AF1-128 Final System Impact Study (Retool 1) Report

v1.00 released 2025-12-08 18:15

Chesterfield 230 kV

569.0 MW Capacity / 569.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia), and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the TC1 projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.
Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of TC1 projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed a Natural Gas generating facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Chesterfield County, Virginia. The installed facilities will have a total capability of 569.0 MW with 569.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AF1-128
Project Name:
Chesterfield 230 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
State:
Virginia
County:
Chesterfield
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
569.0
MWE:
569.0
MWC:
569.0
Fuel Type:
Natural Gas
Basecase Study Year:
2027

Capacity Interconnection Rights (CIR) Transfer Details

This project intends to claim and transfer CIRs from the following Deactivation capacity generation resources. PJM performed a reliability analysis of the impacts to the system capability for the proposed transfer of CIRs from the Deactivation generation resources.

Unit NameStatusCIR ClaimedPOI Transfer
Chesterfield 3Deactivated Generator100.0Yes
Chesterfield 4Deactivated Generator119.0Yes
Chesterfield 5Deactivated Generator350.0No

Physical Interconnection Facility Study

Received

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AF1-128 will interconnect on the Dominion transmission system via a direct connection at the existing 230 kV Chesterfield Power Station.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AF1-128 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AF1-128Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$853,497$853,497
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$2,182,499$2,182,499
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$3,035,996$3,035,996

* Contributes to calculation for Security. See Security Section of this report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF1-128

Security has been calculated for the AF1-128 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF1-128
Project(s): AF1-128
Final Agreement Security (A): $3,035,996
Portion of Costs Already Paid (B): $3,028,778
Revised Net Security (C): A − B = $7,218
Security on Hand with PJM (D): $671,776
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

The New Service Request Project will interconnect with the Dominion transmission system via a direct connect to the Chesterfield 230 kV Sub. The required work for the interconnection of the New Service Request Project to the Dominion Transmission System is detailed in the following tables.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n8282

Expansion of Existing Chesterfield Substation

$1,436,190$583,876$117,227$45,206$2,182,499$2,182,499
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Transmission Owner Interconnection Facilities, including one (1) 230 kV backbone structure and foundation outside the fence of the interconnection substation will be constructed to terminate the Project Developer’s generator lead line. There will also be a line conductor constructed from the backbone structure to the bus position in the switchyard of the interconnection substation.

$559,966$231,352$48,497$13,682$853,497$853,497

Based on the scope of work for the Interconnection Facilities, it is expected to take 21 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

It is estimated to take 21 months to complete this work upon execution of the Generator Interconnection Agreement (GIA).This estimated time to complete is dependent on major equipment lead times. These preliminary cost estimates are based on typical engineering costs. A more detailed engineering cost estimates are normally done when the Project Developer provides an exact site plan location for the generation substation during a future study phase.
 
Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.
 
Remote Terminal Work: During Phase 2 of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2027 load flow model and the results were verified by Dominion.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AF1-128 was evaluated as a 219.0 MW (569.0 MW Capacity) injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC104.31 %3637.0C3793.6950.14

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.31 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:3793.69
MW Contribution:50.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.75764705882352950.644
961942AG1-037 E
Adder
0.50470588235294120.429
963041AG1-153 C
Adder
7.662352941176476.513
963042AG1-153 E
Adder
11.4941176470588249.77
3145413WATKINS
Adder
1.09647058823529430.932
3145723EMPORIA
Adder
0.57058823529411760.485
918492AA1-063AE OP
Adder
5.82352941176470654.95
919692AA2-053 E OP
Adder
5.8800000000000014.998
920042AA2-088 E OP
Adder
16.1705882352941213.745
934521AD1-076 C
Adder
19.5552941176470616.622
934522AD1-076 E
Adder
9.9670588235294128.472
943172AE2-346 E
Adder
0.90941176470588240.773
944011AF1-069 C
Adder
18.13647058823529415.416
944012AF1-069 E
Adder
7.04588235294117655.989
960081AF2-299 C
Adder
2.12235294117647081.804
316141AB2-099 E
Adder
0.37882352941176470.322
900672V4-068 E
Adder
0.53882352941176470.458
923263AB1-132 E OP
Adder
8.3529411764705897.1
923573AB1-173 E OP
Adder
4.3988235294117643.739
940492AE2-034 E
Adder
5.057647058823534.299
941031AE2-094 C
Adder
55.5058823529411847.18
941032AE2-094 E
Adder
24.8621.131
3145393UNCAMP
Adder
9.815294117647068.343
916042Z1-036 E
50/50
48.46248.462
938771AE1-103 C
Adder
4.7799999999999994.063
938772AE1-103 E
Adder
6.6011764705882355.611
313526AB2-022 C
50/50
0.6650.665
3144216WINCHST
50/50
0.2410.241
3145256KINGFORK
50/50
1.7881.788
3145506HICKORY
50/50
3.9493.949
3150601CHESTF5
Adder
80.1388235294117768.118
3150921YORKTN3
50/50
222.183222.183
925865AC1-065 E
Adder
25.8294117647058821.955
926662AC1-147 E
50/50
2.3992.399
926755AC1-161 E
50/50
25.37725.377
927226AC1-216 E
Adder
11.3047058823529419.609
934392AD1-063 E
Adder
1.69764705882352951.443
935112AD1-144 E
50/50
1.661.66
936591AD2-074 C
Adder
8.3435294117647067.092
936592AD2-074 E
Adder
13.61411764705882311.572
942341AE2-247 C
Adder
2.40705882352941152.046
942342AE2-247 E
Adder
3.3247058823529412.826
943461AF1-017 C
Adder
2.17764705882352951.851
943462AF1-017 E
Adder
3.55294117647058853.02
943612AF1-032 E
50/50
1.6391.639
943741AF1-042 C
Adder
4.3658823529411773.711
943742AF1-042 E
Adder
7.1235294117647056.055
961951AG1-038 C
Adder
4.8258823529411774.102
961952AG1-038 E
Adder
6.66352941176470555.664
966661AG1-536 C
Adder
7.9129411764705886.726
966662AG1-536 E
Adder
10.6329411764705889.038
3150981CHESPKA
50/50
0.7870.787
3150991CHESPKB
50/50
1.3041.304
3151081ELIZAR1
50/50
5.7935.793
3151091ELIZAR2
50/50
5.6915.691
3151101ELIZAR3
50/50
5.8665.866
3151161SURRY 1
50/50
40.01440.014
3152331SURRY 2
50/50
52.5452.54
3156056W1-029WIND
50/50
1.351.35
3156116Z1-036WIND
50/50
1.1111.111
316076AC2-137 E
Adder
1.77294117647058821.507
316078AC2-138 E
Adder
1.30588235294117671.11
316157AD2-030 E
Adder
1.88588235294117661.603
913392Y1-086 E
50/50
3.893.89
916192Z1-068 E
50/50
3.4083.408
923832AB2-022 E
50/50
2.1962.196
923842AB2-024 E
Adder
2.84000000000000032.414
923852AB2-025 E
Adder
1.53294117647058831.303
939312AE1-162 E
50/50
2.4312.431
957492AF2-043 E
50/50
2.5222.522
957601AF2-054 C
Adder
3.36117647058823542.857
957602AF2-054 E
Adder
2.24117647058823531.905
962861AG1-135 C
Adder
8.9694117647058827.624
962862AG1-135 E
Adder
5.985.083
962962AG1-145 E
50/50
2.6032.603
963611AG1-210 C
Adder
0.93294117647058830.793
963612AG1-210 E
Adder
1.39882352941176481.189
964211AG1-282 C
Adder
2.87176470588235282.441
964212AG1-282 E
Adder
1.91529411764705881.628
901082W1-029 E
50/50
55.655.6
917122Z2-027 E
50/50
2.3642.364
925332AB2-190 E
Adder
11.1811764705882369.504
925522AC1-027 E
50/50
2.2062.206
957831AF2-077 C
50/50
0.570.57
957832AF2-077 E
50/50
2.4692.469
957871AF2-081 C
50/50
17.9717.97
957872AF2-081 E
50/50
7.7017.701
958161AF2-110 C
50/50
2.3482.348
958162AF2-110 E
50/50
3.7353.735
3138116ELKO L286
Adder
1.84941176470588251.572
3141813NORNECK
Adder
1.24235294117647071.056
926071AC1-086 C
Adder
28.7023529411764724.397
926072AC1-086 E
Adder
13.06352941176470511.104
933291AC2-141 C
50/50
59.4559.45
933292AC2-141 E
50/50
25.37725.377
939411AE1-173 C
50/50
144.69144.69
939412AE1-173 E
50/50
96.4696.46
934012AD1-025 E
Adder
14.63647058823529612.441
916191Z1-068 C
50/50
0.0790.079
933981AD1-022 C
Adder
13.8411.764
933982AD1-022 E
Adder
7.5341176470588246.404
962572AG1-106 E
Adder
1.62470588235294121.381
962571AG1-106 C
Adder
3.71294117647058863.156
3130536PAPERMILL
Adder
10.4988235294117648.924
3145946PLYMOUTH TP
Adder
0.51882352941176470.441
3146326AYDLETT TAP
50/50
2.4292.429
316036AC1-147 C
50/50
0.6650.665
316072AD1-144 C
50/50
0.4940.494
316159AE1-175 C
50/50
0.7040.704
316160AE1-175 E
50/50
2.1482.148
316169AC1-164 GEN
50/50
65.01265.012
316185AD1-033 C
50/50
2.2242.224
316236AE1-162 C
50/50
0.5940.594
316246AF1-032 C
50/50
0.5030.503
316294AC1-161 C
50/50
9.6819.681
316305AF2-043 C
50/50
0.6160.616
316316AC1-027 C
50/50
0.5710.571
316320Y1-086 C
50/50
0.3880.388
316321Z2-027 C
50/50
0.6380.638
316382AG1-145 C
50/50
0.6360.636
917332KELFORD E
Adder
2.42.04
924516AB2-100 E1
Adder
3.87764705882352923.296
924517AB2-100 E2
Adder
3.87764705882352923.296
926785AC1-164_E
50/50
29.20829.208
934065AD1-033 E
50/50
9.1079.107
937226AE2-253 E
50/50
10.53510.535
939612AE1-191 E
Adder
8.9247058823529427.586
939246AE1-155 E
Adder
12.80941176470588310.888
918512AA1-065 E OP
Adder
8.4494117647058827.182
316017AA1-139 ULT1
50/50
1.9391.939
316018AA1-139 ULT2
50/50
1.9391.939
919153AA1-139 E2
50/50
7.3487.348
919152AA1-139 E1
50/50
7.3487.348
920692AA2-178 E
Adder
6.7435294117647065.732
923994AB2-040_E
Adder
8.2482352941176477.011
924814AB2-134 E
Adder
18.51882352941176515.741
316084AB2-161 E
Adder
8.0411764705882356.835
925122AB2-169 E
Adder
8.6941176470588237.39
316088AB2-174 E
Adder
8.6929411764705897.389
316375AC2-012 C
50/50
2.4382.438
932046AC2-012 E
50/50
23.72823.728
316311AC2-079 C
Adder
9.3282352941176477.929
932596AC2-079 E
Adder
15.21999999999999912.937
934146AD1-041 E
Adder
5.5776470588235294.741
934576AD1-082 E
Adder
6.4070588235294125.446
316349AD2-085 C
Adder
5.5541176470588244.721
936666AD2-085 E
Adder
9.0611764705882357.702
316388AE2-253 GEN
50/50
3.5313.531
961611AG1-000B C
Adder
25.22588235294117721.442
941591AE2-156 C
50/50
32.45632.456
944581AF1-123 C
50/50
83.73183.731
944582AF1-123 E
50/50
191.735191.735
944591AF1-124 C
50/50
84.02984.029
944592AF1-124 E
50/50
192.429192.429
944601AF1-125 C
50/50
82.44182.441
944602AF1-125 E
50/50
188.725188.725
944631AF1-128 C
Adder
50.1435294117647142.622
958261AF2-120 C
Adder
9.1988235294117657.819
958262AF2-120 E
Adder
6.1329411764705885.213
3137643SOCKMAN
Adder
0.96588235294117640.821
934501AD1-074 C
Adder
53.8447058823529445.768
934502AD1-074 E
Adder
27.4094117647058823.298
934511AD1-075 C
Adder
13.46117647058823511.442
934512AD1-075 E
Adder
6.8529411764705895.825
935161AD1-151 C
Adder
22.94117647058823619.5
935162AD1-151 E
Adder
15.29411764705882413
938531AE1-072 C
50/50
31.50731.507
938532AE1-072 E
50/50
16.42416.424
939191AE1-149 C
Adder
14.42941176470588312.265
939192AE1-149 E
Adder
9.628.177
939602AE1-190 E
Adder
2.23058823529411751.896
940481AE2-033 C
Adder
21.4117647058823518.2
940482AE2-033 E
Adder
14.43529411764705912.27
940541AE2-040 C
Adder
3.79058823529411763.222
940551AE2-041 C
Adder
11.3211764705882359.623
940641AE2-051 C
50/50
26.37426.374
940642AE2-051 E
50/50
17.58317.583
941101AE2-104 C
50/50
5.7555.755
941102AE2-104 E
50/50
9.159.15
943471AF1-018 C
Adder
11.3211764705882359.623
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.41628.416
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.24623.246
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
111.34111.34
G-007PJM->LTFIMP_G-007
CMTX_NF
4.3044.304
NYPJM->LTFIMP_NY
CLTF
2.0382.038
LGEELTFEXP_LGEE->PJM
CLTF
1.1621.162
WECLTFEXP_WEC->PJM
CLTF
0.5990.599
CPLELTFEXP_CPLE->PJM
CLTF
13.75813.758
TVALTFEXP_TVA->PJM
CLTF
6.4816.481
MECLTFEXP_MEC->PJM
CLTF
3.853.85
LAGNLTFEXP_LAGN->PJM
CLTF
8.2678.267
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234
O66PJM->LTFIMP_O-066
CMTX_NF
27.4327.43
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.5566.556
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
314903 to 314908 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 567_SRT-A
OPAC117.72 %934.92B1100.6238.59
GD1DVP
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
OPAC119.65 %663.64B794.0549.91
GD1DVP
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
OPAC110.61 %663.64B734.0449.89
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC136.21 %2442.12B3326.445.64
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC115.81 %4070.2B4713.5967.28
GD1DVP
8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
OPAC113.6 %3220.44B3658.5648.57

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 567_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.72 %
Rating:934.92 MVA
Rating Type:B
MVA to Mitigate:1100.62
MW Contribution:38.59
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:124.05 %
Rating:934.92 MVA
Rating Type:B
MVA to Mitigate:1159.8
MW Contribution:39.13
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.250588235294117670.213
961942AG1-037 E
Adder
0.167058823529411760.142
3145413WATKINS
Adder
0.371764705882352940.316
918492AA1-063AE OP
Adder
1.9235294117647061.635
919692AA2-053 E OP
Adder
1.9247058823529411.636
920042AA2-088 E OP
Adder
5.4247058823529414.611
934521AD1-076 C
Adder
6.4588235294117655.49
934522AD1-076 E
Adder
3.2917647058823532.798
943172AE2-346 E
Adder
0.30.255
316141AB2-099 E
Adder
0.124705882352941180.106
900672V4-068 E
Adder
0.178823529411764710.152
923263AB1-132 E OP
Adder
2.76588235294117672.351
940492AE2-034 E
Adder
1.67529411764705881.424
3145393UNCAMP
Adder
3.34588235294117632.844
916042Z1-036 E
Adder
16.12117647058823513.703
938771AE1-103 C
Adder
1.63411764705882371.389
938772AE1-103 E
Adder
2.25764705882352961.919
3141843SHACKLE
50/50
0.6030.603
3143316POE
Adder
0.72470588235294120.616
3145256KINGFORK
Adder
0.64941176470588250.552
3145506HICKORY
Adder
1.3035294117647061.108
3150601CHESTF5
Adder
61.6852.428
3150651CHESTF6
Adder
10.5635294117647058.979
3150731STONECA
Adder
5.1505882352941184.378
3150831SPRUNCA
Adder
4.643.944
3150841SPRUNCB
Adder
4.643.944
3150921YORKTN3
Adder
101.5176470588235486.29
925865AC1-065 E
50/50
18.90818.908
926412AC1-112 E
Adder
0.95058823529411770.808
926472AC1-118 E
Adder
1.07411764705882360.913
926662AC1-147 E
Adder
0.80941176470588230.688
926755AC1-161 E
Adder
7.7070588235294126.551
927226AC1-216 E
Adder
5.5894117647058834.751
934392AD1-063 E
50/50
1.2811.281
935112AD1-144 E
Adder
0.60235294117647060.512
936582AD2-073 E
Adder
1.1482352941176470.976
936591AD2-074 C
50/50
6.2326.232
936592AD2-074 E
50/50
10.16810.168
942341AE2-247 C
Adder
0.88823529411764710.755
942342AE2-247 E
Adder
1.22588235294117661.042
943461AF1-017 C
Adder
0.80352941176470590.683
943462AF1-017 E
Adder
1.31058823529411781.114
943612AF1-032 E
Adder
0.5564705882352940.473
943741AF1-042 C
50/50
3.2613.261
943742AF1-042 E
50/50
5.3215.321
944491AF1-114 C
Adder
5.0717647058823534.311
944492AF1-114 E
Adder
7.0035294117647065.953
961951AG1-038 C
50/50
3.6043.604
961952AG1-038 E
50/50
4.9774.977
966661AG1-536 C
50/50
6.0266.026
966662AG1-536 E
50/50
8.0978.097
316075AC2-137 C
50/50
0.4510.451
316076AC2-137 E
50/50
1.5851.585
316078AC2-138 E
Adder
1.04235294117647070.886
316156AD2-030 C
50/50
0.4250.425
316157AD2-030 E
50/50
1.331.33
913392Y1-086 E
Adder
1.29176470588235311.098
916192Z1-068 E
Adder
1.13647058823529410.966
923832AB2-022 E
Adder
0.72941176470588230.62
923842AB2-024 E
50/50
2.2272.227
923852AB2-025 E
Adder
0.53647058823529410.456
930122AB1-027 E
Adder
1.1682352941176470.993
939312AE1-162 E
Adder
0.95764705882352940.814
946262AF1-291 E
Adder
0.81058823529411760.689
957492AF2-043 E
Adder
0.85647058823529410.728
957601AF2-054 C
50/50
2.372.37
957602AF2-054 E
50/50
1.581.58
962861AG1-135 C
50/50
6.7996.799
962862AG1-135 E
50/50
4.5334.533
962962AG1-145 E
50/50
1.5371.537
963611AG1-210 C
Adder
0.74470588235294120.633
963612AG1-210 E
Adder
1.11764705882352940.95
964211AG1-282 C
50/50
2.3232.323
964212AG1-282 E
50/50
1.5491.549
901082W1-029 E
Adder
18.5929411764705915.804
917122Z2-027 E
Adder
0.78588235294117660.668
925332AB2-190 E
Adder
5.91411764705882355.027
925522AC1-027 E
Adder
0.73647058823529410.626
942001AE2-212 C
Adder
1.18941176470588221.011
942002AE2-212 E
Adder
0.79294117647058830.674
957832AF2-077 E
Adder
1.39411764705882371.185
957871AF2-081 C
Adder
5.94117647058823555.05
957872AF2-081 E
Adder
2.5458823529411772.164
957971AF2-091 C
Adder
1.7247058823529411.466
957972AF2-091 E
Adder
2.38117647058823542.024
958161AF2-110 C
Adder
0.81411764705882350.692
958162AF2-110 E
Adder
1.29411764705882361.1
3138116ELKO L286
50/50
1.6531.653
3141813NORNECK
Adder
0.99176470588235290.843
926071AC1-086 C
Adder
9.502352941176478.077
926072AC1-086 E
Adder
4.3247058823529423.676
933291AC2-141 C
Adder
18.0552941176470615.347
933292AC2-141 E
Adder
7.7070588235294126.551
939411AE1-173 C
Adder
43.0494117647058836.592
939412AE1-173 E
Adder
28.724.395
934012AD1-025 E
Adder
7.2364705882352946.151
933981AD1-022 C
Adder
4.5705882352941173.885
933982AD1-022 E
Adder
2.48823529411764752.115
962572AG1-106 E
Adder
0.53764705882352950.457
962571AG1-106 C
Adder
1.22941176470588221.045
3130536PAPERMILL
50/50
8.178.17
3145946PLYMOUTH TP
Adder
0.171764705882352930.146
3146326AYDLETT TAP
Adder
0.80352941176470590.683
316059AD1-063 C
50/50
0.3140.314
316159AE1-175 C
50/50
0.4180.418
316160AE1-175 E
50/50
1.2681.268
316169AC1-164 GEN
50/50
59.62859.628
316240AF1-291 C
Adder
1.21647058823529421.034
316314AB2-024 C
50/50
0.3640.364
316382AG1-145 C
50/50
0.3770.377
917332KELFORD E
Adder
0.78588235294117660.668
924516AB2-100 E1
Adder
1.31411764705882361.117
924517AB2-100 E2
Adder
1.31411764705882361.117
926785AC1-164_E
50/50
26.78926.789
934065AD1-033 E
Adder
3.0082352941176472.557
937226AE2-253 E
Adder
3.48117647058823552.959
939611AE1-191 C
50/50
1.5481.548
939612AE1-191 E
50/50
6.4276.427
316201AC1-065 C
50/50
1.8491.849
316404AE1-155 C
50/50
2.3762.376
939246AE1-155 E
50/50
9.7559.755
918512AA1-065 E OP
Adder
2.78823529411764742.37
919153AA1-139 E2
Adder
2.4294117647058822.065
919152AA1-139 E1
Adder
2.4294117647058822.065
920692AA2-178 E
Adder
2.23411764705882381.899
924814AB2-134 E
Adder
9.155294117647067.782
316084AB2-161 E
Adder
3.2882352941176472.795
925122AB2-169 E
Adder
2.8305882352941182.406
932046AC2-012 E
Adder
8.0047058823529426.804
316311AC2-079 C
Adder
3.4117647058823532.9
932596AC2-079 E
Adder
5.5670588235294124.732
316280AD1-041 C
50/50
0.9810.981
934146AD1-041 E
50/50
4.0174.017
934576AD1-082 E
Adder
2.622.227
316349AD2-085 C
Adder
2.0482352941176471.741
936666AD2-085 E
Adder
3.34117647058823542.84
961611AG1-000B C
Adder
11.3023529411764719.607
941591AE2-156 C
Adder
10.929411764705889.29
944581AF1-123 C
Adder
27.16823529411764723.093
944582AF1-123 E
Adder
62.2117647058823652.88
944591AF1-124 C
Adder
27.26470588235294223.175
944592AF1-124 E
Adder
62.43647058823529553.071
944601AF1-125 C
Adder
26.7494117647058822.737
944602AF1-125 E
Adder
61.2352941176470652.05
944631AF1-128 C
Adder
38.5941176470588232.805
958261AF2-120 C
50/50
7.0057.005
958262AF2-120 E
50/50
4.674.67
934501AD1-074 C
Adder
17.7847058823529415.117
934502AD1-074 E
Adder
9.0529411764705887.695
934511AD1-075 C
Adder
4.4458823529411773.779
934512AD1-075 E
Adder
2.2635294117647061.924
935161AD1-151 C
Adder
11.755294117647069.992
935162AD1-151 E
Adder
7.837647058823536.662
938531AE1-072 C
Adder
10.4258823529411768.862
938532AE1-072 E
Adder
5.4352941176470594.62
939191AE1-149 C
Adder
6.3788235294117655.422
939192AE1-149 E
Adder
4.2529411764705883.615
939601AE1-190 C
50/50
0.3840.384
939602AE1-190 E
50/50
1.6071.607
940431AE2-027 C
Adder
8.0564705882352946.848
940432AE2-027 E
Adder
5.3717647058823534.566
940481AE2-033 C
Adder
7.4635294117647066.344
940482AE2-033 E
Adder
5.0317647058823534.277
940541AE2-040 C
Adder
1.32705882352941161.128
940551AE2-041 C
50/50
8.5438.543
940641AE2-051 C
Adder
7.5435294117647066.412
940642AE2-051 E
Adder
5.0282352941176474.274
941101AE2-104 C
Adder
1.99529411764705891.696
941102AE2-104 E
Adder
3.1717647058823532.696
943471AF1-018 C
50/50
8.5438.543
944641AF1-129 C
Adder
58.0164705882352949.314
957191AF2-013 C
Adder
8.1011764705882366.886
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.8251.825
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.0931.093
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.8973.897
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.11329.113
G-007PJM->LTFIMP_G-007
CMTX_NF
1.1231.123
NYPJM->LTFIMP_NY
CLTF
0.5590.559
LGEELTFEXP_LGEE->PJM
CLTF
0.0680.068
WECLTFEXP_WEC->PJM
CLTF
0.0320.032
CPLELTFEXP_CPLE->PJM
CLTF
3.8353.835
TVALTFEXP_TVA->PJM
CLTF
1.2591.259
MECLTFEXP_MEC->PJM
CLTF
0.4280.428
LAGNLTFEXP_LAGN->PJM
CLTF
1.6451.645
SIGELTFEXP_SIGE->PJM
CLTF
0.0210.021
O66PJM->LTFIMP_O-066
CMTX_NF
7.1797.179

Details for 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:119.65 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:794.05
MW Contribution:49.91
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:118.19 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:784.36
MW Contribution:49.41
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3145393UNCAMP
Adder
1.761.496
916042Z1-036 E
Adder
8.517647058823537.24
938771AE1-103 C
Adder
0.86470588235294120.735
938772AE1-103 E
Adder
1.19411764705882351.015
3145256KINGFORK
Adder
0.360.306
3145506HICKORY
Adder
0.70117647058823530.596
3150601CHESTF5
50/50
79.76279.762
3150611CHESTG7
50/50
4.8674.867
3150621CHESTS7
50/50
2.2342.234
3150631CHESTG8
50/50
4.7894.789
3150641CHESTS8
50/50
2.4652.465
3150731STONECA
50/50
4.6744.674
3150761HOPPOLC
50/50
1.0381.038
3150771HOPHCF1
50/50
1.6511.651
3150781HOPHCF2
50/50
1.6511.651
3150791HOPHCF3
50/50
1.6511.651
3150801HOPHCF4
50/50
2.5062.506
3150921YORKTN3
Adder
49.1152941176470641.748
925865AC1-065 E
Adder
7.5929411764705886.454
926472AC1-118 E
Adder
0.40352941176470590.343
926662AC1-147 E
Adder
0.44705882352941180.38
926755AC1-161 E
Adder
3.96117647058823553.367
927226AC1-216 E
50/50
4.3534.353
934392AD1-063 E
Adder
0.50823529411764710.432
935112AD1-144 E
Adder
0.33411764705882350.284
936582AD2-073 E
Adder
0.43647058823529410.371
936591AD2-074 C
Adder
2.4564705882352942.088
936592AD2-074 E
Adder
4.00705882352941253.406
942341AE2-247 C
Adder
0.49647058823529410.422
942342AE2-247 E
Adder
0.68588235294117650.583
943461AF1-017 C
Adder
0.44941176470588240.382
943462AF1-017 E
Adder
0.73294117647058820.623
943612AF1-032 E
Adder
0.30.255
943741AF1-042 C
Adder
1.28470588235294141.092
943742AF1-042 E
Adder
2.09647058823529431.782
961951AG1-038 C
Adder
1.42000000000000021.207
961952AG1-038 E
Adder
1.96117647058823531.667
966661AG1-536 C
Adder
2.35294117647058832
966662AG1-536 E
Adder
3.16117647058823532.687
316076AC2-137 E
Adder
0.52823529411764710.449
316078AC2-138 E
Adder
0.40352941176470590.343
316132AB2-190 C
50/50
2.5252.525
316157AD2-030 E
Adder
0.53882352941176470.458
913392Y1-086 E
Adder
0.6917647058823530.588
916192Z1-068 E
Adder
0.620.527
923832AB2-022 E
Adder
0.39058823529411770.332
923842AB2-024 E
Adder
0.87294117647058820.742
939312AE1-162 E
Adder
0.60.51
957492AF2-043 E
Adder
0.46117647058823530.392
957601AF2-054 C
Adder
0.96117647058823530.817
957602AF2-054 E
Adder
0.64117647058823530.545
962861AG1-135 C
Adder
2.66117647058823532.262
962862AG1-135 E
Adder
1.77411764705882361.508
962962AG1-145 E
Adder
0.65882352941176480.56
963611AG1-210 C
Adder
0.288235294117647030.245
963612AG1-210 E
Adder
0.43294117647058820.368
964211AG1-282 C
Adder
0.89529411764705890.761
964212AG1-282 E
Adder
0.59647058823529410.507
901082W1-029 E
Adder
9.9247058823529428.436
917122Z2-027 E
Adder
0.420.357
925332AB2-190 E
50/50
4.9124.912
925522AC1-027 E
Adder
0.402352941176470640.342
957832AF2-077 E
Adder
0.61529411764705890.523
957871AF2-081 C
Adder
3.1905882352941182.712
957872AF2-081 E
Adder
1.36705882352941171.162
958161AF2-110 C
Adder
0.44117647058823530.375
958162AF2-110 E
Adder
0.70235294117647060.597
3138116ELKO L286
Adder
0.55176470588235290.469
3141813NORNECK
Adder
0.38352941176470590.326
933291AC2-141 C
Adder
9.287.888
933292AC2-141 E
Adder
3.96117647058823553.367
934011AD1-025 C
50/50
1.4651.465
934012AD1-025 E
50/50
5.6355.635
3130536PAPERMILL
Adder
3.2082352941176472.727
3146326AYDLETT TAP
Adder
0.431764705882352940.367
316160AE1-175 E
Adder
0.54352941176470590.462
316169AC1-164 GEN
50/50
22.41822.418
316369AC1-216 C
50/50
0.9040.904
926785AC1-164_E
50/50
10.07210.072
934065AD1-033 E
Adder
1.62117647058823521.378
937226AE2-253 E
Adder
1.86941176470588231.589
939612AE1-191 E
Adder
2.5917647058823532.203
939246AE1-155 E
Adder
3.80823529411764743.237
919153AA1-139 E2
Adder
1.30470588235294121.109
919152AA1-139 E1
Adder
1.30470588235294121.109
316033AB2-134 GEN
50/50
1.1851.185
924814AB2-134 E
50/50
7.137.13
316084AB2-161 E
Adder
1.92235294117647061.634
932046AC2-012 E
Adder
4.42705882352941153.763
316311AC2-079 C
Adder
1.90117647058823551.616
932596AC2-079 E
Adder
3.10117647058823562.636
934146AD1-041 E
Adder
1.621.377
934576AD1-082 E
Adder
1.53176470588235311.302
316349AD2-085 C
Adder
1.14470588235294120.973
936666AD2-085 E
Adder
1.86823529411764721.588
961611AG1-000B C
Adder
7.877647058823536.696
941591AE2-156 C
Adder
6.0388235294117655.133
944581AF1-123 C
Adder
14.61529411764705912.423
944582AF1-123 E
Adder
33.4682352941176528.448
944591AF1-124 C
Adder
14.66705882352941312.467
944592AF1-124 E
Adder
33.5894117647058828.551
944601AF1-125 C
Adder
14.39058823529411812.232
944602AF1-125 E
Adder
32.9423529411764728.001
944631AF1-128 C
50/50
49.90849.908
958261AF2-120 C
Adder
2.73529411764705932.325
958262AF2-120 E
Adder
1.8235294117647061.55
935161AD1-151 C
50/50
9.4829.482
935162AD1-151 E
50/50
6.3216.321
938531AE1-072 C
Adder
5.5941176470588234.755
938532AE1-072 E
Adder
2.9164705882352942.479
939191AE1-149 C
Adder
3.84235294117647053.266
939192AE1-149 E
Adder
2.56235294117647072.178
939602AE1-190 E
Adder
0.64823529411764710.551
940431AE2-027 C
Adder
3.98470588235294133.387
940432AE2-027 E
Adder
2.65647058823529442.258
940551AE2-041 C
Adder
3.3882352941176472.88
941101AE2-104 C
Adder
1.08235294117647070.92
941102AE2-104 E
Adder
1.72117647058823551.463
943471AF1-018 C
Adder
3.3882352941176472.88
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.8090.809
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.4860.486
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.7321.732
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.85612.856
G-007PJM->LTFIMP_G-007
CMTX_NF
0.5680.568
NYPJM->LTFIMP_NY
CLTF
0.280.28
LGEELTFEXP_LGEE->PJM
CLTF
0.0310.031
WECLTFEXP_WEC->PJM
CLTF
0.0140.014
CPLELTFEXP_CPLE->PJM
CLTF
1.71.7
TVALTFEXP_TVA->PJM
CLTF
0.5590.559
MECLTFEXP_MEC->PJM
CLTF
0.1910.191
LAGNLTFEXP_LAGN->PJM
CLTF
0.7290.729
SIGELTFEXP_SIGE->PJM
CLTF
0.010.01
O66PJM->LTFIMP_O-066
CMTX_NF
3.6293.629

Details for 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:110.61 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:734.04
MW Contribution:49.89
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:110.43 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:732.86
MW Contribution:49.39
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3145393UNCAMP
Adder
1.75764705882352961.494
916042Z1-036 E
Adder
8.5047058823529427.229
938771AE1-103 C
Adder
0.86352941176470590.734
938772AE1-103 E
Adder
1.19294117647058821.014
3143096IRON208
50/50
1.1521.152
3145256KINGFORK
Adder
0.35882352941176470.305
3145506HICKORY
Adder
0.70.595
3150601CHESTF5
50/50
79.73479.734
3150611CHESTG7
50/50
4.8664.866
3150621CHESTS7
50/50
2.2332.233
3150631CHESTG8
50/50
4.7884.788
3150641CHESTS8
50/50
2.4642.464
3150731STONECA
Adder
4.6705882352941183.97
3150771HOPHCF1
50/50
1.651.65
3150781HOPHCF2
50/50
1.651.65
3150791HOPHCF3
50/50
1.651.65
3150801HOPHCF4
50/50
2.5042.504
3150921YORKTN3
Adder
49.06352941176470541.704
925865AC1-065 E
Adder
7.5847058823529416.447
926472AC1-118 E
Adder
0.402352941176470640.342
926662AC1-147 E
Adder
0.44705882352941180.38
926755AC1-161 E
Adder
3.9564705882352943.363
927226AC1-216 E
Adder
4.34941176470588253.697
934392AD1-063 E
Adder
0.50823529411764710.432
935112AD1-144 E
Adder
0.332941176470588240.283
936582AD2-073 E
Adder
0.43647058823529410.371
936591AD2-074 C
Adder
2.45411764705882352.086
936592AD2-074 E
Adder
4.0035294117647063.403
942341AE2-247 C
Adder
0.495294117647058830.421
942342AE2-247 E
Adder
0.68470588235294120.582
943461AF1-017 C
Adder
0.448235294117647070.381
943462AF1-017 E
Adder
0.7317647058823530.622
943612AF1-032 E
Adder
0.30.255
943741AF1-042 C
Adder
1.28352941176470581.091
943742AF1-042 E
Adder
2.09529411764705881.781
961951AG1-038 C
Adder
1.41882352941176461.206
961952AG1-038 E
Adder
1.961.666
966661AG1-536 C
Adder
2.35058823529411761.998
966662AG1-536 E
Adder
3.1588235294117652.685
316076AC2-137 E
Adder
0.52823529411764710.449
316078AC2-138 E
Adder
0.40352941176470590.343
316157AD2-030 E
Adder
0.53882352941176470.458
913392Y1-086 E
Adder
0.69058823529411760.587
916192Z1-068 E
Adder
0.61882352941176480.526
923832AB2-022 E
Adder
0.38941176470588240.331
923842AB2-024 E
Adder
0.8717647058823530.741
939312AE1-162 E
Adder
0.60.51
957492AF2-043 E
Adder
0.46117647058823530.392
957601AF2-054 C
Adder
0.960.816
957602AF2-054 E
Adder
0.640.544
962861AG1-135 C
Adder
2.65764705882352952.259
962862AG1-135 E
Adder
1.7717647058823531.506
962962AG1-145 E
Adder
0.65764705882352950.559
963611AG1-210 C
Adder
0.288235294117647030.245
963612AG1-210 E
Adder
0.431764705882352940.367
964211AG1-282 C
Adder
0.89411764705882360.76
964212AG1-282 E
Adder
0.59647058823529410.507
901082W1-029 E
Adder
9.9105882352941178.424
917122Z2-027 E
Adder
0.420.357
925332AB2-190 E
Adder
4.9082352941176474.172
925522AC1-027 E
Adder
0.401176470588235360.341
957832AF2-077 E
Adder
0.61529411764705890.523
957871AF2-081 C
Adder
3.18588235294117662.708
957872AF2-081 E
Adder
1.36588235294117651.161
958161AF2-110 C
Adder
0.44117647058823530.375
958162AF2-110 E
Adder
0.70117647058823530.596
3138116ELKO L286
Adder
0.55058823529411770.468
3141813NORNECK
Adder
0.38352941176470590.326
933291AC2-141 C
Adder
9.2670588235294127.877
933292AC2-141 E
Adder
3.9564705882352943.363
934012AD1-025 E
Adder
5.6305882352941174.786
3130536PAPERMILL
Adder
3.20588235294117662.725
3146326AYDLETT TAP
Adder
0.430588235294117660.366
316160AE1-175 E
Adder
0.54235294117647060.461
316169AC1-164 GEN
Adder
22.40117647058823619.041
926785AC1-164_E
Adder
10.0635294117647078.554
934065AD1-033 E
Adder
1.61882352941176461.376
937226AE2-253 E
Adder
1.86705882352941191.587
939612AE1-191 E
Adder
2.58941176470588232.201
939246AE1-155 E
Adder
3.8047058823529413.234
919153AA1-139 E2
Adder
1.30235294117647071.107
919152AA1-139 E1
Adder
1.30235294117647071.107
924814AB2-134 E
Adder
7.1247058823529416.056
316084AB2-161 E
Adder
1.921.632
932046AC2-012 E
Adder
4.4211764705882353.758
316311AC2-079 C
Adder
1.89882352941176481.614
932596AC2-079 E
Adder
3.09764705882352942.633
934146AD1-041 E
Adder
1.61882352941176461.376
934576AD1-082 E
Adder
1.52941176470588251.3
316349AD2-085 C
Adder
1.1435294117647060.972
936666AD2-085 E
Adder
1.86588235294117651.586
961611AG1-000B C
Adder
7.8705882352941186.69
941591AE2-156 C
Adder
6.0305882352941185.126
944581AF1-123 C
Adder
14.5952941176470612.406
944582AF1-123 E
Adder
33.4223529411764728.409
944591AF1-124 C
Adder
14.64823529411764712.451
944592AF1-124 E
Adder
33.5435294117647128.512
944601AF1-125 C
Adder
14.37058823529411812.215
944602AF1-125 E
Adder
32.8976470588235327.963
944631AF1-128 C
50/50
49.89149.891
958261AF2-120 C
Adder
2.7317647058823532.322
958262AF2-120 E
Adder
1.82117647058823541.548
935161AD1-151 C
Adder
9.475294117647068.054
935162AD1-151 E
Adder
6.3164705882352945.369
938531AE1-072 C
Adder
5.58588235294117654.748
938532AE1-072 E
Adder
2.91176470588235332.475
939191AE1-149 C
Adder
3.83764705882352963.262
939192AE1-149 E
Adder
2.55882352941176452.175
939602AE1-190 E
Adder
0.64705882352941180.55
940431AE2-027 C
Adder
3.9788235294117653.382
940432AE2-027 E
Adder
2.6529411764705882.255
940551AE2-041 C
Adder
3.3847058823529412.877
941101AE2-104 C
Adder
1.08117647058823540.919
941102AE2-104 E
Adder
1.71882352941176491.461
943471AF1-018 C
Adder
3.3847058823529412.877
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.8060.806
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.3540.354
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.6811.681
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.77712.777
G-007PJM->LTFIMP_G-007
CMTX_NF
0.5760.576
NYPJM->LTFIMP_NY
CLTF
0.2840.284
LGEELTFEXP_LGEE->PJM
CLTF
0.0270.027
WECLTFEXP_WEC->PJM
CLTF
0.0120.012
CPLELTFEXP_CPLE->PJM
CLTF
1.6931.693
TVALTFEXP_TVA->PJM
CLTF
0.5480.548
MECLTFEXP_MEC->PJM
CLTF
0.1790.179
LAGNLTFEXP_LAGN->PJM
CLTF
0.7160.716
SIGELTFEXP_SIGE->PJM
CLTF
0.0090.009
O66PJM->LTFIMP_O-066
CMTX_NF
3.6813.681

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:136.21 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3326.4
MW Contribution:45.64
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:145.97 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3564.84
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.71294117647058820.606
961942AG1-037 E
Adder
0.475294117647058870.404
963041AG1-153 C
Adder
7.1717647058823536.096
963042AG1-153 E
Adder
10.757647058823539.144
966621AG1-532 C
Adder
1.72705882352941181.468
966622AG1-532 E
Adder
1.1517647058823530.979
3145413WATKINS
Adder
1.03764705882352940.882
3145723EMPORIA
Adder
0.53411764705882360.454
918492AA1-063AE OP
Adder
5.464705882352944.645
918532AA1-067 E
Adder
0.94588235294117650.804
919692AA2-053 E OP
Adder
5.50588235294117644.68
920042AA2-088 E OP
Adder
15.25058823529411712.963
934521AD1-076 C
Adder
18.52705882352941215.748
934522AD1-076 E
Adder
9.4435294117647068.027
943172AE2-346 E
Adder
0.85647058823529410.728
944011AF1-069 C
Adder
17.03647058823529314.481
944012AF1-069 E
Adder
6.6188235294117655.626
960081AF2-299 C
Adder
2.3023529411764711.957
960082AF2-299 E
Adder
1.53529411764705871.305
316141AB2-099 E
Adder
0.35647058823529410.303
900672V4-068 E
Adder
0.50705882352941180.431
923263AB1-132 E OP
Adder
7.79647058823529456.627
923573AB1-173 E OP
Adder
4.1152941176470593.498
940492AE2-034 E
Adder
4.8058823529411764.085
941031AE2-094 C
Adder
52.14117647058823544.32
941032AE2-094 E
Adder
23.3529411764705919.85
946281AF1-292 C
Adder
1.90588235294117661.62
946282AF1-292 E
Adder
1.27058823529411781.08
3145393UNCAMP
Adder
9.2964705882352947.902
916042Z1-036 E
50/50
46.21946.219
938771AE1-103 C
Adder
4.5305882352941173.851
938772AE1-103 E
Adder
6.257647058823535.319
313526AB2-022 C
50/50
0.640.64
3144216WINCHST
50/50
0.2310.231
3145256KINGFORK
50/50
1.7041.704
3145506HICKORY
50/50
3.8083.808
3150601CHESTF5
Adder
72.936470588235361.996
3150921YORKTN3
50/50
212.818212.818
925865AC1-065 E
Adder
24.48470588235294420.812
926662AC1-147 E
50/50
2.2972.297
926755AC1-161 E
50/50
24.37824.378
927226AC1-216 E
Adder
10.5317647058823528.952
934392AD1-063 E
Adder
1.61529411764705881.373
935112AD1-144 E
50/50
1.5821.582
936591AD2-074 C
Adder
7.8788235294117656.697
936592AD2-074 E
Adder
12.85529411764705910.927
942341AE2-247 C
Adder
2.2741176470588241.933
942342AE2-247 E
Adder
3.142.669
943461AF1-017 C
Adder
2.05764705882352941.749
943462AF1-017 E
Adder
3.35647058823529452.853
943612AF1-032 E
50/50
1.5651.565
943741AF1-042 C
Adder
4.122352941176473.504
943742AF1-042 E
Adder
6.7258823529411765.717
961951AG1-038 C
Adder
4.5564705882352943.873
961952AG1-038 E
Adder
6.2929411764705885.349
966661AG1-536 C
Adder
7.4564705882352956.338
966662AG1-536 E
Adder
10.0188235294117658.516
3150981CHESPKA
50/50
0.7560.756
3150991CHESPKB
50/50
1.2531.253
3151081ELIZAR1
50/50
5.5655.565
3151091ELIZAR2
50/50
5.4685.468
3151101ELIZAR3
50/50
5.6365.636
3151161SURRY 1
50/50
37.92137.921
3152331SURRY 2
50/50
50.93450.934
3156056W1-029WIND
50/50
1.2961.296
3156116Z1-036WIND
50/50
1.0631.063
316076AC2-137 E
Adder
1.64117647058823551.395
316078AC2-138 E
Adder
1.26470588235294111.075
316157AD2-030 E
Adder
1.7917647058823531.523
913392Y1-086 E
50/50
3.7343.734
916192Z1-068 E
50/50
3.2743.274
923832AB2-022 E
50/50
2.1082.108
923842AB2-024 E
Adder
2.7035294117647062.298
923852AB2-025 E
Adder
1.42470588235294131.211
939312AE1-162 E
50/50
2.3092.309
957492AF2-043 E
50/50
2.4072.407
957601AF2-054 C
Adder
3.1929411764705882.714
957602AF2-054 E
Adder
2.12823529411764721.809
962861AG1-135 C
Adder
8.4564705882352957.188
962862AG1-135 E
Adder
5.63764705882352954.792
962962AG1-145 E
50/50
2.4882.488
963611AG1-210 C
Adder
0.90352941176470590.768
963612AG1-210 E
Adder
1.35529411764705881.152
964211AG1-282 C
Adder
2.76588235294117672.351
964212AG1-282 E
Adder
1.84352941176470591.567
901082W1-029 E
50/50
53.16253.162
917122Z2-027 E
50/50
2.2672.267
925332AB2-190 E
Adder
10.335294117647068.785
925522AC1-027 E
50/50
2.1192.119
957831AF2-077 C
50/50
0.5460.546
957832AF2-077 E
50/50
2.3562.356
957871AF2-081 C
50/50
17.30217.302
957872AF2-081 E
50/50
7.4157.415
958161AF2-110 C
50/50
2.2342.234
958162AF2-110 E
50/50
3.5543.554
3138116ELKO L286
Adder
1.71058823529411771.454
3141813NORNECK
Adder
1.20352941176470571.023
926071AC1-086 C
Adder
26.78823529411764822.77
926072AC1-086 E
Adder
12.19176470588235310.363
933291AC2-141 C
50/50
57.10857.108
933292AC2-141 E
50/50
24.37824.378
939411AE1-173 C
50/50
137.269137.269
939412AE1-173 E
50/50
91.51291.512
934012AD1-025 E
Adder
13.63529411764705811.59
916191Z1-068 C
50/50
0.0760.076
933981AD1-022 C
Adder
13.0952941176470611.131
933982AD1-022 E
Adder
7.1294117647058826.06
962572AG1-106 E
Adder
1.5164705882352941.289
962571AG1-106 C
Adder
3.4647058823529412.945
3130536PAPERMILL
Adder
9.9929411764705888.494
3145946PLYMOUTH TP
Adder
0.491764705882352940.418
3146326AYDLETT TAP
50/50
2.3362.336
316036AC1-147 C
50/50
0.6390.639
316072AD1-144 C
50/50
0.4730.473
316159AE1-175 C
50/50
0.6760.676
316160AE1-175 E
50/50
2.0532.053
316169AC1-164 GEN
50/50
61.5761.57
316185AD1-033 C
50/50
2.1522.152
316236AE1-162 C
50/50
0.5660.566
316246AF1-032 C
50/50
0.4820.482
316294AC1-161 C
50/50
9.3329.332
316305AF2-043 C
50/50
0.590.59
316316AC1-027 C
50/50
0.550.55
316320Y1-086 C
50/50
0.3740.374
316321Z2-027 C
50/50
0.6140.614
316382AG1-145 C
50/50
0.610.61
917332KELFORD E
Adder
2.25294117647058821.915
924516AB2-100 E1
Adder
3.61411764705882373.072
924517AB2-100 E2
Adder
3.61411764705882373.072
926206AC1-098 E
Adder
4.72941176470588154.02
926214AC1-099 E
Adder
1.56235294117647071.328
926785AC1-164_E
50/50
27.66227.662
934065AD1-033 E
50/50
8.788.78
937226AE2-253 E
50/50
10.1510.15
939612AE1-191 E
Adder
8.4670588235294127.197
939246AE1-155 E
Adder
12.06941176470588310.259
918512AA1-065 E OP
Adder
7.9635294117647066.769
316017AA1-139 ULT1
50/50
1.8731.873
316018AA1-139 ULT2
50/50
1.8731.873
919153AA1-139 E2
50/50
7.0757.075
919152AA1-139 E1
50/50
7.0757.075
920692AA2-178 E
Adder
6.4070588235294125.446
923994AB2-040_E
Adder
7.7152941176470586.558
924814AB2-134 E
Adder
17.2517647058823514.664
316084AB2-161 E
Adder
7.497647058823536.373
925122AB2-169 E
Adder
8.1847058823529426.957
316088AB2-174 E
Adder
8.1305882352941186.911
316375AC2-012 C
50/50
2.3432.343
932046AC2-012 E
50/50
22.72422.724
316311AC2-079 C
Adder
8.827.497
932596AC2-079 E
Adder
14.39058823529411812.232
934146AD1-041 E
Adder
5.2917647058823534.498
934576AD1-082 E
Adder
5.9741176470588245.078
316349AD2-085 C
Adder
5.2458823529411764.459
936666AD2-085 E
Adder
8.5588235294117647.275
316388AE2-253 GEN
50/50
3.4133.413
961611AG1-000B C
Adder
23.74470588235294220.183
941591AE2-156 C
50/50
31.07431.074
944581AF1-123 C
50/50
79.48679.486
944582AF1-123 E
50/50
182.015182.015
944591AF1-124 C
50/50
79.76979.769
944592AF1-124 E
50/50
182.674182.674
944601AF1-125 C
50/50
78.26278.262
944602AF1-125 E
50/50
179.158179.158
944631AF1-128 C
Adder
26.26705882352941422.327
958261AF2-120 C
Adder
8.6682352941176477.368
958262AF2-120 E
Adder
5.7788235294117654.912
3137643SOCKMAN
Adder
0.90352941176470590.768
932632AC2-084 E
Adder
4.183.553
934501AD1-074 C
Adder
51.01411764705882543.362
934502AD1-074 E
Adder
25.96941176470588522.074
934511AD1-075 C
Adder
12.75411764705882310.841
934512AD1-075 E
Adder
6.4917647058823525.518
935161AD1-151 C
Adder
21.28588235294117618.093
935162AD1-151 E
Adder
14.19058823529411712.062
938531AE1-072 C
50/50
30.31830.318
938532AE1-072 E
50/50
15.80515.805
939191AE1-149 C
Adder
13.30705882352941111.311
939192AE1-149 E
Adder
8.8705882352941187.54
939602AE1-190 E
Adder
2.1164705882352941.799
940481AE2-033 C
Adder
19.89882352941176816.914
940482AE2-033 E
Adder
13.4152941176470611.403
940541AE2-040 C
Adder
3.5223529411764712.994
940551AE2-041 C
Adder
10.7682352941176489.153
940641AE2-051 C
50/50
24.9624.96
940642AE2-051 E
50/50
16.6416.64
941101AE2-104 C
50/50
5.4755.475
941102AE2-104 E
50/50
8.7058.705
943471AF1-018 C
Adder
10.7682352941176489.153
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.8765.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.55415.554
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.85316.853
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69696.696
G-007PJM->LTFIMP_G-007
CMTX_NF
3.3653.365
NYPJM->LTFIMP_NY
CLTF
1.6271.627
LGEELTFEXP_LGEE->PJM
CLTF
0.6520.652
WECLTFEXP_WEC->PJM
CLTF
0.3380.338
CPLELTFEXP_CPLE->PJM
CLTF
12.33712.337
TVALTFEXP_TVA->PJM
CLTF
4.9324.932
MECLTFEXP_MEC->PJM
CLTF
2.4842.484
LAGNLTFEXP_LAGN->PJM
CLTF
6.3726.372
SIGELTFEXP_SIGE->PJM
CLTF
0.1430.143
O66PJM->LTFIMP_O-066
CMTX_NF
21.46821.468

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.81 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4713.59
MW Contribution:67.28
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:137.17 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5582.91
MW Contribution:71.32
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.76117647058823530.647
961942AG1-037 E
Adder
0.50705882352941180.431
963041AG1-153 C
Adder
7.67882352941176556.527
963042AG1-153 E
Adder
11.517647058823539.79
966621AG1-532 C
Adder
2.00705882352941161.706
966622AG1-532 E
Adder
1.33882352941176451.138
3145413WATKINS
Adder
1.08705882352941190.924
3145723EMPORIA
Adder
0.61764705882352940.525
918492AA1-063AE OP
Adder
6.0129411764705885.111
920042AA2-088 E OP
Adder
16.25647058823529513.818
934521AD1-076 C
Adder
19.0647058823529416.205
934522AD1-076 E
Adder
9.7164705882352948.259
943172AE2-346 E
Adder
0.91294117647058830.776
944011AF1-069 C
Adder
18.02352941176470615.32
944012AF1-069 E
Adder
7.0023529411764715.952
960081AF2-299 C
Adder
2.6764705882352942.275
960082AF2-299 E
Adder
1.78470588235294111.517
316141AB2-099 E
Adder
0.380.323
900672V4-068 E
Adder
0.54235294117647060.461
923573AB1-173 E OP
Adder
4.7082352941176474.002
940492AE2-034 E
Adder
4.8823529411764714.15
941031AE2-094 C
Adder
55.1635294117647146.889
941032AE2-094 E
Adder
24.70588235294117821
946281AF1-292 C
Adder
2.2152941176470591.883
946282AF1-292 E
Adder
1.47764705882352951.256
3145393UNCAMP
Adder
9.664705882352948.215
916042Z1-036 E
Adder
46.2035294117647139.273
938771AE1-103 C
Adder
4.6882352941176473.985
938772AE1-103 E
Adder
6.4741176470588245.503
3143316POE
Adder
2.15411764705882371.831
3144216WINCHST
50/50
0.2290.229
3145256KINGFORK
Adder
1.70470588235294131.449
3145506HICKORY
Adder
3.66705882352941173.117
3150601CHESTF5
50/50
107.532107.532
3150611CHESTG7
50/50
6.5626.562
3150621CHESTS7
50/50
3.0123.012
3150631CHESTG8
50/50
6.4576.457
3150641CHESTS8
50/50
3.3243.324
3150651CHESTF6
Adder
30.4035294117647125.843
3150681DARBY 2
50/50
4.2574.257
3150691DARBY 3
50/50
4.2724.272
3150701DARBY 4
50/50
4.2774.277
3150731STONECA
Adder
11.5258823529411789.797
3150831SPRUNCA
Adder
14.5823529411764712.395
3150841SPRUNCB
Adder
14.5823529411764712.395
3150921YORKTN3
50/50
208.205208.205
925865AC1-065 E
Adder
27.3976470588235323.288
926412AC1-112 E
50/50
1.9031.903
926662AC1-147 E
Adder
2.2364705882352941.901
926755AC1-161 E
50/50
22.27722.277
927226AC1-216 E
Adder
12.9976470588235311.048
934392AD1-063 E
Adder
1.77411764705882361.508
935112AD1-144 E
Adder
1.58235294117647051.345
936591AD2-074 C
Adder
8.5505882352941187.268
936592AD2-074 E
Adder
13.95176470588235211.859
942341AE2-247 C
Adder
2.4552941176470592.087
942342AE2-247 E
Adder
3.39176470588235322.883
943461AF1-017 C
Adder
2.2223529411764711.889
943462AF1-017 E
Adder
3.62470588235294143.081
943612AF1-032 E
Adder
1.54117647058823541.31
943741AF1-042 C
Adder
4.4741176470588243.803
943742AF1-042 E
Adder
7.3000000000000016.205
961951AG1-038 C
Adder
4.9458823529411764.204
961952AG1-038 E
Adder
6.8294117647058825.805
966661AG1-536 C
Adder
8.0929411764705876.879
966662AG1-536 E
Adder
10.8741176470588249.243
966871AG1-558 C
Adder
3.73647058823529443.176
966872AG1-558 E
Adder
1.88235294117647081.6
3152331SURRY 2
50/50
44.51344.513
316075AC2-137 C
50/50
0.6540.654
316076AC2-137 E
50/50
2.32.3
316078AC2-138 E
Adder
1.37294117647058831.167
316157AD2-030 E
Adder
1.94470588235294131.653
913392Y1-086 E
Adder
3.6470588235294123.1
916192Z1-068 E
Adder
3.16941176470588242.694
923832AB2-022 E
Adder
2.0588235294117651.75
923842AB2-024 E
Adder
2.99058823529411732.542
923852AB2-025 E
Adder
1.7117647058823531.455
930122AB1-027 E
50/50
2.342.34
938552AE1-074 E
Adder
1.90000000000000011.615
939312AE1-162 E
Adder
2.4211764705882352.058
946262AF1-291 E
Adder
2.34117647058823541.99
957492AF2-043 E
Adder
2.37058823529411772.015
957601AF2-054 C
Adder
3.4647058823529412.945
957602AF2-054 E
Adder
2.31058823529411761.964
962861AG1-135 C
Adder
9.177647058823537.801
962862AG1-135 E
Adder
6.1188235294117645.201
962962AG1-145 E
50/50
2.5352.535
963611AG1-210 C
Adder
0.980.833
963612AG1-210 E
Adder
1.47058823529411781.25
964211AG1-282 C
Adder
3.02000000000000052.567
964212AG1-282 E
Adder
2.01294117647058851.711
901082W1-029 E
Adder
52.4682352941176544.598
917122Z2-027 E
Adder
2.22117647058823531.888
925332AB2-190 E
Adder
13.54588235294117611.514
925522AC1-027 E
Adder
2.05294117647058851.745
942001AE2-212 C
Adder
3.4764705882352942.955
942002AE2-212 E
Adder
2.31764705882352961.97
957832AF2-077 E
Adder
2.41411764705882352.052
957871AF2-081 C
Adder
16.73529411764705814.225
957872AF2-081 E
Adder
7.1717647058823536.096
958161AF2-110 C
Adder
2.2623529411764711.923
958162AF2-110 E
Adder
3.5988235294117653.059
3138116ELKO L286
50/50
2.3992.399
3141813NORNECK
Adder
1.30588235294117671.11
926071AC1-086 C
Adder
8.492941176470597.219
933291AC2-141 C
50/50
52.18752.187
933292AC2-141 E
50/50
22.27722.277
939411AE1-173 C
Adder
137.65882352941176117.01
939412AE1-173 E
Adder
91.772941176470678.007
934012AD1-025 E
Adder
16.82705882352941314.303
927041AC1-191 C
Adder
15.00352941176470612.753
927042AC1-191 E
Adder
7.4741176470588236.353
933981AD1-022 C
Adder
13.55882352941176611.525
933982AD1-022 E
Adder
7.3811764705882366.274
3130536PAPERMILL
Adder
11.0400000000000019.384
3145946PLYMOUTH TP
Adder
0.50470588235294120.429
3146326AYDLETT TAP
Adder
2.26588235294117621.926
316004AC1-112 C
50/50
0.5560.556
316159AE1-175 C
50/50
0.6890.689
316160AE1-175 E
50/50
2.0922.092
316169AC1-164 GEN
50/50
71.02671.026
316233AE1-074 C
Adder
3.7705882352941183.205
316240AF1-291 C
Adder
3.5117647058823532.985
316294AC1-161 C
50/50
8.5288.528
316312AB1-027 C
50/50
0.8920.892
316382AG1-145 C
50/50
0.6220.622
917332KELFORD E
Adder
2.43058823529411772.066
924516AB2-100 E1
Adder
4.20352941176470553.573
924517AB2-100 E2
Adder
4.20352941176470553.573
926785AC1-164_E
50/50
31.9131.91
934065AD1-033 E
Adder
8.4505882352941187.183
937226AE2-253 E
Adder
9.88.33
939612AE1-191 E
Adder
9.3494117647058837.947
939246AE1-155 E
Adder
13.111.135
918512AA1-065 E OP
Adder
8.397647058823537.138
919153AA1-139 E2
Adder
6.8435294117647065.817
919152AA1-139 E1
Adder
6.8435294117647065.817
920692AA2-178 E
Adder
6.5094117647058835.533
923994AB2-040_E
Adder
8.8282352941176477.504
924814AB2-134 E
Adder
21.28941176470588218.096
316084AB2-161 E
Adder
9.0294117647058827.675
925122AB2-169 E
Adder
8.6200000000000017.327
316088AB2-174 E
Adder
9.3494117647058837.947
932046AC2-012 E
Adder
22.12352941176470718.805
316311AC2-079 C
Adder
9.4458823529411768.029
932596AC2-079 E
Adder
15.41176470588235313.1
934146AD1-041 E
Adder
5.8435294117647054.967
934576AD1-082 E
Adder
7.1941176470588246.115
316349AD2-085 C
Adder
5.6658823529411774.816
936666AD2-085 E
Adder
9.244705882352947.858
961611AG1-000B C
Adder
26.9129411764705922.876
941591AE2-156 C
Adder
30.2317647058823525.697
944581AF1-123 C
Adder
76.4247058823529464.961
944582AF1-123 E
Adder
175.0035294117647148.753
944591AF1-124 C
Adder
76.6964705882352965.192
944592AF1-124 E
Adder
175.63764705882355149.292
944601AF1-125 C
Adder
75.2470588235294163.96
944602AF1-125 E
Adder
172.25764705882355146.419
944631AF1-128 C
50/50
67.28467.284
958261AF2-120 C
Adder
9.4070588235294137.996
958262AF2-120 E
Adder
6.2717647058823545.331
934501AD1-074 C
Adder
52.4929411764705944.619
934502AD1-074 E
Adder
26.72117647058823722.713
934511AD1-075 C
Adder
13.12352941176470511.155
934512AD1-075 E
Adder
6.685.678
935161AD1-151 C
Adder
27.11411764705882623.047
935162AD1-151 E
Adder
18.0752941176470615.364
938531AE1-072 C
Adder
29.3776470588235324.971
938532AE1-072 E
Adder
15.31411764705882413.017
939191AE1-149 C
Adder
17.43176470588235514.817
939192AE1-149 E
Adder
11.6211764705882359.878
939602AE1-190 E
Adder
2.33764705882352961.987
940431AE2-027 C
Adder
21.05411764705882417.896
940432AE2-027 E
Adder
14.03647058823529311.931
940481AE2-033 C
Adder
23.8117647058823520.24
940482AE2-033 E
Adder
16.0529411764705913.645
940541AE2-040 C
Adder
4.2317647058823533.597
940551AE2-041 C
Adder
11.82823529411764710.054
940641AE2-051 C
Adder
25.38941176470588321.581
940642AE2-051 E
Adder
16.92588235294117614.387
941101AE2-104 C
Adder
5.5447058823529414.713
941102AE2-104 E
Adder
8.815294117647067.493
943471AF1-018 C
Adder
11.82823529411764710.054
944641AF1-129 C
Adder
166.98352941176472141.936
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.017.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.3345.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.55730.557
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.912122.912
G-007PJM->LTFIMP_G-007
CMTX_NF
6.8256.825
NYPJM->LTFIMP_NY
CLTF
3.1153.115
LGEELTFEXP_LGEE->PJM
CLTF
1.8191.819
WECLTFEXP_WEC->PJM
CLTF
0.9390.939
CPLELTFEXP_CPLE->PJM
CLTF
14.714.7
TVALTFEXP_TVA->PJM
CLTF
8.1358.135
MECLTFEXP_MEC->PJM
CLTF
5.5435.543
LAGNLTFEXP_LAGN->PJM
CLTF
10.28110.281
SIGELTFEXP_SIGE->PJM
CLTF
0.3490.349
O66PJM->LTFIMP_O-066
CMTX_NF
43.443.4

Details for 8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.6 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3658.56
MW Contribution:48.57
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.485882352941176430.413
961942AG1-037 E
Adder
0.32352941176470590.275
966621AG1-532 C
Adder
1.28235294117647071.09
966622AG1-532 E
Adder
0.85529411764705890.727
3145413WATKINS
Adder
0.69764705882352940.593
3145723EMPORIA
Adder
0.39411764705882360.335
918492AA1-063AE OP
Adder
3.83529411764705853.26
920042AA2-088 E OP
Adder
10.4070588235294138.846
934521AD1-076 C
Adder
12.16705882352941310.342
934522AD1-076 E
Adder
6.2011764705882355.271
943172AE2-346 E
Adder
0.58235294117647060.495
944011AF1-069 C
Adder
10.9635294117647079.319
944012AF1-069 E
Adder
4.2588235294117653.62
960081AF2-299 C
Adder
1.71058823529411771.454
960082AF2-299 E
Adder
1.140.969
316141AB2-099 E
Adder
0.242352941176470580.206
900672V4-068 E
Adder
0.34588235294117650.294
923573AB1-173 E OP
Adder
3.00235294117647072.552
940492AE2-034 E
Adder
3.11882352941176462.651
941031AE2-094 C
Adder
33.5552941176470628.522
941032AE2-094 E
Adder
15.02823529411764612.774
946281AF1-292 C
Adder
1.4152941176470591.203
946282AF1-292 E
Adder
0.9435294117647060.802
3145393UNCAMP
Adder
6.2117647058823535.28
916042Z1-036 E
Adder
29.55058823529411825.118
938771AE1-103 C
Adder
3.0152941176470592.563
938772AE1-103 E
Adder
4.16470588235294153.54
3142296MT RD221
50/50
0.1630.163
3142366NRTHEST
50/50
0.2360.236
3143316POE
Adder
1.46235294117647091.243
3145256KINGFORK
Adder
1.10588235294117650.94
3145506HICKORY
Adder
2.3435294117647061.992
3150391LDYSMT3
50/50
7.2317.231
3150401LDYSMT4
50/50
7.2447.244
3150411LDYSMT5
50/50
7.2677.267
3150601CHESTF5
Adder
77.6188235294117765.976
3150651CHESTF6
Adder
21.86235294117646818.583
3150691DARBY 3
50/50
3.2613.261
3150701DARBY 4
50/50
3.2653.265
3150731STONECA
Adder
8.157647058823536.934
3150831SPRUNCA
Adder
10.5929411764705879.004
3150841SPRUNCB
Adder
10.5929411764705879.004
3150921YORKTN3
Adder
139.0764705882353118.215
925865AC1-065 E
Adder
19.93176470588235516.942
926412AC1-112 E
50/50
1.481.48
926472AC1-118 E
Adder
1.221.037
926662AC1-147 E
Adder
1.43647058823529421.221
926755AC1-161 E
Adder
14.11411764705882511.997
927226AC1-216 E
Adder
8.9282352941176487.589
934392AD1-063 E
Adder
1.28823529411764711.095
934782AD1-105 E
Adder
6.1211764705882365.203
935112AD1-144 E
Adder
1.02705882352941180.873
936582AD2-073 E
Adder
1.24588235294117641.059
936591AD2-074 C
Adder
6.6105882352941175.619
936592AD2-074 E
Adder
10.7858823529411769.168
942341AE2-247 C
Adder
1.6082352941176471.367
942342AE2-247 E
Adder
2.22117647058823531.888
943461AF1-017 C
Adder
1.4552941176470591.237
943462AF1-017 E
Adder
2.37411764705882342.018
943612AF1-032 E
Adder
0.98941176470588230.841
943741AF1-042 C
Adder
3.4588235294117652.94
943742AF1-042 E
Adder
5.6435294117647064.797
944491AF1-114 C
Adder
6.6258823529411775.632
944492AF1-114 E
Adder
9.1505882352941177.778
958502AF2-144 E
Adder
1.0717647058823530.911
961951AG1-038 C
Adder
3.8235294117647063.25
961952AG1-038 E
Adder
5.2788235294117654.487
966661AG1-536 C
Adder
6.3847058823529415.427
966662AG1-536 E
Adder
8.587.293
966871AG1-558 C
50/50
3.1913.191
966872AG1-558 E
50/50
1.6071.607
966881AG1-559 C
50/50
3.5873.587
966882AG1-559 E
50/50
1.8071.807
316076AC2-137 E
Adder
1.6835294117647061.431
316078AC2-138 E
Adder
1.10352941176470590.938
316157AD2-030 E
Adder
1.4152941176470591.203
913392Y1-086 E
Adder
2.33294117647058831.983
916192Z1-068 E
Adder
2.0305882352941181.726
923832AB2-022 E
Adder
1.31764705882352961.12
923842AB2-024 E
Adder
2.16941176470588241.844
923852AB2-025 E
Adder
1.10705882352941170.941
923862AB2-026 E
Adder
1.09058823529411760.927
930122AB1-027 E
50/50
1.821.82
938552AE1-074 E
Adder
1.32352941176470581.125
938562AE1-075 E
Adder
0.92941176470588240.79
939312AE1-162 E
Adder
1.5964705882352941.357
946262AF1-291 E
Adder
1.67294117647058821.422
957492AF2-043 E
Adder
1.52235294117647071.294
957601AF2-054 C
Adder
2.5211764705882352.143
957602AF2-054 E
Adder
1.68117647058823551.429
962861AG1-135 C
Adder
7.2058823529411776.125
962862AG1-135 E
Adder
4.8047058823529414.084
962962AG1-145 E
Adder
1.73058823529411781.471
963611AG1-210 C
Adder
0.78823529411764710.67
963612AG1-210 E
Adder
1.18235294117647041.005
964211AG1-282 C
Adder
2.3988235294117652.039
964212AG1-282 E
Adder
1.59882352941176481.359
901082W1-029 E
Adder
33.6023529411764728.562
917122Z2-027 E
Adder
1.42117647058823531.208
925332AB2-190 E
Adder
9.4164705882352948.004
925522AC1-027 E
Adder
1.3152941176470591.118
942001AE2-212 C
Adder
2.4364705882352942.071
942002AE2-212 E
Adder
1.62470588235294121.381
957832AF2-077 E
Adder
1.67882352941176481.427
957871AF2-081 C
Adder
10.7011764705882359.096
957872AF2-081 E
Adder
4.58588235294117653.898
957971AF2-091 C
Adder
2.25294117647058821.915
957972AF2-091 E
Adder
3.1105882352941182.644
958161AF2-110 C
Adder
1.46000000000000021.241
958162AF2-110 E
Adder
2.3235294117647061.975
3138116ELKO L286
Adder
1.75647058823529421.493
3141813NORNECK
Adder
1.05058823529411760.893
926071AC1-086 C
Adder
1.16117647058823530.987
933291AC2-141 C
Adder
33.06352941176470528.104
933292AC2-141 E
Adder
14.11411764705882511.997
939411AE1-173 C
Adder
85.3176470588235272.52
939412AE1-173 E
Adder
56.8788235294117748.347
934012AD1-025 E
Adder
11.569.826
927041AC1-191 C
50/50
12.81112.811
927042AC1-191 E
50/50
6.3816.381
933981AD1-022 C
Adder
8.6517647058823537.354
933982AD1-022 E
Adder
4.7105882352941174.004
3130536PAPERMILL
Adder
8.0105882352941196.809
3145946PLYMOUTH TP
Adder
0.32235294117647060.274
3146326AYDLETT TAP
Adder
1.44941176470588241.232
316004AC1-112 C
50/50
0.4320.432
316160AE1-175 E
Adder
1.4270588235294121.213
316169AC1-164 GEN
Adder
50.7141176470588243.107
316233AE1-074 C
Adder
2.6270588235294122.233
316240AF1-291 C
Adder
2.5105882352941182.134
316312AB1-027 C
50/50
0.6940.694
924516AB2-100 E1
Adder
2.69764705882352952.293
924517AB2-100 E2
Adder
2.69764705882352952.293
926785AC1-164_E
Adder
22.7847058823529419.367
934065AD1-033 E
Adder
5.4035294117647064.593
937226AE2-253 E
Adder
6.2658823529411765.326
939612AE1-191 E
Adder
6.8023529411764715.782
3150371LDYSMT1
50/50
6.9556.955
3150381LDYSMT2
50/50
7.0467.046
315051AA1-145 CT1
50/50
7.0497.049
315052AA1-145 CT2
50/50
7.0467.046
939246AE1-155 E
Adder
10.3364705882352948.786
918512AA1-065 E OP
Adder
5.3564705882352944.553
919153AA1-139 E2
Adder
4.3764705882352953.72
919152AA1-139 E1
Adder
4.3764705882352953.72
920692AA2-178 E
Adder
4.1576470588235293.534
923994AB2-040_E
Adder
5.6294117647058834.785
924814AB2-134 E
Adder
14.62588235294117712.432
316084AB2-161 E
Adder
6.0470588235294125.14
925122AB2-169 E
Adder
5.48117647058823554.659
316088AB2-174 E
Adder
5.9647058823529415.07
932046AC2-012 E
Adder
14.21176470588235412.08
316311AC2-079 C
Adder
6.1752941176470585.249
932596AC2-079 E
Adder
10.0764705882352948.565
934146AD1-041 E
Adder
4.2517647058823533.614
934576AD1-082 E
Adder
4.8176470588235294.095
316349AD2-085 C
Adder
3.71176470588235263.155
936666AD2-085 E
Adder
6.0552941176470595.147
961611AG1-000B C
Adder
18.15411764705882215.431
941591AE2-156 C
Adder
19.41529411764705816.503
944581AF1-123 C
Adder
48.8541176470588341.526
944582AF1-123 E
Adder
111.8694117647058995.089
944591AF1-124 C
Adder
49.02705882352941641.673
944592AF1-124 E
Adder
112.2741176470588395.433
944601AF1-125 C
Adder
48.1011764705882440.886
944602AF1-125 E
Adder
110.112941176470693.596
944631AF1-128 C
Adder
48.5670588235294141.282
958261AF2-120 C
Adder
7.4223529411764716.309
958262AF2-120 E
Adder
4.9482352941176484.206
934501AD1-074 C
Adder
33.50117647058823428.476
934502AD1-074 E
Adder
17.05411764705882414.496
934511AD1-075 C
Adder
8.3752941176470597.119
934512AD1-075 E
Adder
4.2635294117647063.624
935161AD1-151 C
Adder
18.74470588235294215.933
935162AD1-151 E
Adder
12.49647058823529410.622
938531AE1-072 C
Adder
18.7870588235294115.969
938532AE1-072 E
Adder
9.7941176470588228.325
939191AE1-149 C
Adder
11.85294117647058710.075
939192AE1-149 E
Adder
7.9023529411764716.717
939261AE1-157 C
50/50
21.18921.189
939262AE1-157 E
50/50
11.49311.493
939602AE1-190 E
Adder
1.70117647058823531.446
940431AE2-027 C
Adder
14.94470588235294212.703
940432AE2-027 E
Adder
9.9623529411764718.468
940481AE2-033 C
Adder
15.38117647058823513.074
940482AE2-033 E
Adder
10.3694117647058828.814
940541AE2-040 C
Adder
2.73647058823529442.326
940551AE2-041 C
Adder
8.5917647058823537.303
940641AE2-051 C
Adder
15.55529411764705813.222
940642AE2-051 E
Adder
10.3694117647058828.814
941101AE2-104 C
Adder
3.57882352941176453.042
941102AE2-104 E
Adder
5.69058823529411754.837
943471AF1-018 C
Adder
8.5917647058823537.303
944641AF1-129 C
Adder
120.07411764705883102.063
3150431FOUR RIVERA
50/50
4.4254.425
3150441FOUR RIVERB
50/50
4.4254.425
3150451FOUR RIVERC
50/50
5.4065.406
3150461FOUR RIVERD
50/50
4.3614.361
3150471FOUR RIVERE
50/50
4.3614.361
3150481FOUR RIVERF
50/50
5.3255.325
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.3184.318
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.54824.548
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.76217.762
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
75.17775.177
G-007PJM->LTFIMP_G-007
CMTX_NF
5.2915.291
NYPJM->LTFIMP_NY
CLTF
2.4212.421
LGEELTFEXP_LGEE->PJM
CLTF
1.011.01
WECLTFEXP_WEC->PJM
CLTF
0.5150.515
CPLELTFEXP_CPLE->PJM
CLTF
9.069.06
TVALTFEXP_TVA->PJM
CLTF
4.8114.811
MECLTFEXP_MEC->PJM
CLTF
3.1253.125
LAGNLTFEXP_LAGN->PJM
CLTF
6.0826.082
SIGELTFEXP_SIGE->PJM
CLTF
0.1960.196
O66PJM->LTFIMP_O-066
CMTX_NF
33.64633.646
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
314214 to 314903 ckt 1
314286 to 314309 ckt 1
314309 to 314338 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314911 to 313483 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Base Case
OPAC104.11 %2442.12A2542.4641.73

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.11 %
Rating:2442.12 MVA
Rating Type:A
MVA to Mitigate:2542.46
MW Contribution:41.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.55529411764705880.472
961942AG1-037 E
Adder
0.370588235294117660.315
963041AG1-153 C
Adder
4.884.148
963042AG1-153 E
Adder
7.3188235294117656.221
966621AG1-532 C
Adder
1.27294117647058851.082
966622AG1-532 E
Adder
0.84823529411764710.721
3145413WATKINS
Adder
0.82235294117647050.699
3145723EMPORIA
Adder
0.39411764705882360.335
918492AA1-063AE OP
Adder
4.17764705882352953.551
918532AA1-067 E
Adder
0.72588235294117650.617
919692AA2-053 E OP
Adder
4.1705882352941183.545
920042AA2-088 E OP
Adder
11.93294117647058910.143
927146AC1-208 E
Adder
3.8470588235294123.27
934521AD1-076 C
Adder
14.67647058823529312.475
934522AD1-076 E
Adder
7.48117647058823556.359
943172AE2-346 E
Adder
0.66705882352941170.567
944011AF1-069 C
Adder
11.532941176470599.803
944012AF1-069 E
Adder
4.47999999999999953.808
960081AF2-299 C
Adder
1.69647058823529421.442
960082AF2-299 E
Adder
1.13058823529411770.961
316141AB2-099 E
Adder
0.27764705882352940.236
900672V4-068 E
Adder
0.395294117647058850.336
923263AB1-132 E OP
Adder
5.86235294117647054.983
923573AB1-173 E OP
Adder
3.06235294117647072.603
940492AE2-034 E
Adder
3.8317647058823533.257
941031AE2-094 C
Adder
35.2988235294117730.004
941032AE2-094 E
Adder
15.80941176470588313.438
946281AF1-292 C
Adder
1.40470588235294121.194
946282AF1-292 E
Adder
0.93647058823529420.796
957861AF2-080 C
Adder
7.47999999999999956.358
957862AF2-080 E
Adder
3.3152941176470592.818
3145393UNCAMP
Adder
7.4105882352941186.299
916042Z1-036 E
Adder
37.13529411764706431.565
938771AE1-103 C
Adder
3.62470588235294143.081
938772AE1-103 E
Adder
5.00588235294117644.255
3143316POE
Adder
1.19294117647058821.014
3144216WINCHST
50/50
0.20.2
3145256KINGFORK
50/50
1.4051.405
3145506HICKORY
50/50
3.0893.089
3150601CHESTF5
Adder
66.756.695
3150731STONECA
Adder
6.8694117647058835.839
3150921YORKTN3
50/50
185.501185.501
925865AC1-065 E
Adder
22.29058823529411618.947
926472AC1-118 E
Adder
1.13411764705882350.964
926662AC1-147 E
50/50
1.8821.882
926755AC1-161 E
50/50
20.21420.214
927226AC1-216 E
Adder
8.9599999999999997.616
934392AD1-063 E
50/50
1.4751.475
935112AD1-144 E
50/50
1.3041.304
936582AD2-073 E
Adder
1.23176470588235291.047
936591AD2-074 C
Adder
7.2670588235294116.177
936592AD2-074 E
Adder
11.85764705882353110.079
942341AE2-247 C
Adder
1.84117647058823521.565
942342AE2-247 E
Adder
2.54235294117647072.161
943461AF1-017 C
Adder
1.66588235294117641.416
943462AF1-017 E
Adder
2.71882352941176462.311
943612AF1-032 E
Adder
1.2764705882352941.085
943741AF1-042 C
Adder
3.8023529411764713.232
943742AF1-042 E
Adder
6.20470588235294155.274
961951AG1-038 C
Adder
4.20352941176470553.573
961952AG1-038 E
Adder
5.8035294117647064.933
966661AG1-536 C
Adder
6.91529411764705955.878
966662AG1-536 E
Adder
9.2917647058823527.898
3150981CHESPKA
50/50
0.6170.617
3150991CHESPKB
50/50
1.0231.023
3151081ELIZAR1
50/50
4.5444.544
3151091ELIZAR2
50/50
4.4644.464
3151101ELIZAR3
50/50
4.6014.601
3152331SURRY 2
50/50
43.89143.891
316076AC2-137 E
Adder
1.53647058823529431.306
316078AC2-138 E
Adder
1.1482352941176470.976
316157AD2-030 E
Adder
1.6270588235294121.383
913392Y1-086 E
Adder
3.0235294117647062.57
916192Z1-068 E
50/50
2.672.67
923832AB2-022 E
Adder
1.7070588235294121.451
923842AB2-024 E
50/50
2.4762.476
923852AB2-025 E
Adder
1.040.884
939312AE1-162 E
Adder
1.9235294117647061.635
957492AF2-043 E
Adder
1.9635294117647061.669
957601AF2-054 C
Adder
2.92.465
957602AF2-054 E
Adder
1.93294117647058841.643
962861AG1-135 C
Adder
7.8329411764705896.658
962862AG1-135 E
Adder
5.2211764705882354.438
962962AG1-145 E
50/50
2.2212.221
963611AG1-210 C
Adder
0.820.697
963612AG1-210 E
Adder
1.23058823529411781.046
964211AG1-282 C
Adder
2.5270588235294122.148
964212AG1-282 E
Adder
1.6847058823529411.432
901082W1-029 E
Adder
43.0176470588235336.565
917122Z2-027 E
Adder
1.83411764705882341.559
925332AB2-190 E
Adder
8.8411764705882367.515
925522AC1-027 E
50/50
1.7291.729
957831AF2-077 C
50/50
0.4830.483
957832AF2-077 E
50/50
2.0912.091
957871AF2-081 C
50/50
14.02714.027
957872AF2-081 E
50/50
6.0126.012
958161AF2-110 C
Adder
1.81529411764705871.543
958162AF2-110 E
Adder
2.8870588235294122.454
3138116ELKO L286
Adder
1.60117647058823541.361
3141813NORNECK
Adder
1.09294117647058830.929
926071AC1-086 C
Adder
20.14470588235294517.123
926072AC1-086 E
Adder
9.1682352941176477.793
927021AC1-189 C
Adder
8.235294117647067
927022AC1-189 E
Adder
4.1023529411764713.487
933291AC2-141 C
50/50
47.35447.354
933292AC2-141 E
50/50
20.21420.214
939411AE1-173 C
Adder
101.4858823529411986.263
939412AE1-173 E
Adder
67.656470588235357.508
934012AD1-025 E
Adder
11.69.86
916191Z1-068 C
50/50
0.0620.062
933981AD1-022 C
Adder
10.3435294117647068.792
933982AD1-022 E
Adder
5.6317647058823534.787
962572AG1-106 E
Adder
1.140.969
962571AG1-106 C
Adder
2.60588235294117652.215
3130536PAPERMILL
50/50
9.1469.146
3145946PLYMOUTH TP
Adder
0.38941176470588240.331
3146326AYDLETT TAP
50/50
1.8931.893
316036AC1-147 C
50/50
0.5220.522
316059AD1-063 C
50/50
0.360.36
316072AD1-144 C
50/50
0.3890.389
316159AE1-175 C
50/50
0.6010.601
316160AE1-175 E
50/50
1.8321.832
316169AC1-164 GEN
50/50
57.50657.506
316185AD1-033 C
50/50
1.7411.741
316274AC1-208 C
Adder
8.6647058823529427.365
316294AC1-161 C
50/50
7.7117.711
316314AB2-024 C
50/50
0.4030.403
316316AC1-027 C
50/50
0.4470.447
316382AG1-145 C
50/50
0.5420.542
917332KELFORD E
Adder
1.74000000000000021.479
924516AB2-100 E1
Adder
2.6788235294117652.277
924517AB2-100 E2
Adder
2.6788235294117652.277
926206AC1-098 E
Adder
3.5952941176470593.056
926214AC1-099 E
Adder
1.18705882352941171.009
926785AC1-164_E
50/50
25.83625.836
934065AD1-033 E
50/50
7.137.13
937226AE2-253 E
50/50
8.238.23
939612AE1-191 E
Adder
7.76.545
939246AE1-155 E
Adder
11.1941176470588259.515
918512AA1-065 E OP
Adder
6.2364705882352955.301
316017AA1-139 ULT1
50/50
1.5131.513
316018AA1-139 ULT2
50/50
1.5131.513
919153AA1-139 E2
50/50
5.7365.736
919152AA1-139 E1
50/50
5.7365.736
920692AA2-178 E
Adder
5.1082352941176474.342
923994AB2-040_E
Adder
5.7423529411764714.881
924814AB2-134 E
Adder
14.67647058823529312.475
316084AB2-161 E
Adder
6.0352941176470595.13
925122AB2-169 E
Adder
6.3976470588235295.438
316088AB2-174 E
Adder
6.03294117647058855.128
316375AC2-012 C
50/50
1.9131.913
932046AC2-012 E
50/50
18.61318.613
316311AC2-079 C
Adder
7.1458823529411766.074
932596AC2-079 E
Adder
11.6588235294117669.91
934146AD1-041 E
Adder
4.8129411764705894.091
934576AD1-082 E
Adder
4.80941176470588254.088
316349AD2-085 C
Adder
4.2482352941176483.611
936666AD2-085 E
Adder
6.9317647058823545.892
316388AE2-253 GEN
50/50
2.7582.758
961611AG1-000B C
Adder
20.0529411764705917.045
941591AE2-156 C
50/50
25.46125.461
944581AF1-123 C
50/50
65.6165.61
944582AF1-123 E
50/50
150.24150.24
944591AF1-124 C
50/50
65.84465.844
944592AF1-124 E
50/50
150.785150.785
944601AF1-125 C
50/50
64.664.6
944602AF1-125 E
50/50
147.882147.882
944631AF1-128 C
Adder
41.73529411764706535.475
958261AF2-120 C
Adder
8.0388235294117656.833
958262AF2-120 E
Adder
5.3588235294117644.555
3137643SOCKMAN
Adder
0.6764705882352940.575
932632AC2-084 E
Adder
3.17764705882352952.701
934501AD1-074 C
Adder
40.41176470588235534.35
934502AD1-074 E
Adder
20.57176470588235517.486
934511AD1-075 C
Adder
10.102352941176478.587
934512AD1-075 E
Adder
5.1435294117647064.372
935161AD1-151 C
Adder
18.1615.436
935162AD1-151 E
Adder
12.10588235294117610.29
938531AE1-072 C
50/50
24.57324.573
938532AE1-072 E
50/50
12.8112.81
939191AE1-149 C
Adder
10.6576470588235289.059
939192AE1-149 E
Adder
7.1047058823529416.039
939602AE1-190 E
Adder
1.9247058823529411.636
940431AE2-027 C
Adder
10.9364705882352939.296
940432AE2-027 E
Adder
3.88235294117647063.3
940481AE2-033 C
Adder
14.5623529411764712.378
940482AE2-033 E
Adder
9.817647058823538.345
940541AE2-040 C
Adder
2.5717647058823532.186
940551AE2-041 C
Adder
9.8305882352941178.356
940641AE2-051 C
Adder
17.715.045
940642AE2-051 E
Adder
11.79999999999999910.03
941101AE2-104 C
Adder
4.4482352941176473.781
941102AE2-104 E
Adder
7.0717647058823536.011
943471AF1-018 C
Adder
9.8305882352941178.356
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.274.27
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.05913.059
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.06213.062
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
70.8670.86
G-007PJM->LTFIMP_G-007
CMTX_NF
2.7242.724
NYPJM->LTFIMP_NY
CLTF
1.3121.312
LGEELTFEXP_LGEE->PJM
CLTF
0.5530.553
WECLTFEXP_WEC->PJM
CLTF
0.2830.283
CPLELTFEXP_CPLE->PJM
CLTF
8.9638.963
TVALTFEXP_TVA->PJM
CLTF
3.7783.778
MECLTFEXP_MEC->PJM
CLTF
1.9921.992
LAGNLTFEXP_LAGN->PJM
CLTF
4.854.85
SIGELTFEXP_SIGE->PJM
CLTF
0.1170.117
O66PJM->LTFIMP_O-066
CMTX_NF
17.37617.376
314903 to 314908 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AF1-128 was evaluated as a 411.5 MW injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests (projects) in PJM Transition Cycle 1 Cluster 48 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 48 project.

 

Table 1: Transition Cycle 1 Cluster 48 Projects

Cluster

Project

Fuel Type

Transmission Owner

MFO (MW)

MWE (MW)

MWC (MW)

Point of Interconnection

48

AF1-128

Natural Gas

Dominion

569

569

569

Chesterfield 230 kV

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 48 project will meet the dynamics requirements of the NERC, Dominion Energy, and PJM reliability standards.

 

The load flow scenario for the analysis was based on the Regional Transmission Expansion Plan (RTEP) 2027 light load case, modified to include applicable projects. Projects in vicinity of Cluster 48 have been dispatched online at maximum power output with electrically close generators dispatched near 50% of the respective units minimum reactive power output.

 

Cluster 48 were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. 126 contingencies were studied, each with a 20 second simulation time period. The studied contingencies included:

  • Steady-state operation (30 seconds)
  • Three-phase faults with normal clearing time
  • Single-phase bus faults with normal clearing time
  • Single-phase faults with stuck breaker
  • Single-phase faults with delayed clearing at remote end
  • Three-phase faults with loss of multiple-circuit tower line.

 

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all of the fault contingencies tested on the RTEP 2027 light load case:

 

  • Cluster 48 was able to ride through the faults (except for faults where protective action trips a generator(s)),
  • The system with Cluster 48 included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes in Dominion area.
  • Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus)
  • For Dominion area, the final voltages are within the steady-state voltage ranges below per Dominion Energy’s transmission planning criteria.
    • P1 Category Contingencies:
      • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.01 to 1.096 p.u. for 500 kV facilities
    • P2, P4, P5, and P7 Category Contingencies:
      • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.00 to 1.096 p.u. for 500 kV facilities
  • No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

The transmission system being studied met the evaluation criteria. Below are some notable results.

 

AD2-074 was observed to trip on overvoltage (1.11 p.u. for 1 second and 1.2 p.u. for 0.001 second) for a number of P1 contingencies. Terminal voltage plots showed that the controller for this unit was freezing and not absorbing reactive power within the studied 20 second simulation. After reviewing the dynamic model, it was found that the REGCA model for this unit had reactive power ramp rate parameters Iqrmax and Iqrmin set to 0.02 and -0.02 p.u. respectively. These values are typically set much higher to allow the unit to respond to voltage variations quicker. Therefore, these values were increased to 100 and -100 p.u.. AD2-074 was then able to reduce the voltage post fault which prevented the unit from tripping on the 1.1 p.u. setpoint. The unit was still tripping for the 1.2 p.u. setpoint because of the low time delay (0.001 second). This time delay was increased slightly to 0.0167s. These changes enabled the unit to ride through all faults.

 

Surry units reactive response took over 20 seconds to settle for some contingencies. A longer 40 second test simulation was conducted which demonstrated that the unit settled shortly after 20 seconds shown in Figure 1 below. Slow settling is not a criteria violation and will not affect the results of the study.

 

AD1-151 reactive power was found to have some oscillations post fault that are positively damped with adequate damping ratio. This is not a criteria violation.

 

AB2-134 unit reactive power was found to not settle during the 20 second simulation. The following adjustments were made:

 

  • REPCA CON (J+1) Kp was adjusted to 1
  • REPCA CON (J+2) Ki was adjusted to 5

 

After these adjustments, the reactive power settlement improved but it did not settle within 20 seconds for some contingencies. This is not criteria violation. The developer should be requested to tune the dynamic model.

AB2-190 units reactive power was found to not settle during the 20 second simulation. The following adjustments were made:

  • PLNTBU1 CON (J+1) Kp was adjusted to 1
  • PLNTBU1 CON (J+2) Ki was adjusted to 5
  • PLNTBU1 CON (J+8) Kc was adjusted to 0.04

 

After these adjustments, the reactive power settlement improved but it did not settle within 20 seconds for some contingencies. This is not criteria violation. The developer should be requested to tune the dynamic model.

 

AG1-154 reactive power was observed to not settle during the 20 second simulation. The following adjustments were made:

 

  • REPCA CON (J+8) Kc was adjusted to 0.04

 

This adjustment improved the reactive power settlement for all contingencies.

 

No mitigation was required.

Reactive Power Analysis

The AF1-128 facility met the 0.95 leading and 0.9 lagging power factor requirements at the generators terminals.

 

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-065Earleys 230kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA1-145Four Rivers 230kVIn Service
AA2-088Boykins-Handsome 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-132Thelma 230kVIn Service
AB1-173Brink-Trego 115kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-040Brink 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-100Clubhouse-Lakeview 230kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-065Harmony Village-Shackleford 115kVUnder Construction
AC1-086Thelma 230kVSuspended
AC1-112Old Church 34.5kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-216Hopewell-Surry 230kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVPartially in Service - Under Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-103Holland-Union Camp 115 kVSuspended
AE1-149Disputanta-Poe 115 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-247Myrtle-Windsor 115 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-346Ahoskie 34.5 kVIn Service
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-028Endless Caverns 115 kVUnder Construction
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-299Fields 34.5 kVActive
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-153Heritage 500 kVActive
AG1-210Northern Neck 34.5 kVWithdrawn
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-536Garner-Northern Neck 115 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
V4-068Murphy's 34.5kVIn Service
W1-029Winfall 230kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z1-068Birdneck 34.5kVIn Service
Z2-027Pasquotank 34.5kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 312.A.1.b and as outlined in PJM Manual 14H, Section 13, in Phase III of the Cycle, PJM coordinates with the Affected System Operators to conduct any studies required to determine the impact of the New Service Request on any Affected System and will include the Affected System Study results in Phase III System Impact Study, if available from the Affected System Operator.

If your project required an Affected System Study, the results are shown below from the Affected System Operator.

For more details, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM will list any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AF1-128 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionb3692Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.Contingent$0N/A
Grand Total:$0

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b3692
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3692
Title
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.
Description
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy with current 500 kV standards construction practices to achieve a summer rating of 4330 MVA. Projected ISD: 06/01/2026
Cost Information
Time Estimate
Jun 01 2026

Contingent

Note: Although AF1-128 may not presently have cost responsibility for this upgrade, AF1-128 may need this upgrade in-service to be deliverable to the PJM system. If AF1-128 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4330.0 MVA
(All)B4330.0 MVA
(All)C5011.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AF1-128


AF1-128 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AF1-128 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AF1-128 One Line Diagram

AF1-128 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.