AF2-115 Final System Impact Study (Retool 2) Report

v2.00 released 2026-05-14 11:52

Jetersville-Ponton 115 kV

13.5 MW Capacity / 25.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Amelia Energy Facility, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.

The AF2-115 Final System Impact Study (Retool 1) Report is available for download here.

Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Amelia County, Virginia. This project is an increase to the developer’s AF1-294 project(s), which will share the same Point of Interconnection. The AF2-115 project is a 25.0 MW uprate (13.5 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 66.0 MW with 35.7 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AF2-115
Project Name:
Jetersville-Ponton 115 kV
Project Developer Name:
Amelia Energy Facility, LLC
State:
Virginia
County:
Amelia
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
66.0
MWE:
25.0
MWC:
13.5
Fuel Type:
Solar
Basecase Study Year:
2027

Physical Interconnection Facility Study

Received

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AF2-115 will interconnect with the Dominion transmission system tapping the Jetersville to Ponton 115 kV line, sharing interconnection facilities with AF1-294 and AG1-021.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AF2-115 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AF2-115Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$956,979$956,979
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$1,370,721$1,370,721
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$2,594,901$2,594,901
Transient Stability$513,287$513,287
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0
AFS - Non-PJM Violations$0 **$0 **
Total$5,435,888$5,435,888

* Contributes to calculation for Security. See Security Requirement Section of this report for additional detail.

** This value reflects the results at the time of the report posting and it is subject to change. AFS – Non-PJM Violations are not subject to Security. For latest AFS – Non-PJM Violations, please refer to the latest Affected System Study Report for your project.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF1-294/AF2-115/AG1-021

Security has been calculated for the AF1-294/AF2-115/AG1-021 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF1-294/AF2-115/AG1-021
Project(s): AF1-294/AF2-115/AG1-021
Final Agreement Security (A): $17,675,327
Portion of Costs Already Paid (B): $0
Revised Net Security (C): A − B = $17,675,327
Security on Hand with PJM (D): $17,585,673
Additional Security Due at Agreement Execution (E): C − D = $89,653
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

The New Service Request Project will interconnect with the Dominion transmission system via a new three breaker ring bus switching station that connects on the Jetersville-Ponton 115 kV Line 1007.   The required work for the interconnection of the New Service Request Project to the Dominion Transmission System is detailed in the following tables.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

(No Transmission Owner Scope for this project.)

Developer Scope

Project Developer has elected the option Option to Build where they will assume responsibility for the design, procurement and construction of the Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades identified in this SIS report.

The Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n9415.0

Re-arrange Line #1007 to loop into and out of the new three-breaker AF1-294/AF2-115/AG1-021 115 kV switching station (including fiber).

$2,217,373$1,201,242$212,962$150,008$3,781,585$1,260,528 (See Note 1)
n9414.0

Remote Relay at Dennisville Road Substation.

$121,050$0$23,111$0$144,161$48,054 (See Note 1)
n9413.0

Remote Relay at Lone Pine Substation.

$128,143$28,809$24,385$5,080$186,417$62,139 (See Note 1)
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Transmission Owner Interconnection Facilities (oversight) Transmission Owner will review the Project Developer’s Option to Build design documents and drawings, provide construction oversight for Option to Build designated facilities and perform a protection and control equipment checkout and end-to-end testing.

$106,788$0$22,352$0$129,140$43,047 (See Note 1)
(Pending)

New interconnection substation (oversight) Transmission Owner will review the Project Developer’s Option to Build design documents and drawings, provide construction oversight for Option to Build designated facilities and perform a protection and control equipment checkout and end-to-end testing.

$1,918,075$387,747$400,710$35,266$2,741,798$913,933 (See Note 1)

Based on the scope of work for the Interconnection Facilities, it is expected to take 39 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

As shown in the oneline diagram, this Interconnection Request is sharing the Point of Interconnection and Interconnection Facilities with one or more other Interconnection Requests. Should other requests withdraw from Transition Cycle 1, the cost allocation for Transmission Owner Interconnection Facilities, Stand Alone Network Upgrades, and applicable Network Upgrades identified in the study report will be updated for the remaining project(s).

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2027 load flow model and the results were verified by Dominion.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AF2-115 was evaluated as a 25.0 MW (13.5 MW Capacity) injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BUCKING-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S-1
BreakerAC116.15 %699.0C811.9210.83
GD1DVP
6BUCKING-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC112.88 %571.52B645.125.84
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC109.81 %1204.0C1322.081.94
GD1DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC108.01 %1204.0C1300.421.94
GD1DVP
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S-1
BreakerAC117.22 %684.0C801.7910.83
GD1DVP
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC113.89 %559.3B636.995.84
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC110.41 %678.68B749.361.13
GD1DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 56372_SRT-S
BreakerAC113.54 %1056.8C1199.861.36
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S_SENS
SingleAC101.85 %3220.44B3279.972.95
GD1DVP
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC107.63 %678.68B730.451.14

Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.15 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:811.92
MW Contribution:10.83
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.96 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:845.48
MW Contribution:10.67
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936261AD2-033 C
50/50
27.66927.669
3144293JTRSVLE
50/50
1.0761.076
961791AG1-021 C
50/50
4.6774.677
962562AG1-105 E
Adder
9.4541176470588238.036
924032AB2-045 E
50/50
5.85.8
936262AD2-033 E
50/50
18.44618.446
958211AF2-115 C
50/50
5.8465.846
964241AG1-285 C
50/50
25.15525.155
316034AC1-036 C
50/50
0.5350.535
958212AF2-115 E
50/50
4.984.98
962561AG1-105 C
Adder
14.18117647058823612.054
957482AF2-042 E
50/50
65.40565.405
934621AD1-088 C
50/50
18.90418.904
946301AF1-294 C
50/50
9.6139.613
942461AE2-259 C
50/50
31.1431.14
935172AD1-152 E
Adder
8.887.548
925785AC1-054 E
Adder
3.35529411764705852.852
959311AF2-222 C
50/50
38.90838.908
942751AE2-291 C
Adder
8.1482352941176476.926
924022AB2-043 E O1
Adder
9.122352941176477.754
3147223TWITTYS
50/50
2.1732.173
959312AF2-222 E
50/50
26.06826.068
926024AC1-080 E
Adder
1.09882352941176480.934
937482AD2-202 E
Adder
1.86823529411764721.588
961792AG1-021 E
50/50
3.9843.984
941011AE2-092 C
Adder
-9.729411764705882-8.27
957481AF2-042 C
50/50
98.10798.107
924322AB2-079 E O1
Adder
2.3152941176470591.968
946302AF1-294 E
50/50
8.1418.141
943902AF1-058 E
Adder
1.841.564
925612AC1-036 E
50/50
1.961.96
924312AB2-078 E O1
Adder
2.3152941176470591.968
926274AC1-105 E
Adder
4.0129411764705883.411
938821AE1-108 C
Adder
-10.607058823529412-9.016
924302AB2-077 E O1
Adder
2.3152941176470591.968
942752AE2-291 E
Adder
5.4329411764705894.618
316336AC2-165 C
Adder
-5.905882352941176-5.02
934622AD1-088 E
50/50
9.1029.102
934612AD1-087 E
Adder
6.3835294117647065.426
927255AC1-221 E
Adder
4.1458823529411773.524
942462AE2-259 E
50/50
20.7620.76
964791AG1-342 C
Adder
5.5435294117647054.712
925997AC1-075 E
Adder
3.31294117647058832.816
3151531CLOVER1
50/50
22.49922.499
3138533PONTONDP
50/50
1.7321.732
3147133PAMPLIN
50/50
2.7572.757
316322AB2-045 C
50/50
1.2941.294
927264AC1-222 E
Adder
5.52000000000000054.692
964242AG1-285 E
50/50
16.7716.77
924162AB2-060 E OP
Adder
7.6670588235294136.517
964792AG1-342 E
Adder
3.6952941176470593.141
932763AC2-100 E
Adder
2.72941176470588242.32
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8050.805
SIGELTFEXP_SIGE->PJM
CLTF
0.0740.074
NYPJM->LTFIMP_NY
CLTF
0.3840.384
LGEELTFEXP_LGEE->PJM
CLTF
0.3670.367
WECLTFEXP_WEC->PJM
CLTF
0.1940.194
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.3429.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.2887.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.2261.226
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1652.165
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.04736.047
CPLELTFEXP_CPLE->PJM
CLTF
4.5424.542
TVALTFEXP_TVA->PJM
CLTF
2.0142.014
O66PJM->LTFIMP_O-066
CMTX_NF
5.1335.133

Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.88 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:645.12
MW Contribution:5.84
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.83 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:684.85
MW Contribution:5.76
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960081AF2-299 C
80/20
0.9410.941
3151391GASTONA
80/20
0.9230.923
3151631KERR 6
80/20
1.5611.561
936261AD2-033 C
80/20
27.64927.649
3144293JTRSVLE
80/20
1.0761.076
961791AG1-021 C
80/20
4.6754.675
316248AF1-058 C
80/20
0.450.45
936171AD2-023 C
80/20
2.1112.111
941801AE2-185 C
80/20
1.9561.956
3151381ROSEMG2
80/20
0.2910.291
934321AD1-056 C
80/20
1.9781.978
934331AD1-057 C
80/20
1.1031.103
958211AF2-115 C
80/20
5.8435.843
946281AF1-292 C
80/20
0.7790.779
926071AC1-086 C
80/20
6.3516.351
3151541CLOVER2
80/20
22.26122.261
964241AG1-285 C
80/20
25.13225.132
316034AC1-036 C
80/20
0.5340.534
962561AG1-105 C
80/20
14.16114.161
942671AE2-283 C
80/20
1.5211.521
3156073AA1-063SOLA
80/20
0.5840.584
3151371ROSEMS1
80/20
0.3840.384
934621AD1-088 C
80/20
18.88618.886
316359AB2-059 C OP
80/20
0.5620.562
946301AF1-294 C
80/20
9.6099.609
942461AE2-259 C
80/20
31.13331.133
316197AC1-042 C
80/20
0.1420.142
316011AB1-132 C OP
80/20
0.7050.705
316263AC1-034 C
80/20
2.2292.229
959311AF2-222 C
80/20
38.88338.883
942751AE2-291 C
80/20
8.1298.129
3151561HALLBR1
80/20
0.5580.558
966621AG1-532 C
80/20
0.7060.706
316003AC1-222 C
80/20
1.3481.348
936161AD2-022 C
80/20
3.6193.619
932631AC2-084 C
80/20
0.3610.361
316274AC1-208 C
80/20
3.5413.541
3151311EDGECMA
80/20
5.0375.037
3151601KERR 3
80/20
1.5611.561
3151581KERR 1
80/20
0.5570.557
3152661PLYWOOD A
80/20
1.751.75
941011AE2-092 C
Adder
-9.714117647058824-8.257
313506AB1-173 C OP
80/20
0.5620.562
3151361ROSEMG1
80/20
0.6210.621
957481AF2-042 C
80/20
97.99997.999
316181AB2-040 GEN
80/20
0.6330.633
3156063AA2-053SOLA
80/20
0.6790.679
3151281ROARAP4
80/20
0.6440.644
316238AB2-078 C O1
80/20
0.5670.567
316237AB2-079 C O1
80/20
0.5670.567
938821AE1-108 C
Adder
-10.596470588235293-9.007
3151411GASTONB
80/20
0.9230.923
3151261ROARAP2
80/20
0.6810.681
3147043LAWRENC
80/20
0.2660.266
3151621KERR 5
80/20
1.5611.561
316222AC1-221 C
80/20
1.5791.579
316336AC2-165 C
Adder
-5.884705882352941-5.002
934611AD1-087 C
80/20
2.212.21
316049AB1-081 C OP
80/20
0.4770.477
3151611KERR 4
80/20
1.5611.561
316210AC1-098 C
80/20
0.3390.339
316327AA2-057 C
80/20
0.4730.473
316239AB2-077 C O1
80/20
0.5670.567
935171AD1-152 C
80/20
2.1552.155
964791AG1-342 C
80/20
5.5355.535
316129AC1-054 C
80/20
1.1891.189
3151531CLOVER1
80/20
22.47122.471
316131AB2-060 C
80/20
2.662.66
3138533PONTONDP
80/20
1.7311.731
316118AC1-105 C
80/20
1.3691.369
316217AC1-145 C
80/20
0.1690.169
316322AB2-045 C
80/20
1.2941.294
3137643SOCKMAN
80/20
0.3520.352
316212AC1-099 C
80/20
0.1130.113
316319Z2-044 C
80/20
0.0740.074
937481AD2-202 C
80/20
0.6410.641
3151641KERR 7
80/20
1.5611.561
316205AC1-080 C
80/20
0.3190.319
316123AC1-075 C
80/20
0.9530.953
316087AB2-174 C
80/20
0.5880.588
313527AB2-043 C
80/20
0.9080.908
3151591KERR 2
80/20
1.5611.561
316283AC2-100 C
80/20
1.2351.235
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072
NYPJM->LTFIMP_NY
CLTF
0.3750.375
LGEELTFEXP_LGEE->PJM
CLTF
0.3550.355
WECLTFEXP_WEC->PJM
CLTF
0.1880.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.0479.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.0847.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1891.189
LAGNLTFEXP_LAGN->PJM
CLTF
2.5082.508
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1162.116
CBM South 2LTFEXP_CBM-S2->PJM
CBM
35.17235.172
CPLELTFEXP_CPLE->PJM
CLTF
4.444.44
TVALTFEXP_TVA->PJM
CLTF
1.9591.959

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.81 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1322.08
MW Contribution:1.94
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.0 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1396.59
MW Contribution:1.83
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3145413WATKINS
Adder
0.265882352941176460.226
960081AF2-299 C
50/50
1.5581.558
3151391GASTONA
50/50
2.2972.297
926072AC1-086 E
50/50
7.1937.193
944011AF1-069 C
50/50
9.4749.474
316023AB2-100 C2
50/50
0.8890.889
960082AF2-299 E
50/50
1.0391.039
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
963042AG1-153 E
50/50
5.9665.966
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
920042AA2-088 E OP
Adder
4.9317647058823534.192
934511AD1-075 C
Adder
3.2917647058823532.798
934521AD1-076 C
Adder
4.7823529411764714.065
3145723EMPORIA
50/50
0.3510.351
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
919692AA2-053 E OP
Adder
2.6788235294117652.277
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
924516AB2-100 E1
50/50
2.6782.678
918512AA1-065 E OP
Adder
2.60941176470588232.218
966621AG1-532 C
50/50
1.1691.169
940492AE2-034 E
Adder
1.07647058823529430.915
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
918492AA1-063AE OP
Adder
2.40470588235294122.044
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
316274AC1-208 C
Adder
5.5235294117647074.695
917342Z2-044 E
Adder
0.36117647058823530.307
923852AB2-025 E
50/50
1.3441.344
939412AE1-173 E
Adder
33.1823529411764728.205
961941AG1-037 C
Adder
0.251764705882352950.214
961942AG1-037 E
Adder
0.167058823529411760.142
3151381ROSEMG2
50/50
0.7050.705
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934321AD1-056 C
Adder
4.1835294117647063.556
934332AD1-057 E
Adder
1.21529411764705891.033
934322AD1-056 E
Adder
2.26941176470588251.929
934331AD1-057 C
Adder
2.33411764705882341.984
927022AC1-189 E
Adder
2.28117647058823541.939
925595AC1-034 E
Adder
3.0235294117647062.57
936262AD2-033 E
Adder
4.6729411764705883.972
958211AF2-115 C
Adder
1.04823529411764720.891
940541AE2-040 C
50/50
3.3223.322
940482AE2-033 E
50/50
12.29712.297
940481AE2-033 C
50/50
18.24118.241
923263AB1-132 E OP
50/50
4.64.6
316181AB2-040 GEN
50/50
0.9590.959
3151281ROARAP4
50/50
0.8680.868
925612AC1-036 E
Adder
0.47058823529411770.4
924312AB2-078 E O1
Adder
0.7917647058823530.673
926274AC1-105 E
Adder
1.50823529411764711.282
3145393UNCAMP
Adder
2.10941176470588231.793
933981AD1-022 C
Adder
3.6082352941176473.067
900672V4-068 E
Adder
0.172941176470588240.147
3151411GASTONB
50/50
2.2972.297
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
924302AB2-077 E O1
Adder
0.7917647058823530.673
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
933982AD1-022 E
Adder
1.9647058823529411.67
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
927146AC1-208 E
Adder
2.45294117647058842.085
934622AD1-088 E
Adder
2.72588235294117662.317
316141AB2-099 E
Adder
0.125882352941176470.107
316088AB2-174 E
50/50
5.0815.081
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151361ROSEMG1
50/50
1.5051.505
957481AF2-042 C
50/50
34.00834.008
961672AG1-007 E
Adder
0.30352941176470590.258
924322AB2-079 E O1
Adder
0.7917647058823530.673
946302AF1-294 E
Adder
1.46000000000000021.241
943902AF1-058 E
Adder
0.71411764705882350.607
918532AA1-067 E
Adder
0.367058823529411770.312
924022AB2-043 E O1
Adder
3.07764705882352942.616
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
926024AC1-080 E
Adder
0.454117647058823570.386
936161AD2-022 C
Adder
3.8235294117647063.25
937482AD2-202 E
Adder
0.64705882352941180.55
3151311EDGECMA
Adder
9.4070588235294137.996
961792AG1-021 E
Adder
0.71411764705882350.607
3143316POE
Adder
0.51176470588235290.435
316365AB2-100 C1
50/50
0.8890.889
926206AC1-098 E
Adder
2.14705882352941171.825
3151021BRUNSWICKG1
50/50
5.8715.871
3151041BRUNSWICKG3
50/50
5.8715.871
942462AE2-259 E
Adder
2.62.21
964791AG1-342 C
Adder
2.0188235294117651.716
925997AC1-075 E
Adder
1.36941176470588231.164
927021AC1-189 C
Adder
4.5788235294117653.892
964241AG1-285 C
Adder
7.502352941176476.377
924152AB2-059 E OP
Adder
3.18705882352941172.709
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
936172AD2-023 E
Adder
1.21058823529411751.029
316315AB2-025 C
50/50
0.4720.472
946282AF1-292 E
50/50
0.860.86
944012AF1-069 E
50/50
3.683.68
3151051BRUNSWICKS1
50/50
12.19612.196
917512Z2-088 E OP1
Adder
2.742.329
3138533PONTONDP
Adder
0.310588235294117660.264
963041AG1-153 C
50/50
3.9773.977
936261AD2-033 C
Adder
7.0082352941176475.957
961791AG1-021 C
Adder
0.83882352941176460.713
962562AG1-105 E
Adder
3.39764705882352922.888
936171AD2-023 C
Adder
2.23058823529411751.896
934612AD1-087 E
Adder
2.20941176470588241.878
927255AC1-221 E
Adder
2.0517647058823531.744
920692AA2-178 E
Adder
1.43529411764705881.22
966622AG1-532 E
50/50
0.7790.779
3152441Z1-086 ST
50/50
13.14613.146
922923AB1-081 E OP
Adder
2.24941176470588241.912
3147133PAMPLIN
Adder
0.454117647058823570.386
927264AC1-222 E
Adder
2.16588235294117661.841
942001AE2-212 C
Adder
-3.7917647058823527-3.223
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
3151371ROSEMS1
50/50
0.9320.932
957482AF2-042 E
50/50
22.67222.672
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
946301AF1-294 C
Adder
1.7247058823529411.466
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
936162AD2-022 E
Adder
2.29411764705882341.95
939411AE1-173 C
Adder
49.7729411764705942.307
3137643SOCKMAN
50/50
0.5020.502
3151031BRUNSWICKG2
50/50
5.8715.871
919710AA2-057 E
Adder
2.3988235294117652.039
316087AB2-174 C
50/50
0.9180.918
932632AC2-084 E
Adder
1.89764705882352951.613
926214AC1-099 E
Adder
0.70941176470588230.603
964242AG1-285 E
Adder
5.0011764705882364.251
924162AB2-060 E OP
Adder
2.522.142
964792AG1-342 E
Adder
1.34588235294117631.144
932763AC2-100 E
Adder
1.3917647058823531.183
925785AC1-054 E
Adder
2.1505882352941181.828
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.01 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1300.42
MW Contribution:1.94
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.2 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1374.95
MW Contribution:1.83
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
923852AB2-025 E
50/50
1.3441.344
939412AE1-173 E
Adder
33.1823529411764728.205
961941AG1-037 C
Adder
0.251764705882352950.214
961942AG1-037 E
Adder
0.167058823529411760.142
3151381ROSEMG2
50/50
0.7050.705
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934321AD1-056 C
Adder
4.1835294117647063.556
934332AD1-057 E
Adder
1.21529411764705891.033
934322AD1-056 E
Adder
2.26941176470588251.929
934331AD1-057 C
Adder
2.33411764705882341.984
927022AC1-189 E
Adder
2.28117647058823541.939
925595AC1-034 E
Adder
3.0235294117647062.57
936262AD2-033 E
Adder
4.6729411764705883.972
958211AF2-115 C
Adder
1.04823529411764720.891
940541AE2-040 C
50/50
3.3223.322
940482AE2-033 E
50/50
12.29712.297
940481AE2-033 C
50/50
18.24118.241
923263AB1-132 E OP
50/50
4.64.6
316181AB2-040 GEN
50/50
0.9590.959
3151281ROARAP4
50/50
0.8680.868
925612AC1-036 E
Adder
0.47058823529411770.4
924312AB2-078 E O1
Adder
0.7917647058823530.673
926274AC1-105 E
Adder
1.50823529411764711.282
3145393UNCAMP
Adder
2.10941176470588231.793
933981AD1-022 C
Adder
3.6082352941176473.067
900672V4-068 E
Adder
0.172941176470588240.147
3151411GASTONB
50/50
2.2972.297
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
924302AB2-077 E O1
Adder
0.7917647058823530.673
316141AB2-099 E
Adder
0.125882352941176470.107
316088AB2-174 E
50/50
5.0815.081
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151361ROSEMG1
50/50
1.5051.505
957481AF2-042 C
50/50
34.00834.008
961672AG1-007 E
Adder
0.30352941176470590.258
924322AB2-079 E O1
Adder
0.7917647058823530.673
946302AF1-294 E
Adder
1.46000000000000021.241
943902AF1-058 E
Adder
0.71411764705882350.607
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
924516AB2-100 E1
50/50
2.6782.678
918512AA1-065 E OP
Adder
2.60941176470588232.218
966621AG1-532 C
50/50
1.1691.169
918532AA1-067 E
Adder
0.367058823529411770.312
924022AB2-043 E O1
Adder
3.07764705882352942.616
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
926024AC1-080 E
Adder
0.454117647058823570.386
936161AD2-022 C
Adder
3.8235294117647063.25
940492AE2-034 E
Adder
1.07647058823529430.915
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
918492AA1-063AE OP
Adder
2.40470588235294122.044
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
316274AC1-208 C
Adder
5.5235294117647074.695
917342Z2-044 E
Adder
0.36117647058823530.307
937482AD2-202 E
Adder
0.64705882352941180.55
3151311EDGECMA
Adder
9.4070588235294137.996
961792AG1-021 E
Adder
0.71411764705882350.607
3143316POE
Adder
0.51176470588235290.435
316365AB2-100 C1
50/50
0.8890.889
926206AC1-098 E
Adder
2.14705882352941171.825
3151021BRUNSWICKG1
50/50
5.8715.871
3151041BRUNSWICKG3
50/50
5.8715.871
942462AE2-259 E
Adder
2.62.21
964791AG1-342 C
Adder
2.0188235294117651.716
925997AC1-075 E
Adder
1.36941176470588231.164
316023AB2-100 C2
50/50
0.8890.889
960082AF2-299 E
50/50
1.0391.039
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
963042AG1-153 E
50/50
5.9665.966
927021AC1-189 C
Adder
4.5788235294117653.892
964241AG1-285 C
Adder
7.502352941176476.377
924152AB2-059 E OP
Adder
3.18705882352941172.709
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
936172AD2-023 E
Adder
1.21058823529411751.029
316315AB2-025 C
50/50
0.4720.472
946282AF1-292 E
50/50
0.860.86
944012AF1-069 E
50/50
3.683.68
3151051BRUNSWICKS1
50/50
12.19612.196
917512Z2-088 E OP1
Adder
2.742.329
3138533PONTONDP
Adder
0.310588235294117660.264
3145413WATKINS
Adder
0.265882352941176460.226
960081AF2-299 C
50/50
1.5581.558
3151391GASTONA
50/50
2.2972.297
926072AC1-086 E
50/50
7.1937.193
944011AF1-069 C
50/50
9.4749.474
963041AG1-153 C
50/50
3.9773.977
936261AD2-033 C
Adder
7.0082352941176475.957
961791AG1-021 C
Adder
0.83882352941176460.713
962562AG1-105 E
Adder
3.39764705882352922.888
936171AD2-023 C
Adder
2.23058823529411751.896
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
933982AD1-022 E
Adder
1.9647058823529411.67
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
927146AC1-208 E
Adder
2.45294117647058842.085
934622AD1-088 E
Adder
2.72588235294117662.317
934612AD1-087 E
Adder
2.20941176470588241.878
927255AC1-221 E
Adder
2.0517647058823531.744
920692AA2-178 E
Adder
1.43529411764705881.22
966622AG1-532 E
50/50
0.7790.779
3152441Z1-086 ST
50/50
13.14613.146
922923AB1-081 E OP
Adder
2.24941176470588241.912
3147133PAMPLIN
Adder
0.454117647058823570.386
927264AC1-222 E
Adder
2.16588235294117661.841
942001AE2-212 C
Adder
-3.7917647058823527-3.223
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
3151371ROSEMS1
50/50
0.9320.932
957482AF2-042 E
50/50
22.67222.672
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
946301AF1-294 C
Adder
1.7247058823529411.466
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
936162AD2-022 E
Adder
2.29411764705882341.95
939411AE1-173 C
Adder
49.7729411764705942.307
3137643SOCKMAN
50/50
0.5020.502
3151031BRUNSWICKG2
50/50
5.8715.871
919710AA2-057 E
Adder
2.3988235294117652.039
316087AB2-174 C
50/50
0.9180.918
932632AC2-084 E
Adder
1.89764705882352951.613
926214AC1-099 E
Adder
0.70941176470588230.603
964242AG1-285 E
Adder
5.0011764705882364.251
924162AB2-060 E OP
Adder
2.522.142
964792AG1-342 E
Adder
1.34588235294117631.144
932763AC2-100 E
Adder
1.3917647058823531.183
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
920042AA2-088 E OP
Adder
4.9317647058823534.192
934511AD1-075 C
Adder
3.2917647058823532.798
934521AD1-076 C
Adder
4.7823529411764714.065
3145723EMPORIA
50/50
0.3510.351
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
919692AA2-053 E OP
Adder
2.6788235294117652.277
925785AC1-054 E
Adder
2.1505882352941181.828
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406

Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.22 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:801.79
MW Contribution:10.83
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.59 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:831.68
MW Contribution:10.67
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960081AF2-299 C
Adder
0.94000000000000010.799
936261AD2-033 C
50/50
27.67327.673
3144293JTRSVLE
50/50
1.0761.076
961791AG1-021 C
50/50
4.6774.677
962562AG1-105 E
Adder
9.4564705882352958.038
936262AD2-033 E
50/50
18.44918.449
958211AF2-115 C
50/50
5.8475.847
960082AF2-299 E
Adder
0.62705882352941180.533
946281AF1-292 C
Adder
0.77764705882352950.661
964241AG1-285 C
50/50
25.15925.159
316034AC1-036 C
50/50
0.5350.535
958212AF2-115 E
50/50
4.9814.981
962561AG1-105 C
Adder
14.18352941176470612.056
957482AF2-042 E
50/50
65.41765.417
934621AD1-088 C
50/50
18.90718.907
946301AF1-294 C
50/50
9.6159.615
942461AE2-259 C
50/50
31.14431.144
935172AD1-152 E
Adder
8.8823529411764717.55
3145723EMPORIA
Adder
0.21647058823529410.184
925785AC1-054 E
Adder
3.35647058823529452.853
959311AF2-222 C
50/50
38.91438.914
942751AE2-291 C
Adder
8.1517647058823536.929
966621AG1-532 C
Adder
0.70470588235294120.599
924022AB2-043 E O1
Adder
9.1247058823529417.756
3147223TWITTYS
50/50
2.1732.173
959312AF2-222 E
50/50
26.07226.072
926024AC1-080 E
Adder
1.10.935
937482AD2-202 E
Adder
1.86823529411764721.588
961792AG1-021 E
50/50
3.9843.984
941011AE2-092 C
Adder
-9.724705882352941-8.266
957481AF2-042 C
50/50
98.12598.125
924322AB2-079 E O1
Adder
2.3164705882352941.969
946302AF1-294 E
50/50
8.1428.142
943902AF1-058 E
Adder
1.841.564
925612AC1-036 E
50/50
1.961.96
924312AB2-078 E O1
Adder
2.3164705882352941.969
926274AC1-105 E
Adder
4.0141176470588233.412
938821AE1-108 C
Adder
-10.602352941176472-9.012
924302AB2-077 E O1
Adder
2.3164705882352941.969
942752AE2-291 E
Adder
5.4352941176470594.62
316336AC2-165 C
Adder
-5.9023529411764715-5.017
934622AD1-088 E
50/50
9.1039.103
934612AD1-087 E
Adder
6.3847058823529415.427
927255AC1-221 E
Adder
4.1470588235294123.525
942462AE2-259 E
50/50
20.76320.763
964791AG1-342 C
Adder
5.5447058823529414.713
925997AC1-075 E
Adder
3.3141176470588242.817
946282AF1-292 E
Adder
0.51882352941176470.441
3151531CLOVER1
50/50
22.50322.503
3138533PONTONDP
50/50
1.7321.732
966622AG1-532 E
Adder
0.47058823529411770.4
3147133PAMPLIN
50/50
2.7572.757
927264AC1-222 E
Adder
5.5211764705882354.693
964242AG1-285 E
50/50
16.77316.773
924162AB2-060 E OP
Adder
7.6694117647058836.519
964792AG1-342 E
Adder
3.6964705882352943.142
932763AC2-100 E
Adder
2.7305882352941182.321
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7990.799
SIGELTFEXP_SIGE->PJM
CLTF
0.0750.075
NYPJM->LTFIMP_NY
CLTF
0.3810.381
LGEELTFEXP_LGEE->PJM
CLTF
0.370.37
WECLTFEXP_WEC->PJM
CLTF
0.1960.196
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.4439.443
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.3277.327
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.2351.235
LAGNLTFEXP_LAGN->PJM
CLTF
2.5882.588
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1672.167
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.10836.108
CPLELTFEXP_CPLE->PJM
CLTF
4.5484.548
TVALTFEXP_TVA->PJM
CLTF
2.0222.022
O66PJM->LTFIMP_O-066
CMTX_NF
5.0935.093

Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.89 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:636.99
MW Contribution:5.84
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.98 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:676.62
MW Contribution:5.76
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960081AF2-299 C
80/20
0.9420.942
3151391GASTONA
80/20
0.9240.924
3151631KERR 6
80/20
1.5621.562
936261AD2-033 C
80/20
27.65427.654
3144293JTRSVLE
80/20
1.0761.076
961791AG1-021 C
80/20
4.6754.675
316248AF1-058 C
80/20
0.450.45
936171AD2-023 C
80/20
2.1132.113
941801AE2-185 C
80/20
1.9581.958
3151381ROSEMG2
80/20
0.2910.291
934321AD1-056 C
80/20
1.981.98
934331AD1-057 C
80/20
1.1051.105
958211AF2-115 C
80/20
5.8445.844
946281AF1-292 C
80/20
0.7790.779
926071AC1-086 C
80/20
6.3586.358
3151541CLOVER2
80/20
22.26622.266
964241AG1-285 C
80/20
25.13725.137
316034AC1-036 C
80/20
0.5340.534
962561AG1-105 C
80/20
14.16414.164
942671AE2-283 C
80/20
1.5231.523
3156073AA1-063SOLA
80/20
0.5850.585
3151371ROSEMS1
80/20
0.3850.385
934621AD1-088 C
80/20
18.88918.889
316359AB2-059 C OP
80/20
0.5630.563
946301AF1-294 C
80/20
9.619.61
942461AE2-259 C
80/20
31.13731.137
316197AC1-042 C
80/20
0.1420.142
316011AB1-132 C OP
80/20
0.7060.706
316263AC1-034 C
80/20
2.2322.232
959311AF2-222 C
80/20
38.88938.889
942751AE2-291 C
80/20
8.1328.132
3151561HALLBR1
80/20
0.5580.558
966621AG1-532 C
80/20
0.7060.706
316003AC1-222 C
80/20
1.3491.349
936161AD2-022 C
80/20
3.6223.622
932631AC2-084 C
80/20
0.3610.361
316274AC1-208 C
80/20
3.5443.544
3151311EDGECMA
80/20
5.0435.043
3151601KERR 3
80/20
1.5621.562
3151581KERR 1
80/20
0.5580.558
3152661PLYWOOD A
80/20
1.751.75
941011AE2-092 C
Adder
-9.709411764705882-8.253
313506AB1-173 C OP
80/20
0.5620.562
3151361ROSEMG1
80/20
0.6210.621
957481AF2-042 C
80/20
98.01698.016
316181AB2-040 GEN
80/20
0.6330.633
3156063AA2-053SOLA
80/20
0.680.68
3151281ROARAP4
80/20
0.6450.645
316238AB2-078 C O1
80/20
0.5670.567
316237AB2-079 C O1
80/20
0.5670.567
938821AE1-108 C
Adder
-10.591764705882353-9.003
3151411GASTONB
80/20
0.9240.924
3151261ROARAP2
80/20
0.6820.682
3147043LAWRENC
80/20
0.2660.266
3151621KERR 5
80/20
1.5621.562
316222AC1-221 C
80/20
1.581.58
316336AC2-165 C
Adder
-5.881176470588235-4.999
934611AD1-087 C
80/20
2.212.21
316049AB1-081 C OP
80/20
0.4780.478
3151611KERR 4
80/20
1.5621.562
316210AC1-098 C
80/20
0.3390.339
316327AA2-057 C
80/20
0.4730.473
316239AB2-077 C O1
80/20
0.5670.567
935171AD1-152 C
80/20
2.1562.156
964791AG1-342 C
80/20
5.5375.537
316129AC1-054 C
80/20
1.1891.189
3151531CLOVER1
80/20
22.47622.476
316131AB2-060 C
80/20
2.6612.661
3138533PONTONDP
80/20
1.7321.732
316118AC1-105 C
80/20
1.3691.369
316217AC1-145 C
80/20
0.1690.169
3137643SOCKMAN
80/20
0.3530.353
316212AC1-099 C
80/20
0.1140.114
316319Z2-044 C
80/20
0.0740.074
937481AD2-202 C
80/20
0.6410.641
3151641KERR 7
80/20
1.5621.562
316205AC1-080 C
80/20
0.3190.319
316123AC1-075 C
80/20
0.9540.954
316087AB2-174 C
80/20
0.5890.589
313527AB2-043 C
80/20
0.9080.908
3151591KERR 2
80/20
1.5621.562
316283AC2-100 C
80/20
1.2351.235
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072
NYPJM->LTFIMP_NY
CLTF
0.3720.372
LGEELTFEXP_LGEE->PJM
CLTF
0.3590.359
WECLTFEXP_WEC->PJM
CLTF
0.190.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.1489.148
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.1237.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1991.199
LAGNLTFEXP_LAGN->PJM
CLTF
2.5182.518
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1192.119
CBM South 2LTFEXP_CBM-S2->PJM
CBM
35.23335.233
CPLELTFEXP_CPLE->PJM
CLTF
4.4464.446
TVALTFEXP_TVA->PJM
CLTF
1.9681.968

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.41 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:749.36
MW Contribution:1.13
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.4 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:769.65
MW Contribution:1.22
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960081AF2-299 C
80/20
4.3984.398
3151391GASTONA
80/20
6.1746.174
3151631KERR 6
80/20
0.8610.861
936261AD2-033 C
80/20
8.0238.023
3144293JTRSVLE
80/20
0.2090.209
961791AG1-021 C
80/20
0.9070.907
961941AG1-037 C
80/20
0.4820.482
943171AE2-346 C
80/20
0.2140.214
3151381ROSEMG2
80/20
1.8431.843
934321AD1-056 C
80/20
9.1989.198
934331AD1-057 C
80/20
5.1315.131
958211AF2-115 C
80/20
1.1341.134
316023AB2-100 C2
80/20
2.7732.773
946281AF1-292 C
80/20
3.643.64
926071AC1-086 C
80/20
42.48542.485
316317KELFORD C
80/20
0.3690.369
927021AC1-189 C
80/20
7.5457.545
964241AG1-285 C
80/20
7.2197.219
316034AC1-036 C
80/20
0.1230.123
962561AG1-105 C
80/20
5.2835.283
934501AD1-074 C
80/20
19.34719.347
3156021HOLLOMANSOL
80/20
1.5851.585
3156073AA1-063SOLA
80/20
1.8141.814
3151371ROSEMS1
80/20
2.4382.438
961671AG1-007 C
80/20
0.9120.912
934621AD1-088 C
80/20
4.4014.401
316359AB2-059 C OP
80/20
1.761.76
946301AF1-294 C
80/20
1.8641.864
934511AD1-075 C
80/20
4.8374.837
934521AD1-076 C
80/20
7.0267.026
316011AB1-132 C OP
80/20
4.7154.715
316263AC1-034 C
80/20
6.9786.978
959311AF2-222 C
80/20
8.6298.629
966621AG1-532 C
80/20
3.2983.298
3151151S HAMPT1
80/20
0.9560.956
932631AC2-084 C
80/20
1.171.17
316274AC1-208 C
80/20
11.22211.222
3151311EDGECMA
80/20
16.54816.548
3151601KERR 3
80/20
0.8610.861
3151581KERR 1
80/20
0.3070.307
3152661PLYWOOD A
80/20
0.6380.638
3156083AA2-088SOLA
80/20
0.9350.935
313506AB1-173 C OP
80/20
2.2292.229
3151361ROSEMG1
80/20
3.9353.935
316005AA1-067 C
80/20
0.2210.221
957481AF2-042 C
80/20
24.2924.29
940541AE2-040 C
80/20
11.68811.688
940481AE2-033 C
80/20
63.40163.401
316181AB2-040 GEN
80/20
2.512.51
316174AB2-169_C
80/20
0.7190.719
3156063AA2-053SOLA
80/20
2.1572.157
3151281ROARAP4
80/20
2.0092.009
3156011CONETOE2SOL
80/20
1.1751.175
316238AB2-078 C O1
80/20
0.2290.229
316237AB2-079 C O1
80/20
0.2290.229
933981AD1-022 C
80/20
5.6845.684
3151411GASTONB
80/20
6.1746.174
3151261ROARAP2
80/20
2.1232.123
3147043LAWRENC
80/20
0.5790.579
3151621KERR 5
80/20
0.8610.861
316049AB1-081 C OP
80/20
1.4931.493
3151611KERR 4
80/20
0.8610.861
316365AB2-100 C1
80/20
2.7732.773
316318V4-068 C
80/20
0.0750.075
316210AC1-098 C
80/20
1.0991.099
316327AA2-057 C
80/20
1.4881.488
316239AB2-077 C O1
80/20
0.2290.229
964791AG1-342 C
80/20
2.0342.034
316315AB2-025 C
80/20
1.661.66
316129AC1-054 C
80/20
1.341.34
3151531CLOVER1
80/20
5.8145.814
316131AB2-060 C
80/20
1.0331.033
3138533PONTONDP
80/20
0.3360.336
316118AC1-105 C
80/20
0.4840.484
3152921DOMTR78
80/20
0.8530.853
316140AB2-099 C
80/20
0.0920.092
3137643SOCKMAN
80/20
1.2371.237
316212AC1-099 C
80/20
0.3680.368
316319Z2-044 C
80/20
0.2310.231
3151641KERR 7
80/20
0.8610.861
316087AB2-174 C
80/20
2.4642.464
313527AB2-043 C
80/20
0.3630.363
3151591KERR 2
80/20
0.8610.861
SIGELTFEXP_SIGE->PJM
CLTF
0.0830.083
NYPJM->LTFIMP_NY
CLTF
0.370.37
LGEELTFEXP_LGEE->PJM
CLTF
0.4270.427
WECLTFEXP_WEC->PJM
CLTF
0.2270.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.08611.086
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.537.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.351.35
LAGNLTFEXP_LAGN->PJM
CLTF
2.5652.565
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1852.185
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.08134.081
CPLELTFEXP_CPLE->PJM
CLTF
4.5834.583
TVALTFEXP_TVA->PJM
CLTF
2.0082.008

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.54 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1199.86
MW Contribution:1.36
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.15 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1216.93
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926662AC1-147 E
Adder
0.448235294117647070.381
916192Z1-068 E
Adder
0.6682352941176470.568
939412AE1-173 E
50/50
44.67444.674
941032AE2-094 E
50/50
15.74915.749
941031AE2-094 C
50/50
35.16335.163
934321AD1-056 C
Adder
-2.142352941176471-1.821
934331AD1-057 C
Adder
-1.1952941176470588-1.016
936262AD2-033 E
Adder
2.89058823529411772.457
958211AF2-115 C
Adder
0.73529411764705890.625
925612AC1-036 E
Adder
0.381176470588235340.324
924312AB2-078 E O1
Adder
0.45058823529411770.383
926274AC1-105 E
Adder
1.15529411764705880.982
932046AC2-012 E
Adder
4.4317647058823533.767
938531AE1-072 C
Adder
5.95529411764705955.062
3152411Z1-086 GT1
50/50
8.9758.975
924302AB2-077 E O1
Adder
0.45058823529411770.383
944581AF1-123 C
Adder
17.0976470588235314.533
957481AF2-042 C
50/50
35.70935.709
924322AB2-079 E O1
Adder
0.45058823529411770.383
946302AF1-294 E
Adder
1.02352941176470580.87
943902AF1-058 E
Adder
0.58823529411764710.5
919153AA1-139 E2
Adder
1.42117647058823531.208
940642AE2-051 E
50/50
9.9019.901
966621AG1-532 C
Adder
-1.14-0.969
924022AB2-043 E O1
Adder
1.75058823529411781.488
3147223TWITTYS
Adder
0.42235294117647060.359
959312AF2-222 E
Adder
4.8764705882352944.145
933292AC2-141 E
Adder
6.3529411764705895.4
944602AF1-125 E
Adder
38.536470588235332.756
3145506HICKORY
Adder
0.80470588235294130.684
957871AF2-081 C
Adder
3.47411764705882352.953
937482AD2-202 E
50/50
0.6470.647
961792AG1-021 E
Adder
0.50117647058823530.426
3151021BRUNSWICKG1
50/50
6.916.91
3151041BRUNSWICKG3
50/50
6.916.91
942462AE2-259 E
Adder
2.21764705882352951.885
964791AG1-342 C
Adder
1.43529411764705881.22
944582AF1-123 E
Adder
39.15058823529411633.278
944592AF1-124 E
Adder
39.2929411764705933.399
923832AB2-022 E
Adder
0.374117647058823550.318
946281AF1-292 C
Adder
-1.2576470588235293-1.069
963042AG1-153 E
50/50
7.0227.022
3151541CLOVER2
50/50
7.7177.717
964241AG1-285 C
Adder
5.9952941176470595.096
958212AF2-115 E
Adder
0.62588235294117660.532
962561AG1-105 C
Adder
3.50352941176470622.978
944012AF1-069 E
50/50
4.4634.463
3151051BRUNSWICKS1
50/50
14.35614.356
3151531CLOVER1
50/50
7.797.79
3138533PONTONDP
Adder
0.217647058823529420.185
941591AE2-156 C
Adder
6.1035294117647065.188
944601AF1-125 C
Adder
16.8341176470588214.309
944591AF1-124 C
Adder
17.15764705882352814.584
944011AF1-069 C
50/50
11.48911.489
963041AG1-153 C
50/50
4.6824.682
936261AD2-033 C
Adder
4.3352941176470593.685
961791AG1-021 C
Adder
0.58823529411764710.5
962562AG1-105 E
Adder
2.3352941176470591.985
940641AE2-051 C
50/50
14.85114.851
3152431Z1-086 GT3
50/50
8.9728.972
3152421Z1-086 GT2
50/50
8.9728.972
934622AD1-088 E
50/50
2.6942.694
934612AD1-087 E
50/50
2.212.21
934611AD1-087 C
50/50
0.7660.766
927255AC1-221 E
Adder
1.70117647058823531.446
938532AE1-072 E
Adder
3.1047058823529412.639
3146326AYDLETT TAP
Adder
0.455294117647058850.387
3152441Z1-086 ST
50/50
15.62215.622
3147133PAMPLIN
Adder
0.377647058823529450.321
927264AC1-222 E
Adder
1.781.513
942001AE2-212 C
Adder
-2.8705882352941177-2.44
934065AD1-033 E
Adder
1.87294117647058831.592
937226AE2-253 E
Adder
2.081.768
957482AF2-042 E
50/50
23.80623.806
934621AD1-088 C
50/50
5.5965.596
946301AF1-294 C
Adder
1.2082352941176471.027
942461AE2-259 C
Adder
3.32588235294117632.827
935172AD1-152 E
Adder
3.1047058823529412.639
913392Y1-086 E
Adder
0.66235294117647060.563
939411AE1-173 C
50/50
67.01167.011
3137643SOCKMAN
Adder
-0.34352941176470586-0.292
3151031BRUNSWICKG2
50/50
6.916.91
937481AD2-202 C
50/50
0.2220.222
925522AC1-027 E
Adder
0.430588235294117660.366
926755AC1-161 E
Adder
6.3529411764705895.4
933291AC2-141 C
Adder
14.88235294117647112.65
957872AF2-081 E
Adder
1.48941176470588241.266
964242AG1-285 E
Adder
3.99647058823529383.397
924162AB2-060 E OP
Adder
1.4435294117647061.227
964792AG1-342 E
Adder
0.95647058823529410.813
932763AC2-100 E
Adder
1.14235294117647060.971
944641AF1-129 C
Adder
-99.89764705882352-84.913
316240AF1-291 C
Adder
-2.2705882352941176-1.93
919152AA1-139 E1
Adder
1.42117647058823531.208
3145723EMPORIA
Adder
-0.3270588235294118-0.278
959311AF2-222 C
Adder
7.2776470588235296.186
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9710.971
SIGELTFEXP_SIGE->PJM
CLTF
0.0920.092
NYPJM->LTFIMP_NY
CLTF
0.4470.447
LGEELTFEXP_LGEE->PJM
CLTF
0.4670.467
WECLTFEXP_WEC->PJM
CLTF
0.2490.249
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.10812.108
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4868.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4991.499
LAGNLTFEXP_LAGN->PJM
CLTF
2.9182.918
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9681.968
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.24536.245
CPLELTFEXP_CPLE->PJM
CLTF
4.1284.128
TVALTFEXP_TVA->PJM
CLTF
2.2832.283
O66PJM->LTFIMP_O-066
CMTX_NF
6.1826.182

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.85 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3279.97
MW Contribution:2.95
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
76.7117647058823665.205
941591AE2-156 C
80/20
26.02126.021
316316AC1-027 C
80/20
0.460.46
944601AF1-125 C
80/20
65.265.2
944591AF1-124 C
80/20
66.45566.455
938771AE1-103 C
80/20
4.24.2
960081AF2-299 C
Adder
2.64941176470588242.252
944011AF1-069 C
80/20
20.29620.296
963041AG1-153 C
80/20
8.5888.588
936261AD2-033 C
Adder
17.57529411764705814.939
961791AG1-021 C
Adder
2.35764705882352972.004
3150831SPRUNCA
80/20
12.34712.347
3150841SPRUNCB
80/20
12.34712.347
961941AG1-037 C
Adder
0.71058823529411760.604
941031AE2-094 C
80/20
62.11762.117
934321AD1-056 C
Adder
8.5376470588235297.257
934331AD1-057 C
Adder
4.7623529411764714.048
958211AF2-115 C
Adder
2.94705882352941152.505
316169AC1-164 GEN
Adder
44.9588235294117738.215
316349AD2-085 C
80/20
4.9434.943
316258AE1-075 C
80/20
0.5030.503
316023AB2-100 C2
80/20
1.3721.372
946281AF1-292 C
Adder
2.19294117647058861.864
926071AC1-086 C
Adder
29.4425.024
927021AC1-189 C
Adder
11.4094117647058839.698
3151541CLOVER2
80/20
17.7117.71
964241AG1-285 C
Adder
17.89058823529411815.207
962561AG1-105 C
Adder
11.8176470588235310.045
942001AE2-212 C
80/20
2.9732.973
3150991CHESPKB
80/20
1.051.05
316321Z2-027 C
80/20
0.5270.527
943741AF1-042 C
Adder
3.01647058823529422.564
934501AD1-074 C
Adder
47.763529411764740.599
962861AG1-135 C
Adder
6.1588235294117655.235
961671AG1-007 C
Adder
1.26588235294117671.076
934621AD1-088 C
80/20
13.42613.426
946301AF1-294 C
Adder
4.8470588235294124.12
942461AE2-259 C
Adder
12.70588235294117810.8
944641AF1-129 C
Adder
134.59058823529412114.402
316240AF1-291 C
Adder
2.86941176470588262.439
3151161SURRY 1
80/20
33.88933.889
316381AD1-082 C
80/20
1.7951.795
316036AC1-147 C
80/20
0.5360.536
316018AA1-139 ULT2
80/20
1.5751.575
934511AD1-075 C
Adder
11.94117647058823610.15
934521AD1-076 C
Adder
17.34705882352941214.745
316263AC1-034 C
Adder
8.8741176470588247.543
959311AF2-222 C
Adder
23.07176470588235519.611
942341AE2-247 C
80/20
2.1432.143
316246AF1-032 C
80/20
0.4130.413
316388AE2-253 GEN
80/20
2.8622.862
966621AG1-532 C
Adder
1.9870588235294121.689
3150651CHESTF6
Adder
24.50588235294117520.83
916191Z1-068 C
80/20
0.0640.064
316294AC1-161 C
80/20
7.267.26
957871AF2-081 C
80/20
14.54714.547
936591AD2-074 C
Adder
5.7647058823529424.9
3151151S HAMPT1
80/20
2.1352.135
316313AB2-026 C
80/20
0.5480.548
316274AC1-208 C
Adder
12.4023529411764710.542
3151311EDGECMA
Adder
20.74352941176470817.632
3150861SPRUNCD
80/20
0.2220.222
940431AE2-027 C
Adder
17.26588235294117614.676
3150981CHESPKA
80/20
0.6340.634
316185AD1-033 C
80/20
1.7941.794
944581AF1-123 C
80/20
66.2266.22
941101AE2-104 C
80/20
4.8434.843
316320Y1-086 C
80/20
0.3190.319
316405AF2-144 C
80/20
0.4280.428
957481AF2-042 C
80/20
77.49977.499
961611AG1-000B C
Adder
21.72352941176470518.465
316236AE1-162 C
80/20
0.4930.493
316375AC2-012 C
80/20
1.9631.963
313526AB2-022 C
80/20
0.5460.546
940541AE2-040 C
80/20
4.2084.208
940481AE2-033 C
80/20
23.64823.648
3150731STONECA
Adder
8.9505882352941187.608
935161AD1-151 C
Adder
21.46588235294117618.246
3151221GRAVEL6
80/20
3.4833.483
3151201GRAVEL4
80/20
3.4873.487
958161AF2-110 C
80/20
1.9761.976
316017AA1-139 ULT1
80/20
1.5751.575
938531AE1-072 C
80/20
25.56125.561
933981AD1-022 C
Adder
12.39411764705882410.535
3152411Z1-086 GT1
80/20
16.26616.266
943471AF1-018 C
Adder
7.9588235294117656.765
316083AB2-161 C
80/20
0.7870.787
316072AD1-144 C
80/20
0.4020.402
940641AE2-051 C
80/20
27.30727.307
316336AC2-165 C
Adder
13.69411764705882511.64
3152431Z1-086 GT3
80/20
16.26116.261
3152421Z1-086 GT2
80/20
16.26116.261
934611AD1-087 C
80/20
1.761.76
939191AE1-149 C
80/20
15.16215.162
957601AF2-054 C
Adder
2.37764705882352922.021
316365AB2-100 C1
80/20
1.3721.372
3151021BRUNSWICKG1
80/20
12.67612.676
3151041BRUNSWICKG3
80/20
12.67612.676
964791AG1-342 C
Adder
4.6788235294117653.977
3151101ELIZAR3
80/20
4.7154.715
3151081ELIZAR1
80/20
4.6564.656
3151091ELIZAR2
80/20
4.5754.575
316315AB2-025 C
80/20
0.5980.598
961951AG1-038 C
Adder
3.3341176470588242.834
3151051BRUNSWICKS1
80/20
26.33526.335
3151531CLOVER1
80/20
17.87717.877
3138533PONTONDP
Adder
0.87294117647058820.742
316233AE1-074 C
80/20
3.7763.776
940551AE2-041 C
Adder
7.9588235294117656.765
3151211GRAVEL5
80/20
3.4433.443
3152331SURRY 2
80/20
34.47934.479
943461AF1-017 C
80/20
1.9381.938
316311AC2-079 C
80/20
8.2428.242
3156056W1-029WIND
80/20
1.1231.123
3152441Z1-086 ST
80/20
28.31528.315
3150851SPRUNCC
80/20
0.2220.222
3156116Z1-036WIND
80/20
0.9440.944
939411AE1-173 C
80/20
140.502140.502
3137643SOCKMAN
Adder
1.00.85
3151031BRUNSWICKG2
80/20
12.67612.676
937481AD2-202 C
80/20
0.5110.511
944631AF1-128 C
Adder
48.040.8
3150921YORKTN3
Adder
157.0388235294118133.483
933291AC2-141 C
80/20
44.42644.426
316305AF2-043 C
80/20
0.5050.505
316303AF2-085
80/20
6.3826.382
SIGELTFEXP_SIGE->PJM
CLTF
0.2960.296
NYPJM->LTFIMP_NY
CLTF
2.4692.469
LGEELTFEXP_LGEE->PJM
CLTF
1.5071.507
WECLTFEXP_WEC->PJM
CLTF
0.7840.784
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.6437.64
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.68227.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8064.806
LAGNLTFEXP_LAGN->PJM
CLTF
9.5879.587
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1347.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.889122.889
CPLELTFEXP_CPLE->PJM
CLTF
14.96614.966
TVALTFEXP_TVA->PJM
CLTF
7.5327.532

Details for AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.63 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:730.45
MW Contribution:1.14
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.61 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:750.7
MW Contribution:1.22
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960081AF2-299 C
80/20
4.3984.398
3151391GASTONA
80/20
6.1756.175
3151631KERR 6
80/20
0.8620.862
936261AD2-033 C
80/20
8.0298.029
3144293JTRSVLE
80/20
0.2090.209
961791AG1-021 C
80/20
0.9080.908
961941AG1-037 C
80/20
0.4820.482
943171AE2-346 C
80/20
0.2140.214
3151381ROSEMG2
80/20
1.8431.843
934321AD1-056 C
80/20
9.2019.201
934331AD1-057 C
80/20
5.1335.133
958211AF2-115 C
80/20
1.1351.135
316023AB2-100 C2
80/20
2.7732.773
946281AF1-292 C
80/20
3.6413.641
926071AC1-086 C
80/20
42.49342.493
316317KELFORD C
80/20
0.370.37
927021AC1-189 C
80/20
7.5497.549
964241AG1-285 C
80/20
7.2257.225
316034AC1-036 C
80/20
0.1240.124
962561AG1-105 C
80/20
5.2875.287
934501AD1-074 C
80/20
19.36119.361
3156021HOLLOMANSOL
80/20
1.5861.586
3156073AA1-063SOLA
80/20
1.8141.814
3151371ROSEMS1
80/20
2.4382.438
961671AG1-007 C
80/20
0.9120.912
934621AD1-088 C
80/20
4.4044.404
316359AB2-059 C OP
80/20
1.7611.761
946301AF1-294 C
80/20
1.8661.866
934511AD1-075 C
80/20
4.844.84
934521AD1-076 C
80/20
7.0327.032
316011AB1-132 C OP
80/20
4.7154.715
316263AC1-034 C
80/20
6.9816.981
959311AF2-222 C
80/20
8.6368.636
966621AG1-532 C
80/20
3.2993.299
3151151S HAMPT1
80/20
0.9570.957
932631AC2-084 C
80/20
1.171.17
316274AC1-208 C
80/20
11.22611.226
3151311EDGECMA
80/20
16.55516.555
3151601KERR 3
80/20
0.8620.862
3151581KERR 1
80/20
0.3080.308
3152661PLYWOOD A
80/20
0.6390.639
3156083AA2-088SOLA
80/20
0.9350.935
313506AB1-173 C OP
80/20
2.2292.229
3151361ROSEMG1
80/20
3.9363.936
316005AA1-067 C
80/20
0.2210.221
957481AF2-042 C
80/20
24.31224.312
940481AE2-033 C
80/20
63.40763.407
316181AB2-040 GEN
80/20
2.5112.511
316174AB2-169_C
80/20
0.7190.719
3156063AA2-053SOLA
80/20
2.1582.158
3151281ROARAP4
80/20
2.0092.009
3156011CONETOE2SOL
80/20
1.1751.175
316238AB2-078 C O1
80/20
0.2290.229
316237AB2-079 C O1
80/20
0.2290.229
933981AD1-022 C
80/20
5.6875.687
3151411GASTONB
80/20
6.1756.175
3151261ROARAP2
80/20
2.1232.123
3147043LAWRENC
80/20
0.5790.579
3151621KERR 5
80/20
0.8620.862
316049AB1-081 C OP
80/20
1.4941.494
3151611KERR 4
80/20
0.8620.862
316365AB2-100 C1
80/20
2.7732.773
316318V4-068 C
80/20
0.0750.075
316210AC1-098 C
80/20
1.0991.099
316327AA2-057 C
80/20
1.4891.489
316239AB2-077 C O1
80/20
0.2290.229
964791AG1-342 C
80/20
2.0352.035
316129AC1-054 C
80/20
1.341.34
3151531CLOVER1
80/20
5.8195.819
316131AB2-060 C
80/20
1.0341.034
3138533PONTONDP
80/20
0.3360.336
316118AC1-105 C
80/20
0.4840.484
3152921DOMTR78
80/20
0.8540.854
316140AB2-099 C
80/20
0.0920.092
3137643SOCKMAN
80/20
1.2371.237
316212AC1-099 C
80/20
0.3680.368
316319Z2-044 C
80/20
0.2310.231
3151641KERR 7
80/20
0.8620.862
316087AB2-174 C
80/20
2.4642.464
313527AB2-043 C
80/20
0.3630.363
3151591KERR 2
80/20
0.8620.862
SIGELTFEXP_SIGE->PJM
CLTF
0.0840.084
NYPJM->LTFIMP_NY
CLTF
0.3660.366
LGEELTFEXP_LGEE->PJM
CLTF
0.4310.431
WECLTFEXP_WEC->PJM
CLTF
0.2290.229
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.20711.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.5767.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.3611.361
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1882.188
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.15434.154
CPLELTFEXP_CPLE->PJM
CLTF
4.5894.589
TVALTFEXP_TVA->PJM
CLTF
2.0182.018
CONTINGENCY 'DVP_P4-2: 511T556_SRT-S-1'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 556_SRT-S-3'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
END
314677 to 314747 ckt 1
314282 to 314285 ckt 1
314285 to 314316 ckt 1
314692 to 314677 ckt 1
314435 to 314282 ckt 1
314902 to 314282 ckt 2
314914 to 314918 ckt 1
940480 to 314435 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
DVP_P4-6: CHASE C T342_SRT-A
BreakerAC126.04 %221.4C279.0511.15
GD1DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P4-6: CHASE C T342_SRT-A
BreakerAC165.99 %208.7C346.4113.84
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC100.29 %984.18B987.040.8
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 246_SRT-A
SingleAC106.25 %678.68B721.080.79
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC101.5 %678.68B688.831.22
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Base Case
SingleAC100.94 %678.68A685.040.73
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.39 %3220.44B3329.542.28
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC119.4 %3220.44B3845.283.01
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC111.63 %3220.44B3595.091.8
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
SingleAC110.86 %3220.44B3570.051.88
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC110.14 %3940.0C4339.533.45
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC116.71 %3220.44B3758.562.02
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC113.93 %3220.44B3669.132.15
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC111.88 %3940.0C4408.083.89
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC106.7 %4070.2B4342.983.3
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC102.59 %4070.2B4175.623.3
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC120.93 %3220.44B3894.331.97
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC119.78 %3220.44B3857.572.12
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC117.54 %3940.0C4631.243.84
GD1DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC104.04 %4070.2B4234.72.89

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-6: CHASE C T342_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.04 %
Rating:221.4 MVA
Rating Type:C
MVA to Mitigate:279.05
MW Contribution:11.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3147223TWITTYS
50/50
2.5462.546
959312AF2-222 E
50/50
29.87729.877
961792AG1-021 E
50/50
4.1034.103
936262AD2-033 E
50/50
23.18823.188
958211AF2-115 C
50/50
6.026.02
964241AG1-285 C
50/50
33.44533.445
316034AC1-036 C
50/50
0.6250.625
958212AF2-115 E
50/50
5.1285.128
3144293JTRSVLE
50/50
1.1041.104
925612AC1-036 E
50/50
2.2972.297
946301AF1-294 C
50/50
9.99.9
942461AE2-259 C
50/50
26.75626.756
946302AF1-294 E
50/50
8.3838.383
942462AE2-259 E
50/50
17.83717.837
316131AB2-060 C
50/50
3.953.95
3138533PONTONDP
50/50
1.7841.784
936261AD2-033 C
50/50
34.78234.782
961791AG1-021 C
50/50
4.8164.816
3147133PAMPLIN
50/50
2.6642.664
924162AB2-060 E OP
50/50
11.41611.416
964242AG1-285 E
50/50
22.29622.296
959311AF2-222 C
50/50
44.59344.593
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0180.018
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0190.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0060.006
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0470.047
MDUPJM->LTFIMP_MDU
CLTF
0.0020.002
NYPJM->LTFIMP_NY
CLTF
0.010.01
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0380.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0110.011
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.010.01
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0320.032
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0140.014
O66PJM->LTFIMP_O-066
CMTX_NF
0.1230.123

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-6: CHASE C T342_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.99 %
Rating:208.7 MVA
Rating Type:C
MVA to Mitigate:346.41
MW Contribution:13.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3147223TWITTYS
50/50
3.1613.161
959312AF2-222 E
50/50
37.09537.095
961792AG1-021 E
50/50
5.0945.094
936262AD2-033 E
50/50
28.7928.79
958211AF2-115 C
50/50
7.4747.474
964241AG1-285 C
50/50
41.52541.525
316034AC1-036 C
50/50
0.7760.776
958212AF2-115 E
50/50
6.3676.367
3144293JTRSVLE
50/50
1.371.37
925612AC1-036 E
50/50
2.8512.851
946301AF1-294 C
50/50
12.29112.291
942461AE2-259 C
50/50
33.2233.22
946302AF1-294 E
50/50
10.40910.409
942462AE2-259 E
50/50
22.14722.147
316131AB2-060 C
50/50
4.9054.905
3138533PONTONDP
50/50
2.2152.215
936261AD2-033 C
50/50
43.18643.186
961791AG1-021 C
50/50
5.985.98
3147133PAMPLIN
50/50
3.3083.308
924162AB2-060 E OP
50/50
14.17414.174
964242AG1-285 E
50/50
27.68327.683
959311AF2-222 C
50/50
55.36655.366
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0230.023
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0240.024
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0080.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0580.058
MDUPJM->LTFIMP_MDU
CLTF
0.0020.002
NYPJM->LTFIMP_NY
CLTF
0.0120.012
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0470.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0130.013
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0130.013
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0390.039
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0170.017
O66PJM->LTFIMP_O-066
CMTX_NF
0.1520.152

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.29 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:987.04
MW Contribution:0.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316318V4-068 C
80/20
0.0370.037
966621AG1-532 C
80/20
1.041.04
313506AB1-173 C OP
80/20
0.7570.757
316210AC1-098 C
80/20
0.50.5
316005AA1-067 C
80/20
0.1280.128
3151601KERR 3
80/20
0.5540.554
3151581KERR 1
80/20
0.1980.198
935171AD1-152 C
80/20
0.620.62
932631AC2-084 C
80/20
0.5330.533
316274AC1-208 C
80/20
4.9624.962
3151311EDGECMA
80/20
8.3398.339
3152661PLYWOOD A
80/20
0.5410.541
943171AE2-346 C
80/20
0.1050.105
961941AG1-037 C
80/20
0.2370.237
3151391GASTONA
80/20
2.0712.071
941031AE2-094 C
80/20
22.06822.068
934331AD1-057 C
80/20
2.0892.089
934321AD1-056 C
80/20
3.7443.744
3151531CLOVER1
80/20
6.056.05
3151541CLOVER2
80/20
5.9935.993
958211AF2-115 C
Adder
0.80.68
946281AF1-292 C
80/20
1.1471.147
926071AC1-086 C
80/20
14.30114.301
927021AC1-189 C
80/20
4.1534.153
964241AG1-285 C
80/20
5.5515.551
316034AC1-036 C
80/20
0.0950.095
962561AG1-105 C
80/20
4.0224.022
316118AC1-105 C
80/20
0.4080.408
315614AA2-178 C
80/20
0.5670.567
940541AE2-040 C
80/20
2.9992.999
940481AE2-033 C
80/20
16.46516.465
3151411GASTONB
80/20
2.0712.071
316181AB2-040 GEN
80/20
0.8530.853
3147043LAWRENC
80/20
0.2030.203
933981AD1-022 C
80/20
3.5783.578
316174AB2-169_C
80/20
0.4490.449
3156063AA2-053SOLA
80/20
0.860.86
3151281ROARAP4
80/20
0.7750.775
316049AB1-081 C OP
80/20
0.7570.757
316238AB2-078 C O1
80/20
0.1510.151
942001AE2-212 C
Adder
-3.9329411764705884-3.343
940491AE2-034 C
80/20
0.4170.417
934501AD1-074 C
80/20
13.23613.236
3151031BRUNSWICKG2
80/20
4.4784.478
961671AG1-007 C
80/20
0.4820.482
316359AB2-059 C OP
80/20
0.8920.892
934621AD1-088 C
80/20
4.424.42
946301AF1-294 C
Adder
1.3164705882352941.119
316283AC2-100 C
80/20
0.510.51
3156083AA2-088SOLA
80/20
0.4670.467
316365AB2-100 C1
80/20
0.7990.799
3151021BRUNSWICKG1
80/20
4.4784.478
957481AF2-042 C
80/20
26.38726.387
316003AC1-222 C
80/20
0.4260.426
3151151S HAMPT1
80/20
0.570.57
3151361ROSEMG1
80/20
1.3551.355
3151041BRUNSWICKG3
80/20
4.4784.478
316327AA2-057 C
80/20
0.7010.701
316239AB2-077 C O1
80/20
0.1510.151
964791AG1-342 C
80/20
1.5971.597
316315AB2-025 C
80/20
0.4250.425
316023AB2-100 C2
80/20
0.7990.799
316317KELFORD C
80/20
0.1760.176
316129AC1-054 C
80/20
0.6480.648
3151631KERR 6
80/20
0.5540.554
316131AB2-060 C
80/20
0.680.68
3138533PONTONDP
Adder
0.237647058823529430.202
938771AE1-103 C
Adder
0.96705882352941170.822
960081AF2-299 C
80/20
1.3861.386
3151381ROSEMG2
80/20
0.6340.634
944011AF1-069 C
80/20
7.217.21
963041AG1-153 C
80/20
3.0443.044
3151051BRUNSWICKS1
80/20
9.3029.302
936261AD2-033 C
80/20
5.4245.424
961791AG1-021 C
Adder
0.640.544
316248AF1-058 C
80/20
0.140.14
940641AE2-051 C
80/20
9.0359.035
3152431Z1-086 GT3
80/20
5.7485.748
3156011CONETOE2SOL
80/20
0.6290.629
934611AD1-087 C
80/20
0.5960.596
3151611KERR 4
80/20
0.5540.554
3151621KERR 5
80/20
0.5540.554
316237AB2-079 C O1
80/20
0.1510.151
316222AC1-221 C
80/20
0.6320.632
3151261ROARAP2
80/20
0.8190.819
3152421Z1-086 GT2
80/20
5.7485.748
3152441Z1-086 ST
80/20
10.00810.008
3152411Z1-086 GT1
80/20
5.755.75
939411AE1-173 C
80/20
41.75841.758
3156021HOLLOMANSOL
80/20
0.830.83
316011AB1-132 C OP
80/20
1.5811.581
3151371ROSEMS1
80/20
0.8390.839
3137643SOCKMAN
80/20
0.4490.449
3152921DOMTR78
80/20
0.5570.557
316140AB2-099 C
80/20
0.0450.045
316319Z2-044 C
80/20
0.1130.113
3151641KERR 7
80/20
0.5540.554
313527AB2-043 C
80/20
0.2380.238
944641AF1-129 C
Adder
-92.12117647058824-78.303
316240AF1-291 C
Adder
-1.6611764705882353-1.412
934521AD1-076 C
80/20
4.8074.807
934511AD1-075 C
80/20
3.3093.309
3156073AA1-063SOLA
80/20
0.7530.753
316087AB2-174 C
80/20
0.8150.815
316212AC1-099 C
80/20
0.1680.168
316263AC1-034 C
80/20
3.5493.549
937481AD2-202 C
80/20
0.1730.173
3151591KERR 2
80/20
0.5540.554
959311AF2-222 C
80/20
6.6486.648
SIGELTFEXP_SIGE->PJM
CLTF
0.1330.133
NYPJM->LTFIMP_NY
CLTF
0.5840.584
LGEELTFEXP_LGEE->PJM
CLTF
0.6950.695
WECLTFEXP_WEC->PJM
CLTF
0.3670.367
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.95317.953
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.57311.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1342.134
LAGNLTFEXP_LAGN->PJM
CLTF
3.8673.867
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.6422.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.16446.164
CPLELTFEXP_CPLE->PJM
CLTF
5.5395.539
TVALTFEXP_TVA->PJM
CLTF
3.0473.047

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.25 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:721.08
MW Contribution:0.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938771AE1-103 C
80/20
1.2731.273
960081AF2-299 C
80/20
4.5664.566
3151381ROSEMG2
80/20
2.0062.006
936261AD2-033 C
80/20
6.4546.454
961791AG1-021 C
80/20
0.6320.632
943171AE2-346 C
80/20
0.2840.284
961941AG1-037 C
80/20
0.6420.642
3151391GASTONA
80/20
6.76.7
934331AD1-057 C
80/20
5.7225.722
934321AD1-056 C
80/20
10.25810.258
958211AF2-115 C
80/20
0.790.79
3156116Z1-036WIND
80/20
0.2510.251
940491AE2-034 C
80/20
0.7340.734
934501AD1-074 C
80/20
28.03828.038
961671AG1-007 C
80/20
1.1061.106
316359AB2-059 C OP
80/20
2.0212.021
946301AF1-294 C
80/20
1.31.3
316318V4-068 C
80/20
0.090.09
966621AG1-532 C
80/20
3.4243.424
313506AB1-173 C OP
80/20
2.3432.343
316210AC1-098 C
80/20
1.2971.297
316005AA1-067 C
80/20
0.2960.296
3151601KERR 3
80/20
0.7120.712
3151581KERR 1
80/20
0.2540.254
932631AC2-084 C
80/20
1.3811.381
316274AC1-208 C
80/20
12.83612.836
3151311EDGECMA
80/20
19.08119.081
3152661PLYWOOD A
80/20
0.3910.391
946281AF1-292 C
80/20
3.783.78
926071AC1-086 C
80/20
46.26846.268
927021AC1-189 C
80/20
9.5779.577
964241AG1-285 C
80/20
7.0017.001
316034AC1-036 C
80/20
0.110.11
962561AG1-105 C
80/20
3.8843.884
316118AC1-105 C
80/20
0.3030.303
3144293JTRSVLE
80/20
0.1450.145
315614AA2-178 C
80/20
0.9970.997
3151411GASTONB
80/20
6.76.7
316181AB2-040 GEN
80/20
2.6392.639
3147043LAWRENC
80/20
0.5880.588
933981AD1-022 C
80/20
8.3538.353
316174AB2-169_C
80/20
0.9970.997
3156063AA2-053SOLA
80/20
2.4062.406
3151281ROARAP4
80/20
2.1722.172
316049AB1-081 C OP
80/20
1.7151.715
316238AB2-078 C O1
80/20
0.1950.195
934521AD1-076 C
80/20
10.18310.183
934511AD1-075 C
80/20
7.017.01
3156073AA1-063SOLA
80/20
1.9821.982
316087AB2-174 C
80/20
2.5762.576
316212AC1-099 C
80/20
0.4340.434
316263AC1-034 C
80/20
8.0388.038
3151591KERR 2
80/20
0.7120.712
959311AF2-222 C
80/20
7.5547.554
3156083AA2-088SOLA
80/20
1.0451.045
316365AB2-100 C1
80/20
2.8782.878
3151151S HAMPT1
80/20
1.0351.035
3151361ROSEMG1
80/20
4.2844.284
316327AA2-057 C
80/20
1.711.71
316239AB2-077 C O1
80/20
0.1950.195
964791AG1-342 C
80/20
1.4341.434
316023AB2-100 C2
80/20
2.8782.878
316317KELFORD C
80/20
0.4780.478
316129AC1-054 C
80/20
1.321.32
3151631KERR 6
80/20
0.7120.712
316131AB2-060 C
80/20
0.8840.884
3138533PONTONDP
80/20
0.2340.234
3156011CONETOE2SOL
80/20
1.4481.448
3151611KERR 4
80/20
0.7120.712
3151621KERR 5
80/20
0.7120.712
316237AB2-079 C O1
80/20
0.1950.195
3151261ROARAP2
80/20
2.2952.295
3156021HOLLOMANSOL
80/20
2.3822.382
316011AB1-132 C OP
80/20
5.1165.116
3151371ROSEMS1
80/20
2.6542.654
3137643SOCKMAN
80/20
1.3221.322
3152921DOMTR78
80/20
1.2081.208
316140AB2-099 C
80/20
0.1220.122
316319Z2-044 C
80/20
0.2660.266
3151641KERR 7
80/20
0.7120.712
313527AB2-043 C
80/20
0.3120.312
SIGELTFEXP_SIGE->PJM
CLTF
0.1110.111
NYPJM->LTFIMP_NY
CLTF
0.4240.424
LGEELTFEXP_LGEE->PJM
CLTF
0.5780.578
WECLTFEXP_WEC->PJM
CLTF
0.3070.307
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.04115.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.5619.561
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.7731.773
LAGNLTFEXP_LAGN->PJM
CLTF
3.1853.185
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5172.517
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.76439.764
CPLELTFEXP_CPLE->PJM
CLTF
5.2785.278
TVALTFEXP_TVA->PJM
CLTF
2.5052.505

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.5 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:688.83
MW Contribution:1.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940491AE2-034 C
80/20
0.5090.509
934501AD1-074 C
80/20
19.21819.218
961671AG1-007 C
80/20
0.9120.912
316359AB2-059 C OP
80/20
1.7561.756
946301AF1-294 C
80/20
2.0132.013
316318V4-068 C
80/20
0.0750.075
966621AG1-532 C
80/20
3.313.31
313506AB1-173 C OP
80/20
2.2272.227
316210AC1-098 C
80/20
1.0951.095
316005AA1-067 C
80/20
0.220.22
3151601KERR 3
80/20
0.8780.878
3151581KERR 1
80/20
0.3140.314
932631AC2-084 C
80/20
1.1661.166
316274AC1-208 C
80/20
11.23211.232
3151311EDGECMA
80/20
16.55916.559
3152661PLYWOOD A
80/20
0.6530.653
943171AE2-346 C
80/20
0.2130.213
961941AG1-037 C
80/20
0.480.48
3151391GASTONA
80/20
6.1476.147
934331AD1-057 C
80/20
5.135.13
934321AD1-056 C
80/20
9.1969.196
3151531CLOVER1
80/20
5.415.41
958211AF2-115 C
80/20
1.2241.224
946281AF1-292 C
80/20
3.6533.653
926071AC1-086 C
80/20
42.4542.45
927021AC1-189 C
80/20
7.547.54
964241AG1-285 C
80/20
9.2089.208
316034AC1-036 C
80/20
0.1530.153
962561AG1-105 C
80/20
5.6645.664
316118AC1-105 C
80/20
0.5020.502
3144293JTRSVLE
80/20
0.2240.224
315614AA2-178 C
80/20
0.6920.692
3151411GASTONB
80/20
6.1476.147
316181AB2-040 GEN
80/20
2.5092.509
3147043LAWRENC
80/20
0.5850.585
933981AD1-022 C
80/20
5.655.65
316174AB2-169_C
80/20
0.7140.714
3156063AA2-053SOLA
80/20
2.1522.152
3151281ROARAP4
80/20
2.0052.005
316049AB1-081 C OP
80/20
1.491.49
316238AB2-078 C O1
80/20
0.2520.252
3156083AA2-088SOLA
80/20
0.9280.928
316365AB2-100 C1
80/20
2.762.76
3151151S HAMPT1
80/20
0.9440.944
3151361ROSEMG1
80/20
3.9193.919
316327AA2-057 C
80/20
1.4841.484
316239AB2-077 C O1
80/20
0.2520.252
964791AG1-342 C
80/20
2.1632.163
316023AB2-100 C2
80/20
2.762.76
316317KELFORD C
80/20
0.3680.368
316129AC1-054 C
80/20
1.3491.349
3151631KERR 6
80/20
0.8780.878
316131AB2-060 C
80/20
1.1411.141
3138533PONTONDP
80/20
0.3630.363
960081AF2-299 C
80/20
4.4134.413
3151381ROSEMG2
80/20
1.8351.835
936261AD2-033 C
80/20
8.8148.814
961791AG1-021 C
80/20
0.9790.979
316248AF1-058 C
80/20
0.1540.154
3156011CONETOE2SOL
80/20
1.171.17
3151611KERR 4
80/20
0.8780.878
3151621KERR 5
80/20
0.8780.878
316237AB2-079 C O1
80/20
0.2520.252
3151261ROARAP2
80/20
2.1192.119
3156021HOLLOMANSOL
80/20
1.5721.572
316011AB1-132 C OP
80/20
4.6944.694
3151371ROSEMS1
80/20
2.4272.427
3137643SOCKMAN
80/20
1.2391.239
3152921DOMTR78
80/20
0.8460.846
316140AB2-099 C
80/20
0.0910.091
316319Z2-044 C
80/20
0.2310.231
3151641KERR 7
80/20
0.8780.878
313527AB2-043 C
80/20
0.4010.401
934521AD1-076 C
80/20
6.986.98
934511AD1-075 C
80/20
4.8054.805
3156073AA1-063SOLA
80/20
1.8081.808
316087AB2-174 C
80/20
2.4632.463
316212AC1-099 C
80/20
0.3670.367
316263AC1-034 C
80/20
6.9846.984
3151591KERR 2
80/20
0.8780.878
959311AF2-222 C
80/20
10.63410.634
SIGELTFEXP_SIGE->PJM
CLTF
0.1050.105
NYPJM->LTFIMP_NY
CLTF
0.4260.426
LGEELTFEXP_LGEE->PJM
CLTF
0.5540.554
WECLTFEXP_WEC->PJM
CLTF
0.2920.292
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.33314.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.9028.902
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.6731.673
LAGNLTFEXP_LAGN->PJM
CLTF
2.9362.936
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.2262.226
CBM South 2LTFEXP_CBM-S2->PJM
CBM
35.70835.708
CPLELTFEXP_CPLE->PJM
CLTF
4.6674.667
TVALTFEXP_TVA->PJM
CLTF
2.3192.319

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.94 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:685.04
MW Contribution:0.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3156116Z1-036WIND
80/20
0.2010.201
940491AE2-034 C
80/20
0.5370.537
316318V4-068 C
80/20
0.0740.074
966621AG1-532 C
80/20
3.2633.263
313506AB1-173 C OP
80/20
2.1872.187
316210AC1-098 C
80/20
1.0791.079
316005AA1-067 C
80/20
0.220.22
3151601KERR 3
80/20
0.6440.644
3151581KERR 1
80/20
0.230.23
932631AC2-084 C
80/20
1.1481.148
316274AC1-208 C
80/20
11.02211.022
3151311EDGECMA
80/20
16.35316.353
943171AE2-346 C
80/20
0.2130.213
961941AG1-037 C
80/20
0.480.48
3151391GASTONA
80/20
6.1336.133
934331AD1-057 C
80/20
5.0965.096
934321AD1-056 C
80/20
9.1359.135
958211AF2-115 C
80/20
0.7340.734
946281AF1-292 C
80/20
3.6023.602
926071AC1-086 C
80/20
42.34842.348
927021AC1-189 C
80/20
7.5047.504
964241AG1-285 C
80/20
6.4946.494
316034AC1-036 C
80/20
0.1020.102
962561AG1-105 C
80/20
3.5683.568
3144293JTRSVLE
80/20
0.1350.135
315614AA2-178 C
80/20
0.7290.729
940541AE2-040 C
80/20
11.74711.747
940481AE2-033 C
80/20
63.69463.694
3151411GASTONB
80/20
6.1336.133
316181AB2-040 GEN
80/20
2.4632.463
3147043LAWRENC
80/20
0.5590.559
933981AD1-022 C
80/20
5.7955.795
316174AB2-169_C
80/20
0.7240.724
3156063AA2-053SOLA
80/20
2.1042.104
3151281ROARAP4
80/20
1.9541.954
316049AB1-081 C OP
80/20
1.4681.468
316238AB2-078 C O1
80/20
0.1810.181
934501AD1-074 C
80/20
19.85319.853
961671AG1-007 C
80/20
0.9040.904
316359AB2-059 C OP
80/20
1.731.73
946301AF1-294 C
80/20
1.2081.208
3156083AA2-088SOLA
80/20
0.9250.925
316365AB2-100 C1
80/20
2.7652.765
3151151S HAMPT1
80/20
0.9570.957
3151361ROSEMG1
80/20
3.9083.908
316327AA2-057 C
80/20
1.461.46
316239AB2-077 C O1
80/20
0.1810.181
964791AG1-342 C
80/20
1.3141.314
316315AB2-025 C
80/20
1.6631.663
316023AB2-100 C2
80/20
2.7652.765
316317KELFORD C
80/20
0.3660.366
316129AC1-054 C
80/20
1.1891.189
3151631KERR 6
80/20
0.6440.644
316131AB2-060 C
80/20
0.820.82
3138533PONTONDP
80/20
0.2180.218
938771AE1-103 C
80/20
1.2791.279
960081AF2-299 C
80/20
4.3514.351
3151381ROSEMG2
80/20
1.831.83
936261AD2-033 C
80/20
5.9895.989
961791AG1-021 C
80/20
0.5880.588
3156011CONETOE2SOL
80/20
1.1621.162
3151611KERR 4
80/20
0.6440.644
3151621KERR 5
80/20
0.6440.644
316237AB2-079 C O1
80/20
0.1810.181
3151261ROARAP2
80/20
2.0652.065
3156021HOLLOMANSOL
80/20
1.5911.591
316011AB1-132 C OP
80/20
4.6834.683
3151371ROSEMS1
80/20
2.422.42
3137643SOCKMAN
80/20
1.2121.212
3152921DOMTR78
80/20
0.8660.866
316140AB2-099 C
80/20
0.0910.091
316319Z2-044 C
80/20
0.2270.227
3151641KERR 7
80/20
0.6440.644
313527AB2-043 C
80/20
0.290.29
934521AD1-076 C
80/20
7.217.21
934511AD1-075 C
80/20
4.9634.963
3156073AA1-063SOLA
80/20
1.7721.772
316087AB2-174 C
80/20
2.4212.421
316212AC1-099 C
80/20
0.3610.361
316263AC1-034 C
80/20
6.8836.883
3151591KERR 2
80/20
0.6440.644
959311AF2-222 C
80/20
7.0127.012
SIGELTFEXP_SIGE->PJM
CLTF
0.0890.089
NYPJM->LTFIMP_NY
CLTF
0.370.37
LGEELTFEXP_LGEE->PJM
CLTF
0.4650.465
WECLTFEXP_WEC->PJM
CLTF
0.2460.246
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.06512.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.7657.765
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4321.432
LAGNLTFEXP_LAGN->PJM
CLTF
2.5962.596
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.0622.062
CBM South 2LTFEXP_CBM-S2->PJM
CBM
32.61632.616
CPLELTFEXP_CPLE->PJM
CLTF
4.3234.323
TVALTFEXP_TVA->PJM
CLTF
2.0422.042

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.39 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3329.54
MW Contribution:2.28
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151081ELIZAR1
80/20
4.2584.258
943171AE2-346 C
80/20
0.2980.298
961941AG1-037 C
80/20
0.6730.673
3151391GASTONA
80/20
4.0664.066
941031AE2-094 C
80/20
66.45566.455
934331AD1-057 C
Adder
4.6482352941176473.951
934321AD1-056 C
Adder
8.332941176470597.083
3151531CLOVER1
80/20
17.9517.95
3151541CLOVER2
80/20
17.78117.781
958211AF2-115 C
Adder
2.28235294117647051.94
942001AE2-212 C
Adder
2.11411764705882371.797
3156116Z1-036WIND
80/20
0.8770.877
940491AE2-034 C
80/20
1.5381.538
934501AD1-074 C
80/20
45.0845.08
3151031BRUNSWICKG2
80/20
13.44613.446
961671AG1-007 C
Adder
1.2482352941176471.061
934621AD1-088 C
80/20
13.20613.206
946301AF1-294 C
Adder
3.75411764705882333.191
942341AE2-247 C
80/20
1.881.88
316246AF1-032 C
80/20
0.3780.378
316388AE2-253 GEN
80/20
2.6322.632
316320Y1-086 C
80/20
0.2940.294
316318V4-068 C
80/20
0.1070.107
966621AG1-532 C
80/20
1.8631.863
313506AB1-173 C OP
80/20
1.4941.494
316210AC1-098 C
80/20
1.251.25
935171AD1-152 C
80/20
1.8271.827
936161AD2-022 C
Adder
9.455294117647068.037
957871AF2-081 C
80/20
13.4313.43
932631AC2-084 C
80/20
1.3311.331
316274AC1-208 C
80/20
11.98411.984
3151311EDGECMA
Adder
20.58941176470588317.501
316349AD2-085 C
80/20
4.3374.337
3151091ELIZAR2
80/20
4.1834.183
946281AF1-292 C
80/20
2.0562.056
926071AC1-086 C
80/20
28.07728.077
927021AC1-189 C
Adder
11.1952941176470599.516
964241AG1-285 C
Adder
14.80352941176470712.583
962561AG1-105 C
Adder
11.0694117647058839.409
961611AG1-000B C
Adder
17.0670588235294114.507
316072AD1-144 C
80/20
0.3590.359
316375AC2-012 C
80/20
1.7911.791
315614AA2-178 C
80/20
2.0912.091
940541AE2-040 C
80/20
3.9443.944
940481AE2-033 C
80/20
22.18122.181
3151411GASTONB
80/20
4.0664.066
316181AB2-040 GEN
80/20
1.6831.683
3147043LAWRENC
80/20
0.3980.398
935161AD1-151 C
Adder
15.27058823529411812.98
958161AF2-110 C
80/20
1.7981.798
938531AE1-072 C
80/20
23.60823.608
933981AD1-022 C
80/20
11.71411.714
316174AB2-169_C
80/20
1.3931.393
3156063AA2-053SOLA
80/20
1.9981.998
3151281ROARAP4
80/20
1.7351.735
316036AC1-147 C
80/20
0.4890.489
316305AF2-043 C
80/20
0.4630.463
316321Z2-027 C
80/20
0.4860.486
934521AD1-076 C
80/20
16.37216.372
934511AD1-075 C
80/20
11.2711.27
3156073AA1-063SOLA
80/20
1.8611.861
316087AB2-174 C
80/20
1.561.56
316212AC1-099 C
80/20
0.4180.418
316263AC1-034 C
Adder
8.8035294117647057.483
937481AD2-202 C
80/20
0.5130.513
959311AF2-222 C
Adder
18.28823529411764815.545
940431AE2-027 C
Adder
11.395294117647069.686
916191Z1-068 C
80/20
0.0580.058
941101AE2-104 C
80/20
4.4074.407
316185AD1-033 C
80/20
1.6481.648
944581AF1-123 C
80/20
61.95761.957
316294AC1-161 C
80/20
6.8246.824
3156083AA2-088SOLA
80/20
1.4051.405
316365AB2-100 C1
80/20
1.2911.291
3151021BRUNSWICKG1
80/20
13.44613.446
957481AF2-042 C
80/20
78.71578.715
939191AE1-149 C
Adder
11.99058823529411710.192
3150981CHESPKA
80/20
0.5780.578
3151151S HAMPT1
80/20
1.9741.974
3151361ROSEMG1
80/20
2.7122.712
3151041BRUNSWICKG3
80/20
13.44613.446
964791AG1-342 C
Adder
4.4317647058823533.767
316316AC1-027 C
80/20
0.4210.421
316315AB2-025 C
80/20
0.5580.558
316023AB2-100 C2
80/20
1.2911.291
316317KELFORD C
80/20
0.4760.476
316129AC1-054 C
80/20
1.5891.589
3138533PONTONDP
Adder
0.6764705882352940.575
941591AE2-156 C
80/20
23.83823.838
3151101ELIZAR3
80/20
4.3114.311
944591AF1-124 C
80/20
62.17762.177
944601AF1-125 C
80/20
61.00261.002
938771AE1-103 C
80/20
3.8693.869
960081AF2-299 C
80/20
2.4842.484
3151381ROSEMG2
80/20
1.271.27
944011AF1-069 C
80/20
21.71321.713
963041AG1-153 C
80/20
9.1419.141
3151051BRUNSWICKS1
80/20
27.93527.935
936261AD2-033 C
Adder
14.72470588235294112.516
961791AG1-021 C
Adder
1.82588235294117651.552
936171AD2-023 C
Adder
5.5152941176470584.688
3152331SURRY 2
80/20
30.82730.827
316017AA1-139 ULT1
80/20
1.4491.449
313526AB2-022 C
80/20
0.5040.504
940641AE2-051 C
80/20
28.76428.764
3152431Z1-086 GT3
80/20
17.27717.277
934611AD1-087 C
80/20
1.7671.767
943461AF1-017 C
80/20
1.7011.701
316311AC2-079 C
80/20
7.2667.266
3156056W1-029WIND
80/20
1.0361.036
3151261ROARAP2
80/20
1.8341.834
3152421Z1-086 GT2
80/20
17.27717.277
3152441Z1-086 ST
80/20
30.08230.082
3152411Z1-086 GT1
80/20
17.28217.282
3150991CHESPKB
80/20
0.9580.958
939411AE1-173 C
80/20
144.1144.1
3156021HOLLOMANSOL
80/20
2.4482.448
316011AB1-132 C OP
80/20
3.1053.105
3151371ROSEMS1
80/20
1.681.68
3137643SOCKMAN
80/20
0.9470.947
3150921YORKTN3
Adder
127.84235294117647108.666
316018AA1-139 ULT2
80/20
1.4491.449
933291AC2-141 C
80/20
41.90441.904
3152921DOMTR78
80/20
1.8181.818
316140AB2-099 C
80/20
0.1280.128
SIGELTFEXP_SIGE->PJM
CLTF
0.4150.415
NYPJM->LTFIMP_NY
CLTF
2.5592.559
LGEELTFEXP_LGEE->PJM
CLTF
2.182.18
WECLTFEXP_WEC->PJM
CLTF
1.1331.133
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.0655.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.38335.383
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.566.56
LAGNLTFEXP_LAGN->PJM
CLTF
11.74411.744
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.597.59
CBM South 2LTFEXP_CBM-S2->PJM
CBM
135.46135.46
CPLELTFEXP_CPLE->PJM
CLTF
15.91315.913
TVALTFEXP_TVA->PJM
CLTF
9.319.31

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.4 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3845.28
MW Contribution:3.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
83.0647058823529570.605
941591AE2-156 C
80/20
27.03327.033
3151101ELIZAR3
80/20
4.8814.881
944591AF1-124 C
80/20
69.22169.221
944601AF1-125 C
80/20
67.91467.914
938771AE1-103 C
80/20
4.3814.381
960081AF2-299 C
Adder
2.74941176470588242.337
944011AF1-069 C
80/20
20.63520.635
963041AG1-153 C
80/20
8.7798.779
3151051BRUNSWICKS1
80/20
26.8326.83
936261AD2-033 C
Adder
17.81058823529411615.139
961791AG1-021 C
Adder
2.40470588235294122.044
3150831SPRUNCA
80/20
13.15813.158
3150841SPRUNCB
80/20
13.15813.158
3151081ELIZAR1
80/20
4.824.82
961941AG1-037 C
Adder
0.74470588235294120.633
941031AE2-094 C
80/20
63.15563.155
934331AD1-057 C
Adder
5.04588235294117654.289
934321AD1-056 C
Adder
9.0458823529411777.689
3151531CLOVER1
80/20
18.57418.574
3151541CLOVER2
80/20
18.39918.399
316258AE1-075 C
80/20
0.5130.513
958211AF2-115 C
Adder
3.0058823529411772.555
942001AE2-212 C
80/20
3.1513.151
3156116Z1-036WIND
80/20
0.9810.981
934501AD1-074 C
Adder
50.0317647058823542.527
3151031BRUNSWICKG2
80/20
12.91412.914
961671AG1-007 C
Adder
1.34941176470588231.147
934621AD1-088 C
80/20
14.01914.019
946301AF1-294 C
Adder
4.9423529411764714.201
942461AE2-259 C
Adder
12.99058823529411711.042
944641AF1-129 C
Adder
144.29529411764705122.651
316240AF1-291 C
Adder
3.0682352941176472.608
316036AC1-147 C
80/20
0.5540.554
316305AF2-043 C
80/20
0.5240.524
316321Z2-027 C
80/20
0.5460.546
934521AD1-076 C
Adder
18.1705882352941215.445
934511AD1-075 C
Adder
12.50823529411764710.632
316263AC1-034 C
Adder
9.488.058
959311AF2-222 C
Adder
22.66470588235294419.265
942341AE2-247 C
80/20
2.2382.238
316246AF1-032 C
80/20
0.4280.428
316388AE2-253 GEN
80/20
2.9552.955
316320Y1-086 C
80/20
0.330.33
966621AG1-532 C
Adder
2.06235294117647071.753
3150651CHESTF6
Adder
26.27176470588235422.331
3150861SPRUNCD
80/20
0.2360.236
957871AF2-081 C
80/20
15.07515.075
316274AC1-208 C
Adder
13.08588235294117711.123
3151311EDGECMA
Adder
22.1658823529411818.841
316405AF2-144 C
80/20
0.4360.436
940431AE2-027 C
Adder
18.39647058823529615.637
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
5.0455.045
316185AD1-033 C
80/20
1.8511.851
944581AF1-123 C
80/20
68.97668.976
316294AC1-161 C
80/20
7.5057.505
316365AB2-100 C1
80/20
1.4231.423
3151021BRUNSWICKG1
80/20
12.91412.914
957481AF2-042 C
80/20
80.37380.373
316169AC1-164 GEN
Adder
49.0282352941176541.674
316349AD2-085 C
80/20
5.1625.162
3151091ELIZAR2
80/20
4.7364.736
946281AF1-292 C
Adder
2.2752941176470591.934
926071AC1-086 C
Adder
30.83882352941176626.213
927021AC1-189 C
Adder
12.14117647058823710.32
964241AG1-285 C
Adder
17.31176470588235414.715
962561AG1-105 C
Adder
12.25882352941176610.42
961611AG1-000B C
Adder
22.90588235294117719.47
316072AD1-144 C
80/20
0.4180.418
316375AC2-012 C
80/20
2.0322.032
940541AE2-040 C
80/20
4.3564.356
940481AE2-033 C
80/20
24.49624.496
3150731STONECA
Adder
9.5788235294117648.142
935161AD1-151 C
Adder
22.80117647058823519.381
316083AB2-161 C
80/20
0.8230.823
958161AF2-110 C
80/20
2.0582.058
938531AE1-072 C
80/20
26.49826.498
933981AD1-022 C
Adder
12.98823529411764711.04
943471AF1-018 C
Adder
8.4917647058823537.218
3151221GRAVEL6
80/20
3.6533.653
3151201GRAVEL4
80/20
3.6573.657
3151211GRAVEL5
80/20
3.6113.611
939191AE1-149 C
80/20
15.94215.942
3150981CHESPKA
80/20
0.6560.656
3151041BRUNSWICKG3
80/20
12.91412.914
316313AB2-026 C
80/20
0.5590.559
964791AG1-342 C
Adder
4.884.148
957601AF2-054 C
Adder
2.53058823529411742.151
316316AC1-027 C
80/20
0.4760.476
316315AB2-025 C
80/20
0.6170.617
316023AB2-100 C2
80/20
1.4231.423
3138533PONTONDP
Adder
0.89058823529411770.757
316236AE1-162 C
80/20
0.5140.514
3152331SURRY 2
80/20
35.95635.956
316017AA1-139 ULT1
80/20
1.6261.626
313526AB2-022 C
80/20
0.5650.565
940641AE2-051 C
80/20
27.74527.745
3152431Z1-086 GT3
80/20
16.53816.538
316336AC2-165 C
Adder
14.04941176470588411.942
940551AE2-041 C
Adder
8.4917647058823537.218
943461AF1-017 C
80/20
2.0242.024
316311AC2-079 C
80/20
8.6058.605
3156056W1-029WIND
80/20
1.1641.164
316233AE1-074 C
80/20
3.9163.916
3152421Z1-086 GT2
80/20
16.53816.538
3152441Z1-086 ST
80/20
28.79528.795
3152411Z1-086 GT1
80/20
16.54216.542
3151161SURRY 1
80/20
35.54335.543
316381AD1-082 C
80/20
1.8751.875
3150991CHESPKB
80/20
1.0871.087
939411AE1-173 C
80/20
143.49143.49
3137643SOCKMAN
Adder
1.04352941176470580.887
944631AF1-128 C
Adder
51.9752941176470644.179
3150921YORKTN3
Adder
165.5670588235294140.732
3151191GRAVEL3
80/20
3.6113.611
3150851SPRUNCC
80/20
0.2360.236
316018AA1-139 ULT2
80/20
1.6261.626
933291AC2-141 C
80/20
46.08646.086
316303AF2-085
80/20
6.4786.478
SIGELTFEXP_SIGE->PJM
CLTF
0.4870.487
NYPJM->LTFIMP_NY
CLTF
3.1863.186
LGEELTFEXP_LGEE->PJM
CLTF
2.5932.593
WECLTFEXP_WEC->PJM
CLTF
1.3381.338
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.12565.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.22440.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6237.623
LAGNLTFEXP_LAGN->PJM
CLTF
13.13513.135
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.9747.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
144.491144.491
CPLELTFEXP_CPLE->PJM
CLTF
16.71416.714
TVALTFEXP_TVA->PJM
CLTF
10.46710.467

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.63 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3595.09
MW Contribution:1.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
941591AE2-156 C
Adder
12.43294117647058910.568
944591AF1-124 C
Adder
32.1611764705882427.337
944601AF1-125 C
Adder
31.55411764705882826.821
938771AE1-103 C
Adder
2.10235294117647081.787
960081AF2-299 C
80/20
1.4551.455
944011AF1-069 C
80/20
12.12612.126
963041AG1-153 C
80/20
5.1375.137
3151051BRUNSWICKS1
80/20
15.69915.699
936261AD2-033 C
80/20
10.37510.375
961791AG1-021 C
80/20
1.4371.437
316045AC1-158 C2
80/20
18.51718.517
316170AC1-121 C
80/20
2.952.95
961941AG1-037 C
Adder
0.37294117647058830.317
941031AE2-094 C
80/20
37.11337.113
934331AD1-057 C
Adder
2.6258823529411772.232
934321AD1-056 C
Adder
4.7070588235294134.001
3151531CLOVER1
80/20
10.82910.829
3151541CLOVER2
80/20
10.72710.727
316258AE1-075 C
80/20
0.320.32
958211AF2-115 C
80/20
1.7961.796
3151791S ANNAG2
80/20
3.2623.262
3151771S ANNAG1
80/20
3.2623.262
3151781S ANNAS1
80/20
1.6761.676
3151761LOISA E
80/20
6.8276.827
208900BRIS G1
80/20
-2.405-2.405
942001AE2-212 C
Adder
1.40235294117647061.192
934501AD1-074 C
Adder
24.38588235294117720.728
3151031BRUNSWICKG2
80/20
7.5577.557
961671AG1-007 C
Adder
0.69647058823529410.592
934621AD1-088 C
80/20
8.2538.253
946301AF1-294 C
80/20
2.9542.954
942461AE2-259 C
80/20
7.9867.986
316192AB2-158 C
80/20
4.3254.325
208901BRIS G2
80/20
-2.846-2.846
934521AD1-076 C
Adder
8.8564705882352937.528
942341AE2-247 C
Adder
1.03882352941176470.883
966621AG1-532 C
80/20
1.0911.091
935171AD1-152 C
80/20
1.0991.099
3152261N ANNA2
80/20
103.963103.963
934861AD1-115 C
80/20
3.3063.306
957871AF2-081 C
Adder
7.0094117647058835.958
316274AC1-208 C
Adder
6.785.763
3151311EDGECMA
Adder
11.569.826
316405AF2-144 C
80/20
0.2720.272
316349AD2-085 C
Adder
2.3964705882352942.037
946281AF1-292 C
80/20
1.2041.204
926071AC1-086 C
Adder
15.98823529411764713.59
927021AC1-189 C
Adder
6.225.287
964241AG1-285 C
80/20
9.9749.974
316034AC1-036 C
80/20
0.1860.186
962561AG1-105 C
Adder
6.9729411764705885.927
3144293JTRSVLE
80/20
0.3290.329
316044AC1-158 C1
80/20
18.51718.517
940541AE2-040 C
80/20
2.2982.298
940481AE2-033 C
80/20
12.91312.913
3147043LAWRENC
80/20
0.240.24
966001AG1-469 C
80/20
2.3822.382
958161AF2-110 C
Adder
0.96117647058823530.817
938531AE1-072 C
Adder
12.33529411764705810.485
933981AD1-022 C
Adder
6.3599999999999995.406
316238AB2-078 C O1
80/20
0.2590.259
934511AD1-075 C
Adder
6.0964705882352945.182
316087AB2-174 C
80/20
0.9080.908
316263AC1-034 C
Adder
4.9470588235294124.205
937481AD2-202 C
80/20
0.3090.309
959311AF2-222 C
80/20
13.30313.303
941101AE2-104 C
Adder
2.35411764705882342.001
944581AF1-123 C
Adder
32.0470588235294127.24
316365AB2-100 C1
80/20
0.7450.745
3151021BRUNSWICKG1
80/20
7.5577.557
957481AF2-042 C
80/20
47.06247.062
3151801S ANNAS2
80/20
1.6761.676
939191AE1-149 C
Adder
7.2929411764705886.199
3151041BRUNSWICKG3
80/20
7.5577.557
316239AB2-077 C O1
80/20
0.2590.259
316313AB2-026 C
80/20
0.3480.348
964791AG1-342 C
Adder
2.77294117647058872.357
3151751LOISA D
80/20
3.3493.349
3151731LOISA B
80/20
3.3493.349
316164AC1-076_C
80/20
1.0891.089
316315AB2-025 C
80/20
0.3250.325
316023AB2-100 C2
80/20
0.7450.745
316131AB2-060 C
80/20
1.1781.178
3138533PONTONDP
80/20
0.5320.532
3151721LOISA A
80/20
3.3313.331
316254AC1-120 C
80/20
8.5918.591
316257AC1-043 C
80/20
6.6126.612
940641AE2-051 C
80/20
15.75815.758
3152431Z1-086 GT3
80/20
9.699.69
934611AD1-087 C
80/20
1.0661.066
316237AB2-079 C O1
80/20
0.2590.259
316336AC2-165 C
80/20
8.8748.874
943461AF1-017 C
Adder
0.94000000000000010.799
316311AC2-079 C
Adder
3.99647058823529383.397
316233AE1-074 C
80/20
2.0672.067
3152421Z1-086 GT2
80/20
9.699.69
3152441Z1-086 ST
80/20
16.87216.872
3152411Z1-086 GT1
80/20
9.6939.693
939411AE1-173 C
80/20
78.11378.113
3137643SOCKMAN
Adder
0.54588235294117650.464
3151741LOISA C
80/20
3.3493.349
933291AC2-141 C
Adder
21.0423529411764717.886
313527AB2-043 C
80/20
0.4090.409
3152251N ANNA1
80/20
103.92103.92
316303AF2-085
80/20
3.8763.876
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165
NYPJM->LTFIMP_NY
CLTF
2.292.29
LGEELTFEXP_LGEE->PJM
CLTF
0.8350.835
WECLTFEXP_WEC->PJM
CLTF
0.4130.413
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.20919.209
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.12316.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.6672.667
LAGNLTFEXP_LAGN->PJM
CLTF
5.7055.705
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2194.219
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.82173.821
CPLELTFEXP_CPLE->PJM
CLTF
8.8538.853
TVALTFEXP_TVA->PJM
CLTF
4.5224.522

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.86 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3570.05
MW Contribution:1.88
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
941591AE2-156 C
Adder
13.23882352941176611.253
944591AF1-124 C
Adder
34.2229.087
944601AF1-125 C
Adder
33.5741176470588328.538
938771AE1-103 C
Adder
2.2329411764705881.898
960081AF2-299 C
80/20
1.5351.535
944011AF1-069 C
80/20
12.71412.714
963041AG1-153 C
80/20
5.3875.387
3151051BRUNSWICKS1
80/20
16.46316.463
936261AD2-033 C
80/20
10.85610.856
961791AG1-021 C
80/20
1.51.5
3150831SPRUNCA
Adder
6.1623529411764715.238
3150841SPRUNCB
Adder
6.1623529411764715.238
961941AG1-037 C
Adder
0.39411764705882360.335
941031AE2-094 C
80/20
38.91138.911
934331AD1-057 C
Adder
2.7741176470588242.358
934321AD1-056 C
Adder
4.9729411764705894.227
3151531CLOVER1
80/20
11.34911.349
3151541CLOVER2
80/20
11.24311.243
316258AE1-075 C
80/20
0.3330.333
958211AF2-115 C
80/20
1.8751.875
3151791S ANNAG2
80/20
3.0413.041
3151771S ANNAG1
80/20
3.0413.041
3151781S ANNAS1
80/20
1.5631.563
3151761LOISA E
80/20
6.316.31
208900BRIS G1
80/20
-2.414-2.414
942001AE2-212 C
Adder
1.49882352941176471.274
934501AD1-074 C
Adder
25.86823529411764621.988
3151031BRUNSWICKG2
80/20
7.9247.924
961671AG1-007 C
Adder
0.73647058823529410.626
934621AD1-088 C
80/20
8.6418.641
946301AF1-294 C
80/20
3.0833.083
942461AE2-259 C
Adder
8.3117647058823547.065
316192AB2-158 C
80/20
4.2764.276
208901BRIS G2
80/20
-2.857-2.857
942341AE2-247 C
Adder
1.10588235294117650.94
966621AG1-532 C
80/20
1.1511.151
313506AB1-173 C OP
80/20
0.9150.915
935171AD1-152 C
80/20
1.1531.153
3152261N ANNA2
80/20
106.999106.999
3150651CHESTF6
Adder
11.5976470588235319.858
957871AF2-081 C
Adder
7.4588235294117656.34
316274AC1-208 C
Adder
7.1635294117647066.089
3151311EDGECMA
Adder
12.21411764705882410.382
316405AF2-144 C
80/20
0.2830.283
316349AD2-085 C
Adder
2.5505882352941182.168
946281AF1-292 C
80/20
1.2711.271
926071AC1-086 C
Adder
16.8929411764705914.359
927021AC1-189 C
Adder
6.5788235294117645.592
964241AG1-285 C
80/20
10.44910.449
316034AC1-036 C
80/20
0.1950.195
962561AG1-105 C
Adder
7.3152941176470596.218
3144293JTRSVLE
80/20
0.3440.344
961611AG1-000B C
Adder
10.3129411764705888.766
940541AE2-040 C
80/20
2.4262.426
940481AE2-033 C
80/20
13.63113.631
316181AB2-040 GEN
80/20
1.0311.031
3147043LAWRENC
80/20
0.2530.253
966001AG1-469 C
80/20
1.9821.982
958161AF2-110 C
Adder
1.02235294117647070.869
938531AE1-072 C
Adder
13.12352941176470511.155
933981AD1-022 C
Adder
6.7447058823529415.733
316238AB2-078 C O1
80/20
0.2720.272
944641AF1-129 C
Adder
63.6988235294117654.144
316240AF1-291 C
Adder
1.37882352941176461.172
934521AD1-076 C
Adder
9.3952941176470587.986
934511AD1-075 C
Adder
6.46705882352941155.497
316087AB2-174 C
80/20
0.9580.958
316263AC1-034 C
Adder
5.2270588235294114.443
937481AD2-202 C
80/20
0.3240.324
959311AF2-222 C
80/20
13.90913.909
940431AE2-027 C
Adder
8.3129411764705887.066
941101AE2-104 C
Adder
2.50470588235294132.129
944581AF1-123 C
Adder
34.0988235294117728.984
316365AB2-100 C1
80/20
0.7870.787
3151021BRUNSWICKG1
80/20
7.9247.924
957481AF2-042 C
80/20
49.31549.315
3151801S ANNAS2
80/20
1.5631.563
939191AE1-149 C
Adder
7.7752941176470596.609
3151041BRUNSWICKG3
80/20
7.9247.924
316239AB2-077 C O1
80/20
0.2720.272
316313AB2-026 C
80/20
0.3630.363
964791AG1-342 C
Adder
2.9105882352941182.474
3151751LOISA D
80/20
3.0953.095
3151731LOISA B
80/20
3.0953.095
316315AB2-025 C
80/20
0.3440.344
316023AB2-100 C2
80/20
0.7870.787
316131AB2-060 C
80/20
1.2351.235
3138533PONTONDP
80/20
0.5550.555
3151721LOISA A
80/20
3.0793.079
940641AE2-051 C
80/20
16.55416.554
3152431Z1-086 GT3
80/20
10.16110.161
934611AD1-087 C
80/20
1.1171.117
316237AB2-079 C O1
80/20
0.2720.272
316336AC2-165 C
80/20
9.2269.226
943461AF1-017 C
Adder
1.00.85
316311AC2-079 C
Adder
4.2541176470588233.616
316233AE1-074 C
80/20
2.1822.182
3152421Z1-086 GT2
80/20
10.16110.161
3152441Z1-086 ST
80/20
17.69217.692
3152411Z1-086 GT1
80/20
10.16410.164
939411AE1-173 C
80/20
82.26382.263
3137643SOCKMAN
Adder
0.57647058823529410.49
3151741LOISA C
80/20
3.0953.095
933291AC2-141 C
Adder
22.41294117647058619.051
313527AB2-043 C
80/20
0.4290.429
3152251N ANNA1
80/20
106.954106.954
316303AF2-085
80/20
4.064.06
SIGELTFEXP_SIGE->PJM
CLTF
0.1860.186
NYPJM->LTFIMP_NY
CLTF
2.2912.291
LGEELTFEXP_LGEE->PJM
CLTF
0.9480.948
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.24822.248
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.65817.658
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.9882.988
LAGNLTFEXP_LAGN->PJM
CLTF
6.1746.174
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4574.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
78.26878.268
CPLELTFEXP_CPLE->PJM
CLTF
9.3529.352
TVALTFEXP_TVA->PJM
CLTF
4.8954.895

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.14 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4339.53
MW Contribution:3.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943462AF1-017 E
Adder
1.621.377
942341AE2-247 C
Adder
1.09764705882352940.933
958162AF2-110 E
Adder
1.61411764705882371.372
934576AD1-082 E
Adder
3.19882352941176462.719
943612AF1-032 E
Adder
0.68470588235294120.582
3145506HICKORY
Adder
1.61411764705882371.372
944602AF1-125 E
Adder
76.3341176470588364.884
957871AF2-081 C
Adder
7.4070588235294126.296
933292AC2-141 E
Adder
9.502352941176478.077
940492AE2-034 E
Adder
2.3364705882352941.986
934522AD1-076 E
Adder
4.7541176470588244.041
3150831SPRUNCA
Adder
6.117647058823535.2
3150841SPRUNCB
Adder
6.117647058823535.2
926662AC1-147 E
Adder
0.97176470588235290.826
916192Z1-068 E
Adder
1.38588235294117631.178
957492AF2-043 E
Adder
1.05294117647058830.895
923852AB2-025 E
Adder
0.97529411764705880.829
939412AE1-173 E
Adder
54.5505882352941246.368
961942AG1-037 E
Adder
0.26117647058823530.222
961941AG1-037 C
Adder
0.391764705882352960.333
941031AE2-094 C
50/50
38.72138.721
941032AE2-094 E
50/50
17.34217.342
934331AD1-057 C
Adder
2.75294117647058822.34
934322AD1-056 E
Adder
2.6764705882352942.275
934332AD1-057 E
Adder
1.43411764705882371.219
934321AD1-056 C
Adder
4.9352941176470594.195
927022AC1-189 E
Adder
3.25058823529411762.763
925595AC1-034 E
Adder
3.91058823529411773.324
936262AD2-033 E
Adder
7.1882352941176476.11
923862AB2-026 E
Adder
1.17294117647058820.997
958211AF2-115 C
Adder
1.86235294117647051.583
3151791S ANNAG2
50/50
3.0513.051
3151771S ANNAG1
50/50
3.0513.051
3151781S ANNAS1
50/50
1.5681.568
3151761LOISA E
50/50
6.3326.332
208900BRIS G1
50/50
-2.489-2.489
940541AE2-040 C
Adder
2.4117647058823532.05
940481AE2-033 C
Adder
13.54823529411764811.516
940482AE2-033 E
Adder
9.1341176470588247.764
923263AB1-132 E OP
Adder
4.8811764705882354.149
924312AB2-078 E O1
Adder
1.10588235294117650.94
925612AC1-036 E
Adder
0.7117647058823530.605
926274AC1-105 E
Adder
2.1788235294117651.852
966001AG1-469 C
50/50
2.0062.006
926740AC1-158 E2
50/50
51.18251.182
932046AC2-012 E
Adder
9.6164705882352938.174
958161AF2-110 C
Adder
1.0152941176470590.863
938531AE1-072 C
Adder
13.03294117647058811.078
3145393UNCAMP
Adder
4.622352941176473.929
933981AD1-022 C
Adder
6.6952941176470595.691
900672V4-068 E
Adder
0.276470588235294130.235
924302AB2-077 E O1
Adder
1.10588235294117650.94
939192AE1-149 E
Adder
5.1470588235294124.375
939312AE1-162 E
Adder
0.97647058823529410.83
942001AE2-212 C
Adder
1.48705882352941181.264
934065AD1-033 E
Adder
3.70941176470588243.153
937226AE2-253 E
Adder
4.3282352941176473.679
934501AD1-074 C
Adder
25.6821.828
924517AB2-100 E2
Adder
2.36470588235294082.01
961671AG1-007 C
Adder
0.73058823529411760.621
957482AF2-042 E
Adder
32.6894117647058927.786
934621AD1-088 C
Adder
8.5905882352941177.302
935172AD1-152 E
Adder
4.7270588235294114.018
958502AF2-144 E
Adder
1.15294117647058810.98
946301AF1-294 C
Adder
3.06235294117647072.603
942461AE2-259 C
Adder
8.257647058823537.019
316192AB2-158 C
50/50
4.2784.278
208901BRIS G2
50/50
-2.946-2.946
942002AE2-212 E
Adder
0.99176470588235290.843
941101AE2-104 C
Adder
2.48705882352941152.114
944581AF1-123 C
Adder
33.8670588235294128.787
316141AB2-099 E
Adder
0.195294117647058840.166
316088AB2-174 E
Adder
5.2858823529411774.493
923994AB2-040_E
Adder
4.9741176470588234.228
961672AG1-007 E
Adder
0.414117647058823530.352
957481AF2-042 C
Adder
49.0341176470588341.679
924322AB2-079 E O1
Adder
1.10588235294117650.94
946302AF1-294 E
Adder
2.59294117647058852.204
943902AF1-058 E
Adder
1.04352941176470580.887
3151801S ANNAS2
50/50
1.5681.568
919153AA1-139 E2
Adder
3.02941176470588272.575
934502AD1-074 E
Adder
13.07176470588235311.111
934512AD1-075 E
Adder
3.26823529411764732.778
918512AA1-065 E OP
Adder
4.2588235294117653.62
924516AB2-100 E1
Adder
2.36470588235294082.01
940642AE2-051 E
50/50
10.98110.981
966621AG1-532 C
Adder
1.1435294117647060.972
918532AA1-067 E
Adder
0.55176470588235290.469
924022AB2-043 E O1
Adder
4.2929411764705883.649
3147223TWITTYS
Adder
0.78941176470588240.671
959312AF2-222 E
Adder
9.2564705882352957.868
3152261N ANNA2
50/50
106.886106.886
943172AE2-346 E
Adder
0.46941176470588240.399
918492AA1-063AE OP
Adder
3.22705882352941182.743
925122AB2-169 E
Adder
4.4105882352941183.749
917332KELFORD E
Adder
1.281.088
316274AC1-208 C
Adder
7.1094117647058826.043
917342Z2-044 E
Adder
0.46823529411764710.398
3151311EDGECMA
Adder
12.11411764705882510.297
937482AD2-202 E
Adder
0.94117647058823540.8
961792AG1-021 E
Adder
1.26941176470588221.079
939191AE1-149 C
Adder
7.7200000000000016.562
3143316POE
Adder
1.04235294117647070.886
901082W1-029 E
Adder
23.76705882352941420.202
926206AC1-098 E
Adder
2.86705882352941142.437
964791AG1-342 C
Adder
2.88941176470588262.456
942462AE2-259 E
Adder
5.5047058823529414.679
3151751LOISA D
50/50
3.1063.106
3151731LOISA B
50/50
3.1063.106
935112AD1-144 E
Adder
0.67176470588235290.571
316349AD2-085 C
Adder
2.53294117647058852.153
944582AF1-123 E
Adder
77.5517647058823565.919
944592AF1-124 E
Adder
77.8317647058823566.157
923832AB2-022 E
Adder
0.92235294117647060.784
938772AE1-103 E
Adder
3.0611764705882352.602
916042Z1-036 E
Adder
21.48117647058823518.259
960082AF2-299 E
Adder
1.01647058823529420.864
946281AF1-292 C
Adder
1.26235294117647071.073
926071AC1-086 C
Adder
16.77411764705882314.258
963042AG1-153 E
Adder
8.0388235294117656.833
927021AC1-189 C
Adder
6.5247058823529425.546
924152AB2-059 E OP
Adder
4.122352941176473.504
964241AG1-285 C
Adder
10.3776470588235298.821
962561AG1-105 C
Adder
7.2635294117647076.174
958212AF2-115 E
Adder
1.58588235294117651.348
925022AB2-158 E
50/50
11.37311.373
316044AC1-158 C1
50/50
19.56819.568
946282AF1-292 E
Adder
0.84117647058823530.715
944012AF1-069 E
50/50
4.9154.915
917512Z2-088 E OP1
Adder
3.8047058823529413.234
3138533PONTONDP
Adder
0.55176470588235290.469
3151721LOISA A
50/50
3.093.09
936666AD2-085 E
Adder
4.1329411764705883.513
941591AE2-156 C
Adder
13.14823529411764711.176
944591AF1-124 C
Adder
33.9870588235294128.889
944601AF1-125 C
Adder
33.3447058823529428.343
938771AE1-103 C
Adder
2.21764705882352951.885
3145413WATKINS
Adder
0.52941176470588240.45
960081AF2-299 C
Adder
1.52470588235294141.296
926072AC1-086 E
Adder
7.6341176470588236.489
944011AF1-069 C
50/50
12.65212.652
963041AG1-153 C
Adder
5.3588235294117644.555
936261AD2-033 C
Adder
10.782352941176479.165
962562AG1-105 E
Adder
4.842352941176474.116
961791AG1-021 C
Adder
1.48941176470588241.266
924032AB2-045 E
Adder
1.08588235294117650.923
316045AC1-158 C2
50/50
19.56819.568
316084AB2-161 E
Adder
4.0141176470588233.412
3145946PLYMOUTH TP
Adder
0.245882352941176470.209
933982AD1-022 E
Adder
3.6447058823529413.098
940641AE2-051 C
50/50
16.47216.472
927146AC1-208 E
Adder
3.1564705882352942.683
934622AD1-088 E
Adder
4.1364705882352943.516
934612AD1-087 E
Adder
3.2152941176470592.733
316336AC2-165 C
Adder
9.177647058823537.801
927255AC1-221 E
Adder
2.9588235294117652.515
943461AF1-017 C
Adder
0.99294117647058820.844
932596AC2-079 E
Adder
6.8929411764705895.859
316311AC2-079 C
Adder
4.2247058823529413.591
938532AE1-072 E
Adder
6.7941176470588245.775
3146326AYDLETT TAP
Adder
1.00588235294117640.855
917122Z2-027 E
Adder
1.00.85
920692AA2-178 E
Adder
3.1141176470588232.647
316233AE1-074 C
Adder
2.17058823529411751.845
966622AG1-532 E
Adder
0.76235294117647070.648
922923AB1-081 E OP
Adder
2.9105882352941182.474
3147133PAMPLIN
Adder
0.82352941176470580.7
927264AC1-222 E
Adder
3.20470588235294152.724
966002AG1-469 E
50/50
1.0031.003
926739AC1-158 E1
50/50
51.18251.182
913392Y1-086 E
Adder
1.63411764705882371.389
939411AE1-173 C
Adder
81.8247058823529469.551
3137643SOCKMAN
Adder
0.57294117647058830.487
919710AA2-057 E
Adder
3.1117647058823532.645
933502AC2-165 E
Adder
6.9070588235294135.871
3151741LOISA C
50/50
3.1063.106
3145256KINGFORK
Adder
0.72352941176470590.615
925522AC1-027 E
Adder
0.89764705882352950.763
941102AE2-104 E
Adder
3.9541176470588243.361
957872AF2-081 E
Adder
3.17411764705882372.698
933291AC2-141 C
Adder
22.2618.921
926755AC1-161 E
Adder
9.502352941176478.077
938552AE1-074 E
Adder
1.09294117647058830.929
932632AC2-084 E
Adder
2.53411764705882362.154
926214AC1-099 E
Adder
0.94705882352941180.805
924162AB2-060 E OP
Adder
3.54470588235294143.013
964242AG1-285 E
Adder
6.9188235294117655.881
938562AE1-075 E
Adder
1.00.85
964792AG1-342 E
Adder
1.92588235294117661.637
932763AC2-100 E
Adder
2.00588235294117641.705
3152251N ANNA1
50/50
106.841106.841
942342AE2-247 E
Adder
1.5164705882352941.289
919152AA1-139 E1
Adder
3.02941176470588272.575
934521AD1-076 C
Adder
9.3258823529411777.927
934511AD1-075 C
Adder
6.425.457
920042AA2-088 E OP
Adder
8.226.987
3145723EMPORIA
Adder
0.350588235294117640.298
923573AB1-173 E OP
Adder
2.6529411764705882.255
919692AA2-053 E OP
Adder
3.36117647058823542.857
925785AC1-054 E
Adder
2.79764705882352962.378
316263AC1-034 C
Adder
5.1835294117647064.406
959311AF2-222 C
Adder
13.8152941176470611.743
316303AF2-085
50/50
4.0434.043
G-007PJM->LTFIMP_G-007
CMTX_NF
5.0575.057
SIGELTFEXP_SIGE->PJM
CLTF
0.1730.173
NYPJM->LTFIMP_NY
CLTF
2.3732.373
LGEELTFEXP_LGEE->PJM
CLTF
0.8720.872
WECLTFEXP_WEC->PJM
CLTF
0.4310.431
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.05120.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.83616.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7842.784
LAGNLTFEXP_LAGN->PJM
CLTF
5.9595.959
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4084.408
CBM South 2LTFEXP_CBM-S2->PJM
CBM
77.11777.117
CPLELTFEXP_CPLE->PJM
CLTF
9.2519.251
TVALTFEXP_TVA->PJM
CLTF
4.7224.722
O66PJM->LTFIMP_O-066
CMTX_NF
32.20632.206

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.71 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3758.56
MW Contribution:2.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
45.29058823529411638.497
941591AE2-156 C
80/20
15.98415.984
3151101ELIZAR3
80/20
2.8872.887
944591AF1-124 C
80/20
41.04941.049
944601AF1-125 C
80/20
40.27340.273
938771AE1-103 C
80/20
2.6332.633
960081AF2-299 C
80/20
1.7191.719
944011AF1-069 C
80/20
13.43113.431
963041AG1-153 C
80/20
5.7035.703
3151051BRUNSWICKS1
80/20
17.42917.429
936261AD2-033 C
Adder
11.7211764705882359.963
961791AG1-021 C
Adder
1.61176470588235321.37
3150831SPRUNCA
Adder
7.7905882352941186.622
3150841SPRUNCB
Adder
7.7905882352941186.622
3151081ELIZAR1
80/20
2.8512.851
961941AG1-037 C
Adder
0.454117647058823570.386
941031AE2-094 C
80/20
41.10641.106
934331AD1-057 C
Adder
3.11764705882352942.65
934321AD1-056 C
Adder
5.5882352941176484.75
3151531CLOVER1
80/20
12.09912.099
3151541CLOVER2
80/20
11.98511.985
316258AE1-075 C
80/20
0.3530.353
958211AF2-115 C
Adder
2.0152941176470591.713
3151791S ANNAG2
80/20
2.372.37
3151771S ANNAG1
80/20
2.372.37
3151781S ANNAS1
80/20
1.2181.218
3151761LOISA E
80/20
4.8664.866
208900BRIS G1
80/20
-2.56-2.56
942001AE2-212 C
Adder
1.8635294117647061.584
934501AD1-074 C
Adder
30.18352941176470625.656
3151031BRUNSWICKG2
80/20
8.3898.389
961671AG1-007 C
Adder
0.82941176470588230.705
934621AD1-088 C
80/20
9.29.2
946301AF1-294 C
Adder
3.3141176470588242.817
942461AE2-259 C
Adder
8.8929411764705887.559
316192AB2-158 C
80/20
3.5593.559
208901BRIS G2
80/20
-3.03-3.03
944641AF1-129 C
Adder
83.2882352941176570.795
316240AF1-291 C
Adder
1.78117647058823541.514
316036AC1-147 C
80/20
0.3280.328
316305AF2-043 C
80/20
0.3110.311
316321Z2-027 C
80/20
0.3250.325
934521AD1-076 C
Adder
10.9623529411764719.318
934511AD1-075 C
Adder
7.54588235294117656.414
316087AB2-174 C
80/20
1.0751.075
316263AC1-034 C
Adder
5.8505882352941184.973
937481AD2-202 C
80/20
0.3460.346
959311AF2-222 C
Adder
14.9976470588235312.748
942341AE2-247 C
80/20
1.3311.331
316246AF1-032 C
80/20
0.2540.254
316388AE2-253 GEN
80/20
1.7531.753
316320Y1-086 C
80/20
0.1960.196
966621AG1-532 C
80/20
1.2891.289
313506AB1-173 C OP
80/20
1.0281.028
935171AD1-152 C
80/20
1.2331.233
3152261N ANNA2
80/20
92.75992.759
3150651CHESTF6
Adder
15.16470588235294212.89
3150861SPRUNCD
80/20
0.140.14
957871AF2-081 C
80/20
8.9458.945
316274AC1-208 C
Adder
8.077647058823536.866
3151311EDGECMA
Adder
13.67647058823529511.625
316405AF2-144 C
80/20
0.30.3
940431AE2-027 C
Adder
10.6976470588235299.093
916191Z1-068 C
80/20
0.0390.039
941101AE2-104 C
80/20
3.0013.001
316185AD1-033 C
80/20
1.0971.097
944581AF1-123 C
80/20
40.90340.903
316294AC1-161 C
80/20
4.4154.415
316365AB2-100 C1
80/20
0.8850.885
316349AD2-085 C
80/20
3.0713.071
3151091ELIZAR2
80/20
2.8012.801
946281AF1-292 C
80/20
1.4231.423
926071AC1-086 C
Adder
19.07647058823529616.215
927021AC1-189 C
Adder
7.4435294117647066.327
964241AG1-285 C
Adder
11.3035294117647079.608
962561AG1-105 C
Adder
7.9117647058823526.725
961611AG1-000B C
Adder
13.19882352941176511.219
316072AD1-144 C
80/20
0.2460.246
316375AC2-012 C
80/20
1.2021.202
940541AE2-040 C
80/20
2.7232.723
940481AE2-033 C
80/20
15.30215.302
316181AB2-040 GEN
80/20
1.1581.158
3147043LAWRENC
80/20
0.2810.281
966001AG1-469 C
Adder
1.43764705882352951.222
3150731STONECA
Adder
5.4352941176470594.62
935161AD1-151 C
Adder
13.03882352941176511.083
316083AB2-161 C
80/20
0.4890.489
958161AF2-110 C
80/20
1.2251.225
938531AE1-072 C
80/20
15.7315.73
933981AD1-022 C
Adder
7.84941176470588256.672
3151021BRUNSWICKG1
80/20
8.3898.389
957481AF2-042 C
80/20
52.44752.447
3151801S ANNAS2
80/20
1.2181.218
939191AE1-149 C
80/20
9.4869.486
3150981CHESPKA
80/20
0.3880.388
3151041BRUNSWICKG3
80/20
8.3898.389
316313AB2-026 C
80/20
0.3850.385
964791AG1-342 C
Adder
3.14588235294117662.674
3151751LOISA D
80/20
2.3872.387
3151731LOISA B
80/20
2.3872.387
316316AC1-027 C
80/20
0.2820.282
316315AB2-025 C
80/20
0.3860.386
316023AB2-100 C2
80/20
0.8850.885
3138533PONTONDP
Adder
0.59764705882352940.508
3151721LOISA A
80/20
2.3742.374
316017AA1-139 ULT1
80/20
0.9650.965
313526AB2-022 C
80/20
0.3360.336
940641AE2-051 C
80/20
17.817.8
3152431Z1-086 GT3
80/20
10.7510.75
934611AD1-087 C
80/20
1.1911.191
316336AC2-165 C
80/20
9.7879.787
943461AF1-017 C
80/20
1.2041.204
316311AC2-079 C
80/20
5.125.12
3156056W1-029WIND
80/20
0.6930.693
316233AE1-074 C
80/20
2.4792.479
3152421Z1-086 GT2
80/20
10.7510.75
3152441Z1-086 ST
80/20
18.71718.717
3152411Z1-086 GT1
80/20
10.75310.753
316381AD1-082 C
80/20
1.1161.116
3150991CHESPKB
80/20
0.6430.643
939411AE1-173 C
80/20
90.4790.47
3137643SOCKMAN
Adder
0.64823529411764710.551
3151741LOISA C
80/20
2.3872.387
944631AF1-128 C
Adder
28.33882352941176624.088
3150921YORKTN3
Adder
92.4352941176470578.57
3150851SPRUNCC
80/20
0.140.14
316018AA1-139 ULT2
80/20
0.9650.965
933291AC2-141 C
80/20
27.11427.114
3152251N ANNA1
80/20
92.7292.72
316303AF2-085
80/20
4.3034.303
SIGELTFEXP_SIGE->PJM
CLTF
0.2110.211
NYPJM->LTFIMP_NY
CLTF
2.4542.454
LGEELTFEXP_LGEE->PJM
CLTF
1.0841.084
WECLTFEXP_WEC->PJM
CLTF
0.5370.537
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.18225.182
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.8619.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.3753.375
LAGNLTFEXP_LAGN->PJM
CLTF
6.9186.918
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.8954.895
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.42786.427
CPLELTFEXP_CPLE->PJM
CLTF
10.2710.27
TVALTFEXP_TVA->PJM
CLTF
5.5015.501

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.93 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3669.13
MW Contribution:2.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
70.4105882352941159.849
941591AE2-156 C
80/20
20.20920.209
3151101ELIZAR3
80/20
3.6473.647
944591AF1-124 C
80/20
51.4651.46
944601AF1-125 C
80/20
50.48850.488
938771AE1-103 C
Adder
3.22705882352941182.743
960081AF2-299 C
Adder
1.95294117647058821.66
944011AF1-069 C
80/20
13.80413.804
963041AG1-153 C
Adder
5.8858823529411765.003
936261AD2-033 C
Adder
12.57294117647058810.687
961791AG1-021 C
Adder
1.71764705882352931.46
966881AG1-559 C
Adder
2.45176470588235332.084
3150801HOPHCF4
80/20
4.1494.149
3150831SPRUNCA
80/20
10.42510.425
3150841SPRUNCB
80/20
10.42510.425
3151081ELIZAR1
80/20
3.6013.601
961941AG1-037 C
Adder
0.53764705882352950.457
941031AE2-094 C
80/20
42.24742.247
934331AD1-057 C
Adder
3.5635294117647063.029
934321AD1-056 C
Adder
6.3870588235294125.429
966871AG1-558 C
Adder
2.56235294117647072.178
958211AF2-115 C
Adder
2.14705882352941171.825
964211AG1-282 C
Adder
2.07882352941176451.767
962861AG1-135 C
Adder
6.3647058823529425.41
943741AF1-042 C
Adder
3.06352941176470632.604
942001AE2-212 C
80/20
2.4472.447
934501AD1-074 C
Adder
36.4552941176470630.987
961671AG1-007 C
Adder
0.95176470588235310.809
934621AD1-088 C
Adder
9.6105882352941188.169
946301AF1-294 C
Adder
3.5305882352941183.001
942461AE2-259 C
Adder
9.4035294117647077.993
3150781HOPHCF2
80/20
2.7332.733
3150761HOPPOLC
80/20
1.7191.719
944641AF1-129 C
80/20
115.84115.84
316240AF1-291 C
80/20
2.4442.444
934521AD1-076 C
Adder
13.2411.254
934511AD1-075 C
Adder
9.1141176470588237.747
316263AC1-034 C
Adder
6.6529411764705895.655
959311AF2-222 C
Adder
16.0552941176470613.647
3150771HOPHCF1
80/20
2.7332.733
942341AE2-247 C
Adder
1.67764705882352931.426
966621AG1-532 C
Adder
1.46470588235294131.245
3152261N ANNA2
80/20
56.72156.721
934861AD1-115 C
Adder
-3.06-2.601
936591AD2-074 C
Adder
5.8552941176470594.977
3150651CHESTF6
80/20
21.09121.091
3150861SPRUNCD
80/20
0.1870.187
957871AF2-081 C
Adder
11.2117647058823529.53
316274AC1-208 C
Adder
9.2835294117647067.891
3151311EDGECMA
Adder
15.55647058823529613.223
316169AC1-164 GEN
Adder
43.66588235294117537.116
316349AD2-085 C
Adder
3.87058823529411773.29
3151091ELIZAR2
80/20
3.5383.538
946281AF1-292 C
Adder
1.61647058823529431.374
926071AC1-086 C
Adder
21.9611764705882418.667
927021AC1-189 C
Adder
8.6023529411764727.312
964241AG1-285 C
Adder
12.1610.336
962561AG1-105 C
Adder
8.5058823529411767.23
939261AE1-157 C
Adder
14.10235294117647211.987
963611AG1-210 C
Adder
0.68235294117647060.58
961611AG1-000B C
Adder
17.92352941176470415.235
316375AC2-012 C
80/20
1.521.52
940541AE2-040 C
Adder
3.10117647058823562.636
940481AE2-033 C
Adder
17.43882352941176714.823
927041AC1-191 C
Adder
10.2870588235294128.744
3150731STONECA
80/20
7.7657.765
935161AD1-151 C
Adder
18.16235294117647215.438
3142366NRTHEST
80/20
0.2040.204
958161AF2-110 C
Adder
1.53294117647058831.303
938531AE1-072 C
Adder
19.70000000000000316.745
933981AD1-022 C
Adder
9.4470588235294128.03
940431AE2-027 C
80/20
14.61614.616
941101AE2-104 C
Adder
3.75764705882352963.194
944581AF1-123 C
80/20
51.27751.277
316294AC1-161 C
80/20
5.5975.597
957481AF2-042 C
Adder
54.6470588235294146.45
958261AF2-120 C
Adder
6.5505882352941175.568
3143096IRON208
80/20
0.4940.494
939191AE1-149 C
80/20
12.15312.153
964791AG1-342 C
Adder
3.38000000000000032.873
957601AF2-054 C
Adder
2.26000000000000021.921
961951AG1-038 C
Adder
3.3858823529411772.878
3150791HOPHCF3
80/20
2.7332.733
3138533PONTONDP
Adder
0.63647058823529420.541
316254AC1-120 C
Adder
-6.376470588235295-5.42
316257AC1-043 C
Adder
-6.121176470588236-5.203
943471AF1-018 C
Adder
7.6152941176470596.473
3152331SURRY 2
80/20
27.86527.865
940641AE2-051 C
80/20
18.8818.88
316336AC2-165 C
Adder
10.1788235294117648.652
940551AE2-041 C
Adder
7.6152941176470596.473
943461AF1-017 C
Adder
1.51764705882352961.29
316311AC2-079 C
Adder
6.4458823529411775.479
316233AE1-074 C
80/20
2.8742.874
966661AG1-536 C
Adder
5.6341176470588234.789
3150991CHESPKB
80/20
0.8130.813
939411AE1-173 C
80/20
99.71499.714
3137643SOCKMAN
Adder
0.74235294117647070.631
944631AF1-128 C
Adder
44.0564705882352937.448
3150921YORKTN3
Adder
133.0105882352941113.059
3150851SPRUNCC
80/20
0.1870.187
933291AC2-141 C
80/20
34.37234.372
3152251N ANNA1
80/20
56.69756.697
316303AF2-085
80/20
4.4474.447
SIGELTFEXP_SIGE->PJM
CLTF
0.2560.256
NYPJM->LTFIMP_NY
CLTF
2.72.7
LGEELTFEXP_LGEE->PJM
CLTF
1.331.33
WECLTFEXP_WEC->PJM
CLTF
0.6540.654
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.72830.728
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.33523.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.0414.041
LAGNLTFEXP_LAGN->PJM
CLTF
8.0268.026
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.4135.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69496.694
CPLELTFEXP_CPLE->PJM
CLTF
11.35211.352
TVALTFEXP_TVA->PJM
CLTF
6.4156.415

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.88 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4408.08
MW Contribution:3.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943462AF1-017 E
Adder
2.06941176470588231.759
942341AE2-247 C
Adder
1.40235294117647061.192
958162AF2-110 E
Adder
2.0505882352941181.743
919153AA1-139 E2
Adder
3.8505882352941183.273
934502AD1-074 E
Adder
16.13411764705882613.714
934512AD1-075 E
Adder
4.0341176470588243.429
918512AA1-065 E OP
Adder
5.2011764705882364.421
924516AB2-100 E1
Adder
2.82.38
940642AE2-051 E
50/50
12.32512.325
966621AG1-532 C
Adder
1.34705882352941191.145
924022AB2-043 E O1
Adder
4.8811764705882354.149
3147223TWITTYS
Adder
0.89294117647058820.759
959312AF2-222 E
Adder
10.4764705882352948.905
3152261N ANNA2
50/50
93.22693.226
3150651CHESTF6
Adder
16.10470588235294213.689
946262AF1-291 E
Adder
1.261.071
934576AD1-082 E
Adder
4.1188235294117653.501
943612AF1-032 E
Adder
0.87058823529411770.74
3145506HICKORY
Adder
2.05411764705882361.746
944602AF1-125 E
Adder
97.0388235294117782.483
957871AF2-081 C
Adder
9.4164705882352948.004
933292AC2-141 E
Adder
12.19411764705882510.365
940492AE2-034 E
Adder
2.90235294117647062.467
934522AD1-076 E
Adder
5.8670588235294124.987
943172AE2-346 E
Adder
0.5717647058823530.486
918492AA1-063AE OP
Adder
3.87294117647058833.292
917332KELFORD E
Adder
1.54588235294117651.314
937482AD2-202 E
Adder
1.04941176470588250.892
961792AG1-021 E
Adder
1.4317647058823531.217
3150831SPRUNCA
Adder
8.2435294117647067.007
3150841SPRUNCB
Adder
8.2435294117647067.007
926662AC1-147 E
Adder
1.24470588235294131.058
916192Z1-068 E
Adder
1.77058823529411761.505
957492AF2-043 E
Adder
1.341.139
923852AB2-025 E
Adder
1.15058823529411770.978
939412AE1-173 E
50/50
62.82462.824
961942AG1-037 E
Adder
0.317647058823529450.27
961941AG1-037 C
Adder
0.476470588235294150.405
941031AE2-094 C
50/50
42.60742.607
941032AE2-094 E
50/50
19.08319.083
936262AD2-033 E
Adder
8.1458823529411776.924
923862AB2-026 E
Adder
1.31.105
958211AF2-115 C
Adder
2.1011764705882351.786
3151791S ANNAG2
50/50
2.42.4
3151771S ANNAG1
50/50
2.42.4
3151781S ANNAS1
50/50
1.2331.233
3151761LOISA E
50/50
4.9314.931
208900BRIS G1
50/50
-2.742-2.742
961611AG1-000B C
Adder
13.98823529411764911.89
940541AE2-040 C
Adder
2.84470588235294162.418
940481AE2-033 C
Adder
15.98588235294117513.588
940482AE2-033 E
Adder
10.777647058823539.161
923263AB1-132 E OP
Adder
5.80941176470588254.938
924312AB2-078 E O1
Adder
1.25764705882352931.069
925612AC1-036 E
Adder
0.80588235294117660.685
966001AG1-469 C
Adder
1.46235294117647091.243
935161AD1-151 C
Adder
13.84941176470588311.772
932046AC2-012 E
Adder
12.31647058823529410.469
958161AF2-110 C
Adder
1.28941176470588251.096
938531AE1-072 C
Adder
16.55647058823529614.073
3145393UNCAMP
Adder
5.7482352941176484.886
933981AD1-022 C
Adder
8.247.004
900672V4-068 E
Adder
0.33764705882352940.287
924302AB2-077 E O1
Adder
1.25764705882352931.069
939192AE1-149 E
Adder
6.6670588235294125.667
939312AE1-162 E
Adder
1.29647058823529431.102
942001AE2-212 C
Adder
1.96941176470588241.674
934065AD1-033 E
Adder
4.7282352941176474.019
937226AE2-253 E
Adder
5.5047058823529414.679
934501AD1-074 C
Adder
31.6952941176470626.941
924517AB2-100 E2
Adder
2.82.38
3151031BRUNSWICKG2
50/50
8.78.7
957482AF2-042 E
Adder
36.31529411764705630.868
934621AD1-088 C
Adder
9.5599999999999998.126
935172AD1-152 E
Adder
5.2941176470588234.5
958502AF2-144 E
Adder
1.2764705882352941.085
946301AF1-294 C
Adder
3.45529411764705862.937
942461AE2-259 C
Adder
9.2705882352941187.88
316192AB2-158 C
50/50
3.5873.587
208901BRIS G2
50/50
-3.245-3.245
940431AE2-027 C
Adder
11.3411764705882369.64
942002AE2-212 E
Adder
1.31294117647058851.116
941101AE2-104 C
Adder
3.1588235294117652.685
944581AF1-123 C
Adder
43.0529411764705936.595
316141AB2-099 E
Adder
0.237647058823529430.202
316088AB2-174 E
Adder
6.242352941176475.306
923994AB2-040_E
Adder
5.8811764705882354.999
3151021BRUNSWICKG1
50/50
8.78.7
957481AF2-042 C
Adder
54.4729411764705946.302
924322AB2-079 E O1
Adder
1.25764705882352931.069
946302AF1-294 E
Adder
2.9258823529411772.487
3151801S ANNAS2
50/50
1.2331.233
939191AE1-149 C
Adder
10.0011764705882348.501
3143316POE
Adder
1.30941176470588231.113
901082W1-029 E
Adder
30.02588235294117425.522
3151041BRUNSWICKG3
50/50
8.78.7
942462AE2-259 E
Adder
6.1800000000000015.253
3151731LOISA B
50/50
2.4192.419
935112AD1-144 E
Adder
0.8717647058823530.741
316349AD2-085 C
Adder
3.23411764705882382.749
944582AF1-123 E
Adder
98.5858823529411883.798
944592AF1-124 E
Adder
98.9435294117647184.102
923832AB2-022 E
Adder
1.1682352941176470.993
938772AE1-103 E
Adder
3.8211764705882363.248
916042Z1-036 E
Adder
26.91882352941176422.881
960082AF2-299 E
Adder
1.19764705882352951.018
946281AF1-292 C
Adder
1.48705882352941181.264
926071AC1-086 C
Adder
19.96117647058823516.967
963042AG1-153 E
50/50
8.8728.872
964241AG1-285 C
Adder
11.78352941176470610.016
958212AF2-115 E
Adder
1.78941176470588231.521
925022AB2-158 E
50/50
9.5359.535
946282AF1-292 E
Adder
0.99176470588235290.843
944012AF1-069 E
50/50
5.4085.408
3138533PONTONDP
Adder
0.62235294117647070.529
927226AC1-216 E
Adder
6.6694117647058825.669
936666AD2-085 E
Adder
5.2764705882352954.485
941591AE2-156 C
Adder
16.83647058823529414.311
944591AF1-124 C
Adder
43.2058823529411836.725
944601AF1-125 C
Adder
42.3894117647058836.031
938771AE1-103 C
Adder
2.7670588235294122.352
3145413WATKINS
Adder
0.65411764705882360.556
960081AF2-299 C
Adder
1.7964705882352941.527
926072AC1-086 E
Adder
9.0847058823529427.722
944011AF1-069 C
50/50
13.92113.921
963041AG1-153 C
50/50
5.9155.915
3151051BRUNSWICKS1
50/50
18.07518.075
936261AD2-033 C
Adder
12.2210.387
961791AG1-021 C
Adder
1.68117647058823551.429
316084AB2-161 E
Adder
5.1694117647058834.394
3145946PLYMOUTH TP
Adder
0.30352941176470590.258
933982AD1-022 E
Adder
4.4858823529411773.813
940641AE2-051 C
50/50
18.48718.487
3152431Z1-086 GT3
50/50
11.14611.146
934622AD1-088 E
Adder
4.6035294117647063.913
934612AD1-087 E
Adder
3.5835294117647063.046
316336AC2-165 C
Adder
10.1788235294117648.652
935162AD1-151 E
Adder
4.4752941176470593.804
943461AF1-017 C
Adder
1.26823529411764711.078
932596AC2-079 E
Adder
8.7952941176470587.476
316311AC2-079 C
Adder
5.3905882352941184.582
938532AE1-072 E
Adder
8.6305882352941187.336
3146326AYDLETT TAP
Adder
1.27764705882352961.086
917122Z2-027 E
Adder
1.26588235294117671.076
920692AA2-178 E
Adder
3.86941176470588263.289
316233AE1-074 C
50/50
2.5912.591
966622AG1-532 E
Adder
0.89882352941176480.764
3152421Z1-086 GT2
50/50
11.14611.146
3152441Z1-086 ST
50/50
19.40819.408
3152411Z1-086 GT1
50/50
11.14911.149
3147133PAMPLIN
Adder
0.92823529411764720.789
966002AG1-469 E
Adder
0.73058823529411760.621
940432AE2-027 E
Adder
7.5611764705882356.427
934012AD1-025 E
Adder
8.6341176470588247.339
913392Y1-086 E
Adder
2.0705882352941181.76
939411AE1-173 C
50/50
94.23794.237
3137643SOCKMAN
Adder
0.67882352941176470.577
933502AC2-165 E
Adder
7.6611764705882356.512
3151741LOISA C
50/50
2.4192.419
3145256KINGFORK
Adder
0.93882352941176480.798
925522AC1-027 E
Adder
1.14588235294117660.974
941102AE2-104 E
Adder
5.0223529411764714.269
957872AF2-081 E
Adder
4.0352941176470593.43
933291AC2-141 C
Adder
28.56588235294117724.281
926755AC1-161 E
Adder
12.19411764705882510.365
938552AE1-074 E
50/50
1.3051.305
924162AB2-060 E OP
Adder
4.0294117647058823.425
964242AG1-285 E
Adder
7.8564705882352946.678
938562AE1-075 E
Adder
1.1082352941176470.942
3152251N ANNA1
50/50
93.18793.187
924814AB2-134 E
Adder
10.9235294117647069.285
944641AF1-129 C
Adder
88.4505882352941375.183
316240AF1-291 C
Adder
1.88941176470588261.606
942342AE2-247 E
Adder
1.93529411764705881.645
919152AA1-139 E1
Adder
3.8505882352941183.273
934521AD1-076 C
Adder
11.5105882352941199.784
934511AD1-075 C
Adder
7.9235294117647066.735
920042AA2-088 E OP
Adder
10.0447058823529418.538
3145723EMPORIA
Adder
0.414117647058823530.352
923573AB1-173 E OP
Adder
3.1364705882352942.666
919692AA2-053 E OP
Adder
4.00705882352941253.406
925785AC1-054 E
Adder
3.24941176470588242.762
959311AF2-222 C
Adder
15.63529411764705813.29
316303AF2-085
50/50
4.464.46
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5685.568
SIGELTFEXP_SIGE->PJM
CLTF
0.2320.232
NYPJM->LTFIMP_NY
CLTF
2.6122.612
LGEELTFEXP_LGEE->PJM
CLTF
1.1951.195
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.02528.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.37921.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.6863.686
LAGNLTFEXP_LAGN->PJM
CLTF
7.3867.386
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.1255.125
CBM South 2LTFEXP_CBM-S2->PJM
CBM
90.8190.81
CPLELTFEXP_CPLE->PJM
CLTF
10.7510.75
TVALTFEXP_TVA->PJM
CLTF
5.8785.878
O66PJM->LTFIMP_O-066
CMTX_NF
35.46935.469

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.7 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4342.98
MW Contribution:3.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944011AF1-069 C
80/20
38.91238.912
963041AG1-153 C
80/20
17.24617.246
3151051BRUNSWICKS1
80/20
52.70552.705
936261AD2-033 C
80/20
19.83719.837
961791AG1-021 C
80/20
2.642.64
316248AF1-058 C
80/20
0.6420.642
936171AD2-023 C
80/20
7.4677.467
941801AE2-185 C
80/20
4.7984.798
941031AE2-094 C
80/20
119.094119.094
3151531CLOVER1
80/20
32.84832.848
3151541CLOVER2
80/20
32.5432.54
958211AF2-115 C
80/20
3.33.3
24684605SMG4
80/20
3.2353.235
964211AG1-282 C
Adder
-1.7882352941176471-1.52
942001AE2-212 C
Adder
-2.1176470588235294-1.8
3151031BRUNSWICKG2
80/20
25.36925.369
316359AB2-059 C OP
80/20
1.1351.135
934621AD1-088 C
80/20
24.38424.384
946301AF1-294 C
80/20
5.4265.426
942461AE2-259 C
80/20
14.02314.023
316283AC2-100 C
80/20
2.3262.326
316197AC1-042 C
80/20
0.3460.346
3151601KERR 3
80/20
1.8191.819
3151581KERR 1
80/20
0.650.65
935171AD1-152 C
80/20
3.2243.224
936161AD2-022 C
80/20
12.80112.801
270197AC1-083 C
80/20
0.9970.997
3151311EDGECMA
80/20
10.35810.358
3152661PLYWOOD A
80/20
2.3542.354
964241AG1-285 C
80/20
19.39519.395
316034AC1-036 C
80/20
0.3540.354
962561AG1-105 C
80/20
15.92115.921
316118AC1-105 C
80/20
1.7691.769
3144293JTRSVLE
80/20
0.6050.605
316217AC1-145 C
80/20
0.4120.412
942671AE2-283 C
80/20
3.7323.732
943811AF1-049 C
80/20
9.4269.426
938741AE1-100 C
80/20
0.7290.729
941671AE2-166 C
80/20
5.7085.708
24728405LEESVG
80/20
0.9740.974
938531AE1-072 C
Adder
-16.896470588235296-14.362
316049AB1-081 C OP
80/20
0.9630.963
316238AB2-078 C O1
80/20
0.5160.516
316322AB2-045 C
80/20
0.2670.267
944641AF1-129 C
Adder
-95.19529411764705-80.916
316240AF1-291 C
Adder
-2.031764705882353-1.727
316263AC1-034 C
80/20
4.5164.516
937481AD2-202 C
80/20
0.9380.938
3151591KERR 2
80/20
1.8191.819
959311AF2-222 C
80/20
25.13225.132
316205AC1-080 C
80/20
0.5050.505
316123AC1-075 C
80/20
1.5121.512
942751AE2-291 C
80/20
13.51213.512
3151561HALLBR1
80/20
1.2391.239
24684305SMG1
80/20
1.1751.175
3151021BRUNSWICKG1
80/20
25.36925.369
957481AF2-042 C
80/20
148.174148.174
316003AC1-222 C
80/20
1.9581.958
24684405SMG2
80/20
3.2353.235
3151041BRUNSWICKG3
80/20
25.36925.369
316239AB2-077 C O1
80/20
0.5160.516
964791AG1-342 C
80/20
6.5026.502
940081AE1-250 C
80/20
13.65313.653
957601AF2-054 C
Adder
-1.8941176470588237-1.61
316129AC1-054 C
80/20
1.1861.186
3151631KERR 6
80/20
1.8191.819
316131AB2-060 C
80/20
2.3152.315
3138533PONTONDP
80/20
0.9780.978
24684505SMG3
80/20
1.9881.988
24684705SMG5
80/20
1.2291.229
941431AE2-140 C
80/20
14.14314.143
940641AE2-051 C
Adder
-22.240000000000002-18.904
3152431Z1-086 GT3
80/20
32.07932.079
934611AD1-087 C
80/20
3.2323.232
3151611KERR 4
80/20
1.8191.819
3151621KERR 5
80/20
1.8191.819
316237AB2-079 C O1
80/20
0.5160.516
316222AC1-221 C
80/20
2.9052.905
3152421Z1-086 GT2
80/20
32.07932.079
3152441Z1-086 ST
80/20
55.85555.855
3152411Z1-086 GT1
80/20
32.08832.088
940601AE2-047 C
80/20
4.254.25
933291AC2-141 C
Adder
-33.98823529411765-28.89
3151641KERR 7
80/20
1.8191.819
313527AB2-043 C
80/20
0.8060.806
SIGELTFEXP_SIGE->PJM
CLTF
0.550.55
NYPJM->LTFIMP_NY
CLTF
2.1882.188
LGEELTFEXP_LGEE->PJM
CLTF
2.8852.885
WECLTFEXP_WEC->PJM
CLTF
1.5251.525
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.77474.774
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.81246.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.7578.757
LAGNLTFEXP_LAGN->PJM
CLTF
15.4915.49
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.6199.619
CBM South 2LTFEXP_CBM-S2->PJM
CBM
177.277177.277
CPLELTFEXP_CPLE->PJM
CLTF
20.16220.162
TVALTFEXP_TVA->PJM
CLTF
12.22612.226

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.59 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4175.62
MW Contribution:3.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151531CLOVER1
80/20
32.84832.848
3151541CLOVER2
80/20
32.5432.54
958211AF2-115 C
80/20
3.33.3
24684605SMG4
80/20
3.2353.235
942001AE2-212 C
Adder
-2.1176470588235294-1.8
3151031BRUNSWICKG2
80/20
25.36925.369
316359AB2-059 C OP
80/20
1.1351.135
934621AD1-088 C
80/20
24.38424.384
946301AF1-294 C
80/20
5.4265.426
942461AE2-259 C
80/20
14.02314.023
316283AC2-100 C
80/20
2.3262.326
316197AC1-042 C
80/20
0.3460.346
3151601KERR 3
80/20
1.8191.819
3151581KERR 1
80/20
0.650.65
935171AD1-152 C
80/20
3.2243.224
936161AD2-022 C
80/20
12.80112.801
270197AC1-083 C
80/20
0.9970.997
3151311EDGECMA
80/20
10.35810.358
3152661PLYWOOD A
80/20
2.3542.354
964241AG1-285 C
80/20
19.39519.395
316034AC1-036 C
80/20
0.3540.354
962561AG1-105 C
80/20
15.92115.921
316118AC1-105 C
80/20
1.7691.769
3144293JTRSVLE
80/20
0.6050.605
316217AC1-145 C
80/20
0.4120.412
942671AE2-283 C
80/20
3.7323.732
964211AG1-282 C
Adder
-1.7882352941176471-1.52
943811AF1-049 C
80/20
9.4269.426
938741AE1-100 C
80/20
0.7290.729
941671AE2-166 C
80/20
5.7085.708
24728405LEESVG
80/20
0.9740.974
938531AE1-072 C
Adder
-16.896470588235296-14.362
316049AB1-081 C OP
80/20
0.9630.963
316238AB2-078 C O1
80/20
0.5160.516
316322AB2-045 C
80/20
0.2670.267
944641AF1-129 C
Adder
-95.19529411764705-80.916
316240AF1-291 C
Adder
-2.031764705882353-1.727
316263AC1-034 C
80/20
4.5164.516
937481AD2-202 C
80/20
0.9380.938
3151591KERR 2
80/20
1.8191.819
959311AF2-222 C
80/20
25.13225.132
316205AC1-080 C
80/20
0.5050.505
316123AC1-075 C
80/20
1.5121.512
3151021BRUNSWICKG1
80/20
25.36925.369
957481AF2-042 C
80/20
148.174148.174
316003AC1-222 C
80/20
1.9581.958
24684405SMG2
80/20
3.2353.235
3151041BRUNSWICKG3
80/20
25.36925.369
316239AB2-077 C O1
80/20
0.5160.516
964791AG1-342 C
80/20
6.5026.502
940081AE1-250 C
80/20
13.65313.653
957601AF2-054 C
Adder
-1.8941176470588237-1.61
316129AC1-054 C
80/20
1.1861.186
3151631KERR 6
80/20
1.8191.819
316131AB2-060 C
80/20
2.3152.315
3138533PONTONDP
80/20
0.9780.978
24684505SMG3
80/20
1.9881.988
24684705SMG5
80/20
1.2291.229
941431AE2-140 C
80/20
14.14314.143
963041AG1-153 C
80/20
17.24617.246
3151051BRUNSWICKS1
80/20
52.70552.705
936261AD2-033 C
80/20
19.83719.837
961791AG1-021 C
80/20
2.642.64
316248AF1-058 C
80/20
0.6420.642
936171AD2-023 C
80/20
7.4677.467
941801AE2-185 C
80/20
4.7984.798
940641AE2-051 C
Adder
-22.240000000000002-18.904
3152431Z1-086 GT3
80/20
32.07932.079
934611AD1-087 C
80/20
3.2323.232
3151611KERR 4
80/20
1.8191.819
3151621KERR 5
80/20
1.8191.819
316237AB2-079 C O1
80/20
0.5160.516
316222AC1-221 C
80/20
2.9052.905
3152421Z1-086 GT2
80/20
32.07932.079
3152441Z1-086 ST
80/20
55.85555.855
3152411Z1-086 GT1
80/20
32.08832.088
940601AE2-047 C
80/20
4.254.25
933291AC2-141 C
Adder
-33.98823529411765-28.89
3151641KERR 7
80/20
1.8191.819
313527AB2-043 C
80/20
0.8060.806
942751AE2-291 C
80/20
13.51213.512
3151561HALLBR1
80/20
1.2391.239
24684305SMG1
80/20
1.1751.175
SIGELTFEXP_SIGE->PJM
CLTF
0.550.55
NYPJM->LTFIMP_NY
CLTF
2.1882.188
LGEELTFEXP_LGEE->PJM
CLTF
2.8852.885
WECLTFEXP_WEC->PJM
CLTF
1.5251.525
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.77474.774
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.81246.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.7578.757
LAGNLTFEXP_LAGN->PJM
CLTF
15.4915.49
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.6199.619
CBM South 2LTFEXP_CBM-S2->PJM
CBM
177.277177.277
CPLELTFEXP_CPLE->PJM
CLTF
20.16220.162
TVALTFEXP_TVA->PJM
CLTF
12.22612.226

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.93 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3894.33
MW Contribution:1.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
941591AE2-156 C
80/20
15.615.6
3151101ELIZAR3
80/20
2.8172.817
944591AF1-124 C
80/20
40.05140.051
944601AF1-125 C
80/20
39.29539.295
938771AE1-103 C
80/20
2.5672.567
960081AF2-299 C
80/20
1.6731.673
944011AF1-069 C
80/20
13.03613.036
963041AG1-153 C
80/20
5.5365.536
3151051BRUNSWICKS1
80/20
16.91816.918
936261AD2-033 C
Adder
11.4505882352941189.733
961791AG1-021 C
Adder
1.57882352941176471.342
316045AC1-158 C2
80/20
19.41819.418
316170AC1-121 C
80/20
2.7242.724
3150831SPRUNCA
Adder
7.6235294117647066.48
3150841SPRUNCB
Adder
7.6235294117647066.48
3151081ELIZAR1
80/20
2.7822.782
961941AG1-037 C
Adder
0.44235294117647060.376
941031AE2-094 C
80/20
39.89839.898
934331AD1-057 C
Adder
3.0305882352941182.576
934321AD1-056 C
Adder
5.4329411764705894.618
3151531CLOVER1
80/20
11.76811.768
3151541CLOVER2
80/20
11.65811.658
316258AE1-075 C
80/20
0.3460.346
958211AF2-115 C
Adder
1.97411764705882351.678
3151791S ANNAG2
80/20
2.6512.651
3151771S ANNAG1
80/20
2.6512.651
3151781S ANNAS1
80/20
1.3621.362
3151761LOISA E
80/20
5.5225.522
208900BRIS G1
80/20
-2.628-2.628
316349AD2-085 C
80/20
2.9972.997
3151091ELIZAR2
80/20
2.7332.733
946281AF1-292 C
80/20
1.3851.385
926071AC1-086 C
Adder
18.5623529411764715.778
927021AC1-189 C
Adder
7.2364705882352946.151
964241AG1-285 C
Adder
11.0294117647058829.375
962561AG1-105 C
Adder
7.70470588235294156.549
316044AC1-158 C1
80/20
19.41819.418
942001AE2-212 C
Adder
1.82117647058823541.548
934501AD1-074 C
Adder
29.40470588235294324.994
3151031BRUNSWICKG2
80/20
8.1438.143
961671AG1-007 C
Adder
0.80588235294117660.685
934621AD1-088 C
80/20
8.9588.958
946301AF1-294 C
Adder
3.2458823529411762.759
942461AE2-259 C
Adder
8.7329411764705887.423
316192AB2-158 C
80/20
3.6253.625
208901BRIS G2
80/20
-3.11-3.11
944641AF1-129 C
Adder
81.5517647058823669.319
316240AF1-291 C
Adder
1.7435294117647061.482
316036AC1-147 C
80/20
0.320.32
316305AF2-043 C
80/20
0.3030.303
316321Z2-027 C
80/20
0.3170.317
934521AD1-076 C
Adder
10.6788235294117659.077
934511AD1-075 C
Adder
7.3517647058823536.249
316087AB2-174 C
80/20
1.0461.046
316263AC1-034 C
Adder
5.6858823529411774.833
937481AD2-202 C
80/20
0.3360.336
959311AF2-222 C
Adder
14.6623529411764712.463
942341AE2-247 C
80/20
1.2991.299
316246AF1-032 C
80/20
0.2480.248
316388AE2-253 GEN
80/20
1.711.71
316320Y1-086 C
80/20
0.1920.192
966621AG1-532 C
80/20
1.2551.255
935171AD1-152 C
80/20
1.1991.199
3152261N ANNA2
80/20
89.07389.073
934861AD1-115 C
Adder
2.8482352941176472.421
3150651CHESTF6
Adder
14.84823529411764812.621
3150861SPRUNCD
80/20
0.1370.137
957871AF2-081 C
80/20
8.7288.728
316274AC1-208 C
Adder
7.857647058823536.679
3151311EDGECMA
Adder
13.28823529411764811.295
316405AF2-144 C
80/20
0.2940.294
940431AE2-027 C
Adder
10.4682352941176488.898
916191Z1-068 C
80/20
0.0380.038
941101AE2-104 C
80/20
2.9282.928
316185AD1-033 C
80/20
1.071.07
944581AF1-123 C
80/20
39.90939.909
316294AC1-161 C
80/20
4.314.31
316365AB2-100 C1
80/20
0.8620.862
3151021BRUNSWICKG1
80/20
8.1438.143
957481AF2-042 C
80/20
51.00351.003
3151801S ANNAS2
80/20
1.3621.362
961611AG1-000B C
Adder
12.91058823529411910.974
316375AC2-012 C
80/20
1.1731.173
940541AE2-040 C
80/20
2.652.65
940481AE2-033 C
80/20
14.89114.891
3147043LAWRENC
80/20
0.2730.273
966001AG1-469 C
80/20
1.9591.959
3150731STONECA
Adder
5.3258823529411774.527
935161AD1-151 C
Adder
12.7647058823529410.85
316083AB2-161 C
80/20
0.4780.478
958161AF2-110 C
80/20
1.1951.195
938531AE1-072 C
80/20
15.34615.346
933981AD1-022 C
Adder
7.6458823529411766.499
316017AA1-139 ULT1
80/20
0.9420.942
313526AB2-022 C
80/20
0.3280.328
940641AE2-051 C
80/20
17.2917.29
3152431Z1-086 GT3
80/20
10.43410.434
934611AD1-087 C
80/20
1.1591.159
316336AC2-165 C
80/20
9.6099.609
939191AE1-149 C
80/20
9.2629.262
3150981CHESPKA
80/20
0.3780.378
3151041BRUNSWICKG3
80/20
8.1438.143
316313AB2-026 C
80/20
0.3770.377
964791AG1-342 C
Adder
3.06352941176470632.604
3151751LOISA D
80/20
2.7082.708
3151731LOISA B
80/20
2.7082.708
316164AC1-076_C
80/20
1.1141.114
316316AC1-027 C
80/20
0.2750.275
316315AB2-025 C
80/20
0.3750.375
316023AB2-100 C2
80/20
0.8620.862
3138533PONTONDP
Adder
0.58470588235294120.497
3151721LOISA A
80/20
2.6942.694
316254AC1-120 C
80/20
7.9327.932
316257AC1-043 C
Adder
5.697647058823534.843
943461AF1-017 C
80/20
1.1751.175
316311AC2-079 C
80/20
4.9964.996
3156056W1-029WIND
80/20
0.6760.676
316233AE1-074 C
80/20
2.4172.417
3152421Z1-086 GT2
80/20
10.43410.434
3152441Z1-086 ST
80/20
18.16818.168
3152411Z1-086 GT1
80/20
10.43710.437
316381AD1-082 C
80/20
1.0891.089
3150991CHESPKB
80/20
0.6270.627
939411AE1-173 C
80/20
87.96287.962
3137643SOCKMAN
Adder
0.6317647058823530.537
3151741LOISA C
80/20
2.7082.708
3150921YORKTN3
Adder
90.5694117647058876.984
3150851SPRUNCC
80/20
0.1370.137
316018AA1-139 ULT2
80/20
0.9420.942
933291AC2-141 C
80/20
26.46526.465
3152251N ANNA1
80/20
89.03589.035
316303AF2-085
80/20
4.1844.184
SIGELTFEXP_SIGE->PJM
CLTF
0.1910.191
NYPJM->LTFIMP_NY
CLTF
2.5322.532
LGEELTFEXP_LGEE->PJM
CLTF
0.9710.971
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.96121.961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.49718.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.0623.062
LAGNLTFEXP_LAGN->PJM
CLTF
6.5316.531
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.744.74
CBM South 2LTFEXP_CBM-S2->PJM
CBM
83.40383.403
CPLELTFEXP_CPLE->PJM
CLTF
9.9459.945
TVALTFEXP_TVA->PJM
CLTF
5.1955.195

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.78 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3857.57
MW Contribution:2.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
68.9811764705882458.634
941591AE2-156 C
80/20
19.79319.793
3151101ELIZAR3
80/20
3.5723.572
944591AF1-124 C
80/20
50.39950.399
944601AF1-125 C
80/20
49.44749.447
938771AE1-103 C
Adder
3.162.686
960081AF2-299 C
Adder
1.91411764705882351.627
944011AF1-069 C
80/20
13.51813.518
963041AG1-153 C
Adder
5.7647058823529424.9
936261AD2-033 C
Adder
12.4023529411764710.542
961791AG1-021 C
Adder
1.70000000000000021.445
316045AC1-158 C2
80/20
14.96214.962
966881AG1-559 C
Adder
2.3964705882352942.037
3150801HOPHCF4
80/20
4.0644.064
3150831SPRUNCA
80/20
10.21910.219
3150841SPRUNCB
80/20
10.21910.219
3151081ELIZAR1
80/20
3.5273.527
961941AG1-037 C
Adder
0.52705882352941180.448
941031AE2-094 C
80/20
41.37341.373
934331AD1-057 C
Adder
3.4882352941176472.965
934321AD1-056 C
Adder
6.2529411764705895.315
966871AG1-558 C
Adder
2.50941176470588222.133
958211AF2-115 C
Adder
2.12470588235294141.806
964211AG1-282 C
Adder
2.0317647058823531.727
316169AC1-164 GEN
Adder
42.77176470588235436.356
316349AD2-085 C
Adder
3.79058823529411763.222
3151091ELIZAR2
80/20
3.4653.465
962861AG1-135 C
Adder
6.222352941176475.289
943741AF1-042 C
Adder
2.9964705882352942.547
942001AE2-212 C
80/20
2.3972.397
934501AD1-074 C
Adder
35.6976470588235330.343
961671AG1-007 C
Adder
0.9317647058823530.792
934621AD1-088 C
Adder
9.4482352941176488.031
946301AF1-294 C
Adder
3.4941176470588242.97
942461AE2-259 C
Adder
9.347.939
316192AB2-158 C
80/20
2.1182.118
3150781HOPHCF2
80/20
2.6772.677
3150761HOPPOLC
80/20
1.6841.684
944641AF1-129 C
80/20
113.49113.49
316240AF1-291 C
80/20
2.3942.394
934521AD1-076 C
Adder
12.96470588235294111.02
934511AD1-075 C
Adder
8.9247058823529427.586
316263AC1-034 C
Adder
6.5105882352941185.534
959311AF2-222 C
Adder
15.85294117647058913.475
3150771HOPHCF1
80/20
2.6772.677
942341AE2-247 C
Adder
1.64235294117647061.396
966621AG1-532 C
Adder
1.43529411764705881.22
3152261N ANNA2
80/20
55.34655.346
936591AD2-074 C
Adder
5.7258823529411764.867
3150651CHESTF6
80/20
20.66420.664
3150861SPRUNCD
80/20
0.1830.183
957871AF2-081 C
Adder
10.989.333
316274AC1-208 C
Adder
9.0917647058823537.728
3151311EDGECMA
Adder
15.22352941176470512.94
940431AE2-027 C
80/20
14.31814.318
941101AE2-104 C
Adder
3.683.128
944581AF1-123 C
80/20
50.22150.221
316294AC1-161 C
80/20
5.4825.482
957481AF2-042 C
Adder
53.64117647058823545.595
946281AF1-292 C
Adder
1.58470588235294121.347
926071AC1-086 C
Adder
21.50823529411764718.282
927021AC1-189 C
Adder
8.4188235294117647.156
964241AG1-285 C
Adder
11.97764705882352810.181
962561AG1-105 C
Adder
8.3588235294117657.105
316044AC1-158 C1
80/20
14.96214.962
939261AE1-157 C
Adder
13.77647058823529511.71
963611AG1-210 C
Adder
0.66705882352941170.567
961611AG1-000B C
Adder
17.55647058823529614.923
316375AC2-012 C
80/20
1.4881.488
940541AE2-040 C
Adder
3.03764705882352942.582
940481AE2-033 C
Adder
17.08117647058823614.519
927041AC1-191 C
Adder
10.0729411764705888.562
3150731STONECA
80/20
7.6067.606
935161AD1-151 C
Adder
17.79176470588235415.123
3142366NRTHEST
80/20
0.20.2
958161AF2-110 C
Adder
1.50117647058823531.276
938531AE1-072 C
Adder
19.2929411764705916.399
933981AD1-022 C
Adder
9.2505882352941197.863
943471AF1-018 C
Adder
7.4541176470588246.336
3152331SURRY 2
80/20
27.29427.294
940641AE2-051 C
80/20
18.48818.488
316336AC2-165 C
Adder
10.1094117647058828.593
958261AF2-120 C
Adder
6.4035294117647065.443
3143096IRON208
80/20
0.4840.484
939191AE1-149 C
80/20
11.90511.905
964791AG1-342 C
Adder
3.32117647058823542.823
957601AF2-054 C
Adder
2.2117647058823531.88
316164AC1-076_C
80/20
0.9930.993
961951AG1-038 C
Adder
3.3117647058823532.815
3150791HOPHCF3
80/20
2.6772.677
3138533PONTONDP
Adder
0.62941176470588240.535
940551AE2-041 C
Adder
7.4541176470588246.336
943461AF1-017 C
Adder
1.48588235294117641.263
316311AC2-079 C
Adder
6.3129411764705885.366
316233AE1-074 C
80/20
2.8192.819
966661AG1-536 C
Adder
5.5082352941176484.682
3150991CHESPKB
80/20
0.7960.796
939411AE1-173 C
80/20
97.64897.648
3137643SOCKMAN
Adder
0.72705882352941180.618
944631AF1-128 C
Adder
43.1623529411764736.688
3150921YORKTN3
Adder
130.26705882352942110.727
3150851SPRUNCC
80/20
0.1830.183
933291AC2-141 C
80/20
33.66433.664
3152251N ANNA1
80/20
55.32355.323
316303AF2-085
80/20
4.3634.363
SIGELTFEXP_SIGE->PJM
CLTF
0.2370.237
NYPJM->LTFIMP_NY
CLTF
2.8062.806
LGEELTFEXP_LGEE->PJM
CLTF
1.2221.222
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.65727.657
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.08222.082
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.7473.747
LAGNLTFEXP_LAGN->PJM
CLTF
7.6777.677
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.2865.286
CBM South 2LTFEXP_CBM-S2->PJM
CBM
94.17394.173
CPLELTFEXP_CPLE->PJM
CLTF
11.08811.088
TVALTFEXP_TVA->PJM
CLTF
6.1396.139

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.54 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4631.24
MW Contribution:3.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943462AF1-017 E
Adder
2.03764705882352941.732
942341AE2-247 C
Adder
1.38000000000000011.173
958162AF2-110 E
Adder
2.01764705882352931.715
919153AA1-139 E2
Adder
3.78941176470588253.221
934502AD1-074 E
Adder
15.85176470588235313.474
934512AD1-075 E
Adder
3.96235294117647063.368
918512AA1-065 E OP
Adder
5.1070588235294124.341
924516AB2-100 E1
Adder
2.74588235294117672.334
940642AE2-051 E
50/50
12.05212.052
966621AG1-532 C
Adder
1.32117647058823541.123
924022AB2-043 E O1
Adder
4.7941176470588244.075
3147223TWITTYS
Adder
0.87882352941176480.747
959312AF2-222 E
Adder
10.3129411764705888.766
3152261N ANNA2
50/50
89.60889.608
934861AD1-115 C
Adder
2.92.465
3150651CHESTF6
Adder
15.92588235294117813.537
946262AF1-291 E
Adder
1.24470588235294131.058
934576AD1-082 E
Adder
4.0564705882352943.448
943612AF1-032 E
Adder
0.85764705882352940.729
3145506HICKORY
Adder
2.02235294117647071.719
944602AF1-125 E
Adder
95.5082352941176581.182
957871AF2-081 C
Adder
9.2670588235294127.877
933292AC2-141 E
Adder
12.0070588235294110.206
940492AE2-034 E
Adder
2.85176470588235282.424
934522AD1-076 E
Adder
5.7635294117647064.899
943172AE2-346 E
Adder
0.56117647058823530.477
918492AA1-063AE OP
Adder
3.80117647058823543.231
925122AB2-169 E
Adder
5.2764705882352954.485
917332KELFORD E
Adder
1.51764705882352961.29
316274AC1-208 C
Adder
8.2905882352941187.047
937482AD2-202 E
Adder
1.02705882352941180.873
961792AG1-021 E
Adder
1.4117647058823531.2
3150831SPRUNCA
Adder
8.1435294117647056.922
3150841SPRUNCB
Adder
8.1435294117647056.922
926662AC1-147 E
Adder
1.22588235294117661.042
916192Z1-068 E
Adder
1.74235294117647071.481
957492AF2-043 E
Adder
1.31882352941176471.121
923852AB2-025 E
Adder
1.1282352941176470.959
939412AE1-173 E
Adder
61.5211764705882452.293
961942AG1-037 E
Adder
0.311764705882352940.265
961941AG1-037 C
Adder
0.46705882352941180.397
941031AE2-094 C
50/50
41.61841.618
941032AE2-094 E
50/50
18.6418.64
936262AD2-033 E
Adder
8.0141176470588256.812
923862AB2-026 E
Adder
1.28117647058823541.089
958211AF2-115 C
Adder
2.0717647058823531.761
3151791S ANNAG2
50/50
2.6852.685
3151771S ANNAG1
50/50
2.6852.685
3151781S ANNAS1
50/50
1.381.38
3151761LOISA E
50/50
5.5965.596
208900BRIS G1
50/50
-2.836-2.836
961611AG1-000B C
Adder
13.8152941176470611.743
940541AE2-040 C
Adder
2.78823529411764742.37
940481AE2-033 C
Adder
15.6752941176470613.324
940482AE2-033 E
Adder
10.5670588235294118.982
923263AB1-132 E OP
Adder
5.697647058823534.843
924312AB2-078 E O1
Adder
1.23529411764705891.05
925612AC1-036 E
Adder
0.79294117647058830.674
966001AG1-469 C
50/50
1.9871.987
926740AC1-158 E2
50/50
50.96750.967
925672AC1-043 E
Adder
9.4635294117647078.044
3150731STONECA
Adder
0.92705882352941180.788
935161AD1-151 C
Adder
13.69411764705882511.64
932046AC2-012 E
Adder
12.12705882352941210.308
958161AF2-110 C
Adder
1.26823529411764711.078
938531AE1-072 C
Adder
16.29411764705882213.85
3145393UNCAMP
Adder
5.65176470588235354.804
933981AD1-022 C
Adder
8.0941176470588236.88
900672V4-068 E
Adder
0.33058823529411770.281
924302AB2-077 E O1
Adder
1.23529411764705891.05
926486AC1-120 E
50/50
4.1534.153
939192AE1-149 E
Adder
6.5694117647058825.584
939312AE1-162 E
Adder
1.27764705882352961.086
942001AE2-212 C
Adder
1.94235294117647061.651
934065AD1-033 E
Adder
4.6541176470588243.956
937226AE2-253 E
Adder
5.4188235294117654.606
934501AD1-074 C
Adder
31.13882352941176626.468
924517AB2-100 E2
Adder
2.74588235294117672.334
957482AF2-042 E
Adder
35.55176470588235630.219
934621AD1-088 C
Adder
9.3717647058823547.966
935172AD1-152 E
Adder
5.1847058823529414.407
958502AF2-144 E
Adder
1.2588235294117651.07
946301AF1-294 C
Adder
3.4070588235294122.896
942461AE2-259 C
Adder
9.1658823529411777.791
316192AB2-158 C
50/50
3.6573.657
208901BRIS G2
50/50
-3.356-3.356
940431AE2-027 C
Adder
11.2058823529411789.525
942002AE2-212 E
Adder
1.2952941176470591.101
941101AE2-104 C
Adder
3.10941176470588232.643
944581AF1-123 C
Adder
42.37411764705882436.018
316141AB2-099 E
Adder
0.234117647058823540.199
316088AB2-174 E
Adder
6.1235294117647065.205
923994AB2-040_E
Adder
5.76941176470588254.904
957481AF2-042 C
Adder
53.3270588235294245.328
924322AB2-079 E O1
Adder
1.23529411764705891.05
946302AF1-294 E
Adder
2.88470588235294122.452
3151801S ANNAS2
50/50
1.381.38
939191AE1-149 C
Adder
9.8529411764705898.375
3143316POE
Adder
1.28823529411764711.095
901082W1-029 E
Adder
29.54000000000000325.109
926206AC1-098 E
Adder
3.35647058823529452.853
942462AE2-259 E
Adder
6.1105882352941175.194
3151751LOISA D
50/50
2.7452.745
3151731LOISA B
50/50
2.7452.745
316164AC1-076_C
50/50
1.1311.131
935112AD1-144 E
Adder
0.85764705882352940.729
316349AD2-085 C
Adder
3.1835294117647062.706
944582AF1-123 E
Adder
97.0317647058823782.477
944592AF1-124 E
Adder
97.3823529411764882.775
923832AB2-022 E
Adder
1.14941176470588240.977
938772AE1-103 E
Adder
3.75764705882352963.194
916042Z1-036 E
Adder
26.4694117647058822.499
960082AF2-299 E
Adder
1.17529411764705880.999
946281AF1-292 C
Adder
1.45882352941176461.24
926071AC1-086 C
Adder
19.57647058823529616.64
963042AG1-153 E
Adder
8.6682352941176477.368
964241AG1-285 C
Adder
11.5811764705882349.844
962561AG1-105 C
Adder
8.0894117647058836.876
958212AF2-115 E
Adder
1.76470588235294111.5
925022AB2-158 E
50/50
9.7219.721
316044AC1-158 C1
50/50
19.48619.486
946282AF1-292 E
Adder
0.97294117647058820.827
944012AF1-069 E
50/50
5.2835.283
3138533PONTONDP
Adder
0.61411764705882350.522
3151721LOISA A
50/50
2.7312.731
316254AC1-120 C
50/50
8.0618.061
316257AC1-043 C
Adder
5.84.93
925332AB2-190 E
Adder
6.8164705882352945.794
927226AC1-216 E
Adder
6.5917647058823535.603
936666AD2-085 E
Adder
5.195294117647064.416
941591AE2-156 C
Adder
16.57647058823529614.09
944591AF1-124 C
Adder
42.5247058823529436.146
944601AF1-125 C
Adder
41.7211764705882435.463
938771AE1-103 C
Adder
2.72117647058823582.313
3145413WATKINS
Adder
0.64235294117647070.546
960081AF2-299 C
Adder
1.76235294117647071.498
926072AC1-086 E
Adder
8.9094117647058837.573
944011AF1-069 C
50/50
13.59813.598
963041AG1-153 C
Adder
5.7788235294117654.912
936261AD2-033 C
Adder
12.02117647058823610.218
962562AG1-105 E
Adder
5.3929411764705884.584
961791AG1-021 C
Adder
1.65764705882352951.409
316045AC1-158 C2
50/50
19.48619.486
316170AC1-121 C
50/50
2.7692.769
316084AB2-161 E
Adder
5.0917647058823544.328
3145946PLYMOUTH TP
Adder
0.29882352941176470.254
933982AD1-022 E
Adder
4.4070588235294123.746
940641AE2-051 C
50/50
18.07818.078
927146AC1-208 E
Adder
3.68117647058823533.129
934622AD1-088 E
Adder
4.5117647058823533.835
934612AD1-087 E
Adder
3.50941176470588272.983
316336AC2-165 C
Adder
10.0588235294117668.55
926004AC1-076_E
50/50
6.486.48
935162AD1-151 E
Adder
9.1294117647058827.76
943461AF1-017 C
Adder
1.2482352941176471.061
932596AC2-079 E
Adder
8.6588235294117667.36
316311AC2-079 C
Adder
5.3070588235294124.511
938532AE1-072 E
Adder
8.4941176470588247.22
3146326AYDLETT TAP
Adder
1.25764705882352931.069
917122Z2-027 E
Adder
1.24470588235294131.058
920692AA2-178 E
Adder
3.8023529411764713.232
316233AE1-074 C
Adder
2.5458823529411772.164
966622AG1-532 E
Adder
0.88117647058823530.749
3147133PAMPLIN
Adder
0.91529411764705890.778
966002AG1-469 E
50/50
0.9930.993
926739AC1-158 E1
50/50
50.96750.967
940432AE2-027 E
Adder
7.4705882352941186.35
934012AD1-025 E
Adder
8.5352941176470597.255
913392Y1-086 E
Adder
2.03647058823529431.731
939411AE1-173 C
Adder
92.2811764705882478.439
3137643SOCKMAN
Adder
0.66588235294117650.566
933502AC2-165 E
Adder
7.5705882352941176.435
3151741LOISA C
50/50
2.7452.745
3145256KINGFORK
Adder
0.92470588235294130.786
925522AC1-027 E
Adder
1.1282352941176470.959
941102AE2-104 E
Adder
4.9423529411764714.201
957872AF2-081 E
Adder
3.9717647058823533.376
933291AC2-141 C
Adder
28.12941176470588223.91
926755AC1-161 E
Adder
12.0070588235294110.206
938552AE1-074 E
Adder
1.28235294117647071.09
932632AC2-084 E
Adder
2.96705882352941152.522
926214AC1-099 E
Adder
1.1082352941176470.942
924162AB2-060 E OP
Adder
3.95764705882352933.364
964242AG1-285 E
Adder
7.7211764705882356.563
938562AE1-075 E
Adder
1.0917647058823530.928
3152251N ANNA1
50/50
89.57189.571
934862AD1-115 E
Adder
4.73176470588235354.022
924814AB2-134 E
Adder
10.7988235294117659.179
944641AF1-129 C
Adder
87.4717647058823574.351
316240AF1-291 C
Adder
1.86705882352941191.587
942342AE2-247 E
Adder
1.90588235294117661.62
919152AA1-139 E1
Adder
3.78941176470588253.221
934521AD1-076 C
Adder
11.3094117647058829.613
934511AD1-075 C
Adder
7.7847058823529426.617
920042AA2-088 E OP
Adder
9.8670588235294128.387
3145723EMPORIA
Adder
0.405882352941176470.345
923573AB1-173 E OP
Adder
3.07647058823529432.615
919692AA2-053 E OP
Adder
3.93176470588235333.342
925785AC1-054 E
Adder
3.18705882352941172.709
959311AF2-222 C
Adder
15.39294117647058813.084
926502AC1-121 E
50/50
1.3031.303
316303AF2-085
50/50
4.3644.364
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7645.764
SIGELTFEXP_SIGE->PJM
CLTF
0.2140.214
NYPJM->LTFIMP_NY
CLTF
2.7142.714
LGEELTFEXP_LGEE->PJM
CLTF
1.0981.098
WECLTFEXP_WEC->PJM
CLTF
0.5410.541
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.22125.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.23820.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.4183.418
LAGNLTFEXP_LAGN->PJM
CLTF
7.0687.068
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.0035.003
CBM South 2LTFEXP_CBM-S2->PJM
CBM
88.42988.429
CPLELTFEXP_CPLE->PJM
CLTF
10.49610.496
TVALTFEXP_TVA->PJM
CLTF
5.6275.627
O66PJM->LTFIMP_O-066
CMTX_NF
36.7236.72

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4234.7
MW Contribution:2.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944011AF1-069 C
80/20
45.1645.16
963041AG1-153 C
80/20
17.10317.103
3151051BRUNSWICKS1
80/20
52.26552.265
941031AE2-094 C
80/20
138.215138.215
3151531CLOVER1
80/20
28.86828.868
3151541CLOVER2
80/20
28.59828.598
958211AF2-115 C
80/20
2.8862.886
24684605SMG4
80/20
3.0033.003
964211AG1-282 C
Adder
-1.7011764705882353-1.446
942001AE2-212 C
Adder
-2.010588235294118-1.709
3151031BRUNSWICKG2
80/20
25.15725.157
316359AB2-059 C OP
80/20
1.0881.088
934621AD1-088 C
80/20
21.36821.368
946301AF1-294 C
80/20
4.7464.746
942461AE2-259 C
80/20
12.19912.199
316283AC2-100 C
80/20
2.1162.116
316197AC1-042 C
80/20
0.3150.315
3151601KERR 3
80/20
1.6151.615
3151581KERR 1
80/20
0.5770.577
935171AD1-152 C
80/20
2.8492.849
936161AD2-022 C
80/20
12.15912.159
270197AC1-083 C
80/20
0.9340.934
3152661PLYWOOD A
80/20
2.0932.093
964241AG1-285 C
80/20
17.07617.076
316034AC1-036 C
80/20
0.3110.311
962561AG1-105 C
80/20
14.10814.108
316118AC1-105 C
80/20
1.5721.572
3144293JTRSVLE
80/20
0.5290.529
316217AC1-145 C
80/20
0.3750.375
942671AE2-283 C
80/20
3.3963.396
943811AF1-049 C
80/20
8.9298.929
938741AE1-100 C
80/20
0.690.69
941671AE2-166 C
80/20
5.45.4
24728405LEESVG
80/20
0.8940.894
938531AE1-072 C
Adder
-16.01294117647059-13.611
316049AB1-081 C OP
80/20
0.9230.923
316238AB2-078 C O1
80/20
0.4550.455
316322AB2-045 C
80/20
0.2270.227
944641AF1-129 C
Adder
-90.49176470588236-76.918
316240AF1-291 C
Adder
-1.9317647058823528-1.642
316263AC1-034 C
80/20
4.3284.328
937481AD2-202 C
80/20
0.8240.824
3151591KERR 2
80/20
1.6151.615
959311AF2-222 C
80/20
22.05622.056
316205AC1-080 C
80/20
0.4520.452
316123AC1-075 C
80/20
1.3531.353
942751AE2-291 C
80/20
12.11212.112
3151561HALLBR1
80/20
1.1241.124
24684305SMG1
80/20
1.0911.091
3151021BRUNSWICKG1
80/20
25.15725.157
957481AF2-042 C
80/20
129.887129.887
316003AC1-222 C
80/20
1.7441.744
24684405SMG2
80/20
3.0033.003
3151041BRUNSWICKG3
80/20
25.15725.157
316239AB2-077 C O1
80/20
0.4550.455
964791AG1-342 C
80/20
5.7665.766
940081AE1-250 C
80/20
12.86112.861
957601AF2-054 C
Adder
-1.8-1.53
316129AC1-054 C
80/20
1.0481.048
3151631KERR 6
80/20
1.6151.615
316131AB2-060 C
80/20
2.042.04
3138533PONTONDP
80/20
0.8550.855
24684505SMG3
80/20
1.8451.845
24684705SMG5
80/20
1.1411.141
941431AE2-140 C
80/20
13.39313.393
936261AD2-033 C
80/20
17.43217.432
961791AG1-021 C
80/20
2.3092.309
316248AF1-058 C
80/20
0.5710.571
936171AD2-023 C
80/20
7.0937.093
941801AE2-185 C
80/20
4.3664.366
940641AE2-051 C
Adder
-21.040000000000003-17.884
3152431Z1-086 GT3
80/20
33.46433.464
934611AD1-087 C
80/20
2.842.84
3151611KERR 4
80/20
1.6151.615
3151621KERR 5
80/20
1.6151.615
316237AB2-079 C O1
80/20
0.4550.455
316222AC1-221 C
80/20
2.6372.637
3152421Z1-086 GT2
80/20
33.46433.464
3152441Z1-086 ST
80/20
58.26658.266
3152411Z1-086 GT1
80/20
33.47333.473
940601AE2-047 C
80/20
4.0274.027
933291AC2-141 C
Adder
-32.203529411764706-27.373
3151641KERR 7
80/20
1.6151.615
313527AB2-043 C
80/20
0.7110.711
SIGELTFEXP_SIGE->PJM
CLTF
0.5240.524
NYPJM->LTFIMP_NY
CLTF
2.1082.108
LGEELTFEXP_LGEE->PJM
CLTF
2.7422.742
WECLTFEXP_WEC->PJM
CLTF
1.451.45
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.06671.066
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.76444.764
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.3488.348
LAGNLTFEXP_LAGN->PJM
CLTF
14.84614.846
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.2639.263
CBM South 2LTFEXP_CBM-S2->PJM
CBM
170.641170.641
CPLELTFEXP_CPLE->PJM
CLTF
19.41719.417
TVALTFEXP_TVA->PJM
CLTF
11.71211.712
CONTINGENCY 'DVP_P4-6: CHASE C T342_SRT-A'
 OPEN BUS 313527   /*AB2-043 C      0.6
 OPEN BUS 313528   /*AB2-043 COL   34.5
 OPEN BUS 313529   /*3BLUESTONE   115.0
 OPEN BUS 314267   /*3CHASCTY2    115.0
 OPEN BUS 314518   /*3CHASC_1     115.0
 OPEN BUS 314681   /*3CHASCTY     115.0
 OPEN BUS 924022   /*AB2-043 E O1   0.6
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 246_SRT-A'
 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1   /*6SUFFOLK     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1   /*6EARLEYS     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1   /*6NUCO TP     230.0 - 6NUCOR       230.0
 OPEN BUS 314575                                   /*6NUCO TP     230.0
 OPEN BUS 314590                                   /*6NUCOR       230.0
END
CONTINGENCY 'DVP_P1-2: LN 556_SRT-S-3'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 568T575_SRT-A'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1   /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1   /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 314940 TO BUS 941030 CKT 1   /*8ROGERS RD   500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314691 to 314692 ckt 1
314691 to 314692 ckt 2
314282 to 314285 ckt 1
314563 to 940480 ckt 1
314435 to 314282 ckt 1
314902 to 314914 ckt 1
314914 to 314918 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314936 to 314902 ckt 1
314934 to 314916 ckt 1
941030 to 314902 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P1-2: LN 235_SRT-A
OPAC121.52 %182.64B221.959.81
GD1DVP
3FLAT CREEK-3MORAN 115.0 kV Ckt 1 line
DVP_P1-2: LN 1045_SRT-A
OPAC119.98 %203.98B244.7424.99
GD1DVP
3LONEPN-3FLAT CREEK 115.0 kV Ckt 1 line
DVP_P1-2: LN 1045_SRT-A
OPAC120.01 %203.98B244.7924.99
GD1DVP
3MORAN-3FARMVIL 115.0 kV Ckt 1 line
DVP_P1-2: LN 1045_SRT-A
OPAC117.13 %203.98B238.9324.99
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC109.21 %678.68B741.185.74
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC108.15 %678.68B734.035.74
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC105.97 %661.76B701.295.35
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC108.64 %661.76B718.915.35
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC102.38 %661.76B677.525.35
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 578_SRT-S-1
OPAC111.64 %3220.44B3595.274.07
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Base Case
OPAC104.13 %3220.44A3353.363.77
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
AEP_P1-2_242515_248184_SRT-A
OPAC101.33 %3220.44B3263.394.53
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
OPAC108.69 %4070.2B4423.717.15
GD1DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC106.0 %2442.12B2588.613.08
GD1DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
OPAC105.93 %4070.2B4311.696.22

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 235_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:121.52 %
Rating:182.64 MVA
Rating Type:B
MVA to Mitigate:221.95
MW Contribution:9.81
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 235_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:149.01 %
Rating:182.64 MVA
Rating Type:B
MVA to Mitigate:272.15
MW Contribution:11.01
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3147133PAMPLIN
50/50
2.4852.485
934622AD1-088 E
Adder
1.42588235294117641.212
924302AB2-077 E O1
50/50
0.9010.901
925612AC1-036 E
50/50
1.1371.137
316237AB2-079 C O1
50/50
0.2210.221
924312AB2-078 E O1
50/50
0.9010.901
316238AB2-078 C O1
50/50
0.2210.221
926274AC1-105 E
Adder
1.0752941176470590.914
938821AE1-108 C
Adder
-5.455294117647059-4.637
936261AD2-033 C
50/50
18.4818.48
3144293JTRSVLE
50/50
0.9750.975
961791AG1-021 C
50/50
4.2384.238
962562AG1-105 E
Adder
3.05294117647058852.595
316131AB2-060 C
50/50
1.1311.131
3138533PONTONDP
50/50
1.571.57
964241AG1-285 C
50/50
8.3818.381
316034AC1-036 C
50/50
0.310.31
958212AF2-115 E
50/50
4.5134.513
962561AG1-105 C
Adder
4.583.893
316239AB2-077 C O1
50/50
0.2210.221
942462AE2-259 E
50/50
22.19822.198
964791AG1-342 C
Adder
1.70117647058823531.446
961792AG1-021 E
50/50
3.613.61
941011AE2-092 C
Adder
-4.856470588235294-4.128
3147223TWITTYS
50/50
1.261.26
959312AF2-222 E
50/50
16.16916.169
924022AB2-043 E O1
50/50
3.623.62
924322AB2-079 E O1
50/50
0.9010.901
946302AF1-294 E
50/50
7.3787.378
943902AF1-058 E
Adder
0.414117647058823530.352
936262AD2-033 E
50/50
12.3212.32
958211AF2-115 C
50/50
5.2985.298
959311AF2-222 C
50/50
24.13324.133
964242AG1-285 E
50/50
5.5885.588
313527AB2-043 C
50/50
0.3610.361
924162AB2-060 E OP
50/50
3.2583.258
964792AG1-342 E
Adder
1.13411764705882350.964
934621AD1-088 C
Adder
2.9611764705882352.517
946301AF1-294 C
50/50
8.7128.712
942461AE2-259 C
50/50
33.29833.298
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.1372.137
G-007PJM->LTFIMP_G-007
CMTX_NF
0.2090.209
CPLELTFEXP_CPLE->PJM
CLTF
1.51.5
SIGELTFEXP_SIGE->PJM
CLTF
0.0180.018
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.68211.682
WECLTFEXP_WEC->PJM
CLTF
0.0450.045
LAGNLTFEXP_LAGN->PJM
CLTF
0.7670.767
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0840.084
MECLTFEXP_MEC->PJM
CLTF
0.3150.315
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.7150.715
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.0592.059
NYPJM->LTFIMP_NY
CLTF
0.1040.104
TVALTFEXP_TVA->PJM
CLTF
0.5920.592
O66PJM->LTFIMP_O-066
CMTX_NF
1.3381.338

Details for 3FLAT CREEK-3MORAN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1045_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
3FLAT CREEK-3MORAN 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1045_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:119.98 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:244.74
MW Contribution:24.99
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
3FLAT CREEK-3MORAN 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1045_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:119.95 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:244.68
MW Contribution:24.99
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936261AD2-033 C
50/50
77.97277.972
3144293JTRSVLE
50/50
2.4842.484
961791AG1-021 C
50/50
10.79610.796
316131AB2-060 C
50/50
8.8878.887
3138533PONTONDP
50/50
3.9993.999
958212AF2-115 E
50/50
11.49611.496
961792AG1-021 E
50/50
9.1979.197
946302AF1-294 E
50/50
18.79318.793
936262AD2-033 E
50/50
51.98151.981
958211AF2-115 C
50/50
13.49513.495
924162AB2-060 E OP
50/50
25.59125.591
946301AF1-294 C
50/50
22.19222.192
NYPJM->LTFIMP_NY
CLTF
0.020.02
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0940.094
MDUPJM->LTFIMP_MDU
CLTF
0.0040.004
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0380.038
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0130.013
O66PJM->LTFIMP_O-066
CMTX_NF
0.2440.244
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0210.021
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0630.063
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0270.027
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0760.076
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.020.02
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0360.036

Details for 3LONEPN-3FLAT CREEK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1045_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
3LONEPN-3FLAT CREEK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1045_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:120.01 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:244.79
MW Contribution:24.99
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
3LONEPN-3FLAT CREEK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1045_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:119.98 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:244.73
MW Contribution:24.99
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936261AD2-033 C
50/50
77.97277.972
3144293JTRSVLE
50/50
2.4842.484
961791AG1-021 C
50/50
10.79610.796
316131AB2-060 C
50/50
8.8878.887
3138533PONTONDP
50/50
3.9993.999
958212AF2-115 E
50/50
11.49611.496
961792AG1-021 E
50/50
9.1979.197
946302AF1-294 E
50/50
18.79318.793
936262AD2-033 E
50/50
51.98151.981
958211AF2-115 C
50/50
13.49513.495
924162AB2-060 E OP
50/50
25.59125.591
946301AF1-294 C
50/50
22.19222.192
NYPJM->LTFIMP_NY
CLTF
0.020.02
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0940.094
MDUPJM->LTFIMP_MDU
CLTF
0.0040.004
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0380.038
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0130.013
O66PJM->LTFIMP_O-066
CMTX_NF
0.2440.244
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0210.021
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0630.063
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0270.027
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0760.076
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.020.02
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0360.036

Details for 3MORAN-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1045_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
3MORAN-3FARMVIL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1045_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.13 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:238.93
MW Contribution:24.99
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
3MORAN-3FARMVIL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1045_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.1 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:238.85
MW Contribution:24.99
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936261AD2-033 C
50/50
77.97277.972
3144293JTRSVLE
50/50
2.4842.484
961791AG1-021 C
50/50
10.79610.796
316131AB2-060 C
50/50
8.8878.887
3138533PONTONDP
50/50
3.9993.999
958212AF2-115 E
50/50
11.49611.496
961792AG1-021 E
50/50
9.1979.197
946302AF1-294 E
50/50
18.79318.793
936262AD2-033 E
50/50
51.98151.981
958211AF2-115 C
50/50
13.49513.495
924162AB2-060 E OP
50/50
25.59125.591
946301AF1-294 C
50/50
22.19222.192
NYPJM->LTFIMP_NY
CLTF
0.020.02
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0940.094
MDUPJM->LTFIMP_MDU
CLTF
0.0040.004
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0380.038
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0130.013
O66PJM->LTFIMP_O-066
CMTX_NF
0.2440.244
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0210.021
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0630.063
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0270.027
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0760.076
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.020.02
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0360.036

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.21 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:741.18
MW Contribution:5.74
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.95 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:773.37
MW Contribution:5.91
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3147133PAMPLIN
50/50
1.4571.457
316322AB2-045 C
50/50
0.840.84
927264AC1-222 E
Adder
1.98117647058823531.684
958132AF2-107 E
Adder
1.30941176470588231.113
316336AC2-165 C
50/50
32.5532.55
934622AD1-088 E
50/50
3.2133.213
934612AD1-087 E
Adder
1.95058823529411751.658
3151931BEARGRDN S1
50/50
23.0223.02
924302AB2-077 E O1
50/50
0.9550.955
958131AF2-107 C
Adder
2.38941176470588262.031
925612AC1-036 E
50/50
0.8890.889
316237AB2-079 C O1
50/50
0.2340.234
924312AB2-078 E O1
50/50
0.9550.955
316238AB2-078 C O1
50/50
0.2340.234
926274AC1-105 E
Adder
1.48352941176470581.261
938821AE1-108 C
50/50
16.62316.623
936261AD2-033 C
50/50
13.17213.172
3144293JTRSVLE
50/50
0.5710.571
961791AG1-021 C
50/50
2.4812.481
962562AG1-105 E
50/50
3.6743.674
924032AB2-045 E
50/50
3.7663.766
316131AB2-060 C
50/50
1.121.12
3138533PONTONDP
50/50
0.9190.919
964241AG1-285 C
50/50
9.9699.969
316034AC1-036 C
50/50
0.2430.243
958212AF2-115 E
50/50
2.6422.642
962561AG1-105 C
50/50
5.5115.511
316239AB2-077 C O1
50/50
0.2340.234
942462AE2-259 E
50/50
11.78211.782
964791AG1-342 C
Adder
2.1235294117647061.805
937482AD2-202 E
Adder
0.57058823529411760.485
961792AG1-021 E
50/50
2.1132.113
3151921BEARGRDN G2
50/50
17.79517.795
941011AE2-092 C
Adder
8.222352941176476.989
3147223TWITTYS
50/50
0.9860.986
959312AF2-222 E
50/50
12.07212.072
924022AB2-043 E O1
50/50
3.7783.778
957481AF2-042 C
Adder
27.58352941176470823.446
924322AB2-079 E O1
50/50
0.9550.955
946302AF1-294 E
50/50
4.3194.319
943902AF1-058 E
Adder
0.65294117647058840.555
936262AD2-033 E
50/50
8.7818.781
958211AF2-115 C
50/50
3.1013.101
941012AE2-092 E
Adder
5.48117647058823554.659
925785AC1-054 E
Adder
1.48235294117647071.26
959311AF2-222 C
50/50
18.01818.018
964242AG1-285 E
50/50
6.6466.646
313527AB2-043 C
50/50
0.3760.376
924162AB2-060 E OP
50/50
3.2253.225
964792AG1-342 E
Adder
1.41647058823529411.204
3151911BEARGRDN G1
50/50
17.79517.795
933502AC2-165 E
50/50
24.49824.498
957482AF2-042 E
Adder
18.38941176470588315.631
934621AD1-088 C
50/50
6.6736.673
935172AD1-152 E
Adder
2.81529411764705852.393
946301AF1-294 C
50/50
5.15.1
942461AE2-259 C
50/50
17.67317.673
938822AE1-108 E
50/50
7.9317.931
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.0390.039
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6760.676
CPLELTFEXP_CPLE->PJM
CLTF
2.8232.823
SIGELTFEXP_SIGE->PJM
CLTF
0.0110.011
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.54721.547
WECLTFEXP_WEC->PJM
CLTF
0.0090.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.161.16
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0240.024
MECLTFEXP_MEC->PJM
CLTF
0.2490.249
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3441.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.6382.638
NYPJM->LTFIMP_NY
CLTF
0.3510.351
TVALTFEXP_TVA->PJM
CLTF
0.8870.887
O66PJM->LTFIMP_O-066
CMTX_NF
4.3344.334

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.15 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:734.03
MW Contribution:5.74
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.89 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:766.15
MW Contribution:5.91
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3147133PAMPLIN
50/50
1.4571.457
316322AB2-045 C
50/50
0.840.84
927264AC1-222 E
Adder
1.98117647058823531.684
958132AF2-107 E
Adder
1.30941176470588231.113
316336AC2-165 C
50/50
32.5532.55
934622AD1-088 E
50/50
3.2133.213
934612AD1-087 E
Adder
1.95058823529411751.658
3151931BEARGRDN S1
50/50
23.0223.02
924302AB2-077 E O1
50/50
0.9550.955
958131AF2-107 C
Adder
2.38941176470588262.031
925612AC1-036 E
50/50
0.8890.889
316237AB2-079 C O1
50/50
0.2340.234
924312AB2-078 E O1
50/50
0.9550.955
316238AB2-078 C O1
50/50
0.2340.234
926274AC1-105 E
Adder
1.48352941176470581.261
938821AE1-108 C
50/50
16.62316.623
936261AD2-033 C
50/50
13.17213.172
3144293JTRSVLE
50/50
0.5710.571
961791AG1-021 C
50/50
2.4812.481
962562AG1-105 E
50/50
3.6743.674
924032AB2-045 E
50/50
3.7663.766
316131AB2-060 C
50/50
1.121.12
3138533PONTONDP
50/50
0.9190.919
964241AG1-285 C
50/50
9.9699.969
316034AC1-036 C
50/50
0.2430.243
958212AF2-115 E
50/50
2.6422.642
962561AG1-105 C
50/50
5.5115.511
316239AB2-077 C O1
50/50
0.2340.234
942462AE2-259 E
50/50
11.78211.782
964791AG1-342 C
Adder
2.1235294117647061.805
937482AD2-202 E
Adder
0.57058823529411760.485
961792AG1-021 E
50/50
2.1132.113
3151921BEARGRDN G2
50/50
17.79517.795
941011AE2-092 C
Adder
8.222352941176476.989
3147223TWITTYS
50/50
0.9860.986
959312AF2-222 E
50/50
12.07212.072
924022AB2-043 E O1
50/50
3.7783.778
957481AF2-042 C
Adder
27.58352941176470823.446
924322AB2-079 E O1
50/50
0.9550.955
946302AF1-294 E
50/50
4.3194.319
943902AF1-058 E
Adder
0.65294117647058840.555
936262AD2-033 E
50/50
8.7818.781
958211AF2-115 C
50/50
3.1013.101
941012AE2-092 E
Adder
5.48117647058823554.659
925785AC1-054 E
Adder
1.48235294117647071.26
959311AF2-222 C
50/50
18.01818.018
964242AG1-285 E
50/50
6.6466.646
313527AB2-043 C
50/50
0.3760.376
924162AB2-060 E OP
50/50
3.2253.225
964792AG1-342 E
Adder
1.41647058823529411.204
3151911BEARGRDN G1
50/50
17.79517.795
933502AC2-165 E
50/50
24.49824.498
957482AF2-042 E
Adder
18.38941176470588315.631
934621AD1-088 C
50/50
6.6736.673
935172AD1-152 E
Adder
2.81529411764705852.393
946301AF1-294 C
50/50
5.15.1
942461AE2-259 C
50/50
17.67317.673
938822AE1-108 E
50/50
7.9317.931
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0240.024
MECLTFEXP_MEC->PJM
CLTF
0.2490.249
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3441.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.6382.638
NYPJM->LTFIMP_NY
CLTF
0.3510.351
TVALTFEXP_TVA->PJM
CLTF
0.8870.887
O66PJM->LTFIMP_O-066
CMTX_NF
4.3344.334
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.0390.039
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6760.676
CPLELTFEXP_CPLE->PJM
CLTF
2.8232.823
SIGELTFEXP_SIGE->PJM
CLTF
0.0110.011
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.54721.547
WECLTFEXP_WEC->PJM
CLTF
0.0090.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.161.16

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.97 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:701.29
MW Contribution:5.35
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.14 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:748.75
MW Contribution:5.51
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3147133PAMPLIN
50/50
1.3571.357
316322AB2-045 C
50/50
0.7820.782
927264AC1-222 E
Adder
1.91647058823529411.629
958132AF2-107 E
50/50
2.5922.592
316336AC2-165 C
50/50
30.2830.28
934622AD1-088 E
50/50
2.9962.996
934612AD1-087 E
Adder
1.8235294117647061.55
3151931BEARGRDN S1
50/50
21.41521.415
924302AB2-077 E O1
50/50
0.8940.894
958131AF2-107 C
50/50
4.7314.731
925612AC1-036 E
50/50
0.8290.829
316237AB2-079 C O1
50/50
0.2190.219
924312AB2-078 E O1
50/50
0.8940.894
316238AB2-078 C O1
50/50
0.2190.219
926274AC1-105 E
Adder
1.40941176470588241.198
938821AE1-108 C
50/50
33.08633.086
936261AD2-033 C
50/50
12.29412.294
3144293JTRSVLE
50/50
0.5320.532
961791AG1-021 C
50/50
2.3122.312
962562AG1-105 E
Adder
3.4647058823529412.945
924032AB2-045 E
50/50
3.5043.504
316131AB2-060 C
50/50
1.0471.047
3138533PONTONDP
50/50
0.8560.856
964241AG1-285 C
50/50
9.3069.306
316034AC1-036 C
50/50
0.2260.226
958212AF2-115 E
50/50
2.4622.462
962561AG1-105 C
Adder
5.197647058823534.418
316239AB2-077 C O1
50/50
0.2190.219
942462AE2-259 E
50/50
10.9710.97
964791AG1-342 C
Adder
2.00705882352941161.706
937482AD2-202 E
Adder
0.53411764705882360.454
961792AG1-021 E
50/50
1.971.97
3151921BEARGRDN G2
50/50
16.55416.554
941011AE2-092 C
50/50
23.99423.994
3147223TWITTYS
50/50
0.9190.919
959312AF2-222 E
50/50
11.25511.255
924022AB2-043 E O1
50/50
3.5343.534
957481AF2-042 C
Adder
25.7317647058823521.872
924322AB2-079 E O1
50/50
0.8940.894
946302AF1-294 E
50/50
4.0254.025
943902AF1-058 E
Adder
0.62352941176470590.53
936262AD2-033 E
50/50
8.1968.196
958211AF2-115 C
50/50
2.892.89
941012AE2-092 E
50/50
15.99615.996
925785AC1-054 E
Adder
1.3870588235294121.179
959311AF2-222 C
50/50
16.79916.799
964242AG1-285 E
50/50
6.2046.204
313527AB2-043 C
50/50
0.3520.352
924162AB2-060 E OP
50/50
3.0163.016
964792AG1-342 E
Adder
1.33764705882352941.137
3151911BEARGRDN G1
50/50
16.55416.554
933502AC2-165 E
50/50
22.78922.789
957482AF2-042 E
Adder
17.15411764705882214.581
934621AD1-088 C
50/50
6.2236.223
935172AD1-152 E
Adder
2.64470588235294152.248
946301AF1-294 C
50/50
4.7534.753
942461AE2-259 C
50/50
16.45516.455
938822AE1-108 E
50/50
15.78715.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.0933.093
NYPJM->LTFIMP_NY
CLTF
0.3520.352
TVALTFEXP_TVA->PJM
CLTF
0.9770.977
O66PJM->LTFIMP_O-066
CMTX_NF
4.4054.405
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4071.407
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6880.688
CPLELTFEXP_CPLE->PJM
CLTF
2.7182.718
SIGELTFEXP_SIGE->PJM
CLTF
0.020.02
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.18821.188
WECLTFEXP_WEC->PJM
CLTF
0.0360.036
LAGNLTFEXP_LAGN->PJM
CLTF
1.2621.262
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
MECLTFEXP_MEC->PJM
CLTF
0.3740.374
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.2941.294

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.64 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:718.91
MW Contribution:5.35
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.82 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:766.43
MW Contribution:5.51
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3147133PAMPLIN
50/50
1.3571.357
316322AB2-045 C
50/50
0.7820.782
927264AC1-222 E
Adder
1.91647058823529411.629
958132AF2-107 E
50/50
2.5922.592
316336AC2-165 C
50/50
30.2830.28
934622AD1-088 E
50/50
2.9962.996
934612AD1-087 E
Adder
1.8235294117647061.55
3151931BEARGRDN S1
50/50
21.41521.415
924302AB2-077 E O1
50/50
0.8940.894
958131AF2-107 C
50/50
4.7314.731
925612AC1-036 E
50/50
0.8290.829
316237AB2-079 C O1
50/50
0.2190.219
924312AB2-078 E O1
50/50
0.8940.894
316238AB2-078 C O1
50/50
0.2190.219
926274AC1-105 E
Adder
1.40941176470588241.198
938821AE1-108 C
50/50
33.08633.086
936261AD2-033 C
50/50
12.29412.294
3144293JTRSVLE
50/50
0.5320.532
961791AG1-021 C
50/50
2.3122.312
962562AG1-105 E
Adder
3.4647058823529412.945
924032AB2-045 E
50/50
3.5043.504
316131AB2-060 C
50/50
1.0471.047
3138533PONTONDP
50/50
0.8560.856
964241AG1-285 C
50/50
9.3069.306
316034AC1-036 C
50/50
0.2260.226
958212AF2-115 E
50/50
2.4622.462
962561AG1-105 C
Adder
5.197647058823534.418
316239AB2-077 C O1
50/50
0.2190.219
942462AE2-259 E
50/50
10.9710.97
964791AG1-342 C
Adder
2.00705882352941161.706
937482AD2-202 E
Adder
0.53411764705882360.454
961792AG1-021 E
50/50
1.971.97
3151921BEARGRDN G2
50/50
16.55416.554
941011AE2-092 C
50/50
23.99423.994
3147223TWITTYS
50/50
0.9190.919
959312AF2-222 E
50/50
11.25511.255
924022AB2-043 E O1
50/50
3.5343.534
957481AF2-042 C
Adder
25.7317647058823521.872
924322AB2-079 E O1
50/50
0.8940.894
946302AF1-294 E
50/50
4.0254.025
943902AF1-058 E
Adder
0.62352941176470590.53
936262AD2-033 E
50/50
8.1968.196
958211AF2-115 C
50/50
2.892.89
941012AE2-092 E
50/50
15.99615.996
925785AC1-054 E
Adder
1.3870588235294121.179
959311AF2-222 C
50/50
16.79916.799
964242AG1-285 E
50/50
6.2046.204
313527AB2-043 C
50/50
0.3520.352
924162AB2-060 E OP
50/50
3.0163.016
964792AG1-342 E
Adder
1.33764705882352941.137
3151911BEARGRDN G1
50/50
16.55416.554
933502AC2-165 E
50/50
22.78922.789
957482AF2-042 E
Adder
17.15411764705882214.581
934621AD1-088 C
50/50
6.2236.223
935172AD1-152 E
Adder
2.64470588235294152.248
946301AF1-294 C
50/50
4.7534.753
942461AE2-259 C
50/50
16.45516.455
938822AE1-108 E
50/50
15.78715.787
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
MECLTFEXP_MEC->PJM
CLTF
0.3740.374
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.2941.294
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.0933.093
NYPJM->LTFIMP_NY
CLTF
0.3520.352
TVALTFEXP_TVA->PJM
CLTF
0.9770.977
O66PJM->LTFIMP_O-066
CMTX_NF
4.4054.405
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4071.407
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6880.688
CPLELTFEXP_CPLE->PJM
CLTF
2.7182.718
SIGELTFEXP_SIGE->PJM
CLTF
0.020.02
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.18821.188
WECLTFEXP_WEC->PJM
CLTF
0.0360.036
LAGNLTFEXP_LAGN->PJM
CLTF
1.2621.262

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.38 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:677.52
MW Contribution:5.35
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.53 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:724.84
MW Contribution:5.51
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3147133PAMPLIN
50/50
1.3571.357
316322AB2-045 C
50/50
0.7820.782
927264AC1-222 E
Adder
1.91647058823529411.629
958132AF2-107 E
50/50
2.5922.592
316336AC2-165 C
50/50
30.2830.28
934622AD1-088 E
50/50
2.9962.996
934612AD1-087 E
Adder
1.8235294117647061.55
3151931BEARGRDN S1
50/50
21.41521.415
924302AB2-077 E O1
50/50
0.8940.894
958131AF2-107 C
50/50
4.7314.731
925612AC1-036 E
50/50
0.8290.829
316237AB2-079 C O1
50/50
0.2190.219
924312AB2-078 E O1
50/50
0.8940.894
316238AB2-078 C O1
50/50
0.2190.219
926274AC1-105 E
Adder
1.40941176470588241.198
938821AE1-108 C
50/50
33.08633.086
936261AD2-033 C
50/50
12.29412.294
3144293JTRSVLE
50/50
0.5320.532
961791AG1-021 C
50/50
2.3122.312
962562AG1-105 E
Adder
3.4647058823529412.945
924032AB2-045 E
50/50
3.5043.504
316131AB2-060 C
50/50
1.0471.047
3138533PONTONDP
50/50
0.8560.856
964241AG1-285 C
50/50
9.3069.306
316034AC1-036 C
50/50
0.2260.226
958212AF2-115 E
50/50
2.4622.462
962561AG1-105 C
Adder
5.197647058823534.418
316239AB2-077 C O1
50/50
0.2190.219
942462AE2-259 E
50/50
10.9710.97
964791AG1-342 C
Adder
2.00705882352941161.706
937482AD2-202 E
Adder
0.53411764705882360.454
961792AG1-021 E
50/50
1.971.97
3151921BEARGRDN G2
50/50
16.55416.554
941011AE2-092 C
50/50
23.99423.994
3147223TWITTYS
50/50
0.9190.919
959312AF2-222 E
50/50
11.25511.255
924022AB2-043 E O1
50/50
3.5343.534
957481AF2-042 C
Adder
25.7317647058823521.872
924322AB2-079 E O1
50/50
0.8940.894
946302AF1-294 E
50/50
4.0254.025
943902AF1-058 E
Adder
0.62352941176470590.53
936262AD2-033 E
50/50
8.1968.196
958211AF2-115 C
50/50
2.892.89
941012AE2-092 E
50/50
15.99615.996
925785AC1-054 E
Adder
1.3870588235294121.179
959311AF2-222 C
50/50
16.79916.799
964242AG1-285 E
50/50
6.2046.204
313527AB2-043 C
50/50
0.3520.352
924162AB2-060 E OP
50/50
3.0163.016
964792AG1-342 E
Adder
1.33764705882352941.137
3151911BEARGRDN G1
50/50
16.55416.554
933502AC2-165 E
50/50
22.78922.789
957482AF2-042 E
Adder
17.15411764705882214.581
934621AD1-088 C
50/50
6.2236.223
935172AD1-152 E
Adder
2.64470588235294152.248
946301AF1-294 C
50/50
4.7534.753
942461AE2-259 C
50/50
16.45516.455
938822AE1-108 E
50/50
15.78715.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.0933.093
NYPJM->LTFIMP_NY
CLTF
0.3520.352
TVALTFEXP_TVA->PJM
CLTF
0.9770.977
O66PJM->LTFIMP_O-066
CMTX_NF
4.4054.405
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4071.407
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6880.688
CPLELTFEXP_CPLE->PJM
CLTF
2.7182.718
SIGELTFEXP_SIGE->PJM
CLTF
0.020.02
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.18821.188
WECLTFEXP_WEC->PJM
CLTF
0.0360.036
LAGNLTFEXP_LAGN->PJM
CLTF
1.2621.262
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
MECLTFEXP_MEC->PJM
CLTF
0.3740.374
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.2941.294

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 578_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 578_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.64 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3595.27
MW Contribution:4.07
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 578_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:116.34 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3746.65
MW Contribution:3.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938532AE1-072 E
50/50
11.18411.184
3146326AYDLETT TAP
50/50
1.6541.654
943461AF1-017 C
Adder
1.45058823529411771.233
316311AC2-079 C
Adder
6.2058823529411775.275
932596AC2-079 E
Adder
10.1247058823529418.606
3152431Z1-086 GT3
50/50
1717
3152441Z1-086 ST
50/50
29.60429.604
917122Z2-027 E
Adder
1.61411764705882371.372
920692AA2-178 E
Adder
4.94.165
966622AG1-532 E
Adder
1.15411764705882350.981
3147133PAMPLIN
Adder
0.97058823529411760.825
922923AB1-081 E OP
Adder
4.4729411764705883.802
927264AC1-222 E
Adder
4.65176470588235353.954
940641AE2-051 C
50/50
28.95128.951
316084AB2-161 E
Adder
5.457647058823534.639
3145946PLYMOUTH TP
Adder
0.38470588235294120.327
933982AD1-022 E
Adder
5.6847058823529414.832
934622AD1-088 E
50/50
5.9785.978
934611AD1-087 C
50/50
1.6841.684
934612AD1-087 E
50/50
4.8584.858
927146AC1-208 E
Adder
4.8317647058823534.107
927255AC1-221 E
Adder
4.4470588235294123.78
932046AC2-012 E
50/50
15.70315.703
316017AA1-139 ULT1
50/50
1.3241.324
938531AE1-072 C
50/50
21.45421.454
958161AF2-110 C
Adder
1.54823529411764721.316
3152411Z1-086 GT1
50/50
17.00617.006
3152421Z1-086 GT2
50/50
1717
3145393UNCAMP
Adder
7.0541176470588245.996
933981AD1-022 C
Adder
10.4411764705882368.875
900672V4-068 E
Adder
0.42352941176470590.36
924302AB2-077 E O1
Adder
1.63411764705882371.389
316375AC2-012 C
50/50
1.6191.619
961611AG1-000B C
Adder
13.20352941176470711.223
940541AE2-040 C
50/50
3.6533.653
940482AE2-033 E
50/50
13.84313.843
940481AE2-033 C
50/50
20.53320.533
923263AB1-132 E OP
Adder
7.4552941176470596.337
925612AC1-036 E
Adder
1.00470588235294110.854
924312AB2-078 E O1
Adder
1.63411764705882371.389
926274AC1-105 E
Adder
3.2105882352941182.729
944011AF1-069 C
50/50
21.38521.385
3151091ELIZAR2
50/50
3.7913.791
3151081ELIZAR1
50/50
3.8583.858
941591AE2-156 C
50/50
21.49421.494
944591AF1-124 C
50/50
56.20456.204
944601AF1-125 C
50/50
55.14255.142
316316AC1-027 C
50/50
0.3830.383
936666AD2-085 E
Adder
6.0364705882352955.131
963041AG1-153 C
50/50
8.9478.947
938771AE1-103 C
Adder
3.38352941176470572.876
3145413WATKINS
Adder
0.80705882352941180.686
960081AF2-299 C
Adder
2.30941176470588251.963
926072AC1-086 E
Adder
11.6588235294117669.91
3151531CLOVER1
50/50
17.10517.105
936261AD2-033 C
Adder
14.54117647058823512.36
961791AG1-021 C
Adder
1.761.496
962562AG1-105 E
Adder
7.1411764705882366.07
944012AF1-069 E
50/50
8.3078.307
316315AB2-025 C
50/50
0.5190.519
946282AF1-292 E
Adder
1.27411764705882361.083
3138533PONTONDP
Adder
0.6517647058823530.554
917512Z2-088 E OP1
Adder
5.8647058823529424.985
3151101ELIZAR3
50/50
3.9073.907
944582AF1-123 E
50/50
128.245128.245
944592AF1-124 E
50/50
128.709128.709
935112AD1-144 E
Adder
1.00470588235294110.854
316349AD2-085 C
Adder
3.73.145
923832AB2-022 E
Adder
1.49882352941176471.274
963042AG1-153 E
50/50
13.4213.42
938772AE1-103 E
Adder
4.6717647058823533.971
916042Z1-036 E
Adder
34.05176470588235628.944
316023AB2-100 C2
50/50
1.1931.193
946281AF1-292 C
Adder
1.9117647058823531.625
960082AF2-299 E
Adder
1.53882352941176471.308
926071AC1-086 C
Adder
25.61647058823529521.774
3151541CLOVER2
50/50
16.94616.946
964241AG1-285 C
Adder
16.00235294117647213.602
958212AF2-115 E
Adder
1.87411764705882341.593
927021AC1-189 C
Adder
10.0670588235294138.557
962561AG1-105 C
Adder
10.7117647058823549.105
924152AB2-059 E OP
Adder
6.33647058823529455.386
3143316POE
Adder
1.37411764705882341.168
939191AE1-149 C
Adder
9.9423529411764728.451
901082W1-029 E
Adder
37.7832.113
316365AB2-100 C1
50/50
1.1931.193
926206AC1-098 E
Adder
4.3952941176470593.736
935171AD1-152 C
50/50
1.7291.729
942462AE2-259 E
Adder
3.39882352941176442.889
964791AG1-342 C
Adder
4.263.621
933292AC2-141 E
50/50
19.76119.761
316294AC1-161 C
50/50
7.5657.565
944602AF1-125 E
50/50
126.232126.232
916191Z1-068 C
50/50
0.0530.053
3145506HICKORY
50/50
2.6852.685
934576AD1-082 E
Adder
4.3482352941176473.696
957871AF2-081 C
50/50
12.23112.231
943612AF1-032 E
Adder
1.06117647058823540.902
940492AE2-034 E
Adder
3.67529411764705933.124
934522AD1-076 E
Adder
7.4376470588235296.322
943172AE2-346 E
Adder
0.72235294117647060.614
918492AA1-063AE OP
Adder
4.9164705882352954.179
937482AD2-202 E
50/50
1.4221.422
917332KELFORD E
Adder
1.96941176470588241.674
925122AB2-169 E
Adder
6.8611764705882355.832
316274AC1-208 C
Adder
10.8799999999999999.248
961792AG1-021 E
Adder
1.49882352941176471.274
917342Z2-044 E
Adder
0.71882352941176480.611
3151311EDGECMA
Adder
18.62235294117647315.829
940642AE2-051 E
50/50
19.30119.301
316388AE2-253 GEN
50/50
2.4112.411
919153AA1-139 E2
50/50
5.0025.002
943462AF1-017 E
Adder
2.3670588235294122.012
942341AE2-247 C
Adder
1.60352941176470591.363
958162AF2-110 E
Adder
2.46235294117647062.093
924516AB2-100 E1
50/50
3.5953.595
934512AD1-075 E
Adder
5.11294117647058854.346
934502AD1-074 E
Adder
20.45294117647059217.385
966621AG1-532 C
Adder
1.73176470588235291.472
918512AA1-065 E OP
Adder
6.582352941176475.595
3147223TWITTYS
Adder
1.11411764705882340.947
959312AF2-222 E
Adder
12.84352941176470610.917
924022AB2-043 E O1
Adder
6.3423529411764715.391
918532AA1-067 E
Adder
0.85411764705882350.726
942002AE2-212 E
Adder
1.11999999999999990.952
944581AF1-123 C
50/50
56.00556.005
316185AD1-033 C
50/50
1.5141.514
941101AE2-104 C
Adder
3.7941176470588243.225
3151041BRUNSWICKG3
50/50
13.20613.206
3151021BRUNSWICKG1
50/50
13.20613.206
957481AF2-042 C
50/50
75.2375.23
316088AB2-174 E
Adder
8.015294117647066.813
316141AB2-099 E
Adder
0.30117647058823530.256
923994AB2-040_E
Adder
7.5482352941176486.416
924322AB2-079 E O1
Adder
1.63411764705882371.389
946302AF1-294 E
Adder
3.06352941176470632.604
961672AG1-007 E
Adder
0.63764705882352950.542
943902AF1-058 E
Adder
1.53647058823529431.306
939412AE1-173 E
50/50
90.81590.815
941032AE2-094 E
50/50
29.31329.313
941031AE2-094 C
50/50
65.44965.449
926662AC1-147 E
Adder
1.58705882352941191.349
916192Z1-068 E
50/50
2.2832.283
957492AF2-043 E
Adder
1.63294117647058811.388
923852AB2-025 E
50/50
1.4781.478
3151051BRUNSWICKS1
50/50
27.43527.435
961941AG1-037 C
Adder
0.60235294117647060.512
961942AG1-037 E
Adder
0.401176470588235360.341
936262AD2-033 E
Adder
9.6941176470588258.24
958211AF2-115 C
Adder
2.21.87
934321AD1-056 C
Adder
7.5647058823529416.43
934331AD1-057 C
Adder
4.2200000000000013.587
934332AD1-057 E
Adder
2.19764705882352951.868
934322AD1-056 E
Adder
4.1035294117647063.488
927022AC1-189 E
Adder
5.0152941176470594.263
925595AC1-034 E
Adder
6.0094117647058825.108
919152AA1-139 E1
50/50
5.0025.002
316018AA1-139 ULT2
50/50
1.3241.324
942342AE2-247 E
Adder
2.21411764705882331.882
920042AA2-088 E OP
Adder
12.54941176470588210.667
934511AD1-075 C
Adder
10.0447058823529418.538
934521AD1-076 C
Adder
14.59176470588235512.403
3145723EMPORIA
Adder
0.53176470588235290.452
923573AB1-173 E OP
Adder
4.0258823529411773.422
919692AA2-053 E OP
Adder
5.1235294117647064.355
925785AC1-054 E
Adder
4.20352941176470553.573
959311AF2-222 C
Adder
19.16941176470588516.294
316263AC1-034 C
Adder
7.9670588235294126.772
926755AC1-161 E
50/50
19.76119.761
933291AC2-141 C
50/50
46.29246.292
925522AC1-027 E
50/50
1.4771.477
957872AF2-081 E
50/50
5.2425.242
3145256KINGFORK
Adder
1.08117647058823540.919
941102AE2-104 E
Adder
6.03176470588235255.127
964242AG1-285 E
Adder
10.6682352941176479.068
926214AC1-099 E
Adder
1.4517647058823531.234
932632AC2-084 E
Adder
3.88470588235294123.302
924162AB2-060 E OP
Adder
5.1964705882352944.417
964792AG1-342 E
Adder
2.84000000000000032.414
932763AC2-100 E
Adder
3.01647058823529422.564
939411AE1-173 C
50/50
136.223136.223
913392Y1-086 E
Adder
2.65411764705882322.256
3137643SOCKMAN
Adder
0.86941176470588230.739
937481AD2-202 C
50/50
0.4890.489
919710AA2-057 E
Adder
4.7729411764705894.057
942001AE2-212 C
Adder
1.681.428
939192AE1-149 E
Adder
6.6282352941176485.634
934065AD1-033 E
50/50
6.1776.177
939312AE1-162 E
Adder
1.42235294117647081.209
937226AE2-253 E
50/50
7.1687.168
3151031BRUNSWICKG2
50/50
13.20613.206
924517AB2-100 E2
50/50
3.5953.595
934501AD1-074 C
Adder
40.1776470588235334.151
957482AF2-042 E
50/50
50.15450.154
934621AD1-088 C
50/50
12.41612.416
935172AD1-152 E
50/50
7.1147.114
946301AF1-294 C
Adder
3.617647058823533.075
942461AE2-259 C
Adder
8.3541176470588237.101
961671AG1-007 C
Adder
1.12470588235294120.956
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.51924.519
NYPJM->LTFIMP_NY
CLTF
1.7391.739
TVALTFEXP_TVA->PJM
CLTF
6.746.74
O66PJM->LTFIMP_O-066
CMTX_NF
23.68623.686
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.88431.884
G-007PJM->LTFIMP_G-007
CMTX_NF
3.7193.719
CPLELTFEXP_CPLE->PJM
CLTF
14.15314.153
SIGELTFEXP_SIGE->PJM
CLTF
0.2520.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
115.14115.14
WECLTFEXP_WEC->PJM
CLTF
0.6630.663
LAGNLTFEXP_LAGN->PJM
CLTF
8.6318.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
1.2571.257
MECLTFEXP_MEC->PJM
CLTF
4.1564.156
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.7456.745

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.13 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3353.36
MW Contribution:3.77
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3493.11
MW Contribution:3.47
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938532AE1-072 E
50/50
10.34610.346
3146326AYDLETT TAP
50/50
1.5311.531
943461AF1-017 C
Adder
1.40235294117647061.192
316311AC2-079 C
Adder
5.9964705882352955.097
932596AC2-079 E
Adder
9.7835294117647078.316
3152431Z1-086 GT3
50/50
15.81115.811
3152441Z1-086 ST
50/50
27.53227.532
917122Z2-027 E
50/50
1.5121.512
920692AA2-178 E
Adder
4.6352941176470593.94
966622AG1-532 E
50/50
1.0851.085
3147133PAMPLIN
Adder
0.89882352941176480.764
922923AB1-081 E OP
Adder
4.20470588235294153.574
927264AC1-222 E
Adder
4.3282352941176473.679
940641AE2-051 C
50/50
26.11526.115
316084AB2-161 E
Adder
5.26941176470588254.479
3145946PLYMOUTH TP
Adder
0.364705882352941160.31
933982AD1-022 E
Adder
5.3847058823529414.577
934622AD1-088 E
50/50
5.5555.555
934611AD1-087 C
50/50
1.5661.566
934612AD1-087 E
50/50
4.5174.517
927146AC1-208 E
Adder
4.5541176470588243.871
927255AC1-221 E
Adder
4.1411764705882363.52
932046AC2-012 E
50/50
14.50114.501
316017AA1-139 ULT1
50/50
1.2231.223
938531AE1-072 C
50/50
19.84719.847
958161AF2-110 C
Adder
1.49647058823529421.272
3152411Z1-086 GT1
50/50
15.81615.816
3152421Z1-086 GT2
50/50
15.81115.811
3145393UNCAMP
Adder
6.7635294117647065.749
933981AD1-022 C
Adder
9.8917647058823528.408
900672V4-068 E
Adder
0.402352941176470640.342
924302AB2-077 E O1
Adder
1.52117647058823541.293
316375AC2-012 C
50/50
1.4951.495
961611AG1-000B C
Adder
13.21058823529411611.229
313526AB2-022 C
50/50
0.4240.424
940541AE2-040 C
50/50
3.4343.434
940482AE2-033 E
50/50
13.01513.015
940481AE2-033 C
50/50
19.30519.305
923263AB1-132 E OP
Adder
7.0270588235294125.973
925612AC1-036 E
Adder
0.93294117647058830.793
924312AB2-078 E O1
Adder
1.52117647058823541.293
926274AC1-105 E
Adder
2.9882352941176472.54
944011AF1-069 C
50/50
19.88619.886
3151091ELIZAR2
50/50
3.4943.494
3151081ELIZAR1
50/50
3.5563.556
941591AE2-156 C
50/50
19.83519.835
944591AF1-124 C
50/50
51.55751.557
944601AF1-125 C
50/50
50.58350.583
316316AC1-027 C
50/50
0.3530.353
936666AD2-085 E
Adder
5.8329411764705884.958
963041AG1-153 C
50/50
8.3218.321
938771AE1-103 C
Adder
3.24823529411764732.761
3145413WATKINS
Adder
0.7717647058823530.656
960081AF2-299 C
50/50
2.1712.171
926072AC1-086 E
Adder
10.9894117647058819.341
3151531CLOVER1
50/50
15.90415.904
936261AD2-033 C
Adder
13.51176470588235311.485
961791AG1-021 C
Adder
1.63058823529411771.386
962562AG1-105 E
Adder
6.6470588235294125.65
944012AF1-069 E
50/50
7.7257.725
316315AB2-025 C
50/50
0.4880.488
946282AF1-292 E
50/50
1.1981.198
3138533PONTONDP
Adder
0.60352941176470590.513
917512Z2-088 E OP1
Adder
5.5247058823529414.696
3151101ELIZAR3
50/50
3.6013.601
944582AF1-123 E
50/50
117.641117.641
944592AF1-124 E
50/50
118.067118.067
935112AD1-144 E
Adder
0.98941176470588230.841
316349AD2-085 C
Adder
3.5752941176470593.039
923832AB2-022 E
50/50
1.3981.398
963042AG1-153 E
50/50
12.48112.481
938772AE1-103 E
Adder
4.4858823529411773.813
916042Z1-036 E
Adder
32.1705882352941227.345
316023AB2-100 C2
50/50
1.1231.123
946281AF1-292 C
50/50
1.7971.797
960082AF2-299 E
50/50
1.4471.447
926071AC1-086 C
Adder
24.1447058823529420.523
3151541CLOVER2
50/50
15.75715.757
964241AG1-285 C
50/50
14.87614.876
958212AF2-115 E
Adder
1.73647058823529421.476
927021AC1-189 C
Adder
9.4905882352941178.067
962561AG1-105 C
Adder
9.9705882352941188.475
924152AB2-059 E OP
Adder
5.9564705882352945.063
3143316POE
Adder
1.30823529411764721.112
939191AE1-149 C
Adder
9.5941176470588238.155
901082W1-029 E
Adder
35.7705882352941230.405
316365AB2-100 C1
50/50
1.1231.123
926206AC1-098 E
Adder
4.1470588235294123.525
935171AD1-152 C
50/50
1.6091.609
964791AG1-342 C
Adder
3.96470588235294133.37
933292AC2-141 E
50/50
14.89414.894
316294AC1-161 C
50/50
5.7015.701
944602AF1-125 E
50/50
115.795115.795
916191Z1-068 C
50/50
0.0490.049
3145506HICKORY
50/50
2.4672.467
934576AD1-082 E
Adder
4.1988235294117653.569
957871AF2-081 C
50/50
11.29311.293
943612AF1-032 E
Adder
1.02823529411764710.874
940492AE2-034 E
Adder
3.4764705882352942.955
934522AD1-076 E
Adder
7.045.984
943172AE2-346 E
Adder
0.68588235294117650.583
918492AA1-063AE OP
Adder
4.65058823529411753.953
937482AD2-202 E
50/50
1.3221.322
917332KELFORD E
Adder
1.8635294117647061.584
925122AB2-169 E
Adder
6.4858823529411775.513
316274AC1-208 C
Adder
10.255294117647068.717
961792AG1-021 E
Adder
1.38941176470588231.181
917342Z2-044 E
Adder
0.6764705882352940.575
3151311EDGECMA
Adder
17.50705882352941214.881
940642AE2-051 E
50/50
17.4117.41
316388AE2-253 GEN
50/50
2.2212.221
919153AA1-139 E2
50/50
4.6184.618
943462AF1-017 E
Adder
2.2870588235294121.944
942341AE2-247 C
Adder
1.54941176470588231.317
958162AF2-110 E
Adder
2.38000000000000032.023
924516AB2-100 E1
50/50
3.3843.384
934512AD1-075 E
Adder
4.844.114
934502AD1-074 E
Adder
19.3616.456
966621AG1-532 C
50/50
1.6281.628
918512AA1-065 E OP
Adder
6.2505882352941175.313
3147223TWITTYS
Adder
1.03411764705882360.879
959312AF2-222 E
Adder
11.9210.132
924022AB2-043 E O1
Adder
5.9035294117647065.018
918532AA1-067 E
Adder
0.80588235294117660.685
944581AF1-123 C
50/50
51.37451.374
316185AD1-033 C
50/50
1.391.39
941101AE2-104 C
Adder
3.66705882352941173.117
316320Y1-086 C
50/50
0.2480.248
3151041BRUNSWICKG3
50/50
12.28212.282
3151021BRUNSWICKG1
50/50
12.28212.282
957481AF2-042 C
50/50
69.9469.94
316088AB2-174 E
50/50
7.5427.542
316141AB2-099 E
Adder
0.28588235294117650.243
923994AB2-040_E
Adder
7.1047058823529416.039
924322AB2-079 E O1
Adder
1.52117647058823541.293
946302AF1-294 E
Adder
2.83882352941176472.413
961672AG1-007 E
Adder
0.60.51
943902AF1-058 E
Adder
1.42941176470588241.215
939412AE1-173 E
50/50
85.77785.777
941032AE2-094 E
50/50
27.25927.259
941031AE2-094 C
50/50
60.86460.864
926662AC1-147 E
Adder
1.46588235294117641.246
916192Z1-068 E
50/50
2.1052.105
957492AF2-043 E
Adder
1.58117647058823541.344
923852AB2-025 E
50/50
1.3891.389
3151051BRUNSWICKS1
50/50
25.51625.516
961941AG1-037 C
Adder
0.5717647058823530.486
961942AG1-037 E
Adder
0.381176470588235340.324
936262AD2-033 E
Adder
9.0082352941176477.657
958211AF2-115 C
Adder
2.03764705882352941.732
934321AD1-056 C
Adder
7.126.052
934331AD1-057 C
Adder
3.9717647058823533.376
934332AD1-057 E
Adder
2.0682352941176471.758
934322AD1-056 E
Adder
3.86117647058823543.282
927022AC1-189 E
Adder
4.7282352941176474.019
925595AC1-034 E
Adder
5.65058823529411754.803
919152AA1-139 E1
50/50
4.6184.618
316018AA1-139 ULT2
50/50
1.2231.223
942342AE2-247 E
Adder
2.141.819
920042AA2-088 E OP
Adder
11.94941176470588210.157
934511AD1-075 C
Adder
9.507058823529418.081
934521AD1-076 C
Adder
13.81176470588235411.74
3145723EMPORIA
50/50
0.50.5
923573AB1-173 E OP
Adder
3.78941176470588253.221
919692AA2-053 E OP
Adder
4.8352941176470594.11
925785AC1-054 E
Adder
3.94000000000000043.349
959311AF2-222 C
Adder
17.79058823529411615.122
316263AC1-034 C
Adder
7.4894117647058826.366
926755AC1-161 E
50/50
14.89414.894
933291AC2-141 C
50/50
34.8934.89
925522AC1-027 E
50/50
1.3621.362
957872AF2-081 E
50/50
4.844.84
3145256KINGFORK
Adder
1.06588235294117650.906
3150921YORKTN3
Adder
6.2929411764705885.349
941102AE2-104 E
Adder
5.8305882352941184.956
316087AB2-174 C
50/50
1.3621.362
964242AG1-285 E
50/50
9.9189.918
926214AC1-099 E
Adder
1.36941176470588231.164
932632AC2-084 E
Adder
3.66588235294117663.116
924162AB2-060 E OP
Adder
4.8364705882352944.111
964792AG1-342 E
Adder
2.6435294117647062.247
932763AC2-100 E
Adder
2.80941176470588252.388
939411AE1-173 C
50/50
128.665128.665
913392Y1-086 E
50/50
2.4762.476
3137643SOCKMAN
Adder
0.81882352941176460.696
937481AD2-202 C
50/50
0.4540.454
919710AA2-057 E
Adder
4.49411764705882363.82
939192AE1-149 E
Adder
6.3964705882352955.437
934065AD1-033 E
50/50
5.6715.671
939312AE1-162 E
Adder
1.37058823529411771.165
937226AE2-253 E
50/50
6.6066.606
316321Z2-027 C
50/50
0.410.41
3151031BRUNSWICKG2
50/50
12.28212.282
924517AB2-100 E2
50/50
3.3843.384
934501AD1-074 C
Adder
38.0305882352941232.326
957482AF2-042 E
50/50
46.62746.627
934621AD1-088 C
50/50
11.53711.537
935172AD1-152 E
50/50
6.6176.617
946301AF1-294 C
Adder
3.3517647058823532.849
961671AG1-007 C
Adder
1.05882352941176470.9
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
1.1651.165
MECLTFEXP_MEC->PJM
CLTF
3.8563.856
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.3016.301
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.8122.81
NYPJM->LTFIMP_NY
CLTF
1.6611.661
TVALTFEXP_TVA->PJM
CLTF
6.2796.279
O66PJM->LTFIMP_O-066
CMTX_NF
22.61622.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.47229.472
G-007PJM->LTFIMP_G-007
CMTX_NF
3.5513.551
CPLELTFEXP_CPLE->PJM
CLTF
13.22113.221
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234
CBM South 2LTFEXP_CBM-S2->PJM
CBM
107.493107.493
WECLTFEXP_WEC->PJM
CLTF
0.6140.614
LAGNLTFEXP_LAGN->PJM
CLTF
8.048.04

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o AEP_P1-2_242515_248184_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_242515_248184_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:101.33 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3263.39
MW Contribution:4.53
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316233AE1-074 C
50/50
3.0023.002
938532AE1-072 E
50/50
10.01210.012
3146326AYDLETT TAP
50/50
1.4821.482
943461AF1-017 C
Adder
1.45647058823529421.238
316311AC2-079 C
Adder
6.1964705882352955.267
932596AC2-079 E
Adder
10.1105882352941178.594
3152431Z1-086 GT3
50/50
13.73913.739
3152441Z1-086 ST
50/50
23.92423.924
917122Z2-027 E
Adder
1.4682352941176471.248
920692AA2-178 E
Adder
4.5188235294117653.841
966622AG1-532 E
50/50
1.0721.072
3147133PAMPLIN
Adder
1.09058823529411760.927
940641AE2-051 C
50/50
22.59322.593
316084AB2-161 E
Adder
5.8929411764705895.009
316336AC2-165 C
50/50
11.28911.289
3145946PLYMOUTH TP
Adder
0.35529411764705880.302
933982AD1-022 E
Adder
5.257647058823534.469
934622AD1-088 E
50/50
5.4335.433
934611AD1-087 C
50/50
1.4861.486
934612AD1-087 E
50/50
4.2874.287
927146AC1-208 E
Adder
4.463.791
932046AC2-012 E
Adder
14.19882352941176712.069
316017AA1-139 ULT1
50/50
1.1821.182
938531AE1-072 C
50/50
19.20519.205
958161AF2-110 C
Adder
1.48823529411764691.265
3152411Z1-086 GT1
50/50
13.74313.743
3152421Z1-086 GT2
50/50
13.73913.739
3145393UNCAMP
Adder
6.6964705882352955.692
933981AD1-022 C
Adder
9.657647058823538.209
900672V4-068 E
Adder
0.396470588235294130.337
3147043LAWRENC
50/50
0.3540.354
924302AB2-077 E O1
Adder
1.54117647058823541.31
961611AG1-000B C
Adder
15.56000000000000213.226
940541AE2-040 C
50/50
3.383.38
940482AE2-033 E
50/50
12.80912.809
940481AE2-033 C
50/50
1919
316181AB2-040 GEN
50/50
1.4461.446
923263AB1-132 E OP
Adder
6.8941176470588245.86
925612AC1-036 E
Adder
0.99764705882352940.848
924312AB2-078 E O1
Adder
1.54117647058823541.31
926274AC1-105 E
Adder
2.9811764705882352.534
944011AF1-069 C
50/50
17.13917.139
3151081ELIZAR1
50/50
3.4743.474
941591AE2-156 C
Adder
19.4082352941176516.497
944591AF1-124 C
50/50
49.76549.765
944601AF1-125 C
50/50
48.82548.825
316316AC1-027 C
50/50
0.3440.344
936666AD2-085 E
Adder
6.062352941176475.153
963041AG1-153 C
50/50
7.2587.258
938771AE1-103 C
Adder
3.2188235294117652.736
3145413WATKINS
Adder
0.76352941176470590.649
960081AF2-299 C
50/50
2.1442.144
926072AC1-086 E
Adder
10.782352941176479.165
3151531CLOVER1
50/50
15.09415.094
936261AD2-033 C
Adder
14.6612.461
961791AG1-021 C
Adder
1.95529411764705881.662
962562AG1-105 E
Adder
6.6752941176470595.674
944012AF1-069 E
50/50
6.6586.658
316315AB2-025 C
50/50
0.480.48
946282AF1-292 E
50/50
1.1831.183
3138533PONTONDP
Adder
0.72470588235294120.616
3151101ELIZAR3
50/50
3.5183.518
944582AF1-123 E
50/50
113.553113.553
944592AF1-124 E
50/50
113.964113.964
935112AD1-144 E
Adder
0.99764705882352940.848
316349AD2-085 C
Adder
3.7152941176470593.158
923832AB2-022 E
Adder
1.3564705882352941.153
963042AG1-153 E
50/50
10.88710.887
316258AE1-075 C
50/50
0.4170.417
938772AE1-103 E
Adder
4.4447058823529423.778
916042Z1-036 E
Adder
31.33529411764706326.635
316023AB2-100 C2
50/50
1.1041.104
3143316POE
50/50
1.5031.503
939191AE1-149 C
Adder
11.3364705882352949.636
901082W1-029 E
Adder
34.83647058823529429.611
316365AB2-100 C1
50/50
1.1041.104
926206AC1-098 E
Adder
4.06000000000000053.451
935171AD1-152 C
50/50
1.5411.541
942462AE2-259 E
Adder
6.9823529411764715.935
964791AG1-342 C
Adder
3.9741176470588243.378
933292AC2-141 E
50/50
14.05414.054
316294AC1-161 C
50/50
5.385.38
944602AF1-125 E
50/50
111.771111.771
916191Z1-068 C
50/50
0.0480.048
3145506HICKORY
50/50
2.3832.383
934576AD1-082 E
Adder
4.6952941176470593.991
957871AF2-081 C
50/50
10.92110.921
943612AF1-032 E
Adder
1.00588235294117640.855
316313AB2-026 C
50/50
0.4550.455
940492AE2-034 E
Adder
3.3894117647058822.881
934522AD1-076 E
Adder
6.8694117647058835.839
943172AE2-346 E
Adder
0.67176470588235290.571
918492AA1-063AE OP
Adder
4.5788235294117653.892
937482AD2-202 E
50/50
1.2551.255
917332KELFORD E
Adder
1.82470588235294121.551
925122AB2-169 E
Adder
6.3270588235294125.378
316274AC1-208 C
Adder
10.0447058823529418.538
961792AG1-021 E
Adder
1.66588235294117641.416
917342Z2-044 E
Adder
0.660.561
940642AE2-051 E
50/50
15.06215.062
316388AE2-253 GEN
50/50
2.1472.147
919153AA1-139 E2
50/50
4.4664.466
943462AF1-017 E
Adder
2.37764705882352922.021
942341AE2-247 C
Adder
1.61058823529411771.369
958162AF2-110 E
Adder
2.3670588235294122.012
924516AB2-100 E1
50/50
3.3273.327
934512AD1-075 E
Adder
4.7223529411764714.014
934502AD1-074 E
Adder
18.89058823529411816.057
966621AG1-532 C
50/50
1.6081.608
918512AA1-065 E OP
Adder
6.1129411764705885.196
3147223TWITTYS
Adder
1.10588235294117650.94
959312AF2-222 E
Adder
12.90117647058823510.966
924022AB2-043 E O1
Adder
5.9905882352941175.092
918532AA1-067 E
Adder
0.78588235294117660.668
942002AE2-212 E
Adder
1.46470588235294131.245
940431AE2-027 C
Adder
2.3247058823529411.976
944581AF1-123 C
50/50
49.58949.589
316185AD1-033 C
50/50
1.3431.343
941101AE2-104 C
Adder
3.6470588235294123.1
3151041BRUNSWICKG3
50/50
10.71310.713
3151021BRUNSWICKG1
50/50
10.71310.713
316405AF2-144 C
50/50
0.3540.354
957481AF2-042 C
50/50
65.35965.359
316088AB2-174 E
50/50
7.4387.438
316141AB2-099 E
Adder
0.279999999999999970.238
923994AB2-040_E
50/50
7.0037.003
313506AB1-173 C OP
50/50
1.2841.284
924322AB2-079 E O1
Adder
1.54117647058823541.31
946302AF1-294 E
Adder
3.40470588235294122.894
943902AF1-058 E
Adder
1.41882352941176461.206
946281AF1-292 C
50/50
1.7741.774
960082AF2-299 E
50/50
1.4291.429
926071AC1-086 C
Adder
23.6894117647058820.136
3151541CLOVER2
50/50
14.95414.954
964241AG1-285 C
50/50
14.99914.999
958212AF2-115 E
Adder
2.08235294117647071.77
927021AC1-189 C
Adder
9.2541176470588237.866
962561AG1-105 C
Adder
10.0129411764705878.511
3150831SPRUNCA
Adder
9.0235294117647067.67
3150841SPRUNCB
Adder
9.0235294117647067.67
939412AE1-173 E
50/50
75.86375.863
941032AE2-094 E
50/50
23.49323.493
941031AE2-094 C
50/50
52.45552.455
926662AC1-147 E
Adder
1.43529411764705881.22
916192Z1-068 E
50/50
2.0462.046
957492AF2-043 E
Adder
1.54705882352941181.315
923852AB2-025 E
50/50
1.3671.367
3151051BRUNSWICKS1
50/50
22.25722.257
923862AB2-026 E
50/50
1.4721.472
961941AG1-037 C
Adder
0.55999999999999990.476
961942AG1-037 E
Adder
0.37294117647058830.317
936262AD2-033 E
Adder
9.7729411764705898.307
958211AF2-115 C
Adder
2.4447058823529412.078
934321AD1-056 C
Adder
6.9588235294117655.915
934331AD1-057 C
Adder
3.88235294117647063.3
934332AD1-057 E
Adder
2.0211764705882351.718
934322AD1-056 E
Adder
3.7752941176470593.209
927022AC1-189 E
Adder
4.6094117647058823.918
919152AA1-139 E1
50/50
4.4664.466
316018AA1-139 ULT2
50/50
1.1821.182
942342AE2-247 E
Adder
2.2235294117647061.89
920042AA2-088 E OP
Adder
11.78823529411764610.02
934511AD1-075 C
Adder
9.2764705882352957.885
934521AD1-076 C
Adder
13.47647058823529411.455
3145723EMPORIA
50/50
0.4940.494
923573AB1-173 E OP
50/50
3.7353.735
919692AA2-053 E OP
Adder
4.7517647058823534.039
925785AC1-054 E
Adder
3.88823529411764753.305
959311AF2-222 C
Adder
19.2552941176470616.367
938552AE1-074 E
50/50
1.5121.512
926755AC1-161 E
50/50
14.05414.054
933291AC2-141 C
50/50
32.92332.923
925522AC1-027 E
50/50
1.3251.325
957872AF2-081 E
50/50
4.6814.681
3145256KINGFORK
Adder
1.07411764705882360.913
941102AE2-104 E
Adder
5.7988235294117664.929
938562AE1-075 E
50/50
1.2551.255
316087AB2-174 C
50/50
1.3431.343
964242AG1-285 E
50/50
1010
926214AC1-099 E
Adder
1.34117647058823521.14
932632AC2-084 E
Adder
3.58823529411764673.05
924162AB2-060 E OP
Adder
4.9352941176470594.195
964792AG1-342 E
Adder
2.64941176470588242.252
939411AE1-173 C
50/50
113.794113.794
913392Y1-086 E
Adder
2.40235294117647062.042
933502AC2-165 E
50/50
8.4968.496
3137643SOCKMAN
Adder
0.80705882352941180.686
937481AD2-202 C
50/50
0.4310.431
919710AA2-057 E
Adder
4.3929411764705883.734
942001AE2-212 C
Adder
2.19764705882352951.868
939192AE1-149 E
Adder
7.557647058823536.424
934065AD1-033 E
50/50
5.485.48
939312AE1-162 E
Adder
1.46588235294117641.246
937226AE2-253 E
50/50
6.3856.385
3151031BRUNSWICKG2
50/50
10.71310.713
958502AF2-144 E
50/50
1.4471.447
924517AB2-100 E2
50/50
3.3273.327
934501AD1-074 C
Adder
37.1082352941176531.542
957482AF2-042 E
50/50
43.57343.573
934621AD1-088 C
50/50
11.28411.284
935172AD1-152 E
50/50
6.3396.339
946301AF1-294 C
Adder
4.023.417
942461AE2-259 C
Adder
10.4729411764705888.902
316303AF2-085
50/50
5.3815.381
CBM South 2LTFEXP_CBM-S2->PJM
CBM
109.89109.89
WECLTFEXP_WEC->PJM
CLTF
0.8760.876
LAGNLTFEXP_LAGN->PJM
CLTF
9.3749.374
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
1.6941.694
MECLTFEXP_MEC->PJM
CLTF
5.1295.129
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.1846.184
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.02428.024
NYPJM->LTFIMP_NY
CLTF
2.1382.138
TVALTFEXP_TVA->PJM
CLTF
7.4317.431
O66PJM->LTFIMP_O-066
CMTX_NF
29.57929.579
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.40542.405
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6484.648
CPLELTFEXP_CPLE->PJM
CLTF
12.96712.967
SIGELTFEXP_SIGE->PJM
CLTF
0.3240.324

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.69 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4423.71
MW Contribution:7.15
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:114.82 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4673.36
MW Contribution:6.11
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3152431Z1-086 GT3
50/50
32.41332.413
3152441Z1-086 ST
50/50
56.44256.442
3147133PAMPLIN
50/50
1.8091.809
927264AC1-222 E
50/50
8.2018.201
940641AE2-051 C
Adder
-21.288235294117648-18.095
934622AD1-088 E
50/50
11.49611.496
934611AD1-087 C
50/50
3.233.23
934612AD1-087 E
50/50
9.3199.319
3151611KERR 4
50/50
1.991.99
927255AC1-221 E
50/50
7.6147.614
938531AE1-072 C
Adder
-16.06705882352941-13.657
3152411Z1-086 GT1
50/50
32.42432.424
3152421Z1-086 GT2
50/50
32.41332.413
924302AB2-077 E O1
50/50
2.6052.605
3151621KERR 5
50/50
1.991.99
316222AC1-221 C
50/50
2.9122.912
942752AE2-291 E
Adder
8.6882352941176467.385
925612AC1-036 E
50/50
1.8171.817
316237AB2-079 C O1
50/50
0.6390.639
924312AB2-078 E O1
50/50
2.6052.605
316238AB2-078 C O1
50/50
0.6390.639
926274AC1-105 E
50/50
5.5465.546
944011AF1-069 C
50/50
39.18539.185
963041AG1-153 C
50/50
17.36617.366
3151531CLOVER1
50/50
32.82832.828
936261AD2-033 C
50/50
24.11624.116
3151631KERR 6
50/50
1.991.99
961791AG1-021 C
Adder
3.08941176470588232.626
962562AG1-105 E
50/50
11.97711.977
924032AB2-045 E
Adder
1.26941176470588221.079
316248AF1-058 C
50/50
0.6640.664
936171AD2-023 C
Adder
7.246.154
944012AF1-069 E
50/50
15.22215.222
316131AB2-060 C
50/50
2.8942.894
3138533PONTONDP
Adder
1.14470588235294120.973
316118AC1-105 C
50/50
1.8951.895
963042AG1-153 E
50/50
26.04926.049
3151541CLOVER2
50/50
32.52432.524
964241AG1-285 C
50/50
28.57228.572
316034AC1-036 C
50/50
0.4960.496
958212AF2-115 E
Adder
3.2894117647058822.796
962561AG1-105 C
50/50
17.96517.965
936172AD2-023 E
Adder
3.9305882352941183.341
957601AF2-054 C
Adder
-1.72-1.462
316239AB2-077 C O1
50/50
0.6390.639
935171AD1-152 C
50/50
3.2363.236
942462AE2-259 E
Adder
10.6764705882352939.075
964791AG1-342 C
50/50
7.2097.209
925997AC1-075 E
Adder
5.1705882352941174.395
937482AD2-202 E
50/50
2.7272.727
3151581KERR 1
50/50
0.7110.711
3151601KERR 3
50/50
1.991.99
961792AG1-021 E
Adder
2.6317647058823532.237
3152661PLYWOOD A
50/50
2.4812.481
3147223TWITTYS
50/50
2.0152.015
959312AF2-222 E
50/50
23.29123.291
924022AB2-043 E O1
50/50
10.1410.14
316003AC1-222 C
50/50
2.0082.008
926024AC1-080 E
Adder
1.71529411764705891.458
936161AD2-022 C
Adder
12.41176470588235310.55
3151041BRUNSWICKG3
50/50
25.63425.634
3151021BRUNSWICKG1
50/50
25.63425.634
957481AF2-042 C
50/50
147.496147.496
924322AB2-079 E O1
50/50
2.6052.605
946302AF1-294 E
Adder
5.377647058823534.571
943902AF1-058 E
50/50
2.7082.708
24401205PINNACLE
Adder
1.62588235294117631.382
941032AE2-094 E
50/50
53.71353.713
941031AE2-094 C
50/50
119.928119.928
3151051BRUNSWICKS1
50/50
53.25453.254
936262AD2-033 E
50/50
16.07816.078
958211AF2-115 C
Adder
3.86117647058823543.282
316240AF1-291 C
Adder
-1.863529411764706-1.584
944641AF1-129 C
Adder
-87.13882352941177-74.068
925785AC1-054 E
Adder
3.75647058823529443.193
959311AF2-222 C
50/50
34.76234.762
942751AE2-291 C
Adder
13.03294117647058811.078
933291AC2-141 C
Adder
-31.96117647058824-27.167
964242AG1-285 E
50/50
19.04819.048
313527AB2-043 C
50/50
1.011.01
924162AB2-060 E OP
50/50
8.3338.333
3151591KERR 2
50/50
1.991.99
964792AG1-342 E
50/50
4.8064.806
932763AC2-100 E
50/50
5.1295.129
316283AC2-100 C
50/50
2.3312.331
937481AD2-202 C
50/50
0.9370.937
3151641KERR 7
50/50
1.991.99
942001AE2-212 C
Adder
-1.9541176470588235-1.661
3151031BRUNSWICKG2
50/50
25.63425.634
957482AF2-042 E
50/50
98.33198.331
934621AD1-088 C
50/50
23.87723.877
935172AD1-152 E
50/50
13.31413.314
946301AF1-294 C
Adder
6.3505882352941185.398
942461AE2-259 C
Adder
16.0152941176470613.613
936162AD2-022 E
Adder
7.4470588235294126.33
CBM South 2LTFEXP_CBM-S2->PJM
CBM
169.426169.426
WECLTFEXP_WEC->PJM
CLTF
1.2081.208
LAGNLTFEXP_LAGN->PJM
CLTF
13.6813.68
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
2.2642.264
MECLTFEXP_MEC->PJM
CLTF
7.1897.189
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.4399.439
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.12440.124
NYPJM->LTFIMP_NY
CLTF
1.8831.883
TVALTFEXP_TVA->PJM
CLTF
10.7110.71
O66PJM->LTFIMP_O-066
CMTX_NF
26.2626.26
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.04159.041
G-007PJM->LTFIMP_G-007
CMTX_NF
4.1284.128
CPLELTFEXP_CPLE->PJM
CLTF
19.79519.795
SIGELTFEXP_SIGE->PJM
CLTF
0.4430.443

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.0 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2588.61
MW Contribution:3.08
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.54 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2748.4
MW Contribution:2.87
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938532AE1-072 E
50/50
8.5488.548
3146326AYDLETT TAP
Adder
1.25647058823529421.068
3152431Z1-086 GT3
50/50
12.4512.45
3152441Z1-086 ST
50/50
21.68121.681
917122Z2-027 E
Adder
1.1117647058823530.945
920692AA2-178 E
Adder
3.0870588235294122.624
966622AG1-532 E
Adder
0.76941176470588240.654
3147133PAMPLIN
Adder
0.740.629
922923AB1-081 E OP
Adder
2.9811764705882352.534
927264AC1-222 E
Adder
3.3870588235294122.879
940641AE2-051 C
50/50
26.4726.47
3145946PLYMOUTH TP
Adder
0.24117647058823530.205
933982AD1-022 E
Adder
3.52470588235294142.996
934622AD1-088 E
50/50
4.4114.411
934611AD1-087 C
50/50
1.2361.236
934612AD1-087 E
50/50
3.5653.565
927146AC1-208 E
Adder
3.14470588235294152.673
927255AC1-221 E
Adder
3.2152941176470592.733
932046AC2-012 E
50/50
12.1712.17
316017AA1-139 ULT1
50/50
1.0281.028
938531AE1-072 C
50/50
16.39816.398
3152411Z1-086 GT1
50/50
12.45512.455
3152421Z1-086 GT2
50/50
12.4512.45
3145393UNCAMP
Adder
3.8517647058823533.274
933981AD1-022 C
Adder
6.4741176470588245.503
900672V4-068 E
Adder
0.254117647058823560.216
924302AB2-077 E O1
Adder
1.18705882352941171.009
316375AC2-012 C
50/50
1.2551.255
940541AE2-040 C
Adder
2.4364705882352942.071
940482AE2-033 E
Adder
9.2211764705882357.838
940481AE2-033 C
Adder
13.6776470588235311.626
923263AB1-132 E OP
Adder
4.8517647058823534.124
925612AC1-036 E
Adder
0.74705882352941180.635
924312AB2-078 E O1
Adder
1.18705882352941171.009
926274AC1-105 E
Adder
2.3364705882352941.986
944011AF1-069 C
50/50
15.67315.673
3151091ELIZAR2
50/50
2.9782.978
3151081ELIZAR1
50/50
3.033.03
941591AE2-156 C
50/50
16.7516.75
944591AF1-124 C
50/50
45.80645.806
944601AF1-125 C
50/50
44.94144.941
316316AC1-027 C
50/50
0.3010.301
963041AG1-153 C
50/50
6.556.55
938771AE1-103 C
Adder
1.81647058823529431.544
3145413WATKINS
Adder
0.451764705882352960.384
960081AF2-299 C
Adder
1.541.309
926072AC1-086 E
Adder
7.5870588235294126.449
3151531CLOVER1
50/50
12.55212.552
936261AD2-033 C
Adder
10.7294117647058829.12
961791AG1-021 C
Adder
1.33058823529411761.131
962562AG1-105 E
Adder
5.1941176470588244.415
944012AF1-069 E
50/50
6.0886.088
946282AF1-292 E
Adder
0.84941176470588230.722
3138533PONTONDP
Adder
0.49294117647058820.419
917512Z2-088 E OP1
Adder
3.83294117647058833.258
3151101ELIZAR3
50/50
3.0693.069
944582AF1-123 E
50/50
104.52104.52
944592AF1-124 E
50/50
104.898104.898
923832AB2-022 E
Adder
1.06823529411764720.908
963042AG1-153 E
50/50
9.8259.825
938772AE1-103 E
Adder
2.50941176470588222.133
916042Z1-036 E
Adder
21.67647058823529718.425
946281AF1-292 C
Adder
1.27411764705882361.083
960082AF2-299 E
Adder
1.02588235294117650.872
926071AC1-086 C
Adder
16.6705882352941214.17
3151541CLOVER2
50/50
12.43612.436
964241AG1-285 C
Adder
11.7588235294117649.995
958212AF2-115 E
Adder
1.41647058823529411.204
927021AC1-189 C
Adder
6.5388235294117655.558
962561AG1-105 C
Adder
7.7917647058823536.623
924152AB2-059 E OP
Adder
4.2235294117647063.59
3143316POE
Adder
0.80823529411764720.687
901082W1-029 E
Adder
23.54352941176470520.012
957601AF2-054 C
Adder
-1.2505882352941176-1.063
926206AC1-098 E
Adder
2.8317647058823532.407
942462AE2-259 E
Adder
4.3564705882352943.703
964791AG1-342 C
Adder
3.09882352941176452.634
933292AC2-141 E
50/50
37.13537.135
316294AC1-161 C
50/50
14.21614.216
944602AF1-125 E
50/50
102.879102.879
916191Z1-068 C
50/50
0.0420.042
3145506HICKORY
50/50
2.1612.161
957871AF2-081 C
50/50
9.4939.493
940492AE2-034 E
Adder
2.3152941176470591.968
934522AD1-076 E
Adder
4.6470588235294123.95
943172AE2-346 E
Adder
0.440.374
918492AA1-063AE OP
Adder
3.0882352941176472.625
937482AD2-202 E
50/50
1.0431.043
917332KELFORD E
Adder
1.2282352941176471.044
925122AB2-169 E
Adder
4.3388235294117653.688
316274AC1-208 C
Adder
7.0835294117647066.021
961792AG1-021 E
Adder
1.13294117647058810.963
917342Z2-044 E
Adder
0.475294117647058870.404
3151311EDGECMA
Adder
12.4152941176470610.553
940642AE2-051 E
50/50
17.64717.647
316388AE2-253 GEN
50/50
1.8981.898
919153AA1-139 E2
50/50
3.8823.882
924516AB2-100 E1
Adder
2.3717647058823532.016
934512AD1-075 E
Adder
3.19529411764705932.716
934502AD1-074 E
Adder
12.7810.863
966621AG1-532 C
Adder
1.15411764705882350.981
918512AA1-065 E OP
Adder
3.98941176470588273.391
3147223TWITTYS
Adder
0.82823529411764710.704
959312AF2-222 E
Adder
9.5670588235294118.132
924022AB2-043 E O1
Adder
4.6082352941176473.917
918532AA1-067 E
Adder
0.54705882352941180.465
944581AF1-123 C
50/50
45.64445.644
316185AD1-033 C
50/50
1.2261.226
3151041BRUNSWICKG3
50/50
9.6689.668
3151021BRUNSWICKG1
50/50
9.6689.668
957481AF2-042 C
50/50
55.26355.263
316088AB2-174 E
Adder
5.3035294117647064.508
316141AB2-099 E
Adder
0.183529411764705890.156
923994AB2-040_E
Adder
4.9776470588235294.231
924322AB2-079 E O1
Adder
1.18705882352941171.009
946302AF1-294 E
Adder
2.3164705882352941.969
961672AG1-007 E
Adder
0.41882352941176470.356
943902AF1-058 E
Adder
1.11882352941176480.951
939412AE1-173 E
50/50
57.94757.947
941032AE2-094 E
50/50
21.48321.483
941031AE2-094 C
50/50
47.96747.967
926662AC1-147 E
Adder
1.23058823529411781.046
916192Z1-068 E
50/50
1.7941.794
923852AB2-025 E
Adder
0.98588235294117640.838
3151051BRUNSWICKS1
50/50
20.08620.086
961941AG1-037 C
Adder
0.367058823529411770.312
961942AG1-037 E
Adder
0.244705882352941160.208
936262AD2-033 E
Adder
7.1529411764705896.08
958211AF2-115 C
Adder
1.6635294117647061.414
934321AD1-056 C
Adder
4.99411764705882364.245
934331AD1-057 C
Adder
2.78588235294117632.368
934332AD1-057 E
Adder
1.45058823529411771.233
934322AD1-056 E
Adder
2.70941176470588242.303
927022AC1-189 E
Adder
3.25764705882352962.769
925595AC1-034 E
Adder
4.00588235294117643.405
919152AA1-139 E1
50/50
3.8823.882
316018AA1-139 ULT2
50/50
1.0281.028
920042AA2-088 E OP
Adder
7.3835294117647066.276
934511AD1-075 C
Adder
6.2764705882352945.335
934521AD1-076 C
Adder
9.1176470588235297.75
3145723EMPORIA
Adder
0.352941176470588260.3
923573AB1-173 E OP
Adder
2.65411764705882322.256
919692AA2-053 E OP
Adder
3.30000000000000032.805
925785AC1-054 E
Adder
2.882.448
959311AF2-222 C
Adder
14.27882352941176512.137
316263AC1-034 C
Adder
5.31058823529411854.514
926755AC1-161 E
50/50
37.13537.135
933291AC2-141 C
50/50
86.99486.994
925522AC1-027 E
50/50
1.1581.158
957872AF2-081 E
50/50
4.0684.068
964242AG1-285 E
Adder
7.846.664
926214AC1-099 E
Adder
0.93529411764705890.795
932632AC2-084 E
Adder
2.50352941176470622.128
924162AB2-060 E OP
Adder
3.78117647058823543.214
964792AG1-342 E
Adder
2.06588235294117651.756
932763AC2-100 E
Adder
2.1788235294117651.852
939411AE1-173 C
50/50
86.92186.921
913392Y1-086 E
Adder
1.8917647058823531.608
3137643SOCKMAN
Adder
0.56941176470588240.484
937481AD2-202 C
50/50
0.3590.359
919710AA2-057 E
Adder
3.1364705882352942.666
934065AD1-033 E
50/50
5.0045.004
937226AE2-253 E
50/50
5.6435.643
3151031BRUNSWICKG2
50/50
9.6689.668
924517AB2-100 E2
Adder
2.3717647058823532.016
934501AD1-074 C
Adder
25.10470588235294221.339
957482AF2-042 E
50/50
36.84236.842
934621AD1-088 C
50/50
9.1619.161
935172AD1-152 E
Adder
5.2058823529411774.425
946301AF1-294 C
Adder
2.73529411764705932.325
942461AE2-259 C
Adder
6.5341176470588245.554
961671AG1-007 C
Adder
0.73882352941176480.628
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.65881.658
WECLTFEXP_WEC->PJM
CLTF
0.5060.506
LAGNLTFEXP_LAGN->PJM
CLTF
6.2356.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.950.95
MECLTFEXP_MEC->PJM
CLTF
3.1033.103
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.7574.757
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.91517.915
NYPJM->LTFIMP_NY
CLTF
0.9860.986
TVALTFEXP_TVA->PJM
CLTF
4.8674.867
O66PJM->LTFIMP_O-066
CMTX_NF
13.52713.527
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.52724.527
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1242.124
CPLELTFEXP_CPLE->PJM
CLTF
9.989.98
SIGELTFEXP_SIGE->PJM
CLTF
0.1890.189

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.93 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4311.69
MW Contribution:6.22
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.26 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4569.37
MW Contribution:5.34
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3152431Z1-086 GT3
50/50
33.83433.834
3152441Z1-086 ST
50/50
58.91758.917
3147133PAMPLIN
50/50
1.5711.571
927264AC1-222 E
50/50
7.2547.254
940641AE2-051 C
Adder
-20.06823529411765-17.058
934622AD1-088 E
50/50
10.02610.026
934611AD1-087 C
50/50
2.8252.825
934612AD1-087 E
50/50
8.158.15
3151611KERR 4
50/50
1.7561.756
927255AC1-221 E
50/50
6.8776.877
938531AE1-072 C
Adder
-15.17764705882353-12.901
3152411Z1-086 GT1
50/50
33.84633.846
3152421Z1-086 GT2
50/50
33.83433.834
924302AB2-077 E O1
50/50
2.2822.282
3151621KERR 5
50/50
1.7561.756
316222AC1-221 C
50/50
2.632.63
942752AE2-291 E
Adder
7.7105882352941186.554
925612AC1-036 E
50/50
1.5841.584
316237AB2-079 C O1
50/50
0.5590.559
924312AB2-078 E O1
50/50
2.2822.282
316238AB2-078 C O1
50/50
0.5590.559
926274AC1-105 E
50/50
4.8944.894
944011AF1-069 C
50/50
45.64245.642
963041AG1-153 C
50/50
17.20617.206
3151531CLOVER1
50/50
28.70728.707
936261AD2-033 C
50/50
21.05721.057
3151631KERR 6
50/50
1.7561.756
961791AG1-021 C
Adder
2.68823529411764732.285
962562AG1-105 E
50/50
10.53610.536
316248AF1-058 C
50/50
0.5870.587
936171AD2-023 C
Adder
6.8564705882352955.828
944012AF1-069 E
50/50
17.73117.731
316131AB2-060 C
50/50
2.5322.532
3138533PONTONDP
Adder
0.99529411764705880.846
316118AC1-105 C
50/50
1.6721.672
963042AG1-153 E
50/50
25.80825.808
3151541CLOVER2
50/50
28.44128.441
964241AG1-285 C
50/50
24.94424.944
316034AC1-036 C
50/50
0.4320.432
958212AF2-115 E
Adder
2.86235294117647052.433
962561AG1-105 C
50/50
15.80415.804
936172AD2-023 E
Adder
3.7223529411764713.164
957601AF2-054 C
Adder
-1.6305882352941177-1.386
316239AB2-077 C O1
50/50
0.5590.559
935171AD1-152 C
50/50
2.8452.845
942462AE2-259 E
Adder
9.2458823529411777.859
964791AG1-342 C
50/50
6.3476.347
925997AC1-075 E
Adder
4.5835294117647063.896
937482AD2-202 E
50/50
2.3852.385
3151581KERR 1
50/50
0.6270.627
3151601KERR 3
50/50
1.7561.756
961792AG1-021 E
Adder
2.28941176470588251.946
3152661PLYWOOD A
50/50
2.1912.191
3147223TWITTYS
50/50
1.7561.756
959312AF2-222 E
50/50
20.29620.296
924022AB2-043 E O1
50/50
8.8758.875
316003AC1-222 C
50/50
1.7761.776
926024AC1-080 E
Adder
1.52117647058823541.293
936161AD2-022 C
Adder
11.7541176470588239.991
3151041BRUNSWICKG3
50/50
25.39725.397
3151021BRUNSWICKG1
50/50
25.39725.397
957481AF2-042 C
50/50
128.648128.648
924322AB2-079 E O1
50/50
2.2822.282
946302AF1-294 E
Adder
4.6788235294117653.977
943902AF1-058 E
50/50
2.3942.394
24401205PINNACLE
Adder
1.53647058823529431.306
941032AE2-094 E
50/50
62.56462.564
941031AE2-094 C
50/50
139.691139.691
3151051BRUNSWICKS1
50/50
52.76252.762
936262AD2-033 E
50/50
14.03814.038
958211AF2-115 C
Adder
3.362.856
316240AF1-291 C
Adder
-1.7670588235294118-1.502
944641AF1-129 C
Adder
-82.61058823529412-70.219
925785AC1-054 E
Adder
3.30235294117647052.807
959311AF2-222 C
50/50
30.29330.293
942751AE2-291 C
Adder
11.5670588235294139.832
933291AC2-141 C
Adder
-30.18235294117647-25.655
964242AG1-285 E
50/50
16.62916.629
313527AB2-043 C
50/50
0.8840.884
924162AB2-060 E OP
50/50
7.2927.292
3151591KERR 2
50/50
1.7561.756
964792AG1-342 E
50/50
4.2324.232
932763AC2-100 E
50/50
4.6444.644
316283AC2-100 C
50/50
2.112.11
937481AD2-202 C
50/50
0.820.82
3151641KERR 7
50/50
1.7561.756
942001AE2-212 C
Adder
-1.851764705882353-1.574
3151031BRUNSWICKG2
50/50
25.39725.397
957482AF2-042 E
50/50
85.76685.766
934621AD1-088 C
50/50
20.82320.823
935172AD1-152 E
50/50
11.70511.705
946301AF1-294 C
Adder
5.5247058823529414.696
942461AE2-259 C
Adder
13.86823529411764811.788
936162AD2-022 E
Adder
7.0529411764705895.995
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5656
G-007PJM->LTFIMP_G-007
CMTX_NF
3.9723.972
CPLELTFEXP_CPLE->PJM
CLTF
19.02319.023
SIGELTFEXP_SIGE->PJM
CLTF
0.4210.421
CBM South 2LTFEXP_CBM-S2->PJM
CBM
162.815162.815
WECLTFEXP_WEC->PJM
CLTF
1.1471.147
LAGNLTFEXP_LAGN->PJM
CLTF
13.09813.098
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
2.1482.148
MECLTFEXP_MEC->PJM
CLTF
6.8436.843
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.0719.071
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.3338.33
NYPJM->LTFIMP_NY
CLTF
1.8141.814
TVALTFEXP_TVA->PJM
CLTF
10.24910.249
O66PJM->LTFIMP_O-066
CMTX_NF
25.2725.27
CONTINGENCY 'DVP_P1-2: LN 235_SRT-A'
 OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1   /*6PRINCE EDW  230.0 - 6BRIERY      230.0
 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1   /*6PRINCE EDW  230.0 - 6FARMVIL     230.0
 OPEN BRANCH FROM BUS 313996 TO BUS 314268 CKT 1   /*6FINNEYWOOD  230.0 - 6BRIERY      230.0
 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1   /*3FARMVIL     115.0 - 6FARMVIL     230.0
 OPEN BUS 313802                                   /*6PRINCE EDW  230.0
 OPEN BUS 314268                                   /*6BRIERY      230.0
END
CONTINGENCY 'DVP_P1-2: LN 1045_SRT-A'
 OPEN BRANCH FROM BUS 313898 TO BUS 314267 CKT 1   /*3BUTCHER CRK 115.0 - 3CHASCTY2    115.0
END
CONTINGENCY 'DVP_P1-2: LN 2027_SRT-A-2'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026 C    230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
 OPEN BUS 923862                                   /*AB2-026 E    230.0
 OPEN BUS 938562                                   /*AE1-075 E    230.0
 OPEN BUS 958502                                   /*AF2-144 E    230.0
END
CONTINGENCY 'DVP_P1-2: LN 578_SRT-S-1'
 OPEN BRANCH FROM BUS 314923 TO BUS 314924 CKT 1                /*8SEPTA       500.0 - 8SURRY       500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 940640 TO BUS 314902 CKT 1 /*AE2-051 TP   500.0 - 8CARSON      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 940640 TO BUS 314923 CKT 1 /*AE2-051 TP   500.0 - 8SEPTA       500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 940640 TO BUS 314902 CKT 1 /*AE2-051 TP   500.0 - 8CARSON      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 940640 TO BUS 314923 CKT 1 /*AE2-051 TP   500.0 - 8SEPTA       500.0
END
CONTINGENCY 'AEP_P1-2_242515_248184_SRT-A'
 OPEN BRANCH FROM BUS 242515 TO BUS 248184 CKT 1   /*05JOSHUA     765.0 - 05YEAT7      765.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314691 to 314692 ckt 2
313755 to 314707 ckt 1
314701 to 313755 ckt 1
314707 to 314691 ckt 1
314747 to 313867 ckt 1
313867 to 313707 ckt 1
313373 to 314765 ckt 1
313707 to 313373 ckt 1
314765 to 314749 ckt 1
314902 to 314914 ckt 1
314914 to 314918 ckt 1
314936 to 314902 ckt 1
314923 to 314924 ckt 1
941030 to 314902 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 2201_SRT-A
OPAC111.87 %252.86B282.871.55
GD1DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S-1
OPAC111.78 %1058.16B1182.762.25
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 550_SRT-S
OPAC105.92 %3220.44B3411.034.62
GD1DVP
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
OPAC105.31 %4070.2B4286.275.34

Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 2201_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.87 %
Rating:252.86 MVA
Rating Type:B
MVA to Mitigate:282.87
MW Contribution:1.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966622AG1-532 E
50/50
2.932.93
3151261ROARAP2
50/50
1.1521.152
927146AC1-208 E
Adder
2.18117647058823531.854
924302AB2-077 E O1
Adder
0.79529411764705890.676
3151281ROARAP4
50/50
1.091.09
3156063AA2-053SOLA
50/50
1.1211.121
900672V4-068 E
Adder
0.149411764705882360.127
925612AC1-036 E
Adder
0.41647058823529410.354
924312AB2-078 E O1
Adder
0.79529411764705890.676
3147043LAWRENC
50/50
0.740.74
316181AB2-040 GEN
50/50
2.6292.629
923263AB1-132 E OP
Adder
2.7023529411764712.297
961791AG1-021 C
Adder
0.67176470588235290.571
936261AD2-033 C
Adder
6.6258823529411775.632
962562AG1-105 E
Adder
2.48588235294117642.113
960081AF2-299 C
50/50
5.865.86
926072AC1-086 E
Adder
4.2270588235294123.593
3138533PONTONDP
Adder
0.248235294117647050.211
316131AB2-060 C
50/50
0.8950.895
316129AC1-054 C
50/50
0.7410.741
946282AF1-292 E
50/50
3.2343.234
958212AF2-115 E
Adder
0.71529411764705890.608
964241AG1-285 C
Adder
7.126.052
962561AG1-105 C
Adder
3.72941176470588243.17
946281AF1-292 C
50/50
4.8514.851
960082AF2-299 E
50/50
3.9073.907
926071AC1-086 C
Adder
9.2870588235294127.894
964791AG1-342 C
Adder
1.3564705882352941.153
926206AC1-098 E
Adder
1.7470588235294121.485
961792AG1-021 E
Adder
0.5717647058823530.486
316274AC1-208 C
Adder
4.9105882352941184.174
918492AA1-063AE OP
50/50
2.7952.795
917332KELFORD E
Adder
0.63764705882352950.542
959312AF2-222 E
Adder
5.2388235294117654.453
3147223TWITTYS
Adder
0.46117647058823530.392
924022AB2-043 E O1
50/50
3.1813.181
924516AB2-100 E1
Adder
1.23882352941176471.053
966621AG1-532 C
50/50
4.3954.395
313506AB1-173 C OP
50/50
2.3342.334
946302AF1-294 E
Adder
1.16941176470588240.994
924322AB2-079 E O1
Adder
0.79529411764705890.676
316088AB2-174 E
50/50
15.67415.674
923994AB2-040_E
50/50
12.77312.773
958211AF2-115 C
Adder
0.840.714
936262AD2-033 E
Adder
4.4164705882352953.754
959311AF2-222 C
Adder
7.8188235294117656.646
925785AC1-054 E
50/50
2.0962.096
3145723EMPORIA
50/50
1.2311.231
316087AB2-174 C
50/50
2.8212.821
923573AB1-173 E OP
50/50
6.8126.812
919692AA2-053 E OP
50/50
3.1533.153
3156073AA1-063SOLA
50/50
0.9590.959
920042AA2-088 E OP
Adder
4.6305882352941183.936
964242AG1-285 E
Adder
4.7470588235294124.035
964792AG1-342 E
Adder
0.90352941176470590.768
924162AB2-060 E OP
50/50
2.5852.585
313527AB2-043 C
50/50
0.3160.316
926214AC1-099 E
Adder
0.57647058823529410.49
932632AC2-084 E
Adder
1.5435294117647061.312
919710AA2-057 E
Adder
1.7070588235294121.451
3137643SOCKMAN
50/50
1.0011.001
946301AF1-294 C
Adder
1.38117647058823521.174
924517AB2-100 E2
Adder
1.23882352941176471.053
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.39311.393
WECLTFEXP_WEC->PJM
CLTF
0.0910.091
LAGNLTFEXP_LAGN->PJM
CLTF
0.9350.935
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.1740.174
MECLTFEXP_MEC->PJM
CLTF
0.5250.525
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.7010.701
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.8192.819
NYPJM->LTFIMP_NY
CLTF
0.1550.155
TVALTFEXP_TVA->PJM
CLTF
0.7390.739
O66PJM->LTFIMP_O-066
CMTX_NF
2.1672.167
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.4494.449
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3410.341
CPLELTFEXP_CPLE->PJM
CLTF
1.471.47
SIGELTFEXP_SIGE->PJM
CLTF
0.0330.033

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.78 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1182.76
MW Contribution:2.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
927042AC1-191 E
Adder
2.55411764705882362.171
316233AE1-074 C
50/50
3.7333.733
3147133PAMPLIN
Adder
0.54941176470588240.467
966622AG1-532 E
Adder
0.42588235294117650.362
935162AD1-151 E
Adder
5.9847058823529415.087
943461AF1-017 C
Adder
0.64470588235294120.548
316311AC2-079 C
Adder
2.71999999999999982.312
932596AC2-079 E
Adder
4.4376470588235293.772
920692AA2-178 E
Adder
1.78588235294117651.518
917122Z2-027 E
Adder
0.58470588235294120.497
3146326AYDLETT TAP
Adder
0.58823529411764710.5
938532AE1-072 E
Adder
3.9729411764705883.377
940551AE2-041 C
Adder
3.25058823529411762.763
957832AF2-077 E
Adder
0.63529411764705890.54
926785AC1-164_E
Adder
8.8941176470588247.56
316336AC2-165 C
50/50
13.55213.552
934622AD1-088 E
Adder
2.08470588235294141.772
934612AD1-087 E
Adder
1.55882352941176471.325
316084AB2-161 E
Adder
2.8764705882352942.445
940641AE2-051 C
Adder
7.0152941176470595.963
943471AF1-018 C
Adder
3.25058823529411762.763
3150731STONECA
Adder
4.1494117647058823.527
924302AB2-077 E O1
Adder
0.62117647058823530.528
935161AD1-151 C
Adder
8.9764705882352947.63
900672V4-068 E
Adder
0.157647058823529420.134
3145393UNCAMP
Adder
2.72117647058823582.313
938531AE1-072 C
Adder
7.6223529411764716.479
932046AC2-012 E
Adder
5.7529411764705884.89
958161AF2-110 C
Adder
0.61529411764705890.523
3138116ELKO L286
Adder
0.76588235294117660.651
927041AC1-191 C
Adder
5.1282352941176474.359
938821AE1-108 C
Adder
8.4270588235294127.163
925612AC1-036 E
Adder
0.435294117647058830.37
924312AB2-078 E O1
Adder
0.62117647058823530.528
940541AE2-040 C
Adder
1.35764705882352941.154
940481AE2-033 C
Adder
7.6223529411764716.479
940482AE2-033 E
Adder
5.13882352941176554.368
923263AB1-132 E OP
Adder
2.70941176470588242.303
961611AG1-000B C
Adder
8.1152941176470596.898
3150601CHESTF5
Adder
39.4470588235294233.53
924032AB2-045 E
Adder
0.94941176470588240.807
961791AG1-021 C
Adder
0.97294117647058820.827
936261AD2-033 C
Adder
6.5000000000000015.525
925332AB2-190 E
Adder
4.5752941176470593.889
963041AG1-153 C
Adder
2.2623529411764711.923
960081AF2-299 C
Adder
0.8517647058823530.724
944011AF1-069 C
Adder
5.2235294117647074.44
926072AC1-086 E
Adder
4.2364705882352943.601
927226AC1-216 E
Adder
4.20352941176470553.573
3145413WATKINS
Adder
0.30941176470588240.263
936666AD2-085 E
Adder
2.6835294117647062.281
962962AG1-145 E
Adder
0.65529411764705890.557
938771AE1-103 C
Adder
1.3117647058823531.115
944591AF1-124 C
Adder
19.5717647058823516.636
944601AF1-125 C
Adder
19.2023529411764716.322
941591AE2-156 C
Adder
7.8529411764705886.675
3138533PONTONDP
Adder
0.360.306
946282AF1-292 E
Adder
0.47058823529411770.4
944012AF1-069 E
Adder
2.02941176470588271.725
925865AC1-065 E
Adder
7.73058823529411756.571
316169AC1-164 GEN
Adder
19.79647058823529816.827
930122AB1-027 E
Adder
0.69529411764705880.591
958212AF2-115 E
Adder
1.0352941176470590.88
964241AG1-285 C
Adder
6.0305882352941185.126
963042AG1-153 E
Adder
3.39411764705882352.885
946281AF1-292 C
Adder
0.70588235294117650.6
960082AF2-299 E
Adder
0.56823529411764710.483
926071AC1-086 C
Adder
9.3082352941176477.912
316349AD2-085 C
Adder
1.6447058823529411.398
938772AE1-103 E
Adder
1.8117647058823531.54
916042Z1-036 E
Adder
12.43647058823529310.571
944592AF1-124 E
Adder
44.82117647058823538.098
944582AF1-123 E
Adder
44.6637.961
923832AB2-022 E
Adder
0.53882352941176470.458
935112AD1-144 E
Adder
0.42235294117647060.359
3143096IRON208
50/50
0.330.33
316313AB2-026 C
50/50
0.5570.557
3143316POE
Adder
0.75647058823529410.643
942462AE2-259 E
Adder
3.8917647058823533.308
939191AE1-149 C
Adder
5.8976470588235295.013
901082W1-029 E
Adder
13.8976470588235311.813
934146AD1-041 E
Adder
1.63058823529411771.386
957601AF2-054 C
Adder
0.95294117647058830.81
3150861SPRUNCD
50/50
0.1690.169
316405AF2-144 C
50/50
0.4340.434
3150651CHESTF6
Adder
11.96588235294117610.171
946262AF1-291 E
Adder
0.91058823529411770.774
941011AE2-092 C
Adder
6.9470588235294125.905
961792AG1-021 E
Adder
0.82823529411764710.704
937482AD2-202 E
Adder
0.456470588235294130.388
934576AD1-082 E
Adder
2.2917647058823531.948
918492AA1-063AE OP
Adder
1.8117647058823531.54
933292AC2-141 E
Adder
2.30588235294117631.96
940492AE2-034 E
Adder
1.33882352941176451.138
944602AF1-125 E
Adder
43.9588235294117737.365
957871AF2-081 C
Adder
4.3329411764705883.683
3145506HICKORY
Adder
0.94470588235294130.803
943612AF1-032 E
Adder
0.405882352941176470.345
3130536PAPERMILL
Adder
3.0341176470588242.579
939602AE1-190 E
Adder
0.6517647058823530.554
926412AC1-112 E
Adder
0.56470588235294120.48
959312AF2-222 E
Adder
5.71764705882352954.86
3147223TWITTYS
Adder
0.48235294117647060.41
924022AB2-043 E O1
Adder
2.4235294117647062.06
924516AB2-100 E1
Adder
1.32117647058823541.123
966621AG1-532 C
Adder
0.63882352941176480.543
940642AE2-051 E
Adder
4.67764705882352953.976
943462AF1-017 E
Adder
1.0517647058823530.894
942341AE2-247 C
Adder
0.71294117647058820.606
919153AA1-139 E2
Adder
1.7717647058823531.506
958162AF2-110 E
Adder
0.97882352941176460.832
942002AE2-212 E
Adder
0.86941176470588230.739
946302AF1-294 E
Adder
1.69294117647058841.439
940431AE2-027 C
Adder
7.9682352941176476.773
924322AB2-079 E O1
Adder
0.62117647058823530.528
957481AF2-042 C
Adder
23.21647058823529619.734
316088AB2-174 E
Adder
2.94705882352941152.505
923994AB2-040_E
Adder
2.76941176470588252.354
944581AF1-123 C
Adder
19.50352941176470616.578
941101AE2-104 C
Adder
1.50823529411764711.282
934392AD1-063 E
Adder
0.487058823529411770.414
316076AC2-137 E
Adder
0.73529411764705890.625
966872AG1-558 E
Adder
0.64352941176470590.547
966871AG1-558 C
Adder
1.27764705882352961.086
3150831SPRUNCA
50/50
9.4469.446
3150841SPRUNCB
50/50
9.4469.446
316258AE1-075 C
50/50
0.5110.511
923862AB2-026 E
50/50
1.8081.808
941012AE2-092 E
Adder
4.6305882352941183.936
958211AF2-115 C
Adder
1.21529411764705891.033
936262AD2-033 E
Adder
4.3329411764705883.683
923852AB2-025 E
Adder
0.54941176470588240.467
941032AE2-094 E
Adder
7.166.086
941031AE2-094 C
Adder
15.98588235294117513.588
939412AE1-173 E
Adder
24.89294117647058621.159
916192Z1-068 E
Adder
0.820.697
926662AC1-147 E
Adder
0.58117647058823530.494
957492AF2-043 E
Adder
0.62470588235294120.531
923842AB2-024 E
Adder
0.82235294117647050.699
316157AD2-030 E
Adder
0.53411764705882360.454
944641AF1-129 C
Adder
65.7211764705882355.863
316240AF1-291 C
Adder
1.36588235294117651.161
959311AF2-222 C
Adder
8.5341176470588237.254
3145723EMPORIA
Adder
0.196470588235294150.167
923573AB1-173 E OP
Adder
1.47764705882352951.256
919692AA2-053 E OP
Adder
1.86823529411764721.588
924814AB2-134 E
Adder
6.8847058823529425.852
920042AA2-088 E OP
Adder
4.724.012
942342AE2-247 E
Adder
0.98470588235294120.837
919152AA1-139 E1
Adder
1.7717647058823531.506
944631AF1-128 C
Adder
24.6823529411764720.98
3150851SPRUNCC
50/50
0.1690.169
938552AE1-074 E
50/50
1.8811.881
938562AE1-075 E
50/50
1.5421.542
964242AG1-285 E
Adder
4.0211764705882363.418
924162AB2-060 E OP
Adder
2.0117647058823531.71
316160AE1-175 E
Adder
0.54117647058823540.46
933291AC2-141 C
Adder
12.51176470588235310.635
957872AF2-081 E
Adder
1.85647058823529431.578
925522AC1-027 E
Adder
0.53176470588235290.452
941102AE2-104 E
Adder
2.39764705882352922.038
3145256KINGFORK
Adder
0.455294117647058850.387
3150921YORKTN3
Adder
52.8152941176470644.893
933502AC2-165 E
50/50
10.19910.199
940432AE2-027 E
Adder
5.3129411764705894.516
3137643SOCKMAN
Adder
0.317647058823529450.27
939411AE1-173 C
Adder
37.3388235294117631.738
934012AD1-025 E
Adder
5.44117647058823554.625
913392Y1-086 E
Adder
0.9552941176470590.812
939612AE1-191 E
Adder
2.6082352941176472.217
957602AF2-054 E
Adder
0.63529411764705890.54
958502AF2-144 E
50/50
1.7771.777
938822AE1-108 E
Adder
4.0211764705882363.418
942001AE2-212 C
Adder
1.3035294117647061.108
942461AE2-259 C
Adder
5.83647058823529454.961
946301AF1-294 C
Adder
1.99882352941176491.699
939192AE1-149 E
Adder
3.93176470588235333.342
934621AD1-088 C
Adder
4.3294117647058833.68
957482AF2-042 E
Adder
15.4776470588235313.156
924517AB2-100 E2
Adder
1.32117647058823541.123
937226AE2-253 E
Adder
2.53176470588235342.152
934065AD1-033 E
Adder
2.1752941176470591.849
939312AE1-162 E
Adder
0.67999999999999990.578
316303AF2-085
50/50
7.0277.027
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.08118.081
G-007PJM->LTFIMP_G-007
CMTX_NF
2.112.11
CPLELTFEXP_CPLE->PJM
CLTF
4.6984.698
SIGELTFEXP_SIGE->PJM
CLTF
0.1370.137
CBM South 2LTFEXP_CBM-S2->PJM
CBM
40.62940.629
WECLTFEXP_WEC->PJM
CLTF
0.3730.373
LAGNLTFEXP_LAGN->PJM
CLTF
3.6953.695
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.7270.727
MECLTFEXP_MEC->PJM
CLTF
2.1322.132
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.2422.242
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.29711.297
NYPJM->LTFIMP_NY
CLTF
0.9630.963
TVALTFEXP_TVA->PJM
CLTF
2.952.95
O66PJM->LTFIMP_O-066
CMTX_NF
13.41813.418

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 550_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.92 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3411.03
MW Contribution:4.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316233AE1-074 C
50/50
3.143.14
3147133PAMPLIN
Adder
1.09647058823529430.932
3152411Z1-086 GT1
50/50
13.99713.997
3152441Z1-086 ST
50/50
24.36424.364
966622AG1-532 E
50/50
1.1011.101
943461AF1-017 C
Adder
1.521.292
316311AC2-079 C
Adder
6.4611764705882355.492
932596AC2-079 E
Adder
10.5423529411764718.961
920692AA2-178 E
Adder
4.6870588235294123.984
917122Z2-027 E
Adder
1.52235294117647071.294
3146326AYDLETT TAP
Adder
1.53411764705882361.304
938532AE1-072 E
Adder
10.3635294117647068.809
316336AC2-165 C
50/50
11.89711.897
934622AD1-088 E
50/50
5.6675.667
934611AD1-087 C
50/50
1.5341.534
934612AD1-087 E
50/50
4.4414.441
927146AC1-208 E
Adder
4.6176470588235293.925
316084AB2-161 E
Adder
6.1764705882352945.25
940641AE2-051 C
50/50
23.07223.072
933982AD1-022 E
Adder
5.4529411764705884.635
3145946PLYMOUTH TP
Adder
0.36941176470588240.314
316017AA1-139 ULT1
50/50
1.221.22
924302AB2-077 E O1
Adder
1.53411764705882361.304
3152421Z1-086 GT2
50/50
13.99313.993
900672V4-068 E
Adder
0.410588235294117640.349
933981AD1-022 C
Adder
10.0176470588235318.515
3145393UNCAMP
Adder
6.9494117647058825.907
938531AE1-072 C
Adder
19.8816.898
932046AC2-012 E
Adder
14.74823529411764712.536
958161AF2-110 C
Adder
1.54823529411764721.316
925612AC1-036 E
Adder
0.96823529411764710.823
926274AC1-105 E
Adder
3.05411764705882362.596
924312AB2-078 E O1
Adder
1.53411764705882361.304
940541AE2-040 C
50/50
3.4933.493
940481AE2-033 C
50/50
19.63119.631
940482AE2-033 E
50/50
13.23413.234
3152431Z1-086 GT3
50/50
13.99313.993
923263AB1-132 E OP
Adder
7.1317647058823546.062
961611AG1-000B C
Adder
16.4223529411764713.959
961791AG1-021 C
Adder
1.99411764705882361.695
936261AD2-033 C
Adder
14.72588235294117712.517
962562AG1-105 E
Adder
6.7588235294117655.745
3151531CLOVER1
50/50
15.58115.581
963041AG1-153 C
50/50
7.4237.423
960081AF2-299 C
50/50
2.2032.203
944011AF1-069 C
50/50
17.48817.488
926072AC1-086 E
Adder
11.152941176470599.48
3145413WATKINS
Adder
0.7917647058823530.673
936666AD2-085 E
Adder
6.3235294117647065.375
938771AE1-103 C
Adder
3.34117647058823542.84
944591AF1-124 C
50/50
51.8551.85
944601AF1-125 C
50/50
50.8750.87
3151101ELIZAR3
50/50
3.6413.641
941591AE2-156 C
Adder
20.1617.136
3138533PONTONDP
Adder
0.73882352941176480.628
316315AB2-025 C
50/50
0.4950.495
316023AB2-100 C2
50/50
1.1361.136
946282AF1-292 E
50/50
1.2161.216
944012AF1-069 E
50/50
6.7946.794
316316AC1-027 C
50/50
0.3550.355
958212AF2-115 E
Adder
2.1235294117647061.805
964241AG1-285 C
Adder
14.29529411764705812.151
962561AG1-105 C
Adder
10.137647058823538.617
3151541CLOVER2
50/50
15.43615.436
963042AG1-153 E
50/50
11.13411.134
946281AF1-292 C
50/50
1.8231.823
960082AF2-299 E
50/50
1.4691.469
926071AC1-086 C
Adder
24.50588235294117520.83
316349AD2-085 C
Adder
3.8752941176470593.294
938772AE1-103 E
Adder
4.6141176470588243.922
916042Z1-036 E
Adder
32.496470588235327.622
944592AF1-124 E
50/50
118.738118.738
944582AF1-123 E
50/50
118.31118.31
923832AB2-022 E
Adder
1.40470588235294121.194
935112AD1-144 E
Adder
1.040.884
316313AB2-026 C
50/50
0.4750.475
3143316POE
50/50
1.5751.575
964791AG1-342 C
Adder
4.037647058823533.432
939191AE1-149 C
Adder
11.92235294117647210.134
3151041BRUNSWICKG3
50/50
10.91910.919
926206AC1-098 E
Adder
4.2058823529411773.575
901082W1-029 E
Adder
36.1329411764705930.713
316405AF2-144 C
50/50
0.370.37
946262AF1-291 E
Adder
1.47176470588235291.251
961792AG1-021 E
Adder
1.69882352941176461.444
937482AD2-202 E
50/50
1.31.3
3151021BRUNSWICKG1
50/50
10.91910.919
316274AC1-208 C
Adder
10.48.84
934576AD1-082 E
Adder
4.9211764705882354.183
918492AA1-063AE OP
Adder
4.7329411764705884.023
917332KELFORD E
Adder
1.8917647058823531.608
925122AB2-169 E
Adder
6.5670588235294125.582
943172AE2-346 E
Adder
0.69647058823529410.592
934522AD1-076 E
Adder
7.12588235294117746.057
933292AC2-141 E
50/50
14.58914.589
940492AE2-034 E
Adder
3.5152941176470592.988
944602AF1-125 E
50/50
116.453116.453
957871AF2-081 C
50/50
11.30311.303
3145506HICKORY
50/50
2.4652.465
943612AF1-032 E
Adder
1.04470588235294120.888
959312AF2-222 E
Adder
12.56588235294117510.681
3147223TWITTYS
Adder
1.07294117647058830.912
924022AB2-043 E O1
Adder
5.9517647058823535.059
935171AD1-152 C
50/50
1.5911.591
924516AB2-100 E1
50/50
3.4373.437
966621AG1-532 C
50/50
1.6521.652
940642AE2-051 E
50/50
15.38115.381
918532AA1-067 E
Adder
0.81647058823529410.694
918512AA1-065 E OP
Adder
6.3400000000000015.389
934502AD1-074 E
Adder
19.59411764705882716.655
934512AD1-075 E
Adder
4.8988235294117644.164
943462AF1-017 E
Adder
2.482.108
942341AE2-247 C
Adder
1.681.428
919153AA1-139 E2
50/50
4.6224.622
316388AE2-253 GEN
50/50
2.2142.214
958162AF2-110 E
Adder
2.46235294117647062.093
942002AE2-212 E
Adder
1.55411764705882361.321
946302AF1-294 E
Adder
3.47176470588235332.951
940431AE2-027 C
Adder
13.27647058823529511.285
943902AF1-058 E
Adder
1.4670588235294121.247
924322AB2-079 E O1
Adder
1.53411764705882361.304
957481AF2-042 C
50/50
67.59667.596
316365AB2-100 C1
50/50
1.1361.136
316088AB2-174 E
Adder
7.6541176470588246.506
923994AB2-040_E
Adder
7.2105882352941176.129
316141AB2-099 E
Adder
0.290588235294117650.247
316294AC1-161 C
50/50
5.5655.565
944581AF1-123 C
50/50
51.66651.666
316185AD1-033 C
50/50
1.3851.385
916191Z1-068 C
50/50
0.0490.049
941101AE2-104 C
Adder
3.79294117647058873.224
3150831SPRUNCA
Adder
9.668.211
3150841SPRUNCB
Adder
9.668.211
316258AE1-075 C
50/50
0.4350.435
923862AB2-026 E
50/50
1.5421.542
958211AF2-115 C
Adder
2.49294117647058842.119
936262AD2-033 E
Adder
9.8164705882352948.344
923852AB2-025 E
50/50
1.4131.413
3151051BRUNSWICKS1
50/50
22.68422.684
941032AE2-094 E
50/50
23.97223.972
941031AE2-094 C
50/50
53.52353.523
934322AD1-056 E
Adder
3.91411764705882353.327
934321AD1-056 C
Adder
7.2164705882352946.134
934332AD1-057 E
Adder
2.09647058823529431.782
934331AD1-057 C
Adder
4.0258823529411773.422
939412AE1-173 E
50/50
77.7577.75
961942AG1-037 E
Adder
0.38705882352941180.329
961941AG1-037 C
Adder
0.580.493
916192Z1-068 E
50/50
2.1212.121
3151081ELIZAR1
50/50
3.5963.596
926662AC1-147 E
Adder
1.49058823529411751.267
957492AF2-043 E
Adder
1.6082352941176471.367
944641AF1-129 C
Adder
29.2682352941176524.878
316240AF1-291 C
Adder
2.20823529411764731.877
959311AF2-222 C
Adder
18.7552941176470615.942
937481AD2-202 C
50/50
0.4450.445
925785AC1-054 E
Adder
3.9917647058823533.393
3145723EMPORIA
50/50
0.5070.507
923573AB1-173 E OP
Adder
3.84588235294117683.269
919692AA2-053 E OP
Adder
4.9082352941176474.172
920042AA2-088 E OP
Adder
12.21058823529411810.379
934521AD1-076 C
Adder
13.97999999999999911.883
934511AD1-075 C
Adder
9.6235294117647058.18
942342AE2-247 E
Adder
2.321.972
919152AA1-139 E1
50/50
4.6224.622
938552AE1-074 E
50/50
1.5821.582
938562AE1-075 E
50/50
1.3151.315
964242AG1-285 E
Adder
9.5294117647058828.1
964792AG1-342 E
Adder
2.69176470588235262.288
924162AB2-060 E OP
Adder
4.9070588235294124.171
3151031BRUNSWICKG2
50/50
10.91910.919
926214AC1-099 E
Adder
1.38941176470588231.181
932632AC2-084 E
Adder
3.71764705882352953.16
933291AC2-141 C
50/50
34.17534.175
926755AC1-161 E
50/50
14.58914.589
957872AF2-081 E
50/50
4.8444.844
316018AA1-139 ULT2
50/50
1.221.22
925522AC1-027 E
50/50
1.3731.373
941102AE2-104 E
Adder
6.0305882352941185.126
3145256KINGFORK
Adder
1.11999999999999990.952
933502AC2-165 E
50/50
8.9548.954
940432AE2-027 E
Adder
8.8517647058823537.524
919710AA2-057 E
Adder
4.5541176470588243.871
3137643SOCKMAN
Adder
0.8317647058823530.707
939411AE1-173 C
50/50
116.624116.624
913392Y1-086 E
Adder
2.48823529411764752.115
958502AF2-144 E
50/50
1.5151.515
942001AE2-212 C
Adder
2.33058823529411761.981
946301AF1-294 C
Adder
4.09882352941176453.484
939192AE1-149 E
Adder
7.9482352941176486.756
935172AD1-152 E
50/50
6.5696.569
934621AD1-088 C
50/50
11.7711.77
957482AF2-042 E
50/50
45.06445.064
924517AB2-100 E2
50/50
3.4373.437
934501AD1-074 C
Adder
38.4929411764705932.719
937226AE2-253 E
50/50
6.6076.607
934065AD1-033 E
50/50
5.675.67
939312AE1-162 E
Adder
1.53529411764705871.305
316303AF2-085
50/50
5.5375.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.44630.446
NYPJM->LTFIMP_NY
CLTF
2.3122.312
TVALTFEXP_TVA->PJM
CLTF
8.0788.078
O66PJM->LTFIMP_O-066
CMTX_NF
31.68131.681
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.12546.125
G-007PJM->LTFIMP_G-007
CMTX_NF
4.9764.976
CPLELTFEXP_CPLE->PJM
CLTF
13.58913.589
SIGELTFEXP_SIGE->PJM
CLTF
0.3550.355
CBM South 2LTFEXP_CBM-S2->PJM
CBM
116.495116.495
WECLTFEXP_WEC->PJM
CLTF
0.9550.955
LAGNLTFEXP_LAGN->PJM
CLTF
10.14710.147
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
1.8681.868
MECLTFEXP_MEC->PJM
CLTF
5.5885.588
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.4826.482

Details for 8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.31 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4286.27
MW Contribution:5.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3147133PAMPLIN
Adder
1.261.071
927264AC1-222 E
50/50
7.1497.149
3152411Z1-086 GT1
50/50
33.47433.474
3152441Z1-086 ST
50/50
58.26658.266
316222AC1-221 C
50/50
2.6372.637
927255AC1-221 E
50/50
6.9166.916
316237AB2-079 C O1
50/50
0.4550.455
934622AD1-088 E
50/50
10.28810.288
934611AD1-087 C
50/50
2.842.84
934612AD1-087 E
50/50
8.2238.223
3151621KERR 5
50/50
1.6151.615
3151611KERR 4
50/50
1.6151.615
940641AE2-051 C
Adder
-21.040000000000003-17.884
942752AE2-291 E
Adder
8.0741176470588246.863
924302AB2-077 E O1
50/50
1.8631.863
316238AB2-078 C O1
50/50
0.4550.455
3152421Z1-086 GT2
50/50
33.46533.465
938531AE1-072 C
Adder
-16.01294117647059-13.611
925612AC1-036 E
50/50
1.1421.142
926274AC1-105 E
50/50
4.6164.616
924312AB2-078 E O1
50/50
1.8631.863
3152431Z1-086 GT3
50/50
33.46533.465
936171AD2-023 C
Adder
7.0929411764705886.029
961791AG1-021 C
Adder
2.30941176470588251.963
936261AD2-033 C
50/50
17.43217.432
316248AF1-058 C
50/50
0.5710.571
962562AG1-105 E
50/50
9.4059.405
3151531CLOVER1
50/50
28.86828.868
963041AG1-153 C
50/50
17.10317.103
3138533PONTONDP
Adder
0.85529411764705890.727
316131AB2-060 C
50/50
2.042.04
3151631KERR 6
50/50
1.6151.615
936172AD2-023 E
Adder
3.8505882352941183.273
958212AF2-115 E
Adder
2.45882352941176442.09
316034AC1-036 C
50/50
0.3110.311
316118AC1-105 C
50/50
1.5721.572
964241AG1-285 C
50/50
17.07617.076
962561AG1-105 C
50/50
14.10814.108
3151541CLOVER2
50/50
28.59928.599
963042AG1-153 E
50/50
25.65425.654
940081AE1-250 C
Adder
12.86117647058823510.932
942462AE2-259 E
Adder
8.1329411764705886.913
925997AC1-075 E
50/50
4.7084.708
964791AG1-342 C
50/50
5.7665.766
316239AB2-077 C O1
50/50
0.4550.455
3151041BRUNSWICKG3
50/50
25.15825.158
957601AF2-054 C
Adder
-1.8-1.53
961792AG1-021 E
Adder
1.96705882352941171.672
3152661PLYWOOD A
50/50
2.0932.093
937482AD2-202 E
50/50
2.4072.407
3151021BRUNSWICKG1
50/50
25.15825.158
926024AC1-080 E
50/50
1.5621.562
936161AD2-022 C
Adder
12.15882352941176610.335
959312AF2-222 E
50/50
14.77814.778
3147223TWITTYS
50/50
1.2661.266
924022AB2-043 E O1
50/50
7.1597.159
935171AD1-152 C
50/50
2.8492.849
3151601KERR 3
50/50
1.6151.615
3151581KERR 1
50/50
0.5770.577
24401205PINNACLE
Adder
1.6670588235294121.417
946302AF1-294 E
Adder
4.01882352941176453.416
316003AC1-222 C
50/50
1.7441.744
943902AF1-058 E
50/50
2.342.34
924322AB2-079 E O1
50/50
1.8631.863
957481AF2-042 C
50/50
129.887129.887
964211AG1-282 C
Adder
-1.7011764705882353-1.446
958211AF2-115 C
Adder
2.88588235294117632.453
936262AD2-033 E
50/50
11.62211.622
3151051BRUNSWICKS1
50/50
52.26552.265
944641AF1-129 C
Adder
-90.49176470588236-76.918
316240AF1-291 C
Adder
-1.9317647058823528-1.642
940082AE1-250 E
Adder
8.5741176470588247.288
942751AE2-291 C
Adder
12.11176470588235310.295
316205AC1-080 C
50/50
0.4520.452
316123AC1-075 C
50/50
1.3531.353
959311AF2-222 C
50/50
22.05622.056
937481AD2-202 C
50/50
0.8240.824
3151591KERR 2
50/50
1.6151.615
925785AC1-054 E
Adder
2.96470588235294132.52
932763AC2-100 E
50/50
4.6734.673
964242AG1-285 E
50/50
11.38411.384
964792AG1-342 E
50/50
3.8443.844
924162AB2-060 E OP
50/50
5.8965.896
313527AB2-043 C
50/50
0.7110.711
3151641KERR 7
50/50
1.6151.615
3151031BRUNSWICKG2
50/50
25.15825.158
933291AC2-141 C
Adder
-32.203529411764706-27.373
942001AE2-212 C
Adder
-2.010588235294118-1.709
942461AE2-259 C
Adder
12.19882352941176510.369
936162AD2-022 E
Adder
7.29529411764705856.201
946301AF1-294 C
Adder
4.7458823529411774.034
316283AC2-100 C
50/50
2.1162.116
935172AD1-152 E
50/50
11.76211.762
934621AD1-088 C
50/50
21.36821.368
957482AF2-042 E
50/50
86.59186.591
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
2.7422.742
MECLTFEXP_MEC->PJM
CLTF
8.3488.348
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.2639.263
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.76444.764
NYPJM->LTFIMP_NY
CLTF
2.1082.108
TVALTFEXP_TVA->PJM
CLTF
11.71211.712
O66PJM->LTFIMP_O-066
CMTX_NF
29.75629.756
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.06671.066
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6814.681
CPLELTFEXP_CPLE->PJM
CLTF
19.41719.417
SIGELTFEXP_SIGE->PJM
CLTF
0.5240.524
CBM South 2LTFEXP_CBM-S2->PJM
CBM
170.641170.641
WECLTFEXP_WEC->PJM
CLTF
1.451.45
LAGNLTFEXP_LAGN->PJM
CLTF
14.84614.846
CONTINGENCY 'DVP_P1-2: LN 2201_SRT-A'
 OPEN BRANCH FROM BUS 313725 TO BUS 314563 CKT 1   /*6DRY BREAD   230.0 - 6CLUBHSE     230.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 550_SRT-S'
 OPEN BRANCH FROM BUS 314917 TO BUS 314926 CKT 1                /*8MT STM      500.0 - 8VALLEY      500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314562 to 314563 ckt 1
314322 to 314914 ckt 1
314914 to 314918 ckt 1
314940 to 941030 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AF2-115 was evaluated as a 25.0 MW injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 1 Cluster 30 for Phase 3 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 30 projects.

 

Table 1: Transition Cycle 1 Cluster 30 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

30

AF1-294

Solar

Dominion

41

41

22.2

Jetersville - Ponton 115 kV

AF2-115

Solar

Dominion

25

25

13.5

AG1-021

Solar

Dominion

20

20

10.8

AG1-166

Solar

Dominion

20

20

6

Lone Pine 115 kV

AG1-167

Solar

Dominion

15

15

4.5

AG1-168

Solar

Dominion

15

15

4.5

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 30 projects will meet the dynamics requirements of the NERC, Dominion Energy, and PJM reliability standards.

 

The load flow case for Phase 2 was used as a starting point and was updated based on latest Cluster 30 data, recommended transmission changes incorporated based on Dominion Energy Phase 2 feedback, and withdrawn generation removed. Cluster 30 projects have been dispatched online at maximum power output with near unity power factor measured at the high-side of the main substation transformer. The dynamic models for Cluster 30 projects were updated based on the latest DP2 data and include any tuning adjustments recommended during Phase 2.

 

Cluster 30 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. During the Phase 2 analysis contingencies were examined around the POIs and no violations were observed as a result of Cluster 30 projects interconnecting.  Due to this the Phase 3 analysis for Cluster 30 focused on the contingencies at Chase City that resulted in instability caused by Cluster 31 and Cluster 40 during Phase 2.  The Phase 3 analysis examined, 8 initial contingencies and 24 sensitivity contingencies were studied, each with a 30 second simulation time period. The studied contingencies included:

 

  • Three-phase faults with normal clearing time.
  • Single-phase bus faults with normal clearing time.
  • Single-phase faults with stuck breaker.

 

Instability was observed for contingencies when the Chase City to AG1-285 Tap 115 kV circuit was tripped. This outage resulted in instability due to insufficient export paths for the generation along the Farmville to Chase City 115 kV path through the radial connection.  Additionally, the Farmville to Chase City 115 kV path is prone to controller instability due to weak grid conditions determined by the composite short circuit ratio assessment.  The instability was caused by the Cluster 31 queue projects. 

 

To following mitigation was tested and all maintain stability:

  1. Adding a new 115 kV line from AG1-285 to Butcher’s Creek.
  2. Moving AF2-222 and AG1-285 to a new 230 kV line from Farmville to Finneywood.
  3. Upgrade the new AG1-285 substation to a breaker and a half scheme to accommodate 2 x 230/115 kV transformers and a 230 kV line from AG1-285 to Finneywood .

 

The Transmission Owner has elected to upgrade the new AG1-285 substation to a breaker and a half scheme to accommodate 2 x 230/115 kV transformers and a 230 kV line from AG1-285 to Finneywood as the mitigation to the instability. This mitigation is required due to the interconnection of the Cluster 31 queue projects. Cluster 30 queue projects did not cause the instability. The mitigation was further tested for all Phase 2 contingencies and no violations were observed.

 

Nearby projects were found to trip based on their protection settings. The protection trip times were increased during Phase 2 analysis and maintained during the Phase 3 analysis:

 

  • AE1-056 tripped for frequencies below 55 hz for more than 0.001 seconds and the relay pick-up time was increased to 0.034 seconds
  • AE1-056 tripped for frequencies above 65 hz for more than 0.001 seconds and the relay pick-up time was increased to 0.020834 seconds
  • AF2-222 tripped for voltages above 1.3 p.u. for more than 0.001 seconds and the relay pick-up time was increased to 0.012501 seconds

 

With the mitigation identified above, the results of the contingencies tested on the RTEP 2027 summer peak case found:

 

  • Cluster 30 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  • The system with Cluster 30 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for inter area modes and 4% for local modes.
  • Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus) and the final voltages are within the steady-state voltage ranges below per Dominion Energy’s transmission planning criteria.
    • P1 Category Contingencies:
      • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.01 to 1.096 p.u. for 500 kV facilities
    • P2, P4, P5, and P7 Category Contingencies:
      • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.00 to 1.096 p.u. for 500 kV facilities
  • No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

No mitigation was needed to connect the Cluster 30 queue projects.

Reactive Power Analysis

The reactive power capability of AF2-115 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-065Earleys 230kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-088Boykins-Handsome 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB1-173Brink-Trego 115kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-100Clubhouse-Lakeview 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVEngineering & Procurement
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-080Perth-Hickory Grove 115kVIn Service
AC1-086Thelma 230kVUnder Construction
AC1-098Dawson-South Justice 115kVIn Service
AC1-099Dawson-South Justice 115kVIn Service
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVUnder Construction
AC2-084Dawson-South Justice 115kVIn Service
AC2-100Halifax-Person 230kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-033Fentress-Landstown 230 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-103Holland-Union Camp 115 kVSuspended
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-149Disputanta-Poe 115 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE2-027Harrowgate-Locks 115kVSuspended
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVIn Service
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVWithdrawn
AE2-156Yadkin 115 kVEngineering & Procurement
AE2-185Gladys DP-Stonemill Switching Station 69 kVEngineering & Procurement
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-247Myrtle-Windsor 115 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVEngineering & Procurement
AE2-346Ahoskie 34.5 kVIn Service
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-123Harper 230 kVUnder Construction
AF1-124Harper 230 kVPartially in Service - Under Construction
AF1-125Harper 230 kVUnder Construction
AF1-128Chesterfield 230 kVUnder Construction
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVUnder Construction
AF1-294Jetersville-Ponton 115 kVEngineering & Procurement
AF2-042Clover-Rawlings 500 kVEngineering & Procurement
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-081Moyock 230 kVEngineering & Procurement
AF2-085Midlothian 34.5 kVIn Service
AF2-110Suffolk 115 kVWithdrawn
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVEngineering & Procurement
AF2-299Fields 34.5 kVEngineering & Procurement
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-021Jetersville-Ponton 115 kVEngineering & Procurement
AG1-037Ahoskie 34.5 kVWithdrawn
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-105Mount Laurel-Barnes Junction 115 kVUnder Construction
AG1-135Garner-Lancaster 115 kVUnder Construction
AG1-153Heritage 500 kVUnder Construction
AG1-285Chase City-Central 115 kVEngineering & Procurement
AG1-342Dryburg 115 kVEngineering & Procurement
AG1-532Fields 34.5 kVUnder Construction
V4-068Murphy's 34.5kVIn Service
Y1-086Morgans CornerIn Service
Z1-068Birdneck 34.5kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-088Tarboro-Everetts 230kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In coordination with other Affected System Operators, PJM has determined that the Affected System Operator for this project that requires an Affected System Study. For the latest Affected System Study results pertaining this project, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM lists any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AF2-115 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionn9220.0Wreck and rebuild 15.49 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.Cost Allocated$1,359,435
Dominionn9217.0Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.Cost Allocated$1,235,466
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$158,850
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$142,059
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$90,608
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$50,138
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$39,520
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$32,112
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0N/A
Dominionb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0N/A
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0N/A
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0N/A
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0N/A
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0N/A
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0N/A
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0N/A
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0N/A
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0N/A
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0N/A
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0N/A
Grand Total:$3,108,188

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Discounted Total Cost ($USD)
$19,755,576
Allocated Cost ($USD)
$513,287
Time Estimate
Dec 31 2029

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

FacilityContingency
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-294 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
41.0 MW4.3%$841,778
AF2-115 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
25.0 MW2.6%$513,287
AF2-222500.9 MW52.1%$10,288,736
AG1-021 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
20.0 MW2.1%$410,629
AG1-285374.9 MW39.0%$7,701,147
System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Allocated Cost ($USD)
$142,059
Time Estimate
Dec 31 2029
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$9,643,407
AF1-12413.4979 %$9,677,731
AF1-12513.2418 %$9,494,085
AF1-2940.3249 %$232,973
AF2-04231.9983 %$22,942,056
AF2-1150.1981 %$142,059
AF2-1205.8297 %$4,179,767
AF2-2223.9954 %$2,864,613
AG1-0210.1585 %$113,647
AG1-1243.1793 %$2,279,469
AG1-1355.5860 %$4,005,041
AG1-2852.9906 %$2,144,197
AG1-5365.5494 %$3,978,787

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.49 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Discounted Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$1,359,435
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
6BUCKING-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A796.0 MVA
(All)B796.0 MVA
(All)C964.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE2-29113.6 MW3.8%$1,705,384
AF1-294 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
17.8 MW5.0%$2,229,393
AF2-042163.5 MW46.2%$20,532,412
AF2-115 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
10.8 MW3.1%$1,359,435
AF2-22265.0 MW18.3%$8,159,120
AG1-021 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
8.7 MW2.4%$1,087,573
AG1-10523.6 MW6.7%$2,967,877
AG1-28541.9 MW11.8%$5,264,576
AG1-3429.2 MW2.6%$1,160,153

System Reinforcement: n9217.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9217.0 / TC1-PH2-DOM-028
Title
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$40,414,822
Discounted Total Cost ($USD)
$40,414,822
Allocated Cost ($USD)
$1,235,466
Time Estimate
45 to 46 Months

Contributor

FacilityContingency
6BUCKING-6FARMVIL 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A797.0 MVA
(All)B797.0 MVA
(All)C1116.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE2-29113.6 MW3.8%$1,550,409
AF1-294 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
17.8 MW5.0%$2,026,247
AF2-042163.5 MW46.2%$18,661,737
AF2-115 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
10.8 MW3.1%$1,235,466
AF2-22265.0 MW18.3%$7,415,536
AG1-021 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
8.7 MW2.4%$988,419
AG1-10523.6 MW6.7%$2,697,555
AG1-28541.9 MW11.8%$4,784,850
AG1-3429.2 MW2.6%$1,054,602

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029
Cost Alloc Type
Contingent

System Reinforcement: n9681.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9681.0
Title
Upgrade 1.04 Miles of 230kV transmission line 249 from 249/86 to 249/93
Description
Reconductor 1.04 miles of 2*636 ACSR 24/7 MOT 150 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" MOT 250 on 230 kV line 249 between Carson and Chaparral
Total Cost ($USD)
$3,042,004
Discounted Total Cost ($USD)
$3,042,004
Allocated Cost ($USD)
$0
Time Estimate
20 to 21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-115 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-115 could receive cost allocation. Although AF2-115 may not presently have cost responsibility for this upgrade, AF2-115 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1442.0 MVA
LLB1540.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1493.0 MVA
WINB1587.0 MVA
WINC1631.0 MVA

System Reinforcement: b3694.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3694.8
Title
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA.
Description
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA. Upgrade terminal equipment at Carson and Locks to not limit the new conductor rating.
Cost Information
Time Estimate
May 03 2025

Not Contingent

Note: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1047.0 MVA
(All)B1047.0 MVA
(All)C1204.0 MVA
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA

System Reinforcement: s3671.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3671.5
Title
Rebuild Line 238 from Carson to Clubhouse for a normal summer rating of 1573 MVA
Description
Rebuild Line 238 from Carson to Clubhouse for a normal summer rating of 1573 MVA
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AF2-115 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA
6SAPONY-AE2-033 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9378.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9378.0 / TC1-PH3-DOM-010
Title
Replace existing 230/500 kV Carson transformer #1 with (4)-480 MVA single phase transformers.
Description
Replace Existing 230/500 kV Carson transformer #1 with (4)-480 MVA Single Phase transformers. 6CARSON - 8CARSON ckt 2 represents tranformer #1.
Total Cost ($USD)
$37,801,301
Discounted Total Cost ($USD)
$37,801,301
Allocated Cost ($USD)
$0
Time Estimate
Mar 29 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-115 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-115 could receive cost allocation. Although AF2-115 may not presently have cost responsibility for this upgrade, AF2-115 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer(Any)
Rating SetRating TypeRating Value
LLA2016.0 MVA
LLB2083.0 MVA
LLC2239.0 MVA
SUMA1707.0 MVA
SUMB1758.0 MVA
SUMC1873.0 MVA
WINA2196.0 MVA
WINB2228.0 MVA
WINC2308.0 MVA

System Reinforcement: b4053.18
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.18
Title
Rebuild approximately 37.4 miles of 500 kV line No. 563 from Carson-Midlothian.
Description
Rebuild approximately 37.4 miles of 500 kV line No. 563 from Carson-Midlothian. The proposed structures to be installed are mainly 500/230 kV double-circuit V-string suspension towers. The 230 kV circuit position will be vacant at the completion of this project but serves to accommodate a future 230 kV line.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4357.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA5155.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b4053.19
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.19
Title
Uprate 500 kV line No. 563 associated terminal equipment at Carson to 5000A standards.
Description
Uprate 500 kV line No. 563 associated terminal equipment at Carson to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4357.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA5155.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b4053.20
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.20
Title
Uprate 500 kV line No. 563 associated terminal equipment at Midlothian to 5000A standards.
Description
Uprate 500 kV line No. 563 associated terminal equipment at Midlothian to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4357.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA5155.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: n9138.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9138.0 / TC1-PH1-DOM-070
Title
ELIM TC1: Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.
Description
Wreck and rebuild 22.59 miles of Line 511 between Carson and Rawlings with three (3) 1351 ACSS/TW and associated substation work.
Total Cost ($USD)
$111,130,292
Discounted Total Cost ($USD)
$111,130,292
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-115 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-115 could receive cost allocation. Although AF2-115 may not presently have cost responsibility for this upgrade, AF2-115 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9250.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9250.0 / TC1-PH2-DOM-044
Title
ELIM TC1: Construct a new 22.59 mile line between Carson and Rawlings Substations.
Description
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Total Cost ($USD)
$108,728,086
Discounted Total Cost ($USD)
$108,728,086
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-115 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-115 could receive cost allocation. Although AF2-115 may not presently have cost responsibility for this upgrade, AF2-115 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.

System Reinforcement: b4053.27
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.27
Title
Upgrade/install 6000A equipment at Midlothian substation to support the new conductor termination from Vontay.
Description
Upgrade/install 6000A equipment at Midlothian substation to support the new conductor termination from Vontay.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: b4053.6
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.6
Title
Rebuild 20 miles of 500 kV line No. 576 from North Anna substation to Vontay substation using 6000A conductor.
Description
Rebuild 20 miles of 500 kV line No. 576 from North Anna substation to Vontay substation using 6000A conductor.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: b4053.7
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.7
Title
Upgrade/install 6000A equipment at North Anna substation to support the new conductor termination.
Description
Upgrade/install 6000A equipment at North Anna substation to support the new conductor termination.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: b4053.26
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.26
Title
Rebuild 20 miles of 500 kV line No. 576 from Vontay substation to Midlothian substation using 6000A conductor.
Description
Rebuild 20 miles of 500 kV line No. 576 from Vontay substation to Midlothian substation using 6000A conductor.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-115 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-115 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-040
Title
ELIM TC1: Wreck and rebuild 18.75 miles of Line 594 btwn Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) Dipper at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 18.75 miles of Line 594 between Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$128,018,212
Discounted Total Cost ($USD)
$128,018,212
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-115 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-115 could receive cost allocation. Although AF2-115 may not presently have cost responsibility for this upgrade, AF2-115 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9247.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9247.0 / TC1-PH2-DOM-041
Title
ELIM TC1: Wreck and rebuild 14.02 miles of Line 573 btwn Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 14.02 miles of Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA
Total Cost ($USD)
$99,636,684
Discounted Total Cost ($USD)
$99,636,684
Allocated Cost ($USD)
$0
Time Estimate
48 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-115 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-115 could receive cost allocation. Although AF2-115 may not presently have cost responsibility for this upgrade, AF2-115 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n8492

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492
Title
Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.
Description
Wreck and rebuild one (1) overhead 500kV transmission line that will start at the existing Fentress 500 kV Substation and terminate at the existing Yadkin 500 kV Substation, located approximately 13.5 miles away.
Total Cost ($USD)
$80,172,278
Allocated Cost ($USD)
$158,850
Time Estimate
Dec 31 2026
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$10,783,252
AF1-12413.4979 %$10,821,574
AF1-12513.2418 %$10,616,253
AF1-2940.3249 %$260,480
AF2-04231.9983 %$25,653,766
AF2-1150.1981 %$158,821
AF2-1205.8297 %$4,673,803
AF2-2223.9954 %$3,203,203
AG1-0210.1585 %$127,073
AG1-1243.1793 %$2,548,917
AG1-1355.5860 %$4,478,423
AG1-2852.9906 %$2,397,632
AG1-5365.5494 %$4,449,080

System Reinforcement: n9267.0

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9267.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9267.0 / TC1-PH2-DOM-067
Title
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.
Description
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner substations with single (1) 768.2 ACSS/TW “Maumee” at 250 degrees C. This new line will be on separate transmission towers from the existing Northern Neck and Moon Corner line 1059. Station expansion is required at Northern Neck and Moon Corner to accommodate the new line.
Total Cost ($USD)
$45,730,074
Allocated Cost ($USD)
$90,608
Time Estimate
45 to 46 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$6,150,741
AF1-12413.4979 %$6,172,600
AF1-12513.2418 %$6,055,485
AF1-2940.3249 %$148,577
AF2-04231.9983 %$14,632,846
AF2-1150.1981 %$90,591
AF2-1205.8297 %$2,665,926
AF2-2223.9954 %$1,827,099
AG1-0210.1585 %$72,482
AG1-1243.1793 %$1,453,896
AG1-1355.5860 %$2,554,482
AG1-2852.9906 %$1,367,604
AG1-5365.5494 %$2,537,745

System Reinforcement: n9259.0

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9259.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9259.0
Title
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Description
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Total Cost ($USD)
$25,304,902
Allocated Cost ($USD)
$50,138
Time Estimate
Jan 01 2030
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$3,403,535
AF1-12413.4979 %$3,415,630
AF1-12513.2418 %$3,350,825
AF1-2940.3249 %$82,216
AF2-04231.9983 %$8,097,138
AF2-1150.1981 %$50,129
AF2-1205.8297 %$1,475,200
AF2-2223.9954 %$1,011,032
AG1-0210.1585 %$40,108
AG1-1243.1793 %$804,519
AG1-1355.5860 %$1,413,532
AG1-2852.9906 %$756,768
AG1-5365.5494 %$1,404,270

System Reinforcement: n8492.1

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.1
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.1
Title
Two Breaker Additions at Fentress Substation.
Description
Install Two 5000 amp GIS Breakers at Fentress Substation to connect the new 500 kV line 5005.
Total Cost ($USD)
$19,945,879
Allocated Cost ($USD)
$39,520
Time Estimate
Dec 31 2026
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$2,682,741
AF1-12413.4979 %$2,692,275
AF1-12513.2418 %$2,641,193
AF1-2940.3249 %$64,804
AF2-04231.9983 %$6,382,342
AF2-1150.1981 %$39,513
AF2-1205.8297 %$1,162,785
AF2-2223.9954 %$796,918
AG1-0210.1585 %$31,614
AG1-1243.1793 %$634,139
AG1-1355.5860 %$1,114,177
AG1-2852.9906 %$596,501
AG1-5365.5494 %$1,106,877

System Reinforcement: n8492.2

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.2
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.2
Title
Expand Yadkin Substation to accommodate the new 500 kV line.
Description
Expansion of yadkins 500 kV switchyard to accommodate the new 500 kV line which includes addition of 5000 amp GIS breakers and relocation of the existing suffolk -yadkin 500 kV line#565
Total Cost ($USD)
$16,207,123
Allocated Cost ($USD)
$32,112
Time Estimate
Dec 31 2026
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$2,179,874
AF1-12413.4979 %$2,187,621
AF1-12513.2418 %$2,146,115
AF1-2940.3249 %$52,657
AF2-04231.9983 %$5,186,004
AF2-1150.1981 %$32,106
AF2-1205.8297 %$944,827
AF2-2223.9954 %$647,539
AG1-0210.1585 %$25,688
AG1-1243.1793 %$515,273
AG1-1355.5860 %$905,330
AG1-2852.9906 %$484,690
AG1-5365.5494 %$899,398

System Reinforcement: b4000.356

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.355

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.325

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.326

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.327

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: s3047.2

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: s3047.2
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3047.2
Title
Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.
Description
Install (2) 1400 MVA 500-230 kV transformers and associated 500 kV and 230 kV equipment (breakers, switches, leads) at Vint Hill Substation to supply the area with a 500 kV source Cut and loop 500 kV line #535 Loudoun – Meadowbrook and #569 Loudoun - Morrisville as the 500 kV sources into the proposed 500 kV ring bus Vint Hill Substation will be expanded to the north of the existing site to accommodate the 500 kV ring required for the addition of the new transformers Existing terminations for 230 kV line #2174 Wheeler – Vint Hill, line #2101 Bristers – Vint Hill, and line #2163 Liberty – Vint Hill will be rearranged to terminate into the expanded Vint Hill Substation 230 kV line #2114 Remington CT – Rollins Ford will also be cut and looped into the expanded Vint Hill Substation due to spatial constraints along the existing right-of-way.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.312

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.312
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.312
Title
Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.
Description
Rebuild 500kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. New conductor to have a summer rating of 4357 MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.313

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.313
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.313
Title
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Description
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.356

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.356
Title
Build a new 500 kV line from Vint Hill to Wishing Star.
Description
Build a new 500kV line from Vint Hill to Wishing Star. The line will be supported on single circuit monopoles. New conductor to have a summer rating of 4357 MVA. Line length is approximately 16.59 miles
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.357

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.357
Title
Build a new 500 kV line from Morrisville to Vint Hill.
Description
Build a new 500kV line from Morrisville to Vint Hill. New conductor to have a summer rating of 4357 MVA. Line length is approximately 19.71 miles.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.354

AF2-115 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.354
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.354
Title
Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.
Description
Install terminal equipment at Wishing Star substation to support a 5000A line to Vint Hill. Update relay settings for 500kV Lines #546 and #590.
Cost Information
Cost Alloc Type
Contingent

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AF2-115


AF2-115 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
StabilityDominionn9630.0 / TC1-PH3-DOM-013Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Topology25.0 MW2.6%Cost Allocated$513,287
Contributions into Topology or Eliminated Reinforcement Total:$513,287
AF2-115 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$158,850
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$142,059
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$90,608
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$50,138
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$39,520
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$32,112
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0
Dominionb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0
Region Topology Upgrade Total:$513,287

Attachments

AF2-115 One Line Diagram

AF2-115 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.