AF2-042 Final System Impact Study (Retool 2) Report

v2.00 released 2026-05-14 11:50

Clover-Rawlings 500 kV

300.0 MW Capacity / 500.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia), and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.

The AF2-042 Final System Impact Study (Retool 1) Report is available for download here.

Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed a Solar generating facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Halifax County, Virginia. The installed facilities will have a total capability of 500.0 MW with 300.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AF2-042
Project Name:
Clover-Rawlings 500 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
State:
Virginia
County:
Halifax
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
500.0
MWE:
500.0
MWC:
300.0
Fuel Type:
Solar
Basecase Study Year:
2027

Physical Interconnection Facility Study

Received

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AF2-042 will interconnect with the Dominion on transmission system tapping the Clover 500 kV to Rawlings 500kV line via a new three breaker switching station.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AF2-042 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AF2-042Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$2,167,703$2,167,703
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$26,741,335$26,741,335
Network Upgrades$9,550,378$9,550,378
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$133,083,749$133,083,749
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0
AFS - Non-PJM Violations$0 **$0 **
Total$171,543,165$171,543,165

* Contributes to calculation for Security. See Security Requirement Section of this report for additional detail.

** This value reflects the results at the time of the report posting and it is subject to change. AFS – Non-PJM Violations are not subject to Security. For latest AFS – Non-PJM Violations, please refer to the latest Affected System Study Report for your project.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF2-042

Security has been calculated for the AF2-042 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF2-042
Project(s): AF2-042
Final Agreement Security (A): $171,543,165
Portion of Costs Already Paid (B): $0
Revised Net Security (C): A − B = $171,543,165
Security on Hand with PJM (D): $350,964,054
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

The New Service Request Project will interconnect with the Dominion transmission system via a new three breaker ring bus switching station that connects on the Clover-Rawlings 500 kV Line.  The required work for the interconnection of the New Service Request Project to the Dominion Transmission System is detailed in the following tables.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n9410.0

Re-arrange line #556 to loop into and out of the new three-breaker AF2-042 500 kV switching station

$4,767,252$3,511,510$448,644$509,044$9,236,450$9,236,450
n9409.0

Remote Relay work at Clover Substation

$121,086$28,809$23,117$5,080$178,092$178,092
n9408.0

Remote Relay work at Finneywood Substation

$113,993$0$21,843$0$135,836$135,836
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n9411.0

Build a new 500 kV three-breaker ring switching station located along Dominion’s existing 500 kV, 556 line from Clover Substation to Finneywood Substation

$12,072,246$10,173,688$3,459,266$1,036,135$26,741,335$26,741,335
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Transmission Owner Interconnection Facilities

$1,102,355$676,479$306,021$82,848$2,167,703$2,167,703

Based on the scope of work for the Interconnection Facilities, it is expected to take 51 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

It is estimated to take 51 months to complete this work upon execution of the Generator Interconnection Agreement (GIA).This estimated time to complete is dependent on major equipment lead times. These preliminary cost estimates are based on typical engineering costs. A more detailed engineering cost estimates are normally done when the IC provides an exact site plan location for the generation substation during a future study phase.
 
Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.
 
Remote Terminal Work: During Phase 2 of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2027 load flow model and the results were verified by Dominion.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AF2-042 was evaluated as a 500.0 MW (300.0 MW Capacity) injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BUCKING-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S-1
BreakerAC116.15 %699.0C811.92163.51
GD1DVP
6BUCKING-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC112.88 %571.52B645.1298.0
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC109.81 %1204.0C1322.0856.68
GD1DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC108.01 %1204.0C1300.4256.68
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC141.99 %812.0C1152.9932.45
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC133.67 %663.64B887.0716.92
GD1DVP
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S-1
BreakerAC117.22 %684.0C801.79163.54
GD1DVP
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC113.89 %559.3B636.9998.02
GD1DVP
6POE-6TYLER1 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC103.31 %541.0C558.9131.26
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC110.41 %678.68B749.3624.29
GD1DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 56372_SRT-S
BreakerAC113.54 %1056.8C1199.8659.51
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC106.13 %3940.0C4181.52138.71
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC104.17 %3940.0C4104.33133.24
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H1T567_SRT-A
BreakerAC103.4 %3940.0C4073.91138.13
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC108.99 %3940.0C4294.13138.0
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC104.84 %3940.0C4130.73136.39
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S_SENS
BreakerAC102.96 %3940.0C4056.64131.7
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S_SENS
SingleAC101.85 %3220.44B3279.9777.5
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC102.49 %3144.0C3222.3797.65
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC102.39 %3144.0C3219.0897.2
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC102.39 %3144.0C3219.0897.2
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC102.38 %3144.0C3218.9297.2
GD1DVP
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC107.63 %678.68B730.4524.31

Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.15 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:811.92
MW Contribution:163.51
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.96 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:845.48
MW Contribution:167.15
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
Adder
-5.905882352941176-5.02
934622AD1-088 E
50/50
9.1029.102
3151531CLOVER1
50/50
22.49922.499
964242AG1-285 E
50/50
16.7716.77
937482AD2-202 E
Adder
1.86823529411764721.588
934612AD1-087 E
Adder
6.3835294117647065.426
924162AB2-060 E OP
Adder
7.6670588235294136.517
961792AG1-021 E
50/50
3.9843.984
3138533PONTONDP
50/50
1.7321.732
964792AG1-342 E
Adder
3.6952941176470593.141
927255AC1-221 E
Adder
4.1458823529411773.524
932763AC2-100 E
Adder
2.72941176470588242.32
941011AE2-092 C
Adder
-9.729411764705882-8.27
925785AC1-054 E
Adder
3.35529411764705852.852
959311AF2-222 C
50/50
38.90838.908
936261AD2-033 C
50/50
27.66927.669
3147133PAMPLIN
50/50
2.7572.757
3144293JTRSVLE
50/50
1.0761.076
961791AG1-021 C
50/50
4.6774.677
942462AE2-259 E
50/50
20.7620.76
962562AG1-105 E
Adder
9.4541176470588238.036
964791AG1-342 C
Adder
5.5435294117647054.712
924032AB2-045 E
50/50
5.85.8
316322AB2-045 C
50/50
1.2941.294
927264AC1-222 E
Adder
5.52000000000000054.692
925997AC1-075 E
Adder
3.31294117647058832.816
942751AE2-291 C
Adder
8.1482352941176476.926
964241AG1-285 C
50/50
25.15525.155
924022AB2-043 E O1
Adder
9.122352941176477.754
316034AC1-036 C
50/50
0.5350.535
3147223TWITTYS
50/50
2.1732.173
959312AF2-222 E
50/50
26.06826.068
924302AB2-077 E O1
Adder
2.3152941176470591.968
958212AF2-115 E
50/50
4.984.98
962561AG1-105 C
Adder
14.18117647058823612.054
926024AC1-080 E
Adder
1.09882352941176480.934
942752AE2-291 E
Adder
5.4329411764705894.618
957481AF2-042 C
50/50
98.10798.107
957482AF2-042 E
50/50
65.40565.405
934621AD1-088 C
50/50
18.90418.904
925612AC1-036 E
50/50
1.961.96
924322AB2-079 E O1
Adder
2.3152941176470591.968
924312AB2-078 E O1
Adder
2.3152941176470591.968
936262AD2-033 E
50/50
18.44618.446
946301AF1-294 C
50/50
9.6139.613
946302AF1-294 E
50/50
8.1418.141
958211AF2-115 C
50/50
5.8465.846
942461AE2-259 C
50/50
31.1431.14
935172AD1-152 E
Adder
8.887.548
926274AC1-105 E
Adder
4.0129411764705883.411
943902AF1-058 E
Adder
1.841.564
938821AE1-108 C
Adder
-10.607058823529412-9.016
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8050.805
SIGELTFEXP_SIGE->PJM
CLTF
0.0740.074
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1652.165
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.04736.047
CPLELTFEXP_CPLE->PJM
CLTF
4.5424.542
TVALTFEXP_TVA->PJM
CLTF
2.0142.014
O66PJM->LTFIMP_O-066
CMTX_NF
5.1335.133
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.3429.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.2887.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.2261.226
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
NYPJM->LTFIMP_NY
CLTF
0.3840.384
LGEELTFEXP_LGEE->PJM
CLTF
0.3670.367
WECLTFEXP_WEC->PJM
CLTF
0.1940.194

Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.88 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:645.12
MW Contribution:98.0
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.83 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:684.85
MW Contribution:100.17
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
Adder
-5.884705882352941-5.002
316087AB2-174 C
80/20
0.5880.588
932631AC2-084 C
80/20
0.3610.361
316274AC1-208 C
80/20
3.5413.541
316129AC1-054 C
80/20
1.1891.189
3151531CLOVER1
80/20
22.47122.471
934611AD1-087 C
80/20
2.212.21
313527AB2-043 C
80/20
0.9080.908
3151311EDGECMA
80/20
5.0375.037
316049AB1-081 C OP
80/20
0.4770.477
316131AB2-060 C
80/20
2.662.66
3151611KERR 4
80/20
1.5611.561
3151601KERR 3
80/20
1.5611.561
3151591KERR 2
80/20
1.5611.561
3151581KERR 1
80/20
0.5570.557
3138533PONTONDP
80/20
1.7311.731
316118AC1-105 C
80/20
1.3691.369
3152661PLYWOOD A
80/20
1.751.75
316283AC2-100 C
80/20
1.2351.235
941011AE2-092 C
Adder
-9.714117647058824-8.257
316217AC1-145 C
80/20
0.1690.169
3156073AA1-063SOLA
80/20
0.5840.584
316181AB2-040 GEN
80/20
0.6330.633
313506AB1-173 C OP
80/20
0.5620.562
3156063AA2-053SOLA
80/20
0.6790.679
3151371ROSEMS1
80/20
0.3840.384
3151361ROSEMG1
80/20
0.6210.621
3151381ROSEMG2
80/20
0.2910.291
3151281ROARAP4
80/20
0.6440.644
934321AD1-056 C
80/20
1.9781.978
934331AD1-057 C
80/20
1.1031.103
957481AF2-042 C
80/20
97.99997.999
934621AD1-088 C
80/20
18.88618.886
316359AB2-059 C OP
80/20
0.5620.562
316238AB2-078 C O1
80/20
0.5670.567
316237AB2-079 C O1
80/20
0.5670.567
946301AF1-294 C
80/20
9.6099.609
958211AF2-115 C
80/20
5.8435.843
942461AE2-259 C
80/20
31.13331.133
938821AE1-108 C
Adder
-10.596470588235293-9.007
316197AC1-042 C
80/20
0.1420.142
960081AF2-299 C
80/20
0.9410.941
3151391GASTONA
80/20
0.9230.923
316011AB1-132 C OP
80/20
0.7050.705
316210AC1-098 C
80/20
0.3390.339
316327AA2-057 C
80/20
0.4730.473
316263AC1-034 C
80/20
2.2292.229
3151631KERR 6
80/20
1.5611.561
959311AF2-222 C
80/20
38.88338.883
316239AB2-077 C O1
80/20
0.5670.567
936261AD2-033 C
80/20
27.64927.649
3144293JTRSVLE
80/20
1.0761.076
961791AG1-021 C
80/20
4.6754.675
935171AD1-152 C
80/20
2.1552.155
964791AG1-342 C
80/20
5.5355.535
316322AB2-045 C
80/20
1.2941.294
316248AF1-058 C
80/20
0.450.45
936171AD2-023 C
80/20
2.1112.111
942751AE2-291 C
80/20
8.1298.129
3151561HALLBR1
80/20
0.5580.558
941801AE2-185 C
80/20
1.9561.956
966621AG1-532 C
80/20
0.7060.706
946281AF1-292 C
80/20
0.7790.779
926071AC1-086 C
80/20
6.3516.351
3151411GASTONB
80/20
0.9230.923
3137643SOCKMAN
80/20
0.3520.352
3151261ROARAP2
80/20
0.6810.681
3147043LAWRENC
80/20
0.2660.266
316212AC1-099 C
80/20
0.1130.113
316319Z2-044 C
80/20
0.0740.074
3151541CLOVER2
80/20
22.26122.261
964241AG1-285 C
80/20
25.13225.132
937481AD2-202 C
80/20
0.6410.641
316034AC1-036 C
80/20
0.5340.534
3151641KERR 7
80/20
1.5611.561
3151621KERR 5
80/20
1.5611.561
962561AG1-105 C
80/20
14.16114.161
316222AC1-221 C
80/20
1.5791.579
316003AC1-222 C
80/20
1.3481.348
316205AC1-080 C
80/20
0.3190.319
316123AC1-075 C
80/20
0.9530.953
936161AD2-022 C
80/20
3.6193.619
942671AE2-283 C
80/20
1.5211.521
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1162.116
CBM South 2LTFEXP_CBM-S2->PJM
CBM
35.17235.172
CPLELTFEXP_CPLE->PJM
CLTF
4.444.44
TVALTFEXP_TVA->PJM
CLTF
1.9591.959
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.0479.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.0847.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1891.189
LAGNLTFEXP_LAGN->PJM
CLTF
2.5082.508
NYPJM->LTFIMP_NY
CLTF
0.3750.375
LGEELTFEXP_LGEE->PJM
CLTF
0.3550.355
WECLTFEXP_WEC->PJM
CLTF
0.1880.188

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.81 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1322.08
MW Contribution:56.68
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.0 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1396.59
MW Contribution:56.18
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316315AB2-025 C
50/50
0.4720.472
940492AE2-034 E
Adder
1.07647058823529430.915
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
934522AD1-076 E
Adder
2.43764705882352972.072
933982AD1-022 E
Adder
1.9647058823529411.67
943172AE2-346 E
Adder
0.30117647058823530.256
946282AF1-292 E
50/50
0.860.86
918492AA1-063AE OP
Adder
2.40470588235294122.044
316087AB2-174 C
50/50
0.9180.918
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
944012AF1-069 E
50/50
3.683.68
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
3143316POE
Adder
0.51176470588235290.435
3145413WATKINS
Adder
0.265882352941176460.226
920692AA2-178 E
Adder
1.43529411764705881.22
920042AA2-088 E OP
Adder
4.9317647058823534.192
934511AD1-075 C
Adder
3.2917647058823532.798
934521AD1-076 C
Adder
4.7823529411764714.065
316365AB2-100 C1
50/50
0.8890.889
960081AF2-299 C
50/50
1.5581.558
966622AG1-532 E
50/50
0.7790.779
3145723EMPORIA
50/50
0.3510.351
3151391GASTONA
50/50
2.2972.297
926072AC1-086 E
50/50
7.1937.193
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
919692AA2-053 E OP
Adder
2.6788235294117652.277
944011AF1-069 C
50/50
9.4749.474
926206AC1-098 E
Adder
2.14705882352941171.825
3152441Z1-086 ST
50/50
13.14613.146
963041AG1-153 C
50/50
3.9773.977
3151021BRUNSWICKG1
50/50
5.8715.871
3151041BRUNSWICKG3
50/50
5.8715.871
925785AC1-054 E
Adder
2.1505882352941181.828
922923AB1-081 E OP
Adder
2.24941176470588241.912
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
936261AD2-033 C
Adder
7.0082352941176475.957
3147133PAMPLIN
Adder
0.454117647058823570.386
961791AG1-021 C
Adder
0.83882352941176460.713
942462AE2-259 E
Adder
2.62.21
962562AG1-105 E
Adder
3.39764705882352922.888
964791AG1-342 C
Adder
2.0188235294117651.716
927264AC1-222 E
Adder
2.16588235294117661.841
925997AC1-075 E
Adder
1.36941176470588231.164
936171AD2-023 C
Adder
2.23058823529411751.896
932632AC2-084 E
Adder
1.89764705882352951.613
926214AC1-099 E
Adder
0.70941176470588230.603
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
316274AC1-208 C
Adder
5.5235294117647074.695
927146AC1-208 E
Adder
2.45294117647058842.085
3151051BRUNSWICKS1
50/50
12.19612.196
917512Z2-088 E OP1
Adder
2.742.329
917342Z2-044 E
Adder
0.36117647058823530.307
934622AD1-088 E
Adder
2.72588235294117662.317
964242AG1-285 E
Adder
5.0011764705882364.251
937482AD2-202 E
Adder
0.64705882352941180.55
934612AD1-087 E
Adder
2.20941176470588241.878
3151311EDGECMA
Adder
9.4070588235294137.996
924162AB2-060 E OP
Adder
2.522.142
961792AG1-021 E
Adder
0.71411764705882350.607
3138533PONTONDP
Adder
0.310588235294117660.264
964792AG1-342 E
Adder
1.34588235294117631.144
927255AC1-221 E
Adder
2.0517647058823531.744
932763AC2-100 E
Adder
1.3917647058823531.183
3145393UNCAMP
Adder
2.10941176470588231.793
939411AE1-173 C
Adder
49.7729411764705942.307
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
933981AD1-022 C
Adder
3.6082352941176473.067
316023AB2-100 C2
50/50
0.8890.889
924516AB2-100 E1
50/50
2.6782.678
900672V4-068 E
Adder
0.172941176470588240.147
918512AA1-065 E OP
Adder
2.60941176470588232.218
960082AF2-299 E
50/50
1.0391.039
966621AG1-532 C
50/50
1.1691.169
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
3151411GASTONB
50/50
2.2972.297
3137643SOCKMAN
50/50
0.5020.502
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
3151031BRUNSWICKG2
50/50
5.8715.871
963042AG1-153 E
50/50
5.9665.966
918532AA1-067 E
Adder
0.367058823529411770.312
919710AA2-057 E
Adder
2.3988235294117652.039
927021AC1-189 C
Adder
4.5788235294117653.892
964241AG1-285 C
Adder
7.502352941176476.377
924022AB2-043 E O1
Adder
3.07764705882352942.616
924152AB2-059 E OP
Adder
3.18705882352941172.709
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
924302AB2-077 E O1
Adder
0.7917647058823530.673
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
926024AC1-080 E
Adder
0.454117647058823570.386
936172AD2-023 E
Adder
1.21058823529411751.029
936161AD2-022 C
Adder
3.8235294117647063.25
942001AE2-212 C
Adder
-3.7917647058823527-3.223
923852AB2-025 E
50/50
1.3441.344
940541AE2-040 C
50/50
3.3223.322
940482AE2-033 E
50/50
12.29712.297
940481AE2-033 C
50/50
18.24118.241
939412AE1-173 E
Adder
33.1823529411764728.205
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
316141AB2-099 E
Adder
0.125882352941176470.107
961941AG1-037 C
Adder
0.251764705882352950.214
961942AG1-037 E
Adder
0.167058823529411760.142
316088AB2-174 E
50/50
5.0815.081
923263AB1-132 E OP
50/50
4.64.6
316181AB2-040 GEN
50/50
0.9590.959
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151371ROSEMS1
50/50
0.9320.932
3151361ROSEMG1
50/50
1.5051.505
3151381ROSEMG2
50/50
0.7050.705
3151281ROARAP4
50/50
0.8680.868
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934321AD1-056 C
Adder
4.1835294117647063.556
934332AD1-057 E
Adder
1.21529411764705891.033
934322AD1-056 E
Adder
2.26941176470588251.929
934331AD1-057 C
Adder
2.33411764705882341.984
927022AC1-189 E
Adder
2.28117647058823541.939
957481AF2-042 C
50/50
34.00834.008
957482AF2-042 E
50/50
22.67222.672
961672AG1-007 E
Adder
0.30352941176470590.258
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
925595AC1-034 E
Adder
3.0235294117647062.57
925612AC1-036 E
Adder
0.47058823529411770.4
924322AB2-079 E O1
Adder
0.7917647058823530.673
924312AB2-078 E O1
Adder
0.7917647058823530.673
936262AD2-033 E
Adder
4.6729411764705883.972
946301AF1-294 C
Adder
1.7247058823529411.466
946302AF1-294 E
Adder
1.46000000000000021.241
958211AF2-115 C
Adder
1.04823529411764720.891
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
926274AC1-105 E
Adder
1.50823529411764711.282
943902AF1-058 E
Adder
0.71411764705882350.607
936162AD2-022 E
Adder
2.29411764705882341.95
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.01 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1300.42
MW Contribution:56.68
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.2 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1374.95
MW Contribution:56.18
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
3143316POE
Adder
0.51176470588235290.435
3145413WATKINS
Adder
0.265882352941176460.226
920692AA2-178 E
Adder
1.43529411764705881.22
920042AA2-088 E OP
Adder
4.9317647058823534.192
934511AD1-075 C
Adder
3.2917647058823532.798
934521AD1-076 C
Adder
4.7823529411764714.065
316365AB2-100 C1
50/50
0.8890.889
960081AF2-299 C
50/50
1.5581.558
966622AG1-532 E
50/50
0.7790.779
3145723EMPORIA
50/50
0.3510.351
3151391GASTONA
50/50
2.2972.297
926072AC1-086 E
50/50
7.1937.193
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
919692AA2-053 E OP
Adder
2.6788235294117652.277
944011AF1-069 C
50/50
9.4749.474
926206AC1-098 E
Adder
2.14705882352941171.825
3152441Z1-086 ST
50/50
13.14613.146
963041AG1-153 C
50/50
3.9773.977
3151021BRUNSWICKG1
50/50
5.8715.871
3151041BRUNSWICKG3
50/50
5.8715.871
925785AC1-054 E
Adder
2.1505882352941181.828
922923AB1-081 E OP
Adder
2.24941176470588241.912
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
936261AD2-033 C
Adder
7.0082352941176475.957
3147133PAMPLIN
Adder
0.454117647058823570.386
961791AG1-021 C
Adder
0.83882352941176460.713
942462AE2-259 E
Adder
2.62.21
962562AG1-105 E
Adder
3.39764705882352922.888
964791AG1-342 C
Adder
2.0188235294117651.716
927264AC1-222 E
Adder
2.16588235294117661.841
925997AC1-075 E
Adder
1.36941176470588231.164
936171AD2-023 C
Adder
2.23058823529411751.896
316315AB2-025 C
50/50
0.4720.472
940492AE2-034 E
Adder
1.07647058823529430.915
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
934522AD1-076 E
Adder
2.43764705882352972.072
933982AD1-022 E
Adder
1.9647058823529411.67
943172AE2-346 E
Adder
0.30117647058823530.256
946282AF1-292 E
50/50
0.860.86
918492AA1-063AE OP
Adder
2.40470588235294122.044
316087AB2-174 C
50/50
0.9180.918
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
944012AF1-069 E
50/50
3.683.68
932632AC2-084 E
Adder
1.89764705882352951.613
926214AC1-099 E
Adder
0.70941176470588230.603
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
316274AC1-208 C
Adder
5.5235294117647074.695
927146AC1-208 E
Adder
2.45294117647058842.085
3151051BRUNSWICKS1
50/50
12.19612.196
917512Z2-088 E OP1
Adder
2.742.329
917342Z2-044 E
Adder
0.36117647058823530.307
934622AD1-088 E
Adder
2.72588235294117662.317
964242AG1-285 E
Adder
5.0011764705882364.251
937482AD2-202 E
Adder
0.64705882352941180.55
934612AD1-087 E
Adder
2.20941176470588241.878
3151311EDGECMA
Adder
9.4070588235294137.996
924162AB2-060 E OP
Adder
2.522.142
961792AG1-021 E
Adder
0.71411764705882350.607
3138533PONTONDP
Adder
0.310588235294117660.264
964792AG1-342 E
Adder
1.34588235294117631.144
927255AC1-221 E
Adder
2.0517647058823531.744
932763AC2-100 E
Adder
1.3917647058823531.183
3145393UNCAMP
Adder
2.10941176470588231.793
939411AE1-173 C
Adder
49.7729411764705942.307
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
933981AD1-022 C
Adder
3.6082352941176473.067
316023AB2-100 C2
50/50
0.8890.889
924516AB2-100 E1
50/50
2.6782.678
900672V4-068 E
Adder
0.172941176470588240.147
918512AA1-065 E OP
Adder
2.60941176470588232.218
960082AF2-299 E
50/50
1.0391.039
966621AG1-532 C
50/50
1.1691.169
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
3151411GASTONB
50/50
2.2972.297
3137643SOCKMAN
50/50
0.5020.502
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
3151031BRUNSWICKG2
50/50
5.8715.871
963042AG1-153 E
50/50
5.9665.966
918532AA1-067 E
Adder
0.367058823529411770.312
919710AA2-057 E
Adder
2.3988235294117652.039
927021AC1-189 C
Adder
4.5788235294117653.892
964241AG1-285 C
Adder
7.502352941176476.377
924022AB2-043 E O1
Adder
3.07764705882352942.616
924152AB2-059 E OP
Adder
3.18705882352941172.709
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
924302AB2-077 E O1
Adder
0.7917647058823530.673
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
926024AC1-080 E
Adder
0.454117647058823570.386
936172AD2-023 E
Adder
1.21058823529411751.029
936161AD2-022 C
Adder
3.8235294117647063.25
942001AE2-212 C
Adder
-3.7917647058823527-3.223
923852AB2-025 E
50/50
1.3441.344
940541AE2-040 C
50/50
3.3223.322
940482AE2-033 E
50/50
12.29712.297
940481AE2-033 C
50/50
18.24118.241
939412AE1-173 E
Adder
33.1823529411764728.205
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
316141AB2-099 E
Adder
0.125882352941176470.107
961941AG1-037 C
Adder
0.251764705882352950.214
961942AG1-037 E
Adder
0.167058823529411760.142
316088AB2-174 E
50/50
5.0815.081
923263AB1-132 E OP
50/50
4.64.6
316181AB2-040 GEN
50/50
0.9590.959
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151371ROSEMS1
50/50
0.9320.932
3151361ROSEMG1
50/50
1.5051.505
3151381ROSEMG2
50/50
0.7050.705
3151281ROARAP4
50/50
0.8680.868
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934321AD1-056 C
Adder
4.1835294117647063.556
934332AD1-057 E
Adder
1.21529411764705891.033
934322AD1-056 E
Adder
2.26941176470588251.929
934331AD1-057 C
Adder
2.33411764705882341.984
927022AC1-189 E
Adder
2.28117647058823541.939
957481AF2-042 C
50/50
34.00834.008
957482AF2-042 E
50/50
22.67222.672
961672AG1-007 E
Adder
0.30352941176470590.258
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
925595AC1-034 E
Adder
3.0235294117647062.57
925612AC1-036 E
Adder
0.47058823529411770.4
924322AB2-079 E O1
Adder
0.7917647058823530.673
924312AB2-078 E O1
Adder
0.7917647058823530.673
936262AD2-033 E
Adder
4.6729411764705883.972
946301AF1-294 C
Adder
1.7247058823529411.466
946302AF1-294 E
Adder
1.46000000000000021.241
958211AF2-115 C
Adder
1.04823529411764720.891
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
926274AC1-105 E
Adder
1.50823529411764711.282
943902AF1-058 E
Adder
0.71411764705882350.607
936162AD2-022 E
Adder
2.29411764705882341.95
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.99 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1152.99
MW Contribution:32.45
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.71 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1061.35
MW Contribution:32.32
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
50/50
25.13725.137
946262AF1-291 E
50/50
1.8721.872
3150761HOPPOLC
50/50
1.0581.058
934576AD1-082 E
50/50
2.7072.707
316084AB2-161 E
50/50
3.3973.397
316083AB2-161 C
50/50
0.340.34
3145256KINGFORK
Adder
0.33882352941176470.288
925522AC1-027 E
Adder
0.380.323
944602AF1-125 E
Adder
31.17176470588235326.496
941102AE2-104 E
Adder
1.98470588235294131.687
3145506HICKORY
Adder
0.6682352941176470.568
943612AF1-032 E
Adder
0.30705882352941180.261
957871AF2-081 C
Adder
3.10588235294117652.64
957872AF2-081 E
Adder
1.33058823529411761.131
316315AB2-025 C
50/50
0.2520.252
940492AE2-034 E
Adder
1.08941176470588250.926
3145946PLYMOUTH TP
Adder
0.116470588235294130.099
934522AD1-076 E
Adder
2.2623529411764711.923
933982AD1-022 E
Adder
1.75647058823529421.493
943172AE2-346 E
Adder
0.238823529411764740.203
946282AF1-292 E
Adder
0.50.425
918492AA1-063AE OP
Adder
1.7070588235294121.451
917332KELFORD E
Adder
0.65058823529411770.553
925122AB2-169 E
Adder
2.1235294117647061.805
944012AF1-069 E
Adder
2.1552941176470591.832
932632AC2-084 E
Adder
1.2988235294117651.104
926214AC1-099 E
Adder
0.484705882352941150.412
316274AC1-208 C
Adder
3.6705882352941183.12
927146AC1-208 E
Adder
1.62941176470588231.385
917512Z2-088 E OP1
Adder
1.88000000000000011.598
917342Z2-044 E
Adder
0.235294117647058850.2
934622AD1-088 E
Adder
1.53176470588235311.302
964242AG1-285 E
Adder
2.7964705882352942.377
937482AD2-202 E
Adder
0.36941176470588240.314
934612AD1-087 E
Adder
1.26235294117647071.073
3151311EDGECMA
Adder
6.0682352941176485.158
924162AB2-060 E OP
Adder
1.41882352941176461.206
964792AG1-342 E
Adder
0.76588235294117660.651
3150781HOPHCF2
50/50
1.6821.682
3150791HOPHCF3
50/50
1.6821.682
3150771HOPHCF1
50/50
1.6821.682
940431AE2-027 C
Adder
5.5282352941176474.699
942001AE2-212 C
50/50
2.3882.388
942002AE2-212 E
50/50
1.5921.592
316132AB2-190 C
50/50
2.4992.499
961611AG1-000B C
Adder
7.286.188
939192AE1-149 E
50/50
5.125.12
939312AE1-162 E
Adder
0.54941176470588240.467
926662AC1-147 E
Adder
0.420.357
916192Z1-068 E
Adder
0.58588235294117650.498
934065AD1-033 E
Adder
1.53411764705882361.304
944581AF1-123 C
Adder
13.82941176470588311.755
941101AE2-104 C
Adder
1.2482352941176471.061
957492AF2-043 E
Adder
0.4717647058823530.401
937226AE2-253 E
Adder
1.80588235294117651.535
923852AB2-025 E
50/50
0.7170.717
940541AE2-040 C
50/50
1.7731.773
940482AE2-033 E
50/50
6.6116.611
940481AE2-033 C
50/50
9.8069.806
939412AE1-173 E
Adder
23.37764705882352719.871
934501AD1-074 C
Adder
12.22470588235294110.391
924517AB2-100 E2
Adder
1.5282352941176471.299
316141AB2-099 E
Adder
0.098823529411764710.084
961941AG1-037 C
Adder
0.198823529411764730.169
961942AG1-037 E
Adder
0.132941176470588230.113
316088AB2-174 E
Adder
3.04352941176470632.587
923263AB1-132 E OP
Adder
2.8364705882352942.411
923994AB2-040_E
Adder
2.8235294117647062.4
941032AE2-094 E
Adder
7.6070588235294126.466
941031AE2-094 C
Adder
16.9847058823529414.437
934321AD1-056 C
Adder
2.642.244
934332AD1-057 E
Adder
0.76705882352941180.652
934322AD1-056 E
Adder
1.4317647058823531.217
934331AD1-057 C
Adder
1.47294117647058821.252
927022AC1-189 E
Adder
1.59882352941176481.359
957481AF2-042 C
Adder
19.4705882352941216.55
957482AF2-042 E
Adder
12.9811.033
961672AG1-007 E
Adder
0.204705882352941150.174
961671AG1-007 C
Adder
0.36235294117647060.308
934621AD1-088 C
Adder
3.18117647058823572.704
925595AC1-034 E
Adder
1.95294117647058821.66
944641AF1-129 C
50/50
138.059138.059
316240AF1-291 C
50/50
2.8082.808
925332AB2-190 E
50/50
4.8614.861
935162AD1-151 E
50/50
6.1926.192
927226AC1-216 E
Adder
4.2082352941176473.577
924814AB2-134 E
Adder
6.8941176470588245.86
939191AE1-149 C
50/50
7.6817.681
3143316POE
50/50
1.2311.231
316381AD1-082 C
50/50
0.7750.775
943461AF1-017 C
Adder
0.6317647058823530.537
942342AE2-247 E
Adder
0.96470588235294120.82
936666AD2-085 E
Adder
2.62823529411764722.234
932596AC2-079 E
Adder
4.2658823529411763.626
316311AC2-079 C
Adder
2.61529411764705882.223
941591AE2-156 C
Adder
5.6635294117647064.814
944601AF1-125 C
Adder
13.61647058823529511.574
944591AF1-124 C
Adder
13.87882352941176711.797
919152AA1-139 E1
Adder
1.27058823529411781.08
938532AE1-072 E
Adder
2.8635294117647062.434
3146326AYDLETT TAP
Adder
0.424705882352941160.361
917122Z2-027 E
Adder
0.435294117647058830.37
901082W1-029 E
Adder
10.5541176470588248.971
938771AE1-103 C
Adder
1.1282352941176470.959
3145413WATKINS
Adder
0.271764705882352960.231
920692AA2-178 E
Adder
1.45294117647058841.235
920042AA2-088 E OP
Adder
4.2552941176470593.617
934511AD1-075 C
Adder
3.0564705882352942.598
934521AD1-076 C
Adder
4.443.774
960081AF2-299 C
Adder
0.90588235294117650.77
966622AG1-532 E
Adder
0.452941176470588240.385
3145723EMPORIA
Adder
0.205882352941176460.175
926072AC1-086 E
Adder
4.4364705882352943.771
923573AB1-173 E OP
Adder
1.50588235294117641.28
919692AA2-053 E OP
Adder
1.7835294117647061.516
944011AF1-069 C
Adder
5.5494117647058824.717
926206AC1-098 E
Adder
1.4682352941176471.248
963041AG1-153 C
Adder
2.32823529411764741.979
925785AC1-054 E
Adder
1.32352941176470581.125
922923AB1-081 E OP
Adder
1.45294117647058841.235
316263AC1-034 C
Adder
2.5882352941176472.2
962562AG1-105 E
Adder
1.93058823529411771.641
964791AG1-342 C
Adder
1.1482352941176470.976
3150801HOPHCF4
50/50
2.5532.553
3150731STONECA
50/50
4.7614.761
940432AE2-027 E
Adder
3.68588235294117663.133
935161AD1-151 C
50/50
9.2889.288
934012AD1-025 E
Adder
5.4482352941176474.631
942341AE2-247 C
Adder
0.69882352941176470.594
316349AD2-085 C
Adder
1.61058823529411771.369
943462AF1-017 E
Adder
1.03058823529411760.876
935112AD1-144 E
Adder
0.315294117647058840.268
932046AC2-012 E
Adder
4.1552941176470593.532
944582AF1-123 E
Adder
31.66823529411764726.918
944592AF1-124 E
Adder
31.78352941176470427.016
958161AF2-110 C
Adder
0.50941176470588230.433
958162AF2-110 E
Adder
0.81058823529411760.689
919153AA1-139 E2
Adder
1.27058823529411781.08
938531AE1-072 C
Adder
5.49411764705882364.67
913392Y1-086 E
Adder
0.70470588235294120.599
923832AB2-022 E
Adder
0.397647058823529460.338
938772AE1-103 E
Adder
1.55882352941176471.325
916042Z1-036 E
Adder
9.7517647058823538.289
3145393UNCAMP
Adder
2.362.006
939411AE1-173 C
Adder
35.0670588235294129.807
934512AD1-075 E
Adder
1.5552941176470591.322
934502AD1-074 E
Adder
6.222352941176475.289
933981AD1-022 C
Adder
3.22705882352941182.743
924516AB2-100 E1
Adder
1.5282352941176471.299
900672V4-068 E
Adder
0.14235294117647060.121
918512AA1-065 E OP
Adder
2.12470588235294141.806
960082AF2-299 E
Adder
0.60352941176470590.513
966621AG1-532 C
Adder
0.67999999999999990.578
946281AF1-292 C
Adder
0.74941176470588230.637
926071AC1-086 C
Adder
9.7470588235294138.285
3137643SOCKMAN
Adder
0.315294117647058840.268
963042AG1-153 E
Adder
3.4917647058823532.968
918532AA1-067 E
Adder
0.269411764705882350.229
919710AA2-057 E
Adder
1.58117647058823541.344
927021AC1-189 C
Adder
3.2094117647058832.728
964241AG1-285 C
Adder
4.1952941176470593.566
924022AB2-043 E O1
Adder
1.73764705882352951.477
924152AB2-059 E OP
Adder
2.0588235294117651.75
924302AB2-077 E O1
Adder
0.448235294117647070.381
962561AG1-105 C
Adder
2.89529411764705862.461
924322AB2-079 E O1
Adder
0.448235294117647070.381
924312AB2-078 E O1
Adder
0.448235294117647070.381
935172AD1-152 E
Adder
1.86235294117647051.583
926274AC1-105 E
Adder
0.860.731
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9850.985
SIGELTFEXP_SIGE->PJM
CLTF
0.0650.065
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.8981.898
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.93631.936
CPLELTFEXP_CPLE->PJM
CLTF
3.9843.984
TVALTFEXP_TVA->PJM
CLTF
1.811.81
O66PJM->LTFIMP_O-066
CMTX_NF
6.2766.276
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.0758.075
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.5166.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.081.08
LAGNLTFEXP_LAGN->PJM
CLTF
2.3232.323
NYPJM->LTFIMP_NY
CLTF
0.4640.464
LGEELTFEXP_LGEE->PJM
CLTF
0.3190.319
WECLTFEXP_WEC->PJM
CLTF
0.1690.169

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.67 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:887.07
MW Contribution:16.92
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.35 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:918.17
MW Contribution:16.76
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
25.04225.042
3150761HOPPOLC
80/20
1.0681.068
316083AB2-161 C
80/20
0.340.34
933291AC2-141 C
Adder
9.0470588235294127.69
957871AF2-081 C
Adder
3.42823529411764752.914
316315AB2-025 C
80/20
0.2380.238
3151151S HAMPT1
80/20
0.5930.593
940641AE2-051 C
80/20
6.3516.351
316336AC2-165 C
Adder
-2.925882352941177-2.487
316087AB2-174 C
80/20
0.5210.521
3152431Z1-086 GT3
80/20
3.8323.832
3152421Z1-086 GT2
80/20
3.8323.832
316274AC1-208 C
Adder
3.50823529411764762.982
3151051BRUNSWICKS1
80/20
6.1926.192
3151311EDGECMA
Adder
5.7282352941176474.869
3150781HOPHCF2
80/20
1.6981.698
3150791HOPHCF3
80/20
1.6981.698
3150771HOPHCF1
80/20
1.6981.698
940431AE2-027 C
80/20
5.4285.428
942001AE2-212 C
80/20
2.3582.358
316132AB2-190 C
80/20
2.552.55
316369AC1-216 C
80/20
0.90.9
961611AG1-000B C
80/20
7.6267.626
316236AE1-162 C
80/20
0.1440.144
944581AF1-123 C
Adder
15.41882352941176613.106
941101AE2-104 C
80/20
1.3111.311
940541AE2-040 C
80/20
1.6761.676
940481AE2-033 C
80/20
9.2759.275
3156083AA2-088SOLA
80/20
0.4240.424
934501AD1-074 C
Adder
12.4576470588235310.589
961941AG1-037 C
Adder
0.196470588235294150.167
3156073AA1-063SOLA
80/20
0.570.57
316181AB2-040 GEN
80/20
0.5530.553
313506AB1-173 C OP
80/20
0.4910.491
3156063AA2-053SOLA
80/20
0.6110.611
3151371ROSEMS1
80/20
0.5510.551
3151361ROSEMG1
80/20
0.8890.889
3151381ROSEMG2
80/20
0.4160.416
3151281ROARAP4
80/20
0.5360.536
941031AE2-094 C
80/20
14.70614.706
934321AD1-056 C
Adder
2.50705882352941162.131
934331AD1-057 C
Adder
1.39882352941176481.189
957481AF2-042 C
Adder
16.9176470588235314.38
961671AG1-007 C
Adder
0.34588235294117650.294
934621AD1-088 C
Adder
2.76235294117647052.348
944641AF1-129 C
80/20
137.537137.537
316240AF1-291 C
80/20
2.7922.792
316033AB2-134 GEN
80/20
1.1791.179
934011AD1-025 C
80/20
1.4591.459
939191AE1-149 C
80/20
7.67.6
3151191GRAVEL3
80/20
1.1271.127
3151161SURRY 1
80/20
11.09811.098
3151211GRAVEL5
80/20
1.1271.127
316381AD1-082 C
80/20
0.7760.776
943461AF1-017 C
80/20
0.6470.647
316311AC2-079 C
80/20
2.6862.686
941591AE2-156 C
Adder
6.2764705882352945.335
944601AF1-125 C
Adder
15.18117647058823612.904
944591AF1-124 C
Adder
15.47294117647058813.152
938771AE1-103 C
80/20
1.1561.156
934511AD1-075 C
Adder
3.1141176470588232.647
934521AD1-076 C
Adder
4.5247058823529423.846
316365AB2-100 C1
80/20
0.4810.481
960081AF2-299 C
80/20
0.8560.856
3151391GASTONA
80/20
1.3541.354
316011AB1-132 C OP
80/20
1.0341.034
944011AF1-069 C
80/20
4.8054.805
3152441Z1-086 ST
80/20
6.6726.672
963041AG1-153 C
Adder
2.0188235294117651.716
3151021BRUNSWICKG1
80/20
2.9812.981
3151041BRUNSWICKG3
80/20
2.9812.981
316263AC1-034 C
Adder
2.44235294117647062.076
3150801HOPHCF4
80/20
2.5772.577
3150731STONECA
80/20
4.8074.807
935161AD1-151 C
80/20
9.5159.515
3151171GRAVELC
80/20
0.3880.388
3151221GRAVEL6
80/20
1.141.14
3151201GRAVEL4
80/20
1.1421.142
942341AE2-247 C
80/20
0.7150.715
316349AD2-085 C
80/20
1.6511.651
958161AF2-110 C
80/20
0.5350.535
938531AE1-072 C
Adder
6.04588235294117655.139
939411AE1-173 C
80/20
32.73632.736
933981AD1-022 C
Adder
3.26941176470588252.779
316023AB2-100 C2
80/20
0.4810.481
966621AG1-532 C
80/20
0.6420.642
946281AF1-292 C
80/20
0.7080.708
926071AC1-086 C
80/20
9.3179.317
3151411GASTONB
80/20
1.3541.354
3137643SOCKMAN
80/20
0.30.3
3151261ROARAP2
80/20
0.5670.567
3147043LAWRENC
80/20
0.1270.127
3152411Z1-086 GT1
80/20
3.8333.833
3151031BRUNSWICKG2
80/20
2.9812.981
927021AC1-189 C
Adder
3.0858823529411772.623
SIGELTFEXP_SIGE->PJM
CLTF
0.0560.056
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7131.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.64628.646
CPLELTFEXP_CPLE->PJM
CLTF
3.5953.595
TVALTFEXP_TVA->PJM
CLTF
1.6011.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.8996.899
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.7315.731
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.9380.938
LAGNLTFEXP_LAGN->PJM
CLTF
2.0572.057
NYPJM->LTFIMP_NY
CLTF
0.4310.431
LGEELTFEXP_LGEE->PJM
CLTF
0.2740.274
WECLTFEXP_WEC->PJM
CLTF
0.1450.145

Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.22 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:801.79
MW Contribution:163.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.59 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:831.68
MW Contribution:167.18
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
946282AF1-292 E
Adder
0.51882352941176470.441
316336AC2-165 C
Adder
-5.9023529411764715-5.017
934622AD1-088 E
50/50
9.1039.103
3151531CLOVER1
50/50
22.50322.503
964242AG1-285 E
50/50
16.77316.773
937482AD2-202 E
Adder
1.86823529411764721.588
934612AD1-087 E
Adder
6.3847058823529415.427
924162AB2-060 E OP
Adder
7.6694117647058836.519
961792AG1-021 E
50/50
3.9843.984
3138533PONTONDP
50/50
1.7321.732
964792AG1-342 E
Adder
3.6964705882352943.142
927255AC1-221 E
Adder
4.1470588235294123.525
932763AC2-100 E
Adder
2.7305882352941182.321
941011AE2-092 C
Adder
-9.724705882352941-8.266
960081AF2-299 C
Adder
0.94000000000000010.799
966622AG1-532 E
Adder
0.47058823529411770.4
3145723EMPORIA
Adder
0.21647058823529410.184
925785AC1-054 E
Adder
3.35647058823529452.853
959311AF2-222 C
50/50
38.91438.914
936261AD2-033 C
50/50
27.67327.673
3147133PAMPLIN
50/50
2.7572.757
3144293JTRSVLE
50/50
1.0761.076
961791AG1-021 C
50/50
4.6774.677
942462AE2-259 E
50/50
20.76320.763
962562AG1-105 E
Adder
9.4564705882352958.038
964791AG1-342 C
Adder
5.5447058823529414.713
927264AC1-222 E
Adder
5.5211764705882354.693
925997AC1-075 E
Adder
3.3141176470588242.817
942751AE2-291 C
Adder
8.1517647058823536.929
960082AF2-299 E
Adder
0.62705882352941180.533
966621AG1-532 C
Adder
0.70470588235294120.599
946281AF1-292 C
Adder
0.77764705882352950.661
964241AG1-285 C
50/50
25.15925.159
924022AB2-043 E O1
Adder
9.1247058823529417.756
316034AC1-036 C
50/50
0.5350.535
3147223TWITTYS
50/50
2.1732.173
959312AF2-222 E
50/50
26.07226.072
924302AB2-077 E O1
Adder
2.3164705882352941.969
958212AF2-115 E
50/50
4.9814.981
962561AG1-105 C
Adder
14.18352941176470612.056
926024AC1-080 E
Adder
1.10.935
942752AE2-291 E
Adder
5.4352941176470594.62
957481AF2-042 C
50/50
98.12598.125
957482AF2-042 E
50/50
65.41765.417
934621AD1-088 C
50/50
18.90718.907
925612AC1-036 E
50/50
1.961.96
924322AB2-079 E O1
Adder
2.3164705882352941.969
924312AB2-078 E O1
Adder
2.3164705882352941.969
936262AD2-033 E
50/50
18.44918.449
946301AF1-294 C
50/50
9.6159.615
946302AF1-294 E
50/50
8.1428.142
958211AF2-115 C
50/50
5.8475.847
942461AE2-259 C
50/50
31.14431.144
935172AD1-152 E
Adder
8.8823529411764717.55
926274AC1-105 E
Adder
4.0141176470588233.412
943902AF1-058 E
Adder
1.841.564
938821AE1-108 C
Adder
-10.602352941176472-9.012
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7990.799
SIGELTFEXP_SIGE->PJM
CLTF
0.0750.075
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1672.167
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.10836.108
CPLELTFEXP_CPLE->PJM
CLTF
4.5484.548
TVALTFEXP_TVA->PJM
CLTF
2.0222.022
O66PJM->LTFIMP_O-066
CMTX_NF
5.0935.093
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.4439.443
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.3277.327
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.2351.235
LAGNLTFEXP_LAGN->PJM
CLTF
2.5882.588
NYPJM->LTFIMP_NY
CLTF
0.3810.381
LGEELTFEXP_LGEE->PJM
CLTF
0.370.37
WECLTFEXP_WEC->PJM
CLTF
0.1960.196

Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.89 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:636.99
MW Contribution:98.02
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.98 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:676.62
MW Contribution:100.19
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
Adder
-5.881176470588235-4.999
316087AB2-174 C
80/20
0.5890.589
932631AC2-084 C
80/20
0.3610.361
316274AC1-208 C
80/20
3.5443.544
316129AC1-054 C
80/20
1.1891.189
3151531CLOVER1
80/20
22.47622.476
934611AD1-087 C
80/20
2.212.21
313527AB2-043 C
80/20
0.9080.908
3151311EDGECMA
80/20
5.0435.043
316049AB1-081 C OP
80/20
0.4780.478
316131AB2-060 C
80/20
2.6612.661
3151611KERR 4
80/20
1.5621.562
3151601KERR 3
80/20
1.5621.562
3151591KERR 2
80/20
1.5621.562
3151581KERR 1
80/20
0.5580.558
3138533PONTONDP
80/20
1.7321.732
316118AC1-105 C
80/20
1.3691.369
3152661PLYWOOD A
80/20
1.751.75
316283AC2-100 C
80/20
1.2351.235
941011AE2-092 C
Adder
-9.709411764705882-8.253
316217AC1-145 C
80/20
0.1690.169
3156073AA1-063SOLA
80/20
0.5850.585
316181AB2-040 GEN
80/20
0.6330.633
313506AB1-173 C OP
80/20
0.5620.562
3156063AA2-053SOLA
80/20
0.680.68
3151371ROSEMS1
80/20
0.3850.385
3151361ROSEMG1
80/20
0.6210.621
3151381ROSEMG2
80/20
0.2910.291
3151281ROARAP4
80/20
0.6450.645
934321AD1-056 C
80/20
1.981.98
934331AD1-057 C
80/20
1.1051.105
957481AF2-042 C
80/20
98.01698.016
934621AD1-088 C
80/20
18.88918.889
316359AB2-059 C OP
80/20
0.5630.563
316238AB2-078 C O1
80/20
0.5670.567
316237AB2-079 C O1
80/20
0.5670.567
946301AF1-294 C
80/20
9.619.61
958211AF2-115 C
80/20
5.8445.844
942461AE2-259 C
80/20
31.13731.137
938821AE1-108 C
Adder
-10.591764705882353-9.003
316197AC1-042 C
80/20
0.1420.142
960081AF2-299 C
80/20
0.9420.942
3151391GASTONA
80/20
0.9240.924
316011AB1-132 C OP
80/20
0.7060.706
316210AC1-098 C
80/20
0.3390.339
316327AA2-057 C
80/20
0.4730.473
316263AC1-034 C
80/20
2.2322.232
3151631KERR 6
80/20
1.5621.562
959311AF2-222 C
80/20
38.88938.889
316239AB2-077 C O1
80/20
0.5670.567
936261AD2-033 C
80/20
27.65427.654
3144293JTRSVLE
80/20
1.0761.076
961791AG1-021 C
80/20
4.6754.675
935171AD1-152 C
80/20
2.1562.156
964791AG1-342 C
80/20
5.5375.537
316248AF1-058 C
80/20
0.450.45
936171AD2-023 C
80/20
2.1132.113
942751AE2-291 C
80/20
8.1328.132
3151561HALLBR1
80/20
0.5580.558
941801AE2-185 C
80/20
1.9581.958
966621AG1-532 C
80/20
0.7060.706
946281AF1-292 C
80/20
0.7790.779
926071AC1-086 C
80/20
6.3586.358
3151411GASTONB
80/20
0.9240.924
3137643SOCKMAN
80/20
0.3530.353
3151261ROARAP2
80/20
0.6820.682
3147043LAWRENC
80/20
0.2660.266
316212AC1-099 C
80/20
0.1140.114
316319Z2-044 C
80/20
0.0740.074
3151541CLOVER2
80/20
22.26622.266
964241AG1-285 C
80/20
25.13725.137
937481AD2-202 C
80/20
0.6410.641
316034AC1-036 C
80/20
0.5340.534
3151641KERR 7
80/20
1.5621.562
3151621KERR 5
80/20
1.5621.562
962561AG1-105 C
80/20
14.16414.164
316222AC1-221 C
80/20
1.581.58
316003AC1-222 C
80/20
1.3491.349
316205AC1-080 C
80/20
0.3190.319
316123AC1-075 C
80/20
0.9540.954
936161AD2-022 C
80/20
3.6223.622
942671AE2-283 C
80/20
1.5231.523
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1192.119
CBM South 2LTFEXP_CBM-S2->PJM
CBM
35.23335.233
CPLELTFEXP_CPLE->PJM
CLTF
4.4464.446
TVALTFEXP_TVA->PJM
CLTF
1.9681.968
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.1489.148
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.1237.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1991.199
LAGNLTFEXP_LAGN->PJM
CLTF
2.5182.518
NYPJM->LTFIMP_NY
CLTF
0.3720.372
LGEELTFEXP_LGEE->PJM
CLTF
0.3590.359
WECLTFEXP_WEC->PJM
CLTF
0.190.19

Details for 6POE-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6POE-6TYLER1 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.31 %
Rating:541.0 MVA
Rating Type:C
MVA to Mitigate:558.91
MW Contribution:31.26
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6POE-6TYLER1 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.59 %
Rating:541.0 MVA
Rating Type:C
MVA to Mitigate:587.46
MW Contribution:30.92
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944641AF1-129 C
Adder
-70.29176470588236-59.748
316240AF1-291 C
Adder
-2.144705882352941-1.823
939191AE1-149 C
50/50
11.48911.489
3143316POE
50/50
2.8062.806
316381AD1-082 C
50/50
1.0531.053
943461AF1-017 C
Adder
0.66588235294117650.566
942342AE2-247 E
Adder
1.01647058823529420.864
936666AD2-085 E
Adder
2.77176470588235272.356
932596AC2-079 E
Adder
4.3541176470588243.701
316311AC2-079 C
Adder
2.6682352941176472.268
938771AE1-103 C
Adder
0.87058823529411770.74
3145413WATKINS
Adder
0.215294117647058830.183
920042AA2-088 E OP
Adder
3.4941176470588242.97
960081AF2-299 C
Adder
0.86705882352941180.737
966622AG1-532 E
Adder
0.434117647058823550.369
3145723EMPORIA
Adder
0.196470588235294150.167
926072AC1-086 E
Adder
4.0752941176470593.464
923573AB1-173 E OP
Adder
1.40588235294117661.195
919692AA2-053 E OP
Adder
1.57764705882352941.341
944011AF1-069 C
Adder
5.2117647058823534.43
926206AC1-098 E
Adder
1.26941176470588221.079
963041AG1-153 C
Adder
2.1905882352941181.862
925785AC1-054 E
Adder
1.22941176470588221.045
922923AB1-081 E OP
Adder
1.2952941176470591.101
316263AC1-034 C
Adder
2.30588235294117631.96
962562AG1-105 E
Adder
1.8835294117647061.601
964791AG1-342 C
Adder
1.11882352941176480.951
934576AD1-082 E
50/50
3.6773.677
316084AB2-161 E
50/50
4.6154.615
316083AB2-161 C
50/50
0.4620.462
316315AB2-025 C
50/50
0.2540.254
943172AE2-346 E
Adder
0.191764705882352950.163
946282AF1-292 E
Adder
0.47882352941176470.407
918492AA1-063AE OP
Adder
1.49058823529411751.267
917332KELFORD E
Adder
0.53411764705882360.454
944012AF1-069 E
Adder
2.02470588235294141.721
932632AC2-084 E
Adder
1.12235294117647060.954
926214AC1-099 E
Adder
0.420.357
316274AC1-208 C
Adder
3.23411764705882382.749
927146AC1-208 E
Adder
1.43647058823529421.221
917512Z2-088 E OP1
Adder
1.60588235294117651.365
917342Z2-044 E
Adder
0.209411764705882350.178
934622AD1-088 E
Adder
1.5035294117647061.278
964242AG1-285 E
Adder
2.76470588235294162.35
937482AD2-202 E
Adder
0.35647058823529410.303
934612AD1-087 E
Adder
1.21882352941176491.036
3151311EDGECMA
Adder
5.4047058823529424.594
924162AB2-060 E OP
Adder
1.39764705882352951.188
964792AG1-342 E
Adder
0.74588235294117660.634
942341AE2-247 C
Adder
0.73647058823529410.626
316349AD2-085 C
Adder
1.69882352941176461.444
943462AF1-017 E
Adder
1.08705882352941190.924
938772AE1-103 E
Adder
1.20117647058823531.021
3145393UNCAMP
Adder
1.841.564
939411AE1-173 C
Adder
28.66352941176470624.364
924516AB2-100 E1
Adder
1.4764705882352941.255
900672V4-068 E
Adder
0.116470588235294130.099
960082AF2-299 E
Adder
0.57764705882352940.491
966621AG1-532 C
Adder
0.65058823529411770.553
946281AF1-292 C
Adder
0.71764705882352940.61
926071AC1-086 C
Adder
8.9552941176470597.612
3137643SOCKMAN
Adder
0.289411764705882370.246
963042AG1-153 E
Adder
3.28588235294117672.793
919710AA2-057 E
Adder
1.39647058823529411.187
927021AC1-189 C
Adder
2.7035294117647062.298
964241AG1-285 C
Adder
4.1470588235294123.525
924022AB2-043 E O1
Adder
1.7070588235294121.451
924152AB2-059 E OP
Adder
1.83411764705882341.559
3147223TWITTYS
Adder
0.288235294117647030.245
924302AB2-077 E O1
Adder
0.440.374
962561AG1-105 C
Adder
2.82588235294117672.402
939192AE1-149 E
50/50
7.667.66
923852AB2-025 E
50/50
0.7230.723
940541AE2-040 C
50/50
1.7881.788
940482AE2-033 E
50/50
6.6366.636
940481AE2-033 C
50/50
9.8449.844
939412AE1-173 E
Adder
19.10941176470588216.243
924517AB2-100 E2
Adder
1.4764705882352941.255
316141AB2-099 E
Adder
0.080.068
961941AG1-037 C
Adder
0.158823529411764720.135
961942AG1-037 E
Adder
0.105882352941176470.09
316088AB2-174 E
Adder
2.8647058823529412.435
923263AB1-132 E OP
Adder
2.60588235294117652.215
923994AB2-040_E
Adder
2.63529411764705922.24
941032AE2-094 E
Adder
7.1447058823529426.073
941031AE2-094 C
Adder
15.95176470588235213.559
934321AD1-056 C
Adder
2.3882352941176472.03
934332AD1-057 E
Adder
0.69411764705882350.59
934322AD1-056 E
Adder
1.2952941176470591.101
934331AD1-057 C
Adder
1.3317647058823531.132
927022AC1-189 E
Adder
1.34705882352941191.145
957481AF2-042 C
Adder
18.75411764705882315.941
957482AF2-042 E
Adder
12.50352941176470610.628
961672AG1-007 E
Adder
0.17764705882352940.151
961671AG1-007 C
Adder
0.31294117647058830.266
934621AD1-088 C
Adder
3.12235294117647082.654
925595AC1-034 E
Adder
1.74000000000000021.479
925612AC1-036 E
Adder
0.260.221
924322AB2-079 E O1
Adder
0.440.374
924312AB2-078 E O1
Adder
0.440.374
935172AD1-152 E
Adder
1.7964705882352941.527
926274AC1-105 E
Adder
0.83529411764705890.71
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7620.762
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7591.759
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.05430.054
CPLELTFEXP_CPLE->PJM
CLTF
3.6893.689
TVALTFEXP_TVA->PJM
CLTF
1.8151.815
O66PJM->LTFIMP_O-066
CMTX_NF
4.8534.853
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.5019.501
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7336.733
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1821.182
LAGNLTFEXP_LAGN->PJM
CLTF
2.3242.324
NYPJM->LTFIMP_NY
CLTF
0.3510.351
LGEELTFEXP_LGEE->PJM
CLTF
0.3660.366
WECLTFEXP_WEC->PJM
CLTF
0.1950.195

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.41 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:749.36
MW Contribution:24.29
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.4 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:769.65
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316315AB2-025 C
80/20
1.661.66
3151151S HAMPT1
80/20
0.9560.956
316087AB2-174 C
80/20
2.4642.464
932631AC2-084 C
80/20
1.171.17
316274AC1-208 C
80/20
11.22211.222
316129AC1-054 C
80/20
1.341.34
3151531CLOVER1
80/20
5.8145.814
313527AB2-043 C
80/20
0.3630.363
3151311EDGECMA
80/20
16.54816.548
316049AB1-081 C OP
80/20
1.4931.493
316131AB2-060 C
80/20
1.0331.033
3151611KERR 4
80/20
0.8610.861
3151601KERR 3
80/20
0.8610.861
3151591KERR 2
80/20
0.8610.861
3151581KERR 1
80/20
0.3070.307
3138533PONTONDP
80/20
0.3360.336
316118AC1-105 C
80/20
0.4840.484
3152661PLYWOOD A
80/20
0.6380.638
940541AE2-040 C
80/20
11.68811.688
940481AE2-033 C
80/20
63.40163.401
3156083AA2-088SOLA
80/20
0.9350.935
934501AD1-074 C
80/20
19.34719.347
3156021HOLLOMANSOL
80/20
1.5851.585
961941AG1-037 C
80/20
0.4820.482
943171AE2-346 C
80/20
0.2140.214
3156073AA1-063SOLA
80/20
1.8141.814
316181AB2-040 GEN
80/20
2.512.51
313506AB1-173 C OP
80/20
2.2292.229
316174AB2-169_C
80/20
0.7190.719
3156063AA2-053SOLA
80/20
2.1572.157
3151371ROSEMS1
80/20
2.4382.438
3151361ROSEMG1
80/20
3.9353.935
3151381ROSEMG2
80/20
1.8431.843
3151281ROARAP4
80/20
2.0092.009
316005AA1-067 C
80/20
0.2210.221
934321AD1-056 C
80/20
9.1989.198
934331AD1-057 C
80/20
5.1315.131
3156011CONETOE2SOL
80/20
1.1751.175
957481AF2-042 C
80/20
24.2924.29
961671AG1-007 C
80/20
0.9120.912
934621AD1-088 C
80/20
4.4014.401
316359AB2-059 C OP
80/20
1.761.76
316238AB2-078 C O1
80/20
0.2290.229
316237AB2-079 C O1
80/20
0.2290.229
946301AF1-294 C
80/20
1.8641.864
958211AF2-115 C
80/20
1.1341.134
934511AD1-075 C
80/20
4.8374.837
934521AD1-076 C
80/20
7.0267.026
316365AB2-100 C1
80/20
2.7732.773
316318V4-068 C
80/20
0.0750.075
960081AF2-299 C
80/20
4.3984.398
3151391GASTONA
80/20
6.1746.174
316011AB1-132 C OP
80/20
4.7154.715
316210AC1-098 C
80/20
1.0991.099
316327AA2-057 C
80/20
1.4881.488
316263AC1-034 C
80/20
6.9786.978
3151631KERR 6
80/20
0.8610.861
959311AF2-222 C
80/20
8.6298.629
316239AB2-077 C O1
80/20
0.2290.229
936261AD2-033 C
80/20
8.0238.023
3144293JTRSVLE
80/20
0.2090.209
961791AG1-021 C
80/20
0.9070.907
964791AG1-342 C
80/20
2.0342.034
933981AD1-022 C
80/20
5.6845.684
316023AB2-100 C2
80/20
2.7732.773
3152921DOMTR78
80/20
0.8530.853
316140AB2-099 C
80/20
0.0920.092
966621AG1-532 C
80/20
3.2983.298
946281AF1-292 C
80/20
3.643.64
926071AC1-086 C
80/20
42.48542.485
3151411GASTONB
80/20
6.1746.174
316317KELFORD C
80/20
0.3690.369
3137643SOCKMAN
80/20
1.2371.237
3151261ROARAP2
80/20
2.1232.123
3147043LAWRENC
80/20
0.5790.579
316212AC1-099 C
80/20
0.3680.368
927021AC1-189 C
80/20
7.5457.545
316319Z2-044 C
80/20
0.2310.231
964241AG1-285 C
80/20
7.2197.219
316034AC1-036 C
80/20
0.1230.123
3151641KERR 7
80/20
0.8610.861
3151621KERR 5
80/20
0.8610.861
962561AG1-105 C
80/20
5.2835.283
SIGELTFEXP_SIGE->PJM
CLTF
0.0830.083
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1852.185
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.08134.081
CPLELTFEXP_CPLE->PJM
CLTF
4.5834.583
TVALTFEXP_TVA->PJM
CLTF
2.0082.008
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.08611.086
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.537.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.351.35
LAGNLTFEXP_LAGN->PJM
CLTF
2.5652.565
NYPJM->LTFIMP_NY
CLTF
0.370.37
LGEELTFEXP_LGEE->PJM
CLTF
0.4270.427
WECLTFEXP_WEC->PJM
CLTF
0.2270.227

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.54 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1199.86
MW Contribution:59.51
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.15 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1216.93
MW Contribution:60.39
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944641AF1-129 C
Adder
-99.89764705882352-84.913
316240AF1-291 C
Adder
-2.2705882352941176-1.93
941591AE2-156 C
Adder
6.1035294117647065.188
944601AF1-125 C
Adder
16.8341176470588214.309
944591AF1-124 C
Adder
17.15764705882352814.584
919152AA1-139 E1
Adder
1.42117647058823531.208
938532AE1-072 E
Adder
3.1047058823529412.639
3146326AYDLETT TAP
Adder
0.455294117647058850.387
3145723EMPORIA
Adder
-0.3270588235294118-0.278
944011AF1-069 C
50/50
11.48911.489
3152441Z1-086 ST
50/50
15.62215.622
963041AG1-153 C
50/50
4.6824.682
3151021BRUNSWICKG1
50/50
6.916.91
3151041BRUNSWICKG3
50/50
6.916.91
959311AF2-222 C
Adder
7.2776470588235296.186
936261AD2-033 C
Adder
4.3352941176470593.685
3147133PAMPLIN
Adder
0.377647058823529450.321
961791AG1-021 C
Adder
0.58823529411764710.5
942462AE2-259 E
Adder
2.21764705882352951.885
962562AG1-105 E
Adder
2.3352941176470591.985
964791AG1-342 C
Adder
1.43529411764705881.22
927264AC1-222 E
Adder
1.781.513
925522AC1-027 E
Adder
0.430588235294117660.366
933292AC2-141 E
Adder
6.3529411764705895.4
926755AC1-161 E
Adder
6.3529411764705895.4
933291AC2-141 C
Adder
14.88235294117647112.65
944602AF1-125 E
Adder
38.536470588235332.756
3145506HICKORY
Adder
0.80470588235294130.684
957871AF2-081 C
Adder
3.47411764705882352.953
957872AF2-081 E
Adder
1.48941176470588241.266
940641AE2-051 C
50/50
14.85114.851
944012AF1-069 E
50/50
4.4634.463
3152431Z1-086 GT3
50/50
8.9728.972
3152421Z1-086 GT2
50/50
8.9728.972
3151051BRUNSWICKS1
50/50
14.35614.356
934622AD1-088 E
50/50
2.6942.694
3151531CLOVER1
50/50
7.797.79
964242AG1-285 E
Adder
3.99647058823529383.397
937482AD2-202 E
50/50
0.6470.647
934612AD1-087 E
50/50
2.212.21
934611AD1-087 C
50/50
0.7660.766
924162AB2-060 E OP
Adder
1.4435294117647061.227
961792AG1-021 E
Adder
0.50117647058823530.426
3138533PONTONDP
Adder
0.217647058823529420.185
964792AG1-342 E
Adder
0.95647058823529410.813
927255AC1-221 E
Adder
1.70117647058823531.446
932763AC2-100 E
Adder
1.14235294117647060.971
932046AC2-012 E
Adder
4.4317647058823533.767
944582AF1-123 E
Adder
39.15058823529411633.278
944592AF1-124 E
Adder
39.2929411764705933.399
919153AA1-139 E2
Adder
1.42117647058823531.208
938531AE1-072 C
Adder
5.95529411764705955.062
913392Y1-086 E
Adder
0.66235294117647060.563
923832AB2-022 E
Adder
0.374117647058823550.318
939411AE1-173 C
50/50
67.01167.011
940642AE2-051 E
50/50
9.9019.901
966621AG1-532 C
Adder
-1.14-0.969
946281AF1-292 C
Adder
-1.2576470588235293-1.069
3137643SOCKMAN
Adder
-0.34352941176470586-0.292
3152411Z1-086 GT1
50/50
8.9758.975
3151031BRUNSWICKG2
50/50
6.916.91
963042AG1-153 E
50/50
7.0227.022
3151541CLOVER2
50/50
7.7177.717
964241AG1-285 C
Adder
5.9952941176470595.096
937481AD2-202 C
50/50
0.2220.222
924022AB2-043 E O1
Adder
1.75058823529411781.488
3147223TWITTYS
Adder
0.42235294117647060.359
959312AF2-222 E
Adder
4.8764705882352944.145
924302AB2-077 E O1
Adder
0.45058823529411770.383
958212AF2-115 E
Adder
0.62588235294117660.532
962561AG1-105 C
Adder
3.50352941176470622.978
942001AE2-212 C
Adder
-2.8705882352941177-2.44
926662AC1-147 E
Adder
0.448235294117647070.381
916192Z1-068 E
Adder
0.6682352941176470.568
934065AD1-033 E
Adder
1.87294117647058831.592
944581AF1-123 C
Adder
17.0976470588235314.533
937226AE2-253 E
Adder
2.081.768
939412AE1-173 E
50/50
44.67444.674
941032AE2-094 E
50/50
15.74915.749
941031AE2-094 C
50/50
35.16335.163
934321AD1-056 C
Adder
-2.142352941176471-1.821
934331AD1-057 C
Adder
-1.1952941176470588-1.016
957481AF2-042 C
50/50
35.70935.709
957482AF2-042 E
50/50
23.80623.806
934621AD1-088 C
50/50
5.5965.596
925612AC1-036 E
Adder
0.381176470588235340.324
924322AB2-079 E O1
Adder
0.45058823529411770.383
924312AB2-078 E O1
Adder
0.45058823529411770.383
936262AD2-033 E
Adder
2.89058823529411772.457
946301AF1-294 C
Adder
1.2082352941176471.027
946302AF1-294 E
Adder
1.02352941176470580.87
958211AF2-115 C
Adder
0.73529411764705890.625
942461AE2-259 C
Adder
3.32588235294117632.827
935172AD1-152 E
Adder
3.1047058823529412.639
926274AC1-105 E
Adder
1.15529411764705880.982
943902AF1-058 E
Adder
0.58823529411764710.5
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9710.971
SIGELTFEXP_SIGE->PJM
CLTF
0.0920.092
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9681.968
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.24536.245
CPLELTFEXP_CPLE->PJM
CLTF
4.1284.128
TVALTFEXP_TVA->PJM
CLTF
2.2832.283
O66PJM->LTFIMP_O-066
CMTX_NF
6.1826.182
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.10812.108
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4868.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4991.499
LAGNLTFEXP_LAGN->PJM
CLTF
2.9182.918
NYPJM->LTFIMP_NY
CLTF
0.4470.447
LGEELTFEXP_LGEE->PJM
CLTF
0.4670.467
WECLTFEXP_WEC->PJM
CLTF
0.2490.249

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.13 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4181.52
MW Contribution:138.71
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.66 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4635.61
MW Contribution:140.46
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150921YORKTN3
Adder
152.65647058823532129.758
934576AD1-082 E
Adder
5.7482352941176484.886
316084AB2-161 E
Adder
7.2141176470588236.132
3145256KINGFORK
Adder
1.48823529411764691.265
3151101ELIZAR3
50/50
4.9744.974
3151081ELIZAR1
50/50
4.9124.912
3151091ELIZAR2
50/50
4.8264.826
925522AC1-027 E
50/50
1.8771.877
916191Z1-068 C
50/50
0.0680.068
933292AC2-141 E
50/50
20.76320.763
926755AC1-161 E
50/50
20.76320.763
316294AC1-161 C
50/50
7.9487.948
933291AC2-141 C
50/50
48.6448.64
944602AF1-125 E
50/50
159.152159.152
941102AE2-104 E
Adder
7.966.766
3145506HICKORY
50/50
3.3883.388
943612AF1-032 E
Adder
1.40823529411764731.197
957871AF2-081 C
50/50
15.47915.479
957872AF2-081 E
50/50
6.6346.634
316315AB2-025 C
50/50
0.6050.605
940492AE2-034 E
Adder
4.6305882352941183.936
3145946PLYMOUTH TP
Adder
0.48235294117647060.41
934522AD1-076 E
Adder
9.3011764705882357.906
933982AD1-022 E
Adder
7.0894117647058836.026
940641AE2-051 C
50/50
31.3831.38
943172AE2-346 E
Adder
0.88941176470588230.756
946282AF1-292 E
Adder
1.49529411764705871.271
918492AA1-063AE OP
Adder
5.9423529411764715.051
917332KELFORD E
Adder
2.39764705882352922.038
925122AB2-169 E
Adder
8.4305882352941197.166
944012AF1-069 E
50/50
9.0749.074
932632AC2-084 E
Adder
4.6458823529411763.949
926214AC1-099 E
Adder
1.73647058823529421.476
3152431Z1-086 GT3
50/50
18.59918.599
3152421Z1-086 GT2
50/50
18.59918.599
316274AC1-208 C
Adder
12.93882352941176410.998
927146AC1-208 E
Adder
5.74470588235294164.883
3151051BRUNSWICKS1
50/50
30.03530.035
917512Z2-088 E OP1
Adder
6.9717647058823535.926
917342Z2-044 E
Adder
0.84705882352941180.72
934622AD1-088 E
Adder
6.6576470588235295.659
964242AG1-285 E
Adder
11.97764705882352810.181
937482AD2-202 E
Adder
1.57764705882352941.341
934612AD1-087 E
Adder
5.3905882352941184.582
3151311EDGECMA
Adder
21.84705882352941218.57
924162AB2-060 E OP
Adder
5.8752941176470594.994
964792AG1-342 E
Adder
3.1905882352941182.712
942341AE2-247 C
Adder
2.11764705882352941.8
316349AD2-085 C
Adder
4.8858823529411764.153
943462AF1-017 E
Adder
3.12588235294117662.657
935112AD1-144 E
Adder
1.38117647058823521.174
932046AC2-012 E
50/50
20.04320.043
939191AE1-149 C
Adder
13.15411764705882411.181
3143316POE
Adder
1.71764705882352931.46
943461AF1-017 C
Adder
1.91529411764705881.628
942342AE2-247 E
Adder
2.92470588235294172.486
936666AD2-085 E
Adder
7.9705882352941196.775
932596AC2-079 E
Adder
13.36941176470588411.364
316311AC2-079 C
Adder
8.1941176470588236.965
316036AC1-147 C
50/50
0.5640.564
941591AE2-156 C
50/50
27.4127.41
316316AC1-027 C
50/50
0.4870.487
944601AF1-125 C
50/50
69.52369.523
944591AF1-124 C
50/50
70.86170.861
316018AA1-139 ULT2
50/50
1.6761.676
919152AA1-139 E1
50/50
6.336.33
938532AE1-072 E
50/50
14.1714.17
3146326AYDLETT TAP
50/50
2.0962.096
917122Z2-027 E
Adder
2.061.751
901082W1-029 E
Adder
48.63529411764706441.34
938771AE1-103 C
Adder
4.3470588235294113.695
3145413WATKINS
Adder
1.02235294117647070.869
920692AA2-178 E
Adder
6.1741176470588245.248
920042AA2-088 E OP
Adder
15.59882352941176513.259
934511AD1-075 C
Adder
12.56117647058823510.677
934521AD1-076 C
Adder
18.24823529411764515.511
960081AF2-299 C
Adder
2.70823529411764732.302
966622AG1-532 E
Adder
1.35411764705882361.151
3145723EMPORIA
Adder
0.62470588235294120.531
926072AC1-086 E
Adder
13.85058823529411711.773
923573AB1-173 E OP
Adder
4.7517647058823534.039
919692AA2-053 E OP
Adder
6.1282352941176475.209
944011AF1-069 C
50/50
23.35723.357
926206AC1-098 E
Adder
5.25647058823529444.468
3152441Z1-086 ST
50/50
32.38632.386
963041AG1-153 C
50/50
9.7959.795
3151021BRUNSWICKG1
50/50
14.45814.458
3151041BRUNSWICKG3
50/50
14.45814.458
925785AC1-054 E
Adder
4.8741176470588234.143
922923AB1-081 E OP
Adder
5.2458823529411764.459
316263AC1-034 C
Adder
9.344705882352947.943
959311AF2-222 C
Adder
21.718.445
936261AD2-033 C
Adder
6.71764705882352955.71
962562AG1-105 E
Adder
8.0317647058823526.827
964791AG1-342 C
Adder
4.7858823529411764.068
944582AF1-123 E
50/50
161.69161.69
944592AF1-124 E
50/50
162.275162.275
958161AF2-110 C
Adder
2.04352941176470631.737
958162AF2-110 E
Adder
3.24941176470588242.762
316388AE2-253 GEN
50/50
3.0473.047
316017AA1-139 ULT1
50/50
1.6761.676
919153AA1-139 E2
50/50
6.336.33
938531AE1-072 C
50/50
27.18327.183
913392Y1-086 E
50/50
3.383.38
923832AB2-022 E
50/50
1.9081.908
938772AE1-103 E
Adder
6.0023529411764715.102
916042Z1-036 E
Adder
43.3141176470588236.817
3145393UNCAMP
Adder
9.0117647058823537.66
939411AE1-173 C
50/50
158.79158.79
934512AD1-075 E
Adder
6.3941176470588235.435
934502AD1-074 E
Adder
25.5776470588235321.741
933981AD1-022 C
Adder
13.02235294117647211.069
924516AB2-100 E1
Adder
4.23058823529411753.596
900672V4-068 E
Adder
0.52352941176470590.445
918512AA1-065 E OP
Adder
8.1470588235294116.925
940642AE2-051 E
50/50
20.9220.92
960082AF2-299 E
Adder
1.80588235294117651.535
966621AG1-532 C
Adder
2.0317647058823531.727
946281AF1-292 C
Adder
2.24235294117647041.906
926071AC1-086 C
Adder
30.4329411764705925.868
3137643SOCKMAN
Adder
1.03058823529411760.876
3152411Z1-086 GT1
50/50
18.60518.605
3151031BRUNSWICKG2
50/50
14.45814.458
963042AG1-153 E
50/50
14.69214.692
918532AA1-067 E
Adder
1.02823529411764710.874
919710AA2-057 E
Adder
5.6458823529411774.799
927021AC1-189 C
Adder
12.02000000000000110.217
964241AG1-285 C
Adder
17.9658823529411815.271
924022AB2-043 E O1
Adder
7.1670588235294126.092
924152AB2-059 E OP
Adder
7.4317647058823546.317
3147223TWITTYS
Adder
1.2588235294117651.07
959312AF2-222 E
Adder
14.53882352941176512.358
924302AB2-077 E O1
Adder
1.84705882352941191.57
962561AG1-105 C
Adder
12.04705882352941210.24
961611AG1-000B C
Adder
19.52941176470588416.6
939192AE1-149 E
Adder
8.7694117647058827.454
939312AE1-162 E
Adder
1.95882352941176491.665
3150981CHESPKA
50/50
0.6670.667
316375AC2-012 C
50/50
2.0662.066
926662AC1-147 E
50/50
2.0262.026
3150991CHESPKB
50/50
1.1051.105
916192Z1-068 E
50/50
2.92.9
316185AD1-033 C
50/50
1.9111.911
934065AD1-033 E
50/50
7.7977.797
944581AF1-123 C
50/50
70.6170.61
941101AE2-104 C
Adder
5.00705882352941254.256
957492AF2-043 E
Adder
2.16705882352941171.842
937226AE2-253 E
50/50
9.0629.062
313526AB2-022 C
50/50
0.5790.579
316320Y1-086 C
50/50
0.3390.339
923852AB2-025 E
50/50
1.7231.723
940541AE2-040 C
Adder
4.263.621
940482AE2-033 E
Adder
16.1613.736
940481AE2-033 C
Adder
23.97176470588235420.376
939412AE1-173 E
50/50
105.86105.86
934501AD1-074 C
Adder
50.2447058823529442.708
924517AB2-100 E2
Adder
4.23058823529411753.596
316141AB2-099 E
Adder
0.370588235294117660.315
961941AG1-037 C
Adder
0.74117647058823530.63
961942AG1-037 E
Adder
0.494117647058823550.42
316088AB2-174 E
Adder
9.4435294117647068.027
923263AB1-132 E OP
Adder
8.8564705882352937.528
923994AB2-040_E
Adder
8.9094117647058837.573
941032AE2-094 E
50/50
32.01732.017
941031AE2-094 C
50/50
71.48571.485
934321AD1-056 C
Adder
8.927.582
934332AD1-057 E
Adder
2.5917647058823532.203
934322AD1-056 E
Adder
4.8388235294117664.113
934331AD1-057 C
Adder
4.9764705882352954.23
927022AC1-189 E
Adder
5.9882352941176475.09
957481AF2-042 C
50/50
83.22783.227
957482AF2-042 E
50/50
55.48555.485
961672AG1-007 E
Adder
0.75529411764705890.642
961671AG1-007 C
Adder
1.33294117647058831.133
934621AD1-088 C
Adder
13.82823529411764711.754
925595AC1-034 E
Adder
7.0494117647058835.992
925612AC1-036 E
Adder
1.13647058823529410.966
924322AB2-079 E O1
Adder
1.84705882352941191.57
924312AB2-078 E O1
Adder
1.84705882352941191.57
935172AD1-152 E
Adder
7.9105882352941186.724
926274AC1-105 E
Adder
3.63.06
943902AF1-058 E
Adder
1.71882352941176491.461
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6364.636
SIGELTFEXP_SIGE->PJM
CLTF
0.2790.279
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6337.633
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.923129.923
CPLELTFEXP_CPLE->PJM
CLTF
16.01716.017
TVALTFEXP_TVA->PJM
CLTF
7.5637.563
O66PJM->LTFIMP_O-066
CMTX_NF
29.52729.527
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.88834.888
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.38927.389
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.6044.604
LAGNLTFEXP_LAGN->PJM
CLTF
9.689.68
NYPJM->LTFIMP_NY
CLTF
2.172.17
LGEELTFEXP_LGEE->PJM
CLTF
1.3891.389
WECLTFEXP_WEC->PJM
CLTF
0.7290.729

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.17 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4104.33
MW Contribution:133.24
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
942341AE2-247 C
Adder
1.9647058823529411.67
316349AD2-085 C
Adder
4.5341176470588243.854
943462AF1-017 E
Adder
2.90117647058823552.466
935112AD1-144 E
Adder
1.2588235294117651.07
932046AC2-012 E
50/50
18.21618.216
944582AF1-123 E
50/50
146.831146.831
944592AF1-124 E
50/50
147.363147.363
958161AF2-110 C
Adder
1.8752941176470591.594
958162AF2-110 E
Adder
2.98235294117647072.535
316388AE2-253 GEN
50/50
2.7712.771
316017AA1-139 ULT1
50/50
1.5241.524
919153AA1-139 E2
50/50
5.7585.758
938531AE1-072 C
50/50
24.73924.739
913392Y1-086 E
Adder
3.08235294117647072.62
923832AB2-022 E
Adder
1.74000000000000021.479
938772AE1-103 E
Adder
5.5529411764705884.72
916042Z1-036 E
Adder
39.78705882352941433.819
3145393UNCAMP
Adder
8.3505882352941197.098
939411AE1-173 C
50/50
149.153149.153
934512AD1-075 E
Adder
5.9258823529411765.037
934502AD1-074 E
Adder
23.70588235294117420.15
933981AD1-022 C
Adder
12.09058823529411710.277
924516AB2-100 E1
Adder
4.042352941176473.436
900672V4-068 E
Adder
0.490588235294117660.417
918512AA1-065 E OP
Adder
7.6023529411764716.462
940642AE2-051 E
50/50
19.82119.821
960082AF2-299 E
Adder
1.7247058823529411.466
966621AG1-532 C
Adder
1.94000000000000021.649
946281AF1-292 C
Adder
2.14117647058823521.82
926071AC1-086 C
Adder
28.90117647058823624.566
3137643SOCKMAN
Adder
0.97882352941176460.832
3152411Z1-086 GT1
50/50
17.81217.812
3151031BRUNSWICKG2
50/50
13.84413.844
963042AG1-153 E
50/50
14.06814.068
918532AA1-067 E
Adder
0.96823529411764710.823
919710AA2-057 E
Adder
5.3541176470588244.551
927021AC1-189 C
Adder
11.3505882352941179.648
3151541CLOVER2
50/50
18.07518.075
961611AG1-000B C
Adder
18.02352941176470615.32
939192AE1-149 E
Adder
8.424705882352947.161
939312AE1-162 E
Adder
1.79058823529411781.522
316375AC2-012 C
50/50
1.8781.878
926662AC1-147 E
Adder
1.84117647058823521.565
916192Z1-068 E
50/50
2.6352.635
316185AD1-033 C
50/50
1.7361.736
934065AD1-033 E
50/50
7.0817.081
944581AF1-123 C
50/50
64.12164.121
941101AE2-104 C
Adder
4.5952941176470593.906
957492AF2-043 E
Adder
1.97647058823529421.68
937226AE2-253 E
50/50
8.2398.239
923852AB2-025 E
50/50
1.6571.657
940541AE2-040 C
50/50
4.0974.097
940482AE2-033 E
50/50
15.52815.528
940481AE2-033 C
50/50
23.03323.033
939412AE1-173 E
50/50
99.43599.435
934501AD1-074 C
Adder
46.5682352941176539.583
924517AB2-100 E2
Adder
4.042352941176473.436
316141AB2-099 E
Adder
0.347058823529411750.295
961941AG1-037 C
Adder
0.69294117647058820.589
961942AG1-037 E
Adder
0.462352941176470630.393
316088AB2-174 E
Adder
8.997647058823537.648
923263AB1-132 E OP
Adder
8.4105882352941177.149
923994AB2-040_E
Adder
8.487.208
941032AE2-094 E
50/50
30.64130.641
941031AE2-094 C
50/50
68.41468.414
934321AD1-056 C
Adder
8.477647058823537.206
934332AD1-057 E
Adder
2.46235294117647062.093
934322AD1-056 E
Adder
4.59882352941176453.909
934331AD1-057 C
Adder
4.72941176470588154.02
927022AC1-189 E
Adder
5.6541176470588244.806
957481AF2-042 C
50/50
79.94679.946
957482AF2-042 E
50/50
53.29753.297
961672AG1-007 E
Adder
0.71529411764705890.608
961671AG1-007 C
Adder
1.26235294117647071.073
934621AD1-088 C
Adder
13.31176470588235211.315
925595AC1-034 E
Adder
6.702352941176475.697
925612AC1-036 E
Adder
1.09882352941176480.934
924322AB2-079 E O1
Adder
1.77764705882352941.511
964241AG1-285 C
Adder
17.3105882352941214.714
937481AD2-202 C
50/50
0.5210.521
924022AB2-043 E O1
Adder
6.95.865
924152AB2-059 E OP
Adder
7.0658823529411776.006
3147223TWITTYS
Adder
1.21764705882352931.035
959312AF2-222 E
Adder
14.06705882352941311.957
924302AB2-077 E O1
Adder
1.77764705882352941.511
962561AG1-105 C
Adder
11.6047058823529429.864
3150921YORKTN3
Adder
64.9600000000000155.216
934576AD1-082 E
Adder
5.4388235294117654.623
316084AB2-161 E
Adder
6.8258823529411765.802
3145256KINGFORK
Adder
1.35529411764705881.152
3151101ELIZAR3
50/50
4.524.52
3151081ELIZAR1
50/50
4.4634.463
3151091ELIZAR2
50/50
4.3854.385
925522AC1-027 E
50/50
1.7051.705
916191Z1-068 C
50/50
0.0610.061
933292AC2-141 E
50/50
18.61818.618
926755AC1-161 E
50/50
18.61818.618
316294AC1-161 C
50/50
7.1277.127
933291AC2-141 C
50/50
43.61643.616
944602AF1-125 E
50/50
144.526144.526
941102AE2-104 E
Adder
7.3058823529411766.21
3145506HICKORY
50/50
3.0783.078
943612AF1-032 E
Adder
1.28470588235294141.092
957871AF2-081 C
50/50
14.0814.08
957872AF2-081 E
50/50
6.0346.034
316315AB2-025 C
50/50
0.5820.582
940492AE2-034 E
Adder
4.2752941176470593.634
3145946PLYMOUTH TP
Adder
0.44705882352941180.38
934522AD1-076 E
Adder
8.6200000000000017.327
933982AD1-022 E
Adder
6.582352941176475.595
940641AE2-051 C
50/50
29.73129.731
943172AE2-346 E
Adder
0.8317647058823530.707
946282AF1-292 E
Adder
1.4270588235294121.213
918492AA1-063AE OP
Adder
5.6035294117647064.763
917332KELFORD E
Adder
2.25058823529411761.913
925122AB2-169 E
Adder
7.8694117647058836.689
944012AF1-069 E
50/50
8.6848.684
932632AC2-084 E
Adder
4.3905882352941183.732
926214AC1-099 E
Adder
1.64117647058823551.395
3152431Z1-086 GT3
50/50
17.80617.806
3152421Z1-086 GT2
50/50
17.80617.806
316274AC1-208 C
Adder
12.25411764705882510.416
927146AC1-208 E
Adder
5.44117647058823554.625
3151051BRUNSWICKS1
50/50
28.7628.76
917512Z2-088 E OP1
Adder
6.5941176470588245.605
917342Z2-044 E
Adder
0.80352941176470590.683
934622AD1-088 E
Adder
6.4094117647058835.448
3151531CLOVER1
50/50
18.24518.245
964242AG1-285 E
Adder
11.549.809
937482AD2-202 E
50/50
1.5171.517
934612AD1-087 E
50/50
5.1825.182
934611AD1-087 C
50/50
1.7961.796
3151311EDGECMA
Adder
20.7705882352941217.655
924162AB2-060 E OP
Adder
5.6588235294117644.81
964792AG1-342 E
Adder
3.07411764705882362.613
939191AE1-149 C
Adder
12.63647058823529410.741
3143316POE
Adder
1.67647058823529421.425
943461AF1-017 C
Adder
1.77764705882352941.511
942342AE2-247 E
Adder
2.71411764705882372.307
936666AD2-085 E
Adder
7.397647058823536.288
932596AC2-079 E
Adder
12.38941176470588310.531
316311AC2-079 C
Adder
7.5929411764705886.454
941591AE2-156 C
50/50
24.9124.91
316316AC1-027 C
50/50
0.4430.443
944601AF1-125 C
50/50
63.13463.134
944591AF1-124 C
50/50
64.34964.349
316018AA1-139 ULT2
50/50
1.5241.524
919152AA1-139 E1
50/50
5.7585.758
938532AE1-072 E
50/50
12.89612.896
3146326AYDLETT TAP
50/50
1.9081.908
917122Z2-027 E
Adder
1.88117647058823521.599
901082W1-029 E
Adder
44.4776470588235337.806
938771AE1-103 C
Adder
4.0211764705882363.418
3145413WATKINS
Adder
0.94941176470588240.807
920692AA2-178 E
Adder
5.74.845
920042AA2-088 E OP
Adder
14.57411764705882412.388
934511AD1-075 C
Adder
11.6423529411764739.896
934521AD1-076 C
Adder
16.9129411764705914.376
960081AF2-299 C
Adder
2.58705882352941162.199
966622AG1-532 E
Adder
1.29294117647058831.099
3145723EMPORIA
Adder
0.59647058823529410.507
926072AC1-086 E
Adder
13.15411764705882411.181
923573AB1-173 E OP
Adder
4.5223529411764713.844
919692AA2-053 E OP
Adder
5.797647058823534.928
944011AF1-069 C
50/50
22.35322.353
926206AC1-098 E
Adder
4.9670588235294124.222
3152441Z1-086 ST
50/50
31.00631.006
963041AG1-153 C
50/50
9.3799.379
3151021BRUNSWICKG1
50/50
13.84413.844
3151041BRUNSWICKG3
50/50
13.84413.844
925785AC1-054 E
Adder
4.65176470588235353.954
922923AB1-081 E OP
Adder
4.9882352941176474.24
316263AC1-034 C
Adder
8.8847058823529417.552
959311AF2-222 C
Adder
20.9952941176470617.846
936261AD2-033 C
Adder
15.9952941176470613.596
962562AG1-105 E
Adder
7.7364705882352946.576
964791AG1-342 C
Adder
4.6105882352941173.919
924312AB2-078 E O1
Adder
1.77764705882352941.511
936262AD2-033 E
Adder
10.6635294117647069.064
935172AD1-152 E
Adder
7.6094117647058826.468
926274AC1-105 E
Adder
3.4682352941176472.948
943902AF1-058 E
Adder
1.65647058823529411.408
G-007PJM->LTFIMP_G-007
CMTX_NF
4.7394.739
SIGELTFEXP_SIGE->PJM
CLTF
0.2910.291
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.3487.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
126.03126.03
CPLELTFEXP_CPLE->PJM
CLTF
15.41515.415
TVALTFEXP_TVA->PJM
CLTF
7.567.56
O66PJM->LTFIMP_O-066
CMTX_NF
30.16830.168
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.99436.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.67827.678
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.7584.758
LAGNLTFEXP_LAGN->PJM
CLTF
9.6549.654
NYPJM->LTFIMP_NY
CLTF
2.22.2
LGEELTFEXP_LGEE->PJM
CLTF
1.4681.468
WECLTFEXP_WEC->PJM
CLTF
0.7690.769

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T567_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T567_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.4 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4073.91
MW Contribution:138.13
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3143316POE
Adder
1.61411764705882371.372
3152331SURRY 2
50/50
39.09539.095
943461AF1-017 C
Adder
1.89411764705882371.61
942342AE2-247 E
Adder
2.89058823529411772.457
936666AD2-085 E
Adder
7.8811764705882356.699
932596AC2-079 E
Adder
13.2447058823529411.258
316311AC2-079 C
Adder
8.117647058823536.9
941591AE2-156 C
50/50
27.78727.787
316316AC1-027 C
50/50
0.4950.495
944601AF1-125 C
50/50
70.76370.763
944591AF1-124 C
50/50
72.12672.126
316018AA1-139 ULT2
50/50
1.7031.703
919152AA1-139 E1
50/50
6.4346.434
938532AE1-072 E
50/50
14.39614.396
3146326AYDLETT TAP
50/50
2.1292.129
917122Z2-027 E
Adder
2.08705882352941161.774
901082W1-029 E
Adder
49.1811764705882441.804
938771AE1-103 C
Adder
4.3517647058823533.699
3145413WATKINS
Adder
1.02235294117647070.869
920692AA2-178 E
Adder
6.2129411764705885.281
920042AA2-088 E OP
Adder
15.5623529411764713.228
934511AD1-075 C
Adder
12.6152941176470610.723
934521AD1-076 C
Adder
18.32705882352941315.578
960081AF2-299 C
Adder
2.6705882352941182.27
966622AG1-532 E
Adder
1.3352941176470591.135
3145723EMPORIA
Adder
0.61647058823529410.524
926072AC1-086 E
Adder
13.70588235294117811.65
923573AB1-173 E OP
Adder
4.6976470588235293.993
919692AA2-053 E OP
Adder
6.08588235294117655.173
944011AF1-069 C
50/50
23.40523.405
926206AC1-098 E
Adder
5.2270588235294114.443
3152441Z1-086 ST
50/50
32.43132.431
963041AG1-153 C
50/50
9.8059.805
3151021BRUNSWICKG1
50/50
14.47314.473
3151041BRUNSWICKG3
50/50
14.47314.473
925785AC1-054 E
Adder
4.8317647058823534.107
922923AB1-081 E OP
Adder
5.2094117647058834.428
316263AC1-034 C
Adder
9.287.888
959311AF2-222 C
Adder
21.34470588235294418.143
936261AD2-033 C
Adder
5.8058823529411764.935
962562AG1-105 E
Adder
7.9482352941176486.756
964791AG1-342 C
Adder
4.737647058823534.027
3150921YORKTN3
Adder
148.4764705882353126.205
934576AD1-082 E
Adder
5.5282352941176474.699
316084AB2-161 E
Adder
6.937647058823535.897
3145256KINGFORK
Adder
1.49058823529411751.267
3151101ELIZAR3
50/50
5.0455.045
3151081ELIZAR1
50/50
4.9824.982
3151091ELIZAR2
50/50
4.8954.895
925522AC1-027 E
50/50
1.9061.906
916191Z1-068 C
50/50
0.0690.069
933292AC2-141 E
50/50
21.46921.469
926755AC1-161 E
50/50
21.46921.469
316294AC1-161 C
50/50
8.2198.219
933291AC2-141 C
50/50
50.29350.293
944602AF1-125 E
50/50
161.991161.991
941102AE2-104 E
Adder
7.99294117647058756.794
3145506HICKORY
50/50
3.4483.448
943612AF1-032 E
Adder
1.42235294117647081.209
957871AF2-081 C
50/50
15.73315.733
957872AF2-081 E
50/50
6.7436.743
940492AE2-034 E
Adder
4.663.961
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
934522AD1-076 E
Adder
9.3411764705882367.94
933982AD1-022 E
Adder
7.11294117647058856.046
940641AE2-051 C
50/50
31.61831.618
943172AE2-346 E
Adder
0.88823529411764710.755
946282AF1-292 E
Adder
1.47411764705882351.253
918492AA1-063AE OP
Adder
5.9070588235294125.021
917332KELFORD E
Adder
2.39058823529411772.032
925122AB2-169 E
Adder
8.4411764705882367.175
944012AF1-069 E
50/50
9.0929.092
932632AC2-084 E
Adder
4.623.927
926214AC1-099 E
Adder
1.72705882352941181.468
3152431Z1-086 GT3
50/50
18.62518.625
3152421Z1-086 GT2
50/50
18.62518.625
316274AC1-208 C
Adder
12.85294117647058910.925
927146AC1-208 E
Adder
5.7070588235294124.851
3151051BRUNSWICKS1
50/50
30.06830.068
917512Z2-088 E OP1
Adder
6.9388235294117645.898
917342Z2-044 E
Adder
0.84117647058823530.715
934622AD1-088 E
Adder
6.6058823529411775.615
964242AG1-285 E
Adder
11.85176470588235310.074
937482AD2-202 E
Adder
1.56941176470588251.334
934612AD1-087 E
Adder
5.3611764705882364.557
3151311EDGECMA
Adder
21.6952941176470618.441
924162AB2-060 E OP
Adder
5.8058823529411764.935
964792AG1-342 E
Adder
3.1588235294117652.685
942341AE2-247 C
Adder
2.09411764705882361.78
961611AG1-000B C
Adder
18.65882352941176615.86
939312AE1-162 E
Adder
1.93058823529411771.641
316375AC2-012 C
50/50
2.0942.094
926662AC1-147 E
Adder
2.05411764705882361.746
3150991CHESPKB
50/50
1.121.12
916192Z1-068 E
50/50
2.9452.945
316185AD1-033 C
50/50
1.9451.945
934065AD1-033 E
50/50
7.9347.934
944581AF1-123 C
50/50
71.8771.87
941101AE2-104 C
Adder
5.0270588235294114.273
957492AF2-043 E
Adder
2.18823529411764731.86
937226AE2-253 E
50/50
9.2149.214
923852AB2-025 E
Adder
1.6847058823529411.432
940541AE2-040 C
Adder
4.16470588235294153.54
940482AE2-033 E
Adder
15.81058823529411813.439
940481AE2-033 C
Adder
23.45176470588235419.934
939412AE1-173 E
50/50
106.866106.866
934501AD1-074 C
Adder
50.4623529411764742.893
924517AB2-100 E2
Adder
4.1635294117647063.539
316141AB2-099 E
Adder
0.36941176470588240.314
961941AG1-037 C
Adder
0.740.629
961942AG1-037 E
Adder
0.49294117647058820.419
316088AB2-174 E
Adder
9.3282352941176477.929
923263AB1-132 E OP
Adder
8.7635294117647067.449
923994AB2-040_E
Adder
8.8082352941176477.487
941032AE2-094 E
50/50
32.08232.082
941031AE2-094 C
50/50
71.63171.631
934321AD1-056 C
Adder
8.844705882352947.518
934332AD1-057 E
Adder
2.56941176470588272.184
934322AD1-056 E
Adder
4.797647058823534.078
934331AD1-057 C
Adder
4.9341176470588244.194
927022AC1-189 E
Adder
5.9647058823529415.07
957481AF2-042 C
Adder
82.8776470588235370.446
957482AF2-042 E
Adder
55.2517647058823546.964
961672AG1-007 E
Adder
0.7517647058823530.639
961671AG1-007 C
Adder
1.32588235294117651.127
934621AD1-088 C
Adder
13.7211.662
925595AC1-034 E
Adder
7.0011764705882355.951
925612AC1-036 E
Adder
1.11882352941176480.951
924322AB2-079 E O1
Adder
1.82588235294117651.552
924312AB2-078 E O1
Adder
1.82588235294117651.552
935172AD1-152 E
Adder
7.8611764705882366.682
926274AC1-105 E
Adder
3.5647058823529413.03
943902AF1-058 E
Adder
1.70235294117647061.447
316349AD2-085 C
Adder
4.8305882352941174.106
943462AF1-017 E
Adder
3.09058823529411742.627
935112AD1-144 E
Adder
1.3835294117647061.176
932046AC2-012 E
50/50
20.31420.314
944582AF1-123 E
50/50
164.574164.574
944592AF1-124 E
50/50
165.171165.171
958161AF2-110 C
Adder
2.0517647058823531.744
958162AF2-110 E
Adder
3.2635294117647062.774
316388AE2-253 GEN
50/50
3.0993.099
316017AA1-139 ULT1
50/50
1.7031.703
919153AA1-139 E2
50/50
6.4346.434
938531AE1-072 C
50/50
27.61527.615
913392Y1-086 E
Adder
3.42705882352941152.913
923832AB2-022 E
Adder
1.93411764705882351.644
938772AE1-103 E
Adder
6.0094117647058825.108
916042Z1-036 E
Adder
43.71058823529412537.154
3145393UNCAMP
Adder
9.017647058823537.665
939411AE1-173 C
50/50
160.299160.299
934512AD1-075 E
Adder
6.422352941176475.459
934502AD1-074 E
Adder
25.6882352941176521.835
933981AD1-022 C
Adder
13.06588235294117711.106
924516AB2-100 E1
Adder
4.1635294117647063.539
900672V4-068 E
Adder
0.52235294117647060.444
918512AA1-065 E OP
Adder
8.1494117647058816.927
940642AE2-051 E
50/50
21.07921.079
960082AF2-299 E
Adder
1.78117647058823541.514
966621AG1-532 C
Adder
2.00352941176470621.703
946281AF1-292 C
Adder
2.21058823529411751.879
926071AC1-086 C
Adder
30.1129411764705925.596
3137643SOCKMAN
Adder
1.02117647058823540.868
3152411Z1-086 GT1
50/50
18.63118.631
3151031BRUNSWICKG2
50/50
14.47314.473
963042AG1-153 E
50/50
14.70814.708
918532AA1-067 E
Adder
1.02588235294117650.872
919710AA2-057 E
Adder
5.6082352941176474.767
927021AC1-189 C
Adder
11.97411764705882410.178
964241AG1-285 C
Adder
17.77647058823529515.11
924022AB2-043 E O1
Adder
7.0847058823529416.022
924152AB2-059 E OP
Adder
7.3811764705882366.274
3147223TWITTYS
Adder
1.241.054
959312AF2-222 E
Adder
14.30117647058823712.156
924302AB2-077 E O1
Adder
1.82588235294117651.552
962561AG1-105 C
Adder
11.92235294117647210.134
G-007PJM->LTFIMP_G-007
CMTX_NF
4.2584.258
SIGELTFEXP_SIGE->PJM
CLTF
0.2610.261
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.5637.563
CBM South 2LTFEXP_CBM-S2->PJM
CBM
128.067128.067
CPLELTFEXP_CPLE->PJM
CLTF
15.87115.871
TVALTFEXP_TVA->PJM
CLTF
7.2977.297
O66PJM->LTFIMP_O-066
CMTX_NF
27.12727.127
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.34332.343
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.24226.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.3444.344
LAGNLTFEXP_LAGN->PJM
CLTF
9.3599.359
NYPJM->LTFIMP_NY
CLTF
2.0052.005
LGEELTFEXP_LGEE->PJM
CLTF
1.2871.287
WECLTFEXP_WEC->PJM
CLTF
0.6770.677

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.99 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4294.13
MW Contribution:138.0
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
Adder
27.96823529411764823.773
946262AF1-291 E
Adder
2.17647058823529441.85
3150731STONECA
Adder
10.1976470588235298.668
940432AE2-027 E
Adder
13.04588235294117711.089
935161AD1-151 C
Adder
24.22470588235294320.591
934012AD1-025 E
Adder
15.07294117647058812.812
942341AE2-247 C
Adder
2.362.006
316349AD2-085 C
Adder
5.4458823529411764.629
943462AF1-017 E
Adder
3.48470588235294132.962
935112AD1-144 E
Adder
1.48117647058823531.259
932046AC2-012 E
50/50
20.89320.893
944582AF1-123 E
50/50
166.107166.107
944592AF1-124 E
50/50
166.709166.709
958161AF2-110 C
Adder
2.16823529411764731.843
958162AF2-110 E
Adder
3.4494117647058822.932
919153AA1-139 E2
Adder
6.5152941176470595.538
938531AE1-072 C
Adder
27.99411764705882523.795
913392Y1-086 E
Adder
3.48941176470588272.966
923832AB2-022 E
Adder
1.96941176470588241.674
938772AE1-103 E
Adder
6.3458823529411775.394
916042Z1-036 E
Adder
44.8811764705882438.149
3145393UNCAMP
Adder
9.5200000000000018.092
939411AE1-173 C
50/50
151.032151.032
934512AD1-075 E
Adder
6.6317647058823535.637
934502AD1-074 E
Adder
26.5247058823529422.546
933981AD1-022 C
Adder
13.5152941176470611.488
924516AB2-100 E1
Adder
4.4917647058823533.818
900672V4-068 E
Adder
0.54941176470588240.467
918512AA1-065 E OP
Adder
0.250588235294117670.213
940642AE2-051 E
50/50
19.46119.461
960082AF2-299 E
Adder
1.91529411764705881.628
966621AG1-532 C
Adder
2.15411764705882371.831
946281AF1-292 C
Adder
2.37764705882352922.021
933502AC2-165 E
Adder
11.189.503
926071AC1-086 C
Adder
31.96588235294117627.171
3137643SOCKMAN
Adder
1.08470588235294120.922
3152411Z1-086 GT1
50/50
17.32817.328
3151031BRUNSWICKG2
50/50
13.50613.506
963042AG1-153 E
50/50
13.72513.725
3150831SPRUNCA
Adder
14.05529411764705811.947
3150841SPRUNCB
Adder
14.05529411764705811.947
940431AE2-027 C
Adder
19.56823529411764516.633
942001AE2-212 C
Adder
3.34588235294117632.844
942002AE2-212 E
Adder
2.23058823529411751.896
961611AG1-000B C
Adder
24.2858823529411820.643
939192AE1-149 E
Adder
11.2529411764705879.565
939312AE1-162 E
Adder
2.22705882352941181.893
316375AC2-012 C
50/50
2.1542.154
926662AC1-147 E
Adder
2.1117647058823531.795
916192Z1-068 E
50/50
3.0013.001
316185AD1-033 C
50/50
1.9651.965
934065AD1-033 E
50/50
8.0198.019
944581AF1-123 C
50/50
72.53972.539
941101AE2-104 C
Adder
5.3141176470588244.517
957492AF2-043 E
Adder
2.25882352941176471.92
937226AE2-253 E
Adder
9.322352941176477.924
923852AB2-025 E
50/50
1.8511.851
940541AE2-040 C
50/50
4.5764.576
940482AE2-033 E
50/50
17.33217.332
940481AE2-033 C
50/50
25.70925.709
939412AE1-173 E
50/50
100.688100.688
934501AD1-074 C
Adder
52.1070588235294144.291
958502AF2-144 E
Adder
1.89058823529411771.607
923862AB2-026 E
Adder
1.9247058823529411.636
924517AB2-100 E2
Adder
4.4917647058823533.818
316141AB2-099 E
Adder
0.38705882352941180.329
961941AG1-037 C
Adder
0.77294117647058820.657
961942AG1-037 E
Adder
0.51529411764705880.438
316088AB2-174 E
Adder
9.988.483
923263AB1-132 E OP
Adder
9.3023529411764717.907
923994AB2-040_E
Adder
9.4011764705882357.991
941032AE2-094 E
50/50
29.62229.622
941031AE2-094 C
50/50
66.13866.138
957481AF2-042 C
Adder
82.7976470588235370.378
957482AF2-042 E
Adder
55.1988235294117646.919
934621AD1-088 C
Adder
14.36470588235294312.21
944641AF1-129 C
Adder
153.60588235294117130.565
316240AF1-291 C
Adder
3.2635294117647062.774
925332AB2-190 E
Adder
12.07529411764705810.264
935162AD1-151 E
Adder
16.1505882352941213.728
316233AE1-074 C
50/50
4.1784.178
927226AC1-216 E
Adder
11.6423529411764739.896
924814AB2-134 E
Adder
19.07058823529411716.21
939191AE1-149 C
Adder
16.88000000000000314.348
3143316POE
50/50
2.1752.175
943461AF1-017 C
Adder
2.1352941176470591.815
942342AE2-247 E
Adder
3.262.771
936666AD2-085 E
Adder
8.8858823529411777.553
932596AC2-079 E
Adder
14.80823529411764712.587
316311AC2-079 C
Adder
9.0764705882352947.715
941591AE2-156 C
50/50
28.55328.553
316316AC1-027 C
50/50
0.5040.504
944601AF1-125 C
50/50
71.42271.422
944591AF1-124 C
50/50
72.79772.797
919152AA1-139 E1
Adder
6.5152941176470595.538
938532AE1-072 E
Adder
14.59294117647058912.404
3146326AYDLETT TAP
Adder
2.161.836
917122Z2-027 E
Adder
2.12941176470588231.81
901082W1-029 E
Adder
50.41764705882352642.855
938771AE1-103 C
Adder
4.5952941176470593.906
3145413WATKINS
Adder
1.07882352941176470.917
920692AA2-178 E
Adder
6.45.44
920042AA2-088 E OP
Adder
16.40941176470588313.948
934511AD1-075 C
Adder
13.02705882352941211.073
934521AD1-076 C
Adder
18.92352941176470816.085
960081AF2-299 C
Adder
2.87294117647058832.442
966622AG1-532 E
Adder
1.43647058823529421.221
3145723EMPORIA
Adder
0.66117647058823540.562
926072AC1-086 E
Adder
14.54823529411764812.366
923573AB1-173 E OP
Adder
5.0141176470588234.262
944011AF1-069 C
50/50
21.6121.61
938552AE1-074 E
50/50
2.1052.105
3150921YORKTN3
Adder
175.7670588235294149.402
934576AD1-082 E
Adder
6.9458823529411775.904
316084AB2-161 E
Adder
8.717647058823537.41
3145256KINGFORK
Adder
1.5952941176470591.356
3151101ELIZAR3
50/50
5.1725.172
3151081ELIZAR1
50/50
5.1085.108
3151091ELIZAR2
50/50
5.0195.019
925522AC1-027 E
50/50
1.9431.943
916191Z1-068 C
50/50
0.070.07
933292AC2-141 E
50/50
20.7620.76
926755AC1-161 E
50/50
20.7620.76
316294AC1-161 C
50/50
7.9477.947
933291AC2-141 C
50/50
48.63248.632
944602AF1-125 E
50/50
163.5163.5
941102AE2-104 E
Adder
8.4494117647058827.182
3145506HICKORY
50/50
3.4833.483
943612AF1-032 E
Adder
1.4682352941176471.248
957871AF2-081 C
Adder
15.93294117647058713.543
957872AF2-081 E
Adder
6.8282352941176485.804
316315AB2-025 C
50/50
0.650.65
940492AE2-034 E
Adder
4.84.08
3145946PLYMOUTH TP
Adder
0.50.425
934522AD1-076 E
Adder
9.6458823529411778.199
933982AD1-022 E
Adder
7.3576470588235296.254
938562AE1-075 E
Adder
1.64117647058823551.395
940641AE2-051 C
50/50
29.19229.192
943172AE2-346 E
Adder
0.92823529411764720.789
946282AF1-292 E
Adder
1.58588235294117651.348
918492AA1-063AE OP
Adder
6.2388235294117655.303
316336AC2-165 C
Adder
14.85411764705882312.626
944012AF1-069 E
50/50
8.3958.395
3152431Z1-086 GT3
50/50
17.32217.322
3152421Z1-086 GT2
50/50
17.32217.322
3151051BRUNSWICKS1
50/50
28.05928.059
934622AD1-088 E
Adder
6.9164705882352945.879
937482AD2-202 E
Adder
1.58941176470588231.351
934612AD1-087 E
Adder
5.42823529411764754.614
3152441Z1-086 ST
50/50
30.16230.162
963041AG1-153 C
50/50
9.159.15
3151021BRUNSWICKG1
50/50
13.50613.506
3151041BRUNSWICKG3
50/50
13.50613.506
316303AF2-085
50/50
6.8996.899
G-007PJM->LTFIMP_G-007
CMTX_NF
5.8875.887
SIGELTFEXP_SIGE->PJM
CLTF
0.3220.322
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6737.673
CBM South 2LTFEXP_CBM-S2->PJM
CBM
132.286132.286
CPLELTFEXP_CPLE->PJM
CLTF
16.09616.096
TVALTFEXP_TVA->PJM
CLTF
8.1488.148
O66PJM->LTFIMP_O-066
CMTX_NF
37.46537.465
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.00241.002
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.98729.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.2215.221
LAGNLTFEXP_LAGN->PJM
CLTF
10.36610.366
NYPJM->LTFIMP_NY
CLTF
2.7212.721
LGEELTFEXP_LGEE->PJM
CLTF
1.6421.642
WECLTFEXP_WEC->PJM
CLTF
0.8540.854

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.84 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4130.73
MW Contribution:136.39
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.16 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4734.49
MW Contribution:140.11
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
946262AF1-291 E
Adder
2.00235294117647071.702
938552AE1-074 E
50/50
1.9361.936
316160AE1-175 E
Adder
1.67529411764705881.424
3150921YORKTN3
Adder
176.88117647058823150.349
934576AD1-082 E
Adder
6.7411764705882365.73
316084AB2-161 E
Adder
8.467.191
3145256KINGFORK
Adder
1.61.36
3151101ELIZAR3
50/50
5.2135.213
3151081ELIZAR1
50/50
5.1485.148
3151091ELIZAR2
50/50
5.0595.059
925522AC1-027 E
50/50
1.961.96
916191Z1-068 C
50/50
0.0710.071
933292AC2-141 E
50/50
21.18321.183
926755AC1-161 E
50/50
21.18321.183
316294AC1-161 C
50/50
8.1098.109
933291AC2-141 C
50/50
49.62549.625
944602AF1-125 E
50/50
165.126165.126
941102AE2-104 E
Adder
8.4505882352941187.183
3145506HICKORY
50/50
3.5173.517
943612AF1-032 E
Adder
1.4764705882352941.255
957871AF2-081 C
Adder
16.07411764705882413.663
957872AF2-081 E
Adder
6.88823529411764755.855
940492AE2-034 E
Adder
4.8023529411764714.082
3145946PLYMOUTH TP
Adder
0.50.425
934522AD1-076 E
Adder
9.6317647058823528.187
933982AD1-022 E
Adder
7.346.239
938562AE1-075 E
Adder
1.53176470588235311.302
940641AE2-051 C
50/50
29.19929.199
943172AE2-346 E
Adder
0.92117647058823540.783
946282AF1-292 E
Adder
1.5564705882352941.323
918492AA1-063AE OP
Adder
6.1705882352941185.245
917332KELFORD E
Adder
2.4741176470588242.103
925122AB2-169 E
Adder
8.6764705882352937.375
944012AF1-069 E
50/50
8.3568.356
3152431Z1-086 GT3
50/50
17.22717.227
3152421Z1-086 GT2
50/50
17.22717.227
3151051BRUNSWICKS1
50/50
27.89627.896
934622AD1-088 E
Adder
6.8105882352941185.789
964242AG1-285 E
Adder
12.5610.676
937482AD2-202 E
Adder
1.5682352941176471.333
934612AD1-087 E
Adder
5.3588235294117644.555
944641AF1-129 C
Adder
134.3435294117647114.192
316240AF1-291 C
Adder
3.0047058823529412.554
925332AB2-190 E
Adder
11.5164705882352939.789
935162AD1-151 E
Adder
15.4776470588235313.156
316233AE1-074 C
50/50
3.8433.843
927226AC1-216 E
Adder
11.2188235294117659.536
924814AB2-134 E
Adder
18.37647058823529315.62
3150731STONECA
Adder
9.5694117647058838.134
940432AE2-027 E
Adder
12.12235294117647110.304
935161AD1-151 C
Adder
23.2152941176470619.733
934012AD1-025 E
Adder
14.52470588235294212.346
942341AE2-247 C
Adder
2.33294117647058831.983
316349AD2-085 C
Adder
5.3835294117647054.576
943462AF1-017 E
Adder
3.44470588235294132.928
935112AD1-144 E
Adder
1.48470588235294131.262
932046AC2-012 E
50/50
21.04921.049
944582AF1-123 E
50/50
167.759167.759
944592AF1-124 E
50/50
168.367168.367
958161AF2-110 C
Adder
2.16941176470588241.844
958162AF2-110 E
Adder
3.45058823529411772.933
316388AE2-253 GEN
50/50
3.1643.164
919153AA1-139 E2
Adder
6.57294117647058855.587
938531AE1-072 C
Adder
28.2329411764705923.998
913392Y1-086 E
Adder
3.51411764705882362.987
923832AB2-022 E
Adder
1.98352941176470581.686
938772AE1-103 E
Adder
6.3270588235294125.378
916042Z1-036 E
Adder
45.0211764705882438.268
3145393UNCAMP
Adder
9.4858823529411778.063
939411AE1-173 C
50/50
151.38151.38
934512AD1-075 E
Adder
6.622352941176475.629
934502AD1-074 E
Adder
26.48705882352941322.514
933981AD1-022 C
Adder
13.48352941176470711.461
924516AB2-100 E1
Adder
4.4035294117647063.743
900672V4-068 E
Adder
0.54588235294117650.464
918512AA1-065 E OP
Adder
8.4305882352941197.166
940642AE2-051 E
50/50
19.46619.466
960082AF2-299 E
Adder
1.88000000000000011.598
966621AG1-532 C
Adder
2.11529411764705881.798
946281AF1-292 C
Adder
2.33411764705882341.984
926071AC1-086 C
Adder
31.48235294117647226.76
3137643SOCKMAN
Adder
1.06823529411764720.908
3152411Z1-086 GT1
50/50
17.23317.233
3151031BRUNSWICKG2
50/50
13.42813.428
963042AG1-153 E
50/50
13.64513.645
964241AG1-285 C
Adder
18.8416.014
962962AG1-145 E
Adder
2.0305882352941181.726
939191AE1-149 C
Adder
16.1694117647058813.744
3143316POE
Adder
2.0705882352941181.76
943461AF1-017 C
Adder
2.1105882352941181.794
942342AE2-247 E
Adder
3.22235294117647042.739
936666AD2-085 E
Adder
8.7835294117647067.466
932596AC2-079 E
Adder
14.6612.461
316311AC2-079 C
Adder
8.9858823529411777.638
941591AE2-156 C
50/50
28.7728.77
316316AC1-027 C
50/50
0.5090.509
944601AF1-125 C
50/50
72.13372.133
944591AF1-124 C
50/50
73.52173.521
919152AA1-139 E1
Adder
6.57294117647058855.587
938532AE1-072 E
Adder
14.7176470588235312.51
3146326AYDLETT TAP
Adder
2.17764705882352951.851
917122Z2-027 E
Adder
2.1435294117647061.822
901082W1-029 E
Adder
50.6800000000000143.078
938771AE1-103 C
Adder
4.582352941176473.895
3145413WATKINS
Adder
1.07411764705882360.913
920692AA2-178 E
Adder
6.4035294117647065.443
920042AA2-088 E OP
Adder
16.29647058823529413.852
934511AD1-075 C
Adder
13.00823529411764811.057
934521AD1-076 C
Adder
18.8976470588235316.063
960081AF2-299 C
Adder
2.822.397
966622AG1-532 E
Adder
1.41058823529411771.199
3145723EMPORIA
Adder
0.65058823529411770.553
926072AC1-086 E
Adder
14.32823529411764712.179
923573AB1-173 E OP
Adder
4.9341176470588244.194
919692AA2-053 E OP
Adder
6.3423529411764715.391
944011AF1-069 C
50/50
21.50921.509
3152441Z1-086 ST
50/50
29.99829.998
963041AG1-153 C
50/50
9.0979.097
3151021BRUNSWICKG1
50/50
13.42813.428
3151041BRUNSWICKG3
50/50
13.42813.428
3150831SPRUNCA
Adder
12.67882352941176410.777
3150841SPRUNCB
Adder
12.67882352941176410.777
940431AE2-027 C
Adder
18.18352941176470615.456
942001AE2-212 C
Adder
3.1211764705882352.653
942002AE2-212 E
Adder
2.0811764705882351.769
961611AG1-000B C
Adder
23.7620.196
939192AE1-149 E
Adder
10.7800000000000019.163
939312AE1-162 E
Adder
2.21058823529411751.879
316375AC2-012 C
50/50
2.172.17
926662AC1-147 E
Adder
2.12823529411764721.809
916192Z1-068 E
50/50
3.0273.027
316185AD1-033 C
50/50
1.9851.985
934065AD1-033 E
50/50
8.0978.097
944581AF1-123 C
50/50
73.26173.261
941101AE2-104 C
Adder
5.3152941176470594.518
957492AF2-043 E
Adder
2.2717647058823531.931
937226AE2-253 E
50/50
9.4079.407
923852AB2-025 E
Adder
1.80470588235294121.534
940541AE2-040 C
Adder
4.4623529411764713.793
940482AE2-033 E
Adder
16.9129411764705914.376
940481AE2-033 C
Adder
25.0882352941176521.325
939412AE1-173 E
50/50
100.92100.92
934501AD1-074 C
Adder
52.03294117647059444.228
958502AF2-144 E
Adder
1.76470588235294111.5
923862AB2-026 E
Adder
1.7964705882352941.527
924517AB2-100 E2
Adder
4.4035294117647063.743
316141AB2-099 E
Adder
0.38352941176470590.326
961941AG1-037 C
Adder
0.76823529411764710.653
961942AG1-037 E
Adder
0.51176470588235290.435
316088AB2-174 E
Adder
9.8129411764705888.341
923263AB1-132 E OP
Adder
9.162352941176477.788
923994AB2-040_E
Adder
9.2505882352941197.863
941032AE2-094 E
50/50
29.48329.483
941031AE2-094 C
50/50
65.82865.828
957481AF2-042 C
Adder
81.8317647058823669.557
957482AF2-042 E
Adder
54.5552941176470646.372
934621AD1-088 C
Adder
14.14588235294117512.024
316303AF2-085
50/50
6.4766.476
G-007PJM->LTFIMP_G-007
CMTX_NF
5.4635.463
SIGELTFEXP_SIGE->PJM
CLTF
0.2970.297
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.547.54
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.173129.173
CPLELTFEXP_CPLE->PJM
CLTF
15.81915.819
TVALTFEXP_TVA->PJM
CLTF
7.767.76
O66PJM->LTFIMP_O-066
CMTX_NF
34.77734.777
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.34537.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.31928.319
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8474.847
LAGNLTFEXP_LAGN->PJM
CLTF
9.8929.892
NYPJM->LTFIMP_NY
CLTF
2.5392.539
LGEELTFEXP_LGEE->PJM
CLTF
1.4991.499
WECLTFEXP_WEC->PJM
CLTF
0.780.78

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.96 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4056.64
MW Contribution:131.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944641AF1-129 C
Adder
140.53529411764706119.455
316240AF1-291 C
Adder
2.99294117647058842.544
925332AB2-190 E
Adder
11.1200000000000019.452
935162AD1-151 E
Adder
14.89411764705882412.66
316233AE1-074 C
50/50
3.8973.897
927226AC1-216 E
Adder
10.7541176470588239.141
924814AB2-134 E
Adder
17.61647058823529514.974
939191AE1-149 C
Adder
15.69529411764705913.341
3143316POE
50/50
2.0282.028
943461AF1-017 C
Adder
2.01.7
942342AE2-247 E
Adder
3.0517647058823532.594
936666AD2-085 E
Adder
8.327.072
932596AC2-079 E
Adder
13.86941176470588211.789
316311AC2-079 C
Adder
8.5011764705882367.226
941591AE2-156 C
50/50
26.80726.807
316316AC1-027 C
50/50
0.4740.474
944601AF1-125 C
50/50
67.12767.127
944591AF1-124 C
50/50
68.4268.42
919152AA1-139 E1
Adder
6.1235294117647065.205
938532AE1-072 E
Adder
13.7176470588235311.66
3146326AYDLETT TAP
Adder
2.02941176470588271.725
917122Z2-027 E
Adder
2.00235294117647071.702
901082W1-029 E
Adder
47.440.29
938771AE1-103 C
Adder
4.3211764705882353.673
3145413WATKINS
Adder
1.0152941176470590.863
920692AA2-178 E
Adder
6.0258823529411775.122
920042AA2-088 E OP
Adder
15.46470588235294113.145
934511AD1-075 C
Adder
12.27176470588235310.431
934521AD1-076 C
Adder
17.82705882352941315.153
960081AF2-299 C
Adder
2.7152941176470592.308
966622AG1-532 E
Adder
1.35764705882352941.154
3145723EMPORIA
Adder
0.62588235294117660.532
926072AC1-086 E
Adder
13.7423529411764711.681
923573AB1-173 E OP
Adder
4.744.029
944011AF1-069 C
50/50
20.67620.676
3152441Z1-086 ST
50/50
28.84928.849
963041AG1-153 C
50/50
8.758.75
3151021BRUNSWICKG1
50/50
12.91612.916
3151041BRUNSWICKG3
50/50
12.91612.916
3150651CHESTF6
Adder
25.5882352941176521.75
946262AF1-291 E
Adder
1.99529411764705891.696
938552AE1-074 E
50/50
1.9631.963
3150921YORKTN3
Adder
163.19176470588235138.713
934576AD1-082 E
Adder
6.4764705882352945.505
316084AB2-161 E
Adder
8.1282352941176486.909
3145256KINGFORK
Adder
1.49529411764705871.271
3151101ELIZAR3
50/50
4.8574.857
3151081ELIZAR1
50/50
4.7964.796
3151091ELIZAR2
50/50
4.7134.713
3150831SPRUNCA
Adder
12.87647058823529510.945
3150841SPRUNCB
Adder
12.87647058823529510.945
940431AE2-027 C
Adder
17.9905882352941215.292
942001AE2-212 C
Adder
3.08941176470588232.626
942002AE2-212 E
Adder
2.0588235294117651.75
961611AG1-000B C
Adder
22.53529411764706219.155
939192AE1-149 E
Adder
10.4635294117647078.894
939312AE1-162 E
Adder
2.07764705882352941.766
316375AC2-012 C
50/50
2.0222.022
926662AC1-147 E
Adder
1.98235294117647071.685
916192Z1-068 E
50/50
2.8192.819
316185AD1-033 C
50/50
1.8471.847
934065AD1-033 E
50/50
7.5367.536
944581AF1-123 C
50/50
68.17868.178
941101AE2-104 C
Adder
4.9894117647058824.241
957492AF2-043 E
Adder
2.12235294117647081.804
937226AE2-253 E
Adder
8.7623529411764727.448
923852AB2-025 E
50/50
1.7471.747
940541AE2-040 C
50/50
4.3194.319
940482AE2-033 E
50/50
16.3616.36
940481AE2-033 C
50/50
24.26824.268
939412AE1-173 E
50/50
95.76595.765
934501AD1-074 C
Adder
49.0858823529411841.723
958502AF2-144 E
Adder
1.78705882352941181.519
923862AB2-026 E
Adder
1.81882352941176471.546
924517AB2-100 E2
Adder
4.2411764705882353.605
316088AB2-174 E
Adder
9.4352941176470598.02
923263AB1-132 E OP
Adder
8.7870588235294127.469
923994AB2-040_E
Adder
8.8870588235294117.554
941032AE2-094 E
50/50
28.34228.342
941031AE2-094 C
50/50
63.2863.28
957481AF2-042 C
Adder
79.0188235294117667.166
957482AF2-042 E
Adder
52.67882352941176544.777
934621AD1-088 C
Adder
13.69411764705882511.64
925522AC1-027 E
50/50
1.8261.826
916191Z1-068 C
50/50
0.0660.066
933292AC2-141 E
50/50
19.5219.52
926755AC1-161 E
50/50
19.5219.52
316294AC1-161 C
50/50
7.4737.473
933291AC2-141 C
50/50
45.72845.728
944602AF1-125 E
50/50
153.669153.669
941102AE2-104 E
Adder
7.9317647058823536.742
3145506HICKORY
50/50
3.2743.274
943612AF1-032 E
Adder
1.38000000000000011.173
957871AF2-081 C
Adder
14.97647058823529412.73
957872AF2-081 E
Adder
6.4188235294117665.456
316315AB2-025 C
50/50
0.6130.613
940492AE2-034 E
Adder
4.5188235294117653.841
3145946PLYMOUTH TP
Adder
0.47058823529411770.4
934522AD1-076 E
Adder
9.0858823529411777.723
933982AD1-022 E
Adder
6.9329411764705885.893
938562AE1-075 E
Adder
1.55058823529411781.318
940641AE2-051 C
50/50
27.86227.862
946282AF1-292 E
Adder
1.49882352941176471.274
918492AA1-063AE OP
Adder
5.8905882352941185.007
316336AC2-165 C
Adder
14.02588235294117811.922
944012AF1-069 E
50/50
8.0328.032
3152431Z1-086 GT3
50/50
16.56716.567
3152421Z1-086 GT2
50/50
16.56716.567
3151051BRUNSWICKS1
50/50
26.83226.832
934622AD1-088 E
Adder
6.5941176470588245.605
937482AD2-202 E
Adder
1.5152941176470591.288
934612AD1-087 E
Adder
5.17764705882352954.401
940432AE2-027 E
Adder
11.99411764705882410.195
935161AD1-151 C
Adder
22.3418.989
934012AD1-025 E
Adder
13.92352941176470811.835
942341AE2-247 C
Adder
2.21058823529411751.879
316349AD2-085 C
Adder
5.09882352941176454.334
943462AF1-017 E
Adder
3.2623529411764712.773
935112AD1-144 E
Adder
1.3882352941176471.18
932046AC2-012 E
50/50
19.61519.615
944582AF1-123 E
50/50
156.119156.119
944592AF1-124 E
50/50
156.684156.684
958161AF2-110 C
Adder
2.03529411764705871.73
958162AF2-110 E
Adder
3.2376470588235292.752
919153AA1-139 E2
Adder
6.1235294117647065.205
938531AE1-072 C
Adder
26.31411764705882622.367
913392Y1-086 E
Adder
3.282.788
923832AB2-022 E
Adder
1.8517647058823531.574
938772AE1-103 E
Adder
5.9670588235294125.072
916042Z1-036 E
Adder
42.2247058823529435.891
3145393UNCAMP
Adder
8.9552941176470597.612
939411AE1-173 C
50/50
143.648143.648
934512AD1-075 E
Adder
6.2470588235294125.31
934502AD1-074 E
Adder
24.98705882352941321.239
933981AD1-022 C
Adder
12.73411764705882410.824
924516AB2-100 E1
Adder
4.2411764705882353.605
900672V4-068 E
Adder
0.51764705882352950.44
940642AE2-051 E
50/50
18.57518.575
960082AF2-299 E
Adder
1.81058823529411761.539
966621AG1-532 C
Adder
2.03647058823529431.731
946281AF1-292 C
Adder
2.24823529411764731.911
933502AC2-165 E
Adder
10.5564705882352968.973
926071AC1-086 C
Adder
30.19411764705882525.665
3137643SOCKMAN
Adder
1.02470588235294110.871
3152411Z1-086 GT1
50/50
16.57316.573
3151031BRUNSWICKG2
50/50
12.91612.916
963042AG1-153 E
50/50
13.12513.125
964241AG1-285 C
Adder
12.04352941176470710.237
316303AF2-085
50/50
6.5326.532
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5125.512
SIGELTFEXP_SIGE->PJM
CLTF
0.30.3
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.2837.283
CBM South 2LTFEXP_CBM-S2->PJM
CBM
125.379125.379
CPLELTFEXP_CPLE->PJM
CLTF
15.2815.28
TVALTFEXP_TVA->PJM
CLTF
7.6637.663
O66PJM->LTFIMP_O-066
CMTX_NF
35.08335.083
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.98737.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.12228.122
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8684.868
LAGNLTFEXP_LAGN->PJM
CLTF
9.7559.755
NYPJM->LTFIMP_NY
CLTF
2.5532.553
LGEELTFEXP_LGEE->PJM
CLTF
1.5241.524
WECLTFEXP_WEC->PJM
CLTF
0.7920.792

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.85 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3279.97
MW Contribution:77.5
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944631AF1-128 C
Adder
48.040.8
3150651CHESTF6
Adder
24.50588235294117520.83
943471AF1-018 C
Adder
7.9588235294117656.765
3150921YORKTN3
Adder
157.0388235294118133.483
316083AB2-161 C
80/20
0.7870.787
316072AD1-144 C
80/20
0.4020.402
3151101ELIZAR3
80/20
4.7154.715
3151081ELIZAR1
80/20
4.6564.656
3151091ELIZAR2
80/20
4.5754.575
916191Z1-068 C
80/20
0.0640.064
316294AC1-161 C
80/20
7.267.26
933291AC2-141 C
80/20
44.42644.426
316305AF2-043 C
80/20
0.5050.505
957871AF2-081 C
80/20
14.54714.547
316315AB2-025 C
80/20
0.5980.598
961951AG1-038 C
Adder
3.3341176470588242.834
936591AD2-074 C
Adder
5.7647058823529424.9
3151151S HAMPT1
80/20
2.1352.135
316313AB2-026 C
80/20
0.5480.548
940641AE2-051 C
80/20
27.30727.307
316336AC2-165 C
Adder
13.69411764705882511.64
3152431Z1-086 GT3
80/20
16.26116.261
3152421Z1-086 GT2
80/20
16.26116.261
316274AC1-208 C
Adder
12.4023529411764710.542
3151051BRUNSWICKS1
80/20
26.33526.335
3151531CLOVER1
80/20
17.87717.877
934611AD1-087 C
80/20
1.761.76
3151311EDGECMA
Adder
20.74352941176470817.632
3138533PONTONDP
Adder
0.87294117647058820.742
3150831SPRUNCA
80/20
12.34712.347
3150841SPRUNCB
80/20
12.34712.347
3150861SPRUNCD
80/20
0.2220.222
940431AE2-027 C
Adder
17.26588235294117614.676
942001AE2-212 C
80/20
2.9732.973
961611AG1-000B C
Adder
21.72352941176470518.465
316236AE1-162 C
80/20
0.4930.493
3150981CHESPKA
80/20
0.6340.634
316375AC2-012 C
80/20
1.9631.963
3150991CHESPKB
80/20
1.051.05
316185AD1-033 C
80/20
1.7941.794
944581AF1-123 C
80/20
66.2266.22
941101AE2-104 C
80/20
4.8434.843
313526AB2-022 C
80/20
0.5460.546
316320Y1-086 C
80/20
0.3190.319
316321Z2-027 C
80/20
0.5270.527
940541AE2-040 C
80/20
4.2084.208
940481AE2-033 C
80/20
23.64823.648
943741AF1-042 C
Adder
3.01647058823529422.564
934501AD1-074 C
Adder
47.763529411764740.599
962861AG1-135 C
Adder
6.1588235294117655.235
316405AF2-144 C
80/20
0.4280.428
961941AG1-037 C
Adder
0.71058823529411760.604
941031AE2-094 C
80/20
62.11762.117
934321AD1-056 C
Adder
8.5376470588235297.257
934331AD1-057 C
Adder
4.7623529411764714.048
957481AF2-042 C
80/20
77.49977.499
961671AG1-007 C
Adder
1.26588235294117671.076
934621AD1-088 C
80/20
13.42613.426
946301AF1-294 C
Adder
4.8470588235294124.12
958211AF2-115 C
Adder
2.94705882352941152.505
942461AE2-259 C
Adder
12.70588235294117810.8
3150601CHESTF5
Adder
76.7117647058823665.205
944641AF1-129 C
Adder
134.59058823529412114.402
316240AF1-291 C
Adder
2.86941176470588262.439
316233AE1-074 C
80/20
3.7763.776
939191AE1-149 C
80/20
15.16215.162
940551AE2-041 C
Adder
7.9588235294117656.765
3151161SURRY 1
80/20
33.88933.889
3151211GRAVEL5
80/20
3.4433.443
316381AD1-082 C
80/20
1.7951.795
957601AF2-054 C
Adder
2.37764705882352922.021
3152331SURRY 2
80/20
34.47934.479
943461AF1-017 C
80/20
1.9381.938
316311AC2-079 C
80/20
8.2428.242
316036AC1-147 C
80/20
0.5360.536
941591AE2-156 C
80/20
26.02126.021
316316AC1-027 C
80/20
0.460.46
944601AF1-125 C
80/20
65.265.2
944591AF1-124 C
80/20
66.45566.455
316018AA1-139 ULT2
80/20
1.5751.575
3156056W1-029WIND
80/20
1.1231.123
938771AE1-103 C
80/20
4.24.2
934511AD1-075 C
Adder
11.94117647058823610.15
934521AD1-076 C
Adder
17.34705882352941214.745
316365AB2-100 C1
80/20
1.3721.372
960081AF2-299 C
Adder
2.64941176470588242.252
944011AF1-069 C
80/20
20.29620.296
3152441Z1-086 ST
80/20
28.31528.315
963041AG1-153 C
80/20
8.5888.588
3151021BRUNSWICKG1
80/20
12.67612.676
3151041BRUNSWICKG3
80/20
12.67612.676
316263AC1-034 C
Adder
8.8741176470588247.543
959311AF2-222 C
Adder
23.07176470588235519.611
936261AD2-033 C
Adder
17.57529411764705814.939
961791AG1-021 C
Adder
2.35764705882352972.004
964791AG1-342 C
Adder
4.6788235294117653.977
3150851SPRUNCC
80/20
0.2220.222
316169AC1-164 GEN
Adder
44.9588235294117738.215
3150731STONECA
Adder
8.9505882352941187.608
935161AD1-151 C
Adder
21.46588235294117618.246
3151221GRAVEL6
80/20
3.4833.483
3151201GRAVEL4
80/20
3.4873.487
942341AE2-247 C
80/20
2.1432.143
316349AD2-085 C
80/20
4.9434.943
958161AF2-110 C
80/20
1.9761.976
316246AF1-032 C
80/20
0.4130.413
316388AE2-253 GEN
80/20
2.8622.862
316017AA1-139 ULT1
80/20
1.5751.575
938531AE1-072 C
80/20
25.56125.561
3156116Z1-036WIND
80/20
0.9440.944
939411AE1-173 C
80/20
140.502140.502
933981AD1-022 C
Adder
12.39411764705882410.535
316258AE1-075 C
80/20
0.5030.503
316023AB2-100 C2
80/20
1.3721.372
966621AG1-532 C
Adder
1.9870588235294121.689
946281AF1-292 C
Adder
2.19294117647058861.864
926071AC1-086 C
Adder
29.4425.024
3137643SOCKMAN
Adder
1.00.85
3152411Z1-086 GT1
80/20
16.26616.266
3151031BRUNSWICKG2
80/20
12.67612.676
927021AC1-189 C
Adder
11.4094117647058839.698
3151541CLOVER2
80/20
17.7117.71
964241AG1-285 C
Adder
17.89058823529411815.207
937481AD2-202 C
80/20
0.5110.511
962561AG1-105 C
Adder
11.8176470588235310.045
316303AF2-085
80/20
6.3826.382
SIGELTFEXP_SIGE->PJM
CLTF
0.2960.296
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1347.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.889122.889
CPLELTFEXP_CPLE->PJM
CLTF
14.96614.966
TVALTFEXP_TVA->PJM
CLTF
7.5327.532
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.6437.64
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.68227.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8064.806
LAGNLTFEXP_LAGN->PJM
CLTF
9.5879.587
NYPJM->LTFIMP_NY
CLTF
2.4692.469
LGEELTFEXP_LGEE->PJM
CLTF
1.5071.507
WECLTFEXP_WEC->PJM
CLTF
0.7840.784

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.49 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3222.37
MW Contribution:97.65
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.18 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3432.65
MW Contribution:98.4
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
927226AC1-216 E
Adder
6.8258823529411765.802
924814AB2-134 E
Adder
11.1823529411764729.505
962962AG1-145 E
Adder
1.36235294117647051.158
939191AE1-149 C
Adder
8.8411764705882367.515
957832AF2-077 E
Adder
1.38000000000000011.173
3152331SURRY 2
50/50
52.22952.229
943461AF1-017 C
Adder
1.75294117647058821.49
942342AE2-247 E
Adder
2.6752941176470592.274
936666AD2-085 E
Adder
7.2929411764705886.199
932596AC2-079 E
Adder
12.36705882352941210.512
316311AC2-079 C
Adder
7.586.443
316036AC1-147 C
50/50
0.60.6
941591AE2-156 C
50/50
29.1829.18
316316AC1-027 C
50/50
0.520.52
944601AF1-125 C
50/50
74.70974.709
944591AF1-124 C
50/50
76.14876.148
316018AA1-139 ULT2
50/50
1.781.78
919152AA1-139 E1
50/50
6.7236.723
938532AE1-072 E
50/50
14.99614.996
3146326AYDLETT TAP
50/50
2.2162.216
917122Z2-027 E
50/50
2.1312.131
901082W1-029 E
50/50
49.64949.649
3156056W1-029WIND
50/50
1.211.21
938771AE1-103 C
50/50
4.0814.081
3145413WATKINS
Adder
0.93058823529411770.791
920692AA2-178 E
50/50
5.9125.912
920042AA2-088 E OP
Adder
13.60117647058823611.561
934511AD1-075 C
Adder
11.6964705882352959.942
934521AD1-076 C
Adder
16.99176470588235314.443
960081AF2-299 C
Adder
1.91882352941176481.631
966622AG1-532 E
Adder
0.95882352941176460.815
3145723EMPORIA
Adder
0.44705882352941180.38
926072AC1-086 E
Adder
10.3658823529411768.811
923573AB1-173 E OP
Adder
3.50352941176470622.978
919692AA2-053 E OP
Adder
4.8294117647058834.105
944011AF1-069 C
50/50
16.3216.32
926206AC1-098 E
Adder
4.2070588235294123.576
963041AG1-153 C
Adder
6.8564705882352955.828
925785AC1-054 E
Adder
3.63176470588235353.087
922923AB1-081 E OP
Adder
4.0270588235294123.423
316263AC1-034 C
Adder
7.1729411764705896.097
959311AF2-222 C
Adder
15.45647058823529513.138
936261AD2-033 C
Adder
11.82117647058823610.048
962562AG1-105 E
Adder
5.74.845
964791AG1-342 C
Adder
3.39411764705882352.885
316160AE1-175 E
Adder
1.12470588235294120.956
3150921YORKTN3
50/50
162.48162.48
934576AD1-082 E
Adder
4.4847058823529413.812
316084AB2-161 E
Adder
5.6282352941176474.784
3145256KINGFORK
50/50
1.5181.518
316072AD1-144 C
50/50
0.4210.421
3151101ELIZAR3
50/50
5.3035.303
3151081ELIZAR1
50/50
5.2375.237
3151091ELIZAR2
50/50
5.1465.146
925522AC1-027 E
50/50
2.0032.003
916191Z1-068 C
50/50
0.0720.072
933292AC2-141 E
50/50
24.4824.48
926755AC1-161 E
50/50
24.4824.48
316294AC1-161 C
50/50
9.3719.371
933291AC2-141 C
50/50
57.34757.347
944602AF1-125 E
50/50
171.025171.025
941102AE2-104 E
50/50
7.8957.895
3145506HICKORY
50/50
3.633.63
943612AF1-032 E
50/50
1.4511.451
316305AF2-043 C
50/50
0.5470.547
957871AF2-081 C
50/50
16.44116.441
957872AF2-081 E
50/50
7.0467.046
940492AE2-034 E
50/50
4.4344.434
3145946PLYMOUTH TP
Adder
0.451764705882352960.384
934522AD1-076 E
Adder
8.667.361
933982AD1-022 E
Adder
6.5129411764705885.536
940641AE2-051 C
50/50
24.20324.203
943172AE2-346 E
Adder
0.76823529411764710.653
946282AF1-292 E
Adder
1.05882352941176470.9
918492AA1-063AE OP
Adder
4.80941176470588254.088
917332KELFORD E
Adder
2.01647058823529421.714
925122AB2-169 E
Adder
7.4694117647058836.349
944012AF1-069 E
50/50
6.346.34
932632AC2-084 E
Adder
3.71882352941176463.161
926214AC1-099 E
Adder
1.38941176470588231.181
316274AC1-208 C
Adder
10.168.636
927146AC1-208 E
Adder
4.5117647058823533.835
917512Z2-088 E OP1
Adder
5.58588235294117654.748
917342Z2-044 E
Adder
0.65529411764705890.557
934622AD1-088 E
Adder
4.70470588235294153.999
964242AG1-285 E
Adder
8.5011764705882367.226
937482AD2-202 E
Adder
1.1129411764705880.946
934612AD1-087 E
Adder
3.80117647058823543.231
3151311EDGECMA
Adder
16.76352941176470814.249
924162AB2-060 E OP
Adder
4.1870588235294123.559
964792AG1-342 E
Adder
2.2623529411764711.923
927255AC1-221 E
Adder
3.5270588235294122.998
932763AC2-100 E
Adder
2.3941176470588242.035
935161AD1-151 C
Adder
9.2600000000000027.871
934012AD1-025 E
Adder
8.837647058823537.512
3144216WINCHST
50/50
0.1770.177
942341AE2-247 C
Adder
1.93764705882352951.647
316349AD2-085 C
Adder
4.4694117647058833.799
943462AF1-017 E
Adder
2.86000000000000032.431
935112AD1-144 E
50/50
1.4091.409
932046AC2-012 E
50/50
21.31821.318
944582AF1-123 E
50/50
173.752173.752
944592AF1-124 E
50/50
174.381174.381
958161AF2-110 C
50/50
2.0262.026
958162AF2-110 E
50/50
3.2233.223
316246AF1-032 C
50/50
0.4470.447
316388AE2-253 GEN
50/50
3.2483.248
316017AA1-139 ULT1
50/50
1.781.78
919153AA1-139 E2
50/50
6.7236.723
938531AE1-072 C
50/50
28.76728.767
913392Y1-086 E
50/50
3.5213.521
923832AB2-022 E
50/50
1.9881.988
938772AE1-103 E
50/50
5.6365.636
916042Z1-036 E
50/50
42.96342.963
3156116Z1-036WIND
50/50
0.9890.989
3145393UNCAMP
Adder
8.367.106
315614AA2-178 C
50/50
2.2542.254
939411AE1-173 C
50/50
132.376132.376
934512AD1-075 E
Adder
5.95411764705882355.061
934502AD1-074 E
Adder
23.81647058823529420.244
933981AD1-022 C
Adder
11.96352941176470710.169
924516AB2-100 E1
Adder
2.92235294117647062.484
900672V4-068 E
Adder
0.452941176470588240.385
918512AA1-065 E OP
Adder
7.1905882352941186.112
940642AE2-051 E
50/50
16.13516.135
960082AF2-299 E
Adder
1.27882352941176471.087
966621AG1-532 C
Adder
1.43882352941176481.223
946281AF1-292 C
Adder
1.58823529411764721.35
926071AC1-086 C
Adder
22.77647058823529519.36
3137643SOCKMAN
Adder
0.77882352941176480.662
963042AG1-153 E
Adder
10.2835294117647068.741
918532AA1-067 E
Adder
0.85764705882352940.729
919710AA2-057 E
Adder
4.43.74
927021AC1-189 C
Adder
9.768.296
964241AG1-285 C
Adder
12.75176470588235310.839
924022AB2-043 E O1
Adder
5.1070588235294124.341
924152AB2-059 E OP
Adder
5.70470588235294154.849
3147223TWITTYS
Adder
0.89647058823529410.762
959312AF2-222 E
Adder
10.3552941176470598.802
924302AB2-077 E O1
Adder
1.3164705882352941.119
962561AG1-105 C
Adder
8.5494117647058847.267
961611AG1-000B C
Adder
17.5717647058823514.936
939192AE1-149 E
Adder
5.8941176470588235.01
939312AE1-162 E
50/50
1.9371.937
316236AE1-162 C
50/50
0.4750.475
3150981CHESPKA
50/50
0.7090.709
316375AC2-012 C
50/50
2.1982.198
926662AC1-147 E
50/50
2.1552.155
3150991CHESPKB
50/50
1.1761.176
916192Z1-068 E
50/50
3.0983.098
316185AD1-033 C
50/50
2.0522.052
934065AD1-033 E
50/50
8.3718.371
944581AF1-123 C
50/50
75.87875.878
941101AE2-104 C
50/50
4.9664.966
957492AF2-043 E
50/50
2.2332.233
937226AE2-253 E
50/50
9.6579.657
313526AB2-022 C
50/50
0.6030.603
316320Y1-086 C
50/50
0.3530.353
316321Z2-027 C
50/50
0.5770.577
923852AB2-025 E
Adder
1.06941176470588250.909
940541AE2-040 C
Adder
2.6435294117647062.247
940482AE2-033 E
Adder
10.1729411764705898.647
940481AE2-033 C
Adder
15.09058823529411912.827
940491AE2-034 C
50/50
1.6591.659
939412AE1-173 E
50/50
88.25188.251
934501AD1-074 C
Adder
46.7858823529411839.768
924517AB2-100 E2
Adder
2.92235294117647062.484
316141AB2-099 E
Adder
0.320.272
961941AG1-037 C
Adder
0.640.544
961942AG1-037 E
Adder
0.427058823529411770.363
316088AB2-174 E
Adder
6.877647058823535.846
923263AB1-132 E OP
Adder
6.6282352941176485.634
923994AB2-040_E
Adder
6.5694117647058825.584
941032AE2-094 E
50/50
22.37122.371
941031AE2-094 C
50/50
49.94849.948
934321AD1-056 C
Adder
6.7670588235294115.752
934332AD1-057 E
Adder
1.96588235294117661.671
934322AD1-056 E
Adder
3.6705882352941183.12
934331AD1-057 C
Adder
3.7752941176470593.209
927022AC1-189 E
Adder
4.86235294117647054.133
957481AF2-042 C
Adder
58.59176470588235549.803
957482AF2-042 E
Adder
39.0611764705882433.202
961672AG1-007 E
Adder
0.59882352941176480.509
961671AG1-007 C
Adder
1.05647058823529430.898
934621AD1-088 C
Adder
9.7717647058823538.306
925595AC1-034 E
Adder
5.4105882352941184.599
925612AC1-036 E
Adder
0.80823529411764720.687
924322AB2-079 E O1
Adder
1.3164705882352941.119
924312AB2-078 E O1
Adder
1.3164705882352941.119
936262AD2-033 E
Adder
7.8811764705882356.699
935172AD1-152 E
Adder
5.5847058823529414.747
926274AC1-105 E
Adder
2.5482352941176472.166
943902AF1-058 E
Adder
1.21411764705882351.032
G-007PJM->LTFIMP_G-007
CMTX_NF
3.0313.031
SIGELTFEXP_SIGE->PJM
CLTF
0.160.16
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.515.51
CBM South 2LTFEXP_CBM-S2->PJM
CBM
91.70491.704
CPLELTFEXP_CPLE->PJM
CLTF
11.56611.566
TVALTFEXP_TVA->PJM
CLTF
4.9264.926
O66PJM->LTFIMP_O-066
CMTX_NF
19.32919.329
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.74418.744
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.28317.283
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.712.71
LAGNLTFEXP_LAGN->PJM
CLTF
6.3446.344
NYPJM->LTFIMP_NY
CLTF
1.4491.449
LGEELTFEXP_LGEE->PJM
CLTF
0.760.76
WECLTFEXP_WEC->PJM
CLTF
0.3980.398

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.39 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3219.08
MW Contribution:97.2
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935162AD1-151 E
Adder
9.3141176470588247.917
927226AC1-216 E
Adder
7.2470588235294126.16
924814AB2-134 E
Adder
11.87058823529411810.09
962962AG1-145 E
Adder
1.40705882352941171.196
961611AG1-000B C
Adder
18.24117647058823615.505
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
316236AE1-162 C
50/50
0.4850.485
3150981CHESPKA
50/50
0.7150.715
316375AC2-012 C
50/50
2.2162.216
926662AC1-147 E
50/50
2.1732.173
3150991CHESPKB
50/50
1.1851.185
916192Z1-068 E
50/50
3.1213.121
316185AD1-033 C
50/50
2.0652.065
934065AD1-033 E
50/50
8.4268.426
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
957492AF2-043 E
50/50
2.2562.256
937226AE2-253 E
50/50
9.7279.727
313526AB2-022 C
50/50
0.6090.609
316320Y1-086 C
50/50
0.3560.356
316321Z2-027 C
50/50
0.5830.583
923852AB2-025 E
Adder
1.22235294117647041.039
940541AE2-040 C
Adder
3.02117647058823562.568
940482AE2-033 E
Adder
11.5564705882352949.823
940481AE2-033 C
Adder
17.1423529411764714.571
940491AE2-034 C
50/50
1.6871.687
939412AE1-173 E
50/50
87.63687.636
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
316141AB2-099 E
Adder
0.32941176470588240.28
961941AG1-037 C
Adder
0.65882352941176480.56
961942AG1-037 E
Adder
0.43882352941176470.373
316088AB2-174 E
Adder
7.3223529411764716.224
923263AB1-132 E OP
Adder
7.045.984
923994AB2-040_E
Adder
6.96705882352941155.922
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934321AD1-056 C
Adder
7.0682352941176476.008
934332AD1-057 E
Adder
2.05294117647058851.745
934322AD1-056 E
Adder
3.83411764705882343.259
934331AD1-057 C
Adder
3.94352941176470573.352
927022AC1-189 E
Adder
4.9929411764705884.244
957481AF2-042 C
Adder
58.3200000000000149.572
957482AF2-042 E
Adder
38.8833.048
961672AG1-007 E
Adder
0.61647058823529410.524
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
925595AC1-034 E
Adder
5.5800000000000014.743
925612AC1-036 E
Adder
0.81882352941176460.696
924322AB2-079 E O1
Adder
1.3364705882352941.136
924312AB2-078 E O1
Adder
1.3364705882352941.136
936262AD2-033 E
Adder
8.0352941176470596.83
935172AD1-152 E
Adder
5.5800000000000014.743
926274AC1-105 E
Adder
2.56470588235294142.18
943902AF1-058 E
Adder
1.21882352941176491.036
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
934576AD1-082 E
Adder
4.8152941176470594.093
316084AB2-161 E
Adder
6.0435294117647055.137
3145256KINGFORK
50/50
1.5391.539
316072AD1-144 C
50/50
0.4270.427
3151101ELIZAR3
50/50
5.3455.345
3151081ELIZAR1
50/50
5.2785.278
3151091ELIZAR2
50/50
5.1875.187
925522AC1-027 E
50/50
2.0192.019
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
926755AC1-161 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
933291AC2-141 C
50/50
57.45157.451
944602AF1-125 E
50/50
172.13172.13
941102AE2-104 E
50/50
8.0328.032
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
316305AF2-043 C
50/50
0.5530.553
957871AF2-081 C
50/50
16.56416.564
957872AF2-081 E
50/50
7.0997.099
940492AE2-034 E
50/50
4.514.51
3145946PLYMOUTH TP
Adder
0.460.391
934522AD1-076 E
Adder
8.832941176470597.508
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
943172AE2-346 E
Adder
0.79058823529411770.672
946282AF1-292 E
Adder
1.13647058823529410.966
918492AA1-063AE OP
Adder
5.04.25
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
944012AF1-069 E
Adder
6.24470588235294165.308
932632AC2-084 E
Adder
3.8494117647058823.272
926214AC1-099 E
Adder
1.43882352941176481.223
316274AC1-208 C
Adder
10.5388235294117658.958
927146AC1-208 E
Adder
4.6800000000000013.978
917512Z2-088 E OP1
Adder
5.7423529411764714.881
917342Z2-044 E
Adder
0.6764705882352940.575
934622AD1-088 E
Adder
4.7082352941176474.002
964242AG1-285 E
Adder
8.5717647058823537.286
937482AD2-202 E
Adder
1.11058823529411770.944
934612AD1-087 E
Adder
3.79294117647058873.224
3151311EDGECMA
Adder
17.2952941176470614.701
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
927255AC1-221 E
Adder
2.40941176470588262.048
935161AD1-151 C
Adder
13.97176470588235211.876
934012AD1-025 E
Adder
9.3823529411764717.975
3144216WINCHST
50/50
0.180.18
942341AE2-247 C
Adder
2.00470588235294131.704
316349AD2-085 C
Adder
4.6258823529411773.932
943462AF1-017 E
Adder
2.962.516
935112AD1-144 E
50/50
1.4291.429
932046AC2-012 E
50/50
21.49421.494
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
958161AF2-110 C
50/50
2.0612.061
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
316017AA1-139 ULT1
50/50
1.7931.793
919153AA1-139 E2
50/50
6.7746.774
938531AE1-072 C
50/50
28.99428.994
913392Y1-086 E
50/50
3.5543.554
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
3156116Z1-036WIND
50/50
1.0021.002
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
939411AE1-173 C
50/50
131.454131.454
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
933981AD1-022 C
Adder
12.2223529411764710.389
924516AB2-100 E1
Adder
3.19529411764705932.716
900672V4-068 E
Adder
0.46705882352941180.397
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
960082AF2-299 E
Adder
1.37411764705882341.168
966621AG1-532 C
Adder
1.54588235294117651.314
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
3137643SOCKMAN
Adder
0.820.697
963042AG1-153 E
Adder
10.1470588235294118.625
918532AA1-067 E
Adder
0.87882352941176480.747
919710AA2-057 E
Adder
4.5505882352941183.868
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924022AB2-043 E O1
Adder
5.1847058823529414.407
924152AB2-059 E OP
Adder
5.8823529411764715
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
924302AB2-077 E O1
Adder
1.3364705882352941.136
962561AG1-105 C
Adder
8.6352941176470587.34
939191AE1-149 C
Adder
9.8705882352941188.39
3143316POE
Adder
1.15647058823529410.983
957832AF2-077 E
Adder
1.4235294117647061.21
3152331SURRY 2
50/50
52.46452.464
943461AF1-017 C
Adder
1.81411764705882361.542
942342AE2-247 E
Adder
2.76823529411764732.353
936666AD2-085 E
Adder
7.5470588235294126.415
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
316036AC1-147 C
50/50
0.6050.605
941591AE2-156 C
50/50
29.41729.417
316316AC1-027 C
50/50
0.5240.524
944601AF1-125 C
50/50
75.19275.192
944591AF1-124 C
50/50
76.6476.64
316018AA1-139 ULT2
50/50
1.7931.793
919152AA1-139 E1
50/50
6.7746.774
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
901082W1-029 E
50/50
50.20950.209
3156056W1-029WIND
50/50
1.2241.224
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
920692AA2-178 E
50/50
6.0146.014
920042AA2-088 E OP
Adder
14.01647058823529311.914
934511AD1-075 C
Adder
11.92941176470588310.14
934521AD1-076 C
Adder
17.32941176470588514.73
960081AF2-299 C
Adder
2.061.751
966622AG1-532 E
Adder
1.03058823529411760.876
3145723EMPORIA
Adder
0.47882352941176470.407
926072AC1-086 E
Adder
11.0094117647058839.358
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
944011AF1-069 C
Adder
16.07529411764705813.664
926206AC1-098 E
Adder
4.3541176470588243.701
963041AG1-153 C
Adder
6.7647058823529415.75
925785AC1-054 E
Adder
3.7423529411764713.181
922923AB1-081 E OP
Adder
4.1529411764705883.53
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
936261AD2-033 C
Adder
12.05176470588235410.244
962562AG1-105 E
Adder
5.75647058823529444.893
964791AG1-342 C
Adder
3.42470588235294132.911
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.39 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3219.08
MW Contribution:97.2
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961611AG1-000B C
Adder
18.24117647058823615.505
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
934576AD1-082 E
Adder
4.8152941176470594.093
316084AB2-161 E
Adder
6.0435294117647055.137
3145256KINGFORK
50/50
1.5391.539
316072AD1-144 C
50/50
0.4270.427
3151101ELIZAR3
50/50
5.3455.345
3151081ELIZAR1
50/50
5.2785.278
3151091ELIZAR2
50/50
5.1875.187
925522AC1-027 E
50/50
2.0192.019
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
926755AC1-161 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
933291AC2-141 C
50/50
57.45157.451
944602AF1-125 E
50/50
172.13172.13
941102AE2-104 E
50/50
8.0328.032
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
316305AF2-043 C
50/50
0.5530.553
957871AF2-081 C
50/50
16.56416.564
957872AF2-081 E
50/50
7.0997.099
940492AE2-034 E
50/50
4.514.51
3145946PLYMOUTH TP
Adder
0.460.391
934522AD1-076 E
Adder
8.832941176470597.508
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
943172AE2-346 E
Adder
0.79058823529411770.672
946282AF1-292 E
Adder
1.13647058823529410.966
918492AA1-063AE OP
Adder
5.04.25
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
944012AF1-069 E
Adder
6.24470588235294165.308
932632AC2-084 E
Adder
3.8494117647058823.272
926214AC1-099 E
Adder
1.43882352941176481.223
316274AC1-208 C
Adder
10.5388235294117658.958
927146AC1-208 E
Adder
4.6800000000000013.978
917512Z2-088 E OP1
Adder
5.7423529411764714.881
917342Z2-044 E
Adder
0.6764705882352940.575
934622AD1-088 E
Adder
4.7082352941176474.002
964242AG1-285 E
Adder
8.5717647058823537.286
937482AD2-202 E
Adder
1.11058823529411770.944
934612AD1-087 E
Adder
3.79294117647058873.224
3151311EDGECMA
Adder
17.2952941176470614.701
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
927255AC1-221 E
Adder
2.40941176470588262.048
935161AD1-151 C
Adder
13.97176470588235211.876
934012AD1-025 E
Adder
9.3823529411764717.975
3144216WINCHST
50/50
0.180.18
942341AE2-247 C
Adder
2.00470588235294131.704
316349AD2-085 C
Adder
4.6258823529411773.932
943462AF1-017 E
Adder
2.962.516
935112AD1-144 E
50/50
1.4291.429
932046AC2-012 E
50/50
21.49421.494
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
958161AF2-110 C
50/50
2.0612.061
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
316017AA1-139 ULT1
50/50
1.7931.793
919153AA1-139 E2
50/50
6.7746.774
938531AE1-072 C
50/50
28.99428.994
913392Y1-086 E
50/50
3.5543.554
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
3156116Z1-036WIND
50/50
1.0021.002
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
939411AE1-173 C
50/50
131.454131.454
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
933981AD1-022 C
Adder
12.2223529411764710.389
924516AB2-100 E1
Adder
3.19529411764705932.716
900672V4-068 E
Adder
0.46705882352941180.397
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
960082AF2-299 E
Adder
1.37411764705882341.168
966621AG1-532 C
Adder
1.54588235294117651.314
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
3137643SOCKMAN
Adder
0.820.697
963042AG1-153 E
Adder
10.1470588235294118.625
918532AA1-067 E
Adder
0.87882352941176480.747
919710AA2-057 E
Adder
4.5505882352941183.868
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924022AB2-043 E O1
Adder
5.1847058823529414.407
924152AB2-059 E OP
Adder
5.8823529411764715
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
924302AB2-077 E O1
Adder
1.3364705882352941.136
962561AG1-105 C
Adder
8.6352941176470587.34
316236AE1-162 C
50/50
0.4850.485
3150981CHESPKA
50/50
0.7150.715
316375AC2-012 C
50/50
2.2162.216
926662AC1-147 E
50/50
2.1732.173
3150991CHESPKB
50/50
1.1851.185
916192Z1-068 E
50/50
3.1213.121
316185AD1-033 C
50/50
2.0652.065
934065AD1-033 E
50/50
8.4268.426
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
957492AF2-043 E
50/50
2.2562.256
937226AE2-253 E
50/50
9.7279.727
313526AB2-022 C
50/50
0.6090.609
316320Y1-086 C
50/50
0.3560.356
316321Z2-027 C
50/50
0.5830.583
923852AB2-025 E
Adder
1.22235294117647041.039
940541AE2-040 C
Adder
3.02117647058823562.568
940482AE2-033 E
Adder
11.5564705882352949.823
940481AE2-033 C
Adder
17.1423529411764714.571
940491AE2-034 C
50/50
1.6871.687
939412AE1-173 E
50/50
87.63687.636
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
316141AB2-099 E
Adder
0.32941176470588240.28
961941AG1-037 C
Adder
0.65882352941176480.56
961942AG1-037 E
Adder
0.43882352941176470.373
316088AB2-174 E
Adder
7.3223529411764716.224
923263AB1-132 E OP
Adder
7.045.984
923994AB2-040_E
Adder
6.96705882352941155.922
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934321AD1-056 C
Adder
7.0682352941176476.008
934332AD1-057 E
Adder
2.05294117647058851.745
934322AD1-056 E
Adder
3.83411764705882343.259
934331AD1-057 C
Adder
3.94352941176470573.352
927022AC1-189 E
Adder
4.9929411764705884.244
957481AF2-042 C
Adder
58.3200000000000149.572
957482AF2-042 E
Adder
38.8833.048
961672AG1-007 E
Adder
0.61647058823529410.524
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
925595AC1-034 E
Adder
5.5800000000000014.743
925612AC1-036 E
Adder
0.81882352941176460.696
924322AB2-079 E O1
Adder
1.3364705882352941.136
924312AB2-078 E O1
Adder
1.3364705882352941.136
936262AD2-033 E
Adder
8.0352941176470596.83
935172AD1-152 E
Adder
5.5800000000000014.743
926274AC1-105 E
Adder
2.56470588235294142.18
943902AF1-058 E
Adder
1.21882352941176491.036
935162AD1-151 E
Adder
9.3141176470588247.917
927226AC1-216 E
Adder
7.2470588235294126.16
924814AB2-134 E
Adder
11.87058823529411810.09
962962AG1-145 E
Adder
1.40705882352941171.196
939191AE1-149 C
Adder
9.8705882352941188.39
3143316POE
Adder
1.15647058823529410.983
957832AF2-077 E
Adder
1.4235294117647061.21
3152331SURRY 2
50/50
52.46452.464
943461AF1-017 C
Adder
1.81411764705882361.542
942342AE2-247 E
Adder
2.76823529411764732.353
936666AD2-085 E
Adder
7.5470588235294126.415
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
316036AC1-147 C
50/50
0.6050.605
941591AE2-156 C
50/50
29.41729.417
316316AC1-027 C
50/50
0.5240.524
944601AF1-125 C
50/50
75.19275.192
944591AF1-124 C
50/50
76.6476.64
316018AA1-139 ULT2
50/50
1.7931.793
919152AA1-139 E1
50/50
6.7746.774
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
901082W1-029 E
50/50
50.20950.209
3156056W1-029WIND
50/50
1.2241.224
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
920692AA2-178 E
50/50
6.0146.014
920042AA2-088 E OP
Adder
14.01647058823529311.914
934511AD1-075 C
Adder
11.92941176470588310.14
934521AD1-076 C
Adder
17.32941176470588514.73
960081AF2-299 C
Adder
2.061.751
966622AG1-532 E
Adder
1.03058823529411760.876
3145723EMPORIA
Adder
0.47882352941176470.407
926072AC1-086 E
Adder
11.0094117647058839.358
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
944011AF1-069 C
Adder
16.07529411764705813.664
926206AC1-098 E
Adder
4.3541176470588243.701
963041AG1-153 C
Adder
6.7647058823529415.75
925785AC1-054 E
Adder
3.7423529411764713.181
922923AB1-081 E OP
Adder
4.1529411764705883.53
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
936261AD2-033 C
Adder
12.05176470588235410.244
962562AG1-105 E
Adder
5.75647058823529444.893
964791AG1-342 C
Adder
3.42470588235294132.911
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.38 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3218.92
MW Contribution:97.2
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.16 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3432.06
MW Contribution:98.39
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935162AD1-151 E
Adder
9.3141176470588247.917
927226AC1-216 E
Adder
7.2470588235294126.16
924814AB2-134 E
Adder
11.87058823529411810.09
962962AG1-145 E
Adder
1.40705882352941171.196
939191AE1-149 C
Adder
9.8705882352941188.39
3143316POE
Adder
1.15647058823529410.983
957832AF2-077 E
Adder
1.4235294117647061.21
3152331SURRY 2
50/50
52.46452.464
943461AF1-017 C
Adder
1.81411764705882361.542
942342AE2-247 E
Adder
2.76823529411764732.353
936666AD2-085 E
Adder
7.5470588235294126.415
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
316036AC1-147 C
50/50
0.6050.605
941591AE2-156 C
50/50
29.41729.417
316316AC1-027 C
50/50
0.5240.524
944601AF1-125 C
50/50
75.19275.192
944591AF1-124 C
50/50
76.6476.64
316018AA1-139 ULT2
50/50
1.7931.793
919152AA1-139 E1
50/50
6.7746.774
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
901082W1-029 E
50/50
50.20950.209
3156056W1-029WIND
50/50
1.2241.224
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
920692AA2-178 E
50/50
6.0146.014
920042AA2-088 E OP
Adder
14.01647058823529311.914
934511AD1-075 C
Adder
11.92941176470588310.14
934521AD1-076 C
Adder
17.32941176470588514.73
960081AF2-299 C
Adder
2.061.751
966622AG1-532 E
Adder
1.03058823529411760.876
3145723EMPORIA
Adder
0.47882352941176470.407
926072AC1-086 E
Adder
11.0094117647058839.358
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
944011AF1-069 C
Adder
16.07529411764705813.664
926206AC1-098 E
Adder
4.3541176470588243.701
963041AG1-153 C
Adder
6.7647058823529415.75
925785AC1-054 E
Adder
3.7423529411764713.181
922923AB1-081 E OP
Adder
4.1529411764705883.53
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
936261AD2-033 C
Adder
12.05176470588235410.244
962562AG1-105 E
Adder
5.75647058823529444.893
964791AG1-342 C
Adder
3.42470588235294132.911
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
934576AD1-082 E
Adder
4.8152941176470594.093
316084AB2-161 E
Adder
6.0435294117647055.137
3145256KINGFORK
50/50
1.5391.539
316072AD1-144 C
50/50
0.4270.427
3151101ELIZAR3
50/50
5.3455.345
3151081ELIZAR1
50/50
5.2785.278
3151091ELIZAR2
50/50
5.1875.187
925522AC1-027 E
50/50
2.0192.019
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
926755AC1-161 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
933291AC2-141 C
50/50
57.45157.451
944602AF1-125 E
50/50
172.13172.13
941102AE2-104 E
50/50
8.0328.032
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
316305AF2-043 C
50/50
0.5530.553
957871AF2-081 C
50/50
16.56416.564
957872AF2-081 E
50/50
7.0997.099
940492AE2-034 E
50/50
4.514.51
3145946PLYMOUTH TP
Adder
0.460.391
934522AD1-076 E
Adder
8.832941176470597.508
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
943172AE2-346 E
Adder
0.79058823529411770.672
946282AF1-292 E
Adder
1.13647058823529410.966
918492AA1-063AE OP
Adder
5.04.25
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
944012AF1-069 E
Adder
6.24470588235294165.308
932632AC2-084 E
Adder
3.8494117647058823.272
926214AC1-099 E
Adder
1.43882352941176481.223
316274AC1-208 C
Adder
10.5388235294117658.958
927146AC1-208 E
Adder
4.6800000000000013.978
917512Z2-088 E OP1
Adder
5.7423529411764714.881
917342Z2-044 E
Adder
0.6764705882352940.575
934622AD1-088 E
Adder
4.7082352941176474.002
964242AG1-285 E
Adder
8.5717647058823537.286
937482AD2-202 E
Adder
1.11058823529411770.944
934612AD1-087 E
Adder
3.79294117647058873.224
3151311EDGECMA
Adder
17.2952941176470614.701
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
927255AC1-221 E
Adder
2.40941176470588262.048
935161AD1-151 C
Adder
13.97176470588235211.876
934012AD1-025 E
Adder
9.3823529411764717.975
3144216WINCHST
50/50
0.180.18
942341AE2-247 C
Adder
2.00470588235294131.704
316349AD2-085 C
Adder
4.6258823529411773.932
943462AF1-017 E
Adder
2.962.516
935112AD1-144 E
50/50
1.4291.429
932046AC2-012 E
50/50
21.49421.494
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
958161AF2-110 C
50/50
2.0612.061
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
316017AA1-139 ULT1
50/50
1.7931.793
919153AA1-139 E2
50/50
6.7746.774
938531AE1-072 C
50/50
28.99428.994
913392Y1-086 E
50/50
3.5543.554
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
3156116Z1-036WIND
50/50
1.0021.002
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
939411AE1-173 C
50/50
131.454131.454
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
933981AD1-022 C
Adder
12.2223529411764710.389
924516AB2-100 E1
Adder
3.19529411764705932.716
900672V4-068 E
Adder
0.46705882352941180.397
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
960082AF2-299 E
Adder
1.37411764705882341.168
966621AG1-532 C
Adder
1.54588235294117651.314
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
3137643SOCKMAN
Adder
0.820.697
963042AG1-153 E
Adder
10.1470588235294118.625
918532AA1-067 E
Adder
0.87882352941176480.747
919710AA2-057 E
Adder
4.5505882352941183.868
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924022AB2-043 E O1
Adder
5.1847058823529414.407
924152AB2-059 E OP
Adder
5.8823529411764715
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
924302AB2-077 E O1
Adder
1.3364705882352941.136
962561AG1-105 C
Adder
8.6352941176470587.34
961611AG1-000B C
Adder
18.24117647058823615.505
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
316236AE1-162 C
50/50
0.4850.485
3150981CHESPKA
50/50
0.7150.715
316375AC2-012 C
50/50
2.2162.216
926662AC1-147 E
50/50
2.1732.173
3150991CHESPKB
50/50
1.1851.185
916192Z1-068 E
50/50
3.1213.121
316185AD1-033 C
50/50
2.0652.065
934065AD1-033 E
50/50
8.4268.426
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
957492AF2-043 E
50/50
2.2562.256
937226AE2-253 E
50/50
9.7279.727
313526AB2-022 C
50/50
0.6090.609
316320Y1-086 C
50/50
0.3560.356
316321Z2-027 C
50/50
0.5830.583
923852AB2-025 E
Adder
1.22235294117647041.039
940541AE2-040 C
Adder
3.02117647058823562.568
940482AE2-033 E
Adder
11.5564705882352949.823
940481AE2-033 C
Adder
17.1423529411764714.571
940491AE2-034 C
50/50
1.6871.687
939412AE1-173 E
50/50
87.63687.636
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
316141AB2-099 E
Adder
0.32941176470588240.28
961941AG1-037 C
Adder
0.65882352941176480.56
961942AG1-037 E
Adder
0.43882352941176470.373
316088AB2-174 E
Adder
7.3223529411764716.224
923263AB1-132 E OP
Adder
7.045.984
923994AB2-040_E
Adder
6.96705882352941155.922
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934321AD1-056 C
Adder
7.0682352941176476.008
934332AD1-057 E
Adder
2.05294117647058851.745
934322AD1-056 E
Adder
3.83411764705882343.259
934331AD1-057 C
Adder
3.94352941176470573.352
927022AC1-189 E
Adder
4.9929411764705884.244
957481AF2-042 C
Adder
58.3200000000000149.572
957482AF2-042 E
Adder
38.8833.048
961672AG1-007 E
Adder
0.61647058823529410.524
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
925595AC1-034 E
Adder
5.5800000000000014.743
925612AC1-036 E
Adder
0.81882352941176460.696
924322AB2-079 E O1
Adder
1.3364705882352941.136
924312AB2-078 E O1
Adder
1.3364705882352941.136
936262AD2-033 E
Adder
8.0352941176470596.83
935172AD1-152 E
Adder
5.5800000000000014.743
926274AC1-105 E
Adder
2.56470588235294142.18
943902AF1-058 E
Adder
1.21882352941176491.036
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401

Details for AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.63 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:730.45
MW Contribution:24.31
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.61 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:750.7
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151151S HAMPT1
80/20
0.9570.957
316087AB2-174 C
80/20
2.4642.464
932631AC2-084 C
80/20
1.171.17
316274AC1-208 C
80/20
11.22611.226
316129AC1-054 C
80/20
1.341.34
3151531CLOVER1
80/20
5.8195.819
313527AB2-043 C
80/20
0.3630.363
3151311EDGECMA
80/20
16.55516.555
316049AB1-081 C OP
80/20
1.4941.494
316131AB2-060 C
80/20
1.0341.034
3151611KERR 4
80/20
0.8620.862
3151601KERR 3
80/20
0.8620.862
3151591KERR 2
80/20
0.8620.862
3151581KERR 1
80/20
0.3080.308
3138533PONTONDP
80/20
0.3360.336
316118AC1-105 C
80/20
0.4840.484
3152661PLYWOOD A
80/20
0.6390.639
940481AE2-033 C
80/20
63.40763.407
3156083AA2-088SOLA
80/20
0.9350.935
934501AD1-074 C
80/20
19.36119.361
3156021HOLLOMANSOL
80/20
1.5861.586
961941AG1-037 C
80/20
0.4820.482
943171AE2-346 C
80/20
0.2140.214
3156073AA1-063SOLA
80/20
1.8141.814
316181AB2-040 GEN
80/20
2.5112.511
313506AB1-173 C OP
80/20
2.2292.229
316174AB2-169_C
80/20
0.7190.719
3156063AA2-053SOLA
80/20
2.1582.158
3151371ROSEMS1
80/20
2.4382.438
3151361ROSEMG1
80/20
3.9363.936
3151381ROSEMG2
80/20
1.8431.843
3151281ROARAP4
80/20
2.0092.009
316005AA1-067 C
80/20
0.2210.221
934321AD1-056 C
80/20
9.2019.201
934331AD1-057 C
80/20
5.1335.133
3156011CONETOE2SOL
80/20
1.1751.175
957481AF2-042 C
80/20
24.31224.312
961671AG1-007 C
80/20
0.9120.912
934621AD1-088 C
80/20
4.4044.404
316359AB2-059 C OP
80/20
1.7611.761
316238AB2-078 C O1
80/20
0.2290.229
316237AB2-079 C O1
80/20
0.2290.229
946301AF1-294 C
80/20
1.8661.866
958211AF2-115 C
80/20
1.1351.135
934511AD1-075 C
80/20
4.844.84
934521AD1-076 C
80/20
7.0327.032
316365AB2-100 C1
80/20
2.7732.773
316318V4-068 C
80/20
0.0750.075
960081AF2-299 C
80/20
4.3984.398
3151391GASTONA
80/20
6.1756.175
316011AB1-132 C OP
80/20
4.7154.715
316210AC1-098 C
80/20
1.0991.099
316327AA2-057 C
80/20
1.4891.489
316263AC1-034 C
80/20
6.9816.981
3151631KERR 6
80/20
0.8620.862
959311AF2-222 C
80/20
8.6368.636
316239AB2-077 C O1
80/20
0.2290.229
936261AD2-033 C
80/20
8.0298.029
3144293JTRSVLE
80/20
0.2090.209
961791AG1-021 C
80/20
0.9080.908
964791AG1-342 C
80/20
2.0352.035
933981AD1-022 C
80/20
5.6875.687
316023AB2-100 C2
80/20
2.7732.773
3152921DOMTR78
80/20
0.8540.854
316140AB2-099 C
80/20
0.0920.092
966621AG1-532 C
80/20
3.2993.299
946281AF1-292 C
80/20
3.6413.641
926071AC1-086 C
80/20
42.49342.493
3151411GASTONB
80/20
6.1756.175
316317KELFORD C
80/20
0.370.37
3137643SOCKMAN
80/20
1.2371.237
3151261ROARAP2
80/20
2.1232.123
3147043LAWRENC
80/20
0.5790.579
316212AC1-099 C
80/20
0.3680.368
927021AC1-189 C
80/20
7.5497.549
316319Z2-044 C
80/20
0.2310.231
964241AG1-285 C
80/20
7.2257.225
316034AC1-036 C
80/20
0.1240.124
3151641KERR 7
80/20
0.8620.862
3151621KERR 5
80/20
0.8620.862
962561AG1-105 C
80/20
5.2875.287
SIGELTFEXP_SIGE->PJM
CLTF
0.0840.084
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1882.188
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.15434.154
CPLELTFEXP_CPLE->PJM
CLTF
4.5894.589
TVALTFEXP_TVA->PJM
CLTF
2.0182.018
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.20711.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.5767.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.3611.361
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
NYPJM->LTFIMP_NY
CLTF
0.3660.366
LGEELTFEXP_LGEE->PJM
CLTF
0.4310.431
WECLTFEXP_WEC->PJM
CLTF
0.2290.229
CONTINGENCY 'DVP_P4-2: 511T556_SRT-S-1'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 556_SRT-S-3'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A'
 OPEN BRANCH FROM BUS 314218 TO BUS 314196 CKT 1   /*6ELMONT      230.0 - 6LADYSMITH   230.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1   /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T567_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1   /*6CHCKAHM     230.0 - 8CHCKAHM     500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
314677 to 314747 ckt 1
314282 to 314285 ckt 1
314285 to 314316 ckt 1
314287 to 314276 ckt 1
314692 to 314677 ckt 1
314331 to 314263 ckt 1
314435 to 314282 ckt 1
314902 to 314282 ckt 2
314902 to 314914 ckt 1
314914 to 314918 ckt 1
314924 to 314903 ckt 1
940480 to 314435 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC100.29 %984.18B987.0426.39
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC113.32 %3940.0C4464.92131.71
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.39 %3220.44B3329.5478.72
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC111.58 %4070.2B4541.4777.77
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC111.48 %5011.0C5586.0677.78
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC100.74 %4070.2B4100.4864.72
GD1DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC100.26 %3220.44B3228.8940.4
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
SingleAC102.3 %1058.16B1082.5228.07
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC119.4 %3220.44B3845.2880.37
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC117.79 %3940.0C4640.88134.88
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC111.63 %3220.44B3595.0947.06
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
SingleAC110.86 %3220.44B3570.0549.31
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC110.14 %3940.0C4339.5381.72
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC116.71 %3220.44B3758.5652.45
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC113.93 %3220.44B3669.1354.65
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC111.88 %3940.0C4408.0890.79
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC106.7 %4070.2B4342.98148.17
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC102.59 %4070.2B4175.62148.17
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC120.93 %3220.44B3894.3351.0
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC119.78 %3220.44B3857.5753.64
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC117.54 %3940.0C4631.2488.88
GD1DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC104.04 %4070.2B4234.7129.89

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.29 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:987.04
MW Contribution:26.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316315AB2-025 C
80/20
0.4250.425
3152921DOMTR78
80/20
0.5570.557
316023AB2-100 C2
80/20
0.7990.799
316140AB2-099 C
80/20
0.0450.045
940641AE2-051 C
80/20
9.0359.035
316317KELFORD C
80/20
0.1760.176
932631AC2-084 C
80/20
0.5330.533
3152431Z1-086 GT3
80/20
5.7485.748
316274AC1-208 C
80/20
4.9624.962
316129AC1-054 C
80/20
0.6480.648
3156011CONETOE2SOL
80/20
0.6290.629
316319Z2-044 C
80/20
0.1130.113
3151311EDGECMA
80/20
8.3398.339
934611AD1-087 C
80/20
0.5960.596
3151611KERR 4
80/20
0.5540.554
3151631KERR 6
80/20
0.5540.554
3151641KERR 7
80/20
0.5540.554
3151621KERR 5
80/20
0.5540.554
313527AB2-043 C
80/20
0.2380.238
316237AB2-079 C O1
80/20
0.1510.151
316131AB2-060 C
80/20
0.680.68
3152661PLYWOOD A
80/20
0.5410.541
3138533PONTONDP
Adder
0.237647058823529430.202
316222AC1-221 C
80/20
0.6320.632
939411AE1-173 C
80/20
41.75841.758
933981AD1-022 C
80/20
3.5783.578
316318V4-068 C
80/20
0.0370.037
3156021HOLLOMANSOL
80/20
0.830.83
316174AB2-169_C
80/20
0.4490.449
966621AG1-532 C
80/20
1.041.04
946281AF1-292 C
80/20
1.1471.147
316011AB1-132 C OP
80/20
1.5811.581
926071AC1-086 C
80/20
14.30114.301
313506AB1-173 C OP
80/20
0.7570.757
3156063AA2-053SOLA
80/20
0.860.86
3151371ROSEMS1
80/20
0.8390.839
3137643SOCKMAN
80/20
0.4490.449
3151281ROARAP4
80/20
0.7750.775
316210AC1-098 C
80/20
0.50.5
316005AA1-067 C
80/20
0.1280.128
927021AC1-189 C
80/20
4.1534.153
316049AB1-081 C OP
80/20
0.7570.757
3151601KERR 3
80/20
0.5540.554
3151581KERR 1
80/20
0.1980.198
935171AD1-152 C
80/20
0.620.62
316238AB2-078 C O1
80/20
0.1510.151
964241AG1-285 C
80/20
5.5515.551
316034AC1-036 C
80/20
0.0950.095
962561AG1-105 C
80/20
4.0224.022
316118AC1-105 C
80/20
0.4080.408
944641AF1-129 C
Adder
-92.12117647058824-78.303
316240AF1-291 C
Adder
-1.6611764705882353-1.412
938771AE1-103 C
Adder
0.96705882352941170.822
3151151S HAMPT1
80/20
0.570.57
934521AD1-076 C
80/20
4.8074.807
934511AD1-075 C
80/20
3.3093.309
3156073AA1-063SOLA
80/20
0.7530.753
960081AF2-299 C
80/20
1.3861.386
316087AB2-174 C
80/20
0.8150.815
3151381ROSEMG2
80/20
0.6340.634
3151361ROSEMG1
80/20
1.3551.355
3151261ROARAP2
80/20
0.8190.819
944011AF1-069 C
80/20
7.217.21
316212AC1-099 C
80/20
0.1680.168
3152421Z1-086 GT2
80/20
5.7485.748
3152441Z1-086 ST
80/20
10.00810.008
3152411Z1-086 GT1
80/20
5.755.75
963041AG1-153 C
80/20
3.0443.044
3151051BRUNSWICKS1
80/20
9.3029.302
3151041BRUNSWICKG3
80/20
4.4784.478
316327AA2-057 C
80/20
0.7010.701
316263AC1-034 C
80/20
3.5493.549
937481AD2-202 C
80/20
0.1730.173
3151591KERR 2
80/20
0.5540.554
316239AB2-077 C O1
80/20
0.1510.151
936261AD2-033 C
80/20
5.4245.424
959311AF2-222 C
80/20
6.6486.648
964791AG1-342 C
80/20
1.5971.597
961791AG1-021 C
Adder
0.640.544
316248AF1-058 C
80/20
0.140.14
942001AE2-212 C
Adder
-3.9329411764705884-3.343
315614AA2-178 C
80/20
0.5670.567
940491AE2-034 C
80/20
0.4170.417
940541AE2-040 C
80/20
2.9992.999
940481AE2-033 C
80/20
16.46516.465
934501AD1-074 C
80/20
13.23613.236
3156083AA2-088SOLA
80/20
0.4670.467
316365AB2-100 C1
80/20
0.7990.799
943171AE2-346 C
80/20
0.1050.105
961941AG1-037 C
80/20
0.2370.237
3151391GASTONA
80/20
2.0712.071
3151411GASTONB
80/20
2.0712.071
316181AB2-040 GEN
80/20
0.8530.853
941031AE2-094 C
80/20
22.06822.068
3147043LAWRENC
80/20
0.2030.203
3151021BRUNSWICKG1
80/20
4.4784.478
3151031BRUNSWICKG2
80/20
4.4784.478
934331AD1-057 C
80/20
2.0892.089
934321AD1-056 C
80/20
3.7443.744
961671AG1-007 C
80/20
0.4820.482
957481AF2-042 C
80/20
26.38726.387
316359AB2-059 C OP
80/20
0.8920.892
934621AD1-088 C
80/20
4.424.42
3151531CLOVER1
80/20
6.056.05
3151541CLOVER2
80/20
5.9935.993
958211AF2-115 C
Adder
0.80.68
946301AF1-294 C
Adder
1.3164705882352941.119
316003AC1-222 C
80/20
0.4260.426
316283AC2-100 C
80/20
0.510.51
SIGELTFEXP_SIGE->PJM
CLTF
0.1330.133
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.6422.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.16446.164
CPLELTFEXP_CPLE->PJM
CLTF
5.5395.539
TVALTFEXP_TVA->PJM
CLTF
3.0473.047
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.95317.953
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.57311.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1342.134
LAGNLTFEXP_LAGN->PJM
CLTF
3.8673.867
NYPJM->LTFIMP_NY
CLTF
0.5840.584
LGEELTFEXP_LGEE->PJM
CLTF
0.6950.695
WECLTFEXP_WEC->PJM
CLTF
0.3670.367

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.32 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4464.92
MW Contribution:131.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935112AD1-144 E
Adder
1.21411764705882351.032
943462AF1-017 E
Adder
2.7964705882352942.377
316349AD2-085 C
Adder
4.3705882352941173.715
942341AE2-247 C
Adder
1.89411764705882371.61
932046AC2-012 E
50/50
17.5517.55
3151091ELIZAR2
50/50
4.2124.212
958161AF2-110 C
Adder
1.8117647058823531.54
958162AF2-110 E
Adder
2.8811764705882352.449
316388AE2-253 GEN
50/50
2.652.65
944582AF1-123 E
50/50
142.834142.834
944592AF1-124 E
50/50
143.351143.351
919153AA1-139 E2
50/50
5.535.53
938531AE1-072 C
50/50
23.77123.771
923832AB2-022 E
Adder
1.67529411764705881.424
913392Y1-086 E
Adder
2.9682352941176472.523
938772AE1-103 E
Adder
5.3788235294117654.572
916042Z1-036 E
Adder
38.52941176470588432.75
3145393UNCAMP
Adder
8.0941176470588236.88
934502AD1-074 E
Adder
23.0929411764705919.629
934512AD1-075 E
Adder
5.7729411764705894.907
939411AE1-173 C
50/50
144.742144.742
933981AD1-022 C
Adder
11.78823529411764610.02
900672V4-068 E
Adder
0.47764705882352950.406
918512AA1-065 E OP
Adder
7.42823529411764756.314
924516AB2-100 E1
Adder
3.9282352941176473.339
940642AE2-051 E
50/50
19.2519.25
966621AG1-532 C
Adder
1.87411764705882341.593
960082AF2-299 E
Adder
1.66588235294117641.416
946281AF1-292 C
Adder
2.0682352941176471.758
926071AC1-086 C
Adder
28.2376470588235324.002
3137643SOCKMAN
Adder
0.95176470588235310.809
963042AG1-153 E
50/50
13.7613.76
918532AA1-067 E
Adder
0.95764705882352940.814
927021AC1-189 C
Adder
11.2564705882352949.568
919710AA2-057 E
Adder
5.2964705882352944.502
924152AB2-059 E OP
Adder
7.0388235294117655.983
924022AB2-043 E O1
Adder
6.3552941176470595.402
924302AB2-077 E O1
Adder
1.6447058823529411.398
964241AG1-285 C
Adder
14.8776470588235312.646
939191AE1-149 C
Adder
12.10588235294117610.29
936666AD2-085 E
Adder
7.1317647058823546.062
942342AE2-247 E
Adder
2.61647058823529432.224
943461AF1-017 C
Adder
1.71411764705882371.457
3143316POE
Adder
1.6082352941176471.367
932596AC2-079 E
Adder
11.94588235294117610.154
316311AC2-079 C
Adder
7.3223529411764716.224
941591AE2-156 C
50/50
24.00724.007
3151101ELIZAR3
50/50
4.3424.342
944591AF1-124 C
50/50
62.59862.598
944601AF1-125 C
50/50
61.41561.415
919152AA1-139 E1
50/50
5.535.53
938532AE1-072 E
50/50
12.39212.392
3146326AYDLETT TAP
50/50
1.8341.834
917122Z2-027 E
Adder
1.81294117647058831.541
901082W1-029 E
Adder
42.9564705882352936.513
938771AE1-103 C
Adder
3.8941176470588243.31
3145413WATKINS
Adder
0.92117647058823540.783
920692AA2-178 E
Adder
5.5388235294117654.708
934521AD1-076 C
Adder
16.4752941176470614.004
934511AD1-075 C
Adder
11.3411764705882369.64
920042AA2-088 E OP
Adder
14.1647058823529412.04
960081AF2-299 C
Adder
2.4988235294117652.124
966622AG1-532 E
Adder
1.24941176470588241.062
926072AC1-086 E
Adder
12.85176470588235310.924
3145723EMPORIA
Adder
0.57647058823529410.49
923573AB1-173 E OP
Adder
4.3858823529411773.728
919692AA2-053 E OP
Adder
5.65176470588235354.804
944011AF1-069 C
50/50
21.78821.788
926206AC1-098 E
Adder
4.8835294117647064.151
3152421Z1-086 GT2
50/50
17.33717.337
3152441Z1-086 ST
50/50
30.18730.187
3152411Z1-086 GT1
50/50
17.34217.342
963041AG1-153 C
50/50
9.1739.173
3151051BRUNSWICKS1
50/50
28.03428.034
3151041BRUNSWICKG3
50/50
13.49413.494
925785AC1-054 E
Adder
4.5188235294117653.841
316263AC1-034 C
Adder
8.8505882352941177.523
922923AB1-081 E OP
Adder
4.9682352941176474.223
937481AD2-202 C
50/50
0.5150.515
962562AG1-105 E
Adder
7.41411764705882356.302
964791AG1-342 C
Adder
4.4517647058823523.784
927264AC1-222 E
Adder
5.0905882352941184.327
939192AE1-149 E
Adder
8.0705882352941176.86
939312AE1-162 E
Adder
1.72117647058823551.463
316375AC2-012 C
50/50
1.8031.803
926662AC1-147 E
Adder
1.77411764705882361.508
3151081ELIZAR1
50/50
4.2884.288
916192Z1-068 E
50/50
2.5342.534
916191Z1-068 C
50/50
0.0590.059
957492AF2-043 E
Adder
1.9105882352941181.624
941101AE2-104 C
Adder
4.4388235294117653.773
934065AD1-033 E
50/50
6.7926.792
316185AD1-033 C
50/50
1.6591.659
937226AE2-253 E
50/50
7.9097.909
944581AF1-123 C
50/50
62.37662.376
316294AC1-161 C
50/50
6.8696.869
940541AE2-040 C
50/50
3.9673.967
923852AB2-025 E
50/50
1.6041.604
940481AE2-033 C
50/50
22.31122.311
940482AE2-033 E
50/50
15.04115.041
934501AD1-074 C
Adder
45.3647058823529438.56
939412AE1-173 E
50/50
96.49596.495
924517AB2-100 E2
Adder
3.9282352941176473.339
961942AG1-037 E
Adder
0.451764705882352960.384
316141AB2-099 E
Adder
0.33882352941176470.288
961941AG1-037 C
Adder
0.6764705882352940.575
923263AB1-132 E OP
Adder
8.217647058823536.985
316088AB2-174 E
Adder
8.7141176470588247.407
923994AB2-040_E
Adder
8.2247058823529416.991
941031AE2-094 C
50/50
66.68466.684
941032AE2-094 E
50/50
29.86629.866
3151021BRUNSWICKG1
50/50
13.49413.494
3151031BRUNSWICKG2
50/50
13.49413.494
934331AD1-057 C
Adder
4.6741176470588233.973
934322AD1-056 E
Adder
4.5447058823529413.863
934332AD1-057 E
Adder
2.43411764705882352.069
934321AD1-056 C
Adder
8.3788235294117657.122
927022AC1-189 E
Adder
5.6070588235294124.766
961672AG1-007 E
Adder
0.71058823529411760.604
961671AG1-007 C
Adder
1.25411764705882361.066
957482AF2-042 E
50/50
52.68252.682
957481AF2-042 C
50/50
79.02379.023
925595AC1-034 E
Adder
6.6764705882352945.675
934621AD1-088 C
50/50
13.2613.26
3151531CLOVER1
50/50
18.02218.022
3151541CLOVER2
50/50
17.85317.853
935172AD1-152 E
Adder
7.5717647058823536.436
924322AB2-079 E O1
Adder
1.6447058823529411.398
924312AB2-078 E O1
Adder
1.6447058823529411.398
926274AC1-105 E
Adder
3.4082352941176472.897
943902AF1-058 E
Adder
1.65529411764705881.407
3150921YORKTN3
Adder
124.22470588235294105.591
934576AD1-082 E
Adder
5.2247058823529414.441
316084AB2-161 E
Adder
6.5576470588235295.574
3145256KINGFORK
Adder
1.30823529411764721.112
925522AC1-027 E
50/50
1.641.64
316316AC1-027 C
50/50
0.4240.424
943612AF1-032 E
Adder
1.24117647058823531.055
941102AE2-104 E
Adder
7.0576470588235295.999
3145506HICKORY
50/50
2.9532.953
944602AF1-125 E
50/50
140.592140.592
957872AF2-081 E
50/50
5.7955.795
957871AF2-081 C
50/50
13.52313.523
316017AA1-139 ULT1
50/50
1.4591.459
316018AA1-139 ULT2
50/50
1.4591.459
933292AC2-141 E
50/50
18.00718.007
933291AC2-141 C
50/50
42.18342.183
926755AC1-161 E
50/50
18.00718.007
940492AE2-034 E
Adder
4.1541176470588243.531
316315AB2-025 C
50/50
0.5620.562
3145946PLYMOUTH TP
Adder
0.435294117647058830.37
934522AD1-076 E
Adder
8.397647058823537.138
933982AD1-022 E
Adder
6.417647058823535.455
943172AE2-346 E
Adder
0.81176470588235290.69
940641AE2-051 C
50/50
28.87528.875
918492AA1-063AE OP
Adder
5.4552941176470594.637
925122AB2-169 E
Adder
7.7223529411764716.564
917332KELFORD E
Adder
2.2035294117647061.873
946282AF1-292 E
Adder
1.37882352941176461.172
944012AF1-069 E
50/50
8.4648.464
932632AC2-084 E
Adder
4.3164705882352943.669
926214AC1-099 E
Adder
1.61294117647058831.371
3152431Z1-086 GT3
50/50
17.33717.337
316274AC1-208 C
Adder
12.05058823529411810.243
927146AC1-208 E
Adder
5.3517647058823544.549
917512Z2-088 E OP1
Adder
6.54705882352941255.565
917342Z2-044 E
Adder
0.79764705882352950.678
3151311EDGECMA
Adder
20.6976470588235317.593
934622AD1-088 E
50/50
6.3856.385
934611AD1-087 C
50/50
1.7741.774
937482AD2-202 E
50/50
1.5031.503
934612AD1-087 E
50/50
5.1365.136
924162AB2-060 E OP
Adder
5.2141176470588244.432
964242AG1-285 E
Adder
9.9188235294117648.431
964792AG1-342 E
Adder
2.9682352941176472.523
927255AC1-221 E
Adder
4.84941176470588254.122
932763AC2-100 E
Adder
3.2952941176470592.801
962561AG1-105 C
Adder
11.1211764705882359.453
G-007PJM->LTFIMP_G-007
CMTX_NF
5.665.66
SIGELTFEXP_SIGE->PJM
CLTF
0.4160.416
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6257.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
136.078136.078
CPLELTFEXP_CPLE->PJM
CLTF
15.98515.985
TVALTFEXP_TVA->PJM
CLTF
9.3529.352
O66PJM->LTFIMP_O-066
CMTX_NF
36.00236.002
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.25255.252
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.53435.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.5866.586
LAGNLTFEXP_LAGN->PJM
CLTF
11.79711.797
NYPJM->LTFIMP_NY
CLTF
2.5842.584
LGEELTFEXP_LGEE->PJM
CLTF
2.1892.189
WECLTFEXP_WEC->PJM
CLTF
1.1371.137

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.39 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3329.54
MW Contribution:78.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935161AD1-151 C
Adder
15.27058823529411812.98
316349AD2-085 C
80/20
4.3374.337
942341AE2-247 C
80/20
1.881.88
3150991CHESPKB
80/20
0.9580.958
3151091ELIZAR2
80/20
4.1834.183
316246AF1-032 C
80/20
0.3780.378
958161AF2-110 C
80/20
1.7981.798
316388AE2-253 GEN
80/20
2.6322.632
938531AE1-072 C
80/20
23.60823.608
316320Y1-086 C
80/20
0.2940.294
939411AE1-173 C
80/20
144.1144.1
933981AD1-022 C
80/20
11.71411.714
316318V4-068 C
80/20
0.1070.107
3156021HOLLOMANSOL
80/20
2.4482.448
316174AB2-169_C
80/20
1.3931.393
966621AG1-532 C
80/20
1.8631.863
946281AF1-292 C
80/20
2.0562.056
316011AB1-132 C OP
80/20
3.1053.105
926071AC1-086 C
80/20
28.07728.077
313506AB1-173 C OP
80/20
1.4941.494
3156063AA2-053SOLA
80/20
1.9981.998
3151371ROSEMS1
80/20
1.681.68
3137643SOCKMAN
80/20
0.9470.947
939191AE1-149 C
Adder
11.99058823529411710.192
943461AF1-017 C
80/20
1.7011.701
316311AC2-079 C
80/20
7.2667.266
3150981CHESPKA
80/20
0.5780.578
316036AC1-147 C
80/20
0.4890.489
941591AE2-156 C
80/20
23.83823.838
3151101ELIZAR3
80/20
4.3114.311
316305AF2-043 C
80/20
0.4630.463
944591AF1-124 C
80/20
62.17762.177
944601AF1-125 C
80/20
61.00261.002
316321Z2-027 C
80/20
0.4860.486
3156056W1-029WIND
80/20
1.0361.036
938771AE1-103 C
80/20
3.8693.869
3151151S HAMPT1
80/20
1.9741.974
934521AD1-076 C
80/20
16.37216.372
934511AD1-075 C
80/20
11.2711.27
3156073AA1-063SOLA
80/20
1.8611.861
960081AF2-299 C
80/20
2.4842.484
316087AB2-174 C
80/20
1.561.56
3151381ROSEMG2
80/20
1.271.27
3151361ROSEMG1
80/20
2.7122.712
3151261ROARAP2
80/20
1.8341.834
944011AF1-069 C
80/20
21.71321.713
316212AC1-099 C
80/20
0.4180.418
3152421Z1-086 GT2
80/20
17.27717.277
3152441Z1-086 ST
80/20
30.08230.082
3152411Z1-086 GT1
80/20
17.28217.282
963041AG1-153 C
80/20
9.1419.141
3151051BRUNSWICKS1
80/20
27.93527.935
3151041BRUNSWICKG3
80/20
13.44613.446
316263AC1-034 C
Adder
8.8035294117647057.483
937481AD2-202 C
80/20
0.5130.513
936261AD2-033 C
Adder
14.72470588235294112.516
959311AF2-222 C
Adder
18.28823529411764815.545
964791AG1-342 C
Adder
4.4317647058823533.767
961791AG1-021 C
Adder
1.82588235294117651.552
936171AD2-023 C
Adder
5.5152941176470584.688
3150921YORKTN3
Adder
127.84235294117647108.666
3152331SURRY 2
80/20
30.82730.827
316316AC1-027 C
80/20
0.4210.421
957871AF2-081 C
80/20
13.4313.43
316017AA1-139 ULT1
80/20
1.4491.449
316018AA1-139 ULT2
80/20
1.4491.449
933291AC2-141 C
80/20
41.90441.904
313526AB2-022 C
80/20
0.5040.504
316315AB2-025 C
80/20
0.5580.558
3152921DOMTR78
80/20
1.8181.818
316023AB2-100 C2
80/20
1.2911.291
316140AB2-099 C
80/20
0.1280.128
940641AE2-051 C
80/20
28.76428.764
316317KELFORD C
80/20
0.4760.476
932631AC2-084 C
80/20
1.3311.331
3152431Z1-086 GT3
80/20
17.27717.277
316274AC1-208 C
80/20
11.98411.984
316129AC1-054 C
80/20
1.5891.589
3151311EDGECMA
Adder
20.58941176470588317.501
934611AD1-087 C
80/20
1.7671.767
3138533PONTONDP
Adder
0.6764705882352940.575
940431AE2-027 C
Adder
11.395294117647069.686
961611AG1-000B C
Adder
17.0670588235294114.507
942001AE2-212 C
Adder
2.11411764705882371.797
316072AD1-144 C
80/20
0.3590.359
316375AC2-012 C
80/20
1.7911.791
3151081ELIZAR1
80/20
4.2584.258
916191Z1-068 C
80/20
0.0580.058
941101AE2-104 C
80/20
4.4074.407
316185AD1-033 C
80/20
1.6481.648
944581AF1-123 C
80/20
61.95761.957
316294AC1-161 C
80/20
6.8246.824
3156116Z1-036WIND
80/20
0.8770.877
315614AA2-178 C
80/20
2.0912.091
940491AE2-034 C
80/20
1.5381.538
940541AE2-040 C
80/20
3.9443.944
940481AE2-033 C
80/20
22.18122.181
934501AD1-074 C
80/20
45.0845.08
3156083AA2-088SOLA
80/20
1.4051.405
316365AB2-100 C1
80/20
1.2911.291
943171AE2-346 C
80/20
0.2980.298
961941AG1-037 C
80/20
0.6730.673
3151391GASTONA
80/20
4.0664.066
3151411GASTONB
80/20
4.0664.066
316181AB2-040 GEN
80/20
1.6831.683
941031AE2-094 C
80/20
66.45566.455
3147043LAWRENC
80/20
0.3980.398
3151021BRUNSWICKG1
80/20
13.44613.446
3151031BRUNSWICKG2
80/20
13.44613.446
934331AD1-057 C
Adder
4.6482352941176473.951
934321AD1-056 C
Adder
8.332941176470597.083
961671AG1-007 C
Adder
1.2482352941176471.061
957481AF2-042 C
80/20
78.71578.715
934621AD1-088 C
80/20
13.20613.206
3151531CLOVER1
80/20
17.9517.95
3151541CLOVER2
80/20
17.78117.781
958211AF2-115 C
Adder
2.28235294117647051.94
946301AF1-294 C
Adder
3.75411764705882333.191
3151281ROARAP4
80/20
1.7351.735
316210AC1-098 C
80/20
1.251.25
927021AC1-189 C
Adder
11.1952941176470599.516
935171AD1-152 C
80/20
1.8271.827
964241AG1-285 C
Adder
14.80352941176470712.583
962561AG1-105 C
Adder
11.0694117647058839.409
936161AD2-022 C
Adder
9.455294117647068.037
SIGELTFEXP_SIGE->PJM
CLTF
0.4150.415
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.597.59
CBM South 2LTFEXP_CBM-S2->PJM
CBM
135.46135.46
CPLELTFEXP_CPLE->PJM
CLTF
15.91315.913
TVALTFEXP_TVA->PJM
CLTF
9.319.31
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.0655.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.38335.383
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.566.56
LAGNLTFEXP_LAGN->PJM
CLTF
11.74411.744
NYPJM->LTFIMP_NY
CLTF
2.5592.559
LGEELTFEXP_LGEE->PJM
CLTF
2.182.18
WECLTFEXP_WEC->PJM
CLTF
1.1331.133

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.58 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4541.47
MW Contribution:77.77
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966661AG1-536 C
Adder
8.2105882352941186.979
316169AC1-164 GEN
80/20
73.90473.904
316159AE1-175 C
80/20
0.7120.712
3150771HOPHCF1
80/20
4.324.32
3150731STONECA
80/20
12.27512.275
935161AD1-151 C
80/20
28.71928.719
316312AB1-027 C
80/20
0.9570.957
3150701DARBY 4
80/20
4.5974.597
3151161SURRY 1
80/20
43.78843.788
3142366NRTHEST
80/20
0.330.33
316349AD2-085 C
Adder
5.9917647058823535.093
942341AE2-247 C
Adder
2.5964705882352942.207
958161AF2-110 C
Adder
2.38352941176470572.026
938531AE1-072 C
Adder
30.76823529411764526.153
939411AE1-173 C
Adder
145.74235294117648123.881
933981AD1-022 C
Adder
14.54588235294117712.364
966621AG1-532 C
Adder
2.1752941176470591.849
946281AF1-292 C
Adder
2.40117647058823552.041
926071AC1-086 C
Adder
32.9752941176470628.029
3137643SOCKMAN
Adder
1.1117647058823530.945
927021AC1-189 C
Adder
13.13058823529411811.161
964241AG1-285 C
Adder
17.71058823529411815.054
958261AF2-120 C
Adder
9.5447058823529418.113
940551AE2-041 C
Adder
12.16117647058823610.337
316382AG1-145 C
80/20
0.6420.642
3150601CHESTF5
80/20
113.981113.981
3150631CHESTG8
80/20
6.826.82
3150621CHESTS7
80/20
3.1823.182
3143096IRON208
80/20
0.7870.787
3150781HOPHCF2
80/20
4.324.32
3150761HOPPOLC
80/20
2.7172.717
316132AB2-190 C
80/20
7.3677.367
316004AC1-112 C
80/20
0.5960.596
3150691DARBY 3
80/20
4.5924.592
939191AE1-149 C
Adder
18.60588235294117615.815
944641AF1-129 C
Adder
179.8423529411765152.866
316240AF1-291 C
Adder
3.78000000000000023.213
943461AF1-017 C
Adder
2.34941176470588251.997
316311AC2-079 C
Adder
9.984705882352948.487
941591AE2-156 C
Adder
31.64823529411764726.901
944591AF1-124 C
Adder
80.4988235294117868.424
944601AF1-125 C
Adder
78.9788235294117767.132
938771AE1-103 C
Adder
4.9788235294117654.232
934521AD1-076 C
Adder
20.41647058823529517.354
934511AD1-075 C
Adder
14.05411764705882411.946
316233AE1-074 C
Adder
4.08588235294117653.473
3142296MT RD221
80/20
0.2170.217
960081AF2-299 C
Adder
2.92.465
944011AF1-069 C
Adder
19.35647058823529316.453
963041AG1-153 C
Adder
8.3011764705882357.056
316263AC1-034 C
Adder
10.102352941176478.587
936261AD2-033 C
Adder
18.25529411764705815.517
957601AF2-054 C
Adder
3.56235294117647073.028
936591AD2-074 C
Adder
8.7058823529411787.4
961951AG1-038 C
Adder
5.035294117647064.28
943471AF1-018 C
Adder
12.16117647058823610.337
944631AF1-128 C
80/20
71.31971.319
3150921YORKTN3
80/20
215.99215.99
3144216WINCHST
80/20
0.2370.237
3150791HOPHCF3
80/20
4.324.32
934011AD1-025 C
80/20
4.6114.611
316033AB2-134 GEN
80/20
3.7293.729
3151191GRAVEL3
80/20
4.4484.448
3151221GRAVEL6
80/20
4.54.5
3151201GRAVEL4
80/20
4.5054.505
3150651CHESTF6
Adder
32.7447058823529427.833
3152331SURRY 2
80/20
45.81645.816
957871AF2-081 C
Adder
17.51647058823529314.889
933291AC2-141 C
80/20
54.34454.344
940641AE2-051 C
Adder
26.97529411764705622.929
316274AC1-208 C
Adder
14.04588235294117711.939
3151311EDGECMA
Adder
23.6270588235294120.083
316336AC2-165 C
Adder
13.90823529411764711.822
963611AG1-210 C
Adder
0.95764705882352940.814
962861AG1-135 C
Adder
9.3188235294117667.921
943741AF1-042 C
Adder
4.5552941176470593.872
940431AE2-027 C
Adder
22.58000000000000219.193
316075AC2-137 C
80/20
0.6870.687
3150641CHESTS8
80/20
3.5113.511
3150611CHESTG7
80/20
6.9316.931
3150801HOPHCF4
80/20
6.5586.558
316369AC1-216 C
80/20
2.8462.846
3150681DARBY 2
80/20
4.5764.576
3150671DARBY 1
80/20
4.574.57
961611AG1-000B C
80/20
28.34928.349
942001AE2-212 C
Adder
3.73882352941176473.178
3150831SPRUNCA
Adder
15.78000000000000113.413
3150841SPRUNCB
Adder
15.78000000000000113.413
941101AE2-104 C
Adder
5.8423529411764714.966
944581AF1-123 C
Adder
80.2141176470588368.182
316294AC1-161 C
80/20
8.8498.849
940541AE2-040 C
Adder
4.5529411764705883.87
940481AE2-033 C
Adder
25.6411764705882421.795
934501AD1-074 C
Adder
56.2176470588235347.785
961941AG1-037 C
Adder
0.82117647058823530.698
941031AE2-094 C
Adder
59.24117647058823650.355
934331AD1-057 C
Adder
5.3847058823529414.577
934321AD1-056 C
Adder
9.6541176470588248.206
961671AG1-007 C
Adder
1.44941176470588241.232
957481AF2-042 C
Adder
77.7682352941176466.103
927041AC1-191 C
Adder
16.39529411764705813.936
966871AG1-558 C
Adder
4.0835294117647063.471
934621AD1-088 C
Adder
13.69294117647058911.639
964211AG1-282 C
Adder
2.9811764705882352.534
SIGELTFEXP_SIGE->PJM
CLTF
0.620.62
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.4058.405
CBM South 2LTFEXP_CBM-S2->PJM
CBM
156.686156.686
CPLELTFEXP_CPLE->PJM
CLTF
17.60717.607
TVALTFEXP_TVA->PJM
CLTF
12.412.4
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.27284.272
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.64648.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
9.5619.561
LAGNLTFEXP_LAGN->PJM
CLTF
15.45715.457
NYPJM->LTFIMP_NY
CLTF
4.1344.134
LGEELTFEXP_LGEE->PJM
CLTF
3.3563.356
WECLTFEXP_WEC->PJM
CLTF
1.7261.726

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.48 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5586.06
MW Contribution:77.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934146AD1-041 E
Adder
6.0129411764705885.111
940551AE2-041 C
Adder
12.15411764705882410.331
962962AG1-145 E
50/50
2.6282.628
316382AG1-145 C
50/50
0.6420.642
3150601CHESTF5
50/50
113.923113.923
3150631CHESTG8
50/50
6.8166.816
3150621CHESTS7
50/50
3.183.18
925332AB2-190 E
Adder
14.35882352941176512.205
935162AD1-151 E
Adder
19.1376470588235316.267
927226AC1-216 E
Adder
13.74117647058823411.68
924814AB2-134 E
Adder
22.5082352941176519.132
316004AC1-112 C
50/50
0.5960.596
3150691DARBY 3
50/50
4.5894.589
939191AE1-149 C
Adder
18.59882352941176415.809
944641AF1-129 C
Adder
179.7623529411765152.798
316240AF1-291 C
Adder
3.7788235294117653.212
936666AD2-085 E
Adder
9.7729411764705898.307
942342AE2-247 E
Adder
3.58470588235294143.047
943461AF1-017 C
Adder
2.34941176470588251.997
3143316POE
Adder
2.31058823529411761.964
932596AC2-079 E
Adder
16.2847058823529413.842
316311AC2-079 C
Adder
9.9811764705882358.484
941591AE2-156 C
Adder
31.63647058823529426.891
944591AF1-124 C
Adder
80.4682352941176568.398
944601AF1-125 C
Adder
78.9482352941176467.106
919152AA1-139 E1
Adder
7.166.086
938532AE1-072 E
Adder
16.0329411764705913.628
3146326AYDLETT TAP
Adder
2.3717647058823532.016
917122Z2-027 E
Adder
2.3352941176470591.985
901082W1-029 E
Adder
55.2529411764705946.965
938771AE1-103 C
Adder
4.9776470588235294.231
3145413WATKINS
Adder
1.15882352941176480.985
920692AA2-178 E
Adder
6.9352941176470585.895
934521AD1-076 C
Adder
20.41176470588235517.35
934511AD1-075 C
Adder
14.05058823529411811.943
316233AE1-074 C
Adder
4.08588235294117653.473
920042AA2-088 E OP
Adder
17.4414.824
3142296MT RD221
50/50
0.2170.217
960081AF2-299 C
Adder
2.92.465
966622AG1-532 E
Adder
1.45058823529411771.233
926072AC1-086 E
Adder
15.0047058823529412.754
3145723EMPORIA
Adder
0.66941176470588230.569
923573AB1-173 E OP
Adder
5.11176470588235254.345
919692AA2-053 E OP
Adder
6.6552941176470595.657
944011AF1-069 C
Adder
19.35294117647058716.45
963041AG1-153 C
Adder
8.37.055
927042AC1-191 E
Adder
8.1611764705882366.937
957832AF2-077 E
Adder
2.49294117647058842.119
957601AF2-054 C
Adder
3.56117647058823563.027
943741AF1-042 C
Adder
4.5517647058823533.869
943742AF1-042 E
Adder
7.42705882352941156.313
934392AD1-063 E
Adder
1.8235294117647061.55
923842AB2-024 E
Adder
3.07294117647058852.612
940431AE2-027 C
Adder
22.57058823529411719.185
316075AC2-137 C
50/50
0.6870.687
316076AC2-137 E
50/50
2.4242.424
3138116ELKO L286
50/50
2.5282.528
3150641CHESTS8
50/50
3.5093.509
3150611CHESTG7
50/50
6.9276.927
3150681DARBY 2
50/50
4.5734.573
3150671DARBY 1
50/50
4.5674.567
961611AG1-000B C
Adder
28.33647058823529424.086
939192AE1-149 E
Adder
12.39882352941176410.539
939312AE1-162 E
Adder
2.54117647058823562.16
942002AE2-212 E
Adder
2.49058823529411782.117
942001AE2-212 C
Adder
3.73647058823529443.176
3150831SPRUNCA
Adder
15.77411764705882313.408
3150841SPRUNCB
Adder
15.77411764705882313.408
926662AC1-147 E
Adder
2.34000000000000031.989
916192Z1-068 E
Adder
3.3141176470588242.817
957492AF2-043 E
Adder
2.48941176470588272.116
941101AE2-104 C
Adder
5.8411764705882354.965
934065AD1-033 E
Adder
8.8270588235294137.503
937226AE2-253 E
Adder
10.2482352941176478.711
944581AF1-123 C
Adder
80.1835294117647168.156
940541AE2-040 C
Adder
4.5517647058823533.869
923852AB2-025 E
Adder
1.84117647058823521.565
940481AE2-033 C
Adder
25.63411764705882621.789
940482AE2-033 E
Adder
17.28117647058823514.689
934501AD1-074 C
Adder
56.2023529411764747.772
939412AE1-173 E
Adder
97.132941176470682.563
924517AB2-100 E2
Adder
4.5505882352941183.868
961942AG1-037 E
Adder
0.54705882352941180.465
316141AB2-099 E
Adder
0.410588235294117640.349
961941AG1-037 C
Adder
0.82117647058823530.698
923263AB1-132 E OP
Adder
9.595294117647068.156
316088AB2-174 E
Adder
10.1435294117647078.622
923994AB2-040_E
Adder
9.5835294117647068.146
941031AE2-094 C
Adder
59.2294117647058850.345
941032AE2-094 E
Adder
26.52705882352941222.548
957481AF2-042 C
Adder
70.616470588235360.024
927041AC1-191 C
Adder
16.38352941176470513.926
966871AG1-558 C
Adder
4.083.468
966872AG1-558 E
Adder
2.0552941176470591.747
316157AD2-030 E
Adder
1.99764705882352931.698
936592AD2-074 E
Adder
14.19411764705882312.065
936591AD2-074 C
Adder
8.77.395
961952AG1-038 E
Adder
6.9482352941176475.906
961951AG1-038 C
Adder
5.0317647058823534.277
939602AE1-190 E
Adder
2.40470588235294122.044
925865AC1-065 E
Adder
28.22117647058823723.988
943471AF1-018 C
Adder
12.15411764705882410.331
3130536PAPERMILL
Adder
11.342352941176479.641
926785AC1-164_E
50/50
33.18433.184
316160AE1-175 E
50/50
2.1682.168
944631AF1-128 C
50/50
71.28371.283
3150921YORKTN3
Adder
215.8894117647059183.506
3150651CHESTF6
Adder
32.7305882352941227.821
946262AF1-291 E
Adder
2.5188235294117652.141
934576AD1-082 E
Adder
7.6470588235294126.5
316084AB2-161 E
Adder
9.597647058823538.158
3145256KINGFORK
Adder
1.78823529411764711.52
3152331SURRY 2
50/50
45.79645.796
925522AC1-027 E
Adder
2.14588235294117661.824
943612AF1-032 E
Adder
1.61764705882352941.375
941102AE2-104 E
Adder
9.2858823529411767.893
3145506HICKORY
Adder
3.83058823529411763.256
944602AF1-125 E
Adder
180.73058823529414153.621
957872AF2-081 E
Adder
7.50470588235294046.379
957871AF2-081 C
Adder
17.5105882352941214.884
933292AC2-141 E
Adder
23.1894117647058819.711
933291AC2-141 C
Adder
54.3223529411764746.174
926755AC1-161 E
Adder
23.1894117647058819.711
940492AE2-034 E
Adder
5.2011764705882364.421
3145946PLYMOUTH TP
Adder
0.540.459
934522AD1-076 E
Adder
10.4035294117647078.843
938552AE1-074 E
Adder
2.05764705882352941.749
933982AD1-022 E
Adder
7.9164705882352956.729
943172AE2-346 E
Adder
0.98588235294117640.838
940641AE2-051 C
Adder
26.96705882352941322.922
918492AA1-063AE OP
Adder
6.5082352941176485.532
925122AB2-169 E
Adder
9.3470588235294127.945
917332KELFORD E
Adder
2.63882352941176462.243
946282AF1-292 E
Adder
1.61.36
944012AF1-069 E
Adder
7.5176470588235296.39
939612AE1-191 E
Adder
9.628.177
316169AC1-164 GEN
50/50
73.86273.862
940432AE2-027 E
Adder
15.04705882352941212.79
316159AE1-175 C
50/50
0.7110.711
3150731STONECA
Adder
12.26941176470588210.429
935161AD1-151 C
Adder
28.70588235294117424.4
934012AD1-025 E
Adder
17.78941176470588215.121
930122AB1-027 E
50/50
2.5162.516
926412AC1-112 E
50/50
2.0462.046
316312AB1-027 C
50/50
0.9560.956
3150701DARBY 4
50/50
4.5944.594
3142366NRTHEST
50/50
0.330.33
935112AD1-144 E
Adder
1.66000000000000011.411
943462AF1-017 E
Adder
3.8317647058823533.257
316349AD2-085 C
Adder
5.9894117647058835.091
942341AE2-247 C
Adder
2.5964705882352942.207
932046AC2-012 E
Adder
23.15176470588235319.679
958161AF2-110 C
Adder
2.38352941176470572.026
958162AF2-110 E
Adder
3.79058823529411763.222
944582AF1-123 E
Adder
183.61176470588234156.07
944592AF1-124 E
Adder
184.2764705882353156.635
919153AA1-139 E2
Adder
7.166.086
938531AE1-072 C
Adder
30.75647058823529526.143
923832AB2-022 E
Adder
2.16117647058823531.837
913392Y1-086 E
Adder
3.8282352941176473.254
938772AE1-103 E
Adder
6.8741176470588235.843
916042Z1-036 E
Adder
48.916470588235341.579
3145393UNCAMP
Adder
10.2788235294117658.737
934502AD1-074 E
Adder
28.60941176470588624.318
934512AD1-075 E
Adder
7.1529411764705896.08
939411AE1-173 C
Adder
145.69882352941175123.844
933981AD1-022 C
Adder
14.54117647058823512.36
900672V4-068 E
Adder
0.58235294117647060.495
918512AA1-065 E OP
Adder
9.0517647058823547.694
924516AB2-100 E1
Adder
4.5505882352941183.868
940642AE2-051 E
Adder
17.97882352941176615.282
966621AG1-532 C
Adder
2.1752941176470591.849
960082AF2-299 E
Adder
1.93294117647058841.643
946281AF1-292 C
Adder
2.40117647058823552.041
926071AC1-086 C
Adder
32.9682352941176528.023
3137643SOCKMAN
Adder
1.1117647058823530.945
963042AG1-153 E
Adder
12.44941176470588410.582
957602AF2-054 E
Adder
2.37411764705882342.018
G-007PJM->LTFIMP_G-007
CMTX_NF
9.2239.223
SIGELTFEXP_SIGE->PJM
CLTF
0.620.62
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.4068.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
156.721156.721
CPLELTFEXP_CPLE->PJM
CLTF
17.60917.609
TVALTFEXP_TVA->PJM
CLTF
12.40612.406
O66PJM->LTFIMP_O-066
CMTX_NF
58.60758.607
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.33484.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.67448.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
9.5679.567
LAGNLTFEXP_LAGN->PJM
CLTF
15.46415.464
NYPJM->LTFIMP_NY
CLTF
4.1384.138
LGEELTFEXP_LGEE->PJM
CLTF
3.3583.358
WECLTFEXP_WEC->PJM
CLTF
1.7271.727

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.74 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4100.48
MW Contribution:64.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936591AD2-074 C
Adder
7.3964705882352946.287
961951AG1-038 C
Adder
4.277647058823533.636
943471AF1-018 C
Adder
10.3670588235294128.812
944631AF1-128 C
80/20
57.75157.751
3150921YORKTN3
80/20
186.63186.63
3144216WINCHST
80/20
0.2040.204
934011AD1-025 C
80/20
3.8313.831
316033AB2-134 GEN
80/20
3.0983.098
3151191GRAVEL3
80/20
3.7583.758
3151221GRAVEL6
80/20
3.8023.802
3151201GRAVEL4
80/20
3.8063.806
3151211GRAVEL5
80/20
3.7583.758
316236AE1-162 C
80/20
0.5280.528
3150651CHESTF6
Adder
26.14823529411764722.226
3152331SURRY 2
80/20
40.26840.268
316316AC1-027 C
80/20
0.4790.479
957871AF2-081 C
80/20
15.09215.092
316017AA1-139 ULT1
80/20
1.6281.628
316018AA1-139 ULT2
80/20
1.6281.628
933291AC2-141 C
80/20
47.32947.329
313526AB2-022 C
80/20
0.5630.563
940641AE2-051 C
Adder
23.00823529411764719.557
316274AC1-208 C
Adder
11.86588235294117810.086
3151311EDGECMA
Adder
20.00352941176470617.003
3152161CUNINGA
80/20
7.9167.916
3152181CUNINGC
80/20
7.9167.916
3152171CUNINGB
80/20
7.9167.916
966661AG1-536 C
Adder
6.96705882352941155.922
316169AC1-164 GEN
80/20
63.00863.008
316159AE1-175 C
80/20
0.6130.613
3150731STONECA
Adder
9.9858823529411778.488
935161AD1-151 C
80/20
23.75423.754
316312AB1-027 C
80/20
0.8120.812
3151161SURRY 1
80/20
36.99436.994
316349AD2-085 C
Adder
5.0752941176470594.314
942341AE2-247 C
Adder
2.21.87
3150991CHESPKB
80/20
1.0961.096
3151091ELIZAR2
80/20
4.7734.773
316246AF1-032 C
80/20
0.4270.427
958161AF2-110 C
80/20
2.042.04
316388AE2-253 GEN
80/20
2.9612.961
938531AE1-072 C
80/20
26.50226.502
316320Y1-086 C
80/20
0.3290.329
939411AE1-173 C
Adder
124.68470588235294105.982
933981AD1-022 C
Adder
12.41647058823529510.554
966621AG1-532 C
Adder
1.81764705882352941.545
946281AF1-292 C
Adder
2.00588235294117641.705
926071AC1-086 C
Adder
27.76352941176470823.599
3137643SOCKMAN
Adder
0.93411764705882360.794
927021AC1-189 C
Adder
11.1482352941176499.476
958261AF2-120 C
Adder
8.16.885
940551AE2-041 C
Adder
10.3670588235294128.812
316382AG1-145 C
80/20
0.5540.554
3150601CHESTF5
80/20
92.29692.296
3150631CHESTG8
80/20
5.5225.522
3150621CHESTS7
80/20
2.5762.576
316004AC1-112 C
80/20
0.5060.506
3151171GRAVELC
80/20
1.2921.292
939191AE1-149 C
Adder
15.33294117647058713.033
944641AF1-129 C
Adder
143.61529411764707122.073
316240AF1-291 C
Adder
3.02705882352941162.573
943461AF1-017 C
Adder
1.99058823529411751.692
316311AC2-079 C
Adder
8.4682352941176487.198
3150981CHESPKA
80/20
0.6610.661
316036AC1-147 C
80/20
0.5590.559
941591AE2-156 C
80/20
27.25627.256
3151101ELIZAR3
80/20
4.9194.919
316305AF2-043 C
80/20
0.5230.523
944591AF1-124 C
80/20
69.53869.538
944601AF1-125 C
80/20
68.22568.225
316321Z2-027 C
80/20
0.5420.542
938771AE1-103 C
Adder
4.2458823529411773.609
934521AD1-076 C
Adder
17.4447058823529414.828
934511AD1-075 C
Adder
12.00823529411764810.207
3142296MT RD221
80/20
0.180.18
960081AF2-299 C
Adder
2.4235294117647062.06
944011AF1-069 C
Adder
16.40117647058823613.941
963041AG1-153 C
Adder
7.0223529411764725.969
316263AC1-034 C
Adder
8.5517647058823547.269
957601AF2-054 C
Adder
3.03647058823529432.581
963611AG1-210 C
Adder
0.81058823529411760.689
962861AG1-135 C
Adder
7.9105882352941186.724
943741AF1-042 C
Adder
3.87058823529411773.29
940431AE2-027 C
Adder
18.18117647058823715.454
316075AC2-137 C
80/20
0.5730.573
3150641CHESTS8
80/20
2.8432.843
3150611CHESTG7
80/20
5.6125.612
316369AC1-216 C
80/20
2.3642.364
961611AG1-000B C
80/20
23.84623.846
942001AE2-212 C
Adder
3.01764705882352932.565
3150831SPRUNCA
Adder
10.6141176470588259.022
3150841SPRUNCB
Adder
10.6141176470588259.022
316072AD1-144 C
80/20
0.4250.425
316375AC2-012 C
80/20
2.0492.049
3151081ELIZAR1
80/20
4.8584.858
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
55
316185AD1-033 C
80/20
1.8591.859
944581AF1-123 C
80/20
69.29269.292
316294AC1-161 C
80/20
7.7077.707
940541AE2-040 C
Adder
3.7941176470588243.225
940481AE2-033 C
Adder
21.37647058823529618.17
934501AD1-074 C
Adder
48.0341176470588340.829
961941AG1-037 C
Adder
0.69764705882352940.593
941031AE2-094 C
Adder
50.196470588235342.667
934331AD1-057 C
Adder
4.5482352941176483.866
934321AD1-056 C
Adder
8.1541176470588246.931
961671AG1-007 C
Adder
1.22941176470588221.045
957481AF2-042 C
Adder
64.7188235294117655.011
927041AC1-191 C
Adder
13.58823529411764911.55
966871AG1-558 C
Adder
3.3847058823529412.877
934621AD1-088 C
Adder
11.2658823529411789.576
3152191CUNINGD
80/20
17.70617.706
957831AF2-077 C
80/20
0.4940.494
964211AG1-282 C
Adder
2.5270588235294122.148
SIGELTFEXP_SIGE->PJM
CLTF
0.5440.544
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1467.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
133.887133.887
CPLELTFEXP_CPLE->PJM
CLTF
14.96914.969
TVALTFEXP_TVA->PJM
CLTF
10.74810.748
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.17274.172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.32542.325
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.3698.369
LAGNLTFEXP_LAGN->PJM
CLTF
13.38813.388
NYPJM->LTFIMP_NY
CLTF
3.5973.597
LGEELTFEXP_LGEE->PJM
CLTF
2.952.95
WECLTFEXP_WEC->PJM
CLTF
1.5171.517

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.26 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3228.89
MW Contribution:40.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936591AD2-074 C
Adder
4.6894117647058823.986
961951AG1-038 C
Adder
2.7117647058823532.305
943471AF1-018 C
Adder
6.2364705882352955.301
944631AF1-128 C
80/20
36.1936.19
3150921YORKTN3
Adder
107.0694117647058991.009
3150651CHESTF6
Adder
16.84705882352941214.32
3150851SPRUNCC
80/20
0.1470.147
3150861SPRUNCD
80/20
0.1470.147
957871AF2-081 C
Adder
8.7129411764705887.406
933291AC2-141 C
Adder
26.7822.763
940641AE2-051 C
Adder
13.71529411764705811.658
316336AC2-165 C
Adder
7.7411764705882356.58
3150481FOUR RIVERF
80/20
3.5533.553
3150461FOUR RIVERD
80/20
2.9092.909
3150471FOUR RIVERE
80/20
2.9092.909
3150441FOUR RIVERB
80/20
2.9522.952
315052AA1-145 CT2
80/20
4.74.7
3150431FOUR RIVERA
80/20
2.9522.952
3152251N ANNA1
80/20
26.07926.079
966661AG1-536 C
Adder
4.4905882352941183.817
316169AC1-164 GEN
80/20
36.80636.806
3150731STONECA
Adder
6.2458823529411775.309
935161AD1-151 C
Adder
14.5176470588235312.34
316312AB1-027 C
80/20
0.4890.489
3150701DARBY 4
80/20
2.3652.365
3142366NRTHEST
80/20
0.1710.171
316349AD2-085 C
Adder
3.0105882352941182.559
942341AE2-247 C
Adder
1.30470588235294121.109
958161AF2-110 C
Adder
1.19176470588235281.013
938531AE1-072 C
Adder
15.30823529411764713.012
939411AE1-173 C
Adder
73.6611764705882562.612
933981AD1-022 C
Adder
7.3258823529411776.227
966621AG1-532 C
Adder
1.1164705882352940.949
946281AF1-292 C
Adder
1.23176470588235291.047
926071AC1-086 C
Adder
16.83294117647058714.308
3137643SOCKMAN
Adder
0.56941176470588240.484
315051AA1-145 CT1
80/20
4.7034.703
3150451FOUR RIVERC
80/20
3.6073.607
3152261N ANNA2
80/20
26.0926.09
939261AE1-157 C
80/20
13.3213.32
958261AF2-120 C
Adder
5.2200000000000014.437
940551AE2-041 C
Adder
6.2364705882352955.301
3150601CHESTF5
80/20
57.83757.837
3150631CHESTG8
80/20
3.4613.461
3150621CHESTS7
80/20
1.6141.614
3143096IRON208
80/20
0.4040.404
316004AC1-112 C
80/20
0.3050.305
3150691DARBY 3
80/20
2.3622.362
939191AE1-149 C
Adder
9.4788235294117668.057
944641AF1-129 C
Adder
92.5282352941176578.649
316240AF1-291 C
Adder
1.94470588235294131.653
943461AF1-017 C
Adder
1.18117647058823531.004
316311AC2-079 C
Adder
5.0141176470588234.262
941591AE2-156 C
Adder
15.7305882352941213.371
944591AF1-124 C
Adder
39.9505882352941233.958
944601AF1-125 C
Adder
39.1964705882352933.317
938771AE1-103 C
Adder
2.5011764705882352.126
934521AD1-076 C
Adder
10.2717647058823538.731
934511AD1-075 C
Adder
7.0705882352941176.01
316233AE1-074 C
Adder
2.1552941176470591.832
3142296MT RD221
80/20
0.1140.114
960081AF2-299 C
Adder
1.48823529411764691.265
944011AF1-069 C
Adder
9.9305882352941198.441
963041AG1-153 C
Adder
4.2658823529411763.626
957601AF2-054 C
Adder
1.83764705882352961.562
966881AG1-559 C
80/20
2.2882.288
3150381LDYSMT2
80/20
4.3034.303
3150411LDYSMT5
80/20
4.4394.439
963611AG1-210 C
Adder
0.53882352941176470.458
962861AG1-135 C
Adder
5.0788235294117654.317
943741AF1-042 C
Adder
2.45411764705882352.086
940431AE2-027 C
Adder
11.5988235294117659.859
316075AC2-137 C
80/20
0.3470.347
3150641CHESTS8
80/20
1.7811.781
3150611CHESTG7
80/20
3.5173.517
3150681DARBY 2
80/20
2.3542.354
3150671DARBY 1
80/20
2.3512.351
961611AG1-000B C
Adder
14.23176470588235412.097
942001AE2-212 C
Adder
1.92117647058823531.633
3150831SPRUNCA
Adder
8.2188235294117656.986
3150841SPRUNCB
80/20
8.2198.219
941101AE2-104 C
Adder
2.92000000000000042.482
944581AF1-123 C
Adder
39.80941176470588533.838
940541AE2-040 C
Adder
2.33294117647058831.983
940481AE2-033 C
Adder
13.13529411764705811.165
934501AD1-074 C
Adder
28.28352941176470724.041
961941AG1-037 C
Adder
0.41529411764705880.353
941031AE2-094 C
Adder
30.39411764705882425.835
957481AF2-042 C
Adder
40.39647058823529634.337
927041AC1-191 C
80/20
8.8178.817
966871AG1-558 C
80/20
2.1962.196
934621AD1-088 C
Adder
7.1611764705882356.087
3150391LDYSMT3
80/20
4.4174.417
3150401LDYSMT4
80/20
4.4254.425
3150371LDYSMT1
80/20
4.2494.249
964211AG1-282 C
Adder
1.65294117647058841.405
SIGELTFEXP_SIGE->PJM
CLTF
0.3350.335
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.3484.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.51781.517
CPLELTFEXP_CPLE->PJM
CLTF
9.1099.109
TVALTFEXP_TVA->PJM
CLTF
6.5746.574
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.86545.865
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.97725.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.1595.159
LAGNLTFEXP_LAGN->PJM
CLTF
8.1928.192
NYPJM->LTFIMP_NY
CLTF
2.8322.832
LGEELTFEXP_LGEE->PJM
CLTF
1.8211.821
WECLTFEXP_WEC->PJM
CLTF
0.9380.938

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.3 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1082.52
MW Contribution:28.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316316AC1-027 C
80/20
0.1220.122
957871AF2-081 C
80/20
3.9453.945
316017AA1-139 ULT1
80/20
0.4260.426
316018AA1-139 ULT2
80/20
0.4260.426
933291AC2-141 C
80/20
12.90812.908
316375AC2-012 C
80/20
0.5120.512
3151081ELIZAR1
80/20
1.2251.225
916191Z1-068 C
80/20
0.0170.017
941101AE2-104 C
Adder
1.23294117647058821.048
316185AD1-033 C
80/20
0.4830.483
944581AF1-123 C
80/20
18.55418.554
313526AB2-022 C
80/20
0.1480.148
316315AB2-025 C
80/20
0.170.17
3152921DOMTR78
80/20
0.5530.553
316023AB2-100 C2
80/20
0.3950.395
316140AB2-099 C
80/20
0.0390.039
940641AE2-051 C
80/20
11.28211.282
316317KELFORD C
80/20
0.1460.146
932631AC2-084 C
80/20
0.4150.415
3152431Z1-086 GT3
80/20
6.8556.855
316274AC1-208 C
80/20
3.7453.745
316129AC1-054 C
80/20
0.4920.492
3151311EDGECMA
Adder
6.6317647058823535.637
934611AD1-087 C
80/20
0.6150.615
3151611KERR 4
80/20
0.460.46
3151631KERR 6
80/20
0.460.46
3151641KERR 7
80/20
0.460.46
3151621KERR 5
80/20
0.460.46
316336AC2-165 C
Adder
-10.934117647058825-9.294
316222AC1-221 C
80/20
0.6220.622
941011AE2-092 C
Adder
-4.542352941176471-3.861
316349AD2-085 C
Adder
1.08823529411764720.925
942341AE2-247 C
Adder
0.4717647058823530.401
3150991CHESPKB
80/20
0.2740.274
3151091ELIZAR2
80/20
1.2031.203
316246AF1-032 C
80/20
0.1090.109
958161AF2-110 C
Adder
0.50352941176470590.428
316388AE2-253 GEN
80/20
0.7730.773
938531AE1-072 C
80/20
6.9356.935
316320Y1-086 C
80/20
0.0860.086
939411AE1-173 C
80/20
53.71753.717
933981AD1-022 C
80/20
3.5393.539
316318V4-068 C
80/20
0.0320.032
3156021HOLLOMANSOL
80/20
0.7440.744
316174AB2-169_C
80/20
0.4290.429
966621AG1-532 C
80/20
0.5650.565
946281AF1-292 C
80/20
0.6230.623
316011AB1-132 C OP
80/20
0.9580.958
926071AC1-086 C
80/20
8.6598.659
313506AB1-173 C OP
80/20
0.4550.455
3156063AA2-053SOLA
80/20
0.6120.612
3151371ROSEMS1
80/20
0.520.52
3137643SOCKMAN
80/20
0.290.29
3151281ROARAP4
80/20
0.5320.532
316210AC1-098 C
80/20
0.390.39
927021AC1-189 C
Adder
3.55058823529411743.018
3151601KERR 3
80/20
0.460.46
3151581KERR 1
80/20
0.1640.164
935171AD1-152 C
80/20
0.6280.628
964241AG1-285 C
Adder
3.8988235294117653.314
962561AG1-105 C
Adder
3.34823529411764742.846
936161AD2-022 C
Adder
3.11647058823529432.649
943461AF1-017 C
Adder
0.427058823529411770.363
316311AC2-079 C
Adder
1.8517647058823531.574
3150981CHESPKA
80/20
0.1650.165
316036AC1-147 C
80/20
0.140.14
941591AE2-156 C
80/20
6.8286.828
3151101ELIZAR3
80/20
1.241.24
316305AF2-043 C
80/20
0.1340.134
944591AF1-124 C
80/20
18.6218.62
944601AF1-125 C
80/20
18.26818.268
316321Z2-027 C
80/20
0.1430.143
3156056W1-029WIND
80/20
0.3040.304
938771AE1-103 C
Adder
1.1117647058823530.945
934521AD1-076 C
80/20
4.9354.935
934511AD1-075 C
80/20
3.3973.397
3156073AA1-063SOLA
80/20
0.5640.564
960081AF2-299 C
80/20
0.7530.753
316087AB2-174 C
80/20
0.4750.475
3151381ROSEMG2
80/20
0.3930.393
3151361ROSEMG1
80/20
0.840.84
3151261ROARAP2
80/20
0.5630.563
944011AF1-069 C
80/20
8.7098.709
316212AC1-099 C
80/20
0.130.13
3152421Z1-086 GT2
80/20
6.8556.855
3152441Z1-086 ST
80/20
11.93511.935
3152411Z1-086 GT1
80/20
6.8566.856
963041AG1-153 C
80/20
3.6093.609
3151051BRUNSWICKS1
80/20
11.02811.028
3151041BRUNSWICKG3
80/20
5.3085.308
316327AA2-057 C
80/20
0.5450.545
316263AC1-034 C
Adder
2.8352941176470592.41
937481AD2-202 C
80/20
0.1780.178
3151591KERR 2
80/20
0.460.46
964791AG1-342 C
Adder
1.35764705882352941.154
316248AF1-058 C
80/20
0.130.13
936171AD2-023 C
Adder
1.81764705882352941.545
316294AC1-161 C
80/20
2.1022.102
3156116Z1-036WIND
80/20
0.260.26
315614AA2-178 C
80/20
0.6260.626
940491AE2-034 C
80/20
0.460.46
940541AE2-040 C
80/20
1.21.2
940481AE2-033 C
80/20
6.7556.755
934501AD1-074 C
80/20
13.58913.589
3156083AA2-088SOLA
80/20
0.4170.417
316365AB2-100 C1
80/20
0.3950.395
943171AE2-346 C
80/20
0.090.09
961941AG1-037 C
80/20
0.2040.204
3151391GASTONA
80/20
1.2541.254
3151411GASTONB
80/20
1.2541.254
316181AB2-040 GEN
80/20
0.5130.513
941031AE2-094 C
80/20
26.65326.653
3151021BRUNSWICKG1
80/20
5.3085.308
3151031BRUNSWICKG2
80/20
5.3085.308
934331AD1-057 C
80/20
1.4711.471
934321AD1-056 C
80/20
2.6372.637
961671AG1-007 C
Adder
0.398823529411764740.339
957481AF2-042 C
80/20
28.07228.072
934621AD1-088 C
80/20
4.3734.373
3151531CLOVER1
80/20
6.2476.247
3151541CLOVER2
80/20
6.1886.188
316283AC2-100 C
80/20
0.5020.502
938821AE1-108 C
Adder
-4.681176470588236-3.979
SIGELTFEXP_SIGE->PJM
CLTF
0.1080.108
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5692.569
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.4944.49
CPLELTFEXP_CPLE->PJM
CLTF
5.3885.388
TVALTFEXP_TVA->PJM
CLTF
2.7252.725
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.11814.118
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.08110.081
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.7671.767
LAGNLTFEXP_LAGN->PJM
CLTF
3.483.48
NYPJM->LTFIMP_NY
CLTF
0.5550.555
LGEELTFEXP_LGEE->PJM
CLTF
0.550.55
WECLTFEXP_WEC->PJM
CLTF
0.2910.291

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.4 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3845.28
MW Contribution:80.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316169AC1-164 GEN
Adder
49.0282352941176541.674
3150731STONECA
Adder
9.5788235294117648.142
935161AD1-151 C
Adder
22.80117647058823519.381
3151161SURRY 1
80/20
35.54335.543
316381AD1-082 C
80/20
1.8751.875
316083AB2-161 C
80/20
0.8230.823
316349AD2-085 C
80/20
5.1625.162
942341AE2-247 C
80/20
2.2382.238
3150991CHESPKB
80/20
1.0871.087
3151091ELIZAR2
80/20
4.7364.736
316246AF1-032 C
80/20
0.4280.428
958161AF2-110 C
80/20
2.0582.058
316388AE2-253 GEN
80/20
2.9552.955
938531AE1-072 C
80/20
26.49826.498
316320Y1-086 C
80/20
0.330.33
939411AE1-173 C
80/20
143.49143.49
933981AD1-022 C
Adder
12.98823529411764711.04
966621AG1-532 C
Adder
2.06235294117647071.753
946281AF1-292 C
Adder
2.2752941176470591.934
926071AC1-086 C
Adder
30.83882352941176626.213
3137643SOCKMAN
Adder
1.04352941176470580.887
927021AC1-189 C
Adder
12.14117647058823710.32
964241AG1-285 C
Adder
17.31176470588235414.715
962561AG1-105 C
Adder
12.25882352941176610.42
940551AE2-041 C
Adder
8.4917647058823537.218
3150601CHESTF5
Adder
83.0647058823529570.605
939191AE1-149 C
80/20
15.94215.942
944641AF1-129 C
Adder
144.29529411764705122.651
316240AF1-291 C
Adder
3.0682352941176472.608
943461AF1-017 C
80/20
2.0242.024
316311AC2-079 C
80/20
8.6058.605
3150981CHESPKA
80/20
0.6560.656
316036AC1-147 C
80/20
0.5540.554
941591AE2-156 C
80/20
27.03327.033
3151101ELIZAR3
80/20
4.8814.881
316305AF2-043 C
80/20
0.5240.524
944591AF1-124 C
80/20
69.22169.221
944601AF1-125 C
80/20
67.91467.914
316321Z2-027 C
80/20
0.5460.546
3156056W1-029WIND
80/20
1.1641.164
938771AE1-103 C
80/20
4.3814.381
934521AD1-076 C
Adder
18.1705882352941215.445
934511AD1-075 C
Adder
12.50823529411764710.632
316233AE1-074 C
80/20
3.9163.916
960081AF2-299 C
Adder
2.74941176470588242.337
944011AF1-069 C
80/20
20.63520.635
3152421Z1-086 GT2
80/20
16.53816.538
3152441Z1-086 ST
80/20
28.79528.795
3152411Z1-086 GT1
80/20
16.54216.542
963041AG1-153 C
80/20
8.7798.779
3151051BRUNSWICKS1
80/20
26.8326.83
3151041BRUNSWICKG3
80/20
12.91412.914
316263AC1-034 C
Adder
9.488.058
936261AD2-033 C
Adder
17.81058823529411615.139
316313AB2-026 C
80/20
0.5590.559
959311AF2-222 C
Adder
22.66470588235294419.265
964791AG1-342 C
Adder
4.884.148
961791AG1-021 C
Adder
2.40470588235294122.044
957601AF2-054 C
Adder
2.53058823529411742.151
940431AE2-027 C
Adder
18.39647058823529615.637
961611AG1-000B C
Adder
22.90588235294117719.47
942001AE2-212 C
80/20
3.1513.151
3150831SPRUNCA
80/20
13.15813.158
3150841SPRUNCB
80/20
13.15813.158
316072AD1-144 C
80/20
0.4180.418
316375AC2-012 C
80/20
2.0322.032
3151081ELIZAR1
80/20
4.824.82
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
5.0455.045
316185AD1-033 C
80/20
1.8511.851
944581AF1-123 C
80/20
68.97668.976
316294AC1-161 C
80/20
7.5057.505
3156116Z1-036WIND
80/20
0.9810.981
940541AE2-040 C
80/20
4.3564.356
940481AE2-033 C
80/20
24.49624.496
934501AD1-074 C
Adder
50.0317647058823542.527
316365AB2-100 C1
80/20
1.4231.423
961941AG1-037 C
Adder
0.74470588235294120.633
941031AE2-094 C
80/20
63.15563.155
3151021BRUNSWICKG1
80/20
12.91412.914
3151031BRUNSWICKG2
80/20
12.91412.914
934331AD1-057 C
Adder
5.04588235294117654.289
934321AD1-056 C
Adder
9.0458823529411777.689
961671AG1-007 C
Adder
1.34941176470588231.147
957481AF2-042 C
80/20
80.37380.373
934621AD1-088 C
80/20
14.01914.019
3151531CLOVER1
80/20
18.57418.574
3151541CLOVER2
80/20
18.39918.399
316258AE1-075 C
80/20
0.5130.513
958211AF2-115 C
Adder
3.0058823529411772.555
946301AF1-294 C
Adder
4.9423529411764714.201
942461AE2-259 C
Adder
12.99058823529411711.042
943471AF1-018 C
Adder
8.4917647058823537.218
944631AF1-128 C
Adder
51.9752941176470644.179
3150921YORKTN3
Adder
165.5670588235294140.732
3151191GRAVEL3
80/20
3.6113.611
3151221GRAVEL6
80/20
3.6533.653
3151201GRAVEL4
80/20
3.6573.657
3151211GRAVEL5
80/20
3.6113.611
316236AE1-162 C
80/20
0.5140.514
3150651CHESTF6
Adder
26.27176470588235422.331
3150851SPRUNCC
80/20
0.2360.236
3150861SPRUNCD
80/20
0.2360.236
3152331SURRY 2
80/20
35.95635.956
316316AC1-027 C
80/20
0.4760.476
957871AF2-081 C
80/20
15.07515.075
316017AA1-139 ULT1
80/20
1.6261.626
316018AA1-139 ULT2
80/20
1.6261.626
933291AC2-141 C
80/20
46.08646.086
313526AB2-022 C
80/20
0.5650.565
316315AB2-025 C
80/20
0.6170.617
316023AB2-100 C2
80/20
1.4231.423
940641AE2-051 C
80/20
27.74527.745
3152431Z1-086 GT3
80/20
16.53816.538
316274AC1-208 C
Adder
13.08588235294117711.123
3151311EDGECMA
Adder
22.1658823529411818.841
316405AF2-144 C
80/20
0.4360.436
3138533PONTONDP
Adder
0.89058823529411770.757
316336AC2-165 C
Adder
14.04941176470588411.942
316303AF2-085
80/20
6.4786.478
SIGELTFEXP_SIGE->PJM
CLTF
0.4870.487
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.9747.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
144.491144.491
CPLELTFEXP_CPLE->PJM
CLTF
16.71416.714
TVALTFEXP_TVA->PJM
CLTF
10.46710.467
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.12565.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.22440.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6237.623
LAGNLTFEXP_LAGN->PJM
CLTF
13.13513.135
NYPJM->LTFIMP_NY
CLTF
3.1863.186
LGEELTFEXP_LGEE->PJM
CLTF
2.5932.593
WECLTFEXP_WEC->PJM
CLTF
1.3381.338

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.79 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4640.88
MW Contribution:134.88
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150921YORKTN3
Adder
168.0623529411765142.853
3150651CHESTF6
Adder
26.6976470588235322.693
946262AF1-291 E
Adder
2.07764705882352941.766
934576AD1-082 E
Adder
6.6517647058823535.654
316084AB2-161 E
Adder
8.3482352941176477.096
3145256KINGFORK
Adder
1.52941176470588251.3
925522AC1-027 E
50/50
1.8591.859
316316AC1-027 C
50/50
0.4810.481
943612AF1-032 E
Adder
1.40941176470588241.198
941102AE2-104 E
Adder
8.1105882352941186.894
3145506HICKORY
50/50
3.3283.328
944602AF1-125 E
50/50
157.162157.162
957872AF2-081 E
Adder
6.53176470588235255.552
957871AF2-081 C
Adder
15.24000000000000212.954
933292AC2-141 E
50/50
19.88619.886
933291AC2-141 C
50/50
46.58646.586
926755AC1-161 E
50/50
19.88619.886
940492AE2-034 E
Adder
4.6423529411764713.946
316315AB2-025 C
50/50
0.6230.623
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
934522AD1-076 E
Adder
9.3564705882352957.953
938552AE1-074 E
50/50
1.9951.995
933982AD1-022 E
Adder
7.1423529411764716.071
943172AE2-346 E
Adder
0.90235294117647060.767
940641AE2-051 C
50/50
27.94427.944
918492AA1-063AE OP
Adder
6.065.151
946282AF1-292 E
Adder
1.53058823529411761.301
944012AF1-069 E
50/50
8.0688.068
3152431Z1-086 GT3
50/50
16.64616.646
934622AD1-088 E
Adder
6.79647058823529455.777
937482AD2-202 E
Adder
1.561.326
934612AD1-087 E
Adder
5.3305882352941174.531
938562AE1-075 E
Adder
1.56235294117647071.328
316336AC2-165 C
Adder
11.2529411764705879.565
940432AE2-027 E
Adder
12.45529411764705910.587
3150731STONECA
Adder
9.735294117647068.275
935161AD1-151 C
Adder
23.14823529411764719.676
934012AD1-025 E
Adder
14.40588235294117712.245
935112AD1-144 E
Adder
1.42000000000000021.207
943462AF1-017 E
Adder
3.34117647058823542.84
316349AD2-085 C
Adder
5.2223529411764714.439
942341AE2-247 C
Adder
2.2635294117647061.924
932046AC2-012 E
50/50
20.00120.001
3151091ELIZAR2
50/50
4.7894.789
958161AF2-110 C
Adder
2.0811764705882351.769
958162AF2-110 E
Adder
3.31058823529411762.814
944582AF1-123 E
50/50
159.668159.668
944592AF1-124 E
50/50
160.246160.246
919153AA1-139 E2
Adder
6.2317647058823535.297
938531AE1-072 C
Adder
26.78823529411764822.77
923832AB2-022 E
Adder
1.8882352941176471.605
913392Y1-086 E
Adder
3.3447058823529412.843
938772AE1-103 E
Adder
6.115294117647065.198
916042Z1-036 E
Adder
43.2517647058823636.764
3145393UNCAMP
Adder
9.1811764705882367.804
934502AD1-074 E
Adder
25.72941176470588321.87
934512AD1-075 E
Adder
6.4317647058823535.467
939411AE1-173 C
50/50
144.64144.64
933981AD1-022 C
Adder
13.12117647058823711.153
900672V4-068 E
Adder
0.53294117647058830.453
918512AA1-065 E OP
Adder
8.2458823529411777.009
924516AB2-100 E1
Adder
4.3447058823529413.693
940642AE2-051 E
50/50
18.62918.629
966621AG1-532 C
Adder
2.0811764705882351.769
960082AF2-299 E
Adder
1.84941176470588251.572
946281AF1-292 C
Adder
2.2964705882352941.952
926071AC1-086 C
Adder
31.12823529411764826.459
3137643SOCKMAN
Adder
1.05294117647058830.895
963042AG1-153 E
50/50
13.25613.256
925332AB2-190 E
Adder
11.5352941176470599.805
935162AD1-151 E
Adder
15.43176470588235513.117
927226AC1-216 E
Adder
11.1270588235294129.458
924814AB2-134 E
Adder
18.2270588235294115.493
939191AE1-149 C
Adder
16.1494117647058813.727
944641AF1-129 C
Adder
146.62823529411764124.634
316240AF1-291 C
Adder
3.11647058823529432.649
936666AD2-085 E
Adder
8.5211764705882367.243
942342AE2-247 E
Adder
3.12588235294117662.657
943461AF1-017 C
Adder
2.0482352941176471.741
3143316POE
50/50
2.082.08
932596AC2-079 E
Adder
14.20352941176470712.073
316311AC2-079 C
Adder
8.7047058823529427.399
941591AE2-156 C
50/50
27.33727.337
3151101ELIZAR3
50/50
4.9364.936
944591AF1-124 C
50/50
69.97569.975
944601AF1-125 C
50/50
68.65368.653
919152AA1-139 E1
Adder
6.2317647058823535.297
938532AE1-072 E
Adder
13.96470588235294111.87
3146326AYDLETT TAP
Adder
2.06705882352941161.757
917122Z2-027 E
Adder
2.04352941176470631.737
901082W1-029 E
Adder
48.43294117647058541.168
938771AE1-103 C
Adder
4.4282352941176473.764
3145413WATKINS
Adder
1.04117647058823540.885
920692AA2-178 E
Adder
6.19058823529411755.262
934521AD1-076 C
Adder
18.35647058823529315.603
934511AD1-075 C
Adder
12.6352941176470610.74
316233AE1-074 C
50/50
3.9613.961
920042AA2-088 E OP
Adder
15.88941176470588313.506
960081AF2-299 C
Adder
2.7741176470588242.358
966622AG1-532 E
Adder
1.3870588235294121.179
926072AC1-086 E
Adder
14.16705882352941312.042
3145723EMPORIA
Adder
0.640.544
923573AB1-173 E OP
Adder
4.8588235294117644.13
919692AA2-053 E OP
Adder
6.2482352941176475.311
944011AF1-069 C
50/50
20.76920.769
3152421Z1-086 GT2
50/50
16.64616.646
3152441Z1-086 ST
50/50
28.98428.984
3152411Z1-086 GT1
50/50
16.65116.651
963041AG1-153 C
50/50
8.8378.837
3151051BRUNSWICKS1
50/50
27.00627.006
3151041BRUNSWICKG3
50/50
12.99912.999
940431AE2-027 C
Adder
18.6823529411764715.88
961611AG1-000B C
Adder
23.2270588235294119.743
939192AE1-149 E
Adder
10.7658823529411769.151
939312AE1-162 E
Adder
2.13058823529411741.811
942002AE2-212 E
Adder
2.13058823529411741.811
942001AE2-212 C
Adder
3.19647058823529442.717
3150831SPRUNCA
Adder
13.36352941176470611.359
3150841SPRUNCB
Adder
13.36352941176470611.359
316375AC2-012 C
50/50
2.0552.055
926662AC1-147 E
Adder
2.02235294117647071.719
3151081ELIZAR1
50/50
4.8744.874
916192Z1-068 E
50/50
2.8712.871
916191Z1-068 C
50/50
0.0670.067
957492AF2-043 E
Adder
2.16705882352941171.842
941101AE2-104 C
Adder
5.1011764705882364.336
934065AD1-033 E
50/50
7.6627.662
316185AD1-033 C
50/50
1.8711.871
937226AE2-253 E
Adder
8.9129411764705877.576
944581AF1-123 C
50/50
69.72769.727
316294AC1-161 C
50/50
7.5867.586
940541AE2-040 C
50/50
4.3984.398
923852AB2-025 E
50/50
1.7791.779
940481AE2-033 C
50/50
24.72924.729
940482AE2-033 E
50/50
16.67116.671
934501AD1-074 C
Adder
50.5435294117647142.962
939412AE1-173 E
50/50
96.42796.427
924517AB2-100 E2
Adder
4.3447058823529413.693
961942AG1-037 E
Adder
0.50117647058823530.426
316141AB2-099 E
Adder
0.37647058823529410.32
961941AG1-037 C
Adder
0.7517647058823530.639
923263AB1-132 E OP
Adder
9.0588235294117647.7
316088AB2-174 E
Adder
9.6611764705882348.212
923994AB2-040_E
Adder
9.1117647058823537.745
941031AE2-094 C
50/50
63.56663.566
941032AE2-094 E
50/50
28.4728.47
3151021BRUNSWICKG1
50/50
12.99912.999
3151031BRUNSWICKG2
50/50
12.99912.999
957482AF2-042 E
Adder
53.94941176470588645.857
957481AF2-042 C
Adder
80.9247058823529468.786
934621AD1-088 C
Adder
14.11647058823529511.999
958502AF2-144 E
Adder
1.81.53
923862AB2-026 E
Adder
1.8317647058823531.557
316303AF2-085
50/50
6.5316.531
G-007PJM->LTFIMP_G-007
CMTX_NF
7.1157.115
SIGELTFEXP_SIGE->PJM
CLTF
0.490.49
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.0368.036
CBM South 2LTFEXP_CBM-S2->PJM
CBM
145.599145.599
CPLELTFEXP_CPLE->PJM
CLTF
16.84316.843
TVALTFEXP_TVA->PJM
CLTF
10.54210.542
O66PJM->LTFIMP_O-066
CMTX_NF
45.24145.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.46965.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.49440.494
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6697.669
LAGNLTFEXP_LAGN->PJM
CLTF
13.22813.228
NYPJM->LTFIMP_NY
CLTF
3.2313.231
LGEELTFEXP_LGEE->PJM
CLTF
2.6092.609
WECLTFEXP_WEC->PJM
CLTF
1.3461.346

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.63 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3595.09
MW Contribution:47.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316349AD2-085 C
Adder
2.3964705882352942.037
942341AE2-247 C
Adder
1.03882352941176470.883
958161AF2-110 C
Adder
0.96117647058823530.817
938531AE1-072 C
Adder
12.33529411764705810.485
939411AE1-173 C
80/20
78.11378.113
933981AD1-022 C
Adder
6.3599999999999995.406
966621AG1-532 C
80/20
1.0911.091
946281AF1-292 C
80/20
1.2041.204
926071AC1-086 C
Adder
15.98823529411764713.59
3137643SOCKMAN
Adder
0.54588235294117650.464
927021AC1-189 C
Adder
6.225.287
935171AD1-152 C
80/20
1.0991.099
316238AB2-078 C O1
80/20
0.2590.259
964241AG1-285 C
80/20
9.9749.974
316034AC1-036 C
80/20
0.1860.186
962561AG1-105 C
Adder
6.9729411764705885.927
3144293JTRSVLE
80/20
0.3290.329
3152261N ANNA2
80/20
103.963103.963
3151741LOISA C
80/20
3.3493.349
316044AC1-158 C1
80/20
18.51718.517
934861AD1-115 C
80/20
3.3063.306
939191AE1-149 C
Adder
7.2929411764705886.199
943461AF1-017 C
Adder
0.94000000000000010.799
316311AC2-079 C
Adder
3.99647058823529383.397
941591AE2-156 C
Adder
12.43294117647058910.568
944591AF1-124 C
Adder
32.1611764705882427.337
944601AF1-125 C
Adder
31.55411764705882826.821
938771AE1-103 C
Adder
2.10235294117647081.787
934521AD1-076 C
Adder
8.8564705882352937.528
934511AD1-075 C
Adder
6.0964705882352945.182
316233AE1-074 C
80/20
2.0672.067
960081AF2-299 C
80/20
1.4551.455
316087AB2-174 C
80/20
0.9080.908
944011AF1-069 C
80/20
12.12612.126
3152421Z1-086 GT2
80/20
9.699.69
3152441Z1-086 ST
80/20
16.87216.872
3152411Z1-086 GT1
80/20
9.6939.693
963041AG1-153 C
80/20
5.1375.137
3151051BRUNSWICKS1
80/20
15.69915.699
3151041BRUNSWICKG3
80/20
7.5577.557
316263AC1-034 C
Adder
4.9470588235294124.205
937481AD2-202 C
80/20
0.3090.309
316239AB2-077 C O1
80/20
0.2590.259
936261AD2-033 C
80/20
10.37510.375
316313AB2-026 C
80/20
0.3480.348
959311AF2-222 C
80/20
13.30313.303
964791AG1-342 C
Adder
2.77294117647058872.357
961791AG1-021 C
80/20
1.4371.437
3151751LOISA D
80/20
3.3493.349
3151731LOISA B
80/20
3.3493.349
316045AC1-158 C2
80/20
18.51718.517
316164AC1-076_C
80/20
1.0891.089
316170AC1-121 C
80/20
2.952.95
957871AF2-081 C
Adder
7.0094117647058835.958
933291AC2-141 C
Adder
21.0423529411764717.886
316315AB2-025 C
80/20
0.3250.325
316023AB2-100 C2
80/20
0.7450.745
940641AE2-051 C
80/20
15.75815.758
3152431Z1-086 GT3
80/20
9.699.69
316274AC1-208 C
Adder
6.785.763
3151311EDGECMA
Adder
11.569.826
934611AD1-087 C
80/20
1.0661.066
313527AB2-043 C
80/20
0.4090.409
316237AB2-079 C O1
80/20
0.2590.259
316131AB2-060 C
80/20
1.1781.178
316405AF2-144 C
80/20
0.2720.272
3138533PONTONDP
80/20
0.5320.532
316336AC2-165 C
80/20
8.8748.874
3152251N ANNA1
80/20
103.92103.92
3151721LOISA A
80/20
3.3313.331
316254AC1-120 C
80/20
8.5918.591
316257AC1-043 C
80/20
6.6126.612
942001AE2-212 C
Adder
1.40235294117647061.192
941101AE2-104 C
Adder
2.35411764705882342.001
944581AF1-123 C
Adder
32.0470588235294127.24
940541AE2-040 C
80/20
2.2982.298
940481AE2-033 C
80/20
12.91312.913
934501AD1-074 C
Adder
24.38588235294117720.728
316365AB2-100 C1
80/20
0.7450.745
961941AG1-037 C
Adder
0.37294117647058830.317
941031AE2-094 C
80/20
37.11337.113
3147043LAWRENC
80/20
0.240.24
3151021BRUNSWICKG1
80/20
7.5577.557
3151031BRUNSWICKG2
80/20
7.5577.557
934331AD1-057 C
Adder
2.6258823529411772.232
934321AD1-056 C
Adder
4.7070588235294134.001
961671AG1-007 C
Adder
0.69647058823529410.592
957481AF2-042 C
80/20
47.06247.062
934621AD1-088 C
80/20
8.2538.253
3151531CLOVER1
80/20
10.82910.829
3151541CLOVER2
80/20
10.72710.727
316258AE1-075 C
80/20
0.320.32
958211AF2-115 C
80/20
1.7961.796
946301AF1-294 C
80/20
2.9542.954
942461AE2-259 C
80/20
7.9867.986
316192AB2-158 C
80/20
4.3254.325
3151801S ANNAS2
80/20
1.6761.676
3151791S ANNAG2
80/20
3.2623.262
3151771S ANNAG1
80/20
3.2623.262
3151781S ANNAS1
80/20
1.6761.676
3151761LOISA E
80/20
6.8276.827
966001AG1-469 C
80/20
2.3822.382
208900BRIS G1
80/20
-2.405-2.405
208901BRIS G2
80/20
-2.846-2.846
316303AF2-085
80/20
3.8763.876
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2194.219
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.82173.821
CPLELTFEXP_CPLE->PJM
CLTF
8.8538.853
TVALTFEXP_TVA->PJM
CLTF
4.5224.522
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.20919.209
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.12316.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.6672.667
LAGNLTFEXP_LAGN->PJM
CLTF
5.7055.705
NYPJM->LTFIMP_NY
CLTF
2.292.29
LGEELTFEXP_LGEE->PJM
CLTF
0.8350.835
WECLTFEXP_WEC->PJM
CLTF
0.4130.413

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.86 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3570.05
MW Contribution:49.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316349AD2-085 C
Adder
2.5505882352941182.168
942341AE2-247 C
Adder
1.10588235294117650.94
958161AF2-110 C
Adder
1.02235294117647070.869
938531AE1-072 C
Adder
13.12352941176470511.155
939411AE1-173 C
80/20
82.26382.263
933981AD1-022 C
Adder
6.7447058823529415.733
966621AG1-532 C
80/20
1.1511.151
946281AF1-292 C
80/20
1.2711.271
926071AC1-086 C
Adder
16.8929411764705914.359
313506AB1-173 C OP
80/20
0.9150.915
3137643SOCKMAN
Adder
0.57647058823529410.49
927021AC1-189 C
Adder
6.5788235294117645.592
935171AD1-152 C
80/20
1.1531.153
316238AB2-078 C O1
80/20
0.2720.272
964241AG1-285 C
80/20
10.44910.449
316034AC1-036 C
80/20
0.1950.195
962561AG1-105 C
Adder
7.3152941176470596.218
3144293JTRSVLE
80/20
0.3440.344
3152261N ANNA2
80/20
106.999106.999
3151741LOISA C
80/20
3.0953.095
939191AE1-149 C
Adder
7.7752941176470596.609
944641AF1-129 C
Adder
63.6988235294117654.144
316240AF1-291 C
Adder
1.37882352941176461.172
943461AF1-017 C
Adder
1.00.85
316311AC2-079 C
Adder
4.2541176470588233.616
941591AE2-156 C
Adder
13.23882352941176611.253
944591AF1-124 C
Adder
34.2229.087
944601AF1-125 C
Adder
33.5741176470588328.538
938771AE1-103 C
Adder
2.2329411764705881.898
934521AD1-076 C
Adder
9.3952941176470587.986
934511AD1-075 C
Adder
6.46705882352941155.497
316233AE1-074 C
80/20
2.1822.182
960081AF2-299 C
80/20
1.5351.535
316087AB2-174 C
80/20
0.9580.958
944011AF1-069 C
80/20
12.71412.714
3152421Z1-086 GT2
80/20
10.16110.161
3152441Z1-086 ST
80/20
17.69217.692
3152411Z1-086 GT1
80/20
10.16410.164
963041AG1-153 C
80/20
5.3875.387
3151051BRUNSWICKS1
80/20
16.46316.463
3151041BRUNSWICKG3
80/20
7.9247.924
316263AC1-034 C
Adder
5.2270588235294114.443
937481AD2-202 C
80/20
0.3240.324
316239AB2-077 C O1
80/20
0.2720.272
936261AD2-033 C
80/20
10.85610.856
316313AB2-026 C
80/20
0.3630.363
959311AF2-222 C
80/20
13.90913.909
964791AG1-342 C
Adder
2.9105882352941182.474
961791AG1-021 C
80/20
1.51.5
3151751LOISA D
80/20
3.0953.095
3151731LOISA B
80/20
3.0953.095
3150651CHESTF6
Adder
11.5976470588235319.858
957871AF2-081 C
Adder
7.4588235294117656.34
933291AC2-141 C
Adder
22.41294117647058619.051
316315AB2-025 C
80/20
0.3440.344
316023AB2-100 C2
80/20
0.7870.787
940641AE2-051 C
80/20
16.55416.554
3152431Z1-086 GT3
80/20
10.16110.161
316274AC1-208 C
Adder
7.1635294117647066.089
3151311EDGECMA
Adder
12.21411764705882410.382
934611AD1-087 C
80/20
1.1171.117
313527AB2-043 C
80/20
0.4290.429
316237AB2-079 C O1
80/20
0.2720.272
316131AB2-060 C
80/20
1.2351.235
316405AF2-144 C
80/20
0.2830.283
3138533PONTONDP
80/20
0.5550.555
316336AC2-165 C
80/20
9.2269.226
3152251N ANNA1
80/20
106.954106.954
3151721LOISA A
80/20
3.0793.079
940431AE2-027 C
Adder
8.3129411764705887.066
961611AG1-000B C
Adder
10.3129411764705888.766
942001AE2-212 C
Adder
1.49882352941176471.274
3150831SPRUNCA
Adder
6.1623529411764715.238
3150841SPRUNCB
Adder
6.1623529411764715.238
941101AE2-104 C
Adder
2.50470588235294132.129
944581AF1-123 C
Adder
34.0988235294117728.984
940541AE2-040 C
80/20
2.4262.426
940481AE2-033 C
80/20
13.63113.631
934501AD1-074 C
Adder
25.86823529411764621.988
316365AB2-100 C1
80/20
0.7870.787
961941AG1-037 C
Adder
0.39411764705882360.335
316181AB2-040 GEN
80/20
1.0311.031
941031AE2-094 C
80/20
38.91138.911
3147043LAWRENC
80/20
0.2530.253
3151021BRUNSWICKG1
80/20
7.9247.924
3151031BRUNSWICKG2
80/20
7.9247.924
934331AD1-057 C
Adder
2.7741176470588242.358
934321AD1-056 C
Adder
4.9729411764705894.227
961671AG1-007 C
Adder
0.73647058823529410.626
957481AF2-042 C
80/20
49.31549.315
934621AD1-088 C
80/20
8.6418.641
3151531CLOVER1
80/20
11.34911.349
3151541CLOVER2
80/20
11.24311.243
316258AE1-075 C
80/20
0.3330.333
958211AF2-115 C
80/20
1.8751.875
946301AF1-294 C
80/20
3.0833.083
942461AE2-259 C
Adder
8.3117647058823547.065
316192AB2-158 C
80/20
4.2764.276
3151801S ANNAS2
80/20
1.5631.563
3151791S ANNAG2
80/20
3.0413.041
3151771S ANNAG1
80/20
3.0413.041
3151781S ANNAS1
80/20
1.5631.563
3151761LOISA E
80/20
6.316.31
966001AG1-469 C
80/20
1.9821.982
208900BRIS G1
80/20
-2.414-2.414
208901BRIS G2
80/20
-2.857-2.857
316303AF2-085
80/20
4.064.06
SIGELTFEXP_SIGE->PJM
CLTF
0.1860.186
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4574.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
78.26878.268
CPLELTFEXP_CPLE->PJM
CLTF
9.3529.352
TVALTFEXP_TVA->PJM
CLTF
4.8954.895
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.24822.248
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.65817.658
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.9882.988
LAGNLTFEXP_LAGN->PJM
CLTF
6.1746.174
NYPJM->LTFIMP_NY
CLTF
2.2912.291
LGEELTFEXP_LGEE->PJM
CLTF
0.9480.948
WECLTFEXP_WEC->PJM
CLTF
0.4740.474

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.14 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4339.53
MW Contribution:81.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
939191AE1-149 C
Adder
7.7200000000000016.562
936666AD2-085 E
Adder
4.1329411764705883.513
942342AE2-247 E
Adder
1.5164705882352941.289
943461AF1-017 C
Adder
0.99294117647058820.844
3143316POE
Adder
1.04235294117647070.886
932596AC2-079 E
Adder
6.8929411764705895.859
316311AC2-079 C
Adder
4.2247058823529413.591
941591AE2-156 C
Adder
13.14823529411764711.176
944591AF1-124 C
Adder
33.9870588235294128.889
944601AF1-125 C
Adder
33.3447058823529428.343
919152AA1-139 E1
Adder
3.02941176470588272.575
939192AE1-149 E
Adder
5.1470588235294124.375
939312AE1-162 E
Adder
0.97647058823529410.83
942002AE2-212 E
Adder
0.99176470588235290.843
942001AE2-212 C
Adder
1.48705882352941181.264
3150831SPRUNCA
Adder
6.117647058823535.2
3150841SPRUNCB
Adder
6.117647058823535.2
926662AC1-147 E
Adder
0.97176470588235290.826
916192Z1-068 E
Adder
1.38588235294117631.178
957492AF2-043 E
Adder
1.05294117647058830.895
941101AE2-104 C
Adder
2.48705882352941152.114
934065AD1-033 E
Adder
3.70941176470588243.153
937226AE2-253 E
Adder
4.3282352941176473.679
934576AD1-082 E
Adder
3.19882352941176462.719
316084AB2-161 E
Adder
4.0141176470588233.412
3145256KINGFORK
Adder
0.72352941176470590.615
925522AC1-027 E
Adder
0.89764705882352950.763
943612AF1-032 E
Adder
0.68470588235294120.582
941102AE2-104 E
Adder
3.9541176470588243.361
3145506HICKORY
Adder
1.61411764705882371.372
944602AF1-125 E
Adder
76.3341176470588364.884
957872AF2-081 E
Adder
3.17411764705882372.698
957871AF2-081 C
Adder
7.4070588235294126.296
933292AC2-141 E
Adder
9.502352941176478.077
933291AC2-141 C
Adder
22.2618.921
926755AC1-161 E
Adder
9.502352941176478.077
940492AE2-034 E
Adder
2.3364705882352941.986
3145946PLYMOUTH TP
Adder
0.245882352941176470.209
934522AD1-076 E
Adder
4.7541176470588244.041
938552AE1-074 E
Adder
1.09294117647058830.929
933982AD1-022 E
Adder
3.6447058823529413.098
943172AE2-346 E
Adder
0.46941176470588240.399
940641AE2-051 C
50/50
16.47216.472
918492AA1-063AE OP
Adder
3.22705882352941182.743
925122AB2-169 E
Adder
4.4105882352941183.749
917332KELFORD E
Adder
1.281.088
946282AF1-292 E
Adder
0.84117647058823530.715
944012AF1-069 E
50/50
4.9154.915
932632AC2-084 E
Adder
2.53411764705882362.154
926214AC1-099 E
Adder
0.94705882352941180.805
316274AC1-208 C
Adder
7.1094117647058826.043
927146AC1-208 E
Adder
3.1564705882352942.683
917512Z2-088 E OP1
Adder
3.8047058823529413.234
917342Z2-044 E
Adder
0.46823529411764710.398
3151311EDGECMA
Adder
12.11411764705882510.297
934622AD1-088 E
Adder
4.1364705882352943.516
937482AD2-202 E
Adder
0.94117647058823540.8
934612AD1-087 E
Adder
3.2152941176470592.733
924162AB2-060 E OP
Adder
3.54470588235294143.013
964242AG1-285 E
Adder
6.9188235294117655.881
938562AE1-075 E
Adder
1.00.85
964792AG1-342 E
Adder
1.92588235294117661.637
961792AG1-021 E
Adder
1.26941176470588221.079
3138533PONTONDP
Adder
0.55176470588235290.469
316336AC2-165 C
Adder
9.177647058823537.801
927255AC1-221 E
Adder
2.9588235294117652.515
932763AC2-100 E
Adder
2.00588235294117641.705
3152251N ANNA1
50/50
106.841106.841
3151721LOISA A
50/50
3.093.09
944581AF1-123 C
Adder
33.8670588235294128.787
940541AE2-040 C
Adder
2.4117647058823532.05
923852AB2-025 E
Adder
0.97529411764705880.829
940481AE2-033 C
Adder
13.54823529411764811.516
940482AE2-033 E
Adder
9.1341176470588247.764
934501AD1-074 C
Adder
25.6821.828
939412AE1-173 E
Adder
54.5505882352941246.368
924517AB2-100 E2
Adder
2.36470588235294082.01
961942AG1-037 E
Adder
0.26117647058823530.222
316141AB2-099 E
Adder
0.195294117647058840.166
961941AG1-037 C
Adder
0.391764705882352960.333
923263AB1-132 E OP
Adder
4.8811764705882354.149
316088AB2-174 E
Adder
5.2858823529411774.493
923994AB2-040_E
Adder
4.9741176470588234.228
941031AE2-094 C
50/50
38.72138.721
941032AE2-094 E
50/50
17.34217.342
934331AD1-057 C
Adder
2.75294117647058822.34
934322AD1-056 E
Adder
2.6764705882352942.275
934332AD1-057 E
Adder
1.43411764705882371.219
934321AD1-056 C
Adder
4.9352941176470594.195
927022AC1-189 E
Adder
3.25058823529411762.763
961672AG1-007 E
Adder
0.414117647058823530.352
961671AG1-007 C
Adder
0.73058823529411760.621
957482AF2-042 E
Adder
32.6894117647058927.786
957481AF2-042 C
Adder
49.0341176470588341.679
925595AC1-034 E
Adder
3.91058823529411773.324
934621AD1-088 C
Adder
8.5905882352941177.302
935172AD1-152 E
Adder
4.7270588235294114.018
924322AB2-079 E O1
Adder
1.10588235294117650.94
924312AB2-078 E O1
Adder
1.10588235294117650.94
936262AD2-033 E
Adder
7.1882352941176476.11
958502AF2-144 E
Adder
1.15294117647058810.98
923862AB2-026 E
Adder
1.17294117647058820.997
925612AC1-036 E
Adder
0.7117647058823530.605
926274AC1-105 E
Adder
2.1788235294117651.852
958211AF2-115 C
Adder
1.86235294117647051.583
946301AF1-294 C
Adder
3.06235294117647072.603
946302AF1-294 E
Adder
2.59294117647058852.204
943902AF1-058 E
Adder
1.04352941176470580.887
942461AE2-259 C
Adder
8.257647058823537.019
316192AB2-158 C
50/50
4.2784.278
3151801S ANNAS2
50/50
1.5681.568
3151791S ANNAG2
50/50
3.0513.051
3151771S ANNAG1
50/50
3.0513.051
3151781S ANNAS1
50/50
1.5681.568
3151761LOISA E
50/50
6.3326.332
966001AG1-469 C
50/50
2.0062.006
926740AC1-158 E2
50/50
51.18251.182
208900BRIS G1
50/50
-2.489-2.489
208901BRIS G2
50/50
-2.946-2.946
938532AE1-072 E
Adder
6.7941176470588245.775
3146326AYDLETT TAP
Adder
1.00588235294117640.855
917122Z2-027 E
Adder
1.00.85
901082W1-029 E
Adder
23.76705882352941420.202
938771AE1-103 C
Adder
2.21764705882352951.885
3145413WATKINS
Adder
0.52941176470588240.45
920692AA2-178 E
Adder
3.1141176470588232.647
934521AD1-076 C
Adder
9.3258823529411777.927
934511AD1-075 C
Adder
6.425.457
316233AE1-074 C
Adder
2.17058823529411751.845
920042AA2-088 E OP
Adder
8.226.987
960081AF2-299 C
Adder
1.52470588235294141.296
966622AG1-532 E
Adder
0.76235294117647070.648
926072AC1-086 E
Adder
7.6341176470588236.489
3145723EMPORIA
Adder
0.350588235294117640.298
923573AB1-173 E OP
Adder
2.6529411764705882.255
919692AA2-053 E OP
Adder
3.36117647058823542.857
944011AF1-069 C
50/50
12.65212.652
926206AC1-098 E
Adder
2.86705882352941142.437
963041AG1-153 C
Adder
5.3588235294117644.555
925785AC1-054 E
Adder
2.79764705882352962.378
316263AC1-034 C
Adder
5.1835294117647064.406
922923AB1-081 E OP
Adder
2.9105882352941182.474
936261AD2-033 C
Adder
10.782352941176479.165
962562AG1-105 E
Adder
4.842352941176474.116
959311AF2-222 C
Adder
13.8152941176470611.743
964791AG1-342 C
Adder
2.88941176470588262.456
961791AG1-021 C
Adder
1.48941176470588241.266
3147133PAMPLIN
Adder
0.82352941176470580.7
942462AE2-259 E
Adder
5.5047058823529414.679
927264AC1-222 E
Adder
3.20470588235294152.724
924032AB2-045 E
Adder
1.08588235294117650.923
3151751LOISA D
50/50
3.1063.106
3151731LOISA B
50/50
3.1063.106
966002AG1-469 E
50/50
1.0031.003
316045AC1-158 C2
50/50
19.56819.568
926739AC1-158 E1
50/50
51.18251.182
935112AD1-144 E
Adder
0.67176470588235290.571
943462AF1-017 E
Adder
1.621.377
316349AD2-085 C
Adder
2.53294117647058852.153
942341AE2-247 C
Adder
1.09764705882352940.933
932046AC2-012 E
Adder
9.6164705882352938.174
958161AF2-110 C
Adder
1.0152941176470590.863
958162AF2-110 E
Adder
1.61411764705882371.372
944582AF1-123 E
Adder
77.5517647058823565.919
944592AF1-124 E
Adder
77.8317647058823566.157
919153AA1-139 E2
Adder
3.02941176470588272.575
938531AE1-072 C
Adder
13.03294117647058811.078
923832AB2-022 E
Adder
0.92235294117647060.784
913392Y1-086 E
Adder
1.63411764705882371.389
938772AE1-103 E
Adder
3.0611764705882352.602
916042Z1-036 E
Adder
21.48117647058823518.259
3145393UNCAMP
Adder
4.622352941176473.929
934502AD1-074 E
Adder
13.07176470588235311.111
934512AD1-075 E
Adder
3.26823529411764732.778
939411AE1-173 C
Adder
81.8247058823529469.551
933981AD1-022 C
Adder
6.6952941176470595.691
900672V4-068 E
Adder
0.276470588235294130.235
918512AA1-065 E OP
Adder
4.2588235294117653.62
924516AB2-100 E1
Adder
2.36470588235294082.01
940642AE2-051 E
50/50
10.98110.981
966621AG1-532 C
Adder
1.1435294117647060.972
960082AF2-299 E
Adder
1.01647058823529420.864
946281AF1-292 C
Adder
1.26235294117647071.073
926071AC1-086 C
Adder
16.77411764705882314.258
3137643SOCKMAN
Adder
0.57294117647058830.487
963042AG1-153 E
Adder
8.0388235294117656.833
918532AA1-067 E
Adder
0.55176470588235290.469
927021AC1-189 C
Adder
6.5247058823529425.546
919710AA2-057 E
Adder
3.1117647058823532.645
924152AB2-059 E OP
Adder
4.122352941176473.504
924022AB2-043 E O1
Adder
4.2929411764705883.649
924302AB2-077 E O1
Adder
1.10588235294117650.94
964241AG1-285 C
Adder
10.3776470588235298.821
3147223TWITTYS
Adder
0.78941176470588240.671
962561AG1-105 C
Adder
7.2635294117647076.174
959312AF2-222 E
Adder
9.2564705882352957.868
958212AF2-115 E
Adder
1.58588235294117651.348
933502AC2-165 E
Adder
6.9070588235294135.871
3152261N ANNA2
50/50
106.886106.886
925022AB2-158 E
50/50
11.37311.373
3151741LOISA C
50/50
3.1063.106
316044AC1-158 C1
50/50
19.56819.568
316303AF2-085
50/50
4.0434.043
G-007PJM->LTFIMP_G-007
CMTX_NF
5.0575.057
SIGELTFEXP_SIGE->PJM
CLTF
0.1730.173
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4084.408
CBM South 2LTFEXP_CBM-S2->PJM
CBM
77.11777.117
CPLELTFEXP_CPLE->PJM
CLTF
9.2519.251
TVALTFEXP_TVA->PJM
CLTF
4.7224.722
O66PJM->LTFIMP_O-066
CMTX_NF
32.20632.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.05120.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.83616.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7842.784
LAGNLTFEXP_LAGN->PJM
CLTF
5.9595.959
NYPJM->LTFIMP_NY
CLTF
2.3732.373
LGEELTFEXP_LGEE->PJM
CLTF
0.8720.872
WECLTFEXP_WEC->PJM
CLTF
0.4310.431

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.71 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3758.56
MW Contribution:52.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150731STONECA
Adder
5.4352941176470594.62
935161AD1-151 C
Adder
13.03882352941176511.083
316381AD1-082 C
80/20
1.1161.116
316083AB2-161 C
80/20
0.4890.489
316349AD2-085 C
80/20
3.0713.071
942341AE2-247 C
80/20
1.3311.331
3150991CHESPKB
80/20
0.6430.643
3151091ELIZAR2
80/20
2.8012.801
316246AF1-032 C
80/20
0.2540.254
958161AF2-110 C
80/20
1.2251.225
316388AE2-253 GEN
80/20
1.7531.753
938531AE1-072 C
80/20
15.7315.73
316320Y1-086 C
80/20
0.1960.196
939411AE1-173 C
80/20
90.4790.47
933981AD1-022 C
Adder
7.84941176470588256.672
966621AG1-532 C
80/20
1.2891.289
946281AF1-292 C
80/20
1.4231.423
926071AC1-086 C
Adder
19.07647058823529616.215
313506AB1-173 C OP
80/20
1.0281.028
3137643SOCKMAN
Adder
0.64823529411764710.551
927021AC1-189 C
Adder
7.4435294117647066.327
935171AD1-152 C
80/20
1.2331.233
964241AG1-285 C
Adder
11.3035294117647079.608
962561AG1-105 C
Adder
7.9117647058823526.725
3152261N ANNA2
80/20
92.75992.759
3151741LOISA C
80/20
2.3872.387
3150601CHESTF5
Adder
45.29058823529411638.497
939191AE1-149 C
80/20
9.4869.486
944641AF1-129 C
Adder
83.2882352941176570.795
316240AF1-291 C
Adder
1.78117647058823541.514
943461AF1-017 C
80/20
1.2041.204
316311AC2-079 C
80/20
5.125.12
3150981CHESPKA
80/20
0.3880.388
316036AC1-147 C
80/20
0.3280.328
941591AE2-156 C
80/20
15.98415.984
3151101ELIZAR3
80/20
2.8872.887
316305AF2-043 C
80/20
0.3110.311
944591AF1-124 C
80/20
41.04941.049
944601AF1-125 C
80/20
40.27340.273
316321Z2-027 C
80/20
0.3250.325
3156056W1-029WIND
80/20
0.6930.693
938771AE1-103 C
80/20
2.6332.633
934521AD1-076 C
Adder
10.9623529411764719.318
934511AD1-075 C
Adder
7.54588235294117656.414
316233AE1-074 C
80/20
2.4792.479
960081AF2-299 C
80/20
1.7191.719
316087AB2-174 C
80/20
1.0751.075
944011AF1-069 C
80/20
13.43113.431
3152421Z1-086 GT2
80/20
10.7510.75
3152441Z1-086 ST
80/20
18.71718.717
3152411Z1-086 GT1
80/20
10.75310.753
963041AG1-153 C
80/20
5.7035.703
3151051BRUNSWICKS1
80/20
17.42917.429
3151041BRUNSWICKG3
80/20
8.3898.389
316263AC1-034 C
Adder
5.8505882352941184.973
937481AD2-202 C
80/20
0.3460.346
936261AD2-033 C
Adder
11.7211764705882359.963
316313AB2-026 C
80/20
0.3850.385
959311AF2-222 C
Adder
14.9976470588235312.748
964791AG1-342 C
Adder
3.14588235294117662.674
961791AG1-021 C
Adder
1.61176470588235321.37
3151751LOISA D
80/20
2.3872.387
3151731LOISA B
80/20
2.3872.387
940431AE2-027 C
Adder
10.6976470588235299.093
961611AG1-000B C
Adder
13.19882352941176511.219
942001AE2-212 C
Adder
1.8635294117647061.584
3150831SPRUNCA
Adder
7.7905882352941186.622
3150841SPRUNCB
Adder
7.7905882352941186.622
316072AD1-144 C
80/20
0.2460.246
316375AC2-012 C
80/20
1.2021.202
3151081ELIZAR1
80/20
2.8512.851
916191Z1-068 C
80/20
0.0390.039
941101AE2-104 C
80/20
3.0013.001
316185AD1-033 C
80/20
1.0971.097
944581AF1-123 C
80/20
40.90340.903
316294AC1-161 C
80/20
4.4154.415
940541AE2-040 C
80/20
2.7232.723
940481AE2-033 C
80/20
15.30215.302
934501AD1-074 C
Adder
30.18352941176470625.656
316365AB2-100 C1
80/20
0.8850.885
961941AG1-037 C
Adder
0.454117647058823570.386
316181AB2-040 GEN
80/20
1.1581.158
941031AE2-094 C
80/20
41.10641.106
3147043LAWRENC
80/20
0.2810.281
944631AF1-128 C
Adder
28.33882352941176624.088
3150921YORKTN3
Adder
92.4352941176470578.57
3150651CHESTF6
Adder
15.16470588235294212.89
3150851SPRUNCC
80/20
0.140.14
3150861SPRUNCD
80/20
0.140.14
316316AC1-027 C
80/20
0.2820.282
957871AF2-081 C
80/20
8.9458.945
316017AA1-139 ULT1
80/20
0.9650.965
316018AA1-139 ULT2
80/20
0.9650.965
933291AC2-141 C
80/20
27.11427.114
313526AB2-022 C
80/20
0.3360.336
316315AB2-025 C
80/20
0.3860.386
316023AB2-100 C2
80/20
0.8850.885
940641AE2-051 C
80/20
17.817.8
3152431Z1-086 GT3
80/20
10.7510.75
316274AC1-208 C
Adder
8.077647058823536.866
3151311EDGECMA
Adder
13.67647058823529511.625
934611AD1-087 C
80/20
1.1911.191
316405AF2-144 C
80/20
0.30.3
3138533PONTONDP
Adder
0.59764705882352940.508
316336AC2-165 C
80/20
9.7879.787
3152251N ANNA1
80/20
92.7292.72
3151721LOISA A
80/20
2.3742.374
3151021BRUNSWICKG1
80/20
8.3898.389
3151031BRUNSWICKG2
80/20
8.3898.389
934331AD1-057 C
Adder
3.11764705882352942.65
934321AD1-056 C
Adder
5.5882352941176484.75
961671AG1-007 C
Adder
0.82941176470588230.705
957481AF2-042 C
80/20
52.44752.447
934621AD1-088 C
80/20
9.29.2
3151531CLOVER1
80/20
12.09912.099
3151541CLOVER2
80/20
11.98511.985
316258AE1-075 C
80/20
0.3530.353
958211AF2-115 C
Adder
2.0152941176470591.713
946301AF1-294 C
Adder
3.3141176470588242.817
942461AE2-259 C
Adder
8.8929411764705887.559
316192AB2-158 C
80/20
3.5593.559
3151801S ANNAS2
80/20
1.2181.218
3151791S ANNAG2
80/20
2.372.37
3151771S ANNAG1
80/20
2.372.37
3151781S ANNAS1
80/20
1.2181.218
3151761LOISA E
80/20
4.8664.866
966001AG1-469 C
Adder
1.43764705882352951.222
208900BRIS G1
80/20
-2.56-2.56
208901BRIS G2
80/20
-3.03-3.03
316303AF2-085
80/20
4.3034.303
SIGELTFEXP_SIGE->PJM
CLTF
0.2110.211
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.8954.895
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.42786.427
CPLELTFEXP_CPLE->PJM
CLTF
10.2710.27
TVALTFEXP_TVA->PJM
CLTF
5.5015.501
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.18225.182
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.8619.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.3753.375
LAGNLTFEXP_LAGN->PJM
CLTF
6.9186.918
NYPJM->LTFIMP_NY
CLTF
2.4542.454
LGEELTFEXP_LGEE->PJM
CLTF
1.0841.084
WECLTFEXP_WEC->PJM
CLTF
0.5370.537

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.93 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3669.13
MW Contribution:54.65
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966661AG1-536 C
Adder
5.6341176470588234.789
316169AC1-164 GEN
Adder
43.66588235294117537.116
3150771HOPHCF1
80/20
2.7332.733
3150731STONECA
80/20
7.7657.765
935161AD1-151 C
Adder
18.16235294117647215.438
3142366NRTHEST
80/20
0.2040.204
316349AD2-085 C
Adder
3.87058823529411773.29
942341AE2-247 C
Adder
1.67764705882352931.426
3150991CHESPKB
80/20
0.8130.813
3151091ELIZAR2
80/20
3.5383.538
958161AF2-110 C
Adder
1.53294117647058831.303
938531AE1-072 C
Adder
19.70000000000000316.745
939411AE1-173 C
80/20
99.71499.714
933981AD1-022 C
Adder
9.4470588235294128.03
966621AG1-532 C
Adder
1.46470588235294131.245
946281AF1-292 C
Adder
1.61647058823529431.374
926071AC1-086 C
Adder
21.9611764705882418.667
3137643SOCKMAN
Adder
0.74235294117647070.631
927021AC1-189 C
Adder
8.6023529411764727.312
964241AG1-285 C
Adder
12.1610.336
962561AG1-105 C
Adder
8.5058823529411767.23
3152261N ANNA2
80/20
56.72156.721
934861AD1-115 C
Adder
-3.06-2.601
939261AE1-157 C
Adder
14.10235294117647211.987
958261AF2-120 C
Adder
6.5505882352941175.568
940551AE2-041 C
Adder
7.6152941176470596.473
3150601CHESTF5
Adder
70.4105882352941159.849
3143096IRON208
80/20
0.4940.494
3150781HOPHCF2
80/20
2.7332.733
3150761HOPPOLC
80/20
1.7191.719
939191AE1-149 C
80/20
12.15312.153
944641AF1-129 C
80/20
115.84115.84
316240AF1-291 C
80/20
2.4442.444
943461AF1-017 C
Adder
1.51764705882352961.29
316311AC2-079 C
Adder
6.4458823529411775.479
941591AE2-156 C
80/20
20.20920.209
3151101ELIZAR3
80/20
3.6473.647
944591AF1-124 C
80/20
51.4651.46
944601AF1-125 C
80/20
50.48850.488
938771AE1-103 C
Adder
3.22705882352941182.743
934521AD1-076 C
Adder
13.2411.254
934511AD1-075 C
Adder
9.1141176470588237.747
316233AE1-074 C
80/20
2.8742.874
960081AF2-299 C
Adder
1.95294117647058821.66
944011AF1-069 C
80/20
13.80413.804
963041AG1-153 C
Adder
5.8858823529411765.003
316263AC1-034 C
Adder
6.6529411764705895.655
936261AD2-033 C
Adder
12.57294117647058810.687
959311AF2-222 C
Adder
16.0552941176470613.647
964791AG1-342 C
Adder
3.38000000000000032.873
961791AG1-021 C
Adder
1.71764705882352931.46
957601AF2-054 C
Adder
2.26000000000000021.921
966881AG1-559 C
Adder
2.45176470588235332.084
936591AD2-074 C
Adder
5.8552941176470594.977
961951AG1-038 C
Adder
3.3858823529411772.878
943471AF1-018 C
Adder
7.6152941176470596.473
944631AF1-128 C
Adder
44.0564705882352937.448
3150921YORKTN3
Adder
133.0105882352941113.059
3150791HOPHCF3
80/20
2.7332.733
3150651CHESTF6
80/20
21.09121.091
3150851SPRUNCC
80/20
0.1870.187
3150861SPRUNCD
80/20
0.1870.187
3152331SURRY 2
80/20
27.86527.865
957871AF2-081 C
Adder
11.2117647058823529.53
933291AC2-141 C
80/20
34.37234.372
940641AE2-051 C
80/20
18.8818.88
316274AC1-208 C
Adder
9.2835294117647067.891
3151311EDGECMA
Adder
15.55647058823529613.223
3138533PONTONDP
Adder
0.63647058823529420.541
316336AC2-165 C
Adder
10.1788235294117648.652
3152251N ANNA1
80/20
56.69756.697
316254AC1-120 C
Adder
-6.376470588235295-5.42
316257AC1-043 C
Adder
-6.121176470588236-5.203
963611AG1-210 C
Adder
0.68235294117647060.58
962861AG1-135 C
Adder
6.3647058823529425.41
943741AF1-042 C
Adder
3.06352941176470632.604
940431AE2-027 C
80/20
14.61614.616
3150801HOPHCF4
80/20
4.1494.149
961611AG1-000B C
Adder
17.92352941176470415.235
942001AE2-212 C
80/20
2.4472.447
3150831SPRUNCA
80/20
10.42510.425
3150841SPRUNCB
80/20
10.42510.425
316375AC2-012 C
80/20
1.521.52
3151081ELIZAR1
80/20
3.6013.601
941101AE2-104 C
Adder
3.75764705882352963.194
944581AF1-123 C
80/20
51.27751.277
316294AC1-161 C
80/20
5.5975.597
940541AE2-040 C
Adder
3.10117647058823562.636
940481AE2-033 C
Adder
17.43882352941176714.823
934501AD1-074 C
Adder
36.4552941176470630.987
961941AG1-037 C
Adder
0.53764705882352950.457
941031AE2-094 C
80/20
42.24742.247
934331AD1-057 C
Adder
3.5635294117647063.029
934321AD1-056 C
Adder
6.3870588235294125.429
961671AG1-007 C
Adder
0.95176470588235310.809
957481AF2-042 C
Adder
54.6470588235294146.45
927041AC1-191 C
Adder
10.2870588235294128.744
966871AG1-558 C
Adder
2.56235294117647072.178
934621AD1-088 C
Adder
9.6105882352941188.169
958211AF2-115 C
Adder
2.14705882352941171.825
946301AF1-294 C
Adder
3.5305882352941183.001
942461AE2-259 C
Adder
9.4035294117647077.993
964211AG1-282 C
Adder
2.07882352941176451.767
316303AF2-085
80/20
4.4474.447
SIGELTFEXP_SIGE->PJM
CLTF
0.2560.256
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.4135.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69496.694
CPLELTFEXP_CPLE->PJM
CLTF
11.35211.352
TVALTFEXP_TVA->PJM
CLTF
6.4156.415
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.72830.728
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.33523.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.0414.041
LAGNLTFEXP_LAGN->PJM
CLTF
8.0268.026
NYPJM->LTFIMP_NY
CLTF
2.72.7
LGEELTFEXP_LGEE->PJM
CLTF
1.331.33
WECLTFEXP_WEC->PJM
CLTF
0.6540.654

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.88 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4408.08
MW Contribution:90.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935162AD1-151 E
Adder
4.4752941176470593.804
927226AC1-216 E
Adder
6.6694117647058825.669
924814AB2-134 E
Adder
10.9235294117647069.285
939191AE1-149 C
Adder
10.0011764705882348.501
944641AF1-129 C
Adder
88.4505882352941375.183
316240AF1-291 C
Adder
1.88941176470588261.606
936666AD2-085 E
Adder
5.2764705882352954.485
942342AE2-247 E
Adder
1.93529411764705881.645
943461AF1-017 C
Adder
1.26823529411764711.078
3143316POE
Adder
1.30941176470588231.113
932596AC2-079 E
Adder
8.7952941176470587.476
316311AC2-079 C
Adder
5.3905882352941184.582
941591AE2-156 C
Adder
16.83647058823529414.311
944591AF1-124 C
Adder
43.2058823529411836.725
944601AF1-125 C
Adder
42.3894117647058836.031
919152AA1-139 E1
Adder
3.8505882352941183.273
938532AE1-072 E
Adder
8.6305882352941187.336
3146326AYDLETT TAP
Adder
1.27764705882352961.086
917122Z2-027 E
Adder
1.26588235294117671.076
901082W1-029 E
Adder
30.02588235294117425.522
938771AE1-103 C
Adder
2.7670588235294122.352
3145413WATKINS
Adder
0.65411764705882360.556
920692AA2-178 E
Adder
3.86941176470588263.289
934521AD1-076 C
Adder
11.5105882352941199.784
934511AD1-075 C
Adder
7.9235294117647066.735
316233AE1-074 C
50/50
2.5912.591
920042AA2-088 E OP
Adder
10.0447058823529418.538
960081AF2-299 C
Adder
1.7964705882352941.527
966622AG1-532 E
Adder
0.89882352941176480.764
926072AC1-086 E
Adder
9.0847058823529427.722
3145723EMPORIA
Adder
0.414117647058823530.352
923573AB1-173 E OP
Adder
3.1364705882352942.666
919692AA2-053 E OP
Adder
4.00705882352941253.406
944011AF1-069 C
50/50
13.92113.921
3152421Z1-086 GT2
50/50
11.14611.146
3152441Z1-086 ST
50/50
19.40819.408
3152411Z1-086 GT1
50/50
11.14911.149
963041AG1-153 C
50/50
5.9155.915
3151051BRUNSWICKS1
50/50
18.07518.075
3151041BRUNSWICKG3
50/50
8.78.7
925785AC1-054 E
Adder
3.24941176470588242.762
936261AD2-033 C
Adder
12.2210.387
959311AF2-222 C
Adder
15.63529411764705813.29
961791AG1-021 C
Adder
1.68117647058823551.429
3147133PAMPLIN
Adder
0.92823529411764720.789
942462AE2-259 E
Adder
6.1800000000000015.253
3151731LOISA B
50/50
2.4192.419
966002AG1-469 E
Adder
0.73058823529411760.621
940431AE2-027 C
Adder
11.3411764705882369.64
961611AG1-000B C
Adder
13.98823529411764911.89
939192AE1-149 E
Adder
6.6670588235294125.667
939312AE1-162 E
Adder
1.29647058823529431.102
942002AE2-212 E
Adder
1.31294117647058851.116
942001AE2-212 C
Adder
1.96941176470588241.674
3150831SPRUNCA
Adder
8.2435294117647067.007
3150841SPRUNCB
Adder
8.2435294117647067.007
926662AC1-147 E
Adder
1.24470588235294131.058
916192Z1-068 E
Adder
1.77058823529411761.505
957492AF2-043 E
Adder
1.341.139
941101AE2-104 C
Adder
3.1588235294117652.685
934065AD1-033 E
Adder
4.7282352941176474.019
937226AE2-253 E
Adder
5.5047058823529414.679
944581AF1-123 C
Adder
43.0529411764705936.595
940541AE2-040 C
Adder
2.84470588235294162.418
923852AB2-025 E
Adder
1.15058823529411770.978
940481AE2-033 C
Adder
15.98588235294117513.588
940482AE2-033 E
Adder
10.777647058823539.161
934501AD1-074 C
Adder
31.6952941176470626.941
939412AE1-173 E
50/50
62.82462.824
924517AB2-100 E2
Adder
2.82.38
961942AG1-037 E
Adder
0.317647058823529450.27
316141AB2-099 E
Adder
0.237647058823529430.202
961941AG1-037 C
Adder
0.476470588235294150.405
923263AB1-132 E OP
Adder
5.80941176470588254.938
316088AB2-174 E
Adder
6.242352941176475.306
923994AB2-040_E
Adder
5.8811764705882354.999
941031AE2-094 C
50/50
42.60742.607
941032AE2-094 E
50/50
19.08319.083
3151021BRUNSWICKG1
50/50
8.78.7
3151031BRUNSWICKG2
50/50
8.78.7
957482AF2-042 E
Adder
36.31529411764705630.868
957481AF2-042 C
Adder
54.4729411764705946.302
934621AD1-088 C
Adder
9.5599999999999998.126
935172AD1-152 E
Adder
5.2941176470588234.5
924322AB2-079 E O1
Adder
1.25764705882352931.069
924312AB2-078 E O1
Adder
1.25764705882352931.069
936262AD2-033 E
Adder
8.1458823529411776.924
958502AF2-144 E
Adder
1.2764705882352941.085
923862AB2-026 E
Adder
1.31.105
925612AC1-036 E
Adder
0.80588235294117660.685
958211AF2-115 C
Adder
2.1011764705882351.786
946301AF1-294 C
Adder
3.45529411764705862.937
946302AF1-294 E
Adder
2.9258823529411772.487
942461AE2-259 C
Adder
9.2705882352941187.88
316192AB2-158 C
50/50
3.5873.587
3151801S ANNAS2
50/50
1.2331.233
3151791S ANNAG2
50/50
2.42.4
3151771S ANNAG1
50/50
2.42.4
3151781S ANNAS1
50/50
1.2331.233
3151761LOISA E
50/50
4.9314.931
966001AG1-469 C
Adder
1.46235294117647091.243
208900BRIS G1
50/50
-2.742-2.742
208901BRIS G2
50/50
-3.245-3.245
3150651CHESTF6
Adder
16.10470588235294213.689
946262AF1-291 E
Adder
1.261.071
934576AD1-082 E
Adder
4.1188235294117653.501
316084AB2-161 E
Adder
5.1694117647058834.394
3145256KINGFORK
Adder
0.93882352941176480.798
925522AC1-027 E
Adder
1.14588235294117660.974
943612AF1-032 E
Adder
0.87058823529411770.74
941102AE2-104 E
Adder
5.0223529411764714.269
3145506HICKORY
Adder
2.05411764705882361.746
944602AF1-125 E
Adder
97.0388235294117782.483
957872AF2-081 E
Adder
4.0352941176470593.43
957871AF2-081 C
Adder
9.4164705882352948.004
933292AC2-141 E
Adder
12.19411764705882510.365
933291AC2-141 C
Adder
28.56588235294117724.281
926755AC1-161 E
Adder
12.19411764705882510.365
940492AE2-034 E
Adder
2.90235294117647062.467
3145946PLYMOUTH TP
Adder
0.30352941176470590.258
934522AD1-076 E
Adder
5.8670588235294124.987
938552AE1-074 E
50/50
1.3051.305
933982AD1-022 E
Adder
4.4858823529411773.813
943172AE2-346 E
Adder
0.5717647058823530.486
940641AE2-051 C
50/50
18.48718.487
918492AA1-063AE OP
Adder
3.87294117647058833.292
917332KELFORD E
Adder
1.54588235294117651.314
946282AF1-292 E
Adder
0.99176470588235290.843
944012AF1-069 E
50/50
5.4085.408
3152431Z1-086 GT3
50/50
11.14611.146
934622AD1-088 E
Adder
4.6035294117647063.913
937482AD2-202 E
Adder
1.04941176470588250.892
934612AD1-087 E
Adder
3.5835294117647063.046
924162AB2-060 E OP
Adder
4.0294117647058823.425
964242AG1-285 E
Adder
7.8564705882352946.678
938562AE1-075 E
Adder
1.1082352941176470.942
961792AG1-021 E
Adder
1.4317647058823531.217
3138533PONTONDP
Adder
0.62235294117647070.529
316336AC2-165 C
Adder
10.1788235294117648.652
3152251N ANNA1
50/50
93.18793.187
940432AE2-027 E
Adder
7.5611764705882356.427
935161AD1-151 C
Adder
13.84941176470588311.772
934012AD1-025 E
Adder
8.6341176470588247.339
935112AD1-144 E
Adder
0.8717647058823530.741
943462AF1-017 E
Adder
2.06941176470588231.759
316349AD2-085 C
Adder
3.23411764705882382.749
942341AE2-247 C
Adder
1.40235294117647061.192
932046AC2-012 E
Adder
12.31647058823529410.469
958161AF2-110 C
Adder
1.28941176470588251.096
958162AF2-110 E
Adder
2.0505882352941181.743
944582AF1-123 E
Adder
98.5858823529411883.798
944592AF1-124 E
Adder
98.9435294117647184.102
919153AA1-139 E2
Adder
3.8505882352941183.273
938531AE1-072 C
Adder
16.55647058823529614.073
923832AB2-022 E
Adder
1.1682352941176470.993
913392Y1-086 E
Adder
2.0705882352941181.76
938772AE1-103 E
Adder
3.8211764705882363.248
916042Z1-036 E
Adder
26.91882352941176422.881
3145393UNCAMP
Adder
5.7482352941176484.886
934502AD1-074 E
Adder
16.13411764705882613.714
934512AD1-075 E
Adder
4.0341176470588243.429
939411AE1-173 C
50/50
94.23794.237
933981AD1-022 C
Adder
8.247.004
900672V4-068 E
Adder
0.33764705882352940.287
918512AA1-065 E OP
Adder
5.2011764705882364.421
924516AB2-100 E1
Adder
2.82.38
940642AE2-051 E
50/50
12.32512.325
966621AG1-532 C
Adder
1.34705882352941191.145
960082AF2-299 E
Adder
1.19764705882352951.018
946281AF1-292 C
Adder
1.48705882352941181.264
926071AC1-086 C
Adder
19.96117647058823516.967
3137643SOCKMAN
Adder
0.67882352941176470.577
963042AG1-153 E
50/50
8.8728.872
924022AB2-043 E O1
Adder
4.8811764705882354.149
924302AB2-077 E O1
Adder
1.25764705882352931.069
964241AG1-285 C
Adder
11.78352941176470610.016
3147223TWITTYS
Adder
0.89294117647058820.759
959312AF2-222 E
Adder
10.4764705882352948.905
958212AF2-115 E
Adder
1.78941176470588231.521
933502AC2-165 E
Adder
7.6611764705882356.512
3152261N ANNA2
50/50
93.22693.226
925022AB2-158 E
50/50
9.5359.535
3151741LOISA C
50/50
2.4192.419
316303AF2-085
50/50
4.464.46
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5685.568
SIGELTFEXP_SIGE->PJM
CLTF
0.2320.232
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.1255.125
CBM South 2LTFEXP_CBM-S2->PJM
CBM
90.8190.81
CPLELTFEXP_CPLE->PJM
CLTF
10.7510.75
TVALTFEXP_TVA->PJM
CLTF
5.8785.878
O66PJM->LTFIMP_O-066
CMTX_NF
35.46935.469
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.02528.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.37921.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.6863.686
LAGNLTFEXP_LAGN->PJM
CLTF
7.3867.386
NYPJM->LTFIMP_NY
CLTF
2.6122.612
LGEELTFEXP_LGEE->PJM
CLTF
1.1951.195
WECLTFEXP_WEC->PJM
CLTF
0.5950.595

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.7 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4342.98
MW Contribution:148.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938531AE1-072 C
Adder
-16.896470588235296-14.362
316049AB1-081 C OP
80/20
0.9630.963
3151601KERR 3
80/20
1.8191.819
3151581KERR 1
80/20
0.650.65
935171AD1-152 C
80/20
3.2243.224
316238AB2-078 C O1
80/20
0.5160.516
964241AG1-285 C
80/20
19.39519.395
316034AC1-036 C
80/20
0.3540.354
962561AG1-105 C
80/20
15.92115.921
316118AC1-105 C
80/20
1.7691.769
3144293JTRSVLE
80/20
0.6050.605
316322AB2-045 C
80/20
0.2670.267
936161AD2-022 C
80/20
12.80112.801
270197AC1-083 C
80/20
0.9970.997
316217AC1-145 C
80/20
0.4120.412
942671AE2-283 C
80/20
3.7323.732
940601AE2-047 C
80/20
4.254.25
943811AF1-049 C
80/20
9.4269.426
938741AE1-100 C
80/20
0.7290.729
941671AE2-166 C
80/20
5.7085.708
944641AF1-129 C
Adder
-95.19529411764705-80.916
316240AF1-291 C
Adder
-2.031764705882353-1.727
944011AF1-069 C
80/20
38.91238.912
3152421Z1-086 GT2
80/20
32.07932.079
3152441Z1-086 ST
80/20
55.85555.855
3152411Z1-086 GT1
80/20
32.08832.088
963041AG1-153 C
80/20
17.24617.246
3151051BRUNSWICKS1
80/20
52.70552.705
3151041BRUNSWICKG3
80/20
25.36925.369
316263AC1-034 C
80/20
4.5164.516
937481AD2-202 C
80/20
0.9380.938
3151591KERR 2
80/20
1.8191.819
316239AB2-077 C O1
80/20
0.5160.516
936261AD2-033 C
80/20
19.83719.837
959311AF2-222 C
80/20
25.13225.132
964791AG1-342 C
80/20
6.5026.502
961791AG1-021 C
80/20
2.642.64
316248AF1-058 C
80/20
0.6420.642
316205AC1-080 C
80/20
0.5050.505
316123AC1-075 C
80/20
1.5121.512
936171AD2-023 C
80/20
7.4677.467
942751AE2-291 C
80/20
13.51213.512
940081AE1-250 C
80/20
13.65313.653
3151561HALLBR1
80/20
1.2391.239
941801AE2-185 C
80/20
4.7984.798
24684305SMG1
80/20
1.1751.175
957601AF2-054 C
Adder
-1.8941176470588237-1.61
933291AC2-141 C
Adder
-33.98823529411765-28.89
940641AE2-051 C
Adder
-22.240000000000002-18.904
3152431Z1-086 GT3
80/20
32.07932.079
316129AC1-054 C
80/20
1.1861.186
3151311EDGECMA
80/20
10.35810.358
934611AD1-087 C
80/20
3.2323.232
3151611KERR 4
80/20
1.8191.819
3151631KERR 6
80/20
1.8191.819
3151641KERR 7
80/20
1.8191.819
3151621KERR 5
80/20
1.8191.819
313527AB2-043 C
80/20
0.8060.806
316237AB2-079 C O1
80/20
0.5160.516
316131AB2-060 C
80/20
2.3152.315
3152661PLYWOOD A
80/20
2.3542.354
3138533PONTONDP
80/20
0.9780.978
316222AC1-221 C
80/20
2.9052.905
24684505SMG3
80/20
1.9881.988
24684705SMG5
80/20
1.2291.229
941431AE2-140 C
80/20
14.14314.143
942001AE2-212 C
Adder
-2.1176470588235294-1.8
941031AE2-094 C
80/20
119.094119.094
3151021BRUNSWICKG1
80/20
25.36925.369
3151031BRUNSWICKG2
80/20
25.36925.369
957481AF2-042 C
80/20
148.174148.174
316359AB2-059 C OP
80/20
1.1351.135
934621AD1-088 C
80/20
24.38424.384
3151531CLOVER1
80/20
32.84832.848
3151541CLOVER2
80/20
32.5432.54
958211AF2-115 C
80/20
3.33.3
946301AF1-294 C
80/20
5.4265.426
942461AE2-259 C
80/20
14.02314.023
316003AC1-222 C
80/20
1.9581.958
316283AC2-100 C
80/20
2.3262.326
316197AC1-042 C
80/20
0.3460.346
24728405LEESVG
80/20
0.9740.974
24684605SMG4
80/20
3.2353.235
24684405SMG2
80/20
3.2353.235
964211AG1-282 C
Adder
-1.7882352941176471-1.52
SIGELTFEXP_SIGE->PJM
CLTF
0.550.55
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.6199.619
CBM South 2LTFEXP_CBM-S2->PJM
CBM
177.277177.277
CPLELTFEXP_CPLE->PJM
CLTF
20.16220.162
TVALTFEXP_TVA->PJM
CLTF
12.22612.226
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.77474.774
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.81246.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.7578.757
LAGNLTFEXP_LAGN->PJM
CLTF
15.4915.49
NYPJM->LTFIMP_NY
CLTF
2.1882.188
LGEELTFEXP_LGEE->PJM
CLTF
2.8852.885
WECLTFEXP_WEC->PJM
CLTF
1.5251.525

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.59 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4175.62
MW Contribution:148.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944641AF1-129 C
Adder
-95.19529411764705-80.916
316240AF1-291 C
Adder
-2.031764705882353-1.727
3152421Z1-086 GT2
80/20
32.07932.079
3152441Z1-086 ST
80/20
55.85555.855
3152411Z1-086 GT1
80/20
32.08832.088
963041AG1-153 C
80/20
17.24617.246
3151051BRUNSWICKS1
80/20
52.70552.705
3151041BRUNSWICKG3
80/20
25.36925.369
316263AC1-034 C
80/20
4.5164.516
937481AD2-202 C
80/20
0.9380.938
3151591KERR 2
80/20
1.8191.819
316239AB2-077 C O1
80/20
0.5160.516
936261AD2-033 C
80/20
19.83719.837
959311AF2-222 C
80/20
25.13225.132
964791AG1-342 C
80/20
6.5026.502
961791AG1-021 C
80/20
2.642.64
316248AF1-058 C
80/20
0.6420.642
316205AC1-080 C
80/20
0.5050.505
316123AC1-075 C
80/20
1.5121.512
933291AC2-141 C
Adder
-33.98823529411765-28.89
940641AE2-051 C
Adder
-22.240000000000002-18.904
3152431Z1-086 GT3
80/20
32.07932.079
316129AC1-054 C
80/20
1.1861.186
3151311EDGECMA
80/20
10.35810.358
934611AD1-087 C
80/20
3.2323.232
3151611KERR 4
80/20
1.8191.819
3151631KERR 6
80/20
1.8191.819
3151641KERR 7
80/20
1.8191.819
3151621KERR 5
80/20
1.8191.819
313527AB2-043 C
80/20
0.8060.806
316237AB2-079 C O1
80/20
0.5160.516
316131AB2-060 C
80/20
2.3152.315
3152661PLYWOOD A
80/20
2.3542.354
3138533PONTONDP
80/20
0.9780.978
316222AC1-221 C
80/20
2.9052.905
24684505SMG3
80/20
1.9881.988
24684705SMG5
80/20
1.2291.229
941431AE2-140 C
80/20
14.14314.143
942001AE2-212 C
Adder
-2.1176470588235294-1.8
3151021BRUNSWICKG1
80/20
25.36925.369
3151031BRUNSWICKG2
80/20
25.36925.369
957481AF2-042 C
80/20
148.174148.174
316359AB2-059 C OP
80/20
1.1351.135
934621AD1-088 C
80/20
24.38424.384
3151531CLOVER1
80/20
32.84832.848
3151541CLOVER2
80/20
32.5432.54
958211AF2-115 C
80/20
3.33.3
946301AF1-294 C
80/20
5.4265.426
942461AE2-259 C
80/20
14.02314.023
316003AC1-222 C
80/20
1.9581.958
316283AC2-100 C
80/20
2.3262.326
316197AC1-042 C
80/20
0.3460.346
24728405LEESVG
80/20
0.9740.974
24684605SMG4
80/20
3.2353.235
24684405SMG2
80/20
3.2353.235
964211AG1-282 C
Adder
-1.7882352941176471-1.52
938531AE1-072 C
Adder
-16.896470588235296-14.362
316049AB1-081 C OP
80/20
0.9630.963
3151601KERR 3
80/20
1.8191.819
3151581KERR 1
80/20
0.650.65
935171AD1-152 C
80/20
3.2243.224
316238AB2-078 C O1
80/20
0.5160.516
964241AG1-285 C
80/20
19.39519.395
316034AC1-036 C
80/20
0.3540.354
962561AG1-105 C
80/20
15.92115.921
316118AC1-105 C
80/20
1.7691.769
3144293JTRSVLE
80/20
0.6050.605
316322AB2-045 C
80/20
0.2670.267
936161AD2-022 C
80/20
12.80112.801
270197AC1-083 C
80/20
0.9970.997
316217AC1-145 C
80/20
0.4120.412
942671AE2-283 C
80/20
3.7323.732
940601AE2-047 C
80/20
4.254.25
943811AF1-049 C
80/20
9.4269.426
938741AE1-100 C
80/20
0.7290.729
941671AE2-166 C
80/20
5.7085.708
936171AD2-023 C
80/20
7.4677.467
942751AE2-291 C
80/20
13.51213.512
940081AE1-250 C
80/20
13.65313.653
3151561HALLBR1
80/20
1.2391.239
941801AE2-185 C
80/20
4.7984.798
24684305SMG1
80/20
1.1751.175
957601AF2-054 C
Adder
-1.8941176470588237-1.61
SIGELTFEXP_SIGE->PJM
CLTF
0.550.55
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.6199.619
CBM South 2LTFEXP_CBM-S2->PJM
CBM
177.277177.277
CPLELTFEXP_CPLE->PJM
CLTF
20.16220.162
TVALTFEXP_TVA->PJM
CLTF
12.22612.226
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.77474.774
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.81246.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.7578.757
LAGNLTFEXP_LAGN->PJM
CLTF
15.4915.49
NYPJM->LTFIMP_NY
CLTF
2.1882.188
LGEELTFEXP_LGEE->PJM
CLTF
2.8852.885
WECLTFEXP_WEC->PJM
CLTF
1.5251.525

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.93 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3894.33
MW Contribution:51.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150731STONECA
Adder
5.3258823529411774.527
935161AD1-151 C
Adder
12.7647058823529410.85
316381AD1-082 C
80/20
1.0891.089
316083AB2-161 C
80/20
0.4780.478
316349AD2-085 C
80/20
2.9972.997
942341AE2-247 C
80/20
1.2991.299
3150991CHESPKB
80/20
0.6270.627
3151091ELIZAR2
80/20
2.7332.733
316246AF1-032 C
80/20
0.2480.248
958161AF2-110 C
80/20
1.1951.195
316388AE2-253 GEN
80/20
1.711.71
938531AE1-072 C
80/20
15.34615.346
316320Y1-086 C
80/20
0.1920.192
939411AE1-173 C
80/20
87.96287.962
933981AD1-022 C
Adder
7.6458823529411766.499
966621AG1-532 C
80/20
1.2551.255
946281AF1-292 C
80/20
1.3851.385
926071AC1-086 C
Adder
18.5623529411764715.778
3137643SOCKMAN
Adder
0.6317647058823530.537
927021AC1-189 C
Adder
7.2364705882352946.151
935171AD1-152 C
80/20
1.1991.199
964241AG1-285 C
Adder
11.0294117647058829.375
962561AG1-105 C
Adder
7.70470588235294156.549
3152261N ANNA2
80/20
89.07389.073
3151741LOISA C
80/20
2.7082.708
316044AC1-158 C1
80/20
19.41819.418
934861AD1-115 C
Adder
2.8482352941176472.421
939191AE1-149 C
80/20
9.2629.262
944641AF1-129 C
Adder
81.5517647058823669.319
316240AF1-291 C
Adder
1.7435294117647061.482
943461AF1-017 C
80/20
1.1751.175
316311AC2-079 C
80/20
4.9964.996
3150981CHESPKA
80/20
0.3780.378
316036AC1-147 C
80/20
0.320.32
941591AE2-156 C
80/20
15.615.6
3151101ELIZAR3
80/20
2.8172.817
316305AF2-043 C
80/20
0.3030.303
944591AF1-124 C
80/20
40.05140.051
944601AF1-125 C
80/20
39.29539.295
316321Z2-027 C
80/20
0.3170.317
3156056W1-029WIND
80/20
0.6760.676
938771AE1-103 C
80/20
2.5672.567
934521AD1-076 C
Adder
10.6788235294117659.077
934511AD1-075 C
Adder
7.3517647058823536.249
316233AE1-074 C
80/20
2.4172.417
960081AF2-299 C
80/20
1.6731.673
316087AB2-174 C
80/20
1.0461.046
944011AF1-069 C
80/20
13.03613.036
3152421Z1-086 GT2
80/20
10.43410.434
3152441Z1-086 ST
80/20
18.16818.168
3152411Z1-086 GT1
80/20
10.43710.437
963041AG1-153 C
80/20
5.5365.536
3151051BRUNSWICKS1
80/20
16.91816.918
3151041BRUNSWICKG3
80/20
8.1438.143
316263AC1-034 C
Adder
5.6858823529411774.833
937481AD2-202 C
80/20
0.3360.336
936261AD2-033 C
Adder
11.4505882352941189.733
316313AB2-026 C
80/20
0.3770.377
959311AF2-222 C
Adder
14.6623529411764712.463
964791AG1-342 C
Adder
3.06352941176470632.604
961791AG1-021 C
Adder
1.57882352941176471.342
3151751LOISA D
80/20
2.7082.708
3151731LOISA B
80/20
2.7082.708
316045AC1-158 C2
80/20
19.41819.418
316164AC1-076_C
80/20
1.1141.114
316170AC1-121 C
80/20
2.7242.724
940431AE2-027 C
Adder
10.4682352941176488.898
961611AG1-000B C
Adder
12.91058823529411910.974
942001AE2-212 C
Adder
1.82117647058823541.548
3150831SPRUNCA
Adder
7.6235294117647066.48
3150841SPRUNCB
Adder
7.6235294117647066.48
316375AC2-012 C
80/20
1.1731.173
3151081ELIZAR1
80/20
2.7822.782
916191Z1-068 C
80/20
0.0380.038
941101AE2-104 C
80/20
2.9282.928
316185AD1-033 C
80/20
1.071.07
944581AF1-123 C
80/20
39.90939.909
316294AC1-161 C
80/20
4.314.31
940541AE2-040 C
80/20
2.652.65
940481AE2-033 C
80/20
14.89114.891
934501AD1-074 C
Adder
29.40470588235294324.994
316365AB2-100 C1
80/20
0.8620.862
961941AG1-037 C
Adder
0.44235294117647060.376
941031AE2-094 C
80/20
39.89839.898
3147043LAWRENC
80/20
0.2730.273
3151021BRUNSWICKG1
80/20
8.1438.143
3151031BRUNSWICKG2
80/20
8.1438.143
934331AD1-057 C
Adder
3.0305882352941182.576
934321AD1-056 C
Adder
5.4329411764705894.618
961671AG1-007 C
Adder
0.80588235294117660.685
957481AF2-042 C
80/20
51.00351.003
934621AD1-088 C
80/20
8.9588.958
3151531CLOVER1
80/20
11.76811.768
3151541CLOVER2
80/20
11.65811.658
316258AE1-075 C
80/20
0.3460.346
958211AF2-115 C
Adder
1.97411764705882351.678
946301AF1-294 C
Adder
3.2458823529411762.759
942461AE2-259 C
Adder
8.7329411764705887.423
316192AB2-158 C
80/20
3.6253.625
3151801S ANNAS2
80/20
1.3621.362
3151791S ANNAG2
80/20
2.6512.651
3151771S ANNAG1
80/20
2.6512.651
3151781S ANNAS1
80/20
1.3621.362
3151761LOISA E
80/20
5.5225.522
966001AG1-469 C
80/20
1.9591.959
208900BRIS G1
80/20
-2.628-2.628
208901BRIS G2
80/20
-3.11-3.11
3150921YORKTN3
Adder
90.5694117647058876.984
3150651CHESTF6
Adder
14.84823529411764812.621
3150851SPRUNCC
80/20
0.1370.137
3150861SPRUNCD
80/20
0.1370.137
316316AC1-027 C
80/20
0.2750.275
957871AF2-081 C
80/20
8.7288.728
316017AA1-139 ULT1
80/20
0.9420.942
316018AA1-139 ULT2
80/20
0.9420.942
933291AC2-141 C
80/20
26.46526.465
313526AB2-022 C
80/20
0.3280.328
316315AB2-025 C
80/20
0.3750.375
316023AB2-100 C2
80/20
0.8620.862
940641AE2-051 C
80/20
17.2917.29
3152431Z1-086 GT3
80/20
10.43410.434
316274AC1-208 C
Adder
7.857647058823536.679
3151311EDGECMA
Adder
13.28823529411764811.295
934611AD1-087 C
80/20
1.1591.159
316405AF2-144 C
80/20
0.2940.294
3138533PONTONDP
Adder
0.58470588235294120.497
316336AC2-165 C
80/20
9.6099.609
3152251N ANNA1
80/20
89.03589.035
3151721LOISA A
80/20
2.6942.694
316254AC1-120 C
80/20
7.9327.932
316257AC1-043 C
Adder
5.697647058823534.843
316303AF2-085
80/20
4.1844.184
SIGELTFEXP_SIGE->PJM
CLTF
0.1910.191
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.744.74
CBM South 2LTFEXP_CBM-S2->PJM
CBM
83.40383.403
CPLELTFEXP_CPLE->PJM
CLTF
9.9459.945
TVALTFEXP_TVA->PJM
CLTF
5.1955.195
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.96121.961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.49718.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.0623.062
LAGNLTFEXP_LAGN->PJM
CLTF
6.5316.531
NYPJM->LTFIMP_NY
CLTF
2.5322.532
LGEELTFEXP_LGEE->PJM
CLTF
0.9710.971
WECLTFEXP_WEC->PJM
CLTF
0.4740.474

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.78 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3857.57
MW Contribution:53.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966661AG1-536 C
Adder
5.5082352941176484.682
316169AC1-164 GEN
Adder
42.77176470588235436.356
3150771HOPHCF1
80/20
2.6772.677
3150731STONECA
80/20
7.6067.606
935161AD1-151 C
Adder
17.79176470588235415.123
3142366NRTHEST
80/20
0.20.2
316349AD2-085 C
Adder
3.79058823529411763.222
942341AE2-247 C
Adder
1.64235294117647061.396
3150991CHESPKB
80/20
0.7960.796
3151091ELIZAR2
80/20
3.4653.465
958161AF2-110 C
Adder
1.50117647058823531.276
938531AE1-072 C
Adder
19.2929411764705916.399
939411AE1-173 C
80/20
97.64897.648
933981AD1-022 C
Adder
9.2505882352941197.863
966621AG1-532 C
Adder
1.43529411764705881.22
946281AF1-292 C
Adder
1.58470588235294121.347
926071AC1-086 C
Adder
21.50823529411764718.282
3137643SOCKMAN
Adder
0.72705882352941180.618
927021AC1-189 C
Adder
8.4188235294117647.156
964241AG1-285 C
Adder
11.97764705882352810.181
962561AG1-105 C
Adder
8.3588235294117657.105
3152261N ANNA2
80/20
55.34655.346
316044AC1-158 C1
80/20
14.96214.962
939261AE1-157 C
Adder
13.77647058823529511.71
958261AF2-120 C
Adder
6.4035294117647065.443
940551AE2-041 C
Adder
7.4541176470588246.336
3150601CHESTF5
Adder
68.9811764705882458.634
3143096IRON208
80/20
0.4840.484
3150781HOPHCF2
80/20
2.6772.677
3150761HOPPOLC
80/20
1.6841.684
939191AE1-149 C
80/20
11.90511.905
944641AF1-129 C
80/20
113.49113.49
316240AF1-291 C
80/20
2.3942.394
943461AF1-017 C
Adder
1.48588235294117641.263
316311AC2-079 C
Adder
6.3129411764705885.366
941591AE2-156 C
80/20
19.79319.793
3151101ELIZAR3
80/20
3.5723.572
944591AF1-124 C
80/20
50.39950.399
944601AF1-125 C
80/20
49.44749.447
938771AE1-103 C
Adder
3.162.686
934521AD1-076 C
Adder
12.96470588235294111.02
934511AD1-075 C
Adder
8.9247058823529427.586
316233AE1-074 C
80/20
2.8192.819
960081AF2-299 C
Adder
1.91411764705882351.627
944011AF1-069 C
80/20
13.51813.518
963041AG1-153 C
Adder
5.7647058823529424.9
316263AC1-034 C
Adder
6.5105882352941185.534
936261AD2-033 C
Adder
12.4023529411764710.542
959311AF2-222 C
Adder
15.85294117647058913.475
964791AG1-342 C
Adder
3.32117647058823542.823
961791AG1-021 C
Adder
1.70000000000000021.445
957601AF2-054 C
Adder
2.2117647058823531.88
316045AC1-158 C2
80/20
14.96214.962
316164AC1-076_C
80/20
0.9930.993
966881AG1-559 C
Adder
2.3964705882352942.037
963611AG1-210 C
Adder
0.66705882352941170.567
962861AG1-135 C
Adder
6.222352941176475.289
943741AF1-042 C
Adder
2.9964705882352942.547
940431AE2-027 C
80/20
14.31814.318
3150801HOPHCF4
80/20
4.0644.064
961611AG1-000B C
Adder
17.55647058823529614.923
942001AE2-212 C
80/20
2.3972.397
3150831SPRUNCA
80/20
10.21910.219
3150841SPRUNCB
80/20
10.21910.219
316375AC2-012 C
80/20
1.4881.488
3151081ELIZAR1
80/20
3.5273.527
941101AE2-104 C
Adder
3.683.128
944581AF1-123 C
80/20
50.22150.221
316294AC1-161 C
80/20
5.4825.482
940541AE2-040 C
Adder
3.03764705882352942.582
940481AE2-033 C
Adder
17.08117647058823614.519
934501AD1-074 C
Adder
35.6976470588235330.343
961941AG1-037 C
Adder
0.52705882352941180.448
941031AE2-094 C
80/20
41.37341.373
934331AD1-057 C
Adder
3.4882352941176472.965
934321AD1-056 C
Adder
6.2529411764705895.315
961671AG1-007 C
Adder
0.9317647058823530.792
957481AF2-042 C
Adder
53.64117647058823545.595
927041AC1-191 C
Adder
10.0729411764705888.562
966871AG1-558 C
Adder
2.50941176470588222.133
934621AD1-088 C
Adder
9.4482352941176488.031
958211AF2-115 C
Adder
2.12470588235294141.806
946301AF1-294 C
Adder
3.4941176470588242.97
942461AE2-259 C
Adder
9.347.939
316192AB2-158 C
80/20
2.1182.118
964211AG1-282 C
Adder
2.0317647058823531.727
936591AD2-074 C
Adder
5.7258823529411764.867
961951AG1-038 C
Adder
3.3117647058823532.815
943471AF1-018 C
Adder
7.4541176470588246.336
944631AF1-128 C
Adder
43.1623529411764736.688
3150921YORKTN3
Adder
130.26705882352942110.727
3150791HOPHCF3
80/20
2.6772.677
3150651CHESTF6
80/20
20.66420.664
3150851SPRUNCC
80/20
0.1830.183
3150861SPRUNCD
80/20
0.1830.183
3152331SURRY 2
80/20
27.29427.294
957871AF2-081 C
Adder
10.989.333
933291AC2-141 C
80/20
33.66433.664
940641AE2-051 C
80/20
18.48818.488
316274AC1-208 C
Adder
9.0917647058823537.728
3151311EDGECMA
Adder
15.22352941176470512.94
3138533PONTONDP
Adder
0.62941176470588240.535
316336AC2-165 C
Adder
10.1094117647058828.593
3152251N ANNA1
80/20
55.32355.323
316303AF2-085
80/20
4.3634.363
SIGELTFEXP_SIGE->PJM
CLTF
0.2370.237
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.2865.286
CBM South 2LTFEXP_CBM-S2->PJM
CBM
94.17394.173
CPLELTFEXP_CPLE->PJM
CLTF
11.08811.088
TVALTFEXP_TVA->PJM
CLTF
6.1396.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.65727.657
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.08222.082
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.7473.747
LAGNLTFEXP_LAGN->PJM
CLTF
7.6777.677
NYPJM->LTFIMP_NY
CLTF
2.8062.806
LGEELTFEXP_LGEE->PJM
CLTF
1.2221.222
WECLTFEXP_WEC->PJM
CLTF
0.5950.595

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.54 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4631.24
MW Contribution:88.88
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
Adder
15.92588235294117813.537
940432AE2-027 E
Adder
7.4705882352941186.35
3150731STONECA
Adder
0.92705882352941180.788
935161AD1-151 C
Adder
13.69411764705882511.64
934012AD1-025 E
Adder
8.5352941176470597.255
935112AD1-144 E
Adder
0.85764705882352940.729
943462AF1-017 E
Adder
2.03764705882352941.732
316349AD2-085 C
Adder
3.1835294117647062.706
942341AE2-247 C
Adder
1.38000000000000011.173
932046AC2-012 E
Adder
12.12705882352941210.308
958161AF2-110 C
Adder
1.26823529411764711.078
958162AF2-110 E
Adder
2.01764705882352931.715
944582AF1-123 E
Adder
97.0317647058823782.477
944592AF1-124 E
Adder
97.3823529411764882.775
919153AA1-139 E2
Adder
3.78941176470588253.221
938531AE1-072 C
Adder
16.29411764705882213.85
923832AB2-022 E
Adder
1.14941176470588240.977
913392Y1-086 E
Adder
2.03647058823529431.731
938772AE1-103 E
Adder
3.75764705882352963.194
916042Z1-036 E
Adder
26.4694117647058822.499
3145393UNCAMP
Adder
5.65176470588235354.804
934502AD1-074 E
Adder
15.85176470588235313.474
934512AD1-075 E
Adder
3.96235294117647063.368
939411AE1-173 C
Adder
92.2811764705882478.439
933981AD1-022 C
Adder
8.0941176470588236.88
900672V4-068 E
Adder
0.33058823529411770.281
918512AA1-065 E OP
Adder
5.1070588235294124.341
924516AB2-100 E1
Adder
2.74588235294117672.334
940642AE2-051 E
50/50
12.05212.052
966621AG1-532 C
Adder
1.32117647058823541.123
960082AF2-299 E
Adder
1.17529411764705880.999
946281AF1-292 C
Adder
1.45882352941176461.24
926071AC1-086 C
Adder
19.57647058823529616.64
3137643SOCKMAN
Adder
0.66588235294117650.566
963042AG1-153 E
Adder
8.6682352941176477.368
924022AB2-043 E O1
Adder
4.7941176470588244.075
924302AB2-077 E O1
Adder
1.23529411764705891.05
964241AG1-285 C
Adder
11.5811764705882349.844
3147223TWITTYS
Adder
0.87882352941176480.747
962561AG1-105 C
Adder
8.0894117647058836.876
959312AF2-222 E
Adder
10.3129411764705888.766
958212AF2-115 E
Adder
1.76470588235294111.5
933502AC2-165 E
Adder
7.5705882352941176.435
3152261N ANNA2
50/50
89.60889.608
925022AB2-158 E
50/50
9.7219.721
3151741LOISA C
50/50
2.7452.745
316044AC1-158 C1
50/50
19.48619.486
926486AC1-120 E
50/50
4.1534.153
934861AD1-115 C
Adder
2.92.465
925332AB2-190 E
Adder
6.8164705882352945.794
935162AD1-151 E
Adder
9.1294117647058827.76
927226AC1-216 E
Adder
6.5917647058823535.603
924814AB2-134 E
Adder
10.7988235294117659.179
939191AE1-149 C
Adder
9.8529411764705898.375
944641AF1-129 C
Adder
87.4717647058823574.351
316240AF1-291 C
Adder
1.86705882352941191.587
936666AD2-085 E
Adder
5.195294117647064.416
942342AE2-247 E
Adder
1.90588235294117661.62
943461AF1-017 C
Adder
1.2482352941176471.061
3143316POE
Adder
1.28823529411764711.095
932596AC2-079 E
Adder
8.6588235294117667.36
316311AC2-079 C
Adder
5.3070588235294124.511
941591AE2-156 C
Adder
16.57647058823529614.09
944591AF1-124 C
Adder
42.5247058823529436.146
944601AF1-125 C
Adder
41.7211764705882435.463
919152AA1-139 E1
Adder
3.78941176470588253.221
938532AE1-072 E
Adder
8.4941176470588247.22
3146326AYDLETT TAP
Adder
1.25764705882352931.069
917122Z2-027 E
Adder
1.24470588235294131.058
901082W1-029 E
Adder
29.54000000000000325.109
938771AE1-103 C
Adder
2.72117647058823582.313
3145413WATKINS
Adder
0.64235294117647070.546
920692AA2-178 E
Adder
3.8023529411764713.232
934521AD1-076 C
Adder
11.3094117647058829.613
934511AD1-075 C
Adder
7.7847058823529426.617
316233AE1-074 C
Adder
2.5458823529411772.164
920042AA2-088 E OP
Adder
9.8670588235294128.387
960081AF2-299 C
Adder
1.76235294117647071.498
966622AG1-532 E
Adder
0.88117647058823530.749
926072AC1-086 E
Adder
8.9094117647058837.573
3145723EMPORIA
Adder
0.405882352941176470.345
923573AB1-173 E OP
Adder
3.07647058823529432.615
919692AA2-053 E OP
Adder
3.93176470588235333.342
944011AF1-069 C
50/50
13.59813.598
926206AC1-098 E
Adder
3.35647058823529452.853
963041AG1-153 C
Adder
5.7788235294117654.912
925785AC1-054 E
Adder
3.18705882352941172.709
936261AD2-033 C
Adder
12.02117647058823610.218
962562AG1-105 E
Adder
5.3929411764705884.584
959311AF2-222 C
Adder
15.39294117647058813.084
961791AG1-021 C
Adder
1.65764705882352951.409
3147133PAMPLIN
Adder
0.91529411764705890.778
942462AE2-259 E
Adder
6.1105882352941175.194
3151751LOISA D
50/50
2.7452.745
3151731LOISA B
50/50
2.7452.745
966002AG1-469 E
50/50
0.9930.993
316045AC1-158 C2
50/50
19.48619.486
926739AC1-158 E1
50/50
50.96750.967
316164AC1-076_C
50/50
1.1311.131
316170AC1-121 C
50/50
2.7692.769
926502AC1-121 E
50/50
1.3031.303
940431AE2-027 C
Adder
11.2058823529411789.525
961611AG1-000B C
Adder
13.8152941176470611.743
939192AE1-149 E
Adder
6.5694117647058825.584
939312AE1-162 E
Adder
1.27764705882352961.086
942002AE2-212 E
Adder
1.2952941176470591.101
942001AE2-212 C
Adder
1.94235294117647061.651
3150831SPRUNCA
Adder
8.1435294117647056.922
3150841SPRUNCB
Adder
8.1435294117647056.922
926662AC1-147 E
Adder
1.22588235294117661.042
916192Z1-068 E
Adder
1.74235294117647071.481
957492AF2-043 E
Adder
1.31882352941176471.121
941101AE2-104 C
Adder
3.10941176470588232.643
934065AD1-033 E
Adder
4.6541176470588243.956
937226AE2-253 E
Adder
5.4188235294117654.606
944581AF1-123 C
Adder
42.37411764705882436.018
940541AE2-040 C
Adder
2.78823529411764742.37
923852AB2-025 E
Adder
1.1282352941176470.959
940481AE2-033 C
Adder
15.6752941176470613.324
940482AE2-033 E
Adder
10.5670588235294118.982
934501AD1-074 C
Adder
31.13882352941176626.468
939412AE1-173 E
Adder
61.5211764705882452.293
924517AB2-100 E2
Adder
2.74588235294117672.334
961942AG1-037 E
Adder
0.311764705882352940.265
316141AB2-099 E
Adder
0.234117647058823540.199
961941AG1-037 C
Adder
0.46705882352941180.397
923263AB1-132 E OP
Adder
5.697647058823534.843
316088AB2-174 E
Adder
6.1235294117647065.205
923994AB2-040_E
Adder
5.76941176470588254.904
941031AE2-094 C
50/50
41.61841.618
941032AE2-094 E
50/50
18.6418.64
957482AF2-042 E
Adder
35.55176470588235630.219
957481AF2-042 C
Adder
53.3270588235294245.328
934621AD1-088 C
Adder
9.3717647058823547.966
935172AD1-152 E
Adder
5.1847058823529414.407
924322AB2-079 E O1
Adder
1.23529411764705891.05
924312AB2-078 E O1
Adder
1.23529411764705891.05
936262AD2-033 E
Adder
8.0141176470588256.812
958502AF2-144 E
Adder
1.2588235294117651.07
923862AB2-026 E
Adder
1.28117647058823541.089
925612AC1-036 E
Adder
0.79294117647058830.674
958211AF2-115 C
Adder
2.0717647058823531.761
946301AF1-294 C
Adder
3.4070588235294122.896
946302AF1-294 E
Adder
2.88470588235294122.452
942461AE2-259 C
Adder
9.1658823529411777.791
316192AB2-158 C
50/50
3.6573.657
3151801S ANNAS2
50/50
1.381.38
3151791S ANNAG2
50/50
2.6852.685
3151771S ANNAG1
50/50
2.6852.685
3151781S ANNAS1
50/50
1.381.38
3151761LOISA E
50/50
5.5965.596
966001AG1-469 C
50/50
1.9871.987
926740AC1-158 E2
50/50
50.96750.967
925672AC1-043 E
Adder
9.4635294117647078.044
208900BRIS G1
50/50
-2.836-2.836
208901BRIS G2
50/50
-3.356-3.356
946262AF1-291 E
Adder
1.24470588235294131.058
934576AD1-082 E
Adder
4.0564705882352943.448
316084AB2-161 E
Adder
5.0917647058823544.328
3145256KINGFORK
Adder
0.92470588235294130.786
925522AC1-027 E
Adder
1.1282352941176470.959
943612AF1-032 E
Adder
0.85764705882352940.729
941102AE2-104 E
Adder
4.9423529411764714.201
3145506HICKORY
Adder
2.02235294117647071.719
944602AF1-125 E
Adder
95.5082352941176581.182
957872AF2-081 E
Adder
3.9717647058823533.376
957871AF2-081 C
Adder
9.2670588235294127.877
933292AC2-141 E
Adder
12.0070588235294110.206
933291AC2-141 C
Adder
28.12941176470588223.91
926755AC1-161 E
Adder
12.0070588235294110.206
940492AE2-034 E
Adder
2.85176470588235282.424
3145946PLYMOUTH TP
Adder
0.29882352941176470.254
934522AD1-076 E
Adder
5.7635294117647064.899
938552AE1-074 E
Adder
1.28235294117647071.09
933982AD1-022 E
Adder
4.4070588235294123.746
943172AE2-346 E
Adder
0.56117647058823530.477
940641AE2-051 C
50/50
18.07818.078
918492AA1-063AE OP
Adder
3.80117647058823543.231
925122AB2-169 E
Adder
5.2764705882352954.485
917332KELFORD E
Adder
1.51764705882352961.29
946282AF1-292 E
Adder
0.97294117647058820.827
944012AF1-069 E
50/50
5.2835.283
932632AC2-084 E
Adder
2.96705882352941152.522
926214AC1-099 E
Adder
1.1082352941176470.942
316274AC1-208 C
Adder
8.2905882352941187.047
927146AC1-208 E
Adder
3.68117647058823533.129
934622AD1-088 E
Adder
4.5117647058823533.835
937482AD2-202 E
Adder
1.02705882352941180.873
934612AD1-087 E
Adder
3.50941176470588272.983
924162AB2-060 E OP
Adder
3.95764705882352933.364
964242AG1-285 E
Adder
7.7211764705882356.563
938562AE1-075 E
Adder
1.0917647058823530.928
961792AG1-021 E
Adder
1.4117647058823531.2
3138533PONTONDP
Adder
0.61411764705882350.522
316336AC2-165 C
Adder
10.0588235294117668.55
3152251N ANNA1
50/50
89.57189.571
3151721LOISA A
50/50
2.7312.731
926004AC1-076_E
50/50
6.486.48
316254AC1-120 C
50/50
8.0618.061
316257AC1-043 C
Adder
5.84.93
934862AD1-115 E
Adder
4.73176470588235354.022
316303AF2-085
50/50
4.3644.364
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7645.764
SIGELTFEXP_SIGE->PJM
CLTF
0.2140.214
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.0035.003
CBM South 2LTFEXP_CBM-S2->PJM
CBM
88.42988.429
CPLELTFEXP_CPLE->PJM
CLTF
10.49610.496
TVALTFEXP_TVA->PJM
CLTF
5.6275.627
O66PJM->LTFIMP_O-066
CMTX_NF
36.7236.72
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.22125.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.23820.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.4183.418
LAGNLTFEXP_LAGN->PJM
CLTF
7.0687.068
NYPJM->LTFIMP_NY
CLTF
2.7142.714
LGEELTFEXP_LGEE->PJM
CLTF
1.0981.098
WECLTFEXP_WEC->PJM
CLTF
0.5410.541

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4234.7
MW Contribution:129.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938531AE1-072 C
Adder
-16.01294117647059-13.611
316049AB1-081 C OP
80/20
0.9230.923
3151601KERR 3
80/20
1.6151.615
3151581KERR 1
80/20
0.5770.577
935171AD1-152 C
80/20
2.8492.849
316238AB2-078 C O1
80/20
0.4550.455
964241AG1-285 C
80/20
17.07617.076
316034AC1-036 C
80/20
0.3110.311
962561AG1-105 C
80/20
14.10814.108
316118AC1-105 C
80/20
1.5721.572
3144293JTRSVLE
80/20
0.5290.529
316322AB2-045 C
80/20
0.2270.227
936161AD2-022 C
80/20
12.15912.159
270197AC1-083 C
80/20
0.9340.934
316217AC1-145 C
80/20
0.3750.375
942671AE2-283 C
80/20
3.3963.396
940601AE2-047 C
80/20
4.0274.027
943811AF1-049 C
80/20
8.9298.929
938741AE1-100 C
80/20
0.690.69
941671AE2-166 C
80/20
5.45.4
944641AF1-129 C
Adder
-90.49176470588236-76.918
316240AF1-291 C
Adder
-1.9317647058823528-1.642
944011AF1-069 C
80/20
45.1645.16
3152421Z1-086 GT2
80/20
33.46433.464
3152441Z1-086 ST
80/20
58.26658.266
3152411Z1-086 GT1
80/20
33.47333.473
963041AG1-153 C
80/20
17.10317.103
3151051BRUNSWICKS1
80/20
52.26552.265
3151041BRUNSWICKG3
80/20
25.15725.157
316263AC1-034 C
80/20
4.3284.328
937481AD2-202 C
80/20
0.8240.824
3151591KERR 2
80/20
1.6151.615
316239AB2-077 C O1
80/20
0.4550.455
936261AD2-033 C
80/20
17.43217.432
959311AF2-222 C
80/20
22.05622.056
964791AG1-342 C
80/20
5.7665.766
961791AG1-021 C
80/20
2.3092.309
316248AF1-058 C
80/20
0.5710.571
316205AC1-080 C
80/20
0.4520.452
316123AC1-075 C
80/20
1.3531.353
936171AD2-023 C
80/20
7.0937.093
942751AE2-291 C
80/20
12.11212.112
940081AE1-250 C
80/20
12.86112.861
3151561HALLBR1
80/20
1.1241.124
941801AE2-185 C
80/20
4.3664.366
24684305SMG1
80/20
1.0911.091
957601AF2-054 C
Adder
-1.8-1.53
933291AC2-141 C
Adder
-32.203529411764706-27.373
940641AE2-051 C
Adder
-21.040000000000003-17.884
3152431Z1-086 GT3
80/20
33.46433.464
316129AC1-054 C
80/20
1.0481.048
934611AD1-087 C
80/20
2.842.84
3151611KERR 4
80/20
1.6151.615
3151631KERR 6
80/20
1.6151.615
3151641KERR 7
80/20
1.6151.615
3151621KERR 5
80/20
1.6151.615
313527AB2-043 C
80/20
0.7110.711
316237AB2-079 C O1
80/20
0.4550.455
316131AB2-060 C
80/20
2.042.04
3152661PLYWOOD A
80/20
2.0932.093
3138533PONTONDP
80/20
0.8550.855
316222AC1-221 C
80/20
2.6372.637
24684505SMG3
80/20
1.8451.845
24684705SMG5
80/20
1.1411.141
941431AE2-140 C
80/20
13.39313.393
942001AE2-212 C
Adder
-2.010588235294118-1.709
941031AE2-094 C
80/20
138.215138.215
3151021BRUNSWICKG1
80/20
25.15725.157
3151031BRUNSWICKG2
80/20
25.15725.157
957481AF2-042 C
80/20
129.887129.887
316359AB2-059 C OP
80/20
1.0881.088
934621AD1-088 C
80/20
21.36821.368
3151531CLOVER1
80/20
28.86828.868
3151541CLOVER2
80/20
28.59828.598
958211AF2-115 C
80/20
2.8862.886
946301AF1-294 C
80/20
4.7464.746
942461AE2-259 C
80/20
12.19912.199
316003AC1-222 C
80/20
1.7441.744
316283AC2-100 C
80/20
2.1162.116
316197AC1-042 C
80/20
0.3150.315
24728405LEESVG
80/20
0.8940.894
24684605SMG4
80/20
3.0033.003
24684405SMG2
80/20
3.0033.003
964211AG1-282 C
Adder
-1.7011764705882353-1.446
SIGELTFEXP_SIGE->PJM
CLTF
0.5240.524
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.2639.263
CBM South 2LTFEXP_CBM-S2->PJM
CBM
170.641170.641
CPLELTFEXP_CPLE->PJM
CLTF
19.41719.417
TVALTFEXP_TVA->PJM
CLTF
11.71211.712
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.06671.066
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.76444.764
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.3488.348
LAGNLTFEXP_LAGN->PJM
CLTF
14.84614.846
NYPJM->LTFIMP_NY
CLTF
2.1082.108
LGEELTFEXP_LGEE->PJM
CLTF
2.7422.742
WECLTFEXP_WEC->PJM
CLTF
1.451.45
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 568T575_SRT-A'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1   /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1   /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 314940 TO BUS 941030 CKT 1   /*8ROGERS RD   500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314282 to 314285 ckt 1
314902 to 314914 ckt 1
314908 to 314911 ckt 1
314911 to 314922 ckt 1
314914 to 314322 ckt 1
314914 to 314918 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314936 to 314902 ckt 1
314934 to 314916 ckt 1
941030 to 314902 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC109.21 %678.68B741.1845.97
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC108.15 %678.68B734.0345.97
GD1DVP
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
OPAC107.58 %571.52B614.81143.24
GD1DVP
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC103.25 %984.18B1016.2128.36
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC105.97 %661.76B701.2942.89
GD1DVP
6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
OPAC108.24 %571.52B618.61143.24
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC108.64 %661.76B718.9142.89
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC102.38 %661.76B677.5242.89
GD1DVP
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
OPAC107.58 %571.52B614.81143.24
GD1DVP
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC103.2 %984.18B1015.6828.36
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Base Case
OPAC104.13 %3220.44A3353.36116.57
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC132.17 %2442.12B3227.6860.76
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
OPAC126.34 %1058.16B1336.8847.23
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
OPAC108.69 %4070.2B4423.71245.83
GD1DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC106.0 %2442.12B2588.6192.1
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN POSSUM-KRAKEN_SRT-A
OPAC103.79 %3220.44B3342.6340.98
GD1DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
OPAC105.93 %4070.2B4311.69214.41

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.21 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:741.18
MW Contribution:45.97
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.95 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:773.37
MW Contribution:45.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
50/50
32.5532.55
934622AD1-088 E
50/50
3.2133.213
934612AD1-087 E
Adder
1.95058823529411751.658
3151931BEARGRDN S1
50/50
23.0223.02
936262AD2-033 E
50/50
8.7818.781
958211AF2-115 C
50/50
3.1013.101
941012AE2-092 E
Adder
5.48117647058823554.659
316131AB2-060 C
50/50
1.121.12
3138533PONTONDP
50/50
0.9190.919
3147133PAMPLIN
50/50
1.4571.457
316322AB2-045 C
50/50
0.840.84
927264AC1-222 E
Adder
1.98117647058823531.684
958132AF2-107 E
Adder
1.30941176470588231.113
936261AD2-033 C
50/50
13.17213.172
3144293JTRSVLE
50/50
0.5710.571
961791AG1-021 C
50/50
2.4812.481
962562AG1-105 E
50/50
3.6743.674
924032AB2-045 E
50/50
3.7663.766
957482AF2-042 E
Adder
18.38941176470588315.631
934621AD1-088 C
50/50
6.6736.673
935172AD1-152 E
Adder
2.81529411764705852.393
946301AF1-294 C
50/50
5.15.1
942461AE2-259 C
50/50
17.67317.673
938822AE1-108 E
50/50
7.9317.931
937482AD2-202 E
Adder
0.57058823529411760.485
961792AG1-021 E
50/50
2.1132.113
3151921BEARGRDN G2
50/50
17.79517.795
964241AG1-285 C
50/50
9.9699.969
316034AC1-036 C
50/50
0.2430.243
958212AF2-115 E
50/50
2.6422.642
962561AG1-105 C
50/50
5.5115.511
941011AE2-092 C
Adder
8.222352941176476.989
3147223TWITTYS
50/50
0.9860.986
959312AF2-222 E
50/50
12.07212.072
924022AB2-043 E O1
50/50
3.7783.778
316239AB2-077 C O1
50/50
0.2340.234
942462AE2-259 E
50/50
11.78211.782
964791AG1-342 C
Adder
2.1235294117647061.805
924302AB2-077 E O1
50/50
0.9550.955
958131AF2-107 C
Adder
2.38941176470588262.031
957481AF2-042 C
Adder
27.58352941176470823.446
924322AB2-079 E O1
50/50
0.9550.955
946302AF1-294 E
50/50
4.3194.319
943902AF1-058 E
Adder
0.65294117647058840.555
964242AG1-285 E
50/50
6.6466.646
313527AB2-043 C
50/50
0.3760.376
924162AB2-060 E OP
50/50
3.2253.225
964792AG1-342 E
Adder
1.41647058823529411.204
3151911BEARGRDN G1
50/50
17.79517.795
925785AC1-054 E
Adder
1.48235294117647071.26
959311AF2-222 C
50/50
18.01818.018
933502AC2-165 E
50/50
24.49824.498
925612AC1-036 E
50/50
0.8890.889
316237AB2-079 C O1
50/50
0.2340.234
924312AB2-078 E O1
50/50
0.9550.955
316238AB2-078 C O1
50/50
0.2340.234
926274AC1-105 E
Adder
1.48352941176470581.261
938821AE1-108 C
50/50
16.62316.623
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0240.024
MECLTFEXP_MEC->PJM
CLTF
0.2490.249
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3441.344
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.54721.547
WECLTFEXP_WEC->PJM
CLTF
0.0090.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.161.16
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.0390.039
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6760.676
CPLELTFEXP_CPLE->PJM
CLTF
2.8232.823
SIGELTFEXP_SIGE->PJM
CLTF
0.0110.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.6382.638
NYPJM->LTFIMP_NY
CLTF
0.3510.351
TVALTFEXP_TVA->PJM
CLTF
0.8870.887
O66PJM->LTFIMP_O-066
CMTX_NF
4.3344.334

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.15 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:734.03
MW Contribution:45.97
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.89 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:766.15
MW Contribution:45.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
50/50
32.5532.55
934622AD1-088 E
50/50
3.2133.213
934612AD1-087 E
Adder
1.95058823529411751.658
3151931BEARGRDN S1
50/50
23.0223.02
936262AD2-033 E
50/50
8.7818.781
958211AF2-115 C
50/50
3.1013.101
941012AE2-092 E
Adder
5.48117647058823554.659
316131AB2-060 C
50/50
1.121.12
3138533PONTONDP
50/50
0.9190.919
3147133PAMPLIN
50/50
1.4571.457
316322AB2-045 C
50/50
0.840.84
927264AC1-222 E
Adder
1.98117647058823531.684
958132AF2-107 E
Adder
1.30941176470588231.113
957482AF2-042 E
Adder
18.38941176470588315.631
934621AD1-088 C
50/50
6.6736.673
935172AD1-152 E
Adder
2.81529411764705852.393
964241AG1-285 C
50/50
9.9699.969
316034AC1-036 C
50/50
0.2430.243
958212AF2-115 E
50/50
2.6422.642
962561AG1-105 C
50/50
5.5115.511
936261AD2-033 C
50/50
13.17213.172
3144293JTRSVLE
50/50
0.5710.571
961791AG1-021 C
50/50
2.4812.481
962562AG1-105 E
50/50
3.6743.674
924032AB2-045 E
50/50
3.7663.766
937482AD2-202 E
Adder
0.57058823529411760.485
961792AG1-021 E
50/50
2.1132.113
3151921BEARGRDN G2
50/50
17.79517.795
941011AE2-092 C
Adder
8.222352941176476.989
3147223TWITTYS
50/50
0.9860.986
959312AF2-222 E
50/50
12.07212.072
924022AB2-043 E O1
50/50
3.7783.778
316239AB2-077 C O1
50/50
0.2340.234
942462AE2-259 E
50/50
11.78211.782
964791AG1-342 C
Adder
2.1235294117647061.805
946301AF1-294 C
50/50
5.15.1
942461AE2-259 C
50/50
17.67317.673
938822AE1-108 E
50/50
7.9317.931
924302AB2-077 E O1
50/50
0.9550.955
958131AF2-107 C
Adder
2.38941176470588262.031
957481AF2-042 C
Adder
27.58352941176470823.446
924322AB2-079 E O1
50/50
0.9550.955
946302AF1-294 E
50/50
4.3194.319
943902AF1-058 E
Adder
0.65294117647058840.555
964242AG1-285 E
50/50
6.6466.646
313527AB2-043 C
50/50
0.3760.376
924162AB2-060 E OP
50/50
3.2253.225
964792AG1-342 E
Adder
1.41647058823529411.204
3151911BEARGRDN G1
50/50
17.79517.795
925785AC1-054 E
Adder
1.48235294117647071.26
959311AF2-222 C
50/50
18.01818.018
933502AC2-165 E
50/50
24.49824.498
925612AC1-036 E
50/50
0.8890.889
316237AB2-079 C O1
50/50
0.2340.234
924312AB2-078 E O1
50/50
0.9550.955
316238AB2-078 C O1
50/50
0.2340.234
926274AC1-105 E
Adder
1.48352941176470581.261
938821AE1-108 C
50/50
16.62316.623
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.54721.547
WECLTFEXP_WEC->PJM
CLTF
0.0090.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.161.16
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.0390.039
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6760.676
CPLELTFEXP_CPLE->PJM
CLTF
2.8232.823
SIGELTFEXP_SIGE->PJM
CLTF
0.0110.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.6382.638
NYPJM->LTFIMP_NY
CLTF
0.3510.351
TVALTFEXP_TVA->PJM
CLTF
0.8870.887
O66PJM->LTFIMP_O-066
CMTX_NF
4.3344.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0240.024
MECLTFEXP_MEC->PJM
CLTF
0.2490.249
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3441.344

Details for 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:107.58 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:614.81
MW Contribution:143.24
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.99 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:645.76
MW Contribution:164.63
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
Adder
-4.488235294117647-3.815
934622AD1-088 E
50/50
8.0788.078
934611AD1-087 C
50/50
1.9191.919
934612AD1-087 E
50/50
5.5365.536
3151611KERR 4
50/50
1.1131.113
927255AC1-221 E
50/50
3.413.41
936262AD2-033 E
Adder
3.5152941176470592.988
946282AF1-292 E
Adder
0.32235294117647060.274
316129AC1-054 C
50/50
0.8410.841
316131AB2-060 C
50/50
1.3891.389
316118AC1-105 C
50/50
0.9880.988
966622AG1-532 E
Adder
0.29176470588235290.248
927264AC1-222 E
50/50
4.2714.271
957482AF2-042 E
50/50
57.29557.295
934621AD1-088 C
50/50
16.77816.778
935172AD1-152 E
50/50
7.5637.563
942461AE2-259 C
Adder
-11.085882352941177-9.423
960081AF2-299 C
Adder
0.58352941176470590.496
3151531CLOVER1
50/50
19.51919.519
936261AD2-033 C
Adder
5.2729411764705894.482
3151631KERR 6
50/50
1.1131.113
962562AG1-105 E
50/50
6.1616.161
316248AF1-058 C
50/50
0.3490.349
946281AF1-292 C
Adder
0.48352941176470590.411
960082AF2-299 E
Adder
0.38941176470588240.331
3151541CLOVER2
50/50
19.33819.338
964241AG1-285 C
50/50
16.2716.27
316034AC1-036 C
50/50
0.1660.166
962561AG1-105 C
50/50
9.2429.242
937482AD2-202 E
50/50
1.621.62
3151581KERR 1
50/50
0.3970.397
3151601KERR 3
50/50
1.1131.113
3152661PLYWOOD A
50/50
1.3061.306
941011AE2-092 C
Adder
-7.384705882352941-6.277
966621AG1-532 C
Adder
0.437647058823529440.372
3147223TWITTYS
50/50
0.6740.674
959312AF2-222 E
Adder
6.66588235294117755.666
924022AB2-043 E O1
50/50
5.1075.107
316003AC1-222 C
50/50
1.0461.046
926024AC1-080 E
50/50
0.8510.851
316239AB2-077 C O1
50/50
0.3240.324
935171AD1-152 C
50/50
1.8391.839
964791AG1-342 C
50/50
3.7243.724
925997AC1-075 E
50/50
2.5662.566
924302AB2-077 E O1
50/50
1.321.32
3151621KERR 5
50/50
1.1131.113
316222AC1-221 C
50/50
1.3041.304
942752AE2-291 E
50/50
4.2094.209
957481AF2-042 C
50/50
85.94285.942
316088AB2-174 E
Adder
2.0917647058823531.778
923994AB2-040_E
Adder
1.99764705882352931.698
924322AB2-079 E O1
50/50
1.321.32
943902AF1-058 E
50/50
1.4231.423
964242AG1-285 E
50/50
10.84610.846
313527AB2-043 C
50/50
0.5090.509
924162AB2-060 E OP
50/50
3.9993.999
3151591KERR 2
50/50
1.1131.113
964792AG1-342 E
50/50
2.4822.482
932763AC2-100 E
50/50
2.2422.242
316283AC2-100 C
50/50
1.0191.019
3145723EMPORIA
Adder
0.136470588235294120.116
923573AB1-173 E OP
Adder
1.06470588235294120.905
919692AA2-053 E OP
Adder
1.31411764705882361.117
925785AC1-054 E
50/50
2.3712.371
959311AF2-222 C
Adder
9.9482352941176468.456
942751AE2-291 C
50/50
6.3136.313
3137643SOCKMAN
Adder
0.236470588235294130.201
937481AD2-202 C
50/50
0.5570.557
3151641KERR 7
50/50
1.1131.113
316205AC1-080 C
50/50
0.2470.247
316123AC1-075 C
50/50
0.740.74
925612AC1-036 E
50/50
0.6080.608
316237AB2-079 C O1
50/50
0.3240.324
924312AB2-078 E O1
50/50
1.321.32
316238AB2-078 C O1
50/50
0.3240.324
926274AC1-105 E
50/50
2.892.89
938821AE1-108 C
Adder
-8.042352941176471-6.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.6115.611
NYPJM->LTFIMP_NY
CLTF
0.2910.291
TVALTFEXP_TVA->PJM
CLTF
1.5461.546
O66PJM->LTFIMP_O-066
CMTX_NF
3.8923.892
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.2860.286
MECLTFEXP_MEC->PJM
CLTF
0.9490.949
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6471.647
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.50427.504
WECLTFEXP_WEC->PJM
CLTF
0.1510.151
LAGNLTFEXP_LAGN->PJM
CLTF
1.9781.978
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.2877.287
G-007PJM->LTFIMP_G-007
CMTX_NF
0.610.61
CPLELTFEXP_CPLE->PJM
CLTF
3.4573.457
SIGELTFEXP_SIGE->PJM
CLTF
0.0570.057

Details for 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.25 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1016.21
MW Contribution:28.36
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.15 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:985.63
MW Contribution:27.18
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
Adder
6.0952941176470595.181
316084AB2-161 E
50/50
3.213.21
316083AB2-161 C
50/50
0.3210.321
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
933982AD1-022 E
Adder
1.721.462
934622AD1-088 E
Adder
1.38117647058823521.174
934612AD1-087 E
Adder
1.1117647058823530.945
927146AC1-208 E
Adder
1.51.275
944012AF1-069 E
Adder
1.7917647058823531.523
946282AF1-292 E
Adder
0.45058823529411770.383
917512Z2-088 E OP1
Adder
1.73411764705882351.474
935162AD1-151 E
50/50
6.0156.015
938532AE1-072 E
Adder
3.07058823529411742.61
3146326AYDLETT TAP
Adder
0.455294117647058850.387
943461AF1-017 C
Adder
0.61882352941176480.526
316311AC2-079 C
Adder
2.5717647058823532.186
932596AC2-079 E
Adder
4.1964705882352953.567
917122Z2-027 E
Adder
0.457647058823529460.389
920692AA2-178 E
Adder
1.4552941176470591.237
966622AG1-532 E
Adder
0.408235294117647030.347
922923AB1-081 E OP
Adder
1.321.122
944011AF1-069 C
Adder
4.6141176470588243.922
941591AE2-156 C
Adder
6.1141176470588245.197
925332AB2-190 E
50/50
4.6914.691
944591AF1-124 C
Adder
15.08705882352941312.824
944601AF1-125 C
Adder
14.80235294117647312.582
927226AC1-216 E
Adder
4.122352941176473.504
936666AD2-085 E
Adder
2.5752941176470592.189
963041AG1-153 C
Adder
1.9482352941176471.656
938771AE1-103 C
Adder
1.11764705882352940.95
3145413WATKINS
Adder
0.26470588235294120.225
960081AF2-299 C
Adder
0.81647058823529410.694
926072AC1-086 E
Adder
4.0352941176470593.43
944582AF1-123 E
Adder
34.4258823529411829.262
944592AF1-124 E
Adder
34.55058823529411429.368
935112AD1-144 E
Adder
0.33176470588235290.282
316349AD2-085 C
Adder
1.57882352941176471.342
923832AB2-022 E
Adder
0.421176470588235260.358
963042AG1-153 E
Adder
2.92235294117647062.484
938772AE1-103 E
Adder
1.5435294117647061.312
916042Z1-036 E
Adder
9.9682352941176488.473
946281AF1-292 C
Adder
0.67529411764705880.574
960082AF2-299 E
Adder
0.54470588235294130.463
926071AC1-086 C
Adder
8.8647058823529427.535
964241AG1-285 C
Adder
3.85882352941176483.28
927021AC1-189 C
Adder
2.97529411764705862.529
924152AB2-059 E OP
Adder
1.87058823529411791.59
3150831SPRUNCA
Adder
2.6776470588235292.276
3150841SPRUNCB
Adder
2.6776470588235292.276
939412AE1-173 E
Adder
21.0235294117647117.87
941032AE2-094 E
Adder
6.3247058823529425.376
941031AE2-094 C
Adder
14.12000000000000112.002
3150801HOPHCF4
50/50
2.4192.419
3150791HOPHCF3
50/50
1.5941.594
926662AC1-147 E
Adder
0.452941176470588240.385
916192Z1-068 E
Adder
0.63294117647058830.538
957492AF2-043 E
Adder
0.49294117647058820.419
923852AB2-025 E
Adder
0.6317647058823530.537
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
934321AD1-056 C
Adder
2.3988235294117652.039
934331AD1-057 C
Adder
1.33882352941176451.138
934332AD1-057 E
Adder
0.69647058823529410.592
934322AD1-056 E
Adder
1.30117647058823541.106
927022AC1-189 E
Adder
1.48235294117647071.26
925595AC1-034 E
Adder
1.77411764705882361.508
933292AC2-141 E
Adder
3.78588235294117673.218
946262AF1-291 E
50/50
1.6321.632
3150651CHESTF6
50/50
21.89721.897
944602AF1-125 E
Adder
33.8847058823529428.802
3145506HICKORY
Adder
0.72352941176470590.615
934576AD1-082 E
50/50
2.5582.558
957871AF2-081 C
Adder
3.34117647058823542.84
943612AF1-032 E
Adder
0.320.272
940492AE2-034 E
Adder
1.09058823529411760.927
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
918492AA1-063AE OP
Adder
1.59411764705882361.355
937482AD2-202 E
Adder
0.32588235294117650.277
917332KELFORD E
Adder
0.61411764705882350.522
925122AB2-169 E
Adder
2.04352941176470631.737
316274AC1-208 C
Adder
3.3788235294117652.872
917342Z2-044 E
Adder
0.215294117647058830.183
3151311EDGECMA
Adder
5.5117647058823534.685
3143316POE
50/50
1.0861.086
939191AE1-149 C
50/50
7.1377.137
901082W1-029 E
Adder
10.9870588235294139.339
926206AC1-098 E
Adder
1.35999999999999991.156
940642AE2-051 E
Adder
4.0635294117647063.454
316132AB2-190 C
50/50
2.4122.412
919153AA1-139 E2
Adder
1.36588235294117651.161
943462AF1-017 E
Adder
1.00941176470588250.858
942341AE2-247 C
Adder
0.68470588235294120.582
958162AF2-110 E
Adder
0.82470588235294120.701
924516AB2-100 E1
Adder
1.36823529411764721.163
934512AD1-075 E
Adder
1.53411764705882361.304
934502AD1-074 E
Adder
6.1364705882352945.216
966621AG1-532 C
Adder
0.61294117647058830.521
918512AA1-065 E OP
Adder
2.04235294117647071.736
924022AB2-043 E O1
Adder
1.60117647058823541.361
918532AA1-067 E
Adder
0.251764705882352950.214
3150731STONECA
50/50
4.5124.512
932046AC2-012 E
Adder
4.4823529411764713.81
935161AD1-151 C
50/50
9.0229.022
938531AE1-072 C
Adder
5.8905882352941185.007
958161AF2-110 C
Adder
0.51764705882352950.44
3145393UNCAMP
Adder
2.3247058823529411.976
933981AD1-022 C
Adder
3.162.686
900672V4-068 E
Adder
0.136470588235294120.116
924302AB2-077 E O1
Adder
0.41176470588235290.35
942002AE2-212 E
50/50
1.4081.408
940431AE2-027 C
Adder
7.0447058823529425.988
3150771HOPHCF1
50/50
1.5941.594
944581AF1-123 C
Adder
15.03411764705882412.779
941101AE2-104 C
Adder
1.26941176470588221.079
957481AF2-042 C
Adder
17.0152941176470614.463
316088AB2-174 E
Adder
2.7588235294117652.345
316141AB2-099 E
Adder
0.095294117647058830.081
923994AB2-040_E
Adder
2.56588235294117652.181
924322AB2-079 E O1
Adder
0.41176470588235290.35
961672AG1-007 E
Adder
0.188235294117647060.16
926755AC1-161 E
Adder
3.78588235294117673.218
933291AC2-141 C
Adder
8.8694117647058827.539
3150761HOPPOLC
50/50
1.0021.002
925522AC1-027 E
Adder
0.410588235294117640.349
957872AF2-081 E
Adder
1.4317647058823531.217
3145256KINGFORK
Adder
0.357647058823529430.304
941102AE2-104 E
Adder
2.0188235294117651.716
964242AG1-285 E
Adder
2.5717647058823532.186
926214AC1-099 E
Adder
0.44941176470588240.382
932632AC2-084 E
Adder
1.20235294117647061.022
924162AB2-060 E OP
Adder
1.3117647058823531.115
316240AF1-291 C
50/50
2.4482.448
944641AF1-129 C
50/50
120.262120.262
924814AB2-134 E
Adder
6.7529411764705885.74
316381AD1-082 C
50/50
0.7330.733
919152AA1-139 E1
Adder
1.36588235294117651.161
942342AE2-247 E
Adder
0.94470588235294130.803
920042AA2-088 E OP
Adder
4.0811764705882353.469
934511AD1-075 C
Adder
3.01411764705882362.562
934521AD1-076 C
Adder
4.377647058823533.721
3145723EMPORIA
Adder
0.185882352941176470.158
923573AB1-173 E OP
Adder
1.36823529411764721.163
919692AA2-053 E OP
Adder
1.64941176470588241.402
925785AC1-054 E
Adder
1.2082352941176471.027
316263AC1-034 C
Adder
2.3517647058823531.999
939411AE1-173 C
Adder
31.5352941176470626.805
940432AE2-027 E
Adder
4.6964705882352943.992
934012AD1-025 E
Adder
5.3364705882352944.536
913392Y1-086 E
Adder
0.74470588235294120.633
3137643SOCKMAN
Adder
0.288235294117647030.245
919710AA2-057 E
Adder
1.44823529411764731.231
942001AE2-212 C
50/50
2.1112.111
939192AE1-149 E
50/50
4.7584.758
3150781HOPHCF2
50/50
1.5941.594
934065AD1-033 E
Adder
1.6670588235294121.417
939312AE1-162 E
Adder
0.5717647058823530.486
937226AE2-253 E
Adder
1.9482352941176471.656
924517AB2-100 E2
Adder
1.36823529411764721.163
934501AD1-074 C
Adder
12.05529411764705810.247
957482AF2-042 E
Adder
11.3435294117647069.642
934621AD1-088 C
Adder
2.86941176470588262.439
935172AD1-152 E
Adder
1.6435294117647061.397
961671AG1-007 C
Adder
0.332941176470588240.283
961611AG1-000B C
Adder
7.342352941176476.241
940541AE2-040 C
Adder
1.56117647058823541.327
940482AE2-033 E
Adder
5.8329411764705884.958
940481AE2-033 C
Adder
8.6517647058823537.354
923263AB1-132 E OP
Adder
2.582.193
924312AB2-078 E O1
Adder
0.41176470588235290.35
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
NYPJM->LTFIMP_NY
CLTF
0.4360.436
TVALTFEXP_TVA->PJM
CLTF
1.561.56
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
WECLTFEXP_WEC->PJM
CLTF
0.140.14
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.97 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:701.29
MW Contribution:42.89
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.14 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:748.75
MW Contribution:42.58
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
50/50
30.2830.28
934622AD1-088 E
50/50
2.9962.996
934612AD1-087 E
Adder
1.8235294117647061.55
3151931BEARGRDN S1
50/50
21.41521.415
936262AD2-033 E
50/50
8.1968.196
958211AF2-115 C
50/50
2.892.89
941012AE2-092 E
50/50
15.99615.996
316131AB2-060 C
50/50
1.0471.047
3138533PONTONDP
50/50
0.8560.856
3147133PAMPLIN
50/50
1.3571.357
316322AB2-045 C
50/50
0.7820.782
927264AC1-222 E
Adder
1.91647058823529411.629
958132AF2-107 E
50/50
2.5922.592
957482AF2-042 E
Adder
17.15411764705882214.581
934621AD1-088 C
50/50
6.2236.223
935172AD1-152 E
Adder
2.64470588235294152.248
946301AF1-294 C
50/50
4.7534.753
942461AE2-259 C
50/50
16.45516.455
938822AE1-108 E
50/50
15.78715.787
936261AD2-033 C
50/50
12.29412.294
3144293JTRSVLE
50/50
0.5320.532
961791AG1-021 C
50/50
2.3122.312
962562AG1-105 E
Adder
3.4647058823529412.945
924032AB2-045 E
50/50
3.5043.504
964241AG1-285 C
50/50
9.3069.306
316034AC1-036 C
50/50
0.2260.226
958212AF2-115 E
50/50
2.4622.462
962561AG1-105 C
Adder
5.197647058823534.418
937482AD2-202 E
Adder
0.53411764705882360.454
961792AG1-021 E
50/50
1.971.97
3151921BEARGRDN G2
50/50
16.55416.554
941011AE2-092 C
50/50
23.99423.994
3147223TWITTYS
50/50
0.9190.919
959312AF2-222 E
50/50
11.25511.255
924022AB2-043 E O1
50/50
3.5343.534
316239AB2-077 C O1
50/50
0.2190.219
942462AE2-259 E
50/50
10.9710.97
964791AG1-342 C
Adder
2.00705882352941161.706
924302AB2-077 E O1
50/50
0.8940.894
958131AF2-107 C
50/50
4.7314.731
957481AF2-042 C
Adder
25.7317647058823521.872
924322AB2-079 E O1
50/50
0.8940.894
946302AF1-294 E
50/50
4.0254.025
943902AF1-058 E
Adder
0.62352941176470590.53
964242AG1-285 E
50/50
6.2046.204
313527AB2-043 C
50/50
0.3520.352
924162AB2-060 E OP
50/50
3.0163.016
964792AG1-342 E
Adder
1.33764705882352941.137
3151911BEARGRDN G1
50/50
16.55416.554
925785AC1-054 E
Adder
1.3870588235294121.179
959311AF2-222 C
50/50
16.79916.799
933502AC2-165 E
50/50
22.78922.789
925612AC1-036 E
50/50
0.8290.829
316237AB2-079 C O1
50/50
0.2190.219
924312AB2-078 E O1
50/50
0.8940.894
316238AB2-078 C O1
50/50
0.2190.219
926274AC1-105 E
Adder
1.40941176470588241.198
938821AE1-108 C
50/50
33.08633.086
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4071.407
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6880.688
CPLELTFEXP_CPLE->PJM
CLTF
2.7182.718
SIGELTFEXP_SIGE->PJM
CLTF
0.020.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.0933.093
NYPJM->LTFIMP_NY
CLTF
0.3520.352
TVALTFEXP_TVA->PJM
CLTF
0.9770.977
O66PJM->LTFIMP_O-066
CMTX_NF
4.4054.405
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
MECLTFEXP_MEC->PJM
CLTF
0.3740.374
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.2941.294
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.18821.188
WECLTFEXP_WEC->PJM
CLTF
0.0360.036
LAGNLTFEXP_LAGN->PJM
CLTF
1.2621.262

Details for 6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.24 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:618.61
MW Contribution:143.24
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.66 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:649.58
MW Contribution:164.63
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
Adder
-4.488235294117647-3.815
934622AD1-088 E
50/50
8.0788.078
934611AD1-087 C
50/50
1.9191.919
934612AD1-087 E
50/50
5.5365.536
3151611KERR 4
50/50
1.1131.113
927255AC1-221 E
50/50
3.413.41
936262AD2-033 E
Adder
3.5152941176470592.988
946282AF1-292 E
Adder
0.32235294117647060.274
316129AC1-054 C
50/50
0.8410.841
316131AB2-060 C
50/50
1.3891.389
316118AC1-105 C
50/50
0.9880.988
966622AG1-532 E
Adder
0.29176470588235290.248
927264AC1-222 E
50/50
4.2714.271
960081AF2-299 C
Adder
0.58352941176470590.496
957482AF2-042 E
50/50
57.29557.295
934621AD1-088 C
50/50
16.77816.778
935172AD1-152 E
50/50
7.5637.563
942461AE2-259 C
Adder
-11.085882352941177-9.423
3151531CLOVER1
50/50
19.51919.519
936261AD2-033 C
Adder
5.2729411764705894.482
3151631KERR 6
50/50
1.1131.113
962562AG1-105 E
50/50
6.1616.161
316248AF1-058 C
50/50
0.3490.349
946281AF1-292 C
Adder
0.48352941176470590.411
960082AF2-299 E
Adder
0.38941176470588240.331
3151541CLOVER2
50/50
19.33819.338
964241AG1-285 C
50/50
16.2716.27
316034AC1-036 C
50/50
0.1660.166
962561AG1-105 C
50/50
9.2429.242
937482AD2-202 E
50/50
1.621.62
3151581KERR 1
50/50
0.3970.397
3151601KERR 3
50/50
1.1131.113
3152661PLYWOOD A
50/50
1.3061.306
941011AE2-092 C
Adder
-7.384705882352941-6.277
966621AG1-532 C
Adder
0.437647058823529440.372
3147223TWITTYS
50/50
0.6740.674
959312AF2-222 E
Adder
6.66588235294117755.666
924022AB2-043 E O1
50/50
5.1075.107
316003AC1-222 C
50/50
1.0461.046
926024AC1-080 E
50/50
0.8510.851
316239AB2-077 C O1
50/50
0.3240.324
935171AD1-152 C
50/50
1.8391.839
964791AG1-342 C
50/50
3.7243.724
925997AC1-075 E
50/50
2.5662.566
924302AB2-077 E O1
50/50
1.321.32
3151621KERR 5
50/50
1.1131.113
316222AC1-221 C
50/50
1.3041.304
942752AE2-291 E
50/50
4.2094.209
957481AF2-042 C
50/50
85.94285.942
316088AB2-174 E
Adder
2.0917647058823531.778
923994AB2-040_E
Adder
1.99764705882352931.698
924322AB2-079 E O1
50/50
1.321.32
943902AF1-058 E
50/50
1.4231.423
964242AG1-285 E
50/50
10.84610.846
313527AB2-043 C
50/50
0.5090.509
924162AB2-060 E OP
50/50
3.9993.999
3151591KERR 2
50/50
1.1131.113
964792AG1-342 E
50/50
2.4822.482
932763AC2-100 E
50/50
2.2422.242
316283AC2-100 C
50/50
1.0191.019
3145723EMPORIA
Adder
0.136470588235294120.116
923573AB1-173 E OP
Adder
1.06470588235294120.905
919692AA2-053 E OP
Adder
1.31411764705882361.117
925785AC1-054 E
50/50
2.3712.371
959311AF2-222 C
Adder
9.9482352941176468.456
942751AE2-291 C
50/50
6.3136.313
3137643SOCKMAN
Adder
0.236470588235294130.201
937481AD2-202 C
50/50
0.5570.557
3151641KERR 7
50/50
1.1131.113
316205AC1-080 C
50/50
0.2470.247
316123AC1-075 C
50/50
0.740.74
925612AC1-036 E
50/50
0.6080.608
316237AB2-079 C O1
50/50
0.3240.324
924312AB2-078 E O1
50/50
1.321.32
316238AB2-078 C O1
50/50
0.3240.324
926274AC1-105 E
50/50
2.892.89
938821AE1-108 C
Adder
-8.042352941176471-6.836
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.50427.504
WECLTFEXP_WEC->PJM
CLTF
0.1510.151
LAGNLTFEXP_LAGN->PJM
CLTF
1.9781.978
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.2877.287
G-007PJM->LTFIMP_G-007
CMTX_NF
0.610.61
CPLELTFEXP_CPLE->PJM
CLTF
3.4573.457
SIGELTFEXP_SIGE->PJM
CLTF
0.0570.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.6115.611
NYPJM->LTFIMP_NY
CLTF
0.2910.291
TVALTFEXP_TVA->PJM
CLTF
1.5461.546
O66PJM->LTFIMP_O-066
CMTX_NF
3.8923.892
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.2860.286
MECLTFEXP_MEC->PJM
CLTF
0.9490.949
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6471.647

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.64 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:718.91
MW Contribution:42.89
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.82 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:766.43
MW Contribution:42.58
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
50/50
30.2830.28
934622AD1-088 E
50/50
2.9962.996
934612AD1-087 E
Adder
1.8235294117647061.55
3151931BEARGRDN S1
50/50
21.41521.415
936262AD2-033 E
50/50
8.1968.196
958211AF2-115 C
50/50
2.892.89
941012AE2-092 E
50/50
15.99615.996
3147133PAMPLIN
50/50
1.3571.357
316322AB2-045 C
50/50
0.7820.782
927264AC1-222 E
Adder
1.91647058823529411.629
958132AF2-107 E
50/50
2.5922.592
316131AB2-060 C
50/50
1.0471.047
3138533PONTONDP
50/50
0.8560.856
936261AD2-033 C
50/50
12.29412.294
3144293JTRSVLE
50/50
0.5320.532
961791AG1-021 C
50/50
2.3122.312
962562AG1-105 E
Adder
3.4647058823529412.945
924032AB2-045 E
50/50
3.5043.504
957482AF2-042 E
Adder
17.15411764705882214.581
934621AD1-088 C
50/50
6.2236.223
935172AD1-152 E
Adder
2.64470588235294152.248
946301AF1-294 C
50/50
4.7534.753
942461AE2-259 C
50/50
16.45516.455
938822AE1-108 E
50/50
15.78715.787
937482AD2-202 E
Adder
0.53411764705882360.454
961792AG1-021 E
50/50
1.971.97
3151921BEARGRDN G2
50/50
16.55416.554
941011AE2-092 C
50/50
23.99423.994
964241AG1-285 C
50/50
9.3069.306
316034AC1-036 C
50/50
0.2260.226
958212AF2-115 E
50/50
2.4622.462
962561AG1-105 C
Adder
5.197647058823534.418
3147223TWITTYS
50/50
0.9190.919
959312AF2-222 E
50/50
11.25511.255
924022AB2-043 E O1
50/50
3.5343.534
316239AB2-077 C O1
50/50
0.2190.219
942462AE2-259 E
50/50
10.9710.97
964791AG1-342 C
Adder
2.00705882352941161.706
924302AB2-077 E O1
50/50
0.8940.894
958131AF2-107 C
50/50
4.7314.731
957481AF2-042 C
Adder
25.7317647058823521.872
924322AB2-079 E O1
50/50
0.8940.894
946302AF1-294 E
50/50
4.0254.025
943902AF1-058 E
Adder
0.62352941176470590.53
964242AG1-285 E
50/50
6.2046.204
313527AB2-043 C
50/50
0.3520.352
924162AB2-060 E OP
50/50
3.0163.016
964792AG1-342 E
Adder
1.33764705882352941.137
3151911BEARGRDN G1
50/50
16.55416.554
925785AC1-054 E
Adder
1.3870588235294121.179
959311AF2-222 C
50/50
16.79916.799
933502AC2-165 E
50/50
22.78922.789
925612AC1-036 E
50/50
0.8290.829
316237AB2-079 C O1
50/50
0.2190.219
924312AB2-078 E O1
50/50
0.8940.894
316238AB2-078 C O1
50/50
0.2190.219
926274AC1-105 E
Adder
1.40941176470588241.198
938821AE1-108 C
50/50
33.08633.086
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4071.407
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6880.688
CPLELTFEXP_CPLE->PJM
CLTF
2.7182.718
SIGELTFEXP_SIGE->PJM
CLTF
0.020.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.0933.093
NYPJM->LTFIMP_NY
CLTF
0.3520.352
TVALTFEXP_TVA->PJM
CLTF
0.9770.977
O66PJM->LTFIMP_O-066
CMTX_NF
4.4054.405
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
MECLTFEXP_MEC->PJM
CLTF
0.3740.374
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.2941.294
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.18821.188
WECLTFEXP_WEC->PJM
CLTF
0.0360.036
LAGNLTFEXP_LAGN->PJM
CLTF
1.2621.262

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.38 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:677.52
MW Contribution:42.89
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.53 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:724.84
MW Contribution:42.58
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
50/50
30.2830.28
934622AD1-088 E
50/50
2.9962.996
934612AD1-087 E
Adder
1.8235294117647061.55
3151931BEARGRDN S1
50/50
21.41521.415
316131AB2-060 C
50/50
1.0471.047
3138533PONTONDP
50/50
0.8560.856
3147133PAMPLIN
50/50
1.3571.357
316322AB2-045 C
50/50
0.7820.782
927264AC1-222 E
Adder
1.91647058823529411.629
958132AF2-107 E
50/50
2.5922.592
936261AD2-033 C
50/50
12.29412.294
3144293JTRSVLE
50/50
0.5320.532
961791AG1-021 C
50/50
2.3122.312
962562AG1-105 E
Adder
3.4647058823529412.945
924032AB2-045 E
50/50
3.5043.504
964241AG1-285 C
50/50
9.3069.306
316034AC1-036 C
50/50
0.2260.226
958212AF2-115 E
50/50
2.4622.462
962561AG1-105 C
Adder
5.197647058823534.418
936262AD2-033 E
50/50
8.1968.196
958211AF2-115 C
50/50
2.892.89
941012AE2-092 E
50/50
15.99615.996
937482AD2-202 E
Adder
0.53411764705882360.454
961792AG1-021 E
50/50
1.971.97
3151921BEARGRDN G2
50/50
16.55416.554
941011AE2-092 C
50/50
23.99423.994
3147223TWITTYS
50/50
0.9190.919
959312AF2-222 E
50/50
11.25511.255
924022AB2-043 E O1
50/50
3.5343.534
316239AB2-077 C O1
50/50
0.2190.219
942462AE2-259 E
50/50
10.9710.97
964791AG1-342 C
Adder
2.00705882352941161.706
957482AF2-042 E
Adder
17.15411764705882214.581
934621AD1-088 C
50/50
6.2236.223
935172AD1-152 E
Adder
2.64470588235294152.248
946301AF1-294 C
50/50
4.7534.753
942461AE2-259 C
50/50
16.45516.455
938822AE1-108 E
50/50
15.78715.787
924302AB2-077 E O1
50/50
0.8940.894
958131AF2-107 C
50/50
4.7314.731
957481AF2-042 C
Adder
25.7317647058823521.872
924322AB2-079 E O1
50/50
0.8940.894
946302AF1-294 E
50/50
4.0254.025
943902AF1-058 E
Adder
0.62352941176470590.53
964242AG1-285 E
50/50
6.2046.204
313527AB2-043 C
50/50
0.3520.352
924162AB2-060 E OP
50/50
3.0163.016
964792AG1-342 E
Adder
1.33764705882352941.137
3151911BEARGRDN G1
50/50
16.55416.554
925785AC1-054 E
Adder
1.3870588235294121.179
959311AF2-222 C
50/50
16.79916.799
933502AC2-165 E
50/50
22.78922.789
925612AC1-036 E
50/50
0.8290.829
316237AB2-079 C O1
50/50
0.2190.219
924312AB2-078 E O1
50/50
0.8940.894
316238AB2-078 C O1
50/50
0.2190.219
926274AC1-105 E
Adder
1.40941176470588241.198
938821AE1-108 C
50/50
33.08633.086
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
MECLTFEXP_MEC->PJM
CLTF
0.3740.374
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.2941.294
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.18821.188
WECLTFEXP_WEC->PJM
CLTF
0.0360.036
LAGNLTFEXP_LAGN->PJM
CLTF
1.2621.262
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4071.407
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6880.688
CPLELTFEXP_CPLE->PJM
CLTF
2.7182.718
SIGELTFEXP_SIGE->PJM
CLTF
0.020.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.0933.093
NYPJM->LTFIMP_NY
CLTF
0.3520.352
TVALTFEXP_TVA->PJM
CLTF
0.9770.977
O66PJM->LTFIMP_O-066
CMTX_NF
4.4054.405

Details for 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:107.58 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:614.81
MW Contribution:143.24
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.99 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:645.76
MW Contribution:164.63
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
Adder
-4.488235294117647-3.815
934622AD1-088 E
50/50
8.0788.078
934611AD1-087 C
50/50
1.9191.919
934612AD1-087 E
50/50
5.5365.536
3151611KERR 4
50/50
1.1131.113
927255AC1-221 E
50/50
3.413.41
936262AD2-033 E
Adder
3.5152941176470592.988
946282AF1-292 E
Adder
0.32235294117647060.274
316129AC1-054 C
50/50
0.8410.841
316131AB2-060 C
50/50
1.3891.389
316118AC1-105 C
50/50
0.9880.988
966622AG1-532 E
Adder
0.29176470588235290.248
927264AC1-222 E
50/50
4.2714.271
957482AF2-042 E
50/50
57.29557.295
934621AD1-088 C
50/50
16.77816.778
935172AD1-152 E
50/50
7.5637.563
942461AE2-259 C
Adder
-11.085882352941177-9.423
960081AF2-299 C
Adder
0.58352941176470590.496
3151531CLOVER1
50/50
19.51919.519
946281AF1-292 C
Adder
0.48352941176470590.411
960082AF2-299 E
Adder
0.38941176470588240.331
3151541CLOVER2
50/50
19.33819.338
964241AG1-285 C
50/50
16.2716.27
316034AC1-036 C
50/50
0.1660.166
962561AG1-105 C
50/50
9.2429.242
936261AD2-033 C
Adder
5.2729411764705894.482
3151631KERR 6
50/50
1.1131.113
962562AG1-105 E
50/50
6.1616.161
316248AF1-058 C
50/50
0.3490.349
937482AD2-202 E
50/50
1.621.62
3151581KERR 1
50/50
0.3970.397
3151601KERR 3
50/50
1.1131.113
3152661PLYWOOD A
50/50
1.3061.306
941011AE2-092 C
Adder
-7.384705882352941-6.277
966621AG1-532 C
Adder
0.437647058823529440.372
3147223TWITTYS
50/50
0.6740.674
959312AF2-222 E
Adder
6.66588235294117755.666
924022AB2-043 E O1
50/50
5.1075.107
316003AC1-222 C
50/50
1.0461.046
926024AC1-080 E
50/50
0.8510.851
316239AB2-077 C O1
50/50
0.3240.324
935171AD1-152 C
50/50
1.8391.839
964791AG1-342 C
50/50
3.7243.724
925997AC1-075 E
50/50
2.5662.566
924302AB2-077 E O1
50/50
1.321.32
3151621KERR 5
50/50
1.1131.113
316222AC1-221 C
50/50
1.3041.304
942752AE2-291 E
50/50
4.2094.209
957481AF2-042 C
50/50
85.94285.942
316088AB2-174 E
Adder
2.0917647058823531.778
923994AB2-040_E
Adder
1.99764705882352931.698
924322AB2-079 E O1
50/50
1.321.32
943902AF1-058 E
50/50
1.4231.423
964242AG1-285 E
50/50
10.84610.846
313527AB2-043 C
50/50
0.5090.509
924162AB2-060 E OP
50/50
3.9993.999
3151591KERR 2
50/50
1.1131.113
964792AG1-342 E
50/50
2.4822.482
932763AC2-100 E
50/50
2.2422.242
316283AC2-100 C
50/50
1.0191.019
3145723EMPORIA
Adder
0.136470588235294120.116
923573AB1-173 E OP
Adder
1.06470588235294120.905
919692AA2-053 E OP
Adder
1.31411764705882361.117
925785AC1-054 E
50/50
2.3712.371
959311AF2-222 C
Adder
9.9482352941176468.456
942751AE2-291 C
50/50
6.3136.313
3137643SOCKMAN
Adder
0.236470588235294130.201
937481AD2-202 C
50/50
0.5570.557
3151641KERR 7
50/50
1.1131.113
316205AC1-080 C
50/50
0.2470.247
316123AC1-075 C
50/50
0.740.74
925612AC1-036 E
50/50
0.6080.608
316237AB2-079 C O1
50/50
0.3240.324
924312AB2-078 E O1
50/50
1.321.32
316238AB2-078 C O1
50/50
0.3240.324
926274AC1-105 E
50/50
2.892.89
938821AE1-108 C
Adder
-8.042352941176471-6.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.2860.286
MECLTFEXP_MEC->PJM
CLTF
0.9490.949
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6471.647
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.50427.504
WECLTFEXP_WEC->PJM
CLTF
0.1510.151
LAGNLTFEXP_LAGN->PJM
CLTF
1.9781.978
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.2877.287
G-007PJM->LTFIMP_G-007
CMTX_NF
0.610.61
CPLELTFEXP_CPLE->PJM
CLTF
3.4573.457
SIGELTFEXP_SIGE->PJM
CLTF
0.0570.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.6115.611
NYPJM->LTFIMP_NY
CLTF
0.2910.291
TVALTFEXP_TVA->PJM
CLTF
1.5461.546
O66PJM->LTFIMP_O-066
CMTX_NF
3.8923.892

Details for 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.2 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1015.68
MW Contribution:28.36
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.1 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:985.14
MW Contribution:27.18
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
Adder
6.0952941176470595.181
316084AB2-161 E
50/50
3.213.21
316083AB2-161 C
50/50
0.3210.321
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
933982AD1-022 E
Adder
1.721.462
934622AD1-088 E
Adder
1.38117647058823521.174
934612AD1-087 E
Adder
1.1117647058823530.945
927146AC1-208 E
Adder
1.51.275
944012AF1-069 E
Adder
1.7917647058823531.523
946282AF1-292 E
Adder
0.45058823529411770.383
917512Z2-088 E OP1
Adder
1.73411764705882351.474
935162AD1-151 E
50/50
6.0156.015
938532AE1-072 E
Adder
3.07058823529411742.61
3146326AYDLETT TAP
Adder
0.455294117647058850.387
943461AF1-017 C
Adder
0.61882352941176480.526
316311AC2-079 C
Adder
2.5717647058823532.186
932596AC2-079 E
Adder
4.1964705882352953.567
917122Z2-027 E
Adder
0.457647058823529460.389
920692AA2-178 E
Adder
1.4552941176470591.237
966622AG1-532 E
Adder
0.408235294117647030.347
922923AB1-081 E OP
Adder
1.321.122
944011AF1-069 C
Adder
4.6141176470588243.922
941591AE2-156 C
Adder
6.1141176470588245.197
925332AB2-190 E
50/50
4.6914.691
944591AF1-124 C
Adder
15.08705882352941312.824
944601AF1-125 C
Adder
14.80235294117647312.582
927226AC1-216 E
Adder
4.122352941176473.504
936666AD2-085 E
Adder
2.5752941176470592.189
963041AG1-153 C
Adder
1.9482352941176471.656
938771AE1-103 C
Adder
1.11764705882352940.95
3145413WATKINS
Adder
0.26470588235294120.225
960081AF2-299 C
Adder
0.81647058823529410.694
926072AC1-086 E
Adder
4.0352941176470593.43
944582AF1-123 E
Adder
34.4258823529411829.262
944592AF1-124 E
Adder
34.55058823529411429.368
935112AD1-144 E
Adder
0.33176470588235290.282
316349AD2-085 C
Adder
1.57882352941176471.342
923832AB2-022 E
Adder
0.421176470588235260.358
963042AG1-153 E
Adder
2.92235294117647062.484
938772AE1-103 E
Adder
1.5435294117647061.312
916042Z1-036 E
Adder
9.9682352941176488.473
946281AF1-292 C
Adder
0.67529411764705880.574
960082AF2-299 E
Adder
0.54470588235294130.463
926071AC1-086 C
Adder
8.8647058823529427.535
964241AG1-285 C
Adder
3.85882352941176483.28
927021AC1-189 C
Adder
2.97529411764705862.529
924152AB2-059 E OP
Adder
1.87058823529411791.59
3150831SPRUNCA
Adder
2.6776470588235292.276
3150841SPRUNCB
Adder
2.6776470588235292.276
939412AE1-173 E
Adder
21.0235294117647117.87
941032AE2-094 E
Adder
6.3247058823529425.376
941031AE2-094 C
Adder
14.12000000000000112.002
3150801HOPHCF4
50/50
2.4192.419
3150791HOPHCF3
50/50
1.5941.594
926662AC1-147 E
Adder
0.452941176470588240.385
916192Z1-068 E
Adder
0.63294117647058830.538
957492AF2-043 E
Adder
0.49294117647058820.419
923852AB2-025 E
Adder
0.6317647058823530.537
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
934321AD1-056 C
Adder
2.3988235294117652.039
934331AD1-057 C
Adder
1.33882352941176451.138
934332AD1-057 E
Adder
0.69647058823529410.592
934322AD1-056 E
Adder
1.30117647058823541.106
927022AC1-189 E
Adder
1.48235294117647071.26
925595AC1-034 E
Adder
1.77411764705882361.508
933292AC2-141 E
Adder
3.78588235294117673.218
946262AF1-291 E
50/50
1.6321.632
3150651CHESTF6
50/50
21.89721.897
944602AF1-125 E
Adder
33.8847058823529428.802
3145506HICKORY
Adder
0.72352941176470590.615
934576AD1-082 E
50/50
2.5582.558
957871AF2-081 C
Adder
3.34117647058823542.84
943612AF1-032 E
Adder
0.320.272
940492AE2-034 E
Adder
1.09058823529411760.927
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
918492AA1-063AE OP
Adder
1.59411764705882361.355
937482AD2-202 E
Adder
0.32588235294117650.277
917332KELFORD E
Adder
0.61411764705882350.522
925122AB2-169 E
Adder
2.04352941176470631.737
316274AC1-208 C
Adder
3.3788235294117652.872
917342Z2-044 E
Adder
0.215294117647058830.183
3151311EDGECMA
Adder
5.5117647058823534.685
3143316POE
50/50
1.0861.086
939191AE1-149 C
50/50
7.1377.137
901082W1-029 E
Adder
10.9870588235294139.339
926206AC1-098 E
Adder
1.35999999999999991.156
940642AE2-051 E
Adder
4.0635294117647063.454
316132AB2-190 C
50/50
2.4122.412
919153AA1-139 E2
Adder
1.36588235294117651.161
943462AF1-017 E
Adder
1.00941176470588250.858
942341AE2-247 C
Adder
0.68470588235294120.582
958162AF2-110 E
Adder
0.82470588235294120.701
924516AB2-100 E1
Adder
1.36823529411764721.163
934512AD1-075 E
Adder
1.53411764705882361.304
934502AD1-074 E
Adder
6.1364705882352945.216
966621AG1-532 C
Adder
0.61294117647058830.521
918512AA1-065 E OP
Adder
2.04235294117647071.736
924022AB2-043 E O1
Adder
1.60117647058823541.361
918532AA1-067 E
Adder
0.251764705882352950.214
3150731STONECA
50/50
4.5124.512
932046AC2-012 E
Adder
4.4823529411764713.81
935161AD1-151 C
50/50
9.0229.022
938531AE1-072 C
Adder
5.8905882352941185.007
958161AF2-110 C
Adder
0.51764705882352950.44
3145393UNCAMP
Adder
2.3247058823529411.976
933981AD1-022 C
Adder
3.162.686
900672V4-068 E
Adder
0.136470588235294120.116
924302AB2-077 E O1
Adder
0.41176470588235290.35
942002AE2-212 E
50/50
1.4081.408
940431AE2-027 C
Adder
7.0447058823529425.988
3150771HOPHCF1
50/50
1.5941.594
944581AF1-123 C
Adder
15.03411764705882412.779
941101AE2-104 C
Adder
1.26941176470588221.079
957481AF2-042 C
Adder
17.0152941176470614.463
316088AB2-174 E
Adder
2.7588235294117652.345
316141AB2-099 E
Adder
0.095294117647058830.081
923994AB2-040_E
Adder
2.56588235294117652.181
924322AB2-079 E O1
Adder
0.41176470588235290.35
961672AG1-007 E
Adder
0.188235294117647060.16
926755AC1-161 E
Adder
3.78588235294117673.218
933291AC2-141 C
Adder
8.8694117647058827.539
3150761HOPPOLC
50/50
1.0021.002
925522AC1-027 E
Adder
0.410588235294117640.349
957872AF2-081 E
Adder
1.4317647058823531.217
3145256KINGFORK
Adder
0.357647058823529430.304
941102AE2-104 E
Adder
2.0188235294117651.716
964242AG1-285 E
Adder
2.5717647058823532.186
926214AC1-099 E
Adder
0.44941176470588240.382
932632AC2-084 E
Adder
1.20235294117647061.022
924162AB2-060 E OP
Adder
1.3117647058823531.115
316240AF1-291 C
50/50
2.4482.448
944641AF1-129 C
50/50
120.262120.262
924814AB2-134 E
Adder
6.7529411764705885.74
316381AD1-082 C
50/50
0.7330.733
919152AA1-139 E1
Adder
1.36588235294117651.161
942342AE2-247 E
Adder
0.94470588235294130.803
920042AA2-088 E OP
Adder
4.0811764705882353.469
934511AD1-075 C
Adder
3.01411764705882362.562
934521AD1-076 C
Adder
4.377647058823533.721
3145723EMPORIA
Adder
0.185882352941176470.158
923573AB1-173 E OP
Adder
1.36823529411764721.163
919692AA2-053 E OP
Adder
1.64941176470588241.402
925785AC1-054 E
Adder
1.2082352941176471.027
316263AC1-034 C
Adder
2.3517647058823531.999
939411AE1-173 C
Adder
31.5352941176470626.805
940432AE2-027 E
Adder
4.6964705882352943.992
934012AD1-025 E
Adder
5.3364705882352944.536
913392Y1-086 E
Adder
0.74470588235294120.633
3137643SOCKMAN
Adder
0.288235294117647030.245
919710AA2-057 E
Adder
1.44823529411764731.231
942001AE2-212 C
50/50
2.1112.111
939192AE1-149 E
50/50
4.7584.758
3150781HOPHCF2
50/50
1.5941.594
934065AD1-033 E
Adder
1.6670588235294121.417
939312AE1-162 E
Adder
0.5717647058823530.486
937226AE2-253 E
Adder
1.9482352941176471.656
924517AB2-100 E2
Adder
1.36823529411764721.163
934501AD1-074 C
Adder
12.05529411764705810.247
957482AF2-042 E
Adder
11.3435294117647069.642
934621AD1-088 C
Adder
2.86941176470588262.439
935172AD1-152 E
Adder
1.6435294117647061.397
961671AG1-007 C
Adder
0.332941176470588240.283
961611AG1-000B C
Adder
7.342352941176476.241
940541AE2-040 C
Adder
1.56117647058823541.327
940482AE2-033 E
Adder
5.8329411764705884.958
940481AE2-033 C
Adder
8.6517647058823537.354
923263AB1-132 E OP
Adder
2.582.193
924312AB2-078 E O1
Adder
0.41176470588235290.35
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
NYPJM->LTFIMP_NY
CLTF
0.4360.436
TVALTFEXP_TVA->PJM
CLTF
1.561.56
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
WECLTFEXP_WEC->PJM
CLTF
0.140.14
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.13 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3353.36
MW Contribution:116.57
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3493.11
MW Contribution:115.31
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
50/50
26.11526.115
316084AB2-161 E
Adder
5.26941176470588254.479
3145946PLYMOUTH TP
Adder
0.364705882352941160.31
933982AD1-022 E
Adder
5.3847058823529414.577
934622AD1-088 E
50/50
5.5555.555
934611AD1-087 C
50/50
1.5661.566
934612AD1-087 E
50/50
4.5174.517
927146AC1-208 E
Adder
4.5541176470588243.871
927255AC1-221 E
Adder
4.1411764705882363.52
944012AF1-069 E
50/50
7.7257.725
316315AB2-025 C
50/50
0.4880.488
946282AF1-292 E
50/50
1.1981.198
3138533PONTONDP
Adder
0.60352941176470590.513
917512Z2-088 E OP1
Adder
5.5247058823529414.696
938532AE1-072 E
50/50
10.34610.346
3146326AYDLETT TAP
50/50
1.5311.531
943461AF1-017 C
Adder
1.40235294117647061.192
316311AC2-079 C
Adder
5.9964705882352955.097
932596AC2-079 E
Adder
9.7835294117647078.316
3152431Z1-086 GT3
50/50
15.81115.811
3152441Z1-086 ST
50/50
27.53227.532
917122Z2-027 E
50/50
1.5121.512
920692AA2-178 E
Adder
4.6352941176470593.94
966622AG1-532 E
50/50
1.0851.085
3147133PAMPLIN
Adder
0.89882352941176480.764
922923AB1-081 E OP
Adder
4.20470588235294153.574
927264AC1-222 E
Adder
4.3282352941176473.679
944011AF1-069 C
50/50
19.88619.886
3151091ELIZAR2
50/50
3.4943.494
3151081ELIZAR1
50/50
3.5563.556
941591AE2-156 C
50/50
19.83519.835
944591AF1-124 C
50/50
51.55751.557
944601AF1-125 C
50/50
50.58350.583
316316AC1-027 C
50/50
0.3530.353
936666AD2-085 E
Adder
5.8329411764705884.958
963041AG1-153 C
50/50
8.3218.321
938771AE1-103 C
Adder
3.24823529411764732.761
3145413WATKINS
Adder
0.7717647058823530.656
960081AF2-299 C
50/50
2.1712.171
926072AC1-086 E
Adder
10.9894117647058819.341
3151531CLOVER1
50/50
15.90415.904
936261AD2-033 C
Adder
13.51176470588235311.485
961791AG1-021 C
Adder
1.63058823529411771.386
962562AG1-105 E
Adder
6.6470588235294125.65
3151101ELIZAR3
50/50
3.6013.601
944582AF1-123 E
50/50
117.641117.641
944592AF1-124 E
50/50
118.067118.067
935112AD1-144 E
Adder
0.98941176470588230.841
316349AD2-085 C
Adder
3.5752941176470593.039
923832AB2-022 E
50/50
1.3981.398
963042AG1-153 E
50/50
12.48112.481
938772AE1-103 E
Adder
4.4858823529411773.813
916042Z1-036 E
Adder
32.1705882352941227.345
316023AB2-100 C2
50/50
1.1231.123
946281AF1-292 C
50/50
1.7971.797
960082AF2-299 E
50/50
1.4471.447
926071AC1-086 C
Adder
24.1447058823529420.523
3151541CLOVER2
50/50
15.75715.757
964241AG1-285 C
50/50
14.87614.876
958212AF2-115 E
Adder
1.73647058823529421.476
927021AC1-189 C
Adder
9.4905882352941178.067
962561AG1-105 C
Adder
9.9705882352941188.475
924152AB2-059 E OP
Adder
5.9564705882352945.063
939412AE1-173 E
50/50
85.77785.777
941032AE2-094 E
50/50
27.25927.259
941031AE2-094 C
50/50
60.86460.864
926662AC1-147 E
Adder
1.46588235294117641.246
916192Z1-068 E
50/50
2.1052.105
957492AF2-043 E
Adder
1.58117647058823541.344
923852AB2-025 E
50/50
1.3891.389
3151051BRUNSWICKS1
50/50
25.51625.516
961941AG1-037 C
Adder
0.5717647058823530.486
961942AG1-037 E
Adder
0.381176470588235340.324
936262AD2-033 E
Adder
9.0082352941176477.657
958211AF2-115 C
Adder
2.03764705882352941.732
934321AD1-056 C
Adder
7.126.052
934331AD1-057 C
Adder
3.9717647058823533.376
934332AD1-057 E
Adder
2.0682352941176471.758
934322AD1-056 E
Adder
3.86117647058823543.282
927022AC1-189 E
Adder
4.7282352941176474.019
925595AC1-034 E
Adder
5.65058823529411754.803
933292AC2-141 E
50/50
14.89414.894
316294AC1-161 C
50/50
5.7015.701
944602AF1-125 E
50/50
115.795115.795
916191Z1-068 C
50/50
0.0490.049
3145506HICKORY
50/50
2.4672.467
934576AD1-082 E
Adder
4.1988235294117653.569
957871AF2-081 C
50/50
11.29311.293
943612AF1-032 E
Adder
1.02823529411764710.874
940492AE2-034 E
Adder
3.4764705882352942.955
934522AD1-076 E
Adder
7.045.984
943172AE2-346 E
Adder
0.68588235294117650.583
918492AA1-063AE OP
Adder
4.65058823529411753.953
937482AD2-202 E
50/50
1.3221.322
917332KELFORD E
Adder
1.8635294117647061.584
925122AB2-169 E
Adder
6.4858823529411775.513
316274AC1-208 C
Adder
10.255294117647068.717
961792AG1-021 E
Adder
1.38941176470588231.181
917342Z2-044 E
Adder
0.6764705882352940.575
3151311EDGECMA
Adder
17.50705882352941214.881
940642AE2-051 E
50/50
17.4117.41
316388AE2-253 GEN
50/50
2.2212.221
919153AA1-139 E2
50/50
4.6184.618
943462AF1-017 E
Adder
2.2870588235294121.944
3143316POE
Adder
1.30823529411764721.112
939191AE1-149 C
Adder
9.5941176470588238.155
901082W1-029 E
Adder
35.7705882352941230.405
316365AB2-100 C1
50/50
1.1231.123
926206AC1-098 E
Adder
4.1470588235294123.525
935171AD1-152 C
50/50
1.6091.609
964791AG1-342 C
Adder
3.96470588235294133.37
942341AE2-247 C
Adder
1.54941176470588231.317
958162AF2-110 E
Adder
2.38000000000000032.023
924516AB2-100 E1
50/50
3.3843.384
934512AD1-075 E
Adder
4.844.114
934502AD1-074 E
Adder
19.3616.456
966621AG1-532 C
50/50
1.6281.628
918512AA1-065 E OP
Adder
6.2505882352941175.313
3147223TWITTYS
Adder
1.03411764705882360.879
959312AF2-222 E
Adder
11.9210.132
924022AB2-043 E O1
Adder
5.9035294117647065.018
918532AA1-067 E
Adder
0.80588235294117660.685
939192AE1-149 E
Adder
6.3964705882352955.437
934065AD1-033 E
50/50
5.6715.671
932046AC2-012 E
50/50
14.50114.501
316017AA1-139 ULT1
50/50
1.2231.223
938531AE1-072 C
50/50
19.84719.847
958161AF2-110 C
Adder
1.49647058823529421.272
3152411Z1-086 GT1
50/50
15.81615.816
3152421Z1-086 GT2
50/50
15.81115.811
3145393UNCAMP
Adder
6.7635294117647065.749
933981AD1-022 C
Adder
9.8917647058823528.408
900672V4-068 E
Adder
0.402352941176470640.342
924302AB2-077 E O1
Adder
1.52117647058823541.293
944581AF1-123 C
50/50
51.37451.374
316185AD1-033 C
50/50
1.391.39
941101AE2-104 C
Adder
3.66705882352941173.117
316320Y1-086 C
50/50
0.2480.248
3151041BRUNSWICKG3
50/50
12.28212.282
3151021BRUNSWICKG1
50/50
12.28212.282
957481AF2-042 C
50/50
69.9469.94
316088AB2-174 E
50/50
7.5427.542
316141AB2-099 E
Adder
0.28588235294117650.243
923994AB2-040_E
Adder
7.1047058823529416.039
924322AB2-079 E O1
Adder
1.52117647058823541.293
946302AF1-294 E
Adder
2.83882352941176472.413
961672AG1-007 E
Adder
0.60.51
943902AF1-058 E
Adder
1.42941176470588241.215
926755AC1-161 E
50/50
14.89414.894
933291AC2-141 C
50/50
34.8934.89
925522AC1-027 E
50/50
1.3621.362
957872AF2-081 E
50/50
4.844.84
3145256KINGFORK
Adder
1.06588235294117650.906
3150921YORKTN3
Adder
6.2929411764705885.349
941102AE2-104 E
Adder
5.8305882352941184.956
316087AB2-174 C
50/50
1.3621.362
964242AG1-285 E
50/50
9.9189.918
926214AC1-099 E
Adder
1.36941176470588231.164
932632AC2-084 E
Adder
3.66588235294117663.116
924162AB2-060 E OP
Adder
4.8364705882352944.111
964792AG1-342 E
Adder
2.6435294117647062.247
932763AC2-100 E
Adder
2.80941176470588252.388
919152AA1-139 E1
50/50
4.6184.618
316018AA1-139 ULT2
50/50
1.2231.223
942342AE2-247 E
Adder
2.141.819
920042AA2-088 E OP
Adder
11.94941176470588210.157
934511AD1-075 C
Adder
9.507058823529418.081
934521AD1-076 C
Adder
13.81176470588235411.74
3145723EMPORIA
50/50
0.50.5
923573AB1-173 E OP
Adder
3.78941176470588253.221
919692AA2-053 E OP
Adder
4.8352941176470594.11
925785AC1-054 E
Adder
3.94000000000000043.349
959311AF2-222 C
Adder
17.79058823529411615.122
316263AC1-034 C
Adder
7.4894117647058826.366
939411AE1-173 C
50/50
128.665128.665
913392Y1-086 E
50/50
2.4762.476
3137643SOCKMAN
Adder
0.81882352941176460.696
937481AD2-202 C
50/50
0.4540.454
919710AA2-057 E
Adder
4.49411764705882363.82
939312AE1-162 E
Adder
1.37058823529411771.165
937226AE2-253 E
50/50
6.6066.606
316321Z2-027 C
50/50
0.410.41
3151031BRUNSWICKG2
50/50
12.28212.282
924517AB2-100 E2
50/50
3.3843.384
934501AD1-074 C
Adder
38.0305882352941232.326
957482AF2-042 E
50/50
46.62746.627
934621AD1-088 C
50/50
11.53711.537
935172AD1-152 E
50/50
6.6176.617
946301AF1-294 C
Adder
3.3517647058823532.849
961671AG1-007 C
Adder
1.05882352941176470.9
316375AC2-012 C
50/50
1.4951.495
961611AG1-000B C
Adder
13.21058823529411611.229
313526AB2-022 C
50/50
0.4240.424
940541AE2-040 C
50/50
3.4343.434
940482AE2-033 E
50/50
13.01513.015
940481AE2-033 C
50/50
19.30519.305
923263AB1-132 E OP
Adder
7.0270588235294125.973
925612AC1-036 E
Adder
0.93294117647058830.793
924312AB2-078 E O1
Adder
1.52117647058823541.293
926274AC1-105 E
Adder
2.9882352941176472.54
CBM South 2LTFEXP_CBM-S2->PJM
CBM
107.493107.493
WECLTFEXP_WEC->PJM
CLTF
0.6140.614
LAGNLTFEXP_LAGN->PJM
CLTF
8.048.04
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.47229.472
G-007PJM->LTFIMP_G-007
CMTX_NF
3.5513.551
CPLELTFEXP_CPLE->PJM
CLTF
13.22113.221
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.8122.81
NYPJM->LTFIMP_NY
CLTF
1.6611.661
TVALTFEXP_TVA->PJM
CLTF
6.2796.279
O66PJM->LTFIMP_O-066
CMTX_NF
22.61622.616
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
1.1651.165
MECLTFEXP_MEC->PJM
CLTF
3.8563.856
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.3016.301

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:132.17 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3227.68
MW Contribution:60.76
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:143.03 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3493.04
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
Adder
24.07647058823529620.465
316084AB2-161 E
Adder
7.7152941176470586.558
316072AD1-144 C
50/50
0.4760.476
926785AC1-164_E
50/50
29.39329.393
943471AF1-018 C
Adder
11.310588235294129.614
3145946PLYMOUTH TP
Adder
0.490588235294117660.417
933982AD1-022 E
Adder
7.1082352941176476.042
927146AC1-208 E
Adder
5.0623529411764714.303
939412AE1-173 E
Adder
89.1152941176470775.748
941032AE2-094 E
Adder
22.3752941176470619.019
941031AE2-094 C
Adder
49.9642.466
926662AC1-147 E
50/50
2.2992.299
916192Z1-068 E
50/50
3.2723.272
316076AC2-137 E
Adder
1.79882352941176471.529
957492AF2-043 E
50/50
2.4082.408
923852AB2-025 E
Adder
1.42470588235294131.211
923842AB2-024 E
50/50
2.8452.845
316157AD2-030 E
Adder
1.8752941176470591.594
964211AG1-282 C
Adder
2.9188235294117652.481
961941AG1-037 C
Adder
0.7117647058823530.605
961942AG1-037 E
Adder
0.47411764705882360.403
3152331SURRY 2
50/50
51.04351.043
935162AD1-151 E
Adder
15.01647058823529312.764
938532AE1-072 E
50/50
15.77615.776
3146326AYDLETT TAP
50/50
2.3322.332
943461AF1-017 C
Adder
2.08235294117647071.77
316311AC2-079 C
Adder
8.917647058823537.58
932596AC2-079 E
Adder
14.55058823529411812.368
917122Z2-027 E
50/50
2.2632.263
3156056W1-029WIND
50/50
1.2941.294
957832AF2-077 E
50/50
2.4292.429
940551AE2-041 C
Adder
11.310588235294129.614
920692AA2-178 E
Adder
6.3917647058823535.433
966622AG1-532 E
Adder
1.14941176470588240.977
944012AF1-069 E
Adder
6.3411764705882355.39
925865AC1-065 E
Adder
25.77529411764705721.909
961951AG1-038 C
Adder
4.7905882352941184.072
961952AG1-038 E
Adder
6.615294117647065.623
946282AF1-292 E
Adder
1.26823529411764711.078
936582AD2-073 E
Adder
1.4282352941176471.214
944011AF1-069 C
Adder
16.32352941176470713.875
3151091ELIZAR2
50/50
5.475.47
3151081ELIZAR1
50/50
5.5665.566
941591AE2-156 C
50/50
31.09131.091
925332AB2-190 E
Adder
11.0035294117647069.353
944591AF1-124 C
50/50
79.60879.608
944601AF1-125 C
50/50
78.10478.104
316316AC1-027 C
50/50
0.550.55
927226AC1-216 E
Adder
11.0717647058823539.411
3150601CHESTF5
Adder
81.2529411764705969.065
936666AD2-085 E
Adder
8.6647058823529427.365
962962AG1-145 E
50/50
2.5662.566
963041AG1-153 C
Adder
6.8917647058823535.858
938771AE1-103 C
Adder
4.5388235294117653.858
3145413WATKINS
Adder
1.03764705882352940.882
960081AF2-299 C
Adder
2.29882352941176471.954
964212AG1-282 E
Adder
1.94588235294117641.654
926072AC1-086 E
Adder
12.14705882352941110.325
939192AE1-149 E
Adder
9.255294117647067.867
3150991CHESPKB
50/50
1.2541.254
934065AD1-033 E
50/50
8.7658.765
939312AE1-162 E
50/50
2.3472.347
937226AE2-253 E
50/50
10.1310.13
316321Z2-027 C
50/50
0.6130.613
924517AB2-100 E2
Adder
3.60705882352941173.066
934501AD1-074 C
Adder
50.8670588235294143.237
943741AF1-042 C
Adder
4.3341176470588233.684
962861AG1-135 C
Adder
8.9011764705882357.566
3141813NORNECK
Adder
1.26941176470588221.079
933292AC2-141 E
50/50
24.24524.245
316294AC1-161 C
50/50
9.2819.281
944602AF1-125 E
50/50
178.798178.798
916191Z1-068 C
50/50
0.0760.076
3145506HICKORY
50/50
3.83.8
934576AD1-082 E
Adder
6.1482352941176475.226
957871AF2-081 C
50/50
17.2717.27
943612AF1-032 E
50/50
1.5651.565
3130536PAPERMILL
50/50
10.51210.512
939602AE1-190 E
Adder
2.2223529411764711.889
940492AE2-034 E
Adder
4.7941176470588244.075
934522AD1-076 E
Adder
9.4164705882352948.004
936591AD2-074 C
Adder
8.2835294117647077.041
943172AE2-346 E
Adder
0.85411764705882350.726
918492AA1-063AE OP
Adder
5.4517647058823534.634
917332KELFORD E
Adder
2.2435294117647061.907
925122AB2-169 E
Adder
8.1458823529411776.924
316274AC1-208 C
Adder
11.402352941176479.692
3151101ELIZAR3
50/50
5.6375.637
944582AF1-123 E
50/50
181.649181.649
944592AF1-124 E
50/50
182.306182.306
3144216WINCHST
50/50
0.2350.235
935112AD1-144 E
50/50
1.5911.591
316349AD2-085 C
Adder
5.31058823529411854.514
316169AC1-164 GEN
50/50
65.42365.423
923832AB2-022 E
50/50
2.1052.105
963042AG1-153 E
Adder
10.3376470588235318.787
316314AB2-024 C
50/50
0.4650.465
938772AE1-103 E
Adder
6.2670588235294125.327
916042Z1-036 E
Adder
46.13529411764706439.215
946281AF1-292 C
Adder
1.90235294117647061.617
960082AF2-299 E
Adder
1.53294117647058831.303
926071AC1-086 C
Adder
26.68941176470588422.686
940642AE2-051 E
Adder
16.05058823529411813.643
316388AE2-253 GEN
50/50
3.4073.407
919153AA1-139 E2
50/50
7.0627.062
943462AF1-017 E
Adder
3.39764705882352922.888
942341AE2-247 C
Adder
2.3023529411764711.957
316246AF1-032 C
50/50
0.4820.482
316382AG1-145 C
50/50
0.6290.629
958162AF2-110 E
50/50
3.5653.565
924516AB2-100 E1
Adder
3.60705882352941173.066
934512AD1-075 E
Adder
6.4741176470588245.503
934502AD1-074 E
Adder
25.89411764705882722.01
966621AG1-532 C
Adder
1.7235294117647061.465
918512AA1-065 E OP
Adder
7.9376470588235296.747
963612AG1-210 E
Adder
1.42941176470588241.215
918532AA1-067 E
Adder
0.93882352941176480.798
3143316POE
Adder
1.61882352941176461.376
939191AE1-149 C
Adder
13.88352941176470711.801
316159AE1-175 C
50/50
0.6970.697
901082W1-029 E
50/50
53.10153.101
934146AD1-041 E
Adder
5.5576470588235294.724
957601AF2-054 C
Adder
3.3423529411764712.841
958261AF2-120 C
Adder
9.1270588235294127.758
926206AC1-098 E
Adder
4.7035294117647063.998
3150981CHESPKA
50/50
0.7570.757
944581AF1-123 C
50/50
79.32679.326
316185AD1-033 C
50/50
2.1482.148
941101AE2-104 C
50/50
5.4935.493
316320Y1-086 C
50/50
0.3730.373
934392AD1-063 E
50/50
1.6971.697
943742AF1-042 E
Adder
7.0717647058823536.011
957481AF2-042 C
Adder
40.46470588235294534.395
962862AG1-135 E
Adder
5.9341176470588235.044
926755AC1-161 E
50/50
24.24524.245
933291AC2-141 C
50/50
56.79756.797
925522AC1-027 E
50/50
2.1182.118
944631AF1-128 C
Adder
50.8411764705882443.215
957872AF2-081 E
50/50
7.4027.402
3145256KINGFORK
50/50
1.7141.714
3150921YORKTN3
50/50
216.891216.891
316305AF2-043 C
50/50
0.590.59
316160AE1-175 E
50/50
2.1172.117
941102AE2-104 E
50/50
8.7338.733
936592AD2-074 E
Adder
13.5152941176470611.488
926214AC1-099 E
Adder
1.55411764705882361.321
932632AC2-084 E
Adder
4.1576470588235293.534
3150731STONECA
Adder
8.6588235294117667.36
932046AC2-012 E
50/50
22.73922.739
935161AD1-151 C
Adder
22.52470588235294419.146
316017AA1-139 ULT1
50/50
1.871.87
938531AE1-072 C
50/50
30.26330.263
958161AF2-110 C
50/50
2.2412.241
316059AD1-063 C
50/50
0.4160.416
3145393UNCAMP
Adder
9.3082352941176477.912
933981AD1-022 C
Adder
13.05647058823529611.098
900672V4-068 E
Adder
0.50588235294117640.43
966662AG1-536 E
Adder
10.5494117647058848.967
316088AB2-174 E
Adder
8.1129411764705896.896
316141AB2-099 E
Adder
0.35529411764705880.302
923994AB2-040_E
Adder
7.6964705882352946.542
316036AC1-147 C
50/50
0.640.64
924814AB2-134 E
Adder
18.13647058823529415.416
919152AA1-139 E1
50/50
7.0627.062
316018AA1-139 ULT2
50/50
1.871.87
942342AE2-247 E
Adder
3.17882352941176462.702
920042AA2-088 E OP
Adder
15.24117647058823612.955
934511AD1-075 C
Adder
12.71647058823529410.809
934521AD1-076 C
Adder
18.47411764705882215.703
3145723EMPORIA
Adder
0.53294117647058830.453
939246AE1-155 E
Adder
12.70823529411764810.802
923573AB1-173 E OP
Adder
4.1047058823529413.489
919692AA2-053 E OP
Adder
5.4882352941176474.665
939411AE1-173 C
Adder
133.67176470588234113.621
934012AD1-025 E
Adder
14.33411764705882312.184
913392Y1-086 E
50/50
3.7283.728
939612AE1-191 E
Adder
8.8917647058823547.558
957602AF2-054 E
Adder
2.2282352941176471.894
966661AG1-536 C
Adder
7.8505882352941186.673
958262AF2-120 E
Adder
6.0847058823529415.172
316078AC2-138 E
Adder
1.33411764705882341.134
3137643SOCKMAN
Adder
0.90.765
316375AC2-012 C
50/50
2.3442.344
316236AE1-162 C
50/50
0.5750.575
961611AG1-000B C
Adder
24.54352941176470520.862
3138116ELKO L286
Adder
1.87647058823529411.595
313526AB2-022 C
50/50
0.6390.639
940541AE2-040 C
Adder
3.5211764705882352.993
940482AE2-033 E
Adder
13.41176470588235311.4
940481AE2-033 C
Adder
19.89411764705882416.91
957831AF2-077 C
50/50
0.5630.563
963611AG1-210 C
Adder
0.95294117647058830.81
923263AB1-132 E OP
Adder
7.7670588235294126.602
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.6420.642
MECLTFEXP_MEC->PJM
CLTF
2.4372.437
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.7575.757
CBM South 2LTFEXP_CBM-S2->PJM
CBM
94.73294.732
WECLTFEXP_WEC->PJM
CLTF
0.3320.332
LAGNLTFEXP_LAGN->PJM
CLTF
6.2526.252
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.21415.214
G-007PJM->LTFIMP_G-007
CMTX_NF
3.4553.455
CPLELTFEXP_CPLE->PJM
CLTF
12.08612.086
SIGELTFEXP_SIGE->PJM
CLTF
0.140.14
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.5416.54
NYPJM->LTFIMP_NY
CLTF
1.6681.668
TVALTFEXP_TVA->PJM
CLTF
4.8434.843
O66PJM->LTFIMP_O-066
CMTX_NF
22.04222.042

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.34 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1336.88
MW Contribution:47.23
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:127.16 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1345.51
MW Contribution:46.79
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
50/50
11.53811.538
316336AC2-165 C
Adder
-10.758823529411764-9.145
3145946PLYMOUTH TP
Adder
0.136470588235294120.116
933982AD1-022 E
Adder
2.01411764705882361.712
934622AD1-088 E
Adder
2.11.785
934612AD1-087 E
Adder
1.79882352941176471.529
927146AC1-208 E
Adder
1.72941176470588241.47
927255AC1-221 E
Adder
1.65176470588235281.404
939412AE1-173 E
50/50
36.75136.751
941032AE2-094 E
50/50
12.16712.167
941031AE2-094 C
50/50
27.16527.165
926662AC1-147 E
Adder
0.53176470588235290.452
916192Z1-068 E
Adder
0.77294117647058820.657
957492AF2-043 E
Adder
0.57529411764705880.489
923852AB2-025 E
Adder
0.50705882352941180.431
3151051BRUNSWICKS1
50/50
11.26311.263
961941AG1-037 C
Adder
0.212941176470588240.181
961942AG1-037 E
Adder
0.14235294117647060.121
936262AD2-033 E
Adder
2.8247058823529412.401
934321AD1-056 C
Adder
2.72588235294117662.317
934331AD1-057 C
Adder
1.52117647058823541.293
934332AD1-057 E
Adder
0.7917647058823530.673
934322AD1-056 E
Adder
1.47882352941176461.257
927022AC1-189 E
Adder
1.8235294117647061.55
925595AC1-034 E
Adder
2.19764705882352951.868
938532AE1-072 E
Adder
3.84235294117647053.266
3146326AYDLETT TAP
Adder
0.56823529411764710.483
943461AF1-017 C
Adder
0.454117647058823570.386
316311AC2-079 C
Adder
1.9682352941176471.673
932596AC2-079 E
Adder
3.2117647058823532.73
3152431Z1-086 GT3
50/50
7.0047.004
3152441Z1-086 ST
50/50
12.19612.196
917122Z2-027 E
Adder
0.55999999999999990.476
920692AA2-178 E
Adder
1.72705882352941181.468
966622AG1-532 E
Adder
0.40.34
922923AB1-081 E OP
Adder
1.63529411764705881.39
927264AC1-222 E
Adder
1.66470588235294131.415
944012AF1-069 E
50/50
3.4483.448
946282AF1-292 E
Adder
0.44235294117647060.376
917512Z2-088 E OP1
Adder
2.1352941176470591.815
944011AF1-069 C
50/50
8.8768.876
941591AE2-156 C
Adder
7.202352941176476.122
944591AF1-124 C
Adder
19.18823529411764616.31
944601AF1-125 C
Adder
18.82588235294117516.002
936666AD2-085 E
Adder
1.89058823529411771.607
963041AG1-153 C
50/50
3.6733.673
938771AE1-103 C
Adder
1.16941176470588240.994
3145413WATKINS
Adder
0.279999999999999970.238
960081AF2-299 C
Adder
0.80117647058823540.681
926072AC1-086 E
Adder
4.11294117647058853.496
936261AD2-033 C
Adder
4.2364705882352943.601
962562AG1-105 E
Adder
2.4729411764705882.102
936171AD2-023 C
Adder
1.80117647058823521.531
934065AD1-033 E
Adder
2.10705882352941171.791
939312AE1-162 E
Adder
0.41294117647058820.351
937226AE2-253 E
Adder
2.4552941176470592.087
3151031BRUNSWICKG2
50/50
5.4215.421
924517AB2-100 E2
Adder
1.25176470588235311.064
934501AD1-074 C
Adder
14.2176470588235312.085
957482AF2-042 E
Adder
18.89411764705882416.06
934621AD1-088 C
Adder
4.3611764705882353.707
935172AD1-152 E
Adder
2.6258823529411772.232
961671AG1-007 C
Adder
0.410588235294117640.349
936162AD2-022 E
Adder
1.85294117647058831.575
933292AC2-141 E
Adder
5.7376470588235294.877
944602AF1-125 E
Adder
43.0952941176470636.631
3145506HICKORY
Adder
0.91764705882352950.78
957871AF2-081 C
Adder
4.1964705882352953.567
943612AF1-032 E
Adder
0.374117647058823550.318
940492AE2-034 E
Adder
1.2952941176470591.101
934522AD1-076 E
Adder
2.6317647058823532.237
943172AE2-346 E
Adder
0.255294117647058840.217
918492AA1-063AE OP
Adder
1.72705882352941181.468
937482AD2-202 E
Adder
0.52588235294117650.447
917332KELFORD E
Adder
0.70117647058823530.596
925122AB2-169 E
Adder
2.4564705882352942.088
316274AC1-208 C
Adder
3.8952941176470593.311
917342Z2-044 E
Adder
0.26117647058823530.222
3151311EDGECMA
Adder
6.8129411764705895.791
941011AE2-092 C
Adder
-4.452941176470588-3.785
944582AF1-123 E
Adder
43.7823529411764837.215
944592AF1-124 E
Adder
43.9411764705882437.35
935112AD1-144 E
Adder
0.339999999999999970.289
316349AD2-085 C
Adder
1.15882352941176480.985
923832AB2-022 E
Adder
0.51764705882352950.44
963042AG1-153 E
50/50
5.5095.509
938772AE1-103 E
Adder
1.61529411764705881.373
916042Z1-036 E
Adder
11.93411764705882510.144
946281AF1-292 C
Adder
0.66352941176470580.564
960082AF2-299 E
Adder
0.53411764705882360.454
926071AC1-086 C
Adder
9.037647058823537.682
964241AG1-285 C
Adder
5.3647058823529414.56
927021AC1-189 C
Adder
3.66117647058823573.112
962561AG1-105 C
Adder
3.70941176470588243.153
924152AB2-059 E OP
Adder
2.31764705882352961.97
936172AD2-023 E
Adder
0.97764705882352940.831
940642AE2-051 E
50/50
7.6927.692
919153AA1-139 E2
Adder
1.71529411764705891.458
943462AF1-017 E
Adder
0.74117647058823530.63
942341AE2-247 C
Adder
0.50235294117647060.427
958162AF2-110 E
Adder
0.84352941176470590.717
924516AB2-100 E1
Adder
1.25176470588235311.064
934512AD1-075 E
Adder
1.80941176470588251.538
934502AD1-074 E
Adder
7.237647058823536.152
966621AG1-532 C
Adder
0.60117647058823530.511
918512AA1-065 E OP
Adder
2.34000000000000031.989
3147223TWITTYS
Adder
0.332941176470588240.283
959312AF2-222 E
Adder
3.73411764705882383.174
924022AB2-043 E O1
Adder
2.11764705882352941.8
918532AA1-067 E
Adder
0.30941176470588240.263
936161AD2-022 C
Adder
3.0882352941176472.625
901082W1-029 E
Adder
13.19764705882352911.218
926206AC1-098 E
Adder
1.57411764705882361.338
964791AG1-342 C
Adder
1.48470588235294131.262
926755AC1-161 E
Adder
5.7376470588235294.877
933291AC2-141 C
Adder
13.44235294117647211.426
925522AC1-027 E
Adder
0.50.425
957872AF2-081 E
Adder
1.79882352941176471.529
3145256KINGFORK
Adder
0.367058823529411770.312
941102AE2-104 E
Adder
2.06588235294117651.756
932046AC2-012 E
Adder
5.2588235294117654.47
938531AE1-072 C
Adder
7.3705882352941176.265
958161AF2-110 C
Adder
0.53058823529411770.451
3152411Z1-086 GT1
50/50
7.0067.006
3152421Z1-086 GT2
50/50
7.0047.004
3145393UNCAMP
Adder
2.44352941176470572.077
933981AD1-022 C
Adder
3.73.145
900672V4-068 E
Adder
0.149411764705882360.127
924302AB2-077 E O1
Adder
0.54823529411764720.466
944581AF1-123 C
Adder
19.11999999999999716.252
941101AE2-104 C
Adder
1.31.105
3151041BRUNSWICKG3
50/50
5.4215.421
3151021BRUNSWICKG1
50/50
5.4215.421
957481AF2-042 C
Adder
28.3424.089
316088AB2-174 E
Adder
2.7941176470588242.375
316141AB2-099 E
Adder
0.107058823529411760.091
923994AB2-040_E
Adder
2.63647058823529432.241
924322AB2-079 E O1
Adder
0.54823529411764720.466
961672AG1-007 E
Adder
0.232941176470588260.198
943902AF1-058 E
Adder
0.55294117647058830.47
964242AG1-285 E
Adder
3.57647058823529433.04
926214AC1-099 E
Adder
0.520.442
932632AC2-084 E
Adder
1.3917647058823531.183
924162AB2-060 E OP
Adder
1.71764705882352931.46
964792AG1-342 E
Adder
0.99058823529411770.842
932763AC2-100 E
Adder
1.12117647058823520.953
919152AA1-139 E1
Adder
1.71529411764705891.458
942342AE2-247 E
Adder
0.69411764705882350.59
920042AA2-088 E OP
Adder
4.3847058823529413.727
934511AD1-075 C
Adder
3.55411764705882363.021
934521AD1-076 C
Adder
5.1635294117647064.389
3145723EMPORIA
Adder
0.18470588235294120.157
923573AB1-173 E OP
Adder
1.40588235294117661.195
919692AA2-053 E OP
Adder
1.80705882352941181.536
925785AC1-054 E
Adder
1.47764705882352951.256
959311AF2-222 C
Adder
5.57411764705882454.738
316263AC1-034 C
Adder
2.91411764705882352.477
939411AE1-173 C
50/50
55.12655.126
913392Y1-086 E
Adder
0.91764705882352950.78
3137643SOCKMAN
Adder
0.30470588235294120.259
919710AA2-057 E
Adder
1.72588235294117661.467
940541AE2-040 C
Adder
1.25411764705882361.066
940482AE2-033 E
Adder
4.7611764705882354.047
940481AE2-033 C
Adder
7.0611764705882366.002
923263AB1-132 E OP
Adder
2.6305882352941182.236
925612AC1-036 E
Adder
0.30.255
924312AB2-078 E O1
Adder
0.54823529411764720.466
926274AC1-105 E
Adder
1.13764705882352950.967
938821AE1-108 C
Adder
-4.716470588235294-4.009
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.69643.696
WECLTFEXP_WEC->PJM
CLTF
0.2390.239
LAGNLTFEXP_LAGN->PJM
CLTF
3.2073.207
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.53211.532
G-007PJM->LTFIMP_G-007
CMTX_NF
1.0921.092
CPLELTFEXP_CPLE->PJM
CLTF
5.3965.396
SIGELTFEXP_SIGE->PJM
CLTF
0.0910.091
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.0379.037
NYPJM->LTFIMP_NY
CLTF
0.5140.514
TVALTFEXP_TVA->PJM
CLTF
2.4942.494
O66PJM->LTFIMP_O-066
CMTX_NF
6.9576.957
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.4480.448
MECLTFEXP_MEC->PJM
CLTF
1.5141.514
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5712.571

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.69 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4423.71
MW Contribution:245.83
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:114.82 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4673.36
MW Contribution:246.96
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
Adder
-21.288235294117648-18.095
934622AD1-088 E
50/50
11.49611.496
934611AD1-087 C
50/50
3.233.23
934612AD1-087 E
50/50
9.3199.319
3151611KERR 4
50/50
1.991.99
927255AC1-221 E
50/50
7.6147.614
941032AE2-094 E
50/50
53.71353.713
941031AE2-094 C
50/50
119.928119.928
3151051BRUNSWICKS1
50/50
53.25453.254
936262AD2-033 E
50/50
16.07816.078
958211AF2-115 C
Adder
3.86117647058823543.282
944012AF1-069 E
50/50
15.22215.222
316131AB2-060 C
50/50
2.8942.894
3138533PONTONDP
Adder
1.14470588235294120.973
316118AC1-105 C
50/50
1.8951.895
3152431Z1-086 GT3
50/50
32.41332.413
3152441Z1-086 ST
50/50
56.44256.442
3147133PAMPLIN
50/50
1.8091.809
927264AC1-222 E
50/50
8.2018.201
944011AF1-069 C
50/50
39.18539.185
963041AG1-153 C
50/50
17.36617.366
3151531CLOVER1
50/50
32.82832.828
936261AD2-033 C
50/50
24.11624.116
3151631KERR 6
50/50
1.991.99
961791AG1-021 C
Adder
3.08941176470588232.626
962562AG1-105 E
50/50
11.97711.977
924032AB2-045 E
Adder
1.26941176470588221.079
316248AF1-058 C
50/50
0.6640.664
936171AD2-023 C
Adder
7.246.154
942001AE2-212 C
Adder
-1.9541176470588235-1.661
3151031BRUNSWICKG2
50/50
25.63425.634
957482AF2-042 E
50/50
98.33198.331
934621AD1-088 C
50/50
23.87723.877
935172AD1-152 E
50/50
13.31413.314
946301AF1-294 C
Adder
6.3505882352941185.398
942461AE2-259 C
Adder
16.0152941176470613.613
936162AD2-022 E
Adder
7.4470588235294126.33
937482AD2-202 E
50/50
2.7272.727
3151581KERR 1
50/50
0.7110.711
3151601KERR 3
50/50
1.991.99
961792AG1-021 E
Adder
2.6317647058823532.237
3152661PLYWOOD A
50/50
2.4812.481
963042AG1-153 E
50/50
26.04926.049
3151541CLOVER2
50/50
32.52432.524
964241AG1-285 C
50/50
28.57228.572
316034AC1-036 C
50/50
0.4960.496
958212AF2-115 E
Adder
3.2894117647058822.796
962561AG1-105 C
50/50
17.96517.965
936172AD2-023 E
Adder
3.9305882352941183.341
3147223TWITTYS
50/50
2.0152.015
959312AF2-222 E
50/50
23.29123.291
924022AB2-043 E O1
50/50
10.1410.14
316003AC1-222 C
50/50
2.0082.008
926024AC1-080 E
Adder
1.71529411764705891.458
936161AD2-022 C
Adder
12.41176470588235310.55
957601AF2-054 C
Adder
-1.72-1.462
316239AB2-077 C O1
50/50
0.6390.639
935171AD1-152 C
50/50
3.2363.236
942462AE2-259 E
Adder
10.6764705882352939.075
964791AG1-342 C
50/50
7.2097.209
925997AC1-075 E
Adder
5.1705882352941174.395
938531AE1-072 C
Adder
-16.06705882352941-13.657
3152411Z1-086 GT1
50/50
32.42432.424
3152421Z1-086 GT2
50/50
32.41332.413
924302AB2-077 E O1
50/50
2.6052.605
3151621KERR 5
50/50
1.991.99
316222AC1-221 C
50/50
2.9122.912
942752AE2-291 E
Adder
8.6882352941176467.385
3151041BRUNSWICKG3
50/50
25.63425.634
3151021BRUNSWICKG1
50/50
25.63425.634
957481AF2-042 C
50/50
147.496147.496
924322AB2-079 E O1
50/50
2.6052.605
946302AF1-294 E
Adder
5.377647058823534.571
943902AF1-058 E
50/50
2.7082.708
24401205PINNACLE
Adder
1.62588235294117631.382
933291AC2-141 C
Adder
-31.96117647058824-27.167
964242AG1-285 E
50/50
19.04819.048
313527AB2-043 C
50/50
1.011.01
924162AB2-060 E OP
50/50
8.3338.333
3151591KERR 2
50/50
1.991.99
964792AG1-342 E
50/50
4.8064.806
932763AC2-100 E
50/50
5.1295.129
316283AC2-100 C
50/50
2.3312.331
316240AF1-291 C
Adder
-1.863529411764706-1.584
944641AF1-129 C
Adder
-87.13882352941177-74.068
925785AC1-054 E
Adder
3.75647058823529443.193
959311AF2-222 C
50/50
34.76234.762
942751AE2-291 C
Adder
13.03294117647058811.078
937481AD2-202 C
50/50
0.9370.937
3151641KERR 7
50/50
1.991.99
925612AC1-036 E
50/50
1.8171.817
316237AB2-079 C O1
50/50
0.6390.639
924312AB2-078 E O1
50/50
2.6052.605
316238AB2-078 C O1
50/50
0.6390.639
926274AC1-105 E
50/50
5.5465.546
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.12440.124
NYPJM->LTFIMP_NY
CLTF
1.8831.883
TVALTFEXP_TVA->PJM
CLTF
10.7110.71
O66PJM->LTFIMP_O-066
CMTX_NF
26.2626.26
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
2.2642.264
MECLTFEXP_MEC->PJM
CLTF
7.1897.189
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.4399.439
CBM South 2LTFEXP_CBM-S2->PJM
CBM
169.426169.426
WECLTFEXP_WEC->PJM
CLTF
1.2081.208
LAGNLTFEXP_LAGN->PJM
CLTF
13.6813.68
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.04159.041
G-007PJM->LTFIMP_G-007
CMTX_NF
4.1284.128
CPLELTFEXP_CPLE->PJM
CLTF
19.79519.795
SIGELTFEXP_SIGE->PJM
CLTF
0.4430.443

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.0 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2588.61
MW Contribution:92.1
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.54 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2748.4
MW Contribution:92.67
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
50/50
26.4726.47
3145946PLYMOUTH TP
Adder
0.24117647058823530.205
933982AD1-022 E
Adder
3.52470588235294142.996
934622AD1-088 E
50/50
4.4114.411
934611AD1-087 C
50/50
1.2361.236
934612AD1-087 E
50/50
3.5653.565
927146AC1-208 E
Adder
3.14470588235294152.673
927255AC1-221 E
Adder
3.2152941176470592.733
939412AE1-173 E
50/50
57.94757.947
941032AE2-094 E
50/50
21.48321.483
941031AE2-094 C
50/50
47.96747.967
926662AC1-147 E
Adder
1.23058823529411781.046
916192Z1-068 E
50/50
1.7941.794
923852AB2-025 E
Adder
0.98588235294117640.838
3151051BRUNSWICKS1
50/50
20.08620.086
961941AG1-037 C
Adder
0.367058823529411770.312
961942AG1-037 E
Adder
0.244705882352941160.208
936262AD2-033 E
Adder
7.1529411764705896.08
958211AF2-115 C
Adder
1.6635294117647061.414
934321AD1-056 C
Adder
4.99411764705882364.245
934331AD1-057 C
Adder
2.78588235294117632.368
934332AD1-057 E
Adder
1.45058823529411771.233
934322AD1-056 E
Adder
2.70941176470588242.303
944012AF1-069 E
50/50
6.0886.088
946282AF1-292 E
Adder
0.84941176470588230.722
3138533PONTONDP
Adder
0.49294117647058820.419
917512Z2-088 E OP1
Adder
3.83294117647058833.258
938532AE1-072 E
50/50
8.5488.548
3146326AYDLETT TAP
Adder
1.25647058823529421.068
3152431Z1-086 GT3
50/50
12.4512.45
3152441Z1-086 ST
50/50
21.68121.681
917122Z2-027 E
Adder
1.1117647058823530.945
920692AA2-178 E
Adder
3.0870588235294122.624
966622AG1-532 E
Adder
0.76941176470588240.654
3147133PAMPLIN
Adder
0.740.629
922923AB1-081 E OP
Adder
2.9811764705882352.534
927264AC1-222 E
Adder
3.3870588235294122.879
3151101ELIZAR3
50/50
3.0693.069
944582AF1-123 E
50/50
104.52104.52
944592AF1-124 E
50/50
104.898104.898
923832AB2-022 E
Adder
1.06823529411764720.908
963042AG1-153 E
50/50
9.8259.825
938772AE1-103 E
Adder
2.50941176470588222.133
944011AF1-069 C
50/50
15.67315.673
3151091ELIZAR2
50/50
2.9782.978
3151081ELIZAR1
50/50
3.033.03
941591AE2-156 C
50/50
16.7516.75
944591AF1-124 C
50/50
45.80645.806
944601AF1-125 C
50/50
44.94144.941
316316AC1-027 C
50/50
0.3010.301
963041AG1-153 C
50/50
6.556.55
938771AE1-103 C
Adder
1.81647058823529431.544
3145413WATKINS
Adder
0.451764705882352960.384
960081AF2-299 C
Adder
1.541.309
926072AC1-086 E
Adder
7.5870588235294126.449
3151531CLOVER1
50/50
12.55212.552
936261AD2-033 C
Adder
10.7294117647058829.12
961791AG1-021 C
Adder
1.33058823529411761.131
962562AG1-105 E
Adder
5.1941176470588244.415
916042Z1-036 E
Adder
21.67647058823529718.425
946281AF1-292 C
Adder
1.27411764705882361.083
960082AF2-299 E
Adder
1.02588235294117650.872
926071AC1-086 C
Adder
16.6705882352941214.17
3151541CLOVER2
50/50
12.43612.436
964241AG1-285 C
Adder
11.7588235294117649.995
958212AF2-115 E
Adder
1.41647058823529411.204
927021AC1-189 C
Adder
6.5388235294117655.558
962561AG1-105 C
Adder
7.7917647058823536.623
924152AB2-059 E OP
Adder
4.2235294117647063.59
927022AC1-189 E
Adder
3.25764705882352962.769
925595AC1-034 E
Adder
4.00588235294117643.405
933292AC2-141 E
50/50
37.13537.135
316294AC1-161 C
50/50
14.21614.216
944602AF1-125 E
50/50
102.879102.879
916191Z1-068 C
50/50
0.0420.042
3145506HICKORY
50/50
2.1612.161
957871AF2-081 C
50/50
9.4939.493
940492AE2-034 E
Adder
2.3152941176470591.968
934522AD1-076 E
Adder
4.6470588235294123.95
943172AE2-346 E
Adder
0.440.374
918492AA1-063AE OP
Adder
3.0882352941176472.625
937482AD2-202 E
50/50
1.0431.043
917332KELFORD E
Adder
1.2282352941176471.044
925122AB2-169 E
Adder
4.3388235294117653.688
316274AC1-208 C
Adder
7.0835294117647066.021
961792AG1-021 E
Adder
1.13294117647058810.963
917342Z2-044 E
Adder
0.475294117647058870.404
3151311EDGECMA
Adder
12.4152941176470610.553
940642AE2-051 E
50/50
17.64717.647
316388AE2-253 GEN
50/50
1.8981.898
919153AA1-139 E2
50/50
3.8823.882
924516AB2-100 E1
Adder
2.3717647058823532.016
934512AD1-075 E
Adder
3.19529411764705932.716
934502AD1-074 E
Adder
12.7810.863
966621AG1-532 C
Adder
1.15411764705882350.981
918512AA1-065 E OP
Adder
3.98941176470588273.391
3147223TWITTYS
Adder
0.82823529411764710.704
959312AF2-222 E
Adder
9.5670588235294118.132
924022AB2-043 E O1
Adder
4.6082352941176473.917
918532AA1-067 E
Adder
0.54705882352941180.465
3143316POE
Adder
0.80823529411764720.687
901082W1-029 E
Adder
23.54352941176470520.012
957601AF2-054 C
Adder
-1.2505882352941176-1.063
926206AC1-098 E
Adder
2.8317647058823532.407
942462AE2-259 E
Adder
4.3564705882352943.703
964791AG1-342 C
Adder
3.09882352941176452.634
934065AD1-033 E
50/50
5.0045.004
937226AE2-253 E
50/50
5.6435.643
3151031BRUNSWICKG2
50/50
9.6689.668
924517AB2-100 E2
Adder
2.3717647058823532.016
934501AD1-074 C
Adder
25.10470588235294221.339
957482AF2-042 E
50/50
36.84236.842
934621AD1-088 C
50/50
9.1619.161
935172AD1-152 E
Adder
5.2058823529411774.425
946301AF1-294 C
Adder
2.73529411764705932.325
942461AE2-259 C
Adder
6.5341176470588245.554
961671AG1-007 C
Adder
0.73882352941176480.628
932046AC2-012 E
50/50
12.1712.17
316017AA1-139 ULT1
50/50
1.0281.028
938531AE1-072 C
50/50
16.39816.398
3152411Z1-086 GT1
50/50
12.45512.455
3152421Z1-086 GT2
50/50
12.4512.45
3145393UNCAMP
Adder
3.8517647058823533.274
933981AD1-022 C
Adder
6.4741176470588245.503
900672V4-068 E
Adder
0.254117647058823560.216
924302AB2-077 E O1
Adder
1.18705882352941171.009
944581AF1-123 C
50/50
45.64445.644
316185AD1-033 C
50/50
1.2261.226
3151041BRUNSWICKG3
50/50
9.6689.668
3151021BRUNSWICKG1
50/50
9.6689.668
957481AF2-042 C
50/50
55.26355.263
316088AB2-174 E
Adder
5.3035294117647064.508
316141AB2-099 E
Adder
0.183529411764705890.156
923994AB2-040_E
Adder
4.9776470588235294.231
924322AB2-079 E O1
Adder
1.18705882352941171.009
946302AF1-294 E
Adder
2.3164705882352941.969
961672AG1-007 E
Adder
0.41882352941176470.356
943902AF1-058 E
Adder
1.11882352941176480.951
926755AC1-161 E
50/50
37.13537.135
933291AC2-141 C
50/50
86.99486.994
925522AC1-027 E
50/50
1.1581.158
957872AF2-081 E
50/50
4.0684.068
964242AG1-285 E
Adder
7.846.664
926214AC1-099 E
Adder
0.93529411764705890.795
932632AC2-084 E
Adder
2.50352941176470622.128
924162AB2-060 E OP
Adder
3.78117647058823543.214
964792AG1-342 E
Adder
2.06588235294117651.756
932763AC2-100 E
Adder
2.1788235294117651.852
919152AA1-139 E1
50/50
3.8823.882
316018AA1-139 ULT2
50/50
1.0281.028
920042AA2-088 E OP
Adder
7.3835294117647066.276
934511AD1-075 C
Adder
6.2764705882352945.335
934521AD1-076 C
Adder
9.1176470588235297.75
3145723EMPORIA
Adder
0.352941176470588260.3
923573AB1-173 E OP
Adder
2.65411764705882322.256
919692AA2-053 E OP
Adder
3.30000000000000032.805
925785AC1-054 E
Adder
2.882.448
959311AF2-222 C
Adder
14.27882352941176512.137
316263AC1-034 C
Adder
5.31058823529411854.514
939411AE1-173 C
50/50
86.92186.921
913392Y1-086 E
Adder
1.8917647058823531.608
3137643SOCKMAN
Adder
0.56941176470588240.484
937481AD2-202 C
50/50
0.3590.359
919710AA2-057 E
Adder
3.1364705882352942.666
316375AC2-012 C
50/50
1.2551.255
940541AE2-040 C
Adder
2.4364705882352942.071
940482AE2-033 E
Adder
9.2211764705882357.838
940481AE2-033 C
Adder
13.6776470588235311.626
923263AB1-132 E OP
Adder
4.8517647058823534.124
925612AC1-036 E
Adder
0.74705882352941180.635
924312AB2-078 E O1
Adder
1.18705882352941171.009
926274AC1-105 E
Adder
2.3364705882352941.986
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.52724.527
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1242.124
CPLELTFEXP_CPLE->PJM
CLTF
9.989.98
SIGELTFEXP_SIGE->PJM
CLTF
0.1890.189
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.91517.915
NYPJM->LTFIMP_NY
CLTF
0.9860.986
TVALTFEXP_TVA->PJM
CLTF
4.8674.867
O66PJM->LTFIMP_O-066
CMTX_NF
13.52713.527
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.950.95
MECLTFEXP_MEC->PJM
CLTF
3.1033.103
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.7574.757
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.65881.658
WECLTFEXP_WEC->PJM
CLTF
0.5060.506
LAGNLTFEXP_LAGN->PJM
CLTF
6.2356.235

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN POSSUM-KRAKEN_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN POSSUM-KRAKEN_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.79 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3342.63
MW Contribution:40.98
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926004AC1-076_E
50/50
5.1345.134
940641AE2-051 C
50/50
14.3414.34
316084AB2-161 E
Adder
4.7082352941176474.002
926785AC1-164_E
Adder
14.68941176470588412.486
943471AF1-018 C
Adder
5.6941176470588244.84
316336AC2-165 C
Adder
7.9058823529411776.72
3145946PLYMOUTH TP
Adder
0.26235294117647060.223
316045AC1-158 C2
50/50
15.05615.056
944012AF1-069 E
50/50
4.0654.065
925865AC1-065 E
Adder
13.29176470588235411.298
316254AC1-120 C
Adder
5.7588235294117654.895
926739AC1-158 E1
50/50
39.25239.252
316233AE1-074 C
50/50
2.1942.194
935162AD1-151 E
Adder
9.1176470588235297.75
938532AE1-072 E
Adder
7.75647058823529446.593
3146326AYDLETT TAP
Adder
1.1482352941176470.976
943461AF1-017 C
Adder
1.1435294117647060.972
316311AC2-079 C
Adder
4.8588235294117644.13
932596AC2-079 E
Adder
7.9270588235294126.738
917122Z2-027 E
Adder
1.12941176470588230.96
957832AF2-077 E
Adder
1.16705882352941170.992
927042AC1-191 E
Adder
3.823.247
940551AE2-041 C
Adder
5.6941176470588244.84
920692AA2-178 E
Adder
3.3635294117647062.859
316044AC1-158 C1
50/50
15.05615.056
944011AF1-069 C
50/50
10.46510.465
941591AE2-156 C
Adder
15.2529411764705912.965
925332AB2-190 E
Adder
6.8411764705882365.815
944591AF1-124 C
Adder
38.73764705882352632.927
944601AF1-125 C
Adder
38.0058823529411832.305
927226AC1-216 E
Adder
6.54588235294117655.564
3150601CHESTF5
Adder
52.9070588235294144.971
936666AD2-085 E
Adder
4.7600000000000014.046
962962AG1-145 E
Adder
1.19529411764705881.016
963041AG1-153 C
Adder
4.4447058823529423.778
938771AE1-103 C
Adder
2.4270588235294122.063
3145413WATKINS
Adder
0.56705882352941170.482
316170AC1-121 C
Adder
1.97764705882352951.681
925022AB2-158 E
50/50
4.8984.898
944582AF1-123 E
Adder
88.3905882352941375.132
944592AF1-124 E
Adder
88.7105882352941175.404
935112AD1-144 E
Adder
0.79764705882352950.678
316349AD2-085 C
Adder
2.91764705882352932.48
930122AB1-027 E
Adder
1.11411764705882340.947
316169AC1-164 GEN
Adder
32.696470588235327.792
923832AB2-022 E
Adder
1.04588235294117650.889
963042AG1-153 E
Adder
6.6670588235294125.667
938772AE1-103 E
Adder
3.35058823529411762.848
916042Z1-036 E
Adder
23.720.145
3150831SPRUNCA
50/50
7.8917.891
3150841SPRUNCB
50/50
7.8917.891
939412AE1-173 E
50/50
50.40250.402
941032AE2-094 E
50/50
14.34414.344
941031AE2-094 C
50/50
32.02832.028
926662AC1-147 E
Adder
1.1282352941176470.959
916192Z1-068 E
Adder
1.61.36
316076AC2-137 E
Adder
1.08941176470588250.926
957492AF2-043 E
Adder
1.20352941176470571.023
923852AB2-025 E
Adder
0.94705882352941180.805
966872AG1-558 E
Adder
0.96235294117647050.818
966871AG1-558 C
Adder
1.9105882352941181.624
923842AB2-024 E
Adder
1.42941176470588241.215
923862AB2-026 E
Adder
1.00588235294117640.855
316157AD2-030 E
Adder
0.94705882352941180.805
933292AC2-141 E
50/50
11.07211.072
316294AC1-161 C
50/50
4.2384.238
946262AF1-291 E
50/50
1.2281.228
3150651CHESTF6
50/50
15.89215.892
944602AF1-125 E
Adder
87.0035294117647273.953
3145506HICKORY
Adder
1.85294117647058831.575
934576AD1-082 E
Adder
3.7517647058823533.189
957871AF2-081 C
Adder
8.4705882352941187.2
943612AF1-032 E
Adder
0.78235294117647070.665
3130536PAPERMILL
Adder
5.2847058823529424.492
939602AE1-190 E
Adder
1.13529411764705880.965
940492AE2-034 E
Adder
2.52235294117647072.144
934522AD1-076 E
Adder
5.0505882352941184.293
3143316POE
50/50
1.1631.163
939191AE1-149 C
Adder
9.1694117647058837.794
901082W1-029 E
Adder
26.73882352941176822.728
934146AD1-041 E
Adder
2.83882352941176472.413
957601AF2-054 C
Adder
1.68705882352941171.434
316164AC1-076_C
50/50
0.8990.899
940642AE2-051 E
50/50
9.569.56
919153AA1-139 E2
Adder
3.46352941176470572.944
943462AF1-017 E
Adder
1.86705882352941191.587
942341AE2-247 C
Adder
1.26470588235294111.075
926412AC1-112 E
Adder
0.90705882352941180.771
958162AF2-110 E
Adder
1.83764705882352961.562
924516AB2-100 E1
Adder
2.3023529411764711.957
934512AD1-075 E
Adder
3.47294117647058842.952
934502AD1-074 E
Adder
13.89058823529411811.807
3150731STONECA
Adder
5.8447058823529414.968
932046AC2-012 E
Adder
11.162352941176479.488
935161AD1-151 C
Adder
13.67647058823529511.625
938531AE1-072 C
Adder
14.87882352941176512.647
958161AF2-110 C
Adder
1.15529411764705880.982
3145393UNCAMP
Adder
5.0176470588235294.265
926486AC1-120 E
Adder
2.96705882352941152.522
3152261N ANNA2
50/50
45.57245.572
3150861SPRUNCD
50/50
0.1420.142
942002AE2-212 E
50/50
1.2311.231
940431AE2-027 C
50/50
11.01611.016
944581AF1-123 C
Adder
38.632.81
941101AE2-104 C
Adder
2.8317647058823532.407
934392AD1-063 E
Adder
0.85411764705882350.726
957481AF2-042 C
Adder
8.0364705882352956.831
3152251N ANNA1
50/50
45.55345.553
316192AB2-158 C
50/50
1.8491.849
938552AE1-074 E
50/50
1.1051.105
926755AC1-161 E
50/50
11.07211.072
933291AC2-141 C
50/50
25.93725.937
925522AC1-027 E
Adder
1.03647058823529430.881
944631AF1-128 C
Adder
33.1047058823529428.139
957872AF2-081 E
Adder
3.63058823529411743.086
3145256KINGFORK
Adder
0.860.731
3150921YORKTN3
Adder
99.9870588235294284.989
316160AE1-175 E
Adder
0.98588235294117640.838
941102AE2-104 E
Adder
4.5011764705882353.826
938562AE1-075 E
Adder
0.85764705882352940.729
316240AF1-291 C
50/50
1.8421.842
944641AF1-129 C
50/50
87.28387.283
924814AB2-134 E
Adder
10.7235294117647079.115
919152AA1-139 E1
Adder
3.46352941176470572.944
942342AE2-247 E
Adder
1.74588235294117641.484
926502AC1-121 E
Adder
0.93058823529411770.791
920042AA2-088 E OP
Adder
8.5658823529411777.281
934511AD1-075 C
Adder
6.8211764705882355.798
934521AD1-076 C
Adder
9.9094117647058838.423
3150851SPRUNCC
50/50
0.1420.142
939411AE1-173 C
50/50
75.60375.603
940432AE2-027 E
50/50
7.3447.344
934012AD1-025 E
Adder
8.4752941176470587.204
913392Y1-086 E
Adder
1.8517647058823531.574
939612AE1-191 E
Adder
4.5423529411764713.861
957602AF2-054 E
Adder
1.12470588235294120.956
933502AC2-165 E
Adder
5.9494117647058835.057
942001AE2-212 C
50/50
1.8461.846
939192AE1-149 E
Adder
6.1129411764705885.196
934065AD1-033 E
Adder
4.2682352941176473.628
939312AE1-162 E
Adder
1.21647058823529421.034
937226AE2-253 E
Adder
4.957647058823534.214
958502AF2-144 E
Adder
0.98823529411764710.84
924517AB2-100 E2
Adder
2.3023529411764711.957
934501AD1-074 C
Adder
27.2870588235294123.194
926740AC1-158 E2
50/50
39.25239.252
961611AG1-000B C
Adder
13.50117647058823611.476
3138116ELKO L286
Adder
1.13647058823529410.966
940541AE2-040 C
Adder
2.3423529411764711.991
940482AE2-033 E
Adder
8.8729411764705887.542
940481AE2-033 C
Adder
13.16117647058823411.187
927041AC1-191 C
Adder
7.6694117647058836.519
316303AF2-085
50/50
3.4183.418
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.6090.609
MECLTFEXP_MEC->PJM
CLTF
2.0372.037
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.8153.815
CBM South 2LTFEXP_CBM-S2->PJM
CBM
65.36565.365
WECLTFEXP_WEC->PJM
CLTF
0.2960.296
LAGNLTFEXP_LAGN->PJM
CLTF
4.7564.756
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.46613.466
G-007PJM->LTFIMP_G-007
CMTX_NF
4.2544.254
CPLELTFEXP_CPLE->PJM
CLTF
8.0088.008
SIGELTFEXP_SIGE->PJM
CLTF
0.1240.124
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.04413.044
NYPJM->LTFIMP_NY
CLTF
2.0162.016
TVALTFEXP_TVA->PJM
CLTF
3.7543.754
O66PJM->LTFIMP_O-066
CMTX_NF
27.11327.113

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.93 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4311.69
MW Contribution:214.41
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.26 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4569.37
MW Contribution:216.48
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
Adder
-20.06823529411765-17.058
934622AD1-088 E
50/50
10.02610.026
934611AD1-087 C
50/50
2.8252.825
934612AD1-087 E
50/50
8.158.15
3151611KERR 4
50/50
1.7561.756
927255AC1-221 E
50/50
6.8776.877
944012AF1-069 E
50/50
17.73117.731
316131AB2-060 C
50/50
2.5322.532
3138533PONTONDP
Adder
0.99529411764705880.846
316118AC1-105 C
50/50
1.6721.672
3152431Z1-086 GT3
50/50
33.83433.834
3152441Z1-086 ST
50/50
58.91758.917
3147133PAMPLIN
50/50
1.5711.571
927264AC1-222 E
50/50
7.2547.254
944011AF1-069 C
50/50
45.64245.642
963041AG1-153 C
50/50
17.20617.206
3151531CLOVER1
50/50
28.70728.707
936261AD2-033 C
50/50
21.05721.057
3151631KERR 6
50/50
1.7561.756
961791AG1-021 C
Adder
2.68823529411764732.285
962562AG1-105 E
50/50
10.53610.536
316248AF1-058 C
50/50
0.5870.587
936171AD2-023 C
Adder
6.8564705882352955.828
963042AG1-153 E
50/50
25.80825.808
3151541CLOVER2
50/50
28.44128.441
964241AG1-285 C
50/50
24.94424.944
316034AC1-036 C
50/50
0.4320.432
958212AF2-115 E
Adder
2.86235294117647052.433
962561AG1-105 C
50/50
15.80415.804
936172AD2-023 E
Adder
3.7223529411764713.164
941032AE2-094 E
50/50
62.56462.564
941031AE2-094 C
50/50
139.691139.691
3151051BRUNSWICKS1
50/50
52.76252.762
936262AD2-033 E
50/50
14.03814.038
958211AF2-115 C
Adder
3.362.856
937482AD2-202 E
50/50
2.3852.385
3151581KERR 1
50/50
0.6270.627
3151601KERR 3
50/50
1.7561.756
961792AG1-021 E
Adder
2.28941176470588251.946
3152661PLYWOOD A
50/50
2.1912.191
3147223TWITTYS
50/50
1.7561.756
959312AF2-222 E
50/50
20.29620.296
924022AB2-043 E O1
50/50
8.8758.875
316003AC1-222 C
50/50
1.7761.776
926024AC1-080 E
Adder
1.52117647058823541.293
936161AD2-022 C
Adder
11.7541176470588239.991
957601AF2-054 C
Adder
-1.6305882352941177-1.386
316239AB2-077 C O1
50/50
0.5590.559
935171AD1-152 C
50/50
2.8452.845
942462AE2-259 E
Adder
9.2458823529411777.859
964791AG1-342 C
50/50
6.3476.347
925997AC1-075 E
Adder
4.5835294117647063.896
942001AE2-212 C
Adder
-1.851764705882353-1.574
3151031BRUNSWICKG2
50/50
25.39725.397
957482AF2-042 E
50/50
85.76685.766
934621AD1-088 C
50/50
20.82320.823
935172AD1-152 E
50/50
11.70511.705
946301AF1-294 C
Adder
5.5247058823529414.696
942461AE2-259 C
Adder
13.86823529411764811.788
936162AD2-022 E
Adder
7.0529411764705895.995
938531AE1-072 C
Adder
-15.17764705882353-12.901
3152411Z1-086 GT1
50/50
33.84633.846
3152421Z1-086 GT2
50/50
33.83433.834
924302AB2-077 E O1
50/50
2.2822.282
3151621KERR 5
50/50
1.7561.756
316222AC1-221 C
50/50
2.632.63
942752AE2-291 E
Adder
7.7105882352941186.554
3151041BRUNSWICKG3
50/50
25.39725.397
3151021BRUNSWICKG1
50/50
25.39725.397
957481AF2-042 C
50/50
128.648128.648
924322AB2-079 E O1
50/50
2.2822.282
946302AF1-294 E
Adder
4.6788235294117653.977
943902AF1-058 E
50/50
2.3942.394
24401205PINNACLE
Adder
1.53647058823529431.306
933291AC2-141 C
Adder
-30.18235294117647-25.655
964242AG1-285 E
50/50
16.62916.629
313527AB2-043 C
50/50
0.8840.884
924162AB2-060 E OP
50/50
7.2927.292
3151591KERR 2
50/50
1.7561.756
964792AG1-342 E
50/50
4.2324.232
932763AC2-100 E
50/50
4.6444.644
316283AC2-100 C
50/50
2.112.11
316240AF1-291 C
Adder
-1.7670588235294118-1.502
944641AF1-129 C
Adder
-82.61058823529412-70.219
925785AC1-054 E
Adder
3.30235294117647052.807
959311AF2-222 C
50/50
30.29330.293
942751AE2-291 C
Adder
11.5670588235294139.832
937481AD2-202 C
50/50
0.820.82
3151641KERR 7
50/50
1.7561.756
925612AC1-036 E
50/50
1.5841.584
316237AB2-079 C O1
50/50
0.5590.559
924312AB2-078 E O1
50/50
2.2822.282
316238AB2-078 C O1
50/50
0.5590.559
926274AC1-105 E
50/50
4.8944.894
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.3338.33
NYPJM->LTFIMP_NY
CLTF
1.8141.814
TVALTFEXP_TVA->PJM
CLTF
10.24910.249
O66PJM->LTFIMP_O-066
CMTX_NF
25.2725.27
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
2.1482.148
MECLTFEXP_MEC->PJM
CLTF
6.8436.843
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.0719.071
CBM South 2LTFEXP_CBM-S2->PJM
CBM
162.815162.815
WECLTFEXP_WEC->PJM
CLTF
1.1471.147
LAGNLTFEXP_LAGN->PJM
CLTF
13.09813.098
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5656
G-007PJM->LTFIMP_G-007
CMTX_NF
3.9723.972
CPLELTFEXP_CPLE->PJM
CLTF
19.02319.023
SIGELTFEXP_SIGE->PJM
CLTF
0.4210.421
CONTINGENCY 'DVP_P1-2: LN 2027_SRT-A-2'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026 C    230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
 OPEN BUS 923862                                   /*AB2-026 E    230.0
 OPEN BUS 938562                                   /*AE1-075 E    230.0
 OPEN BUS 958502                                   /*AF2-144 E    230.0
END
CONTINGENCY 'DVP_P1-2: LN 556_SRT-S-3'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN POSSUM-KRAKEN_SRT-A'
 OPEN BRANCH FROM BUS 314922 TO BUS 313483 CKT 1   /*8POSSUM      500.0 - 8KRAKEN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314268 to 313802 ckt 1
314287 to 314260 ckt 1
313373 to 314765 ckt 1
313996 to 314268 ckt 1
313707 to 313373 ckt 1
314765 to 314749 ckt 1
313802 to 314692 ckt 1
314260 to 314225 ckt 1
314902 to 314914 ckt 1
314903 to 314908 ckt 1
314914 to 314322 ckt 1
314936 to 314902 ckt 1
314923 to 314924 ckt 1
314934 to 314916 ckt 1
941030 to 314902 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
OPAC108.91 %888.3B967.4220.33
GD1DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
DVP_P1-2: LN 576_SRT-A
OPAC109.68 %879.84B965.0120.28
GD1DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S-1
OPAC111.78 %1058.16B1182.7638.69
GD1DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
OPAC112.61 %3220.44B3626.5339.69
GD1DVP
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
OPAC105.31 %4070.2B4286.27216.48
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Base Case
OPAC104.94 %3220.44A3379.5440.34

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.91 %
Rating:888.3 MVA
Rating Type:B
MVA to Mitigate:967.42
MW Contribution:20.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926472AC1-118 E
Adder
0.46470588235294120.395
926785AC1-164_E
Adder
10.222352941176478.689
316336AC2-165 C
Adder
5.1470588235294124.375
316084AB2-161 E
Adder
3.057647058823532.599
940641AE2-051 C
Adder
6.94117647058823555.9
933982AD1-022 E
Adder
1.91764705882352931.63
3145946PLYMOUTH TP
Adder
0.129411764705882370.11
943471AF1-018 C
Adder
3.6235294117647063.08
964211AG1-282 C
Adder
0.97764705882352940.831
316076AC2-137 E
Adder
0.91882352941176480.781
966872AG1-558 E
50/50
1.3791.379
966871AG1-558 C
50/50
2.7372.737
3150831SPRUNCA
Adder
7.5870588235294126.449
3150841SPRUNCB
50/50
7.5877.587
923862AB2-026 E
Adder
0.68823529411764710.585
923852AB2-025 E
Adder
0.57882352941176470.492
941032AE2-094 E
Adder
7.1552941176470596.082
941031AE2-094 C
Adder
15.97647058823529413.58
939412AE1-173 E
Adder
24.13882352941176620.518
961942AG1-037 E
Adder
0.137647058823529430.117
961941AG1-037 C
Adder
0.205882352941176460.175
916192Z1-068 E
Adder
0.75294117647058820.64
926662AC1-147 E
Adder
0.53647058823529410.456
957492AF2-043 E
Adder
0.57882352941176470.492
923842AB2-024 E
Adder
0.92235294117647060.784
316157AD2-030 E
Adder
0.58823529411764710.5
3150691DARBY 3
50/50
2.2852.285
927042AC1-191 E
50/50
5.4755.475
316233AE1-074 C
Adder
1.93529411764705881.645
966622AG1-532 E
Adder
0.408235294117647030.347
935162AD1-151 E
Adder
6.5000000000000015.525
943461AF1-017 C
Adder
0.64352941176470590.547
316311AC2-079 C
Adder
2.6964705882352942.292
932596AC2-079 E
Adder
4.3988235294117643.739
920692AA2-178 E
Adder
1.65058823529411771.403
917122Z2-027 E
Adder
0.53764705882352950.457
3146326AYDLETT TAP
Adder
0.53882352941176470.458
938532AE1-072 E
Adder
3.64117647058823573.095
940551AE2-041 C
Adder
3.6235294117647063.08
957832AF2-077 E
Adder
0.65058823529411770.553
961952AG1-038 E
Adder
2.1729411764705881.847
961951AG1-038 C
Adder
1.57294117647058831.337
936582AD2-073 E
Adder
0.490588235294117660.417
939262AE1-157 E
Adder
3.01647058823529422.564
946282AF1-292 E
Adder
0.45058823529411770.383
944012AF1-069 E
Adder
2.0282352941176471.724
925865AC1-065 E
Adder
8.6294117647058827.335
3150701DARBY 4
50/50
2.2872.287
3142366NRTHEST
50/50
0.1750.175
315051AA1-145 CT1
50/50
4.9224.922
3150481FOUR RIVERF
50/50
3.7183.718
3150731STONECA
Adder
4.69058823529411753.987
935161AD1-151 C
Adder
9.7494117647058838.287
900672V4-068 E
Adder
0.147058823529411770.125
964212AG1-282 E
Adder
0.6517647058823530.554
3150601CHESTF5
Adder
44.0411764705882437.435
3150431FOUR RIVERA
50/50
3.093.09
966881AG1-559 C
Adder
1.30235294117647071.107
925332AB2-190 E
Adder
5.01882352941176454.266
963041AG1-153 C
Adder
2.21411764705882331.882
960081AF2-299 C
Adder
0.81647058823529410.694
944011AF1-069 C
Adder
5.2200000000000014.437
926072AC1-086 E
Adder
4.0835294117647063.471
927226AC1-216 E
Adder
4.5094117647058833.833
3145413WATKINS
Adder
0.290588235294117650.247
936666AD2-085 E
Adder
2.6764705882352942.275
962962AG1-145 E
Adder
0.66352941176470580.564
938771AE1-103 C
Adder
1.23764705882352951.052
944591AF1-124 C
Adder
17.70588235294117815.05
944601AF1-125 C
Adder
17.37176470588235214.766
941591AE2-156 C
Adder
7.237647058823536.152
943741AF1-042 C
Adder
1.4235294117647061.21
962861AG1-135 C
Adder
2.95764705882352932.514
3141813NORNECK
Adder
0.42235294117647060.359
3150671DARBY 1
50/50
2.2742.274
958502AF2-144 E
Adder
0.6764705882352940.575
942001AE2-212 C
Adder
1.52470588235294141.296
939192AE1-149 E
Adder
4.33647058823529453.686
924517AB2-100 E2
Adder
1.32235294117647071.124
934501AD1-074 C
Adder
13.52352941176470611.495
937226AE2-253 E
Adder
2.31764705882352961.97
934065AD1-033 E
Adder
1.9882352941176471.69
939312AE1-162 E
Adder
0.6682352941176470.568
936591AD2-074 C
Adder
2.71999999999999982.312
3150461FOUR RIVERD
50/50
3.0453.045
3150861SPRUNCD
50/50
0.1360.136
3150651CHESTF6
Adder
14.30352941176470512.158
946262AF1-291 E
Adder
1.08352941176470590.921
934576AD1-082 E
Adder
2.4364705882352942.071
918492AA1-063AE OP
Adder
1.69294117647058841.439
943172AE2-346 E
Adder
0.247058823529411780.21
934522AD1-076 E
Adder
2.50352941176470622.128
940492AE2-034 E
Adder
1.23764705882352951.052
944602AF1-125 E
Adder
39.76823529411764533.803
957871AF2-081 C
Adder
3.96823529411764753.373
3145506HICKORY
Adder
0.86352941176470590.734
943612AF1-032 E
Adder
0.37647058823529410.32
3130536PAPERMILL
Adder
3.40117647058823552.891
939602AE1-190 E
Adder
0.72352941176470590.615
316169AC1-164 GEN
Adder
22.7529411764705919.34
930122AB1-027 E
50/50
1.261.26
966882AG1-559 E
Adder
0.65647058823529430.558
939261AE1-157 C
Adder
5.5611764705882364.727
963042AG1-153 E
Adder
3.32117647058823542.823
946281AF1-292 C
Adder
0.6764705882352940.575
960082AF2-299 E
Adder
0.54470588235294130.463
926071AC1-086 C
Adder
8.9717647058823547.626
316349AD2-085 C
Adder
1.641.394
938772AE1-103 E
Adder
1.7082352941176471.452
916042Z1-036 E
Adder
11.4799999999999999.758
944592AF1-124 E
Adder
40.5482352941176534.466
944582AF1-123 E
Adder
40.4023529411764734.342
923832AB2-022 E
Adder
0.495294117647058830.421
935112AD1-144 E
Adder
0.398823529411764740.339
963612AG1-210 E
Adder
0.476470588235294150.405
926412AC1-112 E
50/50
1.0251.025
3150441FOUR RIVERB
50/50
3.093.09
924516AB2-100 E1
Adder
1.32235294117647071.124
966621AG1-532 C
Adder
0.61294117647058830.521
940642AE2-051 E
Adder
4.6270588235294123.933
918512AA1-065 E OP
Adder
2.2364705882352941.901
934502AD1-074 E
Adder
6.8835294117647065.851
934512AD1-075 E
Adder
1.72117647058823551.463
943462AF1-017 E
Adder
1.04941176470588250.892
942341AE2-247 C
Adder
0.71058823529411760.604
919153AA1-139 E2
Adder
1.62235294117647061.379
958162AF2-110 E
Adder
0.92705882352941180.788
958261AF2-120 C
Adder
3.04352941176470632.587
934781AD1-105 C
50/50
1.1541.154
3143316POE
Adder
0.85529411764705890.727
939191AE1-149 C
Adder
6.5047058823529415.529
901082W1-029 E
Adder
12.82352941176470710.9
934146AD1-041 E
Adder
1.80941176470588251.538
957601AF2-054 C
Adder
1.04941176470588250.892
943742AF1-042 E
Adder
2.32235294117647051.974
962862AG1-135 E
Adder
1.97176470588235291.676
966662AG1-536 E
Adder
3.517647058823532.99
3150681DARBY 2
50/50
2.2772.277
942002AE2-212 E
Adder
1.01647058823529420.864
940431AE2-027 C
Adder
9.2847058823529427.892
957481AF2-042 C
Adder
12.16117647058823610.337
316088AB2-174 E
Adder
2.82.38
923994AB2-040_E
Adder
2.62117647058823572.228
316141AB2-099 E
Adder
0.102352941176470580.087
944581AF1-123 C
Adder
17.64352941176470714.997
941101AE2-104 C
Adder
1.42941176470588241.215
934392AD1-063 E
Adder
0.54352941176470590.462
936592AD2-074 E
Adder
4.4376470588235293.772
944631AF1-128 C
Adder
27.55647058823529223.423
315052AA1-145 CT2
50/50
4.9194.919
3150471FOUR RIVERE
50/50
3.0453.045
934782AD1-105 E
50/50
4.8014.801
3150851SPRUNCC
50/50
0.1360.136
938552AE1-074 E
Adder
0.97529411764705880.829
938562AE1-075 E
Adder
0.58705882352941170.499
316160AE1-175 E
Adder
0.54823529411764720.466
957872AF2-081 E
Adder
1.70000000000000021.445
925522AC1-027 E
Adder
0.488235294117647050.415
941102AE2-104 E
Adder
2.2717647058823531.931
3145256KINGFORK
Adder
0.42941176470588230.365
3150921YORKTN3
Adder
50.19411764705882542.665
933981AD1-022 C
Adder
3.52352941176470622.995
3145393UNCAMP
Adder
2.5635294117647062.179
938531AE1-072 C
Adder
6.9847058823529425.937
932046AC2-012 E
Adder
5.3070588235294124.511
958161AF2-110 C
Adder
0.58352941176470590.496
939246AE1-155 E
Adder
4.2376470588235293.602
316004AC1-112 C
50/50
0.2980.298
3142296MT RD221
50/50
0.1440.144
3150501FOURRIVERG
50/50
4.714.71
944641AF1-129 C
Adder
78.5611764705882466.777
316240AF1-291 C
Adder
1.62470588235294121.381
3145723EMPORIA
Adder
0.187058823529411780.159
923573AB1-173 E OP
Adder
1.39764705882352951.188
919692AA2-053 E OP
Adder
1.74117647058823531.48
924814AB2-134 E
Adder
7.38705882352941156.279
920042AA2-088 E OP
Adder
4.4247058823529413.761
934521AD1-076 C
Adder
4.9117647058823534.175
934511AD1-075 C
Adder
3.38117647058823542.874
942342AE2-247 E
Adder
0.98117647058823530.834
919152AA1-139 E1
Adder
1.62235294117647061.379
958262AF2-120 E
Adder
2.02941176470588271.725
966661AG1-536 C
Adder
2.61764705882352942.225
316078AC2-138 E
Adder
0.44470588235294120.378
316312AB1-027 C
50/50
0.4790.479
3150451FOUR RIVERC
50/50
3.7753.775
933502AC2-165 E
Adder
3.87294117647058833.292
940432AE2-027 E
Adder
6.1894117647058825.261
3137643SOCKMAN
Adder
0.29882352941176470.254
939411AE1-173 C
Adder
36.2082352941176530.777
934012AD1-025 E
Adder
5.8388235294117654.963
913392Y1-086 E
Adder
0.87764705882352940.746
939612AE1-191 E
Adder
2.89529411764705862.461
957602AF2-054 E
Adder
0.70.595
963611AG1-210 C
Adder
0.317647058823529450.27
3138116ELKO L286
Adder
0.95764705882352940.814
927041AC1-191 C
50/50
10.99110.991
940541AE2-040 C
Adder
1.4317647058823531.217
940481AE2-033 C
Adder
7.9823529411764716.785
940482AE2-033 E
Adder
5.3811764705882354.574
923263AB1-132 E OP
Adder
2.61058823529411742.219
961611AG1-000B C
Adder
8.3752941176470597.119
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.91730.917
WECLTFEXP_WEC->PJM
CLTF
0.1050.105
LAGNLTFEXP_LAGN->PJM
CLTF
2.0642.064
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.74.7
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3651.365
CPLELTFEXP_CPLE->PJM
CLTF
3.8973.897
SIGELTFEXP_SIGE->PJM
CLTF
0.0460.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.445.44
NYPJM->LTFIMP_NY
CLTF
0.6610.661
TVALTFEXP_TVA->PJM
CLTF
1.6091.609
O66PJM->LTFIMP_O-066
CMTX_NF
8.718.71
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.2110.211
MECLTFEXP_MEC->PJM
CLTF
0.7890.789
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.8561.856

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.68 %
Rating:879.84 MVA
Rating Type:B
MVA to Mitigate:965.01
MW Contribution:20.28
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926472AC1-118 E
Adder
0.46352941176470590.394
926785AC1-164_E
Adder
10.1964705882352958.667
316336AC2-165 C
Adder
5.1341176470588234.364
316084AB2-161 E
Adder
3.0505882352941182.593
940641AE2-051 C
Adder
6.9235294117647065.885
933982AD1-022 E
Adder
1.91294117647058811.626
3145946PLYMOUTH TP
Adder
0.129411764705882370.11
943471AF1-018 C
Adder
3.61529411764705883.073
964211AG1-282 C
Adder
0.97411764705882350.828
316076AC2-137 E
Adder
0.91647058823529410.779
966872AG1-558 E
50/50
1.3761.376
966871AG1-558 C
50/50
2.7312.731
3150831SPRUNCA
Adder
7.5682352941176476.433
3150841SPRUNCB
50/50
7.5687.568
923862AB2-026 E
Adder
0.68588235294117650.583
923852AB2-025 E
Adder
0.57764705882352940.491
941032AE2-094 E
Adder
7.13764705882352956.067
941031AE2-094 C
Adder
15.93647058823529313.546
939412AE1-173 E
Adder
24.07882352941176420.467
961942AG1-037 E
Adder
0.136470588235294120.116
961941AG1-037 C
Adder
0.205882352941176460.175
916192Z1-068 E
Adder
0.75058823529411770.638
926662AC1-147 E
Adder
0.53529411764705880.455
957492AF2-043 E
Adder
0.57764705882352940.491
923842AB2-024 E
Adder
0.920.782
316157AD2-030 E
Adder
0.58705882352941170.499
3150691DARBY 3
50/50
2.2792.279
927042AC1-191 E
50/50
5.4615.461
316233AE1-074 C
Adder
1.93058823529411771.641
966622AG1-532 E
Adder
0.407058823529411750.346
935162AD1-151 E
Adder
6.4835294117647065.511
943461AF1-017 C
Adder
0.64117647058823530.545
316311AC2-079 C
Adder
2.68941176470588242.286
932596AC2-079 E
Adder
4.38823529411764753.73
920692AA2-178 E
Adder
1.64588235294117661.399
917122Z2-027 E
Adder
0.53647058823529410.456
3146326AYDLETT TAP
Adder
0.53764705882352950.457
938532AE1-072 E
Adder
3.63176470588235353.087
940551AE2-041 C
Adder
3.61529411764705883.073
957832AF2-077 E
Adder
0.64823529411764710.551
961952AG1-038 E
Adder
2.16705882352941171.842
961951AG1-038 C
Adder
1.56941176470588251.334
936582AD2-073 E
Adder
0.48941176470588230.416
939262AE1-157 E
Adder
3.00941176470588222.558
946282AF1-292 E
Adder
0.44941176470588240.382
944012AF1-069 E
Adder
2.02235294117647071.719
925865AC1-065 E
Adder
8.6082352941176487.317
3150701DARBY 4
50/50
2.2822.282
3142366NRTHEST
50/50
0.1750.175
315051AA1-145 CT1
50/50
4.914.91
3150481FOUR RIVERF
50/50
3.7093.709
3150731STONECA
Adder
4.6788235294117653.977
935161AD1-151 C
Adder
9.7247058823529418.266
900672V4-068 E
Adder
0.147058823529411770.125
933981AD1-022 C
Adder
3.51411764705882362.987
3145393UNCAMP
Adder
2.55764705882352942.174
938531AE1-072 C
Adder
6.96705882352941155.922
932046AC2-012 E
Adder
5.2941176470588234.5
958161AF2-110 C
Adder
0.58117647058823530.494
964212AG1-282 E
Adder
0.64941176470588250.552
3150601CHESTF5
Adder
43.9317647058823537.342
3150431FOUR RIVERA
50/50
3.0823.082
966881AG1-559 C
Adder
1.2988235294117651.104
925332AB2-190 E
Adder
5.00588235294117644.255
963041AG1-153 C
Adder
2.20823529411764731.877
960081AF2-299 C
Adder
0.81411764705882350.692
944011AF1-069 C
Adder
5.2070588235294124.426
926072AC1-086 E
Adder
4.07294117647058853.462
927226AC1-216 E
Adder
4.4988235294117653.824
3145413WATKINS
Adder
0.289411764705882370.246
936666AD2-085 E
Adder
2.66941176470588242.269
962962AG1-145 E
Adder
0.66235294117647060.563
938771AE1-103 C
Adder
1.23411764705882351.049
944591AF1-124 C
Adder
17.66235294117647215.013
944601AF1-125 C
Adder
17.32823529411764714.729
941591AE2-156 C
Adder
7.226.137
943741AF1-042 C
Adder
1.42000000000000021.207
962861AG1-135 C
Adder
2.94941176470588262.507
3141813NORNECK
Adder
0.421176470588235260.358
3150671DARBY 1
50/50
2.2682.268
958502AF2-144 E
Adder
0.67411764705882350.573
942001AE2-212 C
Adder
1.52117647058823541.293
939192AE1-149 E
Adder
4.3258823529411773.677
924517AB2-100 E2
Adder
1.31882352941176471.121
934501AD1-074 C
Adder
13.48941176470588111.466
937226AE2-253 E
Adder
2.3117647058823531.965
934065AD1-033 E
Adder
1.98352941176470581.686
939312AE1-162 E
Adder
0.66588235294117650.566
936591AD2-074 C
Adder
2.7129411764705882.306
3150461FOUR RIVERD
50/50
3.0373.037
3150861SPRUNCD
50/50
0.1360.136
3150651CHESTF6
Adder
14.26823529411764812.128
946262AF1-291 E
Adder
1.080.918
934576AD1-082 E
Adder
2.43058823529411772.066
918492AA1-063AE OP
Adder
1.6882352941176471.435
943172AE2-346 E
Adder
0.245882352941176470.209
934522AD1-076 E
Adder
2.4964705882352942.122
940492AE2-034 E
Adder
1.23529411764705891.05
944602AF1-125 E
Adder
39.66941176470588533.719
957871AF2-081 C
Adder
3.95764705882352933.364
3145506HICKORY
Adder
0.86117647058823530.732
943612AF1-032 E
Adder
0.375294117647058830.319
3130536PAPERMILL
Adder
3.39176470588235322.883
939602AE1-190 E
Adder
0.72235294117647060.614
316169AC1-164 GEN
Adder
22.6952941176470619.291
930122AB1-027 E
50/50
1.2571.257
966882AG1-559 E
Adder
0.65411764705882360.556
939261AE1-157 C
Adder
5.5470588235294124.715
963042AG1-153 E
Adder
3.31294117647058832.816
946281AF1-292 C
Adder
0.67411764705882350.573
960082AF2-299 E
Adder
0.54352941176470590.462
926071AC1-086 C
Adder
8.9494117647058827.607
316349AD2-085 C
Adder
1.63647058823529411.391
938772AE1-103 E
Adder
1.70470588235294131.449
916042Z1-036 E
Adder
11.4505882352941189.733
944592AF1-124 E
Adder
40.4482352941176534.381
944582AF1-123 E
Adder
40.3011764705882434.256
923832AB2-022 E
Adder
0.494117647058823550.42
935112AD1-144 E
Adder
0.397647058823529460.338
963612AG1-210 E
Adder
0.475294117647058870.404
926412AC1-112 E
50/50
1.0221.022
3150441FOUR RIVERB
50/50
3.0823.082
924516AB2-100 E1
Adder
1.31882352941176471.121
966621AG1-532 C
Adder
0.61058823529411770.519
940642AE2-051 E
Adder
4.6152941176470593.923
918512AA1-065 E OP
Adder
2.2317647058823531.897
934502AD1-074 E
Adder
6.8670588235294125.837
934512AD1-075 E
Adder
1.71647058823529421.459
943462AF1-017 E
Adder
1.04705882352941180.89
942341AE2-247 C
Adder
0.70941176470588230.603
919153AA1-139 E2
Adder
1.61882352941176461.376
958162AF2-110 E
Adder
0.92470588235294130.786
958261AF2-120 C
Adder
3.0352941176470592.58
934781AD1-105 C
50/50
1.1511.151
3143316POE
Adder
0.85294117647058820.725
939191AE1-149 C
Adder
6.4882352941176475.515
901082W1-029 E
Adder
12.79176470588235210.873
934146AD1-041 E
Adder
1.80470588235294121.534
957601AF2-054 C
Adder
1.04705882352941180.89
943742AF1-042 E
Adder
2.3164705882352941.969
962862AG1-135 E
Adder
1.96705882352941171.672
966662AG1-536 E
Adder
3.50941176470588272.983
3150681DARBY 2
50/50
2.2712.271
942002AE2-212 E
Adder
1.01411764705882360.862
940431AE2-027 C
Adder
9.2611764705882367.872
957481AF2-042 C
Adder
12.13176470588235210.312
316088AB2-174 E
Adder
2.79294117647058832.374
923994AB2-040_E
Adder
2.61529411764705882.223
316141AB2-099 E
Adder
0.102352941176470580.087
944581AF1-123 C
Adder
17.614.96
941101AE2-104 C
Adder
1.42588235294117641.212
934392AD1-063 E
Adder
0.54235294117647060.461
936592AD2-074 E
Adder
4.42705882352941153.763
944631AF1-128 C
Adder
27.48823529411764723.365
315052AA1-145 CT2
50/50
4.9074.907
3150471FOUR RIVERE
50/50
3.0373.037
934782AD1-105 E
50/50
4.7894.789
3150851SPRUNCC
50/50
0.1360.136
938552AE1-074 E
Adder
0.97294117647058820.827
938562AE1-075 E
Adder
0.58470588235294120.497
316160AE1-175 E
Adder
0.54588235294117650.464
957872AF2-081 E
Adder
1.69647058823529421.442
925522AC1-027 E
Adder
0.487058823529411770.414
941102AE2-104 E
Adder
2.2670588235294121.927
3145256KINGFORK
Adder
0.42941176470588230.365
3150921YORKTN3
Adder
50.0694117647058842.559
939246AE1-155 E
Adder
4.2270588235294123.593
316004AC1-112 C
50/50
0.2980.298
3142296MT RD221
50/50
0.1440.144
3150501FOURRIVERG
50/50
4.6984.698
944641AF1-129 C
Adder
78.3658823529411866.611
316240AF1-291 C
Adder
1.621.377
3145723EMPORIA
Adder
0.187058823529411780.159
923573AB1-173 E OP
Adder
1.39411764705882371.185
919692AA2-053 E OP
Adder
1.73647058823529421.476
924814AB2-134 E
Adder
7.3694117647058836.264
920042AA2-088 E OP
Adder
4.41411764705882353.752
934521AD1-076 C
Adder
4.8988235294117644.164
934511AD1-075 C
Adder
3.3717647058823532.866
942342AE2-247 E
Adder
0.97882352941176460.832
919152AA1-139 E1
Adder
1.61882352941176461.376
958262AF2-120 E
Adder
2.0235294117647061.72
966661AG1-536 C
Adder
2.61176470588235342.22
316078AC2-138 E
Adder
0.44352941176470590.377
316312AB1-027 C
50/50
0.4780.478
3150451FOUR RIVERC
50/50
3.7663.766
933502AC2-165 E
Adder
3.86352941176470573.284
940432AE2-027 E
Adder
6.1741176470588245.248
3137643SOCKMAN
Adder
0.297647058823529430.253
939411AE1-173 C
Adder
36.1188235294117630.701
934012AD1-025 E
Adder
5.8247058823529414.951
913392Y1-086 E
Adder
0.87529411764705890.744
939612AE1-191 E
Adder
2.8882352941176472.455
957602AF2-054 E
Adder
0.69764705882352940.593
963611AG1-210 C
Adder
0.316470588235294170.269
3138116ELKO L286
Adder
0.9552941176470590.812
927041AC1-191 C
50/50
10.96310.963
940541AE2-040 C
Adder
1.4282352941176471.214
940481AE2-033 C
Adder
7.962352941176476.768
940482AE2-033 E
Adder
5.3682352941176474.563
923263AB1-132 E OP
Adder
2.60470588235294142.214
961611AG1-000B C
Adder
8.3541176470588237.101
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.210.21
MECLTFEXP_MEC->PJM
CLTF
0.7870.787
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.8521.852
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.8430.84
WECLTFEXP_WEC->PJM
CLTF
0.1050.105
LAGNLTFEXP_LAGN->PJM
CLTF
2.0592.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.6884.688
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3611.361
CPLELTFEXP_CPLE->PJM
CLTF
3.8883.888
SIGELTFEXP_SIGE->PJM
CLTF
0.0460.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.4265.426
NYPJM->LTFIMP_NY
CLTF
0.6590.659
TVALTFEXP_TVA->PJM
CLTF
1.6051.605
O66PJM->LTFIMP_O-066
CMTX_NF
8.6888.688

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.78 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1182.76
MW Contribution:38.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926785AC1-164_E
Adder
8.8941176470588247.56
316336AC2-165 C
50/50
13.55213.552
934622AD1-088 E
Adder
2.08470588235294141.772
934612AD1-087 E
Adder
1.55882352941176471.325
316084AB2-161 E
Adder
2.8764705882352942.445
940641AE2-051 C
Adder
7.0152941176470595.963
943471AF1-018 C
Adder
3.25058823529411762.763
316076AC2-137 E
Adder
0.73529411764705890.625
966872AG1-558 E
Adder
0.64352941176470590.547
966871AG1-558 C
Adder
1.27764705882352961.086
3150831SPRUNCA
50/50
9.4469.446
3150841SPRUNCB
50/50
9.4469.446
316258AE1-075 C
50/50
0.5110.511
923862AB2-026 E
50/50
1.8081.808
941012AE2-092 E
Adder
4.6305882352941183.936
958211AF2-115 C
Adder
1.21529411764705891.033
936262AD2-033 E
Adder
4.3329411764705883.683
923852AB2-025 E
Adder
0.54941176470588240.467
941032AE2-094 E
Adder
7.166.086
941031AE2-094 C
Adder
15.98588235294117513.588
939412AE1-173 E
Adder
24.89294117647058621.159
916192Z1-068 E
Adder
0.820.697
926662AC1-147 E
Adder
0.58117647058823530.494
957492AF2-043 E
Adder
0.62470588235294120.531
923842AB2-024 E
Adder
0.82235294117647050.699
316157AD2-030 E
Adder
0.53411764705882360.454
927042AC1-191 E
Adder
2.55411764705882362.171
316233AE1-074 C
50/50
3.7333.733
3147133PAMPLIN
Adder
0.54941176470588240.467
966622AG1-532 E
Adder
0.42588235294117650.362
935162AD1-151 E
Adder
5.9847058823529415.087
943461AF1-017 C
Adder
0.64470588235294120.548
316311AC2-079 C
Adder
2.71999999999999982.312
932596AC2-079 E
Adder
4.4376470588235293.772
920692AA2-178 E
Adder
1.78588235294117651.518
917122Z2-027 E
Adder
0.58470588235294120.497
3146326AYDLETT TAP
Adder
0.58823529411764710.5
938532AE1-072 E
Adder
3.9729411764705883.377
940551AE2-041 C
Adder
3.25058823529411762.763
957832AF2-077 E
Adder
0.63529411764705890.54
3138533PONTONDP
Adder
0.360.306
946282AF1-292 E
Adder
0.47058823529411770.4
944012AF1-069 E
Adder
2.02941176470588271.725
925865AC1-065 E
Adder
7.73058823529411756.571
3150731STONECA
Adder
4.1494117647058823.527
924302AB2-077 E O1
Adder
0.62117647058823530.528
935161AD1-151 C
Adder
8.9764705882352947.63
900672V4-068 E
Adder
0.157647058823529420.134
3145393UNCAMP
Adder
2.72117647058823582.313
938531AE1-072 C
Adder
7.6223529411764716.479
932046AC2-012 E
Adder
5.7529411764705884.89
958161AF2-110 C
Adder
0.61529411764705890.523
3150601CHESTF5
Adder
39.4470588235294233.53
924032AB2-045 E
Adder
0.94941176470588240.807
961791AG1-021 C
Adder
0.97294117647058820.827
936261AD2-033 C
Adder
6.5000000000000015.525
925332AB2-190 E
Adder
4.5752941176470593.889
963041AG1-153 C
Adder
2.2623529411764711.923
960081AF2-299 C
Adder
0.8517647058823530.724
944011AF1-069 C
Adder
5.2235294117647074.44
926072AC1-086 E
Adder
4.2364705882352943.601
927226AC1-216 E
Adder
4.20352941176470553.573
3145413WATKINS
Adder
0.30941176470588240.263
936666AD2-085 E
Adder
2.6835294117647062.281
962962AG1-145 E
Adder
0.65529411764705890.557
938771AE1-103 C
Adder
1.3117647058823531.115
944591AF1-124 C
Adder
19.5717647058823516.636
944601AF1-125 C
Adder
19.2023529411764716.322
941591AE2-156 C
Adder
7.8529411764705886.675
958502AF2-144 E
50/50
1.7771.777
938822AE1-108 E
Adder
4.0211764705882363.418
942001AE2-212 C
Adder
1.3035294117647061.108
942461AE2-259 C
Adder
5.83647058823529454.961
946301AF1-294 C
Adder
1.99882352941176491.699
939192AE1-149 E
Adder
3.93176470588235333.342
934621AD1-088 C
Adder
4.3294117647058833.68
957482AF2-042 E
Adder
15.4776470588235313.156
924517AB2-100 E2
Adder
1.32117647058823541.123
937226AE2-253 E
Adder
2.53176470588235342.152
934065AD1-033 E
Adder
2.1752941176470591.849
939312AE1-162 E
Adder
0.67999999999999990.578
3150861SPRUNCD
50/50
0.1690.169
316405AF2-144 C
50/50
0.4340.434
3150651CHESTF6
Adder
11.96588235294117610.171
946262AF1-291 E
Adder
0.91058823529411770.774
941011AE2-092 C
Adder
6.9470588235294125.905
961792AG1-021 E
Adder
0.82823529411764710.704
937482AD2-202 E
Adder
0.456470588235294130.388
934576AD1-082 E
Adder
2.2917647058823531.948
918492AA1-063AE OP
Adder
1.8117647058823531.54
933292AC2-141 E
Adder
2.30588235294117631.96
940492AE2-034 E
Adder
1.33882352941176451.138
944602AF1-125 E
Adder
43.9588235294117737.365
957871AF2-081 C
Adder
4.3329411764705883.683
3145506HICKORY
Adder
0.94470588235294130.803
943612AF1-032 E
Adder
0.405882352941176470.345
3130536PAPERMILL
Adder
3.0341176470588242.579
939602AE1-190 E
Adder
0.6517647058823530.554
316169AC1-164 GEN
Adder
19.79647058823529816.827
930122AB1-027 E
Adder
0.69529411764705880.591
958212AF2-115 E
Adder
1.0352941176470590.88
964241AG1-285 C
Adder
6.0305882352941185.126
963042AG1-153 E
Adder
3.39411764705882352.885
946281AF1-292 C
Adder
0.70588235294117650.6
960082AF2-299 E
Adder
0.56823529411764710.483
926071AC1-086 C
Adder
9.3082352941176477.912
316349AD2-085 C
Adder
1.6447058823529411.398
938772AE1-103 E
Adder
1.8117647058823531.54
916042Z1-036 E
Adder
12.43647058823529310.571
944592AF1-124 E
Adder
44.82117647058823538.098
944582AF1-123 E
Adder
44.6637.961
923832AB2-022 E
Adder
0.53882352941176470.458
935112AD1-144 E
Adder
0.42235294117647060.359
926412AC1-112 E
Adder
0.56470588235294120.48
959312AF2-222 E
Adder
5.71764705882352954.86
3147223TWITTYS
Adder
0.48235294117647060.41
924022AB2-043 E O1
Adder
2.4235294117647062.06
924516AB2-100 E1
Adder
1.32117647058823541.123
966621AG1-532 C
Adder
0.63882352941176480.543
940642AE2-051 E
Adder
4.67764705882352953.976
943462AF1-017 E
Adder
1.0517647058823530.894
942341AE2-247 C
Adder
0.71294117647058820.606
919153AA1-139 E2
Adder
1.7717647058823531.506
958162AF2-110 E
Adder
0.97882352941176460.832
3143096IRON208
50/50
0.330.33
316313AB2-026 C
50/50
0.5570.557
3143316POE
Adder
0.75647058823529410.643
942462AE2-259 E
Adder
3.8917647058823533.308
939191AE1-149 C
Adder
5.8976470588235295.013
901082W1-029 E
Adder
13.8976470588235311.813
934146AD1-041 E
Adder
1.63058823529411771.386
957601AF2-054 C
Adder
0.95294117647058830.81
942002AE2-212 E
Adder
0.86941176470588230.739
946302AF1-294 E
Adder
1.69294117647058841.439
940431AE2-027 C
Adder
7.9682352941176476.773
924322AB2-079 E O1
Adder
0.62117647058823530.528
957481AF2-042 C
Adder
23.21647058823529619.734
316088AB2-174 E
Adder
2.94705882352941152.505
923994AB2-040_E
Adder
2.76941176470588252.354
944581AF1-123 C
Adder
19.50352941176470616.578
941101AE2-104 C
Adder
1.50823529411764711.282
934392AD1-063 E
Adder
0.487058823529411770.414
944631AF1-128 C
Adder
24.6823529411764720.98
3150851SPRUNCC
50/50
0.1690.169
938552AE1-074 E
50/50
1.8811.881
938562AE1-075 E
50/50
1.5421.542
964242AG1-285 E
Adder
4.0211764705882363.418
924162AB2-060 E OP
Adder
2.0117647058823531.71
316160AE1-175 E
Adder
0.54117647058823540.46
933291AC2-141 C
Adder
12.51176470588235310.635
957872AF2-081 E
Adder
1.85647058823529431.578
925522AC1-027 E
Adder
0.53176470588235290.452
941102AE2-104 E
Adder
2.39764705882352922.038
3145256KINGFORK
Adder
0.455294117647058850.387
3150921YORKTN3
Adder
52.8152941176470644.893
3138116ELKO L286
Adder
0.76588235294117660.651
927041AC1-191 C
Adder
5.1282352941176474.359
944641AF1-129 C
Adder
65.7211764705882355.863
316240AF1-291 C
Adder
1.36588235294117651.161
959311AF2-222 C
Adder
8.5341176470588237.254
3145723EMPORIA
Adder
0.196470588235294150.167
923573AB1-173 E OP
Adder
1.47764705882352951.256
919692AA2-053 E OP
Adder
1.86823529411764721.588
924814AB2-134 E
Adder
6.8847058823529425.852
920042AA2-088 E OP
Adder
4.724.012
942342AE2-247 E
Adder
0.98470588235294120.837
919152AA1-139 E1
Adder
1.7717647058823531.506
933502AC2-165 E
50/50
10.19910.199
940432AE2-027 E
Adder
5.3129411764705894.516
3137643SOCKMAN
Adder
0.317647058823529450.27
939411AE1-173 C
Adder
37.3388235294117631.738
934012AD1-025 E
Adder
5.44117647058823554.625
913392Y1-086 E
Adder
0.9552941176470590.812
939612AE1-191 E
Adder
2.6082352941176472.217
957602AF2-054 E
Adder
0.63529411764705890.54
938821AE1-108 C
Adder
8.4270588235294127.163
925612AC1-036 E
Adder
0.435294117647058830.37
924312AB2-078 E O1
Adder
0.62117647058823530.528
940541AE2-040 C
Adder
1.35764705882352941.154
940481AE2-033 C
Adder
7.6223529411764716.479
940482AE2-033 E
Adder
5.13882352941176554.368
923263AB1-132 E OP
Adder
2.70941176470588242.303
961611AG1-000B C
Adder
8.1152941176470596.898
316303AF2-085
50/50
7.0277.027
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.29711.297
NYPJM->LTFIMP_NY
CLTF
0.9630.963
TVALTFEXP_TVA->PJM
CLTF
2.952.95
O66PJM->LTFIMP_O-066
CMTX_NF
13.41813.418
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.7270.727
MECLTFEXP_MEC->PJM
CLTF
2.1322.132
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.2422.242
CBM South 2LTFEXP_CBM-S2->PJM
CBM
40.62940.629
WECLTFEXP_WEC->PJM
CLTF
0.3730.373
LAGNLTFEXP_LAGN->PJM
CLTF
3.6953.695
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.08118.081
G-007PJM->LTFIMP_G-007
CMTX_NF
2.112.11
CPLELTFEXP_CPLE->PJM
CLTF
4.6984.698
SIGELTFEXP_SIGE->PJM
CLTF
0.1370.137

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.61 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3626.53
MW Contribution:39.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926785AC1-164_E
Adder
15.18705882352941212.909
316336AC2-165 C
Adder
7.5952941176470596.456
316084AB2-161 E
Adder
4.6294117647058833.935
940641AE2-051 C
Adder
13.44352941176470611.427
933982AD1-022 E
Adder
3.82588235294117633.252
3145946PLYMOUTH TP
Adder
0.260.221
943471AF1-018 C
Adder
5.74470588235294164.883
316076AC2-137 E
Adder
1.12470588235294120.956
966872AG1-558 E
Adder
1.00235294117647070.852
966871AG1-558 C
Adder
1.99058823529411751.692
3150831SPRUNCA
Adder
7.76941176470588256.604
3150841SPRUNCB
Adder
7.76941176470588256.604
923862AB2-026 E
Adder
0.9552941176470590.812
923852AB2-025 E
Adder
0.91294117647058830.776
941032AE2-094 E
Adder
13.42117647058823411.408
941031AE2-094 C
Adder
29.96705882352941325.472
939412AE1-173 E
Adder
47.7988235294117640.629
961942AG1-037 E
Adder
0.26705882352941180.227
961941AG1-037 C
Adder
0.40.34
916192Z1-068 E
Adder
1.57058823529411761.335
926662AC1-147 E
Adder
1.1082352941176470.942
957492AF2-043 E
Adder
1.1835294117647061.006
923842AB2-024 E
Adder
1.44588235294117661.229
316157AD2-030 E
Adder
0.95058823529411770.808
3150691DARBY 3
50/50
2.1782.178
927042AC1-191 E
Adder
3.9811764705882353.384
316233AE1-074 C
50/50
2.0812.081
966622AG1-532 E
Adder
0.720.612
935162AD1-151 E
Adder
9.1035294117647067.738
943461AF1-017 C
Adder
1.12470588235294120.956
316311AC2-079 C
Adder
4.7788235294117654.062
932596AC2-079 E
Adder
7.797647058823536.628
920692AA2-178 E
Adder
3.3341176470588242.834
917122Z2-027 E
Adder
1.1117647058823530.945
3146326AYDLETT TAP
Adder
1.12588235294117660.957
938532AE1-072 E
Adder
7.61176470588235256.47
940551AE2-041 C
Adder
5.74470588235294164.883
957832AF2-077 E
Adder
1.17058823529411770.995
939262AE1-157 E
Adder
6.1717647058823545.246
946282AF1-292 E
Adder
0.79529411764705890.676
944012AF1-069 E
Adder
3.8035294117647063.233
925865AC1-065 E
Adder
13.38705882352941111.379
3150601CHESTF5
Adder
53.7270588235294145.668
3150431FOUR RIVERA
50/50
2.6242.624
966881AG1-559 C
Adder
1.97411764705882351.678
925332AB2-190 E
Adder
6.83529411764705855.81
963041AG1-153 C
Adder
4.2011764705882353.571
960081AF2-299 C
Adder
1.44117647058823551.225
944011AF1-069 C
Adder
9.7917647058823548.323
927226AC1-216 E
Adder
6.5294117647058825.55
3145413WATKINS
Adder
0.55999999999999990.476
936666AD2-085 E
Adder
4.6811764705882363.979
962962AG1-145 E
Adder
1.21294117647058821.031
938771AE1-103 C
Adder
2.3929411764705882.034
3150701DARBY 4
50/50
2.182.18
3142366NRTHEST
50/50
0.1580.158
315051AA1-145 CT1
50/50
4.184.18
3150481FOUR RIVERF
50/50
3.1583.158
3150731STONECA
Adder
5.857647058823534.979
935161AD1-151 C
Adder
13.65411764705882411.606
900672V4-068 E
Adder
0.283529411764705860.241
933981AD1-022 C
Adder
7.0282352941176475.974
3145393UNCAMP
Adder
4.9517647058823524.209
938531AE1-072 C
Adder
14.60235294117647212.412
932046AC2-012 E
Adder
10.9658823529411779.321
958161AF2-110 C
Adder
1.13647058823529410.966
944591AF1-124 C
Adder
38.1011764705882432.386
944601AF1-125 C
Adder
37.3823529411764731.775
941591AE2-156 C
Adder
14.9847058823529412.737
3150671DARBY 1
50/50
2.1682.168
958502AF2-144 E
Adder
0.93882352941176480.798
3152251N ANNA1
50/50
31.17231.172
942001AE2-212 C
Adder
1.82117647058823541.548
939192AE1-149 E
Adder
6.0082352941176485.107
924517AB2-100 E2
Adder
2.2517647058823531.914
934501AD1-074 C
Adder
27.1223.052
937226AE2-253 E
Adder
4.8611764705882354.132
934065AD1-033 E
Adder
4.1835294117647063.556
939312AE1-162 E
Adder
1.20352941176470571.023
3150461FOUR RIVERD
50/50
2.5862.586
3150861SPRUNCD
50/50
0.1390.139
3150651CHESTF6
Adder
15.84823529411764813.471
946262AF1-291 E
Adder
1.22117647058823531.038
934576AD1-082 E
Adder
3.6882352941176473.135
918492AA1-063AE OP
Adder
3.19411764705882332.715
943172AE2-346 E
Adder
0.480.408
934522AD1-076 E
Adder
5.02000000000000054.267
933292AC2-141 E
Adder
10.8847058823529439.252
940492AE2-034 E
Adder
2.5011764705882352.126
944602AF1-125 E
Adder
85.5752941176470672.739
957871AF2-081 C
Adder
8.3094117647058827.063
3145506HICKORY
Adder
1.81647058823529431.544
943612AF1-032 E
Adder
0.76941176470588240.654
3130536PAPERMILL
Adder
5.3435294117647064.542
939602AE1-190 E
Adder
1.14235294117647060.971
316169AC1-164 GEN
Adder
33.8035294117647128.733
930122AB1-027 E
50/50
1.1721.172
966882AG1-559 E
Adder
0.99411764705882360.845
939261AE1-157 C
Adder
11.3776470588235299.671
963042AG1-153 E
Adder
6.3023529411764715.357
946281AF1-292 C
Adder
1.19294117647058821.014
960082AF2-299 E
Adder
0.960.816
316349AD2-085 C
Adder
2.86941176470588262.439
938772AE1-103 E
Adder
3.30470588235294162.809
916042Z1-036 E
Adder
23.40823529411764519.897
944592AF1-124 E
Adder
87.2541176470588274.166
944582AF1-123 E
Adder
86.9473.899
923832AB2-022 E
Adder
1.02823529411764710.874
935112AD1-144 E
Adder
0.78705882352941180.669
926412AC1-112 E
50/50
0.9540.954
3150441FOUR RIVERB
50/50
2.6242.624
3152261N ANNA2
50/50
31.18431.184
924516AB2-100 E1
Adder
2.2517647058823531.914
966621AG1-532 C
Adder
1.080.918
940642AE2-051 E
Adder
8.9623529411764717.618
918512AA1-065 E OP
Adder
4.3952941176470593.736
934502AD1-074 E
Adder
13.80588235294117511.735
934512AD1-075 E
Adder
3.45176470588235332.934
943462AF1-017 E
Adder
1.8364705882352941.561
942341AE2-247 C
Adder
1.24352941176470581.057
919153AA1-139 E2
Adder
3.39764705882352922.888
958162AF2-110 E
Adder
1.8082352941176471.537
3143316POE
Adder
1.13294117647058810.963
939191AE1-149 C
Adder
9.0129411764705877.661
901082W1-029 E
Adder
26.33176470588235722.382
934146AD1-041 E
Adder
2.8564705882352942.428
957601AF2-054 C
Adder
1.69529411764705881.441
3150681DARBY 2
50/50
2.172.17
942002AE2-212 E
Adder
1.21411764705882351.032
940431AE2-027 C
Adder
10.9364705882352939.296
957481AF2-042 C
Adder
33.9223529411764728.834
316088AB2-174 E
Adder
5.0294117647058834.275
316141AB2-099 E
Adder
0.20.17
944581AF1-123 C
Adder
37.9670588235294132.272
941101AE2-104 C
Adder
2.78588235294117632.368
934392AD1-063 E
Adder
0.86117647058823530.732
944631AF1-128 C
Adder
33.6176470588235328.575
315052AA1-145 CT2
50/50
4.1784.178
3150471FOUR RIVERE
50/50
2.5862.586
3150851SPRUNCC
50/50
0.1390.139
938552AE1-074 E
50/50
1.0481.048
938562AE1-075 E
Adder
0.81529411764705880.693
316160AE1-175 E
Adder
1.00.85
933291AC2-141 C
Adder
25.521.675
926755AC1-161 E
Adder
10.8847058823529439.252
957872AF2-081 E
Adder
3.56117647058823563.027
925522AC1-027 E
Adder
1.01647058823529420.864
941102AE2-104 E
Adder
4.4294117647058833.765
3145256KINGFORK
Adder
0.84823529411764710.721
3150921YORKTN3
Adder
100.3188235294117785.271
3138116ELKO L286
Adder
1.17294117647058820.997
927041AC1-191 C
Adder
7.99294117647058756.794
940541AE2-040 C
Adder
2.25764705882352961.919
940481AE2-033 C
Adder
12.71176470588235210.805
940482AE2-033 E
Adder
8.5694117647058837.284
961611AG1-000B C
Adder
13.42823529411764711.414
316004AC1-112 C
50/50
0.2780.278
3142296MT RD221
50/50
0.1030.103
944641AF1-129 C
Adder
87.0435294117647173.987
316240AF1-291 C
Adder
1.8317647058823531.557
3145723EMPORIA
Adder
0.332941176470588240.283
924814AB2-134 E
Adder
10.6952941176470599.091
920042AA2-088 E OP
Adder
8.4752941176470587.204
934521AD1-076 C
Adder
9.8494117647058838.372
934511AD1-075 C
Adder
6.785.763
942342AE2-247 E
Adder
1.71764705882352931.46
919152AA1-139 E1
Adder
3.39764705882352922.888
316312AB1-027 C
50/50
0.4460.446
3150451FOUR RIVERC
50/50
3.2063.206
933502AC2-165 E
Adder
5.7164705882352944.859
940432AE2-027 E
Adder
7.2905882352941186.197
939411AE1-173 C
Adder
71.6988235294117760.944
934012AD1-025 E
Adder
8.4541176470588247.186
913392Y1-086 E
Adder
1.82117647058823541.548
939612AE1-191 E
Adder
4.5694117647058823.884
957602AF2-054 E
Adder
1.12941176470588230.96
316303AF2-085
50/50
3.1343.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.92243.922
G-007PJM->LTFIMP_G-007
CMTX_NF
6.1246.124
CPLELTFEXP_CPLE->PJM
CLTF
8.8478.847
SIGELTFEXP_SIGE->PJM
CLTF
0.3210.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.96124.961
NYPJM->LTFIMP_NY
CLTF
2.7142.714
TVALTFEXP_TVA->PJM
CLTF
6.3246.324
O66PJM->LTFIMP_O-066
CMTX_NF
38.87538.875
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
1.7421.742
MECLTFEXP_MEC->PJM
CLTF
4.9474.947
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2224.222
CBM South 2LTFEXP_CBM-S2->PJM
CBM
78.96778.967
WECLTFEXP_WEC->PJM
CLTF
0.8990.899
LAGNLTFEXP_LAGN->PJM
CLTF
7.8857.885

Details for 8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.31 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4286.27
MW Contribution:216.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316222AC1-221 C
50/50
2.6372.637
927255AC1-221 E
50/50
6.9166.916
316237AB2-079 C O1
50/50
0.4550.455
934622AD1-088 E
50/50
10.28810.288
934611AD1-087 C
50/50
2.842.84
934612AD1-087 E
50/50
8.2238.223
3151621KERR 5
50/50
1.6151.615
3151611KERR 4
50/50
1.6151.615
940641AE2-051 C
Adder
-21.040000000000003-17.884
964211AG1-282 C
Adder
-1.7011764705882353-1.446
958211AF2-115 C
Adder
2.88588235294117632.453
936262AD2-033 E
50/50
11.62211.622
3151051BRUNSWICKS1
50/50
52.26552.265
3147133PAMPLIN
Adder
1.261.071
927264AC1-222 E
50/50
7.1497.149
3152411Z1-086 GT1
50/50
33.47433.474
3152441Z1-086 ST
50/50
58.26658.266
3138533PONTONDP
Adder
0.85529411764705890.727
316131AB2-060 C
50/50
2.042.04
3151631KERR 6
50/50
1.6151.615
936171AD2-023 C
Adder
7.0929411764705886.029
961791AG1-021 C
Adder
2.30941176470588251.963
936261AD2-033 C
50/50
17.43217.432
316248AF1-058 C
50/50
0.5710.571
962562AG1-105 E
50/50
9.4059.405
3151531CLOVER1
50/50
28.86828.868
963041AG1-153 C
50/50
17.10317.103
942001AE2-212 C
Adder
-2.010588235294118-1.709
942461AE2-259 C
Adder
12.19882352941176510.369
936162AD2-022 E
Adder
7.29529411764705856.201
946301AF1-294 C
Adder
4.7458823529411774.034
316283AC2-100 C
50/50
2.1162.116
935172AD1-152 E
50/50
11.76211.762
934621AD1-088 C
50/50
21.36821.368
957482AF2-042 E
50/50
86.59186.591
961792AG1-021 E
Adder
1.96705882352941171.672
3152661PLYWOOD A
50/50
2.0932.093
937482AD2-202 E
50/50
2.4072.407
3151021BRUNSWICKG1
50/50
25.15825.158
936172AD2-023 E
Adder
3.8505882352941183.273
958212AF2-115 E
Adder
2.45882352941176442.09
316034AC1-036 C
50/50
0.3110.311
316118AC1-105 C
50/50
1.5721.572
964241AG1-285 C
50/50
17.07617.076
962561AG1-105 C
50/50
14.10814.108
3151541CLOVER2
50/50
28.59928.599
963042AG1-153 E
50/50
25.65425.654
926024AC1-080 E
50/50
1.5621.562
936161AD2-022 C
Adder
12.15882352941176610.335
959312AF2-222 E
50/50
14.77814.778
3147223TWITTYS
50/50
1.2661.266
924022AB2-043 E O1
50/50
7.1597.159
935171AD1-152 C
50/50
2.8492.849
3151601KERR 3
50/50
1.6151.615
3151581KERR 1
50/50
0.5770.577
940081AE1-250 C
Adder
12.86117647058823510.932
942462AE2-259 E
Adder
8.1329411764705886.913
925997AC1-075 E
50/50
4.7084.708
964791AG1-342 C
50/50
5.7665.766
316239AB2-077 C O1
50/50
0.4550.455
3151041BRUNSWICKG3
50/50
25.15825.158
957601AF2-054 C
Adder
-1.8-1.53
24401205PINNACLE
Adder
1.6670588235294121.417
946302AF1-294 E
Adder
4.01882352941176453.416
316003AC1-222 C
50/50
1.7441.744
943902AF1-058 E
50/50
2.342.34
924322AB2-079 E O1
50/50
1.8631.863
957481AF2-042 C
50/50
129.887129.887
932763AC2-100 E
50/50
4.6734.673
964242AG1-285 E
50/50
11.38411.384
964792AG1-342 E
50/50
3.8443.844
924162AB2-060 E OP
50/50
5.8965.896
313527AB2-043 C
50/50
0.7110.711
3151641KERR 7
50/50
1.6151.615
3151031BRUNSWICKG2
50/50
25.15825.158
933291AC2-141 C
Adder
-32.203529411764706-27.373
942752AE2-291 E
Adder
8.0741176470588246.863
924302AB2-077 E O1
50/50
1.8631.863
316238AB2-078 C O1
50/50
0.4550.455
3152421Z1-086 GT2
50/50
33.46533.465
938531AE1-072 C
Adder
-16.01294117647059-13.611
944641AF1-129 C
Adder
-90.49176470588236-76.918
316240AF1-291 C
Adder
-1.9317647058823528-1.642
940082AE1-250 E
Adder
8.5741176470588247.288
942751AE2-291 C
Adder
12.11176470588235310.295
316205AC1-080 C
50/50
0.4520.452
316123AC1-075 C
50/50
1.3531.353
959311AF2-222 C
50/50
22.05622.056
937481AD2-202 C
50/50
0.8240.824
3151591KERR 2
50/50
1.6151.615
925785AC1-054 E
Adder
2.96470588235294132.52
925612AC1-036 E
50/50
1.1421.142
926274AC1-105 E
50/50
4.6164.616
924312AB2-078 E O1
50/50
1.8631.863
3152431Z1-086 GT3
50/50
33.46533.465
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.06671.066
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6814.681
CPLELTFEXP_CPLE->PJM
CLTF
19.41719.417
SIGELTFEXP_SIGE->PJM
CLTF
0.5240.524
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.76444.764
NYPJM->LTFIMP_NY
CLTF
2.1082.108
TVALTFEXP_TVA->PJM
CLTF
11.71211.712
O66PJM->LTFIMP_O-066
CMTX_NF
29.75629.756
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
2.7422.742
MECLTFEXP_MEC->PJM
CLTF
8.3488.348
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.2639.263
CBM South 2LTFEXP_CBM-S2->PJM
CBM
170.641170.641
WECLTFEXP_WEC->PJM
CLTF
1.451.45
LAGNLTFEXP_LAGN->PJM
CLTF
14.84614.846

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.94 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3379.54
MW Contribution:40.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926785AC1-164_E
Adder
13.34823529411764811.346
926004AC1-076_E
50/50
4.684.68
316084AB2-161 E
Adder
4.4435294117647063.777
940641AE2-051 C
50/50
13.8813.88
316076AC2-137 E
Adder
0.99176470588235290.843
3150831SPRUNCA
50/50
7.377.37
3150841SPRUNCB
50/50
7.377.37
923862AB2-026 E
Adder
0.96705882352941170.822
316045AC1-158 C2
50/50
14.72914.729
316044AC1-158 C1
50/50
14.72914.729
923852AB2-025 E
Adder
0.90941176470588240.773
3151051BRUNSWICKS1
50/50
13.28713.287
941032AE2-094 E
50/50
13.99213.992
941031AE2-094 C
50/50
31.24231.242
939412AE1-173 E
50/50
48.51748.517
916192Z1-068 E
Adder
1.51058823529411781.284
3151081ELIZAR1
50/50
2.5662.566
926662AC1-147 E
Adder
1.06470588235294120.905
957492AF2-043 E
Adder
1.13882352941176480.968
316233AE1-074 C
50/50
2.0822.082
926739AC1-158 E1
50/50
38.52538.525
3152411Z1-086 GT1
50/50
8.198.19
3152441Z1-086 ST
50/50
14.25614.256
935162AD1-151 E
Adder
8.4988235294117667.224
943461AF1-017 C
Adder
1.08235294117647070.92
316311AC2-079 C
Adder
4.5952941176470593.906
932596AC2-079 E
Adder
7.497647058823536.373
917122Z2-027 E
Adder
1.06941176470588250.909
3146326AYDLETT TAP
Adder
1.08470588235294120.922
938532AE1-072 E
Adder
7.3270588235294126.228
957832AF2-077 E
Adder
1.07764705882352940.916
944012AF1-069 E
50/50
3.9663.966
3150601CHESTF5
Adder
48.65647058823529441.358
925332AB2-190 E
Adder
6.3717647058823535.416
963041AG1-153 C
50/50
4.3484.348
944011AF1-069 C
50/50
10.20810.208
927226AC1-216 E
Adder
6.1082352941176475.192
3145413WATKINS
Adder
0.54117647058823540.46
936666AD2-085 E
Adder
4.5011764705882353.826
962962AG1-145 E
Adder
1.10235294117647080.937
938771AE1-103 C
Adder
2.30941176470588251.963
944591AF1-124 C
50/50
36.71436.714
944601AF1-125 C
50/50
36.02136.021
3151101ELIZAR3
50/50
2.5992.599
941591AE2-156 C
Adder
14.39882352941176612.239
958502AF2-144 E
Adder
0.95058823529411770.808
3152251N ANNA1
50/50
47.55247.552
316192AB2-158 C
50/50
1.8381.838
942001AE2-212 C
50/50
1.7341.734
939192AE1-149 E
50/50
5.7625.762
924517AB2-100 E2
Adder
2.21882352941176461.886
937226AE2-253 E
Adder
4.6788235294117653.977
934065AD1-033 E
Adder
4.0258823529411773.422
939312AE1-162 E
Adder
1.14235294117647060.971
3150861SPRUNCD
50/50
0.1320.132
3150651CHESTF6
Adder
14.8105882352941212.589
946262AF1-291 E
Adder
1.14588235294117660.974
3151021BRUNSWICKG1
50/50
6.3966.396
934576AD1-082 E
Adder
3.5411764705882353.01
933292AC2-141 E
50/50
10.44910.449
944602AF1-125 E
50/50
82.45882.458
957871AF2-081 C
Adder
7.9988235294117666.799
3145506HICKORY
Adder
1.7482352941176471.486
943612AF1-032 E
Adder
0.740.629
316169AC1-164 GEN
Adder
29.7105882352941225.254
925022AB2-158 E
50/50
4.8864.886
963042AG1-153 E
50/50
6.5226.522
316349AD2-085 C
Adder
2.7588235294117652.345
938772AE1-103 E
Adder
3.18941176470588242.711
916042Z1-036 E
Adder
22.54588235294117719.164
944592AF1-124 E
50/50
84.07784.077
944582AF1-123 E
50/50
83.77383.773
923832AB2-022 E
Adder
0.98941176470588230.841
3151091ELIZAR2
50/50
2.5212.521
935112AD1-144 E
Adder
0.75294117647058820.64
3152261N ANNA2
50/50
47.5747.57
924516AB2-100 E1
Adder
2.21882352941176461.886
940642AE2-051 E
50/50
9.2539.253
943462AF1-017 E
Adder
1.76470588235294111.5
942341AE2-247 C
Adder
1.19529411764705881.016
919153AA1-139 E2
Adder
3.27058823529411762.78
958162AF2-110 E
Adder
1.74000000000000021.479
316164AC1-076_C
50/50
0.8170.817
3143316POE
50/50
1.1011.101
939191AE1-149 C
50/50
8.6438.643
3151041BRUNSWICKG3
50/50
6.3966.396
901082W1-029 E
Adder
25.35058823529411521.548
942002AE2-212 E
50/50
1.1561.156
940431AE2-027 C
Adder
10.2917647058823528.748
957481AF2-042 C
Adder
12.04117647058823510.235
316294AC1-161 C
50/50
3.9863.986
944581AF1-123 C
50/50
36.58436.584
941101AE2-104 C
Adder
2.68117647058823532.279
944631AF1-128 C
Adder
30.4447058823529425.878
3150851SPRUNCC
50/50
0.1320.132
938552AE1-074 E
50/50
1.0491.049
938562AE1-075 E
Adder
0.82470588235294120.701
3151031BRUNSWICKG2
50/50
6.3966.396
316160AE1-175 E
Adder
0.90941176470588240.773
933291AC2-141 C
50/50
24.47824.478
926755AC1-161 E
50/50
10.44910.449
957872AF2-081 E
Adder
3.42823529411764752.914
925522AC1-027 E
Adder
0.97764705882352940.831
941102AE2-104 E
Adder
4.2623529411764713.623
3145256KINGFORK
Adder
0.81058823529411760.689
3150921YORKTN3
Adder
92.9023529411764778.967
3150731STONECA
Adder
5.4305882352941184.616
3152421Z1-086 GT2
50/50
8.1888.188
935161AD1-151 C
Adder
12.74823529411764710.836
3145393UNCAMP
Adder
4.7823529411764714.065
938531AE1-072 C
Adder
14.05529411764705811.947
932046AC2-012 E
Adder
10.5364705882352958.956
958161AF2-110 C
Adder
1.09411764705882360.93
944641AF1-129 C
Adder
81.343529411764769.142
316240AF1-291 C
Adder
1.721.462
924814AB2-134 E
Adder
10.004705882352948.504
942342AE2-247 E
Adder
1.65176470588235281.404
919152AA1-139 E1
Adder
3.27058823529411762.78
940432AE2-027 E
Adder
6.8611764705882355.832
939411AE1-173 C
50/50
72.77672.776
934012AD1-025 E
Adder
7.9070588235294126.721
913392Y1-086 E
Adder
1.75294117647058821.49
3138116ELKO L286
Adder
1.03411764705882360.879
926740AC1-158 E2
50/50
38.52538.525
940541AE2-040 C
Adder
2.24941176470588241.912
940481AE2-033 C
Adder
12.64705882352941110.75
940482AE2-033 E
Adder
8.5258823529411767.247
3152431Z1-086 GT3
50/50
8.1888.188
961611AG1-000B C
Adder
12.62823529411764810.734
316303AF2-085
50/50
3.2933.293
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.62115.621
NYPJM->LTFIMP_NY
CLTF
2.0512.051
TVALTFEXP_TVA->PJM
CLTF
4.3954.395
O66PJM->LTFIMP_O-066
CMTX_NF
27.29527.295
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.8310.831
MECLTFEXP_MEC->PJM
CLTF
2.5882.588
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.9113.911
CBM South 2LTFEXP_CBM-S2->PJM
CBM
69.2669.26
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
LAGNLTFEXP_LAGN->PJM
CLTF
5.5035.503
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.47618.476
G-007PJM->LTFIMP_G-007
CMTX_NF
4.2794.279
CPLELTFEXP_CPLE->PJM
CLTF
8.2058.205
SIGELTFEXP_SIGE->PJM
CLTF
0.1630.163
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314218 to 314908 ckt 1
314218 to 314908 ckt 2
314322 to 314914 ckt 1
314911 to 314922 ckt 1
314940 to 941030 ckt 1
314934 to 314916 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AF2-042 was evaluated as a 500.0 MW injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 1 Cluster 45 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 45 projects.

Table 1: Transition Cycle 1 Cluster 45 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO (MW)

MWE (MW)

MWC (MW)

Point of Interconnection

45

AF2-042

Solar

Dominion

500

500

300

Clover-Finneywood 500 kV

AG1-098

Solar

Dominion

107

107

64.2

Briery-Finneywood 230 kV

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 45 projects will meet the dynamics requirements of the NERC, Dominion Energy, and PJM reliability standards.

 

The load flow scenario for the analysis was based on the Regional Transmission Expansion Plan (RTEP) 2027 summer peak case, modified to include applicable projects. Cluster 45 projects have been dispatched online at maximum power output with near unity power factor measured at the high-side of the main substation transformer.

 

Cluster 45 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. 104 contingencies were studied, each with a 30 second simulation time period. The studied contingencies included:

  • Steady-state operation (30 seconds)
  • Three-phase faults with normal clearing time
  • Single-phase bus faults with normal clearing time
  • Single-phase faults with stuck breaker
  • Single-phase faults with delayed clearing at remote end
  • Three-phase faults with loss of multiple-circuit tower line

 

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all of the fault contingencies tested on the RTEP 2027 summer peak case:

 

  • Cluster 45 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  • The system with Cluster 45 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.
  • Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus) and the final voltages are within the steady-state voltage ranges below per Dominion Energy’s transmission planning criteria.
    • P1 Category Contingencies:
      • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.01 to 1.096 p.u. for 500 kV facilities
    • P2, P4, P5, and P7 Category Contingencies:
      • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.00 to 1.096 p.u. for 500 kV facilities
  • No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

The results of the analysis indicated all evaluation criteria were met.

 

The following observations were made:

 

AF2-042’s reactive power took longer than 20 seconds to settle to a steady state value  While this is not a criteria violations the model could be tuned to decrease the settling time.

Contingencies P123, P124 and P125 diverged due to the AG1-098 queue project.  This issue was resolved by updating the PSS/E Dynamic Simulation Acceleration factor from 0.5 and 0.25.

Controller oscillations were observed for AG1-098 Generators 1 & 2 during the fault on selected P4 contingencies. After the fault is cleared, no controller oscillations were observed. This did not cause instability and is not a concern.

 

AD2-202 tripped due to the overvoltage protection (1.12 p.u. in 5 seconds). When the protection model was disabled the units reached terminal voltages above 1.12 p.u. with its reactive power reaching its upper limit.  To resolve the tripping the transformer tap on the high side of the AD1-087 and AD2-202 main station transformers was changed to 1.05 p.u and by changing the two projects to control the POI voltage in the power flow case.

 

No mitigation was required.

Reactive Power Analysis

The reactive power capability of AF2-042 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-065Earleys 230kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-088Boykins-Handsome 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB1-173Brink-Trego 115kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-100Clubhouse-Lakeview 230kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVEngineering & Procurement
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-080Perth-Hickory Grove 115kVIn Service
AC1-086Thelma 230kVUnder Construction
AC1-098Dawson-South Justice 115kVIn Service
AC1-099Dawson-South Justice 115kVIn Service
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-216Hopewell-Surry 230kVIn Service
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVUnder Construction
AC2-084Dawson-South Justice 115kVIn Service
AC2-100Halifax-Person 230kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-103Holland-Union Camp 115 kVSuspended
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-149Disputanta-Poe 115 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE2-027Harrowgate-Locks 115kVSuspended
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVIn Service
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVWithdrawn
AE2-156Yadkin 115 kVEngineering & Procurement
AE2-185Gladys DP-Stonemill Switching Station 69 kVEngineering & Procurement
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-247Myrtle-Windsor 115 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVEngineering & Procurement
AE2-346Ahoskie 34.5 kVIn Service
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-123Harper 230 kVUnder Construction
AF1-124Harper 230 kVPartially in Service - Under Construction
AF1-125Harper 230 kVUnder Construction
AF1-128Chesterfield 230 kVUnder Construction
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVUnder Construction
AF1-294Jetersville-Ponton 115 kVEngineering & Procurement
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-081Moyock 230 kVEngineering & Procurement
AF2-085Midlothian 34.5 kVIn Service
AF2-110Suffolk 115 kVWithdrawn
AF2-115Jetersville-Ponton 115 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVEngineering & Procurement
AF2-299Fields 34.5 kVEngineering & Procurement
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-021Jetersville-Ponton 115 kVEngineering & Procurement
AG1-037Ahoskie 34.5 kVWithdrawn
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-105Mount Laurel-Barnes Junction 115 kVUnder Construction
AG1-135Garner-Lancaster 115 kVUnder Construction
AG1-145Lightfoot 34.5 kVIn Service
AG1-153Heritage 500 kVUnder Construction
AG1-285Chase City-Central 115 kVEngineering & Procurement
AG1-342Dryburg 115 kVEngineering & Procurement
AG1-532Fields 34.5 kVUnder Construction
V4-068Murphy's 34.5kVIn Service
W1-029Winfall 230kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z1-068Birdneck 34.5kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-088Tarboro-Everetts 230kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In coordination with other Affected System Operators, PJM has determined that the Affected System Operator for this project that requires an Affected System Study. For the latest Affected System Study results pertaining this project, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM lists any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AF2-042 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$25,653,730
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$22,942,056
Dominionn9220.0Wreck and rebuild 15.49 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.Cost Allocated$20,532,412
Dominionn9217.0Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.Cost Allocated$18,661,737
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$14,632,826
Dominionn9378.0Replace existing 230/500 kV Carson transformer #1 with (4)-480 MVA single phase transformers.Cost Allocated$8,947,219
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$8,097,127
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$6,382,333
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$5,185,997
Dominionn9681.0Upgrade 1.04 Miles of 230kV transmission line 249 from 249/86 to 249/93Cost Allocated$2,048,312
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0N/A
Dominionb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0N/A
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0N/A
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0N/A
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0N/A
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0N/A
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0N/A
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0N/A
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0N/A
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0N/A
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0N/A
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0N/A
Dominionb4030.1Chesterfield-Basin 230 kV rebuild: Wreck and rebuild approximately 12.5 miles of Chesterfield-Basin 230 kV line.Contingent$0N/A
Dominionb4030.3Basin 230 kV substation scope: Replace all terminal equipment, line leads and bus at Basin 230 kV substation to be rated to 4000A.Contingent$0N/A
Dominionb4030.4Chesterfield 230 kV substation scope: Install a new 230 kV, 80 kA 4000A circuit breaker at Chesterfield 230 kV substation.Contingent$0N/A
Dominions3671.5Rebuild Line 238 from Carson to Clubhouse for a normal summer rating of 1573 MVAContingent$0N/A
Dominionb4000.315Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.Contingent$0N/A
Dominionb4000.316At Poe substation, uprate all Line #2003 terminal equipment, line leads, and bus to be rated to 4000A.Contingent$0N/A
Dominionb4000.317At Tyler substation, upgrade the necessary line terminal equipment to maintain 4000A at Tyler substation.Contingent$0N/A
Dominionb4053.18Rebuild approximately 37.4 miles of 500 kV line No. 563 from Carson-Midlothian.Contingent$0N/A
Dominionb4053.19Uprate 500 kV line No. 563 associated terminal equipment at Carson to 5000A standards.Contingent$0N/A
Dominionb4053.20Uprate 500 kV line No. 563 associated terminal equipment at Midlothian to 5000A standards.Contingent$0N/A
Dominionb4053.21Uprate 500 kV line No. 567 associated terminal equipment at Chickahominy to 5000A standards.Contingent$0N/A
Dominionb4053.22Uprate 500 kV line No. 567 associated terminal equipment at Surry to 5000A standards.Contingent$0N/A
Dominionb4053.27Upgrade/install 6000A equipment at Midlothian substation to support the new conductor termination from Vontay.Contingent$0N/A
Dominionb4053.6Rebuild 20 miles of 500 kV line No. 576 from North Anna substation to Vontay substation using 6000A conductor.Contingent$0N/A
Dominionb4053.7Upgrade/install 6000A equipment at North Anna substation to support the new conductor termination.Contingent$0N/A
Dominionb4053.26Rebuild 20 miles of 500 kV line No. 576 from Vontay substation to Midlothian substation using 6000A conductor.Contingent$0N/A
Grand Total:$133,083,749

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9138.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9138.0 / TC1-PH1-DOM-070
Title
ELIM TC1: Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.
Description
Wreck and rebuild 22.59 miles of Line 511 between Carson and Rawlings with three (3) 1351 ACSS/TW and associated substation work.
Total Cost ($USD)
$111,130,292
Discounted Total Cost ($USD)
$30,620,771
Allocated Cost ($USD)
$30,620,771
Time Estimate
60 to 61 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-042278.1 MW100.0%$30,620,771

System Reinforcement: n9250.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9250.0 / TC1-PH2-DOM-044
Title
ELIM TC1: Construct a new 22.59 mile line between Carson and Rawlings Substations.
Description
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Total Cost ($USD)
$108,728,086
Discounted Total Cost ($USD)
$29,958,869
Allocated Cost ($USD)
$29,958,869
Time Estimate
60 to 61 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-042278.1 MW100.0%$29,958,869

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-040
Title
ELIM TC1: Wreck and rebuild 18.75 miles of Line 594 btwn Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) Dipper at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 18.75 miles of Line 594 between Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$128,018,212
Discounted Total Cost ($USD)
$35,274,058
Allocated Cost ($USD)
$10,566,803
Time Estimate
60 to 61 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
39.9 MW23.4%$8,268,348
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
40.1 MW23.5%$8,297,767
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
39.3 MW23.1%$8,141,139
AF2-04251.0 MW30.0%$10,566,803

System Reinforcement: n9247.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9247.0 / TC1-PH2-DOM-041
Title
ELIM TC1: Wreck and rebuild 14.02 miles of Line 573 btwn Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 14.02 miles of Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA
Total Cost ($USD)
$99,636,684
Discounted Total Cost ($USD)
$27,453,830
Allocated Cost ($USD)
$8,243,285
Time Estimate
48 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
40.9 MW23.4%$6,428,872
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
41.0 MW23.5%$6,451,820
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
40.3 MW23.1%$6,329,853
AF2-04252.4 MW30.0%$8,243,285

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.49 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Discounted Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$20,532,412
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
6BUCKING-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A796.0 MVA
(All)B796.0 MVA
(All)C964.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE2-29113.6 MW3.8%$1,705,384
AF1-294 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
17.8 MW5.0%$2,229,393
AF2-042163.5 MW46.2%$20,532,412
AF2-115 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
10.8 MW3.1%$1,359,435
AF2-22265.0 MW18.3%$8,159,120
AG1-021 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
8.7 MW2.4%$1,087,573
AG1-10523.6 MW6.7%$2,967,877
AG1-28541.9 MW11.8%$5,264,576
AG1-3429.2 MW2.6%$1,160,153

System Reinforcement: n9217.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9217.0 / TC1-PH2-DOM-028
Title
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$40,414,822
Discounted Total Cost ($USD)
$40,414,822
Allocated Cost ($USD)
$18,661,737
Time Estimate
45 to 46 Months

Contributor

FacilityContingency
6BUCKING-6FARMVIL 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A797.0 MVA
(All)B797.0 MVA
(All)C1116.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE2-29113.6 MW3.8%$1,550,409
AF1-294 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
17.8 MW5.0%$2,026,247
AF2-042163.5 MW46.2%$18,661,737
AF2-115 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
10.8 MW3.1%$1,235,466
AF2-22265.0 MW18.3%$7,415,536
AG1-021 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
8.7 MW2.4%$988,419
AG1-10523.6 MW6.7%$2,697,555
AG1-28541.9 MW11.8%$4,784,850
AG1-3429.2 MW2.6%$1,054,602

System Reinforcement: n9379.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9379.0 / TC1-PH3-DOM-011
Title
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.
Description
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase 500/230 kV transformers.
Total Cost ($USD)
$37,836,293
Discounted Total Cost ($USD)
$10,425,388
Allocated Cost ($USD)
$3,504,341
Time Estimate
Oct 01 2029

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
18.6 MW22.2%$2,316,170
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
18.6 MW22.3%$2,324,409
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
18.3 MW21.9%$2,280,468
AF2-04228.1 MW33.6%$3,504,341

System Reinforcement: n9378.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9378.0 / TC1-PH3-DOM-010
Title
Replace existing 230/500 kV Carson transformer #1 with (4)-480 MVA single phase transformers.
Description
Replace Existing 230/500 kV Carson transformer #1 with (4)-480 MVA Single Phase transformers. 6CARSON - 8CARSON ckt 2 represents tranformer #1.
Total Cost ($USD)
$37,801,301
Discounted Total Cost ($USD)
$37,801,301
Allocated Cost ($USD)
$8,947,219
Time Estimate
Mar 29 2029

Contributor

FacilityContingency
6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer(Any)
Rating SetRating TypeRating Value
LLA2016.0 MVA
LLB2083.0 MVA
LLC2239.0 MVA
SUMA1707.0 MVA
SUMB1758.0 MVA
SUMC1873.0 MVA
WINA2196.0 MVA
WINB2228.0 MVA
WINC2308.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
56.2 MW22.4%$8,456,365
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
56.5 MW22.5%$8,486,733
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
55.4 MW22.0%$8,324,368
AF2-04259.5 MW23.7%$8,947,219
AF2-22212.2 MW4.8%$1,827,058
AG1-15311.7 MW4.7%$1,759,557

System Reinforcement: n9681.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9681.0
Title
Upgrade 1.04 Miles of 230kV transmission line 249 from 249/86 to 249/93
Description
Reconductor 1.04 miles of 2*636 ACSR 24/7 MOT 150 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" MOT 250 on 230 kV line 249 between Carson and Chaparral
Total Cost ($USD)
$3,042,004
Discounted Total Cost ($USD)
$3,042,004
Allocated Cost ($USD)
$2,048,312
Time Estimate
20 to 21 Months

Contributor

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1442.0 MVA
LLB1540.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1493.0 MVA
WINB1587.0 MVA
WINC1631.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-04256.7 MW67.3%$2,048,312
AF2-22215.0 MW17.8%$541,856
AG1-28512.5 MW14.9%$451,836

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-L
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029
Cost Alloc Type
Contingent

System Reinforcement: b4030.1
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.1
Title
Chesterfield-Basin 230 kV rebuild: Wreck and rebuild approximately 12.5 miles of Chesterfield-Basin 230 kV line.
Description
Chesterfield-Basin 230 kV rebuild: Wreck and rebuild approximately 12.5 miles of Chesterfield-Basin 230 kV line.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1572.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.3
Title
Basin 230 kV substation scope: Replace all terminal equipment, line leads and bus at Basin 230 kV substation to be rated to 4000A.
Description
Basin 230 kV substation scope: Replace all terminal equipment, line leads and bus at Basin 230 kV substation to be rated to 4000A.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1572.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.4
Title
Chesterfield 230 kV substation scope: Install a new 230 kV, 80 kA 4000A circuit breaker at Chesterfield 230 kV substation.
Description
Chesterfield 230 kV substation scope: Install a new 230 kV, 80 kA 4000A circuit breaker at Chesterfield 230 kV substation.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1572.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b3694.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3694.8
Title
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA.
Description
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA. Upgrade terminal equipment at Carson and Locks to not limit the new conductor rating.
Cost Information
Time Estimate
May 03 2025

Not Contingent

Note: AF2-042 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-042 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1047.0 MVA
(All)B1047.0 MVA
(All)C1204.0 MVA
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA

System Reinforcement: s3671.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3671.5
Title
Rebuild Line 238 from Carson to Clubhouse for a normal summer rating of 1573 MVA
Description
Rebuild Line 238 from Carson to Clubhouse for a normal summer rating of 1573 MVA
Cost Information
Time Estimate
Dec 31 2030

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA
6SAPONY-AE2-033 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.315
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.315
Title
Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.
Description
Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Apr 22 2030

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6TYLER1-6POE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA

System Reinforcement: b4000.316
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.316
Title
At Poe substation, uprate all Line #2003 terminal equipment, line leads, and bus to be rated to 4000A.
Description
At Poe substation, uprate all Line #2003 terminal equipment, line leads, and bus to be rated to 4000A.
Cost Information
Time Estimate
Apr 22 2030

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6TYLER1-6POE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA

System Reinforcement: b4000.317
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.317
Title
At Tyler substation, upgrade the necessary line terminal equipment to maintain 4000A at Tyler substation.
Description
At Tyler substation, upgrade the necessary line terminal equipment to maintain 4000A at Tyler substation.
Cost Information
Time Estimate
Apr 22 2030

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6TYLER1-6POE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA

System Reinforcement: b4053.18
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.18
Title
Rebuild approximately 37.4 miles of 500 kV line No. 563 from Carson-Midlothian.
Description
Rebuild approximately 37.4 miles of 500 kV line No. 563 from Carson-Midlothian. The proposed structures to be installed are mainly 500/230 kV double-circuit V-string suspension towers. The 230 kV circuit position will be vacant at the completion of this project but serves to accommodate a future 230 kV line.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4357.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA5155.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b4053.19
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.19
Title
Uprate 500 kV line No. 563 associated terminal equipment at Carson to 5000A standards.
Description
Uprate 500 kV line No. 563 associated terminal equipment at Carson to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4357.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA5155.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b4053.20
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.20
Title
Uprate 500 kV line No. 563 associated terminal equipment at Midlothian to 5000A standards.
Description
Uprate 500 kV line No. 563 associated terminal equipment at Midlothian to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4357.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA5155.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b4053.21
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.21
Title
Uprate 500 kV line No. 567 associated terminal equipment at Chickahominy to 5000A standards.
Description
Uprate 500 kV line No. 567 associated terminal equipment at Chickahominy to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3322.0 MVA
(All)B3425.0 MVA
(All)C3939.0 MVA
WINA4191.0 MVA
WINB4376.0 MVA
WINC5032.0 MVA

System Reinforcement: b4053.22
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.22
Title
Uprate 500 kV line No. 567 associated terminal equipment at Surry to 5000A standards.
Description
Uprate 500 kV line No. 567 associated terminal equipment at Surry to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3322.0 MVA
(All)B3425.0 MVA
(All)C3939.0 MVA
WINA4191.0 MVA
WINB4376.0 MVA
WINC5032.0 MVA

System Reinforcement: b4053.27
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.27
Title
Upgrade/install 6000A equipment at Midlothian substation to support the new conductor termination from Vontay.
Description
Upgrade/install 6000A equipment at Midlothian substation to support the new conductor termination from Vontay.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: b4053.6
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.6
Title
Rebuild 20 miles of 500 kV line No. 576 from North Anna substation to Vontay substation using 6000A conductor.
Description
Rebuild 20 miles of 500 kV line No. 576 from North Anna substation to Vontay substation using 6000A conductor.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: b4053.7
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.7
Title
Upgrade/install 6000A equipment at North Anna substation to support the new conductor termination.
Description
Upgrade/install 6000A equipment at North Anna substation to support the new conductor termination.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: b4053.26
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.26
Title
Rebuild 20 miles of 500 kV line No. 576 from Vontay substation to Midlothian substation using 6000A conductor.
Description
Rebuild 20 miles of 500 kV line No. 576 from Vontay substation to Midlothian substation using 6000A conductor.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AF2-042 may not presently have cost responsibility for this upgrade, AF2-042 may need this upgrade in-service to be deliverable to the PJM system. If AF2-042 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: n8492

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492
Title
Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.
Description
Wreck and rebuild one (1) overhead 500kV transmission line that will start at the existing Fentress 500 kV Substation and terminate at the existing Yadkin 500 kV Substation, located approximately 13.5 miles away.
Total Cost ($USD)
$80,172,278
Allocated Cost ($USD)
$25,653,730
Time Estimate
Dec 31 2026
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$10,783,252
AF1-12413.4979 %$10,821,574
AF1-12513.2418 %$10,616,253
AF1-2940.3249 %$260,480
AF2-04231.9983 %$25,653,766
AF2-1150.1981 %$158,821
AF2-1205.8297 %$4,673,803
AF2-2223.9954 %$3,203,203
AG1-0210.1585 %$127,073
AG1-1243.1793 %$2,548,917
AG1-1355.5860 %$4,478,423
AG1-2852.9906 %$2,397,632
AG1-5365.5494 %$4,449,080

System Reinforcement: n9630.0

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Allocated Cost ($USD)
$22,942,056
Time Estimate
Dec 31 2029
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$9,643,430
AF1-12413.4979 %$9,677,702
AF1-12513.2418 %$9,494,084
AF1-2940.3249 %$232,946
AF2-04231.9983 %$22,942,088
AF2-1150.1981 %$142,033
AF2-1205.8297 %$4,179,769
AF2-2223.9954 %$2,864,615
AG1-0210.1585 %$113,641
AG1-1243.1793 %$2,279,489
AG1-1355.5860 %$4,005,041
AG1-2852.9906 %$2,144,195
AG1-5365.5494 %$3,978,800

System Reinforcement: n9267.0

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9267.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9267.0 / TC1-PH2-DOM-067
Title
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.
Description
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner substations with single (1) 768.2 ACSS/TW “Maumee” at 250 degrees C. This new line will be on separate transmission towers from the existing Northern Neck and Moon Corner line 1059. Station expansion is required at Northern Neck and Moon Corner to accommodate the new line.
Total Cost ($USD)
$45,730,074
Allocated Cost ($USD)
$14,632,826
Time Estimate
45 to 46 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$6,150,741
AF1-12413.4979 %$6,172,600
AF1-12513.2418 %$6,055,485
AF1-2940.3249 %$148,577
AF2-04231.9983 %$14,632,846
AF2-1150.1981 %$90,591
AF2-1205.8297 %$2,665,926
AF2-2223.9954 %$1,827,099
AG1-0210.1585 %$72,482
AG1-1243.1793 %$1,453,896
AG1-1355.5860 %$2,554,482
AG1-2852.9906 %$1,367,604
AG1-5365.5494 %$2,537,745

System Reinforcement: n9259.0

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9259.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9259.0
Title
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Description
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Total Cost ($USD)
$25,304,902
Allocated Cost ($USD)
$8,097,127
Time Estimate
Jan 01 2030
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$3,403,535
AF1-12413.4979 %$3,415,630
AF1-12513.2418 %$3,350,825
AF1-2940.3249 %$82,216
AF2-04231.9983 %$8,097,138
AF2-1150.1981 %$50,129
AF2-1205.8297 %$1,475,200
AF2-2223.9954 %$1,011,032
AG1-0210.1585 %$40,108
AG1-1243.1793 %$804,519
AG1-1355.5860 %$1,413,532
AG1-2852.9906 %$756,768
AG1-5365.5494 %$1,404,270

System Reinforcement: n8492.1

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.1
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.1
Title
Two Breaker Additions at Fentress Substation.
Description
Install Two 5000 amp GIS Breakers at Fentress Substation to connect the new 500 kV line 5005.
Total Cost ($USD)
$19,945,879
Allocated Cost ($USD)
$6,382,333
Time Estimate
Dec 31 2026
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$2,682,741
AF1-12413.4979 %$2,692,275
AF1-12513.2418 %$2,641,193
AF1-2940.3249 %$64,804
AF2-04231.9983 %$6,382,342
AF2-1150.1981 %$39,513
AF2-1205.8297 %$1,162,785
AF2-2223.9954 %$796,918
AG1-0210.1585 %$31,614
AG1-1243.1793 %$634,139
AG1-1355.5860 %$1,114,177
AG1-2852.9906 %$596,501
AG1-5365.5494 %$1,106,877

System Reinforcement: n8492.2

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.2
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.2
Title
Expand Yadkin Substation to accommodate the new 500 kV line.
Description
Expansion of yadkins 500 kV switchyard to accommodate the new 500 kV line which includes addition of 5000 amp GIS breakers and relocation of the existing suffolk -yadkin 500 kV line#565
Total Cost ($USD)
$16,207,123
Allocated Cost ($USD)
$5,185,997
Time Estimate
Dec 31 2026
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$2,179,874
AF1-12413.4979 %$2,187,621
AF1-12513.2418 %$2,146,115
AF1-2940.3249 %$52,657
AF2-04231.9983 %$5,186,004
AF2-1150.1981 %$32,106
AF2-1205.8297 %$944,827
AF2-2223.9954 %$647,539
AG1-0210.1585 %$25,688
AG1-1243.1793 %$515,273
AG1-1355.5860 %$905,330
AG1-2852.9906 %$484,690
AG1-5365.5494 %$899,398

System Reinforcement: b4000.356

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.355

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.325

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.326

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.327

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: s3047.2

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: s3047.2
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3047.2
Title
Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.
Description
Install (2) 1400 MVA 500-230 kV transformers and associated 500 kV and 230 kV equipment (breakers, switches, leads) at Vint Hill Substation to supply the area with a 500 kV source Cut and loop 500 kV line #535 Loudoun – Meadowbrook and #569 Loudoun - Morrisville as the 500 kV sources into the proposed 500 kV ring bus Vint Hill Substation will be expanded to the north of the existing site to accommodate the 500 kV ring required for the addition of the new transformers Existing terminations for 230 kV line #2174 Wheeler – Vint Hill, line #2101 Bristers – Vint Hill, and line #2163 Liberty – Vint Hill will be rearranged to terminate into the expanded Vint Hill Substation 230 kV line #2114 Remington CT – Rollins Ford will also be cut and looped into the expanded Vint Hill Substation due to spatial constraints along the existing right-of-way.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.312

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.312
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.312
Title
Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.
Description
Rebuild 500kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. New conductor to have a summer rating of 4357 MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.313

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.313
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.313
Title
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Description
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.356

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.356
Title
Build a new 500 kV line from Vint Hill to Wishing Star.
Description
Build a new 500kV line from Vint Hill to Wishing Star. The line will be supported on single circuit monopoles. New conductor to have a summer rating of 4357 MVA. Line length is approximately 16.59 miles
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.357

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.357
Title
Build a new 500 kV line from Morrisville to Vint Hill.
Description
Build a new 500kV line from Morrisville to Vint Hill. New conductor to have a summer rating of 4357 MVA. Line length is approximately 19.71 miles.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.354

AF2-042 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.354
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.354
Title
Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.
Description
Install terminal equipment at Wishing Star substation to support a 5000A line to Vint Hill. Update relay settings for 500kV Lines #546 and #590.
Cost Information
Cost Alloc Type
Contingent

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AF2-042


AF2-042 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowDominionn9138.0 / TC1-PH1-DOM-070ELIM TC1: Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.Eliminated278.1 MW100.0%Cost Allocated$30,620,771
Load FlowDominionn9250.0 / TC1-PH2-DOM-044ELIM TC1: Construct a new 22.59 mile line between Carson and Rawlings Substations.Eliminated278.1 MW100.0%Cost Allocated$29,958,869
Load FlowDominion(Pending) / TC1-PH2-DOM-040ELIM TC1: Wreck and rebuild 18.75 miles of Line 594 btwn Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) Dipper at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)Eliminated51.0 MW30.0%Cost Allocated$10,566,803
Load FlowDominionn9247.0 / TC1-PH2-DOM-041ELIM TC1: Wreck and rebuild 14.02 miles of Line 573 btwn Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)Eliminated52.4 MW30.0%Cost Allocated$8,243,285
Load FlowDominionn9379.0 / TC1-PH3-DOM-011Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.Eliminated28.1 MW33.6%Cost Allocated$3,504,341
Load FlowDominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Topology-0.0%Contingent$0
Load FlowDominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Topology-0.0%Contingent$0
Load FlowDominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationTopology-0.0%Contingent$0
Load FlowDominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Topology-0.0%Contingent$0
Load FlowDominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$82,894,069
AF2-042 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$25,653,730
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$22,942,056
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$14,632,826
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$8,097,127
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$6,382,333
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$5,185,997
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0
Dominionb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0
Region Topology Upgrade Total:$82,894,069

Attachments

AF2-042 One Line Diagram

AF2-042 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.