AF1-280 Final System Impact Study (Retool 2) Report

v2.00 released 2026-05-14 11:49

Nelson-Lee County

0.0 MW Capacity / 200.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Deriva Energy Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Commonwealth Edison Company.

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.

The AF1-280 Final System Impact Study (Retool 1) Report is available for download here.

Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed a Solar generating facility located in the Commonwealth Edison Company zone — Lee County, Illinois. The installed facilities will have a total capability of 200.0 MW with 0.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AF1-280
Project Name:
Nelson-Lee County
Project Developer Name:
Deriva Energy Solar, LLC
State:
Illinois
County:
Lee
Transmission Owner:
Commonwealth Edison Company
MFO:
200.0
MWE:
200.0
MWC:
0.0
Fuel Type:
Solar
Basecase Study Year:
2027

Physical Interconnection Facility Study

Received

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AF1-280 will interconnect with the ComEd transmission system via a newly constructed 345 kV breaker and a half substation, TSS 953 Renner Road, tapping the TSS 155 Nelson – TSS 937 Lee County 345kV line, L.15501, approximately 9.0 miles from TSS 155 Nelson and approximately 4.0 miles from TSS 937 Lee County.

 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AF1-280 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AF1-280Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$970,966$970,966
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$12,467,942$12,467,942
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$14,292,703$14,292,703
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0
AFS - Non-PJM Violations$640,007 **$0 **
Total$28,371,618$27,731,611

* Contributes to calculation for Security. See Security Requirement Section of this report for additional detail.

** This value reflects the results at the time of the report posting and it is subject to change. AFS – Non-PJM Violations are not subject to Security. For latest AFS – Non-PJM Violations, please refer to the latest Affected System Study Report for your project.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF1-280/AF2-182

Security has been calculated for the AF1-280/AF2-182 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF1-280/AF2-182
Project(s): AF1-280/AF2-182
Final Agreement Security (A): $62,609,467
Portion of Costs Already Paid (B): $0
Revised Net Security (C): A − B = $62,609,467
Security on Hand with PJM (D): $62,609,467
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

As shown in the one line diagram, this Interconnection Request is sharing the Point of Interconnection (POI) with one or more other Interconnection Requests. Should other requests withdraw from the Interconnection Queue, the cost allocation for Transmission Owner Interconnection Facilities, Stand Alone Network Upgrades, and applicable Network Upgrades identified in the study report will be updated for the remaining project(s). Refer to the one line for other Interconnection Requests at this POI.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

(No Transmission Owner Scope for this project.)

Developer Scope

Project Developer has elected the option Option to Build where they will assume responsibility for the design, procurement and construction of the Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades identified in this SIS report.

The Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n9342.0

Cut the L15501 transmission line to loop into the new TSS 953 Renner Road substation

$4,767,048$2,121,849$1,109,823$101,120$8,099,840$4,049,920 (See Note 1)
n9341.0

Perform Relaying Upgrades at TSS 155 Nelson substation

$475,413$89,296$110,682$4,256$679,647$339,824 (See Note 1)
n9340.0

Perform Relaying Upgrades at TSS 937 Lee County substation

$475,413$89,296$110,682$4,256$679,647$339,824 (See Note 1)
n9339.0

Build new fiber path (estimated ~9 miles) from TSS 953 Renner Road to TSS 155 Nelson substation existing fiber and new fiber path (estimated ~4 miles) from TSS 953 Renner Road to TSS 937 Lee County substation existing fiber

$7,401,345$4,606,284$1,723,117$219,519$13,950,265$6,975,132 (See Note 1)
n9338.0

Extend existing distribution power no more than 1 mile to tie in the auxilliary power for the new interconnection substation

$383,916$244,365$89,380$11,646$729,307$364,654 (See Note 1)
n9337.0

Fiber multiplexer installation at 6 remote substations: TSS 155 Nelson, TSS 937 Lee County, STA 6 Byron, TSS 144 Wayne, TSS 111 Electric Junction, TSS 113 Waterman

$605,101$48,873$140,874$2,329$797,177$398,588 (See Note 1)
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Oversight to construct a new 345 kV breaker and a half TSS 954 Renner Road Substation tapping the L15501 transmission line

$1,515,406$0$352,804$0$1,868,210$934,105 (See Note 1)
(Pending)

Oversight of construct Transmission Owner Interconnection Facilities from the Point of Change in Ownership to the TSS 953 Renner Road substation

$59,800$0$13,922$0$73,722$36,861 (See Note 1)

Based on the scope of work for the Interconnection Facilities, it is expected to take 60 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

Notes on Cost Estimate:

  1. These estimates are Order-of-Magnitude estimates of the costs that ComEd would bill to the Project Developer for this interconnection. These estimates are based on a one-line electrical diagram of the project and the information provided by the Project Developer.
  2. There were no site visits performed for these estimates. There may be costs related to specific site related issues that are not identified in these estimates. The site reviews will be performed during the Facilities Study or during detailed engineering.
  3. These estimates are not a guarantee of the maximum amount payable by the Project Developer and the actual costs of ComEd's work may differ significantly from these estimates. The Project Developer will be responsible for paying actual costs of ComEd's work in accordance with the PJM Open Access Transmission Tariff.
  4. The Project Developer is responsible for all engineering, procurement, testing and construction of all equipment on the Project Developer’s side of the Point of Change in Ownership.

5.    The Project Developer confirmed that all circuit breakers connected to the gen-tie line at the Generating Facility are protected by a single relay scheme with a common ground grid. Additional Project Developer Interconnection Facilities will be required in accordance with Comed's Applicable Technical Requirements and Standards, if the described protection scheme is modified.

These cost estimates do not include cost of acquiring right-of-way for the transmission line and purchasing any additional land, if needed, for the line terminations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. ComEd interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AF1-280 was evaluated as a 200.0 MW (0.0 MW Capacity) injection in the ComEd area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1CE
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
COMED_P4_006-45-BT3-8___SRT-A
BreakerAC115.39 %1837.0STE2119.7767.19
GD1CE
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
COMED_P4_006-45-BT3-4___SRT-A
BreakerAC114.8 %1837.0STE2108.8467.05

Details for AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.39 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2119.77
MW Contribution:67.19
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.95 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2129.98
MW Contribution:67.3
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
990901L-005 E
Adder
12.2223529411764710.389
295109WESTBROOK E
Adder
4.0305882352941183.426
939061AE1-134 2
50/50
4.0994.099
927208AC1-214 E1
Adder
2.84000000000000032.414
293717O-029 E
50/50
10.66510.665
293516O-009 E
50/50
40.92240.922
946321AF1-296 C
Adder
7.7494117647058826.587
274718NELSON EC;2S
50/50
6.8026.802
933911AD1-013 C
Adder
1.2588235294117651.07
927209AC1-214 E2
Adder
2.84000000000000032.414
295111SUBLETTE E
Adder
1.95882352941176491.665
946322AF1-296 E
Adder
36.2788235294117730.837
274860EASYR;U2 E
50/50
35.20335.203
274859EASYR;U1 E
50/50
35.20335.203
293771O-035 E
Adder
5.9905882352941175.092
293716O-029 E
50/50
11.60411.604
276158O-029 C
50/50
0.7890.789
276156O-029 C
50/50
0.4370.437
933912AD1-013 E
Adder
2.0105882352941181.709
965931AG1-462 C
50/50
36.41936.419
946152AF1-280 E
50/50
67.18767.187
294401BSHIL;1U E
Adder
9.1588235294117667.785
290051GSG-6; E
Adder
7.5282352941176476.399
274716NELSON EC;1S
50/50
6.7426.742
959082AF2-199 E
50/50
17.71517.715
958912AF2-182 E
50/50
100.78100.78
274766LEE CO EC;7U
50/50
4.6054.605
274764LEE CO EC;5U
50/50
4.6714.671
946671AF1-331 C
Adder
1.63529411764705881.39
276676AA2-030 GEN
50/50
8.628.62
957471AF2-041 C
50/50
106.288106.288
938861AE1-114 C
Adder
4.9835294117647064.236
274858BIG SKY ;U2
50/50
0.8340.834
937002AD2-134 E
Adder
7.2788235294117656.187
276677AA1-146
50/50
10.43210.432
274762LEE CO EC;3U
50/50
4.664.66
274761LEE CO EC;2U
50/50
4.664.66
293715O-029 E
50/50
21.16321.163
274857BIG SKY ;U1
50/50
0.8340.834
276157O-029 C
50/50
0.7890.789
274881WALNUT RG;1U
50/50
1.6721.672
916221Z1-073 E
Adder
5.3047058823529424.509
274715NELSON EC;1C
50/50
9.249.24
959092AF2-200 E
50/50
47.23947.239
957472AF2-041 E
50/50
53.14453.144
938862AE1-114 E
Adder
17.00352941176470614.453
272363ESS H440 ; R
Adder
1.821.547
965932AG1-462 E
50/50
24.27924.279
939051AE1-134 1
50/50
0.6580.658
959091AF2-200 C
50/50
70.85970.859
916212CRESCENT ;1U
Adder
4.2082352941176473.577
294410BSHIL;2U E
Adder
9.1588235294117667.785
966822AG1-553 E
50/50
61.88861.888
274717NELSON EC;2C
50/50
9.3129.312
959081AF2-199 C
50/50
35.42935.429
274765LEE CO EC;6U
50/50
4.6714.671
274763LEE CO EC;4U
50/50
4.6164.616
274760LEE CO EC;1U
50/50
4.664.66
274767LEE CO EC;8U
50/50
4.6054.605
925582AC1-033 E
Adder
10.0435294117647078.537
962012AG1-044 E
50/50
0.1520.152
276626AG1-044 E
50/50
0.1520.152
991092J1477
External Queue
7.7741432189941417.774143218994141
955972J1084
External Queue
29.59977722167968829.599777221679688
990947J1432 C
External Queue
6.4772243499755866.477224349975586
990948J1432 E
External Queue
35.043445587158235.0434455871582
956412J1131
External Queue
15.51725292205810515.517252922058105
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0170.017
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0260.026
SIGELTFEXP_SIGE->PJM
CLTF
0.0520.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.02215.022
NYPJM->LTFIMP_NY
CLTF
0.1950.195
TVALTFEXP_TVA->PJM
CLTF
2.2672.267
LAGNLTFEXP_LAGN->PJM
CLTF
4.6314.631
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.0865.08
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3440.344
CPLELTFEXP_CPLE->PJM
CLTF
0.270.27
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0080.008
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.1270.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.8814.881
WECLTFEXP_WEC->PJM
CLTF
0.0040.004
MECLTFEXP_MEC->PJM
CLTF
16.85816.858
O66PJM->LTFIMP_O-066
CMTX_NF
2.2112.211

Details for AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.8 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2108.84
MW Contribution:67.05
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.58 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2123.16
MW Contribution:67.16
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
990901L-005 E
Adder
12.1847058823529410.357
295109WESTBROOK E
Adder
3.99411764705882363.395
939061AE1-134 2
50/50
4.0914.091
927208AC1-214 E1
Adder
2.8317647058823532.407
293717O-029 E
50/50
10.63310.633
293516O-009 E
50/50
40.840.8
946321AF1-296 C
Adder
7.71764705882352956.56
274718NELSON EC;2S
50/50
6.7886.788
927209AC1-214 E2
Adder
2.8317647058823532.407
295111SUBLETTE E
Adder
1.94235294117647061.651
946322AF1-296 E
Adder
36.12941176470588530.71
274860EASYR;U2 E
50/50
35.1335.13
274859EASYR;U1 E
50/50
35.1335.13
293771O-035 E
Adder
5.9729411764705885.077
293716O-029 E
50/50
11.56911.569
276158O-029 C
50/50
0.7860.786
276156O-029 C
50/50
0.4360.436
965931AG1-462 C
50/50
36.28536.285
946152AF1-280 E
50/50
67.04767.047
294401BSHIL;1U E
Adder
9.1305882352941187.761
290051GSG-6; E
Adder
7.4611764705882356.342
274716NELSON EC;1S
50/50
6.7286.728
959082AF2-199 E
50/50
17.7117.71
958912AF2-182 E
50/50
100.57100.57
274766LEE CO EC;7U
50/50
4.5964.596
274764LEE CO EC;5U
50/50
4.6614.661
276676AA2-030 GEN
50/50
8.6028.602
957471AF2-041 C
50/50
106.259106.259
938861AE1-114 C
Adder
4.90117647058823554.166
274858BIG SKY ;U2
50/50
0.8330.833
937002AD2-134 E
Adder
7.2141176470588236.132
276677AA1-146
50/50
10.41110.411
274762LEE CO EC;3U
50/50
4.6514.651
274761LEE CO EC;2U
50/50
4.6514.651
293715O-029 E
50/50
21.121.1
274857BIG SKY ;U1
50/50
0.8330.833
276157O-029 C
50/50
0.7860.786
274881WALNUT RG;1U
50/50
1.6671.667
916221Z1-073 E
Adder
5.257647058823534.469
274715NELSON EC;1C
50/50
9.2219.221
959092AF2-200 E
50/50
47.22647.226
957472AF2-041 E
50/50
53.1353.13
938862AE1-114 E
Adder
16.7223529411764714.214
916212CRESCENT ;1U
Adder
4.1964705882352953.567
294410BSHIL;2U E
Adder
9.1305882352941187.761
966822AG1-553 E
50/50
61.66161.661
274717NELSON EC;2C
50/50
9.2929.292
959081AF2-199 C
50/50
35.4235.42
274765LEE CO EC;6U
50/50
4.6614.661
274763LEE CO EC;4U
50/50
4.6064.606
274760LEE CO EC;1U
50/50
4.6514.651
272363ESS H440 ; R
Adder
1.80352941176470581.533
965932AG1-462 E
50/50
24.1924.19
939051AE1-134 1
50/50
0.6570.657
959091AF2-200 C
50/50
70.8470.84
274767LEE CO EC;8U
50/50
4.5964.596
925582AC1-033 E
Adder
10.0117647058823538.51
962012AG1-044 E
50/50
0.1520.152
276626AG1-044 E
50/50
0.1520.152
991092J1477
External Queue
7.7651863098144537.765186309814453
955972J1084
External Queue
29.56552124023437529.565521240234375
990947J1432 C
External Queue
6.457697391510016.45769739151001
990948J1432 E
External Queue
34.9377975463867234.93779754638672
956412J1131
External Queue
15.49937438964843815.499374389648438
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.88914.889
NYPJM->LTFIMP_NY
CLTF
0.1940.194
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0260.026
SIGELTFEXP_SIGE->PJM
CLTF
0.0510.051
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.43163.431
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3420.342
TVALTFEXP_TVA->PJM
CLTF
2.2452.245
LAGNLTFEXP_LAGN->PJM
CLTF
4.5854.585
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.8234.823
CPLELTFEXP_CPLE->PJM
CLTF
0.2660.266
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0090.009
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.1250.125
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0160.016
MECLTFEXP_MEC->PJM
CLTF
16.69316.693
O66PJM->LTFIMP_O-066
CMTX_NF
2.2012.201
CONTINGENCY 'COMED_P4_006-45-BT3-8___SRT-A'
 TRIP BRANCH FROM BUS 270678 TO BUS 270679 CKT Z1   /*BYRON    ; B 345.0 - BYRON    ; R 345.0
 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1    /*LEE CO EC;BP 345.0 - BYRON    ; B 345.0
END
CONTINGENCY 'COMED_P4_006-45-BT3-4___SRT-A'
 REMOVE UNIT 1 FROM BUS 274656                     /*BYRON    ;1U  25.0
 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1   /*LEE CO EC;BP 345.0 - BYRON    ; B 345.0
END
957470 to 270730 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC146.62 %971.0B1423.7219.08
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC146.52 %971.0B1422.6919.2
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC146.52 %971.0B1422.6919.2
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC126.45 %1399.0B1768.9723.25
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC126.44 %1399.0B1768.923.25
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC126.42 %1399.0B1768.6723.17
GD1CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4-6_116-345-R______SRT-A
BreakerAC107.57 %2297.0STE2471.018.73
GD1CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4_116-45-L11614__SRT-A
BreakerAC103.27 %2297.0STE2372.116.2
GD1CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4_112-45-BT4-5___SRT-A
BreakerAC100.41 %2297.0STE2306.4720.52
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC126.43 %970.0STE1226.419.2
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC126.43 %970.0STE1226.419.2
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC126.41 %970.0STE1226.1519.08

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.62 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1423.72
MW Contribution:19.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957331AF2-027 C
Adder
2.1047058823529411.789
936511AD2-066 C
Adder
7.1305882352941186.061
936512AD2-066 E
Adder
4.7541176470588244.041
295109WESTBROOK E
Adder
4.7152941176470594.008
939061AE1-134 2
Adder
1.14705882352941170.975
960681AF2-359 C
50/50
63.75263.752
274813UNIV PK N;9U
50/50
1.8991.899
274811UNIV PK N;7U
50/50
1.9151.915
941551AE2-152 C
Adder
9.7929411764705888.324
274676JOLIET 29;8U
Adder
61.7682352941176552.503
958481AF2-142 C
Adder
10.2035294117647068.673
957332AF2-027 E
Adder
3.15764705882352952.684
274891CAYUG;2U E
Adder
11.395294117647069.686
926822AC1-168 E
Adder
6.4258823529411765.462
943122AE2-341 E
Adder
5.2905882352941184.497
939322AE1-163 E
Adder
32.5729411764705927.687
293516O-009 E
Adder
15.7576470588235313.394
293717O-029 E
Adder
4.1070588235294123.491
936372AD2-047 E
Adder
18.36705882352941215.612
276591L-013 2
Adder
3.09411764705882362.63
962781AG1-127 C
Adder
5.8976470588235295.013
933911AD1-013 C
Adder
1.55058823529411781.318
293519PILOT HIL;1E
Adder
15.48823529411764713.165
939351AE1-166 C
Adder
8.4870588235294137.214
274675JOLIET 29;7U
Adder
61.79058823529411652.522
274674JOLIET 9 ;6U
Adder
31.0329411764705926.378
293061N-015 E
Adder
13.10117647058823411.136
943121AE2-341 C
Adder
10.7729411764705899.157
939321AE1-163 C
Adder
5.302352941176474.507
295111SUBLETTE E
Adder
2.29294117647058831.949
274860EASYR;U2 E
Adder
10.0658823529411758.556
965791AG1-447 C
50/50
46.75146.751
965682AG1-436 E
50/50
42.50142.501
960591AF2-350 C
Adder
6.637647058823535.642
960592AF2-350 E
Adder
4.4247058823529413.761
275149KELLYCK ;1E
Adder
15.48823529411764713.165
934722AD1-100 E
Adder
76.1647058823529364.74
960751AF2-366 C
Adder
5.8811764705882354.999
942422AE2-255 E
Adder
7.61411764705882456.472
960582AF2-349 E
Adder
30.4847058823529425.912
937312AD2-172 E
Adder
2.84588235294117682.419
274859EASYR;U1 E
Adder
10.0658823529411758.556
293644O22 E1
Adder
11.5517647058823549.819
960281AF2-319 C
Adder
2.0105882352941181.709
960752AF2-366 E
Adder
3.92117647058823553.333
957471AF2-041 C
Adder
17.9576470588235315.264
294763P-046 E
Adder
7.9094117647058826.723
938861AE1-114 C
Adder
3.2964705882352942.802
274808UNIV PK N;4U
50/50
1.9071.907
959351AF2-226 C
Adder
2.0105882352941181.709
958491AF2-143 C
Adder
9.748.279
933912AD1-013 E
Adder
2.47764705882352932.106
946152AF1-280 E
Adder
19.08352941176470816.221
293716O-029 E
Adder
4.46823529411764753.798
274815UNIV PK N;XU
50/50
1.9031.903
958012AF2-095 E
Adder
6.3717647058823535.416
934111AD2-000 2
Adder
5.0470588235294124.29
966442AG1-513 E
Adder
0.64470588235294120.548
274683WAUKEGAN ;8U
Adder
37.5458823529411831.914
290051GSG-6; E
Adder
8.8082352941176477.487
959082AF2-199 E
Adder
2.99294117647058842.544
958912AF2-182 E
Adder
28.6258823529411824.332
936371AD2-047 C
Adder
3.76235294117647053.198
936461AD2-060 C
Adder
2.2129411764705881.881
933412AC2-154 E
Adder
3.42941176470588262.915
962782AG1-127 E
Adder
3.92470588235294133.336
946671AF1-331 C
Adder
2.01411764705882361.712
274805UNIV PK N;1U
50/50
1.9031.903
943592AF1-030 E
Adder
3.54470588235294143.013
943591AF1-030 C
Adder
7.1635294117647066.089
936292AD2-038 E
Adder
13.37529411764705911.369
290021O50 E
Adder
16.24352941176470813.807
937002AD2-134 E
Adder
8.5164705882352937.239
965681AG1-436 C
50/50
63.75263.752
293645O22 E2
Adder
13.2305882352941211.246
960282AF2-319 E
Adder
3.01647058823529422.564
918052AA1-018 E OP
Adder
14.7952941176470612.576
293715O-029 E
Adder
8.1494117647058816.927
910542X3-005 E
Adder
0.53058823529411770.451
939352AE1-166 E
Adder
7.8341176470588236.659
294392P-010 E
Adder
16.63882352941176614.143
959352AF2-226 E
Adder
3.01647058823529422.564
934101AD2-000 1
Adder
4.8788235294117654.147
958492AF2-143 E
Adder
6.4929411764705885.519
942421AE2-255 C
Adder
2.53764705882352942.157
290108LEEDK;1U E
Adder
20.2152941176470617.183
916221Z1-073 E
Adder
6.2070588235294125.276
957472AF2-041 E
Adder
8.9788235294117647.632
959092AF2-200 E
Adder
7.98117647058823556.784
926821AC1-168 C
Adder
0.95764705882352940.814
938862AE1-114 E
Adder
11.244705882352949.558
966092AG1-478 E
Adder
0.44117647058823530.375
274682WAUKEGAN ;7U
Adder
34.8235294117647129.6
942651AE2-281 C
Adder
0.75764705882352950.644
942652AE2-281 E
Adder
4.6529411764705893.955
962691AG1-118 C
Adder
18.6752941176470615.874
962692AG1-118 E
Adder
12.45058823529411810.583
938851AE1-113 C
Adder
6.75.695
272363ESS H440 ; R
Adder
2.21411764705882331.882
959091AF2-200 C
Adder
11.97176470588235410.176
940502AE2-035 E
Adder
2.84588235294117682.419
274814UNIV PK N;0U
50/50
1.8911.891
274807UNIV PK N;3U
50/50
1.9151.915
274816UNIV PK N;YU
50/50
1.9151.915
958011AF2-095 C
Adder
9.557647058823538.124
933411AC2-154 C
Adder
2.10235294117647081.787
274687WILL CNTY;4U
Adder
55.58000000000000547.243
966091AG1-478 C
Adder
1.7552941176470591.492
966441AG1-513 C
Adder
0.430588235294117660.366
959081AF2-199 C
Adder
5.9858823529411775.088
960682AF2-359 E
50/50
42.50142.501
274810UNIV PK N;6U
50/50
1.9071.907
274812UNIV PK N;8U
50/50
1.8991.899
941552AE2-152 E
Adder
6.5282352941176485.549
958482AF2-142 E
Adder
6.8023529411764715.782
938852AE1-113 E
Adder
23.75647058823529520.193
274890CAYUG;1U E
Adder
11.395294117647069.686
962012AG1-044 E
Adder
0.0529411764705882350.045
276626AG1-044 E
Adder
0.061176470588235290.052
276675AE2-062 E
Adder
0.134117647058823540.114
920272AA2-123 E
Adder
2.4188235294117652.056
276170Z1-108 E
Adder
2.4670588235294122.097
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4090.409
MECLTFEXP_MEC->PJM
CLTF
10.92410.924
O66PJM->LTFIMP_O-066
CMTX_NF
11.09411.094
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.47412.474
WECLTFEXP_WEC->PJM
CLTF
3.2883.288
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.4090.409
SIGELTFEXP_SIGE->PJM
CLTF
0.0150.015
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.23368.233
NYPJM->LTFIMP_NY
CLTF
0.9310.931
TVALTFEXP_TVA->PJM
CLTF
1.1671.167
LAGNLTFEXP_LAGN->PJM
CLTF
2.992.99
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7291.729
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.210.21
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.1721.172
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6070.607

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.52 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1422.69
MW Contribution:19.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957331AF2-027 C
Adder
2.1211764705882351.803
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
295109WESTBROOK E
Adder
4.7482352941176474.036
939061AE1-134 2
Adder
1.15294117647058810.98
943122AE2-341 E
Adder
5.3317647058823534.532
939322AE1-163 E
Adder
32.7952941176470627.876
293516O-009 E
Adder
15.8423529411764713.466
293717O-029 E
Adder
4.1282352941176473.509
936372AD2-047 E
Adder
18.53411764705882415.754
276591L-013 2
Adder
3.11882352941176462.651
962781AG1-127 C
Adder
5.94117647058823555.05
933911AD1-013 C
Adder
1.56117647058823541.327
293519PILOT HIL;1E
Adder
15.63058823529411813.286
939351AE1-166 C
Adder
8.555294117647067.272
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
293061N-015 E
Adder
13.20352941176470711.223
943121AE2-341 C
Adder
10.8588235294117659.23
939321AE1-163 C
Adder
5.3388235294117654.538
295111SUBLETTE E
Adder
2.3082352941176471.962
274860EASYR;U2 E
Adder
10.1270588235294138.608
965791AG1-447 C
50/50
46.89646.896
965682AG1-436 E
50/50
42.63342.633
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
275149KELLYCK ;1E
Adder
15.63058823529411813.286
934722AD1-100 E
Adder
76.7823529411764765.265
960751AF2-366 C
Adder
5.9247058823529415.036
942422AE2-255 E
Adder
7.6658823529411776.516
960582AF2-349 E
Adder
30.726.095
937312AD2-172 E
Adder
2.8647058823529412.435
274859EASYR;U1 E
Adder
10.1270588235294138.608
274808UNIV PK N;4U
50/50
1.9171.917
959351AF2-226 C
Adder
2.0270588235294121.723
958491AF2-143 C
Adder
9.8058823529411778.335
933912AD1-013 E
Adder
2.49411764705882362.12
946152AF1-280 E
Adder
19.1976470588235316.318
293716O-029 E
Adder
4.4917647058823533.818
274815UNIV PK N;XU
50/50
1.9131.913
958012AF2-095 E
Adder
6.4305882352941185.466
934111AD2-000 2
Adder
5.0882352941176484.325
966442AG1-513 E
Adder
0.65058823529411770.553
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
290051GSG-6; E
Adder
8.8682352941176487.538
959082AF2-199 E
Adder
3.01294117647058852.561
958912AF2-182 E
Adder
28.79647058823529424.477
293644O22 E1
Adder
11.6458823529411759.899
960281AF2-319 C
Adder
2.0270588235294121.723
960752AF2-366 E
Adder
3.94941176470588263.357
957471AF2-041 C
Adder
18.07882352941176815.367
294763P-046 E
Adder
7.9611764705882366.767
938861AE1-114 C
Adder
3.3164705882352942.819
936371AD2-047 C
Adder
3.7964705882352943.227
936461AD2-060 C
Adder
2.2329411764705881.898
933412AC2-154 E
Adder
3.46117647058823552.942
962782AG1-127 E
Adder
3.9541176470588243.361
946671AF1-331 C
Adder
2.0282352941176471.724
274805UNIV PK N;1U
50/50
1.9131.913
943592AF1-030 E
Adder
3.5729411764705883.037
943591AF1-030 C
Adder
7.2211764705882366.138
936292AD2-038 E
Adder
13.46705882352941211.447
290021O50 E
Adder
16.3552941176470613.902
937002AD2-134 E
Adder
8.5752941176470587.289
965681AG1-436 C
50/50
63.94963.949
293645O22 E2
Adder
13.33882352941176411.338
960282AF2-319 E
Adder
3.0411764705882352.585
918052AA1-018 E OP
Adder
14.9023529411764712.667
293715O-029 E
Adder
8.1929411764705896.964
960681AF2-359 C
50/50
63.94963.949
274813UNIV PK N;9U
50/50
1.9091.909
274811UNIV PK N;7U
50/50
1.9251.925
941551AE2-152 C
Adder
9.8717647058823528.391
274676JOLIET 29;8U
Adder
62.29647058823529452.952
958481AF2-142 C
Adder
10.2776470588235318.736
957332AF2-027 E
Adder
3.1823529411764712.705
274891CAYUG;2U E
Adder
11.4552941176470599.737
926822AC1-168 E
Adder
6.4588235294117655.49
910542X3-005 E
Adder
0.53764705882352950.457
939352AE1-166 E
Adder
7.897647058823536.713
294392P-010 E
Adder
16.76941176470588214.254
959352AF2-226 E
Adder
3.0411764705882352.585
934101AD2-000 1
Adder
4.91411764705882354.177
958492AF2-143 E
Adder
6.537647058823535.557
942421AE2-255 C
Adder
2.5552941176470592.172
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
957472AF2-041 E
Adder
9.0400000000000017.684
959092AF2-200 E
Adder
8.0352941176470596.83
926821AC1-168 C
Adder
0.96235294117647050.818
938862AE1-114 E
Adder
11.315294117647069.618
274814UNIV PK N;0U
50/50
1.9011.901
274807UNIV PK N;3U
50/50
1.9251.925
274816UNIV PK N;YU
50/50
1.9251.925
958011AF2-095 C
Adder
9.6458823529411778.199
933411AC2-154 C
Adder
2.1211764705882351.803
274687WILL CNTY;4U
Adder
56.08235294117647447.67
966091AG1-478 C
Adder
1.76941176470588251.504
966441AG1-513 C
Adder
0.434117647058823550.369
959081AF2-199 C
Adder
6.0258823529411775.122
966092AG1-478 E
Adder
0.44470588235294120.378
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
938851AE1-113 C
Adder
6.7458823529411775.734
272363ESS H440 ; R
Adder
2.22941176470588241.895
959091AF2-200 C
Adder
12.05294117647058810.245
940502AE2-035 E
Adder
2.8647058823529412.435
960682AF2-359 E
50/50
42.63342.633
274810UNIV PK N;6U
50/50
1.9171.917
274812UNIV PK N;8U
50/50
1.9091.909
941552AE2-152 E
Adder
6.5811764705882365.594
958482AF2-142 E
Adder
6.8517647058823535.824
938852AE1-113 E
Adder
23.91882352941176420.331
274890CAYUG;1U E
Adder
11.4552941176470599.737
962012AG1-044 E
Adder
0.0529411764705882350.045
276626AG1-044 E
Adder
0.062352941176470590.053
276675AE2-062 E
Adder
0.135294117647058840.115
920272AA2-123 E
Adder
2.4364705882352942.071
276170Z1-108 E
Adder
2.48588235294117642.113
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
NYPJM->LTFIMP_NY
CLTF
0.9330.933
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.52 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1422.69
MW Contribution:19.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957331AF2-027 C
Adder
2.1211764705882351.803
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
295109WESTBROOK E
Adder
4.7482352941176474.036
939061AE1-134 2
Adder
1.15294117647058810.98
960681AF2-359 C
50/50
63.94963.949
274813UNIV PK N;9U
50/50
1.9091.909
274811UNIV PK N;7U
50/50
1.9251.925
941551AE2-152 C
Adder
9.8717647058823528.391
274676JOLIET 29;8U
Adder
62.29647058823529452.952
958481AF2-142 C
Adder
10.2776470588235318.736
957332AF2-027 E
Adder
3.1823529411764712.705
274891CAYUG;2U E
Adder
11.4552941176470599.737
926822AC1-168 E
Adder
6.4588235294117655.49
943122AE2-341 E
Adder
5.3317647058823534.532
939322AE1-163 E
Adder
32.7952941176470627.876
293516O-009 E
Adder
15.8423529411764713.466
293717O-029 E
Adder
4.1282352941176473.509
936372AD2-047 E
Adder
18.53411764705882415.754
276591L-013 2
Adder
3.11882352941176462.651
962781AG1-127 C
Adder
5.94117647058823555.05
933911AD1-013 C
Adder
1.56117647058823541.327
293519PILOT HIL;1E
Adder
15.63058823529411813.286
939351AE1-166 C
Adder
8.555294117647067.272
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
293061N-015 E
Adder
13.20352941176470711.223
943121AE2-341 C
Adder
10.8588235294117659.23
939321AE1-163 C
Adder
5.3388235294117654.538
295111SUBLETTE E
Adder
2.3082352941176471.962
274860EASYR;U2 E
Adder
10.1270588235294138.608
965791AG1-447 C
50/50
46.89646.896
965682AG1-436 E
50/50
42.63342.633
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
275149KELLYCK ;1E
Adder
15.63058823529411813.286
934722AD1-100 E
Adder
76.7823529411764765.265
960751AF2-366 C
Adder
5.9247058823529415.036
942422AE2-255 E
Adder
7.6658823529411776.516
960582AF2-349 E
Adder
30.726.095
937312AD2-172 E
Adder
2.8647058823529412.435
274859EASYR;U1 E
Adder
10.1270588235294138.608
293644O22 E1
Adder
11.6458823529411759.899
960281AF2-319 C
Adder
2.0270588235294121.723
960752AF2-366 E
Adder
3.94941176470588263.357
957471AF2-041 C
Adder
18.07882352941176815.367
294763P-046 E
Adder
7.9611764705882366.767
274808UNIV PK N;4U
50/50
1.9171.917
959351AF2-226 C
Adder
2.0270588235294121.723
958491AF2-143 C
Adder
9.8058823529411778.335
933912AD1-013 E
Adder
2.49411764705882362.12
946152AF1-280 E
Adder
19.1976470588235316.318
293716O-029 E
Adder
4.4917647058823533.818
274815UNIV PK N;XU
50/50
1.9131.913
958012AF2-095 E
Adder
6.4305882352941185.466
934111AD2-000 2
Adder
5.0882352941176484.325
966442AG1-513 E
Adder
0.65058823529411770.553
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
290051GSG-6; E
Adder
8.8682352941176487.538
959082AF2-199 E
Adder
3.01294117647058852.561
958912AF2-182 E
Adder
28.79647058823529424.477
936371AD2-047 C
Adder
3.7964705882352943.227
936461AD2-060 C
Adder
2.2329411764705881.898
933412AC2-154 E
Adder
3.46117647058823552.942
962782AG1-127 E
Adder
3.9541176470588243.361
946671AF1-331 C
Adder
2.0282352941176471.724
938861AE1-114 C
Adder
3.3164705882352942.819
274805UNIV PK N;1U
50/50
1.9131.913
943592AF1-030 E
Adder
3.5729411764705883.037
943591AF1-030 C
Adder
7.2211764705882366.138
936292AD2-038 E
Adder
13.46705882352941211.447
290021O50 E
Adder
16.3552941176470613.902
937002AD2-134 E
Adder
8.5752941176470587.289
965681AG1-436 C
50/50
63.94963.949
293645O22 E2
Adder
13.33882352941176411.338
960282AF2-319 E
Adder
3.0411764705882352.585
918052AA1-018 E OP
Adder
14.9023529411764712.667
293715O-029 E
Adder
8.1929411764705896.964
910542X3-005 E
Adder
0.53764705882352950.457
939352AE1-166 E
Adder
7.897647058823536.713
294392P-010 E
Adder
16.76941176470588214.254
959352AF2-226 E
Adder
3.0411764705882352.585
934101AD2-000 1
Adder
4.91411764705882354.177
958492AF2-143 E
Adder
6.537647058823535.557
942421AE2-255 C
Adder
2.5552941176470592.172
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
957472AF2-041 E
Adder
9.0400000000000017.684
959092AF2-200 E
Adder
8.0352941176470596.83
926821AC1-168 C
Adder
0.96235294117647050.818
938862AE1-114 E
Adder
11.315294117647069.618
966092AG1-478 E
Adder
0.44470588235294120.378
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
938851AE1-113 C
Adder
6.7458823529411775.734
272363ESS H440 ; R
Adder
2.22941176470588241.895
959091AF2-200 C
Adder
12.05294117647058810.245
940502AE2-035 E
Adder
2.8647058823529412.435
274814UNIV PK N;0U
50/50
1.9011.901
274807UNIV PK N;3U
50/50
1.9251.925
274816UNIV PK N;YU
50/50
1.9251.925
958011AF2-095 C
Adder
9.6458823529411778.199
933411AC2-154 C
Adder
2.1211764705882351.803
274687WILL CNTY;4U
Adder
56.08235294117647447.67
966091AG1-478 C
Adder
1.76941176470588251.504
966441AG1-513 C
Adder
0.434117647058823550.369
959081AF2-199 C
Adder
6.0258823529411775.122
960682AF2-359 E
50/50
42.63342.633
274810UNIV PK N;6U
50/50
1.9171.917
274812UNIV PK N;8U
50/50
1.9091.909
941552AE2-152 E
Adder
6.5811764705882365.594
958482AF2-142 E
Adder
6.8517647058823535.824
938852AE1-113 E
Adder
23.91882352941176420.331
274890CAYUG;1U E
Adder
11.4552941176470599.737
962012AG1-044 E
Adder
0.0529411764705882350.045
276626AG1-044 E
Adder
0.062352941176470590.053
276675AE2-062 E
Adder
0.135294117647058840.115
920272AA2-123 E
Adder
2.4364705882352942.071
276170Z1-108 E
Adder
2.48588235294117642.113
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
NYPJM->LTFIMP_NY
CLTF
0.9330.933
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.45 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1768.97
MW Contribution:23.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274707KENDALL ;2S
50/50
2.7692.769
957331AF2-027 C
Adder
2.57411764705882362.188
936511AD2-066 C
Adder
8.5164705882352937.239
936512AD2-066 E
Adder
5.67764705882352954.826
295109WESTBROOK E
Adder
5.7364705882352954.876
939061AE1-134 2
Adder
1.39764705882352951.188
943122AE2-341 E
Adder
6.4094117647058835.448
939322AE1-163 E
Adder
36.1270588235294130.708
293516O-009 E
Adder
8.2905882352941187.047
274753CRETE EC ;3U
50/50
6.1116.111
936372AD2-047 E
Adder
19.6616.711
274654BRAIDWOOD;1U
50/50
27.62127.621
274861TOP CROP ;1U
50/50
0.4420.442
276591L-013 2
Adder
3.7670588235294123.202
962781AG1-127 C
Adder
7.1717647058823536.096
933911AD1-013 C
Adder
1.88588235294117661.603
293519PILOT HIL;1E
Adder
16.58000000000000214.093
939351AE1-166 C
Adder
10.217647058823538.685
274675JOLIET 29;7U
Adder
76.2117647058823664.78
274674JOLIET 9 ;6U
Adder
35.323529411764730.025
293061N-015 E
Adder
16.04470588235294313.638
943121AE2-341 C
Adder
13.05176470588235211.094
274862TOP CROP ;2U
50/50
0.8420.842
939321AE1-163 C
Adder
5.8811764705882354.999
295111SUBLETTE E
Adder
2.78941176470588252.371
274860EASYR;U2 E
Adder
12.26705882352941210.427
960591AF2-350 C
Adder
7.1058823529411776.04
960592AF2-350 E
Adder
4.737647058823534.027
275149KELLYCK ;1E
Adder
16.58000000000000214.093
934722AD1-100 E
Adder
91.6917647058823677.938
960751AF2-366 C
Adder
7.1517647058823536.079
942422AE2-255 E
Adder
9.4505882352941168.033
960582AF2-349 E
Adder
37.19058823529411531.612
937312AD2-172 E
Adder
3.4682352941176472.948
274859EASYR;U1 E
Adder
12.26705882352941210.427
274655BRAIDWOOD;2U
50/50
26.87526.875
959351AF2-226 C
50/50
2.9472.947
958491AF2-143 C
Adder
10.8023529411764719.182
933912AD1-013 E
Adder
3.01294117647058852.561
946152AF1-280 E
Adder
23.25529411764705819.767
274754CRETE EC ;4U
50/50
6.1116.111
958012AF2-095 E
Adder
6.8211764705882355.798
934111AD2-000 2
Adder
6.3129411764705885.366
966442AG1-513 E
Adder
0.78235294117647070.665
274683WAUKEGAN ;8U
Adder
45.9439.049
290051GSG-6; E
Adder
10.715294117647069.108
959082AF2-199 E
Adder
3.65647058823529443.108
958912AF2-182 E
Adder
34.8823529411764729.65
274752CRETE EC ;2U
50/50
6.1116.111
936371AD2-047 C
Adder
4.0270588235294123.423
936461AD2-060 C
Adder
2.3682352941176472.013
933412AC2-154 E
Adder
3.6717647058823533.121
962782AG1-127 E
Adder
4.7729411764705894.057
946671AF1-331 C
Adder
2.4494117647058822.082
274751CRETE EC ;1U
50/50
6.1116.111
293644O22 E1
50/50
16.92816.928
960281AF2-319 C
50/50
2.9472.947
960752AF2-366 E
Adder
4.7682352941176474.053
957471AF2-041 C
Adder
21.9376470588235318.647
294763P-046 E
Adder
9.6411764705882378.195
938861AE1-114 C
Adder
4.0152941176470593.413
943592AF1-030 E
Adder
4.2941176470588233.65
943591AF1-030 C
Adder
8.687.378
936292AD2-038 E
Adder
14.8352941176470612.61
290021O50 E
Adder
20.16117647058823817.137
937002AD2-134 E
Adder
10.368.806
293645O22 E2
50/50
19.38819.388
960282AF2-319 E
50/50
4.424.42
918052AA1-018 E OP
Adder
15.76000000000000213.396
939352AE1-166 E
Adder
9.4317647058823538.017
294392P-010 E
Adder
20.3776470588235317.321
959352AF2-226 E
50/50
4.424.42
934101AD2-000 1
Adder
5.8964705882352945.012
958492AF2-143 E
Adder
7.2011764705882366.121
942421AE2-255 C
Adder
3.15058823529411752.678
290108LEEDK;1U E
Adder
24.58352941176470820.896
916221Z1-073 E
Adder
7.5505882352941186.418
957472AF2-041 E
Adder
10.9682352941176489.323
959092AF2-200 E
Adder
9.7494117647058838.287
926821AC1-168 C
Adder
1.16235294117647060.988
938862AE1-114 E
Adder
13.70117647058823711.646
941551AE2-152 C
Adder
11.78941176470588410.021
274676JOLIET 29;8U
50/50
76.25576.255
274704KENDALL ;1C
50/50
4.144.14
274706KENDALL ;2C
50/50
4.144.14
274705KENDALL ;1S
50/50
2.7692.769
958481AF2-142 C
Adder
10.8694117647058849.239
957332AF2-027 E
Adder
3.86117647058823543.282
274891CAYUG;2U E
Adder
13.66000000000000211.611
926822AC1-168 E
Adder
7.797647058823536.628
966092AG1-478 E
Adder
0.50588235294117640.43
274682WAUKEGAN ;7U
Adder
42.623529411764736.23
942651AE2-281 C
Adder
0.840.714
942652AE2-281 E
Adder
5.1611764705882354.387
962691AG1-118 C
Adder
22.70941176470588419.303
962692AG1-118 E
Adder
15.1412.869
938851AE1-113 C
Adder
8.3164705882352947.069
272363ESS H440 ; R
Adder
2.69411764705882372.29
958011AF2-095 C
Adder
10.2317647058823528.697
933411AC2-154 C
Adder
2.25058823529411761.913
274687WILL CNTY;4U
50/50
71.93671.936
966091AG1-478 C
Adder
2.00941176470588221.708
966441AG1-513 C
Adder
0.52235294117647060.444
959081AF2-199 C
Adder
7.3129411764705896.216
959091AF2-200 C
Adder
14.62470588235294112.431
940502AE2-035 E
Adder
3.4682352941176472.948
941552AE2-152 E
Adder
7.8588235294117646.68
958482AF2-142 E
Adder
7.2458823529411776.159
938852AE1-113 E
Adder
29.48470588235294425.062
274890CAYUG;1U E
Adder
13.66000000000000211.611
962012AG1-044 E
Adder
0.063529411764705890.054
276626AG1-044 E
Adder
0.075294117647058830.064
276675AE2-062 E
Adder
0.152941176470588250.13
920272AA2-123 E
Adder
2.9517647058823532.509
276170Z1-108 E
Adder
3.01294117647058852.561
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.30480.304
NYPJM->LTFIMP_NY
CLTF
1.1511.151
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
LAGNLTFEXP_LAGN->PJM
CLTF
3.2773.277
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1432.143
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0692.069
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5770.577
MECLTFEXP_MEC->PJM
CLTF
13.16213.162
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.41313.413
WECLTFEXP_WEC->PJM
CLTF
4.0154.015
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7060.706
O66PJM->LTFIMP_O-066
CMTX_NF
13.7513.75

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.44 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1768.9
MW Contribution:23.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274707KENDALL ;2S
50/50
2.7692.769
957331AF2-027 C
Adder
2.57411764705882362.188
936511AD2-066 C
Adder
8.5164705882352937.239
936512AD2-066 E
Adder
5.67764705882352954.826
295109WESTBROOK E
Adder
5.7364705882352954.876
939061AE1-134 2
Adder
1.39764705882352951.188
941551AE2-152 C
Adder
11.78941176470588410.021
274676JOLIET 29;8U
50/50
76.25276.252
274704KENDALL ;1C
50/50
4.144.14
274706KENDALL ;2C
50/50
4.144.14
274705KENDALL ;1S
50/50
2.7692.769
958481AF2-142 C
Adder
10.8694117647058849.239
957332AF2-027 E
Adder
3.86117647058823543.282
274891CAYUG;2U E
Adder
13.66000000000000211.611
926822AC1-168 E
Adder
7.79647058823529456.627
943122AE2-341 E
Adder
6.4082352941176475.447
939322AE1-163 E
Adder
36.12588235294117630.707
293516O-009 E
Adder
8.2905882352941187.047
274753CRETE EC ;3U
50/50
6.1116.111
936372AD2-047 E
Adder
19.66117647058823416.712
274654BRAIDWOOD;1U
50/50
27.62127.621
274861TOP CROP ;1U
50/50
0.4420.442
276591L-013 2
Adder
3.7670588235294123.202
962781AG1-127 C
Adder
7.1717647058823536.096
933911AD1-013 C
Adder
1.88588235294117661.603
293519PILOT HIL;1E
Adder
16.58117647058823614.094
939351AE1-166 C
Adder
10.217647058823538.685
274675JOLIET 29;7U
Adder
76.2094117647058964.778
274674JOLIET 9 ;6U
Adder
35.32235294117647630.024
293061N-015 E
Adder
16.04470588235294313.638
943121AE2-341 C
Adder
13.05058823529411811.093
274862TOP CROP ;2U
50/50
0.8420.842
939321AE1-163 C
Adder
5.8811764705882354.999
295111SUBLETTE E
Adder
2.78823529411764742.37
274860EASYR;U2 E
Adder
12.26588235294117610.426
960591AF2-350 C
Adder
7.1058823529411776.04
960592AF2-350 E
Adder
4.737647058823534.027
275149KELLYCK ;1E
Adder
16.58117647058823614.094
934722AD1-100 E
Adder
91.6988235294117777.944
960751AF2-366 C
Adder
7.1517647058823536.079
942422AE2-255 E
Adder
9.4494117647058828.032
960582AF2-349 E
Adder
37.1870588235294131.609
937312AD2-172 E
Adder
3.4682352941176472.948
274859EASYR;U1 E
Adder
12.26588235294117610.426
274751CRETE EC ;1U
50/50
6.1116.111
293644O22 E1
50/50
16.92816.928
960281AF2-319 C
50/50
2.9462.946
960752AF2-366 E
Adder
4.7670588235294114.052
957471AF2-041 C
Adder
21.93529411764705718.645
294763P-046 E
Adder
9.648.194
938861AE1-114 C
Adder
4.0152941176470593.413
274655BRAIDWOOD;2U
50/50
26.87526.875
959351AF2-226 C
50/50
2.9462.946
958491AF2-143 C
Adder
10.8023529411764719.182
933912AD1-013 E
Adder
3.01294117647058852.561
946152AF1-280 E
Adder
23.2529411764705919.765
274754CRETE EC ;4U
50/50
6.1116.111
958012AF2-095 E
Adder
6.8211764705882355.798
934111AD2-000 2
Adder
6.3117647058823545.365
966442AG1-513 E
Adder
0.78235294117647070.665
274683WAUKEGAN ;8U
Adder
45.93647058823529539.046
290051GSG-6; E
Adder
10.7141176470588229.107
959082AF2-199 E
Adder
3.65529411764705923.107
958912AF2-182 E
Adder
34.8788235294117629.647
274752CRETE EC ;2U
50/50
6.1116.111
936371AD2-047 C
Adder
4.0270588235294123.423
936461AD2-060 C
Adder
2.3682352941176472.013
933412AC2-154 E
Adder
3.6717647058823533.121
962782AG1-127 E
Adder
4.7729411764705894.057
946671AF1-331 C
Adder
2.4494117647058822.082
943592AF1-030 E
Adder
4.2941176470588233.65
943591AF1-030 C
Adder
8.6788235294117657.377
936292AD2-038 E
Adder
14.83411764705882312.609
290021O50 E
Adder
20.1617.136
937002AD2-134 E
Adder
10.3588235294117658.805
293645O22 E2
50/50
19.38819.388
960282AF2-319 E
50/50
4.424.42
918052AA1-018 E OP
Adder
15.76000000000000213.396
939352AE1-166 E
Adder
9.4317647058823538.017
294392P-010 E
Adder
20.37647058823529617.32
959352AF2-226 E
50/50
4.424.42
934101AD2-000 1
Adder
5.8952941176470595.011
958492AF2-143 E
Adder
7.2011764705882366.121
942421AE2-255 C
Adder
3.14941176470588242.677
290108LEEDK;1U E
Adder
24.58117647058823320.894
916221Z1-073 E
Adder
7.5494117647058836.417
957472AF2-041 E
Adder
10.9670588235294129.322
959092AF2-200 E
Adder
9.7494117647058838.287
926821AC1-168 C
Adder
1.16235294117647060.988
938862AE1-114 E
Adder
13.711.645
966092AG1-478 E
Adder
0.50588235294117640.43
274682WAUKEGAN ;7U
Adder
42.6236.227
942651AE2-281 C
Adder
0.840.714
942652AE2-281 E
Adder
5.1611764705882354.387
962691AG1-118 C
Adder
22.7070588235294119.301
962692AG1-118 E
Adder
15.13882352941176612.868
938851AE1-113 C
Adder
8.3164705882352947.069
272363ESS H440 ; R
Adder
2.69411764705882372.29
959091AF2-200 C
Adder
14.62352941176470512.43
940502AE2-035 E
Adder
3.4682352941176472.948
958011AF2-095 C
Adder
10.232941176470598.698
933411AC2-154 C
Adder
2.25058823529411761.913
274687WILL CNTY;4U
50/50
71.93571.935
966091AG1-478 C
Adder
2.00941176470588221.708
966441AG1-513 C
Adder
0.52235294117647060.444
959081AF2-199 C
Adder
7.3117647058823536.215
941552AE2-152 E
Adder
7.866.681
958482AF2-142 E
Adder
7.2458823529411776.159
938852AE1-113 E
Adder
29.48352941176470725.061
274890CAYUG;1U E
Adder
13.66000000000000211.611
962012AG1-044 E
Adder
0.063529411764705890.054
276626AG1-044 E
Adder
0.075294117647058830.064
276675AE2-062 E
Adder
0.152941176470588250.13
920272AA2-123 E
Adder
2.9517647058823532.509
276170Z1-108 E
Adder
3.0117647058823532.56
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.41213.412
WECLTFEXP_WEC->PJM
CLTF
4.0154.015
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7060.706
O66PJM->LTFIMP_O-066
CMTX_NF
13.7513.75
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.29780.297
NYPJM->LTFIMP_NY
CLTF
1.1511.151
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
LAGNLTFEXP_LAGN->PJM
CLTF
3.2773.277
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1432.143
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0692.069
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5760.576
MECLTFEXP_MEC->PJM
CLTF
13.16113.161
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.42 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1768.67
MW Contribution:23.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274707KENDALL ;2S
50/50
2.7572.757
957331AF2-027 C
Adder
2.5635294117647062.179
936511AD2-066 C
Adder
8.484705882352947.212
936512AD2-066 E
Adder
5.6564705882352944.808
295109WESTBROOK E
Adder
5.7129411764705884.856
939061AE1-134 2
Adder
1.39294117647058811.184
943122AE2-341 E
Adder
6.377647058823535.421
939322AE1-163 E
Adder
35.98588235294117530.588
293516O-009 E
Adder
8.2647058823529427.025
274753CRETE EC ;3U
50/50
6.1016.101
936372AD2-047 E
Adder
19.5623529411764716.628
274654BRAIDWOOD;1U
50/50
27.51327.513
274861TOP CROP ;1U
50/50
0.440.44
276591L-013 2
Adder
3.7505882352941183.188
293519PILOT HIL;1E
Adder
16.49764705882352814.023
939351AE1-166 C
Adder
10.1800000000000018.653
274675JOLIET 29;7U
Adder
75.8694117647058964.489
274674JOLIET 9 ;6U
Adder
35.15058823529411629.878
293061N-015 E
Adder
15.9752941176470613.579
943121AE2-341 C
Adder
12.98823529411764711.04
274862TOP CROP ;2U
50/50
0.8390.839
939321AE1-163 C
Adder
5.8588235294117654.98
295111SUBLETTE E
Adder
2.77764705882352962.361
960591AF2-350 C
Adder
7.0705882352941176.01
960592AF2-350 E
Adder
4.7141176470588234.007
275149KELLYCK ;1E
Adder
16.49764705882352814.023
934722AD1-100 E
Adder
91.3611764705882377.657
960751AF2-366 C
Adder
7.1211764705882356.053
942422AE2-255 E
Adder
9.415294117647068.003
960582AF2-349 E
Adder
37.0376470588235331.482
937312AD2-172 E
Adder
3.45529411764705862.937
274859EASYR;U1 E
Adder
12.2223529411764710.389
274860EASYR;U2 E
Adder
12.2223529411764710.389
274655BRAIDWOOD;2U
50/50
26.76926.769
959351AF2-226 C
50/50
2.9362.936
958491AF2-143 C
Adder
10.7600000000000029.146
933912AD1-013 E
Adder
3.00117647058823562.551
946152AF1-280 E
Adder
23.17176470588235719.696
274754CRETE EC ;4U
50/50
6.1016.101
958012AF2-095 E
Adder
6.7870588235294125.769
934111AD2-000 2
Adder
6.2858823529411775.343
966442AG1-513 E
Adder
0.77882352941176480.662
274683WAUKEGAN ;8U
Adder
45.7388235294117738.878
290051GSG-6; E
Adder
10.6705882352941199.07
959082AF2-199 E
Adder
3.64117647058823573.095
958912AF2-182 E
Adder
34.7576470588235329.544
274751CRETE EC ;1U
50/50
6.1016.101
293644O22 E1
50/50
16.86916.869
960281AF2-319 C
50/50
2.9362.936
960752AF2-366 E
Adder
4.7470588235294124.035
957471AF2-041 C
Adder
21.8494117647058818.572
294763P-046 E
Adder
9.6035294117647068.163
938861AE1-114 C
Adder
4.0011764705882353.401
274752CRETE EC ;2U
50/50
6.1016.101
936371AD2-047 C
Adder
4.00705882352941253.406
936461AD2-060 C
Adder
2.3564705882352942.003
933412AC2-154 E
Adder
3.6529411764705883.105
962782AG1-127 E
Adder
4.7517647058823534.039
946671AF1-331 C
Adder
2.442.074
943592AF1-030 E
Adder
4.2741176470588243.633
943591AF1-030 C
Adder
8.6376470588235297.342
936292AD2-038 E
Adder
14.7776470588235312.561
290021O50 E
Adder
20.08705882352941417.074
937002AD2-134 E
Adder
10.317647058823538.77
293645O22 E2
50/50
19.32119.321
960282AF2-319 E
50/50
4.4044.404
918052AA1-018 E OP
Adder
15.69411764705882513.34
962781AG1-127 C
Adder
7.1411764705882366.07
933911AD1-013 C
Adder
1.87882352941176481.597
941551AE2-152 C
Adder
11.7458823529411779.984
274676JOLIET 29;8U
50/50
75.91275.912
274704KENDALL ;1C
50/50
4.1234.123
274706KENDALL ;2C
50/50
4.1234.123
274705KENDALL ;1S
50/50
2.7572.757
958481AF2-142 C
Adder
10.8235294117647059.2
957332AF2-027 E
Adder
3.8447058823529413.268
274891CAYUG;2U E
Adder
13.62588235294117711.582
926822AC1-168 E
Adder
7.7741176470588236.608
939352AE1-166 E
Adder
9.397647058823537.988
294392P-010 E
Adder
20.28941176470588217.246
959352AF2-226 E
50/50
4.4044.404
934101AD2-000 1
Adder
5.8705882352941184.99
958492AF2-143 E
Adder
7.1729411764705896.097
942421AE2-255 C
Adder
3.1388235294117652.668
290108LEEDK;1U E
Adder
24.47764705882353220.806
916221Z1-073 E
Adder
7.52000000000000056.392
957472AF2-041 E
Adder
10.924705882352949.286
958011AF2-095 C
Adder
10.1811764705882368.654
933411AC2-154 C
Adder
2.23882352941176471.903
274687WILL CNTY;4U
50/50
71.61971.619
966091AG1-478 C
Adder
2.01.7
966441AG1-513 C
Adder
0.520.442
959081AF2-199 C
Adder
7.2835294117647066.191
959092AF2-200 E
Adder
9.7105882352941188.254
926821AC1-168 C
Adder
1.15882352941176480.985
938862AE1-114 E
Adder
13.65058823529411711.603
966092AG1-478 E
Adder
0.50352941176470590.428
274682WAUKEGAN ;7U
Adder
42.43647058823529536.071
942651AE2-281 C
Adder
0.83647058823529410.711
942652AE2-281 E
Adder
5.1411764705882364.37
962691AG1-118 C
Adder
22.60941176470588219.218
962692AG1-118 E
Adder
15.07294117647058812.812
938851AE1-113 C
Adder
8.2858823529411787.043
272363ESS H440 ; R
Adder
2.68235294117647042.28
959091AF2-200 C
Adder
14.56588235294117712.381
940502AE2-035 E
Adder
3.45529411764705862.937
941552AE2-152 E
Adder
7.8305882352941176.656
958482AF2-142 E
Adder
7.2152941176470596.133
938852AE1-113 E
Adder
29.3776470588235324.971
274890CAYUG;1U E
Adder
13.62588235294117711.582
962012AG1-044 E
Adder
0.063529411764705890.054
276626AG1-044 E
Adder
0.075294117647058830.064
276675AE2-062 E
Adder
0.152941176470588250.13
920272AA2-123 E
Adder
2.9388235294117652.498
276170Z1-108 E
Adder
2.9988235294117652.549
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5540.554
MECLTFEXP_MEC->PJM
CLTF
13.15813.158
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8080.808
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.83113.831
WECLTFEXP_WEC->PJM
CLTF
3.9993.999
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6340.634
O66PJM->LTFIMP_O-066
CMTX_NF
13.71713.717
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.46579.465
NYPJM->LTFIMP_NY
CLTF
1.151.15
TVALTFEXP_TVA->PJM
CLTF
1.191.19
LAGNLTFEXP_LAGN->PJM
CLTF
3.3653.365
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1382.138
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2920.292
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.8531.853

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4-6_116-345-R______SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_116-345-R______SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.57 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2471.0
MW Contribution:18.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276642AC1-204 GEN2
50/50
19.02419.024
957331AF2-027 C
Adder
2.0988235294117651.784
936511AD2-066 C
Adder
7.0129411764705895.961
936512AD2-066 E
Adder
4.6752941176470593.974
295109WESTBROOK E
Adder
4.197647058823533.568
939061AE1-134 2
Adder
1.13411764705882350.964
990901L-005 E
Adder
11.329.622
943122AE2-341 E
Adder
3.75411764705882333.191
939322AE1-163 E
Adder
44.6517647058823637.954
927208AC1-214 E1
Adder
2.69411764705882372.29
293516O-009 E
Adder
15.7152941176470613.358
293717O-029 E
Adder
4.0952941176470593.481
946321AF1-296 C
Adder
3.02705882352941162.573
274861TOP CROP ;1U
50/50
0.8730.873
276591L-013 2
Adder
2.7541176470588242.341
962781AG1-127 C
Adder
5.0494117647058834.292
933911AD1-013 C
Adder
1.37647058823529411.17
274675JOLIET 29;7U
Adder
83.9305882352941171.341
943121AE2-341 C
Adder
7.6458823529411766.499
274862TOP CROP ;2U
50/50
1.6661.666
939321AE1-163 C
Adder
7.26941176470588256.179
295111SUBLETTE E
Adder
2.041.734
274860EASYR;U2 E
Adder
9.8505882352941178.373
927209AC1-214 E2
Adder
2.69411764705882372.29
946322AF1-296 E
Adder
14.17411764705882312.048
274728ELWOOD EC;5P
50/50
5.1145.114
960751AF2-366 C
Adder
5.035294117647064.28
942422AE2-255 E
Adder
11.99176470588235310.193
960582AF2-349 E
Adder
29.2670588235294124.877
937312AD2-172 E
Adder
2.74941176470588242.337
274859EASYR;U1 E
Adder
9.8505882352941178.373
276640AC1-204 GEN1
50/50
18.92818.928
959351AF2-226 C
50/50
5.8285.828
958491AF2-143 C
Adder
13.35058823529411911.348
933912AD1-013 E
Adder
2.19882352941176461.869
946152AF1-280 E
Adder
18.7352941176470615.925
293771O-035 E
Adder
5.6823529411764714.83
293716O-029 E
Adder
4.4564705882352943.788
965931AG1-462 C
Adder
13.77411764705882511.708
934111AD2-000 2
Adder
7.8929411764705886.709
966442AG1-513 E
Adder
0.54705882352941180.465
274683WAUKEGAN ;8U
Adder
37.50470588235294431.879
290051GSG-6; E
Adder
7.846.664
959082AF2-199 E
Adder
2.87294117647058832.442
958912AF2-182 E
Adder
28.10235294117647323.887
294401BSHIL;1U E
Adder
7.4129411764705886.301
274732ELWOOD EC;7P
50/50
5.1145.114
274730ELWOOD EC;6P
50/50
5.1145.114
962782AG1-127 E
Adder
3.362.856
274729ELWOOD EC;1P
50/50
5.0895.089
293644O22 E1
50/50
33.48133.481
960281AF2-319 C
50/50
5.8285.828
960752AF2-366 E
Adder
3.35647058823529452.853
957471AF2-041 C
Adder
17.23882352941176414.653
294763P-046 E
Adder
7.6411764705882366.495
938861AE1-114 C
Adder
3.19411764705882332.715
943592AF1-030 E
Adder
2.51529411764705872.138
943591AF1-030 C
Adder
5.0847058823529414.322
936292AD2-038 E
Adder
18.3352941176470615.585
290021O50 E
Adder
25.58117647058823621.744
937002AD2-134 E
Adder
7.586.443
946671AF1-331 C
Adder
1.78823529411764711.52
293645O22 E2
50/50
38.34738.347
960282AF2-319 E
50/50
8.7428.742
918052AA1-018 E OP
Adder
19.13411764705882216.264
293715O-029 E
Adder
8.1270588235294126.908
959352AF2-226 E
50/50
8.7428.742
934101AD2-000 1
Adder
5.88705882352941155.004
958492AF2-143 E
Adder
8.9011764705882357.566
942421AE2-255 C
Adder
3.99764705882352983.398
290108LEEDK;1U E
Adder
17.4505882352941214.833
916221Z1-073 E
Adder
5.5247058823529414.696
957472AF2-041 E
Adder
8.6188235294117657.326
959092AF2-200 E
Adder
7.6611764705882356.512
926821AC1-168 C
Adder
0.77294117647058820.657
938862AE1-114 E
Adder
10.8952941176470589.261
274676JOLIET 29;8U
Adder
84.2188235294117671.586
937401AD2-194 1
50/50
1.9831.983
958481AF2-142 C
Adder
13.19647058823529511.217
957332AF2-027 E
Adder
3.14705882352941172.675
926822AC1-168 E
Adder
5.1858823529411774.408
966091AG1-478 C
Adder
1.16588235294117660.991
274733ELWOOD EC;3P
50/50
5.0895.089
966441AG1-513 C
Adder
0.364705882352941160.31
959081AF2-199 C
Adder
5.7458823529411774.884
916212CRESCENT ;1U
Adder
3.9917647058823533.393
294410BSHIL;2U E
Adder
7.4129411764705886.301
966822AG1-553 E
Adder
23.40705882352941519.896
966092AG1-478 E
Adder
0.292941176470588260.249
274734ELWOOD EC;8P
50/50
5.1145.114
274736ELWOOD EC;9P
50/50
5.1145.114
274735ELWOOD EC;4P
50/50
5.0895.089
274682WAUKEGAN ;7U
Adder
34.8294117647058829.605
942651AE2-281 C
Adder
1.03882352941176470.883
942652AE2-281 E
Adder
6.3788235294117655.422
962691AG1-118 C
Adder
15.91411764705882313.527
962692AG1-118 E
Adder
10.6094117647058849.018
938851AE1-113 C
Adder
10.552941176470598.97
272363ESS H440 ; R
Adder
1.96705882352941171.672
959091AF2-200 C
Adder
11.4917647058823539.768
940502AE2-035 E
Adder
2.74941176470588242.337
965932AG1-462 E
Adder
9.1835294117647067.806
937411AD2-194 2
50/50
1.9931.993
958482AF2-142 E
Adder
8.7976470588235297.478
938852AE1-113 E
Adder
37.4129411764705931.801
962012AG1-044 E
Adder
0.051764705882352940.044
925582AC1-033 E
Adder
8.1270588235294126.908
276170Z1-108 E
Adder
2.35294117647058832
276626AG1-044 E
Adder
0.061176470588235290.052
920272AA2-123 E
Adder
2.3082352941176471.962
990647J1355
External Queue
-10.193851470947266-10.193851470947266
990552J1334 G
External Queue
-23.77029800415039-23.77029800415039
990557J1335 G
External Queue
-23.77029800415039-23.77029800415039
990562J1336 G
External Queue
-23.77029800415039-23.77029800415039
990577J1339
External Queue
-28.123506546020508-28.123506546020508
990547J1333 G
External Queue
-23.77029800415039-23.77029800415039
990582J1340
External Queue
-28.123506546020508-28.123506546020508
990662J1358
External Queue
-12.060297966003418-12.060297966003418
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.94111.941
WECLTFEXP_WEC->PJM
CLTF
3.283.28
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.3970.397
O66PJM->LTFIMP_O-066
CMTX_NF
8.148.14
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.268.2
NYPJM->LTFIMP_NY
CLTF
0.6860.686
TVALTFEXP_TVA->PJM
CLTF
1.2761.276
LAGNLTFEXP_LAGN->PJM
CLTF
3.1343.134
G-007PJM->LTFIMP_G-007
CMTX_NF
1.2681.268
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1170.117
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.1491.149
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2450.245
MECLTFEXP_MEC->PJM
CLTF
11.3111.31
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.3820.382

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614__SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_116-45-L11614__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.27 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2372.1
MW Contribution:16.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276642AC1-204 GEN2
50/50
18.72218.722
957331AF2-027 C
Adder
1.69529411764705881.441
936511AD2-066 C
Adder
6.53294117647058855.553
936512AD2-066 E
Adder
4.3552941176470593.702
295109WESTBROOK E
Adder
3.6164705882352943.074
939061AE1-134 2
Adder
0.98823529411764710.84
990901L-005 E
Adder
10.5717647058823538.986
274676JOLIET 29;8U
Adder
63.8752941176470654.294
937401AD2-194 1
50/50
1.951.95
958481AF2-142 C
Adder
12.96117647058823511.017
943122AE2-341 E
Adder
3.22705882352941182.743
939322AE1-163 E
Adder
43.8082352941176537.237
927208AC1-214 E1
Adder
2.50588235294117642.13
293516O-009 E
Adder
13.94235294117647211.851
293717O-029 E
Adder
3.63411764705882373.089
946321AF1-296 C
Adder
2.6705882352941182.27
274731ELWOOD EC;2P
50/50
5.0055.005
274861TOP CROP ;1U
50/50
0.8930.893
276591L-013 2
Adder
2.32235294117647051.974
962781AG1-127 C
Adder
4.32235294117647053.674
933911AD1-013 C
Adder
1.18588235294117661.008
274675JOLIET 29;7U
Adder
63.4341176470588253.919
943121AE2-341 C
Adder
6.5717647058823535.586
274862TOP CROP ;2U
50/50
1.7031.703
939321AE1-163 C
Adder
7.1317647058823546.062
295111SUBLETTE E
Adder
1.7588235294117651.495
274860EASYR;U2 E
Adder
8.4917647058823537.218
927209AC1-214 E2
Adder
2.50588235294117642.13
946322AF1-296 E
Adder
12.50235294117647210.627
274728ELWOOD EC;5P
50/50
5.0335.033
960751AF2-366 C
Adder
4.3105882352941183.664
942422AE2-255 E
Adder
11.5717647058823539.836
960582AF2-349 E
Adder
24.51176470588235320.835
937312AD2-172 E
Adder
2.3423529411764711.991
274859EASYR;U1 E
Adder
8.4917647058823537.218
276640AC1-204 GEN1
50/50
18.61918.619
959351AF2-226 C
50/50
5.9595.959
958491AF2-143 C
Adder
13.09882352941176511.134
933912AD1-013 E
Adder
1.89411764705882371.61
946152AF1-280 E
Adder
16.2023529411764713.772
293771O-035 E
Adder
5.2858823529411774.493
293716O-029 E
Adder
3.95294117647058843.36
965931AG1-462 C
Adder
12.18352941176470610.356
934111AD2-000 2
Adder
7.502352941176476.377
966442AG1-513 E
Adder
0.46117647058823530.392
274683WAUKEGAN ;8U
Adder
30.27176470588235425.731
290051GSG-6; E
Adder
6.7552941176470595.742
959082AF2-199 E
Adder
2.48705882352941152.114
958912AF2-182 E
Adder
24.30352941176470720.658
294401BSHIL;1U E
Adder
6.8764705882352945.845
274732ELWOOD EC;7P
50/50
5.0335.033
274730ELWOOD EC;6P
50/50
5.0335.033
962782AG1-127 E
Adder
2.8764705882352942.445
946671AF1-331 C
Adder
1.541.309
274729ELWOOD EC;1P
50/50
5.0055.005
293644O22 E1
50/50
34.23434.234
960281AF2-319 C
50/50
5.9595.959
960752AF2-366 E
Adder
2.87294117647058832.442
957471AF2-041 C
Adder
14.92470588235294212.686
294763P-046 E
Adder
6.5117647058823535.535
938861AE1-114 C
Adder
2.74470588235294162.333
943592AF1-030 E
Adder
2.1623529411764711.838
943591AF1-030 C
Adder
4.3694117647058823.714
936292AD2-038 E
Adder
17.98823529411764715.29
290021O50 E
Adder
24.68705882352941620.984
937002AD2-134 E
Adder
6.53176470588235255.552
293645O22 E2
50/50
39.2139.21
960282AF2-319 E
50/50
8.9388.938
918052AA1-018 E OP
Adder
18.79411764705882215.975
293715O-029 E
Adder
7.2105882352941176.129
959352AF2-226 E
50/50
8.9388.938
934101AD2-000 1
Adder
5.4164705882352954.604
958492AF2-143 E
Adder
8.7329411764705887.423
942421AE2-255 C
Adder
3.8576470588235293.279
290108LEEDK;1U E
Adder
14.98705882352941312.739
916221Z1-073 E
Adder
4.7611764705882354.047
957472AF2-041 E
Adder
7.4623529411764716.343
959092AF2-200 E
Adder
6.6329411764705885.638
926821AC1-168 C
Adder
0.72352941176470590.615
938862AE1-114 E
Adder
9.3635294117647067.959
957332AF2-027 E
Adder
2.54235294117647072.161
926822AC1-168 E
Adder
4.8552941176470594.127
966092AG1-478 E
Adder
0.268235294117647070.228
274734ELWOOD EC;8P
50/50
5.0335.033
274736ELWOOD EC;9P
50/50
5.0335.033
274682WAUKEGAN ;7U
Adder
28.12352941176470723.905
942651AE2-281 C
Adder
1.01882352941176470.866
942652AE2-281 E
Adder
6.2588235294117665.32
962691AG1-118 C
Adder
13.63294117647058811.588
962692AG1-118 E
Adder
9.0882352941176477.725
938851AE1-113 C
Adder
10.1835294117647088.656
272363ESS H440 ; R
Adder
1.69529411764705881.441
959091AF2-200 C
Adder
9.9494117647058848.457
940502AE2-035 E
Adder
2.3423529411764711.991
965932AG1-462 E
Adder
8.1223529411764716.904
966091AG1-478 C
Adder
1.06705882352941180.907
274733ELWOOD EC;3P
50/50
5.0055.005
966441AG1-513 C
Adder
0.30705882352941180.261
959081AF2-199 C
Adder
4.9752941176470594.229
916212CRESCENT ;1U
Adder
3.71294117647058863.156
294410BSHIL;2U E
Adder
6.8764705882352945.845
966822AG1-553 E
Adder
20.70352941176470617.598
937411AD2-194 2
50/50
1.9611.961
958482AF2-142 E
Adder
8.6411764705882357.345
938852AE1-113 E
Adder
36.10470588235294530.689
962012AG1-044 E
Adder
0.045882352941176470.039
925582AC1-033 E
Adder
7.5388235294117656.408
276170Z1-108 E
Adder
1.94588235294117641.654
920272AA2-123 E
Adder
1.92705882352941171.638
276626AG1-044 E
Adder
0.054117647058823530.046
990647J1355
External Queue
-9.393627166748047-9.393627166748047
990552J1334 G
External Queue
-22.909955978393555-22.909955978393555
990557J1335 G
External Queue
-22.909955978393555-22.909955978393555
990562J1336 G
External Queue
-22.909955978393555-22.909955978393555
990577J1339
External Queue
-27.099620819091797-27.099620819091797
990547J1333 G
External Queue
-22.909955978393555-22.909955978393555
990582J1340
External Queue
-27.099620819091797-27.099620819091797
990662J1358
External Queue
-11.463173866271973-11.463173866271973
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2250.225
MECLTFEXP_MEC->PJM
CLTF
10.03810.038
O66PJM->LTFIMP_O-066
CMTX_NF
7.4827.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.99810.998
WECLTFEXP_WEC->PJM
CLTF
2.6952.695
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.3610.361
SIGELTFEXP_SIGE->PJM
CLTF
00
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.86656.866
NYPJM->LTFIMP_NY
CLTF
0.630.63
TVALTFEXP_TVA->PJM
CLTF
1.1651.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.8362.836
G-007PJM->LTFIMP_G-007
CMTX_NF
1.1661.166
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1080.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.0441.044
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.3520.352

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-45-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.41 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2306.47
MW Contribution:20.52
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276642AC1-204 GEN2
50/50
17.50217.502
274707KENDALL ;2S
50/50
3.9613.961
957331AF2-027 C
Adder
2.3352941176470591.985
936511AD2-066 C
Adder
7.3411764705882366.24
936512AD2-066 E
Adder
4.8941176470588244.16
295109WESTBROOK E
Adder
4.5905882352941183.902
939061AE1-134 2
Adder
1.24117647058823531.055
990901L-005 E
Adder
12.28823529411764810.445
290261S-027 E
Adder
12.5152941176470610.638
290265S-028 E
Adder
12.43882352941176510.573
943122AE2-341 E
Adder
4.0811764705882353.469
939322AE1-163 E
Adder
28.22941176470588323.995
927208AC1-214 E1
Adder
2.92941176470588262.49
293516O-009 E
Adder
17.15882352941176614.585
293717O-029 E
Adder
4.4717647058823533.801
946321AF1-296 C
Adder
3.32000000000000032.822
274731ELWOOD EC;2P
50/50
4.6474.647
274861TOP CROP ;1U
50/50
1.0691.069
276591L-013 2
Adder
3.00235294117647072.552
962781AG1-127 C
Adder
5.5211764705882354.693
933911AD1-013 C
Adder
1.50588235294117641.28
274675JOLIET 29;7U
Adder
91.0294117647058877.375
943121AE2-341 C
Adder
8.3105882352941187.064
274862TOP CROP ;2U
50/50
2.0392.039
939321AE1-163 C
Adder
4.5952941176470593.906
295111SUBLETTE E
Adder
2.2317647058823531.897
274860EASYR;U2 E
Adder
10.7905882352941189.172
927209AC1-214 E2
Adder
2.92941176470588262.49
946322AF1-296 E
Adder
15.54588235294117713.214
274728ELWOOD EC;5P
50/50
4.7054.705
960751AF2-366 C
Adder
5.50588235294117644.68
942422AE2-255 E
Adder
12.25411764705882510.416
960582AF2-349 E
Adder
32.12588235294117627.307
937312AD2-172 E
Adder
3.01647058823529422.564
274859EASYR;U1 E
Adder
10.7905882352941189.172
276640AC1-204 GEN1
50/50
17.28517.285
959351AF2-226 C
50/50
7.1367.136
958491AF2-143 C
Adder
8.4411764705882367.175
933912AD1-013 E
Adder
2.40470588235294122.044
946152AF1-280 E
Adder
20.51882352941176517.441
293771O-035 E
Adder
6.177647058823535.251
293716O-029 E
Adder
4.8658823529411774.136
939742AE1-205 E
Adder
9.247.854
965931AG1-462 C
Adder
15.10352941176470612.838
934111AD2-000 2
Adder
8.1694117647058836.944
966442AG1-513 E
Adder
0.59411764705882350.505
274683WAUKEGAN ;8U
Adder
41.79647058823529435.527
290051GSG-6; E
Adder
8.5729411764705887.287
959082AF2-199 E
Adder
3.13764705882352952.667
958912AF2-182 E
Adder
30.77764705882353326.161
294401BSHIL;1U E
Adder
8.0376470588235296.832
942112AE2-223 E
Adder
10.3941176470588268.835
959612AF2-252 E
Adder
2.30117647058823541.956
274729ELWOOD EC;1P
50/50
4.6474.647
293644O22 E1
50/50
40.99540.995
960281AF2-319 C
50/50
7.1367.136
960752AF2-366 E
Adder
3.6705882352941183.12
957471AF2-041 C
Adder
18.82352941176470716
294763P-046 E
Adder
8.3823529411764717.125
938861AE1-114 C
Adder
3.52.975
943592AF1-030 E
Adder
2.73411764705882332.324
943591AF1-030 C
Adder
5.5270588235294124.698
936292AD2-038 E
Adder
11.5917647058823539.853
290021O50 E
Adder
26.14235294117647322.221
937002AD2-134 E
Adder
8.2894117647058827.046
274732ELWOOD EC;7P
50/50
4.7054.705
274730ELWOOD EC;6P
50/50
4.7054.705
962782AG1-127 E
Adder
3.67411764705882373.123
946671AF1-331 C
Adder
1.95529411764705881.662
960611AF2-352 C
Adder
1.53411764705882361.304
293645O22 E2
50/50
46.95446.954
960282AF2-319 E
50/50
10.70410.704
293715O-029 E
Adder
8.8741176470588247.543
959352AF2-226 E
50/50
10.70410.704
934101AD2-000 1
Adder
5.8152941176470594.943
958492AF2-143 E
Adder
5.6270588235294134.783
942421AE2-255 C
Adder
4.0847058823529413.472
290108LEEDK;1U E
Adder
19.07882352941176416.217
916221Z1-073 E
Adder
6.0411764705882355.135
957472AF2-041 E
Adder
9.4117647058823538
959092AF2-200 E
Adder
8.3658823529411767.111
274676JOLIET 29;8U
Adder
91.5117647058823677.785
937401AD2-194 1
50/50
1.8111.811
274704KENDALL ;1C
50/50
5.9235.923
274706KENDALL ;2C
50/50
5.9235.923
274705KENDALL ;1S
50/50
3.9613.961
957332AF2-027 E
Adder
3.50235294117647072.977
926822AC1-168 E
Adder
5.5847058823529414.747
926821AC1-168 C
Adder
0.8317647058823530.707
938862AE1-114 E
Adder
11.94117647058823610.15
959611AF2-252 C
Adder
1.53411764705882361.304
966441AG1-513 C
Adder
0.396470588235294130.337
959081AF2-199 C
Adder
6.2741176470588245.333
916212CRESCENT ;1U
Adder
4.343.689
294410BSHIL;2U E
Adder
8.0376470588235296.832
917502Z2-087 E
Adder
13.85882352941176311.78
942111AE2-223 C
Adder
1.55294117647058831.32
939741AE1-205 C
Adder
6.6905882352941185.687
960612AF2-352 E
Adder
2.30117647058823541.956
966822AG1-553 E
Adder
25.66705882352941321.817
274734ELWOOD EC;8P
50/50
4.7054.705
274736ELWOOD EC;9P
50/50
4.7054.705
274735ELWOOD EC;4P
50/50
4.6474.647
274682WAUKEGAN ;7U
Adder
38.8423529411764733.016
942651AE2-281 C
Adder
0.65647058823529430.558
942652AE2-281 E
Adder
4.03294117647058853.428
962691AG1-118 C
Adder
17.414.79
962692AG1-118 E
Adder
11.69.86
938851AE1-113 C
Adder
10.7835294117647079.166
272363ESS H440 ; R
Adder
2.1517647058823531.829
959091AF2-200 C
Adder
12.54823529411764810.666
940502AE2-035 E
Adder
3.01647058823529422.564
924048AB2-047 E1
Adder
8.5941176470588237.305
959341AF2-225 C
Adder
5.0176470588235294.265
965092AG1-374 E
Adder
9.2023529411764717.822
965091AG1-374 C
Adder
13.80470588235294111.734
965932AG1-462 E
Adder
10.0694117647058818.559
937411AD2-194 2
50/50
1.8341.834
938852AE1-113 E
Adder
38.2329411764705932.498
962012AG1-044 E
Adder
0.056470588235294120.048
925582AC1-033 E
Adder
8.8105882352941187.489
924049AB2-047 E2
Adder
8.7294117647058837.42
959342AF2-225 E
Adder
6.9294117647058825.89
920272AA2-123 E
Adder
2.53411764705882362.154
276626AG1-044 E
Adder
0.067058823529411770.057
276170Z1-108 E
Adder
2.58588235294117652.198
991182J1586 G
External Queue
-35.323299407958984-35.323299407958984
990647J1355
External Queue
-11.565272331237793-11.565272331237793
990552J1334 G
External Queue
-25.95514488220215-25.95514488220215
990557J1335 G
External Queue
-25.95514488220215-25.95514488220215
990562J1336 G
External Queue
-25.95514488220215-25.95514488220215
990577J1339
External Queue
-28.660625457763672-28.660625457763672
990497J1323
External Queue
-1.8008151054382324-1.8008151054382324
990547J1333 G
External Queue
-25.95514488220215-25.95514488220215
990582J1340
External Queue
-28.660625457763672-28.660625457763672
990662J1358
External Queue
-13.962589263916016-13.962589263916016
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1710.171
MECLTFEXP_MEC->PJM
CLTF
12.68312.683
O66PJM->LTFIMP_O-066
CMTX_NF
8.3278.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.95815.958
WECLTFEXP_WEC->PJM
CLTF
3.6463.646
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.3060.306
SIGELTFEXP_SIGE->PJM
CLTF
0.0390.039
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.48876.488
NYPJM->LTFIMP_NY
CLTF
0.7040.704
TVALTFEXP_TVA->PJM
CLTF
1.831.83
LAGNLTFEXP_LAGN->PJM
CLTF
3.9933.993
G-007PJM->LTFIMP_G-007
CMTX_NF
1.2971.297
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0650.065
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.8420.842
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.2990.299

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.43 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1226.4
MW Contribution:19.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957331AF2-027 C
Adder
2.1211764705882351.803
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
295109WESTBROOK E
Adder
4.7482352941176474.036
939061AE1-134 2
Adder
1.15294117647058810.98
274813UNIV PK N;9U
50/50
1.9091.909
274811UNIV PK N;7U
50/50
1.9251.925
941551AE2-152 C
Adder
9.8717647058823528.391
274676JOLIET 29;8U
Adder
62.29647058823529452.952
958481AF2-142 C
Adder
10.2776470588235318.736
957332AF2-027 E
Adder
3.1823529411764712.705
274891CAYUG;2U E
Adder
11.4552941176470599.737
926822AC1-168 E
Adder
6.4588235294117655.49
961502AF2-441 E
Adder
10.8105882352941189.189
943122AE2-341 E
Adder
5.3317647058823534.532
939322AE1-163 E
Adder
32.7952941176470627.876
927208AC1-214 E1
Adder
2.7435294117647062.332
293516O-009 E
Adder
15.8423529411764713.466
293717O-029 E
Adder
4.1282352941176473.509
936372AD2-047 E
Adder
18.53411764705882415.754
276591L-013 2
Adder
3.11882352941176462.651
962781AG1-127 C
Adder
5.94117647058823555.05
933911AD1-013 C
Adder
1.56117647058823541.327
961501AF2-441 C
Adder
7.2070588235294136.126
293519PILOT HIL;1E
Adder
15.63058823529411813.286
939351AE1-166 C
Adder
8.555294117647067.272
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
293061N-015 E
Adder
13.20352941176470711.223
943121AE2-341 C
Adder
10.8588235294117659.23
939321AE1-163 C
Adder
5.3388235294117654.538
295111SUBLETTE E
Adder
2.3082352941176471.962
274860EASYR;U2 E
Adder
10.1270588235294138.608
927209AC1-214 E2
Adder
2.7435294117647062.332
946322AF1-296 E
Adder
5.1964705882352944.417
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
275149KELLYCK ;1E
Adder
15.63058823529411813.286
934722AD1-100 E
Adder
76.7823529411764765.265
960751AF2-366 C
Adder
5.9247058823529415.036
942422AE2-255 E
Adder
7.6658823529411776.516
960582AF2-349 E
Adder
30.726.095
937312AD2-172 E
Adder
2.8647058823529412.435
274859EASYR;U1 E
Adder
10.1270588235294138.608
274808UNIV PK N;4U
50/50
1.9171.917
959351AF2-226 C
Adder
2.0270588235294121.723
958491AF2-143 C
Adder
9.8058823529411778.335
933912AD1-013 E
Adder
2.49411764705882362.12
946152AF1-280 E
Adder
19.1976470588235316.318
293771O-035 E
Adder
5.7870588235294124.919
293716O-029 E
Adder
4.4917647058823533.818
274815UNIV PK N;XU
50/50
1.9131.913
958012AF2-095 E
Adder
6.4305882352941185.466
934111AD2-000 2
Adder
5.0882352941176484.325
966442AG1-513 E
Adder
0.65058823529411770.553
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
290051GSG-6; E
Adder
8.8682352941176487.538
959082AF2-199 E
Adder
3.01294117647058852.561
958912AF2-182 E
Adder
28.79647058823529424.477
294401BSHIL;1U E
Adder
7.2082352941176476.127
936371AD2-047 C
Adder
3.7964705882352943.227
936461AD2-060 C
Adder
2.2329411764705881.898
933412AC2-154 E
Adder
3.46117647058823552.942
962782AG1-127 E
Adder
3.9541176470588243.361
946671AF1-331 C
Adder
2.0282352941176471.724
293644O22 E1
Adder
11.6458823529411759.899
960281AF2-319 C
Adder
2.0270588235294121.723
960752AF2-366 E
Adder
3.94941176470588263.357
957471AF2-041 C
Adder
18.07882352941176815.367
294763P-046 E
Adder
7.9611764705882366.767
938861AE1-114 C
Adder
3.3164705882352942.819
274805UNIV PK N;1U
50/50
1.9131.913
943592AF1-030 E
Adder
3.5729411764705883.037
943591AF1-030 C
Adder
7.2211764705882366.138
936292AD2-038 E
Adder
13.46705882352941211.447
290021O50 E
Adder
16.3552941176470613.902
937002AD2-134 E
Adder
8.5752941176470587.289
293645O22 E2
Adder
13.33882352941176411.338
960282AF2-319 E
Adder
3.0411764705882352.585
918052AA1-018 E OP
Adder
14.9023529411764712.667
293715O-029 E
Adder
8.1929411764705896.964
910542X3-005 E
Adder
0.53764705882352950.457
939352AE1-166 E
Adder
7.897647058823536.713
294392P-010 E
Adder
16.76941176470588214.254
959352AF2-226 E
Adder
3.0411764705882352.585
934101AD2-000 1
Adder
4.91411764705882354.177
958492AF2-143 E
Adder
6.537647058823535.557
942421AE2-255 C
Adder
2.5552941176470592.172
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
957472AF2-041 E
Adder
9.0400000000000017.684
959092AF2-200 E
Adder
8.0352941176470596.83
926821AC1-168 C
Adder
0.96235294117647050.818
938862AE1-114 E
Adder
11.315294117647069.618
966092AG1-478 E
Adder
0.44470588235294120.378
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
938851AE1-113 C
Adder
6.7458823529411775.734
272363ESS H440 ; R
Adder
2.22941176470588241.895
959091AF2-200 C
Adder
12.05294117647058810.245
940502AE2-035 E
Adder
2.8647058823529412.435
274814UNIV PK N;0U
50/50
1.9011.901
274807UNIV PK N;3U
50/50
1.9251.925
274816UNIV PK N;YU
50/50
1.9251.925
958011AF2-095 C
Adder
9.6458823529411778.199
933411AC2-154 C
Adder
2.1211764705882351.803
274687WILL CNTY;4U
Adder
56.08235294117647447.67
966091AG1-478 C
Adder
1.76941176470588251.504
966441AG1-513 C
Adder
0.434117647058823550.369
959081AF2-199 C
Adder
6.0258823529411775.122
916212CRESCENT ;1U
Adder
4.0658823529411773.456
294410BSHIL;2U E
Adder
7.2082352941176476.127
274810UNIV PK N;6U
50/50
1.9171.917
274812UNIV PK N;8U
50/50
1.9091.909
941552AE2-152 E
Adder
6.5811764705882365.594
958482AF2-142 E
Adder
6.8517647058823535.824
938852AE1-113 E
Adder
23.91882352941176420.331
274890CAYUG;1U E
Adder
11.4552941176470599.737
962012AG1-044 E
Adder
0.0529411764705882350.045
925582AC1-033 E
Adder
7.9023529411764716.717
276626AG1-044 E
Adder
0.062352941176470590.053
276675AE2-062 E
Adder
0.135294117647058840.115
920272AA2-123 E
Adder
2.4364705882352942.071
276170Z1-108 E
Adder
2.48588235294117642.113
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
NYPJM->LTFIMP_NY
CLTF
0.9330.933
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.43 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1226.4
MW Contribution:19.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957331AF2-027 C
Adder
2.1211764705882351.803
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
295109WESTBROOK E
Adder
4.7482352941176474.036
939061AE1-134 2
Adder
1.15294117647058810.98
961502AF2-441 E
Adder
10.8105882352941189.189
943122AE2-341 E
Adder
5.3317647058823534.532
939322AE1-163 E
Adder
32.7952941176470627.876
927208AC1-214 E1
Adder
2.7435294117647062.332
293516O-009 E
Adder
15.8423529411764713.466
293717O-029 E
Adder
4.1282352941176473.509
936372AD2-047 E
Adder
18.53411764705882415.754
276591L-013 2
Adder
3.11882352941176462.651
962781AG1-127 C
Adder
5.94117647058823555.05
933911AD1-013 C
Adder
1.56117647058823541.327
961501AF2-441 C
Adder
7.2070588235294136.126
293519PILOT HIL;1E
Adder
15.63058823529411813.286
939351AE1-166 C
Adder
8.555294117647067.272
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
293061N-015 E
Adder
13.20352941176470711.223
943121AE2-341 C
Adder
10.8588235294117659.23
939321AE1-163 C
Adder
5.3388235294117654.538
295111SUBLETTE E
Adder
2.3082352941176471.962
274860EASYR;U2 E
Adder
10.1270588235294138.608
927209AC1-214 E2
Adder
2.7435294117647062.332
946322AF1-296 E
Adder
5.1964705882352944.417
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
275149KELLYCK ;1E
Adder
15.63058823529411813.286
934722AD1-100 E
Adder
76.7823529411764765.265
960751AF2-366 C
Adder
5.9247058823529415.036
942422AE2-255 E
Adder
7.6658823529411776.516
960582AF2-349 E
Adder
30.726.095
937312AD2-172 E
Adder
2.8647058823529412.435
274859EASYR;U1 E
Adder
10.1270588235294138.608
274808UNIV PK N;4U
50/50
1.9171.917
959351AF2-226 C
Adder
2.0270588235294121.723
958491AF2-143 C
Adder
9.8058823529411778.335
933912AD1-013 E
Adder
2.49411764705882362.12
946152AF1-280 E
Adder
19.1976470588235316.318
293771O-035 E
Adder
5.7870588235294124.919
293716O-029 E
Adder
4.4917647058823533.818
274815UNIV PK N;XU
50/50
1.9131.913
958012AF2-095 E
Adder
6.4305882352941185.466
934111AD2-000 2
Adder
5.0882352941176484.325
966442AG1-513 E
Adder
0.65058823529411770.553
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
290051GSG-6; E
Adder
8.8682352941176487.538
959082AF2-199 E
Adder
3.01294117647058852.561
958912AF2-182 E
Adder
28.79647058823529424.477
294401BSHIL;1U E
Adder
7.2082352941176476.127
936371AD2-047 C
Adder
3.7964705882352943.227
936461AD2-060 C
Adder
2.2329411764705881.898
933412AC2-154 E
Adder
3.46117647058823552.942
962782AG1-127 E
Adder
3.9541176470588243.361
946671AF1-331 C
Adder
2.0282352941176471.724
293644O22 E1
Adder
11.6458823529411759.899
960281AF2-319 C
Adder
2.0270588235294121.723
960752AF2-366 E
Adder
3.94941176470588263.357
957471AF2-041 C
Adder
18.07882352941176815.367
294763P-046 E
Adder
7.9611764705882366.767
938861AE1-114 C
Adder
3.3164705882352942.819
274805UNIV PK N;1U
50/50
1.9131.913
943592AF1-030 E
Adder
3.5729411764705883.037
943591AF1-030 C
Adder
7.2211764705882366.138
936292AD2-038 E
Adder
13.46705882352941211.447
290021O50 E
Adder
16.3552941176470613.902
937002AD2-134 E
Adder
8.5752941176470587.289
293645O22 E2
Adder
13.33882352941176411.338
960282AF2-319 E
Adder
3.0411764705882352.585
918052AA1-018 E OP
Adder
14.9023529411764712.667
293715O-029 E
Adder
8.1929411764705896.964
910542X3-005 E
Adder
0.53764705882352950.457
939352AE1-166 E
Adder
7.897647058823536.713
294392P-010 E
Adder
16.76941176470588214.254
959352AF2-226 E
Adder
3.0411764705882352.585
934101AD2-000 1
Adder
4.91411764705882354.177
958492AF2-143 E
Adder
6.537647058823535.557
942421AE2-255 C
Adder
2.5552941176470592.172
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
957472AF2-041 E
Adder
9.0400000000000017.684
959092AF2-200 E
Adder
8.0352941176470596.83
926821AC1-168 C
Adder
0.96235294117647050.818
938862AE1-114 E
Adder
11.315294117647069.618
274813UNIV PK N;9U
50/50
1.9091.909
274811UNIV PK N;7U
50/50
1.9251.925
941551AE2-152 C
Adder
9.8717647058823528.391
274676JOLIET 29;8U
Adder
62.29647058823529452.952
958481AF2-142 C
Adder
10.2776470588235318.736
957332AF2-027 E
Adder
3.1823529411764712.705
274891CAYUG;2U E
Adder
11.4552941176470599.737
926822AC1-168 E
Adder
6.4588235294117655.49
274814UNIV PK N;0U
50/50
1.9011.901
274807UNIV PK N;3U
50/50
1.9251.925
274816UNIV PK N;YU
50/50
1.9251.925
958011AF2-095 C
Adder
9.6458823529411778.199
933411AC2-154 C
Adder
2.1211764705882351.803
274687WILL CNTY;4U
Adder
56.08235294117647447.67
966091AG1-478 C
Adder
1.76941176470588251.504
966441AG1-513 C
Adder
0.434117647058823550.369
959081AF2-199 C
Adder
6.0258823529411775.122
916212CRESCENT ;1U
Adder
4.0658823529411773.456
294410BSHIL;2U E
Adder
7.2082352941176476.127
966092AG1-478 E
Adder
0.44470588235294120.378
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
938851AE1-113 C
Adder
6.7458823529411775.734
272363ESS H440 ; R
Adder
2.22941176470588241.895
959091AF2-200 C
Adder
12.05294117647058810.245
940502AE2-035 E
Adder
2.8647058823529412.435
274810UNIV PK N;6U
50/50
1.9171.917
274812UNIV PK N;8U
50/50
1.9091.909
941552AE2-152 E
Adder
6.5811764705882365.594
958482AF2-142 E
Adder
6.8517647058823535.824
938852AE1-113 E
Adder
23.91882352941176420.331
274890CAYUG;1U E
Adder
11.4552941176470599.737
962012AG1-044 E
Adder
0.0529411764705882350.045
925582AC1-033 E
Adder
7.9023529411764716.717
276626AG1-044 E
Adder
0.062352941176470590.053
276675AE2-062 E
Adder
0.135294117647058840.115
920272AA2-123 E
Adder
2.4364705882352942.071
276170Z1-108 E
Adder
2.48588235294117642.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
NYPJM->LTFIMP_NY
CLTF
0.9330.933
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.41 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1226.15
MW Contribution:19.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957331AF2-027 C
Adder
2.1047058823529411.789
936511AD2-066 C
Adder
7.1305882352941186.061
936512AD2-066 E
Adder
4.7541176470588244.041
295109WESTBROOK E
Adder
4.7152941176470594.008
939061AE1-134 2
Adder
1.14705882352941170.975
274813UNIV PK N;9U
50/50
1.8991.899
274811UNIV PK N;7U
50/50
1.9151.915
941551AE2-152 C
Adder
9.7929411764705888.324
274676JOLIET 29;8U
Adder
61.7682352941176552.503
958481AF2-142 C
Adder
10.2035294117647068.673
957332AF2-027 E
Adder
3.15764705882352952.684
274891CAYUG;2U E
Adder
11.395294117647069.686
926822AC1-168 E
Adder
6.4258823529411765.462
961502AF2-441 E
Adder
10.6611764705882349.062
943122AE2-341 E
Adder
5.2905882352941184.497
939322AE1-163 E
Adder
32.5729411764705927.687
927208AC1-214 E1
Adder
2.7317647058823532.322
293516O-009 E
Adder
15.7576470588235313.394
293717O-029 E
Adder
4.1070588235294123.491
936372AD2-047 E
Adder
18.36705882352941215.612
276591L-013 2
Adder
3.09411764705882362.63
962781AG1-127 C
Adder
5.8976470588235295.013
933911AD1-013 C
Adder
1.55058823529411781.318
961501AF2-441 C
Adder
7.1070588235294126.041
293519PILOT HIL;1E
Adder
15.48823529411764713.165
939351AE1-166 C
Adder
8.4870588235294137.214
274675JOLIET 29;7U
Adder
61.79058823529411652.522
274674JOLIET 9 ;6U
Adder
31.0329411764705926.378
293061N-015 E
Adder
13.10117647058823411.136
943121AE2-341 C
Adder
10.7729411764705899.157
939321AE1-163 C
Adder
5.302352941176474.507
295111SUBLETTE E
Adder
2.29294117647058831.949
274860EASYR;U2 E
Adder
10.0658823529411758.556
927209AC1-214 E2
Adder
2.7317647058823532.322
946322AF1-296 E
Adder
5.1729411764705894.397
960591AF2-350 C
Adder
6.637647058823535.642
960592AF2-350 E
Adder
4.4247058823529413.761
275149KELLYCK ;1E
Adder
15.48823529411764713.165
934722AD1-100 E
Adder
76.1647058823529364.74
960751AF2-366 C
Adder
5.8811764705882354.999
942422AE2-255 E
Adder
7.61411764705882456.472
960582AF2-349 E
Adder
30.4847058823529425.912
937312AD2-172 E
Adder
2.84588235294117682.419
274859EASYR;U1 E
Adder
10.0658823529411758.556
274808UNIV PK N;4U
50/50
1.9071.907
959351AF2-226 C
Adder
2.0105882352941181.709
958491AF2-143 C
Adder
9.748.279
933912AD1-013 E
Adder
2.47764705882352932.106
946152AF1-280 E
Adder
19.08352941176470816.221
293771O-035 E
Adder
5.7611764705882364.897
293716O-029 E
Adder
4.46823529411764753.798
274815UNIV PK N;XU
50/50
1.9031.903
958012AF2-095 E
Adder
6.3717647058823535.416
934111AD2-000 2
Adder
5.0470588235294124.29
966442AG1-513 E
Adder
0.64470588235294120.548
274683WAUKEGAN ;8U
Adder
37.5458823529411831.914
290051GSG-6; E
Adder
8.8082352941176477.487
959082AF2-199 E
Adder
2.99294117647058842.544
958912AF2-182 E
Adder
28.6258823529411824.332
294401BSHIL;1U E
Adder
7.17647058823529356.1
936371AD2-047 C
Adder
3.76235294117647053.198
936461AD2-060 C
Adder
2.2129411764705881.881
933412AC2-154 E
Adder
3.42941176470588262.915
962782AG1-127 E
Adder
3.92470588235294133.336
946671AF1-331 C
Adder
2.01411764705882361.712
293644O22 E1
Adder
11.5517647058823549.819
960281AF2-319 C
Adder
2.0105882352941181.709
960752AF2-366 E
Adder
3.92117647058823553.333
957471AF2-041 C
Adder
17.9576470588235315.264
294763P-046 E
Adder
7.9094117647058826.723
938861AE1-114 C
Adder
3.2964705882352942.802
274805UNIV PK N;1U
50/50
1.9031.903
943592AF1-030 E
Adder
3.54470588235294143.013
943591AF1-030 C
Adder
7.1635294117647066.089
936292AD2-038 E
Adder
13.37529411764705911.369
290021O50 E
Adder
16.24352941176470813.807
937002AD2-134 E
Adder
8.5164705882352937.239
293645O22 E2
Adder
13.2305882352941211.246
960282AF2-319 E
Adder
3.01647058823529422.564
918052AA1-018 E OP
Adder
14.7952941176470612.576
293715O-029 E
Adder
8.1494117647058816.927
910542X3-005 E
Adder
0.53058823529411770.451
939352AE1-166 E
Adder
7.8341176470588236.659
294392P-010 E
Adder
16.63882352941176614.143
959352AF2-226 E
Adder
3.01647058823529422.564
934101AD2-000 1
Adder
4.8788235294117654.147
958492AF2-143 E
Adder
6.4929411764705885.519
942421AE2-255 C
Adder
2.53764705882352942.157
290108LEEDK;1U E
Adder
20.2152941176470617.183
916221Z1-073 E
Adder
6.2070588235294125.276
957472AF2-041 E
Adder
8.9788235294117647.632
959092AF2-200 E
Adder
7.98117647058823556.784
926821AC1-168 C
Adder
0.95764705882352940.814
938862AE1-114 E
Adder
11.244705882352949.558
966092AG1-478 E
Adder
0.44117647058823530.375
274682WAUKEGAN ;7U
Adder
34.8235294117647129.6
942651AE2-281 C
Adder
0.75764705882352950.644
942652AE2-281 E
Adder
4.6529411764705893.955
962691AG1-118 C
Adder
18.6752941176470615.874
962692AG1-118 E
Adder
12.45058823529411810.583
938851AE1-113 C
Adder
6.75.695
272363ESS H440 ; R
Adder
2.21411764705882331.882
959091AF2-200 C
Adder
11.97176470588235410.176
940502AE2-035 E
Adder
2.84588235294117682.419
274814UNIV PK N;0U
50/50
1.8911.891
274807UNIV PK N;3U
50/50
1.9151.915
274816UNIV PK N;YU
50/50
1.9151.915
958011AF2-095 C
Adder
9.557647058823538.124
933411AC2-154 C
Adder
2.10235294117647081.787
274687WILL CNTY;4U
Adder
55.58000000000000547.243
966091AG1-478 C
Adder
1.7552941176470591.492
966441AG1-513 C
Adder
0.430588235294117660.366
959081AF2-199 C
Adder
5.9858823529411775.088
916212CRESCENT ;1U
Adder
4.0470588235294123.44
294410BSHIL;2U E
Adder
7.17647058823529356.1
274810UNIV PK N;6U
50/50
1.9071.907
274812UNIV PK N;8U
50/50
1.8991.899
941552AE2-152 E
Adder
6.5282352941176485.549
958482AF2-142 E
Adder
6.8023529411764715.782
938852AE1-113 E
Adder
23.75647058823529520.193
274890CAYUG;1U E
Adder
11.395294117647069.686
962012AG1-044 E
Adder
0.0529411764705882350.045
925582AC1-033 E
Adder
7.8670588235294126.687
276626AG1-044 E
Adder
0.061176470588235290.052
276675AE2-062 E
Adder
0.134117647058823540.114
920272AA2-123 E
Adder
2.4188235294117652.056
276170Z1-108 E
Adder
2.4670588235294122.097
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.47412.474
WECLTFEXP_WEC->PJM
CLTF
3.2883.288
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.4090.409
SIGELTFEXP_SIGE->PJM
CLTF
0.0150.015
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.23368.233
NYPJM->LTFIMP_NY
CLTF
0.9310.931
TVALTFEXP_TVA->PJM
CLTF
1.1671.167
LAGNLTFEXP_LAGN->PJM
CLTF
2.992.99
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7291.729
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.210.21
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.1721.172
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6070.607
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4090.409
MECLTFEXP_MEC->PJM
CLTF
10.92410.924
O66PJM->LTFIMP_O-066
CMTX_NF
11.09411.094
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243207 CKT 1   /*05DUMONT     765.0 - 05GRNTWN     765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'COMED_P4_112-65-BT3-4___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT4-5___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'COMED_P4-6_116-345-R______SRT-A'
 DISCONNECT BUS 270767                                          /*GOODINGS ;1R 345.0
 DISCONNECT BUS 270769                                          /*GOODINGS ;2R 345.0
 DISCONNECT BUS 275240                                          /*GOODINGS ;1M 138.0
 TRIP BRANCH FROM BUS 270729 TO BUS 271385 TO BUS 275351 CKT 1  /*E FRANKFO; R 345.0 - E FRANKFO; R 138.0 - E FRANKFO;3C  34.5
END
CONTINGENCY 'COMED_P4_116-45-L11614__SRT-A'
 DISCONNECT BUS 270769                             /*GOODINGS ;2R 345.0
 TRIP BRANCH FROM BUS 270667 TO BUS 270665 CKT 1   /*BLUE ISL ;RT 345.0 - BLUE ISL ; R 345.0
 TRIP BRANCH FROM BUS 270667 TO BUS 270927 CKT 1   /*BLUE ISL ;RT 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 270769 TO BUS 270667 CKT 1   /*GOODINGS ;2R 345.0 - BLUE ISL ;RT 345.0
END
CONTINGENCY 'COMED_P4_112-45-BT4-5___SRT-A'
 TRIP BRANCH FROM BUS 270666 TO BUS 270664 CKT 1   /*BLUE ISL ;BT 345.0 - BLUE ISL ; B 345.0
 TRIP BRANCH FROM BUS 270666 TO BUS 270926 CKT 1   /*BLUE ISL ;BT 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 270770 TO BUS 270666 CKT 1   /*GOODINGS ;4B 345.0 - BLUE ISL ;BT 345.0
 TRIP BRANCH FROM BUS 270852 TO BUS 270704 CKT 1   /*PONTIAC  ; B 345.0 - LORETTO  ; B 345.0
END
960680 to 243229 ckt 1
274750 to 255112 ckt 1
270770 to 270766 ckt 1
274804 to 960680 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1CE
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
Base Case
OPAC126.28 %1334.0A1684.5940.22
GD1CE
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
COMED_P1-2_345-L0626__B-R_SRT-A
OPAC116.23 %1479.0B1719.0432.26
GD1CE
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
Base Case
OPAC103.49 %1201.0A1242.8722.74
GD1CE
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
Base Case
OPAC106.45 %1201.0A1278.4214.7
GD1CE
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
COMED_P1-2_345-L11120_R-N_SRT-A
OPAC100.63 %1479.0B1488.315.58
GD1CE
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P1-2_345-L0626__B-R_SRT-A
OPAC126.4 %1479.0B1869.4232.26
GD1CE
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
Base Case
OPAC115.04 %1201.0A1381.5922.74
GD1CE
LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line
COMED_P1-2_345-L15502_B-R_SRT-A-2
OPAC115.83 %1726.0B1999.2696.75
GD1CE
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line
COMED_P1-2_345-L0627__B-R_SRT-A
OPAC108.05 %1656.0B1789.3567.05
GD1CE
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line
Base Case
OPAC103.46 %1334.0A1380.140.22
GD1CE/MEC
QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line
EXT_636600 SUB 39 3 345 636605 MEC CORDOVA3 345 1 _SRT-S
OPAC103.43 %1471.0B1521.5330.94

Details for AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.28 %
Rating:1334.0 MVA
Rating Type:A
MVA to Mitigate:1684.59
MW Contribution:40.22
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.78 %
Rating:1334.0 MVA
Rating Type:A
MVA to Mitigate:1691.31
MW Contribution:40.26
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
293715O-029 E
50/50
15.50715.507
274857BIG SKY ;U1
50/50
0.4550.455
938861AE1-114 C
Adder
4.69058823529411753.987
294763P-046 E
Adder
8.5905882352941177.302
276677AA1-146
50/50
7.4897.489
276676AA2-030 GEN
50/50
6.1886.188
274858BIG SKY ;U2
50/50
0.4550.455
957471AF2-041 C
50/50
97.33797.337
937312AD2-172 E
Adder
3.09058823529411742.627
274859EASYR;U1 E
50/50
19.219.2
937002AD2-134 E
Adder
6.2658823529411765.326
274761LEE CO EC;2U
50/50
2.5422.542
274762LEE CO EC;3U
50/50
2.5422.542
946671AF1-331 C
Adder
1.42000000000000021.207
276156O-029 C
50/50
0.3210.321
276158O-029 C
50/50
0.5780.578
293716O-029 E
50/50
8.5028.502
946152AF1-280 E
50/50
40.21540.215
965931AG1-462 C
50/50
26.7526.75
293771O-035 E
Adder
4.3282352941176473.679
933912AD1-013 E
Adder
1.74588235294117641.484
962012AG1-044 E
50/50
0.1120.112
925582AC1-033 E
Adder
7.3023529411764716.207
295109WESTBROOK E
Adder
3.4694117647058822.949
939061AE1-134 2
50/50
2.9432.943
990901L-005 E
Adder
8.8729411764705887.542
916221Z1-073 E
Adder
4.5670588235294123.882
938862AE1-114 E
Adder
16.0047058823529413.604
276157O-029 C
50/50
0.5780.578
274881WALNUT RG;1U
50/50
1.2251.225
959092AF2-200 E
50/50
43.26143.261
957472AF2-041 E
50/50
48.66948.669
933911AD1-013 C
Adder
1.09294117647058830.929
295111SUBLETTE E
Adder
1.68705882352941171.434
946322AF1-296 E
Adder
26.91882352941176422.881
274860EASYR;U2 E
50/50
19.219.2
927209AC1-214 E2
Adder
2.0517647058823531.744
290051GSG-6; E
Adder
6.48117647058823555.509
274716NELSON EC;1S
50/50
4.844.84
958912AF2-182 E
50/50
60.32260.322
274764LEE CO EC;5U
50/50
2.5482.548
274766LEE CO EC;7U
50/50
2.5122.512
294401BSHIL;1U E
Adder
6.6588235294117655.66
959082AF2-199 E
50/50
16.22316.223
293717O-029 E
50/50
7.8157.815
293516O-009 E
50/50
29.98629.986
946321AF1-296 C
Adder
5.7494117647058824.887
274718NELSON EC;2S
50/50
4.8834.883
927208AC1-214 E1
Adder
2.0517647058823531.744
274717NELSON EC;2C
50/50
6.6856.685
274715NELSON EC;1C
50/50
6.6346.634
274763LEE CO EC;4U
50/50
2.5182.518
274760LEE CO EC;1U
50/50
2.5422.542
274765LEE CO EC;6U
50/50
2.5482.548
966822AG1-553 E
50/50
45.45745.457
294410BSHIL;2U E
Adder
6.6588235294117655.66
916212CRESCENT ;1U
Adder
3.0411764705882352.585
959081AF2-199 C
50/50
32.44632.446
940502AE2-035 E
Adder
3.09058823529411742.627
939051AE1-134 1
50/50
0.4730.473
274767LEE CO EC;8U
50/50
2.5122.512
965932AG1-462 E
50/50
17.83317.833
959091AF2-200 C
50/50
64.89164.891
272363ESS H440 ; R
Adder
1.57764705882352941.341
276626AG1-044 E
50/50
0.1120.112
991092J1477
External Queue
5.500812053680425.50081205368042
955972J1084
External Queue
20.9585704803466820.95857048034668
990947J1432 C
External Queue
4.7147688865661624.714768886566162
990948J1432 E
External Queue
25.50810813903808625.508108139038086
956412J1131
External Queue
10.9796648025512710.97966480255127
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.33663.336
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3650.365
TVALTFEXP_TVA->PJM
CLTF
1.6851.685
LAGNLTFEXP_LAGN->PJM
CLTF
3.5753.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
WECLTFEXP_WEC->PJM
CLTF
0.6580.658
MECLTFEXP_MEC->PJM
CLTF
13.47113.471
O66PJM->LTFIMP_O-066
CMTX_NF
2.3472.347
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.35211.352
NYPJM->LTFIMP_NY
CLTF
0.2040.204
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0730.073
SIGELTFEXP_SIGE->PJM
CLTF
0.0310.031
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.0093.009
CPLELTFEXP_CPLE->PJM
CLTF
0.1330.133
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.1690.169
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0610.061

Details for CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0626__B-R_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0626__B-R_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:116.23 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1719.04
MW Contribution:32.26
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0626__B-R_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:116.75 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1726.77
MW Contribution:32.28
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
293715O-029 E
Adder
9.222352941176477.839
938861AE1-114 C
50/50
6.0246.024
294763P-046 E
50/50
16.81516.815
274856ECOGROVE ;U1
50/50
0.6610.661
957471AF2-041 C
Adder
10.5894117647058839.001
960752AF2-366 E
Adder
3.2717647058823532.781
937312AD2-172 E
50/50
6.056.05
274859EASYR;U1 E
Adder
18.5305882352941215.751
274657BYRON ;2U
50/50
47.35647.356
960751AF2-366 C
Adder
4.9070588235294124.171
937002AD2-134 E
Adder
7.95411764705882356.761
274761LEE CO EC;2U
50/50
2.4532.453
274762LEE CO EC;3U
50/50
2.4532.453
962782AG1-127 E
Adder
3.27529411764705852.784
946671AF1-331 C
Adder
1.85411764705882361.576
293716O-029 E
Adder
5.0564705882352944.298
946152AF1-280 E
Adder
32.2576470588235327.419
965931AG1-462 C
Adder
15.37882352941176513.072
274823ROCKFORD ;21
50/50
7.1147.114
933912AD1-013 E
Adder
2.28117647058823541.939
295111SUBLETTE E
Adder
2.14117647058823521.82
946322AF1-296 E
Adder
16.34705882352941213.895
274860EASYR;U2 E
Adder
18.5305882352941215.751
276590R-018
50/50
0.2570.257
962012AG1-044 E
Adder
0.065882352941176480.056
295109WESTBROOK E
Adder
4.4047058823529423.744
939061AE1-134 2
Adder
1.54235294117647051.311
940502AE2-035 E
50/50
6.056.05
965932AG1-462 E
Adder
10.252941176470598.715
959091AF2-200 C
Adder
7.05882352941176456
962692AG1-118 E
Adder
8.226.987
962691AG1-118 C
Adder
12.33058823529411710.481
272363ESS H440 ; R
Adder
2.04588235294117651.739
916221Z1-073 E
Adder
5.797647058823534.928
938862AE1-114 E
50/50
20.55220.552
274822ROCKFORD ;11
50/50
7.0787.078
959092AF2-200 E
Adder
4.7058823529411774
957472AF2-041 E
Adder
5.2941176470588234.5
290108LEEDK;1U E
Adder
15.72235294117647313.364
274824ROCKFORD ;12
50/50
7.0267.026
274656BYRON ;1U
50/50
48.4248.42
962781AG1-127 C
Adder
4.9211764705882354.183
933911AD1-013 C
Adder
1.4282352941176471.214
290051GSG-6; E
Adder
8.2270588235294136.993
276612AE2-035 C
50/50
0.7160.716
958912AF2-182 E
Adder
48.3858823529411841.128
274764LEE CO EC;5U
50/50
2.4592.459
274766LEE CO EC;7U
50/50
2.4242.424
959082AF2-199 E
Adder
1.76470588235294111.5
293717O-029 E
Adder
4.6470588235294123.95
293516O-009 E
Adder
17.83294117647058715.158
946321AF1-296 C
Adder
3.4917647058823532.968
276611AD2-172 C
50/50
0.7160.716
274763LEE CO EC;4U
50/50
2.432.43
274760LEE CO EC;1U
50/50
2.4532.453
274765LEE CO EC;6U
50/50
2.4592.459
966822AG1-553 E
Adder
26.1352941176470622.215
959081AF2-199 C
Adder
3.52941176470588223
276626AG1-044 E
Adder
0.077647058823529420.066
920272AA2-123 E
Adder
1.20235294117647061.022
990407J1304 G
External Queue
9.3612556457519539.361255645751953
991777J1629 G
External Queue
10.9501476287841810.95014762878418
991092J1477
External Queue
2.92044234275817872.9204423427581787
990727J1377 G
External Queue
16.432250976562516.4322509765625
955972J1084
External Queue
11.01287746429443411.012877464294434
990512J1326 G
External Queue
9.6151580810546889.615158081054688
990947J1432 C
External Queue
2.801840066909792.80184006690979
990948J1432 E
External Queue
15.15867328643798815.158673286437988
956412J1131
External Queue
5.8292260169982915.829226016998291
990117J1214 G
External Queue
38.40942001342773438.409420013427734
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.88759.887
NYPJM->LTFIMP_NY
CLTF
0.2690.269
TVALTFEXP_TVA->PJM
CLTF
0.9250.925
LAGNLTFEXP_LAGN->PJM
CLTF
2.2922.292
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0390.039
MECLTFEXP_MEC->PJM
CLTF
9.849.84
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0850.085
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7576.757
WECLTFEXP_WEC->PJM
CLTF
0.5290.529
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1820.182
O66PJM->LTFIMP_O-066
CMTX_NF
3.1743.174
G-007PJM->LTFIMP_G-007
CMTX_NF
0.4940.494
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0070.007
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.5250.525

Details for CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.49 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1242.87
MW Contribution:22.74
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.66 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1244.97
MW Contribution:22.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
293715O-029 E
Adder
6.6905882352941185.687
938861AE1-114 C
50/50
4.6134.613
294763P-046 E
50/50
13.05813.058
274856ECOGROVE ;U1
50/50
0.5140.514
960752AF2-366 E
Adder
2.6717647058823532.271
937312AD2-172 E
50/50
4.6984.698
274859EASYR;U1 E
Adder
13.01294117647058911.061
274657BYRON ;2U
50/50
32.93832.938
960751AF2-366 C
Adder
4.0082352941176483.407
937002AD2-134 E
Adder
6.2388235294117655.303
274761LEE CO EC;2U
50/50
1.7231.723
274762LEE CO EC;3U
50/50
1.7231.723
962782AG1-127 E
Adder
2.6752941176470592.274
946671AF1-331 C
Adder
1.45764705882352951.239
293716O-029 E
Adder
3.6682352941176473.118
946152AF1-280 E
Adder
22.73647058823529619.326
965931AG1-462 C
Adder
11.004705882352949.354
274823ROCKFORD ;21
50/50
5.6575.657
933912AD1-013 E
Adder
1.79294117647058831.524
295111SUBLETTE E
Adder
1.681.428
946322AF1-296 E
Adder
11.77529411764705910.009
962012AG1-044 E
Adder
0.0482352941176470640.041
295109WESTBROOK E
Adder
3.45411764705882352.936
939061AE1-134 2
Adder
1.10.935
940502AE2-035 E
50/50
4.6984.698
965932AG1-462 E
Adder
7.3364705882352946.236
962692AG1-118 E
Adder
6.777647058823535.761
962691AG1-118 C
Adder
10.1658823529411778.641
272363ESS H440 ; R
Adder
1.60705882352941191.366
916221Z1-073 E
Adder
4.54705882352941253.865
938862AE1-114 E
50/50
15.7415.74
274822ROCKFORD ;11
50/50
5.6285.628
290108LEEDK;1U E
Adder
12.69882352941176510.794
274824ROCKFORD ;12
50/50
5.5875.587
274656BYRON ;1U
50/50
33.633.6
962781AG1-127 C
Adder
4.01882352941176453.416
933911AD1-013 C
Adder
1.12235294117647060.954
274860EASYR;U2 E
Adder
13.01294117647058911.061
276590R-018
50/50
0.2050.205
290051GSG-6; E
Adder
6.4529411764705885.485
276612AE2-035 C
50/50
0.5560.556
958912AF2-182 E
Adder
34.10470588235294528.989
274764LEE CO EC;5U
50/50
1.7271.727
274766LEE CO EC;7U
50/50
1.7021.702
293717O-029 E
Adder
3.3717647058823532.866
293516O-009 E
Adder
12.93647058823529510.996
946321AF1-296 C
Adder
2.51529411764705872.138
276611AD2-172 C
50/50
0.5560.556
274763LEE CO EC;4U
50/50
1.7061.706
274760LEE CO EC;1U
50/50
1.7231.723
274765LEE CO EC;6U
50/50
1.7271.727
966822AG1-553 E
Adder
18.715.895
276626AG1-044 E
Adder
0.056470588235294120.048
990407J1304 G
External Queue
7.0667271614074717.066727161407471
990727J1377 G
External Queue
12.48061370849609412.480613708496094
955972J1084
External Queue
7.95014476776123057.9501447677612305
990512J1326 G
External Queue
7.2312178611755377.231217861175537
990947J1432 C
External Queue
2.031287193298342.03128719329834
990948J1432 E
External Queue
10.98978519439697310.989785194396973
990117J1214 G
External Queue
28.88635635375976628.886356353759766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.8764.876
NYPJM->LTFIMP_NY
CLTF
0.1890.189
TVALTFEXP_TVA->PJM
CLTF
0.670.67
LAGNLTFEXP_LAGN->PJM
CLTF
1.6491.649
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.0480.048
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0240.024
MECLTFEXP_MEC->PJM
CLTF
7.0467.046
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0570.057
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
WECLTFEXP_WEC->PJM
CLTF
0.1810.181
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1270.127
O66PJM->LTFIMP_O-066
CMTX_NF
2.2342.234
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.77141.771
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3480.348
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0030.003
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.3660.366

Details for ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.45 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1278.42
MW Contribution:14.7
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.39 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1277.74
MW Contribution:14.67
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
293715O-029 E
Adder
5.5423529411764714.711
938861AE1-114 C
Adder
2.141.819
294763P-046 E
Adder
4.4788235294117643.807
957471AF2-041 C
50/50
26.37726.377
960752AF2-366 E
Adder
3.6623529411764713.113
937312AD2-172 E
Adder
1.61176470588235321.37
274859EASYR;U1 E
Adder
7.4211764705882356.308
960751AF2-366 C
Adder
5.49294117647058754.669
937002AD2-134 E
Adder
7.6458823529411766.499
943592AF1-030 E
Adder
3.2105882352941182.729
943591AF1-030 C
Adder
6.4905882352941185.517
962782AG1-127 E
Adder
3.66588235294117663.116
946671AF1-331 C
Adder
1.81529411764705871.543
293716O-029 E
Adder
3.0388235294117652.583
946152AF1-280 E
Adder
14.69529411764705912.491
965931AG1-462 C
Adder
8.6917647058823537.388
933912AD1-013 E
Adder
2.2329411764705881.898
295111SUBLETTE E
Adder
2.05764705882352941.749
946322AF1-296 E
Adder
9.0211764705882367.668
274860EASYR;U2 E
Adder
7.4211764705882356.308
943121AE2-341 C
Adder
9.7588235294117668.295
962012AG1-044 E
Adder
0.040.034
274738AURORA EC;3P
50/50
4.3424.342
295109WESTBROOK E
Adder
4.2341176470588243.599
939061AE1-134 2
Adder
0.96941176470588230.824
940502AE2-035 E
Adder
1.61176470588235321.37
965932AG1-462 E
Adder
5.7941176470588234.925
959091AF2-200 C
50/50
17.58417.584
962692AG1-118 E
50/50
12.43312.433
962691AG1-118 C
50/50
18.6518.65
272363ESS H440 ; R
Adder
1.99411764705882361.695
916221Z1-073 E
Adder
5.57176470588235254.736
938862AE1-114 E
Adder
7.3000000000000016.205
959092AF2-200 E
50/50
11.72311.723
957472AF2-041 E
50/50
13.18813.188
290108LEEDK;1U E
Adder
19.04117647058823316.185
276591L-013 2
Adder
2.78823529411764742.37
274740AURORA EC;4P
50/50
4.3424.342
962781AG1-127 C
Adder
5.5082352941176484.682
933911AD1-013 C
Adder
1.39764705882352951.188
290051GSG-6; E
Adder
7.9070588235294126.721
958912AF2-182 E
Adder
22.0423529411764718.736
959082AF2-199 E
50/50
4.3964.396
966442AG1-513 E
Adder
0.408235294117647030.347
293717O-029 E
Adder
2.79294117647058832.374
293516O-009 E
Adder
10.7176470588235299.11
946321AF1-296 C
Adder
1.92705882352941171.638
943122AE2-341 E
Adder
4.7917647058823534.073
966822AG1-553 E
Adder
14.77058823529411812.555
959081AF2-199 C
50/50
8.7928.792
966441AG1-513 C
Adder
0.271764705882352960.231
276626AG1-044 E
Adder
0.0470588235294117640.04
955972J1084
External Queue
7.6018819808959967.601881980895996
G-007PJM->LTFIMP_G-007
CMTX_NF
0.30.3
TVALTFEXP_TVA->PJM
CLTF
0.2960.296
LAGNLTFEXP_LAGN->PJM
CLTF
0.8220.822
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.5222.522
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0620.062
MECLTFEXP_MEC->PJM
CLTF
3.9293.929
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0950.095
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.4658.465
NYPJM->LTFIMP_NY
CLTF
0.1620.162
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1180.118
O66PJM->LTFIMP_O-066
CMTX_NF
1.9231.923
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.030.03
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.3510.351

Details for ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11120_R-N_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L11120_R-N_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.63 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1488.3
MW Contribution:15.58
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L11120_R-N_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.56 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1487.28
MW Contribution:15.55
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
293715O-029 E
Adder
5.8482352941176474.971
938861AE1-114 C
Adder
2.2870588235294121.944
294763P-046 E
Adder
4.8235294117647064.1
957471AF2-041 C
50/50
27.25527.255
960752AF2-366 E
50/50
4.0014.001
937312AD2-172 E
Adder
1.73529411764705891.475
274859EASYR;U1 E
Adder
7.9058823529411776.72
960751AF2-366 C
50/50
6.0026.002
937002AD2-134 E
Adder
8.2976470588235297.053
943592AF1-030 E
50/50
3.6353.635
943591AF1-030 C
50/50
7.3477.347
962782AG1-127 E
50/50
4.0054.005
274872LEE DEKAL;1U
50/50
0.6880.688
946671AF1-331 C
Adder
1.97058823529411781.675
293716O-029 E
Adder
3.20588235294117662.725
946152AF1-280 E
Adder
15.58352941176470613.246
965931AG1-462 C
Adder
9.0964705882352957.732
933912AD1-013 E
Adder
2.42470588235294132.061
962012AG1-044 E
Adder
0.04117647058823530.035
274738AURORA EC;3P
50/50
4.6254.625
295109WESTBROOK E
Adder
4.5941176470588233.905
939061AE1-134 2
Adder
1.01882352941176470.866
940502AE2-035 E
Adder
1.73529411764705891.475
965932AG1-462 E
Adder
6.0635294117647065.154
959091AF2-200 C
50/50
18.1718.17
962692AG1-118 E
50/50
13.55613.556
962691AG1-118 C
50/50
20.33320.333
272363ESS H440 ; R
Adder
2.16470588235294151.84
916221Z1-073 E
Adder
6.0470588235294125.14
938862AE1-114 E
Adder
7.8035294117647066.633
959092AF2-200 E
50/50
12.11412.114
957472AF2-041 E
50/50
13.62813.628
290108LEEDK;1U E
50/50
20.78420.784
276591L-013 2
50/50
3.3053.305
274740AURORA EC;4P
50/50
4.6254.625
962781AG1-127 C
50/50
6.0196.019
933911AD1-013 C
Adder
1.51764705882352961.29
295111SUBLETTE E
Adder
2.2329411764705881.898
946322AF1-296 E
Adder
9.455294117647068.037
274860EASYR;U2 E
Adder
7.9058823529411776.72
943121AE2-341 C
50/50
11.04711.047
290051GSG-6; E
Adder
8.5811764705882347.294
958912AF2-182 E
Adder
23.3741176470588219.868
959082AF2-199 E
50/50
4.5434.543
966442AG1-513 E
Adder
0.5917647058823530.503
293717O-029 E
Adder
2.94705882352941152.505
293516O-009 E
Adder
11.3070588235294139.611
946321AF1-296 C
Adder
2.021.717
943122AE2-341 E
50/50
5.4255.425
966822AG1-553 E
Adder
15.45764705882352913.139
959081AF2-199 C
50/50
9.0859.085
966441AG1-513 C
Adder
0.39411764705882360.335
276626AG1-044 E
Adder
0.0494117647058823560.042
955972J1084
External Queue
8.1039762496948248.103976249694824
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.2666.266
NYPJM->LTFIMP_NY
CLTF
0.1820.182
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1330.133
O66PJM->LTFIMP_O-066
CMTX_NF
2.162.16
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0380.038
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.3940.394
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.5682.568
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0760.076
MECLTFEXP_MEC->PJM
CLTF
4.0164.016
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.1140.114
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3370.337
TVALTFEXP_TVA->PJM
CLTF
0.2870.287
LAGNLTFEXP_LAGN->PJM
CLTF
0.8250.825

Details for GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0626__B-R_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0626__B-R_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.4 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1869.42
MW Contribution:32.26
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0626__B-R_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1877.2
MW Contribution:32.28
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
293715O-029 E
Adder
9.222352941176477.839
938861AE1-114 C
50/50
6.0246.024
294763P-046 E
50/50
16.81516.815
274856ECOGROVE ;U1
50/50
0.6610.661
957471AF2-041 C
Adder
10.5894117647058839.001
960752AF2-366 E
Adder
3.2717647058823532.781
937312AD2-172 E
50/50
6.056.05
274859EASYR;U1 E
Adder
18.5305882352941215.751
274657BYRON ;2U
50/50
47.35647.356
960582AF2-349 E
50/50
148.497148.497
960751AF2-366 C
Adder
4.9070588235294124.171
937002AD2-134 E
Adder
7.95411764705882356.761
274761LEE CO EC;2U
50/50
2.4532.453
274762LEE CO EC;3U
50/50
2.4532.453
962782AG1-127 E
Adder
3.27529411764705852.784
946671AF1-331 C
Adder
1.85411764705882361.576
293716O-029 E
Adder
5.0564705882352944.298
946152AF1-280 E
Adder
32.2576470588235327.419
965931AG1-462 C
Adder
15.37882352941176513.072
274823ROCKFORD ;21
50/50
7.1147.114
933912AD1-013 E
Adder
2.28117647058823541.939
962012AG1-044 E
Adder
0.065882352941176480.056
295109WESTBROOK E
Adder
4.4047058823529423.744
939061AE1-134 2
Adder
1.54235294117647051.311
916221Z1-073 E
Adder
5.797647058823534.928
938862AE1-114 E
50/50
20.55220.552
274822ROCKFORD ;11
50/50
7.0787.078
959092AF2-200 E
Adder
4.7058823529411774
957472AF2-041 E
Adder
5.2941176470588234.5
290108LEEDK;1U E
Adder
15.72235294117647313.364
274824ROCKFORD ;12
50/50
7.0267.026
274656BYRON ;1U
50/50
48.4248.42
962781AG1-127 C
Adder
4.9211764705882354.183
933911AD1-013 C
Adder
1.4282352941176471.214
295111SUBLETTE E
Adder
2.14117647058823521.82
946322AF1-296 E
Adder
16.34705882352941213.895
274860EASYR;U2 E
Adder
18.5305882352941215.751
276590R-018
50/50
0.2570.257
290051GSG-6; E
Adder
8.2270588235294136.993
276612AE2-035 C
50/50
0.7160.716
958912AF2-182 E
Adder
48.3858823529411841.128
274764LEE CO EC;5U
50/50
2.4592.459
959082AF2-199 E
Adder
1.76470588235294111.5
293717O-029 E
Adder
4.6470588235294123.95
293516O-009 E
Adder
17.83294117647058715.158
946321AF1-296 C
Adder
3.4917647058823532.968
276611AD2-172 C
50/50
0.7160.716
274763LEE CO EC;4U
50/50
2.432.43
274760LEE CO EC;1U
50/50
2.4532.453
274765LEE CO EC;6U
50/50
2.4592.459
966822AG1-553 E
Adder
26.1352941176470622.215
959081AF2-199 C
Adder
3.52941176470588223
940502AE2-035 E
50/50
6.056.05
274767LEE CO EC;8U
50/50
2.4242.424
965932AG1-462 E
Adder
10.252941176470598.715
959091AF2-200 C
Adder
7.05882352941176456
962692AG1-118 E
Adder
8.226.987
962691AG1-118 C
Adder
12.33058823529411710.481
272363ESS H440 ; R
Adder
2.04588235294117651.739
920272AA2-123 E
Adder
1.20235294117647061.022
276626AG1-044 E
Adder
0.077647058823529420.066
990407J1304 G
External Queue
9.3612556457519539.361255645751953
991777J1629 G
External Queue
10.9501476287841810.95014762878418
991092J1477
External Queue
2.92044234275817872.9204423427581787
990727J1377 G
External Queue
16.432250976562516.4322509765625
955972J1084
External Queue
11.01287746429443411.012877464294434
990512J1326 G
External Queue
9.6151580810546889.615158081054688
990947J1432 C
External Queue
2.801840066909792.80184006690979
990948J1432 E
External Queue
15.15867328643798815.158673286437988
956412J1131
External Queue
5.8292260169982915.829226016998291
990117J1214 G
External Queue
38.40942001342773438.409420013427734
G-007PJM->LTFIMP_G-007
CMTX_NF
0.4940.494
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0070.007
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.5250.525
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7576.757
WECLTFEXP_WEC->PJM
CLTF
0.5290.529
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1820.182
O66PJM->LTFIMP_O-066
CMTX_NF
3.1743.174
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.88759.887
NYPJM->LTFIMP_NY
CLTF
0.2690.269
TVALTFEXP_TVA->PJM
CLTF
0.9250.925
LAGNLTFEXP_LAGN->PJM
CLTF
2.2922.292
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0390.039
MECLTFEXP_MEC->PJM
CLTF
9.849.84
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0850.085

Details for GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.04 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1381.59
MW Contribution:22.74
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.21 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1383.73
MW Contribution:22.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
293715O-029 E
Adder
6.6905882352941185.687
938861AE1-114 C
50/50
4.6134.613
294763P-046 E
50/50
13.05813.058
274856ECOGROVE ;U1
50/50
0.5140.514
960752AF2-366 E
Adder
2.6717647058823532.271
937312AD2-172 E
50/50
4.6984.698
274859EASYR;U1 E
Adder
13.01294117647058911.061
274657BYRON ;2U
50/50
32.93832.938
960582AF2-349 E
50/50
137.351137.351
960751AF2-366 C
Adder
4.0082352941176483.407
937002AD2-134 E
Adder
6.2388235294117655.303
274761LEE CO EC;2U
50/50
1.7231.723
274762LEE CO EC;3U
50/50
1.7231.723
962782AG1-127 E
Adder
2.6752941176470592.274
946671AF1-331 C
Adder
1.45764705882352951.239
293716O-029 E
Adder
3.6682352941176473.118
946152AF1-280 E
Adder
22.73647058823529619.326
965931AG1-462 C
Adder
11.004705882352949.354
274823ROCKFORD ;21
50/50
5.6575.657
933912AD1-013 E
Adder
1.79294117647058831.524
295111SUBLETTE E
Adder
1.681.428
946322AF1-296 E
Adder
11.77529411764705910.009
274860EASYR;U2 E
Adder
13.01294117647058911.061
276590R-018
50/50
0.2050.205
962012AG1-044 E
Adder
0.0482352941176470640.041
295109WESTBROOK E
Adder
3.45411764705882352.936
939061AE1-134 2
Adder
1.10.935
940502AE2-035 E
50/50
4.6984.698
965932AG1-462 E
Adder
7.3364705882352946.236
962692AG1-118 E
Adder
6.777647058823535.761
962691AG1-118 C
Adder
10.1658823529411778.641
272363ESS H440 ; R
Adder
1.60705882352941191.366
916221Z1-073 E
Adder
4.54705882352941253.865
938862AE1-114 E
50/50
15.7415.74
274822ROCKFORD ;11
50/50
5.6285.628
290108LEEDK;1U E
Adder
12.69882352941176510.794
274824ROCKFORD ;12
50/50
5.5875.587
274656BYRON ;1U
50/50
33.633.6
962781AG1-127 C
Adder
4.01882352941176453.416
933911AD1-013 C
Adder
1.12235294117647060.954
290051GSG-6; E
Adder
6.4529411764705885.485
276612AE2-035 C
50/50
0.5560.556
958912AF2-182 E
Adder
34.10470588235294528.989
274764LEE CO EC;5U
50/50
1.7271.727
274766LEE CO EC;7U
50/50
1.7021.702
293717O-029 E
Adder
3.3717647058823532.866
293516O-009 E
Adder
12.93647058823529510.996
946321AF1-296 C
Adder
2.51529411764705872.138
276611AD2-172 C
50/50
0.5560.556
274763LEE CO EC;4U
50/50
1.7061.706
274760LEE CO EC;1U
50/50
1.7231.723
274765LEE CO EC;6U
50/50
1.7271.727
966822AG1-553 E
Adder
18.715.895
276626AG1-044 E
Adder
0.056470588235294120.048
990407J1304 G
External Queue
7.0667271614074717.066727161407471
990727J1377 G
External Queue
12.48061370849609412.480613708496094
955972J1084
External Queue
7.95014476776123057.9501447677612305
990512J1326 G
External Queue
7.2312178611755377.231217861175537
990947J1432 C
External Queue
2.031287193298342.03128719329834
990948J1432 E
External Queue
10.98978519439697310.989785194396973
990117J1214 G
External Queue
28.88635635375976628.886356353759766
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.0480.048
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0240.024
MECLTFEXP_MEC->PJM
CLTF
7.0467.046
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0570.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.8764.876
NYPJM->LTFIMP_NY
CLTF
0.1890.189
TVALTFEXP_TVA->PJM
CLTF
0.670.67
LAGNLTFEXP_LAGN->PJM
CLTF
1.6491.649
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.77141.771
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3480.348
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0030.003
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.3660.366
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
WECLTFEXP_WEC->PJM
CLTF
0.1810.181
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1270.127
O66PJM->LTFIMP_O-066
CMTX_NF
2.2342.234

Details for LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L15502_B-R_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.83 %
Rating:1726.0 MVA
Rating Type:B
MVA to Mitigate:1999.26
MW Contribution:96.75
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L15502_B-R_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:116.25 %
Rating:1726.0 MVA
Rating Type:B
MVA to Mitigate:2006.52
MW Contribution:96.86
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
293715O-029 E
50/50
23.28823.288
274857BIG SKY ;U1
50/50
1.3131.313
276677AA1-146
50/50
11.89511.895
276676AA2-030 GEN
50/50
9.8299.829
274858BIG SKY ;U2
50/50
1.3131.313
957471AF2-041 C
50/50
68.94768.947
274859EASYR;U1 E
50/50
55.39355.393
274761LEE CO EC;2U
50/50
7.3337.333
274762LEE CO EC;3U
50/50
7.3337.333
276156O-029 C
50/50
0.4810.481
276158O-029 C
50/50
0.8680.868
293716O-029 E
50/50
12.76912.769
946152AF1-280 E
50/50
96.75496.754
965931AG1-462 C
50/50
39.84139.841
293771O-035 E
Adder
6.7470588235294135.735
962012AG1-044 E
50/50
0.1680.168
925582AC1-033 E
Adder
11.1917647058823539.513
939061AE1-134 2
50/50
4.6744.674
990901L-005 E
Adder
13.6529411764705911.605
276157O-029 C
50/50
0.8680.868
274881WALNUT RG;1U
50/50
1.8391.839
959092AF2-200 E
50/50
30.64330.643
957472AF2-041 E
50/50
34.47434.474
946322AF1-296 E
Adder
38.9564705882352933.113
274860EASYR;U2 E
50/50
55.39355.393
927209AC1-214 E2
Adder
3.19882352941176462.719
274716NELSON EC;1S
50/50
7.6887.688
958912AF2-182 E
50/50
145.131145.131
274764LEE CO EC;5U
50/50
7.357.35
274766LEE CO EC;7U
50/50
7.2477.247
294401BSHIL;1U E
Adder
10.2058823529411788.675
959082AF2-199 E
50/50
11.49111.491
293717O-029 E
50/50
11.73611.736
293516O-009 E
50/50
45.03145.031
946321AF1-296 C
Adder
8.3211764705882367.073
274718NELSON EC;2S
50/50
7.7577.757
927208AC1-214 E1
Adder
3.19882352941176462.719
274717NELSON EC;2C
50/50
10.61810.618
274715NELSON EC;1C
50/50
10.53710.537
274763LEE CO EC;4U
50/50
7.2637.263
274760LEE CO EC;1U
50/50
7.3337.333
274765LEE CO EC;6U
50/50
7.357.35
966822AG1-553 E
50/50
67.70467.704
294410BSHIL;2U E
Adder
10.2058823529411788.675
916212CRESCENT ;1U
Adder
4.744.029
959081AF2-199 C
50/50
22.98222.982
939051AE1-134 1
50/50
0.7510.751
274767LEE CO EC;8U
50/50
7.2477.247
965932AG1-462 E
50/50
26.56126.561
959091AF2-200 C
50/50
45.96545.965
276626AG1-044 E
50/50
0.1680.168
991092J1477
External Queue
9.0879898071289069.087989807128906
955972J1084
External Queue
34.5655326843261734.56553268432617
990512J1326 G
External Queue
-7.79633092880249-7.79633092880249
990947J1432 C
External Queue
7.2057147026062017.205714702606201
990948J1432 E
External Queue
38.98476409912109438.984764099121094
956412J1131
External Queue
18.13969993591308618.139699935913086
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.40315.403
NYPJM->LTFIMP_NY
CLTF
0.0620.062
MECLTFEXP_MEC->PJM
CLTF
15.40315.403
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.2140.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.676.67
CPLELTFEXP_CPLE->PJM
CLTF
0.450.45
SIGELTFEXP_SIGE->PJM
CLTF
0.0740.074
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.1540.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.5464.546
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.0228.02
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0920.092
TVALTFEXP_TVA->PJM
CLTF
2.392.39
O66PJM->LTFIMP_O-066
CMTX_NF
0.5990.599

Details for NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0627__B-R_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0627__B-R_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.05 %
Rating:1656.0 MVA
Rating Type:B
MVA to Mitigate:1789.35
MW Contribution:67.05
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0627__B-R_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.65 %
Rating:1656.0 MVA
Rating Type:B
MVA to Mitigate:1799.28
MW Contribution:67.16
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
293715O-029 E
50/50
21.121.1
274857BIG SKY ;U1
50/50
0.8330.833
938861AE1-114 C
Adder
4.90117647058823554.166
294763P-046 E
Adder
6.2611764705882365.322
276677AA1-146
50/50
10.4110.41
276676AA2-030 GEN
50/50
8.6028.602
274858BIG SKY ;U2
50/50
0.8330.833
937312AD2-172 E
Adder
2.25294117647058821.915
274859EASYR;U1 E
50/50
35.1335.13
937002AD2-134 E
Adder
7.2141176470588236.132
274761LEE CO EC;2U
50/50
4.6514.651
274762LEE CO EC;3U
50/50
4.6514.651
946671AF1-331 C
Adder
1.621.377
276156O-029 C
50/50
0.4360.436
276158O-029 C
50/50
0.7860.786
293716O-029 E
50/50
11.56911.569
946152AF1-280 E
50/50
67.04767.047
965931AG1-462 C
50/50
36.28536.285
293771O-035 E
Adder
5.9729411764705885.077
933912AD1-013 E
Adder
1.99294117647058821.694
962012AG1-044 E
50/50
0.1520.152
925582AC1-033 E
Adder
10.0117647058823538.51
295109WESTBROOK E
Adder
3.99411764705882363.395
939061AE1-134 2
50/50
4.0914.091
990901L-005 E
Adder
12.1847058823529410.357
916221Z1-073 E
Adder
5.257647058823534.469
938862AE1-114 E
Adder
16.7223529411764714.214
276157O-029 C
50/50
0.7860.786
274881WALNUT RG;1U
50/50
1.6671.667
933911AD1-013 C
Adder
1.24705882352941181.06
295111SUBLETTE E
Adder
1.94235294117647061.651
946322AF1-296 E
Adder
36.12941176470588530.71
274860EASYR;U2 E
50/50
35.1335.13
927209AC1-214 E2
Adder
2.8317647058823532.407
290051GSG-6; E
Adder
7.4611764705882356.342
274716NELSON EC;1S
50/50
6.7286.728
958912AF2-182 E
50/50
100.57100.57
274764LEE CO EC;5U
50/50
4.6614.661
274766LEE CO EC;7U
50/50
4.5964.596
294401BSHIL;1U E
Adder
9.1305882352941187.761
293717O-029 E
50/50
10.63310.633
293516O-009 E
50/50
40.840.8
946321AF1-296 C
Adder
7.71764705882352956.56
274718NELSON EC;2S
50/50
6.7886.788
927208AC1-214 E1
Adder
2.8317647058823532.407
274717NELSON EC;2C
50/50
9.2929.292
274715NELSON EC;1C
50/50
9.2219.221
274763LEE CO EC;4U
50/50
4.6064.606
274760LEE CO EC;1U
50/50
4.6514.651
274765LEE CO EC;6U
50/50
4.6614.661
966822AG1-553 E
50/50
61.66161.661
294410BSHIL;2U E
Adder
9.1305882352941187.761
916212CRESCENT ;1U
Adder
4.1964705882352953.567
940502AE2-035 E
Adder
2.25294117647058821.915
939051AE1-134 1
50/50
0.6570.657
274767LEE CO EC;8U
50/50
4.5964.596
965932AG1-462 E
50/50
24.1924.19
272363ESS H440 ; R
Adder
1.80352941176470581.533
276626AG1-044 E
50/50
0.1520.152
991092J1477
External Queue
7.7651863098144537.765186309814453
955972J1084
External Queue
29.56552124023437529.565521240234375
990947J1432 C
External Queue
6.457697391510016.45769739151001
990948J1432 E
External Queue
34.9377975463867234.93779754638672
956412J1131
External Queue
15.49937438964843815.499374389648438
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.8234.823
CPLELTFEXP_CPLE->PJM
CLTF
0.2660.266
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0090.009
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.1250.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.88914.889
NYPJM->LTFIMP_NY
CLTF
0.1940.194
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0260.026
SIGELTFEXP_SIGE->PJM
CLTF
0.0510.051
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.43163.431
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3420.342
TVALTFEXP_TVA->PJM
CLTF
2.2452.245
LAGNLTFEXP_LAGN->PJM
CLTF
4.5854.585
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0160.016
MECLTFEXP_MEC->PJM
CLTF
16.69316.693
O66PJM->LTFIMP_O-066
CMTX_NF
2.2012.201

Details for NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.46 %
Rating:1334.0 MVA
Rating Type:A
MVA to Mitigate:1380.1
MW Contribution:40.22
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.95 %
Rating:1334.0 MVA
Rating Type:A
MVA to Mitigate:1386.65
MW Contribution:40.26
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
293715O-029 E
50/50
15.50715.507
274857BIG SKY ;U1
50/50
0.4550.455
938861AE1-114 C
Adder
4.69058823529411753.987
294763P-046 E
Adder
8.5905882352941177.302
276677AA1-146
50/50
7.4897.489
276676AA2-030 GEN
50/50
6.1886.188
274858BIG SKY ;U2
50/50
0.4550.455
937312AD2-172 E
Adder
3.09058823529411742.627
274859EASYR;U1 E
50/50
19.219.2
937002AD2-134 E
Adder
6.2658823529411765.326
274761LEE CO EC;2U
50/50
2.5422.542
274762LEE CO EC;3U
50/50
2.5422.542
946671AF1-331 C
Adder
1.42000000000000021.207
276156O-029 C
50/50
0.3210.321
276158O-029 C
50/50
0.5780.578
293716O-029 E
50/50
8.5028.502
946152AF1-280 E
50/50
40.21540.215
965931AG1-462 C
50/50
26.7526.75
293771O-035 E
Adder
4.3282352941176473.679
933912AD1-013 E
Adder
1.74588235294117641.484
962012AG1-044 E
50/50
0.1120.112
925582AC1-033 E
Adder
7.3023529411764716.207
295109WESTBROOK E
Adder
3.4694117647058822.949
939061AE1-134 2
50/50
2.9432.943
990901L-005 E
Adder
8.8729411764705887.542
916221Z1-073 E
Adder
4.5670588235294123.882
938862AE1-114 E
Adder
16.0047058823529413.604
276157O-029 C
50/50
0.5780.578
274881WALNUT RG;1U
50/50
1.2251.225
933911AD1-013 C
Adder
1.09294117647058830.929
295111SUBLETTE E
Adder
1.68705882352941171.434
946322AF1-296 E
Adder
26.91882352941176422.881
274860EASYR;U2 E
50/50
19.219.2
927209AC1-214 E2
Adder
2.0517647058823531.744
290051GSG-6; E
Adder
6.48117647058823555.509
274716NELSON EC;1S
50/50
4.844.84
958912AF2-182 E
50/50
60.32260.322
274764LEE CO EC;5U
50/50
2.5482.548
274766LEE CO EC;7U
50/50
2.5122.512
294401BSHIL;1U E
Adder
6.6588235294117655.66
293717O-029 E
50/50
7.8157.815
293516O-009 E
50/50
29.98629.986
946321AF1-296 C
Adder
5.7494117647058824.887
274718NELSON EC;2S
50/50
4.8834.883
927208AC1-214 E1
Adder
2.0517647058823531.744
274717NELSON EC;2C
50/50
6.6856.685
940502AE2-035 E
Adder
3.09058823529411742.627
939051AE1-134 1
50/50
0.4730.473
274767LEE CO EC;8U
50/50
2.5122.512
965932AG1-462 E
50/50
17.83317.833
272363ESS H440 ; R
Adder
1.57764705882352941.341
274715NELSON EC;1C
50/50
6.6346.634
274763LEE CO EC;4U
50/50
2.5182.518
274760LEE CO EC;1U
50/50
2.5422.542
274765LEE CO EC;6U
50/50
2.5482.548
966822AG1-553 E
50/50
45.45745.457
294410BSHIL;2U E
Adder
6.6588235294117655.66
916212CRESCENT ;1U
Adder
3.0411764705882352.585
276626AG1-044 E
50/50
0.1120.112
991092J1477
External Queue
5.500812053680425.50081205368042
955972J1084
External Queue
20.9585704803466820.95857048034668
990947J1432 C
External Queue
4.7147688865661624.714768886566162
990948J1432 E
External Queue
25.50810813903808625.508108139038086
956412J1131
External Queue
10.9796648025512710.97966480255127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.35211.352
NYPJM->LTFIMP_NY
CLTF
0.2040.204
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0730.073
SIGELTFEXP_SIGE->PJM
CLTF
0.0310.031
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.0093.009
CPLELTFEXP_CPLE->PJM
CLTF
0.1330.133
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.1690.169
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0610.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
WECLTFEXP_WEC->PJM
CLTF
0.6580.658
MECLTFEXP_MEC->PJM
CLTF
13.47113.471
O66PJM->LTFIMP_O-066
CMTX_NF
2.3472.347
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.33663.336
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3650.365
TVALTFEXP_TVA->PJM
CLTF
1.6851.685
LAGNLTFEXP_LAGN->PJM
CLTF
3.5753.575

Details for QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_636600 SUB 39 3 345 636605 MEC CORDOVA3 345 1 _SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/MEC
Facility Description:
QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line
Contingency Name:
EXT_636600 SUB 39 3 345 636605 MEC CORDOVA3 345 1 _SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.43 %
Rating:1471.0 MVA
Rating Type:B
MVA to Mitigate:1521.53
MW Contribution:30.94
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE/MEC
Facility Description:
QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line
Contingency Name:
EXT_636600 SUB 39 3 345 636605 MEC CORDOVA3 345 1 _SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.47 %
Rating:1471.0 MVA
Rating Type:B
MVA to Mitigate:1522.0
MW Contribution:30.96
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
293715O-029 E
Adder
9.7658823529411768.301
938861AE1-114 C
Adder
3.86588235294117683.286
294763P-046 E
Adder
7.8470588235294126.67
276677AA1-146
50/50
5.4945.494
276676AA2-030 GEN
50/50
4.544.54
957471AF2-041 C
Adder
21.40705882352941518.196
960752AF2-366 E
Adder
2.69058823529411752.287
937312AD2-172 E
Adder
2.8235294117647062.4
274859EASYR;U1 E
Adder
15.17411764705882312.898
274700CORDOVA ;2C
50/50
7.5677.567
274699CORDOVA ;1C
50/50
7.5677.567
960582AF2-349 E
Adder
21.9705882352941218.675
960751AF2-366 C
Adder
4.0352941176470593.43
937002AD2-134 E
Adder
7.6988235294117646.544
274761LEE CO EC;2U
50/50
2.0092.009
274762LEE CO EC;3U
50/50
2.0092.009
962782AG1-127 E
Adder
2.69294117647058862.289
946671AF1-331 C
Adder
1.79294117647058831.524
293716O-029 E
Adder
5.3541176470588244.551
946152AF1-280 E
50/50
30.9430.94
965931AG1-462 C
50/50
44.23144.231
933912AD1-013 E
Adder
2.20588235294117661.875
962012AG1-044 E
Adder
0.076470588235294120.065
295109WESTBROOK E
Adder
4.2635294117647063.624
939061AE1-134 2
50/50
2.1592.159
916221Z1-073 E
Adder
5.61176470588235254.77
938862AE1-114 E
Adder
13.19176470588235311.213
274701CORDOVA ;1S
50/50
8.5138.513
959092AF2-200 E
Adder
9.5141176470588238.087
957472AF2-041 E
Adder
10.7035294117647079.098
290108LEEDK;1U E
Adder
14.94352941176470612.702
962781AG1-127 C
Adder
4.0470588235294123.44
933911AD1-013 C
Adder
1.38117647058823521.174
295111SUBLETTE E
Adder
2.07294117647058851.762
946322AF1-296 E
Adder
10.1752941176470578.649
274860EASYR;U2 E
Adder
15.17411764705882312.898
274662QUAD CITI;1U
50/50
43.85643.856
290051GSG-6; E
Adder
7.9635294117647066.769
274716NELSON EC;1S
50/50
3.5513.551
958912AF2-182 E
50/50
46.4146.41
274764LEE CO EC;5U
50/50
2.0142.014
959082AF2-199 E
Adder
3.5682352941176473.033
293717O-029 E
Adder
4.9211764705882354.183
293516O-009 E
Adder
18.88352941176470516.051
946321AF1-296 C
Adder
2.1729411764705881.847
274718NELSON EC;2S
50/50
3.5833.583
274663QUAD CITI;2U
50/50
43.32643.326
940502AE2-035 E
Adder
2.8235294117647062.4
939051AE1-134 1
50/50
0.3470.347
965932AG1-462 E
50/50
29.48729.487
959091AF2-200 C
Adder
14.27058823529411812.13
962692AG1-118 E
Adder
8.1858823529411766.958
962691AG1-118 C
Adder
12.27882352941176510.437
272363ESS H440 ; R
Adder
1.97882352941176461.682
274717NELSON EC;2C
50/50
4.9044.904
274715NELSON EC;1C
50/50
4.8674.867
274763LEE CO EC;4U
50/50
1.991.99
274760LEE CO EC;1U
50/50
2.0092.009
274765LEE CO EC;6U
50/50
2.0142.014
966822AG1-553 E
50/50
75.16475.164
959081AF2-199 C
Adder
7.1352941176470596.065
276170Z1-108 E
Adder
1.22941176470588221.045
276626AG1-044 E
Adder
0.090588235294117650.077
920272AA2-123 E
Adder
1.53647058823529431.306
990407J1304 G
External Queue
5.6877913475036625.687791347503662
991777J1629 G
External Queue
11.71470451354980511.714704513549805
991092J1477
External Queue
-14.100622177124023-14.100622177124023
990727J1377 G
External Queue
8.9315605163574228.931560516357422
955972J1084
External Queue
42.9220466613769542.92204666137695
990512J1326 G
External Queue
5.8924369812011725.892436981201172
990947J1432 C
External Queue
7.8979654312133797.897965431213379
990948J1432 E
External Queue
42.73001861572265642.730018615722656
990117J1214 G
External Queue
23.5383644104003923.53836441040039
NYPJM->LTFIMP_NY
CLTF
0.5220.522
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.5880.588
O66PJM->LTFIMP_O-066
CMTX_NF
6.5076.507
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
7.8377.837
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6860.686
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
3.3263.326
WECLTFEXP_WEC->PJM
CLTF
1.1391.139
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
10.87110.871
MDUPJM->LTFIMP_MDU
CLTF
0.5030.503
G-007PJM->LTFIMP_G-007
CMTX_NF
1.0161.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.9270.927
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.2052.205
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
1.1491.149
CONTINGENCY 'COMED_P1-2_345-L0626__B-R_SRT-A'
 TRIP BRANCH FROM BUS 270678 TO BUS 270916 CKT 1   /*BYRON    ; B 345.0 - WAYNE    ; B 345.0
END
CONTINGENCY 'COMED_P1-2_345-L11120_R-N_SRT-A'
 MOVE 100 PERCENT LOAD FROM BUS 270749 TO BUS 270751   /*ESS W407M; R 345.0 - ESS W407M;9T 345.0
 TRIP BRANCH FROM BUS 270733 TO BUS 270747 CKT 1       /*ELECT JCT;3R 345.0 - ESS W407K;0T 345.0
 TRIP BRANCH FROM BUS 270747 TO BUS 270753 CKT 1       /*ESS W407K;0T 345.0 - ESS W407M;0T 345.0
 TRIP BRANCH FROM BUS 270753 TO BUS 270749 CKT 1       /*ESS W407M;0T 345.0 - ESS W407M; R 345.0
 TRIP BRANCH FROM BUS 270753 TO BUS 270813 CKT 1       /*ESS W407M;0T 345.0 - LOMBARD  ; R 345.0
END
CONTINGENCY 'COMED_P1-2_345-L15502_B-R_SRT-A-2'
 TRIP BRANCH FROM BUS 957470 TO BUS 270730 CKT 1   /*AF2-041 TP   345.0 - ELECT JCT; B 345.0
END
CONTINGENCY 'COMED_P1-2_345-L0627__B-R_SRT-A'
 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1   /*LEE CO EC;BP 345.0 - BYRON    ; B 345.0
END
CONTINGENCY 'EXT_636600 SUB 39 3 345 636605 MEC CORDOVA3 345 1 _SRT-S'
 OPEN BRANCH FROM BUS 636600 TO BUS 636605 CKT 1   /*SUB 39 3     345.0 - MEC CORDOVA3 345.0
END
957470 to 270730 ckt 1
270694 to 276670 ckt 1
270730 to 270812 ckt 1
276670 to 270883 ckt 1
274768 to 270678 ckt 1
270828 to 957470 ckt 1
270866 to 636610 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Base Case
OPAC112.52 %1075.0A1209.6114.84
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Base Case
OPAC114.84 %1091.0A1252.9515.41

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.52 %
Rating:1075.0 MVA
Rating Type:A
MVA to Mitigate:1209.61
MW Contribution:14.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960282AF2-319 E
Adder
2.70941176470588242.303
293645O22 E2
Adder
11.88588235294117710.103
918052AA1-018 E OP
Adder
11.3482352941176489.646
293715O-029 E
Adder
6.3811764705882365.424
274724RIVER EC ;11
50/50
3.9023.902
957372AF2-031 E
50/50
1.7751.775
293644O22 E1
Adder
10.3776470588235298.821
960281AF2-319 C
Adder
1.80588235294117651.535
960752AF2-366 E
Adder
2.98470588235294132.537
957471AF2-041 C
Adder
13.84352941176470611.767
294763P-046 E
Adder
6.13764705882352955.217
938861AE1-114 C
Adder
2.562.176
957371AF2-031 C
50/50
1.1831.183
960591AF2-350 C
Adder
6.05.1
960592AF2-350 E
Adder
4.03.4
275149KELLYCK ;1E
Adder
14.00117647058823611.901
934722AD1-100 E
Adder
60.7764705882352951.66
960751AF2-366 C
Adder
4.4776470588235293.806
942422AE2-255 E
Adder
6.1670588235294125.242
960582AF2-349 E
Adder
23.60470588235294220.064
937312AD2-172 E
Adder
2.20823529411764731.877
274859EASYR;U1 E
Adder
7.82352941176470656.65
943592AF1-030 E
Adder
2.6305882352941182.236
943591AF1-030 C
Adder
5.3176470588235294.52
936292AD2-038 E
Adder
10.4164705882352948.854
290021O50 E
Adder
13.1552941176470611.182
937002AD2-134 E
Adder
6.5247058823529425.546
274794SE CHICAG;1U
50/50
5.4655.465
936371AD2-047 C
Adder
3.40000000000000042.89
933412AC2-154 E
Adder
3.09999999999999962.635
936461AD2-060 C
Adder
2.01.7
962782AG1-127 E
Adder
2.9882352941176472.54
946671AF1-331 C
Adder
1.54235294117647051.311
959351AF2-226 C
Adder
1.80588235294117651.535
958491AF2-143 C
Adder
7.5847058823529416.447
933912AD1-013 E
Adder
1.89647058823529441.612
946152AF1-280 E
Adder
14.84352941176470812.617
293716O-029 E
Adder
3.4988235294117652.974
293771O-035 E
Adder
4.5764705882352953.89
961501AF2-441 C
Adder
10.915294117647069.278
293519PILOT HIL;1E
Adder
14.00117647058823611.901
939351AE1-166 C
Adder
6.7717647058823545.756
274675JOLIET 29;7U
Adder
49.9447058823529542.453
274674JOLIET 9 ;6U
Adder
25.73058823529411821.871
293061N-015 E
Adder
9.8294117647058838.355
943121AE2-341 C
Adder
7.99529411764705966.796
939321AE1-163 C
Adder
4.1294117647058823.51
295111SUBLETTE E
Adder
1.75647058823529421.493
274860EASYR;U2 E
Adder
7.82352941176470656.65
927209AC1-214 E2
Adder
2.16941176470588241.844
274792SE CHICAG;9U
50/50
5.4655.465
941552AE2-152 E
Adder
5.2094117647058834.428
958482AF2-142 E
Adder
5.21764705882352954.435
938852AE1-113 E
Adder
19.2416.354
274890CAYUG;1U E
Adder
9.1035294117647067.738
962012AG1-044 E
Adder
0.04117647058823530.035
925582AC1-033 E
Adder
2.2152941176470591.883
941551AE2-152 C
Adder
7.8141176470588246.642
274676JOLIET 29;8U
Adder
49.9529411764705942.46
958481AF2-142 C
Adder
7.8258823529411776.652
957332AF2-027 E
Adder
2.4741176470588242.103
274891CAYUG;2U E
Adder
9.1035294117647067.738
926822AC1-168 E
Adder
5.0564705882352944.298
957331AF2-027 C
Adder
1.64941176470588241.402
936511AD2-066 C
Adder
5.6788235294117654.827
936512AD2-066 E
Adder
3.78588235294117673.218
295109WESTBROOK E
Adder
3.61294117647058853.071
939061AE1-134 2
Adder
0.89294117647058820.759
274790SE CHICAG;7U
50/50
5.5385.538
274791SE CHICAG;8U
50/50
5.5385.538
274789SE CHICAG;6U
50/50
5.5385.538
966092AG1-478 E
Adder
0.36941176470588240.314
274682WAUKEGAN ;7U
Adder
27.29294117647059223.199
962692AG1-118 E
Adder
9.4717647058823548.051
962691AG1-118 C
Adder
14.20823529411764812.077
942652AE2-281 E
Adder
3.6235294117647063.08
942651AE2-281 C
Adder
0.58941176470588240.501
938851AE1-113 C
Adder
5.4270588235294124.613
272363ESS H440 ; R
Adder
1.69647058823529421.442
959091AF2-200 C
Adder
9.2294117647058827.845
940502AE2-035 E
Adder
2.20823529411764731.877
910542X3-005 E
Adder
0.71294117647058820.606
939352AE1-166 E
Adder
6.2517647058823535.314
294392P-010 E
Adder
12.48352941176470710.611
934101AD2-000 1
Adder
3.68941176470588243.136
959352AF2-226 E
Adder
2.70941176470588242.303
958492AF2-143 E
Adder
5.0564705882352944.298
290108LEEDK;1U E
Adder
15.41176470588235313.1
942421AE2-255 C
Adder
2.0552941176470591.747
916221Z1-073 E
Adder
4.75529411764705844.042
959092AF2-200 E
Adder
6.1529411764705895.23
957472AF2-041 E
Adder
6.9211764705882355.883
938862AE1-114 E
Adder
8.7329411764705887.423
926821AC1-168 C
Adder
0.75294117647058820.64
274795SE CHICAG;2U
Adder
5.464705882352944.645
274793SE CHICAG;0U
Adder
5.464705882352944.645
936372AD2-047 E
Adder
16.614.11
276591L-013 2
Adder
2.36235294117647052.008
962781AG1-127 C
Adder
4.4894117647058823.816
933911AD1-013 C
Adder
1.18705882352941171.009
961502AF2-441 E
Adder
16.37411764705882413.918
943122AE2-341 E
Adder
3.9258823529411773.337
939322AE1-163 E
Adder
25.36588235294117821.561
293717O-029 E
Adder
3.2152941176470592.733
958012AF2-095 E
Adder
5.764.896
934111AD2-000 2
Adder
4.077647058823533.466
966442AG1-513 E
Adder
0.48941176470588230.416
274683WAUKEGAN ;8U
Adder
29.42352941176470825.01
290051GSG-6; E
Adder
6.7482352941176475.736
959082AF2-199 E
Adder
2.3070588235294121.961
958912AF2-182 E
Adder
22.26470588235294218.925
293516O-009 E
Adder
12.33882352941176410.488
927208AC1-214 E1
Adder
2.16941176470588241.844
274788SE CHICAG;5U
50/50
5.5385.538
958011AF2-095 C
Adder
8.6411764705882357.345
933411AC2-154 C
Adder
1.90000000000000011.615
274687WILL CNTY;4U
Adder
48.5929411764705941.304
966091AG1-478 C
Adder
1.46941176470588241.249
966441AG1-513 C
Adder
0.32705882352941180.278
959081AF2-199 C
Adder
4.6141176470588243.922
916212CRESCENT ;1U
Adder
3.2152941176470592.733
276170Z1-108 E
Adder
1.9070588235294121.621
276626AG1-044 E
Adder
0.0482352941176470640.041
276675AE2-062 E
Adder
0.107058823529411760.091
920272AA2-123 E
Adder
1.87058823529411791.59
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3871.387
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1480.148
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.6110.611
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.4540.454
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.85611.856
WECLTFEXP_WEC->PJM
CLTF
2.5782.578
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.2290.229
SIGELTFEXP_SIGE->PJM
CLTF
0.0530.053
CBM West 1LTFEXP_CBM-W1->PJM
CBM
75.73675.736
NYPJM->LTFIMP_NY
CLTF
0.7460.746
TVALTFEXP_TVA->PJM
CLTF
1.1741.174
LAGNLTFEXP_LAGN->PJM
CLTF
2.6762.676
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2990.299
MECLTFEXP_MEC->PJM
CLTF
8.7698.769
O66PJM->LTFIMP_O-066
CMTX_NF
8.8988.898

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:114.84 %
Rating:1091.0 MVA
Rating Type:A
MVA to Mitigate:1252.95
MW Contribution:15.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960282AF2-319 E
50/50
3.2523.252
293645O22 E2
50/50
14.26614.266
918052AA1-018 E OP
Adder
10.6611764705882349.062
293715O-029 E
Adder
6.58705882352941255.599
274751CRETE EC ;1U
50/50
5.7635.763
293644O22 E1
50/50
12.45512.455
960281AF2-319 C
50/50
2.1682.168
960752AF2-366 E
Adder
3.12235294117647082.654
957471AF2-041 C
Adder
14.49058823529411912.317
294763P-046 E
Adder
6.3917647058823535.433
938861AE1-114 C
Adder
2.66117647058823532.262
960591AF2-350 C
Adder
4.6364705882352943.941
960592AF2-350 E
Adder
3.09058823529411742.627
275149KELLYCK ;1E
Adder
10.8188235294117649.196
934722AD1-100 E
Adder
60.5729411764705951.487
960751AF2-366 C
Adder
4.6847058823529423.982
942422AE2-255 E
Adder
6.5047058823529415.529
960582AF2-349 E
Adder
24.68117647058823420.979
937312AD2-172 E
Adder
2.30000000000000031.955
274859EASYR;U1 E
Adder
8.1305882352941186.911
943592AF1-030 E
Adder
2.7635294117647062.349
943591AF1-030 C
Adder
5.5847058823529414.747
936292AD2-038 E
Adder
10.0823529411764728.57
290021O50 E
Adder
13.8752941176470611.794
937002AD2-134 E
Adder
6.8070588235294115.786
274752CRETE EC ;2U
50/50
5.7635.763
936371AD2-047 C
Adder
2.6270588235294122.233
933412AC2-154 E
Adder
2.3952941176470592.036
936461AD2-060 C
Adder
1.54588235294117651.314
962782AG1-127 E
Adder
3.12588235294117662.657
946671AF1-331 C
Adder
1.60941176470588251.368
959351AF2-226 C
50/50
2.1682.168
958491AF2-143 C
Adder
7.3411764705882366.24
933912AD1-013 E
Adder
1.97882352941176461.682
946152AF1-280 E
Adder
15.4129411764705913.101
293716O-029 E
Adder
3.6117647058823533.07
293771O-035 E
Adder
4.6694117647058823.969
941552AE2-152 E
Adder
5.19176470588235354.413
958482AF2-142 E
Adder
4.90117647058823554.166
938852AE1-113 E
Adder
20.2929411764705917.249
274890CAYUG;1U E
Adder
8.9564705882352957.613
962012AG1-044 E
Adder
0.0423529411764705860.036
925582AC1-033 E
Adder
6.3858823529411765.428
941551AE2-152 C
Adder
7.7882352941176486.62
274676JOLIET 29;8U
Adder
52.9223529411764844.984
958481AF2-142 C
Adder
7.3529411764705896.25
957332AF2-027 E
Adder
2.5917647058823532.203
274891CAYUG;2U E
Adder
8.9564705882352957.613
926822AC1-168 E
Adder
5.2117647058823534.43
957331AF2-027 C
Adder
1.7282352941176471.469
936511AD2-066 C
Adder
5.7423529411764714.881
936512AD2-066 E
Adder
3.8282352941176473.254
295109WESTBROOK E
Adder
3.76941176470588253.204
939061AE1-134 2
Adder
0.92588235294117650.787
966092AG1-478 E
Adder
0.33882352941176470.288
274682WAUKEGAN ;7U
Adder
28.6329411764705924.338
962692AG1-118 E
Adder
9.912941176470598.426
962691AG1-118 C
Adder
14.86823529411764812.638
942652AE2-281 E
Adder
3.50705882352941162.981
942651AE2-281 C
Adder
0.57058823529411760.485
274654BRAIDWOOD;1U
50/50
19.28319.283
939352AE1-166 E
Adder
6.2305882352941185.296
294392P-010 E
Adder
13.53764705882352911.507
934101AD2-000 1
Adder
3.8435294117647063.267
959352AF2-226 E
50/50
3.2523.252
958492AF2-143 E
Adder
4.8941176470588244.16
290108LEEDK;1U E
Adder
16.10823529411764813.692
942421AE2-255 C
Adder
2.16823529411764731.843
916221Z1-073 E
Adder
4.9611764705882354.217
959092AF2-200 E
Adder
6.445.474
957472AF2-041 E
Adder
7.24470588235294166.158
938862AE1-114 E
Adder
9.087.718
926821AC1-168 C
Adder
0.77647058823529410.66
274753CRETE EC ;3U
50/50
5.7635.763
936372AD2-047 E
Adder
12.82823529411764710.904
276591L-013 2
Adder
2.4788235294117652.107
274861TOP CROP ;1U
50/50
0.3250.325
962781AG1-127 C
Adder
4.6976470588235293.993
933911AD1-013 C
Adder
1.23882352941176471.053
293519PILOT HIL;1E
Adder
10.8188235294117649.196
939351AE1-166 C
Adder
6.7494117647058835.737
274675JOLIET 29;7U
Adder
52.87529411764706644.944
274674JOLIET 9 ;6U
Adder
23.3929411764705919.884
293061N-015 E
Adder
10.669.061
943121AE2-341 C
Adder
8.397647058823537.138
274862TOP CROP ;2U
50/50
0.620.62
939321AE1-163 C
Adder
3.99647058823529383.397
295111SUBLETTE E
Adder
1.8317647058823531.557
274860EASYR;U2 E
Adder
8.1305882352941186.911
927209AC1-214 E2
Adder
2.21411764705882331.882
274754CRETE EC ;4U
50/50
5.7635.763
958012AF2-095 E
Adder
4.4505882352941173.783
934111AD2-000 2
Adder
4.3529411764705893.7
966442AG1-513 E
Adder
0.51294117647058820.436
274683WAUKEGAN ;8U
Adder
30.8552941176470626.227
290051GSG-6; E
Adder
7.045.984
959082AF2-199 E
Adder
2.41529411764705862.053
958912AF2-182 E
Adder
23.1219.652
294401BSHIL;1U E
Adder
5.8247058823529414.951
943122AE2-341 E
Adder
4.1235294117647053.505
939322AE1-163 E
Adder
24.55176470588235220.869
293717O-029 E
Adder
3.32000000000000032.822
293516O-009 E
Adder
12.7376470588235310.827
927208AC1-214 E1
Adder
2.21411764705882331.882
958011AF2-095 C
Adder
6.6764705882352945.675
933411AC2-154 C
Adder
1.4682352941176471.248
274687WILL CNTY;4U
Adder
50.79647058823529443.177
966091AG1-478 C
Adder
1.3482352941176471.146
966441AG1-513 C
Adder
0.34235294117647060.291
959081AF2-199 C
Adder
4.8305882352941174.106
916212CRESCENT ;1U
Adder
3.282.788
294410BSHIL;2U E
Adder
1.40235294117647061.192
938851AE1-113 C
Adder
5.7235294117647064.865
272363ESS H440 ; R
Adder
1.76941176470588251.504
959091AF2-200 C
Adder
9.668.211
940502AE2-035 E
Adder
2.30000000000000031.955
276170Z1-108 E
Adder
2.00117647058823561.701
276626AG1-044 E
Adder
0.0494117647058823560.042
276675AE2-062 E
Adder
0.103529411764705880.088
920272AA2-123 E
Adder
1.95882352941176491.665
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.3940.394
MECLTFEXP_MEC->PJM
CLTF
8.7288.728
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.5680.568
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.81249.812
NYPJM->LTFIMP_NY
CLTF
0.7740.774
TVALTFEXP_TVA->PJM
CLTF
0.660.66
LAGNLTFEXP_LAGN->PJM
CLTF
2.092.09
G-007PJM->LTFIMP_G-007
CMTX_NF
1.4391.439
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2110.211
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.491.49
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.3588.358
WECLTFEXP_WEC->PJM
CLTF
2.6882.688
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5040.504
O66PJM->LTFIMP_O-066
CMTX_NF
9.239.23
255113 to 243219 ckt 1
274750 to 255112 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AF1-280 was evaluated as a 200.0 MW injection in the ComEd area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 1, Cluster 16 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 16 projects.

This analysis is effectively a screening study to determine whether the addition of the Cluster 16 projects will meet the dynamics requirements of the NERC, ComEd and PJM reliability standards.

The load flow scenario for the analysis was based on the RTEP 2027 summer peak load case, modified to include applicable projects. Cluster 16 projects have been dispatched online at maximum power output and the voltage schedule set to achieve near unity power factor at the high side of the main transformer.

Cluster 16 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 112 contingencies were studied, each with a 20 second simulation time period. Studied faults included:

  1. Steady-state operation (20 second run);
  2. Three-phase faults with normal clearing time;
  3. Three-phase bus faults with normal clearing time;
  4. Three-phase to ground faults with three-phase delayed clearing due to a stuck breaker (GO breakers);
  5. Three-phase to ground faults with single-phase delayed clearing due to a stuck breaker (IPO breakers);
  6. Three-phase faults with loss of multiple-circuit tower line;

No relevant high speed reclosing (HSR) contingencies were identified for this study.

For all simulations, the Cluster 16 projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

For all of the fault contingencies tested on the 2027 peak load case:

  1. Cluster 16 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  2. The system with Cluster 16 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3%.
  3. Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).
  4. No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

AF1-280, AF2-182, and AF2-349 meet the 0.95 leading and lagging PF requirement.

The IPCMD and IQCMD states in the REGCA1 models of AF1-280 GEN, AF2-182 GEN, AF2-349 GEN1, and AF2-349 GEN2 showed erratic behavior for some contingencies in which this generator has been disconnected as part of the contingency event. Since the machine is disconnected and no active or reactive power is injected into the system, these plots are ignored.

Voltage response at Brooke wind generator terminal bus (631215) caused the generator terminal voltage to drop below 0.892 pu resulting in the unit being tripped instantaneously by voltage relay instance 63121502. The relay pickup time was extended to 3 seconds (PRC-024-3 compliant) to prevent the plant from tripping.

Initial simulations showed a poorly damped oscillation in voltage/reactive power at the Easy Road Type 3 Wind plant for contingency P1.02 (fault at AF1-280/AF2-182 POI on Lee County EC 345 kV circuit). Tuning the Torque controller in the Type 3 wind plant resolved the oscillation:

WTTQA1:

CON(J+11) = 0.98 (spd3, shaft speed for power p3 (pu)) from 1.2

CON(J+13) = 1.0 (spd4, shaft speed for power p4 (pu)) from 1.2

Initial simulations showed a poorly damped oscillation in AC1-111 power. The AC1-111 dynamic model was updated to the most recent (revision 1) model which uses the AC7B exciter model instead of the ESAC1A model. The updated dynamic model eliminated these oscillations.

No mitigations were found to be required.

Table 1: TC1 Cluster 16 Projects

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

16

AF1-280

Solar

ComEd

200

200

0

Nelson – Lee County 345 kV

AF2-182

Solar

ComEd

300

300

0

Nelson – Lee County 345 kV

AF2-349

Solar

ComEd

300

300

0

Silver Lake – Cherry Valley 345 kV

 

 

Reactive Power Analysis

The reactive power capability of AF1-280 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-146NelsonIn Service
AA2-030NelsonIn Service
AA2-123Marengo 34kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-168Kewanee-StreatorSuspended
AC1-214Crescent RidgeIn Service
AC2-154Davis Creek 138kVEngineering & Procurement
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-134Shady OaksPartially in Service - Under Construction
AD2-172Lena 138kVIn Service
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-134Nelson 345 kVIn Service
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-035Lena 138 kVIn Service
AE2-062Romeoville 12 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-255Molecreek 345 kVUnder Construction
AE2-281Powerton-Nevada 345 kVUnder Construction
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-027Zion Energy Center 345 kVEngineering & Procurement
AF2-031CalumetEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-182Nelson-Lee County 345 kV IIEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-226Katydid Road 345 kVEngineering & Procurement
AF2-319Katydid Road 345 kVEngineering & Procurement
AF2-349SILVER LAKE- CHERRY VALLEY 345 KVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-366Crego Rd 138 kVEngineering & Procurement
AF2-441Burnham 138kVEngineering & Procurement
AG1-044Whiteside CountyIn Service
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-513Aurora 138 kVSuspended
AG1-553Cordova 345 kVEngineering & Procurement
X3-005Wildwood 12kVIn Service
Z1-073Mendota HillsIn Service
Z1-108McHenry 34kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In coordination with other Affected System Operators, PJM has determined that the Affected System Operator for this project that requires an Affected System Study. For the latest Affected System Study results pertaining this project, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM lists any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO) Identified Impacts
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AF1-280 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
ComEdn6639.2Reconductor the Electric Junction 345 kV line 93407, perform sag mitigation on 345 kV line 93407, upgrade one 345 kV circuit breaker and associated motor operated disconnect switches.Cost Allocated$14,292,703
ComEdb3775.1Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV lineContingent$0N/A
AEPb3775.10Perform sag study mitigation work on Olive – University ParkContingent$0N/A
ComEdb3775.3Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to CreteContingent$0N/A
Grand Total:$14,292,703

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n6639.2
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n6639.2 / CE_NUN_L15502_4
Title
Reconductor the Electric Junction 345 kV line 93407, perform sag mitigation on 345 kV line 93407, upgrade one 345 kV circuit breaker and associated motor operated disconnect switches.
Description
• Reconductor 27.2 Miles of 345kV transmission line 93407 from structure 339 to structure 454 • Perform sag mitigation on 13.5 miles of 345kV transmission line 93407 from structure 454 to TSS 111 Electric Junction • Upgrade the existing substation TSS 111 Electric Junction by replacing L.93407 CB motor-operated disconnect switches on both sides of the breaker.
Total Cost ($USD)
$146,197,759
Discounted Total Cost ($USD)
$146,197,759
Allocated Cost ($USD)
$14,292,703
Time Estimate
Sep 30 2029

Contributor

FacilityContingency
ELECT JCT; B-AF2-041 TP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE1-11422.0 MW3.2%$4,677,511
AF1-280 ⧉ Nelson - Lee County 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-280, AF2-182
67.2 MW9.8%$14,292,703
AF1-29644.0 MW6.4%$9,366,298
AF2-041 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-041, AF2-199, AF2-200
159.4 MW23.2%$33,916,212
AF2-182 ⧉ Nelson - Lee County 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-280, AF2-182
100.8 MW14.7%$21,438,948
AF2-199 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-041, AF2-199, AF2-200
53.1 MW7.7%$11,305,333
AF2-200 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-041, AF2-199, AF2-200
118.1 MW17.2%$25,123,010
AG1-462 ⧉ Cordova 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-462, AG1-553
60.7 MW8.8%$12,912,297
AG1-553 ⧉ Cordova 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-462, AG1-553
61.9 MW9.0%$13,165,446

System Reinforcement: b3775.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.1
Title
Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line
Description
Outside of the Green Acres substation, swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line to the University Park N-Olive 345 kV line to create a University Park N-Green Acres-Olive and St. John-Olive 345 kV lines.
Cost Information
Time Estimate
Mar 30 2027

Contingent

Note: Although AF1-280 may not presently have cost responsibility for this upgrade, AF1-280 may need this upgrade in-service to be deliverable to the PJM system. If AF1-280 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)ALDR9999.0 MVA
(All)STE9999.0 MVA
05OLIVE-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A9999.0 MVA
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A9999.0 MVA

System Reinforcement: b3775.10
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.10
Title
Perform sag study mitigation work on Olive – University Park
Description
Perform a sag study on the Olive – University Park 345kV line to increase the operating temperature to 225 F. Remediation work includes two tower replacements on the line.
Cost Information
Time Estimate
Dec 01 2026

Contingent

Note: Although AF1-280 may not presently have cost responsibility for this upgrade, AF1-280 may need this upgrade in-service to be deliverable to the PJM system. If AF1-280 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA

System Reinforcement: b3775.3
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.3
Title
Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete
Description
Part of b3775 baseline. Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete (5 miles) with twin bundled 1277 ACAR conductor.
Cost Information
Time Estimate
Dec 01 2026

Contingent

Note: Although AF1-280 may not presently have cost responsibility for this upgrade, AF1-280 may need this upgrade in-service to be deliverable to the PJM system. If AF1-280 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA
(All)C2280.0 MVA
(All)STE2107.0 MVA

System Reinforcement: b3775.2
Type
Load Flow
TO
NextEra
RTEP ID / TO ID
b3775.2
Title
Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles).
Description
Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles).
Cost Information
Time Estimate
May 09 2023

Not Contingent

Note: AF1-280 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF1-280 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA
(All)C2280.0 MVA
(All)STE2107.0 MVA

System Reinforcement: s3011
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
s3011 / CE_S3011
Title
Replace 345kV straight bus at TSS 116 Goodings Grove with a gas insulated switchgear ("GIS") breaker and a half configuration.
Description
Replace 345 kV open air straight bus with GIS in a breaker and half configuration (34 Circuit Breakers) at Goodings Grove with 80kA capability.
Cost Information
Time Estimate
Dec 31 2029

Not Contingent

Note: AF1-280 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AF1-280 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
(Any)COMED_P4_116-45-L11614__SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4-6_116-345-R______SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4_112-45-BT4-5___SRT-A
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AF1-280


AF1-280 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AF1-280 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AF1-280 One Line Diagram

AF1-280 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.