AF2-222 Final System Impact Study (Retool 1) Report

v1.00 released 2025-12-08 18:19

Madisonville DP-Twitty's Creek 115 kV

100.0 MW Capacity / 167.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia), and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the TC1 projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.
Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of TC1 projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed a Solar generating facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Charlotte County, Virginia. The installed facilities will have a total capability of 167.0 MW with 100.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AF2-222
Project Name:
Madisonville DP-Twitty's Creek 115 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
State:
Virginia
County:
Charlotte
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
167.0
MWE:
167.0
MWC:
100.0
Fuel Type:
Solar
Basecase Study Year:
2027

Physical Interconnection Facility Study

Received

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AF2-222 will interconnect with the Dominion transmission system via a three breaker switching station on Line 154 between Madisonville and Twitty's Creek 115 kV substations.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AF2-222 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AF2-222Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$1,080,391$1,080,391
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$11,332,601$11,332,601
Network Upgrades$4,742,414$4,742,414
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$31,872,537$31,872,537
Transient Stability$9,766,518$9,766,518
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$58,794,462$58,794,462

* Contributes to calculation for Security. See Security Section of this report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF2-222

Security has been calculated for the AF2-222 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF2-222
Project(s): AF2-222
Final Agreement Security (A): $58,794,462
Portion of Costs Already Paid (B): $2,061,057
Revised Net Security (C): A − B = $56,733,405
Security on Hand with PJM (D): $58,018,028
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

AF2-222 will interconnect with the Dominion transmission system at a new three breaker switching station on Line 154 between Madisonville and Twitty's Creek 115 kV substations. 

The required work for the interconnection of the New Service Request Project to the Dominion Transmission System is detailed in the following tables.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n8205.2

Re-arrange line 154 to loop into and out of the new three-breaker AF2-222 115 kV switching station.

$2,376,518$1,466,265$232,561$63,972$4,139,316$4,139,316
n9655.0

Remote end substation work at Chase City to support new interconnection substation

$67,868$35,494$18,904$6,323$128,589$128,589
n9656.0

Remote end substation work at Farmville to support new interconnection substation

$71,122$28,814$19,898$5,133$124,967$124,967
n9657.0

Remote end substation work at Pamplin to support new interconnection substation

$74,008$28,814$20,618$5,133$128,573$128,573
n9658.0

Remote end substation work at Twitty's Creek to support new interconnection substation

$107,219$71,832$29,121$12,797$220,969$220,969
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n8205.1

Build a new 115 kV three-breaker ring switching station located along line 154 from Pamplin Substation to Twitty Creek Substation.

$5,902,826$3,429,077$1,548,448$452,250$11,332,601$11,332,601
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

A 115 kV backbone structure and foundation within the fence of the Interconnection Substation, to terminate the Project Developer’s generator lead line. Line conductor from the structure to the bus position in the switchyard of the interconnection substation.

$649,633$236,109$162,373$32,276$1,080,391$1,080,391

Based on the scope of work for the Interconnection Facilities, it is expected to take 47 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

 

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2027 load flow model and the results were verified by Dominion.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AF2-222 was evaluated as a 167.0 MW (100.0 MW Capacity) injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BUCKING-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S-1
BreakerAC116.16 %699.0C811.9764.98
GD1DVP
6BUCKING-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC113.03 %571.52B645.9938.88
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC110.49 %1204.0C1330.3414.99
GD1DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC108.7 %1204.0C1308.7814.99
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC100.22 %678.68B680.188.64
GD1DVP
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S-1
BreakerAC117.22 %684.0C801.7964.99
GD1DVP
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC114.05 %559.3B637.8638.89
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC112.21 %678.68B761.578.63
GD1DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 56372_SRT-S
BreakerAC113.54 %1056.8C1199.8612.15
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC106.16 %3940.0C4182.7436.24
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC104.22 %3940.0C4106.1235.06
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H1T567_SRT-A
BreakerAC103.44 %3940.0C4075.5535.65
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
SingleAC100.39 %1058.16B1062.255.57
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S_SENS
SingleAC102.07 %3220.44B3287.0123.07
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC102.59 %3144.0C3225.3225.81
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC102.48 %3144.0C3221.9726.18
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC102.48 %3144.0C3221.9726.18
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC102.48 %3144.0C3221.8126.18
GD1DVP
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC109.42 %678.68B742.638.64

Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.16 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:811.97
MW Contribution:64.98
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.96 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:845.48
MW Contribution:61.73
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
925612AC1-036 E
50/50
1.961.96
924312AB2-078 E O1
Adder
2.3152941176470591.968
926274AC1-105 E
Adder
4.0129411764705883.411
938821AE1-108 C
Adder
-10.607058823529412-9.016
957481AF2-042 C
50/50
98.10798.107
924322AB2-079 E O1
Adder
2.3152941176470591.968
946302AF1-294 E
50/50
8.1418.141
943902AF1-058 E
Adder
1.841.564
924302AB2-077 E O1
Adder
2.3152941176470591.968
942752AE2-291 E
Adder
5.4329411764705894.618
936262AD2-033 E
50/50
18.44618.446
958211AF2-115 C
50/50
5.8465.846
316336AC2-165 C
Adder
-5.905882352941176-5.02
934622AD1-088 E
50/50
9.1029.102
934612AD1-087 E
Adder
6.3835294117647065.426
927255AC1-221 E
Adder
4.1458823529411773.524
3151531CLOVER1
50/50
22.522.5
964241AG1-285 C
50/50
25.15525.155
316034AC1-036 C
50/50
0.5350.535
958212AF2-115 E
50/50
4.984.98
962561AG1-105 C
Adder
14.18117647058823612.054
937482AD2-202 E
Adder
1.86823529411764721.588
961792AG1-021 E
50/50
3.9843.984
941011AE2-092 C
Adder
-9.729411764705882-8.27
924022AB2-043 E O1
Adder
9.122352941176477.754
3147223TWITTYS
50/50
2.1732.173
959312AF2-222 E
50/50
26.06826.068
926024AC1-080 E
Adder
1.09882352941176480.934
957482AF2-042 E
50/50
65.40565.405
934621AD1-088 C
50/50
18.90418.904
946301AF1-294 C
50/50
9.6139.613
942461AE2-259 C
50/50
31.1431.14
935172AD1-152 E
Adder
8.887.548
964242AG1-285 E
50/50
16.7716.77
924162AB2-060 E OP
Adder
7.6670588235294136.517
964792AG1-342 E
Adder
3.6952941176470593.141
932763AC2-100 E
Adder
2.72941176470588242.32
3147133PAMPLIN
50/50
2.7572.757
316322AB2-045 C
50/50
1.2941.294
927264AC1-222 E
Adder
5.52000000000000054.692
925785AC1-054 E
Adder
3.35529411764705852.852
959311AF2-222 C
50/50
38.90838.908
942751AE2-291 C
Adder
8.1482352941176476.926
942462AE2-259 E
50/50
20.7620.76
964791AG1-342 C
Adder
5.5435294117647054.712
925997AC1-075 E
Adder
3.31294117647058832.816
3138533PONTONDP
50/50
1.7321.732
936261AD2-033 C
50/50
27.66927.669
961791AG1-021 C
50/50
4.6774.677
3144293JTRSVLE
50/50
1.0761.076
962562AG1-105 E
Adder
9.4541176470588238.036
924032AB2-045 E
50/50
5.85.8
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.3429.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.2887.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.2261.226
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8050.805
SIGELTFEXP_SIGE->PJM
CLTF
0.0740.074
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1652.165
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.04736.047
CPLELTFEXP_CPLE->PJM
CLTF
4.5424.542
TVALTFEXP_TVA->PJM
CLTF
2.0142.014
O66PJM->LTFIMP_O-066
CMTX_NF
5.1335.133
NYPJM->LTFIMP_NY
CLTF
0.3840.384
LGEELTFEXP_LGEE->PJM
CLTF
0.3670.367
WECLTFEXP_WEC->PJM
CLTF
0.1940.194

Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.03 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:645.99
MW Contribution:38.88
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.98 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:685.72
MW Contribution:36.94
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151261ROARAP2
80/20
0.6810.681
3147043LAWRENC
80/20
0.2660.266
3151621KERR 5
80/20
1.5611.561
316222AC1-221 C
80/20
1.5791.579
316336AC2-165 C
Adder
-5.884705882352941-5.002
934611AD1-087 C
80/20
2.212.21
316049AB1-081 C OP
80/20
0.4770.477
3151611KERR 4
80/20
1.5611.561
962571AG1-106 C
80/20
0.8210.821
932631AC2-084 C
80/20
0.3610.361
316274AC1-208 C
80/20
3.5413.541
3151311EDGECMA
80/20
5.0375.037
3151601KERR 3
80/20
1.5611.561
3151581KERR 1
80/20
0.5570.557
3152661PLYWOOD A
80/20
1.751.75
966621AG1-532 C
80/20
0.7060.706
316003AC1-222 C
80/20
1.3481.348
936161AD2-022 C
80/20
3.6193.619
941011AE2-092 C
Adder
-9.714117647058824-8.257
3137643SOCKMAN
80/20
0.3520.352
316212AC1-099 C
80/20
0.1130.113
316319Z2-044 C
80/20
0.0740.074
937481AD2-202 C
80/20
0.6410.641
3151641KERR 7
80/20
1.5611.561
316123AC1-075 C
80/20
0.9530.953
316205AC1-080 C
80/20
0.3190.319
316087AB2-174 C
80/20
0.5880.588
313527AB2-043 C
80/20
0.9080.908
3151591KERR 2
80/20
1.5611.561
316283AC2-100 C
80/20
1.2351.235
316011AB1-132 C OP
80/20
0.7050.705
316263AC1-034 C
80/20
2.2292.229
959311AF2-222 C
80/20
38.88338.883
942751AE2-291 C
80/20
8.1298.129
3151561HALLBR1
80/20
0.5580.558
316322AB2-045 C
80/20
1.2941.294
3151411GASTONB
80/20
0.9230.923
316181AB2-040 GEN
80/20
0.6330.633
3156063AA2-053SOLA
80/20
0.6790.679
3151281ROARAP4
80/20
0.6440.644
316238AB2-078 C O1
80/20
0.5670.567
316237AB2-079 C O1
80/20
0.5670.567
938821AE1-108 C
Adder
-10.596470588235293-9.007
3156073AA1-063SOLA
80/20
0.5840.584
3151371ROSEMS1
80/20
0.3840.384
934621AD1-088 C
80/20
18.88618.886
316359AB2-059 C OP
80/20
0.5620.562
946301AF1-294 C
80/20
9.6099.609
942461AE2-259 C
80/20
31.13331.133
316197AC1-042 C
80/20
0.1420.142
316210AC1-098 C
80/20
0.3390.339
316327AA2-057 C
80/20
0.4730.473
316239AB2-077 C O1
80/20
0.5670.567
935171AD1-152 C
80/20
2.1552.155
964791AG1-342 C
80/20
5.5355.535
313506AB1-173 C OP
80/20
0.5620.562
3151361ROSEMG1
80/20
0.6210.621
957481AF2-042 C
80/20
97.99997.999
946281AF1-292 C
80/20
0.7790.779
926071AC1-086 C
80/20
6.3516.351
3151531CLOVER1
80/20
22.47222.472
964241AG1-285 C
80/20
25.13225.132
316034AC1-036 C
80/20
0.5340.534
962561AG1-105 C
80/20
14.16114.161
942671AE2-283 C
80/20
1.5211.521
316129AC1-054 C
80/20
1.1891.189
316131AB2-060 C
80/20
2.662.66
3138533PONTONDP
80/20
1.7311.731
316118AC1-105 C
80/20
1.3691.369
316217AC1-145 C
80/20
0.1690.169
960081AF2-299 C
80/20
0.9410.941
3151541CLOVER2
80/20
22.26222.262
3151631KERR 6
80/20
1.5611.561
936261AD2-033 C
80/20
27.64927.649
961791AG1-021 C
80/20
4.6754.675
3144293JTRSVLE
80/20
1.0761.076
316248AF1-058 C
80/20
0.450.45
936171AD2-023 C
80/20
2.1112.111
941801AE2-185 C
80/20
1.9561.956
3151391GASTONA
80/20
0.9230.923
3151381ROSEMG2
80/20
0.2910.291
934331AD1-057 C
80/20
1.1031.103
934321AD1-056 C
80/20
1.9781.978
958211AF2-115 C
80/20
5.8435.843
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.0479.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.0847.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1891.189
LAGNLTFEXP_LAGN->PJM
CLTF
2.5082.508
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1162.116
CBM South 2LTFEXP_CBM-S2->PJM
CBM
35.17235.172
CPLELTFEXP_CPLE->PJM
CLTF
4.444.44
TVALTFEXP_TVA->PJM
CLTF
1.9591.959
NYPJM->LTFIMP_NY
CLTF
0.3750.375
LGEELTFEXP_LGEE->PJM
CLTF
0.3550.355
WECLTFEXP_WEC->PJM
CLTF
0.1880.188

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.49 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1330.34
MW Contribution:14.99
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.67 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1404.76
MW Contribution:13.57
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316141AB2-099 E
Adder
0.125882352941176470.107
316088AB2-174 E
50/50
5.0815.081
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151361ROSEMG1
50/50
1.5051.505
957481AF2-042 C
50/50
34.00834.008
961672AG1-007 E
Adder
0.30352941176470590.258
924322AB2-079 E O1
Adder
0.7917647058823530.673
946302AF1-294 E
Adder
1.46000000000000021.241
943902AF1-058 E
Adder
0.71411764705882350.607
940541AE2-040 C
50/50
3.3223.322
940481AE2-033 C
50/50
18.24118.241
940482AE2-033 E
50/50
12.29712.297
923263AB1-132 E OP
50/50
4.64.6
3151411GASTONB
50/50
2.2972.297
316181AB2-040 GEN
50/50
0.9590.959
3151281ROARAP4
50/50
0.8680.868
3152441Z1-086 ST
50/50
13.14613.146
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
925612AC1-036 E
Adder
0.47058823529411770.4
924312AB2-078 E O1
Adder
0.7917647058823530.673
926274AC1-105 E
Adder
1.50823529411764711.282
3145393UNCAMP
Adder
2.10941176470588231.793
933981AD1-022 C
Adder
3.6082352941176473.067
900672V4-068 E
Adder
0.172941176470588240.147
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
924302AB2-077 E O1
Adder
0.7917647058823530.673
923852AB2-025 E
50/50
1.3441.344
939412AE1-173 E
Adder
33.1823529411764728.205
961942AG1-037 E
Adder
0.167058823529411760.142
961941AG1-037 C
Adder
0.251764705882352950.214
3151391GASTONA
50/50
2.2972.297
3151381ROSEMG2
50/50
0.7050.705
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934332AD1-057 E
Adder
1.21529411764705891.033
934331AD1-057 C
Adder
2.33411764705882341.984
934321AD1-056 C
Adder
4.1835294117647063.556
934322AD1-056 E
Adder
2.26941176470588251.929
927022AC1-189 E
Adder
2.28117647058823541.939
925595AC1-034 E
Adder
3.0235294117647062.57
936262AD2-033 E
Adder
4.6729411764705883.972
958211AF2-115 C
Adder
1.04823529411764720.891
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
933982AD1-022 E
Adder
1.9647058823529411.67
927146AC1-208 E
Adder
2.45294117647058842.085
934622AD1-088 E
Adder
2.72588235294117662.317
934612AD1-087 E
Adder
2.20941176470588241.878
927255AC1-221 E
Adder
2.0517647058823531.744
316023AB2-100 C2
50/50
0.8890.889
960082AF2-299 E
50/50
1.0391.039
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
3151051BRUNSWICKS1
50/50
12.19612.196
963042AG1-153 E
50/50
5.9665.966
927021AC1-189 C
Adder
4.5788235294117653.892
964241AG1-285 C
Adder
7.502352941176476.377
924152AB2-059 E OP
Adder
3.18705882352941172.709
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
936172AD2-023 E
Adder
1.21058823529411751.029
940492AE2-034 E
Adder
1.07647058823529430.915
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
924516AB2-100 E1
50/50
2.6782.678
918512AA1-065 E OP
Adder
2.60941176470588232.218
966621AG1-532 C
50/50
1.1691.169
918532AA1-067 E
Adder
0.367058823529411770.312
924022AB2-043 E O1
Adder
3.07764705882352942.616
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
926024AC1-080 E
Adder
0.454117647058823570.386
936161AD2-022 C
Adder
3.8235294117647063.25
918492AA1-063AE OP
Adder
2.40470588235294122.044
962571AG1-106 C
50/50
2.0442.044
316087AB2-174 C
50/50
0.9180.918
962572AG1-106 E
50/50
0.8940.894
926214AC1-099 E
Adder
0.70941176470588230.603
932632AC2-084 E
Adder
1.89764705882352951.613
964242AG1-285 E
Adder
5.0011764705882364.251
924162AB2-060 E OP
Adder
2.522.142
964792AG1-342 E
Adder
1.34588235294117631.144
932763AC2-100 E
Adder
1.3917647058823531.183
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
316274AC1-208 C
Adder
5.5235294117647074.695
917342Z2-044 E
Adder
0.36117647058823530.307
937482AD2-202 E
Adder
0.64705882352941180.55
3151311EDGECMA
Adder
9.4070588235294137.996
961792AG1-021 E
Adder
0.71411764705882350.607
920692AA2-178 E
Adder
1.43529411764705881.22
966622AG1-532 E
50/50
0.7790.779
922923AB1-081 E OP
Adder
2.24941176470588241.912
3147133PAMPLIN
Adder
0.454117647058823570.386
927264AC1-222 E
Adder
2.16588235294117661.841
939411AE1-173 C
Adder
49.7729411764705942.307
3137643SOCKMAN
50/50
0.5020.502
3151031BRUNSWICKG2
50/50
5.8715.871
919710AA2-057 E
Adder
2.3988235294117652.039
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
920042AA2-088 E OP
Adder
4.9317647058823534.192
934521AD1-076 C
Adder
4.7823529411764714.065
934511AD1-075 C
Adder
3.2917647058823532.798
3145723EMPORIA
50/50
0.3510.351
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
919692AA2-053 E OP
Adder
2.6788235294117652.277
925785AC1-054 E
Adder
2.1505882352941181.828
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
942001AE2-212 C
Adder
-3.7917647058823527-3.223
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
3151371ROSEMS1
50/50
0.9320.932
957482AF2-042 E
50/50
22.67222.672
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
946301AF1-294 C
Adder
1.7247058823529411.466
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
936162AD2-022 E
Adder
2.29411764705882341.95
3143316POE
Adder
0.51176470588235290.435
316365AB2-100 C1
50/50
0.8890.889
926206AC1-098 E
Adder
2.14705882352941171.825
3151041BRUNSWICKG3
50/50
5.8715.871
3151021BRUNSWICKG1
50/50
5.8715.871
942462AE2-259 E
Adder
2.62.21
964791AG1-342 C
Adder
2.0188235294117651.716
925997AC1-075 E
Adder
1.36941176470588231.164
316315AB2-025 C
50/50
0.4720.472
946282AF1-292 E
50/50
0.860.86
944012AF1-069 E
50/50
3.683.68
957861AF2-080 C
Adder
4.1588235294117653.535
917512Z2-088 E OP1
Adder
2.742.329
3138533PONTONDP
Adder
0.310588235294117660.264
3145413WATKINS
Adder
0.265882352941176460.226
960081AF2-299 C
50/50
1.5581.558
926072AC1-086 E
50/50
7.1937.193
944011AF1-069 C
50/50
9.4749.474
963041AG1-153 C
50/50
3.9773.977
957862AF2-080 E
Adder
1.84352941176470591.567
936261AD2-033 C
Adder
7.0082352941176475.957
961791AG1-021 C
Adder
0.83882352941176460.713
962562AG1-105 E
Adder
3.39764705882352922.888
936171AD2-023 C
Adder
2.23058823529411751.896
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.7 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1308.78
MW Contribution:14.99
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.88 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1383.11
MW Contribution:13.57
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316141AB2-099 E
Adder
0.125882352941176470.107
316088AB2-174 E
50/50
5.0815.081
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151361ROSEMG1
50/50
1.5051.505
957481AF2-042 C
50/50
34.00834.008
961672AG1-007 E
Adder
0.30352941176470590.258
924322AB2-079 E O1
Adder
0.7917647058823530.673
946302AF1-294 E
Adder
1.46000000000000021.241
943902AF1-058 E
Adder
0.71411764705882350.607
940541AE2-040 C
50/50
3.3223.322
940481AE2-033 C
50/50
18.24118.241
940482AE2-033 E
50/50
12.29712.297
923263AB1-132 E OP
50/50
4.64.6
3151411GASTONB
50/50
2.2972.297
316181AB2-040 GEN
50/50
0.9590.959
3151281ROARAP4
50/50
0.8680.868
3152441Z1-086 ST
50/50
13.14613.146
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
925612AC1-036 E
Adder
0.47058823529411770.4
924312AB2-078 E O1
Adder
0.7917647058823530.673
3145393UNCAMP
Adder
2.10941176470588231.793
933981AD1-022 C
Adder
3.6082352941176473.067
900672V4-068 E
Adder
0.172941176470588240.147
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
924302AB2-077 E O1
Adder
0.7917647058823530.673
923852AB2-025 E
50/50
1.3441.344
939412AE1-173 E
Adder
33.1823529411764728.205
961942AG1-037 E
Adder
0.167058823529411760.142
961941AG1-037 C
Adder
0.251764705882352950.214
3151391GASTONA
50/50
2.2972.297
3151381ROSEMG2
50/50
0.7050.705
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934332AD1-057 E
Adder
1.21529411764705891.033
934331AD1-057 C
Adder
2.33411764705882341.984
934321AD1-056 C
Adder
4.1835294117647063.556
934322AD1-056 E
Adder
2.26941176470588251.929
927022AC1-189 E
Adder
2.28117647058823541.939
925595AC1-034 E
Adder
3.0235294117647062.57
936262AD2-033 E
Adder
4.6729411764705883.972
958211AF2-115 C
Adder
1.04823529411764720.891
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
933982AD1-022 E
Adder
1.9647058823529411.67
927146AC1-208 E
Adder
2.45294117647058842.085
934622AD1-088 E
Adder
2.72588235294117662.317
934612AD1-087 E
Adder
2.20941176470588241.878
927255AC1-221 E
Adder
2.0517647058823531.744
316023AB2-100 C2
50/50
0.8890.889
960082AF2-299 E
50/50
1.0391.039
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
3151051BRUNSWICKS1
50/50
12.19612.196
963042AG1-153 E
50/50
5.9665.966
927021AC1-189 C
Adder
4.5788235294117653.892
964241AG1-285 C
Adder
7.502352941176476.377
924152AB2-059 E OP
Adder
3.18705882352941172.709
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
936172AD2-023 E
Adder
1.21058823529411751.029
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
924516AB2-100 E1
50/50
2.6782.678
918512AA1-065 E OP
Adder
2.60941176470588232.218
966621AG1-532 C
50/50
1.1691.169
918532AA1-067 E
Adder
0.367058823529411770.312
924022AB2-043 E O1
Adder
3.07764705882352942.616
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
926024AC1-080 E
Adder
0.454117647058823570.386
936161AD2-022 C
Adder
3.8235294117647063.25
316087AB2-174 C
50/50
0.9180.918
962572AG1-106 E
50/50
0.8940.894
926214AC1-099 E
Adder
0.70941176470588230.603
932632AC2-084 E
Adder
1.89764705882352951.613
964242AG1-285 E
Adder
5.0011764705882364.251
924162AB2-060 E OP
Adder
2.522.142
964792AG1-342 E
Adder
1.34588235294117631.144
940492AE2-034 E
Adder
1.07647058823529430.915
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
918492AA1-063AE OP
Adder
2.40470588235294122.044
962571AG1-106 C
50/50
2.0442.044
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
316274AC1-208 C
Adder
5.5235294117647074.695
917342Z2-044 E
Adder
0.36117647058823530.307
937482AD2-202 E
Adder
0.64705882352941180.55
3151311EDGECMA
Adder
9.4070588235294137.996
961792AG1-021 E
Adder
0.71411764705882350.607
939411AE1-173 C
Adder
49.7729411764705942.307
3137643SOCKMAN
50/50
0.5020.502
3151031BRUNSWICKG2
50/50
5.8715.871
919710AA2-057 E
Adder
2.3988235294117652.039
932763AC2-100 E
Adder
1.3917647058823531.183
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
920042AA2-088 E OP
Adder
4.9317647058823534.192
934521AD1-076 C
Adder
4.7823529411764714.065
934511AD1-075 C
Adder
3.2917647058823532.798
3145723EMPORIA
50/50
0.3510.351
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
919692AA2-053 E OP
Adder
2.6788235294117652.277
925785AC1-054 E
Adder
2.1505882352941181.828
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
942001AE2-212 C
Adder
-3.7917647058823527-3.223
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
3151371ROSEMS1
50/50
0.9320.932
957482AF2-042 E
50/50
22.67222.672
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
946301AF1-294 C
Adder
1.7247058823529411.466
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
936162AD2-022 E
Adder
2.29411764705882341.95
920692AA2-178 E
Adder
1.43529411764705881.22
966622AG1-532 E
50/50
0.7790.779
922923AB1-081 E OP
Adder
2.24941176470588241.912
3147133PAMPLIN
Adder
0.454117647058823570.386
927264AC1-222 E
Adder
2.16588235294117661.841
926274AC1-105 E
Adder
1.50823529411764711.282
3143316POE
Adder
0.51176470588235290.435
316365AB2-100 C1
50/50
0.8890.889
926206AC1-098 E
Adder
2.14705882352941171.825
3151041BRUNSWICKG3
50/50
5.8715.871
3151021BRUNSWICKG1
50/50
5.8715.871
942462AE2-259 E
Adder
2.62.21
964791AG1-342 C
Adder
2.0188235294117651.716
925997AC1-075 E
Adder
1.36941176470588231.164
316315AB2-025 C
50/50
0.4720.472
946282AF1-292 E
50/50
0.860.86
944012AF1-069 E
50/50
3.683.68
957861AF2-080 C
Adder
4.1588235294117653.535
917512Z2-088 E OP1
Adder
2.742.329
3138533PONTONDP
Adder
0.310588235294117660.264
3145413WATKINS
Adder
0.265882352941176460.226
960081AF2-299 C
50/50
1.5581.558
926072AC1-086 E
50/50
7.1937.193
944011AF1-069 C
50/50
9.4749.474
963041AG1-153 C
50/50
3.9773.977
957862AF2-080 E
Adder
1.84352941176470591.567
936261AD2-033 C
Adder
7.0082352941176475.957
961791AG1-021 C
Adder
0.83882352941176460.713
962562AG1-105 E
Adder
3.39764705882352922.888
936171AD2-023 C
Adder
2.23058823529411751.896
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.22 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:680.18
MW Contribution:8.64
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.36 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:701.52
MW Contribution:10.63
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
933981AD1-022 C
80/20
5.6875.687
3151261ROARAP2
80/20
2.1232.123
3147043LAWRENC
80/20
0.5790.579
3151621KERR 5
80/20
0.8620.862
316049AB1-081 C OP
80/20
1.4941.494
3151611KERR 4
80/20
0.8620.862
966621AG1-532 C
80/20
3.2993.299
3151151S HAMPT1
80/20
0.9570.957
962571AG1-106 C
80/20
5.4965.496
932631AC2-084 C
80/20
1.171.17
316274AC1-208 C
80/20
11.22611.226
3151311EDGECMA
80/20
16.55516.555
3151601KERR 3
80/20
0.8620.862
3151581KERR 1
80/20
0.3080.308
3152661PLYWOOD A
80/20
0.6390.639
3152921DOMTR78
80/20
0.8540.854
316140AB2-099 C
80/20
0.0920.092
3137643SOCKMAN
80/20
1.2371.237
316212AC1-099 C
80/20
0.3680.368
316319Z2-044 C
80/20
0.2310.231
3151641KERR 7
80/20
0.8620.862
316087AB2-174 C
80/20
2.4642.464
313527AB2-043 C
80/20
0.3630.363
3151591KERR 2
80/20
0.8620.862
934521AD1-076 C
80/20
7.0327.032
934511AD1-075 C
80/20
4.844.84
316011AB1-132 C OP
80/20
4.7154.715
316263AC1-034 C
80/20
6.9816.981
959311AF2-222 C
80/20
8.6368.636
3151411GASTONB
80/20
6.1766.176
316181AB2-040 GEN
80/20
2.5112.511
316174AB2-169_C
80/20
0.7190.719
3156063AA2-053SOLA
80/20
2.1582.158
3151281ROARAP4
80/20
2.0092.009
3156011CONETOE2SOL
80/20
1.1751.175
316238AB2-078 C O1
80/20
0.2290.229
316237AB2-079 C O1
80/20
0.2290.229
934501AD1-074 C
80/20
19.36119.361
3156021HOLLOMANSOL
80/20
1.5861.586
3156073AA1-063SOLA
80/20
1.8141.814
3151371ROSEMS1
80/20
2.4382.438
961671AG1-007 C
80/20
0.9120.912
934621AD1-088 C
80/20
4.4044.404
316359AB2-059 C OP
80/20
1.7611.761
946301AF1-294 C
80/20
1.8661.866
316365AB2-100 C1
80/20
2.7732.773
316318V4-068 C
80/20
0.0750.075
316210AC1-098 C
80/20
1.0991.099
316327AA2-057 C
80/20
1.4891.489
316239AB2-077 C O1
80/20
0.2290.229
964791AG1-342 C
80/20
2.0352.035
3156083AA2-088SOLA
80/20
0.9350.935
313506AB1-173 C OP
80/20
2.2292.229
3151361ROSEMG1
80/20
3.9363.936
316005AA1-067 C
80/20
0.2210.221
957481AF2-042 C
80/20
24.31224.312
316023AB2-100 C2
80/20
2.7732.773
946281AF1-292 C
80/20
3.6413.641
926071AC1-086 C
80/20
42.49342.493
316317KELFORD C
80/20
0.370.37
927021AC1-189 C
80/20
7.5497.549
3151531CLOVER1
80/20
5.8195.819
964241AG1-285 C
80/20
7.2257.225
316034AC1-036 C
80/20
0.1240.124
962561AG1-105 C
80/20
5.2875.287
316129AC1-054 C
80/20
1.341.34
957861AF2-080 C
80/20
6.8566.856
316131AB2-060 C
80/20
1.0341.034
3138533PONTONDP
80/20
0.3360.336
316118AC1-105 C
80/20
0.4840.484
960081AF2-299 C
80/20
4.3984.398
3151631KERR 6
80/20
0.8620.862
936261AD2-033 C
80/20
8.0298.029
961791AG1-021 C
80/20
0.9080.908
3144293JTRSVLE
80/20
0.2090.209
943171AE2-346 C
80/20
0.2140.214
961941AG1-037 C
80/20
0.4820.482
3151391GASTONA
80/20
6.1766.176
3151381ROSEMG2
80/20
1.8431.843
934331AD1-057 C
80/20
5.1335.133
934321AD1-056 C
80/20
9.2019.201
958211AF2-115 C
80/20
1.1351.135
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.20711.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.5767.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.3611.361
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
SIGELTFEXP_SIGE->PJM
CLTF
0.0840.084
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1882.188
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.15434.154
CPLELTFEXP_CPLE->PJM
CLTF
4.5894.589
TVALTFEXP_TVA->PJM
CLTF
2.0182.018
NYPJM->LTFIMP_NY
CLTF
0.3660.366
LGEELTFEXP_LGEE->PJM
CLTF
0.4310.431
WECLTFEXP_WEC->PJM
CLTF
0.2290.229

Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.22 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:801.79
MW Contribution:64.99
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.59 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:831.68
MW Contribution:61.74
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966621AG1-532 C
Adder
0.70470588235294120.599
924022AB2-043 E O1
Adder
9.1247058823529417.756
3147223TWITTYS
50/50
2.1732.173
959312AF2-222 E
50/50
26.07226.072
926024AC1-080 E
Adder
1.10.935
925612AC1-036 E
50/50
1.961.96
924312AB2-078 E O1
Adder
2.3164705882352941.969
926274AC1-105 E
Adder
4.0141176470588233.412
938821AE1-108 C
Adder
-10.602352941176472-9.012
957481AF2-042 C
50/50
98.12598.125
924322AB2-079 E O1
Adder
2.3164705882352941.969
946302AF1-294 E
50/50
8.1428.142
943902AF1-058 E
Adder
1.841.564
924302AB2-077 E O1
Adder
2.3164705882352941.969
942752AE2-291 E
Adder
5.4352941176470594.62
936262AD2-033 E
50/50
18.44918.449
958211AF2-115 C
50/50
5.8475.847
316336AC2-165 C
Adder
-5.9023529411764715-5.017
934622AD1-088 E
50/50
9.1039.103
934612AD1-087 E
Adder
6.3847058823529415.427
927255AC1-221 E
Adder
4.1470588235294123.525
960082AF2-299 E
Adder
0.62705882352941180.533
946281AF1-292 C
Adder
0.77764705882352950.661
3151531CLOVER1
50/50
22.50522.505
964241AG1-285 C
50/50
25.15925.159
316034AC1-036 C
50/50
0.5350.535
958212AF2-115 E
50/50
4.9814.981
962561AG1-105 C
Adder
14.18352941176470612.056
937482AD2-202 E
Adder
1.86823529411764721.588
961792AG1-021 E
50/50
3.9843.984
941011AE2-092 C
Adder
-9.724705882352941-8.266
957482AF2-042 E
50/50
65.41765.417
934621AD1-088 C
50/50
18.90718.907
946301AF1-294 C
50/50
9.6159.615
942461AE2-259 C
50/50
31.14431.144
935172AD1-152 E
Adder
8.8823529411764717.55
964242AG1-285 E
50/50
16.77316.773
924162AB2-060 E OP
Adder
7.6694117647058836.519
964792AG1-342 E
Adder
3.6964705882352943.142
932763AC2-100 E
Adder
2.7305882352941182.321
966622AG1-532 E
Adder
0.47058823529411770.4
3147133PAMPLIN
50/50
2.7572.757
927264AC1-222 E
Adder
5.5211764705882354.693
3145723EMPORIA
Adder
0.21647058823529410.184
925785AC1-054 E
Adder
3.35647058823529452.853
959311AF2-222 C
50/50
38.91438.914
942751AE2-291 C
Adder
8.1517647058823536.929
942462AE2-259 E
50/50
20.76320.763
964791AG1-342 C
Adder
5.5447058823529414.713
925997AC1-075 E
Adder
3.3141176470588242.817
946282AF1-292 E
Adder
0.51882352941176470.441
3138533PONTONDP
50/50
1.7321.732
960081AF2-299 C
Adder
0.94000000000000010.799
936261AD2-033 C
50/50
27.67327.673
961791AG1-021 C
50/50
4.6774.677
3144293JTRSVLE
50/50
1.0761.076
962562AG1-105 E
Adder
9.4564705882352958.038
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.4439.443
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.3277.327
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.2351.235
LAGNLTFEXP_LAGN->PJM
CLTF
2.5882.588
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7990.799
SIGELTFEXP_SIGE->PJM
CLTF
0.0750.075
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1672.167
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.10836.108
CPLELTFEXP_CPLE->PJM
CLTF
4.5484.548
TVALTFEXP_TVA->PJM
CLTF
2.0222.022
O66PJM->LTFIMP_O-066
CMTX_NF
5.0935.093
NYPJM->LTFIMP_NY
CLTF
0.3810.381
LGEELTFEXP_LGEE->PJM
CLTF
0.370.37
WECLTFEXP_WEC->PJM
CLTF
0.1960.196

Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.05 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:637.86
MW Contribution:38.89
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.13 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:677.49
MW Contribution:36.95
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151261ROARAP2
80/20
0.6820.682
3147043LAWRENC
80/20
0.2660.266
3151621KERR 5
80/20
1.5621.562
316222AC1-221 C
80/20
1.581.58
316336AC2-165 C
Adder
-5.881176470588235-4.999
934611AD1-087 C
80/20
2.212.21
316049AB1-081 C OP
80/20
0.4780.478
3151611KERR 4
80/20
1.5621.562
962571AG1-106 C
80/20
0.8220.822
932631AC2-084 C
80/20
0.3610.361
316274AC1-208 C
80/20
3.5443.544
3151311EDGECMA
80/20
5.0435.043
3151601KERR 3
80/20
1.5621.562
3151581KERR 1
80/20
0.5580.558
3152661PLYWOOD A
80/20
1.751.75
941011AE2-092 C
Adder
-9.709411764705882-8.253
966621AG1-532 C
80/20
0.7060.706
316003AC1-222 C
80/20
1.3491.349
936161AD2-022 C
80/20
3.6223.622
3137643SOCKMAN
80/20
0.3530.353
316212AC1-099 C
80/20
0.1140.114
316319Z2-044 C
80/20
0.0740.074
937481AD2-202 C
80/20
0.6410.641
3151641KERR 7
80/20
1.5621.562
316123AC1-075 C
80/20
0.9540.954
316205AC1-080 C
80/20
0.3190.319
316087AB2-174 C
80/20
0.5890.589
313527AB2-043 C
80/20
0.9080.908
3151591KERR 2
80/20
1.5621.562
316283AC2-100 C
80/20
1.2351.235
316011AB1-132 C OP
80/20
0.7060.706
316263AC1-034 C
80/20
2.2322.232
959311AF2-222 C
80/20
38.88938.889
942751AE2-291 C
80/20
8.1328.132
3151561HALLBR1
80/20
0.5580.558
3151411GASTONB
80/20
0.9240.924
316181AB2-040 GEN
80/20
0.6330.633
3156063AA2-053SOLA
80/20
0.680.68
3151281ROARAP4
80/20
0.6450.645
316238AB2-078 C O1
80/20
0.5670.567
316237AB2-079 C O1
80/20
0.5670.567
938821AE1-108 C
Adder
-10.591764705882353-9.003
3156073AA1-063SOLA
80/20
0.5850.585
3151371ROSEMS1
80/20
0.3850.385
934621AD1-088 C
80/20
18.88918.889
316359AB2-059 C OP
80/20
0.5630.563
946301AF1-294 C
80/20
9.619.61
942461AE2-259 C
80/20
31.13731.137
316197AC1-042 C
80/20
0.1420.142
316210AC1-098 C
80/20
0.3390.339
316327AA2-057 C
80/20
0.4730.473
316239AB2-077 C O1
80/20
0.5670.567
935171AD1-152 C
80/20
2.1562.156
964791AG1-342 C
80/20
5.5375.537
313506AB1-173 C OP
80/20
0.5620.562
3151361ROSEMG1
80/20
0.6210.621
957481AF2-042 C
80/20
98.01698.016
946281AF1-292 C
80/20
0.7790.779
926071AC1-086 C
80/20
6.3586.358
3151531CLOVER1
80/20
22.47722.477
964241AG1-285 C
80/20
25.13725.137
316034AC1-036 C
80/20
0.5340.534
962561AG1-105 C
80/20
14.16414.164
942671AE2-283 C
80/20
1.5231.523
316129AC1-054 C
80/20
1.1891.189
316131AB2-060 C
80/20
2.6612.661
3138533PONTONDP
80/20
1.7321.732
316118AC1-105 C
80/20
1.3691.369
316217AC1-145 C
80/20
0.1690.169
960081AF2-299 C
80/20
0.9420.942
3151541CLOVER2
80/20
22.26722.267
3151631KERR 6
80/20
1.5621.562
936261AD2-033 C
80/20
27.65427.654
961791AG1-021 C
80/20
4.6754.675
3144293JTRSVLE
80/20
1.0761.076
316248AF1-058 C
80/20
0.450.45
936171AD2-023 C
80/20
2.1132.113
941801AE2-185 C
80/20
1.9581.958
3151391GASTONA
80/20
0.9240.924
3151381ROSEMG2
80/20
0.2910.291
934331AD1-057 C
80/20
1.1051.105
934321AD1-056 C
80/20
1.981.98
958211AF2-115 C
80/20
5.8445.844
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.1489.148
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.1237.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1991.199
LAGNLTFEXP_LAGN->PJM
CLTF
2.5182.518
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1192.119
CBM South 2LTFEXP_CBM-S2->PJM
CBM
35.23335.233
CPLELTFEXP_CPLE->PJM
CLTF
4.4464.446
TVALTFEXP_TVA->PJM
CLTF
1.9681.968
NYPJM->LTFIMP_NY
CLTF
0.3720.372
LGEELTFEXP_LGEE->PJM
CLTF
0.3590.359
WECLTFEXP_WEC->PJM
CLTF
0.190.19

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.21 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:761.57
MW Contribution:8.63
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.21 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:781.94
MW Contribution:10.63
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
933981AD1-022 C
80/20
5.6845.684
3151261ROARAP2
80/20
2.1232.123
3147043LAWRENC
80/20
0.5790.579
3151621KERR 5
80/20
0.8610.861
316049AB1-081 C OP
80/20
1.4931.493
3151611KERR 4
80/20
0.8610.861
966621AG1-532 C
80/20
3.2983.298
3151151S HAMPT1
80/20
0.9560.956
962571AG1-106 C
80/20
5.4955.495
932631AC2-084 C
80/20
1.171.17
316274AC1-208 C
80/20
11.22211.222
3151311EDGECMA
80/20
16.54816.548
3151601KERR 3
80/20
0.8610.861
3151581KERR 1
80/20
0.3070.307
3152661PLYWOOD A
80/20
0.6380.638
3152921DOMTR78
80/20
0.8530.853
316140AB2-099 C
80/20
0.0920.092
3137643SOCKMAN
80/20
1.2371.237
316212AC1-099 C
80/20
0.3680.368
316319Z2-044 C
80/20
0.2310.231
3151641KERR 7
80/20
0.8610.861
316087AB2-174 C
80/20
2.4642.464
313527AB2-043 C
80/20
0.3630.363
3151591KERR 2
80/20
0.8610.861
934521AD1-076 C
80/20
7.0267.026
934511AD1-075 C
80/20
4.8374.837
316011AB1-132 C OP
80/20
4.7154.715
316263AC1-034 C
80/20
6.9786.978
959311AF2-222 C
80/20
8.6298.629
940541AE2-040 C
80/20
11.68811.688
940481AE2-033 C
80/20
63.40163.401
3151411GASTONB
80/20
6.1746.174
316181AB2-040 GEN
80/20
2.512.51
316174AB2-169_C
80/20
0.7190.719
3156063AA2-053SOLA
80/20
2.1572.157
3151281ROARAP4
80/20
2.0092.009
3156011CONETOE2SOL
80/20
1.1751.175
316238AB2-078 C O1
80/20
0.2290.229
316237AB2-079 C O1
80/20
0.2290.229
934501AD1-074 C
80/20
19.34719.347
3156021HOLLOMANSOL
80/20
1.5851.585
3156073AA1-063SOLA
80/20
1.8141.814
3151371ROSEMS1
80/20
2.4382.438
961671AG1-007 C
80/20
0.9120.912
934621AD1-088 C
80/20
4.4014.401
316359AB2-059 C OP
80/20
1.761.76
946301AF1-294 C
80/20
1.8641.864
316365AB2-100 C1
80/20
2.7732.773
316318V4-068 C
80/20
0.0750.075
316210AC1-098 C
80/20
1.0991.099
316327AA2-057 C
80/20
1.4881.488
316239AB2-077 C O1
80/20
0.2290.229
964791AG1-342 C
80/20
2.0342.034
3156083AA2-088SOLA
80/20
0.9350.935
313506AB1-173 C OP
80/20
2.2292.229
3151361ROSEMG1
80/20
3.9353.935
316005AA1-067 C
80/20
0.2210.221
957481AF2-042 C
80/20
24.2924.29
316023AB2-100 C2
80/20
2.7732.773
946281AF1-292 C
80/20
3.643.64
926071AC1-086 C
80/20
42.48542.485
316317KELFORD C
80/20
0.3690.369
927021AC1-189 C
80/20
7.5457.545
3151531CLOVER1
80/20
5.8145.814
964241AG1-285 C
80/20
7.2197.219
316034AC1-036 C
80/20
0.1230.123
962561AG1-105 C
80/20
5.2835.283
316315AB2-025 C
80/20
1.661.66
316129AC1-054 C
80/20
1.341.34
957861AF2-080 C
80/20
6.8536.853
316131AB2-060 C
80/20
1.0331.033
3138533PONTONDP
80/20
0.3360.336
316118AC1-105 C
80/20
0.4840.484
960081AF2-299 C
80/20
4.3984.398
3151631KERR 6
80/20
0.8610.861
936261AD2-033 C
80/20
8.0238.023
961791AG1-021 C
80/20
0.9070.907
3144293JTRSVLE
80/20
0.2090.209
943171AE2-346 C
80/20
0.2140.214
961941AG1-037 C
80/20
0.4820.482
3151391GASTONA
80/20
6.1746.174
3151381ROSEMG2
80/20
1.8431.843
934331AD1-057 C
80/20
5.1315.131
934321AD1-056 C
80/20
9.1989.198
958211AF2-115 C
80/20
1.1341.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.08611.086
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.537.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.351.35
LAGNLTFEXP_LAGN->PJM
CLTF
2.5652.565
SIGELTFEXP_SIGE->PJM
CLTF
0.0830.083
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1852.185
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.08134.081
CPLELTFEXP_CPLE->PJM
CLTF
4.5834.583
TVALTFEXP_TVA->PJM
CLTF
2.0082.008
NYPJM->LTFIMP_NY
CLTF
0.370.37
LGEELTFEXP_LGEE->PJM
CLTF
0.4270.427
WECLTFEXP_WEC->PJM
CLTF
0.2270.227

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.54 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1199.86
MW Contribution:12.15
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.15 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1216.94
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944581AF1-123 C
Adder
17.0976470588235314.533
957481AF2-042 C
50/50
35.70935.709
924322AB2-079 E O1
Adder
0.45058823529411770.383
946302AF1-294 E
Adder
1.02352941176470580.87
943902AF1-058 E
Adder
0.58823529411764710.5
3152441Z1-086 ST
50/50
15.62315.623
3152431Z1-086 GT3
50/50
8.9718.971
3152421Z1-086 GT2
50/50
8.9718.971
925612AC1-036 E
Adder
0.381176470588235340.324
924312AB2-078 E O1
Adder
0.45058823529411770.383
926274AC1-105 E
Adder
1.15529411764705880.982
932046AC2-012 E
Adder
4.4317647058823533.767
938531AE1-072 C
Adder
5.95529411764705955.062
3152411Z1-086 GT1
50/50
8.9758.975
924302AB2-077 E O1
Adder
0.45058823529411770.383
926662AC1-147 E
Adder
0.448235294117647070.381
916192Z1-068 E
Adder
0.6682352941176470.568
939412AE1-173 E
50/50
44.67444.674
941032AE2-094 E
50/50
15.74915.749
941031AE2-094 C
50/50
35.16335.163
934331AD1-057 C
Adder
-1.1952941176470588-1.016
934321AD1-056 C
Adder
-2.142352941176471-1.821
936262AD2-033 E
Adder
2.89058823529411772.457
958211AF2-115 C
Adder
0.73529411764705890.625
940641AE2-051 C
50/50
14.85114.851
934622AD1-088 E
50/50
2.6942.694
934611AD1-087 C
50/50
0.7660.766
934612AD1-087 E
50/50
2.212.21
927255AC1-221 E
Adder
1.70117647058823531.446
944582AF1-123 E
Adder
39.15058823529411633.278
944592AF1-124 E
Adder
39.2929411764705933.399
923832AB2-022 E
Adder
0.374117647058823550.318
946281AF1-292 C
Adder
-1.2576470588235293-1.069
3151051BRUNSWICKS1
50/50
14.35614.356
963042AG1-153 E
50/50
7.0227.022
3151531CLOVER1
50/50
7.797.79
964241AG1-285 C
Adder
5.9952941176470595.096
958212AF2-115 E
Adder
0.62588235294117660.532
962561AG1-105 C
Adder
3.50352941176470622.978
919153AA1-139 E2
Adder
1.42117647058823531.208
940642AE2-051 E
50/50
9.9019.901
966621AG1-532 C
Adder
-1.14-0.969
924022AB2-043 E O1
Adder
1.75058823529411781.488
3147223TWITTYS
Adder
0.42235294117647060.359
959312AF2-222 E
Adder
4.8764705882352944.145
925522AC1-027 E
Adder
0.430588235294117660.366
933291AC2-141 C
Adder
14.88235294117647112.65
926755AC1-161 E
Adder
6.3529411764705895.4
957872AF2-081 E
Adder
1.48941176470588241.266
964242AG1-285 E
Adder
3.99647058823529383.397
924162AB2-060 E OP
Adder
1.4435294117647061.227
964792AG1-342 E
Adder
0.95647058823529410.813
932763AC2-100 E
Adder
1.14235294117647060.971
933292AC2-141 E
Adder
6.3529411764705895.4
944602AF1-125 E
Adder
38.536470588235332.756
3145506HICKORY
Adder
0.80470588235294130.684
957871AF2-081 C
Adder
3.47411764705882352.953
937482AD2-202 E
50/50
0.6470.647
961792AG1-021 E
Adder
0.50117647058823530.426
913392Y1-086 E
Adder
0.66235294117647060.563
939411AE1-173 C
50/50
67.01167.011
3137643SOCKMAN
Adder
-0.34352941176470586-0.292
3151031BRUNSWICKG2
50/50
6.916.91
937481AD2-202 C
50/50
0.2220.222
944641AF1-129 C
Adder
-99.89764705882352-84.913
316240AF1-291 C
Adder
-2.2705882352941176-1.93
919152AA1-139 E1
Adder
1.42117647058823531.208
3145723EMPORIA
Adder
-0.3270588235294118-0.278
959311AF2-222 C
Adder
7.2776470588235296.186
942001AE2-212 C
Adder
-2.8705882352941177-2.44
934065AD1-033 E
Adder
1.87294117647058831.592
937226AE2-253 E
Adder
2.081.768
957482AF2-042 E
50/50
23.80623.806
934621AD1-088 C
50/50
5.5965.596
946301AF1-294 C
Adder
1.2082352941176471.027
942461AE2-259 C
Adder
3.32588235294117632.827
935172AD1-152 E
Adder
3.1047058823529412.639
938532AE1-072 E
Adder
3.1047058823529412.639
3146326AYDLETT TAP
Adder
0.455294117647058850.387
3147133PAMPLIN
Adder
0.377647058823529450.321
927264AC1-222 E
Adder
1.781.513
3151041BRUNSWICKG3
50/50
6.916.91
3151021BRUNSWICKG1
50/50
6.916.91
942462AE2-259 E
Adder
2.21764705882352951.885
964791AG1-342 C
Adder
1.43529411764705881.22
944012AF1-069 E
50/50
4.4634.463
3138533PONTONDP
Adder
0.217647058823529420.185
941591AE2-156 C
Adder
6.1035294117647065.188
944591AF1-124 C
Adder
17.15764705882352814.584
944601AF1-125 C
Adder
16.8341176470588214.309
944011AF1-069 C
50/50
11.48911.489
963041AG1-153 C
50/50
4.6824.682
3151541CLOVER2
50/50
7.7177.717
936261AD2-033 C
Adder
4.3352941176470593.685
961791AG1-021 C
Adder
0.58823529411764710.5
962562AG1-105 E
Adder
2.3352941176470591.985
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.10812.108
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4868.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4991.499
LAGNLTFEXP_LAGN->PJM
CLTF
2.9182.918
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9710.971
SIGELTFEXP_SIGE->PJM
CLTF
0.0920.092
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9681.968
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.24536.245
CPLELTFEXP_CPLE->PJM
CLTF
4.1284.128
TVALTFEXP_TVA->PJM
CLTF
2.2832.283
O66PJM->LTFIMP_O-066
CMTX_NF
6.1826.182
NYPJM->LTFIMP_NY
CLTF
0.4470.447
LGEELTFEXP_LGEE->PJM
CLTF
0.4670.467
WECLTFEXP_WEC->PJM
CLTF
0.2490.249

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.16 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4182.74
MW Contribution:36.24
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.7 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4637.48
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961611AG1-000B C
Adder
19.52941176470588416.6
316375AC2-012 C
50/50
2.0662.066
313526AB2-022 C
50/50
0.5790.579
940541AE2-040 C
Adder
4.263.621
940481AE2-033 C
Adder
23.97176470588235420.376
940482AE2-033 E
Adder
16.1613.736
923263AB1-132 E OP
Adder
8.8564705882352937.528
3152441Z1-086 ST
50/50
32.38732.387
3152431Z1-086 GT3
50/50
18.59718.597
3152421Z1-086 GT2
50/50
18.59718.597
925612AC1-036 E
Adder
1.13647058823529410.966
924312AB2-078 E O1
Adder
1.84705882352941191.57
926274AC1-105 E
Adder
3.63.06
3150981CHESPKA
50/50
0.6670.667
316185AD1-033 C
50/50
1.9111.911
944581AF1-123 C
50/50
70.6170.61
941101AE2-104 C
Adder
5.00705882352941254.256
316320Y1-086 C
50/50
0.3390.339
316141AB2-099 E
Adder
0.370588235294117660.315
316088AB2-174 E
Adder
9.4435294117647068.027
923994AB2-040_E
Adder
8.9094117647058837.573
957481AF2-042 C
50/50
83.22783.227
961672AG1-007 E
Adder
0.75529411764705890.642
924322AB2-079 E O1
Adder
1.84705882352941191.57
932046AC2-012 E
50/50
20.04320.043
958161AF2-110 C
Adder
2.04352941176470631.737
316017AA1-139 ULT1
50/50
1.6761.676
938531AE1-072 C
50/50
27.18327.183
3145393UNCAMP
Adder
9.0117647058823537.66
933981AD1-022 C
Adder
13.02235294117647211.069
900672V4-068 E
Adder
0.52352941176470590.445
3152411Z1-086 GT1
50/50
18.60518.605
924302AB2-077 E O1
Adder
1.84705882352941191.57
926662AC1-147 E
50/50
2.0262.026
916192Z1-068 E
50/50
2.92.9
957492AF2-043 E
Adder
2.16705882352941171.842
923852AB2-025 E
50/50
1.7231.723
939412AE1-173 E
50/50
105.86105.86
961942AG1-037 E
Adder
0.494117647058823550.42
961941AG1-037 C
Adder
0.74117647058823530.63
941032AE2-094 E
50/50
32.01732.017
941031AE2-094 C
50/50
71.48571.485
934332AD1-057 E
Adder
2.5917647058823532.203
934331AD1-057 C
Adder
4.9764705882352954.23
934321AD1-056 C
Adder
8.927.582
934322AD1-056 E
Adder
4.8388235294117664.113
927022AC1-189 E
Adder
5.9882352941176475.09
925595AC1-034 E
Adder
7.0494117647058835.992
316084AB2-161 E
Adder
7.2141176470588236.132
3145946PLYMOUTH TP
Adder
0.48235294117647060.41
933982AD1-022 E
Adder
7.0894117647058836.026
940641AE2-051 C
50/50
31.3831.38
927146AC1-208 E
Adder
5.74470588235294164.883
934622AD1-088 E
Adder
6.6576470588235295.659
934612AD1-087 E
Adder
5.3905882352941184.582
316349AD2-085 C
Adder
4.8858823529411764.153
935112AD1-144 E
Adder
1.38117647058823521.174
3151091ELIZAR2
50/50
4.8274.827
944582AF1-123 E
50/50
161.69161.69
944592AF1-124 E
50/50
162.275162.275
923832AB2-022 E
50/50
1.9081.908
938772AE1-103 E
Adder
6.0023529411764715.102
916042Z1-036 E
Adder
43.3141176470588236.817
960082AF2-299 E
Adder
1.80588235294117651.535
946281AF1-292 C
Adder
2.24235294117647041.906
926071AC1-086 C
Adder
30.4329411764705925.868
3151051BRUNSWICKS1
50/50
30.03530.035
963042AG1-153 E
50/50
14.69214.692
927021AC1-189 C
Adder
12.02000000000000110.217
964241AG1-285 C
Adder
17.9658823529411815.271
924152AB2-059 E OP
Adder
7.4317647058823546.317
962561AG1-105 C
Adder
12.04705882352941210.24
934576AD1-082 E
Adder
5.7482352941176484.886
916191Z1-068 C
50/50
0.0680.068
933292AC2-141 E
50/50
20.76320.763
316294AC1-161 C
50/50
7.9487.948
944602AF1-125 E
50/50
159.152159.152
3145506HICKORY
50/50
3.3883.388
943612AF1-032 E
Adder
1.40823529411764731.197
957871AF2-081 C
50/50
15.47915.479
940492AE2-034 E
Adder
4.6305882352941183.936
934522AD1-076 E
Adder
9.3011764705882357.906
943172AE2-346 E
Adder
0.88941176470588230.756
918492AA1-063AE OP
Adder
5.9423529411764715.051
962571AG1-106 C
Adder
3.9364705882352943.346
917332KELFORD E
Adder
2.39764705882352922.038
925122AB2-169 E
Adder
8.4305882352941197.166
316274AC1-208 C
Adder
12.93882352941176410.998
917342Z2-044 E
Adder
0.84705882352941180.72
937482AD2-202 E
Adder
1.57764705882352941.341
3151311EDGECMA
Adder
21.84705882352941218.57
942341AE2-247 C
Adder
2.11764705882352941.8
943462AF1-017 E
Adder
3.12588235294117662.657
958162AF2-110 E
Adder
3.24941176470588242.762
316388AE2-253 GEN
50/50
3.0473.047
919153AA1-139 E2
50/50
6.336.33
934512AD1-075 E
Adder
6.3941176470588235.435
934502AD1-074 E
Adder
25.5776470588235321.741
924516AB2-100 E1
Adder
4.23058823529411753.596
918512AA1-065 E OP
Adder
8.1470588235294116.925
940642AE2-051 E
50/50
20.9220.92
966621AG1-532 C
Adder
2.0317647058823531.727
918532AA1-067 E
Adder
1.02823529411764710.874
924022AB2-043 E O1
Adder
7.1670588235294126.092
3147223TWITTYS
Adder
1.2588235294117651.07
959312AF2-222 E
Adder
2.9682352941176472.523
939192AE1-149 E
Adder
8.7694117647058827.454
939312AE1-162 E
Adder
1.95882352941176491.665
3150921YORKTN3
Adder
152.65647058823532129.758
3145256KINGFORK
Adder
1.48823529411764691.265
925522AC1-027 E
50/50
1.8771.877
933291AC2-141 C
50/50
48.6448.64
926755AC1-161 E
50/50
20.76320.763
941102AE2-104 E
Adder
7.966.766
957872AF2-081 E
50/50
6.6346.634
962572AG1-106 E
Adder
1.72235294117647061.464
926214AC1-099 E
Adder
1.73647058823529421.476
932632AC2-084 E
Adder
4.6458823529411763.949
964242AG1-285 E
Adder
11.97764705882352810.181
924162AB2-060 E OP
Adder
5.8752941176470594.994
964792AG1-342 E
Adder
3.1905882352941182.712
943461AF1-017 C
Adder
1.91529411764705881.628
932596AC2-079 E
Adder
13.36941176470588411.364
316311AC2-079 C
Adder
8.1941176470588236.965
938532AE1-072 E
50/50
14.1714.17
3146326AYDLETT TAP
50/50
2.0962.096
917122Z2-027 E
Adder
2.061.751
920692AA2-178 E
Adder
6.1741176470588245.248
966622AG1-532 E
Adder
1.35411764705882361.151
922923AB1-081 E OP
Adder
5.2458823529411764.459
913392Y1-086 E
50/50
3.383.38
939411AE1-173 C
50/50
158.79158.79
3137643SOCKMAN
Adder
1.03058823529411760.876
3151031BRUNSWICKG2
50/50
14.45714.457
919710AA2-057 E
Adder
5.6458823529411774.799
942342AE2-247 E
Adder
2.92470588235294172.486
316036AC1-147 C
50/50
0.5640.564
919152AA1-139 E1
50/50
6.336.33
316018AA1-139 ULT2
50/50
1.6761.676
920042AA2-088 E OP
Adder
15.59882352941176513.259
934521AD1-076 C
Adder
18.24823529411764515.511
934511AD1-075 C
Adder
12.56117647058823510.677
3145723EMPORIA
Adder
0.62470588235294120.531
923573AB1-173 E OP
Adder
4.7517647058823534.039
919692AA2-053 E OP
Adder
6.1282352941176475.209
925785AC1-054 E
Adder
4.8741176470588234.143
316263AC1-034 C
Adder
9.344705882352947.943
959311AF2-222 C
Adder
21.718.445
3150991CHESPKB
50/50
1.1051.105
934065AD1-033 E
50/50
7.7977.797
937226AE2-253 E
50/50
9.0629.062
934501AD1-074 C
Adder
50.2447058823529442.708
924517AB2-100 E2
Adder
4.23058823529411753.596
957482AF2-042 E
50/50
55.48555.485
961671AG1-007 C
Adder
1.33294117647058831.133
934621AD1-088 C
Adder
13.82823529411764711.754
935172AD1-152 E
Adder
7.9105882352941186.724
939191AE1-149 C
Adder
13.15411764705882411.181
3143316POE
Adder
1.71764705882352931.46
901082W1-029 E
Adder
48.63529411764706441.34
926206AC1-098 E
Adder
5.25647058823529444.468
3151041BRUNSWICKG3
50/50
14.45714.457
3151021BRUNSWICKG1
50/50
14.45714.457
964791AG1-342 C
Adder
4.7858823529411764.068
3151101ELIZAR3
50/50
4.9744.974
316315AB2-025 C
50/50
0.6050.605
946282AF1-292 E
Adder
1.49529411764705871.271
944012AF1-069 E
50/50
9.0749.074
957861AF2-080 C
Adder
10.917647058823539.28
917512Z2-088 E OP1
Adder
6.9717647058823535.926
936666AD2-085 E
Adder
7.9705882352941196.775
941591AE2-156 C
50/50
27.4127.41
3151081ELIZAR1
50/50
4.9124.912
316316AC1-027 C
50/50
0.4870.487
944591AF1-124 C
50/50
70.86170.861
944601AF1-125 C
50/50
69.52369.523
938771AE1-103 C
Adder
4.3470588235294113.695
3145413WATKINS
Adder
1.02235294117647070.869
960081AF2-299 C
Adder
2.70823529411764732.302
926072AC1-086 E
Adder
13.85058823529411711.773
944011AF1-069 C
50/50
23.35723.357
963041AG1-153 C
50/50
9.7959.795
957862AF2-080 E
Adder
4.844.114
962562AG1-105 E
Adder
8.0317647058823526.827
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.88834.888
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.38927.389
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.6044.604
LAGNLTFEXP_LAGN->PJM
CLTF
9.689.68
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6364.636
SIGELTFEXP_SIGE->PJM
CLTF
0.2790.279
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6337.633
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.923129.923
CPLELTFEXP_CPLE->PJM
CLTF
16.01716.017
TVALTFEXP_TVA->PJM
CLTF
7.5637.563
O66PJM->LTFIMP_O-066
CMTX_NF
29.52729.527
NYPJM->LTFIMP_NY
CLTF
2.172.17
LGEELTFEXP_LGEE->PJM
CLTF
1.3891.389
WECLTFEXP_WEC->PJM
CLTF
0.7290.729

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.22 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4106.12
MW Contribution:35.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
932046AC2-012 E
50/50
18.21618.216
958161AF2-110 C
Adder
1.8752941176470591.594
316017AA1-139 ULT1
50/50
1.5241.524
938531AE1-072 C
50/50
24.73924.739
3145393UNCAMP
Adder
8.3505882352941197.098
933981AD1-022 C
Adder
12.09058823529411710.277
900672V4-068 E
Adder
0.490588235294117660.417
3152411Z1-086 GT1
50/50
17.81217.812
924302AB2-077 E O1
Adder
1.77764705882352941.511
316084AB2-161 E
Adder
6.8258823529411765.802
3145946PLYMOUTH TP
Adder
0.44705882352941180.38
933982AD1-022 E
Adder
6.582352941176475.595
940641AE2-051 C
50/50
29.73129.731
927146AC1-208 E
Adder
5.44117647058823554.625
934622AD1-088 E
Adder
6.4094117647058835.448
934611AD1-087 C
50/50
1.7961.796
942341AE2-247 C
Adder
1.9647058823529411.67
943462AF1-017 E
Adder
2.90117647058823552.466
958162AF2-110 E
Adder
2.98235294117647072.535
316388AE2-253 GEN
50/50
2.7712.771
919153AA1-139 E2
50/50
5.7585.758
934512AD1-075 E
Adder
5.9258823529411765.037
934502AD1-074 E
Adder
23.70588235294117420.15
924516AB2-100 E1
Adder
4.042352941176473.436
918512AA1-065 E OP
Adder
7.6023529411764716.462
940642AE2-051 E
50/50
19.82119.821
966621AG1-532 C
Adder
1.94000000000000021.649
918532AA1-067 E
Adder
0.96823529411764710.823
924022AB2-043 E O1
Adder
6.95.865
3147223TWITTYS
Adder
1.21764705882352931.035
959312AF2-222 E
Adder
14.06705882352941311.957
934576AD1-082 E
Adder
5.4388235294117654.623
916191Z1-068 C
50/50
0.0610.061
933292AC2-141 E
50/50
18.61818.618
316294AC1-161 C
50/50
7.1277.127
944602AF1-125 E
50/50
144.526144.526
3145506HICKORY
50/50
3.0783.078
943612AF1-032 E
Adder
1.28470588235294141.092
957871AF2-081 C
50/50
14.0814.08
940492AE2-034 E
Adder
4.2752941176470593.634
934522AD1-076 E
Adder
8.6200000000000017.327
943172AE2-346 E
Adder
0.8317647058823530.707
918492AA1-063AE OP
Adder
5.6035294117647064.763
962571AG1-106 C
Adder
3.73764705882352953.177
934612AD1-087 E
50/50
5.1825.182
913392Y1-086 E
Adder
3.08235294117647072.62
939411AE1-173 C
50/50
149.153149.153
3137643SOCKMAN
Adder
0.97882352941176460.832
3151031BRUNSWICKG2
50/50
13.84313.843
919710AA2-057 E
Adder
5.3541176470588244.551
937481AD2-202 C
50/50
0.5210.521
3150921YORKTN3
Adder
46.1517647058823539.229
3145256KINGFORK
Adder
1.35529411764705881.152
925522AC1-027 E
50/50
1.7051.705
933291AC2-141 C
50/50
43.61643.616
926755AC1-161 E
50/50
18.61818.618
941102AE2-104 E
Adder
7.3058823529411766.21
957872AF2-081 E
50/50
6.0346.034
962572AG1-106 E
Adder
1.63529411764705881.39
926214AC1-099 E
Adder
1.64117647058823551.395
932632AC2-084 E
Adder
4.3905882352941183.732
964242AG1-285 E
Adder
11.549.809
924162AB2-060 E OP
Adder
5.6588235294117644.81
964792AG1-342 E
Adder
3.07411764705882362.613
942342AE2-247 E
Adder
2.71411764705882372.307
919152AA1-139 E1
50/50
5.7585.758
316018AA1-139 ULT2
50/50
1.5241.524
920042AA2-088 E OP
Adder
14.57411764705882412.388
934521AD1-076 C
Adder
16.9129411764705914.376
934511AD1-075 C
Adder
11.6423529411764739.896
3145723EMPORIA
Adder
0.59647058823529410.507
923573AB1-173 E OP
Adder
4.5223529411764713.844
919692AA2-053 E OP
Adder
5.797647058823534.928
925785AC1-054 E
Adder
4.65176470588235353.954
316263AC1-034 C
Adder
8.8847058823529417.552
959311AF2-222 C
Adder
20.9952941176470617.846
943461AF1-017 C
Adder
1.77764705882352941.511
932596AC2-079 E
Adder
12.38941176470588310.531
316311AC2-079 C
Adder
7.5929411764705886.454
938532AE1-072 E
50/50
12.89612.896
3146326AYDLETT TAP
50/50
1.9081.908
917122Z2-027 E
Adder
1.88117647058823521.599
920692AA2-178 E
Adder
5.74.845
966622AG1-532 E
Adder
1.29294117647058831.099
922923AB1-081 E OP
Adder
4.9882352941176474.24
917332KELFORD E
Adder
2.25058823529411761.913
925122AB2-169 E
Adder
7.8694117647058836.689
316274AC1-208 C
Adder
12.25411764705882510.416
917342Z2-044 E
Adder
0.80352941176470590.683
937482AD2-202 E
50/50
1.5171.517
3151311EDGECMA
Adder
20.7705882352941217.655
961611AG1-000B C
Adder
18.02352941176470615.32
316375AC2-012 C
50/50
1.8781.878
940541AE2-040 C
50/50
4.0974.097
940481AE2-033 C
50/50
23.03323.033
940482AE2-033 E
50/50
15.52815.528
923263AB1-132 E OP
Adder
8.4105882352941177.149
3152441Z1-086 ST
50/50
31.00731.007
939192AE1-149 E
Adder
8.424705882352947.161
939312AE1-162 E
Adder
1.79058823529411781.522
934065AD1-033 E
50/50
7.0817.081
937226AE2-253 E
50/50
8.2398.239
934501AD1-074 C
Adder
46.5682352941176539.583
924517AB2-100 E2
Adder
4.042352941176473.436
957482AF2-042 E
50/50
53.29753.297
961671AG1-007 C
Adder
1.26235294117647071.073
934621AD1-088 C
Adder
13.31176470588235211.315
935172AD1-152 E
Adder
7.6094117647058826.468
939191AE1-149 C
Adder
12.63647058823529410.741
3143316POE
Adder
1.67647058823529421.425
901082W1-029 E
Adder
44.4776470588235337.806
926206AC1-098 E
Adder
4.9670588235294124.222
3151041BRUNSWICKG3
50/50
13.84313.843
3151021BRUNSWICKG1
50/50
13.84313.843
964791AG1-342 C
Adder
4.6105882352941173.919
3152431Z1-086 GT3
50/50
17.80517.805
3152421Z1-086 GT2
50/50
17.80517.805
925612AC1-036 E
Adder
1.09882352941176480.934
924312AB2-078 E O1
Adder
1.77764705882352941.511
926274AC1-105 E
Adder
3.4682352941176472.948
316185AD1-033 C
50/50
1.7361.736
944581AF1-123 C
50/50
64.12164.121
941101AE2-104 C
Adder
4.5952941176470593.906
316141AB2-099 E
Adder
0.347058823529411750.295
316088AB2-174 E
Adder
8.997647058823537.648
923994AB2-040_E
Adder
8.487.208
957481AF2-042 C
50/50
79.94679.946
961672AG1-007 E
Adder
0.71529411764705890.608
924322AB2-079 E O1
Adder
1.77764705882352941.511
943902AF1-058 E
Adder
1.65647058823529411.408
316349AD2-085 C
Adder
4.5341176470588243.854
935112AD1-144 E
Adder
1.2588235294117651.07
3151091ELIZAR2
50/50
4.3864.386
944582AF1-123 E
50/50
146.831146.831
944592AF1-124 E
50/50
147.363147.363
923832AB2-022 E
Adder
1.74000000000000021.479
938772AE1-103 E
Adder
5.5529411764705884.72
916042Z1-036 E
Adder
39.78705882352941433.819
960082AF2-299 E
Adder
1.7247058823529411.466
946281AF1-292 C
Adder
2.14117647058823521.82
926071AC1-086 C
Adder
28.90117647058823624.566
3151051BRUNSWICKS1
50/50
28.75928.759
963042AG1-153 E
50/50
14.06814.068
927021AC1-189 C
Adder
11.3505882352941179.648
3151531CLOVER1
50/50
18.24618.246
964241AG1-285 C
Adder
17.3105882352941214.714
924152AB2-059 E OP
Adder
7.0658823529411776.006
962561AG1-105 C
Adder
11.6047058823529429.864
3151101ELIZAR3
50/50
4.5194.519
316315AB2-025 C
50/50
0.5820.582
946282AF1-292 E
Adder
1.4270588235294121.213
944012AF1-069 E
50/50
8.6848.684
957861AF2-080 C
Adder
10.3094117647058838.763
917512Z2-088 E OP1
Adder
6.5941176470588245.605
936666AD2-085 E
Adder
7.397647058823536.288
941591AE2-156 C
50/50
24.9124.91
3151081ELIZAR1
50/50
4.4634.463
316316AC1-027 C
50/50
0.4430.443
944591AF1-124 C
50/50
64.34964.349
944601AF1-125 C
50/50
63.13463.134
938771AE1-103 C
Adder
4.0211764705882363.418
3145413WATKINS
Adder
0.94941176470588240.807
960081AF2-299 C
Adder
2.58705882352941162.199
926072AC1-086 E
Adder
13.15411764705882411.181
944011AF1-069 C
50/50
22.35322.353
963041AG1-153 C
50/50
9.3799.379
957862AF2-080 E
Adder
4.5705882352941173.885
3151541CLOVER2
50/50
18.07618.076
936261AD2-033 C
Adder
15.9952941176470613.596
962562AG1-105 E
Adder
7.7364705882352946.576
926662AC1-147 E
Adder
1.84117647058823521.565
916192Z1-068 E
50/50
2.6352.635
957492AF2-043 E
Adder
1.97647058823529421.68
923852AB2-025 E
50/50
1.6571.657
939412AE1-173 E
50/50
99.43599.435
961942AG1-037 E
Adder
0.462352941176470630.393
961941AG1-037 C
Adder
0.69294117647058820.589
941032AE2-094 E
50/50
30.64130.641
941031AE2-094 C
50/50
68.41468.414
934332AD1-057 E
Adder
2.46235294117647062.093
934331AD1-057 C
Adder
4.72941176470588154.02
934321AD1-056 C
Adder
8.477647058823537.206
934322AD1-056 E
Adder
4.59882352941176453.909
927022AC1-189 E
Adder
5.6541176470588244.806
925595AC1-034 E
Adder
6.702352941176475.697
936262AD2-033 E
Adder
10.6635294117647069.064
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.99436.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.67827.678
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.7584.758
LAGNLTFEXP_LAGN->PJM
CLTF
9.6549.654
G-007PJM->LTFIMP_G-007
CMTX_NF
4.7394.739
SIGELTFEXP_SIGE->PJM
CLTF
0.2910.291
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.3487.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
126.03126.03
CPLELTFEXP_CPLE->PJM
CLTF
15.41515.415
TVALTFEXP_TVA->PJM
CLTF
7.567.56
O66PJM->LTFIMP_O-066
CMTX_NF
30.16830.168
NYPJM->LTFIMP_NY
CLTF
2.22.2
LGEELTFEXP_LGEE->PJM
CLTF
1.4681.468
WECLTFEXP_WEC->PJM
CLTF
0.7690.769

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T567_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T567_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.44 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4075.55
MW Contribution:35.65
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
932046AC2-012 E
50/50
20.31420.314
958161AF2-110 C
Adder
2.0517647058823531.744
316017AA1-139 ULT1
50/50
1.7031.703
938531AE1-072 C
50/50
27.61527.615
3145393UNCAMP
Adder
9.017647058823537.665
933981AD1-022 C
Adder
13.06588235294117711.106
900672V4-068 E
Adder
0.52235294117647060.444
3152411Z1-086 GT1
50/50
18.63118.631
924302AB2-077 E O1
Adder
1.82588235294117651.552
926662AC1-147 E
Adder
2.05411764705882361.746
916192Z1-068 E
50/50
2.9452.945
957492AF2-043 E
Adder
2.18823529411764731.86
923852AB2-025 E
Adder
1.6847058823529411.432
939412AE1-173 E
50/50
106.866106.866
961942AG1-037 E
Adder
0.49294117647058820.419
961941AG1-037 C
Adder
0.740.629
941032AE2-094 E
50/50
32.08232.082
941031AE2-094 C
50/50
71.63171.631
934332AD1-057 E
Adder
2.56941176470588272.184
934331AD1-057 C
Adder
4.9341176470588244.194
934321AD1-056 C
Adder
8.844705882352947.518
934322AD1-056 E
Adder
4.797647058823534.078
927022AC1-189 E
Adder
5.9647058823529415.07
925595AC1-034 E
Adder
7.0011764705882355.951
316084AB2-161 E
Adder
6.937647058823535.897
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
933982AD1-022 E
Adder
7.11294117647058856.046
940641AE2-051 C
50/50
31.61831.618
927146AC1-208 E
Adder
5.7070588235294124.851
934622AD1-088 E
Adder
6.6058823529411775.615
934612AD1-087 E
Adder
5.3611764705882364.557
316349AD2-085 C
Adder
4.8305882352941174.106
935112AD1-144 E
Adder
1.3835294117647061.176
3151091ELIZAR2
50/50
4.8964.896
944582AF1-123 E
50/50
164.574164.574
944592AF1-124 E
50/50
165.171165.171
923832AB2-022 E
Adder
1.93411764705882351.644
938772AE1-103 E
Adder
6.0094117647058825.108
916042Z1-036 E
Adder
43.71058823529412537.154
960082AF2-299 E
Adder
1.78117647058823541.514
946281AF1-292 C
Adder
2.21058823529411751.879
926071AC1-086 C
Adder
30.1129411764705925.596
3151051BRUNSWICKS1
50/50
30.06830.068
963042AG1-153 E
50/50
14.70814.708
927021AC1-189 C
Adder
11.97411764705882410.178
964241AG1-285 C
Adder
17.77647058823529515.11
924152AB2-059 E OP
Adder
7.3811764705882366.274
962561AG1-105 C
Adder
11.92235294117647210.134
942341AE2-247 C
Adder
2.09411764705882361.78
943462AF1-017 E
Adder
3.09058823529411742.627
958162AF2-110 E
Adder
3.2635294117647062.774
316388AE2-253 GEN
50/50
3.0993.099
919153AA1-139 E2
50/50
6.4346.434
934512AD1-075 E
Adder
6.422352941176475.459
934502AD1-074 E
Adder
25.6882352941176521.835
924516AB2-100 E1
Adder
4.1635294117647063.539
918512AA1-065 E OP
Adder
8.1494117647058816.927
940642AE2-051 E
50/50
21.07921.079
966621AG1-532 C
Adder
2.00352941176470621.703
918532AA1-067 E
Adder
1.02588235294117650.872
924022AB2-043 E O1
Adder
7.0847058823529416.022
3147223TWITTYS
Adder
1.241.054
959312AF2-222 E
Adder
14.30117647058823712.156
934576AD1-082 E
Adder
5.5282352941176474.699
916191Z1-068 C
50/50
0.0690.069
933292AC2-141 E
50/50
21.46921.469
316294AC1-161 C
50/50
8.2198.219
944602AF1-125 E
50/50
161.991161.991
3145506HICKORY
50/50
3.4483.448
943612AF1-032 E
Adder
1.42235294117647081.209
957871AF2-081 C
50/50
15.73315.733
940492AE2-034 E
Adder
4.663.961
934522AD1-076 E
Adder
9.3411764705882367.94
943172AE2-346 E
Adder
0.88823529411764710.755
918492AA1-063AE OP
Adder
5.9070588235294125.021
962571AG1-106 C
Adder
3.8952941176470593.311
917332KELFORD E
Adder
2.39058823529411772.032
925122AB2-169 E
Adder
8.4411764705882367.175
316274AC1-208 C
Adder
12.85294117647058910.925
917342Z2-044 E
Adder
0.84117647058823530.715
937482AD2-202 E
Adder
1.56941176470588251.334
3151311EDGECMA
Adder
21.6952941176470618.441
913392Y1-086 E
Adder
3.42705882352941152.913
939411AE1-173 C
50/50
160.299160.299
3137643SOCKMAN
Adder
1.02117647058823540.868
3151031BRUNSWICKG2
50/50
14.47314.473
919710AA2-057 E
Adder
5.6082352941176474.767
3150921YORKTN3
Adder
148.4764705882353126.205
3145256KINGFORK
Adder
1.49058823529411751.267
925522AC1-027 E
50/50
1.9061.906
933291AC2-141 C
50/50
50.29350.293
926755AC1-161 E
50/50
21.46921.469
941102AE2-104 E
Adder
7.99294117647058756.794
957872AF2-081 E
50/50
6.7436.743
962572AG1-106 E
Adder
1.7035294117647061.448
926214AC1-099 E
Adder
1.72705882352941181.468
932632AC2-084 E
Adder
4.623.927
964242AG1-285 E
Adder
11.85176470588235310.074
924162AB2-060 E OP
Adder
5.8058823529411764.935
964792AG1-342 E
Adder
3.1588235294117652.685
942342AE2-247 E
Adder
2.89058823529411772.457
919152AA1-139 E1
50/50
6.4346.434
316018AA1-139 ULT2
50/50
1.7031.703
920042AA2-088 E OP
Adder
15.5623529411764713.228
934521AD1-076 C
Adder
18.32705882352941315.578
934511AD1-075 C
Adder
12.6152941176470610.723
3145723EMPORIA
Adder
0.61647058823529410.524
923573AB1-173 E OP
Adder
4.6976470588235293.993
919692AA2-053 E OP
Adder
6.08588235294117655.173
925785AC1-054 E
Adder
4.8317647058823534.107
316263AC1-034 C
Adder
9.287.888
959311AF2-222 C
Adder
21.34470588235294418.143
939312AE1-162 E
Adder
1.93058823529411771.641
3150991CHESPKB
50/50
1.121.12
934065AD1-033 E
50/50
7.9347.934
937226AE2-253 E
50/50
9.2149.214
934501AD1-074 C
Adder
50.4623529411764742.893
924517AB2-100 E2
Adder
4.1635294117647063.539
957482AF2-042 E
Adder
55.2517647058823546.964
961671AG1-007 C
Adder
1.32588235294117651.127
934621AD1-088 C
Adder
13.7211.662
935172AD1-152 E
Adder
7.8611764705882366.682
943461AF1-017 C
Adder
1.89411764705882371.61
932596AC2-079 E
Adder
13.2447058823529411.258
316311AC2-079 C
Adder
8.117647058823536.9
938532AE1-072 E
50/50
14.39614.396
3146326AYDLETT TAP
50/50
2.1292.129
917122Z2-027 E
Adder
2.08705882352941161.774
920692AA2-178 E
Adder
6.2129411764705885.281
966622AG1-532 E
Adder
1.3352941176470591.135
922923AB1-081 E OP
Adder
5.2094117647058834.428
961611AG1-000B C
Adder
5.04.25
3152331SURRY 2
50/50
39.09439.094
316375AC2-012 C
50/50
2.0942.094
940541AE2-040 C
Adder
4.16470588235294153.54
940481AE2-033 C
Adder
23.45176470588235419.934
940482AE2-033 E
Adder
15.81058823529411813.439
923263AB1-132 E OP
Adder
8.7635294117647067.449
3152441Z1-086 ST
50/50
32.43232.432
3152431Z1-086 GT3
50/50
18.62318.623
3152421Z1-086 GT2
50/50
18.62318.623
925612AC1-036 E
Adder
1.11882352941176480.951
924312AB2-078 E O1
Adder
1.82588235294117651.552
926274AC1-105 E
Adder
3.5647058823529413.03
3143316POE
Adder
1.61411764705882371.372
901082W1-029 E
Adder
49.1811764705882441.804
926206AC1-098 E
Adder
5.2270588235294114.443
3151041BRUNSWICKG3
50/50
14.47314.473
3151021BRUNSWICKG1
50/50
14.47314.473
964791AG1-342 C
Adder
4.737647058823534.027
316185AD1-033 C
50/50
1.9451.945
944581AF1-123 C
50/50
71.8771.87
941101AE2-104 C
Adder
5.0270588235294114.273
316141AB2-099 E
Adder
0.36941176470588240.314
316088AB2-174 E
Adder
9.3282352941176477.929
923994AB2-040_E
Adder
8.8082352941176477.487
957481AF2-042 C
Adder
82.8776470588235370.446
961672AG1-007 E
Adder
0.7517647058823530.639
924322AB2-079 E O1
Adder
1.82588235294117651.552
943902AF1-058 E
Adder
1.70235294117647061.447
3151101ELIZAR3
50/50
5.0455.045
946282AF1-292 E
Adder
1.47411764705882351.253
944012AF1-069 E
50/50
9.0929.092
957861AF2-080 C
Adder
10.8752941176470599.244
917512Z2-088 E OP1
Adder
6.9388235294117645.898
936666AD2-085 E
Adder
7.8811764705882356.699
941591AE2-156 C
50/50
27.78727.787
3151081ELIZAR1
50/50
4.9824.982
316316AC1-027 C
50/50
0.4950.495
944591AF1-124 C
50/50
72.12672.126
944601AF1-125 C
50/50
70.76370.763
938771AE1-103 C
Adder
4.3517647058823533.699
3145413WATKINS
Adder
1.02235294117647070.869
960081AF2-299 C
Adder
2.6705882352941182.27
926072AC1-086 E
Adder
13.70588235294117811.65
944011AF1-069 C
50/50
23.40523.405
963041AG1-153 C
50/50
9.8059.805
957862AF2-080 E
Adder
4.8211764705882354.098
962562AG1-105 E
Adder
7.9482352941176486.756
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.34332.343
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.24226.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.3444.344
LAGNLTFEXP_LAGN->PJM
CLTF
9.3599.359
G-007PJM->LTFIMP_G-007
CMTX_NF
4.2584.258
SIGELTFEXP_SIGE->PJM
CLTF
0.2610.261
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.5637.563
CBM South 2LTFEXP_CBM-S2->PJM
CBM
128.067128.067
CPLELTFEXP_CPLE->PJM
CLTF
15.87115.871
TVALTFEXP_TVA->PJM
CLTF
7.2977.297
O66PJM->LTFIMP_O-066
CMTX_NF
27.12727.127
NYPJM->LTFIMP_NY
CLTF
2.0052.005
LGEELTFEXP_LGEE->PJM
CLTF
1.2871.287
WECLTFEXP_WEC->PJM
CLTF
0.6770.677

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.39 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1062.25
MW Contribution:5.57
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.68 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1086.53
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
958161AF2-110 C
Adder
0.53058823529411770.451
316017AA1-139 ULT1
80/20
0.4540.454
938531AE1-072 C
80/20
7.3717.371
315614AA2-178 C
80/20
0.6580.658
933981AD1-022 C
80/20
3.6993.699
3151261ROARAP2
80/20
0.5930.593
3147043LAWRENC
80/20
0.130.13
3152411Z1-086 GT1
80/20
7.0067.006
3151621KERR 5
80/20
0.4940.494
940641AE2-051 C
80/20
11.53811.538
316336AC2-165 C
Adder
-10.758823529411764-9.145
934611AD1-087 C
80/20
0.6230.623
3151611KERR 4
80/20
0.4940.494
942341AE2-247 C
Adder
0.50235294117647060.427
316246AF1-032 C
80/20
0.1150.115
316388AE2-253 GEN
80/20
0.8260.826
966621AG1-532 C
80/20
0.6010.601
936161AD2-022 C
Adder
3.0882352941176472.625
916191Z1-068 C
80/20
0.0180.018
316294AC1-161 C
80/20
2.1972.197
957871AF2-081 C
80/20
4.1964.196
962571AG1-106 C
80/20
1.1691.169
932631AC2-084 C
80/20
0.4330.433
316274AC1-208 C
80/20
3.8963.896
3151311EDGECMA
Adder
6.8129411764705895.791
3151601KERR 3
80/20
0.4940.494
3151581KERR 1
80/20
0.1760.176
941011AE2-092 C
Adder
-4.452941176470588-3.785
3156116Z1-036WIND
80/20
0.2750.275
939411AE1-173 C
80/20
55.12655.126
3152921DOMTR78
80/20
0.5790.579
316140AB2-099 C
80/20
0.0410.041
3137643SOCKMAN
80/20
0.3050.305
316212AC1-099 C
80/20
0.1360.136
3151031BRUNSWICKG2
80/20
5.4215.421
937481AD2-202 C
80/20
0.1810.181
3151641KERR 7
80/20
0.4940.494
933291AC2-141 C
80/20
13.44213.442
316305AF2-043 C
80/20
0.1410.141
316087AB2-174 C
80/20
0.5050.505
3151591KERR 2
80/20
0.4940.494
316036AC1-147 C
80/20
0.1480.148
316018AA1-139 ULT2
80/20
0.4540.454
934521AD1-076 C
80/20
5.1645.164
934511AD1-075 C
80/20
3.5543.554
316011AB1-132 C OP
80/20
1.0031.003
316263AC1-034 C
Adder
2.91411764705882352.477
959311AF2-222 C
Adder
5.57411764705882454.738
943461AF1-017 C
Adder
0.454117647058823570.386
316311AC2-079 C
Adder
1.9682352941176471.673
3156056W1-029WIND
80/20
0.3220.322
316375AC2-012 C
80/20
0.5420.542
313526AB2-022 C
80/20
0.1570.157
940541AE2-040 C
80/20
1.2541.254
940481AE2-033 C
80/20
7.0627.062
3151411GASTONB
80/20
1.3141.314
316181AB2-040 GEN
80/20
0.5450.545
316174AB2-169_C
80/20
0.4470.447
3156063AA2-053SOLA
80/20
0.6450.645
3151281ROARAP4
80/20
0.5610.561
3152441Z1-086 ST
80/20
12.19612.196
3152431Z1-086 GT3
80/20
7.0037.003
3152421Z1-086 GT2
80/20
7.0037.003
938821AE1-108 C
Adder
-4.716470588235294-4.009
3150991CHESPKB
80/20
0.290.29
316321Z2-027 C
80/20
0.1520.152
940491AE2-034 C
80/20
0.4850.485
934501AD1-074 C
80/20
14.21814.218
3156021HOLLOMANSOL
80/20
0.7790.779
3156073AA1-063SOLA
80/20
0.5950.595
3151371ROSEMS1
80/20
0.5440.544
961671AG1-007 C
Adder
0.410588235294117640.349
934621AD1-088 C
80/20
4.3624.362
316365AB2-100 C1
80/20
0.4150.415
316318V4-068 C
80/20
0.0340.034
316210AC1-098 C
80/20
0.4070.407
3151041BRUNSWICKG3
80/20
5.4215.421
3151021BRUNSWICKG1
80/20
5.4215.421
935171AD1-152 C
80/20
0.6380.638
964791AG1-342 C
Adder
1.48470588235294131.262
3150981CHESPKA
80/20
0.1750.175
316185AD1-033 C
80/20
0.5160.516
944581AF1-123 C
80/20
19.1219.12
941101AE2-104 C
Adder
1.31.105
316320Y1-086 C
80/20
0.0920.092
3156083AA2-088SOLA
80/20
0.4390.439
313506AB1-173 C OP
80/20
0.4830.483
3151361ROSEMG1
80/20
0.8780.878
957481AF2-042 C
80/20
28.34128.341
316349AD2-085 C
Adder
1.15882352941176480.985
3151091ELIZAR2
80/20
1.2731.273
316023AB2-100 C2
80/20
0.4150.415
946281AF1-292 C
80/20
0.6630.663
926071AC1-086 C
80/20
9.0389.038
316317KELFORD C
80/20
0.1530.153
3151051BRUNSWICKS1
80/20
11.26211.262
927021AC1-189 C
Adder
3.66117647058823573.112
3151531CLOVER1
80/20
6.3346.334
964241AG1-285 C
80/20
5.3655.365
962561AG1-105 C
Adder
3.70941176470588243.153
3151101ELIZAR3
80/20
1.3121.312
316315AB2-025 C
80/20
0.1780.178
316129AC1-054 C
80/20
0.5240.524
957861AF2-080 C
Adder
3.3247058823529412.826
941591AE2-156 C
80/20
7.2027.202
3151081ELIZAR1
80/20
1.2951.295
316316AC1-027 C
80/20
0.130.13
944591AF1-124 C
80/20
19.18819.188
944601AF1-125 C
80/20
18.82618.826
938771AE1-103 C
Adder
1.16941176470588240.994
960081AF2-299 C
80/20
0.8010.801
944011AF1-069 C
80/20
8.8768.876
963041AG1-153 C
80/20
3.6733.673
3151541CLOVER2
80/20
6.2756.275
3151631KERR 6
80/20
0.4940.494
936261AD2-033 C
Adder
4.2364705882352943.601
936171AD2-023 C
Adder
1.80117647058823521.531
943171AE2-346 C
80/20
0.0950.095
961941AG1-037 C
80/20
0.2130.213
3151391GASTONA
80/20
1.3141.314
3151381ROSEMG2
80/20
0.4110.411
941031AE2-094 C
80/20
27.16527.165
934331AD1-057 C
Adder
1.52117647058823541.293
934321AD1-056 C
Adder
2.72588235294117662.317
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.53211.532
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.0379.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5141.514
LAGNLTFEXP_LAGN->PJM
CLTF
3.2073.207
SIGELTFEXP_SIGE->PJM
CLTF
0.0910.091
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5712.571
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.69643.696
CPLELTFEXP_CPLE->PJM
CLTF
5.3965.396
TVALTFEXP_TVA->PJM
CLTF
2.4942.494
NYPJM->LTFIMP_NY
CLTF
0.5140.514
LGEELTFEXP_LGEE->PJM
CLTF
0.4480.448
WECLTFEXP_WEC->PJM
CLTF
0.2390.239

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.07 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3287.01
MW Contribution:23.07
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150731STONECA
Adder
8.9505882352941187.608
935161AD1-151 C
Adder
21.46588235294117618.246
3151221GRAVEL6
80/20
3.4833.483
3151201GRAVEL4
80/20
3.4873.487
958161AF2-110 C
80/20
1.9761.976
316017AA1-139 ULT1
80/20
1.5751.575
938531AE1-072 C
80/20
25.56125.561
933981AD1-022 C
Adder
12.39411764705882410.535
3152411Z1-086 GT1
80/20
16.26716.267
943471AF1-018 C
Adder
7.9588235294117656.765
316083AB2-161 C
80/20
0.7870.787
316072AD1-144 C
80/20
0.4020.402
940641AE2-051 C
80/20
27.30727.307
316336AC2-165 C
Adder
13.69411764705882511.64
934611AD1-087 C
80/20
1.761.76
942341AE2-247 C
80/20
2.1432.143
316246AF1-032 C
80/20
0.4130.413
316388AE2-253 GEN
80/20
2.8622.862
966621AG1-532 C
Adder
1.9870588235294121.689
3150651CHESTF6
Adder
24.50588235294117520.83
916191Z1-068 C
80/20
0.0640.064
316294AC1-161 C
80/20
7.267.26
957871AF2-081 C
80/20
14.54714.547
936591AD2-074 C
Adder
5.7647058823529424.9
3151151S HAMPT1
80/20
2.1352.135
316313AB2-026 C
80/20
0.5480.548
962571AG1-106 C
Adder
3.80823529411764743.237
316274AC1-208 C
Adder
12.4023529411764710.542
3151311EDGECMA
Adder
20.74352941176470817.632
3150851SPRUNCC
80/20
0.2220.222
3156116Z1-036WIND
80/20
0.9440.944
939411AE1-173 C
80/20
140.502140.502
3137643SOCKMAN
Adder
1.00.85
3151031BRUNSWICKG2
80/20
12.67612.676
937481AD2-202 C
80/20
0.5110.511
944631AF1-128 C
Adder
48.040.8
3150921YORKTN3
Adder
157.0388235294118133.483
933291AC2-141 C
80/20
44.42644.426
316305AF2-043 C
80/20
0.5050.505
944641AF1-129 C
Adder
134.59058823529412114.402
316240AF1-291 C
Adder
2.86941176470588262.439
316381AD1-082 C
80/20
1.7951.795
316036AC1-147 C
80/20
0.5360.536
316018AA1-139 ULT2
80/20
1.5751.575
934521AD1-076 C
Adder
17.34705882352941214.745
934511AD1-075 C
Adder
11.94117647058823610.15
316263AC1-034 C
Adder
8.8741176470588247.543
959311AF2-222 C
Adder
23.07176470588235519.611
316233AE1-074 C
80/20
3.7763.776
940551AE2-041 C
Adder
7.9588235294117656.765
3151211GRAVEL5
80/20
3.4433.443
943461AF1-017 C
80/20
1.9381.938
316311AC2-079 C
80/20
8.2428.242
3156056W1-029WIND
80/20
1.1231.123
961611AG1-000B C
Adder
21.72352941176470518.465
316236AE1-162 C
80/20
0.4930.493
3152331SURRY 2
80/20
34.47834.478
316375AC2-012 C
80/20
1.9631.963
313526AB2-022 C
80/20
0.5460.546
940541AE2-040 C
80/20
4.2084.208
940481AE2-033 C
80/20
23.64823.648
3152441Z1-086 ST
80/20
28.31628.316
3152431Z1-086 GT3
80/20
16.2616.26
3152421Z1-086 GT2
80/20
16.2616.26
942001AE2-212 C
80/20
2.9732.973
3151161SURRY 1
80/20
33.88933.889
3150991CHESPKB
80/20
1.051.05
316321Z2-027 C
80/20
0.5270.527
943741AF1-042 C
Adder
3.01647058823529422.564
934501AD1-074 C
Adder
47.763529411764740.599
961671AG1-007 C
Adder
1.26588235294117671.076
934621AD1-088 C
80/20
13.42613.426
946301AF1-294 C
Adder
4.8470588235294124.12
942461AE2-259 C
Adder
12.70588235294117810.8
939191AE1-149 C
80/20
15.16215.162
957601AF2-054 C
Adder
2.37764705882352922.021
316365AB2-100 C1
80/20
1.3721.372
3151041BRUNSWICKG3
80/20
12.67612.676
3151021BRUNSWICKG1
80/20
12.67612.676
964791AG1-342 C
Adder
4.6788235294117653.977
3150861SPRUNCD
80/20
0.2220.222
940431AE2-027 C
Adder
17.26588235294117614.676
3150981CHESPKA
80/20
0.6340.634
316185AD1-033 C
80/20
1.7941.794
944581AF1-123 C
80/20
66.2266.22
941101AE2-104 C
80/20
4.8434.843
316320Y1-086 C
80/20
0.3190.319
316405AF2-144 C
80/20
0.4280.428
957481AF2-042 C
80/20
77.49977.499
316169AC1-164 GEN
Adder
44.9588235294117738.215
316349AD2-085 C
80/20
4.9434.943
3151091ELIZAR2
80/20
4.5754.575
316258AE1-075 C
80/20
0.5030.503
316023AB2-100 C2
80/20
1.3721.372
946281AF1-292 C
Adder
2.19294117647058861.864
926071AC1-086 C
Adder
29.4425.024
3151051BRUNSWICKS1
80/20
26.33426.334
927021AC1-189 C
Adder
11.4094117647058839.698
3151531CLOVER1
80/20
17.87817.878
964241AG1-285 C
Adder
17.89058823529411815.207
962561AG1-105 C
Adder
11.8176470588235310.045
3151101ELIZAR3
80/20
4.7154.715
316315AB2-025 C
80/20
0.5980.598
961951AG1-038 C
Adder
3.3341176470588242.834
957861AF2-080 C
Adder
10.3623529411764718.808
3138533PONTONDP
Adder
0.87294117647058820.742
3150601CHESTF5
Adder
76.7117647058823665.205
941591AE2-156 C
80/20
26.02126.021
3151081ELIZAR1
80/20
4.6564.656
316316AC1-027 C
80/20
0.460.46
944591AF1-124 C
80/20
66.45566.455
944601AF1-125 C
80/20
65.265.2
938771AE1-103 C
80/20
4.24.2
960081AF2-299 C
Adder
2.64941176470588242.252
944011AF1-069 C
80/20
20.29620.296
963041AG1-153 C
80/20
8.5888.588
3151541CLOVER2
80/20
17.71117.711
936261AD2-033 C
Adder
17.57529411764705814.939
961791AG1-021 C
Adder
2.35764705882352972.004
3150841SPRUNCB
80/20
12.34712.347
3150831SPRUNCA
80/20
12.34712.347
961941AG1-037 C
Adder
0.71058823529411760.604
941031AE2-094 C
80/20
62.11762.117
934331AD1-057 C
Adder
4.7623529411764714.048
934321AD1-056 C
Adder
8.5376470588235297.257
958211AF2-115 C
Adder
2.94705882352941152.505
316303AF2-085
80/20
6.3826.382
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.6437.64
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.68227.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8064.806
LAGNLTFEXP_LAGN->PJM
CLTF
9.5879.587
SIGELTFEXP_SIGE->PJM
CLTF
0.2960.296
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1347.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.889122.889
CPLELTFEXP_CPLE->PJM
CLTF
14.96614.966
TVALTFEXP_TVA->PJM
CLTF
7.5327.532
NYPJM->LTFIMP_NY
CLTF
2.4692.469
LGEELTFEXP_LGEE->PJM
CLTF
1.5071.507
WECLTFEXP_WEC->PJM
CLTF
0.7840.784

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.59 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3225.32
MW Contribution:25.81
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.29 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3436.04
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150981CHESPKA
50/50
0.7090.709
316185AD1-033 C
50/50
2.0522.052
944581AF1-123 C
50/50
75.87875.878
941101AE2-104 C
50/50
4.9664.966
316320Y1-086 C
50/50
0.3530.353
316141AB2-099 E
Adder
0.320.272
932046AC2-012 E
50/50
21.31821.318
958161AF2-110 C
50/50
2.0262.026
316017AA1-139 ULT1
50/50
1.781.78
938531AE1-072 C
50/50
28.76728.767
3145393UNCAMP
Adder
8.367.106
315614AA2-178 C
50/50
2.2542.254
933981AD1-022 C
Adder
11.96352941176470710.169
900672V4-068 E
Adder
0.452941176470588240.385
924302AB2-077 E O1
Adder
1.3164705882352941.119
926662AC1-147 E
50/50
2.1552.155
916192Z1-068 E
50/50
3.0983.098
957492AF2-043 E
50/50
2.2332.233
923852AB2-025 E
Adder
1.06941176470588250.909
939412AE1-173 E
50/50
88.25188.251
961942AG1-037 E
Adder
0.427058823529411770.363
961941AG1-037 C
Adder
0.640.544
941032AE2-094 E
50/50
22.37122.371
941031AE2-094 C
50/50
49.94849.948
934332AD1-057 E
Adder
1.96588235294117661.671
934331AD1-057 C
Adder
3.7752941176470593.209
934321AD1-056 C
Adder
6.7670588235294115.752
934322AD1-056 E
Adder
3.6705882352941183.12
927022AC1-189 E
Adder
4.86235294117647054.133
925595AC1-034 E
Adder
5.4105882352941184.599
936262AD2-033 E
Adder
7.8811764705882356.699
316084AB2-161 E
Adder
5.6282352941176474.784
316072AD1-144 C
50/50
0.4210.421
3145946PLYMOUTH TP
Adder
0.451764705882352960.384
933982AD1-022 E
Adder
6.5129411764705885.536
940641AE2-051 C
50/50
24.20324.203
927146AC1-208 E
Adder
4.5117647058823533.835
934622AD1-088 E
Adder
4.70470588235294153.999
934612AD1-087 E
Adder
3.80117647058823543.231
927255AC1-221 E
Adder
3.5270588235294122.998
3144216WINCHST
50/50
0.1770.177
316349AD2-085 C
Adder
4.4694117647058833.799
935112AD1-144 E
50/50
1.4091.409
3151091ELIZAR2
50/50
5.1465.146
944582AF1-123 E
50/50
173.752173.752
944592AF1-124 E
50/50
174.381174.381
923832AB2-022 E
50/50
1.9881.988
938772AE1-103 E
50/50
5.6365.636
916042Z1-036 E
50/50
42.96342.963
960082AF2-299 E
Adder
1.27882352941176471.087
946281AF1-292 C
Adder
1.58823529411764721.35
926071AC1-086 C
Adder
22.77647058823529519.36
963042AG1-153 E
Adder
10.2835294117647068.741
927021AC1-189 C
Adder
9.768.296
964241AG1-285 C
Adder
12.75176470588235310.839
924152AB2-059 E OP
Adder
5.70470588235294154.849
962561AG1-105 C
Adder
8.5494117647058847.267
942341AE2-247 C
Adder
1.93764705882352951.647
943462AF1-017 E
Adder
2.86000000000000032.431
958162AF2-110 E
50/50
3.2233.223
316246AF1-032 C
50/50
0.4470.447
316388AE2-253 GEN
50/50
3.2483.248
919153AA1-139 E2
50/50
6.7236.723
934512AD1-075 E
Adder
5.95411764705882355.061
934502AD1-074 E
Adder
23.81647058823529420.244
924516AB2-100 E1
Adder
2.92235294117647062.484
918512AA1-065 E OP
Adder
7.1905882352941186.112
940642AE2-051 E
50/50
16.13516.135
966621AG1-532 C
Adder
1.43882352941176481.223
918532AA1-067 E
Adder
0.85764705882352940.729
924022AB2-043 E O1
Adder
5.1070588235294124.341
3147223TWITTYS
Adder
0.89647058823529410.762
959312AF2-222 E
Adder
10.3552941176470598.802
934576AD1-082 E
Adder
4.4847058823529413.812
916191Z1-068 C
50/50
0.0720.072
933292AC2-141 E
50/50
24.4824.48
316294AC1-161 C
50/50
9.3719.371
944602AF1-125 E
50/50
171.025171.025
3145506HICKORY
50/50
3.633.63
943612AF1-032 E
50/50
1.4511.451
957871AF2-081 C
50/50
16.44116.441
940492AE2-034 E
50/50
4.4344.434
934522AD1-076 E
Adder
8.667.361
943172AE2-346 E
Adder
0.76823529411764710.653
918492AA1-063AE OP
Adder
4.80941176470588254.088
962571AG1-106 C
Adder
2.94588235294117642.504
917332KELFORD E
Adder
2.01647058823529421.714
925122AB2-169 E
Adder
7.4694117647058836.349
316274AC1-208 C
Adder
10.168.636
917342Z2-044 E
Adder
0.65529411764705890.557
937482AD2-202 E
Adder
1.1129411764705880.946
3151311EDGECMA
Adder
16.76352941176470814.249
934012AD1-025 E
Adder
8.837647058823537.512
913392Y1-086 E
50/50
3.5213.521
3156116Z1-036WIND
50/50
0.9890.989
939411AE1-173 C
50/50
132.376132.376
3137643SOCKMAN
Adder
0.77882352941176480.662
919710AA2-057 E
Adder
4.43.74
316160AE1-175 E
Adder
1.12470588235294120.956
3150921YORKTN3
50/50
162.48162.48
3145256KINGFORK
50/50
1.5181.518
925522AC1-027 E
50/50
2.0032.003
933291AC2-141 C
50/50
57.34757.347
926755AC1-161 E
50/50
24.4824.48
941102AE2-104 E
50/50
7.8957.895
316305AF2-043 C
50/50
0.5470.547
957872AF2-081 E
50/50
7.0467.046
962572AG1-106 E
Adder
1.28941176470588251.096
926214AC1-099 E
Adder
1.38941176470588231.181
932632AC2-084 E
Adder
3.71882352941176463.161
964242AG1-285 E
Adder
8.5011764705882367.226
924162AB2-060 E OP
Adder
4.1870588235294123.559
964792AG1-342 E
Adder
2.2623529411764711.923
924814AB2-134 E
Adder
11.1823529411764729.505
942342AE2-247 E
Adder
2.6752941176470592.274
316036AC1-147 C
50/50
0.60.6
919152AA1-139 E1
50/50
6.7236.723
316018AA1-139 ULT2
50/50
1.781.78
920042AA2-088 E OP
Adder
13.60117647058823611.561
934521AD1-076 C
Adder
16.99176470588235314.443
934511AD1-075 C
Adder
11.6964705882352959.942
3145723EMPORIA
Adder
0.44705882352941180.38
923573AB1-173 E OP
Adder
3.50352941176470622.978
919692AA2-053 E OP
Adder
4.8294117647058834.105
925785AC1-054 E
Adder
3.63176470588235353.087
316263AC1-034 C
Adder
7.1729411764705896.097
959311AF2-222 C
Adder
15.45647058823529513.138
939192AE1-149 E
Adder
4.0364705882352953.431
939312AE1-162 E
50/50
1.9371.937
3150991CHESPKB
50/50
1.1761.176
934065AD1-033 E
50/50
8.3718.371
937226AE2-253 E
50/50
9.6579.657
316321Z2-027 C
50/50
0.5770.577
940491AE2-034 C
50/50
1.6591.659
934501AD1-074 C
Adder
46.7858823529411839.768
924517AB2-100 E2
Adder
2.92235294117647062.484
957482AF2-042 E
Adder
39.0611764705882433.202
961671AG1-007 C
Adder
1.05647058823529430.898
934621AD1-088 C
Adder
9.7717647058823538.306
935172AD1-152 E
Adder
5.5847058823529414.747
957832AF2-077 E
Adder
1.38000000000000011.173
943461AF1-017 C
Adder
1.75294117647058821.49
932596AC2-079 E
Adder
12.36705882352941210.512
316311AC2-079 C
Adder
7.586.443
938532AE1-072 E
50/50
14.99614.996
3146326AYDLETT TAP
50/50
2.2162.216
917122Z2-027 E
50/50
2.1312.131
3156056W1-029WIND
50/50
1.211.21
920692AA2-178 E
50/50
5.9125.912
966622AG1-532 E
Adder
0.95882352941176460.815
922923AB1-081 E OP
Adder
4.0270588235294123.423
961611AG1-000B C
Adder
17.5717647058823514.936
316236AE1-162 C
50/50
0.4750.475
3152331SURRY 2
50/50
52.22852.228
316375AC2-012 C
50/50
2.1982.198
313526AB2-022 C
50/50
0.6030.603
940541AE2-040 C
Adder
2.6435294117647062.247
940481AE2-033 C
Adder
15.09058823529411912.827
940482AE2-033 E
Adder
10.1729411764705898.647
923263AB1-132 E OP
Adder
6.6282352941176485.634
925612AC1-036 E
Adder
0.80823529411764720.687
924312AB2-078 E O1
Adder
1.3164705882352941.119
926274AC1-105 E
Adder
2.5482352941176472.166
939191AE1-149 C
Adder
8.8411764705882367.515
901082W1-029 E
50/50
49.64949.649
926206AC1-098 E
Adder
4.2070588235294123.576
964791AG1-342 C
Adder
3.39411764705882352.885
316088AB2-174 E
Adder
6.877647058823535.846
923994AB2-040_E
Adder
6.5694117647058825.584
957481AF2-042 C
Adder
58.59176470588235549.803
961672AG1-007 E
Adder
0.59882352941176480.509
924322AB2-079 E O1
Adder
1.3164705882352941.119
943902AF1-058 E
Adder
1.21411764705882351.032
3151101ELIZAR3
50/50
5.3035.303
946282AF1-292 E
Adder
1.05882352941176470.9
944012AF1-069 E
50/50
6.346.34
957861AF2-080 C
Adder
8.8647058823529427.535
917512Z2-088 E OP1
Adder
5.58588235294117654.748
927226AC1-216 E
Adder
6.8258823529411765.802
962962AG1-145 E
Adder
1.36235294117647051.158
936666AD2-085 E
Adder
7.2929411764705886.199
941591AE2-156 C
50/50
29.1829.18
3151081ELIZAR1
50/50
5.2375.237
316316AC1-027 C
50/50
0.520.52
944591AF1-124 C
50/50
76.14876.148
944601AF1-125 C
50/50
74.70974.709
938771AE1-103 C
50/50
4.0814.081
3145413WATKINS
Adder
0.93058823529411770.791
960081AF2-299 C
Adder
1.91882352941176481.631
926072AC1-086 E
Adder
10.3658823529411768.811
944011AF1-069 C
50/50
16.3216.32
963041AG1-153 C
Adder
6.8564705882352955.828
957862AF2-080 E
Adder
3.9294117647058823.34
936261AD2-033 C
Adder
11.82117647058823610.048
962562AG1-105 E
Adder
5.74.845
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.74418.744
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.28317.283
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.712.71
LAGNLTFEXP_LAGN->PJM
CLTF
6.3446.344
G-007PJM->LTFIMP_G-007
CMTX_NF
3.0313.031
SIGELTFEXP_SIGE->PJM
CLTF
0.160.16
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.515.51
CBM South 2LTFEXP_CBM-S2->PJM
CBM
91.70491.704
CPLELTFEXP_CPLE->PJM
CLTF
11.56611.566
TVALTFEXP_TVA->PJM
CLTF
4.9264.926
O66PJM->LTFIMP_O-066
CMTX_NF
19.32919.329
NYPJM->LTFIMP_NY
CLTF
1.4491.449
LGEELTFEXP_LGEE->PJM
CLTF
0.760.76
WECLTFEXP_WEC->PJM
CLTF
0.3980.398

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3221.97
MW Contribution:26.18
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961942AG1-037 E
Adder
0.43882352941176470.373
961941AG1-037 C
Adder
0.65882352941176480.56
941032AE2-094 E
Adder
22.03411764705882418.729
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
962571AG1-106 C
Adder
3.1282352941176472.659
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
933291AC2-141 C
50/50
57.45157.451
926755AC1-161 E
50/50
24.52424.524
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
962572AG1-106 E
Adder
1.36823529411764721.163
926214AC1-099 E
Adder
1.43882352941176481.223
932632AC2-084 E
Adder
3.8494117647058823.272
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
919152AA1-139 E1
50/50
6.7746.774
316018AA1-139 ULT2
50/50
1.7931.793
920042AA2-088 E OP
Adder
14.01647058823529311.914
934521AD1-076 C
Adder
17.32941176470588514.73
934511AD1-075 C
Adder
11.92941176470588310.14
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
3152331SURRY 2
50/50
52.46452.464
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940481AE2-033 C
Adder
17.1423529411764714.571
940482AE2-033 E
Adder
11.5564705882352949.823
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
935172AD1-152 E
Adder
5.5800000000000014.743
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
3151101ELIZAR3
50/50
5.3455.345
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
957861AF2-080 C
Adder
9.1035294117647067.738
917512Z2-088 E OP1
Adder
5.7423529411764714.881
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
3151091ELIZAR2
50/50
5.1875.187
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
3151081ELIZAR1
50/50
5.2795.279
316316AC1-027 C
50/50
0.5240.524
944591AF1-124 C
50/50
76.6476.64
944601AF1-125 C
50/50
75.19275.192
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
957862AF2-080 E
Adder
4.0352941176470593.43
936261AD2-033 C
Adder
10.6341176470588249.039
962562AG1-105 E
Adder
5.75647058823529444.893
941031AE2-094 C
Adder
49.1976470588235341.818
934332AD1-057 E
Adder
2.05294117647058851.745
934331AD1-057 C
Adder
3.94352941176470573.352
934321AD1-056 C
Adder
7.0682352941176476.008
934322AD1-056 E
Adder
3.83411764705882343.259
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3221.97
MW Contribution:26.18
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
962571AG1-106 C
Adder
3.1282352941176472.659
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
933291AC2-141 C
50/50
57.45157.451
926755AC1-161 E
50/50
24.52424.524
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
962572AG1-106 E
Adder
1.36823529411764721.163
926214AC1-099 E
Adder
1.43882352941176481.223
932632AC2-084 E
Adder
3.8494117647058823.272
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
919152AA1-139 E1
50/50
6.7746.774
316018AA1-139 ULT2
50/50
1.7931.793
920042AA2-088 E OP
Adder
14.01647058823529311.914
934521AD1-076 C
Adder
17.32941176470588514.73
934511AD1-075 C
Adder
11.92941176470588310.14
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
3152331SURRY 2
50/50
52.46452.464
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940481AE2-033 C
Adder
17.1423529411764714.571
940482AE2-033 E
Adder
11.5564705882352949.823
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
3151101ELIZAR3
50/50
5.3455.345
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
3151091ELIZAR2
50/50
5.1875.187
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
957861AF2-080 C
Adder
9.1035294117647067.738
917512Z2-088 E OP1
Adder
5.7423529411764714.881
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
3151081ELIZAR1
50/50
5.2795.279
316316AC1-027 C
50/50
0.5240.524
944591AF1-124 C
50/50
76.6476.64
944601AF1-125 C
50/50
75.19275.192
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
957862AF2-080 E
Adder
4.0352941176470593.43
936261AD2-033 C
Adder
10.6341176470588249.039
962562AG1-105 E
Adder
5.75647058823529444.893
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961942AG1-037 E
Adder
0.43882352941176470.373
961941AG1-037 C
Adder
0.65882352941176480.56
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934332AD1-057 E
Adder
2.05294117647058851.745
934331AD1-057 C
Adder
3.94352941176470573.352
934321AD1-056 C
Adder
7.0682352941176476.008
934322AD1-056 E
Adder
3.83411764705882343.259
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3221.81
MW Contribution:26.18
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.28 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3435.8
MW Contribution:14.38
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961942AG1-037 E
Adder
0.43882352941176470.373
961941AG1-037 C
Adder
0.65882352941176480.56
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934332AD1-057 E
Adder
2.05294117647058851.745
934331AD1-057 C
Adder
3.94352941176470573.352
934321AD1-056 C
Adder
7.0682352941176476.008
934322AD1-056 E
Adder
3.83411764705882343.259
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
3151091ELIZAR2
50/50
5.1875.187
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
962571AG1-106 C
Adder
3.1282352941176472.659
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
933291AC2-141 C
50/50
57.45157.451
926755AC1-161 E
50/50
24.52424.524
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
962572AG1-106 E
Adder
1.36823529411764721.163
926214AC1-099 E
Adder
1.43882352941176481.223
932632AC2-084 E
Adder
3.8494117647058823.272
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
919152AA1-139 E1
50/50
6.7746.774
316018AA1-139 ULT2
50/50
1.7931.793
920042AA2-088 E OP
Adder
14.01647058823529311.914
934521AD1-076 C
Adder
17.32941176470588514.73
934511AD1-075 C
Adder
11.92941176470588310.14
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
3152331SURRY 2
50/50
52.46452.464
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940481AE2-033 C
Adder
17.1423529411764714.571
940482AE2-033 E
Adder
11.5564705882352949.823
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
3151101ELIZAR3
50/50
5.3455.345
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
957861AF2-080 C
Adder
9.1035294117647067.738
917512Z2-088 E OP1
Adder
5.7423529411764714.881
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
3151081ELIZAR1
50/50
5.2795.279
316316AC1-027 C
50/50
0.5240.524
944591AF1-124 C
50/50
76.6476.64
944601AF1-125 C
50/50
75.19275.192
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
957862AF2-080 E
Adder
4.0352941176470593.43
936261AD2-033 C
Adder
10.6341176470588249.039
962562AG1-105 E
Adder
5.75647058823529444.893
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401

Details for AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.42 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:742.63
MW Contribution:8.64
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.42 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:762.95
MW Contribution:10.63
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
933981AD1-022 C
80/20
5.6875.687
3151261ROARAP2
80/20
2.1232.123
3147043LAWRENC
80/20
0.5790.579
3151621KERR 5
80/20
0.8620.862
316049AB1-081 C OP
80/20
1.4941.494
3151611KERR 4
80/20
0.8620.862
966621AG1-532 C
80/20
3.2993.299
3151151S HAMPT1
80/20
0.9570.957
962571AG1-106 C
80/20
5.4965.496
932631AC2-084 C
80/20
1.171.17
316274AC1-208 C
80/20
11.22611.226
3151311EDGECMA
80/20
16.55516.555
3151601KERR 3
80/20
0.8620.862
3151581KERR 1
80/20
0.3080.308
3152661PLYWOOD A
80/20
0.6390.639
3152921DOMTR78
80/20
0.8540.854
316140AB2-099 C
80/20
0.0920.092
3137643SOCKMAN
80/20
1.2371.237
316212AC1-099 C
80/20
0.3680.368
316319Z2-044 C
80/20
0.2310.231
3151641KERR 7
80/20
0.8620.862
316087AB2-174 C
80/20
2.4642.464
313527AB2-043 C
80/20
0.3630.363
3151591KERR 2
80/20
0.8620.862
934521AD1-076 C
80/20
7.0327.032
934511AD1-075 C
80/20
4.844.84
316011AB1-132 C OP
80/20
4.7154.715
316263AC1-034 C
80/20
6.9816.981
959311AF2-222 C
80/20
8.6368.636
940481AE2-033 C
80/20
63.40763.407
3151411GASTONB
80/20
6.1766.176
316181AB2-040 GEN
80/20
2.5112.511
316174AB2-169_C
80/20
0.7190.719
3156063AA2-053SOLA
80/20
2.1582.158
3151281ROARAP4
80/20
2.0092.009
3156011CONETOE2SOL
80/20
1.1751.175
316238AB2-078 C O1
80/20
0.2290.229
316237AB2-079 C O1
80/20
0.2290.229
934501AD1-074 C
80/20
19.36119.361
3156021HOLLOMANSOL
80/20
1.5861.586
3156073AA1-063SOLA
80/20
1.8141.814
3151371ROSEMS1
80/20
2.4382.438
961671AG1-007 C
80/20
0.9120.912
934621AD1-088 C
80/20
4.4044.404
316359AB2-059 C OP
80/20
1.7611.761
946301AF1-294 C
80/20
1.8661.866
316365AB2-100 C1
80/20
2.7732.773
316318V4-068 C
80/20
0.0750.075
316210AC1-098 C
80/20
1.0991.099
316327AA2-057 C
80/20
1.4891.489
316239AB2-077 C O1
80/20
0.2290.229
964791AG1-342 C
80/20
2.0352.035
3156083AA2-088SOLA
80/20
0.9350.935
313506AB1-173 C OP
80/20
2.2292.229
3151361ROSEMG1
80/20
3.9363.936
316005AA1-067 C
80/20
0.2210.221
957481AF2-042 C
80/20
24.31224.312
316023AB2-100 C2
80/20
2.7732.773
946281AF1-292 C
80/20
3.6413.641
926071AC1-086 C
80/20
42.49342.493
316317KELFORD C
80/20
0.370.37
927021AC1-189 C
80/20
7.5497.549
3151531CLOVER1
80/20
5.8195.819
964241AG1-285 C
80/20
7.2257.225
316034AC1-036 C
80/20
0.1240.124
962561AG1-105 C
80/20
5.2875.287
316129AC1-054 C
80/20
1.341.34
957861AF2-080 C
80/20
6.8566.856
316131AB2-060 C
80/20
1.0341.034
3138533PONTONDP
80/20
0.3360.336
316118AC1-105 C
80/20
0.4840.484
960081AF2-299 C
80/20
4.3984.398
3151631KERR 6
80/20
0.8620.862
936261AD2-033 C
80/20
8.0298.029
961791AG1-021 C
80/20
0.9080.908
3144293JTRSVLE
80/20
0.2090.209
943171AE2-346 C
80/20
0.2140.214
961941AG1-037 C
80/20
0.4820.482
3151391GASTONA
80/20
6.1766.176
3151381ROSEMG2
80/20
1.8431.843
934331AD1-057 C
80/20
5.1335.133
934321AD1-056 C
80/20
9.2019.201
958211AF2-115 C
80/20
1.1351.135
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.20711.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.5767.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.3611.361
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
SIGELTFEXP_SIGE->PJM
CLTF
0.0840.084
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1882.188
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.15434.154
CPLELTFEXP_CPLE->PJM
CLTF
4.5894.589
TVALTFEXP_TVA->PJM
CLTF
2.0182.018
NYPJM->LTFIMP_NY
CLTF
0.3660.366
LGEELTFEXP_LGEE->PJM
CLTF
0.4310.431
WECLTFEXP_WEC->PJM
CLTF
0.2290.229
CONTINGENCY 'DVP_P4-2: 511T556_SRT-S-1'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 556_SRT-S-3'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A'
 OPEN BRANCH FROM BUS 314218 TO BUS 314196 CKT 1   /*6ELMONT      230.0 - 6LADYSMITH   230.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1   /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T567_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1   /*6CHCKAHM     230.0 - 8CHCKAHM     500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
314677 to 314747 ckt 1
314282 to 314285 ckt 1
314285 to 314316 ckt 1
314563 to 940480 ckt 1
314692 to 314677 ckt 1
314435 to 314282 ckt 1
314902 to 314282 ckt 2
314902 to 314914 ckt 1
314914 to 314322 ckt 1
314914 to 314918 ckt 1
314924 to 314903 ckt 1
940480 to 314435 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
DVP_P4-6: CHASE C T342_SRT-A
BreakerAC126.04 %221.4C279.0574.47
GD1DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P4-6: CHASE C T342_SRT-A
BreakerAC165.99 %208.7C346.4192.46
GD1DVP
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
DVP_P1-2: LN 1012_SRT-A-4
SingleAC101.66 %205.86B209.27100.0
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC100.89 %984.18B992.946.65
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 246_SRT-A
SingleAC108.46 %678.68B736.137.55
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A
SingleAC104.8 %678.68B711.276.45
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Base Case
SingleAC102.72 %678.68A697.117.01
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.8 %3220.44B3342.6818.29
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC119.82 %3220.44B3858.5922.66
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC111.38 %3220.44B3586.7813.3
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
SingleAC111.09 %3220.44B3577.6113.91
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC110.41 %3940.0C4350.1723.07
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H1T594_SRT-S
BreakerAC106.75 %3940.0C4205.8122.31
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC116.97 %3220.44B3767.0315.0
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC114.22 %3220.44B3678.4916.05
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC111.99 %3940.0C4412.3626.11
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC106.7 %4070.2B4342.9725.13
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC102.59 %4070.2B4175.6225.13
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC121.18 %3220.44B3902.6214.66
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC120.07 %3220.44B3866.7915.85
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC117.55 %3940.0C4631.3225.71
GD1DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC104.04 %4070.2B4234.722.06
GD1DVP
AG1-285 TP-3CHASCTY 115.0 kV Ckt 1 line
DVP_P4-2: 15832_SRT-A
BreakerAC107.58 %349.0C375.45166.99
GD1DVP
AG1-285 TP-3CHASCTY 115.0 kV Ckt 1 line
DVP_P4-5: FARMVIL L432_SRT-A-1
BreakerAC107.57 %349.0C375.41166.99

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-6: CHASE C T342_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.04 %
Rating:221.4 MVA
Rating Type:C
MVA to Mitigate:279.05
MW Contribution:74.47
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936261AD2-033 C
50/50
34.78234.782
961791AG1-021 C
50/50
4.8164.816
964241AG1-285 C
50/50
33.44533.445
316034AC1-036 C
50/50
0.6250.625
958212AF2-115 E
50/50
5.1285.128
3144293JTRSVLE
50/50
1.1041.104
3147223TWITTYS
50/50
2.5462.546
959312AF2-222 E
50/50
29.87729.877
946302AF1-294 E
50/50
8.3838.383
925612AC1-036 E
50/50
2.2972.297
946301AF1-294 C
50/50
9.99.9
942461AE2-259 C
50/50
26.75626.756
961792AG1-021 E
50/50
4.1034.103
936262AD2-033 E
50/50
23.18823.188
958211AF2-115 C
50/50
6.026.02
924162AB2-060 E OP
50/50
11.41611.416
964242AG1-285 E
50/50
22.29622.296
959311AF2-222 C
50/50
44.59344.593
3147133PAMPLIN
50/50
2.6642.664
942462AE2-259 E
50/50
17.83717.837
316131AB2-060 C
50/50
3.953.95
3138533PONTONDP
50/50
1.7841.784
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.010.01
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0320.032
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0180.018
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0190.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0060.006
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0470.047
MDUPJM->LTFIMP_MDU
CLTF
0.0020.002
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0140.014
O66PJM->LTFIMP_O-066
CMTX_NF
0.1230.123
NYPJM->LTFIMP_NY
CLTF
0.010.01
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0380.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0110.011

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-6: CHASE C T342_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.99 %
Rating:208.7 MVA
Rating Type:C
MVA to Mitigate:346.41
MW Contribution:92.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936261AD2-033 C
50/50
43.18643.186
961791AG1-021 C
50/50
5.985.98
964241AG1-285 C
50/50
41.52541.525
316034AC1-036 C
50/50
0.7760.776
958212AF2-115 E
50/50
6.3676.367
3144293JTRSVLE
50/50
1.371.37
3147223TWITTYS
50/50
3.1613.161
959312AF2-222 E
50/50
37.09537.095
946302AF1-294 E
50/50
10.40910.409
925612AC1-036 E
50/50
2.8512.851
946301AF1-294 C
50/50
12.29112.291
942461AE2-259 C
50/50
33.2233.22
961792AG1-021 E
50/50
5.0945.094
936262AD2-033 E
50/50
28.7928.79
958211AF2-115 C
50/50
7.4747.474
924162AB2-060 E OP
50/50
14.17414.174
964242AG1-285 E
50/50
27.68327.683
959311AF2-222 C
50/50
55.36655.366
3147133PAMPLIN
50/50
3.3083.308
942462AE2-259 E
50/50
22.14722.147
316131AB2-060 C
50/50
4.9054.905
3138533PONTONDP
50/50
2.2152.215
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0130.013
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0390.039
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0230.023
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0240.024
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0080.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0580.058
MDUPJM->LTFIMP_MDU
CLTF
0.0020.002
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0170.017
O66PJM->LTFIMP_O-066
CMTX_NF
0.1520.152
NYPJM->LTFIMP_NY
CLTF
0.0120.012
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0470.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0130.013

Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012_SRT-A-4


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1012_SRT-A-4
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.66 %
Rating:205.86 MVA
Rating Type:B
MVA to Mitigate:209.27
MW Contribution:100.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
964241AG1-285 C
80/20
74.99774.997
316034AC1-036 C
80/20
1.4011.401
942461AE2-259 C
80/20
59.99759.997
959311AF2-222 C
80/20
99.99699.996
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0020.002
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0080.008
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0040.004
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0020.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0120.012
MDUPJM->LTFIMP_MDU
CLTF
00
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0030.003
NYPJM->LTFIMP_NY
CLTF
0.0020.002
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0090.009
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0030.003

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.89 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:992.94
MW Contribution:6.65
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151381ROSEMG2
80/20
0.6340.634
960081AF2-299 C
80/20
1.3861.386
936261AD2-033 C
80/20
5.4245.424
316248AF1-058 C
80/20
0.140.14
961791AG1-021 C
Adder
0.640.544
938771AE1-103 C
Adder
0.96705882352941170.822
963041AG1-153 C
80/20
3.0443.044
3151051BRUNSWICKS1
80/20
9.3029.302
944011AF1-069 C
80/20
7.217.21
927021AC1-189 C
80/20
4.1534.153
926071AC1-086 C
80/20
14.30114.301
946281AF1-292 C
80/20
1.1471.147
964241AG1-285 C
80/20
5.5515.551
962561AG1-105 C
80/20
4.0224.022
316034AC1-036 C
80/20
0.0950.095
316118AC1-105 C
80/20
0.4080.408
316005AA1-067 C
80/20
0.1280.128
316210AC1-098 C
80/20
0.50.5
316318V4-068 C
80/20
0.0370.037
313506AB1-173 C OP
80/20
0.7570.757
966621AG1-532 C
80/20
1.041.04
3151601KERR 3
80/20
0.5540.554
3151581KERR 1
80/20
0.1980.198
935171AD1-152 C
80/20
0.620.62
3151021BRUNSWICKG1
80/20
4.4774.477
3151041BRUNSWICKG3
80/20
4.4774.477
316365AB2-100 C1
80/20
0.7990.799
3156083AA2-088SOLA
80/20
0.4670.467
316003AC1-222 C
80/20
0.4260.426
957481AF2-042 C
80/20
26.38726.387
315614AA2-178 C
80/20
0.5670.567
3151411GASTONB
80/20
2.0712.071
316181AB2-040 GEN
80/20
0.8530.853
3147043LAWRENC
80/20
0.2030.203
940481AE2-033 C
80/20
16.46516.465
940541AE2-040 C
80/20
2.9992.999
3152441Z1-086 ST
80/20
10.00810.008
934501AD1-074 C
80/20
13.23613.236
961671AG1-007 C
80/20
0.4820.482
940491AE2-034 C
80/20
0.4170.417
316359AB2-059 C OP
80/20
0.8920.892
316283AC2-100 C
80/20
0.510.51
946301AF1-294 C
Adder
1.3164705882352941.119
934621AD1-088 C
80/20
4.424.42
942001AE2-212 C
Adder
-3.9329411764705884-3.343
932631AC2-084 C
80/20
0.5330.533
316274AC1-208 C
80/20
4.9624.962
962571AG1-106 C
80/20
1.851.85
3151311EDGECMA
80/20
8.3398.339
3152661PLYWOOD A
80/20
0.5410.541
933981AD1-022 C
80/20
3.5783.578
316174AB2-169_C
80/20
0.4490.449
3156063AA2-053SOLA
80/20
0.860.86
3151281ROARAP4
80/20
0.7750.775
316049AB1-081 C OP
80/20
0.7570.757
316238AB2-078 C O1
80/20
0.1510.151
3156011CONETOE2SOL
80/20
0.6290.629
3151611KERR 4
80/20
0.5540.554
3151621KERR 5
80/20
0.5540.554
316237AB2-079 C O1
80/20
0.1510.151
316222AC1-221 C
80/20
0.6320.632
943171AE2-346 C
80/20
0.1050.105
961941AG1-037 C
80/20
0.2370.237
3151391GASTONA
80/20
2.0712.071
934321AD1-056 C
80/20
3.7443.744
934331AD1-057 C
80/20
2.0892.089
958211AF2-115 C
Adder
0.80.68
3151531CLOVER1
80/20
6.056.05
941031AE2-094 C
80/20
22.06822.068
934611AD1-087 C
80/20
0.5960.596
3152431Z1-086 GT3
80/20
5.7485.748
940641AE2-051 C
80/20
9.0359.035
316140AB2-099 C
80/20
0.0450.045
3152921DOMTR78
80/20
0.5570.557
316319Z2-044 C
80/20
0.1130.113
3151641KERR 7
80/20
0.5540.554
313527AB2-043 C
80/20
0.2380.238
934521AD1-076 C
80/20
4.8074.807
934511AD1-075 C
80/20
3.3093.309
316212AC1-099 C
80/20
0.1680.168
316263AC1-034 C
80/20
3.5493.549
3156073AA1-063SOLA
80/20
0.7530.753
316087AB2-174 C
80/20
0.8150.815
3151591KERR 2
80/20
0.5540.554
959311AF2-222 C
80/20
6.6486.648
937481AD2-202 C
80/20
0.1730.173
3151031BRUNSWICKG2
80/20
4.4774.477
316240AF1-291 C
Adder
-1.6611764705882353-1.412
944641AF1-129 C
Adder
-92.12117647058824-78.303
3151261ROARAP2
80/20
0.8190.819
3152411Z1-086 GT1
80/20
5.755.75
3152421Z1-086 GT2
80/20
5.7485.748
3156021HOLLOMANSOL
80/20
0.830.83
316011AB1-132 C OP
80/20
1.5811.581
3151371ROSEMS1
80/20
0.8390.839
3137643SOCKMAN
80/20
0.4490.449
939411AE1-173 C
80/20
41.75841.758
3151361ROSEMG1
80/20
1.3551.355
316327AA2-057 C
80/20
0.7010.701
3151151S HAMPT1
80/20
0.570.57
316239AB2-077 C O1
80/20
0.1510.151
964791AG1-342 C
80/20
1.5971.597
316317KELFORD C
80/20
0.1760.176
957861AF2-080 C
80/20
3.7723.772
316023AB2-100 C2
80/20
0.7990.799
316129AC1-054 C
80/20
0.6480.648
3151631KERR 6
80/20
0.5540.554
316315AB2-025 C
80/20
0.4250.425
316131AB2-060 C
80/20
0.680.68
3138533PONTONDP
Adder
0.237647058823529430.202
3151541CLOVER2
80/20
5.9935.993
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.95317.953
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.57311.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1342.134
LAGNLTFEXP_LAGN->PJM
CLTF
3.8673.867
SIGELTFEXP_SIGE->PJM
CLTF
0.1330.133
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.6422.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.16446.164
CPLELTFEXP_CPLE->PJM
CLTF
5.5395.539
TVALTFEXP_TVA->PJM
CLTF
3.0473.047
NYPJM->LTFIMP_NY
CLTF
0.5840.584
LGEELTFEXP_LGEE->PJM
CLTF
0.6950.695
WECLTFEXP_WEC->PJM
CLTF
0.3670.367

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:736.13
MW Contribution:7.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
933981AD1-022 C
80/20
8.3538.353
316174AB2-169_C
80/20
0.9970.997
3156063AA2-053SOLA
80/20
2.4062.406
3151281ROARAP4
80/20
2.1722.172
316049AB1-081 C OP
80/20
1.7151.715
316238AB2-078 C O1
80/20
0.1950.195
927021AC1-189 C
80/20
9.5779.577
316005AA1-067 C
80/20
0.2960.296
316210AC1-098 C
80/20
1.2971.297
316318V4-068 C
80/20
0.090.09
313506AB1-173 C OP
80/20
2.3432.343
966621AG1-532 C
80/20
3.4243.424
3151601KERR 3
80/20
0.7120.712
3151581KERR 1
80/20
0.2540.254
932631AC2-084 C
80/20
1.3811.381
316274AC1-208 C
80/20
12.83612.836
962571AG1-106 C
80/20
5.9855.985
3151311EDGECMA
80/20
19.08119.081
3152661PLYWOOD A
80/20
0.3910.391
3156011CONETOE2SOL
80/20
1.4481.448
3151611KERR 4
80/20
0.7120.712
3151621KERR 5
80/20
0.7120.712
316237AB2-079 C O1
80/20
0.1950.195
3156021HOLLOMANSOL
80/20
2.3822.382
316011AB1-132 C OP
80/20
5.1165.116
3151371ROSEMS1
80/20
2.6542.654
3137643SOCKMAN
80/20
1.3221.322
316140AB2-099 C
80/20
0.1220.122
3152921DOMTR78
80/20
1.2081.208
316319Z2-044 C
80/20
0.2660.266
3151641KERR 7
80/20
0.7120.712
313527AB2-043 C
80/20
0.3120.312
934521AD1-076 C
80/20
10.18310.183
934511AD1-075 C
80/20
7.017.01
316212AC1-099 C
80/20
0.4340.434
316263AC1-034 C
80/20
8.0388.038
3156073AA1-063SOLA
80/20
1.9821.982
316087AB2-174 C
80/20
2.5762.576
3151591KERR 2
80/20
0.7120.712
959311AF2-222 C
80/20
7.5547.554
934501AD1-074 C
80/20
28.03828.038
961671AG1-007 C
80/20
1.1061.106
940491AE2-034 C
80/20
0.7340.734
316359AB2-059 C OP
80/20
2.0212.021
3156116Z1-036WIND
80/20
0.2510.251
946301AF1-294 C
80/20
1.31.3
3151261ROARAP2
80/20
2.2952.295
315614AA2-178 C
80/20
0.9970.997
3151411GASTONB
80/20
6.76.7
316181AB2-040 GEN
80/20
2.6392.639
3147043LAWRENC
80/20
0.5880.588
3151361ROSEMG1
80/20
4.2844.284
316327AA2-057 C
80/20
1.711.71
3151151S HAMPT1
80/20
1.0351.035
316239AB2-077 C O1
80/20
0.1950.195
964791AG1-342 C
80/20
1.4341.434
316365AB2-100 C1
80/20
2.8782.878
3156083AA2-088SOLA
80/20
1.0451.045
926071AC1-086 C
80/20
46.26846.268
946281AF1-292 C
80/20
3.783.78
964241AG1-285 C
80/20
7.0017.001
962561AG1-105 C
80/20
3.8843.884
316034AC1-036 C
80/20
0.110.11
316118AC1-105 C
80/20
0.3030.303
3144293JTRSVLE
80/20
0.1450.145
316317KELFORD C
80/20
0.4780.478
957861AF2-080 C
80/20
8.6988.698
316023AB2-100 C2
80/20
2.8782.878
316129AC1-054 C
80/20
1.321.32
3151631KERR 6
80/20
0.7120.712
316131AB2-060 C
80/20
0.8840.884
3138533PONTONDP
80/20
0.2340.234
3151381ROSEMG2
80/20
2.0062.006
960081AF2-299 C
80/20
4.5664.566
936261AD2-033 C
80/20
6.4546.454
961791AG1-021 C
80/20
0.6320.632
938771AE1-103 C
80/20
1.2731.273
943171AE2-346 C
80/20
0.2840.284
961941AG1-037 C
80/20
0.6420.642
3151391GASTONA
80/20
6.76.7
934321AD1-056 C
80/20
10.25810.258
934331AD1-057 C
80/20
5.7225.722
958211AF2-115 C
80/20
0.790.79
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.04115.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.5619.561
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.7731.773
LAGNLTFEXP_LAGN->PJM
CLTF
3.1853.185
SIGELTFEXP_SIGE->PJM
CLTF
0.1110.111
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5172.517
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.76439.764
CPLELTFEXP_CPLE->PJM
CLTF
5.2785.278
TVALTFEXP_TVA->PJM
CLTF
2.5052.505
NYPJM->LTFIMP_NY
CLTF
0.4240.424
LGEELTFEXP_LGEE->PJM
CLTF
0.5780.578
WECLTFEXP_WEC->PJM
CLTF
0.3070.307

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.8 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:711.27
MW Contribution:6.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
933981AD1-022 C
80/20
5.6735.673
316174AB2-169_C
80/20
0.7390.739
3156063AA2-053SOLA
80/20
2.0962.096
3151281ROARAP4
80/20
1.9471.947
316049AB1-081 C OP
80/20
1.5831.583
316238AB2-078 C O1
80/20
0.1730.173
316005AA1-067 C
80/20
0.2330.233
316210AC1-098 C
80/20
1.1041.104
316318V4-068 C
80/20
0.0730.073
313506AB1-173 C OP
80/20
2.1692.169
966621AG1-532 C
80/20
3.233.23
3151601KERR 3
80/20
0.6330.633
3151581KERR 1
80/20
0.2260.226
936161AD2-022 C
80/20
3.4423.442
932631AC2-084 C
80/20
1.1761.176
316274AC1-208 C
80/20
11.28911.289
962571AG1-106 C
80/20
5.4715.471
3151311EDGECMA
80/20
17.61917.619
3156011CONETOE2SOL
80/20
1.2441.244
3151611KERR 4
80/20
0.6330.633
3151621KERR 5
80/20
0.6330.633
316237AB2-079 C O1
80/20
0.1730.173
3156021HOLLOMANSOL
80/20
1.581.58
316011AB1-132 C OP
80/20
4.6784.678
3151371ROSEMS1
80/20
2.4282.428
3137643SOCKMAN
80/20
1.2051.205
316140AB2-099 C
80/20
0.0910.091
3152921DOMTR78
80/20
0.8630.863
316319Z2-044 C
80/20
0.2410.241
3151641KERR 7
80/20
0.6330.633
313527AB2-043 C
80/20
0.2770.277
934521AD1-076 C
80/20
7.0037.003
934511AD1-075 C
80/20
4.8214.821
316212AC1-099 C
80/20
0.370.37
316263AC1-034 C
80/20
7.4217.421
3156073AA1-063SOLA
80/20
1.7541.754
316087AB2-174 C
80/20
2.42.4
3151591KERR 2
80/20
0.6330.633
959311AF2-222 C
80/20
6.4496.449
934501AD1-074 C
80/20
19.28319.283
961671AG1-007 C
80/20
0.970.97
940491AE2-034 C
80/20
0.5050.505
316359AB2-059 C OP
80/20
1.8661.866
3151261ROARAP2
80/20
2.0572.057
315614AA2-178 C
80/20
0.6860.686
3151411GASTONB
80/20
6.1266.126
316181AB2-040 GEN
80/20
2.4442.444
3147043LAWRENC
80/20
0.5520.552
3151361ROSEMG1
80/20
3.923.92
316327AA2-057 C
80/20
1.5281.528
3151151S HAMPT1
80/20
0.9030.903
316239AB2-077 C O1
80/20
0.1730.173
964791AG1-342 C
80/20
1.2551.255
316365AB2-100 C1
80/20
2.7382.738
3156083AA2-088SOLA
80/20
0.8980.898
927021AC1-189 C
80/20
8.0138.013
926071AC1-086 C
80/20
42.342.3
946281AF1-292 C
80/20
3.5653.565
964241AG1-285 C
80/20
6.1446.144
962561AG1-105 C
80/20
3.4083.408
316034AC1-036 C
80/20
0.0940.094
316317KELFORD C
80/20
0.3680.368
957861AF2-080 C
80/20
7.2787.278
316023AB2-100 C2
80/20
2.7382.738
316129AC1-054 C
80/20
1.1791.179
3151631KERR 6
80/20
0.6330.633
316131AB2-060 C
80/20
0.7820.782
3151381ROSEMG2
80/20
1.8351.835
960081AF2-299 C
80/20
4.3064.306
936171AD2-023 C
80/20
2.0082.008
936261AD2-033 C
80/20
5.5815.581
938771AE1-103 C
80/20
1.1451.145
943171AE2-346 C
80/20
0.2110.211
961941AG1-037 C
80/20
0.4770.477
3151391GASTONA
80/20
6.1266.126
934321AD1-056 C
80/20
9.4289.428
934331AD1-057 C
80/20
5.2595.259
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.22922.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.65213.652
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.5732.573
LAGNLTFEXP_LAGN->PJM
CLTF
4.5044.504
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1753.175
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.41853.418
CPLELTFEXP_CPLE->PJM
CLTF
6.6566.656
TVALTFEXP_TVA->PJM
CLTF
3.5423.542
NYPJM->LTFIMP_NY
CLTF
0.4770.477
LGEELTFEXP_LGEE->PJM
CLTF
0.8450.845
WECLTFEXP_WEC->PJM
CLTF
0.4510.451

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.72 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:697.11
MW Contribution:7.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
933981AD1-022 C
80/20
5.7955.795
316174AB2-169_C
80/20
0.7240.724
3156063AA2-053SOLA
80/20
2.1042.104
3151281ROARAP4
80/20
1.9541.954
316049AB1-081 C OP
80/20
1.4681.468
316238AB2-078 C O1
80/20
0.1810.181
316005AA1-067 C
80/20
0.220.22
316210AC1-098 C
80/20
1.0791.079
316318V4-068 C
80/20
0.0740.074
313506AB1-173 C OP
80/20
2.1872.187
966621AG1-532 C
80/20
3.2633.263
3151601KERR 3
80/20
0.6440.644
3151581KERR 1
80/20
0.230.23
932631AC2-084 C
80/20
1.1481.148
316274AC1-208 C
80/20
11.02211.022
962571AG1-106 C
80/20
5.4785.478
3151311EDGECMA
80/20
16.35316.353
3156011CONETOE2SOL
80/20
1.1621.162
3151611KERR 4
80/20
0.6440.644
3151621KERR 5
80/20
0.6440.644
316237AB2-079 C O1
80/20
0.1810.181
3156021HOLLOMANSOL
80/20
1.5911.591
316011AB1-132 C OP
80/20
4.6834.683
3151371ROSEMS1
80/20
2.422.42
3137643SOCKMAN
80/20
1.2121.212
316140AB2-099 C
80/20
0.0910.091
3152921DOMTR78
80/20
0.8660.866
316319Z2-044 C
80/20
0.2270.227
3151641KERR 7
80/20
0.6440.644
313527AB2-043 C
80/20
0.290.29
934521AD1-076 C
80/20
7.217.21
934511AD1-075 C
80/20
4.9634.963
316212AC1-099 C
80/20
0.3610.361
316263AC1-034 C
80/20
6.8836.883
3156073AA1-063SOLA
80/20
1.7721.772
316087AB2-174 C
80/20
2.4212.421
3151591KERR 2
80/20
0.6440.644
959311AF2-222 C
80/20
7.0127.012
934501AD1-074 C
80/20
19.85319.853
961671AG1-007 C
80/20
0.9040.904
940491AE2-034 C
80/20
0.5370.537
316359AB2-059 C OP
80/20
1.731.73
3156116Z1-036WIND
80/20
0.2010.201
946301AF1-294 C
80/20
1.2081.208
3151261ROARAP2
80/20
2.0652.065
315614AA2-178 C
80/20
0.7290.729
3151411GASTONB
80/20
6.1336.133
316181AB2-040 GEN
80/20
2.4632.463
3147043LAWRENC
80/20
0.5590.559
940481AE2-033 C
80/20
63.69463.694
940541AE2-040 C
80/20
11.74711.747
3151361ROSEMG1
80/20
3.9083.908
316327AA2-057 C
80/20
1.461.46
3151151S HAMPT1
80/20
0.9570.957
316239AB2-077 C O1
80/20
0.1810.181
964791AG1-342 C
80/20
1.3141.314
316365AB2-100 C1
80/20
2.7652.765
3156083AA2-088SOLA
80/20
0.9250.925
927021AC1-189 C
80/20
7.5047.504
926071AC1-086 C
80/20
42.34842.348
946281AF1-292 C
80/20
3.6023.602
964241AG1-285 C
80/20
6.4946.494
962561AG1-105 C
80/20
3.5683.568
316034AC1-036 C
80/20
0.1020.102
3144293JTRSVLE
80/20
0.1350.135
316317KELFORD C
80/20
0.3660.366
957861AF2-080 C
80/20
6.8156.815
316023AB2-100 C2
80/20
2.7652.765
316129AC1-054 C
80/20
1.1891.189
3151631KERR 6
80/20
0.6440.644
316315AB2-025 C
80/20
1.6631.663
316131AB2-060 C
80/20
0.820.82
3138533PONTONDP
80/20
0.2180.218
3151381ROSEMG2
80/20
1.831.83
960081AF2-299 C
80/20
4.3514.351
936261AD2-033 C
80/20
5.9895.989
961791AG1-021 C
80/20
0.5880.588
938771AE1-103 C
80/20
1.2791.279
943171AE2-346 C
80/20
0.2130.213
961941AG1-037 C
80/20
0.480.48
3151391GASTONA
80/20
6.1336.133
934321AD1-056 C
80/20
9.1359.135
934331AD1-057 C
80/20
5.0965.096
958211AF2-115 C
80/20
0.7340.734
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.06512.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.7657.765
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4321.432
LAGNLTFEXP_LAGN->PJM
CLTF
2.5962.596
SIGELTFEXP_SIGE->PJM
CLTF
0.0890.089
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.0622.062
CBM South 2LTFEXP_CBM-S2->PJM
CBM
32.61632.616
CPLELTFEXP_CPLE->PJM
CLTF
4.3234.323
TVALTFEXP_TVA->PJM
CLTF
2.0422.042
NYPJM->LTFIMP_NY
CLTF
0.370.37
LGEELTFEXP_LGEE->PJM
CLTF
0.4650.465
WECLTFEXP_WEC->PJM
CLTF
0.2460.246

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.8 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3342.68
MW Contribution:18.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151381ROSEMG2
80/20
1.271.27
960081AF2-299 C
80/20
2.4842.484
936171AD2-023 C
Adder
5.5152941176470584.688
936261AD2-033 C
Adder
14.72470588235294112.516
961791AG1-021 C
Adder
1.82588235294117651.552
938771AE1-103 C
80/20
3.8693.869
963041AG1-153 C
80/20
9.1419.141
3151051BRUNSWICKS1
80/20
27.93627.936
944011AF1-069 C
80/20
21.71321.713
944591AF1-124 C
80/20
62.17762.177
944601AF1-125 C
80/20
61.00261.002
3151101ELIZAR3
80/20
4.3114.311
941591AE2-156 C
80/20
23.83823.838
927021AC1-189 C
Adder
11.1952941176470599.516
926071AC1-086 C
80/20
28.07728.077
946281AF1-292 C
80/20
2.0562.056
964241AG1-285 C
Adder
14.80352941176470712.583
962561AG1-105 C
Adder
11.0694117647058839.409
3151091ELIZAR2
80/20
4.1834.183
316349AD2-085 C
80/20
4.3374.337
316210AC1-098 C
80/20
1.251.25
316318V4-068 C
80/20
0.1070.107
313506AB1-173 C OP
80/20
1.4941.494
966621AG1-532 C
80/20
1.8631.863
316320Y1-086 C
80/20
0.2940.294
316388AE2-253 GEN
80/20
2.6322.632
936161AD2-022 C
Adder
9.455294117647068.037
935171AD1-152 C
80/20
1.8271.827
3151021BRUNSWICKG1
80/20
13.44613.446
3151041BRUNSWICKG3
80/20
13.44613.446
942341AE2-247 C
80/20
1.881.88
316246AF1-032 C
80/20
0.3780.378
316365AB2-100 C1
80/20
1.2911.291
3156083AA2-088SOLA
80/20
1.4051.405
957481AF2-042 C
80/20
78.71578.715
940431AE2-027 C
Adder
11.395294117647069.686
316294AC1-161 C
80/20
6.8246.824
944581AF1-123 C
80/20
61.95761.957
316185AD1-033 C
80/20
1.6481.648
916191Z1-068 C
80/20
0.0580.058
941101AE2-104 C
80/20
4.4074.407
315614AA2-178 C
80/20
2.0912.091
3151411GASTONB
80/20
4.0664.066
316181AB2-040 GEN
80/20
1.6831.683
3147043LAWRENC
80/20
0.3980.398
940481AE2-033 C
80/20
22.18122.181
940541AE2-040 C
80/20
3.9443.944
3152441Z1-086 ST
80/20
30.08130.081
961611AG1-000B C
Adder
17.0670588235294114.507
316375AC2-012 C
80/20
1.7911.791
316072AD1-144 C
80/20
0.3590.359
934501AD1-074 C
80/20
45.0845.08
961671AG1-007 C
Adder
1.2482352941176471.061
940491AE2-034 C
80/20
1.5381.538
3156116Z1-036WIND
80/20
0.8770.877
946301AF1-294 C
Adder
3.75411764705882333.191
934621AD1-088 C
80/20
13.20613.206
942001AE2-212 C
Adder
2.11411764705882371.797
932631AC2-084 C
80/20
1.3311.331
316274AC1-208 C
80/20
11.98411.984
962571AG1-106 C
80/20
3.6323.632
3151311EDGECMA
Adder
20.58941176470588317.501
957871AF2-081 C
80/20
13.4313.43
933981AD1-022 C
80/20
11.71411.714
316174AB2-169_C
80/20
1.3931.393
3156063AA2-053SOLA
80/20
1.9981.998
3151281ROARAP4
80/20
1.7351.735
938531AE1-072 C
80/20
23.60823.608
935161AD1-151 C
Adder
15.27058823529411812.98
958161AF2-110 C
80/20
1.7981.798
313526AB2-022 C
80/20
0.5040.504
316017AA1-139 ULT1
80/20
1.4491.449
934611AD1-087 C
80/20
1.7671.767
3152431Z1-086 GT3
80/20
17.27717.277
940641AE2-051 C
80/20
28.76428.764
3152331SURRY 2
80/20
30.82730.827
943171AE2-346 C
80/20
0.2980.298
961941AG1-037 C
80/20
0.6730.673
3151391GASTONA
80/20
4.0664.066
934321AD1-056 C
Adder
8.332941176470597.083
934331AD1-057 C
Adder
4.6482352941176473.951
958211AF2-115 C
Adder
2.28235294117647051.94
3151531CLOVER1
80/20
17.9517.95
941031AE2-094 C
80/20
66.45566.455
3151081ELIZAR1
80/20
4.2584.258
316140AB2-099 C
80/20
0.1280.128
3152921DOMTR78
80/20
1.8181.818
316018AA1-139 ULT2
80/20
1.4491.449
933291AC2-141 C
80/20
41.90441.904
3150921YORKTN3
Adder
127.84235294117647108.666
934521AD1-076 C
80/20
16.37216.372
934511AD1-075 C
80/20
11.2711.27
316212AC1-099 C
80/20
0.4180.418
316263AC1-034 C
Adder
8.8035294117647057.483
3156073AA1-063SOLA
80/20
1.8611.861
316087AB2-174 C
80/20
1.561.56
316321Z2-027 C
80/20
0.4860.486
959311AF2-222 C
Adder
18.28823529411764815.545
937481AD2-202 C
80/20
0.5130.513
3151031BRUNSWICKG2
80/20
13.44613.446
316036AC1-147 C
80/20
0.4890.489
316305AF2-043 C
80/20
0.4630.463
3156021HOLLOMANSOL
80/20
2.4482.448
316011AB1-132 C OP
80/20
3.1053.105
3151371ROSEMS1
80/20
1.681.68
3151261ROARAP2
80/20
1.8341.834
3156056W1-029WIND
80/20
1.0361.036
3152411Z1-086 GT1
80/20
17.28117.281
3152421Z1-086 GT2
80/20
17.27717.277
943461AF1-017 C
80/20
1.7011.701
316311AC2-079 C
80/20
7.2667.266
3137643SOCKMAN
80/20
0.9470.947
939411AE1-173 C
80/20
144.1144.1
3150991CHESPKB
80/20
0.9580.958
3151361ROSEMG1
80/20
2.7122.712
3151151S HAMPT1
80/20
1.9741.974
964791AG1-342 C
Adder
4.4317647058823533.767
939191AE1-149 C
Adder
11.99058823529411710.192
3150981CHESPKA
80/20
0.5780.578
316317KELFORD C
80/20
0.4760.476
957861AF2-080 C
Adder
10.167058823529418.642
316023AB2-100 C2
80/20
1.2911.291
316129AC1-054 C
80/20
1.5891.589
316315AB2-025 C
80/20
0.5580.558
3138533PONTONDP
Adder
0.6764705882352940.575
3151541CLOVER2
80/20
17.78217.782
316316AC1-027 C
80/20
0.4210.421
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.0655.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.38335.383
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.566.56
LAGNLTFEXP_LAGN->PJM
CLTF
11.74411.744
SIGELTFEXP_SIGE->PJM
CLTF
0.4150.415
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.597.59
CBM South 2LTFEXP_CBM-S2->PJM
CBM
135.46135.46
CPLELTFEXP_CPLE->PJM
CLTF
15.91315.913
TVALTFEXP_TVA->PJM
CLTF
9.319.31
NYPJM->LTFIMP_NY
CLTF
2.5592.559
LGEELTFEXP_LGEE->PJM
CLTF
2.182.18
WECLTFEXP_WEC->PJM
CLTF
1.1331.133

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.82 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3858.59
MW Contribution:22.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960081AF2-299 C
Adder
2.74941176470588242.337
936261AD2-033 C
Adder
17.81058823529411615.139
961791AG1-021 C
Adder
2.40470588235294122.044
938771AE1-103 C
80/20
4.3814.381
963041AG1-153 C
80/20
8.7798.779
3151051BRUNSWICKS1
80/20
26.8326.83
944011AF1-069 C
80/20
20.63520.635
3150601CHESTF5
Adder
83.0647058823529570.605
944591AF1-124 C
80/20
69.22169.221
944601AF1-125 C
80/20
67.91467.914
3151101ELIZAR3
80/20
4.8814.881
941591AE2-156 C
80/20
27.03327.033
927021AC1-189 C
Adder
12.14117647058823710.32
926071AC1-086 C
Adder
30.83882352941176626.213
946281AF1-292 C
Adder
2.2752941176470591.934
964241AG1-285 C
Adder
17.31176470588235414.715
962561AG1-105 C
Adder
12.25882352941176610.42
316169AC1-164 GEN
Adder
49.0282352941176541.674
3151091ELIZAR2
80/20
4.7354.735
316349AD2-085 C
80/20
5.1625.162
966621AG1-532 C
Adder
2.06235294117647071.753
316320Y1-086 C
80/20
0.330.33
316388AE2-253 GEN
80/20
2.9552.955
3151021BRUNSWICKG1
80/20
12.91412.914
3151041BRUNSWICKG3
80/20
12.91412.914
942341AE2-247 C
80/20
2.2382.238
316246AF1-032 C
80/20
0.4280.428
316365AB2-100 C1
80/20
1.4231.423
957481AF2-042 C
80/20
80.37380.373
940431AE2-027 C
Adder
18.39647058823529615.637
316294AC1-161 C
80/20
7.5057.505
944581AF1-123 C
80/20
68.97668.976
316185AD1-033 C
80/20
1.8511.851
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
5.0455.045
940481AE2-033 C
80/20
24.49624.496
940541AE2-040 C
80/20
4.3564.356
3152441Z1-086 ST
80/20
28.79528.795
961611AG1-000B C
Adder
22.90588235294117719.47
316375AC2-012 C
80/20
2.0322.032
316072AD1-144 C
80/20
0.4180.418
934501AD1-074 C
Adder
50.0317647058823542.527
961671AG1-007 C
Adder
1.34941176470588231.147
3156116Z1-036WIND
80/20
0.9810.981
946301AF1-294 C
Adder
4.9423529411764714.201
942461AE2-259 C
Adder
12.99058823529411711.042
934621AD1-088 C
80/20
14.01914.019
942001AE2-212 C
80/20
3.1513.151
316274AC1-208 C
Adder
13.08588235294117711.123
962571AG1-106 C
Adder
3.98941176470588273.391
3151311EDGECMA
Adder
22.1658823529411818.841
957871AF2-081 C
80/20
15.07515.075
316405AF2-144 C
80/20
0.4360.436
3150651CHESTF6
Adder
26.27176470588235422.331
3150861SPRUNCD
80/20
0.2360.236
933981AD1-022 C
Adder
12.98823529411764711.04
938531AE1-072 C
80/20
26.49826.498
3150731STONECA
Adder
9.5788235294117648.142
935161AD1-151 C
Adder
22.80117647058823519.381
316083AB2-161 C
80/20
0.8230.823
958161AF2-110 C
80/20
2.0582.058
961941AG1-037 C
Adder
0.74470588235294120.633
934321AD1-056 C
Adder
9.0458823529411777.689
934331AD1-057 C
Adder
5.04588235294117654.289
958211AF2-115 C
Adder
3.0058823529411772.555
3151531CLOVER1
80/20
18.57418.574
316258AE1-075 C
80/20
0.5130.513
941031AE2-094 C
80/20
63.15563.155
3150831SPRUNCA
80/20
13.15813.158
3150841SPRUNCB
80/20
13.15813.158
3151081ELIZAR1
80/20
4.824.82
313526AB2-022 C
80/20
0.5650.565
316017AA1-139 ULT1
80/20
1.6261.626
3152431Z1-086 GT3
80/20
16.53816.538
316336AC2-165 C
Adder
14.04941176470588411.942
940641AE2-051 C
80/20
27.74527.745
943471AF1-018 C
Adder
8.4917647058823537.218
3152331SURRY 2
80/20
35.95635.956
3151201GRAVEL4
80/20
3.6573.657
3151211GRAVEL5
80/20
3.6113.611
3151221GRAVEL6
80/20
3.6533.653
316236AE1-162 C
80/20
0.5140.514
316018AA1-139 ULT2
80/20
1.6261.626
3150851SPRUNCC
80/20
0.2360.236
944631AF1-128 C
Adder
51.9752941176470644.179
933291AC2-141 C
80/20
46.08646.086
3150921YORKTN3
Adder
165.5670588235294140.732
3151191GRAVEL3
80/20
3.6113.611
934521AD1-076 C
Adder
18.1705882352941215.445
934511AD1-075 C
Adder
12.50823529411764710.632
316263AC1-034 C
Adder
9.488.058
316321Z2-027 C
80/20
0.5460.546
959311AF2-222 C
Adder
22.66470588235294419.265
3151031BRUNSWICKG2
80/20
12.91412.914
316240AF1-291 C
Adder
3.0682352941176472.608
944641AF1-129 C
Adder
144.29529411764705122.651
316036AC1-147 C
80/20
0.5540.554
316305AF2-043 C
80/20
0.5240.524
3137643SOCKMAN
Adder
1.04352941176470580.887
939411AE1-173 C
80/20
143.49143.49
316381AD1-082 C
80/20
1.8751.875
3151161SURRY 1
80/20
35.54335.543
3150991CHESPKB
80/20
1.0871.087
3156056W1-029WIND
80/20
1.1641.164
3152411Z1-086 GT1
80/20
16.54216.542
3152421Z1-086 GT2
80/20
16.53816.538
316233AE1-074 C
80/20
3.9163.916
940551AE2-041 C
Adder
8.4917647058823537.218
943461AF1-017 C
80/20
2.0242.024
316311AC2-079 C
80/20
8.6058.605
964791AG1-342 C
Adder
4.884.148
316313AB2-026 C
80/20
0.5590.559
939191AE1-149 C
80/20
15.94215.942
957601AF2-054 C
Adder
2.53058823529411742.151
3150981CHESPKA
80/20
0.6560.656
957861AF2-080 C
Adder
11.0270588235294129.373
316023AB2-100 C2
80/20
1.4231.423
316315AB2-025 C
80/20
0.6170.617
3138533PONTONDP
Adder
0.89058823529411770.757
3151541CLOVER2
80/20
18.418.4
316316AC1-027 C
80/20
0.4760.476
316303AF2-085
80/20
6.4786.478
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.12565.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.22440.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6237.623
LAGNLTFEXP_LAGN->PJM
CLTF
13.13513.135
SIGELTFEXP_SIGE->PJM
CLTF
0.4870.487
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.9747.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
144.491144.491
CPLELTFEXP_CPLE->PJM
CLTF
16.71416.714
TVALTFEXP_TVA->PJM
CLTF
10.46710.467
NYPJM->LTFIMP_NY
CLTF
3.1863.186
LGEELTFEXP_LGEE->PJM
CLTF
2.5932.593
WECLTFEXP_WEC->PJM
CLTF
1.3381.338

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.38 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3586.78
MW Contribution:13.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
933981AD1-022 C
Adder
6.3599999999999995.406
938531AE1-072 C
Adder
12.33529411764705810.485
316238AB2-078 C O1
80/20
0.2590.259
958161AF2-110 C
Adder
0.96117647058823530.817
961941AG1-037 C
Adder
0.37294117647058830.317
934321AD1-056 C
Adder
4.7070588235294134.001
934331AD1-057 C
Adder
2.6258823529411772.232
958211AF2-115 C
80/20
1.7961.796
3151531CLOVER1
80/20
10.82910.829
208900BRIS G1
80/20
-2.405-2.405
3151761LOISA E
80/20
6.8276.827
3151771S ANNAG1
80/20
3.2623.262
3151791S ANNAG2
80/20
3.2623.262
3151781S ANNAS1
80/20
1.6761.676
927021AC1-189 C
Adder
6.225.287
926071AC1-086 C
Adder
15.98823529411764713.59
946281AF1-292 C
80/20
1.2041.204
964241AG1-285 C
80/20
9.9749.974
962561AG1-105 C
Adder
6.9729411764705885.927
316034AC1-036 C
80/20
0.1860.186
3144293JTRSVLE
80/20
0.3290.329
316044AC1-158 C1
80/20
18.51718.517
316349AD2-085 C
Adder
2.3964705882352942.037
966621AG1-532 C
80/20
1.0911.091
935171AD1-152 C
80/20
1.0991.099
3151021BRUNSWICKG1
80/20
7.5567.556
3151041BRUNSWICKG3
80/20
7.5567.556
934861AD1-115 C
80/20
3.3063.306
3152261N ANNA2
80/20
103.964103.964
942341AE2-247 C
Adder
1.03882352941176470.883
316274AC1-208 C
Adder
6.785.763
962571AG1-106 C
Adder
2.0682352941176471.758
957871AF2-081 C
Adder
7.0094117647058835.958
316405AF2-144 C
80/20
0.2720.272
316237AB2-079 C O1
80/20
0.2590.259
934611AD1-087 C
80/20
1.0661.066
3152431Z1-086 GT3
80/20
9.699.69
316336AC2-165 C
80/20
8.8748.874
940641AE2-051 C
80/20
15.75815.758
3137643SOCKMAN
Adder
0.54588235294117650.464
3151741LOISA C
80/20
3.3493.349
3151721LOISA A
80/20
3.3313.331
939411AE1-173 C
80/20
78.11378.113
313527AB2-043 C
80/20
0.4090.409
3152251N ANNA1
80/20
103.92103.92
933291AC2-141 C
Adder
21.0423529411764717.886
934521AD1-076 C
Adder
8.8564705882352937.528
934511AD1-075 C
Adder
6.0964705882352945.182
316087AB2-174 C
80/20
0.9080.908
959311AF2-222 C
80/20
13.30313.303
937481AD2-202 C
80/20
0.3090.309
3151031BRUNSWICKG2
80/20
7.5567.556
934501AD1-074 C
Adder
24.38588235294117720.728
961671AG1-007 C
Adder
0.69647058823529410.592
946301AF1-294 C
80/20
2.9542.954
942461AE2-259 C
80/20
7.9867.986
934621AD1-088 C
80/20
8.2538.253
208901BRIS G2
80/20
-2.846-2.846
316192AB2-158 C
80/20
4.3254.325
942001AE2-212 C
Adder
1.40235294117647061.192
3152411Z1-086 GT1
80/20
9.6939.693
3152421Z1-086 GT2
80/20
9.699.69
316233AE1-074 C
80/20
2.0672.067
943461AF1-017 C
Adder
0.94000000000000010.799
316311AC2-079 C
Adder
3.99647058823529383.397
3147043LAWRENC
80/20
0.240.24
940481AE2-033 C
80/20
12.91312.913
940541AE2-040 C
80/20
2.2982.298
3152441Z1-086 ST
80/20
16.87216.872
966001AG1-469 C
80/20
2.3822.382
316239AB2-077 C O1
80/20
0.2590.259
964791AG1-342 C
Adder
2.77294117647058872.357
3151731LOISA B
80/20
3.3493.349
3151751LOISA D
80/20
3.3493.349
316313AB2-026 C
80/20
0.3480.348
316164AC1-076_C
80/20
1.0891.089
939191AE1-149 C
Adder
7.2929411764705886.199
316365AB2-100 C1
80/20
0.7450.745
957481AF2-042 C
80/20
47.06247.062
3151801S ANNAS2
80/20
1.6761.676
944581AF1-123 C
Adder
32.0470588235294127.24
941101AE2-104 C
Adder
2.35411764705882342.001
957861AF2-080 C
Adder
5.6494117647058824.802
316023AB2-100 C2
80/20
0.7450.745
316315AB2-025 C
80/20
0.3250.325
316131AB2-060 C
80/20
1.1781.178
3138533PONTONDP
80/20
0.5320.532
3151541CLOVER2
80/20
10.72710.727
316257AC1-043 C
80/20
6.6126.612
316254AC1-120 C
80/20
8.5918.591
960081AF2-299 C
80/20
1.4551.455
936261AD2-033 C
80/20
10.37510.375
961791AG1-021 C
80/20
1.4371.437
938771AE1-103 C
Adder
2.10235294117647081.787
963041AG1-153 C
80/20
5.1375.137
3151051BRUNSWICKS1
80/20
15.69915.699
316170AC1-121 C
80/20
2.952.95
944011AF1-069 C
80/20
12.12612.126
316045AC1-158 C2
80/20
18.51718.517
944591AF1-124 C
Adder
32.1611764705882427.337
944601AF1-125 C
Adder
31.55411764705882826.821
941591AE2-156 C
Adder
12.43294117647058910.568
316258AE1-075 C
80/20
0.320.32
941031AE2-094 C
80/20
37.11337.113
316303AF2-085
80/20
3.8763.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.20919.209
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.12316.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.6672.667
LAGNLTFEXP_LAGN->PJM
CLTF
5.7055.705
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2194.219
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.82173.821
CPLELTFEXP_CPLE->PJM
CLTF
8.8538.853
TVALTFEXP_TVA->PJM
CLTF
4.5224.522
NYPJM->LTFIMP_NY
CLTF
2.292.29
LGEELTFEXP_LGEE->PJM
CLTF
0.8350.835
WECLTFEXP_WEC->PJM
CLTF
0.4130.413

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.09 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3577.61
MW Contribution:13.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960081AF2-299 C
80/20
1.5351.535
936261AD2-033 C
80/20
10.85610.856
961791AG1-021 C
80/20
1.51.5
938771AE1-103 C
Adder
2.2329411764705881.898
963041AG1-153 C
80/20
5.3875.387
3151051BRUNSWICKS1
80/20
16.46316.463
944011AF1-069 C
80/20
12.71412.714
944591AF1-124 C
Adder
34.2229.087
944601AF1-125 C
Adder
33.5741176470588328.538
941591AE2-156 C
Adder
13.23882352941176611.253
927021AC1-189 C
Adder
6.5788235294117645.592
926071AC1-086 C
Adder
16.8929411764705914.359
946281AF1-292 C
80/20
1.2711.271
964241AG1-285 C
80/20
10.44910.449
962561AG1-105 C
Adder
7.3152941176470596.218
316034AC1-036 C
80/20
0.1950.195
3144293JTRSVLE
80/20
0.3440.344
316349AD2-085 C
Adder
2.5505882352941182.168
313506AB1-173 C OP
80/20
0.9150.915
966621AG1-532 C
80/20
1.1511.151
935171AD1-152 C
80/20
1.1531.153
3151021BRUNSWICKG1
80/20
7.9247.924
3151041BRUNSWICKG3
80/20
7.9247.924
3152261N ANNA2
80/20
106.999106.999
942341AE2-247 C
Adder
1.10588235294117650.94
316365AB2-100 C1
80/20
0.7870.787
957481AF2-042 C
80/20
49.31549.315
3151801S ANNAS2
80/20
1.5631.563
940431AE2-027 C
Adder
8.3129411764705887.066
944581AF1-123 C
Adder
34.0988235294117728.984
941101AE2-104 C
Adder
2.50470588235294132.129
316181AB2-040 GEN
80/20
1.0311.031
3147043LAWRENC
80/20
0.2530.253
940481AE2-033 C
80/20
13.63113.631
940541AE2-040 C
80/20
2.4262.426
3152441Z1-086 ST
80/20
17.69217.692
966001AG1-469 C
80/20
1.9821.982
961611AG1-000B C
Adder
10.3129411764705888.766
934501AD1-074 C
Adder
25.86823529411764621.988
961671AG1-007 C
Adder
0.73647058823529410.626
946301AF1-294 C
80/20
3.0833.083
942461AE2-259 C
Adder
8.3117647058823547.065
934621AD1-088 C
80/20
8.6418.641
208901BRIS G2
80/20
-2.857-2.857
316192AB2-158 C
80/20
4.2764.276
942001AE2-212 C
Adder
1.49882352941176471.274
316274AC1-208 C
Adder
7.1635294117647066.089
962571AG1-106 C
Adder
2.1847058823529411.857
3151311EDGECMA
Adder
12.21411764705882410.382
957871AF2-081 C
Adder
7.4588235294117656.34
316405AF2-144 C
80/20
0.2830.283
3150651CHESTF6
Adder
11.5976470588235319.858
933981AD1-022 C
Adder
6.7447058823529415.733
938531AE1-072 C
Adder
13.12352941176470511.155
316238AB2-078 C O1
80/20
0.2720.272
958161AF2-110 C
Adder
1.02235294117647070.869
961941AG1-037 C
Adder
0.39411764705882360.335
934321AD1-056 C
Adder
4.9729411764705894.227
934331AD1-057 C
Adder
2.7741176470588242.358
958211AF2-115 C
80/20
1.8751.875
316237AB2-079 C O1
80/20
0.2720.272
934611AD1-087 C
80/20
1.1171.117
3152431Z1-086 GT3
80/20
10.16110.161
316336AC2-165 C
80/20
9.2269.226
940641AE2-051 C
80/20
16.55416.554
3151531CLOVER1
80/20
11.34911.349
208900BRIS G1
80/20
-2.414-2.414
3151761LOISA E
80/20
6.316.31
3151771S ANNAG1
80/20
3.0413.041
3151791S ANNAG2
80/20
3.0413.041
3151781S ANNAS1
80/20
1.5631.563
316258AE1-075 C
80/20
0.3330.333
941031AE2-094 C
80/20
38.91138.911
3150831SPRUNCA
Adder
6.1623529411764715.238
3150841SPRUNCB
Adder
6.1623529411764715.238
313527AB2-043 C
80/20
0.4290.429
3152251N ANNA1
80/20
106.954106.954
933291AC2-141 C
Adder
22.41294117647058619.051
934521AD1-076 C
Adder
9.3952941176470587.986
934511AD1-075 C
Adder
6.46705882352941155.497
316263AC1-034 C
Adder
5.2270588235294114.443
316087AB2-174 C
80/20
0.9580.958
959311AF2-222 C
80/20
13.90913.909
937481AD2-202 C
80/20
0.3240.324
3151031BRUNSWICKG2
80/20
7.9247.924
316240AF1-291 C
Adder
1.37882352941176461.172
944641AF1-129 C
Adder
63.6988235294117654.144
3137643SOCKMAN
Adder
0.57647058823529410.49
3151741LOISA C
80/20
3.0953.095
3151721LOISA A
80/20
3.0793.079
939411AE1-173 C
80/20
82.26382.263
3152411Z1-086 GT1
80/20
10.16410.164
3152421Z1-086 GT2
80/20
10.16110.161
316233AE1-074 C
80/20
2.1822.182
943461AF1-017 C
Adder
1.00.85
316311AC2-079 C
Adder
4.2541176470588233.616
316239AB2-077 C O1
80/20
0.2720.272
964791AG1-342 C
Adder
2.9105882352941182.474
3151731LOISA B
80/20
3.0953.095
3151751LOISA D
80/20
3.0953.095
316313AB2-026 C
80/20
0.3630.363
939191AE1-149 C
Adder
7.7752941176470596.609
957861AF2-080 C
Adder
5.9741176470588245.078
316023AB2-100 C2
80/20
0.7870.787
316315AB2-025 C
80/20
0.3440.344
316131AB2-060 C
80/20
1.2351.235
3138533PONTONDP
80/20
0.5550.555
3151541CLOVER2
80/20
11.24311.243
316303AF2-085
80/20
4.064.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.24822.248
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.65817.658
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.9882.988
LAGNLTFEXP_LAGN->PJM
CLTF
6.1746.174
SIGELTFEXP_SIGE->PJM
CLTF
0.1860.186
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4574.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
78.26878.268
CPLELTFEXP_CPLE->PJM
CLTF
9.3529.352
TVALTFEXP_TVA->PJM
CLTF
4.8954.895
NYPJM->LTFIMP_NY
CLTF
2.2912.291
LGEELTFEXP_LGEE->PJM
CLTF
0.9480.948
WECLTFEXP_WEC->PJM
CLTF
0.4740.474

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.41 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4350.17
MW Contribution:23.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957862AF2-080 E
Adder
2.6270588235294122.233
926072AC1-086 E
Adder
7.6341176470588236.489
960081AF2-299 C
Adder
1.52470588235294141.296
3145413WATKINS
Adder
0.52941176470588240.45
936261AD2-033 C
Adder
10.782352941176479.165
962562AG1-105 E
Adder
4.842352941176474.116
961791AG1-021 C
Adder
1.48941176470588241.266
938771AE1-103 C
Adder
2.21764705882352951.885
924032AB2-045 E
Adder
1.08588235294117650.923
963041AG1-153 C
Adder
5.3588235294117644.555
944011AF1-069 C
50/50
12.65212.652
316045AC1-158 C2
50/50
19.56819.568
918512AA1-065 E OP
Adder
4.2588235294117653.62
918532AA1-067 E
Adder
0.55176470588235290.469
934502AD1-074 E
Adder
13.07176470588235311.111
934512AD1-075 E
Adder
3.26823529411764732.778
924516AB2-100 E1
Adder
2.36470588235294082.01
966621AG1-532 C
Adder
1.1435294117647060.972
919153AA1-139 E2
Adder
3.02941176470588272.575
924022AB2-043 E O1
Adder
4.2929411764705883.649
3147223TWITTYS
Adder
0.78941176470588240.671
959312AF2-222 E
Adder
9.2564705882352957.868
3152261N ANNA2
50/50
106.886106.886
940642AE2-051 E
50/50
10.98110.981
942341AE2-247 C
Adder
1.09764705882352940.933
943462AF1-017 E
Adder
1.621.377
958162AF2-110 E
Adder
1.61411764705882371.372
316141AB2-099 E
Adder
0.195294117647058840.166
961672AG1-007 E
Adder
0.414117647058823530.352
923994AB2-040_E
Adder
4.9741176470588234.228
316088AB2-174 E
Adder
5.2858823529411774.493
924322AB2-079 E O1
Adder
1.10588235294117650.94
943902AF1-058 E
Adder
1.04352941176470580.887
946302AF1-294 E
Adder
2.59294117647058852.204
957481AF2-042 C
Adder
49.0341176470588341.679
3151801S ANNAS2
50/50
1.5681.568
942002AE2-212 E
Adder
0.99176470588235290.843
944581AF1-123 C
Adder
33.8670588235294128.787
923263AB1-132 E OP
Adder
4.8811764705882354.149
940481AE2-033 C
Adder
13.54823529411764811.516
940482AE2-033 E
Adder
9.1341176470588247.764
940541AE2-040 C
Adder
2.4117647058823532.05
924312AB2-078 E O1
Adder
1.10588235294117650.94
925612AC1-036 E
Adder
0.7117647058823530.605
926274AC1-105 E
Adder
2.1788235294117651.852
966001AG1-469 C
50/50
2.0062.006
926740AC1-158 E2
50/50
51.18251.182
934501AD1-074 C
Adder
25.6821.828
961671AG1-007 C
Adder
0.73058823529411760.621
924517AB2-100 E2
Adder
2.36470588235294082.01
937226AE2-253 E
Adder
4.3282352941176473.679
946301AF1-294 C
Adder
3.06235294117647072.603
935172AD1-152 E
Adder
4.7270588235294114.018
942461AE2-259 C
Adder
8.257647058823537.019
934621AD1-088 C
Adder
8.5905882352941177.302
957482AF2-042 E
Adder
32.6894117647058927.786
208901BRIS G2
50/50
-2.946-2.946
958502AF2-144 E
Adder
1.15294117647058810.98
316192AB2-158 C
50/50
4.2784.278
942001AE2-212 C
Adder
1.48705882352941181.264
939192AE1-149 E
Adder
5.1470588235294124.375
941101AE2-104 C
Adder
2.48705882352941152.114
933981AD1-022 C
Adder
6.6952941176470595.691
900672V4-068 E
Adder
0.276470588235294130.235
938531AE1-072 C
Adder
13.03294117647058811.078
924302AB2-077 E O1
Adder
1.10588235294117650.94
3145393UNCAMP
Adder
4.622352941176473.929
932046AC2-012 E
Adder
9.6164705882352938.174
958161AF2-110 C
Adder
1.0152941176470590.863
927021AC1-189 C
Adder
6.5247058823529425.546
926071AC1-086 C
Adder
16.77411764705882314.258
924152AB2-059 E OP
Adder
4.122352941176473.504
946281AF1-292 C
Adder
1.26235294117647071.073
960082AF2-299 E
Adder
1.01647058823529420.864
916042Z1-036 E
Adder
21.48117647058823518.259
923832AB2-022 E
Adder
0.92235294117647060.784
964241AG1-285 C
Adder
10.3776470588235298.821
962561AG1-105 C
Adder
7.2635294117647076.174
958212AF2-115 E
Adder
1.58588235294117651.348
938772AE1-103 E
Adder
3.0611764705882352.602
963042AG1-153 E
Adder
8.0388235294117656.833
925022AB2-158 E
50/50
11.37311.373
316044AC1-158 C1
50/50
19.56819.568
944592AF1-124 E
Adder
77.8317647058823566.157
944582AF1-123 E
Adder
77.5517647058823565.919
316349AD2-085 C
Adder
2.53294117647058852.153
935112AD1-144 E
Adder
0.67176470588235290.571
961942AG1-037 E
Adder
0.26117647058823530.222
961941AG1-037 C
Adder
0.391764705882352960.333
927022AC1-189 E
Adder
3.25058823529411762.763
934322AD1-056 E
Adder
2.6764705882352942.275
934332AD1-057 E
Adder
1.43411764705882371.219
934321AD1-056 C
Adder
4.9352941176470594.195
934331AD1-057 C
Adder
2.75294117647058822.34
925595AC1-034 E
Adder
3.91058823529411773.324
923852AB2-025 E
Adder
0.97529411764705880.829
936262AD2-033 E
Adder
7.1882352941176476.11
958211AF2-115 C
Adder
1.86235294117647051.583
208900BRIS G1
50/50
-2.489-2.489
3151761LOISA E
50/50
6.3326.332
3151771S ANNAG1
50/50
3.0513.051
3151791S ANNAG2
50/50
3.0513.051
3151781S ANNAS1
50/50
1.5681.568
923862AB2-026 E
Adder
1.17294117647058820.997
941031AE2-094 C
50/50
38.72138.721
941032AE2-094 E
50/50
17.34217.342
3150831SPRUNCA
Adder
6.117647058823535.2
3150841SPRUNCB
Adder
6.117647058823535.2
939412AE1-173 E
Adder
54.5505882352941246.368
926662AC1-147 E
Adder
0.97176470588235290.826
916192Z1-068 E
Adder
1.38588235294117631.178
957492AF2-043 E
Adder
1.05294117647058830.895
933982AD1-022 E
Adder
3.6447058823529413.098
3145946PLYMOUTH TP
Adder
0.245882352941176470.209
927146AC1-208 E
Adder
3.1564705882352942.683
927255AC1-221 E
Adder
2.9588235294117652.515
934612AD1-087 E
Adder
3.2152941176470592.733
934622AD1-088 E
Adder
4.1364705882352943.516
316336AC2-165 C
Adder
9.177647058823537.801
940641AE2-051 C
50/50
16.47216.472
316084AB2-161 E
Adder
4.0141176470588233.412
943172AE2-346 E
Adder
0.46941176470588240.399
917332KELFORD E
Adder
1.281.088
925122AB2-169 E
Adder
4.4105882352941183.749
934522AD1-076 E
Adder
4.7541176470588244.041
940492AE2-034 E
Adder
2.3364705882352941.986
316274AC1-208 C
Adder
7.1094117647058826.043
962571AG1-106 C
Adder
2.16941176470588241.844
917342Z2-044 E
Adder
0.46823529411764710.398
3151311EDGECMA
Adder
12.11411764705882510.297
918492AA1-063AE OP
Adder
3.22705882352941182.743
957871AF2-081 C
Adder
7.4070588235294126.296
961792AG1-021 E
Adder
1.26941176470588221.079
937482AD2-202 E
Adder
0.94117647058823540.8
3145506HICKORY
Adder
1.61411764705882371.372
933292AC2-141 E
Adder
9.502352941176478.077
934576AD1-082 E
Adder
3.19882352941176462.719
944602AF1-125 E
Adder
76.3341176470588364.884
943612AF1-032 E
Adder
0.68470588235294120.582
939312AE1-162 E
Adder
0.97647058823529410.83
934065AD1-033 E
Adder
3.70941176470588243.153
926214AC1-099 E
Adder
0.94705882352941180.805
932632AC2-084 E
Adder
2.53411764705882362.154
962572AG1-106 E
Adder
0.94941176470588240.807
957872AF2-081 E
Adder
3.17411764705882372.698
924162AB2-060 E OP
Adder
3.54470588235294143.013
964242AG1-285 E
Adder
6.9188235294117655.881
964792AG1-342 E
Adder
1.92588235294117661.637
932763AC2-100 E
Adder
2.00588235294117641.705
938562AE1-075 E
Adder
1.00.85
3152251N ANNA1
50/50
106.841106.841
938552AE1-074 E
Adder
1.09294117647058830.929
926755AC1-161 E
Adder
9.502352941176478.077
933291AC2-141 C
Adder
22.2618.921
925522AC1-027 E
Adder
0.89764705882352950.763
941102AE2-104 E
Adder
3.9541176470588243.361
3145256KINGFORK
Adder
0.72352941176470590.615
934521AD1-076 C
Adder
9.3258823529411777.927
934511AD1-075 C
Adder
6.425.457
919692AA2-053 E OP
Adder
3.36117647058823542.857
316263AC1-034 C
Adder
5.1835294117647064.406
923573AB1-173 E OP
Adder
2.6529411764705882.255
3145723EMPORIA
Adder
0.350588235294117640.298
920042AA2-088 E OP
Adder
8.226.987
925785AC1-054 E
Adder
2.79764705882352962.378
919152AA1-139 E1
Adder
3.02941176470588272.575
959311AF2-222 C
Adder
13.8152941176470611.743
942342AE2-247 E
Adder
1.5164705882352941.289
920692AA2-178 E
Adder
3.1141176470588232.647
922923AB1-081 E OP
Adder
2.9105882352941182.474
966622AG1-532 E
Adder
0.76235294117647070.648
917122Z2-027 E
Adder
1.00.85
3146326AYDLETT TAP
Adder
1.00588235294117640.855
938532AE1-072 E
Adder
6.7941176470588245.775
927264AC1-222 E
Adder
3.20470588235294152.724
3147133PAMPLIN
Adder
0.82352941176470580.7
966002AG1-469 E
50/50
1.0031.003
926739AC1-158 E1
50/50
51.18251.182
316233AE1-074 C
Adder
2.17058823529411751.845
943461AF1-017 C
Adder
0.99294117647058820.844
316311AC2-079 C
Adder
4.2247058823529413.591
932596AC2-079 E
Adder
6.8929411764705895.859
919710AA2-057 E
Adder
3.1117647058823532.645
3137643SOCKMAN
Adder
0.57294117647058830.487
913392Y1-086 E
Adder
1.63411764705882371.389
933502AC2-165 E
Adder
6.9070588235294135.871
3151741LOISA C
50/50
3.1063.106
3151721LOISA A
50/50
3.093.09
939411AE1-173 C
Adder
81.8247058823529469.551
926206AC1-098 E
Adder
2.86705882352941142.437
964791AG1-342 C
Adder
2.88941176470588262.456
901082W1-029 E
Adder
23.76705882352941420.202
942462AE2-259 E
Adder
5.5047058823529414.679
3151731LOISA B
50/50
3.1063.106
3151751LOISA D
50/50
3.1063.106
3143316POE
Adder
1.04235294117647070.886
939191AE1-149 C
Adder
7.7200000000000016.562
957861AF2-080 C
Adder
5.9270588235294125.038
917512Z2-088 E OP1
Adder
3.8047058823529413.234
946282AF1-292 E
Adder
0.84117647058823530.715
3138533PONTONDP
Adder
0.55176470588235290.469
944012AF1-069 E
50/50
4.9154.915
944591AF1-124 C
Adder
33.9870588235294128.889
944601AF1-125 C
Adder
33.3447058823529428.343
941591AE2-156 C
Adder
13.14823529411764711.176
936666AD2-085 E
Adder
4.1329411764705883.513
316303AF2-085
50/50
4.0434.043
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.05120.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.83616.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7842.784
LAGNLTFEXP_LAGN->PJM
CLTF
5.9595.959
G-007PJM->LTFIMP_G-007
CMTX_NF
5.0575.057
SIGELTFEXP_SIGE->PJM
CLTF
0.1730.173
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4084.408
CBM South 2LTFEXP_CBM-S2->PJM
CBM
77.11777.117
CPLELTFEXP_CPLE->PJM
CLTF
9.2519.251
TVALTFEXP_TVA->PJM
CLTF
4.7224.722
O66PJM->LTFIMP_O-066
CMTX_NF
32.20632.206
NYPJM->LTFIMP_NY
CLTF
2.3732.373
LGEELTFEXP_LGEE->PJM
CLTF
0.8720.872
WECLTFEXP_WEC->PJM
CLTF
0.4310.431

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.75 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4205.81
MW Contribution:22.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
918512AA1-065 E OP
Adder
4.06000000000000053.451
918532AA1-067 E
Adder
0.52705882352941180.448
934502AD1-074 E
Adder
12.44588235294117810.579
934512AD1-075 E
Adder
3.1117647058823532.645
924516AB2-100 E1
Adder
2.26000000000000021.921
966621AG1-532 C
Adder
1.09411764705882360.93
919153AA1-139 E2
Adder
2.8741176470588242.443
924022AB2-043 E O1
Adder
4.1364705882352943.516
3147223TWITTYS
Adder
0.76235294117647070.648
959312AF2-222 E
Adder
8.9494117647058827.607
934861AD1-115 C
50/50
3.523.52
3152261N ANNA2
50/50
104.075104.075
940642AE2-051 E
50/50
10.52910.529
942341AE2-247 C
Adder
1.04117647058823540.885
943462AF1-017 E
Adder
1.53764705882352941.307
958162AF2-110 E
Adder
1.53176470588235311.302
923263AB1-132 E OP
Adder
4.66470588235294153.965
940481AE2-033 C
Adder
12.94470588235294211.003
940482AE2-033 E
Adder
8.7270588235294117.418
940541AE2-040 C
Adder
2.3035294117647061.958
924312AB2-078 E O1
Adder
1.06588235294117650.906
925612AC1-036 E
Adder
0.68823529411764710.585
926274AC1-105 E
Adder
2.09764705882352941.783
966001AG1-469 C
50/50
2.4612.461
925672AC1-043 E
50/50
11.48611.486
926740AC1-158 E2
50/50
48.49548.495
316141AB2-099 E
Adder
0.187058823529411780.159
923994AB2-040_E
Adder
4.7588235294117654.045
316088AB2-174 E
Adder
5.0564705882352944.298
924322AB2-079 E O1
Adder
1.06588235294117650.906
943902AF1-058 E
Adder
1.00470588235294110.854
946302AF1-294 E
Adder
2.51294117647058852.136
957481AF2-042 C
Adder
47.1905882352941240.112
3151801S ANNAS2
50/50
1.7251.725
942002AE2-212 E
Adder
0.93764705882352950.797
944581AF1-123 C
Adder
32.1329411764705927.313
941101AE2-104 C
Adder
2.362.006
933981AD1-022 C
Adder
6.3764705882352955.42
900672V4-068 E
Adder
0.26352941176470590.224
938531AE1-072 C
Adder
12.36823529411764810.513
924302AB2-077 E O1
Adder
1.06588235294117650.906
3145393UNCAMP
Adder
4.3976470588235293.738
926486AC1-120 E
50/50
4.6124.612
932046AC2-012 E
Adder
9.1176470588235297.75
958161AF2-110 C
Adder
0.96352941176470590.819
927021AC1-189 C
Adder
6.2352941176470595.3
926071AC1-086 C
Adder
16.0282352941176513.624
946281AF1-292 C
Adder
1.2082352941176471.027
960082AF2-299 E
Adder
0.97294117647058820.827
916042Z1-036 E
Adder
20.41647058823529517.354
923832AB2-022 E
Adder
0.87529411764705890.744
964241AG1-285 C
Adder
10.0105882352941198.509
962561AG1-105 C
Adder
6.9952941176470595.946
958212AF2-115 E
Adder
1.53764705882352941.307
938772AE1-103 E
Adder
2.91176470588235332.475
961942AG1-037 E
Adder
0.249411764705882360.212
961941AG1-037 C
Adder
0.37294117647058830.317
927022AC1-189 E
Adder
3.10588235294117652.64
934322AD1-056 E
Adder
2.562.176
934332AD1-057 E
Adder
1.37058823529411771.165
934321AD1-056 C
Adder
4.7188235294117654.011
934331AD1-057 C
Adder
2.6329411764705882.238
923852AB2-025 E
Adder
0.9317647058823530.792
936262AD2-033 E
Adder
6.9435294117647075.902
958211AF2-115 C
Adder
1.80470588235294121.534
208900BRIS G1
50/50
-2.42-2.42
3151761LOISA E
50/50
7.047.04
3151771S ANNAG1
50/50
3.3573.357
3151791S ANNAG2
50/50
3.3573.357
3151781S ANNAS1
50/50
1.7251.725
923862AB2-026 E
Adder
1.13764705882352950.967
941031AE2-094 C
50/50
37.19337.193
941032AE2-094 E
50/50
16.65816.658
939412AE1-173 E
Adder
52.19411764705882544.365
926662AC1-147 E
Adder
0.92117647058823540.783
916192Z1-068 E
Adder
1.31411764705882361.117
957492AF2-043 E
Adder
0.99882352941176470.849
963042AG1-153 E
Adder
7.7235294117647076.565
925022AB2-158 E
50/50
11.64111.641
316044AC1-158 C1
50/50
18.54118.541
944592AF1-124 E
Adder
73.8458823529411762.769
944582AF1-123 E
Adder
73.5862.543
316349AD2-085 C
Adder
2.40235294117647062.042
933982AD1-022 E
Adder
3.47058823529411782.95
3145946PLYMOUTH TP
Adder
0.234117647058823540.199
927146AC1-208 E
Adder
3.01882352941176452.566
927255AC1-221 E
Adder
2.84470588235294162.418
934612AD1-087 E
Adder
3.09529411764705882.631
934622AD1-088 E
Adder
3.98588235294117643.388
316336AC2-165 C
Adder
8.9188235294117667.581
926004AC1-076_E
50/50
6.3656.365
940641AE2-051 C
50/50
15.79315.793
316084AB2-161 E
Adder
3.8047058823529413.234
935112AD1-144 E
Adder
0.63647058823529420.541
943172AE2-346 E
Adder
0.448235294117647070.381
917332KELFORD E
Adder
1.22235294117647041.039
925122AB2-169 E
Adder
4.2058823529411773.575
934522AD1-076 E
Adder
4.5258823529411773.847
940492AE2-034 E
Adder
2.2223529411764711.889
316274AC1-208 C
Adder
6.7976470588235295.778
962571AG1-106 C
Adder
2.07294117647058851.762
917342Z2-044 E
Adder
0.448235294117647070.381
918492AA1-063AE OP
Adder
3.08235294117647072.62
957871AF2-081 C
Adder
7.0282352941176475.974
961792AG1-021 E
Adder
1.22941176470588221.045
937482AD2-202 E
Adder
0.90588235294117650.77
3145506HICKORY
Adder
1.53058823529411761.301
933292AC2-141 E
Adder
9.0070588235294127.656
934576AD1-082 E
Adder
3.0317647058823532.577
944602AF1-125 E
Adder
72.4247058823529461.561
943612AF1-032 E
Adder
0.64941176470588250.552
934501AD1-074 C
Adder
24.44941176470588220.782
924517AB2-100 E2
Adder
2.26000000000000021.921
937226AE2-253 E
Adder
4.1070588235294123.491
946301AF1-294 C
Adder
2.96705882352941152.522
935172AD1-152 E
Adder
4.5494117647058833.867
942461AE2-259 C
Adder
8.0294117647058826.825
934621AD1-088 C
Adder
8.277647058823537.036
957482AF2-042 E
Adder
31.4626.741
208901BRIS G2
50/50
-2.864-2.864
958502AF2-144 E
Adder
1.11764705882352940.95
316192AB2-158 C
50/50
4.384.38
942001AE2-212 C
Adder
1.40588235294117661.195
939192AE1-149 E
Adder
4.87529411764705944.144
934065AD1-033 E
Adder
3.5188235294117652.991
926214AC1-099 E
Adder
0.90470588235294120.769
932632AC2-084 E
Adder
2.4211764705882352.058
962572AG1-106 E
Adder
0.90705882352941180.771
957872AF2-081 E
Adder
3.0117647058823532.56
924162AB2-060 E OP
Adder
3.4164705882352942.904
964242AG1-285 E
Adder
6.6741176470588245.673
964792AG1-342 E
Adder
1.85529411764705881.577
932763AC2-100 E
Adder
1.9282352941176471.639
934862AD1-115 E
50/50
5.7435.743
938562AE1-075 E
Adder
0.96941176470588230.824
3152251N ANNA1
50/50
104.031104.031
938552AE1-074 E
Adder
1.04470588235294120.888
926755AC1-161 E
Adder
9.0070588235294127.656
933291AC2-141 C
Adder
21.09882352941176717.934
925522AC1-027 E
Adder
0.85058823529411760.723
941102AE2-104 E
Adder
3.75294117647058823.19
3145256KINGFORK
Adder
0.68588235294117650.583
934521AD1-076 C
Adder
8.8788235294117657.547
934511AD1-075 C
Adder
6.1117647058823535.195
919692AA2-053 E OP
Adder
3.2129411764705882.731
923573AB1-173 E OP
Adder
2.53764705882352942.157
3145723EMPORIA
Adder
0.33529411764705880.285
920692AA2-178 E
Adder
2.9635294117647062.519
966622AG1-532 E
Adder
0.72941176470588230.62
917122Z2-027 E
Adder
0.94941176470588240.807
3146326AYDLETT TAP
Adder
0.95411764705882360.811
938532AE1-072 E
Adder
6.4470588235294135.48
927264AC1-222 E
Adder
3.0847058823529412.622
3147133PAMPLIN
Adder
0.79882352941176480.679
966002AG1-469 E
50/50
1.231.23
926739AC1-158 E1
50/50
48.49548.495
316233AE1-074 C
Adder
2.07294117647058851.762
943461AF1-017 C
Adder
0.94235294117647060.801
316311AC2-079 C
Adder
4.00705882352941253.406
932596AC2-079 E
Adder
6.5388235294117655.558
919710AA2-057 E
Adder
2.97647058823529382.53
3137643SOCKMAN
Adder
0.54705882352941180.465
913392Y1-086 E
Adder
1.5517647058823531.319
933502AC2-165 E
Adder
6.7129411764705895.706
3151741LOISA C
50/50
3.4533.453
3151721LOISA A
50/50
3.4353.435
939411AE1-173 C
Adder
78.2905882352941166.547
920042AA2-088 E OP
Adder
7.8352941176470596.66
925785AC1-054 E
Adder
2.6835294117647062.281
919152AA1-139 E1
Adder
2.8741176470588242.443
959311AF2-222 C
Adder
13.3576470588235311.354
926502AC1-121 E
50/50
1.4471.447
942342AE2-247 E
Adder
1.43764705882352951.222
926206AC1-098 E
Adder
2.742.329
964791AG1-342 C
Adder
2.7823529411764712.365
901082W1-029 E
Adder
22.56941176470588319.184
942462AE2-259 E
Adder
5.3529411764705884.55
3151731LOISA B
50/50
3.4533.453
3151751LOISA D
50/50
3.4533.453
3143316POE
Adder
0.99058823529411770.842
316164AC1-076_C
50/50
1.1111.111
939191AE1-149 C
Adder
7.3129411764705896.216
957861AF2-080 C
Adder
5.6635294117647064.814
946282AF1-292 E
Adder
0.80470588235294130.684
3138533PONTONDP
Adder
0.53411764705882360.454
316257AC1-043 C
50/50
7.047.04
316254AC1-120 C
50/50
8.9538.953
944012AF1-069 E
50/50
4.7214.721
957862AF2-080 E
Adder
2.5105882352941182.134
926072AC1-086 E
Adder
7.29529411764705856.201
960081AF2-299 C
Adder
1.45882352941176461.24
3145413WATKINS
Adder
0.50352941176470590.428
936261AD2-033 C
Adder
10.415294117647068.853
962562AG1-105 E
Adder
4.6635294117647063.964
961791AG1-021 C
Adder
1.4435294117647061.227
938771AE1-103 C
Adder
2.1082352941176471.792
924032AB2-045 E
Adder
1.06588235294117650.906
963041AG1-153 C
Adder
5.1482352941176474.376
316170AC1-121 C
50/50
3.0753.075
944011AF1-069 C
50/50
12.15212.152
316045AC1-158 C2
50/50
18.54118.541
944591AF1-124 C
Adder
32.24705882352941427.41
944601AF1-125 C
Adder
31.6376470588235326.892
941591AE2-156 C
Adder
12.46588235294117710.596
936666AD2-085 E
Adder
3.923.332
316303AF2-085
50/50
3.8863.886
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.05119.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.10316.103
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.6562.656
LAGNLTFEXP_LAGN->PJM
CLTF
5.7065.706
G-007PJM->LTFIMP_G-007
CMTX_NF
4.9174.917
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2284.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.97573.975
CPLELTFEXP_CPLE->PJM
CLTF
8.8738.873
TVALTFEXP_TVA->PJM
CLTF
4.5234.523
O66PJM->LTFIMP_O-066
CMTX_NF
31.31531.315
NYPJM->LTFIMP_NY
CLTF
2.3072.307
LGEELTFEXP_LGEE->PJM
CLTF
0.8310.831
WECLTFEXP_WEC->PJM
CLTF
0.410.41

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.97 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3767.03
MW Contribution:15.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960081AF2-299 C
80/20
1.7191.719
936261AD2-033 C
Adder
11.7211764705882359.963
961791AG1-021 C
Adder
1.61176470588235321.37
938771AE1-103 C
80/20
2.6332.633
963041AG1-153 C
80/20
5.7035.703
3151051BRUNSWICKS1
80/20
17.42917.429
944011AF1-069 C
80/20
13.43113.431
3150601CHESTF5
Adder
45.29058823529411638.497
944591AF1-124 C
80/20
41.04941.049
944601AF1-125 C
80/20
40.27340.273
3151101ELIZAR3
80/20
2.8872.887
941591AE2-156 C
80/20
15.98415.984
927021AC1-189 C
Adder
7.4435294117647066.327
926071AC1-086 C
Adder
19.07647058823529616.215
946281AF1-292 C
80/20
1.4231.423
964241AG1-285 C
Adder
11.3035294117647079.608
962561AG1-105 C
Adder
7.9117647058823526.725
3151091ELIZAR2
80/20
2.8012.801
316349AD2-085 C
80/20
3.0713.071
313506AB1-173 C OP
80/20
1.0281.028
966621AG1-532 C
80/20
1.2891.289
316320Y1-086 C
80/20
0.1960.196
316388AE2-253 GEN
80/20
1.7531.753
935171AD1-152 C
80/20
1.2331.233
3151021BRUNSWICKG1
80/20
8.3898.389
3151041BRUNSWICKG3
80/20
8.3898.389
3152261N ANNA2
80/20
92.75992.759
942341AE2-247 C
80/20
1.3311.331
316246AF1-032 C
80/20
0.2540.254
316365AB2-100 C1
80/20
0.8850.885
957481AF2-042 C
80/20
52.44752.447
3151801S ANNAS2
80/20
1.2181.218
940431AE2-027 C
Adder
10.6976470588235299.093
316294AC1-161 C
80/20
4.4154.415
944581AF1-123 C
80/20
40.90340.903
316185AD1-033 C
80/20
1.0971.097
916191Z1-068 C
80/20
0.0390.039
941101AE2-104 C
80/20
3.0013.001
316181AB2-040 GEN
80/20
1.1581.158
3147043LAWRENC
80/20
0.2810.281
940481AE2-033 C
80/20
15.30215.302
940541AE2-040 C
80/20
2.7232.723
3152441Z1-086 ST
80/20
18.71718.717
966001AG1-469 C
Adder
1.43764705882352951.222
961611AG1-000B C
Adder
13.19882352941176511.219
316375AC2-012 C
80/20
1.2021.202
316072AD1-144 C
80/20
0.2460.246
934501AD1-074 C
Adder
30.18352941176470625.656
961671AG1-007 C
Adder
0.82941176470588230.705
946301AF1-294 C
Adder
3.3141176470588242.817
942461AE2-259 C
Adder
8.8929411764705887.559
934621AD1-088 C
80/20
9.29.2
208901BRIS G2
80/20
-3.03-3.03
316192AB2-158 C
80/20
3.5593.559
942001AE2-212 C
Adder
1.8635294117647061.584
316274AC1-208 C
Adder
8.077647058823536.866
962571AG1-106 C
Adder
2.4670588235294122.097
3151311EDGECMA
Adder
13.67647058823529511.625
957871AF2-081 C
80/20
8.9458.945
316405AF2-144 C
80/20
0.30.3
3150651CHESTF6
Adder
15.16470588235294212.89
3150861SPRUNCD
80/20
0.140.14
933981AD1-022 C
Adder
7.84941176470588256.672
938531AE1-072 C
80/20
15.7315.73
3150731STONECA
Adder
5.4352941176470594.62
935161AD1-151 C
Adder
13.03882352941176511.083
316083AB2-161 C
80/20
0.4890.489
958161AF2-110 C
80/20
1.2251.225
961941AG1-037 C
Adder
0.454117647058823570.386
934321AD1-056 C
Adder
5.5882352941176484.75
934331AD1-057 C
Adder
3.11764705882352942.65
958211AF2-115 C
Adder
2.0152941176470591.713
3151531CLOVER1
80/20
12.09912.099
208900BRIS G1
80/20
-2.561-2.561
3151761LOISA E
80/20
4.8664.866
3151771S ANNAG1
80/20
2.372.37
3151791S ANNAG2
80/20
2.372.37
3151781S ANNAS1
80/20
1.2181.218
316258AE1-075 C
80/20
0.3530.353
941031AE2-094 C
80/20
41.10641.106
3150831SPRUNCA
Adder
7.7905882352941186.622
3150841SPRUNCB
Adder
7.7905882352941186.622
3151081ELIZAR1
80/20
2.8512.851
313526AB2-022 C
80/20
0.3360.336
316017AA1-139 ULT1
80/20
0.9650.965
934611AD1-087 C
80/20
1.1911.191
3152431Z1-086 GT3
80/20
10.7510.75
316336AC2-165 C
80/20
9.7879.787
940641AE2-051 C
80/20
17.817.8
316018AA1-139 ULT2
80/20
0.9650.965
3152251N ANNA1
80/20
92.7292.72
3150851SPRUNCC
80/20
0.140.14
944631AF1-128 C
Adder
28.33882352941176624.088
933291AC2-141 C
80/20
27.11427.114
3150921YORKTN3
Adder
92.4352941176470578.57
934521AD1-076 C
Adder
10.9623529411764719.318
934511AD1-075 C
Adder
7.54588235294117656.414
316263AC1-034 C
Adder
5.8505882352941184.973
316087AB2-174 C
80/20
1.0751.075
316321Z2-027 C
80/20
0.3250.325
959311AF2-222 C
Adder
14.9976470588235312.748
937481AD2-202 C
80/20
0.3460.346
3151031BRUNSWICKG2
80/20
8.3898.389
316240AF1-291 C
Adder
1.78117647058823541.514
944641AF1-129 C
Adder
83.2882352941176570.795
316036AC1-147 C
80/20
0.3280.328
316305AF2-043 C
80/20
0.3110.311
3137643SOCKMAN
Adder
0.64823529411764710.551
3151741LOISA C
80/20
2.3872.387
3151721LOISA A
80/20
2.3742.374
939411AE1-173 C
80/20
90.4790.47
316381AD1-082 C
80/20
1.1161.116
3150991CHESPKB
80/20
0.6430.643
3156056W1-029WIND
80/20
0.6930.693
3152411Z1-086 GT1
80/20
10.75310.753
3152421Z1-086 GT2
80/20
10.7510.75
316233AE1-074 C
80/20
2.4792.479
943461AF1-017 C
80/20
1.2041.204
316311AC2-079 C
80/20
5.125.12
964791AG1-342 C
Adder
3.14588235294117662.674
3151731LOISA B
80/20
2.3872.387
3151751LOISA D
80/20
2.3872.387
316313AB2-026 C
80/20
0.3850.385
939191AE1-149 C
80/20
9.4869.486
3150981CHESPKA
80/20
0.3880.388
957861AF2-080 C
Adder
6.7600000000000015.746
316023AB2-100 C2
80/20
0.8850.885
316315AB2-025 C
80/20
0.3860.386
3138533PONTONDP
Adder
0.59764705882352940.508
3151541CLOVER2
80/20
11.98611.986
316316AC1-027 C
80/20
0.2820.282
316303AF2-085
80/20
4.3034.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.18225.182
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.8619.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.3753.375
LAGNLTFEXP_LAGN->PJM
CLTF
6.9186.918
SIGELTFEXP_SIGE->PJM
CLTF
0.2110.211
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.8954.895
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.42786.427
CPLELTFEXP_CPLE->PJM
CLTF
10.2710.27
TVALTFEXP_TVA->PJM
CLTF
5.5015.501
NYPJM->LTFIMP_NY
CLTF
2.4542.454
LGEELTFEXP_LGEE->PJM
CLTF
1.0841.084
WECLTFEXP_WEC->PJM
CLTF
0.5370.537

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.22 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3678.49
MW Contribution:16.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960081AF2-299 C
Adder
1.95294117647058821.66
936261AD2-033 C
Adder
12.57294117647058810.687
961791AG1-021 C
Adder
1.71764705882352931.46
938771AE1-103 C
Adder
3.22705882352941182.743
963041AG1-153 C
Adder
5.8858823529411765.003
944011AF1-069 C
80/20
13.80413.804
966881AG1-559 C
Adder
2.45176470588235332.084
3150601CHESTF5
Adder
70.4105882352941159.849
944591AF1-124 C
80/20
51.4651.46
944601AF1-125 C
80/20
50.48850.488
3151101ELIZAR3
80/20
3.6473.647
941591AE2-156 C
80/20
20.20920.209
927021AC1-189 C
Adder
8.6023529411764727.312
926071AC1-086 C
Adder
21.9611764705882418.667
946281AF1-292 C
Adder
1.61647058823529431.374
964241AG1-285 C
Adder
12.1610.336
962561AG1-105 C
Adder
8.5058823529411767.23
939261AE1-157 C
Adder
14.10235294117647211.987
316169AC1-164 GEN
Adder
43.66588235294117537.116
3151091ELIZAR2
80/20
3.5383.538
316349AD2-085 C
Adder
3.87058823529411773.29
966621AG1-532 C
Adder
1.46470588235294131.245
934861AD1-115 C
Adder
-3.06-2.601
3152261N ANNA2
80/20
56.72156.721
3150771HOPHCF1
80/20
2.7332.733
942341AE2-247 C
Adder
1.67764705882352931.426
957481AF2-042 C
Adder
54.6470588235294146.45
940431AE2-027 C
80/20
14.61614.616
316294AC1-161 C
80/20
5.5975.597
944581AF1-123 C
80/20
51.27751.277
941101AE2-104 C
Adder
3.75764705882352963.194
940481AE2-033 C
Adder
17.43882352941176714.823
940541AE2-040 C
Adder
3.10117647058823562.636
927041AC1-191 C
Adder
10.2870588235294128.744
963611AG1-210 C
Adder
0.68235294117647060.58
961611AG1-000B C
Adder
17.92352941176470415.235
316375AC2-012 C
80/20
1.521.52
934501AD1-074 C
Adder
36.4552941176470630.987
961671AG1-007 C
Adder
0.95176470588235310.809
946301AF1-294 C
Adder
3.5305882352941183.001
942461AE2-259 C
Adder
9.4035294117647077.993
934621AD1-088 C
Adder
9.6105882352941188.169
942001AE2-212 C
80/20
2.4472.447
962861AG1-135 C
Adder
6.3647058823529425.41
943741AF1-042 C
Adder
3.06352941176470632.604
316274AC1-208 C
Adder
9.2835294117647067.891
962571AG1-106 C
Adder
2.84117647058823542.415
3151311EDGECMA
Adder
15.55647058823529613.223
957871AF2-081 C
Adder
11.2117647058823529.53
3150651CHESTF6
80/20
21.09121.091
3150861SPRUNCD
80/20
0.1870.187
936591AD2-074 C
Adder
5.8552941176470594.977
933981AD1-022 C
Adder
9.4470588235294128.03
938531AE1-072 C
Adder
19.70000000000000316.745
3142366NRTHEST
80/20
0.2040.204
3150731STONECA
80/20
7.7657.765
935161AD1-151 C
Adder
18.16235294117647215.438
958161AF2-110 C
Adder
1.53294117647058831.303
961941AG1-037 C
Adder
0.53764705882352950.457
934321AD1-056 C
Adder
6.3870588235294125.429
934331AD1-057 C
Adder
3.5635294117647063.029
958211AF2-115 C
Adder
2.14705882352941171.825
941031AE2-094 C
80/20
42.24742.247
3150831SPRUNCA
80/20
10.42510.425
3150841SPRUNCB
80/20
10.42510.425
966871AG1-558 C
Adder
2.56235294117647072.178
964211AG1-282 C
Adder
2.07882352941176451.767
3150801HOPHCF4
80/20
4.1494.149
3151081ELIZAR1
80/20
3.6013.601
316336AC2-165 C
Adder
10.1788235294117648.652
940641AE2-051 C
80/20
18.8818.88
943471AF1-018 C
Adder
7.6152941176470596.473
3152331SURRY 2
80/20
27.86527.865
3152251N ANNA1
80/20
56.69756.697
3150851SPRUNCC
80/20
0.1870.187
944631AF1-128 C
Adder
44.0564705882352937.448
933291AC2-141 C
80/20
34.37234.372
3150921YORKTN3
Adder
133.0105882352941113.059
934521AD1-076 C
Adder
13.2411.254
934511AD1-075 C
Adder
9.1141176470588237.747
316263AC1-034 C
Adder
6.6529411764705895.655
959311AF2-222 C
Adder
16.0552941176470613.647
316240AF1-291 C
80/20
2.4442.444
944641AF1-129 C
80/20
115.84115.84
3150781HOPHCF2
80/20
2.7332.733
3150761HOPPOLC
80/20
1.7191.719
3137643SOCKMAN
Adder
0.74235294117647070.631
966661AG1-536 C
Adder
5.6341176470588234.789
939411AE1-173 C
80/20
99.71499.714
3150991CHESPKB
80/20
0.8130.813
316233AE1-074 C
80/20
2.8742.874
940551AE2-041 C
Adder
7.6152941176470596.473
943461AF1-017 C
Adder
1.51764705882352961.29
316311AC2-079 C
Adder
6.4458823529411775.479
964791AG1-342 C
Adder
3.38000000000000032.873
3143096IRON208
80/20
0.4940.494
958261AF2-120 C
Adder
6.5505882352941175.568
939191AE1-149 C
80/20
12.15312.153
957601AF2-054 C
Adder
2.26000000000000021.921
957861AF2-080 C
Adder
7.8129411764705896.641
3138533PONTONDP
Adder
0.63647058823529420.541
316257AC1-043 C
Adder
-6.121176470588236-5.203
316254AC1-120 C
Adder
-6.376470588235295-5.42
3150791HOPHCF3
80/20
2.7332.733
961951AG1-038 C
Adder
3.3858823529411772.878
316303AF2-085
80/20
4.4474.447
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.72830.728
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.33523.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.0414.041
LAGNLTFEXP_LAGN->PJM
CLTF
8.0268.026
SIGELTFEXP_SIGE->PJM
CLTF
0.2560.256
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.4135.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69496.694
CPLELTFEXP_CPLE->PJM
CLTF
11.35211.352
TVALTFEXP_TVA->PJM
CLTF
6.4156.415
NYPJM->LTFIMP_NY
CLTF
2.72.7
LGEELTFEXP_LGEE->PJM
CLTF
1.331.33
WECLTFEXP_WEC->PJM
CLTF
0.6540.654

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.99 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4412.36
MW Contribution:26.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926072AC1-086 E
Adder
9.0847058823529427.722
960081AF2-299 C
Adder
1.7964705882352941.527
3145413WATKINS
Adder
0.65411764705882360.556
936261AD2-033 C
Adder
12.2210.387
961791AG1-021 C
Adder
1.68117647058823551.429
938771AE1-103 C
Adder
2.7670588235294122.352
963041AG1-153 C
50/50
5.9155.915
3151051BRUNSWICKS1
50/50
18.07518.075
944011AF1-069 C
50/50
13.92113.921
927226AC1-216 E
Adder
6.6694117647058825.669
944591AF1-124 C
Adder
43.2058823529411836.725
944601AF1-125 C
Adder
42.3894117647058836.031
941591AE2-156 C
Adder
16.83647058823529414.311
936666AD2-085 E
Adder
5.2764705882352954.485
918512AA1-065 E OP
Adder
5.2011764705882364.421
934502AD1-074 E
Adder
16.13411764705882613.714
934512AD1-075 E
Adder
4.0341176470588243.429
924516AB2-100 E1
Adder
2.82.38
966621AG1-532 C
Adder
1.34705882352941191.145
919153AA1-139 E2
Adder
3.8505882352941183.273
924022AB2-043 E O1
Adder
4.8811764705882354.149
3147223TWITTYS
Adder
0.89294117647058820.759
959312AF2-222 E
Adder
10.4764705882352948.905
3151021BRUNSWICKG1
50/50
8.78.7
3151041BRUNSWICKG3
50/50
8.78.7
3152261N ANNA2
50/50
93.22693.226
940642AE2-051 E
50/50
12.32512.325
942341AE2-247 C
Adder
1.40235294117647061.192
943462AF1-017 E
Adder
2.06941176470588231.759
958162AF2-110 E
Adder
2.0505882352941181.743
316141AB2-099 E
Adder
0.237647058823529430.202
923994AB2-040_E
Adder
5.8811764705882354.999
316088AB2-174 E
Adder
6.242352941176475.306
924322AB2-079 E O1
Adder
1.25764705882352931.069
946302AF1-294 E
Adder
2.9258823529411772.487
957481AF2-042 C
Adder
54.4729411764705946.302
3151801S ANNAS2
50/50
1.2331.233
942002AE2-212 E
Adder
1.31294117647058851.116
940431AE2-027 C
Adder
11.3411764705882369.64
944581AF1-123 C
Adder
43.0529411764705936.595
941101AE2-104 C
Adder
3.1588235294117652.685
923263AB1-132 E OP
Adder
5.80941176470588254.938
940481AE2-033 C
Adder
15.98588235294117513.588
940482AE2-033 E
Adder
10.777647058823539.161
940541AE2-040 C
Adder
2.84470588235294162.418
924312AB2-078 E O1
Adder
1.25764705882352931.069
925612AC1-036 E
Adder
0.80588235294117660.685
3152441Z1-086 ST
50/50
19.40819.408
966001AG1-469 C
Adder
1.46235294117647091.243
961611AG1-000B C
Adder
13.98823529411764911.89
934501AD1-074 C
Adder
31.6952941176470626.941
924517AB2-100 E2
Adder
2.82.38
937226AE2-253 E
Adder
5.5047058823529414.679
946301AF1-294 C
Adder
3.45529411764705862.937
935172AD1-152 E
Adder
5.2941176470588234.5
942461AE2-259 C
Adder
9.2705882352941187.88
934621AD1-088 C
Adder
9.5599999999999998.126
957482AF2-042 E
Adder
36.31529411764705630.868
208901BRIS G2
50/50
-3.245-3.245
958502AF2-144 E
Adder
1.2764705882352941.085
316192AB2-158 C
50/50
3.5873.587
942001AE2-212 C
Adder
1.96941176470588241.674
939192AE1-149 E
Adder
6.6670588235294125.667
939312AE1-162 E
Adder
1.29647058823529431.102
934065AD1-033 E
Adder
4.7282352941176474.019
933981AD1-022 C
Adder
8.247.004
900672V4-068 E
Adder
0.33764705882352940.287
938531AE1-072 C
Adder
16.55647058823529614.073
924302AB2-077 E O1
Adder
1.25764705882352931.069
3145393UNCAMP
Adder
5.7482352941176484.886
935161AD1-151 C
Adder
13.84941176470588311.772
932046AC2-012 E
Adder
12.31647058823529410.469
958161AF2-110 C
Adder
1.28941176470588251.096
926071AC1-086 C
Adder
19.96117647058823516.967
946281AF1-292 C
Adder
1.48705882352941181.264
960082AF2-299 E
Adder
1.19764705882352951.018
916042Z1-036 E
Adder
26.91882352941176422.881
923832AB2-022 E
Adder
1.1682352941176470.993
964241AG1-285 C
Adder
11.78352941176470610.016
958212AF2-115 E
Adder
1.78941176470588231.521
938772AE1-103 E
Adder
3.8211764705882363.248
963042AG1-153 E
50/50
8.8728.872
925022AB2-158 E
50/50
9.5359.535
944592AF1-124 E
Adder
98.9435294117647184.102
944582AF1-123 E
Adder
98.5858823529411883.798
316349AD2-085 C
Adder
3.23411764705882382.749
935112AD1-144 E
Adder
0.8717647058823530.741
961942AG1-037 E
Adder
0.317647058823529450.27
961941AG1-037 C
Adder
0.476470588235294150.405
923852AB2-025 E
Adder
1.15058823529411770.978
936262AD2-033 E
Adder
8.1458823529411776.924
958211AF2-115 C
Adder
2.1011764705882351.786
3151761LOISA E
50/50
4.9314.931
3151771S ANNAG1
50/50
2.42.4
3151791S ANNAG2
50/50
2.42.4
3151781S ANNAS1
50/50
1.2331.233
923862AB2-026 E
Adder
1.31.105
941031AE2-094 C
50/50
42.60742.607
941032AE2-094 E
50/50
19.08319.083
3150831SPRUNCA
Adder
8.2435294117647067.007
3150841SPRUNCB
Adder
8.2435294117647067.007
939412AE1-173 E
50/50
62.82462.824
926662AC1-147 E
Adder
1.24470588235294131.058
916192Z1-068 E
Adder
1.77058823529411761.505
957492AF2-043 E
Adder
1.341.139
933982AD1-022 E
Adder
4.4858823529411773.813
3145946PLYMOUTH TP
Adder
0.30352941176470590.258
934612AD1-087 E
Adder
3.5835294117647063.046
934622AD1-088 E
Adder
4.6035294117647063.913
3152431Z1-086 GT3
50/50
11.14611.146
316336AC2-165 C
Adder
10.1788235294117648.652
940641AE2-051 C
50/50
18.48718.487
316084AB2-161 E
Adder
5.1694117647058834.394
943172AE2-346 E
Adder
0.5717647058823530.486
917332KELFORD E
Adder
1.54588235294117651.314
934522AD1-076 E
Adder
5.8670588235294124.987
940492AE2-034 E
Adder
2.90235294117647062.467
962571AG1-106 C
Adder
2.58235294117647032.195
918492AA1-063AE OP
Adder
3.87294117647058833.292
957871AF2-081 C
Adder
9.4164705882352948.004
961792AG1-021 E
Adder
1.4317647058823531.217
937482AD2-202 E
Adder
1.04941176470588250.892
3145506HICKORY
Adder
2.05411764705882361.746
946262AF1-291 E
Adder
1.261.071
3150651CHESTF6
Adder
16.10470588235294213.689
933292AC2-141 E
Adder
12.19411764705882510.365
934576AD1-082 E
Adder
4.1188235294117653.501
944602AF1-125 E
Adder
97.0388235294117782.483
943612AF1-032 E
Adder
0.87058823529411770.74
962572AG1-106 E
Adder
1.12941176470588230.96
957872AF2-081 E
Adder
4.0352941176470593.43
924162AB2-060 E OP
Adder
4.0294117647058823.425
964242AG1-285 E
Adder
7.8564705882352946.678
938562AE1-075 E
Adder
1.1082352941176470.942
3152251N ANNA1
50/50
93.18793.187
938552AE1-074 E
50/50
1.3051.305
926755AC1-161 E
Adder
12.19411764705882510.365
933291AC2-141 C
Adder
28.56588235294117724.281
925522AC1-027 E
Adder
1.14588235294117660.974
941102AE2-104 E
Adder
5.0223529411764714.269
3145256KINGFORK
Adder
0.93882352941176480.798
934521AD1-076 C
Adder
11.5105882352941199.784
934511AD1-075 C
Adder
7.9235294117647066.735
919692AA2-053 E OP
Adder
4.00705882352941253.406
923573AB1-173 E OP
Adder
3.1364705882352942.666
3145723EMPORIA
Adder
0.414117647058823530.352
920042AA2-088 E OP
Adder
10.0447058823529418.538
925785AC1-054 E
Adder
3.24941176470588242.762
919152AA1-139 E1
Adder
3.8505882352941183.273
959311AF2-222 C
Adder
15.63529411764705813.29
3151031BRUNSWICKG2
50/50
8.78.7
316240AF1-291 C
Adder
1.88941176470588261.606
944641AF1-129 C
Adder
88.4505882352941375.183
924814AB2-134 E
Adder
10.9235294117647069.285
942342AE2-247 E
Adder
1.93529411764705881.645
920692AA2-178 E
Adder
3.86941176470588263.289
966622AG1-532 E
Adder
0.89882352941176480.764
917122Z2-027 E
Adder
1.26588235294117671.076
3146326AYDLETT TAP
Adder
1.27764705882352961.086
938532AE1-072 E
Adder
8.6305882352941187.336
3147133PAMPLIN
Adder
0.92823529411764720.789
3152411Z1-086 GT1
50/50
11.14911.149
3152421Z1-086 GT2
50/50
11.14611.146
966002AG1-469 E
Adder
0.73058823529411760.621
316233AE1-074 C
50/50
2.5912.591
935162AD1-151 E
Adder
0.93764705882352950.797
943461AF1-017 C
Adder
1.26823529411764711.078
316311AC2-079 C
Adder
5.3905882352941184.582
932596AC2-079 E
Adder
8.7952941176470587.476
3137643SOCKMAN
Adder
0.67882352941176470.577
913392Y1-086 E
Adder
2.0705882352941181.76
933502AC2-165 E
Adder
7.6611764705882356.512
940432AE2-027 E
Adder
7.5611764705882356.427
939411AE1-173 C
50/50
94.23794.237
934012AD1-025 E
Adder
8.6341176470588247.339
901082W1-029 E
Adder
30.02588235294117425.522
942462AE2-259 E
Adder
6.1800000000000015.253
3151731LOISA B
50/50
2.4192.419
3151751LOISA D
50/50
2.4192.419
3143316POE
Adder
1.30941176470588231.113
939191AE1-149 C
Adder
10.0011764705882348.501
946282AF1-292 E
Adder
0.99176470588235290.843
3138533PONTONDP
Adder
0.62235294117647070.529
944012AF1-069 E
50/50
5.4085.408
316303AF2-085
50/50
4.464.46
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.02528.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.37921.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.6863.686
LAGNLTFEXP_LAGN->PJM
CLTF
7.3867.386
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5685.568
SIGELTFEXP_SIGE->PJM
CLTF
0.2320.232
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.1255.125
CBM South 2LTFEXP_CBM-S2->PJM
CBM
90.8190.81
CPLELTFEXP_CPLE->PJM
CLTF
10.7510.75
TVALTFEXP_TVA->PJM
CLTF
5.8785.878
O66PJM->LTFIMP_O-066
CMTX_NF
35.46935.469
NYPJM->LTFIMP_NY
CLTF
2.6122.612
LGEELTFEXP_LGEE->PJM
CLTF
1.1951.195
WECLTFEXP_WEC->PJM
CLTF
0.5950.595

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.7 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4342.97
MW Contribution:25.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936171AD2-023 C
80/20
7.4677.467
936261AD2-033 C
80/20
19.83719.837
316248AF1-058 C
80/20
0.6420.642
961791AG1-021 C
80/20
2.642.64
941801AE2-185 C
80/20
4.7984.798
963041AG1-153 C
80/20
17.24617.246
3151051BRUNSWICKS1
80/20
52.70552.705
944011AF1-069 C
80/20
38.91238.912
964241AG1-285 C
80/20
19.39519.395
962561AG1-105 C
80/20
15.92115.921
316034AC1-036 C
80/20
0.3540.354
316118AC1-105 C
80/20
1.7691.769
943811AF1-049 C
80/20
9.4269.426
3144293JTRSVLE
80/20
0.6050.605
938741AE1-100 C
80/20
0.7290.729
941671AE2-166 C
80/20
5.7085.708
942671AE2-283 C
80/20
3.7323.732
316217AC1-145 C
80/20
0.4120.412
3151601KERR 3
80/20
1.8191.819
3151581KERR 1
80/20
0.650.65
936161AD2-022 C
80/20
12.80112.801
270197AC1-083 C
80/20
0.9970.997
24684605SMG4
80/20
3.2353.235
935171AD1-152 C
80/20
3.2243.224
3151021BRUNSWICKG1
80/20
25.36825.368
3151041BRUNSWICKG3
80/20
25.36825.368
316003AC1-222 C
80/20
1.9581.958
957481AF2-042 C
80/20
148.174148.174
24728405LEESVG
80/20
0.9740.974
3152441Z1-086 ST
80/20
55.85455.854
316359AB2-059 C OP
80/20
1.1351.135
316283AC2-100 C
80/20
2.3262.326
946301AF1-294 C
80/20
5.4265.426
316197AC1-042 C
80/20
0.3460.346
942461AE2-259 C
80/20
14.02314.023
934621AD1-088 C
80/20
24.38424.384
942001AE2-212 C
Adder
-2.1176470588235294-1.8
3151311EDGECMA
80/20
10.35810.358
3152661PLYWOOD A
80/20
2.3542.354
24684405SMG2
80/20
3.2353.235
316049AB1-081 C OP
80/20
0.9630.963
938531AE1-072 C
Adder
-16.896470588235296-14.362
316238AB2-078 C O1
80/20
0.5160.516
316322AB2-045 C
80/20
0.2670.267
3151611KERR 4
80/20
1.8191.819
3151621KERR 5
80/20
1.8191.819
316237AB2-079 C O1
80/20
0.5160.516
316222AC1-221 C
80/20
2.9052.905
934611AD1-087 C
80/20
3.2323.232
3152431Z1-086 GT3
80/20
32.07932.079
940641AE2-051 C
Adder
-22.240000000000002-18.904
958211AF2-115 C
80/20
3.33.3
3151531CLOVER1
80/20
32.84832.848
941031AE2-094 C
80/20
119.094119.094
964211AG1-282 C
Adder
-1.7882352941176471-1.52
3151641KERR 7
80/20
1.8191.819
313527AB2-043 C
80/20
0.8060.806
933291AC2-141 C
Adder
-33.98823529411765-28.89
316263AC1-034 C
80/20
4.5164.516
3151591KERR 2
80/20
1.8191.819
959311AF2-222 C
80/20
25.13225.132
316205AC1-080 C
80/20
0.5050.505
316123AC1-075 C
80/20
1.5121.512
942751AE2-291 C
80/20
13.51213.512
24684705SMG5
80/20
1.2291.229
3151561HALLBR1
80/20
1.2391.239
937481AD2-202 C
80/20
0.9380.938
3151031BRUNSWICKG2
80/20
25.36825.368
316240AF1-291 C
Adder
-2.031764705882353-1.727
944641AF1-129 C
Adder
-95.19529411764705-80.916
940601AE2-047 C
80/20
4.254.25
24684505SMG3
80/20
1.9881.988
3152411Z1-086 GT1
80/20
32.08832.088
3152421Z1-086 GT2
80/20
32.07932.079
316239AB2-077 C O1
80/20
0.5160.516
964791AG1-342 C
80/20
6.5026.502
940081AE1-250 C
80/20
13.65313.653
957601AF2-054 C
Adder
-1.8941176470588237-1.61
316129AC1-054 C
80/20
1.1861.186
3151631KERR 6
80/20
1.8191.819
316131AB2-060 C
80/20
2.3152.315
3138533PONTONDP
80/20
0.9780.978
941431AE2-140 C
80/20
14.14314.143
24684305SMG1
80/20
1.1751.175
3151541CLOVER2
80/20
32.5432.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.77474.774
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.81246.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.7578.757
LAGNLTFEXP_LAGN->PJM
CLTF
15.4915.49
SIGELTFEXP_SIGE->PJM
CLTF
0.550.55
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.6199.619
CBM South 2LTFEXP_CBM-S2->PJM
CBM
177.277177.277
CPLELTFEXP_CPLE->PJM
CLTF
20.16220.162
TVALTFEXP_TVA->PJM
CLTF
12.22612.226
NYPJM->LTFIMP_NY
CLTF
2.1882.188
LGEELTFEXP_LGEE->PJM
CLTF
2.8852.885
WECLTFEXP_WEC->PJM
CLTF
1.5251.525

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.59 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4175.62
MW Contribution:25.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936171AD2-023 C
80/20
7.4677.467
936261AD2-033 C
80/20
19.83719.837
316248AF1-058 C
80/20
0.6420.642
961791AG1-021 C
80/20
2.642.64
941801AE2-185 C
80/20
4.7984.798
963041AG1-153 C
80/20
17.24617.246
3151051BRUNSWICKS1
80/20
52.70552.705
964241AG1-285 C
80/20
19.39519.395
962561AG1-105 C
80/20
15.92115.921
316034AC1-036 C
80/20
0.3540.354
316118AC1-105 C
80/20
1.7691.769
943811AF1-049 C
80/20
9.4269.426
3144293JTRSVLE
80/20
0.6050.605
938741AE1-100 C
80/20
0.7290.729
941671AE2-166 C
80/20
5.7085.708
942671AE2-283 C
80/20
3.7323.732
316217AC1-145 C
80/20
0.4120.412
3151601KERR 3
80/20
1.8191.819
3151581KERR 1
80/20
0.650.65
936161AD2-022 C
80/20
12.80112.801
270197AC1-083 C
80/20
0.9970.997
24684605SMG4
80/20
3.2353.235
935171AD1-152 C
80/20
3.2243.224
3151021BRUNSWICKG1
80/20
25.36825.368
3151041BRUNSWICKG3
80/20
25.36825.368
316003AC1-222 C
80/20
1.9581.958
957481AF2-042 C
80/20
148.174148.174
24728405LEESVG
80/20
0.9740.974
3152441Z1-086 ST
80/20
55.85455.854
316359AB2-059 C OP
80/20
1.1351.135
316283AC2-100 C
80/20
2.3262.326
946301AF1-294 C
80/20
5.4265.426
316197AC1-042 C
80/20
0.3460.346
942461AE2-259 C
80/20
14.02314.023
934621AD1-088 C
80/20
24.38424.384
942001AE2-212 C
Adder
-2.1176470588235294-1.8
3151311EDGECMA
80/20
10.35810.358
3152661PLYWOOD A
80/20
2.3542.354
24684405SMG2
80/20
3.2353.235
316049AB1-081 C OP
80/20
0.9630.963
938531AE1-072 C
Adder
-16.896470588235296-14.362
316238AB2-078 C O1
80/20
0.5160.516
316322AB2-045 C
80/20
0.2670.267
3151611KERR 4
80/20
1.8191.819
3151621KERR 5
80/20
1.8191.819
316237AB2-079 C O1
80/20
0.5160.516
316222AC1-221 C
80/20
2.9052.905
934611AD1-087 C
80/20
3.2323.232
3152431Z1-086 GT3
80/20
32.07932.079
940641AE2-051 C
Adder
-22.240000000000002-18.904
958211AF2-115 C
80/20
3.33.3
3151531CLOVER1
80/20
32.84832.848
964211AG1-282 C
Adder
-1.7882352941176471-1.52
3151641KERR 7
80/20
1.8191.819
313527AB2-043 C
80/20
0.8060.806
933291AC2-141 C
Adder
-33.98823529411765-28.89
316263AC1-034 C
80/20
4.5164.516
3151591KERR 2
80/20
1.8191.819
959311AF2-222 C
80/20
25.13225.132
316205AC1-080 C
80/20
0.5050.505
316123AC1-075 C
80/20
1.5121.512
942751AE2-291 C
80/20
13.51213.512
24684705SMG5
80/20
1.2291.229
3151561HALLBR1
80/20
1.2391.239
937481AD2-202 C
80/20
0.9380.938
3151031BRUNSWICKG2
80/20
25.36825.368
316240AF1-291 C
Adder
-2.031764705882353-1.727
944641AF1-129 C
Adder
-95.19529411764705-80.916
3152411Z1-086 GT1
80/20
32.08832.088
3152421Z1-086 GT2
80/20
32.07932.079
940601AE2-047 C
80/20
4.254.25
24684505SMG3
80/20
1.9881.988
316239AB2-077 C O1
80/20
0.5160.516
964791AG1-342 C
80/20
6.5026.502
940081AE1-250 C
80/20
13.65313.653
957601AF2-054 C
Adder
-1.8941176470588237-1.61
316129AC1-054 C
80/20
1.1861.186
3151631KERR 6
80/20
1.8191.819
316131AB2-060 C
80/20
2.3152.315
3138533PONTONDP
80/20
0.9780.978
941431AE2-140 C
80/20
14.14314.143
24684305SMG1
80/20
1.1751.175
3151541CLOVER2
80/20
32.5432.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.77474.774
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.81246.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.7578.757
LAGNLTFEXP_LAGN->PJM
CLTF
15.4915.49
SIGELTFEXP_SIGE->PJM
CLTF
0.550.55
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.6199.619
CBM South 2LTFEXP_CBM-S2->PJM
CBM
177.277177.277
CPLELTFEXP_CPLE->PJM
CLTF
20.16220.162
TVALTFEXP_TVA->PJM
CLTF
12.22612.226
NYPJM->LTFIMP_NY
CLTF
2.1882.188
LGEELTFEXP_LGEE->PJM
CLTF
2.8852.885
WECLTFEXP_WEC->PJM
CLTF
1.5251.525

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.18 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3902.62
MW Contribution:14.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960081AF2-299 C
80/20
1.6731.673
936261AD2-033 C
Adder
11.4505882352941189.733
961791AG1-021 C
Adder
1.57882352941176471.342
938771AE1-103 C
80/20
2.5672.567
963041AG1-153 C
80/20
5.5365.536
3151051BRUNSWICKS1
80/20
16.91816.918
316170AC1-121 C
80/20
2.7242.724
944011AF1-069 C
80/20
13.03613.036
316045AC1-158 C2
80/20
19.41919.419
944591AF1-124 C
80/20
40.05140.051
944601AF1-125 C
80/20
39.29539.295
3151101ELIZAR3
80/20
2.8172.817
941591AE2-156 C
80/20
15.615.6
927021AC1-189 C
Adder
7.2364705882352946.151
926071AC1-086 C
Adder
18.5623529411764715.778
946281AF1-292 C
80/20
1.3851.385
964241AG1-285 C
Adder
11.0294117647058829.375
962561AG1-105 C
Adder
7.70470588235294156.549
316044AC1-158 C1
80/20
19.41919.419
3151091ELIZAR2
80/20
2.7332.733
316349AD2-085 C
80/20
2.9972.997
966621AG1-532 C
80/20
1.2551.255
316320Y1-086 C
80/20
0.1920.192
316388AE2-253 GEN
80/20
1.711.71
935171AD1-152 C
80/20
1.1991.199
3151021BRUNSWICKG1
80/20
8.1438.143
3151041BRUNSWICKG3
80/20
8.1438.143
934861AD1-115 C
Adder
2.8482352941176472.421
3152261N ANNA2
80/20
89.07389.073
942341AE2-247 C
80/20
1.2991.299
316246AF1-032 C
80/20
0.2480.248
316365AB2-100 C1
80/20
0.8620.862
957481AF2-042 C
80/20
51.00351.003
3151801S ANNAS2
80/20
1.3621.362
940431AE2-027 C
Adder
10.4682352941176488.898
316294AC1-161 C
80/20
4.314.31
944581AF1-123 C
80/20
39.90939.909
316185AD1-033 C
80/20
1.071.07
916191Z1-068 C
80/20
0.0380.038
941101AE2-104 C
80/20
2.9282.928
3147043LAWRENC
80/20
0.2730.273
940481AE2-033 C
80/20
14.89114.891
940541AE2-040 C
80/20
2.652.65
3152441Z1-086 ST
80/20
18.16818.168
966001AG1-469 C
80/20
1.9591.959
961611AG1-000B C
Adder
12.91058823529411910.974
316375AC2-012 C
80/20
1.1731.173
934501AD1-074 C
Adder
29.40470588235294324.994
961671AG1-007 C
Adder
0.80588235294117660.685
946301AF1-294 C
Adder
3.2458823529411762.759
942461AE2-259 C
Adder
8.7329411764705887.423
934621AD1-088 C
80/20
8.9588.958
208901BRIS G2
80/20
-3.11-3.11
316192AB2-158 C
80/20
3.6253.625
942001AE2-212 C
Adder
1.82117647058823541.548
316274AC1-208 C
Adder
7.857647058823536.679
962571AG1-106 C
Adder
2.40117647058823552.041
3151311EDGECMA
Adder
13.28823529411764811.295
957871AF2-081 C
80/20
8.7288.728
316405AF2-144 C
80/20
0.2940.294
3150651CHESTF6
Adder
14.84823529411764812.621
3150861SPRUNCD
80/20
0.1370.137
933981AD1-022 C
Adder
7.6458823529411766.499
938531AE1-072 C
80/20
15.34615.346
3150731STONECA
Adder
5.3258823529411774.527
935161AD1-151 C
Adder
12.7647058823529410.85
316083AB2-161 C
80/20
0.4780.478
958161AF2-110 C
80/20
1.1951.195
961941AG1-037 C
Adder
0.44235294117647060.376
934321AD1-056 C
Adder
5.4329411764705894.618
934331AD1-057 C
Adder
3.0305882352941182.576
958211AF2-115 C
Adder
1.97411764705882351.678
3151531CLOVER1
80/20
11.76811.768
208900BRIS G1
80/20
-2.628-2.628
3151761LOISA E
80/20
5.5225.522
3151771S ANNAG1
80/20
2.6512.651
3151791S ANNAG2
80/20
2.6512.651
3151781S ANNAS1
80/20
1.3621.362
316258AE1-075 C
80/20
0.3460.346
941031AE2-094 C
80/20
39.89839.898
3150831SPRUNCA
Adder
7.6235294117647066.48
3150841SPRUNCB
Adder
7.6235294117647066.48
3151081ELIZAR1
80/20
2.7822.782
313526AB2-022 C
80/20
0.3280.328
316017AA1-139 ULT1
80/20
0.9420.942
934611AD1-087 C
80/20
1.1591.159
3152431Z1-086 GT3
80/20
10.43410.434
316336AC2-165 C
80/20
9.6099.609
940641AE2-051 C
80/20
17.2917.29
316018AA1-139 ULT2
80/20
0.9420.942
3152251N ANNA1
80/20
89.03589.035
3150851SPRUNCC
80/20
0.1370.137
933291AC2-141 C
80/20
26.46526.465
3150921YORKTN3
Adder
90.5694117647058876.984
934521AD1-076 C
Adder
10.6788235294117659.077
934511AD1-075 C
Adder
7.3517647058823536.249
316263AC1-034 C
Adder
5.6858823529411774.833
316087AB2-174 C
80/20
1.0461.046
316321Z2-027 C
80/20
0.3170.317
959311AF2-222 C
Adder
14.6623529411764712.463
937481AD2-202 C
80/20
0.3360.336
3151031BRUNSWICKG2
80/20
8.1438.143
316240AF1-291 C
Adder
1.7435294117647061.482
944641AF1-129 C
Adder
81.5517647058823669.319
316036AC1-147 C
80/20
0.320.32
316305AF2-043 C
80/20
0.3030.303
3137643SOCKMAN
Adder
0.6317647058823530.537
3151741LOISA C
80/20
2.7082.708
3151721LOISA A
80/20
2.6942.694
939411AE1-173 C
80/20
87.96287.962
316381AD1-082 C
80/20
1.0891.089
3150991CHESPKB
80/20
0.6270.627
3156056W1-029WIND
80/20
0.6760.676
3152411Z1-086 GT1
80/20
10.43710.437
3152421Z1-086 GT2
80/20
10.43410.434
316233AE1-074 C
80/20
2.4172.417
943461AF1-017 C
80/20
1.1751.175
316311AC2-079 C
80/20
4.9964.996
964791AG1-342 C
Adder
3.06352941176470632.604
3151731LOISA B
80/20
2.7082.708
3151751LOISA D
80/20
2.7082.708
316313AB2-026 C
80/20
0.3770.377
316164AC1-076_C
80/20
1.1141.114
939191AE1-149 C
80/20
9.2629.262
3150981CHESPKA
80/20
0.3780.378
957861AF2-080 C
Adder
6.57294117647058855.587
316023AB2-100 C2
80/20
0.8620.862
316315AB2-025 C
80/20
0.3750.375
3138533PONTONDP
Adder
0.58470588235294120.497
3151541CLOVER2
80/20
11.65811.658
316257AC1-043 C
Adder
5.697647058823534.843
316254AC1-120 C
80/20
7.9327.932
316316AC1-027 C
80/20
0.2750.275
316303AF2-085
80/20
4.1844.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.96121.961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.49718.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.0623.062
LAGNLTFEXP_LAGN->PJM
CLTF
6.5316.531
SIGELTFEXP_SIGE->PJM
CLTF
0.1910.191
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.744.74
CBM South 2LTFEXP_CBM-S2->PJM
CBM
83.40383.403
CPLELTFEXP_CPLE->PJM
CLTF
9.9459.945
TVALTFEXP_TVA->PJM
CLTF
5.1955.195
NYPJM->LTFIMP_NY
CLTF
2.5322.532
LGEELTFEXP_LGEE->PJM
CLTF
0.9710.971
WECLTFEXP_WEC->PJM
CLTF
0.4740.474

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.07 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3866.79
MW Contribution:15.85
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
960081AF2-299 C
Adder
1.91411764705882351.627
936261AD2-033 C
Adder
12.4023529411764710.542
961791AG1-021 C
Adder
1.70000000000000021.445
938771AE1-103 C
Adder
3.162.686
963041AG1-153 C
Adder
5.7647058823529424.9
944011AF1-069 C
80/20
13.51813.518
316045AC1-158 C2
80/20
14.96214.962
966881AG1-559 C
Adder
2.3964705882352942.037
3150601CHESTF5
Adder
68.9811764705882458.634
944591AF1-124 C
80/20
50.39950.399
944601AF1-125 C
80/20
49.44749.447
3151101ELIZAR3
80/20
3.5723.572
941591AE2-156 C
80/20
19.79319.793
927021AC1-189 C
Adder
8.4188235294117647.156
926071AC1-086 C
Adder
21.50823529411764718.282
946281AF1-292 C
Adder
1.58470588235294121.347
964241AG1-285 C
Adder
11.97764705882352810.181
962561AG1-105 C
Adder
8.3588235294117657.105
316044AC1-158 C1
80/20
14.96214.962
939261AE1-157 C
Adder
13.77647058823529511.71
316169AC1-164 GEN
Adder
42.77176470588235436.356
3151091ELIZAR2
80/20
3.4653.465
316349AD2-085 C
Adder
3.79058823529411763.222
966621AG1-532 C
Adder
1.43529411764705881.22
3152261N ANNA2
80/20
55.34655.346
3150771HOPHCF1
80/20
2.6772.677
942341AE2-247 C
Adder
1.64235294117647061.396
957481AF2-042 C
Adder
53.64117647058823545.595
940431AE2-027 C
80/20
14.31814.318
316294AC1-161 C
80/20
5.4825.482
944581AF1-123 C
80/20
50.22150.221
941101AE2-104 C
Adder
3.683.128
940481AE2-033 C
Adder
17.08117647058823614.519
940541AE2-040 C
Adder
3.03764705882352942.582
927041AC1-191 C
Adder
10.0729411764705888.562
963611AG1-210 C
Adder
0.66705882352941170.567
961611AG1-000B C
Adder
17.55647058823529614.923
316375AC2-012 C
80/20
1.4881.488
934501AD1-074 C
Adder
35.6976470588235330.343
961671AG1-007 C
Adder
0.9317647058823530.792
946301AF1-294 C
Adder
3.4941176470588242.97
942461AE2-259 C
Adder
9.347.939
934621AD1-088 C
Adder
9.4482352941176488.031
316192AB2-158 C
80/20
2.1182.118
942001AE2-212 C
80/20
2.3972.397
962861AG1-135 C
Adder
6.222352941176475.289
943741AF1-042 C
Adder
2.9964705882352942.547
316274AC1-208 C
Adder
9.0917647058823537.728
962571AG1-106 C
Adder
2.7823529411764712.365
3151311EDGECMA
Adder
15.22352941176470512.94
957871AF2-081 C
Adder
10.989.333
3150651CHESTF6
80/20
20.66420.664
3150861SPRUNCD
80/20
0.1830.183
936591AD2-074 C
Adder
5.7258823529411764.867
933981AD1-022 C
Adder
9.2505882352941197.863
938531AE1-072 C
Adder
19.2929411764705916.399
3142366NRTHEST
80/20
0.20.2
3150731STONECA
80/20
7.6067.606
935161AD1-151 C
Adder
17.79176470588235415.123
958161AF2-110 C
Adder
1.50117647058823531.276
961941AG1-037 C
Adder
0.52705882352941180.448
934321AD1-056 C
Adder
6.2529411764705895.315
934331AD1-057 C
Adder
3.4882352941176472.965
958211AF2-115 C
Adder
2.12470588235294141.806
941031AE2-094 C
80/20
41.37341.373
3150831SPRUNCA
80/20
10.21910.219
3150841SPRUNCB
80/20
10.21910.219
966871AG1-558 C
Adder
2.50941176470588222.133
964211AG1-282 C
Adder
2.0317647058823531.727
3150801HOPHCF4
80/20
4.0644.064
3151081ELIZAR1
80/20
3.5273.527
316336AC2-165 C
Adder
10.1094117647058828.593
940641AE2-051 C
80/20
18.48818.488
943471AF1-018 C
Adder
7.4541176470588246.336
3152331SURRY 2
80/20
27.29427.294
3152251N ANNA1
80/20
55.32355.323
3150851SPRUNCC
80/20
0.1830.183
944631AF1-128 C
Adder
43.1623529411764736.688
933291AC2-141 C
80/20
33.66433.664
3150921YORKTN3
Adder
130.26705882352942110.727
934521AD1-076 C
Adder
12.96470588235294111.02
934511AD1-075 C
Adder
8.9247058823529427.586
316263AC1-034 C
Adder
6.5105882352941185.534
959311AF2-222 C
Adder
15.85294117647058913.475
316240AF1-291 C
80/20
2.3942.394
944641AF1-129 C
80/20
113.49113.49
3150781HOPHCF2
80/20
2.6772.677
3150761HOPPOLC
80/20
1.6841.684
3137643SOCKMAN
Adder
0.72705882352941180.618
966661AG1-536 C
Adder
5.5082352941176484.682
939411AE1-173 C
80/20
97.64897.648
3150991CHESPKB
80/20
0.7960.796
316233AE1-074 C
80/20
2.8192.819
940551AE2-041 C
Adder
7.4541176470588246.336
943461AF1-017 C
Adder
1.48588235294117641.263
316311AC2-079 C
Adder
6.3129411764705885.366
964791AG1-342 C
Adder
3.32117647058823542.823
316164AC1-076_C
80/20
0.9930.993
3143096IRON208
80/20
0.4840.484
958261AF2-120 C
Adder
6.4035294117647065.443
939191AE1-149 C
80/20
11.90511.905
957601AF2-054 C
Adder
2.2117647058823531.88
957861AF2-080 C
Adder
7.6458823529411766.499
3138533PONTONDP
Adder
0.62941176470588240.535
3150791HOPHCF3
80/20
2.6772.677
961951AG1-038 C
Adder
3.3117647058823532.815
316303AF2-085
80/20
4.3634.363
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.65727.657
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.08222.082
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.7473.747
LAGNLTFEXP_LAGN->PJM
CLTF
7.6777.677
SIGELTFEXP_SIGE->PJM
CLTF
0.2370.237
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.2865.286
CBM South 2LTFEXP_CBM-S2->PJM
CBM
94.17394.173
CPLELTFEXP_CPLE->PJM
CLTF
11.08811.088
TVALTFEXP_TVA->PJM
CLTF
6.1396.139
NYPJM->LTFIMP_NY
CLTF
2.8062.806
LGEELTFEXP_LGEE->PJM
CLTF
1.2221.222
WECLTFEXP_WEC->PJM
CLTF
0.5950.595

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.55 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4631.32
MW Contribution:25.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926072AC1-086 E
Adder
8.9094117647058837.573
960081AF2-299 C
Adder
1.76235294117647071.498
3145413WATKINS
Adder
0.64235294117647070.546
936261AD2-033 C
Adder
12.02117647058823610.218
962562AG1-105 E
Adder
5.3929411764705884.584
961791AG1-021 C
Adder
1.65764705882352951.409
938771AE1-103 C
Adder
2.72117647058823582.313
963041AG1-153 C
Adder
5.7788235294117654.912
316170AC1-121 C
50/50
2.7692.769
944011AF1-069 C
50/50
13.59813.598
316045AC1-158 C2
50/50
19.48619.486
925332AB2-190 E
Adder
6.8164705882352945.794
927226AC1-216 E
Adder
6.5917647058823535.603
944591AF1-124 C
Adder
42.5247058823529436.146
944601AF1-125 C
Adder
41.7211764705882435.463
941591AE2-156 C
Adder
16.57647058823529614.09
936666AD2-085 E
Adder
5.195294117647064.416
926071AC1-086 C
Adder
19.57647058823529616.64
946281AF1-292 C
Adder
1.45882352941176461.24
918512AA1-065 E OP
Adder
5.1070588235294124.341
934502AD1-074 E
Adder
15.85176470588235313.474
934512AD1-075 E
Adder
3.96235294117647063.368
924516AB2-100 E1
Adder
2.74588235294117672.334
966621AG1-532 C
Adder
1.32117647058823541.123
919153AA1-139 E2
Adder
3.78941176470588253.221
924022AB2-043 E O1
Adder
4.7941176470588244.075
3147223TWITTYS
Adder
0.87882352941176480.747
959312AF2-222 E
Adder
10.3129411764705888.766
934861AD1-115 C
Adder
2.92.465
3152261N ANNA2
50/50
89.60989.609
940642AE2-051 E
50/50
12.05212.052
942341AE2-247 C
Adder
1.38000000000000011.173
943462AF1-017 E
Adder
2.03764705882352941.732
958162AF2-110 E
Adder
2.01764705882352931.715
316141AB2-099 E
Adder
0.234117647058823540.199
923994AB2-040_E
Adder
5.76941176470588254.904
316088AB2-174 E
Adder
6.1235294117647065.205
924322AB2-079 E O1
Adder
1.23529411764705891.05
946302AF1-294 E
Adder
2.88470588235294122.452
957481AF2-042 C
Adder
53.3270588235294245.328
3151801S ANNAS2
50/50
1.381.38
942002AE2-212 E
Adder
1.2952941176470591.101
940431AE2-027 C
Adder
11.2058823529411789.525
944581AF1-123 C
Adder
42.37411764705882436.018
941101AE2-104 C
Adder
3.10941176470588232.643
923263AB1-132 E OP
Adder
5.697647058823534.843
940481AE2-033 C
Adder
15.6752941176470613.324
940482AE2-033 E
Adder
10.5670588235294118.982
940541AE2-040 C
Adder
2.78823529411764742.37
924312AB2-078 E O1
Adder
1.23529411764705891.05
925612AC1-036 E
Adder
0.79294117647058830.674
966001AG1-469 C
50/50
1.9871.987
925672AC1-043 E
Adder
9.4635294117647078.044
926740AC1-158 E2
50/50
50.96750.967
961611AG1-000B C
Adder
13.8152941176470611.743
934501AD1-074 C
Adder
31.13882352941176626.468
924517AB2-100 E2
Adder
2.74588235294117672.334
937226AE2-253 E
Adder
5.4188235294117654.606
946301AF1-294 C
Adder
3.4070588235294122.896
935172AD1-152 E
Adder
5.1847058823529414.407
942461AE2-259 C
Adder
9.1658823529411777.791
934621AD1-088 C
Adder
9.3717647058823547.966
957482AF2-042 E
Adder
35.55176470588235630.219
208901BRIS G2
50/50
-3.356-3.356
958502AF2-144 E
Adder
1.2588235294117651.07
316192AB2-158 C
50/50
3.6573.657
942001AE2-212 C
Adder
1.94235294117647061.651
939192AE1-149 E
Adder
6.5694117647058825.584
939312AE1-162 E
Adder
1.27764705882352961.086
934065AD1-033 E
Adder
4.6541176470588243.956
943172AE2-346 E
Adder
0.56117647058823530.477
917332KELFORD E
Adder
1.51764705882352961.29
925122AB2-169 E
Adder
5.2764705882352954.485
934522AD1-076 E
Adder
5.7635294117647064.899
940492AE2-034 E
Adder
2.85176470588235282.424
933981AD1-022 C
Adder
8.0941176470588236.88
900672V4-068 E
Adder
0.33058823529411770.281
938531AE1-072 C
Adder
16.29411764705882213.85
924302AB2-077 E O1
Adder
1.23529411764705891.05
3145393UNCAMP
Adder
5.65176470588235354.804
926486AC1-120 E
50/50
4.1534.153
935161AD1-151 C
Adder
13.69411764705882511.64
932046AC2-012 E
Adder
12.12705882352941210.308
958161AF2-110 C
Adder
1.26823529411764711.078
960082AF2-299 E
Adder
1.17529411764705880.999
916042Z1-036 E
Adder
26.4694117647058822.499
923832AB2-022 E
Adder
1.14941176470588240.977
964241AG1-285 C
Adder
11.5811764705882349.844
962561AG1-105 C
Adder
8.0894117647058836.876
958212AF2-115 E
Adder
1.76470588235294111.5
938772AE1-103 E
Adder
3.75764705882352963.194
963042AG1-153 E
Adder
8.6682352941176477.368
925022AB2-158 E
50/50
9.7219.721
316044AC1-158 C1
50/50
19.48619.486
944592AF1-124 E
Adder
97.3823529411764882.775
944582AF1-123 E
Adder
97.0317647058823782.477
316349AD2-085 C
Adder
3.1835294117647062.706
935112AD1-144 E
Adder
0.85764705882352940.729
961942AG1-037 E
Adder
0.311764705882352940.265
961941AG1-037 C
Adder
0.46705882352941180.397
923852AB2-025 E
Adder
1.1282352941176470.959
936262AD2-033 E
Adder
8.0141176470588256.812
958211AF2-115 C
Adder
2.0717647058823531.761
208900BRIS G1
50/50
-2.836-2.836
3151761LOISA E
50/50
5.5965.596
3151771S ANNAG1
50/50
2.6852.685
3151791S ANNAG2
50/50
2.6852.685
3151781S ANNAS1
50/50
1.381.38
923862AB2-026 E
Adder
1.28117647058823541.089
941031AE2-094 C
50/50
41.61841.618
941032AE2-094 E
50/50
18.6418.64
3150831SPRUNCA
Adder
8.1435294117647056.922
3150841SPRUNCB
Adder
8.1435294117647056.922
939412AE1-173 E
Adder
61.5211764705882452.293
926662AC1-147 E
Adder
1.22588235294117661.042
916192Z1-068 E
Adder
1.74235294117647071.481
957492AF2-043 E
Adder
1.31882352941176471.121
933982AD1-022 E
Adder
4.4070588235294123.746
3145946PLYMOUTH TP
Adder
0.29882352941176470.254
927146AC1-208 E
Adder
1.16941176470588240.994
934612AD1-087 E
Adder
3.50941176470588272.983
934622AD1-088 E
Adder
4.5117647058823533.835
316336AC2-165 C
Adder
10.0588235294117668.55
926004AC1-076_E
50/50
6.486.48
940641AE2-051 C
50/50
18.07818.078
316084AB2-161 E
Adder
5.0917647058823544.328
316274AC1-208 C
Adder
8.2905882352941187.047
962571AG1-106 C
Adder
2.53176470588235342.152
918492AA1-063AE OP
Adder
3.80117647058823543.231
957871AF2-081 C
Adder
9.2670588235294127.877
961792AG1-021 E
Adder
1.4117647058823531.2
937482AD2-202 E
Adder
1.02705882352941180.873
3145506HICKORY
Adder
2.02235294117647071.719
946262AF1-291 E
Adder
1.24470588235294131.058
3150651CHESTF6
Adder
15.92588235294117813.537
933292AC2-141 E
Adder
12.0070588235294110.206
934576AD1-082 E
Adder
4.0564705882352943.448
944602AF1-125 E
Adder
95.5082352941176581.182
943612AF1-032 E
Adder
0.85764705882352940.729
926214AC1-099 E
Adder
1.1082352941176470.942
932632AC2-084 E
Adder
2.96705882352941152.522
962572AG1-106 E
Adder
1.1082352941176470.942
957872AF2-081 E
Adder
3.9717647058823533.376
924162AB2-060 E OP
Adder
3.95764705882352933.364
964242AG1-285 E
Adder
7.7211764705882356.563
934862AD1-115 E
Adder
4.73176470588235354.022
938562AE1-075 E
Adder
1.0917647058823530.928
3152251N ANNA1
50/50
89.57189.571
938552AE1-074 E
Adder
1.28235294117647071.09
926755AC1-161 E
Adder
12.0070588235294110.206
933291AC2-141 C
Adder
28.12941176470588223.91
925522AC1-027 E
Adder
1.1282352941176470.959
941102AE2-104 E
Adder
4.9423529411764714.201
3145256KINGFORK
Adder
0.92470588235294130.786
934521AD1-076 C
Adder
11.3094117647058829.613
934511AD1-075 C
Adder
7.7847058823529426.617
919692AA2-053 E OP
Adder
3.93176470588235333.342
923573AB1-173 E OP
Adder
3.07647058823529432.615
3145723EMPORIA
Adder
0.405882352941176470.345
920042AA2-088 E OP
Adder
9.8670588235294128.387
925785AC1-054 E
Adder
3.18705882352941172.709
919152AA1-139 E1
Adder
3.78941176470588253.221
959311AF2-222 C
Adder
15.39294117647058813.084
926502AC1-121 E
50/50
1.3031.303
316240AF1-291 C
Adder
1.86705882352941191.587
944641AF1-129 C
Adder
87.4717647058823574.351
924814AB2-134 E
Adder
10.7988235294117659.179
942342AE2-247 E
Adder
1.90588235294117661.62
920692AA2-178 E
Adder
3.8023529411764713.232
966622AG1-532 E
Adder
0.88117647058823530.749
917122Z2-027 E
Adder
1.24470588235294131.058
3146326AYDLETT TAP
Adder
1.25764705882352931.069
938532AE1-072 E
Adder
8.4941176470588247.22
3147133PAMPLIN
Adder
0.91529411764705890.778
966002AG1-469 E
50/50
0.9930.993
926739AC1-158 E1
50/50
50.96750.967
316233AE1-074 C
Adder
2.5458823529411772.164
935162AD1-151 E
Adder
9.1294117647058827.76
943461AF1-017 C
Adder
1.2482352941176471.061
316311AC2-079 C
Adder
5.3070588235294124.511
932596AC2-079 E
Adder
8.6588235294117667.36
3137643SOCKMAN
Adder
0.66588235294117650.566
913392Y1-086 E
Adder
2.03647058823529431.731
933502AC2-165 E
Adder
7.5705882352941176.435
3151741LOISA C
50/50
2.7452.745
3151721LOISA A
50/50
2.7312.731
940432AE2-027 E
Adder
7.4705882352941186.35
939411AE1-173 C
Adder
92.2811764705882478.439
934012AD1-025 E
Adder
8.5352941176470597.255
926206AC1-098 E
Adder
3.35647058823529452.853
901082W1-029 E
Adder
29.54000000000000325.109
942462AE2-259 E
Adder
6.1105882352941175.194
3151731LOISA B
50/50
2.7452.745
3151751LOISA D
50/50
2.7452.745
3143316POE
Adder
1.28823529411764711.095
316164AC1-076_C
50/50
1.1311.131
939191AE1-149 C
Adder
9.8529411764705898.375
946282AF1-292 E
Adder
0.97294117647058820.827
3138533PONTONDP
Adder
0.61411764705882350.522
316257AC1-043 C
Adder
5.84.93
316254AC1-120 C
50/50
8.0618.061
944012AF1-069 E
50/50
5.2835.283
316303AF2-085
50/50
4.3644.364
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.22125.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.23820.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.4183.418
LAGNLTFEXP_LAGN->PJM
CLTF
7.0687.068
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7645.764
SIGELTFEXP_SIGE->PJM
CLTF
0.2140.214
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.0035.003
CBM South 2LTFEXP_CBM-S2->PJM
CBM
88.42988.429
CPLELTFEXP_CPLE->PJM
CLTF
10.49610.496
TVALTFEXP_TVA->PJM
CLTF
5.6275.627
O66PJM->LTFIMP_O-066
CMTX_NF
36.7236.72
NYPJM->LTFIMP_NY
CLTF
2.7142.714
LGEELTFEXP_LGEE->PJM
CLTF
1.0981.098
WECLTFEXP_WEC->PJM
CLTF
0.5410.541

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4234.7
MW Contribution:22.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316049AB1-081 C OP
80/20
0.9230.923
938531AE1-072 C
Adder
-16.01294117647059-13.611
316238AB2-078 C O1
80/20
0.4550.455
316322AB2-045 C
80/20
0.2270.227
3151601KERR 3
80/20
1.6151.615
3151581KERR 1
80/20
0.5770.577
936161AD2-022 C
80/20
12.15912.159
270197AC1-083 C
80/20
0.9340.934
24684605SMG4
80/20
3.0033.003
935171AD1-152 C
80/20
2.8492.849
3151021BRUNSWICKG1
80/20
25.15625.156
3151041BRUNSWICKG3
80/20
25.15625.156
3152661PLYWOOD A
80/20
2.0932.093
24684405SMG2
80/20
3.0033.003
3151611KERR 4
80/20
1.6151.615
3151621KERR 5
80/20
1.6151.615
316237AB2-079 C O1
80/20
0.4550.455
316222AC1-221 C
80/20
2.6372.637
934611AD1-087 C
80/20
2.842.84
3152431Z1-086 GT3
80/20
33.46433.464
940641AE2-051 C
Adder
-21.040000000000003-17.884
940601AE2-047 C
80/20
4.0274.027
24684505SMG3
80/20
1.8451.845
3151641KERR 7
80/20
1.6151.615
313527AB2-043 C
80/20
0.7110.711
933291AC2-141 C
Adder
-32.203529411764706-27.373
316263AC1-034 C
80/20
4.3284.328
3151591KERR 2
80/20
1.6151.615
959311AF2-222 C
80/20
22.05622.056
316205AC1-080 C
80/20
0.4520.452
316123AC1-075 C
80/20
1.3531.353
942751AE2-291 C
80/20
12.11212.112
24684705SMG5
80/20
1.1411.141
3151561HALLBR1
80/20
1.1241.124
937481AD2-202 C
80/20
0.8240.824
3151031BRUNSWICKG2
80/20
25.15625.156
316240AF1-291 C
Adder
-1.9317647058823528-1.642
944641AF1-129 C
Adder
-90.49176470588236-76.918
316359AB2-059 C OP
80/20
1.0881.088
316283AC2-100 C
80/20
2.1162.116
946301AF1-294 C
80/20
4.7464.746
316197AC1-042 C
80/20
0.3150.315
942461AE2-259 C
80/20
12.19912.199
934621AD1-088 C
80/20
21.36821.368
942001AE2-212 C
Adder
-2.010588235294118-1.709
3152411Z1-086 GT1
80/20
33.47333.473
3152421Z1-086 GT2
80/20
33.46433.464
24728405LEESVG
80/20
0.8940.894
3152441Z1-086 ST
80/20
58.26658.266
316239AB2-077 C O1
80/20
0.4550.455
964791AG1-342 C
80/20
5.7665.766
940081AE1-250 C
80/20
12.86112.861
957601AF2-054 C
Adder
-1.8-1.53
316003AC1-222 C
80/20
1.7441.744
957481AF2-042 C
80/20
129.887129.887
964241AG1-285 C
80/20
17.07617.076
962561AG1-105 C
80/20
14.10814.108
316034AC1-036 C
80/20
0.3110.311
316118AC1-105 C
80/20
1.5721.572
943811AF1-049 C
80/20
8.9298.929
3144293JTRSVLE
80/20
0.5290.529
938741AE1-100 C
80/20
0.690.69
941671AE2-166 C
80/20
5.45.4
942671AE2-283 C
80/20
3.3963.396
316217AC1-145 C
80/20
0.3750.375
316129AC1-054 C
80/20
1.0481.048
3151631KERR 6
80/20
1.6151.615
316131AB2-060 C
80/20
2.042.04
3138533PONTONDP
80/20
0.8550.855
941431AE2-140 C
80/20
13.39313.393
24684305SMG1
80/20
1.0911.091
3151541CLOVER2
80/20
28.59828.598
936171AD2-023 C
80/20
7.0937.093
936261AD2-033 C
80/20
17.43217.432
316248AF1-058 C
80/20
0.5710.571
961791AG1-021 C
80/20
2.3092.309
941801AE2-185 C
80/20
4.3664.366
963041AG1-153 C
80/20
17.10317.103
3151051BRUNSWICKS1
80/20
52.26552.265
944011AF1-069 C
80/20
45.1645.16
958211AF2-115 C
80/20
2.8862.886
3151531CLOVER1
80/20
28.86928.869
941031AE2-094 C
80/20
138.215138.215
964211AG1-282 C
Adder
-1.7011764705882353-1.446
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.06671.066
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.76444.764
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.3488.348
LAGNLTFEXP_LAGN->PJM
CLTF
14.84614.846
SIGELTFEXP_SIGE->PJM
CLTF
0.5240.524
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.2639.263
CBM South 2LTFEXP_CBM-S2->PJM
CBM
170.641170.641
CPLELTFEXP_CPLE->PJM
CLTF
19.41719.417
TVALTFEXP_TVA->PJM
CLTF
11.71211.712
NYPJM->LTFIMP_NY
CLTF
2.1082.108
LGEELTFEXP_LGEE->PJM
CLTF
2.7422.742
WECLTFEXP_WEC->PJM
CLTF
1.451.45

Details for AG1-285 TP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG1-285 TP-3CHASCTY 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 15832_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.58 %
Rating:349.0 MVA
Rating Type:C
MVA to Mitigate:375.45
MW Contribution:166.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3147223TWITTYS
50/50
5.7095.709
959312AF2-222 E
50/50
66.99766.997
925612AC1-036 E
50/50
5.155.15
964241AG1-285 C
50/50
74.99774.997
316034AC1-036 C
50/50
1.4011.401
942461AE2-259 C
50/50
59.99759.997
964242AG1-285 E
50/50
49.99849.998
959311AF2-222 C
50/50
99.99699.996
3147133PAMPLIN
50/50
5.9755.975
942462AE2-259 E
50/50
39.99839.998
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0020.002
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0080.008
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0040.004
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0050.005
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0020.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0120.012
MDUPJM->LTFIMP_MDU
CLTF
00
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0030.003
O66PJM->LTFIMP_O-066
CMTX_NF
0.030.03
NYPJM->LTFIMP_NY
CLTF
0.0020.002
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0090.009
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0030.003

Details for AG1-285 TP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG1-285 TP-3CHASCTY 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: FARMVIL L432_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.57 %
Rating:349.0 MVA
Rating Type:C
MVA to Mitigate:375.41
MW Contribution:166.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3147223TWITTYS
50/50
5.7095.709
959312AF2-222 E
50/50
66.99766.997
925612AC1-036 E
50/50
5.155.15
964241AG1-285 C
50/50
74.99774.997
316034AC1-036 C
50/50
1.4011.401
942461AE2-259 C
50/50
59.99759.997
964242AG1-285 E
50/50
49.99849.998
959311AF2-222 C
50/50
99.99699.996
3147133PAMPLIN
50/50
5.9755.975
942462AE2-259 E
50/50
39.99839.998
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0020.002
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0080.008
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0040.004
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0050.005
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0020.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0120.012
MDUPJM->LTFIMP_MDU
CLTF
00
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0030.003
O66PJM->LTFIMP_O-066
CMTX_NF
0.030.03
NYPJM->LTFIMP_NY
CLTF
0.0020.002
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0090.009
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0030.003
CONTINGENCY 'DVP_P4-6: CHASE C T342_SRT-A'
 OPEN BUS 313527   /*AB2-043 C      0.6
 OPEN BUS 313528   /*AB2-043 COL   34.5
 OPEN BUS 313529   /*3BLUESTONE   115.0
 OPEN BUS 314267   /*3CHASCTY2    115.0
 OPEN BUS 314518   /*3CHASC_1     115.0
 OPEN BUS 314681   /*3CHASCTY     115.0
 OPEN BUS 924022   /*AB2-043 E O1   0.6
END
CONTINGENCY 'DVP_P1-2: LN 1012_SRT-A-4'
 OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1   /*AG1-285 TP   115.0 - 3CHASCTY     115.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 246_SRT-A'
 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1   /*6SUFFOLK     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1   /*6EARLEYS     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1   /*6NUCO TP     230.0 - 6NUCOR       230.0
 OPEN BUS 314575                                   /*6NUCO TP     230.0
 OPEN BUS 314590                                   /*6NUCOR       230.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A'
 OPEN BRANCH FROM BUS 304183 TO BUS 314935 CKT 1   /*8WAKE 500 TT 500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314063 TO BUS 314916 CKT 1                /*6MORRSVL     230.0 - 8MORRSVL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BUS 314897                                                /*8MORRS_1     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 568T575_SRT-A'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1   /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1   /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 314940 TO BUS 941030 CKT 1   /*8ROGERS RD   500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 15832_SRT-A'
 OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1   /*3FLAT CREEK  115.0 - 3LONEPN      115.0
 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1   /*3FLAT CREEK  115.0 - 3MORAN       115.0
 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1   /*3LONEPINE_1  115.0 - 3LONEPN      115.0
 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1   /*3FARMVIL     115.0 - 3MORAN       115.0
 OPEN BUS 313755                                   /*3FLAT CREEK  115.0
 OPEN BUS 314519                                   /*3LONEPINE_1  115.0
 OPEN BUS 314691                                   /*3FARMVIL     115.0
 OPEN BUS 314707                                   /*3MORAN       115.0
END
CONTINGENCY 'DVP_P4-5: FARMVIL L432_SRT-A-1'
 OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1   /*6PRINCE EDW  230.0 - 6BRIERY      230.0
 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1   /*6PRINCE EDW  230.0 - 6FARMVIL     230.0
 OPEN BRANCH FROM BUS 314268 TO BUS 313996 CKT 1   /*6BRIERY      230.0 - 6FINNEYWOOD  230.0
 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1   /*3FARMVIL     115.0 - 6FARMVIL     230.0
 OPEN BUS 313802                                   /*6PRINCE EDW  230.0
 OPEN BUS 314268                                   /*6BRIERY      230.0
 OPEN BUS 314691                                   /*3FARMVIL     115.0
END
314691 to 314692 ckt 1
314691 to 314692 ckt 2
314726 to 314691 ckt 1
314282 to 314285 ckt 1
314563 to 940480 ckt 1
314435 to 314282 ckt 1
314902 to 314914 ckt 1
314914 to 314918 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314936 to 314902 ckt 1
314934 to 314916 ckt 1
941030 to 314902 ckt 1
964240 to 314681 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P1-2: LN 235_SRT-A
OPAC121.52 %182.64B221.9540.3
GD1DVP
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
DVP_P1-2: LN 1012_SRT-A-1
OPAC127.32 %205.86B262.1166.99
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC109.21 %678.68B741.1830.09
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC108.15 %678.68B734.0330.09
GD1DVP
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
OPAC107.58 %571.52B614.8216.61
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC105.97 %661.76B701.2928.05
GD1DVP
6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
OPAC108.24 %571.52B618.6116.61
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC108.64 %661.76B718.9128.05
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC102.38 %661.76B677.5228.05
GD1DVP
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
OPAC107.58 %571.52B614.8116.61
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Base Case
OPAC104.12 %3220.44A3352.9929.71
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
OPAC126.88 %1058.16B1342.559.31
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
OPAC110.47 %3220.44B3557.6637.07
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
OPAC108.69 %4070.2B4423.7258.05
GD1DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC106.42 %2442.12B2598.9323.85
GD1DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
OPAC105.93 %4070.2B4311.7150.59

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 235_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:121.52 %
Rating:182.64 MVA
Rating Type:B
MVA to Mitigate:221.95
MW Contribution:40.3
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 235_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:149.01 %
Rating:182.64 MVA
Rating Type:B
MVA to Mitigate:272.15
MW Contribution:56.16
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
4.2384.238
961792AG1-021 E
50/50
3.613.61
964791AG1-342 C
Adder
1.70117647058823531.446
964792AG1-342 E
Adder
1.13411764705882350.964
3138533PONTONDP
50/50
1.571.57
3144293JTRSVLE
50/50
0.9750.975
3147133PAMPLIN
50/50
2.4852.485
926274AC1-105 E
Adder
1.0752941176470590.914
943902AF1-058 E
Adder
0.414117647058823530.352
959311AF2-222 C
50/50
24.13324.133
959312AF2-222 E
50/50
16.16916.169
316131AB2-060 C
50/50
1.1311.131
924162AB2-060 E OP
50/50
3.2583.258
924302AB2-077 E O1
50/50
0.9010.901
924312AB2-078 E O1
50/50
0.9010.901
924322AB2-079 E O1
50/50
0.9010.901
925612AC1-036 E
50/50
1.1371.137
941011AE2-092 C
Adder
-4.856470588235294-4.128
946301AF1-294 C
50/50
8.7128.712
946302AF1-294 E
50/50
7.3787.378
958211AF2-115 C
50/50
5.2985.298
958212AF2-115 E
50/50
4.5134.513
3147223TWITTYS
50/50
1.261.26
936261AD2-033 C
50/50
18.4818.48
936262AD2-033 E
50/50
12.3212.32
934621AD1-088 C
Adder
2.9611764705882352.517
934622AD1-088 E
Adder
1.42588235294117641.212
316034AC1-036 C
50/50
0.310.31
316237AB2-079 C O1
50/50
0.2210.221
316238AB2-078 C O1
50/50
0.2210.221
316239AB2-077 C O1
50/50
0.2210.221
313527AB2-043 C
50/50
0.3610.361
924022AB2-043 E O1
50/50
3.623.62
962561AG1-105 C
Adder
4.583.893
962562AG1-105 E
Adder
3.05294117647058852.595
964241AG1-285 C
50/50
8.3818.381
964242AG1-285 E
50/50
5.5885.588
938821AE1-108 C
Adder
-5.455294117647059-4.637
942461AE2-259 C
50/50
33.29833.298
942462AE2-259 E
50/50
22.19822.198
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.7150.715
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.1372.137
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.0592.059
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.68211.682
G-007PJM->LTFIMP_G-007
CMTX_NF
0.2090.209
NYPJM->LTFIMP_NY
CLTF
0.1040.104
LGEELTFEXP_LGEE->PJM
CLTF
0.0840.084
WECLTFEXP_WEC->PJM
CLTF
0.0450.045
CPLELTFEXP_CPLE->PJM
CLTF
1.51.5
TVALTFEXP_TVA->PJM
CLTF
0.5920.592
MECLTFEXP_MEC->PJM
CLTF
0.3150.315
LAGNLTFEXP_LAGN->PJM
CLTF
0.7670.767
SIGELTFEXP_SIGE->PJM
CLTF
0.0180.018
O66PJM->LTFIMP_O-066
CMTX_NF
1.3381.338

Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1012_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:127.32 %
Rating:205.86 MVA
Rating Type:B
MVA to Mitigate:262.1
MW Contribution:166.99
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1012_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:127.32 %
Rating:205.86 MVA
Rating Type:B
MVA to Mitigate:262.1
MW Contribution:166.99
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3147133PAMPLIN
50/50
5.9755.975
959311AF2-222 C
50/50
99.99699.996
959312AF2-222 E
50/50
66.99766.997
925612AC1-036 E
50/50
5.155.15
3147223TWITTYS
50/50
5.7095.709
316034AC1-036 C
50/50
1.4051.405
942461AE2-259 C
50/50
59.99759.997
942462AE2-259 E
50/50
39.99839.998
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0040.004
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0030.003
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0050.005
NYPJM->LTFIMP_NY
CLTF
0.0020.002
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0090.009
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0030.003
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0020.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0120.012
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0020.002
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0080.008
O66PJM->LTFIMP_O-066
CMTX_NF
0.030.03
MDUPJM->LTFIMP_MDU
CLTF
00

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.21 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:741.18
MW Contribution:30.09
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.95 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:773.37
MW Contribution:32.59
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
2.4812.481
961792AG1-021 E
50/50
2.1132.113
964791AG1-342 C
Adder
2.1235294117647061.805
964792AG1-342 E
Adder
1.41647058823529411.204
3138533PONTONDP
50/50
0.9190.919
3144293JTRSVLE
50/50
0.5710.571
3147133PAMPLIN
50/50
1.4571.457
925785AC1-054 E
Adder
1.48235294117647071.26
926274AC1-105 E
Adder
1.48352941176470581.261
943902AF1-058 E
Adder
0.65294117647058840.555
959311AF2-222 C
50/50
18.01818.018
959312AF2-222 E
50/50
12.07212.072
316131AB2-060 C
50/50
1.121.12
924162AB2-060 E OP
50/50
3.2253.225
924302AB2-077 E O1
50/50
0.9550.955
924312AB2-078 E O1
50/50
0.9550.955
924322AB2-079 E O1
50/50
0.9550.955
925612AC1-036 E
50/50
0.8890.889
941011AE2-092 C
Adder
8.222352941176476.989
941012AE2-092 E
Adder
5.48117647058823554.659
946301AF1-294 C
50/50
5.15.1
946302AF1-294 E
50/50
4.3194.319
957481AF2-042 C
Adder
27.58352941176470823.446
957482AF2-042 E
Adder
18.38941176470588315.631
958131AF2-107 C
Adder
2.38941176470588262.031
958132AF2-107 E
Adder
1.30941176470588231.113
958211AF2-115 C
50/50
3.1013.101
958212AF2-115 E
50/50
2.6422.642
924032AB2-045 E
50/50
3.7663.766
933502AC2-165 E
50/50
24.49824.498
3151911BEARGRDN G1
50/50
17.79517.795
3151921BEARGRDN G2
50/50
17.79517.795
3147223TWITTYS
50/50
0.9860.986
936261AD2-033 C
50/50
13.17213.172
936262AD2-033 E
50/50
8.7818.781
934621AD1-088 C
50/50
6.6736.673
934622AD1-088 E
50/50
3.2133.213
3151931BEARGRDN S1
50/50
23.02123.021
316034AC1-036 C
50/50
0.2430.243
316237AB2-079 C O1
50/50
0.2340.234
316238AB2-078 C O1
50/50
0.2340.234
316239AB2-077 C O1
50/50
0.2340.234
316322AB2-045 C
50/50
0.840.84
316336AC2-165 C
50/50
32.5532.55
927264AC1-222 E
Adder
1.98117647058823531.684
313527AB2-043 C
50/50
0.3760.376
924022AB2-043 E O1
50/50
3.7783.778
962561AG1-105 C
50/50
5.5115.511
962562AG1-105 E
50/50
3.6743.674
964241AG1-285 C
50/50
9.9699.969
964242AG1-285 E
50/50
6.6466.646
934612AD1-087 E
Adder
1.95058823529411751.658
935172AD1-152 E
Adder
2.81529411764705852.393
937482AD2-202 E
Adder
0.57058823529411760.485
938821AE1-108 C
50/50
16.62316.623
938822AE1-108 E
50/50
7.9317.931
942461AE2-259 C
50/50
17.67317.673
942462AE2-259 E
50/50
11.78211.782
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3441.344
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.0390.039
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.6382.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.54721.547
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6760.676
NYPJM->LTFIMP_NY
CLTF
0.3510.351
LGEELTFEXP_LGEE->PJM
CLTF
0.0240.024
WECLTFEXP_WEC->PJM
CLTF
0.0090.009
CPLELTFEXP_CPLE->PJM
CLTF
2.8232.823
TVALTFEXP_TVA->PJM
CLTF
0.8870.887
MECLTFEXP_MEC->PJM
CLTF
0.2490.249
LAGNLTFEXP_LAGN->PJM
CLTF
1.161.16
SIGELTFEXP_SIGE->PJM
CLTF
0.0110.011
O66PJM->LTFIMP_O-066
CMTX_NF
4.3344.334

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.15 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:734.03
MW Contribution:30.09
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.89 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:766.15
MW Contribution:32.59
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
2.4812.481
961792AG1-021 E
50/50
2.1132.113
964791AG1-342 C
Adder
2.1235294117647061.805
964792AG1-342 E
Adder
1.41647058823529411.204
3138533PONTONDP
50/50
0.9190.919
3144293JTRSVLE
50/50
0.5710.571
3147133PAMPLIN
50/50
1.4571.457
925785AC1-054 E
Adder
1.48235294117647071.26
926274AC1-105 E
Adder
1.48352941176470581.261
943902AF1-058 E
Adder
0.65294117647058840.555
959311AF2-222 C
50/50
18.01818.018
959312AF2-222 E
50/50
12.07212.072
316131AB2-060 C
50/50
1.121.12
924162AB2-060 E OP
50/50
3.2253.225
924302AB2-077 E O1
50/50
0.9550.955
924312AB2-078 E O1
50/50
0.9550.955
924322AB2-079 E O1
50/50
0.9550.955
925612AC1-036 E
50/50
0.8890.889
941011AE2-092 C
Adder
8.222352941176476.989
941012AE2-092 E
Adder
5.48117647058823554.659
946301AF1-294 C
50/50
5.15.1
946302AF1-294 E
50/50
4.3194.319
957481AF2-042 C
Adder
27.58352941176470823.446
957482AF2-042 E
Adder
18.38941176470588315.631
958131AF2-107 C
Adder
2.38941176470588262.031
958132AF2-107 E
Adder
1.30941176470588231.113
958211AF2-115 C
50/50
3.1013.101
958212AF2-115 E
50/50
2.6422.642
924032AB2-045 E
50/50
3.7663.766
933502AC2-165 E
50/50
24.49824.498
3151911BEARGRDN G1
50/50
17.79517.795
3151921BEARGRDN G2
50/50
17.79517.795
3147223TWITTYS
50/50
0.9860.986
936261AD2-033 C
50/50
13.17213.172
936262AD2-033 E
50/50
8.7818.781
934621AD1-088 C
50/50
6.6736.673
934622AD1-088 E
50/50
3.2133.213
3151931BEARGRDN S1
50/50
23.02123.021
316034AC1-036 C
50/50
0.2430.243
316237AB2-079 C O1
50/50
0.2340.234
316238AB2-078 C O1
50/50
0.2340.234
316239AB2-077 C O1
50/50
0.2340.234
316322AB2-045 C
50/50
0.840.84
316336AC2-165 C
50/50
32.5532.55
927264AC1-222 E
Adder
1.98117647058823531.684
313527AB2-043 C
50/50
0.3760.376
924022AB2-043 E O1
50/50
3.7783.778
962561AG1-105 C
50/50
5.5115.511
962562AG1-105 E
50/50
3.6743.674
964241AG1-285 C
50/50
9.9699.969
964242AG1-285 E
50/50
6.6466.646
934612AD1-087 E
Adder
1.95058823529411751.658
935172AD1-152 E
Adder
2.81529411764705852.393
937482AD2-202 E
Adder
0.57058823529411760.485
938821AE1-108 C
50/50
16.62316.623
938822AE1-108 E
50/50
7.9317.931
942461AE2-259 C
50/50
17.67317.673
942462AE2-259 E
50/50
11.78211.782
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3441.344
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.0390.039
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.6382.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.54721.547
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6760.676
NYPJM->LTFIMP_NY
CLTF
0.3510.351
LGEELTFEXP_LGEE->PJM
CLTF
0.0240.024
WECLTFEXP_WEC->PJM
CLTF
0.0090.009
CPLELTFEXP_CPLE->PJM
CLTF
2.8232.823
TVALTFEXP_TVA->PJM
CLTF
0.8870.887
MECLTFEXP_MEC->PJM
CLTF
0.2490.249
LAGNLTFEXP_LAGN->PJM
CLTF
1.161.16
SIGELTFEXP_SIGE->PJM
CLTF
0.0110.011
O66PJM->LTFIMP_O-066
CMTX_NF
4.3344.334

Details for 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:107.58 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:614.82
MW Contribution:16.61
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.99 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:645.76
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
964791AG1-342 C
50/50
3.7243.724
964792AG1-342 E
50/50
2.4822.482
966621AG1-532 C
Adder
0.437647058823529440.372
966622AG1-532 E
Adder
0.29176470588235290.248
3145723EMPORIA
Adder
0.136470588235294120.116
3151531CLOVER1
50/50
19.51919.519
3151541CLOVER2
50/50
19.33819.338
3151581KERR 1
50/50
0.3970.397
3151591KERR 2
50/50
1.1131.113
3151601KERR 3
50/50
1.1131.113
3151611KERR 4
50/50
1.1131.113
3151621KERR 5
50/50
1.1131.113
919692AA2-053 E OP
Adder
1.31411764705882361.117
925785AC1-054 E
50/50
2.3712.371
926274AC1-105 E
50/50
2.892.89
942751AE2-291 C
50/50
6.3136.313
942752AE2-291 E
50/50
4.2094.209
943902AF1-058 E
50/50
1.4231.423
959311AF2-222 C
Adder
9.9482352941176468.456
959312AF2-222 E
Adder
6.66588235294117755.666
960081AF2-299 C
Adder
0.58352941176470590.496
960082AF2-299 E
Adder
0.38941176470588240.331
3151631KERR 6
50/50
1.1131.113
3151641KERR 7
50/50
1.1131.113
3152661PLYWOOD A
50/50
1.3061.306
316118AC1-105 C
50/50
0.9880.988
316129AC1-054 C
50/50
0.8410.841
316131AB2-060 C
50/50
1.3891.389
923573AB1-173 E OP
Adder
1.06470588235294120.905
924162AB2-060 E OP
50/50
3.9993.999
924302AB2-077 E O1
50/50
1.321.32
924312AB2-078 E O1
50/50
1.321.32
924322AB2-079 E O1
50/50
1.321.32
925612AC1-036 E
50/50
0.6080.608
941011AE2-092 C
Adder
-7.384705882352941-6.277
946281AF1-292 C
Adder
0.48352941176470590.411
946282AF1-292 E
Adder
0.32235294117647060.274
957481AF2-042 C
50/50
85.94285.942
957482AF2-042 E
50/50
57.29557.295
3147223TWITTYS
50/50
0.6740.674
936261AD2-033 C
Adder
5.2729411764705894.482
936262AD2-033 E
Adder
3.5152941176470592.988
934621AD1-088 C
50/50
16.77816.778
934622AD1-088 E
50/50
8.0788.078
316003AC1-222 C
50/50
1.0461.046
316034AC1-036 C
50/50
0.1660.166
316222AC1-221 C
50/50
1.3041.304
316237AB2-079 C O1
50/50
0.3240.324
316238AB2-078 C O1
50/50
0.3240.324
316239AB2-077 C O1
50/50
0.3240.324
316248AF1-058 C
50/50
0.3490.349
316283AC2-100 C
50/50
1.0191.019
316336AC2-165 C
Adder
-4.488235294117647-3.815
927255AC1-221 E
50/50
3.413.41
927264AC1-222 E
50/50
4.2714.271
932763AC2-100 E
50/50
2.2422.242
923994AB2-040_E
Adder
1.99764705882352931.698
313527AB2-043 C
50/50
0.5090.509
924022AB2-043 E O1
50/50
5.1075.107
316088AB2-174 E
Adder
2.0917647058823531.778
316123AC1-075 C
50/50
0.740.74
925997AC1-075 E
50/50
2.5662.566
316205AC1-080 C
50/50
0.2470.247
926024AC1-080 E
50/50
0.8510.851
962561AG1-105 C
50/50
9.2429.242
962562AG1-105 E
50/50
6.1616.161
964241AG1-285 C
50/50
16.2716.27
964242AG1-285 E
50/50
10.84610.846
3137643SOCKMAN
Adder
0.236470588235294130.201
934611AD1-087 C
50/50
1.9191.919
934612AD1-087 E
50/50
5.5365.536
935171AD1-152 C
50/50
1.8391.839
935172AD1-152 E
50/50
7.5637.563
937481AD2-202 C
50/50
0.5570.557
937482AD2-202 E
50/50
1.621.62
938821AE1-108 C
Adder
-8.042352941176471-6.836
942461AE2-259 C
Adder
-11.085882352941177-9.423
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6471.647
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.2877.287
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.6115.611
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.50427.504
G-007PJM->LTFIMP_G-007
CMTX_NF
0.610.61
NYPJM->LTFIMP_NY
CLTF
0.2910.291
LGEELTFEXP_LGEE->PJM
CLTF
0.2860.286
WECLTFEXP_WEC->PJM
CLTF
0.1510.151
CPLELTFEXP_CPLE->PJM
CLTF
3.4573.457
TVALTFEXP_TVA->PJM
CLTF
1.5461.546
MECLTFEXP_MEC->PJM
CLTF
0.9490.949
LAGNLTFEXP_LAGN->PJM
CLTF
1.9781.978
SIGELTFEXP_SIGE->PJM
CLTF
0.0570.057
O66PJM->LTFIMP_O-066
CMTX_NF
3.8923.892

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.97 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:701.29
MW Contribution:28.05
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.14 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:748.75
MW Contribution:30.42
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
2.3122.312
961792AG1-021 E
50/50
1.971.97
964791AG1-342 C
Adder
2.00705882352941161.706
964792AG1-342 E
Adder
1.33764705882352941.137
3138533PONTONDP
50/50
0.8560.856
3144293JTRSVLE
50/50
0.5320.532
3147133PAMPLIN
50/50
1.3571.357
925785AC1-054 E
Adder
1.3870588235294121.179
926274AC1-105 E
Adder
1.40941176470588241.198
943902AF1-058 E
Adder
0.62352941176470590.53
959311AF2-222 C
50/50
16.79916.799
959312AF2-222 E
50/50
11.25511.255
316131AB2-060 C
50/50
1.0471.047
924162AB2-060 E OP
50/50
3.0163.016
924302AB2-077 E O1
50/50
0.8940.894
924312AB2-078 E O1
50/50
0.8940.894
924322AB2-079 E O1
50/50
0.8940.894
925612AC1-036 E
50/50
0.8290.829
941011AE2-092 C
50/50
23.99423.994
941012AE2-092 E
50/50
15.99615.996
946301AF1-294 C
50/50
4.7534.753
946302AF1-294 E
50/50
4.0254.025
957481AF2-042 C
Adder
25.7317647058823521.872
957482AF2-042 E
Adder
17.15411764705882214.581
958131AF2-107 C
50/50
4.7314.731
958132AF2-107 E
50/50
2.5922.592
958211AF2-115 C
50/50
2.892.89
958212AF2-115 E
50/50
2.4622.462
924032AB2-045 E
50/50
3.5043.504
933502AC2-165 E
50/50
22.78922.789
3151911BEARGRDN G1
50/50
16.55416.554
3151921BEARGRDN G2
50/50
16.55416.554
3147223TWITTYS
50/50
0.9190.919
936261AD2-033 C
50/50
12.29412.294
936262AD2-033 E
50/50
8.1968.196
934621AD1-088 C
50/50
6.2236.223
934622AD1-088 E
50/50
2.9962.996
3151931BEARGRDN S1
50/50
21.41521.415
316034AC1-036 C
50/50
0.2260.226
316237AB2-079 C O1
50/50
0.2190.219
316238AB2-078 C O1
50/50
0.2190.219
316239AB2-077 C O1
50/50
0.2190.219
316322AB2-045 C
50/50
0.7820.782
316336AC2-165 C
50/50
30.2830.28
927264AC1-222 E
Adder
1.91647058823529411.629
313527AB2-043 C
50/50
0.3520.352
924022AB2-043 E O1
50/50
3.5343.534
962561AG1-105 C
Adder
5.197647058823534.418
962562AG1-105 E
Adder
3.4647058823529412.945
964241AG1-285 C
50/50
9.3069.306
964242AG1-285 E
50/50
6.2046.204
934612AD1-087 E
Adder
1.8235294117647061.55
935172AD1-152 E
Adder
2.64470588235294152.248
937482AD2-202 E
Adder
0.53411764705882360.454
938821AE1-108 C
50/50
33.08633.086
938822AE1-108 E
50/50
15.78715.787
942461AE2-259 C
50/50
16.45516.455
942462AE2-259 E
50/50
10.9710.97
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.2941.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4071.407
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.0933.093
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.18821.188
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6880.688
NYPJM->LTFIMP_NY
CLTF
0.3520.352
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
WECLTFEXP_WEC->PJM
CLTF
0.0360.036
CPLELTFEXP_CPLE->PJM
CLTF
2.7182.718
TVALTFEXP_TVA->PJM
CLTF
0.9770.977
MECLTFEXP_MEC->PJM
CLTF
0.3740.374
LAGNLTFEXP_LAGN->PJM
CLTF
1.2621.262
SIGELTFEXP_SIGE->PJM
CLTF
0.020.02
O66PJM->LTFIMP_O-066
CMTX_NF
4.4054.405

Details for 6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.24 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:618.61
MW Contribution:16.61
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.66 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:649.58
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
964791AG1-342 C
50/50
3.7243.724
964792AG1-342 E
50/50
2.4822.482
966621AG1-532 C
Adder
0.437647058823529440.372
966622AG1-532 E
Adder
0.29176470588235290.248
3145723EMPORIA
Adder
0.136470588235294120.116
3151531CLOVER1
50/50
19.51919.519
3151541CLOVER2
50/50
19.33819.338
3151581KERR 1
50/50
0.3970.397
3151591KERR 2
50/50
1.1131.113
3151601KERR 3
50/50
1.1131.113
3151611KERR 4
50/50
1.1131.113
3151621KERR 5
50/50
1.1131.113
919692AA2-053 E OP
Adder
1.31411764705882361.117
925785AC1-054 E
50/50
2.3712.371
926274AC1-105 E
50/50
2.892.89
942751AE2-291 C
50/50
6.3136.313
942752AE2-291 E
50/50
4.2094.209
943902AF1-058 E
50/50
1.4231.423
959311AF2-222 C
Adder
9.9482352941176468.456
959312AF2-222 E
Adder
6.66588235294117755.666
960081AF2-299 C
Adder
0.58352941176470590.496
960082AF2-299 E
Adder
0.38941176470588240.331
3151631KERR 6
50/50
1.1131.113
3151641KERR 7
50/50
1.1131.113
3152661PLYWOOD A
50/50
1.3061.306
316118AC1-105 C
50/50
0.9880.988
316129AC1-054 C
50/50
0.8410.841
316131AB2-060 C
50/50
1.3891.389
923573AB1-173 E OP
Adder
1.06470588235294120.905
924162AB2-060 E OP
50/50
3.9993.999
924302AB2-077 E O1
50/50
1.321.32
924312AB2-078 E O1
50/50
1.321.32
924322AB2-079 E O1
50/50
1.321.32
925612AC1-036 E
50/50
0.6080.608
941011AE2-092 C
Adder
-7.384705882352941-6.277
946281AF1-292 C
Adder
0.48352941176470590.411
946282AF1-292 E
Adder
0.32235294117647060.274
957481AF2-042 C
50/50
85.94285.942
957482AF2-042 E
50/50
57.29557.295
3147223TWITTYS
50/50
0.6740.674
936261AD2-033 C
Adder
5.2729411764705894.482
936262AD2-033 E
Adder
3.5152941176470592.988
934621AD1-088 C
50/50
16.77816.778
934622AD1-088 E
50/50
8.0788.078
316003AC1-222 C
50/50
1.0461.046
316034AC1-036 C
50/50
0.1660.166
316222AC1-221 C
50/50
1.3041.304
316237AB2-079 C O1
50/50
0.3240.324
316238AB2-078 C O1
50/50
0.3240.324
316239AB2-077 C O1
50/50
0.3240.324
316248AF1-058 C
50/50
0.3490.349
316283AC2-100 C
50/50
1.0191.019
316336AC2-165 C
Adder
-4.488235294117647-3.815
927255AC1-221 E
50/50
3.413.41
927264AC1-222 E
50/50
4.2714.271
932763AC2-100 E
50/50
2.2422.242
923994AB2-040_E
Adder
1.99764705882352931.698
313527AB2-043 C
50/50
0.5090.509
924022AB2-043 E O1
50/50
5.1075.107
316088AB2-174 E
Adder
2.0917647058823531.778
316123AC1-075 C
50/50
0.740.74
925997AC1-075 E
50/50
2.5662.566
316205AC1-080 C
50/50
0.2470.247
926024AC1-080 E
50/50
0.8510.851
962561AG1-105 C
50/50
9.2429.242
962562AG1-105 E
50/50
6.1616.161
964241AG1-285 C
50/50
16.2716.27
964242AG1-285 E
50/50
10.84610.846
3137643SOCKMAN
Adder
0.236470588235294130.201
934611AD1-087 C
50/50
1.9191.919
934612AD1-087 E
50/50
5.5365.536
935171AD1-152 C
50/50
1.8391.839
935172AD1-152 E
50/50
7.5637.563
937481AD2-202 C
50/50
0.5570.557
937482AD2-202 E
50/50
1.621.62
938821AE1-108 C
Adder
-8.042352941176471-6.836
942461AE2-259 C
Adder
-11.085882352941177-9.423
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6471.647
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.2877.287
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.6115.611
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.50427.504
G-007PJM->LTFIMP_G-007
CMTX_NF
0.610.61
NYPJM->LTFIMP_NY
CLTF
0.2910.291
LGEELTFEXP_LGEE->PJM
CLTF
0.2860.286
WECLTFEXP_WEC->PJM
CLTF
0.1510.151
CPLELTFEXP_CPLE->PJM
CLTF
3.4573.457
TVALTFEXP_TVA->PJM
CLTF
1.5461.546
MECLTFEXP_MEC->PJM
CLTF
0.9490.949
LAGNLTFEXP_LAGN->PJM
CLTF
1.9781.978
SIGELTFEXP_SIGE->PJM
CLTF
0.0570.057
O66PJM->LTFIMP_O-066
CMTX_NF
3.8923.892

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.64 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:718.91
MW Contribution:28.05
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.82 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:766.43
MW Contribution:30.42
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
2.3122.312
961792AG1-021 E
50/50
1.971.97
964791AG1-342 C
Adder
2.00705882352941161.706
964792AG1-342 E
Adder
1.33764705882352941.137
3138533PONTONDP
50/50
0.8560.856
3144293JTRSVLE
50/50
0.5320.532
3147133PAMPLIN
50/50
1.3571.357
925785AC1-054 E
Adder
1.3870588235294121.179
926274AC1-105 E
Adder
1.40941176470588241.198
943902AF1-058 E
Adder
0.62352941176470590.53
959311AF2-222 C
50/50
16.79916.799
959312AF2-222 E
50/50
11.25511.255
316131AB2-060 C
50/50
1.0471.047
924162AB2-060 E OP
50/50
3.0163.016
924302AB2-077 E O1
50/50
0.8940.894
924312AB2-078 E O1
50/50
0.8940.894
924322AB2-079 E O1
50/50
0.8940.894
925612AC1-036 E
50/50
0.8290.829
941011AE2-092 C
50/50
23.99423.994
941012AE2-092 E
50/50
15.99615.996
946301AF1-294 C
50/50
4.7534.753
946302AF1-294 E
50/50
4.0254.025
957481AF2-042 C
Adder
25.7317647058823521.872
957482AF2-042 E
Adder
17.15411764705882214.581
958131AF2-107 C
50/50
4.7314.731
958132AF2-107 E
50/50
2.5922.592
958211AF2-115 C
50/50
2.892.89
958212AF2-115 E
50/50
2.4622.462
924032AB2-045 E
50/50
3.5043.504
933502AC2-165 E
50/50
22.78922.789
3151911BEARGRDN G1
50/50
16.55416.554
3151921BEARGRDN G2
50/50
16.55416.554
3147223TWITTYS
50/50
0.9190.919
936261AD2-033 C
50/50
12.29412.294
936262AD2-033 E
50/50
8.1968.196
934621AD1-088 C
50/50
6.2236.223
934622AD1-088 E
50/50
2.9962.996
3151931BEARGRDN S1
50/50
21.41521.415
316034AC1-036 C
50/50
0.2260.226
316237AB2-079 C O1
50/50
0.2190.219
316238AB2-078 C O1
50/50
0.2190.219
316239AB2-077 C O1
50/50
0.2190.219
316322AB2-045 C
50/50
0.7820.782
316336AC2-165 C
50/50
30.2830.28
927264AC1-222 E
Adder
1.91647058823529411.629
313527AB2-043 C
50/50
0.3520.352
924022AB2-043 E O1
50/50
3.5343.534
962561AG1-105 C
Adder
5.197647058823534.418
962562AG1-105 E
Adder
3.4647058823529412.945
964241AG1-285 C
50/50
9.3069.306
964242AG1-285 E
50/50
6.2046.204
934612AD1-087 E
Adder
1.8235294117647061.55
935172AD1-152 E
Adder
2.64470588235294152.248
937482AD2-202 E
Adder
0.53411764705882360.454
938821AE1-108 C
50/50
33.08633.086
938822AE1-108 E
50/50
15.78715.787
942461AE2-259 C
50/50
16.45516.455
942462AE2-259 E
50/50
10.9710.97
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.2941.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4071.407
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.0933.093
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.18821.188
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6880.688
NYPJM->LTFIMP_NY
CLTF
0.3520.352
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
WECLTFEXP_WEC->PJM
CLTF
0.0360.036
CPLELTFEXP_CPLE->PJM
CLTF
2.7182.718
TVALTFEXP_TVA->PJM
CLTF
0.9770.977
MECLTFEXP_MEC->PJM
CLTF
0.3740.374
LAGNLTFEXP_LAGN->PJM
CLTF
1.2621.262
SIGELTFEXP_SIGE->PJM
CLTF
0.020.02
O66PJM->LTFIMP_O-066
CMTX_NF
4.4054.405

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.38 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:677.52
MW Contribution:28.05
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.53 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:724.84
MW Contribution:30.42
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
2.3122.312
961792AG1-021 E
50/50
1.971.97
964791AG1-342 C
Adder
2.00705882352941161.706
964792AG1-342 E
Adder
1.33764705882352941.137
3138533PONTONDP
50/50
0.8560.856
3144293JTRSVLE
50/50
0.5320.532
3147133PAMPLIN
50/50
1.3571.357
925785AC1-054 E
Adder
1.3870588235294121.179
926274AC1-105 E
Adder
1.40941176470588241.198
943902AF1-058 E
Adder
0.62352941176470590.53
959311AF2-222 C
50/50
16.79916.799
959312AF2-222 E
50/50
11.25511.255
316131AB2-060 C
50/50
1.0471.047
924162AB2-060 E OP
50/50
3.0163.016
924302AB2-077 E O1
50/50
0.8940.894
924312AB2-078 E O1
50/50
0.8940.894
924322AB2-079 E O1
50/50
0.8940.894
925612AC1-036 E
50/50
0.8290.829
941011AE2-092 C
50/50
23.99423.994
941012AE2-092 E
50/50
15.99615.996
946301AF1-294 C
50/50
4.7534.753
946302AF1-294 E
50/50
4.0254.025
957481AF2-042 C
Adder
25.7317647058823521.872
957482AF2-042 E
Adder
17.15411764705882214.581
958131AF2-107 C
50/50
4.7314.731
958132AF2-107 E
50/50
2.5922.592
958211AF2-115 C
50/50
2.892.89
958212AF2-115 E
50/50
2.4622.462
924032AB2-045 E
50/50
3.5043.504
933502AC2-165 E
50/50
22.78922.789
3151911BEARGRDN G1
50/50
16.55416.554
3151921BEARGRDN G2
50/50
16.55416.554
3147223TWITTYS
50/50
0.9190.919
936261AD2-033 C
50/50
12.29412.294
936262AD2-033 E
50/50
8.1968.196
934621AD1-088 C
50/50
6.2236.223
934622AD1-088 E
50/50
2.9962.996
3151931BEARGRDN S1
50/50
21.41521.415
316034AC1-036 C
50/50
0.2260.226
316237AB2-079 C O1
50/50
0.2190.219
316238AB2-078 C O1
50/50
0.2190.219
316239AB2-077 C O1
50/50
0.2190.219
316322AB2-045 C
50/50
0.7820.782
316336AC2-165 C
50/50
30.2830.28
927264AC1-222 E
Adder
1.91647058823529411.629
313527AB2-043 C
50/50
0.3520.352
924022AB2-043 E O1
50/50
3.5343.534
962561AG1-105 C
Adder
5.197647058823534.418
962562AG1-105 E
Adder
3.4647058823529412.945
964241AG1-285 C
50/50
9.3069.306
964242AG1-285 E
50/50
6.2046.204
934612AD1-087 E
Adder
1.8235294117647061.55
935172AD1-152 E
Adder
2.64470588235294152.248
937482AD2-202 E
Adder
0.53411764705882360.454
938821AE1-108 C
50/50
33.08633.086
938822AE1-108 E
50/50
15.78715.787
942461AE2-259 C
50/50
16.45516.455
942462AE2-259 E
50/50
10.9710.97
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.2941.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4071.407
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.0933.093
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.18821.188
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6880.688
NYPJM->LTFIMP_NY
CLTF
0.3520.352
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
WECLTFEXP_WEC->PJM
CLTF
0.0360.036
CPLELTFEXP_CPLE->PJM
CLTF
2.7182.718
TVALTFEXP_TVA->PJM
CLTF
0.9770.977
MECLTFEXP_MEC->PJM
CLTF
0.3740.374
LAGNLTFEXP_LAGN->PJM
CLTF
1.2621.262
SIGELTFEXP_SIGE->PJM
CLTF
0.020.02
O66PJM->LTFIMP_O-066
CMTX_NF
4.4054.405

Details for 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:107.58 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:614.81
MW Contribution:16.61
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.99 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:645.76
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
964791AG1-342 C
50/50
3.7243.724
964792AG1-342 E
50/50
2.4822.482
966621AG1-532 C
Adder
0.437647058823529440.372
966622AG1-532 E
Adder
0.29176470588235290.248
3145723EMPORIA
Adder
0.136470588235294120.116
3151531CLOVER1
50/50
19.51919.519
3151541CLOVER2
50/50
19.33819.338
3151581KERR 1
50/50
0.3970.397
3151591KERR 2
50/50
1.1131.113
3151601KERR 3
50/50
1.1131.113
3151611KERR 4
50/50
1.1131.113
3151621KERR 5
50/50
1.1131.113
919692AA2-053 E OP
Adder
1.31411764705882361.117
925785AC1-054 E
50/50
2.3712.371
926274AC1-105 E
50/50
2.892.89
942751AE2-291 C
50/50
6.3136.313
942752AE2-291 E
50/50
4.2094.209
943902AF1-058 E
50/50
1.4231.423
959311AF2-222 C
Adder
9.9482352941176468.456
959312AF2-222 E
Adder
6.66588235294117755.666
960081AF2-299 C
Adder
0.58352941176470590.496
960082AF2-299 E
Adder
0.38941176470588240.331
3151631KERR 6
50/50
1.1131.113
3151641KERR 7
50/50
1.1131.113
3152661PLYWOOD A
50/50
1.3061.306
316118AC1-105 C
50/50
0.9880.988
316129AC1-054 C
50/50
0.8410.841
316131AB2-060 C
50/50
1.3891.389
923573AB1-173 E OP
Adder
1.06470588235294120.905
924162AB2-060 E OP
50/50
3.9993.999
924302AB2-077 E O1
50/50
1.321.32
924312AB2-078 E O1
50/50
1.321.32
924322AB2-079 E O1
50/50
1.321.32
925612AC1-036 E
50/50
0.6080.608
941011AE2-092 C
Adder
-7.384705882352941-6.277
946281AF1-292 C
Adder
0.48352941176470590.411
946282AF1-292 E
Adder
0.32235294117647060.274
957481AF2-042 C
50/50
85.94285.942
957482AF2-042 E
50/50
57.29557.295
3147223TWITTYS
50/50
0.6740.674
936261AD2-033 C
Adder
5.2729411764705894.482
936262AD2-033 E
Adder
3.5152941176470592.988
934621AD1-088 C
50/50
16.77816.778
934622AD1-088 E
50/50
8.0788.078
316003AC1-222 C
50/50
1.0461.046
316034AC1-036 C
50/50
0.1660.166
316222AC1-221 C
50/50
1.3041.304
316237AB2-079 C O1
50/50
0.3240.324
316238AB2-078 C O1
50/50
0.3240.324
316239AB2-077 C O1
50/50
0.3240.324
316248AF1-058 C
50/50
0.3490.349
316283AC2-100 C
50/50
1.0191.019
316336AC2-165 C
Adder
-4.488235294117647-3.815
927255AC1-221 E
50/50
3.413.41
927264AC1-222 E
50/50
4.2714.271
932763AC2-100 E
50/50
2.2422.242
923994AB2-040_E
Adder
1.99764705882352931.698
313527AB2-043 C
50/50
0.5090.509
924022AB2-043 E O1
50/50
5.1075.107
316088AB2-174 E
Adder
2.0917647058823531.778
316123AC1-075 C
50/50
0.740.74
925997AC1-075 E
50/50
2.5662.566
316205AC1-080 C
50/50
0.2470.247
926024AC1-080 E
50/50
0.8510.851
962561AG1-105 C
50/50
9.2429.242
962562AG1-105 E
50/50
6.1616.161
964241AG1-285 C
50/50
16.2716.27
964242AG1-285 E
50/50
10.84610.846
3137643SOCKMAN
Adder
0.236470588235294130.201
934611AD1-087 C
50/50
1.9191.919
934612AD1-087 E
50/50
5.5365.536
935171AD1-152 C
50/50
1.8391.839
935172AD1-152 E
50/50
7.5637.563
937481AD2-202 C
50/50
0.5570.557
937482AD2-202 E
50/50
1.621.62
938821AE1-108 C
Adder
-8.042352941176471-6.836
942461AE2-259 C
Adder
-11.085882352941177-9.423
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6471.647
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.2877.287
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.6115.611
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.50427.504
G-007PJM->LTFIMP_G-007
CMTX_NF
0.610.61
NYPJM->LTFIMP_NY
CLTF
0.2910.291
LGEELTFEXP_LGEE->PJM
CLTF
0.2860.286
WECLTFEXP_WEC->PJM
CLTF
0.1510.151
CPLELTFEXP_CPLE->PJM
CLTF
3.4573.457
TVALTFEXP_TVA->PJM
CLTF
1.5461.546
MECLTFEXP_MEC->PJM
CLTF
0.9490.949
LAGNLTFEXP_LAGN->PJM
CLTF
1.9781.978
SIGELTFEXP_SIGE->PJM
CLTF
0.0570.057
O66PJM->LTFIMP_O-066
CMTX_NF
3.8923.892

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.12 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3352.99
MW Contribution:29.71
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3492.91
MW Contribution:25.43
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
1.05882352941176470.9
961672AG1-007 E
Adder
0.60.51
961791AG1-021 C
Adder
1.63058823529411771.386
961792AG1-021 E
Adder
1.38941176470588231.181
961941AG1-037 C
Adder
0.5717647058823530.486
961942AG1-037 E
Adder
0.381176470588235340.324
963041AG1-153 C
50/50
8.3218.321
963042AG1-153 E
50/50
12.48112.481
964791AG1-342 C
Adder
3.96470588235294133.37
964792AG1-342 E
Adder
2.6435294117647062.247
966621AG1-532 C
50/50
1.6281.628
966622AG1-532 E
50/50
1.0851.085
3138533PONTONDP
Adder
0.60352941176470590.513
3145413WATKINS
Adder
0.7717647058823530.656
3145723EMPORIA
50/50
0.50.5
3147133PAMPLIN
Adder
0.89882352941176480.764
3151311EDGECMA
Adder
17.50705882352941214.881
3151531CLOVER1
50/50
15.90515.905
3151541CLOVER2
50/50
15.75715.757
918492AA1-063AE OP
Adder
4.65058823529411753.953
918532AA1-067 E
Adder
0.80588235294117660.685
919692AA2-053 E OP
Adder
4.8352941176470594.11
920042AA2-088 E OP
Adder
11.94941176470588210.157
925785AC1-054 E
Adder
3.94000000000000043.349
926274AC1-105 E
Adder
2.9882352941176472.54
927146AC1-208 E
Adder
4.5541176470588243.871
934521AD1-076 C
Adder
13.81176470588235411.74
934522AD1-076 E
Adder
7.045.984
943172AE2-346 E
Adder
0.68588235294117650.583
943902AF1-058 E
Adder
1.42941176470588241.215
944011AF1-069 C
50/50
19.88619.886
944012AF1-069 E
50/50
7.7257.725
959311AF2-222 C
Adder
17.79058823529411615.122
959312AF2-222 E
Adder
11.9210.132
960081AF2-299 C
50/50
2.1712.171
960082AF2-299 E
50/50
1.4471.447
316141AB2-099 E
Adder
0.28588235294117650.243
900672V4-068 E
Adder
0.402352941176470640.342
917342Z2-044 E
Adder
0.6764705882352940.575
922923AB1-081 E OP
Adder
4.20470588235294153.574
923263AB1-132 E OP
Adder
7.0270588235294125.973
923573AB1-173 E OP
Adder
3.78941176470588253.221
924162AB2-060 E OP
Adder
4.8364705882352944.111
924302AB2-077 E O1
Adder
1.52117647058823541.293
924312AB2-078 E O1
Adder
1.52117647058823541.293
924322AB2-079 E O1
Adder
1.52117647058823541.293
925612AC1-036 E
Adder
0.93294117647058830.793
940492AE2-034 E
Adder
3.4764705882352942.955
941031AE2-094 C
50/50
60.86460.864
941032AE2-094 E
50/50
27.25927.259
946281AF1-292 C
50/50
1.7971.797
946282AF1-292 E
50/50
1.1981.198
946301AF1-294 C
Adder
3.3517647058823532.849
946302AF1-294 E
Adder
2.83882352941176472.413
957481AF2-042 C
50/50
69.9469.94
957482AF2-042 E
50/50
46.62746.627
957861AF2-080 C
Adder
8.6200000000000017.327
957862AF2-080 E
Adder
3.8211764705882363.248
958211AF2-115 C
Adder
2.03764705882352941.732
958212AF2-115 E
Adder
1.73647058823529421.476
3145393UNCAMP
Adder
6.7635294117647065.749
916042Z1-036 E
Adder
32.1705882352941227.345
938771AE1-103 C
Adder
3.24823529411764732.761
938772AE1-103 E
Adder
4.4858823529411773.813
313526AB2-022 C
50/50
0.4240.424
3143316POE
Adder
1.30823529411764721.112
3145256KINGFORK
Adder
1.06588235294117650.906
3145506HICKORY
50/50
2.4672.467
926662AC1-147 E
Adder
1.46588235294117641.246
926755AC1-161 E
50/50
14.89414.894
935112AD1-144 E
Adder
0.98941176470588230.841
942341AE2-247 C
Adder
1.54941176470588231.317
942342AE2-247 E
Adder
2.141.819
943461AF1-017 C
Adder
1.40235294117647061.192
943462AF1-017 E
Adder
2.2870588235294121.944
943612AF1-032 E
Adder
1.02823529411764710.874
3151021BRUNSWICKG1
50/50
12.28212.282
3151031BRUNSWICKG2
50/50
12.28212.282
3151041BRUNSWICKG3
50/50
12.28212.282
3151051BRUNSWICKS1
50/50
25.51625.516
3151081ELIZAR1
50/50
3.5563.556
3151091ELIZAR2
50/50
3.4953.495
3151101ELIZAR3
50/50
3.6013.601
3152411Z1-086 GT1
50/50
15.81615.816
3152421Z1-086 GT2
50/50
15.81115.811
3152431Z1-086 GT3
50/50
15.81115.811
3152441Z1-086 ST
50/50
27.53327.533
913392Y1-086 E
50/50
2.4762.476
916192Z1-068 E
50/50
2.1052.105
923832AB2-022 E
50/50
1.3981.398
923852AB2-025 E
50/50
1.3891.389
939312AE1-162 E
Adder
1.37058823529411771.165
957492AF2-043 E
Adder
1.58117647058823541.344
901082W1-029 E
Adder
35.7705882352941230.405
917122Z2-027 E
50/50
1.5121.512
925522AC1-027 E
50/50
1.3621.362
957871AF2-081 C
50/50
11.29311.293
957872AF2-081 E
50/50
4.844.84
958161AF2-110 C
Adder
1.49647058823529421.272
958162AF2-110 E
Adder
2.38000000000000032.023
3147223TWITTYS
Adder
1.03411764705882360.879
917512Z2-088 E OP1
Adder
5.5247058823529414.696
926071AC1-086 C
Adder
24.1447058823529420.523
926072AC1-086 E
Adder
10.9894117647058819.341
927021AC1-189 C
Adder
9.4905882352941178.067
927022AC1-189 E
Adder
4.7282352941176474.019
936261AD2-033 C
Adder
13.51176470588235311.485
936262AD2-033 E
Adder
9.0082352941176477.657
933291AC2-141 C
50/50
34.8934.89
933292AC2-141 E
50/50
14.89414.894
934621AD1-088 C
50/50
11.53711.537
934622AD1-088 E
50/50
5.5555.555
939411AE1-173 C
50/50
128.665128.665
939412AE1-173 E
50/50
85.77785.777
916191Z1-068 C
50/50
0.0490.049
933981AD1-022 C
Adder
9.8917647058823528.408
933982AD1-022 E
Adder
5.3847058823529414.577
962572AG1-106 E
Adder
1.36588235294117651.161
962571AG1-106 C
Adder
3.1235294117647062.655
3145946PLYMOUTH TP
Adder
0.364705882352941160.31
3146326AYDLETT TAP
50/50
1.5311.531
316023AB2-100 C2
50/50
1.1231.123
316185AD1-033 C
50/50
1.391.39
316263AC1-034 C
Adder
7.4894117647058826.366
316274AC1-208 C
Adder
10.255294117647068.717
316294AC1-161 C
50/50
5.7015.701
316315AB2-025 C
50/50
0.4880.488
316316AC1-027 C
50/50
0.3530.353
316320Y1-086 C
50/50
0.2480.248
316321Z2-027 C
50/50
0.410.41
316365AB2-100 C1
50/50
1.1231.123
917332KELFORD E
Adder
1.8635294117647061.584
924516AB2-100 E1
50/50
3.3843.384
924517AB2-100 E2
50/50
3.3843.384
925595AC1-034 E
Adder
5.65058823529411754.803
926206AC1-098 E
Adder
4.1470588235294123.525
926214AC1-099 E
Adder
1.36941176470588231.164
927255AC1-221 E
Adder
4.1411764705882363.52
927264AC1-222 E
Adder
4.3282352941176473.679
932763AC2-100 E
Adder
2.80941176470588252.388
934065AD1-033 E
50/50
5.6715.671
937226AE2-253 E
50/50
6.6066.606
918512AA1-065 E OP
Adder
6.2505882352941175.313
316017AA1-139 ULT1
50/50
1.2231.223
316018AA1-139 ULT2
50/50
1.2231.223
919153AA1-139 E2
50/50
4.6184.618
919152AA1-139 E1
50/50
4.6184.618
919710AA2-057 E
Adder
4.49411764705882363.82
920692AA2-178 E
Adder
4.6352941176470593.94
923994AB2-040_E
Adder
7.1047058823529416.039
924022AB2-043 E O1
Adder
5.9035294117647065.018
924152AB2-059 E OP
Adder
5.9564705882352945.063
316084AB2-161 E
Adder
5.26941176470588254.479
925122AB2-169 E
Adder
6.4858823529411775.513
316087AB2-174 C
50/50
1.3621.362
316088AB2-174 E
50/50
7.5427.542
316375AC2-012 C
50/50
1.4951.495
932046AC2-012 E
50/50
14.50114.501
316311AC2-079 C
Adder
5.9964705882352955.097
932596AC2-079 E
Adder
9.7835294117647078.316
934576AD1-082 E
Adder
4.1988235294117653.569
316349AD2-085 C
Adder
3.5752941176470593.039
936666AD2-085 E
Adder
5.8329411764705884.958
316388AE2-253 GEN
50/50
2.2212.221
961611AG1-000B C
Adder
5.824.947
941591AE2-156 C
50/50
19.83519.835
944581AF1-123 C
50/50
51.37451.374
944582AF1-123 E
50/50
117.641117.641
944591AF1-124 C
50/50
51.55751.557
944592AF1-124 E
50/50
118.067118.067
944601AF1-125 C
50/50
50.58350.583
944602AF1-125 E
50/50
115.795115.795
962561AG1-105 C
Adder
9.9705882352941188.475
962562AG1-105 E
Adder
6.6470588235294125.65
964241AG1-285 C
50/50
14.87614.876
964242AG1-285 E
50/50
9.9189.918
3137643SOCKMAN
Adder
0.81882352941176460.696
932632AC2-084 E
Adder
3.66588235294117663.116
934321AD1-056 C
Adder
7.126.052
934322AD1-056 E
Adder
3.86117647058823543.282
934331AD1-057 C
Adder
3.9717647058823533.376
934332AD1-057 E
Adder
2.0682352941176471.758
934501AD1-074 C
Adder
38.0305882352941232.326
934502AD1-074 E
Adder
19.3616.456
934511AD1-075 C
Adder
9.507058823529418.081
934512AD1-075 E
Adder
4.844.114
934611AD1-087 C
50/50
1.5661.566
934612AD1-087 E
50/50
4.5174.517
935171AD1-152 C
50/50
1.6091.609
935172AD1-152 E
50/50
6.6176.617
937481AD2-202 C
50/50
0.4540.454
937482AD2-202 E
50/50
1.3221.322
938531AE1-072 C
50/50
19.84719.847
938532AE1-072 E
50/50
10.34610.346
939191AE1-149 C
Adder
9.5941176470588238.155
939192AE1-149 E
Adder
6.3964705882352955.437
940481AE2-033 C
50/50
19.30519.305
940482AE2-033 E
50/50
13.01513.015
940541AE2-040 C
50/50
3.4343.434
940641AE2-051 C
50/50
26.11526.115
940642AE2-051 E
50/50
17.4117.41
941101AE2-104 C
Adder
3.66705882352941173.117
941102AE2-104 E
Adder
5.8305882352941184.956
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.3016.301
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.47229.472
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.8122.81
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
107.493107.493
G-007PJM->LTFIMP_G-007
CMTX_NF
3.5513.551
NYPJM->LTFIMP_NY
CLTF
1.6611.661
LGEELTFEXP_LGEE->PJM
CLTF
1.1651.165
WECLTFEXP_WEC->PJM
CLTF
0.6140.614
CPLELTFEXP_CPLE->PJM
CLTF
13.22113.221
TVALTFEXP_TVA->PJM
CLTF
6.2796.279
MECLTFEXP_MEC->PJM
CLTF
3.8563.856
LAGNLTFEXP_LAGN->PJM
CLTF
8.048.04
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234
O66PJM->LTFIMP_O-066
CMTX_NF
22.61622.616

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.88 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1342.55
MW Contribution:9.31
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:127.67 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1350.99
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.410588235294117640.349
961672AG1-007 E
Adder
0.232941176470588260.198
961941AG1-037 C
Adder
0.212941176470588240.181
961942AG1-037 E
Adder
0.14235294117647060.121
963041AG1-153 C
50/50
3.6733.673
963042AG1-153 E
50/50
5.5095.509
964791AG1-342 C
Adder
1.48470588235294131.262
964792AG1-342 E
Adder
0.99058823529411770.842
966621AG1-532 C
Adder
0.60117647058823530.511
966622AG1-532 E
Adder
0.40.34
3145413WATKINS
Adder
0.279999999999999970.238
3145723EMPORIA
Adder
0.18470588235294120.157
3151311EDGECMA
Adder
6.8129411764705895.791
918492AA1-063AE OP
Adder
1.72705882352941181.468
918532AA1-067 E
Adder
0.30941176470588240.263
919692AA2-053 E OP
Adder
1.80705882352941181.536
920042AA2-088 E OP
Adder
4.3847058823529413.727
925785AC1-054 E
Adder
1.47764705882352951.256
926274AC1-105 E
Adder
1.13764705882352950.967
927146AC1-208 E
Adder
1.72941176470588241.47
934521AD1-076 C
Adder
5.1635294117647064.389
934522AD1-076 E
Adder
2.6317647058823532.237
943172AE2-346 E
Adder
0.255294117647058840.217
943902AF1-058 E
Adder
0.55294117647058830.47
944011AF1-069 C
50/50
8.8768.876
944012AF1-069 E
50/50
3.4483.448
959311AF2-222 C
Adder
5.57411764705882454.738
959312AF2-222 E
Adder
3.73411764705882383.174
960081AF2-299 C
Adder
0.80117647058823540.681
960082AF2-299 E
Adder
0.53411764705882360.454
316141AB2-099 E
Adder
0.107058823529411760.091
900672V4-068 E
Adder
0.149411764705882360.127
917342Z2-044 E
Adder
0.26117647058823530.222
922923AB1-081 E OP
Adder
1.63529411764705881.39
923263AB1-132 E OP
Adder
2.6305882352941182.236
923573AB1-173 E OP
Adder
1.40588235294117661.195
924162AB2-060 E OP
Adder
1.71764705882352931.46
924302AB2-077 E O1
Adder
0.54823529411764720.466
924312AB2-078 E O1
Adder
0.54823529411764720.466
924322AB2-079 E O1
Adder
0.54823529411764720.466
925612AC1-036 E
Adder
0.30.255
940492AE2-034 E
Adder
1.2952941176470591.101
941011AE2-092 C
Adder
-4.452941176470588-3.785
941031AE2-094 C
50/50
27.16527.165
941032AE2-094 E
50/50
12.16712.167
946281AF1-292 C
Adder
0.66352941176470580.564
946282AF1-292 E
Adder
0.44235294117647060.376
957481AF2-042 C
Adder
28.3424.089
957482AF2-042 E
Adder
18.89411764705882416.06
957861AF2-080 C
Adder
3.3247058823529412.826
957862AF2-080 E
Adder
1.47411764705882351.253
3145393UNCAMP
Adder
2.44352941176470572.077
916042Z1-036 E
Adder
11.93411764705882510.144
938771AE1-103 C
Adder
1.16941176470588240.994
938772AE1-103 E
Adder
1.61529411764705881.373
3145256KINGFORK
Adder
0.367058823529411770.312
3145506HICKORY
Adder
0.91764705882352950.78
926662AC1-147 E
Adder
0.53176470588235290.452
926755AC1-161 E
Adder
5.7376470588235294.877
935112AD1-144 E
Adder
0.339999999999999970.289
942341AE2-247 C
Adder
0.50235294117647060.427
942342AE2-247 E
Adder
0.69411764705882350.59
943461AF1-017 C
Adder
0.454117647058823570.386
943462AF1-017 E
Adder
0.74117647058823530.63
943612AF1-032 E
Adder
0.374117647058823550.318
3151021BRUNSWICKG1
50/50
5.4215.421
3151031BRUNSWICKG2
50/50
5.4215.421
3151041BRUNSWICKG3
50/50
5.4215.421
3151051BRUNSWICKS1
50/50
11.26311.263
3152411Z1-086 GT1
50/50
7.0067.006
3152421Z1-086 GT2
50/50
7.0037.003
3152431Z1-086 GT3
50/50
7.0037.003
3152441Z1-086 ST
50/50
12.19612.196
913392Y1-086 E
Adder
0.91764705882352950.78
916192Z1-068 E
Adder
0.77294117647058820.657
923832AB2-022 E
Adder
0.51764705882352950.44
923852AB2-025 E
Adder
0.50705882352941180.431
939312AE1-162 E
Adder
0.41294117647058820.351
957492AF2-043 E
Adder
0.57529411764705880.489
901082W1-029 E
Adder
13.19764705882352911.218
917122Z2-027 E
Adder
0.55999999999999990.476
925522AC1-027 E
Adder
0.50.425
957871AF2-081 C
Adder
4.1964705882352953.567
957872AF2-081 E
Adder
1.79882352941176471.529
958161AF2-110 C
Adder
0.53058823529411770.451
958162AF2-110 E
Adder
0.84352941176470590.717
3147223TWITTYS
Adder
0.332941176470588240.283
917512Z2-088 E OP1
Adder
2.1352941176470591.815
926071AC1-086 C
Adder
9.037647058823537.682
926072AC1-086 E
Adder
4.11294117647058853.496
927021AC1-189 C
Adder
3.66117647058823573.112
927022AC1-189 E
Adder
1.8235294117647061.55
936261AD2-033 C
Adder
4.2364705882352943.601
936262AD2-033 E
Adder
2.8247058823529412.401
933291AC2-141 C
Adder
13.44235294117647211.426
933292AC2-141 E
Adder
5.7376470588235294.877
934621AD1-088 C
Adder
4.3611764705882353.707
934622AD1-088 E
Adder
2.11.785
939411AE1-173 C
50/50
55.12655.126
939412AE1-173 E
50/50
36.75136.751
933981AD1-022 C
Adder
3.73.145
933982AD1-022 E
Adder
2.01411764705882361.712
962572AG1-106 E
Adder
0.51176470588235290.435
962571AG1-106 C
Adder
1.16941176470588240.994
3145946PLYMOUTH TP
Adder
0.136470588235294120.116
3146326AYDLETT TAP
Adder
0.56823529411764710.483
316263AC1-034 C
Adder
2.91411764705882352.477
316274AC1-208 C
Adder
3.8952941176470593.311
316336AC2-165 C
Adder
-10.758823529411764-9.145
917332KELFORD E
Adder
0.70117647058823530.596
924516AB2-100 E1
Adder
1.25176470588235311.064
924517AB2-100 E2
Adder
1.25176470588235311.064
925595AC1-034 E
Adder
2.19764705882352951.868
926206AC1-098 E
Adder
1.57411764705882361.338
926214AC1-099 E
Adder
0.520.442
927255AC1-221 E
Adder
1.65176470588235281.404
927264AC1-222 E
Adder
1.66470588235294131.415
932763AC2-100 E
Adder
1.12117647058823520.953
934065AD1-033 E
Adder
2.10705882352941171.791
937226AE2-253 E
Adder
2.4552941176470592.087
918512AA1-065 E OP
Adder
2.34000000000000031.989
919153AA1-139 E2
Adder
1.71529411764705891.458
919152AA1-139 E1
Adder
1.71529411764705891.458
919710AA2-057 E
Adder
1.72588235294117661.467
920692AA2-178 E
Adder
1.72705882352941181.468
923994AB2-040_E
Adder
2.63647058823529432.241
924022AB2-043 E O1
Adder
2.11764705882352941.8
924152AB2-059 E OP
Adder
2.31764705882352961.97
925122AB2-169 E
Adder
2.4564705882352942.088
316088AB2-174 E
Adder
2.7941176470588242.375
932046AC2-012 E
Adder
5.2588235294117654.47
316311AC2-079 C
Adder
1.9682352941176471.673
932596AC2-079 E
Adder
3.2117647058823532.73
316349AD2-085 C
Adder
1.15882352941176480.985
936666AD2-085 E
Adder
1.89058823529411771.607
941591AE2-156 C
Adder
7.202352941176476.122
944581AF1-123 C
Adder
19.11999999999999716.252
944582AF1-123 E
Adder
43.7823529411764837.215
944591AF1-124 C
Adder
19.18823529411764616.31
944592AF1-124 E
Adder
43.9411764705882437.35
944601AF1-125 C
Adder
18.82588235294117516.002
944602AF1-125 E
Adder
43.0952941176470636.631
962561AG1-105 C
Adder
3.70941176470588243.153
962562AG1-105 E
Adder
2.4729411764705882.102
964241AG1-285 C
Adder
5.3647058823529414.56
964242AG1-285 E
Adder
3.57647058823529433.04
3137643SOCKMAN
Adder
0.30470588235294120.259
932632AC2-084 E
Adder
1.3917647058823531.183
934321AD1-056 C
Adder
2.72588235294117662.317
934322AD1-056 E
Adder
1.47882352941176461.257
934331AD1-057 C
Adder
1.52117647058823541.293
934332AD1-057 E
Adder
0.7917647058823530.673
934501AD1-074 C
Adder
14.2176470588235312.085
934502AD1-074 E
Adder
7.237647058823536.152
934511AD1-075 C
Adder
3.55411764705882363.021
934512AD1-075 E
Adder
1.80941176470588251.538
934612AD1-087 E
Adder
1.79882352941176471.529
935172AD1-152 E
Adder
2.6258823529411772.232
936161AD2-022 C
Adder
3.0882352941176472.625
936162AD2-022 E
Adder
1.85294117647058831.575
936171AD2-023 C
Adder
1.80117647058823521.531
936172AD2-023 E
Adder
0.97764705882352940.831
937482AD2-202 E
Adder
0.52588235294117650.447
938531AE1-072 C
Adder
7.3705882352941176.265
938532AE1-072 E
Adder
3.84235294117647053.266
938821AE1-108 C
Adder
-4.716470588235294-4.009
940481AE2-033 C
Adder
7.0611764705882366.002
940482AE2-033 E
Adder
4.7611764705882354.047
940541AE2-040 C
Adder
1.25411764705882361.066
940641AE2-051 C
50/50
11.53811.538
940642AE2-051 E
50/50
7.6927.692
941101AE2-104 C
Adder
1.31.105
941102AE2-104 E
Adder
2.06588235294117651.756
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5712.571
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.53211.532
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.0379.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.69643.696
G-007PJM->LTFIMP_G-007
CMTX_NF
1.0921.092
NYPJM->LTFIMP_NY
CLTF
0.5140.514
LGEELTFEXP_LGEE->PJM
CLTF
0.4480.448
WECLTFEXP_WEC->PJM
CLTF
0.2390.239
CPLELTFEXP_CPLE->PJM
CLTF
5.3965.396
TVALTFEXP_TVA->PJM
CLTF
2.4942.494
MECLTFEXP_MEC->PJM
CLTF
1.5141.514
LAGNLTFEXP_LAGN->PJM
CLTF
3.2073.207
SIGELTFEXP_SIGE->PJM
CLTF
0.0910.091
O66PJM->LTFIMP_O-066
CMTX_NF
6.9576.957

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:110.47 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3557.66
MW Contribution:37.07
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:116.35 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3746.98
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.70117647058823530.596
961942AG1-037 E
Adder
0.46705882352941180.397
963041AG1-153 C
50/50
8.5318.531
963042AG1-153 E
50/50
12.79612.796
966621AG1-532 C
Adder
1.93411764705882351.644
966622AG1-532 E
Adder
1.28941176470588251.096
3145413WATKINS
Adder
0.97764705882352940.831
3145723EMPORIA
Adder
0.59411764705882350.505
918492AA1-063AE OP
Adder
5.6364705882352944.791
919692AA2-053 E OP
Adder
5.797647058823534.928
920042AA2-088 E OP
Adder
14.8552941176470612.627
925785AC1-054 E
Adder
4.61294117647058853.921
927146AC1-208 E
Adder
5.3941176470588244.585
934521AD1-076 C
Adder
17.2376470588235314.652
934522AD1-076 E
Adder
8.7858823529411767.468
943172AE2-346 E
Adder
0.84117647058823530.715
944011AF1-069 C
50/50
20.20820.208
944012AF1-069 E
50/50
7.8517.851
959311AF2-222 C
Adder
22.19764705882352718.868
959312AF2-222 E
Adder
14.87294117647058812.642
960081AF2-299 C
Adder
2.5788235294117652.192
960082AF2-299 E
Adder
1.71882352941176491.461
316141AB2-099 E
Adder
0.350588235294117640.298
900672V4-068 E
Adder
0.49764705882352940.423
923263AB1-132 E OP
Adder
8.3705882352941187.115
923573AB1-173 E OP
Adder
4.5117647058823533.835
924162AB2-060 E OP
Adder
5.7141176470588244.857
924302AB2-077 E O1
Adder
1.78470588235294111.517
924312AB2-078 E O1
Adder
1.78470588235294111.517
924322AB2-079 E O1
Adder
1.78470588235294111.517
925612AC1-036 E
Adder
1.15058823529411770.978
940492AE2-034 E
Adder
4.383.723
941031AE2-094 C
50/50
61.84961.849
941032AE2-094 E
50/50
27.70127.701
946281AF1-292 C
Adder
2.13411764705882371.814
946282AF1-292 E
Adder
1.4235294117647061.21
957481AF2-042 C
Adder
76.1282352941176664.709
957482AF2-042 E
Adder
50.7517647058823643.139
3145393UNCAMP
Adder
8.6294117647058827.335
916042Z1-036 E
Adder
41.0352941176470634.88
938771AE1-103 C
Adder
4.1670588235294123.542
938772AE1-103 E
Adder
5.7541176470588234.891
933502AC2-165 E
Adder
2.92000000000000042.482
3143316POE
Adder
1.8364705882352941.561
3145256KINGFORK
Adder
1.44705882352941171.23
3145506HICKORY
50/50
3.2063.206
3150921YORKTN3
Adder
157.07176470588234133.511
926662AC1-147 E
Adder
1.93529411764705881.645
926755AC1-161 E
50/50
19.3819.38
927226AC1-216 E
Adder
9.7882352941176488.32
935112AD1-144 E
Adder
1.34352941176470591.142
942341AE2-247 C
Adder
2.10235294117647081.787
942342AE2-247 E
Adder
2.9035294117647062.468
943461AF1-017 C
Adder
1.90235294117647061.617
943462AF1-017 E
Adder
3.1035294117647062.638
943612AF1-032 E
Adder
1.34352941176470591.142
958502AF2-144 E
Adder
1.58117647058823541.344
3151021BRUNSWICKG1
50/50
12.59212.592
3151031BRUNSWICKG2
50/50
12.59212.592
3151041BRUNSWICKG3
50/50
12.59212.592
3151051BRUNSWICKS1
50/50
26.16126.161
3151081ELIZAR1
50/50
4.6844.684
3151091ELIZAR2
50/50
4.6034.603
3151101ELIZAR3
50/50
4.7444.744
3152411Z1-086 GT1
50/50
16.1716.17
3152421Z1-086 GT2
50/50
16.16416.164
3152431Z1-086 GT3
50/50
16.16416.164
3152441Z1-086 ST
50/50
28.14928.149
913392Y1-086 E
Adder
3.2023529411764712.722
916192Z1-068 E
50/50
2.7572.757
923832AB2-022 E
Adder
1.8082352941176471.537
923852AB2-025 E
Adder
1.64705882352941171.4
923862AB2-026 E
Adder
1.60941176470588251.368
938552AE1-074 E
Adder
1.70588235294117641.45
938562AE1-075 E
Adder
1.3717647058823531.166
939312AE1-162 E
Adder
1.98117647058823531.684
957492AF2-043 E
Adder
2.06705882352941161.757
962962AG1-145 E
Adder
1.77058823529411761.505
901082W1-029 E
Adder
46.16941176470588539.244
917122Z2-027 E
Adder
1.95294117647058821.66
925332AB2-190 E
Adder
9.9635294117647058.469
925522AC1-027 E
50/50
1.7851.785
942001AE2-212 C
Adder
2.7023529411764712.297
942002AE2-212 E
Adder
1.80117647058823521.531
957871AF2-081 C
50/50
14.65414.654
957872AF2-081 E
50/50
6.286.28
958161AF2-110 C
Adder
1.9682352941176471.673
958162AF2-110 E
Adder
3.1317647058823532.662
3147223TWITTYS
Adder
1.2764705882352941.085
926071AC1-086 C
Adder
28.76235294117647424.448
926072AC1-086 E
Adder
13.09058823529411911.127
936261AD2-033 C
Adder
16.90117647058823614.366
936262AD2-033 E
Adder
11.2670588235294129.577
933291AC2-141 C
50/50
45.445.4
933292AC2-141 E
50/50
19.3819.38
934621AD1-088 C
Adder
13.09882352941176511.134
934622AD1-088 E
Adder
6.3070588235294115.361
939411AE1-173 C
50/50
140.92140.92
939412AE1-173 E
50/50
93.94693.946
934012AD1-025 E
Adder
12.67294117647058910.772
916191Z1-068 C
50/50
0.0640.064
933981AD1-022 C
Adder
12.310.455
933982AD1-022 E
Adder
6.6964705882352955.692
962572AG1-106 E
Adder
1.6270588235294121.383
962571AG1-106 C
Adder
3.723.162
3145946PLYMOUTH TP
Adder
0.455294117647058850.387
3146326AYDLETT TAP
Adder
1.98470588235294131.687
316160AE1-175 E
Adder
1.46117647058823531.242
316185AD1-033 C
50/50
1.8091.809
316233AE1-074 C
Adder
3.3858823529411772.878
316274AC1-208 C
Adder
12.14823529411764710.326
316294AC1-161 C
50/50
7.4197.419
316316AC1-027 C
50/50
0.4630.463
316336AC2-165 C
Adder
12.31647058823529410.469
917332KELFORD E
Adder
2.26000000000000021.921
924516AB2-100 E1
Adder
4.0211764705882363.418
924517AB2-100 E2
Adder
4.0211764705882363.418
926206AC1-098 E
Adder
4.9364705882352944.196
926214AC1-099 E
Adder
1.63058823529411771.386
934065AD1-033 E
50/50
7.3827.382
937226AE2-253 E
50/50
8.5778.577
918512AA1-065 E OP
Adder
7.6929411764705886.539
316017AA1-139 ULT1
50/50
1.5871.587
316018AA1-139 ULT2
50/50
1.5871.587
919153AA1-139 E2
50/50
5.9935.993
919152AA1-139 E1
50/50
5.9935.993
920692AA2-178 E
Adder
5.8388235294117654.963
923994AB2-040_E
Adder
8.4588235294117657.19
924022AB2-043 E O1
Adder
6.945.899
924814AB2-134 E
Adder
16.03411764705882413.629
316084AB2-161 E
Adder
7.535294117647066.405
925122AB2-169 E
Adder
7.9211764705882356.733
316088AB2-174 E
Adder
8.9729411764705887.627
316375AC2-012 C
50/50
1.9741.974
932046AC2-012 E
50/50
19.14419.144
316311AC2-079 C
Adder
8.1047058823529426.889
932596AC2-079 E
Adder
13.22352941176470711.24
934576AD1-082 E
Adder
6.0047058823529415.104
316349AD2-085 C
Adder
4.8517647058823534.124
936666AD2-085 E
Adder
7.9152941176470596.728
316388AE2-253 GEN
50/50
2.8852.885
961611AG1-000B C
Adder
20.99058823529411617.842
941591AE2-156 C
50/50
26.1726.17
944581AF1-123 C
50/50
66.80566.805
944582AF1-123 E
50/50
152.975152.975
944591AF1-124 C
50/50
67.04267.042
944592AF1-124 E
50/50
153.529153.529
944601AF1-125 C
50/50
65.77665.776
944602AF1-125 E
50/50
150.574150.574
964241AG1-285 C
Adder
17.3776470588235314.771
964242AG1-285 E
Adder
11.584705882352949.847
3137643SOCKMAN
Adder
0.97647058823529410.83
932632AC2-084 E
Adder
4.3635294117647063.709
934501AD1-074 C
Adder
47.46117647058823540.342
934502AD1-074 E
Adder
24.16117647058823420.537
934511AD1-075 C
Adder
11.86588235294117810.086
934512AD1-075 E
Adder
6.0400000000000015.134
934612AD1-087 E
Adder
4.9741176470588234.228
935161AD1-151 C
Adder
20.16470588235294417.14
935162AD1-151 E
Adder
13.44352941176470611.427
935172AD1-152 E
Adder
7.3070588235294126.211
937482AD2-202 E
Adder
1.4552941176470591.237
938531AE1-072 C
Adder
25.73882352941176421.878
938532AE1-072 E
Adder
13.4176470588235311.405
939191AE1-149 C
Adder
14.28235294117647112.14
939192AE1-149 E
Adder
9.522352941176478.094
940431AE2-027 C
Adder
15.5729411764705913.237
940432AE2-027 E
Adder
10.382352941176478.825
940481AE2-033 C
Adder
22.89176470588235219.458
940482AE2-033 E
Adder
15.43294117647058913.118
940541AE2-040 C
Adder
4.0705882352941173.46
940641AE2-051 C
50/50
27.34927.349
940642AE2-051 E
50/50
18.23318.233
941101AE2-104 C
Adder
4.8247058823529424.101
941102AE2-104 E
Adder
7.6705882352941176.52
316303AF2-085
50/50
5.9055.905
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.96.9
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.17830.178
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.34224.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
117.126117.126
G-007PJM->LTFIMP_G-007
CMTX_NF
4.4674.467
NYPJM->LTFIMP_NY
CLTF
2.0972.097
LGEELTFEXP_LGEE->PJM
CLTF
1.2141.214
WECLTFEXP_WEC->PJM
CLTF
0.6330.633
CPLELTFEXP_CPLE->PJM
CLTF
14.4814.48
TVALTFEXP_TVA->PJM
CLTF
6.7616.761
MECLTFEXP_MEC->PJM
CLTF
4.0484.048
LAGNLTFEXP_LAGN->PJM
CLTF
8.658.65
SIGELTFEXP_SIGE->PJM
CLTF
0.2450.245
O66PJM->LTFIMP_O-066
CMTX_NF
28.45628.456

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.69 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4423.72
MW Contribution:58.05
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:114.82 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4673.36
MW Contribution:41.97
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
3.08941176470588232.626
961792AG1-021 E
Adder
2.6317647058823532.237
963041AG1-153 C
50/50
17.36617.366
963042AG1-153 E
50/50
26.04926.049
964791AG1-342 C
50/50
7.2097.209
964792AG1-342 E
50/50
4.8064.806
3138533PONTONDP
Adder
1.14470588235294120.973
3147133PAMPLIN
50/50
1.8091.809
3151531CLOVER1
50/50
32.82932.829
3151541CLOVER2
50/50
32.52432.524
3151581KERR 1
50/50
0.7110.711
3151591KERR 2
50/50
1.991.99
3151601KERR 3
50/50
1.991.99
3151611KERR 4
50/50
1.991.99
3151621KERR 5
50/50
1.991.99
925785AC1-054 E
Adder
3.75647058823529443.193
926274AC1-105 E
50/50
5.5465.546
942751AE2-291 C
Adder
13.03294117647058811.078
942752AE2-291 E
Adder
8.6882352941176467.385
943902AF1-058 E
50/50
2.7082.708
944011AF1-069 C
50/50
39.18539.185
944012AF1-069 E
50/50
15.22215.222
959311AF2-222 C
50/50
34.76234.762
959312AF2-222 E
50/50
23.29123.291
24401205PINNACLE
Adder
1.62588235294117631.382
3151631KERR 6
50/50
1.991.99
3151641KERR 7
50/50
1.991.99
3152661PLYWOOD A
50/50
2.4812.481
316118AC1-105 C
50/50
1.8951.895
316131AB2-060 C
50/50
2.8942.894
924162AB2-060 E OP
50/50
8.3338.333
924302AB2-077 E O1
50/50
2.6052.605
924312AB2-078 E O1
50/50
2.6052.605
924322AB2-079 E O1
50/50
2.6052.605
925612AC1-036 E
50/50
1.8171.817
941031AE2-094 C
50/50
119.928119.928
941032AE2-094 E
50/50
53.71353.713
946301AF1-294 C
Adder
6.3505882352941185.398
946302AF1-294 E
Adder
5.377647058823534.571
957481AF2-042 C
50/50
147.496147.496
957482AF2-042 E
50/50
98.33198.331
958211AF2-115 C
Adder
3.86117647058823543.282
958212AF2-115 E
Adder
3.2894117647058822.796
924032AB2-045 E
Adder
1.26941176470588221.079
3151021BRUNSWICKG1
50/50
25.63425.634
3151031BRUNSWICKG2
50/50
25.63425.634
3151041BRUNSWICKG3
50/50
25.63425.634
3151051BRUNSWICKS1
50/50
53.25453.254
3152411Z1-086 GT1
50/50
32.42432.424
3152421Z1-086 GT2
50/50
32.41332.413
3152431Z1-086 GT3
50/50
32.41332.413
3152441Z1-086 ST
50/50
56.44456.444
957601AF2-054 C
Adder
-1.72-1.462
942001AE2-212 C
Adder
-1.9541176470588235-1.661
3147223TWITTYS
50/50
2.0152.015
936261AD2-033 C
50/50
24.11624.116
936262AD2-033 E
50/50
16.07816.078
933291AC2-141 C
Adder
-31.96117647058824-27.167
934621AD1-088 C
50/50
23.87723.877
934622AD1-088 E
50/50
11.49611.496
316003AC1-222 C
50/50
2.0082.008
316034AC1-036 C
50/50
0.4960.496
316222AC1-221 C
50/50
2.9122.912
316237AB2-079 C O1
50/50
0.6390.639
316238AB2-078 C O1
50/50
0.6390.639
316239AB2-077 C O1
50/50
0.6390.639
316240AF1-291 C
Adder
-1.863529411764706-1.584
316248AF1-058 C
50/50
0.6640.664
316283AC2-100 C
50/50
2.3312.331
927255AC1-221 E
50/50
7.6147.614
927264AC1-222 E
50/50
8.2018.201
932763AC2-100 E
50/50
5.1295.129
313527AB2-043 C
50/50
1.011.01
924022AB2-043 E O1
50/50
10.1410.14
925997AC1-075 E
Adder
5.1705882352941174.395
926024AC1-080 E
Adder
1.71529411764705891.458
962561AG1-105 C
50/50
17.96517.965
962562AG1-105 E
50/50
11.97711.977
964241AG1-285 C
50/50
28.57228.572
964242AG1-285 E
50/50
19.04819.048
934611AD1-087 C
50/50
3.233.23
934612AD1-087 E
50/50
9.3199.319
935171AD1-152 C
50/50
3.2363.236
935172AD1-152 E
50/50
13.31413.314
936161AD2-022 C
Adder
12.41176470588235310.55
936162AD2-022 E
Adder
7.4470588235294126.33
936171AD2-023 C
Adder
7.246.154
936172AD2-023 E
Adder
3.9305882352941183.341
937481AD2-202 C
50/50
0.9370.937
937482AD2-202 E
50/50
2.7272.727
938531AE1-072 C
Adder
-16.06705882352941-13.657
940641AE2-051 C
Adder
-21.288235294117648-18.095
942461AE2-259 C
Adder
16.0152941176470613.613
942462AE2-259 E
Adder
10.6764705882352939.075
944641AF1-129 C
Adder
-87.13882352941177-74.068
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.4399.439
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.04159.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.12440.124
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
169.426169.426
G-007PJM->LTFIMP_G-007
CMTX_NF
4.1284.128
NYPJM->LTFIMP_NY
CLTF
1.8831.883
LGEELTFEXP_LGEE->PJM
CLTF
2.2642.264
WECLTFEXP_WEC->PJM
CLTF
1.2081.208
CPLELTFEXP_CPLE->PJM
CLTF
19.79519.795
TVALTFEXP_TVA->PJM
CLTF
10.7110.71
MECLTFEXP_MEC->PJM
CLTF
7.1897.189
LAGNLTFEXP_LAGN->PJM
CLTF
13.6813.68
SIGELTFEXP_SIGE->PJM
CLTF
0.4430.443
O66PJM->LTFIMP_O-066
CMTX_NF
26.2626.26

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.42 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2598.93
MW Contribution:23.85
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.96 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2758.53
MW Contribution:20.56
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.73882352941176480.628
961672AG1-007 E
Adder
0.41882352941176470.356
961791AG1-021 C
Adder
1.33058823529411761.131
961792AG1-021 E
Adder
1.13294117647058810.963
961941AG1-037 C
Adder
0.367058823529411770.312
961942AG1-037 E
Adder
0.244705882352941160.208
963041AG1-153 C
50/50
6.556.55
963042AG1-153 E
50/50
9.8259.825
964791AG1-342 C
Adder
3.09882352941176452.634
964792AG1-342 E
Adder
2.06588235294117651.756
966621AG1-532 C
Adder
1.15411764705882350.981
966622AG1-532 E
Adder
0.76941176470588240.654
3138533PONTONDP
Adder
0.49294117647058820.419
3145413WATKINS
Adder
0.451764705882352960.384
3145723EMPORIA
Adder
0.352941176470588260.3
3147133PAMPLIN
Adder
0.740.629
3151311EDGECMA
Adder
12.4152941176470610.553
3151531CLOVER1
50/50
12.55212.552
3151541CLOVER2
50/50
12.43612.436
918492AA1-063AE OP
Adder
3.0882352941176472.625
918532AA1-067 E
Adder
0.54705882352941180.465
919692AA2-053 E OP
Adder
3.30000000000000032.805
920042AA2-088 E OP
Adder
7.3835294117647066.276
925785AC1-054 E
Adder
2.882.448
926274AC1-105 E
Adder
2.3364705882352941.986
927146AC1-208 E
Adder
3.14470588235294152.673
934521AD1-076 C
Adder
9.1176470588235297.75
934522AD1-076 E
Adder
4.6470588235294123.95
943172AE2-346 E
Adder
0.440.374
943902AF1-058 E
Adder
1.11882352941176480.951
944011AF1-069 C
50/50
15.67315.673
944012AF1-069 E
50/50
6.0886.088
959311AF2-222 C
Adder
14.27882352941176512.137
959312AF2-222 E
Adder
9.5670588235294118.132
960081AF2-299 C
Adder
1.541.309
960082AF2-299 E
Adder
1.02588235294117650.872
316141AB2-099 E
Adder
0.183529411764705890.156
900672V4-068 E
Adder
0.254117647058823560.216
917342Z2-044 E
Adder
0.475294117647058870.404
922923AB1-081 E OP
Adder
2.9811764705882352.534
923263AB1-132 E OP
Adder
4.8517647058823534.124
923573AB1-173 E OP
Adder
2.65411764705882322.256
924162AB2-060 E OP
Adder
3.78117647058823543.214
924302AB2-077 E O1
Adder
1.18705882352941171.009
924312AB2-078 E O1
Adder
1.18705882352941171.009
924322AB2-079 E O1
Adder
1.18705882352941171.009
925612AC1-036 E
Adder
0.74705882352941180.635
940492AE2-034 E
Adder
2.3152941176470591.968
941031AE2-094 C
50/50
47.96747.967
941032AE2-094 E
50/50
21.48321.483
946281AF1-292 C
Adder
1.27411764705882361.083
946282AF1-292 E
Adder
0.84941176470588230.722
946301AF1-294 C
Adder
2.73529411764705932.325
946302AF1-294 E
Adder
2.3164705882352941.969
957481AF2-042 C
50/50
55.26355.263
957482AF2-042 E
50/50
36.84236.842
957861AF2-080 C
Adder
5.9388235294117655.048
957862AF2-080 E
Adder
2.6329411764705882.238
958211AF2-115 C
Adder
1.6635294117647061.414
958212AF2-115 E
Adder
1.41647058823529411.204
3145393UNCAMP
Adder
3.8517647058823533.274
916042Z1-036 E
Adder
21.67647058823529718.425
938771AE1-103 C
Adder
1.81647058823529431.544
938772AE1-103 E
Adder
2.50941176470588222.133
3143316POE
Adder
0.80823529411764720.687
3145506HICKORY
50/50
2.1612.161
926662AC1-147 E
Adder
1.23058823529411781.046
926755AC1-161 E
50/50
37.13537.135
3151021BRUNSWICKG1
50/50
9.6689.668
3151031BRUNSWICKG2
50/50
9.6689.668
3151041BRUNSWICKG3
50/50
9.6689.668
3151051BRUNSWICKS1
50/50
20.08620.086
3151081ELIZAR1
50/50
3.033.03
3151091ELIZAR2
50/50
2.9782.978
3151101ELIZAR3
50/50
3.0693.069
3152411Z1-086 GT1
50/50
12.45512.455
3152421Z1-086 GT2
50/50
12.4512.45
3152431Z1-086 GT3
50/50
12.4512.45
3152441Z1-086 ST
50/50
21.68121.681
913392Y1-086 E
Adder
1.8917647058823531.608
916192Z1-068 E
50/50
1.7941.794
923832AB2-022 E
Adder
1.06823529411764720.908
923852AB2-025 E
Adder
0.98588235294117640.838
957601AF2-054 C
Adder
-1.2505882352941176-1.063
901082W1-029 E
Adder
23.54352941176470520.012
917122Z2-027 E
Adder
1.1117647058823530.945
925522AC1-027 E
50/50
1.1581.158
957871AF2-081 C
50/50
9.4939.493
957872AF2-081 E
50/50
4.0684.068
3147223TWITTYS
Adder
0.82823529411764710.704
917512Z2-088 E OP1
Adder
3.83294117647058833.258
926071AC1-086 C
Adder
16.6705882352941214.17
926072AC1-086 E
Adder
7.5870588235294126.449
927021AC1-189 C
Adder
6.5388235294117655.558
927022AC1-189 E
Adder
3.25764705882352962.769
936261AD2-033 C
Adder
10.7294117647058829.12
936262AD2-033 E
Adder
7.1529411764705896.08
933291AC2-141 C
50/50
86.99486.994
933292AC2-141 E
50/50
37.13537.135
934621AD1-088 C
50/50
9.1619.161
934622AD1-088 E
50/50
4.4114.411
939411AE1-173 C
50/50
86.92186.921
939412AE1-173 E
50/50
57.94757.947
916191Z1-068 C
50/50
0.0420.042
933981AD1-022 C
Adder
6.4741176470588245.503
933982AD1-022 E
Adder
3.52470588235294142.996
962572AG1-106 E
Adder
0.9435294117647060.802
962571AG1-106 C
Adder
2.1564705882352941.833
3145946PLYMOUTH TP
Adder
0.24117647058823530.205
3146326AYDLETT TAP
Adder
1.25647058823529421.068
316185AD1-033 C
50/50
1.2261.226
316263AC1-034 C
Adder
5.31058823529411854.514
316274AC1-208 C
Adder
7.0835294117647066.021
316294AC1-161 C
50/50
14.21614.216
316316AC1-027 C
50/50
0.3010.301
917332KELFORD E
Adder
1.2282352941176471.044
924516AB2-100 E1
Adder
2.3717647058823532.016
924517AB2-100 E2
Adder
2.3717647058823532.016
925595AC1-034 E
Adder
4.00588235294117643.405
926206AC1-098 E
Adder
2.8317647058823532.407
926214AC1-099 E
Adder
0.93529411764705890.795
927255AC1-221 E
Adder
3.2152941176470592.733
927264AC1-222 E
Adder
3.3870588235294122.879
932763AC2-100 E
Adder
2.1788235294117651.852
934065AD1-033 E
50/50
5.0045.004
937226AE2-253 E
50/50
5.6435.643
918512AA1-065 E OP
Adder
3.98941176470588273.391
316017AA1-139 ULT1
50/50
1.0281.028
316018AA1-139 ULT2
50/50
1.0281.028
919153AA1-139 E2
50/50
3.8823.882
919152AA1-139 E1
50/50
3.8823.882
919710AA2-057 E
Adder
3.1364705882352942.666
920692AA2-178 E
Adder
3.0870588235294122.624
923994AB2-040_E
Adder
4.9776470588235294.231
924022AB2-043 E O1
Adder
4.6082352941176473.917
924152AB2-059 E OP
Adder
4.2235294117647063.59
925122AB2-169 E
Adder
4.3388235294117653.688
316088AB2-174 E
Adder
5.3035294117647064.508
316375AC2-012 C
50/50
1.2551.255
932046AC2-012 E
50/50
12.1712.17
316388AE2-253 GEN
50/50
1.8981.898
941591AE2-156 C
50/50
16.7516.75
944581AF1-123 C
50/50
45.64445.644
944582AF1-123 E
50/50
104.52104.52
944591AF1-124 C
50/50
45.80645.806
944592AF1-124 E
50/50
104.898104.898
944601AF1-125 C
50/50
44.94144.941
944602AF1-125 E
50/50
102.879102.879
962561AG1-105 C
Adder
7.7917647058823536.623
962562AG1-105 E
Adder
5.1941176470588244.415
964241AG1-285 C
Adder
11.7588235294117649.995
964242AG1-285 E
Adder
7.846.664
3137643SOCKMAN
Adder
0.56941176470588240.484
932632AC2-084 E
Adder
2.50352941176470622.128
934321AD1-056 C
Adder
4.99411764705882364.245
934322AD1-056 E
Adder
2.70941176470588242.303
934331AD1-057 C
Adder
2.78588235294117632.368
934332AD1-057 E
Adder
1.45058823529411771.233
934501AD1-074 C
Adder
25.10470588235294221.339
934502AD1-074 E
Adder
12.7810.863
934511AD1-075 C
Adder
6.2764705882352945.335
934512AD1-075 E
Adder
3.19529411764705932.716
934611AD1-087 C
50/50
1.2361.236
934612AD1-087 E
50/50
3.5653.565
935172AD1-152 E
Adder
5.2058823529411774.425
937481AD2-202 C
50/50
0.3590.359
937482AD2-202 E
50/50
1.0431.043
938531AE1-072 C
50/50
16.39816.398
938532AE1-072 E
50/50
8.5488.548
940481AE2-033 C
Adder
13.6776470588235311.626
940482AE2-033 E
Adder
9.2211764705882357.838
940541AE2-040 C
Adder
2.4364705882352942.071
940641AE2-051 C
50/50
26.4726.47
940642AE2-051 E
50/50
17.64717.647
942461AE2-259 C
Adder
6.5341176470588245.554
942462AE2-259 E
Adder
4.3564705882352943.703
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.7574.757
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.52724.527
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.91517.915
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.65881.658
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1242.124
NYPJM->LTFIMP_NY
CLTF
0.9860.986
LGEELTFEXP_LGEE->PJM
CLTF
0.950.95
WECLTFEXP_WEC->PJM
CLTF
0.5060.506
CPLELTFEXP_CPLE->PJM
CLTF
9.989.98
TVALTFEXP_TVA->PJM
CLTF
4.8674.867
MECLTFEXP_MEC->PJM
CLTF
3.1033.103
LAGNLTFEXP_LAGN->PJM
CLTF
6.2356.235
SIGELTFEXP_SIGE->PJM
CLTF
0.1890.189
O66PJM->LTFIMP_O-066
CMTX_NF
13.52713.527

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.93 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4311.71
MW Contribution:50.59
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.26 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4569.37
MW Contribution:36.83
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
2.68823529411764732.285
961792AG1-021 E
Adder
2.28941176470588251.946
963041AG1-153 C
50/50
17.20617.206
963042AG1-153 E
50/50
25.80825.808
964791AG1-342 C
50/50
6.3476.347
964792AG1-342 E
50/50
4.2324.232
3138533PONTONDP
Adder
0.99529411764705880.846
3147133PAMPLIN
50/50
1.5711.571
3151531CLOVER1
50/50
28.70828.708
3151541CLOVER2
50/50
28.44128.441
3151581KERR 1
50/50
0.6270.627
3151591KERR 2
50/50
1.7561.756
3151601KERR 3
50/50
1.7561.756
3151611KERR 4
50/50
1.7561.756
3151621KERR 5
50/50
1.7561.756
925785AC1-054 E
Adder
3.30235294117647052.807
926274AC1-105 E
50/50
4.8944.894
942751AE2-291 C
Adder
11.5670588235294139.832
942752AE2-291 E
Adder
7.7105882352941186.554
943902AF1-058 E
50/50
2.3942.394
944011AF1-069 C
50/50
45.64245.642
944012AF1-069 E
50/50
17.73117.731
959311AF2-222 C
50/50
30.29330.293
959312AF2-222 E
50/50
20.29620.296
24401205PINNACLE
Adder
1.53647058823529431.306
3151631KERR 6
50/50
1.7561.756
3151641KERR 7
50/50
1.7561.756
3152661PLYWOOD A
50/50
2.1912.191
316118AC1-105 C
50/50
1.6721.672
316131AB2-060 C
50/50
2.5322.532
924162AB2-060 E OP
50/50
7.2927.292
924302AB2-077 E O1
50/50
2.2822.282
924312AB2-078 E O1
50/50
2.2822.282
924322AB2-079 E O1
50/50
2.2822.282
925612AC1-036 E
50/50
1.5841.584
941031AE2-094 C
50/50
139.691139.691
941032AE2-094 E
50/50
62.56462.564
946301AF1-294 C
Adder
5.5247058823529414.696
946302AF1-294 E
Adder
4.6788235294117653.977
957481AF2-042 C
50/50
128.648128.648
957482AF2-042 E
50/50
85.76685.766
958211AF2-115 C
Adder
3.362.856
958212AF2-115 E
Adder
2.86235294117647052.433
3151021BRUNSWICKG1
50/50
25.39725.397
3151031BRUNSWICKG2
50/50
25.39725.397
3151041BRUNSWICKG3
50/50
25.39725.397
3151051BRUNSWICKS1
50/50
52.76252.762
3152411Z1-086 GT1
50/50
33.84633.846
3152421Z1-086 GT2
50/50
33.83433.834
3152431Z1-086 GT3
50/50
33.83433.834
3152441Z1-086 ST
50/50
58.91958.919
957601AF2-054 C
Adder
-1.6305882352941177-1.386
942001AE2-212 C
Adder
-1.851764705882353-1.574
3147223TWITTYS
50/50
1.7561.756
936261AD2-033 C
50/50
21.05721.057
936262AD2-033 E
50/50
14.03814.038
933291AC2-141 C
Adder
-30.18235294117647-25.655
934621AD1-088 C
50/50
20.82320.823
934622AD1-088 E
50/50
10.02610.026
316003AC1-222 C
50/50
1.7761.776
316034AC1-036 C
50/50
0.4320.432
316222AC1-221 C
50/50
2.632.63
316237AB2-079 C O1
50/50
0.5590.559
316238AB2-078 C O1
50/50
0.5590.559
316239AB2-077 C O1
50/50
0.5590.559
316240AF1-291 C
Adder
-1.7670588235294118-1.502
316248AF1-058 C
50/50
0.5870.587
316283AC2-100 C
50/50
2.112.11
927255AC1-221 E
50/50
6.8776.877
927264AC1-222 E
50/50
7.2547.254
932763AC2-100 E
50/50
4.6444.644
313527AB2-043 C
50/50
0.8840.884
924022AB2-043 E O1
50/50
8.8758.875
925997AC1-075 E
Adder
4.5835294117647063.896
926024AC1-080 E
Adder
1.52117647058823541.293
962561AG1-105 C
50/50
15.80415.804
962562AG1-105 E
50/50
10.53610.536
964241AG1-285 C
50/50
24.94424.944
964242AG1-285 E
50/50
16.62916.629
934611AD1-087 C
50/50
2.8252.825
934612AD1-087 E
50/50
8.158.15
935171AD1-152 C
50/50
2.8452.845
935172AD1-152 E
50/50
11.70511.705
936161AD2-022 C
Adder
11.7541176470588239.991
936162AD2-022 E
Adder
7.0529411764705895.995
936171AD2-023 C
Adder
6.8564705882352955.828
936172AD2-023 E
Adder
3.7223529411764713.164
937481AD2-202 C
50/50
0.820.82
937482AD2-202 E
50/50
2.3852.385
938531AE1-072 C
Adder
-15.17764705882353-12.901
940641AE2-051 C
Adder
-20.06823529411765-17.058
942461AE2-259 C
Adder
13.86823529411764811.788
942462AE2-259 E
Adder
9.2458823529411777.859
944641AF1-129 C
Adder
-82.61058823529412-70.219
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.0719.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5656
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.3338.33
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
162.815162.815
G-007PJM->LTFIMP_G-007
CMTX_NF
3.9723.972
NYPJM->LTFIMP_NY
CLTF
1.8141.814
LGEELTFEXP_LGEE->PJM
CLTF
2.1482.148
WECLTFEXP_WEC->PJM
CLTF
1.1471.147
CPLELTFEXP_CPLE->PJM
CLTF
19.02319.023
TVALTFEXP_TVA->PJM
CLTF
10.24910.249
MECLTFEXP_MEC->PJM
CLTF
6.8436.843
LAGNLTFEXP_LAGN->PJM
CLTF
13.09813.098
SIGELTFEXP_SIGE->PJM
CLTF
0.4210.421
O66PJM->LTFIMP_O-066
CMTX_NF
25.2725.27
CONTINGENCY 'DVP_P1-2: LN 235_SRT-A'
 OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1   /*6PRINCE EDW  230.0 - 6BRIERY      230.0
 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1   /*6PRINCE EDW  230.0 - 6FARMVIL     230.0
 OPEN BRANCH FROM BUS 313996 TO BUS 314268 CKT 1   /*6FINNEYWOOD  230.0 - 6BRIERY      230.0
 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1   /*3FARMVIL     115.0 - 6FARMVIL     230.0
 OPEN BUS 313802                                   /*6PRINCE EDW  230.0
 OPEN BUS 314268                                   /*6BRIERY      230.0
END
CONTINGENCY 'DVP_P1-2: LN 1012_SRT-A-1'
 OPEN BRANCH FROM BUS 313139 TO BUS 314679 CKT 1   /*3DRAKES B TP 115.0 - 3CENTRAL     115.0
 OPEN BRANCH FROM BUS 314679 TO BUS 314722 CKT 1   /*3CENTRAL     115.0 - 3TWITTYS     115.0
 OPEN BRANCH FROM BUS 314679 TO BUS 964240 CKT 1   /*3CENTRAL     115.0 - AG1-285 TP   115.0
END
CONTINGENCY 'DVP_P1-2: LN 2027_SRT-A-2'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026 C    230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
 OPEN BUS 923862                                   /*AB2-026 E    230.0
 OPEN BUS 938562                                   /*AE1-075 E    230.0
 OPEN BUS 958502                                   /*AF2-144 E    230.0
END
CONTINGENCY 'DVP_P1-2: LN 556_SRT-S-3'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314691 to 314692 ckt 2
314726 to 314691 ckt 1
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314268 to 313802 ckt 1
313373 to 314765 ckt 1
313996 to 314268 ckt 1
313707 to 313373 ckt 1
314765 to 314749 ckt 1
313802 to 314692 ckt 1
314902 to 314914 ckt 1
314914 to 314322 ckt 1
314914 to 314918 ckt 1
314936 to 314902 ckt 1
314923 to 314924 ckt 1
941030 to 314902 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 2201_SRT-A
OPAC112.45 %252.86B284.3513.06
GD1DVP
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
DVP_P1-2: LN 1012_SRT-A-4
OPAC182.98 %205.86B376.68166.99
GD1DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S-1
OPAC111.78 %1058.16B1182.7814.25
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 550_SRT-S
OPAC105.93 %3220.44B3411.4531.32
GD1DVP
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
OPAC105.31 %4070.2B4286.2636.83

Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 2201_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.45 %
Rating:252.86 MVA
Rating Type:B
MVA to Mitigate:284.35
MW Contribution:13.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
0.67176470588235290.571
961792AG1-021 E
Adder
0.5717647058823530.486
964791AG1-342 C
Adder
1.3564705882352941.153
964792AG1-342 E
Adder
0.90352941176470590.768
966621AG1-532 C
50/50
4.3954.395
966622AG1-532 E
50/50
2.932.93
313506AB1-173 C OP
50/50
2.3342.334
3138533PONTONDP
Adder
0.248235294117647050.211
3145723EMPORIA
50/50
1.2311.231
3147043LAWRENC
50/50
0.740.74
3151261ROARAP2
50/50
1.1521.152
3151281ROARAP4
50/50
1.091.09
918492AA1-063AE OP
50/50
2.7952.795
919692AA2-053 E OP
50/50
3.1533.153
920042AA2-088 E OP
Adder
4.6305882352941183.936
925785AC1-054 E
50/50
2.0962.096
927146AC1-208 E
Adder
2.18117647058823531.854
959311AF2-222 C
Adder
7.8188235294117656.646
959312AF2-222 E
Adder
5.2388235294117654.453
960081AF2-299 C
50/50
5.865.86
960082AF2-299 E
50/50
3.9073.907
3156063AA2-053SOLA
50/50
1.1211.121
316129AC1-054 C
50/50
0.7410.741
316131AB2-060 C
50/50
0.8950.895
900672V4-068 E
Adder
0.149411764705882360.127
923263AB1-132 E OP
Adder
2.7023529411764712.297
923573AB1-173 E OP
50/50
6.8126.812
924162AB2-060 E OP
50/50
2.5852.585
924302AB2-077 E O1
Adder
0.79529411764705890.676
924312AB2-078 E O1
Adder
0.79529411764705890.676
924322AB2-079 E O1
Adder
0.79529411764705890.676
925612AC1-036 E
Adder
0.41647058823529410.354
946281AF1-292 C
50/50
4.8514.851
946282AF1-292 E
50/50
3.2343.234
946301AF1-294 C
Adder
1.38117647058823521.174
946302AF1-294 E
Adder
1.16941176470588240.994
958211AF2-115 C
Adder
0.840.714
958212AF2-115 E
Adder
0.71529411764705890.608
3156073AA1-063SOLA
50/50
0.9590.959
3147223TWITTYS
Adder
0.46117647058823530.392
926071AC1-086 C
Adder
9.2870588235294127.894
926072AC1-086 E
Adder
4.2270588235294123.593
936261AD2-033 C
Adder
6.6258823529411775.632
936262AD2-033 E
Adder
4.4164705882352953.754
962572AG1-106 E
Adder
0.52588235294117650.447
962571AG1-106 C
Adder
1.20117647058823531.021
316274AC1-208 C
Adder
4.9105882352941184.174
917332KELFORD E
Adder
0.63764705882352950.542
924516AB2-100 E1
Adder
1.23882352941176471.053
924517AB2-100 E2
Adder
1.23882352941176471.053
926206AC1-098 E
Adder
1.7470588235294121.485
926214AC1-099 E
Adder
0.57647058823529410.49
919710AA2-057 E
Adder
1.7070588235294121.451
316181AB2-040 GEN
50/50
2.6292.629
923994AB2-040_E
50/50
12.77312.773
313527AB2-043 C
50/50
0.3160.316
924022AB2-043 E O1
50/50
3.1813.181
316087AB2-174 C
50/50
2.8212.821
316088AB2-174 E
50/50
15.67415.674
962561AG1-105 C
Adder
3.72941176470588243.17
962562AG1-105 E
Adder
2.48588235294117642.113
964241AG1-285 C
Adder
7.126.052
964242AG1-285 E
Adder
4.7470588235294124.035
3137643SOCKMAN
50/50
1.0011.001
932632AC2-084 E
Adder
1.5435294117647061.312
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.7010.701
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.4494.449
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.8192.819
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.39311.393
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3410.341
NYPJM->LTFIMP_NY
CLTF
0.1550.155
LGEELTFEXP_LGEE->PJM
CLTF
0.1740.174
WECLTFEXP_WEC->PJM
CLTF
0.0910.091
CPLELTFEXP_CPLE->PJM
CLTF
1.471.47
TVALTFEXP_TVA->PJM
CLTF
0.7390.739
MECLTFEXP_MEC->PJM
CLTF
0.5250.525
LAGNLTFEXP_LAGN->PJM
CLTF
0.9350.935
SIGELTFEXP_SIGE->PJM
CLTF
0.0330.033
O66PJM->LTFIMP_O-066
CMTX_NF
2.1672.167

Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012_SRT-A-4


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1012_SRT-A-4
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:182.98 %
Rating:205.86 MVA
Rating Type:B
MVA to Mitigate:376.68
MW Contribution:166.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3147133PAMPLIN
50/50
5.9755.975
959311AF2-222 C
50/50
99.99699.996
959312AF2-222 E
50/50
66.99766.997
925612AC1-036 E
50/50
5.155.15
3147223TWITTYS
50/50
5.7095.709
316034AC1-036 C
50/50
1.4011.401
964241AG1-285 C
50/50
74.99774.997
964242AG1-285 E
50/50
49.99849.998
942461AE2-259 C
50/50
59.99759.997
942462AE2-259 E
50/50
39.99839.998
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0040.004
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0030.003
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0050.005
NYPJM->LTFIMP_NY
CLTF
0.0020.002
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0090.009
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0030.003
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0020.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0120.012
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0020.002
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0080.008
O66PJM->LTFIMP_O-066
CMTX_NF
0.030.03
MDUPJM->LTFIMP_MDU
CLTF
00

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.78 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1182.78
MW Contribution:14.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
0.97294117647058820.827
961792AG1-021 E
Adder
0.82823529411764710.704
963041AG1-153 C
Adder
2.2623529411764711.923
963042AG1-153 E
Adder
3.39411764705882352.885
966621AG1-532 C
Adder
0.63882352941176480.543
966622AG1-532 E
Adder
0.42588235294117650.362
3138533PONTONDP
Adder
0.360.306
3145413WATKINS
Adder
0.30941176470588240.263
3145723EMPORIA
Adder
0.196470588235294150.167
3147133PAMPLIN
Adder
0.54941176470588240.467
918492AA1-063AE OP
Adder
1.8117647058823531.54
919692AA2-053 E OP
Adder
1.86823529411764721.588
920042AA2-088 E OP
Adder
4.724.012
944011AF1-069 C
Adder
5.2235294117647074.44
944012AF1-069 E
Adder
2.02941176470588271.725
959311AF2-222 C
Adder
8.5341176470588237.254
959312AF2-222 E
Adder
5.71764705882352954.86
960081AF2-299 C
Adder
0.8517647058823530.724
960082AF2-299 E
Adder
0.56823529411764710.483
900672V4-068 E
Adder
0.157647058823529420.134
923263AB1-132 E OP
Adder
2.70941176470588242.303
923573AB1-173 E OP
Adder
1.47764705882352951.256
924162AB2-060 E OP
Adder
2.0117647058823531.71
924302AB2-077 E O1
Adder
0.62117647058823530.528
924312AB2-078 E O1
Adder
0.62117647058823530.528
924322AB2-079 E O1
Adder
0.62117647058823530.528
925612AC1-036 E
Adder
0.435294117647058830.37
940492AE2-034 E
Adder
1.33882352941176451.138
941011AE2-092 C
Adder
6.9470588235294125.905
941012AE2-092 E
Adder
4.6305882352941183.936
941031AE2-094 C
Adder
15.98588235294117513.588
941032AE2-094 E
Adder
7.166.086
946281AF1-292 C
Adder
0.70588235294117650.6
946282AF1-292 E
Adder
0.47058823529411770.4
946301AF1-294 C
Adder
1.99882352941176491.699
946302AF1-294 E
Adder
1.69294117647058841.439
957481AF2-042 C
Adder
23.21647058823529619.734
957482AF2-042 E
Adder
15.4776470588235313.156
958211AF2-115 C
Adder
1.21529411764705891.033
958212AF2-115 E
Adder
1.0352941176470590.88
3145393UNCAMP
Adder
2.72117647058823582.313
916042Z1-036 E
Adder
12.43647058823529310.571
938771AE1-103 C
Adder
1.3117647058823531.115
938772AE1-103 E
Adder
1.8117647058823531.54
924032AB2-045 E
Adder
0.94941176470588240.807
933502AC2-165 E
50/50
10.19910.199
3143096IRON208
50/50
0.330.33
3143316POE
Adder
0.75647058823529410.643
3145256KINGFORK
Adder
0.455294117647058850.387
3145506HICKORY
Adder
0.94470588235294130.803
3150601CHESTF5
Adder
39.4470588235294233.53
3150651CHESTF6
Adder
11.96588235294117610.171
3150731STONECA
Adder
4.1494117647058823.527
3150831SPRUNCA
50/50
9.4469.446
3150841SPRUNCB
50/50
9.4469.446
3150921YORKTN3
Adder
52.8152941176470644.893
925865AC1-065 E
Adder
7.73058823529411756.571
926412AC1-112 E
Adder
0.56470588235294120.48
926662AC1-147 E
Adder
0.58117647058823530.494
926755AC1-161 E
Adder
0.59529411764705890.506
927226AC1-216 E
Adder
4.20352941176470553.573
934392AD1-063 E
Adder
0.487058823529411770.414
935112AD1-144 E
Adder
0.42235294117647060.359
942341AE2-247 C
Adder
0.71294117647058820.606
942342AE2-247 E
Adder
0.98470588235294120.837
943461AF1-017 C
Adder
0.64470588235294120.548
943462AF1-017 E
Adder
1.0517647058823530.894
943612AF1-032 E
Adder
0.405882352941176470.345
958502AF2-144 E
50/50
1.7771.777
966871AG1-558 C
Adder
1.27764705882352961.086
966872AG1-558 E
Adder
0.64352941176470590.547
316076AC2-137 E
Adder
0.73529411764705890.625
316157AD2-030 E
Adder
0.53411764705882360.454
913392Y1-086 E
Adder
0.9552941176470590.812
916192Z1-068 E
Adder
0.820.697
923832AB2-022 E
Adder
0.53882352941176470.458
923842AB2-024 E
Adder
0.82235294117647050.699
923852AB2-025 E
Adder
0.54941176470588240.467
923862AB2-026 E
50/50
1.8081.808
930122AB1-027 E
Adder
0.69529411764705880.591
938552AE1-074 E
50/50
1.8811.881
938562AE1-075 E
50/50
1.5421.542
939312AE1-162 E
Adder
0.67999999999999990.578
946262AF1-291 E
Adder
0.91058823529411770.774
957492AF2-043 E
Adder
0.62470588235294120.531
957601AF2-054 C
Adder
0.95294117647058830.81
957602AF2-054 E
Adder
0.63529411764705890.54
962962AG1-145 E
Adder
0.65529411764705890.557
901082W1-029 E
Adder
13.8976470588235311.813
917122Z2-027 E
Adder
0.58470588235294120.497
925332AB2-190 E
Adder
4.5752941176470593.889
925522AC1-027 E
Adder
0.53176470588235290.452
942001AE2-212 C
Adder
1.3035294117647061.108
942002AE2-212 E
Adder
0.86941176470588230.739
957832AF2-077 E
Adder
0.63529411764705890.54
957871AF2-081 C
Adder
4.3329411764705883.683
957872AF2-081 E
Adder
1.85647058823529431.578
958161AF2-110 C
Adder
0.61529411764705890.523
958162AF2-110 E
Adder
0.97882352941176460.832
3138116ELKO L286
Adder
0.76588235294117660.651
3147223TWITTYS
Adder
0.48235294117647060.41
926071AC1-086 C
Adder
9.3082352941176477.912
926072AC1-086 E
Adder
4.2364705882352943.601
936261AD2-033 C
Adder
6.5000000000000015.525
936262AD2-033 E
Adder
4.3329411764705883.683
933291AC2-141 C
Adder
12.51176470588235310.635
934621AD1-088 C
Adder
4.3294117647058833.68
934622AD1-088 E
Adder
2.08470588235294141.772
939411AE1-173 C
Adder
37.3388235294117631.738
939412AE1-173 E
Adder
24.89294117647058621.159
934012AD1-025 E
Adder
5.44117647058823554.625
927041AC1-191 C
Adder
5.1282352941176474.359
927042AC1-191 E
Adder
2.55411764705882362.171
962572AG1-106 E
Adder
0.52705882352941180.448
962571AG1-106 C
Adder
1.20352941176470571.023
3130536PAPERMILL
Adder
3.0341176470588242.579
3146326AYDLETT TAP
Adder
0.58823529411764710.5
316160AE1-175 E
Adder
0.54117647058823540.46
316169AC1-164 GEN
Adder
19.79647058823529816.827
316233AE1-074 C
50/50
3.7333.733
316240AF1-291 C
Adder
1.36588235294117651.161
316258AE1-075 C
50/50
0.5110.511
316313AB2-026 C
50/50
0.5570.557
316336AC2-165 C
50/50
13.55213.552
316405AF2-144 C
50/50
0.4340.434
924516AB2-100 E1
Adder
1.32117647058823541.123
924517AB2-100 E2
Adder
1.32117647058823541.123
926785AC1-164_E
Adder
8.8941176470588247.56
934065AD1-033 E
Adder
2.1752941176470591.849
937226AE2-253 E
Adder
2.53176470588235342.152
939612AE1-191 E
Adder
2.6082352941176472.217
919153AA1-139 E2
Adder
1.7717647058823531.506
919152AA1-139 E1
Adder
1.7717647058823531.506
920692AA2-178 E
Adder
1.78588235294117651.518
923994AB2-040_E
Adder
2.76941176470588252.354
924022AB2-043 E O1
Adder
2.4235294117647062.06
924814AB2-134 E
Adder
6.8847058823529425.852
316084AB2-161 E
Adder
2.8764705882352942.445
316088AB2-174 E
Adder
2.94705882352941152.505
932046AC2-012 E
Adder
5.7529411764705884.89
316311AC2-079 C
Adder
2.71999999999999982.312
932596AC2-079 E
Adder
4.4376470588235293.772
934146AD1-041 E
Adder
1.63058823529411771.386
934576AD1-082 E
Adder
2.2917647058823531.948
316349AD2-085 C
Adder
1.6447058823529411.398
936666AD2-085 E
Adder
2.6835294117647062.281
961611AG1-000B C
Adder
8.1152941176470596.898
941591AE2-156 C
Adder
7.8529411764705886.675
944581AF1-123 C
Adder
19.50352941176470616.578
944582AF1-123 E
Adder
44.6637.961
944591AF1-124 C
Adder
19.5717647058823516.636
944592AF1-124 E
Adder
44.82117647058823538.098
944601AF1-125 C
Adder
19.2023529411764716.322
944602AF1-125 E
Adder
43.9588235294117737.365
944631AF1-128 C
Adder
24.6823529411764720.98
964241AG1-285 C
Adder
6.0305882352941185.126
964242AG1-285 E
Adder
4.0211764705882363.418
3137643SOCKMAN
Adder
0.317647058823529450.27
934612AD1-087 E
Adder
1.55882352941176471.325
935161AD1-151 C
Adder
8.9764705882352947.63
935162AD1-151 E
Adder
5.9847058823529415.087
937482AD2-202 E
Adder
0.456470588235294130.388
938531AE1-072 C
Adder
7.6223529411764716.479
938532AE1-072 E
Adder
3.9729411764705883.377
938821AE1-108 C
Adder
8.4270588235294127.163
938822AE1-108 E
Adder
4.0211764705882363.418
939191AE1-149 C
Adder
5.8976470588235295.013
939192AE1-149 E
Adder
3.93176470588235333.342
939602AE1-190 E
Adder
0.6517647058823530.554
940431AE2-027 C
Adder
7.9682352941176476.773
940432AE2-027 E
Adder
5.3129411764705894.516
940481AE2-033 C
Adder
7.6223529411764716.479
940482AE2-033 E
Adder
5.13882352941176554.368
940541AE2-040 C
Adder
1.35764705882352941.154
940551AE2-041 C
Adder
3.25058823529411762.763
940641AE2-051 C
Adder
7.0152941176470595.963
940642AE2-051 E
Adder
4.67764705882352953.976
941101AE2-104 C
Adder
1.50823529411764711.282
941102AE2-104 E
Adder
2.39764705882352922.038
942461AE2-259 C
Adder
5.83647058823529454.961
942462AE2-259 E
Adder
3.8917647058823533.308
943471AF1-018 C
Adder
3.25058823529411762.763
944641AF1-129 C
Adder
65.7211764705882355.863
3150851SPRUNCC
50/50
0.1690.169
3150861SPRUNCD
50/50
0.1690.169
316303AF2-085
50/50
7.0277.027
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.2422.242
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.08118.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.29711.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
40.62940.629
G-007PJM->LTFIMP_G-007
CMTX_NF
2.112.11
NYPJM->LTFIMP_NY
CLTF
0.9630.963
LGEELTFEXP_LGEE->PJM
CLTF
0.7270.727
WECLTFEXP_WEC->PJM
CLTF
0.3730.373
CPLELTFEXP_CPLE->PJM
CLTF
4.6984.698
TVALTFEXP_TVA->PJM
CLTF
2.952.95
MECLTFEXP_MEC->PJM
CLTF
2.1322.132
LAGNLTFEXP_LAGN->PJM
CLTF
3.6953.695
SIGELTFEXP_SIGE->PJM
CLTF
0.1370.137
O66PJM->LTFIMP_O-066
CMTX_NF
13.41813.418

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 550_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.93 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3411.45
MW Contribution:31.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
1.99411764705882361.695
961792AG1-021 E
Adder
1.69882352941176461.444
961941AG1-037 C
Adder
0.580.493
961942AG1-037 E
Adder
0.38705882352941180.329
963041AG1-153 C
50/50
7.4237.423
963042AG1-153 E
50/50
11.13411.134
964791AG1-342 C
Adder
4.037647058823533.432
964792AG1-342 E
Adder
2.69176470588235262.288
966621AG1-532 C
50/50
1.6521.652
966622AG1-532 E
50/50
1.1011.101
3138533PONTONDP
Adder
0.73882352941176480.628
3145413WATKINS
Adder
0.7917647058823530.673
3145723EMPORIA
50/50
0.5070.507
3147133PAMPLIN
Adder
1.09647058823529430.932
3151531CLOVER1
50/50
15.58115.581
3151541CLOVER2
50/50
15.43615.436
918492AA1-063AE OP
Adder
4.7329411764705884.023
918532AA1-067 E
Adder
0.81647058823529410.694
919692AA2-053 E OP
Adder
4.9082352941176474.172
920042AA2-088 E OP
Adder
12.21058823529411810.379
925785AC1-054 E
Adder
3.9917647058823533.393
926274AC1-105 E
Adder
3.05411764705882362.596
927146AC1-208 E
Adder
4.6176470588235293.925
934521AD1-076 C
Adder
13.97999999999999911.883
934522AD1-076 E
Adder
7.12588235294117746.057
943172AE2-346 E
Adder
0.69647058823529410.592
943902AF1-058 E
Adder
1.4670588235294121.247
944011AF1-069 C
50/50
17.48817.488
944012AF1-069 E
50/50
6.7946.794
959311AF2-222 C
Adder
18.7552941176470615.942
959312AF2-222 E
Adder
12.56588235294117510.681
960081AF2-299 C
50/50
2.2032.203
960082AF2-299 E
50/50
1.4691.469
316141AB2-099 E
Adder
0.290588235294117650.247
900672V4-068 E
Adder
0.410588235294117640.349
923263AB1-132 E OP
Adder
7.1317647058823546.062
923573AB1-173 E OP
Adder
3.84588235294117683.269
924162AB2-060 E OP
Adder
4.9070588235294124.171
924302AB2-077 E O1
Adder
1.53411764705882361.304
924312AB2-078 E O1
Adder
1.53411764705882361.304
924322AB2-079 E O1
Adder
1.53411764705882361.304
925612AC1-036 E
Adder
0.96823529411764710.823
940492AE2-034 E
Adder
3.5152941176470592.988
941031AE2-094 C
50/50
53.52353.523
941032AE2-094 E
50/50
23.97223.972
946281AF1-292 C
50/50
1.8231.823
946282AF1-292 E
50/50
1.2161.216
946301AF1-294 C
Adder
4.09882352941176453.484
946302AF1-294 E
Adder
3.47176470588235332.951
957481AF2-042 C
50/50
67.59667.596
957482AF2-042 E
50/50
45.06445.064
958211AF2-115 C
Adder
2.49294117647058842.119
958212AF2-115 E
Adder
2.1235294117647061.805
3145393UNCAMP
Adder
6.9494117647058825.907
916042Z1-036 E
Adder
32.496470588235327.622
938771AE1-103 C
Adder
3.34117647058823542.84
938772AE1-103 E
Adder
4.6141176470588243.922
933502AC2-165 E
50/50
8.9548.954
3143316POE
50/50
1.5751.575
3145256KINGFORK
Adder
1.11999999999999990.952
3145506HICKORY
50/50
2.4652.465
3150831SPRUNCA
Adder
9.668.211
3150841SPRUNCB
Adder
9.668.211
926662AC1-147 E
Adder
1.49058823529411751.267
926755AC1-161 E
50/50
14.58914.589
935112AD1-144 E
Adder
1.040.884
942341AE2-247 C
Adder
1.681.428
942342AE2-247 E
Adder
2.321.972
943461AF1-017 C
Adder
1.521.292
943462AF1-017 E
Adder
2.482.108
943612AF1-032 E
Adder
1.04470588235294120.888
958502AF2-144 E
50/50
1.5151.515
3151021BRUNSWICKG1
50/50
10.91910.919
3151031BRUNSWICKG2
50/50
10.91910.919
3151041BRUNSWICKG3
50/50
10.91910.919
3151051BRUNSWICKS1
50/50
22.68422.684
3151081ELIZAR1
50/50
3.5963.596
3151101ELIZAR3
50/50
3.6413.641
3152411Z1-086 GT1
50/50
13.99713.997
3152421Z1-086 GT2
50/50
13.99313.993
3152431Z1-086 GT3
50/50
13.99313.993
3152441Z1-086 ST
50/50
24.36424.364
913392Y1-086 E
Adder
2.48823529411764752.115
916192Z1-068 E
50/50
2.1212.121
923832AB2-022 E
Adder
1.40470588235294121.194
923852AB2-025 E
50/50
1.4131.413
923862AB2-026 E
50/50
1.5421.542
938552AE1-074 E
50/50
1.5821.582
938562AE1-075 E
50/50
1.3151.315
939312AE1-162 E
Adder
1.53529411764705871.305
946262AF1-291 E
Adder
1.47176470588235291.251
957492AF2-043 E
Adder
1.6082352941176471.367
901082W1-029 E
Adder
36.1329411764705930.713
917122Z2-027 E
Adder
1.52235294117647071.294
925522AC1-027 E
50/50
1.3731.373
942001AE2-212 C
Adder
2.33058823529411761.981
942002AE2-212 E
Adder
1.55411764705882361.321
957871AF2-081 C
50/50
11.30311.303
957872AF2-081 E
50/50
4.8444.844
958161AF2-110 C
Adder
1.54823529411764721.316
958162AF2-110 E
Adder
2.46235294117647062.093
3147223TWITTYS
Adder
1.07294117647058830.912
926071AC1-086 C
Adder
24.50588235294117520.83
926072AC1-086 E
Adder
11.152941176470599.48
936261AD2-033 C
Adder
14.72588235294117712.517
936262AD2-033 E
Adder
9.8164705882352948.344
933291AC2-141 C
50/50
34.17534.175
933292AC2-141 E
50/50
14.58914.589
934621AD1-088 C
50/50
11.7711.77
934622AD1-088 E
50/50
5.6675.667
939411AE1-173 C
50/50
116.624116.624
939412AE1-173 E
50/50
77.7577.75
916191Z1-068 C
50/50
0.0490.049
933981AD1-022 C
Adder
10.0176470588235318.515
933982AD1-022 E
Adder
5.4529411764705884.635
962572AG1-106 E
Adder
1.3870588235294121.179
962571AG1-106 C
Adder
3.16941176470588242.694
3145946PLYMOUTH TP
Adder
0.36941176470588240.314
3146326AYDLETT TAP
Adder
1.53411764705882361.304
316023AB2-100 C2
50/50
1.1361.136
316185AD1-033 C
50/50
1.3851.385
316233AE1-074 C
50/50
3.143.14
316240AF1-291 C
Adder
2.20823529411764731.877
316258AE1-075 C
50/50
0.4350.435
316274AC1-208 C
Adder
10.48.84
316294AC1-161 C
50/50
5.5655.565
316313AB2-026 C
50/50
0.4750.475
316315AB2-025 C
50/50
0.4950.495
316316AC1-027 C
50/50
0.3550.355
316336AC2-165 C
50/50
11.89711.897
316365AB2-100 C1
50/50
1.1361.136
316405AF2-144 C
50/50
0.370.37
917332KELFORD E
Adder
1.8917647058823531.608
924516AB2-100 E1
50/50
3.4373.437
924517AB2-100 E2
50/50
3.4373.437
926206AC1-098 E
Adder
4.2058823529411773.575
926214AC1-099 E
Adder
1.38941176470588231.181
934065AD1-033 E
50/50
5.675.67
937226AE2-253 E
50/50
6.6076.607
918512AA1-065 E OP
Adder
6.3400000000000015.389
316017AA1-139 ULT1
50/50
1.221.22
316018AA1-139 ULT2
50/50
1.221.22
919153AA1-139 E2
50/50
4.6224.622
919152AA1-139 E1
50/50
4.6224.622
919710AA2-057 E
Adder
4.5541176470588243.871
920692AA2-178 E
Adder
4.6870588235294123.984
923994AB2-040_E
Adder
7.2105882352941176.129
924022AB2-043 E O1
Adder
5.9517647058823535.059
316084AB2-161 E
Adder
6.1764705882352945.25
925122AB2-169 E
Adder
6.5670588235294125.582
316088AB2-174 E
Adder
7.6541176470588246.506
932046AC2-012 E
Adder
14.74823529411764712.536
316311AC2-079 C
Adder
6.4611764705882355.492
932596AC2-079 E
Adder
10.5423529411764718.961
934576AD1-082 E
Adder
4.9211764705882354.183
316349AD2-085 C
Adder
3.8752941176470593.294
936666AD2-085 E
Adder
6.3235294117647065.375
316388AE2-253 GEN
50/50
2.2142.214
961611AG1-000B C
Adder
16.4223529411764713.959
941591AE2-156 C
Adder
20.1617.136
944581AF1-123 C
50/50
51.66651.666
944582AF1-123 E
50/50
118.31118.31
944591AF1-124 C
50/50
51.8551.85
944592AF1-124 E
50/50
118.738118.738
944601AF1-125 C
50/50
50.8750.87
944602AF1-125 E
50/50
116.453116.453
962561AG1-105 C
Adder
10.137647058823538.617
962562AG1-105 E
Adder
6.7588235294117655.745
964241AG1-285 C
Adder
14.29529411764705812.151
964242AG1-285 E
Adder
9.5294117647058828.1
3137643SOCKMAN
Adder
0.8317647058823530.707
932632AC2-084 E
Adder
3.71764705882352953.16
934321AD1-056 C
Adder
7.2164705882352946.134
934322AD1-056 E
Adder
3.91411764705882353.327
934331AD1-057 C
Adder
4.0258823529411773.422
934332AD1-057 E
Adder
2.09647058823529431.782
934501AD1-074 C
Adder
38.4929411764705932.719
934502AD1-074 E
Adder
19.59411764705882716.655
934511AD1-075 C
Adder
9.6235294117647058.18
934512AD1-075 E
Adder
4.8988235294117644.164
934611AD1-087 C
50/50
1.5341.534
934612AD1-087 E
50/50
4.4414.441
935171AD1-152 C
50/50
1.5911.591
935172AD1-152 E
50/50
6.5696.569
937481AD2-202 C
50/50
0.4450.445
937482AD2-202 E
50/50
1.31.3
938531AE1-072 C
Adder
19.8816.898
938532AE1-072 E
Adder
10.3635294117647068.809
939191AE1-149 C
Adder
11.92235294117647210.134
939192AE1-149 E
Adder
7.9482352941176486.756
940431AE2-027 C
Adder
13.27647058823529511.285
940432AE2-027 E
Adder
8.8517647058823537.524
940481AE2-033 C
50/50
19.63119.631
940482AE2-033 E
50/50
13.23413.234
940541AE2-040 C
50/50
3.4933.493
940641AE2-051 C
50/50
23.07223.072
940642AE2-051 E
50/50
15.38115.381
941101AE2-104 C
Adder
3.79294117647058873.224
941102AE2-104 E
Adder
6.0305882352941185.126
944641AF1-129 C
Adder
25.10705882352941421.341
316303AF2-085
50/50
5.5375.537
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.4826.482
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.12546.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.44630.446
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
116.495116.495
G-007PJM->LTFIMP_G-007
CMTX_NF
4.9764.976
NYPJM->LTFIMP_NY
CLTF
2.3122.312
LGEELTFEXP_LGEE->PJM
CLTF
1.8681.868
WECLTFEXP_WEC->PJM
CLTF
0.9550.955
CPLELTFEXP_CPLE->PJM
CLTF
13.58913.589
TVALTFEXP_TVA->PJM
CLTF
8.0788.078
MECLTFEXP_MEC->PJM
CLTF
5.5885.588
LAGNLTFEXP_LAGN->PJM
CLTF
10.14710.147
SIGELTFEXP_SIGE->PJM
CLTF
0.3550.355
O66PJM->LTFIMP_O-066
CMTX_NF
31.68131.681

Details for 8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.31 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4286.26
MW Contribution:36.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
2.30941176470588251.963
961792AG1-021 E
Adder
1.96705882352941171.672
963041AG1-153 C
50/50
17.10317.103
963042AG1-153 E
50/50
25.65425.654
964791AG1-342 C
50/50
5.7665.766
964792AG1-342 E
50/50
3.8443.844
3138533PONTONDP
Adder
0.85529411764705890.727
3147133PAMPLIN
Adder
1.261.071
3151531CLOVER1
50/50
28.86828.868
3151541CLOVER2
50/50
28.59928.599
3151581KERR 1
50/50
0.5770.577
3151591KERR 2
50/50
1.6151.615
3151601KERR 3
50/50
1.6151.615
3151611KERR 4
50/50
1.6151.615
3151621KERR 5
50/50
1.6151.615
925785AC1-054 E
Adder
2.96470588235294132.52
926274AC1-105 E
50/50
4.6164.616
942751AE2-291 C
Adder
12.11176470588235310.295
942752AE2-291 E
Adder
8.0741176470588246.863
943902AF1-058 E
50/50
2.342.34
959311AF2-222 C
50/50
22.05622.056
959312AF2-222 E
50/50
14.77814.778
24401205PINNACLE
Adder
1.6670588235294121.417
3151631KERR 6
50/50
1.6151.615
3151641KERR 7
50/50
1.6151.615
3152661PLYWOOD A
50/50
2.0932.093
316118AC1-105 C
50/50
1.5721.572
316131AB2-060 C
50/50
2.042.04
924162AB2-060 E OP
50/50
5.8965.896
924302AB2-077 E O1
50/50
1.8631.863
924312AB2-078 E O1
50/50
1.8631.863
924322AB2-079 E O1
50/50
1.8631.863
925612AC1-036 E
50/50
1.1421.142
940081AE1-250 C
Adder
12.86117647058823510.932
940082AE1-250 E
Adder
8.5741176470588247.288
946301AF1-294 C
Adder
4.7458823529411774.034
946302AF1-294 E
Adder
4.01882352941176453.416
957481AF2-042 C
50/50
129.887129.887
957482AF2-042 E
50/50
86.59186.591
958211AF2-115 C
Adder
2.88588235294117632.453
958212AF2-115 E
Adder
2.45882352941176442.09
3151021BRUNSWICKG1
50/50
25.15825.158
3151031BRUNSWICKG2
50/50
25.15825.158
3151041BRUNSWICKG3
50/50
25.15825.158
3151051BRUNSWICKS1
50/50
52.26552.265
3152411Z1-086 GT1
50/50
33.47433.474
3152421Z1-086 GT2
50/50
33.46533.465
3152431Z1-086 GT3
50/50
33.46533.465
3152441Z1-086 ST
50/50
58.26658.266
957601AF2-054 C
Adder
-1.8-1.53
964211AG1-282 C
Adder
-1.7011764705882353-1.446
942001AE2-212 C
Adder
-2.010588235294118-1.709
3147223TWITTYS
50/50
1.2661.266
936261AD2-033 C
50/50
17.43217.432
936262AD2-033 E
50/50
11.62211.622
933291AC2-141 C
Adder
-32.203529411764706-27.373
934621AD1-088 C
50/50
21.36821.368
934622AD1-088 E
50/50
10.28810.288
316003AC1-222 C
50/50
1.7441.744
316034AC1-036 C
50/50
0.3110.311
316222AC1-221 C
50/50
2.6372.637
316237AB2-079 C O1
50/50
0.4550.455
316238AB2-078 C O1
50/50
0.4550.455
316239AB2-077 C O1
50/50
0.4550.455
316240AF1-291 C
Adder
-1.9317647058823528-1.642
316248AF1-058 C
50/50
0.5710.571
316283AC2-100 C
50/50
2.1162.116
927255AC1-221 E
50/50
6.9166.916
927264AC1-222 E
50/50
7.1497.149
932763AC2-100 E
50/50
4.6734.673
313527AB2-043 C
50/50
0.7110.711
924022AB2-043 E O1
50/50
7.1597.159
316123AC1-075 C
50/50
1.3531.353
925997AC1-075 E
50/50
4.7084.708
316205AC1-080 C
50/50
0.4520.452
926024AC1-080 E
50/50
1.5621.562
962561AG1-105 C
50/50
14.10814.108
962562AG1-105 E
50/50
9.4059.405
964241AG1-285 C
50/50
17.07617.076
964242AG1-285 E
50/50
11.38411.384
934611AD1-087 C
50/50
2.842.84
934612AD1-087 E
50/50
8.2238.223
935171AD1-152 C
50/50
2.8492.849
935172AD1-152 E
50/50
11.76211.762
936161AD2-022 C
Adder
12.15882352941176610.335
936162AD2-022 E
Adder
7.29529411764705856.201
936171AD2-023 C
Adder
7.0929411764705886.029
936172AD2-023 E
Adder
3.8505882352941183.273
937481AD2-202 C
50/50
0.8240.824
937482AD2-202 E
50/50
2.4072.407
938531AE1-072 C
Adder
-16.01294117647059-13.611
940641AE2-051 C
Adder
-21.040000000000003-17.884
942461AE2-259 C
Adder
12.19882352941176510.369
942462AE2-259 E
Adder
8.1329411764705886.913
944641AF1-129 C
Adder
-90.49176470588236-76.918
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.2639.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.06671.066
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.76444.764
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
170.641170.641
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6814.681
NYPJM->LTFIMP_NY
CLTF
2.1082.108
LGEELTFEXP_LGEE->PJM
CLTF
2.7422.742
WECLTFEXP_WEC->PJM
CLTF
1.451.45
CPLELTFEXP_CPLE->PJM
CLTF
19.41719.417
TVALTFEXP_TVA->PJM
CLTF
11.71211.712
MECLTFEXP_MEC->PJM
CLTF
8.3488.348
LAGNLTFEXP_LAGN->PJM
CLTF
14.84614.846
SIGELTFEXP_SIGE->PJM
CLTF
0.5240.524
O66PJM->LTFIMP_O-066
CMTX_NF
29.75629.756
CONTINGENCY 'DVP_P1-2: LN 2201_SRT-A'
 OPEN BRANCH FROM BUS 313725 TO BUS 314563 CKT 1   /*6DRY BREAD   230.0 - 6CLUBHSE     230.0
END
CONTINGENCY 'DVP_P1-2: LN 1012_SRT-A-4'
 OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1   /*AG1-285 TP   115.0 - 3CHASCTY     115.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 550_SRT-S'
 OPEN BRANCH FROM BUS 314917 TO BUS 314926 CKT 1                /*8MT STM      500.0 - 8VALLEY      500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314562 to 314563 ckt 1
314726 to 314691 ckt 1
314322 to 314914 ckt 1
314914 to 314918 ckt 1
314940 to 941030 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AF2-222 was evaluated as a 167.0 MW injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

(No impacts were found for this analysis)

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

(No impacts were found for this analysis)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - Issues Found

Executive Summary for Dynamic Stability Analysis Using PSSE

New Service Requests (projects) in PJM Transition Cycle 1 Cluster 31 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 31 projects.

 

 

Table 1: Transition Cycle 1 Cluster 31 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO

(MW)

MWE

(MW)

MWC

(MW)

Point of Interconnection

31

AF2-222

Solar

Dominion

167

167

100

Madisonville DP-Twitty's Creek 115 kV

AG1-285

Solar

Dominion

125

125

75

Chase City-Central 115 kV

 

For the Cluster 31 base run, the latest data from DP3 was used to update the models for the Cluster 31 generation in addition to removing withdrawn generation from the dispatch.

 

Cluster 31 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. 136 initial contingencies and 169 sensitivity contingencies were studied, each with a 20 second simulation time period. The contingencies studied included:

 

  • Steady-state operation (30 seconds)
  • Three-phase faults with normal clearing time
  • Single-phase bus faults with normal clearing time
  • Single-phase faults with stuck breaker
  • Single-phase faults with delayed clearing at remote end
  • Three-phase faults with loss of multiple-circuit tower line.

The results of the analysis identified instability for outages of the Chase City – AG1-285 115 kV circuit as observed in the Phase 3 analysis. The mitigation recommended from the Phase 3 analysis was then tested and resolved the instability. Network upgrade N9630 is still recommended. N9630 updates the new AG1-285 230 kV substation to a breaker and a half scheme to accommodate 2 x 230/115 kV AG1-285 transformers, and a 230 kV line from AG1-285 to Finneywood.

 

AG1-285 DP3 data included  a 0.84 MVA base for the inverters based on  a 25? PQ curve rating.  A sensitivity was performed to determine the impacts of AG1-285 model with inverter rating 0.81 MVA at 35?. The results of the analysis matched when using the 25? and 35? ratings. The network upgrade is still required.

 

 

The following changes were required during Phase 3 analysis that would still apply for the Restudy results: 

 

The protection settings for AE2-259 regarding frequency above 62.5 Hz for more than 0 seconds and frequencies below 56.5 Hz for more than 0 seconds are commented due to tripping of the generator during the Phase 3 analysis.  

With the mitigation identified above, the results of the contingencies tested on the RTEP 2027 summer peak case found:

 

  • Cluster 31 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  • The system with Cluster 31 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for inter area modes and 4% for local modes.
  • Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus) and the final voltages are within the steady-state voltage ranges below per Dominion Energy’s transmission planning criteria.
    • P1 Category Contingencies:
      • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.01 to 1.096 p.u. for 500 kV facilities
    • P2, P4, P5, and P7 Category Contingencies:
      • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.00 to 1.096 p.u. for 500 kV facilities
  • No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

Executive Summary for Dynamic Stability Analysis Using  PSCAD/EMT

 

Model Quality Testing Report

PSCAD model for Queue project AF2-222 and AG1-285 was developed and tested individually to ensure the model was in compliance with the PJM requirements. Test summary and result of test been summarized below in table 2. it is confirmed that PSCAD model was set up properly and satisfied the PJM requirement.

 

Table 2. MQT Result for each Project

 

Test

Status

Flat Start Test 

Pass 

Voltage Step-Down 

Pass 

Voltage Step-Up 

Pass 

Frequency Step-Down, No Headroom

Pass 

Frequency Step-Down, Headroom

Pass 

Frequency Step-Up, Headroom 

Pass 

HVRT Leading

Pass 

HVRT Lagging

Pass 

LVRT Leading

Pass 

LVRT Lagging

Pass 

System Strength Test 

Pass 

Voltage Ride Through

Pass 

Phase Angle Step-Down 

Pass 

Phase Angle Step-Up 

Pass 

 

Weak Grid Assessment

This Weak Grid Assessment evaluates two projects from PJM Transition Cycle 1 (TC1) Cluster 31 for risk of voltage instability due to weak grid conditions in an EMT simulation environment.  The two projects, AF2-222 and AG1-285, were identified in the Cluster Study as having risk of undamped oscillations during a contingency condition and indicating system instability after dynamic simulation analysis in PSS/E. Three potential network upgrades were considered to resolve this instability, and Network Upgrades 2 and 3 were shown to be effective through sensitivity analysis.

This assessment, completed by INS Engineering, aims to verify the impact of Network Upgrade 2 and 3 identified in the Cluster Study, using detailed models in an EMT simulation.  Summary descriptions of each project and the two network upgrades are listed below:

 

Table 3. Summary Description of TC1 Cluster 31 Projects

 

 

 

 

Project Name

Project Type

Project Size (MW)

POI

POI Bus Number

AF2-222 Courthouse Solar

PV

167

Madisonville DP-Twitty's Creek 115 kV

959310

AG1-285 Quarter Horse Solar

PV

125

Chase City-Central 115 kV

964240

 

The following network upgrades proposed as mitigation in cluster 31 are evaluated in this weak grid assessment:

  • Network Upgrade 2: Moving AF2-222 and AG1-285 to a new 230 kV line from Farmville to Finneywood
    • Evaluated in the main body of this report
  • Network Upgrade 3: Upgrading the new AG1-285 230 kV substation to a breaker and a half scheme to accommodate 2 x 230/115 kV AG1-285 transformers, and a 230 kV line from AG1-285 to Finneywood
    • Evaluated in Appendix B
    • This option has been selected by the Transmission Owner

First, the individual project PSCAD models were evaluated for data consistency and model performance as part of the standard Model Quality Test in [2] and [3], with model updates being made where needed.  INS confirmed that the PSCAD models were set up properly and satisfied the requirements of PJM. After satisfactory configuration and performance of the individual projects were obtained, the models were integrated into a translated reduced network in PSCAD to create an overall detailed system model. 

 

For Network Upgrade 2, two representative contingency cases from the Cluster Study, considered effectively the worst case in terms of risk for weak grid instability, were simulated in the PSCAD detailed system model. For Cluster 31, the following contingency cases were chosen.

 

  • P=1.0pu, 3LG fault, 150ms, on AF2-171 POI to Farmville 230kV and loss of circuit
  • P=1.0pu, 3LG fault, 150ms, on AG1-427 to Finneywood 230kV and loss of circuit

 

Simulation results in PSCAD are summarized below.  It can be observed that both contingency cases using the detailed PSCAD system model results in a stable recovery, matching the results of the Cluster Study. 

 

Table 4. Summary of cases tested in the PSCAD system study with Network Upgrade 2

 

 

 

Case ID

Fault Description

Cluster Study Result [1]

PSCAD Study Result

Case 1.0

P=1.0pu, 3LG fault, 150ms, on AF2-171 POI to Farmville 230kV and loss of circuit

Stable

Stable

Case 2.0

P=1.0pu, 3LG fault, 150ms, on AG1-427 to Finneywood 230kV and loss of circuit

Stable

Stable

 

For Network Upgrade 3, three representative contingency cases from the Cluster Study, considered effectively the worst case in terms of risk for weak grid instability, were then simulated in the PSCAD detailed system model. Simulation results in PSCAD are summarized below.  It can be observed that all three contingency cases using the detailed PSCAD system model results in a stable recovery, matching the results of the Cluster Study. 

 

 

Table 5. Summary of cases tested in the PSCAD system study with Network Upgrade 3

 

 

 

Case ID

Fault Description

Cluster Study Result [1]

PSCAD Study Result

Case 3.1
(SP1.01)

P=1.0pu, 3LG fault, 150ms, on AF2-222 115 kV on Pamplin 115 kV circuit 154 and loss of circuit

Stable

Stable

Case 3.2
(SP1.10)

P=1.0pu, 3LG fault, 150ms, on AG1-285 POI switching station 115 kV on Chase City 115 kV circuit 1012 and loss of circuit

Stable

Stable

Case 3.3
(SP1.51)

P=1.0pu, 3LG fault, 150ms, on Finneywood 230 kV on AG1-285 – Finneywood 230 kV circuit and loss of circuit 

Stable

Stable

 

The results of this assessment show stable recovery in worst-case contingencies using either Network Upgrade 2 or 3, and support the conclusion from the Cluster Study that these proposed network upgrades mitigate the identified weak grid instability issues.

Reactive Power Analysis

The reactive power capability of AF2-222 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-065Earleys 230kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-088Boykins-Handsome 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB1-173Brink-Trego 115kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-100Clubhouse-Lakeview 230kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-080Perth-Hickory Grove 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-216Hopewell-Surry 230kVIn Service
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-084Dawson-South Justice 115kVPartially in Service - Under Construction
AC2-100Halifax-Person 230kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVPartially in Service - Under Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-103Holland-Union Camp 115 kVSuspended
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-149Disputanta-Poe 115 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-247Myrtle-Windsor 115 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-299Fields 34.5 kVActive
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-153Heritage 500 kVActive
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-532Fields 34.5 kVEngineering & Procurement
V4-068Murphy's 34.5kVIn Service
W1-029Winfall 230kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z1-068Birdneck 34.5kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-088Tarboro-Everetts 230kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 312.A.1.b and as outlined in PJM Manual 14H, Section 13, in Phase III of the Cycle, PJM coordinates with the Affected System Operators to conduct any studies required to determine the impact of the New Service Request on any Affected System and will include the Affected System Study results in Phase III System Impact Study, if available from the Affected System Operator.

If your project required an Affected System Study, the results are shown below from the Affected System Operator.

For more details, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM will list any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AF2-222 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionn9220.0Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.Cost Allocated$8,159,120
Dominionn6872Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C.Cost Allocated$7,438,616
Dominionn9217.0Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.Cost Allocated$7,415,536
Dominionn9200.0Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" conductors.Cost Allocated$5,405,710
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$3,040,619
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$2,719,216
Dominionn9378.0Replace existing 230/500 kV Carson transformer 2 with (4)-480 MVA single phase transformers.Cost Allocated$1,827,058
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$1,734,362
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$959,715
Dominionn9204.0Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.Cost Allocated$945,201
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$756,469
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$614,672
Dominionn9681.0Upgrade 1.04 Miles of 230kV transmission line 249 from 249/86 to 249/93Cost Allocated$541,856
Dominionn9201.0Replace wave trap at Carson 230 kV (Carson - Sapony).Cost Allocated$80,905
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Kraken substation into Yeat substationContingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0N/A
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0N/A
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0N/A
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0N/A
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0N/A
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0N/A
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0N/A
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0N/A
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0N/A
Grand Total:$41,639,055

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Discounted Total Cost ($USD)
$18,752,679
Allocated Cost ($USD)
$9,766,518
Time Estimate
Dec 31 2029

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

FacilityContingency
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
3CHASCTY-AG1-285 TP 115.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-294 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
41.0 MW4.3%$799,036
AF2-115 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
25.0 MW2.6%$487,224
AF2-222500.9 MW52.1%$9,766,518
AG1-021 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
20.0 MW2.1%$389,779
AG1-285374.9 MW39.0%$7,310,120
System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Allocated Cost ($USD)
$2,719,216
Time Estimate
Dec 31 2029
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$10,680,188
AF1-12414.9488 %$10,717,979
AF1-12514.6652 %$10,514,642
AF1-2940.3084 %$221,144
AF2-04229.0898 %$20,856,758
AF2-1150.1881 %$134,846
AF2-1205.5338 %$3,967,580
AF2-2223.7926 %$2,719,216
AG1-0210.1505 %$107,877
AG1-1243.0179 %$2,163,751
AG1-1355.3024 %$3,801,724
AG1-2852.8388 %$2,035,325
AG1-5365.2677 %$3,776,802

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Discounted Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$8,159,120
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
6BUCKING-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A796.0 MVA
(All)B796.0 MVA
(All)C964.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE2-29113.6 MW3.8%$1,705,384
AF1-294 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
17.8 MW5.0%$2,229,393
AF2-042163.5 MW46.2%$20,532,412
AF2-115 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
10.8 MW3.1%$1,359,435
AF2-22265.0 MW18.3%$8,159,120
AG1-021 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
8.7 MW2.4%$1,087,573
AG1-10523.6 MW6.7%$2,967,877
AG1-28541.9 MW11.8%$5,264,576
AG1-3429.2 MW2.6%$1,160,153

System Reinforcement: n6872
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6872 / dom-047
Title
Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C.
Description
Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C
Total Cost ($USD)
$59,572,939
Discounted Total Cost ($USD)
$59,572,939
Allocated Cost ($USD)
$7,438,616
Time Estimate
Dec 31 2029

Contributor

FacilityContingency
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1168.0 MVA
(All)B1195.0 MVA
(All)C1348.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-04224.3 MW40.2%$23,940,647
AF2-08013.0 MW21.4%$12,754,165
AF2-2227.6 MW12.5%$7,438,616
AG1-1068.7 MW14.3%$8,545,448
AG1-2857.0 MW11.6%$6,894,063

System Reinforcement: n9217.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9217.0 / TC1-PH2-DOM-028
Title
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$40,414,822
Discounted Total Cost ($USD)
$40,414,822
Allocated Cost ($USD)
$7,415,536
Time Estimate
45 to 46 Months

Contributor

FacilityContingency
6BUCKING-6FARMVIL 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A797.0 MVA
(All)B797.0 MVA
(All)C1116.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE2-29113.6 MW3.8%$1,550,409
AF1-294 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
17.8 MW5.0%$2,026,247
AF2-042163.5 MW46.2%$18,661,737
AF2-115 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
10.8 MW3.1%$1,235,466
AF2-22265.0 MW18.3%$7,415,536
AG1-021 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
8.7 MW2.4%$988,419
AG1-10523.6 MW6.7%$2,697,555
AG1-28541.9 MW11.8%$4,784,850
AG1-3429.2 MW2.6%$1,054,602

System Reinforcement: n9200.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9200.0 / TC1-PH2-DOM-005
Title
Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" conductors.
Description
Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$38,691,326
Discounted Total Cost ($USD)
$38,691,326
Allocated Cost ($USD)
$5,405,710
Time Estimate
45 to 46 Months

Contributor

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA797.0 MVA
SUMB797.0 MVA
SUMC1115.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-04224.3 MW39.3%$15,216,675
AF2-08012.9 MW21.0%$8,110,757
AF2-2228.6 MW14.0%$5,405,710
AG1-1068.7 MW14.0%$5,435,780
AG1-2857.2 MW11.7%$4,522,403

System Reinforcement: n9378.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9378.0 / TC1-PH3-DOM-010
Title
Replace existing 230/500 kV Carson transformer 2 with (4)-480 MVA single phase transformers.
Description
Replace Existing 230/500 kV Carson transformer 2 with (4)-480 MVA Single Phase transformers.
Total Cost ($USD)
$37,801,301
Discounted Total Cost ($USD)
$37,801,301
Allocated Cost ($USD)
$1,827,058
Time Estimate
Dec 31 2029

Contributor

FacilityContingency
6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer(Any)
Rating SetRating TypeRating Value
LLA2016.0 MVA
LLB2083.0 MVA
LLC2239.0 MVA
SUMA1707.0 MVA
SUMB1758.0 MVA
SUMC1873.0 MVA
WINA2196.0 MVA
WINB2228.0 MVA
WINC2308.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
56.2 MW22.4%$8,456,365
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
56.5 MW22.5%$8,486,733
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
55.4 MW22.0%$8,324,368
AF2-04259.5 MW23.7%$8,947,219
AF2-22212.2 MW4.8%$1,827,058
AG1-15311.7 MW4.7%$1,759,557

System Reinforcement: n9204.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9204.0 / TC1-PH2-DOM-014
Title
Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C
Total Cost ($USD)
$6,764,273
Discounted Total Cost ($USD)
$6,764,273
Allocated Cost ($USD)
$945,201
Time Estimate
42 to 43 Months

Contributor

FacilityContingency
6SAPONY-AE2-033 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA876.0 MVA
SUMB956.0 MVA
SUMC1163.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-04224.3 MW39.3%$2,660,923
AF2-08013.0 MW21.0%$1,417,583
AF2-2228.6 MW14.0%$945,201
AG1-1068.7 MW14.0%$949,798
AG1-2857.2 MW11.7%$790,769

System Reinforcement: n9681.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9681.0
Title
Upgrade 1.04 Miles of 230kV transmission line 249 from 249/86 to 249/93
Description
Reconductor 1.04 miles of 2*636 ACSR 24/7 MOT 150 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" MOT 250 on 230 kV line 249 between Carson and Chaparral
Total Cost ($USD)
$3,042,004
Discounted Total Cost ($USD)
$3,042,004
Allocated Cost ($USD)
$541,856
Time Estimate
20 to 21 Months

Contributor

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1442.0 MVA
LLB1540.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1493.0 MVA
WINB1587.0 MVA
WINC1631.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-04256.7 MW67.3%$2,048,312
AF2-22215.0 MW17.8%$541,856
AG1-28512.5 MW14.9%$451,836

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH3-DOM-009
Title
ELIMINATED FOR TC1: Replace 795 AAC 37 line lead at Farmville 115 kV.
Description
Replace 795 AAC 37 line lead at Farmville 115 kV.
Total Cost ($USD)
$391,643
Discounted Total Cost ($USD)
$102,435
Allocated Cost ($USD)
$58,534
Time Estimate
12 to 13 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
3FARMVIL-3WILLIS 115.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A270.0 MVA
(All)B289.0 MVA
(All)C351.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-222100.0 MW57.1%$58,534
AG1-28575.0 MW42.9%$43,901

System Reinforcement: n9201.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9201.0 / TC1-PH2-DOM-006
Title
Replace wave trap at Carson 230 kV (Carson - Sapony).
Description
Replace wave trap at Carson 230 kV (Carson - Sapony).
Total Cost ($USD)
$521,941
Discounted Total Cost ($USD)
$521,941
Allocated Cost ($USD)
$80,905
Time Estimate
14 to 15 Months

Contributor

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA876.0 MVA
SUMB956.0 MVA
SUMC1163.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-04224.3 MW43.6%$227,742
AF2-0806.9 MW12.3%$64,253
AF2-2228.6 MW15.5%$80,905
AG1-1068.7 MW15.6%$81,355
AG1-2857.2 MW13.0%$67,685

System Reinforcement: b3694.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3694.8
Title
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA.
Description
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA. Upgrade terminal equipment at Carson and Locks to not limit the new conductor rating.
Cost Information
Time Estimate
May 03 2025

Not Contingent

Note: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1047.0 MVA
(All)B1047.0 MVA
(All)C1204.0 MVA
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA

System Reinforcement: n9379.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9379.0 / TC1-PH3-DOM-011
Title
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.
Description
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase 500/230 kV transformers.
Total Cost ($USD)
$37,836,293
Discounted Total Cost ($USD)
$37,836,293
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-222 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-222 could receive cost allocation. Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 is a potential Aggregate Pool Contributor.

FacilityContingency
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-222 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-222 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: n9139.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9139.0 / TC1-PH1-DOM-073
Title
Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.
Description
Wreck and rebuild 37.41 miles of 500kV transmission line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA. Remove wave traps.
Total Cost ($USD)
$245,455,768
Discounted Total Cost ($USD)
$245,455,768
Allocated Cost ($USD)
$0
Time Estimate
69 to 70 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-222 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-222 could receive cost allocation. Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9264.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9264.0 / TC1-PH1-DOM-080
Title
Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1.
Description
Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1.
Total Cost ($USD)
$582,006
Discounted Total Cost ($USD)
$582,006
Allocated Cost ($USD)
$0
Time Estimate
12 to 13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-222 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-222 could receive cost allocation. Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 is a potential Aggregate Pool Contributor.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2650.0 MVA
(All)B2831.0 MVA
(All)C3663.0 MVA

System Reinforcement: n9191.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9191.0 / TC1-PH1-DOM-090
Title
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.
Description
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$256,706,175
Discounted Total Cost ($USD)
$256,706,175
Allocated Cost ($USD)
$0
Time Estimate
74 to 75 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-222 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-222 could receive cost allocation. Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 is a potential Aggregate Pool Contributor.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9138.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9138.0 / TC1-PH1-DOM-070
Title
ELIM TC1: Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.
Description
Wreck and rebuild 22.59 miles of Line 511 between Carson and Rawlings with three (3) 1351 ACSS/TW and associated substation work.
Total Cost ($USD)
$111,130,292
Discounted Total Cost ($USD)
$111,130,292
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-222 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-222 could receive cost allocation. Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.

System Reinforcement: n9250.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9250.0 / TC1-PH2-DOM-044
Title
ELIM TC1: Construct a new 22.59 mile line between Carson and Rawlings Substations.
Description
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Total Cost ($USD)
$108,728,086
Discounted Total Cost ($USD)
$108,728,086
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-222 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-222 could receive cost allocation. Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-040
Title
ELIM TC1: Wreck and rebuild 18.75 miles of Line 594 btwn Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) Dipper at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 18.75 miles of Line 594 between Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$128,018,212
Discounted Total Cost ($USD)
$128,018,212
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-222 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-222 could receive cost allocation. Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9247.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9247.0 / TC1-PH2-DOM-041
Title
ELIM TC1: Wreck and rebuild 14.02 miles of Line 573 btwn Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 14.02 miles of Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA
Total Cost ($USD)
$99,636,684
Discounted Total Cost ($USD)
$99,636,684
Allocated Cost ($USD)
$0
Time Estimate
48 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-222 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-222 could receive cost allocation. Although AF2-222 may not presently have cost responsibility for this upgrade, AF2-222 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n8492

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492
Title
Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.
Description
Wreck and rebuild one (1) overhead 500kV transmission line that will start at the existing Fentress 500 kV Substation and terminate at the existing Yadkin 500 kV Substation, located approximately 13.5 miles away.
Total Cost ($USD)
$80,172,278
Allocated Cost ($USD)
$3,040,619
Time Estimate
26 to 27 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$11,942,543
AF1-12414.9488 %$11,984,793
AF1-12514.6652 %$11,757,425
AF1-2940.3084 %$247,251
AF2-04229.0898 %$23,321,955
AF2-1150.1881 %$150,804
AF2-1205.5338 %$4,436,574
AF2-2223.7926 %$3,040,614
AG1-0210.1505 %$120,659
AG1-1243.0179 %$2,419,519
AG1-1355.3024 %$4,251,055
AG1-2852.8388 %$2,275,931
AG1-5365.2677 %$4,223,235

System Reinforcement: n9267.0

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9267.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9267.0 / TC1-PH2-DOM-067
Title
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.
Description
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner substations with single (1) 768.2 ACSS/TW “Maumee” at 250 degrees C. This new line will be on separate transmission towers from the existing Northern Neck and Moon Corner line 1059. Station expansion is required at Northern Neck and Moon Corner to accommodate the new line.
Total Cost ($USD)
$45,730,074
Allocated Cost ($USD)
$1,734,362
Time Estimate
45 to 46 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$6,811,998
AF1-12414.9488 %$6,836,097
AF1-12514.6652 %$6,706,407
AF1-2940.3084 %$141,032
AF2-04229.0898 %$13,302,787
AF2-1150.1881 %$86,018
AF2-1205.5338 %$2,530,611
AF2-2223.7926 %$1,734,359
AG1-0210.1505 %$68,824
AG1-1243.0179 %$1,380,088
AG1-1355.3024 %$2,424,791
AG1-2852.8388 %$1,298,185
AG1-5365.2677 %$2,408,923

System Reinforcement: n9259.0

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9259.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9259.0
Title
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Description
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Total Cost ($USD)
$25,304,902
Allocated Cost ($USD)
$959,715
Time Estimate
38 to 39 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$3,769,444
AF1-12414.9488 %$3,782,779
AF1-12514.6652 %$3,711,014
AF1-2940.3084 %$78,040
AF2-04229.0898 %$7,361,145
AF2-1150.1881 %$47,599
AF2-1205.5338 %$1,400,323
AF2-2223.7926 %$959,714
AG1-0210.1505 %$38,084
AG1-1243.0179 %$763,677
AG1-1355.3024 %$1,341,767
AG1-2852.8388 %$718,356
AG1-5365.2677 %$1,332,986

System Reinforcement: n8492.1

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.1
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.1
Title
Two Breaker Additions at Fentress Substation.
Description
Install Two 5000 amp GIS Breakers at Fentress Substation to connect the new 500 kV line 5005.
Total Cost ($USD)
$19,945,879
Allocated Cost ($USD)
$756,469
Time Estimate
30 to 36 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$2,971,158
AF1-12414.9488 %$2,981,670
AF1-12514.6652 %$2,925,103
AF1-2940.3084 %$61,513
AF2-04229.0898 %$5,802,216
AF2-1150.1881 %$37,518
AF2-1205.5338 %$1,103,765
AF2-2223.7926 %$756,467
AG1-0210.1505 %$30,019
AG1-1243.0179 %$601,947
AG1-1355.3024 %$1,057,610
AG1-2852.8388 %$566,224
AG1-5365.2677 %$1,050,689

System Reinforcement: n8492.2

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.2
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.2
Title
Expand Yadkin Substation to accommodate the new 500 kV line.
Description
Expansion of yadkins 500 kV switchyard to accommodate the new 500 kV line which includes addition of 5000 amp GIS breakers and relocation of the existing suffolk -yadkin 500 kV line#565
Total Cost ($USD)
$16,207,123
Allocated Cost ($USD)
$614,672
Time Estimate
15 to 16 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$2,414,229
AF1-12414.9488 %$2,422,770
AF1-12514.6652 %$2,376,807
AF1-2940.3084 %$49,983
AF2-04229.0898 %$4,714,620
AF2-1150.1881 %$30,486
AF2-1205.5338 %$896,870
AF2-2223.7926 %$614,671
AG1-0210.1505 %$24,392
AG1-1243.0179 %$489,115
AG1-1355.3024 %$859,366
AG1-2852.8388 %$460,088
AG1-5365.2677 %$853,743

System Reinforcement: b4000.325

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.326

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.327

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: s3047.2

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: s3047.2
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3047.2
Title
Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.
Description
Install (2) 1400 MVA 500-230 kV transformers and associated 500 kV and 230 kV equipment (breakers, switches, leads) at Vint Hill Substation to supply the area with a 500 kV source Cut and loop 500 kV line #535 Loudoun – Meadowbrook and #569 Loudoun - Morrisville as the 500 kV sources into the proposed 500 kV ring bus Vint Hill Substation will be expanded to the north of the existing site to accommodate the 500 kV ring required for the addition of the new transformers Existing terminations for 230 kV line #2174 Wheeler – Vint Hill, line #2101 Bristers – Vint Hill, and line #2163 Liberty – Vint Hill will be rearranged to terminate into the expanded Vint Hill Substation 230 kV line #2114 Remington CT – Rollins Ford will also be cut and looped into the expanded Vint Hill Substation due to spatial constraints along the existing right-of-way.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.312

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.312
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.312
Title
Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.
Description
Rebuild 500kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. New conductor to have a summer rating of 4357 MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.313

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.313
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.313
Title
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Description
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.356

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.356
Title
Build a new 500 kV line from Vint Hill to Wishing Star.
Description
Build a new 500kV line from Vint Hill to Wishing Star. The line will be supported on single circuit monopoles. New conductor to have a summer rating of 4357 MVA. Line length is approximately 16.59 miles
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.357

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.357
Title
Build a new 500 kV line from Morrisville to Vint Hill.
Description
Build a new 500kV line from Morrisville to Vint Hill. New conductor to have a summer rating of 4357 MVA. Line length is approximately 19.71 miles.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.354

AF2-222 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.354
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.354
Title
Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.
Description
Install terminal equipment at Wishing Star substation to support a 5000A line to Vint Hill. Update relay settings for 500kV Lines #546 and #590.
Cost Information
Cost Alloc Type
Contingent

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AF2-222


AF2-222 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
StabilityDominionn9630.0 / TC1-PH3-DOM-013Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Topology500.9 MW52.1%Cost Allocated$9,766,518
Load FlowDominion(Pending) / TC1-PH3-DOM-009ELIMINATED FOR TC1: Replace 795 AAC 37 line lead at Farmville 115 kV.Eliminated100.0 MW57.1%Cost Allocated$58,534
Contributions into Topology or Eliminated Reinforcement Total:$9,825,052
AF2-222 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$3,040,619
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$2,719,216
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$1,734,362
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$959,715
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$756,469
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$614,672
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.Contingent$0
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.Contingent$0
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.Contingent$0
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.Contingent$0
Dominionb4000.348Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0
Dominionb4000.346Cut-in 500kV line from Kraken substation into Yeat substationContingent$0
Dominionb4000.345Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0
Region Topology Upgrade Total:$9,825,053

Attachments

AF2-222 One Line Diagram

AF2-222 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.