
4.88823529411764754.155
944601AF1-125 C
Adder
2.09411764705882361.78
944602AF1-125 E
Adder
4.7941176470588244.075
958502AF2-144 E
Adder
0.740.629

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.03 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:728.15
MW Contribution:34.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.398.39
3150651CHESTF6
80/20
3.4453.445
3150831SPRUNCA
80/20
1.4641.464
3150841SPRUNCB
80/20
1.4641.464
3156056W1-029WIND
80/20
0.5590.559
3156116Z1-036WIND
80/20
1.0071.007
901082W1-029 E
80/20
3.7483.748
916042Z1-036 E
80/20
6.7636.763
916192Z1-068 E
80/20
0.2190.219
941032AE2-094 E
80/20
11.9111.91
944012AF1-069 E
80/20
3.8913.891
961942AG1-037 E
80/20
0.0870.087
963041AG1-153 C
80/20
1.7571.757
963042AG1-153 E
80/20
2.6362.636
916191Z1-068 C
80/20
0.0310.031
961611AG1-000B C
80/20
1.5771.577
940541AE2-040 C
80/20
0.8830.883
941591AE2-156 C
80/20
5.2155.215
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
80/20
10.55910.559
944582AF1-123 E
80/20
24.1824.18
944591AF1-124 C
80/20
10.59710.597
944592AF1-124 E
80/20
24.26824.268
944601AF1-125 C
80/20
10.39710.397
944602AF1-125 E
80/20
23.823.8
944631AF1-128 C
80/20
21.92121.921
944641AF1-129 C
80/20
31.53431.534
961612AG1-000B E
80/20
2.3662.366
316303AF2-085
80/20
1.8091.809
958502AF2-144 E
Adder
2.68235294117647042.28
943573AF1-028 BT
80/20
15.50215.502

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.32 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:670.5
MW Contribution:35.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.3773.377
3150831SPRUNCA
80/20
1.4651.465
3150841SPRUNCB
80/20
1.4651.465
3151311EDGECMA
80/20
2.4182.418
3156056W1-029WIND
80/20
0.5910.591
3156116Z1-036WIND
80/20
1.0781.078
901082W1-029 E
80/20
3.9623.962
916042Z1-036 E
80/20
7.2357.235
916192Z1-068 E
80/20
0.2280.228
941032AE2-094 E
80/20
14.06514.065
944012AF1-069 E
80/20
4.5964.596
961942AG1-037 E
80/20
0.0970.097
963041AG1-153 C
80/20
2.072.07
963042AG1-153 E
80/20
3.1043.104
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5651.565
940541AE2-040 C
80/20
0.9830.983
941591AE2-156 C
80/20
5.4145.414
943571AF1-028 C
Adder
-11.711764705882354-9.955
944581AF1-123 C
80/20
11.01711.017
944582AF1-123 E
80/20
25.22825.228
944591AF1-124 C
80/20
11.05611.056
944592AF1-124 E
80/20
25.3225.32
944601AF1-125 C
80/20
10.84810.848
944602AF1-125 E
80/20
24.83224.832
944641AF1-129 C
80/20
30.90830.908
961602AG1-000A E
80/20
1.8811.881
961612AG1-000B E
80/20
2.3482.348
316303AF2-085
80/20
2.0152.015
958502AF2-144 E
Adder
2.84235294117647052.416
943573AF1-028 BT
80/20
11.71211.712

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 588_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:155.94 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1058.33
MW Contribution:373.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3156056W1-029WIND
80/20
2.1742.174
3156116Z1-036WIND
80/20
3.7493.749
901082W1-029 E
80/20
14.57514.575
916042Z1-036 E
80/20
25.17225.172
916192Z1-068 E
80/20
0.4760.476
916191Z1-068 C
80/20
0.0680.068
944581AF1-123 C
80/20
115.178115.178
944582AF1-123 E
80/20
263.744263.744
944591AF1-124 C
80/20
115.587115.587
944592AF1-124 E
80/20
264.699264.699
944601AF1-125 C
80/20
113.404113.404
944602AF1-125 E
80/20
259.605259.605

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.3 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:736.51
MW Contribution:34.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.398.39
3150651CHESTF6
80/20
3.4453.445
3150831SPRUNCA
80/20
1.4641.464
3150841SPRUNCB
80/20
1.4641.464
3156056W1-029WIND
80/20
0.5590.559
3156116Z1-036WIND
80/20
1.0071.007
901082W1-029 E
80/20
3.7483.748
916042Z1-036 E
80/20
6.7636.763
916192Z1-068 E
80/20
0.2190.219
941032AE2-094 E
80/20
11.9111.91
944012AF1-069 E
80/20
3.8913.891
961942AG1-037 E
80/20
0.0870.087
963041AG1-153 C
80/20
1.7571.757
963042AG1-153 E
80/20
2.6362.636
916191Z1-068 C
80/20
0.0310.031
961611AG1-000B C
80/20
1.5771.577
940541AE2-040 C
80/20
0.8830.883
941591AE2-156 C
80/20
5.2155.215
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
80/20
10.55910.559
944582AF1-123 E
80/20
24.1824.18
944591AF1-124 C
80/20
10.59710.597
944592AF1-124 E
80/20
24.26824.268
944601AF1-125 C
80/20
10.39710.397
944602AF1-125 E
80/20
23.823.8
944631AF1-128 C
80/20
21.92121.921
944641AF1-129 C
80/20
31.53431.534
961612AG1-000B E
80/20
2.3662.366
316303AF2-085
80/20
1.8091.809
958502AF2-144 E
Adder
2.68235294117647042.28
943573AF1-028 BT
80/20
15.50215.502

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.58 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:678.83
MW Contribution:35.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.3773.377
3150831SPRUNCA
80/20
1.4651.465
3150841SPRUNCB
80/20
1.4651.465
3151311EDGECMA
80/20
2.4182.418
3156056W1-029WIND
80/20
0.5910.591
3156116Z1-036WIND
80/20
1.0781.078
901082W1-029 E
80/20
3.9623.962
916042Z1-036 E
80/20
7.2357.235
916192Z1-068 E
80/20
0.2280.228
941032AE2-094 E
80/20
14.06514.065
944012AF1-069 E
80/20
4.5964.596
961942AG1-037 E
80/20
0.0970.097
963041AG1-153 C
80/20
2.072.07
963042AG1-153 E
80/20
3.1043.104
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5651.565
940541AE2-040 C
80/20
0.9830.983
941591AE2-156 C
80/20
5.4145.414
943571AF1-028 C
Adder
-11.711764705882354-9.955
944581AF1-123 C
80/20
11.01711.017
944582AF1-123 E
80/20
25.22825.228
944591AF1-124 C
80/20
11.05611.056
944592AF1-124 E
80/20
25.3225.32
944601AF1-125 C
80/20
10.84810.848
944602AF1-125 E
80/20
24.83224.832
944641AF1-129 C
80/20
30.90830.908
961602AG1-000A E
80/20
1.8811.881
961612AG1-000B E
80/20
2.3482.348
316303AF2-085
80/20
2.0152.015
958502AF2-144 E
Adder
2.84235294117647052.416
943573AF1-028 BT
80/20
11.71211.712

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.36 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:717.07
MW Contribution:34.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.398.39
3150651CHESTF6
80/20
3.4453.445
3150831SPRUNCA
80/20
1.4641.464
3150841SPRUNCB
80/20
1.4641.464
3156056W1-029WIND
80/20
0.5590.559
3156116Z1-036WIND
80/20
1.0071.007
901082W1-029 E
80/20
3.7483.748
916042Z1-036 E
80/20
6.7636.763
916192Z1-068 E
80/20
0.2190.219
941032AE2-094 E
80/20
11.9111.91
944012AF1-069 E
80/20
3.8913.891
961942AG1-037 E
80/20
0.0870.087
963041AG1-153 C
80/20
1.7571.757
963042AG1-153 E
80/20
2.6362.636
916191Z1-068 C
80/20
0.0310.031
961611AG1-000B C
80/20
1.5771.577
940541AE2-040 C
80/20
0.8830.883
941591AE2-156 C
80/20
5.2155.215
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
80/20
10.55910.559
944582AF1-123 E
80/20
24.1824.18
944591AF1-124 C
80/20
10.59710.597
944592AF1-124 E
80/20
24.26824.268
944601AF1-125 C
80/20
10.39710.397
944602AF1-125 E
80/20
23.823.8
944631AF1-128 C
80/20
21.92121.921
944641AF1-129 C
80/20
31.53431.534
961612AG1-000B E
80/20
2.3662.366
316303AF2-085
80/20
1.8091.809
958502AF2-144 E
Adder
2.68235294117647042.28
943573AF1-028 BT
80/20
15.50215.502
CONTINGENCY 'DVP_P1-2: LN 2193_SRT-A'
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
END
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A'
 OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1   /*8FENTRES     500.0 - 8YADKIN      500.0
END
314744 to 313708 ckt 2
313373 to 314765 ckt 1
314466 to 314508 ckt 1
313707 to 313373 ckt 1
314765 to 314749 ckt 1

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC108.48 %678.68B736.2233.33
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC108.04 %678.68B733.2233.33
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P1-2: LN 271_SRT-A
OPAC109.46 %678.68B742.85165.69

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.48 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:736.22
MW Contribution:33.33
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.77 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:772.11
MW Contribution:37.37
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.0247058823529426.821
3150651CHESTF6
Adder
3.3176470588235292.82
3150831SPRUNCA
Adder
1.43058823529411771.216
3150841SPRUNCB
Adder
1.43058823529411771.216
3156116Z1-036WIND
Adder
0.98588235294117640.838
916042Z1-036 E
Adder
6.625.627
941032AE2-094 E
Adder
11.86588235294117810.086
944012AF1-069 E
Adder
3.87764705882352923.296
961942AG1-037 E
Adder
0.085882352941176470.073
963041AG1-153 C
Adder
1.76117647058823561.497
963042AG1-153 E
Adder
2.6423529411764712.246
961611AG1-000B C
Adder
1.52588235294117651.297
940541AE2-040 C
Adder
0.86823529411764710.738
941591AE2-156 C
Adder
5.0811764705882354.319
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
Adder
10.2917647058823528.748
944582AF1-123 E
Adder
23.5682352941176520.033
944591AF1-124 C
Adder
10.3282352941176478.779
944592AF1-124 E
Adder
23.65294117647058820.105
944601AF1-125 C
Adder
10.1341176470588248.614
944602AF1-125 E
Adder
23.1976470588235319.718
944631AF1-128 C
Adder
20.9658823529411817.821
944641AF1-129 C
Adder
30.36705882352941525.812
961612AG1-000B E
Adder
2.28823529411764741.945
316303AF2-085
Adder
2.1552941176470591.832
958502AF2-144 E
Adder
2.8294117647058822.405

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.04 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:733.22
MW Contribution:33.33
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.32 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:769.11
MW Contribution:37.37
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.0247058823529426.821
3150651CHESTF6
Adder
3.3176470588235292.82
3150831SPRUNCA
Adder
1.43058823529411771.216
3150841SPRUNCB
Adder
1.43058823529411771.216
3156116Z1-036WIND
Adder
0.98588235294117640.838
916042Z1-036 E
Adder
6.625.627
941032AE2-094 E
Adder
11.86588235294117810.086
944012AF1-069 E
Adder
3.87764705882352923.296
961942AG1-037 E
Adder
0.085882352941176470.073
963041AG1-153 C
Adder
1.76117647058823561.497
963042AG1-153 E
Adder
2.6423529411764712.246
961611AG1-000B C
Adder
1.52588235294117651.297
940541AE2-040 C
Adder
0.86823529411764710.738
941591AE2-156 C
Adder
5.0811764705882354.319
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
Adder
10.2917647058823528.748
944582AF1-123 E
Adder
23.5682352941176520.033
944591AF1-124 C
Adder
10.3282352941176478.779
944592AF1-124 E
Adder
23.65294117647058820.105
944601AF1-125 C
Adder
10.1341176470588248.614
944602AF1-125 E
Adder
23.1976470588235319.718
944631AF1-128 C
Adder
20.9658823529411817.821
944641AF1-129 C
Adder
30.36705882352941525.812
961612AG1-000B E
Adder
2.28823529411764741.945
316303AF2-085
Adder
2.1552941176470591.832
958502AF2-144 E
Adder
2.8294117647058822.405

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 271_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 271_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.46 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:742.85
MW Contribution:165.69
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3156116Z1-036WIND
Adder
1.1117647058823530.945
916042Z1-036 E
Adder
7.4623529411764716.343
944581AF1-123 C
50/50
51.16351.163
944582AF1-123 E
50/50
117.157117.157
944591AF1-124 C
50/50
51.34451.344
944592AF1-124 E
50/50
117.581117.581
944601AF1-125 C
50/50
50.37550.375
944602AF1-125 E
50/50
115.318115.318
941593AE2-156 BT
50/50
18.68818.688
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 271_SRT-A'
 OPEN BRANCH FROM BUS 314481 TO BUS 316171 CKT 1   /*6LANDSTN     230.0 - 6POCATY      230.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314466 to 314508 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
DVP_P1-2: LN 2193_SRT-A
OPAC112.33 %134.42B151.06.89
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC103.72 %661.76B686.4134.2
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P1-2: LN 588_SRT-A
OPAC155.94 %678.68B1058.33373.01
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC105.01 %661.76B694.9134.2
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC102.08 %661.76B675.5134.2

Details for 3BREMO-3FORK UNION 115.0 kV Ckt 2 line l/o DVP_P1-2: LN 2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
Contingency Name:
DVP_P1-2: LN 2193_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.33 %
Rating:134.42 MVA
Rating Type:B
MVA to Mitigate:151.0
MW Contribution:6.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944581AF1-123 C
Adder
2.12705882352941171.808
944582AF1-123 E
Adder
4.8705882352941174.14
944591AF1-124 C
Adder
2.13411764705882371.814
944592AF1-124 E
Adder
4.88823529411764754.155
944601AF1-125 C
Adder
2.09411764705882361.78
944602AF1-125 E
Adder
4.7941176470588244.075
958502AF2-144 E
Adder
0.740.629

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.72 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:686.41
MW Contribution:34.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.3894117647058837.131
3150651CHESTF6
Adder
3.44470588235294132.928
3150831SPRUNCA
Adder
1.46470588235294131.245
3150841SPRUNCB
Adder
1.46470588235294131.245
3156116Z1-036WIND
Adder
1.00705882352941180.856
916042Z1-036 E
Adder
6.7623529411764715.748
941032AE2-094 E
Adder
11.90941176470588110.123
944012AF1-069 E
Adder
3.8917647058823533.308
961942AG1-037 E
Adder
0.087058823529411760.074
963041AG1-153 C
Adder
1.75764705882352961.494
963042AG1-153 E
Adder
2.63647058823529432.241
961611AG1-000B C
Adder
1.57764705882352941.341
940541AE2-040 C
Adder
0.88352941176470590.751
941591AE2-156 C
Adder
5.2152941176470584.433
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
Adder
10.568.976
944582AF1-123 E
Adder
24.18000000000000320.553
944591AF1-124 C
Adder
10.5964705882352939.007
944592AF1-124 E
Adder
24.2670588235294120.627
944601AF1-125 C
Adder
10.3964705882352948.837
944602AF1-125 E
Adder
23.820.23
944631AF1-128 C
Adder
21.92117647058823618.633
944641AF1-129 C
Adder
31.5341176470588226.804
961612AG1-000B E
Adder
2.36588235294117682.011
316303AF2-085
Adder
2.12823529411764721.809
958502AF2-144 E
Adder
2.68235294117647042.28

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 588_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:155.94 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1058.33
MW Contribution:373.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3156056W1-029WIND
50/50
2.1742.174
3156116Z1-036WIND
50/50
3.7493.749
901082W1-029 E
50/50
14.57514.575
916042Z1-036 E
50/50
25.17225.172
916192Z1-068 E
50/50
0.4760.476
916191Z1-068 C
50/50
0.0680.068
944581AF1-123 C
50/50
115.178115.178
944582AF1-123 E
50/50
263.744263.744
944591AF1-124 C
50/50
115.587115.587
944592AF1-124 E
50/50
264.699264.699
944601AF1-125 C
50/50
113.404113.404
944602AF1-125 E
50/50
259.605259.605

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.01 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:694.91
MW Contribution:34.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.3894117647058837.131
3150651CHESTF6
Adder
3.44470588235294132.928
3150831SPRUNCA
Adder
1.46470588235294131.245
3150841SPRUNCB
Adder
1.46470588235294131.245
3156116Z1-036WIND
Adder
1.00705882352941180.856
916042Z1-036 E
Adder
6.7623529411764715.748
941032AE2-094 E
Adder
11.90941176470588110.123
944012AF1-069 E
Adder
3.8917647058823533.308
961942AG1-037 E
Adder
0.087058823529411760.074
963041AG1-153 C
Adder
1.75764705882352961.494
963042AG1-153 E
Adder
2.63647058823529432.241
961611AG1-000B C
Adder
1.57764705882352941.341
940541AE2-040 C
Adder
0.88352941176470590.751
941591AE2-156 C
Adder
5.2152941176470584.433
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
Adder
10.568.976
944582AF1-123 E
Adder
24.18000000000000320.553
944591AF1-124 C
Adder
10.5964705882352939.007
944592AF1-124 E
Adder
24.2670588235294120.627
944601AF1-125 C
Adder
10.3964705882352948.837
944602AF1-125 E
Adder
23.820.23
944631AF1-128 C
Adder
21.92117647058823618.633
944641AF1-129 C
Adder
31.5341176470588226.804
961612AG1-000B E
Adder
2.36588235294117682.011
316303AF2-085
Adder
2.12823529411764721.809
958502AF2-144 E
Adder
2.68235294117647042.28

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:675.51
MW Contribution:34.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.3894117647058837.131
3150651CHESTF6
Adder
3.44470588235294132.928
3150831SPRUNCA
Adder
1.46470588235294131.245
3150841SPRUNCB
Adder
1.46470588235294131.245
3156116Z1-036WIND
Adder
1.00705882352941180.856
916042Z1-036 E
Adder
6.7623529411764715.748
941032AE2-094 E
Adder
11.90941176470588110.123
944012AF1-069 E
Adder
3.8917647058823533.308
961942AG1-037 E
Adder
0.087058823529411760.074
963041AG1-153 C
Adder
1.75764705882352961.494
963042AG1-153 E
Adder
2.63647058823529432.241
961611AG1-000B C
Adder
1.57764705882352941.341
940541AE2-040 C
Adder
0.88352941176470590.751
941591AE2-156 C
Adder
5.2152941176470584.433
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
Adder
10.568.976
944582AF1-123 E
Adder
24.18000000000000320.553
944591AF1-124 C
Adder
10.5964705882352939.007
944592AF1-124 E
Adder
24.2670588235294120.627
944601AF1-125 C
Adder
10.3964705882352948.837
944602AF1-125 E
Adder
23.820.23
944631AF1-128 C
Adder
21.92117647058823618.633
944641AF1-129 C
Adder
31.5341176470588226.804
961612AG1-000B E
Adder
2.36588235294117682.011
316303AF2-085
Adder
2.12823529411764721.809
958502AF2-144 E
Adder
2.68235294117647042.28
CONTINGENCY 'DVP_P1-2: LN 2193_SRT-A'
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
END
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A'
 OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1   /*8FENTRES     500.0 - 8YADKIN      500.0
END
314744 to 313708 ckt 2
313373 to 314765 ckt 1
314466 to 314508 ckt 1
313707 to 313373 ckt 1
314765 to 314749 ckt 1

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - Issues Found

Executive Summary for Dynamic Stability Analysis using PSSE

New Service Requests (projects) in PJM Transition Cycle 1 Cluster 29 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 29 projects.

 

Table 1: Transition Cycle 1 Cluster 29 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO (MW)

MWE (MW)

MWC (MW)

Point of Interconnection

29

AF1-123

Wind

Dominion

833

833

253.2

Harper 230 kV

AF1-124

Wind

Dominion

836

836

254.1

Harper 230 kV

AF1-125

Wind

Dominion

820

820

249.3

Harper 230 kV

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 29 projects will meet the dynamics requirements of the NERC, Dominion Energy, and PJM reliability standards.

 

The load flow case finalized for Phase 2 was used as a starting point and was updated based on latest Cluster 29 data, Dominion Energy recommended transmission changes and withdrawn generation. Projects in vicinity of Cluster 29 have been dispatched online at maximum power output with near unity power factor measured at the high-side of the main substation transformer. The dynamic models for Cluster 29 projects were updated based on the latest DP2 data and include any tuning adjustments recommended during Phase 2.

 

This analysis currently was performed using the PSSE library models provided the developer.  Dominion Energy Transmission provided the models for the FACT’s devices for the AF1-123, AF1-124, and AF1-125 queue projects.

 

Cluster 29 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. 133 contingencies were studied, each with a 20 second simulation time period. The studied contingencies included:

  • Steady-state operation (30 seconds)
  • Three-phase faults with normal clearing time
  • Single-phase bus faults with normal clearing time
  • Single-phase faults with stuck breaker
  • Single-phase faults with delayed clearing at remote end
  • Single-phase faults with loss of multiple-circuit tower line.

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

The results of the analysis were evaluated against the following recovery criteria per PJM’s Regional Transmission Planning Process and Transmission Owner criteria:

  • Cluster 29 projects were able to ride through the faults (except for faults where protective action trips a generator(s)).
  • The system with Cluster 29 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.
  • Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus) and the final voltages are within the steady-state voltage ranges below per Dominion Energy’s transmission planning criteria.
    • P1 Category Contingencies:
      • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.01 to 1.096 p.u. for 500 kV facilities
    • P2, P4, P5, and P7 Category Contingencies:
      • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.00 to 1.096 p.u. for 500 kV facilities
  • No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

AF1-123, AF1-124 and AF1-125 met the 0.95 lagging and leading power factor requirements at the point of interconnect (POI) at Harpers 230 kV substation.

 

The results of the analysis identified that the addition of the AF1-123, AF1-124 and AF1-125 queue projects resulted in instability in a majority of contingencies. The following mitigation is required to maintain stability:

  • Add a second 500 kV line from the Updated Fentress to the Yadkin substations
  • Add two 230 kV gas-insulated lines (GILs) from the existing Fentress to the New Fentress substations
  • All 230 kV breakers (212822, 269T2128, 26922, 224022-1, 224022-2, 208722, W22, L122, L322, H22, SC122, SC322, SC422, SV122, and the new breakers G1 and G2 for the gas insulated lines) at Fentress 230 kV Substation require a 14 cycle clearing time
  • Dual pilot protection is required for the Fentress to AD1-033 POI 230 kV line circuit 2240

No voltage or frequency protection trips occurred for AF1-123, AF1-124 and AF1-125 queue projects using the settings provided.

 

The AF1-123, AF1-124 and AF1-125 queue projects exhibited slow active power recovery after the fault cleared and this is recovery was expected based on the model documentation provided for the OEMs’ wind turbine. The WGOWECC controller, clamps the active power at 95% for up to 5 seconds to ensure steady recovery of the system and then releases the active power to 100% to restore full operation.

 

An EMT analysis and stability analysis using a PSS/E user defined model is recommended for AF1-123, AF1-124 and AF1-125 due to the CSCR values being less than 3. A user defined model is under development by the IC and it will be evaluated as a sensitivity once the model initializes properly.

 

AE2-156 reactive power and terminal voltage recovery was not settling to a steady state value during the analysis. However, it was observed that reactive settling doesn’t violate PJM or Dominion’s criteria. The models were tuned to achieve a faster recovery in Cluster 46 Phase 2 Stability Analysis.

 

AE2-051 reactive power and terminal voltage recovery was not settling to a steady state value during the analysis. The models can be tuned to achieve a faster recovery upon request.

 

AB2-169 generator tripped for overvoltage’s above 1.25 p.u. The unit rode through when the pickup timer  was increased from 0.0 seconds to 0.0125 seconds.

 

Executive Summary for Dynamic Stability Analysis using PSCAD/EMT

 

The EMT dynamic performance analysis was revelated with the latest PSCAD models pprovided by CVOW (AF1-123, 124 & 125) generation developer.   A detailed model quality testing was performed. Below are some deficiency and corresponding update that were applied to the plant model.

 

  • CVOW initialization issues were cured by using a stiff voltage source model at POI during the initialization period and disconnected later in the simulation.
  • Pi-circuit equivalents for 66 kV IAC cables were updated to Bergeron models using best available data.
  • Onshore cable section was updated into onshore and HDD sections using best available data.
  • Earthing transformer model was included at the 66 kV delta winding of OSS transformer.
  • OSS LTC transformer taps were set to match values used for TC1 analysis.
  • Harpers STATCOM model was updated to latest OEM model.

 

Preliminary results of CVOW performance for Summer peak and Light Load system conditions for select TPL contingencies indicate the following:

 

  • Instability of the project post-fault was observed for select P1 and P6 contingencies prior to the inclusion of all proposed upgrades.
  • With the inclusion of the proposed upgrades namely the 500 kV Line 5005 between Fentress and Yadkin and two GIL circuits between new and existing Fentress 230 kV, CVOW fully recovers post-fault for a severe P4 contingency.
  • The preliminary results demonstrate the impact of the weak system strength and the improvements provided by the proposed upgrades.
  • Analysis of CVOW performance for severe P6 contingencies with the proposed upgrades is ongoing.
  • Investigation of partial nuisance tripping of CVOW post-fault is also on-going for other contingencies and system conditions.

 

CVOW Flicker

 

Preliminary analysis shows flicker issue induced by CVOW project. Preliminary flicker analysis was conducted using a range of ramp rates in the absence of data on power fluctuation in response to wind speed variation. To assess flicker impact, MEPPI evaluated multiple wind profiles, spanning from conservative scenarios to less conservative ramp rates. Results indicate that the ramp rate significantly influences the flicker observed at the POI and we violate the criteria of 1 Pst for various profiles considered. Flicker analysis was performed in PSCAD using detailed models of the CVOW project and a system equivalent at the POI.  In order to mitigate the flicker issue an addition of 300 MVAR STATCOM will need to be installed at Fentress 230 kV Substation.

 

Note:

 

TC1 Phase 3 Dynamic  Stability analysis has been completed by using library model provided in TC1 Phase 2.  For TC1 Phase 3, a PSSE User Defined Model was requested due to low SCR concerns in the area. The CVOW project developer provided a User Defined Model that did not work properly in the TC1 base case. The CVOW  project development team is actively working on getting an updated User Defined Model for the AF1-123/AF1-124/AF1-125 projects from Siemens Gamesa Renewable Energy (SGRE). This updated model was not ready at the time TC1 Phase 3 studies concluded, and CVOW will need to initiate a Necessary Study request post GIA to have the updated User Defined Model provided to PJM to perform a Dynamic Stability analysis for the AF1-123/AF1-124/AF1-125 projects.

Also, CVOW notified PJM of a change for nineteen (19) of the GSUs that are planned to be installed for the CVOW Project for Queue Position AF1-123 (OSS T1L11). Note that these 19 GSUs – installed in 19 of the 59 wind turbine generators – have been manufactured and have higher impedance values that was in the original design. Following evaluation, it has been determined that these changes in impedances to these 19 units do not affect the MFO/gross output, have very limited changes for the  losses, and the MW output at the POI will be changed, but insubstantially. The other queues AF1-124 & AF1-125 are unchanged/unaffected. This GSU change for AF1-123 will also be evaluated as part of the Necessary Study being requested above.

 

Bellow are some of the item that will be captured during post GIA Necessary study request for CVOW project.

 

  1. The User Defined Model dynamic stability analysis for AF1-123/AF1-124/AF1-125 as well as the GSU change for AF1-123.
  2. The EMT Analysis is based on PSCAD Models provided to PJM & DEV-ET on May 19th, the developers needs to confirm that these models are still valid and if updates to these models need to be made to represent changes made in the UDM please provide updated EMT models.
  3. As identified in the TC1 Phase 2 Reports and the June 2025 “EMT Generation Model Review” Report Nuisance Tripping is still occurring which can result in up to 1600 MW Tripping Off-Line.  This tripping is being initiated by the DC Protection Scheme of the WTGs, the developer needs to provide a solution to PJM & DEV-ET for this deficiency.   This solution will be evaluated in the NSA to determine if it resolves the nuisance tripping issue.  
  4. The developer needs to indicate if margin can be increased in the Over-Voltage Ride Through, Under Voltage Ride Through & Frequency Ride-Through to increase the margins from the PRC-024 & IEEE 2800 Requirements as identified in the TC1 Phase 2 Reports and the June 2025 “EMT Generation Model Review” Report.
  5. Preliminary Study Results indicate that the CVOW Project will result in a Pst Value greater than 1.  This will adversely impact Dominion’s Customers the proposed solution to this flicker issue will be to install a 300 MVAR STATCOM at Fentress Substation on the 230 kV Bus.   The developer can provide updated Ramp Rates  as part of the NSA to determine if mitigation is still required.

Reactive Power Analysis

The reactive power capability of AF1-125 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-065Earleys 230kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA1-145Four Rivers 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-088Boykins-Handsome 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB1-173Brink-Trego 115kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-100Clubhouse-Lakeview 230kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVEngineering & Procurement
AC1-036Twittys Creek 34.5kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-065Harmony Village-Shackleford 115kVSuspended
AC1-086Thelma 230kVUnder Construction
AC1-098Dawson-South Justice 115kVIn Service
AC1-099Dawson-South Justice 115kVIn Service
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-112Old Church 34.5kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-216Hopewell-Surry 230kVIn Service
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVUnder Construction
AC2-084Dawson-South Justice 115kVIn Service
AC2-100Halifax-Person 230kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-103Holland-Union Camp 115 kVSuspended
AE1-149Disputanta-Poe 115 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-157Ladysmith CT-St. Johns 230 kVUnder Construction
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE2-027Harrowgate-Locks 115kVSuspended
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVIn Service
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVWithdrawn
AE2-156Yadkin 115 kVEngineering & Procurement
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-247Myrtle-Windsor 115 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-346Ahoskie 34.5 kVIn Service
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-028Endless Caverns 115 kVPartially in Service - Under Construction
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVUnder Construction
AF1-124Harper 230 kVPartially in Service - Under Construction
AF1-128Chesterfield 230 kVUnder Construction
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVUnder Construction
AF1-294Jetersville-Ponton 115 kVEngineering & Procurement
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-042Clover-Rawlings 500 kVEngineering & Procurement
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-081Moyock 230 kVEngineering & Procurement
AF2-085Midlothian 34.5 kVIn Service
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-110Suffolk 115 kVWithdrawn
AF2-115Jetersville-Ponton 115 kVEngineering & Procurement
AF2-120Garner-Northern Neck 115 kVUnder Construction
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVEngineering & Procurement
AF2-299Fields 34.5 kVEngineering & Procurement
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-021Jetersville-Ponton 115 kVEngineering & Procurement
AG1-037Ahoskie 34.5 kVWithdrawn
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-105Mount Laurel-Barnes Junction 115 kVUnder Construction
AG1-135Garner-Lancaster 115 kVUnder Construction
AG1-145Lightfoot 34.5 kVIn Service
AG1-153Heritage 500 kVUnder Construction
AG1-210Northern Neck 34.5 kVWithdrawn
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-285Chase City-Central 115 kVEngineering & Procurement
AG1-342Dryburg 115 kVEngineering & Procurement
AG1-532Fields 34.5 kVUnder Construction
AG1-536Garner-Northern Neck 115 kVEngineering & Procurement
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
V4-068Murphy's 34.5kVIn Service
W1-029Winfall 230kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z1-068Birdneck 34.5kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-088Tarboro-Everetts 230kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In coordination with other Affected System Operators, PJM has determined that the Affected System Operator for this project that requires an Affected System Study. For the latest Affected System Study results pertaining this project, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM lists any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AF1-125 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionn9647.0Install a 300 MVAR STATCOM at Fentress Substation.Cost Allocated$16,196,842
Dominionn9380.0Replace existing Ladysmith 230/500 kV transformer 1 with four (4) 480 MVA single phase transformers.Cost Allocated$11,433,686
Dominionn9207.0Replace 6ELMONT 230 kV to 8ELMONT 500 kV circuit 1 with larger transformer (3-480 MVA single phase transformer).Cost Allocated$11,099,228
Dominionn9153.0Wreck and rebuild 5.9 miles of 230 kV line 2128 between Fentress and Thrasher with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Fentress.Cost Allocated$10,623,269
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$10,616,255
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$9,494,085
Dominionn9378.0Replace existing 230/500 kV Carson transformer #1 with (4)-480 MVA single phase transformers.Cost Allocated$8,324,368
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$6,055,486
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$3,350,825
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$2,641,194
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$2,146,115
Dominionn6605Wreck and rebuild 0.99 miles of line 271 between Pocaty and Landstown with (2)-768 ACSS (20/7) “MAUMEE” conductor @ 250 degrees C. Replace the line lead at Landstown.Cost Allocated$2,100,719
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0N/A
Dominionb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0N/A
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0N/A
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0N/A
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0N/A
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0N/A
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0N/A
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0N/A
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0N/A
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0N/A
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0N/A
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0N/A
Dominionb4030.1Chesterfield-Basin 230 kV rebuild: Wreck and rebuild approximately 12.5 miles of Chesterfield-Basin 230 kV line.Contingent$0N/A
Dominionb4030.3Basin 230 kV substation scope: Replace all terminal equipment, line leads and bus at Basin 230 kV substation to be rated to 4000A.Contingent$0N/A
Dominionb4030.4Chesterfield 230 kV substation scope: Install a new 230 kV, 80 kA 4000A circuit breaker at Chesterfield 230 kV substation.Contingent$0N/A
Dominionb4030.9Charlottesville-Fork Union 230 kV rebuild: Wreck and rebuild ~24 miles of Charlottesville-Fork Union 230 kV line.New ReinforcementContingent$0N/A
Dominionb4030.15Upgrade disconnect switches at Mt. Eagle tap 230 kV substation to 4000A.Contingent$0N/A
Dominionb4030.11Replace all terminal equipment at Charlottesville 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.Contingent$0N/A
Dominionb4030.12Replace all terminal equipment at Fork Union 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.Contingent$0N/A
Dominionb4030.10Fork Union-Bremo 230 kV rebuild: Wreck and Rebuild approximately 1.74 miles of Fork Union-Bremo 230 kV line.Contingent$0N/A
Dominionb4030.13Replace all terminal equipment at Fork Union 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.Contingent$0N/A
Dominionb4030.14Replace all terminal equipment at Bremo 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.Contingent$0N/A
Dominionb3800.373Wreck and rebuild approximately 7.14 miles of 230kV line #256 from St. Johns to structure 256/108 to achieve a summer rating of 1573 MVA. Line switch 25666 at St. Johns to be upgraded to 4000A.Contingent$0N/A
Dominionb3800.374Reconductor approximately 5.30 miles of 230kV line #256 from Ladysmith CT to structure 256/107 to achieve a summer rating of 1573 MVA.Contingent$0N/A
Dominionb4053.18Rebuild approximately 37.4 miles of 500 kV line No. 563 from Carson-Midlothian.Contingent$0N/A
Dominionb4053.19Uprate 500 kV line No. 563 associated terminal equipment at Carson to 5000A standards.Contingent$0N/A
Dominionb4053.20Uprate 500 kV line No. 563 associated terminal equipment at Midlothian to 5000A standards.Contingent$0N/A
Dominionb3692Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.Contingent$0N/A
Dominionb4053.21Uprate 500 kV line No. 567 associated terminal equipment at Chickahominy to 5000A standards.Contingent$0N/A
Dominionb4053.22Uprate 500 kV line No. 567 associated terminal equipment at Surry to 5000A standards.Contingent$0N/A
Dominionb4053.27Upgrade/install 6000A equipment at Midlothian substation to support the new conductor termination from Vontay.Contingent$0N/A
Dominionb4053.6Rebuild 20 miles of 500 kV line No. 576 from North Anna substation to Vontay substation using 6000A conductor.Contingent$0N/A
Dominionb4053.7Upgrade/install 6000A equipment at North Anna substation to support the new conductor termination.Contingent$0N/A
Dominionb4053.26Rebuild 20 miles of 500 kV line No. 576 from Vontay substation to Midlothian substation using 6000A conductor.Contingent$0N/A
Grand Total:$94,082,072

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n8492
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492
Title
Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.
Description
Wreck and rebuild one (1) overhead 500kV transmission line that will start at the existing Fentress 500 kV Substation and terminate at the existing Yadkin 500 kV Substation, located approximately 13.5 miles away.
Total Cost ($USD)
$80,172,278
Discounted Total Cost ($USD)
$22,090,619
Allocated Cost ($USD)
$7,277,745
Time Estimate
Dec 31 2026

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123833.0 MW33.5%$7,393,124
AF1-124836.0 MW33.6%$7,419,750
AF1-125820.0 MW32.9%$7,277,745
System Reinforcement: n8492
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492
Title
Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.
Description
Wreck and rebuild one (1) overhead 500kV transmission line that will start at the existing Fentress 500 kV Substation and terminate at the existing Yadkin 500 kV Substation, located approximately 13.5 miles away.
Total Cost ($USD)
$80,172,278
Allocated Cost ($USD)
$10,616,255
Time Estimate
Dec 31 2026
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$10,783,226
AF1-12413.4979 %$10,821,607
AF1-12513.2418 %$10,616,255
AF1-2940.3249 %$260,510
AF2-04231.9983 %$25,653,730
AF2-1150.1981 %$158,850
AF2-1205.8297 %$4,673,802
AF2-2223.9954 %$3,203,201
AG1-0210.1585 %$127,080
AG1-1243.1793 %$2,548,895
AG1-1355.5860 %$4,478,424
AG1-2852.9906 %$2,397,633
AG1-5365.5494 %$4,449,066

System Reinforcement: n9647.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9647.0
Title
Install a 300 MVAR STATCOM at Fentress Substation.
Description
Install a 300 MVAR STATCOM at Fentress Substation.
Total Cost ($USD)
$49,163,341
Discounted Total Cost ($USD)
$49,163,341
Allocated Cost ($USD)
$16,196,842
Time Estimate
Mar 31 2029

Contributor

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123833.0 MW33.5%$16,453,621
AF1-124836.0 MW33.6%$16,512,878
AF1-125820.0 MW32.9%$16,196,842

System Reinforcement: n9259.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9259.0
Title
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Description
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Total Cost ($USD)
$25,304,902
Discounted Total Cost ($USD)
$6,972,497
Allocated Cost ($USD)
$2,297,086
Time Estimate
Jan 01 2030

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123833.0 MW33.5%$2,333,503
AF1-124836.0 MW33.6%$2,341,907
AF1-125820.0 MW32.9%$2,297,086
System Reinforcement: n9259.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9259.0
Title
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Description
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Total Cost ($USD)
$25,304,902
Allocated Cost ($USD)
$3,350,825
Time Estimate
Jan 01 2030
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$3,403,527
AF1-12413.4979 %$3,415,641
AF1-12513.2418 %$3,350,825
AF1-2940.3249 %$82,225
AF2-04231.9983 %$8,097,127
AF2-1150.1981 %$50,138
AF2-1205.8297 %$1,475,199
AF2-2223.9954 %$1,011,031
AG1-0210.1585 %$40,110
AG1-1243.1793 %$804,512
AG1-1355.5860 %$1,413,532
AG1-2852.9906 %$756,769
AG1-5365.5494 %$1,404,266

System Reinforcement: n8492.1
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.1
Title
Two Breaker Additions at Fentress Substation.
Description
Install Two 5000 amp GIS Breakers at Fentress Substation to connect the new 500 kV line 5005.
Total Cost ($USD)
$19,945,879
Discounted Total Cost ($USD)
$5,495,875
Allocated Cost ($USD)
$1,810,614
Time Estimate
Dec 31 2026

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123833.0 MW33.5%$1,839,319
AF1-124836.0 MW33.6%$1,845,943
AF1-125820.0 MW32.9%$1,810,614
System Reinforcement: n8492.1
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.1
Title
Two Breaker Additions at Fentress Substation.
Description
Install Two 5000 amp GIS Breakers at Fentress Substation to connect the new 500 kV line 5005.
Total Cost ($USD)
$19,945,879
Allocated Cost ($USD)
$2,641,194
Time Estimate
Dec 31 2026
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$2,682,734
AF1-12413.4979 %$2,692,283
AF1-12513.2418 %$2,641,194
AF1-2940.3249 %$64,812
AF2-04231.9983 %$6,382,333
AF2-1150.1981 %$39,520
AF2-1205.8297 %$1,162,785
AF2-2223.9954 %$796,917
AG1-0210.1585 %$31,616
AG1-1243.1793 %$634,134
AG1-1355.5860 %$1,114,177
AG1-2852.9906 %$596,502
AG1-5365.5494 %$1,106,873

System Reinforcement: n8492.2
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.2
Title
Expand Yadkin Substation to accommodate the new 500 kV line.
Description
Expansion of yadkins 500 kV switchyard to accommodate the new 500 kV line which includes addition of 5000 amp GIS breakers and relocation of the existing suffolk -yadkin 500 kV line#565
Total Cost ($USD)
$16,207,123
Discounted Total Cost ($USD)
$4,465,701
Allocated Cost ($USD)
$1,471,223
Time Estimate
Dec 31 2026

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123833.0 MW33.5%$1,494,547
AF1-124836.0 MW33.6%$1,499,930
AF1-125820.0 MW32.9%$1,471,223
System Reinforcement: n8492.2
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.2
Title
Expand Yadkin Substation to accommodate the new 500 kV line.
Description
Expansion of yadkins 500 kV switchyard to accommodate the new 500 kV line which includes addition of 5000 amp GIS breakers and relocation of the existing suffolk -yadkin 500 kV line#565
Total Cost ($USD)
$16,207,123
Allocated Cost ($USD)
$2,146,115
Time Estimate
Dec 31 2026
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$2,179,869
AF1-12413.4979 %$2,187,628
AF1-12513.2418 %$2,146,115
AF1-2940.3249 %$52,663
AF2-04231.9983 %$5,185,997
AF2-1150.1981 %$32,112
AF2-1205.8297 %$944,826
AF2-2223.9954 %$647,539
AG1-0210.1585 %$25,690
AG1-1243.1793 %$515,269
AG1-1355.5860 %$905,330
AG1-2852.9906 %$484,690
AG1-5365.5494 %$899,395

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-040
Title
ELIM TC1: Wreck and rebuild 18.75 miles of Line 594 btwn Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) Dipper at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 18.75 miles of Line 594 between Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$128,018,212
Discounted Total Cost ($USD)
$35,274,058
Allocated Cost ($USD)
$8,141,139
Time Estimate
60 to 61 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
39.9 MW23.4%$8,268,348
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
40.1 MW23.5%$8,297,767
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
39.3 MW23.1%$8,141,139
AF2-04251.0 MW30.0%$10,566,803

System Reinforcement: n9247.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9247.0 / TC1-PH2-DOM-041
Title
ELIM TC1: Wreck and rebuild 14.02 miles of Line 573 btwn Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 14.02 miles of Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA
Total Cost ($USD)
$99,636,684
Discounted Total Cost ($USD)
$27,453,830
Allocated Cost ($USD)
$6,329,853
Time Estimate
48 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
40.9 MW23.4%$6,428,872
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
41.0 MW23.5%$6,451,820
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
40.3 MW23.1%$6,329,853
AF2-04252.4 MW30.0%$8,243,285

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-062
Title
ELIMINATED FOR TC1: Wreck and Rebuild 14.83 miles of 230 kV line 256 with (2) 768.2 ACSS/TW (20/7) ""Maumee"" conductor @ 250 degrees C.
Description
Wreck and Rebuild 14.83 miles of 230 kV line 256 with (2) 768.2 ACSS/TW (20/7) ""Maumee"" conductor @ 250 degrees C.
Total Cost ($USD)
$41,037,004
Discounted Total Cost ($USD)
$11,307,310
Allocated Cost ($USD)
$3,725,770
Time Estimate
46 to 47 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1174.0 MVA
(All)B1302.0 MVA
(All)C1360.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
20.7 MW33.5%$3,784,097
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
20.8 MW33.6%$3,797,444
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
20.4 MW33.0%$3,725,770

System Reinforcement: n9380.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9380.0 / TC1-PH3-DOM-012
Title
Replace existing Ladysmith 230/500 kV transformer 1 with four (4) 480 MVA single phase transformers.
Description
Replace existing Ladysmith 230/500 kV transformer 1 with four (4) 480 MVA single phase transformers.
Total Cost ($USD)
$37,587,605
Discounted Total Cost ($USD)
$37,587,605
Allocated Cost ($USD)
$11,433,686
Time Estimate
Dec 31 2029

Contributor

FacilityContingency
6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
70.3 MW30.9%$11,614,950
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
70.5 MW31.0%$11,656,754
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
69.2 MW30.4%$11,433,686
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
7.9 MW3.5%$1,304,375
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
9.5 MW4.2%$1,577,841

System Reinforcement: n9207.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9207.0 / TC1-PH2-DOM-018
Title
Replace 6ELMONT 230 kV to 8ELMONT 500 kV circuit 1 with larger transformer (3-480 MVA single phase transformer).
Description
Replace 6ELMONT 230 KV to 8ELMONT 500 kV ckt 1 with Larger XFRM. (3-480 MVA Single Phase XFRM).
Total Cost ($USD)
$38,254,469
Discounted Total Cost ($USD)
$38,254,469
Allocated Cost ($USD)
$11,099,228
Time Estimate
Dec 31 2028

Contributor

FacilityContingency
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE2-15614.4 MW3.6%$1,375,093
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
118.1 MW29.5%$11,275,111
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
118.6 MW29.6%$11,315,765
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
116.3 MW29.0%$11,099,228
AF2-08111.2 MW2.8%$1,072,666
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
10.0 MW2.5%$957,860
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
12.1 MW3.0%$1,158,746

System Reinforcement: n9153.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9153.0 / TC1-PH1-DOM-043
Title
Wreck and rebuild 5.9 miles of 230 kV line 2128 between Fentress and Thrasher with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Fentress.
Description
Wreck and rebuild 5.9 miles of 230 kV line 2128 between Fentress and Thrasher with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Fentress.
Total Cost ($USD)
$33,297,247
Discounted Total Cost ($USD)
$33,297,247
Allocated Cost ($USD)
$10,623,269
Time Estimate
Jul 01 2027

Contributor

FacilityContingency
6FENTRES-6THRASHER 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1174.0 MVA
(All)B1195.0 MVA
(All)C1360.0 MVA
LLA1410.0 MVA
LLB1481.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1446.0 MVA
WINB1517.0 MVA
WINC1631.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE2-15618.7 MW1.6%$532,288
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
378.9 MW32.4%$10,791,585
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
380.3 MW32.5%$10,830,603
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
373.0 MW31.9%$10,623,269
AF2-08118.2 MW1.6%$519,501

System Reinforcement: n9378.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9378.0 / TC1-PH3-DOM-010
Title
Replace existing 230/500 kV Carson transformer #1 with (4)-480 MVA single phase transformers.
Description
Replace Existing 230/500 kV Carson transformer #1 with (4)-480 MVA Single Phase transformers. 6CARSON - 8CARSON ckt 2 represents tranformer #1.
Total Cost ($USD)
$37,801,301
Discounted Total Cost ($USD)
$37,801,301
Allocated Cost ($USD)
$8,324,368
Time Estimate
Mar 29 2029

Contributor

FacilityContingency
6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer(Any)
Rating SetRating TypeRating Value
LLA2016.0 MVA
LLB2083.0 MVA
LLC2239.0 MVA
SUMA1707.0 MVA
SUMB1758.0 MVA
SUMC1873.0 MVA
WINA2196.0 MVA
WINB2228.0 MVA
WINC2308.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
56.2 MW22.4%$8,456,365
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
56.5 MW22.5%$8,486,733
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
55.4 MW22.0%$8,324,368
AF2-04259.5 MW23.7%$8,947,219
AF2-22212.2 MW4.8%$1,827,058
AG1-15311.7 MW4.7%$1,759,557

System Reinforcement: n9379.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9379.0 / TC1-PH3-DOM-011
Title
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.
Description
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase 500/230 kV transformers.
Total Cost ($USD)
$37,836,293
Discounted Total Cost ($USD)
$10,425,388
Allocated Cost ($USD)
$2,280,468
Time Estimate
Oct 01 2029

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
18.6 MW22.2%$2,316,170
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
18.6 MW22.3%$2,324,409
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
18.3 MW21.9%$2,280,468
AF2-04228.1 MW33.6%$3,504,341

System Reinforcement: n9146.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9146.0 / TC1-PH1-DOM-004
Title
ELIMINATED FOR TC1: Wreck and rebuild 1.51 miles of 115 kV Line No. 5 between Bremo and Fork Union with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees Celsius. Replace line lead at Bremo.
Description
Wreck and rebuild 1.51 miles of 115 kV Line No. 5 between Bremo and Fork Union with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees Celsius. Replace line lead at Bremo.
Total Cost ($USD)
$7,535,533
Discounted Total Cost ($USD)
$2,076,336
Allocated Cost ($USD)
$684,168
Time Estimate
42 to 43 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
Rating SetRating TypeRating Value
LLA242.0 MVA
LLB258.0 MVA
LLC265.0 MVA
SUMA198.0 MVA
SUMB218.0 MVA
SUMC228.0 MVA
WINA250.0 MVA
WINB266.0 MVA
WINC273.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
7.0 MW33.5%$695,091
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
7.0 MW33.6%$697,077
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
6.9 MW33.0%$684,168

System Reinforcement: n6605
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6605 / dom-101
Title
Wreck and rebuild 0.99 miles of line 271 between Pocaty and Landstown with (2)-768 ACSS (20/7) “MAUMEE” conductor @ 250 degrees C. Replace the line lead at Landstown.
Description
Wreck and rebuild 0.99 miles of line 271 between Pocaty and Landstown with (2)-768 ACSS (20/7) “MAUMEE” conductor @ 250 degrees C. Replace the line lead at Landstown.
Total Cost ($USD)
$6,555,756
Discounted Total Cost ($USD)
$6,555,756
Allocated Cost ($USD)
$2,100,719
Time Estimate
May 31 2027

Contributor

FacilityContingency
6LANDSTN-6POCATY 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1174.0 MVA
(All)B1195.0 MVA
(All)C1360.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
129.1 MW32.6%$2,134,014
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
129.6 MW32.7%$2,141,702
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
127.1 MW32.0%$2,100,719
AF2-08110.8 MW2.7%$179,321

System Reinforcement: n6161
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6161 / dom-039
Title
ELIMINATED FOR TC1: Replace 500 kV circuit breaker H1T561 at Clifton with a higher rated device (Clifton - Ox).
Description
Replace 500 kV circuit breaker H1T561 at Clifton with a higher rated device (Clifton - Ox).
Total Cost ($USD)
$2,634,901
Discounted Total Cost ($USD)
$726,019
Allocated Cost ($USD)
$239,186
Time Estimate
Dec 31 2029

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
8CLIFTON-8OX 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2857.0 MVA
(All)B3117.0 MVA
(All)C3793.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
97.5 MW33.5%$242,979
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
97.8 MW33.6%$243,854
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
96.0 MW32.9%$239,186

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-061
Title
ELIMINATED FOR TC1: Replace wave trap 256WT at Four River 230 kV station (Four River - St. John).
Description
Replace wave trap 256WT at Four River 230 kV station (Four River - St. John).
Total Cost ($USD)
$514,454
Discounted Total Cost ($USD)
$141,752
Allocated Cost ($USD)
$46,708
Time Estimate
14 to 15 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1174.0 MVA
(All)B1225.0 MVA
(All)C1360.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
20.7 MW33.5%$47,439
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
20.8 MW33.6%$47,606
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
20.4 MW33.0%$46,708

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029
Cost Alloc Type
Contingent

System Reinforcement: b4030.1
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.1
Title
Chesterfield-Basin 230 kV rebuild: Wreck and rebuild approximately 12.5 miles of Chesterfield-Basin 230 kV line.
Description
Chesterfield-Basin 230 kV rebuild: Wreck and rebuild approximately 12.5 miles of Chesterfield-Basin 230 kV line.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1572.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.3
Title
Basin 230 kV substation scope: Replace all terminal equipment, line leads and bus at Basin 230 kV substation to be rated to 4000A.
Description
Basin 230 kV substation scope: Replace all terminal equipment, line leads and bus at Basin 230 kV substation to be rated to 4000A.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1572.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.4
Title
Chesterfield 230 kV substation scope: Install a new 230 kV, 80 kA 4000A circuit breaker at Chesterfield 230 kV substation.
Description
Chesterfield 230 kV substation scope: Install a new 230 kV, 80 kA 4000A circuit breaker at Chesterfield 230 kV substation.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1572.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.9
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.9
Title
Charlottesville-Fork Union 230 kV rebuild: Wreck and rebuild ~24 miles of Charlottesville-Fork Union 230 kV line.New Reinforcement
Description
Charlottesville-Fork Union 230 kV rebuild: Wreck and rebuild ~24 miles of Charlottesville-Fork Union 230 kV line.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6CUNNING-6FORK UNION 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.15
Title
Upgrade disconnect switches at Mt. Eagle tap 230 kV substation to 4000A.
Description
Mt. Eagle tap 230 kV substation scope: Upgrade disconnect switches at Mt. Eagle tap 230 kV substation to 4000A.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.11
Title
Replace all terminal equipment at Charlottesville 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Description
Charlottesville 230 kV substation scope: Replace all terminal equipment at Charlottesville 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC16480.0 MVA

System Reinforcement: b4030.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.12
Title
Replace all terminal equipment at Fork Union 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Description
Fork Union 230 kV substation scope: Replace all terminal equipment at Fork Union 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CUNNING-6FORK UNION 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.10
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.10
Title
Fork Union-Bremo 230 kV rebuild: Wreck and Rebuild approximately 1.74 miles of Fork Union-Bremo 230 kV line.
Description
Fork Union-Bremo 230 kV rebuild: Wreck and Rebuild approximately 1.74 miles of Fork Union-Bremo 230 kV line.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB16480.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.13
Title
Replace all terminal equipment at Fork Union 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Description
Fork Union 230 kV substation scope: Replace all terminal equipment at Fork Union 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.14
Title
Replace all terminal equipment at Bremo 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Description
Bremo 230 kV substation scope: Replace all terminal equipment at Bremo 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b3800.373
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.373
Title
Wreck and rebuild approximately 7.14 miles of 230kV line #256 from St. Johns to structure 256/108 to achieve a summer rating of 1573 MVA. Line switch 25666 at St. Johns to be upgraded to 4000A.
Description
Wreck and rebuild approximately 7.14 miles of 230kV line #256 from St. Johns to structure 256/108 to achieve a summer rating of 1573 MVA. Line switch 25666 at St. Johns to be upgraded to 4000A.
Cost Information
Time Estimate
Dec 18 2026

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1809.0 MVA

System Reinforcement: b3800.374
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.374
Title
Reconductor approximately 5.30 miles of 230kV line #256 from Ladysmith CT to structure 256/107 to achieve a summer rating of 1573 MVA.
Description
Reconductor approximately 5.30 miles of 230kV line #256 from Ladysmith CT to structure 256/107 to achieve a summer rating of 1573 MVA. Terminal equipment at remote end substations will be upgraded to 4000A.
Cost Information
Time Estimate
Dec 31 2027

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1809.0 MVA

System Reinforcement: b4053.18
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.18
Title
Rebuild approximately 37.4 miles of 500 kV line No. 563 from Carson-Midlothian.
Description
Rebuild approximately 37.4 miles of 500 kV line No. 563 from Carson-Midlothian. The proposed structures to be installed are mainly 500/230 kV double-circuit V-string suspension towers. The 230 kV circuit position will be vacant at the completion of this project but serves to accommodate a future 230 kV line.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4357.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA5155.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b4053.19
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.19
Title
Uprate 500 kV line No. 563 associated terminal equipment at Carson to 5000A standards.
Description
Uprate 500 kV line No. 563 associated terminal equipment at Carson to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4357.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA5155.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b4053.20
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.20
Title
Uprate 500 kV line No. 563 associated terminal equipment at Midlothian to 5000A standards.
Description
Uprate 500 kV line No. 563 associated terminal equipment at Midlothian to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4357.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA5155.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b3692
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3692
Title
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.
Description
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy with current 500 kV standards construction practices to achieve a summer rating of 4330 MVA. Projected ISD: 06/01/2026
Cost Information
Time Estimate
Jun 01 2026

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4330.0 MVA
(All)B4330.0 MVA
(All)C5011.0 MVA

System Reinforcement: b4053.21
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.21
Title
Uprate 500 kV line No. 567 associated terminal equipment at Chickahominy to 5000A standards.
Description
Uprate 500 kV line No. 567 associated terminal equipment at Chickahominy to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3322.0 MVA
(All)B3425.0 MVA
(All)C3939.0 MVA
WINA4191.0 MVA
WINB4376.0 MVA
WINC5032.0 MVA

System Reinforcement: b4053.22
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.22
Title
Uprate 500 kV line No. 567 associated terminal equipment at Surry to 5000A standards.
Description
Uprate 500 kV line No. 567 associated terminal equipment at Surry to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3322.0 MVA
(All)B3425.0 MVA
(All)C3939.0 MVA
WINA4191.0 MVA
WINB4376.0 MVA
WINC5032.0 MVA

System Reinforcement: b3800.312
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.312
Title
Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.
Description
Rebuild 500kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. New conductor to have a summer rating of 4357 MVA.
Cost Information
Time Estimate
Jun 30 2030

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8LOUDOUN-8MORRSVL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
System Reinforcement: b3800.312
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.312
Title
Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.
Description
Rebuild 500kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. New conductor to have a summer rating of 4357 MVA.
Cost Information
Time Estimate
Jun 30 2030
Cost Alloc Type
Contingent

System Reinforcement: b4053.27
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.27
Title
Upgrade/install 6000A equipment at Midlothian substation to support the new conductor termination from Vontay.
Description
Upgrade/install 6000A equipment at Midlothian substation to support the new conductor termination from Vontay.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: b4053.6
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.6
Title
Rebuild 20 miles of 500 kV line No. 576 from North Anna substation to Vontay substation using 6000A conductor.
Description
Rebuild 20 miles of 500 kV line No. 576 from North Anna substation to Vontay substation using 6000A conductor.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: b4053.7
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.7
Title
Upgrade/install 6000A equipment at North Anna substation to support the new conductor termination.
Description
Upgrade/install 6000A equipment at North Anna substation to support the new conductor termination.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: b4053.26
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.26
Title
Rebuild 20 miles of 500 kV line No. 576 from Vontay substation to Midlothian substation using 6000A conductor.
Description
Rebuild 20 miles of 500 kV line No. 576 from Vontay substation to Midlothian substation using 6000A conductor.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: n9630.0

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Allocated Cost ($USD)
$9,494,085
Time Estimate
Dec 31 2029
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$9,643,430
AF1-12413.4979 %$9,677,702
AF1-12513.2418 %$9,494,084
AF1-2940.3249 %$232,946
AF2-04231.9983 %$22,942,088
AF2-1150.1981 %$142,033
AF2-1205.8297 %$4,179,769
AF2-2223.9954 %$2,864,615
AG1-0210.1585 %$113,641
AG1-1243.1793 %$2,279,489
AG1-1355.5860 %$4,005,041
AG1-2852.9906 %$2,144,195
AG1-5365.5494 %$3,978,800

System Reinforcement: n9267.0

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9267.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9267.0 / TC1-PH2-DOM-067
Title
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.
Description
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner substations with single (1) 768.2 ACSS/TW “Maumee” at 250 degrees C. This new line will be on separate transmission towers from the existing Northern Neck and Moon Corner line 1059. Station expansion is required at Northern Neck and Moon Corner to accommodate the new line.
Total Cost ($USD)
$45,730,074
Allocated Cost ($USD)
$6,055,486
Time Estimate
45 to 46 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$6,150,741
AF1-12413.4979 %$6,172,600
AF1-12513.2418 %$6,055,485
AF1-2940.3249 %$148,577
AF2-04231.9983 %$14,632,846
AF2-1150.1981 %$90,591
AF2-1205.8297 %$2,665,926
AF2-2223.9954 %$1,827,099
AG1-0210.1585 %$72,482
AG1-1243.1793 %$1,453,896
AG1-1355.5860 %$2,554,482
AG1-2852.9906 %$1,367,604
AG1-5365.5494 %$2,537,745

System Reinforcement: b4000.356

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.355

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.325

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.326

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.327

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: s3047.2

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: s3047.2
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3047.2
Title
Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.
Description
Install (2) 1400 MVA 500-230 kV transformers and associated 500 kV and 230 kV equipment (breakers, switches, leads) at Vint Hill Substation to supply the area with a 500 kV source Cut and loop 500 kV line #535 Loudoun – Meadowbrook and #569 Loudoun - Morrisville as the 500 kV sources into the proposed 500 kV ring bus Vint Hill Substation will be expanded to the north of the existing site to accommodate the 500 kV ring required for the addition of the new transformers Existing terminations for 230 kV line #2174 Wheeler – Vint Hill, line #2101 Bristers – Vint Hill, and line #2163 Liberty – Vint Hill will be rearranged to terminate into the expanded Vint Hill Substation 230 kV line #2114 Remington CT – Rollins Ford will also be cut and looped into the expanded Vint Hill Substation due to spatial constraints along the existing right-of-way.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.313

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.313
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.313
Title
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Description
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.356

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.356
Title
Build a new 500 kV line from Vint Hill to Wishing Star.
Description
Build a new 500kV line from Vint Hill to Wishing Star. The line will be supported on single circuit monopoles. New conductor to have a summer rating of 4357 MVA. Line length is approximately 16.59 miles
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.357

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.357
Title
Build a new 500 kV line from Morrisville to Vint Hill.
Description
Build a new 500kV line from Morrisville to Vint Hill. New conductor to have a summer rating of 4357 MVA. Line length is approximately 19.71 miles.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.354

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.354
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.354
Title
Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.
Description
Install terminal equipment at Wishing Star substation to support a 5000A line to Vint Hill. Update relay settings for 500kV Lines #546 and #590.
Cost Information
Cost Alloc Type
Contingent

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AF1-125


AF1-125 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
StabilityDominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Topology820.0 MW32.9%Cost Allocated$7,277,745
StabilityDominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Topology820.0 MW32.9%Cost Allocated$2,297,086
StabilityDominionn8492.1Two Breaker Additions at Fentress Substation.Topology820.0 MW32.9%Cost Allocated$1,810,614
StabilityDominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Topology820.0 MW32.9%Cost Allocated$1,471,223
Load FlowDominion(Pending) / TC1-PH2-DOM-040ELIM TC1: Wreck and rebuild 18.75 miles of Line 594 btwn Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) Dipper at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)Eliminated39.3 MW23.1%Cost Allocated$8,141,139
Load FlowDominionn9247.0 / TC1-PH2-DOM-041ELIM TC1: Wreck and rebuild 14.02 miles of Line 573 btwn Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)Eliminated40.3 MW23.1%Cost Allocated$6,329,853
Load FlowDominion(Pending) / TC1-PH2-DOM-062ELIMINATED FOR TC1: Wreck and Rebuild 14.83 miles of 230 kV line 256 with (2) 768.2 ACSS/TW (20/7) ""Maumee"" conductor @ 250 degrees C.Eliminated20.4 MW33.0%Cost Allocated$3,725,770
Load FlowDominionn9379.0 / TC1-PH3-DOM-011Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.Eliminated18.3 MW21.9%Cost Allocated$2,280,468
Load FlowDominionn9146.0 / TC1-PH1-DOM-004ELIMINATED FOR TC1: Wreck and rebuild 1.51 miles of 115 kV Line No. 5 between Bremo and Fork Union with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees Celsius. Replace line lead at Bremo.Eliminated6.9 MW33.0%Cost Allocated$684,168
Load FlowDominionn6161 / dom-039ELIMINATED FOR TC1: Replace 500 kV circuit breaker H1T561 at Clifton with a higher rated device (Clifton - Ox).Eliminated96.0 MW32.9%Cost Allocated$239,186
Load FlowDominion(Pending) / TC1-PH2-DOM-061ELIMINATED FOR TC1: Replace wave trap 256WT at Four River 230 kV station (Four River - St. John).Eliminated20.4 MW33.0%Cost Allocated$46,708
Load FlowDominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Topology-0.0%Contingent$0
Load FlowDominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Topology-0.0%Contingent$0
Load FlowDominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationTopology-0.0%Contingent$0
Load FlowDominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Topology-0.0%Contingent$0
Load FlowDominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Topology-0.0%Contingent$0
Load FlowDominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$34,303,960
AF1-125 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$10,616,255
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$9,494,085
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$6,055,486
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$3,350,825
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$2,641,194
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$2,146,115
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0
Dominionb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0
Region Topology Upgrade Total:$34,303,960

Attachments

AF1-125 One Line Diagram

AF1-125 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.