AF1-125 Final System Impact Study (Retool 1) Report

v1.00 released 2025-12-08 18:17

Harper 230 kV

249.3 MW Capacity / 820.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia), and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the TC1 projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.
Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of TC1 projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed a Offshore Wind generating facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — City of Chesapeake County, Virginia. The installed facilities will have a total capability of 820.0 MW with 249.3 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AF1-125
Project Name:
Harper 230 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
State:
Virginia
County:
City of Chesapeake
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
820.0
MWE:
820.0
MWC:
249.3
Fuel Type:
Offshore Wind
Basecase Study Year:
2027

Physical Interconnection Facility Study

Reviewed

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AF1-123, AF1-124 and AF1-125 will interconnect on the Dominion transmission system at the Harpers 230 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AF1-125 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AF1-125Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$7,308,561$7,308,561
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$98,140,632$98,140,632
Network Upgrades$151,928,890$151,928,890
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$231,154,224$231,154,224
Transient Stability$28,400,838$28,400,838
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$516,933,145$516,933,145

* Contributes to calculation for Security. See Security Section of this report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF1-125

Security has been calculated for the AF1-125 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF1-125
Project(s): AF1-125
Final Agreement Security (A): $516,933,145
Portion of Costs Already Paid (B): $239,142,991
Revised Net Security (C): A B = $277,790,154
Security on Hand with PJM (D): $261,850,591
Additional Security Due at Agreement Execution (E): C D = $15,939,563
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

The New Service Request Project will interconnect with the Dominion transmission system via a new Harpers switching station that connects at Fentress 230/500 kV substation. The required work for the interconnection of the New Service Request Project to the Dominion Transmission System is detailed in the following tables.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n8317.1

Expand Fentress 500 kV and 230 kV substations to terminate three new 230 kV lines from Harpers Road substation and connect them to Fentress 500 kV

$32,089,434$188,729,124$3,121,660$2,604,178$226,544,396$75,514,799 (See Note 1)
n8317.2

Construct three (3) overhead 230kV transmission lines that will start at the existing Fentress Substation and terminate at the new Harpers Road Substation, located approximately 14.3 miles away

$87,809,759$122,418,217$7,002,882$12,011,417$229,242,275$76,414,092 (See Note 1)
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n8317.3

Build new 230 kV Harpers Road switching station to terminate nine offshore wind export cables for AF1-123/124/125 and consolidate to three overhead 230 kV transmission lines to go to Fentress Substation

$54,931,535$211,895,213$9,823,673$17,771,475$294,421,896$98,140,632 (See Note 1)
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install 230 kV backbone structures and foundations within the fence of the Interconnection Substation, to terminate the Project Developer’s generator lead lines. Line conductor from the backbone structure to the bus position in the switchyard of the interconnection substation.

$497,960$6,185,453$105,765$519,383$7,308,561$7,308,561

Based on the scope of work for the Interconnection Facilities, it is expected to take 10 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

It is estimated to take 10 months to complete this work upon execution of the Generator Interconnection Agreement (GIA).This estimated time to complete is dependent on major equipment lead times. These preliminary cost estimates are based on typical engineering costs. A more detailed engineering cost estimates are normally done when the Project Developer provides an exact site plan location for the generation substation during a future study phase.  As shown in the one line diagram, this Interconnection Request is sharing the Point of Interconnection (POI) and Interconnection Facilities with one or more other Interconnection Requests. Should other requests withdraw from Transition Cycle 1, the cost allocation for Transmission Owner Interconnection Facilities, Stand Alone Network Upgrades, and applicable Network Upgrades identified in the study report will be updated for the remaining project(s). Refer to the one line for other Interconnection Requests at this POI. 


Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.
 
Remote Terminal Work: During Phase 2 of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2027 load flow model and the results were verified by Dominion.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The wind generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Wind speed (meters/second) - (Required)
  • Wind direction (decimal degrees from true north) - (Required)
  • Ambient air temperature (Fahrenheit) - (Required)
  • Air Pressure (Hectopascals) - (Required)
  • Humidity (Percent) - (Accepted, not required)
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AF1-125 was evaluated as a 820.0 MW (249.3 MW Capacity) injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC142.63 %812.0C1158.1444.79
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC133.85 %663.64B888.2715.18
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 217_SRT-A
SingleAC109.77 %663.64B728.512.81
GD1DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: H2T557_SRT-S
BreakerAC132.14 %1065.0C1407.28116.3
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P4-2: 224022-1_SRT-S
BreakerAC145.91 %830.0C1211.04221.77
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P4-2: 224022-2_SRT-S
BreakerAC145.75 %830.0C1209.69221.56
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P1-2: LN 271_SRT-A
SingleAC107.49 %678.68B729.563.02
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P1-2: LN 2240_SRT-A
SingleAC104.51 %678.68B709.2763.05
GD1DVP
6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: H2T574_SRT-S_SENS
BreakerAC134.99 %1031.0C1391.7369.2
GD1DVP
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
DVP_P4-2: 2110T2128_SRT-A
BreakerAC122.86 %830.0C1019.7127.07
GD1DVP
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
DVP_P4-2: 212822_SRT-S
BreakerAC120.29 %830.0C998.4157.15
GD1DVP
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
DVP_P4-2: 269T2128_SRT-S
BreakerAC116.98 %830.0C970.97147.89
GD1DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 56372_SRT-S
BreakerAC113.54 %1056.8C1199.8655.37
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC106.16 %3940.0C4182.74228.68
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC104.22 %3940.0C4106.12207.66
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H1T567_SRT-A
BreakerAC103.44 %3940.0C4075.55232.75
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
SingleAC100.39 %1058.16B1062.2518.83
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC108.98 %3940.0C4293.98234.92
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC104.85 %3940.0C4130.98237.26
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S_SENS
BreakerAC102.96 %3940.0C4056.76220.8
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S_SENS
SingleAC102.07 %3220.44B3287.0165.2
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC102.59 %3144.0C3225.32245.73
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC102.48 %3144.0C3221.97247.32
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC102.48 %3144.0C3221.97247.32
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC102.48 %3144.0C3221.81247.32

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.63 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1158.14
MW Contribution:44.79
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.2 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1065.31
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150731STONECA
50/50
4.7614.761
935161AD1-151 C
50/50
9.2889.288
932046AC2-012 E
Adder
4.1552941176470593.532
958161AF2-110 C
Adder
0.50941176470588230.433
938531AE1-072 C
Adder
5.49411764705882364.67
3145393UNCAMP
Adder
2.362.006
933981AD1-022 C
Adder
3.22705882352941182.743
900672V4-068 E
Adder
0.14235294117647060.121
924302AB2-077 E O1
Adder
0.448235294117647070.381
316084AB2-161 E
50/50
3.3973.397
316083AB2-161 C
50/50
0.340.34
3145946PLYMOUTH TP
Adder
0.116470588235294130.099
933982AD1-022 E
Adder
1.75647058823529421.493
927146AC1-208 E
Adder
1.62941176470588231.385
934622AD1-088 E
Adder
1.53176470588235311.302
934612AD1-087 E
Adder
1.26235294117647071.073
3150791HOPHCF3
50/50
1.6821.682
926662AC1-147 E
Adder
0.420.357
916192Z1-068 E
Adder
0.58588235294117650.498
957492AF2-043 E
Adder
0.4717647058823530.401
923852AB2-025 E
50/50
0.7170.717
939412AE1-173 E
Adder
23.37764705882352719.871
961942AG1-037 E
Adder
0.132941176470588230.113
961941AG1-037 C
Adder
0.198823529411764730.169
941032AE2-094 E
Adder
7.6070588235294126.466
941031AE2-094 C
Adder
16.9847058823529414.437
934332AD1-057 E
Adder
0.76705882352941180.652
934331AD1-057 C
Adder
1.47294117647058821.252
934321AD1-056 C
Adder
2.642.244
934322AD1-056 E
Adder
1.4317647058823531.217
927022AC1-189 E
Adder
1.59882352941176481.359
925595AC1-034 E
Adder
1.95294117647058821.66
316315AB2-025 C
50/50
0.2520.252
946282AF1-292 E
Adder
0.50.425
944012AF1-069 E
Adder
2.1552941176470591.832
957861AF2-080 C
Adder
2.9152941176470592.478
917512Z2-088 E OP1
Adder
1.88000000000000011.598
961611AG1-000B C
Adder
7.286.188
940541AE2-040 C
50/50
1.7731.773
940481AE2-033 C
50/50
9.8069.806
940482AE2-033 E
50/50
6.6116.611
923263AB1-132 E OP
Adder
2.8364705882352942.411
924312AB2-078 E O1
Adder
0.448235294117647070.381
926274AC1-105 E
Adder
0.860.731
935162AD1-151 E
50/50
6.1926.192
943461AF1-017 C
Adder
0.6317647058823530.537
932596AC2-079 E
Adder
4.2658823529411763.626
316311AC2-079 C
Adder
2.61529411764705882.223
938532AE1-072 E
Adder
2.8635294117647062.434
3146326AYDLETT TAP
Adder
0.424705882352941160.361
917122Z2-027 E
Adder
0.435294117647058830.37
920692AA2-178 E
Adder
1.45294117647058841.235
966622AG1-532 E
Adder
0.452941176470588240.385
922923AB1-081 E OP
Adder
1.45294117647058841.235
925332AB2-190 E
50/50
4.8614.861
927226AC1-216 E
Adder
4.2082352941176473.577
936666AD2-085 E
Adder
2.62823529411764722.234
941591AE2-156 C
Adder
5.6635294117647064.814
944591AF1-124 C
Adder
13.87882352941176711.797
944601AF1-125 C
Adder
13.61647058823529511.574
938771AE1-103 C
Adder
1.1282352941176470.959
3145413WATKINS
Adder
0.271764705882352960.231
960081AF2-299 C
Adder
0.90588235294117650.77
926072AC1-086 E
Adder
4.4364705882352943.771
944011AF1-069 C
Adder
5.5494117647058824.717
963041AG1-153 C
Adder
2.32823529411764741.979
957862AF2-080 E
Adder
1.29176470588235311.098
962562AG1-105 E
Adder
1.93058823529411771.641
944641AF1-129 C
50/50
138.059138.059
316240AF1-291 C
50/50
2.8082.808
924814AB2-134 E
Adder
6.8941176470588245.86
316381AD1-082 C
50/50
0.7750.775
942342AE2-247 E
Adder
0.96470588235294120.82
919152AA1-139 E1
Adder
1.27058823529411781.08
920042AA2-088 E OP
Adder
4.2552941176470593.617
934521AD1-076 C
Adder
4.443.774
934511AD1-075 C
Adder
3.0564705882352942.598
3145723EMPORIA
Adder
0.205882352941176460.175
923573AB1-173 E OP
Adder
1.50588235294117641.28
919692AA2-053 E OP
Adder
1.7835294117647061.516
925785AC1-054 E
Adder
1.32352941176470581.125
316263AC1-034 C
Adder
2.5882352941176472.2
3150781HOPHCF2
50/50
1.6821.682
942001AE2-212 C
50/50
2.3882.388
939192AE1-149 E
50/50
5.125.12
939312AE1-162 E
Adder
0.54941176470588240.467
934065AD1-033 E
Adder
1.53411764705882361.304
937226AE2-253 E
Adder
1.80588235294117651.535
934501AD1-074 C
Adder
12.22470588235294110.391
924517AB2-100 E2
Adder
1.5282352941176471.299
957482AF2-042 E
Adder
12.9811.033
961671AG1-007 C
Adder
0.36235294117647060.308
934621AD1-088 C
Adder
3.18117647058823572.704
935172AD1-152 E
Adder
1.86235294117647051.583
3150761HOPPOLC
50/50
1.0581.058
3145256KINGFORK
Adder
0.33882352941176470.288
925522AC1-027 E
Adder
0.380.323
941102AE2-104 E
Adder
1.98470588235294131.687
957872AF2-081 E
Adder
1.33058823529411761.131
962572AG1-106 E
Adder
0.55176470588235290.469
926214AC1-099 E
Adder
0.484705882352941150.412
932632AC2-084 E
Adder
1.2988235294117651.104
964242AG1-285 E
Adder
2.7964705882352942.377
924162AB2-060 E OP
Adder
1.41882352941176461.206
964792AG1-342 E
Adder
0.76588235294117660.651
3150771HOPHCF1
50/50
1.6821.682
940431AE2-027 C
Adder
5.5282352941176474.699
942002AE2-212 E
50/50
1.5921.592
316132AB2-190 C
50/50
2.4992.499
944581AF1-123 C
Adder
13.82941176470588311.755
3150651CHESTF6
50/50
25.13725.137
946262AF1-291 E
50/50
1.8721.872
934576AD1-082 E
50/50
2.7072.707
944602AF1-125 E
Adder
31.17176470588235326.496
3145506HICKORY
Adder
0.6682352941176470.568
943612AF1-032 E
Adder
0.30705882352941180.261
957871AF2-081 C
Adder
3.10588235294117652.64
940492AE2-034 E
Adder
1.08941176470588250.926
934522AD1-076 E
Adder
2.2623529411764711.923
943172AE2-346 E
Adder
0.238823529411764740.203
918492AA1-063AE OP
Adder
1.7070588235294121.451
962571AG1-106 C
Adder
1.26117647058823531.072
917332KELFORD E
Adder
0.65058823529411770.553
925122AB2-169 E
Adder
2.1235294117647061.805
316274AC1-208 C
Adder
3.6705882352941183.12
917342Z2-044 E
Adder
0.235294117647058850.2
937482AD2-202 E
Adder
0.36941176470588240.314
3151311EDGECMA
Adder
6.0682352941176485.158
939191AE1-149 C
50/50
7.6817.681
3143316POE
50/50
1.2311.231
901082W1-029 E
Adder
10.5541176470588248.971
926206AC1-098 E
Adder
1.4682352941176471.248
964791AG1-342 C
Adder
1.1482352941176470.976
941101AE2-104 C
Adder
1.2482352941176471.061
316141AB2-099 E
Adder
0.098823529411764710.084
316088AB2-174 E
Adder
3.04352941176470632.587
923994AB2-040_E
Adder
2.8235294117647062.4
957481AF2-042 C
Adder
19.4705882352941216.55
961672AG1-007 E
Adder
0.204705882352941150.174
924322AB2-079 E O1
Adder
0.448235294117647070.381
3150801HOPHCF4
50/50
2.5532.553
316349AD2-085 C
Adder
1.61058823529411771.369
935112AD1-144 E
Adder
0.315294117647058840.268
944582AF1-123 E
Adder
31.66823529411764726.918
944592AF1-124 E
Adder
31.78352941176470427.016
923832AB2-022 E
Adder
0.397647058823529460.338
938772AE1-103 E
Adder
1.55882352941176471.325
916042Z1-036 E
Adder
9.7517647058823538.289
960082AF2-299 E
Adder
0.60352941176470590.513
946281AF1-292 C
Adder
0.74941176470588230.637
926071AC1-086 C
Adder
9.7470588235294138.285
963042AG1-153 E
Adder
3.4917647058823532.968
927021AC1-189 C
Adder
3.2094117647058832.728
964241AG1-285 C
Adder
4.1952941176470593.566
924152AB2-059 E OP
Adder
2.0588235294117651.75
962561AG1-105 C
Adder
2.89529411764705862.461
942341AE2-247 C
Adder
0.69882352941176470.594
943462AF1-017 E
Adder
1.03058823529411760.876
958162AF2-110 E
Adder
0.81058823529411760.689
919153AA1-139 E2
Adder
1.27058823529411781.08
934512AD1-075 E
Adder
1.5552941176470591.322
934502AD1-074 E
Adder
6.222352941176475.289
924516AB2-100 E1
Adder
1.5282352941176471.299
918512AA1-065 E OP
Adder
2.12470588235294141.806
966621AG1-532 C
Adder
0.67999999999999990.578
918532AA1-067 E
Adder
0.269411764705882350.229
924022AB2-043 E O1
Adder
1.73764705882352951.477
940432AE2-027 E
Adder
3.68588235294117663.133
934012AD1-025 E
Adder
5.4482352941176474.631
913392Y1-086 E
Adder
0.70470588235294120.599
939411AE1-173 C
Adder
35.0670588235294129.807
3137643SOCKMAN
Adder
0.315294117647058840.268
919710AA2-057 E
Adder
1.58117647058823541.344
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.8981.898
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.93631.936
NYPJM->LTFIMP_NY
CLTF
0.4640.464
LGEELTFEXP_LGEE->PJM
CLTF
0.3190.319
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9850.985
SIGELTFEXP_SIGE->PJM
CLTF
0.0650.065
WECLTFEXP_WEC->PJM
CLTF
0.1690.169
CPLELTFEXP_CPLE->PJM
CLTF
3.9843.984
TVALTFEXP_TVA->PJM
CLTF
1.811.81
O66PJM->LTFIMP_O-066
CMTX_NF
6.2766.276
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.0758.075
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.5166.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.081.08
LAGNLTFEXP_LAGN->PJM
CLTF
2.3232.323

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.85 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:888.27
MW Contribution:15.18
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.9 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:921.81
MW Contribution:14.6
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151211GRAVEL5
80/20
1.1271.127
943461AF1-017 C
80/20
0.6470.647
316311AC2-079 C
80/20
2.6862.686
3150781HOPHCF2
80/20
1.6981.698
942001AE2-212 C
80/20
2.3582.358
3151161SURRY 1
80/20
11.09811.098
934501AD1-074 C
Adder
12.4576470588235310.589
3156073AA1-063SOLA
80/20
0.570.57
3151371ROSEMS1
80/20
0.5510.551
961671AG1-007 C
Adder
0.34588235294117650.294
961611AG1-000B C
80/20
7.6267.626
316236AE1-162 C
80/20
0.1440.144
940541AE2-040 C
80/20
1.6761.676
940481AE2-033 C
80/20
9.2759.275
3151411GASTONB
80/20
1.3541.354
316181AB2-040 GEN
80/20
0.5530.553
3156063AA2-053SOLA
80/20
0.6110.611
3151281ROARAP4
80/20
0.5360.536
3152441Z1-086 ST
80/20
6.6736.673
3152431Z1-086 GT3
80/20
3.8323.832
3152421Z1-086 GT2
80/20
3.8323.832
3150791HOPHCF3
80/20
1.6981.698
316369AC1-216 C
80/20
0.90.9
961941AG1-037 C
Adder
0.196470588235294150.167
3151391GASTONA
80/20
1.3541.354
3151381ROSEMG2
80/20
0.4160.416
941031AE2-094 C
80/20
14.70614.706
934331AD1-057 C
Adder
1.39882352941176481.189
934321AD1-056 C
Adder
2.50705882352941162.131
3150761HOPPOLC
80/20
1.0681.068
933291AC2-141 C
Adder
9.0470588235294127.69
316087AB2-174 C
80/20
0.5210.521
941591AE2-156 C
Adder
6.2764705882352945.335
944591AF1-124 C
Adder
15.47294117647058813.152
944601AF1-125 C
Adder
15.18117647058823612.904
938771AE1-103 C
80/20
1.1561.156
960081AF2-299 C
80/20
0.8560.856
944011AF1-069 C
80/20
4.8054.805
963041AG1-153 C
Adder
2.0188235294117651.716
3150771HOPHCF1
80/20
1.6981.698
940431AE2-027 C
80/20
5.4285.428
316132AB2-190 C
80/20
2.552.55
944581AF1-123 C
Adder
15.41882352941176613.106
941101AE2-104 C
80/20
1.3111.311
3156083AA2-088SOLA
80/20
0.4240.424
313506AB1-173 C OP
80/20
0.4910.491
3151361ROSEMG1
80/20
0.8890.889
957481AF2-042 C
Adder
16.9176470588235314.38
3151171GRAVELC
80/20
0.3880.388
942341AE2-247 C
80/20
0.7150.715
966621AG1-532 C
80/20
0.6420.642
3150651CHESTF6
80/20
25.04225.042
957871AF2-081 C
Adder
3.42823529411764752.914
3151151S HAMPT1
80/20
0.5930.593
962571AG1-106 C
80/20
1.2051.205
316274AC1-208 C
Adder
3.50823529411764762.982
3151311EDGECMA
Adder
5.7282352941176474.869
316033AB2-134 GEN
80/20
1.1791.179
934011AD1-025 C
80/20
1.4591.459
939191AE1-149 C
80/20
7.67.6
316365AB2-100 C1
80/20
0.4810.481
3151041BRUNSWICKG3
80/20
2.9812.981
3151021BRUNSWICKG1
80/20
2.9812.981
316083AB2-161 C
80/20
0.340.34
940641AE2-051 C
80/20
6.3516.351
316336AC2-165 C
Adder
-2.925882352941177-2.487
944641AF1-129 C
80/20
137.537137.537
316240AF1-291 C
80/20
2.7922.792
3151191GRAVEL3
80/20
1.1271.127
316381AD1-082 C
80/20
0.7760.776
934521AD1-076 C
Adder
4.5247058823529423.846
934511AD1-075 C
Adder
3.1141176470588232.647
316011AB1-132 C OP
80/20
1.0341.034
316263AC1-034 C
Adder
2.44235294117647062.076
3150731STONECA
80/20
4.8074.807
935161AD1-151 C
80/20
9.5159.515
3151221GRAVEL6
80/20
1.141.14
3151201GRAVEL4
80/20
1.1421.142
958161AF2-110 C
80/20
0.5350.535
938531AE1-072 C
Adder
6.04588235294117655.139
933981AD1-022 C
Adder
3.26941176470588252.779
3151261ROARAP2
80/20
0.5670.567
3147043LAWRENC
80/20
0.1270.127
3152411Z1-086 GT1
80/20
3.8333.833
3150801HOPHCF4
80/20
2.5782.578
316349AD2-085 C
80/20
1.6511.651
316023AB2-100 C2
80/20
0.4810.481
946281AF1-292 C
80/20
0.7080.708
926071AC1-086 C
80/20
9.3179.317
3151051BRUNSWICKS1
80/20
6.1926.192
927021AC1-189 C
Adder
3.0858823529411772.623
316315AB2-025 C
80/20
0.2380.238
957861AF2-080 C
Adder
2.8035294117647062.383
939411AE1-173 C
80/20
32.73632.736
3137643SOCKMAN
80/20
0.30.3
3151031BRUNSWICKG2
80/20
2.9812.981
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7131.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.64628.646
NYPJM->LTFIMP_NY
CLTF
0.4310.431
LGEELTFEXP_LGEE->PJM
CLTF
0.2740.274
WECLTFEXP_WEC->PJM
CLTF
0.1450.145
SIGELTFEXP_SIGE->PJM
CLTF
0.0560.056
CPLELTFEXP_CPLE->PJM
CLTF
3.5953.595
TVALTFEXP_TVA->PJM
CLTF
1.6011.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.8996.899
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.7315.731
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.9380.938
LAGNLTFEXP_LAGN->PJM
CLTF
2.0572.057

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.77 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:728.5
MW Contribution:12.81
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.54 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:707.05
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151211GRAVEL5
80/20
1.1871.187
943461AF1-017 C
80/20
0.6550.655
316311AC2-079 C
80/20
2.6932.693
3150781HOPHCF2
80/20
2.052.05
942001AE2-212 C
80/20
2.8572.857
3151161SURRY 1
80/20
11.68311.683
940491AE2-034 C
80/20
0.370.37
934501AD1-074 C
80/20
11.00411.004
3156021HOLLOMANSOL
80/20
0.6320.632
3156073AA1-063SOLA
80/20
0.5230.523
3151371ROSEMS1
80/20
0.5190.519
961611AG1-000B C
80/20
8.238.23
316236AE1-162 C
80/20
0.1430.143
316375AC2-012 C
80/20
0.4130.413
940541AE2-040 C
80/20
1.7111.711
940481AE2-033 C
80/20
9.4279.427
3151411GASTONB
80/20
1.2821.282
316181AB2-040 GEN
80/20
0.520.52
3156063AA2-053SOLA
80/20
0.560.56
3151281ROARAP4
80/20
0.4930.493
3150791HOPHCF3
80/20
2.052.05
316369AC1-216 C
80/20
1.0251.025
943171AE2-346 C
80/20
0.0790.079
961941AG1-037 C
80/20
0.1780.178
3151391GASTONA
80/20
1.2821.282
3151381ROSEMG2
80/20
0.3920.392
934331AD1-057 C
80/20
1.2741.274
934321AD1-056 C
80/20
2.2852.285
3150761HOPPOLC
80/20
1.2891.289
316305AF2-043 C
80/20
0.1080.108
316087AB2-174 C
80/20
0.4920.492
941591AE2-156 C
Adder
5.457647058823534.639
944591AF1-124 C
Adder
13.0623529411764711.103
944601AF1-125 C
Adder
12.8152941176470610.893
938771AE1-103 C
80/20
1.0631.063
960081AF2-299 C
80/20
0.8180.818
3150771HOPHCF1
80/20
2.052.05
940431AE2-027 C
80/20
6.666.66
316132AB2-190 C
80/20
2.9822.982
944581AF1-123 C
Adder
13.0152941176470611.063
941101AE2-104 C
80/20
1.2091.209
3156083AA2-088SOLA
80/20
0.3880.388
313506AB1-173 C OP
80/20
0.4620.462
3151361ROSEMG1
80/20
0.8370.837
3151171GRAVELC
80/20
0.4080.408
942341AE2-247 C
80/20
0.7240.724
316246AF1-032 C
80/20
0.0890.089
966621AG1-532 C
80/20
0.6130.613
3150651CHESTF6
80/20
31.16731.167
957871AF2-081 C
Adder
2.91294117647058842.476
3151151S HAMPT1
80/20
0.5450.545
962571AG1-106 C
80/20
1.1411.141
932631AC2-084 C
80/20
0.3490.349
316274AC1-208 C
80/20
3.1613.161
316033AB2-134 GEN
80/20
1.3431.343
934011AD1-025 C
80/20
1.6611.661
939191AE1-149 C
80/20
8.6748.674
316365AB2-100 C1
80/20
0.4730.473
316318V4-068 C
80/20
0.0290.029
316210AC1-098 C
80/20
0.3280.328
316083AB2-161 C
80/20
0.3740.374
316072AD1-144 C
80/20
0.0920.092
944641AF1-129 C
80/20
171.179171.179
316240AF1-291 C
80/20
3.4573.457
3151191GRAVEL3
80/20
1.1871.187
316381AD1-082 C
80/20
0.8530.853
934521AD1-076 C
80/20
3.9963.996
934511AD1-075 C
80/20
2.7512.751
316011AB1-132 C OP
80/20
0.9790.979
3150731STONECA
80/20
5.8035.803
935161AD1-151 C
80/20
10.99910.999
3151221GRAVEL6
80/20
1.2011.201
3151201GRAVEL4
80/20
1.2021.202
958161AF2-110 C
80/20
0.4930.493
938531AE1-072 C
Adder
5.1458823529411764.374
315614AA2-178 C
80/20
0.5030.503
933981AD1-022 C
80/20
2.92.9
3151261ROARAP2
80/20
0.5210.521
3147043LAWRENC
80/20
0.1170.117
3150801HOPHCF4
80/20
3.1113.111
316349AD2-085 C
80/20
1.6711.671
316023AB2-100 C2
80/20
0.4730.473
316315AB2-025 C
80/20
0.2430.243
946281AF1-292 C
80/20
0.6770.677
926071AC1-086 C
80/20
8.8218.821
316317KELFORD C
80/20
0.1250.125
316140AB2-099 C
80/20
0.0340.034
3137643SOCKMAN
80/20
0.2790.279
316212AC1-099 C
80/20
0.110.11
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3561.356
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.36622.366
NYPJM->LTFIMP_NY
CLTF
0.3360.336
LGEELTFEXP_LGEE->PJM
CLTF
0.1940.194
SIGELTFEXP_SIGE->PJM
CLTF
0.040.04
WECLTFEXP_WEC->PJM
CLTF
0.1020.102
CPLELTFEXP_CPLE->PJM
CLTF
2.8462.846
TVALTFEXP_TVA->PJM
CLTF
1.211.21
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.844.84
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.2794.279
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.6820.682
LAGNLTFEXP_LAGN->PJM
CLTF
1.5581.558

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: H2T557_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.14 %
Rating:1065.0 MVA
Rating Type:C
MVA to Mitigate:1407.28
MW Contribution:116.3
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: H2T557_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.17 %
Rating:1065.0 MVA
Rating Type:C
MVA to Mitigate:1780.31
MW Contribution:134.71
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926412AC1-112 E
50/50
1.5121.512
3150681DARBY 2
50/50
3.2633.263
934781AD1-105 C
50/50
1.5491.549
942341AE2-247 C
Adder
1.25176470588235311.064
943462AF1-017 E
Adder
1.8482352941176471.571
958162AF2-110 E
Adder
1.74470588235294131.483
919153AA1-139 E2
Adder
3.21764705882352952.735
934512AD1-075 E
Adder
3.10117647058823562.636
934502AD1-074 E
Adder
12.40352941176470510.543
924516AB2-100 E1
Adder
2.0282352941176471.724
918512AA1-065 E OP
Adder
3.88823529411764753.305
940642AE2-051 E
Adder
7.3317647058823536.232
966621AG1-532 C
Adder
0.94117647058823540.8
963612AG1-210 E
Adder
0.95647058823529410.813
3150441FOUR RIVERB
50/50
4.1244.124
3150651CHESTF6
Adder
20.39176470588235217.333
946262AF1-291 E
Adder
1.54705882352941181.315
3130536PAPERMILL
Adder
6.6941176470588245.69
939602AE1-190 E
Adder
1.41058823529411771.199
934576AD1-082 E
Adder
3.94470588235294173.353
933292AC2-141 E
Adder
10.1388235294117658.618
944602AF1-125 E
Adder
80.9447058823529368.803
3145506HICKORY
Adder
1.7235294117647061.465
943612AF1-032 E
Adder
0.73411764705882350.624
957871AF2-081 C
Adder
7.8682352941176476.688
936591AD2-074 C
Adder
5.3811764705882354.574
940492AE2-034 E
Adder
2.2764705882352941.935
934522AD1-076 E
Adder
4.5105882352941183.834
943172AE2-346 E
Adder
0.42235294117647060.359
918492AA1-063AE OP
Adder
2.78000000000000022.363
962571AG1-106 C
Adder
1.83294117647058831.558
3150701DARBY 4
50/50
3.2783.278
3150731STONECA
Adder
7.29647058823529456.202
935161AD1-151 C
Adder
16.05058823529411813.643
932046AC2-012 E
Adder
10.5517647058823528.969
958161AF2-110 C
Adder
1.09647058823529430.932
938531AE1-072 C
Adder
13.81411764705882611.742
3145393UNCAMP
Adder
4.6082352941176473.917
933981AD1-022 C
Adder
6.2894117647058835.346
900672V4-068 E
Adder
0.25294117647058820.215
926785AC1-164_E
Adder
19.72000000000000216.762
943471AF1-018 C
Adder
7.1435294117647066.072
316084AB2-161 E
Adder
4.9517647058823524.209
3145946PLYMOUTH TP
Adder
0.234117647058823540.199
933982AD1-022 E
Adder
3.4235294117647062.91
940641AE2-051 C
Adder
10.9988235294117669.349
926472AC1-118 E
Adder
0.95294117647058830.81
930122AB1-027 E
50/50
1.8591.859
316169AC1-164 GEN
Adder
43.8917647058823537.308
316349AD2-085 C
Adder
2.8882352941176472.455
935112AD1-144 E
Adder
0.77529411764705890.659
944582AF1-123 E
Adder
82.2352941176470769.9
944592AF1-124 E
Adder
82.532941176470670.153
923832AB2-022 E
Adder
0.96823529411764710.823
938772AE1-103 E
Adder
3.09647058823529432.632
916042Z1-036 E
Adder
21.6647058823529418.415
960082AF2-299 E
Adder
0.83647058823529410.711
946281AF1-292 C
Adder
1.03882352941176470.883
926071AC1-086 C
Adder
14.17176470588235312.046
957971AF2-091 C
Adder
1.66117647058823531.412
939261AE1-157 C
Adder
9.7317647058823548.272
966882AG1-559 E
Adder
1.02588235294117650.872
966872AG1-558 E
50/50
1.7921.792
966871AG1-558 C
50/50
3.5563.556
316076AC2-137 E
Adder
1.54705882352941181.315
3150841SPRUNCB
Adder
10.1282352941176488.609
3150831SPRUNCA
Adder
10.1282352941176488.609
923842AB2-024 E
Adder
1.81529411764705871.543
316157AD2-030 E
Adder
1.1635294117647060.989
926662AC1-147 E
Adder
1.06705882352941180.907
916192Z1-068 E
Adder
1.50117647058823531.276
957492AF2-043 E
Adder
1.12941176470588230.96
923852AB2-025 E
Adder
0.86235294117647050.733
939412AE1-173 E
Adder
40.66352941176470634.564
964211AG1-282 C
Adder
1.95411764705882351.661
961942AG1-037 E
Adder
0.235294117647058850.2
961941AG1-037 C
Adder
0.352941176470588260.3
941032AE2-094 E
Adder
10.4941176470588248.92
941031AE2-094 C
Adder
23.43176470588235519.917
316312AB1-027 C
50/50
0.7090.709
944631AF1-128 C
Adder
44.20941176470588437.578
938552AE1-074 E
Adder
1.21058823529411751.029
316160AE1-175 E
Adder
1.14588235294117660.974
3150921YORKTN3
Adder
107.5905882352941291.452
934782AD1-105 E
50/50
6.4256.425
3145256KINGFORK
Adder
0.83411764705882350.709
925522AC1-027 E
Adder
0.97294117647058820.827
933291AC2-141 C
Adder
23.7529411764705920.19
926755AC1-161 E
Adder
10.1388235294117658.618
941102AE2-104 E
Adder
4.2741176470588243.633
957872AF2-081 E
Adder
3.3717647058823532.866
936592AD2-074 E
Adder
8.7800000000000017.463
962572AG1-106 E
Adder
0.80235294117647070.682
3150431FOUR RIVERA
50/50
4.1244.124
925865AC1-065 E
Adder
16.6414.144
961951AG1-038 C
Adder
3.1117647058823532.645
961952AG1-038 E
Adder
4.297647058823533.653
946282AF1-292 E
Adder
0.69294117647058820.589
936582AD2-073 E
Adder
0.99294117647058820.844
939262AE1-157 E
Adder
5.2788235294117654.487
315051AA1-145 CT1
50/50
6.5696.569
927041AC1-191 C
50/50
14.27914.279
3142366NRTHEST
50/50
0.2420.242
3138116ELKO L286
Adder
1.61294117647058831.371
961611AG1-000B C
Adder
14.80117647058823512.581
940541AE2-040 C
Adder
2.13058823529411741.811
940481AE2-033 C
Adder
11.9247058823529410.136
940482AE2-033 E
Adder
8.0388235294117656.833
923263AB1-132 E OP
Adder
4.1247058823529413.506
963611AG1-210 C
Adder
0.63764705882352950.542
3150601CHESTF5
Adder
70.6552941176470660.057
925332AB2-190 E
Adder
8.1470588235294116.925
927226AC1-216 E
Adder
7.5517647058823536.419
962962AG1-145 E
Adder
1.38941176470588231.181
936666AD2-085 E
Adder
4.7117647058823534.005
941591AE2-156 C
Adder
14.40941176470588112.248
944591AF1-124 C
Adder
36.0430.634
944601AF1-125 C
Adder
35.35882352941176530.055
938771AE1-103 C
Adder
2.24235294117647041.906
3145413WATKINS
Adder
0.51529411764705880.438
964212AG1-282 E
Adder
1.30235294117647071.107
960081AF2-299 C
Adder
1.2552941176470591.067
926072AC1-086 E
Adder
6.4505882352941175.483
944011AF1-069 C
Adder
4.4164705882352953.754
966881AG1-559 C
Adder
2.03647058823529431.731
3150481FOUR RIVERF
50/50
4.9634.963
927042AC1-191 E
50/50
7.1137.113
3150691DARBY 3
50/50
3.2743.274
935162AD1-151 E
Adder
10.7000000000000019.095
316233AE1-074 C
Adder
2.40235294117647062.042
940551AE2-041 C
Adder
7.1435294117647066.072
957832AF2-077 E
Adder
1.33764705882352941.137
943461AF1-017 C
Adder
1.13294117647058810.963
932596AC2-079 E
Adder
7.8070588235294126.636
316311AC2-079 C
Adder
4.7847058823529424.067
938532AE1-072 E
Adder
7.2011764705882366.121
3146326AYDLETT TAP
Adder
1.06588235294117650.906
917122Z2-027 E
Adder
1.04588235294117650.889
920692AA2-178 E
Adder
3.0352941176470592.58
966622AG1-532 E
Adder
0.62705882352941180.533
3142296MT RD221
50/50
0.1860.186
316004AC1-112 C
50/50
0.4420.442
942001AE2-212 C
Adder
2.1905882352941181.862
3150501FOURRIVERG
50/50
6.2846.284
939192AE1-149 E
Adder
6.6870588235294125.684
939312AE1-162 E
Adder
1.24705882352941181.06
934065AD1-033 E
Adder
3.9752941176470593.379
937226AE2-253 E
Adder
4.6070588235294123.916
943741AF1-042 C
Adder
2.81529411764705852.393
934501AD1-074 C
Adder
24.36705882352941220.712
962861AG1-135 C
Adder
5.8517647058823544.974
924517AB2-100 E2
Adder
2.0282352941176471.724
3141813NORNECK
Adder
0.84941176470588230.722
944641AF1-129 C
Adder
111.9952941176470695.196
316240AF1-291 C
Adder
2.32117647058823541.973
924814AB2-134 E
Adder
12.37058823529411810.515
942342AE2-247 E
Adder
1.7282352941176471.469
919152AA1-139 E1
Adder
3.21764705882352952.735
920042AA2-088 E OP
Adder
7.6305882352941186.486
934521AD1-076 C
Adder
8.8494117647058837.522
934511AD1-075 C
Adder
6.0917647058823535.178
939246AE1-155 E
Adder
8.3858823529411777.128
3145723EMPORIA
Adder
0.289411764705882370.246
923573AB1-173 E OP
Adder
2.1847058823529411.857
957972AF2-091 E
Adder
2.29411764705882341.95
940431AE2-027 C
Adder
13.56705882352941311.532
942002AE2-212 E
Adder
1.46000000000000021.241
934392AD1-063 E
Adder
1.0717647058823530.911
944581AF1-123 C
Adder
35.91176470588235530.525
941101AE2-104 C
Adder
2.68823529411764732.285
943742AF1-042 E
Adder
4.5941176470588233.905
962862AG1-135 E
Adder
3.9011764705882353.316
966662AG1-536 E
Adder
6.9611764705882355.917
316141AB2-099 E
Adder
0.176470588235294130.15
316088AB2-174 E
Adder
4.3517647058823533.699
923994AB2-040_E
Adder
4.0952941176470593.481
944492AF1-114 E
Adder
6.7482352941176475.736
3150461FOUR RIVERD
50/50
4.0644.064
939191AE1-149 C
Adder
10.0305882352941188.526
3143316POE
Adder
1.24941176470588241.062
934146AD1-041 E
Adder
3.52588235294117652.997
957601AF2-054 C
Adder
2.07411764705882361.763
901082W1-029 E
Adder
24.7470588235294121.035
958261AF2-120 C
Adder
6.0223529411764715.119
3150451FOUR RIVERC
50/50
5.0385.038
3150471FOUR RIVERE
50/50
4.0644.064
315052AA1-145 CT2
50/50
6.5666.566
3150671DARBY 1
50/50
3.2593.259
940432AE2-027 E
Adder
9.0447058823529417.688
934012AD1-025 E
Adder
9.777647058823538.311
939612AE1-191 E
Adder
5.6423529411764714.796
957602AF2-054 E
Adder
1.38235294117647081.175
913392Y1-086 E
Adder
1.71647058823529421.459
939411AE1-173 C
Adder
60.99529411764705651.846
958262AF2-120 E
Adder
4.0152941176470593.413
966661AG1-536 C
Adder
5.184.403
316078AC2-138 E
Adder
0.89294117647058820.759
944491AF1-114 C
Adder
4.88705882352941154.154
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.6452.645
CBM South 2LTFEXP_CBM-S2->PJM
CBM
41.47141.471
NYPJM->LTFIMP_NY
CLTF
0.8060.806
G-007PJM->LTFIMP_G-007
CMTX_NF
1.5811.581
SIGELTFEXP_SIGE->PJM
CLTF
0.0090.009
CPLELTFEXP_CPLE->PJM
CLTF
5.5585.558
TVALTFEXP_TVA->PJM
CLTF
1.5691.569
O66PJM->LTFIMP_O-066
CMTX_NF
10.11910.119
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.3964.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0520.052
MECLTFEXP_MEC->PJM
CLTF
0.2980.298
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.1280.128
LAGNLTFEXP_LAGN->PJM
CLTF
2.0762.076

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P4-2: 224022-1_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 224022-1_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.91 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1211.04
MW Contribution:221.77
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944602AF1-125 E
50/50
154.345154.345
3145506HICKORY
50/50
3.183.18
957871AF2-081 C
50/50
12.76912.769
901082W1-029 E
Adder
11.6788235294117649.927
938532AE1-072 E
50/50
11.02911.029
3146326AYDLETT TAP
50/50
1.5961.596
917122Z2-027 E
50/50
0.9950.995
957872AF2-081 E
50/50
5.4725.472
313526AB2-022 C
50/50
0.3340.334
944591AF1-124 C
50/50
68.72168.721
944601AF1-125 C
50/50
67.42367.423
919152AA1-139 E1
50/50
5.2215.221
316018AA1-139 ULT2
50/50
1.3821.382
937226AE2-253 E
50/50
7.8747.874
316321Z2-027 C
50/50
0.2690.269
316017AA1-139 ULT1
50/50
1.3821.382
938531AE1-072 C
50/50
21.15821.158
944582AF1-123 E
50/50
156.806156.806
944592AF1-124 E
50/50
157.374157.374
923832AB2-022 E
50/50
1.11.1
916042Z1-036 E
Adder
10.5388235294117658.958
944581AF1-123 C
50/50
68.47768.477
316320Y1-086 C
50/50
0.1950.195
913392Y1-086 E
50/50
1.9491.949
316388AE2-253 GEN
50/50
2.6482.648
919153AA1-139 E2
50/50
5.2215.221
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.110.11
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.1422.142
LGEELTFEXP_LGEE->PJM
CLTF
0.0670.067
VTFLTFEXP_VFT->PJM
CMTX
0.3620.362
SIGELTFEXP_SIGE->PJM
CLTF
0.0120.012
WECLTFEXP_WEC->PJM
CLTF
0.0370.037
G-007ALTFEXP_G-007A->PJM
CMTX
0.1340.134
CPLELTFEXP_CPLE->PJM
CLTF
0.2290.229
TVALTFEXP_TVA->PJM
CLTF
0.1990.199
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0780.078
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.8761.876
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.8560.856
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.1890.189
LAGNLTFEXP_LAGN->PJM
CLTF
0.2510.251

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P4-2: 224022-2_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 224022-2_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.75 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1209.69
MW Contribution:221.56
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944602AF1-125 E
50/50
154.201154.201
3145506HICKORY
50/50
3.1773.177
957871AF2-081 C
50/50
12.75612.756
901082W1-029 E
Adder
11.6588235294117669.91
938532AE1-072 E
50/50
11.01811.018
3146326AYDLETT TAP
50/50
1.5941.594
917122Z2-027 E
50/50
0.9940.994
957872AF2-081 E
50/50
5.4675.467
313526AB2-022 C
50/50
0.3340.334
944591AF1-124 C
50/50
68.65768.657
944601AF1-125 C
50/50
67.3667.36
919152AA1-139 E1
50/50
5.2165.216
316018AA1-139 ULT2
50/50
1.3811.381
937226AE2-253 E
50/50
7.8667.866
316321Z2-027 C
50/50
0.2690.269
316017AA1-139 ULT1
50/50
1.3811.381
938531AE1-072 C
50/50
21.13621.136
944582AF1-123 E
50/50
156.659156.659
944592AF1-124 E
50/50
157.227157.227
923832AB2-022 E
50/50
1.0991.099
916042Z1-036 E
Adder
10.5223529411764728.944
944581AF1-123 C
50/50
68.41368.413
316320Y1-086 C
50/50
0.1950.195
913392Y1-086 E
50/50
1.9471.947
316388AE2-253 GEN
50/50
2.6452.645
919153AA1-139 E2
50/50
5.2165.216
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.1090.109
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.1392.139
LGEELTFEXP_LGEE->PJM
CLTF
0.0670.067
VTFLTFEXP_VFT->PJM
CMTX
0.3620.362
SIGELTFEXP_SIGE->PJM
CLTF
0.0120.012
WECLTFEXP_WEC->PJM
CLTF
0.0370.037
G-007ALTFEXP_G-007A->PJM
CMTX
0.1340.134
CPLELTFEXP_CPLE->PJM
CLTF
0.2280.228
TVALTFEXP_TVA->PJM
CLTF
0.1990.199
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0790.079
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.8761.876
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.8550.855
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.1880.188
LAGNLTFEXP_LAGN->PJM
CLTF
0.2510.251

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 271_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 271_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.49 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:729.5
MW Contribution:63.02
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957871AF2-081 C
80/20
11.88711.887
3156056W1-029WIND
80/20
0.2510.251
313526AB2-022 C
80/20
0.3080.308
316018AA1-139 ULT2
80/20
1.2871.287
944591AF1-124 C
80/20
64.23364.233
944601AF1-125 C
80/20
63.0263.02
316321Z2-027 C
80/20
0.2470.247
316017AA1-139 ULT1
80/20
1.2871.287
938531AE1-072 C
80/20
19.67219.672
316185AD1-033 C
80/20
1.7471.747
944581AF1-123 C
80/20
64.00664.006
316320Y1-086 C
80/20
0.180.18
3156116Z1-036WIND
80/20
0.2150.215
316388AE2-253 GEN
80/20
2.4682.468
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0890.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.8161.816
LGEELTFEXP_LGEE->PJM
CLTF
0.0590.059
VTFLTFEXP_VFT->PJM
CMTX
0.3330.333
SIGELTFEXP_SIGE->PJM
CLTF
0.0110.011
WECLTFEXP_WEC->PJM
CLTF
0.0330.033
G-007ALTFEXP_G-007A->PJM
CMTX
0.1240.124
CPLELTFEXP_CPLE->PJM
CLTF
0.1870.187
TVALTFEXP_TVA->PJM
CLTF
0.1740.174
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0720.072
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.6591.659
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.7490.749
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.1660.166
LAGNLTFEXP_LAGN->PJM
CLTF
0.2190.219

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2240_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2240_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.51 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:709.27
MW Contribution:63.05
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3156056W1-029WIND
80/20
0.2510.251
316321Z2-027 C
80/20
0.2470.247
313526AB2-022 C
80/20
0.3080.308
944591AF1-124 C
80/20
64.26664.266
944601AF1-125 C
80/20
63.05263.052
944581AF1-123 C
80/20
64.03864.038
316320Y1-086 C
80/20
0.180.18
316388AE2-253 GEN
80/20
2.4692.469
957871AF2-081 C
80/20
11.89411.894
316018AA1-139 ULT2
80/20
1.2881.288
316017AA1-139 ULT1
80/20
1.2881.288
938531AE1-072 C
80/20
19.68519.685
3156116Z1-036WIND
80/20
0.2160.216
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0950.095
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.9451.945
LGEELTFEXP_LGEE->PJM
CLTF
0.0670.067
WECLTFEXP_WEC->PJM
CLTF
0.0370.037
VTFLTFEXP_VFT->PJM
CMTX
0.4150.415
SIGELTFEXP_SIGE->PJM
CLTF
0.0120.012
G-007ALTFEXP_G-007A->PJM
CMTX
0.1540.154
CPLELTFEXP_CPLE->PJM
CLTF
0.1990.199
TVALTFEXP_TVA->PJM
CLTF
0.1910.191
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0880.088
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.8721.872
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.8320.832
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.1860.186
LAGNLTFEXP_LAGN->PJM
CLTF
0.2410.241

Details for 6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: H2T574_SRT-S_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.99 %
Rating:1031.0 MVA
Rating Type:C
MVA to Mitigate:1391.73
MW Contribution:69.2
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150441FOUR RIVERB
50/50
3.823.82
3150651CHESTF6
Adder
11.81411764705882410.042
946262AF1-291 E
Adder
0.89529411764705890.761
3130536PAPERMILL
Adder
4.4917647058823533.818
939602AE1-190 E
Adder
0.95764705882352940.814
934576AD1-082 E
Adder
2.3047058823529411.959
933292AC2-141 E
Adder
6.0694117647058825.159
944602AF1-125 E
Adder
48.1588235294117740.935
3145506HICKORY
Adder
1.02470588235294110.871
943612AF1-032 E
Adder
0.43647058823529410.371
957871AF2-081 C
Adder
4.6800000000000013.978
936591AD2-074 C
Adder
4.0976470588235293.483
926785AC1-164_E
Adder
12.38352941176470510.526
943471AF1-018 C
Adder
4.8258823529411774.102
316084AB2-161 E
Adder
2.89176470588235322.458
926472AC1-118 E
Adder
0.93294117647058830.793
3150481FOUR RIVERF
50/50
4.5984.598
927042AC1-191 E
50/50
4.3364.336
935162AD1-151 E
Adder
6.3635294117647065.409
316233AE1-074 C
Adder
1.32470588235294121.126
940551AE2-041 C
Adder
4.8258823529411774.102
957832AF2-077 E
Adder
0.87647058823529410.745
943461AF1-017 C
Adder
0.66705882352941170.567
932596AC2-079 E
Adder
4.6035294117647063.913
316311AC2-079 C
Adder
2.82235294117647052.399
938532AE1-072 E
Adder
4.2835294117647063.641
3146326AYDLETT TAP
Adder
0.63411764705882360.539
917122Z2-027 E
Adder
0.62117647058823530.528
3150381LDYSMT2
50/50
9.9319.931
944631AF1-128 C
Adder
26.61176470588235422.62
938552AE1-074 E
Adder
0.66705882352941170.567
316160AE1-175 E
Adder
0.71882352941176480.611
3150921YORKTN3
Adder
67.1576470588235357.084
934782AD1-105 E
50/50
4.8864.886
3145256KINGFORK
Adder
0.49882352941176470.424
925522AC1-027 E
Adder
0.57882352941176470.492
933291AC2-141 C
Adder
14.21882352941176512.086
926755AC1-161 E
Adder
6.0694117647058825.159
941102AE2-104 E
Adder
2.53411764705882362.154
957872AF2-081 E
Adder
2.00588235294117641.705
936592AD2-074 E
Adder
6.6858823529411765.683
3150411LDYSMT5
50/50
10.24410.244
315051AA1-145 CT1
50/50
6.0866.086
927041AC1-191 C
50/50
8.7048.704
3138116ELKO L286
Adder
0.98705882352941180.839
961611AG1-000B C
Adder
8.8552941176470597.527
963611AG1-210 C
Adder
0.51647058823529410.439
3150371LDYSMT1
50/50
9.8049.804
3150431FOUR RIVERA
50/50
3.823.82
925865AC1-065 E
Adder
11.2164705882352949.534
961951AG1-038 C
Adder
2.37058823529411772.015
961952AG1-038 E
Adder
3.27294117647058822.782
936582AD2-073 E
Adder
0.880.748
939262AE1-157 E
50/50
14.45514.455
3150601CHESTF5
Adder
42.53058823529412536.151
925332AB2-190 E
Adder
4.8388235294117664.113
927226AC1-216 E
Adder
4.497647058823533.823
962962AG1-145 E
Adder
0.87058823529411770.74
936666AD2-085 E
Adder
2.7764705882352942.36
941591AE2-156 C
Adder
8.587.293
944591AF1-124 C
Adder
21.4423529411764718.226
944601AF1-125 C
Adder
21.0376470588235317.882
944641AF1-129 C
Adder
64.8858823529411855.153
316240AF1-291 C
Adder
1.34352941176470591.142
924814AB2-134 E
Adder
7.3670588235294126.262
942342AE2-247 E
Adder
1.01882352941176470.866
919152AA1-139 E1
Adder
1.91411764705882351.627
939246AE1-155 E
Adder
6.5952941176470595.606
957972AF2-091 E
Adder
2.8811764705882352.449
964212AG1-282 E
Adder
1.02941176470588250.875
966881AG1-559 C
50/50
4.1864.186
966872AG1-558 E
50/50
1.0921.092
966871AG1-558 C
50/50
2.1682.168
316076AC2-137 E
Adder
0.94588235294117650.804
3150841SPRUNCB
Adder
5.78235294117647054.915
3150831SPRUNCA
Adder
5.78235294117647054.915
923842AB2-024 E
Adder
1.21529411764705891.033
316157AD2-030 E
Adder
0.79764705882352950.678
926662AC1-147 E
Adder
0.63529411764705890.54
916192Z1-068 E
Adder
0.89294117647058820.759
957492AF2-043 E
Adder
0.67176470588235290.571
964211AG1-282 C
Adder
1.54470588235294121.313
957191AF2-013 C
Adder
15.57176470588235313.236
3141316ARNOLDS
50/50
0.2260.226
3142296MT RD221
50/50
0.1070.107
942001AE2-212 C
Adder
1.26117647058823531.072
3150501FOURRIVERG
50/50
4.5754.575
939192AE1-149 E
Adder
3.88470588235294123.302
939312AE1-162 E
Adder
0.74588235294117660.634
934065AD1-033 E
Adder
2.36588235294117682.011
937226AE2-253 E
Adder
2.742.329
943741AF1-042 C
Adder
2.1447058823529411.823
962861AG1-135 C
Adder
4.5670588235294123.882
3141813NORNECK
Adder
0.68705882352941170.584
3150731STONECA
Adder
4.3176470588235293.67
935161AD1-151 C
Adder
9.5447058823529418.113
932046AC2-012 E
Adder
6.28352941176470655.341
958161AF2-110 C
Adder
0.65058823529411770.553
938531AE1-072 C
Adder
8.2164705882352946.984
930122AB1-027 E
Adder
1.10941176470588230.943
316169AC1-164 GEN
Adder
27.56470588235294323.43
316349AD2-085 C
Adder
1.70235294117647061.447
935112AD1-144 E
Adder
0.46352941176470590.394
944582AF1-123 E
Adder
48.92705882352941441.588
944592AF1-124 E
Adder
49.10352941176470441.738
923832AB2-022 E
Adder
0.57647058823529410.49
957971AF2-091 C
Adder
2.08705882352941161.774
3150391LDYSMT3
50/50
10.19310.193
939261AE1-157 C
50/50
26.64926.649
966882AG1-559 E
50/50
2.1092.109
3150461FOUR RIVERD
50/50
3.7653.765
939191AE1-149 C
Adder
5.8258823529411774.952
3143316POE
Adder
0.71411764705882350.607
934146AD1-041 E
Adder
2.3952941176470592.036
957601AF2-054 C
Adder
1.42235294117647081.209
958261AF2-120 C
Adder
4.7364705882352944.026
3150401LDYSMT4
50/50
10.21110.211
940431AE2-027 C
Adder
7.917647058823536.73
942002AE2-212 E
Adder
0.84117647058823530.715
934392AD1-063 E
Adder
0.72352941176470590.615
944581AF1-123 C
Adder
21.36588235294117818.161
941101AE2-104 C
Adder
1.59411764705882361.355
943742AF1-042 E
Adder
3.4988235294117652.974
962862AG1-135 E
Adder
3.04470588235294142.588
966662AG1-536 E
Adder
5.4752941176470594.654
944492AF1-114 E
Adder
8.4752941176470587.204
3150451FOUR RIVERC
50/50
4.6684.668
3150471FOUR RIVERE
50/50
3.7653.765
315052AA1-145 CT2
50/50
6.0836.083
940432AE2-027 E
Adder
5.2776470588235294.486
934012AD1-025 E
Adder
5.82352941176470654.95
939612AE1-191 E
Adder
3.8317647058823533.257
957602AF2-054 E
Adder
0.94823529411764720.806
913392Y1-086 E
Adder
1.020.867
958262AF2-120 E
Adder
3.15764705882352952.684
966661AG1-536 C
Adder
4.0741176470588243.463
316078AC2-138 E
Adder
0.72235294117647060.614
944491AF1-114 C
Adder
6.13764705882352955.217
3150331BIRCHWDA
50/50
33.12333.123
926412AC1-112 E
Adder
0.90235294117647060.767
934781AD1-105 C
50/50
1.1781.178
942341AE2-247 C
Adder
0.73764705882352940.627
943462AF1-017 E
Adder
1.08941176470588250.926
958162AF2-110 E
Adder
1.0352941176470590.88
919153AA1-139 E2
Adder
1.91411764705882351.627
963612AG1-210 E
Adder
0.77411764705882360.658
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6281.628
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.18327.183
NYPJM->LTFIMP_NY
CLTF
0.920.92
LGEELTFEXP_LGEE->PJM
CLTF
0.1870.187
G-007PJM->LTFIMP_G-007
CMTX_NF
1.9371.937
SIGELTFEXP_SIGE->PJM
CLTF
0.040.04
WECLTFEXP_WEC->PJM
CLTF
0.0880.088
CPLELTFEXP_CPLE->PJM
CLTF
3.4193.419
TVALTFEXP_TVA->PJM
CLTF
1.4341.434
O66PJM->LTFIMP_O-066
CMTX_NF
12.34612.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.7883.788
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.7974.797
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.6820.682
LAGNLTFEXP_LAGN->PJM
CLTF
1.8271.827

Details for 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2110T2128_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2110T2128_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.86 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1019.7
MW Contribution:127.07
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2110T2128_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.8 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:844.95
MW Contribution:76.07
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316388AE2-253 GEN
50/50
1.5561.556
919153AA1-139 E2
50/50
3.1053.105
944602AF1-125 E
50/50
88.43888.438
3145506HICKORY
50/50
1.8381.838
957871AF2-081 C
50/50
7.5937.593
316017AA1-139 ULT1
50/50
0.8220.822
938531AE1-072 C
50/50
12.75712.757
944582AF1-123 E
50/50
89.84889.848
944592AF1-124 E
50/50
90.17490.174
923832AB2-022 E
50/50
0.720.72
916042Z1-036 E
Adder
9.4541176470588238.036
957872AF2-081 E
50/50
3.2543.254
313526AB2-022 C
50/50
0.2190.219
944591AF1-124 C
50/50
39.37639.376
944601AF1-125 C
50/50
38.63338.633
938532AE1-072 E
50/50
6.656.65
3146326AYDLETT TAP
50/50
0.9670.967
917122Z2-027 E
Adder
0.68941176470588230.586
934065AD1-033 E
50/50
6.1486.148
937226AE2-253 E
50/50
4.6274.627
919152AA1-139 E1
50/50
3.1053.105
316018AA1-139 ULT2
50/50
0.8220.822
316185AD1-033 C
50/50
1.5071.507
944581AF1-123 C
50/50
39.23739.237
316320Y1-086 C
50/50
0.1280.128
901082W1-029 E
Adder
10.9882352941176479.34
913392Y1-086 E
50/50
1.2751.275
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.2270.227
LGEELTFEXP_LGEE->PJM
CLTF
0.0820.082
WECLTFEXP_WEC->PJM
CLTF
0.0450.045
VTFLTFEXP_VFT->PJM
CMTX
0.0910.091
SIGELTFEXP_SIGE->PJM
CLTF
0.0150.015
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.8453.845
G-007ALTFEXP_G-007A->PJM
CMTX
0.0330.033
CPLELTFEXP_CPLE->PJM
CLTF
0.4750.475
TVALTFEXP_TVA->PJM
CLTF
0.2870.287
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0290.029
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.2612.261
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.1721.172
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.240.24
LAGNLTFEXP_LAGN->PJM
CLTF
0.3650.365

Details for 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P4-2: 212822_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 212822_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.29 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:998.4
MW Contribution:157.15
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316017AA1-139 ULT1
50/50
0.9850.985
938531AE1-072 C
50/50
15.10215.102
313526AB2-022 C
50/50
0.2410.241
938532AE1-072 E
50/50
7.8727.872
3146326AYDLETT TAP
50/50
1.141.14
917122Z2-027 E
Adder
0.72470588235294120.616
944591AF1-124 C
50/50
48.69848.698
944601AF1-125 C
50/50
47.77847.778
919152AA1-139 E1
50/50
3.723.72
316018AA1-139 ULT2
50/50
0.9850.985
934065AD1-033 E
50/50
7.2747.274
937226AE2-253 E
50/50
5.65.6
957872AF2-081 E
50/50
3.8983.898
944602AF1-125 E
50/50
109.375109.375
3145506HICKORY
50/50
2.2562.256
957871AF2-081 C
50/50
9.0969.096
316185AD1-033 C
50/50
1.7831.783
944581AF1-123 C
50/50
48.52648.526
316320Y1-086 C
50/50
0.1410.141
944582AF1-123 E
50/50
111.119111.119
944592AF1-124 E
50/50
111.521111.521
923832AB2-022 E
50/50
0.7950.795
316388AE2-253 GEN
50/50
1.8831.883
919153AA1-139 E2
50/50
3.723.72
913392Y1-086 E
50/50
1.4081.408
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.1020.102
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.8891.889
LGEELTFEXP_LGEE->PJM
CLTF
0.0510.051
VTFLTFEXP_VFT->PJM
CMTX
0.190.19
SIGELTFEXP_SIGE->PJM
CLTF
0.0090.009
WECLTFEXP_WEC->PJM
CLTF
0.0280.028
G-007ALTFEXP_G-007A->PJM
CMTX
0.070.07
CPLELTFEXP_CPLE->PJM
CLTF
0.2140.214
TVALTFEXP_TVA->PJM
CLTF
0.160.16
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0430.043
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4081.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.6750.675
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.1450.145
LAGNLTFEXP_LAGN->PJM
CLTF
0.2030.203

Details for 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P4-2: 269T2128_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 269T2128_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.98 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:970.97
MW Contribution:147.89
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938532AE1-072 E
50/50
5.8245.824
3146326AYDLETT TAP
50/50
0.8630.863
917122Z2-027 E
Adder
0.52941176470588240.45
934065AD1-033 E
50/50
6.9816.981
937226AE2-253 E
50/50
4.8124.812
957872AF2-081 E
50/50
3.1993.199
944591AF1-124 C
50/50
45.82945.829
944601AF1-125 C
50/50
44.96344.963
316185AD1-033 C
50/50
1.7111.711
944581AF1-123 C
50/50
45.66745.667
316388AE2-253 GEN
50/50
1.6181.618
919153AA1-139 E2
50/50
3.0523.052
944602AF1-125 E
50/50
102.93102.93
3145506HICKORY
50/50
2.0612.061
957871AF2-081 C
50/50
7.4647.464
919152AA1-139 E1
50/50
3.0523.052
316018AA1-139 ULT2
50/50
0.8080.808
316017AA1-139 ULT1
50/50
0.8080.808
938531AE1-072 C
50/50
11.17211.172
944582AF1-123 E
50/50
104.572104.572
944592AF1-124 E
50/50
104.95104.95
923832AB2-022 E
Adder
0.58941176470588240.501
913392Y1-086 E
Adder
1.04352941176470580.887
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.070.07
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.4241.424
LGEELTFEXP_LGEE->PJM
CLTF
0.0470.047
VTFLTFEXP_VFT->PJM
CMTX
0.2740.274
SIGELTFEXP_SIGE->PJM
CLTF
0.0090.009
WECLTFEXP_WEC->PJM
CLTF
0.0260.026
G-007ALTFEXP_G-007A->PJM
CMTX
0.1020.102
CPLELTFEXP_CPLE->PJM
CLTF
0.1470.147
TVALTFEXP_TVA->PJM
CLTF
0.1370.137
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0590.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.321.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.5930.593
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.1320.132
LAGNLTFEXP_LAGN->PJM
CLTF
0.1730.173

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.54 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1199.86
MW Contribution:55.37
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.15 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1216.94
MW Contribution:55.94
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
933292AC2-141 E
Adder
6.3529411764705895.4
944602AF1-125 E
Adder
38.536470588235332.756
3145506HICKORY
Adder
0.80470588235294130.684
957871AF2-081 C
Adder
3.47411764705882352.953
937482AD2-202 E
50/50
0.6470.647
961792AG1-021 E
Adder
0.50117647058823530.426
3151041BRUNSWICKG3
50/50
6.916.91
3151021BRUNSWICKG1
50/50
6.916.91
942462AE2-259 E
Adder
2.21764705882352951.885
964791AG1-342 C
Adder
1.43529411764705881.22
3152441Z1-086 ST
50/50
15.62315.623
3152431Z1-086 GT3
50/50
8.9718.971
3152421Z1-086 GT2
50/50
8.9718.971
925612AC1-036 E
Adder
0.381176470588235340.324
924312AB2-078 E O1
Adder
0.45058823529411770.383
926274AC1-105 E
Adder
1.15529411764705880.982
940641AE2-051 C
50/50
14.85114.851
934622AD1-088 E
50/50
2.6942.694
934611AD1-087 C
50/50
0.7660.766
934612AD1-087 E
50/50
2.212.21
927255AC1-221 E
Adder
1.70117647058823531.446
938532AE1-072 E
Adder
3.1047058823529412.639
3146326AYDLETT TAP
Adder
0.455294117647058850.387
3147133PAMPLIN
Adder
0.377647058823529450.321
927264AC1-222 E
Adder
1.781.513
925522AC1-027 E
Adder
0.430588235294117660.366
933291AC2-141 C
Adder
14.88235294117647112.65
926755AC1-161 E
Adder
6.3529411764705895.4
957872AF2-081 E
Adder
1.48941176470588241.266
964242AG1-285 E
Adder
3.99647058823529383.397
924162AB2-060 E OP
Adder
1.4435294117647061.227
964792AG1-342 E
Adder
0.95647058823529410.813
932763AC2-100 E
Adder
1.14235294117647060.971
944012AF1-069 E
50/50
4.4634.463
3138533PONTONDP
Adder
0.217647058823529420.185
941591AE2-156 C
Adder
6.1035294117647065.188
944591AF1-124 C
Adder
17.15764705882352814.584
944601AF1-125 C
Adder
16.8341176470588214.309
944011AF1-069 C
50/50
11.48911.489
963041AG1-153 C
50/50
4.6824.682
3151541CLOVER2
50/50
7.7177.717
936261AD2-033 C
Adder
4.3352941176470593.685
961791AG1-021 C
Adder
0.58823529411764710.5
962562AG1-105 E
Adder
2.3352941176470591.985
944641AF1-129 C
Adder
-99.89764705882352-84.913
316240AF1-291 C
Adder
-2.2705882352941176-1.93
919152AA1-139 E1
Adder
1.42117647058823531.208
3145723EMPORIA
Adder
-0.3270588235294118-0.278
959311AF2-222 C
Adder
7.2776470588235296.186
942001AE2-212 C
Adder
-2.8705882352941177-2.44
934065AD1-033 E
Adder
1.87294117647058831.592
937226AE2-253 E
Adder
2.081.768
957482AF2-042 E
50/50
23.80623.806
926662AC1-147 E
Adder
0.448235294117647070.381
916192Z1-068 E
Adder
0.6682352941176470.568
939412AE1-173 E
50/50
44.67444.674
941032AE2-094 E
50/50
15.74915.749
941031AE2-094 C
50/50
35.16335.163
934331AD1-057 C
Adder
-1.1952941176470588-1.016
934321AD1-056 C
Adder
-2.142352941176471-1.821
936262AD2-033 E
Adder
2.89058823529411772.457
958211AF2-115 C
Adder
0.73529411764705890.625
944582AF1-123 E
Adder
39.15058823529411633.278
934621AD1-088 C
50/50
5.5965.596
946301AF1-294 C
Adder
1.2082352941176471.027
942461AE2-259 C
Adder
3.32588235294117632.827
935172AD1-152 E
Adder
3.1047058823529412.639
913392Y1-086 E
Adder
0.66235294117647060.563
939411AE1-173 C
50/50
67.01167.011
3137643SOCKMAN
Adder
-0.34352941176470586-0.292
3151031BRUNSWICKG2
50/50
6.916.91
937481AD2-202 C
50/50
0.2220.222
932046AC2-012 E
Adder
4.4317647058823533.767
938531AE1-072 C
Adder
5.95529411764705955.062
3152411Z1-086 GT1
50/50
8.9758.975
924302AB2-077 E O1
Adder
0.45058823529411770.383
944592AF1-124 E
Adder
39.2929411764705933.399
923832AB2-022 E
Adder
0.374117647058823550.318
946281AF1-292 C
Adder
-1.2576470588235293-1.069
3151051BRUNSWICKS1
50/50
14.35614.356
963042AG1-153 E
50/50
7.0227.022
3151531CLOVER1
50/50
7.797.79
964241AG1-285 C
Adder
5.9952941176470595.096
958212AF2-115 E
Adder
0.62588235294117660.532
962561AG1-105 C
Adder
3.50352941176470622.978
944581AF1-123 C
Adder
17.0976470588235314.533
957481AF2-042 C
50/50
35.70935.709
924322AB2-079 E O1
Adder
0.45058823529411770.383
946302AF1-294 E
Adder
1.02352941176470580.87
943902AF1-058 E
Adder
0.58823529411764710.5
919153AA1-139 E2
Adder
1.42117647058823531.208
940642AE2-051 E
50/50
9.9019.901
966621AG1-532 C
Adder
-1.14-0.969
924022AB2-043 E O1
Adder
1.75058823529411781.488
3147223TWITTYS
Adder
0.42235294117647060.359
959312AF2-222 E
Adder
4.8764705882352944.145
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9681.968
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.24536.245
NYPJM->LTFIMP_NY
CLTF
0.4470.447
LGEELTFEXP_LGEE->PJM
CLTF
0.4670.467
WECLTFEXP_WEC->PJM
CLTF
0.2490.249
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9710.971
SIGELTFEXP_SIGE->PJM
CLTF
0.0920.092
CPLELTFEXP_CPLE->PJM
CLTF
4.1284.128
TVALTFEXP_TVA->PJM
CLTF
2.2832.283
O66PJM->LTFIMP_O-066
CMTX_NF
6.1826.182
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.10812.108
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4868.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4991.499
LAGNLTFEXP_LAGN->PJM
CLTF
2.9182.918

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.16 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4182.74
MW Contribution:228.68
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.7 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4637.48
MW Contribution:230.13
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936666AD2-085 E
Adder
7.9705882352941196.775
941591AE2-156 C
50/50
27.4127.41
3151081ELIZAR1
50/50
4.9124.912
316316AC1-027 C
50/50
0.4870.487
944591AF1-124 C
50/50
70.86170.861
944601AF1-125 C
50/50
69.52369.523
938771AE1-103 C
Adder
4.3470588235294113.695
3145413WATKINS
Adder
1.02235294117647070.869
960081AF2-299 C
Adder
2.70823529411764732.302
926072AC1-086 E
Adder
13.85058823529411711.773
944011AF1-069 C
50/50
23.35723.357
963041AG1-153 C
50/50
9.7959.795
934576AD1-082 E
Adder
5.7482352941176484.886
916191Z1-068 C
50/50
0.0680.068
933292AC2-141 E
50/50
20.76320.763
316294AC1-161 C
50/50
7.9487.948
944602AF1-125 E
50/50
159.152159.152
3145506HICKORY
50/50
3.3883.388
943612AF1-032 E
Adder
1.40823529411764731.197
957871AF2-081 C
50/50
15.47915.479
940492AE2-034 E
Adder
4.6305882352941183.936
934522AD1-076 E
Adder
9.3011764705882357.906
943172AE2-346 E
Adder
0.88941176470588230.756
918492AA1-063AE OP
Adder
5.9423529411764715.051
962571AG1-106 C
Adder
3.9364705882352943.346
917332KELFORD E
Adder
2.39764705882352922.038
925122AB2-169 E
Adder
8.4305882352941197.166
316274AC1-208 C
Adder
12.93882352941176410.998
917342Z2-044 E
Adder
0.84705882352941180.72
937482AD2-202 E
Adder
1.57764705882352941.341
3151311EDGECMA
Adder
21.84705882352941218.57
939191AE1-149 C
Adder
13.15411764705882411.181
3143316POE
Adder
1.71764705882352931.46
901082W1-029 E
Adder
48.63529411764706441.34
926206AC1-098 E
Adder
5.25647058823529444.468
3151041BRUNSWICKG3
50/50
14.45714.457
3151021BRUNSWICKG1
50/50
14.45714.457
964791AG1-342 C
Adder
4.7858823529411764.068
961611AG1-000B C
Adder
19.52941176470588416.6
316375AC2-012 C
50/50
2.0662.066
313526AB2-022 C
50/50
0.5790.579
940541AE2-040 C
Adder
4.263.621
940481AE2-033 C
Adder
23.97176470588235420.376
940482AE2-033 E
Adder
16.1613.736
923263AB1-132 E OP
Adder
8.8564705882352937.528
3152441Z1-086 ST
50/50
32.38732.387
3152431Z1-086 GT3
50/50
18.59718.597
3152421Z1-086 GT2
50/50
18.59718.597
925612AC1-036 E
Adder
1.13647058823529410.966
924312AB2-078 E O1
Adder
1.84705882352941191.57
926274AC1-105 E
Adder
3.63.06
316084AB2-161 E
Adder
7.2141176470588236.132
3145946PLYMOUTH TP
Adder
0.48235294117647060.41
933982AD1-022 E
Adder
7.0894117647058836.026
940641AE2-051 C
50/50
31.3831.38
927146AC1-208 E
Adder
5.74470588235294164.883
934622AD1-088 E
Adder
6.6576470588235295.659
934612AD1-087 E
Adder
5.3905882352941184.582
943461AF1-017 C
Adder
1.91529411764705881.628
932596AC2-079 E
Adder
13.36941176470588411.364
316311AC2-079 C
Adder
8.1941176470588236.965
938532AE1-072 E
50/50
14.1714.17
3146326AYDLETT TAP
50/50
2.0962.096
917122Z2-027 E
Adder
2.061.751
920692AA2-178 E
Adder
6.1741176470588245.248
966622AG1-532 E
Adder
1.35411764705882361.151
922923AB1-081 E OP
Adder
5.2458823529411764.459
3150921YORKTN3
Adder
152.65647058823532129.758
3145256KINGFORK
Adder
1.48823529411764691.265
925522AC1-027 E
50/50
1.8771.877
933291AC2-141 C
50/50
48.6448.64
926755AC1-161 E
50/50
20.76320.763
941102AE2-104 E
Adder
7.966.766
957872AF2-081 E
50/50
6.6346.634
962572AG1-106 E
Adder
1.72235294117647061.464
926214AC1-099 E
Adder
1.73647058823529421.476
932632AC2-084 E
Adder
4.6458823529411763.949
964242AG1-285 E
Adder
11.97764705882352810.181
924162AB2-060 E OP
Adder
5.8752941176470594.994
964792AG1-342 E
Adder
3.1905882352941182.712
3151101ELIZAR3
50/50
4.9744.974
316315AB2-025 C
50/50
0.6050.605
946282AF1-292 E
Adder
1.49529411764705871.271
944012AF1-069 E
50/50
9.0749.074
957861AF2-080 C
Adder
10.917647058823539.28
917512Z2-088 E OP1
Adder
6.9717647058823535.926
957862AF2-080 E
Adder
4.844.114
962562AG1-105 E
Adder
8.0317647058823526.827
942342AE2-247 E
Adder
2.92470588235294172.486
316036AC1-147 C
50/50
0.5640.564
919152AA1-139 E1
50/50
6.336.33
316018AA1-139 ULT2
50/50
1.6761.676
920042AA2-088 E OP
Adder
15.59882352941176513.259
934521AD1-076 C
Adder
18.24823529411764515.511
934511AD1-075 C
Adder
12.56117647058823510.677
3145723EMPORIA
Adder
0.62470588235294120.531
923573AB1-173 E OP
Adder
4.7517647058823534.039
919692AA2-053 E OP
Adder
6.1282352941176475.209
925785AC1-054 E
Adder
4.8741176470588234.143
316263AC1-034 C
Adder
9.344705882352947.943
959311AF2-222 C
Adder
21.718.445
939192AE1-149 E
Adder
8.7694117647058827.454
939312AE1-162 E
Adder
1.95882352941176491.665
3150991CHESPKB
50/50
1.1051.105
934065AD1-033 E
50/50
7.7977.797
937226AE2-253 E
50/50
9.0629.062
934501AD1-074 C
Adder
50.2447058823529442.708
924517AB2-100 E2
Adder
4.23058823529411753.596
957482AF2-042 E
50/50
55.48555.485
961671AG1-007 C
Adder
1.33294117647058831.133
934621AD1-088 C
Adder
13.82823529411764711.754
935172AD1-152 E
Adder
7.9105882352941186.724
926662AC1-147 E
50/50
2.0262.026
916192Z1-068 E
50/50
2.92.9
957492AF2-043 E
Adder
2.16705882352941171.842
923852AB2-025 E
50/50
1.7231.723
939412AE1-173 E
50/50
105.86105.86
961942AG1-037 E
Adder
0.494117647058823550.42
961941AG1-037 C
Adder
0.74117647058823530.63
941032AE2-094 E
50/50
32.01732.017
941031AE2-094 C
50/50
71.48571.485
934332AD1-057 E
Adder
2.5917647058823532.203
934331AD1-057 C
Adder
4.9764705882352954.23
934321AD1-056 C
Adder
8.927.582
934322AD1-056 E
Adder
4.8388235294117664.113
927022AC1-189 E
Adder
5.9882352941176475.09
925595AC1-034 E
Adder
7.0494117647058835.992
316349AD2-085 C
Adder
4.8858823529411764.153
935112AD1-144 E
Adder
1.38117647058823521.174
3151091ELIZAR2
50/50
4.8274.827
944582AF1-123 E
50/50
161.69161.69
944592AF1-124 E
50/50
162.275162.275
923832AB2-022 E
50/50
1.9081.908
938772AE1-103 E
Adder
6.0023529411764715.102
916042Z1-036 E
Adder
43.3141176470588236.817
960082AF2-299 E
Adder
1.80588235294117651.535
946281AF1-292 C
Adder
2.24235294117647041.906
926071AC1-086 C
Adder
30.4329411764705925.868
3151051BRUNSWICKS1
50/50
30.03530.035
963042AG1-153 E
50/50
14.69214.692
927021AC1-189 C
Adder
12.02000000000000110.217
964241AG1-285 C
Adder
17.9658823529411815.271
924152AB2-059 E OP
Adder
7.4317647058823546.317
962561AG1-105 C
Adder
12.04705882352941210.24
913392Y1-086 E
50/50
3.383.38
939411AE1-173 C
50/50
158.79158.79
3137643SOCKMAN
Adder
1.03058823529411760.876
3151031BRUNSWICKG2
50/50
14.45714.457
919710AA2-057 E
Adder
5.6458823529411774.799
932046AC2-012 E
50/50
20.04320.043
958161AF2-110 C
Adder
2.04352941176470631.737
316017AA1-139 ULT1
50/50
1.6761.676
938531AE1-072 C
50/50
27.18327.183
3145393UNCAMP
Adder
9.0117647058823537.66
933981AD1-022 C
Adder
13.02235294117647211.069
900672V4-068 E
Adder
0.52352941176470590.445
3152411Z1-086 GT1
50/50
18.60518.605
924302AB2-077 E O1
Adder
1.84705882352941191.57
3150981CHESPKA
50/50
0.6670.667
316185AD1-033 C
50/50
1.9111.911
944581AF1-123 C
50/50
70.6170.61
941101AE2-104 C
Adder
5.00705882352941254.256
316320Y1-086 C
50/50
0.3390.339
316141AB2-099 E
Adder
0.370588235294117660.315
316088AB2-174 E
Adder
9.4435294117647068.027
923994AB2-040_E
Adder
8.9094117647058837.573
957481AF2-042 C
50/50
83.22783.227
961672AG1-007 E
Adder
0.75529411764705890.642
924322AB2-079 E O1
Adder
1.84705882352941191.57
942341AE2-247 C
Adder
2.11764705882352941.8
943462AF1-017 E
Adder
3.12588235294117662.657
958162AF2-110 E
Adder
3.24941176470588242.762
316388AE2-253 GEN
50/50
3.0473.047
919153AA1-139 E2
50/50
6.336.33
934512AD1-075 E
Adder
6.3941176470588235.435
934502AD1-074 E
Adder
25.5776470588235321.741
924516AB2-100 E1
Adder
4.23058823529411753.596
918512AA1-065 E OP
Adder
8.1470588235294116.925
940642AE2-051 E
50/50
20.9220.92
966621AG1-532 C
Adder
2.0317647058823531.727
918532AA1-067 E
Adder
1.02823529411764710.874
924022AB2-043 E O1
Adder
7.1670588235294126.092
3147223TWITTYS
Adder
1.2588235294117651.07
959312AF2-222 E
Adder
2.9682352941176472.523
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6337.633
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.923129.923
NYPJM->LTFIMP_NY
CLTF
2.172.17
LGEELTFEXP_LGEE->PJM
CLTF
1.3891.389
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6364.636
SIGELTFEXP_SIGE->PJM
CLTF
0.2790.279
WECLTFEXP_WEC->PJM
CLTF
0.7290.729
CPLELTFEXP_CPLE->PJM
CLTF
16.01716.017
TVALTFEXP_TVA->PJM
CLTF
7.5637.563
O66PJM->LTFIMP_O-066
CMTX_NF
29.52729.527
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.88834.888
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.38927.389
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.6044.604
LAGNLTFEXP_LAGN->PJM
CLTF
9.689.68

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.22 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4106.12
MW Contribution:207.66
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943461AF1-017 C
Adder
1.77764705882352941.511
932596AC2-079 E
Adder
12.38941176470588310.531
316311AC2-079 C
Adder
7.5929411764705886.454
938532AE1-072 E
50/50
12.89612.896
3146326AYDLETT TAP
50/50
1.9081.908
917122Z2-027 E
Adder
1.88117647058823521.599
920692AA2-178 E
Adder
5.74.845
966622AG1-532 E
Adder
1.29294117647058831.099
922923AB1-081 E OP
Adder
4.9882352941176474.24
939192AE1-149 E
Adder
8.424705882352947.161
939312AE1-162 E
Adder
1.79058823529411781.522
934065AD1-033 E
50/50
7.0817.081
937226AE2-253 E
50/50
8.2398.239
934501AD1-074 C
Adder
46.5682352941176539.583
924517AB2-100 E2
Adder
4.042352941176473.436
957482AF2-042 E
50/50
53.29753.297
961671AG1-007 C
Adder
1.26235294117647071.073
934621AD1-088 C
Adder
13.31176470588235211.315
935172AD1-152 E
Adder
7.6094117647058826.468
961611AG1-000B C
Adder
18.02352941176470615.32
316375AC2-012 C
50/50
1.8781.878
926662AC1-147 E
Adder
1.84117647058823521.565
916192Z1-068 E
50/50
2.6352.635
957492AF2-043 E
Adder
1.97647058823529421.68
923852AB2-025 E
50/50
1.6571.657
939412AE1-173 E
50/50
99.43599.435
961942AG1-037 E
Adder
0.462352941176470630.393
961941AG1-037 C
Adder
0.69294117647058820.589
941032AE2-094 E
50/50
30.64130.641
941031AE2-094 C
50/50
68.41468.414
934332AD1-057 E
Adder
2.46235294117647062.093
934331AD1-057 C
Adder
4.72941176470588154.02
934321AD1-056 C
Adder
8.477647058823537.206
934322AD1-056 E
Adder
4.59882352941176453.909
927022AC1-189 E
Adder
5.6541176470588244.806
925595AC1-034 E
Adder
6.702352941176475.697
936262AD2-033 E
Adder
10.6635294117647069.064
3150921YORKTN3
Adder
46.1517647058823539.229
3145256KINGFORK
Adder
1.35529411764705881.152
925522AC1-027 E
50/50
1.7051.705
933291AC2-141 C
50/50
43.61643.616
926755AC1-161 E
50/50
18.61818.618
941102AE2-104 E
Adder
7.3058823529411766.21
957872AF2-081 E
50/50
6.0346.034
962572AG1-106 E
Adder
1.63529411764705881.39
926214AC1-099 E
Adder
1.64117647058823551.395
932632AC2-084 E
Adder
4.3905882352941183.732
964242AG1-285 E
Adder
11.549.809
924162AB2-060 E OP
Adder
5.6588235294117644.81
964792AG1-342 E
Adder
3.07411764705882362.613
936666AD2-085 E
Adder
7.397647058823536.288
941591AE2-156 C
50/50
24.9124.91
3151081ELIZAR1
50/50
4.4634.463
316316AC1-027 C
50/50
0.4430.443
944591AF1-124 C
50/50
64.34964.349
944601AF1-125 C
50/50
63.13463.134
938771AE1-103 C
Adder
4.0211764705882363.418
3145413WATKINS
Adder
0.94941176470588240.807
960081AF2-299 C
Adder
2.58705882352941162.199
926072AC1-086 E
Adder
13.15411764705882411.181
944011AF1-069 C
50/50
22.35322.353
963041AG1-153 C
50/50
9.3799.379
957862AF2-080 E
Adder
4.5705882352941173.885
3151541CLOVER2
50/50
18.07618.076
936261AD2-033 C
Adder
15.9952941176470613.596
962562AG1-105 E
Adder
7.7364705882352946.576
316185AD1-033 C
50/50
1.7361.736
944581AF1-123 C
50/50
64.12164.121
941101AE2-104 C
Adder
4.5952941176470593.906
316141AB2-099 E
Adder
0.347058823529411750.295
316088AB2-174 E
Adder
8.997647058823537.648
923994AB2-040_E
Adder
8.487.208
957481AF2-042 C
50/50
79.94679.946
961672AG1-007 E
Adder
0.71529411764705890.608
924322AB2-079 E O1
Adder
1.77764705882352941.511
943902AF1-058 E
Adder
1.65647058823529411.408
942341AE2-247 C
Adder
1.9647058823529411.67
943462AF1-017 E
Adder
2.90117647058823552.466
958162AF2-110 E
Adder
2.98235294117647072.535
316388AE2-253 GEN
50/50
2.7712.771
919153AA1-139 E2
50/50
5.7585.758
934512AD1-075 E
Adder
5.9258823529411765.037
934502AD1-074 E
Adder
23.70588235294117420.15
924516AB2-100 E1
Adder
4.042352941176473.436
918512AA1-065 E OP
Adder
7.6023529411764716.462
940642AE2-051 E
50/50
19.82119.821
966621AG1-532 C
Adder
1.94000000000000021.649
934576AD1-082 E
Adder
5.4388235294117654.623
916191Z1-068 C
50/50
0.0610.061
933292AC2-141 E
50/50
18.61818.618
316294AC1-161 C
50/50
7.1277.127
944602AF1-125 E
50/50
144.526144.526
3145506HICKORY
50/50
3.0783.078
943612AF1-032 E
Adder
1.28470588235294141.092
957871AF2-081 C
50/50
14.0814.08
940492AE2-034 E
Adder
4.2752941176470593.634
934522AD1-076 E
Adder
8.6200000000000017.327
943172AE2-346 E
Adder
0.8317647058823530.707
918492AA1-063AE OP
Adder
5.6035294117647064.763
962571AG1-106 C
Adder
3.73764705882352953.177
917332KELFORD E
Adder
2.25058823529411761.913
925122AB2-169 E
Adder
7.8694117647058836.689
316274AC1-208 C
Adder
12.25411764705882510.416
917342Z2-044 E
Adder
0.80352941176470590.683
937482AD2-202 E
50/50
1.5171.517
3151311EDGECMA
Adder
20.7705882352941217.655
939191AE1-149 C
Adder
12.63647058823529410.741
3143316POE
Adder
1.67647058823529421.425
901082W1-029 E
Adder
44.4776470588235337.806
926206AC1-098 E
Adder
4.9670588235294124.222
3151041BRUNSWICKG3
50/50
13.84313.843
3151021BRUNSWICKG1
50/50
13.84313.843
964791AG1-342 C
Adder
4.6105882352941173.919
940541AE2-040 C
50/50
4.0974.097
940481AE2-033 C
50/50
23.03323.033
940482AE2-033 E
50/50
15.52815.528
923263AB1-132 E OP
Adder
8.4105882352941177.149
3152441Z1-086 ST
50/50
31.00731.007
3152431Z1-086 GT3
50/50
17.80517.805
3152421Z1-086 GT2
50/50
17.80517.805
925612AC1-036 E
Adder
1.09882352941176480.934
924312AB2-078 E O1
Adder
1.77764705882352941.511
926274AC1-105 E
Adder
3.4682352941176472.948
316084AB2-161 E
Adder
6.8258823529411765.802
3145946PLYMOUTH TP
Adder
0.44705882352941180.38
933982AD1-022 E
Adder
6.582352941176475.595
940641AE2-051 C
50/50
29.73129.731
927146AC1-208 E
Adder
5.44117647058823554.625
934622AD1-088 E
Adder
6.4094117647058835.448
934611AD1-087 C
50/50
1.7961.796
934612AD1-087 E
50/50
5.1825.182
942342AE2-247 E
Adder
2.71411764705882372.307
919152AA1-139 E1
50/50
5.7585.758
316018AA1-139 ULT2
50/50
1.5241.524
920042AA2-088 E OP
Adder
14.57411764705882412.388
934521AD1-076 C
Adder
16.9129411764705914.376
934511AD1-075 C
Adder
11.6423529411764739.896
3145723EMPORIA
Adder
0.59647058823529410.507
923573AB1-173 E OP
Adder
4.5223529411764713.844
919692AA2-053 E OP
Adder
5.797647058823534.928
925785AC1-054 E
Adder
4.65176470588235353.954
316263AC1-034 C
Adder
8.8847058823529417.552
959311AF2-222 C
Adder
20.9952941176470617.846
932046AC2-012 E
50/50
18.21618.216
958161AF2-110 C
Adder
1.8752941176470591.594
316017AA1-139 ULT1
50/50
1.5241.524
938531AE1-072 C
50/50
24.73924.739
3145393UNCAMP
Adder
8.3505882352941197.098
3151101ELIZAR3
50/50
4.5194.519
316315AB2-025 C
50/50
0.5820.582
946282AF1-292 E
Adder
1.4270588235294121.213
944012AF1-069 E
50/50
8.6848.684
957861AF2-080 C
Adder
10.3094117647058838.763
917512Z2-088 E OP1
Adder
6.5941176470588245.605
316349AD2-085 C
Adder
4.5341176470588243.854
935112AD1-144 E
Adder
1.2588235294117651.07
3151091ELIZAR2
50/50
4.3864.386
944582AF1-123 E
50/50
146.831146.831
944592AF1-124 E
50/50
147.363147.363
923832AB2-022 E
Adder
1.74000000000000021.479
938772AE1-103 E
Adder
5.5529411764705884.72
916042Z1-036 E
Adder
39.78705882352941433.819
960082AF2-299 E
Adder
1.7247058823529411.466
946281AF1-292 C
Adder
2.14117647058823521.82
926071AC1-086 C
Adder
28.90117647058823624.566
3151051BRUNSWICKS1
50/50
28.75928.759
963042AG1-153 E
50/50
14.06814.068
927021AC1-189 C
Adder
11.3505882352941179.648
3151531CLOVER1
50/50
18.24618.246
964241AG1-285 C
Adder
17.3105882352941214.714
924152AB2-059 E OP
Adder
7.0658823529411776.006
962561AG1-105 C
Adder
11.6047058823529429.864
913392Y1-086 E
Adder
3.08235294117647072.62
939411AE1-173 C
50/50
149.153149.153
3137643SOCKMAN
Adder
0.97882352941176460.832
3151031BRUNSWICKG2
50/50
13.84313.843
919710AA2-057 E
Adder
5.3541176470588244.551
937481AD2-202 C
50/50
0.5210.521
933981AD1-022 C
Adder
12.09058823529411710.277
900672V4-068 E
Adder
0.490588235294117660.417
3152411Z1-086 GT1
50/50
17.81217.812
924302AB2-077 E O1
Adder
1.77764705882352941.511
918532AA1-067 E
Adder
0.96823529411764710.823
924022AB2-043 E O1
Adder
6.95.865
3147223TWITTYS
Adder
1.21764705882352931.035
959312AF2-222 E
Adder
14.06705882352941311.957
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.3487.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
126.03126.03
NYPJM->LTFIMP_NY
CLTF
2.22.2
LGEELTFEXP_LGEE->PJM
CLTF
1.4681.468
WECLTFEXP_WEC->PJM
CLTF
0.7690.769
G-007PJM->LTFIMP_G-007
CMTX_NF
4.7394.739
SIGELTFEXP_SIGE->PJM
CLTF
0.2910.291
CPLELTFEXP_CPLE->PJM
CLTF
15.41515.415
TVALTFEXP_TVA->PJM
CLTF
7.567.56
O66PJM->LTFIMP_O-066
CMTX_NF
30.16830.168
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.99436.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.67827.678
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.7584.758
LAGNLTFEXP_LAGN->PJM
CLTF
9.6549.654

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T567_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T567_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.44 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4075.55
MW Contribution:232.75
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934576AD1-082 E
Adder
5.5282352941176474.699
916191Z1-068 C
50/50
0.0690.069
933292AC2-141 E
50/50
21.46921.469
316294AC1-161 C
50/50
8.2198.219
944602AF1-125 E
50/50
161.991161.991
3145506HICKORY
50/50
3.4483.448
943612AF1-032 E
Adder
1.42235294117647081.209
957871AF2-081 C
50/50
15.73315.733
940492AE2-034 E
Adder
4.663.961
934522AD1-076 E
Adder
9.3411764705882367.94
943172AE2-346 E
Adder
0.88823529411764710.755
918492AA1-063AE OP
Adder
5.9070588235294125.021
962571AG1-106 C
Adder
3.8952941176470593.311
917332KELFORD E
Adder
2.39058823529411772.032
925122AB2-169 E
Adder
8.4411764705882367.175
316274AC1-208 C
Adder
12.85294117647058910.925
917342Z2-044 E
Adder
0.84117647058823530.715
937482AD2-202 E
Adder
1.56941176470588251.334
3151311EDGECMA
Adder
21.6952941176470618.441
316084AB2-161 E
Adder
6.937647058823535.897
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
933982AD1-022 E
Adder
7.11294117647058856.046
940641AE2-051 C
50/50
31.61831.618
927146AC1-208 E
Adder
5.7070588235294124.851
934622AD1-088 E
Adder
6.6058823529411775.615
934612AD1-087 E
Adder
5.3611764705882364.557
943461AF1-017 C
Adder
1.89411764705882371.61
932596AC2-079 E
Adder
13.2447058823529411.258
316311AC2-079 C
Adder
8.117647058823536.9
938532AE1-072 E
50/50
14.39614.396
3146326AYDLETT TAP
50/50
2.1292.129
917122Z2-027 E
Adder
2.08705882352941161.774
920692AA2-178 E
Adder
6.2129411764705885.281
966622AG1-532 E
Adder
1.3352941176470591.135
922923AB1-081 E OP
Adder
5.2094117647058834.428
3150921YORKTN3
Adder
148.4764705882353126.205
3145256KINGFORK
Adder
1.49058823529411751.267
925522AC1-027 E
50/50
1.9061.906
933291AC2-141 C
50/50
50.29350.293
926755AC1-161 E
50/50
21.46921.469
941102AE2-104 E
Adder
7.99294117647058756.794
957872AF2-081 E
50/50
6.7436.743
962572AG1-106 E
Adder
1.7035294117647061.448
926214AC1-099 E
Adder
1.72705882352941181.468
932632AC2-084 E
Adder
4.623.927
964242AG1-285 E
Adder
11.85176470588235310.074
924162AB2-060 E OP
Adder
5.8058823529411764.935
964792AG1-342 E
Adder
3.1588235294117652.685
961611AG1-000B C
Adder
5.04.25
3152331SURRY 2
50/50
39.09439.094
316375AC2-012 C
50/50
2.0942.094
940541AE2-040 C
Adder
4.16470588235294153.54
940481AE2-033 C
Adder
23.45176470588235419.934
940482AE2-033 E
Adder
15.81058823529411813.439
923263AB1-132 E OP
Adder
8.7635294117647067.449
3152441Z1-086 ST
50/50
32.43232.432
3152431Z1-086 GT3
50/50
18.62318.623
3152421Z1-086 GT2
50/50
18.62318.623
925612AC1-036 E
Adder
1.11882352941176480.951
924312AB2-078 E O1
Adder
1.82588235294117651.552
926274AC1-105 E
Adder
3.5647058823529413.03
3151101ELIZAR3
50/50
5.0455.045
946282AF1-292 E
Adder
1.47411764705882351.253
944012AF1-069 E
50/50
9.0929.092
957861AF2-080 C
Adder
10.8752941176470599.244
917512Z2-088 E OP1
Adder
6.9388235294117645.898
942342AE2-247 E
Adder
2.89058823529411772.457
919152AA1-139 E1
50/50
6.4346.434
316018AA1-139 ULT2
50/50
1.7031.703
920042AA2-088 E OP
Adder
15.5623529411764713.228
934521AD1-076 C
Adder
18.32705882352941315.578
934511AD1-075 C
Adder
12.6152941176470610.723
3145723EMPORIA
Adder
0.61647058823529410.524
923573AB1-173 E OP
Adder
4.6976470588235293.993
919692AA2-053 E OP
Adder
6.08588235294117655.173
925785AC1-054 E
Adder
4.8317647058823534.107
316263AC1-034 C
Adder
9.287.888
959311AF2-222 C
Adder
21.34470588235294418.143
936666AD2-085 E
Adder
7.8811764705882356.699
941591AE2-156 C
50/50
27.78727.787
3151081ELIZAR1
50/50
4.9824.982
316316AC1-027 C
50/50
0.4950.495
944591AF1-124 C
50/50
72.12672.126
944601AF1-125 C
50/50
70.76370.763
938771AE1-103 C
Adder
4.3517647058823533.699
3145413WATKINS
Adder
1.02235294117647070.869
960081AF2-299 C
Adder
2.6705882352941182.27
926072AC1-086 E
Adder
13.70588235294117811.65
944011AF1-069 C
50/50
23.40523.405
963041AG1-153 C
50/50
9.8059.805
957862AF2-080 E
Adder
4.8211764705882354.098
962562AG1-105 E
Adder
7.9482352941176486.756
926662AC1-147 E
Adder
2.05411764705882361.746
916192Z1-068 E
50/50
2.9452.945
957492AF2-043 E
Adder
2.18823529411764731.86
923852AB2-025 E
Adder
1.6847058823529411.432
939412AE1-173 E
50/50
106.866106.866
961942AG1-037 E
Adder
0.49294117647058820.419
961941AG1-037 C
Adder
0.740.629
941032AE2-094 E
50/50
32.08232.082
941031AE2-094 C
50/50
71.63171.631
934332AD1-057 E
Adder
2.56941176470588272.184
934331AD1-057 C
Adder
4.9341176470588244.194
934321AD1-056 C
Adder
8.844705882352947.518
934322AD1-056 E
Adder
4.797647058823534.078
927022AC1-189 E
Adder
5.9647058823529415.07
925595AC1-034 E
Adder
7.0011764705882355.951
939312AE1-162 E
Adder
1.93058823529411771.641
3150991CHESPKB
50/50
1.121.12
934065AD1-033 E
50/50
7.9347.934
937226AE2-253 E
50/50
9.2149.214
934501AD1-074 C
Adder
50.4623529411764742.893
924517AB2-100 E2
Adder
4.1635294117647063.539
957482AF2-042 E
Adder
55.2517647058823546.964
961671AG1-007 C
Adder
1.32588235294117651.127
934621AD1-088 C
Adder
13.7211.662
935172AD1-152 E
Adder
7.8611764705882366.682
932046AC2-012 E
50/50
20.31420.314
958161AF2-110 C
Adder
2.0517647058823531.744
316017AA1-139 ULT1
50/50
1.7031.703
938531AE1-072 C
50/50
27.61527.615
3145393UNCAMP
Adder
9.017647058823537.665
933981AD1-022 C
Adder
13.06588235294117711.106
900672V4-068 E
Adder
0.52235294117647060.444
3152411Z1-086 GT1
50/50
18.63118.631
924302AB2-077 E O1
Adder
1.82588235294117651.552
316349AD2-085 C
Adder
4.8305882352941174.106
935112AD1-144 E
Adder
1.3835294117647061.176
3151091ELIZAR2
50/50
4.8964.896
944582AF1-123 E
50/50
164.574164.574
944592AF1-124 E
50/50
165.171165.171
923832AB2-022 E
Adder
1.93411764705882351.644
938772AE1-103 E
Adder
6.0094117647058825.108
916042Z1-036 E
Adder
43.71058823529412537.154
960082AF2-299 E
Adder
1.78117647058823541.514
946281AF1-292 C
Adder
2.21058823529411751.879
926071AC1-086 C
Adder
30.1129411764705925.596
3151051BRUNSWICKS1
50/50
30.06830.068
963042AG1-153 E
50/50
14.70814.708
927021AC1-189 C
Adder
11.97411764705882410.178
964241AG1-285 C
Adder
17.77647058823529515.11
924152AB2-059 E OP
Adder
7.3811764705882366.274
962561AG1-105 C
Adder
11.92235294117647210.134
3143316POE
Adder
1.61411764705882371.372
901082W1-029 E
Adder
49.1811764705882441.804
926206AC1-098 E
Adder
5.2270588235294114.443
3151041BRUNSWICKG3
50/50
14.47314.473
3151021BRUNSWICKG1
50/50
14.47314.473
964791AG1-342 C
Adder
4.737647058823534.027
316185AD1-033 C
50/50
1.9451.945
944581AF1-123 C
50/50
71.8771.87
941101AE2-104 C
Adder
5.0270588235294114.273
316141AB2-099 E
Adder
0.36941176470588240.314
316088AB2-174 E
Adder
9.3282352941176477.929
923994AB2-040_E
Adder
8.8082352941176477.487
957481AF2-042 C
Adder
82.8776470588235370.446
961672AG1-007 E
Adder
0.7517647058823530.639
924322AB2-079 E O1
Adder
1.82588235294117651.552
943902AF1-058 E
Adder
1.70235294117647061.447
913392Y1-086 E
Adder
3.42705882352941152.913
939411AE1-173 C
50/50
160.299160.299
3137643SOCKMAN
Adder
1.02117647058823540.868
3151031BRUNSWICKG2
50/50
14.47314.473
919710AA2-057 E
Adder
5.6082352941176474.767
942341AE2-247 C
Adder
2.09411764705882361.78
943462AF1-017 E
Adder
3.09058823529411742.627
958162AF2-110 E
Adder
3.2635294117647062.774
316388AE2-253 GEN
50/50
3.0993.099
919153AA1-139 E2
50/50
6.4346.434
934512AD1-075 E
Adder
6.422352941176475.459
934502AD1-074 E
Adder
25.6882352941176521.835
924516AB2-100 E1
Adder
4.1635294117647063.539
918512AA1-065 E OP
Adder
8.1494117647058816.927
940642AE2-051 E
50/50
21.07921.079
966621AG1-532 C
Adder
2.00352941176470621.703
918532AA1-067 E
Adder
1.02588235294117650.872
924022AB2-043 E O1
Adder
7.0847058823529416.022
3147223TWITTYS
Adder
1.241.054
959312AF2-222 E
Adder
14.30117647058823712.156
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.5637.563
CBM South 2LTFEXP_CBM-S2->PJM
CBM
128.067128.067
NYPJM->LTFIMP_NY
CLTF
2.0052.005
LGEELTFEXP_LGEE->PJM
CLTF
1.2871.287
WECLTFEXP_WEC->PJM
CLTF
0.6770.677
G-007PJM->LTFIMP_G-007
CMTX_NF
4.2584.258
SIGELTFEXP_SIGE->PJM
CLTF
0.2610.261
CPLELTFEXP_CPLE->PJM
CLTF
15.87115.871
TVALTFEXP_TVA->PJM
CLTF
7.2977.297
O66PJM->LTFIMP_O-066
CMTX_NF
27.12727.127
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.34332.343
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.24226.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.3444.344
LAGNLTFEXP_LAGN->PJM
CLTF
9.3599.359

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.39 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1062.25
MW Contribution:18.83
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.68 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1086.53
MW Contribution:18.27
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
916191Z1-068 C
80/20
0.0180.018
316294AC1-161 C
80/20
2.1972.197
957871AF2-081 C
80/20
4.1964.196
962571AG1-106 C
80/20
1.1691.169
932631AC2-084 C
80/20
0.4330.433
316274AC1-208 C
80/20
3.8963.896
3151311EDGECMA
Adder
6.8129411764705895.791
3151601KERR 3
80/20
0.4940.494
3151581KERR 1
80/20
0.1760.176
941011AE2-092 C
Adder
-4.452941176470588-3.785
940641AE2-051 C
80/20
11.53811.538
316336AC2-165 C
Adder
-10.758823529411764-9.145
934611AD1-087 C
80/20
0.6230.623
3151611KERR 4
80/20
0.4940.494
943461AF1-017 C
Adder
0.454117647058823570.386
316311AC2-079 C
Adder
1.9682352941176471.673
933291AC2-141 C
80/20
13.44213.442
316305AF2-043 C
80/20
0.1410.141
316087AB2-174 C
80/20
0.5050.505
3151591KERR 2
80/20
0.4940.494
3156056W1-029WIND
80/20
0.3220.322
316375AC2-012 C
80/20
0.5420.542
313526AB2-022 C
80/20
0.1570.157
940541AE2-040 C
80/20
1.2541.254
940481AE2-033 C
80/20
7.0627.062
3151411GASTONB
80/20
1.3141.314
316181AB2-040 GEN
80/20
0.5450.545
316174AB2-169_C
80/20
0.4470.447
3156063AA2-053SOLA
80/20
0.6450.645
3151281ROARAP4
80/20
0.5610.561
3152441Z1-086 ST
80/20
12.19612.196
3152431Z1-086 GT3
80/20
7.0037.003
3152421Z1-086 GT2
80/20
7.0037.003
938821AE1-108 C
Adder
-4.716470588235294-4.009
3151101ELIZAR3
80/20
1.3121.312
316315AB2-025 C
80/20
0.1780.178
316129AC1-054 C
80/20
0.5240.524
957861AF2-080 C
Adder
3.3247058823529412.826
316036AC1-147 C
80/20
0.1480.148
316018AA1-139 ULT2
80/20
0.4540.454
934521AD1-076 C
80/20
5.1645.164
934511AD1-075 C
80/20
3.5543.554
316011AB1-132 C OP
80/20
1.0031.003
316263AC1-034 C
Adder
2.91411764705882352.477
959311AF2-222 C
Adder
5.57411764705882454.738
941591AE2-156 C
80/20
7.2027.202
3151081ELIZAR1
80/20
1.2951.295
316316AC1-027 C
80/20
0.130.13
944591AF1-124 C
80/20
19.18819.188
944601AF1-125 C
80/20
18.82618.826
938771AE1-103 C
Adder
1.16941176470588240.994
960081AF2-299 C
80/20
0.8010.801
944011AF1-069 C
80/20
8.8768.876
963041AG1-153 C
80/20
3.6733.673
3151541CLOVER2
80/20
6.2756.275
3151631KERR 6
80/20
0.4940.494
936261AD2-033 C
Adder
4.2364705882352943.601
936171AD2-023 C
Adder
1.80117647058823521.531
943171AE2-346 C
80/20
0.0950.095
961941AG1-037 C
80/20
0.2130.213
3151391GASTONA
80/20
1.3141.314
3151381ROSEMG2
80/20
0.4110.411
941031AE2-094 C
80/20
27.16527.165
934331AD1-057 C
Adder
1.52117647058823541.293
934321AD1-056 C
Adder
2.72588235294117662.317
3150991CHESPKB
80/20
0.290.29
316321Z2-027 C
80/20
0.1520.152
940491AE2-034 C
80/20
0.4850.485
934501AD1-074 C
80/20
14.21814.218
3156021HOLLOMANSOL
80/20
0.7790.779
3156073AA1-063SOLA
80/20
0.5950.595
3151371ROSEMS1
80/20
0.5440.544
961671AG1-007 C
Adder
0.410588235294117640.349
934621AD1-088 C
80/20
4.3624.362
958161AF2-110 C
Adder
0.53058823529411770.451
316017AA1-139 ULT1
80/20
0.4540.454
938531AE1-072 C
80/20
7.3717.371
315614AA2-178 C
80/20
0.6580.658
933981AD1-022 C
80/20
3.6993.699
3151261ROARAP2
80/20
0.5930.593
3147043LAWRENC
80/20
0.130.13
3152411Z1-086 GT1
80/20
7.0067.006
3151621KERR 5
80/20
0.4940.494
316349AD2-085 C
Adder
1.15882352941176480.985
3151091ELIZAR2
80/20
1.2731.273
316023AB2-100 C2
80/20
0.4150.415
946281AF1-292 C
80/20
0.6630.663
926071AC1-086 C
80/20
9.0389.038
316317KELFORD C
80/20
0.1530.153
3151051BRUNSWICKS1
80/20
11.26211.262
927021AC1-189 C
Adder
3.66117647058823573.112
3151531CLOVER1
80/20
6.3346.334
964241AG1-285 C
80/20
5.3655.365
962561AG1-105 C
Adder
3.70941176470588243.153
316365AB2-100 C1
80/20
0.4150.415
316318V4-068 C
80/20
0.0340.034
316210AC1-098 C
80/20
0.4070.407
3151041BRUNSWICKG3
80/20
5.4215.421
3151021BRUNSWICKG1
80/20
5.4215.421
935171AD1-152 C
80/20
0.6380.638
964791AG1-342 C
Adder
1.48470588235294131.262
3150981CHESPKA
80/20
0.1750.175
316185AD1-033 C
80/20
0.5160.516
944581AF1-123 C
80/20
19.1219.12
941101AE2-104 C
Adder
1.31.105
316320Y1-086 C
80/20
0.0920.092
3156083AA2-088SOLA
80/20
0.4390.439
313506AB1-173 C OP
80/20
0.4830.483
3151361ROSEMG1
80/20
0.8780.878
957481AF2-042 C
80/20
28.34128.341
3156116Z1-036WIND
80/20
0.2750.275
939411AE1-173 C
80/20
55.12655.126
3152921DOMTR78
80/20
0.5790.579
316140AB2-099 C
80/20
0.0410.041
3137643SOCKMAN
80/20
0.3050.305
316212AC1-099 C
80/20
0.1360.136
3151031BRUNSWICKG2
80/20
5.4215.421
937481AD2-202 C
80/20
0.1810.181
3151641KERR 7
80/20
0.4940.494
942341AE2-247 C
Adder
0.50235294117647060.427
316246AF1-032 C
80/20
0.1150.115
316388AE2-253 GEN
80/20
0.8260.826
966621AG1-532 C
80/20
0.6010.601
936161AD2-022 C
Adder
3.0882352941176472.625
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5712.571
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.69643.696
NYPJM->LTFIMP_NY
CLTF
0.5140.514
LGEELTFEXP_LGEE->PJM
CLTF
0.4480.448
WECLTFEXP_WEC->PJM
CLTF
0.2390.239
SIGELTFEXP_SIGE->PJM
CLTF
0.0910.091
CPLELTFEXP_CPLE->PJM
CLTF
5.3965.396
TVALTFEXP_TVA->PJM
CLTF
2.4942.494
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.53211.532
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.0379.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5141.514
LAGNLTFEXP_LAGN->PJM
CLTF
3.2073.207

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.98 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4293.98
MW Contribution:234.92
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316084AB2-161 E
Adder
8.717647058823537.41
3145946PLYMOUTH TP
Adder
0.50.425
933982AD1-022 E
Adder
7.3576470588235296.254
940641AE2-051 C
50/50
29.19229.192
316336AC2-165 C
Adder
14.85411764705882312.626
934622AD1-088 E
Adder
6.9164705882352945.879
934612AD1-087 E
Adder
5.42823529411764754.614
3151101ELIZAR3
50/50
5.1725.172
316315AB2-025 C
50/50
0.650.65
946282AF1-292 E
Adder
1.58588235294117651.348
944012AF1-069 E
50/50
8.3958.395
935162AD1-151 E
Adder
16.1505882352941213.728
316233AE1-074 C
50/50
4.1784.178
943461AF1-017 C
Adder
2.1352941176470591.815
932596AC2-079 E
Adder
14.80823529411764712.587
316311AC2-079 C
Adder
9.0764705882352947.715
938532AE1-072 E
Adder
14.59294117647058912.404
3146326AYDLETT TAP
Adder
2.161.836
917122Z2-027 E
Adder
2.12941176470588231.81
920692AA2-178 E
Adder
6.45.44
966622AG1-532 E
Adder
1.43647058823529421.221
925332AB2-190 E
Adder
12.07529411764705810.264
927226AC1-216 E
Adder
11.6423529411764739.896
936666AD2-085 E
Adder
8.8858823529411777.553
941591AE2-156 C
50/50
28.55328.553
3151081ELIZAR1
50/50
5.1085.108
316316AC1-027 C
50/50
0.5040.504
944591AF1-124 C
50/50
72.79772.797
944601AF1-125 C
50/50
71.42271.422
938771AE1-103 C
Adder
4.5952941176470593.906
3145413WATKINS
Adder
1.07882352941176470.917
960081AF2-299 C
Adder
2.87294117647058832.442
926072AC1-086 E
Adder
14.54823529411764812.366
944011AF1-069 C
50/50
21.6121.61
3150841SPRUNCB
Adder
14.05529411764705811.947
3150831SPRUNCA
Adder
14.05529411764705811.947
926662AC1-147 E
Adder
2.1117647058823531.795
916192Z1-068 E
50/50
3.0013.001
957492AF2-043 E
Adder
2.25882352941176471.92
923852AB2-025 E
50/50
1.8511.851
939412AE1-173 E
50/50
100.688100.688
923862AB2-026 E
Adder
1.9247058823529411.636
941032AE2-094 E
50/50
29.62229.622
941031AE2-094 C
50/50
66.13866.138
944641AF1-129 C
Adder
153.60588235294117130.565
316240AF1-291 C
Adder
3.2635294117647062.774
924814AB2-134 E
Adder
19.07058823529411716.21
942342AE2-247 E
Adder
3.262.771
919152AA1-139 E1
Adder
6.5152941176470595.538
920042AA2-088 E OP
Adder
16.40941176470588313.948
934521AD1-076 C
Adder
18.92352941176470816.085
934511AD1-075 C
Adder
13.02705882352941211.073
3145723EMPORIA
Adder
0.66117647058823540.562
923573AB1-173 E OP
Adder
5.0141176470588234.262
942001AE2-212 C
Adder
3.34588235294117632.844
939192AE1-149 E
Adder
11.2529411764705879.565
939312AE1-162 E
Adder
2.22705882352941181.893
934065AD1-033 E
50/50
8.0198.019
937226AE2-253 E
Adder
9.322352941176477.924
934501AD1-074 C
Adder
52.1070588235294144.291
958502AF2-144 E
Adder
1.89058823529411771.607
924517AB2-100 E2
Adder
4.4917647058823533.818
957482AF2-042 E
Adder
55.1988235294117646.919
934621AD1-088 C
Adder
14.36470588235294312.21
938552AE1-074 E
50/50
2.1052.105
3150921YORKTN3
Adder
175.7670588235294149.402
3145256KINGFORK
Adder
1.5952941176470591.356
925522AC1-027 E
50/50
1.9431.943
933291AC2-141 C
50/50
48.63248.632
926755AC1-161 E
50/50
20.7620.76
941102AE2-104 E
Adder
8.4494117647058827.182
957872AF2-081 E
Adder
6.8282352941176485.804
938562AE1-075 E
Adder
1.64117647058823551.395
961611AG1-000B C
Adder
24.2858823529411820.643
316375AC2-012 C
50/50
2.1542.154
940541AE2-040 C
50/50
4.5764.576
940481AE2-033 C
50/50
25.70925.709
940482AE2-033 E
50/50
17.33217.332
923263AB1-132 E OP
Adder
9.3023529411764717.907
3152441Z1-086 ST
50/50
30.16330.163
3152431Z1-086 GT3
50/50
17.32117.321
3152421Z1-086 GT2
50/50
17.32117.321
963041AG1-153 C
50/50
9.159.15
3150651CHESTF6
Adder
27.96823529411764823.773
946262AF1-291 E
Adder
2.17647058823529441.85
934576AD1-082 E
Adder
6.9458823529411775.904
916191Z1-068 C
50/50
0.070.07
933292AC2-141 E
50/50
20.7620.76
316294AC1-161 C
50/50
7.9477.947
944602AF1-125 E
50/50
163.5163.5
3145506HICKORY
50/50
3.4833.483
943612AF1-032 E
Adder
1.4682352941176471.248
957871AF2-081 C
Adder
15.93294117647058713.543
940492AE2-034 E
Adder
4.84.08
934522AD1-076 E
Adder
9.6458823529411778.199
918492AA1-063AE OP
Adder
6.2388235294117655.303
962571AG1-106 C
Adder
3.9470588235294123.355
937482AD2-202 E
Adder
1.58941176470588231.351
939191AE1-149 C
Adder
16.88000000000000314.348
3143316POE
50/50
2.1752.175
901082W1-029 E
Adder
50.41764705882352642.855
3151041BRUNSWICKG3
50/50
13.50613.506
3151021BRUNSWICKG1
50/50
13.50613.506
940431AE2-027 C
Adder
19.56823529411764516.633
942002AE2-212 E
Adder
2.23058823529411751.896
316185AD1-033 C
50/50
1.9651.965
944581AF1-123 C
50/50
72.53972.539
941101AE2-104 C
Adder
5.3141176470588244.517
316088AB2-174 E
Adder
9.988.483
923994AB2-040_E
Adder
9.4011764705882357.991
957481AF2-042 C
Adder
82.7976470588235370.378
316349AD2-085 C
Adder
5.4458823529411764.629
935112AD1-144 E
Adder
1.48117647058823531.259
3151091ELIZAR2
50/50
5.0195.019
944582AF1-123 E
50/50
166.107166.107
944592AF1-124 E
50/50
166.709166.709
923832AB2-022 E
Adder
1.96941176470588241.674
938772AE1-103 E
Adder
6.3458823529411775.394
916042Z1-036 E
Adder
44.8811764705882438.149
960082AF2-299 E
Adder
1.91529411764705881.628
946281AF1-292 C
Adder
2.37764705882352922.021
926071AC1-086 C
Adder
31.96588235294117627.171
3151051BRUNSWICKS1
50/50
28.05828.058
963042AG1-153 E
50/50
13.72513.725
942341AE2-247 C
Adder
2.362.006
943462AF1-017 E
Adder
3.48470588235294132.962
958162AF2-110 E
Adder
3.4494117647058822.932
919153AA1-139 E2
Adder
6.5152941176470595.538
934512AD1-075 E
Adder
6.6317647058823535.637
934502AD1-074 E
Adder
26.5247058823529422.546
924516AB2-100 E1
Adder
4.4917647058823533.818
940642AE2-051 E
50/50
19.46119.461
966621AG1-532 C
Adder
2.15411764705882371.831
940432AE2-027 E
Adder
13.04588235294117711.089
934012AD1-025 E
Adder
15.07294117647058812.812
913392Y1-086 E
Adder
3.48941176470588272.966
939411AE1-173 C
50/50
151.032151.032
933502AC2-165 E
Adder
11.189.503
3151031BRUNSWICKG2
50/50
13.50613.506
3150731STONECA
Adder
10.1976470588235298.668
935161AD1-151 C
Adder
24.22470588235294320.591
932046AC2-012 E
50/50
20.89320.893
958161AF2-110 C
Adder
2.16823529411764731.843
938531AE1-072 C
Adder
27.99411764705882523.795
3145393UNCAMP
Adder
9.5200000000000018.092
933981AD1-022 C
Adder
13.5152941176470611.488
900672V4-068 E
Adder
0.54941176470588240.467
3152411Z1-086 GT1
50/50
17.32817.328
316303AF2-085
50/50
6.8996.899
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6737.673
CBM South 2LTFEXP_CBM-S2->PJM
CBM
132.286132.286
NYPJM->LTFIMP_NY
CLTF
2.7212.721
LGEELTFEXP_LGEE->PJM
CLTF
1.6421.642
WECLTFEXP_WEC->PJM
CLTF
0.8540.854
G-007PJM->LTFIMP_G-007
CMTX_NF
5.8875.887
SIGELTFEXP_SIGE->PJM
CLTF
0.3220.322
CPLELTFEXP_CPLE->PJM
CLTF
16.09616.096
TVALTFEXP_TVA->PJM
CLTF
8.1488.148
O66PJM->LTFIMP_O-066
CMTX_NF
37.46537.465
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.00241.002
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.98729.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.2215.221
LAGNLTFEXP_LAGN->PJM
CLTF
10.36610.366

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.85 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4130.98
MW Contribution:237.26
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.17 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4734.56
MW Contribution:242.98
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935162AD1-151 E
Adder
15.4776470588235313.156
316233AE1-074 C
50/50
3.8433.843
943461AF1-017 C
Adder
2.1105882352941181.794
932596AC2-079 E
Adder
14.6612.461
316311AC2-079 C
Adder
8.9858823529411777.638
3150841SPRUNCB
Adder
12.67882352941176410.777
3150831SPRUNCA
Adder
12.67882352941176410.777
926662AC1-147 E
Adder
2.12823529411764721.809
925332AB2-190 E
Adder
11.5164705882352939.789
927226AC1-216 E
Adder
11.2188235294117659.536
962962AG1-145 E
Adder
2.0305882352941181.726
936666AD2-085 E
Adder
8.7835294117647067.466
941591AE2-156 C
50/50
28.7728.77
3151081ELIZAR1
50/50
5.1485.148
316316AC1-027 C
50/50
0.5090.509
944591AF1-124 C
50/50
73.52173.521
944601AF1-125 C
50/50
72.13372.133
938771AE1-103 C
Adder
4.582352941176473.895
3145413WATKINS
Adder
1.07411764705882360.913
960081AF2-299 C
Adder
2.822.397
926072AC1-086 E
Adder
14.32823529411764712.179
944011AF1-069 C
50/50
21.50921.509
963041AG1-153 C
50/50
9.0979.097
946262AF1-291 E
Adder
2.00235294117647071.702
934576AD1-082 E
Adder
6.7411764705882365.73
916191Z1-068 C
50/50
0.0710.071
933292AC2-141 E
50/50
21.18321.183
316294AC1-161 C
50/50
8.1098.109
944602AF1-125 E
50/50
165.126165.126
3145506HICKORY
50/50
3.5173.517
943612AF1-032 E
Adder
1.4764705882352941.255
957871AF2-081 C
Adder
16.07411764705882413.663
940492AE2-034 E
Adder
4.8023529411764714.082
934522AD1-076 E
Adder
9.6317647058823528.187
943172AE2-346 E
Adder
0.92117647058823540.783
918492AA1-063AE OP
Adder
6.1705882352941185.245
962571AG1-106 C
Adder
4.07176470588235253.461
917332KELFORD E
Adder
2.4741176470588242.103
925122AB2-169 E
Adder
8.6764705882352937.375
937482AD2-202 E
Adder
1.5682352941176471.333
939191AE1-149 C
Adder
16.1694117647058813.744
3143316POE
Adder
2.0705882352941181.76
901082W1-029 E
Adder
50.6800000000000143.078
3151041BRUNSWICKG3
50/50
13.42713.427
3151021BRUNSWICKG1
50/50
13.42713.427
961611AG1-000B C
Adder
23.7620.196
316375AC2-012 C
50/50
2.172.17
940541AE2-040 C
Adder
4.4623529411764713.793
940481AE2-033 C
Adder
25.0882352941176521.325
940482AE2-033 E
Adder
16.9129411764705914.376
923263AB1-132 E OP
Adder
9.162352941176477.788
3152441Z1-086 ST
50/50
29.99929.999
3152431Z1-086 GT3
50/50
17.22617.226
3152421Z1-086 GT2
50/50
17.22617.226
316084AB2-161 E
Adder
8.467.191
3145946PLYMOUTH TP
Adder
0.50.425
933982AD1-022 E
Adder
7.346.239
940641AE2-051 C
50/50
29.19929.199
934622AD1-088 E
Adder
6.8105882352941185.789
934612AD1-087 E
Adder
5.3588235294117644.555
938532AE1-072 E
Adder
14.7176470588235312.51
3146326AYDLETT TAP
Adder
2.17764705882352951.851
917122Z2-027 E
Adder
2.1435294117647061.822
920692AA2-178 E
Adder
6.4035294117647065.443
966622AG1-532 E
Adder
1.41058823529411771.199
938552AE1-074 E
50/50
1.9361.936
316160AE1-175 E
Adder
1.67529411764705881.424
3150921YORKTN3
Adder
176.88117647058823150.349
3145256KINGFORK
Adder
1.61.36
925522AC1-027 E
50/50
1.961.96
933291AC2-141 C
50/50
49.62549.625
926755AC1-161 E
50/50
21.18321.183
941102AE2-104 E
Adder
8.4505882352941187.183
957872AF2-081 E
Adder
6.88823529411764755.855
938562AE1-075 E
Adder
1.53176470588235311.302
962572AG1-106 E
Adder
1.78117647058823541.514
964242AG1-285 E
Adder
12.5610.676
944641AF1-129 C
Adder
128.6564705882353109.358
316240AF1-291 C
Adder
3.0047058823529412.554
924814AB2-134 E
Adder
18.37647058823529315.62
942342AE2-247 E
Adder
3.22235294117647042.739
919152AA1-139 E1
Adder
6.57294117647058855.587
920042AA2-088 E OP
Adder
16.29647058823529413.852
934521AD1-076 C
Adder
18.8976470588235316.063
3151101ELIZAR3
50/50
5.2135.213
946282AF1-292 E
Adder
1.5564705882352941.323
944012AF1-069 E
50/50
8.3568.356
934511AD1-075 C
Adder
13.00823529411764811.057
3145723EMPORIA
Adder
0.65058823529411770.553
923573AB1-173 E OP
Adder
4.9341176470588244.194
919692AA2-053 E OP
Adder
6.3423529411764715.391
942001AE2-212 C
Adder
3.1211764705882352.653
939192AE1-149 E
Adder
10.7800000000000019.163
939312AE1-162 E
Adder
2.21058823529411751.879
934065AD1-033 E
50/50
8.0978.097
937226AE2-253 E
50/50
9.4079.407
934501AD1-074 C
Adder
52.03294117647059444.228
958502AF2-144 E
Adder
1.76470588235294111.5
924517AB2-100 E2
Adder
4.4035294117647063.743
957482AF2-042 E
Adder
54.5552941176470646.372
934621AD1-088 C
Adder
14.14588235294117512.024
916192Z1-068 E
50/50
3.0273.027
957492AF2-043 E
Adder
2.2717647058823531.931
923852AB2-025 E
Adder
1.80470588235294121.534
939412AE1-173 E
50/50
100.92100.92
923862AB2-026 E
Adder
1.7964705882352941.527
961942AG1-037 E
Adder
0.51176470588235290.435
961941AG1-037 C
Adder
0.76823529411764710.653
941032AE2-094 E
50/50
29.48329.483
941031AE2-094 C
50/50
65.82865.828
316349AD2-085 C
Adder
5.3835294117647054.576
935112AD1-144 E
Adder
1.48470588235294131.262
3151091ELIZAR2
50/50
5.0595.059
944582AF1-123 E
50/50
167.759167.759
944592AF1-124 E
50/50
168.367168.367
923832AB2-022 E
Adder
1.98352941176470581.686
938772AE1-103 E
Adder
6.3270588235294125.378
916042Z1-036 E
Adder
45.0211764705882438.268
960082AF2-299 E
Adder
1.88000000000000011.598
946281AF1-292 C
Adder
2.33411764705882341.984
926071AC1-086 C
Adder
31.48235294117647226.76
3151051BRUNSWICKS1
50/50
27.89527.895
963042AG1-153 E
50/50
13.64513.645
964241AG1-285 C
Adder
18.8416.014
940432AE2-027 E
Adder
12.12235294117647110.304
934012AD1-025 E
Adder
14.52470588235294212.346
913392Y1-086 E
Adder
3.51411764705882362.987
939411AE1-173 C
50/50
151.38151.38
3137643SOCKMAN
Adder
1.06823529411764720.908
3151031BRUNSWICKG2
50/50
13.42713.427
3150731STONECA
Adder
9.5694117647058838.134
935161AD1-151 C
Adder
23.2152941176470619.733
932046AC2-012 E
50/50
21.04921.049
958161AF2-110 C
Adder
2.16941176470588241.844
938531AE1-072 C
Adder
28.2329411764705923.998
3145393UNCAMP
Adder
9.4858823529411778.063
933981AD1-022 C
Adder
13.48352941176470711.461
900672V4-068 E
Adder
0.54588235294117650.464
3152411Z1-086 GT1
50/50
17.23317.233
940431AE2-027 C
Adder
18.18352941176470615.456
942002AE2-212 E
Adder
2.0811764705882351.769
316185AD1-033 C
50/50
1.9851.985
944581AF1-123 C
50/50
73.26173.261
941101AE2-104 C
Adder
5.3152941176470594.518
316141AB2-099 E
Adder
0.38352941176470590.326
316088AB2-174 E
Adder
9.8129411764705888.341
923994AB2-040_E
Adder
9.2505882352941197.863
957481AF2-042 C
Adder
81.8317647058823669.557
942341AE2-247 C
Adder
2.33294117647058831.983
943462AF1-017 E
Adder
3.44470588235294132.928
958162AF2-110 E
Adder
3.45058823529411772.933
316388AE2-253 GEN
50/50
3.1643.164
919153AA1-139 E2
Adder
6.57294117647058855.587
934512AD1-075 E
Adder
6.622352941176475.629
934502AD1-074 E
Adder
26.48705882352941322.514
924516AB2-100 E1
Adder
4.4035294117647063.743
918512AA1-065 E OP
Adder
8.4305882352941197.166
940642AE2-051 E
50/50
19.46619.466
966621AG1-532 C
Adder
2.11529411764705881.798
316303AF2-085
50/50
6.4766.476
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.547.54
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.173129.173
NYPJM->LTFIMP_NY
CLTF
2.5392.539
LGEELTFEXP_LGEE->PJM
CLTF
1.4991.499
G-007PJM->LTFIMP_G-007
CMTX_NF
5.4635.463
SIGELTFEXP_SIGE->PJM
CLTF
0.2970.297
WECLTFEXP_WEC->PJM
CLTF
0.780.78
CPLELTFEXP_CPLE->PJM
CLTF
15.81915.819
TVALTFEXP_TVA->PJM
CLTF
7.767.76
O66PJM->LTFIMP_O-066
CMTX_NF
34.77734.777
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.34537.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.31928.319
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8474.847
LAGNLTFEXP_LAGN->PJM
CLTF
9.8929.892

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.96 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4056.76
MW Contribution:220.8
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
Adder
25.5882352941176521.75
946262AF1-291 E
Adder
1.99529411764705891.696
934576AD1-082 E
Adder
6.4764705882352945.505
916191Z1-068 C
50/50
0.0660.066
933292AC2-141 E
50/50
19.5219.52
316294AC1-161 C
50/50
7.4737.473
944602AF1-125 E
50/50
153.669153.669
3145506HICKORY
50/50
3.2743.274
943612AF1-032 E
Adder
1.38000000000000011.173
957871AF2-081 C
Adder
14.97647058823529412.73
940492AE2-034 E
Adder
4.5188235294117653.841
934522AD1-076 E
Adder
9.0858823529411777.723
918492AA1-063AE OP
Adder
5.8905882352941185.007
962571AG1-106 C
Adder
3.90588235294117643.32
937482AD2-202 E
Adder
1.5152941176470591.288
316084AB2-161 E
Adder
8.1282352941176486.909
3145946PLYMOUTH TP
Adder
0.47058823529411770.4
933982AD1-022 E
Adder
6.9329411764705885.893
940641AE2-051 C
50/50
27.86227.862
316336AC2-165 C
Adder
14.02588235294117811.922
934622AD1-088 E
Adder
6.5941176470588245.605
934612AD1-087 E
Adder
5.17764705882352954.401
935162AD1-151 E
Adder
14.89411764705882412.66
316233AE1-074 C
50/50
3.8973.897
943461AF1-017 C
Adder
2.01.7
932596AC2-079 E
Adder
13.86941176470588211.789
316311AC2-079 C
Adder
8.5011764705882367.226
938532AE1-072 E
Adder
13.7176470588235311.66
3146326AYDLETT TAP
Adder
2.02941176470588271.725
917122Z2-027 E
Adder
2.00235294117647071.702
920692AA2-178 E
Adder
6.0258823529411775.122
966622AG1-532 E
Adder
1.35764705882352941.154
938552AE1-074 E
50/50
1.9631.963
3150921YORKTN3
Adder
163.19176470588235138.713
3145256KINGFORK
Adder
1.49529411764705871.271
925522AC1-027 E
50/50
1.8261.826
933291AC2-141 C
50/50
45.72845.728
926755AC1-161 E
50/50
19.5219.52
941102AE2-104 E
Adder
7.9317647058823536.742
957872AF2-081 E
Adder
6.4188235294117665.456
938562AE1-075 E
Adder
1.55058823529411781.318
962572AG1-106 E
Adder
1.7082352941176471.452
961611AG1-000B C
Adder
22.53529411764706219.155
316375AC2-012 C
50/50
2.0222.022
940541AE2-040 C
50/50
4.3194.319
940481AE2-033 C
50/50
24.26824.268
940482AE2-033 E
50/50
16.3616.36
923263AB1-132 E OP
Adder
8.7870588235294127.469
3152441Z1-086 ST
50/50
28.8528.85
3152431Z1-086 GT3
50/50
16.56616.566
3152421Z1-086 GT2
50/50
16.56616.566
3151101ELIZAR3
50/50
4.8574.857
316315AB2-025 C
50/50
0.6130.613
946282AF1-292 E
Adder
1.49882352941176471.274
944012AF1-069 E
50/50
8.0328.032
944641AF1-129 C
Adder
140.53529411764706119.455
316240AF1-291 C
Adder
2.99294117647058842.544
924814AB2-134 E
Adder
17.61647058823529514.974
942342AE2-247 E
Adder
3.0517647058823532.594
919152AA1-139 E1
Adder
6.1235294117647065.205
920042AA2-088 E OP
Adder
15.46470588235294113.145
934521AD1-076 C
Adder
17.82705882352941315.153
934511AD1-075 C
Adder
12.27176470588235310.431
3145723EMPORIA
Adder
0.62588235294117660.532
923573AB1-173 E OP
Adder
4.744.029
925332AB2-190 E
Adder
11.1200000000000019.452
927226AC1-216 E
Adder
10.7541176470588239.141
936666AD2-085 E
Adder
8.327.072
941591AE2-156 C
50/50
26.80726.807
3151081ELIZAR1
50/50
4.7964.796
316316AC1-027 C
50/50
0.4740.474
944591AF1-124 C
50/50
68.4268.42
944601AF1-125 C
50/50
67.12767.127
938771AE1-103 C
Adder
4.3211764705882353.673
3145413WATKINS
Adder
1.0152941176470590.863
960081AF2-299 C
Adder
2.7152941176470592.308
926072AC1-086 E
Adder
13.7423529411764711.681
944011AF1-069 C
50/50
20.67620.676
963041AG1-153 C
50/50
8.758.75
3150841SPRUNCB
Adder
12.87647058823529510.945
3150831SPRUNCA
Adder
12.87647058823529510.945
926662AC1-147 E
Adder
1.98235294117647071.685
916192Z1-068 E
50/50
2.8192.819
957492AF2-043 E
Adder
2.12235294117647081.804
923852AB2-025 E
50/50
1.7471.747
939412AE1-173 E
50/50
95.76595.765
923862AB2-026 E
Adder
1.81882352941176471.546
941032AE2-094 E
50/50
28.34228.342
941031AE2-094 C
50/50
63.2863.28
942001AE2-212 C
Adder
3.08941176470588232.626
939192AE1-149 E
Adder
10.4635294117647078.894
939312AE1-162 E
Adder
2.07764705882352941.766
934065AD1-033 E
50/50
7.5367.536
937226AE2-253 E
Adder
8.7623529411764727.448
934501AD1-074 C
Adder
49.0858823529411841.723
958502AF2-144 E
Adder
1.78705882352941181.519
924517AB2-100 E2
Adder
4.2411764705882353.605
957482AF2-042 E
Adder
52.67882352941176544.777
934621AD1-088 C
Adder
13.69411764705882511.64
935161AD1-151 C
Adder
22.3418.989
932046AC2-012 E
50/50
19.61519.615
958161AF2-110 C
Adder
2.03529411764705871.73
938531AE1-072 C
Adder
26.31411764705882622.367
3145393UNCAMP
Adder
8.9552941176470597.612
933981AD1-022 C
Adder
12.73411764705882410.824
900672V4-068 E
Adder
0.51764705882352950.44
3152411Z1-086 GT1
50/50
16.57316.573
316349AD2-085 C
Adder
5.09882352941176454.334
935112AD1-144 E
Adder
1.3882352941176471.18
3151091ELIZAR2
50/50
4.7134.713
944582AF1-123 E
50/50
156.119156.119
944592AF1-124 E
50/50
156.684156.684
923832AB2-022 E
Adder
1.8517647058823531.574
938772AE1-103 E
Adder
5.9670588235294125.072
916042Z1-036 E
Adder
42.2247058823529435.891
960082AF2-299 E
Adder
1.81058823529411761.539
946281AF1-292 C
Adder
2.24823529411764731.911
926071AC1-086 C
Adder
30.19411764705882525.665
3151051BRUNSWICKS1
50/50
26.83226.832
963042AG1-153 E
50/50
13.12513.125
964241AG1-285 C
Adder
6.4458823529411775.479
939191AE1-149 C
Adder
15.69529411764705913.341
3143316POE
50/50
2.0282.028
901082W1-029 E
Adder
47.440.29
3151041BRUNSWICKG3
50/50
12.91612.916
3151021BRUNSWICKG1
50/50
12.91612.916
940431AE2-027 C
Adder
17.9905882352941215.292
942002AE2-212 E
Adder
2.0588235294117651.75
316185AD1-033 C
50/50
1.8471.847
944581AF1-123 C
50/50
68.17868.178
941101AE2-104 C
Adder
4.9894117647058824.241
316088AB2-174 E
Adder
9.4352941176470598.02
923994AB2-040_E
Adder
8.8870588235294117.554
957481AF2-042 C
Adder
79.0188235294117667.166
940432AE2-027 E
Adder
11.99411764705882410.195
934012AD1-025 E
Adder
13.92352941176470811.835
913392Y1-086 E
Adder
3.282.788
939411AE1-173 C
50/50
143.648143.648
933502AC2-165 E
Adder
10.5564705882352968.973
3137643SOCKMAN
Adder
1.02470588235294110.871
3151031BRUNSWICKG2
50/50
12.91612.916
942341AE2-247 C
Adder
2.21058823529411751.879
943462AF1-017 E
Adder
3.2623529411764712.773
958162AF2-110 E
Adder
3.2376470588235292.752
919153AA1-139 E2
Adder
6.1235294117647065.205
934512AD1-075 E
Adder
6.2470588235294125.31
934502AD1-074 E
Adder
24.98705882352941321.239
924516AB2-100 E1
Adder
4.2411764705882353.605
940642AE2-051 E
50/50
18.57518.575
966621AG1-532 C
Adder
2.03647058823529431.731
316303AF2-085
50/50
6.5326.532
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.2837.283
CBM South 2LTFEXP_CBM-S2->PJM
CBM
125.379125.379
NYPJM->LTFIMP_NY
CLTF
2.5532.553
LGEELTFEXP_LGEE->PJM
CLTF
1.5241.524
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5125.512
SIGELTFEXP_SIGE->PJM
CLTF
0.30.3
WECLTFEXP_WEC->PJM
CLTF
0.7920.792
CPLELTFEXP_CPLE->PJM
CLTF
15.2815.28
TVALTFEXP_TVA->PJM
CLTF
7.6637.663
O66PJM->LTFIMP_O-066
CMTX_NF
35.08335.083
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.98737.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.12228.122
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8684.868
LAGNLTFEXP_LAGN->PJM
CLTF
9.7559.755

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.07 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3287.01
MW Contribution:65.2
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150731STONECA
Adder
8.9505882352941187.608
935161AD1-151 C
Adder
21.46588235294117618.246
3151221GRAVEL6
80/20
3.4833.483
3151201GRAVEL4
80/20
3.4873.487
943471AF1-018 C
Adder
7.9588235294117656.765
316083AB2-161 C
80/20
0.7870.787
316072AD1-144 C
80/20
0.4020.402
940641AE2-051 C
80/20
27.30727.307
316336AC2-165 C
Adder
13.69411764705882511.64
934611AD1-087 C
80/20
1.761.76
3150841SPRUNCB
80/20
12.34712.347
3150831SPRUNCA
80/20
12.34712.347
961941AG1-037 C
Adder
0.71058823529411760.604
941031AE2-094 C
80/20
62.11762.117
934331AD1-057 C
Adder
4.7623529411764714.048
934321AD1-056 C
Adder
8.5376470588235297.257
3151101ELIZAR3
80/20
4.7154.715
316315AB2-025 C
80/20
0.5980.598
961951AG1-038 C
Adder
3.3341176470588242.834
957861AF2-080 C
Adder
10.3623529411764718.808
3138533PONTONDP
Adder
0.87294117647058820.742
961611AG1-000B C
Adder
21.72352941176470518.465
316236AE1-162 C
80/20
0.4930.493
3152331SURRY 2
80/20
34.47834.478
316375AC2-012 C
80/20
1.9631.963
313526AB2-022 C
80/20
0.5460.546
940541AE2-040 C
80/20
4.2084.208
940481AE2-033 C
80/20
23.64823.648
3152441Z1-086 ST
80/20
28.31628.316
3152431Z1-086 GT3
80/20
16.2616.26
3152421Z1-086 GT2
80/20
16.2616.26
316233AE1-074 C
80/20
3.7763.776
940551AE2-041 C
Adder
7.9588235294117656.765
3151211GRAVEL5
80/20
3.4433.443
943461AF1-017 C
80/20
1.9381.938
316311AC2-079 C
80/20
8.2428.242
3156056W1-029WIND
80/20
1.1231.123
3150601CHESTF5
Adder
76.7117647058823665.205
941591AE2-156 C
80/20
26.02126.021
3151081ELIZAR1
80/20
4.6564.656
316316AC1-027 C
80/20
0.460.46
944591AF1-124 C
80/20
66.45566.455
944601AF1-125 C
80/20
65.265.2
938771AE1-103 C
80/20
4.24.2
960081AF2-299 C
Adder
2.64941176470588242.252
944011AF1-069 C
80/20
20.29620.296
963041AG1-153 C
80/20
8.5888.588
3151541CLOVER2
80/20
17.71117.711
936261AD2-033 C
Adder
17.57529411764705814.939
961791AG1-021 C
Adder
2.35764705882352972.004
958211AF2-115 C
Adder
2.94705882352941152.505
944641AF1-129 C
Adder
134.59058823529412114.402
316240AF1-291 C
Adder
2.86941176470588262.439
316381AD1-082 C
80/20
1.7951.795
316036AC1-147 C
80/20
0.5360.536
316018AA1-139 ULT2
80/20
1.5751.575
934521AD1-076 C
Adder
17.34705882352941214.745
934511AD1-075 C
Adder
11.94117647058823610.15
316263AC1-034 C
Adder
8.8741176470588247.543
959311AF2-222 C
Adder
23.07176470588235519.611
942001AE2-212 C
80/20
2.9732.973
3151161SURRY 1
80/20
33.88933.889
3150991CHESPKB
80/20
1.051.05
316321Z2-027 C
80/20
0.5270.527
943741AF1-042 C
Adder
3.01647058823529422.564
934501AD1-074 C
Adder
47.763529411764740.599
961671AG1-007 C
Adder
1.26588235294117671.076
934621AD1-088 C
80/20
13.42613.426
946301AF1-294 C
Adder
4.8470588235294124.12
942461AE2-259 C
Adder
12.70588235294117810.8
944631AF1-128 C
Adder
48.040.8
3150921YORKTN3
Adder
157.0388235294118133.483
933291AC2-141 C
80/20
44.42644.426
316305AF2-043 C
80/20
0.5050.505
3150651CHESTF6
Adder
24.50588235294117520.83
916191Z1-068 C
80/20
0.0640.064
316294AC1-161 C
80/20
7.267.26
957871AF2-081 C
80/20
14.54714.547
936591AD2-074 C
Adder
5.7647058823529424.9
3151151S HAMPT1
80/20
2.1352.135
316313AB2-026 C
80/20
0.5480.548
962571AG1-106 C
Adder
3.80823529411764743.237
316274AC1-208 C
Adder
12.4023529411764710.542
3151311EDGECMA
Adder
20.74352941176470817.632
939191AE1-149 C
80/20
15.16215.162
957601AF2-054 C
Adder
2.37764705882352922.021
316365AB2-100 C1
80/20
1.3721.372
3151041BRUNSWICKG3
80/20
12.67612.676
3151021BRUNSWICKG1
80/20
12.67612.676
964791AG1-342 C
Adder
4.6788235294117653.977
3150861SPRUNCD
80/20
0.2220.222
940431AE2-027 C
Adder
17.26588235294117614.676
3150981CHESPKA
80/20
0.6340.634
316185AD1-033 C
80/20
1.7941.794
944581AF1-123 C
80/20
66.2266.22
941101AE2-104 C
80/20
4.8434.843
316320Y1-086 C
80/20
0.3190.319
316405AF2-144 C
80/20
0.4280.428
957481AF2-042 C
80/20
77.49977.499
316169AC1-164 GEN
Adder
44.9588235294117738.215
316349AD2-085 C
80/20
4.9434.943
3151091ELIZAR2
80/20
4.5754.575
316258AE1-075 C
80/20
0.5030.503
316023AB2-100 C2
80/20
1.3721.372
946281AF1-292 C
Adder
2.19294117647058861.864
926071AC1-086 C
Adder
29.4425.024
3151051BRUNSWICKS1
80/20
26.33426.334
927021AC1-189 C
Adder
11.4094117647058839.698
3151531CLOVER1
80/20
17.87817.878
964241AG1-285 C
Adder
17.89058823529411815.207
962561AG1-105 C
Adder
11.8176470588235310.045
942341AE2-247 C
80/20
2.1432.143
316246AF1-032 C
80/20
0.4130.413
316388AE2-253 GEN
80/20
2.8622.862
966621AG1-532 C
Adder
1.9870588235294121.689
3150851SPRUNCC
80/20
0.2220.222
3156116Z1-036WIND
80/20
0.9440.944
939411AE1-173 C
80/20
140.502140.502
3137643SOCKMAN
Adder
1.00.85
3151031BRUNSWICKG2
80/20
12.67612.676
937481AD2-202 C
80/20
0.5110.511
958161AF2-110 C
80/20
1.9761.976
316017AA1-139 ULT1
80/20
1.5751.575
938531AE1-072 C
80/20
25.56125.561
933981AD1-022 C
Adder
12.39411764705882410.535
3152411Z1-086 GT1
80/20
16.26716.267
316303AF2-085
80/20
6.3826.382
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1347.134
NYPJM->LTFIMP_NY
CLTF
2.4692.469
LGEELTFEXP_LGEE->PJM
CLTF
1.5071.507
SIGELTFEXP_SIGE->PJM
CLTF
0.2960.296
WECLTFEXP_WEC->PJM
CLTF
0.7840.784
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.889122.889
CPLELTFEXP_CPLE->PJM
CLTF
14.96614.966
TVALTFEXP_TVA->PJM
CLTF
7.5327.532
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.6437.64
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.68227.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8064.806
LAGNLTFEXP_LAGN->PJM
CLTF
9.5879.587

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.59 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3225.32
MW Contribution:245.73
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.29 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3436.04
MW Contribution:246.71
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934576AD1-082 E
Adder
4.4847058823529413.812
916191Z1-068 C
50/50
0.0720.072
933292AC2-141 E
50/50
24.4824.48
316294AC1-161 C
50/50
9.3719.371
944602AF1-125 E
50/50
171.025171.025
3145506HICKORY
50/50
3.633.63
943612AF1-032 E
50/50
1.4511.451
957871AF2-081 C
50/50
16.44116.441
940492AE2-034 E
50/50
4.4344.434
934522AD1-076 E
Adder
8.667.361
943172AE2-346 E
Adder
0.76823529411764710.653
918492AA1-063AE OP
Adder
4.80941176470588254.088
962571AG1-106 C
Adder
2.94588235294117642.504
917332KELFORD E
Adder
2.01647058823529421.714
925122AB2-169 E
Adder
7.4694117647058836.349
316274AC1-208 C
Adder
10.168.636
917342Z2-044 E
Adder
0.65529411764705890.557
937482AD2-202 E
Adder
1.1129411764705880.946
3151311EDGECMA
Adder
16.76352941176470814.249
939191AE1-149 C
Adder
8.8411764705882367.515
901082W1-029 E
50/50
49.64949.649
926206AC1-098 E
Adder
4.2070588235294123.576
964791AG1-342 C
Adder
3.39411764705882352.885
961611AG1-000B C
Adder
17.5717647058823514.936
316236AE1-162 C
50/50
0.4750.475
3152331SURRY 2
50/50
52.22852.228
316375AC2-012 C
50/50
2.1982.198
313526AB2-022 C
50/50
0.6030.603
940541AE2-040 C
Adder
2.6435294117647062.247
940481AE2-033 C
Adder
15.09058823529411912.827
316084AB2-161 E
Adder
5.6282352941176474.784
316072AD1-144 C
50/50
0.4210.421
3145946PLYMOUTH TP
Adder
0.451764705882352960.384
933982AD1-022 E
Adder
6.5129411764705885.536
940641AE2-051 C
50/50
24.20324.203
927146AC1-208 E
Adder
4.5117647058823533.835
934622AD1-088 E
Adder
4.70470588235294153.999
934612AD1-087 E
Adder
3.80117647058823543.231
927255AC1-221 E
Adder
3.5270588235294122.998
957832AF2-077 E
Adder
1.38000000000000011.173
943461AF1-017 C
Adder
1.75294117647058821.49
932596AC2-079 E
Adder
12.36705882352941210.512
316311AC2-079 C
Adder
7.586.443
938532AE1-072 E
50/50
14.99614.996
3146326AYDLETT TAP
50/50
2.2162.216
917122Z2-027 E
50/50
2.1312.131
3156056W1-029WIND
50/50
1.211.21
920692AA2-178 E
50/50
5.9125.912
966622AG1-532 E
Adder
0.95882352941176460.815
922923AB1-081 E OP
Adder
4.0270588235294123.423
316160AE1-175 E
Adder
1.12470588235294120.956
3150921YORKTN3
50/50
162.48162.48
3145256KINGFORK
50/50
1.5181.518
925522AC1-027 E
50/50
2.0032.003
933291AC2-141 C
50/50
57.34757.347
926755AC1-161 E
50/50
24.4824.48
941102AE2-104 E
50/50
7.8957.895
316305AF2-043 C
50/50
0.5470.547
957872AF2-081 E
50/50
7.0467.046
962572AG1-106 E
Adder
1.28941176470588251.096
926214AC1-099 E
Adder
1.38941176470588231.181
932632AC2-084 E
Adder
3.71882352941176463.161
964242AG1-285 E
Adder
8.5011764705882367.226
924162AB2-060 E OP
Adder
4.1870588235294123.559
964792AG1-342 E
Adder
2.2623529411764711.923
940482AE2-033 E
Adder
10.1729411764705898.647
923263AB1-132 E OP
Adder
6.6282352941176485.634
925612AC1-036 E
Adder
0.80823529411764720.687
924312AB2-078 E O1
Adder
1.3164705882352941.119
926274AC1-105 E
Adder
2.5482352941176472.166
3151101ELIZAR3
50/50
5.3035.303
946282AF1-292 E
Adder
1.05882352941176470.9
944012AF1-069 E
50/50
6.346.34
957861AF2-080 C
Adder
8.8647058823529427.535
917512Z2-088 E OP1
Adder
5.58588235294117654.748
927226AC1-216 E
Adder
6.8258823529411765.802
962962AG1-145 E
Adder
1.36235294117647051.158
936666AD2-085 E
Adder
7.2929411764705886.199
941591AE2-156 C
50/50
29.1829.18
3151081ELIZAR1
50/50
5.2375.237
316316AC1-027 C
50/50
0.520.52
944591AF1-124 C
50/50
76.14876.148
944601AF1-125 C
50/50
74.70974.709
938771AE1-103 C
50/50
4.0814.081
3145413WATKINS
Adder
0.93058823529411770.791
960081AF2-299 C
Adder
1.91882352941176481.631
926072AC1-086 E
Adder
10.3658823529411768.811
944011AF1-069 C
50/50
16.3216.32
963041AG1-153 C
Adder
6.8564705882352955.828
957862AF2-080 E
Adder
3.9294117647058823.34
936261AD2-033 C
Adder
11.82117647058823610.048
962562AG1-105 E
Adder
5.74.845
924814AB2-134 E
Adder
11.1823529411764729.505
942342AE2-247 E
Adder
2.6752941176470592.274
316036AC1-147 C
50/50
0.60.6
919152AA1-139 E1
50/50
6.7236.723
316018AA1-139 ULT2
50/50
1.781.78
920042AA2-088 E OP
Adder
13.60117647058823611.561
934521AD1-076 C
Adder
16.99176470588235314.443
934511AD1-075 C
Adder
11.6964705882352959.942
3145723EMPORIA
Adder
0.44705882352941180.38
923573AB1-173 E OP
Adder
3.50352941176470622.978
919692AA2-053 E OP
Adder
4.8294117647058834.105
925785AC1-054 E
Adder
3.63176470588235353.087
316263AC1-034 C
Adder
7.1729411764705896.097
959311AF2-222 C
Adder
15.45647058823529513.138
926662AC1-147 E
50/50
2.1552.155
916192Z1-068 E
50/50
3.0983.098
957492AF2-043 E
50/50
2.2332.233
923852AB2-025 E
Adder
1.06941176470588250.909
939412AE1-173 E
50/50
88.25188.251
961942AG1-037 E
Adder
0.427058823529411770.363
961941AG1-037 C
Adder
0.640.544
941032AE2-094 E
50/50
22.37122.371
941031AE2-094 C
50/50
49.94849.948
934332AD1-057 E
Adder
1.96588235294117661.671
934331AD1-057 C
Adder
3.7752941176470593.209
934321AD1-056 C
Adder
6.7670588235294115.752
934322AD1-056 E
Adder
3.6705882352941183.12
927022AC1-189 E
Adder
4.86235294117647054.133
925595AC1-034 E
Adder
5.4105882352941184.599
936262AD2-033 E
Adder
7.8811764705882356.699
939192AE1-149 E
Adder
4.0364705882352953.431
939312AE1-162 E
50/50
1.9371.937
3150991CHESPKB
50/50
1.1761.176
934065AD1-033 E
50/50
8.3718.371
937226AE2-253 E
50/50
9.6579.657
316321Z2-027 C
50/50
0.5770.577
940491AE2-034 C
50/50
1.6591.659
934501AD1-074 C
Adder
46.7858823529411839.768
924517AB2-100 E2
Adder
2.92235294117647062.484
957482AF2-042 E
Adder
39.0611764705882433.202
961671AG1-007 C
Adder
1.05647058823529430.898
934621AD1-088 C
Adder
9.7717647058823538.306
935172AD1-152 E
Adder
5.5847058823529414.747
932046AC2-012 E
50/50
21.31821.318
958161AF2-110 C
50/50
2.0262.026
316017AA1-139 ULT1
50/50
1.781.78
938531AE1-072 C
50/50
28.76728.767
3145393UNCAMP
Adder
8.367.106
315614AA2-178 C
50/50
2.2542.254
933981AD1-022 C
Adder
11.96352941176470710.169
900672V4-068 E
Adder
0.452941176470588240.385
924302AB2-077 E O1
Adder
1.3164705882352941.119
3144216WINCHST
50/50
0.1770.177
316349AD2-085 C
Adder
4.4694117647058833.799
935112AD1-144 E
50/50
1.4091.409
3151091ELIZAR2
50/50
5.1465.146
944582AF1-123 E
50/50
173.752173.752
944592AF1-124 E
50/50
174.381174.381
923832AB2-022 E
50/50
1.9881.988
938772AE1-103 E
50/50
5.6365.636
916042Z1-036 E
50/50
42.96342.963
960082AF2-299 E
Adder
1.27882352941176471.087
946281AF1-292 C
Adder
1.58823529411764721.35
926071AC1-086 C
Adder
22.77647058823529519.36
963042AG1-153 E
Adder
10.2835294117647068.741
927021AC1-189 C
Adder
9.768.296
964241AG1-285 C
Adder
12.75176470588235310.839
924152AB2-059 E OP
Adder
5.70470588235294154.849
962561AG1-105 C
Adder
8.5494117647058847.267
3150981CHESPKA
50/50
0.7090.709
316185AD1-033 C
50/50
2.0522.052
944581AF1-123 C
50/50
75.87875.878
941101AE2-104 C
50/50
4.9664.966
316320Y1-086 C
50/50
0.3530.353
316141AB2-099 E
Adder
0.320.272
316088AB2-174 E
Adder
6.877647058823535.846
923994AB2-040_E
Adder
6.5694117647058825.584
957481AF2-042 C
Adder
58.59176470588235549.803
961672AG1-007 E
Adder
0.59882352941176480.509
924322AB2-079 E O1
Adder
1.3164705882352941.119
943902AF1-058 E
Adder
1.21411764705882351.032
934012AD1-025 E
Adder
8.837647058823537.512
913392Y1-086 E
50/50
3.5213.521
3156116Z1-036WIND
50/50
0.9890.989
939411AE1-173 C
50/50
132.376132.376
3137643SOCKMAN
Adder
0.77882352941176480.662
919710AA2-057 E
Adder
4.43.74
942341AE2-247 C
Adder
1.93764705882352951.647
943462AF1-017 E
Adder
2.86000000000000032.431
958162AF2-110 E
50/50
3.2233.223
316246AF1-032 C
50/50
0.4470.447
316388AE2-253 GEN
50/50
3.2483.248
919153AA1-139 E2
50/50
6.7236.723
934512AD1-075 E
Adder
5.95411764705882355.061
934502AD1-074 E
Adder
23.81647058823529420.244
924516AB2-100 E1
Adder
2.92235294117647062.484
918512AA1-065 E OP
Adder
7.1905882352941186.112
940642AE2-051 E
50/50
16.13516.135
966621AG1-532 C
Adder
1.43882352941176481.223
918532AA1-067 E
Adder
0.85764705882352940.729
924022AB2-043 E O1
Adder
5.1070588235294124.341
3147223TWITTYS
Adder
0.89647058823529410.762
959312AF2-222 E
Adder
10.3552941176470598.802
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.515.51
CBM South 2LTFEXP_CBM-S2->PJM
CBM
91.70491.704
NYPJM->LTFIMP_NY
CLTF
1.4491.449
LGEELTFEXP_LGEE->PJM
CLTF
0.760.76
WECLTFEXP_WEC->PJM
CLTF
0.3980.398
G-007PJM->LTFIMP_G-007
CMTX_NF
3.0313.031
SIGELTFEXP_SIGE->PJM
CLTF
0.160.16
CPLELTFEXP_CPLE->PJM
CLTF
11.56611.566
TVALTFEXP_TVA->PJM
CLTF
4.9264.926
O66PJM->LTFIMP_O-066
CMTX_NF
19.32919.329
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.74418.744
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.28317.283
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.712.71
LAGNLTFEXP_LAGN->PJM
CLTF
6.3446.344

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3221.97
MW Contribution:247.32
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
3151091ELIZAR2
50/50
5.1875.187
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
933291AC2-141 C
50/50
57.45157.451
926755AC1-161 E
50/50
24.52424.524
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
3151101ELIZAR3
50/50
5.3455.345
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
957861AF2-080 C
Adder
9.1035294117647067.738
917512Z2-088 E OP1
Adder
5.7423529411764714.881
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
3152331SURRY 2
50/50
52.46452.464
316375AC2-012 C
50/50
2.2162.216
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961942AG1-037 E
Adder
0.43882352941176470.373
961941AG1-037 C
Adder
0.65882352941176480.56
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934332AD1-057 E
Adder
2.05294117647058851.745
934331AD1-057 C
Adder
3.94352941176470573.352
934321AD1-056 C
Adder
7.0682352941176476.008
934322AD1-056 E
Adder
3.83411764705882343.259
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
919152AA1-139 E1
50/50
6.7746.774
316018AA1-139 ULT2
50/50
1.7931.793
920042AA2-088 E OP
Adder
14.01647058823529311.914
934521AD1-076 C
Adder
17.32941176470588514.73
934511AD1-075 C
Adder
11.92941176470588310.14
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
962572AG1-106 E
Adder
1.36823529411764721.163
926214AC1-099 E
Adder
1.43882352941176481.223
932632AC2-084 E
Adder
3.8494117647058823.272
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940481AE2-033 C
Adder
17.1423529411764714.571
940482AE2-033 E
Adder
11.5564705882352949.823
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
941591AE2-156 C
50/50
29.41729.417
3151081ELIZAR1
50/50
5.2795.279
316316AC1-027 C
50/50
0.5240.524
944591AF1-124 C
50/50
76.6476.64
944601AF1-125 C
50/50
75.19275.192
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
957862AF2-080 E
Adder
4.0352941176470593.43
936261AD2-033 C
Adder
10.6341176470588249.039
962562AG1-105 E
Adder
5.75647058823529444.893
3150981CHESPKA
50/50
0.7150.715
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
962571AG1-106 C
Adder
3.1282352941176472.659
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3221.97
MW Contribution:247.32
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151101ELIZAR3
50/50
5.3455.345
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
957861AF2-080 C
Adder
9.1035294117647067.738
917512Z2-088 E OP1
Adder
5.7423529411764714.881
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961942AG1-037 E
Adder
0.43882352941176470.373
961941AG1-037 C
Adder
0.65882352941176480.56
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934332AD1-057 E
Adder
2.05294117647058851.745
934331AD1-057 C
Adder
3.94352941176470573.352
934321AD1-056 C
Adder
7.0682352941176476.008
934322AD1-056 E
Adder
3.83411764705882343.259
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
919152AA1-139 E1
50/50
6.7746.774
316018AA1-139 ULT2
50/50
1.7931.793
920042AA2-088 E OP
Adder
14.01647058823529311.914
934521AD1-076 C
Adder
17.32941176470588514.73
934511AD1-075 C
Adder
11.92941176470588310.14
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
933291AC2-141 C
50/50
57.45157.451
926755AC1-161 E
50/50
24.52424.524
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
962572AG1-106 E
Adder
1.36823529411764721.163
926214AC1-099 E
Adder
1.43882352941176481.223
932632AC2-084 E
Adder
3.8494117647058823.272
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
3152331SURRY 2
50/50
52.46452.464
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940481AE2-033 C
Adder
17.1423529411764714.571
940482AE2-033 E
Adder
11.5564705882352949.823
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
3151081ELIZAR1
50/50
5.2795.279
316316AC1-027 C
50/50
0.5240.524
944591AF1-124 C
50/50
76.6476.64
944601AF1-125 C
50/50
75.19275.192
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
957862AF2-080 E
Adder
4.0352941176470593.43
936261AD2-033 C
Adder
10.6341176470588249.039
962562AG1-105 E
Adder
5.75647058823529444.893
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
962571AG1-106 C
Adder
3.1282352941176472.659
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
3151091ELIZAR2
50/50
5.1875.187
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3221.81
MW Contribution:247.32
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.28 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3435.8
MW Contribution:249.01
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
919152AA1-139 E1
50/50
6.7746.774
316018AA1-139 ULT2
50/50
1.7931.793
920042AA2-088 E OP
Adder
14.01647058823529311.914
934521AD1-076 C
Adder
17.32941176470588514.73
934511AD1-075 C
Adder
11.92941176470588310.14
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
3152331SURRY 2
50/50
52.46452.464
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940481AE2-033 C
Adder
17.1423529411764714.571
940482AE2-033 E
Adder
11.5564705882352949.823
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
939412AE1-173 E
50/50
87.63687.636
961942AG1-037 E
Adder
0.43882352941176470.373
961941AG1-037 C
Adder
0.65882352941176480.56
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934332AD1-057 E
Adder
2.05294117647058851.745
934331AD1-057 C
Adder
3.94352941176470573.352
934321AD1-056 C
Adder
7.0682352941176476.008
934322AD1-056 E
Adder
3.83411764705882343.259
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
933291AC2-141 C
50/50
57.45157.451
926755AC1-161 E
50/50
24.52424.524
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
962572AG1-106 E
Adder
1.36823529411764721.163
926214AC1-099 E
Adder
1.43882352941176481.223
932632AC2-084 E
Adder
3.8494117647058823.272
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
3151081ELIZAR1
50/50
5.2795.279
316316AC1-027 C
50/50
0.5240.524
944591AF1-124 C
50/50
76.6476.64
944601AF1-125 C
50/50
75.19275.192
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
957862AF2-080 E
Adder
4.0352941176470593.43
936261AD2-033 C
Adder
10.6341176470588249.039
962562AG1-105 E
Adder
5.75647058823529444.893
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
3151091ELIZAR2
50/50
5.1875.187
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
962571AG1-106 C
Adder
3.1282352941176472.659
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
3151101ELIZAR3
50/50
5.3455.345
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
957861AF2-080 C
Adder
9.1035294117647067.738
917512Z2-088 E OP1
Adder
5.7423529411764714.881
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 217_SRT-A'
 OPEN BRANCH FROM BUS 314225 TO BUS 314227 CKT 1   /*6CHARCTY     230.0 - 6LAKESIDE    230.0
 OPEN BRANCH FROM BUS 314225 TO BUS 314260 CKT 1   /*6CHARCTY     230.0 - 6VARINA      230.0
 OPEN BRANCH FROM BUS 314260 TO BUS 314287 CKT 1   /*6VARINA      230.0 - 6CHESTF B    230.0
 OPEN BUS 314225                                   /*6CHARCTY     230.0
 OPEN BUS 314260                                   /*6VARINA      230.0
END
CONTINGENCY 'DVP_P4-2: H2T557_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 224022-1_SRT-S'
 OPEN BRANCH FROM BUS 314466 TO BUS 314909 CKT 1                /*6FENTRES     230.0 - 8FENTRES     500.0
 OPEN BRANCH FROM BUS 314466 TO BUS 316171 CKT 1                /*6FENTRES     230.0 - 6POCATY      230.0
 OPEN BUS 314655                                                /*6FENTR_2     230.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES     500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES     500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P4-2: 224022-2_SRT-S'
 OPEN BRANCH FROM BUS 314466 TO BUS 314909 CKT 2                /*6FENTRES     230.0 - 8FENTRES     500.0
 OPEN BRANCH FROM BUS 314466 TO BUS 316171 CKT 1                /*6FENTRES     230.0 - 6POCATY      230.0
 OPEN BUS 313889                                                /*6FENTRES_STC 230.0
 OPEN BUS 314654                                                /*6FENTR_1     230.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES     500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES     500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 271_SRT-A'
 OPEN BRANCH FROM BUS 314481 TO BUS 316171 CKT 1   /*6LANDSTN     230.0 - 6POCATY      230.0
END
CONTINGENCY 'DVP_P1-2: LN 2240_SRT-A'
 OPEN BRANCH FROM BUS 314466 TO BUS 316171 CKT 1   /*6FENTRES     230.0 - 6POCATY      230.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
END
CONTINGENCY 'DVP_P4-2: 2110T2128_SRT-A'
 OPEN BRANCH FROM BUS 314466 TO BUS 314508 CKT 1   /*6FENTRES     230.0 - 6THRASHER    230.0
 OPEN BRANCH FROM BUS 314480 TO BUS 314508 CKT 1   /*6HUNTSMN     230.0 - 6THRASHER    230.0
 OPEN BRANCH FROM BUS 314480 TO BUS 314537 CKT 1   /*6HUNTSMN     230.0 - 6SUFFOLK     230.0
 OPEN BUS 314480                                   /*6HUNTSMN     230.0
END
CONTINGENCY 'DVP_P4-2: 212822_SRT-S'
 OPEN BRANCH FROM BUS 314466 TO BUS 314508 CKT 1                /*6FENTRES     230.0 - 6THRASHER    230.0
 OPEN BRANCH FROM BUS 314466 TO BUS 314909 CKT 1                /*6FENTRES     230.0 - 8FENTRES     500.0
 OPEN BUS 314655                                                /*6FENTR_2     230.0
 SET POSTCONTRATING 1166 BRANCH FROM BUS 314480 TO BUS 314508 CKT 1 /*6HUNTSMN     230.0 - 6THRASHER    230.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES     500.0 - 8YADKIN      500.0
 SET PRECONTRATING 1051 BRANCH FROM BUS 314480 TO BUS 314508 CKT 1 /*6HUNTSMN     230.0 - 6THRASHER    230.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES     500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P4-2: 269T2128_SRT-S'
 OPEN BRANCH FROM BUS 314466 TO BUS 314508 CKT 1                /*6FENTRES     230.0 - 6THRASHER    230.0
 OPEN BRANCH FROM BUS 314466 TO BUS 314645 CKT 1                /*6FENTRES     230.0 - 6SLIGO L269  230.0
 OPEN BRANCH FROM BUS 314645 TO BUS 938530 CKT 1                /*6SLIGO L269  230.0 - AE1-072 TP   230.0
 SET POSTCONTRATING 1166 BRANCH FROM BUS 314480 TO BUS 314508 CKT 1 /*6HUNTSMN     230.0 - 6THRASHER    230.0
 SET PRECONTRATING 1051 BRANCH FROM BUS 314480 TO BUS 314508 CKT 1 /*6HUNTSMN     230.0 - 6THRASHER    230.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A'
 OPEN BRANCH FROM BUS 314218 TO BUS 314196 CKT 1   /*6ELMONT      230.0 - 6LADYSMITH   230.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1   /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T567_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1   /*6CHCKAHM     230.0 - 8CHCKAHM     500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
314287 to 314276 ckt 1
314218 to 314908 ckt 1
314466 to 314508 ckt 1
314196 to 314911 ckt 1
316171 to 314481 ckt 1
314902 to 314282 ckt 2
314902 to 314914 ckt 1
314914 to 314322 ckt 1
314914 to 314918 ckt 1
314924 to 314903 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC107.9 %1123.3B1212.0520.38
GD1DVP
6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC101.4 %1123.3B1139.0120.38
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC113.38 %3940.0C4467.2202.01
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.8 %3220.44B3342.6861.0
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC104.31 %3637.0C3793.69271.17
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC111.92 %4070.2B4555.5678.98
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC111.48 %5011.0C5586.28259.68
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC101.04 %4070.2B4112.568.22
GD1DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: 545T552_SRT-S
BreakerAC107.93 %3940.0C4252.57134.24
GD1DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC100.32 %3220.44B3230.7939.2
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC119.82 %3220.44B3858.5967.91
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC117.79 %3940.0C4641.11225.81
GD1DVP
8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line
DVP_P4-2: H3T539_SRT-A
BreakerAC105.76 %3532.0C3735.4295.45
GD1DVP
8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line
DVP_P4-2: H1T539_SRT-S
BreakerAC105.47 %3532.0C3725.1695.27
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC111.38 %3220.44B3586.7831.55
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
SingleAC111.09 %3220.44B3577.6133.57
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC110.41 %3940.0C4350.17109.68
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H1T594_SRT-S
BreakerAC106.75 %3940.0C4205.81104.06
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC116.97 %3220.44B3767.0340.27
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC114.22 %3220.44B3678.4950.49
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC111.99 %3940.0C4412.36139.43
GD1DVP
8OX-8CLIFTON 500.0 kV Ckt 1 line
DVP_P7-1: LN 2101-569_SRT-S
TowerAC105.43 %3144.0C3314.5795.98
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC121.18 %3220.44B3902.6239.3
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC120.07 %3220.44B3866.7949.45
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC117.55 %3940.0C4631.32137.23

Details for 6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.9 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1212.05
MW Contribution:20.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316169AC1-164 GEN
80/20
24.58124.581
316349AD2-085 C
Adder
1.65294117647058841.405
3150771HOPHCF1
80/20
1.4371.437
942341AE2-247 C
Adder
0.71647058823529410.609
957871AF2-081 C
Adder
4.5541176470588243.871
3150651CHESTF6
80/20
11.36811.368
3150461FOUR RIVERD
80/20
5.3725.372
3150441FOUR RIVERB
80/20
5.4515.451
3150861SPRUNCD
80/20
0.10.1
940431AE2-027 C
Adder
7.5435294117647066.412
3150681DARBY 2
80/20
1.8091.809
944581AF1-123 C
Adder
20.69529411764706217.591
941101AE2-104 C
Adder
1.55058823529411781.318
938531AE1-072 C
Adder
8.06.8
315051AA1-145 CT1
80/20
8.6838.683
3142366NRTHEST
80/20
0.1340.134
3150701DARBY 4
80/20
1.8171.817
3150731STONECA
Adder
4.0823529411764713.47
935161AD1-151 C
Adder
9.0317647058823527.677
958161AF2-110 C
Adder
0.63294117647058830.538
3150481FOUR RIVERF
80/20
6.566.56
943471AF1-018 C
Adder
3.70470588235294153.149
927041AC1-191 C
80/20
7.557.55
961611AG1-000B C
Adder
8.3835294117647077.126
3150831SPRUNCA
80/20
5.5985.598
3150841SPRUNCB
80/20
5.5985.598
966871AG1-558 C
80/20
1.881.88
316075AC2-137 C
80/20
0.2450.245
3150801HOPHCF4
80/20
2.1822.182
3150471FOUR RIVERE
80/20
5.3725.372
315052AA1-145 CT2
80/20
8.6788.678
3150851SPRUNCC
80/20
0.10.1
944631AF1-128 C
80/20
24.66324.663
933291AC2-141 C
Adder
13.77294117647058911.707
3150921YORKTN3
Adder
60.82117647058823551.698
942001AE2-212 C
Adder
1.22235294117647041.039
3150671DARBY 1
80/20
1.8071.807
3150641CHESTS8
80/20
1.2141.214
3150431FOUR RIVERA
80/20
5.4515.451
3150631CHESTG8
80/20
2.3582.358
3150611CHESTG7
80/20
2.3972.397
3150791HOPHCF3
80/20
1.4371.437
3150621CHESTS7
80/20
1.11.1
3150601CHESTF5
80/20
39.41539.415
944591AF1-124 C
Adder
20.76941176470588217.654
944601AF1-125 C
Adder
20.37647058823529617.32
941591AE2-156 C
Adder
8.3011764705882357.056
316233AE1-074 C
Adder
1.31411764705882361.117
3150691DARBY 3
80/20
1.8151.815
940551AE2-041 C
Adder
3.70470588235294153.149
943461AF1-017 C
Adder
0.64823529411764710.551
316311AC2-079 C
Adder
2.74117647058823532.33
316240AF1-291 C
80/20
1.2941.294
944641AF1-129 C
80/20
62.43662.436
3150451FOUR RIVERC
80/20
6.666.66
3142296MT RD221
80/20
0.1030.103
316004AC1-112 C
80/20
0.2460.246
3150781HOPHCF2
80/20
1.4371.437
3143096IRON208
80/20
0.2880.288
939191AE1-149 C
Adder
5.63882352941176554.793
957601AF2-054 C
Adder
1.060.901
316312AB1-027 C
80/20
0.3940.394
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9991.999
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.12437.124
NYPJM->LTFIMP_NY
CLTF
1.1351.135
LGEELTFEXP_LGEE->PJM
CLTF
0.7730.773
WECLTFEXP_WEC->PJM
CLTF
0.3950.395
SIGELTFEXP_SIGE->PJM
CLTF
0.1430.143
CPLELTFEXP_CPLE->PJM
CLTF
4.1874.187
TVALTFEXP_TVA->PJM
CLTF
2.9092.909
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.18619.186
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.3311.33
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.2052.205
LAGNLTFEXP_LAGN->PJM
CLTF
3.6223.622

Details for 6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.4 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1139.01
MW Contribution:20.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316169AC1-164 GEN
80/20
24.58124.581
316349AD2-085 C
Adder
1.65294117647058841.405
3150771HOPHCF1
80/20
1.4371.437
942341AE2-247 C
Adder
0.71647058823529410.609
957871AF2-081 C
Adder
4.5541176470588243.871
3150651CHESTF6
80/20
11.36811.368
3150461FOUR RIVERD
80/20
5.3725.372
3150441FOUR RIVERB
80/20
5.4515.451
3150861SPRUNCD
80/20
0.10.1
940431AE2-027 C
Adder
7.5435294117647066.412
3150681DARBY 2
80/20
1.8091.809
938531AE1-072 C
Adder
8.06.8
315051AA1-145 CT1
80/20
8.6838.683
3142366NRTHEST
80/20
0.1340.134
3150701DARBY 4
80/20
1.8171.817
3150731STONECA
Adder
4.0823529411764713.47
935161AD1-151 C
Adder
9.0317647058823527.677
958161AF2-110 C
Adder
0.63294117647058830.538
3150481FOUR RIVERF
80/20
6.566.56
943471AF1-018 C
Adder
3.70470588235294153.149
927041AC1-191 C
80/20
7.557.55
961611AG1-000B C
Adder
8.3835294117647077.126
3150831SPRUNCA
80/20
5.5985.598
3150841SPRUNCB
80/20
5.5985.598
966871AG1-558 C
80/20
1.881.88
316075AC2-137 C
80/20
0.2450.245
3150801HOPHCF4
80/20
2.1822.182
3150471FOUR RIVERE
80/20
5.3725.372
315052AA1-145 CT2
80/20
8.6788.678
3150851SPRUNCC
80/20
0.10.1
944631AF1-128 C
80/20
24.66324.663
933291AC2-141 C
Adder
13.77294117647058911.707
3150921YORKTN3
Adder
60.82117647058823551.698
942001AE2-212 C
Adder
1.22235294117647041.039
3150671DARBY 1
80/20
1.8071.807
3150641CHESTS8
80/20
1.2141.214
3150431FOUR RIVERA
80/20
5.4515.451
3150631CHESTG8
80/20
2.3582.358
3150611CHESTG7
80/20
2.3972.397
3150791HOPHCF3
80/20
1.4371.437
966881AG1-559 C
80/20
7.7447.744
3150621CHESTS7
80/20
1.11.1
3150601CHESTF5
80/20
39.41539.415
944591AF1-124 C
Adder
20.76941176470588217.654
944601AF1-125 C
Adder
20.37647058823529617.32
941591AE2-156 C
Adder
8.3011764705882357.056
316233AE1-074 C
Adder
1.31411764705882361.117
3150691DARBY 3
80/20
1.8151.815
940551AE2-041 C
Adder
3.70470588235294153.149
943461AF1-017 C
Adder
0.64823529411764710.551
316311AC2-079 C
Adder
2.74117647058823532.33
316240AF1-291 C
80/20
1.2941.294
944641AF1-129 C
80/20
62.43662.436
3150451FOUR RIVERC
80/20
6.666.66
3142296MT RD221
80/20
0.1030.103
316004AC1-112 C
80/20
0.2460.246
3150781HOPHCF2
80/20
1.4371.437
944581AF1-123 C
Adder
20.69529411764706217.591
941101AE2-104 C
Adder
1.55058823529411781.318
3143096IRON208
80/20
0.2880.288
939191AE1-149 C
Adder
5.63882352941176554.793
957601AF2-054 C
Adder
1.060.901
316312AB1-027 C
80/20
0.3940.394
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9991.999
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.12437.124
NYPJM->LTFIMP_NY
CLTF
1.1351.135
LGEELTFEXP_LGEE->PJM
CLTF
0.7730.773
WECLTFEXP_WEC->PJM
CLTF
0.3950.395
SIGELTFEXP_SIGE->PJM
CLTF
0.1430.143
CPLELTFEXP_CPLE->PJM
CLTF
4.1874.187
TVALTFEXP_TVA->PJM
CLTF
2.9092.909
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.18619.186
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.3311.33
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.2052.205
LAGNLTFEXP_LAGN->PJM
CLTF
3.6223.622

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.38 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4467.2
MW Contribution:202.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
927021AC1-189 C
Adder
11.2564705882352949.568
926071AC1-086 C
Adder
28.2376470588235324.002
924152AB2-059 E OP
Adder
7.0388235294117655.983
946281AF1-292 C
Adder
2.0682352941176471.758
960082AF2-299 E
Adder
1.66588235294117641.416
916042Z1-036 E
Adder
38.52941176470588432.75
923832AB2-022 E
Adder
1.67529411764705881.424
964241AG1-285 C
Adder
14.8776470588235312.646
962561AG1-105 C
Adder
11.1211764705882359.453
938772AE1-103 E
Adder
5.3788235294117654.572
963042AG1-153 E
50/50
13.7613.76
944592AF1-124 E
50/50
143.351143.351
944582AF1-123 E
50/50
142.834142.834
3151091ELIZAR2
50/50
4.2124.212
316349AD2-085 C
Adder
4.3705882352941173.715
935112AD1-144 E
Adder
1.21411764705882351.032
918512AA1-065 E OP
Adder
7.42823529411764756.314
918532AA1-067 E
Adder
0.95764705882352940.814
934502AD1-074 E
Adder
23.0929411764705919.629
934512AD1-075 E
Adder
5.7729411764705894.907
924516AB2-100 E1
Adder
3.9282352941176473.339
966621AG1-532 C
Adder
1.87411764705882341.593
919153AA1-139 E2
50/50
5.535.53
316388AE2-253 GEN
50/50
2.652.65
924022AB2-043 E O1
Adder
6.3552941176470595.402
3151021BRUNSWICKG1
50/50
13.49313.493
3151041BRUNSWICKG3
50/50
13.49313.493
940642AE2-051 E
50/50
19.2519.25
942341AE2-247 C
Adder
1.89411764705882371.61
943462AF1-017 E
Adder
2.7964705882352942.377
958162AF2-110 E
Adder
2.8811764705882352.449
943172AE2-346 E
Adder
0.81176470588235290.69
917332KELFORD E
Adder
2.2035294117647061.873
925122AB2-169 E
Adder
7.7223529411764716.564
934522AD1-076 E
Adder
8.397647058823537.138
940492AE2-034 E
Adder
4.1541176470588243.531
316274AC1-208 C
Adder
12.05058823529411810.243
962571AG1-106 C
Adder
3.6529411764705883.105
917342Z2-044 E
Adder
0.79764705882352950.678
3151311EDGECMA
Adder
20.6976470588235317.593
918492AA1-063AE OP
Adder
5.4552941176470594.637
957871AF2-081 C
50/50
13.52313.523
937482AD2-202 E
50/50
1.5031.503
3145506HICKORY
50/50
2.9532.953
933292AC2-141 E
50/50
18.00718.007
934576AD1-082 E
Adder
5.2247058823529414.441
944602AF1-125 E
50/50
140.592140.592
943612AF1-032 E
Adder
1.24117647058823531.055
316141AB2-099 E
Adder
0.33882352941176470.288
961672AG1-007 E
Adder
0.71058823529411760.604
923994AB2-040_E
Adder
8.2247058823529416.991
316088AB2-174 E
Adder
8.7141176470588247.407
924322AB2-079 E O1
Adder
1.6447058823529411.398
943902AF1-058 E
Adder
1.65529411764705881.407
957481AF2-042 C
50/50
79.02379.023
316294AC1-161 C
50/50
6.8696.869
944581AF1-123 C
50/50
62.37662.376
316185AD1-033 C
50/50
1.6591.659
916191Z1-068 C
50/50
0.0590.059
941101AE2-104 C
Adder
4.4388235294117653.773
933981AD1-022 C
Adder
11.78823529411764610.02
900672V4-068 E
Adder
0.47764705882352950.406
938531AE1-072 C
50/50
23.77123.771
924302AB2-077 E O1
Adder
1.6447058823529411.398
3145393UNCAMP
Adder
8.0941176470588236.88
932046AC2-012 E
50/50
17.5517.55
958161AF2-110 C
Adder
1.8117647058823531.54
933982AD1-022 E
Adder
6.417647058823535.455
3145946PLYMOUTH TP
Adder
0.435294117647058830.37
927146AC1-208 E
Adder
5.3517647058823544.549
316017AA1-139 ULT1
50/50
1.4591.459
927255AC1-221 E
Adder
4.84941176470588254.122
934612AD1-087 E
50/50
5.1365.136
934611AD1-087 C
50/50
1.7741.774
934622AD1-088 E
50/50
6.3856.385
3152431Z1-086 GT3
50/50
17.33717.337
940641AE2-051 C
50/50
28.87528.875
316084AB2-161 E
Adder
6.5576470588235295.574
923263AB1-132 E OP
Adder
8.217647058823536.985
940481AE2-033 C
50/50
22.31122.311
940482AE2-033 E
50/50
15.04115.041
940541AE2-040 C
50/50
3.9673.967
924312AB2-078 E O1
Adder
1.6447058823529411.398
926274AC1-105 E
Adder
3.4082352941176472.897
3152441Z1-086 ST
50/50
30.18730.187
316375AC2-012 C
50/50
1.8031.803
961942AG1-037 E
Adder
0.451764705882352960.384
961941AG1-037 C
Adder
0.6764705882352940.575
927022AC1-189 E
Adder
5.6070588235294124.766
934322AD1-056 E
Adder
4.5447058823529413.863
934332AD1-057 E
Adder
2.43411764705882352.069
934321AD1-056 C
Adder
8.3788235294117657.122
934331AD1-057 C
Adder
4.6741176470588233.973
925595AC1-034 E
Adder
6.6764705882352945.675
923852AB2-025 E
50/50
1.6041.604
3151531CLOVER1
50/50
18.02218.022
941031AE2-094 C
50/50
66.68466.684
941032AE2-094 E
50/50
29.86629.866
939412AE1-173 E
50/50
96.49596.495
3151081ELIZAR1
50/50
4.2884.288
926662AC1-147 E
Adder
1.77411764705882361.508
916192Z1-068 E
50/50
2.5342.534
957492AF2-043 E
Adder
1.9105882352941181.624
957861AF2-080 C
Adder
10.2235294117647058.69
917512Z2-088 E OP1
Adder
6.54705882352941255.565
946282AF1-292 E
Adder
1.37882352941176461.172
316315AB2-025 C
50/50
0.5620.562
3151541CLOVER2
50/50
17.85317.853
944012AF1-069 E
50/50
8.4648.464
316316AC1-027 C
50/50
0.4240.424
926214AC1-099 E
Adder
1.61294117647058831.371
932632AC2-084 E
Adder
4.3164705882352943.669
962572AG1-106 E
Adder
1.59764705882352961.358
957872AF2-081 E
50/50
5.7955.795
316018AA1-139 ULT2
50/50
1.4591.459
924162AB2-060 E OP
Adder
5.2141176470588244.432
964242AG1-285 E
Adder
9.9188235294117648.431
964792AG1-342 E
Adder
2.9682352941176472.523
932763AC2-100 E
Adder
3.2952941176470592.801
926755AC1-161 E
50/50
18.00718.007
933291AC2-141 C
50/50
42.18342.183
3150921YORKTN3
Adder
106.1988235294117790.269
925522AC1-027 E
50/50
1.641.64
941102AE2-104 E
Adder
7.0576470588235295.999
3145256KINGFORK
Adder
1.30823529411764721.112
934501AD1-074 C
Adder
45.3647058823529438.56
961671AG1-007 C
Adder
1.25411764705882361.066
924517AB2-100 E2
Adder
3.9282352941176473.339
937226AE2-253 E
50/50
7.9097.909
935172AD1-152 E
Adder
7.5717647058823536.436
934621AD1-088 C
50/50
13.2613.26
957482AF2-042 E
50/50
52.68252.682
939192AE1-149 E
Adder
8.0705882352941176.86
939312AE1-162 E
Adder
1.72117647058823551.463
934065AD1-033 E
50/50
6.7926.792
957862AF2-080 E
Adder
4.53176470588235253.852
926072AC1-086 E
Adder
12.85176470588235310.924
960081AF2-299 C
Adder
2.4988235294117652.124
3145413WATKINS
Adder
0.92117647058823540.783
962562AG1-105 E
Adder
7.41411764705882356.302
938771AE1-103 C
Adder
3.8941176470588243.31
963041AG1-153 C
50/50
9.1739.173
3151051BRUNSWICKS1
50/50
28.03428.034
944011AF1-069 C
50/50
21.78821.788
944591AF1-124 C
50/50
62.59862.598
944601AF1-125 C
50/50
61.41561.415
3151101ELIZAR3
50/50
4.3424.342
941591AE2-156 C
50/50
24.00724.007
936666AD2-085 E
Adder
7.1317647058823546.062
920692AA2-178 E
Adder
5.5388235294117654.708
922923AB1-081 E OP
Adder
4.9682352941176474.223
966622AG1-532 E
Adder
1.24941176470588241.062
917122Z2-027 E
Adder
1.81294117647058831.541
3146326AYDLETT TAP
50/50
1.8341.834
938532AE1-072 E
50/50
12.39212.392
927264AC1-222 E
Adder
5.0905882352941184.327
3152411Z1-086 GT1
50/50
17.34217.342
3152421Z1-086 GT2
50/50
17.33717.337
943461AF1-017 C
Adder
1.71411764705882371.457
316311AC2-079 C
Adder
7.3223529411764716.224
932596AC2-079 E
Adder
11.94588235294117610.154
934521AD1-076 C
Adder
16.4752941176470614.004
934511AD1-075 C
Adder
11.3411764705882369.64
919692AA2-053 E OP
Adder
5.65176470588235354.804
316263AC1-034 C
Adder
8.8505882352941177.523
923573AB1-173 E OP
Adder
4.3858823529411773.728
3145723EMPORIA
Adder
0.57647058823529410.49
920042AA2-088 E OP
Adder
14.1647058823529412.04
925785AC1-054 E
Adder
4.5188235294117653.841
919152AA1-139 E1
50/50
5.535.53
937481AD2-202 C
50/50
0.5150.515
3151031BRUNSWICKG2
50/50
13.49313.493
942342AE2-247 E
Adder
2.61647058823529432.224
926206AC1-098 E
Adder
4.8835294117647064.151
964791AG1-342 C
Adder
4.4517647058823523.784
901082W1-029 E
Adder
42.9564705882352936.513
3143316POE
Adder
1.6082352941176471.367
939191AE1-149 C
Adder
12.10588235294117610.29
919710AA2-057 E
Adder
5.2964705882352944.502
3137643SOCKMAN
Adder
0.95176470588235310.809
913392Y1-086 E
Adder
2.9682352941176472.523
939411AE1-173 C
50/50
144.742144.742
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6257.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
136.078136.078
NYPJM->LTFIMP_NY
CLTF
2.5842.584
LGEELTFEXP_LGEE->PJM
CLTF
2.1892.189
WECLTFEXP_WEC->PJM
CLTF
1.1371.137
G-007PJM->LTFIMP_G-007
CMTX_NF
5.665.66
SIGELTFEXP_SIGE->PJM
CLTF
0.4160.416
CPLELTFEXP_CPLE->PJM
CLTF
15.98515.985
TVALTFEXP_TVA->PJM
CLTF
9.3529.352
O66PJM->LTFIMP_O-066
CMTX_NF
36.00236.002
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.25255.252
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.53435.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.5866.586
LAGNLTFEXP_LAGN->PJM
CLTF
11.79711.797

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.8 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3342.68
MW Contribution:61.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316210AC1-098 C
80/20
1.251.25
316318V4-068 C
80/20
0.1070.107
313506AB1-173 C OP
80/20
1.4941.494
966621AG1-532 C
80/20
1.8631.863
316320Y1-086 C
80/20
0.2940.294
316388AE2-253 GEN
80/20
2.6322.632
936161AD2-022 C
Adder
9.455294117647068.037
935171AD1-152 C
80/20
1.8271.827
933981AD1-022 C
80/20
11.71411.714
316174AB2-169_C
80/20
1.3931.393
3156063AA2-053SOLA
80/20
1.9981.998
3151281ROARAP4
80/20
1.7351.735
938531AE1-072 C
80/20
23.60823.608
935161AD1-151 C
Adder
15.27058823529411812.98
958161AF2-110 C
80/20
1.7981.798
313526AB2-022 C
80/20
0.5040.504
316017AA1-139 ULT1
80/20
1.4491.449
934611AD1-087 C
80/20
1.7671.767
3152431Z1-086 GT3
80/20
17.27717.277
940641AE2-051 C
80/20
28.76428.764
3152331SURRY 2
80/20
30.82730.827
943171AE2-346 C
80/20
0.2980.298
961941AG1-037 C
80/20
0.6730.673
3151391GASTONA
80/20
4.0664.066
934321AD1-056 C
Adder
8.332941176470597.083
934331AD1-057 C
Adder
4.6482352941176473.951
958211AF2-115 C
Adder
2.28235294117647051.94
3151531CLOVER1
80/20
17.9517.95
941031AE2-094 C
80/20
66.45566.455
3151081ELIZAR1
80/20
4.2584.258
316140AB2-099 C
80/20
0.1280.128
3152921DOMTR78
80/20
1.8181.818
316018AA1-139 ULT2
80/20
1.4491.449
933291AC2-141 C
80/20
41.90441.904
3150921YORKTN3
Adder
127.84235294117647108.666
316317KELFORD C
80/20
0.4760.476
957861AF2-080 C
Adder
10.167058823529418.642
316023AB2-100 C2
80/20
1.2911.291
316129AC1-054 C
80/20
1.5891.589
316315AB2-025 C
80/20
0.5580.558
3138533PONTONDP
Adder
0.6764705882352940.575
3151541CLOVER2
80/20
17.78217.782
316316AC1-027 C
80/20
0.4210.421
315614AA2-178 C
80/20
2.0912.091
3151411GASTONB
80/20
4.0664.066
316181AB2-040 GEN
80/20
1.6831.683
3147043LAWRENC
80/20
0.3980.398
940481AE2-033 C
80/20
22.18122.181
940541AE2-040 C
80/20
3.9443.944
3152441Z1-086 ST
80/20
30.08130.081
961611AG1-000B C
Adder
17.0670588235294114.507
316375AC2-012 C
80/20
1.7911.791
316072AD1-144 C
80/20
0.3590.359
3151381ROSEMG2
80/20
1.271.27
960081AF2-299 C
80/20
2.4842.484
936171AD2-023 C
Adder
5.5152941176470584.688
936261AD2-033 C
Adder
14.72470588235294112.516
961791AG1-021 C
Adder
1.82588235294117651.552
938771AE1-103 C
80/20
3.8693.869
963041AG1-153 C
80/20
9.1419.141
3151051BRUNSWICKS1
80/20
27.93627.936
944011AF1-069 C
80/20
21.71321.713
944591AF1-124 C
80/20
62.17762.177
944601AF1-125 C
80/20
61.00261.002
3151101ELIZAR3
80/20
4.3114.311
941591AE2-156 C
80/20
23.83823.838
3151261ROARAP2
80/20
1.8341.834
3156056W1-029WIND
80/20
1.0361.036
3152411Z1-086 GT1
80/20
17.28117.281
3152421Z1-086 GT2
80/20
17.27717.277
943461AF1-017 C
80/20
1.7011.701
316311AC2-079 C
80/20
7.2667.266
934501AD1-074 C
80/20
45.0845.08
961671AG1-007 C
Adder
1.2482352941176471.061
940491AE2-034 C
80/20
1.5381.538
3156116Z1-036WIND
80/20
0.8770.877
946301AF1-294 C
Adder
3.75411764705882333.191
934621AD1-088 C
80/20
13.20613.206
942001AE2-212 C
Adder
2.11411764705882371.797
934521AD1-076 C
80/20
16.37216.372
934511AD1-075 C
80/20
11.2711.27
316212AC1-099 C
80/20
0.4180.418
316263AC1-034 C
Adder
8.8035294117647057.483
3156073AA1-063SOLA
80/20
1.8611.861
316087AB2-174 C
80/20
1.561.56
316321Z2-027 C
80/20
0.4860.486
959311AF2-222 C
Adder
18.28823529411764815.545
937481AD2-202 C
80/20
0.5130.513
3151031BRUNSWICKG2
80/20
13.44613.446
316036AC1-147 C
80/20
0.4890.489
316305AF2-043 C
80/20
0.4630.463
316365AB2-100 C1
80/20
1.2911.291
3156083AA2-088SOLA
80/20
1.4051.405
957481AF2-042 C
80/20
78.71578.715
940431AE2-027 C
Adder
11.395294117647069.686
316294AC1-161 C
80/20
6.8246.824
944581AF1-123 C
80/20
61.95761.957
316185AD1-033 C
80/20
1.6481.648
916191Z1-068 C
80/20
0.0580.058
941101AE2-104 C
80/20
4.4074.407
932631AC2-084 C
80/20
1.3311.331
316274AC1-208 C
80/20
11.98411.984
962571AG1-106 C
80/20
3.6323.632
3151311EDGECMA
Adder
20.58941176470588317.501
957871AF2-081 C
80/20
13.4313.43
3151361ROSEMG1
80/20
2.7122.712
3151151S HAMPT1
80/20
1.9741.974
964791AG1-342 C
Adder
4.4317647058823533.767
939191AE1-149 C
Adder
11.99058823529411710.192
3150981CHESPKA
80/20
0.5780.578
927021AC1-189 C
Adder
11.1952941176470599.516
926071AC1-086 C
80/20
28.07728.077
946281AF1-292 C
80/20
2.0562.056
964241AG1-285 C
Adder
14.80352941176470712.583
962561AG1-105 C
Adder
11.0694117647058839.409
3151091ELIZAR2
80/20
4.1834.183
316349AD2-085 C
80/20
4.3374.337
3151021BRUNSWICKG1
80/20
13.44613.446
3151041BRUNSWICKG3
80/20
13.44613.446
942341AE2-247 C
80/20
1.881.88
316246AF1-032 C
80/20
0.3780.378
3156021HOLLOMANSOL
80/20
2.4482.448
316011AB1-132 C OP
80/20
3.1053.105
3151371ROSEMS1
80/20
1.681.68
3137643SOCKMAN
80/20
0.9470.947
939411AE1-173 C
80/20
144.1144.1
3150991CHESPKB
80/20
0.9580.958
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.597.59
CBM South 2LTFEXP_CBM-S2->PJM
CBM
135.46135.46
NYPJM->LTFIMP_NY
CLTF
2.5592.559
LGEELTFEXP_LGEE->PJM
CLTF
2.182.18
SIGELTFEXP_SIGE->PJM
CLTF
0.4150.415
WECLTFEXP_WEC->PJM
CLTF
1.1331.133
CPLELTFEXP_CPLE->PJM
CLTF
15.91315.913
TVALTFEXP_TVA->PJM
CLTF
9.319.31
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.0655.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.38335.383
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.566.56
LAGNLTFEXP_LAGN->PJM
CLTF
11.74411.744

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.31 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:3793.69
MW Contribution:271.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
933981AD1-022 C
Adder
13.8411.764
900672V4-068 E
Adder
0.53882352941176470.458
938531AE1-072 C
50/50
31.50731.507
3145393UNCAMP
Adder
9.815294117647068.343
933982AD1-022 E
Adder
7.5341176470588246.404
3145946PLYMOUTH TP
Adder
0.51882352941176470.441
313526AB2-022 C
50/50
0.6650.665
316017AA1-139 ULT1
50/50
1.9391.939
940641AE2-051 C
50/50
26.37426.374
926785AC1-164_E
50/50
29.20829.208
943471AF1-018 C
Adder
11.3211764705882359.623
3152331SURRY 2
50/50
52.5452.54
316084AB2-161 E
Adder
8.0411764705882356.835
316236AE1-162 C
50/50
0.5940.594
944012AF1-069 E
Adder
7.04588235294117655.989
961952AG1-038 E
Adder
6.66352941176470555.664
961951AG1-038 C
Adder
4.8258823529411774.102
925865AC1-065 E
Adder
25.8294117647058821.955
3144216WINCHST
50/50
0.2410.241
920692AA2-178 E
Adder
6.7435294117647065.732
917122Z2-027 E
50/50
2.3642.364
3146326AYDLETT TAP
50/50
2.4292.429
938532AE1-072 E
50/50
16.42416.424
3156056W1-029WIND
50/50
1.351.35
940551AE2-041 C
Adder
11.3211764705882359.623
935162AD1-151 E
Adder
15.29411764705882413
957832AF2-077 E
50/50
2.4692.469
943461AF1-017 C
Adder
2.17764705882352951.851
316311AC2-079 C
Adder
9.3282352941176477.929
932596AC2-079 E
Adder
15.21999999999999912.937
961942AG1-037 E
Adder
0.50470588235294120.429
961941AG1-037 C
Adder
0.75764705882352950.644
923852AB2-025 E
Adder
1.53294117647058831.303
941031AE2-094 C
Adder
55.5058823529411847.18
941032AE2-094 E
Adder
24.8621.131
316076AC2-137 E
Adder
1.77294117647058821.507
964211AG1-282 C
Adder
2.87176470588235282.441
923842AB2-024 E
Adder
2.84000000000000032.414
316157AD2-030 E
Adder
1.88588235294117661.603
939412AE1-173 E
50/50
96.4696.46
3151081ELIZAR1
50/50
5.7935.793
926662AC1-147 E
50/50
2.3992.399
916192Z1-068 E
50/50
3.4083.408
957492AF2-043 E
50/50
2.5222.522
934521AD1-076 C
Adder
19.5552941176470616.622
934511AD1-075 C
Adder
13.46117647058823511.442
919692AA2-053 E OP
Adder
5.8800000000000014.998
923573AB1-173 E OP
Adder
4.3988235294117643.739
3145723EMPORIA
Adder
0.57058823529411760.485
920042AA2-088 E OP
Adder
16.1705882352941213.745
316321Z2-027 C
50/50
0.6380.638
919152AA1-139 E1
50/50
7.3487.348
939246AE1-155 E
Adder
12.80941176470588310.888
924814AB2-134 E
Adder
18.51882352941176515.741
316036AC1-147 C
50/50
0.6650.665
942342AE2-247 E
Adder
3.3247058823529412.826
316305AF2-043 C
50/50
0.6160.616
934501AD1-074 C
Adder
53.8447058823529445.768
924517AB2-100 E2
Adder
3.87764705882352923.296
3156116Z1-036WIND
50/50
1.1111.111
937226AE2-253 E
50/50
10.53510.535
3141813NORNECK
Adder
1.24235294117647071.056
962861AG1-135 C
Adder
8.9694117647058827.624
939192AE1-149 E
Adder
9.628.177
943741AF1-042 C
Adder
4.3658823529411773.711
939312AE1-162 E
50/50
2.4312.431
934065AD1-033 E
50/50
9.1079.107
962572AG1-106 E
Adder
1.62470588235294121.381
957872AF2-081 E
50/50
7.7017.701
316018AA1-139 ULT2
50/50
1.9391.939
944631AF1-128 C
Adder
50.1435294117647142.622
936592AD2-074 E
Adder
13.61411764705882311.572
316160AE1-175 E
50/50
2.1482.148
926755AC1-161 E
50/50
25.37725.377
933291AC2-141 C
50/50
59.4559.45
3150921YORKTN3
50/50
222.183222.183
923263AB1-132 E OP
Adder
8.3529411764705897.1
940481AE2-033 C
Adder
21.4117647058823518.2
940482AE2-033 E
Adder
14.43529411764705912.27
940541AE2-040 C
Adder
3.79058823529411763.222
3138116ELKO L286
Adder
1.84941176470588251.572
963611AG1-210 C
Adder
0.93294117647058830.793
957831AF2-077 C
50/50
0.570.57
961611AG1-000B C
Adder
25.22588235294117721.442
316375AC2-012 C
50/50
2.4382.438
316072AD1-144 C
50/50
0.4940.494
926072AC1-086 E
Adder
13.06352941176470511.104
960081AF2-299 C
Adder
2.12235294117647081.804
3145413WATKINS
Adder
1.09647058823529430.932
938771AE1-103 C
Adder
4.7799999999999994.063
963041AG1-153 C
Adder
7.662352941176476.513
944011AF1-069 C
Adder
18.13647058823529415.416
3150601CHESTF5
Adder
80.1388235294117768.118
964212AG1-282 E
Adder
1.91529411764705881.628
943172AE2-346 E
Adder
0.90941176470588240.773
917332KELFORD E
Adder
2.42.04
925122AB2-169 E
Adder
8.6941176470588237.39
934522AD1-076 E
Adder
9.9670588235294128.472
940492AE2-034 E
Adder
5.057647058823534.299
962571AG1-106 C
Adder
3.71294117647058863.156
918492AA1-063AE OP
Adder
5.82352941176470654.95
957871AF2-081 C
50/50
17.9717.97
3145506HICKORY
50/50
3.9493.949
936591AD2-074 C
Adder
8.3435294117647067.092
3130536PAPERMILL
Adder
10.4988235294117648.924
939602AE1-190 E
Adder
2.23058823529411751.896
933292AC2-141 E
50/50
25.37725.377
934576AD1-082 E
Adder
6.4070588235294125.446
901082W1-029 E
50/50
55.655.6
316141AB2-099 E
Adder
0.37882352941176470.322
923994AB2-040_E
Adder
8.2482352941176477.011
316088AB2-174 E
Adder
8.6929411764705897.389
966662AG1-536 E
Adder
10.6329411764705889.038
962862AG1-135 E
Adder
5.985.083
943742AF1-042 E
Adder
7.1235294117647056.055
934392AD1-063 E
Adder
1.69764705882352951.443
316294AC1-161 C
50/50
9.6819.681
944581AF1-123 C
50/50
83.73183.731
316185AD1-033 C
50/50
2.2242.224
916191Z1-068 C
50/50
0.0790.079
941101AE2-104 C
50/50
5.7555.755
925522AC1-027 E
50/50
2.2062.206
941102AE2-104 E
50/50
9.159.15
3145256KINGFORK
50/50
1.7881.788
925332AB2-190 E
Adder
11.1811764705882369.504
962962AG1-145 E
50/50
2.6032.603
927226AC1-216 E
Adder
11.3047058823529419.609
944591AF1-124 C
50/50
84.02984.029
944601AF1-125 C
50/50
82.44182.441
3151101ELIZAR3
50/50
5.8665.866
941591AE2-156 C
50/50
32.45632.456
936666AD2-085 E
Adder
9.0611764705882357.702
926071AC1-086 C
Adder
28.7023529411764724.397
916042Z1-036 E
50/50
48.46248.462
923832AB2-022 E
50/50
2.1962.196
938772AE1-103 E
Adder
6.6011764705882355.611
963042AG1-153 E
Adder
11.4941176470588249.77
316169AC1-164 GEN
50/50
65.01265.012
944592AF1-124 E
50/50
192.429192.429
944582AF1-123 E
50/50
191.735191.735
3151091ELIZAR2
50/50
5.6915.691
316349AD2-085 C
Adder
5.5541176470588244.721
935112AD1-144 E
50/50
1.661.66
918512AA1-065 E OP
Adder
8.4494117647058827.182
934502AD1-074 E
Adder
27.4094117647058823.298
934512AD1-075 E
Adder
6.8529411764705895.825
924516AB2-100 E1
Adder
3.87764705882352923.296
316320Y1-086 C
50/50
0.3880.388
919153AA1-139 E2
50/50
7.3487.348
316388AE2-253 GEN
50/50
3.5313.531
940642AE2-051 E
50/50
17.58317.583
963612AG1-210 E
Adder
1.39882352941176481.189
316159AE1-175 C
50/50
0.7040.704
942341AE2-247 C
Adder
2.40705882352941152.046
943462AF1-017 E
Adder
3.55294117647058853.02
958162AF2-110 E
50/50
3.7353.735
316246AF1-032 C
50/50
0.5030.503
944602AF1-125 E
50/50
188.725188.725
943612AF1-032 E
50/50
1.6391.639
958261AF2-120 C
Adder
9.1988235294117657.819
939191AE1-149 C
Adder
14.42941176470588312.265
934146AD1-041 E
Adder
5.5776470588235294.741
957601AF2-054 C
Adder
3.36117647058823542.857
316382AG1-145 C
50/50
0.6360.636
3150981CHESPKA
50/50
0.7870.787
3137643SOCKMAN
Adder
0.96588235294117640.821
913392Y1-086 E
50/50
3.893.89
316078AC2-138 E
Adder
1.30588235294117671.11
958262AF2-120 E
Adder
6.1329411764705885.213
966661AG1-536 C
Adder
7.9129411764705886.726
939612AE1-191 E
Adder
8.9247058823529427.586
957602AF2-054 E
Adder
2.24117647058823531.905
939411AE1-173 C
50/50
144.69144.69
934012AD1-025 E
Adder
14.63647058823529612.441
3151161SURRY 1
50/50
40.01440.014
3150991CHESPKB
50/50
1.3041.304
935161AD1-151 C
Adder
22.94117647058823619.5
932046AC2-012 E
50/50
23.72823.728
958161AF2-110 C
50/50
2.3482.348
316316AC1-027 C
50/50
0.5710.571
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.5566.556
NYPJM->LTFIMP_NY
CLTF
2.0382.038
LGEELTFEXP_LGEE->PJM
CLTF
1.1621.162
WECLTFEXP_WEC->PJM
CLTF
0.5990.599
G-007PJM->LTFIMP_G-007
CMTX_NF
4.3044.304
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234
CBM South 2LTFEXP_CBM-S2->PJM
CBM
111.34111.34
CPLELTFEXP_CPLE->PJM
CLTF
13.75813.758
TVALTFEXP_TVA->PJM
CLTF
6.4816.481
O66PJM->LTFIMP_O-066
CMTX_NF
27.4327.43
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.41628.416
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.24623.246
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.853.85
LAGNLTFEXP_LAGN->PJM
CLTF
8.2678.267

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.92 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4555.56
MW Contribution:78.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
927021AC1-189 C
Adder
13.13058823529411811.161
926071AC1-086 C
Adder
32.9752941176470628.029
946281AF1-292 C
Adder
2.40117647058823552.041
964241AG1-285 C
Adder
17.71058823529411815.054
316169AC1-164 GEN
80/20
73.90473.904
316349AD2-085 C
Adder
5.9917647058823535.093
966621AG1-532 C
Adder
2.1752941176470591.849
3150771HOPHCF1
80/20
4.324.32
316159AE1-175 C
80/20
0.7120.712
942341AE2-247 C
Adder
2.5964705882352942.207
316274AC1-208 C
Adder
14.04588235294117711.939
962571AG1-106 C
Adder
4.2647058823529413.625
3151311EDGECMA
Adder
23.6270588235294120.083
957871AF2-081 C
Adder
17.51647058823529314.889
3150651CHESTF6
Adder
32.7447058823529427.833
936591AD2-074 C
Adder
8.7058823529411787.4
316033AB2-134 GEN
80/20
3.7293.729
934011AD1-025 C
80/20
4.6114.611
957481AF2-042 C
Adder
77.7682352941176466.103
940431AE2-027 C
Adder
22.58000000000000219.193
3150681DARBY 2
80/20
4.5764.576
316294AC1-161 C
80/20
8.8498.849
944581AF1-123 C
Adder
80.2141176470588368.182
941101AE2-104 C
Adder
5.8423529411764714.966
933981AD1-022 C
Adder
14.54588235294117712.364
938531AE1-072 C
Adder
30.76823529411764526.153
3142366NRTHEST
80/20
0.330.33
3150701DARBY 4
80/20
4.5974.597
3150731STONECA
80/20
12.27512.275
935161AD1-151 C
80/20
28.71928.719
958161AF2-110 C
Adder
2.38352941176470572.026
316336AC2-165 C
Adder
13.90823529411764711.822
940641AE2-051 C
Adder
26.97529411764705622.929
943471AF1-018 C
Adder
12.16117647058823610.337
3152331SURRY 2
80/20
45.81645.816
3151201GRAVEL4
80/20
4.5054.505
3151221GRAVEL6
80/20
4.54.5
940481AE2-033 C
Adder
25.6411764705882421.795
940541AE2-040 C
Adder
4.5529411764705883.87
927041AC1-191 C
Adder
16.39529411764705813.936
963611AG1-210 C
Adder
0.95764705882352940.814
961611AG1-000B C
80/20
28.34928.349
961941AG1-037 C
Adder
0.82117647058823530.698
934321AD1-056 C
Adder
9.6541176470588248.206
934331AD1-057 C
Adder
5.3847058823529414.577
941031AE2-094 C
Adder
59.24117647058823650.355
3150831SPRUNCA
Adder
15.78000000000000113.413
3150841SPRUNCB
Adder
15.78000000000000113.413
966871AG1-558 C
Adder
4.0835294117647063.471
316075AC2-137 C
80/20
0.6870.687
964211AG1-282 C
Adder
2.9811764705882352.534
3150801HOPHCF4
80/20
6.5586.558
316369AC1-216 C
80/20
2.8462.846
957861AF2-080 C
Adder
11.92588235294117810.137
3150631CHESTG8
80/20
6.826.82
3150611CHESTG7
80/20
6.936.93
3150791HOPHCF3
80/20
4.324.32
961951AG1-038 C
Adder
5.035294117647064.28
3144216WINCHST
80/20
0.2370.237
944631AF1-128 C
80/20
71.31971.319
933291AC2-141 C
80/20
54.34454.344
3150921YORKTN3
80/20
215.99215.99
3151191GRAVEL3
80/20
4.4484.448
934501AD1-074 C
Adder
56.2176470588235347.785
961671AG1-007 C
Adder
1.44941176470588241.232
934621AD1-088 C
Adder
13.69294117647058911.639
942001AE2-212 C
Adder
3.73882352941176473.178
3150671DARBY 1
80/20
4.574.57
3150641CHESTS8
80/20
3.5113.511
962861AG1-135 C
Adder
9.3188235294117667.921
943741AF1-042 C
Adder
4.5552941176470593.872
960081AF2-299 C
Adder
2.92.465
936261AD2-033 C
Adder
18.25529411764705815.517
938771AE1-103 C
Adder
4.9788235294117654.232
963041AG1-153 C
Adder
8.3011764705882357.056
944011AF1-069 C
Adder
19.35647058823529316.453
3150621CHESTS7
80/20
3.1823.182
3150601CHESTF5
80/20
113.981113.981
944591AF1-124 C
Adder
80.4988235294117868.424
944601AF1-125 C
Adder
78.9788235294117767.132
941591AE2-156 C
Adder
31.64823529411764726.901
316233AE1-074 C
Adder
4.08588235294117653.473
3150691DARBY 3
80/20
4.5924.592
940551AE2-041 C
Adder
12.16117647058823610.337
943461AF1-017 C
Adder
2.34941176470588251.997
316311AC2-079 C
Adder
9.984705882352948.487
934521AD1-076 C
Adder
20.41647058823529517.354
934511AD1-075 C
Adder
14.05411764705882411.946
316263AC1-034 C
Adder
10.102352941176478.587
316240AF1-291 C
Adder
3.78000000000000023.213
944641AF1-129 C
Adder
179.8423529411765152.866
3142296MT RD221
80/20
0.2170.217
316004AC1-112 C
80/20
0.5960.596
3150781HOPHCF2
80/20
4.324.32
3150761HOPPOLC
80/20
2.7172.717
3143096IRON208
80/20
0.7870.787
958261AF2-120 C
Adder
9.5447058823529418.113
939191AE1-149 C
Adder
18.60588235294117615.815
957601AF2-054 C
Adder
3.56235294117647073.028
316132AB2-190 C
80/20
7.3677.367
316382AG1-145 C
80/20
0.6420.642
3137643SOCKMAN
Adder
1.1117647058823530.945
316312AB1-027 C
80/20
0.9570.957
966661AG1-536 C
Adder
8.2105882352941186.979
939411AE1-173 C
Adder
145.74235294117648123.881
3151161SURRY 1
80/20
43.78743.787
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.4058.405
CBM South 2LTFEXP_CBM-S2->PJM
CBM
156.686156.686
NYPJM->LTFIMP_NY
CLTF
4.1344.134
LGEELTFEXP_LGEE->PJM
CLTF
3.3563.356
WECLTFEXP_WEC->PJM
CLTF
1.7261.726
SIGELTFEXP_SIGE->PJM
CLTF
0.620.62
CPLELTFEXP_CPLE->PJM
CLTF
17.60717.607
TVALTFEXP_TVA->PJM
CLTF
12.412.4
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.27284.272
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.64648.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
9.5619.561
LAGNLTFEXP_LAGN->PJM
CLTF
15.45715.457

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.48 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5586.28
MW Contribution:259.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926071AC1-086 C
Adder
32.9682352941176528.023
946281AF1-292 C
Adder
2.40117647058823552.041
960082AF2-299 E
Adder
1.93294117647058841.643
916042Z1-036 E
Adder
48.916470588235341.579
923832AB2-022 E
Adder
2.16117647058823531.837
938772AE1-103 E
Adder
6.8741176470588235.843
963042AG1-153 E
Adder
12.44941176470588410.582
930122AB1-027 E
50/50
2.5162.516
316169AC1-164 GEN
50/50
73.86273.862
944592AF1-124 E
Adder
184.2764705882353156.635
944582AF1-123 E
Adder
183.61176470588234156.07
316349AD2-085 C
Adder
5.9894117647058835.091
935112AD1-144 E
Adder
1.66000000000000011.411
918512AA1-065 E OP
Adder
9.0517647058823547.694
934502AD1-074 E
Adder
28.60941176470588624.318
934512AD1-075 E
Adder
7.1529411764705896.08
924516AB2-100 E1
Adder
4.5505882352941183.868
966621AG1-532 C
Adder
2.1752941176470591.849
919153AA1-139 E2
Adder
7.166.086
940642AE2-051 E
Adder
17.97882352941176615.282
926412AC1-112 E
50/50
2.0462.046
316159AE1-175 C
50/50
0.7110.711
942341AE2-247 C
Adder
2.5964705882352942.207
943462AF1-017 E
Adder
3.8317647058823533.257
958162AF2-110 E
Adder
3.79058823529411763.222
943172AE2-346 E
Adder
0.98588235294117640.838
917332KELFORD E
Adder
2.63882352941176462.243
925122AB2-169 E
Adder
9.3470588235294127.945
934522AD1-076 E
Adder
10.4035294117647078.843
940492AE2-034 E
Adder
5.2011764705882364.421
962571AG1-106 C
Adder
4.2647058823529413.625
918492AA1-063AE OP
Adder
6.5082352941176485.532
957871AF2-081 C
Adder
17.5105882352941214.884
3145506HICKORY
Adder
3.83058823529411763.256
946262AF1-291 E
Adder
2.5188235294117652.141
3150651CHESTF6
Adder
32.7305882352941227.821
936591AD2-074 C
Adder
8.77.395
3130536PAPERMILL
Adder
11.342352941176479.641
939602AE1-190 E
Adder
2.40470588235294122.044
933292AC2-141 E
Adder
23.1894117647058819.711
934576AD1-082 E
Adder
7.6470588235294126.5
944602AF1-125 E
Adder
180.73058823529414153.621
943612AF1-032 E
Adder
1.61764705882352941.375
933981AD1-022 C
Adder
14.54117647058823512.36
900672V4-068 E
Adder
0.58235294117647060.495
938531AE1-072 C
Adder
30.75647058823529526.143
3145393UNCAMP
Adder
10.2788235294117658.737
3142366NRTHEST
50/50
0.330.33
3150701DARBY 4
50/50
4.5944.594
3150731STONECA
Adder
12.26941176470588210.429
935161AD1-151 C
Adder
28.70588235294117424.4
932046AC2-012 E
Adder
23.15176470588235319.679
958161AF2-110 C
Adder
2.38352941176470572.026
933982AD1-022 E
Adder
7.9164705882352956.729
3145946PLYMOUTH TP
Adder
0.540.459
940641AE2-051 C
Adder
26.96705882352941322.922
926785AC1-164_E
50/50
33.18433.184
943471AF1-018 C
Adder
12.15411764705882410.331
3152331SURRY 2
50/50
45.79645.796
316084AB2-161 E
Adder
9.597647058823538.158
961942AG1-037 E
Adder
0.54705882352941180.465
961941AG1-037 C
Adder
0.82117647058823530.698
923852AB2-025 E
Adder
1.84117647058823521.565
941031AE2-094 C
Adder
59.2294117647058850.345
941032AE2-094 E
Adder
26.52705882352941222.548
3150831SPRUNCA
Adder
15.77411764705882313.408
3150841SPRUNCB
Adder
15.77411764705882313.408
966872AG1-558 E
Adder
2.0552941176470591.747
966871AG1-558 C
Adder
4.083.468
316076AC2-137 E
50/50
2.4242.424
316075AC2-137 C
50/50
0.6870.687
923842AB2-024 E
Adder
3.07294117647058852.612
316157AD2-030 E
Adder
1.99764705882352931.698
939412AE1-173 E
Adder
97.132941176470682.563
926662AC1-147 E
Adder
2.34000000000000031.989
916192Z1-068 E
Adder
3.3141176470588242.817
957492AF2-043 E
Adder
2.48941176470588272.116
962572AG1-106 E
Adder
1.86588235294117651.586
957872AF2-081 E
Adder
7.50470588235294046.379
938552AE1-074 E
Adder
2.05764705882352941.749
944631AF1-128 C
50/50
71.28371.283
936592AD2-074 E
Adder
14.19411764705882312.065
316160AE1-175 E
50/50
2.1682.168
926755AC1-161 E
Adder
23.1894117647058819.711
933291AC2-141 C
Adder
54.3223529411764746.174
3150921YORKTN3
Adder
215.8894117647059183.506
925522AC1-027 E
Adder
2.14588235294117661.824
941102AE2-104 E
Adder
9.2858823529411767.893
3145256KINGFORK
Adder
1.78823529411764711.52
946282AF1-292 E
Adder
1.61.36
944012AF1-069 E
Adder
7.5176470588235296.39
3150631CHESTG8
50/50
6.8166.816
3150611CHESTG7
50/50
6.9276.927
961952AG1-038 E
Adder
6.9482352941176475.906
961951AG1-038 C
Adder
5.0317647058823534.277
925865AC1-065 E
Adder
28.22117647058823723.988
923263AB1-132 E OP
Adder
9.595294117647068.156
940481AE2-033 C
Adder
25.63411764705882621.789
940482AE2-033 E
Adder
17.28117647058823514.689
940541AE2-040 C
Adder
4.5517647058823533.869
927041AC1-191 C
Adder
16.38352941176470513.926
3138116ELKO L286
50/50
2.5282.528
961611AG1-000B C
Adder
28.33647058823529424.086
926072AC1-086 E
Adder
15.0047058823529412.754
960081AF2-299 C
Adder
2.92.465
3145413WATKINS
Adder
1.15882352941176480.985
938771AE1-103 C
Adder
4.9776470588235294.231
963041AG1-153 C
Adder
8.37.055
944011AF1-069 C
Adder
19.35294117647058716.45
3150621CHESTS7
50/50
3.183.18
3150601CHESTF5
50/50
113.923113.923
925332AB2-190 E
Adder
14.35882352941176512.205
962962AG1-145 E
50/50
2.6282.628
927226AC1-216 E
Adder
13.74117647058823411.68
944591AF1-124 C
Adder
80.4682352941176568.398
944601AF1-125 C
Adder
78.9482352941176467.106
941591AE2-156 C
Adder
31.63647058823529426.891
936666AD2-085 E
Adder
9.7729411764705898.307
920692AA2-178 E
Adder
6.9352941176470585.895
966622AG1-532 E
Adder
1.45058823529411771.233
917122Z2-027 E
Adder
2.3352941176470591.985
3146326AYDLETT TAP
Adder
2.3717647058823532.016
938532AE1-072 E
Adder
16.0329411764705913.628
316233AE1-074 C
Adder
4.08588235294117653.473
927042AC1-191 E
Adder
8.1611764705882366.937
3150691DARBY 3
50/50
4.5894.589
940551AE2-041 C
Adder
12.15411764705882410.331
935162AD1-151 E
Adder
19.1376470588235316.267
957832AF2-077 E
Adder
2.49294117647058842.119
943461AF1-017 C
Adder
2.34941176470588251.997
316311AC2-079 C
Adder
9.9811764705882358.484
932596AC2-079 E
Adder
16.2847058823529413.842
934501AD1-074 C
Adder
56.2023529411764747.772
924517AB2-100 E2
Adder
4.5505882352941183.868
937226AE2-253 E
Adder
10.2482352941176478.711
942001AE2-212 C
Adder
3.73647058823529443.176
3150671DARBY 1
50/50
4.5674.567
3150641CHESTS8
50/50
3.5093.509
939192AE1-149 E
Adder
12.39882352941176410.539
943741AF1-042 C
Adder
4.5517647058823533.869
939312AE1-162 E
Adder
2.54117647058823562.16
934065AD1-033 E
Adder
8.8270588235294137.503
934521AD1-076 C
Adder
20.41176470588235517.35
934511AD1-075 C
Adder
14.05058823529411811.943
919692AA2-053 E OP
Adder
6.6552941176470595.657
923573AB1-173 E OP
Adder
5.11176470588235254.345
3145723EMPORIA
Adder
0.66941176470588230.569
920042AA2-088 E OP
Adder
17.4414.824
919152AA1-139 E1
Adder
7.166.086
316240AF1-291 C
Adder
3.7788235294117653.212
944641AF1-129 C
Adder
179.7623529411765152.798
3142296MT RD221
50/50
0.2170.217
316004AC1-112 C
50/50
0.5960.596
924814AB2-134 E
Adder
22.5082352941176519.132
942342AE2-247 E
Adder
3.58470588235294143.047
316141AB2-099 E
Adder
0.410588235294117640.349
923994AB2-040_E
Adder
9.5835294117647068.146
316088AB2-174 E
Adder
10.1435294117647078.622
957481AF2-042 C
Adder
64.6541176470588354.956
942002AE2-212 E
Adder
2.49058823529411782.117
940431AE2-027 C
Adder
22.57058823529411719.185
3150681DARBY 2
50/50
4.5734.573
943742AF1-042 E
Adder
7.42705882352941156.313
934392AD1-063 E
Adder
1.8235294117647061.55
944581AF1-123 C
Adder
80.1835294117647168.156
941101AE2-104 C
Adder
5.8411764705882354.965
901082W1-029 E
Adder
55.2529411764705946.965
3143316POE
Adder
2.31058823529411761.964
939191AE1-149 C
Adder
18.59882352941176415.809
934146AD1-041 E
Adder
6.0129411764705885.111
957601AF2-054 C
Adder
3.56117647058823563.027
316382AG1-145 C
50/50
0.6420.642
3137643SOCKMAN
Adder
1.1117647058823530.945
913392Y1-086 E
Adder
3.8282352941176473.254
940432AE2-027 E
Adder
15.04705882352941212.79
316312AB1-027 C
50/50
0.9560.956
939612AE1-191 E
Adder
9.628.177
957602AF2-054 E
Adder
2.37411764705882342.018
939411AE1-173 C
Adder
145.69882352941175123.844
934012AD1-025 E
Adder
17.78941176470588215.121
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.4068.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
156.721156.721
NYPJM->LTFIMP_NY
CLTF
4.1384.138
LGEELTFEXP_LGEE->PJM
CLTF
3.3583.358
G-007PJM->LTFIMP_G-007
CMTX_NF
9.2239.223
SIGELTFEXP_SIGE->PJM
CLTF
0.620.62
WECLTFEXP_WEC->PJM
CLTF
1.7271.727
CPLELTFEXP_CPLE->PJM
CLTF
17.60917.609
TVALTFEXP_TVA->PJM
CLTF
12.40612.406
O66PJM->LTFIMP_O-066
CMTX_NF
58.60758.607
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.33484.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.67448.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
9.5679.567
LAGNLTFEXP_LAGN->PJM
CLTF
15.46415.464

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.04 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4112.5
MW Contribution:68.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
927021AC1-189 C
Adder
11.1482352941176499.476
926071AC1-086 C
Adder
27.76352941176470823.599
946281AF1-292 C
Adder
2.00588235294117641.705
316169AC1-164 GEN
80/20
63.00863.008
3151091ELIZAR2
80/20
4.7734.773
316349AD2-085 C
Adder
5.0752941176470594.314
966621AG1-532 C
Adder
1.81764705882352941.545
316320Y1-086 C
80/20
0.3290.329
316388AE2-253 GEN
80/20
2.9612.961
316159AE1-175 C
80/20
0.6130.613
942341AE2-247 C
Adder
2.21.87
316246AF1-032 C
80/20
0.4270.427
316274AC1-208 C
Adder
11.86588235294117810.086
962571AG1-106 C
Adder
3.5905882352941183.052
3151311EDGECMA
Adder
20.00352941176470617.003
957871AF2-081 C
80/20
15.09215.092
3150651CHESTF6
Adder
26.14823529411764722.226
936591AD2-074 C
Adder
7.3964705882352946.287
316033AB2-134 GEN
80/20
3.0983.098
934011AD1-025 C
80/20
3.8313.831
933981AD1-022 C
Adder
12.41647058823529510.554
938531AE1-072 C
80/20
26.50226.502
3150731STONECA
Adder
9.9858823529411778.488
935161AD1-151 C
80/20
23.75423.754
958161AF2-110 C
80/20
2.042.04
313526AB2-022 C
80/20
0.5630.563
316017AA1-139 ULT1
80/20
1.6281.628
940641AE2-051 C
Adder
23.00823529411764719.557
943471AF1-018 C
Adder
10.3670588235294128.812
3152331SURRY 2
80/20
40.26840.268
3151201GRAVEL4
80/20
3.8063.806
3151211GRAVEL5
80/20
3.7583.758
3151221GRAVEL6
80/20
3.8023.802
316236AE1-162 C
80/20
0.5280.528
961941AG1-037 C
Adder
0.69764705882352940.593
934321AD1-056 C
Adder
8.1541176470588246.931
934331AD1-057 C
Adder
4.5482352941176483.866
941031AE2-094 C
Adder
50.196470588235342.667
3150831SPRUNCA
Adder
10.6141176470588259.022
3150841SPRUNCB
Adder
10.6141176470588259.022
966871AG1-558 C
Adder
3.3847058823529412.877
316075AC2-137 C
80/20
0.5730.573
964211AG1-282 C
Adder
2.5270588235294122.148
316369AC1-216 C
80/20
2.3642.364
3151081ELIZAR1
80/20
4.8584.858
316018AA1-139 ULT2
80/20
1.6281.628
3152181CUNINGC
80/20
7.9167.916
944631AF1-128 C
80/20
57.75157.751
933291AC2-141 C
80/20
47.32947.329
3150921YORKTN3
80/20
186.63186.63
3151191GRAVEL3
80/20
3.7583.758
934501AD1-074 C
Adder
48.0341176470588340.829
961671AG1-007 C
Adder
1.22941176470588221.045
957861AF2-080 C
Adder
10.1247058823529418.606
3152161CUNINGA
80/20
7.9167.916
3152171CUNINGB
80/20
7.9167.916
3150631CHESTG8
80/20
5.5225.522
3150611CHESTG7
80/20
5.6125.612
961951AG1-038 C
Adder
4.277647058823533.636
3144216WINCHST
80/20
0.2040.204
316316AC1-027 C
80/20
0.4790.479
940481AE2-033 C
Adder
21.37647058823529618.17
940541AE2-040 C
Adder
3.7941176470588243.225
927041AC1-191 C
Adder
13.58823529411764911.55
963611AG1-210 C
Adder
0.81058823529411760.689
957831AF2-077 C
80/20
0.4940.494
961611AG1-000B C
80/20
23.84623.846
316375AC2-012 C
80/20
2.0492.049
316072AD1-144 C
80/20
0.4250.425
960081AF2-299 C
Adder
2.4235294117647062.06
938771AE1-103 C
Adder
4.2458823529411773.609
963041AG1-153 C
Adder
7.0223529411764725.969
944011AF1-069 C
Adder
16.40117647058823613.941
3150621CHESTS7
80/20
2.5762.576
3150601CHESTF5
80/20
92.29692.296
944591AF1-124 C
80/20
69.53869.538
944601AF1-125 C
80/20
68.22568.225
3151101ELIZAR3
80/20
4.9194.919
941591AE2-156 C
80/20
27.25627.256
940551AE2-041 C
Adder
10.3670588235294128.812
943461AF1-017 C
Adder
1.99058823529411751.692
316311AC2-079 C
Adder
8.4682352941176487.198
934521AD1-076 C
Adder
17.4447058823529414.828
934511AD1-075 C
Adder
12.00823529411764810.207
316263AC1-034 C
Adder
8.5517647058823547.269
316321Z2-027 C
80/20
0.5420.542
316240AF1-291 C
Adder
3.02705882352941162.573
944641AF1-129 C
Adder
143.61529411764707122.073
3142296MT RD221
80/20
0.180.18
316004AC1-112 C
80/20
0.5060.506
316036AC1-147 C
80/20
0.5590.559
316305AF2-043 C
80/20
0.5230.523
934621AD1-088 C
Adder
11.2658823529411789.576
942001AE2-212 C
Adder
3.01764705882352932.565
3150641CHESTS8
80/20
2.8432.843
962861AG1-135 C
Adder
7.9105882352941186.724
943741AF1-042 C
Adder
3.87058823529411773.29
958261AF2-120 C
Adder
8.16.885
939191AE1-149 C
Adder
15.33294117647058713.033
957601AF2-054 C
Adder
3.03647058823529432.581
316382AG1-145 C
80/20
0.5540.554
3151171GRAVELC
80/20
1.2921.292
3150981CHESPKA
80/20
0.6610.661
957481AF2-042 C
Adder
64.7188235294117655.011
3152191CUNINGD
80/20
17.70617.706
940431AE2-027 C
Adder
18.18117647058823715.454
316294AC1-161 C
80/20
7.7077.707
944581AF1-123 C
80/20
69.29269.292
316185AD1-033 C
80/20
1.8591.859
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
55
3137643SOCKMAN
Adder
0.93411764705882360.794
316312AB1-027 C
80/20
0.8120.812
966661AG1-536 C
Adder
6.96705882352941155.922
939411AE1-173 C
Adder
124.68470588235294105.982
3151161SURRY 1
80/20
36.99336.993
3150991CHESPKB
80/20
1.0961.096
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1467.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
133.887133.887
NYPJM->LTFIMP_NY
CLTF
3.5973.597
LGEELTFEXP_LGEE->PJM
CLTF
2.952.95
WECLTFEXP_WEC->PJM
CLTF
1.5171.517
SIGELTFEXP_SIGE->PJM
CLTF
0.5440.544
CPLELTFEXP_CPLE->PJM
CLTF
14.96914.969
TVALTFEXP_TVA->PJM
CLTF
10.74810.748
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.17274.172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.32542.325
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.3698.369
LAGNLTFEXP_LAGN->PJM
CLTF
13.38813.388

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.93 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4252.57
MW Contribution:134.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
920692AA2-178 E
Adder
3.6352941176470593.09
966622AG1-532 E
Adder
0.780.663
961942AG1-037 E
Adder
0.290588235294117650.247
934521AD1-076 C
Adder
10.7329411764705889.123
934511AD1-075 C
Adder
7.38823529411764756.28
3145723EMPORIA
Adder
0.360.306
934501AD1-074 C
Adder
29.5529411764705925.12
924517AB2-100 E2
Adder
2.4388235294117652.073
937226AE2-253 E
Adder
5.30941176470588254.513
957872AF2-081 E
Adder
3.88941176470588263.306
917122Z2-027 E
Adder
1.21294117647058821.031
3146326AYDLETT TAP
Adder
1.22941176470588221.045
938532AE1-072 E
Adder
8.3117647058823547.065
316233AE1-074 C
Adder
2.25058823529411761.913
927042AC1-191 E
Adder
4.4917647058823533.818
3150691DARBY 3
50/50
2.4352.435
940551AE2-041 C
Adder
6.3964705882352955.437
935162AD1-151 E
Adder
10.0317647058823528.527
957832AF2-077 E
Adder
1.29764705882352941.103
943461AF1-017 C
Adder
1.22941176470588221.045
316311AC2-079 C
Adder
5.2200000000000014.437
932596AC2-079 E
Adder
8.517647058823537.24
961941AG1-037 C
Adder
0.435294117647058830.37
923852AB2-025 E
Adder
0.98705882352941180.839
923862AB2-026 E
Adder
1.02941176470588250.875
941031AE2-094 C
Adder
31.94588235294117627.154
941032AE2-094 E
Adder
14.3082352941176512.162
3150831SPRUNCA
Adder
8.5294117647058827.25
3150841SPRUNCB
Adder
8.5294117647058827.25
966872AG1-558 E
Adder
1.1317647058823530.962
966871AG1-558 C
Adder
2.24588235294117671.909
316076AC2-137 E
50/50
1.2591.259
316075AC2-137 C
50/50
0.3570.357
923842AB2-024 E
Adder
1.61176470588235321.37
316157AD2-030 E
Adder
1.05647058823529430.898
939412AE1-173 E
Adder
51.40235294117647443.692
926662AC1-147 E
Adder
1.2117647058823531.03
916192Z1-068 E
Adder
1.71529411764705891.458
957492AF2-043 E
Adder
1.29176470588235311.098
316141AB2-099 E
Adder
0.217647058823529420.185
938562AE1-075 E
Adder
0.87764705882352940.746
3152251N ANNA1
50/50
28.6128.61
938552AE1-074 E
Adder
1.13294117647058810.963
3150471FOUR RIVERE
50/50
2.9592.959
315052AA1-145 CT2
50/50
4.7814.781
944631AF1-128 C
Adder
37.3682352941176531.763
936592AD2-074 E
Adder
7.7847058823529426.617
316160AE1-175 E
Adder
1.11058823529411770.944
926755AC1-161 E
Adder
11.89764705882352810.113
933291AC2-141 C
Adder
27.87176470588235223.691
3150921YORKTN3
Adder
110.8188235294117694.196
925522AC1-027 E
Adder
1.11058823529411770.944
941102AE2-104 E
Adder
4.8364705882352944.111
3145256KINGFORK
Adder
0.92823529411764720.789
960081AF2-299 C
Adder
1.56117647058823541.327
3145413WATKINS
Adder
0.60941176470588240.518
938771AE1-103 C
Adder
2.60941176470588232.218
963041AG1-153 C
Adder
4.4858823529411773.813
944011AF1-069 C
Adder
10.437647058823538.872
966881AG1-559 C
50/50
2.2942.294
3150601CHESTF5
Adder
59.7211764705882350.763
925332AB2-190 E
Adder
7.537647058823536.407
962962AG1-145 E
Adder
1.34588235294117631.144
927226AC1-216 E
Adder
7.19176470588235356.113
944591AF1-124 C
Adder
41.5988235294117735.359
944601AF1-125 C
Adder
40.81294117647059534.691
941591AE2-156 C
Adder
16.3729411764705913.917
936666AD2-085 E
Adder
5.11411764705882454.347
923994AB2-040_E
Adder
1.6270588235294121.383
316088AB2-174 E
Adder
5.4517647058823534.634
942002AE2-212 E
Adder
1.33058823529411761.131
940431AE2-027 C
Adder
12.02823529411764810.224
3150681DARBY 2
50/50
2.4262.426
962862AG1-135 E
Adder
3.43764705882352972.922
943742AF1-042 E
Adder
4.07294117647058853.462
934392AD1-063 E
Adder
0.960.816
944581AF1-123 C
Adder
41.45176470588235435.234
941101AE2-104 C
Adder
3.04235294117647072.586
918512AA1-065 E OP
Adder
4.7847058823529424.067
934502AD1-074 E
Adder
15.04470588235294112.788
934512AD1-075 E
Adder
3.76117647058823533.197
924516AB2-100 E1
Adder
2.4388235294117652.073
966621AG1-532 C
Adder
1.17058823529411770.995
919153AA1-139 E2
Adder
3.71058823529411753.154
226704AOCX4-046 E
Adder
-2.8423529411764705-2.416
943172AE2-346 E
Adder
0.52235294117647060.444
934522AD1-076 E
Adder
5.4705882352941194.65
940492AE2-034 E
Adder
2.72588235294117662.317
918492AA1-063AE OP
Adder
3.47058823529411782.95
957871AF2-081 C
Adder
9.0741176470588247.713
3145506HICKORY
Adder
1.98352941176470581.686
946262AF1-291 E
Adder
1.34470588235294121.143
3150651CHESTF6
Adder
17.46352941176470714.844
3150461FOUR RIVERD
50/50
2.9592.959
3150441FOUR RIVERB
50/50
3.0033.003
936591AD2-074 C
Adder
4.7717647058823534.056
3130536PAPERMILL
Adder
5.95411764705882355.061
939602AE1-190 E
Adder
1.27058823529411781.08
933292AC2-141 E
Adder
11.89764705882352810.113
934576AD1-082 E
Adder
4.0317647058823533.427
944602AF1-125 E
Adder
93.4294117647058979.415
943612AF1-032 E
Adder
0.840.714
901082W1-029 E
Adder
28.74235294117647424.431
3143316POE
Adder
1.23411764705882351.049
939191AE1-149 C
Adder
9.8564705882352958.378
934146AD1-041 E
Adder
3.17647058823529442.7
957601AF2-054 C
Adder
1.8835294117647061.601
940481AE2-033 C
Adder
13.74117647058823411.68
940482AE2-033 E
Adder
9.2635294117647067.874
940541AE2-040 C
Adder
2.442.074
927041AC1-191 C
Adder
9.0164705882352937.664
3138116ELKO L286
50/50
1.3131.313
961611AG1-000B C
Adder
14.76705882352941212.552
933982AD1-022 E
Adder
4.1682352941176483.543
3145946PLYMOUTH TP
Adder
0.283529411764705860.241
316336AC2-165 C
Adder
8.2082352941176486.977
3150481FOUR RIVERF
50/50
3.6143.614
940641AE2-051 C
Adder
14.38235294117647112.225
926785AC1-164_E
Adder
17.0152941176470614.463
943471AF1-018 C
Adder
6.3964705882352955.437
316084AB2-161 E
Adder
5.06000000000000054.301
920042AA2-088 E OP
Adder
9.2247058823529417.841
919152AA1-139 E1
Adder
3.71058823529411753.154
316240AF1-291 C
Adder
2.01647058823529421.714
944641AF1-129 C
Adder
95.9141176470588381.527
3150451FOUR RIVERC
50/50
3.6693.669
3142296MT RD221
50/50
0.1170.117
316004AC1-112 C
50/50
0.3130.313
924814AB2-134 E
Adder
11.78117647058823510.014
942342AE2-247 E
Adder
1.87647058823529411.595
946282AF1-292 E
Adder
0.86117647058823530.732
944012AF1-069 E
Adder
4.0552941176470593.447
939262AE1-157 E
Adder
7.2070588235294136.126
3150431FOUR RIVERA
50/50
3.0033.003
961952AG1-038 E
Adder
3.81058823529411763.239
961951AG1-038 C
Adder
2.7588235294117652.345
925865AC1-065 E
Adder
14.8929411764705912.659
226896D-009
Adder
-1.4576470588235295-1.239
958502AF2-144 E
Adder
1.0117647058823530.86
942001AE2-212 C
Adder
1.99647058823529421.697
3150671DARBY 1
50/50
2.4232.423
962861AG1-135 C
Adder
5.1564705882352944.383
939192AE1-149 E
Adder
6.5717647058823535.586
943741AF1-042 C
Adder
2.4964705882352942.122
939312AE1-162 E
Adder
1.31882352941176471.121
934065AD1-033 E
Adder
4.5682352941176473.883
946281AF1-292 C
Adder
1.29176470588235311.098
960082AF2-299 E
Adder
1.040.884
916042Z1-036 E
Adder
25.53647058823529321.706
923832AB2-022 E
Adder
1.12235294117647060.954
938772AE1-103 E
Adder
3.60352941176470633.063
963042AG1-153 E
Adder
6.7294117647058825.72
939261AE1-157 C
Adder
13.28588235294117611.293
966882AG1-559 E
50/50
1.1551.155
930122AB1-027 E
50/50
1.3221.322
316169AC1-164 GEN
Adder
37.8729411764705932.192
944592AF1-124 E
Adder
95.2635294117647180.974
944582AF1-123 E
Adder
94.9280.682
316349AD2-085 C
Adder
3.13411764705882372.664
935112AD1-144 E
Adder
0.86117647058823530.732
913392Y1-086 E
Adder
1.9870588235294121.689
933502AC2-165 E
Adder
6.177647058823535.251
940432AE2-027 E
Adder
8.0188235294117656.816
316312AB1-027 C
50/50
0.5020.502
939612AE1-191 E
Adder
5.0823529411764714.32
957602AF2-054 E
Adder
1.2552941176470591.067
939411AE1-173 C
Adder
77.103529411764765.538
934012AD1-025 E
Adder
9.3117647058823547.915
933981AD1-022 C
Adder
7.6564705882352946.508
900672V4-068 E
Adder
0.308235294117647050.262
938531AE1-072 C
Adder
15.94470588235294213.553
3145393UNCAMP
Adder
5.3964705882352944.587
315051AA1-145 CT1
50/50
4.7834.783
3142366NRTHEST
50/50
0.1760.176
3150701DARBY 4
50/50
2.4382.438
3150731STONECA
Adder
6.46823529411764755.498
935161AD1-151 C
Adder
15.04823529411764812.791
932046AC2-012 E
Adder
11.9823529411764710.185
958161AF2-110 C
Adder
1.24117647058823531.055
3152261N ANNA2
50/50
28.62228.622
940642AE2-051 E
Adder
9.5882352941176498.15
926412AC1-112 E
50/50
1.0751.075
942341AE2-247 C
Adder
1.35882352941176481.155
943462AF1-017 E
Adder
2.00588235294117641.705
958162AF2-110 E
Adder
1.97411764705882351.678
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.6074.607
NYPJM->LTFIMP_NY
CLTF
3.113.11
LGEELTFEXP_LGEE->PJM
CLTF
2.0262.026
WECLTFEXP_WEC->PJM
CLTF
1.0481.048
G-007PJM->LTFIMP_G-007
CMTX_NF
7.0597.059
SIGELTFEXP_SIGE->PJM
CLTF
0.3720.372
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.84786.847
CPLELTFEXP_CPLE->PJM
CLTF
9.659.65
TVALTFEXP_TVA->PJM
CLTF
7.1437.143
O66PJM->LTFIMP_O-066
CMTX_NF
44.79944.799
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.34851.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.44428.444
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.7125.712
LAGNLTFEXP_LAGN->PJM
CLTF
8.98.9

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.32 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3230.79
MW Contribution:39.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926071AC1-086 C
Adder
16.83294117647058714.308
946281AF1-292 C
Adder
1.23176470588235291.047
939261AE1-157 C
80/20
13.3213.32
316169AC1-164 GEN
80/20
36.80636.806
966621AG1-532 C
Adder
1.1164705882352940.949
3152261N ANNA2
80/20
26.0926.09
962571AG1-106 C
Adder
2.17764705882352951.851
957871AF2-081 C
Adder
8.7129411764705887.406
3150651CHESTF6
Adder
16.84705882352941214.32
933981AD1-022 C
Adder
7.3258823529411776.227
938531AE1-072 C
Adder
15.30823529411764713.012
315051AA1-145 CT1
80/20
4.7034.703
3142366NRTHEST
80/20
0.1710.171
3150701DARBY 4
80/20
2.3652.365
3150731STONECA
Adder
6.2458823529411775.309
316336AC2-165 C
Adder
7.7411764705882356.58
961941AG1-037 C
Adder
0.41529411764705880.353
941031AE2-094 C
Adder
30.39411764705882425.835
3150391LDYSMT3
80/20
4.4174.417
3150831SPRUNCA
80/20
8.2198.219
3150841SPRUNCB
Adder
8.2188235294117656.986
966871AG1-558 C
80/20
2.1962.196
316075AC2-137 C
80/20
0.3470.347
964211AG1-282 C
Adder
1.65294117647058841.405
3152251N ANNA1
80/20
26.07926.079
3150431FOUR RIVERA
80/20
2.9522.952
3150631CHESTG8
80/20
3.4613.461
3150611CHESTG7
80/20
3.5173.517
961951AG1-038 C
Adder
2.7117647058823532.305
940481AE2-033 C
Adder
13.13529411764705811.165
940541AE2-040 C
Adder
2.33294117647058831.983
960081AF2-299 C
Adder
1.48823529411764691.265
938771AE1-103 C
Adder
2.5011764705882352.126
963041AG1-153 C
Adder
4.2658823529411763.626
944011AF1-069 C
Adder
9.9305882352941198.441
966881AG1-559 C
80/20
2.2882.288
3150621CHESTS7
80/20
1.6141.614
3150601CHESTF5
80/20
57.83757.837
944591AF1-124 C
Adder
39.9505882352941233.958
944601AF1-125 C
Adder
39.1964705882352933.317
941591AE2-156 C
Adder
15.7305882352941213.371
3150381LDYSMT2
80/20
4.3034.303
316233AE1-074 C
Adder
2.1552941176470591.832
3150691DARBY 3
80/20
2.3622.362
940551AE2-041 C
Adder
6.2364705882352955.301
943461AF1-017 C
Adder
1.18117647058823531.004
316311AC2-079 C
Adder
5.0141176470588234.262
934521AD1-076 C
Adder
10.2717647058823538.731
934511AD1-075 C
Adder
7.0705882352941176.01
3150411LDYSMT5
80/20
4.4394.439
316240AF1-291 C
Adder
1.94470588235294131.653
944641AF1-129 C
Adder
92.5282352941176578.649
3150451FOUR RIVERC
80/20
3.6073.607
3142296MT RD221
80/20
0.1140.114
316004AC1-112 C
80/20
0.3050.305
934501AD1-074 C
Adder
28.28352941176470724.041
934621AD1-088 C
Adder
7.1611764705882356.087
942001AE2-212 C
Adder
1.92117647058823531.633
3150671DARBY 1
80/20
2.3512.351
3150641CHESTS8
80/20
1.7811.781
962861AG1-135 C
Adder
5.0788235294117654.317
943741AF1-042 C
Adder
2.45411764705882352.086
3150471FOUR RIVERE
80/20
2.9092.909
315052AA1-145 CT2
80/20
4.74.7
3150851SPRUNCC
80/20
0.1470.147
944631AF1-128 C
80/20
36.1936.19
933291AC2-141 C
Adder
26.7822.763
3150921YORKTN3
Adder
107.0694117647058991.009
3150371LDYSMT1
80/20
4.2494.249
927041AC1-191 C
80/20
8.8178.817
963611AG1-210 C
Adder
0.53882352941176470.458
961611AG1-000B C
Adder
14.23176470588235412.097
3150461FOUR RIVERD
80/20
2.9092.909
3150441FOUR RIVERB
80/20
2.9522.952
3150861SPRUNCD
80/20
0.1470.147
936591AD2-074 C
Adder
4.6894117647058823.986
3143096IRON208
80/20
0.4040.404
958261AF2-120 C
Adder
5.2200000000000014.437
939191AE1-149 C
Adder
9.4788235294117668.057
957601AF2-054 C
Adder
1.83764705882352961.562
957481AF2-042 C
Adder
40.39647058823529634.337
3150401LDYSMT4
80/20
4.4254.425
940431AE2-027 C
Adder
11.5988235294117659.859
3150681DARBY 2
80/20
2.3542.354
944581AF1-123 C
Adder
39.80941176470588533.838
941101AE2-104 C
Adder
2.92000000000000042.482
3137643SOCKMAN
Adder
0.56941176470588240.484
316312AB1-027 C
80/20
0.4890.489
966661AG1-536 C
Adder
4.4905882352941183.817
939411AE1-173 C
Adder
73.6611764705882562.612
942341AE2-247 C
Adder
1.30470588235294121.109
3150481FOUR RIVERF
80/20
3.5533.553
940641AE2-051 C
Adder
13.71529411764705811.658
943471AF1-018 C
Adder
6.2364705882352955.301
316349AD2-085 C
Adder
3.0105882352941182.559
935161AD1-151 C
Adder
14.5176470588235312.34
958161AF2-110 C
Adder
1.19176470588235281.013
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.3484.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.51781.517
NYPJM->LTFIMP_NY
CLTF
2.8322.832
LGEELTFEXP_LGEE->PJM
CLTF
1.8211.821
SIGELTFEXP_SIGE->PJM
CLTF
0.3350.335
WECLTFEXP_WEC->PJM
CLTF
0.9380.938
CPLELTFEXP_CPLE->PJM
CLTF
9.1099.109
TVALTFEXP_TVA->PJM
CLTF
6.5746.574
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.86545.865
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.97725.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.1595.159
LAGNLTFEXP_LAGN->PJM
CLTF
8.1928.192

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.82 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3858.59
MW Contribution:67.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966621AG1-532 C
Adder
2.06235294117647071.753
316320Y1-086 C
80/20
0.330.33
316388AE2-253 GEN
80/20
2.9552.955
3151021BRUNSWICKG1
80/20
12.91412.914
3151041BRUNSWICKG3
80/20
12.91412.914
942341AE2-247 C
80/20
2.2382.238
316246AF1-032 C
80/20
0.4280.428
933981AD1-022 C
Adder
12.98823529411764711.04
938531AE1-072 C
80/20
26.49826.498
3150731STONECA
Adder
9.5788235294117648.142
935161AD1-151 C
Adder
22.80117647058823519.381
316083AB2-161 C
80/20
0.8230.823
958161AF2-110 C
80/20
2.0582.058
313526AB2-022 C
80/20
0.5650.565
316017AA1-139 ULT1
80/20
1.6261.626
3152431Z1-086 GT3
80/20
16.53816.538
316336AC2-165 C
Adder
14.04941176470588411.942
940641AE2-051 C
80/20
27.74527.745
943471AF1-018 C
Adder
8.4917647058823537.218
3152331SURRY 2
80/20
35.95635.956
3151201GRAVEL4
80/20
3.6573.657
3151211GRAVEL5
80/20
3.6113.611
3151221GRAVEL6
80/20
3.6533.653
316236AE1-162 C
80/20
0.5140.514
961941AG1-037 C
Adder
0.74470588235294120.633
934321AD1-056 C
Adder
9.0458823529411777.689
934331AD1-057 C
Adder
5.04588235294117654.289
958211AF2-115 C
Adder
3.0058823529411772.555
3151531CLOVER1
80/20
18.57418.574
316258AE1-075 C
80/20
0.5130.513
941031AE2-094 C
80/20
63.15563.155
3150831SPRUNCA
80/20
13.15813.158
3150841SPRUNCB
80/20
13.15813.158
3151081ELIZAR1
80/20
4.824.82
316018AA1-139 ULT2
80/20
1.6261.626
3150851SPRUNCC
80/20
0.2360.236
944631AF1-128 C
Adder
51.9752941176470644.179
933291AC2-141 C
80/20
46.08646.086
3150921YORKTN3
Adder
165.5670588235294140.732
3151191GRAVEL3
80/20
3.6113.611
934501AD1-074 C
Adder
50.0317647058823542.527
961671AG1-007 C
Adder
1.34941176470588231.147
3156116Z1-036WIND
80/20
0.9810.981
957861AF2-080 C
Adder
11.0270588235294129.373
316023AB2-100 C2
80/20
1.4231.423
316315AB2-025 C
80/20
0.6170.617
3138533PONTONDP
Adder
0.89058823529411770.757
3151541CLOVER2
80/20
18.418.4
316316AC1-027 C
80/20
0.4760.476
960081AF2-299 C
Adder
2.74941176470588242.337
936261AD2-033 C
Adder
17.81058823529411615.139
961791AG1-021 C
Adder
2.40470588235294122.044
940481AE2-033 C
80/20
24.49624.496
940541AE2-040 C
80/20
4.3564.356
3152441Z1-086 ST
80/20
28.79528.795
961611AG1-000B C
Adder
22.90588235294117719.47
316375AC2-012 C
80/20
2.0322.032
316072AD1-144 C
80/20
0.4180.418
938771AE1-103 C
80/20
4.3814.381
963041AG1-153 C
80/20
8.7798.779
3151051BRUNSWICKS1
80/20
26.8326.83
944011AF1-069 C
80/20
20.63520.635
3150601CHESTF5
Adder
83.0647058823529570.605
944591AF1-124 C
80/20
69.22169.221
944601AF1-125 C
80/20
67.91467.914
3151101ELIZAR3
80/20
4.8814.881
941591AE2-156 C
80/20
27.03327.033
3156056W1-029WIND
80/20
1.1641.164
3152411Z1-086 GT1
80/20
16.54216.542
3152421Z1-086 GT2
80/20
16.53816.538
316233AE1-074 C
80/20
3.9163.916
940551AE2-041 C
Adder
8.4917647058823537.218
943461AF1-017 C
80/20
2.0242.024
316311AC2-079 C
80/20
8.6058.605
946301AF1-294 C
Adder
4.9423529411764714.201
942461AE2-259 C
Adder
12.99058823529411711.042
934621AD1-088 C
80/20
14.01914.019
942001AE2-212 C
80/20
3.1513.151
934521AD1-076 C
Adder
18.1705882352941215.445
934511AD1-075 C
Adder
12.50823529411764710.632
316263AC1-034 C
Adder
9.488.058
316321Z2-027 C
80/20
0.5460.546
959311AF2-222 C
Adder
22.66470588235294419.265
3151031BRUNSWICKG2
80/20
12.91412.914
316240AF1-291 C
Adder
3.0682352941176472.608
944641AF1-129 C
Adder
144.29529411764705122.651
316036AC1-147 C
80/20
0.5540.554
316305AF2-043 C
80/20
0.5240.524
316365AB2-100 C1
80/20
1.4231.423
957481AF2-042 C
80/20
80.37380.373
940431AE2-027 C
Adder
18.39647058823529615.637
316294AC1-161 C
80/20
7.5057.505
944581AF1-123 C
80/20
68.97668.976
316185AD1-033 C
80/20
1.8511.851
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
5.0455.045
316274AC1-208 C
Adder
13.08588235294117711.123
962571AG1-106 C
Adder
3.98941176470588273.391
3151311EDGECMA
Adder
22.1658823529411818.841
957871AF2-081 C
80/20
15.07515.075
316405AF2-144 C
80/20
0.4360.436
3150651CHESTF6
Adder
26.27176470588235422.331
3150861SPRUNCD
80/20
0.2360.236
964791AG1-342 C
Adder
4.884.148
316313AB2-026 C
80/20
0.5590.559
939191AE1-149 C
80/20
15.94215.942
957601AF2-054 C
Adder
2.53058823529411742.151
3150981CHESPKA
80/20
0.6560.656
927021AC1-189 C
Adder
12.14117647058823710.32
926071AC1-086 C
Adder
30.83882352941176626.213
946281AF1-292 C
Adder
2.2752941176470591.934
964241AG1-285 C
Adder
17.31176470588235414.715
962561AG1-105 C
Adder
12.25882352941176610.42
316169AC1-164 GEN
Adder
49.0282352941176541.674
3151091ELIZAR2
80/20
4.7354.735
316349AD2-085 C
80/20
5.1625.162
3137643SOCKMAN
Adder
1.04352941176470580.887
939411AE1-173 C
80/20
143.49143.49
316381AD1-082 C
80/20
1.8751.875
3151161SURRY 1
80/20
35.54335.543
3150991CHESPKB
80/20
1.0871.087
316303AF2-085
80/20
6.4786.478
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.9747.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
144.491144.491
NYPJM->LTFIMP_NY
CLTF
3.1863.186
LGEELTFEXP_LGEE->PJM
CLTF
2.5932.593
WECLTFEXP_WEC->PJM
CLTF
1.3381.338
SIGELTFEXP_SIGE->PJM
CLTF
0.4870.487
CPLELTFEXP_CPLE->PJM
CLTF
16.71416.714
TVALTFEXP_TVA->PJM
CLTF
10.46710.467
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.12565.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.22440.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6237.623
LAGNLTFEXP_LAGN->PJM
CLTF
13.13513.135

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.79 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4641.11
MW Contribution:225.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961942AG1-037 E
Adder
0.50117647058823530.426
961941AG1-037 C
Adder
0.7517647058823530.639
923852AB2-025 E
50/50
1.7791.779
923862AB2-026 E
Adder
1.8317647058823531.557
941031AE2-094 C
50/50
63.56663.566
941032AE2-094 E
50/50
28.4728.47
3150831SPRUNCA
Adder
13.36352941176470611.359
3150841SPRUNCB
Adder
13.36352941176470611.359
939412AE1-173 E
50/50
96.42796.427
3151081ELIZAR1
50/50
4.8744.874
926662AC1-147 E
Adder
2.02235294117647071.719
916192Z1-068 E
50/50
2.8712.871
957492AF2-043 E
Adder
2.16705882352941171.842
946282AF1-292 E
Adder
1.53058823529411761.301
316315AB2-025 C
50/50
0.6230.623
944012AF1-069 E
50/50
8.0688.068
316316AC1-027 C
50/50
0.4810.481
926072AC1-086 E
Adder
14.16705882352941312.042
960081AF2-299 C
Adder
2.7741176470588242.358
3145413WATKINS
Adder
1.04117647058823540.885
938771AE1-103 C
Adder
4.4282352941176473.764
963041AG1-153 C
50/50
8.8378.837
3151051BRUNSWICKS1
50/50
27.00627.006
944011AF1-069 C
50/50
20.76920.769
925332AB2-190 E
Adder
11.5352941176470599.805
927226AC1-216 E
Adder
11.1270588235294129.458
944591AF1-124 C
50/50
69.97569.975
944601AF1-125 C
50/50
68.65368.653
3151101ELIZAR3
50/50
4.9354.935
941591AE2-156 C
50/50
27.33727.337
936666AD2-085 E
Adder
8.5211764705882367.243
920692AA2-178 E
Adder
6.19058823529411755.262
966622AG1-532 E
Adder
1.3870588235294121.179
917122Z2-027 E
Adder
2.04352941176470631.737
3146326AYDLETT TAP
Adder
2.06705882352941161.757
938532AE1-072 E
Adder
13.96470588235294111.87
3152411Z1-086 GT1
50/50
16.65116.651
3152421Z1-086 GT2
50/50
16.64616.646
316233AE1-074 C
50/50
3.9613.961
935162AD1-151 E
Adder
15.43176470588235513.117
943461AF1-017 C
Adder
2.0482352941176471.741
316311AC2-079 C
Adder
8.7047058823529427.399
932596AC2-079 E
Adder
14.20352941176470712.073
934521AD1-076 C
Adder
18.35647058823529315.603
934511AD1-075 C
Adder
12.6352941176470610.74
919692AA2-053 E OP
Adder
6.2482352941176475.311
923573AB1-173 E OP
Adder
4.8588235294117644.13
3145723EMPORIA
Adder
0.640.544
920042AA2-088 E OP
Adder
15.88941176470588313.506
919152AA1-139 E1
Adder
6.2317647058823535.297
3151031BRUNSWICKG2
50/50
12.99912.999
316240AF1-291 C
Adder
3.11647058823529432.649
944641AF1-129 C
Adder
146.62823529411764124.634
924814AB2-134 E
Adder
18.2270588235294115.493
942342AE2-247 E
Adder
3.12588235294117662.657
934501AD1-074 C
Adder
50.5435294117647142.962
924517AB2-100 E2
Adder
4.3447058823529413.693
937226AE2-253 E
Adder
8.9129411764705877.576
934621AD1-088 C
Adder
14.11647058823529511.999
957482AF2-042 E
Adder
53.94941176470588645.857
958502AF2-144 E
Adder
1.81.53
942001AE2-212 C
Adder
3.19647058823529442.717
939192AE1-149 E
Adder
10.7658823529411769.151
939312AE1-162 E
Adder
2.13058823529411741.811
934065AD1-033 E
50/50
7.6627.662
962572AG1-106 E
Adder
1.76117647058823561.497
957872AF2-081 E
Adder
6.53176470588235255.552
938562AE1-075 E
Adder
1.56235294117647071.328
938552AE1-074 E
50/50
1.9951.995
926755AC1-161 E
50/50
19.88619.886
933291AC2-141 C
50/50
46.58646.586
3150921YORKTN3
Adder
168.0623529411765142.853
925522AC1-027 E
50/50
1.8591.859
941102AE2-104 E
Adder
8.1105882352941186.894
3145256KINGFORK
Adder
1.52941176470588251.3
923263AB1-132 E OP
Adder
9.0588235294117647.7
940481AE2-033 C
50/50
24.72924.729
940482AE2-033 E
50/50
16.67116.671
940541AE2-040 C
50/50
4.3984.398
3152441Z1-086 ST
50/50
28.98428.984
961611AG1-000B C
Adder
23.2270588235294119.743
316375AC2-012 C
50/50
2.0552.055
943172AE2-346 E
Adder
0.90235294117647060.767
934522AD1-076 E
Adder
9.3564705882352957.953
940492AE2-034 E
Adder
4.6423529411764713.946
962571AG1-106 C
Adder
4.0258823529411773.422
918492AA1-063AE OP
Adder
6.065.151
957871AF2-081 C
Adder
15.24000000000000212.954
937482AD2-202 E
Adder
1.561.326
3145506HICKORY
50/50
3.3283.328
946262AF1-291 E
Adder
2.07764705882352941.766
3150651CHESTF6
Adder
26.6976470588235322.693
933292AC2-141 E
50/50
19.88619.886
934576AD1-082 E
Adder
6.6517647058823535.654
944602AF1-125 E
50/50
157.162157.162
943612AF1-032 E
Adder
1.40941176470588241.198
901082W1-029 E
Adder
48.43294117647058541.168
3143316POE
50/50
2.082.08
939191AE1-149 C
Adder
16.1494117647058813.727
316141AB2-099 E
Adder
0.37647058823529410.32
923994AB2-040_E
Adder
9.1117647058823537.745
316088AB2-174 E
Adder
9.6611764705882348.212
957481AF2-042 C
Adder
80.9247058823529468.786
942002AE2-212 E
Adder
2.13058823529411741.811
940431AE2-027 C
Adder
18.6823529411764715.88
316294AC1-161 C
50/50
7.5867.586
944581AF1-123 C
50/50
69.72769.727
316185AD1-033 C
50/50
1.8711.871
916191Z1-068 C
50/50
0.0670.067
941101AE2-104 C
Adder
5.1011764705882364.336
918512AA1-065 E OP
Adder
8.2458823529411777.009
934502AD1-074 E
Adder
25.72941176470588321.87
934512AD1-075 E
Adder
6.4317647058823535.467
924516AB2-100 E1
Adder
4.3447058823529413.693
966621AG1-532 C
Adder
2.0811764705882351.769
919153AA1-139 E2
Adder
6.2317647058823535.297
3151021BRUNSWICKG1
50/50
12.99912.999
3151041BRUNSWICKG3
50/50
12.99912.999
940642AE2-051 E
50/50
18.62918.629
942341AE2-247 C
Adder
2.2635294117647061.924
943462AF1-017 E
Adder
3.34117647058823542.84
958162AF2-110 E
Adder
3.31058823529411762.814
933982AD1-022 E
Adder
7.1423529411764716.071
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
934612AD1-087 E
Adder
5.3305882352941174.531
934622AD1-088 E
Adder
6.79647058823529455.777
3152431Z1-086 GT3
50/50
16.64616.646
316336AC2-165 C
Adder
5.537647058823534.707
940641AE2-051 C
50/50
27.94427.944
316084AB2-161 E
Adder
8.3482352941176477.096
926071AC1-086 C
Adder
31.12823529411764826.459
946281AF1-292 C
Adder
2.2964705882352941.952
960082AF2-299 E
Adder
1.84941176470588251.572
916042Z1-036 E
Adder
43.2517647058823636.764
923832AB2-022 E
Adder
1.8882352941176471.605
938772AE1-103 E
Adder
6.115294117647065.198
963042AG1-153 E
50/50
13.25613.256
944592AF1-124 E
50/50
160.246160.246
944582AF1-123 E
50/50
159.668159.668
3151091ELIZAR2
50/50
4.7894.789
316349AD2-085 C
Adder
5.2223529411764714.439
935112AD1-144 E
Adder
1.42000000000000021.207
3137643SOCKMAN
Adder
1.05294117647058830.895
913392Y1-086 E
Adder
3.3447058823529412.843
940432AE2-027 E
Adder
12.45529411764705910.587
939411AE1-173 C
50/50
144.64144.64
934012AD1-025 E
Adder
14.40588235294117712.245
933981AD1-022 C
Adder
13.12117647058823711.153
900672V4-068 E
Adder
0.53294117647058830.453
938531AE1-072 C
Adder
26.78823529411764822.77
3145393UNCAMP
Adder
9.1811764705882367.804
3150731STONECA
Adder
9.735294117647068.275
935161AD1-151 C
Adder
23.14823529411764719.676
932046AC2-012 E
50/50
20.00120.001
958161AF2-110 C
Adder
2.0811764705882351.769
316303AF2-085
50/50
6.5316.531
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.0368.036
CBM South 2LTFEXP_CBM-S2->PJM
CBM
145.599145.599
NYPJM->LTFIMP_NY
CLTF
3.2313.231
LGEELTFEXP_LGEE->PJM
CLTF
2.6092.609
WECLTFEXP_WEC->PJM
CLTF
1.3461.346
G-007PJM->LTFIMP_G-007
CMTX_NF
7.1157.115
SIGELTFEXP_SIGE->PJM
CLTF
0.490.49
CPLELTFEXP_CPLE->PJM
CLTF
16.84316.843
TVALTFEXP_TVA->PJM
CLTF
10.54210.542
O66PJM->LTFIMP_O-066
CMTX_NF
45.24145.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.46965.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.49440.494
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6697.669
LAGNLTFEXP_LAGN->PJM
CLTF
13.22813.228

Details for 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: H3T539_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H3T539_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.76 %
Rating:3532.0 MVA
Rating Type:C
MVA to Mitigate:3735.42
MW Contribution:95.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150211REMNGT1
50/50
5.0095.009
963031AG1-152 C
50/50
8.228.22
926486AC1-120 E
50/50
4.0694.069
3150731STONECA
Adder
4.46823529411764753.798
3150231REMNGT3
50/50
5.6895.689
926004AC1-076_E
50/50
4.5534.553
940641AE2-051 C
Adder
10.7188235294117669.111
316411AF1-147_GEN1
Adder
-4.564705882352941-3.88
3151771S ANNAG1
50/50
2.0282.028
3151791S ANNAG2
50/50
2.0282.028
3151781S ANNAS1
50/50
1.0421.042
923862AB2-026 E
Adder
0.80470588235294130.684
941031AE2-094 C
Adder
24.10352941176470820.488
941032AE2-094 E
Adder
10.7952941176470589.176
3150831SPRUNCA
Adder
5.9811764705882355.084
3150841SPRUNCB
Adder
5.9811764705882355.084
934862AD1-115 E
50/50
6.2266.226
938562AE1-075 E
Adder
0.68588235294117650.583
3152251N ANNA1
50/50
28.128.1
938552AE1-074 E
Adder
0.82588235294117640.702
926755AC1-161 E
Adder
8.4282352941176477.164
933291AC2-141 C
Adder
19.74352941176470516.782
316267AC1-143 C
50/50
8.4218.421
316257AC1-043 C
50/50
7.6327.632
316254AC1-120 C
50/50
7.97.9
944012AF1-069 E
Adder
3.062.601
966001AG1-469 C
50/50
1.6461.646
3150221REMNGT2
50/50
5.0565.056
925672AC1-043 E
50/50
12.45212.452
926740AC1-158 E2
50/50
17.30117.301
316170AC1-121 C
50/50
2.7132.713
944011AF1-069 C
Adder
7.8752941176470596.694
316045AC1-158 C2
50/50
6.6156.615
944591AF1-124 C
Adder
29.5776470588235325.141
966002AG1-469 E
50/50
0.8230.823
3150241REMNGT4
50/50
5.0775.077
926739AC1-158 E1
50/50
17.30117.301
316233AE1-074 C
Adder
1.63882352941176481.393
958502AF2-144 E
Adder
0.79058823529411770.672
316192AB2-158 C
50/50
1.8041.804
942001AE2-212 C
Adder
1.40470588235294121.194
939412AE1-173 E
Adder
37.8611764705882432.182
963032AG1-152 E
50/50
12.3312.33
926502AC1-121 E
50/50
1.2771.277
316240AF1-291 C
Adder
1.40470588235294121.194
944641AF1-129 C
Adder
66.6117647058823556.62
939192AE1-149 E
Adder
4.6529411764705893.955
944601AF1-125 C
Adder
29.01882352941176524.666
3151801S ANNAS2
50/50
1.0421.042
3150281M RUN A
50/50
5.6655.665
942002AE2-212 E
Adder
0.93647058823529420.796
940431AE2-027 C
Adder
8.392941176470597.134
926615AC1-143 E
50/50
3.8433.843
946262AF1-291 E
Adder
0.93647058823529420.796
3150651CHESTF6
Adder
12.12823529411764610.309
933292AC2-141 E
Adder
8.4282352941176477.164
944602AF1-125 E
Adder
66.4305882352941256.466
939221AE1-153 C
50/50
17.37117.371
316006AB2-029 C
50/50
0.2550.255
3143316POE
Adder
0.88235294117647060.75
316164AC1-076_C
50/50
0.7950.795
939191AE1-149 C
Adder
6.97999999999999955.933
944581AF1-123 C
Adder
29.47294117647058825.052
316415AF1-147_GEN2
Adder
-4.564705882352941-3.88
939222AE1-153 E
50/50
11.58111.581
923892AB2-029 E
50/50
2.5092.509
925022AB2-158 E
50/50
4.7944.794
316044AC1-158 C1
50/50
6.6156.615
944592AF1-124 E
Adder
67.7341176470588257.574
944582AF1-123 E
Adder
67.4905882352941157.367
3150301M RUN C
50/50
5.6625.662
934861AD1-115 C
50/50
3.8163.816
3152261N ANNA2
50/50
28.11228.112
940642AE2-051 E
Adder
7.1458823529411766.074
3150291M RUN B
50/50
5.625.62
940432AE2-027 E
Adder
5.5952941176470594.756
939411AE1-173 C
Adder
56.79058823529411648.272
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.4753.475
CBM South 2LTFEXP_CBM-S2->PJM
CBM
65.85665.856
NYPJM->LTFIMP_NY
CLTF
2.8362.836
LGEELTFEXP_LGEE->PJM
CLTF
1.5711.571
WECLTFEXP_WEC->PJM
CLTF
0.8110.811
G-007PJM->LTFIMP_G-007
CMTX_NF
6.4046.404
SIGELTFEXP_SIGE->PJM
CLTF
0.2880.288
CPLELTFEXP_CPLE->PJM
CLTF
7.2777.277
TVALTFEXP_TVA->PJM
CLTF
5.4825.482
O66PJM->LTFIMP_O-066
CMTX_NF
40.65740.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.67939.679
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.88221.882
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.4114.411
LAGNLTFEXP_LAGN->PJM
CLTF
6.8256.825

Details for 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T539_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T539_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.47 %
Rating:3532.0 MVA
Rating Type:C
MVA to Mitigate:3725.16
MW Contribution:95.27
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150731STONECA
Adder
4.4588235294117653.79
926486AC1-120 E
50/50
4.0644.064
963031AG1-152 C
50/50
8.2178.217
3150211REMNGT1
50/50
5.0075.007
940641AE2-051 C
Adder
10.6976470588235299.093
926004AC1-076_E
50/50
4.5464.546
3150231REMNGT3
50/50
5.6865.686
939412AE1-173 E
Adder
37.7882352941176532.12
3150841SPRUNCB
Adder
5.9694117647058835.074
3150831SPRUNCA
Adder
5.9694117647058835.074
941032AE2-094 E
Adder
10.775294117647069.159
941031AE2-094 C
Adder
24.0576470588235320.449
923862AB2-026 E
Adder
0.80352941176470590.683
3151781S ANNAS1
50/50
1.0411.041
3151791S ANNAG2
50/50
2.0262.026
3151771S ANNAG1
50/50
2.0262.026
316411AF1-147_GEN1
Adder
-4.552941176470588-3.87
944012AF1-069 E
Adder
3.05411764705882362.596
316254AC1-120 C
50/50
7.897.89
316257AC1-043 C
50/50
7.6247.624
316267AC1-143 C
50/50
8.4158.415
926740AC1-158 E2
50/50
17.27317.273
925672AC1-043 E
50/50
12.43912.439
3150221REMNGT2
50/50
5.0545.054
966001AG1-469 C
50/50
1.6441.644
316233AE1-074 C
Adder
1.63647058823529411.391
926739AC1-158 E1
50/50
17.27317.273
3150241REMNGT4
50/50
5.0755.075
966002AG1-469 E
50/50
0.8220.822
944601AF1-125 C
Adder
28.9623529411764724.618
944591AF1-124 C
Adder
29.5225.092
316045AC1-158 C2
50/50
6.6046.604
944011AF1-069 C
Adder
7.8611764705882366.682
316170AC1-121 C
50/50
2.712.71
944641AF1-129 C
Adder
66.4811764705882456.509
316240AF1-291 C
Adder
1.40235294117647061.192
926502AC1-121 E
50/50
1.2751.275
963032AG1-152 E
50/50
12.32512.325
939192AE1-149 E
Adder
4.6435294117647063.947
942001AE2-212 C
Adder
1.40235294117647061.192
316192AB2-158 C
50/50
1.8011.801
958502AF2-144 E
Adder
0.78941176470588240.671
933291AC2-141 C
Adder
19.7047058823529416.749
926755AC1-161 E
Adder
8.4117647058823537.15
938552AE1-074 E
Adder
0.82470588235294120.701
3152251N ANNA1
50/50
28.04928.049
938562AE1-075 E
Adder
0.68470588235294120.582
934862AD1-115 E
50/50
6.2196.219
944581AF1-123 C
Adder
29.4152941176470625.003
940431AE2-027 C
Adder
8.3764705882352957.12
942002AE2-212 E
Adder
0.93411764705882360.794
3150281M RUN A
50/50
5.6625.662
3151801S ANNAS2
50/50
1.0411.041
944602AF1-125 E
Adder
66.3023529411764756.357
933292AC2-141 E
Adder
8.4117647058823537.15
3150651CHESTF6
Adder
12.10470588235294210.289
946262AF1-291 E
Adder
0.93411764705882360.794
926615AC1-143 E
50/50
3.843.84
939191AE1-149 C
Adder
6.9658823529411775.921
316164AC1-076_C
50/50
0.7940.794
3143316POE
Adder
0.880.748
316006AB2-029 C
50/50
0.2540.254
939221AE1-153 C
50/50
17.35917.359
944582AF1-123 E
Adder
67.3588235294117757.255
944592AF1-124 E
Adder
67.6035294117647157.463
316044AC1-158 C1
50/50
6.6046.604
925022AB2-158 E
50/50
4.7874.787
923892AB2-029 E
50/50
2.5082.508
939222AE1-153 E
50/50
11.57311.573
316415AF1-147_GEN2
Adder
-4.552941176470588-3.87
940642AE2-051 E
Adder
7.1317647058823546.062
3152261N ANNA2
50/50
28.06128.061
934861AD1-115 C
50/50
3.8123.812
3150301M RUN C
50/50
5.6595.659
939411AE1-173 C
Adder
56.6811764705882448.179
940432AE2-027 E
Adder
5.5835294117647064.746
3150291M RUN B
50/50
5.6175.617
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.4683.468
CBM South 2LTFEXP_CBM-S2->PJM
CBM
65.72665.726
NYPJM->LTFIMP_NY
CLTF
2.8312.831
LGEELTFEXP_LGEE->PJM
CLTF
1.5681.568
WECLTFEXP_WEC->PJM
CLTF
0.8090.809
G-007PJM->LTFIMP_G-007
CMTX_NF
6.3926.392
SIGELTFEXP_SIGE->PJM
CLTF
0.2870.287
CPLELTFEXP_CPLE->PJM
CLTF
7.2637.263
TVALTFEXP_TVA->PJM
CLTF
5.4715.471
O66PJM->LTFIMP_O-066
CMTX_NF
40.58140.581
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.59339.593
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.83721.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.4014.401
LAGNLTFEXP_LAGN->PJM
CLTF
6.8116.811

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.38 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3586.78
MW Contribution:31.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
927021AC1-189 C
Adder
6.225.287
926071AC1-086 C
Adder
15.98823529411764713.59
946281AF1-292 C
80/20
1.2041.204
964241AG1-285 C
80/20
9.9749.974
962561AG1-105 C
Adder
6.9729411764705885.927
316034AC1-036 C
80/20
0.1860.186
3144293JTRSVLE
80/20
0.3290.329
316044AC1-158 C1
80/20
18.51718.517
316349AD2-085 C
Adder
2.3964705882352942.037
966621AG1-532 C
80/20
1.0911.091
935171AD1-152 C
80/20
1.0991.099
3151021BRUNSWICKG1
80/20
7.5567.556
3151041BRUNSWICKG3
80/20
7.5567.556
934861AD1-115 C
80/20
3.3063.306
3152261N ANNA2
80/20
103.964103.964
942341AE2-247 C
Adder
1.03882352941176470.883
316274AC1-208 C
Adder
6.785.763
962571AG1-106 C
Adder
2.0682352941176471.758
957871AF2-081 C
Adder
7.0094117647058835.958
316405AF2-144 C
80/20
0.2720.272
316365AB2-100 C1
80/20
0.7450.745
957481AF2-042 C
80/20
47.06247.062
3151801S ANNAS2
80/20
1.6761.676
944581AF1-123 C
Adder
32.0470588235294127.24
941101AE2-104 C
Adder
2.35411764705882342.001
933981AD1-022 C
Adder
6.3599999999999995.406
938531AE1-072 C
Adder
12.33529411764705810.485
316238AB2-078 C O1
80/20
0.2590.259
958161AF2-110 C
Adder
0.96117647058823530.817
316237AB2-079 C O1
80/20
0.2590.259
934611AD1-087 C
80/20
1.0661.066
3152431Z1-086 GT3
80/20
9.699.69
316336AC2-165 C
80/20
8.8748.874
940641AE2-051 C
80/20
15.75815.758
3147043LAWRENC
80/20
0.240.24
940481AE2-033 C
80/20
12.91312.913
940541AE2-040 C
80/20
2.2982.298
3152441Z1-086 ST
80/20
16.87216.872
966001AG1-469 C
80/20
2.3822.382
961941AG1-037 C
Adder
0.37294117647058830.317
934321AD1-056 C
Adder
4.7070588235294134.001
934331AD1-057 C
Adder
2.6258823529411772.232
958211AF2-115 C
80/20
1.7961.796
3151531CLOVER1
80/20
10.82910.829
208900BRIS G1
80/20
-2.405-2.405
3151761LOISA E
80/20
6.8276.827
3151771S ANNAG1
80/20
3.2623.262
3151791S ANNAG2
80/20
3.2623.262
3151781S ANNAS1
80/20
1.6761.676
316258AE1-075 C
80/20
0.320.32
941031AE2-094 C
80/20
37.11337.113
957861AF2-080 C
Adder
5.6494117647058824.802
316023AB2-100 C2
80/20
0.7450.745
313527AB2-043 C
80/20
0.4090.409
3152251N ANNA1
80/20
103.92103.92
933291AC2-141 C
Adder
21.0423529411764717.886
934501AD1-074 C
Adder
24.38588235294117720.728
961671AG1-007 C
Adder
0.69647058823529410.592
946301AF1-294 C
80/20
2.9542.954
942461AE2-259 C
80/20
7.9867.986
934621AD1-088 C
80/20
8.2538.253
208901BRIS G2
80/20
-2.846-2.846
316192AB2-158 C
80/20
4.3254.325
942001AE2-212 C
Adder
1.40235294117647061.192
316315AB2-025 C
80/20
0.3250.325
316131AB2-060 C
80/20
1.1781.178
3138533PONTONDP
80/20
0.5320.532
3151541CLOVER2
80/20
10.72710.727
316257AC1-043 C
80/20
6.6126.612
316254AC1-120 C
80/20
8.5918.591
960081AF2-299 C
80/20
1.4551.455
936261AD2-033 C
80/20
10.37510.375
961791AG1-021 C
80/20
1.4371.437
938771AE1-103 C
Adder
2.10235294117647081.787
963041AG1-153 C
80/20
5.1375.137
3151051BRUNSWICKS1
80/20
15.69915.699
316170AC1-121 C
80/20
2.952.95
944011AF1-069 C
80/20
12.12612.126
316045AC1-158 C2
80/20
18.51718.517
944591AF1-124 C
Adder
32.1611764705882427.337
944601AF1-125 C
Adder
31.55411764705882826.821
941591AE2-156 C
Adder
12.43294117647058910.568
3152411Z1-086 GT1
80/20
9.6939.693
3152421Z1-086 GT2
80/20
9.699.69
316233AE1-074 C
80/20
2.0672.067
943461AF1-017 C
Adder
0.94000000000000010.799
316311AC2-079 C
Adder
3.99647058823529383.397
934521AD1-076 C
Adder
8.8564705882352937.528
934511AD1-075 C
Adder
6.0964705882352945.182
316087AB2-174 C
80/20
0.9080.908
959311AF2-222 C
80/20
13.30313.303
937481AD2-202 C
80/20
0.3090.309
3151031BRUNSWICKG2
80/20
7.5567.556
316239AB2-077 C O1
80/20
0.2590.259
964791AG1-342 C
Adder
2.77294117647058872.357
3151731LOISA B
80/20
3.3493.349
3151751LOISA D
80/20
3.3493.349
316313AB2-026 C
80/20
0.3480.348
316164AC1-076_C
80/20
1.0891.089
939191AE1-149 C
Adder
7.2929411764705886.199
3137643SOCKMAN
Adder
0.54588235294117650.464
3151741LOISA C
80/20
3.3493.349
3151721LOISA A
80/20
3.3313.331
939411AE1-173 C
80/20
78.11378.113
316303AF2-085
80/20
3.8763.876
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2194.219
NYPJM->LTFIMP_NY
CLTF
2.292.29
LGEELTFEXP_LGEE->PJM
CLTF
0.8350.835
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165
WECLTFEXP_WEC->PJM
CLTF
0.4130.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.82173.821
CPLELTFEXP_CPLE->PJM
CLTF
8.8538.853
TVALTFEXP_TVA->PJM
CLTF
4.5224.522
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.20919.209
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.12316.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.6672.667
LAGNLTFEXP_LAGN->PJM
CLTF
5.7055.705

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.09 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3577.61
MW Contribution:33.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
927021AC1-189 C
Adder
6.5788235294117645.592
926071AC1-086 C
Adder
16.8929411764705914.359
946281AF1-292 C
80/20
1.2711.271
964241AG1-285 C
80/20
10.44910.449
962561AG1-105 C
Adder
7.3152941176470596.218
316034AC1-036 C
80/20
0.1950.195
3144293JTRSVLE
80/20
0.3440.344
316349AD2-085 C
Adder
2.5505882352941182.168
313506AB1-173 C OP
80/20
0.9150.915
966621AG1-532 C
80/20
1.1511.151
935171AD1-152 C
80/20
1.1531.153
3151021BRUNSWICKG1
80/20
7.9247.924
3151041BRUNSWICKG3
80/20
7.9247.924
3152261N ANNA2
80/20
106.999106.999
942341AE2-247 C
Adder
1.10588235294117650.94
316274AC1-208 C
Adder
7.1635294117647066.089
962571AG1-106 C
Adder
2.1847058823529411.857
3151311EDGECMA
Adder
12.21411764705882410.382
957871AF2-081 C
Adder
7.4588235294117656.34
316405AF2-144 C
80/20
0.2830.283
3150651CHESTF6
Adder
11.5976470588235319.858
316365AB2-100 C1
80/20
0.7870.787
957481AF2-042 C
80/20
49.31549.315
3151801S ANNAS2
80/20
1.5631.563
940431AE2-027 C
Adder
8.3129411764705887.066
944581AF1-123 C
Adder
34.0988235294117728.984
941101AE2-104 C
Adder
2.50470588235294132.129
933981AD1-022 C
Adder
6.7447058823529415.733
938531AE1-072 C
Adder
13.12352941176470511.155
316238AB2-078 C O1
80/20
0.2720.272
958161AF2-110 C
Adder
1.02235294117647070.869
316237AB2-079 C O1
80/20
0.2720.272
934611AD1-087 C
80/20
1.1171.117
3152431Z1-086 GT3
80/20
10.16110.161
316336AC2-165 C
80/20
9.2269.226
940641AE2-051 C
80/20
16.55416.554
316181AB2-040 GEN
80/20
1.0311.031
3147043LAWRENC
80/20
0.2530.253
940481AE2-033 C
80/20
13.63113.631
940541AE2-040 C
80/20
2.4262.426
3152441Z1-086 ST
80/20
17.69217.692
966001AG1-469 C
80/20
1.9821.982
961611AG1-000B C
Adder
10.3129411764705888.766
961941AG1-037 C
Adder
0.39411764705882360.335
934321AD1-056 C
Adder
4.9729411764705894.227
934331AD1-057 C
Adder
2.7741176470588242.358
958211AF2-115 C
80/20
1.8751.875
3151531CLOVER1
80/20
11.34911.349
208900BRIS G1
80/20
-2.414-2.414
3151761LOISA E
80/20
6.316.31
3151771S ANNAG1
80/20
3.0413.041
3151791S ANNAG2
80/20
3.0413.041
3151781S ANNAS1
80/20
1.5631.563
316258AE1-075 C
80/20
0.3330.333
941031AE2-094 C
80/20
38.91138.911
3150831SPRUNCA
Adder
6.1623529411764715.238
3150841SPRUNCB
Adder
6.1623529411764715.238
313527AB2-043 C
80/20
0.4290.429
3152251N ANNA1
80/20
106.954106.954
933291AC2-141 C
Adder
22.41294117647058619.051
934501AD1-074 C
Adder
25.86823529411764621.988
961671AG1-007 C
Adder
0.73647058823529410.626
946301AF1-294 C
80/20
3.0833.083
942461AE2-259 C
Adder
8.3117647058823547.065
934621AD1-088 C
80/20
8.6418.641
208901BRIS G2
80/20
-2.857-2.857
316192AB2-158 C
80/20
4.2764.276
942001AE2-212 C
Adder
1.49882352941176471.274
957861AF2-080 C
Adder
5.9741176470588245.078
316023AB2-100 C2
80/20
0.7870.787
316315AB2-025 C
80/20
0.3440.344
316131AB2-060 C
80/20
1.2351.235
3138533PONTONDP
80/20
0.5550.555
3151541CLOVER2
80/20
11.24311.243
960081AF2-299 C
80/20
1.5351.535
936261AD2-033 C
80/20
10.85610.856
961791AG1-021 C
80/20
1.51.5
938771AE1-103 C
Adder
2.2329411764705881.898
963041AG1-153 C
80/20
5.3875.387
3151051BRUNSWICKS1
80/20
16.46316.463
944011AF1-069 C
80/20
12.71412.714
944591AF1-124 C
Adder
34.2229.087
944601AF1-125 C
Adder
33.5741176470588328.538
941591AE2-156 C
Adder
13.23882352941176611.253
3152411Z1-086 GT1
80/20
10.16410.164
3152421Z1-086 GT2
80/20
10.16110.161
316233AE1-074 C
80/20
2.1822.182
943461AF1-017 C
Adder
1.00.85
316311AC2-079 C
Adder
4.2541176470588233.616
934521AD1-076 C
Adder
9.3952941176470587.986
934511AD1-075 C
Adder
6.46705882352941155.497
316263AC1-034 C
Adder
5.2270588235294114.443
316087AB2-174 C
80/20
0.9580.958
959311AF2-222 C
80/20
13.90913.909
937481AD2-202 C
80/20
0.3240.324
3151031BRUNSWICKG2
80/20
7.9247.924
316240AF1-291 C
Adder
1.37882352941176461.172
944641AF1-129 C
Adder
63.6988235294117654.144
316239AB2-077 C O1
80/20
0.2720.272
964791AG1-342 C
Adder
2.9105882352941182.474
3151731LOISA B
80/20
3.0953.095
3151751LOISA D
80/20
3.0953.095
316313AB2-026 C
80/20
0.3630.363
939191AE1-149 C
Adder
7.7752941176470596.609
3137643SOCKMAN
Adder
0.57647058823529410.49
3151741LOISA C
80/20
3.0953.095
3151721LOISA A
80/20
3.0793.079
939411AE1-173 C
80/20
82.26382.263
316303AF2-085
80/20
4.064.06
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4574.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
78.26878.268
NYPJM->LTFIMP_NY
CLTF
2.2912.291
LGEELTFEXP_LGEE->PJM
CLTF
0.9480.948
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
SIGELTFEXP_SIGE->PJM
CLTF
0.1860.186
CPLELTFEXP_CPLE->PJM
CLTF
9.3529.352
TVALTFEXP_TVA->PJM
CLTF
4.8954.895
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.24822.248
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.65817.658
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.9882.988
LAGNLTFEXP_LAGN->PJM
CLTF
6.1746.174

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.41 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4350.17
MW Contribution:109.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
927021AC1-189 C
Adder
6.5247058823529425.546
926071AC1-086 C
Adder
16.77411764705882314.258
924152AB2-059 E OP
Adder
4.122352941176473.504
946281AF1-292 C
Adder
1.26235294117647071.073
960082AF2-299 E
Adder
1.01647058823529420.864
916042Z1-036 E
Adder
21.48117647058823518.259
923832AB2-022 E
Adder
0.92235294117647060.784
964241AG1-285 C
Adder
10.3776470588235298.821
962561AG1-105 C
Adder
7.2635294117647076.174
958212AF2-115 E
Adder
1.58588235294117651.348
938772AE1-103 E
Adder
3.0611764705882352.602
963042AG1-153 E
Adder
8.0388235294117656.833
925022AB2-158 E
50/50
11.37311.373
316044AC1-158 C1
50/50
19.56819.568
944592AF1-124 E
Adder
77.8317647058823566.157
944582AF1-123 E
Adder
77.5517647058823565.919
918512AA1-065 E OP
Adder
4.2588235294117653.62
918532AA1-067 E
Adder
0.55176470588235290.469
934502AD1-074 E
Adder
13.07176470588235311.111
934512AD1-075 E
Adder
3.26823529411764732.778
924516AB2-100 E1
Adder
2.36470588235294082.01
966621AG1-532 C
Adder
1.1435294117647060.972
919153AA1-139 E2
Adder
3.02941176470588272.575
924022AB2-043 E O1
Adder
4.2929411764705883.649
3147223TWITTYS
Adder
0.78941176470588240.671
959312AF2-222 E
Adder
9.2564705882352957.868
3152261N ANNA2
50/50
106.886106.886
940642AE2-051 E
50/50
10.98110.981
943172AE2-346 E
Adder
0.46941176470588240.399
917332KELFORD E
Adder
1.281.088
925122AB2-169 E
Adder
4.4105882352941183.749
934522AD1-076 E
Adder
4.7541176470588244.041
940492AE2-034 E
Adder
2.3364705882352941.986
316274AC1-208 C
Adder
7.1094117647058826.043
962571AG1-106 C
Adder
2.16941176470588241.844
917342Z2-044 E
Adder
0.46823529411764710.398
3151311EDGECMA
Adder
12.11411764705882510.297
918492AA1-063AE OP
Adder
3.22705882352941182.743
957871AF2-081 C
Adder
7.4070588235294126.296
961792AG1-021 E
Adder
1.26941176470588221.079
937482AD2-202 E
Adder
0.94117647058823540.8
3145506HICKORY
Adder
1.61411764705882371.372
933292AC2-141 E
Adder
9.502352941176478.077
316141AB2-099 E
Adder
0.195294117647058840.166
961672AG1-007 E
Adder
0.414117647058823530.352
923994AB2-040_E
Adder
4.9741176470588234.228
316088AB2-174 E
Adder
5.2858823529411774.493
933981AD1-022 C
Adder
6.6952941176470595.691
900672V4-068 E
Adder
0.276470588235294130.235
938531AE1-072 C
Adder
13.03294117647058811.078
924302AB2-077 E O1
Adder
1.10588235294117650.94
3145393UNCAMP
Adder
4.622352941176473.929
932046AC2-012 E
Adder
9.6164705882352938.174
958161AF2-110 C
Adder
1.0152941176470590.863
933982AD1-022 E
Adder
3.6447058823529413.098
3145946PLYMOUTH TP
Adder
0.245882352941176470.209
927146AC1-208 E
Adder
3.1564705882352942.683
927255AC1-221 E
Adder
2.9588235294117652.515
934612AD1-087 E
Adder
3.2152941176470592.733
934622AD1-088 E
Adder
4.1364705882352943.516
316336AC2-165 C
Adder
9.177647058823537.801
940641AE2-051 C
50/50
16.47216.472
316084AB2-161 E
Adder
4.0141176470588233.412
923263AB1-132 E OP
Adder
4.8811764705882354.149
961942AG1-037 E
Adder
0.26117647058823530.222
961941AG1-037 C
Adder
0.391764705882352960.333
927022AC1-189 E
Adder
3.25058823529411762.763
934322AD1-056 E
Adder
2.6764705882352942.275
934332AD1-057 E
Adder
1.43411764705882371.219
934321AD1-056 C
Adder
4.9352941176470594.195
934331AD1-057 C
Adder
2.75294117647058822.34
925595AC1-034 E
Adder
3.91058823529411773.324
923852AB2-025 E
Adder
0.97529411764705880.829
936262AD2-033 E
Adder
7.1882352941176476.11
958211AF2-115 C
Adder
1.86235294117647051.583
208900BRIS G1
50/50
-2.489-2.489
3151761LOISA E
50/50
6.3326.332
3151771S ANNAG1
50/50
3.0513.051
3151791S ANNAG2
50/50
3.0513.051
3151781S ANNAS1
50/50
1.5681.568
923862AB2-026 E
Adder
1.17294117647058820.997
941031AE2-094 C
50/50
38.72138.721
941032AE2-094 E
50/50
17.34217.342
3150831SPRUNCA
Adder
6.117647058823535.2
3150841SPRUNCB
Adder
6.117647058823535.2
939412AE1-173 E
Adder
54.5505882352941246.368
926662AC1-147 E
Adder
0.97176470588235290.826
916192Z1-068 E
Adder
1.38588235294117631.178
957492AF2-043 E
Adder
1.05294117647058830.895
957861AF2-080 C
Adder
5.9270588235294125.038
917512Z2-088 E OP1
Adder
3.8047058823529413.234
946282AF1-292 E
Adder
0.84117647058823530.715
3138533PONTONDP
Adder
0.55176470588235290.469
944012AF1-069 E
50/50
4.9154.915
926214AC1-099 E
Adder
0.94705882352941180.805
932632AC2-084 E
Adder
2.53411764705882362.154
962572AG1-106 E
Adder
0.94941176470588240.807
957872AF2-081 E
Adder
3.17411764705882372.698
924162AB2-060 E OP
Adder
3.54470588235294143.013
964242AG1-285 E
Adder
6.9188235294117655.881
964792AG1-342 E
Adder
1.92588235294117661.637
932763AC2-100 E
Adder
2.00588235294117641.705
938562AE1-075 E
Adder
1.00.85
3152251N ANNA1
50/50
106.841106.841
938552AE1-074 E
Adder
1.09294117647058830.929
926755AC1-161 E
Adder
9.502352941176478.077
933291AC2-141 C
Adder
22.2618.921
934501AD1-074 C
Adder
25.6821.828
961671AG1-007 C
Adder
0.73058823529411760.621
957862AF2-080 E
Adder
2.6270588235294122.233
926072AC1-086 E
Adder
7.6341176470588236.489
960081AF2-299 C
Adder
1.52470588235294141.296
3145413WATKINS
Adder
0.52941176470588240.45
936261AD2-033 C
Adder
10.782352941176479.165
962562AG1-105 E
Adder
4.842352941176474.116
961791AG1-021 C
Adder
1.48941176470588241.266
940481AE2-033 C
Adder
13.54823529411764811.516
940482AE2-033 E
Adder
9.1341176470588247.764
940541AE2-040 C
Adder
2.4117647058823532.05
924312AB2-078 E O1
Adder
1.10588235294117650.94
925612AC1-036 E
Adder
0.7117647058823530.605
926274AC1-105 E
Adder
2.1788235294117651.852
966001AG1-469 C
50/50
2.0062.006
926740AC1-158 E2
50/50
51.18251.182
938771AE1-103 C
Adder
2.21764705882352951.885
920692AA2-178 E
Adder
3.1141176470588232.647
922923AB1-081 E OP
Adder
2.9105882352941182.474
966622AG1-532 E
Adder
0.76235294117647070.648
917122Z2-027 E
Adder
1.00.85
3146326AYDLETT TAP
Adder
1.00588235294117640.855
938532AE1-072 E
Adder
6.7941176470588245.775
927264AC1-222 E
Adder
3.20470588235294152.724
3147133PAMPLIN
Adder
0.82352941176470580.7
966002AG1-469 E
50/50
1.0031.003
926739AC1-158 E1
50/50
51.18251.182
316233AE1-074 C
Adder
2.17058823529411751.845
943461AF1-017 C
Adder
0.99294117647058820.844
316311AC2-079 C
Adder
4.2247058823529413.591
932596AC2-079 E
Adder
6.8929411764705895.859
924517AB2-100 E2
Adder
2.36470588235294082.01
937226AE2-253 E
Adder
4.3282352941176473.679
946301AF1-294 C
Adder
3.06235294117647072.603
935172AD1-152 E
Adder
4.7270588235294114.018
942461AE2-259 C
Adder
8.257647058823537.019
934621AD1-088 C
Adder
8.5905882352941177.302
957482AF2-042 E
Adder
32.6894117647058927.786
208901BRIS G2
50/50
-2.946-2.946
958502AF2-144 E
Adder
1.15294117647058810.98
316192AB2-158 C
50/50
4.2784.278
942001AE2-212 C
Adder
1.48705882352941181.264
924032AB2-045 E
Adder
1.08588235294117650.923
963041AG1-153 C
Adder
5.3588235294117644.555
944011AF1-069 C
50/50
12.65212.652
316045AC1-158 C2
50/50
19.56819.568
944591AF1-124 C
Adder
33.9870588235294128.889
944601AF1-125 C
Adder
33.3447058823529428.343
941591AE2-156 C
Adder
13.14823529411764711.176
936666AD2-085 E
Adder
4.1329411764705883.513
934521AD1-076 C
Adder
9.3258823529411777.927
934511AD1-075 C
Adder
6.425.457
919692AA2-053 E OP
Adder
3.36117647058823542.857
316263AC1-034 C
Adder
5.1835294117647064.406
923573AB1-173 E OP
Adder
2.6529411764705882.255
3145723EMPORIA
Adder
0.350588235294117640.298
920042AA2-088 E OP
Adder
8.226.987
925785AC1-054 E
Adder
2.79764705882352962.378
919152AA1-139 E1
Adder
3.02941176470588272.575
959311AF2-222 C
Adder
13.8152941176470611.743
942342AE2-247 E
Adder
1.5164705882352941.289
939192AE1-149 E
Adder
5.1470588235294124.375
939312AE1-162 E
Adder
0.97647058823529410.83
934065AD1-033 E
Adder
3.70941176470588243.153
925522AC1-027 E
Adder
0.89764705882352950.763
941102AE2-104 E
Adder
3.9541176470588243.361
3145256KINGFORK
Adder
0.72352941176470590.615
924322AB2-079 E O1
Adder
1.10588235294117650.94
943902AF1-058 E
Adder
1.04352941176470580.887
946302AF1-294 E
Adder
2.59294117647058852.204
957481AF2-042 C
Adder
49.0341176470588341.679
3151801S ANNAS2
50/50
1.5681.568
942002AE2-212 E
Adder
0.99176470588235290.843
944581AF1-123 C
Adder
33.8670588235294128.787
941101AE2-104 C
Adder
2.48705882352941152.114
934576AD1-082 E
Adder
3.19882352941176462.719
944602AF1-125 E
Adder
76.3341176470588364.884
943612AF1-032 E
Adder
0.68470588235294120.582
926206AC1-098 E
Adder
2.86705882352941142.437
964791AG1-342 C
Adder
2.88941176470588262.456
901082W1-029 E
Adder
23.76705882352941420.202
942462AE2-259 E
Adder
5.5047058823529414.679
3151731LOISA B
50/50
3.1063.106
3151751LOISA D
50/50
3.1063.106
3143316POE
Adder
1.04235294117647070.886
939191AE1-149 C
Adder
7.7200000000000016.562
919710AA2-057 E
Adder
3.1117647058823532.645
3137643SOCKMAN
Adder
0.57294117647058830.487
913392Y1-086 E
Adder
1.63411764705882371.389
933502AC2-165 E
Adder
6.9070588235294135.871
3151741LOISA C
50/50
3.1063.106
3151721LOISA A
50/50
3.093.09
939411AE1-173 C
Adder
81.8247058823529469.551
316349AD2-085 C
Adder
2.53294117647058852.153
935112AD1-144 E
Adder
0.67176470588235290.571
942341AE2-247 C
Adder
1.09764705882352940.933
943462AF1-017 E
Adder
1.621.377
958162AF2-110 E
Adder
1.61411764705882371.372
316303AF2-085
50/50
4.0434.043
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4084.408
CBM South 2LTFEXP_CBM-S2->PJM
CBM
77.11777.117
NYPJM->LTFIMP_NY
CLTF
2.3732.373
LGEELTFEXP_LGEE->PJM
CLTF
0.8720.872
WECLTFEXP_WEC->PJM
CLTF
0.4310.431
G-007PJM->LTFIMP_G-007
CMTX_NF
5.0575.057
SIGELTFEXP_SIGE->PJM
CLTF
0.1730.173
CPLELTFEXP_CPLE->PJM
CLTF
9.2519.251
TVALTFEXP_TVA->PJM
CLTF
4.7224.722
O66PJM->LTFIMP_O-066
CMTX_NF
32.20632.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.05120.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.83616.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7842.784
LAGNLTFEXP_LAGN->PJM
CLTF
5.9595.959

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.75 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4205.81
MW Contribution:104.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
920692AA2-178 E
Adder
2.9635294117647062.519
966622AG1-532 E
Adder
0.72941176470588230.62
917122Z2-027 E
Adder
0.94941176470588240.807
3146326AYDLETT TAP
Adder
0.95411764705882360.811
938532AE1-072 E
Adder
6.4470588235294135.48
927264AC1-222 E
Adder
3.0847058823529412.622
3147133PAMPLIN
Adder
0.79882352941176480.679
966002AG1-469 E
50/50
1.231.23
926739AC1-158 E1
50/50
48.49548.495
316233AE1-074 C
Adder
2.07294117647058851.762
943461AF1-017 C
Adder
0.94235294117647060.801
316311AC2-079 C
Adder
4.00705882352941253.406
932596AC2-079 E
Adder
6.5388235294117655.558
961942AG1-037 E
Adder
0.249411764705882360.212
961941AG1-037 C
Adder
0.37294117647058830.317
927022AC1-189 E
Adder
3.10588235294117652.64
934322AD1-056 E
Adder
2.562.176
934332AD1-057 E
Adder
1.37058823529411771.165
934321AD1-056 C
Adder
4.7188235294117654.011
934331AD1-057 C
Adder
2.6329411764705882.238
923852AB2-025 E
Adder
0.9317647058823530.792
936262AD2-033 E
Adder
6.9435294117647075.902
958211AF2-115 C
Adder
1.80470588235294121.534
208900BRIS G1
50/50
-2.42-2.42
3151761LOISA E
50/50
7.047.04
3151771S ANNAG1
50/50
3.3573.357
3151791S ANNAG2
50/50
3.3573.357
3151781S ANNAS1
50/50
1.7251.725
923862AB2-026 E
Adder
1.13764705882352950.967
941031AE2-094 C
50/50
37.19337.193
941032AE2-094 E
50/50
16.65816.658
939412AE1-173 E
Adder
52.19411764705882544.365
926662AC1-147 E
Adder
0.92117647058823540.783
916192Z1-068 E
Adder
1.31411764705882361.117
957492AF2-043 E
Adder
0.99882352941176470.849
926214AC1-099 E
Adder
0.90470588235294120.769
932632AC2-084 E
Adder
2.4211764705882352.058
962572AG1-106 E
Adder
0.90705882352941180.771
957872AF2-081 E
Adder
3.0117647058823532.56
924162AB2-060 E OP
Adder
3.4164705882352942.904
964242AG1-285 E
Adder
6.6741176470588245.673
964792AG1-342 E
Adder
1.85529411764705881.577
932763AC2-100 E
Adder
1.9282352941176471.639
957862AF2-080 E
Adder
2.5105882352941182.134
926072AC1-086 E
Adder
7.29529411764705856.201
960081AF2-299 C
Adder
1.45882352941176461.24
3145413WATKINS
Adder
0.50352941176470590.428
936261AD2-033 C
Adder
10.415294117647068.853
962562AG1-105 E
Adder
4.6635294117647063.964
961791AG1-021 C
Adder
1.4435294117647061.227
938771AE1-103 C
Adder
2.1082352941176471.792
924032AB2-045 E
Adder
1.06588235294117650.906
963041AG1-153 C
Adder
5.1482352941176474.376
316170AC1-121 C
50/50
3.0753.075
944011AF1-069 C
50/50
12.15212.152
316045AC1-158 C2
50/50
18.54118.541
944591AF1-124 C
Adder
32.24705882352941427.41
944601AF1-125 C
Adder
31.6376470588235326.892
941591AE2-156 C
Adder
12.46588235294117710.596
936666AD2-085 E
Adder
3.923.332
316141AB2-099 E
Adder
0.187058823529411780.159
923994AB2-040_E
Adder
4.7588235294117654.045
316088AB2-174 E
Adder
5.0564705882352944.298
924322AB2-079 E O1
Adder
1.06588235294117650.906
943902AF1-058 E
Adder
1.00470588235294110.854
946302AF1-294 E
Adder
2.51294117647058852.136
943172AE2-346 E
Adder
0.448235294117647070.381
917332KELFORD E
Adder
1.22235294117647041.039
925122AB2-169 E
Adder
4.2058823529411773.575
934522AD1-076 E
Adder
4.5258823529411773.847
940492AE2-034 E
Adder
2.2223529411764711.889
316274AC1-208 C
Adder
6.7976470588235295.778
962571AG1-106 C
Adder
2.07294117647058851.762
917342Z2-044 E
Adder
0.448235294117647070.381
918492AA1-063AE OP
Adder
3.08235294117647072.62
957871AF2-081 C
Adder
7.0282352941176475.974
961792AG1-021 E
Adder
1.22941176470588221.045
937482AD2-202 E
Adder
0.90588235294117650.77
3145506HICKORY
Adder
1.53058823529411761.301
933292AC2-141 E
Adder
9.0070588235294127.656
934576AD1-082 E
Adder
3.0317647058823532.577
944602AF1-125 E
Adder
72.4247058823529461.561
943612AF1-032 E
Adder
0.64941176470588250.552
926206AC1-098 E
Adder
2.742.329
964791AG1-342 C
Adder
2.7823529411764712.365
901082W1-029 E
Adder
22.56941176470588319.184
942462AE2-259 E
Adder
5.3529411764705884.55
3151731LOISA B
50/50
3.4533.453
3151751LOISA D
50/50
3.4533.453
3143316POE
Adder
0.99058823529411770.842
316164AC1-076_C
50/50
1.1111.111
939191AE1-149 C
Adder
7.3129411764705896.216
923263AB1-132 E OP
Adder
4.66470588235294153.965
940481AE2-033 C
Adder
12.94470588235294211.003
940482AE2-033 E
Adder
8.7270588235294117.418
940541AE2-040 C
Adder
2.3035294117647061.958
924312AB2-078 E O1
Adder
1.06588235294117650.906
925612AC1-036 E
Adder
0.68823529411764710.585
926274AC1-105 E
Adder
2.09764705882352941.783
966001AG1-469 C
50/50
2.4612.461
925672AC1-043 E
50/50
11.48611.486
926740AC1-158 E2
50/50
48.49548.495
933982AD1-022 E
Adder
3.47058823529411782.95
3145946PLYMOUTH TP
Adder
0.234117647058823540.199
927146AC1-208 E
Adder
3.01882352941176452.566
927255AC1-221 E
Adder
2.84470588235294162.418
934612AD1-087 E
Adder
3.09529411764705882.631
934622AD1-088 E
Adder
3.98588235294117643.388
316336AC2-165 C
Adder
8.9188235294117667.581
926004AC1-076_E
50/50
6.3656.365
940641AE2-051 C
50/50
15.79315.793
316084AB2-161 E
Adder
3.8047058823529413.234
934862AD1-115 E
50/50
5.7435.743
938562AE1-075 E
Adder
0.96941176470588230.824
3152251N ANNA1
50/50
104.031104.031
938552AE1-074 E
Adder
1.04470588235294120.888
926755AC1-161 E
Adder
9.0070588235294127.656
933291AC2-141 C
Adder
21.09882352941176717.934
925522AC1-027 E
Adder
0.85058823529411760.723
941102AE2-104 E
Adder
3.75294117647058823.19
3145256KINGFORK
Adder
0.68588235294117650.583
934521AD1-076 C
Adder
8.8788235294117657.547
934511AD1-075 C
Adder
6.1117647058823535.195
919692AA2-053 E OP
Adder
3.2129411764705882.731
923573AB1-173 E OP
Adder
2.53764705882352942.157
3145723EMPORIA
Adder
0.33529411764705880.285
920042AA2-088 E OP
Adder
7.8352941176470596.66
925785AC1-054 E
Adder
2.6835294117647062.281
919152AA1-139 E1
Adder
2.8741176470588242.443
959311AF2-222 C
Adder
13.3576470588235311.354
926502AC1-121 E
50/50
1.4471.447
942342AE2-247 E
Adder
1.43764705882352951.222
957861AF2-080 C
Adder
5.6635294117647064.814
946282AF1-292 E
Adder
0.80470588235294130.684
3138533PONTONDP
Adder
0.53411764705882360.454
316257AC1-043 C
50/50
7.047.04
316254AC1-120 C
50/50
8.9538.953
944012AF1-069 E
50/50
4.7214.721
934501AD1-074 C
Adder
24.44941176470588220.782
924517AB2-100 E2
Adder
2.26000000000000021.921
937226AE2-253 E
Adder
4.1070588235294123.491
946301AF1-294 C
Adder
2.96705882352941152.522
935172AD1-152 E
Adder
4.5494117647058833.867
942461AE2-259 C
Adder
8.0294117647058826.825
934621AD1-088 C
Adder
8.277647058823537.036
957482AF2-042 E
Adder
31.4626.741
208901BRIS G2
50/50
-2.864-2.864
958502AF2-144 E
Adder
1.11764705882352940.95
316192AB2-158 C
50/50
4.384.38
942001AE2-212 C
Adder
1.40588235294117661.195
939192AE1-149 E
Adder
4.87529411764705944.144
934065AD1-033 E
Adder
3.5188235294117652.991
927021AC1-189 C
Adder
6.2352941176470595.3
926071AC1-086 C
Adder
16.0282352941176513.624
946281AF1-292 C
Adder
1.2082352941176471.027
960082AF2-299 E
Adder
0.97294117647058820.827
916042Z1-036 E
Adder
20.41647058823529517.354
923832AB2-022 E
Adder
0.87529411764705890.744
964241AG1-285 C
Adder
10.0105882352941198.509
962561AG1-105 C
Adder
6.9952941176470595.946
958212AF2-115 E
Adder
1.53764705882352941.307
938772AE1-103 E
Adder
2.91176470588235332.475
963042AG1-153 E
Adder
7.7235294117647076.565
925022AB2-158 E
50/50
11.64111.641
316044AC1-158 C1
50/50
18.54118.541
944592AF1-124 E
Adder
73.8458823529411762.769
944582AF1-123 E
Adder
73.5862.543
316349AD2-085 C
Adder
2.40235294117647062.042
935112AD1-144 E
Adder
0.63647058823529420.541
919710AA2-057 E
Adder
2.97647058823529382.53
3137643SOCKMAN
Adder
0.54705882352941180.465
913392Y1-086 E
Adder
1.5517647058823531.319
933502AC2-165 E
Adder
6.7129411764705895.706
3151741LOISA C
50/50
3.4533.453
3151721LOISA A
50/50
3.4353.435
939411AE1-173 C
Adder
78.2905882352941166.547
933981AD1-022 C
Adder
6.3764705882352955.42
900672V4-068 E
Adder
0.26352941176470590.224
938531AE1-072 C
Adder
12.36823529411764810.513
924302AB2-077 E O1
Adder
1.06588235294117650.906
3145393UNCAMP
Adder
4.3976470588235293.738
926486AC1-120 E
50/50
4.6124.612
932046AC2-012 E
Adder
9.1176470588235297.75
958161AF2-110 C
Adder
0.96352941176470590.819
957481AF2-042 C
Adder
47.1905882352941240.112
3151801S ANNAS2
50/50
1.7251.725
942002AE2-212 E
Adder
0.93764705882352950.797
944581AF1-123 C
Adder
32.1329411764705927.313
941101AE2-104 C
Adder
2.362.006
918512AA1-065 E OP
Adder
4.06000000000000053.451
918532AA1-067 E
Adder
0.52705882352941180.448
934502AD1-074 E
Adder
12.44588235294117810.579
934512AD1-075 E
Adder
3.1117647058823532.645
924516AB2-100 E1
Adder
2.26000000000000021.921
966621AG1-532 C
Adder
1.09411764705882360.93
919153AA1-139 E2
Adder
2.8741176470588242.443
924022AB2-043 E O1
Adder
4.1364705882352943.516
3147223TWITTYS
Adder
0.76235294117647070.648
959312AF2-222 E
Adder
8.9494117647058827.607
934861AD1-115 C
50/50
3.523.52
3152261N ANNA2
50/50
104.075104.075
940642AE2-051 E
50/50
10.52910.529
942341AE2-247 C
Adder
1.04117647058823540.885
943462AF1-017 E
Adder
1.53764705882352941.307
958162AF2-110 E
Adder
1.53176470588235311.302
316303AF2-085
50/50
3.8863.886
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2284.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.97573.975
NYPJM->LTFIMP_NY
CLTF
2.3072.307
LGEELTFEXP_LGEE->PJM
CLTF
0.8310.831
G-007PJM->LTFIMP_G-007
CMTX_NF
4.9174.917
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165
WECLTFEXP_WEC->PJM
CLTF
0.410.41
CPLELTFEXP_CPLE->PJM
CLTF
8.8738.873
TVALTFEXP_TVA->PJM
CLTF
4.5234.523
O66PJM->LTFIMP_O-066
CMTX_NF
31.31531.315
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.05119.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.10316.103
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.6562.656
LAGNLTFEXP_LAGN->PJM
CLTF
5.7065.706

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.97 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3767.03
MW Contribution:40.27
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
927021AC1-189 C
Adder
7.4435294117647066.327
926071AC1-086 C
Adder
19.07647058823529616.215
946281AF1-292 C
80/20
1.4231.423
964241AG1-285 C
Adder
11.3035294117647079.608
962561AG1-105 C
Adder
7.9117647058823526.725
3151091ELIZAR2
80/20
2.8012.801
316349AD2-085 C
80/20
3.0713.071
313506AB1-173 C OP
80/20
1.0281.028
966621AG1-532 C
80/20
1.2891.289
316320Y1-086 C
80/20
0.1960.196
316388AE2-253 GEN
80/20
1.7531.753
935171AD1-152 C
80/20
1.2331.233
3151021BRUNSWICKG1
80/20
8.3898.389
3151041BRUNSWICKG3
80/20
8.3898.389
3152261N ANNA2
80/20
92.75992.759
942341AE2-247 C
80/20
1.3311.331
316246AF1-032 C
80/20
0.2540.254
316274AC1-208 C
Adder
8.077647058823536.866
962571AG1-106 C
Adder
2.4670588235294122.097
3151311EDGECMA
Adder
13.67647058823529511.625
957871AF2-081 C
80/20
8.9458.945
316405AF2-144 C
80/20
0.30.3
3150651CHESTF6
Adder
15.16470588235294212.89
3150861SPRUNCD
80/20
0.140.14
316365AB2-100 C1
80/20
0.8850.885
957481AF2-042 C
80/20
52.44752.447
3151801S ANNAS2
80/20
1.2181.218
940431AE2-027 C
Adder
10.6976470588235299.093
316294AC1-161 C
80/20
4.4154.415
944581AF1-123 C
80/20
40.90340.903
316185AD1-033 C
80/20
1.0971.097
916191Z1-068 C
80/20
0.0390.039
941101AE2-104 C
80/20
3.0013.001
933981AD1-022 C
Adder
7.84941176470588256.672
938531AE1-072 C
80/20
15.7315.73
3150731STONECA
Adder
5.4352941176470594.62
935161AD1-151 C
Adder
13.03882352941176511.083
316083AB2-161 C
80/20
0.4890.489
958161AF2-110 C
80/20
1.2251.225
313526AB2-022 C
80/20
0.3360.336
316017AA1-139 ULT1
80/20
0.9650.965
934611AD1-087 C
80/20
1.1911.191
3152431Z1-086 GT3
80/20
10.7510.75
316336AC2-165 C
80/20
9.7879.787
940641AE2-051 C
80/20
17.817.8
316181AB2-040 GEN
80/20
1.1581.158
3147043LAWRENC
80/20
0.2810.281
940481AE2-033 C
80/20
15.30215.302
940541AE2-040 C
80/20
2.7232.723
3152441Z1-086 ST
80/20
18.71718.717
966001AG1-469 C
Adder
1.43764705882352951.222
961611AG1-000B C
Adder
13.19882352941176511.219
316375AC2-012 C
80/20
1.2021.202
316072AD1-144 C
80/20
0.2460.246
961941AG1-037 C
Adder
0.454117647058823570.386
934321AD1-056 C
Adder
5.5882352941176484.75
934331AD1-057 C
Adder
3.11764705882352942.65
958211AF2-115 C
Adder
2.0152941176470591.713
3151531CLOVER1
80/20
12.09912.099
208900BRIS G1
80/20
-2.561-2.561
3151761LOISA E
80/20
4.8664.866
3151771S ANNAG1
80/20
2.372.37
3151791S ANNAG2
80/20
2.372.37
3151781S ANNAS1
80/20
1.2181.218
316258AE1-075 C
80/20
0.3530.353
941031AE2-094 C
80/20
41.10641.106
3150831SPRUNCA
Adder
7.7905882352941186.622
3150841SPRUNCB
Adder
7.7905882352941186.622
3151081ELIZAR1
80/20
2.8512.851
957861AF2-080 C
Adder
6.7600000000000015.746
316023AB2-100 C2
80/20
0.8850.885
316315AB2-025 C
80/20
0.3860.386
3138533PONTONDP
Adder
0.59764705882352940.508
3151541CLOVER2
80/20
11.98611.986
316316AC1-027 C
80/20
0.2820.282
316018AA1-139 ULT2
80/20
0.9650.965
3152251N ANNA1
80/20
92.7292.72
3150851SPRUNCC
80/20
0.140.14
944631AF1-128 C
Adder
28.33882352941176624.088
933291AC2-141 C
80/20
27.11427.114
3150921YORKTN3
Adder
92.4352941176470578.57
934501AD1-074 C
Adder
30.18352941176470625.656
961671AG1-007 C
Adder
0.82941176470588230.705
946301AF1-294 C
Adder
3.3141176470588242.817
942461AE2-259 C
Adder
8.8929411764705887.559
934621AD1-088 C
80/20
9.29.2
208901BRIS G2
80/20
-3.03-3.03
316192AB2-158 C
80/20
3.5593.559
942001AE2-212 C
Adder
1.8635294117647061.584
960081AF2-299 C
80/20
1.7191.719
936261AD2-033 C
Adder
11.7211764705882359.963
961791AG1-021 C
Adder
1.61176470588235321.37
938771AE1-103 C
80/20
2.6332.633
963041AG1-153 C
80/20
5.7035.703
3151051BRUNSWICKS1
80/20
17.42917.429
944011AF1-069 C
80/20
13.43113.431
3150601CHESTF5
Adder
45.29058823529411638.497
944591AF1-124 C
80/20
41.04941.049
944601AF1-125 C
80/20
40.27340.273
3151101ELIZAR3
80/20
2.8872.887
941591AE2-156 C
80/20
15.98415.984
3156056W1-029WIND
80/20
0.6930.693
3152411Z1-086 GT1
80/20
10.75310.753
3152421Z1-086 GT2
80/20
10.7510.75
316233AE1-074 C
80/20
2.4792.479
943461AF1-017 C
80/20
1.2041.204
316311AC2-079 C
80/20
5.125.12
934521AD1-076 C
Adder
10.9623529411764719.318
934511AD1-075 C
Adder
7.54588235294117656.414
316263AC1-034 C
Adder
5.8505882352941184.973
316087AB2-174 C
80/20
1.0751.075
316321Z2-027 C
80/20
0.3250.325
959311AF2-222 C
Adder
14.9976470588235312.748
937481AD2-202 C
80/20
0.3460.346
3151031BRUNSWICKG2
80/20
8.3898.389
316240AF1-291 C
Adder
1.78117647058823541.514
944641AF1-129 C
Adder
83.2882352941176570.795
316036AC1-147 C
80/20
0.3280.328
316305AF2-043 C
80/20
0.3110.311
964791AG1-342 C
Adder
3.14588235294117662.674
3151731LOISA B
80/20
2.3872.387
3151751LOISA D
80/20
2.3872.387
316313AB2-026 C
80/20
0.3850.385
939191AE1-149 C
80/20
9.4869.486
3150981CHESPKA
80/20
0.3880.388
3137643SOCKMAN
Adder
0.64823529411764710.551
3151741LOISA C
80/20
2.3872.387
3151721LOISA A
80/20
2.3742.374
939411AE1-173 C
80/20
90.4790.47
316381AD1-082 C
80/20
1.1161.116
3150991CHESPKB
80/20
0.6430.643
316303AF2-085
80/20
4.3034.303
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.8954.895
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.42786.427
NYPJM->LTFIMP_NY
CLTF
2.4542.454
LGEELTFEXP_LGEE->PJM
CLTF
1.0841.084
WECLTFEXP_WEC->PJM
CLTF
0.5370.537
SIGELTFEXP_SIGE->PJM
CLTF
0.2110.211
CPLELTFEXP_CPLE->PJM
CLTF
10.2710.27
TVALTFEXP_TVA->PJM
CLTF
5.5015.501
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.18225.182
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.8619.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.3753.375
LAGNLTFEXP_LAGN->PJM
CLTF
6.9186.918

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.22 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3678.49
MW Contribution:50.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
927021AC1-189 C
Adder
8.6023529411764727.312
926071AC1-086 C
Adder
21.9611764705882418.667
946281AF1-292 C
Adder
1.61647058823529431.374
964241AG1-285 C
Adder
12.1610.336
962561AG1-105 C
Adder
8.5058823529411767.23
939261AE1-157 C
Adder
14.10235294117647211.987
316169AC1-164 GEN
Adder
43.66588235294117537.116
3151091ELIZAR2
80/20
3.5383.538
316349AD2-085 C
Adder
3.87058823529411773.29
966621AG1-532 C
Adder
1.46470588235294131.245
934861AD1-115 C
Adder
-3.06-2.601
3152261N ANNA2
80/20
56.72156.721
3150771HOPHCF1
80/20
2.7332.733
942341AE2-247 C
Adder
1.67764705882352931.426
316274AC1-208 C
Adder
9.2835294117647067.891
962571AG1-106 C
Adder
2.84117647058823542.415
3151311EDGECMA
Adder
15.55647058823529613.223
957871AF2-081 C
Adder
11.2117647058823529.53
3150651CHESTF6
80/20
21.09121.091
3150861SPRUNCD
80/20
0.1870.187
936591AD2-074 C
Adder
5.8552941176470594.977
957481AF2-042 C
Adder
54.6470588235294146.45
940431AE2-027 C
80/20
14.61614.616
316294AC1-161 C
80/20
5.5975.597
944581AF1-123 C
80/20
51.27751.277
941101AE2-104 C
Adder
3.75764705882352963.194
933981AD1-022 C
Adder
9.4470588235294128.03
938531AE1-072 C
Adder
19.70000000000000316.745
3142366NRTHEST
80/20
0.2040.204
3150731STONECA
80/20
7.7657.765
935161AD1-151 C
Adder
18.16235294117647215.438
958161AF2-110 C
Adder
1.53294117647058831.303
316336AC2-165 C
Adder
10.1788235294117648.652
940641AE2-051 C
80/20
18.8818.88
943471AF1-018 C
Adder
7.6152941176470596.473
3152331SURRY 2
80/20
27.86527.865
940481AE2-033 C
Adder
17.43882352941176714.823
940541AE2-040 C
Adder
3.10117647058823562.636
927041AC1-191 C
Adder
10.2870588235294128.744
963611AG1-210 C
Adder
0.68235294117647060.58
961611AG1-000B C
Adder
17.92352941176470415.235
316375AC2-012 C
80/20
1.521.52
961941AG1-037 C
Adder
0.53764705882352950.457
934321AD1-056 C
Adder
6.3870588235294125.429
934331AD1-057 C
Adder
3.5635294117647063.029
958211AF2-115 C
Adder
2.14705882352941171.825
941031AE2-094 C
80/20
42.24742.247
3150831SPRUNCA
80/20
10.42510.425
3150841SPRUNCB
80/20
10.42510.425
966871AG1-558 C
Adder
2.56235294117647072.178
964211AG1-282 C
Adder
2.07882352941176451.767
3150801HOPHCF4
80/20
4.1494.149
3151081ELIZAR1
80/20
3.6013.601
957861AF2-080 C
Adder
7.8129411764705896.641
3138533PONTONDP
Adder
0.63647058823529420.541
316257AC1-043 C
Adder
-6.121176470588236-5.203
316254AC1-120 C
Adder
-6.376470588235295-5.42
3150791HOPHCF3
80/20
2.7332.733
961951AG1-038 C
Adder
3.3858823529411772.878
3152251N ANNA1
80/20
56.69756.697
3150851SPRUNCC
80/20
0.1870.187
944631AF1-128 C
Adder
44.0564705882352937.448
933291AC2-141 C
80/20
34.37234.372
3150921YORKTN3
Adder
133.0105882352941113.059
934501AD1-074 C
Adder
36.4552941176470630.987
961671AG1-007 C
Adder
0.95176470588235310.809
946301AF1-294 C
Adder
3.5305882352941183.001
942461AE2-259 C
Adder
9.4035294117647077.993
934621AD1-088 C
Adder
9.6105882352941188.169
942001AE2-212 C
80/20
2.4472.447
962861AG1-135 C
Adder
6.3647058823529425.41
943741AF1-042 C
Adder
3.06352941176470632.604
960081AF2-299 C
Adder
1.95294117647058821.66
936261AD2-033 C
Adder
12.57294117647058810.687
961791AG1-021 C
Adder
1.71764705882352931.46
938771AE1-103 C
Adder
3.22705882352941182.743
963041AG1-153 C
Adder
5.8858823529411765.003
944011AF1-069 C
80/20
13.80413.804
966881AG1-559 C
Adder
2.45176470588235332.084
3150601CHESTF5
Adder
70.4105882352941159.849
944591AF1-124 C
80/20
51.4651.46
944601AF1-125 C
80/20
50.48850.488
3151101ELIZAR3
80/20
3.6473.647
941591AE2-156 C
80/20
20.20920.209
316233AE1-074 C
80/20
2.8742.874
940551AE2-041 C
Adder
7.6152941176470596.473
943461AF1-017 C
Adder
1.51764705882352961.29
316311AC2-079 C
Adder
6.4458823529411775.479
934521AD1-076 C
Adder
13.2411.254
934511AD1-075 C
Adder
9.1141176470588237.747
316263AC1-034 C
Adder
6.6529411764705895.655
959311AF2-222 C
Adder
16.0552941176470613.647
316240AF1-291 C
80/20
2.4442.444
944641AF1-129 C
80/20
115.84115.84
3150781HOPHCF2
80/20
2.7332.733
3150761HOPPOLC
80/20
1.7191.719
964791AG1-342 C
Adder
3.38000000000000032.873
3143096IRON208
80/20
0.4940.494
958261AF2-120 C
Adder
6.5505882352941175.568
939191AE1-149 C
80/20
12.15312.153
957601AF2-054 C
Adder
2.26000000000000021.921
3137643SOCKMAN
Adder
0.74235294117647070.631
966661AG1-536 C
Adder
5.6341176470588234.789
939411AE1-173 C
80/20
99.71499.714
3150991CHESPKB
80/20
0.8130.813
316303AF2-085
80/20
4.4474.447
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.4135.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69496.694
NYPJM->LTFIMP_NY
CLTF
2.72.7
LGEELTFEXP_LGEE->PJM
CLTF
1.331.33
WECLTFEXP_WEC->PJM
CLTF
0.6540.654
SIGELTFEXP_SIGE->PJM
CLTF
0.2560.256
CPLELTFEXP_CPLE->PJM
CLTF
11.35211.352
TVALTFEXP_TVA->PJM
CLTF
6.4156.415
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.72830.728
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.33523.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.0414.041
LAGNLTFEXP_LAGN->PJM
CLTF
8.0268.026

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.99 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4412.36
MW Contribution:139.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926071AC1-086 C
Adder
19.96117647058823516.967
946281AF1-292 C
Adder
1.48705882352941181.264
960082AF2-299 E
Adder
1.19764705882352951.018
916042Z1-036 E
Adder
26.91882352941176422.881
923832AB2-022 E
Adder
1.1682352941176470.993
964241AG1-285 C
Adder
11.78352941176470610.016
958212AF2-115 E
Adder
1.78941176470588231.521
938772AE1-103 E
Adder
3.8211764705882363.248
963042AG1-153 E
50/50
8.8728.872
925022AB2-158 E
50/50
9.5359.535
944592AF1-124 E
Adder
98.9435294117647184.102
944582AF1-123 E
Adder
98.5858823529411883.798
316349AD2-085 C
Adder
3.23411764705882382.749
935112AD1-144 E
Adder
0.8717647058823530.741
918512AA1-065 E OP
Adder
5.2011764705882364.421
934502AD1-074 E
Adder
16.13411764705882613.714
934512AD1-075 E
Adder
4.0341176470588243.429
924516AB2-100 E1
Adder
2.82.38
966621AG1-532 C
Adder
1.34705882352941191.145
919153AA1-139 E2
Adder
3.8505882352941183.273
924022AB2-043 E O1
Adder
4.8811764705882354.149
3147223TWITTYS
Adder
0.89294117647058820.759
959312AF2-222 E
Adder
10.4764705882352948.905
3151021BRUNSWICKG1
50/50
8.78.7
3151041BRUNSWICKG3
50/50
8.78.7
3152261N ANNA2
50/50
93.22693.226
940642AE2-051 E
50/50
12.32512.325
942341AE2-247 C
Adder
1.40235294117647061.192
943462AF1-017 E
Adder
2.06941176470588231.759
958162AF2-110 E
Adder
2.0505882352941181.743
943172AE2-346 E
Adder
0.5717647058823530.486
917332KELFORD E
Adder
1.54588235294117651.314
934522AD1-076 E
Adder
5.8670588235294124.987
940492AE2-034 E
Adder
2.90235294117647062.467
962571AG1-106 C
Adder
2.58235294117647032.195
918492AA1-063AE OP
Adder
3.87294117647058833.292
957871AF2-081 C
Adder
9.4164705882352948.004
961792AG1-021 E
Adder
1.4317647058823531.217
937482AD2-202 E
Adder
1.04941176470588250.892
3145506HICKORY
Adder
2.05411764705882361.746
946262AF1-291 E
Adder
1.261.071
3150651CHESTF6
Adder
16.10470588235294213.689
933292AC2-141 E
Adder
12.19411764705882510.365
934576AD1-082 E
Adder
4.1188235294117653.501
944602AF1-125 E
Adder
97.0388235294117782.483
943612AF1-032 E
Adder
0.87058823529411770.74
316141AB2-099 E
Adder
0.237647058823529430.202
923994AB2-040_E
Adder
5.8811764705882354.999
316088AB2-174 E
Adder
6.242352941176475.306
924322AB2-079 E O1
Adder
1.25764705882352931.069
946302AF1-294 E
Adder
2.9258823529411772.487
957481AF2-042 C
Adder
54.4729411764705946.302
3151801S ANNAS2
50/50
1.2331.233
942002AE2-212 E
Adder
1.31294117647058851.116
940431AE2-027 C
Adder
11.3411764705882369.64
944581AF1-123 C
Adder
43.0529411764705936.595
941101AE2-104 C
Adder
3.1588235294117652.685
933981AD1-022 C
Adder
8.247.004
900672V4-068 E
Adder
0.33764705882352940.287
938531AE1-072 C
Adder
16.55647058823529614.073
924302AB2-077 E O1
Adder
1.25764705882352931.069
3145393UNCAMP
Adder
5.7482352941176484.886
935161AD1-151 C
Adder
13.84941176470588311.772
932046AC2-012 E
Adder
12.31647058823529410.469
958161AF2-110 C
Adder
1.28941176470588251.096
933982AD1-022 E
Adder
4.4858823529411773.813
3145946PLYMOUTH TP
Adder
0.30352941176470590.258
934612AD1-087 E
Adder
3.5835294117647063.046
934622AD1-088 E
Adder
4.6035294117647063.913
3152431Z1-086 GT3
50/50
11.14611.146
316336AC2-165 C
Adder
10.1788235294117648.652
940641AE2-051 C
50/50
18.48718.487
316084AB2-161 E
Adder
5.1694117647058834.394
923263AB1-132 E OP
Adder
5.80941176470588254.938
940481AE2-033 C
Adder
15.98588235294117513.588
940482AE2-033 E
Adder
10.777647058823539.161
940541AE2-040 C
Adder
2.84470588235294162.418
924312AB2-078 E O1
Adder
1.25764705882352931.069
925612AC1-036 E
Adder
0.80588235294117660.685
3152441Z1-086 ST
50/50
19.40819.408
966001AG1-469 C
Adder
1.46235294117647091.243
961611AG1-000B C
Adder
13.98823529411764911.89
961942AG1-037 E
Adder
0.317647058823529450.27
961941AG1-037 C
Adder
0.476470588235294150.405
923852AB2-025 E
Adder
1.15058823529411770.978
936262AD2-033 E
Adder
8.1458823529411776.924
958211AF2-115 C
Adder
2.1011764705882351.786
3151761LOISA E
50/50
4.9314.931
3151771S ANNAG1
50/50
2.42.4
3151791S ANNAG2
50/50
2.42.4
3151781S ANNAS1
50/50
1.2331.233
923862AB2-026 E
Adder
1.31.105
941031AE2-094 C
50/50
42.60742.607
941032AE2-094 E
50/50
19.08319.083
3150831SPRUNCA
Adder
8.2435294117647067.007
3150841SPRUNCB
Adder
8.2435294117647067.007
939412AE1-173 E
50/50
62.82462.824
926662AC1-147 E
Adder
1.24470588235294131.058
916192Z1-068 E
Adder
1.77058823529411761.505
957492AF2-043 E
Adder
1.341.139
946282AF1-292 E
Adder
0.99176470588235290.843
3138533PONTONDP
Adder
0.62235294117647070.529
944012AF1-069 E
50/50
5.4085.408
962572AG1-106 E
Adder
1.12941176470588230.96
957872AF2-081 E
Adder
4.0352941176470593.43
924162AB2-060 E OP
Adder
4.0294117647058823.425
964242AG1-285 E
Adder
7.8564705882352946.678
938562AE1-075 E
Adder
1.1082352941176470.942
3152251N ANNA1
50/50
93.18793.187
938552AE1-074 E
50/50
1.3051.305
926755AC1-161 E
Adder
12.19411764705882510.365
933291AC2-141 C
Adder
28.56588235294117724.281
925522AC1-027 E
Adder
1.14588235294117660.974
941102AE2-104 E
Adder
5.0223529411764714.269
3145256KINGFORK
Adder
0.93882352941176480.798
934501AD1-074 C
Adder
31.6952941176470626.941
924517AB2-100 E2
Adder
2.82.38
937226AE2-253 E
Adder
5.5047058823529414.679
946301AF1-294 C
Adder
3.45529411764705862.937
935172AD1-152 E
Adder
5.2941176470588234.5
942461AE2-259 C
Adder
9.2705882352941187.88
934621AD1-088 C
Adder
9.5599999999999998.126
957482AF2-042 E
Adder
36.31529411764705630.868
208901BRIS G2
50/50
-3.245-3.245
958502AF2-144 E
Adder
1.2764705882352941.085
316192AB2-158 C
50/50
3.5873.587
942001AE2-212 C
Adder
1.96941176470588241.674
939192AE1-149 E
Adder
6.6670588235294125.667
939312AE1-162 E
Adder
1.29647058823529431.102
934065AD1-033 E
Adder
4.7282352941176474.019
926072AC1-086 E
Adder
9.0847058823529427.722
960081AF2-299 C
Adder
1.7964705882352941.527
3145413WATKINS
Adder
0.65411764705882360.556
936261AD2-033 C
Adder
12.2210.387
961791AG1-021 C
Adder
1.68117647058823551.429
938771AE1-103 C
Adder
2.7670588235294122.352
963041AG1-153 C
50/50
5.9155.915
3151051BRUNSWICKS1
50/50
18.07518.075
944011AF1-069 C
50/50
13.92113.921
927226AC1-216 E
Adder
6.6694117647058825.669
944591AF1-124 C
Adder
43.2058823529411836.725
944601AF1-125 C
Adder
42.3894117647058836.031
941591AE2-156 C
Adder
16.83647058823529414.311
936666AD2-085 E
Adder
5.2764705882352954.485
920692AA2-178 E
Adder
3.86941176470588263.289
966622AG1-532 E
Adder
0.89882352941176480.764
917122Z2-027 E
Adder
1.26588235294117671.076
3146326AYDLETT TAP
Adder
1.27764705882352961.086
938532AE1-072 E
Adder
8.6305882352941187.336
3147133PAMPLIN
Adder
0.92823529411764720.789
3152411Z1-086 GT1
50/50
11.14911.149
3152421Z1-086 GT2
50/50
11.14611.146
966002AG1-469 E
Adder
0.73058823529411760.621
316233AE1-074 C
50/50
2.5912.591
935162AD1-151 E
Adder
0.93764705882352950.797
943461AF1-017 C
Adder
1.26823529411764711.078
316311AC2-079 C
Adder
5.3905882352941184.582
932596AC2-079 E
Adder
8.7952941176470587.476
934521AD1-076 C
Adder
11.5105882352941199.784
934511AD1-075 C
Adder
7.9235294117647066.735
919692AA2-053 E OP
Adder
4.00705882352941253.406
923573AB1-173 E OP
Adder
3.1364705882352942.666
3145723EMPORIA
Adder
0.414117647058823530.352
920042AA2-088 E OP
Adder
10.0447058823529418.538
925785AC1-054 E
Adder
3.24941176470588242.762
919152AA1-139 E1
Adder
3.8505882352941183.273
959311AF2-222 C
Adder
15.63529411764705813.29
3151031BRUNSWICKG2
50/50
8.78.7
316240AF1-291 C
Adder
1.88941176470588261.606
944641AF1-129 C
Adder
88.4505882352941375.183
924814AB2-134 E
Adder
10.9235294117647069.285
942342AE2-247 E
Adder
1.93529411764705881.645
901082W1-029 E
Adder
30.02588235294117425.522
942462AE2-259 E
Adder
6.1800000000000015.253
3151731LOISA B
50/50
2.4192.419
3151751LOISA D
50/50
2.4192.419
3143316POE
Adder
1.30941176470588231.113
939191AE1-149 C
Adder
10.0011764705882348.501
3137643SOCKMAN
Adder
0.67882352941176470.577
913392Y1-086 E
Adder
2.0705882352941181.76
933502AC2-165 E
Adder
7.6611764705882356.512
940432AE2-027 E
Adder
7.5611764705882356.427
939411AE1-173 C
50/50
94.23794.237
934012AD1-025 E
Adder
8.6341176470588247.339
316303AF2-085
50/50
4.464.46
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.1255.125
CBM South 2LTFEXP_CBM-S2->PJM
CBM
90.8190.81
NYPJM->LTFIMP_NY
CLTF
2.6122.612
LGEELTFEXP_LGEE->PJM
CLTF
1.1951.195
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5685.568
SIGELTFEXP_SIGE->PJM
CLTF
0.2320.232
CPLELTFEXP_CPLE->PJM
CLTF
10.7510.75
TVALTFEXP_TVA->PJM
CLTF
5.8785.878
O66PJM->LTFIMP_O-066
CMTX_NF
35.46935.469
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.02528.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.37921.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.6863.686
LAGNLTFEXP_LAGN->PJM
CLTF
7.3867.386

Details for 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8OX-8CLIFTON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2101-569_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.43 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3314.57
MW Contribution:95.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
923832AB2-022 E
Adder
0.80.68
316415AF1-147_GEN2
Adder
-5.709411764705882-4.853
925022AB2-158 E
Adder
3.342.839
316044AC1-158 C1
50/50
4.244.24
939261AE1-157 C
50/50
11.34411.344
966882AG1-559 E
50/50
0.9590.959
957971AF2-091 C
Adder
1.91529411764705881.628
930122AB1-027 E
Adder
0.95294117647058830.81
316169AC1-164 GEN
Adder
27.6552941176470623.507
944592AF1-124 E
Adder
68.1082352941176557.892
944582AF1-123 E
Adder
67.8623529411764757.683
316349AD2-085 C
Adder
2.24588235294117671.909
935112AD1-144 E
Adder
0.61764705882352940.525
919153AA1-139 E2
Adder
2.6505882352941182.253
3152261N ANNA2
50/50
23.22323.223
940642AE2-051 E
Adder
6.9188235294117655.881
926412AC1-112 E
Adder
0.77529411764705890.659
963612AG1-210 E
Adder
0.76823529411764710.653
942341AE2-247 C
Adder
0.97294117647058820.827
943462AF1-017 E
Adder
1.43647058823529421.221
958162AF2-110 E
Adder
1.4117647058823531.2
957871AF2-081 C
Adder
6.4823529411764715.51
3145506HICKORY
Adder
1.41764705882352951.205
946262AF1-291 E
Adder
0.97058823529411760.825
3150651CHESTF6
Adder
12.60823529411764810.717
936591AD2-074 C
Adder
4.13764705882352953.517
3130536PAPERMILL
Adder
4.6305882352941183.936
939602AE1-190 E
Adder
0.99882352941176470.849
933292AC2-141 E
Adder
8.4905882352941177.217
934576AD1-082 E
Adder
2.8988235294117652.464
944602AF1-125 E
Adder
66.7976470588235356.778
943612AF1-032 E
Adder
0.60.51
938531AE1-072 C
Adder
11.3870588235294139.679
926486AC1-120 E
Adder
2.38235294117647062.025
3150731STONECA
Adder
4.6788235294117653.977
935161AD1-151 C
Adder
10.8658823529411789.236
932046AC2-012 E
Adder
8.5752941176470587.289
958161AF2-110 C
Adder
0.88705882352941180.754
926004AC1-076_E
Adder
2.9364705882352942.496
940641AE2-051 C
Adder
10.3776470588235298.821
926472AC1-118 E
Adder
0.89058823529411770.757
926785AC1-164_E
Adder
12.42470588235294210.561
943471AF1-018 C
Adder
5.002352941176474.252
316084AB2-161 E
Adder
3.63882352941176463.093
923852AB2-025 E
Adder
0.70705882352941170.601
316411AF1-147_GEN1
Adder
-5.709411764705882-4.853
941031AE2-094 C
Adder
7.7070588235294126.551
3150081POSSM6A
50/50
3.7073.707
3150391LDYSMT3
50/50
3.9183.918
3150831SPRUNCA
Adder
6.19058823529411755.262
3150841SPRUNCB
Adder
6.19058823529411755.262
957191AF2-013 C
Adder
13.7647058823529411.7
966872AG1-558 E
Adder
0.86352941176470590.734
966871AG1-558 C
Adder
1.71411764705882371.457
316076AC2-137 E
Adder
0.91529411764705890.778
964211AG1-282 C
Adder
1.53411764705882361.304
923842AB2-024 E
Adder
1.25176470588235311.064
316157AD2-030 E
Adder
0.83647058823529410.711
939412AE1-173 E
Adder
37.00235294117647631.452
926662AC1-147 E
Adder
0.86705882352941180.737
916192Z1-068 E
Adder
1.22705882352941181.043
957492AF2-043 E
Adder
0.92352941176470590.785
957872AF2-081 E
Adder
2.77764705882352962.361
3152251N ANNA1
50/50
23.21323.213
938552AE1-074 E
Adder
0.82823529411764710.704
934782AD1-105 E
Adder
3.91411764705882353.327
944631AF1-128 C
Adder
27.14823529411764723.076
936592AD2-074 E
Adder
6.7505882352941185.738
316160AE1-175 E
Adder
0.80823529411764720.687
926755AC1-161 E
Adder
8.4905882352941177.217
933291AC2-141 C
Adder
19.89058823529411816.907
3150921YORKTN3
Adder
80.576470588235368.49
925522AC1-027 E
Adder
0.79411764705882360.675
941102AE2-104 E
Adder
3.4564705882352942.938
3145256KINGFORK
Adder
0.66470588235294110.565
316254AC1-120 C
Adder
4.6235294117647063.93
939262AE1-157 E
50/50
6.1536.153
936582AD2-073 E
Adder
0.85411764705882350.726
961952AG1-038 E
Adder
3.30470588235294162.809
961951AG1-038 C
Adder
2.3929411764705882.034
925865AC1-065 E
Adder
11.6529411764705889.905
940541AE2-040 C
Adder
1.7482352941176471.486
926740AC1-158 E2
50/50
11.0911.09
3150371LDYSMT1
50/50
3.7683.768
927041AC1-191 C
Adder
6.8811764705882365.849
3138116ELKO L286
Adder
0.9552941176470590.812
963611AG1-210 C
Adder
0.51294117647058820.436
961611AG1-000B C
Adder
10.6435294117647079.047
316170AC1-121 C
Adder
1.58823529411764721.35
3150071POSSM 5
Adder
89.4835294117647276.061
316045AC1-158 C2
50/50
4.244.24
966881AG1-559 C
50/50
1.9031.903
3150601CHESTF5
Adder
43.3882352941176536.88
964212AG1-282 E
Adder
1.02235294117647070.869
925332AB2-190 E
Adder
5.4447058823529424.628
962962AG1-145 E
Adder
0.980.833
927226AC1-216 E
Adder
5.19058823529411754.412
944591AF1-124 C
Adder
29.74117647058823625.28
944601AF1-125 C
Adder
29.17882352941176524.802
941591AE2-156 C
Adder
11.7164705882352949.959
936666AD2-085 E
Adder
3.66470588235294153.115
917122Z2-027 E
Adder
0.86470588235294120.735
3146326AYDLETT TAP
Adder
0.87882352941176480.747
938532AE1-072 E
Adder
5.9364705882352945.046
926739AC1-158 E1
50/50
11.0911.09
3150381LDYSMT2
50/50
3.8173.817
316233AE1-074 C
Adder
1.6435294117647061.397
927042AC1-191 E
Adder
3.42823529411764752.914
940551AE2-041 C
Adder
5.002352941176474.252
935162AD1-151 E
Adder
7.24470588235294166.158
957832AF2-077 E
Adder
0.98235294117647050.835
943461AF1-017 C
Adder
0.88117647058823530.749
316311AC2-079 C
Adder
3.73882352941176473.178
932596AC2-079 E
Adder
6.1011764705882365.186
937226AE2-253 E
Adder
3.79294117647058873.224
942001AE2-212 C
Adder
1.44117647058823551.225
3141813NORNECK
Adder
0.68235294117647060.58
962861AG1-135 C
Adder
4.57294117647058853.887
939192AE1-149 E
Adder
4.7364705882352944.026
943741AF1-042 C
Adder
2.16470588235294151.84
939312AE1-162 E
Adder
0.94823529411764720.806
934065AD1-033 E
Adder
3.2670588235294122.777
919152AA1-139 E1
Adder
2.6505882352941182.253
926502AC1-121 E
Adder
0.74705882352941180.635
3150411LDYSMT5
50/50
3.9383.938
316240AF1-291 C
Adder
1.4552941176470591.237
944641AF1-129 C
Adder
69.2494117647058858.862
957972AF2-091 E
Adder
2.64588235294117662.249
939246AE1-155 E
Adder
6.58588235294117655.598
924814AB2-134 E
Adder
8.5035294117647067.228
942342AE2-247 E
Adder
1.34470588235294121.143
942002AE2-212 E
Adder
0.96117647058823530.817
3150401LDYSMT4
50/50
3.9253.925
940431AE2-027 C
Adder
8.722352941176477.414
944492AF1-114 E
Adder
7.7811764705882356.614
966662AG1-536 E
Adder
5.4670588235294124.647
962862AG1-135 E
Adder
3.0482352941176472.591
943742AF1-042 E
Adder
3.5317647058823533.002
934392AD1-063 E
Adder
0.75058823529411770.638
944581AF1-123 C
Adder
29.6352941176470625.19
941101AE2-104 C
Adder
2.17411764705882371.848
901082W1-029 E
Adder
20.48235294117647217.41
3150101POSSM6S
50/50
5.7795.779
3150181POSSMC2
50/50
0.8240.824
3143316POE
Adder
0.89058823529411770.757
958261AF2-120 C
Adder
4.72941176470588154.02
939191AE1-149 C
Adder
7.1058823529411776.04
934146AD1-041 E
Adder
2.49764705882352982.123
957601AF2-054 C
Adder
1.49058823529411751.267
913392Y1-086 E
Adder
1.41764705882352951.205
3150091POSSM6B
50/50
3.7073.707
3150331BIRCHWDA
Adder
28.4352941176470624.17
940432AE2-027 E
Adder
5.8152941176470594.943
944491AF1-114 C
Adder
5.6352941176470594.79
316078AC2-138 E
Adder
0.71764705882352940.61
958262AF2-120 E
Adder
3.15294117647058862.68
966661AG1-536 C
Adder
4.0682352941176473.458
939612AE1-191 E
Adder
3.99529411764705873.396
957602AF2-054 E
Adder
0.99411764705882360.845
939411AE1-173 C
Adder
55.50470588235294447.179
934012AD1-025 E
Adder
6.725.712
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.9592.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
52.10752.107
NYPJM->LTFIMP_NY
CLTF
1.9611.961
LGEELTFEXP_LGEE->PJM
CLTF
0.4830.483
G-007PJM->LTFIMP_G-007
CMTX_NF
3.9723.972
SIGELTFEXP_SIGE->PJM
CLTF
0.0980.098
WECLTFEXP_WEC->PJM
CLTF
0.2130.213
CPLELTFEXP_CPLE->PJM
CLTF
6.2066.206
TVALTFEXP_TVA->PJM
CLTF
3.123.12
O66PJM->LTFIMP_O-066
CMTX_NF
25.38725.387
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.0499.049
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.51310.513
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5641.564
LAGNLTFEXP_LAGN->PJM
CLTF
3.8863.886

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.18 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3902.62
MW Contribution:39.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966621AG1-532 C
80/20
1.2551.255
316320Y1-086 C
80/20
0.1920.192
316388AE2-253 GEN
80/20
1.711.71
935171AD1-152 C
80/20
1.1991.199
3151021BRUNSWICKG1
80/20
8.1438.143
3151041BRUNSWICKG3
80/20
8.1438.143
934861AD1-115 C
Adder
2.8482352941176472.421
3152261N ANNA2
80/20
89.07389.073
942341AE2-247 C
80/20
1.2991.299
316246AF1-032 C
80/20
0.2480.248
933981AD1-022 C
Adder
7.6458823529411766.499
938531AE1-072 C
80/20
15.34615.346
3150731STONECA
Adder
5.3258823529411774.527
935161AD1-151 C
Adder
12.7647058823529410.85
316083AB2-161 C
80/20
0.4780.478
958161AF2-110 C
80/20
1.1951.195
313526AB2-022 C
80/20
0.3280.328
316017AA1-139 ULT1
80/20
0.9420.942
934611AD1-087 C
80/20
1.1591.159
3152431Z1-086 GT3
80/20
10.43410.434
316336AC2-165 C
80/20
9.6099.609
940641AE2-051 C
80/20
17.2917.29
3147043LAWRENC
80/20
0.2730.273
940481AE2-033 C
80/20
14.89114.891
940541AE2-040 C
80/20
2.652.65
3152441Z1-086 ST
80/20
18.16818.168
966001AG1-469 C
80/20
1.9591.959
961611AG1-000B C
Adder
12.91058823529411910.974
316375AC2-012 C
80/20
1.1731.173
927021AC1-189 C
Adder
7.2364705882352946.151
926071AC1-086 C
Adder
18.5623529411764715.778
946281AF1-292 C
80/20
1.3851.385
964241AG1-285 C
Adder
11.0294117647058829.375
962561AG1-105 C
Adder
7.70470588235294156.549
316044AC1-158 C1
80/20
19.41919.419
961941AG1-037 C
Adder
0.44235294117647060.376
934321AD1-056 C
Adder
5.4329411764705894.618
934331AD1-057 C
Adder
3.0305882352941182.576
958211AF2-115 C
Adder
1.97411764705882351.678
3151531CLOVER1
80/20
11.76811.768
208900BRIS G1
80/20
-2.628-2.628
3151761LOISA E
80/20
5.5225.522
3151771S ANNAG1
80/20
2.6512.651
3151791S ANNAG2
80/20
2.6512.651
3151781S ANNAS1
80/20
1.3621.362
316258AE1-075 C
80/20
0.3460.346
941031AE2-094 C
80/20
39.89839.898
3150831SPRUNCA
Adder
7.6235294117647066.48
3150841SPRUNCB
Adder
7.6235294117647066.48
3151081ELIZAR1
80/20
2.7822.782
316018AA1-139 ULT2
80/20
0.9420.942
3152251N ANNA1
80/20
89.03589.035
3150851SPRUNCC
80/20
0.1370.137
933291AC2-141 C
80/20
26.46526.465
3150921YORKTN3
Adder
90.5694117647058876.984
934501AD1-074 C
Adder
29.40470588235294324.994
961671AG1-007 C
Adder
0.80588235294117660.685
946301AF1-294 C
Adder
3.2458823529411762.759
942461AE2-259 C
Adder
8.7329411764705887.423
934621AD1-088 C
80/20
8.9588.958
208901BRIS G2
80/20
-3.11-3.11
316192AB2-158 C
80/20
3.6253.625
942001AE2-212 C
Adder
1.82117647058823541.548
957861AF2-080 C
Adder
6.57294117647058855.587
316023AB2-100 C2
80/20
0.8620.862
316315AB2-025 C
80/20
0.3750.375
3138533PONTONDP
Adder
0.58470588235294120.497
3151541CLOVER2
80/20
11.65811.658
316257AC1-043 C
Adder
5.697647058823534.843
316254AC1-120 C
80/20
7.9327.932
316316AC1-027 C
80/20
0.2750.275
960081AF2-299 C
80/20
1.6731.673
936261AD2-033 C
Adder
11.4505882352941189.733
961791AG1-021 C
Adder
1.57882352941176471.342
938771AE1-103 C
80/20
2.5672.567
963041AG1-153 C
80/20
5.5365.536
3151051BRUNSWICKS1
80/20
16.91816.918
316170AC1-121 C
80/20
2.7242.724
944011AF1-069 C
80/20
13.03613.036
316045AC1-158 C2
80/20
19.41919.419
944591AF1-124 C
80/20
40.05140.051
944601AF1-125 C
80/20
39.29539.295
3151101ELIZAR3
80/20
2.8172.817
941591AE2-156 C
80/20
15.615.6
3156056W1-029WIND
80/20
0.6760.676
3152411Z1-086 GT1
80/20
10.43710.437
3152421Z1-086 GT2
80/20
10.43410.434
316233AE1-074 C
80/20
2.4172.417
943461AF1-017 C
80/20
1.1751.175
316311AC2-079 C
80/20
4.9964.996
934521AD1-076 C
Adder
10.6788235294117659.077
934511AD1-075 C
Adder
7.3517647058823536.249
316263AC1-034 C
Adder
5.6858823529411774.833
316087AB2-174 C
80/20
1.0461.046
316321Z2-027 C
80/20
0.3170.317
959311AF2-222 C
Adder
14.6623529411764712.463
937481AD2-202 C
80/20
0.3360.336
3151031BRUNSWICKG2
80/20
8.1438.143
316240AF1-291 C
Adder
1.7435294117647061.482
944641AF1-129 C
Adder
81.5517647058823669.319
316036AC1-147 C
80/20
0.320.32
316305AF2-043 C
80/20
0.3030.303
316365AB2-100 C1
80/20
0.8620.862
957481AF2-042 C
80/20
51.00351.003
3151801S ANNAS2
80/20
1.3621.362
940431AE2-027 C
Adder
10.4682352941176488.898
316294AC1-161 C
80/20
4.314.31
944581AF1-123 C
80/20
39.90939.909
316185AD1-033 C
80/20
1.071.07
916191Z1-068 C
80/20
0.0380.038
941101AE2-104 C
80/20
2.9282.928
316274AC1-208 C
Adder
7.857647058823536.679
962571AG1-106 C
Adder
2.40117647058823552.041
3151311EDGECMA
Adder
13.28823529411764811.295
957871AF2-081 C
80/20
8.7288.728
316405AF2-144 C
80/20
0.2940.294
3150651CHESTF6
Adder
14.84823529411764812.621
3150861SPRUNCD
80/20
0.1370.137
964791AG1-342 C
Adder
3.06352941176470632.604
3151731LOISA B
80/20
2.7082.708
3151751LOISA D
80/20
2.7082.708
316313AB2-026 C
80/20
0.3770.377
316164AC1-076_C
80/20
1.1141.114
939191AE1-149 C
80/20
9.2629.262
3150981CHESPKA
80/20
0.3780.378
3151091ELIZAR2
80/20
2.7332.733
316349AD2-085 C
80/20
2.9972.997
3137643SOCKMAN
Adder
0.6317647058823530.537
3151741LOISA C
80/20
2.7082.708
3151721LOISA A
80/20
2.6942.694
939411AE1-173 C
80/20
87.96287.962
316381AD1-082 C
80/20
1.0891.089
3150991CHESPKB
80/20
0.6270.627
316303AF2-085
80/20
4.1844.184
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.744.74
CBM South 2LTFEXP_CBM-S2->PJM
CBM
83.40383.403
NYPJM->LTFIMP_NY
CLTF
2.5322.532
LGEELTFEXP_LGEE->PJM
CLTF
0.9710.971
SIGELTFEXP_SIGE->PJM
CLTF
0.1910.191
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
CPLELTFEXP_CPLE->PJM
CLTF
9.9459.945
TVALTFEXP_TVA->PJM
CLTF
5.1955.195
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.96121.961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.49718.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.0623.062
LAGNLTFEXP_LAGN->PJM
CLTF
6.5316.531

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.07 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3866.79
MW Contribution:49.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966621AG1-532 C
Adder
1.43529411764705881.22
3152261N ANNA2
80/20
55.34655.346
3150771HOPHCF1
80/20
2.6772.677
942341AE2-247 C
Adder
1.64235294117647061.396
933981AD1-022 C
Adder
9.2505882352941197.863
938531AE1-072 C
Adder
19.2929411764705916.399
3142366NRTHEST
80/20
0.20.2
3150731STONECA
80/20
7.6067.606
935161AD1-151 C
Adder
17.79176470588235415.123
958161AF2-110 C
Adder
1.50117647058823531.276
316336AC2-165 C
Adder
10.1094117647058828.593
940641AE2-051 C
80/20
18.48818.488
943471AF1-018 C
Adder
7.4541176470588246.336
3152331SURRY 2
80/20
27.29427.294
940481AE2-033 C
Adder
17.08117647058823614.519
940541AE2-040 C
Adder
3.03764705882352942.582
961941AG1-037 C
Adder
0.52705882352941180.448
934321AD1-056 C
Adder
6.2529411764705895.315
934331AD1-057 C
Adder
3.4882352941176472.965
958211AF2-115 C
Adder
2.12470588235294141.806
941031AE2-094 C
80/20
41.37341.373
3150831SPRUNCA
80/20
10.21910.219
3150841SPRUNCB
80/20
10.21910.219
966871AG1-558 C
Adder
2.50941176470588222.133
964211AG1-282 C
Adder
2.0317647058823531.727
3150801HOPHCF4
80/20
4.0644.064
3151081ELIZAR1
80/20
3.5273.527
3152251N ANNA1
80/20
55.32355.323
3150851SPRUNCC
80/20
0.1830.183
944631AF1-128 C
Adder
43.1623529411764736.688
933291AC2-141 C
80/20
33.66433.664
3150921YORKTN3
Adder
130.26705882352942110.727
934501AD1-074 C
Adder
35.6976470588235330.343
961671AG1-007 C
Adder
0.9317647058823530.792
946301AF1-294 C
Adder
3.4941176470588242.97
942461AE2-259 C
Adder
9.347.939
934621AD1-088 C
Adder
9.4482352941176488.031
316192AB2-158 C
80/20
2.1182.118
942001AE2-212 C
80/20
2.3972.397
962861AG1-135 C
Adder
6.222352941176475.289
943741AF1-042 C
Adder
2.9964705882352942.547
957861AF2-080 C
Adder
7.6458823529411766.499
3138533PONTONDP
Adder
0.62941176470588240.535
3150791HOPHCF3
80/20
2.6772.677
961951AG1-038 C
Adder
3.3117647058823532.815
960081AF2-299 C
Adder
1.91411764705882351.627
936261AD2-033 C
Adder
12.4023529411764710.542
961791AG1-021 C
Adder
1.70000000000000021.445
938771AE1-103 C
Adder
3.162.686
963041AG1-153 C
Adder
5.7647058823529424.9
944011AF1-069 C
80/20
13.51813.518
316045AC1-158 C2
80/20
14.96214.962
966881AG1-559 C
Adder
2.3964705882352942.037
3150601CHESTF5
Adder
68.9811764705882458.634
944591AF1-124 C
80/20
50.39950.399
944601AF1-125 C
80/20
49.44749.447
3151101ELIZAR3
80/20
3.5723.572
941591AE2-156 C
80/20
19.79319.793
927041AC1-191 C
Adder
10.0729411764705888.562
963611AG1-210 C
Adder
0.66705882352941170.567
961611AG1-000B C
Adder
17.55647058823529614.923
316375AC2-012 C
80/20
1.4881.488
316233AE1-074 C
80/20
2.8192.819
940551AE2-041 C
Adder
7.4541176470588246.336
943461AF1-017 C
Adder
1.48588235294117641.263
316311AC2-079 C
Adder
6.3129411764705885.366
934521AD1-076 C
Adder
12.96470588235294111.02
934511AD1-075 C
Adder
8.9247058823529427.586
316263AC1-034 C
Adder
6.5105882352941185.534
959311AF2-222 C
Adder
15.85294117647058913.475
316240AF1-291 C
80/20
2.3942.394
944641AF1-129 C
80/20
113.49113.49
3150781HOPHCF2
80/20
2.6772.677
3150761HOPPOLC
80/20
1.6841.684
957481AF2-042 C
Adder
53.64117647058823545.595
940431AE2-027 C
80/20
14.31814.318
316294AC1-161 C
80/20
5.4825.482
944581AF1-123 C
80/20
50.22150.221
941101AE2-104 C
Adder
3.683.128
316274AC1-208 C
Adder
9.0917647058823537.728
962571AG1-106 C
Adder
2.7823529411764712.365
3151311EDGECMA
Adder
15.22352941176470512.94
957871AF2-081 C
Adder
10.989.333
3150651CHESTF6
80/20
20.66420.664
3150861SPRUNCD
80/20
0.1830.183
936591AD2-074 C
Adder
5.7258823529411764.867
964791AG1-342 C
Adder
3.32117647058823542.823
316164AC1-076_C
80/20
0.9930.993
3143096IRON208
80/20
0.4840.484
958261AF2-120 C
Adder
6.4035294117647065.443
939191AE1-149 C
80/20
11.90511.905
957601AF2-054 C
Adder
2.2117647058823531.88
927021AC1-189 C
Adder
8.4188235294117647.156
926071AC1-086 C
Adder
21.50823529411764718.282
946281AF1-292 C
Adder
1.58470588235294121.347
964241AG1-285 C
Adder
11.97764705882352810.181
962561AG1-105 C
Adder
8.3588235294117657.105
316044AC1-158 C1
80/20
14.96214.962
939261AE1-157 C
Adder
13.77647058823529511.71
316169AC1-164 GEN
Adder
42.77176470588235436.356
3151091ELIZAR2
80/20
3.4653.465
316349AD2-085 C
Adder
3.79058823529411763.222
3137643SOCKMAN
Adder
0.72705882352941180.618
966661AG1-536 C
Adder
5.5082352941176484.682
939411AE1-173 C
80/20
97.64897.648
3150991CHESPKB
80/20
0.7960.796
316303AF2-085
80/20
4.3634.363
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.2865.286
NYPJM->LTFIMP_NY
CLTF
2.8062.806
LGEELTFEXP_LGEE->PJM
CLTF
1.2221.222
SIGELTFEXP_SIGE->PJM
CLTF
0.2370.237
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
CBM South 2LTFEXP_CBM-S2->PJM
CBM
94.17394.173
CPLELTFEXP_CPLE->PJM
CLTF
11.08811.088
TVALTFEXP_TVA->PJM
CLTF
6.1396.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.65727.657
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.08222.082
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.7473.747
LAGNLTFEXP_LAGN->PJM
CLTF
7.6777.677

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.55 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4631.32
MW Contribution:137.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961942AG1-037 E
Adder
0.311764705882352940.265
961941AG1-037 C
Adder
0.46705882352941180.397
923852AB2-025 E
Adder
1.1282352941176470.959
936262AD2-033 E
Adder
8.0141176470588256.812
958211AF2-115 C
Adder
2.0717647058823531.761
208900BRIS G1
50/50
-2.836-2.836
3151761LOISA E
50/50
5.5965.596
946282AF1-292 E
Adder
0.97294117647058820.827
3138533PONTONDP
Adder
0.61411764705882350.522
926072AC1-086 E
Adder
8.9094117647058837.573
960081AF2-299 C
Adder
1.76235294117647071.498
3145413WATKINS
Adder
0.64235294117647070.546
936261AD2-033 C
Adder
12.02117647058823610.218
962562AG1-105 E
Adder
5.3929411764705884.584
961791AG1-021 C
Adder
1.65764705882352951.409
938771AE1-103 C
Adder
2.72117647058823582.313
963041AG1-153 C
Adder
5.7788235294117654.912
316170AC1-121 C
50/50
2.7692.769
944011AF1-069 C
50/50
13.59813.598
316045AC1-158 C2
50/50
19.48619.486
925332AB2-190 E
Adder
6.8164705882352945.794
927226AC1-216 E
Adder
6.5917647058823535.603
944591AF1-124 C
Adder
42.5247058823529436.146
944601AF1-125 C
Adder
41.7211764705882435.463
941591AE2-156 C
Adder
16.57647058823529614.09
936666AD2-085 E
Adder
5.195294117647064.416
920692AA2-178 E
Adder
3.8023529411764713.232
966622AG1-532 E
Adder
0.88117647058823530.749
917122Z2-027 E
Adder
1.24470588235294131.058
3146326AYDLETT TAP
Adder
1.25764705882352931.069
938532AE1-072 E
Adder
8.4941176470588247.22
3147133PAMPLIN
Adder
0.91529411764705890.778
966002AG1-469 E
50/50
0.9930.993
926739AC1-158 E1
50/50
50.96750.967
316233AE1-074 C
Adder
2.5458823529411772.164
935162AD1-151 E
Adder
9.1294117647058827.76
943461AF1-017 C
Adder
1.2482352941176471.061
316311AC2-079 C
Adder
5.3070588235294124.511
932596AC2-079 E
Adder
8.6588235294117667.36
3151771S ANNAG1
50/50
2.6852.685
3151791S ANNAG2
50/50
2.6852.685
3151781S ANNAS1
50/50
1.381.38
923862AB2-026 E
Adder
1.28117647058823541.089
941031AE2-094 C
50/50
41.61841.618
941032AE2-094 E
50/50
18.6418.64
3150831SPRUNCA
Adder
8.1435294117647056.922
3150841SPRUNCB
Adder
8.1435294117647056.922
939412AE1-173 E
Adder
61.5211764705882452.293
926662AC1-147 E
Adder
1.22588235294117661.042
916192Z1-068 E
Adder
1.74235294117647071.481
957492AF2-043 E
Adder
1.31882352941176471.121
934521AD1-076 C
Adder
11.3094117647058829.613
934511AD1-075 C
Adder
7.7847058823529426.617
919692AA2-053 E OP
Adder
3.93176470588235333.342
923573AB1-173 E OP
Adder
3.07647058823529432.615
3145723EMPORIA
Adder
0.405882352941176470.345
920042AA2-088 E OP
Adder
9.8670588235294128.387
925785AC1-054 E
Adder
3.18705882352941172.709
919152AA1-139 E1
Adder
3.78941176470588253.221
959311AF2-222 C
Adder
15.39294117647058813.084
926502AC1-121 E
50/50
1.3031.303
316240AF1-291 C
Adder
1.86705882352941191.587
944641AF1-129 C
Adder
87.4717647058823574.351
924814AB2-134 E
Adder
10.7988235294117659.179
942342AE2-247 E
Adder
1.90588235294117661.62
934501AD1-074 C
Adder
31.13882352941176626.468
924517AB2-100 E2
Adder
2.74588235294117672.334
937226AE2-253 E
Adder
5.4188235294117654.606
946301AF1-294 C
Adder
3.4070588235294122.896
935172AD1-152 E
Adder
5.1847058823529414.407
942461AE2-259 C
Adder
9.1658823529411777.791
934621AD1-088 C
Adder
9.3717647058823547.966
957482AF2-042 E
Adder
35.55176470588235630.219
208901BRIS G2
50/50
-3.356-3.356
958502AF2-144 E
Adder
1.2588235294117651.07
316192AB2-158 C
50/50
3.6573.657
942001AE2-212 C
Adder
1.94235294117647061.651
939192AE1-149 E
Adder
6.5694117647058825.584
939312AE1-162 E
Adder
1.27764705882352961.086
934065AD1-033 E
Adder
4.6541176470588243.956
926214AC1-099 E
Adder
1.1082352941176470.942
932632AC2-084 E
Adder
2.96705882352941152.522
962572AG1-106 E
Adder
1.1082352941176470.942
957872AF2-081 E
Adder
3.9717647058823533.376
924162AB2-060 E OP
Adder
3.95764705882352933.364
964242AG1-285 E
Adder
7.7211764705882356.563
934862AD1-115 E
Adder
4.73176470588235354.022
938562AE1-075 E
Adder
1.0917647058823530.928
3152251N ANNA1
50/50
89.57189.571
938552AE1-074 E
Adder
1.28235294117647071.09
926755AC1-161 E
Adder
12.0070588235294110.206
933291AC2-141 C
Adder
28.12941176470588223.91
925522AC1-027 E
Adder
1.1282352941176470.959
941102AE2-104 E
Adder
4.9423529411764714.201
3145256KINGFORK
Adder
0.92470588235294130.786
923263AB1-132 E OP
Adder
5.697647058823534.843
940481AE2-033 C
Adder
15.6752941176470613.324
940482AE2-033 E
Adder
10.5670588235294118.982
940541AE2-040 C
Adder
2.78823529411764742.37
924312AB2-078 E O1
Adder
1.23529411764705891.05
925612AC1-036 E
Adder
0.79294117647058830.674
966001AG1-469 C
50/50
1.9871.987
925672AC1-043 E
Adder
9.4635294117647078.044
926740AC1-158 E2
50/50
50.96750.967
961611AG1-000B C
Adder
13.8152941176470611.743
943172AE2-346 E
Adder
0.56117647058823530.477
917332KELFORD E
Adder
1.51764705882352961.29
925122AB2-169 E
Adder
5.2764705882352954.485
934522AD1-076 E
Adder
5.7635294117647064.899
940492AE2-034 E
Adder
2.85176470588235282.424
316274AC1-208 C
Adder
8.2905882352941187.047
962571AG1-106 C
Adder
2.53176470588235342.152
926206AC1-098 E
Adder
3.35647058823529452.853
901082W1-029 E
Adder
29.54000000000000325.109
942462AE2-259 E
Adder
6.1105882352941175.194
3151731LOISA B
50/50
2.7452.745
3151751LOISA D
50/50
2.7452.745
3143316POE
Adder
1.28823529411764711.095
316164AC1-076_C
50/50
1.1311.131
939191AE1-149 C
Adder
9.8529411764705898.375
316141AB2-099 E
Adder
0.234117647058823540.199
923994AB2-040_E
Adder
5.76941176470588254.904
316088AB2-174 E
Adder
6.1235294117647065.205
924322AB2-079 E O1
Adder
1.23529411764705891.05
946302AF1-294 E
Adder
2.88470588235294122.452
957481AF2-042 C
Adder
53.3270588235294245.328
3151801S ANNAS2
50/50
1.381.38
942002AE2-212 E
Adder
1.2952941176470591.101
940431AE2-027 C
Adder
11.2058823529411789.525
944581AF1-123 C
Adder
42.37411764705882436.018
941101AE2-104 C
Adder
3.10941176470588232.643
918512AA1-065 E OP
Adder
5.1070588235294124.341
934502AD1-074 E
Adder
15.85176470588235313.474
934512AD1-075 E
Adder
3.96235294117647063.368
924516AB2-100 E1
Adder
2.74588235294117672.334
966621AG1-532 C
Adder
1.32117647058823541.123
919153AA1-139 E2
Adder
3.78941176470588253.221
924022AB2-043 E O1
Adder
4.7941176470588244.075
3147223TWITTYS
Adder
0.87882352941176480.747
959312AF2-222 E
Adder
10.3129411764705888.766
934861AD1-115 C
Adder
2.92.465
3152261N ANNA2
50/50
89.60989.609
940642AE2-051 E
50/50
12.05212.052
942341AE2-247 C
Adder
1.38000000000000011.173
943462AF1-017 E
Adder
2.03764705882352941.732
958162AF2-110 E
Adder
2.01764705882352931.715
918492AA1-063AE OP
Adder
3.80117647058823543.231
957871AF2-081 C
Adder
9.2670588235294127.877
961792AG1-021 E
Adder
1.4117647058823531.2
937482AD2-202 E
Adder
1.02705882352941180.873
3145506HICKORY
Adder
2.02235294117647071.719
946262AF1-291 E
Adder
1.24470588235294131.058
3150651CHESTF6
Adder
15.92588235294117813.537
933292AC2-141 E
Adder
12.0070588235294110.206
934576AD1-082 E
Adder
4.0564705882352943.448
944602AF1-125 E
Adder
95.5082352941176581.182
943612AF1-032 E
Adder
0.85764705882352940.729
933982AD1-022 E
Adder
4.4070588235294123.746
3145946PLYMOUTH TP
Adder
0.29882352941176470.254
927146AC1-208 E
Adder
1.16941176470588240.994
934612AD1-087 E
Adder
3.50941176470588272.983
934622AD1-088 E
Adder
4.5117647058823533.835
316336AC2-165 C
Adder
10.0588235294117668.55
926004AC1-076_E
50/50
6.486.48
940641AE2-051 C
50/50
18.07818.078
316084AB2-161 E
Adder
5.0917647058823544.328
316257AC1-043 C
Adder
5.84.93
316254AC1-120 C
50/50
8.0618.061
944012AF1-069 E
50/50
5.2835.283
926071AC1-086 C
Adder
19.57647058823529616.64
946281AF1-292 C
Adder
1.45882352941176461.24
960082AF2-299 E
Adder
1.17529411764705880.999
916042Z1-036 E
Adder
26.4694117647058822.499
923832AB2-022 E
Adder
1.14941176470588240.977
964241AG1-285 C
Adder
11.5811764705882349.844
962561AG1-105 C
Adder
8.0894117647058836.876
958212AF2-115 E
Adder
1.76470588235294111.5
938772AE1-103 E
Adder
3.75764705882352963.194
963042AG1-153 E
Adder
8.6682352941176477.368
925022AB2-158 E
50/50
9.7219.721
316044AC1-158 C1
50/50
19.48619.486
944592AF1-124 E
Adder
97.3823529411764882.775
944582AF1-123 E
Adder
97.0317647058823782.477
316349AD2-085 C
Adder
3.1835294117647062.706
935112AD1-144 E
Adder
0.85764705882352940.729
3137643SOCKMAN
Adder
0.66588235294117650.566
913392Y1-086 E
Adder
2.03647058823529431.731
933502AC2-165 E
Adder
7.5705882352941176.435
3151741LOISA C
50/50
2.7452.745
3151721LOISA A
50/50
2.7312.731
940432AE2-027 E
Adder
7.4705882352941186.35
939411AE1-173 C
Adder
92.2811764705882478.439
934012AD1-025 E
Adder
8.5352941176470597.255
933981AD1-022 C
Adder
8.0941176470588236.88
900672V4-068 E
Adder
0.33058823529411770.281
938531AE1-072 C
Adder
16.29411764705882213.85
924302AB2-077 E O1
Adder
1.23529411764705891.05
3145393UNCAMP
Adder
5.65176470588235354.804
926486AC1-120 E
50/50
4.1534.153
935161AD1-151 C
Adder
13.69411764705882511.64
932046AC2-012 E
Adder
12.12705882352941210.308
958161AF2-110 C
Adder
1.26823529411764711.078
316303AF2-085
50/50
4.3644.364
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.0035.003
CBM South 2LTFEXP_CBM-S2->PJM
CBM
88.42988.429
NYPJM->LTFIMP_NY
CLTF
2.7142.714
LGEELTFEXP_LGEE->PJM
CLTF
1.0981.098
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7645.764
SIGELTFEXP_SIGE->PJM
CLTF
0.2140.214
WECLTFEXP_WEC->PJM
CLTF
0.5410.541
CPLELTFEXP_CPLE->PJM
CLTF
10.49610.496
TVALTFEXP_TVA->PJM
CLTF
5.6275.627
O66PJM->LTFIMP_O-066
CMTX_NF
36.7236.72
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.22125.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.23820.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.4183.418
LAGNLTFEXP_LAGN->PJM
CLTF
7.0687.068
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 545T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314916 CKT 1                /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H3T539_SRT-A'
 OPEN BRANCH FROM BUS 314130 TO BUS 314900 CKT 2   /*6BRISTER     230.0 - 8BRISTER     500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314919 CKT 1   /*8BRISTER     500.0 - 8OX          500.0
END
CONTINGENCY 'DVP_P4-2: H1T539_SRT-S'
 OPEN BRANCH FROM BUS 314130 TO BUS 314900 CKT 1                /*6BRISTER     230.0 - 8BRISTER     500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314919 CKT 1                /*8BRISTER     500.0 - 8OX          500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314063 TO BUS 314916 CKT 1                /*6MORRSVL     230.0 - 8MORRSVL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BUS 314897                                                /*8MORRS_1     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 568T575_SRT-A'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1   /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1   /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P7-1: LN 2101-569_SRT-S'
 OPEN BRANCH FROM BUS 313712 TO BUS 313716 CKT 1                /*6VINTHIL TP  230.0 - 6VINTHIL DP  230.0
 OPEN BRANCH FROM BUS 313712 TO BUS 314119 CKT 1                /*6VINTHIL TP  230.0 - 6NOKESVL     230.0
 OPEN BRANCH FROM BUS 313712 TO BUS 314125 CKT 1                /*6VINTHIL TP  230.0 - 6VINTHIL     230.0
 OPEN BRANCH FROM BUS 314119 TO BUS 314130 CKT 1                /*6NOKESVL     230.0 - 6BRISTER     230.0
 OPEN BRANCH FROM BUS 314913 TO BUS 314916 CKT 1                /*8LOUDOUN     500.0 - 8MORRSVL     500.0
 OPEN BUS 313712                                                /*6VINTHIL TP  230.0
 OPEN BUS 313716                                                /*6VINTHIL DP  230.0
 OPEN BUS 314119                                                /*6NOKESVL     230.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
314212 to 314150 ckt 1
314150 to 939260 ckt 1
314902 to 314914 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314911 to 314922 ckt 1
314914 to 314918 ckt 1
314916 to 314913 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314919 to 314904 ckt 1
314934 to 314916 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC100.11 %984.18B985.2948.69
GD1DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 567_SRT-A
OPAC117.72 %934.92B1100.6287.98
GD1DVP
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
OPAC119.65 %663.64B794.0547.33
GD1DVP
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC103.74 %984.18B1020.9648.69
GD1DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
DVP_P1-2: LN 557_SRT-S
OPAC108.08 %879.84B950.9478.65
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Base Case
OPAC120.66 %678.68A818.89161.31
GD1DVP
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
OPAC110.61 %663.64B734.0447.27
GD1DVP
6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 2 transformer
DVP_P1-2: LN 574_SRT-S_SENS
OPAC103.88 %889.43B923.9745.9
GD1DVP
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
OPAC117.46 %678.68B797.1663.39
GD1DVP
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC103.68 %984.18B1020.4248.69
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Base Case
OPAC104.12 %3220.44A3352.99166.38
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC136.21 %2442.12B3326.4257.42
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC115.81 %4070.2B4713.59247.5
GD1DVP
8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
OPAC113.6 %3220.44B3658.56158.22
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
OPAC126.88 %1058.16B1342.5561.92
GD1DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC106.42 %2442.12B2598.93147.82
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
OPAC105.3 %3220.44B3390.97137.93

Details for 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.11 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:985.29
MW Contribution:48.69
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:96.98 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:954.41
MW Contribution:45.0
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.332941176470588240.283
961672AG1-007 E
Adder
0.188235294117647060.16
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
963041AG1-153 C
Adder
1.9482352941176471.656
963042AG1-153 E
Adder
2.92235294117647062.484
966621AG1-532 C
Adder
0.61294117647058830.521
966622AG1-532 E
Adder
0.408235294117647030.347
3145413WATKINS
Adder
0.26470588235294120.225
3145723EMPORIA
Adder
0.185882352941176470.158
3151311EDGECMA
Adder
5.5117647058823534.685
918492AA1-063AE OP
Adder
1.59411764705882361.355
918532AA1-067 E
Adder
0.251764705882352950.214
919692AA2-053 E OP
Adder
1.64941176470588241.402
920042AA2-088 E OP
Adder
4.0811764705882353.469
925785AC1-054 E
Adder
1.2082352941176471.027
927146AC1-208 E
Adder
1.51.275
934521AD1-076 C
Adder
4.377647058823533.721
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
944011AF1-069 C
Adder
4.6141176470588243.922
944012AF1-069 E
Adder
1.7917647058823531.523
960081AF2-299 C
Adder
0.81647058823529410.694
960082AF2-299 E
Adder
0.54470588235294130.463
316141AB2-099 E
Adder
0.095294117647058830.081
900672V4-068 E
Adder
0.136470588235294120.116
917342Z2-044 E
Adder
0.215294117647058830.183
922923AB1-081 E OP
Adder
1.321.122
923263AB1-132 E OP
Adder
2.582.193
923573AB1-173 E OP
Adder
1.36823529411764721.163
924162AB2-060 E OP
Adder
1.3117647058823531.115
924302AB2-077 E O1
Adder
0.41176470588235290.35
924312AB2-078 E O1
Adder
0.41176470588235290.35
924322AB2-079 E O1
Adder
0.41176470588235290.35
940492AE2-034 E
Adder
1.09058823529411760.927
941031AE2-094 C
Adder
14.12000000000000112.002
941032AE2-094 E
Adder
6.3247058823529425.376
946281AF1-292 C
Adder
0.67529411764705880.574
946282AF1-292 E
Adder
0.45058823529411770.383
957481AF2-042 C
Adder
17.0152941176470614.463
957482AF2-042 E
Adder
11.3435294117647069.642
957861AF2-080 C
Adder
2.7023529411764712.297
957862AF2-080 E
Adder
1.19764705882352951.018
3145393UNCAMP
Adder
2.3247058823529411.976
916042Z1-036 E
Adder
9.9682352941176488.473
938771AE1-103 C
Adder
1.11764705882352940.95
938772AE1-103 E
Adder
1.5435294117647061.312
3143316POE
50/50
1.0861.086
3145256KINGFORK
Adder
0.357647058823529430.304
3145506HICKORY
Adder
0.72352941176470590.615
3150651CHESTF6
50/50
21.89721.897
3150731STONECA
50/50
4.5124.512
3150761HOPPOLC
50/50
1.0021.002
3150771HOPHCF1
50/50
1.5941.594
3150781HOPHCF2
50/50
1.5941.594
3150791HOPHCF3
50/50
1.5941.594
3150801HOPHCF4
50/50
2.4192.419
3150831SPRUNCA
Adder
2.6776470588235292.276
3150841SPRUNCB
Adder
2.6776470588235292.276
926662AC1-147 E
Adder
0.452941176470588240.385
926755AC1-161 E
Adder
3.78588235294117673.218
927226AC1-216 E
Adder
4.122352941176473.504
935112AD1-144 E
Adder
0.33176470588235290.282
942341AE2-247 C
Adder
0.68470588235294120.582
942342AE2-247 E
Adder
0.94470588235294130.803
943461AF1-017 C
Adder
0.61882352941176480.526
943462AF1-017 E
Adder
1.00941176470588250.858
943612AF1-032 E
Adder
0.320.272
316132AB2-190 C
50/50
2.4122.412
913392Y1-086 E
Adder
0.74470588235294120.633
916192Z1-068 E
Adder
0.63294117647058830.538
923832AB2-022 E
Adder
0.421176470588235260.358
923852AB2-025 E
Adder
0.6317647058823530.537
939312AE1-162 E
Adder
0.5717647058823530.486
946262AF1-291 E
50/50
1.6321.632
957492AF2-043 E
Adder
0.49294117647058820.419
901082W1-029 E
Adder
10.9870588235294139.339
917122Z2-027 E
Adder
0.457647058823529460.389
925332AB2-190 E
50/50
4.6914.691
925522AC1-027 E
Adder
0.410588235294117640.349
942001AE2-212 C
50/50
2.1112.111
942002AE2-212 E
50/50
1.4081.408
957871AF2-081 C
Adder
3.34117647058823542.84
957872AF2-081 E
Adder
1.4317647058823531.217
958161AF2-110 C
Adder
0.51764705882352950.44
958162AF2-110 E
Adder
0.82470588235294120.701
917512Z2-088 E OP1
Adder
1.73411764705882351.474
926071AC1-086 C
Adder
8.8647058823529427.535
926072AC1-086 E
Adder
4.0352941176470593.43
927021AC1-189 C
Adder
2.97529411764705862.529
927022AC1-189 E
Adder
1.48235294117647071.26
933291AC2-141 C
Adder
8.8694117647058827.539
933292AC2-141 E
Adder
3.78588235294117673.218
934621AD1-088 C
Adder
2.86941176470588262.439
934622AD1-088 E
Adder
1.38117647058823521.174
939411AE1-173 C
Adder
31.5352941176470626.805
939412AE1-173 E
Adder
21.0235294117647117.87
934012AD1-025 E
Adder
5.3364705882352944.536
933981AD1-022 C
Adder
3.162.686
933982AD1-022 E
Adder
1.721.462
962572AG1-106 E
Adder
0.50117647058823530.426
962571AG1-106 C
Adder
1.14705882352941170.975
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
3146326AYDLETT TAP
Adder
0.455294117647058850.387
316240AF1-291 C
50/50
2.4482.448
316263AC1-034 C
Adder
2.3517647058823531.999
316274AC1-208 C
Adder
3.3788235294117652.872
917332KELFORD E
Adder
0.61411764705882350.522
924516AB2-100 E1
Adder
1.36823529411764721.163
924517AB2-100 E2
Adder
1.36823529411764721.163
925595AC1-034 E
Adder
1.77411764705882361.508
926206AC1-098 E
Adder
1.35999999999999991.156
926214AC1-099 E
Adder
0.44941176470588240.382
934065AD1-033 E
Adder
1.6670588235294121.417
937226AE2-253 E
Adder
1.9482352941176471.656
918512AA1-065 E OP
Adder
2.04235294117647071.736
919153AA1-139 E2
Adder
1.36588235294117651.161
919152AA1-139 E1
Adder
1.36588235294117651.161
919710AA2-057 E
Adder
1.44823529411764731.231
920692AA2-178 E
Adder
1.4552941176470591.237
923994AB2-040_E
Adder
2.56588235294117652.181
924022AB2-043 E O1
Adder
1.60117647058823541.361
924152AB2-059 E OP
Adder
1.87058823529411791.59
924814AB2-134 E
Adder
6.7529411764705885.74
316083AB2-161 C
50/50
0.3210.321
316084AB2-161 E
50/50
3.213.21
925122AB2-169 E
Adder
2.04352941176470631.737
316088AB2-174 E
Adder
2.7588235294117652.345
932046AC2-012 E
Adder
4.4823529411764713.81
316311AC2-079 C
Adder
2.5717647058823532.186
932596AC2-079 E
Adder
4.1964705882352953.567
316381AD1-082 C
50/50
0.7330.733
934576AD1-082 E
50/50
2.5582.558
316349AD2-085 C
Adder
1.57882352941176471.342
936666AD2-085 E
Adder
2.5752941176470592.189
961611AG1-000B C
Adder
7.342352941176476.241
941591AE2-156 C
Adder
6.1141176470588245.197
944581AF1-123 C
Adder
15.03411764705882412.779
944582AF1-123 E
Adder
34.4258823529411829.262
944591AF1-124 C
Adder
15.08705882352941312.824
944592AF1-124 E
Adder
34.55058823529411429.368
944601AF1-125 C
Adder
14.80235294117647312.582
944602AF1-125 E
Adder
33.8847058823529428.802
964241AG1-285 C
Adder
3.85882352941176483.28
964242AG1-285 E
Adder
2.5717647058823532.186
3137643SOCKMAN
Adder
0.288235294117647030.245
932632AC2-084 E
Adder
1.20235294117647061.022
934321AD1-056 C
Adder
2.3988235294117652.039
934322AD1-056 E
Adder
1.30117647058823541.106
934331AD1-057 C
Adder
1.33882352941176451.138
934332AD1-057 E
Adder
0.69647058823529410.592
934501AD1-074 C
Adder
12.05529411764705810.247
934502AD1-074 E
Adder
6.1364705882352945.216
934511AD1-075 C
Adder
3.01411764705882362.562
934512AD1-075 E
Adder
1.53411764705882361.304
934612AD1-087 E
Adder
1.1117647058823530.945
935161AD1-151 C
50/50
9.0229.022
935162AD1-151 E
50/50
6.0156.015
935172AD1-152 E
Adder
1.6435294117647061.397
937482AD2-202 E
Adder
0.32588235294117650.277
938531AE1-072 C
Adder
5.8905882352941185.007
938532AE1-072 E
Adder
3.07058823529411742.61
939191AE1-149 C
50/50
7.1377.137
939192AE1-149 E
50/50
4.7584.758
940431AE2-027 C
Adder
7.0447058823529425.988
940432AE2-027 E
Adder
4.6964705882352943.992
940481AE2-033 C
Adder
8.6517647058823537.354
940482AE2-033 E
Adder
5.8329411764705884.958
940541AE2-040 C
Adder
1.56117647058823541.327
940641AE2-051 C
Adder
6.0952941176470595.181
940642AE2-051 E
Adder
4.0635294117647063.454
941101AE2-104 C
Adder
1.26941176470588221.079
941102AE2-104 E
Adder
2.0188235294117651.716
944641AF1-129 C
50/50
120.262120.262
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
NYPJM->LTFIMP_NY
CLTF
0.4360.436
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
WECLTFEXP_WEC->PJM
CLTF
0.140.14
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
TVALTFEXP_TVA->PJM
CLTF
1.561.56
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 567_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.72 %
Rating:934.92 MVA
Rating Type:B
MVA to Mitigate:1100.62
MW Contribution:87.98
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:124.05 %
Rating:934.92 MVA
Rating Type:B
MVA to Mitigate:1159.8
MW Contribution:89.42
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.250588235294117670.213
961942AG1-037 E
Adder
0.167058823529411760.142
3145413WATKINS
Adder
0.371764705882352940.316
918492AA1-063AE OP
Adder
1.9235294117647061.635
919692AA2-053 E OP
Adder
1.9247058823529411.636
920042AA2-088 E OP
Adder
5.4247058823529414.611
934521AD1-076 C
Adder
6.4588235294117655.49
934522AD1-076 E
Adder
3.2917647058823532.798
943172AE2-346 E
Adder
0.30.255
316141AB2-099 E
Adder
0.124705882352941180.106
900672V4-068 E
Adder
0.178823529411764710.152
923263AB1-132 E OP
Adder
2.76588235294117672.351
940492AE2-034 E
Adder
1.67529411764705881.424
3145393UNCAMP
Adder
3.34588235294117632.844
916042Z1-036 E
Adder
16.12117647058823513.703
938771AE1-103 C
Adder
1.63411764705882371.389
938772AE1-103 E
Adder
2.25764705882352961.919
3141843SHACKLE
50/50
0.6030.603
3143316POE
Adder
0.72470588235294120.616
3145256KINGFORK
Adder
0.64941176470588250.552
3145506HICKORY
Adder
1.3035294117647061.108
3150601CHESTF5
Adder
61.6852.428
3150651CHESTF6
Adder
10.5635294117647058.979
3150731STONECA
Adder
5.1505882352941184.378
3150831SPRUNCA
Adder
4.643.944
3150841SPRUNCB
Adder
4.643.944
3150921YORKTN3
Adder
101.5176470588235486.29
925865AC1-065 E
50/50
18.90818.908
926412AC1-112 E
Adder
0.95058823529411770.808
926472AC1-118 E
Adder
1.07411764705882360.913
926662AC1-147 E
Adder
0.80941176470588230.688
926755AC1-161 E
Adder
7.7070588235294126.551
927226AC1-216 E
Adder
5.5894117647058834.751
934392AD1-063 E
50/50
1.2811.281
935112AD1-144 E
Adder
0.60235294117647060.512
936582AD2-073 E
Adder
1.1482352941176470.976
936591AD2-074 C
50/50
6.2326.232
936592AD2-074 E
50/50
10.16810.168
942341AE2-247 C
Adder
0.88823529411764710.755
942342AE2-247 E
Adder
1.22588235294117661.042
943461AF1-017 C
Adder
0.80352941176470590.683
943462AF1-017 E
Adder
1.31058823529411781.114
943612AF1-032 E
Adder
0.5564705882352940.473
943741AF1-042 C
50/50
3.2613.261
943742AF1-042 E
50/50
5.3215.321
944491AF1-114 C
Adder
5.0717647058823534.311
944492AF1-114 E
Adder
7.0035294117647065.953
961951AG1-038 C
50/50
3.6043.604
961952AG1-038 E
50/50
4.9774.977
966661AG1-536 C
50/50
6.0266.026
966662AG1-536 E
50/50
8.0978.097
316075AC2-137 C
50/50
0.4510.451
316076AC2-137 E
50/50
1.5851.585
316078AC2-138 E
Adder
1.04235294117647070.886
316156AD2-030 C
50/50
0.4250.425
316157AD2-030 E
50/50
1.331.33
913392Y1-086 E
Adder
1.29176470588235311.098
916192Z1-068 E
Adder
1.13647058823529410.966
923832AB2-022 E
Adder
0.72941176470588230.62
923842AB2-024 E
50/50
2.2272.227
923852AB2-025 E
Adder
0.53647058823529410.456
930122AB1-027 E
Adder
1.1682352941176470.993
939312AE1-162 E
Adder
0.95764705882352940.814
946262AF1-291 E
Adder
0.81058823529411760.689
957492AF2-043 E
Adder
0.85647058823529410.728
957601AF2-054 C
50/50
2.372.37
957602AF2-054 E
50/50
1.581.58
962861AG1-135 C
50/50
6.7996.799
962862AG1-135 E
50/50
4.5334.533
962962AG1-145 E
50/50
1.5371.537
963611AG1-210 C
Adder
0.74470588235294120.633
963612AG1-210 E
Adder
1.11764705882352940.95
964211AG1-282 C
50/50
2.3232.323
964212AG1-282 E
50/50
1.5491.549
901082W1-029 E
Adder
18.5929411764705915.804
917122Z2-027 E
Adder
0.78588235294117660.668
925332AB2-190 E
Adder
5.91411764705882355.027
925522AC1-027 E
Adder
0.73647058823529410.626
942001AE2-212 C
Adder
1.18941176470588221.011
942002AE2-212 E
Adder
0.79294117647058830.674
957832AF2-077 E
Adder
1.39411764705882371.185
957871AF2-081 C
Adder
5.94117647058823555.05
957872AF2-081 E
Adder
2.5458823529411772.164
957971AF2-091 C
Adder
1.7247058823529411.466
957972AF2-091 E
Adder
2.38117647058823542.024
958161AF2-110 C
Adder
0.81411764705882350.692
958162AF2-110 E
Adder
1.29411764705882361.1
3138116ELKO L286
50/50
1.6531.653
3141813NORNECK
Adder
0.99176470588235290.843
926071AC1-086 C
Adder
9.502352941176478.077
926072AC1-086 E
Adder
4.3247058823529423.676
933291AC2-141 C
Adder
18.0552941176470615.347
933292AC2-141 E
Adder
7.7070588235294126.551
939411AE1-173 C
Adder
43.0494117647058836.592
939412AE1-173 E
Adder
28.724.395
934012AD1-025 E
Adder
7.2364705882352946.151
933981AD1-022 C
Adder
4.5705882352941173.885
933982AD1-022 E
Adder
2.48823529411764752.115
962572AG1-106 E
Adder
0.53764705882352950.457
962571AG1-106 C
Adder
1.22941176470588221.045
3130536PAPERMILL
50/50
8.178.17
3145946PLYMOUTH TP
Adder
0.171764705882352930.146
3146326AYDLETT TAP
Adder
0.80352941176470590.683
316059AD1-063 C
50/50
0.3140.314
316159AE1-175 C
50/50
0.4180.418
316160AE1-175 E
50/50
1.2681.268
316169AC1-164 GEN
50/50
59.62859.628
316240AF1-291 C
Adder
1.21647058823529421.034
316314AB2-024 C
50/50
0.3640.364
316382AG1-145 C
50/50
0.3770.377
917332KELFORD E
Adder
0.78588235294117660.668
924516AB2-100 E1
Adder
1.31411764705882361.117
924517AB2-100 E2
Adder
1.31411764705882361.117
926785AC1-164_E
50/50
26.78926.789
934065AD1-033 E
Adder
3.0082352941176472.557
937226AE2-253 E
Adder
3.48117647058823552.959
939611AE1-191 C
50/50
1.5481.548
939612AE1-191 E
50/50
6.4276.427
316201AC1-065 C
50/50
1.8491.849
316404AE1-155 C
50/50
2.3762.376
939246AE1-155 E
50/50
9.7559.755
918512AA1-065 E OP
Adder
2.78823529411764742.37
919153AA1-139 E2
Adder
2.4294117647058822.065
919152AA1-139 E1
Adder
2.4294117647058822.065
920692AA2-178 E
Adder
2.23411764705882381.899
924814AB2-134 E
Adder
9.155294117647067.782
316084AB2-161 E
Adder
3.2882352941176472.795
925122AB2-169 E
Adder
2.8305882352941182.406
932046AC2-012 E
Adder
8.0047058823529426.804
316311AC2-079 C
Adder
3.4117647058823532.9
932596AC2-079 E
Adder
5.5670588235294124.732
316280AD1-041 C
50/50
0.9810.981
934146AD1-041 E
50/50
4.0174.017
934576AD1-082 E
Adder
2.622.227
316349AD2-085 C
Adder
2.0482352941176471.741
936666AD2-085 E
Adder
3.34117647058823542.84
961611AG1-000B C
Adder
11.3023529411764719.607
941591AE2-156 C
Adder
10.929411764705889.29
944581AF1-123 C
Adder
27.16823529411764723.093
944582AF1-123 E
Adder
62.2117647058823652.88
944591AF1-124 C
Adder
27.26470588235294223.175
944592AF1-124 E
Adder
62.43647058823529553.071
944601AF1-125 C
Adder
26.7494117647058822.737
944602AF1-125 E
Adder
61.2352941176470652.05
944631AF1-128 C
Adder
38.5941176470588232.805
958261AF2-120 C
50/50
7.0057.005
958262AF2-120 E
50/50
4.674.67
934501AD1-074 C
Adder
17.7847058823529415.117
934502AD1-074 E
Adder
9.0529411764705887.695
934511AD1-075 C
Adder
4.4458823529411773.779
934512AD1-075 E
Adder
2.2635294117647061.924
935161AD1-151 C
Adder
11.755294117647069.992
935162AD1-151 E
Adder
7.837647058823536.662
938531AE1-072 C
Adder
10.4258823529411768.862
938532AE1-072 E
Adder
5.4352941176470594.62
939191AE1-149 C
Adder
6.3788235294117655.422
939192AE1-149 E
Adder
4.2529411764705883.615
939601AE1-190 C
50/50
0.3840.384
939602AE1-190 E
50/50
1.6071.607
940431AE2-027 C
Adder
8.0564705882352946.848
940432AE2-027 E
Adder
5.3717647058823534.566
940481AE2-033 C
Adder
7.4635294117647066.344
940482AE2-033 E
Adder
5.0317647058823534.277
940541AE2-040 C
Adder
1.32705882352941161.128
940551AE2-041 C
50/50
8.5438.543
940641AE2-051 C
Adder
7.5435294117647066.412
940642AE2-051 E
Adder
5.0282352941176474.274
941101AE2-104 C
Adder
1.99529411764705891.696
941102AE2-104 E
Adder
3.1717647058823532.696
943471AF1-018 C
50/50
8.5438.543
944641AF1-129 C
Adder
58.0164705882352949.314
957191AF2-013 C
Adder
8.1011764705882366.886
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.8251.825
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.0931.093
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.8973.897
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.11329.113
G-007PJM->LTFIMP_G-007
CMTX_NF
1.1231.123
NYPJM->LTFIMP_NY
CLTF
0.5590.559
LGEELTFEXP_LGEE->PJM
CLTF
0.0680.068
WECLTFEXP_WEC->PJM
CLTF
0.0320.032
CPLELTFEXP_CPLE->PJM
CLTF
3.8353.835
TVALTFEXP_TVA->PJM
CLTF
1.2591.259
MECLTFEXP_MEC->PJM
CLTF
0.4280.428
LAGNLTFEXP_LAGN->PJM
CLTF
1.6451.645
SIGELTFEXP_SIGE->PJM
CLTF
0.0210.021
O66PJM->LTFIMP_O-066
CMTX_NF
7.1797.179

Details for 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:119.65 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:794.05
MW Contribution:47.33
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:118.19 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:784.36
MW Contribution:45.66
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3145393UNCAMP
Adder
1.761.496
916042Z1-036 E
Adder
8.517647058823537.24
938771AE1-103 C
Adder
0.86470588235294120.735
938772AE1-103 E
Adder
1.19411764705882351.015
3145256KINGFORK
Adder
0.360.306
3145506HICKORY
Adder
0.70117647058823530.596
3150601CHESTF5
50/50
79.76279.762
3150611CHESTG7
50/50
4.8674.867
3150621CHESTS7
50/50
2.2342.234
3150631CHESTG8
50/50
4.7894.789
3150641CHESTS8
50/50
2.4652.465
3150731STONECA
50/50
4.6744.674
3150761HOPPOLC
50/50
1.0381.038
3150771HOPHCF1
50/50
1.6511.651
3150781HOPHCF2
50/50
1.6511.651
3150791HOPHCF3
50/50
1.6511.651
3150801HOPHCF4
50/50
2.5062.506
3150921YORKTN3
Adder
49.1152941176470641.748
925865AC1-065 E
Adder
7.5929411764705886.454
926472AC1-118 E
Adder
0.40352941176470590.343
926662AC1-147 E
Adder
0.44705882352941180.38
926755AC1-161 E
Adder
3.96117647058823553.367
927226AC1-216 E
50/50
4.3534.353
934392AD1-063 E
Adder
0.50823529411764710.432
935112AD1-144 E
Adder
0.33411764705882350.284
936582AD2-073 E
Adder
0.43647058823529410.371
936591AD2-074 C
Adder
2.4564705882352942.088
936592AD2-074 E
Adder
4.00705882352941253.406
942341AE2-247 C
Adder
0.49647058823529410.422
942342AE2-247 E
Adder
0.68588235294117650.583
943461AF1-017 C
Adder
0.44941176470588240.382
943462AF1-017 E
Adder
0.73294117647058820.623
943612AF1-032 E
Adder
0.30.255
943741AF1-042 C
Adder
1.28470588235294141.092
943742AF1-042 E
Adder
2.09647058823529431.782
961951AG1-038 C
Adder
1.42000000000000021.207
961952AG1-038 E
Adder
1.96117647058823531.667
966661AG1-536 C
Adder
2.35294117647058832
966662AG1-536 E
Adder
3.16117647058823532.687
316076AC2-137 E
Adder
0.52823529411764710.449
316078AC2-138 E
Adder
0.40352941176470590.343
316132AB2-190 C
50/50
2.5252.525
316157AD2-030 E
Adder
0.53882352941176470.458
913392Y1-086 E
Adder
0.6917647058823530.588
916192Z1-068 E
Adder
0.620.527
923832AB2-022 E
Adder
0.39058823529411770.332
923842AB2-024 E
Adder
0.87294117647058820.742
939312AE1-162 E
Adder
0.60.51
957492AF2-043 E
Adder
0.46117647058823530.392
957601AF2-054 C
Adder
0.96117647058823530.817
957602AF2-054 E
Adder
0.64117647058823530.545
962861AG1-135 C
Adder
2.66117647058823532.262
962862AG1-135 E
Adder
1.77411764705882361.508
962962AG1-145 E
Adder
0.65882352941176480.56
963611AG1-210 C
Adder
0.288235294117647030.245
963612AG1-210 E
Adder
0.43294117647058820.368
964211AG1-282 C
Adder
0.89529411764705890.761
964212AG1-282 E
Adder
0.59647058823529410.507
901082W1-029 E
Adder
9.9247058823529428.436
917122Z2-027 E
Adder
0.420.357
925332AB2-190 E
50/50
4.9124.912
925522AC1-027 E
Adder
0.402352941176470640.342
957832AF2-077 E
Adder
0.61529411764705890.523
957871AF2-081 C
Adder
3.1905882352941182.712
957872AF2-081 E
Adder
1.36705882352941171.162
958161AF2-110 C
Adder
0.44117647058823530.375
958162AF2-110 E
Adder
0.70235294117647060.597
3138116ELKO L286
Adder
0.55176470588235290.469
3141813NORNECK
Adder
0.38352941176470590.326
933291AC2-141 C
Adder
9.287.888
933292AC2-141 E
Adder
3.96117647058823553.367
934011AD1-025 C
50/50
1.4651.465
934012AD1-025 E
50/50
5.6355.635
3130536PAPERMILL
Adder
3.2082352941176472.727
3146326AYDLETT TAP
Adder
0.431764705882352940.367
316160AE1-175 E
Adder
0.54352941176470590.462
316169AC1-164 GEN
50/50
22.41822.418
316369AC1-216 C
50/50
0.9040.904
926785AC1-164_E
50/50
10.07210.072
934065AD1-033 E
Adder
1.62117647058823521.378
937226AE2-253 E
Adder
1.86941176470588231.589
939612AE1-191 E
Adder
2.5917647058823532.203
939246AE1-155 E
Adder
3.80823529411764743.237
919153AA1-139 E2
Adder
1.30470588235294121.109
919152AA1-139 E1
Adder
1.30470588235294121.109
316033AB2-134 GEN
50/50
1.1851.185
924814AB2-134 E
50/50
7.137.13
316084AB2-161 E
Adder
1.92235294117647061.634
932046AC2-012 E
Adder
4.42705882352941153.763
316311AC2-079 C
Adder
1.90117647058823551.616
932596AC2-079 E
Adder
3.10117647058823562.636
934146AD1-041 E
Adder
1.621.377
934576AD1-082 E
Adder
1.53176470588235311.302
316349AD2-085 C
Adder
1.14470588235294120.973
936666AD2-085 E
Adder
1.86823529411764721.588
961611AG1-000B C
Adder
7.877647058823536.696
941591AE2-156 C
Adder
6.0388235294117655.133
944581AF1-123 C
Adder
14.61529411764705912.423
944582AF1-123 E
Adder
33.4682352941176528.448
944591AF1-124 C
Adder
14.66705882352941312.467
944592AF1-124 E
Adder
33.5894117647058828.551
944601AF1-125 C
Adder
14.39058823529411812.232
944602AF1-125 E
Adder
32.9423529411764728.001
944631AF1-128 C
50/50
49.90849.908
958261AF2-120 C
Adder
2.73529411764705932.325
958262AF2-120 E
Adder
1.8235294117647061.55
935161AD1-151 C
50/50
9.4829.482
935162AD1-151 E
50/50
6.3216.321
938531AE1-072 C
Adder
5.5941176470588234.755
938532AE1-072 E
Adder
2.9164705882352942.479
939191AE1-149 C
Adder
3.84235294117647053.266
939192AE1-149 E
Adder
2.56235294117647072.178
939602AE1-190 E
Adder
0.64823529411764710.551
940431AE2-027 C
Adder
3.98470588235294133.387
940432AE2-027 E
Adder
2.65647058823529442.258
940551AE2-041 C
Adder
3.3882352941176472.88
941101AE2-104 C
Adder
1.08235294117647070.92
941102AE2-104 E
Adder
1.72117647058823551.463
943471AF1-018 C
Adder
3.3882352941176472.88
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.8090.809
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.4860.486
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.7321.732
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.85612.856
G-007PJM->LTFIMP_G-007
CMTX_NF
0.5680.568
NYPJM->LTFIMP_NY
CLTF
0.280.28
LGEELTFEXP_LGEE->PJM
CLTF
0.0310.031
WECLTFEXP_WEC->PJM
CLTF
0.0140.014
CPLELTFEXP_CPLE->PJM
CLTF
1.71.7
TVALTFEXP_TVA->PJM
CLTF
0.5590.559
MECLTFEXP_MEC->PJM
CLTF
0.1910.191
LAGNLTFEXP_LAGN->PJM
CLTF
0.7290.729
SIGELTFEXP_SIGE->PJM
CLTF
0.010.01
O66PJM->LTFIMP_O-066
CMTX_NF
3.6293.629

Details for 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.74 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1020.96
MW Contribution:48.69
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.61 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:990.18
MW Contribution:45.0
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.332941176470588240.283
961672AG1-007 E
Adder
0.188235294117647060.16
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
963041AG1-153 C
Adder
1.9482352941176471.656
963042AG1-153 E
Adder
2.92235294117647062.484
966621AG1-532 C
Adder
0.61294117647058830.521
966622AG1-532 E
Adder
0.408235294117647030.347
3145413WATKINS
Adder
0.26470588235294120.225
3145723EMPORIA
Adder
0.185882352941176470.158
3151311EDGECMA
Adder
5.5117647058823534.685
918492AA1-063AE OP
Adder
1.59411764705882361.355
918532AA1-067 E
Adder
0.251764705882352950.214
919692AA2-053 E OP
Adder
1.64941176470588241.402
920042AA2-088 E OP
Adder
4.0811764705882353.469
925785AC1-054 E
Adder
1.2082352941176471.027
927146AC1-208 E
Adder
1.51.275
934521AD1-076 C
Adder
4.377647058823533.721
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
944011AF1-069 C
Adder
4.6141176470588243.922
944012AF1-069 E
Adder
1.7917647058823531.523
960081AF2-299 C
Adder
0.81647058823529410.694
960082AF2-299 E
Adder
0.54470588235294130.463
316141AB2-099 E
Adder
0.095294117647058830.081
900672V4-068 E
Adder
0.136470588235294120.116
917342Z2-044 E
Adder
0.215294117647058830.183
922923AB1-081 E OP
Adder
1.321.122
923263AB1-132 E OP
Adder
2.582.193
923573AB1-173 E OP
Adder
1.36823529411764721.163
924162AB2-060 E OP
Adder
1.3117647058823531.115
924302AB2-077 E O1
Adder
0.41176470588235290.35
924312AB2-078 E O1
Adder
0.41176470588235290.35
924322AB2-079 E O1
Adder
0.41176470588235290.35
940492AE2-034 E
Adder
1.09058823529411760.927
941031AE2-094 C
Adder
14.12000000000000112.002
941032AE2-094 E
Adder
6.3247058823529425.376
946281AF1-292 C
Adder
0.67529411764705880.574
946282AF1-292 E
Adder
0.45058823529411770.383
957481AF2-042 C
Adder
17.0152941176470614.463
957482AF2-042 E
Adder
11.3435294117647069.642
957861AF2-080 C
Adder
2.7023529411764712.297
957862AF2-080 E
Adder
1.19764705882352951.018
3145393UNCAMP
Adder
2.3247058823529411.976
916042Z1-036 E
Adder
9.9682352941176488.473
938771AE1-103 C
Adder
1.11764705882352940.95
938772AE1-103 E
Adder
1.5435294117647061.312
3143316POE
50/50
1.0861.086
3145256KINGFORK
Adder
0.357647058823529430.304
3145506HICKORY
Adder
0.72352941176470590.615
3150651CHESTF6
50/50
21.89721.897
3150731STONECA
50/50
4.5124.512
3150761HOPPOLC
50/50
1.0021.002
3150771HOPHCF1
50/50
1.5941.594
3150781HOPHCF2
50/50
1.5941.594
3150791HOPHCF3
50/50
1.5941.594
3150801HOPHCF4
50/50
2.4192.419
3150831SPRUNCA
Adder
2.6776470588235292.276
3150841SPRUNCB
Adder
2.6776470588235292.276
926662AC1-147 E
Adder
0.452941176470588240.385
926755AC1-161 E
Adder
3.78588235294117673.218
927226AC1-216 E
Adder
4.122352941176473.504
935112AD1-144 E
Adder
0.33176470588235290.282
942341AE2-247 C
Adder
0.68470588235294120.582
942342AE2-247 E
Adder
0.94470588235294130.803
943461AF1-017 C
Adder
0.61882352941176480.526
943462AF1-017 E
Adder
1.00941176470588250.858
943612AF1-032 E
Adder
0.320.272
316132AB2-190 C
50/50
2.4122.412
913392Y1-086 E
Adder
0.74470588235294120.633
916192Z1-068 E
Adder
0.63294117647058830.538
923832AB2-022 E
Adder
0.421176470588235260.358
923852AB2-025 E
Adder
0.6317647058823530.537
939312AE1-162 E
Adder
0.5717647058823530.486
946262AF1-291 E
50/50
1.6321.632
957492AF2-043 E
Adder
0.49294117647058820.419
901082W1-029 E
Adder
10.9870588235294139.339
917122Z2-027 E
Adder
0.457647058823529460.389
925332AB2-190 E
50/50
4.6914.691
925522AC1-027 E
Adder
0.410588235294117640.349
942001AE2-212 C
50/50
2.1112.111
942002AE2-212 E
50/50
1.4081.408
957871AF2-081 C
Adder
3.34117647058823542.84
957872AF2-081 E
Adder
1.4317647058823531.217
958161AF2-110 C
Adder
0.51764705882352950.44
958162AF2-110 E
Adder
0.82470588235294120.701
917512Z2-088 E OP1
Adder
1.73411764705882351.474
926071AC1-086 C
Adder
8.8647058823529427.535
926072AC1-086 E
Adder
4.0352941176470593.43
927021AC1-189 C
Adder
2.97529411764705862.529
927022AC1-189 E
Adder
1.48235294117647071.26
933291AC2-141 C
Adder
8.8694117647058827.539
933292AC2-141 E
Adder
3.78588235294117673.218
934621AD1-088 C
Adder
2.86941176470588262.439
934622AD1-088 E
Adder
1.38117647058823521.174
939411AE1-173 C
Adder
31.5352941176470626.805
939412AE1-173 E
Adder
21.0235294117647117.87
934012AD1-025 E
Adder
5.3364705882352944.536
933981AD1-022 C
Adder
3.162.686
933982AD1-022 E
Adder
1.721.462
962572AG1-106 E
Adder
0.50117647058823530.426
962571AG1-106 C
Adder
1.14705882352941170.975
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
3146326AYDLETT TAP
Adder
0.455294117647058850.387
316240AF1-291 C
50/50
2.4482.448
316263AC1-034 C
Adder
2.3517647058823531.999
316274AC1-208 C
Adder
3.3788235294117652.872
917332KELFORD E
Adder
0.61411764705882350.522
924516AB2-100 E1
Adder
1.36823529411764721.163
924517AB2-100 E2
Adder
1.36823529411764721.163
925595AC1-034 E
Adder
1.77411764705882361.508
926206AC1-098 E
Adder
1.35999999999999991.156
926214AC1-099 E
Adder
0.44941176470588240.382
934065AD1-033 E
Adder
1.6670588235294121.417
937226AE2-253 E
Adder
1.9482352941176471.656
918512AA1-065 E OP
Adder
2.04235294117647071.736
919153AA1-139 E2
Adder
1.36588235294117651.161
919152AA1-139 E1
Adder
1.36588235294117651.161
919710AA2-057 E
Adder
1.44823529411764731.231
920692AA2-178 E
Adder
1.4552941176470591.237
923994AB2-040_E
Adder
2.56588235294117652.181
924022AB2-043 E O1
Adder
1.60117647058823541.361
924152AB2-059 E OP
Adder
1.87058823529411791.59
924814AB2-134 E
Adder
6.7529411764705885.74
316083AB2-161 C
50/50
0.3210.321
316084AB2-161 E
50/50
3.213.21
925122AB2-169 E
Adder
2.04352941176470631.737
316088AB2-174 E
Adder
2.7588235294117652.345
932046AC2-012 E
Adder
4.4823529411764713.81
316311AC2-079 C
Adder
2.5717647058823532.186
932596AC2-079 E
Adder
4.1964705882352953.567
316381AD1-082 C
50/50
0.7330.733
934576AD1-082 E
50/50
2.5582.558
316349AD2-085 C
Adder
1.57882352941176471.342
936666AD2-085 E
Adder
2.5752941176470592.189
961611AG1-000B C
Adder
7.342352941176476.241
941591AE2-156 C
Adder
6.1141176470588245.197
944581AF1-123 C
Adder
15.03411764705882412.779
944582AF1-123 E
Adder
34.4258823529411829.262
944591AF1-124 C
Adder
15.08705882352941312.824
944592AF1-124 E
Adder
34.55058823529411429.368
944601AF1-125 C
Adder
14.80235294117647312.582
944602AF1-125 E
Adder
33.8847058823529428.802
964241AG1-285 C
Adder
3.85882352941176483.28
964242AG1-285 E
Adder
2.5717647058823532.186
3137643SOCKMAN
Adder
0.288235294117647030.245
932632AC2-084 E
Adder
1.20235294117647061.022
934321AD1-056 C
Adder
2.3988235294117652.039
934322AD1-056 E
Adder
1.30117647058823541.106
934331AD1-057 C
Adder
1.33882352941176451.138
934332AD1-057 E
Adder
0.69647058823529410.592
934501AD1-074 C
Adder
12.05529411764705810.247
934502AD1-074 E
Adder
6.1364705882352945.216
934511AD1-075 C
Adder
3.01411764705882362.562
934512AD1-075 E
Adder
1.53411764705882361.304
934612AD1-087 E
Adder
1.1117647058823530.945
935161AD1-151 C
50/50
9.0229.022
935162AD1-151 E
50/50
6.0156.015
935172AD1-152 E
Adder
1.6435294117647061.397
937482AD2-202 E
Adder
0.32588235294117650.277
938531AE1-072 C
Adder
5.8905882352941185.007
938532AE1-072 E
Adder
3.07058823529411742.61
939191AE1-149 C
50/50
7.1377.137
939192AE1-149 E
50/50
4.7584.758
940431AE2-027 C
Adder
7.0447058823529425.988
940432AE2-027 E
Adder
4.6964705882352943.992
940481AE2-033 C
Adder
8.6517647058823537.354
940482AE2-033 E
Adder
5.8329411764705884.958
940541AE2-040 C
Adder
1.56117647058823541.327
940641AE2-051 C
Adder
6.0952941176470595.181
940642AE2-051 E
Adder
4.0635294117647063.454
941101AE2-104 C
Adder
1.26941176470588221.079
941102AE2-104 E
Adder
2.0188235294117651.716
944641AF1-129 C
50/50
120.262120.262
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
NYPJM->LTFIMP_NY
CLTF
0.4360.436
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
WECLTFEXP_WEC->PJM
CLTF
0.140.14
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
TVALTFEXP_TVA->PJM
CLTF
1.561.56
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.08 %
Rating:879.84 MVA
Rating Type:B
MVA to Mitigate:950.94
MW Contribution:78.65
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:132.71 %
Rating:879.84 MVA
Rating Type:B
MVA to Mitigate:1167.6
MW Contribution:88.24
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.238823529411764740.203
961942AG1-037 E
Adder
0.158823529411764720.135
966621AG1-532 C
Adder
0.63647058823529420.541
966622AG1-532 E
Adder
0.424705882352941160.361
3145413WATKINS
Adder
0.348235294117647030.296
3145723EMPORIA
Adder
0.195294117647058840.166
918492AA1-063AE OP
Adder
1.88000000000000011.598
920042AA2-088 E OP
Adder
5.164.386
934521AD1-076 C
Adder
5.9847058823529415.087
934522AD1-076 E
Adder
3.0505882352941182.593
943172AE2-346 E
Adder
0.28588235294117650.243
944011AF1-069 C
Adder
2.9870588235294122.539
960081AF2-299 C
Adder
0.84823529411764710.721
960082AF2-299 E
Adder
0.56588235294117650.481
316141AB2-099 E
Adder
0.118823529411764720.101
900672V4-068 E
Adder
0.170588235294117650.145
923263AB1-132 E OP
Adder
2.78941176470588252.371
923573AB1-173 E OP
Adder
1.4764705882352941.255
940492AE2-034 E
Adder
1.53882352941176471.308
941031AE2-094 C
Adder
15.84470588235294213.468
941032AE2-094 E
Adder
7.0964705882352946.032
946281AF1-292 C
Adder
0.70235294117647060.597
946282AF1-292 E
Adder
0.46823529411764710.398
3145393UNCAMP
Adder
3.11647058823529432.649
916042Z1-036 E
Adder
14.65058823529411712.453
938771AE1-103 C
Adder
1.5164705882352941.289
938772AE1-103 E
Adder
2.09411764705882361.78
3142296MT RD221
50/50
0.1260.126
3142366NRTHEST
50/50
0.1640.164
3143316POE
Adder
0.84470588235294120.718
3145256KINGFORK
Adder
0.56470588235294120.48
3145506HICKORY
Adder
1.16588235294117660.991
3150501FOURRIVERG
50/50
4.254.25
3150601CHESTF5
Adder
47.7840.613
3150651CHESTF6
Adder
13.78941176470588211.721
3150671DARBY 1
50/50
2.2042.204
3150681DARBY 2
50/50
2.2072.207
3150691DARBY 3
50/50
2.2142.214
3150701DARBY 4
50/50
2.2172.217
3150731STONECA
Adder
4.9341176470588244.194
3150831SPRUNCA
Adder
6.84941176470588255.822
3150841SPRUNCB
Adder
6.84941176470588255.822
3150921YORKTN3
Adder
72.7576470588235461.844
925865AC1-065 E
Adder
11.2529411764705879.565
926412AC1-112 E
50/50
1.0221.022
926472AC1-118 E
Adder
0.64470588235294120.548
926662AC1-147 E
Adder
0.72117647058823530.613
926755AC1-161 E
Adder
6.8564705882352955.828
927226AC1-216 E
Adder
5.1070588235294124.341
934392AD1-063 E
Adder
0.72470588235294120.616
934781AD1-105 C
50/50
1.0481.048
934782AD1-105 E
50/50
4.3454.345
935112AD1-144 E
Adder
0.52352941176470590.445
936582AD2-073 E
Adder
0.67176470588235290.571
936591AD2-074 C
Adder
3.63882352941176463.093
936592AD2-074 E
Adder
5.9376470588235295.047
942341AE2-247 C
Adder
0.84705882352941180.72
942342AE2-247 E
Adder
1.16941176470588240.994
943461AF1-017 C
Adder
0.76588235294117660.651
943462AF1-017 E
Adder
1.24941176470588241.062
943612AF1-032 E
Adder
0.49647058823529410.422
943741AF1-042 C
Adder
1.90352941176470611.618
943742AF1-042 E
Adder
3.10705882352941172.641
944491AF1-114 C
Adder
3.30470588235294162.809
944492AF1-114 E
Adder
4.5635294117647063.879
961951AG1-038 C
Adder
2.1047058823529411.789
961952AG1-038 E
Adder
2.9058823529411772.47
966661AG1-536 C
Adder
3.50352941176470622.978
966662AG1-536 E
Adder
4.7070588235294134.001
966871AG1-558 C
50/50
2.4052.405
966872AG1-558 E
50/50
1.2121.212
966881AG1-559 C
Adder
1.37764705882352941.171
966882AG1-559 E
Adder
0.69411764705882350.59
316076AC2-137 E
Adder
1.04588235294117650.889
316078AC2-138 E
Adder
0.60352941176470590.513
316157AD2-030 E
Adder
0.78705882352941180.669
913392Y1-086 E
Adder
1.160.986
916192Z1-068 E
Adder
1.0152941176470590.863
923832AB2-022 E
Adder
0.65529411764705890.557
923842AB2-024 E
Adder
1.2282352941176471.044
923852AB2-025 E
Adder
0.58235294117647060.495
930122AB1-027 E
50/50
1.2571.257
938552AE1-074 E
Adder
0.81882352941176460.696
939312AE1-162 E
Adder
0.84352941176470590.717
946262AF1-291 E
Adder
1.04588235294117650.889
957492AF2-043 E
Adder
0.76352941176470590.649
957601AF2-054 C
Adder
1.40235294117647061.192
957602AF2-054 E
Adder
0.93529411764705890.795
962861AG1-135 C
Adder
3.9564705882352943.363
962862AG1-135 E
Adder
2.63764705882352952.242
962962AG1-145 E
Adder
0.94000000000000010.799
963611AG1-210 C
Adder
0.431764705882352940.367
963612AG1-210 E
Adder
0.64705882352941180.55
964211AG1-282 C
Adder
1.32117647058823541.123
964212AG1-282 E
Adder
0.88117647058823530.749
901082W1-029 E
Adder
16.73529411764705814.225
917122Z2-027 E
Adder
0.70705882352941170.601
925332AB2-190 E
Adder
5.5094117647058834.683
925522AC1-027 E
Adder
0.65764705882352950.559
942001AE2-212 C
Adder
1.48117647058823531.259
942002AE2-212 E
Adder
0.98705882352941180.839
957832AF2-077 E
Adder
0.90470588235294120.769
957871AF2-081 C
Adder
5.3211764705882354.523
957872AF2-081 E
Adder
2.281.938
957971AF2-091 C
Adder
1.12352941176470590.955
957972AF2-091 E
Adder
1.5517647058823531.319
958161AF2-110 C
Adder
0.74235294117647070.631
958162AF2-110 E
Adder
1.181.003
3138116ELKO L286
Adder
1.09058823529411760.927
3141813NORNECK
Adder
0.57411764705882350.488
926071AC1-086 C
Adder
9.5835294117647068.146
926072AC1-086 E
Adder
4.36235294117647053.708
933291AC2-141 C
Adder
16.0623529411764713.653
933292AC2-141 E
Adder
6.8564705882352955.828
939411AE1-173 C
Adder
41.24705882352941435.06
939412AE1-173 E
Adder
27.4976470588235323.373
934012AD1-025 E
Adder
6.6117647058823535.62
927041AC1-191 C
50/50
9.6569.656
927042AC1-191 E
50/50
4.814.81
933981AD1-022 C
Adder
4.2529411764705883.615
933982AD1-022 E
Adder
2.3152941176470591.968
962572AG1-106 E
Adder
0.54235294117647060.461
962571AG1-106 C
Adder
1.241.054
3130536PAPERMILL
Adder
4.5270588235294123.848
3145946PLYMOUTH TP
Adder
0.158823529411764720.135
3146326AYDLETT TAP
Adder
0.720.612
316004AC1-112 C
50/50
0.2990.299
316160AE1-175 E
Adder
0.77529411764705890.659
316169AC1-164 GEN
Adder
29.68117647058823425.229
316233AE1-074 C
Adder
1.62470588235294121.381
316240AF1-291 C
Adder
1.56941176470588251.334
316312AB1-027 C
50/50
0.4790.479
924516AB2-100 E1
Adder
1.3717647058823531.166
924517AB2-100 E2
Adder
1.3717647058823531.166
926785AC1-164_E
Adder
13.3352941176470611.335
934065AD1-033 E
Adder
2.68823529411764732.285
937226AE2-253 E
Adder
3.1152941176470592.648
939612AE1-191 E
Adder
3.8152941176470593.243
315051AA1-145 CT1
50/50
4.4424.442
315052AA1-145 CT2
50/50
4.444.44
939246AE1-155 E
Adder
5.6705882352941184.82
918512AA1-065 E OP
Adder
2.62941176470588232.235
919153AA1-139 E2
Adder
2.1752941176470591.849
919152AA1-139 E1
Adder
2.1752941176470591.849
920692AA2-178 E
Adder
2.05294117647058851.745
923994AB2-040_E
Adder
2.76941176470588252.354
924814AB2-134 E
Adder
8.3647058823529427.11
316084AB2-161 E
Adder
3.34823529411764742.846
316088AB2-174 E
Adder
2.94235294117647062.501
932046AC2-012 E
Adder
7.1352941176470596.065
316311AC2-079 C
Adder
3.2352941176470592.75
932596AC2-079 E
Adder
5.284.488
934146AD1-041 E
Adder
2.38470588235294122.027
934576AD1-082 E
Adder
2.6682352941176472.268
316349AD2-085 C
Adder
1.95294117647058821.66
936666AD2-085 E
Adder
3.18705882352941172.709
961611AG1-000B C
Adder
10.0094117647058818.508
941591AE2-156 C
Adder
9.744705882352948.283
944581AF1-123 C
Adder
24.2847058823529420.642
944582AF1-123 E
Adder
55.6105882352941247.269
944591AF1-124 C
Adder
24.37176470588235620.716
944592AF1-124 E
Adder
55.81176470588235447.44
944601AF1-125 C
Adder
23.9117647058823520.325
944602AF1-125 E
Adder
54.7376470588235346.527
944631AF1-128 C
Adder
29.89647058823529225.412
958261AF2-120 C
Adder
4.07294117647058853.462
958262AF2-120 E
Adder
2.7152941176470592.308
934501AD1-074 C
Adder
16.4776470588235314.006
934502AD1-074 E
Adder
8.3882352941176477.13
934511AD1-075 C
Adder
4.1188235294117653.501
934512AD1-075 E
Adder
2.09647058823529431.782
935161AD1-151 C
Adder
10.8541176470588259.226
935162AD1-151 E
Adder
7.235294117647066.15
938531AE1-072 C
Adder
9.3411764705882367.94
938532AE1-072 E
Adder
4.8694117647058834.139
939191AE1-149 C
Adder
6.78235294117647055.765
939192AE1-149 E
Adder
4.5223529411764713.844
939261AE1-157 C
Adder
6.5811764705882365.594
939262AE1-157 E
Adder
3.56941176470588233.034
939602AE1-190 E
Adder
0.95411764705882360.811
940431AE2-027 C
Adder
9.175294117647067.799
940432AE2-027 E
Adder
6.1164705882352945.199
940481AE2-033 C
Adder
8.0647058823529436.855
940482AE2-033 E
Adder
5.4364705882352954.621
940541AE2-040 C
Adder
1.44117647058823551.225
940551AE2-041 C
Adder
4.8305882352941174.106
940641AE2-051 C
Adder
7.4376470588235296.322
940642AE2-051 E
Adder
4.9588235294117654.215
941101AE2-104 C
Adder
1.81764705882352941.545
941102AE2-104 E
Adder
2.89058823529411772.457
943471AF1-018 C
Adder
4.8305882352941174.106
944641AF1-129 C
Adder
75.7352941176470664.375
3150431FOUR RIVERA
50/50
2.7882.788
3150441FOUR RIVERB
50/50
2.7882.788
3150451FOUR RIVERC
50/50
3.4073.407
3150461FOUR RIVERD
50/50
2.7482.748
3150471FOUR RIVERE
50/50
2.7482.748
3150481FOUR RIVERF
50/50
3.3563.356
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7881.788
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.9732.973
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.04428.044
G-007PJM->LTFIMP_G-007
CMTX_NF
1.0691.069
NYPJM->LTFIMP_NY
CLTF
0.5450.545
CPLELTFEXP_CPLE->PJM
CLTF
3.7593.759
TVALTFEXP_TVA->PJM
CLTF
1.0611.061
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0350.035
MECLTFEXP_MEC->PJM
CLTF
0.2010.201
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0870.087
LAGNLTFEXP_LAGN->PJM
CLTF
1.4041.404
SIGELTFEXP_SIGE->PJM
CLTF
0.0060.006
O66PJM->LTFIMP_O-066
CMTX_NF
6.8436.843

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:120.66 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:818.89
MW Contribution:161.31
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
313526AB2-022 C
50/50
0.2360.236
3145506HICKORY
50/50
2.3082.308
913392Y1-086 E
50/50
1.3781.378
923832AB2-022 E
50/50
0.7780.778
917122Z2-027 E
Adder
0.69411764705882350.59
957871AF2-081 C
50/50
9.2149.214
957872AF2-081 E
50/50
3.9493.949
3146326AYDLETT TAP
50/50
1.1471.147
316185AD1-033 C
50/50
1.0081.008
316320Y1-086 C
50/50
0.1380.138
934065AD1-033 E
50/50
4.1134.113
937226AE2-253 E
50/50
5.6955.695
316017AA1-139 ULT1
50/50
0.9980.998
316018AA1-139 ULT2
50/50
0.9980.998
919153AA1-139 E2
50/50
3.7683.768
919152AA1-139 E1
50/50
3.7683.768
316388AE2-253 GEN
50/50
1.9151.915
944581AF1-123 C
50/50
49.8149.81
944582AF1-123 E
50/50
114.059114.059
944591AF1-124 C
50/50
49.98749.987
944592AF1-124 E
50/50
114.472114.472
944601AF1-125 C
50/50
49.04249.042
944602AF1-125 E
50/50
112.268112.268
938531AE1-072 C
50/50
15.22515.225
938532AE1-072 E
50/50
7.9377.937
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0480.048
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0560.056
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.1121.112
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.4850.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.0581.058
G-007ALTFEXP_G-007A->PJM
CMTX
0.0980.098
VTFLTFEXP_VFT->PJM
CMTX
0.2650.265
LGEELTFEXP_LGEE->PJM
CLTF
0.040.04
WECLTFEXP_WEC->PJM
CLTF
0.0220.022
CPLELTFEXP_CPLE->PJM
CLTF
0.0990.099
TVALTFEXP_TVA->PJM
CLTF
0.1110.111
MECLTFEXP_MEC->PJM
CLTF
0.110.11
LAGNLTFEXP_LAGN->PJM
CLTF
0.1390.139
SIGELTFEXP_SIGE->PJM
CLTF
0.0070.007

Details for 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:110.61 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:734.04
MW Contribution:47.27
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:110.43 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:732.86
MW Contribution:45.6
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3145393UNCAMP
Adder
1.75764705882352961.494
916042Z1-036 E
Adder
8.5047058823529427.229
938771AE1-103 C
Adder
0.86352941176470590.734
938772AE1-103 E
Adder
1.19294117647058821.014
3143096IRON208
50/50
1.1521.152
3145256KINGFORK
Adder
0.35882352941176470.305
3145506HICKORY
Adder
0.70.595
3150601CHESTF5
50/50
79.73479.734
3150611CHESTG7
50/50
4.8664.866
3150621CHESTS7
50/50
2.2332.233
3150631CHESTG8
50/50
4.7884.788
3150641CHESTS8
50/50
2.4642.464
3150731STONECA
Adder
4.6705882352941183.97
3150771HOPHCF1
50/50
1.651.65
3150781HOPHCF2
50/50
1.651.65
3150791HOPHCF3
50/50
1.651.65
3150801HOPHCF4
50/50
2.5042.504
3150921YORKTN3
Adder
49.06352941176470541.704
925865AC1-065 E
Adder
7.5847058823529416.447
926472AC1-118 E
Adder
0.402352941176470640.342
926662AC1-147 E
Adder
0.44705882352941180.38
926755AC1-161 E
Adder
3.9564705882352943.363
927226AC1-216 E
Adder
4.34941176470588253.697
934392AD1-063 E
Adder
0.50823529411764710.432
935112AD1-144 E
Adder
0.332941176470588240.283
936582AD2-073 E
Adder
0.43647058823529410.371
936591AD2-074 C
Adder
2.45411764705882352.086
936592AD2-074 E
Adder
4.0035294117647063.403
942341AE2-247 C
Adder
0.495294117647058830.421
942342AE2-247 E
Adder
0.68470588235294120.582
943461AF1-017 C
Adder
0.448235294117647070.381
943462AF1-017 E
Adder
0.7317647058823530.622
943612AF1-032 E
Adder
0.30.255
943741AF1-042 C
Adder
1.28352941176470581.091
943742AF1-042 E
Adder
2.09529411764705881.781
961951AG1-038 C
Adder
1.41882352941176461.206
961952AG1-038 E
Adder
1.961.666
966661AG1-536 C
Adder
2.35058823529411761.998
966662AG1-536 E
Adder
3.1588235294117652.685
316076AC2-137 E
Adder
0.52823529411764710.449
316078AC2-138 E
Adder
0.40352941176470590.343
316157AD2-030 E
Adder
0.53882352941176470.458
913392Y1-086 E
Adder
0.69058823529411760.587
916192Z1-068 E
Adder
0.61882352941176480.526
923832AB2-022 E
Adder
0.38941176470588240.331
923842AB2-024 E
Adder
0.8717647058823530.741
939312AE1-162 E
Adder
0.60.51
957492AF2-043 E
Adder
0.46117647058823530.392
957601AF2-054 C
Adder
0.960.816
957602AF2-054 E
Adder
0.640.544
962861AG1-135 C
Adder
2.65764705882352952.259
962862AG1-135 E
Adder
1.7717647058823531.506
962962AG1-145 E
Adder
0.65764705882352950.559
963611AG1-210 C
Adder
0.288235294117647030.245
963612AG1-210 E
Adder
0.431764705882352940.367
964211AG1-282 C
Adder
0.89411764705882360.76
964212AG1-282 E
Adder
0.59647058823529410.507
901082W1-029 E
Adder
9.9105882352941178.424
917122Z2-027 E
Adder
0.420.357
925332AB2-190 E
Adder
4.9082352941176474.172
925522AC1-027 E
Adder
0.401176470588235360.341
957832AF2-077 E
Adder
0.61529411764705890.523
957871AF2-081 C
Adder
3.18588235294117662.708
957872AF2-081 E
Adder
1.36588235294117651.161
958161AF2-110 C
Adder
0.44117647058823530.375
958162AF2-110 E
Adder
0.70117647058823530.596
3138116ELKO L286
Adder
0.55058823529411770.468
3141813NORNECK
Adder
0.38352941176470590.326
933291AC2-141 C
Adder
9.2670588235294127.877
933292AC2-141 E
Adder
3.9564705882352943.363
934012AD1-025 E
Adder
5.6305882352941174.786
3130536PAPERMILL
Adder
3.20588235294117662.725
3146326AYDLETT TAP
Adder
0.430588235294117660.366
316160AE1-175 E
Adder
0.54235294117647060.461
316169AC1-164 GEN
Adder
22.40117647058823619.041
926785AC1-164_E
Adder
10.0635294117647078.554
934065AD1-033 E
Adder
1.61882352941176461.376
937226AE2-253 E
Adder
1.86705882352941191.587
939612AE1-191 E
Adder
2.58941176470588232.201
939246AE1-155 E
Adder
3.8047058823529413.234
919153AA1-139 E2
Adder
1.30235294117647071.107
919152AA1-139 E1
Adder
1.30235294117647071.107
924814AB2-134 E
Adder
7.1247058823529416.056
316084AB2-161 E
Adder
1.921.632
932046AC2-012 E
Adder
4.4211764705882353.758
316311AC2-079 C
Adder
1.89882352941176481.614
932596AC2-079 E
Adder
3.09764705882352942.633
934146AD1-041 E
Adder
1.61882352941176461.376
934576AD1-082 E
Adder
1.52941176470588251.3
316349AD2-085 C
Adder
1.1435294117647060.972
936666AD2-085 E
Adder
1.86588235294117651.586
961611AG1-000B C
Adder
7.8705882352941186.69
941591AE2-156 C
Adder
6.0305882352941185.126
944581AF1-123 C
Adder
14.5952941176470612.406
944582AF1-123 E
Adder
33.4223529411764728.409
944591AF1-124 C
Adder
14.64823529411764712.451
944592AF1-124 E
Adder
33.5435294117647128.512
944601AF1-125 C
Adder
14.37058823529411812.215
944602AF1-125 E
Adder
32.8976470588235327.963
944631AF1-128 C
50/50
49.89149.891
958261AF2-120 C
Adder
2.7317647058823532.322
958262AF2-120 E
Adder
1.82117647058823541.548
935161AD1-151 C
Adder
9.475294117647068.054
935162AD1-151 E
Adder
6.3164705882352945.369
938531AE1-072 C
Adder
5.58588235294117654.748
938532AE1-072 E
Adder
2.91176470588235332.475
939191AE1-149 C
Adder
3.83764705882352963.262
939192AE1-149 E
Adder
2.55882352941176452.175
939602AE1-190 E
Adder
0.64705882352941180.55
940431AE2-027 C
Adder
3.9788235294117653.382
940432AE2-027 E
Adder
2.6529411764705882.255
940551AE2-041 C
Adder
3.3847058823529412.877
941101AE2-104 C
Adder
1.08117647058823540.919
941102AE2-104 E
Adder
1.71882352941176491.461
943471AF1-018 C
Adder
3.3847058823529412.877
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.8060.806
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.3540.354
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.6811.681
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.77712.777
G-007PJM->LTFIMP_G-007
CMTX_NF
0.5760.576
NYPJM->LTFIMP_NY
CLTF
0.2840.284
LGEELTFEXP_LGEE->PJM
CLTF
0.0270.027
WECLTFEXP_WEC->PJM
CLTF
0.0120.012
CPLELTFEXP_CPLE->PJM
CLTF
1.6931.693
TVALTFEXP_TVA->PJM
CLTF
0.5480.548
MECLTFEXP_MEC->PJM
CLTF
0.1790.179
LAGNLTFEXP_LAGN->PJM
CLTF
0.7160.716
SIGELTFEXP_SIGE->PJM
CLTF
0.0090.009
O66PJM->LTFIMP_O-066
CMTX_NF
3.6813.681

Details for 6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 574_SRT-S_SENS
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.88 %
Rating:889.43 MVA
Rating Type:B
MVA to Mitigate:923.97
MW Contribution:45.9
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3141316ARNOLDS
50/50
0.150.15
3142296MT RD221
50/50
0.0710.071
3143316POE
Adder
0.47411764705882360.403
3145256KINGFORK
Adder
0.33176470588235290.282
3145506HICKORY
Adder
0.67999999999999990.578
3150331BIRCHWDA
50/50
21.96921.969
3150391LDYSMT3
50/50
6.7616.761
3150401LDYSMT4
50/50
6.7736.773
3150411LDYSMT5
50/50
6.7946.794
3150501FOURRIVERG
50/50
3.0343.034
3150601CHESTF5
Adder
28.20941176470588423.978
3150651CHESTF6
Adder
7.8352941176470596.66
3150731STONECA
Adder
2.8635294117647062.434
3150831SPRUNCA
Adder
3.83529411764705853.26
3150841SPRUNCB
Adder
3.83529411764705853.26
3150921YORKTN3
Adder
44.5435294117647137.862
925865AC1-065 E
Adder
7.446.324
926412AC1-112 E
Adder
0.59882352941176480.509
926472AC1-118 E
Adder
0.61882352941176480.526
926662AC1-147 E
Adder
0.421176470588235260.358
926755AC1-161 E
Adder
4.0258823529411773.422
927226AC1-216 E
Adder
2.9835294117647062.536
934392AD1-063 E
Adder
0.480.408
934781AD1-105 C
50/50
0.7810.781
934782AD1-105 E
50/50
3.2413.241
935112AD1-144 E
Adder
0.30705882352941180.261
936582AD2-073 E
Adder
0.58352941176470590.496
936591AD2-074 C
Adder
2.71764705882352952.31
936592AD2-074 E
Adder
4.4352941176470593.77
942341AE2-247 C
Adder
0.48941176470588230.416
942342AE2-247 E
Adder
0.67529411764705880.574
943461AF1-017 C
Adder
0.44235294117647060.376
943462AF1-017 E
Adder
0.72235294117647060.614
943612AF1-032 E
Adder
0.289411764705882370.246
943741AF1-042 C
Adder
1.42235294117647081.209
943742AF1-042 E
Adder
2.321.972
944491AF1-114 C
Adder
4.0705882352941173.46
944492AF1-114 E
Adder
5.6211764705882354.778
961951AG1-038 C
Adder
1.57176470588235321.336
961952AG1-038 E
Adder
2.17058823529411751.845
966661AG1-536 C
Adder
2.7023529411764712.297
966662AG1-536 E
Adder
3.63176470588235353.087
966871AG1-558 C
50/50
1.4381.438
966872AG1-558 E
50/50
0.7240.724
966881AG1-559 C
50/50
2.7772.777
966882AG1-559 E
50/50
1.3991.399
316076AC2-137 E
Adder
0.62823529411764710.534
316078AC2-138 E
Adder
0.47882352941176470.407
316157AD2-030 E
Adder
0.52941176470588240.45
913392Y1-086 E
Adder
0.6764705882352940.575
916192Z1-068 E
Adder
0.59294117647058830.504
923832AB2-022 E
Adder
0.38235294117647060.325
923842AB2-024 E
Adder
0.80588235294117660.685
930122AB1-027 E
Adder
0.73529411764705890.625
938552AE1-074 E
Adder
0.44235294117647060.376
939312AE1-162 E
Adder
0.494117647058823550.42
946262AF1-291 E
Adder
0.59411764705882350.505
957492AF2-043 E
Adder
0.44588235294117650.379
957601AF2-054 C
Adder
0.9435294117647060.802
957602AF2-054 E
Adder
0.62941176470588240.535
962861AG1-135 C
Adder
3.02941176470588272.575
962862AG1-135 E
Adder
2.021.717
962962AG1-145 E
Adder
0.57764705882352940.491
963611AG1-210 C
Adder
0.34235294117647060.291
963612AG1-210 E
Adder
0.51294117647058820.436
964211AG1-282 C
Adder
1.02470588235294110.871
964212AG1-282 E
Adder
0.68352941176470580.581
917122Z2-027 E
Adder
0.41176470588235290.35
925332AB2-190 E
Adder
3.2094117647058832.728
925522AC1-027 E
Adder
0.38352941176470590.326
942001AE2-212 C
Adder
0.83647058823529410.711
942002AE2-212 E
Adder
0.55764705882352940.474
957832AF2-077 E
Adder
0.58117647058823530.494
957871AF2-081 C
Adder
3.1047058823529412.639
957872AF2-081 E
Adder
1.33058823529411761.131
957971AF2-091 C
Adder
1.3835294117647061.176
957972AF2-091 E
Adder
1.9117647058823531.625
958161AF2-110 C
Adder
0.431764705882352940.367
958162AF2-110 E
Adder
0.68588235294117650.583
3138116ELKO L286
Adder
0.65411764705882360.556
3141813NORNECK
Adder
0.456470588235294130.388
933291AC2-141 C
Adder
9.4305882352941198.016
933292AC2-141 E
Adder
4.0258823529411773.422
934012AD1-025 E
Adder
3.86235294117647053.283
927041AC1-191 C
50/50
5.7735.773
927042AC1-191 E
50/50
2.8762.876
3130536PAPERMILL
Adder
2.9788235294117652.532
3146326AYDLETT TAP
Adder
0.420.357
316160AE1-175 E
Adder
0.476470588235294150.405
316169AC1-164 GEN
Adder
18.2823529411764715.54
316233AE1-074 C
Adder
0.87882352941176480.747
316240AF1-291 C
Adder
0.89058823529411770.757
926785AC1-164_E
Adder
8.2141176470588246.982
934065AD1-033 E
Adder
1.56941176470588251.334
937226AE2-253 E
Adder
1.81764705882352941.545
939612AE1-191 E
Adder
2.54117647058823562.16
3150371LDYSMT1
50/50
6.5036.503
3150381LDYSMT2
50/50
6.5876.587
315051AA1-145 CT1
50/50
4.0364.036
315052AA1-145 CT2
50/50
4.0344.034
939246AE1-155 E
Adder
4.3741176470588233.718
919153AA1-139 E2
Adder
1.26941176470588221.079
919152AA1-139 E1
Adder
1.26941176470588221.079
924814AB2-134 E
Adder
4.88705882352941154.154
316084AB2-161 E
Adder
1.91764705882352931.63
932046AC2-012 E
Adder
4.1682352941176483.543
316311AC2-079 C
Adder
1.8717647058823531.591
932596AC2-079 E
Adder
3.05411764705882362.596
934146AD1-041 E
Adder
1.58823529411764721.35
934576AD1-082 E
Adder
1.5282352941176471.299
316349AD2-085 C
Adder
1.1282352941176470.959
936666AD2-085 E
Adder
1.84117647058823521.565
961611AG1-000B C
Adder
5.8729411764705884.992
941591AE2-156 C
Adder
5.69058823529411754.837
944581AF1-123 C
Adder
14.17176470588235312.046
944582AF1-123 E
Adder
32.4505882352941227.583
944591AF1-124 C
Adder
14.2223529411764712.089
944592AF1-124 E
Adder
32.5682352941176527.683
944601AF1-125 C
Adder
13.95294117647058811.86
944602AF1-125 E
Adder
31.9423529411764727.151
944631AF1-128 C
Adder
17.6505882352941215.003
958261AF2-120 C
Adder
3.14117647058823522.67
958262AF2-120 E
Adder
2.09411764705882361.78
935161AD1-151 C
Adder
6.3305882352941185.381
935162AD1-151 E
Adder
4.2200000000000013.587
938531AE1-072 C
Adder
5.4494117647058824.632
938532AE1-072 E
Adder
2.84117647058823542.415
939191AE1-149 C
Adder
3.86470588235294173.285
939192AE1-149 E
Adder
2.57647058823529432.19
939261AE1-157 C
50/50
17.67517.675
939262AE1-157 E
50/50
9.5879.587
939602AE1-190 E
Adder
0.63529411764705890.54
940431AE2-027 C
Adder
5.2517647058823544.464
940432AE2-027 E
Adder
3.50117647058823562.976
940551AE2-041 C
Adder
3.20117647058823532.721
941101AE2-104 C
Adder
1.05764705882352940.899
941102AE2-104 E
Adder
1.68117647058823551.429
943471AF1-018 C
Adder
3.20117647058823532.721
944641AF1-129 C
Adder
43.036470588235336.581
957191AF2-013 C
Adder
10.3282352941176478.779
3150431FOUR RIVERA
50/50
2.5342.534
3150441FOUR RIVERB
50/50
2.5342.534
3150451FOUR RIVERC
50/50
3.0963.096
3150461FOUR RIVERD
50/50
2.4972.497
3150471FOUR RIVERE
50/50
2.4972.497
3150481FOUR RIVERF
50/50
3.0493.049
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.081.08
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.5122.512
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.1823.182
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.02918.029
G-007PJM->LTFIMP_G-007
CMTX_NF
1.2851.285
NYPJM->LTFIMP_NY
CLTF
0.610.61
LGEELTFEXP_LGEE->PJM
CLTF
0.1240.124
WECLTFEXP_WEC->PJM
CLTF
0.0580.058
CPLELTFEXP_CPLE->PJM
CLTF
2.2672.267
TVALTFEXP_TVA->PJM
CLTF
0.9510.951
MECLTFEXP_MEC->PJM
CLTF
0.4520.452
LAGNLTFEXP_LAGN->PJM
CLTF
1.2121.212
SIGELTFEXP_SIGE->PJM
CLTF
0.0270.027
O66PJM->LTFIMP_O-066
CMTX_NF
8.1888.188

Details for 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.46 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:797.16
MW Contribution:63.39
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.99 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:766.86
MW Contribution:59.57
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.192941176470588250.164
961942AG1-037 E
Adder
0.129411764705882370.11
966621AG1-532 C
Adder
0.51647058823529410.439
966622AG1-532 E
Adder
0.343529411764705860.292
3145413WATKINS
Adder
0.28235294117647060.24
920042AA2-088 E OP
Adder
4.1788235294117653.552
934521AD1-076 C
Adder
4.8470588235294124.12
934522AD1-076 E
Adder
2.47058823529411782.1
943172AE2-346 E
Adder
0.231764705882352960.197
960081AF2-299 C
Adder
0.68823529411764710.585
960082AF2-299 E
Adder
0.458823529411764740.39
316141AB2-099 E
Adder
0.096470588235294130.082
900672V4-068 E
Adder
0.13882352941176470.118
940492AE2-034 E
Adder
1.24588235294117641.059
946281AF1-292 C
Adder
0.56941176470588240.484
946282AF1-292 E
Adder
0.380.323
3145393UNCAMP
Adder
2.522.142
916042Z1-036 E
Adder
11.8376470588235310.062
938771AE1-103 C
Adder
1.22588235294117661.042
938772AE1-103 E
Adder
1.69294117647058841.439
3142366NRTHEST
50/50
0.4150.415
3143316POE
Adder
0.69294117647058820.589
3145256KINGFORK
Adder
0.455294117647058850.387
3145506HICKORY
Adder
0.93882352941176480.798
3150601CHESTF5
Adder
33.5858823529411828.548
3150651CHESTF6
Adder
11.472941176470599.752
3150671DARBY 1
50/50
5.1375.137
3150681DARBY 2
50/50
5.1435.143
3150691DARBY 3
50/50
5.1615.161
3150701DARBY 4
50/50
5.1675.167
3150731STONECA
Adder
3.82941176470588253.255
3150831SPRUNCA
50/50
10.71910.719
3150841SPRUNCB
50/50
10.71910.719
3150921YORKTN3
Adder
59.65411764705882550.706
925865AC1-065 E
Adder
9.377647058823537.971
926472AC1-118 E
Adder
0.448235294117647070.381
926662AC1-147 E
Adder
0.580.493
926755AC1-161 E
Adder
5.5482352941176484.716
927226AC1-216 E
Adder
4.0164705882352943.414
934392AD1-063 E
Adder
0.60.51
935112AD1-144 E
Adder
0.42235294117647060.359
936582AD2-073 E
Adder
0.494117647058823550.42
936591AD2-074 C
Adder
2.8741176470588242.443
936592AD2-074 E
Adder
4.6894117647058823.986
942341AE2-247 C
Adder
0.68588235294117650.583
942342AE2-247 E
Adder
0.94705882352941180.805
943461AF1-017 C
Adder
0.620.527
943462AF1-017 E
Adder
1.0117647058823530.86
943612AF1-032 E
Adder
0.40.34
943741AF1-042 C
Adder
1.5035294117647061.278
943742AF1-042 E
Adder
2.45411764705882352.086
961951AG1-038 C
Adder
1.66235294117647061.413
961952AG1-038 E
Adder
2.2952941176470591.951
966661AG1-536 C
Adder
2.7305882352941182.321
966662AG1-536 E
Adder
3.6694117647058833.119
316075AC2-137 C
50/50
0.4380.438
316076AC2-137 E
50/50
1.5391.539
316078AC2-138 E
Adder
0.46470588235294120.395
316157AD2-030 E
Adder
0.64705882352941180.55
913392Y1-086 E
Adder
0.93647058823529420.796
916192Z1-068 E
Adder
0.81764705882352940.695
923832AB2-022 E
Adder
0.52823529411764710.449
923842AB2-024 E
Adder
1.02235294117647070.869
923852AB2-025 E
Adder
0.47411764705882360.403
939312AE1-162 E
Adder
0.67411764705882350.573
946262AF1-291 E
Adder
0.86941176470588230.739
957492AF2-043 E
Adder
0.61647058823529410.524
957601AF2-054 C
Adder
1.15294117647058810.98
957602AF2-054 E
Adder
0.76823529411764710.653
962861AG1-135 C
Adder
3.09411764705882362.63
962862AG1-135 E
Adder
2.06235294117647071.753
962962AG1-145 E
Adder
0.78470588235294130.667
963611AG1-210 C
Adder
0.33176470588235290.282
963612AG1-210 E
Adder
0.49764705882352940.423
964211AG1-282 C
Adder
1.02941176470588250.875
964212AG1-282 E
Adder
0.68588235294117650.583
901082W1-029 E
Adder
13.50705882352941211.481
917122Z2-027 E
Adder
0.57058823529411760.485
925332AB2-190 E
Adder
4.3082352941176473.662
925522AC1-027 E
Adder
0.52941176470588240.45
942001AE2-212 C
Adder
1.23176470588235291.047
942002AE2-212 E
Adder
0.82117647058823530.698
957832AF2-077 E
Adder
0.74235294117647070.631
957871AF2-081 C
Adder
4.2894117647058823.646
957872AF2-081 E
Adder
1.83882352941176471.563
958161AF2-110 C
Adder
0.59882352941176480.509
958162AF2-110 E
Adder
0.95294117647058830.81
3138116ELKO L286
50/50
1.6051.605
3141813NORNECK
Adder
0.44235294117647060.376
933291AC2-141 C
Adder
12.9976470588235311.048
933292AC2-141 E
Adder
5.5482352941176484.716
939411AE1-173 C
Adder
32.84941176470588427.922
939412AE1-173 E
Adder
21.918.615
934012AD1-025 E
Adder
5.1988235294117644.419
933981AD1-022 C
Adder
3.44588235294117642.929
933982AD1-022 E
Adder
1.87647058823529411.595
3130536PAPERMILL
Adder
3.7670588235294123.202
3145946PLYMOUTH TP
Adder
0.128235294117647060.109
3146326AYDLETT TAP
Adder
0.58117647058823530.494
316160AE1-175 E
Adder
0.64705882352941180.55
316169AC1-164 GEN
50/50
25.43925.439
316240AF1-291 C
Adder
1.30470588235294121.109
924516AB2-100 E1
Adder
1.11411764705882340.947
924517AB2-100 E2
Adder
1.11411764705882340.947
926785AC1-164_E
50/50
11.42911.429
934065AD1-033 E
Adder
2.16705882352941171.842
937226AE2-253 E
Adder
2.5117647058823532.135
939612AE1-191 E
Adder
3.16117647058823532.687
939246AE1-155 E
Adder
4.423.757
918512AA1-065 E OP
Adder
2.1329411764705881.813
919153AA1-139 E2
Adder
1.75411764705882381.491
919152AA1-139 E1
Adder
1.75411764705882381.491
920692AA2-178 E
Adder
1.66000000000000011.411
924814AB2-134 E
Adder
6.5788235294117645.592
316084AB2-161 E
Adder
2.7223529411764712.314
932046AC2-012 E
Adder
5.74352941176470564.882
316311AC2-079 C
Adder
2.622.227
932596AC2-079 E
Adder
4.2752941176470593.634
934146AD1-041 E
Adder
1.97529411764705891.679
934576AD1-082 E
Adder
2.16941176470588241.844
316349AD2-085 C
Adder
1.58235294117647051.345
936666AD2-085 E
Adder
2.5811764705882352.194
961611AG1-000B C
Adder
7.94235294117647156.751
941591AE2-156 C
Adder
7.8423529411764716.666
944581AF1-123 C
Adder
19.5729411764705916.637
944582AF1-123 E
Adder
44.8238.097
944591AF1-124 C
Adder
19.64235294117647316.696
944592AF1-124 E
Adder
44.9823529411764738.235
944601AF1-125 C
Adder
19.27176470588235416.381
944602AF1-125 E
Adder
44.11647058823529537.499
944631AF1-128 C
Adder
21.0152941176470617.863
958261AF2-120 C
Adder
3.17411764705882372.698
958262AF2-120 E
Adder
2.1164705882352941.799
934501AD1-074 C
Adder
13.34588235294117611.344
934502AD1-074 E
Adder
6.7941176470588245.775
934511AD1-075 C
Adder
3.3364705882352942.836
934512AD1-075 E
Adder
1.69882352941176461.444
935161AD1-151 C
Adder
8.5094117647058837.233
935162AD1-151 E
Adder
5.6729411764705884.822
938531AE1-072 C
Adder
7.5329411764705886.403
938532AE1-072 E
Adder
3.9270588235294123.338
939191AE1-149 C
Adder
5.5294117647058834.7
939192AE1-149 E
Adder
3.68588235294117663.133
939602AE1-190 E
Adder
0.79058823529411770.672
940431AE2-027 C
Adder
8.0694117647058836.859
940432AE2-027 E
Adder
5.3800000000000014.573
940481AE2-033 C
Adder
6.5541176470588235.571
940482AE2-033 E
Adder
4.4188235294117653.756
940541AE2-040 C
Adder
1.1717647058823530.996
940551AE2-041 C
Adder
4.0035294117647063.403
940641AE2-051 C
Adder
5.8941176470588235.01
940642AE2-051 E
Adder
3.9294117647058823.34
941101AE2-104 C
Adder
1.4682352941176471.248
941102AE2-104 E
Adder
2.33411764705882341.984
943471AF1-018 C
Adder
4.0035294117647063.403
944641AF1-129 C
Adder
63.01529411764706653.563
3150851SPRUNCC
50/50
0.1930.193
3150861SPRUNCD
50/50
0.1930.193
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.5041.504
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.4653.465
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.1394.139
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.58824.588
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9570.957
NYPJM->LTFIMP_NY
CLTF
0.4630.463
LGEELTFEXP_LGEE->PJM
CLTF
0.150.15
WECLTFEXP_WEC->PJM
CLTF
0.0770.077
CPLELTFEXP_CPLE->PJM
CLTF
3.1573.157
TVALTFEXP_TVA->PJM
CLTF
1.2281.228
MECLTFEXP_MEC->PJM
CLTF
0.590.59
LAGNLTFEXP_LAGN->PJM
CLTF
1.5871.587
SIGELTFEXP_SIGE->PJM
CLTF
0.0340.034
O66PJM->LTFIMP_O-066
CMTX_NF
6.1076.107

Details for 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.68 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1020.42
MW Contribution:48.69
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.56 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:989.69
MW Contribution:45.0
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.332941176470588240.283
961672AG1-007 E
Adder
0.188235294117647060.16
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
963041AG1-153 C
Adder
1.9482352941176471.656
963042AG1-153 E
Adder
2.92235294117647062.484
966621AG1-532 C
Adder
0.61294117647058830.521
966622AG1-532 E
Adder
0.408235294117647030.347
3145413WATKINS
Adder
0.26470588235294120.225
3145723EMPORIA
Adder
0.185882352941176470.158
3151311EDGECMA
Adder
5.5117647058823534.685
918492AA1-063AE OP
Adder
1.59411764705882361.355
918532AA1-067 E
Adder
0.251764705882352950.214
919692AA2-053 E OP
Adder
1.64941176470588241.402
920042AA2-088 E OP
Adder
4.0811764705882353.469
925785AC1-054 E
Adder
1.2082352941176471.027
927146AC1-208 E
Adder
1.51.275
934521AD1-076 C
Adder
4.377647058823533.721
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
944011AF1-069 C
Adder
4.6141176470588243.922
944012AF1-069 E
Adder
1.7917647058823531.523
960081AF2-299 C
Adder
0.81647058823529410.694
960082AF2-299 E
Adder
0.54470588235294130.463
316141AB2-099 E
Adder
0.095294117647058830.081
900672V4-068 E
Adder
0.136470588235294120.116
917342Z2-044 E
Adder
0.215294117647058830.183
922923AB1-081 E OP
Adder
1.321.122
923263AB1-132 E OP
Adder
2.582.193
923573AB1-173 E OP
Adder
1.36823529411764721.163
924162AB2-060 E OP
Adder
1.3117647058823531.115
924302AB2-077 E O1
Adder
0.41176470588235290.35
924312AB2-078 E O1
Adder
0.41176470588235290.35
924322AB2-079 E O1
Adder
0.41176470588235290.35
940492AE2-034 E
Adder
1.09058823529411760.927
941031AE2-094 C
Adder
14.12000000000000112.002
941032AE2-094 E
Adder
6.3247058823529425.376
946281AF1-292 C
Adder
0.67529411764705880.574
946282AF1-292 E
Adder
0.45058823529411770.383
957481AF2-042 C
Adder
17.0152941176470614.463
957482AF2-042 E
Adder
11.3435294117647069.642
957861AF2-080 C
Adder
2.7023529411764712.297
957862AF2-080 E
Adder
1.19764705882352951.018
3145393UNCAMP
Adder
2.3247058823529411.976
916042Z1-036 E
Adder
9.9682352941176488.473
938771AE1-103 C
Adder
1.11764705882352940.95
938772AE1-103 E
Adder
1.5435294117647061.312
3143316POE
50/50
1.0861.086
3145256KINGFORK
Adder
0.357647058823529430.304
3145506HICKORY
Adder
0.72352941176470590.615
3150651CHESTF6
50/50
21.89721.897
3150731STONECA
50/50
4.5124.512
3150761HOPPOLC
50/50
1.0021.002
3150771HOPHCF1
50/50
1.5941.594
3150781HOPHCF2
50/50
1.5941.594
3150791HOPHCF3
50/50
1.5941.594
3150801HOPHCF4
50/50
2.4192.419
3150831SPRUNCA
Adder
2.6776470588235292.276
3150841SPRUNCB
Adder
2.6776470588235292.276
926662AC1-147 E
Adder
0.452941176470588240.385
926755AC1-161 E
Adder
3.78588235294117673.218
927226AC1-216 E
Adder
4.122352941176473.504
935112AD1-144 E
Adder
0.33176470588235290.282
942341AE2-247 C
Adder
0.68470588235294120.582
942342AE2-247 E
Adder
0.94470588235294130.803
943461AF1-017 C
Adder
0.61882352941176480.526
943462AF1-017 E
Adder
1.00941176470588250.858
943612AF1-032 E
Adder
0.320.272
316132AB2-190 C
50/50
2.4122.412
913392Y1-086 E
Adder
0.74470588235294120.633
916192Z1-068 E
Adder
0.63294117647058830.538
923832AB2-022 E
Adder
0.421176470588235260.358
923852AB2-025 E
Adder
0.6317647058823530.537
939312AE1-162 E
Adder
0.5717647058823530.486
946262AF1-291 E
50/50
1.6321.632
957492AF2-043 E
Adder
0.49294117647058820.419
901082W1-029 E
Adder
10.9870588235294139.339
917122Z2-027 E
Adder
0.457647058823529460.389
925332AB2-190 E
50/50
4.6914.691
925522AC1-027 E
Adder
0.410588235294117640.349
942001AE2-212 C
50/50
2.1112.111
942002AE2-212 E
50/50
1.4081.408
957871AF2-081 C
Adder
3.34117647058823542.84
957872AF2-081 E
Adder
1.4317647058823531.217
958161AF2-110 C
Adder
0.51764705882352950.44
958162AF2-110 E
Adder
0.82470588235294120.701
917512Z2-088 E OP1
Adder
1.73411764705882351.474
926071AC1-086 C
Adder
8.8647058823529427.535
926072AC1-086 E
Adder
4.0352941176470593.43
927021AC1-189 C
Adder
2.97529411764705862.529
927022AC1-189 E
Adder
1.48235294117647071.26
933291AC2-141 C
Adder
8.8694117647058827.539
933292AC2-141 E
Adder
3.78588235294117673.218
934621AD1-088 C
Adder
2.86941176470588262.439
934622AD1-088 E
Adder
1.38117647058823521.174
939411AE1-173 C
Adder
31.5352941176470626.805
939412AE1-173 E
Adder
21.0235294117647117.87
934012AD1-025 E
Adder
5.3364705882352944.536
933981AD1-022 C
Adder
3.162.686
933982AD1-022 E
Adder
1.721.462
962572AG1-106 E
Adder
0.50117647058823530.426
962571AG1-106 C
Adder
1.14705882352941170.975
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
3146326AYDLETT TAP
Adder
0.455294117647058850.387
316240AF1-291 C
50/50
2.4482.448
316263AC1-034 C
Adder
2.3517647058823531.999
316274AC1-208 C
Adder
3.3788235294117652.872
917332KELFORD E
Adder
0.61411764705882350.522
924516AB2-100 E1
Adder
1.36823529411764721.163
924517AB2-100 E2
Adder
1.36823529411764721.163
925595AC1-034 E
Adder
1.77411764705882361.508
926206AC1-098 E
Adder
1.35999999999999991.156
926214AC1-099 E
Adder
0.44941176470588240.382
934065AD1-033 E
Adder
1.6670588235294121.417
937226AE2-253 E
Adder
1.9482352941176471.656
918512AA1-065 E OP
Adder
2.04235294117647071.736
919153AA1-139 E2
Adder
1.36588235294117651.161
919152AA1-139 E1
Adder
1.36588235294117651.161
919710AA2-057 E
Adder
1.44823529411764731.231
920692AA2-178 E
Adder
1.4552941176470591.237
923994AB2-040_E
Adder
2.56588235294117652.181
924022AB2-043 E O1
Adder
1.60117647058823541.361
924152AB2-059 E OP
Adder
1.87058823529411791.59
924814AB2-134 E
Adder
6.7529411764705885.74
316083AB2-161 C
50/50
0.3210.321
316084AB2-161 E
50/50
3.213.21
925122AB2-169 E
Adder
2.04352941176470631.737
316088AB2-174 E
Adder
2.7588235294117652.345
932046AC2-012 E
Adder
4.4823529411764713.81
316311AC2-079 C
Adder
2.5717647058823532.186
932596AC2-079 E
Adder
4.1964705882352953.567
316381AD1-082 C
50/50
0.7330.733
934576AD1-082 E
50/50
2.5582.558
316349AD2-085 C
Adder
1.57882352941176471.342
936666AD2-085 E
Adder
2.5752941176470592.189
961611AG1-000B C
Adder
7.342352941176476.241
941591AE2-156 C
Adder
6.1141176470588245.197
944581AF1-123 C
Adder
15.03411764705882412.779
944582AF1-123 E
Adder
34.4258823529411829.262
944591AF1-124 C
Adder
15.08705882352941312.824
944592AF1-124 E
Adder
34.55058823529411429.368
944601AF1-125 C
Adder
14.80235294117647312.582
944602AF1-125 E
Adder
33.8847058823529428.802
964241AG1-285 C
Adder
3.85882352941176483.28
964242AG1-285 E
Adder
2.5717647058823532.186
3137643SOCKMAN
Adder
0.288235294117647030.245
932632AC2-084 E
Adder
1.20235294117647061.022
934321AD1-056 C
Adder
2.3988235294117652.039
934322AD1-056 E
Adder
1.30117647058823541.106
934331AD1-057 C
Adder
1.33882352941176451.138
934332AD1-057 E
Adder
0.69647058823529410.592
934501AD1-074 C
Adder
12.05529411764705810.247
934502AD1-074 E
Adder
6.1364705882352945.216
934511AD1-075 C
Adder
3.01411764705882362.562
934512AD1-075 E
Adder
1.53411764705882361.304
934612AD1-087 E
Adder
1.1117647058823530.945
935161AD1-151 C
50/50
9.0229.022
935162AD1-151 E
50/50
6.0156.015
935172AD1-152 E
Adder
1.6435294117647061.397
937482AD2-202 E
Adder
0.32588235294117650.277
938531AE1-072 C
Adder
5.8905882352941185.007
938532AE1-072 E
Adder
3.07058823529411742.61
939191AE1-149 C
50/50
7.1377.137
939192AE1-149 E
50/50
4.7584.758
940431AE2-027 C
Adder
7.0447058823529425.988
940432AE2-027 E
Adder
4.6964705882352943.992
940481AE2-033 C
Adder
8.6517647058823537.354
940482AE2-033 E
Adder
5.8329411764705884.958
940541AE2-040 C
Adder
1.56117647058823541.327
940641AE2-051 C
Adder
6.0952941176470595.181
940642AE2-051 E
Adder
4.0635294117647063.454
941101AE2-104 C
Adder
1.26941176470588221.079
941102AE2-104 E
Adder
2.0188235294117651.716
944641AF1-129 C
50/50
120.262120.262
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
NYPJM->LTFIMP_NY
CLTF
0.4360.436
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
WECLTFEXP_WEC->PJM
CLTF
0.140.14
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
TVALTFEXP_TVA->PJM
CLTF
1.561.56
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.12 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3352.99
MW Contribution:166.38
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3492.91
MW Contribution:161.87
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
1.05882352941176470.9
961672AG1-007 E
Adder
0.60.51
961791AG1-021 C
Adder
1.63058823529411771.386
961792AG1-021 E
Adder
1.38941176470588231.181
961941AG1-037 C
Adder
0.5717647058823530.486
961942AG1-037 E
Adder
0.381176470588235340.324
963041AG1-153 C
50/50
8.3218.321
963042AG1-153 E
50/50
12.48112.481
964791AG1-342 C
Adder
3.96470588235294133.37
964792AG1-342 E
Adder
2.6435294117647062.247
966621AG1-532 C
50/50
1.6281.628
966622AG1-532 E
50/50
1.0851.085
3138533PONTONDP
Adder
0.60352941176470590.513
3145413WATKINS
Adder
0.7717647058823530.656
3145723EMPORIA
50/50
0.50.5
3147133PAMPLIN
Adder
0.89882352941176480.764
3151311EDGECMA
Adder
17.50705882352941214.881
3151531CLOVER1
50/50
15.90515.905
3151541CLOVER2
50/50
15.75715.757
918492AA1-063AE OP
Adder
4.65058823529411753.953
918532AA1-067 E
Adder
0.80588235294117660.685
919692AA2-053 E OP
Adder
4.8352941176470594.11
920042AA2-088 E OP
Adder
11.94941176470588210.157
925785AC1-054 E
Adder
3.94000000000000043.349
926274AC1-105 E
Adder
2.9882352941176472.54
927146AC1-208 E
Adder
4.5541176470588243.871
934521AD1-076 C
Adder
13.81176470588235411.74
934522AD1-076 E
Adder
7.045.984
943172AE2-346 E
Adder
0.68588235294117650.583
943902AF1-058 E
Adder
1.42941176470588241.215
944011AF1-069 C
50/50
19.88619.886
944012AF1-069 E
50/50
7.7257.725
959311AF2-222 C
Adder
17.79058823529411615.122
959312AF2-222 E
Adder
11.9210.132
960081AF2-299 C
50/50
2.1712.171
960082AF2-299 E
50/50
1.4471.447
316141AB2-099 E
Adder
0.28588235294117650.243
900672V4-068 E
Adder
0.402352941176470640.342
917342Z2-044 E
Adder
0.6764705882352940.575
922923AB1-081 E OP
Adder
4.20470588235294153.574
923263AB1-132 E OP
Adder
7.0270588235294125.973
923573AB1-173 E OP
Adder
3.78941176470588253.221
924162AB2-060 E OP
Adder
4.8364705882352944.111
924302AB2-077 E O1
Adder
1.52117647058823541.293
924312AB2-078 E O1
Adder
1.52117647058823541.293
924322AB2-079 E O1
Adder
1.52117647058823541.293
925612AC1-036 E
Adder
0.93294117647058830.793
940492AE2-034 E
Adder
3.4764705882352942.955
941031AE2-094 C
50/50
60.86460.864
941032AE2-094 E
50/50
27.25927.259
946281AF1-292 C
50/50
1.7971.797
946282AF1-292 E
50/50
1.1981.198
946301AF1-294 C
Adder
3.3517647058823532.849
946302AF1-294 E
Adder
2.83882352941176472.413
957481AF2-042 C
50/50
69.9469.94
957482AF2-042 E
50/50
46.62746.627
957861AF2-080 C
Adder
8.6200000000000017.327
957862AF2-080 E
Adder
3.8211764705882363.248
958211AF2-115 C
Adder
2.03764705882352941.732
958212AF2-115 E
Adder
1.73647058823529421.476
3145393UNCAMP
Adder
6.7635294117647065.749
916042Z1-036 E
Adder
32.1705882352941227.345
938771AE1-103 C
Adder
3.24823529411764732.761
938772AE1-103 E
Adder
4.4858823529411773.813
313526AB2-022 C
50/50
0.4240.424
3143316POE
Adder
1.30823529411764721.112
3145256KINGFORK
Adder
1.06588235294117650.906
3145506HICKORY
50/50
2.4672.467
926662AC1-147 E
Adder
1.46588235294117641.246
926755AC1-161 E
50/50
14.89414.894
935112AD1-144 E
Adder
0.98941176470588230.841
942341AE2-247 C
Adder
1.54941176470588231.317
942342AE2-247 E
Adder
2.141.819
943461AF1-017 C
Adder
1.40235294117647061.192
943462AF1-017 E
Adder
2.2870588235294121.944
943612AF1-032 E
Adder
1.02823529411764710.874
3151021BRUNSWICKG1
50/50
12.28212.282
3151031BRUNSWICKG2
50/50
12.28212.282
3151041BRUNSWICKG3
50/50
12.28212.282
3151051BRUNSWICKS1
50/50
25.51625.516
3151081ELIZAR1
50/50
3.5563.556
3151091ELIZAR2
50/50
3.4953.495
3151101ELIZAR3
50/50
3.6013.601
3152411Z1-086 GT1
50/50
15.81615.816
3152421Z1-086 GT2
50/50
15.81115.811
3152431Z1-086 GT3
50/50
15.81115.811
3152441Z1-086 ST
50/50
27.53327.533
913392Y1-086 E
50/50
2.4762.476
916192Z1-068 E
50/50
2.1052.105
923832AB2-022 E
50/50
1.3981.398
923852AB2-025 E
50/50
1.3891.389
939312AE1-162 E
Adder
1.37058823529411771.165
957492AF2-043 E
Adder
1.58117647058823541.344
901082W1-029 E
Adder
35.7705882352941230.405
917122Z2-027 E
50/50
1.5121.512
925522AC1-027 E
50/50
1.3621.362
957871AF2-081 C
50/50
11.29311.293
957872AF2-081 E
50/50
4.844.84
958161AF2-110 C
Adder
1.49647058823529421.272
958162AF2-110 E
Adder
2.38000000000000032.023
3147223TWITTYS
Adder
1.03411764705882360.879
917512Z2-088 E OP1
Adder
5.5247058823529414.696
926071AC1-086 C
Adder
24.1447058823529420.523
926072AC1-086 E
Adder
10.9894117647058819.341
927021AC1-189 C
Adder
9.4905882352941178.067
927022AC1-189 E
Adder
4.7282352941176474.019
936261AD2-033 C
Adder
13.51176470588235311.485
936262AD2-033 E
Adder
9.0082352941176477.657
933291AC2-141 C
50/50
34.8934.89
933292AC2-141 E
50/50
14.89414.894
934621AD1-088 C
50/50
11.53711.537
934622AD1-088 E
50/50
5.5555.555
939411AE1-173 C
50/50
128.665128.665
939412AE1-173 E
50/50
85.77785.777
916191Z1-068 C
50/50
0.0490.049
933981AD1-022 C
Adder
9.8917647058823528.408
933982AD1-022 E
Adder
5.3847058823529414.577
962572AG1-106 E
Adder
1.36588235294117651.161
962571AG1-106 C
Adder
3.1235294117647062.655
3145946PLYMOUTH TP
Adder
0.364705882352941160.31
3146326AYDLETT TAP
50/50
1.5311.531
316023AB2-100 C2
50/50
1.1231.123
316185AD1-033 C
50/50
1.391.39
316263AC1-034 C
Adder
7.4894117647058826.366
316274AC1-208 C
Adder
10.255294117647068.717
316294AC1-161 C
50/50
5.7015.701
316315AB2-025 C
50/50
0.4880.488
316316AC1-027 C
50/50
0.3530.353
316320Y1-086 C
50/50
0.2480.248
316321Z2-027 C
50/50
0.410.41
316365AB2-100 C1
50/50
1.1231.123
917332KELFORD E
Adder
1.8635294117647061.584
924516AB2-100 E1
50/50
3.3843.384
924517AB2-100 E2
50/50
3.3843.384
925595AC1-034 E
Adder
5.65058823529411754.803
926206AC1-098 E
Adder
4.1470588235294123.525
926214AC1-099 E
Adder
1.36941176470588231.164
927255AC1-221 E
Adder
4.1411764705882363.52
927264AC1-222 E
Adder
4.3282352941176473.679
932763AC2-100 E
Adder
2.80941176470588252.388
934065AD1-033 E
50/50
5.6715.671
937226AE2-253 E
50/50
6.6066.606
918512AA1-065 E OP
Adder
6.2505882352941175.313
316017AA1-139 ULT1
50/50
1.2231.223
316018AA1-139 ULT2
50/50
1.2231.223
919153AA1-139 E2
50/50
4.6184.618
919152AA1-139 E1
50/50
4.6184.618
919710AA2-057 E
Adder
4.49411764705882363.82
920692AA2-178 E
Adder
4.6352941176470593.94
923994AB2-040_E
Adder
7.1047058823529416.039
924022AB2-043 E O1
Adder
5.9035294117647065.018
924152AB2-059 E OP
Adder
5.9564705882352945.063
316084AB2-161 E
Adder
5.26941176470588254.479
925122AB2-169 E
Adder
6.4858823529411775.513
316087AB2-174 C
50/50
1.3621.362
316088AB2-174 E
50/50
7.5427.542
316375AC2-012 C
50/50
1.4951.495
932046AC2-012 E
50/50
14.50114.501
316311AC2-079 C
Adder
5.9964705882352955.097
932596AC2-079 E
Adder
9.7835294117647078.316
934576AD1-082 E
Adder
4.1988235294117653.569
316349AD2-085 C
Adder
3.5752941176470593.039
936666AD2-085 E
Adder
5.8329411764705884.958
316388AE2-253 GEN
50/50
2.2212.221
961611AG1-000B C
Adder
5.824.947
941591AE2-156 C
50/50
19.83519.835
944581AF1-123 C
50/50
51.37451.374
944582AF1-123 E
50/50
117.641117.641
944591AF1-124 C
50/50
51.55751.557
944592AF1-124 E
50/50
118.067118.067
944601AF1-125 C
50/50
50.58350.583
944602AF1-125 E
50/50
115.795115.795
962561AG1-105 C
Adder
9.9705882352941188.475
962562AG1-105 E
Adder
6.6470588235294125.65
964241AG1-285 C
50/50
14.87614.876
964242AG1-285 E
50/50
9.9189.918
3137643SOCKMAN
Adder
0.81882352941176460.696
932632AC2-084 E
Adder
3.66588235294117663.116
934321AD1-056 C
Adder
7.126.052
934322AD1-056 E
Adder
3.86117647058823543.282
934331AD1-057 C
Adder
3.9717647058823533.376
934332AD1-057 E
Adder
2.0682352941176471.758
934501AD1-074 C
Adder
38.0305882352941232.326
934502AD1-074 E
Adder
19.3616.456
934511AD1-075 C
Adder
9.507058823529418.081
934512AD1-075 E
Adder
4.844.114
934611AD1-087 C
50/50
1.5661.566
934612AD1-087 E
50/50
4.5174.517
935171AD1-152 C
50/50
1.6091.609
935172AD1-152 E
50/50
6.6176.617
937481AD2-202 C
50/50
0.4540.454
937482AD2-202 E
50/50
1.3221.322
938531AE1-072 C
50/50
19.84719.847
938532AE1-072 E
50/50
10.34610.346
939191AE1-149 C
Adder
9.5941176470588238.155
939192AE1-149 E
Adder
6.3964705882352955.437
940481AE2-033 C
50/50
19.30519.305
940482AE2-033 E
50/50
13.01513.015
940541AE2-040 C
50/50
3.4343.434
940641AE2-051 C
50/50
26.11526.115
940642AE2-051 E
50/50
17.4117.41
941101AE2-104 C
Adder
3.66705882352941173.117
941102AE2-104 E
Adder
5.8305882352941184.956
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.3016.301
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.47229.472
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.8122.81
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
107.493107.493
G-007PJM->LTFIMP_G-007
CMTX_NF
3.5513.551
NYPJM->LTFIMP_NY
CLTF
1.6611.661
LGEELTFEXP_LGEE->PJM
CLTF
1.1651.165
WECLTFEXP_WEC->PJM
CLTF
0.6140.614
CPLELTFEXP_CPLE->PJM
CLTF
13.22113.221
TVALTFEXP_TVA->PJM
CLTF
6.2796.279
MECLTFEXP_MEC->PJM
CLTF
3.8563.856
LAGNLTFEXP_LAGN->PJM
CLTF
8.048.04
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234
O66PJM->LTFIMP_O-066
CMTX_NF
22.61622.616

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:136.21 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3326.4
MW Contribution:257.42
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:145.97 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3564.84
MW Contribution:259.27
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.71294117647058820.606
961942AG1-037 E
Adder
0.475294117647058870.404
963041AG1-153 C
Adder
7.1717647058823536.096
963042AG1-153 E
Adder
10.757647058823539.144
966621AG1-532 C
Adder
1.72705882352941181.468
966622AG1-532 E
Adder
1.1517647058823530.979
3145413WATKINS
Adder
1.03764705882352940.882
3145723EMPORIA
Adder
0.53411764705882360.454
918492AA1-063AE OP
Adder
5.464705882352944.645
918532AA1-067 E
Adder
0.94588235294117650.804
919692AA2-053 E OP
Adder
5.50588235294117644.68
920042AA2-088 E OP
Adder
15.25058823529411712.963
934521AD1-076 C
Adder
18.52705882352941215.748
934522AD1-076 E
Adder
9.4435294117647068.027
943172AE2-346 E
Adder
0.85647058823529410.728
944011AF1-069 C
Adder
17.03647058823529314.481
944012AF1-069 E
Adder
6.6188235294117655.626
960081AF2-299 C
Adder
2.3023529411764711.957
960082AF2-299 E
Adder
1.53529411764705871.305
316141AB2-099 E
Adder
0.35647058823529410.303
900672V4-068 E
Adder
0.50705882352941180.431
923263AB1-132 E OP
Adder
7.79647058823529456.627
923573AB1-173 E OP
Adder
4.1152941176470593.498
940492AE2-034 E
Adder
4.8058823529411764.085
941031AE2-094 C
Adder
52.14117647058823544.32
941032AE2-094 E
Adder
23.3529411764705919.85
946281AF1-292 C
Adder
1.90588235294117661.62
946282AF1-292 E
Adder
1.27058823529411781.08
3145393UNCAMP
Adder
9.2964705882352947.902
916042Z1-036 E
50/50
46.21946.219
938771AE1-103 C
Adder
4.5305882352941173.851
938772AE1-103 E
Adder
6.257647058823535.319
313526AB2-022 C
50/50
0.640.64
3144216WINCHST
50/50
0.2310.231
3145256KINGFORK
50/50
1.7041.704
3145506HICKORY
50/50
3.8083.808
3150601CHESTF5
Adder
72.936470588235361.996
3150921YORKTN3
50/50
212.818212.818
925865AC1-065 E
Adder
24.48470588235294420.812
926662AC1-147 E
50/50
2.2972.297
926755AC1-161 E
50/50
24.37824.378
927226AC1-216 E
Adder
10.5317647058823528.952
934392AD1-063 E
Adder
1.61529411764705881.373
935112AD1-144 E
50/50
1.5821.582
936591AD2-074 C
Adder
7.8788235294117656.697
936592AD2-074 E
Adder
12.85529411764705910.927
942341AE2-247 C
Adder
2.2741176470588241.933
942342AE2-247 E
Adder
3.142.669
943461AF1-017 C
Adder
2.05764705882352941.749
943462AF1-017 E
Adder
3.35647058823529452.853
943612AF1-032 E
50/50
1.5651.565
943741AF1-042 C
Adder
4.122352941176473.504
943742AF1-042 E
Adder
6.7258823529411765.717
961951AG1-038 C
Adder
4.5564705882352943.873
961952AG1-038 E
Adder
6.2929411764705885.349
966661AG1-536 C
Adder
7.4564705882352956.338
966662AG1-536 E
Adder
10.0188235294117658.516
3150981CHESPKA
50/50
0.7560.756
3150991CHESPKB
50/50
1.2531.253
3151081ELIZAR1
50/50
5.5655.565
3151091ELIZAR2
50/50
5.4685.468
3151101ELIZAR3
50/50
5.6365.636
3151161SURRY 1
50/50
37.92137.921
3152331SURRY 2
50/50
50.93450.934
3156056W1-029WIND
50/50
1.2961.296
3156116Z1-036WIND
50/50
1.0631.063
316076AC2-137 E
Adder
1.64117647058823551.395
316078AC2-138 E
Adder
1.26470588235294111.075
316157AD2-030 E
Adder
1.7917647058823531.523
913392Y1-086 E
50/50
3.7343.734
916192Z1-068 E
50/50
3.2743.274
923832AB2-022 E
50/50
2.1082.108
923842AB2-024 E
Adder
2.7035294117647062.298
923852AB2-025 E
Adder
1.42470588235294131.211
939312AE1-162 E
50/50
2.3092.309
957492AF2-043 E
50/50
2.4072.407
957601AF2-054 C
Adder
3.1929411764705882.714
957602AF2-054 E
Adder
2.12823529411764721.809
962861AG1-135 C
Adder
8.4564705882352957.188
962862AG1-135 E
Adder
5.63764705882352954.792
962962AG1-145 E
50/50
2.4882.488
963611AG1-210 C
Adder
0.90352941176470590.768
963612AG1-210 E
Adder
1.35529411764705881.152
964211AG1-282 C
Adder
2.76588235294117672.351
964212AG1-282 E
Adder
1.84352941176470591.567
901082W1-029 E
50/50
53.16253.162
917122Z2-027 E
50/50
2.2672.267
925332AB2-190 E
Adder
10.335294117647068.785
925522AC1-027 E
50/50
2.1192.119
957831AF2-077 C
50/50
0.5460.546
957832AF2-077 E
50/50
2.3562.356
957871AF2-081 C
50/50
17.30217.302
957872AF2-081 E
50/50
7.4157.415
958161AF2-110 C
50/50
2.2342.234
958162AF2-110 E
50/50
3.5543.554
3138116ELKO L286
Adder
1.71058823529411771.454
3141813NORNECK
Adder
1.20352941176470571.023
926071AC1-086 C
Adder
26.78823529411764822.77
926072AC1-086 E
Adder
12.19176470588235310.363
933291AC2-141 C
50/50
57.10857.108
933292AC2-141 E
50/50
24.37824.378
939411AE1-173 C
50/50
137.269137.269
939412AE1-173 E
50/50
91.51291.512
934012AD1-025 E
Adder
13.63529411764705811.59
916191Z1-068 C
50/50
0.0760.076
933981AD1-022 C
Adder
13.0952941176470611.131
933982AD1-022 E
Adder
7.1294117647058826.06
962572AG1-106 E
Adder
1.5164705882352941.289
962571AG1-106 C
Adder
3.4647058823529412.945
3130536PAPERMILL
Adder
9.9929411764705888.494
3145946PLYMOUTH TP
Adder
0.491764705882352940.418
3146326AYDLETT TAP
50/50
2.3362.336
316036AC1-147 C
50/50
0.6390.639
316072AD1-144 C
50/50
0.4730.473
316159AE1-175 C
50/50
0.6760.676
316160AE1-175 E
50/50
2.0532.053
316169AC1-164 GEN
50/50
61.5761.57
316185AD1-033 C
50/50
2.1522.152
316236AE1-162 C
50/50
0.5660.566
316246AF1-032 C
50/50
0.4820.482
316294AC1-161 C
50/50
9.3329.332
316305AF2-043 C
50/50
0.590.59
316316AC1-027 C
50/50
0.550.55
316320Y1-086 C
50/50
0.3740.374
316321Z2-027 C
50/50
0.6140.614
316382AG1-145 C
50/50
0.610.61
917332KELFORD E
Adder
2.25294117647058821.915
924516AB2-100 E1
Adder
3.61411764705882373.072
924517AB2-100 E2
Adder
3.61411764705882373.072
926206AC1-098 E
Adder
4.72941176470588154.02
926214AC1-099 E
Adder
1.56235294117647071.328
926785AC1-164_E
50/50
27.66227.662
934065AD1-033 E
50/50
8.788.78
937226AE2-253 E
50/50
10.1510.15
939612AE1-191 E
Adder
8.4670588235294127.197
939246AE1-155 E
Adder
12.06941176470588310.259
918512AA1-065 E OP
Adder
7.9635294117647066.769
316017AA1-139 ULT1
50/50
1.8731.873
316018AA1-139 ULT2
50/50
1.8731.873
919153AA1-139 E2
50/50
7.0757.075
919152AA1-139 E1
50/50
7.0757.075
920692AA2-178 E
Adder
6.4070588235294125.446
923994AB2-040_E
Adder
7.7152941176470586.558
924814AB2-134 E
Adder
17.2517647058823514.664
316084AB2-161 E
Adder
7.497647058823536.373
925122AB2-169 E
Adder
8.1847058823529426.957
316088AB2-174 E
Adder
8.1305882352941186.911
316375AC2-012 C
50/50
2.3432.343
932046AC2-012 E
50/50
22.72422.724
316311AC2-079 C
Adder
8.827.497
932596AC2-079 E
Adder
14.39058823529411812.232
934146AD1-041 E
Adder
5.2917647058823534.498
934576AD1-082 E
Adder
5.9741176470588245.078
316349AD2-085 C
Adder
5.2458823529411764.459
936666AD2-085 E
Adder
8.5588235294117647.275
316388AE2-253 GEN
50/50
3.4133.413
961611AG1-000B C
Adder
23.74470588235294220.183
941591AE2-156 C
50/50
31.07431.074
944581AF1-123 C
50/50
79.48679.486
944582AF1-123 E
50/50
182.015182.015
944591AF1-124 C
50/50
79.76979.769
944592AF1-124 E
50/50
182.674182.674
944601AF1-125 C
50/50
78.26278.262
944602AF1-125 E
50/50
179.158179.158
944631AF1-128 C
Adder
26.26705882352941422.327
958261AF2-120 C
Adder
8.6682352941176477.368
958262AF2-120 E
Adder
5.7788235294117654.912
3137643SOCKMAN
Adder
0.90352941176470590.768
932632AC2-084 E
Adder
4.183.553
934501AD1-074 C
Adder
51.01411764705882543.362
934502AD1-074 E
Adder
25.96941176470588522.074
934511AD1-075 C
Adder
12.75411764705882310.841
934512AD1-075 E
Adder
6.4917647058823525.518
935161AD1-151 C
Adder
21.28588235294117618.093
935162AD1-151 E
Adder
14.19058823529411712.062
938531AE1-072 C
50/50
30.31830.318
938532AE1-072 E
50/50
15.80515.805
939191AE1-149 C
Adder
13.30705882352941111.311
939192AE1-149 E
Adder
8.8705882352941187.54
939602AE1-190 E
Adder
2.1164705882352941.799
940481AE2-033 C
Adder
19.89882352941176816.914
940482AE2-033 E
Adder
13.4152941176470611.403
940541AE2-040 C
Adder
3.5223529411764712.994
940551AE2-041 C
Adder
10.7682352941176489.153
940641AE2-051 C
50/50
24.9624.96
940642AE2-051 E
50/50
16.6416.64
941101AE2-104 C
50/50
5.4755.475
941102AE2-104 E
50/50
8.7058.705
943471AF1-018 C
Adder
10.7682352941176489.153
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.8765.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.55415.554
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.85316.853
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69696.696
G-007PJM->LTFIMP_G-007
CMTX_NF
3.3653.365
NYPJM->LTFIMP_NY
CLTF
1.6271.627
LGEELTFEXP_LGEE->PJM
CLTF
0.6520.652
WECLTFEXP_WEC->PJM
CLTF
0.3380.338
CPLELTFEXP_CPLE->PJM
CLTF
12.33712.337
TVALTFEXP_TVA->PJM
CLTF
4.9324.932
MECLTFEXP_MEC->PJM
CLTF
2.4842.484
LAGNLTFEXP_LAGN->PJM
CLTF
6.3726.372
SIGELTFEXP_SIGE->PJM
CLTF
0.1430.143
O66PJM->LTFIMP_O-066
CMTX_NF
21.46821.468

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.81 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4713.59
MW Contribution:247.5
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:137.17 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5582.91
MW Contribution:259.78
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.76117647058823530.647
961942AG1-037 E
Adder
0.50705882352941180.431
963041AG1-153 C
Adder
7.67882352941176556.527
963042AG1-153 E
Adder
11.517647058823539.79
966621AG1-532 C
Adder
2.00705882352941161.706
966622AG1-532 E
Adder
1.33882352941176451.138
3145413WATKINS
Adder
1.08705882352941190.924
3145723EMPORIA
Adder
0.61764705882352940.525
918492AA1-063AE OP
Adder
6.0129411764705885.111
920042AA2-088 E OP
Adder
16.25647058823529513.818
934521AD1-076 C
Adder
19.0647058823529416.205
934522AD1-076 E
Adder
9.7164705882352948.259
943172AE2-346 E
Adder
0.91294117647058830.776
944011AF1-069 C
Adder
18.02352941176470615.32
944012AF1-069 E
Adder
7.0023529411764715.952
960081AF2-299 C
Adder
2.6764705882352942.275
960082AF2-299 E
Adder
1.78470588235294111.517
316141AB2-099 E
Adder
0.380.323
900672V4-068 E
Adder
0.54235294117647060.461
923573AB1-173 E OP
Adder
4.7082352941176474.002
940492AE2-034 E
Adder
4.8823529411764714.15
941031AE2-094 C
Adder
55.1635294117647146.889
941032AE2-094 E
Adder
24.70588235294117821
946281AF1-292 C
Adder
2.2152941176470591.883
946282AF1-292 E
Adder
1.47764705882352951.256
3145393UNCAMP
Adder
9.664705882352948.215
916042Z1-036 E
Adder
46.2035294117647139.273
938771AE1-103 C
Adder
4.6882352941176473.985
938772AE1-103 E
Adder
6.4741176470588245.503
3143316POE
Adder
2.15411764705882371.831
3144216WINCHST
50/50
0.2290.229
3145256KINGFORK
Adder
1.70470588235294131.449
3145506HICKORY
Adder
3.66705882352941173.117
3150601CHESTF5
50/50
107.532107.532
3150611CHESTG7
50/50
6.5626.562
3150621CHESTS7
50/50
3.0123.012
3150631CHESTG8
50/50
6.4576.457
3150641CHESTS8
50/50
3.3243.324
3150651CHESTF6
Adder
30.4035294117647125.843
3150681DARBY 2
50/50
4.2574.257
3150691DARBY 3
50/50
4.2724.272
3150701DARBY 4
50/50
4.2774.277
3150731STONECA
Adder
11.5258823529411789.797
3150831SPRUNCA
Adder
14.5823529411764712.395
3150841SPRUNCB
Adder
14.5823529411764712.395
3150921YORKTN3
50/50
208.205208.205
925865AC1-065 E
Adder
27.3976470588235323.288
926412AC1-112 E
50/50
1.9031.903
926662AC1-147 E
Adder
2.2364705882352941.901
926755AC1-161 E
50/50
22.27722.277
927226AC1-216 E
Adder
12.9976470588235311.048
934392AD1-063 E
Adder
1.77411764705882361.508
935112AD1-144 E
Adder
1.58235294117647051.345
936591AD2-074 C
Adder
8.5505882352941187.268
936592AD2-074 E
Adder
13.95176470588235211.859
942341AE2-247 C
Adder
2.4552941176470592.087
942342AE2-247 E
Adder
3.39176470588235322.883
943461AF1-017 C
Adder
2.2223529411764711.889
943462AF1-017 E
Adder
3.62470588235294143.081
943612AF1-032 E
Adder
1.54117647058823541.31
943741AF1-042 C
Adder
4.4741176470588243.803
943742AF1-042 E
Adder
7.3000000000000016.205
961951AG1-038 C
Adder
4.9458823529411764.204
961952AG1-038 E
Adder
6.8294117647058825.805
966661AG1-536 C
Adder
8.0929411764705876.879
966662AG1-536 E
Adder
10.8741176470588249.243
966871AG1-558 C
Adder
3.73647058823529443.176
966872AG1-558 E
Adder
1.88235294117647081.6
3152331SURRY 2
50/50
44.51344.513
316075AC2-137 C
50/50
0.6540.654
316076AC2-137 E
50/50
2.32.3
316078AC2-138 E
Adder
1.37294117647058831.167
316157AD2-030 E
Adder
1.94470588235294131.653
913392Y1-086 E
Adder
3.6470588235294123.1
916192Z1-068 E
Adder
3.16941176470588242.694
923832AB2-022 E
Adder
2.0588235294117651.75
923842AB2-024 E
Adder
2.99058823529411732.542
923852AB2-025 E
Adder
1.7117647058823531.455
930122AB1-027 E
50/50
2.342.34
938552AE1-074 E
Adder
1.90000000000000011.615
939312AE1-162 E
Adder
2.4211764705882352.058
946262AF1-291 E
Adder
2.34117647058823541.99
957492AF2-043 E
Adder
2.37058823529411772.015
957601AF2-054 C
Adder
3.4647058823529412.945
957602AF2-054 E
Adder
2.31058823529411761.964
962861AG1-135 C
Adder
9.177647058823537.801
962862AG1-135 E
Adder
6.1188235294117645.201
962962AG1-145 E
50/50
2.5352.535
963611AG1-210 C
Adder
0.980.833
963612AG1-210 E
Adder
1.47058823529411781.25
964211AG1-282 C
Adder
3.02000000000000052.567
964212AG1-282 E
Adder
2.01294117647058851.711
901082W1-029 E
Adder
52.4682352941176544.598
917122Z2-027 E
Adder
2.22117647058823531.888
925332AB2-190 E
Adder
13.54588235294117611.514
925522AC1-027 E
Adder
2.05294117647058851.745
942001AE2-212 C
Adder
3.4764705882352942.955
942002AE2-212 E
Adder
2.31764705882352961.97
957832AF2-077 E
Adder
2.41411764705882352.052
957871AF2-081 C
Adder
16.73529411764705814.225
957872AF2-081 E
Adder
7.1717647058823536.096
958161AF2-110 C
Adder
2.2623529411764711.923
958162AF2-110 E
Adder
3.5988235294117653.059
3138116ELKO L286
50/50
2.3992.399
3141813NORNECK
Adder
1.30588235294117671.11
926071AC1-086 C
Adder
8.492941176470597.219
933291AC2-141 C
50/50
52.18752.187
933292AC2-141 E
50/50
22.27722.277
939411AE1-173 C
Adder
137.65882352941176117.01
939412AE1-173 E
Adder
91.772941176470678.007
934012AD1-025 E
Adder
16.82705882352941314.303
927041AC1-191 C
Adder
15.00352941176470612.753
927042AC1-191 E
Adder
7.4741176470588236.353
933981AD1-022 C
Adder
13.55882352941176611.525
933982AD1-022 E
Adder
7.3811764705882366.274
3130536PAPERMILL
Adder
11.0400000000000019.384
3145946PLYMOUTH TP
Adder
0.50470588235294120.429
3146326AYDLETT TAP
Adder
2.26588235294117621.926
316004AC1-112 C
50/50
0.5560.556
316159AE1-175 C
50/50
0.6890.689
316160AE1-175 E
50/50
2.0922.092
316169AC1-164 GEN
50/50
71.02671.026
316233AE1-074 C
Adder
3.7705882352941183.205
316240AF1-291 C
Adder
3.5117647058823532.985
316294AC1-161 C
50/50
8.5288.528
316312AB1-027 C
50/50
0.8920.892
316382AG1-145 C
50/50
0.6220.622
917332KELFORD E
Adder
2.43058823529411772.066
924516AB2-100 E1
Adder
4.20352941176470553.573
924517AB2-100 E2
Adder
4.20352941176470553.573
926785AC1-164_E
50/50
31.9131.91
934065AD1-033 E
Adder
8.4505882352941187.183
937226AE2-253 E
Adder
9.88.33
939612AE1-191 E
Adder
9.3494117647058837.947
939246AE1-155 E
Adder
13.111.135
918512AA1-065 E OP
Adder
8.397647058823537.138
919153AA1-139 E2
Adder
6.8435294117647065.817
919152AA1-139 E1
Adder
6.8435294117647065.817
920692AA2-178 E
Adder
6.5094117647058835.533
923994AB2-040_E
Adder
8.8282352941176477.504
924814AB2-134 E
Adder
21.28941176470588218.096
316084AB2-161 E
Adder
9.0294117647058827.675
925122AB2-169 E
Adder
8.6200000000000017.327
316088AB2-174 E
Adder
9.3494117647058837.947
932046AC2-012 E
Adder
22.12352941176470718.805
316311AC2-079 C
Adder
9.4458823529411768.029
932596AC2-079 E
Adder
15.41176470588235313.1
934146AD1-041 E
Adder
5.8435294117647054.967
934576AD1-082 E
Adder
7.1941176470588246.115
316349AD2-085 C
Adder
5.6658823529411774.816
936666AD2-085 E
Adder
9.244705882352947.858
961611AG1-000B C
Adder
26.9129411764705922.876
941591AE2-156 C
Adder
30.2317647058823525.697
944581AF1-123 C
Adder
76.4247058823529464.961
944582AF1-123 E
Adder
175.0035294117647148.753
944591AF1-124 C
Adder
76.6964705882352965.192
944592AF1-124 E
Adder
175.63764705882355149.292
944601AF1-125 C
Adder
75.2470588235294163.96
944602AF1-125 E
Adder
172.25764705882355146.419
944631AF1-128 C
50/50
67.28467.284
958261AF2-120 C
Adder
9.4070588235294137.996
958262AF2-120 E
Adder
6.2717647058823545.331
934501AD1-074 C
Adder
52.4929411764705944.619
934502AD1-074 E
Adder
26.72117647058823722.713
934511AD1-075 C
Adder
13.12352941176470511.155
934512AD1-075 E
Adder
6.685.678
935161AD1-151 C
Adder
27.11411764705882623.047
935162AD1-151 E
Adder
18.0752941176470615.364
938531AE1-072 C
Adder
29.3776470588235324.971
938532AE1-072 E
Adder
15.31411764705882413.017
939191AE1-149 C
Adder
17.43176470588235514.817
939192AE1-149 E
Adder
11.6211764705882359.878
939602AE1-190 E
Adder
2.33764705882352961.987
940431AE2-027 C
Adder
21.05411764705882417.896
940432AE2-027 E
Adder
14.03647058823529311.931
940481AE2-033 C
Adder
23.8117647058823520.24
940482AE2-033 E
Adder
16.0529411764705913.645
940541AE2-040 C
Adder
4.2317647058823533.597
940551AE2-041 C
Adder
11.82823529411764710.054
940641AE2-051 C
Adder
25.38941176470588321.581
940642AE2-051 E
Adder
16.92588235294117614.387
941101AE2-104 C
Adder
5.5447058823529414.713
941102AE2-104 E
Adder
8.815294117647067.493
943471AF1-018 C
Adder
11.82823529411764710.054
944641AF1-129 C
Adder
166.98352941176472141.936
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.017.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.3345.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.55730.557
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.912122.912
G-007PJM->LTFIMP_G-007
CMTX_NF
6.8256.825
NYPJM->LTFIMP_NY
CLTF
3.1153.115
LGEELTFEXP_LGEE->PJM
CLTF
1.8191.819
WECLTFEXP_WEC->PJM
CLTF
0.9390.939
CPLELTFEXP_CPLE->PJM
CLTF
14.714.7
TVALTFEXP_TVA->PJM
CLTF
8.1358.135
MECLTFEXP_MEC->PJM
CLTF
5.5435.543
LAGNLTFEXP_LAGN->PJM
CLTF
10.28110.281
SIGELTFEXP_SIGE->PJM
CLTF
0.3490.349
O66PJM->LTFIMP_O-066
CMTX_NF
43.443.4

Details for 8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.6 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3658.56
MW Contribution:158.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.485882352941176430.413
961942AG1-037 E
Adder
0.32352941176470590.275
966621AG1-532 C
Adder
1.28235294117647071.09
966622AG1-532 E
Adder
0.85529411764705890.727
3145413WATKINS
Adder
0.69764705882352940.593
3145723EMPORIA
Adder
0.39411764705882360.335
918492AA1-063AE OP
Adder
3.83529411764705853.26
920042AA2-088 E OP
Adder
10.4070588235294138.846
934521AD1-076 C
Adder
12.16705882352941310.342
934522AD1-076 E
Adder
6.2011764705882355.271
943172AE2-346 E
Adder
0.58235294117647060.495
944011AF1-069 C
Adder
10.9635294117647079.319
944012AF1-069 E
Adder
4.2588235294117653.62
960081AF2-299 C
Adder
1.71058823529411771.454
960082AF2-299 E
Adder
1.140.969
316141AB2-099 E
Adder
0.242352941176470580.206
900672V4-068 E
Adder
0.34588235294117650.294
923573AB1-173 E OP
Adder
3.00235294117647072.552
940492AE2-034 E
Adder
3.11882352941176462.651
941031AE2-094 C
Adder
33.5552941176470628.522
941032AE2-094 E
Adder
15.02823529411764612.774
946281AF1-292 C
Adder
1.4152941176470591.203
946282AF1-292 E
Adder
0.9435294117647060.802
3145393UNCAMP
Adder
6.2117647058823535.28
916042Z1-036 E
Adder
29.55058823529411825.118
938771AE1-103 C
Adder
3.0152941176470592.563
938772AE1-103 E
Adder
4.16470588235294153.54
3142296MT RD221
50/50
0.1630.163
3142366NRTHEST
50/50
0.2360.236
3143316POE
Adder
1.46235294117647091.243
3145256KINGFORK
Adder
1.10588235294117650.94
3145506HICKORY
Adder
2.3435294117647061.992
3150391LDYSMT3
50/50
7.2317.231
3150401LDYSMT4
50/50
7.2447.244
3150411LDYSMT5
50/50
7.2677.267
3150601CHESTF5
Adder
77.6188235294117765.976
3150651CHESTF6
Adder
21.86235294117646818.583
3150691DARBY 3
50/50
3.2613.261
3150701DARBY 4
50/50
3.2653.265
3150731STONECA
Adder
8.157647058823536.934
3150831SPRUNCA
Adder
10.5929411764705879.004
3150841SPRUNCB
Adder
10.5929411764705879.004
3150921YORKTN3
Adder
139.0764705882353118.215
925865AC1-065 E
Adder
19.93176470588235516.942
926412AC1-112 E
50/50
1.481.48
926472AC1-118 E
Adder
1.221.037
926662AC1-147 E
Adder
1.43647058823529421.221
926755AC1-161 E
Adder
14.11411764705882511.997
927226AC1-216 E
Adder
8.9282352941176487.589
934392AD1-063 E
Adder
1.28823529411764711.095
934782AD1-105 E
Adder
6.1211764705882365.203
935112AD1-144 E
Adder
1.02705882352941180.873
936582AD2-073 E
Adder
1.24588235294117641.059
936591AD2-074 C
Adder
6.6105882352941175.619
936592AD2-074 E
Adder
10.7858823529411769.168
942341AE2-247 C
Adder
1.6082352941176471.367
942342AE2-247 E
Adder
2.22117647058823531.888
943461AF1-017 C
Adder
1.4552941176470591.237
943462AF1-017 E
Adder
2.37411764705882342.018
943612AF1-032 E
Adder
0.98941176470588230.841
943741AF1-042 C
Adder
3.4588235294117652.94
943742AF1-042 E
Adder
5.6435294117647064.797
944491AF1-114 C
Adder
6.6258823529411775.632
944492AF1-114 E
Adder
9.1505882352941177.778
958502AF2-144 E
Adder
1.0717647058823530.911
961951AG1-038 C
Adder
3.8235294117647063.25
961952AG1-038 E
Adder
5.2788235294117654.487
966661AG1-536 C
Adder
6.3847058823529415.427
966662AG1-536 E
Adder
8.587.293
966871AG1-558 C
50/50
3.1913.191
966872AG1-558 E
50/50
1.6071.607
966881AG1-559 C
50/50
3.5873.587
966882AG1-559 E
50/50
1.8071.807
316076AC2-137 E
Adder
1.6835294117647061.431
316078AC2-138 E
Adder
1.10352941176470590.938
316157AD2-030 E
Adder
1.4152941176470591.203
913392Y1-086 E
Adder
2.33294117647058831.983
916192Z1-068 E
Adder
2.0305882352941181.726
923832AB2-022 E
Adder
1.31764705882352961.12
923842AB2-024 E
Adder
2.16941176470588241.844
923852AB2-025 E
Adder
1.10705882352941170.941
923862AB2-026 E
Adder
1.09058823529411760.927
930122AB1-027 E
50/50
1.821.82
938552AE1-074 E
Adder
1.32352941176470581.125
938562AE1-075 E
Adder
0.92941176470588240.79
939312AE1-162 E
Adder
1.5964705882352941.357
946262AF1-291 E
Adder
1.67294117647058821.422
957492AF2-043 E
Adder
1.52235294117647071.294
957601AF2-054 C
Adder
2.5211764705882352.143
957602AF2-054 E
Adder
1.68117647058823551.429
962861AG1-135 C
Adder
7.2058823529411776.125
962862AG1-135 E
Adder
4.8047058823529414.084
962962AG1-145 E
Adder
1.73058823529411781.471
963611AG1-210 C
Adder
0.78823529411764710.67
963612AG1-210 E
Adder
1.18235294117647041.005
964211AG1-282 C
Adder
2.3988235294117652.039
964212AG1-282 E
Adder
1.59882352941176481.359
901082W1-029 E
Adder
33.6023529411764728.562
917122Z2-027 E
Adder
1.42117647058823531.208
925332AB2-190 E
Adder
9.4164705882352948.004
925522AC1-027 E
Adder
1.3152941176470591.118
942001AE2-212 C
Adder
2.4364705882352942.071
942002AE2-212 E
Adder
1.62470588235294121.381
957832AF2-077 E
Adder
1.67882352941176481.427
957871AF2-081 C
Adder
10.7011764705882359.096
957872AF2-081 E
Adder
4.58588235294117653.898
957971AF2-091 C
Adder
2.25294117647058821.915
957972AF2-091 E
Adder
3.1105882352941182.644
958161AF2-110 C
Adder
1.46000000000000021.241
958162AF2-110 E
Adder
2.3235294117647061.975
3138116ELKO L286
Adder
1.75647058823529421.493
3141813NORNECK
Adder
1.05058823529411760.893
926071AC1-086 C
Adder
1.16117647058823530.987
933291AC2-141 C
Adder
33.06352941176470528.104
933292AC2-141 E
Adder
14.11411764705882511.997
939411AE1-173 C
Adder
85.3176470588235272.52
939412AE1-173 E
Adder
56.8788235294117748.347
934012AD1-025 E
Adder
11.569.826
927041AC1-191 C
50/50
12.81112.811
927042AC1-191 E
50/50
6.3816.381
933981AD1-022 C
Adder
8.6517647058823537.354
933982AD1-022 E
Adder
4.7105882352941174.004
3130536PAPERMILL
Adder
8.0105882352941196.809
3145946PLYMOUTH TP
Adder
0.32235294117647060.274
3146326AYDLETT TAP
Adder
1.44941176470588241.232
316004AC1-112 C
50/50
0.4320.432
316160AE1-175 E
Adder
1.4270588235294121.213
316169AC1-164 GEN
Adder
50.7141176470588243.107
316233AE1-074 C
Adder
2.6270588235294122.233
316240AF1-291 C
Adder
2.5105882352941182.134
316312AB1-027 C
50/50
0.6940.694
924516AB2-100 E1
Adder
2.69764705882352952.293
924517AB2-100 E2
Adder
2.69764705882352952.293
926785AC1-164_E
Adder
22.7847058823529419.367
934065AD1-033 E
Adder
5.4035294117647064.593
937226AE2-253 E
Adder
6.2658823529411765.326
939612AE1-191 E
Adder
6.8023529411764715.782
3150371LDYSMT1
50/50
6.9556.955
3150381LDYSMT2
50/50
7.0467.046
315051AA1-145 CT1
50/50
7.0497.049
315052AA1-145 CT2
50/50
7.0467.046
939246AE1-155 E
Adder
10.3364705882352948.786
918512AA1-065 E OP
Adder
5.3564705882352944.553
919153AA1-139 E2
Adder
4.3764705882352953.72
919152AA1-139 E1
Adder
4.3764705882352953.72
920692AA2-178 E
Adder
4.1576470588235293.534
923994AB2-040_E
Adder
5.6294117647058834.785
924814AB2-134 E
Adder
14.62588235294117712.432
316084AB2-161 E
Adder
6.0470588235294125.14
925122AB2-169 E
Adder
5.48117647058823554.659
316088AB2-174 E
Adder
5.9647058823529415.07
932046AC2-012 E
Adder
14.21176470588235412.08
316311AC2-079 C
Adder
6.1752941176470585.249
932596AC2-079 E
Adder
10.0764705882352948.565
934146AD1-041 E
Adder
4.2517647058823533.614
934576AD1-082 E
Adder
4.8176470588235294.095
316349AD2-085 C
Adder
3.71176470588235263.155
936666AD2-085 E
Adder
6.0552941176470595.147
961611AG1-000B C
Adder
18.15411764705882215.431
941591AE2-156 C
Adder
19.41529411764705816.503
944581AF1-123 C
Adder
48.8541176470588341.526
944582AF1-123 E
Adder
111.8694117647058995.089
944591AF1-124 C
Adder
49.02705882352941641.673
944592AF1-124 E
Adder
112.2741176470588395.433
944601AF1-125 C
Adder
48.1011764705882440.886
944602AF1-125 E
Adder
110.112941176470693.596
944631AF1-128 C
Adder
48.5670588235294141.282
958261AF2-120 C
Adder
7.4223529411764716.309
958262AF2-120 E
Adder
4.9482352941176484.206
934501AD1-074 C
Adder
33.50117647058823428.476
934502AD1-074 E
Adder
17.05411764705882414.496
934511AD1-075 C
Adder
8.3752941176470597.119
934512AD1-075 E
Adder
4.2635294117647063.624
935161AD1-151 C
Adder
18.74470588235294215.933
935162AD1-151 E
Adder
12.49647058823529410.622
938531AE1-072 C
Adder
18.7870588235294115.969
938532AE1-072 E
Adder
9.7941176470588228.325
939191AE1-149 C
Adder
11.85294117647058710.075
939192AE1-149 E
Adder
7.9023529411764716.717
939261AE1-157 C
50/50
21.18921.189
939262AE1-157 E
50/50
11.49311.493
939602AE1-190 E
Adder
1.70117647058823531.446
940431AE2-027 C
Adder
14.94470588235294212.703
940432AE2-027 E
Adder
9.9623529411764718.468
940481AE2-033 C
Adder
15.38117647058823513.074
940482AE2-033 E
Adder
10.3694117647058828.814
940541AE2-040 C
Adder
2.73647058823529442.326
940551AE2-041 C
Adder
8.5917647058823537.303
940641AE2-051 C
Adder
15.55529411764705813.222
940642AE2-051 E
Adder
10.3694117647058828.814
941101AE2-104 C
Adder
3.57882352941176453.042
941102AE2-104 E
Adder
5.69058823529411754.837
943471AF1-018 C
Adder
8.5917647058823537.303
944641AF1-129 C
Adder
120.07411764705883102.063
3150431FOUR RIVERA
50/50
4.4254.425
3150441FOUR RIVERB
50/50
4.4254.425
3150451FOUR RIVERC
50/50
5.4065.406
3150461FOUR RIVERD
50/50
4.3614.361
3150471FOUR RIVERE
50/50
4.3614.361
3150481FOUR RIVERF
50/50
5.3255.325
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.3184.318
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.54824.548
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.76217.762
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
75.17775.177
G-007PJM->LTFIMP_G-007
CMTX_NF
5.2915.291
NYPJM->LTFIMP_NY
CLTF
2.4212.421
LGEELTFEXP_LGEE->PJM
CLTF
1.011.01
WECLTFEXP_WEC->PJM
CLTF
0.5150.515
CPLELTFEXP_CPLE->PJM
CLTF
9.069.06
TVALTFEXP_TVA->PJM
CLTF
4.8114.811
MECLTFEXP_MEC->PJM
CLTF
3.1253.125
LAGNLTFEXP_LAGN->PJM
CLTF
6.0826.082
SIGELTFEXP_SIGE->PJM
CLTF
0.1960.196
O66PJM->LTFIMP_O-066
CMTX_NF
33.64633.646

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.88 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1342.55
MW Contribution:61.92
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:127.67 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1350.99
MW Contribution:60.09
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.410588235294117640.349
961672AG1-007 E
Adder
0.232941176470588260.198
961941AG1-037 C
Adder
0.212941176470588240.181
961942AG1-037 E
Adder
0.14235294117647060.121
963041AG1-153 C
50/50
3.6733.673
963042AG1-153 E
50/50
5.5095.509
964791AG1-342 C
Adder
1.48470588235294131.262
964792AG1-342 E
Adder
0.99058823529411770.842
966621AG1-532 C
Adder
0.60117647058823530.511
966622AG1-532 E
Adder
0.40.34
3145413WATKINS
Adder
0.279999999999999970.238
3145723EMPORIA
Adder
0.18470588235294120.157
3151311EDGECMA
Adder
6.8129411764705895.791
918492AA1-063AE OP
Adder
1.72705882352941181.468
918532AA1-067 E
Adder
0.30941176470588240.263
919692AA2-053 E OP
Adder
1.80705882352941181.536
920042AA2-088 E OP
Adder
4.3847058823529413.727
925785AC1-054 E
Adder
1.47764705882352951.256
926274AC1-105 E
Adder
1.13764705882352950.967
927146AC1-208 E
Adder
1.72941176470588241.47
934521AD1-076 C
Adder
5.1635294117647064.389
934522AD1-076 E
Adder
2.6317647058823532.237
943172AE2-346 E
Adder
0.255294117647058840.217
943902AF1-058 E
Adder
0.55294117647058830.47
944011AF1-069 C
50/50
8.8768.876
944012AF1-069 E
50/50
3.4483.448
959311AF2-222 C
Adder
5.57411764705882454.738
959312AF2-222 E
Adder
3.73411764705882383.174
960081AF2-299 C
Adder
0.80117647058823540.681
960082AF2-299 E
Adder
0.53411764705882360.454
316141AB2-099 E
Adder
0.107058823529411760.091
900672V4-068 E
Adder
0.149411764705882360.127
917342Z2-044 E
Adder
0.26117647058823530.222
922923AB1-081 E OP
Adder
1.63529411764705881.39
923263AB1-132 E OP
Adder
2.6305882352941182.236
923573AB1-173 E OP
Adder
1.40588235294117661.195
924162AB2-060 E OP
Adder
1.71764705882352931.46
924302AB2-077 E O1
Adder
0.54823529411764720.466
924312AB2-078 E O1
Adder
0.54823529411764720.466
924322AB2-079 E O1
Adder
0.54823529411764720.466
925612AC1-036 E
Adder
0.30.255
940492AE2-034 E
Adder
1.2952941176470591.101
941011AE2-092 C
Adder
-4.452941176470588-3.785
941031AE2-094 C
50/50
27.16527.165
941032AE2-094 E
50/50
12.16712.167
946281AF1-292 C
Adder
0.66352941176470580.564
946282AF1-292 E
Adder
0.44235294117647060.376
957481AF2-042 C
Adder
28.3424.089
957482AF2-042 E
Adder
18.89411764705882416.06
957861AF2-080 C
Adder
3.3247058823529412.826
957862AF2-080 E
Adder
1.47411764705882351.253
3145393UNCAMP
Adder
2.44352941176470572.077
916042Z1-036 E
Adder
11.93411764705882510.144
938771AE1-103 C
Adder
1.16941176470588240.994
938772AE1-103 E
Adder
1.61529411764705881.373
3145256KINGFORK
Adder
0.367058823529411770.312
3145506HICKORY
Adder
0.91764705882352950.78
926662AC1-147 E
Adder
0.53176470588235290.452
926755AC1-161 E
Adder
5.7376470588235294.877
935112AD1-144 E
Adder
0.339999999999999970.289
942341AE2-247 C
Adder
0.50235294117647060.427
942342AE2-247 E
Adder
0.69411764705882350.59
943461AF1-017 C
Adder
0.454117647058823570.386
943462AF1-017 E
Adder
0.74117647058823530.63
943612AF1-032 E
Adder
0.374117647058823550.318
3151021BRUNSWICKG1
50/50
5.4215.421
3151031BRUNSWICKG2
50/50
5.4215.421
3151041BRUNSWICKG3
50/50
5.4215.421
3151051BRUNSWICKS1
50/50
11.26311.263
3152411Z1-086 GT1
50/50
7.0067.006
3152421Z1-086 GT2
50/50
7.0037.003
3152431Z1-086 GT3
50/50
7.0037.003
3152441Z1-086 ST
50/50
12.19612.196
913392Y1-086 E
Adder
0.91764705882352950.78
916192Z1-068 E
Adder
0.77294117647058820.657
923832AB2-022 E
Adder
0.51764705882352950.44
923852AB2-025 E
Adder
0.50705882352941180.431
939312AE1-162 E
Adder
0.41294117647058820.351
957492AF2-043 E
Adder
0.57529411764705880.489
901082W1-029 E
Adder
13.19764705882352911.218
917122Z2-027 E
Adder
0.55999999999999990.476
925522AC1-027 E
Adder
0.50.425
957871AF2-081 C
Adder
4.1964705882352953.567
957872AF2-081 E
Adder
1.79882352941176471.529
958161AF2-110 C
Adder
0.53058823529411770.451
958162AF2-110 E
Adder
0.84352941176470590.717
3147223TWITTYS
Adder
0.332941176470588240.283
917512Z2-088 E OP1
Adder
2.1352941176470591.815
926071AC1-086 C
Adder
9.037647058823537.682
926072AC1-086 E
Adder
4.11294117647058853.496
927021AC1-189 C
Adder
3.66117647058823573.112
927022AC1-189 E
Adder
1.8235294117647061.55
936261AD2-033 C
Adder
4.2364705882352943.601
936262AD2-033 E
Adder
2.8247058823529412.401
933291AC2-141 C
Adder
13.44235294117647211.426
933292AC2-141 E
Adder
5.7376470588235294.877
934621AD1-088 C
Adder
4.3611764705882353.707
934622AD1-088 E
Adder
2.11.785
939411AE1-173 C
50/50
55.12655.126
939412AE1-173 E
50/50
36.75136.751
933981AD1-022 C
Adder
3.73.145
933982AD1-022 E
Adder
2.01411764705882361.712
962572AG1-106 E
Adder
0.51176470588235290.435
962571AG1-106 C
Adder
1.16941176470588240.994
3145946PLYMOUTH TP
Adder
0.136470588235294120.116
3146326AYDLETT TAP
Adder
0.56823529411764710.483
316263AC1-034 C
Adder
2.91411764705882352.477
316274AC1-208 C
Adder
3.8952941176470593.311
316336AC2-165 C
Adder
-10.758823529411764-9.145
917332KELFORD E
Adder
0.70117647058823530.596
924516AB2-100 E1
Adder
1.25176470588235311.064
924517AB2-100 E2
Adder
1.25176470588235311.064
925595AC1-034 E
Adder
2.19764705882352951.868
926206AC1-098 E
Adder
1.57411764705882361.338
926214AC1-099 E
Adder
0.520.442
927255AC1-221 E
Adder
1.65176470588235281.404
927264AC1-222 E
Adder
1.66470588235294131.415
932763AC2-100 E
Adder
1.12117647058823520.953
934065AD1-033 E
Adder
2.10705882352941171.791
937226AE2-253 E
Adder
2.4552941176470592.087
918512AA1-065 E OP
Adder
2.34000000000000031.989
919153AA1-139 E2
Adder
1.71529411764705891.458
919152AA1-139 E1
Adder
1.71529411764705891.458
919710AA2-057 E
Adder
1.72588235294117661.467
920692AA2-178 E
Adder
1.72705882352941181.468
923994AB2-040_E
Adder
2.63647058823529432.241
924022AB2-043 E O1
Adder
2.11764705882352941.8
924152AB2-059 E OP
Adder
2.31764705882352961.97
925122AB2-169 E
Adder
2.4564705882352942.088
316088AB2-174 E
Adder
2.7941176470588242.375
932046AC2-012 E
Adder
5.2588235294117654.47
316311AC2-079 C
Adder
1.9682352941176471.673
932596AC2-079 E
Adder
3.2117647058823532.73
316349AD2-085 C
Adder
1.15882352941176480.985
936666AD2-085 E
Adder
1.89058823529411771.607
941591AE2-156 C
Adder
7.202352941176476.122
944581AF1-123 C
Adder
19.11999999999999716.252
944582AF1-123 E
Adder
43.7823529411764837.215
944591AF1-124 C
Adder
19.18823529411764616.31
944592AF1-124 E
Adder
43.9411764705882437.35
944601AF1-125 C
Adder
18.82588235294117516.002
944602AF1-125 E
Adder
43.0952941176470636.631
962561AG1-105 C
Adder
3.70941176470588243.153
962562AG1-105 E
Adder
2.4729411764705882.102
964241AG1-285 C
Adder
5.3647058823529414.56
964242AG1-285 E
Adder
3.57647058823529433.04
3137643SOCKMAN
Adder
0.30470588235294120.259
932632AC2-084 E
Adder
1.3917647058823531.183
934321AD1-056 C
Adder
2.72588235294117662.317
934322AD1-056 E
Adder
1.47882352941176461.257
934331AD1-057 C
Adder
1.52117647058823541.293
934332AD1-057 E
Adder
0.7917647058823530.673
934501AD1-074 C
Adder
14.2176470588235312.085
934502AD1-074 E
Adder
7.237647058823536.152
934511AD1-075 C
Adder
3.55411764705882363.021
934512AD1-075 E
Adder
1.80941176470588251.538
934612AD1-087 E
Adder
1.79882352941176471.529
935172AD1-152 E
Adder
2.6258823529411772.232
936161AD2-022 C
Adder
3.0882352941176472.625
936162AD2-022 E
Adder
1.85294117647058831.575
936171AD2-023 C
Adder
1.80117647058823521.531
936172AD2-023 E
Adder
0.97764705882352940.831
937482AD2-202 E
Adder
0.52588235294117650.447
938531AE1-072 C
Adder
7.3705882352941176.265
938532AE1-072 E
Adder
3.84235294117647053.266
938821AE1-108 C
Adder
-4.716470588235294-4.009
940481AE2-033 C
Adder
7.0611764705882366.002
940482AE2-033 E
Adder
4.7611764705882354.047
940541AE2-040 C
Adder
1.25411764705882361.066
940641AE2-051 C
50/50
11.53811.538
940642AE2-051 E
50/50
7.6927.692
941101AE2-104 C
Adder
1.31.105
941102AE2-104 E
Adder
2.06588235294117651.756
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5712.571
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.53211.532
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.0379.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.69643.696
G-007PJM->LTFIMP_G-007
CMTX_NF
1.0921.092
NYPJM->LTFIMP_NY
CLTF
0.5140.514
LGEELTFEXP_LGEE->PJM
CLTF
0.4480.448
WECLTFEXP_WEC->PJM
CLTF
0.2390.239
CPLELTFEXP_CPLE->PJM
CLTF
5.3965.396
TVALTFEXP_TVA->PJM
CLTF
2.4942.494
MECLTFEXP_MEC->PJM
CLTF
1.5141.514
LAGNLTFEXP_LAGN->PJM
CLTF
3.2073.207
SIGELTFEXP_SIGE->PJM
CLTF
0.0910.091
O66PJM->LTFIMP_O-066
CMTX_NF
6.9576.957

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.42 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2598.93
MW Contribution:147.82
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.96 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2758.53
MW Contribution:152.19
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.73882352941176480.628
961672AG1-007 E
Adder
0.41882352941176470.356
961791AG1-021 C
Adder
1.33058823529411761.131
961792AG1-021 E
Adder
1.13294117647058810.963
961941AG1-037 C
Adder
0.367058823529411770.312
961942AG1-037 E
Adder
0.244705882352941160.208
963041AG1-153 C
50/50
6.556.55
963042AG1-153 E
50/50
9.8259.825
964791AG1-342 C
Adder
3.09882352941176452.634
964792AG1-342 E
Adder
2.06588235294117651.756
966621AG1-532 C
Adder
1.15411764705882350.981
966622AG1-532 E
Adder
0.76941176470588240.654
3138533PONTONDP
Adder
0.49294117647058820.419
3145413WATKINS
Adder
0.451764705882352960.384
3145723EMPORIA
Adder
0.352941176470588260.3
3147133PAMPLIN
Adder
0.740.629
3151311EDGECMA
Adder
12.4152941176470610.553
3151531CLOVER1
50/50
12.55212.552
3151541CLOVER2
50/50
12.43612.436
918492AA1-063AE OP
Adder
3.0882352941176472.625
918532AA1-067 E
Adder
0.54705882352941180.465
919692AA2-053 E OP
Adder
3.30000000000000032.805
920042AA2-088 E OP
Adder
7.3835294117647066.276
925785AC1-054 E
Adder
2.882.448
926274AC1-105 E
Adder
2.3364705882352941.986
927146AC1-208 E
Adder
3.14470588235294152.673
934521AD1-076 C
Adder
9.1176470588235297.75
934522AD1-076 E
Adder
4.6470588235294123.95
943172AE2-346 E
Adder
0.440.374
943902AF1-058 E
Adder
1.11882352941176480.951
944011AF1-069 C
50/50
15.67315.673
944012AF1-069 E
50/50
6.0886.088
959311AF2-222 C
Adder
14.27882352941176512.137
959312AF2-222 E
Adder
9.5670588235294118.132
960081AF2-299 C
Adder
1.541.309
960082AF2-299 E
Adder
1.02588235294117650.872
316141AB2-099 E
Adder
0.183529411764705890.156
900672V4-068 E
Adder
0.254117647058823560.216
917342Z2-044 E
Adder
0.475294117647058870.404
922923AB1-081 E OP
Adder
2.9811764705882352.534
923263AB1-132 E OP
Adder
4.8517647058823534.124
923573AB1-173 E OP
Adder
2.65411764705882322.256
924162AB2-060 E OP
Adder
3.78117647058823543.214
924302AB2-077 E O1
Adder
1.18705882352941171.009
924312AB2-078 E O1
Adder
1.18705882352941171.009
924322AB2-079 E O1
Adder
1.18705882352941171.009
925612AC1-036 E
Adder
0.74705882352941180.635
940492AE2-034 E
Adder
2.3152941176470591.968
941031AE2-094 C
50/50
47.96747.967
941032AE2-094 E
50/50
21.48321.483
946281AF1-292 C
Adder
1.27411764705882361.083
946282AF1-292 E
Adder
0.84941176470588230.722
946301AF1-294 C
Adder
2.73529411764705932.325
946302AF1-294 E
Adder
2.3164705882352941.969
957481AF2-042 C
50/50
55.26355.263
957482AF2-042 E
50/50
36.84236.842
957861AF2-080 C
Adder
5.9388235294117655.048
957862AF2-080 E
Adder
2.6329411764705882.238
958211AF2-115 C
Adder
1.6635294117647061.414
958212AF2-115 E
Adder
1.41647058823529411.204
3145393UNCAMP
Adder
3.8517647058823533.274
916042Z1-036 E
Adder
21.67647058823529718.425
938771AE1-103 C
Adder
1.81647058823529431.544
938772AE1-103 E
Adder
2.50941176470588222.133
3143316POE
Adder
0.80823529411764720.687
3145506HICKORY
50/50
2.1612.161
926662AC1-147 E
Adder
1.23058823529411781.046
926755AC1-161 E
50/50
37.13537.135
3151021BRUNSWICKG1
50/50
9.6689.668
3151031BRUNSWICKG2
50/50
9.6689.668
3151041BRUNSWICKG3
50/50
9.6689.668
3151051BRUNSWICKS1
50/50
20.08620.086
3151081ELIZAR1
50/50
3.033.03
3151091ELIZAR2
50/50
2.9782.978
3151101ELIZAR3
50/50
3.0693.069
3152411Z1-086 GT1
50/50
12.45512.455
3152421Z1-086 GT2
50/50
12.4512.45
3152431Z1-086 GT3
50/50
12.4512.45
3152441Z1-086 ST
50/50
21.68121.681
913392Y1-086 E
Adder
1.8917647058823531.608
916192Z1-068 E
50/50
1.7941.794
923832AB2-022 E
Adder
1.06823529411764720.908
923852AB2-025 E
Adder
0.98588235294117640.838
957601AF2-054 C
Adder
-1.2505882352941176-1.063
901082W1-029 E
Adder
23.54352941176470520.012
917122Z2-027 E
Adder
1.1117647058823530.945
925522AC1-027 E
50/50
1.1581.158
957871AF2-081 C
50/50
9.4939.493
957872AF2-081 E
50/50
4.0684.068
3147223TWITTYS
Adder
0.82823529411764710.704
917512Z2-088 E OP1
Adder
3.83294117647058833.258
926071AC1-086 C
Adder
16.6705882352941214.17
926072AC1-086 E
Adder
7.5870588235294126.449
927021AC1-189 C
Adder
6.5388235294117655.558
927022AC1-189 E
Adder
3.25764705882352962.769
936261AD2-033 C
Adder
10.7294117647058829.12
936262AD2-033 E
Adder
7.1529411764705896.08
933291AC2-141 C
50/50
86.99486.994
933292AC2-141 E
50/50
37.13537.135
934621AD1-088 C
50/50
9.1619.161
934622AD1-088 E
50/50
4.4114.411
939411AE1-173 C
50/50
86.92186.921
939412AE1-173 E
50/50
57.94757.947
916191Z1-068 C
50/50
0.0420.042
933981AD1-022 C
Adder
6.4741176470588245.503
933982AD1-022 E
Adder
3.52470588235294142.996
962572AG1-106 E
Adder
0.9435294117647060.802
962571AG1-106 C
Adder
2.1564705882352941.833
3145946PLYMOUTH TP
Adder
0.24117647058823530.205
3146326AYDLETT TAP
Adder
1.25647058823529421.068
316185AD1-033 C
50/50
1.2261.226
316263AC1-034 C
Adder
5.31058823529411854.514
316274AC1-208 C
Adder
7.0835294117647066.021
316294AC1-161 C
50/50
14.21614.216
316316AC1-027 C
50/50
0.3010.301
917332KELFORD E
Adder
1.2282352941176471.044
924516AB2-100 E1
Adder
2.3717647058823532.016
924517AB2-100 E2
Adder
2.3717647058823532.016
925595AC1-034 E
Adder
4.00588235294117643.405
926206AC1-098 E
Adder
2.8317647058823532.407
926214AC1-099 E
Adder
0.93529411764705890.795
927255AC1-221 E
Adder
3.2152941176470592.733
927264AC1-222 E
Adder
3.3870588235294122.879
932763AC2-100 E
Adder
2.1788235294117651.852
934065AD1-033 E
50/50
5.0045.004
937226AE2-253 E
50/50
5.6435.643
918512AA1-065 E OP
Adder
3.98941176470588273.391
316017AA1-139 ULT1
50/50
1.0281.028
316018AA1-139 ULT2
50/50
1.0281.028
919153AA1-139 E2
50/50
3.8823.882
919152AA1-139 E1
50/50
3.8823.882
919710AA2-057 E
Adder
3.1364705882352942.666
920692AA2-178 E
Adder
3.0870588235294122.624
923994AB2-040_E
Adder
4.9776470588235294.231
924022AB2-043 E O1
Adder
4.6082352941176473.917
924152AB2-059 E OP
Adder
4.2235294117647063.59
925122AB2-169 E
Adder
4.3388235294117653.688
316088AB2-174 E
Adder
5.3035294117647064.508
316375AC2-012 C
50/50
1.2551.255
932046AC2-012 E
50/50
12.1712.17
316388AE2-253 GEN
50/50
1.8981.898
941591AE2-156 C
50/50
16.7516.75
944581AF1-123 C
50/50
45.64445.644
944582AF1-123 E
50/50
104.52104.52
944591AF1-124 C
50/50
45.80645.806
944592AF1-124 E
50/50
104.898104.898
944601AF1-125 C
50/50
44.94144.941
944602AF1-125 E
50/50
102.879102.879
962561AG1-105 C
Adder
7.7917647058823536.623
962562AG1-105 E
Adder
5.1941176470588244.415
964241AG1-285 C
Adder
11.7588235294117649.995
964242AG1-285 E
Adder
7.846.664
3137643SOCKMAN
Adder
0.56941176470588240.484
932632AC2-084 E
Adder
2.50352941176470622.128
934321AD1-056 C
Adder
4.99411764705882364.245
934322AD1-056 E
Adder
2.70941176470588242.303
934331AD1-057 C
Adder
2.78588235294117632.368
934332AD1-057 E
Adder
1.45058823529411771.233
934501AD1-074 C
Adder
25.10470588235294221.339
934502AD1-074 E
Adder
12.7810.863
934511AD1-075 C
Adder
6.2764705882352945.335
934512AD1-075 E
Adder
3.19529411764705932.716
934611AD1-087 C
50/50
1.2361.236
934612AD1-087 E
50/50
3.5653.565
935172AD1-152 E
Adder
5.2058823529411774.425
937481AD2-202 C
50/50
0.3590.359
937482AD2-202 E
50/50
1.0431.043
938531AE1-072 C
50/50
16.39816.398
938532AE1-072 E
50/50
8.5488.548
940481AE2-033 C
Adder
13.6776470588235311.626
940482AE2-033 E
Adder
9.2211764705882357.838
940541AE2-040 C
Adder
2.4364705882352942.071
940641AE2-051 C
50/50
26.4726.47
940642AE2-051 E
50/50
17.64717.647
942461AE2-259 C
Adder
6.5341176470588245.554
942462AE2-259 E
Adder
4.3564705882352943.703
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.7574.757
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.52724.527
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.91517.915
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.65881.658
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1242.124
NYPJM->LTFIMP_NY
CLTF
0.9860.986
LGEELTFEXP_LGEE->PJM
CLTF
0.950.95
WECLTFEXP_WEC->PJM
CLTF
0.5060.506
CPLELTFEXP_CPLE->PJM
CLTF
9.989.98
TVALTFEXP_TVA->PJM
CLTF
4.8674.867
MECLTFEXP_MEC->PJM
CLTF
3.1033.103
LAGNLTFEXP_LAGN->PJM
CLTF
6.2356.235
SIGELTFEXP_SIGE->PJM
CLTF
0.1890.189
O66PJM->LTFIMP_O-066
CMTX_NF
13.52713.527

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.3 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3390.97
MW Contribution:137.93
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:138.84 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4471.41
MW Contribution:162.64
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
963041AG1-153 C
Adder
4.8047058823529414.084
963042AG1-153 E
Adder
7.2070588235294136.126
3145413WATKINS
Adder
0.62117647058823530.528
920042AA2-088 E OP
Adder
9.3552941176470597.952
934521AD1-076 C
Adder
10.8305882352941179.206
944011AF1-069 C
Adder
11.3364705882352949.636
944012AF1-069 E
Adder
4.4035294117647063.743
940492AE2-034 E
Adder
2.7635294117647062.349
941031AE2-094 C
Adder
34.69411764705882529.49
941032AE2-094 E
Adder
15.53882352941176513.208
3145393UNCAMP
Adder
5.5035294117647064.678
916042Z1-036 E
Adder
26.0235294117647122.12
938771AE1-103 C
Adder
2.66470588235294152.265
938772AE1-103 E
Adder
3.67882352941176463.127
3143316POE
Adder
1.28352941176470581.091
3145256KINGFORK
Adder
0.94941176470588240.807
3145506HICKORY
Adder
2.04352941176470631.737
3150601CHESTF5
Adder
59.5223529411764750.594
3150651CHESTF6
Adder
17.73411764705882415.074
3150731STONECA
Adder
6.53294117647058855.553
3150831SPRUNCA
50/50
8.7958.795
3150841SPRUNCB
50/50
8.7958.795
3150921YORKTN3
Adder
111.6988235294117794.944
925865AC1-065 E
Adder
15.09882352941176512.834
926412AC1-112 E
Adder
1.03294117647058830.878
926662AC1-147 E
Adder
1.24588235294117641.059
926755AC1-161 E
Adder
12.22823529411764710.394
927226AC1-216 E
Adder
7.2941176470588246.2
934392AD1-063 E
Adder
0.97058823529411760.825
935112AD1-144 E
Adder
0.88235294117647060.75
936591AD2-074 C
Adder
4.9882352941176474.24
936592AD2-074 E
Adder
8.1388235294117656.918
942341AE2-247 C
Adder
1.39529411764705881.186
942342AE2-247 E
Adder
1.92705882352941171.638
943461AF1-017 C
Adder
1.26235294117647071.073
943462AF1-017 E
Adder
2.061.751
943612AF1-032 E
Adder
0.86235294117647050.733
943741AF1-042 C
Adder
2.61058823529411742.219
943742AF1-042 E
Adder
4.2588235294117653.62
958502AF2-144 E
Adder
1.07058823529411760.91
961951AG1-038 C
Adder
2.88470588235294122.452
961952AG1-038 E
Adder
3.98470588235294133.387
966661AG1-536 C
Adder
4.8058823529411764.085
966662AG1-536 E
Adder
6.4588235294117655.49
966871AG1-558 C
Adder
2.1964705882352941.867
966872AG1-558 E
Adder
1.10705882352941170.941
966881AG1-559 C
Adder
2.14941176470588241.827
966882AG1-559 E
Adder
1.08235294117647070.92
3152251N ANNA1
50/50
47.25147.251
3152261N ANNA2
50/50
47.2747.27
316076AC2-137 E
Adder
1.23411764705882351.049
316157AD2-030 E
Adder
1.07647058823529430.915
913392Y1-086 E
Adder
2.041.734
916192Z1-068 E
Adder
1.76588235294117651.501
923832AB2-022 E
Adder
1.1517647058823530.979
923842AB2-024 E
Adder
1.62470588235294121.381
923852AB2-025 E
Adder
1.0352941176470590.88
923862AB2-026 E
Adder
1.08941176470588250.926
925022AB2-158 E
50/50
5.0315.031
930122AB1-027 E
Adder
1.27058823529411781.08
938552AE1-074 E
50/50
1.2191.219
938562AE1-075 E
Adder
0.92941176470588240.79
939312AE1-162 E
Adder
1.3482352941176471.146
946262AF1-291 E
Adder
1.36823529411764721.163
957492AF2-043 E
Adder
1.32705882352941161.128
957601AF2-054 C
Adder
1.91764705882352931.63
957602AF2-054 E
Adder
1.27882352941176471.087
962861AG1-135 C
Adder
5.42823529411764754.614
962862AG1-135 E
Adder
3.6188235294117653.076
962962AG1-145 E
Adder
1.34235294117647071.141
901082W1-029 E
Adder
29.42941176470588325.015
917122Z2-027 E
Adder
1.24470588235294131.058
925332AB2-190 E
Adder
7.6305882352941186.486
925522AC1-027 E
Adder
1.1435294117647060.972
942001AE2-212 C
Adder
2.0505882352941181.743
942002AE2-212 E
Adder
1.36705882352941171.162
957832AF2-077 E
Adder
1.31411764705882361.117
957871AF2-081 C
Adder
9.347.939
957872AF2-081 E
Adder
4.0035294117647063.403
958161AF2-110 C
Adder
1.27411764705882361.083
958162AF2-110 E
Adder
2.02588235294117651.722
3138116ELKO L286
Adder
1.28705882352941181.094
933291AC2-141 C
Adder
28.64705882352941324.35
933292AC2-141 E
Adder
12.22823529411764710.394
939411AE1-173 C
50/50
82.56982.569
939412AE1-173 E
50/50
55.04655.046
934012AD1-025 E
Adder
9.442352941176478.026
927041AC1-191 C
Adder
8.827.497
927042AC1-191 E
Adder
4.3941176470588243.735
3130536PAPERMILL
Adder
6.0070588235294125.106
3145946PLYMOUTH TP
Adder
0.287058823529411760.244
3146326AYDLETT TAP
Adder
1.26470588235294111.075
316160AE1-175 E
Adder
1.10705882352941170.941
316164AC1-076_C
50/50
1.0121.012
316169AC1-164 GEN
Adder
37.0447058823529431.488
316170AC1-121 C
Adder
2.1788235294117651.852
316192AB2-158 C
50/50
1.8991.899
316233AE1-074 C
50/50
2.4192.419
316240AF1-291 C
Adder
2.05294117647058851.745
316254AC1-120 C
Adder
6.3435294117647065.392
924516AB2-100 E1
Adder
2.50705882352941162.131
924517AB2-100 E2
Adder
2.50705882352941162.131
926785AC1-164_E
Adder
16.64352941176470714.147
934065AD1-033 E
Adder
4.7094117647058834.003
937226AE2-253 E
Adder
5.4670588235294124.647
939612AE1-191 E
Adder
5.162352941176474.388
926004AC1-076_E
50/50
5.7785.778
926486AC1-120 E
Adder
3.26823529411764732.778
926502AC1-121 E
Adder
1.02470588235294110.871
939246AE1-155 E
Adder
7.7800000000000016.613
919153AA1-139 E2
Adder
3.823.247
919152AA1-139 E1
Adder
3.823.247
920692AA2-178 E
Adder
3.6835294117647063.131
924814AB2-134 E
Adder
11.94705882352941210.155
316084AB2-161 E
Adder
5.2058823529411774.425
316044AC1-158 C1
50/50
15.00715.007
316045AC1-158 C2
50/50
15.00715.007
926739AC1-158 E1
50/50
39.12239.122
926740AC1-158 E2
50/50
39.12239.122
932046AC2-012 E
Adder
12.32588235294117710.477
316311AC2-079 C
Adder
5.3611764705882364.557
932596AC2-079 E
Adder
8.7482352941176477.436
934146AD1-041 E
Adder
3.22588235294117662.742
934576AD1-082 E
Adder
4.1482352941176473.526
316349AD2-085 C
Adder
3.222.737
936666AD2-085 E
Adder
5.2529411764705884.465
961611AG1-000B C
Adder
15.01294117647058712.761
941591AE2-156 C
Adder
16.84235294117647214.316
944581AF1-123 C
Adder
42.58941176470588636.201
944582AF1-123 E
Adder
97.5247058823529582.896
944591AF1-124 C
Adder
42.74117647058823636.33
944592AF1-124 E
Adder
97.8776470588235383.196
944601AF1-125 C
Adder
41.9329411764705935.643
944602AF1-125 E
Adder
95.9941176470588381.595
944631AF1-128 C
Adder
37.24352941176470531.657
958261AF2-120 C
Adder
5.5870588235294124.749
958262AF2-120 E
Adder
3.7247058823529413.166
934501AD1-074 C
Adder
29.82235294117647225.349
934502AD1-074 E
Adder
15.18117647058823612.904
934511AD1-075 C
Adder
3.1717647058823532.696
935161AD1-151 C
Adder
15.24705882352941312.96
935162AD1-151 E
Adder
10.1647058823529428.64
938531AE1-072 C
Adder
16.40352941176470513.943
938532AE1-072 E
Adder
8.5517647058823547.269
939191AE1-149 C
Adder
10.152941176470598.63
939192AE1-149 E
Adder
6.7682352941176475.753
939261AE1-157 C
Adder
12.43411764705882510.569
939262AE1-157 E
Adder
6.7447058823529415.733
939602AE1-190 E
Adder
1.29058823529411761.097
940431AE2-027 C
Adder
12.27647058823529510.435
940432AE2-027 E
Adder
8.1835294117647066.956
940481AE2-033 C
Adder
14.37882352941176512.222
940482AE2-033 E
Adder
9.6941176470588258.24
940541AE2-040 C
Adder
2.562.176
940551AE2-041 C
Adder
6.4717647058823545.501
940641AE2-051 C
50/50
15.61115.611
940642AE2-051 E
50/50
10.40710.407
941101AE2-104 C
Adder
3.1211764705882352.653
941102AE2-104 E
Adder
4.9623529411764714.218
943471AF1-018 C
Adder
6.4717647058823545.501
944641AF1-129 C
Adder
97.3976470588235282.788
3150851SPRUNCC
50/50
0.1580.158
3150861SPRUNCD
50/50
0.1580.158
316303AF2-085
50/50
3.7313.731
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.9713.971
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.2045.204
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.39910.399
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
66.04366.043
G-007PJM->LTFIMP_G-007
CMTX_NF
3.9253.925
NYPJM->LTFIMP_NY
CLTF
1.9221.922
LGEELTFEXP_LGEE->PJM
CLTF
0.310.31
WECLTFEXP_WEC->PJM
CLTF
0.1350.135
CPLELTFEXP_CPLE->PJM
CLTF
8.348.34
TVALTFEXP_TVA->PJM
CLTF
3.2553.255
MECLTFEXP_MEC->PJM
CLTF
1.3051.305
LAGNLTFEXP_LAGN->PJM
CLTF
4.1614.161
SIGELTFEXP_SIGE->PJM
CLTF
0.0740.074
O66PJM->LTFIMP_O-066
CMTX_NF
25.06225.062
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
314225 to 314227 ckt 1
314214 to 314903 ckt 1
314286 to 314309 ckt 1
314287 to 314260 ckt 1
314218 to 314908 ckt 2
314466 to 314508 ckt 1
314309 to 314338 ckt 1
314196 to 314911 ckt 2
314236 to 314218 ckt 1
314260 to 314225 ckt 1
314902 to 314914 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314911 to 313483 ckt 1
314914 to 314322 ckt 1
314923 to 314924 ckt 1
314934 to 314916 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6FENT1-8FENTRES 230.0/500.0 kV Ckt 1 transformer
DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 3_SRT-A
OPAC112.51 %1130.82B1272.23410.0
GD1DVP
6FENT1-8FENTRES 230.0/500.0 kV Ckt 2 transformer
DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 1_SRT-A
OPAC112.51 %1130.82B1272.23410.0
GD1DVP
6FENT1-8FENTRES 230.0/500.0 kV Ckt 3 transformer
DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 1_SRT-A
OPAC112.51 %1130.82B1272.23410.0
GD1DVP
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
OPAC128.71 %1123.3B1445.8267.02
GD1DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S-1
OPAC111.78 %1058.16B1182.7863.16
GD1DVP
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
DVP_P1-2: LN 588_SRT-A
OPAC160.69 %678.68B1090.58236.24
GD1DVP
6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
OPAC121.31 %1123.3B1362.6567.02
GD1DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
OPAC103.49 %4070.2B4212.31158.45
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Base Case
OPAC104.11 %2442.12A2542.46212.48
GD1DVP
8FENTRES-6FENTRES 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 588_SRT-A
OPAC117.03 %1115.59B1305.6412.54
GD1DVP
8FENTRES-6FENTRES 500.0/230.0 kV Ckt 2 transformer
DVP_P1-2: LN 588_SRT-A
OPAC116.88 %1103.28B1289.51407.46
GD1DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
OPAC103.53 %4070.2B4213.9161.52
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Base Case
OPAC104.94 %3220.44A3379.54118.48

Details for 6FENT1-8FENTRES 230.0/500.0 kV Ckt 1 transformer l/o DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 3_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FENT1-8FENTRES 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 3_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.51 %
Rating:1130.82 MVA
Rating Type:B
MVA to Mitigate:1272.23
MW Contribution:410.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944581AF1-123 C
50/50
126.6126.6
944582AF1-123 E
50/50
289.9289.9
944591AF1-124 C
50/50
127.05127.05
944592AF1-124 E
50/50
290.95290.95
944601AF1-125 C
50/50
124.65124.65
944602AF1-125 E
50/50
285.35285.35

Details for 6FENT1-8FENTRES 230.0/500.0 kV Ckt 2 transformer l/o DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FENT1-8FENTRES 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 1_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.51 %
Rating:1130.82 MVA
Rating Type:B
MVA to Mitigate:1272.23
MW Contribution:410.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944581AF1-123 C
50/50
126.6126.6
944582AF1-123 E
50/50
289.9289.9
944591AF1-124 C
50/50
127.05127.05
944592AF1-124 E
50/50
290.95290.95
944601AF1-125 C
50/50
124.65124.65
944602AF1-125 E
50/50
285.35285.35

Details for 6FENT1-8FENTRES 230.0/500.0 kV Ckt 3 transformer l/o DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FENT1-8FENTRES 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 1_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.51 %
Rating:1130.82 MVA
Rating Type:B
MVA to Mitigate:1272.23
MW Contribution:410.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944581AF1-123 C
50/50
126.6126.6
944582AF1-123 E
50/50
289.9289.9
944591AF1-124 C
50/50
127.05127.05
944592AF1-124 E
50/50
290.95290.95
944601AF1-125 C
50/50
124.65124.65
944602AF1-125 E
50/50
285.35285.35

Details for 6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:128.71 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1445.82
MW Contribution:67.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3142296MT RD221
50/50
0.1030.103
3142366NRTHEST
50/50
0.1340.134
3143316POE
Adder
0.69882352941176470.594
3145256KINGFORK
Adder
0.480.408
3145506HICKORY
Adder
0.99647058823529410.847
3150601CHESTF5
Adder
39.4152941176470633.503
3150651CHESTF6
Adder
11.3682352941176489.663
3150671DARBY 1
50/50
1.8071.807
3150681DARBY 2
50/50
1.8091.809
3150691DARBY 3
50/50
1.8151.815
3150701DARBY 4
50/50
1.8171.817
3150731STONECA
Adder
4.0823529411764713.47
3150831SPRUNCA
Adder
5.5988235294117654.759
3150841SPRUNCB
Adder
5.5988235294117654.759
3150921YORKTN3
Adder
60.82117647058823551.698
925865AC1-065 E
Adder
8.6211764705882357.328
926412AC1-112 E
50/50
0.8440.844
926662AC1-147 E
Adder
0.61411764705882350.522
926755AC1-161 E
Adder
5.8788235294117654.997
927226AC1-216 E
Adder
4.25647058823529443.618
934392AD1-063 E
Adder
0.55529411764705880.472
934782AD1-105 E
Adder
2.55647058823529432.173
935112AD1-144 E
Adder
0.44470588235294120.378
942341AE2-247 C
Adder
0.71647058823529410.609
942342AE2-247 E
Adder
0.98941176470588230.841
943461AF1-017 C
Adder
0.64823529411764710.551
943462AF1-017 E
Adder
1.05764705882352940.899
943612AF1-032 E
Adder
0.42352941176470590.36
966871AG1-558 C
50/50
1.881.88
966872AG1-558 E
50/50
0.9470.947
316076AC2-137 E
Adder
0.86352941176470590.734
316157AD2-030 E
Adder
0.59529411764705890.506
913392Y1-086 E
Adder
0.99529411764705880.846
916192Z1-068 E
Adder
0.86588235294117640.736
923832AB2-022 E
Adder
0.56235294117647060.478
923842AB2-024 E
Adder
0.94941176470588240.807
930122AB1-027 E
50/50
1.0381.038
938552AE1-074 E
Adder
0.66235294117647060.563
939312AE1-162 E
Adder
0.7117647058823530.605
946262AF1-291 E
Adder
0.86352941176470590.734
957492AF2-043 E
Adder
0.6517647058823530.554
957601AF2-054 C
Adder
1.060.901
957602AF2-054 E
Adder
0.70705882352941170.601
962962AG1-145 E
Adder
0.78352941176470590.666
901082W1-029 E
Adder
14.38705882352941112.229
917122Z2-027 E
Adder
0.60705882352941180.516
925332AB2-190 E
Adder
4.577647058823533.891
925522AC1-027 E
Adder
0.56117647058823530.477
942001AE2-212 C
Adder
1.22235294117647041.039
942002AE2-212 E
Adder
0.81529411764705880.693
957832AF2-077 E
Adder
0.72117647058823530.613
957871AF2-081 C
Adder
4.5541176470588243.871
957872AF2-081 E
Adder
1.9517647058823531.659
958161AF2-110 C
Adder
0.63294117647058830.538
958162AF2-110 E
Adder
1.00588235294117640.855
3138116ELKO L286
Adder
0.90117647058823540.766
933291AC2-141 C
Adder
13.77294117647058911.707
933292AC2-141 E
Adder
5.8788235294117654.997
934012AD1-025 E
Adder
5.5105882352941184.684
927041AC1-191 C
50/50
7.557.55
927042AC1-191 E
50/50
3.7613.761
3130536PAPERMILL
Adder
3.4952941176470592.971
3146326AYDLETT TAP
Adder
0.61764705882352940.525
316004AC1-112 C
50/50
0.2460.246
316160AE1-175 E
Adder
0.64588235294117660.549
316169AC1-164 GEN
Adder
24.58000000000000220.893
316233AE1-074 C
Adder
1.31411764705882361.117
316240AF1-291 C
Adder
1.29411764705882361.1
316312AB1-027 C
50/50
0.3940.394
926785AC1-164_E
Adder
11.0435294117647079.387
934065AD1-033 E
Adder
2.29764705882352961.953
937226AE2-253 E
Adder
2.66588235294117662.266
939612AE1-191 E
Adder
2.9070588235294122.471
315051AA1-145 CT1
50/50
8.6838.683
315052AA1-145 CT2
50/50
8.6788.678
919153AA1-139 E2
Adder
1.86235294117647051.583
919152AA1-139 E1
Adder
1.86235294117647051.583
924814AB2-134 E
Adder
6.9717647058823535.926
316084AB2-161 E
Adder
2.8023529411764712.382
932046AC2-012 E
Adder
6.0788235294117655.167
316311AC2-079 C
Adder
2.74117647058823532.33
932596AC2-079 E
Adder
4.4717647058823533.801
934146AD1-041 E
Adder
1.81647058823529431.544
934576AD1-082 E
Adder
2.2329411764705881.898
316349AD2-085 C
Adder
1.65294117647058841.405
936666AD2-085 E
Adder
2.6964705882352942.292
961611AG1-000B C
Adder
8.3835294117647077.126
941591AE2-156 C
Adder
8.3011764705882357.056
944581AF1-123 C
Adder
20.69529411764706217.591
944582AF1-123 E
Adder
47.3905882352941240.282
944591AF1-124 C
Adder
20.76941176470588217.654
944592AF1-124 E
Adder
47.5623529411764740.428
944601AF1-125 C
Adder
20.37647058823529617.32
944602AF1-125 E
Adder
46.6470588235294139.65
944631AF1-128 C
Adder
24.66235294117647220.963
935161AD1-151 C
Adder
9.0317647058823527.677
935162AD1-151 E
Adder
6.0211764705882365.118
938531AE1-072 C
Adder
8.06.8
938532AE1-072 E
Adder
4.1705882352941183.545
939191AE1-149 C
Adder
5.63882352941176554.793
939192AE1-149 E
Adder
3.75882352941176473.195
939602AE1-190 E
Adder
0.72705882352941180.618
940431AE2-027 C
Adder
7.5435294117647066.412
940432AE2-027 E
Adder
5.0282352941176474.274
940551AE2-041 C
Adder
3.70470588235294153.149
941101AE2-104 C
Adder
1.55058823529411781.318
941102AE2-104 E
Adder
2.46470588235294132.095
943471AF1-018 C
Adder
3.70470588235294153.149
944641AF1-129 C
Adder
62.4352941176470653.07
3150431FOUR RIVERA
50/50
5.4515.451
3150441FOUR RIVERB
50/50
5.4515.451
3150451FOUR RIVERC
50/50
6.666.66
3150461FOUR RIVERD
50/50
5.3725.372
3150471FOUR RIVERE
50/50
5.3725.372
3150481FOUR RIVERF
50/50
6.566.56
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9991.999
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.18619.186
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.3311.33
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.12437.124
G-007PJM->LTFIMP_G-007
CMTX_NF
2.5152.515
NYPJM->LTFIMP_NY
CLTF
1.1351.135
LGEELTFEXP_LGEE->PJM
CLTF
0.7730.773
WECLTFEXP_WEC->PJM
CLTF
0.3950.395
CPLELTFEXP_CPLE->PJM
CLTF
4.1874.187
TVALTFEXP_TVA->PJM
CLTF
2.9092.909
MECLTFEXP_MEC->PJM
CLTF
2.2052.205
LAGNLTFEXP_LAGN->PJM
CLTF
3.6223.622
SIGELTFEXP_SIGE->PJM
CLTF
0.1430.143
O66PJM->LTFIMP_O-066
CMTX_NF
15.98515.985

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.78 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1182.78
MW Contribution:63.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
0.97294117647058820.827
961792AG1-021 E
Adder
0.82823529411764710.704
963041AG1-153 C
Adder
2.2623529411764711.923
963042AG1-153 E
Adder
3.39411764705882352.885
966621AG1-532 C
Adder
0.63882352941176480.543
966622AG1-532 E
Adder
0.42588235294117650.362
3138533PONTONDP
Adder
0.360.306
3145413WATKINS
Adder
0.30941176470588240.263
3145723EMPORIA
Adder
0.196470588235294150.167
3147133PAMPLIN
Adder
0.54941176470588240.467
918492AA1-063AE OP
Adder
1.8117647058823531.54
919692AA2-053 E OP
Adder
1.86823529411764721.588
920042AA2-088 E OP
Adder
4.724.012
944011AF1-069 C
Adder
5.2235294117647074.44
944012AF1-069 E
Adder
2.02941176470588271.725
959311AF2-222 C
Adder
8.5341176470588237.254
959312AF2-222 E
Adder
5.71764705882352954.86
960081AF2-299 C
Adder
0.8517647058823530.724
960082AF2-299 E
Adder
0.56823529411764710.483
900672V4-068 E
Adder
0.157647058823529420.134
923263AB1-132 E OP
Adder
2.70941176470588242.303
923573AB1-173 E OP
Adder
1.47764705882352951.256
924162AB2-060 E OP
Adder
2.0117647058823531.71
924302AB2-077 E O1
Adder
0.62117647058823530.528
924312AB2-078 E O1
Adder
0.62117647058823530.528
924322AB2-079 E O1
Adder
0.62117647058823530.528
925612AC1-036 E
Adder
0.435294117647058830.37
940492AE2-034 E
Adder
1.33882352941176451.138
941011AE2-092 C
Adder
6.9470588235294125.905
941012AE2-092 E
Adder
4.6305882352941183.936
941031AE2-094 C
Adder
15.98588235294117513.588
941032AE2-094 E
Adder
7.166.086
946281AF1-292 C
Adder
0.70588235294117650.6
946282AF1-292 E
Adder
0.47058823529411770.4
946301AF1-294 C
Adder
1.99882352941176491.699
946302AF1-294 E
Adder
1.69294117647058841.439
957481AF2-042 C
Adder
23.21647058823529619.734
957482AF2-042 E
Adder
15.4776470588235313.156
958211AF2-115 C
Adder
1.21529411764705891.033
958212AF2-115 E
Adder
1.0352941176470590.88
3145393UNCAMP
Adder
2.72117647058823582.313
916042Z1-036 E
Adder
12.43647058823529310.571
938771AE1-103 C
Adder
1.3117647058823531.115
938772AE1-103 E
Adder
1.8117647058823531.54
924032AB2-045 E
Adder
0.94941176470588240.807
933502AC2-165 E
50/50
10.19910.199
3143096IRON208
50/50
0.330.33
3143316POE
Adder
0.75647058823529410.643
3145256KINGFORK
Adder
0.455294117647058850.387
3145506HICKORY
Adder
0.94470588235294130.803
3150601CHESTF5
Adder
39.4470588235294233.53
3150651CHESTF6
Adder
11.96588235294117610.171
3150731STONECA
Adder
4.1494117647058823.527
3150831SPRUNCA
50/50
9.4469.446
3150841SPRUNCB
50/50
9.4469.446
3150921YORKTN3
Adder
52.8152941176470644.893
925865AC1-065 E
Adder
7.73058823529411756.571
926412AC1-112 E
Adder
0.56470588235294120.48
926662AC1-147 E
Adder
0.58117647058823530.494
926755AC1-161 E
Adder
0.59529411764705890.506
927226AC1-216 E
Adder
4.20352941176470553.573
934392AD1-063 E
Adder
0.487058823529411770.414
935112AD1-144 E
Adder
0.42235294117647060.359
942341AE2-247 C
Adder
0.71294117647058820.606
942342AE2-247 E
Adder
0.98470588235294120.837
943461AF1-017 C
Adder
0.64470588235294120.548
943462AF1-017 E
Adder
1.0517647058823530.894
943612AF1-032 E
Adder
0.405882352941176470.345
958502AF2-144 E
50/50
1.7771.777
966871AG1-558 C
Adder
1.27764705882352961.086
966872AG1-558 E
Adder
0.64352941176470590.547
316076AC2-137 E
Adder
0.73529411764705890.625
316157AD2-030 E
Adder
0.53411764705882360.454
913392Y1-086 E
Adder
0.9552941176470590.812
916192Z1-068 E
Adder
0.820.697
923832AB2-022 E
Adder
0.53882352941176470.458
923842AB2-024 E
Adder
0.82235294117647050.699
923852AB2-025 E
Adder
0.54941176470588240.467
923862AB2-026 E
50/50
1.8081.808
930122AB1-027 E
Adder
0.69529411764705880.591
938552AE1-074 E
50/50
1.8811.881
938562AE1-075 E
50/50
1.5421.542
939312AE1-162 E
Adder
0.67999999999999990.578
946262AF1-291 E
Adder
0.91058823529411770.774
957492AF2-043 E
Adder
0.62470588235294120.531
957601AF2-054 C
Adder
0.95294117647058830.81
957602AF2-054 E
Adder
0.63529411764705890.54
962962AG1-145 E
Adder
0.65529411764705890.557
901082W1-029 E
Adder
13.8976470588235311.813
917122Z2-027 E
Adder
0.58470588235294120.497
925332AB2-190 E
Adder
4.5752941176470593.889
925522AC1-027 E
Adder
0.53176470588235290.452
942001AE2-212 C
Adder
1.3035294117647061.108
942002AE2-212 E
Adder
0.86941176470588230.739
957832AF2-077 E
Adder
0.63529411764705890.54
957871AF2-081 C
Adder
4.3329411764705883.683
957872AF2-081 E
Adder
1.85647058823529431.578
958161AF2-110 C
Adder
0.61529411764705890.523
958162AF2-110 E
Adder
0.97882352941176460.832
3138116ELKO L286
Adder
0.76588235294117660.651
3147223TWITTYS
Adder
0.48235294117647060.41
926071AC1-086 C
Adder
9.3082352941176477.912
926072AC1-086 E
Adder
4.2364705882352943.601
936261AD2-033 C
Adder
6.5000000000000015.525
936262AD2-033 E
Adder
4.3329411764705883.683
933291AC2-141 C
Adder
12.51176470588235310.635
934621AD1-088 C
Adder
4.3294117647058833.68
934622AD1-088 E
Adder
2.08470588235294141.772
939411AE1-173 C
Adder
37.3388235294117631.738
939412AE1-173 E
Adder
24.89294117647058621.159
934012AD1-025 E
Adder
5.44117647058823554.625
927041AC1-191 C
Adder
5.1282352941176474.359
927042AC1-191 E
Adder
2.55411764705882362.171
962572AG1-106 E
Adder
0.52705882352941180.448
962571AG1-106 C
Adder
1.20352941176470571.023
3130536PAPERMILL
Adder
3.0341176470588242.579
3146326AYDLETT TAP
Adder
0.58823529411764710.5
316160AE1-175 E
Adder
0.54117647058823540.46
316169AC1-164 GEN
Adder
19.79647058823529816.827
316233AE1-074 C
50/50
3.7333.733
316240AF1-291 C
Adder
1.36588235294117651.161
316258AE1-075 C
50/50
0.5110.511
316313AB2-026 C
50/50
0.5570.557
316336AC2-165 C
50/50
13.55213.552
316405AF2-144 C
50/50
0.4340.434
924516AB2-100 E1
Adder
1.32117647058823541.123
924517AB2-100 E2
Adder
1.32117647058823541.123
926785AC1-164_E
Adder
8.8941176470588247.56
934065AD1-033 E
Adder
2.1752941176470591.849
937226AE2-253 E
Adder
2.53176470588235342.152
939612AE1-191 E
Adder
2.6082352941176472.217
919153AA1-139 E2
Adder
1.7717647058823531.506
919152AA1-139 E1
Adder
1.7717647058823531.506
920692AA2-178 E
Adder
1.78588235294117651.518
923994AB2-040_E
Adder
2.76941176470588252.354
924022AB2-043 E O1
Adder
2.4235294117647062.06
924814AB2-134 E
Adder
6.8847058823529425.852
316084AB2-161 E
Adder
2.8764705882352942.445
316088AB2-174 E
Adder
2.94705882352941152.505
932046AC2-012 E
Adder
5.7529411764705884.89
316311AC2-079 C
Adder
2.71999999999999982.312
932596AC2-079 E
Adder
4.4376470588235293.772
934146AD1-041 E
Adder
1.63058823529411771.386
934576AD1-082 E
Adder
2.2917647058823531.948
316349AD2-085 C
Adder
1.6447058823529411.398
936666AD2-085 E
Adder
2.6835294117647062.281
961611AG1-000B C
Adder
8.1152941176470596.898
941591AE2-156 C
Adder
7.8529411764705886.675
944581AF1-123 C
Adder
19.50352941176470616.578
944582AF1-123 E
Adder
44.6637.961
944591AF1-124 C
Adder
19.5717647058823516.636
944592AF1-124 E
Adder
44.82117647058823538.098
944601AF1-125 C
Adder
19.2023529411764716.322
944602AF1-125 E
Adder
43.9588235294117737.365
944631AF1-128 C
Adder
24.6823529411764720.98
964241AG1-285 C
Adder
6.0305882352941185.126
964242AG1-285 E
Adder
4.0211764705882363.418
3137643SOCKMAN
Adder
0.317647058823529450.27
934612AD1-087 E
Adder
1.55882352941176471.325
935161AD1-151 C
Adder
8.9764705882352947.63
935162AD1-151 E
Adder
5.9847058823529415.087
937482AD2-202 E
Adder
0.456470588235294130.388
938531AE1-072 C
Adder
7.6223529411764716.479
938532AE1-072 E
Adder
3.9729411764705883.377
938821AE1-108 C
Adder
8.4270588235294127.163
938822AE1-108 E
Adder
4.0211764705882363.418
939191AE1-149 C
Adder
5.8976470588235295.013
939192AE1-149 E
Adder
3.93176470588235333.342
939602AE1-190 E
Adder
0.6517647058823530.554
940431AE2-027 C
Adder
7.9682352941176476.773
940432AE2-027 E
Adder
5.3129411764705894.516
940481AE2-033 C
Adder
7.6223529411764716.479
940482AE2-033 E
Adder
5.13882352941176554.368
940541AE2-040 C
Adder
1.35764705882352941.154
940551AE2-041 C
Adder
3.25058823529411762.763
940641AE2-051 C
Adder
7.0152941176470595.963
940642AE2-051 E
Adder
4.67764705882352953.976
941101AE2-104 C
Adder
1.50823529411764711.282
941102AE2-104 E
Adder
2.39764705882352922.038
942461AE2-259 C
Adder
5.83647058823529454.961
942462AE2-259 E
Adder
3.8917647058823533.308
943471AF1-018 C
Adder
3.25058823529411762.763
944641AF1-129 C
Adder
65.7211764705882355.863
3150851SPRUNCC
50/50
0.1690.169
3150861SPRUNCD
50/50
0.1690.169
316303AF2-085
50/50
7.0277.027
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.2422.242
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.08118.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.29711.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
40.62940.629
G-007PJM->LTFIMP_G-007
CMTX_NF
2.112.11
NYPJM->LTFIMP_NY
CLTF
0.9630.963
LGEELTFEXP_LGEE->PJM
CLTF
0.7270.727
WECLTFEXP_WEC->PJM
CLTF
0.3730.373
CPLELTFEXP_CPLE->PJM
CLTF
4.6984.698
TVALTFEXP_TVA->PJM
CLTF
2.952.95
MECLTFEXP_MEC->PJM
CLTF
2.1322.132
LAGNLTFEXP_LAGN->PJM
CLTF
3.6953.695
SIGELTFEXP_SIGE->PJM
CLTF
0.1370.137
O66PJM->LTFIMP_O-066
CMTX_NF
13.41813.418

Details for 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 588_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:160.69 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1090.58
MW Contribution:236.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934521AD1-076 C
Adder
4.6141176470588243.922
934522AD1-076 E
Adder
2.3517647058823531.999
940492AE2-034 E
Adder
1.45294117647058841.235
916042Z1-036 E
50/50
17.00117.001
313526AB2-022 C
50/50
0.3990.399
3145506HICKORY
50/50
3.3893.389
3156056W1-029WIND
50/50
0.4810.481
3156116Z1-036WIND
50/50
0.390.39
913392Y1-086 E
50/50
2.3352.335
923832AB2-022 E
50/50
1.3181.318
901082W1-029 E
50/50
19.78819.788
917122Z2-027 E
50/50
1.2581.258
957871AF2-081 C
50/50
13.97813.978
957872AF2-081 E
50/50
5.9915.991
933981AD1-022 C
Adder
2.84588235294117682.419
933982AD1-022 E
Adder
1.54941176470588231.317
3145946PLYMOUTH TP
Adder
0.127058823529411780.108
3146326AYDLETT TAP
50/50
1.7791.779
316185AD1-033 C
50/50
2.5062.506
316320Y1-086 C
50/50
0.2330.233
316321Z2-027 C
50/50
0.340.34
934065AD1-033 E
50/50
10.2610.26
937226AE2-253 E
50/50
8.5248.524
316017AA1-139 ULT1
50/50
1.5081.508
316018AA1-139 ULT2
50/50
1.5081.508
919153AA1-139 E2
50/50
5.7165.716
919152AA1-139 E1
50/50
5.7165.716
920692AA2-178 E
Adder
1.93647058823529421.646
316388AE2-253 GEN
50/50
2.8572.857
944581AF1-123 C
50/50
72.94872.948
944582AF1-123 E
50/50
167.042167.042
944591AF1-124 C
50/50
73.20773.207
944592AF1-124 E
50/50
167.647167.647
944601AF1-125 C
50/50
71.82471.824
944602AF1-125 E
50/50
164.42164.42
934501AD1-074 C
Adder
12.70470588235294210.799
934502AD1-074 E
Adder
6.46823529411764755.498
934511AD1-075 C
Adder
3.17647058823529442.7
934512AD1-075 E
Adder
1.61647058823529431.374
938531AE1-072 C
50/50
23.46523.465
938532AE1-072 E
50/50
12.23212.232
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.2290.229
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.0861.086
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.7620.762
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.53.5
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0960.096
NYPJM->LTFIMP_NY
CLTF
0.0440.044
LGEELTFEXP_LGEE->PJM
CLTF
0.0420.042
WECLTFEXP_WEC->PJM
CLTF
0.0220.022
CPLELTFEXP_CPLE->PJM
CLTF
0.480.48
TVALTFEXP_TVA->PJM
CLTF
0.2050.205
MECLTFEXP_MEC->PJM
CLTF
0.1350.135
LAGNLTFEXP_LAGN->PJM
CLTF
0.2620.262
SIGELTFEXP_SIGE->PJM
CLTF
0.0080.008
O66PJM->LTFIMP_O-066
CMTX_NF
0.6090.609

Details for 6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:121.31 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1362.65
MW Contribution:67.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3142296MT RD221
50/50
0.1030.103
3142366NRTHEST
50/50
0.1340.134
3143316POE
Adder
0.69882352941176470.594
3145256KINGFORK
Adder
0.480.408
3145506HICKORY
Adder
0.99647058823529410.847
3150601CHESTF5
Adder
39.4152941176470633.503
3150651CHESTF6
Adder
11.3682352941176489.663
3150671DARBY 1
50/50
1.8071.807
3150681DARBY 2
50/50
1.8091.809
3150691DARBY 3
50/50
1.8151.815
3150701DARBY 4
50/50
1.8171.817
3150731STONECA
Adder
4.0823529411764713.47
3150831SPRUNCA
Adder
5.5988235294117654.759
3150841SPRUNCB
Adder
5.5988235294117654.759
3150921YORKTN3
Adder
60.82117647058823551.698
925865AC1-065 E
Adder
8.6211764705882357.328
926412AC1-112 E
50/50
0.8440.844
926662AC1-147 E
Adder
0.61411764705882350.522
926755AC1-161 E
Adder
5.8788235294117654.997
927226AC1-216 E
Adder
4.25647058823529443.618
934392AD1-063 E
Adder
0.55529411764705880.472
934782AD1-105 E
Adder
2.55647058823529432.173
935112AD1-144 E
Adder
0.44470588235294120.378
942341AE2-247 C
Adder
0.71647058823529410.609
942342AE2-247 E
Adder
0.98941176470588230.841
943461AF1-017 C
Adder
0.64823529411764710.551
943462AF1-017 E
Adder
1.05764705882352940.899
943612AF1-032 E
Adder
0.42352941176470590.36
966871AG1-558 C
50/50
1.881.88
966872AG1-558 E
50/50
0.9470.947
966881AG1-559 C
50/50
7.7447.744
966882AG1-559 E
50/50
3.9013.901
316076AC2-137 E
Adder
0.86352941176470590.734
316157AD2-030 E
Adder
0.59529411764705890.506
916192Z1-068 E
Adder
0.86588235294117640.736
923842AB2-024 E
Adder
0.94941176470588240.807
930122AB1-027 E
50/50
1.0381.038
938552AE1-074 E
Adder
0.66235294117647060.563
939312AE1-162 E
Adder
0.7117647058823530.605
946262AF1-291 E
Adder
0.86352941176470590.734
957492AF2-043 E
Adder
0.6517647058823530.554
957601AF2-054 C
Adder
1.060.901
957602AF2-054 E
Adder
0.70705882352941170.601
962962AG1-145 E
Adder
0.78352941176470590.666
925332AB2-190 E
Adder
4.577647058823533.891
925522AC1-027 E
Adder
0.56117647058823530.477
942001AE2-212 C
Adder
1.22235294117647041.039
942002AE2-212 E
Adder
0.81529411764705880.693
957832AF2-077 E
Adder
0.72117647058823530.613
957871AF2-081 C
Adder
4.5541176470588243.871
957872AF2-081 E
Adder
1.9517647058823531.659
958161AF2-110 C
Adder
0.63294117647058830.538
958162AF2-110 E
Adder
1.00588235294117640.855
3138116ELKO L286
Adder
0.90117647058823540.766
933291AC2-141 C
Adder
13.77294117647058911.707
933292AC2-141 E
Adder
5.8788235294117654.997
934012AD1-025 E
Adder
5.5105882352941184.684
927041AC1-191 C
50/50
7.557.55
927042AC1-191 E
50/50
3.7613.761
3130536PAPERMILL
Adder
3.4952941176470592.971
3146326AYDLETT TAP
Adder
0.61764705882352940.525
316004AC1-112 C
50/50
0.2460.246
316160AE1-175 E
Adder
0.64588235294117660.549
316169AC1-164 GEN
Adder
24.58000000000000220.893
316233AE1-074 C
Adder
1.31411764705882361.117
316240AF1-291 C
Adder
1.29411764705882361.1
316312AB1-027 C
50/50
0.3940.394
926785AC1-164_E
Adder
11.0435294117647079.387
934065AD1-033 E
Adder
2.29764705882352961.953
937226AE2-253 E
Adder
2.66588235294117662.266
939612AE1-191 E
Adder
2.9070588235294122.471
315051AA1-145 CT1
50/50
8.6838.683
315052AA1-145 CT2
50/50
8.6788.678
919153AA1-139 E2
Adder
1.86235294117647051.583
919152AA1-139 E1
Adder
1.86235294117647051.583
924814AB2-134 E
Adder
6.9717647058823535.926
316084AB2-161 E
Adder
2.8023529411764712.382
932046AC2-012 E
Adder
6.0788235294117655.167
316311AC2-079 C
Adder
2.74117647058823532.33
932596AC2-079 E
Adder
4.4717647058823533.801
934146AD1-041 E
Adder
1.81647058823529431.544
934576AD1-082 E
Adder
2.2329411764705881.898
316349AD2-085 C
Adder
1.65294117647058841.405
936666AD2-085 E
Adder
2.6964705882352942.292
961611AG1-000B C
Adder
8.3835294117647077.126
941591AE2-156 C
Adder
8.3011764705882357.056
944581AF1-123 C
Adder
20.69529411764706217.591
944582AF1-123 E
Adder
47.3905882352941240.282
944591AF1-124 C
Adder
20.76941176470588217.654
944592AF1-124 E
Adder
47.5623529411764740.428
944601AF1-125 C
Adder
20.37647058823529617.32
944602AF1-125 E
Adder
46.6470588235294139.65
944631AF1-128 C
Adder
24.66235294117647220.963
935161AD1-151 C
Adder
9.0317647058823527.677
935162AD1-151 E
Adder
6.0211764705882365.118
938531AE1-072 C
Adder
8.06.8
938532AE1-072 E
Adder
4.1705882352941183.545
939191AE1-149 C
Adder
5.63882352941176554.793
939192AE1-149 E
Adder
3.75882352941176473.195
939602AE1-190 E
Adder
0.72705882352941180.618
940431AE2-027 C
Adder
7.5435294117647066.412
940432AE2-027 E
Adder
5.0282352941176474.274
940551AE2-041 C
Adder
3.70470588235294153.149
941101AE2-104 C
Adder
1.55058823529411781.318
941102AE2-104 E
Adder
2.46470588235294132.095
943471AF1-018 C
Adder
3.70470588235294153.149
944641AF1-129 C
Adder
62.4352941176470653.07
3150431FOUR RIVERA
50/50
5.4515.451
3150441FOUR RIVERB
50/50
5.4515.451
3150451FOUR RIVERC
50/50
6.666.66
3150461FOUR RIVERD
50/50
5.3725.372
3150471FOUR RIVERE
50/50
5.3725.372
3150481FOUR RIVERF
50/50
6.566.56
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9991.999
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.18619.186
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.3311.33
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.12437.124
G-007PJM->LTFIMP_G-007
CMTX_NF
2.5152.515
NYPJM->LTFIMP_NY
CLTF
1.1351.135
LGEELTFEXP_LGEE->PJM
CLTF
0.7730.773
WECLTFEXP_WEC->PJM
CLTF
0.3950.395
CPLELTFEXP_CPLE->PJM
CLTF
4.1874.187
TVALTFEXP_TVA->PJM
CLTF
2.9092.909
MECLTFEXP_MEC->PJM
CLTF
2.2052.205
LAGNLTFEXP_LAGN->PJM
CLTF
3.6223.622
SIGELTFEXP_SIGE->PJM
CLTF
0.1430.143
O66PJM->LTFIMP_O-066
CMTX_NF
15.98515.985

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.49 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4212.31
MW Contribution:158.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
963041AG1-153 C
Adder
5.3364705882352944.536
963042AG1-153 E
Adder
8.0047058823529426.804
3145413WATKINS
Adder
0.71529411764705890.608
920042AA2-088 E OP
Adder
10.782352941176479.165
944011AF1-069 C
Adder
12.49058823529411910.617
944012AF1-069 E
Adder
4.8517647058823534.124
940492AE2-034 E
Adder
3.1905882352941182.712
941031AE2-094 C
Adder
38.2270588235294232.493
941032AE2-094 E
Adder
17.12117647058823514.553
3145393UNCAMP
Adder
6.3329411764705885.383
916042Z1-036 E
Adder
29.97176470588235425.476
938771AE1-103 C
Adder
3.06470588235294142.605
938772AE1-103 E
Adder
4.2317647058823533.597
3142296MT RD221
50/50
0.1350.135
3142366NRTHEST
50/50
0.2060.206
3143316POE
Adder
1.4635294117647061.244
3145256KINGFORK
Adder
1.09411764705882360.93
3145506HICKORY
Adder
2.34000000000000031.989
3150391LDYSMT3
50/50
5.3915.391
3150401LDYSMT4
50/50
5.4015.401
3150411LDYSMT5
50/50
5.4185.418
3150601CHESTF5
Adder
70.2058823529411759.675
3150651CHESTF6
Adder
20.5870588235294117.499
3150701DARBY 4
50/50
2.8532.853
3150731STONECA
Adder
7.6200000000000016.477
3150831SPRUNCA
Adder
10.0964705882352958.582
3150841SPRUNCB
Adder
10.0964705882352958.582
3150921YORKTN3
Adder
130.66235294117647111.063
925865AC1-065 E
Adder
17.8870588235294115.204
926412AC1-112 E
50/50
1.2521.252
926662AC1-147 E
Adder
1.42941176470588241.215
926755AC1-161 E
Adder
14.03647058823529311.931
927226AC1-216 E
Adder
8.4752941176470587.204
934392AD1-063 E
Adder
1.1517647058823530.979
935112AD1-144 E
Adder
1.0152941176470590.863
936591AD2-074 C
Adder
5.9258823529411765.037
936592AD2-074 E
Adder
9.6694117647058818.219
942341AE2-247 C
Adder
1.60235294117647081.362
942342AE2-247 E
Adder
2.2129411764705881.881
943461AF1-017 C
Adder
1.44941176470588241.232
943462AF1-017 E
Adder
2.36588235294117682.011
943612AF1-032 E
Adder
0.99058823529411770.842
943741AF1-042 C
Adder
3.10117647058823562.636
943742AF1-042 E
Adder
5.05882352941176454.3
961951AG1-038 C
Adder
3.42705882352941152.913
961952AG1-038 E
Adder
4.7329411764705884.023
966661AG1-536 C
Adder
5.7152941176470584.858
966662AG1-536 E
Adder
7.686.528
966871AG1-558 C
Adder
2.662.261
966872AG1-558 E
Adder
1.341.139
966881AG1-559 C
50/50
2.7662.766
966882AG1-559 E
50/50
1.3931.393
3152251N ANNA1
50/50
40.24640.246
3152261N ANNA2
50/50
40.26240.262
316076AC2-137 E
Adder
1.47529411764705891.254
316078AC2-138 E
Adder
0.97411764705882350.828
316157AD2-030 E
Adder
1.27411764705882361.083
913392Y1-086 E
Adder
2.34117647058823541.99
916192Z1-068 E
Adder
2.0235294117647061.72
923832AB2-022 E
Adder
1.32117647058823541.123
923842AB2-024 E
Adder
1.92941176470588241.64
923852AB2-025 E
Adder
1.16941176470588240.994
930122AB1-027 E
50/50
1.5391.539
938552AE1-074 E
Adder
1.35529411764705881.152
939312AE1-162 E
Adder
1.5552941176470591.322
946262AF1-291 E
Adder
1.58588235294117651.348
957492AF2-043 E
Adder
1.52352941176470581.295
957601AF2-054 C
Adder
2.2717647058823531.931
957602AF2-054 E
Adder
1.51411764705882361.287
962861AG1-135 C
Adder
6.4529411764705885.485
962862AG1-135 E
Adder
4.3023529411764713.657
962962AG1-145 E
Adder
1.5835294117647061.346
963611AG1-210 C
Adder
0.69529411764705880.591
963612AG1-210 E
Adder
1.04352941176470580.887
964211AG1-282 C
Adder
2.11764705882352941.8
964212AG1-282 E
Adder
1.4117647058823531.2
901082W1-029 E
Adder
33.8176470588235328.745
917122Z2-027 E
Adder
1.4282352941176471.214
925332AB2-190 E
Adder
8.8811764705882377.549
925522AC1-027 E
Adder
1.31058823529411781.114
942001AE2-212 C
Adder
2.35882352941176482.005
942002AE2-212 E
Adder
1.57294117647058831.337
957832AF2-077 E
Adder
1.54588235294117651.314
957871AF2-081 C
Adder
10.6988235294117659.094
957872AF2-081 E
Adder
4.5847058823529413.897
958161AF2-110 C
Adder
1.46235294117647091.243
958162AF2-110 E
Adder
2.3270588235294121.978
3138116ELKO L286
Adder
1.53882352941176471.308
3141813NORNECK
Adder
0.92588235294117650.787
933291AC2-141 C
Adder
32.8811764705882427.949
933292AC2-141 E
Adder
14.03647058823529311.931
939411AE1-173 C
Adder
92.0364705882352978.231
939412AE1-173 E
Adder
61.3576470588235452.154
934012AD1-025 E
Adder
10.9729411764705889.327
927041AC1-191 C
Adder
10.6788235294117659.077
927042AC1-191 E
Adder
5.3188235294117654.521
3130536PAPERMILL
Adder
7.1317647058823546.062
3145946PLYMOUTH TP
Adder
0.33176470588235290.282
3146326AYDLETT TAP
Adder
1.44941176470588241.232
316004AC1-112 C
50/50
0.3640.364
316160AE1-175 E
Adder
1.30705882352941181.111
316169AC1-164 GEN
Adder
44.39529411764705537.736
316233AE1-074 C
Adder
2.69176470588235262.288
316240AF1-291 C
Adder
2.37882352941176432.022
316312AB1-027 C
50/50
0.5850.585
926785AC1-164_E
Adder
19.94588235294117616.954
934065AD1-033 E
Adder
5.3894117647058834.581
937226AE2-253 E
Adder
6.265.321
939612AE1-191 E
Adder
6.1141176470588245.197
926004AC1-076_E
Adder
4.277647058823533.636
3150371LDYSMT1
50/50
5.1855.185
3150381LDYSMT2
50/50
5.2525.252
315051AA1-145 CT1
50/50
5.6195.619
315052AA1-145 CT2
50/50
5.6165.616
939246AE1-155 E
Adder
9.2517647058823537.864
919153AA1-139 E2
Adder
4.3752941176470593.719
919152AA1-139 E1
Adder
4.3752941176470593.719
920692AA2-178 E
Adder
4.2541176470588233.616
924814AB2-134 E
Adder
13.88352941176470711.801
316084AB2-161 E
Adder
5.9764705882352945.08
316044AC1-158 C1
50/50
7.3677.367
316045AC1-158 C2
50/50
7.3677.367
926739AC1-158 E1
50/50
19.2719.27
926740AC1-158 E2
50/50
19.2719.27
932046AC2-012 E
Adder
14.1412.019
316311AC2-079 C
Adder
6.1564705882352945.233
932596AC2-079 E
Adder
10.0458823529411768.539
934146AD1-041 E
Adder
3.8211764705882363.248
934576AD1-082 E
Adder
4.7623529411764714.048
316349AD2-085 C
Adder
3.6976470588235293.143
936666AD2-085 E
Adder
6.03294117647058855.128
961611AG1-000B C
Adder
17.4070588235294114.796
941591AE2-156 C
Adder
19.3216.422
944581AF1-123 C
Adder
48.9258823529411841.587
944582AF1-123 E
Adder
112.0352941176470795.23
944591AF1-124 C
Adder
49.141.735
944592AF1-124 E
Adder
112.4411764705882595.575
944601AF1-125 C
Adder
48.17294117647059440.947
944602AF1-125 E
Adder
110.2776470588235393.736
944631AF1-128 C
Adder
43.9294117647058937.34
958261AF2-120 C
Adder
6.6447058823529415.648
958262AF2-120 E
Adder
4.4294117647058833.765
934501AD1-074 C
Adder
34.51411764705882529.337
934502AD1-074 E
Adder
8.9670588235294127.622
935161AD1-151 C
Adder
17.7317647058823515.072
935162AD1-151 E
Adder
11.82117647058823610.048
938531AE1-072 C
Adder
18.79411764705882215.975
938532AE1-072 E
Adder
9.7976470588235298.328
939191AE1-149 C
Adder
11.6529411764705889.905
939192AE1-149 E
Adder
7.7682352941176476.603
939261AE1-157 C
50/50
16.15516.155
939262AE1-157 E
50/50
8.7638.763
939602AE1-190 E
Adder
1.5282352941176471.299
940431AE2-027 C
Adder
14.21058823529411812.079
940432AE2-027 E
Adder
9.4729411764705888.052
940481AE2-033 C
Adder
16.25647058823529513.818
940482AE2-033 E
Adder
10.969.316
940541AE2-040 C
Adder
2.89058823529411772.457
940551AE2-041 C
Adder
7.67764705882352956.526
940641AE2-051 C
Adder
17.23529411764705814.65
940642AE2-051 E
Adder
11.4905882352941179.767
941101AE2-104 C
Adder
3.58470588235294143.047
941102AE2-104 E
Adder
5.6988235294117654.844
943471AF1-018 C
Adder
7.67764705882352956.526
944641AF1-129 C
Adder
113.0705882352941296.11
3150431FOUR RIVERA
50/50
3.5273.527
3150441FOUR RIVERB
50/50
3.5273.527
3150451FOUR RIVERC
50/50
4.314.31
3150461FOUR RIVERD
50/50
3.4763.476
3150471FOUR RIVERE
50/50
3.4763.476
3150481FOUR RIVERF
50/50
4.2454.245
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.0355.035
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.06830.068
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.37922.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
90.48890.488
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7495.749
NYPJM->LTFIMP_NY
CLTF
2.722.72
LGEELTFEXP_LGEE->PJM
CLTF
1.3021.302
WECLTFEXP_WEC->PJM
CLTF
0.640.64
CPLELTFEXP_CPLE->PJM
CLTF
10.55810.558
TVALTFEXP_TVA->PJM
CLTF
6.1246.124
MECLTFEXP_MEC->PJM
CLTF
3.9143.914
LAGNLTFEXP_LAGN->PJM
CLTF
7.6467.646
SIGELTFEXP_SIGE->PJM
CLTF
0.2490.249
O66PJM->LTFIMP_O-066
CMTX_NF
36.64136.641

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.11 %
Rating:2442.12 MVA
Rating Type:A
MVA to Mitigate:2542.46
MW Contribution:212.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.55529411764705880.472
961942AG1-037 E
Adder
0.370588235294117660.315
963041AG1-153 C
Adder
4.884.148
963042AG1-153 E
Adder
7.3188235294117656.221
966621AG1-532 C
Adder
1.27294117647058851.082
966622AG1-532 E
Adder
0.84823529411764710.721
3145413WATKINS
Adder
0.82235294117647050.699
3145723EMPORIA
Adder
0.39411764705882360.335
918492AA1-063AE OP
Adder
4.17764705882352953.551
918532AA1-067 E
Adder
0.72588235294117650.617
919692AA2-053 E OP
Adder
4.1705882352941183.545
920042AA2-088 E OP
Adder
11.93294117647058910.143
927146AC1-208 E
Adder
3.8470588235294123.27
934521AD1-076 C
Adder
14.67647058823529312.475
934522AD1-076 E
Adder
7.48117647058823556.359
943172AE2-346 E
Adder
0.66705882352941170.567
944011AF1-069 C
Adder
11.532941176470599.803
944012AF1-069 E
Adder
4.47999999999999953.808
960081AF2-299 C
Adder
1.69647058823529421.442
960082AF2-299 E
Adder
1.13058823529411770.961
316141AB2-099 E
Adder
0.27764705882352940.236
900672V4-068 E
Adder
0.395294117647058850.336
923263AB1-132 E OP
Adder
5.86235294117647054.983
923573AB1-173 E OP
Adder
3.06235294117647072.603
940492AE2-034 E
Adder
3.8317647058823533.257
941031AE2-094 C
Adder
35.2988235294117730.004
941032AE2-094 E
Adder
15.80941176470588313.438
946281AF1-292 C
Adder
1.40470588235294121.194
946282AF1-292 E
Adder
0.93647058823529420.796
957861AF2-080 C
Adder
7.47999999999999956.358
957862AF2-080 E
Adder
3.3152941176470592.818
3145393UNCAMP
Adder
7.4105882352941186.299
916042Z1-036 E
Adder
37.13529411764706431.565
938771AE1-103 C
Adder
3.62470588235294143.081
938772AE1-103 E
Adder
5.00588235294117644.255
3143316POE
Adder
1.19294117647058821.014
3144216WINCHST
50/50
0.20.2
3145256KINGFORK
50/50
1.4051.405
3145506HICKORY
50/50
3.0893.089
3150601CHESTF5
Adder
66.756.695
3150731STONECA
Adder
6.8694117647058835.839
3150921YORKTN3
50/50
185.501185.501
925865AC1-065 E
Adder
22.29058823529411618.947
926472AC1-118 E
Adder
1.13411764705882350.964
926662AC1-147 E
50/50
1.8821.882
926755AC1-161 E
50/50
20.21420.214
927226AC1-216 E
Adder
8.9599999999999997.616
934392AD1-063 E
50/50
1.4751.475
935112AD1-144 E
50/50
1.3041.304
936582AD2-073 E
Adder
1.23176470588235291.047
936591AD2-074 C
Adder
7.2670588235294116.177
936592AD2-074 E
Adder
11.85764705882353110.079
942341AE2-247 C
Adder
1.84117647058823521.565
942342AE2-247 E
Adder
2.54235294117647072.161
943461AF1-017 C
Adder
1.66588235294117641.416
943462AF1-017 E
Adder
2.71882352941176462.311
943612AF1-032 E
Adder
1.2764705882352941.085
943741AF1-042 C
Adder
3.8023529411764713.232
943742AF1-042 E
Adder
6.20470588235294155.274
961951AG1-038 C
Adder
4.20352941176470553.573
961952AG1-038 E
Adder
5.8035294117647064.933
966661AG1-536 C
Adder
6.91529411764705955.878
966662AG1-536 E
Adder
9.2917647058823527.898
3150981CHESPKA
50/50
0.6170.617
3150991CHESPKB
50/50
1.0231.023
3151081ELIZAR1
50/50
4.5444.544
3151091ELIZAR2
50/50
4.4644.464
3151101ELIZAR3
50/50
4.6014.601
3152331SURRY 2
50/50
43.89143.891
316076AC2-137 E
Adder
1.53647058823529431.306
316078AC2-138 E
Adder
1.1482352941176470.976
316157AD2-030 E
Adder
1.6270588235294121.383
913392Y1-086 E
Adder
3.0235294117647062.57
916192Z1-068 E
50/50
2.672.67
923832AB2-022 E
Adder
1.7070588235294121.451
923842AB2-024 E
50/50
2.4762.476
923852AB2-025 E
Adder
1.040.884
939312AE1-162 E
Adder
1.9235294117647061.635
957492AF2-043 E
Adder
1.9635294117647061.669
957601AF2-054 C
Adder
2.92.465
957602AF2-054 E
Adder
1.93294117647058841.643
962861AG1-135 C
Adder
7.8329411764705896.658
962862AG1-135 E
Adder
5.2211764705882354.438
962962AG1-145 E
50/50
2.2212.221
963611AG1-210 C
Adder
0.820.697
963612AG1-210 E
Adder
1.23058823529411781.046
964211AG1-282 C
Adder
2.5270588235294122.148
964212AG1-282 E
Adder
1.6847058823529411.432
901082W1-029 E
Adder
43.0176470588235336.565
917122Z2-027 E
Adder
1.83411764705882341.559
925332AB2-190 E
Adder
8.8411764705882367.515
925522AC1-027 E
50/50
1.7291.729
957831AF2-077 C
50/50
0.4830.483
957832AF2-077 E
50/50
2.0912.091
957871AF2-081 C
50/50
14.02714.027
957872AF2-081 E
50/50
6.0126.012
958161AF2-110 C
Adder
1.81529411764705871.543
958162AF2-110 E
Adder
2.8870588235294122.454
3138116ELKO L286
Adder
1.60117647058823541.361
3141813NORNECK
Adder
1.09294117647058830.929
926071AC1-086 C
Adder
20.14470588235294517.123
926072AC1-086 E
Adder
9.1682352941176477.793
927021AC1-189 C
Adder
8.235294117647067
927022AC1-189 E
Adder
4.1023529411764713.487
933291AC2-141 C
50/50
47.35447.354
933292AC2-141 E
50/50
20.21420.214
939411AE1-173 C
Adder
101.4858823529411986.263
939412AE1-173 E
Adder
67.656470588235357.508
934012AD1-025 E
Adder
11.69.86
916191Z1-068 C
50/50
0.0620.062
933981AD1-022 C
Adder
10.3435294117647068.792
933982AD1-022 E
Adder
5.6317647058823534.787
962572AG1-106 E
Adder
1.140.969
962571AG1-106 C
Adder
2.60588235294117652.215
3130536PAPERMILL
50/50
9.1469.146
3145946PLYMOUTH TP
Adder
0.38941176470588240.331
3146326AYDLETT TAP
50/50
1.8931.893
316036AC1-147 C
50/50
0.5220.522
316059AD1-063 C
50/50
0.360.36
316072AD1-144 C
50/50
0.3890.389
316159AE1-175 C
50/50
0.6010.601
316160AE1-175 E
50/50
1.8321.832
316169AC1-164 GEN
50/50
57.50657.506
316185AD1-033 C
50/50
1.7411.741
316274AC1-208 C
Adder
8.6647058823529427.365
316294AC1-161 C
50/50
7.7117.711
316314AB2-024 C
50/50
0.4030.403
316316AC1-027 C
50/50
0.4470.447
316382AG1-145 C
50/50
0.5420.542
917332KELFORD E
Adder
1.74000000000000021.479
924516AB2-100 E1
Adder
2.6788235294117652.277
924517AB2-100 E2
Adder
2.6788235294117652.277
926206AC1-098 E
Adder
3.5952941176470593.056
926214AC1-099 E
Adder
1.18705882352941171.009
926785AC1-164_E
50/50
25.83625.836
934065AD1-033 E
50/50
7.137.13
937226AE2-253 E
50/50
8.238.23
939612AE1-191 E
Adder
7.76.545
939246AE1-155 E
Adder
11.1941176470588259.515
918512AA1-065 E OP
Adder
6.2364705882352955.301
316017AA1-139 ULT1
50/50
1.5131.513
316018AA1-139 ULT2
50/50
1.5131.513
919153AA1-139 E2
50/50
5.7365.736
919152AA1-139 E1
50/50
5.7365.736
920692AA2-178 E
Adder
5.1082352941176474.342
923994AB2-040_E
Adder
5.7423529411764714.881
924814AB2-134 E
Adder
14.67647058823529312.475
316084AB2-161 E
Adder
6.0352941176470595.13
925122AB2-169 E
Adder
6.3976470588235295.438
316088AB2-174 E
Adder
6.03294117647058855.128
316375AC2-012 C
50/50
1.9131.913
932046AC2-012 E
50/50
18.61318.613
316311AC2-079 C
Adder
7.1458823529411766.074
932596AC2-079 E
Adder
11.6588235294117669.91
934146AD1-041 E
Adder
4.8129411764705894.091
934576AD1-082 E
Adder
4.80941176470588254.088
316349AD2-085 C
Adder
4.2482352941176483.611
936666AD2-085 E
Adder
6.9317647058823545.892
316388AE2-253 GEN
50/50
2.7582.758
961611AG1-000B C
Adder
20.0529411764705917.045
941591AE2-156 C
50/50
25.46125.461
944581AF1-123 C
50/50
65.6165.61
944582AF1-123 E
50/50
150.24150.24
944591AF1-124 C
50/50
65.84465.844
944592AF1-124 E
50/50
150.785150.785
944601AF1-125 C
50/50
64.664.6
944602AF1-125 E
50/50
147.882147.882
944631AF1-128 C
Adder
41.73529411764706535.475
958261AF2-120 C
Adder
8.0388235294117656.833
958262AF2-120 E
Adder
5.3588235294117644.555
3137643SOCKMAN
Adder
0.6764705882352940.575
932632AC2-084 E
Adder
3.17764705882352952.701
934501AD1-074 C
Adder
40.41176470588235534.35
934502AD1-074 E
Adder
20.57176470588235517.486
934511AD1-075 C
Adder
10.102352941176478.587
934512AD1-075 E
Adder
5.1435294117647064.372
935161AD1-151 C
Adder
18.1615.436
935162AD1-151 E
Adder
12.10588235294117610.29
938531AE1-072 C
50/50
24.57324.573
938532AE1-072 E
50/50
12.8112.81
939191AE1-149 C
Adder
10.6576470588235289.059
939192AE1-149 E
Adder
7.1047058823529416.039
939602AE1-190 E
Adder
1.9247058823529411.636
940431AE2-027 C
Adder
10.9364705882352939.296
940432AE2-027 E
Adder
3.88235294117647063.3
940481AE2-033 C
Adder
14.5623529411764712.378
940482AE2-033 E
Adder
9.817647058823538.345
940541AE2-040 C
Adder
2.5717647058823532.186
940551AE2-041 C
Adder
9.8305882352941178.356
940641AE2-051 C
Adder
17.715.045
940642AE2-051 E
Adder
11.79999999999999910.03
941101AE2-104 C
Adder
4.4482352941176473.781
941102AE2-104 E
Adder
7.0717647058823536.011
943471AF1-018 C
Adder
9.8305882352941178.356
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.274.27
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.05913.059
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.06213.062
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
70.8670.86
G-007PJM->LTFIMP_G-007
CMTX_NF
2.7242.724
NYPJM->LTFIMP_NY
CLTF
1.3121.312
LGEELTFEXP_LGEE->PJM
CLTF
0.5530.553
WECLTFEXP_WEC->PJM
CLTF
0.2830.283
CPLELTFEXP_CPLE->PJM
CLTF
8.9638.963
TVALTFEXP_TVA->PJM
CLTF
3.7783.778
MECLTFEXP_MEC->PJM
CLTF
1.9921.992
LAGNLTFEXP_LAGN->PJM
CLTF
4.854.85
SIGELTFEXP_SIGE->PJM
CLTF
0.1170.117
O66PJM->LTFIMP_O-066
CMTX_NF
17.37617.376

Details for 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 588_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8FENTRES-6FENTRES 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 588_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.03 %
Rating:1115.59 MVA
Rating Type:B
MVA to Mitigate:1305.6
MW Contribution:412.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944581AF1-123 C
50/50
127.385127.385
944582AF1-123 E
50/50
291.697291.697
944591AF1-124 C
50/50
127.837127.837
944592AF1-124 E
50/50
292.753292.753
944601AF1-125 C
50/50
125.423125.423
944602AF1-125 E
50/50
287.119287.119

Details for 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 588_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8FENTRES-6FENTRES 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 588_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:116.88 %
Rating:1103.28 MVA
Rating Type:B
MVA to Mitigate:1289.51
MW Contribution:407.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944581AF1-123 C
50/50
125.815125.815
944582AF1-123 E
50/50
288.103288.103
944591AF1-124 C
50/50
126.263126.263
944592AF1-124 E
50/50
289.147289.147
944601AF1-125 C
50/50
123.877123.877
944602AF1-125 E
50/50
283.581283.581

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.53 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4213.9
MW Contribution:161.52
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
963041AG1-153 C
Adder
5.4305882352941184.616
963042AG1-153 E
Adder
8.1447058823529416.923
3145413WATKINS
Adder
0.72823529411764710.619
920042AA2-088 E OP
Adder
10.9811764705882359.334
934521AD1-076 C
Adder
12.77058823529411810.855
934522AD1-076 E
Adder
6.5094117647058835.533
944011AF1-069 C
Adder
12.71176470588235210.805
944012AF1-069 E
Adder
4.9388235294117654.198
940492AE2-034 E
Adder
3.25176470588235272.764
941031AE2-094 C
Adder
38.9070588235294133.071
941032AE2-094 E
Adder
17.42588235294117614.812
3145393UNCAMP
Adder
6.4517647058823535.484
916042Z1-036 E
Adder
30.54352941176470525.962
938771AE1-103 C
Adder
3.12235294117647082.654
938772AE1-103 E
Adder
4.3117647058823533.665
3142296MT RD221
50/50
0.1380.138
3142366NRTHEST
50/50
0.2110.211
3143316POE
Adder
1.4917647058823531.268
3145256KINGFORK
Adder
1.11529411764705880.948
3145506HICKORY
Adder
2.38470588235294122.027
3150391LDYSMT3
50/50
5.5445.544
3150401LDYSMT4
50/50
5.5555.555
3150411LDYSMT5
50/50
5.5725.572
3150601CHESTF5
Adder
71.6458823529411960.899
3150651CHESTF6
Adder
20.99647058823529717.847
3150701DARBY 4
50/50
2.9132.913
3150731STONECA
Adder
7.7717647058823536.606
3150831SPRUNCA
Adder
10.2905882352941188.747
3150841SPRUNCB
Adder
10.2905882352941188.747
3150921YORKTN3
Adder
133.3164705882353113.319
925865AC1-065 E
Adder
18.27411764705882315.533
926412AC1-112 E
50/50
1.2791.279
926662AC1-147 E
Adder
1.45764705882352951.239
926755AC1-161 E
Adder
14.30941176470588312.163
927226AC1-216 E
Adder
8.6447058823529417.348
934392AD1-063 E
Adder
1.17647058823529421
934782AD1-105 E
Adder
2.9682352941176472.523
935112AD1-144 E
Adder
1.0352941176470590.88
936591AD2-074 C
Adder
6.0611764705882365.152
936592AD2-074 E
Adder
9.8894117647058838.406
942341AE2-247 C
Adder
1.63294117647058811.388
942342AE2-247 E
Adder
2.2552941176470591.917
943461AF1-017 C
Adder
1.47764705882352951.256
943462AF1-017 E
Adder
2.4117647058823532.05
943612AF1-032 E
Adder
1.00941176470588250.858
943741AF1-042 C
Adder
3.1717647058823532.696
943742AF1-042 E
Adder
5.1741176470588234.398
961951AG1-038 C
Adder
3.50588235294117642.98
961952AG1-038 E
Adder
4.8411764705882364.115
966661AG1-536 C
Adder
5.8482352941176474.971
966662AG1-536 E
Adder
7.857647058823536.679
966871AG1-558 C
Adder
2.71882352941176462.311
966872AG1-558 E
Adder
1.36941176470588231.164
966881AG1-559 C
50/50
2.8382.838
966882AG1-559 E
50/50
1.431.43
3152251N ANNA1
50/50
40.87840.878
3152261N ANNA2
50/50
40.89340.893
316076AC2-137 E
Adder
1.50588235294117641.28
316078AC2-138 E
Adder
0.99647058823529410.847
316157AD2-030 E
Adder
1.30235294117647071.107
913392Y1-086 E
Adder
2.38588235294117632.028
916192Z1-068 E
Adder
2.0635294117647061.754
923832AB2-022 E
Adder
1.34705882352941191.145
923842AB2-024 E
Adder
1.97176470588235291.676
923852AB2-025 E
Adder
1.19058823529411771.012
930122AB1-027 E
50/50
1.5721.572
938552AE1-074 E
Adder
1.38000000000000011.173
939312AE1-162 E
Adder
1.58588235294117651.348
946262AF1-291 E
Adder
1.61764705882352941.375
957492AF2-043 E
Adder
1.55294117647058831.32
957601AF2-054 C
Adder
2.321.972
957602AF2-054 E
Adder
1.54705882352941181.315
962861AG1-135 C
Adder
6.6023529411764715.612
962862AG1-135 E
Adder
4.40117647058823553.741
962962AG1-145 E
Adder
1.61647058823529431.374
963611AG1-210 C
Adder
0.7117647058823530.605
963612AG1-210 E
Adder
1.06823529411764720.908
964211AG1-282 C
Adder
2.16705882352941171.842
964212AG1-282 E
Adder
1.44470588235294131.228
901082W1-029 E
Adder
34.4682352941176529.298
917122Z2-027 E
Adder
1.4552941176470591.237
925332AB2-190 E
Adder
9.057647058823537.699
925522AC1-027 E
Adder
1.3364705882352941.136
942001AE2-212 C
Adder
2.40588235294117642.045
942002AE2-212 E
Adder
1.60352941176470591.363
957832AF2-077 E
Adder
1.57882352941176471.342
957871AF2-081 C
Adder
10.904705882352949.269
957872AF2-081 E
Adder
4.6741176470588233.973
958161AF2-110 C
Adder
1.49058823529411751.267
958162AF2-110 E
Adder
2.3717647058823532.016
3138116ELKO L286
Adder
1.57058823529411761.335
3141813NORNECK
Adder
0.94823529411764720.806
933291AC2-141 C
Adder
33.5211764705882428.493
933292AC2-141 E
Adder
14.30941176470588312.163
939411AE1-173 C
Adder
93.7423529411764679.681
939412AE1-173 E
Adder
62.4952941176470653.121
934012AD1-025 E
Adder
11.1917647058823539.513
927041AC1-191 C
Adder
10.915294117647069.278
927042AC1-191 E
Adder
5.4376470588235294.622
3130536PAPERMILL
Adder
7.2870588235294126.194
3145946PLYMOUTH TP
Adder
0.33764705882352940.287
3146326AYDLETT TAP
Adder
1.47764705882352951.256
316004AC1-112 C
50/50
0.3720.372
316160AE1-175 E
Adder
1.33411764705882341.134
316169AC1-164 GEN
Adder
45.3376470588235338.537
316233AE1-074 C
Adder
2.73882352941176472.328
316240AF1-291 C
Adder
2.42588235294117642.062
316312AB1-027 C
50/50
0.5970.597
924516AB2-100 E1
Adder
2.91411764705882352.477
924517AB2-100 E2
Adder
2.91411764705882352.477
926785AC1-164_E
Adder
20.36941176470588417.314
934065AD1-033 E
Adder
5.49411764705882364.67
937226AE2-253 E
Adder
6.3811764705882365.424
939612AE1-191 E
Adder
6.2458823529411775.309
3150371LDYSMT1
50/50
5.3335.333
3150381LDYSMT2
50/50
5.4025.402
315051AA1-145 CT1
50/50
5.755.75
315052AA1-145 CT2
50/50
5.7475.747
939246AE1-155 E
Adder
9.4658823529411768.046
919153AA1-139 E2
Adder
4.463.791
919152AA1-139 E1
Adder
4.463.791
920692AA2-178 E
Adder
4.3352941176470593.685
924814AB2-134 E
Adder
14.1612.036
316084AB2-161 E
Adder
6.0929411764705895.179
932046AC2-012 E
Adder
14.41411764705882512.252
316311AC2-079 C
Adder
6.2752941176470595.334
932596AC2-079 E
Adder
10.2388235294117648.703
934146AD1-041 E
Adder
3.9035294117647063.318
934576AD1-082 E
Adder
4.8541176470588244.126
316349AD2-085 C
Adder
3.7682352941176473.203
936666AD2-085 E
Adder
6.1494117647058835.227
961611AG1-000B C
Adder
17.75176470588235515.089
941591AE2-156 C
Adder
19.6952941176470616.741
944581AF1-123 C
Adder
49.87411764705882442.393
944582AF1-123 E
Adder
114.2058823529411997.075
944591AF1-124 C
Adder
50.0517647058823542.544
944592AF1-124 E
Adder
114.6297.427
944601AF1-125 C
Adder
49.1058823529411841.74
944602AF1-125 E
Adder
112.412941176470695.551
944631AF1-128 C
Adder
44.8294117647058838.105
958261AF2-120 C
Adder
6.7976470588235295.778
958262AF2-120 E
Adder
4.53176470588235253.852
934501AD1-074 C
Adder
35.1647058823529429.89
934502AD1-074 E
Adder
17.90117647058823615.216
934511AD1-075 C
Adder
8.7917647058823527.473
934512AD1-075 E
Adder
4.4752941176470593.804
935161AD1-151 C
Adder
18.08588235294117715.373
935162AD1-151 E
Adder
12.0576470588235310.249
938531AE1-072 C
Adder
19.15764705882352816.284
938532AE1-072 E
Adder
9.9870588235294138.489
939191AE1-149 C
Adder
11.8810.098
939192AE1-149 E
Adder
7.9200000000000016.732
939261AE1-157 C
50/50
16.59116.591
939262AE1-157 E
50/50
8.9998.999
939602AE1-190 E
Adder
1.56117647058823541.327
940431AE2-027 C
Adder
14.49176470588235312.318
940432AE2-027 E
Adder
9.6611764705882348.212
940481AE2-033 C
Adder
16.55647058823529614.073
940482AE2-033 E
Adder
11.1611764705882369.487
940541AE2-040 C
Adder
2.94352941176470572.502
940551AE2-041 C
Adder
7.8435294117647066.667
940641AE2-051 C
Adder
17.55058823529411814.918
940642AE2-051 E
Adder
11.7000000000000019.945
941101AE2-104 C
Adder
3.65411764705882373.106
941102AE2-104 E
Adder
5.80941176470588254.938
943471AF1-018 C
Adder
7.8435294117647066.667
944641AF1-129 C
Adder
115.3152941176470698.018
3150431FOUR RIVERA
50/50
3.613.61
3150441FOUR RIVERB
50/50
3.613.61
3150451FOUR RIVERC
50/50
4.414.41
3150461FOUR RIVERD
50/50
3.5573.557
3150471FOUR RIVERE
50/50
3.5573.557
3150481FOUR RIVERF
50/50
4.3444.344
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.1265.126
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.55931.559
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.04923.049
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.18992.189
G-007PJM->LTFIMP_G-007
CMTX_NF
5.6455.645
NYPJM->LTFIMP_NY
CLTF
2.6672.667
LGEELTFEXP_LGEE->PJM
CLTF
1.3551.355
WECLTFEXP_WEC->PJM
CLTF
0.6690.669
CPLELTFEXP_CPLE->PJM
CLTF
10.74810.748
TVALTFEXP_TVA->PJM
CLTF
6.2796.279
MECLTFEXP_MEC->PJM
CLTF
4.0634.063
LAGNLTFEXP_LAGN->PJM
CLTF
7.8427.842
SIGELTFEXP_SIGE->PJM
CLTF
0.2590.259
O66PJM->LTFIMP_O-066
CMTX_NF
35.97435.974

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.94 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3379.54
MW Contribution:118.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
963041AG1-153 C
50/50
4.3484.348
963042AG1-153 E
50/50
6.5226.522
3145413WATKINS
Adder
0.54117647058823540.46
944011AF1-069 C
50/50
10.20810.208
944012AF1-069 E
50/50
3.9663.966
941031AE2-094 C
50/50
31.24231.242
941032AE2-094 E
50/50
13.99213.992
957481AF2-042 C
Adder
12.04117647058823510.235
3145393UNCAMP
Adder
4.7823529411764714.065
916042Z1-036 E
Adder
22.54588235294117719.164
938771AE1-103 C
Adder
2.30941176470588251.963
938772AE1-103 E
Adder
3.18941176470588242.711
3143316POE
50/50
1.1011.101
3145256KINGFORK
Adder
0.81058823529411760.689
3145506HICKORY
Adder
1.7482352941176471.486
3150601CHESTF5
Adder
48.65647058823529441.358
3150651CHESTF6
Adder
14.8105882352941212.589
3150731STONECA
Adder
5.4305882352941184.616
3150831SPRUNCA
50/50
7.377.37
3150841SPRUNCB
50/50
7.377.37
3150921YORKTN3
Adder
92.9023529411764778.967
926662AC1-147 E
Adder
1.06470588235294120.905
926755AC1-161 E
50/50
10.44910.449
927226AC1-216 E
Adder
6.1082352941176475.192
935112AD1-144 E
Adder
0.75294117647058820.64
942341AE2-247 C
Adder
1.19529411764705881.016
942342AE2-247 E
Adder
1.65176470588235281.404
943461AF1-017 C
Adder
1.08235294117647070.92
943462AF1-017 E
Adder
1.76470588235294111.5
943612AF1-032 E
Adder
0.740.629
958502AF2-144 E
Adder
0.95058823529411770.808
3151021BRUNSWICKG1
50/50
6.3966.396
3151031BRUNSWICKG2
50/50
6.3966.396
3151041BRUNSWICKG3
50/50
6.3966.396
3151051BRUNSWICKS1
50/50
13.28713.287
3151081ELIZAR1
50/50
2.5662.566
3151091ELIZAR2
50/50
2.5212.521
3151101ELIZAR3
50/50
2.5992.599
3152251N ANNA1
50/50
47.55247.552
3152261N ANNA2
50/50
47.5747.57
3152411Z1-086 GT1
50/50
8.198.19
3152421Z1-086 GT2
50/50
8.1888.188
3152431Z1-086 GT3
50/50
8.1888.188
3152441Z1-086 ST
50/50
14.25614.256
316076AC2-137 E
Adder
0.99176470588235290.843
913392Y1-086 E
Adder
1.75294117647058821.49
916192Z1-068 E
Adder
1.51058823529411781.284
923832AB2-022 E
Adder
0.98941176470588230.841
923852AB2-025 E
Adder
0.90941176470588240.773
923862AB2-026 E
Adder
0.96705882352941170.822
925022AB2-158 E
50/50
4.8864.886
938552AE1-074 E
50/50
1.0491.049
938562AE1-075 E
Adder
0.82470588235294120.701
939312AE1-162 E
Adder
1.14235294117647060.971
946262AF1-291 E
Adder
1.14588235294117660.974
957492AF2-043 E
Adder
1.13882352941176480.968
962962AG1-145 E
Adder
1.10235294117647080.937
901082W1-029 E
Adder
25.35058823529411521.548
917122Z2-027 E
Adder
1.06941176470588250.909
925332AB2-190 E
Adder
6.3717647058823535.416
925522AC1-027 E
Adder
0.97764705882352940.831
942001AE2-212 C
50/50
1.7341.734
942002AE2-212 E
50/50
1.1561.156
957832AF2-077 E
Adder
1.07764705882352940.916
957871AF2-081 C
Adder
7.9988235294117666.799
957872AF2-081 E
Adder
3.42823529411764752.914
958161AF2-110 C
Adder
1.09411764705882360.93
958162AF2-110 E
Adder
1.74000000000000021.479
3138116ELKO L286
Adder
1.03411764705882360.879
933291AC2-141 C
50/50
24.47824.478
933292AC2-141 E
50/50
10.44910.449
939411AE1-173 C
50/50
72.77672.776
939412AE1-173 E
50/50
48.51748.517
934012AD1-025 E
Adder
7.9070588235294126.721
3146326AYDLETT TAP
Adder
1.08470588235294120.922
316160AE1-175 E
Adder
0.90941176470588240.773
316164AC1-076_C
50/50
0.8170.817
316169AC1-164 GEN
Adder
29.7105882352941225.254
316192AB2-158 C
50/50
1.8381.838
316233AE1-074 C
50/50
2.0822.082
316240AF1-291 C
Adder
1.721.462
316294AC1-161 C
50/50
3.9863.986
924516AB2-100 E1
Adder
2.21882352941176461.886
924517AB2-100 E2
Adder
2.21882352941176461.886
926785AC1-164_E
Adder
13.34823529411764811.346
934065AD1-033 E
Adder
4.0258823529411773.422
937226AE2-253 E
Adder
4.6788235294117653.977
926004AC1-076_E
50/50
4.684.68
919153AA1-139 E2
Adder
3.27058823529411762.78
919152AA1-139 E1
Adder
3.27058823529411762.78
924814AB2-134 E
Adder
10.004705882352948.504
316084AB2-161 E
Adder
4.4435294117647063.777
316044AC1-158 C1
50/50
14.72914.729
316045AC1-158 C2
50/50
14.72914.729
926739AC1-158 E1
50/50
38.52538.525
926740AC1-158 E2
50/50
38.52538.525
932046AC2-012 E
Adder
10.5364705882352958.956
316311AC2-079 C
Adder
4.5952941176470593.906
932596AC2-079 E
Adder
7.497647058823536.373
934576AD1-082 E
Adder
3.5411764705882353.01
316349AD2-085 C
Adder
2.7588235294117652.345
936666AD2-085 E
Adder
4.5011764705882353.826
961611AG1-000B C
Adder
12.62823529411764810.734
941591AE2-156 C
Adder
14.39882352941176612.239
944581AF1-123 C
50/50
36.58436.584
944582AF1-123 E
50/50
83.77383.773
944591AF1-124 C
50/50
36.71436.714
944592AF1-124 E
50/50
84.07784.077
944601AF1-125 C
50/50
36.02136.021
944602AF1-125 E
50/50
82.45882.458
944631AF1-128 C
Adder
30.4447058823529425.878
935161AD1-151 C
Adder
12.74823529411764710.836
935162AD1-151 E
Adder
8.4988235294117667.224
938531AE1-072 C
Adder
14.05529411764705811.947
938532AE1-072 E
Adder
7.3270588235294126.228
939191AE1-149 C
50/50
8.6438.643
939192AE1-149 E
50/50
5.7625.762
940431AE2-027 C
Adder
10.2917647058823528.748
940432AE2-027 E
Adder
6.8611764705882355.832
940481AE2-033 C
Adder
12.64705882352941110.75
940482AE2-033 E
Adder
8.5258823529411767.247
940541AE2-040 C
Adder
2.24941176470588241.912
940641AE2-051 C
50/50
13.8813.88
940642AE2-051 E
50/50
9.2539.253
941101AE2-104 C
Adder
2.68117647058823532.279
941102AE2-104 E
Adder
4.2623529411764713.623
944641AF1-129 C
Adder
81.343529411764769.142
3150851SPRUNCC
50/50
0.1320.132
3150861SPRUNCD
50/50
0.1320.132
316303AF2-085
50/50
3.2933.293
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.9113.911
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.47618.476
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.62115.621
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
69.2669.26
G-007PJM->LTFIMP_G-007
CMTX_NF
4.2794.279
NYPJM->LTFIMP_NY
CLTF
2.0512.051
LGEELTFEXP_LGEE->PJM
CLTF
0.8310.831
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
CPLELTFEXP_CPLE->PJM
CLTF
8.2058.205
TVALTFEXP_TVA->PJM
CLTF
4.3954.395
MECLTFEXP_MEC->PJM
CLTF
2.5882.588
LAGNLTFEXP_LAGN->PJM
CLTF
5.5035.503
SIGELTFEXP_SIGE->PJM
CLTF
0.1630.163
O66PJM->LTFIMP_O-066
CMTX_NF
27.29527.295
CONTINGENCY 'DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 3_SRT-A'
 OPEN BRANCH FROM BUS 314909 TO BUS 314960 CKT 3   /*8FENTRES     500.0 - 6FENT1       230.0
END
CONTINGENCY 'DVP P1-3: 8FENTRESS 500 - 6FENT1 230 XFMR 1_SRT-A'
 OPEN BRANCH FROM BUS 314909 TO BUS 314960 CKT 1   /*8FENTRES     500.0 - 6FENT1       230.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A'
 OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1   /*8FENTRES     500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
314960 to 314909 ckt 1
314960 to 314909 ckt 2
314960 to 314909 ckt 3
314212 to 314150 ckt 1
314322 to 314914 ckt 1
316171 to 314481 ckt 1
314150 to 939260 ckt 1
314905 to 314900 ckt 1
314903 to 314908 ckt 1
314909 to 314466 ckt 1
314909 to 314466 ckt 2
314911 to 314905 ckt 1
314934 to 314916 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AF1-125 was evaluated as a 820.0 MW injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC113.52 %678.68B770.4633.33
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC106.87 %678.68B725.2936.58
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC113.06 %678.68B767.333.33
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC106.41 %678.68B722.1636.58
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P1-2: LN 271_SRT-A
SingleAC111.0 %678.68B753.35165.69
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P1-2: LN 2240_SRT-A
SingleAC111.0 %678.68B753.33165.69

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.52 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:770.46
MW Contribution:33.33
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.06 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:814.82
MW Contribution:37.37
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.0258.025
3150651CHESTF6
80/20
3.3173.317
3150831SPRUNCA
80/20
1.4311.431
3150841SPRUNCB
80/20
1.4311.431
3156056W1-029WIND
80/20
0.5460.546
3156116Z1-036WIND
80/20
0.9860.986
901082W1-029 E
80/20
3.6623.662
916042Z1-036 E
80/20
6.626.62
916192Z1-068 E
80/20
0.2130.213
941032AE2-094 E
80/20
11.86611.866
944012AF1-069 E
80/20
3.8773.877
961942AG1-037 E
80/20
0.0860.086
963041AG1-153 C
80/20
1.7621.762
963042AG1-153 E
80/20
2.6422.642
916191Z1-068 C
80/20
0.030.03
961611AG1-000B C
80/20
1.5261.526
940541AE2-040 C
80/20
0.8680.868
941591AE2-156 C
80/20
5.0815.081
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
80/20
10.29210.292
944582AF1-123 E
80/20
23.56823.568
944591AF1-124 C
80/20
10.32910.329
944592AF1-124 E
80/20
23.65323.653
944601AF1-125 C
80/20
10.13310.133
944602AF1-125 E
80/20
23.19823.198
944631AF1-128 C
80/20
20.96620.966
944641AF1-129 C
80/20
30.36730.367
961612AG1-000B E
80/20
2.2892.289
316303AF2-085
80/20
1.8321.832
958502AF2-144 E
Adder
2.8294117647058822.405
943573AF1-028 BT
80/20
15.77615.776

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.87 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:725.29
MW Contribution:36.58
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.5 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:777.06
MW Contribution:38.72
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.4243.424
3150831SPRUNCA
80/20
1.4991.499
3150841SPRUNCB
80/20
1.4991.499
3151311EDGECMA
80/20
2.4292.429
3156056W1-029WIND
80/20
0.6050.605
3156116Z1-036WIND
80/20
1.11.1
901082W1-029 E
80/20
4.0534.053
916042Z1-036 E
80/20
7.3857.385
916192Z1-068 E
80/20
0.2340.234
941032AE2-094 E
80/20
14.50614.506
944012AF1-069 E
80/20
4.744.74
961942AG1-037 E
80/20
0.0980.098
963041AG1-153 C
80/20
2.1352.135
963042AG1-153 E
80/20
3.2023.202
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5981.598
940541AE2-040 C
80/20
1.0031.003
941591AE2-156 C
80/20
5.5525.552
943571AF1-028 C
Adder
-12.025882352941176-10.222
944581AF1-123 C
80/20
11.29511.295
944582AF1-123 E
80/20
25.86425.864
944591AF1-124 C
80/20
11.33511.335
944592AF1-124 E
80/20
25.95725.957
944601AF1-125 C
80/20
11.12111.121
944602AF1-125 E
80/20
25.45825.458
944641AF1-129 C
80/20
31.34631.346
961602AG1-000A E
80/20
1.8891.889
961612AG1-000B E
80/20
2.3972.397
316303AF2-085
80/20
2.1022.102
958502AF2-144 E
Adder
3.01882352941176452.566
943573AF1-028 BT
80/20
12.02612.026

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.06 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:767.3
MW Contribution:33.33
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.58 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:811.59
MW Contribution:37.37
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.0258.025
3150651CHESTF6
80/20
3.3173.317
3150831SPRUNCA
80/20
1.4311.431
3150841SPRUNCB
80/20
1.4311.431
3156056W1-029WIND
80/20
0.5460.546
3156116Z1-036WIND
80/20
0.9860.986
901082W1-029 E
80/20
3.6623.662
916042Z1-036 E
80/20
6.626.62
916192Z1-068 E
80/20
0.2130.213
941032AE2-094 E
80/20
11.86611.866
944012AF1-069 E
80/20
3.8773.877
961942AG1-037 E
80/20
0.0860.086
963041AG1-153 C
80/20
1.7621.762
963042AG1-153 E
80/20
2.6422.642
916191Z1-068 C
80/20
0.030.03
961611AG1-000B C
80/20
1.5261.526
940541AE2-040 C
80/20
0.8680.868
941591AE2-156 C
80/20
5.0815.081
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
80/20
10.29210.292
944582AF1-123 E
80/20
23.56823.568
944591AF1-124 C
80/20
10.32910.329
944592AF1-124 E
80/20
23.65323.653
944601AF1-125 C
80/20
10.13310.133
944602AF1-125 E
80/20
23.19823.198
944631AF1-128 C
80/20
20.96620.966
944641AF1-129 C
80/20
30.36730.367
961612AG1-000B E
80/20
2.2892.289
316303AF2-085
80/20
1.8321.832
958502AF2-144 E
Adder
2.8294117647058822.405
943573AF1-028 BT
80/20
15.77615.776

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.41 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:722.16
MW Contribution:36.58
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.03 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:773.89
MW Contribution:38.72
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.4243.424
3150831SPRUNCA
80/20
1.4991.499
3150841SPRUNCB
80/20
1.4991.499
3151311EDGECMA
80/20
2.4292.429
3156056W1-029WIND
80/20
0.6050.605
3156116Z1-036WIND
80/20
1.11.1
901082W1-029 E
80/20
4.0534.053
916042Z1-036 E
80/20
7.3857.385
916192Z1-068 E
80/20
0.2340.234
941032AE2-094 E
80/20
14.50614.506
944012AF1-069 E
80/20
4.744.74
961942AG1-037 E
80/20
0.0980.098
963041AG1-153 C
80/20
2.1352.135
963042AG1-153 E
80/20
3.2023.202
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5981.598
940541AE2-040 C
80/20
1.0031.003
941591AE2-156 C
80/20
5.5525.552
943571AF1-028 C
Adder
-12.025882352941176-10.222
944581AF1-123 C
80/20
11.29511.295
944582AF1-123 E
80/20
25.86425.864
944591AF1-124 C
80/20
11.33511.335
944592AF1-124 E
80/20
25.95725.957
944601AF1-125 C
80/20
11.12111.121
944602AF1-125 E
80/20
25.45825.458
944641AF1-129 C
80/20
31.34631.346
961602AG1-000A E
80/20
1.8891.889
961612AG1-000B E
80/20
2.3972.397
316303AF2-085
80/20
2.1022.102
958502AF2-144 E
Adder
3.01882352941176452.566
943573AF1-028 BT
80/20
12.02612.026

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 271_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 271_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.0 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:753.35
MW Contribution:165.69
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3156056W1-029WIND
80/20
0.6120.612
3156116Z1-036WIND
80/20
1.1111.111
901082W1-029 E
80/20
4.1024.102
916042Z1-036 E
80/20
7.4627.462
944581AF1-123 C
80/20
51.16351.163
944582AF1-123 E
80/20
117.157117.157
944591AF1-124 C
80/20
51.34451.344
944592AF1-124 E
80/20
117.581117.581
944601AF1-125 C
80/20
50.37550.375
944602AF1-125 E
80/20
115.318115.318
941593AE2-156 BT
80/20
18.68818.688
961613AG1-000B BT
80/20
4.8344.834

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2240_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2240_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.0 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:753.33
MW Contribution:165.69
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3156056W1-029WIND
80/20
0.6120.612
3156116Z1-036WIND
80/20
1.1111.111
901082W1-029 E
80/20
4.1024.102
916042Z1-036 E
80/20
7.4627.462
944581AF1-123 C
80/20
51.16351.163
944582AF1-123 E
80/20
117.157117.157
944591AF1-124 C
80/20
51.34451.344
944592AF1-124 E
80/20
117.581117.581
944601AF1-125 C
80/20
50.37550.375
944602AF1-125 E
80/20
115.318115.318
941593AE2-156 BT
80/20
18.68818.688
961613AG1-000B BT
80/20
4.8344.834
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 271_SRT-A'
 OPEN BRANCH FROM BUS 314481 TO BUS 316171 CKT 1   /*6LANDSTN     230.0 - 6POCATY      230.0
END
CONTINGENCY 'DVP_P1-2: LN 2240_SRT-A'
 OPEN BRANCH FROM BUS 314466 TO BUS 316171 CKT 1   /*6FENTRES     230.0 - 6POCATY      230.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314466 to 314508 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
DVP_P1-2: LN 2193_SRT-A
SingleAC112.33 %134.42B151.06.89
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC110.03 %661.76B728.1534.2
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC101.32 %661.76B670.535.68
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P1-2: LN 588_SRT-A
SingleAC155.94 %678.68B1058.33373.01
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC111.3 %661.76B736.5134.2
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC102.58 %661.76B678.8335.68
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC108.36 %661.76B717.0734.2

Details for 3BREMO-3FORK UNION 115.0 kV Ckt 2 line l/o DVP_P1-2: LN 2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
Contingency Name:
DVP_P1-2: LN 2193_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.33 %
Rating:134.42 MVA
Rating Type:B
MVA to Mitigate:151.0
MW Contribution:6.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944581AF1-123 C
Adder
2.12705882352941171.808
944582AF1-123 E
Adder
4.8705882352941174.14
944591AF1-124 C
Adder
2.13411764705882371.814
944592AF1-124 E
Adder
4.88823529411764754.155
944601AF1-125 C
Adder
2.09411764705882361.78
944602AF1-125 E
Adder
4.7941176470588244.075
958502AF2-144 E
Adder
0.740.629

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.03 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:728.15
MW Contribution:34.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.398.39
3150651CHESTF6
80/20
3.4453.445
3150831SPRUNCA
80/20
1.4641.464
3150841SPRUNCB
80/20
1.4641.464
3156056W1-029WIND
80/20
0.5590.559
3156116Z1-036WIND
80/20
1.0071.007
901082W1-029 E
80/20
3.7483.748
916042Z1-036 E
80/20
6.7636.763
916192Z1-068 E
80/20
0.2190.219
941032AE2-094 E
80/20
11.9111.91
944012AF1-069 E
80/20
3.8913.891
961942AG1-037 E
80/20
0.0870.087
963041AG1-153 C
80/20
1.7571.757
963042AG1-153 E
80/20
2.6362.636
916191Z1-068 C
80/20
0.0310.031
961611AG1-000B C
80/20
1.5771.577
940541AE2-040 C
80/20
0.8830.883
941591AE2-156 C
80/20
5.2155.215
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
80/20
10.55910.559
944582AF1-123 E
80/20
24.1824.18
944591AF1-124 C
80/20
10.59710.597
944592AF1-124 E
80/20
24.26824.268
944601AF1-125 C
80/20
10.39710.397
944602AF1-125 E
80/20
23.823.8
944631AF1-128 C
80/20
21.92121.921
944641AF1-129 C
80/20
31.53431.534
961612AG1-000B E
80/20
2.3662.366
316303AF2-085
80/20
1.8091.809
958502AF2-144 E
Adder
2.68235294117647042.28
943573AF1-028 BT
80/20
15.50215.502

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.32 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:670.5
MW Contribution:35.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.3773.377
3150831SPRUNCA
80/20
1.4651.465
3150841SPRUNCB
80/20
1.4651.465
3151311EDGECMA
80/20
2.4182.418
3156056W1-029WIND
80/20
0.5910.591
3156116Z1-036WIND
80/20
1.0781.078
901082W1-029 E
80/20
3.9623.962
916042Z1-036 E
80/20
7.2357.235
916192Z1-068 E
80/20
0.2280.228
941032AE2-094 E
80/20
14.06514.065
944012AF1-069 E
80/20
4.5964.596
961942AG1-037 E
80/20
0.0970.097
963041AG1-153 C
80/20
2.072.07
963042AG1-153 E
80/20
3.1043.104
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5651.565
940541AE2-040 C
80/20
0.9830.983
941591AE2-156 C
80/20
5.4145.414
943571AF1-028 C
Adder
-11.711764705882354-9.955
944581AF1-123 C
80/20
11.01711.017
944582AF1-123 E
80/20
25.22825.228
944591AF1-124 C
80/20
11.05611.056
944592AF1-124 E
80/20
25.3225.32
944601AF1-125 C
80/20
10.84810.848
944602AF1-125 E
80/20
24.83224.832
944641AF1-129 C
80/20
30.90830.908
961602AG1-000A E
80/20
1.8811.881
961612AG1-000B E
80/20
2.3482.348
316303AF2-085
80/20
2.0152.015
958502AF2-144 E
Adder
2.84235294117647052.416
943573AF1-028 BT
80/20
11.71211.712

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 588_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:155.94 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1058.33
MW Contribution:373.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3156056W1-029WIND
80/20
2.1742.174
3156116Z1-036WIND
80/20
3.7493.749
901082W1-029 E
80/20
14.57514.575
916042Z1-036 E
80/20
25.17225.172
916192Z1-068 E
80/20
0.4760.476
916191Z1-068 C
80/20
0.0680.068
944581AF1-123 C
80/20
115.178115.178
944582AF1-123 E
80/20
263.744263.744
944591AF1-124 C
80/20
115.587115.587
944592AF1-124 E
80/20
264.699264.699
944601AF1-125 C
80/20
113.404113.404
944602AF1-125 E
80/20
259.605259.605

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.3 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:736.51
MW Contribution:34.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.398.39
3150651CHESTF6
80/20
3.4453.445
3150831SPRUNCA
80/20
1.4641.464
3150841SPRUNCB
80/20
1.4641.464
3156056W1-029WIND
80/20
0.5590.559
3156116Z1-036WIND
80/20
1.0071.007
901082W1-029 E
80/20
3.7483.748
916042Z1-036 E
80/20
6.7636.763
916192Z1-068 E
80/20
0.2190.219
941032AE2-094 E
80/20
11.9111.91
944012AF1-069 E
80/20
3.8913.891
961942AG1-037 E
80/20
0.0870.087
963041AG1-153 C
80/20
1.7571.757
963042AG1-153 E
80/20
2.6362.636
916191Z1-068 C
80/20
0.0310.031
961611AG1-000B C
80/20
1.5771.577
940541AE2-040 C
80/20
0.8830.883
941591AE2-156 C
80/20
5.2155.215
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
80/20
10.55910.559
944582AF1-123 E
80/20
24.1824.18
944591AF1-124 C
80/20
10.59710.597
944592AF1-124 E
80/20
24.26824.268
944601AF1-125 C
80/20
10.39710.397
944602AF1-125 E
80/20
23.823.8
944631AF1-128 C
80/20
21.92121.921
944641AF1-129 C
80/20
31.53431.534
961612AG1-000B E
80/20
2.3662.366
316303AF2-085
80/20
1.8091.809
958502AF2-144 E
Adder
2.68235294117647042.28
943573AF1-028 BT
80/20
15.50215.502

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.58 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:678.83
MW Contribution:35.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.3773.377
3150831SPRUNCA
80/20
1.4651.465
3150841SPRUNCB
80/20
1.4651.465
3151311EDGECMA
80/20
2.4182.418
3156056W1-029WIND
80/20
0.5910.591
3156116Z1-036WIND
80/20
1.0781.078
901082W1-029 E
80/20
3.9623.962
916042Z1-036 E
80/20
7.2357.235
916192Z1-068 E
80/20
0.2280.228
941032AE2-094 E
80/20
14.06514.065
944012AF1-069 E
80/20
4.5964.596
961942AG1-037 E
80/20
0.0970.097
963041AG1-153 C
80/20
2.072.07
963042AG1-153 E
80/20
3.1043.104
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5651.565
940541AE2-040 C
80/20
0.9830.983
941591AE2-156 C
80/20
5.4145.414
943571AF1-028 C
Adder
-11.711764705882354-9.955
944581AF1-123 C
80/20
11.01711.017
944582AF1-123 E
80/20
25.22825.228
944591AF1-124 C
80/20
11.05611.056
944592AF1-124 E
80/20
25.3225.32
944601AF1-125 C
80/20
10.84810.848
944602AF1-125 E
80/20
24.83224.832
944641AF1-129 C
80/20
30.90830.908
961602AG1-000A E
80/20
1.8811.881
961612AG1-000B E
80/20
2.3482.348
316303AF2-085
80/20
2.0152.015
958502AF2-144 E
Adder
2.84235294117647052.416
943573AF1-028 BT
80/20
11.71211.712

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.36 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:717.07
MW Contribution:34.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.398.39
3150651CHESTF6
80/20
3.4453.445
3150831SPRUNCA
80/20
1.4641.464
3150841SPRUNCB
80/20
1.4641.464
3156056W1-029WIND
80/20
0.5590.559
3156116Z1-036WIND
80/20
1.0071.007
901082W1-029 E
80/20
3.7483.748
916042Z1-036 E
80/20
6.7636.763
916192Z1-068 E
80/20
0.2190.219
941032AE2-094 E
80/20
11.9111.91
944012AF1-069 E
80/20
3.8913.891
961942AG1-037 E
80/20
0.0870.087
963041AG1-153 C
80/20
1.7571.757
963042AG1-153 E
80/20
2.6362.636
916191Z1-068 C
80/20
0.0310.031
961611AG1-000B C
80/20
1.5771.577
940541AE2-040 C
80/20
0.8830.883
941591AE2-156 C
80/20
5.2155.215
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
80/20
10.55910.559
944582AF1-123 E
80/20
24.1824.18
944591AF1-124 C
80/20
10.59710.597
944592AF1-124 E
80/20
24.26824.268
944601AF1-125 C
80/20
10.39710.397
944602AF1-125 E
80/20
23.823.8
944631AF1-128 C
80/20
21.92121.921
944641AF1-129 C
80/20
31.53431.534
961612AG1-000B E
80/20
2.3662.366
316303AF2-085
80/20
1.8091.809
958502AF2-144 E
Adder
2.68235294117647042.28
943573AF1-028 BT
80/20
15.50215.502
CONTINGENCY 'DVP_P1-2: LN 2193_SRT-A'
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
END
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A'
 OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1   /*8FENTRES     500.0 - 8YADKIN      500.0
END
314744 to 313708 ckt 2
313373 to 314765 ckt 1
314466 to 314508 ckt 1
313707 to 313373 ckt 1
314765 to 314749 ckt 1

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC108.48 %678.68B736.2233.33
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC108.04 %678.68B733.2233.33
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P1-2: LN 271_SRT-A
OPAC109.46 %678.68B742.85165.69

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.48 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:736.22
MW Contribution:33.33
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.77 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:772.11
MW Contribution:37.37
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.0247058823529426.821
3150651CHESTF6
Adder
3.3176470588235292.82
3150831SPRUNCA
Adder
1.43058823529411771.216
3150841SPRUNCB
Adder
1.43058823529411771.216
3156116Z1-036WIND
Adder
0.98588235294117640.838
916042Z1-036 E
Adder
6.625.627
941032AE2-094 E
Adder
11.86588235294117810.086
944012AF1-069 E
Adder
3.87764705882352923.296
961942AG1-037 E
Adder
0.085882352941176470.073
963041AG1-153 C
Adder
1.76117647058823561.497
963042AG1-153 E
Adder
2.6423529411764712.246
961611AG1-000B C
Adder
1.52588235294117651.297
940541AE2-040 C
Adder
0.86823529411764710.738
941591AE2-156 C
Adder
5.0811764705882354.319
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
Adder
10.2917647058823528.748
944582AF1-123 E
Adder
23.5682352941176520.033
944591AF1-124 C
Adder
10.3282352941176478.779
944592AF1-124 E
Adder
23.65294117647058820.105
944601AF1-125 C
Adder
10.1341176470588248.614
944602AF1-125 E
Adder
23.1976470588235319.718
944631AF1-128 C
Adder
20.9658823529411817.821
944641AF1-129 C
Adder
30.36705882352941525.812
961612AG1-000B E
Adder
2.28823529411764741.945
316303AF2-085
Adder
2.1552941176470591.832
958502AF2-144 E
Adder
2.8294117647058822.405

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.04 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:733.22
MW Contribution:33.33
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.32 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:769.11
MW Contribution:37.37
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.0247058823529426.821
3150651CHESTF6
Adder
3.3176470588235292.82
3150831SPRUNCA
Adder
1.43058823529411771.216
3150841SPRUNCB
Adder
1.43058823529411771.216
3156116Z1-036WIND
Adder
0.98588235294117640.838
916042Z1-036 E
Adder
6.625.627
941032AE2-094 E
Adder
11.86588235294117810.086
944012AF1-069 E
Adder
3.87764705882352923.296
961942AG1-037 E
Adder
0.085882352941176470.073
963041AG1-153 C
Adder
1.76117647058823561.497
963042AG1-153 E
Adder
2.6423529411764712.246
961611AG1-000B C
Adder
1.52588235294117651.297
940541AE2-040 C
Adder
0.86823529411764710.738
941591AE2-156 C
Adder
5.0811764705882354.319
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
Adder
10.2917647058823528.748
944582AF1-123 E
Adder
23.5682352941176520.033
944591AF1-124 C
Adder
10.3282352941176478.779
944592AF1-124 E
Adder
23.65294117647058820.105
944601AF1-125 C
Adder
10.1341176470588248.614
944602AF1-125 E
Adder
23.1976470588235319.718
944631AF1-128 C
Adder
20.9658823529411817.821
944641AF1-129 C
Adder
30.36705882352941525.812
961612AG1-000B E
Adder
2.28823529411764741.945
316303AF2-085
Adder
2.1552941176470591.832
958502AF2-144 E
Adder
2.8294117647058822.405

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 271_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 271_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.46 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:742.85
MW Contribution:165.69
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3156116Z1-036WIND
Adder
1.1117647058823530.945
916042Z1-036 E
Adder
7.4623529411764716.343
944581AF1-123 C
50/50
51.16351.163
944582AF1-123 E
50/50
117.157117.157
944591AF1-124 C
50/50
51.34451.344
944592AF1-124 E
50/50
117.581117.581
944601AF1-125 C
50/50
50.37550.375
944602AF1-125 E
50/50
115.318115.318
941593AE2-156 BT
50/50
18.68818.688
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 271_SRT-A'
 OPEN BRANCH FROM BUS 314481 TO BUS 316171 CKT 1   /*6LANDSTN     230.0 - 6POCATY      230.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314466 to 314508 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
DVP_P1-2: LN 2193_SRT-A
OPAC112.33 %134.42B151.06.89
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC103.72 %661.76B686.4134.2
GD1DVP
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
DVP_P1-2: LN 588_SRT-A
OPAC155.94 %678.68B1058.33373.01
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC105.01 %661.76B694.9134.2
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC102.08 %661.76B675.5134.2

Details for 3BREMO-3FORK UNION 115.0 kV Ckt 2 line l/o DVP_P1-2: LN 2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
Contingency Name:
DVP_P1-2: LN 2193_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.33 %
Rating:134.42 MVA
Rating Type:B
MVA to Mitigate:151.0
MW Contribution:6.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944581AF1-123 C
Adder
2.12705882352941171.808
944582AF1-123 E
Adder
4.8705882352941174.14
944591AF1-124 C
Adder
2.13411764705882371.814
944592AF1-124 E
Adder
4.88823529411764754.155
944601AF1-125 C
Adder
2.09411764705882361.78
944602AF1-125 E
Adder
4.7941176470588244.075
958502AF2-144 E
Adder
0.740.629

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.72 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:686.41
MW Contribution:34.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.3894117647058837.131
3150651CHESTF6
Adder
3.44470588235294132.928
3150831SPRUNCA
Adder
1.46470588235294131.245
3150841SPRUNCB
Adder
1.46470588235294131.245
3156116Z1-036WIND
Adder
1.00705882352941180.856
916042Z1-036 E
Adder
6.7623529411764715.748
941032AE2-094 E
Adder
11.90941176470588110.123
944012AF1-069 E
Adder
3.8917647058823533.308
961942AG1-037 E
Adder
0.087058823529411760.074
963041AG1-153 C
Adder
1.75764705882352961.494
963042AG1-153 E
Adder
2.63647058823529432.241
961611AG1-000B C
Adder
1.57764705882352941.341
940541AE2-040 C
Adder
0.88352941176470590.751
941591AE2-156 C
Adder
5.2152941176470584.433
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
Adder
10.568.976
944582AF1-123 E
Adder
24.18000000000000320.553
944591AF1-124 C
Adder
10.5964705882352939.007
944592AF1-124 E
Adder
24.2670588235294120.627
944601AF1-125 C
Adder
10.3964705882352948.837
944602AF1-125 E
Adder
23.820.23
944631AF1-128 C
Adder
21.92117647058823618.633
944641AF1-129 C
Adder
31.5341176470588226.804
961612AG1-000B E
Adder
2.36588235294117682.011
316303AF2-085
Adder
2.12823529411764721.809
958502AF2-144 E
Adder
2.68235294117647042.28

Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 588_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:155.94 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1058.33
MW Contribution:373.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3156056W1-029WIND
50/50
2.1742.174
3156116Z1-036WIND
50/50
3.7493.749
901082W1-029 E
50/50
14.57514.575
916042Z1-036 E
50/50
25.17225.172
916192Z1-068 E
50/50
0.4760.476
916191Z1-068 C
50/50
0.0680.068
944581AF1-123 C
50/50
115.178115.178
944582AF1-123 E
50/50
263.744263.744
944591AF1-124 C
50/50
115.587115.587
944592AF1-124 E
50/50
264.699264.699
944601AF1-125 C
50/50
113.404113.404
944602AF1-125 E
50/50
259.605259.605

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.01 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:694.91
MW Contribution:34.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.3894117647058837.131
3150651CHESTF6
Adder
3.44470588235294132.928
3150831SPRUNCA
Adder
1.46470588235294131.245
3150841SPRUNCB
Adder
1.46470588235294131.245
3156116Z1-036WIND
Adder
1.00705882352941180.856
916042Z1-036 E
Adder
6.7623529411764715.748
941032AE2-094 E
Adder
11.90941176470588110.123
944012AF1-069 E
Adder
3.8917647058823533.308
961942AG1-037 E
Adder
0.087058823529411760.074
963041AG1-153 C
Adder
1.75764705882352961.494
963042AG1-153 E
Adder
2.63647058823529432.241
961611AG1-000B C
Adder
1.57764705882352941.341
940541AE2-040 C
Adder
0.88352941176470590.751
941591AE2-156 C
Adder
5.2152941176470584.433
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
Adder
10.568.976
944582AF1-123 E
Adder
24.18000000000000320.553
944591AF1-124 C
Adder
10.5964705882352939.007
944592AF1-124 E
Adder
24.2670588235294120.627
944601AF1-125 C
Adder
10.3964705882352948.837
944602AF1-125 E
Adder
23.820.23
944631AF1-128 C
Adder
21.92117647058823618.633
944641AF1-129 C
Adder
31.5341176470588226.804
961612AG1-000B E
Adder
2.36588235294117682.011
316303AF2-085
Adder
2.12823529411764721.809
958502AF2-144 E
Adder
2.68235294117647042.28

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:675.51
MW Contribution:34.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.3894117647058837.131
3150651CHESTF6
Adder
3.44470588235294132.928
3150831SPRUNCA
Adder
1.46470588235294131.245
3150841SPRUNCB
Adder
1.46470588235294131.245
3156116Z1-036WIND
Adder
1.00705882352941180.856
916042Z1-036 E
Adder
6.7623529411764715.748
941032AE2-094 E
Adder
11.90941176470588110.123
944012AF1-069 E
Adder
3.8917647058823533.308
961942AG1-037 E
Adder
0.087058823529411760.074
963041AG1-153 C
Adder
1.75764705882352961.494
963042AG1-153 E
Adder
2.63647058823529432.241
961611AG1-000B C
Adder
1.57764705882352941.341
940541AE2-040 C
Adder
0.88352941176470590.751
941591AE2-156 C
Adder
5.2152941176470584.433
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
Adder
10.568.976
944582AF1-123 E
Adder
24.18000000000000320.553
944591AF1-124 C
Adder
10.5964705882352939.007
944592AF1-124 E
Adder
24.2670588235294120.627
944601AF1-125 C
Adder
10.3964705882352948.837
944602AF1-125 E
Adder
23.820.23
944631AF1-128 C
Adder
21.92117647058823618.633
944641AF1-129 C
Adder
31.5341176470588226.804
961612AG1-000B E
Adder
2.36588235294117682.011
316303AF2-085
Adder
2.12823529411764721.809
958502AF2-144 E
Adder
2.68235294117647042.28
CONTINGENCY 'DVP_P1-2: LN 2193_SRT-A'
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
END
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A'
 OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1   /*8FENTRES     500.0 - 8YADKIN      500.0
END
314744 to 313708 ckt 2
313373 to 314765 ckt 1
314466 to 314508 ckt 1
313707 to 313373 ckt 1
314765 to 314749 ckt 1

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - Issues Found

Executive Summary for Dynamic Stability Analysis using PSSE

New Service Requests (projects) in PJM Transition Cycle 1 Cluster 29 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 29 projects.

 

Table 1: Transition Cycle 1 Cluster 29 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO (MW)

MWE (MW)

MWC (MW)

Point of Interconnection

29

AF1-123

Wind

Dominion

833

833

253.2

Harper 230 kV

AF1-124

Wind

Dominion

836

836

254.1

Harper 230 kV

AF1-125

Wind

Dominion

820

820

249.3

Harper 230 kV

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 29 projects will meet the dynamics requirements of the NERC, Dominion Energy, and PJM reliability standards.

 

The load flow case finalized for Phase 2 was used as a starting point and was updated based on latest Cluster 29 data, Dominion Energy recommended transmission changes and withdrawn generation. Projects in vicinity of Cluster 29 have been dispatched online at maximum power output with near unity power factor measured at the high-side of the main substation transformer. The dynamic models for Cluster 29 projects were updated based on the latest DP2 data and include any tuning adjustments recommended during Phase 2.

 

This analysis currently was performed using the PSSE library models provided the developer.  Dominion Energy Transmission provided the models for the FACT’s devices for the AF1-123, AF1-124, and AF1-125 queue projects.

 

Cluster 29 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. 133 contingencies were studied, each with a 20 second simulation time period. The studied contingencies included:

  • Steady-state operation (30 seconds)
  • Three-phase faults with normal clearing time
  • Single-phase bus faults with normal clearing time
  • Single-phase faults with stuck breaker
  • Single-phase faults with delayed clearing at remote end
  • Single-phase faults with loss of multiple-circuit tower line.

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

The results of the analysis were evaluated against the following recovery criteria per PJM’s Regional Transmission Planning Process and Transmission Owner criteria:

  • Cluster 29 projects were able to ride through the faults (except for faults where protective action trips a generator(s)).
  • The system with Cluster 29 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.
  • Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus) and the final voltages are within the steady-state voltage ranges below per Dominion Energy’s transmission planning criteria.
    • P1 Category Contingencies:
      • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.01 to 1.096 p.u. for 500 kV facilities
    • P2, P4, P5, and P7 Category Contingencies:
      • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.00 to 1.096 p.u. for 500 kV facilities
  • No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

AF1-123, AF1-124 and AF1-125 met the 0.95 lagging and leading power factor requirements at the point of interconnect (POI) at Harpers 230 kV substation.

 

The results of the analysis identified that the addition of the AF1-123, AF1-124 and AF1-125 queue projects resulted in instability in a majority of contingencies. The following mitigation is required to maintain stability:

  • Add a second 500 kV line from the Updated Fentress to the Yadkin substations
  • Add two 230 kV gas-insulated lines (GILs) from the existing Fentress to the New Fentress substations
  • All 230 kV breakers (212822, 269T2128, 26922, 224022-1, 224022-2, 208722, W22, L122, L322, H22, SC122, SC322, SC422, SV122, and the new breakers G1 and G2 for the gas insulated lines) at Fentress 230 kV Substation require a 14 cycle clearing time
  • Dual pilot protection is required for the Fentress to AD1-033 POI 230 kV line circuit 2240

No voltage or frequency protection trips occurred for AF1-123, AF1-124 and AF1-125 queue projects using the settings provided.

 

The AF1-123, AF1-124 and AF1-125 queue projects exhibited slow active power recovery after the fault cleared and this is recovery was expected based on the model documentation provided for the OEMs’ wind turbine. The WGOWECC controller, clamps the active power at 95% for up to 5 seconds to ensure steady recovery of the system and then releases the active power to 100% to restore full operation.

 

An EMT analysis and stability analysis using a PSS/E user defined model is recommended for AF1-123, AF1-124 and AF1-125 due to the CSCR values being less than 3. A user defined model is under development by the IC and it will be evaluated as a sensitivity once the model initializes properly.

 

AE2-156 reactive power and terminal voltage recovery was not settling to a steady state value during the analysis. However, it was observed that reactive settling doesn’t violate PJM or Dominion’s criteria. The models were tuned to achieve a faster recovery in Cluster 46 Phase 2 Stability Analysis.

 

AE2-051 reactive power and terminal voltage recovery was not settling to a steady state value during the analysis. The models can be tuned to achieve a faster recovery upon request.

 

AB2-169 generator tripped for overvoltage’s above 1.25 p.u. The unit rode through when the pickup timer  was increased from 0.0 seconds to 0.0125 seconds.

 

Executive Summary for Dynamic Stability Analysis using PSCAD/EMT

 

The EMT dynamic performance analysis was revelated with the latest PSCAD models pprovided by CVOW (AF1-123, 124 & 125) generation developer.   A detailed model quality testing was performed. Below are some deficiency and corresponding update that were applied to the plant model.

 

  • CVOW initialization issues were cured by using a stiff voltage source model at POI during the initialization period and disconnected later in the simulation.
  • Pi-circuit equivalents for 66 kV IAC cables were updated to Bergeron models using best available data.
  • Onshore cable section was updated into onshore and HDD sections using best available data.
  • Earthing transformer model was included at the 66 kV delta winding of OSS transformer.
  • OSS LTC transformer taps were set to match values used for TC1 analysis.
  • Harpers STATCOM model was updated to latest OEM model.

 

Preliminary results of CVOW performance for Summer peak and Light Load system conditions for select TPL contingencies indicate the following:

 

  • Instability of the project post-fault was observed for select P1 and P6 contingencies prior to the inclusion of all proposed upgrades.
  • With the inclusion of the proposed upgrades namely the 500 kV Line 5005 between Fentress and Yadkin and two GIL circuits between new and existing Fentress 230 kV, CVOW fully recovers post-fault for a severe P4 contingency.
  • The preliminary results demonstrate the impact of the weak system strength and the improvements provided by the proposed upgrades.
  • Analysis of CVOW performance for severe P6 contingencies with the proposed upgrades is ongoing.
  • Investigation of partial nuisance tripping of CVOW post-fault is also on-going for other contingencies and system conditions.

 

CVOW Flicker

 

Preliminary analysis shows flicker issue induced by CVOW project. Preliminary flicker analysis was conducted using a range of ramp rates in the absence of data on power fluctuation in response to wind speed variation. To assess flicker impact, MEPPI evaluated multiple wind profiles, spanning from conservative scenarios to less conservative ramp rates. Results indicate that the ramp rate significantly influences the flicker observed at the POI and we violate the criteria of 1 Pst for various profiles considered. Flicker analysis was performed in PSCAD using detailed models of the CVOW project and a system equivalent at the POI.  In order to mitigate the flicker issue an addition of 300 MVAR STATCOM will need to be installed at Fentress 230 kV Substation.

 

Note:

 

TC1 Phase 3 Dynamic  Stability analysis has been completed by using library model provided in TC1 Phase 2.  For TC1 Phase 3, a PSSE User Defined Model was requested due to low SCR concerns in the area. The CVOW project developer provided a User Defined Model that did not work properly in the TC1 base case. The CVOW  project development team is actively working on getting an updated User Defined Model for the AF1-123/AF1-124/AF1-125 projects from Siemens Gamesa Renewable Energy (SGRE). This updated model was not ready at the time TC1 Phase 3 studies concluded, and CVOW will need to initiate a Necessary Study request post GIA to have the updated User Defined Model provided to PJM to perform a Dynamic Stability analysis for the AF1-123/AF1-124/AF1-125 projects.

Also, CVOW notified PJM of a change for nineteen (19) of the GSUs that are planned to be installed for the CVOW Project for Queue Position AF1-123 (OSS T1L11). Note that these 19 GSUs – installed in 19 of the 59 wind turbine generators – have been manufactured and have higher impedance values that was in the original design. Following evaluation, it has been determined that these changes in impedances to these 19 units do not affect the MFO/gross output, have very limited changes for the  losses, and the MW output at the POI will be changed, but insubstantially. The other queues AF1-124 & AF1-125 are unchanged/unaffected. This GSU change for AF1-123 will also be evaluated as part of the Necessary Study being requested above.

 

Bellow are some of the item that will be captured during post GIA Necessary study request for CVOW project.

 

  1. The User Defined Model dynamic stability analysis for AF1-123/AF1-124/AF1-125 as well as the GSU change for AF1-123.
  2. The EMT Analysis is based on PSCAD Models provided to PJM & DEV-ET on May 19th, the developers needs to confirm that these models are still valid and if updates to these models need to be made to represent changes made in the UDM please provide updated EMT models.
  3. As identified in the TC1 Phase 2 Reports and the June 2025 “EMT Generation Model Review” Report Nuisance Tripping is still occurring which can result in up to 1600 MW Tripping Off-Line.  This tripping is being initiated by the DC Protection Scheme of the WTGs, the developer needs to provide a solution to PJM & DEV-ET for this deficiency.   This solution will be evaluated in the NSA to determine if it resolves the nuisance tripping issue.  
  4. The developer needs to indicate if margin can be increased in the Over-Voltage Ride Through, Under Voltage Ride Through & Frequency Ride-Through to increase the margins from the PRC-024 & IEEE 2800 Requirements as identified in the TC1 Phase 2 Reports and the June 2025 “EMT Generation Model Review” Report.
  5. Preliminary Study Results indicate that the CVOW Project will result in a Pst Value greater than 1.  This will adversely impact Dominion’s Customers the proposed solution to this flicker issue will be to install a 300 MVAR STATCOM at Fentress Substation on the 230 kV Bus.   The developer can provide updated Ramp Rates  as part of the NSA to determine if mitigation is still required.

Reactive Power Analysis

The reactive power capability of AF1-125 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-065Earleys 230kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA1-145Four Rivers 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-088Boykins-Handsome 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB1-173Brink-Trego 115kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-100Clubhouse-Lakeview 230kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-065Harmony Village-Shackleford 115kVUnder Construction
AC1-086Thelma 230kVSuspended
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-112Old Church 34.5kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-216Hopewell-Surry 230kVIn Service
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-084Dawson-South Justice 115kVPartially in Service - Under Construction
AC2-100Halifax-Person 230kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVPartially in Service - Under Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-103Holland-Union Camp 115 kVSuspended
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-149Disputanta-Poe 115 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-247Myrtle-Windsor 115 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-346Ahoskie 34.5 kVIn Service
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-028Endless Caverns 115 kVUnder Construction
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-299Fields 34.5 kVActive
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-153Heritage 500 kVActive
AG1-210Northern Neck 34.5 kVWithdrawn
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-536Garner-Northern Neck 115 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
V4-068Murphy's 34.5kVIn Service
W1-029Winfall 230kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z1-068Birdneck 34.5kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-088Tarboro-Everetts 230kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 312.A.1.b and as outlined in PJM Manual 14H, Section 13, in Phase III of the Cycle, PJM coordinates with the Affected System Operators to conduct any studies required to determine the impact of the New Service Request on any Affected System and will include the Affected System Study results in Phase III System Impact Study, if available from the Affected System Operator.

If your project required an Affected System Study, the results are shown below from the Affected System Operator.

For more details, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM will list any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AF1-125 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionn9139.0Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.Cost Allocated$66,566,940
Dominionn9191.0Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.Cost Allocated$60,854,858
Dominionn9112.0Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.Cost Allocated$23,146,929
Dominionn9647.0Install a 300 MVAR STATCOM at Fentress Substation.Cost Allocated$16,196,842
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$11,757,438
Dominionn9380.0Replace existing Ladysmith 230/500 kV transformer 1 with four (4) 480 MVA single phase transformers.Cost Allocated$11,433,686
Dominionn9207.0Replace 6ELMONT 230 kV to 8ELMONT 500 kV circuit 1 with larger transformer (3-480 MVA single phase transformer).Cost Allocated$11,099,228
Dominionn9153.0Wreck and rebuild 5.9 miles of 230 kV line 2128 between Fentress and Thrasher with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Fentress.Cost Allocated$10,623,269
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$10,514,642
Dominionn9379.0Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.Cost Allocated$8,333,502
Dominionn9378.0Replace existing 230/500 kV Carson transformer 2 with (4)-480 MVA single phase transformers.Cost Allocated$8,324,368
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$6,706,414
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$3,711,019
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$2,925,106
Dominionn9199.0Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.Cost Allocated$2,618,305
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$2,376,810
Dominionn6605Wreck and rebuild 0.99 miles of line 271 between Pocaty and Landstown with (2)-768 ACSS (20/7) “MAUMEE” conductor @ 250 degrees C. Replace the line lead at Landstown.Cost Allocated$2,100,719
Dominionn9264.0Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1.Cost Allocated$169,545
Dominionn9265.0Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).Cost Allocated$95,442
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Kraken substation into Yeat substationContingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0N/A
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0N/A
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0N/A
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0N/A
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0N/A
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0N/A
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0N/A
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0N/A
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0N/A
Dominionb3800.373Wreck and rebuild approximately 7.14 miles of 230kV line #256 from St. Johns to structure 256/108 to achieve a summer rating of 1573 MVA. Line switch 25666 at St. Johns to be upgraded to 4000A.Contingent$0N/A
Dominionb3800.374Reconductor approximately 5.30 miles of 230kV line #256 from Ladysmith CT to structure 256/107 to achieve a summer rating of 1573 MVA.Contingent$0N/A
Dominionb3692Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.Contingent$0N/A
Grand Total:$259,555,062

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n8492
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492
Title
Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.
Description
Wreck and rebuild one (1) overhead 500kV transmission line that will start at the existing Fentress 500 kV Substation and terminate at the existing Yadkin 500 kV Substation, located approximately 13.5 miles away.
Total Cost ($USD)
$80,172,278
Discounted Total Cost ($USD)
$20,969,183
Allocated Cost ($USD)
$6,908,288
Time Estimate
26 to 27 Months

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123833.0 MW33.5%$7,017,810
AF1-124836.0 MW33.6%$7,043,084
AF1-125820.0 MW32.9%$6,908,288
System Reinforcement: n8492
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492
Title
Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.
Description
Wreck and rebuild one (1) overhead 500kV transmission line that will start at the existing Fentress 500 kV Substation and terminate at the existing Yadkin 500 kV Substation, located approximately 13.5 miles away.
Total Cost ($USD)
$80,172,278
Allocated Cost ($USD)
$11,757,438
Time Estimate
26 to 27 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$11,942,551
AF1-12414.9488 %$11,984,808
AF1-12514.6652 %$11,757,438
AF1-2940.3084 %$247,283
AF2-04229.0898 %$23,321,957
AF2-1150.1881 %$150,784
AF2-1205.5338 %$4,436,535
AF2-2223.7926 %$3,040,619
AG1-0210.1505 %$120,627
AG1-1243.0179 %$2,419,500
AG1-1355.3024 %$4,251,075
AG1-2852.8388 %$2,275,893
AG1-5365.2677 %$4,223,208

System Reinforcement: n9647.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9647.0
Title
Install a 300 MVAR STATCOM at Fentress Substation.
Description
Install a 300 MVAR STATCOM at Fentress Substation.
Total Cost ($USD)
$49,163,341
Discounted Total Cost ($USD)
$49,163,341
Allocated Cost ($USD)
$16,196,842
Time Estimate
Mar 31 2029

Contributor

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123833.0 MW33.5%$16,453,621
AF1-124836.0 MW33.6%$16,512,878
AF1-125820.0 MW32.9%$16,196,842

System Reinforcement: n9259.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9259.0
Title
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Description
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Total Cost ($USD)
$25,304,902
Discounted Total Cost ($USD)
$6,618,536
Allocated Cost ($USD)
$2,180,474
Time Estimate
38 to 39 Months

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123833.0 MW33.5%$2,215,042
AF1-124836.0 MW33.6%$2,223,020
AF1-125820.0 MW32.9%$2,180,474
System Reinforcement: n9259.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9259.0
Title
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Description
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Total Cost ($USD)
$25,304,902
Allocated Cost ($USD)
$3,711,019
Time Estimate
38 to 39 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$3,769,446
AF1-12414.9488 %$3,782,784
AF1-12514.6652 %$3,711,019
AF1-2940.3084 %$78,050
AF2-04229.0898 %$7,361,146
AF2-1150.1881 %$47,592
AF2-1205.5338 %$1,400,310
AF2-2223.7926 %$959,715
AG1-0210.1505 %$38,074
AG1-1243.0179 %$763,670
AG1-1355.3024 %$1,341,774
AG1-2852.8388 %$718,344
AG1-5365.2677 %$1,332,978

System Reinforcement: n8492.1
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.1
Title
Two Breaker Additions at Fentress Substation.
Description
Install Two 5000 amp GIS Breakers at Fentress Substation to connect the new 500 kV line 5005.
Total Cost ($USD)
$19,945,879
Discounted Total Cost ($USD)
$5,216,875
Allocated Cost ($USD)
$1,718,697
Time Estimate
30 to 36 Months

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123833.0 MW33.5%$1,745,945
AF1-124836.0 MW33.6%$1,752,233
AF1-125820.0 MW32.9%$1,718,697
System Reinforcement: n8492.1
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.1
Title
Two Breaker Additions at Fentress Substation.
Description
Install Two 5000 amp GIS Breakers at Fentress Substation to connect the new 500 kV line 5005.
Total Cost ($USD)
$19,945,879
Allocated Cost ($USD)
$2,925,106
Time Estimate
30 to 36 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$2,971,160
AF1-12414.9488 %$2,981,673
AF1-12514.6652 %$2,925,106
AF1-2940.3084 %$61,521
AF2-04229.0898 %$5,802,217
AF2-1150.1881 %$37,513
AF2-1205.5338 %$1,103,755
AF2-2223.7926 %$756,469
AG1-0210.1505 %$30,011
AG1-1243.0179 %$601,942
AG1-1355.3024 %$1,057,615
AG1-2852.8388 %$566,214
AG1-5365.2677 %$1,050,682

System Reinforcement: n8492.2
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.2
Title
Expand Yadkin Substation to accommodate the new 500 kV line.
Description
Expansion of yadkins 500 kV switchyard to accommodate the new 500 kV line which includes addition of 5000 amp GIS breakers and relocation of the existing suffolk -yadkin 500 kV line#565
Total Cost ($USD)
$16,207,123
Discounted Total Cost ($USD)
$4,238,998
Allocated Cost ($USD)
$1,396,536
Time Estimate
15 to 16 Months

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123833.0 MW33.5%$1,418,676
AF1-124836.0 MW33.6%$1,423,786
AF1-125820.0 MW32.9%$1,396,536
System Reinforcement: n8492.2
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.2
Title
Expand Yadkin Substation to accommodate the new 500 kV line.
Description
Expansion of yadkins 500 kV switchyard to accommodate the new 500 kV line which includes addition of 5000 amp GIS breakers and relocation of the existing suffolk -yadkin 500 kV line#565
Total Cost ($USD)
$16,207,123
Allocated Cost ($USD)
$2,376,810
Time Estimate
15 to 16 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$2,414,231
AF1-12414.9488 %$2,422,773
AF1-12514.6652 %$2,376,810
AF1-2940.3084 %$49,989
AF2-04229.0898 %$4,714,620
AF2-1150.1881 %$30,482
AF2-1205.5338 %$896,862
AF2-2223.7926 %$614,672
AG1-0210.1505 %$24,385
AG1-1243.0179 %$489,111
AG1-1355.3024 %$859,371
AG1-2852.8388 %$460,080
AG1-5365.2677 %$853,737

System Reinforcement: n9139.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9139.0 / TC1-PH1-DOM-073
Title
Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.
Description
Wreck and rebuild 37.41 miles of 500kV transmission line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA. Remove wave traps.
Total Cost ($USD)
$245,455,768
Discounted Total Cost ($USD)
$245,455,768
Allocated Cost ($USD)
$66,566,940
Time Estimate
69 to 70 Months

Contributor

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
205.2 MW27.5%$67,622,418
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
205.9 MW27.6%$67,865,939
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
202.0 MW27.1%$66,566,940
AF2-042131.7 MW17.7%$43,400,471

System Reinforcement: n9191.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9191.0 / TC1-PH1-DOM-090
Title
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.
Description
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$256,706,175
Discounted Total Cost ($USD)
$256,706,175
Allocated Cost ($USD)
$60,854,858
Time Estimate
74 to 75 Months

Contributor

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
69.0 MW24.1%$61,806,471
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
69.2 MW24.2%$62,026,005
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
67.9 MW23.7%$60,854,858
AF2-04280.4 MW28.1%$72,018,840

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-040
Title
ELIM TC1: Wreck and rebuild 18.75 miles of Line 594 btwn Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) Dipper at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 18.75 miles of Line 594 between Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$128,018,212
Discounted Total Cost ($USD)
$33,483,361
Allocated Cost ($USD)
$7,727,852
Time Estimate
60 to 61 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
39.9 MW23.4%$7,848,603
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
40.1 MW23.5%$7,876,529
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
39.3 MW23.1%$7,727,852
AF2-04251.0 MW30.0%$10,030,376

System Reinforcement: n9112.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9112.0 / TC1-PH2-DOM-063
Title
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Description
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Total Cost ($USD)
$87,030,447
Discounted Total Cost ($USD)
$87,030,447
Allocated Cost ($USD)
$23,146,929
Time Estimate
46 to 47 Months

Contributor

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A797.0 MVA
(All)B797.0 MVA
(All)C1115.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
45.5 MW27.0%$23,513,865
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
45.7 MW27.1%$23,598,622
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
44.8 MW26.6%$23,146,929
AF2-04232.5 MW19.3%$16,771,032

System Reinforcement: n9247.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9247.0 / TC1-PH2-DOM-041
Title
ELIM TC1: Wreck and rebuild 14.02 miles of Line 573 btwn Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 14.02 miles of Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA
Total Cost ($USD)
$99,636,684
Discounted Total Cost ($USD)
$26,060,128
Allocated Cost ($USD)
$6,008,516
Time Estimate
48 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
40.9 MW23.4%$6,102,509
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
41.0 MW23.5%$6,124,291
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
40.3 MW23.1%$6,008,516
AF2-04252.4 MW30.0%$7,824,812

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-062
Title
ELIMINATED FOR TC1: Wreck and Rebuild 14.83 miles of 230 kV line 256 with (2) 768.2 ACSS/TW (20/7) ""Maumee"" conductor @ 250 degrees C.
Description
Wreck and Rebuild 14.83 miles of 230 kV line 256 with (2) 768.2 ACSS/TW (20/7) ""Maumee"" conductor @ 250 degrees C.
Total Cost ($USD)
$41,037,004
Discounted Total Cost ($USD)
$10,733,292
Allocated Cost ($USD)
$3,536,630
Time Estimate
46 to 47 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1174.0 MVA
(All)B1302.0 MVA
(All)C1360.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
20.7 MW33.5%$3,591,996
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
20.8 MW33.6%$3,604,666
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
20.4 MW33.0%$3,536,630

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / dom-369
Title
ELIM FOR TC1: Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C and replace line lead at Mt. Eagle.
Description
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C and replace line lead at Mt. Eagle.
Total Cost ($USD)
$36,802,018
Discounted Total Cost ($USD)
$9,625,624
Allocated Cost ($USD)
$3,171,449
Time Estimate
43 to 44 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A781.0 MVA
(All)B796.0 MVA
(All)C909.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
34.7 MW33.5%$3,221,524
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
34.9 MW33.6%$3,232,652
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
34.2 MW32.9%$3,171,449

System Reinforcement: n9380.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9380.0 / TC1-PH3-DOM-012
Title
Replace existing Ladysmith 230/500 kV transformer 1 with four (4) 480 MVA single phase transformers.
Description
Replace existing Ladysmith 230/500 kV transformer 1 with four (4) 480 MVA single phase transformers.
Total Cost ($USD)
$37,587,605
Discounted Total Cost ($USD)
$37,587,605
Allocated Cost ($USD)
$11,433,686
Time Estimate
Dec 31 2029

Contributor

FacilityContingency
6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
70.3 MW30.9%$11,614,950
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
70.5 MW31.0%$11,656,754
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
69.2 MW30.4%$11,433,686
AF2-120 AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
7.9 MW3.5%$1,304,375
AG1-536 AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
9.5 MW4.2%$1,577,841

System Reinforcement: n9207.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9207.0 / TC1-PH2-DOM-018
Title
Replace 6ELMONT 230 kV to 8ELMONT 500 kV circuit 1 with larger transformer (3-480 MVA single phase transformer).
Description
Replace 6ELMONT 230 KV to 8ELMONT 500 kV ckt 1 with Larger XFRM. (3-480 MVA Single Phase XFRM).
Total Cost ($USD)
$38,254,469
Discounted Total Cost ($USD)
$38,254,469
Allocated Cost ($USD)
$11,099,228
Time Estimate
59 to 60 Months

Contributor

FacilityContingency
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE2-15614.4 MW3.6%$1,375,093
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
118.1 MW29.5%$11,275,111
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
118.6 MW29.6%$11,315,765
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
116.3 MW29.0%$11,099,228
AF2-08111.2 MW2.8%$1,072,666
AF2-120 AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
10.0 MW2.5%$957,860
AG1-536 AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
12.1 MW3.0%$1,158,746

System Reinforcement: n9153.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9153.0 / TC1-PH1-DOM-043
Title
Wreck and rebuild 5.9 miles of 230 kV line 2128 between Fentress and Thrasher with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Fentress.
Description
Wreck and rebuild 5.9 miles of 230 kV line 2128 between Fentress and Thrasher with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Fentress.
Total Cost ($USD)
$33,297,247
Discounted Total Cost ($USD)
$33,297,247
Allocated Cost ($USD)
$10,623,269
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
6FENTRES-6THRASHER 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1174.0 MVA
(All)B1195.0 MVA
(All)C1360.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE2-15618.7 MW1.6%$532,288
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
378.9 MW32.4%$10,791,585
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
380.3 MW32.5%$10,830,603
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
373.0 MW31.9%$10,623,269
AF2-08118.2 MW1.6%$519,501

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-008
Title
ELIMINATED FOR TC1: Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Description
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Total Cost ($USD)
$29,539,973
Discounted Total Cost ($USD)
$7,726,225
Allocated Cost ($USD)
$2,545,635
Time Estimate
45 to 46 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
6CUNNING-6FORK UNION 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1046.0 MVA
(All)B1046.0 MVA
(All)C1203.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
34.7 MW33.5%$2,585,829
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
34.9 MW33.6%$2,594,761
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
34.2 MW32.9%$2,545,635

System Reinforcement: n9379.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9379.0 / TC1-PH3-DOM-011
Title
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.
Description
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase 500/230 kV transformers.
Total Cost ($USD)
$37,836,293
Discounted Total Cost ($USD)
$37,836,293
Allocated Cost ($USD)
$8,333,502
Time Estimate
Dec 31 2029

Contributor

FacilityContingency
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
19.1 MW22.4%$8,463,643
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
19.2 MW22.4%$8,493,744
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
18.8 MW22.0%$8,333,502
AF2-04228.3 MW33.2%$12,545,404

System Reinforcement: n9378.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9378.0 / TC1-PH3-DOM-010
Title
Replace existing 230/500 kV Carson transformer 2 with (4)-480 MVA single phase transformers.
Description
Replace Existing 230/500 kV Carson transformer 2 with (4)-480 MVA Single Phase transformers.
Total Cost ($USD)
$37,801,301
Discounted Total Cost ($USD)
$37,801,301
Allocated Cost ($USD)
$8,324,368
Time Estimate
Dec 31 2029

Contributor

FacilityContingency
6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer(Any)
Rating SetRating TypeRating Value
LLA2016.0 MVA
LLB2083.0 MVA
LLC2239.0 MVA
SUMA1707.0 MVA
SUMB1758.0 MVA
SUMC1873.0 MVA
WINA2196.0 MVA
WINB2228.0 MVA
WINC2308.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
56.2 MW22.4%$8,456,365
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
56.5 MW22.5%$8,486,733
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
55.4 MW22.0%$8,324,368
AF2-04259.5 MW23.7%$8,947,219
AF2-22212.2 MW4.8%$1,827,058
AG1-15311.7 MW4.7%$1,759,557

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / dom-490
Title
ELIMINATED FOR TC1: Upgrade a 3.78 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine Substations at structure 2080/73.
Description
Uograde 3.78 miles of transmission line 2028 between Mt. Eagle and Grape Vine with (2) 768.2 ACSS/TW (20/7) "MAUMEE". The segment runs from Mt Eagle to structure 2080/73.
Total Cost ($USD)
$13,360,242
Discounted Total Cost ($USD)
$3,494,392
Allocated Cost ($USD)
$1,151,331
Time Estimate
43 to 44 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A721.0 MVA
(All)B721.0 MVA
(All)C829.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
34.7 MW33.5%$1,169,510
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
34.9 MW33.6%$1,173,550
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
34.2 MW32.9%$1,151,331

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH3-DOM-006
Title
ELIM FOR TC1: Upgrade a 2.73 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine. This segment runs from Grape Vine substation to structure 2080/73.
Description
Rebuild a 2.73 mile segment of 230kV line 2028 between Mt. Eagle and Grape Vinew with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @250 degrees C.
Total Cost ($USD)
$8,415,380
Discounted Total Cost ($USD)
$2,201,056
Allocated Cost ($USD)
$725,203
Time Estimate
42 to 43 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1174.0 MVA
(All)B1302.0 MVA
(All)C1360.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
34.7 MW33.5%$736,654
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
34.9 MW33.6%$739,198
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
34.2 MW32.9%$725,203

System Reinforcement: n9199.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9199.0 / TC1-PH2-DOM-004
Title
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Description
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Total Cost ($USD)
$7,947,612
Discounted Total Cost ($USD)
$7,947,612
Allocated Cost ($USD)
$2,618,305
Time Estimate
42 to 43 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA956.0 MVA
LLB1011.0 MVA
LLC1091.0 MVA
SUMA782.0 MVA
SUMB870.0 MVA
SUMC910.0 MVA
WINA979.0 MVA
WINB1043.0 MVA
WINC1115.0 MVA
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA956.0 MVA
LLB1011.0 MVA
LLC1091.0 MVA
SUMA782.0 MVA
SUMB870.0 MVA
SUMC910.0 MVA
WINA979.0 MVA
WINB1043.0 MVA
WINC1115.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
67.7 MW33.5%$2,659,940
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
68.0 MW33.6%$2,669,367
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
66.7 MW32.9%$2,618,305

System Reinforcement: n9146.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9146.0 / TC1-PH1-DOM-004
Title
ELIMINATED FOR TC1: Wreck and rebuild 1.51 miles of 115 kV Line No. 5 between Bremo and Fork Union with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees Celsius. Replace line lead at Bremo.
Description
Wreck and rebuild 1.51 miles of 115 kV Line No. 5 between Bremo and Fork Union with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees Celsius. Replace line lead at Bremo.
Total Cost ($USD)
$7,535,533
Discounted Total Cost ($USD)
$1,970,930
Allocated Cost ($USD)
$649,436
Time Estimate
42 to 43 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
Rating SetRating TypeRating Value
LLA242.0 MVA
LLB258.0 MVA
LLC265.0 MVA
SUMA198.0 MVA
SUMB218.0 MVA
SUMC228.0 MVA
WINA250.0 MVA
WINB266.0 MVA
WINC273.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
7.0 MW33.5%$659,804
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
7.0 MW33.6%$661,690
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
6.9 MW33.0%$649,436

System Reinforcement: n6605
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6605 / dom-101
Title
Wreck and rebuild 0.99 miles of line 271 between Pocaty and Landstown with (2)-768 ACSS (20/7) “MAUMEE” conductor @ 250 degrees C. Replace the line lead at Landstown.
Description
Wreck and rebuild 0.99 miles of line 271 between Pocaty and Landstown with (2)-768 ACSS (20/7) “MAUMEE” conductor @ 250 degrees C. Replace the line lead at Landstown.
Total Cost ($USD)
$6,555,756
Discounted Total Cost ($USD)
$6,555,756
Allocated Cost ($USD)
$2,100,719
Time Estimate
Dec 31 2026

Contributor

FacilityContingency
6LANDSTN-6POCATY 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1174.0 MVA
(All)B1195.0 MVA
(All)C1360.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
129.1 MW32.6%$2,134,014
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
129.6 MW32.7%$2,141,702
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
127.1 MW32.0%$2,100,719
AF2-08110.8 MW2.7%$179,321

System Reinforcement: n6161
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6161 / dom-039
Title
ELIMINATED FOR TC1: Replace 500 kV circuit breaker H1T561 at Clifton with a higher rated device (Clifton - Ox).
Description
Replace 500 kV circuit breaker H1T561 at Clifton with a higher rated device (Clifton - Ox).
Total Cost ($USD)
$2,634,901
Discounted Total Cost ($USD)
$689,162
Allocated Cost ($USD)
$227,044
Time Estimate
Dec 31 2029

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
8CLIFTON-8OX 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2857.0 MVA
(All)B3117.0 MVA
(All)C3793.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
97.5 MW33.5%$230,644
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
97.8 MW33.6%$231,475
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
96.0 MW32.9%$227,044

System Reinforcement: n9264.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9264.0 / TC1-PH1-DOM-080
Title
Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1.
Description
Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1.
Total Cost ($USD)
$582,006
Discounted Total Cost ($USD)
$582,006
Allocated Cost ($USD)
$169,545
Time Estimate
12 to 13 Months

Contributor

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2650.0 MVA
(All)B2831.0 MVA
(All)C3663.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
249.6 MW29.6%$172,233
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
250.5 MW29.7%$172,853
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
245.7 MW29.1%$169,545
AF2-04297.7 MW11.6%$67,376

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-061
Title
ELIMINATED FOR TC1: Replace wave trap 256WT at Four River 230 kV station (Four River - St. John).
Description
Replace wave trap 256WT at Four River 230 kV station (Four River - St. John).
Total Cost ($USD)
$514,454
Discounted Total Cost ($USD)
$134,556
Allocated Cost ($USD)
$44,336
Time Estimate
14 to 15 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1174.0 MVA
(All)B1225.0 MVA
(All)C1360.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
20.7 MW33.5%$45,030
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
20.8 MW33.6%$45,189
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
20.4 MW33.0%$44,336

System Reinforcement: n9265.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9265.0 / TC1-PH2-DOM-064
Title
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Description
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Total Cost ($USD)
$396,021
Discounted Total Cost ($USD)
$396,021
Allocated Cost ($USD)
$95,442
Time Estimate
14 to 15 Months

Contributor

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A876.0 MVA
(All)B956.0 MVA
(All)C1163.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
15.4 MW24.5%$96,938
AF1-124 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
15.5 MW24.6%$97,278
AF1-125 CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
15.2 MW24.1%$95,442
AF2-04216.9 MW26.9%$106,363

System Reinforcement: b3800.373
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.373
Title
Wreck and rebuild approximately 7.14 miles of 230kV line #256 from St. Johns to structure 256/108 to achieve a summer rating of 1573 MVA. Line switch 25666 at St. Johns to be upgraded to 4000A.
Description
Wreck and rebuild approximately 7.14 miles of 230kV line #256 from St. Johns to structure 256/108 to achieve a summer rating of 1573 MVA. Line switch 25666 at St. Johns to be upgraded to 4000A.
Cost Information
Time Estimate
Jun 15 2027

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1809.0 MVA

System Reinforcement: b3800.374
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.374
Title
Reconductor approximately 5.30 miles of 230kV line #256 from Ladysmith CT to structure 256/107 to achieve a summer rating of 1573 MVA.
Description
Reconductor approximately 5.30 miles of 230kV line #256 from Ladysmith CT to structure 256/107 to achieve a summer rating of 1573 MVA. Terminal equipment at remote end substations will be upgraded to 4000A.
Cost Information
Time Estimate
Jun 15 2027

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6STJOHN-AE1-157 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1809.0 MVA

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029
Cost Alloc Type
Contingent

System Reinforcement: b3692
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3692
Title
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.
Description
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy with current 500 kV standards construction practices to achieve a summer rating of 4330 MVA. Projected ISD: 06/01/2026
Cost Information
Time Estimate
Jun 01 2026

Contingent

Note: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4330.0 MVA
(All)B4330.0 MVA
(All)C5011.0 MVA

System Reinforcement: b3800.312
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.312
Title
Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.
Description
Rebuild 500kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. New conductor to have a summer rating of 4357 MVA.
Cost Information
Time Estimate
Jun 30 2030

ContingentTopology Changing

Note 1: Although AF1-125 may not presently have cost responsibility for this upgrade, AF1-125 may need this upgrade in-service to be deliverable to the PJM system. If AF1-125 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8LOUDOUN-8MORRSVL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
System Reinforcement: b3800.312
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.312
Title
Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.
Description
Rebuild 500kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. New conductor to have a summer rating of 4357 MVA.
Cost Information
Time Estimate
Jun 30 2030
Cost Alloc Type
Contingent

System Reinforcement: n9630.0

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Allocated Cost ($USD)
$10,514,642
Time Estimate
Dec 31 2029
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$10,680,181
AF1-12414.9488 %$10,717,966
AF1-12514.6652 %$10,514,631
AF1-2940.3084 %$221,116
AF2-04229.0898 %$20,856,756
AF2-1150.1881 %$134,864
AF2-1205.5338 %$3,967,615
AF2-2223.7926 %$2,719,212
AG1-0210.1505 %$107,905
AG1-1243.0179 %$2,163,769
AG1-1355.3024 %$3,801,706
AG1-2852.8388 %$2,035,358
AG1-5365.2677 %$3,776,827

System Reinforcement: n9267.0

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9267.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9267.0 / TC1-PH2-DOM-067
Title
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.
Description
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner substations with single (1) 768.2 ACSS/TW “Maumee” at 250 degrees C. This new line will be on separate transmission towers from the existing Northern Neck and Moon Corner line 1059. Station expansion is required at Northern Neck and Moon Corner to accommodate the new line.
Total Cost ($USD)
$45,730,074
Allocated Cost ($USD)
$6,706,414
Time Estimate
45 to 46 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$6,811,998
AF1-12414.9488 %$6,836,097
AF1-12514.6652 %$6,706,407
AF1-2940.3084 %$141,032
AF2-04229.0898 %$13,302,787
AF2-1150.1881 %$86,018
AF2-1205.5338 %$2,530,611
AF2-2223.7926 %$1,734,359
AG1-0210.1505 %$68,824
AG1-1243.0179 %$1,380,088
AG1-1355.3024 %$2,424,791
AG1-2852.8388 %$1,298,185
AG1-5365.2677 %$2,408,923

System Reinforcement: b4000.325

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: s3047.2

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: s3047.2
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3047.2
Title
Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.
Description
Install (2) 1400 MVA 500-230 kV transformers and associated 500 kV and 230 kV equipment (breakers, switches, leads) at Vint Hill Substation to supply the area with a 500 kV source Cut and loop 500 kV line #535 Loudoun – Meadowbrook and #569 Loudoun - Morrisville as the 500 kV sources into the proposed 500 kV ring bus Vint Hill Substation will be expanded to the north of the existing site to accommodate the 500 kV ring required for the addition of the new transformers Existing terminations for 230 kV line #2174 Wheeler – Vint Hill, line #2101 Bristers – Vint Hill, and line #2163 Liberty – Vint Hill will be rearranged to terminate into the expanded Vint Hill Substation 230 kV line #2114 Remington CT – Rollins Ford will also be cut and looped into the expanded Vint Hill Substation due to spatial constraints along the existing right-of-way.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.313

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.313
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.313
Title
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Description
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.356

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.356
Title
Build a new 500 kV line from Vint Hill to Wishing Star.
Description
Build a new 500kV line from Vint Hill to Wishing Star. The line will be supported on single circuit monopoles. New conductor to have a summer rating of 4357 MVA. Line length is approximately 16.59 miles
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.357

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.357
Title
Build a new 500 kV line from Morrisville to Vint Hill.
Description
Build a new 500kV line from Morrisville to Vint Hill. New conductor to have a summer rating of 4357 MVA. Line length is approximately 19.71 miles.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.354

AF1-125 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.354
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.354
Title
Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.
Description
Install terminal equipment at Wishing Star substation to support a 5000A line to Vint Hill. Update relay settings for 500kV Lines #546 and #590.
Cost Information
Cost Alloc Type
Contingent

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AF1-125


AF1-125 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
StabilityDominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Topology820.0 MW32.9%Cost Allocated$6,908,288
StabilityDominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Topology820.0 MW32.9%Cost Allocated$2,180,474
StabilityDominionn8492.1Two Breaker Additions at Fentress Substation.Topology820.0 MW32.9%Cost Allocated$1,718,697
StabilityDominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Topology820.0 MW32.9%Cost Allocated$1,396,536
Load FlowDominion(Pending) / TC1-PH2-DOM-040ELIM TC1: Wreck and rebuild 18.75 miles of Line 594 btwn Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) Dipper at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)Eliminated39.3 MW23.1%Cost Allocated$7,727,852
Load FlowDominionn9247.0 / TC1-PH2-DOM-041ELIM TC1: Wreck and rebuild 14.02 miles of Line 573 btwn Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)Eliminated40.3 MW23.1%Cost Allocated$6,008,516
Load FlowDominion(Pending) / TC1-PH2-DOM-062ELIMINATED FOR TC1: Wreck and Rebuild 14.83 miles of 230 kV line 256 with (2) 768.2 ACSS/TW (20/7) ""Maumee"" conductor @ 250 degrees C.Eliminated20.4 MW33.0%Cost Allocated$3,536,630
Load FlowDominion(Pending) / dom-369ELIM FOR TC1: Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C and replace line lead at Mt. Eagle.Eliminated34.2 MW32.9%Cost Allocated$3,171,449
Load FlowDominion(Pending) / TC1-PH2-DOM-008ELIMINATED FOR TC1: Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.Eliminated34.2 MW32.9%Cost Allocated$2,545,635
Load FlowDominion(Pending) / dom-490ELIMINATED FOR TC1: Upgrade a 3.78 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine Substations at structure 2080/73.Eliminated34.2 MW32.9%Cost Allocated$1,151,331
Load FlowDominion(Pending) / TC1-PH3-DOM-006ELIM FOR TC1: Upgrade a 2.73 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine. This segment runs from Grape Vine substation to structure 2080/73.Eliminated34.2 MW32.9%Cost Allocated$725,203
Load FlowDominionn9146.0 / TC1-PH1-DOM-004ELIMINATED FOR TC1: Wreck and rebuild 1.51 miles of 115 kV Line No. 5 between Bremo and Fork Union with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees Celsius. Replace line lead at Bremo.Eliminated6.9 MW33.0%Cost Allocated$649,436
Load FlowDominionn6161 / dom-039ELIMINATED FOR TC1: Replace 500 kV circuit breaker H1T561 at Clifton with a higher rated device (Clifton - Ox).Eliminated96.0 MW32.9%Cost Allocated$227,044
Load FlowDominion(Pending) / TC1-PH2-DOM-061ELIMINATED FOR TC1: Replace wave trap 256WT at Four River 230 kV station (Four River - St. John).Eliminated20.4 MW33.0%Cost Allocated$44,336
Load FlowDominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.Topology-0.0%Contingent$0
Load FlowDominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.Topology-0.0%Contingent$0
Load FlowDominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.Topology-0.0%Contingent$0
Load FlowDominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.Topology-0.0%Contingent$0
Load FlowDominionb4000.348Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Topology-0.0%Contingent$0
Load FlowDominionb4000.346Cut-in 500kV line from Kraken substation into Yeat substationTopology-0.0%Contingent$0
Load FlowDominionb4000.345Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Topology-0.0%Contingent$0
Load FlowDominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Topology-0.0%Contingent$0
Load FlowDominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$37,991,427
AF1-125 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$11,757,438
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$10,514,642
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$6,706,414
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$3,711,019
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$2,925,106
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$2,376,810
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.Contingent$0
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.Contingent$0
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.Contingent$0
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.Contingent$0
Dominionb4000.348Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0
Dominionb4000.346Cut-in 500kV line from Kraken substation into Yeat substationContingent$0
Dominionb4000.345Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0
Region Topology Upgrade Total:$37,991,429

Attachments

AF1-125 One Line Diagram

AF1-125 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.