AF1-296 Final System Impact Study (Retool 2) Report

v2.00 released 2026-05-14 11:49

Garden Plain 138 kV

33.6 MW Capacity / 190.89 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Gipper Wind Farm, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Commonwealth Edison Company.

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.

The AF1-296 Final System Impact Study (Retool 1) Report is available for download here.

Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed a Wind generating facility located in the Commonwealth Edison Company zone — Whiteside County, Illinois. The installed facilities will have a total capability of 190.89 MW with 33.6 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AF1-296
Project Name:
Garden Plain 138 kV
Project Developer Name:
Gipper Wind Farm, LLC
State:
Illinois
County:
Whiteside
Transmission Owner:
Commonwealth Edison Company
MFO:
190.89
MWE:
190.89
MWC:
33.6
Fuel Type:
Wind
Basecase Study Year:
2027

Physical Interconnection Facility Study

Received

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AF1-296 will interconnect on the ComEd transmission system by a direct connection into the TSS 132 Garden Plain 138 kV substation.

 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AF1-296 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AF1-296Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$717,375$717,375
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$11,672,026$11,672,026
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$9,366,298$9,366,298
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0
AFS - Non-PJM Violations$86,606 **$0 **
Total$21,842,305$21,755,699

* Contributes to calculation for Security. See Security Requirement Section of this report for additional detail.

** This value reflects the results at the time of the report posting and it is subject to change. AFS – Non-PJM Violations are not subject to Security. For latest AFS – Non-PJM Violations, please refer to the latest Affected System Study Report for your project.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF1-296

Security has been calculated for the AF1-296 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF1-296
Project(s): AF1-296
Final Agreement Security (A): $21,755,699
Portion of Costs Already Paid (B): $0
Revised Net Security (C): A − B = $21,755,699
Security on Hand with PJM (D): $21,755,699
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n9629.0

Expand the TSS 132 Garden Plain substation to accommodate the AF1-296 project.

$6,837,831$2,846,065$1,819,139$168,991$11,672,026$11,672,026
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Construct Transmission Owner Interconnection Facilities from the Point of Change in Ownership to the TSS 132 substation.

$185,242$455,788$49,282$27,063$717,375$717,375

Based on the scope of work for the Interconnection Facilities, it is expected to take 36 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Notes on Cost Estimate:

  1. These estimates are Order-of-Magnitude estimates of the costs that ComEd would bill to the Project Developer for this interconnection. These estimates are based on a one-line electrical diagram of the project and the information provided by the Project Developer.
  2. There were no site visits performed for these estimates. There may be costs related to specific site related issues that are not identified in these estimates. The site reviews will be performed during the Facilities Study or during detailed engineering.
  3. These estimates are not a guarantee of the maximum amount payable by the Project Developer and the actual costs of ComEd's work may differ significantly from these estimates. The Project Developer will be responsible for paying actual costs of ComEd's work in accordance with the PJM Open Access Transmission Tariff.
  4. The Project Developer is responsible for all engineering, procurement, testing and construction of all equipment on the Project Developer’s side of the Point of Change in Ownership.

These cost estimates do not include cost of acquiring right-of-way for the transmission line and purchasing any additional land, if needed, for the line terminations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. ComEd interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The wind generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Wind speed (meters/second) - (Required)
  • Wind direction (decimal degrees from true north) - (Required)
  • Ambient air temperature (Fahrenheit) - (Required)
  • Air Pressure (Hectopascals) - (Required)
  • Humidity (Percent) - (Accepted, not required)
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AF1-296 was evaluated as a 190.9 MW (33.6 MW Capacity) injection in the ComEd area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1CE
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
COMED_P4_006-45-BT3-8___SRT-A
BreakerAC115.39 %1837.0STE2119.7744.03
GD1CE
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
COMED_P4_006-45-BT3-4___SRT-A
BreakerAC114.8 %1837.0STE2108.8443.85

Details for AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.39 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2119.77
MW Contribution:44.03
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.95 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2129.98
MW Contribution:44.13
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274859EASYR;U1 E
50/50
35.20335.203
276676AA2-030 GEN
50/50
8.628.62
957471AF2-041 C
50/50
106.288106.288
938861AE1-114 C
Adder
4.9835294117647064.236
274858BIG SKY ;U2
50/50
0.8340.834
927209AC1-214 E2
Adder
2.84000000000000032.414
295111SUBLETTE E
Adder
1.95882352941176491.665
946322AF1-296 E
Adder
36.2788235294117730.837
274860EASYR;U2 E
50/50
35.20335.203
990901L-005 E
Adder
12.2223529411764710.389
295109WESTBROOK E
Adder
4.0305882352941183.426
939061AE1-134 2
50/50
4.0994.099
927208AC1-214 E1
Adder
2.84000000000000032.414
293717O-029 E
50/50
10.66510.665
293516O-009 E
50/50
40.92240.922
946321AF1-296 C
Adder
7.7494117647058826.587
274718NELSON EC;2S
50/50
6.8026.802
933911AD1-013 C
Adder
1.2588235294117651.07
276157O-029 C
50/50
0.7890.789
274881WALNUT RG;1U
50/50
1.6721.672
916221Z1-073 E
Adder
5.3047058823529424.509
274715NELSON EC;1C
50/50
9.249.24
959092AF2-200 E
50/50
47.23947.239
957472AF2-041 E
50/50
53.14453.144
938862AE1-114 E
Adder
17.00352941176470614.453
916212CRESCENT ;1U
Adder
4.2082352941176473.577
294410BSHIL;2U E
Adder
9.1588235294117667.785
966822AG1-553 E
50/50
61.88861.888
274717NELSON EC;2C
50/50
9.3129.312
959081AF2-199 C
50/50
35.42935.429
274765LEE CO EC;6U
50/50
4.6714.671
274763LEE CO EC;4U
50/50
4.6164.616
274760LEE CO EC;1U
50/50
4.664.66
293771O-035 E
Adder
5.9905882352941175.092
293716O-029 E
50/50
11.60411.604
276158O-029 C
50/50
0.7890.789
276156O-029 C
50/50
0.4370.437
933912AD1-013 E
Adder
2.0105882352941181.709
965931AG1-462 C
50/50
36.41936.419
946152AF1-280 E
50/50
67.18767.187
946671AF1-331 C
Adder
1.63529411764705881.39
293715O-029 E
50/50
21.16321.163
274857BIG SKY ;U1
50/50
0.8340.834
937002AD2-134 E
Adder
7.2788235294117656.187
276677AA1-146
50/50
10.43210.432
274762LEE CO EC;3U
50/50
4.664.66
274761LEE CO EC;2U
50/50
4.664.66
294401BSHIL;1U E
Adder
9.1588235294117667.785
290051GSG-6; E
Adder
7.5282352941176476.399
274716NELSON EC;1S
50/50
6.7426.742
959082AF2-199 E
50/50
17.71517.715
958912AF2-182 E
50/50
100.78100.78
274766LEE CO EC;7U
50/50
4.6054.605
274764LEE CO EC;5U
50/50
4.6714.671
925582AC1-033 E
Adder
10.0435294117647078.537
962012AG1-044 E
50/50
0.1520.152
272363ESS H440 ; R
Adder
1.821.547
965932AG1-462 E
50/50
24.27924.279
939051AE1-134 1
50/50
0.6580.658
959091AF2-200 C
50/50
70.85970.859
274767LEE CO EC;8U
50/50
4.6054.605
276626AG1-044 E
50/50
0.1520.152
991092J1477
External Queue
7.7741432189941417.774143218994141
990948J1432 E
External Queue
35.043445587158235.0434455871582
956412J1131
External Queue
15.51725292205810515.517252922058105
955972J1084
External Queue
29.59977722167968829.599777221679688
990947J1432 C
External Queue
6.4772243499755866.477224349975586
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.02215.022
NYPJM->LTFIMP_NY
CLTF
0.1950.195
TVALTFEXP_TVA->PJM
CLTF
2.2672.267
LAGNLTFEXP_LAGN->PJM
CLTF
4.6314.631
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.0865.08
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3440.344
CPLELTFEXP_CPLE->PJM
CLTF
0.270.27
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0080.008
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.1270.127
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0170.017
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0260.026
SIGELTFEXP_SIGE->PJM
CLTF
0.0520.052
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.8814.881
WECLTFEXP_WEC->PJM
CLTF
0.0040.004
MECLTFEXP_MEC->PJM
CLTF
16.85816.858
O66PJM->LTFIMP_O-066
CMTX_NF
2.2112.211

Details for AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.8 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2108.84
MW Contribution:43.85
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.58 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2123.16
MW Contribution:43.95
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274859EASYR;U1 E
50/50
35.1335.13
276676AA2-030 GEN
50/50
8.6028.602
957471AF2-041 C
50/50
106.259106.259
938861AE1-114 C
Adder
4.90117647058823554.166
274858BIG SKY ;U2
50/50
0.8330.833
927209AC1-214 E2
Adder
2.8317647058823532.407
295111SUBLETTE E
Adder
1.94235294117647061.651
946322AF1-296 E
Adder
36.12941176470588530.71
274860EASYR;U2 E
50/50
35.1335.13
990901L-005 E
Adder
12.1847058823529410.357
295109WESTBROOK E
Adder
3.99411764705882363.395
939061AE1-134 2
50/50
4.0914.091
927208AC1-214 E1
Adder
2.8317647058823532.407
293717O-029 E
50/50
10.63310.633
293516O-009 E
50/50
40.840.8
946321AF1-296 C
Adder
7.71764705882352956.56
274718NELSON EC;2S
50/50
6.7886.788
276157O-029 C
50/50
0.7860.786
274881WALNUT RG;1U
50/50
1.6671.667
916221Z1-073 E
Adder
5.257647058823534.469
274715NELSON EC;1C
50/50
9.2219.221
959092AF2-200 E
50/50
47.22647.226
957472AF2-041 E
50/50
53.1353.13
938862AE1-114 E
Adder
16.7223529411764714.214
916212CRESCENT ;1U
Adder
4.1964705882352953.567
294410BSHIL;2U E
Adder
9.1305882352941187.761
966822AG1-553 E
50/50
61.66161.661
274717NELSON EC;2C
50/50
9.2929.292
959081AF2-199 C
50/50
35.4235.42
274765LEE CO EC;6U
50/50
4.6614.661
274763LEE CO EC;4U
50/50
4.6064.606
274760LEE CO EC;1U
50/50
4.6514.651
293771O-035 E
Adder
5.9729411764705885.077
293716O-029 E
50/50
11.56911.569
276158O-029 C
50/50
0.7860.786
276156O-029 C
50/50
0.4360.436
965931AG1-462 C
50/50
36.28536.285
946152AF1-280 E
50/50
67.04767.047
293715O-029 E
50/50
21.121.1
274857BIG SKY ;U1
50/50
0.8330.833
937002AD2-134 E
Adder
7.2141176470588236.132
276677AA1-146
50/50
10.41110.411
274762LEE CO EC;3U
50/50
4.6514.651
274761LEE CO EC;2U
50/50
4.6514.651
294401BSHIL;1U E
Adder
9.1305882352941187.761
290051GSG-6; E
Adder
7.4611764705882356.342
274716NELSON EC;1S
50/50
6.7286.728
959082AF2-199 E
50/50
17.7117.71
958912AF2-182 E
50/50
100.57100.57
274766LEE CO EC;7U
50/50
4.5964.596
274764LEE CO EC;5U
50/50
4.6614.661
925582AC1-033 E
Adder
10.0117647058823538.51
962012AG1-044 E
50/50
0.1520.152
272363ESS H440 ; R
Adder
1.80352941176470581.533
965932AG1-462 E
50/50
24.1924.19
939051AE1-134 1
50/50
0.6570.657
959091AF2-200 C
50/50
70.8470.84
274767LEE CO EC;8U
50/50
4.5964.596
276626AG1-044 E
50/50
0.1520.152
991092J1477
External Queue
7.7651863098144537.765186309814453
990948J1432 E
External Queue
34.9377975463867234.93779754638672
956412J1131
External Queue
15.49937438964843815.499374389648438
955972J1084
External Queue
29.56552124023437529.565521240234375
990947J1432 C
External Queue
6.457697391510016.45769739151001
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.43163.431
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3420.342
TVALTFEXP_TVA->PJM
CLTF
2.2452.245
LAGNLTFEXP_LAGN->PJM
CLTF
4.5854.585
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.8234.823
CPLELTFEXP_CPLE->PJM
CLTF
0.2660.266
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0090.009
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.1250.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.88914.889
NYPJM->LTFIMP_NY
CLTF
0.1940.194
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0260.026
SIGELTFEXP_SIGE->PJM
CLTF
0.0510.051
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0160.016
MECLTFEXP_MEC->PJM
CLTF
16.69316.693
O66PJM->LTFIMP_O-066
CMTX_NF
2.2012.201
CONTINGENCY 'COMED_P4_006-45-BT3-8___SRT-A'
 TRIP BRANCH FROM BUS 270678 TO BUS 270679 CKT Z1   /*BYRON    ; B 345.0 - BYRON    ; R 345.0
 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1    /*LEE CO EC;BP 345.0 - BYRON    ; B 345.0
END
CONTINGENCY 'COMED_P4_006-45-BT3-4___SRT-A'
 REMOVE UNIT 1 FROM BUS 274656                     /*BYRON    ;1U  25.0
 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1   /*LEE CO EC;BP 345.0 - BYRON    ; B 345.0
END
957470 to 270730 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC143.99 %1075.0B1547.914.03
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC143.99 %1075.0B1547.874.03
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Base Case
SingleAC108.83 %1075.0A1169.932.34
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC100.5 %1399.0B1405.953.62
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC100.5 %1399.0B1405.933.62
GD1CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4-6_116-345-R______SRT-A
BreakerAC107.57 %2297.0STE2471.017.2
GD1CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4_116-45-L11614__SRT-A
BreakerAC103.27 %2297.0STE2372.115.17
GD1CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4_112-45-BT4-5___SRT-A
BreakerAC100.41 %2297.0STE2306.4718.87
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC126.43 %970.0STE1226.414.01
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC126.43 %970.0STE1226.414.01
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC126.41 %970.0STE1226.1513.94

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.99 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1547.91
MW Contribution:4.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957371AF2-031 C
80/20
1.5531.553
960591AF2-350 C
80/20
9.4429.442
960751AF2-366 C
Adder
7.9070588235294126.721
274751CRETE EC ;1U
80/20
1.941.94
274723RIVER EC ;12
80/20
5.1225.122
274724RIVER EC ;11
80/20
5.1235.123
960281AF2-319 C
Adder
2.89058823529411772.457
957471AF2-041 C
Adder
24.1929411764705920.564
938861AE1-114 C
Adder
4.4423529411764713.776
961501AF2-441 C
80/20
14.87514.875
274826FISK ;BP
80/20
2.6552.655
939351AE1-166 C
Adder
11.6094117647058829.868
274675JOLIET 29;7U
Adder
82.4117647058823570.05
274674JOLIET 9 ;6U
Adder
42.3282352941176535.979
943121AE2-341 C
Adder
14.46117647058823512.292
939321AE1-163 C
Adder
6.7517647058823535.739
276164X3-005 C
80/20
0.0990.099
274827FISK ;RP
80/20
1.8821.882
957331AF2-027 C
Adder
2.82588235294117672.402
936511AD2-066 C
Adder
9.5376470588235298.107
939061AE1-134 2
Adder
1.54823529411764721.316
274800UNIV PARK;3U
80/20
1.3961.396
941551AE2-152 C
Adder
13.39529411764705811.386
274676JOLIET 29;8U
Adder
82.4152941176470670.053
958481AF2-142 C
Adder
12.7223529411764710.814
946321AF1-296 C
Adder
4.0305882352941183.426
274753CRETE EC ;3U
80/20
1.941.94
274793SE CHICAG;0U
80/20
7.1437.143
274795SE CHICAG;2U
80/20
7.1437.143
962781AG1-127 C
Adder
7.92823529411764756.739
933911AD1-013 C
Adder
2.08705882352941161.774
934101AD2-000 1
Adder
6.542352941176475.561
942421AE2-255 C
Adder
3.42117647058823552.908
926821AC1-168 C
Adder
1.28941176470588251.096
959611AF2-252 C
Adder
2.1329411764705881.813
274788SE CHICAG;5U
80/20
7.2327.232
274798UNIV PARK;1U
80/20
1.4061.406
958011AF2-095 C
80/20
13.59713.597
933411AC2-154 C
80/20
2.992.99
274687WILL CNTY;4U
Adder
78.0176470588235366.315
966091AG1-478 C
Adder
2.38941176470588262.031
966441AG1-513 C
Adder
0.57647058823529410.49
959081AF2-199 C
Adder
8.0647058823529436.855
942111AE2-223 C
Adder
2.17764705882352951.851
939741AE1-205 C
Adder
9.3811764705882357.974
959351AF2-226 C
Adder
2.89058823529411772.457
958491AF2-143 C
Adder
12.40117647058823610.541
965931AG1-462 C
Adder
18.16117647058823415.437
274752CRETE EC ;2U
80/20
1.941.94
274794SE CHICAG;1U
80/20
7.1437.143
936371AD2-047 C
80/20
5.355.35
936461AD2-060 C
80/20
3.1473.147
946671AF1-331 C
Adder
2.71058823529411752.304
960611AF2-352 C
Adder
2.1329411764705881.813
274888KELLY CRK;1U
80/20
0.8970.897
943591AF1-030 C
Adder
9.6164705882352938.174
274754CRETE EC ;4U
80/20
1.941.94
274887PILOT HIL;1U
80/20
0.8970.897
934111AD2-000 2
Adder
6.8035294117647065.783
274683WAUKEGAN ;8U
Adder
50.3941176470588342.835
274792SE CHICAG;9U
80/20
7.1437.143
274799UNIV PARK;2U
80/20
1.3961.396
274801UNIV PARK;4U
80/20
1.3961.396
274790SE CHICAG;7U
80/20
7.2327.232
274791SE CHICAG;8U
80/20
7.2327.232
274789SE CHICAG;6U
80/20
7.2327.232
274682WAUKEGAN ;7U
Adder
46.7423529411764739.731
942651AE2-281 C
Adder
0.96470588235294120.82
962691AG1-118 C
Adder
25.1023529411764721.337
938851AE1-113 C
Adder
9.0329411764705887.678
959091AF2-200 C
Adder
16.12823529411764813.709
959341AF2-225 C
Adder
7.0364705882352945.981
965091AG1-374 C
Adder
19.1976470588235316.318
990762J1386
External Queue
12.93081378936767612.930813789367676
990547J1333 G
External Queue
40.5239410400390640.52394104003906
990582J1340
External Queue
26.57409286499023426.574092864990234
990662J1358
External Queue
14.93047237396240214.930472373962402
991332J1785
External Queue
13.53217792510986313.532177925109863
990552J1334 G
External Queue
40.5239410400390640.52394104003906
990557J1335 G
External Queue
40.5239410400390640.52394104003906
990562J1336 G
External Queue
40.5239410400390640.52394104003906
990577J1339
External Queue
26.57409286499023426.574092864990234
991247J1684 G
External Queue
33.61624908447265633.616249084472656
990647J1355
External Queue
42.268421173095742.2684211730957
955742J1058 G
External Queue
35.2828559875488335.28285598754883
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2810.281
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.4171.417
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.88718.887
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5520.552
MECLTFEXP_MEC->PJM
CLTF
14.93414.934
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8260.826
NYPJM->LTFIMP_NY
CLTF
1.271.27
TVALTFEXP_TVA->PJM
CLTF
1.7951.795
LAGNLTFEXP_LAGN->PJM
CLTF
4.3274.327
CBM West 1LTFEXP_CBM-W1->PJM
CBM
118.129118.129
WECLTFEXP_WEC->PJM
CLTF
4.4234.423
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.510.51
SIGELTFEXP_SIGE->PJM
CLTF
0.060.06

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.99 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1547.87
MW Contribution:4.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957371AF2-031 C
80/20
1.5531.553
960591AF2-350 C
80/20
9.4429.442
960751AF2-366 C
Adder
7.9070588235294126.721
274751CRETE EC ;1U
80/20
1.941.94
274723RIVER EC ;12
80/20
5.1225.122
274724RIVER EC ;11
80/20
5.1235.123
960281AF2-319 C
Adder
2.89058823529411772.457
957471AF2-041 C
Adder
24.1929411764705920.564
938861AE1-114 C
Adder
4.4423529411764713.776
961501AF2-441 C
80/20
14.87514.875
274826FISK ;BP
80/20
2.6552.655
939351AE1-166 C
Adder
11.6094117647058829.868
274675JOLIET 29;7U
Adder
82.4117647058823570.05
274674JOLIET 9 ;6U
Adder
42.3282352941176535.979
943121AE2-341 C
Adder
14.46117647058823512.292
939321AE1-163 C
Adder
6.7517647058823535.739
276164X3-005 C
80/20
0.0990.099
274827FISK ;RP
80/20
1.8821.882
957331AF2-027 C
Adder
2.82588235294117672.402
936511AD2-066 C
Adder
9.5376470588235298.107
939061AE1-134 2
Adder
1.54823529411764721.316
274800UNIV PARK;3U
80/20
1.3961.396
941551AE2-152 C
Adder
13.39529411764705811.386
274676JOLIET 29;8U
Adder
82.4152941176470670.053
958481AF2-142 C
Adder
12.7223529411764710.814
946321AF1-296 C
Adder
4.0305882352941183.426
274753CRETE EC ;3U
80/20
1.941.94
274793SE CHICAG;0U
80/20
7.1437.143
274795SE CHICAG;2U
80/20
7.1437.143
962781AG1-127 C
Adder
7.92823529411764756.739
933911AD1-013 C
Adder
2.08705882352941161.774
934101AD2-000 1
Adder
6.542352941176475.561
942421AE2-255 C
Adder
3.42117647058823552.908
926821AC1-168 C
Adder
1.28941176470588251.096
959611AF2-252 C
Adder
2.1329411764705881.813
274788SE CHICAG;5U
80/20
7.2327.232
274798UNIV PARK;1U
80/20
1.4061.406
958011AF2-095 C
80/20
13.59713.597
933411AC2-154 C
80/20
2.992.99
274687WILL CNTY;4U
Adder
78.0176470588235366.315
966091AG1-478 C
Adder
2.38941176470588262.031
966441AG1-513 C
Adder
0.57647058823529410.49
959081AF2-199 C
Adder
8.0647058823529436.855
942111AE2-223 C
Adder
2.17764705882352951.851
939741AE1-205 C
Adder
9.3811764705882357.974
959351AF2-226 C
Adder
2.89058823529411772.457
958491AF2-143 C
Adder
12.40117647058823610.541
965931AG1-462 C
Adder
18.16117647058823415.437
274752CRETE EC ;2U
80/20
1.941.94
274794SE CHICAG;1U
80/20
7.1437.143
936371AD2-047 C
80/20
5.355.35
936461AD2-060 C
80/20
3.1473.147
946671AF1-331 C
Adder
2.71058823529411752.304
960611AF2-352 C
Adder
2.1329411764705881.813
274888KELLY CRK;1U
80/20
0.8970.897
943591AF1-030 C
Adder
9.6164705882352938.174
274754CRETE EC ;4U
80/20
1.941.94
274887PILOT HIL;1U
80/20
0.8970.897
934111AD2-000 2
Adder
6.8035294117647065.783
274683WAUKEGAN ;8U
Adder
50.3941176470588342.835
274792SE CHICAG;9U
80/20
7.1437.143
274799UNIV PARK;2U
80/20
1.3961.396
274801UNIV PARK;4U
80/20
1.3961.396
274790SE CHICAG;7U
80/20
7.2327.232
274791SE CHICAG;8U
80/20
7.2327.232
274789SE CHICAG;6U
80/20
7.2327.232
274682WAUKEGAN ;7U
Adder
46.7423529411764739.731
942651AE2-281 C
Adder
0.96470588235294120.82
962691AG1-118 C
Adder
25.1023529411764721.337
938851AE1-113 C
Adder
9.0329411764705887.678
959091AF2-200 C
Adder
16.12823529411764813.709
959341AF2-225 C
Adder
7.0364705882352945.981
965091AG1-374 C
Adder
19.1976470588235316.318
990762J1386
External Queue
12.93081378936767612.930813789367676
990547J1333 G
External Queue
40.5239410400390640.52394104003906
990582J1340
External Queue
26.57409286499023426.574092864990234
990662J1358
External Queue
14.93047237396240214.930472373962402
991332J1785
External Queue
13.53217792510986313.532177925109863
990552J1334 G
External Queue
40.5239410400390640.52394104003906
990557J1335 G
External Queue
40.5239410400390640.52394104003906
990562J1336 G
External Queue
40.5239410400390640.52394104003906
990577J1339
External Queue
26.57409286499023426.574092864990234
991247J1684 G
External Queue
33.61624908447265633.616249084472656
990647J1355
External Queue
42.268421173095742.2684211730957
955742J1058 G
External Queue
35.2828559875488335.28285598754883
CBM West 1LTFEXP_CBM-W1->PJM
CBM
118.129118.129
WECLTFEXP_WEC->PJM
CLTF
4.4234.423
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.510.51
SIGELTFEXP_SIGE->PJM
CLTF
0.060.06
NYPJM->LTFIMP_NY
CLTF
1.271.27
TVALTFEXP_TVA->PJM
CLTF
1.7951.795
LAGNLTFEXP_LAGN->PJM
CLTF
4.3274.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.88718.887
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5520.552
MECLTFEXP_MEC->PJM
CLTF
14.93414.934
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8260.826
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2810.281
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.4171.417

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.83 %
Rating:1075.0 MVA
Rating Type:A
MVA to Mitigate:1169.93
MW Contribution:2.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957371AF2-031 C
80/20
1.1831.183
960591AF2-350 C
80/20
66
960751AF2-366 C
Adder
4.4776470588235293.806
274751CRETE EC ;1U
80/20
1.4551.455
274723RIVER EC ;12
80/20
3.8963.896
274724RIVER EC ;11
80/20
3.9023.902
960281AF2-319 C
Adder
1.80588235294117651.535
957471AF2-041 C
Adder
13.84352941176470611.767
938861AE1-114 C
Adder
2.562.176
961501AF2-441 C
80/20
10.91610.916
274826FISK ;BP
80/20
1.7681.768
939351AE1-166 C
Adder
6.7717647058823545.756
274675JOLIET 29;7U
Adder
49.9447058823529542.453
274674JOLIET 9 ;6U
Adder
25.73058823529411821.871
943121AE2-341 C
Adder
7.99529411764705966.796
939321AE1-163 C
Adder
4.1294117647058823.51
276164X3-005 C
80/20
0.070.07
274827FISK ;RP
80/20
1.2531.253
957331AF2-027 C
Adder
1.64941176470588241.402
936511AD2-066 C
Adder
5.6788235294117654.827
939061AE1-134 2
Adder
0.89294117647058820.759
274800UNIV PARK;3U
80/20
0.9170.917
941551AE2-152 C
Adder
7.8141176470588246.642
274676JOLIET 29;8U
Adder
49.9529411764705942.46
958481AF2-142 C
Adder
7.8258823529411776.652
946321AF1-296 C
Adder
2.34000000000000031.989
274753CRETE EC ;3U
80/20
1.4551.455
274793SE CHICAG;0U
80/20
5.4655.465
274795SE CHICAG;2U
80/20
5.4655.465
962781AG1-127 C
Adder
4.4894117647058823.816
933911AD1-013 C
Adder
1.18705882352941171.009
934101AD2-000 1
Adder
3.68941176470588243.136
942421AE2-255 C
Adder
2.0552941176470591.747
926821AC1-168 C
Adder
0.75294117647058820.64
959611AF2-252 C
Adder
1.24941176470588241.062
274788SE CHICAG;5U
80/20
5.5385.538
274798UNIV PARK;1U
80/20
0.9230.923
958011AF2-095 C
80/20
8.6418.641
933411AC2-154 C
80/20
1.91.9
274687WILL CNTY;4U
Adder
48.5929411764705941.304
966091AG1-478 C
Adder
1.46941176470588241.249
966441AG1-513 C
Adder
0.32705882352941180.278
959081AF2-199 C
Adder
4.6141176470588243.922
942111AE2-223 C
Adder
1.2717647058823531.081
939741AE1-205 C
Adder
5.4776470588235294.656
959351AF2-226 C
Adder
1.80588235294117651.535
958491AF2-143 C
Adder
7.5847058823529416.447
965931AG1-462 C
Adder
10.5505882352941188.968
274752CRETE EC ;2U
80/20
1.4551.455
274794SE CHICAG;1U
80/20
5.4655.465
936371AD2-047 C
80/20
3.43.4
936461AD2-060 C
80/20
22
946671AF1-331 C
Adder
1.54235294117647051.311
960611AF2-352 C
Adder
1.24941176470588241.062
274888KELLY CRK;1U
80/20
0.570.57
943591AF1-030 C
Adder
5.3176470588235294.52
274754CRETE EC ;4U
80/20
1.4551.455
274887PILOT HIL;1U
80/20
0.570.57
934111AD2-000 2
Adder
4.077647058823533.466
274683WAUKEGAN ;8U
Adder
29.42352941176470825.01
274792SE CHICAG;9U
80/20
5.4655.465
274799UNIV PARK;2U
80/20
0.9170.917
274801UNIV PARK;4U
80/20
0.9170.917
274790SE CHICAG;7U
80/20
5.5385.538
274791SE CHICAG;8U
80/20
5.5385.538
274789SE CHICAG;6U
80/20
5.5385.538
274682WAUKEGAN ;7U
Adder
27.29294117647059223.199
942651AE2-281 C
Adder
0.58941176470588240.501
962691AG1-118 C
Adder
14.20823529411764812.077
938851AE1-113 C
Adder
5.4270588235294124.613
959091AF2-200 C
Adder
9.2294117647058827.845
959341AF2-225 C
Adder
4.1082352941176473.492
965091AG1-374 C
Adder
11.249.554
990762J1386
External Queue
12.26621055603027312.266210556030273
990547J1333 G
External Queue
40.5459747314453140.54597473144531
990582J1340
External Queue
26.6973209381103526.69732093811035
990662J1358
External Queue
15.6888904571533215.68889045715332
991332J1785
External Queue
15.41609477996826215.416094779968262
991337J1802
External Queue
11.39966201782226611.399662017822266
990552J1334 G
External Queue
40.5459747314453140.54597473144531
990557J1335 G
External Queue
40.5459747314453140.54597473144531
990562J1336 G
External Queue
40.5459747314453140.54597473144531
990577J1339
External Queue
26.6973209381103526.69732093811035
991247J1684 G
External Queue
33.68902206420898433.689022064208984
990647J1355
External Queue
45.41125869750976645.411258697509766
955742J1058 G
External Queue
34.2569389343261734.25693893432617
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1480.148
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.6110.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.85611.856
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2990.299
MECLTFEXP_MEC->PJM
CLTF
8.7698.769
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.4540.454
NYPJM->LTFIMP_NY
CLTF
0.7460.746
TVALTFEXP_TVA->PJM
CLTF
1.1741.174
LAGNLTFEXP_LAGN->PJM
CLTF
2.6762.676
CBM West 1LTFEXP_CBM-W1->PJM
CBM
75.73675.736
WECLTFEXP_WEC->PJM
CLTF
2.5782.578
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.2290.229
SIGELTFEXP_SIGE->PJM
CLTF
0.0530.053

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.5 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1405.95
MW Contribution:3.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960591AF2-350 C
Adder
7.1082352941176476.042
934721AD1-100 C
80/20
3.0093.009
274728ELWOOD EC;5P
80/20
3.3643.364
274745AURORA EC;9P
80/20
1.0831.083
960751AF2-366 C
Adder
7.1470588235294126.075
274751CRETE EC ;1U
80/20
6.1116.111
274729ELWOOD EC;1P
80/20
3.3583.358
960281AF2-319 C
80/20
2.9462.946
957471AF2-041 C
Adder
21.9223529411764718.634
938861AE1-114 C
Adder
4.0129411764705883.411
961501AF2-441 C
Adder
6.6670588235294125.667
939351AE1-166 C
80/20
10.22310.223
274675JOLIET 29;7U
80/20
76.19176.191
274674JOLIET 9 ;6U
Adder
35.31176470588235430.015
943121AE2-341 C
Adder
13.0411.084
274862TOP CROP ;2U
80/20
0.8420.842
939321AE1-163 C
Adder
5.8800000000000014.998
274710KENDALL ;4C
80/20
3.8793.879
274709KENDALL ;3S
80/20
2.5942.594
276642AC1-204 GEN2
80/20
12.51212.512
274707KENDALL ;2S
80/20
2.7682.768
274871GR RIDGE ;2U
80/20
0.2220.222
957331AF2-027 C
Adder
2.5729411764705882.187
936511AD2-066 C
Adder
8.5141176470588237.237
939061AE1-134 2
Adder
1.39647058823529411.187
941551AE2-152 C
80/20
11.79611.796
274676JOLIET 29;8U
80/20
76.23476.234
937401AD2-194 1
80/20
1.3081.308
274704KENDALL ;1C
80/20
4.1394.139
274706KENDALL ;2C
80/20
4.1394.139
274705KENDALL ;1S
80/20
2.7682.768
274847GR RIDGE ;BU
80/20
0.5960.596
958481AF2-142 C
Adder
10.8682352941176469.238
274661LASCO STA;2U
80/20
25.57725.577
276658AB1-122 CT1
80/20
11.86311.863
946321AF1-296 C
Adder
3.6188235294117653.076
274753CRETE EC ;3U
80/20
6.1116.111
274654BRAIDWOOD;1U
80/20
27.62627.626
274731ELWOOD EC;2P
80/20
3.3583.358
274861TOP CROP ;1U
80/20
0.4420.442
962781AG1-127 C
Adder
7.1670588235294126.092
933911AD1-013 C
Adder
1.88470588235294121.602
274711KENDALL ;4S
80/20
2.5942.594
934101AD2-000 1
80/20
5.8925.892
942421AE2-255 C
Adder
3.14941176470588242.677
926821AC1-168 C
Adder
1.16117647058823530.987
959611AF2-252 C
Adder
1.82117647058823541.548
958011AF2-095 C
Adder
10.2352941176470588.7
933411AC2-154 C
Adder
2.25058823529411761.913
274687WILL CNTY;4U
80/20
71.92771.927
966091AG1-478 C
Adder
2.00941176470588221.708
274733ELWOOD EC;3P
80/20
3.3583.358
966441AG1-513 C
Adder
0.52117647058823540.443
959081AF2-199 C
Adder
7.3070588235294126.211
942111AE2-223 C
Adder
1.86941176470588231.589
939741AE1-205 C
Adder
8.0529411764705886.845
274655BRAIDWOOD;2U
80/20
26.8826.88
276640AC1-204 GEN1
80/20
12.4912.49
959351AF2-226 C
80/20
2.9462.946
958491AF2-143 C
Adder
10.89.18
965931AG1-462 C
Adder
16.29411764705882213.85
274752CRETE EC ;2U
80/20
6.1116.111
936371AD2-047 C
Adder
4.0282352941176473.424
936461AD2-060 C
Adder
2.3694117647058822.014
274732ELWOOD EC;7P
80/20
3.3643.364
274730ELWOOD EC;6P
80/20
3.3643.364
276660AB1-122 CT2
80/20
12.70612.706
274739AURORA EC;2P
80/20
3.5563.556
946671AF1-331 C
Adder
2.4482352941176472.081
960611AF2-352 C
Adder
1.82117647058823541.548
274658DRESDEN ;2U
80/20
19.99619.996
274660LASCO STA;1U
80/20
25.49425.494
943591AF1-030 C
Adder
8.6717647058823537.371
274754CRETE EC ;4U
80/20
6.1116.111
934111AD2-000 2
80/20
6.316.31
274683WAUKEGAN ;8U
Adder
45.9152941176470639.028
937411AD2-194 2
80/20
1.3111.311
274737AURORA EC;1P
80/20
3.5563.556
274708KENDALL ;3C
80/20
3.9223.922
274734ELWOOD EC;8P
80/20
3.3643.364
274736ELWOOD EC;9P
80/20
3.3643.364
274735ELWOOD EC;4P
80/20
3.3583.358
274682WAUKEGAN ;7U
Adder
42.636.21
942651AE2-281 C
Adder
0.840.714
962691AG1-118 C
Adder
22.6929411764705919.289
938851AE1-113 C
Adder
8.3141176470588247.067
959091AF2-200 C
Adder
14.61529411764705912.423
959341AF2-225 C
Adder
6.0400000000000015.134
965091AG1-374 C
Adder
16.39058823529411813.932
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.25680.256
WECLTFEXP_WEC->PJM
CLTF
4.0134.013
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7050.705
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835
NYPJM->LTFIMP_NY
CLTF
1.1511.151
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
LAGNLTFEXP_LAGN->PJM
CLTF
3.2763.276
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.40713.407
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5760.576
MECLTFEXP_MEC->PJM
CLTF
13.15513.155
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0682.068

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.5 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1405.93
MW Contribution:3.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960591AF2-350 C
Adder
7.1082352941176476.042
934721AD1-100 C
80/20
3.0093.009
274728ELWOOD EC;5P
80/20
3.3643.364
274745AURORA EC;9P
80/20
1.0831.083
960751AF2-366 C
Adder
7.1470588235294126.075
274751CRETE EC ;1U
80/20
6.1116.111
274729ELWOOD EC;1P
80/20
3.3583.358
960281AF2-319 C
80/20
2.9462.946
957471AF2-041 C
Adder
21.9223529411764718.634
938861AE1-114 C
Adder
4.0129411764705883.411
961501AF2-441 C
Adder
6.6670588235294125.667
939351AE1-166 C
80/20
10.22310.223
274675JOLIET 29;7U
80/20
76.19176.191
274674JOLIET 9 ;6U
Adder
35.31176470588235430.015
943121AE2-341 C
Adder
13.0411.084
274862TOP CROP ;2U
80/20
0.8420.842
939321AE1-163 C
Adder
5.8800000000000014.998
274710KENDALL ;4C
80/20
3.8793.879
274709KENDALL ;3S
80/20
2.5942.594
276642AC1-204 GEN2
80/20
12.51212.512
274707KENDALL ;2S
80/20
2.7682.768
274871GR RIDGE ;2U
80/20
0.2220.222
957331AF2-027 C
Adder
2.5729411764705882.187
936511AD2-066 C
Adder
8.5141176470588237.237
939061AE1-134 2
Adder
1.39647058823529411.187
941551AE2-152 C
80/20
11.79611.796
274676JOLIET 29;8U
80/20
76.23476.234
937401AD2-194 1
80/20
1.3081.308
274704KENDALL ;1C
80/20
4.1394.139
274706KENDALL ;2C
80/20
4.1394.139
274705KENDALL ;1S
80/20
2.7682.768
274847GR RIDGE ;BU
80/20
0.5960.596
958481AF2-142 C
Adder
10.8682352941176469.238
274661LASCO STA;2U
80/20
25.57725.577
276658AB1-122 CT1
80/20
11.86311.863
946321AF1-296 C
Adder
3.6188235294117653.076
274753CRETE EC ;3U
80/20
6.1116.111
274654BRAIDWOOD;1U
80/20
27.62627.626
274731ELWOOD EC;2P
80/20
3.3583.358
274861TOP CROP ;1U
80/20
0.4420.442
962781AG1-127 C
Adder
7.1670588235294126.092
933911AD1-013 C
Adder
1.88470588235294121.602
274711KENDALL ;4S
80/20
2.5942.594
934101AD2-000 1
80/20
5.8925.892
942421AE2-255 C
Adder
3.14941176470588242.677
926821AC1-168 C
Adder
1.16117647058823530.987
959611AF2-252 C
Adder
1.82117647058823541.548
958011AF2-095 C
Adder
10.2352941176470588.7
933411AC2-154 C
Adder
2.25058823529411761.913
274687WILL CNTY;4U
80/20
71.92771.927
966091AG1-478 C
Adder
2.00941176470588221.708
274733ELWOOD EC;3P
80/20
3.3583.358
966441AG1-513 C
Adder
0.52117647058823540.443
959081AF2-199 C
Adder
7.3070588235294126.211
942111AE2-223 C
Adder
1.86941176470588231.589
939741AE1-205 C
Adder
8.0529411764705886.845
274655BRAIDWOOD;2U
80/20
26.8826.88
276640AC1-204 GEN1
80/20
12.4912.49
959351AF2-226 C
80/20
2.9462.946
958491AF2-143 C
Adder
10.89.18
965931AG1-462 C
Adder
16.29411764705882213.85
274752CRETE EC ;2U
80/20
6.1116.111
936371AD2-047 C
Adder
4.0282352941176473.424
936461AD2-060 C
Adder
2.3694117647058822.014
274732ELWOOD EC;7P
80/20
3.3643.364
274730ELWOOD EC;6P
80/20
3.3643.364
276660AB1-122 CT2
80/20
12.70612.706
274739AURORA EC;2P
80/20
3.5563.556
946671AF1-331 C
Adder
2.4482352941176472.081
960611AF2-352 C
Adder
1.82117647058823541.548
274658DRESDEN ;2U
80/20
19.99619.996
274660LASCO STA;1U
80/20
25.49425.494
943591AF1-030 C
Adder
8.6717647058823537.371
274754CRETE EC ;4U
80/20
6.1116.111
934111AD2-000 2
80/20
6.316.31
274683WAUKEGAN ;8U
Adder
45.9152941176470639.028
937411AD2-194 2
80/20
1.3111.311
274737AURORA EC;1P
80/20
3.5563.556
274708KENDALL ;3C
80/20
3.9223.922
274734ELWOOD EC;8P
80/20
3.3643.364
274736ELWOOD EC;9P
80/20
3.3643.364
274735ELWOOD EC;4P
80/20
3.3583.358
274682WAUKEGAN ;7U
Adder
42.636.21
942651AE2-281 C
Adder
0.840.714
962691AG1-118 C
Adder
22.6929411764705919.289
938851AE1-113 C
Adder
8.3141176470588247.067
959091AF2-200 C
Adder
14.61529411764705912.423
959341AF2-225 C
Adder
6.0400000000000015.134
965091AG1-374 C
Adder
16.39058823529411813.932
NYPJM->LTFIMP_NY
CLTF
1.1511.151
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
LAGNLTFEXP_LAGN->PJM
CLTF
3.2763.276
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0682.068
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.25680.256
WECLTFEXP_WEC->PJM
CLTF
4.0134.013
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7050.705
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.40713.407
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5760.576
MECLTFEXP_MEC->PJM
CLTF
13.15513.155

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4-6_116-345-R______SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_116-345-R______SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.57 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2471.0
MW Contribution:17.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274728ELWOOD EC;5P
50/50
5.1145.114
960751AF2-366 C
Adder
5.035294117647064.28
942422AE2-255 E
Adder
11.99176470588235310.193
960582AF2-349 E
Adder
29.2670588235294124.877
937312AD2-172 E
Adder
2.74941176470588242.337
274859EASYR;U1 E
Adder
9.8505882352941178.373
274729ELWOOD EC;1P
50/50
5.0895.089
293644O22 E1
50/50
33.48133.481
960281AF2-319 C
50/50
5.8285.828
960752AF2-366 E
Adder
3.35647058823529452.853
957471AF2-041 C
Adder
17.23882352941176414.653
294763P-046 E
Adder
7.6411764705882366.495
938861AE1-114 C
Adder
3.19411764705882332.715
274675JOLIET 29;7U
Adder
83.9305882352941171.341
943121AE2-341 C
Adder
7.6458823529411766.499
274862TOP CROP ;2U
50/50
1.6661.666
939321AE1-163 C
Adder
7.26941176470588256.179
295111SUBLETTE E
Adder
2.041.734
274860EASYR;U2 E
Adder
9.8505882352941178.373
927209AC1-214 E2
Adder
2.69411764705882372.29
946322AF1-296 E
Adder
14.17411764705882312.048
276640AC1-204 GEN1
50/50
18.92818.928
959351AF2-226 C
50/50
5.8285.828
958491AF2-143 C
Adder
13.35058823529411911.348
933912AD1-013 E
Adder
2.19882352941176461.869
946152AF1-280 E
Adder
18.7352941176470615.925
293771O-035 E
Adder
5.6823529411764714.83
293716O-029 E
Adder
4.4564705882352943.788
965931AG1-462 C
Adder
13.77411764705882511.708
276642AC1-204 GEN2
50/50
19.02419.024
957331AF2-027 C
Adder
2.0988235294117651.784
936511AD2-066 C
Adder
7.0129411764705895.961
936512AD2-066 E
Adder
4.6752941176470593.974
295109WESTBROOK E
Adder
4.197647058823533.568
939061AE1-134 2
Adder
1.13411764705882350.964
990901L-005 E
Adder
11.329.622
274676JOLIET 29;8U
Adder
84.2188235294117671.586
937401AD2-194 1
50/50
1.9831.983
958481AF2-142 C
Adder
13.19647058823529511.217
957332AF2-027 E
Adder
3.14705882352941172.675
926822AC1-168 E
Adder
5.1858823529411774.408
943122AE2-341 E
Adder
3.75411764705882333.191
939322AE1-163 E
Adder
44.6517647058823637.954
927208AC1-214 E1
Adder
2.69411764705882372.29
293516O-009 E
Adder
15.7152941176470613.358
293717O-029 E
Adder
4.0952941176470593.481
946321AF1-296 C
Adder
3.02705882352941162.573
274861TOP CROP ;1U
50/50
0.8730.873
276591L-013 2
Adder
2.7541176470588242.341
962781AG1-127 C
Adder
5.0494117647058834.292
933911AD1-013 C
Adder
1.37647058823529411.17
959352AF2-226 E
50/50
8.7428.742
934101AD2-000 1
Adder
5.88705882352941155.004
958492AF2-143 E
Adder
8.9011764705882357.566
942421AE2-255 C
Adder
3.99764705882352983.398
290108LEEDK;1U E
Adder
17.4505882352941214.833
916221Z1-073 E
Adder
5.5247058823529414.696
957472AF2-041 E
Adder
8.6188235294117657.326
959092AF2-200 E
Adder
7.6611764705882356.512
926821AC1-168 C
Adder
0.77294117647058820.657
938862AE1-114 E
Adder
10.8952941176470589.261
966091AG1-478 C
Adder
1.16588235294117660.991
274733ELWOOD EC;3P
50/50
5.0895.089
966441AG1-513 C
Adder
0.364705882352941160.31
959081AF2-199 C
Adder
5.7458823529411774.884
916212CRESCENT ;1U
Adder
3.9917647058823533.393
294410BSHIL;2U E
Adder
7.4129411764705886.301
966822AG1-553 E
Adder
23.40705882352941519.896
274732ELWOOD EC;7P
50/50
5.1145.114
274730ELWOOD EC;6P
50/50
5.1145.114
962782AG1-127 E
Adder
3.362.856
946671AF1-331 C
Adder
1.78823529411764711.52
934111AD2-000 2
Adder
7.8929411764705886.709
966442AG1-513 E
Adder
0.54705882352941180.465
293645O22 E2
50/50
38.34738.347
960282AF2-319 E
50/50
8.7428.742
918052AA1-018 E OP
Adder
19.13411764705882216.264
293715O-029 E
Adder
8.1270588235294126.908
943592AF1-030 E
Adder
2.51529411764705872.138
943591AF1-030 C
Adder
5.0847058823529414.322
936292AD2-038 E
Adder
18.3352941176470615.585
290021O50 E
Adder
25.58117647058823621.744
937002AD2-134 E
Adder
7.586.443
274683WAUKEGAN ;8U
Adder
37.50470588235294431.879
290051GSG-6; E
Adder
7.846.664
959082AF2-199 E
Adder
2.87294117647058832.442
958912AF2-182 E
Adder
28.10235294117647323.887
294401BSHIL;1U E
Adder
7.4129411764705886.301
937411AD2-194 2
50/50
1.9931.993
958482AF2-142 E
Adder
8.7976470588235297.478
938852AE1-113 E
Adder
37.4129411764705931.801
962012AG1-044 E
Adder
0.051764705882352940.044
925582AC1-033 E
Adder
8.1270588235294126.908
966092AG1-478 E
Adder
0.292941176470588260.249
274734ELWOOD EC;8P
50/50
5.1145.114
274736ELWOOD EC;9P
50/50
5.1145.114
274735ELWOOD EC;4P
50/50
5.0895.089
274682WAUKEGAN ;7U
Adder
34.8294117647058829.605
942651AE2-281 C
Adder
1.03882352941176470.883
942652AE2-281 E
Adder
6.3788235294117655.422
962691AG1-118 C
Adder
15.91411764705882313.527
962692AG1-118 E
Adder
10.6094117647058849.018
938851AE1-113 C
Adder
10.552941176470598.97
272363ESS H440 ; R
Adder
1.96705882352941171.672
959091AF2-200 C
Adder
11.4917647058823539.768
940502AE2-035 E
Adder
2.74941176470588242.337
965932AG1-462 E
Adder
9.1835294117647067.806
276170Z1-108 E
Adder
2.35294117647058832
920272AA2-123 E
Adder
2.3082352941176471.962
276626AG1-044 E
Adder
0.061176470588235290.052
990547J1333 G
External Queue
-23.77029800415039-23.77029800415039
990582J1340
External Queue
-28.123506546020508-28.123506546020508
990662J1358
External Queue
-12.060297966003418-12.060297966003418
990552J1334 G
External Queue
-23.77029800415039-23.77029800415039
990557J1335 G
External Queue
-23.77029800415039-23.77029800415039
990562J1336 G
External Queue
-23.77029800415039-23.77029800415039
990577J1339
External Queue
-28.123506546020508-28.123506546020508
990647J1355
External Queue
-10.193851470947266-10.193851470947266
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.268.2
NYPJM->LTFIMP_NY
CLTF
0.6860.686
TVALTFEXP_TVA->PJM
CLTF
1.2761.276
LAGNLTFEXP_LAGN->PJM
CLTF
3.1343.134
G-007PJM->LTFIMP_G-007
CMTX_NF
1.2681.268
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1170.117
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.1491.149
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.94111.941
WECLTFEXP_WEC->PJM
CLTF
3.283.28
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.3970.397
O66PJM->LTFIMP_O-066
CMTX_NF
8.148.14
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2450.245
MECLTFEXP_MEC->PJM
CLTF
11.3111.31
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.3820.382

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614__SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_116-45-L11614__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.27 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2372.1
MW Contribution:15.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274728ELWOOD EC;5P
50/50
5.0335.033
960751AF2-366 C
Adder
4.3105882352941183.664
942422AE2-255 E
Adder
11.5717647058823539.836
960582AF2-349 E
Adder
24.51176470588235320.835
937312AD2-172 E
Adder
2.3423529411764711.991
274859EASYR;U1 E
Adder
8.4917647058823537.218
274729ELWOOD EC;1P
50/50
5.0055.005
293644O22 E1
50/50
34.23434.234
960281AF2-319 C
50/50
5.9595.959
960752AF2-366 E
Adder
2.87294117647058832.442
957471AF2-041 C
Adder
14.92470588235294212.686
294763P-046 E
Adder
6.5117647058823535.535
938861AE1-114 C
Adder
2.74470588235294162.333
274675JOLIET 29;7U
Adder
63.4341176470588253.919
943121AE2-341 C
Adder
6.5717647058823535.586
274862TOP CROP ;2U
50/50
1.7031.703
939321AE1-163 C
Adder
7.1317647058823546.062
295111SUBLETTE E
Adder
1.7588235294117651.495
274860EASYR;U2 E
Adder
8.4917647058823537.218
927209AC1-214 E2
Adder
2.50588235294117642.13
946322AF1-296 E
Adder
12.50235294117647210.627
276640AC1-204 GEN1
50/50
18.61918.619
959351AF2-226 C
50/50
5.9595.959
958491AF2-143 C
Adder
13.09882352941176511.134
933912AD1-013 E
Adder
1.89411764705882371.61
946152AF1-280 E
Adder
16.2023529411764713.772
293771O-035 E
Adder
5.2858823529411774.493
293716O-029 E
Adder
3.95294117647058843.36
965931AG1-462 C
Adder
12.18352941176470610.356
276642AC1-204 GEN2
50/50
18.72218.722
957331AF2-027 C
Adder
1.69529411764705881.441
936511AD2-066 C
Adder
6.53294117647058855.553
936512AD2-066 E
Adder
4.3552941176470593.702
295109WESTBROOK E
Adder
3.6164705882352943.074
939061AE1-134 2
Adder
0.98823529411764710.84
990901L-005 E
Adder
10.5717647058823538.986
274676JOLIET 29;8U
Adder
63.8752941176470654.294
937401AD2-194 1
50/50
1.951.95
958481AF2-142 C
Adder
12.96117647058823511.017
957332AF2-027 E
Adder
2.54235294117647072.161
926822AC1-168 E
Adder
4.8552941176470594.127
943122AE2-341 E
Adder
3.22705882352941182.743
939322AE1-163 E
Adder
43.8082352941176537.237
927208AC1-214 E1
Adder
2.50588235294117642.13
293516O-009 E
Adder
13.94235294117647211.851
293717O-029 E
Adder
3.63411764705882373.089
946321AF1-296 C
Adder
2.6705882352941182.27
274731ELWOOD EC;2P
50/50
5.0055.005
274861TOP CROP ;1U
50/50
0.8930.893
276591L-013 2
Adder
2.32235294117647051.974
962781AG1-127 C
Adder
4.32235294117647053.674
933911AD1-013 C
Adder
1.18588235294117661.008
959352AF2-226 E
50/50
8.9388.938
934101AD2-000 1
Adder
5.4164705882352954.604
958492AF2-143 E
Adder
8.7329411764705887.423
942421AE2-255 C
Adder
3.8576470588235293.279
290108LEEDK;1U E
Adder
14.98705882352941312.739
916221Z1-073 E
Adder
4.7611764705882354.047
957472AF2-041 E
Adder
7.4623529411764716.343
959092AF2-200 E
Adder
6.6329411764705885.638
926821AC1-168 C
Adder
0.72352941176470590.615
938862AE1-114 E
Adder
9.3635294117647067.959
966091AG1-478 C
Adder
1.06705882352941180.907
274733ELWOOD EC;3P
50/50
5.0055.005
966441AG1-513 C
Adder
0.30705882352941180.261
959081AF2-199 C
Adder
4.9752941176470594.229
916212CRESCENT ;1U
Adder
3.71294117647058863.156
294410BSHIL;2U E
Adder
6.8764705882352945.845
966822AG1-553 E
Adder
20.70352941176470617.598
274732ELWOOD EC;7P
50/50
5.0335.033
274730ELWOOD EC;6P
50/50
5.0335.033
962782AG1-127 E
Adder
2.8764705882352942.445
946671AF1-331 C
Adder
1.541.309
293645O22 E2
50/50
39.2139.21
960282AF2-319 E
50/50
8.9388.938
918052AA1-018 E OP
Adder
18.79411764705882215.975
293715O-029 E
Adder
7.2105882352941176.129
943592AF1-030 E
Adder
2.1623529411764711.838
943591AF1-030 C
Adder
4.3694117647058823.714
936292AD2-038 E
Adder
17.98823529411764715.29
290021O50 E
Adder
24.68705882352941620.984
937002AD2-134 E
Adder
6.53176470588235255.552
934111AD2-000 2
Adder
7.502352941176476.377
966442AG1-513 E
Adder
0.46117647058823530.392
274683WAUKEGAN ;8U
Adder
30.27176470588235425.731
290051GSG-6; E
Adder
6.7552941176470595.742
959082AF2-199 E
Adder
2.48705882352941152.114
958912AF2-182 E
Adder
24.30352941176470720.658
294401BSHIL;1U E
Adder
6.8764705882352945.845
937411AD2-194 2
50/50
1.9611.961
958482AF2-142 E
Adder
8.6411764705882357.345
938852AE1-113 E
Adder
36.10470588235294530.689
962012AG1-044 E
Adder
0.045882352941176470.039
925582AC1-033 E
Adder
7.5388235294117656.408
966092AG1-478 E
Adder
0.268235294117647070.228
274734ELWOOD EC;8P
50/50
5.0335.033
274736ELWOOD EC;9P
50/50
5.0335.033
274682WAUKEGAN ;7U
Adder
28.12352941176470723.905
942651AE2-281 C
Adder
1.01882352941176470.866
942652AE2-281 E
Adder
6.2588235294117665.32
962691AG1-118 C
Adder
13.63294117647058811.588
962692AG1-118 E
Adder
9.0882352941176477.725
938851AE1-113 C
Adder
10.1835294117647088.656
272363ESS H440 ; R
Adder
1.69529411764705881.441
959091AF2-200 C
Adder
9.9494117647058848.457
940502AE2-035 E
Adder
2.3423529411764711.991
965932AG1-462 E
Adder
8.1223529411764716.904
920272AA2-123 E
Adder
1.92705882352941171.638
276170Z1-108 E
Adder
1.94588235294117641.654
276626AG1-044 E
Adder
0.054117647058823530.046
990547J1333 G
External Queue
-22.909955978393555-22.909955978393555
990582J1340
External Queue
-27.099620819091797-27.099620819091797
990662J1358
External Queue
-11.463173866271973-11.463173866271973
990552J1334 G
External Queue
-22.909955978393555-22.909955978393555
990557J1335 G
External Queue
-22.909955978393555-22.909955978393555
990562J1336 G
External Queue
-22.909955978393555-22.909955978393555
990577J1339
External Queue
-27.099620819091797-27.099620819091797
990647J1355
External Queue
-9.393627166748047-9.393627166748047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.99810.998
WECLTFEXP_WEC->PJM
CLTF
2.6952.695
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.3610.361
SIGELTFEXP_SIGE->PJM
CLTF
00
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.86656.866
NYPJM->LTFIMP_NY
CLTF
0.630.63
TVALTFEXP_TVA->PJM
CLTF
1.1651.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.8362.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2250.225
MECLTFEXP_MEC->PJM
CLTF
10.03810.038
O66PJM->LTFIMP_O-066
CMTX_NF
7.4827.482
G-007PJM->LTFIMP_G-007
CMTX_NF
1.1661.166
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1080.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.0441.044
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.3520.352

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-45-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.41 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2306.47
MW Contribution:18.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274728ELWOOD EC;5P
50/50
4.7054.705
960751AF2-366 C
Adder
5.50588235294117644.68
942422AE2-255 E
Adder
12.25411764705882510.416
960582AF2-349 E
Adder
32.12588235294117627.307
937312AD2-172 E
Adder
3.01647058823529422.564
274859EASYR;U1 E
Adder
10.7905882352941189.172
274729ELWOOD EC;1P
50/50
4.6474.647
293644O22 E1
50/50
40.99540.995
960281AF2-319 C
50/50
7.1367.136
960752AF2-366 E
Adder
3.6705882352941183.12
957471AF2-041 C
Adder
18.82352941176470716
294763P-046 E
Adder
8.3823529411764717.125
938861AE1-114 C
Adder
3.52.975
274675JOLIET 29;7U
Adder
91.0294117647058877.375
943121AE2-341 C
Adder
8.3105882352941187.064
274862TOP CROP ;2U
50/50
2.0392.039
939321AE1-163 C
Adder
4.5952941176470593.906
295111SUBLETTE E
Adder
2.2317647058823531.897
274860EASYR;U2 E
Adder
10.7905882352941189.172
927209AC1-214 E2
Adder
2.92941176470588262.49
946322AF1-296 E
Adder
15.54588235294117713.214
276640AC1-204 GEN1
50/50
17.28517.285
959351AF2-226 C
50/50
7.1367.136
958491AF2-143 C
Adder
8.4411764705882367.175
933912AD1-013 E
Adder
2.40470588235294122.044
946152AF1-280 E
Adder
20.51882352941176517.441
276642AC1-204 GEN2
50/50
17.50217.502
274707KENDALL ;2S
50/50
3.9613.961
957331AF2-027 C
Adder
2.3352941176470591.985
936511AD2-066 C
Adder
7.3411764705882366.24
936512AD2-066 E
Adder
4.8941176470588244.16
295109WESTBROOK E
Adder
4.5905882352941183.902
939061AE1-134 2
Adder
1.24117647058823531.055
990901L-005 E
Adder
12.28823529411764810.445
290261S-027 E
Adder
12.5152941176470610.638
290265S-028 E
Adder
12.43882352941176510.573
274676JOLIET 29;8U
Adder
91.5117647058823677.785
937401AD2-194 1
50/50
1.8111.811
274704KENDALL ;1C
50/50
5.9235.923
274706KENDALL ;2C
50/50
5.9235.923
274705KENDALL ;1S
50/50
3.9613.961
957332AF2-027 E
Adder
3.50235294117647072.977
926822AC1-168 E
Adder
5.5847058823529414.747
943122AE2-341 E
Adder
4.0811764705882353.469
939322AE1-163 E
Adder
28.22941176470588323.995
927208AC1-214 E1
Adder
2.92941176470588262.49
293516O-009 E
Adder
17.15882352941176614.585
293717O-029 E
Adder
4.4717647058823533.801
946321AF1-296 C
Adder
3.32000000000000032.822
274731ELWOOD EC;2P
50/50
4.6474.647
274861TOP CROP ;1U
50/50
1.0691.069
276591L-013 2
Adder
3.00235294117647072.552
962781AG1-127 C
Adder
5.5211764705882354.693
933911AD1-013 C
Adder
1.50588235294117641.28
959352AF2-226 E
50/50
10.70410.704
934101AD2-000 1
Adder
5.8152941176470594.943
958492AF2-143 E
Adder
5.6270588235294134.783
942421AE2-255 C
Adder
4.0847058823529413.472
290108LEEDK;1U E
Adder
19.07882352941176416.217
916221Z1-073 E
Adder
6.0411764705882355.135
957472AF2-041 E
Adder
9.4117647058823538
959092AF2-200 E
Adder
8.3658823529411767.111
926821AC1-168 C
Adder
0.8317647058823530.707
938862AE1-114 E
Adder
11.94117647058823610.15
959611AF2-252 C
Adder
1.53411764705882361.304
966441AG1-513 C
Adder
0.396470588235294130.337
959081AF2-199 C
Adder
6.2741176470588245.333
916212CRESCENT ;1U
Adder
4.343.689
294410BSHIL;2U E
Adder
8.0376470588235296.832
917502Z2-087 E
Adder
13.85882352941176311.78
942111AE2-223 C
Adder
1.55294117647058831.32
939741AE1-205 C
Adder
6.6905882352941185.687
960612AF2-352 E
Adder
2.30117647058823541.956
966822AG1-553 E
Adder
25.66705882352941321.817
293771O-035 E
Adder
6.177647058823535.251
293716O-029 E
Adder
4.8658823529411774.136
939742AE1-205 E
Adder
9.247.854
965931AG1-462 C
Adder
15.10352941176470612.838
274732ELWOOD EC;7P
50/50
4.7054.705
274730ELWOOD EC;6P
50/50
4.7054.705
962782AG1-127 E
Adder
3.67411764705882373.123
946671AF1-331 C
Adder
1.95529411764705881.662
960611AF2-352 C
Adder
1.53411764705882361.304
293645O22 E2
50/50
46.95446.954
960282AF2-319 E
50/50
10.70410.704
293715O-029 E
Adder
8.8741176470588247.543
943592AF1-030 E
Adder
2.73411764705882332.324
943591AF1-030 C
Adder
5.5270588235294124.698
936292AD2-038 E
Adder
11.5917647058823539.853
290021O50 E
Adder
26.14235294117647322.221
937002AD2-134 E
Adder
8.2894117647058827.046
934111AD2-000 2
Adder
8.1694117647058836.944
966442AG1-513 E
Adder
0.59411764705882350.505
274683WAUKEGAN ;8U
Adder
41.79647058823529435.527
290051GSG-6; E
Adder
8.5729411764705887.287
959082AF2-199 E
Adder
3.13764705882352952.667
958912AF2-182 E
Adder
30.77764705882353326.161
294401BSHIL;1U E
Adder
8.0376470588235296.832
942112AE2-223 E
Adder
10.3941176470588268.835
959612AF2-252 E
Adder
2.30117647058823541.956
937411AD2-194 2
50/50
1.8341.834
938852AE1-113 E
Adder
38.2329411764705932.498
962012AG1-044 E
Adder
0.056470588235294120.048
925582AC1-033 E
Adder
8.8105882352941187.489
924049AB2-047 E2
Adder
8.7294117647058837.42
959342AF2-225 E
Adder
6.9294117647058825.89
274734ELWOOD EC;8P
50/50
4.7054.705
274736ELWOOD EC;9P
50/50
4.7054.705
274735ELWOOD EC;4P
50/50
4.6474.647
274682WAUKEGAN ;7U
Adder
38.8423529411764733.016
942651AE2-281 C
Adder
0.65647058823529430.558
942652AE2-281 E
Adder
4.03294117647058853.428
962691AG1-118 C
Adder
17.414.79
962692AG1-118 E
Adder
11.69.86
938851AE1-113 C
Adder
10.7835294117647079.166
272363ESS H440 ; R
Adder
2.1517647058823531.829
959091AF2-200 C
Adder
12.54823529411764810.666
940502AE2-035 E
Adder
3.01647058823529422.564
924048AB2-047 E1
Adder
8.5941176470588237.305
959341AF2-225 C
Adder
5.0176470588235294.265
965092AG1-374 E
Adder
9.2023529411764717.822
965091AG1-374 C
Adder
13.80470588235294111.734
965932AG1-462 E
Adder
10.0694117647058818.559
276626AG1-044 E
Adder
0.067058823529411770.057
920272AA2-123 E
Adder
2.53411764705882362.154
276170Z1-108 E
Adder
2.58588235294117652.198
990497J1323
External Queue
-1.8008151054382324-1.8008151054382324
990547J1333 G
External Queue
-25.95514488220215-25.95514488220215
990582J1340
External Queue
-28.660625457763672-28.660625457763672
990662J1358
External Queue
-13.962589263916016-13.962589263916016
991182J1586 G
External Queue
-35.323299407958984-35.323299407958984
990552J1334 G
External Queue
-25.95514488220215-25.95514488220215
990557J1335 G
External Queue
-25.95514488220215-25.95514488220215
990562J1336 G
External Queue
-25.95514488220215-25.95514488220215
990577J1339
External Queue
-28.660625457763672-28.660625457763672
990647J1355
External Queue
-11.565272331237793-11.565272331237793
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.95815.958
WECLTFEXP_WEC->PJM
CLTF
3.6463.646
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.3060.306
SIGELTFEXP_SIGE->PJM
CLTF
0.0390.039
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.48876.488
NYPJM->LTFIMP_NY
CLTF
0.7040.704
TVALTFEXP_TVA->PJM
CLTF
1.831.83
LAGNLTFEXP_LAGN->PJM
CLTF
3.9933.993
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1710.171
MECLTFEXP_MEC->PJM
CLTF
12.68312.683
O66PJM->LTFIMP_O-066
CMTX_NF
8.3278.327
G-007PJM->LTFIMP_G-007
CMTX_NF
1.2971.297
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0650.065
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.8420.842
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.2990.299

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.43 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1226.4
MW Contribution:14.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
275149KELLYCK ;1E
Adder
15.63058823529411813.286
934722AD1-100 E
Adder
76.7823529411764765.265
960751AF2-366 C
Adder
5.9247058823529415.036
942422AE2-255 E
Adder
7.6658823529411776.516
960582AF2-349 E
Adder
30.726.095
937312AD2-172 E
Adder
2.8647058823529412.435
274859EASYR;U1 E
Adder
10.1270588235294138.608
293644O22 E1
Adder
11.6458823529411759.899
961501AF2-441 C
Adder
7.2070588235294136.126
293519PILOT HIL;1E
Adder
15.63058823529411813.286
939351AE1-166 C
Adder
8.555294117647067.272
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
293061N-015 E
Adder
13.20352941176470711.223
943121AE2-341 C
Adder
10.8588235294117659.23
939321AE1-163 C
Adder
5.3388235294117654.538
295111SUBLETTE E
Adder
2.3082352941176471.962
274860EASYR;U2 E
Adder
10.1270588235294138.608
927209AC1-214 E2
Adder
2.7435294117647062.332
946322AF1-296 E
Adder
5.1964705882352944.417
957331AF2-027 C
Adder
2.1211764705882351.803
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
295109WESTBROOK E
Adder
4.7482352941176474.036
939061AE1-134 2
Adder
1.15294117647058810.98
274813UNIV PK N;9U
50/50
1.9091.909
274811UNIV PK N;7U
50/50
1.9251.925
961502AF2-441 E
Adder
10.8105882352941189.189
943122AE2-341 E
Adder
5.3317647058823534.532
939322AE1-163 E
Adder
32.7952941176470627.876
927208AC1-214 E1
Adder
2.7435294117647062.332
293516O-009 E
Adder
15.8423529411764713.466
293717O-029 E
Adder
4.1282352941176473.509
936372AD2-047 E
Adder
18.53411764705882415.754
276591L-013 2
Adder
3.11882352941176462.651
962781AG1-127 C
Adder
5.94117647058823555.05
933911AD1-013 C
Adder
1.56117647058823541.327
910542X3-005 E
Adder
0.53764705882352950.457
939352AE1-166 E
Adder
7.897647058823536.713
294392P-010 E
Adder
16.76941176470588214.254
959352AF2-226 E
Adder
3.0411764705882352.585
934101AD2-000 1
Adder
4.91411764705882354.177
958492AF2-143 E
Adder
6.537647058823535.557
942421AE2-255 C
Adder
2.5552941176470592.172
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
957472AF2-041 E
Adder
9.0400000000000017.684
959092AF2-200 E
Adder
8.0352941176470596.83
926821AC1-168 C
Adder
0.96235294117647050.818
938862AE1-114 E
Adder
11.315294117647069.618
274814UNIV PK N;0U
50/50
1.9011.901
274807UNIV PK N;3U
50/50
1.9251.925
274816UNIV PK N;YU
50/50
1.9251.925
958011AF2-095 C
Adder
9.6458823529411778.199
933411AC2-154 C
Adder
2.1211764705882351.803
274687WILL CNTY;4U
Adder
56.08235294117647447.67
966091AG1-478 C
Adder
1.76941176470588251.504
966441AG1-513 C
Adder
0.434117647058823550.369
959081AF2-199 C
Adder
6.0258823529411775.122
916212CRESCENT ;1U
Adder
4.0658823529411773.456
294410BSHIL;2U E
Adder
7.2082352941176476.127
274808UNIV PK N;4U
50/50
1.9171.917
959351AF2-226 C
Adder
2.0270588235294121.723
958491AF2-143 C
Adder
9.8058823529411778.335
933912AD1-013 E
Adder
2.49411764705882362.12
946152AF1-280 E
Adder
19.1976470588235316.318
293771O-035 E
Adder
5.7870588235294124.919
293716O-029 E
Adder
4.4917647058823533.818
936371AD2-047 C
Adder
3.7964705882352943.227
936461AD2-060 C
Adder
2.2329411764705881.898
933412AC2-154 E
Adder
3.46117647058823552.942
962782AG1-127 E
Adder
3.9541176470588243.361
946671AF1-331 C
Adder
2.0282352941176471.724
960281AF2-319 C
Adder
2.0270588235294121.723
960752AF2-366 E
Adder
3.94941176470588263.357
957471AF2-041 C
Adder
18.07882352941176815.367
294763P-046 E
Adder
7.9611764705882366.767
938861AE1-114 C
Adder
3.3164705882352942.819
293645O22 E2
Adder
13.33882352941176411.338
960282AF2-319 E
Adder
3.0411764705882352.585
918052AA1-018 E OP
Adder
14.9023529411764712.667
293715O-029 E
Adder
8.1929411764705896.964
274805UNIV PK N;1U
50/50
1.9131.913
943592AF1-030 E
Adder
3.5729411764705883.037
943591AF1-030 C
Adder
7.2211764705882366.138
936292AD2-038 E
Adder
13.46705882352941211.447
290021O50 E
Adder
16.3552941176470613.902
937002AD2-134 E
Adder
8.5752941176470587.289
274815UNIV PK N;XU
50/50
1.9131.913
958012AF2-095 E
Adder
6.4305882352941185.466
934111AD2-000 2
Adder
5.0882352941176484.325
966442AG1-513 E
Adder
0.65058823529411770.553
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
290051GSG-6; E
Adder
8.8682352941176487.538
959082AF2-199 E
Adder
3.01294117647058852.561
958912AF2-182 E
Adder
28.79647058823529424.477
294401BSHIL;1U E
Adder
7.2082352941176476.127
941551AE2-152 C
Adder
9.8717647058823528.391
274676JOLIET 29;8U
Adder
62.29647058823529452.952
958481AF2-142 C
Adder
10.2776470588235318.736
957332AF2-027 E
Adder
3.1823529411764712.705
274891CAYUG;2U E
Adder
11.4552941176470599.737
926822AC1-168 E
Adder
6.4588235294117655.49
274810UNIV PK N;6U
50/50
1.9171.917
274812UNIV PK N;8U
50/50
1.9091.909
941552AE2-152 E
Adder
6.5811764705882365.594
958482AF2-142 E
Adder
6.8517647058823535.824
938852AE1-113 E
Adder
23.91882352941176420.331
274890CAYUG;1U E
Adder
11.4552941176470599.737
962012AG1-044 E
Adder
0.0529411764705882350.045
925582AC1-033 E
Adder
7.9023529411764716.717
966092AG1-478 E
Adder
0.44470588235294120.378
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
938851AE1-113 C
Adder
6.7458823529411775.734
272363ESS H440 ; R
Adder
2.22941176470588241.895
959091AF2-200 C
Adder
12.05294117647058810.245
940502AE2-035 E
Adder
2.8647058823529412.435
276675AE2-062 E
Adder
0.135294117647058840.115
276626AG1-044 E
Adder
0.062352941176470590.053
276170Z1-108 E
Adder
2.48588235294117642.113
920272AA2-123 E
Adder
2.4364705882352942.071
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
NYPJM->LTFIMP_NY
CLTF
0.9330.933
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.43 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1226.4
MW Contribution:14.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
275149KELLYCK ;1E
Adder
15.63058823529411813.286
934722AD1-100 E
Adder
76.7823529411764765.265
960751AF2-366 C
Adder
5.9247058823529415.036
942422AE2-255 E
Adder
7.6658823529411776.516
960582AF2-349 E
Adder
30.726.095
937312AD2-172 E
Adder
2.8647058823529412.435
274859EASYR;U1 E
Adder
10.1270588235294138.608
961501AF2-441 C
Adder
7.2070588235294136.126
293519PILOT HIL;1E
Adder
15.63058823529411813.286
939351AE1-166 C
Adder
8.555294117647067.272
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
293061N-015 E
Adder
13.20352941176470711.223
943121AE2-341 C
Adder
10.8588235294117659.23
939321AE1-163 C
Adder
5.3388235294117654.538
295111SUBLETTE E
Adder
2.3082352941176471.962
274860EASYR;U2 E
Adder
10.1270588235294138.608
927209AC1-214 E2
Adder
2.7435294117647062.332
946322AF1-296 E
Adder
5.1964705882352944.417
957331AF2-027 C
Adder
2.1211764705882351.803
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
295109WESTBROOK E
Adder
4.7482352941176474.036
939061AE1-134 2
Adder
1.15294117647058810.98
961502AF2-441 E
Adder
10.8105882352941189.189
943122AE2-341 E
Adder
5.3317647058823534.532
939322AE1-163 E
Adder
32.7952941176470627.876
927208AC1-214 E1
Adder
2.7435294117647062.332
293516O-009 E
Adder
15.8423529411764713.466
293717O-029 E
Adder
4.1282352941176473.509
936372AD2-047 E
Adder
18.53411764705882415.754
276591L-013 2
Adder
3.11882352941176462.651
962781AG1-127 C
Adder
5.94117647058823555.05
933911AD1-013 C
Adder
1.56117647058823541.327
910542X3-005 E
Adder
0.53764705882352950.457
939352AE1-166 E
Adder
7.897647058823536.713
294392P-010 E
Adder
16.76941176470588214.254
959352AF2-226 E
Adder
3.0411764705882352.585
934101AD2-000 1
Adder
4.91411764705882354.177
958492AF2-143 E
Adder
6.537647058823535.557
942421AE2-255 C
Adder
2.5552941176470592.172
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
957472AF2-041 E
Adder
9.0400000000000017.684
959092AF2-200 E
Adder
8.0352941176470596.83
926821AC1-168 C
Adder
0.96235294117647050.818
938862AE1-114 E
Adder
11.315294117647069.618
274814UNIV PK N;0U
50/50
1.9011.901
274807UNIV PK N;3U
50/50
1.9251.925
274816UNIV PK N;YU
50/50
1.9251.925
958011AF2-095 C
Adder
9.6458823529411778.199
933411AC2-154 C
Adder
2.1211764705882351.803
274687WILL CNTY;4U
Adder
56.08235294117647447.67
966091AG1-478 C
Adder
1.76941176470588251.504
966441AG1-513 C
Adder
0.434117647058823550.369
959081AF2-199 C
Adder
6.0258823529411775.122
916212CRESCENT ;1U
Adder
4.0658823529411773.456
294410BSHIL;2U E
Adder
7.2082352941176476.127
274808UNIV PK N;4U
50/50
1.9171.917
959351AF2-226 C
Adder
2.0270588235294121.723
958491AF2-143 C
Adder
9.8058823529411778.335
933912AD1-013 E
Adder
2.49411764705882362.12
946152AF1-280 E
Adder
19.1976470588235316.318
293771O-035 E
Adder
5.7870588235294124.919
293716O-029 E
Adder
4.4917647058823533.818
936371AD2-047 C
Adder
3.7964705882352943.227
936461AD2-060 C
Adder
2.2329411764705881.898
933412AC2-154 E
Adder
3.46117647058823552.942
962782AG1-127 E
Adder
3.9541176470588243.361
946671AF1-331 C
Adder
2.0282352941176471.724
293644O22 E1
Adder
11.6458823529411759.899
960281AF2-319 C
Adder
2.0270588235294121.723
960752AF2-366 E
Adder
3.94941176470588263.357
957471AF2-041 C
Adder
18.07882352941176815.367
294763P-046 E
Adder
7.9611764705882366.767
938861AE1-114 C
Adder
3.3164705882352942.819
293645O22 E2
Adder
13.33882352941176411.338
960282AF2-319 E
Adder
3.0411764705882352.585
918052AA1-018 E OP
Adder
14.9023529411764712.667
293715O-029 E
Adder
8.1929411764705896.964
274805UNIV PK N;1U
50/50
1.9131.913
943592AF1-030 E
Adder
3.5729411764705883.037
943591AF1-030 C
Adder
7.2211764705882366.138
936292AD2-038 E
Adder
13.46705882352941211.447
290021O50 E
Adder
16.3552941176470613.902
937002AD2-134 E
Adder
8.5752941176470587.289
274815UNIV PK N;XU
50/50
1.9131.913
958012AF2-095 E
Adder
6.4305882352941185.466
934111AD2-000 2
Adder
5.0882352941176484.325
966442AG1-513 E
Adder
0.65058823529411770.553
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
290051GSG-6; E
Adder
8.8682352941176487.538
959082AF2-199 E
Adder
3.01294117647058852.561
958912AF2-182 E
Adder
28.79647058823529424.477
294401BSHIL;1U E
Adder
7.2082352941176476.127
274813UNIV PK N;9U
50/50
1.9091.909
274811UNIV PK N;7U
50/50
1.9251.925
941551AE2-152 C
Adder
9.8717647058823528.391
274676JOLIET 29;8U
Adder
62.29647058823529452.952
958481AF2-142 C
Adder
10.2776470588235318.736
957332AF2-027 E
Adder
3.1823529411764712.705
274891CAYUG;2U E
Adder
11.4552941176470599.737
926822AC1-168 E
Adder
6.4588235294117655.49
274810UNIV PK N;6U
50/50
1.9171.917
274812UNIV PK N;8U
50/50
1.9091.909
941552AE2-152 E
Adder
6.5811764705882365.594
958482AF2-142 E
Adder
6.8517647058823535.824
938852AE1-113 E
Adder
23.91882352941176420.331
274890CAYUG;1U E
Adder
11.4552941176470599.737
962012AG1-044 E
Adder
0.0529411764705882350.045
925582AC1-033 E
Adder
7.9023529411764716.717
966092AG1-478 E
Adder
0.44470588235294120.378
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
938851AE1-113 C
Adder
6.7458823529411775.734
272363ESS H440 ; R
Adder
2.22941176470588241.895
959091AF2-200 C
Adder
12.05294117647058810.245
940502AE2-035 E
Adder
2.8647058823529412.435
276675AE2-062 E
Adder
0.135294117647058840.115
276626AG1-044 E
Adder
0.062352941176470590.053
276170Z1-108 E
Adder
2.48588235294117642.113
920272AA2-123 E
Adder
2.4364705882352942.071
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
NYPJM->LTFIMP_NY
CLTF
0.9330.933
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.41 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1226.15
MW Contribution:13.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960591AF2-350 C
Adder
6.637647058823535.642
960592AF2-350 E
Adder
4.4247058823529413.761
275149KELLYCK ;1E
Adder
15.48823529411764713.165
934722AD1-100 E
Adder
76.1647058823529364.74
960751AF2-366 C
Adder
5.8811764705882354.999
942422AE2-255 E
Adder
7.61411764705882456.472
960582AF2-349 E
Adder
30.4847058823529425.912
937312AD2-172 E
Adder
2.84588235294117682.419
274859EASYR;U1 E
Adder
10.0658823529411758.556
961501AF2-441 C
Adder
7.1070588235294126.041
293519PILOT HIL;1E
Adder
15.48823529411764713.165
939351AE1-166 C
Adder
8.4870588235294137.214
274675JOLIET 29;7U
Adder
61.79058823529411652.522
274674JOLIET 9 ;6U
Adder
31.0329411764705926.378
293061N-015 E
Adder
13.10117647058823411.136
943121AE2-341 C
Adder
10.7729411764705899.157
939321AE1-163 C
Adder
5.302352941176474.507
295111SUBLETTE E
Adder
2.29294117647058831.949
274860EASYR;U2 E
Adder
10.0658823529411758.556
927209AC1-214 E2
Adder
2.7317647058823532.322
946322AF1-296 E
Adder
5.1729411764705894.397
957331AF2-027 C
Adder
2.1047058823529411.789
936511AD2-066 C
Adder
7.1305882352941186.061
936512AD2-066 E
Adder
4.7541176470588244.041
295109WESTBROOK E
Adder
4.7152941176470594.008
939061AE1-134 2
Adder
1.14705882352941170.975
961502AF2-441 E
Adder
10.6611764705882349.062
943122AE2-341 E
Adder
5.2905882352941184.497
939322AE1-163 E
Adder
32.5729411764705927.687
927208AC1-214 E1
Adder
2.7317647058823532.322
293516O-009 E
Adder
15.7576470588235313.394
293717O-029 E
Adder
4.1070588235294123.491
936372AD2-047 E
Adder
18.36705882352941215.612
276591L-013 2
Adder
3.09411764705882362.63
962781AG1-127 C
Adder
5.8976470588235295.013
933911AD1-013 C
Adder
1.55058823529411781.318
910542X3-005 E
Adder
0.53058823529411770.451
939352AE1-166 E
Adder
7.8341176470588236.659
294392P-010 E
Adder
16.63882352941176614.143
959352AF2-226 E
Adder
3.01647058823529422.564
934101AD2-000 1
Adder
4.8788235294117654.147
958492AF2-143 E
Adder
6.4929411764705885.519
942421AE2-255 C
Adder
2.53764705882352942.157
290108LEEDK;1U E
Adder
20.2152941176470617.183
916221Z1-073 E
Adder
6.2070588235294125.276
957472AF2-041 E
Adder
8.9788235294117647.632
959092AF2-200 E
Adder
7.98117647058823556.784
926821AC1-168 C
Adder
0.95764705882352940.814
938862AE1-114 E
Adder
11.244705882352949.558
274814UNIV PK N;0U
50/50
1.8911.891
274807UNIV PK N;3U
50/50
1.9151.915
274816UNIV PK N;YU
50/50
1.9151.915
958011AF2-095 C
Adder
9.557647058823538.124
933411AC2-154 C
Adder
2.10235294117647081.787
274687WILL CNTY;4U
Adder
55.58000000000000547.243
966091AG1-478 C
Adder
1.7552941176470591.492
966441AG1-513 C
Adder
0.430588235294117660.366
959081AF2-199 C
Adder
5.9858823529411775.088
916212CRESCENT ;1U
Adder
4.0470588235294123.44
294410BSHIL;2U E
Adder
7.17647058823529356.1
274808UNIV PK N;4U
50/50
1.9071.907
959351AF2-226 C
Adder
2.0105882352941181.709
958491AF2-143 C
Adder
9.748.279
933912AD1-013 E
Adder
2.47764705882352932.106
946152AF1-280 E
Adder
19.08352941176470816.221
293771O-035 E
Adder
5.7611764705882364.897
293716O-029 E
Adder
4.46823529411764753.798
936371AD2-047 C
Adder
3.76235294117647053.198
936461AD2-060 C
Adder
2.2129411764705881.881
933412AC2-154 E
Adder
3.42941176470588262.915
962782AG1-127 E
Adder
3.92470588235294133.336
946671AF1-331 C
Adder
2.01411764705882361.712
293644O22 E1
Adder
11.5517647058823549.819
960281AF2-319 C
Adder
2.0105882352941181.709
960752AF2-366 E
Adder
3.92117647058823553.333
957471AF2-041 C
Adder
17.9576470588235315.264
294763P-046 E
Adder
7.9094117647058826.723
938861AE1-114 C
Adder
3.2964705882352942.802
293645O22 E2
Adder
13.2305882352941211.246
960282AF2-319 E
Adder
3.01647058823529422.564
918052AA1-018 E OP
Adder
14.7952941176470612.576
293715O-029 E
Adder
8.1494117647058816.927
274805UNIV PK N;1U
50/50
1.9031.903
943592AF1-030 E
Adder
3.54470588235294143.013
943591AF1-030 C
Adder
7.1635294117647066.089
936292AD2-038 E
Adder
13.37529411764705911.369
290021O50 E
Adder
16.24352941176470813.807
937002AD2-134 E
Adder
8.5164705882352937.239
274815UNIV PK N;XU
50/50
1.9031.903
958012AF2-095 E
Adder
6.3717647058823535.416
934111AD2-000 2
Adder
5.0470588235294124.29
966442AG1-513 E
Adder
0.64470588235294120.548
274683WAUKEGAN ;8U
Adder
37.5458823529411831.914
290051GSG-6; E
Adder
8.8082352941176477.487
959082AF2-199 E
Adder
2.99294117647058842.544
958912AF2-182 E
Adder
28.6258823529411824.332
294401BSHIL;1U E
Adder
7.17647058823529356.1
274813UNIV PK N;9U
50/50
1.8991.899
274811UNIV PK N;7U
50/50
1.9151.915
941551AE2-152 C
Adder
9.7929411764705888.324
274676JOLIET 29;8U
Adder
61.7682352941176552.503
958481AF2-142 C
Adder
10.2035294117647068.673
957332AF2-027 E
Adder
3.15764705882352952.684
274891CAYUG;2U E
Adder
11.395294117647069.686
926822AC1-168 E
Adder
6.4258823529411765.462
274810UNIV PK N;6U
50/50
1.9071.907
274812UNIV PK N;8U
50/50
1.8991.899
941552AE2-152 E
Adder
6.5282352941176485.549
958482AF2-142 E
Adder
6.8023529411764715.782
938852AE1-113 E
Adder
23.75647058823529520.193
274890CAYUG;1U E
Adder
11.395294117647069.686
962012AG1-044 E
Adder
0.0529411764705882350.045
925582AC1-033 E
Adder
7.8670588235294126.687
966092AG1-478 E
Adder
0.44117647058823530.375
274682WAUKEGAN ;7U
Adder
34.8235294117647129.6
942651AE2-281 C
Adder
0.75764705882352950.644
942652AE2-281 E
Adder
4.6529411764705893.955
962691AG1-118 C
Adder
18.6752941176470615.874
962692AG1-118 E
Adder
12.45058823529411810.583
938851AE1-113 C
Adder
6.75.695
272363ESS H440 ; R
Adder
2.21411764705882331.882
959091AF2-200 C
Adder
11.97176470588235410.176
940502AE2-035 E
Adder
2.84588235294117682.419
276675AE2-062 E
Adder
0.134117647058823540.114
276626AG1-044 E
Adder
0.061176470588235290.052
276170Z1-108 E
Adder
2.4670588235294122.097
920272AA2-123 E
Adder
2.4188235294117652.056
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.23368.233
NYPJM->LTFIMP_NY
CLTF
0.9310.931
TVALTFEXP_TVA->PJM
CLTF
1.1671.167
LAGNLTFEXP_LAGN->PJM
CLTF
2.992.99
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7291.729
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.210.21
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.1721.172
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6070.607
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.47412.474
WECLTFEXP_WEC->PJM
CLTF
3.2883.288
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.4090.409
SIGELTFEXP_SIGE->PJM
CLTF
0.0150.015
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4090.409
MECLTFEXP_MEC->PJM
CLTF
10.92410.924
O66PJM->LTFIMP_O-066
CMTX_NF
11.09411.094
CONTINGENCY '765-L11215__-S_SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
END
CONTINGENCY 'AEP_P1-2_#695_1681_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'COMED_P4-6_116-345-R______SRT-A'
 DISCONNECT BUS 270767                                          /*GOODINGS ;1R 345.0
 DISCONNECT BUS 270769                                          /*GOODINGS ;2R 345.0
 DISCONNECT BUS 275240                                          /*GOODINGS ;1M 138.0
 TRIP BRANCH FROM BUS 270729 TO BUS 271385 TO BUS 275351 CKT 1  /*E FRANKFO; R 345.0 - E FRANKFO; R 138.0 - E FRANKFO;3C  34.5
END
CONTINGENCY 'COMED_P4_116-45-L11614__SRT-A'
 DISCONNECT BUS 270769                             /*GOODINGS ;2R 345.0
 TRIP BRANCH FROM BUS 270667 TO BUS 270665 CKT 1   /*BLUE ISL ;RT 345.0 - BLUE ISL ; R 345.0
 TRIP BRANCH FROM BUS 270667 TO BUS 270927 CKT 1   /*BLUE ISL ;RT 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 270769 TO BUS 270667 CKT 1   /*GOODINGS ;2R 345.0 - BLUE ISL ;RT 345.0
END
CONTINGENCY 'COMED_P4_112-45-BT4-5___SRT-A'
 TRIP BRANCH FROM BUS 270666 TO BUS 270664 CKT 1   /*BLUE ISL ;BT 345.0 - BLUE ISL ; B 345.0
 TRIP BRANCH FROM BUS 270666 TO BUS 270926 CKT 1   /*BLUE ISL ;BT 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 270770 TO BUS 270666 CKT 1   /*GOODINGS ;4B 345.0 - BLUE ISL ;BT 345.0
 TRIP BRANCH FROM BUS 270852 TO BUS 270704 CKT 1   /*PONTIAC  ; B 345.0 - LORETTO  ; B 345.0
END
CONTINGENCY 'COMED_P4_112-65-BT4-5___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT3-4___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243207 CKT 1   /*05DUMONT     765.0 - 05GRNTWN     765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
255113 to 243219 ckt 1
274750 to 255112 ckt 1
270770 to 270766 ckt 1
274804 to 960680 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1CE
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
Base Case
OPAC126.28 %1334.0A1684.5932.67
GD1CE
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
COMED_P1-2_345-L0626__B-R_SRT-A
OPAC116.23 %1479.0B1719.0419.84
GD1CE
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
Base Case
OPAC103.49 %1201.0A1242.8714.29
GD1CE
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
Base Case
OPAC106.45 %1201.0A1278.4210.95
GD1CE
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
COMED_P1-2_345-L11120_R-N_SRT-A
OPAC100.63 %1479.0B1488.311.47
GD1CE
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P1-2_345-L0626__B-R_SRT-A
OPAC126.4 %1479.0B1869.4219.84
GD1CE
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
Base Case
OPAC115.04 %1201.0A1381.5914.29
GD1CE
LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line
COMED_P1-2_345-L15502_B-R_SRT-A-2
OPAC115.83 %1726.0B1999.2647.28
GD1CE
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line
COMED_P1-2_345-L0627__B-R_SRT-A
OPAC108.05 %1656.0B1789.3543.85
GD1CE
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line
Base Case
OPAC103.46 %1334.0A1380.132.67
GD1CE/MEC
QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line
EXT_636600 SUB 39 3 345 636605 MEC CORDOVA3 345 1 _SRT-S
OPAC103.43 %1471.0B1521.5312.35

Details for AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.28 %
Rating:1334.0 MVA
Rating Type:A
MVA to Mitigate:1684.59
MW Contribution:32.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT; B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.78 %
Rating:1334.0 MVA
Rating Type:A
MVA to Mitigate:1691.31
MW Contribution:32.73
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.57764705882352941.341
962012AG1-044 E
50/50
0.1120.112
290051GSG-6; E
Adder
6.48117647058823555.509
295109WESTBROOK E
Adder
3.4694117647058822.949
295111SUBLETTE E
Adder
1.68705882352941171.434
933911AD1-013 C
Adder
1.09294117647058830.929
933912AD1-013 E
Adder
1.74588235294117641.484
937002AD2-134 E
Adder
6.2658823529411765.326
937312AD2-172 E
Adder
3.09058823529411742.627
958912AF2-182 E
50/50
60.32260.322
959081AF2-199 C
50/50
32.44632.446
959082AF2-199 E
50/50
16.22316.223
274715NELSON EC;1C
50/50
6.6346.634
274717NELSON EC;2C
50/50
6.6856.685
274857BIG SKY ;U1
50/50
0.4550.455
274858BIG SKY ;U2
50/50
0.4550.455
274859EASYR;U1 E
50/50
19.219.2
274860EASYR;U2 E
50/50
19.219.2
276156O-029 C
50/50
0.3210.321
276157O-029 C
50/50
0.5780.578
276158O-029 C
50/50
0.5780.578
293715O-029 E
50/50
15.50715.507
293716O-029 E
50/50
8.5028.502
293717O-029 E
50/50
7.8157.815
293771O-035 E
Adder
4.3282352941176473.679
294401BSHIL;1U E
Adder
6.6588235294117655.66
294410BSHIL;2U E
Adder
6.6588235294117655.66
294763P-046 E
Adder
8.5905882352941177.302
925582AC1-033 E
Adder
7.3023529411764716.207
939051AE1-134 1
50/50
0.4730.473
939061AE1-134 2
50/50
2.9432.943
940502AE2-035 E
Adder
3.09058823529411742.627
957471AF2-041 C
50/50
97.33797.337
957472AF2-041 E
50/50
48.66948.669
274760LEE CO EC;1U
50/50
2.5422.542
274881WALNUT RG;1U
50/50
1.2251.225
276676AA2-030 GEN
50/50
6.1886.188
276677AA1-146
50/50
7.4897.489
293516O-009 E
50/50
29.98629.986
916212CRESCENT ;1U
Adder
3.0411764705882352.585
927208AC1-214 E1
Adder
2.0517647058823531.744
927209AC1-214 E2
Adder
2.0517647058823531.744
990901L-005 E
Adder
8.8729411764705887.542
916221Z1-073 E
Adder
4.5670588235294123.882
274761LEE CO EC;2U
50/50
2.5422.542
274762LEE CO EC;3U
50/50
2.5422.542
274763LEE CO EC;4U
50/50
2.5182.518
274764LEE CO EC;5U
50/50
2.5482.548
274765LEE CO EC;6U
50/50
2.5482.548
274766LEE CO EC;7U
50/50
2.5122.512
274767LEE CO EC;8U
50/50
2.5122.512
959091AF2-200 C
50/50
64.89164.891
959092AF2-200 E
50/50
43.26143.261
966822AG1-553 E
50/50
45.45745.457
938861AE1-114 C
Adder
4.69058823529411753.987
938862AE1-114 E
Adder
16.0047058823529413.604
946152AF1-280 E
50/50
40.21540.215
946321AF1-296 C
Adder
5.7494117647058824.887
946322AF1-296 E
Adder
26.91882352941176422.881
946671AF1-331 C
Adder
1.42000000000000021.207
965931AG1-462 C
50/50
26.7526.75
965932AG1-462 E
50/50
17.83317.833
274716NELSON EC;1S
50/50
4.844.84
274718NELSON EC;2S
50/50
4.8834.883
276626AG1-044 E
50/50
0.1120.112
991092J1477
External Queue
5.500812053680425.50081205368042
955972J1084
External Queue
20.9585704803466820.95857048034668
956412J1131
External Queue
10.9796648025512710.97966480255127
990947J1432 C
External Queue
4.7147688865661624.714768886566162
990948J1432 E
External Queue
25.50810813903808625.508108139038086
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0610.061
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.33663.336
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.35211.352
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.0093.009
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3650.365
NYPJM->LTFIMP_NY
CLTF
0.2040.204
WECLTFEXP_WEC->PJM
CLTF
0.6580.658
CPLELTFEXP_CPLE->PJM
CLTF
0.1330.133
TVALTFEXP_TVA->PJM
CLTF
1.6851.685
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0730.073
MECLTFEXP_MEC->PJM
CLTF
13.47113.471
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.1690.169
LAGNLTFEXP_LAGN->PJM
CLTF
3.5753.575
SIGELTFEXP_SIGE->PJM
CLTF
0.0310.031
O66PJM->LTFIMP_O-066
CMTX_NF
2.3472.347

Details for CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0626__B-R_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0626__B-R_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:116.23 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1719.04
MW Contribution:19.84
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0626__B-R_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:116.75 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1726.77
MW Contribution:19.86
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.04588235294117651.739
962012AG1-044 E
Adder
0.065882352941176480.056
962781AG1-127 C
Adder
4.9211764705882354.183
962782AG1-127 E
Adder
3.27529411764705852.784
290051GSG-6; E
Adder
8.2270588235294136.993
295109WESTBROOK E
Adder
4.4047058823529423.744
295111SUBLETTE E
Adder
2.14117647058823521.82
933911AD1-013 C
Adder
1.4282352941176471.214
933912AD1-013 E
Adder
2.28117647058823541.939
937002AD2-134 E
Adder
7.95411764705882356.761
937312AD2-172 E
50/50
6.056.05
958912AF2-182 E
Adder
48.3858823529411841.128
959081AF2-199 C
Adder
3.52941176470588223
959082AF2-199 E
Adder
1.76470588235294111.5
960751AF2-366 C
Adder
4.9070588235294124.171
960752AF2-366 E
Adder
3.2717647058823532.781
274656BYRON ;1U
50/50
48.4248.42
274657BYRON ;2U
50/50
47.35647.356
274822ROCKFORD ;11
50/50
7.0787.078
274823ROCKFORD ;21
50/50
7.1147.114
274824ROCKFORD ;12
50/50
7.0267.026
274856ECOGROVE ;U1
50/50
0.6610.661
274859EASYR;U1 E
Adder
18.5305882352941215.751
274860EASYR;U2 E
Adder
18.5305882352941215.751
276590R-018
50/50
0.2570.257
293715O-029 E
Adder
9.222352941176477.839
293716O-029 E
Adder
5.0564705882352944.298
293717O-029 E
Adder
4.6470588235294123.95
294763P-046 E
50/50
16.81516.815
939061AE1-134 2
Adder
1.54235294117647051.311
940502AE2-035 E
50/50
6.056.05
957471AF2-041 C
Adder
10.5894117647058839.001
957472AF2-041 E
Adder
5.2941176470588234.5
274760LEE CO EC;1U
50/50
2.4532.453
276611AD2-172 C
50/50
0.7160.716
276612AE2-035 C
50/50
0.7160.716
293516O-009 E
Adder
17.83294117647058715.158
290108LEEDK;1U E
Adder
15.72235294117647313.364
916221Z1-073 E
Adder
5.797647058823534.928
274761LEE CO EC;2U
50/50
2.4532.453
274762LEE CO EC;3U
50/50
2.4532.453
274763LEE CO EC;4U
50/50
2.432.43
274764LEE CO EC;5U
50/50
2.4592.459
274765LEE CO EC;6U
50/50
2.4592.459
274766LEE CO EC;7U
50/50
2.4242.424
959091AF2-200 C
Adder
7.05882352941176456
959092AF2-200 E
Adder
4.7058823529411774
966822AG1-553 E
Adder
26.1352941176470622.215
938861AE1-114 C
50/50
6.0246.024
938862AE1-114 E
50/50
20.55220.552
946152AF1-280 E
Adder
32.2576470588235327.419
946321AF1-296 C
Adder
3.4917647058823532.968
946322AF1-296 E
Adder
16.34705882352941213.895
946671AF1-331 C
Adder
1.85411764705882361.576
962691AG1-118 C
Adder
12.33058823529411710.481
962692AG1-118 E
Adder
8.226.987
965931AG1-462 C
Adder
15.37882352941176513.072
965932AG1-462 E
Adder
10.252941176470598.715
920272AA2-123 E
Adder
1.20235294117647061.022
276626AG1-044 E
Adder
0.077647058823529420.066
990512J1326 G
External Queue
9.6151580810546889.615158081054688
991092J1477
External Queue
2.92044234275817872.9204423427581787
955972J1084
External Queue
11.01287746429443411.012877464294434
956412J1131
External Queue
5.8292260169982915.829226016998291
990117J1214 G
External Queue
38.40942001342773438.409420013427734
990407J1304 G
External Queue
9.3612556457519539.361255645751953
990727J1377 G
External Queue
16.432250976562516.4322509765625
990947J1432 C
External Queue
2.801840066909792.80184006690979
990948J1432 E
External Queue
15.15867328643798815.158673286437988
991777J1629 G
External Queue
10.9501476287841810.95014762878418
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0850.085
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.88759.887
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7576.757
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
0.4940.494
NYPJM->LTFIMP_NY
CLTF
0.2690.269
WECLTFEXP_WEC->PJM
CLTF
0.5290.529
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0390.039
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0070.007
TVALTFEXP_TVA->PJM
CLTF
0.9250.925
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1820.182
MECLTFEXP_MEC->PJM
CLTF
9.849.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.5250.525
LAGNLTFEXP_LAGN->PJM
CLTF
2.2922.292
O66PJM->LTFIMP_O-066
CMTX_NF
3.1743.174

Details for CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.49 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1242.87
MW Contribution:14.29
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.66 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1244.97
MW Contribution:14.3
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.60705882352941191.366
962012AG1-044 E
Adder
0.0482352941176470640.041
962781AG1-127 C
Adder
4.01882352941176453.416
962782AG1-127 E
Adder
2.6752941176470592.274
290051GSG-6; E
Adder
6.4529411764705885.485
295109WESTBROOK E
Adder
3.45411764705882352.936
295111SUBLETTE E
Adder
1.681.428
933911AD1-013 C
Adder
1.12235294117647060.954
933912AD1-013 E
Adder
1.79294117647058831.524
937002AD2-134 E
Adder
6.2388235294117655.303
937312AD2-172 E
50/50
4.6984.698
958912AF2-182 E
Adder
34.10470588235294528.989
960751AF2-366 C
Adder
4.0082352941176483.407
960752AF2-366 E
Adder
2.6717647058823532.271
274656BYRON ;1U
50/50
33.633.6
274657BYRON ;2U
50/50
32.93832.938
274822ROCKFORD ;11
50/50
5.6285.628
274823ROCKFORD ;21
50/50
5.6575.657
274824ROCKFORD ;12
50/50
5.5875.587
274856ECOGROVE ;U1
50/50
0.5140.514
274859EASYR;U1 E
Adder
13.01294117647058911.061
274860EASYR;U2 E
Adder
13.01294117647058911.061
276590R-018
50/50
0.2050.205
293715O-029 E
Adder
6.6905882352941185.687
293716O-029 E
Adder
3.6682352941176473.118
293717O-029 E
Adder
3.3717647058823532.866
294763P-046 E
50/50
13.05813.058
939061AE1-134 2
Adder
1.10.935
940502AE2-035 E
50/50
4.6984.698
274760LEE CO EC;1U
50/50
1.7231.723
276611AD2-172 C
50/50
0.5560.556
276612AE2-035 C
50/50
0.5560.556
293516O-009 E
Adder
12.93647058823529510.996
290108LEEDK;1U E
Adder
12.69882352941176510.794
916221Z1-073 E
Adder
4.54705882352941253.865
274761LEE CO EC;2U
50/50
1.7231.723
274762LEE CO EC;3U
50/50
1.7231.723
274763LEE CO EC;4U
50/50
1.7061.706
274764LEE CO EC;5U
50/50
1.7271.727
274765LEE CO EC;6U
50/50
1.7271.727
274766LEE CO EC;7U
50/50
1.7021.702
966822AG1-553 E
Adder
18.715.895
938861AE1-114 C
50/50
4.6134.613
938862AE1-114 E
50/50
15.7415.74
946152AF1-280 E
Adder
22.73647058823529619.326
946321AF1-296 C
Adder
2.51529411764705872.138
946322AF1-296 E
Adder
11.77529411764705910.009
946671AF1-331 C
Adder
1.45764705882352951.239
962691AG1-118 C
Adder
10.1658823529411778.641
962692AG1-118 E
Adder
6.777647058823535.761
965931AG1-462 C
Adder
11.004705882352949.354
965932AG1-462 E
Adder
7.3364705882352946.236
276626AG1-044 E
Adder
0.056470588235294120.048
990512J1326 G
External Queue
7.2312178611755377.231217861175537
955972J1084
External Queue
7.95014476776123057.9501447677612305
990117J1214 G
External Queue
28.88635635375976628.886356353759766
990407J1304 G
External Queue
7.0667271614074717.066727161407471
990727J1377 G
External Queue
12.48061370849609412.480613708496094
990947J1432 C
External Queue
2.031287193298342.03128719329834
990948J1432 E
External Queue
10.98978519439697310.989785194396973
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0570.057
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.77141.771
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.8764.876
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.0480.048
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3480.348
NYPJM->LTFIMP_NY
CLTF
0.1890.189
WECLTFEXP_WEC->PJM
CLTF
0.1810.181
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0240.024
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0030.003
TVALTFEXP_TVA->PJM
CLTF
0.670.67
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1270.127
MECLTFEXP_MEC->PJM
CLTF
7.0467.046
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.3660.366
LAGNLTFEXP_LAGN->PJM
CLTF
1.6491.649
O66PJM->LTFIMP_O-066
CMTX_NF
2.2342.234

Details for ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.45 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1278.42
MW Contribution:10.95
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.39 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1277.74
MW Contribution:10.92
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.99411764705882361.695
962012AG1-044 E
Adder
0.040.034
962781AG1-127 C
Adder
5.5082352941176484.682
962782AG1-127 E
Adder
3.66588235294117663.116
966441AG1-513 C
Adder
0.271764705882352960.231
966442AG1-513 E
Adder
0.408235294117647030.347
290051GSG-6; E
Adder
7.9070588235294126.721
295109WESTBROOK E
Adder
4.2341176470588243.599
295111SUBLETTE E
Adder
2.05764705882352941.749
933911AD1-013 C
Adder
1.39764705882352951.188
933912AD1-013 E
Adder
2.2329411764705881.898
937002AD2-134 E
Adder
7.6458823529411766.499
937312AD2-172 E
Adder
1.61176470588235321.37
958912AF2-182 E
Adder
22.0423529411764718.736
959081AF2-199 C
50/50
8.7928.792
959082AF2-199 E
50/50
4.3964.396
960751AF2-366 C
Adder
5.49294117647058754.669
960752AF2-366 E
Adder
3.6623529411764713.113
274738AURORA EC;3P
50/50
4.3424.342
274740AURORA EC;4P
50/50
4.3424.342
274859EASYR;U1 E
Adder
7.4211764705882356.308
274860EASYR;U2 E
Adder
7.4211764705882356.308
276591L-013 2
Adder
2.78823529411764742.37
293715O-029 E
Adder
5.5423529411764714.711
293716O-029 E
Adder
3.0388235294117652.583
293717O-029 E
Adder
2.79294117647058832.374
294763P-046 E
Adder
4.4788235294117643.807
939061AE1-134 2
Adder
0.96941176470588230.824
940502AE2-035 E
Adder
1.61176470588235321.37
957471AF2-041 C
50/50
26.37726.377
957472AF2-041 E
50/50
13.18813.188
293516O-009 E
Adder
10.7176470588235299.11
290108LEEDK;1U E
Adder
19.04117647058823316.185
916221Z1-073 E
Adder
5.57176470588235254.736
943121AE2-341 C
Adder
9.7588235294117668.295
943122AE2-341 E
Adder
4.7917647058823534.073
943591AF1-030 C
Adder
6.4905882352941185.517
943592AF1-030 E
Adder
3.2105882352941182.729
959091AF2-200 C
50/50
17.58417.584
959092AF2-200 E
50/50
11.72311.723
966822AG1-553 E
Adder
14.77058823529411812.555
938861AE1-114 C
Adder
2.141.819
938862AE1-114 E
Adder
7.3000000000000016.205
946152AF1-280 E
Adder
14.69529411764705912.491
946321AF1-296 C
Adder
1.92705882352941171.638
946322AF1-296 E
Adder
9.0211764705882367.668
946671AF1-331 C
Adder
1.81529411764705871.543
962691AG1-118 C
50/50
18.6518.65
962692AG1-118 E
50/50
12.43312.433
965931AG1-462 C
Adder
8.6917647058823537.388
965932AG1-462 E
Adder
5.7941176470588234.925
276626AG1-044 E
Adder
0.0470588235294117640.04
955972J1084
External Queue
7.6018819808959967.601881980895996
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0950.095
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.4658.465
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.5222.522
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
0.30.3
NYPJM->LTFIMP_NY
CLTF
0.1620.162
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0620.062
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.030.03
TVALTFEXP_TVA->PJM
CLTF
0.2960.296
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1180.118
MECLTFEXP_MEC->PJM
CLTF
3.9293.929
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.3510.351
LAGNLTFEXP_LAGN->PJM
CLTF
0.8220.822
O66PJM->LTFIMP_O-066
CMTX_NF
1.9231.923

Details for ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11120_R-N_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L11120_R-N_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.63 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1488.3
MW Contribution:11.47
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L11120_R-N_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.56 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1487.28
MW Contribution:11.45
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.16470588235294151.84
962012AG1-044 E
Adder
0.04117647058823530.035
962781AG1-127 C
50/50
6.0196.019
962782AG1-127 E
50/50
4.0054.005
966441AG1-513 C
Adder
0.39411764705882360.335
966442AG1-513 E
Adder
0.5917647058823530.503
290051GSG-6; E
Adder
8.5811764705882347.294
295109WESTBROOK E
Adder
4.5941176470588233.905
295111SUBLETTE E
Adder
2.2329411764705881.898
933911AD1-013 C
Adder
1.51764705882352961.29
933912AD1-013 E
Adder
2.42470588235294132.061
937002AD2-134 E
Adder
8.2976470588235297.053
937312AD2-172 E
Adder
1.73529411764705891.475
958912AF2-182 E
Adder
23.3741176470588219.868
959081AF2-199 C
50/50
9.0859.085
959082AF2-199 E
50/50
4.5434.543
960751AF2-366 C
50/50
6.0026.002
960752AF2-366 E
50/50
4.0014.001
274738AURORA EC;3P
50/50
4.6254.625
274740AURORA EC;4P
50/50
4.6254.625
274859EASYR;U1 E
Adder
7.9058823529411776.72
274860EASYR;U2 E
Adder
7.9058823529411776.72
276591L-013 2
50/50
3.3053.305
293715O-029 E
Adder
5.8482352941176474.971
293716O-029 E
Adder
3.20588235294117662.725
293717O-029 E
Adder
2.94705882352941152.505
294763P-046 E
Adder
4.8235294117647064.1
939061AE1-134 2
Adder
1.01882352941176470.866
940502AE2-035 E
Adder
1.73529411764705891.475
957471AF2-041 C
50/50
27.25527.255
957472AF2-041 E
50/50
13.62813.628
293516O-009 E
Adder
11.3070588235294139.611
274872LEE DEKAL;1U
50/50
0.6880.688
290108LEEDK;1U E
50/50
20.78420.784
916221Z1-073 E
Adder
6.0470588235294125.14
943121AE2-341 C
50/50
11.04711.047
943122AE2-341 E
50/50
5.4255.425
943591AF1-030 C
50/50
7.3477.347
943592AF1-030 E
50/50
3.6353.635
959091AF2-200 C
50/50
18.1718.17
959092AF2-200 E
50/50
12.11412.114
966822AG1-553 E
Adder
15.45764705882352913.139
938861AE1-114 C
Adder
2.2870588235294121.944
938862AE1-114 E
Adder
7.8035294117647066.633
946152AF1-280 E
Adder
15.58352941176470613.246
946321AF1-296 C
Adder
2.021.717
946322AF1-296 E
Adder
9.455294117647068.037
946671AF1-331 C
Adder
1.97058823529411781.675
962691AG1-118 C
50/50
20.33320.333
962692AG1-118 E
50/50
13.55613.556
965931AG1-462 C
Adder
9.0964705882352957.732
965932AG1-462 E
Adder
6.0635294117647065.154
276626AG1-044 E
Adder
0.0494117647058823560.042
955972J1084
External Queue
8.1039762496948248.103976249694824
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.1140.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.2666.266
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.5682.568
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3370.337
NYPJM->LTFIMP_NY
CLTF
0.1820.182
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0760.076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0380.038
TVALTFEXP_TVA->PJM
CLTF
0.2870.287
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1330.133
MECLTFEXP_MEC->PJM
CLTF
4.0164.016
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.3940.394
LAGNLTFEXP_LAGN->PJM
CLTF
0.8250.825
O66PJM->LTFIMP_O-066
CMTX_NF
2.162.16

Details for GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0626__B-R_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0626__B-R_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.4 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1869.42
MW Contribution:19.84
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0626__B-R_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1877.2
MW Contribution:19.86
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.04588235294117651.739
962012AG1-044 E
Adder
0.065882352941176480.056
962781AG1-127 C
Adder
4.9211764705882354.183
962782AG1-127 E
Adder
3.27529411764705852.784
290051GSG-6; E
Adder
8.2270588235294136.993
295109WESTBROOK E
Adder
4.4047058823529423.744
295111SUBLETTE E
Adder
2.14117647058823521.82
933911AD1-013 C
Adder
1.4282352941176471.214
933912AD1-013 E
Adder
2.28117647058823541.939
937002AD2-134 E
Adder
7.95411764705882356.761
937312AD2-172 E
50/50
6.056.05
958912AF2-182 E
Adder
48.3858823529411841.128
959081AF2-199 C
Adder
3.52941176470588223
959082AF2-199 E
Adder
1.76470588235294111.5
960582AF2-349 E
50/50
148.497148.497
960751AF2-366 C
Adder
4.9070588235294124.171
960752AF2-366 E
Adder
3.2717647058823532.781
274656BYRON ;1U
50/50
48.4248.42
274657BYRON ;2U
50/50
47.35647.356
274822ROCKFORD ;11
50/50
7.0787.078
274823ROCKFORD ;21
50/50
7.1147.114
274824ROCKFORD ;12
50/50
7.0267.026
274856ECOGROVE ;U1
50/50
0.6610.661
274859EASYR;U1 E
Adder
18.5305882352941215.751
274860EASYR;U2 E
Adder
18.5305882352941215.751
276590R-018
50/50
0.2570.257
293715O-029 E
Adder
9.222352941176477.839
293716O-029 E
Adder
5.0564705882352944.298
293717O-029 E
Adder
4.6470588235294123.95
294763P-046 E
50/50
16.81516.815
939061AE1-134 2
Adder
1.54235294117647051.311
940502AE2-035 E
50/50
6.056.05
957471AF2-041 C
Adder
10.5894117647058839.001
957472AF2-041 E
Adder
5.2941176470588234.5
274760LEE CO EC;1U
50/50
2.4532.453
276611AD2-172 C
50/50
0.7160.716
276612AE2-035 C
50/50
0.7160.716
293516O-009 E
Adder
17.83294117647058715.158
290108LEEDK;1U E
Adder
15.72235294117647313.364
916221Z1-073 E
Adder
5.797647058823534.928
274761LEE CO EC;2U
50/50
2.4532.453
274762LEE CO EC;3U
50/50
2.4532.453
274763LEE CO EC;4U
50/50
2.432.43
274764LEE CO EC;5U
50/50
2.4592.459
274765LEE CO EC;6U
50/50
2.4592.459
274767LEE CO EC;8U
50/50
2.4242.424
959091AF2-200 C
Adder
7.05882352941176456
959092AF2-200 E
Adder
4.7058823529411774
966822AG1-553 E
Adder
26.1352941176470622.215
938861AE1-114 C
50/50
6.0246.024
938862AE1-114 E
50/50
20.55220.552
946152AF1-280 E
Adder
32.2576470588235327.419
946321AF1-296 C
Adder
3.4917647058823532.968
946322AF1-296 E
Adder
16.34705882352941213.895
946671AF1-331 C
Adder
1.85411764705882361.576
962691AG1-118 C
Adder
12.33058823529411710.481
962692AG1-118 E
Adder
8.226.987
965931AG1-462 C
Adder
15.37882352941176513.072
965932AG1-462 E
Adder
10.252941176470598.715
920272AA2-123 E
Adder
1.20235294117647061.022
276626AG1-044 E
Adder
0.077647058823529420.066
990512J1326 G
External Queue
9.6151580810546889.615158081054688
991092J1477
External Queue
2.92044234275817872.9204423427581787
955972J1084
External Queue
11.01287746429443411.012877464294434
956412J1131
External Queue
5.8292260169982915.829226016998291
990117J1214 G
External Queue
38.40942001342773438.409420013427734
990407J1304 G
External Queue
9.3612556457519539.361255645751953
990727J1377 G
External Queue
16.432250976562516.4322509765625
990947J1432 C
External Queue
2.801840066909792.80184006690979
990948J1432 E
External Queue
15.15867328643798815.158673286437988
991777J1629 G
External Queue
10.9501476287841810.95014762878418
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0850.085
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.88759.887
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7576.757
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
0.4940.494
NYPJM->LTFIMP_NY
CLTF
0.2690.269
WECLTFEXP_WEC->PJM
CLTF
0.5290.529
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0390.039
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0070.007
TVALTFEXP_TVA->PJM
CLTF
0.9250.925
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1820.182
MECLTFEXP_MEC->PJM
CLTF
9.849.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.5250.525
LAGNLTFEXP_LAGN->PJM
CLTF
2.2922.292
O66PJM->LTFIMP_O-066
CMTX_NF
3.1743.174

Details for GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.04 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1381.59
MW Contribution:14.29
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.21 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1383.73
MW Contribution:14.3
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.60705882352941191.366
962012AG1-044 E
Adder
0.0482352941176470640.041
962781AG1-127 C
Adder
4.01882352941176453.416
962782AG1-127 E
Adder
2.6752941176470592.274
290051GSG-6; E
Adder
6.4529411764705885.485
295109WESTBROOK E
Adder
3.45411764705882352.936
295111SUBLETTE E
Adder
1.681.428
933911AD1-013 C
Adder
1.12235294117647060.954
933912AD1-013 E
Adder
1.79294117647058831.524
937002AD2-134 E
Adder
6.2388235294117655.303
937312AD2-172 E
50/50
4.6984.698
958912AF2-182 E
Adder
34.10470588235294528.989
960582AF2-349 E
50/50
137.351137.351
960751AF2-366 C
Adder
4.0082352941176483.407
960752AF2-366 E
Adder
2.6717647058823532.271
274656BYRON ;1U
50/50
33.633.6
274657BYRON ;2U
50/50
32.93832.938
274822ROCKFORD ;11
50/50
5.6285.628
274823ROCKFORD ;21
50/50
5.6575.657
274824ROCKFORD ;12
50/50
5.5875.587
274856ECOGROVE ;U1
50/50
0.5140.514
274859EASYR;U1 E
Adder
13.01294117647058911.061
274860EASYR;U2 E
Adder
13.01294117647058911.061
276590R-018
50/50
0.2050.205
293715O-029 E
Adder
6.6905882352941185.687
293716O-029 E
Adder
3.6682352941176473.118
293717O-029 E
Adder
3.3717647058823532.866
294763P-046 E
50/50
13.05813.058
939061AE1-134 2
Adder
1.10.935
940502AE2-035 E
50/50
4.6984.698
274760LEE CO EC;1U
50/50
1.7231.723
276611AD2-172 C
50/50
0.5560.556
276612AE2-035 C
50/50
0.5560.556
293516O-009 E
Adder
12.93647058823529510.996
290108LEEDK;1U E
Adder
12.69882352941176510.794
916221Z1-073 E
Adder
4.54705882352941253.865
274761LEE CO EC;2U
50/50
1.7231.723
274762LEE CO EC;3U
50/50
1.7231.723
274763LEE CO EC;4U
50/50
1.7061.706
274764LEE CO EC;5U
50/50
1.7271.727
274765LEE CO EC;6U
50/50
1.7271.727
274766LEE CO EC;7U
50/50
1.7021.702
966822AG1-553 E
Adder
18.715.895
938861AE1-114 C
50/50
4.6134.613
938862AE1-114 E
50/50
15.7415.74
946152AF1-280 E
Adder
22.73647058823529619.326
946321AF1-296 C
Adder
2.51529411764705872.138
946322AF1-296 E
Adder
11.77529411764705910.009
946671AF1-331 C
Adder
1.45764705882352951.239
962691AG1-118 C
Adder
10.1658823529411778.641
962692AG1-118 E
Adder
6.777647058823535.761
965931AG1-462 C
Adder
11.004705882352949.354
965932AG1-462 E
Adder
7.3364705882352946.236
276626AG1-044 E
Adder
0.056470588235294120.048
990512J1326 G
External Queue
7.2312178611755377.231217861175537
955972J1084
External Queue
7.95014476776123057.9501447677612305
990117J1214 G
External Queue
28.88635635375976628.886356353759766
990407J1304 G
External Queue
7.0667271614074717.066727161407471
990727J1377 G
External Queue
12.48061370849609412.480613708496094
990947J1432 C
External Queue
2.031287193298342.03128719329834
990948J1432 E
External Queue
10.98978519439697310.989785194396973
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0570.057
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.77141.771
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.8764.876
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.0480.048
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3480.348
NYPJM->LTFIMP_NY
CLTF
0.1890.189
WECLTFEXP_WEC->PJM
CLTF
0.1810.181
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0240.024
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0030.003
TVALTFEXP_TVA->PJM
CLTF
0.670.67
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1270.127
MECLTFEXP_MEC->PJM
CLTF
7.0467.046
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.3660.366
LAGNLTFEXP_LAGN->PJM
CLTF
1.6491.649
O66PJM->LTFIMP_O-066
CMTX_NF
2.2342.234

Details for LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L15502_B-R_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.83 %
Rating:1726.0 MVA
Rating Type:B
MVA to Mitigate:1999.26
MW Contribution:47.28
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L15502_B-R_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:116.25 %
Rating:1726.0 MVA
Rating Type:B
MVA to Mitigate:2006.52
MW Contribution:47.4
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
962012AG1-044 E
50/50
0.1680.168
958912AF2-182 E
50/50
145.131145.131
959081AF2-199 C
50/50
22.98222.982
959082AF2-199 E
50/50
11.49111.491
274715NELSON EC;1C
50/50
10.53710.537
274717NELSON EC;2C
50/50
10.61810.618
274857BIG SKY ;U1
50/50
1.3131.313
274858BIG SKY ;U2
50/50
1.3131.313
274859EASYR;U1 E
50/50
55.39355.393
274860EASYR;U2 E
50/50
55.39355.393
276156O-029 C
50/50
0.4810.481
276157O-029 C
50/50
0.8680.868
276158O-029 C
50/50
0.8680.868
293715O-029 E
50/50
23.28823.288
293716O-029 E
50/50
12.76912.769
293717O-029 E
50/50
11.73611.736
293771O-035 E
Adder
6.7470588235294135.735
294401BSHIL;1U E
Adder
10.2058823529411788.675
294410BSHIL;2U E
Adder
10.2058823529411788.675
925582AC1-033 E
Adder
11.1917647058823539.513
939051AE1-134 1
50/50
0.7510.751
939061AE1-134 2
50/50
4.6744.674
957471AF2-041 C
50/50
68.94768.947
957472AF2-041 E
50/50
34.47434.474
274760LEE CO EC;1U
50/50
7.3337.333
274881WALNUT RG;1U
50/50
1.8391.839
276676AA2-030 GEN
50/50
9.8299.829
276677AA1-146
50/50
11.89511.895
293516O-009 E
50/50
45.03145.031
916212CRESCENT ;1U
Adder
4.744.029
927208AC1-214 E1
Adder
3.19882352941176462.719
927209AC1-214 E2
Adder
3.19882352941176462.719
990901L-005 E
Adder
13.6529411764705911.605
274761LEE CO EC;2U
50/50
7.3337.333
274762LEE CO EC;3U
50/50
7.3337.333
274763LEE CO EC;4U
50/50
7.2637.263
274764LEE CO EC;5U
50/50
7.357.35
274765LEE CO EC;6U
50/50
7.357.35
274766LEE CO EC;7U
50/50
7.2477.247
274767LEE CO EC;8U
50/50
7.2477.247
959091AF2-200 C
50/50
45.96545.965
959092AF2-200 E
50/50
30.64330.643
966822AG1-553 E
50/50
67.70467.704
946152AF1-280 E
50/50
96.75496.754
946321AF1-296 C
Adder
8.3211764705882367.073
946322AF1-296 E
Adder
38.9564705882352933.113
965931AG1-462 C
50/50
39.84139.841
965932AG1-462 E
50/50
26.56126.561
274716NELSON EC;1S
50/50
7.6887.688
274718NELSON EC;2S
50/50
7.7577.757
276626AG1-044 E
50/50
0.1680.168
990512J1326 G
External Queue
-7.79633092880249-7.79633092880249
991092J1477
External Queue
9.0879898071289069.087989807128906
955972J1084
External Queue
34.5655326843261734.56553268432617
956412J1131
External Queue
18.13969993591308618.139699935913086
990947J1432 C
External Queue
7.2057147026062017.205714702606201
990948J1432 E
External Queue
38.98476409912109438.984764099121094
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.2140.214
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.0228.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.40315.403
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.676.67
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0920.092
NYPJM->LTFIMP_NY
CLTF
0.0620.062
LGEELTFEXP_LGEE->PJM
CLTF
0.1540.154
CPLELTFEXP_CPLE->PJM
CLTF
0.450.45
TVALTFEXP_TVA->PJM
CLTF
2.392.39
MECLTFEXP_MEC->PJM
CLTF
15.40315.403
LAGNLTFEXP_LAGN->PJM
CLTF
4.5464.546
SIGELTFEXP_SIGE->PJM
CLTF
0.0740.074
O66PJM->LTFIMP_O-066
CMTX_NF
0.5990.599

Details for NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0627__B-R_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0627__B-R_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.05 %
Rating:1656.0 MVA
Rating Type:B
MVA to Mitigate:1789.35
MW Contribution:43.85
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0627__B-R_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.65 %
Rating:1656.0 MVA
Rating Type:B
MVA to Mitigate:1799.28
MW Contribution:43.95
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.80352941176470581.533
962012AG1-044 E
50/50
0.1520.152
290051GSG-6; E
Adder
7.4611764705882356.342
295109WESTBROOK E
Adder
3.99411764705882363.395
295111SUBLETTE E
Adder
1.94235294117647061.651
933911AD1-013 C
Adder
1.24705882352941181.06
933912AD1-013 E
Adder
1.99294117647058821.694
937002AD2-134 E
Adder
7.2141176470588236.132
937312AD2-172 E
Adder
2.25294117647058821.915
958912AF2-182 E
50/50
100.57100.57
274715NELSON EC;1C
50/50
9.2219.221
274717NELSON EC;2C
50/50
9.2929.292
274857BIG SKY ;U1
50/50
0.8330.833
274858BIG SKY ;U2
50/50
0.8330.833
274859EASYR;U1 E
50/50
35.1335.13
274860EASYR;U2 E
50/50
35.1335.13
276156O-029 C
50/50
0.4360.436
276157O-029 C
50/50
0.7860.786
276158O-029 C
50/50
0.7860.786
293715O-029 E
50/50
21.121.1
293716O-029 E
50/50
11.56911.569
293717O-029 E
50/50
10.63310.633
293771O-035 E
Adder
5.9729411764705885.077
294401BSHIL;1U E
Adder
9.1305882352941187.761
294410BSHIL;2U E
Adder
9.1305882352941187.761
294763P-046 E
Adder
6.2611764705882365.322
925582AC1-033 E
Adder
10.0117647058823538.51
939051AE1-134 1
50/50
0.6570.657
939061AE1-134 2
50/50
4.0914.091
940502AE2-035 E
Adder
2.25294117647058821.915
274760LEE CO EC;1U
50/50
4.6514.651
274881WALNUT RG;1U
50/50
1.6671.667
276676AA2-030 GEN
50/50
8.6028.602
276677AA1-146
50/50
10.4110.41
293516O-009 E
50/50
40.840.8
916212CRESCENT ;1U
Adder
4.1964705882352953.567
927208AC1-214 E1
Adder
2.8317647058823532.407
927209AC1-214 E2
Adder
2.8317647058823532.407
990901L-005 E
Adder
12.1847058823529410.357
916221Z1-073 E
Adder
5.257647058823534.469
274761LEE CO EC;2U
50/50
4.6514.651
274762LEE CO EC;3U
50/50
4.6514.651
274763LEE CO EC;4U
50/50
4.6064.606
274764LEE CO EC;5U
50/50
4.6614.661
274765LEE CO EC;6U
50/50
4.6614.661
274766LEE CO EC;7U
50/50
4.5964.596
274767LEE CO EC;8U
50/50
4.5964.596
966822AG1-553 E
50/50
61.66161.661
938861AE1-114 C
Adder
4.90117647058823554.166
938862AE1-114 E
Adder
16.7223529411764714.214
946152AF1-280 E
50/50
67.04767.047
946321AF1-296 C
Adder
7.71764705882352956.56
946322AF1-296 E
Adder
36.12941176470588530.71
946671AF1-331 C
Adder
1.621.377
965931AG1-462 C
50/50
36.28536.285
965932AG1-462 E
50/50
24.1924.19
274716NELSON EC;1S
50/50
6.7286.728
274718NELSON EC;2S
50/50
6.7886.788
276626AG1-044 E
50/50
0.1520.152
991092J1477
External Queue
7.7651863098144537.765186309814453
955972J1084
External Queue
29.56552124023437529.565521240234375
956412J1131
External Queue
15.49937438964843815.499374389648438
990947J1432 C
External Queue
6.457697391510016.45769739151001
990948J1432 E
External Queue
34.9377975463867234.93779754638672
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.1250.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.43163.431
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.88914.889
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.8234.823
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3420.342
NYPJM->LTFIMP_NY
CLTF
0.1940.194
LGEELTFEXP_LGEE->PJM
CLTF
0.0160.016
CPLELTFEXP_CPLE->PJM
CLTF
0.2660.266
TVALTFEXP_TVA->PJM
CLTF
2.2452.245
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0260.026
MECLTFEXP_MEC->PJM
CLTF
16.69316.693
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0090.009
LAGNLTFEXP_LAGN->PJM
CLTF
4.5854.585
SIGELTFEXP_SIGE->PJM
CLTF
0.0510.051
O66PJM->LTFIMP_O-066
CMTX_NF
2.2012.201

Details for NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.46 %
Rating:1334.0 MVA
Rating Type:A
MVA to Mitigate:1380.1
MW Contribution:32.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.95 %
Rating:1334.0 MVA
Rating Type:A
MVA to Mitigate:1386.65
MW Contribution:32.73
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.57764705882352941.341
962012AG1-044 E
50/50
0.1120.112
290051GSG-6; E
Adder
6.48117647058823555.509
295109WESTBROOK E
Adder
3.4694117647058822.949
295111SUBLETTE E
Adder
1.68705882352941171.434
933911AD1-013 C
Adder
1.09294117647058830.929
933912AD1-013 E
Adder
1.74588235294117641.484
937002AD2-134 E
Adder
6.2658823529411765.326
937312AD2-172 E
Adder
3.09058823529411742.627
958912AF2-182 E
50/50
60.32260.322
274715NELSON EC;1C
50/50
6.6346.634
274717NELSON EC;2C
50/50
6.6856.685
274857BIG SKY ;U1
50/50
0.4550.455
274858BIG SKY ;U2
50/50
0.4550.455
274859EASYR;U1 E
50/50
19.219.2
274860EASYR;U2 E
50/50
19.219.2
276156O-029 C
50/50
0.3210.321
276157O-029 C
50/50
0.5780.578
276158O-029 C
50/50
0.5780.578
293715O-029 E
50/50
15.50715.507
293716O-029 E
50/50
8.5028.502
293717O-029 E
50/50
7.8157.815
293771O-035 E
Adder
4.3282352941176473.679
294401BSHIL;1U E
Adder
6.6588235294117655.66
294410BSHIL;2U E
Adder
6.6588235294117655.66
294763P-046 E
Adder
8.5905882352941177.302
925582AC1-033 E
Adder
7.3023529411764716.207
939051AE1-134 1
50/50
0.4730.473
939061AE1-134 2
50/50
2.9432.943
940502AE2-035 E
Adder
3.09058823529411742.627
274760LEE CO EC;1U
50/50
2.5422.542
274881WALNUT RG;1U
50/50
1.2251.225
276676AA2-030 GEN
50/50
6.1886.188
276677AA1-146
50/50
7.4897.489
293516O-009 E
50/50
29.98629.986
916212CRESCENT ;1U
Adder
3.0411764705882352.585
927208AC1-214 E1
Adder
2.0517647058823531.744
927209AC1-214 E2
Adder
2.0517647058823531.744
990901L-005 E
Adder
8.8729411764705887.542
916221Z1-073 E
Adder
4.5670588235294123.882
274761LEE CO EC;2U
50/50
2.5422.542
274762LEE CO EC;3U
50/50
2.5422.542
274763LEE CO EC;4U
50/50
2.5182.518
274764LEE CO EC;5U
50/50
2.5482.548
274765LEE CO EC;6U
50/50
2.5482.548
274766LEE CO EC;7U
50/50
2.5122.512
274767LEE CO EC;8U
50/50
2.5122.512
966822AG1-553 E
50/50
45.45745.457
938861AE1-114 C
Adder
4.69058823529411753.987
938862AE1-114 E
Adder
16.0047058823529413.604
946152AF1-280 E
50/50
40.21540.215
946321AF1-296 C
Adder
5.7494117647058824.887
946322AF1-296 E
Adder
26.91882352941176422.881
946671AF1-331 C
Adder
1.42000000000000021.207
965931AG1-462 C
50/50
26.7526.75
965932AG1-462 E
50/50
17.83317.833
274716NELSON EC;1S
50/50
4.844.84
274718NELSON EC;2S
50/50
4.8834.883
276626AG1-044 E
50/50
0.1120.112
991092J1477
External Queue
5.500812053680425.50081205368042
955972J1084
External Queue
20.9585704803466820.95857048034668
956412J1131
External Queue
10.9796648025512710.97966480255127
990947J1432 C
External Queue
4.7147688865661624.714768886566162
990948J1432 E
External Queue
25.50810813903808625.508108139038086
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0610.061
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.33663.336
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.35211.352
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.0093.009
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3650.365
NYPJM->LTFIMP_NY
CLTF
0.2040.204
WECLTFEXP_WEC->PJM
CLTF
0.6580.658
CPLELTFEXP_CPLE->PJM
CLTF
0.1330.133
TVALTFEXP_TVA->PJM
CLTF
1.6851.685
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0730.073
MECLTFEXP_MEC->PJM
CLTF
13.47113.471
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.1690.169
LAGNLTFEXP_LAGN->PJM
CLTF
3.5753.575
SIGELTFEXP_SIGE->PJM
CLTF
0.0310.031
O66PJM->LTFIMP_O-066
CMTX_NF
2.3472.347

Details for QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_636600 SUB 39 3 345 636605 MEC CORDOVA3 345 1 _SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/MEC
Facility Description:
QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line
Contingency Name:
EXT_636600 SUB 39 3 345 636605 MEC CORDOVA3 345 1 _SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.43 %
Rating:1471.0 MVA
Rating Type:B
MVA to Mitigate:1521.53
MW Contribution:12.35
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE/MEC
Facility Description:
QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line
Contingency Name:
EXT_636600 SUB 39 3 345 636605 MEC CORDOVA3 345 1 _SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.47 %
Rating:1471.0 MVA
Rating Type:B
MVA to Mitigate:1522.0
MW Contribution:12.37
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.97882352941176461.682
962012AG1-044 E
Adder
0.076470588235294120.065
962781AG1-127 C
Adder
4.0470588235294123.44
962782AG1-127 E
Adder
2.69294117647058862.289
290051GSG-6; E
Adder
7.9635294117647066.769
295109WESTBROOK E
Adder
4.2635294117647063.624
295111SUBLETTE E
Adder
2.07294117647058851.762
933911AD1-013 C
Adder
1.38117647058823521.174
933912AD1-013 E
Adder
2.20588235294117661.875
937002AD2-134 E
Adder
7.6988235294117646.544
937312AD2-172 E
Adder
2.8235294117647062.4
958912AF2-182 E
50/50
46.4146.41
959081AF2-199 C
Adder
7.1352941176470596.065
959082AF2-199 E
Adder
3.5682352941176473.033
960582AF2-349 E
Adder
21.9705882352941218.675
960751AF2-366 C
Adder
4.0352941176470593.43
960752AF2-366 E
Adder
2.69058823529411752.287
274662QUAD CITI;1U
50/50
43.85643.856
274663QUAD CITI;2U
50/50
43.32643.326
274699CORDOVA ;1C
50/50
7.5677.567
274700CORDOVA ;2C
50/50
7.5677.567
274701CORDOVA ;1S
50/50
8.5138.513
274715NELSON EC;1C
50/50
4.8674.867
274717NELSON EC;2C
50/50
4.9044.904
274859EASYR;U1 E
Adder
15.17411764705882312.898
274860EASYR;U2 E
Adder
15.17411764705882312.898
293715O-029 E
Adder
9.7658823529411768.301
293716O-029 E
Adder
5.3541176470588244.551
293717O-029 E
Adder
4.9211764705882354.183
294763P-046 E
Adder
7.8470588235294126.67
939051AE1-134 1
50/50
0.3470.347
939061AE1-134 2
50/50
2.1592.159
940502AE2-035 E
Adder
2.8235294117647062.4
957471AF2-041 C
Adder
21.40705882352941518.196
957472AF2-041 E
Adder
10.7035294117647079.098
274760LEE CO EC;1U
50/50
2.0092.009
276676AA2-030 GEN
50/50
4.544.54
276677AA1-146
50/50
5.4945.494
293516O-009 E
Adder
18.88352941176470516.051
290108LEEDK;1U E
Adder
14.94352941176470612.702
916221Z1-073 E
Adder
5.61176470588235254.77
274761LEE CO EC;2U
50/50
2.0092.009
274762LEE CO EC;3U
50/50
2.0092.009
274763LEE CO EC;4U
50/50
1.991.99
274764LEE CO EC;5U
50/50
2.0142.014
274765LEE CO EC;6U
50/50
2.0142.014
959091AF2-200 C
Adder
14.27058823529411812.13
959092AF2-200 E
Adder
9.5141176470588238.087
966822AG1-553 E
50/50
75.16475.164
938861AE1-114 C
Adder
3.86588235294117683.286
938862AE1-114 E
Adder
13.19176470588235311.213
946152AF1-280 E
50/50
30.9430.94
946321AF1-296 C
Adder
2.1729411764705881.847
946322AF1-296 E
Adder
10.1752941176470578.649
946671AF1-331 C
Adder
1.79294117647058831.524
962691AG1-118 C
Adder
12.27882352941176510.437
962692AG1-118 E
Adder
8.1858823529411766.958
965931AG1-462 C
50/50
44.23144.231
965932AG1-462 E
50/50
29.48729.487
274716NELSON EC;1S
50/50
3.5513.551
274718NELSON EC;2S
50/50
3.5833.583
920272AA2-123 E
Adder
1.53647058823529431.306
276170Z1-108 E
Adder
1.22941176470588221.045
276626AG1-044 E
Adder
0.090588235294117650.077
990512J1326 G
External Queue
5.8924369812011725.892436981201172
991092J1477
External Queue
-14.100622177124023-14.100622177124023
955972J1084
External Queue
42.9220466613769542.92204666137695
990117J1214 G
External Queue
23.5383644104003923.53836441040039
990407J1304 G
External Queue
5.6877913475036625.687791347503662
990727J1377 G
External Queue
8.9315605163574228.931560516357422
990947J1432 C
External Queue
7.8979654312133797.897965431213379
990948J1432 E
External Queue
42.73001861572265642.730018615722656
991777J1629 G
External Queue
11.71470451354980511.714704513549805
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
3.3263.326
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
1.1491.149
G-007PJM->LTFIMP_G-007
CMTX_NF
1.0161.016
NYPJM->LTFIMP_NY
CLTF
0.5220.522
WECLTFEXP_WEC->PJM
CLTF
1.1391.139
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
7.8377.837
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.9270.927
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.5880.588
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
10.87110.871
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6860.686
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.2052.205
O66PJM->LTFIMP_O-066
CMTX_NF
6.5076.507
MDUPJM->LTFIMP_MDU
CLTF
0.5030.503
CONTINGENCY 'COMED_P1-2_345-L0626__B-R_SRT-A'
 TRIP BRANCH FROM BUS 270678 TO BUS 270916 CKT 1   /*BYRON    ; B 345.0 - WAYNE    ; B 345.0
END
CONTINGENCY 'COMED_P1-2_345-L11120_R-N_SRT-A'
 MOVE 100 PERCENT LOAD FROM BUS 270749 TO BUS 270751   /*ESS W407M; R 345.0 - ESS W407M;9T 345.0
 TRIP BRANCH FROM BUS 270733 TO BUS 270747 CKT 1       /*ELECT JCT;3R 345.0 - ESS W407K;0T 345.0
 TRIP BRANCH FROM BUS 270747 TO BUS 270753 CKT 1       /*ESS W407K;0T 345.0 - ESS W407M;0T 345.0
 TRIP BRANCH FROM BUS 270753 TO BUS 270749 CKT 1       /*ESS W407M;0T 345.0 - ESS W407M; R 345.0
 TRIP BRANCH FROM BUS 270753 TO BUS 270813 CKT 1       /*ESS W407M;0T 345.0 - LOMBARD  ; R 345.0
END
CONTINGENCY 'COMED_P1-2_345-L15502_B-R_SRT-A-2'
 TRIP BRANCH FROM BUS 957470 TO BUS 270730 CKT 1   /*AF2-041 TP   345.0 - ELECT JCT; B 345.0
END
CONTINGENCY 'COMED_P1-2_345-L0627__B-R_SRT-A'
 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1   /*LEE CO EC;BP 345.0 - BYRON    ; B 345.0
END
CONTINGENCY 'EXT_636600 SUB 39 3 345 636605 MEC CORDOVA3 345 1 _SRT-S'
 OPEN BRANCH FROM BUS 636600 TO BUS 636605 CKT 1   /*SUB 39 3     345.0 - MEC CORDOVA3 345.0
END
957470 to 270730 ckt 1
270694 to 276670 ckt 1
270730 to 270812 ckt 1
276670 to 270883 ckt 1
274768 to 270678 ckt 1
270828 to 957470 ckt 1
270866 to 636610 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AF1-296 was evaluated as a 190.9 MW injection in the ComEd area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC127.96 %1075.0B1375.5917.62
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC127.94 %1075.0B1375.3717.62
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC117.34 %1075.0B1261.4317.33
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC122.26 %971.0B1187.1213.03
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC122.21 %971.0B1186.713.03
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC108.87 %971.0B1057.1213.03
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC108.87 %971.0B1057.1113.03
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC115.73 %1399.0B1619.0115.69
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC115.64 %1399.0B1617.8415.69
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC103.82 %1399.0B1452.4615.64
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC102.92 %1399.0B1439.8115.7
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Base Case
SingleAC100.53 %1091.0A1096.7910.42
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC115.75 %1399.0B1619.415.69
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC115.67 %1399.0B1618.2215.69
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC103.83 %1399.0B1452.5315.64
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC102.92 %1399.0B1439.8615.7
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Base Case
SingleAC100.52 %1091.0A1096.7210.42
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC119.44 %970.0STE1158.6113.03
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC119.42 %970.0STE1158.4213.03
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC105.94 %970.0STE1027.613.03
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC105.94 %970.0STE1027.5913.03

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.96 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1375.59
MW Contribution:17.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
5.3895.389
290051GSG-6; E
80/20
2.8722.872
290108LEEDK;1U E
80/20
6.5926.592
290261S-027 E
80/20
4.1334.133
290265S-028 E
80/20
4.1084.108
295111SUBLETTE E
80/20
0.7470.747
925581AC1-033 C
80/20
0.6150.615
925582AC1-033 E
80/20
4.1154.115
938861AE1-114 C
80/20
3.4363.436
957371AF2-031 C
80/20
1.5261.526
960261AF2-317 C
80/20
0.4950.495
961501AF2-441 C
80/20
14.5914.59
274851PROVIDENC;RU
80/20
0.3040.304
274853TWINGROVE;U1
80/20
0.8810.881
274854TWINGROVE;U2
80/20
0.9070.907
274855GSG-6 ;RU
80/20
0.7180.718
274879MINONK ;1U
80/20
1.3331.333
274880RADFORD R;1U
80/20
0.9440.944
274881WALNUT RG;1U
80/20
1.2841.284
293645O22 E2
80/20
4.6364.636
293715O-029 E
80/20
2.6572.657
293717O-029 E
80/20
1.3391.339
916212CRESCENT ;1U
80/20
1.3211.321
916221Z1-073 E
80/20
2.0242.024
957331AF2-027 C
80/20
2.7442.744
957332AF2-027 E
80/20
4.1174.117
959352AF2-226 E
80/20
4.2274.227
960281AF2-319 C
80/20
2.8182.818
960282AF2-319 E
80/20
4.2274.227
270839OTTER CRK; R
80/20
0.6710.671
274888KELLY CRK;1U
80/20
1.3431.343
293716O-029 E
80/20
1.4571.457
937002AD2-134 E
80/20
4.4474.447
938852AE1-113 E
80/20
24.94624.946
938862AE1-114 E
80/20
11.72411.724
270681BRIGHTSTK; R
80/20
0.6920.692
274887PILOT HIL;1U
80/20
1.3431.343
275149KELLYCK ;1E
80/20
5.3725.372
293771O-035 E
80/20
1.8811.881
924048AB2-047 E1
80/20
2.8732.873
937001AD2-134 C
80/20
1.1131.113
944221AF1-090 C
80/20
1.7541.754
274682WAUKEGAN ;7U
80/20
20.43720.437
274683WAUKEGAN ;8U
80/20
22.03122.031
274861TOP CROP ;1U
80/20
0.6480.648
274862TOP CROP ;2U
80/20
1.2361.236
274863CAYUGA RI;1U
80/20
0.7080.708
276157O-029 C
80/20
0.6060.606
276158O-029 C
80/20
0.6060.606
934721AD1-100 C
80/20
5.2135.213
942421AE2-255 C
80/20
2.6652.665
942422AE2-255 E
80/20
7.9967.996
959611AF2-252 C
80/20
2.0262.026
960611AF2-352 C
80/20
2.0262.026
960612AF2-352 E
80/20
3.0393.039
990901L-005 E
80/20
3.4733.473
276645AC1-214 C1
80/20
0.2510.251
276646AC1-214 C2
80/20
0.2510.251
925771AC1-053 C
80/20
0.8460.846
962012AG1-044 E
80/20
0.0610.061
274864CAYUGA RI;2U
80/20
0.7080.708
276655AB2-047 C1
80/20
0.4330.433
294392P-010 E
80/20
5.3475.347
294410BSHIL;2U E
80/20
2.3442.344
918052AA1-018 E OP
80/20
4.4934.493
926822AC1-168 E
80/20
6.6946.694
927209AC1-214 E2
80/20
0.8920.892
274687WILL CNTY;4U
80/20
45.63745.637
276656AB2-047 C2
80/20
0.4330.433
294401BSHIL;1U E
80/20
2.3442.344
925772AC1-053 E
80/20
5.6625.662
926821AC1-168 C
80/20
0.9980.998
927208AC1-214 E1
80/20
0.8920.892
959612AF2-252 E
80/20
3.0393.039
274848CAMPGROVE;RU
80/20
0.3760.376
274850MENDOTA H;RU
80/20
0.4720.472
274856ECOGROVE ;U1
80/20
0.620.62
274858BIG SKY ;U2
80/20
0.4760.476
274871GR RIDGE ;2U
80/20
0.3580.358
274877BISHOP HL;1U
80/20
0.5860.586
276615W2-048 GEN
80/20
1.2811.281
293516O-009 E
80/20
5.1385.138
293644O22 E1
80/20
4.0484.048
924266AB2-070 E
80/20
3.253.25
936372AD2-047 E
80/20
20.38420.384
939321AE1-163 C
80/20
5.2615.261
942111AE2-223 C
80/20
1.6621.662
942652AE2-281 E
80/20
4.6174.617
946321AF1-296 C
80/20
3.1023.102
966441AG1-513 C
80/20
0.5610.561
274676JOLIET 29;8U
80/20
48.17348.173
294763P-046 E
80/20
2.5772.577
295109WESTBROOK E
80/20
1.5381.538
936371AD2-047 C
80/20
4.1754.175
938851AE1-113 C
80/20
7.0367.036
957372AF2-031 E
80/20
2.2882.288
965331AG1-398 C
80/20
0.2420.242
966442AG1-513 E
80/20
0.8410.841
274675JOLIET 29;7U
80/20
48.1748.17
274860EASYR;U2 E
80/20
3.283.28
276156O-029 C
80/20
0.3360.336
290021O50 E
80/20
5.335.33
961502AF2-441 E
80/20
21.88421.884
966091AG1-478 C
80/20
0.5860.586
274847GR RIDGE ;BU
80/20
0.9610.961
274849CRESCENT ;1U
80/20
0.2860.286
274857BIG SKY ;U1
80/20
0.4760.476
274859EASYR;U1 E
80/20
3.283.28
274872LEE DEKAL;1U
80/20
1.3351.335
276621X2-022 GEN
80/20
3.6453.645
293061N-015 E
80/20
4.214.21
293519PILOT HIL;1E
80/20
5.3725.372
924049AB2-047 E2
80/20
2.9192.919
934722AD1-100 E
80/20
81.09481.094
939322AE1-163 E
80/20
32.3232.32
944222AF1-090 E
80/20
8.2118.211
946322AF1-296 E
80/20
14.52214.522
959351AF2-226 C
80/20
2.8182.818
966092AG1-478 E
80/20
0.8780.878
276627AG1-044 BAT
80/20
0.0120.012
935141AD1-148 C
80/20
1.1451.145
957382AF2-032 E
80/20
0.1430.143
274891CAYUG;2U E
80/20
3.7773.777
276603SUBLETTE C
80/20
0.1050.105
276668AB2-070 C
80/20
0.5370.537
274878BISHOP HL;2U
80/20
0.5860.586
276626AG1-044 E
80/20
0.0680.068
917502Z2-087 E
80/20
4.6344.634
942112AE2-223 E
80/20
11.12111.121
274674JOLIET 9 ;6U
80/20
18.55318.553
274890CAYUG;1U E
80/20
3.7773.777
276602WESTBROOK C
80/20
0.2330.233
276675AE2-062 E
80/20
0.1460.146
942651AE2-281 C
80/20
0.7520.752
965913AG1-460 BT
80/20
0.0070.007
920272AA2-123 E
80/20
2.682.68
276170Z1-108 E
80/20
2.7352.735
990647J1355
External Queue
42.973342.9733
990547J1333 G
External Queue
9.21919.2191
990582J1340
External Queue
6.17656.1765
990552J1334 G
External Queue
9.21919.2191
990557J1335 G
External Queue
9.21919.2191
990562J1336 G
External Queue
9.21919.2191
990577J1339
External Queue
2.90532.9053

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.94 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1375.37
MW Contribution:17.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
5.3895.389
290051GSG-6; E
80/20
2.8722.872
290108LEEDK;1U E
80/20
6.5926.592
290261S-027 E
80/20
4.1334.133
290265S-028 E
80/20
4.1084.108
295111SUBLETTE E
80/20
0.7470.747
925581AC1-033 C
80/20
0.6150.615
925582AC1-033 E
80/20
4.1154.115
938861AE1-114 C
80/20
3.4363.436
957371AF2-031 C
80/20
1.5261.526
960261AF2-317 C
80/20
0.4950.495
961501AF2-441 C
80/20
14.5914.59
274851PROVIDENC;RU
80/20
0.3040.304
274853TWINGROVE;U1
80/20
0.8810.881
274854TWINGROVE;U2
80/20
0.9070.907
274855GSG-6 ;RU
80/20
0.7180.718
274879MINONK ;1U
80/20
1.3331.333
274880RADFORD R;1U
80/20
0.9440.944
274881WALNUT RG;1U
80/20
1.2841.284
293645O22 E2
80/20
4.6364.636
293715O-029 E
80/20
2.6572.657
293717O-029 E
80/20
1.3391.339
916212CRESCENT ;1U
80/20
1.3211.321
916221Z1-073 E
80/20
2.0242.024
957331AF2-027 C
80/20
2.7442.744
957332AF2-027 E
80/20
4.1174.117
959352AF2-226 E
80/20
4.2274.227
960281AF2-319 C
80/20
2.8182.818
960282AF2-319 E
80/20
4.2274.227
270839OTTER CRK; R
80/20
0.6710.671
274888KELLY CRK;1U
80/20
1.3431.343
293716O-029 E
80/20
1.4571.457
937002AD2-134 E
80/20
4.4474.447
938852AE1-113 E
80/20
24.94624.946
938862AE1-114 E
80/20
11.72411.724
270681BRIGHTSTK; R
80/20
0.6920.692
274887PILOT HIL;1U
80/20
1.3431.343
275149KELLYCK ;1E
80/20
5.3725.372
293771O-035 E
80/20
1.8811.881
924048AB2-047 E1
80/20
2.8732.873
937001AD2-134 C
80/20
1.1131.113
944221AF1-090 C
80/20
1.7541.754
274682WAUKEGAN ;7U
80/20
20.43720.437
274683WAUKEGAN ;8U
80/20
22.03122.031
274861TOP CROP ;1U
80/20
0.6480.648
274862TOP CROP ;2U
80/20
1.2361.236
274863CAYUGA RI;1U
80/20
0.7080.708
276157O-029 C
80/20
0.6060.606
276158O-029 C
80/20
0.6060.606
934721AD1-100 C
80/20
5.2135.213
942421AE2-255 C
80/20
2.6652.665
942422AE2-255 E
80/20
7.9967.996
959611AF2-252 C
80/20
2.0262.026
960611AF2-352 C
80/20
2.0262.026
960612AF2-352 E
80/20
3.0393.039
990901L-005 E
80/20
3.4733.473
276645AC1-214 C1
80/20
0.2510.251
276646AC1-214 C2
80/20
0.2510.251
925771AC1-053 C
80/20
0.8460.846
962012AG1-044 E
80/20
0.0610.061
274864CAYUGA RI;2U
80/20
0.7080.708
276655AB2-047 C1
80/20
0.4330.433
294392P-010 E
80/20
5.3475.347
294410BSHIL;2U E
80/20
2.3442.344
918052AA1-018 E OP
80/20
4.4934.493
926822AC1-168 E
80/20
6.6946.694
927209AC1-214 E2
80/20
0.8920.892
274687WILL CNTY;4U
80/20
45.63745.637
276656AB2-047 C2
80/20
0.4330.433
294401BSHIL;1U E
80/20
2.3442.344
925772AC1-053 E
80/20
5.6625.662
926821AC1-168 C
80/20
0.9980.998
927208AC1-214 E1
80/20
0.8920.892
959612AF2-252 E
80/20
3.0393.039
274848CAMPGROVE;RU
80/20
0.3760.376
274850MENDOTA H;RU
80/20
0.4720.472
274856ECOGROVE ;U1
80/20
0.620.62
274858BIG SKY ;U2
80/20
0.4760.476
274871GR RIDGE ;2U
80/20
0.3580.358
274877BISHOP HL;1U
80/20
0.5860.586
276615W2-048 GEN
80/20
1.2811.281
293516O-009 E
80/20
5.1385.138
293644O22 E1
80/20
4.0484.048
924266AB2-070 E
80/20
3.253.25
936372AD2-047 E
80/20
20.38420.384
939321AE1-163 C
80/20
5.2615.261
942111AE2-223 C
80/20
1.6621.662
942652AE2-281 E
80/20
4.6174.617
946321AF1-296 C
80/20
3.1023.102
966441AG1-513 C
80/20
0.5610.561
274676JOLIET 29;8U
80/20
48.17348.173
294763P-046 E
80/20
2.5772.577
295109WESTBROOK E
80/20
1.5381.538
936371AD2-047 C
80/20
4.1754.175
938851AE1-113 C
80/20
7.0367.036
957372AF2-031 E
80/20
2.2882.288
965331AG1-398 C
80/20
0.2420.242
966442AG1-513 E
80/20
0.8410.841
274675JOLIET 29;7U
80/20
48.1748.17
274860EASYR;U2 E
80/20
3.283.28
276156O-029 C
80/20
0.3360.336
290021O50 E
80/20
5.335.33
961502AF2-441 E
80/20
21.88421.884
966091AG1-478 C
80/20
0.5860.586
274847GR RIDGE ;BU
80/20
0.9610.961
274849CRESCENT ;1U
80/20
0.2860.286
274857BIG SKY ;U1
80/20
0.4760.476
274859EASYR;U1 E
80/20
3.283.28
274872LEE DEKAL;1U
80/20
1.3351.335
276621X2-022 GEN
80/20
3.6453.645
293061N-015 E
80/20
4.214.21
293519PILOT HIL;1E
80/20
5.3725.372
924049AB2-047 E2
80/20
2.9192.919
934722AD1-100 E
80/20
81.09481.094
939322AE1-163 E
80/20
32.3232.32
944222AF1-090 E
80/20
8.2118.211
946322AF1-296 E
80/20
14.52214.522
959351AF2-226 C
80/20
2.8182.818
966092AG1-478 E
80/20
0.8780.878
276627AG1-044 BAT
80/20
0.0120.012
935141AD1-148 C
80/20
1.1451.145
957382AF2-032 E
80/20
0.1430.143
274891CAYUG;2U E
80/20
3.7773.777
276603SUBLETTE C
80/20
0.1050.105
276668AB2-070 C
80/20
0.5370.537
274878BISHOP HL;2U
80/20
0.5860.586
276626AG1-044 E
80/20
0.0680.068
917502Z2-087 E
80/20
4.6344.634
942112AE2-223 E
80/20
11.12111.121
274674JOLIET 9 ;6U
80/20
18.55318.553
274890CAYUG;1U E
80/20
3.7773.777
276602WESTBROOK C
80/20
0.2330.233
276675AE2-062 E
80/20
0.1460.146
942651AE2-281 C
80/20
0.7520.752
965913AG1-460 BT
80/20
0.0070.007
920272AA2-123 E
80/20
2.682.68
276170Z1-108 E
80/20
2.7352.735
990647J1355
External Queue
42.973342.9733
990547J1333 G
External Queue
9.21919.2191
990582J1340
External Queue
6.17656.1765
990552J1334 G
External Queue
9.21919.2191
990557J1335 G
External Queue
9.21919.2191
990562J1336 G
External Queue
9.21919.2191
990577J1339
External Queue
2.90532.9053

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.34 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1261.43
MW Contribution:17.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
3.35882352941176482.855
957371AF2-031 C
50/50
1.4761.476
961501AF2-441 C
50/50
14.11814.118
293645O22 E2
50/50
4.5074.507
957331AF2-027 C
Adder
2.66941176470588242.269
957332AF2-027 E
Adder
4.0035294117647063.403
959352AF2-226 E
50/50
4.114.11
960281AF2-319 C
50/50
2.742.74
960282AF2-319 E
50/50
4.114.11
274888KELLY CRK;1U
50/50
1.3011.301
938852AE1-113 E
Adder
24.32235294117647220.674
938862AE1-114 E
Adder
11.4611764705882379.742
274887PILOT HIL;1U
50/50
1.3011.301
275149KELLYCK ;1E
50/50
5.2055.205
944221AF1-090 C
Adder
1.85529411764705881.577
274682WAUKEGAN ;7U
50/50
19.86719.867
274683WAUKEGAN ;8U
Adder
21.4218.207
274861TOP CROP ;1U
50/50
0.630.63
274862TOP CROP ;2U
50/50
1.2021.202
934721AD1-100 C
50/50
5.0615.061
942421AE2-255 C
Adder
2.5988235294117652.209
942422AE2-255 E
Adder
7.7952941176470596.626
959611AF2-252 C
Adder
2.02588235294117651.722
960611AF2-352 C
Adder
2.02588235294117651.722
960612AF2-352 E
Adder
3.03764705882352942.582
962012AG1-044 E
Adder
0.060.051
294392P-010 E
50/50
5.1945.194
926822AC1-168 E
Adder
6.5682352941176475.583
274687WILL CNTY;4U
50/50
44.2244.22
926821AC1-168 C
Adder
0.97882352941176460.832
959612AF2-252 E
Adder
3.03764705882352942.582
274676JOLIET 29;8U
50/50
46.68546.685
936371AD2-047 C
50/50
4.0454.045
938851AE1-113 C
Adder
6.865.831
957372AF2-031 E
50/50
2.2132.213
274675JOLIET 29;7U
50/50
46.68246.682
961502AF2-441 E
50/50
21.17621.176
966091AG1-478 C
50/50
0.5680.568
966442AG1-513 E
50/50
0.8170.817
276627AG1-044 BAT
Adder
0.0117647058823529410.01
957382AF2-032 E
Adder
0.148235294117647080.126
274871GR RIDGE ;2U
50/50
0.3480.348
276626AG1-044 E
Adder
0.067058823529411770.057
942112AE2-223 E
Adder
11.0670588235294139.407
274847GR RIDGE ;BU
50/50
0.9340.934
293061N-015 E
50/50
4.094.09
293519PILOT HIL;1E
50/50
5.2055.205
934722AD1-100 E
50/50
78.72578.725
939322AE1-163 E
Adder
31.4705882352941226.75
944222AF1-090 E
Adder
8.684705882352947.382
946322AF1-296 E
Adder
14.27882352941176512.137
959351AF2-226 C
50/50
2.742.74
966092AG1-478 E
50/50
0.8520.852
293644O22 E1
50/50
3.9353.935
936372AD2-047 E
50/50
19.74719.747
939321AE1-163 C
Adder
5.1235294117647064.355
942111AE2-223 C
Adder
1.65411764705882351.406
942652AE2-281 E
Adder
4.49529411764705963.821
946321AF1-296 C
Adder
3.0505882352941182.593
966441AG1-513 C
50/50
0.5450.545
274674JOLIET 9 ;6U
50/50
17.99517.995
276675AE2-062 E
50/50
0.1410.141
942651AE2-281 C
Adder
0.7317647058823530.622
965913AG1-460 BT
Adder
0.0070588235294117650.006
920272AA2-123 E
Adder
3.07176470588235342.611
276170Z1-108 E
Adder
3.1294117647058832.66
990512J1326 G
External Queue
5.28785.2878
990647J1355
External Queue
41.608541.6085
990547J1333 G
External Queue
8.86958.8695
991302J1755
External Queue
9.68289.6828
990582J1340
External Queue
5.89225.8922
990662J1358
External Queue
14.341514.3415
990947J1432 G
External Queue
14.957514.9575
991092J1477
External Queue
2.81562.8156
990052J1200
External Queue
0.42270.4227
990552J1334 G
External Queue
8.86958.8695
990557J1335 G
External Queue
8.86958.8695
990562J1336 G
External Queue
8.86958.8695
990577J1339
External Queue
5.89225.8922

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.26 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1187.12
MW Contribution:13.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
3.7663.766
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
295111SUBLETTE E
80/20
0.5570.557
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
938861AE1-114 C
80/20
2.5552.555
957371AF2-031 C
80/20
0.6360.636
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274881WALNUT RG;1U
80/20
0.9520.952
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293717O-029 E
80/20
0.9930.993
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959352AF2-226 E
80/20
2.9452.945
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
270839OTTER CRK; R
80/20
0.5410.541
274888KELLY CRK;1U
80/20
0.9460.946
293716O-029 E
80/20
1.081.08
937002AD2-134 E
80/20
3.3123.312
938852AE1-113 E
80/20
18.55518.555
938862AE1-114 E
80/20
8.7168.716
270681BRIGHTSTK; R
80/20
0.4980.498
274887PILOT HIL;1U
80/20
0.9460.946
275149KELLYCK ;1E
80/20
3.7863.786
293771O-035 E
80/20
1.3921.392
924048AB2-047 E1
80/20
2.0672.067
937001AD2-134 C
80/20
0.8290.829
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
934721AD1-100 C
80/20
3.8223.822
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
959611AF2-252 C
80/20
1.4511.451
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
990901L-005 E
80/20
2.5642.564
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
925771AC1-053 C
80/20
0.590.59
962012AG1-044 E
80/20
0.0450.045
274864CAYUGA RI;2U
80/20
0.5160.516
276655AB2-047 C1
80/20
0.3110.311
294392P-010 E
80/20
4.0594.059
294410BSHIL;2U E
80/20
1.7331.733
918052AA1-018 E OP
80/20
3.6223.622
926822AC1-168 E
80/20
4.9814.981
927209AC1-214 E2
80/20
0.660.66
965791AG1-447 C
80/20
46.67646.676
274687WILL CNTY;4U
80/20
32.59232.592
276656AB2-047 C2
80/20
0.3110.311
294401BSHIL;1U E
80/20
1.7331.733
925772AC1-053 E
80/20
3.953.95
926821AC1-168 C
80/20
0.7420.742
927208AC1-214 E1
80/20
0.660.66
959612AF2-252 E
80/20
2.1762.176
274848CAMPGROVE;RU
80/20
0.2780.278
274850MENDOTA H;RU
80/20
0.3520.352
274856ECOGROVE ;U1
80/20
0.4620.462
274858BIG SKY ;U2
80/20
0.3530.353
274871GR RIDGE ;2U
80/20
0.2720.272
274877BISHOP HL;1U
80/20
0.4330.433
276615W2-048 GEN
80/20
0.8910.891
293516O-009 E
80/20
3.8093.809
293644O22 E1
80/20
2.822.82
924266AB2-070 E
80/20
2.272.27
936372AD2-047 E
80/20
14.36514.365
939321AE1-163 C
80/20
4.1514.151
942111AE2-223 C
80/20
1.1951.195
942652AE2-281 E
80/20
3.6423.642
946321AF1-296 C
80/20
2.2942.294
966441AG1-513 C
80/20
0.4190.419
274676JOLIET 29;8U
80/20
36.23736.237
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
936371AD2-047 C
80/20
2.9422.942
938851AE1-113 C
80/20
5.2345.234
957372AF2-031 E
80/20
0.9540.954
965331AG1-398 C
80/20
0.1690.169
966442AG1-513 E
80/20
0.6290.629
274675JOLIET 29;7U
80/20
36.25136.251
274860EASYR;U2 E
80/20
2.4372.437
276156O-029 C
80/20
0.2490.249
290021O50 E
80/20
3.9653.965
961502AF2-441 E
80/20
10.40210.402
966091AG1-478 C
80/20
0.4310.431
274847GR RIDGE ;BU
80/20
0.730.73
274849CRESCENT ;1U
80/20
0.2120.212
274857BIG SKY ;U1
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274872LEE DEKAL;1U
80/20
0.9950.995
276621X2-022 GEN
80/20
2.5362.536
293061N-015 E
80/20
3.1963.196
293519PILOT HIL;1E
80/20
3.7863.786
924049AB2-047 E2
80/20
2.0992.099
934722AD1-100 E
80/20
59.4559.45
939322AE1-163 E
80/20
25.49625.496
946322AF1-296 E
80/20
10.73910.739
959351AF2-226 C
80/20
1.9641.964
966092AG1-478 E
80/20
0.6470.647
276627AG1-044 BAT
80/20
0.0090.009
935141AD1-148 C
80/20
0.7970.797
274891CAYUG;2U E
80/20
2.7522.752
276603SUBLETTE C
80/20
0.0780.078
276668AB2-070 C
80/20
0.3750.375
274878BISHOP HL;2U
80/20
0.4330.433
276626AG1-044 E
80/20
0.0510.051
917502Z2-087 E
80/20
3.3333.333
942112AE2-223 E
80/20
7.9997.999
274674JOLIET 9 ;6U
80/20
13.64413.644
274890CAYUG;1U E
80/20
2.7522.752
276602WESTBROOK C
80/20
0.1730.173
276675AE2-062 E
80/20
0.1120.112
942651AE2-281 C
80/20
0.5930.593
276170Z1-108 E
80/20
2.0422.042
920272AA2-123 E
80/20
22
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769
990052J1200
External Queue
0.35320.3532

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.21 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1186.7
MW Contribution:13.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
3.7663.766
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
295111SUBLETTE E
80/20
0.5570.557
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
938861AE1-114 C
80/20
2.5552.555
957371AF2-031 C
80/20
0.6360.636
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274881WALNUT RG;1U
80/20
0.9520.952
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293717O-029 E
80/20
0.9930.993
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959352AF2-226 E
80/20
2.9452.945
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
270839OTTER CRK; R
80/20
0.5410.541
274888KELLY CRK;1U
80/20
0.9460.946
293716O-029 E
80/20
1.081.08
937002AD2-134 E
80/20
3.3123.312
938852AE1-113 E
80/20
18.55518.555
938862AE1-114 E
80/20
8.7168.716
270681BRIGHTSTK; R
80/20
0.4980.498
274887PILOT HIL;1U
80/20
0.9460.946
275149KELLYCK ;1E
80/20
3.7863.786
293771O-035 E
80/20
1.3921.392
924048AB2-047 E1
80/20
2.0672.067
937001AD2-134 C
80/20
0.8290.829
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
934721AD1-100 C
80/20
3.8223.822
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
959611AF2-252 C
80/20
1.4511.451
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
990901L-005 E
80/20
2.5642.564
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
925771AC1-053 C
80/20
0.590.59
962012AG1-044 E
80/20
0.0450.045
274864CAYUGA RI;2U
80/20
0.5160.516
276655AB2-047 C1
80/20
0.3110.311
294392P-010 E
80/20
4.0594.059
294410BSHIL;2U E
80/20
1.7331.733
918052AA1-018 E OP
80/20
3.6223.622
926822AC1-168 E
80/20
4.9814.981
927209AC1-214 E2
80/20
0.660.66
965791AG1-447 C
80/20
46.67646.676
274687WILL CNTY;4U
80/20
32.59232.592
276656AB2-047 C2
80/20
0.3110.311
294401BSHIL;1U E
80/20
1.7331.733
925772AC1-053 E
80/20
3.953.95
926821AC1-168 C
80/20
0.7420.742
927208AC1-214 E1
80/20
0.660.66
959612AF2-252 E
80/20
2.1762.176
274848CAMPGROVE;RU
80/20
0.2780.278
274850MENDOTA H;RU
80/20
0.3520.352
274856ECOGROVE ;U1
80/20
0.4620.462
274858BIG SKY ;U2
80/20
0.3530.353
274871GR RIDGE ;2U
80/20
0.2720.272
274877BISHOP HL;1U
80/20
0.4330.433
276615W2-048 GEN
80/20
0.8910.891
293516O-009 E
80/20
3.8093.809
293644O22 E1
80/20
2.822.82
924266AB2-070 E
80/20
2.272.27
936372AD2-047 E
80/20
14.36514.365
939321AE1-163 C
80/20
4.1514.151
942111AE2-223 C
80/20
1.1951.195
942652AE2-281 E
80/20
3.6423.642
946321AF1-296 C
80/20
2.2942.294
966441AG1-513 C
80/20
0.4190.419
274676JOLIET 29;8U
80/20
36.23736.237
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
936371AD2-047 C
80/20
2.9422.942
938851AE1-113 C
80/20
5.2345.234
957372AF2-031 E
80/20
0.9540.954
965331AG1-398 C
80/20
0.1690.169
966442AG1-513 E
80/20
0.6290.629
274675JOLIET 29;7U
80/20
36.25136.251
274860EASYR;U2 E
80/20
2.4372.437
276156O-029 C
80/20
0.2490.249
290021O50 E
80/20
3.9653.965
961502AF2-441 E
80/20
10.40210.402
966091AG1-478 C
80/20
0.4310.431
274847GR RIDGE ;BU
80/20
0.730.73
274849CRESCENT ;1U
80/20
0.2120.212
274857BIG SKY ;U1
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274872LEE DEKAL;1U
80/20
0.9950.995
276621X2-022 GEN
80/20
2.5362.536
293061N-015 E
80/20
3.1963.196
293519PILOT HIL;1E
80/20
3.7863.786
924049AB2-047 E2
80/20
2.0992.099
934722AD1-100 E
80/20
59.4559.45
939322AE1-163 E
80/20
25.49625.496
946322AF1-296 E
80/20
10.73910.739
959351AF2-226 C
80/20
1.9641.964
966092AG1-478 E
80/20
0.6470.647
276627AG1-044 BAT
80/20
0.0090.009
935141AD1-148 C
80/20
0.7970.797
274891CAYUG;2U E
80/20
2.7522.752
276603SUBLETTE C
80/20
0.0780.078
276668AB2-070 C
80/20
0.3750.375
274878BISHOP HL;2U
80/20
0.4330.433
276626AG1-044 E
80/20
0.0510.051
917502Z2-087 E
80/20
3.3333.333
942112AE2-223 E
80/20
7.9997.999
274674JOLIET 9 ;6U
80/20
13.64413.644
274890CAYUG;1U E
80/20
2.7522.752
276602WESTBROOK C
80/20
0.1730.173
276675AE2-062 E
80/20
0.1120.112
942651AE2-281 C
80/20
0.5930.593
920272AA2-123 E
80/20
22
276170Z1-108 E
80/20
2.0422.042
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769
990052J1200
External Queue
0.35320.3532

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.87 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1057.12
MW Contribution:13.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
2.5552941176470592.172
957371AF2-031 C
Adder
0.63647058823529420.541
961501AF2-441 C
Adder
6.9341176470588245.894
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959352AF2-226 E
Adder
2.94588235294117642.504
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
270839OTTER CRK; R
50/50
0.5410.541
274888KELLY CRK;1U
50/50
0.9460.946
938852AE1-113 E
Adder
18.5576470588235315.774
938862AE1-114 E
Adder
8.717647058823537.41
274887PILOT HIL;1U
50/50
0.9460.946
275149KELLYCK ;1E
50/50
3.7853.785
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
934721AD1-100 C
50/50
3.8213.821
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
959611AF2-252 C
Adder
1.45058823529411771.233
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
962012AG1-044 E
Adder
0.044705882352941180.038
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
926822AC1-168 E
Adder
4.98117647058823554.234
965791AG1-447 C
50/50
46.67546.675
274687WILL CNTY;4U
50/50
32.59532.595
926821AC1-168 C
Adder
0.74235294117647070.631
959612AF2-252 E
Adder
2.17647058823529441.85
274676JOLIET 29;8U
50/50
36.23736.237
936371AD2-047 C
50/50
2.9422.942
938851AE1-113 C
Adder
5.2341176470588244.449
957372AF2-031 E
Adder
0.95411764705882360.811
274675JOLIET 29;7U
50/50
36.25136.251
961502AF2-441 E
Adder
10.48.84
966442AG1-513 E
50/50
0.6290.629
966091AG1-478 C
50/50
0.4310.431
276627AG1-044 BAT
Adder
0.0094117647058823540.008
274871GR RIDGE ;2U
50/50
0.2720.272
276626AG1-044 E
Adder
0.050588235294117640.043
942112AE2-223 E
Adder
7.9988235294117666.799
274847GR RIDGE ;BU
50/50
0.730.73
293061N-015 E
50/50
3.1963.196
293519PILOT HIL;1E
50/50
3.7853.785
934722AD1-100 E
50/50
59.44459.444
939322AE1-163 E
50/50
25.49625.496
946322AF1-296 E
Adder
10.749.129
959351AF2-226 C
Adder
1.9635294117647061.669
966092AG1-478 E
50/50
0.6470.647
936372AD2-047 E
50/50
14.36514.365
939321AE1-163 C
50/50
4.1514.151
942111AE2-223 C
Adder
1.19529411764705881.016
942652AE2-281 E
50/50
3.6423.642
946321AF1-296 C
Adder
2.29411764705882341.95
966441AG1-513 C
50/50
0.420.42
274674JOLIET 9 ;6U
50/50
13.64513.645
276675AE2-062 E
50/50
0.1120.112
942651AE2-281 C
50/50
0.5930.593
920272AA2-123 E
Adder
2.35294117647058832
276170Z1-108 E
50/50
2.0432.043
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769
990947J1432 G
External Queue
12.502512.5025
990052J1200
External Queue
0.35320.3532

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.87 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1057.11
MW Contribution:13.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
2.5552941176470592.172
957371AF2-031 C
Adder
0.63647058823529420.541
961501AF2-441 C
Adder
6.9341176470588245.894
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959352AF2-226 E
Adder
2.94588235294117642.504
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
270839OTTER CRK; R
50/50
0.5410.541
274888KELLY CRK;1U
50/50
0.9460.946
938852AE1-113 E
Adder
18.5576470588235315.774
938862AE1-114 E
Adder
8.717647058823537.41
274887PILOT HIL;1U
50/50
0.9460.946
275149KELLYCK ;1E
50/50
3.7853.785
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
934721AD1-100 C
50/50
3.8213.821
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
959611AF2-252 C
Adder
1.45058823529411771.233
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
962012AG1-044 E
Adder
0.044705882352941180.038
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
926822AC1-168 E
Adder
4.98117647058823554.234
965791AG1-447 C
50/50
46.67546.675
274687WILL CNTY;4U
50/50
32.59532.595
926821AC1-168 C
Adder
0.74235294117647070.631
959612AF2-252 E
Adder
2.17647058823529441.85
274676JOLIET 29;8U
50/50
36.23736.237
936371AD2-047 C
50/50
2.9422.942
938851AE1-113 C
Adder
5.2341176470588244.449
957372AF2-031 E
Adder
0.95411764705882360.811
274675JOLIET 29;7U
50/50
36.25136.251
961502AF2-441 E
Adder
10.48.84
966442AG1-513 E
50/50
0.6290.629
966091AG1-478 C
50/50
0.4310.431
276627AG1-044 BAT
Adder
0.0094117647058823540.008
274871GR RIDGE ;2U
50/50
0.2720.272
276626AG1-044 E
Adder
0.050588235294117640.043
942112AE2-223 E
Adder
7.9988235294117666.799
274847GR RIDGE ;BU
50/50
0.730.73
293061N-015 E
50/50
3.1963.196
293519PILOT HIL;1E
50/50
3.7853.785
934722AD1-100 E
50/50
59.44459.444
939322AE1-163 E
50/50
25.49625.496
946322AF1-296 E
Adder
10.749.129
959351AF2-226 C
Adder
1.9635294117647061.669
966092AG1-478 E
50/50
0.6470.647
936372AD2-047 E
50/50
14.36514.365
939321AE1-163 C
50/50
4.1514.151
942111AE2-223 C
Adder
1.19529411764705881.016
942652AE2-281 E
50/50
3.6423.642
946321AF1-296 C
Adder
2.29411764705882341.95
966441AG1-513 C
50/50
0.420.42
274674JOLIET 9 ;6U
50/50
13.64513.645
276675AE2-062 E
50/50
0.1120.112
942651AE2-281 C
50/50
0.5930.593
920272AA2-123 E
Adder
2.35294117647058832
276170Z1-108 E
50/50
2.0432.043
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769
990947J1432 G
External Queue
12.502512.5025
990052J1200
External Queue
0.35320.3532

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.73 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1619.01
MW Contribution:15.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
4.4614.461
290051GSG-6; E
80/20
2.5672.567
290108LEEDK;1U E
80/20
5.8935.893
290261S-027 E
80/20
3.5093.509
290265S-028 E
80/20
3.4883.488
295111SUBLETTE E
80/20
0.6680.668
925581AC1-033 C
80/20
0.5470.547
925582AC1-033 E
80/20
3.6613.661
938861AE1-114 C
80/20
3.0753.075
957371AF2-031 C
80/20
0.470.47
960261AF2-317 C
80/20
0.4080.408
961501AF2-441 C
80/20
6.2416.241
274851PROVIDENC;RU
80/20
0.270.27
274853TWINGROVE;U1
80/20
0.7480.748
274854TWINGROVE;U2
80/20
0.770.77
274855GSG-6 ;RU
80/20
0.6420.642
274879MINONK ;1U
80/20
1.2161.216
274880RADFORD R;1U
80/20
0.7810.781
274881WALNUT RG;1U
80/20
1.1461.146
293645O22 E2
80/20
4.6944.694
293715O-029 E
80/20
2.3712.371
293717O-029 E
80/20
1.1951.195
916212CRESCENT ;1U
80/20
1.1741.174
916221Z1-073 E
80/20
1.8091.809
957331AF2-027 C
80/20
2.4722.472
957332AF2-027 E
80/20
3.7083.708
959352AF2-226 E
80/20
4.284.28
960281AF2-319 C
80/20
2.8532.853
960282AF2-319 E
80/20
4.284.28
270839OTTER CRK; R
80/20
0.5660.566
274888KELLY CRK;1U
80/20
0.9910.991
293716O-029 E
80/20
1.31.3
937002AD2-134 E
80/20
3.9763.976
938852AE1-113 E
80/20
22.75422.754
938862AE1-114 E
80/20
10.49110.491
270681BRIGHTSTK; R
80/20
0.5910.591
274887PILOT HIL;1U
80/20
0.9910.991
275149KELLYCK ;1E
80/20
3.9663.966
293771O-035 E
80/20
1.6711.671
924048AB2-047 E1
80/20
2.4512.451
937001AD2-134 C
80/20
0.9950.995
274682WAUKEGAN ;7U
80/20
18.42518.425
274683WAUKEGAN ;8U
80/20
19.85719.857
274861TOP CROP ;1U
80/20
0.6560.656
274862TOP CROP ;2U
80/20
1.2521.252
274863CAYUGA RI;1U
80/20
0.6120.612
276157O-029 C
80/20
0.5410.541
276158O-029 C
80/20
0.5410.541
934721AD1-100 C
80/20
4.5344.534
942421AE2-255 C
80/20
2.4312.431
942422AE2-255 E
80/20
7.2937.293
959611AF2-252 C
80/20
1.721.72
960611AF2-352 C
80/20
1.721.72
960612AF2-352 E
80/20
2.582.58
990901L-005 E
80/20
3.0863.086
276645AC1-214 C1
80/20
0.2230.223
276646AC1-214 C2
80/20
0.2230.223
925771AC1-053 C
80/20
0.70.7
962012AG1-044 E
80/20
0.0540.054
274864CAYUGA RI;2U
80/20
0.6120.612
276655AB2-047 C1
80/20
0.3690.369
294392P-010 E
80/20
4.9014.901
294410BSHIL;2U E
80/20
2.0852.085
918052AA1-018 E OP
80/20
3.793.79
926822AC1-168 E
80/20
5.9825.982
927209AC1-214 E2
80/20
0.7920.792
274687WILL CNTY;4U
80/20
41.59241.592
276656AB2-047 C2
80/20
0.3690.369
294401BSHIL;1U E
80/20
2.0852.085
925772AC1-053 E
80/20
4.6814.681
926821AC1-168 C
80/20
0.8910.891
927208AC1-214 E1
80/20
0.7920.792
959612AF2-252 E
80/20
2.582.58
274848CAMPGROVE;RU
80/20
0.3340.334
274850MENDOTA H;RU
80/20
0.4220.422
274856ECOGROVE ;U1
80/20
0.5550.555
274858BIG SKY ;U2
80/20
0.4250.425
274676JOLIET 29;8U
80/20
44.06544.065
294763P-046 E
80/20
2.3082.308
295109WESTBROOK E
80/20
1.3751.375
936371AD2-047 C
80/20
3.0823.082
938851AE1-113 C
80/20
6.4186.418
957372AF2-031 E
80/20
0.7050.705
965331AG1-398 C
80/20
0.2010.201
966442AG1-513 E
80/20
0.7520.752
274871GR RIDGE ;2U
80/20
0.3280.328
274877BISHOP HL;1U
80/20
0.5210.521
276615W2-048 GEN
80/20
1.0561.056
293516O-009 E
80/20
4.5854.585
293644O22 E1
80/20
4.0984.098
924266AB2-070 E
80/20
2.692.69
936372AD2-047 E
80/20
15.04615.046
274675JOLIET 29;7U
80/20
44.03844.038
274860EASYR;U2 E
80/20
2.9342.934
276156O-029 C
80/20
0.30.3
290021O50 E
80/20
4.8624.862
961502AF2-441 E
80/20
9.3619.361
966091AG1-478 C
80/20
0.4850.485
274847GR RIDGE ;BU
80/20
0.8810.881
274849CRESCENT ;1U
80/20
0.2550.255
274857BIG SKY ;U1
80/20
0.4250.425
274859EASYR;U1 E
80/20
2.9342.934
276627AG1-044 BAT
80/20
0.0110.011
935141AD1-148 C
80/20
0.9450.945
957382AF2-032 E
80/20
0.1170.117
274891CAYUG;2U E
80/20
3.2643.264
276603SUBLETTE C
80/20
0.0940.094
276668AB2-070 C
80/20
0.4440.444
939321AE1-163 C
80/20
4.5314.531
942111AE2-223 C
80/20
1.4181.418
942652AE2-281 E
80/20
3.9763.976
946321AF1-296 C
80/20
2.7622.762
966441AG1-513 C
80/20
0.5010.501
274872LEE DEKAL;1U
80/20
1.1941.194
276621X2-022 GEN
80/20
3.0063.006
293061N-015 E
80/20
3.8593.859
293519PILOT HIL;1E
80/20
3.9663.966
924049AB2-047 E2
80/20
2.492.49
934722AD1-100 E
80/20
70.52170.521
939322AE1-163 E
80/20
27.83427.834
946322AF1-296 E
80/20
12.93112.931
274878BISHOP HL;2U
80/20
0.5210.521
276626AG1-044 E
80/20
0.0610.061
917502Z2-087 E
80/20
3.9533.953
942112AE2-223 E
80/20
9.4879.487
959351AF2-226 C
80/20
2.8532.853
966092AG1-478 E
80/20
0.7280.728
274674JOLIET 9 ;6U
80/20
15.24915.249
274890CAYUG;1U E
80/20
3.2643.264
276602WESTBROOK C
80/20
0.2080.208
276675AE2-062 E
80/20
0.1250.125
942651AE2-281 C
80/20
0.6470.647
965913AG1-460 BT
80/20
0.0060.006
920272AA2-123 E
80/20
2.4072.407
276170Z1-108 E
80/20
2.4582.458
990512J1326 G
External Queue
5.43125.4312
991302J1755
External Queue
9.86249.8624
990947J1432 G
External Queue
15.3415.34
991092J1477
External Queue
2.88432.8843
990052J1200
External Queue
0.43040.4304

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.64 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1617.84
MW Contribution:15.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
4.4614.461
290051GSG-6; E
80/20
2.5672.567
290108LEEDK;1U E
80/20
5.8935.893
290261S-027 E
80/20
3.5093.509
290265S-028 E
80/20
3.4883.488
295111SUBLETTE E
80/20
0.6680.668
925581AC1-033 C
80/20
0.5470.547
925582AC1-033 E
80/20
3.6613.661
938861AE1-114 C
80/20
3.0753.075
957371AF2-031 C
80/20
0.470.47
960261AF2-317 C
80/20
0.4080.408
961501AF2-441 C
80/20
6.2416.241
274851PROVIDENC;RU
80/20
0.270.27
274853TWINGROVE;U1
80/20
0.7480.748
274854TWINGROVE;U2
80/20
0.770.77
274855GSG-6 ;RU
80/20
0.6420.642
274879MINONK ;1U
80/20
1.2161.216
274880RADFORD R;1U
80/20
0.7810.781
274881WALNUT RG;1U
80/20
1.1461.146
293645O22 E2
80/20
4.6944.694
293715O-029 E
80/20
2.3712.371
293717O-029 E
80/20
1.1951.195
916212CRESCENT ;1U
80/20
1.1741.174
916221Z1-073 E
80/20
1.8091.809
957331AF2-027 C
80/20
2.4722.472
957332AF2-027 E
80/20
3.7083.708
959352AF2-226 E
80/20
4.284.28
960281AF2-319 C
80/20
2.8532.853
960282AF2-319 E
80/20
4.284.28
270839OTTER CRK; R
80/20
0.5660.566
274888KELLY CRK;1U
80/20
0.9910.991
293716O-029 E
80/20
1.31.3
937002AD2-134 E
80/20
3.9763.976
938852AE1-113 E
80/20
22.75422.754
938862AE1-114 E
80/20
10.49110.491
270681BRIGHTSTK; R
80/20
0.5910.591
274887PILOT HIL;1U
80/20
0.9910.991
275149KELLYCK ;1E
80/20
3.9663.966
293771O-035 E
80/20
1.6711.671
924048AB2-047 E1
80/20
2.4512.451
937001AD2-134 C
80/20
0.9950.995
274682WAUKEGAN ;7U
80/20
18.42518.425
274683WAUKEGAN ;8U
80/20
19.85719.857
274861TOP CROP ;1U
80/20
0.6560.656
274862TOP CROP ;2U
80/20
1.2521.252
274863CAYUGA RI;1U
80/20
0.6120.612
276157O-029 C
80/20
0.5410.541
276158O-029 C
80/20
0.5410.541
934721AD1-100 C
80/20
4.5344.534
942421AE2-255 C
80/20
2.4312.431
942422AE2-255 E
80/20
7.2937.293
959611AF2-252 C
80/20
1.721.72
960611AF2-352 C
80/20
1.721.72
960612AF2-352 E
80/20
2.582.58
990901L-005 E
80/20
3.0863.086
276645AC1-214 C1
80/20
0.2230.223
276646AC1-214 C2
80/20
0.2230.223
925771AC1-053 C
80/20
0.70.7
962012AG1-044 E
80/20
0.0540.054
274864CAYUGA RI;2U
80/20
0.6120.612
276655AB2-047 C1
80/20
0.3690.369
294392P-010 E
80/20
4.9014.901
294410BSHIL;2U E
80/20
2.0852.085
918052AA1-018 E OP
80/20
3.793.79
926822AC1-168 E
80/20
5.9825.982
927209AC1-214 E2
80/20
0.7920.792
274687WILL CNTY;4U
80/20
41.59241.592
276656AB2-047 C2
80/20
0.3690.369
294401BSHIL;1U E
80/20
2.0852.085
925772AC1-053 E
80/20
4.6814.681
926821AC1-168 C
80/20
0.8910.891
927208AC1-214 E1
80/20
0.7920.792
959612AF2-252 E
80/20
2.582.58
274848CAMPGROVE;RU
80/20
0.3340.334
274850MENDOTA H;RU
80/20
0.4220.422
274856ECOGROVE ;U1
80/20
0.5550.555
274858BIG SKY ;U2
80/20
0.4250.425
274676JOLIET 29;8U
80/20
44.06544.065
294763P-046 E
80/20
2.3082.308
295109WESTBROOK E
80/20
1.3751.375
936371AD2-047 C
80/20
3.0823.082
938851AE1-113 C
80/20
6.4186.418
957372AF2-031 E
80/20
0.7050.705
965331AG1-398 C
80/20
0.2010.201
966442AG1-513 E
80/20
0.7520.752
274871GR RIDGE ;2U
80/20
0.3280.328
274877BISHOP HL;1U
80/20
0.5210.521
276615W2-048 GEN
80/20
1.0561.056
293516O-009 E
80/20
4.5854.585
293644O22 E1
80/20
4.0984.098
924266AB2-070 E
80/20
2.692.69
274675JOLIET 29;7U
80/20
44.03844.038
274860EASYR;U2 E
80/20
2.9342.934
276156O-029 C
80/20
0.30.3
290021O50 E
80/20
4.8624.862
961502AF2-441 E
80/20
9.3619.361
966091AG1-478 C
80/20
0.4850.485
274847GR RIDGE ;BU
80/20
0.8810.881
274849CRESCENT ;1U
80/20
0.2550.255
274857BIG SKY ;U1
80/20
0.4250.425
274859EASYR;U1 E
80/20
2.9342.934
276627AG1-044 BAT
80/20
0.0110.011
935141AD1-148 C
80/20
0.9450.945
957382AF2-032 E
80/20
0.1170.117
274891CAYUG;2U E
80/20
3.2643.264
276603SUBLETTE C
80/20
0.0940.094
276668AB2-070 C
80/20
0.4440.444
936372AD2-047 E
80/20
15.04615.046
939321AE1-163 C
80/20
4.5314.531
942111AE2-223 C
80/20
1.4181.418
942652AE2-281 E
80/20
3.9763.976
946321AF1-296 C
80/20
2.7622.762
966441AG1-513 C
80/20
0.5010.501
274872LEE DEKAL;1U
80/20
1.1941.194
276621X2-022 GEN
80/20
3.0063.006
293061N-015 E
80/20
3.8593.859
293519PILOT HIL;1E
80/20
3.9663.966
924049AB2-047 E2
80/20
2.492.49
934722AD1-100 E
80/20
70.52170.521
939322AE1-163 E
80/20
27.83427.834
946322AF1-296 E
80/20
12.93112.931
274878BISHOP HL;2U
80/20
0.5210.521
276626AG1-044 E
80/20
0.0610.061
917502Z2-087 E
80/20
3.9533.953
942112AE2-223 E
80/20
9.4879.487
959351AF2-226 C
80/20
2.8532.853
966092AG1-478 E
80/20
0.7280.728
274674JOLIET 9 ;6U
80/20
15.24915.249
274890CAYUG;1U E
80/20
3.2643.264
276602WESTBROOK C
80/20
0.2080.208
276675AE2-062 E
80/20
0.1250.125
942651AE2-281 C
80/20
0.6470.647
965913AG1-460 BT
80/20
0.0060.006
920272AA2-123 E
80/20
2.4072.407
276170Z1-108 E
80/20
2.4582.458
990512J1326 G
External Queue
5.43125.4312
991302J1755
External Queue
9.86249.8624
990947J1432 G
External Queue
15.3415.34
991092J1477
External Queue
2.88432.8843
990052J1200
External Queue
0.43040.4304

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.82 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1452.46
MW Contribution:15.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
3.06235294117647072.603
957371AF2-031 C
Adder
0.462352941176470630.393
961501AF2-441 C
Adder
6.16352941176470555.239
274879MINONK ;1U
50/50
1.211.21
293645O22 E2
50/50
4.6734.673
957331AF2-027 C
50/50
2.462.46
957332AF2-027 E
50/50
3.693.69
959352AF2-226 E
50/50
4.2614.261
960281AF2-319 C
50/50
2.8412.841
960282AF2-319 E
50/50
4.2614.261
938852AE1-113 E
50/50
22.65322.653
938862AE1-114 E
Adder
10.4482352941176488.881
944221AF1-090 C
Adder
1.41647058823529411.204
274682WAUKEGAN ;7U
50/50
18.33318.333
274683WAUKEGAN ;8U
50/50
19.75819.758
274861TOP CROP ;1U
50/50
0.6530.653
274862TOP CROP ;2U
50/50
1.2461.246
934721AD1-100 C
50/50
4.5094.509
942421AE2-255 C
50/50
2.422.42
942422AE2-255 E
50/50
7.2617.261
959611AF2-252 C
Adder
1.721.462
960611AF2-352 C
Adder
1.721.462
960612AF2-352 E
Adder
2.582.193
962012AG1-044 E
Adder
0.054117647058823530.046
294392P-010 E
50/50
4.8764.876
926822AC1-168 E
Adder
5.9611764705882365.067
274687WILL CNTY;4U
50/50
41.36241.362
926821AC1-168 C
Adder
0.88823529411764710.755
959612AF2-252 E
Adder
2.582.193
274676JOLIET 29;8U
50/50
43.82443.824
936371AD2-047 C
Adder
3.0611764705882352.602
938851AE1-113 C
50/50
6.3896.389
274675JOLIET 29;7U
50/50
43.79843.798
290021O50 E
50/50
4.844.84
961502AF2-441 E
Adder
9.2458823529411777.859
957372AF2-031 E
Adder
0.69294117647058820.589
966442AG1-513 E
50/50
0.7480.748
966091AG1-478 C
50/50
0.4820.482
276627AG1-044 BAT
Adder
0.0105882352941176470.009
957382AF2-032 E
Adder
0.117647058823529420.1
274871GR RIDGE ;2U
50/50
0.3260.326
276626AG1-044 E
Adder
0.061176470588235290.052
942112AE2-223 E
Adder
9.4776470588235288.056
274847GR RIDGE ;BU
50/50
0.8770.877
293061N-015 E
50/50
3.8393.839
934722AD1-100 E
50/50
70.13470.134
939322AE1-163 E
Adder
27.69647058823529723.542
944222AF1-090 E
Adder
6.6294117647058825.635
946322AF1-296 E
Adder
12.8905882352941210.957
959351AF2-226 C
50/50
2.8412.841
966092AG1-478 E
50/50
0.7240.724
293644O22 E1
50/50
4.084.08
936372AD2-047 E
Adder
14.94235294117647212.701
939321AE1-163 C
Adder
4.5094117647058833.833
942111AE2-223 C
Adder
1.41647058823529411.204
942652AE2-281 E
Adder
3.9564705882352943.363
946321AF1-296 C
Adder
2.7541176470588242.341
966441AG1-513 C
50/50
0.4990.499
274674JOLIET 9 ;6U
Adder
15.1576470588235312.884
276675AE2-062 E
50/50
0.1240.124
942651AE2-281 C
Adder
0.64352941176470590.547
965913AG1-460 BT
Adder
0.00588235294117647050.005
920272AA2-123 E
Adder
2.81764705882352962.395
276170Z1-108 E
50/50
2.4462.446
990512J1326 G
External Queue
5.40125.4012
991302J1755
External Queue
9.81979.8197
990947J1432 G
External Queue
15.277515.2775
991092J1477
External Queue
2.87522.8752
990052J1200
External Queue
0.42840.4284

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.92 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1439.81
MW Contribution:15.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
3.07647058823529432.615
957371AF2-031 C
Adder
0.46941176470588240.399
961501AF2-441 C
Adder
6.2364705882352955.301
274879MINONK ;1U
50/50
1.2161.216
293645O22 E2
50/50
4.6944.694
957331AF2-027 C
50/50
2.4742.474
957332AF2-027 E
50/50
3.713.71
959352AF2-226 E
50/50
4.284.28
960281AF2-319 C
50/50
2.8532.853
960282AF2-319 E
50/50
4.284.28
938852AE1-113 E
50/50
22.76222.762
938862AE1-114 E
Adder
10.497647058823538.923
274682WAUKEGAN ;7U
50/50
18.43518.435
274683WAUKEGAN ;8U
50/50
19.86819.868
274861TOP CROP ;1U
50/50
0.6560.656
274862TOP CROP ;2U
50/50
1.2521.252
934721AD1-100 C
50/50
4.5314.531
942421AE2-255 C
50/50
2.4322.432
942422AE2-255 E
50/50
7.2957.295
959611AF2-252 C
Adder
1.721.462
960611AF2-352 C
Adder
1.721.462
960612AF2-352 E
Adder
2.582.193
962012AG1-044 E
Adder
0.054117647058823530.046
294392P-010 E
50/50
4.9034.903
926822AC1-168 E
Adder
5.9847058823529415.087
274687WILL CNTY;4U
50/50
41.59841.598
926821AC1-168 C
Adder
0.8917647058823530.758
959612AF2-252 E
Adder
2.582.193
274676JOLIET 29;8U
50/50
44.07844.078
936371AD2-047 C
Adder
3.08117647058823562.619
938851AE1-113 C
50/50
6.426.42
274675JOLIET 29;7U
50/50
44.05244.052
290021O50 E
50/50
4.8644.864
961502AF2-441 E
Adder
9.3552941176470597.952
957372AF2-031 E
Adder
0.70470588235294120.599
966442AG1-513 E
50/50
0.7530.753
966091AG1-478 C
50/50
0.4850.485
276627AG1-044 BAT
Adder
0.0105882352941176470.009
957382AF2-032 E
Adder
0.117647058823529420.1
276626AG1-044 E
Adder
0.061176470588235290.052
942112AE2-223 E
Adder
9.4870588235294138.064
274847GR RIDGE ;BU
50/50
0.8810.881
293061N-015 E
50/50
3.863.86
934722AD1-100 E
50/50
70.47670.476
939322AE1-163 E
Adder
27.83882352941176623.663
946322AF1-296 E
Adder
12.93882352941176410.998
959351AF2-226 C
50/50
2.8532.853
966092AG1-478 E
50/50
0.7280.728
274871GR RIDGE ;2U
50/50
0.3280.328
293644O22 E1
50/50
4.0984.098
936372AD2-047 E
Adder
15.04117647058823512.785
939321AE1-163 C
Adder
4.53176470588235253.852
942111AE2-223 C
Adder
1.41764705882352951.205
942652AE2-281 E
Adder
3.9764705882352943.38
946321AF1-296 C
Adder
2.7635294117647062.349
966441AG1-513 C
50/50
0.5020.502
274674JOLIET 9 ;6U
Adder
15.25411764705882312.966
276675AE2-062 E
50/50
0.1250.125
942651AE2-281 C
Adder
0.64705882352941180.55
276170Z1-108 E
50/50
2.462.46
965913AG1-460 BT
Adder
0.00588235294117647050.005
920272AA2-123 E
Adder
2.83294117647058832.408
990512J1326 G
External Queue
5.4355.435
991302J1755
External Queue
9.86539.8653
990947J1432 G
External Queue
15.3515.35
991092J1477
External Queue
2.88632.8863
990052J1200
External Queue
0.43050.4305

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.53 %
Rating:1091.0 MVA
Rating Type:A
MVA to Mitigate:1096.79
MW Contribution:10.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
290051GSG-6; E
80/20
1.6851.685
290108LEEDK;1U E
80/20
3.8583.858
290261S-027 E
80/20
2.2852.285
290265S-028 E
80/20
2.2712.271
295111SUBLETTE E
80/20
0.4390.439
925581AC1-033 C
80/20
0.3660.366
925582AC1-033 E
80/20
2.4492.449
938861AE1-114 C
80/20
2.0372.037
274851PROVIDENC;RU
80/20
0.1810.181
274853TWINGROVE;U1
80/20
0.4870.487
274854TWINGROVE;U2
80/20
0.5010.501
274855GSG-6 ;RU
80/20
0.4210.421
274879MINONK ;1U
80/20
0.8370.837
274881WALNUT RG;1U
80/20
0.7610.761
293645O22 E2
80/20
3.4613.461
293715O-029 E
80/20
1.5751.575
293717O-029 E
80/20
0.7940.794
916212CRESCENT ;1U
80/20
0.7850.785
916221Z1-073 E
80/20
1.1881.188
957331AF2-027 C
80/20
1.6591.659
957332AF2-027 E
80/20
2.4882.488
959352AF2-226 E
80/20
3.1563.156
960281AF2-319 C
80/20
2.1042.104
960282AF2-319 E
80/20
3.1563.156
270839OTTER CRK; R
80/20
0.3830.383
274888KELLY CRK;1U
80/20
0.6450.645
293716O-029 E
80/20
0.8630.863
937002AD2-134 E
80/20
2.612.61
938852AE1-113 E
80/20
15.67215.672
938862AE1-114 E
80/20
6.9496.949
270681BRIGHTSTK; R
80/20
0.3850.385
274887PILOT HIL;1U
80/20
0.6450.645
275149KELLYCK ;1E
80/20
2.5792.579
293771O-035 E
80/20
1.1181.118
924048AB2-047 E1
80/20
1.5971.597
937001AD2-134 C
80/20
0.6530.653
274682WAUKEGAN ;7U
80/20
12.37312.373
274683WAUKEGAN ;8U
80/20
13.33213.332
274861TOP CROP ;1U
80/20
0.4840.484
274862TOP CROP ;2U
80/20
0.9230.923
274863CAYUGA RI;1U
80/20
0.4010.401
276157O-029 C
80/20
0.3590.359
276158O-029 C
80/20
0.3590.359
934721AD1-100 C
80/20
2.9882.988
942421AE2-255 C
80/20
1.6741.674
942422AE2-255 E
80/20
5.0235.023
959611AF2-252 C
80/20
1.121.12
960611AF2-352 C
80/20
1.121.12
960612AF2-352 E
80/20
1.681.68
990901L-005 E
80/20
2.0672.067
276645AC1-214 C1
80/20
0.1490.149
276646AC1-214 C2
80/20
0.1490.149
962012AG1-044 E
80/20
0.0360.036
274864CAYUGA RI;2U
80/20
0.4010.401
276655AB2-047 C1
80/20
0.240.24
294392P-010 E
80/20
3.2533.253
294410BSHIL;2U E
80/20
1.3951.395
918052AA1-018 E OP
80/20
2.5632.563
926822AC1-168 E
80/20
44
927209AC1-214 E2
80/20
0.530.53
274687WILL CNTY;4U
80/20
29.39129.391
276656AB2-047 C2
80/20
0.240.24
294401BSHIL;1U E
80/20
1.3951.395
926821AC1-168 C
80/20
0.5960.596
927208AC1-214 E1
80/20
0.530.53
959612AF2-252 E
80/20
1.681.68
274848CAMPGROVE;RU
80/20
0.2240.224
274850MENDOTA H;RU
80/20
0.2770.277
274856ECOGROVE ;U1
80/20
0.3680.368
274858BIG SKY ;U2
80/20
0.2820.282
274676JOLIET 29;8U
80/20
30.59430.594
294763P-046 E
80/20
1.5291.529
295109WESTBROOK E
80/20
0.9020.902
936371AD2-047 C
80/20
2.0042.004
938851AE1-113 C
80/20
4.424.42
966442AG1-513 E
80/20
0.4920.492
274871GR RIDGE ;2U
80/20
0.2180.218
274877BISHOP HL;1U
80/20
0.3490.349
293516O-009 E
80/20
3.0453.045
293644O22 E1
80/20
3.0223.022
274675JOLIET 29;7U
80/20
30.56830.568
274860EASYR;U2 E
80/20
1.9441.944
276156O-029 C
80/20
0.1990.199
290021O50 E
80/20
3.3493.349
966091AG1-478 C
80/20
0.3250.325
274847GR RIDGE ;BU
80/20
0.5850.585
274849CRESCENT ;1U
80/20
0.170.17
274857BIG SKY ;U1
80/20
0.2820.282
274859EASYR;U1 E
80/20
1.9441.944
276627AG1-044 BAT
80/20
0.0070.007
274891CAYUG;2U E
80/20
2.1372.137
276603SUBLETTE C
80/20
0.0620.062
936372AD2-047 E
80/20
9.7859.785
939321AE1-163 C
80/20
3.083.08
942111AE2-223 C
80/20
0.9230.923
942652AE2-281 E
80/20
2.7032.703
946321AF1-296 C
80/20
1.8341.834
966441AG1-513 C
80/20
0.3280.328
274872LEE DEKAL;1U
80/20
0.7810.781
293061N-015 E
80/20
2.5612.561
293519PILOT HIL;1E
80/20
2.5792.579
924049AB2-047 E2
80/20
1.6221.622
934722AD1-100 E
80/20
46.47446.474
939322AE1-163 E
80/20
18.9218.92
946322AF1-296 E
80/20
8.5868.586
274878BISHOP HL;2U
80/20
0.3490.349
276626AG1-044 E
80/20
0.0410.041
917502Z2-087 E
80/20
2.5752.575
942112AE2-223 E
80/20
6.1816.181
959351AF2-226 C
80/20
2.1042.104
966092AG1-478 E
80/20
0.4880.488
274674JOLIET 9 ;6U
80/20
10.08310.083
274890CAYUG;1U E
80/20
2.1372.137
276602WESTBROOK C
80/20
0.1370.137
276675AE2-062 E
80/20
0.0850.085
942651AE2-281 C
80/20
0.440.44
276170Z1-108 E
80/20
1.6321.632
920272AA2-123 E
80/20
1.5961.596

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.75 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1619.4
MW Contribution:15.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
4.4614.461
290051GSG-6; E
80/20
2.5672.567
290108LEEDK;1U E
80/20
5.8935.893
290261S-027 E
80/20
3.5093.509
290265S-028 E
80/20
3.4883.488
295111SUBLETTE E
80/20
0.6680.668
925581AC1-033 C
80/20
0.5470.547
925582AC1-033 E
80/20
3.6613.661
938861AE1-114 C
80/20
3.0753.075
957371AF2-031 C
80/20
0.470.47
960261AF2-317 C
80/20
0.4080.408
961501AF2-441 C
80/20
6.2416.241
274851PROVIDENC;RU
80/20
0.270.27
274853TWINGROVE;U1
80/20
0.7480.748
274854TWINGROVE;U2
80/20
0.770.77
274855GSG-6 ;RU
80/20
0.6420.642
274879MINONK ;1U
80/20
1.2161.216
274880RADFORD R;1U
80/20
0.7810.781
274881WALNUT RG;1U
80/20
1.1461.146
293645O22 E2
80/20
4.6944.694
293715O-029 E
80/20
2.3712.371
293717O-029 E
80/20
1.1951.195
916212CRESCENT ;1U
80/20
1.1741.174
916221Z1-073 E
80/20
1.8091.809
957331AF2-027 C
80/20
2.4722.472
957332AF2-027 E
80/20
3.7083.708
959352AF2-226 E
80/20
4.284.28
960281AF2-319 C
80/20
2.8532.853
960282AF2-319 E
80/20
4.284.28
270839OTTER CRK; R
80/20
0.5660.566
274888KELLY CRK;1U
80/20
0.9910.991
293716O-029 E
80/20
1.31.3
937002AD2-134 E
80/20
3.9763.976
938852AE1-113 E
80/20
22.75422.754
938862AE1-114 E
80/20
10.49110.491
270681BRIGHTSTK; R
80/20
0.5910.591
274887PILOT HIL;1U
80/20
0.9910.991
275149KELLYCK ;1E
80/20
3.9663.966
293771O-035 E
80/20
1.6711.671
924048AB2-047 E1
80/20
2.4512.451
937001AD2-134 C
80/20
0.9950.995
274682WAUKEGAN ;7U
80/20
18.42518.425
274683WAUKEGAN ;8U
80/20
19.85719.857
274861TOP CROP ;1U
80/20
0.6560.656
274862TOP CROP ;2U
80/20
1.2521.252
274863CAYUGA RI;1U
80/20
0.6120.612
276157O-029 C
80/20
0.5410.541
276158O-029 C
80/20
0.5410.541
934721AD1-100 C
80/20
4.5344.534
942421AE2-255 C
80/20
2.4312.431
942422AE2-255 E
80/20
7.2937.293
959611AF2-252 C
80/20
1.721.72
960611AF2-352 C
80/20
1.721.72
960612AF2-352 E
80/20
2.582.58
990901L-005 E
80/20
3.0863.086
276645AC1-214 C1
80/20
0.2230.223
276646AC1-214 C2
80/20
0.2230.223
925771AC1-053 C
80/20
0.70.7
962012AG1-044 E
80/20
0.0540.054
274864CAYUGA RI;2U
80/20
0.6120.612
276655AB2-047 C1
80/20
0.3690.369
294392P-010 E
80/20
4.9014.901
294410BSHIL;2U E
80/20
2.0852.085
918052AA1-018 E OP
80/20
3.793.79
926822AC1-168 E
80/20
5.9825.982
927209AC1-214 E2
80/20
0.7920.792
274687WILL CNTY;4U
80/20
41.59241.592
276656AB2-047 C2
80/20
0.3690.369
294401BSHIL;1U E
80/20
2.0852.085
925772AC1-053 E
80/20
4.6814.681
926821AC1-168 C
80/20
0.8910.891
927208AC1-214 E1
80/20
0.7920.792
959612AF2-252 E
80/20
2.582.58
274848CAMPGROVE;RU
80/20
0.3340.334
274850MENDOTA H;RU
80/20
0.4220.422
274856ECOGROVE ;U1
80/20
0.5550.555
274858BIG SKY ;U2
80/20
0.4250.425
274871GR RIDGE ;2U
80/20
0.3280.328
274676JOLIET 29;8U
80/20
44.06544.065
294763P-046 E
80/20
2.3082.308
295109WESTBROOK E
80/20
1.3751.375
936371AD2-047 C
80/20
3.0823.082
938851AE1-113 C
80/20
6.4186.418
957372AF2-031 E
80/20
0.7050.705
965331AG1-398 C
80/20
0.2010.201
966442AG1-513 E
80/20
0.7520.752
274877BISHOP HL;1U
80/20
0.5210.521
276615W2-048 GEN
80/20
1.0561.056
293516O-009 E
80/20
4.5854.585
293644O22 E1
80/20
4.0984.098
924266AB2-070 E
80/20
2.692.69
936372AD2-047 E
80/20
15.04615.046
274675JOLIET 29;7U
80/20
44.03844.038
274860EASYR;U2 E
80/20
2.9342.934
276156O-029 C
80/20
0.30.3
290021O50 E
80/20
4.8624.862
961502AF2-441 E
80/20
9.3619.361
966091AG1-478 C
80/20
0.4850.485
274847GR RIDGE ;BU
80/20
0.8810.881
274849CRESCENT ;1U
80/20
0.2550.255
274857BIG SKY ;U1
80/20
0.4250.425
274859EASYR;U1 E
80/20
2.9342.934
276627AG1-044 BAT
80/20
0.0110.011
935141AD1-148 C
80/20
0.9450.945
957382AF2-032 E
80/20
0.1170.117
274891CAYUG;2U E
80/20
3.2643.264
276603SUBLETTE C
80/20
0.0940.094
276668AB2-070 C
80/20
0.4440.444
939321AE1-163 C
80/20
4.5314.531
942111AE2-223 C
80/20
1.4181.418
942652AE2-281 E
80/20
3.9763.976
946321AF1-296 C
80/20
2.7622.762
966441AG1-513 C
80/20
0.5010.501
274872LEE DEKAL;1U
80/20
1.1941.194
276621X2-022 GEN
80/20
3.0063.006
293061N-015 E
80/20
3.8593.859
293519PILOT HIL;1E
80/20
3.9663.966
924049AB2-047 E2
80/20
2.492.49
934722AD1-100 E
80/20
70.52170.521
939322AE1-163 E
80/20
27.83427.834
946322AF1-296 E
80/20
12.93112.931
274878BISHOP HL;2U
80/20
0.5210.521
276626AG1-044 E
80/20
0.0610.061
917502Z2-087 E
80/20
3.9533.953
942112AE2-223 E
80/20
9.4879.487
959351AF2-226 C
80/20
2.8532.853
966092AG1-478 E
80/20
0.7280.728
274674JOLIET 9 ;6U
80/20
15.24915.249
274890CAYUG;1U E
80/20
3.2643.264
276602WESTBROOK C
80/20
0.2080.208
276675AE2-062 E
80/20
0.1250.125
942651AE2-281 C
80/20
0.6470.647
965913AG1-460 BT
80/20
0.0060.006
920272AA2-123 E
80/20
2.4072.407
276170Z1-108 E
80/20
2.4582.458
990512J1326 G
External Queue
5.43125.4312
991302J1755
External Queue
9.86249.8624
990947J1432 G
External Queue
15.3415.34
991092J1477
External Queue
2.88432.8843
990052J1200
External Queue
0.43040.4304

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1618.22
MW Contribution:15.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
4.4614.461
290051GSG-6; E
80/20
2.5672.567
290108LEEDK;1U E
80/20
5.8935.893
290261S-027 E
80/20
3.5093.509
290265S-028 E
80/20
3.4883.488
295111SUBLETTE E
80/20
0.6680.668
925581AC1-033 C
80/20
0.5470.547
925582AC1-033 E
80/20
3.6613.661
938861AE1-114 C
80/20
3.0753.075
957371AF2-031 C
80/20
0.470.47
960261AF2-317 C
80/20
0.4080.408
961501AF2-441 C
80/20
6.2416.241
274851PROVIDENC;RU
80/20
0.270.27
274853TWINGROVE;U1
80/20
0.7480.748
274854TWINGROVE;U2
80/20
0.770.77
274855GSG-6 ;RU
80/20
0.6420.642
274879MINONK ;1U
80/20
1.2161.216
274880RADFORD R;1U
80/20
0.7810.781
274881WALNUT RG;1U
80/20
1.1461.146
293645O22 E2
80/20
4.6944.694
293715O-029 E
80/20
2.3712.371
293717O-029 E
80/20
1.1951.195
916212CRESCENT ;1U
80/20
1.1741.174
916221Z1-073 E
80/20
1.8091.809
957331AF2-027 C
80/20
2.4722.472
957332AF2-027 E
80/20
3.7083.708
959352AF2-226 E
80/20
4.284.28
960281AF2-319 C
80/20
2.8532.853
960282AF2-319 E
80/20
4.284.28
270839OTTER CRK; R
80/20
0.5660.566
274888KELLY CRK;1U
80/20
0.9910.991
293716O-029 E
80/20
1.31.3
937002AD2-134 E
80/20
3.9763.976
938852AE1-113 E
80/20
22.75422.754
938862AE1-114 E
80/20
10.49110.491
270681BRIGHTSTK; R
80/20
0.5910.591
274887PILOT HIL;1U
80/20
0.9910.991
275149KELLYCK ;1E
80/20
3.9663.966
293771O-035 E
80/20
1.6711.671
924048AB2-047 E1
80/20
2.4512.451
937001AD2-134 C
80/20
0.9950.995
274682WAUKEGAN ;7U
80/20
18.42518.425
274683WAUKEGAN ;8U
80/20
19.85719.857
274861TOP CROP ;1U
80/20
0.6560.656
274862TOP CROP ;2U
80/20
1.2521.252
274863CAYUGA RI;1U
80/20
0.6120.612
276157O-029 C
80/20
0.5410.541
276158O-029 C
80/20
0.5410.541
934721AD1-100 C
80/20
4.5344.534
942421AE2-255 C
80/20
2.4312.431
942422AE2-255 E
80/20
7.2937.293
959611AF2-252 C
80/20
1.721.72
960611AF2-352 C
80/20
1.721.72
960612AF2-352 E
80/20
2.582.58
990901L-005 E
80/20
3.0863.086
276645AC1-214 C1
80/20
0.2230.223
276646AC1-214 C2
80/20
0.2230.223
925771AC1-053 C
80/20
0.70.7
962012AG1-044 E
80/20
0.0540.054
274864CAYUGA RI;2U
80/20
0.6120.612
276655AB2-047 C1
80/20
0.3690.369
294392P-010 E
80/20
4.9014.901
294410BSHIL;2U E
80/20
2.0852.085
918052AA1-018 E OP
80/20
3.793.79
926822AC1-168 E
80/20
5.9825.982
927209AC1-214 E2
80/20
0.7920.792
274687WILL CNTY;4U
80/20
41.59241.592
276656AB2-047 C2
80/20
0.3690.369
294401BSHIL;1U E
80/20
2.0852.085
925772AC1-053 E
80/20
4.6814.681
926821AC1-168 C
80/20
0.8910.891
927208AC1-214 E1
80/20
0.7920.792
959612AF2-252 E
80/20
2.582.58
274848CAMPGROVE;RU
80/20
0.3340.334
274850MENDOTA H;RU
80/20
0.4220.422
274856ECOGROVE ;U1
80/20
0.5550.555
274858BIG SKY ;U2
80/20
0.4250.425
274871GR RIDGE ;2U
80/20
0.3280.328
274676JOLIET 29;8U
80/20
44.06544.065
294763P-046 E
80/20
2.3082.308
295109WESTBROOK E
80/20
1.3751.375
936371AD2-047 C
80/20
3.0823.082
938851AE1-113 C
80/20
6.4186.418
957372AF2-031 E
80/20
0.7050.705
965331AG1-398 C
80/20
0.2010.201
966442AG1-513 E
80/20
0.7520.752
274877BISHOP HL;1U
80/20
0.5210.521
276615W2-048 GEN
80/20
1.0561.056
293516O-009 E
80/20
4.5854.585
293644O22 E1
80/20
4.0984.098
924266AB2-070 E
80/20
2.692.69
936372AD2-047 E
80/20
15.04615.046
274675JOLIET 29;7U
80/20
44.03844.038
274860EASYR;U2 E
80/20
2.9342.934
276156O-029 C
80/20
0.30.3
290021O50 E
80/20
4.8624.862
961502AF2-441 E
80/20
9.3619.361
966091AG1-478 C
80/20
0.4850.485
274847GR RIDGE ;BU
80/20
0.8810.881
274849CRESCENT ;1U
80/20
0.2550.255
274857BIG SKY ;U1
80/20
0.4250.425
274859EASYR;U1 E
80/20
2.9342.934
276627AG1-044 BAT
80/20
0.0110.011
935141AD1-148 C
80/20
0.9450.945
957382AF2-032 E
80/20
0.1170.117
274891CAYUG;2U E
80/20
3.2643.264
276603SUBLETTE C
80/20
0.0940.094
276668AB2-070 C
80/20
0.4440.444
939321AE1-163 C
80/20
4.5314.531
942111AE2-223 C
80/20
1.4181.418
942652AE2-281 E
80/20
3.9763.976
946321AF1-296 C
80/20
2.7622.762
966441AG1-513 C
80/20
0.5010.501
274872LEE DEKAL;1U
80/20
1.1941.194
276621X2-022 GEN
80/20
3.0063.006
293061N-015 E
80/20
3.8593.859
293519PILOT HIL;1E
80/20
3.9663.966
924049AB2-047 E2
80/20
2.492.49
934722AD1-100 E
80/20
70.52170.521
939322AE1-163 E
80/20
27.83427.834
946322AF1-296 E
80/20
12.93112.931
274878BISHOP HL;2U
80/20
0.5210.521
276626AG1-044 E
80/20
0.0610.061
917502Z2-087 E
80/20
3.9533.953
942112AE2-223 E
80/20
9.4879.487
959351AF2-226 C
80/20
2.8532.853
966092AG1-478 E
80/20
0.7280.728
274674JOLIET 9 ;6U
80/20
15.24915.249
274890CAYUG;1U E
80/20
3.2643.264
276602WESTBROOK C
80/20
0.2080.208
276675AE2-062 E
80/20
0.1250.125
942651AE2-281 C
80/20
0.6470.647
965913AG1-460 BT
80/20
0.0060.006
920272AA2-123 E
80/20
2.4072.407
276170Z1-108 E
80/20
2.4582.458
990512J1326 G
External Queue
5.43125.4312
991302J1755
External Queue
9.86249.8624
990947J1432 G
External Queue
15.3415.34
991092J1477
External Queue
2.88432.8843
990052J1200
External Queue
0.43040.4304

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.83 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1452.53
MW Contribution:15.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
3.06235294117647072.603
957371AF2-031 C
Adder
0.462352941176470630.393
961501AF2-441 C
Adder
6.16352941176470555.239
274879MINONK ;1U
50/50
1.211.21
293645O22 E2
50/50
4.6734.673
957331AF2-027 C
50/50
2.462.46
957332AF2-027 E
50/50
3.693.69
959352AF2-226 E
50/50
4.2614.261
960281AF2-319 C
50/50
2.8412.841
960282AF2-319 E
50/50
4.2614.261
938852AE1-113 E
50/50
22.65322.653
938862AE1-114 E
Adder
10.4482352941176488.881
944221AF1-090 C
Adder
1.41647058823529411.204
274682WAUKEGAN ;7U
50/50
18.33318.333
274683WAUKEGAN ;8U
50/50
19.75819.758
274861TOP CROP ;1U
50/50
0.6530.653
274862TOP CROP ;2U
50/50
1.2461.246
934721AD1-100 C
50/50
4.5094.509
942421AE2-255 C
50/50
2.422.42
942422AE2-255 E
50/50
7.2617.261
959611AF2-252 C
Adder
1.721.462
960611AF2-352 C
Adder
1.721.462
960612AF2-352 E
Adder
2.582.193
962012AG1-044 E
Adder
0.054117647058823530.046
294392P-010 E
50/50
4.8764.876
926822AC1-168 E
Adder
5.9611764705882365.067
274687WILL CNTY;4U
50/50
41.36241.362
926821AC1-168 C
Adder
0.88823529411764710.755
959612AF2-252 E
Adder
2.582.193
274676JOLIET 29;8U
50/50
43.82443.824
936371AD2-047 C
Adder
3.0611764705882352.602
938851AE1-113 C
50/50
6.3896.389
274675JOLIET 29;7U
50/50
43.79843.798
290021O50 E
50/50
4.844.84
961502AF2-441 E
Adder
9.2458823529411777.859
957372AF2-031 E
Adder
0.69294117647058820.589
966442AG1-513 E
50/50
0.7480.748
966091AG1-478 C
50/50
0.4820.482
276627AG1-044 BAT
Adder
0.0105882352941176470.009
957382AF2-032 E
Adder
0.117647058823529420.1
274871GR RIDGE ;2U
50/50
0.3260.326
276626AG1-044 E
Adder
0.061176470588235290.052
942112AE2-223 E
Adder
9.4776470588235288.056
274847GR RIDGE ;BU
50/50
0.8770.877
293061N-015 E
50/50
3.8393.839
934722AD1-100 E
50/50
70.13470.134
939322AE1-163 E
Adder
27.69647058823529723.542
944222AF1-090 E
Adder
6.6294117647058825.635
946322AF1-296 E
Adder
12.8905882352941210.957
959351AF2-226 C
50/50
2.8412.841
966092AG1-478 E
50/50
0.7240.724
293644O22 E1
50/50
4.084.08
936372AD2-047 E
Adder
14.94235294117647212.701
939321AE1-163 C
Adder
4.5094117647058833.833
942111AE2-223 C
Adder
1.41647058823529411.204
942652AE2-281 E
Adder
3.9564705882352943.363
946321AF1-296 C
Adder
2.7541176470588242.341
966441AG1-513 C
50/50
0.4990.499
274674JOLIET 9 ;6U
Adder
15.1576470588235312.884
276675AE2-062 E
50/50
0.1240.124
942651AE2-281 C
Adder
0.64352941176470590.547
920272AA2-123 E
Adder
2.81764705882352962.395
276170Z1-108 E
50/50
2.4462.446
965913AG1-460 BT
Adder
0.00588235294117647050.005
990512J1326 G
External Queue
5.40125.4012
991302J1755
External Queue
9.81979.8197
990947J1432 G
External Queue
15.277515.2775
991092J1477
External Queue
2.87522.8752
990052J1200
External Queue
0.42840.4284

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.92 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1439.86
MW Contribution:15.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
3.07647058823529432.615
957371AF2-031 C
Adder
0.46941176470588240.399
961501AF2-441 C
Adder
6.2364705882352955.301
274879MINONK ;1U
50/50
1.2161.216
293645O22 E2
50/50
4.6944.694
957331AF2-027 C
50/50
2.4742.474
957332AF2-027 E
50/50
3.713.71
959352AF2-226 E
50/50
4.284.28
960281AF2-319 C
50/50
2.8532.853
960282AF2-319 E
50/50
4.284.28
938852AE1-113 E
50/50
22.76222.762
938862AE1-114 E
Adder
10.497647058823538.923
274682WAUKEGAN ;7U
50/50
18.43518.435
274683WAUKEGAN ;8U
50/50
19.86819.868
274861TOP CROP ;1U
50/50
0.6560.656
274862TOP CROP ;2U
50/50
1.2521.252
934721AD1-100 C
50/50
4.5314.531
942421AE2-255 C
50/50
2.4322.432
942422AE2-255 E
50/50
7.2957.295
959611AF2-252 C
Adder
1.721.462
960611AF2-352 C
Adder
1.721.462
960612AF2-352 E
Adder
2.582.193
962012AG1-044 E
Adder
0.054117647058823530.046
294392P-010 E
50/50
4.9034.903
926822AC1-168 E
Adder
5.9847058823529415.087
274687WILL CNTY;4U
50/50
41.59841.598
926821AC1-168 C
Adder
0.8917647058823530.758
959612AF2-252 E
Adder
2.582.193
274676JOLIET 29;8U
50/50
44.07844.078
936371AD2-047 C
Adder
3.08117647058823562.619
938851AE1-113 C
50/50
6.426.42
274675JOLIET 29;7U
50/50
44.05244.052
290021O50 E
50/50
4.8644.864
961502AF2-441 E
Adder
9.3552941176470597.952
957372AF2-031 E
Adder
0.70470588235294120.599
966442AG1-513 E
50/50
0.7530.753
966091AG1-478 C
50/50
0.4850.485
276627AG1-044 BAT
Adder
0.0105882352941176470.009
957382AF2-032 E
Adder
0.117647058823529420.1
274871GR RIDGE ;2U
50/50
0.3280.328
276626AG1-044 E
Adder
0.061176470588235290.052
942112AE2-223 E
Adder
9.4870588235294138.064
274847GR RIDGE ;BU
50/50
0.8810.881
293061N-015 E
50/50
3.863.86
934722AD1-100 E
50/50
70.47670.476
939322AE1-163 E
Adder
27.83882352941176623.663
946322AF1-296 E
Adder
12.93882352941176410.998
959351AF2-226 C
50/50
2.8532.853
966092AG1-478 E
50/50
0.7280.728
293644O22 E1
50/50
4.0984.098
936372AD2-047 E
Adder
15.04117647058823512.785
939321AE1-163 C
Adder
4.53176470588235253.852
942111AE2-223 C
Adder
1.41764705882352951.205
942652AE2-281 E
Adder
3.9764705882352943.38
946321AF1-296 C
Adder
2.7635294117647062.349
966441AG1-513 C
50/50
0.5020.502
274674JOLIET 9 ;6U
Adder
15.25411764705882312.966
276675AE2-062 E
50/50
0.1250.125
942651AE2-281 C
Adder
0.64705882352941180.55
965913AG1-460 BT
Adder
0.00588235294117647050.005
920272AA2-123 E
Adder
2.83294117647058832.408
276170Z1-108 E
50/50
2.462.46
990512J1326 G
External Queue
5.4355.435
991302J1755
External Queue
9.86539.8653
990947J1432 G
External Queue
15.3515.35
991092J1477
External Queue
2.88632.8863
990052J1200
External Queue
0.43050.4305

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.52 %
Rating:1091.0 MVA
Rating Type:A
MVA to Mitigate:1096.72
MW Contribution:10.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
290051GSG-6; E
80/20
1.6851.685
290108LEEDK;1U E
80/20
3.8583.858
290261S-027 E
80/20
2.2852.285
290265S-028 E
80/20
2.2712.271
295111SUBLETTE E
80/20
0.4390.439
925581AC1-033 C
80/20
0.3660.366
925582AC1-033 E
80/20
2.4492.449
938861AE1-114 C
80/20
2.0372.037
274851PROVIDENC;RU
80/20
0.1810.181
274853TWINGROVE;U1
80/20
0.4870.487
274854TWINGROVE;U2
80/20
0.5010.501
274855GSG-6 ;RU
80/20
0.4210.421
274879MINONK ;1U
80/20
0.8370.837
274881WALNUT RG;1U
80/20
0.7610.761
293645O22 E2
80/20
3.4613.461
293715O-029 E
80/20
1.5751.575
293717O-029 E
80/20
0.7940.794
916212CRESCENT ;1U
80/20
0.7850.785
916221Z1-073 E
80/20
1.1881.188
957331AF2-027 C
80/20
1.6591.659
957332AF2-027 E
80/20
2.4882.488
959352AF2-226 E
80/20
3.1563.156
960281AF2-319 C
80/20
2.1042.104
960282AF2-319 E
80/20
3.1563.156
270839OTTER CRK; R
80/20
0.3830.383
274888KELLY CRK;1U
80/20
0.6450.645
293716O-029 E
80/20
0.8630.863
937002AD2-134 E
80/20
2.612.61
938852AE1-113 E
80/20
15.67215.672
938862AE1-114 E
80/20
6.9496.949
270681BRIGHTSTK; R
80/20
0.3850.385
274887PILOT HIL;1U
80/20
0.6450.645
275149KELLYCK ;1E
80/20
2.5792.579
293771O-035 E
80/20
1.1181.118
924048AB2-047 E1
80/20
1.5971.597
937001AD2-134 C
80/20
0.6530.653
274682WAUKEGAN ;7U
80/20
12.37312.373
274683WAUKEGAN ;8U
80/20
13.33213.332
274861TOP CROP ;1U
80/20
0.4840.484
274862TOP CROP ;2U
80/20
0.9230.923
274863CAYUGA RI;1U
80/20
0.4010.401
276157O-029 C
80/20
0.3590.359
276158O-029 C
80/20
0.3590.359
934721AD1-100 C
80/20
2.9882.988
942421AE2-255 C
80/20
1.6741.674
942422AE2-255 E
80/20
5.0235.023
959611AF2-252 C
80/20
1.121.12
960611AF2-352 C
80/20
1.121.12
960612AF2-352 E
80/20
1.681.68
990901L-005 E
80/20
2.0672.067
276645AC1-214 C1
80/20
0.1490.149
276646AC1-214 C2
80/20
0.1490.149
962012AG1-044 E
80/20
0.0360.036
274864CAYUGA RI;2U
80/20
0.4010.401
276655AB2-047 C1
80/20
0.240.24
294392P-010 E
80/20
3.2533.253
294410BSHIL;2U E
80/20
1.3951.395
918052AA1-018 E OP
80/20
2.5632.563
926822AC1-168 E
80/20
44
927209AC1-214 E2
80/20
0.530.53
274687WILL CNTY;4U
80/20
29.39129.391
276656AB2-047 C2
80/20
0.240.24
294401BSHIL;1U E
80/20
1.3951.395
926821AC1-168 C
80/20
0.5960.596
927208AC1-214 E1
80/20
0.530.53
959612AF2-252 E
80/20
1.681.68
274848CAMPGROVE;RU
80/20
0.2240.224
274850MENDOTA H;RU
80/20
0.2770.277
274856ECOGROVE ;U1
80/20
0.3680.368
274858BIG SKY ;U2
80/20
0.2820.282
274871GR RIDGE ;2U
80/20
0.2180.218
274676JOLIET 29;8U
80/20
30.59430.594
294763P-046 E
80/20
1.5291.529
295109WESTBROOK E
80/20
0.9020.902
936371AD2-047 C
80/20
2.0042.004
938851AE1-113 C
80/20
4.424.42
966442AG1-513 E
80/20
0.4920.492
274877BISHOP HL;1U
80/20
0.3490.349
293516O-009 E
80/20
3.0453.045
293644O22 E1
80/20
3.0223.022
936372AD2-047 E
80/20
9.7859.785
274675JOLIET 29;7U
80/20
30.56830.568
274860EASYR;U2 E
80/20
1.9441.944
276156O-029 C
80/20
0.1990.199
290021O50 E
80/20
3.3493.349
966091AG1-478 C
80/20
0.3250.325
274847GR RIDGE ;BU
80/20
0.5850.585
274849CRESCENT ;1U
80/20
0.170.17
274857BIG SKY ;U1
80/20
0.2820.282
274859EASYR;U1 E
80/20
1.9441.944
276627AG1-044 BAT
80/20
0.0070.007
274891CAYUG;2U E
80/20
2.1372.137
276603SUBLETTE C
80/20
0.0620.062
939321AE1-163 C
80/20
3.083.08
942111AE2-223 C
80/20
0.9230.923
942652AE2-281 E
80/20
2.7032.703
946321AF1-296 C
80/20
1.8341.834
966441AG1-513 C
80/20
0.3280.328
274872LEE DEKAL;1U
80/20
0.7810.781
293061N-015 E
80/20
2.5612.561
293519PILOT HIL;1E
80/20
2.5792.579
924049AB2-047 E2
80/20
1.6221.622
934722AD1-100 E
80/20
46.47446.474
939322AE1-163 E
80/20
18.9218.92
946322AF1-296 E
80/20
8.5868.586
274878BISHOP HL;2U
80/20
0.3490.349
276626AG1-044 E
80/20
0.0410.041
917502Z2-087 E
80/20
2.5752.575
942112AE2-223 E
80/20
6.1816.181
959351AF2-226 C
80/20
2.1042.104
966092AG1-478 E
80/20
0.4880.488
274674JOLIET 9 ;6U
80/20
10.08310.083
274890CAYUG;1U E
80/20
2.1372.137
276602WESTBROOK C
80/20
0.1370.137
276675AE2-062 E
80/20
0.0850.085
942651AE2-281 C
80/20
0.440.44
276170Z1-108 E
80/20
1.6321.632
920272AA2-123 E
80/20
1.5961.596

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.44 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1158.61
MW Contribution:13.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
3.7663.766
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
295111SUBLETTE E
80/20
0.5570.557
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
938861AE1-114 C
80/20
2.5552.555
957371AF2-031 C
80/20
0.6360.636
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274881WALNUT RG;1U
80/20
0.9520.952
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293717O-029 E
80/20
0.9930.993
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959352AF2-226 E
80/20
2.9452.945
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
270839OTTER CRK; R
80/20
0.5410.541
274888KELLY CRK;1U
80/20
0.9460.946
293716O-029 E
80/20
1.081.08
937002AD2-134 E
80/20
3.3123.312
938852AE1-113 E
80/20
18.55518.555
938862AE1-114 E
80/20
8.7168.716
270681BRIGHTSTK; R
80/20
0.4980.498
274887PILOT HIL;1U
80/20
0.9460.946
275149KELLYCK ;1E
80/20
3.7863.786
293771O-035 E
80/20
1.3921.392
924048AB2-047 E1
80/20
2.0672.067
937001AD2-134 C
80/20
0.8290.829
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
934721AD1-100 C
80/20
3.8223.822
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
959611AF2-252 C
80/20
1.4511.451
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
990901L-005 E
80/20
2.5642.564
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
925771AC1-053 C
80/20
0.590.59
962012AG1-044 E
80/20
0.0450.045
274864CAYUGA RI;2U
80/20
0.5160.516
276655AB2-047 C1
80/20
0.3110.311
294392P-010 E
80/20
4.0594.059
294410BSHIL;2U E
80/20
1.7331.733
918052AA1-018 E OP
80/20
3.6223.622
926822AC1-168 E
80/20
4.9814.981
927209AC1-214 E2
80/20
0.660.66
274687WILL CNTY;4U
80/20
32.59232.592
276656AB2-047 C2
80/20
0.3110.311
294401BSHIL;1U E
80/20
1.7331.733
925772AC1-053 E
80/20
3.953.95
926821AC1-168 C
80/20
0.7420.742
927208AC1-214 E1
80/20
0.660.66
959612AF2-252 E
80/20
2.1762.176
274848CAMPGROVE;RU
80/20
0.2780.278
274850MENDOTA H;RU
80/20
0.3520.352
274856ECOGROVE ;U1
80/20
0.4620.462
274858BIG SKY ;U2
80/20
0.3530.353
274871GR RIDGE ;2U
80/20
0.2720.272
274877BISHOP HL;1U
80/20
0.4330.433
276615W2-048 GEN
80/20
0.8910.891
293516O-009 E
80/20
3.8093.809
293644O22 E1
80/20
2.822.82
924266AB2-070 E
80/20
2.272.27
936372AD2-047 E
80/20
14.36514.365
939321AE1-163 C
80/20
4.1514.151
942111AE2-223 C
80/20
1.1951.195
942652AE2-281 E
80/20
3.6423.642
946321AF1-296 C
80/20
2.2942.294
966441AG1-513 C
80/20
0.4190.419
274676JOLIET 29;8U
80/20
36.23736.237
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
936371AD2-047 C
80/20
2.9422.942
938851AE1-113 C
80/20
5.2345.234
957372AF2-031 E
80/20
0.9540.954
965331AG1-398 C
80/20
0.1690.169
966442AG1-513 E
80/20
0.6290.629
274675JOLIET 29;7U
80/20
36.25136.251
274860EASYR;U2 E
80/20
2.4372.437
276156O-029 C
80/20
0.2490.249
290021O50 E
80/20
3.9653.965
961502AF2-441 E
80/20
10.40210.402
966091AG1-478 C
80/20
0.4310.431
274847GR RIDGE ;BU
80/20
0.730.73
274849CRESCENT ;1U
80/20
0.2120.212
274857BIG SKY ;U1
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274872LEE DEKAL;1U
80/20
0.9950.995
276621X2-022 GEN
80/20
2.5362.536
293061N-015 E
80/20
3.1963.196
293519PILOT HIL;1E
80/20
3.7863.786
924049AB2-047 E2
80/20
2.0992.099
934722AD1-100 E
80/20
59.4559.45
939322AE1-163 E
80/20
25.49625.496
946322AF1-296 E
80/20
10.73910.739
959351AF2-226 C
80/20
1.9641.964
966092AG1-478 E
80/20
0.6470.647
276627AG1-044 BAT
80/20
0.0090.009
935141AD1-148 C
80/20
0.7970.797
274891CAYUG;2U E
80/20
2.7522.752
276603SUBLETTE C
80/20
0.0780.078
276668AB2-070 C
80/20
0.3750.375
274878BISHOP HL;2U
80/20
0.4330.433
276626AG1-044 E
80/20
0.0510.051
917502Z2-087 E
80/20
3.3333.333
942112AE2-223 E
80/20
7.9997.999
274674JOLIET 9 ;6U
80/20
13.64413.644
274890CAYUG;1U E
80/20
2.7522.752
276602WESTBROOK C
80/20
0.1730.173
276675AE2-062 E
80/20
0.1120.112
942651AE2-281 C
80/20
0.5930.593
276170Z1-108 E
80/20
2.0422.042
965793AG1-447 BT
80/20
8.3248.324
920272AA2-123 E
80/20
22
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769
990052J1200
External Queue
0.35320.3532

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.42 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1158.42
MW Contribution:13.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
3.7663.766
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
295111SUBLETTE E
80/20
0.5570.557
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
938861AE1-114 C
80/20
2.5552.555
957371AF2-031 C
80/20
0.6360.636
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274881WALNUT RG;1U
80/20
0.9520.952
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293717O-029 E
80/20
0.9930.993
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959352AF2-226 E
80/20
2.9452.945
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
270839OTTER CRK; R
80/20
0.5410.541
274888KELLY CRK;1U
80/20
0.9460.946
293716O-029 E
80/20
1.081.08
937002AD2-134 E
80/20
3.3123.312
938852AE1-113 E
80/20
18.55518.555
938862AE1-114 E
80/20
8.7168.716
270681BRIGHTSTK; R
80/20
0.4980.498
274887PILOT HIL;1U
80/20
0.9460.946
275149KELLYCK ;1E
80/20
3.7863.786
293771O-035 E
80/20
1.3921.392
924048AB2-047 E1
80/20
2.0672.067
937001AD2-134 C
80/20
0.8290.829
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
934721AD1-100 C
80/20
3.8223.822
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
959611AF2-252 C
80/20
1.4511.451
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
990901L-005 E
80/20
2.5642.564
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
925771AC1-053 C
80/20
0.590.59
962012AG1-044 E
80/20
0.0450.045
274864CAYUGA RI;2U
80/20
0.5160.516
276655AB2-047 C1
80/20
0.3110.311
294392P-010 E
80/20
4.0594.059
294410BSHIL;2U E
80/20
1.7331.733
918052AA1-018 E OP
80/20
3.6223.622
926822AC1-168 E
80/20
4.9814.981
927209AC1-214 E2
80/20
0.660.66
274687WILL CNTY;4U
80/20
32.59232.592
276656AB2-047 C2
80/20
0.3110.311
294401BSHIL;1U E
80/20
1.7331.733
925772AC1-053 E
80/20
3.953.95
926821AC1-168 C
80/20
0.7420.742
927208AC1-214 E1
80/20
0.660.66
959612AF2-252 E
80/20
2.1762.176
274848CAMPGROVE;RU
80/20
0.2780.278
274850MENDOTA H;RU
80/20
0.3520.352
274856ECOGROVE ;U1
80/20
0.4620.462
274858BIG SKY ;U2
80/20
0.3530.353
274871GR RIDGE ;2U
80/20
0.2720.272
274877BISHOP HL;1U
80/20
0.4330.433
276615W2-048 GEN
80/20
0.8910.891
293516O-009 E
80/20
3.8093.809
293644O22 E1
80/20
2.822.82
924266AB2-070 E
80/20
2.272.27
936372AD2-047 E
80/20
14.36514.365
939321AE1-163 C
80/20
4.1514.151
942111AE2-223 C
80/20
1.1951.195
942652AE2-281 E
80/20
3.6423.642
946321AF1-296 C
80/20
2.2942.294
966441AG1-513 C
80/20
0.4190.419
274676JOLIET 29;8U
80/20
36.23736.237
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
936371AD2-047 C
80/20
2.9422.942
938851AE1-113 C
80/20
5.2345.234
957372AF2-031 E
80/20
0.9540.954
965331AG1-398 C
80/20
0.1690.169
966442AG1-513 E
80/20
0.6290.629
274675JOLIET 29;7U
80/20
36.25136.251
274860EASYR;U2 E
80/20
2.4372.437
276156O-029 C
80/20
0.2490.249
290021O50 E
80/20
3.9653.965
961502AF2-441 E
80/20
10.40210.402
966091AG1-478 C
80/20
0.4310.431
274847GR RIDGE ;BU
80/20
0.730.73
274849CRESCENT ;1U
80/20
0.2120.212
274857BIG SKY ;U1
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274872LEE DEKAL;1U
80/20
0.9950.995
276621X2-022 GEN
80/20
2.5362.536
293061N-015 E
80/20
3.1963.196
293519PILOT HIL;1E
80/20
3.7863.786
924049AB2-047 E2
80/20
2.0992.099
934722AD1-100 E
80/20
59.4559.45
939322AE1-163 E
80/20
25.49625.496
946322AF1-296 E
80/20
10.73910.739
959351AF2-226 C
80/20
1.9641.964
966092AG1-478 E
80/20
0.6470.647
276627AG1-044 BAT
80/20
0.0090.009
935141AD1-148 C
80/20
0.7970.797
274891CAYUG;2U E
80/20
2.7522.752
276603SUBLETTE C
80/20
0.0780.078
276668AB2-070 C
80/20
0.3750.375
274878BISHOP HL;2U
80/20
0.4330.433
276626AG1-044 E
80/20
0.0510.051
917502Z2-087 E
80/20
3.3333.333
942112AE2-223 E
80/20
7.9997.999
274674JOLIET 9 ;6U
80/20
13.64413.644
274890CAYUG;1U E
80/20
2.7522.752
276602WESTBROOK C
80/20
0.1730.173
276675AE2-062 E
80/20
0.1120.112
942651AE2-281 C
80/20
0.5930.593
920272AA2-123 E
80/20
22
276170Z1-108 E
80/20
2.0422.042
965793AG1-447 BT
80/20
8.3248.324
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769
990052J1200
External Queue
0.35320.3532

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.94 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1027.6
MW Contribution:13.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
2.5552941176470592.172
957371AF2-031 C
Adder
0.63647058823529420.541
961501AF2-441 C
Adder
6.9341176470588245.894
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959352AF2-226 E
Adder
2.94588235294117642.504
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
270839OTTER CRK; R
50/50
0.5410.541
274888KELLY CRK;1U
50/50
0.9460.946
938852AE1-113 E
Adder
18.5576470588235315.774
938862AE1-114 E
Adder
8.717647058823537.41
274887PILOT HIL;1U
50/50
0.9460.946
275149KELLYCK ;1E
50/50
3.7853.785
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
934721AD1-100 C
50/50
3.8213.821
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
959611AF2-252 C
Adder
1.45058823529411771.233
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
962012AG1-044 E
Adder
0.044705882352941180.038
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
926822AC1-168 E
Adder
4.98117647058823554.234
274687WILL CNTY;4U
50/50
32.59532.595
926821AC1-168 C
Adder
0.74235294117647070.631
959612AF2-252 E
Adder
2.17647058823529441.85
274676JOLIET 29;8U
50/50
36.23736.237
936371AD2-047 C
50/50
2.9422.942
938851AE1-113 C
Adder
5.2341176470588244.449
957372AF2-031 E
Adder
0.95411764705882360.811
274675JOLIET 29;7U
50/50
36.25136.251
961502AF2-441 E
Adder
10.48.84
966442AG1-513 E
50/50
0.6290.629
966091AG1-478 C
50/50
0.4310.431
276627AG1-044 BAT
Adder
0.0094117647058823540.008
274871GR RIDGE ;2U
50/50
0.2720.272
276626AG1-044 E
Adder
0.050588235294117640.043
942112AE2-223 E
Adder
7.9988235294117666.799
274847GR RIDGE ;BU
50/50
0.730.73
293061N-015 E
50/50
3.1963.196
293519PILOT HIL;1E
50/50
3.7853.785
934722AD1-100 E
50/50
59.44459.444
939322AE1-163 E
50/50
25.49625.496
946322AF1-296 E
Adder
10.749.129
959351AF2-226 C
Adder
1.9635294117647061.669
966092AG1-478 E
50/50
0.6470.647
936372AD2-047 E
50/50
14.36514.365
939321AE1-163 C
50/50
4.1514.151
942111AE2-223 C
Adder
1.19529411764705881.016
942652AE2-281 E
50/50
3.6423.642
946321AF1-296 C
Adder
2.29411764705882341.95
966441AG1-513 C
50/50
0.420.42
274674JOLIET 9 ;6U
50/50
13.64513.645
276675AE2-062 E
50/50
0.1120.112
942651AE2-281 C
50/50
0.5930.593
965793AG1-447 BT
50/50
8.3258.325
920272AA2-123 E
50/50
22
276170Z1-108 E
50/50
2.0432.043
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769
990947J1432 G
External Queue
12.502512.5025
990052J1200
External Queue
0.35320.3532

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.94 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1027.59
MW Contribution:13.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
2.5552941176470592.172
957371AF2-031 C
Adder
0.63647058823529420.541
961501AF2-441 C
Adder
6.9341176470588245.894
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959352AF2-226 E
Adder
2.94588235294117642.504
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
270839OTTER CRK; R
50/50
0.5410.541
274888KELLY CRK;1U
50/50
0.9460.946
938852AE1-113 E
Adder
18.5576470588235315.774
938862AE1-114 E
Adder
8.717647058823537.41
274887PILOT HIL;1U
50/50
0.9460.946
275149KELLYCK ;1E
50/50
3.7853.785
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
934721AD1-100 C
50/50
3.8213.821
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
959611AF2-252 C
Adder
1.45058823529411771.233
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
962012AG1-044 E
Adder
0.044705882352941180.038
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
926822AC1-168 E
Adder
4.98117647058823554.234
274687WILL CNTY;4U
50/50
32.59532.595
926821AC1-168 C
Adder
0.74235294117647070.631
959612AF2-252 E
Adder
2.17647058823529441.85
274676JOLIET 29;8U
50/50
36.23736.237
936371AD2-047 C
50/50
2.9422.942
938851AE1-113 C
Adder
5.2341176470588244.449
957372AF2-031 E
Adder
0.95411764705882360.811
274675JOLIET 29;7U
50/50
36.25136.251
961502AF2-441 E
Adder
10.48.84
966442AG1-513 E
50/50
0.6290.629
966091AG1-478 C
50/50
0.4310.431
276627AG1-044 BAT
Adder
0.0094117647058823540.008
274871GR RIDGE ;2U
50/50
0.2720.272
276626AG1-044 E
Adder
0.050588235294117640.043
942112AE2-223 E
Adder
7.9988235294117666.799
274847GR RIDGE ;BU
50/50
0.730.73
293061N-015 E
50/50
3.1963.196
293519PILOT HIL;1E
50/50
3.7853.785
934722AD1-100 E
50/50
59.44459.444
939322AE1-163 E
50/50
25.49625.496
946322AF1-296 E
Adder
10.749.129
959351AF2-226 C
Adder
1.9635294117647061.669
966092AG1-478 E
50/50
0.6470.647
936372AD2-047 E
50/50
14.36514.365
939321AE1-163 C
50/50
4.1514.151
942111AE2-223 C
Adder
1.19529411764705881.016
942652AE2-281 E
50/50
3.6423.642
946321AF1-296 C
Adder
2.29411764705882341.95
966441AG1-513 C
50/50
0.420.42
274674JOLIET 9 ;6U
50/50
13.64513.645
276675AE2-062 E
50/50
0.1120.112
942651AE2-281 C
50/50
0.5930.593
276170Z1-108 E
50/50
2.0432.043
965793AG1-447 BT
50/50
8.3258.325
920272AA2-123 E
50/50
22
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769
990947J1432 G
External Queue
12.502512.5025
990052J1200
External Queue
0.35320.3532
CONTINGENCY '765-L11215__-S_SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
END
CONTINGENCY 'AEP_P1-2_#695_1681_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243207 CKT 1   /*05DUMONT     765.0 - 05GRNTWN     765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'COMED_P4_112-65-BT4-5___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT3-4___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
255113 to 243219 ckt 1
960680 to 243229 ckt 1
274750 to 255112 ckt 1
270728 to 274750 ckt 1
274804 to 960680 ckt 1

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1CE
AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line
765-L11216__-S_SRT-A
OPAC113.92 %1528.0B1740.748.11

Details for AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o 765-L11216__-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line
Contingency Name:
765-L11216__-S_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.92 %
Rating:1528.0 MVA
Rating Type:B
MVA to Mitigate:1740.74
MW Contribution:8.11
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line
Contingency Name:
765-L11216__-S_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.89 %
Rating:1528.0 MVA
Rating Type:B
MVA to Mitigate:1770.85
MW Contribution:8.26
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
50/50
0.9240.924
274853TWINGROVE;U1
50/50
1.0791.079
274854TWINGROVE;U2
50/50
1.111.11
274863CAYUGA RI;1U
50/50
1.141.14
274864CAYUGA RI;2U
50/50
1.141.14
274871GR RIDGE ;2U
50/50
0.3440.344
274887PILOT HIL;1U
50/50
1.3051.305
274888KELLY CRK;1U
50/50
1.3051.305
290261S-027 E
50/50
5.0595.059
290265S-028 E
50/50
5.0285.028
293061N-015 E
50/50
4.0464.046
294392P-010 E
50/50
5.1395.139
917502Z2-087 E
50/50
5.775.77
934721AD1-100 C
50/50
10.63310.633
934722AD1-100 E
50/50
165.396165.396
942111AE2-223 C
50/50
2.0692.069
942112AE2-223 E
50/50
13.84913.849
957331AF2-027 C
Adder
1.00117647058823530.851
957332AF2-027 E
Adder
1.50117647058823531.276
959611AF2-252 C
50/50
2.482.48
959612AF2-252 E
50/50
3.723.72
960611AF2-352 C
50/50
2.482.48
960612AF2-352 E
50/50
3.723.72
962012AG1-044 E
Adder
0.028235294117647060.024
966091AG1-478 C
Adder
0.36588235294117650.311
966092AG1-478 E
Adder
0.54823529411764720.466
966441AG1-513 C
Adder
0.248235294117647050.211
966442AG1-513 E
Adder
0.37294117647058830.317
274674JOLIET 9 ;6U
Adder
8.327.072
274890CAYUG;1U E
50/50
6.086.08
274891CAYUG;2U E
50/50
6.086.08
957382AF2-032 E
Adder
0.135294117647058840.115
270681BRIGHTSTK; R
50/50
0.8620.862
275149KELLYCK ;1E
50/50
5.2195.219
276626AG1-044 E
Adder
0.0317647058823529450.027
276627AG1-044 BAT
Adder
0.00588235294117647050.005
276655AB2-047 C1
50/50
0.5390.539
276656AB2-047 C2
50/50
0.5390.539
293519PILOT HIL;1E
50/50
5.2195.219
924048AB2-047 E1
50/50
3.5783.578
924049AB2-047 E2
50/50
3.6353.635
926821AC1-168 C
Adder
0.65882352941176480.56
926822AC1-168 E
Adder
4.4211764705882353.758
936371AD2-047 C
50/50
4.0564.056
936372AD2-047 E
50/50
19.80319.803
938861AE1-114 C
Adder
1.5152941176470591.288
938862AE1-114 E
Adder
5.1717647058823534.396
944221AF1-090 C
Adder
1.60705882352941191.366
944222AF1-090 E
Adder
7.5247058823529416.396
946321AF1-296 C
Adder
1.4270588235294121.213
946322AF1-296 E
Adder
6.685.678
276170Z1-108 E
Adder
1.31.105
920272AA2-123 E
Adder
1.30470588235294121.109
965913AG1-460 BT
Adder
0.0070588235294117650.006
956282J1115 G
External Queue
11.74411.744
990052J1200
External Queue
0.32890.3289
CONTINGENCY '765-L11216__-S_SRT-A'
 TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1   /*WILTON   ;   765.0 - COLLINS  ;   765.0
END
934720 to 270926 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests AF1-296, AG1-462 and AG1-553 in PJM Transition Cycle 1, Cluster 17 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 17 projects.

This analysis is effectively a screening study to determine whether the addition of the Cluster 17 projects will meet the dynamics requirements of the NERC, ComEd and PJM reliability standards.

The load flow scenario for the analysis was based on the RTEP 2027 summer peak load case, modified to include applicable projects. Cluster 17 projects have been dispatched online at maximum power output, with 1.0 pu voltage at the terminal bus, except AF1-296, which was allowed to have a terminal voltage of 1.027 pu.

Cluster 17 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 197 contingencies were studied, each with a 20 second simulation time period. Studied faults included:

  1. Steady-state operation (20 second run);
  2. Three-phase faults with normal clearing time;
  3. Three-phase bus faults with normal clearing time;
  4. Three-phase faults with single-phase delayed clearing due to a stuck breaker (IPO breaker with FD Logic).
  5. Three-phase faults with three-phase delayed clearing due to a stuck breaker (GO Breakers with A-contact Logic);
  6. Three-phase faults with single-phase delayed clearing due to a stuck breaker (GO Breakers with FD Logic);
  7. Three-phase faults with three-phase delayed clearing due to a stuck breaker (GO breakers with FD Logic);
  8. Single-phase faults with stuck breaker (for MISO substations);
  9. Three-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure;
  10. Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (for MISO substations);
  11. Three-phase faults with loss of multiple-circuit tower line.

No relevant high-speed reclosing (HSR) contingencies were identified for this study.

Buses at which the faults listed above were applied are:

  • Cordova E.C. TSS 940 (AG1-553/AG1-462 POI) 345 kV
  • Cordova M.E.C. 345 kV
  • Nelson TSS 155 (AE1-134/AA2-030/AA1-146 POI) 345 kV
  • E. Molin (Barstow SUB. 39 M.E.C.) 345 kV
  • Quad Cities STA. 4 345 kV
  • Garden Plain TSS 132 (AF1-296 POI) 138 kV
  • Nelson TSS 155 138 kV
  • AF2-392 TAP 138 kV
  • Sterling Steel (ESS H71) 138 kV
  • Rock Falls TSS 133 138 kV
  • Albany S.S. 138 kV & 161 kV
  • Beaver Channel 161 kV
  • York 161 kV
  • Savanna 161 kV
  • Rock Creek 161 kV
  • SUB 49 161 kV

For all simulations, the queue projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

For all of the fault contingencies tested on the 2027 peak load case:

  1. Cluster 17 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  2. The system with Cluster 17 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.
  3. Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).
  4. No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

AG1-553, AG1-462 and AF1-296 meet the 0.95 leading and lagging PF requirement.

The composite short-circuit ratio (CSCR) assessment was performed for inverter-based renewable generation units which are within one (1) substation away of Cluster 17. The CSCR results for AF1-296 are summarized in Table 7 through Table 17 and revealed a minimum and maximum CSCR values of 2.64 for P4.84 & P4.86 and 4.45 for P1.64, respectively. The CSCR results for AG1-553 and AG1-462 revealed a minimum and maximum CSCR values of 3.81 for P4.08 & P4.10 and 7.24 for P1.02 & P4.03, respectively.

Specific findings from the simulations for each of the queue projects of Cluster 17 are indicated below.

AG1-553 and AG1-462

The IPCMD and IQCMD states in the REGCA1 models of AG1-553 GEN 1&2 and AG1-462 GEN 1 showed erratic behavior for some contingencies in which AG1-553 or AG1-462 generators have been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

High voltage spikes on the terminal voltages of AG1-462 and AG1-553, occurred in the simulations immediately after fault clearing for a few of the contingencies studied (i.e. fault where spike is observed). The voltage spike is a known artifact of the WECC generic renewable models as stated in the WECC Solar Plant Dynamic Model Guidelines: “It should be noted that generic dynamic models for inverter-based generator tend to produce a short-duration (a cycle or shorter) voltage spike at fault inception and clearing. These spikes should be ignored in most cases, as they do not represent the performance of actual hardware. They are simply a consequence of the model’s limited bandwidth, integration time step, and the way current injection models interface with the network solution.”

AF1-296

For 24 contingencies out of 197, the steady state post-contingency terminal voltage of AF1-296 went slightly above 1.05 pu (Et ≈ 1.056 pu – 14 contingencies, Et ≈ 1.051 pu – 10 contingencies). This is due to the fact that the terminal voltage of AF1-296 pre-contingency is 1.027 pu.

High voltage spikes at the terminals of AF1-296 and its POI, Garden Plain 138 kV, occurred in the simulations immediately after fault clearing for some of the contingencies studied (i.e. fault where spike is observed]). As, with the WECC models, these voltage spikes are considered a consequence of the model’s limited bandwidth, integration time step and the way it interfaces with the network solution. Therefore, it is estimated that they do not represent the performance of actual equipment and can be ignored in most cases. The spike at Garden Plain is a consequence of the spike at the terminals of AF1-296.

No mitigations were found to be required. However, it is recommended that the developer of AF1-296 provides an adjusted model that allows specifying the generator’s reactive power output at levels that support initial conditions with a terminal voltage close to 1.0 pu.

 

Table 1: Cluster 17 Projects

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

17

AF1-296

Wind

ComEd

190.89

190.89

33.6

Garden Plain 138 kV

AG1-462

Solar

ComEd

255

255

153

Cordova 345 kV

AG1-553

Solar

ComEd

260

260

0

Cordova 345 kV

 

Reactive Power Analysis

The reactive power capability of AF1-296 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-146NelsonIn Service
AA2-030NelsonIn Service
AC1-033Kewanee 138 kVIn Service
AC1-214Crescent RidgeIn Service
AD1-013Twombly Road 138kVEngineering & Procurement
AD2-134Shady OaksPartially in Service - Under Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-134Nelson 345 kVIn Service
AF1-280Nelson-Lee CountyEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-182Nelson-Lee County 345 kV IIEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AG1-044Whiteside CountyIn Service
AG1-462Cordova 345 kVEngineering & Procurement
AG1-553Cordova 345 kVEngineering & Procurement
Z1-073Mendota HillsIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In coordination with other Affected System Operators, PJM has determined that the Affected System Operator for this project that requires an Affected System Study. For the latest Affected System Study results pertaining this project, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM lists any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO) Identified Impacts
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AF1-296 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
ComEdn6639.2Reconductor the Electric Junction 345 kV line 93407, perform sag mitigation on 345 kV line 93407, upgrade one 345 kV circuit breaker and associated motor operated disconnect switches.Cost Allocated$9,366,298
AEPb3775.6Perform sag study mitigation work on the Dumont-Stillwell 345 kV lineContingent$0N/A
AEPb3775.11Upgrade the wavetrap at Dumont substation to increase the rating of the Stillwell-Dumont 345 kV line to match conductor rating.Contingent$0N/A
AEPb3775.7Upgrade breakers at Dumont substation on the Stillwell-Dumont 345 kV line.Contingent$0N/A
ComEdb3775.1Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV lineContingent$0N/A
AEPb3775.10Perform sag study mitigation work on Olive – University ParkContingent$0N/A
ComEdb3775.3Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to CreteContingent$0N/A
ComEdn5145Reconfigure Wilton 765kV busContingent$0N/A
ComEdb3775.4Rebuild 345 kV double circuit extending from Crete to E. Frankfort.Contingent$0N/A
Grand Total:$9,366,298

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n6639.2
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n6639.2 / CE_NUN_L15502_4
Title
Reconductor the Electric Junction 345 kV line 93407, perform sag mitigation on 345 kV line 93407, upgrade one 345 kV circuit breaker and associated motor operated disconnect switches.
Description
• Reconductor 27.2 Miles of 345kV transmission line 93407 from structure 339 to structure 454 • Perform sag mitigation on 13.5 miles of 345kV transmission line 93407 from structure 454 to TSS 111 Electric Junction • Upgrade the existing substation TSS 111 Electric Junction by replacing L.93407 CB motor-operated disconnect switches on both sides of the breaker.
Total Cost ($USD)
$146,197,759
Discounted Total Cost ($USD)
$146,197,759
Allocated Cost ($USD)
$9,366,298
Time Estimate
Sep 30 2029

Contributor

FacilityContingency
ELECT JCT; B-AF2-041 TP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE1-11422.0 MW3.2%$4,677,511
AF1-280 ⧉ Nelson - Lee County 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-280, AF2-182
67.2 MW9.8%$14,292,703
AF1-29644.0 MW6.4%$9,366,298
AF2-041 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-041, AF2-199, AF2-200
159.4 MW23.2%$33,916,212
AF2-182 ⧉ Nelson - Lee County 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-280, AF2-182
100.8 MW14.7%$21,438,948
AF2-199 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-041, AF2-199, AF2-200
53.1 MW7.7%$11,305,333
AF2-200 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-041, AF2-199, AF2-200
118.1 MW17.2%$25,123,010
AG1-462 ⧉ Cordova 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-462, AG1-553
60.7 MW8.8%$12,912,297
AG1-553 ⧉ Cordova 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-462, AG1-553
61.9 MW9.0%$13,165,446

System Reinforcement: b3775.6
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.6
Title
Perform sag study mitigation work on the Dumont-Stillwell 345 kV line
Description
Perform sag study mitigation work on the Dumont-Stillwell 345 kV line (remove a center-pivot irrigation system from under the line, allowing for the normal and emergency ratings of the line to increase, replace two structures and modify a third structure).
Cost Information
Time Estimate
Nov 20 2026

Contingent

Note: Although AF1-296 may not presently have cost responsibility for this upgrade, AF1-296 may need this upgrade in-service to be deliverable to the PJM system. If AF1-296 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1409.0 MVA
(All)B1718.0 MVA

System Reinforcement: b3775.11
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.11 / b3775.7a
Title
Upgrade the wavetrap at Dumont substation to increase the rating of the Stillwell-Dumont 345 kV line to match conductor rating.
Description
Upgrade the wavetrap at Dumont substation to increase the rating of the Stillwell-Dumont 345 kV line to match conductor rating.
Cost Information
Time Estimate
Dec 01 2026

Contingent

Note: Although AF1-296 may not presently have cost responsibility for this upgrade, AF1-296 may need this upgrade in-service to be deliverable to the PJM system. If AF1-296 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1409.0 MVA
(All)B1737.0 MVA

System Reinforcement: b3775.7
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.7 / b3775.7b
Title
Upgrade breakers at Dumont substation on the Stillwell-Dumont 345 kV line.
Description
Upgrade the limiting element at Dumont substation to increase the rating of the Stillwell-Dumont 345 kV line to match conductor rating. This includes replacement of breakers F and F1.
Cost Information
Time Estimate
Dec 01 2026

Contingent

Note: Although AF1-296 may not presently have cost responsibility for this upgrade, AF1-296 may need this upgrade in-service to be deliverable to the PJM system. If AF1-296 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1408.0 MVA
(All)B1887.0 MVA

System Reinforcement: b3775.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.1
Title
Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line
Description
Outside of the Green Acres substation, swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line to the University Park N-Olive 345 kV line to create a University Park N-Green Acres-Olive and St. John-Olive 345 kV lines.
Cost Information
Time Estimate
Mar 30 2027

Contingent

Note: Although AF1-296 may not presently have cost responsibility for this upgrade, AF1-296 may need this upgrade in-service to be deliverable to the PJM system. If AF1-296 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)ALDR9999.0 MVA
(All)STE9999.0 MVA
05OLIVE-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A9999.0 MVA
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A9999.0 MVA

System Reinforcement: b3775.10
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.10
Title
Perform sag study mitigation work on Olive – University Park
Description
Perform a sag study on the Olive – University Park 345kV line to increase the operating temperature to 225 F. Remediation work includes two tower replacements on the line.
Cost Information
Time Estimate
Dec 01 2026

Contingent

Note: Although AF1-296 may not presently have cost responsibility for this upgrade, AF1-296 may need this upgrade in-service to be deliverable to the PJM system. If AF1-296 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA

System Reinforcement: b3775.2
Type
Load Flow
TO
NextEra
RTEP ID / TO ID
b3775.2
Title
Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles).
Description
Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles).
Cost Information
Time Estimate
May 09 2023

Not Contingent

Note: AF1-296 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF1-296 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA
(All)C2280.0 MVA
(All)STE2107.0 MVA

System Reinforcement: b3775.3
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.3
Title
Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete
Description
Part of b3775 baseline. Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete (5 miles) with twin bundled 1277 ACAR conductor.
Cost Information
Time Estimate
Dec 01 2026

Contingent

Note: Although AF1-296 may not presently have cost responsibility for this upgrade, AF1-296 may need this upgrade in-service to be deliverable to the PJM system. If AF1-296 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA
(All)C2280.0 MVA
(All)STE2107.0 MVA

System Reinforcement: b3775.5
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.5
Title
Replace E. Frankfort 345 kV circuit breaker “9-14” with 3150A SF6 circuit breaker.
Description
Part of b3775 baseline. Replace E. Frankfort 345 kV circuit breaker “9-14” with 3150A SF6 circuit breaker.
Cost Information
Time Estimate
Oct 06 2025

Not Contingent

Note: AF1-296 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF1-296 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1826.0 MVA
(All)B2070.0 MVA
(All)C2390.0 MVA
SUMSTE2385.0 MVA

System Reinforcement: s3011
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
s3011 / CE_S3011
Title
Replace 345kV straight bus at TSS 116 Goodings Grove with a gas insulated switchgear ("GIS") breaker and a half configuration.
Description
Replace 345 kV open air straight bus with GIS in a breaker and half configuration (34 Circuit Breakers) at Goodings Grove with 80kA capability.
Cost Information
Time Estimate
Dec 31 2029

Not Contingent

Note: AF1-296 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AF1-296 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
(Any)COMED_P4_116-45-L11614__SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4-6_116-345-R______SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4_112-45-BT4-5___SRT-A
No new ratings for this Flowgate.

System Reinforcement: n5145
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n5145
Title
Reconfigure Wilton 765kV bus
Description
Reconfigure Wilton 765kV bus thereby allowing for 765kV L11216 (currently on Bus 6) to be relocated to Bus 8. Along with this line relocation, installation of 2-765kV BT CBs (6-8 & 8-2). Cost increased from $12M to $55M. This will eliminate the stuck breaker contingencies '112-65-BT4-5__' and '112-65-BT5-6__'. No other contingency updates needed.
Total Cost ($USD)
$55,229,373
Discounted Total Cost ($USD)
$55,229,373
Allocated Cost ($USD)
$0
Time Estimate
Jun 30 2026

Contingent

Note: Based on PJM cost allocation criteria, AF1-296 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AF1-296 may not have cost responsibility for this upgrade, AF1-296 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AF1-296 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
(Any)COMED_P4_112-65-BT4-5___SRT-A
No new ratings for this Flowgate.

System Reinforcement: b3775.4
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.4 / CE_B3775.4
Title
Rebuild 345 kV double circuit extending from Crete to E. Frankfort.
Description
Part of b3775 baseline. Rebuild 12.7 miles of 345 kV double circuit extending from Crete to E. Frankfort with twin bundled 1277 ACAR conductor.
Cost Information
Time Estimate
Jun 01 2026

Contingent

Note: Although AF1-296 may not presently have cost responsibility for this upgrade, AF1-296 may need this upgrade in-service to be deliverable to the PJM system. If AF1-296 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
(Any)765-L11215__-S_SRT-A
No new ratings for this Flowgate.
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA
(All)C2280.0 MVA
(All)STE2017.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AF1-296


AF1-296 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AF1-296 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AF1-296 One Line Diagram

AF1-296 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.