AF2-222 Final System Impact Study (Retool 2) Report

v2.00 released 2026-05-14 11:53

Madisonville DP-Twitty's Creek 115 kV

100.0 MW Capacity / 167.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia), and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.

The AF2-222 Final System Impact Study (Retool 1) Report is available for download here.

Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed a Solar generating facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Charlotte County, Virginia. The installed facilities will have a total capability of 167.0 MW with 100.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AF2-222
Project Name:
Madisonville DP-Twitty's Creek 115 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
State:
Virginia
County:
Charlotte
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
167.0
MWE:
167.0
MWC:
100.0
Fuel Type:
Solar
Basecase Study Year:
2027

Physical Interconnection Facility Study

Received

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AF2-222 will interconnect with the Dominion transmission system via a three breaker switching station on Line 154 between Madisonville and Twitty's Creek 115 kV substations.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AF2-222 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AF2-222Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$1,080,391$1,080,391
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$11,332,601$11,332,601
Network Upgrades$4,742,414$4,742,414
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$18,005,235$18,005,235
Transient Stability$10,288,736$10,288,736
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0
AFS - Non-PJM Violations$0 **$0 **
Total$45,449,377$45,449,377

* Contributes to calculation for Security. See Security Requirement Section of this report for additional detail.

** This value reflects the results at the time of the report posting and it is subject to change. AFS – Non-PJM Violations are not subject to Security. For latest AFS – Non-PJM Violations, please refer to the latest Affected System Study Report for your project.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF2-222

Security has been calculated for the AF2-222 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF2-222
Project(s): AF2-222
Final Agreement Security (A): $45,449,377
Portion of Costs Already Paid (B): $2,061,057
Revised Net Security (C): A − B = $43,388,320
Security on Hand with PJM (D): $56,733,405
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

AF2-222 will interconnect with the Dominion transmission system at a new three breaker switching station on Line 154 between Madisonville and Twitty's Creek 115 kV substations. 

The required work for the interconnection of the New Service Request Project to the Dominion Transmission System is detailed in the following tables.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n8205.2

Re-arrange line 154 to loop into and out of the new three-breaker AF2-222 115 kV switching station.

$2,376,518$1,466,265$232,561$63,972$4,139,316$4,139,316
n9655.0

Remote end substation work at Chase City to support new interconnection substation

$67,868$35,494$18,904$6,323$128,589$128,589
n9656.0

Remote end substation work at Farmville to support new interconnection substation

$71,122$28,814$19,898$5,133$124,967$124,967
n9657.0

Remote end substation work at Pamplin to support new interconnection substation

$74,008$28,814$20,618$5,133$128,573$128,573
n9658.0

Remote end substation work at Twitty's Creek to support new interconnection substation

$107,219$71,832$29,121$12,797$220,969$220,969
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n8205.1

Build a new 115 kV three-breaker ring switching station located along line 154 from Pamplin Substation to Twitty Creek Substation.

$5,902,826$3,429,077$1,548,448$452,250$11,332,601$11,332,601
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

A 115 kV backbone structure and foundation within the fence of the Interconnection Substation, to terminate the Project Developer’s generator lead line. Line conductor from the structure to the bus position in the switchyard of the interconnection substation.

$649,633$236,109$162,373$32,276$1,080,391$1,080,391

Based on the scope of work for the Interconnection Facilities, it is expected to take 47 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

 

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2027 load flow model and the results were verified by Dominion.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AF2-222 was evaluated as a 167.0 MW (100.0 MW Capacity) injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BUCKING-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S-1
BreakerAC116.15 %699.0C811.9264.98
GD1DVP
6BUCKING-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC112.88 %571.52B645.1238.88
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC109.81 %1204.0C1322.0814.99
GD1DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC108.01 %1204.0C1300.4214.99
GD1DVP
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S-1
BreakerAC117.22 %684.0C801.7964.99
GD1DVP
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC113.89 %559.3B636.9938.89
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC110.41 %678.68B749.368.63
GD1DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 56372_SRT-S
BreakerAC113.54 %1056.8C1199.8612.15
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC106.13 %3940.0C4181.5236.24
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC104.17 %3940.0C4104.3335.06
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H1T567_SRT-A
BreakerAC103.4 %3940.0C4073.9135.65
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S_SENS
SingleAC101.85 %3220.44B3279.9723.07
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC102.49 %3144.0C3222.3725.81
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC102.39 %3144.0C3219.0826.18
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC102.39 %3144.0C3219.0826.18
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC102.38 %3144.0C3218.9226.18
GD1DVP
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC107.63 %678.68B730.458.64

Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.15 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:811.92
MW Contribution:64.98
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.96 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:845.48
MW Contribution:61.73
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957481AF2-042 C
50/50
98.10798.107
924322AB2-079 E O1
Adder
2.3152941176470591.968
946302AF1-294 E
50/50
8.1418.141
943902AF1-058 E
Adder
1.841.564
925612AC1-036 E
50/50
1.961.96
924312AB2-078 E O1
Adder
2.3152941176470591.968
926274AC1-105 E
Adder
4.0129411764705883.411
938821AE1-108 C
Adder
-10.607058823529412-9.016
924302AB2-077 E O1
Adder
2.3152941176470591.968
942752AE2-291 E
Adder
5.4329411764705894.618
3151531CLOVER1
50/50
22.49922.499
3138533PONTONDP
50/50
1.7321.732
936262AD2-033 E
50/50
18.44618.446
958211AF2-115 C
50/50
5.8465.846
316336AC2-165 C
Adder
-5.905882352941176-5.02
934622AD1-088 E
50/50
9.1029.102
934612AD1-087 E
Adder
6.3835294117647065.426
927255AC1-221 E
Adder
4.1458823529411773.524
3147133PAMPLIN
50/50
2.7572.757
316322AB2-045 C
50/50
1.2941.294
927264AC1-222 E
Adder
5.52000000000000054.692
936261AD2-033 C
50/50
27.66927.669
3144293JTRSVLE
50/50
1.0761.076
961791AG1-021 C
50/50
4.6774.677
962562AG1-105 E
Adder
9.4541176470588238.036
924032AB2-045 E
50/50
5.85.8
964242AG1-285 E
50/50
16.7716.77
924162AB2-060 E OP
Adder
7.6670588235294136.517
964792AG1-342 E
Adder
3.6952941176470593.141
932763AC2-100 E
Adder
2.72941176470588242.32
937482AD2-202 E
Adder
1.86823529411764721.588
961792AG1-021 E
50/50
3.9843.984
941011AE2-092 C
Adder
-9.729411764705882-8.27
942462AE2-259 E
50/50
20.7620.76
964791AG1-342 C
Adder
5.5435294117647054.712
925997AC1-075 E
Adder
3.31294117647058832.816
924022AB2-043 E O1
Adder
9.122352941176477.754
3147223TWITTYS
50/50
2.1732.173
959312AF2-222 E
50/50
26.06826.068
926024AC1-080 E
Adder
1.09882352941176480.934
964241AG1-285 C
50/50
25.15525.155
316034AC1-036 C
50/50
0.5350.535
958212AF2-115 E
50/50
4.984.98
962561AG1-105 C
Adder
14.18117647058823612.054
925785AC1-054 E
Adder
3.35529411764705852.852
959311AF2-222 C
50/50
38.90838.908
942751AE2-291 C
Adder
8.1482352941176476.926
957482AF2-042 E
50/50
65.40565.405
934621AD1-088 C
50/50
18.90418.904
946301AF1-294 C
50/50
9.6139.613
942461AE2-259 C
50/50
31.1431.14
935172AD1-152 E
Adder
8.887.548
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1652.165
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.04736.047
CPLELTFEXP_CPLE->PJM
CLTF
4.5424.542
TVALTFEXP_TVA->PJM
CLTF
2.0142.014
O66PJM->LTFIMP_O-066
CMTX_NF
5.1335.133
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.3429.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.2887.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.2261.226
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
NYPJM->LTFIMP_NY
CLTF
0.3840.384
LGEELTFEXP_LGEE->PJM
CLTF
0.3670.367
WECLTFEXP_WEC->PJM
CLTF
0.1940.194
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8050.805
SIGELTFEXP_SIGE->PJM
CLTF
0.0740.074

Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.88 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:645.12
MW Contribution:38.88
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.83 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:684.85
MW Contribution:36.94
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
313506AB1-173 C OP
80/20
0.5620.562
3151361ROSEMG1
80/20
0.6210.621
957481AF2-042 C
80/20
97.99997.999
316181AB2-040 GEN
80/20
0.6330.633
3156063AA2-053SOLA
80/20
0.6790.679
3151281ROARAP4
80/20
0.6440.644
316238AB2-078 C O1
80/20
0.5670.567
316237AB2-079 C O1
80/20
0.5670.567
938821AE1-108 C
Adder
-10.596470588235293-9.007
3151411GASTONB
80/20
0.9230.923
3151261ROARAP2
80/20
0.6810.681
3147043LAWRENC
80/20
0.2660.266
3151621KERR 5
80/20
1.5611.561
316222AC1-221 C
80/20
1.5791.579
966621AG1-532 C
80/20
0.7060.706
316003AC1-222 C
80/20
1.3481.348
936161AD2-022 C
80/20
3.6193.619
316129AC1-054 C
80/20
1.1891.189
3151531CLOVER1
80/20
22.47122.471
316131AB2-060 C
80/20
2.662.66
3138533PONTONDP
80/20
1.7311.731
316118AC1-105 C
80/20
1.3691.369
316217AC1-145 C
80/20
0.1690.169
3151381ROSEMG2
80/20
0.2910.291
934321AD1-056 C
80/20
1.9781.978
934331AD1-057 C
80/20
1.1031.103
958211AF2-115 C
80/20
5.8435.843
316336AC2-165 C
Adder
-5.884705882352941-5.002
934611AD1-087 C
80/20
2.212.21
316049AB1-081 C OP
80/20
0.4770.477
3151611KERR 4
80/20
1.5611.561
316322AB2-045 C
80/20
1.2941.294
960081AF2-299 C
80/20
0.9410.941
3151391GASTONA
80/20
0.9230.923
3151631KERR 6
80/20
1.5611.561
936261AD2-033 C
80/20
27.64927.649
3144293JTRSVLE
80/20
1.0761.076
961791AG1-021 C
80/20
4.6754.675
316248AF1-058 C
80/20
0.450.45
936171AD2-023 C
80/20
2.1112.111
941801AE2-185 C
80/20
1.9561.956
316087AB2-174 C
80/20
0.5880.588
313527AB2-043 C
80/20
0.9080.908
3151591KERR 2
80/20
1.5611.561
316283AC2-100 C
80/20
1.2351.235
316011AB1-132 C OP
80/20
0.7050.705
932631AC2-084 C
80/20
0.3610.361
316274AC1-208 C
80/20
3.5413.541
3151311EDGECMA
80/20
5.0375.037
3151601KERR 3
80/20
1.5611.561
3151581KERR 1
80/20
0.5570.557
3152661PLYWOOD A
80/20
1.751.75
941011AE2-092 C
Adder
-9.714117647058824-8.257
946281AF1-292 C
80/20
0.7790.779
926071AC1-086 C
80/20
6.3516.351
3151541CLOVER2
80/20
22.26122.261
964241AG1-285 C
80/20
25.13225.132
316034AC1-036 C
80/20
0.5340.534
962561AG1-105 C
80/20
14.16114.161
942671AE2-283 C
80/20
1.5211.521
316210AC1-098 C
80/20
0.3390.339
316327AA2-057 C
80/20
0.4730.473
316239AB2-077 C O1
80/20
0.5670.567
935171AD1-152 C
80/20
2.1552.155
964791AG1-342 C
80/20
5.5355.535
316263AC1-034 C
80/20
2.2292.229
959311AF2-222 C
80/20
38.88338.883
942751AE2-291 C
80/20
8.1298.129
3151561HALLBR1
80/20
0.5580.558
3137643SOCKMAN
80/20
0.3520.352
316212AC1-099 C
80/20
0.1130.113
316319Z2-044 C
80/20
0.0740.074
937481AD2-202 C
80/20
0.6410.641
3151641KERR 7
80/20
1.5611.561
316205AC1-080 C
80/20
0.3190.319
316123AC1-075 C
80/20
0.9530.953
3156073AA1-063SOLA
80/20
0.5840.584
3151371ROSEMS1
80/20
0.3840.384
934621AD1-088 C
80/20
18.88618.886
316359AB2-059 C OP
80/20
0.5620.562
946301AF1-294 C
80/20
9.6099.609
942461AE2-259 C
80/20
31.13331.133
316197AC1-042 C
80/20
0.1420.142
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1162.116
CBM South 2LTFEXP_CBM-S2->PJM
CBM
35.17235.172
CPLELTFEXP_CPLE->PJM
CLTF
4.444.44
TVALTFEXP_TVA->PJM
CLTF
1.9591.959
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.0479.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.0847.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1891.189
LAGNLTFEXP_LAGN->PJM
CLTF
2.5082.508
NYPJM->LTFIMP_NY
CLTF
0.3750.375
LGEELTFEXP_LGEE->PJM
CLTF
0.3550.355
WECLTFEXP_WEC->PJM
CLTF
0.1880.188
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.81 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1322.08
MW Contribution:14.99
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.0 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1396.59
MW Contribution:13.57
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3145393UNCAMP
Adder
2.10941176470588231.793
933981AD1-022 C
Adder
3.6082352941176473.067
900672V4-068 E
Adder
0.172941176470588240.147
3151411GASTONB
50/50
2.2972.297
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
924302AB2-077 E O1
Adder
0.7917647058823530.673
316315AB2-025 C
50/50
0.4720.472
946282AF1-292 E
50/50
0.860.86
944012AF1-069 E
50/50
3.683.68
3151051BRUNSWICKS1
50/50
12.19612.196
917512Z2-088 E OP1
Adder
2.742.329
3138533PONTONDP
Adder
0.310588235294117660.264
923852AB2-025 E
50/50
1.3441.344
939412AE1-173 E
Adder
33.1823529411764728.205
961941AG1-037 C
Adder
0.251764705882352950.214
961942AG1-037 E
Adder
0.167058823529411760.142
3151381ROSEMG2
50/50
0.7050.705
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934321AD1-056 C
Adder
4.1835294117647063.556
934332AD1-057 E
Adder
1.21529411764705891.033
934322AD1-056 E
Adder
2.26941176470588251.929
934331AD1-057 C
Adder
2.33411764705882341.984
927022AC1-189 E
Adder
2.28117647058823541.939
925595AC1-034 E
Adder
3.0235294117647062.57
936262AD2-033 E
Adder
4.6729411764705883.972
958211AF2-115 C
Adder
1.04823529411764720.891
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
933982AD1-022 E
Adder
1.9647058823529411.67
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
927146AC1-208 E
Adder
2.45294117647058842.085
920692AA2-178 E
Adder
1.43529411764705881.22
966622AG1-532 E
50/50
0.7790.779
3152441Z1-086 ST
50/50
13.14613.146
922923AB1-081 E OP
Adder
2.24941176470588241.912
3147133PAMPLIN
Adder
0.454117647058823570.386
927264AC1-222 E
Adder
2.16588235294117661.841
316087AB2-174 C
50/50
0.9180.918
932632AC2-084 E
Adder
1.89764705882352951.613
926214AC1-099 E
Adder
0.70941176470588230.603
964242AG1-285 E
Adder
5.0011764705882364.251
924162AB2-060 E OP
Adder
2.522.142
3145413WATKINS
Adder
0.265882352941176460.226
960081AF2-299 C
50/50
1.5581.558
3151391GASTONA
50/50
2.2972.297
926072AC1-086 E
50/50
7.1937.193
944011AF1-069 C
50/50
9.4749.474
963041AG1-153 C
50/50
3.9773.977
936261AD2-033 C
Adder
7.0082352941176475.957
961791AG1-021 C
Adder
0.83882352941176460.713
962562AG1-105 E
Adder
3.39764705882352922.888
936171AD2-023 C
Adder
2.23058823529411751.896
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
924516AB2-100 E1
50/50
2.6782.678
918512AA1-065 E OP
Adder
2.60941176470588232.218
966621AG1-532 C
50/50
1.1691.169
918532AA1-067 E
Adder
0.367058823529411770.312
924022AB2-043 E O1
Adder
3.07764705882352942.616
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
926024AC1-080 E
Adder
0.454117647058823570.386
936161AD2-022 C
Adder
3.8235294117647063.25
316141AB2-099 E
Adder
0.125882352941176470.107
316088AB2-174 E
50/50
5.0815.081
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151361ROSEMG1
50/50
1.5051.505
957481AF2-042 C
50/50
34.00834.008
961672AG1-007 E
Adder
0.30352941176470590.258
924322AB2-079 E O1
Adder
0.7917647058823530.673
946302AF1-294 E
Adder
1.46000000000000021.241
943902AF1-058 E
Adder
0.71411764705882350.607
316023AB2-100 C2
50/50
0.8890.889
960082AF2-299 E
50/50
1.0391.039
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
963042AG1-153 E
50/50
5.9665.966
927021AC1-189 C
Adder
4.5788235294117653.892
964241AG1-285 C
Adder
7.502352941176476.377
924152AB2-059 E OP
Adder
3.18705882352941172.709
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
936172AD2-023 E
Adder
1.21058823529411751.029
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
920042AA2-088 E OP
Adder
4.9317647058823534.192
934511AD1-075 C
Adder
3.2917647058823532.798
934521AD1-076 C
Adder
4.7823529411764714.065
3145723EMPORIA
50/50
0.3510.351
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
919692AA2-053 E OP
Adder
2.6788235294117652.277
925785AC1-054 E
Adder
2.1505882352941181.828
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
939411AE1-173 C
Adder
49.7729411764705942.307
3137643SOCKMAN
50/50
0.5020.502
3151031BRUNSWICKG2
50/50
5.8715.871
919710AA2-057 E
Adder
2.3988235294117652.039
942001AE2-212 C
Adder
-3.7917647058823527-3.223
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
3151371ROSEMS1
50/50
0.9320.932
957482AF2-042 E
50/50
22.67222.672
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
946301AF1-294 C
Adder
1.7247058823529411.466
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
936162AD2-022 E
Adder
2.29411764705882341.95
940541AE2-040 C
50/50
3.3223.322
940482AE2-033 E
50/50
12.29712.297
940481AE2-033 C
50/50
18.24118.241
923263AB1-132 E OP
50/50
4.64.6
316181AB2-040 GEN
50/50
0.9590.959
3151281ROARAP4
50/50
0.8680.868
925612AC1-036 E
Adder
0.47058823529411770.4
924312AB2-078 E O1
Adder
0.7917647058823530.673
926274AC1-105 E
Adder
1.50823529411764711.282
3143316POE
Adder
0.51176470588235290.435
316365AB2-100 C1
50/50
0.8890.889
926206AC1-098 E
Adder
2.14705882352941171.825
3151021BRUNSWICKG1
50/50
5.8715.871
3151041BRUNSWICKG3
50/50
5.8715.871
942462AE2-259 E
Adder
2.62.21
964791AG1-342 C
Adder
2.0188235294117651.716
925997AC1-075 E
Adder
1.36941176470588231.164
940492AE2-034 E
Adder
1.07647058823529430.915
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
918492AA1-063AE OP
Adder
2.40470588235294122.044
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
316274AC1-208 C
Adder
5.5235294117647074.695
917342Z2-044 E
Adder
0.36117647058823530.307
937482AD2-202 E
Adder
0.64705882352941180.55
3151311EDGECMA
Adder
9.4070588235294137.996
961792AG1-021 E
Adder
0.71411764705882350.607
964792AG1-342 E
Adder
1.34588235294117631.144
932763AC2-100 E
Adder
1.3917647058823531.183
934622AD1-088 E
Adder
2.72588235294117662.317
934612AD1-087 E
Adder
2.20941176470588241.878
927255AC1-221 E
Adder
2.0517647058823531.744
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.01 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1300.42
MW Contribution:14.99
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.2 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1374.95
MW Contribution:13.57
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
923852AB2-025 E
50/50
1.3441.344
939412AE1-173 E
Adder
33.1823529411764728.205
961941AG1-037 C
Adder
0.251764705882352950.214
961942AG1-037 E
Adder
0.167058823529411760.142
3151381ROSEMG2
50/50
0.7050.705
920692AA2-178 E
Adder
1.43529411764705881.22
966622AG1-532 E
50/50
0.7790.779
3152441Z1-086 ST
50/50
13.14613.146
922923AB1-081 E OP
Adder
2.24941176470588241.912
3147133PAMPLIN
Adder
0.454117647058823570.386
927264AC1-222 E
Adder
2.16588235294117661.841
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934321AD1-056 C
Adder
4.1835294117647063.556
934332AD1-057 E
Adder
1.21529411764705891.033
934322AD1-056 E
Adder
2.26941176470588251.929
934331AD1-057 C
Adder
2.33411764705882341.984
927022AC1-189 E
Adder
2.28117647058823541.939
925595AC1-034 E
Adder
3.0235294117647062.57
936262AD2-033 E
Adder
4.6729411764705883.972
958211AF2-115 C
Adder
1.04823529411764720.891
3145413WATKINS
Adder
0.265882352941176460.226
960081AF2-299 C
50/50
1.5581.558
3151391GASTONA
50/50
2.2972.297
926072AC1-086 E
50/50
7.1937.193
944011AF1-069 C
50/50
9.4749.474
963041AG1-153 C
50/50
3.9773.977
936261AD2-033 C
Adder
7.0082352941176475.957
961791AG1-021 C
Adder
0.83882352941176460.713
962562AG1-105 E
Adder
3.39764705882352922.888
936171AD2-023 C
Adder
2.23058823529411751.896
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
924516AB2-100 E1
50/50
2.6782.678
918512AA1-065 E OP
Adder
2.60941176470588232.218
966621AG1-532 C
50/50
1.1691.169
918532AA1-067 E
Adder
0.367058823529411770.312
924022AB2-043 E O1
Adder
3.07764705882352942.616
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
926024AC1-080 E
Adder
0.454117647058823570.386
936161AD2-022 C
Adder
3.8235294117647063.25
316141AB2-099 E
Adder
0.125882352941176470.107
316088AB2-174 E
50/50
5.0815.081
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151361ROSEMG1
50/50
1.5051.505
957481AF2-042 C
50/50
34.00834.008
961672AG1-007 E
Adder
0.30352941176470590.258
924322AB2-079 E O1
Adder
0.7917647058823530.673
946302AF1-294 E
Adder
1.46000000000000021.241
943902AF1-058 E
Adder
0.71411764705882350.607
316023AB2-100 C2
50/50
0.8890.889
960082AF2-299 E
50/50
1.0391.039
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
963042AG1-153 E
50/50
5.9665.966
927021AC1-189 C
Adder
4.5788235294117653.892
964241AG1-285 C
Adder
7.502352941176476.377
924152AB2-059 E OP
Adder
3.18705882352941172.709
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
936172AD2-023 E
Adder
1.21058823529411751.029
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
920042AA2-088 E OP
Adder
4.9317647058823534.192
934511AD1-075 C
Adder
3.2917647058823532.798
934521AD1-076 C
Adder
4.7823529411764714.065
3145723EMPORIA
50/50
0.3510.351
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
919692AA2-053 E OP
Adder
2.6788235294117652.277
925785AC1-054 E
Adder
2.1505882352941181.828
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
939411AE1-173 C
Adder
49.7729411764705942.307
3137643SOCKMAN
50/50
0.5020.502
3151031BRUNSWICKG2
50/50
5.8715.871
919710AA2-057 E
Adder
2.3988235294117652.039
3145393UNCAMP
Adder
2.10941176470588231.793
933981AD1-022 C
Adder
3.6082352941176473.067
900672V4-068 E
Adder
0.172941176470588240.147
3151411GASTONB
50/50
2.2972.297
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
924302AB2-077 E O1
Adder
0.7917647058823530.673
940541AE2-040 C
50/50
3.3223.322
940482AE2-033 E
50/50
12.29712.297
940481AE2-033 C
50/50
18.24118.241
923263AB1-132 E OP
50/50
4.64.6
316181AB2-040 GEN
50/50
0.9590.959
3151281ROARAP4
50/50
0.8680.868
925612AC1-036 E
Adder
0.47058823529411770.4
924312AB2-078 E O1
Adder
0.7917647058823530.673
926274AC1-105 E
Adder
1.50823529411764711.282
316315AB2-025 C
50/50
0.4720.472
946282AF1-292 E
50/50
0.860.86
944012AF1-069 E
50/50
3.683.68
3151051BRUNSWICKS1
50/50
12.19612.196
917512Z2-088 E OP1
Adder
2.742.329
3138533PONTONDP
Adder
0.310588235294117660.264
3143316POE
Adder
0.51176470588235290.435
316365AB2-100 C1
50/50
0.8890.889
926206AC1-098 E
Adder
2.14705882352941171.825
3151021BRUNSWICKG1
50/50
5.8715.871
3151041BRUNSWICKG3
50/50
5.8715.871
942462AE2-259 E
Adder
2.62.21
964791AG1-342 C
Adder
2.0188235294117651.716
925997AC1-075 E
Adder
1.36941176470588231.164
940492AE2-034 E
Adder
1.07647058823529430.915
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
918492AA1-063AE OP
Adder
2.40470588235294122.044
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
316274AC1-208 C
Adder
5.5235294117647074.695
917342Z2-044 E
Adder
0.36117647058823530.307
937482AD2-202 E
Adder
0.64705882352941180.55
3151311EDGECMA
Adder
9.4070588235294137.996
961792AG1-021 E
Adder
0.71411764705882350.607
942001AE2-212 C
Adder
-3.7917647058823527-3.223
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
3151371ROSEMS1
50/50
0.9320.932
957482AF2-042 E
50/50
22.67222.672
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
946301AF1-294 C
Adder
1.7247058823529411.466
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
936162AD2-022 E
Adder
2.29411764705882341.95
316087AB2-174 C
50/50
0.9180.918
932632AC2-084 E
Adder
1.89764705882352951.613
926214AC1-099 E
Adder
0.70941176470588230.603
964242AG1-285 E
Adder
5.0011764705882364.251
924162AB2-060 E OP
Adder
2.522.142
964792AG1-342 E
Adder
1.34588235294117631.144
932763AC2-100 E
Adder
1.3917647058823531.183
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
933982AD1-022 E
Adder
1.9647058823529411.67
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
927146AC1-208 E
Adder
2.45294117647058842.085
934622AD1-088 E
Adder
2.72588235294117662.317
934612AD1-087 E
Adder
2.20941176470588241.878
927255AC1-221 E
Adder
2.0517647058823531.744
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132

Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.22 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:801.79
MW Contribution:64.99
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.59 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:831.68
MW Contribution:61.74
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957481AF2-042 C
50/50
98.12598.125
924322AB2-079 E O1
Adder
2.3164705882352941.969
946302AF1-294 E
50/50
8.1428.142
943902AF1-058 E
Adder
1.841.564
925612AC1-036 E
50/50
1.961.96
924312AB2-078 E O1
Adder
2.3164705882352941.969
926274AC1-105 E
Adder
4.0141176470588233.412
938821AE1-108 C
Adder
-10.602352941176472-9.012
924302AB2-077 E O1
Adder
2.3164705882352941.969
942752AE2-291 E
Adder
5.4352941176470594.62
946282AF1-292 E
Adder
0.51882352941176470.441
3151531CLOVER1
50/50
22.50322.503
3138533PONTONDP
50/50
1.7321.732
936262AD2-033 E
50/50
18.44918.449
958211AF2-115 C
50/50
5.8475.847
316336AC2-165 C
Adder
-5.9023529411764715-5.017
934622AD1-088 E
50/50
9.1039.103
934612AD1-087 E
Adder
6.3847058823529415.427
927255AC1-221 E
Adder
4.1470588235294123.525
966622AG1-532 E
Adder
0.47058823529411770.4
3147133PAMPLIN
50/50
2.7572.757
927264AC1-222 E
Adder
5.5211764705882354.693
960081AF2-299 C
Adder
0.94000000000000010.799
936261AD2-033 C
50/50
27.67327.673
3144293JTRSVLE
50/50
1.0761.076
961791AG1-021 C
50/50
4.6774.677
962562AG1-105 E
Adder
9.4564705882352958.038
964242AG1-285 E
50/50
16.77316.773
924162AB2-060 E OP
Adder
7.6694117647058836.519
964792AG1-342 E
Adder
3.6964705882352943.142
932763AC2-100 E
Adder
2.7305882352941182.321
937482AD2-202 E
Adder
1.86823529411764721.588
961792AG1-021 E
50/50
3.9843.984
941011AE2-092 C
Adder
-9.724705882352941-8.266
960082AF2-299 E
Adder
0.62705882352941180.533
946281AF1-292 C
Adder
0.77764705882352950.661
942462AE2-259 E
50/50
20.76320.763
964791AG1-342 C
Adder
5.5447058823529414.713
925997AC1-075 E
Adder
3.3141176470588242.817
966621AG1-532 C
Adder
0.70470588235294120.599
924022AB2-043 E O1
Adder
9.1247058823529417.756
3147223TWITTYS
50/50
2.1732.173
959312AF2-222 E
50/50
26.07226.072
926024AC1-080 E
Adder
1.10.935
964241AG1-285 C
50/50
25.15925.159
316034AC1-036 C
50/50
0.5350.535
958212AF2-115 E
50/50
4.9814.981
962561AG1-105 C
Adder
14.18352941176470612.056
3145723EMPORIA
Adder
0.21647058823529410.184
925785AC1-054 E
Adder
3.35647058823529452.853
959311AF2-222 C
50/50
38.91438.914
942751AE2-291 C
Adder
8.1517647058823536.929
957482AF2-042 E
50/50
65.41765.417
934621AD1-088 C
50/50
18.90718.907
946301AF1-294 C
50/50
9.6159.615
942461AE2-259 C
50/50
31.14431.144
935172AD1-152 E
Adder
8.8823529411764717.55
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1672.167
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.10836.108
CPLELTFEXP_CPLE->PJM
CLTF
4.5484.548
TVALTFEXP_TVA->PJM
CLTF
2.0222.022
O66PJM->LTFIMP_O-066
CMTX_NF
5.0935.093
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.4439.443
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.3277.327
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.2351.235
LAGNLTFEXP_LAGN->PJM
CLTF
2.5882.588
NYPJM->LTFIMP_NY
CLTF
0.3810.381
LGEELTFEXP_LGEE->PJM
CLTF
0.370.37
WECLTFEXP_WEC->PJM
CLTF
0.1960.196
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7990.799
SIGELTFEXP_SIGE->PJM
CLTF
0.0750.075

Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.89 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:636.99
MW Contribution:38.89
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.98 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:676.62
MW Contribution:36.95
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
313506AB1-173 C OP
80/20
0.5620.562
3151361ROSEMG1
80/20
0.6210.621
957481AF2-042 C
80/20
98.01698.016
316181AB2-040 GEN
80/20
0.6330.633
3156063AA2-053SOLA
80/20
0.680.68
3151281ROARAP4
80/20
0.6450.645
316238AB2-078 C O1
80/20
0.5670.567
316237AB2-079 C O1
80/20
0.5670.567
938821AE1-108 C
Adder
-10.591764705882353-9.003
3151411GASTONB
80/20
0.9240.924
3151261ROARAP2
80/20
0.6820.682
3147043LAWRENC
80/20
0.2660.266
3151621KERR 5
80/20
1.5621.562
316222AC1-221 C
80/20
1.581.58
966621AG1-532 C
80/20
0.7060.706
316003AC1-222 C
80/20
1.3491.349
936161AD2-022 C
80/20
3.6223.622
316129AC1-054 C
80/20
1.1891.189
3151531CLOVER1
80/20
22.47622.476
316131AB2-060 C
80/20
2.6612.661
3138533PONTONDP
80/20
1.7321.732
316118AC1-105 C
80/20
1.3691.369
316217AC1-145 C
80/20
0.1690.169
3151381ROSEMG2
80/20
0.2910.291
934321AD1-056 C
80/20
1.981.98
934331AD1-057 C
80/20
1.1051.105
958211AF2-115 C
80/20
5.8445.844
316336AC2-165 C
Adder
-5.881176470588235-4.999
934611AD1-087 C
80/20
2.212.21
316049AB1-081 C OP
80/20
0.4780.478
3151611KERR 4
80/20
1.5621.562
960081AF2-299 C
80/20
0.9420.942
3151391GASTONA
80/20
0.9240.924
3151631KERR 6
80/20
1.5621.562
936261AD2-033 C
80/20
27.65427.654
3144293JTRSVLE
80/20
1.0761.076
961791AG1-021 C
80/20
4.6754.675
316248AF1-058 C
80/20
0.450.45
936171AD2-023 C
80/20
2.1132.113
941801AE2-185 C
80/20
1.9581.958
316087AB2-174 C
80/20
0.5890.589
313527AB2-043 C
80/20
0.9080.908
3151591KERR 2
80/20
1.5621.562
316283AC2-100 C
80/20
1.2351.235
316011AB1-132 C OP
80/20
0.7060.706
316263AC1-034 C
80/20
2.2322.232
959311AF2-222 C
80/20
38.88938.889
942751AE2-291 C
80/20
8.1328.132
3151561HALLBR1
80/20
0.5580.558
932631AC2-084 C
80/20
0.3610.361
316274AC1-208 C
80/20
3.5443.544
3151311EDGECMA
80/20
5.0435.043
3151601KERR 3
80/20
1.5621.562
3151581KERR 1
80/20
0.5580.558
3152661PLYWOOD A
80/20
1.751.75
941011AE2-092 C
Adder
-9.709411764705882-8.253
946281AF1-292 C
80/20
0.7790.779
926071AC1-086 C
80/20
6.3586.358
3151541CLOVER2
80/20
22.26622.266
964241AG1-285 C
80/20
25.13725.137
316034AC1-036 C
80/20
0.5340.534
962561AG1-105 C
80/20
14.16414.164
942671AE2-283 C
80/20
1.5231.523
316210AC1-098 C
80/20
0.3390.339
316327AA2-057 C
80/20
0.4730.473
316239AB2-077 C O1
80/20
0.5670.567
935171AD1-152 C
80/20
2.1562.156
964791AG1-342 C
80/20
5.5375.537
3137643SOCKMAN
80/20
0.3530.353
316212AC1-099 C
80/20
0.1140.114
316319Z2-044 C
80/20
0.0740.074
937481AD2-202 C
80/20
0.6410.641
3151641KERR 7
80/20
1.5621.562
316205AC1-080 C
80/20
0.3190.319
316123AC1-075 C
80/20
0.9540.954
3156073AA1-063SOLA
80/20
0.5850.585
3151371ROSEMS1
80/20
0.3850.385
934621AD1-088 C
80/20
18.88918.889
316359AB2-059 C OP
80/20
0.5630.563
946301AF1-294 C
80/20
9.619.61
942461AE2-259 C
80/20
31.13731.137
316197AC1-042 C
80/20
0.1420.142
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1192.119
CBM South 2LTFEXP_CBM-S2->PJM
CBM
35.23335.233
CPLELTFEXP_CPLE->PJM
CLTF
4.4464.446
TVALTFEXP_TVA->PJM
CLTF
1.9681.968
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.1489.148
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.1237.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1991.199
LAGNLTFEXP_LAGN->PJM
CLTF
2.5182.518
NYPJM->LTFIMP_NY
CLTF
0.3720.372
LGEELTFEXP_LGEE->PJM
CLTF
0.3590.359
WECLTFEXP_WEC->PJM
CLTF
0.190.19
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.41 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:749.36
MW Contribution:8.63
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.4 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:769.65
MW Contribution:10.63
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3156083AA2-088SOLA
80/20
0.9350.935
313506AB1-173 C OP
80/20
2.2292.229
3151361ROSEMG1
80/20
3.9353.935
316005AA1-067 C
80/20
0.2210.221
957481AF2-042 C
80/20
24.2924.29
940541AE2-040 C
80/20
11.68811.688
940481AE2-033 C
80/20
63.40163.401
316181AB2-040 GEN
80/20
2.512.51
316174AB2-169_C
80/20
0.7190.719
3156063AA2-053SOLA
80/20
2.1572.157
3151281ROARAP4
80/20
2.0092.009
3156011CONETOE2SOL
80/20
1.1751.175
316238AB2-078 C O1
80/20
0.2290.229
316237AB2-079 C O1
80/20
0.2290.229
933981AD1-022 C
80/20
5.6845.684
3151411GASTONB
80/20
6.1746.174
3151261ROARAP2
80/20
2.1232.123
3147043LAWRENC
80/20
0.5790.579
3151621KERR 5
80/20
0.8610.861
966621AG1-532 C
80/20
3.2983.298
316315AB2-025 C
80/20
1.661.66
316129AC1-054 C
80/20
1.341.34
3151531CLOVER1
80/20
5.8145.814
316131AB2-060 C
80/20
1.0331.033
3138533PONTONDP
80/20
0.3360.336
316118AC1-105 C
80/20
0.4840.484
961941AG1-037 C
80/20
0.4820.482
943171AE2-346 C
80/20
0.2140.214
3151381ROSEMG2
80/20
1.8431.843
934321AD1-056 C
80/20
9.1989.198
934331AD1-057 C
80/20
5.1315.131
958211AF2-115 C
80/20
1.1341.134
316049AB1-081 C OP
80/20
1.4931.493
3151611KERR 4
80/20
0.8610.861
960081AF2-299 C
80/20
4.3984.398
3151391GASTONA
80/20
6.1746.174
3151631KERR 6
80/20
0.8610.861
936261AD2-033 C
80/20
8.0238.023
3144293JTRSVLE
80/20
0.2090.209
961791AG1-021 C
80/20
0.9070.907
316087AB2-174 C
80/20
2.4642.464
313527AB2-043 C
80/20
0.3630.363
3151591KERR 2
80/20
0.8610.861
3151151S HAMPT1
80/20
0.9560.956
932631AC2-084 C
80/20
1.171.17
316274AC1-208 C
80/20
11.22211.222
3151311EDGECMA
80/20
16.54816.548
3151601KERR 3
80/20
0.8610.861
3151581KERR 1
80/20
0.3070.307
3152661PLYWOOD A
80/20
0.6380.638
316023AB2-100 C2
80/20
2.7732.773
946281AF1-292 C
80/20
3.643.64
926071AC1-086 C
80/20
42.48542.485
316317KELFORD C
80/20
0.3690.369
927021AC1-189 C
80/20
7.5457.545
964241AG1-285 C
80/20
7.2197.219
316034AC1-036 C
80/20
0.1230.123
962561AG1-105 C
80/20
5.2835.283
316365AB2-100 C1
80/20
2.7732.773
316318V4-068 C
80/20
0.0750.075
316210AC1-098 C
80/20
1.0991.099
316327AA2-057 C
80/20
1.4881.488
316239AB2-077 C O1
80/20
0.2290.229
964791AG1-342 C
80/20
2.0342.034
934511AD1-075 C
80/20
4.8374.837
934521AD1-076 C
80/20
7.0267.026
316011AB1-132 C OP
80/20
4.7154.715
316263AC1-034 C
80/20
6.9786.978
959311AF2-222 C
80/20
8.6298.629
3152921DOMTR78
80/20
0.8530.853
316140AB2-099 C
80/20
0.0920.092
3137643SOCKMAN
80/20
1.2371.237
316212AC1-099 C
80/20
0.3680.368
316319Z2-044 C
80/20
0.2310.231
3151641KERR 7
80/20
0.8610.861
934501AD1-074 C
80/20
19.34719.347
3156021HOLLOMANSOL
80/20
1.5851.585
3156073AA1-063SOLA
80/20
1.8141.814
3151371ROSEMS1
80/20
2.4382.438
961671AG1-007 C
80/20
0.9120.912
934621AD1-088 C
80/20
4.4014.401
316359AB2-059 C OP
80/20
1.761.76
946301AF1-294 C
80/20
1.8641.864
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1852.185
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.08134.081
CPLELTFEXP_CPLE->PJM
CLTF
4.5834.583
TVALTFEXP_TVA->PJM
CLTF
2.0082.008
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.08611.086
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.537.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.351.35
LAGNLTFEXP_LAGN->PJM
CLTF
2.5652.565
NYPJM->LTFIMP_NY
CLTF
0.370.37
LGEELTFEXP_LGEE->PJM
CLTF
0.4270.427
WECLTFEXP_WEC->PJM
CLTF
0.2270.227
SIGELTFEXP_SIGE->PJM
CLTF
0.0830.083

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.54 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1199.86
MW Contribution:12.15
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.15 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1216.93
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926662AC1-147 E
Adder
0.448235294117647070.381
916192Z1-068 E
Adder
0.6682352941176470.568
939412AE1-173 E
50/50
44.67444.674
941032AE2-094 E
50/50
15.74915.749
941031AE2-094 C
50/50
35.16335.163
934321AD1-056 C
Adder
-2.142352941176471-1.821
934331AD1-057 C
Adder
-1.1952941176470588-1.016
936262AD2-033 E
Adder
2.89058823529411772.457
958211AF2-115 C
Adder
0.73529411764705890.625
938532AE1-072 E
Adder
3.1047058823529412.639
3146326AYDLETT TAP
Adder
0.455294117647058850.387
3152441Z1-086 ST
50/50
15.62215.622
3147133PAMPLIN
Adder
0.377647058823529450.321
927264AC1-222 E
Adder
1.781.513
941591AE2-156 C
Adder
6.1035294117647065.188
944601AF1-125 C
Adder
16.8341176470588214.309
944591AF1-124 C
Adder
17.15764705882352814.584
944011AF1-069 C
50/50
11.48911.489
963041AG1-153 C
50/50
4.6824.682
936261AD2-033 C
Adder
4.3352941176470593.685
961791AG1-021 C
Adder
0.58823529411764710.5
962562AG1-105 E
Adder
2.3352941176470591.985
919153AA1-139 E2
Adder
1.42117647058823531.208
940642AE2-051 E
50/50
9.9019.901
966621AG1-532 C
Adder
-1.14-0.969
924022AB2-043 E O1
Adder
1.75058823529411781.488
3147223TWITTYS
Adder
0.42235294117647060.359
959312AF2-222 E
Adder
4.8764705882352944.145
944581AF1-123 C
Adder
17.0976470588235314.533
957481AF2-042 C
50/50
35.70935.709
924322AB2-079 E O1
Adder
0.45058823529411770.383
946302AF1-294 E
Adder
1.02352941176470580.87
943902AF1-058 E
Adder
0.58823529411764710.5
944582AF1-123 E
Adder
39.15058823529411633.278
944592AF1-124 E
Adder
39.2929411764705933.399
923832AB2-022 E
Adder
0.374117647058823550.318
946281AF1-292 C
Adder
-1.2576470588235293-1.069
963042AG1-153 E
50/50
7.0227.022
3151541CLOVER2
50/50
7.7177.717
964241AG1-285 C
Adder
5.9952941176470595.096
958212AF2-115 E
Adder
0.62588235294117660.532
962561AG1-105 C
Adder
3.50352941176470622.978
944641AF1-129 C
Adder
-99.89764705882352-84.913
316240AF1-291 C
Adder
-2.2705882352941176-1.93
919152AA1-139 E1
Adder
1.42117647058823531.208
3145723EMPORIA
Adder
-0.3270588235294118-0.278
959311AF2-222 C
Adder
7.2776470588235296.186
913392Y1-086 E
Adder
0.66235294117647060.563
939411AE1-173 C
50/50
67.01167.011
3137643SOCKMAN
Adder
-0.34352941176470586-0.292
3151031BRUNSWICKG2
50/50
6.916.91
937481AD2-202 C
50/50
0.2220.222
942001AE2-212 C
Adder
-2.8705882352941177-2.44
934065AD1-033 E
Adder
1.87294117647058831.592
937226AE2-253 E
Adder
2.081.768
957482AF2-042 E
50/50
23.80623.806
934621AD1-088 C
50/50
5.5965.596
946301AF1-294 C
Adder
1.2082352941176471.027
942461AE2-259 C
Adder
3.32588235294117632.827
932046AC2-012 E
Adder
4.4317647058823533.767
938531AE1-072 C
Adder
5.95529411764705955.062
3152411Z1-086 GT1
50/50
8.9758.975
924302AB2-077 E O1
Adder
0.45058823529411770.383
925612AC1-036 E
Adder
0.381176470588235340.324
924312AB2-078 E O1
Adder
0.45058823529411770.383
926274AC1-105 E
Adder
1.15529411764705880.982
944012AF1-069 E
50/50
4.4634.463
3151051BRUNSWICKS1
50/50
14.35614.356
3151531CLOVER1
50/50
7.797.79
3138533PONTONDP
Adder
0.217647058823529420.185
3151021BRUNSWICKG1
50/50
6.916.91
3151041BRUNSWICKG3
50/50
6.916.91
942462AE2-259 E
Adder
2.21764705882352951.885
964791AG1-342 C
Adder
1.43529411764705881.22
933292AC2-141 E
Adder
6.3529411764705895.4
944602AF1-125 E
Adder
38.536470588235332.756
3145506HICKORY
Adder
0.80470588235294130.684
957871AF2-081 C
Adder
3.47411764705882352.953
937482AD2-202 E
50/50
0.6470.647
961792AG1-021 E
Adder
0.50117647058823530.426
935172AD1-152 E
Adder
3.1047058823529412.639
925522AC1-027 E
Adder
0.430588235294117660.366
926755AC1-161 E
Adder
6.3529411764705895.4
933291AC2-141 C
Adder
14.88235294117647112.65
957872AF2-081 E
Adder
1.48941176470588241.266
964242AG1-285 E
Adder
3.99647058823529383.397
924162AB2-060 E OP
Adder
1.4435294117647061.227
964792AG1-342 E
Adder
0.95647058823529410.813
932763AC2-100 E
Adder
1.14235294117647060.971
940641AE2-051 C
50/50
14.85114.851
3152431Z1-086 GT3
50/50
8.9728.972
3152421Z1-086 GT2
50/50
8.9728.972
934622AD1-088 E
50/50
2.6942.694
934612AD1-087 E
50/50
2.212.21
934611AD1-087 C
50/50
0.7660.766
927255AC1-221 E
Adder
1.70117647058823531.446
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9681.968
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.24536.245
CPLELTFEXP_CPLE->PJM
CLTF
4.1284.128
TVALTFEXP_TVA->PJM
CLTF
2.2832.283
O66PJM->LTFIMP_O-066
CMTX_NF
6.1826.182
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.10812.108
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4868.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4991.499
LAGNLTFEXP_LAGN->PJM
CLTF
2.9182.918
NYPJM->LTFIMP_NY
CLTF
0.4470.447
LGEELTFEXP_LGEE->PJM
CLTF
0.4670.467
WECLTFEXP_WEC->PJM
CLTF
0.2490.249
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9710.971
SIGELTFEXP_SIGE->PJM
CLTF
0.0920.092

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.13 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4181.52
MW Contribution:36.24
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.66 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4635.61
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150981CHESPKA
50/50
0.6670.667
961611AG1-000B C
Adder
19.52941176470588416.6
316375AC2-012 C
50/50
2.0662.066
313526AB2-022 C
50/50
0.5790.579
940541AE2-040 C
Adder
4.263.621
940482AE2-033 E
Adder
16.1613.736
940481AE2-033 C
Adder
23.97176470588235420.376
923263AB1-132 E OP
Adder
8.8564705882352937.528
925612AC1-036 E
Adder
1.13647058823529410.966
924312AB2-078 E O1
Adder
1.84705882352941191.57
932046AC2-012 E
50/50
20.04320.043
958161AF2-110 C
Adder
2.04352941176470631.737
316017AA1-139 ULT1
50/50
1.6761.676
938531AE1-072 C
50/50
27.18327.183
3145393UNCAMP
Adder
9.0117647058823537.66
933981AD1-022 C
Adder
13.02235294117647211.069
900672V4-068 E
Adder
0.52352941176470590.445
3152411Z1-086 GT1
50/50
18.60518.605
924302AB2-077 E O1
Adder
1.84705882352941191.57
3151101ELIZAR3
50/50
4.9744.974
3151081ELIZAR1
50/50
4.9124.912
3151091ELIZAR2
50/50
4.8264.826
316315AB2-025 C
50/50
0.6050.605
946282AF1-292 E
Adder
1.49529411764705871.271
944012AF1-069 E
50/50
9.0749.074
3151051BRUNSWICKS1
50/50
30.03530.035
917512Z2-088 E OP1
Adder
6.9717647058823535.926
926662AC1-147 E
50/50
2.0262.026
916192Z1-068 E
50/50
2.92.9
957492AF2-043 E
Adder
2.16705882352941171.842
923852AB2-025 E
50/50
1.7231.723
939412AE1-173 E
50/50
105.86105.86
961941AG1-037 C
Adder
0.74117647058823530.63
961942AG1-037 E
Adder
0.494117647058823550.42
941032AE2-094 E
50/50
32.01732.017
941031AE2-094 C
50/50
71.48571.485
934321AD1-056 C
Adder
8.927.582
934332AD1-057 E
Adder
2.5917647058823532.203
934322AD1-056 E
Adder
4.8388235294117664.113
934331AD1-057 C
Adder
4.9764705882352954.23
927022AC1-189 E
Adder
5.9882352941176475.09
925595AC1-034 E
Adder
7.0494117647058835.992
316084AB2-161 E
Adder
7.2141176470588236.132
3145946PLYMOUTH TP
Adder
0.48235294117647060.41
933982AD1-022 E
Adder
7.0894117647058836.026
940641AE2-051 C
50/50
31.3831.38
3152431Z1-086 GT3
50/50
18.59918.599
3152421Z1-086 GT2
50/50
18.59918.599
927146AC1-208 E
Adder
5.74470588235294164.883
934622AD1-088 E
Adder
6.6576470588235295.659
934612AD1-087 E
Adder
5.3905882352941184.582
943461AF1-017 C
Adder
1.91529411764705881.628
932596AC2-079 E
Adder
13.36941176470588411.364
316311AC2-079 C
Adder
8.1941176470588236.965
938532AE1-072 E
50/50
14.1714.17
3146326AYDLETT TAP
50/50
2.0962.096
917122Z2-027 E
Adder
2.061.751
920692AA2-178 E
Adder
6.1741176470588245.248
966622AG1-532 E
Adder
1.35411764705882361.151
3152441Z1-086 ST
50/50
32.38632.386
922923AB1-081 E OP
Adder
5.2458823529411764.459
936666AD2-085 E
Adder
7.9705882352941196.775
941591AE2-156 C
50/50
27.4127.41
316316AC1-027 C
50/50
0.4870.487
944601AF1-125 C
50/50
69.52369.523
944591AF1-124 C
50/50
70.86170.861
938771AE1-103 C
Adder
4.3470588235294113.695
3145413WATKINS
Adder
1.02235294117647070.869
960081AF2-299 C
Adder
2.70823529411764732.302
926072AC1-086 E
Adder
13.85058823529411711.773
944011AF1-069 C
50/50
23.35723.357
963041AG1-153 C
50/50
9.7959.795
936261AD2-033 C
Adder
6.71764705882352955.71
962562AG1-105 E
Adder
8.0317647058823526.827
3150921YORKTN3
Adder
152.65647058823532129.758
3145256KINGFORK
Adder
1.48823529411764691.265
925522AC1-027 E
50/50
1.8771.877
926755AC1-161 E
50/50
20.76320.763
933291AC2-141 C
50/50
48.6448.64
941102AE2-104 E
Adder
7.966.766
957872AF2-081 E
50/50
6.6346.634
932632AC2-084 E
Adder
4.6458823529411763.949
926214AC1-099 E
Adder
1.73647058823529421.476
964242AG1-285 E
Adder
11.97764705882352810.181
924162AB2-060 E OP
Adder
5.8752941176470594.994
964792AG1-342 E
Adder
3.1905882352941182.712
939191AE1-149 C
Adder
13.15411764705882411.181
3143316POE
Adder
1.71764705882352931.46
901082W1-029 E
Adder
48.63529411764706441.34
926206AC1-098 E
Adder
5.25647058823529444.468
3151021BRUNSWICKG1
50/50
14.45814.458
3151041BRUNSWICKG3
50/50
14.45814.458
964791AG1-342 C
Adder
4.7858823529411764.068
942341AE2-247 C
Adder
2.11764705882352941.8
943462AF1-017 E
Adder
3.12588235294117662.657
958162AF2-110 E
Adder
3.24941176470588242.762
316388AE2-253 GEN
50/50
3.0473.047
919153AA1-139 E2
50/50
6.336.33
934512AD1-075 E
Adder
6.3941176470588235.435
934502AD1-074 E
Adder
25.5776470588235321.741
924516AB2-100 E1
Adder
4.23058823529411753.596
918512AA1-065 E OP
Adder
8.1470588235294116.925
940642AE2-051 E
50/50
20.9220.92
966621AG1-532 C
Adder
2.0317647058823531.727
918532AA1-067 E
Adder
1.02823529411764710.874
924022AB2-043 E O1
Adder
7.1670588235294126.092
3147223TWITTYS
Adder
1.2588235294117651.07
959312AF2-222 E
Adder
14.53882352941176512.358
316185AD1-033 C
50/50
1.9111.911
944581AF1-123 C
50/50
70.6170.61
941101AE2-104 C
Adder
5.00705882352941254.256
316320Y1-086 C
50/50
0.3390.339
316141AB2-099 E
Adder
0.370588235294117660.315
316088AB2-174 E
Adder
9.4435294117647068.027
923994AB2-040_E
Adder
8.9094117647058837.573
957481AF2-042 C
50/50
83.22783.227
961672AG1-007 E
Adder
0.75529411764705890.642
924322AB2-079 E O1
Adder
1.84705882352941191.57
943902AF1-058 E
Adder
1.71882352941176491.461
316349AD2-085 C
Adder
4.8858823529411764.153
935112AD1-144 E
Adder
1.38117647058823521.174
944582AF1-123 E
50/50
161.69161.69
944592AF1-124 E
50/50
162.275162.275
923832AB2-022 E
50/50
1.9081.908
938772AE1-103 E
Adder
6.0023529411764715.102
916042Z1-036 E
Adder
43.3141176470588236.817
960082AF2-299 E
Adder
1.80588235294117651.535
946281AF1-292 C
Adder
2.24235294117647041.906
926071AC1-086 C
Adder
30.4329411764705925.868
963042AG1-153 E
50/50
14.69214.692
927021AC1-189 C
Adder
12.02000000000000110.217
964241AG1-285 C
Adder
17.9658823529411815.271
924152AB2-059 E OP
Adder
7.4317647058823546.317
962561AG1-105 C
Adder
12.04705882352941210.24
942342AE2-247 E
Adder
2.92470588235294172.486
316036AC1-147 C
50/50
0.5640.564
316018AA1-139 ULT2
50/50
1.6761.676
919152AA1-139 E1
50/50
6.336.33
920042AA2-088 E OP
Adder
15.59882352941176513.259
934511AD1-075 C
Adder
12.56117647058823510.677
934521AD1-076 C
Adder
18.24823529411764515.511
3145723EMPORIA
Adder
0.62470588235294120.531
923573AB1-173 E OP
Adder
4.7517647058823534.039
919692AA2-053 E OP
Adder
6.1282352941176475.209
925785AC1-054 E
Adder
4.8741176470588234.143
316263AC1-034 C
Adder
9.344705882352947.943
959311AF2-222 C
Adder
21.718.445
913392Y1-086 E
50/50
3.383.38
939411AE1-173 C
50/50
158.79158.79
3137643SOCKMAN
Adder
1.03058823529411760.876
3151031BRUNSWICKG2
50/50
14.45814.458
919710AA2-057 E
Adder
5.6458823529411774.799
939192AE1-149 E
Adder
8.7694117647058827.454
939312AE1-162 E
Adder
1.95882352941176491.665
3150991CHESPKB
50/50
1.1051.105
934065AD1-033 E
50/50
7.7977.797
937226AE2-253 E
50/50
9.0629.062
934501AD1-074 C
Adder
50.2447058823529442.708
924517AB2-100 E2
Adder
4.23058823529411753.596
957482AF2-042 E
50/50
55.48555.485
961671AG1-007 C
Adder
1.33294117647058831.133
934621AD1-088 C
Adder
13.82823529411764711.754
935172AD1-152 E
Adder
7.9105882352941186.724
926274AC1-105 E
Adder
3.63.06
934576AD1-082 E
Adder
5.7482352941176484.886
916191Z1-068 C
50/50
0.0680.068
933292AC2-141 E
50/50
20.76320.763
316294AC1-161 C
50/50
7.9487.948
944602AF1-125 E
50/50
159.152159.152
3145506HICKORY
50/50
3.3883.388
943612AF1-032 E
Adder
1.40823529411764731.197
957871AF2-081 C
50/50
15.47915.479
940492AE2-034 E
Adder
4.6305882352941183.936
934522AD1-076 E
Adder
9.3011764705882357.906
943172AE2-346 E
Adder
0.88941176470588230.756
918492AA1-063AE OP
Adder
5.9423529411764715.051
917332KELFORD E
Adder
2.39764705882352922.038
925122AB2-169 E
Adder
8.4305882352941197.166
316274AC1-208 C
Adder
12.93882352941176410.998
917342Z2-044 E
Adder
0.84705882352941180.72
937482AD2-202 E
Adder
1.57764705882352941.341
3151311EDGECMA
Adder
21.84705882352941218.57
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6337.633
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.923129.923
CPLELTFEXP_CPLE->PJM
CLTF
16.01716.017
TVALTFEXP_TVA->PJM
CLTF
7.5637.563
O66PJM->LTFIMP_O-066
CMTX_NF
29.52729.527
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.88834.888
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.38927.389
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.6044.604
LAGNLTFEXP_LAGN->PJM
CLTF
9.689.68
NYPJM->LTFIMP_NY
CLTF
2.172.17
LGEELTFEXP_LGEE->PJM
CLTF
1.3891.389
WECLTFEXP_WEC->PJM
CLTF
0.7290.729
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6364.636
SIGELTFEXP_SIGE->PJM
CLTF
0.2790.279

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.17 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4104.33
MW Contribution:35.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
942341AE2-247 C
Adder
1.9647058823529411.67
943462AF1-017 E
Adder
2.90117647058823552.466
958162AF2-110 E
Adder
2.98235294117647072.535
316388AE2-253 GEN
50/50
2.7712.771
919153AA1-139 E2
50/50
5.7585.758
934512AD1-075 E
Adder
5.9258823529411765.037
934502AD1-074 E
Adder
23.70588235294117420.15
924516AB2-100 E1
Adder
4.042352941176473.436
918512AA1-065 E OP
Adder
7.6023529411764716.462
940642AE2-051 E
50/50
19.82119.821
966621AG1-532 C
Adder
1.94000000000000021.649
918532AA1-067 E
Adder
0.96823529411764710.823
924022AB2-043 E O1
Adder
6.95.865
3147223TWITTYS
Adder
1.21764705882352931.035
959312AF2-222 E
Adder
14.06705882352941311.957
316185AD1-033 C
50/50
1.7361.736
944581AF1-123 C
50/50
64.12164.121
941101AE2-104 C
Adder
4.5952941176470593.906
316141AB2-099 E
Adder
0.347058823529411750.295
316088AB2-174 E
Adder
8.997647058823537.648
923994AB2-040_E
Adder
8.487.208
957481AF2-042 C
50/50
79.94679.946
961672AG1-007 E
Adder
0.71529411764705890.608
924322AB2-079 E O1
Adder
1.77764705882352941.511
943902AF1-058 E
Adder
1.65647058823529411.408
913392Y1-086 E
Adder
3.08235294117647072.62
939411AE1-173 C
50/50
149.153149.153
316349AD2-085 C
Adder
4.5341176470588243.854
935112AD1-144 E
Adder
1.2588235294117651.07
944582AF1-123 E
50/50
146.831146.831
944592AF1-124 E
50/50
147.363147.363
923832AB2-022 E
Adder
1.74000000000000021.479
938772AE1-103 E
Adder
5.5529411764705884.72
916042Z1-036 E
Adder
39.78705882352941433.819
960082AF2-299 E
Adder
1.7247058823529411.466
946281AF1-292 C
Adder
2.14117647058823521.82
926071AC1-086 C
Adder
28.90117647058823624.566
963042AG1-153 E
50/50
14.06814.068
927021AC1-189 C
Adder
11.3505882352941179.648
3151541CLOVER2
50/50
18.07518.075
964241AG1-285 C
Adder
17.3105882352941214.714
924152AB2-059 E OP
Adder
7.0658823529411776.006
962561AG1-105 C
Adder
11.6047058823529429.864
926662AC1-147 E
Adder
1.84117647058823521.565
916192Z1-068 E
50/50
2.6352.635
957492AF2-043 E
Adder
1.97647058823529421.68
923852AB2-025 E
50/50
1.6571.657
939412AE1-173 E
50/50
99.43599.435
961941AG1-037 C
Adder
0.69294117647058820.589
961942AG1-037 E
Adder
0.462352941176470630.393
941032AE2-094 E
50/50
30.64130.641
941031AE2-094 C
50/50
68.41468.414
934321AD1-056 C
Adder
8.477647058823537.206
934332AD1-057 E
Adder
2.46235294117647062.093
934322AD1-056 E
Adder
4.59882352941176453.909
934331AD1-057 C
Adder
4.72941176470588154.02
927022AC1-189 E
Adder
5.6541176470588244.806
925595AC1-034 E
Adder
6.702352941176475.697
936262AD2-033 E
Adder
10.6635294117647069.064
932046AC2-012 E
50/50
18.21618.216
958161AF2-110 C
Adder
1.8752941176470591.594
316017AA1-139 ULT1
50/50
1.5241.524
938531AE1-072 C
50/50
24.73924.739
3145393UNCAMP
Adder
8.3505882352941197.098
933981AD1-022 C
Adder
12.09058823529411710.277
900672V4-068 E
Adder
0.490588235294117660.417
3152411Z1-086 GT1
50/50
17.81217.812
924302AB2-077 E O1
Adder
1.77764705882352941.511
936666AD2-085 E
Adder
7.397647058823536.288
941591AE2-156 C
50/50
24.9124.91
316316AC1-027 C
50/50
0.4430.443
944601AF1-125 C
50/50
63.13463.134
944591AF1-124 C
50/50
64.34964.349
938771AE1-103 C
Adder
4.0211764705882363.418
3145413WATKINS
Adder
0.94941176470588240.807
960081AF2-299 C
Adder
2.58705882352941162.199
926072AC1-086 E
Adder
13.15411764705882411.181
944011AF1-069 C
50/50
22.35322.353
963041AG1-153 C
50/50
9.3799.379
936261AD2-033 C
Adder
15.9952941176470613.596
962562AG1-105 E
Adder
7.7364705882352946.576
3151101ELIZAR3
50/50
4.524.52
3151081ELIZAR1
50/50
4.4634.463
3151091ELIZAR2
50/50
4.3854.385
316315AB2-025 C
50/50
0.5820.582
946282AF1-292 E
Adder
1.4270588235294121.213
944012AF1-069 E
50/50
8.6848.684
3151051BRUNSWICKS1
50/50
28.7628.76
917512Z2-088 E OP1
Adder
6.5941176470588245.605
3151531CLOVER1
50/50
18.24518.245
939191AE1-149 C
Adder
12.63647058823529410.741
3143316POE
Adder
1.67647058823529421.425
901082W1-029 E
Adder
44.4776470588235337.806
926206AC1-098 E
Adder
4.9670588235294124.222
3151021BRUNSWICKG1
50/50
13.84413.844
3151041BRUNSWICKG3
50/50
13.84413.844
964791AG1-342 C
Adder
4.6105882352941173.919
934576AD1-082 E
Adder
5.4388235294117654.623
916191Z1-068 C
50/50
0.0610.061
933292AC2-141 E
50/50
18.61818.618
316294AC1-161 C
50/50
7.1277.127
944602AF1-125 E
50/50
144.526144.526
3145506HICKORY
50/50
3.0783.078
943612AF1-032 E
Adder
1.28470588235294141.092
957871AF2-081 C
50/50
14.0814.08
940492AE2-034 E
Adder
4.2752941176470593.634
934522AD1-076 E
Adder
8.6200000000000017.327
943172AE2-346 E
Adder
0.8317647058823530.707
918492AA1-063AE OP
Adder
5.6035294117647064.763
917332KELFORD E
Adder
2.25058823529411761.913
925122AB2-169 E
Adder
7.8694117647058836.689
316274AC1-208 C
Adder
12.25411764705882510.416
917342Z2-044 E
Adder
0.80352941176470590.683
937482AD2-202 E
50/50
1.5171.517
3151311EDGECMA
Adder
20.7705882352941217.655
3137643SOCKMAN
Adder
0.97882352941176460.832
3151031BRUNSWICKG2
50/50
13.84413.844
919710AA2-057 E
Adder
5.3541176470588244.551
937481AD2-202 C
50/50
0.5210.521
939192AE1-149 E
Adder
8.424705882352947.161
939312AE1-162 E
Adder
1.79058823529411781.522
934065AD1-033 E
50/50
7.0817.081
937226AE2-253 E
50/50
8.2398.239
934501AD1-074 C
Adder
46.5682352941176539.583
924517AB2-100 E2
Adder
4.042352941176473.436
957482AF2-042 E
50/50
53.29753.297
961671AG1-007 C
Adder
1.26235294117647071.073
934621AD1-088 C
Adder
13.31176470588235211.315
935172AD1-152 E
Adder
7.6094117647058826.468
942342AE2-247 E
Adder
2.71411764705882372.307
316018AA1-139 ULT2
50/50
1.5241.524
919152AA1-139 E1
50/50
5.7585.758
920042AA2-088 E OP
Adder
14.57411764705882412.388
934511AD1-075 C
Adder
11.6423529411764739.896
934521AD1-076 C
Adder
16.9129411764705914.376
3145723EMPORIA
Adder
0.59647058823529410.507
923573AB1-173 E OP
Adder
4.5223529411764713.844
919692AA2-053 E OP
Adder
5.797647058823534.928
925785AC1-054 E
Adder
4.65176470588235353.954
316263AC1-034 C
Adder
8.8847058823529417.552
959311AF2-222 C
Adder
20.9952941176470617.846
3150921YORKTN3
Adder
64.9600000000000155.216
3145256KINGFORK
Adder
1.35529411764705881.152
925522AC1-027 E
50/50
1.7051.705
926755AC1-161 E
50/50
18.61818.618
933291AC2-141 C
50/50
43.61643.616
941102AE2-104 E
Adder
7.3058823529411766.21
957872AF2-081 E
50/50
6.0346.034
932632AC2-084 E
Adder
4.3905882352941183.732
926214AC1-099 E
Adder
1.64117647058823551.395
964242AG1-285 E
Adder
11.549.809
924162AB2-060 E OP
Adder
5.6588235294117644.81
964792AG1-342 E
Adder
3.07411764705882362.613
961611AG1-000B C
Adder
18.02352941176470615.32
316375AC2-012 C
50/50
1.8781.878
940541AE2-040 C
50/50
4.0974.097
940482AE2-033 E
50/50
15.52815.528
940481AE2-033 C
50/50
23.03323.033
923263AB1-132 E OP
Adder
8.4105882352941177.149
925612AC1-036 E
Adder
1.09882352941176480.934
924312AB2-078 E O1
Adder
1.77764705882352941.511
926274AC1-105 E
Adder
3.4682352941176472.948
943461AF1-017 C
Adder
1.77764705882352941.511
932596AC2-079 E
Adder
12.38941176470588310.531
316311AC2-079 C
Adder
7.5929411764705886.454
938532AE1-072 E
50/50
12.89612.896
3146326AYDLETT TAP
50/50
1.9081.908
917122Z2-027 E
Adder
1.88117647058823521.599
920692AA2-178 E
Adder
5.74.845
966622AG1-532 E
Adder
1.29294117647058831.099
3152441Z1-086 ST
50/50
31.00631.006
922923AB1-081 E OP
Adder
4.9882352941176474.24
316084AB2-161 E
Adder
6.8258823529411765.802
3145946PLYMOUTH TP
Adder
0.44705882352941180.38
933982AD1-022 E
Adder
6.582352941176475.595
940641AE2-051 C
50/50
29.73129.731
3152431Z1-086 GT3
50/50
17.80617.806
3152421Z1-086 GT2
50/50
17.80617.806
927146AC1-208 E
Adder
5.44117647058823554.625
934622AD1-088 E
Adder
6.4094117647058835.448
934612AD1-087 E
50/50
5.1825.182
934611AD1-087 C
50/50
1.7961.796
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.3487.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
126.03126.03
CPLELTFEXP_CPLE->PJM
CLTF
15.41515.415
TVALTFEXP_TVA->PJM
CLTF
7.567.56
O66PJM->LTFIMP_O-066
CMTX_NF
30.16830.168
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.99436.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.67827.678
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.7584.758
LAGNLTFEXP_LAGN->PJM
CLTF
9.6549.654
NYPJM->LTFIMP_NY
CLTF
2.22.2
LGEELTFEXP_LGEE->PJM
CLTF
1.4681.468
WECLTFEXP_WEC->PJM
CLTF
0.7690.769
G-007PJM->LTFIMP_G-007
CMTX_NF
4.7394.739
SIGELTFEXP_SIGE->PJM
CLTF
0.2910.291

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T567_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T567_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.4 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4073.91
MW Contribution:35.65
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
942341AE2-247 C
Adder
2.09411764705882361.78
943462AF1-017 E
Adder
3.09058823529411742.627
958162AF2-110 E
Adder
3.2635294117647062.774
316388AE2-253 GEN
50/50
3.0993.099
919153AA1-139 E2
50/50
6.4346.434
934512AD1-075 E
Adder
6.422352941176475.459
934502AD1-074 E
Adder
25.6882352941176521.835
924516AB2-100 E1
Adder
4.1635294117647063.539
918512AA1-065 E OP
Adder
8.1494117647058816.927
940642AE2-051 E
50/50
21.07921.079
966621AG1-532 C
Adder
2.00352941176470621.703
918532AA1-067 E
Adder
1.02588235294117650.872
924022AB2-043 E O1
Adder
7.0847058823529416.022
3147223TWITTYS
Adder
1.241.054
959312AF2-222 E
Adder
14.30117647058823712.156
316185AD1-033 C
50/50
1.9451.945
944581AF1-123 C
50/50
71.8771.87
941101AE2-104 C
Adder
5.0270588235294114.273
316141AB2-099 E
Adder
0.36941176470588240.314
316088AB2-174 E
Adder
9.3282352941176477.929
923994AB2-040_E
Adder
8.8082352941176477.487
957481AF2-042 C
Adder
82.8776470588235370.446
961672AG1-007 E
Adder
0.7517647058823530.639
924322AB2-079 E O1
Adder
1.82588235294117651.552
943902AF1-058 E
Adder
1.70235294117647061.447
316349AD2-085 C
Adder
4.8305882352941174.106
935112AD1-144 E
Adder
1.3835294117647061.176
944582AF1-123 E
50/50
164.574164.574
944592AF1-124 E
50/50
165.171165.171
923832AB2-022 E
Adder
1.93411764705882351.644
938772AE1-103 E
Adder
6.0094117647058825.108
916042Z1-036 E
Adder
43.71058823529412537.154
960082AF2-299 E
Adder
1.78117647058823541.514
946281AF1-292 C
Adder
2.21058823529411751.879
926071AC1-086 C
Adder
30.1129411764705925.596
963042AG1-153 E
50/50
14.70814.708
927021AC1-189 C
Adder
11.97411764705882410.178
964241AG1-285 C
Adder
17.77647058823529515.11
924152AB2-059 E OP
Adder
7.3811764705882366.274
962561AG1-105 C
Adder
11.92235294117647210.134
942342AE2-247 E
Adder
2.89058823529411772.457
316018AA1-139 ULT2
50/50
1.7031.703
919152AA1-139 E1
50/50
6.4346.434
920042AA2-088 E OP
Adder
15.5623529411764713.228
934511AD1-075 C
Adder
12.6152941176470610.723
934521AD1-076 C
Adder
18.32705882352941315.578
3145723EMPORIA
Adder
0.61647058823529410.524
923573AB1-173 E OP
Adder
4.6976470588235293.993
919692AA2-053 E OP
Adder
6.08588235294117655.173
925785AC1-054 E
Adder
4.8317647058823534.107
316263AC1-034 C
Adder
9.287.888
959311AF2-222 C
Adder
21.34470588235294418.143
913392Y1-086 E
Adder
3.42705882352941152.913
939411AE1-173 C
50/50
160.299160.299
3137643SOCKMAN
Adder
1.02117647058823540.868
3151031BRUNSWICKG2
50/50
14.47314.473
919710AA2-057 E
Adder
5.6082352941176474.767
926662AC1-147 E
Adder
2.05411764705882361.746
916192Z1-068 E
50/50
2.9452.945
957492AF2-043 E
Adder
2.18823529411764731.86
923852AB2-025 E
Adder
1.6847058823529411.432
939412AE1-173 E
50/50
106.866106.866
961941AG1-037 C
Adder
0.740.629
961942AG1-037 E
Adder
0.49294117647058820.419
941032AE2-094 E
50/50
32.08232.082
941031AE2-094 C
50/50
71.63171.631
934321AD1-056 C
Adder
8.844705882352947.518
934332AD1-057 E
Adder
2.56941176470588272.184
934322AD1-056 E
Adder
4.797647058823534.078
934331AD1-057 C
Adder
4.9341176470588244.194
927022AC1-189 E
Adder
5.9647058823529415.07
925595AC1-034 E
Adder
7.0011764705882355.951
936666AD2-085 E
Adder
7.8811764705882356.699
941591AE2-156 C
50/50
27.78727.787
316316AC1-027 C
50/50
0.4950.495
944601AF1-125 C
50/50
70.76370.763
944591AF1-124 C
50/50
72.12672.126
938771AE1-103 C
Adder
4.3517647058823533.699
3145413WATKINS
Adder
1.02235294117647070.869
960081AF2-299 C
Adder
2.6705882352941182.27
926072AC1-086 E
Adder
13.70588235294117811.65
944011AF1-069 C
50/50
23.40523.405
963041AG1-153 C
50/50
9.8059.805
936261AD2-033 C
Adder
5.8058823529411764.935
962562AG1-105 E
Adder
7.9482352941176486.756
932046AC2-012 E
50/50
20.31420.314
958161AF2-110 C
Adder
2.0517647058823531.744
316017AA1-139 ULT1
50/50
1.7031.703
938531AE1-072 C
50/50
27.61527.615
3145393UNCAMP
Adder
9.017647058823537.665
933981AD1-022 C
Adder
13.06588235294117711.106
900672V4-068 E
Adder
0.52235294117647060.444
3152411Z1-086 GT1
50/50
18.63118.631
924302AB2-077 E O1
Adder
1.82588235294117651.552
961611AG1-000B C
Adder
18.65882352941176615.86
316375AC2-012 C
50/50
2.0942.094
940541AE2-040 C
Adder
4.16470588235294153.54
940482AE2-033 E
Adder
15.81058823529411813.439
940481AE2-033 C
Adder
23.45176470588235419.934
923263AB1-132 E OP
Adder
8.7635294117647067.449
925612AC1-036 E
Adder
1.11882352941176480.951
3151101ELIZAR3
50/50
5.0455.045
3151081ELIZAR1
50/50
4.9824.982
3151091ELIZAR2
50/50
4.8954.895
946282AF1-292 E
Adder
1.47411764705882351.253
944012AF1-069 E
50/50
9.0929.092
3151051BRUNSWICKS1
50/50
30.06830.068
917512Z2-088 E OP1
Adder
6.9388235294117645.898
3143316POE
Adder
1.61411764705882371.372
901082W1-029 E
Adder
49.1811764705882441.804
926206AC1-098 E
Adder
5.2270588235294114.443
3151021BRUNSWICKG1
50/50
14.47314.473
3151041BRUNSWICKG3
50/50
14.47314.473
964791AG1-342 C
Adder
4.737647058823534.027
934576AD1-082 E
Adder
5.5282352941176474.699
916191Z1-068 C
50/50
0.0690.069
933292AC2-141 E
50/50
21.46921.469
316294AC1-161 C
50/50
8.2198.219
944602AF1-125 E
50/50
161.991161.991
3145506HICKORY
50/50
3.4483.448
943612AF1-032 E
Adder
1.42235294117647081.209
957871AF2-081 C
50/50
15.73315.733
940492AE2-034 E
Adder
4.663.961
934522AD1-076 E
Adder
9.3411764705882367.94
943172AE2-346 E
Adder
0.88823529411764710.755
918492AA1-063AE OP
Adder
5.9070588235294125.021
917332KELFORD E
Adder
2.39058823529411772.032
925122AB2-169 E
Adder
8.4411764705882367.175
316274AC1-208 C
Adder
12.85294117647058910.925
917342Z2-044 E
Adder
0.84117647058823530.715
937482AD2-202 E
Adder
1.56941176470588251.334
3151311EDGECMA
Adder
21.6952941176470618.441
939312AE1-162 E
Adder
1.93058823529411771.641
3150991CHESPKB
50/50
1.121.12
934065AD1-033 E
50/50
7.9347.934
937226AE2-253 E
50/50
9.2149.214
934501AD1-074 C
Adder
50.4623529411764742.893
924517AB2-100 E2
Adder
4.1635294117647063.539
957482AF2-042 E
Adder
55.2517647058823546.964
961671AG1-007 C
Adder
1.32588235294117651.127
934621AD1-088 C
Adder
13.7211.662
935172AD1-152 E
Adder
7.8611764705882366.682
3150921YORKTN3
Adder
148.4764705882353126.205
3145256KINGFORK
Adder
1.49058823529411751.267
925522AC1-027 E
50/50
1.9061.906
926755AC1-161 E
50/50
21.46921.469
933291AC2-141 C
50/50
50.29350.293
941102AE2-104 E
Adder
7.99294117647058756.794
957872AF2-081 E
50/50
6.7436.743
932632AC2-084 E
Adder
4.623.927
926214AC1-099 E
Adder
1.72705882352941181.468
964242AG1-285 E
Adder
11.85176470588235310.074
924162AB2-060 E OP
Adder
5.8058823529411764.935
964792AG1-342 E
Adder
3.1588235294117652.685
924312AB2-078 E O1
Adder
1.82588235294117651.552
926274AC1-105 E
Adder
3.5647058823529413.03
3152331SURRY 2
50/50
39.09539.095
943461AF1-017 C
Adder
1.89411764705882371.61
932596AC2-079 E
Adder
13.2447058823529411.258
316311AC2-079 C
Adder
8.117647058823536.9
938532AE1-072 E
50/50
14.39614.396
3146326AYDLETT TAP
50/50
2.1292.129
917122Z2-027 E
Adder
2.08705882352941161.774
920692AA2-178 E
Adder
6.2129411764705885.281
966622AG1-532 E
Adder
1.3352941176470591.135
3152441Z1-086 ST
50/50
32.43132.431
922923AB1-081 E OP
Adder
5.2094117647058834.428
316084AB2-161 E
Adder
6.937647058823535.897
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
933982AD1-022 E
Adder
7.11294117647058856.046
940641AE2-051 C
50/50
31.61831.618
3152431Z1-086 GT3
50/50
18.62518.625
3152421Z1-086 GT2
50/50
18.62518.625
927146AC1-208 E
Adder
5.7070588235294124.851
934622AD1-088 E
Adder
6.6058823529411775.615
934612AD1-087 E
Adder
5.3611764705882364.557
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.5637.563
CBM South 2LTFEXP_CBM-S2->PJM
CBM
128.067128.067
CPLELTFEXP_CPLE->PJM
CLTF
15.87115.871
TVALTFEXP_TVA->PJM
CLTF
7.2977.297
O66PJM->LTFIMP_O-066
CMTX_NF
27.12727.127
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.34332.343
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.24226.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.3444.344
LAGNLTFEXP_LAGN->PJM
CLTF
9.3599.359
NYPJM->LTFIMP_NY
CLTF
2.0052.005
LGEELTFEXP_LGEE->PJM
CLTF
1.2871.287
WECLTFEXP_WEC->PJM
CLTF
0.6770.677
G-007PJM->LTFIMP_G-007
CMTX_NF
4.2584.258
SIGELTFEXP_SIGE->PJM
CLTF
0.2610.261

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.85 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3279.97
MW Contribution:23.07
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150861SPRUNCD
80/20
0.2220.222
940431AE2-027 C
Adder
17.26588235294117614.676
3150981CHESPKA
80/20
0.6340.634
316185AD1-033 C
80/20
1.7941.794
944581AF1-123 C
80/20
66.2266.22
941101AE2-104 C
80/20
4.8434.843
316320Y1-086 C
80/20
0.3190.319
316405AF2-144 C
80/20
0.4280.428
957481AF2-042 C
80/20
77.49977.499
961611AG1-000B C
Adder
21.72352941176470518.465
316236AE1-162 C
80/20
0.4930.493
316375AC2-012 C
80/20
1.9631.963
313526AB2-022 C
80/20
0.5460.546
940541AE2-040 C
80/20
4.2084.208
940481AE2-033 C
80/20
23.64823.648
3150731STONECA
Adder
8.9505882352941187.608
935161AD1-151 C
Adder
21.46588235294117618.246
3151221GRAVEL6
80/20
3.4833.483
3151201GRAVEL4
80/20
3.4873.487
958161AF2-110 C
80/20
1.9761.976
316017AA1-139 ULT1
80/20
1.5751.575
938531AE1-072 C
80/20
25.56125.561
933981AD1-022 C
Adder
12.39411764705882410.535
3152411Z1-086 GT1
80/20
16.26616.266
942341AE2-247 C
80/20
2.1432.143
3151101ELIZAR3
80/20
4.7154.715
3151081ELIZAR1
80/20
4.6564.656
3151091ELIZAR2
80/20
4.5754.575
316315AB2-025 C
80/20
0.5980.598
961951AG1-038 C
Adder
3.3341176470588242.834
3151051BRUNSWICKS1
80/20
26.33526.335
3151531CLOVER1
80/20
17.87717.877
3138533PONTONDP
Adder
0.87294117647058820.742
3150831SPRUNCA
80/20
12.34712.347
3150841SPRUNCB
80/20
12.34712.347
961941AG1-037 C
Adder
0.71058823529411760.604
941031AE2-094 C
80/20
62.11762.117
934321AD1-056 C
Adder
8.5376470588235297.257
934331AD1-057 C
Adder
4.7623529411764714.048
958211AF2-115 C
Adder
2.94705882352941152.505
943471AF1-018 C
Adder
7.9588235294117656.765
316083AB2-161 C
80/20
0.7870.787
316072AD1-144 C
80/20
0.4020.402
940641AE2-051 C
80/20
27.30727.307
316336AC2-165 C
Adder
13.69411764705882511.64
3152431Z1-086 GT3
80/20
16.26116.261
3152421Z1-086 GT2
80/20
16.26116.261
934611AD1-087 C
80/20
1.761.76
316233AE1-074 C
80/20
3.7763.776
940551AE2-041 C
Adder
7.9588235294117656.765
3151211GRAVEL5
80/20
3.4433.443
3152331SURRY 2
80/20
34.47934.479
943461AF1-017 C
80/20
1.9381.938
316311AC2-079 C
80/20
8.2428.242
3156056W1-029WIND
80/20
1.1231.123
3152441Z1-086 ST
80/20
28.31528.315
3150601CHESTF5
Adder
76.7117647058823665.205
941591AE2-156 C
80/20
26.02126.021
316316AC1-027 C
80/20
0.460.46
944601AF1-125 C
80/20
65.265.2
944591AF1-124 C
80/20
66.45566.455
938771AE1-103 C
80/20
4.24.2
960081AF2-299 C
Adder
2.64941176470588242.252
944011AF1-069 C
80/20
20.29620.296
963041AG1-153 C
80/20
8.5888.588
936261AD2-033 C
Adder
17.57529411764705814.939
961791AG1-021 C
Adder
2.35764705882352972.004
944631AF1-128 C
Adder
48.040.8
3150921YORKTN3
Adder
157.0388235294118133.483
933291AC2-141 C
80/20
44.42644.426
316305AF2-043 C
80/20
0.5050.505
3150651CHESTF6
Adder
24.50588235294117520.83
916191Z1-068 C
80/20
0.0640.064
316294AC1-161 C
80/20
7.267.26
957871AF2-081 C
80/20
14.54714.547
936591AD2-074 C
Adder
5.7647058823529424.9
3151151S HAMPT1
80/20
2.1352.135
316313AB2-026 C
80/20
0.5480.548
316274AC1-208 C
Adder
12.4023529411764710.542
3151311EDGECMA
Adder
20.74352941176470817.632
316169AC1-164 GEN
Adder
44.9588235294117738.215
316349AD2-085 C
80/20
4.9434.943
316258AE1-075 C
80/20
0.5030.503
316023AB2-100 C2
80/20
1.3721.372
946281AF1-292 C
Adder
2.19294117647058861.864
926071AC1-086 C
Adder
29.4425.024
927021AC1-189 C
Adder
11.4094117647058839.698
3151541CLOVER2
80/20
17.7117.71
964241AG1-285 C
Adder
17.89058823529411815.207
962561AG1-105 C
Adder
11.8176470588235310.045
939191AE1-149 C
80/20
15.16215.162
957601AF2-054 C
Adder
2.37764705882352922.021
316365AB2-100 C1
80/20
1.3721.372
3151021BRUNSWICKG1
80/20
12.67612.676
3151041BRUNSWICKG3
80/20
12.67612.676
964791AG1-342 C
Adder
4.6788235294117653.977
316246AF1-032 C
80/20
0.4130.413
316388AE2-253 GEN
80/20
2.8622.862
966621AG1-532 C
Adder
1.9870588235294121.689
944641AF1-129 C
Adder
134.59058823529412114.402
316240AF1-291 C
Adder
2.86941176470588262.439
3151161SURRY 1
80/20
33.88933.889
316381AD1-082 C
80/20
1.7951.795
316036AC1-147 C
80/20
0.5360.536
316018AA1-139 ULT2
80/20
1.5751.575
934511AD1-075 C
Adder
11.94117647058823610.15
934521AD1-076 C
Adder
17.34705882352941214.745
316263AC1-034 C
Adder
8.8741176470588247.543
959311AF2-222 C
Adder
23.07176470588235519.611
3150851SPRUNCC
80/20
0.2220.222
3156116Z1-036WIND
80/20
0.9440.944
939411AE1-173 C
80/20
140.502140.502
3137643SOCKMAN
Adder
1.00.85
3151031BRUNSWICKG2
80/20
12.67612.676
937481AD2-202 C
80/20
0.5110.511
942001AE2-212 C
80/20
2.9732.973
3150991CHESPKB
80/20
1.051.05
316321Z2-027 C
80/20
0.5270.527
943741AF1-042 C
Adder
3.01647058823529422.564
934501AD1-074 C
Adder
47.763529411764740.599
962861AG1-135 C
Adder
6.1588235294117655.235
961671AG1-007 C
Adder
1.26588235294117671.076
934621AD1-088 C
80/20
13.42613.426
946301AF1-294 C
Adder
4.8470588235294124.12
942461AE2-259 C
Adder
12.70588235294117810.8
316303AF2-085
80/20
6.3826.382
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1347.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.889122.889
CPLELTFEXP_CPLE->PJM
CLTF
14.96614.966
TVALTFEXP_TVA->PJM
CLTF
7.5327.532
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.6437.64
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.68227.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8064.806
LAGNLTFEXP_LAGN->PJM
CLTF
9.5879.587
NYPJM->LTFIMP_NY
CLTF
2.4692.469
LGEELTFEXP_LGEE->PJM
CLTF
1.5071.507
WECLTFEXP_WEC->PJM
CLTF
0.7840.784
SIGELTFEXP_SIGE->PJM
CLTF
0.2960.296

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.49 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3222.37
MW Contribution:25.81
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.18 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3432.65
MW Contribution:13.85
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926662AC1-147 E
50/50
2.1552.155
916192Z1-068 E
50/50
3.0983.098
957492AF2-043 E
50/50
2.2332.233
923852AB2-025 E
Adder
1.06941176470588250.909
939412AE1-173 E
50/50
88.25188.251
961941AG1-037 C
Adder
0.640.544
961942AG1-037 E
Adder
0.427058823529411770.363
941032AE2-094 E
50/50
22.37122.371
941031AE2-094 C
50/50
49.94849.948
934321AD1-056 C
Adder
6.7670588235294115.752
934332AD1-057 E
Adder
1.96588235294117661.671
934322AD1-056 E
Adder
3.6705882352941183.12
934331AD1-057 C
Adder
3.7752941176470593.209
927022AC1-189 E
Adder
4.86235294117647054.133
927226AC1-216 E
Adder
6.8258823529411765.802
962962AG1-145 E
Adder
1.36235294117647051.158
936666AD2-085 E
Adder
7.2929411764705886.199
941591AE2-156 C
50/50
29.1829.18
316316AC1-027 C
50/50
0.520.52
944601AF1-125 C
50/50
74.70974.709
944591AF1-124 C
50/50
76.14876.148
938771AE1-103 C
50/50
4.0814.081
3145413WATKINS
Adder
0.93058823529411770.791
960081AF2-299 C
Adder
1.91882352941176481.631
926072AC1-086 E
Adder
10.3658823529411768.811
944011AF1-069 C
50/50
16.3216.32
963041AG1-153 C
Adder
6.8564705882352955.828
936261AD2-033 C
Adder
11.82117647058823610.048
962562AG1-105 E
Adder
5.74.845
942341AE2-247 C
Adder
1.93764705882352951.647
943462AF1-017 E
Adder
2.86000000000000032.431
958162AF2-110 E
50/50
3.2233.223
316246AF1-032 C
50/50
0.4470.447
316388AE2-253 GEN
50/50
3.2483.248
919153AA1-139 E2
50/50
6.7236.723
934512AD1-075 E
Adder
5.95411764705882355.061
934502AD1-074 E
Adder
23.81647058823529420.244
924516AB2-100 E1
Adder
2.92235294117647062.484
918512AA1-065 E OP
Adder
7.1905882352941186.112
940642AE2-051 E
50/50
16.13516.135
966621AG1-532 C
Adder
1.43882352941176481.223
918532AA1-067 E
Adder
0.85764705882352940.729
924022AB2-043 E O1
Adder
5.1070588235294124.341
3147223TWITTYS
Adder
0.89647058823529410.762
959312AF2-222 E
Adder
10.3552941176470598.802
3150981CHESPKA
50/50
0.7090.709
316185AD1-033 C
50/50
2.0522.052
944581AF1-123 C
50/50
75.87875.878
941101AE2-104 C
50/50
4.9664.966
316320Y1-086 C
50/50
0.3530.353
316141AB2-099 E
Adder
0.320.272
316088AB2-174 E
Adder
6.877647058823535.846
923994AB2-040_E
Adder
6.5694117647058825.584
957481AF2-042 C
Adder
58.59176470588235549.803
961672AG1-007 E
Adder
0.59882352941176480.509
924322AB2-079 E O1
Adder
1.3164705882352941.119
943902AF1-058 E
Adder
1.21411764705882351.032
3144216WINCHST
50/50
0.1770.177
316349AD2-085 C
Adder
4.4694117647058833.799
935112AD1-144 E
50/50
1.4091.409
944582AF1-123 E
50/50
173.752173.752
944592AF1-124 E
50/50
174.381174.381
923832AB2-022 E
50/50
1.9881.988
938772AE1-103 E
50/50
5.6365.636
916042Z1-036 E
50/50
42.96342.963
960082AF2-299 E
Adder
1.27882352941176471.087
946281AF1-292 C
Adder
1.58823529411764721.35
926071AC1-086 C
Adder
22.77647058823529519.36
963042AG1-153 E
Adder
10.2835294117647068.741
927021AC1-189 C
Adder
9.768.296
964241AG1-285 C
Adder
12.75176470588235310.839
924152AB2-059 E OP
Adder
5.70470588235294154.849
962561AG1-105 C
Adder
8.5494117647058847.267
924814AB2-134 E
Adder
11.1823529411764729.505
942342AE2-247 E
Adder
2.6752941176470592.274
316036AC1-147 C
50/50
0.60.6
316018AA1-139 ULT2
50/50
1.781.78
919152AA1-139 E1
50/50
6.7236.723
920042AA2-088 E OP
Adder
13.60117647058823611.561
934511AD1-075 C
Adder
11.6964705882352959.942
934521AD1-076 C
Adder
16.99176470588235314.443
3145723EMPORIA
Adder
0.44705882352941180.38
923573AB1-173 E OP
Adder
3.50352941176470622.978
919692AA2-053 E OP
Adder
4.8294117647058834.105
925785AC1-054 E
Adder
3.63176470588235353.087
316263AC1-034 C
Adder
7.1729411764705896.097
959311AF2-222 C
Adder
15.45647058823529513.138
934012AD1-025 E
Adder
8.837647058823537.512
913392Y1-086 E
50/50
3.5213.521
3156116Z1-036WIND
50/50
0.9890.989
939411AE1-173 C
50/50
132.376132.376
3137643SOCKMAN
Adder
0.77882352941176480.662
919710AA2-057 E
Adder
4.43.74
925595AC1-034 E
Adder
5.4105882352941184.599
936262AD2-033 E
Adder
7.8811764705882356.699
957832AF2-077 E
Adder
1.38000000000000011.173
3152331SURRY 2
50/50
52.22952.229
943461AF1-017 C
Adder
1.75294117647058821.49
935161AD1-151 C
Adder
9.2600000000000027.871
932046AC2-012 E
50/50
21.31821.318
958161AF2-110 C
50/50
2.0262.026
316017AA1-139 ULT1
50/50
1.781.78
938531AE1-072 C
50/50
28.76728.767
3145393UNCAMP
Adder
8.367.106
315614AA2-178 C
50/50
2.2542.254
933981AD1-022 C
Adder
11.96352941176470710.169
900672V4-068 E
Adder
0.452941176470588240.385
924302AB2-077 E O1
Adder
1.3164705882352941.119
961611AG1-000B C
Adder
17.5717647058823514.936
316236AE1-162 C
50/50
0.4750.475
316375AC2-012 C
50/50
2.1982.198
313526AB2-022 C
50/50
0.6030.603
940541AE2-040 C
Adder
2.6435294117647062.247
940482AE2-033 E
Adder
10.1729411764705898.647
940481AE2-033 C
Adder
15.09058823529411912.827
923263AB1-132 E OP
Adder
6.6282352941176485.634
925612AC1-036 E
Adder
0.80823529411764720.687
924312AB2-078 E O1
Adder
1.3164705882352941.119
926274AC1-105 E
Adder
2.5482352941176472.166
3151101ELIZAR3
50/50
5.3035.303
3151081ELIZAR1
50/50
5.2375.237
3151091ELIZAR2
50/50
5.1465.146
946282AF1-292 E
Adder
1.05882352941176470.9
944012AF1-069 E
50/50
6.346.34
917512Z2-088 E OP1
Adder
5.58588235294117654.748
939191AE1-149 C
Adder
8.8411764705882367.515
901082W1-029 E
50/50
49.64949.649
926206AC1-098 E
Adder
4.2070588235294123.576
964791AG1-342 C
Adder
3.39411764705882352.885
934576AD1-082 E
Adder
4.4847058823529413.812
916191Z1-068 C
50/50
0.0720.072
933292AC2-141 E
50/50
24.4824.48
316294AC1-161 C
50/50
9.3719.371
944602AF1-125 E
50/50
171.025171.025
3145506HICKORY
50/50
3.633.63
943612AF1-032 E
50/50
1.4511.451
957871AF2-081 C
50/50
16.44116.441
940492AE2-034 E
50/50
4.4344.434
934522AD1-076 E
Adder
8.667.361
943172AE2-346 E
Adder
0.76823529411764710.653
918492AA1-063AE OP
Adder
4.80941176470588254.088
917332KELFORD E
Adder
2.01647058823529421.714
925122AB2-169 E
Adder
7.4694117647058836.349
316274AC1-208 C
Adder
10.168.636
917342Z2-044 E
Adder
0.65529411764705890.557
937482AD2-202 E
Adder
1.1129411764705880.946
3151311EDGECMA
Adder
16.76352941176470814.249
939192AE1-149 E
Adder
5.8941176470588235.01
939312AE1-162 E
50/50
1.9371.937
3150991CHESPKB
50/50
1.1761.176
934065AD1-033 E
50/50
8.3718.371
937226AE2-253 E
50/50
9.6579.657
316321Z2-027 C
50/50
0.5770.577
940491AE2-034 C
50/50
1.6591.659
934501AD1-074 C
Adder
46.7858823529411839.768
924517AB2-100 E2
Adder
2.92235294117647062.484
957482AF2-042 E
Adder
39.0611764705882433.202
961671AG1-007 C
Adder
1.05647058823529430.898
934621AD1-088 C
Adder
9.7717647058823538.306
935172AD1-152 E
Adder
5.5847058823529414.747
316160AE1-175 E
Adder
1.12470588235294120.956
3150921YORKTN3
50/50
162.48162.48
3145256KINGFORK
50/50
1.5181.518
925522AC1-027 E
50/50
2.0032.003
926755AC1-161 E
50/50
24.4824.48
933291AC2-141 C
50/50
57.34757.347
941102AE2-104 E
50/50
7.8957.895
316305AF2-043 C
50/50
0.5470.547
957872AF2-081 E
50/50
7.0467.046
932632AC2-084 E
Adder
3.71882352941176463.161
926214AC1-099 E
Adder
1.38941176470588231.181
964242AG1-285 E
Adder
8.5011764705882367.226
924162AB2-060 E OP
Adder
4.1870588235294123.559
964792AG1-342 E
Adder
2.2623529411764711.923
932763AC2-100 E
Adder
2.3941176470588242.035
932596AC2-079 E
Adder
12.36705882352941210.512
316311AC2-079 C
Adder
7.586.443
938532AE1-072 E
50/50
14.99614.996
3146326AYDLETT TAP
50/50
2.2162.216
917122Z2-027 E
50/50
2.1312.131
3156056W1-029WIND
50/50
1.211.21
920692AA2-178 E
50/50
5.9125.912
966622AG1-532 E
Adder
0.95882352941176460.815
922923AB1-081 E OP
Adder
4.0270588235294123.423
316084AB2-161 E
Adder
5.6282352941176474.784
316072AD1-144 C
50/50
0.4210.421
3145946PLYMOUTH TP
Adder
0.451764705882352960.384
933982AD1-022 E
Adder
6.5129411764705885.536
940641AE2-051 C
50/50
24.20324.203
927146AC1-208 E
Adder
4.5117647058823533.835
934622AD1-088 E
Adder
4.70470588235294153.999
934612AD1-087 E
Adder
3.80117647058823543.231
927255AC1-221 E
Adder
3.5270588235294122.998
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.515.51
CBM South 2LTFEXP_CBM-S2->PJM
CBM
91.70491.704
CPLELTFEXP_CPLE->PJM
CLTF
11.56611.566
TVALTFEXP_TVA->PJM
CLTF
4.9264.926
O66PJM->LTFIMP_O-066
CMTX_NF
19.32919.329
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.74418.744
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.28317.283
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.712.71
LAGNLTFEXP_LAGN->PJM
CLTF
6.3446.344
NYPJM->LTFIMP_NY
CLTF
1.4491.449
LGEELTFEXP_LGEE->PJM
CLTF
0.760.76
WECLTFEXP_WEC->PJM
CLTF
0.3980.398
G-007PJM->LTFIMP_G-007
CMTX_NF
3.0313.031
SIGELTFEXP_SIGE->PJM
CLTF
0.160.16

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.39 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3219.08
MW Contribution:26.18
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
943902AF1-058 E
Adder
1.21882352941176491.036
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
316018AA1-139 ULT2
50/50
1.7931.793
919152AA1-139 E1
50/50
6.7746.774
920042AA2-088 E OP
Adder
14.01647058823529311.914
934511AD1-075 C
Adder
11.92941176470588310.14
934521AD1-076 C
Adder
17.32941176470588514.73
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961941AG1-037 C
Adder
0.65882352941176480.56
961942AG1-037 E
Adder
0.43882352941176470.373
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934321AD1-056 C
Adder
7.0682352941176476.008
934332AD1-057 E
Adder
2.05294117647058851.745
934322AD1-056 E
Adder
3.83411764705882343.259
934331AD1-057 C
Adder
3.94352941176470573.352
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
936262AD2-033 E
Adder
8.0352941176470596.83
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
316316AC1-027 C
50/50
0.5240.524
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
944601AF1-125 C
50/50
75.19275.192
944591AF1-124 C
50/50
76.6476.64
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
936261AD2-033 C
Adder
12.05176470588235410.244
962562AG1-105 E
Adder
5.75647058823529444.893
3151101ELIZAR3
50/50
5.3455.345
3151081ELIZAR1
50/50
5.2785.278
3151091ELIZAR2
50/50
5.1875.187
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
917512Z2-088 E OP1
Adder
5.7423529411764714.881
939191AE1-149 C
Adder
9.8705882352941188.39
3143316POE
Adder
1.15647058823529410.983
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
926755AC1-161 E
50/50
24.52424.524
933291AC2-141 C
50/50
57.45157.451
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
932632AC2-084 E
Adder
3.8494117647058823.272
926214AC1-099 E
Adder
1.43882352941176481.223
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940482AE2-033 E
Adder
11.5564705882352949.823
940481AE2-033 C
Adder
17.1423529411764714.571
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
3152331SURRY 2
50/50
52.46452.464
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
927255AC1-221 E
Adder
2.40941176470588262.048
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.39 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3219.08
MW Contribution:26.18
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
943902AF1-058 E
Adder
1.21882352941176491.036
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961941AG1-037 C
Adder
0.65882352941176480.56
961942AG1-037 E
Adder
0.43882352941176470.373
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934321AD1-056 C
Adder
7.0682352941176476.008
934332AD1-057 E
Adder
2.05294117647058851.745
934322AD1-056 E
Adder
3.83411764705882343.259
934331AD1-057 C
Adder
3.94352941176470573.352
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
936262AD2-033 E
Adder
8.0352941176470596.83
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
316316AC1-027 C
50/50
0.5240.524
944601AF1-125 C
50/50
75.19275.192
944591AF1-124 C
50/50
76.6476.64
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
936261AD2-033 C
Adder
12.05176470588235410.244
962562AG1-105 E
Adder
5.75647058823529444.893
3151101ELIZAR3
50/50
5.3455.345
3151081ELIZAR1
50/50
5.2785.278
3151091ELIZAR2
50/50
5.1875.187
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
917512Z2-088 E OP1
Adder
5.7423529411764714.881
939191AE1-149 C
Adder
9.8705882352941188.39
3143316POE
Adder
1.15647058823529410.983
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
316018AA1-139 ULT2
50/50
1.7931.793
919152AA1-139 E1
50/50
6.7746.774
920042AA2-088 E OP
Adder
14.01647058823529311.914
934511AD1-075 C
Adder
11.92941176470588310.14
934521AD1-076 C
Adder
17.32941176470588514.73
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
926755AC1-161 E
50/50
24.52424.524
933291AC2-141 C
50/50
57.45157.451
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
932632AC2-084 E
Adder
3.8494117647058823.272
926214AC1-099 E
Adder
1.43882352941176481.223
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940482AE2-033 E
Adder
11.5564705882352949.823
940481AE2-033 C
Adder
17.1423529411764714.571
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
3152331SURRY 2
50/50
52.46452.464
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
927255AC1-221 E
Adder
2.40941176470588262.048
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.38 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3218.92
MW Contribution:26.18
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.16 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3432.06
MW Contribution:24.01
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
316316AC1-027 C
50/50
0.5240.524
944601AF1-125 C
50/50
75.19275.192
944591AF1-124 C
50/50
76.6476.64
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
943902AF1-058 E
Adder
1.21882352941176491.036
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
316018AA1-139 ULT2
50/50
1.7931.793
919152AA1-139 E1
50/50
6.7746.774
920042AA2-088 E OP
Adder
14.01647058823529311.914
934511AD1-075 C
Adder
11.92941176470588310.14
934521AD1-076 C
Adder
17.32941176470588514.73
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961941AG1-037 C
Adder
0.65882352941176480.56
961942AG1-037 E
Adder
0.43882352941176470.373
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934321AD1-056 C
Adder
7.0682352941176476.008
934332AD1-057 E
Adder
2.05294117647058851.745
934322AD1-056 E
Adder
3.83411764705882343.259
934331AD1-057 C
Adder
3.94352941176470573.352
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
936262AD2-033 E
Adder
8.0352941176470596.83
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
936261AD2-033 C
Adder
12.05176470588235410.244
962562AG1-105 E
Adder
5.75647058823529444.893
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940482AE2-033 E
Adder
11.5564705882352949.823
940481AE2-033 C
Adder
17.1423529411764714.571
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
3151101ELIZAR3
50/50
5.3455.345
3151081ELIZAR1
50/50
5.2785.278
3151091ELIZAR2
50/50
5.1875.187
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
917512Z2-088 E OP1
Adder
5.7423529411764714.881
939191AE1-149 C
Adder
9.8705882352941188.39
3143316POE
Adder
1.15647058823529410.983
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
926755AC1-161 E
50/50
24.52424.524
933291AC2-141 C
50/50
57.45157.451
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
932632AC2-084 E
Adder
3.8494117647058823.272
926214AC1-099 E
Adder
1.43882352941176481.223
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
3152331SURRY 2
50/50
52.46452.464
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
927255AC1-221 E
Adder
2.40941176470588262.048
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161

Details for AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.63 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:730.45
MW Contribution:8.64
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.61 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:750.7
MW Contribution:10.63
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3156083AA2-088SOLA
80/20
0.9350.935
313506AB1-173 C OP
80/20
2.2292.229
3151361ROSEMG1
80/20
3.9363.936
316005AA1-067 C
80/20
0.2210.221
957481AF2-042 C
80/20
24.31224.312
940481AE2-033 C
80/20
63.40763.407
316181AB2-040 GEN
80/20
2.5112.511
316174AB2-169_C
80/20
0.7190.719
3156063AA2-053SOLA
80/20
2.1582.158
3151281ROARAP4
80/20
2.0092.009
3156011CONETOE2SOL
80/20
1.1751.175
316238AB2-078 C O1
80/20
0.2290.229
316237AB2-079 C O1
80/20
0.2290.229
933981AD1-022 C
80/20
5.6875.687
3151411GASTONB
80/20
6.1756.175
3151261ROARAP2
80/20
2.1232.123
3147043LAWRENC
80/20
0.5790.579
3151621KERR 5
80/20
0.8620.862
966621AG1-532 C
80/20
3.2993.299
316129AC1-054 C
80/20
1.341.34
3151531CLOVER1
80/20
5.8195.819
316131AB2-060 C
80/20
1.0341.034
3138533PONTONDP
80/20
0.3360.336
316118AC1-105 C
80/20
0.4840.484
961941AG1-037 C
80/20
0.4820.482
943171AE2-346 C
80/20
0.2140.214
3151381ROSEMG2
80/20
1.8431.843
934321AD1-056 C
80/20
9.2019.201
934331AD1-057 C
80/20
5.1335.133
958211AF2-115 C
80/20
1.1351.135
316049AB1-081 C OP
80/20
1.4941.494
3151611KERR 4
80/20
0.8620.862
960081AF2-299 C
80/20
4.3984.398
3151391GASTONA
80/20
6.1756.175
3151631KERR 6
80/20
0.8620.862
936261AD2-033 C
80/20
8.0298.029
3144293JTRSVLE
80/20
0.2090.209
961791AG1-021 C
80/20
0.9080.908
316087AB2-174 C
80/20
2.4642.464
313527AB2-043 C
80/20
0.3630.363
3151591KERR 2
80/20
0.8620.862
3151151S HAMPT1
80/20
0.9570.957
932631AC2-084 C
80/20
1.171.17
316274AC1-208 C
80/20
11.22611.226
3151311EDGECMA
80/20
16.55516.555
3151601KERR 3
80/20
0.8620.862
3151581KERR 1
80/20
0.3080.308
3152661PLYWOOD A
80/20
0.6390.639
316023AB2-100 C2
80/20
2.7732.773
946281AF1-292 C
80/20
3.6413.641
926071AC1-086 C
80/20
42.49342.493
316317KELFORD C
80/20
0.370.37
927021AC1-189 C
80/20
7.5497.549
964241AG1-285 C
80/20
7.2257.225
316034AC1-036 C
80/20
0.1240.124
962561AG1-105 C
80/20
5.2875.287
316365AB2-100 C1
80/20
2.7732.773
316318V4-068 C
80/20
0.0750.075
316210AC1-098 C
80/20
1.0991.099
316327AA2-057 C
80/20
1.4891.489
316239AB2-077 C O1
80/20
0.2290.229
964791AG1-342 C
80/20
2.0352.035
934511AD1-075 C
80/20
4.844.84
934521AD1-076 C
80/20
7.0327.032
316011AB1-132 C OP
80/20
4.7154.715
316263AC1-034 C
80/20
6.9816.981
959311AF2-222 C
80/20
8.6368.636
3152921DOMTR78
80/20
0.8540.854
316140AB2-099 C
80/20
0.0920.092
3137643SOCKMAN
80/20
1.2371.237
316212AC1-099 C
80/20
0.3680.368
316319Z2-044 C
80/20
0.2310.231
3151641KERR 7
80/20
0.8620.862
934501AD1-074 C
80/20
19.36119.361
3156021HOLLOMANSOL
80/20
1.5861.586
3156073AA1-063SOLA
80/20
1.8141.814
3151371ROSEMS1
80/20
2.4382.438
961671AG1-007 C
80/20
0.9120.912
934621AD1-088 C
80/20
4.4044.404
316359AB2-059 C OP
80/20
1.7611.761
946301AF1-294 C
80/20
1.8661.866
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1882.188
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.15434.154
CPLELTFEXP_CPLE->PJM
CLTF
4.5894.589
TVALTFEXP_TVA->PJM
CLTF
2.0182.018
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.20711.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.5767.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.3611.361
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
NYPJM->LTFIMP_NY
CLTF
0.3660.366
LGEELTFEXP_LGEE->PJM
CLTF
0.4310.431
WECLTFEXP_WEC->PJM
CLTF
0.2290.229
SIGELTFEXP_SIGE->PJM
CLTF
0.0840.084
CONTINGENCY 'DVP_P4-2: 511T556_SRT-S-1'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 556_SRT-S-3'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A'
 OPEN BRANCH FROM BUS 314218 TO BUS 314196 CKT 1   /*6ELMONT      230.0 - 6LADYSMITH   230.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1   /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T567_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1   /*6CHCKAHM     230.0 - 8CHCKAHM     500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
314677 to 314747 ckt 1
314282 to 314285 ckt 1
314285 to 314316 ckt 1
314692 to 314677 ckt 1
314435 to 314282 ckt 1
314902 to 314282 ckt 2
314902 to 314914 ckt 1
314914 to 314918 ckt 1
314924 to 314903 ckt 1
940480 to 314435 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
DVP_P4-6: CHASE C T342_SRT-A
BreakerAC126.04 %221.4C279.0574.47
GD1DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P4-6: CHASE C T342_SRT-A
BreakerAC165.99 %208.7C346.4192.46
GD1DVP
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
DVP_P1-2: LN 1012_SRT-A-4
SingleAC101.66 %205.86B209.27100.0
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC100.29 %984.18B987.046.65
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 246_SRT-A
SingleAC106.25 %678.68B721.087.55
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A
SingleAC102.88 %678.68B698.26.45
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Base Case
SingleAC100.94 %678.68A685.047.01
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.39 %3220.44B3329.5418.29
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC119.4 %3220.44B3845.2822.66
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC111.63 %3220.44B3595.0913.3
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
SingleAC110.86 %3220.44B3570.0513.91
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC110.14 %3940.0C4339.5323.07
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC116.71 %3220.44B3758.5615.0
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC113.93 %3220.44B3669.1316.05
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC111.88 %3940.0C4408.0826.11
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC106.7 %4070.2B4342.9825.13
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC102.59 %4070.2B4175.6225.13
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC120.93 %3220.44B3894.3314.66
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC119.78 %3220.44B3857.5715.85
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC117.54 %3940.0C4631.2425.71
GD1DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC104.04 %4070.2B4234.722.06
GD1DVP
AG1-285 TP-3CHASCTY 115.0 kV Ckt 1 line
DVP_P4-2: 15832_SRT-A
BreakerAC107.58 %349.0C375.45166.99
GD1DVP
AG1-285 TP-3CHASCTY 115.0 kV Ckt 1 line
DVP_P4-5: FARMVIL L432_SRT-A-1
BreakerAC107.57 %349.0C375.41166.99

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-6: CHASE C T342_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.04 %
Rating:221.4 MVA
Rating Type:C
MVA to Mitigate:279.05
MW Contribution:74.47
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936262AD2-033 E
50/50
23.18823.188
958211AF2-115 C
50/50
6.026.02
946301AF1-294 C
50/50
9.99.9
942461AE2-259 C
50/50
26.75626.756
964241AG1-285 C
50/50
33.44533.445
316034AC1-036 C
50/50
0.6250.625
958212AF2-115 E
50/50
5.1285.128
3144293JTRSVLE
50/50
1.1041.104
946302AF1-294 E
50/50
8.3838.383
925612AC1-036 E
50/50
2.2972.297
936261AD2-033 C
50/50
34.78234.782
961791AG1-021 C
50/50
4.8164.816
959311AF2-222 C
50/50
44.59344.593
3147223TWITTYS
50/50
2.5462.546
959312AF2-222 E
50/50
29.87729.877
961792AG1-021 E
50/50
4.1034.103
316131AB2-060 C
50/50
3.953.95
3138533PONTONDP
50/50
1.7841.784
3147133PAMPLIN
50/50
2.6642.664
924162AB2-060 E OP
50/50
11.41611.416
964242AG1-285 E
50/50
22.29622.296
942462AE2-259 E
50/50
17.83717.837
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0140.014
O66PJM->LTFIMP_O-066
CMTX_NF
0.1230.123
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.010.01
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0320.032
NYPJM->LTFIMP_NY
CLTF
0.010.01
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0380.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0110.011
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0180.018
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0190.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0060.006
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0470.047
MDUPJM->LTFIMP_MDU
CLTF
0.0020.002

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-6: CHASE C T342_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.99 %
Rating:208.7 MVA
Rating Type:C
MVA to Mitigate:346.41
MW Contribution:92.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936262AD2-033 E
50/50
28.7928.79
958211AF2-115 C
50/50
7.4747.474
946301AF1-294 C
50/50
12.29112.291
942461AE2-259 C
50/50
33.2233.22
964241AG1-285 C
50/50
41.52541.525
316034AC1-036 C
50/50
0.7760.776
958212AF2-115 E
50/50
6.3676.367
3144293JTRSVLE
50/50
1.371.37
946302AF1-294 E
50/50
10.40910.409
925612AC1-036 E
50/50
2.8512.851
936261AD2-033 C
50/50
43.18643.186
961791AG1-021 C
50/50
5.985.98
959311AF2-222 C
50/50
55.36655.366
3147223TWITTYS
50/50
3.1613.161
959312AF2-222 E
50/50
37.09537.095
961792AG1-021 E
50/50
5.0945.094
316131AB2-060 C
50/50
4.9054.905
3138533PONTONDP
50/50
2.2152.215
3147133PAMPLIN
50/50
3.3083.308
924162AB2-060 E OP
50/50
14.17414.174
964242AG1-285 E
50/50
27.68327.683
942462AE2-259 E
50/50
22.14722.147
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0170.017
O66PJM->LTFIMP_O-066
CMTX_NF
0.1520.152
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0130.013
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0390.039
NYPJM->LTFIMP_NY
CLTF
0.0120.012
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0470.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0130.013
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0230.023
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0240.024
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0080.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0580.058
MDUPJM->LTFIMP_MDU
CLTF
0.0020.002

Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012_SRT-A-4


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1012_SRT-A-4
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.66 %
Rating:205.86 MVA
Rating Type:B
MVA to Mitigate:209.27
MW Contribution:100.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
942461AE2-259 C
80/20
59.99759.997
964241AG1-285 C
80/20
74.99774.997
316034AC1-036 C
80/20
1.4011.401
959311AF2-222 C
80/20
99.99699.996
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0030.003
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0020.002
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0080.008
NYPJM->LTFIMP_NY
CLTF
0.0020.002
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0090.009
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0030.003
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0040.004
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0020.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0120.012
MDUPJM->LTFIMP_MDU
CLTF
00

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.29 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:987.04
MW Contribution:6.65
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943171AE2-346 C
80/20
0.1050.105
961941AG1-037 C
80/20
0.2370.237
3151391GASTONA
80/20
2.0712.071
941031AE2-094 C
80/20
22.06822.068
934331AD1-057 C
80/20
2.0892.089
934321AD1-056 C
80/20
3.7443.744
3151531CLOVER1
80/20
6.056.05
3151541CLOVER2
80/20
5.9935.993
958211AF2-115 C
Adder
0.80.68
942001AE2-212 C
Adder
-3.9329411764705884-3.343
940491AE2-034 C
80/20
0.4170.417
934501AD1-074 C
80/20
13.23613.236
3151031BRUNSWICKG2
80/20
4.4784.478
961671AG1-007 C
80/20
0.4820.482
316359AB2-059 C OP
80/20
0.8920.892
934621AD1-088 C
80/20
4.424.42
946301AF1-294 C
Adder
1.3164705882352941.119
316283AC2-100 C
80/20
0.510.51
946281AF1-292 C
80/20
1.1471.147
926071AC1-086 C
80/20
14.30114.301
927021AC1-189 C
80/20
4.1534.153
964241AG1-285 C
80/20
5.5515.551
316034AC1-036 C
80/20
0.0950.095
962561AG1-105 C
80/20
4.0224.022
316118AC1-105 C
80/20
0.4080.408
3156083AA2-088SOLA
80/20
0.4670.467
316365AB2-100 C1
80/20
0.7990.799
3151021BRUNSWICKG1
80/20
4.4784.478
957481AF2-042 C
80/20
26.38726.387
316003AC1-222 C
80/20
0.4260.426
316318V4-068 C
80/20
0.0370.037
966621AG1-532 C
80/20
1.041.04
313506AB1-173 C OP
80/20
0.7570.757
316210AC1-098 C
80/20
0.50.5
316005AA1-067 C
80/20
0.1280.128
3151601KERR 3
80/20
0.5540.554
3151581KERR 1
80/20
0.1980.198
315614AA2-178 C
80/20
0.5670.567
940541AE2-040 C
80/20
2.9992.999
940481AE2-033 C
80/20
16.46516.465
3151411GASTONB
80/20
2.0712.071
316181AB2-040 GEN
80/20
0.8530.853
3147043LAWRENC
80/20
0.2030.203
933981AD1-022 C
80/20
3.5783.578
316174AB2-169_C
80/20
0.4490.449
3156063AA2-053SOLA
80/20
0.860.86
3151281ROARAP4
80/20
0.7750.775
316049AB1-081 C OP
80/20
0.7570.757
316238AB2-078 C O1
80/20
0.1510.151
938771AE1-103 C
Adder
0.96705882352941170.822
960081AF2-299 C
80/20
1.3861.386
3151381ROSEMG2
80/20
0.6340.634
944011AF1-069 C
80/20
7.217.21
963041AG1-153 C
80/20
3.0443.044
3151051BRUNSWICKS1
80/20
9.3029.302
936261AD2-033 C
80/20
5.4245.424
961791AG1-021 C
Adder
0.640.544
316248AF1-058 C
80/20
0.140.14
944641AF1-129 C
Adder
-92.12117647058824-78.303
316240AF1-291 C
Adder
-1.6611764705882353-1.412
934521AD1-076 C
80/20
4.8074.807
934511AD1-075 C
80/20
3.3093.309
3156073AA1-063SOLA
80/20
0.7530.753
316087AB2-174 C
80/20
0.8150.815
316212AC1-099 C
80/20
0.1680.168
316263AC1-034 C
80/20
3.5493.549
937481AD2-202 C
80/20
0.1730.173
3151591KERR 2
80/20
0.5540.554
959311AF2-222 C
80/20
6.6486.648
3152921DOMTR78
80/20
0.5570.557
316140AB2-099 C
80/20
0.0450.045
935171AD1-152 C
80/20
0.620.62
932631AC2-084 C
80/20
0.5330.533
316274AC1-208 C
80/20
4.9624.962
3151311EDGECMA
80/20
8.3398.339
3152661PLYWOOD A
80/20
0.5410.541
316315AB2-025 C
80/20
0.4250.425
316023AB2-100 C2
80/20
0.7990.799
316317KELFORD C
80/20
0.1760.176
316129AC1-054 C
80/20
0.6480.648
3151631KERR 6
80/20
0.5540.554
316131AB2-060 C
80/20
0.680.68
3138533PONTONDP
Adder
0.237647058823529430.202
940641AE2-051 C
80/20
9.0359.035
3152431Z1-086 GT3
80/20
5.7485.748
3156011CONETOE2SOL
80/20
0.6290.629
934611AD1-087 C
80/20
0.5960.596
3151611KERR 4
80/20
0.5540.554
3151621KERR 5
80/20
0.5540.554
316237AB2-079 C O1
80/20
0.1510.151
316222AC1-221 C
80/20
0.6320.632
3151261ROARAP2
80/20
0.8190.819
3152421Z1-086 GT2
80/20
5.7485.748
3152441Z1-086 ST
80/20
10.00810.008
3152411Z1-086 GT1
80/20
5.755.75
316319Z2-044 C
80/20
0.1130.113
3151641KERR 7
80/20
0.5540.554
313527AB2-043 C
80/20
0.2380.238
3151151S HAMPT1
80/20
0.570.57
3151361ROSEMG1
80/20
1.3551.355
3151041BRUNSWICKG3
80/20
4.4784.478
316327AA2-057 C
80/20
0.7010.701
316239AB2-077 C O1
80/20
0.1510.151
964791AG1-342 C
80/20
1.5971.597
939411AE1-173 C
80/20
41.75841.758
3156021HOLLOMANSOL
80/20
0.830.83
316011AB1-132 C OP
80/20
1.5811.581
3151371ROSEMS1
80/20
0.8390.839
3137643SOCKMAN
80/20
0.4490.449
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.6422.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.16446.164
CPLELTFEXP_CPLE->PJM
CLTF
5.5395.539
TVALTFEXP_TVA->PJM
CLTF
3.0473.047
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.95317.953
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.57311.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1342.134
LAGNLTFEXP_LAGN->PJM
CLTF
3.8673.867
NYPJM->LTFIMP_NY
CLTF
0.5840.584
LGEELTFEXP_LGEE->PJM
CLTF
0.6950.695
WECLTFEXP_WEC->PJM
CLTF
0.3670.367
SIGELTFEXP_SIGE->PJM
CLTF
0.1330.133

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.25 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:721.08
MW Contribution:7.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943171AE2-346 C
80/20
0.2840.284
961941AG1-037 C
80/20
0.6420.642
3151391GASTONA
80/20
6.76.7
934331AD1-057 C
80/20
5.7225.722
934321AD1-056 C
80/20
10.25810.258
958211AF2-115 C
80/20
0.790.79
946281AF1-292 C
80/20
3.783.78
926071AC1-086 C
80/20
46.26846.268
927021AC1-189 C
80/20
9.5779.577
964241AG1-285 C
80/20
7.0017.001
316034AC1-036 C
80/20
0.110.11
962561AG1-105 C
80/20
3.8843.884
316118AC1-105 C
80/20
0.3030.303
3144293JTRSVLE
80/20
0.1450.145
3156116Z1-036WIND
80/20
0.2510.251
940491AE2-034 C
80/20
0.7340.734
934501AD1-074 C
80/20
28.03828.038
961671AG1-007 C
80/20
1.1061.106
316359AB2-059 C OP
80/20
2.0212.021
946301AF1-294 C
80/20
1.31.3
934521AD1-076 C
80/20
10.18310.183
934511AD1-075 C
80/20
7.017.01
3156073AA1-063SOLA
80/20
1.9821.982
316087AB2-174 C
80/20
2.5762.576
316212AC1-099 C
80/20
0.4340.434
316263AC1-034 C
80/20
8.0388.038
3151591KERR 2
80/20
0.7120.712
959311AF2-222 C
80/20
7.5547.554
3156083AA2-088SOLA
80/20
1.0451.045
316365AB2-100 C1
80/20
2.8782.878
316318V4-068 C
80/20
0.090.09
966621AG1-532 C
80/20
3.4243.424
313506AB1-173 C OP
80/20
2.3432.343
316210AC1-098 C
80/20
1.2971.297
316005AA1-067 C
80/20
0.2960.296
3151601KERR 3
80/20
0.7120.712
3151581KERR 1
80/20
0.2540.254
315614AA2-178 C
80/20
0.9970.997
3151411GASTONB
80/20
6.76.7
316181AB2-040 GEN
80/20
2.6392.639
3147043LAWRENC
80/20
0.5880.588
933981AD1-022 C
80/20
8.3538.353
316174AB2-169_C
80/20
0.9970.997
3156063AA2-053SOLA
80/20
2.4062.406
3151281ROARAP4
80/20
2.1722.172
316049AB1-081 C OP
80/20
1.7151.715
316238AB2-078 C O1
80/20
0.1950.195
938771AE1-103 C
80/20
1.2731.273
960081AF2-299 C
80/20
4.5664.566
3151381ROSEMG2
80/20
2.0062.006
936261AD2-033 C
80/20
6.4546.454
961791AG1-021 C
80/20
0.6320.632
3156011CONETOE2SOL
80/20
1.4481.448
3151611KERR 4
80/20
0.7120.712
3151621KERR 5
80/20
0.7120.712
316237AB2-079 C O1
80/20
0.1950.195
3152921DOMTR78
80/20
1.2081.208
316140AB2-099 C
80/20
0.1220.122
316319Z2-044 C
80/20
0.2660.266
3151641KERR 7
80/20
0.7120.712
313527AB2-043 C
80/20
0.3120.312
932631AC2-084 C
80/20
1.3811.381
316274AC1-208 C
80/20
12.83612.836
3151311EDGECMA
80/20
19.08119.081
3152661PLYWOOD A
80/20
0.3910.391
316023AB2-100 C2
80/20
2.8782.878
316317KELFORD C
80/20
0.4780.478
316129AC1-054 C
80/20
1.321.32
3151631KERR 6
80/20
0.7120.712
316131AB2-060 C
80/20
0.8840.884
3138533PONTONDP
80/20
0.2340.234
3151261ROARAP2
80/20
2.2952.295
3151151S HAMPT1
80/20
1.0351.035
3151361ROSEMG1
80/20
4.2844.284
316327AA2-057 C
80/20
1.711.71
316239AB2-077 C O1
80/20
0.1950.195
964791AG1-342 C
80/20
1.4341.434
3156021HOLLOMANSOL
80/20
2.3822.382
316011AB1-132 C OP
80/20
5.1165.116
3151371ROSEMS1
80/20
2.6542.654
3137643SOCKMAN
80/20
1.3221.322
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5172.517
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.76439.764
CPLELTFEXP_CPLE->PJM
CLTF
5.2785.278
TVALTFEXP_TVA->PJM
CLTF
2.5052.505
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.04115.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.5619.561
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.7731.773
LAGNLTFEXP_LAGN->PJM
CLTF
3.1853.185
NYPJM->LTFIMP_NY
CLTF
0.4240.424
LGEELTFEXP_LGEE->PJM
CLTF
0.5780.578
WECLTFEXP_WEC->PJM
CLTF
0.3070.307
SIGELTFEXP_SIGE->PJM
CLTF
0.1110.111

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.88 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:698.2
MW Contribution:6.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943171AE2-346 C
80/20
0.2110.211
961941AG1-037 C
80/20
0.4770.477
3151391GASTONA
80/20
6.1266.126
934331AD1-057 C
80/20
5.2595.259
934321AD1-056 C
80/20
9.4289.428
946281AF1-292 C
80/20
3.5653.565
926071AC1-086 C
80/20
42.342.3
940491AE2-034 C
80/20
0.5050.505
934501AD1-074 C
80/20
19.28319.283
961671AG1-007 C
80/20
0.970.97
316359AB2-059 C OP
80/20
1.8661.866
927021AC1-189 C
80/20
8.0138.013
964241AG1-285 C
80/20
6.1446.144
316034AC1-036 C
80/20
0.0940.094
962561AG1-105 C
80/20
3.4083.408
3156083AA2-088SOLA
80/20
0.8980.898
316365AB2-100 C1
80/20
2.7382.738
316318V4-068 C
80/20
0.0730.073
966621AG1-532 C
80/20
3.233.23
313506AB1-173 C OP
80/20
2.1692.169
316210AC1-098 C
80/20
1.1041.104
316005AA1-067 C
80/20
0.2330.233
3151601KERR 3
80/20
0.6330.633
3151581KERR 1
80/20
0.2260.226
936161AD2-022 C
80/20
3.4423.442
315614AA2-178 C
80/20
0.6860.686
3151411GASTONB
80/20
6.1266.126
316181AB2-040 GEN
80/20
2.4442.444
3147043LAWRENC
80/20
0.5520.552
933981AD1-022 C
80/20
5.6735.673
316174AB2-169_C
80/20
0.7390.739
3156063AA2-053SOLA
80/20
2.0962.096
3151281ROARAP4
80/20
1.9471.947
316049AB1-081 C OP
80/20
1.5831.583
316238AB2-078 C O1
80/20
0.1730.173
938771AE1-103 C
80/20
1.1451.145
960081AF2-299 C
80/20
4.3064.306
3151381ROSEMG2
80/20
1.8351.835
936261AD2-033 C
80/20
5.5815.581
936171AD2-023 C
80/20
2.0082.008
934521AD1-076 C
80/20
7.0037.003
934511AD1-075 C
80/20
4.8214.821
3156073AA1-063SOLA
80/20
1.7541.754
316087AB2-174 C
80/20
2.42.4
316212AC1-099 C
80/20
0.370.37
316263AC1-034 C
80/20
7.4217.421
3151591KERR 2
80/20
0.6330.633
959311AF2-222 C
80/20
6.4496.449
3152921DOMTR78
80/20
0.8630.863
316140AB2-099 C
80/20
0.0910.091
316319Z2-044 C
80/20
0.2410.241
3151641KERR 7
80/20
0.6330.633
313527AB2-043 C
80/20
0.2770.277
932631AC2-084 C
80/20
1.1761.176
316274AC1-208 C
80/20
11.28911.289
3151311EDGECMA
80/20
17.61917.619
316023AB2-100 C2
80/20
2.7382.738
316317KELFORD C
80/20
0.3680.368
316129AC1-054 C
80/20
1.1791.179
3151631KERR 6
80/20
0.6330.633
316131AB2-060 C
80/20
0.7820.782
3156011CONETOE2SOL
80/20
1.2441.244
3151611KERR 4
80/20
0.6330.633
3151621KERR 5
80/20
0.6330.633
316237AB2-079 C O1
80/20
0.1730.173
3151261ROARAP2
80/20
2.0572.057
3151151S HAMPT1
80/20
0.9030.903
3151361ROSEMG1
80/20
3.923.92
316327AA2-057 C
80/20
1.5281.528
316239AB2-077 C O1
80/20
0.1730.173
964791AG1-342 C
80/20
1.2551.255
3156021HOLLOMANSOL
80/20
1.581.58
316011AB1-132 C OP
80/20
4.6784.678
3151371ROSEMS1
80/20
2.4282.428
3137643SOCKMAN
80/20
1.2051.205
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1753.175
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.41853.418
CPLELTFEXP_CPLE->PJM
CLTF
6.6566.656
TVALTFEXP_TVA->PJM
CLTF
3.5423.542
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.22922.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.65213.652
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.5732.573
LAGNLTFEXP_LAGN->PJM
CLTF
4.5044.504
NYPJM->LTFIMP_NY
CLTF
0.4770.477
LGEELTFEXP_LGEE->PJM
CLTF
0.8450.845
WECLTFEXP_WEC->PJM
CLTF
0.4510.451
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.94 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:685.04
MW Contribution:7.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943171AE2-346 C
80/20
0.2130.213
961941AG1-037 C
80/20
0.480.48
3151391GASTONA
80/20
6.1336.133
934331AD1-057 C
80/20
5.0965.096
934321AD1-056 C
80/20
9.1359.135
958211AF2-115 C
80/20
0.7340.734
3156116Z1-036WIND
80/20
0.2010.201
940491AE2-034 C
80/20
0.5370.537
934501AD1-074 C
80/20
19.85319.853
961671AG1-007 C
80/20
0.9040.904
316359AB2-059 C OP
80/20
1.731.73
946301AF1-294 C
80/20
1.2081.208
946281AF1-292 C
80/20
3.6023.602
926071AC1-086 C
80/20
42.34842.348
927021AC1-189 C
80/20
7.5047.504
964241AG1-285 C
80/20
6.4946.494
316034AC1-036 C
80/20
0.1020.102
962561AG1-105 C
80/20
3.5683.568
3144293JTRSVLE
80/20
0.1350.135
3156083AA2-088SOLA
80/20
0.9250.925
316365AB2-100 C1
80/20
2.7652.765
316318V4-068 C
80/20
0.0740.074
966621AG1-532 C
80/20
3.2633.263
313506AB1-173 C OP
80/20
2.1872.187
316210AC1-098 C
80/20
1.0791.079
316005AA1-067 C
80/20
0.220.22
3151601KERR 3
80/20
0.6440.644
3151581KERR 1
80/20
0.230.23
315614AA2-178 C
80/20
0.7290.729
940541AE2-040 C
80/20
11.74711.747
940481AE2-033 C
80/20
63.69463.694
3151411GASTONB
80/20
6.1336.133
316181AB2-040 GEN
80/20
2.4632.463
3147043LAWRENC
80/20
0.5590.559
933981AD1-022 C
80/20
5.7955.795
316174AB2-169_C
80/20
0.7240.724
3156063AA2-053SOLA
80/20
2.1042.104
3151281ROARAP4
80/20
1.9541.954
316049AB1-081 C OP
80/20
1.4681.468
316238AB2-078 C O1
80/20
0.1810.181
938771AE1-103 C
80/20
1.2791.279
960081AF2-299 C
80/20
4.3514.351
3151381ROSEMG2
80/20
1.831.83
936261AD2-033 C
80/20
5.9895.989
961791AG1-021 C
80/20
0.5880.588
934521AD1-076 C
80/20
7.217.21
934511AD1-075 C
80/20
4.9634.963
3156073AA1-063SOLA
80/20
1.7721.772
316087AB2-174 C
80/20
2.4212.421
316212AC1-099 C
80/20
0.3610.361
316263AC1-034 C
80/20
6.8836.883
3151591KERR 2
80/20
0.6440.644
959311AF2-222 C
80/20
7.0127.012
3152921DOMTR78
80/20
0.8660.866
316140AB2-099 C
80/20
0.0910.091
316319Z2-044 C
80/20
0.2270.227
3151641KERR 7
80/20
0.6440.644
313527AB2-043 C
80/20
0.290.29
932631AC2-084 C
80/20
1.1481.148
316274AC1-208 C
80/20
11.02211.022
3151311EDGECMA
80/20
16.35316.353
316315AB2-025 C
80/20
1.6631.663
316023AB2-100 C2
80/20
2.7652.765
316317KELFORD C
80/20
0.3660.366
316129AC1-054 C
80/20
1.1891.189
3151631KERR 6
80/20
0.6440.644
316131AB2-060 C
80/20
0.820.82
3138533PONTONDP
80/20
0.2180.218
3156011CONETOE2SOL
80/20
1.1621.162
3151611KERR 4
80/20
0.6440.644
3151621KERR 5
80/20
0.6440.644
316237AB2-079 C O1
80/20
0.1810.181
3151261ROARAP2
80/20
2.0652.065
3151151S HAMPT1
80/20
0.9570.957
3151361ROSEMG1
80/20
3.9083.908
316327AA2-057 C
80/20
1.461.46
316239AB2-077 C O1
80/20
0.1810.181
964791AG1-342 C
80/20
1.3141.314
3156021HOLLOMANSOL
80/20
1.5911.591
316011AB1-132 C OP
80/20
4.6834.683
3151371ROSEMS1
80/20
2.422.42
3137643SOCKMAN
80/20
1.2121.212
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.0622.062
CBM South 2LTFEXP_CBM-S2->PJM
CBM
32.61632.616
CPLELTFEXP_CPLE->PJM
CLTF
4.3234.323
TVALTFEXP_TVA->PJM
CLTF
2.0422.042
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.06512.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.7657.765
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4321.432
LAGNLTFEXP_LAGN->PJM
CLTF
2.5962.596
NYPJM->LTFIMP_NY
CLTF
0.370.37
LGEELTFEXP_LGEE->PJM
CLTF
0.4650.465
WECLTFEXP_WEC->PJM
CLTF
0.2460.246
SIGELTFEXP_SIGE->PJM
CLTF
0.0890.089

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.39 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3329.54
MW Contribution:18.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151081ELIZAR1
80/20
4.2584.258
943171AE2-346 C
80/20
0.2980.298
961941AG1-037 C
80/20
0.6730.673
3151391GASTONA
80/20
4.0664.066
941031AE2-094 C
80/20
66.45566.455
934331AD1-057 C
Adder
4.6482352941176473.951
934321AD1-056 C
Adder
8.332941176470597.083
3151531CLOVER1
80/20
17.9517.95
3151541CLOVER2
80/20
17.78117.781
958211AF2-115 C
Adder
2.28235294117647051.94
316349AD2-085 C
80/20
4.3374.337
3151091ELIZAR2
80/20
4.1834.183
946281AF1-292 C
80/20
2.0562.056
926071AC1-086 C
80/20
28.07728.077
927021AC1-189 C
Adder
11.1952941176470599.516
964241AG1-285 C
Adder
14.80352941176470712.583
962561AG1-105 C
Adder
11.0694117647058839.409
942001AE2-212 C
Adder
2.11411764705882371.797
3156116Z1-036WIND
80/20
0.8770.877
940491AE2-034 C
80/20
1.5381.538
934501AD1-074 C
80/20
45.0845.08
3151031BRUNSWICKG2
80/20
13.44613.446
961671AG1-007 C
Adder
1.2482352941176471.061
934621AD1-088 C
80/20
13.20613.206
946301AF1-294 C
Adder
3.75411764705882333.191
316036AC1-147 C
80/20
0.4890.489
316305AF2-043 C
80/20
0.4630.463
316321Z2-027 C
80/20
0.4860.486
934521AD1-076 C
80/20
16.37216.372
940431AE2-027 C
Adder
11.395294117647069.686
916191Z1-068 C
80/20
0.0580.058
941101AE2-104 C
80/20
4.4074.407
316185AD1-033 C
80/20
1.6481.648
944581AF1-123 C
80/20
61.95761.957
316294AC1-161 C
80/20
6.8246.824
3156083AA2-088SOLA
80/20
1.4051.405
316365AB2-100 C1
80/20
1.2911.291
3151021BRUNSWICKG1
80/20
13.44613.446
957481AF2-042 C
80/20
78.71578.715
942341AE2-247 C
80/20
1.881.88
316246AF1-032 C
80/20
0.3780.378
316388AE2-253 GEN
80/20
2.6322.632
316320Y1-086 C
80/20
0.2940.294
316318V4-068 C
80/20
0.1070.107
966621AG1-532 C
80/20
1.8631.863
313506AB1-173 C OP
80/20
1.4941.494
316210AC1-098 C
80/20
1.251.25
935171AD1-152 C
80/20
1.8271.827
936161AD2-022 C
Adder
9.455294117647068.037
961611AG1-000B C
Adder
17.0670588235294114.507
316072AD1-144 C
80/20
0.3590.359
316375AC2-012 C
80/20
1.7911.791
315614AA2-178 C
80/20
2.0912.091
940541AE2-040 C
80/20
3.9443.944
940481AE2-033 C
80/20
22.18122.181
3151411GASTONB
80/20
4.0664.066
316181AB2-040 GEN
80/20
1.6831.683
3147043LAWRENC
80/20
0.3980.398
935161AD1-151 C
Adder
15.27058823529411812.98
958161AF2-110 C
80/20
1.7981.798
938531AE1-072 C
80/20
23.60823.608
933981AD1-022 C
80/20
11.71411.714
316174AB2-169_C
80/20
1.3931.393
3156063AA2-053SOLA
80/20
1.9981.998
3151281ROARAP4
80/20
1.7351.735
941591AE2-156 C
80/20
23.83823.838
3151101ELIZAR3
80/20
4.3114.311
944591AF1-124 C
80/20
62.17762.177
944601AF1-125 C
80/20
61.00261.002
938771AE1-103 C
80/20
3.8693.869
960081AF2-299 C
80/20
2.4842.484
3151381ROSEMG2
80/20
1.271.27
944011AF1-069 C
80/20
21.71321.713
963041AG1-153 C
80/20
9.1419.141
3151051BRUNSWICKS1
80/20
27.93527.935
936261AD2-033 C
Adder
14.72470588235294112.516
961791AG1-021 C
Adder
1.82588235294117651.552
936171AD2-023 C
Adder
5.5152941176470584.688
3152331SURRY 2
80/20
30.82730.827
316017AA1-139 ULT1
80/20
1.4491.449
934511AD1-075 C
80/20
11.2711.27
3156073AA1-063SOLA
80/20
1.8611.861
316087AB2-174 C
80/20
1.561.56
316212AC1-099 C
80/20
0.4180.418
316263AC1-034 C
Adder
8.8035294117647057.483
937481AD2-202 C
80/20
0.5130.513
959311AF2-222 C
Adder
18.28823529411764815.545
3150921YORKTN3
Adder
127.84235294117647108.666
316018AA1-139 ULT2
80/20
1.4491.449
933291AC2-141 C
80/20
41.90441.904
3152921DOMTR78
80/20
1.8181.818
316140AB2-099 C
80/20
0.1280.128
957871AF2-081 C
80/20
13.4313.43
932631AC2-084 C
80/20
1.3311.331
316274AC1-208 C
80/20
11.98411.984
3151311EDGECMA
Adder
20.58941176470588317.501
316316AC1-027 C
80/20
0.4210.421
316315AB2-025 C
80/20
0.5580.558
316023AB2-100 C2
80/20
1.2911.291
316317KELFORD C
80/20
0.4760.476
316129AC1-054 C
80/20
1.5891.589
3138533PONTONDP
Adder
0.6764705882352940.575
313526AB2-022 C
80/20
0.5040.504
940641AE2-051 C
80/20
28.76428.764
3152431Z1-086 GT3
80/20
17.27717.277
934611AD1-087 C
80/20
1.7671.767
943461AF1-017 C
80/20
1.7011.701
316311AC2-079 C
80/20
7.2667.266
3156056W1-029WIND
80/20
1.0361.036
3151261ROARAP2
80/20
1.8341.834
3152421Z1-086 GT2
80/20
17.27717.277
3152441Z1-086 ST
80/20
30.08230.082
3152411Z1-086 GT1
80/20
17.28217.282
939191AE1-149 C
Adder
11.99058823529411710.192
3150981CHESPKA
80/20
0.5780.578
3151151S HAMPT1
80/20
1.9741.974
3151361ROSEMG1
80/20
2.7122.712
3151041BRUNSWICKG3
80/20
13.44613.446
964791AG1-342 C
Adder
4.4317647058823533.767
3150991CHESPKB
80/20
0.9580.958
939411AE1-173 C
80/20
144.1144.1
3156021HOLLOMANSOL
80/20
2.4482.448
316011AB1-132 C OP
80/20
3.1053.105
3151371ROSEMS1
80/20
1.681.68
3137643SOCKMAN
80/20
0.9470.947
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.597.59
CBM South 2LTFEXP_CBM-S2->PJM
CBM
135.46135.46
CPLELTFEXP_CPLE->PJM
CLTF
15.91315.913
TVALTFEXP_TVA->PJM
CLTF
9.319.31
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.0655.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.38335.383
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.566.56
LAGNLTFEXP_LAGN->PJM
CLTF
11.74411.744
NYPJM->LTFIMP_NY
CLTF
2.5592.559
LGEELTFEXP_LGEE->PJM
CLTF
2.182.18
WECLTFEXP_WEC->PJM
CLTF
1.1331.133
SIGELTFEXP_SIGE->PJM
CLTF
0.4150.415

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.4 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3845.28
MW Contribution:22.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150831SPRUNCA
80/20
13.15813.158
3150841SPRUNCB
80/20
13.15813.158
3151081ELIZAR1
80/20
4.824.82
961941AG1-037 C
Adder
0.74470588235294120.633
941031AE2-094 C
80/20
63.15563.155
934331AD1-057 C
Adder
5.04588235294117654.289
934321AD1-056 C
Adder
9.0458823529411777.689
3151531CLOVER1
80/20
18.57418.574
3151541CLOVER2
80/20
18.39918.399
316258AE1-075 C
80/20
0.5130.513
958211AF2-115 C
Adder
3.0058823529411772.555
316169AC1-164 GEN
Adder
49.0282352941176541.674
316349AD2-085 C
80/20
5.1625.162
3151091ELIZAR2
80/20
4.7364.736
946281AF1-292 C
Adder
2.2752941176470591.934
926071AC1-086 C
Adder
30.83882352941176626.213
927021AC1-189 C
Adder
12.14117647058823710.32
964241AG1-285 C
Adder
17.31176470588235414.715
962561AG1-105 C
Adder
12.25882352941176610.42
942001AE2-212 C
80/20
3.1513.151
3156116Z1-036WIND
80/20
0.9810.981
934501AD1-074 C
Adder
50.0317647058823542.527
3151031BRUNSWICKG2
80/20
12.91412.914
961671AG1-007 C
Adder
1.34941176470588231.147
934621AD1-088 C
80/20
14.01914.019
946301AF1-294 C
Adder
4.9423529411764714.201
942461AE2-259 C
Adder
12.99058823529411711.042
3150601CHESTF5
Adder
83.0647058823529570.605
941591AE2-156 C
80/20
27.03327.033
3151101ELIZAR3
80/20
4.8814.881
944591AF1-124 C
80/20
69.22169.221
944601AF1-125 C
80/20
67.91467.914
938771AE1-103 C
80/20
4.3814.381
960081AF2-299 C
Adder
2.74941176470588242.337
944011AF1-069 C
80/20
20.63520.635
963041AG1-153 C
80/20
8.7798.779
3151051BRUNSWICKS1
80/20
26.8326.83
936261AD2-033 C
Adder
17.81058823529411615.139
961791AG1-021 C
Adder
2.40470588235294122.044
944641AF1-129 C
Adder
144.29529411764705122.651
316240AF1-291 C
Adder
3.0682352941176472.608
316036AC1-147 C
80/20
0.5540.554
316305AF2-043 C
80/20
0.5240.524
316321Z2-027 C
80/20
0.5460.546
934521AD1-076 C
Adder
18.1705882352941215.445
934511AD1-075 C
Adder
12.50823529411764710.632
316263AC1-034 C
Adder
9.488.058
959311AF2-222 C
Adder
22.66470588235294419.265
940431AE2-027 C
Adder
18.39647058823529615.637
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
5.0455.045
316185AD1-033 C
80/20
1.8511.851
944581AF1-123 C
80/20
68.97668.976
316294AC1-161 C
80/20
7.5057.505
316365AB2-100 C1
80/20
1.4231.423
3151021BRUNSWICKG1
80/20
12.91412.914
957481AF2-042 C
80/20
80.37380.373
942341AE2-247 C
80/20
2.2382.238
316246AF1-032 C
80/20
0.4280.428
316388AE2-253 GEN
80/20
2.9552.955
316320Y1-086 C
80/20
0.330.33
966621AG1-532 C
Adder
2.06235294117647071.753
961611AG1-000B C
Adder
22.90588235294117719.47
316072AD1-144 C
80/20
0.4180.418
316375AC2-012 C
80/20
2.0322.032
940541AE2-040 C
80/20
4.3564.356
940481AE2-033 C
80/20
24.49624.496
3150731STONECA
Adder
9.5788235294117648.142
935161AD1-151 C
Adder
22.80117647058823519.381
316083AB2-161 C
80/20
0.8230.823
958161AF2-110 C
80/20
2.0582.058
938531AE1-072 C
80/20
26.49826.498
933981AD1-022 C
Adder
12.98823529411764711.04
316316AC1-027 C
80/20
0.4760.476
316315AB2-025 C
80/20
0.6170.617
316023AB2-100 C2
80/20
1.4231.423
3138533PONTONDP
Adder
0.89058823529411770.757
943471AF1-018 C
Adder
8.4917647058823537.218
3151221GRAVEL6
80/20
3.6533.653
3151201GRAVEL4
80/20
3.6573.657
3151211GRAVEL5
80/20
3.6113.611
316236AE1-162 C
80/20
0.5140.514
3152331SURRY 2
80/20
35.95635.956
316017AA1-139 ULT1
80/20
1.6261.626
313526AB2-022 C
80/20
0.5650.565
940641AE2-051 C
80/20
27.74527.745
3152431Z1-086 GT3
80/20
16.53816.538
316336AC2-165 C
Adder
14.04941176470588411.942
944631AF1-128 C
Adder
51.9752941176470644.179
3150921YORKTN3
Adder
165.5670588235294140.732
3151191GRAVEL3
80/20
3.6113.611
3150851SPRUNCC
80/20
0.2360.236
316018AA1-139 ULT2
80/20
1.6261.626
933291AC2-141 C
80/20
46.08646.086
3150651CHESTF6
Adder
26.27176470588235422.331
3150861SPRUNCD
80/20
0.2360.236
957871AF2-081 C
80/20
15.07515.075
316274AC1-208 C
Adder
13.08588235294117711.123
3151311EDGECMA
Adder
22.1658823529411818.841
316405AF2-144 C
80/20
0.4360.436
940551AE2-041 C
Adder
8.4917647058823537.218
943461AF1-017 C
80/20
2.0242.024
316311AC2-079 C
80/20
8.6058.605
3156056W1-029WIND
80/20
1.1641.164
316233AE1-074 C
80/20
3.9163.916
3152421Z1-086 GT2
80/20
16.53816.538
3152441Z1-086 ST
80/20
28.79528.795
3152411Z1-086 GT1
80/20
16.54216.542
939191AE1-149 C
80/20
15.94215.942
3150981CHESPKA
80/20
0.6560.656
3151041BRUNSWICKG3
80/20
12.91412.914
316313AB2-026 C
80/20
0.5590.559
964791AG1-342 C
Adder
4.884.148
957601AF2-054 C
Adder
2.53058823529411742.151
3151161SURRY 1
80/20
35.54335.543
316381AD1-082 C
80/20
1.8751.875
3150991CHESPKB
80/20
1.0871.087
939411AE1-173 C
80/20
143.49143.49
3137643SOCKMAN
Adder
1.04352941176470580.887
316303AF2-085
80/20
6.4786.478
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.9747.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
144.491144.491
CPLELTFEXP_CPLE->PJM
CLTF
16.71416.714
TVALTFEXP_TVA->PJM
CLTF
10.46710.467
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.12565.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.22440.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6237.623
LAGNLTFEXP_LAGN->PJM
CLTF
13.13513.135
NYPJM->LTFIMP_NY
CLTF
3.1863.186
LGEELTFEXP_LGEE->PJM
CLTF
2.5932.593
WECLTFEXP_WEC->PJM
CLTF
1.3381.338
SIGELTFEXP_SIGE->PJM
CLTF
0.4870.487

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.63 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3595.09
MW Contribution:13.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.37294117647058830.317
941031AE2-094 C
80/20
37.11337.113
934331AD1-057 C
Adder
2.6258823529411772.232
934321AD1-056 C
Adder
4.7070588235294134.001
3151531CLOVER1
80/20
10.82910.829
3151541CLOVER2
80/20
10.72710.727
316258AE1-075 C
80/20
0.320.32
958211AF2-115 C
80/20
1.7961.796
3151791S ANNAG2
80/20
3.2623.262
3151771S ANNAG1
80/20
3.2623.262
3151781S ANNAS1
80/20
1.6761.676
3151761LOISA E
80/20
6.8276.827
208900BRIS G1
80/20
-2.405-2.405
316349AD2-085 C
Adder
2.3964705882352942.037
946281AF1-292 C
80/20
1.2041.204
926071AC1-086 C
Adder
15.98823529411764713.59
927021AC1-189 C
Adder
6.225.287
964241AG1-285 C
80/20
9.9749.974
316034AC1-036 C
80/20
0.1860.186
962561AG1-105 C
Adder
6.9729411764705885.927
3144293JTRSVLE
80/20
0.3290.329
316044AC1-158 C1
80/20
18.51718.517
942001AE2-212 C
Adder
1.40235294117647061.192
934501AD1-074 C
Adder
24.38588235294117720.728
3151031BRUNSWICKG2
80/20
7.5577.557
961671AG1-007 C
Adder
0.69647058823529410.592
934621AD1-088 C
80/20
8.2538.253
946301AF1-294 C
80/20
2.9542.954
942461AE2-259 C
80/20
7.9867.986
316192AB2-158 C
80/20
4.3254.325
208901BRIS G2
80/20
-2.846-2.846
941591AE2-156 C
Adder
12.43294117647058910.568
944591AF1-124 C
Adder
32.1611764705882427.337
944601AF1-125 C
Adder
31.55411764705882826.821
938771AE1-103 C
Adder
2.10235294117647081.787
934521AD1-076 C
Adder
8.8564705882352937.528
934511AD1-075 C
Adder
6.0964705882352945.182
316087AB2-174 C
80/20
0.9080.908
316263AC1-034 C
Adder
4.9470588235294124.205
937481AD2-202 C
80/20
0.3090.309
959311AF2-222 C
80/20
13.30313.303
941101AE2-104 C
Adder
2.35411764705882342.001
944581AF1-123 C
Adder
32.0470588235294127.24
316365AB2-100 C1
80/20
0.7450.745
3151021BRUNSWICKG1
80/20
7.5577.557
957481AF2-042 C
80/20
47.06247.062
3151801S ANNAS2
80/20
1.6761.676
942341AE2-247 C
Adder
1.03882352941176470.883
966621AG1-532 C
80/20
1.0911.091
935171AD1-152 C
80/20
1.0991.099
3152261N ANNA2
80/20
103.963103.963
934861AD1-115 C
80/20
3.3063.306
940541AE2-040 C
80/20
2.2982.298
940481AE2-033 C
80/20
12.91312.913
3147043LAWRENC
80/20
0.240.24
966001AG1-469 C
80/20
2.3822.382
958161AF2-110 C
Adder
0.96117647058823530.817
938531AE1-072 C
Adder
12.33529411764705810.485
933981AD1-022 C
Adder
6.3599999999999995.406
316238AB2-078 C O1
80/20
0.2590.259
960081AF2-299 C
80/20
1.4551.455
944011AF1-069 C
80/20
12.12612.126
963041AG1-153 C
80/20
5.1375.137
3151051BRUNSWICKS1
80/20
15.69915.699
936261AD2-033 C
80/20
10.37510.375
961791AG1-021 C
80/20
1.4371.437
316045AC1-158 C2
80/20
18.51718.517
316170AC1-121 C
80/20
2.952.95
316315AB2-025 C
80/20
0.3250.325
316023AB2-100 C2
80/20
0.7450.745
316131AB2-060 C
80/20
1.1781.178
3138533PONTONDP
80/20
0.5320.532
3151721LOISA A
80/20
3.3313.331
316254AC1-120 C
80/20
8.5918.591
316257AC1-043 C
80/20
6.6126.612
940641AE2-051 C
80/20
15.75815.758
3152431Z1-086 GT3
80/20
9.699.69
934611AD1-087 C
80/20
1.0661.066
316237AB2-079 C O1
80/20
0.2590.259
316336AC2-165 C
80/20
8.8748.874
933291AC2-141 C
Adder
21.0423529411764717.886
313527AB2-043 C
80/20
0.4090.409
3152251N ANNA1
80/20
103.92103.92
957871AF2-081 C
Adder
7.0094117647058835.958
316274AC1-208 C
Adder
6.785.763
3151311EDGECMA
Adder
11.569.826
316405AF2-144 C
80/20
0.2720.272
943461AF1-017 C
Adder
0.94000000000000010.799
316311AC2-079 C
Adder
3.99647058823529383.397
316233AE1-074 C
80/20
2.0672.067
3152421Z1-086 GT2
80/20
9.699.69
3152441Z1-086 ST
80/20
16.87216.872
3152411Z1-086 GT1
80/20
9.6939.693
939191AE1-149 C
Adder
7.2929411764705886.199
3151041BRUNSWICKG3
80/20
7.5577.557
316239AB2-077 C O1
80/20
0.2590.259
316313AB2-026 C
80/20
0.3480.348
964791AG1-342 C
Adder
2.77294117647058872.357
3151751LOISA D
80/20
3.3493.349
3151731LOISA B
80/20
3.3493.349
316164AC1-076_C
80/20
1.0891.089
939411AE1-173 C
80/20
78.11378.113
3137643SOCKMAN
Adder
0.54588235294117650.464
3151741LOISA C
80/20
3.3493.349
316303AF2-085
80/20
3.8763.876
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2194.219
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.82173.821
CPLELTFEXP_CPLE->PJM
CLTF
8.8538.853
TVALTFEXP_TVA->PJM
CLTF
4.5224.522
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.20919.209
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.12316.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.6672.667
LAGNLTFEXP_LAGN->PJM
CLTF
5.7055.705
NYPJM->LTFIMP_NY
CLTF
2.292.29
LGEELTFEXP_LGEE->PJM
CLTF
0.8350.835
WECLTFEXP_WEC->PJM
CLTF
0.4130.413
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.86 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3570.05
MW Contribution:13.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150831SPRUNCA
Adder
6.1623529411764715.238
3150841SPRUNCB
Adder
6.1623529411764715.238
961941AG1-037 C
Adder
0.39411764705882360.335
941031AE2-094 C
80/20
38.91138.911
934331AD1-057 C
Adder
2.7741176470588242.358
934321AD1-056 C
Adder
4.9729411764705894.227
3151531CLOVER1
80/20
11.34911.349
3151541CLOVER2
80/20
11.24311.243
316258AE1-075 C
80/20
0.3330.333
958211AF2-115 C
80/20
1.8751.875
3151791S ANNAG2
80/20
3.0413.041
3151771S ANNAG1
80/20
3.0413.041
3151781S ANNAS1
80/20
1.5631.563
3151761LOISA E
80/20
6.316.31
208900BRIS G1
80/20
-2.414-2.414
316349AD2-085 C
Adder
2.5505882352941182.168
946281AF1-292 C
80/20
1.2711.271
926071AC1-086 C
Adder
16.8929411764705914.359
927021AC1-189 C
Adder
6.5788235294117645.592
964241AG1-285 C
80/20
10.44910.449
316034AC1-036 C
80/20
0.1950.195
962561AG1-105 C
Adder
7.3152941176470596.218
3144293JTRSVLE
80/20
0.3440.344
942001AE2-212 C
Adder
1.49882352941176471.274
934501AD1-074 C
Adder
25.86823529411764621.988
3151031BRUNSWICKG2
80/20
7.9247.924
961671AG1-007 C
Adder
0.73647058823529410.626
934621AD1-088 C
80/20
8.6418.641
946301AF1-294 C
80/20
3.0833.083
942461AE2-259 C
Adder
8.3117647058823547.065
316192AB2-158 C
80/20
4.2764.276
208901BRIS G2
80/20
-2.857-2.857
944641AF1-129 C
Adder
63.6988235294117654.144
316240AF1-291 C
Adder
1.37882352941176461.172
934521AD1-076 C
Adder
9.3952941176470587.986
934511AD1-075 C
Adder
6.46705882352941155.497
316087AB2-174 C
80/20
0.9580.958
316263AC1-034 C
Adder
5.2270588235294114.443
937481AD2-202 C
80/20
0.3240.324
959311AF2-222 C
80/20
13.90913.909
940431AE2-027 C
Adder
8.3129411764705887.066
941101AE2-104 C
Adder
2.50470588235294132.129
944581AF1-123 C
Adder
34.0988235294117728.984
316365AB2-100 C1
80/20
0.7870.787
3151021BRUNSWICKG1
80/20
7.9247.924
957481AF2-042 C
80/20
49.31549.315
3151801S ANNAS2
80/20
1.5631.563
942341AE2-247 C
Adder
1.10588235294117650.94
966621AG1-532 C
80/20
1.1511.151
313506AB1-173 C OP
80/20
0.9150.915
935171AD1-152 C
80/20
1.1531.153
3152261N ANNA2
80/20
106.999106.999
961611AG1-000B C
Adder
10.3129411764705888.766
940541AE2-040 C
80/20
2.4262.426
940481AE2-033 C
80/20
13.63113.631
316181AB2-040 GEN
80/20
1.0311.031
3147043LAWRENC
80/20
0.2530.253
966001AG1-469 C
80/20
1.9821.982
958161AF2-110 C
Adder
1.02235294117647070.869
938531AE1-072 C
Adder
13.12352941176470511.155
933981AD1-022 C
Adder
6.7447058823529415.733
316238AB2-078 C O1
80/20
0.2720.272
941591AE2-156 C
Adder
13.23882352941176611.253
944591AF1-124 C
Adder
34.2229.087
944601AF1-125 C
Adder
33.5741176470588328.538
938771AE1-103 C
Adder
2.2329411764705881.898
960081AF2-299 C
80/20
1.5351.535
944011AF1-069 C
80/20
12.71412.714
963041AG1-153 C
80/20
5.3875.387
3151051BRUNSWICKS1
80/20
16.46316.463
936261AD2-033 C
80/20
10.85610.856
961791AG1-021 C
80/20
1.51.5
316315AB2-025 C
80/20
0.3440.344
316023AB2-100 C2
80/20
0.7870.787
316131AB2-060 C
80/20
1.2351.235
3138533PONTONDP
80/20
0.5550.555
3151721LOISA A
80/20
3.0793.079
940641AE2-051 C
80/20
16.55416.554
3152431Z1-086 GT3
80/20
10.16110.161
934611AD1-087 C
80/20
1.1171.117
316237AB2-079 C O1
80/20
0.2720.272
316336AC2-165 C
80/20
9.2269.226
933291AC2-141 C
Adder
22.41294117647058619.051
313527AB2-043 C
80/20
0.4290.429
3152251N ANNA1
80/20
106.954106.954
3150651CHESTF6
Adder
11.5976470588235319.858
957871AF2-081 C
Adder
7.4588235294117656.34
316274AC1-208 C
Adder
7.1635294117647066.089
3151311EDGECMA
Adder
12.21411764705882410.382
316405AF2-144 C
80/20
0.2830.283
943461AF1-017 C
Adder
1.00.85
316311AC2-079 C
Adder
4.2541176470588233.616
316233AE1-074 C
80/20
2.1822.182
3152421Z1-086 GT2
80/20
10.16110.161
3152441Z1-086 ST
80/20
17.69217.692
3152411Z1-086 GT1
80/20
10.16410.164
939191AE1-149 C
Adder
7.7752941176470596.609
3151041BRUNSWICKG3
80/20
7.9247.924
316239AB2-077 C O1
80/20
0.2720.272
316313AB2-026 C
80/20
0.3630.363
964791AG1-342 C
Adder
2.9105882352941182.474
3151751LOISA D
80/20
3.0953.095
3151731LOISA B
80/20
3.0953.095
939411AE1-173 C
80/20
82.26382.263
3137643SOCKMAN
Adder
0.57647058823529410.49
3151741LOISA C
80/20
3.0953.095
316303AF2-085
80/20
4.064.06
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4574.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
78.26878.268
CPLELTFEXP_CPLE->PJM
CLTF
9.3529.352
TVALTFEXP_TVA->PJM
CLTF
4.8954.895
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.24822.248
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.65817.658
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.9882.988
LAGNLTFEXP_LAGN->PJM
CLTF
6.1746.174
NYPJM->LTFIMP_NY
CLTF
2.2912.291
LGEELTFEXP_LGEE->PJM
CLTF
0.9480.948
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
SIGELTFEXP_SIGE->PJM
CLTF
0.1860.186

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.14 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4339.53
MW Contribution:23.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
939192AE1-149 E
Adder
5.1470588235294124.375
939312AE1-162 E
Adder
0.97647058823529410.83
942002AE2-212 E
Adder
0.99176470588235290.843
941101AE2-104 C
Adder
2.48705882352941152.114
944581AF1-123 C
Adder
33.8670588235294128.787
316141AB2-099 E
Adder
0.195294117647058840.166
316088AB2-174 E
Adder
5.2858823529411774.493
923994AB2-040_E
Adder
4.9741176470588234.228
961672AG1-007 E
Adder
0.414117647058823530.352
957481AF2-042 C
Adder
49.0341176470588341.679
924322AB2-079 E O1
Adder
1.10588235294117650.94
946302AF1-294 E
Adder
2.59294117647058852.204
943902AF1-058 E
Adder
1.04352941176470580.887
3151801S ANNAS2
50/50
1.5681.568
940541AE2-040 C
Adder
2.4117647058823532.05
940481AE2-033 C
Adder
13.54823529411764811.516
940482AE2-033 E
Adder
9.1341176470588247.764
923263AB1-132 E OP
Adder
4.8811764705882354.149
924312AB2-078 E O1
Adder
1.10588235294117650.94
925612AC1-036 E
Adder
0.7117647058823530.605
926274AC1-105 E
Adder
2.1788235294117651.852
966001AG1-469 C
50/50
2.0062.006
926740AC1-158 E2
50/50
51.18251.182
932046AC2-012 E
Adder
9.6164705882352938.174
958161AF2-110 C
Adder
1.0152941176470590.863
938531AE1-072 C
Adder
13.03294117647058811.078
3145393UNCAMP
Adder
4.622352941176473.929
933981AD1-022 C
Adder
6.6952941176470595.691
900672V4-068 E
Adder
0.276470588235294130.235
924302AB2-077 E O1
Adder
1.10588235294117650.94
943462AF1-017 E
Adder
1.621.377
942341AE2-247 C
Adder
1.09764705882352940.933
958162AF2-110 E
Adder
1.61411764705882371.372
919153AA1-139 E2
Adder
3.02941176470588272.575
934502AD1-074 E
Adder
13.07176470588235311.111
934512AD1-075 E
Adder
3.26823529411764732.778
918512AA1-065 E OP
Adder
4.2588235294117653.62
924516AB2-100 E1
Adder
2.36470588235294082.01
940642AE2-051 E
50/50
10.98110.981
966621AG1-532 C
Adder
1.1435294117647060.972
918532AA1-067 E
Adder
0.55176470588235290.469
924022AB2-043 E O1
Adder
4.2929411764705883.649
3147223TWITTYS
Adder
0.78941176470588240.671
959312AF2-222 E
Adder
9.2564705882352957.868
3152261N ANNA2
50/50
106.886106.886
946282AF1-292 E
Adder
0.84117647058823530.715
944012AF1-069 E
50/50
4.9154.915
917512Z2-088 E OP1
Adder
3.8047058823529413.234
3138533PONTONDP
Adder
0.55176470588235290.469
3151721LOISA A
50/50
3.093.09
3150831SPRUNCA
Adder
6.117647058823535.2
3150841SPRUNCB
Adder
6.117647058823535.2
926662AC1-147 E
Adder
0.97176470588235290.826
916192Z1-068 E
Adder
1.38588235294117631.178
957492AF2-043 E
Adder
1.05294117647058830.895
923852AB2-025 E
Adder
0.97529411764705880.829
939412AE1-173 E
Adder
54.5505882352941246.368
961942AG1-037 E
Adder
0.26117647058823530.222
961941AG1-037 C
Adder
0.391764705882352960.333
941031AE2-094 C
50/50
38.72138.721
941032AE2-094 E
50/50
17.34217.342
934331AD1-057 C
Adder
2.75294117647058822.34
934322AD1-056 E
Adder
2.6764705882352942.275
934332AD1-057 E
Adder
1.43411764705882371.219
934321AD1-056 C
Adder
4.9352941176470594.195
927022AC1-189 E
Adder
3.25058823529411762.763
925595AC1-034 E
Adder
3.91058823529411773.324
936262AD2-033 E
Adder
7.1882352941176476.11
923862AB2-026 E
Adder
1.17294117647058820.997
958211AF2-115 C
Adder
1.86235294117647051.583
3151791S ANNAG2
50/50
3.0513.051
3151771S ANNAG1
50/50
3.0513.051
3151781S ANNAS1
50/50
1.5681.568
3151761LOISA E
50/50
6.3326.332
208900BRIS G1
50/50
-2.489-2.489
316084AB2-161 E
Adder
4.0141176470588233.412
3145946PLYMOUTH TP
Adder
0.245882352941176470.209
933982AD1-022 E
Adder
3.6447058823529413.098
940641AE2-051 C
50/50
16.47216.472
927146AC1-208 E
Adder
3.1564705882352942.683
934622AD1-088 E
Adder
4.1364705882352943.516
934612AD1-087 E
Adder
3.2152941176470592.733
316336AC2-165 C
Adder
9.177647058823537.801
927255AC1-221 E
Adder
2.9588235294117652.515
943461AF1-017 C
Adder
0.99294117647058820.844
932596AC2-079 E
Adder
6.8929411764705895.859
316311AC2-079 C
Adder
4.2247058823529413.591
938532AE1-072 E
Adder
6.7941176470588245.775
3146326AYDLETT TAP
Adder
1.00588235294117640.855
917122Z2-027 E
Adder
1.00.85
920692AA2-178 E
Adder
3.1141176470588232.647
316233AE1-074 C
Adder
2.17058823529411751.845
966622AG1-532 E
Adder
0.76235294117647070.648
922923AB1-081 E OP
Adder
2.9105882352941182.474
3147133PAMPLIN
Adder
0.82352941176470580.7
927264AC1-222 E
Adder
3.20470588235294152.724
966002AG1-469 E
50/50
1.0031.003
926739AC1-158 E1
50/50
51.18251.182
936666AD2-085 E
Adder
4.1329411764705883.513
941591AE2-156 C
Adder
13.14823529411764711.176
944591AF1-124 C
Adder
33.9870588235294128.889
944601AF1-125 C
Adder
33.3447058823529428.343
938771AE1-103 C
Adder
2.21764705882352951.885
3145413WATKINS
Adder
0.52941176470588240.45
960081AF2-299 C
Adder
1.52470588235294141.296
926072AC1-086 E
Adder
7.6341176470588236.489
944011AF1-069 C
50/50
12.65212.652
963041AG1-153 C
Adder
5.3588235294117644.555
936261AD2-033 C
Adder
10.782352941176479.165
962562AG1-105 E
Adder
4.842352941176474.116
961791AG1-021 C
Adder
1.48941176470588241.266
924032AB2-045 E
Adder
1.08588235294117650.923
316045AC1-158 C2
50/50
19.56819.568
3145256KINGFORK
Adder
0.72352941176470590.615
925522AC1-027 E
Adder
0.89764705882352950.763
941102AE2-104 E
Adder
3.9541176470588243.361
957872AF2-081 E
Adder
3.17411764705882372.698
933291AC2-141 C
Adder
22.2618.921
926755AC1-161 E
Adder
9.502352941176478.077
938552AE1-074 E
Adder
1.09294117647058830.929
932632AC2-084 E
Adder
2.53411764705882362.154
926214AC1-099 E
Adder
0.94705882352941180.805
924162AB2-060 E OP
Adder
3.54470588235294143.013
964242AG1-285 E
Adder
6.9188235294117655.881
938562AE1-075 E
Adder
1.00.85
964792AG1-342 E
Adder
1.92588235294117661.637
932763AC2-100 E
Adder
2.00588235294117641.705
3152251N ANNA1
50/50
106.841106.841
942342AE2-247 E
Adder
1.5164705882352941.289
919152AA1-139 E1
Adder
3.02941176470588272.575
934521AD1-076 C
Adder
9.3258823529411777.927
934511AD1-075 C
Adder
6.425.457
920042AA2-088 E OP
Adder
8.226.987
3145723EMPORIA
Adder
0.350588235294117640.298
923573AB1-173 E OP
Adder
2.6529411764705882.255
919692AA2-053 E OP
Adder
3.36117647058823542.857
925785AC1-054 E
Adder
2.79764705882352962.378
316263AC1-034 C
Adder
5.1835294117647064.406
959311AF2-222 C
Adder
13.8152941176470611.743
934576AD1-082 E
Adder
3.19882352941176462.719
943612AF1-032 E
Adder
0.68470588235294120.582
3145506HICKORY
Adder
1.61411764705882371.372
944602AF1-125 E
Adder
76.3341176470588364.884
957871AF2-081 C
Adder
7.4070588235294126.296
933292AC2-141 E
Adder
9.502352941176478.077
940492AE2-034 E
Adder
2.3364705882352941.986
934522AD1-076 E
Adder
4.7541176470588244.041
943172AE2-346 E
Adder
0.46941176470588240.399
918492AA1-063AE OP
Adder
3.22705882352941182.743
925122AB2-169 E
Adder
4.4105882352941183.749
917332KELFORD E
Adder
1.281.088
316274AC1-208 C
Adder
7.1094117647058826.043
917342Z2-044 E
Adder
0.46823529411764710.398
3151311EDGECMA
Adder
12.11411764705882510.297
937482AD2-202 E
Adder
0.94117647058823540.8
961792AG1-021 E
Adder
1.26941176470588221.079
935112AD1-144 E
Adder
0.67176470588235290.571
316349AD2-085 C
Adder
2.53294117647058852.153
944582AF1-123 E
Adder
77.5517647058823565.919
944592AF1-124 E
Adder
77.8317647058823566.157
923832AB2-022 E
Adder
0.92235294117647060.784
938772AE1-103 E
Adder
3.0611764705882352.602
916042Z1-036 E
Adder
21.48117647058823518.259
960082AF2-299 E
Adder
1.01647058823529420.864
946281AF1-292 C
Adder
1.26235294117647071.073
926071AC1-086 C
Adder
16.77411764705882314.258
963042AG1-153 E
Adder
8.0388235294117656.833
927021AC1-189 C
Adder
6.5247058823529425.546
924152AB2-059 E OP
Adder
4.122352941176473.504
964241AG1-285 C
Adder
10.3776470588235298.821
962561AG1-105 C
Adder
7.2635294117647076.174
958212AF2-115 E
Adder
1.58588235294117651.348
925022AB2-158 E
50/50
11.37311.373
316044AC1-158 C1
50/50
19.56819.568
939191AE1-149 C
Adder
7.7200000000000016.562
3143316POE
Adder
1.04235294117647070.886
901082W1-029 E
Adder
23.76705882352941420.202
926206AC1-098 E
Adder
2.86705882352941142.437
964791AG1-342 C
Adder
2.88941176470588262.456
942462AE2-259 E
Adder
5.5047058823529414.679
3151751LOISA D
50/50
3.1063.106
3151731LOISA B
50/50
3.1063.106
913392Y1-086 E
Adder
1.63411764705882371.389
939411AE1-173 C
Adder
81.8247058823529469.551
3137643SOCKMAN
Adder
0.57294117647058830.487
919710AA2-057 E
Adder
3.1117647058823532.645
933502AC2-165 E
Adder
6.9070588235294135.871
3151741LOISA C
50/50
3.1063.106
942001AE2-212 C
Adder
1.48705882352941181.264
934065AD1-033 E
Adder
3.70941176470588243.153
937226AE2-253 E
Adder
4.3282352941176473.679
934501AD1-074 C
Adder
25.6821.828
924517AB2-100 E2
Adder
2.36470588235294082.01
961671AG1-007 C
Adder
0.73058823529411760.621
957482AF2-042 E
Adder
32.6894117647058927.786
934621AD1-088 C
Adder
8.5905882352941177.302
935172AD1-152 E
Adder
4.7270588235294114.018
958502AF2-144 E
Adder
1.15294117647058810.98
946301AF1-294 C
Adder
3.06235294117647072.603
942461AE2-259 C
Adder
8.257647058823537.019
316192AB2-158 C
50/50
4.2784.278
208901BRIS G2
50/50
-2.946-2.946
316303AF2-085
50/50
4.0434.043
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4084.408
CBM South 2LTFEXP_CBM-S2->PJM
CBM
77.11777.117
CPLELTFEXP_CPLE->PJM
CLTF
9.2519.251
TVALTFEXP_TVA->PJM
CLTF
4.7224.722
O66PJM->LTFIMP_O-066
CMTX_NF
32.20632.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.05120.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.83616.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7842.784
LAGNLTFEXP_LAGN->PJM
CLTF
5.9595.959
NYPJM->LTFIMP_NY
CLTF
2.3732.373
LGEELTFEXP_LGEE->PJM
CLTF
0.8720.872
WECLTFEXP_WEC->PJM
CLTF
0.4310.431
G-007PJM->LTFIMP_G-007
CMTX_NF
5.0575.057
SIGELTFEXP_SIGE->PJM
CLTF
0.1730.173

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.71 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3758.56
MW Contribution:15.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150831SPRUNCA
Adder
7.7905882352941186.622
3150841SPRUNCB
Adder
7.7905882352941186.622
3151081ELIZAR1
80/20
2.8512.851
961941AG1-037 C
Adder
0.454117647058823570.386
941031AE2-094 C
80/20
41.10641.106
934331AD1-057 C
Adder
3.11764705882352942.65
934321AD1-056 C
Adder
5.5882352941176484.75
3151531CLOVER1
80/20
12.09912.099
3151541CLOVER2
80/20
11.98511.985
316258AE1-075 C
80/20
0.3530.353
958211AF2-115 C
Adder
2.0152941176470591.713
3151791S ANNAG2
80/20
2.372.37
3151771S ANNAG1
80/20
2.372.37
3151781S ANNAS1
80/20
1.2181.218
3151761LOISA E
80/20
4.8664.866
208900BRIS G1
80/20
-2.56-2.56
316349AD2-085 C
80/20
3.0713.071
3151091ELIZAR2
80/20
2.8012.801
946281AF1-292 C
80/20
1.4231.423
926071AC1-086 C
Adder
19.07647058823529616.215
927021AC1-189 C
Adder
7.4435294117647066.327
964241AG1-285 C
Adder
11.3035294117647079.608
962561AG1-105 C
Adder
7.9117647058823526.725
942001AE2-212 C
Adder
1.8635294117647061.584
934501AD1-074 C
Adder
30.18352941176470625.656
3151031BRUNSWICKG2
80/20
8.3898.389
961671AG1-007 C
Adder
0.82941176470588230.705
934621AD1-088 C
80/20
9.29.2
946301AF1-294 C
Adder
3.3141176470588242.817
942461AE2-259 C
Adder
8.8929411764705887.559
316192AB2-158 C
80/20
3.5593.559
208901BRIS G2
80/20
-3.03-3.03
3150601CHESTF5
Adder
45.29058823529411638.497
941591AE2-156 C
80/20
15.98415.984
3151101ELIZAR3
80/20
2.8872.887
944591AF1-124 C
80/20
41.04941.049
944601AF1-125 C
80/20
40.27340.273
938771AE1-103 C
80/20
2.6332.633
960081AF2-299 C
80/20
1.7191.719
944011AF1-069 C
80/20
13.43113.431
963041AG1-153 C
80/20
5.7035.703
3151051BRUNSWICKS1
80/20
17.42917.429
936261AD2-033 C
Adder
11.7211764705882359.963
961791AG1-021 C
Adder
1.61176470588235321.37
944641AF1-129 C
Adder
83.2882352941176570.795
316240AF1-291 C
Adder
1.78117647058823541.514
316036AC1-147 C
80/20
0.3280.328
316305AF2-043 C
80/20
0.3110.311
316321Z2-027 C
80/20
0.3250.325
934521AD1-076 C
Adder
10.9623529411764719.318
934511AD1-075 C
Adder
7.54588235294117656.414
316087AB2-174 C
80/20
1.0751.075
316263AC1-034 C
Adder
5.8505882352941184.973
937481AD2-202 C
80/20
0.3460.346
959311AF2-222 C
Adder
14.9976470588235312.748
940431AE2-027 C
Adder
10.6976470588235299.093
916191Z1-068 C
80/20
0.0390.039
941101AE2-104 C
80/20
3.0013.001
316185AD1-033 C
80/20
1.0971.097
944581AF1-123 C
80/20
40.90340.903
316294AC1-161 C
80/20
4.4154.415
316365AB2-100 C1
80/20
0.8850.885
3151021BRUNSWICKG1
80/20
8.3898.389
957481AF2-042 C
80/20
52.44752.447
3151801S ANNAS2
80/20
1.2181.218
942341AE2-247 C
80/20
1.3311.331
316246AF1-032 C
80/20
0.2540.254
316388AE2-253 GEN
80/20
1.7531.753
316320Y1-086 C
80/20
0.1960.196
966621AG1-532 C
80/20
1.2891.289
313506AB1-173 C OP
80/20
1.0281.028
935171AD1-152 C
80/20
1.2331.233
3152261N ANNA2
80/20
92.75992.759
961611AG1-000B C
Adder
13.19882352941176511.219
316072AD1-144 C
80/20
0.2460.246
316375AC2-012 C
80/20
1.2021.202
940541AE2-040 C
80/20
2.7232.723
940481AE2-033 C
80/20
15.30215.302
316181AB2-040 GEN
80/20
1.1581.158
3147043LAWRENC
80/20
0.2810.281
966001AG1-469 C
Adder
1.43764705882352951.222
3150731STONECA
Adder
5.4352941176470594.62
935161AD1-151 C
Adder
13.03882352941176511.083
316083AB2-161 C
80/20
0.4890.489
958161AF2-110 C
80/20
1.2251.225
938531AE1-072 C
80/20
15.7315.73
933981AD1-022 C
Adder
7.84941176470588256.672
316316AC1-027 C
80/20
0.2820.282
316315AB2-025 C
80/20
0.3860.386
316023AB2-100 C2
80/20
0.8850.885
3138533PONTONDP
Adder
0.59764705882352940.508
3151721LOISA A
80/20
2.3742.374
316017AA1-139 ULT1
80/20
0.9650.965
313526AB2-022 C
80/20
0.3360.336
940641AE2-051 C
80/20
17.817.8
3152431Z1-086 GT3
80/20
10.7510.75
934611AD1-087 C
80/20
1.1911.191
316336AC2-165 C
80/20
9.7879.787
944631AF1-128 C
Adder
28.33882352941176624.088
3150921YORKTN3
Adder
92.4352941176470578.57
3150851SPRUNCC
80/20
0.140.14
316018AA1-139 ULT2
80/20
0.9650.965
933291AC2-141 C
80/20
27.11427.114
3152251N ANNA1
80/20
92.7292.72
3150651CHESTF6
Adder
15.16470588235294212.89
3150861SPRUNCD
80/20
0.140.14
957871AF2-081 C
80/20
8.9458.945
316274AC1-208 C
Adder
8.077647058823536.866
3151311EDGECMA
Adder
13.67647058823529511.625
316405AF2-144 C
80/20
0.30.3
943461AF1-017 C
80/20
1.2041.204
316311AC2-079 C
80/20
5.125.12
3156056W1-029WIND
80/20
0.6930.693
316233AE1-074 C
80/20
2.4792.479
3152421Z1-086 GT2
80/20
10.7510.75
3152441Z1-086 ST
80/20
18.71718.717
3152411Z1-086 GT1
80/20
10.75310.753
939191AE1-149 C
80/20
9.4869.486
3150981CHESPKA
80/20
0.3880.388
3151041BRUNSWICKG3
80/20
8.3898.389
316313AB2-026 C
80/20
0.3850.385
964791AG1-342 C
Adder
3.14588235294117662.674
3151751LOISA D
80/20
2.3872.387
3151731LOISA B
80/20
2.3872.387
316381AD1-082 C
80/20
1.1161.116
3150991CHESPKB
80/20
0.6430.643
939411AE1-173 C
80/20
90.4790.47
3137643SOCKMAN
Adder
0.64823529411764710.551
3151741LOISA C
80/20
2.3872.387
316303AF2-085
80/20
4.3034.303
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.8954.895
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.42786.427
CPLELTFEXP_CPLE->PJM
CLTF
10.2710.27
TVALTFEXP_TVA->PJM
CLTF
5.5015.501
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.18225.182
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.8619.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.3753.375
LAGNLTFEXP_LAGN->PJM
CLTF
6.9186.918
NYPJM->LTFIMP_NY
CLTF
2.4542.454
LGEELTFEXP_LGEE->PJM
CLTF
1.0841.084
WECLTFEXP_WEC->PJM
CLTF
0.5370.537
SIGELTFEXP_SIGE->PJM
CLTF
0.2110.211

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.93 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3669.13
MW Contribution:16.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150801HOPHCF4
80/20
4.1494.149
3150831SPRUNCA
80/20
10.42510.425
3150841SPRUNCB
80/20
10.42510.425
3151081ELIZAR1
80/20
3.6013.601
961941AG1-037 C
Adder
0.53764705882352950.457
941031AE2-094 C
80/20
42.24742.247
934331AD1-057 C
Adder
3.5635294117647063.029
934321AD1-056 C
Adder
6.3870588235294125.429
966871AG1-558 C
Adder
2.56235294117647072.178
958211AF2-115 C
Adder
2.14705882352941171.825
964211AG1-282 C
Adder
2.07882352941176451.767
316169AC1-164 GEN
Adder
43.66588235294117537.116
316349AD2-085 C
Adder
3.87058823529411773.29
3151091ELIZAR2
80/20
3.5383.538
946281AF1-292 C
Adder
1.61647058823529431.374
926071AC1-086 C
Adder
21.9611764705882418.667
927021AC1-189 C
Adder
8.6023529411764727.312
964241AG1-285 C
Adder
12.1610.336
962561AG1-105 C
Adder
8.5058823529411767.23
939261AE1-157 C
Adder
14.10235294117647211.987
962861AG1-135 C
Adder
6.3647058823529425.41
943741AF1-042 C
Adder
3.06352941176470632.604
942001AE2-212 C
80/20
2.4472.447
934501AD1-074 C
Adder
36.4552941176470630.987
961671AG1-007 C
Adder
0.95176470588235310.809
934621AD1-088 C
Adder
9.6105882352941188.169
946301AF1-294 C
Adder
3.5305882352941183.001
942461AE2-259 C
Adder
9.4035294117647077.993
3150601CHESTF5
Adder
70.4105882352941159.849
941591AE2-156 C
80/20
20.20920.209
3151101ELIZAR3
80/20
3.6473.647
944591AF1-124 C
80/20
51.4651.46
944601AF1-125 C
80/20
50.48850.488
938771AE1-103 C
Adder
3.22705882352941182.743
960081AF2-299 C
Adder
1.95294117647058821.66
944011AF1-069 C
80/20
13.80413.804
963041AG1-153 C
Adder
5.8858823529411765.003
936261AD2-033 C
Adder
12.57294117647058810.687
961791AG1-021 C
Adder
1.71764705882352931.46
966881AG1-559 C
Adder
2.45176470588235332.084
3150781HOPHCF2
80/20
2.7332.733
3150761HOPPOLC
80/20
1.7191.719
944641AF1-129 C
80/20
115.84115.84
316240AF1-291 C
80/20
2.4442.444
934521AD1-076 C
Adder
13.2411.254
934511AD1-075 C
Adder
9.1141176470588237.747
316263AC1-034 C
Adder
6.6529411764705895.655
959311AF2-222 C
Adder
16.0552941176470613.647
940431AE2-027 C
80/20
14.61614.616
941101AE2-104 C
Adder
3.75764705882352963.194
944581AF1-123 C
80/20
51.27751.277
316294AC1-161 C
80/20
5.5975.597
957481AF2-042 C
Adder
54.6470588235294146.45
3150771HOPHCF1
80/20
2.7332.733
942341AE2-247 C
Adder
1.67764705882352931.426
966621AG1-532 C
Adder
1.46470588235294131.245
3152261N ANNA2
80/20
56.72156.721
934861AD1-115 C
Adder
-3.06-2.601
963611AG1-210 C
Adder
0.68235294117647060.58
961611AG1-000B C
Adder
17.92352941176470415.235
316375AC2-012 C
80/20
1.521.52
940541AE2-040 C
Adder
3.10117647058823562.636
940481AE2-033 C
Adder
17.43882352941176714.823
927041AC1-191 C
Adder
10.2870588235294128.744
3150731STONECA
80/20
7.7657.765
935161AD1-151 C
Adder
18.16235294117647215.438
3142366NRTHEST
80/20
0.2040.204
958161AF2-110 C
Adder
1.53294117647058831.303
938531AE1-072 C
Adder
19.70000000000000316.745
933981AD1-022 C
Adder
9.4470588235294128.03
961951AG1-038 C
Adder
3.3858823529411772.878
3150791HOPHCF3
80/20
2.7332.733
3138533PONTONDP
Adder
0.63647058823529420.541
316254AC1-120 C
Adder
-6.376470588235295-5.42
316257AC1-043 C
Adder
-6.121176470588236-5.203
943471AF1-018 C
Adder
7.6152941176470596.473
3152331SURRY 2
80/20
27.86527.865
940641AE2-051 C
80/20
18.8818.88
316336AC2-165 C
Adder
10.1788235294117648.652
944631AF1-128 C
Adder
44.0564705882352937.448
3150921YORKTN3
Adder
133.0105882352941113.059
3150851SPRUNCC
80/20
0.1870.187
933291AC2-141 C
80/20
34.37234.372
3152251N ANNA1
80/20
56.69756.697
936591AD2-074 C
Adder
5.8552941176470594.977
3150651CHESTF6
80/20
21.09121.091
3150861SPRUNCD
80/20
0.1870.187
957871AF2-081 C
Adder
11.2117647058823529.53
316274AC1-208 C
Adder
9.2835294117647067.891
3151311EDGECMA
Adder
15.55647058823529613.223
940551AE2-041 C
Adder
7.6152941176470596.473
943461AF1-017 C
Adder
1.51764705882352961.29
316311AC2-079 C
Adder
6.4458823529411775.479
316233AE1-074 C
80/20
2.8742.874
958261AF2-120 C
Adder
6.5505882352941175.568
3143096IRON208
80/20
0.4940.494
939191AE1-149 C
80/20
12.15312.153
964791AG1-342 C
Adder
3.38000000000000032.873
957601AF2-054 C
Adder
2.26000000000000021.921
966661AG1-536 C
Adder
5.6341176470588234.789
3150991CHESPKB
80/20
0.8130.813
939411AE1-173 C
80/20
99.71499.714
3137643SOCKMAN
Adder
0.74235294117647070.631
316303AF2-085
80/20
4.4474.447
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.4135.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69496.694
CPLELTFEXP_CPLE->PJM
CLTF
11.35211.352
TVALTFEXP_TVA->PJM
CLTF
6.4156.415
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.72830.728
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.33523.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.0414.041
LAGNLTFEXP_LAGN->PJM
CLTF
8.0268.026
NYPJM->LTFIMP_NY
CLTF
2.72.7
LGEELTFEXP_LGEE->PJM
CLTF
1.331.33
WECLTFEXP_WEC->PJM
CLTF
0.6540.654
SIGELTFEXP_SIGE->PJM
CLTF
0.2560.256

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.88 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4408.08
MW Contribution:26.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935112AD1-144 E
Adder
0.8717647058823530.741
316349AD2-085 C
Adder
3.23411764705882382.749
944582AF1-123 E
Adder
98.5858823529411883.798
944592AF1-124 E
Adder
98.9435294117647184.102
923832AB2-022 E
Adder
1.1682352941176470.993
938772AE1-103 E
Adder
3.8211764705882363.248
939192AE1-149 E
Adder
6.6670588235294125.667
939312AE1-162 E
Adder
1.29647058823529431.102
942001AE2-212 C
Adder
1.96941176470588241.674
934065AD1-033 E
Adder
4.7282352941176474.019
937226AE2-253 E
Adder
5.5047058823529414.679
934501AD1-074 C
Adder
31.6952941176470626.941
924517AB2-100 E2
Adder
2.82.38
3151031BRUNSWICKG2
50/50
8.78.7
957482AF2-042 E
Adder
36.31529411764705630.868
934621AD1-088 C
Adder
9.5599999999999998.126
935172AD1-152 E
Adder
5.2941176470588234.5
958502AF2-144 E
Adder
1.2764705882352941.085
946301AF1-294 C
Adder
3.45529411764705862.937
942461AE2-259 C
Adder
9.2705882352941187.88
316192AB2-158 C
50/50
3.5873.587
208901BRIS G2
50/50
-3.245-3.245
940431AE2-027 C
Adder
11.3411764705882369.64
942002AE2-212 E
Adder
1.31294117647058851.116
941101AE2-104 C
Adder
3.1588235294117652.685
944581AF1-123 C
Adder
43.0529411764705936.595
316141AB2-099 E
Adder
0.237647058823529430.202
316088AB2-174 E
Adder
6.242352941176475.306
923994AB2-040_E
Adder
5.8811764705882354.999
3151021BRUNSWICKG1
50/50
8.78.7
957481AF2-042 C
Adder
54.4729411764705946.302
924322AB2-079 E O1
Adder
1.25764705882352931.069
946302AF1-294 E
Adder
2.9258823529411772.487
3151801S ANNAS2
50/50
1.2331.233
961611AG1-000B C
Adder
13.98823529411764911.89
940541AE2-040 C
Adder
2.84470588235294162.418
940481AE2-033 C
Adder
15.98588235294117513.588
940482AE2-033 E
Adder
10.777647058823539.161
923263AB1-132 E OP
Adder
5.80941176470588254.938
924312AB2-078 E O1
Adder
1.25764705882352931.069
925612AC1-036 E
Adder
0.80588235294117660.685
966001AG1-469 C
Adder
1.46235294117647091.243
935161AD1-151 C
Adder
13.84941176470588311.772
932046AC2-012 E
Adder
12.31647058823529410.469
958161AF2-110 C
Adder
1.28941176470588251.096
938531AE1-072 C
Adder
16.55647058823529614.073
3145393UNCAMP
Adder
5.7482352941176484.886
933981AD1-022 C
Adder
8.247.004
900672V4-068 E
Adder
0.33764705882352940.287
924302AB2-077 E O1
Adder
1.25764705882352931.069
943462AF1-017 E
Adder
2.06941176470588231.759
942341AE2-247 C
Adder
1.40235294117647061.192
958162AF2-110 E
Adder
2.0505882352941181.743
919153AA1-139 E2
Adder
3.8505882352941183.273
934502AD1-074 E
Adder
16.13411764705882613.714
934512AD1-075 E
Adder
4.0341176470588243.429
918512AA1-065 E OP
Adder
5.2011764705882364.421
924516AB2-100 E1
Adder
2.82.38
940642AE2-051 E
50/50
12.32512.325
966621AG1-532 C
Adder
1.34705882352941191.145
924022AB2-043 E O1
Adder
4.8811764705882354.149
3147223TWITTYS
Adder
0.89294117647058820.759
959312AF2-222 E
Adder
10.4764705882352948.905
3152261N ANNA2
50/50
93.22693.226
946282AF1-292 E
Adder
0.99176470588235290.843
944012AF1-069 E
50/50
5.4085.408
3138533PONTONDP
Adder
0.62235294117647070.529
3150831SPRUNCA
Adder
8.2435294117647067.007
3150841SPRUNCB
Adder
8.2435294117647067.007
926662AC1-147 E
Adder
1.24470588235294131.058
916192Z1-068 E
Adder
1.77058823529411761.505
957492AF2-043 E
Adder
1.341.139
923852AB2-025 E
Adder
1.15058823529411770.978
939412AE1-173 E
50/50
62.82462.824
961942AG1-037 E
Adder
0.317647058823529450.27
961941AG1-037 C
Adder
0.476470588235294150.405
941031AE2-094 C
50/50
42.60742.607
941032AE2-094 E
50/50
19.08319.083
936262AD2-033 E
Adder
8.1458823529411776.924
923862AB2-026 E
Adder
1.31.105
958211AF2-115 C
Adder
2.1011764705882351.786
3151791S ANNAG2
50/50
2.42.4
3151771S ANNAG1
50/50
2.42.4
3151781S ANNAS1
50/50
1.2331.233
3151761LOISA E
50/50
4.9314.931
208900BRIS G1
50/50
-2.742-2.742
316084AB2-161 E
Adder
5.1694117647058834.394
3145946PLYMOUTH TP
Adder
0.30352941176470590.258
933982AD1-022 E
Adder
4.4858823529411773.813
940641AE2-051 C
50/50
18.48718.487
3152431Z1-086 GT3
50/50
11.14611.146
934622AD1-088 E
Adder
4.6035294117647063.913
934612AD1-087 E
Adder
3.5835294117647063.046
316336AC2-165 C
Adder
10.1788235294117648.652
935162AD1-151 E
Adder
4.4752941176470593.804
943461AF1-017 C
Adder
1.26823529411764711.078
932596AC2-079 E
Adder
8.7952941176470587.476
316311AC2-079 C
Adder
5.3905882352941184.582
938532AE1-072 E
Adder
8.6305882352941187.336
3146326AYDLETT TAP
Adder
1.27764705882352961.086
917122Z2-027 E
Adder
1.26588235294117671.076
920692AA2-178 E
Adder
3.86941176470588263.289
316233AE1-074 C
50/50
2.5912.591
966622AG1-532 E
Adder
0.89882352941176480.764
3152421Z1-086 GT2
50/50
11.14611.146
3152441Z1-086 ST
50/50
19.40819.408
3152411Z1-086 GT1
50/50
11.14911.149
3147133PAMPLIN
Adder
0.92823529411764720.789
966002AG1-469 E
Adder
0.73058823529411760.621
927226AC1-216 E
Adder
6.6694117647058825.669
936666AD2-085 E
Adder
5.2764705882352954.485
941591AE2-156 C
Adder
16.83647058823529414.311
944591AF1-124 C
Adder
43.2058823529411836.725
944601AF1-125 C
Adder
42.3894117647058836.031
938771AE1-103 C
Adder
2.7670588235294122.352
3145413WATKINS
Adder
0.65411764705882360.556
960081AF2-299 C
Adder
1.7964705882352941.527
926072AC1-086 E
Adder
9.0847058823529427.722
944011AF1-069 C
50/50
13.92113.921
963041AG1-153 C
50/50
5.9155.915
3151051BRUNSWICKS1
50/50
18.07518.075
936261AD2-033 C
Adder
12.2210.387
961791AG1-021 C
Adder
1.68117647058823551.429
3145256KINGFORK
Adder
0.93882352941176480.798
925522AC1-027 E
Adder
1.14588235294117660.974
941102AE2-104 E
Adder
5.0223529411764714.269
957872AF2-081 E
Adder
4.0352941176470593.43
933291AC2-141 C
Adder
28.56588235294117724.281
926755AC1-161 E
Adder
12.19411764705882510.365
938552AE1-074 E
50/50
1.3051.305
924162AB2-060 E OP
Adder
4.0294117647058823.425
964242AG1-285 E
Adder
7.8564705882352946.678
938562AE1-075 E
Adder
1.1082352941176470.942
3152251N ANNA1
50/50
93.18793.187
924814AB2-134 E
Adder
10.9235294117647069.285
944641AF1-129 C
Adder
88.4505882352941375.183
316240AF1-291 C
Adder
1.88941176470588261.606
942342AE2-247 E
Adder
1.93529411764705881.645
919152AA1-139 E1
Adder
3.8505882352941183.273
934521AD1-076 C
Adder
11.5105882352941199.784
934511AD1-075 C
Adder
7.9235294117647066.735
920042AA2-088 E OP
Adder
10.0447058823529418.538
3145723EMPORIA
Adder
0.414117647058823530.352
923573AB1-173 E OP
Adder
3.1364705882352942.666
919692AA2-053 E OP
Adder
4.00705882352941253.406
925785AC1-054 E
Adder
3.24941176470588242.762
959311AF2-222 C
Adder
15.63529411764705813.29
3150651CHESTF6
Adder
16.10470588235294213.689
946262AF1-291 E
Adder
1.261.071
934576AD1-082 E
Adder
4.1188235294117653.501
943612AF1-032 E
Adder
0.87058823529411770.74
3145506HICKORY
Adder
2.05411764705882361.746
944602AF1-125 E
Adder
97.0388235294117782.483
957871AF2-081 C
Adder
9.4164705882352948.004
933292AC2-141 E
Adder
12.19411764705882510.365
940492AE2-034 E
Adder
2.90235294117647062.467
934522AD1-076 E
Adder
5.8670588235294124.987
943172AE2-346 E
Adder
0.5717647058823530.486
918492AA1-063AE OP
Adder
3.87294117647058833.292
917332KELFORD E
Adder
1.54588235294117651.314
937482AD2-202 E
Adder
1.04941176470588250.892
961792AG1-021 E
Adder
1.4317647058823531.217
916042Z1-036 E
Adder
26.91882352941176422.881
960082AF2-299 E
Adder
1.19764705882352951.018
946281AF1-292 C
Adder
1.48705882352941181.264
926071AC1-086 C
Adder
19.96117647058823516.967
963042AG1-153 E
50/50
8.8728.872
964241AG1-285 C
Adder
11.78352941176470610.016
958212AF2-115 E
Adder
1.78941176470588231.521
925022AB2-158 E
50/50
9.5359.535
939191AE1-149 C
Adder
10.0011764705882348.501
3143316POE
Adder
1.30941176470588231.113
901082W1-029 E
Adder
30.02588235294117425.522
3151041BRUNSWICKG3
50/50
8.78.7
942462AE2-259 E
Adder
6.1800000000000015.253
3151731LOISA B
50/50
2.4192.419
940432AE2-027 E
Adder
7.5611764705882356.427
934012AD1-025 E
Adder
8.6341176470588247.339
913392Y1-086 E
Adder
2.0705882352941181.76
939411AE1-173 C
50/50
94.23794.237
3137643SOCKMAN
Adder
0.67882352941176470.577
933502AC2-165 E
Adder
7.6611764705882356.512
3151741LOISA C
50/50
2.4192.419
316303AF2-085
50/50
4.464.46
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.1255.125
CBM South 2LTFEXP_CBM-S2->PJM
CBM
90.8190.81
CPLELTFEXP_CPLE->PJM
CLTF
10.7510.75
TVALTFEXP_TVA->PJM
CLTF
5.8785.878
O66PJM->LTFIMP_O-066
CMTX_NF
35.46935.469
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.02528.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.37921.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.6863.686
LAGNLTFEXP_LAGN->PJM
CLTF
7.3867.386
NYPJM->LTFIMP_NY
CLTF
2.6122.612
LGEELTFEXP_LGEE->PJM
CLTF
1.1951.195
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5685.568
SIGELTFEXP_SIGE->PJM
CLTF
0.2320.232

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.7 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4342.98
MW Contribution:25.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
941031AE2-094 C
80/20
119.094119.094
3151531CLOVER1
80/20
32.84832.848
3151541CLOVER2
80/20
32.5432.54
958211AF2-115 C
80/20
3.33.3
24684605SMG4
80/20
3.2353.235
964211AG1-282 C
Adder
-1.7882352941176471-1.52
964241AG1-285 C
80/20
19.39519.395
316034AC1-036 C
80/20
0.3540.354
962561AG1-105 C
80/20
15.92115.921
316118AC1-105 C
80/20
1.7691.769
3144293JTRSVLE
80/20
0.6050.605
316217AC1-145 C
80/20
0.4120.412
942671AE2-283 C
80/20
3.7323.732
943811AF1-049 C
80/20
9.4269.426
938741AE1-100 C
80/20
0.7290.729
941671AE2-166 C
80/20
5.7085.708
942001AE2-212 C
Adder
-2.1176470588235294-1.8
3151031BRUNSWICKG2
80/20
25.36925.369
316359AB2-059 C OP
80/20
1.1351.135
934621AD1-088 C
80/20
24.38424.384
946301AF1-294 C
80/20
5.4265.426
942461AE2-259 C
80/20
14.02314.023
316283AC2-100 C
80/20
2.3262.326
316197AC1-042 C
80/20
0.3460.346
944641AF1-129 C
Adder
-95.19529411764705-80.916
316240AF1-291 C
Adder
-2.031764705882353-1.727
316263AC1-034 C
80/20
4.5164.516
937481AD2-202 C
80/20
0.9380.938
3151591KERR 2
80/20
1.8191.819
959311AF2-222 C
80/20
25.13225.132
316205AC1-080 C
80/20
0.5050.505
316123AC1-075 C
80/20
1.5121.512
942751AE2-291 C
80/20
13.51213.512
3151561HALLBR1
80/20
1.2391.239
24684305SMG1
80/20
1.1751.175
3151021BRUNSWICKG1
80/20
25.36925.369
957481AF2-042 C
80/20
148.174148.174
316003AC1-222 C
80/20
1.9581.958
24684405SMG2
80/20
3.2353.235
3151601KERR 3
80/20
1.8191.819
3151581KERR 1
80/20
0.650.65
935171AD1-152 C
80/20
3.2243.224
936161AD2-022 C
80/20
12.80112.801
270197AC1-083 C
80/20
0.9970.997
24728405LEESVG
80/20
0.9740.974
938531AE1-072 C
Adder
-16.896470588235296-14.362
316049AB1-081 C OP
80/20
0.9630.963
316238AB2-078 C O1
80/20
0.5160.516
316322AB2-045 C
80/20
0.2670.267
944011AF1-069 C
80/20
38.91238.912
963041AG1-153 C
80/20
17.24617.246
3151051BRUNSWICKS1
80/20
52.70552.705
936261AD2-033 C
80/20
19.83719.837
961791AG1-021 C
80/20
2.642.64
316248AF1-058 C
80/20
0.6420.642
936171AD2-023 C
80/20
7.4677.467
941801AE2-185 C
80/20
4.7984.798
940641AE2-051 C
Adder
-22.240000000000002-18.904
3152431Z1-086 GT3
80/20
32.07932.079
934611AD1-087 C
80/20
3.2323.232
3151611KERR 4
80/20
1.8191.819
3151621KERR 5
80/20
1.8191.819
316237AB2-079 C O1
80/20
0.5160.516
316222AC1-221 C
80/20
2.9052.905
933291AC2-141 C
Adder
-33.98823529411765-28.89
3151641KERR 7
80/20
1.8191.819
313527AB2-043 C
80/20
0.8060.806
3151311EDGECMA
80/20
10.35810.358
3152661PLYWOOD A
80/20
2.3542.354
316129AC1-054 C
80/20
1.1861.186
3151631KERR 6
80/20
1.8191.819
316131AB2-060 C
80/20
2.3152.315
3138533PONTONDP
80/20
0.9780.978
24684505SMG3
80/20
1.9881.988
24684705SMG5
80/20
1.2291.229
941431AE2-140 C
80/20
14.14314.143
3152421Z1-086 GT2
80/20
32.07932.079
3152441Z1-086 ST
80/20
55.85555.855
3152411Z1-086 GT1
80/20
32.08832.088
3151041BRUNSWICKG3
80/20
25.36925.369
316239AB2-077 C O1
80/20
0.5160.516
964791AG1-342 C
80/20
6.5026.502
940081AE1-250 C
80/20
13.65313.653
957601AF2-054 C
Adder
-1.8941176470588237-1.61
940601AE2-047 C
80/20
4.254.25
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.6199.619
CBM South 2LTFEXP_CBM-S2->PJM
CBM
177.277177.277
CPLELTFEXP_CPLE->PJM
CLTF
20.16220.162
TVALTFEXP_TVA->PJM
CLTF
12.22612.226
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.77474.774
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.81246.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.7578.757
LAGNLTFEXP_LAGN->PJM
CLTF
15.4915.49
NYPJM->LTFIMP_NY
CLTF
2.1882.188
LGEELTFEXP_LGEE->PJM
CLTF
2.8852.885
WECLTFEXP_WEC->PJM
CLTF
1.5251.525
SIGELTFEXP_SIGE->PJM
CLTF
0.550.55

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.59 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4175.62
MW Contribution:25.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151531CLOVER1
80/20
32.84832.848
3151541CLOVER2
80/20
32.5432.54
958211AF2-115 C
80/20
3.33.3
24684605SMG4
80/20
3.2353.235
964211AG1-282 C
Adder
-1.7882352941176471-1.52
942001AE2-212 C
Adder
-2.1176470588235294-1.8
3151031BRUNSWICKG2
80/20
25.36925.369
316359AB2-059 C OP
80/20
1.1351.135
934621AD1-088 C
80/20
24.38424.384
946301AF1-294 C
80/20
5.4265.426
942461AE2-259 C
80/20
14.02314.023
316283AC2-100 C
80/20
2.3262.326
316197AC1-042 C
80/20
0.3460.346
964241AG1-285 C
80/20
19.39519.395
316034AC1-036 C
80/20
0.3540.354
962561AG1-105 C
80/20
15.92115.921
316118AC1-105 C
80/20
1.7691.769
3144293JTRSVLE
80/20
0.6050.605
316217AC1-145 C
80/20
0.4120.412
942671AE2-283 C
80/20
3.7323.732
943811AF1-049 C
80/20
9.4269.426
938741AE1-100 C
80/20
0.7290.729
941671AE2-166 C
80/20
5.7085.708
3151021BRUNSWICKG1
80/20
25.36925.369
957481AF2-042 C
80/20
148.174148.174
316003AC1-222 C
80/20
1.9581.958
24684405SMG2
80/20
3.2353.235
3151601KERR 3
80/20
1.8191.819
3151581KERR 1
80/20
0.650.65
935171AD1-152 C
80/20
3.2243.224
936161AD2-022 C
80/20
12.80112.801
270197AC1-083 C
80/20
0.9970.997
24728405LEESVG
80/20
0.9740.974
938531AE1-072 C
Adder
-16.896470588235296-14.362
316049AB1-081 C OP
80/20
0.9630.963
316238AB2-078 C O1
80/20
0.5160.516
316322AB2-045 C
80/20
0.2670.267
963041AG1-153 C
80/20
17.24617.246
3151051BRUNSWICKS1
80/20
52.70552.705
936261AD2-033 C
80/20
19.83719.837
961791AG1-021 C
80/20
2.642.64
316248AF1-058 C
80/20
0.6420.642
936171AD2-023 C
80/20
7.4677.467
941801AE2-185 C
80/20
4.7984.798
944641AF1-129 C
Adder
-95.19529411764705-80.916
316240AF1-291 C
Adder
-2.031764705882353-1.727
316263AC1-034 C
80/20
4.5164.516
937481AD2-202 C
80/20
0.9380.938
3151591KERR 2
80/20
1.8191.819
959311AF2-222 C
80/20
25.13225.132
316205AC1-080 C
80/20
0.5050.505
316123AC1-075 C
80/20
1.5121.512
942751AE2-291 C
80/20
13.51213.512
3151561HALLBR1
80/20
1.2391.239
24684305SMG1
80/20
1.1751.175
933291AC2-141 C
Adder
-33.98823529411765-28.89
3151641KERR 7
80/20
1.8191.819
313527AB2-043 C
80/20
0.8060.806
3151311EDGECMA
80/20
10.35810.358
3152661PLYWOOD A
80/20
2.3542.354
316129AC1-054 C
80/20
1.1861.186
3151631KERR 6
80/20
1.8191.819
316131AB2-060 C
80/20
2.3152.315
3138533PONTONDP
80/20
0.9780.978
24684505SMG3
80/20
1.9881.988
24684705SMG5
80/20
1.2291.229
941431AE2-140 C
80/20
14.14314.143
940641AE2-051 C
Adder
-22.240000000000002-18.904
3152431Z1-086 GT3
80/20
32.07932.079
934611AD1-087 C
80/20
3.2323.232
3151611KERR 4
80/20
1.8191.819
3151621KERR 5
80/20
1.8191.819
316237AB2-079 C O1
80/20
0.5160.516
316222AC1-221 C
80/20
2.9052.905
3152421Z1-086 GT2
80/20
32.07932.079
3152441Z1-086 ST
80/20
55.85555.855
3152411Z1-086 GT1
80/20
32.08832.088
3151041BRUNSWICKG3
80/20
25.36925.369
316239AB2-077 C O1
80/20
0.5160.516
964791AG1-342 C
80/20
6.5026.502
940081AE1-250 C
80/20
13.65313.653
957601AF2-054 C
Adder
-1.8941176470588237-1.61
940601AE2-047 C
80/20
4.254.25
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.6199.619
CBM South 2LTFEXP_CBM-S2->PJM
CBM
177.277177.277
CPLELTFEXP_CPLE->PJM
CLTF
20.16220.162
TVALTFEXP_TVA->PJM
CLTF
12.22612.226
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.77474.774
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.81246.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.7578.757
LAGNLTFEXP_LAGN->PJM
CLTF
15.4915.49
NYPJM->LTFIMP_NY
CLTF
2.1882.188
LGEELTFEXP_LGEE->PJM
CLTF
2.8852.885
WECLTFEXP_WEC->PJM
CLTF
1.5251.525
SIGELTFEXP_SIGE->PJM
CLTF
0.550.55

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.93 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3894.33
MW Contribution:14.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150831SPRUNCA
Adder
7.6235294117647066.48
3150841SPRUNCB
Adder
7.6235294117647066.48
3151081ELIZAR1
80/20
2.7822.782
961941AG1-037 C
Adder
0.44235294117647060.376
941031AE2-094 C
80/20
39.89839.898
934331AD1-057 C
Adder
3.0305882352941182.576
934321AD1-056 C
Adder
5.4329411764705894.618
3151531CLOVER1
80/20
11.76811.768
3151541CLOVER2
80/20
11.65811.658
316258AE1-075 C
80/20
0.3460.346
958211AF2-115 C
Adder
1.97411764705882351.678
3151791S ANNAG2
80/20
2.6512.651
3151771S ANNAG1
80/20
2.6512.651
3151781S ANNAS1
80/20
1.3621.362
3151761LOISA E
80/20
5.5225.522
208900BRIS G1
80/20
-2.628-2.628
316349AD2-085 C
80/20
2.9972.997
3151091ELIZAR2
80/20
2.7332.733
946281AF1-292 C
80/20
1.3851.385
926071AC1-086 C
Adder
18.5623529411764715.778
927021AC1-189 C
Adder
7.2364705882352946.151
964241AG1-285 C
Adder
11.0294117647058829.375
962561AG1-105 C
Adder
7.70470588235294156.549
316044AC1-158 C1
80/20
19.41819.418
942001AE2-212 C
Adder
1.82117647058823541.548
934501AD1-074 C
Adder
29.40470588235294324.994
3151031BRUNSWICKG2
80/20
8.1438.143
961671AG1-007 C
Adder
0.80588235294117660.685
934621AD1-088 C
80/20
8.9588.958
946301AF1-294 C
Adder
3.2458823529411762.759
942461AE2-259 C
Adder
8.7329411764705887.423
316192AB2-158 C
80/20
3.6253.625
208901BRIS G2
80/20
-3.11-3.11
941591AE2-156 C
80/20
15.615.6
3151101ELIZAR3
80/20
2.8172.817
944591AF1-124 C
80/20
40.05140.051
944601AF1-125 C
80/20
39.29539.295
938771AE1-103 C
80/20
2.5672.567
960081AF2-299 C
80/20
1.6731.673
944011AF1-069 C
80/20
13.03613.036
963041AG1-153 C
80/20
5.5365.536
3151051BRUNSWICKS1
80/20
16.91816.918
936261AD2-033 C
Adder
11.4505882352941189.733
961791AG1-021 C
Adder
1.57882352941176471.342
316045AC1-158 C2
80/20
19.41819.418
316170AC1-121 C
80/20
2.7242.724
944641AF1-129 C
Adder
81.5517647058823669.319
316240AF1-291 C
Adder
1.7435294117647061.482
316036AC1-147 C
80/20
0.320.32
316305AF2-043 C
80/20
0.3030.303
316321Z2-027 C
80/20
0.3170.317
934521AD1-076 C
Adder
10.6788235294117659.077
934511AD1-075 C
Adder
7.3517647058823536.249
316087AB2-174 C
80/20
1.0461.046
316263AC1-034 C
Adder
5.6858823529411774.833
937481AD2-202 C
80/20
0.3360.336
959311AF2-222 C
Adder
14.6623529411764712.463
940431AE2-027 C
Adder
10.4682352941176488.898
916191Z1-068 C
80/20
0.0380.038
941101AE2-104 C
80/20
2.9282.928
316185AD1-033 C
80/20
1.071.07
944581AF1-123 C
80/20
39.90939.909
316294AC1-161 C
80/20
4.314.31
316365AB2-100 C1
80/20
0.8620.862
3151021BRUNSWICKG1
80/20
8.1438.143
957481AF2-042 C
80/20
51.00351.003
3151801S ANNAS2
80/20
1.3621.362
942341AE2-247 C
80/20
1.2991.299
316246AF1-032 C
80/20
0.2480.248
316388AE2-253 GEN
80/20
1.711.71
316320Y1-086 C
80/20
0.1920.192
966621AG1-532 C
80/20
1.2551.255
935171AD1-152 C
80/20
1.1991.199
3152261N ANNA2
80/20
89.07389.073
934861AD1-115 C
Adder
2.8482352941176472.421
961611AG1-000B C
Adder
12.91058823529411910.974
316375AC2-012 C
80/20
1.1731.173
940541AE2-040 C
80/20
2.652.65
940481AE2-033 C
80/20
14.89114.891
3147043LAWRENC
80/20
0.2730.273
966001AG1-469 C
80/20
1.9591.959
3150731STONECA
Adder
5.3258823529411774.527
935161AD1-151 C
Adder
12.7647058823529410.85
316083AB2-161 C
80/20
0.4780.478
958161AF2-110 C
80/20
1.1951.195
938531AE1-072 C
80/20
15.34615.346
933981AD1-022 C
Adder
7.6458823529411766.499
316316AC1-027 C
80/20
0.2750.275
316315AB2-025 C
80/20
0.3750.375
316023AB2-100 C2
80/20
0.8620.862
3138533PONTONDP
Adder
0.58470588235294120.497
3151721LOISA A
80/20
2.6942.694
316254AC1-120 C
80/20
7.9327.932
316257AC1-043 C
Adder
5.697647058823534.843
316017AA1-139 ULT1
80/20
0.9420.942
313526AB2-022 C
80/20
0.3280.328
940641AE2-051 C
80/20
17.2917.29
3152431Z1-086 GT3
80/20
10.43410.434
934611AD1-087 C
80/20
1.1591.159
316336AC2-165 C
80/20
9.6099.609
3150921YORKTN3
Adder
90.5694117647058876.984
3150851SPRUNCC
80/20
0.1370.137
316018AA1-139 ULT2
80/20
0.9420.942
933291AC2-141 C
80/20
26.46526.465
3152251N ANNA1
80/20
89.03589.035
3150651CHESTF6
Adder
14.84823529411764812.621
3150861SPRUNCD
80/20
0.1370.137
957871AF2-081 C
80/20
8.7288.728
316274AC1-208 C
Adder
7.857647058823536.679
3151311EDGECMA
Adder
13.28823529411764811.295
316405AF2-144 C
80/20
0.2940.294
943461AF1-017 C
80/20
1.1751.175
316311AC2-079 C
80/20
4.9964.996
3156056W1-029WIND
80/20
0.6760.676
316233AE1-074 C
80/20
2.4172.417
3152421Z1-086 GT2
80/20
10.43410.434
3152441Z1-086 ST
80/20
18.16818.168
3152411Z1-086 GT1
80/20
10.43710.437
939191AE1-149 C
80/20
9.2629.262
3150981CHESPKA
80/20
0.3780.378
3151041BRUNSWICKG3
80/20
8.1438.143
316313AB2-026 C
80/20
0.3770.377
964791AG1-342 C
Adder
3.06352941176470632.604
3151751LOISA D
80/20
2.7082.708
3151731LOISA B
80/20
2.7082.708
316164AC1-076_C
80/20
1.1141.114
316381AD1-082 C
80/20
1.0891.089
3150991CHESPKB
80/20
0.6270.627
939411AE1-173 C
80/20
87.96287.962
3137643SOCKMAN
Adder
0.6317647058823530.537
3151741LOISA C
80/20
2.7082.708
316303AF2-085
80/20
4.1844.184
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.744.74
CBM South 2LTFEXP_CBM-S2->PJM
CBM
83.40383.403
CPLELTFEXP_CPLE->PJM
CLTF
9.9459.945
TVALTFEXP_TVA->PJM
CLTF
5.1955.195
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.96121.961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.49718.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.0623.062
LAGNLTFEXP_LAGN->PJM
CLTF
6.5316.531
NYPJM->LTFIMP_NY
CLTF
2.5322.532
LGEELTFEXP_LGEE->PJM
CLTF
0.9710.971
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
SIGELTFEXP_SIGE->PJM
CLTF
0.1910.191

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.78 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3857.57
MW Contribution:15.85
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150801HOPHCF4
80/20
4.0644.064
3150831SPRUNCA
80/20
10.21910.219
3150841SPRUNCB
80/20
10.21910.219
3151081ELIZAR1
80/20
3.5273.527
961941AG1-037 C
Adder
0.52705882352941180.448
941031AE2-094 C
80/20
41.37341.373
934331AD1-057 C
Adder
3.4882352941176472.965
934321AD1-056 C
Adder
6.2529411764705895.315
966871AG1-558 C
Adder
2.50941176470588222.133
958211AF2-115 C
Adder
2.12470588235294141.806
964211AG1-282 C
Adder
2.0317647058823531.727
316169AC1-164 GEN
Adder
42.77176470588235436.356
316349AD2-085 C
Adder
3.79058823529411763.222
3151091ELIZAR2
80/20
3.4653.465
946281AF1-292 C
Adder
1.58470588235294121.347
926071AC1-086 C
Adder
21.50823529411764718.282
927021AC1-189 C
Adder
8.4188235294117647.156
964241AG1-285 C
Adder
11.97764705882352810.181
962561AG1-105 C
Adder
8.3588235294117657.105
316044AC1-158 C1
80/20
14.96214.962
939261AE1-157 C
Adder
13.77647058823529511.71
962861AG1-135 C
Adder
6.222352941176475.289
943741AF1-042 C
Adder
2.9964705882352942.547
942001AE2-212 C
80/20
2.3972.397
934501AD1-074 C
Adder
35.6976470588235330.343
961671AG1-007 C
Adder
0.9317647058823530.792
934621AD1-088 C
Adder
9.4482352941176488.031
946301AF1-294 C
Adder
3.4941176470588242.97
942461AE2-259 C
Adder
9.347.939
316192AB2-158 C
80/20
2.1182.118
3150601CHESTF5
Adder
68.9811764705882458.634
941591AE2-156 C
80/20
19.79319.793
3151101ELIZAR3
80/20
3.5723.572
944591AF1-124 C
80/20
50.39950.399
944601AF1-125 C
80/20
49.44749.447
938771AE1-103 C
Adder
3.162.686
960081AF2-299 C
Adder
1.91411764705882351.627
944011AF1-069 C
80/20
13.51813.518
963041AG1-153 C
Adder
5.7647058823529424.9
936261AD2-033 C
Adder
12.4023529411764710.542
961791AG1-021 C
Adder
1.70000000000000021.445
316045AC1-158 C2
80/20
14.96214.962
966881AG1-559 C
Adder
2.3964705882352942.037
3150781HOPHCF2
80/20
2.6772.677
3150761HOPPOLC
80/20
1.6841.684
944641AF1-129 C
80/20
113.49113.49
316240AF1-291 C
80/20
2.3942.394
934521AD1-076 C
Adder
12.96470588235294111.02
934511AD1-075 C
Adder
8.9247058823529427.586
316263AC1-034 C
Adder
6.5105882352941185.534
959311AF2-222 C
Adder
15.85294117647058913.475
940431AE2-027 C
80/20
14.31814.318
941101AE2-104 C
Adder
3.683.128
944581AF1-123 C
80/20
50.22150.221
316294AC1-161 C
80/20
5.4825.482
957481AF2-042 C
Adder
53.64117647058823545.595
3150771HOPHCF1
80/20
2.6772.677
942341AE2-247 C
Adder
1.64235294117647061.396
966621AG1-532 C
Adder
1.43529411764705881.22
3152261N ANNA2
80/20
55.34655.346
963611AG1-210 C
Adder
0.66705882352941170.567
961611AG1-000B C
Adder
17.55647058823529614.923
316375AC2-012 C
80/20
1.4881.488
940541AE2-040 C
Adder
3.03764705882352942.582
940481AE2-033 C
Adder
17.08117647058823614.519
927041AC1-191 C
Adder
10.0729411764705888.562
3150731STONECA
80/20
7.6067.606
935161AD1-151 C
Adder
17.79176470588235415.123
3142366NRTHEST
80/20
0.20.2
958161AF2-110 C
Adder
1.50117647058823531.276
938531AE1-072 C
Adder
19.2929411764705916.399
933981AD1-022 C
Adder
9.2505882352941197.863
961951AG1-038 C
Adder
3.3117647058823532.815
3150791HOPHCF3
80/20
2.6772.677
3138533PONTONDP
Adder
0.62941176470588240.535
943471AF1-018 C
Adder
7.4541176470588246.336
3152331SURRY 2
80/20
27.29427.294
940641AE2-051 C
80/20
18.48818.488
316336AC2-165 C
Adder
10.1094117647058828.593
944631AF1-128 C
Adder
43.1623529411764736.688
3150921YORKTN3
Adder
130.26705882352942110.727
3150851SPRUNCC
80/20
0.1830.183
933291AC2-141 C
80/20
33.66433.664
3152251N ANNA1
80/20
55.32355.323
936591AD2-074 C
Adder
5.7258823529411764.867
3150651CHESTF6
80/20
20.66420.664
3150861SPRUNCD
80/20
0.1830.183
957871AF2-081 C
Adder
10.989.333
316274AC1-208 C
Adder
9.0917647058823537.728
3151311EDGECMA
Adder
15.22352941176470512.94
940551AE2-041 C
Adder
7.4541176470588246.336
943461AF1-017 C
Adder
1.48588235294117641.263
316311AC2-079 C
Adder
6.3129411764705885.366
316233AE1-074 C
80/20
2.8192.819
958261AF2-120 C
Adder
6.4035294117647065.443
3143096IRON208
80/20
0.4840.484
939191AE1-149 C
80/20
11.90511.905
964791AG1-342 C
Adder
3.32117647058823542.823
957601AF2-054 C
Adder
2.2117647058823531.88
316164AC1-076_C
80/20
0.9930.993
966661AG1-536 C
Adder
5.5082352941176484.682
3150991CHESPKB
80/20
0.7960.796
939411AE1-173 C
80/20
97.64897.648
3137643SOCKMAN
Adder
0.72705882352941180.618
316303AF2-085
80/20
4.3634.363
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.2865.286
CBM South 2LTFEXP_CBM-S2->PJM
CBM
94.17394.173
CPLELTFEXP_CPLE->PJM
CLTF
11.08811.088
TVALTFEXP_TVA->PJM
CLTF
6.1396.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.65727.657
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.08222.082
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.7473.747
LAGNLTFEXP_LAGN->PJM
CLTF
7.6777.677
NYPJM->LTFIMP_NY
CLTF
2.8062.806
LGEELTFEXP_LGEE->PJM
CLTF
1.2221.222
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
SIGELTFEXP_SIGE->PJM
CLTF
0.2370.237

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.54 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4631.24
MW Contribution:25.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150831SPRUNCA
Adder
8.1435294117647056.922
3150841SPRUNCB
Adder
8.1435294117647056.922
926662AC1-147 E
Adder
1.22588235294117661.042
916192Z1-068 E
Adder
1.74235294117647071.481
957492AF2-043 E
Adder
1.31882352941176471.121
923852AB2-025 E
Adder
1.1282352941176470.959
939192AE1-149 E
Adder
6.5694117647058825.584
939312AE1-162 E
Adder
1.27764705882352961.086
935112AD1-144 E
Adder
0.85764705882352940.729
316349AD2-085 C
Adder
3.1835294117647062.706
944582AF1-123 E
Adder
97.0317647058823782.477
944592AF1-124 E
Adder
97.3823529411764882.775
923832AB2-022 E
Adder
1.14941176470588240.977
938772AE1-103 E
Adder
3.75764705882352963.194
916042Z1-036 E
Adder
26.4694117647058822.499
960082AF2-299 E
Adder
1.17529411764705880.999
946281AF1-292 C
Adder
1.45882352941176461.24
926071AC1-086 C
Adder
19.57647058823529616.64
963042AG1-153 E
Adder
8.6682352941176477.368
964241AG1-285 C
Adder
11.5811764705882349.844
962561AG1-105 C
Adder
8.0894117647058836.876
958212AF2-115 E
Adder
1.76470588235294111.5
925022AB2-158 E
50/50
9.7219.721
316044AC1-158 C1
50/50
19.48619.486
942001AE2-212 C
Adder
1.94235294117647061.651
934065AD1-033 E
Adder
4.6541176470588243.956
937226AE2-253 E
Adder
5.4188235294117654.606
934501AD1-074 C
Adder
31.13882352941176626.468
924517AB2-100 E2
Adder
2.74588235294117672.334
957482AF2-042 E
Adder
35.55176470588235630.219
934621AD1-088 C
Adder
9.3717647058823547.966
935172AD1-152 E
Adder
5.1847058823529414.407
958502AF2-144 E
Adder
1.2588235294117651.07
946301AF1-294 C
Adder
3.4070588235294122.896
942461AE2-259 C
Adder
9.1658823529411777.791
316192AB2-158 C
50/50
3.6573.657
208901BRIS G2
50/50
-3.356-3.356
940431AE2-027 C
Adder
11.2058823529411789.525
942002AE2-212 E
Adder
1.2952941176470591.101
941101AE2-104 C
Adder
3.10941176470588232.643
944581AF1-123 C
Adder
42.37411764705882436.018
316141AB2-099 E
Adder
0.234117647058823540.199
316088AB2-174 E
Adder
6.1235294117647065.205
923994AB2-040_E
Adder
5.76941176470588254.904
957481AF2-042 C
Adder
53.3270588235294245.328
924322AB2-079 E O1
Adder
1.23529411764705891.05
946302AF1-294 E
Adder
2.88470588235294122.452
3151801S ANNAS2
50/50
1.381.38
961611AG1-000B C
Adder
13.8152941176470611.743
940541AE2-040 C
Adder
2.78823529411764742.37
940481AE2-033 C
Adder
15.6752941176470613.324
940482AE2-033 E
Adder
10.5670588235294118.982
923263AB1-132 E OP
Adder
5.697647058823534.843
924312AB2-078 E O1
Adder
1.23529411764705891.05
925612AC1-036 E
Adder
0.79294117647058830.674
966001AG1-469 C
50/50
1.9871.987
926740AC1-158 E2
50/50
50.96750.967
925672AC1-043 E
Adder
9.4635294117647078.044
3150731STONECA
Adder
0.92705882352941180.788
935161AD1-151 C
Adder
13.69411764705882511.64
932046AC2-012 E
Adder
12.12705882352941210.308
958161AF2-110 C
Adder
1.26823529411764711.078
938531AE1-072 C
Adder
16.29411764705882213.85
3145393UNCAMP
Adder
5.65176470588235354.804
933981AD1-022 C
Adder
8.0941176470588236.88
900672V4-068 E
Adder
0.33058823529411770.281
924302AB2-077 E O1
Adder
1.23529411764705891.05
926486AC1-120 E
50/50
4.1534.153
925332AB2-190 E
Adder
6.8164705882352945.794
927226AC1-216 E
Adder
6.5917647058823535.603
936666AD2-085 E
Adder
5.195294117647064.416
941591AE2-156 C
Adder
16.57647058823529614.09
944591AF1-124 C
Adder
42.5247058823529436.146
944601AF1-125 C
Adder
41.7211764705882435.463
938771AE1-103 C
Adder
2.72117647058823582.313
3145413WATKINS
Adder
0.64235294117647070.546
924814AB2-134 E
Adder
10.7988235294117659.179
944641AF1-129 C
Adder
87.4717647058823574.351
316240AF1-291 C
Adder
1.86705882352941191.587
942342AE2-247 E
Adder
1.90588235294117661.62
919152AA1-139 E1
Adder
3.78941176470588253.221
934521AD1-076 C
Adder
11.3094117647058829.613
934511AD1-075 C
Adder
7.7847058823529426.617
920042AA2-088 E OP
Adder
9.8670588235294128.387
3145723EMPORIA
Adder
0.405882352941176470.345
923573AB1-173 E OP
Adder
3.07647058823529432.615
919692AA2-053 E OP
Adder
3.93176470588235333.342
925785AC1-054 E
Adder
3.18705882352941172.709
959311AF2-222 C
Adder
15.39294117647058813.084
943462AF1-017 E
Adder
2.03764705882352941.732
942341AE2-247 C
Adder
1.38000000000000011.173
958162AF2-110 E
Adder
2.01764705882352931.715
919153AA1-139 E2
Adder
3.78941176470588253.221
934502AD1-074 E
Adder
15.85176470588235313.474
934512AD1-075 E
Adder
3.96235294117647063.368
918512AA1-065 E OP
Adder
5.1070588235294124.341
924516AB2-100 E1
Adder
2.74588235294117672.334
940642AE2-051 E
50/50
12.05212.052
966621AG1-532 C
Adder
1.32117647058823541.123
924022AB2-043 E O1
Adder
4.7941176470588244.075
3147223TWITTYS
Adder
0.87882352941176480.747
959312AF2-222 E
Adder
10.3129411764705888.766
3152261N ANNA2
50/50
89.60889.608
934861AD1-115 C
Adder
2.92.465
946282AF1-292 E
Adder
0.97294117647058820.827
944012AF1-069 E
50/50
5.2835.283
3138533PONTONDP
Adder
0.61411764705882350.522
3151721LOISA A
50/50
2.7312.731
316254AC1-120 C
50/50
8.0618.061
316257AC1-043 C
Adder
5.84.93
939412AE1-173 E
Adder
61.5211764705882452.293
961942AG1-037 E
Adder
0.311764705882352940.265
961941AG1-037 C
Adder
0.46705882352941180.397
941031AE2-094 C
50/50
41.61841.618
941032AE2-094 E
50/50
18.6418.64
936262AD2-033 E
Adder
8.0141176470588256.812
923862AB2-026 E
Adder
1.28117647058823541.089
958211AF2-115 C
Adder
2.0717647058823531.761
3151791S ANNAG2
50/50
2.6852.685
3151771S ANNAG1
50/50
2.6852.685
3151781S ANNAS1
50/50
1.381.38
3151761LOISA E
50/50
5.5965.596
208900BRIS G1
50/50
-2.836-2.836
316084AB2-161 E
Adder
5.0917647058823544.328
3145946PLYMOUTH TP
Adder
0.29882352941176470.254
933982AD1-022 E
Adder
4.4070588235294123.746
940641AE2-051 C
50/50
18.07818.078
927146AC1-208 E
Adder
3.68117647058823533.129
934622AD1-088 E
Adder
4.5117647058823533.835
934612AD1-087 E
Adder
3.50941176470588272.983
316336AC2-165 C
Adder
10.0588235294117668.55
926004AC1-076_E
50/50
6.486.48
935162AD1-151 E
Adder
9.1294117647058827.76
943461AF1-017 C
Adder
1.2482352941176471.061
932596AC2-079 E
Adder
8.6588235294117667.36
316311AC2-079 C
Adder
5.3070588235294124.511
938532AE1-072 E
Adder
8.4941176470588247.22
3146326AYDLETT TAP
Adder
1.25764705882352931.069
917122Z2-027 E
Adder
1.24470588235294131.058
920692AA2-178 E
Adder
3.8023529411764713.232
316233AE1-074 C
Adder
2.5458823529411772.164
966622AG1-532 E
Adder
0.88117647058823530.749
3147133PAMPLIN
Adder
0.91529411764705890.778
966002AG1-469 E
50/50
0.9930.993
926739AC1-158 E1
50/50
50.96750.967
960081AF2-299 C
Adder
1.76235294117647071.498
926072AC1-086 E
Adder
8.9094117647058837.573
944011AF1-069 C
50/50
13.59813.598
963041AG1-153 C
Adder
5.7788235294117654.912
936261AD2-033 C
Adder
12.02117647058823610.218
962562AG1-105 E
Adder
5.3929411764705884.584
961791AG1-021 C
Adder
1.65764705882352951.409
316045AC1-158 C2
50/50
19.48619.486
316170AC1-121 C
50/50
2.7692.769
3145256KINGFORK
Adder
0.92470588235294130.786
925522AC1-027 E
Adder
1.1282352941176470.959
941102AE2-104 E
Adder
4.9423529411764714.201
957872AF2-081 E
Adder
3.9717647058823533.376
933291AC2-141 C
Adder
28.12941176470588223.91
926755AC1-161 E
Adder
12.0070588235294110.206
938552AE1-074 E
Adder
1.28235294117647071.09
932632AC2-084 E
Adder
2.96705882352941152.522
926214AC1-099 E
Adder
1.1082352941176470.942
924162AB2-060 E OP
Adder
3.95764705882352933.364
964242AG1-285 E
Adder
7.7211764705882356.563
938562AE1-075 E
Adder
1.0917647058823530.928
3152251N ANNA1
50/50
89.57189.571
934862AD1-115 E
Adder
4.73176470588235354.022
926502AC1-121 E
50/50
1.3031.303
3150651CHESTF6
Adder
15.92588235294117813.537
946262AF1-291 E
Adder
1.24470588235294131.058
934576AD1-082 E
Adder
4.0564705882352943.448
943612AF1-032 E
Adder
0.85764705882352940.729
3145506HICKORY
Adder
2.02235294117647071.719
944602AF1-125 E
Adder
95.5082352941176581.182
957871AF2-081 C
Adder
9.2670588235294127.877
933292AC2-141 E
Adder
12.0070588235294110.206
940492AE2-034 E
Adder
2.85176470588235282.424
934522AD1-076 E
Adder
5.7635294117647064.899
943172AE2-346 E
Adder
0.56117647058823530.477
918492AA1-063AE OP
Adder
3.80117647058823543.231
925122AB2-169 E
Adder
5.2764705882352954.485
917332KELFORD E
Adder
1.51764705882352961.29
316274AC1-208 C
Adder
8.2905882352941187.047
937482AD2-202 E
Adder
1.02705882352941180.873
961792AG1-021 E
Adder
1.4117647058823531.2
939191AE1-149 C
Adder
9.8529411764705898.375
3143316POE
Adder
1.28823529411764711.095
901082W1-029 E
Adder
29.54000000000000325.109
926206AC1-098 E
Adder
3.35647058823529452.853
942462AE2-259 E
Adder
6.1105882352941175.194
3151751LOISA D
50/50
2.7452.745
3151731LOISA B
50/50
2.7452.745
316164AC1-076_C
50/50
1.1311.131
940432AE2-027 E
Adder
7.4705882352941186.35
934012AD1-025 E
Adder
8.5352941176470597.255
913392Y1-086 E
Adder
2.03647058823529431.731
939411AE1-173 C
Adder
92.2811764705882478.439
3137643SOCKMAN
Adder
0.66588235294117650.566
933502AC2-165 E
Adder
7.5705882352941176.435
3151741LOISA C
50/50
2.7452.745
316303AF2-085
50/50
4.3644.364
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.0035.003
CBM South 2LTFEXP_CBM-S2->PJM
CBM
88.42988.429
CPLELTFEXP_CPLE->PJM
CLTF
10.49610.496
TVALTFEXP_TVA->PJM
CLTF
5.6275.627
O66PJM->LTFIMP_O-066
CMTX_NF
36.7236.72
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.22125.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.23820.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.4183.418
LAGNLTFEXP_LAGN->PJM
CLTF
7.0687.068
NYPJM->LTFIMP_NY
CLTF
2.7142.714
LGEELTFEXP_LGEE->PJM
CLTF
1.0981.098
WECLTFEXP_WEC->PJM
CLTF
0.5410.541
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7645.764
SIGELTFEXP_SIGE->PJM
CLTF
0.2140.214

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4234.7
MW Contribution:22.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
941031AE2-094 C
80/20
138.215138.215
3151531CLOVER1
80/20
28.86828.868
3151541CLOVER2
80/20
28.59828.598
958211AF2-115 C
80/20
2.8862.886
24684605SMG4
80/20
3.0033.003
964211AG1-282 C
Adder
-1.7011764705882353-1.446
964241AG1-285 C
80/20
17.07617.076
316034AC1-036 C
80/20
0.3110.311
962561AG1-105 C
80/20
14.10814.108
316118AC1-105 C
80/20
1.5721.572
3144293JTRSVLE
80/20
0.5290.529
316217AC1-145 C
80/20
0.3750.375
942671AE2-283 C
80/20
3.3963.396
943811AF1-049 C
80/20
8.9298.929
938741AE1-100 C
80/20
0.690.69
941671AE2-166 C
80/20
5.45.4
942001AE2-212 C
Adder
-2.010588235294118-1.709
3151031BRUNSWICKG2
80/20
25.15725.157
316359AB2-059 C OP
80/20
1.0881.088
934621AD1-088 C
80/20
21.36821.368
946301AF1-294 C
80/20
4.7464.746
942461AE2-259 C
80/20
12.19912.199
316283AC2-100 C
80/20
2.1162.116
316197AC1-042 C
80/20
0.3150.315
944641AF1-129 C
Adder
-90.49176470588236-76.918
316240AF1-291 C
Adder
-1.9317647058823528-1.642
316263AC1-034 C
80/20
4.3284.328
937481AD2-202 C
80/20
0.8240.824
3151591KERR 2
80/20
1.6151.615
959311AF2-222 C
80/20
22.05622.056
316205AC1-080 C
80/20
0.4520.452
316123AC1-075 C
80/20
1.3531.353
942751AE2-291 C
80/20
12.11212.112
3151561HALLBR1
80/20
1.1241.124
24684305SMG1
80/20
1.0911.091
3151021BRUNSWICKG1
80/20
25.15725.157
957481AF2-042 C
80/20
129.887129.887
316003AC1-222 C
80/20
1.7441.744
24684405SMG2
80/20
3.0033.003
3151601KERR 3
80/20
1.6151.615
3151581KERR 1
80/20
0.5770.577
935171AD1-152 C
80/20
2.8492.849
936161AD2-022 C
80/20
12.15912.159
270197AC1-083 C
80/20
0.9340.934
24728405LEESVG
80/20
0.8940.894
938531AE1-072 C
Adder
-16.01294117647059-13.611
316049AB1-081 C OP
80/20
0.9230.923
316238AB2-078 C O1
80/20
0.4550.455
316322AB2-045 C
80/20
0.2270.227
944011AF1-069 C
80/20
45.1645.16
963041AG1-153 C
80/20
17.10317.103
3151051BRUNSWICKS1
80/20
52.26552.265
936261AD2-033 C
80/20
17.43217.432
961791AG1-021 C
80/20
2.3092.309
316248AF1-058 C
80/20
0.5710.571
936171AD2-023 C
80/20
7.0937.093
941801AE2-185 C
80/20
4.3664.366
940641AE2-051 C
Adder
-21.040000000000003-17.884
3152431Z1-086 GT3
80/20
33.46433.464
934611AD1-087 C
80/20
2.842.84
3151611KERR 4
80/20
1.6151.615
3151621KERR 5
80/20
1.6151.615
316237AB2-079 C O1
80/20
0.4550.455
316222AC1-221 C
80/20
2.6372.637
933291AC2-141 C
Adder
-32.203529411764706-27.373
3151641KERR 7
80/20
1.6151.615
313527AB2-043 C
80/20
0.7110.711
3152661PLYWOOD A
80/20
2.0932.093
316129AC1-054 C
80/20
1.0481.048
3151631KERR 6
80/20
1.6151.615
316131AB2-060 C
80/20
2.042.04
3138533PONTONDP
80/20
0.8550.855
24684505SMG3
80/20
1.8451.845
24684705SMG5
80/20
1.1411.141
941431AE2-140 C
80/20
13.39313.393
3152421Z1-086 GT2
80/20
33.46433.464
3152441Z1-086 ST
80/20
58.26658.266
3152411Z1-086 GT1
80/20
33.47333.473
3151041BRUNSWICKG3
80/20
25.15725.157
316239AB2-077 C O1
80/20
0.4550.455
964791AG1-342 C
80/20
5.7665.766
940081AE1-250 C
80/20
12.86112.861
957601AF2-054 C
Adder
-1.8-1.53
940601AE2-047 C
80/20
4.0274.027
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.2639.263
CBM South 2LTFEXP_CBM-S2->PJM
CBM
170.641170.641
CPLELTFEXP_CPLE->PJM
CLTF
19.41719.417
TVALTFEXP_TVA->PJM
CLTF
11.71211.712
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.06671.066
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.76444.764
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.3488.348
LAGNLTFEXP_LAGN->PJM
CLTF
14.84614.846
NYPJM->LTFIMP_NY
CLTF
2.1082.108
LGEELTFEXP_LGEE->PJM
CLTF
2.7422.742
WECLTFEXP_WEC->PJM
CLTF
1.451.45
SIGELTFEXP_SIGE->PJM
CLTF
0.5240.524

Details for AG1-285 TP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG1-285 TP-3CHASCTY 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 15832_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.58 %
Rating:349.0 MVA
Rating Type:C
MVA to Mitigate:375.45
MW Contribution:166.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
925612AC1-036 E
50/50
5.155.15
3147223TWITTYS
50/50
5.7095.709
959312AF2-222 E
50/50
66.99766.997
3147133PAMPLIN
50/50
5.9755.975
964242AG1-285 E
50/50
49.99849.998
959311AF2-222 C
50/50
99.99699.996
964241AG1-285 C
50/50
74.99774.997
316034AC1-036 C
50/50
1.4011.401
942462AE2-259 E
50/50
39.99839.998
942461AE2-259 C
50/50
59.99759.997
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0030.003
O66PJM->LTFIMP_O-066
CMTX_NF
0.030.03
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0020.002
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0080.008
NYPJM->LTFIMP_NY
CLTF
0.0020.002
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0090.009
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0030.003
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0040.004
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0050.005
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0020.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0120.012
MDUPJM->LTFIMP_MDU
CLTF
00

Details for AG1-285 TP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG1-285 TP-3CHASCTY 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: FARMVIL L432_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.57 %
Rating:349.0 MVA
Rating Type:C
MVA to Mitigate:375.41
MW Contribution:166.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
925612AC1-036 E
50/50
5.155.15
3147223TWITTYS
50/50
5.7095.709
959312AF2-222 E
50/50
66.99766.997
3147133PAMPLIN
50/50
5.9755.975
964242AG1-285 E
50/50
49.99849.998
959311AF2-222 C
50/50
99.99699.996
964241AG1-285 C
50/50
74.99774.997
316034AC1-036 C
50/50
1.4011.401
942462AE2-259 E
50/50
39.99839.998
942461AE2-259 C
50/50
59.99759.997
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0030.003
O66PJM->LTFIMP_O-066
CMTX_NF
0.030.03
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0020.002
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0080.008
NYPJM->LTFIMP_NY
CLTF
0.0020.002
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0090.009
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0030.003
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0040.004
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0050.005
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0020.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0120.012
MDUPJM->LTFIMP_MDU
CLTF
00
CONTINGENCY 'DVP_P4-6: CHASE C T342_SRT-A'
 OPEN BUS 313527   /*AB2-043 C      0.6
 OPEN BUS 313528   /*AB2-043 COL   34.5
 OPEN BUS 313529   /*3BLUESTONE   115.0
 OPEN BUS 314267   /*3CHASCTY2    115.0
 OPEN BUS 314518   /*3CHASC_1     115.0
 OPEN BUS 314681   /*3CHASCTY     115.0
 OPEN BUS 924022   /*AB2-043 E O1   0.6
END
CONTINGENCY 'DVP_P1-2: LN 1012_SRT-A-4'
 OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1   /*AG1-285 TP   115.0 - 3CHASCTY     115.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 246_SRT-A'
 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1   /*6SUFFOLK     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1   /*6EARLEYS     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1   /*6NUCO TP     230.0 - 6NUCOR       230.0
 OPEN BUS 314575                                   /*6NUCO TP     230.0
 OPEN BUS 314590                                   /*6NUCOR       230.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A'
 OPEN BRANCH FROM BUS 304183 TO BUS 314935 CKT 1   /*8WAKE 500 TT 500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 568T575_SRT-A'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1   /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1   /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 314940 TO BUS 941030 CKT 1   /*8ROGERS RD   500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 15832_SRT-A'
 OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1   /*3FLAT CREEK  115.0 - 3LONEPN      115.0
 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1   /*3FLAT CREEK  115.0 - 3MORAN       115.0
 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1   /*3LONEPINE_1  115.0 - 3LONEPN      115.0
 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1   /*3FARMVIL     115.0 - 3MORAN       115.0
 OPEN BUS 313755                                   /*3FLAT CREEK  115.0
 OPEN BUS 314519                                   /*3LONEPINE_1  115.0
 OPEN BUS 314691                                   /*3FARMVIL     115.0
 OPEN BUS 314707                                   /*3MORAN       115.0
END
CONTINGENCY 'DVP_P4-5: FARMVIL L432_SRT-A-1'
 OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1   /*6PRINCE EDW  230.0 - 6BRIERY      230.0
 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1   /*6PRINCE EDW  230.0 - 6FARMVIL     230.0
 OPEN BRANCH FROM BUS 314268 TO BUS 313996 CKT 1   /*6BRIERY      230.0 - 6FINNEYWOOD  230.0
 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1   /*3FARMVIL     115.0 - 6FARMVIL     230.0
 OPEN BUS 313802                                   /*6PRINCE EDW  230.0
 OPEN BUS 314268                                   /*6BRIERY      230.0
 OPEN BUS 314691                                   /*3FARMVIL     115.0
END
314691 to 314692 ckt 1
314691 to 314692 ckt 2
314726 to 314691 ckt 1
314282 to 314285 ckt 1
314563 to 940480 ckt 1
314435 to 314282 ckt 1
314902 to 314914 ckt 1
314914 to 314918 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314936 to 314902 ckt 1
314934 to 314916 ckt 1
941030 to 314902 ckt 1
964240 to 314681 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P1-2: LN 235_SRT-A
OPAC121.52 %182.64B221.9540.3
GD1DVP
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
DVP_P1-2: LN 1012_SRT-A-1
OPAC127.32 %205.86B262.1166.99
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC109.21 %678.68B741.1830.09
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC108.15 %678.68B734.0330.09
GD1DVP
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
OPAC107.58 %571.52B614.8116.61
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC105.97 %661.76B701.2928.05
GD1DVP
6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
OPAC108.24 %571.52B618.6116.61
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC108.64 %661.76B718.9128.05
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC102.38 %661.76B677.5228.05
GD1DVP
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
OPAC107.58 %571.52B614.8116.61
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Base Case
OPAC104.13 %3220.44A3353.3629.71
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
OPAC126.34 %1058.16B1336.889.31
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
OPAC110.46 %3220.44B3557.2337.07
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
OPAC108.69 %4070.2B4423.7158.05
GD1DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC106.0 %2442.12B2588.6123.85
GD1DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
OPAC105.93 %4070.2B4311.6950.59

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 235_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:121.52 %
Rating:182.64 MVA
Rating Type:B
MVA to Mitigate:221.95
MW Contribution:40.3
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 235_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:149.01 %
Rating:182.64 MVA
Rating Type:B
MVA to Mitigate:272.15
MW Contribution:56.16
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934622AD1-088 E
Adder
1.42588235294117641.212
924302AB2-077 E O1
50/50
0.9010.901
3147133PAMPLIN
50/50
2.4852.485
925612AC1-036 E
50/50
1.1371.137
316237AB2-079 C O1
50/50
0.2210.221
924312AB2-078 E O1
50/50
0.9010.901
316238AB2-078 C O1
50/50
0.2210.221
926274AC1-105 E
Adder
1.0752941176470590.914
938821AE1-108 C
Adder
-5.455294117647059-4.637
964242AG1-285 E
50/50
5.5885.588
313527AB2-043 C
50/50
0.3610.361
924162AB2-060 E OP
50/50
3.2583.258
964792AG1-342 E
Adder
1.13411764705882350.964
959311AF2-222 C
50/50
24.13324.133
934621AD1-088 C
Adder
2.9611764705882352.517
946301AF1-294 C
50/50
8.7128.712
942461AE2-259 C
50/50
33.29833.298
961792AG1-021 E
50/50
3.613.61
941011AE2-092 C
Adder
-4.856470588235294-4.128
3147223TWITTYS
50/50
1.261.26
959312AF2-222 E
50/50
16.16916.169
924022AB2-043 E O1
50/50
3.623.62
316239AB2-077 C O1
50/50
0.2210.221
942462AE2-259 E
50/50
22.19822.198
964791AG1-342 C
Adder
1.70117647058823531.446
924322AB2-079 E O1
50/50
0.9010.901
946302AF1-294 E
50/50
7.3787.378
943902AF1-058 E
Adder
0.414117647058823530.352
316131AB2-060 C
50/50
1.1311.131
3138533PONTONDP
50/50
1.571.57
964241AG1-285 C
50/50
8.3818.381
316034AC1-036 C
50/50
0.310.31
958212AF2-115 E
50/50
4.5134.513
962561AG1-105 C
Adder
4.583.893
936261AD2-033 C
50/50
18.4818.48
3144293JTRSVLE
50/50
0.9750.975
961791AG1-021 C
50/50
4.2384.238
962562AG1-105 E
Adder
3.05294117647058852.595
936262AD2-033 E
50/50
12.3212.32
958211AF2-115 C
50/50
5.2985.298
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.1372.137
G-007PJM->LTFIMP_G-007
CMTX_NF
0.2090.209
CPLELTFEXP_CPLE->PJM
CLTF
1.51.5
SIGELTFEXP_SIGE->PJM
CLTF
0.0180.018
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0840.084
MECLTFEXP_MEC->PJM
CLTF
0.3150.315
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.7150.715
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.68211.682
WECLTFEXP_WEC->PJM
CLTF
0.0450.045
LAGNLTFEXP_LAGN->PJM
CLTF
0.7670.767
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.0592.059
NYPJM->LTFIMP_NY
CLTF
0.1040.104
TVALTFEXP_TVA->PJM
CLTF
0.5920.592
O66PJM->LTFIMP_O-066
CMTX_NF
1.3381.338

Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1012_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:127.32 %
Rating:205.86 MVA
Rating Type:B
MVA to Mitigate:262.1
MW Contribution:166.99
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1012_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:127.32 %
Rating:205.86 MVA
Rating Type:B
MVA to Mitigate:262.1
MW Contribution:166.99
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3147133PAMPLIN
50/50
5.9755.975
925612AC1-036 E
50/50
5.155.15
959311AF2-222 C
50/50
99.99699.996
942461AE2-259 C
50/50
59.99759.997
3147223TWITTYS
50/50
5.7095.709
959312AF2-222 E
50/50
66.99766.997
942462AE2-259 E
50/50
39.99839.998
316034AC1-036 C
50/50
1.4051.405
NYPJM->LTFIMP_NY
CLTF
0.0020.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0120.012
MDUPJM->LTFIMP_MDU
CLTF
00
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0030.003
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0080.008
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0030.003
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0050.005
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0020.002
O66PJM->LTFIMP_O-066
CMTX_NF
0.030.03
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0090.009
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0020.002
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0040.004

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.21 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:741.18
MW Contribution:30.09
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.95 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:773.37
MW Contribution:32.59
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
50/50
32.5532.55
934622AD1-088 E
50/50
3.2133.213
934612AD1-087 E
Adder
1.95058823529411751.658
3151931BEARGRDN S1
50/50
23.0223.02
924302AB2-077 E O1
50/50
0.9550.955
958131AF2-107 C
Adder
2.38941176470588262.031
3147133PAMPLIN
50/50
1.4571.457
316322AB2-045 C
50/50
0.840.84
927264AC1-222 E
Adder
1.98117647058823531.684
958132AF2-107 E
Adder
1.30941176470588231.113
925612AC1-036 E
50/50
0.8890.889
316237AB2-079 C O1
50/50
0.2340.234
924312AB2-078 E O1
50/50
0.9550.955
316238AB2-078 C O1
50/50
0.2340.234
926274AC1-105 E
Adder
1.48352941176470581.261
938821AE1-108 C
50/50
16.62316.623
964242AG1-285 E
50/50
6.6466.646
313527AB2-043 C
50/50
0.3760.376
924162AB2-060 E OP
50/50
3.2253.225
964792AG1-342 E
Adder
1.41647058823529411.204
3151911BEARGRDN G1
50/50
17.79517.795
933502AC2-165 E
50/50
24.49824.498
925785AC1-054 E
Adder
1.48235294117647071.26
959311AF2-222 C
50/50
18.01818.018
957482AF2-042 E
Adder
18.38941176470588315.631
934621AD1-088 C
50/50
6.6736.673
935172AD1-152 E
Adder
2.81529411764705852.393
946301AF1-294 C
50/50
5.15.1
942461AE2-259 C
50/50
17.67317.673
938822AE1-108 E
50/50
7.9317.931
937482AD2-202 E
Adder
0.57058823529411760.485
961792AG1-021 E
50/50
2.1132.113
3151921BEARGRDN G2
50/50
17.79517.795
941011AE2-092 C
Adder
8.222352941176476.989
3147223TWITTYS
50/50
0.9860.986
959312AF2-222 E
50/50
12.07212.072
924022AB2-043 E O1
50/50
3.7783.778
316239AB2-077 C O1
50/50
0.2340.234
942462AE2-259 E
50/50
11.78211.782
964791AG1-342 C
Adder
2.1235294117647061.805
957481AF2-042 C
Adder
27.58352941176470823.446
924322AB2-079 E O1
50/50
0.9550.955
946302AF1-294 E
50/50
4.3194.319
943902AF1-058 E
Adder
0.65294117647058840.555
316131AB2-060 C
50/50
1.121.12
3138533PONTONDP
50/50
0.9190.919
964241AG1-285 C
50/50
9.9699.969
316034AC1-036 C
50/50
0.2430.243
958212AF2-115 E
50/50
2.6422.642
962561AG1-105 C
50/50
5.5115.511
936261AD2-033 C
50/50
13.17213.172
3144293JTRSVLE
50/50
0.5710.571
961791AG1-021 C
50/50
2.4812.481
962562AG1-105 E
50/50
3.6743.674
924032AB2-045 E
50/50
3.7663.766
936262AD2-033 E
50/50
8.7818.781
958211AF2-115 C
50/50
3.1013.101
941012AE2-092 E
Adder
5.48117647058823554.659
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.6382.638
NYPJM->LTFIMP_NY
CLTF
0.3510.351
TVALTFEXP_TVA->PJM
CLTF
0.8870.887
O66PJM->LTFIMP_O-066
CMTX_NF
4.3344.334
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.54721.547
WECLTFEXP_WEC->PJM
CLTF
0.0090.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.161.16
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.0390.039
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6760.676
CPLELTFEXP_CPLE->PJM
CLTF
2.8232.823
SIGELTFEXP_SIGE->PJM
CLTF
0.0110.011
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0240.024
MECLTFEXP_MEC->PJM
CLTF
0.2490.249
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3441.344

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.15 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:734.03
MW Contribution:30.09
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.89 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:766.15
MW Contribution:32.59
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
50/50
32.5532.55
934622AD1-088 E
50/50
3.2133.213
934612AD1-087 E
Adder
1.95058823529411751.658
3151931BEARGRDN S1
50/50
23.0223.02
924302AB2-077 E O1
50/50
0.9550.955
958131AF2-107 C
Adder
2.38941176470588262.031
3147133PAMPLIN
50/50
1.4571.457
316322AB2-045 C
50/50
0.840.84
927264AC1-222 E
Adder
1.98117647058823531.684
958132AF2-107 E
Adder
1.30941176470588231.113
925612AC1-036 E
50/50
0.8890.889
316237AB2-079 C O1
50/50
0.2340.234
924312AB2-078 E O1
50/50
0.9550.955
316238AB2-078 C O1
50/50
0.2340.234
926274AC1-105 E
Adder
1.48352941176470581.261
938821AE1-108 C
50/50
16.62316.623
964242AG1-285 E
50/50
6.6466.646
313527AB2-043 C
50/50
0.3760.376
924162AB2-060 E OP
50/50
3.2253.225
964792AG1-342 E
Adder
1.41647058823529411.204
3151911BEARGRDN G1
50/50
17.79517.795
933502AC2-165 E
50/50
24.49824.498
925785AC1-054 E
Adder
1.48235294117647071.26
959311AF2-222 C
50/50
18.01818.018
957482AF2-042 E
Adder
18.38941176470588315.631
934621AD1-088 C
50/50
6.6736.673
935172AD1-152 E
Adder
2.81529411764705852.393
946301AF1-294 C
50/50
5.15.1
942461AE2-259 C
50/50
17.67317.673
938822AE1-108 E
50/50
7.9317.931
937482AD2-202 E
Adder
0.57058823529411760.485
961792AG1-021 E
50/50
2.1132.113
3151921BEARGRDN G2
50/50
17.79517.795
941011AE2-092 C
Adder
8.222352941176476.989
3147223TWITTYS
50/50
0.9860.986
959312AF2-222 E
50/50
12.07212.072
924022AB2-043 E O1
50/50
3.7783.778
316239AB2-077 C O1
50/50
0.2340.234
942462AE2-259 E
50/50
11.78211.782
964791AG1-342 C
Adder
2.1235294117647061.805
957481AF2-042 C
Adder
27.58352941176470823.446
924322AB2-079 E O1
50/50
0.9550.955
946302AF1-294 E
50/50
4.3194.319
943902AF1-058 E
Adder
0.65294117647058840.555
316131AB2-060 C
50/50
1.121.12
3138533PONTONDP
50/50
0.9190.919
964241AG1-285 C
50/50
9.9699.969
316034AC1-036 C
50/50
0.2430.243
958212AF2-115 E
50/50
2.6422.642
962561AG1-105 C
50/50
5.5115.511
936261AD2-033 C
50/50
13.17213.172
3144293JTRSVLE
50/50
0.5710.571
961791AG1-021 C
50/50
2.4812.481
962562AG1-105 E
50/50
3.6743.674
924032AB2-045 E
50/50
3.7663.766
936262AD2-033 E
50/50
8.7818.781
958211AF2-115 C
50/50
3.1013.101
941012AE2-092 E
Adder
5.48117647058823554.659
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0240.024
MECLTFEXP_MEC->PJM
CLTF
0.2490.249
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3441.344
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.0390.039
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6760.676
CPLELTFEXP_CPLE->PJM
CLTF
2.8232.823
SIGELTFEXP_SIGE->PJM
CLTF
0.0110.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.6382.638
NYPJM->LTFIMP_NY
CLTF
0.3510.351
TVALTFEXP_TVA->PJM
CLTF
0.8870.887
O66PJM->LTFIMP_O-066
CMTX_NF
4.3344.334
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.54721.547
WECLTFEXP_WEC->PJM
CLTF
0.0090.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.161.16

Details for 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:107.58 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:614.81
MW Contribution:16.61
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.99 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:645.76
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
Adder
-4.488235294117647-3.815
934622AD1-088 E
50/50
8.0788.078
934611AD1-087 C
50/50
1.9191.919
934612AD1-087 E
50/50
5.5365.536
3151611KERR 4
50/50
1.1131.113
927255AC1-221 E
50/50
3.413.41
924302AB2-077 E O1
50/50
1.321.32
3151621KERR 5
50/50
1.1131.113
316222AC1-221 C
50/50
1.3041.304
942752AE2-291 E
50/50
4.2094.209
966622AG1-532 E
Adder
0.29176470588235290.248
927264AC1-222 E
50/50
4.2714.271
925612AC1-036 E
50/50
0.6080.608
316237AB2-079 C O1
50/50
0.3240.324
924312AB2-078 E O1
50/50
1.321.32
316238AB2-078 C O1
50/50
0.3240.324
926274AC1-105 E
50/50
2.892.89
938821AE1-108 C
Adder
-8.042352941176471-6.836
964242AG1-285 E
50/50
10.84610.846
313527AB2-043 C
50/50
0.5090.509
924162AB2-060 E OP
50/50
3.9993.999
3151591KERR 2
50/50
1.1131.113
964792AG1-342 E
50/50
2.4822.482
932763AC2-100 E
50/50
2.2422.242
316283AC2-100 C
50/50
1.0191.019
3137643SOCKMAN
Adder
0.236470588235294130.201
937481AD2-202 C
50/50
0.5570.557
3151641KERR 7
50/50
1.1131.113
316205AC1-080 C
50/50
0.2470.247
316123AC1-075 C
50/50
0.740.74
3145723EMPORIA
Adder
0.136470588235294120.116
923573AB1-173 E OP
Adder
1.06470588235294120.905
919692AA2-053 E OP
Adder
1.31411764705882361.117
925785AC1-054 E
50/50
2.3712.371
959311AF2-222 C
Adder
9.9482352941176468.456
942751AE2-291 C
50/50
6.3136.313
957482AF2-042 E
50/50
57.29557.295
934621AD1-088 C
50/50
16.77816.778
935172AD1-152 E
50/50
7.5637.563
942461AE2-259 C
Adder
-11.085882352941177-9.423
937482AD2-202 E
50/50
1.621.62
3151581KERR 1
50/50
0.3970.397
3151601KERR 3
50/50
1.1131.113
3152661PLYWOOD A
50/50
1.3061.306
941011AE2-092 C
Adder
-7.384705882352941-6.277
966621AG1-532 C
Adder
0.437647058823529440.372
3147223TWITTYS
50/50
0.6740.674
959312AF2-222 E
Adder
6.66588235294117755.666
924022AB2-043 E O1
50/50
5.1075.107
316003AC1-222 C
50/50
1.0461.046
926024AC1-080 E
50/50
0.8510.851
316239AB2-077 C O1
50/50
0.3240.324
935171AD1-152 C
50/50
1.8391.839
964791AG1-342 C
50/50
3.7243.724
925997AC1-075 E
50/50
2.5662.566
957481AF2-042 C
50/50
85.94285.942
316088AB2-174 E
Adder
2.0917647058823531.778
923994AB2-040_E
Adder
1.99764705882352931.698
924322AB2-079 E O1
50/50
1.321.32
943902AF1-058 E
50/50
1.4231.423
946282AF1-292 E
Adder
0.32235294117647060.274
316129AC1-054 C
50/50
0.8410.841
316131AB2-060 C
50/50
1.3891.389
316118AC1-105 C
50/50
0.9880.988
946281AF1-292 C
Adder
0.48352941176470590.411
960082AF2-299 E
Adder
0.38941176470588240.331
3151541CLOVER2
50/50
19.33819.338
964241AG1-285 C
50/50
16.2716.27
316034AC1-036 C
50/50
0.1660.166
962561AG1-105 C
50/50
9.2429.242
960081AF2-299 C
Adder
0.58352941176470590.496
3151531CLOVER1
50/50
19.51919.519
936261AD2-033 C
Adder
5.2729411764705894.482
3151631KERR 6
50/50
1.1131.113
962562AG1-105 E
50/50
6.1616.161
316248AF1-058 C
50/50
0.3490.349
936262AD2-033 E
Adder
3.5152941176470592.988
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.2877.287
G-007PJM->LTFIMP_G-007
CMTX_NF
0.610.61
CPLELTFEXP_CPLE->PJM
CLTF
3.4573.457
SIGELTFEXP_SIGE->PJM
CLTF
0.0570.057
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.2860.286
MECLTFEXP_MEC->PJM
CLTF
0.9490.949
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6471.647
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.50427.504
WECLTFEXP_WEC->PJM
CLTF
0.1510.151
LAGNLTFEXP_LAGN->PJM
CLTF
1.9781.978
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.6115.611
NYPJM->LTFIMP_NY
CLTF
0.2910.291
TVALTFEXP_TVA->PJM
CLTF
1.5461.546
O66PJM->LTFIMP_O-066
CMTX_NF
3.8923.892

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.97 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:701.29
MW Contribution:28.05
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.14 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:748.75
MW Contribution:30.42
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
50/50
30.2830.28
934622AD1-088 E
50/50
2.9962.996
934612AD1-087 E
Adder
1.8235294117647061.55
3151931BEARGRDN S1
50/50
21.41521.415
924302AB2-077 E O1
50/50
0.8940.894
958131AF2-107 C
50/50
4.7314.731
3147133PAMPLIN
50/50
1.3571.357
316322AB2-045 C
50/50
0.7820.782
927264AC1-222 E
Adder
1.91647058823529411.629
958132AF2-107 E
50/50
2.5922.592
925612AC1-036 E
50/50
0.8290.829
316237AB2-079 C O1
50/50
0.2190.219
924312AB2-078 E O1
50/50
0.8940.894
316238AB2-078 C O1
50/50
0.2190.219
926274AC1-105 E
Adder
1.40941176470588241.198
938821AE1-108 C
50/50
33.08633.086
964242AG1-285 E
50/50
6.2046.204
313527AB2-043 C
50/50
0.3520.352
924162AB2-060 E OP
50/50
3.0163.016
964792AG1-342 E
Adder
1.33764705882352941.137
3151911BEARGRDN G1
50/50
16.55416.554
933502AC2-165 E
50/50
22.78922.789
925785AC1-054 E
Adder
1.3870588235294121.179
959311AF2-222 C
50/50
16.79916.799
957482AF2-042 E
Adder
17.15411764705882214.581
934621AD1-088 C
50/50
6.2236.223
935172AD1-152 E
Adder
2.64470588235294152.248
946301AF1-294 C
50/50
4.7534.753
942461AE2-259 C
50/50
16.45516.455
938822AE1-108 E
50/50
15.78715.787
937482AD2-202 E
Adder
0.53411764705882360.454
961792AG1-021 E
50/50
1.971.97
3151921BEARGRDN G2
50/50
16.55416.554
941011AE2-092 C
50/50
23.99423.994
3147223TWITTYS
50/50
0.9190.919
959312AF2-222 E
50/50
11.25511.255
924022AB2-043 E O1
50/50
3.5343.534
316239AB2-077 C O1
50/50
0.2190.219
942462AE2-259 E
50/50
10.9710.97
964791AG1-342 C
Adder
2.00705882352941161.706
957481AF2-042 C
Adder
25.7317647058823521.872
924322AB2-079 E O1
50/50
0.8940.894
946302AF1-294 E
50/50
4.0254.025
943902AF1-058 E
Adder
0.62352941176470590.53
316131AB2-060 C
50/50
1.0471.047
3138533PONTONDP
50/50
0.8560.856
964241AG1-285 C
50/50
9.3069.306
316034AC1-036 C
50/50
0.2260.226
958212AF2-115 E
50/50
2.4622.462
962561AG1-105 C
Adder
5.197647058823534.418
936261AD2-033 C
50/50
12.29412.294
3144293JTRSVLE
50/50
0.5320.532
961791AG1-021 C
50/50
2.3122.312
962562AG1-105 E
Adder
3.4647058823529412.945
924032AB2-045 E
50/50
3.5043.504
936262AD2-033 E
50/50
8.1968.196
958211AF2-115 C
50/50
2.892.89
941012AE2-092 E
50/50
15.99615.996
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.18821.188
WECLTFEXP_WEC->PJM
CLTF
0.0360.036
LAGNLTFEXP_LAGN->PJM
CLTF
1.2621.262
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.0933.093
NYPJM->LTFIMP_NY
CLTF
0.3520.352
TVALTFEXP_TVA->PJM
CLTF
0.9770.977
O66PJM->LTFIMP_O-066
CMTX_NF
4.4054.405
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
MECLTFEXP_MEC->PJM
CLTF
0.3740.374
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.2941.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4071.407
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6880.688
CPLELTFEXP_CPLE->PJM
CLTF
2.7182.718
SIGELTFEXP_SIGE->PJM
CLTF
0.020.02

Details for 6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.24 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:618.61
MW Contribution:16.61
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.66 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:649.58
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
Adder
-4.488235294117647-3.815
934622AD1-088 E
50/50
8.0788.078
934611AD1-087 C
50/50
1.9191.919
934612AD1-087 E
50/50
5.5365.536
3151611KERR 4
50/50
1.1131.113
927255AC1-221 E
50/50
3.413.41
924302AB2-077 E O1
50/50
1.321.32
3151621KERR 5
50/50
1.1131.113
316222AC1-221 C
50/50
1.3041.304
942752AE2-291 E
50/50
4.2094.209
966622AG1-532 E
Adder
0.29176470588235290.248
927264AC1-222 E
50/50
4.2714.271
925612AC1-036 E
50/50
0.6080.608
316237AB2-079 C O1
50/50
0.3240.324
924312AB2-078 E O1
50/50
1.321.32
316238AB2-078 C O1
50/50
0.3240.324
926274AC1-105 E
50/50
2.892.89
938821AE1-108 C
Adder
-8.042352941176471-6.836
964242AG1-285 E
50/50
10.84610.846
313527AB2-043 C
50/50
0.5090.509
924162AB2-060 E OP
50/50
3.9993.999
3151591KERR 2
50/50
1.1131.113
964792AG1-342 E
50/50
2.4822.482
932763AC2-100 E
50/50
2.2422.242
316283AC2-100 C
50/50
1.0191.019
3137643SOCKMAN
Adder
0.236470588235294130.201
937481AD2-202 C
50/50
0.5570.557
3151641KERR 7
50/50
1.1131.113
316205AC1-080 C
50/50
0.2470.247
316123AC1-075 C
50/50
0.740.74
3145723EMPORIA
Adder
0.136470588235294120.116
923573AB1-173 E OP
Adder
1.06470588235294120.905
919692AA2-053 E OP
Adder
1.31411764705882361.117
925785AC1-054 E
50/50
2.3712.371
959311AF2-222 C
Adder
9.9482352941176468.456
942751AE2-291 C
50/50
6.3136.313
957482AF2-042 E
50/50
57.29557.295
934621AD1-088 C
50/50
16.77816.778
935172AD1-152 E
50/50
7.5637.563
942461AE2-259 C
Adder
-11.085882352941177-9.423
937482AD2-202 E
50/50
1.621.62
3151581KERR 1
50/50
0.3970.397
3151601KERR 3
50/50
1.1131.113
3152661PLYWOOD A
50/50
1.3061.306
941011AE2-092 C
Adder
-7.384705882352941-6.277
966621AG1-532 C
Adder
0.437647058823529440.372
3147223TWITTYS
50/50
0.6740.674
959312AF2-222 E
Adder
6.66588235294117755.666
924022AB2-043 E O1
50/50
5.1075.107
316003AC1-222 C
50/50
1.0461.046
926024AC1-080 E
50/50
0.8510.851
316239AB2-077 C O1
50/50
0.3240.324
935171AD1-152 C
50/50
1.8391.839
964791AG1-342 C
50/50
3.7243.724
925997AC1-075 E
50/50
2.5662.566
957481AF2-042 C
50/50
85.94285.942
316088AB2-174 E
Adder
2.0917647058823531.778
923994AB2-040_E
Adder
1.99764705882352931.698
924322AB2-079 E O1
50/50
1.321.32
943902AF1-058 E
50/50
1.4231.423
946282AF1-292 E
Adder
0.32235294117647060.274
316129AC1-054 C
50/50
0.8410.841
316131AB2-060 C
50/50
1.3891.389
316118AC1-105 C
50/50
0.9880.988
946281AF1-292 C
Adder
0.48352941176470590.411
960082AF2-299 E
Adder
0.38941176470588240.331
3151541CLOVER2
50/50
19.33819.338
964241AG1-285 C
50/50
16.2716.27
316034AC1-036 C
50/50
0.1660.166
962561AG1-105 C
50/50
9.2429.242
960081AF2-299 C
Adder
0.58352941176470590.496
3151531CLOVER1
50/50
19.51919.519
936261AD2-033 C
Adder
5.2729411764705894.482
3151631KERR 6
50/50
1.1131.113
962562AG1-105 E
50/50
6.1616.161
316248AF1-058 C
50/50
0.3490.349
936262AD2-033 E
Adder
3.5152941176470592.988
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.2860.286
MECLTFEXP_MEC->PJM
CLTF
0.9490.949
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6471.647
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.2877.287
G-007PJM->LTFIMP_G-007
CMTX_NF
0.610.61
CPLELTFEXP_CPLE->PJM
CLTF
3.4573.457
SIGELTFEXP_SIGE->PJM
CLTF
0.0570.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.6115.611
NYPJM->LTFIMP_NY
CLTF
0.2910.291
TVALTFEXP_TVA->PJM
CLTF
1.5461.546
O66PJM->LTFIMP_O-066
CMTX_NF
3.8923.892
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.50427.504
WECLTFEXP_WEC->PJM
CLTF
0.1510.151
LAGNLTFEXP_LAGN->PJM
CLTF
1.9781.978

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.64 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:718.91
MW Contribution:28.05
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.82 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:766.43
MW Contribution:30.42
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
50/50
30.2830.28
934622AD1-088 E
50/50
2.9962.996
934612AD1-087 E
Adder
1.8235294117647061.55
3151931BEARGRDN S1
50/50
21.41521.415
924302AB2-077 E O1
50/50
0.8940.894
958131AF2-107 C
50/50
4.7314.731
3147133PAMPLIN
50/50
1.3571.357
316322AB2-045 C
50/50
0.7820.782
927264AC1-222 E
Adder
1.91647058823529411.629
958132AF2-107 E
50/50
2.5922.592
925612AC1-036 E
50/50
0.8290.829
316237AB2-079 C O1
50/50
0.2190.219
924312AB2-078 E O1
50/50
0.8940.894
316238AB2-078 C O1
50/50
0.2190.219
926274AC1-105 E
Adder
1.40941176470588241.198
938821AE1-108 C
50/50
33.08633.086
964242AG1-285 E
50/50
6.2046.204
313527AB2-043 C
50/50
0.3520.352
924162AB2-060 E OP
50/50
3.0163.016
964792AG1-342 E
Adder
1.33764705882352941.137
3151911BEARGRDN G1
50/50
16.55416.554
933502AC2-165 E
50/50
22.78922.789
925785AC1-054 E
Adder
1.3870588235294121.179
959311AF2-222 C
50/50
16.79916.799
957482AF2-042 E
Adder
17.15411764705882214.581
934621AD1-088 C
50/50
6.2236.223
935172AD1-152 E
Adder
2.64470588235294152.248
946301AF1-294 C
50/50
4.7534.753
942461AE2-259 C
50/50
16.45516.455
938822AE1-108 E
50/50
15.78715.787
937482AD2-202 E
Adder
0.53411764705882360.454
961792AG1-021 E
50/50
1.971.97
3151921BEARGRDN G2
50/50
16.55416.554
941011AE2-092 C
50/50
23.99423.994
3147223TWITTYS
50/50
0.9190.919
959312AF2-222 E
50/50
11.25511.255
924022AB2-043 E O1
50/50
3.5343.534
316239AB2-077 C O1
50/50
0.2190.219
942462AE2-259 E
50/50
10.9710.97
964791AG1-342 C
Adder
2.00705882352941161.706
957481AF2-042 C
Adder
25.7317647058823521.872
924322AB2-079 E O1
50/50
0.8940.894
946302AF1-294 E
50/50
4.0254.025
943902AF1-058 E
Adder
0.62352941176470590.53
316131AB2-060 C
50/50
1.0471.047
3138533PONTONDP
50/50
0.8560.856
964241AG1-285 C
50/50
9.3069.306
316034AC1-036 C
50/50
0.2260.226
958212AF2-115 E
50/50
2.4622.462
962561AG1-105 C
Adder
5.197647058823534.418
936261AD2-033 C
50/50
12.29412.294
3144293JTRSVLE
50/50
0.5320.532
961791AG1-021 C
50/50
2.3122.312
962562AG1-105 E
Adder
3.4647058823529412.945
924032AB2-045 E
50/50
3.5043.504
936262AD2-033 E
50/50
8.1968.196
958211AF2-115 C
50/50
2.892.89
941012AE2-092 E
50/50
15.99615.996
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.18821.188
WECLTFEXP_WEC->PJM
CLTF
0.0360.036
LAGNLTFEXP_LAGN->PJM
CLTF
1.2621.262
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.0933.093
NYPJM->LTFIMP_NY
CLTF
0.3520.352
TVALTFEXP_TVA->PJM
CLTF
0.9770.977
O66PJM->LTFIMP_O-066
CMTX_NF
4.4054.405
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
MECLTFEXP_MEC->PJM
CLTF
0.3740.374
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.2941.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4071.407
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6880.688
CPLELTFEXP_CPLE->PJM
CLTF
2.7182.718
SIGELTFEXP_SIGE->PJM
CLTF
0.020.02

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.38 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:677.52
MW Contribution:28.05
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.53 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:724.84
MW Contribution:30.42
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
50/50
30.2830.28
934622AD1-088 E
50/50
2.9962.996
934612AD1-087 E
Adder
1.8235294117647061.55
3151931BEARGRDN S1
50/50
21.41521.415
924302AB2-077 E O1
50/50
0.8940.894
958131AF2-107 C
50/50
4.7314.731
3147133PAMPLIN
50/50
1.3571.357
316322AB2-045 C
50/50
0.7820.782
927264AC1-222 E
Adder
1.91647058823529411.629
958132AF2-107 E
50/50
2.5922.592
925612AC1-036 E
50/50
0.8290.829
316237AB2-079 C O1
50/50
0.2190.219
924312AB2-078 E O1
50/50
0.8940.894
316238AB2-078 C O1
50/50
0.2190.219
926274AC1-105 E
Adder
1.40941176470588241.198
938821AE1-108 C
50/50
33.08633.086
964242AG1-285 E
50/50
6.2046.204
313527AB2-043 C
50/50
0.3520.352
924162AB2-060 E OP
50/50
3.0163.016
964792AG1-342 E
Adder
1.33764705882352941.137
3151911BEARGRDN G1
50/50
16.55416.554
933502AC2-165 E
50/50
22.78922.789
925785AC1-054 E
Adder
1.3870588235294121.179
959311AF2-222 C
50/50
16.79916.799
957482AF2-042 E
Adder
17.15411764705882214.581
934621AD1-088 C
50/50
6.2236.223
935172AD1-152 E
Adder
2.64470588235294152.248
946301AF1-294 C
50/50
4.7534.753
942461AE2-259 C
50/50
16.45516.455
938822AE1-108 E
50/50
15.78715.787
937482AD2-202 E
Adder
0.53411764705882360.454
961792AG1-021 E
50/50
1.971.97
3151921BEARGRDN G2
50/50
16.55416.554
941011AE2-092 C
50/50
23.99423.994
3147223TWITTYS
50/50
0.9190.919
959312AF2-222 E
50/50
11.25511.255
924022AB2-043 E O1
50/50
3.5343.534
316239AB2-077 C O1
50/50
0.2190.219
942462AE2-259 E
50/50
10.9710.97
964791AG1-342 C
Adder
2.00705882352941161.706
957481AF2-042 C
Adder
25.7317647058823521.872
924322AB2-079 E O1
50/50
0.8940.894
946302AF1-294 E
50/50
4.0254.025
943902AF1-058 E
Adder
0.62352941176470590.53
316131AB2-060 C
50/50
1.0471.047
3138533PONTONDP
50/50
0.8560.856
964241AG1-285 C
50/50
9.3069.306
316034AC1-036 C
50/50
0.2260.226
958212AF2-115 E
50/50
2.4622.462
962561AG1-105 C
Adder
5.197647058823534.418
936261AD2-033 C
50/50
12.29412.294
3144293JTRSVLE
50/50
0.5320.532
961791AG1-021 C
50/50
2.3122.312
962562AG1-105 E
Adder
3.4647058823529412.945
924032AB2-045 E
50/50
3.5043.504
936262AD2-033 E
50/50
8.1968.196
958211AF2-115 C
50/50
2.892.89
941012AE2-092 E
50/50
15.99615.996
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.0933.093
NYPJM->LTFIMP_NY
CLTF
0.3520.352
TVALTFEXP_TVA->PJM
CLTF
0.9770.977
O66PJM->LTFIMP_O-066
CMTX_NF
4.4054.405
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.18821.188
WECLTFEXP_WEC->PJM
CLTF
0.0360.036
LAGNLTFEXP_LAGN->PJM
CLTF
1.2621.262
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4071.407
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6880.688
CPLELTFEXP_CPLE->PJM
CLTF
2.7182.718
SIGELTFEXP_SIGE->PJM
CLTF
0.020.02
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
MECLTFEXP_MEC->PJM
CLTF
0.3740.374
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.2941.294

Details for 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:107.58 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:614.81
MW Contribution:16.61
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.99 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:645.76
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
Adder
-4.488235294117647-3.815
934622AD1-088 E
50/50
8.0788.078
934611AD1-087 C
50/50
1.9191.919
934612AD1-087 E
50/50
5.5365.536
3151611KERR 4
50/50
1.1131.113
927255AC1-221 E
50/50
3.413.41
924302AB2-077 E O1
50/50
1.321.32
3151621KERR 5
50/50
1.1131.113
316222AC1-221 C
50/50
1.3041.304
942752AE2-291 E
50/50
4.2094.209
966622AG1-532 E
Adder
0.29176470588235290.248
927264AC1-222 E
50/50
4.2714.271
925612AC1-036 E
50/50
0.6080.608
316237AB2-079 C O1
50/50
0.3240.324
924312AB2-078 E O1
50/50
1.321.32
316238AB2-078 C O1
50/50
0.3240.324
926274AC1-105 E
50/50
2.892.89
938821AE1-108 C
Adder
-8.042352941176471-6.836
964242AG1-285 E
50/50
10.84610.846
313527AB2-043 C
50/50
0.5090.509
924162AB2-060 E OP
50/50
3.9993.999
3151591KERR 2
50/50
1.1131.113
964792AG1-342 E
50/50
2.4822.482
932763AC2-100 E
50/50
2.2422.242
316283AC2-100 C
50/50
1.0191.019
3137643SOCKMAN
Adder
0.236470588235294130.201
937481AD2-202 C
50/50
0.5570.557
3151641KERR 7
50/50
1.1131.113
316205AC1-080 C
50/50
0.2470.247
316123AC1-075 C
50/50
0.740.74
3145723EMPORIA
Adder
0.136470588235294120.116
923573AB1-173 E OP
Adder
1.06470588235294120.905
919692AA2-053 E OP
Adder
1.31411764705882361.117
925785AC1-054 E
50/50
2.3712.371
959311AF2-222 C
Adder
9.9482352941176468.456
942751AE2-291 C
50/50
6.3136.313
957482AF2-042 E
50/50
57.29557.295
934621AD1-088 C
50/50
16.77816.778
935172AD1-152 E
50/50
7.5637.563
942461AE2-259 C
Adder
-11.085882352941177-9.423
937482AD2-202 E
50/50
1.621.62
3151581KERR 1
50/50
0.3970.397
3151601KERR 3
50/50
1.1131.113
3152661PLYWOOD A
50/50
1.3061.306
941011AE2-092 C
Adder
-7.384705882352941-6.277
966621AG1-532 C
Adder
0.437647058823529440.372
3147223TWITTYS
50/50
0.6740.674
959312AF2-222 E
Adder
6.66588235294117755.666
924022AB2-043 E O1
50/50
5.1075.107
316003AC1-222 C
50/50
1.0461.046
926024AC1-080 E
50/50
0.8510.851
316239AB2-077 C O1
50/50
0.3240.324
935171AD1-152 C
50/50
1.8391.839
964791AG1-342 C
50/50
3.7243.724
925997AC1-075 E
50/50
2.5662.566
957481AF2-042 C
50/50
85.94285.942
316088AB2-174 E
Adder
2.0917647058823531.778
923994AB2-040_E
Adder
1.99764705882352931.698
924322AB2-079 E O1
50/50
1.321.32
943902AF1-058 E
50/50
1.4231.423
946282AF1-292 E
Adder
0.32235294117647060.274
316129AC1-054 C
50/50
0.8410.841
316131AB2-060 C
50/50
1.3891.389
316118AC1-105 C
50/50
0.9880.988
946281AF1-292 C
Adder
0.48352941176470590.411
960082AF2-299 E
Adder
0.38941176470588240.331
3151541CLOVER2
50/50
19.33819.338
964241AG1-285 C
50/50
16.2716.27
316034AC1-036 C
50/50
0.1660.166
962561AG1-105 C
50/50
9.2429.242
960081AF2-299 C
Adder
0.58352941176470590.496
3151531CLOVER1
50/50
19.51919.519
936261AD2-033 C
Adder
5.2729411764705894.482
3151631KERR 6
50/50
1.1131.113
962562AG1-105 E
50/50
6.1616.161
316248AF1-058 C
50/50
0.3490.349
936262AD2-033 E
Adder
3.5152941176470592.988
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.6115.611
NYPJM->LTFIMP_NY
CLTF
0.2910.291
TVALTFEXP_TVA->PJM
CLTF
1.5461.546
O66PJM->LTFIMP_O-066
CMTX_NF
3.8923.892
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.50427.504
WECLTFEXP_WEC->PJM
CLTF
0.1510.151
LAGNLTFEXP_LAGN->PJM
CLTF
1.9781.978
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.2877.287
G-007PJM->LTFIMP_G-007
CMTX_NF
0.610.61
CPLELTFEXP_CPLE->PJM
CLTF
3.4573.457
SIGELTFEXP_SIGE->PJM
CLTF
0.0570.057
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.2860.286
MECLTFEXP_MEC->PJM
CLTF
0.9490.949
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6471.647

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.13 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3353.36
MW Contribution:29.71
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3493.11
MW Contribution:25.43
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
50/50
26.11526.115
316084AB2-161 E
Adder
5.26941176470588254.479
3145946PLYMOUTH TP
Adder
0.364705882352941160.31
933982AD1-022 E
Adder
5.3847058823529414.577
934622AD1-088 E
50/50
5.5555.555
934611AD1-087 C
50/50
1.5661.566
934612AD1-087 E
50/50
4.5174.517
927146AC1-208 E
Adder
4.5541176470588243.871
927255AC1-221 E
Adder
4.1411764705882363.52
932046AC2-012 E
50/50
14.50114.501
316017AA1-139 ULT1
50/50
1.2231.223
938531AE1-072 C
50/50
19.84719.847
958161AF2-110 C
Adder
1.49647058823529421.272
3152411Z1-086 GT1
50/50
15.81615.816
3152421Z1-086 GT2
50/50
15.81115.811
3145393UNCAMP
Adder
6.7635294117647065.749
933981AD1-022 C
Adder
9.8917647058823528.408
900672V4-068 E
Adder
0.402352941176470640.342
924302AB2-077 E O1
Adder
1.52117647058823541.293
938532AE1-072 E
50/50
10.34610.346
3146326AYDLETT TAP
50/50
1.5311.531
943461AF1-017 C
Adder
1.40235294117647061.192
316311AC2-079 C
Adder
5.9964705882352955.097
932596AC2-079 E
Adder
9.7835294117647078.316
3152431Z1-086 GT3
50/50
15.81115.811
3152441Z1-086 ST
50/50
27.53227.532
917122Z2-027 E
50/50
1.5121.512
920692AA2-178 E
Adder
4.6352941176470593.94
966622AG1-532 E
50/50
1.0851.085
3147133PAMPLIN
Adder
0.89882352941176480.764
922923AB1-081 E OP
Adder
4.20470588235294153.574
927264AC1-222 E
Adder
4.3282352941176473.679
316375AC2-012 C
50/50
1.4951.495
961611AG1-000B C
Adder
13.21058823529411611.229
313526AB2-022 C
50/50
0.4240.424
940541AE2-040 C
50/50
3.4343.434
940482AE2-033 E
50/50
13.01513.015
940481AE2-033 C
50/50
19.30519.305
923263AB1-132 E OP
Adder
7.0270588235294125.973
925612AC1-036 E
Adder
0.93294117647058830.793
924312AB2-078 E O1
Adder
1.52117647058823541.293
926274AC1-105 E
Adder
2.9882352941176472.54
926755AC1-161 E
50/50
14.89414.894
933291AC2-141 C
50/50
34.8934.89
925522AC1-027 E
50/50
1.3621.362
957872AF2-081 E
50/50
4.844.84
3145256KINGFORK
Adder
1.06588235294117650.906
3150921YORKTN3
Adder
6.2929411764705885.349
941102AE2-104 E
Adder
5.8305882352941184.956
316087AB2-174 C
50/50
1.3621.362
964242AG1-285 E
50/50
9.9189.918
926214AC1-099 E
Adder
1.36941176470588231.164
932632AC2-084 E
Adder
3.66588235294117663.116
924162AB2-060 E OP
Adder
4.8364705882352944.111
964792AG1-342 E
Adder
2.6435294117647062.247
932763AC2-100 E
Adder
2.80941176470588252.388
939411AE1-173 C
50/50
128.665128.665
913392Y1-086 E
50/50
2.4762.476
3137643SOCKMAN
Adder
0.81882352941176460.696
937481AD2-202 C
50/50
0.4540.454
919710AA2-057 E
Adder
4.49411764705882363.82
919152AA1-139 E1
50/50
4.6184.618
316018AA1-139 ULT2
50/50
1.2231.223
942342AE2-247 E
Adder
2.141.819
920042AA2-088 E OP
Adder
11.94941176470588210.157
934511AD1-075 C
Adder
9.507058823529418.081
934521AD1-076 C
Adder
13.81176470588235411.74
3145723EMPORIA
50/50
0.50.5
923573AB1-173 E OP
Adder
3.78941176470588253.221
919692AA2-053 E OP
Adder
4.8352941176470594.11
925785AC1-054 E
Adder
3.94000000000000043.349
959311AF2-222 C
Adder
17.79058823529411615.122
316263AC1-034 C
Adder
7.4894117647058826.366
939192AE1-149 E
Adder
6.3964705882352955.437
934065AD1-033 E
50/50
5.6715.671
939312AE1-162 E
Adder
1.37058823529411771.165
937226AE2-253 E
50/50
6.6066.606
316321Z2-027 C
50/50
0.410.41
3151031BRUNSWICKG2
50/50
12.28212.282
924517AB2-100 E2
50/50
3.3843.384
934501AD1-074 C
Adder
38.0305882352941232.326
957482AF2-042 E
50/50
46.62746.627
934621AD1-088 C
50/50
11.53711.537
935172AD1-152 E
50/50
6.6176.617
946301AF1-294 C
Adder
3.3517647058823532.849
961671AG1-007 C
Adder
1.05882352941176470.9
933292AC2-141 E
50/50
14.89414.894
316294AC1-161 C
50/50
5.7015.701
944602AF1-125 E
50/50
115.795115.795
916191Z1-068 C
50/50
0.0490.049
3145506HICKORY
50/50
2.4672.467
934576AD1-082 E
Adder
4.1988235294117653.569
957871AF2-081 C
50/50
11.29311.293
943612AF1-032 E
Adder
1.02823529411764710.874
940492AE2-034 E
Adder
3.4764705882352942.955
934522AD1-076 E
Adder
7.045.984
943172AE2-346 E
Adder
0.68588235294117650.583
918492AA1-063AE OP
Adder
4.65058823529411753.953
937482AD2-202 E
50/50
1.3221.322
917332KELFORD E
Adder
1.8635294117647061.584
925122AB2-169 E
Adder
6.4858823529411775.513
316274AC1-208 C
Adder
10.255294117647068.717
961792AG1-021 E
Adder
1.38941176470588231.181
917342Z2-044 E
Adder
0.6764705882352940.575
3151311EDGECMA
Adder
17.50705882352941214.881
940642AE2-051 E
50/50
17.4117.41
316388AE2-253 GEN
50/50
2.2212.221
919153AA1-139 E2
50/50
4.6184.618
943462AF1-017 E
Adder
2.2870588235294121.944
942341AE2-247 C
Adder
1.54941176470588231.317
958162AF2-110 E
Adder
2.38000000000000032.023
924516AB2-100 E1
50/50
3.3843.384
934512AD1-075 E
Adder
4.844.114
934502AD1-074 E
Adder
19.3616.456
966621AG1-532 C
50/50
1.6281.628
918512AA1-065 E OP
Adder
6.2505882352941175.313
3147223TWITTYS
Adder
1.03411764705882360.879
959312AF2-222 E
Adder
11.9210.132
924022AB2-043 E O1
Adder
5.9035294117647065.018
918532AA1-067 E
Adder
0.80588235294117660.685
3143316POE
Adder
1.30823529411764721.112
939191AE1-149 C
Adder
9.5941176470588238.155
901082W1-029 E
Adder
35.7705882352941230.405
316365AB2-100 C1
50/50
1.1231.123
926206AC1-098 E
Adder
4.1470588235294123.525
935171AD1-152 C
50/50
1.6091.609
964791AG1-342 C
Adder
3.96470588235294133.37
944581AF1-123 C
50/50
51.37451.374
316185AD1-033 C
50/50
1.391.39
941101AE2-104 C
Adder
3.66705882352941173.117
316320Y1-086 C
50/50
0.2480.248
3151041BRUNSWICKG3
50/50
12.28212.282
3151021BRUNSWICKG1
50/50
12.28212.282
957481AF2-042 C
50/50
69.9469.94
316088AB2-174 E
50/50
7.5427.542
316141AB2-099 E
Adder
0.28588235294117650.243
923994AB2-040_E
Adder
7.1047058823529416.039
924322AB2-079 E O1
Adder
1.52117647058823541.293
946302AF1-294 E
Adder
2.83882352941176472.413
961672AG1-007 E
Adder
0.60.51
943902AF1-058 E
Adder
1.42941176470588241.215
944012AF1-069 E
50/50
7.7257.725
316315AB2-025 C
50/50
0.4880.488
946282AF1-292 E
50/50
1.1981.198
3138533PONTONDP
Adder
0.60352941176470590.513
917512Z2-088 E OP1
Adder
5.5247058823529414.696
3151101ELIZAR3
50/50
3.6013.601
944582AF1-123 E
50/50
117.641117.641
944592AF1-124 E
50/50
118.067118.067
935112AD1-144 E
Adder
0.98941176470588230.841
316349AD2-085 C
Adder
3.5752941176470593.039
923832AB2-022 E
50/50
1.3981.398
963042AG1-153 E
50/50
12.48112.481
938772AE1-103 E
Adder
4.4858823529411773.813
916042Z1-036 E
Adder
32.1705882352941227.345
316023AB2-100 C2
50/50
1.1231.123
946281AF1-292 C
50/50
1.7971.797
960082AF2-299 E
50/50
1.4471.447
926071AC1-086 C
Adder
24.1447058823529420.523
3151541CLOVER2
50/50
15.75715.757
964241AG1-285 C
50/50
14.87614.876
958212AF2-115 E
Adder
1.73647058823529421.476
927021AC1-189 C
Adder
9.4905882352941178.067
962561AG1-105 C
Adder
9.9705882352941188.475
924152AB2-059 E OP
Adder
5.9564705882352945.063
944011AF1-069 C
50/50
19.88619.886
3151091ELIZAR2
50/50
3.4943.494
3151081ELIZAR1
50/50
3.5563.556
941591AE2-156 C
50/50
19.83519.835
944591AF1-124 C
50/50
51.55751.557
944601AF1-125 C
50/50
50.58350.583
316316AC1-027 C
50/50
0.3530.353
936666AD2-085 E
Adder
5.8329411764705884.958
963041AG1-153 C
50/50
8.3218.321
938771AE1-103 C
Adder
3.24823529411764732.761
3145413WATKINS
Adder
0.7717647058823530.656
960081AF2-299 C
50/50
2.1712.171
926072AC1-086 E
Adder
10.9894117647058819.341
3151531CLOVER1
50/50
15.90415.904
936261AD2-033 C
Adder
13.51176470588235311.485
961791AG1-021 C
Adder
1.63058823529411771.386
962562AG1-105 E
Adder
6.6470588235294125.65
939412AE1-173 E
50/50
85.77785.777
941032AE2-094 E
50/50
27.25927.259
941031AE2-094 C
50/50
60.86460.864
926662AC1-147 E
Adder
1.46588235294117641.246
916192Z1-068 E
50/50
2.1052.105
957492AF2-043 E
Adder
1.58117647058823541.344
923852AB2-025 E
50/50
1.3891.389
3151051BRUNSWICKS1
50/50
25.51625.516
961941AG1-037 C
Adder
0.5717647058823530.486
961942AG1-037 E
Adder
0.381176470588235340.324
936262AD2-033 E
Adder
9.0082352941176477.657
958211AF2-115 C
Adder
2.03764705882352941.732
934321AD1-056 C
Adder
7.126.052
934331AD1-057 C
Adder
3.9717647058823533.376
934332AD1-057 E
Adder
2.0682352941176471.758
934322AD1-056 E
Adder
3.86117647058823543.282
927022AC1-189 E
Adder
4.7282352941176474.019
925595AC1-034 E
Adder
5.65058823529411754.803
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
1.1651.165
MECLTFEXP_MEC->PJM
CLTF
3.8563.856
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.3016.301
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.47229.472
G-007PJM->LTFIMP_G-007
CMTX_NF
3.5513.551
CPLELTFEXP_CPLE->PJM
CLTF
13.22113.221
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.8122.81
NYPJM->LTFIMP_NY
CLTF
1.6611.661
TVALTFEXP_TVA->PJM
CLTF
6.2796.279
O66PJM->LTFIMP_O-066
CMTX_NF
22.61622.616
CBM South 2LTFEXP_CBM-S2->PJM
CBM
107.493107.493
WECLTFEXP_WEC->PJM
CLTF
0.6140.614
LAGNLTFEXP_LAGN->PJM
CLTF
8.048.04

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.34 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1336.88
MW Contribution:9.31
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:127.16 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1345.51
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
50/50
11.53811.538
316336AC2-165 C
Adder
-10.758823529411764-9.145
3145946PLYMOUTH TP
Adder
0.136470588235294120.116
933982AD1-022 E
Adder
2.01411764705882361.712
934622AD1-088 E
Adder
2.11.785
934612AD1-087 E
Adder
1.79882352941176471.529
927146AC1-208 E
Adder
1.72941176470588241.47
927255AC1-221 E
Adder
1.65176470588235281.404
932046AC2-012 E
Adder
5.2588235294117654.47
938531AE1-072 C
Adder
7.3705882352941176.265
958161AF2-110 C
Adder
0.53058823529411770.451
3152411Z1-086 GT1
50/50
7.0067.006
3152421Z1-086 GT2
50/50
7.0047.004
3145393UNCAMP
Adder
2.44352941176470572.077
933981AD1-022 C
Adder
3.73.145
900672V4-068 E
Adder
0.149411764705882360.127
924302AB2-077 E O1
Adder
0.54823529411764720.466
938532AE1-072 E
Adder
3.84235294117647053.266
3146326AYDLETT TAP
Adder
0.56823529411764710.483
943461AF1-017 C
Adder
0.454117647058823570.386
316311AC2-079 C
Adder
1.9682352941176471.673
932596AC2-079 E
Adder
3.2117647058823532.73
3152431Z1-086 GT3
50/50
7.0047.004
3152441Z1-086 ST
50/50
12.19612.196
917122Z2-027 E
Adder
0.55999999999999990.476
920692AA2-178 E
Adder
1.72705882352941181.468
966622AG1-532 E
Adder
0.40.34
922923AB1-081 E OP
Adder
1.63529411764705881.39
927264AC1-222 E
Adder
1.66470588235294131.415
940541AE2-040 C
Adder
1.25411764705882361.066
940482AE2-033 E
Adder
4.7611764705882354.047
940481AE2-033 C
Adder
7.0611764705882366.002
923263AB1-132 E OP
Adder
2.6305882352941182.236
925612AC1-036 E
Adder
0.30.255
924312AB2-078 E O1
Adder
0.54823529411764720.466
926274AC1-105 E
Adder
1.13764705882352950.967
938821AE1-108 C
Adder
-4.716470588235294-4.009
926755AC1-161 E
Adder
5.7376470588235294.877
933291AC2-141 C
Adder
13.44235294117647211.426
925522AC1-027 E
Adder
0.50.425
957872AF2-081 E
Adder
1.79882352941176471.529
3145256KINGFORK
Adder
0.367058823529411770.312
941102AE2-104 E
Adder
2.06588235294117651.756
964242AG1-285 E
Adder
3.57647058823529433.04
926214AC1-099 E
Adder
0.520.442
932632AC2-084 E
Adder
1.3917647058823531.183
924162AB2-060 E OP
Adder
1.71764705882352931.46
964792AG1-342 E
Adder
0.99058823529411770.842
932763AC2-100 E
Adder
1.12117647058823520.953
939411AE1-173 C
50/50
55.12655.126
913392Y1-086 E
Adder
0.91764705882352950.78
3137643SOCKMAN
Adder
0.30470588235294120.259
919710AA2-057 E
Adder
1.72588235294117661.467
919152AA1-139 E1
Adder
1.71529411764705891.458
942342AE2-247 E
Adder
0.69411764705882350.59
920042AA2-088 E OP
Adder
4.3847058823529413.727
934511AD1-075 C
Adder
3.55411764705882363.021
934521AD1-076 C
Adder
5.1635294117647064.389
3145723EMPORIA
Adder
0.18470588235294120.157
923573AB1-173 E OP
Adder
1.40588235294117661.195
919692AA2-053 E OP
Adder
1.80705882352941181.536
925785AC1-054 E
Adder
1.47764705882352951.256
959311AF2-222 C
Adder
5.57411764705882454.738
316263AC1-034 C
Adder
2.91411764705882352.477
934065AD1-033 E
Adder
2.10705882352941171.791
939312AE1-162 E
Adder
0.41294117647058820.351
937226AE2-253 E
Adder
2.4552941176470592.087
3151031BRUNSWICKG2
50/50
5.4215.421
924517AB2-100 E2
Adder
1.25176470588235311.064
934501AD1-074 C
Adder
14.2176470588235312.085
957482AF2-042 E
Adder
18.89411764705882416.06
934621AD1-088 C
Adder
4.3611764705882353.707
935172AD1-152 E
Adder
2.6258823529411772.232
961671AG1-007 C
Adder
0.410588235294117640.349
936162AD2-022 E
Adder
1.85294117647058831.575
933292AC2-141 E
Adder
5.7376470588235294.877
944602AF1-125 E
Adder
43.0952941176470636.631
3145506HICKORY
Adder
0.91764705882352950.78
957871AF2-081 C
Adder
4.1964705882352953.567
943612AF1-032 E
Adder
0.374117647058823550.318
940492AE2-034 E
Adder
1.2952941176470591.101
934522AD1-076 E
Adder
2.6317647058823532.237
943172AE2-346 E
Adder
0.255294117647058840.217
918492AA1-063AE OP
Adder
1.72705882352941181.468
937482AD2-202 E
Adder
0.52588235294117650.447
917332KELFORD E
Adder
0.70117647058823530.596
925122AB2-169 E
Adder
2.4564705882352942.088
316274AC1-208 C
Adder
3.8952941176470593.311
917342Z2-044 E
Adder
0.26117647058823530.222
3151311EDGECMA
Adder
6.8129411764705895.791
941011AE2-092 C
Adder
-4.452941176470588-3.785
940642AE2-051 E
50/50
7.6927.692
919153AA1-139 E2
Adder
1.71529411764705891.458
943462AF1-017 E
Adder
0.74117647058823530.63
942341AE2-247 C
Adder
0.50235294117647060.427
958162AF2-110 E
Adder
0.84352941176470590.717
924516AB2-100 E1
Adder
1.25176470588235311.064
934512AD1-075 E
Adder
1.80941176470588251.538
934502AD1-074 E
Adder
7.237647058823536.152
966621AG1-532 C
Adder
0.60117647058823530.511
918512AA1-065 E OP
Adder
2.34000000000000031.989
3147223TWITTYS
Adder
0.332941176470588240.283
959312AF2-222 E
Adder
3.73411764705882383.174
924022AB2-043 E O1
Adder
2.11764705882352941.8
918532AA1-067 E
Adder
0.30941176470588240.263
936161AD2-022 C
Adder
3.0882352941176472.625
901082W1-029 E
Adder
13.19764705882352911.218
926206AC1-098 E
Adder
1.57411764705882361.338
964791AG1-342 C
Adder
1.48470588235294131.262
944581AF1-123 C
Adder
19.11999999999999716.252
941101AE2-104 C
Adder
1.31.105
3151041BRUNSWICKG3
50/50
5.4215.421
3151021BRUNSWICKG1
50/50
5.4215.421
957481AF2-042 C
Adder
28.3424.089
316088AB2-174 E
Adder
2.7941176470588242.375
316141AB2-099 E
Adder
0.107058823529411760.091
923994AB2-040_E
Adder
2.63647058823529432.241
924322AB2-079 E O1
Adder
0.54823529411764720.466
961672AG1-007 E
Adder
0.232941176470588260.198
943902AF1-058 E
Adder
0.55294117647058830.47
944012AF1-069 E
50/50
3.4483.448
946282AF1-292 E
Adder
0.44235294117647060.376
917512Z2-088 E OP1
Adder
2.1352941176470591.815
944582AF1-123 E
Adder
43.7823529411764837.215
944592AF1-124 E
Adder
43.9411764705882437.35
935112AD1-144 E
Adder
0.339999999999999970.289
316349AD2-085 C
Adder
1.15882352941176480.985
923832AB2-022 E
Adder
0.51764705882352950.44
963042AG1-153 E
50/50
5.5095.509
938772AE1-103 E
Adder
1.61529411764705881.373
916042Z1-036 E
Adder
11.93411764705882510.144
946281AF1-292 C
Adder
0.66352941176470580.564
960082AF2-299 E
Adder
0.53411764705882360.454
926071AC1-086 C
Adder
9.037647058823537.682
964241AG1-285 C
Adder
5.3647058823529414.56
927021AC1-189 C
Adder
3.66117647058823573.112
962561AG1-105 C
Adder
3.70941176470588243.153
924152AB2-059 E OP
Adder
2.31764705882352961.97
936172AD2-023 E
Adder
0.97764705882352940.831
944011AF1-069 C
50/50
8.8768.876
941591AE2-156 C
Adder
7.202352941176476.122
944591AF1-124 C
Adder
19.18823529411764616.31
944601AF1-125 C
Adder
18.82588235294117516.002
936666AD2-085 E
Adder
1.89058823529411771.607
963041AG1-153 C
50/50
3.6733.673
938771AE1-103 C
Adder
1.16941176470588240.994
3145413WATKINS
Adder
0.279999999999999970.238
960081AF2-299 C
Adder
0.80117647058823540.681
926072AC1-086 E
Adder
4.11294117647058853.496
936261AD2-033 C
Adder
4.2364705882352943.601
962562AG1-105 E
Adder
2.4729411764705882.102
936171AD2-023 C
Adder
1.80117647058823521.531
939412AE1-173 E
50/50
36.75136.751
941032AE2-094 E
50/50
12.16712.167
941031AE2-094 C
50/50
27.16527.165
926662AC1-147 E
Adder
0.53176470588235290.452
916192Z1-068 E
Adder
0.77294117647058820.657
957492AF2-043 E
Adder
0.57529411764705880.489
923852AB2-025 E
Adder
0.50705882352941180.431
3151051BRUNSWICKS1
50/50
11.26311.263
961941AG1-037 C
Adder
0.212941176470588240.181
961942AG1-037 E
Adder
0.14235294117647060.121
936262AD2-033 E
Adder
2.8247058823529412.401
934321AD1-056 C
Adder
2.72588235294117662.317
934331AD1-057 C
Adder
1.52117647058823541.293
934332AD1-057 E
Adder
0.7917647058823530.673
934322AD1-056 E
Adder
1.47882352941176461.257
927022AC1-189 E
Adder
1.8235294117647061.55
925595AC1-034 E
Adder
2.19764705882352951.868
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.0379.037
NYPJM->LTFIMP_NY
CLTF
0.5140.514
TVALTFEXP_TVA->PJM
CLTF
2.4942.494
O66PJM->LTFIMP_O-066
CMTX_NF
6.9576.957
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.69643.696
WECLTFEXP_WEC->PJM
CLTF
0.2390.239
LAGNLTFEXP_LAGN->PJM
CLTF
3.2073.207
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.53211.532
G-007PJM->LTFIMP_G-007
CMTX_NF
1.0921.092
CPLELTFEXP_CPLE->PJM
CLTF
5.3965.396
SIGELTFEXP_SIGE->PJM
CLTF
0.0910.091
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.4480.448
MECLTFEXP_MEC->PJM
CLTF
1.5141.514
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5712.571

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:110.46 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3557.23
MW Contribution:37.07
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:116.33 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3746.4
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
50/50
27.34927.349
316084AB2-161 E
Adder
7.535294117647066.405
316336AC2-165 C
Adder
12.31647058823529410.469
3145946PLYMOUTH TP
Adder
0.455294117647058850.387
933982AD1-022 E
Adder
6.6964705882352955.692
934622AD1-088 E
Adder
6.3070588235294115.361
934612AD1-087 E
Adder
4.9741176470588234.228
927146AC1-208 E
Adder
5.3941176470588244.585
932046AC2-012 E
50/50
19.14419.144
935161AD1-151 C
Adder
20.16470588235294417.14
316017AA1-139 ULT1
50/50
1.5871.587
938531AE1-072 C
Adder
25.73882352941176421.878
958161AF2-110 C
Adder
1.9682352941176471.673
3152411Z1-086 GT1
50/50
16.1716.17
3152421Z1-086 GT2
50/50
16.16516.165
3145393UNCAMP
Adder
8.6294117647058827.335
933981AD1-022 C
Adder
12.310.455
900672V4-068 E
Adder
0.49764705882352940.423
924302AB2-077 E O1
Adder
1.78470588235294111.517
316233AE1-074 C
Adder
3.3858823529411772.878
935162AD1-151 E
Adder
13.44352941176470611.427
938532AE1-072 E
Adder
13.4176470588235311.405
3146326AYDLETT TAP
Adder
1.98470588235294131.687
943461AF1-017 C
Adder
1.90235294117647061.617
316311AC2-079 C
Adder
8.1047058823529426.889
932596AC2-079 E
Adder
13.22352941176470711.24
3152431Z1-086 GT3
50/50
16.16516.165
3152441Z1-086 ST
50/50
28.14828.148
917122Z2-027 E
Adder
1.95294117647058821.66
920692AA2-178 E
Adder
5.8388235294117654.963
966622AG1-532 E
Adder
1.28941176470588251.096
316375AC2-012 C
50/50
1.9741.974
961611AG1-000B C
Adder
20.99058823529411617.842
940541AE2-040 C
Adder
4.0705882352941173.46
940482AE2-033 E
Adder
15.43294117647058913.118
940481AE2-033 C
Adder
22.89176470588235219.458
923263AB1-132 E OP
Adder
8.3705882352941187.115
925612AC1-036 E
Adder
1.15058823529411770.978
924312AB2-078 E O1
Adder
1.78470588235294111.517
938552AE1-074 E
Adder
1.70588235294117641.45
926755AC1-161 E
50/50
19.3819.38
933291AC2-141 C
50/50
45.445.4
925522AC1-027 E
50/50
1.7851.785
957872AF2-081 E
50/50
6.286.28
3145256KINGFORK
Adder
1.44705882352941171.23
3150921YORKTN3
Adder
157.07176470588234133.511
316160AE1-175 E
Adder
1.46117647058823531.242
941102AE2-104 E
Adder
7.6705882352941176.52
938562AE1-075 E
Adder
1.3717647058823531.166
964242AG1-285 E
Adder
11.584705882352949.847
926214AC1-099 E
Adder
1.63058823529411771.386
932632AC2-084 E
Adder
4.3635294117647063.709
924162AB2-060 E OP
Adder
5.7141176470588244.857
939411AE1-173 C
50/50
140.92140.92
940432AE2-027 E
Adder
10.382352941176478.825
934012AD1-025 E
Adder
12.67294117647058910.772
913392Y1-086 E
Adder
3.2023529411764712.722
933502AC2-165 E
Adder
7.88941176470588356.706
3137643SOCKMAN
Adder
0.97647058823529410.83
924814AB2-134 E
Adder
16.03411764705882413.629
919152AA1-139 E1
50/50
5.9935.993
316018AA1-139 ULT2
50/50
1.5871.587
942342AE2-247 E
Adder
2.9035294117647062.468
920042AA2-088 E OP
Adder
14.8552941176470612.627
934511AD1-075 C
Adder
11.86588235294117810.086
934521AD1-076 C
Adder
17.2376470588235314.652
3145723EMPORIA
Adder
0.59411764705882350.505
923573AB1-173 E OP
Adder
4.5117647058823533.835
919692AA2-053 E OP
Adder
5.797647058823534.928
925785AC1-054 E
Adder
4.61294117647058853.921
959311AF2-222 C
Adder
22.19764705882352718.868
942001AE2-212 C
Adder
2.7023529411764712.297
939192AE1-149 E
Adder
9.522352941176478.094
934065AD1-033 E
50/50
7.3827.382
939312AE1-162 E
Adder
1.98117647058823531.684
937226AE2-253 E
50/50
8.5778.577
3151031BRUNSWICKG2
50/50
12.59212.592
958502AF2-144 E
Adder
1.58117647058823541.344
924517AB2-100 E2
Adder
4.0211764705882363.418
934501AD1-074 C
Adder
47.46117647058823540.342
957482AF2-042 E
Adder
50.7517647058823643.139
934621AD1-088 C
Adder
13.09882352941176511.134
935172AD1-152 E
Adder
7.3070588235294126.211
933292AC2-141 E
50/50
19.3819.38
316294AC1-161 C
50/50
7.4197.419
944602AF1-125 E
50/50
150.574150.574
916191Z1-068 C
50/50
0.0640.064
3145506HICKORY
50/50
3.2063.206
934576AD1-082 E
Adder
6.0047058823529415.104
957871AF2-081 C
50/50
14.65414.654
943612AF1-032 E
Adder
1.34352941176470591.142
940492AE2-034 E
Adder
4.383.723
934522AD1-076 E
Adder
8.7858823529411767.468
943172AE2-346 E
Adder
0.84117647058823530.715
918492AA1-063AE OP
Adder
5.6364705882352944.791
937482AD2-202 E
Adder
1.4552941176470591.237
917332KELFORD E
Adder
2.26000000000000021.921
925122AB2-169 E
Adder
7.9211764705882356.733
316274AC1-208 C
Adder
12.14823529411764710.326
940642AE2-051 E
50/50
18.23318.233
316388AE2-253 GEN
50/50
2.8852.885
919153AA1-139 E2
50/50
5.9935.993
943462AF1-017 E
Adder
3.1035294117647062.638
942341AE2-247 C
Adder
2.10235294117647081.787
958162AF2-110 E
Adder
3.1317647058823532.662
924516AB2-100 E1
Adder
4.0211764705882363.418
934512AD1-075 E
Adder
6.0400000000000015.134
934502AD1-074 E
Adder
24.16117647058823420.537
966621AG1-532 C
Adder
1.93411764705882351.644
918512AA1-065 E OP
Adder
7.6929411764705886.539
3147223TWITTYS
Adder
1.2764705882352941.085
959312AF2-222 E
Adder
14.87294117647058812.642
924022AB2-043 E O1
Adder
6.945.899
3143316POE
Adder
1.8364705882352941.561
939191AE1-149 C
Adder
14.28235294117647112.14
901082W1-029 E
Adder
46.16941176470588539.244
926206AC1-098 E
Adder
4.9364705882352944.196
942002AE2-212 E
Adder
1.80117647058823521.531
940431AE2-027 C
Adder
15.5729411764705913.237
944581AF1-123 C
50/50
66.80566.805
316185AD1-033 C
50/50
1.8091.809
941101AE2-104 C
Adder
4.8247058823529424.101
3151041BRUNSWICKG3
50/50
12.59212.592
3151021BRUNSWICKG1
50/50
12.59212.592
957481AF2-042 C
Adder
76.1282352941176664.709
316088AB2-174 E
Adder
8.9729411764705887.627
316141AB2-099 E
Adder
0.350588235294117640.298
923994AB2-040_E
Adder
8.4588235294117657.19
924322AB2-079 E O1
Adder
1.78470588235294111.517
944012AF1-069 E
50/50
7.8517.851
946282AF1-292 E
Adder
1.4235294117647061.21
3151101ELIZAR3
50/50
4.7444.744
944582AF1-123 E
50/50
152.975152.975
944592AF1-124 E
50/50
153.529153.529
935112AD1-144 E
Adder
1.34352941176470591.142
316349AD2-085 C
Adder
4.8517647058823534.124
923832AB2-022 E
Adder
1.8082352941176471.537
963042AG1-153 E
50/50
12.79612.796
938772AE1-103 E
Adder
5.7541176470588234.891
916042Z1-036 E
Adder
41.0352941176470634.88
946281AF1-292 C
Adder
2.13411764705882371.814
960082AF2-299 E
Adder
1.71882352941176491.461
926071AC1-086 C
Adder
28.76235294117647424.448
964241AG1-285 C
Adder
17.3776470588235314.771
944011AF1-069 C
50/50
20.20820.208
3151091ELIZAR2
50/50
4.6034.603
3151081ELIZAR1
50/50
4.6844.684
941591AE2-156 C
50/50
26.1726.17
925332AB2-190 E
Adder
9.9635294117647058.469
944591AF1-124 C
50/50
67.04267.042
944601AF1-125 C
50/50
65.77665.776
316316AC1-027 C
50/50
0.4630.463
927226AC1-216 E
Adder
9.7882352941176488.32
936666AD2-085 E
Adder
7.9152941176470596.728
962962AG1-145 E
Adder
1.77058823529411761.505
963041AG1-153 C
50/50
8.5318.531
938771AE1-103 C
Adder
4.1670588235294123.542
3145413WATKINS
Adder
0.97764705882352940.831
960081AF2-299 C
Adder
2.5788235294117652.192
926072AC1-086 E
Adder
13.09058823529411911.127
936261AD2-033 C
Adder
16.90117647058823614.366
939412AE1-173 E
50/50
93.94693.946
941032AE2-094 E
50/50
27.70127.701
941031AE2-094 C
50/50
61.84961.849
926662AC1-147 E
Adder
1.93529411764705881.645
916192Z1-068 E
50/50
2.7572.757
957492AF2-043 E
Adder
2.06705882352941161.757
923852AB2-025 E
Adder
1.64705882352941171.4
3151051BRUNSWICKS1
50/50
26.16126.161
923862AB2-026 E
Adder
1.60941176470588251.368
961941AG1-037 C
Adder
0.70117647058823530.596
961942AG1-037 E
Adder
0.46705882352941180.397
936262AD2-033 E
Adder
11.2670588235294129.577
316303AF2-085
50/50
5.9055.905
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
1.2141.214
MECLTFEXP_MEC->PJM
CLTF
4.0484.048
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.96.9
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.17830.178
G-007PJM->LTFIMP_G-007
CMTX_NF
4.4674.467
CPLELTFEXP_CPLE->PJM
CLTF
14.4814.48
SIGELTFEXP_SIGE->PJM
CLTF
0.2450.245
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.34224.342
NYPJM->LTFIMP_NY
CLTF
2.0972.097
TVALTFEXP_TVA->PJM
CLTF
6.7616.761
O66PJM->LTFIMP_O-066
CMTX_NF
28.45628.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
117.126117.126
WECLTFEXP_WEC->PJM
CLTF
0.6330.633
LAGNLTFEXP_LAGN->PJM
CLTF
8.658.65

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.69 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4423.71
MW Contribution:58.05
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:114.82 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4673.36
MW Contribution:41.97
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
Adder
-21.288235294117648-18.095
934622AD1-088 E
50/50
11.49611.496
934611AD1-087 C
50/50
3.233.23
934612AD1-087 E
50/50
9.3199.319
3151611KERR 4
50/50
1.991.99
927255AC1-221 E
50/50
7.6147.614
938531AE1-072 C
Adder
-16.06705882352941-13.657
3152411Z1-086 GT1
50/50
32.42432.424
3152421Z1-086 GT2
50/50
32.41332.413
924302AB2-077 E O1
50/50
2.6052.605
3151621KERR 5
50/50
1.991.99
316222AC1-221 C
50/50
2.9122.912
942752AE2-291 E
Adder
8.6882352941176467.385
3152431Z1-086 GT3
50/50
32.41332.413
3152441Z1-086 ST
50/50
56.44256.442
3147133PAMPLIN
50/50
1.8091.809
927264AC1-222 E
50/50
8.2018.201
925612AC1-036 E
50/50
1.8171.817
316237AB2-079 C O1
50/50
0.6390.639
924312AB2-078 E O1
50/50
2.6052.605
316238AB2-078 C O1
50/50
0.6390.639
926274AC1-105 E
50/50
5.5465.546
933291AC2-141 C
Adder
-31.96117647058824-27.167
964242AG1-285 E
50/50
19.04819.048
313527AB2-043 C
50/50
1.011.01
924162AB2-060 E OP
50/50
8.3338.333
3151591KERR 2
50/50
1.991.99
964792AG1-342 E
50/50
4.8064.806
932763AC2-100 E
50/50
5.1295.129
316283AC2-100 C
50/50
2.3312.331
937481AD2-202 C
50/50
0.9370.937
3151641KERR 7
50/50
1.991.99
316240AF1-291 C
Adder
-1.863529411764706-1.584
944641AF1-129 C
Adder
-87.13882352941177-74.068
925785AC1-054 E
Adder
3.75647058823529443.193
959311AF2-222 C
50/50
34.76234.762
942751AE2-291 C
Adder
13.03294117647058811.078
942001AE2-212 C
Adder
-1.9541176470588235-1.661
3151031BRUNSWICKG2
50/50
25.63425.634
957482AF2-042 E
50/50
98.33198.331
934621AD1-088 C
50/50
23.87723.877
935172AD1-152 E
50/50
13.31413.314
946301AF1-294 C
Adder
6.3505882352941185.398
942461AE2-259 C
Adder
16.0152941176470613.613
936162AD2-022 E
Adder
7.4470588235294126.33
937482AD2-202 E
50/50
2.7272.727
3151581KERR 1
50/50
0.7110.711
3151601KERR 3
50/50
1.991.99
961792AG1-021 E
Adder
2.6317647058823532.237
3152661PLYWOOD A
50/50
2.4812.481
3147223TWITTYS
50/50
2.0152.015
959312AF2-222 E
50/50
23.29123.291
924022AB2-043 E O1
50/50
10.1410.14
316003AC1-222 C
50/50
2.0082.008
926024AC1-080 E
Adder
1.71529411764705891.458
936161AD2-022 C
Adder
12.41176470588235310.55
957601AF2-054 C
Adder
-1.72-1.462
316239AB2-077 C O1
50/50
0.6390.639
935171AD1-152 C
50/50
3.2363.236
942462AE2-259 E
Adder
10.6764705882352939.075
964791AG1-342 C
50/50
7.2097.209
925997AC1-075 E
Adder
5.1705882352941174.395
3151041BRUNSWICKG3
50/50
25.63425.634
3151021BRUNSWICKG1
50/50
25.63425.634
957481AF2-042 C
50/50
147.496147.496
924322AB2-079 E O1
50/50
2.6052.605
946302AF1-294 E
Adder
5.377647058823534.571
943902AF1-058 E
50/50
2.7082.708
24401205PINNACLE
Adder
1.62588235294117631.382
944012AF1-069 E
50/50
15.22215.222
316131AB2-060 C
50/50
2.8942.894
3138533PONTONDP
Adder
1.14470588235294120.973
316118AC1-105 C
50/50
1.8951.895
963042AG1-153 E
50/50
26.04926.049
3151541CLOVER2
50/50
32.52432.524
964241AG1-285 C
50/50
28.57228.572
316034AC1-036 C
50/50
0.4960.496
958212AF2-115 E
Adder
3.2894117647058822.796
962561AG1-105 C
50/50
17.96517.965
936172AD2-023 E
Adder
3.9305882352941183.341
944011AF1-069 C
50/50
39.18539.185
963041AG1-153 C
50/50
17.36617.366
3151531CLOVER1
50/50
32.82832.828
936261AD2-033 C
50/50
24.11624.116
3151631KERR 6
50/50
1.991.99
961791AG1-021 C
Adder
3.08941176470588232.626
962562AG1-105 E
50/50
11.97711.977
924032AB2-045 E
Adder
1.26941176470588221.079
316248AF1-058 C
50/50
0.6640.664
936171AD2-023 C
Adder
7.246.154
941032AE2-094 E
50/50
53.71353.713
941031AE2-094 C
50/50
119.928119.928
3151051BRUNSWICKS1
50/50
53.25453.254
936262AD2-033 E
50/50
16.07816.078
958211AF2-115 C
Adder
3.86117647058823543.282
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.04159.041
G-007PJM->LTFIMP_G-007
CMTX_NF
4.1284.128
CPLELTFEXP_CPLE->PJM
CLTF
19.79519.795
SIGELTFEXP_SIGE->PJM
CLTF
0.4430.443
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
2.2642.264
MECLTFEXP_MEC->PJM
CLTF
7.1897.189
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.4399.439
CBM South 2LTFEXP_CBM-S2->PJM
CBM
169.426169.426
WECLTFEXP_WEC->PJM
CLTF
1.2081.208
LAGNLTFEXP_LAGN->PJM
CLTF
13.6813.68
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.12440.124
NYPJM->LTFIMP_NY
CLTF
1.8831.883
TVALTFEXP_TVA->PJM
CLTF
10.7110.71
O66PJM->LTFIMP_O-066
CMTX_NF
26.2626.26

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.0 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2588.61
MW Contribution:23.85
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.54 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2748.4
MW Contribution:20.56
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
50/50
26.4726.47
3145946PLYMOUTH TP
Adder
0.24117647058823530.205
933982AD1-022 E
Adder
3.52470588235294142.996
934622AD1-088 E
50/50
4.4114.411
934611AD1-087 C
50/50
1.2361.236
934612AD1-087 E
50/50
3.5653.565
927146AC1-208 E
Adder
3.14470588235294152.673
927255AC1-221 E
Adder
3.2152941176470592.733
932046AC2-012 E
50/50
12.1712.17
316017AA1-139 ULT1
50/50
1.0281.028
938531AE1-072 C
50/50
16.39816.398
3152411Z1-086 GT1
50/50
12.45512.455
3152421Z1-086 GT2
50/50
12.4512.45
3145393UNCAMP
Adder
3.8517647058823533.274
933981AD1-022 C
Adder
6.4741176470588245.503
900672V4-068 E
Adder
0.254117647058823560.216
924302AB2-077 E O1
Adder
1.18705882352941171.009
938532AE1-072 E
50/50
8.5488.548
3146326AYDLETT TAP
Adder
1.25647058823529421.068
3152431Z1-086 GT3
50/50
12.4512.45
3152441Z1-086 ST
50/50
21.68121.681
917122Z2-027 E
Adder
1.1117647058823530.945
920692AA2-178 E
Adder
3.0870588235294122.624
966622AG1-532 E
Adder
0.76941176470588240.654
3147133PAMPLIN
Adder
0.740.629
922923AB1-081 E OP
Adder
2.9811764705882352.534
927264AC1-222 E
Adder
3.3870588235294122.879
316375AC2-012 C
50/50
1.2551.255
940541AE2-040 C
Adder
2.4364705882352942.071
940482AE2-033 E
Adder
9.2211764705882357.838
940481AE2-033 C
Adder
13.6776470588235311.626
923263AB1-132 E OP
Adder
4.8517647058823534.124
925612AC1-036 E
Adder
0.74705882352941180.635
924312AB2-078 E O1
Adder
1.18705882352941171.009
926274AC1-105 E
Adder
2.3364705882352941.986
926755AC1-161 E
50/50
37.13537.135
933291AC2-141 C
50/50
86.99486.994
925522AC1-027 E
50/50
1.1581.158
957872AF2-081 E
50/50
4.0684.068
964242AG1-285 E
Adder
7.846.664
926214AC1-099 E
Adder
0.93529411764705890.795
932632AC2-084 E
Adder
2.50352941176470622.128
924162AB2-060 E OP
Adder
3.78117647058823543.214
964792AG1-342 E
Adder
2.06588235294117651.756
932763AC2-100 E
Adder
2.1788235294117651.852
939411AE1-173 C
50/50
86.92186.921
913392Y1-086 E
Adder
1.8917647058823531.608
3137643SOCKMAN
Adder
0.56941176470588240.484
937481AD2-202 C
50/50
0.3590.359
919710AA2-057 E
Adder
3.1364705882352942.666
919152AA1-139 E1
50/50
3.8823.882
316018AA1-139 ULT2
50/50
1.0281.028
920042AA2-088 E OP
Adder
7.3835294117647066.276
934511AD1-075 C
Adder
6.2764705882352945.335
934521AD1-076 C
Adder
9.1176470588235297.75
3145723EMPORIA
Adder
0.352941176470588260.3
923573AB1-173 E OP
Adder
2.65411764705882322.256
919692AA2-053 E OP
Adder
3.30000000000000032.805
925785AC1-054 E
Adder
2.882.448
959311AF2-222 C
Adder
14.27882352941176512.137
316263AC1-034 C
Adder
5.31058823529411854.514
934065AD1-033 E
50/50
5.0045.004
937226AE2-253 E
50/50
5.6435.643
3151031BRUNSWICKG2
50/50
9.6689.668
924517AB2-100 E2
Adder
2.3717647058823532.016
934501AD1-074 C
Adder
25.10470588235294221.339
957482AF2-042 E
50/50
36.84236.842
934621AD1-088 C
50/50
9.1619.161
935172AD1-152 E
Adder
5.2058823529411774.425
946301AF1-294 C
Adder
2.73529411764705932.325
942461AE2-259 C
Adder
6.5341176470588245.554
961671AG1-007 C
Adder
0.73882352941176480.628
933292AC2-141 E
50/50
37.13537.135
316294AC1-161 C
50/50
14.21614.216
944602AF1-125 E
50/50
102.879102.879
916191Z1-068 C
50/50
0.0420.042
3145506HICKORY
50/50
2.1612.161
957871AF2-081 C
50/50
9.4939.493
940492AE2-034 E
Adder
2.3152941176470591.968
934522AD1-076 E
Adder
4.6470588235294123.95
943172AE2-346 E
Adder
0.440.374
918492AA1-063AE OP
Adder
3.0882352941176472.625
937482AD2-202 E
50/50
1.0431.043
917332KELFORD E
Adder
1.2282352941176471.044
925122AB2-169 E
Adder
4.3388235294117653.688
316274AC1-208 C
Adder
7.0835294117647066.021
961792AG1-021 E
Adder
1.13294117647058810.963
917342Z2-044 E
Adder
0.475294117647058870.404
3151311EDGECMA
Adder
12.4152941176470610.553
940642AE2-051 E
50/50
17.64717.647
316388AE2-253 GEN
50/50
1.8981.898
919153AA1-139 E2
50/50
3.8823.882
924516AB2-100 E1
Adder
2.3717647058823532.016
934512AD1-075 E
Adder
3.19529411764705932.716
934502AD1-074 E
Adder
12.7810.863
966621AG1-532 C
Adder
1.15411764705882350.981
918512AA1-065 E OP
Adder
3.98941176470588273.391
3147223TWITTYS
Adder
0.82823529411764710.704
959312AF2-222 E
Adder
9.5670588235294118.132
924022AB2-043 E O1
Adder
4.6082352941176473.917
918532AA1-067 E
Adder
0.54705882352941180.465
3143316POE
Adder
0.80823529411764720.687
901082W1-029 E
Adder
23.54352941176470520.012
957601AF2-054 C
Adder
-1.2505882352941176-1.063
926206AC1-098 E
Adder
2.8317647058823532.407
942462AE2-259 E
Adder
4.3564705882352943.703
964791AG1-342 C
Adder
3.09882352941176452.634
944581AF1-123 C
50/50
45.64445.644
316185AD1-033 C
50/50
1.2261.226
3151041BRUNSWICKG3
50/50
9.6689.668
3151021BRUNSWICKG1
50/50
9.6689.668
957481AF2-042 C
50/50
55.26355.263
316088AB2-174 E
Adder
5.3035294117647064.508
316141AB2-099 E
Adder
0.183529411764705890.156
923994AB2-040_E
Adder
4.9776470588235294.231
924322AB2-079 E O1
Adder
1.18705882352941171.009
946302AF1-294 E
Adder
2.3164705882352941.969
961672AG1-007 E
Adder
0.41882352941176470.356
943902AF1-058 E
Adder
1.11882352941176480.951
944012AF1-069 E
50/50
6.0886.088
946282AF1-292 E
Adder
0.84941176470588230.722
3138533PONTONDP
Adder
0.49294117647058820.419
917512Z2-088 E OP1
Adder
3.83294117647058833.258
3151101ELIZAR3
50/50
3.0693.069
944582AF1-123 E
50/50
104.52104.52
944592AF1-124 E
50/50
104.898104.898
923832AB2-022 E
Adder
1.06823529411764720.908
963042AG1-153 E
50/50
9.8259.825
938772AE1-103 E
Adder
2.50941176470588222.133
916042Z1-036 E
Adder
21.67647058823529718.425
946281AF1-292 C
Adder
1.27411764705882361.083
960082AF2-299 E
Adder
1.02588235294117650.872
926071AC1-086 C
Adder
16.6705882352941214.17
3151541CLOVER2
50/50
12.43612.436
964241AG1-285 C
Adder
11.7588235294117649.995
958212AF2-115 E
Adder
1.41647058823529411.204
927021AC1-189 C
Adder
6.5388235294117655.558
962561AG1-105 C
Adder
7.7917647058823536.623
924152AB2-059 E OP
Adder
4.2235294117647063.59
944011AF1-069 C
50/50
15.67315.673
3151091ELIZAR2
50/50
2.9782.978
3151081ELIZAR1
50/50
3.033.03
941591AE2-156 C
50/50
16.7516.75
944591AF1-124 C
50/50
45.80645.806
944601AF1-125 C
50/50
44.94144.941
316316AC1-027 C
50/50
0.3010.301
963041AG1-153 C
50/50
6.556.55
938771AE1-103 C
Adder
1.81647058823529431.544
3145413WATKINS
Adder
0.451764705882352960.384
960081AF2-299 C
Adder
1.541.309
926072AC1-086 E
Adder
7.5870588235294126.449
3151531CLOVER1
50/50
12.55212.552
936261AD2-033 C
Adder
10.7294117647058829.12
961791AG1-021 C
Adder
1.33058823529411761.131
962562AG1-105 E
Adder
5.1941176470588244.415
939412AE1-173 E
50/50
57.94757.947
941032AE2-094 E
50/50
21.48321.483
941031AE2-094 C
50/50
47.96747.967
926662AC1-147 E
Adder
1.23058823529411781.046
916192Z1-068 E
50/50
1.7941.794
923852AB2-025 E
Adder
0.98588235294117640.838
3151051BRUNSWICKS1
50/50
20.08620.086
961941AG1-037 C
Adder
0.367058823529411770.312
961942AG1-037 E
Adder
0.244705882352941160.208
936262AD2-033 E
Adder
7.1529411764705896.08
958211AF2-115 C
Adder
1.6635294117647061.414
934321AD1-056 C
Adder
4.99411764705882364.245
934331AD1-057 C
Adder
2.78588235294117632.368
934332AD1-057 E
Adder
1.45058823529411771.233
934322AD1-056 E
Adder
2.70941176470588242.303
927022AC1-189 E
Adder
3.25764705882352962.769
925595AC1-034 E
Adder
4.00588235294117643.405
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.65881.658
WECLTFEXP_WEC->PJM
CLTF
0.5060.506
LAGNLTFEXP_LAGN->PJM
CLTF
6.2356.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.91517.915
NYPJM->LTFIMP_NY
CLTF
0.9860.986
TVALTFEXP_TVA->PJM
CLTF
4.8674.867
O66PJM->LTFIMP_O-066
CMTX_NF
13.52713.527
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.950.95
MECLTFEXP_MEC->PJM
CLTF
3.1033.103
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.7574.757
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.52724.527
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1242.124
CPLELTFEXP_CPLE->PJM
CLTF
9.989.98
SIGELTFEXP_SIGE->PJM
CLTF
0.1890.189

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.93 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4311.69
MW Contribution:50.59
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.26 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4569.37
MW Contribution:36.83
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
Adder
-20.06823529411765-17.058
934622AD1-088 E
50/50
10.02610.026
934611AD1-087 C
50/50
2.8252.825
934612AD1-087 E
50/50
8.158.15
3151611KERR 4
50/50
1.7561.756
927255AC1-221 E
50/50
6.8776.877
938531AE1-072 C
Adder
-15.17764705882353-12.901
3152411Z1-086 GT1
50/50
33.84633.846
3152421Z1-086 GT2
50/50
33.83433.834
924302AB2-077 E O1
50/50
2.2822.282
3151621KERR 5
50/50
1.7561.756
316222AC1-221 C
50/50
2.632.63
942752AE2-291 E
Adder
7.7105882352941186.554
3152431Z1-086 GT3
50/50
33.83433.834
3152441Z1-086 ST
50/50
58.91758.917
3147133PAMPLIN
50/50
1.5711.571
927264AC1-222 E
50/50
7.2547.254
925612AC1-036 E
50/50
1.5841.584
316237AB2-079 C O1
50/50
0.5590.559
924312AB2-078 E O1
50/50
2.2822.282
316238AB2-078 C O1
50/50
0.5590.559
926274AC1-105 E
50/50
4.8944.894
933291AC2-141 C
Adder
-30.18235294117647-25.655
964242AG1-285 E
50/50
16.62916.629
313527AB2-043 C
50/50
0.8840.884
924162AB2-060 E OP
50/50
7.2927.292
3151591KERR 2
50/50
1.7561.756
964792AG1-342 E
50/50
4.2324.232
932763AC2-100 E
50/50
4.6444.644
316283AC2-100 C
50/50
2.112.11
937481AD2-202 C
50/50
0.820.82
3151641KERR 7
50/50
1.7561.756
316240AF1-291 C
Adder
-1.7670588235294118-1.502
944641AF1-129 C
Adder
-82.61058823529412-70.219
925785AC1-054 E
Adder
3.30235294117647052.807
959311AF2-222 C
50/50
30.29330.293
942751AE2-291 C
Adder
11.5670588235294139.832
942001AE2-212 C
Adder
-1.851764705882353-1.574
3151031BRUNSWICKG2
50/50
25.39725.397
957482AF2-042 E
50/50
85.76685.766
934621AD1-088 C
50/50
20.82320.823
935172AD1-152 E
50/50
11.70511.705
946301AF1-294 C
Adder
5.5247058823529414.696
942461AE2-259 C
Adder
13.86823529411764811.788
936162AD2-022 E
Adder
7.0529411764705895.995
937482AD2-202 E
50/50
2.3852.385
3151581KERR 1
50/50
0.6270.627
3151601KERR 3
50/50
1.7561.756
961792AG1-021 E
Adder
2.28941176470588251.946
3152661PLYWOOD A
50/50
2.1912.191
3147223TWITTYS
50/50
1.7561.756
959312AF2-222 E
50/50
20.29620.296
924022AB2-043 E O1
50/50
8.8758.875
316003AC1-222 C
50/50
1.7761.776
926024AC1-080 E
Adder
1.52117647058823541.293
936161AD2-022 C
Adder
11.7541176470588239.991
957601AF2-054 C
Adder
-1.6305882352941177-1.386
316239AB2-077 C O1
50/50
0.5590.559
935171AD1-152 C
50/50
2.8452.845
942462AE2-259 E
Adder
9.2458823529411777.859
964791AG1-342 C
50/50
6.3476.347
925997AC1-075 E
Adder
4.5835294117647063.896
3151041BRUNSWICKG3
50/50
25.39725.397
3151021BRUNSWICKG1
50/50
25.39725.397
957481AF2-042 C
50/50
128.648128.648
924322AB2-079 E O1
50/50
2.2822.282
946302AF1-294 E
Adder
4.6788235294117653.977
943902AF1-058 E
50/50
2.3942.394
24401205PINNACLE
Adder
1.53647058823529431.306
944012AF1-069 E
50/50
17.73117.731
316131AB2-060 C
50/50
2.5322.532
3138533PONTONDP
Adder
0.99529411764705880.846
316118AC1-105 C
50/50
1.6721.672
963042AG1-153 E
50/50
25.80825.808
3151541CLOVER2
50/50
28.44128.441
964241AG1-285 C
50/50
24.94424.944
316034AC1-036 C
50/50
0.4320.432
958212AF2-115 E
Adder
2.86235294117647052.433
962561AG1-105 C
50/50
15.80415.804
936172AD2-023 E
Adder
3.7223529411764713.164
944011AF1-069 C
50/50
45.64245.642
963041AG1-153 C
50/50
17.20617.206
3151531CLOVER1
50/50
28.70728.707
936261AD2-033 C
50/50
21.05721.057
3151631KERR 6
50/50
1.7561.756
961791AG1-021 C
Adder
2.68823529411764732.285
962562AG1-105 E
50/50
10.53610.536
316248AF1-058 C
50/50
0.5870.587
936171AD2-023 C
Adder
6.8564705882352955.828
941032AE2-094 E
50/50
62.56462.564
941031AE2-094 C
50/50
139.691139.691
3151051BRUNSWICKS1
50/50
52.76252.762
936262AD2-033 E
50/50
14.03814.038
958211AF2-115 C
Adder
3.362.856
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5656
G-007PJM->LTFIMP_G-007
CMTX_NF
3.9723.972
CPLELTFEXP_CPLE->PJM
CLTF
19.02319.023
SIGELTFEXP_SIGE->PJM
CLTF
0.4210.421
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
2.1482.148
MECLTFEXP_MEC->PJM
CLTF
6.8436.843
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.0719.071
CBM South 2LTFEXP_CBM-S2->PJM
CBM
162.815162.815
WECLTFEXP_WEC->PJM
CLTF
1.1471.147
LAGNLTFEXP_LAGN->PJM
CLTF
13.09813.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.3338.33
NYPJM->LTFIMP_NY
CLTF
1.8141.814
TVALTFEXP_TVA->PJM
CLTF
10.24910.249
O66PJM->LTFIMP_O-066
CMTX_NF
25.2725.27
CONTINGENCY 'DVP_P1-2: LN 235_SRT-A'
 OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1   /*6PRINCE EDW  230.0 - 6BRIERY      230.0
 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1   /*6PRINCE EDW  230.0 - 6FARMVIL     230.0
 OPEN BRANCH FROM BUS 313996 TO BUS 314268 CKT 1   /*6FINNEYWOOD  230.0 - 6BRIERY      230.0
 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1   /*3FARMVIL     115.0 - 6FARMVIL     230.0
 OPEN BUS 313802                                   /*6PRINCE EDW  230.0
 OPEN BUS 314268                                   /*6BRIERY      230.0
END
CONTINGENCY 'DVP_P1-2: LN 1012_SRT-A-1'
 OPEN BRANCH FROM BUS 313139 TO BUS 314679 CKT 1   /*3DRAKES B TP 115.0 - 3CENTRAL     115.0
 OPEN BRANCH FROM BUS 314679 TO BUS 314722 CKT 1   /*3CENTRAL     115.0 - 3TWITTYS     115.0
 OPEN BRANCH FROM BUS 314679 TO BUS 964240 CKT 1   /*3CENTRAL     115.0 - AG1-285 TP   115.0
END
CONTINGENCY 'DVP_P1-2: LN 2027_SRT-A-2'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026 C    230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
 OPEN BUS 923862                                   /*AB2-026 E    230.0
 OPEN BUS 938562                                   /*AE1-075 E    230.0
 OPEN BUS 958502                                   /*AF2-144 E    230.0
END
CONTINGENCY 'DVP_P1-2: LN 556_SRT-S-3'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314691 to 314692 ckt 2
314726 to 314691 ckt 1
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314268 to 313802 ckt 1
313373 to 314765 ckt 1
313996 to 314268 ckt 1
313707 to 313373 ckt 1
314765 to 314749 ckt 1
313802 to 314692 ckt 1
314902 to 314914 ckt 1
314914 to 314322 ckt 1
314914 to 314918 ckt 1
314936 to 314902 ckt 1
314923 to 314924 ckt 1
941030 to 314902 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 2201_SRT-A
OPAC111.87 %252.86B282.8713.06
GD1DVP
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
DVP_P1-2: LN 1012_SRT-A-4
OPAC182.98 %205.86B376.68166.99
GD1DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S-1
OPAC111.78 %1058.16B1182.7614.25
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 550_SRT-S
OPAC105.92 %3220.44B3411.0331.32
GD1DVP
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
OPAC105.31 %4070.2B4286.2736.83

Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 2201_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.87 %
Rating:252.86 MVA
Rating Type:B
MVA to Mitigate:282.87
MW Contribution:13.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
927146AC1-208 E
Adder
2.18117647058823531.854
924302AB2-077 E O1
Adder
0.79529411764705890.676
3151281ROARAP4
50/50
1.091.09
3156063AA2-053SOLA
50/50
1.1211.121
900672V4-068 E
Adder
0.149411764705882360.127
966622AG1-532 E
50/50
2.932.93
3151261ROARAP2
50/50
1.1521.152
925612AC1-036 E
Adder
0.41647058823529410.354
924312AB2-078 E O1
Adder
0.79529411764705890.676
3147043LAWRENC
50/50
0.740.74
316181AB2-040 GEN
50/50
2.6292.629
923263AB1-132 E OP
Adder
2.7023529411764712.297
964242AG1-285 E
Adder
4.7470588235294124.035
964792AG1-342 E
Adder
0.90352941176470590.768
924162AB2-060 E OP
50/50
2.5852.585
313527AB2-043 C
50/50
0.3160.316
926214AC1-099 E
Adder
0.57647058823529410.49
932632AC2-084 E
Adder
1.5435294117647061.312
919710AA2-057 E
Adder
1.7070588235294121.451
3137643SOCKMAN
50/50
1.0011.001
959311AF2-222 C
Adder
7.8188235294117656.646
925785AC1-054 E
50/50
2.0962.096
3145723EMPORIA
50/50
1.2311.231
316087AB2-174 C
50/50
2.8212.821
923573AB1-173 E OP
50/50
6.8126.812
919692AA2-053 E OP
50/50
3.1533.153
3156073AA1-063SOLA
50/50
0.9590.959
920042AA2-088 E OP
Adder
4.6305882352941183.936
946301AF1-294 C
Adder
1.38117647058823521.174
924517AB2-100 E2
Adder
1.23882352941176471.053
961792AG1-021 E
Adder
0.5717647058823530.486
316274AC1-208 C
Adder
4.9105882352941184.174
918492AA1-063AE OP
50/50
2.7952.795
917332KELFORD E
Adder
0.63764705882352950.542
959312AF2-222 E
Adder
5.2388235294117654.453
3147223TWITTYS
Adder
0.46117647058823530.392
924022AB2-043 E O1
50/50
3.1813.181
924516AB2-100 E1
Adder
1.23882352941176471.053
966621AG1-532 C
50/50
4.3954.395
313506AB1-173 C OP
50/50
2.3342.334
964791AG1-342 C
Adder
1.3564705882352941.153
926206AC1-098 E
Adder
1.7470588235294121.485
946302AF1-294 E
Adder
1.16941176470588240.994
924322AB2-079 E O1
Adder
0.79529411764705890.676
316088AB2-174 E
50/50
15.67415.674
923994AB2-040_E
50/50
12.77312.773
3138533PONTONDP
Adder
0.248235294117647050.211
316131AB2-060 C
50/50
0.8950.895
316129AC1-054 C
50/50
0.7410.741
946282AF1-292 E
50/50
3.2343.234
958212AF2-115 E
Adder
0.71529411764705890.608
964241AG1-285 C
Adder
7.126.052
962561AG1-105 C
Adder
3.72941176470588243.17
946281AF1-292 C
50/50
4.8514.851
960082AF2-299 E
50/50
3.9073.907
926071AC1-086 C
Adder
9.2870588235294127.894
961791AG1-021 C
Adder
0.67176470588235290.571
936261AD2-033 C
Adder
6.6258823529411775.632
962562AG1-105 E
Adder
2.48588235294117642.113
960081AF2-299 C
50/50
5.865.86
926072AC1-086 E
Adder
4.2270588235294123.593
958211AF2-115 C
Adder
0.840.714
936262AD2-033 E
Adder
4.4164705882352953.754
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.4494.449
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3410.341
CPLELTFEXP_CPLE->PJM
CLTF
1.471.47
SIGELTFEXP_SIGE->PJM
CLTF
0.0330.033
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.1740.174
MECLTFEXP_MEC->PJM
CLTF
0.5250.525
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.7010.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.39311.393
WECLTFEXP_WEC->PJM
CLTF
0.0910.091
LAGNLTFEXP_LAGN->PJM
CLTF
0.9350.935
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.8192.819
NYPJM->LTFIMP_NY
CLTF
0.1550.155
TVALTFEXP_TVA->PJM
CLTF
0.7390.739
O66PJM->LTFIMP_O-066
CMTX_NF
2.1672.167

Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012_SRT-A-4


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1012_SRT-A-4
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:182.98 %
Rating:205.86 MVA
Rating Type:B
MVA to Mitigate:376.68
MW Contribution:166.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3147133PAMPLIN
50/50
5.9755.975
925612AC1-036 E
50/50
5.155.15
964242AG1-285 E
50/50
49.99849.998
959311AF2-222 C
50/50
99.99699.996
942461AE2-259 C
50/50
59.99759.997
959312AF2-222 E
50/50
66.99766.997
3147223TWITTYS
50/50
5.7095.709
942462AE2-259 E
50/50
39.99839.998
316034AC1-036 C
50/50
1.4011.401
964241AG1-285 C
50/50
74.99774.997
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0050.005
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0020.002
O66PJM->LTFIMP_O-066
CMTX_NF
0.030.03
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0090.009
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0020.002
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0040.004
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0030.003
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0080.008
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0030.003
NYPJM->LTFIMP_NY
CLTF
0.0020.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0120.012
MDUPJM->LTFIMP_MDU
CLTF
00

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.78 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1182.76
MW Contribution:14.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926785AC1-164_E
Adder
8.8941176470588247.56
316336AC2-165 C
50/50
13.55213.552
934622AD1-088 E
Adder
2.08470588235294141.772
934612AD1-087 E
Adder
1.55882352941176471.325
316084AB2-161 E
Adder
2.8764705882352942.445
940641AE2-051 C
Adder
7.0152941176470595.963
943471AF1-018 C
Adder
3.25058823529411762.763
3150731STONECA
Adder
4.1494117647058823.527
924302AB2-077 E O1
Adder
0.62117647058823530.528
935161AD1-151 C
Adder
8.9764705882352947.63
900672V4-068 E
Adder
0.157647058823529420.134
3145393UNCAMP
Adder
2.72117647058823582.313
938531AE1-072 C
Adder
7.6223529411764716.479
932046AC2-012 E
Adder
5.7529411764705884.89
958161AF2-110 C
Adder
0.61529411764705890.523
927042AC1-191 E
Adder
2.55411764705882362.171
316233AE1-074 C
50/50
3.7333.733
3147133PAMPLIN
Adder
0.54941176470588240.467
966622AG1-532 E
Adder
0.42588235294117650.362
935162AD1-151 E
Adder
5.9847058823529415.087
943461AF1-017 C
Adder
0.64470588235294120.548
316311AC2-079 C
Adder
2.71999999999999982.312
932596AC2-079 E
Adder
4.4376470588235293.772
920692AA2-178 E
Adder
1.78588235294117651.518
917122Z2-027 E
Adder
0.58470588235294120.497
3146326AYDLETT TAP
Adder
0.58823529411764710.5
938532AE1-072 E
Adder
3.9729411764705883.377
940551AE2-041 C
Adder
3.25058823529411762.763
957832AF2-077 E
Adder
0.63529411764705890.54
3138116ELKO L286
Adder
0.76588235294117660.651
927041AC1-191 C
Adder
5.1282352941176474.359
938821AE1-108 C
Adder
8.4270588235294127.163
925612AC1-036 E
Adder
0.435294117647058830.37
924312AB2-078 E O1
Adder
0.62117647058823530.528
940541AE2-040 C
Adder
1.35764705882352941.154
940481AE2-033 C
Adder
7.6223529411764716.479
940482AE2-033 E
Adder
5.13882352941176554.368
923263AB1-132 E OP
Adder
2.70941176470588242.303
961611AG1-000B C
Adder
8.1152941176470596.898
944631AF1-128 C
Adder
24.6823529411764720.98
3150851SPRUNCC
50/50
0.1690.169
938552AE1-074 E
50/50
1.8811.881
938562AE1-075 E
50/50
1.5421.542
964242AG1-285 E
Adder
4.0211764705882363.418
924162AB2-060 E OP
Adder
2.0117647058823531.71
316160AE1-175 E
Adder
0.54117647058823540.46
933291AC2-141 C
Adder
12.51176470588235310.635
957872AF2-081 E
Adder
1.85647058823529431.578
925522AC1-027 E
Adder
0.53176470588235290.452
941102AE2-104 E
Adder
2.39764705882352922.038
3145256KINGFORK
Adder
0.455294117647058850.387
3150921YORKTN3
Adder
52.8152941176470644.893
933502AC2-165 E
50/50
10.19910.199
940432AE2-027 E
Adder
5.3129411764705894.516
3137643SOCKMAN
Adder
0.317647058823529450.27
939411AE1-173 C
Adder
37.3388235294117631.738
934012AD1-025 E
Adder
5.44117647058823554.625
913392Y1-086 E
Adder
0.9552941176470590.812
939612AE1-191 E
Adder
2.6082352941176472.217
957602AF2-054 E
Adder
0.63529411764705890.54
944641AF1-129 C
Adder
65.7211764705882355.863
316240AF1-291 C
Adder
1.36588235294117651.161
959311AF2-222 C
Adder
8.5341176470588237.254
3145723EMPORIA
Adder
0.196470588235294150.167
923573AB1-173 E OP
Adder
1.47764705882352951.256
919692AA2-053 E OP
Adder
1.86823529411764721.588
924814AB2-134 E
Adder
6.8847058823529425.852
920042AA2-088 E OP
Adder
4.724.012
942342AE2-247 E
Adder
0.98470588235294120.837
919152AA1-139 E1
Adder
1.7717647058823531.506
958502AF2-144 E
50/50
1.7771.777
938822AE1-108 E
Adder
4.0211764705882363.418
942001AE2-212 C
Adder
1.3035294117647061.108
942461AE2-259 C
Adder
5.83647058823529454.961
946301AF1-294 C
Adder
1.99882352941176491.699
939192AE1-149 E
Adder
3.93176470588235333.342
934621AD1-088 C
Adder
4.3294117647058833.68
957482AF2-042 E
Adder
15.4776470588235313.156
924517AB2-100 E2
Adder
1.32117647058823541.123
937226AE2-253 E
Adder
2.53176470588235342.152
934065AD1-033 E
Adder
2.1752941176470591.849
939312AE1-162 E
Adder
0.67999999999999990.578
3150861SPRUNCD
50/50
0.1690.169
316405AF2-144 C
50/50
0.4340.434
3150651CHESTF6
Adder
11.96588235294117610.171
946262AF1-291 E
Adder
0.91058823529411770.774
941011AE2-092 C
Adder
6.9470588235294125.905
961792AG1-021 E
Adder
0.82823529411764710.704
937482AD2-202 E
Adder
0.456470588235294130.388
934576AD1-082 E
Adder
2.2917647058823531.948
918492AA1-063AE OP
Adder
1.8117647058823531.54
933292AC2-141 E
Adder
2.30588235294117631.96
940492AE2-034 E
Adder
1.33882352941176451.138
944602AF1-125 E
Adder
43.9588235294117737.365
957871AF2-081 C
Adder
4.3329411764705883.683
3145506HICKORY
Adder
0.94470588235294130.803
943612AF1-032 E
Adder
0.405882352941176470.345
3130536PAPERMILL
Adder
3.0341176470588242.579
939602AE1-190 E
Adder
0.6517647058823530.554
926412AC1-112 E
Adder
0.56470588235294120.48
959312AF2-222 E
Adder
5.71764705882352954.86
3147223TWITTYS
Adder
0.48235294117647060.41
924022AB2-043 E O1
Adder
2.4235294117647062.06
924516AB2-100 E1
Adder
1.32117647058823541.123
966621AG1-532 C
Adder
0.63882352941176480.543
940642AE2-051 E
Adder
4.67764705882352953.976
943462AF1-017 E
Adder
1.0517647058823530.894
942341AE2-247 C
Adder
0.71294117647058820.606
919153AA1-139 E2
Adder
1.7717647058823531.506
958162AF2-110 E
Adder
0.97882352941176460.832
3143096IRON208
50/50
0.330.33
316313AB2-026 C
50/50
0.5570.557
3143316POE
Adder
0.75647058823529410.643
942462AE2-259 E
Adder
3.8917647058823533.308
939191AE1-149 C
Adder
5.8976470588235295.013
901082W1-029 E
Adder
13.8976470588235311.813
934146AD1-041 E
Adder
1.63058823529411771.386
957601AF2-054 C
Adder
0.95294117647058830.81
942002AE2-212 E
Adder
0.86941176470588230.739
946302AF1-294 E
Adder
1.69294117647058841.439
940431AE2-027 C
Adder
7.9682352941176476.773
924322AB2-079 E O1
Adder
0.62117647058823530.528
957481AF2-042 C
Adder
23.21647058823529619.734
316088AB2-174 E
Adder
2.94705882352941152.505
923994AB2-040_E
Adder
2.76941176470588252.354
944581AF1-123 C
Adder
19.50352941176470616.578
941101AE2-104 C
Adder
1.50823529411764711.282
934392AD1-063 E
Adder
0.487058823529411770.414
3138533PONTONDP
Adder
0.360.306
946282AF1-292 E
Adder
0.47058823529411770.4
944012AF1-069 E
Adder
2.02941176470588271.725
925865AC1-065 E
Adder
7.73058823529411756.571
316169AC1-164 GEN
Adder
19.79647058823529816.827
930122AB1-027 E
Adder
0.69529411764705880.591
958212AF2-115 E
Adder
1.0352941176470590.88
964241AG1-285 C
Adder
6.0305882352941185.126
963042AG1-153 E
Adder
3.39411764705882352.885
946281AF1-292 C
Adder
0.70588235294117650.6
960082AF2-299 E
Adder
0.56823529411764710.483
926071AC1-086 C
Adder
9.3082352941176477.912
316349AD2-085 C
Adder
1.6447058823529411.398
938772AE1-103 E
Adder
1.8117647058823531.54
916042Z1-036 E
Adder
12.43647058823529310.571
944592AF1-124 E
Adder
44.82117647058823538.098
944582AF1-123 E
Adder
44.6637.961
923832AB2-022 E
Adder
0.53882352941176470.458
935112AD1-144 E
Adder
0.42235294117647060.359
3150601CHESTF5
Adder
39.4470588235294233.53
924032AB2-045 E
Adder
0.94941176470588240.807
961791AG1-021 C
Adder
0.97294117647058820.827
936261AD2-033 C
Adder
6.5000000000000015.525
925332AB2-190 E
Adder
4.5752941176470593.889
963041AG1-153 C
Adder
2.2623529411764711.923
960081AF2-299 C
Adder
0.8517647058823530.724
944011AF1-069 C
Adder
5.2235294117647074.44
926072AC1-086 E
Adder
4.2364705882352943.601
927226AC1-216 E
Adder
4.20352941176470553.573
3145413WATKINS
Adder
0.30941176470588240.263
936666AD2-085 E
Adder
2.6835294117647062.281
962962AG1-145 E
Adder
0.65529411764705890.557
938771AE1-103 C
Adder
1.3117647058823531.115
944591AF1-124 C
Adder
19.5717647058823516.636
944601AF1-125 C
Adder
19.2023529411764716.322
941591AE2-156 C
Adder
7.8529411764705886.675
316076AC2-137 E
Adder
0.73529411764705890.625
966872AG1-558 E
Adder
0.64352941176470590.547
966871AG1-558 C
Adder
1.27764705882352961.086
3150831SPRUNCA
50/50
9.4469.446
3150841SPRUNCB
50/50
9.4469.446
316258AE1-075 C
50/50
0.5110.511
923862AB2-026 E
50/50
1.8081.808
941012AE2-092 E
Adder
4.6305882352941183.936
958211AF2-115 C
Adder
1.21529411764705891.033
936262AD2-033 E
Adder
4.3329411764705883.683
923852AB2-025 E
Adder
0.54941176470588240.467
941032AE2-094 E
Adder
7.166.086
941031AE2-094 C
Adder
15.98588235294117513.588
939412AE1-173 E
Adder
24.89294117647058621.159
916192Z1-068 E
Adder
0.820.697
926662AC1-147 E
Adder
0.58117647058823530.494
957492AF2-043 E
Adder
0.62470588235294120.531
923842AB2-024 E
Adder
0.82235294117647050.699
316157AD2-030 E
Adder
0.53411764705882360.454
316303AF2-085
50/50
7.0277.027
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.29711.297
NYPJM->LTFIMP_NY
CLTF
0.9630.963
TVALTFEXP_TVA->PJM
CLTF
2.952.95
O66PJM->LTFIMP_O-066
CMTX_NF
13.41813.418
CBM South 2LTFEXP_CBM-S2->PJM
CBM
40.62940.629
WECLTFEXP_WEC->PJM
CLTF
0.3730.373
LAGNLTFEXP_LAGN->PJM
CLTF
3.6953.695
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.08118.081
G-007PJM->LTFIMP_G-007
CMTX_NF
2.112.11
CPLELTFEXP_CPLE->PJM
CLTF
4.6984.698
SIGELTFEXP_SIGE->PJM
CLTF
0.1370.137
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.7270.727
MECLTFEXP_MEC->PJM
CLTF
2.1322.132
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.2422.242

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 550_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.92 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3411.03
MW Contribution:31.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
50/50
11.89711.897
934622AD1-088 E
50/50
5.6675.667
934611AD1-087 C
50/50
1.5341.534
934612AD1-087 E
50/50
4.4414.441
927146AC1-208 E
Adder
4.6176470588235293.925
316084AB2-161 E
Adder
6.1764705882352945.25
940641AE2-051 C
50/50
23.07223.072
933982AD1-022 E
Adder
5.4529411764705884.635
3145946PLYMOUTH TP
Adder
0.36941176470588240.314
316017AA1-139 ULT1
50/50
1.221.22
924302AB2-077 E O1
Adder
1.53411764705882361.304
3152421Z1-086 GT2
50/50
13.99313.993
900672V4-068 E
Adder
0.410588235294117640.349
933981AD1-022 C
Adder
10.0176470588235318.515
3145393UNCAMP
Adder
6.9494117647058825.907
938531AE1-072 C
Adder
19.8816.898
932046AC2-012 E
Adder
14.74823529411764712.536
958161AF2-110 C
Adder
1.54823529411764721.316
316233AE1-074 C
50/50
3.143.14
3147133PAMPLIN
Adder
1.09647058823529430.932
3152411Z1-086 GT1
50/50
13.99713.997
3152441Z1-086 ST
50/50
24.36424.364
966622AG1-532 E
50/50
1.1011.101
943461AF1-017 C
Adder
1.521.292
316311AC2-079 C
Adder
6.4611764705882355.492
932596AC2-079 E
Adder
10.5423529411764718.961
920692AA2-178 E
Adder
4.6870588235294123.984
917122Z2-027 E
Adder
1.52235294117647071.294
3146326AYDLETT TAP
Adder
1.53411764705882361.304
938532AE1-072 E
Adder
10.3635294117647068.809
925612AC1-036 E
Adder
0.96823529411764710.823
926274AC1-105 E
Adder
3.05411764705882362.596
924312AB2-078 E O1
Adder
1.53411764705882361.304
940541AE2-040 C
50/50
3.4933.493
940481AE2-033 C
50/50
19.63119.631
940482AE2-033 E
50/50
13.23413.234
3152431Z1-086 GT3
50/50
13.99313.993
923263AB1-132 E OP
Adder
7.1317647058823546.062
961611AG1-000B C
Adder
16.4223529411764713.959
938552AE1-074 E
50/50
1.5821.582
938562AE1-075 E
50/50
1.3151.315
964242AG1-285 E
Adder
9.5294117647058828.1
964792AG1-342 E
Adder
2.69176470588235262.288
924162AB2-060 E OP
Adder
4.9070588235294124.171
3151031BRUNSWICKG2
50/50
10.91910.919
926214AC1-099 E
Adder
1.38941176470588231.181
932632AC2-084 E
Adder
3.71764705882352953.16
933291AC2-141 C
50/50
34.17534.175
926755AC1-161 E
50/50
14.58914.589
957872AF2-081 E
50/50
4.8444.844
316018AA1-139 ULT2
50/50
1.221.22
925522AC1-027 E
50/50
1.3731.373
941102AE2-104 E
Adder
6.0305882352941185.126
3145256KINGFORK
Adder
1.11999999999999990.952
933502AC2-165 E
50/50
8.9548.954
940432AE2-027 E
Adder
8.8517647058823537.524
919710AA2-057 E
Adder
4.5541176470588243.871
3137643SOCKMAN
Adder
0.8317647058823530.707
939411AE1-173 C
50/50
116.624116.624
913392Y1-086 E
Adder
2.48823529411764752.115
944641AF1-129 C
Adder
29.2682352941176524.878
316240AF1-291 C
Adder
2.20823529411764731.877
959311AF2-222 C
Adder
18.7552941176470615.942
937481AD2-202 C
50/50
0.4450.445
925785AC1-054 E
Adder
3.9917647058823533.393
3145723EMPORIA
50/50
0.5070.507
923573AB1-173 E OP
Adder
3.84588235294117683.269
919692AA2-053 E OP
Adder
4.9082352941176474.172
920042AA2-088 E OP
Adder
12.21058823529411810.379
934521AD1-076 C
Adder
13.97999999999999911.883
934511AD1-075 C
Adder
9.6235294117647058.18
942342AE2-247 E
Adder
2.321.972
919152AA1-139 E1
50/50
4.6224.622
958502AF2-144 E
50/50
1.5151.515
942001AE2-212 C
Adder
2.33058823529411761.981
946301AF1-294 C
Adder
4.09882352941176453.484
939192AE1-149 E
Adder
7.9482352941176486.756
935172AD1-152 E
50/50
6.5696.569
934621AD1-088 C
50/50
11.7711.77
957482AF2-042 E
50/50
45.06445.064
924517AB2-100 E2
50/50
3.4373.437
934501AD1-074 C
Adder
38.4929411764705932.719
937226AE2-253 E
50/50
6.6076.607
934065AD1-033 E
50/50
5.675.67
939312AE1-162 E
Adder
1.53529411764705871.305
316405AF2-144 C
50/50
0.370.37
946262AF1-291 E
Adder
1.47176470588235291.251
961792AG1-021 E
Adder
1.69882352941176461.444
937482AD2-202 E
50/50
1.31.3
3151021BRUNSWICKG1
50/50
10.91910.919
316274AC1-208 C
Adder
10.48.84
934576AD1-082 E
Adder
4.9211764705882354.183
918492AA1-063AE OP
Adder
4.7329411764705884.023
917332KELFORD E
Adder
1.8917647058823531.608
925122AB2-169 E
Adder
6.5670588235294125.582
943172AE2-346 E
Adder
0.69647058823529410.592
934522AD1-076 E
Adder
7.12588235294117746.057
933292AC2-141 E
50/50
14.58914.589
940492AE2-034 E
Adder
3.5152941176470592.988
944602AF1-125 E
50/50
116.453116.453
957871AF2-081 C
50/50
11.30311.303
3145506HICKORY
50/50
2.4652.465
943612AF1-032 E
Adder
1.04470588235294120.888
959312AF2-222 E
Adder
12.56588235294117510.681
3147223TWITTYS
Adder
1.07294117647058830.912
924022AB2-043 E O1
Adder
5.9517647058823535.059
935171AD1-152 C
50/50
1.5911.591
924516AB2-100 E1
50/50
3.4373.437
966621AG1-532 C
50/50
1.6521.652
940642AE2-051 E
50/50
15.38115.381
918532AA1-067 E
Adder
0.81647058823529410.694
918512AA1-065 E OP
Adder
6.3400000000000015.389
934502AD1-074 E
Adder
19.59411764705882716.655
934512AD1-075 E
Adder
4.8988235294117644.164
943462AF1-017 E
Adder
2.482.108
942341AE2-247 C
Adder
1.681.428
919153AA1-139 E2
50/50
4.6224.622
316388AE2-253 GEN
50/50
2.2142.214
958162AF2-110 E
Adder
2.46235294117647062.093
316313AB2-026 C
50/50
0.4750.475
3143316POE
50/50
1.5751.575
964791AG1-342 C
Adder
4.037647058823533.432
939191AE1-149 C
Adder
11.92235294117647210.134
3151041BRUNSWICKG3
50/50
10.91910.919
926206AC1-098 E
Adder
4.2058823529411773.575
901082W1-029 E
Adder
36.1329411764705930.713
942002AE2-212 E
Adder
1.55411764705882361.321
946302AF1-294 E
Adder
3.47176470588235332.951
940431AE2-027 C
Adder
13.27647058823529511.285
943902AF1-058 E
Adder
1.4670588235294121.247
924322AB2-079 E O1
Adder
1.53411764705882361.304
957481AF2-042 C
50/50
67.59667.596
316365AB2-100 C1
50/50
1.1361.136
316088AB2-174 E
Adder
7.6541176470588246.506
923994AB2-040_E
Adder
7.2105882352941176.129
316141AB2-099 E
Adder
0.290588235294117650.247
316294AC1-161 C
50/50
5.5655.565
944581AF1-123 C
50/50
51.66651.666
316185AD1-033 C
50/50
1.3851.385
916191Z1-068 C
50/50
0.0490.049
941101AE2-104 C
Adder
3.79294117647058873.224
3138533PONTONDP
Adder
0.73882352941176480.628
316315AB2-025 C
50/50
0.4950.495
316023AB2-100 C2
50/50
1.1361.136
946282AF1-292 E
50/50
1.2161.216
944012AF1-069 E
50/50
6.7946.794
316316AC1-027 C
50/50
0.3550.355
958212AF2-115 E
Adder
2.1235294117647061.805
964241AG1-285 C
Adder
14.29529411764705812.151
962561AG1-105 C
Adder
10.137647058823538.617
3151541CLOVER2
50/50
15.43615.436
963042AG1-153 E
50/50
11.13411.134
946281AF1-292 C
50/50
1.8231.823
960082AF2-299 E
50/50
1.4691.469
926071AC1-086 C
Adder
24.50588235294117520.83
316349AD2-085 C
Adder
3.8752941176470593.294
938772AE1-103 E
Adder
4.6141176470588243.922
916042Z1-036 E
Adder
32.496470588235327.622
944592AF1-124 E
50/50
118.738118.738
944582AF1-123 E
50/50
118.31118.31
923832AB2-022 E
Adder
1.40470588235294121.194
935112AD1-144 E
Adder
1.040.884
961791AG1-021 C
Adder
1.99411764705882361.695
936261AD2-033 C
Adder
14.72588235294117712.517
962562AG1-105 E
Adder
6.7588235294117655.745
3151531CLOVER1
50/50
15.58115.581
963041AG1-153 C
50/50
7.4237.423
960081AF2-299 C
50/50
2.2032.203
944011AF1-069 C
50/50
17.48817.488
926072AC1-086 E
Adder
11.152941176470599.48
3145413WATKINS
Adder
0.7917647058823530.673
936666AD2-085 E
Adder
6.3235294117647065.375
938771AE1-103 C
Adder
3.34117647058823542.84
944591AF1-124 C
50/50
51.8551.85
944601AF1-125 C
50/50
50.8750.87
3151101ELIZAR3
50/50
3.6413.641
941591AE2-156 C
Adder
20.1617.136
3150831SPRUNCA
Adder
9.668.211
3150841SPRUNCB
Adder
9.668.211
316258AE1-075 C
50/50
0.4350.435
923862AB2-026 E
50/50
1.5421.542
958211AF2-115 C
Adder
2.49294117647058842.119
936262AD2-033 E
Adder
9.8164705882352948.344
923852AB2-025 E
50/50
1.4131.413
3151051BRUNSWICKS1
50/50
22.68422.684
941032AE2-094 E
50/50
23.97223.972
941031AE2-094 C
50/50
53.52353.523
934322AD1-056 E
Adder
3.91411764705882353.327
934321AD1-056 C
Adder
7.2164705882352946.134
934332AD1-057 E
Adder
2.09647058823529431.782
934331AD1-057 C
Adder
4.0258823529411773.422
939412AE1-173 E
50/50
77.7577.75
961942AG1-037 E
Adder
0.38705882352941180.329
961941AG1-037 C
Adder
0.580.493
916192Z1-068 E
50/50
2.1212.121
3151081ELIZAR1
50/50
3.5963.596
926662AC1-147 E
Adder
1.49058823529411751.267
957492AF2-043 E
Adder
1.6082352941176471.367
316303AF2-085
50/50
5.5375.537
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
1.8681.868
MECLTFEXP_MEC->PJM
CLTF
5.5885.588
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.4826.482
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.12546.125
G-007PJM->LTFIMP_G-007
CMTX_NF
4.9764.976
CPLELTFEXP_CPLE->PJM
CLTF
13.58913.589
SIGELTFEXP_SIGE->PJM
CLTF
0.3550.355
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.44630.446
NYPJM->LTFIMP_NY
CLTF
2.3122.312
TVALTFEXP_TVA->PJM
CLTF
8.0788.078
O66PJM->LTFIMP_O-066
CMTX_NF
31.68131.681
CBM South 2LTFEXP_CBM-S2->PJM
CBM
116.495116.495
WECLTFEXP_WEC->PJM
CLTF
0.9550.955
LAGNLTFEXP_LAGN->PJM
CLTF
10.14710.147

Details for 8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.31 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4286.27
MW Contribution:36.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316222AC1-221 C
50/50
2.6372.637
927255AC1-221 E
50/50
6.9166.916
316237AB2-079 C O1
50/50
0.4550.455
934622AD1-088 E
50/50
10.28810.288
934611AD1-087 C
50/50
2.842.84
934612AD1-087 E
50/50
8.2238.223
3151621KERR 5
50/50
1.6151.615
3151611KERR 4
50/50
1.6151.615
940641AE2-051 C
Adder
-21.040000000000003-17.884
942752AE2-291 E
Adder
8.0741176470588246.863
924302AB2-077 E O1
50/50
1.8631.863
316238AB2-078 C O1
50/50
0.4550.455
3152421Z1-086 GT2
50/50
33.46533.465
938531AE1-072 C
Adder
-16.01294117647059-13.611
3147133PAMPLIN
Adder
1.261.071
927264AC1-222 E
50/50
7.1497.149
3152411Z1-086 GT1
50/50
33.47433.474
3152441Z1-086 ST
50/50
58.26658.266
925612AC1-036 E
50/50
1.1421.142
926274AC1-105 E
50/50
4.6164.616
924312AB2-078 E O1
50/50
1.8631.863
3152431Z1-086 GT3
50/50
33.46533.465
932763AC2-100 E
50/50
4.6734.673
964242AG1-285 E
50/50
11.38411.384
964792AG1-342 E
50/50
3.8443.844
924162AB2-060 E OP
50/50
5.8965.896
313527AB2-043 C
50/50
0.7110.711
3151641KERR 7
50/50
1.6151.615
3151031BRUNSWICKG2
50/50
25.15825.158
933291AC2-141 C
Adder
-32.203529411764706-27.373
944641AF1-129 C
Adder
-90.49176470588236-76.918
316240AF1-291 C
Adder
-1.9317647058823528-1.642
940082AE1-250 E
Adder
8.5741176470588247.288
942751AE2-291 C
Adder
12.11176470588235310.295
316205AC1-080 C
50/50
0.4520.452
316123AC1-075 C
50/50
1.3531.353
959311AF2-222 C
50/50
22.05622.056
937481AD2-202 C
50/50
0.8240.824
3151591KERR 2
50/50
1.6151.615
925785AC1-054 E
Adder
2.96470588235294132.52
942001AE2-212 C
Adder
-2.010588235294118-1.709
942461AE2-259 C
Adder
12.19882352941176510.369
936162AD2-022 E
Adder
7.29529411764705856.201
946301AF1-294 C
Adder
4.7458823529411774.034
316283AC2-100 C
50/50
2.1162.116
935172AD1-152 E
50/50
11.76211.762
934621AD1-088 C
50/50
21.36821.368
957482AF2-042 E
50/50
86.59186.591
961792AG1-021 E
Adder
1.96705882352941171.672
3152661PLYWOOD A
50/50
2.0932.093
937482AD2-202 E
50/50
2.4072.407
3151021BRUNSWICKG1
50/50
25.15825.158
926024AC1-080 E
50/50
1.5621.562
936161AD2-022 C
Adder
12.15882352941176610.335
959312AF2-222 E
50/50
14.77814.778
3147223TWITTYS
50/50
1.2661.266
924022AB2-043 E O1
50/50
7.1597.159
935171AD1-152 C
50/50
2.8492.849
3151601KERR 3
50/50
1.6151.615
3151581KERR 1
50/50
0.5770.577
940081AE1-250 C
Adder
12.86117647058823510.932
942462AE2-259 E
Adder
8.1329411764705886.913
925997AC1-075 E
50/50
4.7084.708
964791AG1-342 C
50/50
5.7665.766
316239AB2-077 C O1
50/50
0.4550.455
3151041BRUNSWICKG3
50/50
25.15825.158
957601AF2-054 C
Adder
-1.8-1.53
24401205PINNACLE
Adder
1.6670588235294121.417
946302AF1-294 E
Adder
4.01882352941176453.416
316003AC1-222 C
50/50
1.7441.744
943902AF1-058 E
50/50
2.342.34
924322AB2-079 E O1
50/50
1.8631.863
957481AF2-042 C
50/50
129.887129.887
3138533PONTONDP
Adder
0.85529411764705890.727
316131AB2-060 C
50/50
2.042.04
3151631KERR 6
50/50
1.6151.615
936172AD2-023 E
Adder
3.8505882352941183.273
958212AF2-115 E
Adder
2.45882352941176442.09
316034AC1-036 C
50/50
0.3110.311
316118AC1-105 C
50/50
1.5721.572
964241AG1-285 C
50/50
17.07617.076
962561AG1-105 C
50/50
14.10814.108
3151541CLOVER2
50/50
28.59928.599
963042AG1-153 E
50/50
25.65425.654
936171AD2-023 C
Adder
7.0929411764705886.029
961791AG1-021 C
Adder
2.30941176470588251.963
936261AD2-033 C
50/50
17.43217.432
316248AF1-058 C
50/50
0.5710.571
962562AG1-105 E
50/50
9.4059.405
3151531CLOVER1
50/50
28.86828.868
963041AG1-153 C
50/50
17.10317.103
964211AG1-282 C
Adder
-1.7011764705882353-1.446
958211AF2-115 C
Adder
2.88588235294117632.453
936262AD2-033 E
50/50
11.62211.622
3151051BRUNSWICKS1
50/50
52.26552.265
CBM South 2LTFEXP_CBM-S2->PJM
CBM
170.641170.641
WECLTFEXP_WEC->PJM
CLTF
1.451.45
LAGNLTFEXP_LAGN->PJM
CLTF
14.84614.846
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.76444.764
NYPJM->LTFIMP_NY
CLTF
2.1082.108
TVALTFEXP_TVA->PJM
CLTF
11.71211.712
O66PJM->LTFIMP_O-066
CMTX_NF
29.75629.756
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
2.7422.742
MECLTFEXP_MEC->PJM
CLTF
8.3488.348
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.2639.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.06671.066
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6814.681
CPLELTFEXP_CPLE->PJM
CLTF
19.41719.417
SIGELTFEXP_SIGE->PJM
CLTF
0.5240.524
CONTINGENCY 'DVP_P1-2: LN 2201_SRT-A'
 OPEN BRANCH FROM BUS 313725 TO BUS 314563 CKT 1   /*6DRY BREAD   230.0 - 6CLUBHSE     230.0
END
CONTINGENCY 'DVP_P1-2: LN 1012_SRT-A-4'
 OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1   /*AG1-285 TP   115.0 - 3CHASCTY     115.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 550_SRT-S'
 OPEN BRANCH FROM BUS 314917 TO BUS 314926 CKT 1                /*8MT STM      500.0 - 8VALLEY      500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314562 to 314563 ckt 1
314726 to 314691 ckt 1
314322 to 314914 ckt 1
314914 to 314918 ckt 1
314940 to 941030 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AF2-222 was evaluated as a 167.0 MW injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - Issues Found

Executive Summary for Dynamic Stability Analysis Using PSSE

New Service Requests (projects) in PJM Transition Cycle 1 Cluster 31 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 31 projects.

 

 

Table 1: Transition Cycle 1 Cluster 31 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO

(MW)

MWE

(MW)

MWC

(MW)

Point of Interconnection

31

AF2-222

Solar

Dominion

167

167

100

Madisonville DP-Twitty's Creek 115 kV

AG1-285

Solar

Dominion

125

125

75

Chase City-Central 115 kV

 

For the Cluster 31 base run, the latest data from DP3 was used to update the models for the Cluster 31 generation in addition to removing withdrawn generation from the dispatch.

 

Cluster 31 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. 136 initial contingencies and 169 sensitivity contingencies were studied, each with a 20 second simulation time period. The contingencies studied included:

 

  • Steady-state operation (30 seconds)
  • Three-phase faults with normal clearing time
  • Single-phase bus faults with normal clearing time
  • Single-phase faults with stuck breaker
  • Single-phase faults with delayed clearing at remote end
  • Three-phase faults with loss of multiple-circuit tower line.

The results of the analysis identified instability for outages of the Chase City – AG1-285 115 kV circuit as observed in the Phase 3 analysis. The mitigation recommended from the Phase 3 analysis was then tested and resolved the instability. Network upgrade N9630 is still recommended. N9630 updates the new AG1-285 230 kV substation to a breaker and a half scheme to accommodate 2 x 230/115 kV AG1-285 transformers, and a 230 kV line from AG1-285 to Finneywood.

 

AG1-285 DP3 data included  a 0.84 MVA base for the inverters based on  a 25? PQ curve rating.  A sensitivity was performed to determine the impacts of AG1-285 model with inverter rating 0.81 MVA at 35?. The results of the analysis matched when using the 25? and 35? ratings. The network upgrade is still required.

 

 

The following changes were required during Phase 3 analysis that would still apply for the Restudy results: 

 

The protection settings for AE2-259 regarding frequency above 62.5 Hz for more than 0 seconds and frequencies below 56.5 Hz for more than 0 seconds are commented due to tripping of the generator during the Phase 3 analysis.  

With the mitigation identified above, the results of the contingencies tested on the RTEP 2027 summer peak case found:

 

  • Cluster 31 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  • The system with Cluster 31 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for inter area modes and 4% for local modes.
  • Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus) and the final voltages are within the steady-state voltage ranges below per Dominion Energy’s transmission planning criteria.
    • P1 Category Contingencies:
      • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.01 to 1.096 p.u. for 500 kV facilities
    • P2, P4, P5, and P7 Category Contingencies:
      • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.00 to 1.096 p.u. for 500 kV facilities
  • No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

Executive Summary for Dynamic Stability Analysis Using  PSCAD/EMT

 

Model Quality Testing Report

PSCAD model for Queue project AF2-222 and AG1-285 was developed and tested individually to ensure the model was in compliance with the PJM requirements. Test summary and result of test been summarized below in table 2. it is confirmed that PSCAD model was set up properly and satisfied the PJM requirement.

 

Table 2. MQT Result for each Project

 

Test

Status

Flat Start Test 

Pass 

Voltage Step-Down 

Pass 

Voltage Step-Up 

Pass 

Frequency Step-Down, No Headroom

Pass 

Frequency Step-Down, Headroom

Pass 

Frequency Step-Up, Headroom 

Pass 

HVRT Leading

Pass 

HVRT Lagging

Pass 

LVRT Leading

Pass 

LVRT Lagging

Pass 

System Strength Test 

Pass 

Voltage Ride Through

Pass 

Phase Angle Step-Down 

Pass 

Phase Angle Step-Up 

Pass 

 

Weak Grid Assessment

This Weak Grid Assessment evaluates two projects from PJM Transition Cycle 1 (TC1) Cluster 31 for risk of voltage instability due to weak grid conditions in an EMT simulation environment.  The two projects, AF2-222 and AG1-285, were identified in the Cluster Study as having risk of undamped oscillations during a contingency condition and indicating system instability after dynamic simulation analysis in PSS/E. Three potential network upgrades were considered to resolve this instability, and Network Upgrades 2 and 3 were shown to be effective through sensitivity analysis.

This assessment, completed by INS Engineering, aims to verify the impact of Network Upgrade 2 and 3 identified in the Cluster Study, using detailed models in an EMT simulation.  Summary descriptions of each project and the two network upgrades are listed below:

 

Table 3. Summary Description of TC1 Cluster 31 Projects

 

 

 

 

Project Name

Project Type

Project Size (MW)

POI

POI Bus Number

AF2-222 Courthouse Solar

PV

167

Madisonville DP-Twitty's Creek 115 kV

959310

AG1-285 Quarter Horse Solar

PV

125

Chase City-Central 115 kV

964240

 

The following network upgrades proposed as mitigation in cluster 31 are evaluated in this weak grid assessment:

  • Network Upgrade 2: Moving AF2-222 and AG1-285 to a new 230 kV line from Farmville to Finneywood
    • Evaluated in the main body of this report
  • Network Upgrade 3: Upgrading the new AG1-285 230 kV substation to a breaker and a half scheme to accommodate 2 x 230/115 kV AG1-285 transformers, and a 230 kV line from AG1-285 to Finneywood
    • Evaluated in Appendix B
    • This option has been selected by the Transmission Owner

First, the individual project PSCAD models were evaluated for data consistency and model performance as part of the standard Model Quality Test in [2] and [3], with model updates being made where needed.  INS confirmed that the PSCAD models were set up properly and satisfied the requirements of PJM. After satisfactory configuration and performance of the individual projects were obtained, the models were integrated into a translated reduced network in PSCAD to create an overall detailed system model. 

 

For Network Upgrade 2, two representative contingency cases from the Cluster Study, considered effectively the worst case in terms of risk for weak grid instability, were simulated in the PSCAD detailed system model. For Cluster 31, the following contingency cases were chosen.

 

  • P=1.0pu, 3LG fault, 150ms, on AF2-171 POI to Farmville 230kV and loss of circuit
  • P=1.0pu, 3LG fault, 150ms, on AG1-427 to Finneywood 230kV and loss of circuit

 

Simulation results in PSCAD are summarized below.  It can be observed that both contingency cases using the detailed PSCAD system model results in a stable recovery, matching the results of the Cluster Study. 

 

Table 4. Summary of cases tested in the PSCAD system study with Network Upgrade 2

 

 

 

Case ID

Fault Description

Cluster Study Result [1]

PSCAD Study Result

Case 1.0

P=1.0pu, 3LG fault, 150ms, on AF2-171 POI to Farmville 230kV and loss of circuit

Stable

Stable

Case 2.0

P=1.0pu, 3LG fault, 150ms, on AG1-427 to Finneywood 230kV and loss of circuit

Stable

Stable

 

For Network Upgrade 3, three representative contingency cases from the Cluster Study, considered effectively the worst case in terms of risk for weak grid instability, were then simulated in the PSCAD detailed system model. Simulation results in PSCAD are summarized below.  It can be observed that all three contingency cases using the detailed PSCAD system model results in a stable recovery, matching the results of the Cluster Study. 

 

 

Table 5. Summary of cases tested in the PSCAD system study with Network Upgrade 3

 

 

 

Case ID

Fault Description

Cluster Study Result [1]

PSCAD Study Result

Case 3.1
(SP1.01)

P=1.0pu, 3LG fault, 150ms, on AF2-222 115 kV on Pamplin 115 kV circuit 154 and loss of circuit

Stable

Stable

Case 3.2
(SP1.10)

P=1.0pu, 3LG fault, 150ms, on AG1-285 POI switching station 115 kV on Chase City 115 kV circuit 1012 and loss of circuit

Stable

Stable

Case 3.3
(SP1.51)

P=1.0pu, 3LG fault, 150ms, on Finneywood 230 kV on AG1-285 – Finneywood 230 kV circuit and loss of circuit 

Stable

Stable

 

The results of this assessment show stable recovery in worst-case contingencies using either Network Upgrade 2 or 3, and support the conclusion from the Cluster Study that these proposed network upgrades mitigate the identified weak grid instability issues.

Reactive Power Analysis

The reactive power capability of AF2-222 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-065Earleys 230kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-088Boykins-Handsome 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB1-173Brink-Trego 115kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-100Clubhouse-Lakeview 230kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVEngineering & Procurement
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-080Perth-Hickory Grove 115kVIn Service
AC1-086Thelma 230kVUnder Construction
AC1-098Dawson-South Justice 115kVIn Service
AC1-099Dawson-South Justice 115kVIn Service
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-216Hopewell-Surry 230kVIn Service
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVUnder Construction
AC2-084Dawson-South Justice 115kVIn Service
AC2-100Halifax-Person 230kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-103Holland-Union Camp 115 kVSuspended
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-149Disputanta-Poe 115 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE2-027Harrowgate-Locks 115kVSuspended
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVIn Service
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVWithdrawn
AE2-156Yadkin 115 kVEngineering & Procurement
AE2-185Gladys DP-Stonemill Switching Station 69 kVEngineering & Procurement
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-247Myrtle-Windsor 115 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVEngineering & Procurement
AE2-346Ahoskie 34.5 kVIn Service
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-123Harper 230 kVUnder Construction
AF1-124Harper 230 kVPartially in Service - Under Construction
AF1-125Harper 230 kVUnder Construction
AF1-128Chesterfield 230 kVUnder Construction
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVUnder Construction
AF1-294Jetersville-Ponton 115 kVEngineering & Procurement
AF2-042Clover-Rawlings 500 kVEngineering & Procurement
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-081Moyock 230 kVEngineering & Procurement
AF2-085Midlothian 34.5 kVIn Service
AF2-110Suffolk 115 kVWithdrawn
AF2-115Jetersville-Ponton 115 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-299Fields 34.5 kVEngineering & Procurement
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-021Jetersville-Ponton 115 kVEngineering & Procurement
AG1-037Ahoskie 34.5 kVWithdrawn
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-105Mount Laurel-Barnes Junction 115 kVUnder Construction
AG1-135Garner-Lancaster 115 kVUnder Construction
AG1-145Lightfoot 34.5 kVIn Service
AG1-153Heritage 500 kVUnder Construction
AG1-285Chase City-Central 115 kVEngineering & Procurement
AG1-342Dryburg 115 kVEngineering & Procurement
AG1-532Fields 34.5 kVUnder Construction
V4-068Murphy's 34.5kVIn Service
W1-029Winfall 230kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z1-068Birdneck 34.5kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-088Tarboro-Everetts 230kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In coordination with other Affected System Operators, PJM has determined that the Affected System Operator for this project that requires an Affected System Study. For the latest Affected System Study results pertaining this project, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM lists any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AF2-222 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionn9220.0Wreck and rebuild 15.49 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.Cost Allocated$8,159,120
Dominionn9217.0Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.Cost Allocated$7,415,536
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$3,203,201
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$2,864,613
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$1,827,098
Dominionn9378.0Replace existing 230/500 kV Carson transformer #1 with (4)-480 MVA single phase transformers.Cost Allocated$1,827,058
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$1,011,031
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$796,917
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$647,539
Dominionn9681.0Upgrade 1.04 Miles of 230kV transmission line 249 from 249/86 to 249/93Cost Allocated$541,856
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0N/A
Dominionb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0N/A
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0N/A
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0N/A
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0N/A
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0N/A
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0N/A
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0N/A
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0N/A
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0N/A
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0N/A
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0N/A
Dominions3671.5Rebuild Line 238 from Carson to Clubhouse for a normal summer rating of 1573 MVAContingent$0N/A
Grand Total:$28,293,969

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Discounted Total Cost ($USD)
$19,755,576
Allocated Cost ($USD)
$10,288,736
Time Estimate
Dec 31 2029

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

FacilityContingency
3FARMVIL-3WILLIS 115.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
3CHASCTY-AG1-285 TP 115.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-294 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
41.0 MW4.3%$841,778
AF2-115 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
25.0 MW2.6%$513,287
AF2-222500.9 MW52.1%$10,288,736
AG1-021 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
20.0 MW2.1%$410,629
AG1-285374.9 MW39.0%$7,701,147
System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Allocated Cost ($USD)
$2,864,613
Time Estimate
Dec 31 2029
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$9,643,407
AF1-12413.4979 %$9,677,731
AF1-12513.2418 %$9,494,085
AF1-2940.3249 %$232,973
AF2-04231.9983 %$22,942,056
AF2-1150.1981 %$142,059
AF2-1205.8297 %$4,179,767
AF2-2223.9954 %$2,864,613
AG1-0210.1585 %$113,647
AG1-1243.1793 %$2,279,469
AG1-1355.5860 %$4,005,041
AG1-2852.9906 %$2,144,197
AG1-5365.5494 %$3,978,787

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.49 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Discounted Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$8,159,120
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
6BUCKING-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A796.0 MVA
(All)B796.0 MVA
(All)C964.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE2-29113.6 MW3.8%$1,705,384
AF1-294 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
17.8 MW5.0%$2,229,393
AF2-042163.5 MW46.2%$20,532,412
AF2-115 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
10.8 MW3.1%$1,359,435
AF2-22265.0 MW18.3%$8,159,120
AG1-021 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
8.7 MW2.4%$1,087,573
AG1-10523.6 MW6.7%$2,967,877
AG1-28541.9 MW11.8%$5,264,576
AG1-3429.2 MW2.6%$1,160,153

System Reinforcement: n9217.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9217.0 / TC1-PH2-DOM-028
Title
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$40,414,822
Discounted Total Cost ($USD)
$40,414,822
Allocated Cost ($USD)
$7,415,536
Time Estimate
45 to 46 Months

Contributor

FacilityContingency
6BUCKING-6FARMVIL 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A797.0 MVA
(All)B797.0 MVA
(All)C1116.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE2-29113.6 MW3.8%$1,550,409
AF1-294 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
17.8 MW5.0%$2,026,247
AF2-042163.5 MW46.2%$18,661,737
AF2-115 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
10.8 MW3.1%$1,235,466
AF2-22265.0 MW18.3%$7,415,536
AG1-021 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
8.7 MW2.4%$988,419
AG1-10523.6 MW6.7%$2,697,555
AG1-28541.9 MW11.8%$4,784,850
AG1-3429.2 MW2.6%$1,054,602

System Reinforcement: n9378.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9378.0 / TC1-PH3-DOM-010
Title
Replace existing 230/500 kV Carson transformer #1 with (4)-480 MVA single phase transformers.
Description
Replace Existing 230/500 kV Carson transformer #1 with (4)-480 MVA Single Phase transformers. 6CARSON - 8CARSON ckt 2 represents tranformer #1.
Total Cost ($USD)
$37,801,301
Discounted Total Cost ($USD)
$37,801,301
Allocated Cost ($USD)
$1,827,058
Time Estimate
Mar 29 2029

Contributor

FacilityContingency
6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer(Any)
Rating SetRating TypeRating Value
LLA2016.0 MVA
LLB2083.0 MVA
LLC2239.0 MVA
SUMA1707.0 MVA
SUMB1758.0 MVA
SUMC1873.0 MVA
WINA2196.0 MVA
WINB2228.0 MVA
WINC2308.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
56.2 MW22.4%$8,456,365
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
56.5 MW22.5%$8,486,733
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
55.4 MW22.0%$8,324,368
AF2-04259.5 MW23.7%$8,947,219
AF2-22212.2 MW4.8%$1,827,058
AG1-15311.7 MW4.7%$1,759,557

System Reinforcement: n9681.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9681.0
Title
Upgrade 1.04 Miles of 230kV transmission line 249 from 249/86 to 249/93
Description
Reconductor 1.04 miles of 2*636 ACSR 24/7 MOT 150 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" MOT 250 on 230 kV line 249 between Carson and Chaparral
Total Cost ($USD)
$3,042,004
Discounted Total Cost ($USD)
$3,042,004
Allocated Cost ($USD)
$541,856
Time Estimate
20 to 21 Months

Contributor

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1442.0 MVA
LLB1540.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1493.0 MVA
WINB1587.0 MVA
WINC1631.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-04256.7 MW67.3%$2,048,312
AF2-22215.0 MW17.8%$541,856
AG1-28512.5 MW14.9%$451,836

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH3-DOM-009
Title
ELIMINATED FOR TC1: Replace 795 AAC 37 line lead at Farmville 115 kV.
Description
Replace 795 AAC 37 line lead at Farmville 115 kV.
Total Cost ($USD)
$391,643
Discounted Total Cost ($USD)
$107,913
Allocated Cost ($USD)
$61,665
Time Estimate
12 to 13 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
3FARMVIL-3WILLIS 115.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A270.0 MVA
(All)B289.0 MVA
(All)C351.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-222100.0 MW57.1%$61,665
AG1-28575.0 MW42.9%$46,248

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 may need this upgrade in-service to be deliverable to the PJM system. If AF2-222 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 may need this upgrade in-service to be deliverable to the PJM system. If AF2-222 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 may need this upgrade in-service to be deliverable to the PJM system. If AF2-222 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 may need this upgrade in-service to be deliverable to the PJM system. If AF2-222 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 may need this upgrade in-service to be deliverable to the PJM system. If AF2-222 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 may need this upgrade in-service to be deliverable to the PJM system. If AF2-222 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 may need this upgrade in-service to be deliverable to the PJM system. If AF2-222 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 may need this upgrade in-service to be deliverable to the PJM system. If AF2-222 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 may need this upgrade in-service to be deliverable to the PJM system. If AF2-222 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 may need this upgrade in-service to be deliverable to the PJM system. If AF2-222 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 may need this upgrade in-service to be deliverable to the PJM system. If AF2-222 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029
Cost Alloc Type
Contingent

System Reinforcement: b3694.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3694.8
Title
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA.
Description
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA. Upgrade terminal equipment at Carson and Locks to not limit the new conductor rating.
Cost Information
Time Estimate
May 03 2025

Not Contingent

Note: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1047.0 MVA
(All)B1047.0 MVA
(All)C1204.0 MVA
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA

System Reinforcement: s3671.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3671.5
Title
Rebuild Line 238 from Carson to Clubhouse for a normal summer rating of 1573 MVA
Description
Rebuild Line 238 from Carson to Clubhouse for a normal summer rating of 1573 MVA
Cost Information
Time Estimate
Dec 31 2030

Contingent

Note: Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 may need this upgrade in-service to be deliverable to the PJM system. If AF2-222 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA
6SAPONY-AE2-033 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.18
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.18
Title
Rebuild approximately 37.4 miles of 500 kV line No. 563 from Carson-Midlothian.
Description
Rebuild approximately 37.4 miles of 500 kV line No. 563 from Carson-Midlothian. The proposed structures to be installed are mainly 500/230 kV double-circuit V-string suspension towers. The 230 kV circuit position will be vacant at the completion of this project but serves to accommodate a future 230 kV line.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4357.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA5155.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b4053.19
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.19
Title
Uprate 500 kV line No. 563 associated terminal equipment at Carson to 5000A standards.
Description
Uprate 500 kV line No. 563 associated terminal equipment at Carson to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4357.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA5155.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b4053.20
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.20
Title
Uprate 500 kV line No. 563 associated terminal equipment at Midlothian to 5000A standards.
Description
Uprate 500 kV line No. 563 associated terminal equipment at Midlothian to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4357.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA5155.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b4053.21
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.21
Title
Uprate 500 kV line No. 567 associated terminal equipment at Chickahominy to 5000A standards.
Description
Uprate 500 kV line No. 567 associated terminal equipment at Chickahominy to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3322.0 MVA
(All)B3425.0 MVA
(All)C3939.0 MVA
WINA4191.0 MVA
WINB4376.0 MVA
WINC5032.0 MVA

System Reinforcement: b4053.22
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.22
Title
Uprate 500 kV line No. 567 associated terminal equipment at Surry to 5000A standards.
Description
Uprate 500 kV line No. 567 associated terminal equipment at Surry to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3322.0 MVA
(All)B3425.0 MVA
(All)C3939.0 MVA
WINA4191.0 MVA
WINB4376.0 MVA
WINC5032.0 MVA

System Reinforcement: n9138.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9138.0 / TC1-PH1-DOM-070
Title
ELIM TC1: Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.
Description
Wreck and rebuild 22.59 miles of Line 511 between Carson and Rawlings with three (3) 1351 ACSS/TW and associated substation work.
Total Cost ($USD)
$111,130,292
Discounted Total Cost ($USD)
$111,130,292
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-222 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-222 could receive cost allocation. Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9250.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9250.0 / TC1-PH2-DOM-044
Title
ELIM TC1: Construct a new 22.59 mile line between Carson and Rawlings Substations.
Description
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Total Cost ($USD)
$108,728,086
Discounted Total Cost ($USD)
$108,728,086
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-222 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-222 could receive cost allocation. Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.

System Reinforcement: b4053.27
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.27
Title
Upgrade/install 6000A equipment at Midlothian substation to support the new conductor termination from Vontay.
Description
Upgrade/install 6000A equipment at Midlothian substation to support the new conductor termination from Vontay.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: b4053.6
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.6
Title
Rebuild 20 miles of 500 kV line No. 576 from North Anna substation to Vontay substation using 6000A conductor.
Description
Rebuild 20 miles of 500 kV line No. 576 from North Anna substation to Vontay substation using 6000A conductor.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: b4053.7
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.7
Title
Upgrade/install 6000A equipment at North Anna substation to support the new conductor termination.
Description
Upgrade/install 6000A equipment at North Anna substation to support the new conductor termination.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: b4053.26
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.26
Title
Rebuild 20 miles of 500 kV line No. 576 from Vontay substation to Midlothian substation using 6000A conductor.
Description
Rebuild 20 miles of 500 kV line No. 576 from Vontay substation to Midlothian substation using 6000A conductor.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-040
Title
ELIM TC1: Wreck and rebuild 18.75 miles of Line 594 btwn Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) Dipper at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 18.75 miles of Line 594 between Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$128,018,212
Discounted Total Cost ($USD)
$128,018,212
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-222 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-222 could receive cost allocation. Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9247.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9247.0 / TC1-PH2-DOM-041
Title
ELIM TC1: Wreck and rebuild 14.02 miles of Line 573 btwn Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 14.02 miles of Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA
Total Cost ($USD)
$99,636,684
Discounted Total Cost ($USD)
$99,636,684
Allocated Cost ($USD)
$0
Time Estimate
48 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-222 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-222 could receive cost allocation. Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n8492

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492
Title
Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.
Description
Wreck and rebuild one (1) overhead 500kV transmission line that will start at the existing Fentress 500 kV Substation and terminate at the existing Yadkin 500 kV Substation, located approximately 13.5 miles away.
Total Cost ($USD)
$80,172,278
Allocated Cost ($USD)
$3,203,201
Time Estimate
Dec 31 2026
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$10,783,252
AF1-12413.4979 %$10,821,574
AF1-12513.2418 %$10,616,253
AF1-2940.3249 %$260,480
AF2-04231.9983 %$25,653,766
AF2-1150.1981 %$158,821
AF2-1205.8297 %$4,673,803
AF2-2223.9954 %$3,203,203
AG1-0210.1585 %$127,073
AG1-1243.1793 %$2,548,917
AG1-1355.5860 %$4,478,423
AG1-2852.9906 %$2,397,632
AG1-5365.5494 %$4,449,080

System Reinforcement: n9267.0

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9267.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9267.0 / TC1-PH2-DOM-067
Title
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.
Description
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner substations with single (1) 768.2 ACSS/TW “Maumee” at 250 degrees C. This new line will be on separate transmission towers from the existing Northern Neck and Moon Corner line 1059. Station expansion is required at Northern Neck and Moon Corner to accommodate the new line.
Total Cost ($USD)
$45,730,074
Allocated Cost ($USD)
$1,827,098
Time Estimate
45 to 46 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$6,150,741
AF1-12413.4979 %$6,172,600
AF1-12513.2418 %$6,055,485
AF1-2940.3249 %$148,577
AF2-04231.9983 %$14,632,846
AF2-1150.1981 %$90,591
AF2-1205.8297 %$2,665,926
AF2-2223.9954 %$1,827,099
AG1-0210.1585 %$72,482
AG1-1243.1793 %$1,453,896
AG1-1355.5860 %$2,554,482
AG1-2852.9906 %$1,367,604
AG1-5365.5494 %$2,537,745

System Reinforcement: n9259.0

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9259.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9259.0
Title
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Description
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Total Cost ($USD)
$25,304,902
Allocated Cost ($USD)
$1,011,031
Time Estimate
Jan 01 2030
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$3,403,535
AF1-12413.4979 %$3,415,630
AF1-12513.2418 %$3,350,825
AF1-2940.3249 %$82,216
AF2-04231.9983 %$8,097,138
AF2-1150.1981 %$50,129
AF2-1205.8297 %$1,475,200
AF2-2223.9954 %$1,011,032
AG1-0210.1585 %$40,108
AG1-1243.1793 %$804,519
AG1-1355.5860 %$1,413,532
AG1-2852.9906 %$756,768
AG1-5365.5494 %$1,404,270

System Reinforcement: n8492.1

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.1
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.1
Title
Two Breaker Additions at Fentress Substation.
Description
Install Two 5000 amp GIS Breakers at Fentress Substation to connect the new 500 kV line 5005.
Total Cost ($USD)
$19,945,879
Allocated Cost ($USD)
$796,917
Time Estimate
Dec 31 2026
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$2,682,741
AF1-12413.4979 %$2,692,275
AF1-12513.2418 %$2,641,193
AF1-2940.3249 %$64,804
AF2-04231.9983 %$6,382,342
AF2-1150.1981 %$39,513
AF2-1205.8297 %$1,162,785
AF2-2223.9954 %$796,918
AG1-0210.1585 %$31,614
AG1-1243.1793 %$634,139
AG1-1355.5860 %$1,114,177
AG1-2852.9906 %$596,501
AG1-5365.5494 %$1,106,877

System Reinforcement: n8492.2

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.2
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.2
Title
Expand Yadkin Substation to accommodate the new 500 kV line.
Description
Expansion of yadkins 500 kV switchyard to accommodate the new 500 kV line which includes addition of 5000 amp GIS breakers and relocation of the existing suffolk -yadkin 500 kV line#565
Total Cost ($USD)
$16,207,123
Allocated Cost ($USD)
$647,539
Time Estimate
Dec 31 2026
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12313.4501 %$2,179,874
AF1-12413.4979 %$2,187,621
AF1-12513.2418 %$2,146,115
AF1-2940.3249 %$52,657
AF2-04231.9983 %$5,186,004
AF2-1150.1981 %$32,106
AF2-1205.8297 %$944,827
AF2-2223.9954 %$647,539
AG1-0210.1585 %$25,688
AG1-1243.1793 %$515,273
AG1-1355.5860 %$905,330
AG1-2852.9906 %$484,690
AG1-5365.5494 %$899,398

System Reinforcement: b4000.356

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.355

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.325

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.326

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.327

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: s3047.2

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: s3047.2
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3047.2
Title
Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.
Description
Install (2) 1400 MVA 500-230 kV transformers and associated 500 kV and 230 kV equipment (breakers, switches, leads) at Vint Hill Substation to supply the area with a 500 kV source Cut and loop 500 kV line #535 Loudoun – Meadowbrook and #569 Loudoun - Morrisville as the 500 kV sources into the proposed 500 kV ring bus Vint Hill Substation will be expanded to the north of the existing site to accommodate the 500 kV ring required for the addition of the new transformers Existing terminations for 230 kV line #2174 Wheeler – Vint Hill, line #2101 Bristers – Vint Hill, and line #2163 Liberty – Vint Hill will be rearranged to terminate into the expanded Vint Hill Substation 230 kV line #2114 Remington CT – Rollins Ford will also be cut and looped into the expanded Vint Hill Substation due to spatial constraints along the existing right-of-way.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.312

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.312
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.312
Title
Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.
Description
Rebuild 500kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. New conductor to have a summer rating of 4357 MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.313

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.313
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.313
Title
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Description
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.356

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.356
Title
Build a new 500 kV line from Vint Hill to Wishing Star.
Description
Build a new 500kV line from Vint Hill to Wishing Star. The line will be supported on single circuit monopoles. New conductor to have a summer rating of 4357 MVA. Line length is approximately 16.59 miles
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.357

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.357
Title
Build a new 500 kV line from Morrisville to Vint Hill.
Description
Build a new 500kV line from Morrisville to Vint Hill. New conductor to have a summer rating of 4357 MVA. Line length is approximately 19.71 miles.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.354

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.354
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.354
Title
Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.
Description
Install terminal equipment at Wishing Star substation to support a 5000A line to Vint Hill. Update relay settings for 500kV Lines #546 and #590.
Cost Information
Cost Alloc Type
Contingent

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AF2-222


AF2-222 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
StabilityDominionn9630.0 / TC1-PH3-DOM-013Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Topology500.9 MW52.1%Cost Allocated$10,288,736
Load FlowDominion(Pending) / TC1-PH3-DOM-009ELIMINATED FOR TC1: Replace 795 AAC 37 line lead at Farmville 115 kV.Eliminated100.0 MW57.1%Cost Allocated$61,665
Load FlowDominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Topology-0.0%Contingent$0
Load FlowDominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Topology-0.0%Contingent$0
Load FlowDominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationTopology-0.0%Contingent$0
Load FlowDominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Topology-0.0%Contingent$0
Load FlowDominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$10,350,401
AF2-222 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$3,203,201
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$2,864,613
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$1,827,098
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$1,011,031
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$796,917
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$647,539
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0
Dominionb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0
Region Topology Upgrade Total:$10,350,399

Attachments

AF2-222 One Line Diagram

AF2-222 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.