AF2-226 Final System Impact Study (Retool 2) Report

v2.00 released 2026-05-14 11:52

Katydid Road 345 kV

20.0 MW Capacity / 50.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Blackstone Wind Farm, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Commonwealth Edison Company.

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.

The AF2-226 Final System Impact Study (Retool 1) Report is available for download here.

Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed a Storage facility located in the Commonwealth Edison Company zone — Lasalle County, Illinois. The installed facilities will have a total capability of 350.0 MW with 20.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AF2-226
Project Name:
Katydid Road 345 kV
Project Developer Name:
Blackstone Wind Farm, LLC
State:
Illinois
County:
Lasalle
Transmission Owner:
Commonwealth Edison Company
MFO:
350.0
MWE:
50.0
MWC:
20.0
Battery Storage Specification:
200.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2027

Physical Interconnection Facility Study

Reviewed

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AF2-226 will interconnect on the ComEd transmission system via a direct connection to the TSS 196 Katydid Rd 345 kV substation and will share interconnection facilities with O22 (Top Crop I and Top Crop II) and AF2-319.

 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AF2-226 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AF2-226Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$256,082$256,082
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$627,185$627,185
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0
AFS - Non-PJM Violations$194,483 **$0 **
Total$1,077,750$883,267

* Contributes to calculation for Security. See Security Requirement Section of this report for additional detail.

** This value reflects the results at the time of the report posting and it is subject to change. AFS – Non-PJM Violations are not subject to Security. For latest AFS – Non-PJM Violations, please refer to the latest Affected System Study Report for your project.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF2-226/AF2-319

Security has been calculated for the AF2-226/AF2-319 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF2-226/AF2-319
Project(s): AF2-226/AF2-319
Final Agreement Security (A): $1,766,534
Portion of Costs Already Paid (B): $0
Revised Net Security (C): A − B = $1,766,534
Security on Hand with PJM (D): $1,766,535
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

As shown in the one line diagram, this Interconnection Request is sharing the Point of Interconnection (POI) with one or more other Interconnection Requests.  Refer to the one line for other Interconnection Requests at this POI.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Oversight and SCADA, Communication and metering settings changes to accommodate the new energy storage.

$153,870$0$102,212$0$256,082$256,082

Based on the scope of work for the Interconnection Facilities, it is expected to take 18 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Notes on Cost Estimate:

  1. These estimates are Order-of-Magnitude estimates of the costs that ComEd would bill to the Project Developer for this interconnection. These estimates are based on a one-line electrical diagram of the project and the information provided by the Project Developer.
  2. There were no site visits performed for these estimates. There may be costs related to specific site related issues that are not identified in these estimates. The site reviews will be performed during the Facilities Study or during detailed engineering.
  3. These estimates are not a guarantee of the maximum amount payable by the Project Developer and the actual costs of ComEd's work may differ significantly from these estimates. The Project Developer will be responsible for paying actual costs of ComEd's work in accordance with the PJM Open Access Transmission Tariff.
  4. The Project Developer is responsible for all engineering, procurement, testing and construction of all equipment on the Project Developer’s side of the Point of Change in Ownership.

These cost estimates do not include cost of acquiring right-of-way for the transmission line and purchasing any additional land, if needed, for the line terminations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. ComEd interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AF2-226 was evaluated as a 50.0 MW (20.0 MW Capacity) injection in the ComEd area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP
05DUMONT-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC111.58 %4142.0B4621.4911.36
GD1AEP
05DUMONT-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC100.3 %4142.0B4154.5410.28
GD1AEP
05SORENS-05MARYSV 765.0 kV Ckt 1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC102.72 %4142.0B4254.7111.96
GD1AMIL/CE
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A
TowerAC156.1 %1489.0B2324.3236.98
GD1AMIL/CE
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
COMED_P4_012-45-BT4-5___SRT-A
BreakerAC125.61 %1489.0B1870.2814.56

Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.58 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4621.49
MW Contribution:11.36
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.09 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4642.69
MW Contribution:11.39
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936512AD2-066 E
Adder
10.422352941176478.859
936511AD2-066 C
Adder
15.63294117647058813.288
295109WESTBROOK E
Adder
10.5011764705882368.926
957331AF2-027 C
Adder
4.55882352941176453.875
966092AG1-478 E
Adder
0.93411764705882360.794
962692AG1-118 E
Adder
27.37176470588235223.266
962691AG1-118 C
Adder
41.05764705882353434.899
272363ESS H440 ; R
Adder
4.9294117647058834.19
959091AF2-200 C
Adder
26.65176470588235322.654
274682WAUKEGAN ;7U
Adder
75.2058823529411763.925
938851AE1-113 C
Adder
14.73882352941176612.528
942652AE2-281 E
Adder
9.6188235294117658.176
942651AE2-281 C
Adder
1.56588235294117651.331
274708KENDALL ;3C
50/50
7.1797.179
274789SE CHICAG;6U
Adder
8.7305882352941187.421
274790SE CHICAG;7U
Adder
8.7305882352941187.421
274791SE CHICAG;8U
Adder
8.7305882352941187.421
936372AD2-047 E
Adder
39.1894117647058833.311
962781AG1-127 C
Adder
12.98470588235294311.037
933911AD1-013 C
Adder
3.45176470588235332.934
276591L-013 2
Adder
6.7270588235294125.718
274795SE CHICAG;2U
Adder
8.722352941176477.414
274793SE CHICAG;0U
Adder
8.722352941176477.414
24796705OLIV SLR E
Adder
0.56117647058823530.477
274776LINCOLN ;7U
50/50
3.1483.148
934721AD1-100 C
50/50
5.4595.459
943591AF1-030 C
Adder
15.67647058823529313.325
943592AF1-030 E
Adder
7.75647058823529446.593
937002AD2-134 E
Adder
18.96352941176470716.119
290021O50 E
Adder
35.73058823529411430.371
936292AD2-038 E
Adder
27.6482352941176523.501
274770LINCOLN ;1U
50/50
3.1483.148
274772LINCOLN ;3U
50/50
3.1483.148
274771LINCOLN ;2U
50/50
3.1483.148
941551AE2-152 C
50/50
21.32121.321
274891CAYUG;2U E
Adder
26.69411764705882522.69
957332AF2-027 E
Adder
6.8388235294117655.813
274709KENDALL ;3S
50/50
4.7494.749
958481AF2-142 C
Adder
20.41411764705882317.352
274676JOLIET 29;8U
Adder
129.0705882352941109.71
960681AF2-359 C
Adder
17.43176470588235514.817
274661LASCO STA;2U
50/50
44.22744.227
943122AE2-341 E
Adder
11.5764705882352949.84
939322AE1-163 E
Adder
67.3294117647058857.23
961502AF2-441 E
Adder
28.3752941176470624.119
934722AD1-100 E
50/50
165.829165.829
274660LASCO STA;1U
50/50
44.08744.087
960591AF2-350 C
Adder
14.1647058823529412.04
275149KELLYCK ;1E
Adder
33.05176470588235628.094
960592AF2-350 E
Adder
9.4435294117647068.027
960751AF2-366 C
Adder
12.94823529411764811.006
960582AF2-349 E
Adder
67.176470588235357.1
942422AE2-255 E
Adder
16.7482352941176514.236
957371AF2-031 C
Adder
1.8882352941176471.605
965791AG1-447 C
Adder
12.78352941176470610.866
965682AG1-436 E
Adder
11.6211764705882359.878
270101AB1-080 CT2
50/50
9.0469.046
270100AB1-080 CT1
50/50
9.0469.046
960752AF2-366 E
Adder
8.6317647058823527.337
957471AF2-041 C
Adder
39.97764705882353633.981
293644O22 E1
Adder
26.09999999999999822.185
960281AF2-319 C
Adder
4.5435294117647063.862
957372AF2-031 E
Adder
2.83294117647058832.408
270102AB1-080 ST
50/50
9.7879.787
274774LINCOLN ;5U
50/50
3.1483.148
933412AC2-154 E
Adder
7.3188235294117656.221
936371AD2-047 C
Adder
8.0270588235294126.823
936461AD2-060 C
Adder
4.7211764705882354.013
939351AE1-166 C
50/50
18.47818.478
293519PILOT HIL;1E
Adder
33.05176470588235628.094
293061N-015 E
Adder
28.1705882352941223.945
274674JOLIET 9 ;6U
Adder
65.8517647058823555.974
943121AE2-341 C
Adder
23.57411764705882420.038
295111SUBLETTE E
Adder
5.1047058823529424.339
939321AE1-163 C
Adder
10.9611764705882359.317
274675JOLIET 29;7U
Adder
129.0741176470588109.713
961501AF2-441 C
Adder
18.91647058823529516.079
274777LINCOLN ;8U
50/50
3.1483.148
933912AD1-013 E
Adder
5.5141176470588244.687
958491AF2-143 C
Adder
20.1317647058823517.112
959351AF2-226 C
Adder
4.5435294117647063.862
962782AG1-127 E
Adder
8.6411764705882357.345
946671AF1-331 C
Adder
4.4823529411764713.81
274794SE CHICAG;1U
Adder
8.722352941176477.414
274775LINCOLN ;6U
50/50
3.1483.148
939352AE1-166 E
50/50
17.05717.057
294392P-010 E
Adder
35.776470588235330.41
290108LEEDK;1U E
Adder
44.7835294117647138.066
916221Z1-073 E
Adder
13.82117647058823511.748
934101AD2-000 1
Adder
10.767058823529419.152
959092AF2-200 E
Adder
1.71529411764705891.458
957472AF2-041 E
Adder
19.98823529411764716.99
942421AE2-255 C
Adder
5.5823529411764714.745
958492AF2-143 E
Adder
13.42117647058823411.408
959352AF2-226 E
Adder
6.8141176470588245.792
910542X3-005 E
Adder
1.32588235294117651.127
24344105CKG2
50/50
60.20560.205
941552AE2-152 E
50/50
14.21414.214
274890CAYUG;1U E
Adder
26.69411764705882522.69
938852AE1-113 E
Adder
52.2552941176470644.417
274710KENDALL ;4C
50/50
7.1017.101
958482AF2-142 E
Adder
13.60941176470588211.568
274792SE CHICAG;9U
Adder
8.722352941176477.414
960682AF2-359 E
Adder
11.6211764705882359.878
933411AC2-154 C
Adder
4.4858823529411773.813
958011AF2-095 C
Adder
20.3976470588235317.338
966091AG1-478 C
Adder
3.71294117647058863.156
966441AG1-513 C
Adder
0.93411764705882360.794
274711KENDALL ;4S
50/50
4.7494.749
274687WILL CNTY;4U
Adder
119.63882352941177101.693
274788SE CHICAG;5U
Adder
8.7305882352941187.421
918052AA1-018 E OP
Adder
29.625.16
293645O22 E2
Adder
29.89294117647058625.409
960282AF2-319 E
Adder
6.8141176470588245.792
965681AG1-436 C
Adder
17.43176470588235514.817
274773LINCOLN ;4U
50/50
3.1483.148
958012AF2-095 E
Adder
13.59882352941176411.559
290051GSG-6; E
Adder
19.6129411764705916.671
966442AG1-513 E
Adder
1.40117647058823551.191
274683WAUKEGAN ;8U
Adder
81.1376470588235368.967
934111AD2-000 2
Adder
10.7964705882352949.177
920272AA2-123 E
Adder
5.30941176470588254.513
276170Z1-108 E
Adder
5.3764705882352954.57
276675AE2-062 E
Adder
0.275294117647058860.234
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
2.162.16
TVALTFEXP_TVA->PJM
CLTF
5.7885.788
O66PJM->LTFIMP_O-066
CMTX_NF
37.87737.877
CBM West 1LTFEXP_CBM-W1->PJM
CBM
268.722268.722
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.75157.751
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
27.4427.44
LAGNLTFEXP_LAGN->PJM
CLTF
10.83410.834
NYPJM->LTFIMP_NY
CLTF
3.0993.099
LGEELTFEXP_LGEE->PJM
CLTF
1.2131.213
WECLTFEXP_WEC->PJM
CLTF
7.2467.246
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.4271.427
G-007PJM->LTFIMP_G-007
CMTX_NF
5.9085.908
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.7140.714
SIGELTFEXP_SIGE->PJM
CLTF
0.7480.748

Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.3 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4154.54
MW Contribution:10.28
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.95 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4181.2
MW Contribution:10.32
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936372AD2-047 E
Adder
35.5211764705882430.193
962781AG1-127 C
Adder
11.7810.013
933911AD1-013 C
Adder
3.1305882352941182.661
934721AD1-100 C
50/50
4.9494.949
943591AF1-030 C
Adder
14.23411764705882412.099
943592AF1-030 E
Adder
7.042352941176475.986
937002AD2-134 E
Adder
17.1976470588235314.618
290021O50 E
Adder
32.3317647058823527.482
936292AD2-038 E
Adder
25.01411764705882521.262
966092AG1-478 E
Adder
0.84705882352941180.72
962692AG1-118 E
Adder
24.8329411764705921.108
936512AD2-066 E
Adder
9.4294117647058838.015
936511AD2-066 C
Adder
14.14470588235294112.023
295109WESTBROOK E
Adder
9.522352941176478.094
957331AF2-027 C
Adder
4.1352941176470593.515
941551AE2-152 C
50/50
19.33119.331
957332AF2-027 E
Adder
6.20352941176470555.273
274709KENDALL ;3S
50/50
4.3114.311
958481AF2-142 C
Adder
18.47882352941176615.707
274676JOLIET 29;8U
Adder
117.0517647058823699.494
960681AF2-359 C
Adder
15.73176470588235413.372
274661LASCO STA;2U
50/50
40.14440.144
943122AE2-341 E
Adder
10.5105882352941178.934
939322AE1-163 E
Adder
60.916470588235351.779
961502AF2-441 E
Adder
25.7070588235294121.851
276591L-013 2
Adder
6.1047058823529415.189
274795SE CHICAG;2U
Adder
7.8964705882352946.712
274793SE CHICAG;0U
Adder
7.8964705882352946.712
24796705OLIV SLR E
Adder
0.50470588235294120.429
274776LINCOLN ;7U
50/50
2.8662.866
934722AD1-100 E
50/50
150.352150.352
274660LASCO STA;1U
50/50
40.01840.018
960591AF2-350 C
Adder
12.83882352941176610.913
275149KELLYCK ;1E
Adder
29.9576470588235325.464
960592AF2-350 E
Adder
8.5588235294117647.275
960751AF2-366 C
Adder
11.747058823529419.985
960582AF2-349 E
Adder
60.9223529411764751.784
942422AE2-255 E
Adder
15.1552941176470612.882
957371AF2-031 C
Adder
1.71058823529411771.454
965791AG1-447 C
Adder
11.5364705882352939.806
965682AG1-436 E
Adder
10.4870588235294118.914
270101AB1-080 CT2
50/50
8.1638.163
270100AB1-080 CT1
50/50
8.1638.163
960752AF2-366 E
Adder
7.8305882352941176.656
957471AF2-041 C
Adder
36.2482352941176530.811
293644O22 E1
Adder
23.6270588235294120.083
960281AF2-319 C
Adder
4.11294117647058853.496
957372AF2-031 E
Adder
2.56470588235294142.18
270102AB1-080 ST
50/50
8.8338.833
274774LINCOLN ;5U
50/50
2.8662.866
939351AE1-166 C
50/50
16.75316.753
293519PILOT HIL;1E
Adder
29.9576470588235325.464
293061N-015 E
Adder
25.55058823529411821.718
274674JOLIET 9 ;6U
Adder
59.7105882352941250.754
943121AE2-341 C
Adder
21.4047058823529418.194
295111SUBLETTE E
Adder
4.6294117647058833.935
939321AE1-163 C
Adder
9.9164705882352958.429
274675JOLIET 29;7U
Adder
117.0552941176470799.497
961501AF2-441 C
Adder
17.1376470588235314.567
274777LINCOLN ;8U
50/50
2.8662.866
933912AD1-013 E
Adder
5.04.25
958491AF2-143 C
Adder
18.21411764705882415.482
959351AF2-226 C
Adder
4.11294117647058853.496
933412AC2-154 E
Adder
6.6329411764705885.638
936371AD2-047 C
Adder
7.2752941176470596.184
936461AD2-060 C
Adder
4.283.638
962782AG1-127 E
Adder
7.8388235294117666.663
939352AE1-166 E
50/50
15.46515.465
294392P-010 E
Adder
32.44823529411764427.581
290108LEEDK;1U E
Adder
40.62588235294117634.532
916221Z1-073 E
Adder
12.53411764705882410.654
934101AD2-000 1
Adder
9.7588235294117668.295
959092AF2-200 E
Adder
16.1105882352941213.694
957472AF2-041 E
Adder
18.12352941176470715.405
942421AE2-255 C
Adder
5.0517647058823534.294
958492AF2-143 E
Adder
12.1423529411764710.321
959352AF2-226 E
Adder
6.1694117647058825.244
910542X3-005 E
Adder
1.20117647058823531.021
24344105CKG2
50/50
55.59555.595
941552AE2-152 E
50/50
12.88712.887
938852AE1-113 E
Adder
47.2858823529411740.193
274710KENDALL ;4C
50/50
6.4476.447
958482AF2-142 E
Adder
12.31882352941176410.471
274792SE CHICAG;9U
Adder
7.8964705882352946.712
960682AF2-359 E
Adder
10.4870588235294118.914
962691AG1-118 C
Adder
37.2494117647058831.662
272363ESS H440 ; R
Adder
4.4705882352941183.8
959091AF2-200 C
Adder
24.1647058823529420.54
274682WAUKEGAN ;7U
Adder
68.2257.987
938851AE1-113 C
Adder
13.33647058823529511.336
942652AE2-281 E
Adder
8.7023529411764717.397
942651AE2-281 C
Adder
1.41647058823529411.204
274708KENDALL ;3C
50/50
6.5186.518
274789SE CHICAG;6U
Adder
7.9058823529411776.72
274790SE CHICAG;7U
Adder
7.9058823529411776.72
274791SE CHICAG;8U
Adder
7.9058823529411776.72
933411AC2-154 C
Adder
4.0658823529411773.456
958011AF2-095 C
Adder
18.48823529411764715.715
966091AG1-478 C
Adder
3.3647058823529412.86
966441AG1-513 C
Adder
0.84705882352941180.72
959081AF2-199 C
Adder
12.0823529411764710.27
274711KENDALL ;4S
50/50
4.3114.311
274687WILL CNTY;4U
Adder
108.4752941176470592.204
274788SE CHICAG;5U
Adder
7.9058823529411776.72
918052AA1-018 E OP
Adder
26.79411764705882222.775
293645O22 E2
Adder
27.06117647058823323.002
960282AF2-319 E
Adder
6.1694117647058825.244
965681AG1-436 C
Adder
15.73176470588235413.372
274773LINCOLN ;4U
50/50
2.8662.866
274770LINCOLN ;1U
50/50
2.8662.866
274772LINCOLN ;3U
50/50
2.8662.866
274771LINCOLN ;2U
50/50
2.8662.866
946671AF1-331 C
Adder
4.0647058823529413.455
274794SE CHICAG;1U
Adder
7.8964705882352946.712
274775LINCOLN ;6U
50/50
2.8662.866
958012AF2-095 E
Adder
12.32588235294117710.477
290051GSG-6; E
Adder
17.78705882352941415.119
966442AG1-513 E
Adder
1.27058823529411781.08
959082AF2-199 E
Adder
5.44117647058823554.625
274683WAUKEGAN ;8U
Adder
73.6000000000000162.56
934111AD2-000 2
Adder
9.7858823529411768.318
276675AE2-062 E
Adder
0.249411764705882360.212
920272AA2-123 E
Adder
4.8164705882352954.094
276170Z1-108 E
Adder
4.877647058823534.146
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
1.8261.826
TVALTFEXP_TVA->PJM
CLTF
5.8945.894
O66PJM->LTFIMP_O-066
CMTX_NF
35.23735.237
CBM West 1LTFEXP_CBM-W1->PJM
CBM
243.013243.013
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.43653.436
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
24.86724.867
LAGNLTFEXP_LAGN->PJM
CLTF
10.36210.362
NYPJM->LTFIMP_NY
CLTF
2.8932.893
LGEELTFEXP_LGEE->PJM
CLTF
3.0323.032
WECLTFEXP_WEC->PJM
CLTF
6.5716.571
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.1751.175
G-007PJM->LTFIMP_G-007
CMTX_NF
5.4955.495
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.5610.561
SIGELTFEXP_SIGE->PJM
CLTF
0.7770.777

Details for 05SORENS-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SORENS-05MARYSV 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.72 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4254.71
MW Contribution:11.96
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05MARYSV 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.53 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4288.42
MW Contribution:11.99
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957331AF2-027 C
Adder
4.7600000000000014.046
957842AF2-078 E
Adder
19.25058823529411716.363
957841AF2-078 C
Adder
28.8752941176470624.544
966092AG1-478 E
Adder
0.97647058823529410.83
962691AG1-118 C
Adder
17.81058823529411615.139
274682WAUKEGAN ;7U
Adder
78.4505882352941366.683
274789SE CHICAG;6U
Adder
9.2541176470588237.866
274790SE CHICAG;7U
Adder
9.2541176470588237.866
274791SE CHICAG;8U
Adder
9.2541176470588237.866
936372AD2-047 E
Adder
40.95294117647059634.81
276591L-013 2
Adder
6.9894117647058825.941
274795SE CHICAG;2U
Adder
9.2541176470588237.866
274793SE CHICAG;0U
Adder
9.2541176470588237.866
24796705OLIV SLR E
50/50
0.6480.648
274776LINCOLN ;7U
50/50
3.1893.189
943591AF1-030 C
Adder
16.21647058823529613.784
943592AF1-030 E
Adder
8.0235294117647066.82
964401AG1-302 C
Adder
44.7047058823529537.999
964402AG1-302 E
Adder
29.80235294117647325.332
24642205MAYFLWER
50/50
0.2440.244
944961AF1-161 C
50/50
6.3426.342
274770LINCOLN ;1U
50/50
3.1893.189
274772LINCOLN ;3U
50/50
3.1893.189
274771LINCOLN ;2U
50/50
3.1893.189
958392AF2-133 E
Adder
29.59529411764705725.156
944242AF1-092 E
Adder
8.822352941176477.499
24647605NILES
50/50
0.0550.055
962601AG1-109 C
50/50
6.3426.342
939391AE1-170 C
50/50
16.1416.14
24335205NTRDAM
50/50
2.4332.433
24641605TWIN BRNCH
50/50
0.0710.071
247643Z2-116 C
50/50
0.0550.055
941551AE2-152 C
Adder
22.1447058823529418.823
957332AF2-027 E
Adder
7.1400000000000016.069
958481AF2-142 C
Adder
21.49882352941176618.274
274676JOLIET 29;8U
Adder
134.5764705882353114.39
945421AF1-207 C
Adder
8.1811764705882366.954
960681AF2-359 C
Adder
18.9305882352941216.091
944241AF1-092 C
Adder
28.98705882352941324.639
943122AE2-341 E
Adder
11.97411764705882410.178
961502AF2-441 E
Adder
29.9258823529411825.437
940581AE2-045 C
Adder
20.59882352941176717.509
24335305OLIVE
50/50
0.2120.212
934722AD1-100 E
Adder
172.2376470588235146.402
960591AF2-350 C
Adder
14.80235294117647312.582
275149KELLYCK ;1E
Adder
34.53882352941176529.358
960592AF2-350 E
Adder
9.8682352941176488.388
957371AF2-031 C
Adder
2.01.7
959142AF2-205 E
Adder
19.65764705882352816.709
945502AF1-215 E
Adder
30.13647058823529425.616
965791AG1-447 C
Adder
13.88235294117647111.8
965682AG1-436 E
Adder
12.62117647058823510.728
943001AE2-323 C
Adder
16.5152941176470614.038
24441505OLIV SLR C
50/50
0.1060.106
944931AF1-158 C
50/50
3.7133.713
270101AB1-080 CT2
50/50
9.9719.971
270100AB1-080 CT1
50/50
9.9719.971
24643105BUCHANAN
50/50
0.0840.084
24307105BERRINSP G
50/50
0.1370.137
944161AF1-084 C
Adder
13.66941176470588311.619
293644O22 E1
Adder
27.48823529411764723.365
960281AF2-319 C
Adder
4.7847058823529424.067
957372AF2-031 E
Adder
3.02.55
270102AB1-080 ST
50/50
10.78910.789
944162AF1-084 E
Adder
7.80823529411764656.637
936142AD2-020 E
50/50
9.6669.666
274774LINCOLN ;5U
50/50
3.1893.189
939351AE1-166 C
Adder
19.19176470588235316.313
293519PILOT HIL;1E
Adder
34.53882352941176529.358
293061N-015 E
Adder
29.2470588235294124.86
274674JOLIET 9 ;6U
Adder
68.6729411764705958.372
943121AE2-341 C
Adder
24.38470588235294320.727
274675JOLIET 29;7U
Adder
134.57764705882354114.391
961501AF2-441 C
Adder
19.95058823529411616.958
940582AE2-045 E
Adder
28.28352941176470724.041
24344005CKG1
50/50
43.40443.404
274777LINCOLN ;8U
50/50
3.1893.189
959351AF2-226 C
Adder
4.7847058823529424.067
959141AF2-205 C
Adder
29.48588235294117525.063
942242AE2-236 E
Adder
4.183.553
944932AF1-158 E
50/50
15.54815.548
945111AF1-176 C
50/50
39.50439.504
957892AF2-083 E
50/50
12.77812.778
24796605WTRV SLR E
Adder
0.57647058823529410.49
933412AC2-154 E
Adder
7.6482352941176476.501
936371AD2-047 C
Adder
8.3882352941176477.13
936461AD2-060 C
Adder
4.9341176470588244.194
274794SE CHICAG;1U
Adder
9.2541176470588237.866
945422AF1-207 E
Adder
35.13176470588235429.862
958391AF2-133 C
Adder
44.3929411764705937.734
939352AE1-166 E
Adder
17.7152941176470615.058
294392P-010 E
Adder
37.143529411764731.572
934101AD2-000 1
Adder
11.2117647058823529.53
959352AF2-226 E
Adder
7.17647058823529356.1
942241AE2-236 C
Adder
9.7541176470588238.291
910542X3-005 E
Adder
1.39411764705882371.185
945112AF1-176 E
50/50
36.6236.62
936141AD2-020 C
50/50
15.70315.703
270144AA2-116_ST
50/50
14.10214.102
24344105CKG2
50/50
55.84955.849
941552AE2-152 E
Adder
14.76352941176470612.549
958482AF2-142 E
Adder
14.3329411764705912.183
274792SE CHICAG;9U
Adder
9.2541176470588237.866
958402AF2-134 E
Adder
10.0458823529411768.539
960682AF2-359 E
Adder
12.62117647058823510.728
247969Z2-116 E
50/50
0.3340.334
957891AF2-083 C
50/50
25.55625.556
961051AF2-396 C
50/50
50.74150.741
939392AE1-170 E
50/50
22.28822.288
933411AC2-154 C
Adder
4.6870588235294123.984
958011AF2-095 C
Adder
21.31529411764705618.118
966091AG1-478 C
Adder
3.88000000000000033.298
966441AG1-513 C
Adder
0.96823529411764710.823
274687WILL CNTY;4U
Adder
124.97176470588235106.226
274788SE CHICAG;5U
Adder
9.2541176470588237.866
964861AG1-349 C
Adder
38.6632.861
958382AF2-132 E
Adder
29.80235294117647325.332
943002AE2-323 E
Adder
8.097647058823536.883
24647705NILES
50/50
0.0550.055
270142AA2-116_CT1
50/50
15.92315.923
918052AA1-018 E OP
Adder
31.17294117647058726.497
293645O22 E2
Adder
31.48352941176470726.761
960282AF2-319 E
Adder
7.17647058823529356.1
965681AG1-436 C
Adder
18.9305882352941216.091
936632AD2-079 E O1
50/50
2.0472.047
274773LINCOLN ;4U
50/50
3.1893.189
958012AF2-095 E
Adder
14.21058823529411812.079
966442AG1-513 E
Adder
1.45294117647058841.235
274683WAUKEGAN ;8U
Adder
84.6588235294117671.96
934111AD2-000 2
Adder
11.2741176470588259.583
964862AG1-349 E
Adder
25.7729411764705921.907
958381AF2-132 C
Adder
44.7047058823529537.999
270216AD2-079_C O1
50/50
0.5020.502
270143AA2-116_CT2
50/50
15.92315.923
276170Z1-108 E
Adder
5.6058823529411764.765
276675AE2-062 E
Adder
0.287058823529411760.244
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
2.3872.387
TVALTFEXP_TVA->PJM
CLTF
8.198.19
O66PJM->LTFIMP_O-066
CMTX_NF
44.79244.792
CBM West 1LTFEXP_CBM-W1->PJM
CBM
319.618319.618
CBM West 2LTFEXP_CBM-W2->PJM
CBM
75.36775.367
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
30.0930.09
LAGNLTFEXP_LAGN->PJM
CLTF
13.77113.771
NYPJM->LTFIMP_NY
CLTF
3.633.63
LGEELTFEXP_LGEE->PJM
CLTF
3.8433.843
WECLTFEXP_WEC->PJM
CLTF
7.6087.608
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.531.53
G-007PJM->LTFIMP_G-007
CMTX_NF
6.9886.988
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.7280.728
SIGELTFEXP_SIGE->PJM
CLTF
1.2341.234

Details for POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AMIL/CE
Facility Description:
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:156.1 %
Rating:1489.0 MVA
Rating Type:B
MVA to Mitigate:2324.32
MW Contribution:36.98
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274677POWERTON ;5U
50/50
92.92392.923
270839OTTER CRK; R
50/50
2.3562.356
958481AF2-142 C
50/50
66.56766.567
939322AE1-163 E
50/50
222.621222.621
942422AE2-255 E
50/50
33.52733.527
936291AD2-038 C
50/50
2.9812.981
293644O22 E1
50/50
84.98584.985
960281AF2-319 C
50/50
14.79314.793
939321AE1-163 C
50/50
36.24136.241
274862TOP CROP ;2U
50/50
4.2434.243
274879MINONK ;1U
50/50
2.9212.921
958491AF2-143 C
50/50
66.56566.565
959351AF2-226 C
50/50
14.79314.793
942421AE2-255 C
50/50
11.17611.176
958492AF2-143 E
50/50
44.37644.376
274861TOP CROP ;1U
50/50
2.2242.224
959352AF2-226 E
50/50
22.18922.189
274678POWERTON ;6U
50/50
92.92292.922
938852AE1-113 E
50/50
104.604104.604
958482AF2-142 E
50/50
44.37844.378
938851AE1-113 C
50/50
29.50429.504
942652AE2-281 E
50/50
31.80331.803
942651AE2-281 C
50/50
5.1775.177
918052AA1-018 E OP
50/50
96.52396.523
293645O22 E2
50/50
97.33797.337
960282AF2-319 E
50/50
22.18922.189
290021O50 E
50/50
71.52471.524
936292AD2-038 E
50/50
91.41591.415
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.9150.915
O66PJM->LTFIMP_O-066
CMTX_NF
5.7815.781
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6460.646
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0622.062
NYPJM->LTFIMP_NY
CLTF
0.4660.466
WECLTFEXP_WEC->PJM
CLTF
0.0510.051
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
5.0885.088
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.7310.731
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
4.1374.137
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9030.903
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.460.46
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
8.1528.152
MDUPJM->LTFIMP_MDU
CLTF
0.3110.311

Details for POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT4-5___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AMIL/CE
Facility Description:
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_012-45-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.61 %
Rating:1489.0 MVA
Rating Type:B
MVA to Mitigate:1870.28
MW Contribution:14.56
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AMIL/CE
Facility Description:
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_012-45-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.57 %
Rating:1489.0 MVA
Rating Type:B
MVA to Mitigate:1869.78
MW Contribution:14.57
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938851AE1-113 C
50/50
41.1141.11
942652AE2-281 E
50/50
17.09117.091
942651AE2-281 C
50/50
2.7822.782
276658AB1-122 CT1
50/50
-3.03-3.03
290021O50 E
50/50
99.6699.66
936292AD2-038 E
50/50
49.12849.128
274677POWERTON ;5U
50/50
77.94477.944
270839OTTER CRK; R
50/50
0.9680.968
958481AF2-142 C
50/50
27.3427.34
939322AE1-163 E
50/50
119.639119.639
942422AE2-255 E
50/50
46.71646.716
936291AD2-038 C
50/50
1.6021.602
293644O22 E1
50/50
33.45733.457
960281AF2-319 C
50/50
5.8245.824
276660AB1-122 CT2
50/50
58.51858.518
939321AE1-163 C
50/50
19.47619.476
274862TOP CROP ;2U
50/50
1.671.67
274879MINONK ;1U
50/50
4.074.07
958491AF2-143 C
50/50
35.77235.772
959351AF2-226 C
50/50
5.8245.824
934101AD2-000 1
50/50
-1.5-1.5
942421AE2-255 C
50/50
15.57215.572
958492AF2-143 E
50/50
23.84823.848
274861TOP CROP ;1U
50/50
0.8760.876
959352AF2-226 E
50/50
8.7358.735
274678POWERTON ;6U
50/50
78.26978.269
938852AE1-113 E
50/50
145.752145.752
958482AF2-142 E
50/50
18.22618.226
918052AA1-018 E OP
50/50
39.64339.643
293645O22 E2
50/50
38.31938.319
960282AF2-319 E
50/50
8.7358.735
934111AD2-000 2
50/50
28.96228.962
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
1.061.06
O66PJM->LTFIMP_O-066
CMTX_NF
5.5525.552
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7280.728
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.352.35
NYPJM->LTFIMP_NY
CLTF
0.4420.442
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
7.1267.126
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.8590.859
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
5.9655.965
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8680.868
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.5480.548
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
11.65611.656
MDUPJM->LTFIMP_MDU
CLTF
0.5030.503
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT Z1   /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1    /*05HANG R     765.0 - 05JEFRSO     765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1   /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1   /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1   /*05HANG R     765.0 - 05JEFRSO     765.0
 REMOVE UNIT 1A FROM BUS 247245                    /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                    /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                    /*05HRKG1S      18.0
 REMOVE UNIT 2 FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2A FROM BUS 247248                    /*05HRKG2A      18.0
 REMOVE UNIT 2S FROM BUS 247250                    /*05HRKG2S      18.0
END
CONTINGENCY 'COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A'
 TRIP BRANCH FROM BUS 270790 TO BUS 270770 CKT 1   /*KATYDID  ; B 345.0 - GOODINGS ; B 345.0
 TRIP BRANCH FROM BUS 270827 TO BUS 270769 CKT 1   /*NEVADA   ; R 345.0 - GOODINGS ; R 345.0
END
CONTINGENCY 'COMED_P4_012-45-BT4-5___SRT-A'
 TRIP BRANCH FROM BUS 270716 TO BUS 270736 CKT 1    /*DRESDEN  ; B 345.0 - ELWOOD   ; B 345.0
 TRIP BRANCH FROM BUS 270716 TO BUS 276659 CKT 1    /*DRESDEN  ; B 345.0 - AB1-122 TAP2 345.0
 TRIP BRANCH FROM BUS 270736 TO BUS 270737 CKT Z1   /*ELWOOD   ; B 345.0 - ELWOOD   ; R 345.0
END
243206 to 246999 ckt 1
246999 to 242928 ckt 1
270855 to 349662 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP
05DUMONT-05SORENS 765.0 kV Ckt 1 line
AEP_P7-1_#11046___SRT-A
TowerAC100.51 %4142.0B4163.0610.2
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC143.99 %1075.0B1547.912.89
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC143.99 %1075.0B1547.872.89
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Base Case
SingleAC108.83 %1075.0A1169.931.81
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC146.62 %971.0B1423.725.03
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC146.52 %971.0B1422.695.07
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC146.52 %971.0B1422.695.07
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC126.45 %1399.0B1768.977.37
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC126.44 %1399.0B1768.97.37
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC126.42 %1399.0B1768.677.34
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC100.5 %1399.0B1405.952.95
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC100.5 %1399.0B1405.932.95
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC110.61 %1399.0B1547.417.42
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC110.58 %1399.0B1546.987.45
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC110.57 %1399.0B1546.927.45
GD1CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4-6_116-345-R______SRT-A
BreakerAC107.57 %2297.0STE2471.014.57
GD1CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4_116-45-L11614__SRT-A
BreakerAC103.27 %2297.0STE2372.114.9
GD1CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4_112-45-BT4-5___SRT-A
BreakerAC100.41 %2297.0STE2306.4717.84
GD1AMIL/CE
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A
TowerAC156.02 %1489.0B2323.1936.98
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC126.43 %970.0STE1226.45.07
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC126.43 %970.0STE1226.45.07
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC126.41 %970.0STE1226.155.03
GD1CE
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
COMED_P4_112-65-BT5-6___SRT-A
BreakerAC115.85 %1469.0STE1701.876.62
GD1CE
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
COMED_P4_112-65-BT2-3___SRT-A
BreakerAC118.88 %1469.0STE1746.336.8
GD1CE
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_112-65-BT5-6___SRT-A
BreakerAC116.01 %1469.0STE1704.126.62
GD1CE
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_112-65-BT2-3___SRT-A
BreakerAC119.03 %1469.0STE1748.526.8

Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P7-1_#11046___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11046___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.51 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4163.06
MW Contribution:10.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957372AF2-031 E
Adder
2.5752941176470592.189
274774LINCOLN ;5U
50/50
2.8472.847
957331AF2-027 C
Adder
4.1035294117647063.488
936511AD2-066 C
Adder
13.97882352941176411.882
936512AD2-066 E
Adder
9.3188235294117667.921
295109WESTBROOK E
Adder
9.3964705882352947.987
274790SE CHICAG;7U
Adder
7.93999999999999956.749
274791SE CHICAG;8U
Adder
7.93999999999999956.749
274789SE CHICAG;6U
Adder
7.93999999999999956.749
966092AG1-478 E
Adder
0.84235294117647050.716
274682WAUKEGAN ;7U
Adder
67.7223529411764757.564
942651AE2-281 C
Adder
1.40235294117647061.192
942652AE2-281 E
Adder
8.6164705882352957.324
962691AG1-118 C
Adder
36.9352941176470631.395
962692AG1-118 E
Adder
24.62352941176470720.93
938851AE1-113 C
Adder
13.18235294117647211.205
272363ESS H440 ; R
Adder
4.4117647058823533.75
959091AF2-200 C
Adder
23.87882352941176520.297
24796705OLIV SLR E
Adder
0.52823529411764710.449
24344105CKG2
50/50
55.71355.713
274793SE CHICAG;0U
Adder
7.9305882352941186.741
274795SE CHICAG;2U
Adder
7.9305882352941186.741
274776LINCOLN ;7U
50/50
2.8472.847
936372AD2-047 E
Adder
35.4435294117647130.127
276591L-013 2
Adder
6.0611764705882365.152
962781AG1-127 C
Adder
11.6764705882352959.925
933911AD1-013 C
Adder
3.08941176470588232.626
274660LASCO STA;1U
50/50
39.69139.691
943592AF1-030 E
Adder
6.9952941176470595.946
943591AF1-030 C
Adder
14.1412.019
936292AD2-038 E
Adder
24.7670588235294121.052
290021O50 E
Adder
31.95647058823529527.163
937002AD2-134 E
Adder
16.9705882352941214.425
960681AF2-359 C
50/50
16.69316.693
941551AE2-152 C
Adder
19.2223529411764716.339
274676JOLIET 29;8U
Adder
116.6341176470588299.139
958481AF2-142 C
Adder
18.34588235294117515.594
957332AF2-027 E
Adder
6.1552941176470595.232
961502AF2-441 E
Adder
25.77529411764705721.909
274661LASCO STA;2U
50/50
39.8239.82
943122AE2-341 E
Adder
10.4411764705882368.875
939322AE1-163 E
Adder
60.3141176470588351.267
270100AB1-080 CT1
50/50
8.4898.489
270101AB1-080 CT2
50/50
8.4898.489
965791AG1-447 C
50/50
12.24212.242
965682AG1-436 E
50/50
11.12911.129
957371AF2-031 C
Adder
1.71647058823529421.459
274770LINCOLN ;1U
50/50
2.8472.847
274773LINCOLN ;4U
50/50
2.8472.847
274772LINCOLN ;3U
50/50
2.8472.847
274771LINCOLN ;2U
50/50
2.8472.847
960591AF2-350 C
Adder
12.81058823529411810.889
960592AF2-350 E
Adder
8.5411764705882357.26
275149KELLYCK ;1E
Adder
29.89176470588235525.408
934722AD1-100 E
Adder
149.50823529411764127.082
960751AF2-366 C
Adder
11.6435294117647079.897
942422AE2-255 E
Adder
14.97882352941176412.732
960582AF2-349 E
Adder
60.28705882352941451.244
293644O22 E1
Adder
23.4329411764705919.918
960281AF2-319 C
Adder
4.0788235294117653.467
960752AF2-366 E
Adder
7.7623529411764716.598
957471AF2-041 C
Adder
35.81882352941176630.446
274794SE CHICAG;1U
Adder
7.9305882352941186.741
274775LINCOLN ;6U
50/50
2.8472.847
274777LINCOLN ;8U
50/50
2.8472.847
936371AD2-047 C
Adder
7.2600000000000016.171
936461AD2-060 C
Adder
4.2705882352941183.63
933412AC2-154 E
Adder
6.6188235294117655.626
962782AG1-127 E
Adder
7.77058823529411856.605
946671AF1-331 C
Adder
4.0117647058823533.41
24344005CKG1
50/50
36.32436.324
961501AF2-441 C
Adder
17.18352941176470614.606
293519PILOT HIL;1E
Adder
29.89176470588235525.408
939351AE1-166 C
Adder
16.6614.161
274675JOLIET 29;7U
Adder
116.6376470588235399.142
274674JOLIET 9 ;6U
Adder
59.4611764705882450.542
293061N-015 E
Adder
25.37882352941176521.572
943121AE2-341 C
Adder
21.2623529411764718.073
939321AE1-163 C
Adder
9.8188235294117648.346
295111SUBLETTE E
Adder
4.5682352941176473.883
944932AF1-158 E
Adder
12.53176470588235210.652
959351AF2-226 C
Adder
4.0788235294117653.467
958491AF2-143 C
Adder
18.03411764705882415.329
933912AD1-013 E
Adder
4.9341176470588244.194
910542X3-005 E
Adder
1.20352941176470571.023
939352AE1-166 E
Adder
15.37764705882352913.071
294392P-010 E
Adder
32.2305882352941227.396
959352AF2-226 E
Adder
6.117647058823535.2
934101AD2-000 1
Adder
9.6658823529411778.216
958492AF2-143 E
Adder
12.0223529411764710.219
942421AE2-255 C
Adder
4.9929411764705884.244
290108LEEDK;1U E
Adder
40.1234.102
916221Z1-073 E
Adder
12.36823529411764810.513
957472AF2-041 E
Adder
17.90941176470588315.223
959092AF2-200 E
Adder
15.91882352941176613.531
960682AF2-359 E
50/50
11.12911.129
274792SE CHICAG;9U
Adder
7.9305882352941186.741
941552AE2-152 E
Adder
12.8152941176470610.893
958482AF2-142 E
Adder
12.2305882352941210.396
938852AE1-113 E
Adder
46.73529411764706539.725
274890CAYUG;1U E
Adder
15.40235294117647213.092
274788SE CHICAG;5U
Adder
7.93999999999999956.749
958011AF2-095 C
Adder
18.44823529411764815.681
933411AC2-154 C
Adder
4.0564705882352943.448
274687WILL CNTY;4U
Adder
108.1341176470588391.914
966091AG1-478 C
Adder
3.35058823529411762.848
966441AG1-513 C
Adder
0.84235294117647050.716
959081AF2-199 C
Adder
11.9410.149
270102AB1-080 ST
50/50
9.1849.184
965681AG1-436 C
50/50
16.69316.693
293645O22 E2
Adder
26.8376470588235322.812
960282AF2-319 E
Adder
6.117647058823535.2
918052AA1-018 E OP
Adder
26.60117647058823622.611
958012AF2-095 E
Adder
12.29882352941176610.454
934111AD2-000 2
Adder
9.7294117647058828.27
966442AG1-513 E
Adder
1.26235294117647071.073
274683WAUKEGAN ;8U
Adder
73.0517647058823662.094
290051GSG-6; E
Adder
17.55176470588235614.919
959082AF2-199 E
Adder
5.9694117647058835.074
920272AA2-123 E
Adder
4.76941176470588254.054
276675AE2-062 E
Adder
0.249411764705882360.212
276170Z1-108 E
Adder
4.837647058823534.112
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
1.4661.466
TVALTFEXP_TVA->PJM
CLTF
5.1695.169
O66PJM->LTFIMP_O-066
CMTX_NF
33.48333.483
CBM West 1LTFEXP_CBM-W1->PJM
CBM
235.985235.985
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.62846.628
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
23.96923.969
LAGNLTFEXP_LAGN->PJM
CLTF
9.4439.443
NYPJM->LTFIMP_NY
CLTF
2.7622.762
LGEELTFEXP_LGEE->PJM
CLTF
1.661.66
WECLTFEXP_WEC->PJM
CLTF
6.4986.498
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.9160.916
G-007PJM->LTFIMP_G-007
CMTX_NF
5.225.22
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.4090.409
SIGELTFEXP_SIGE->PJM
CLTF
0.560.56

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.99 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1547.91
MW Contribution:2.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274788SE CHICAG;5U
80/20
7.2327.232
274798UNIV PARK;1U
80/20
1.4061.406
958011AF2-095 C
80/20
13.59713.597
933411AC2-154 C
80/20
2.992.99
274687WILL CNTY;4U
Adder
78.0176470588235366.315
966091AG1-478 C
Adder
2.38941176470588262.031
966441AG1-513 C
Adder
0.57647058823529410.49
959081AF2-199 C
Adder
8.0647058823529436.855
942111AE2-223 C
Adder
2.17764705882352951.851
939741AE1-205 C
Adder
9.3811764705882357.974
934101AD2-000 1
Adder
6.542352941176475.561
942421AE2-255 C
Adder
3.42117647058823552.908
926821AC1-168 C
Adder
1.28941176470588251.096
959611AF2-252 C
Adder
2.1329411764705881.813
274790SE CHICAG;7U
80/20
7.2327.232
274791SE CHICAG;8U
80/20
7.2327.232
274789SE CHICAG;6U
80/20
7.2327.232
274682WAUKEGAN ;7U
Adder
46.7423529411764739.731
942651AE2-281 C
Adder
0.96470588235294120.82
962691AG1-118 C
Adder
25.1023529411764721.337
938851AE1-113 C
Adder
9.0329411764705887.678
959091AF2-200 C
Adder
16.12823529411764813.709
959341AF2-225 C
Adder
7.0364705882352945.981
965091AG1-374 C
Adder
19.1976470588235316.318
961501AF2-441 C
80/20
14.87514.875
274826FISK ;BP
80/20
2.6552.655
939351AE1-166 C
Adder
11.6094117647058829.868
274675JOLIET 29;7U
Adder
82.4117647058823570.05
274674JOLIET 9 ;6U
Adder
42.3282352941176535.979
943121AE2-341 C
Adder
14.46117647058823512.292
939321AE1-163 C
Adder
6.7517647058823535.739
957371AF2-031 C
80/20
1.5531.553
960591AF2-350 C
80/20
9.4429.442
960751AF2-366 C
Adder
7.9070588235294126.721
274754CRETE EC ;4U
80/20
1.941.94
274887PILOT HIL;1U
80/20
0.8970.897
934111AD2-000 2
Adder
6.8035294117647065.783
274683WAUKEGAN ;8U
Adder
50.3941176470588342.835
274800UNIV PARK;3U
80/20
1.3961.396
941551AE2-152 C
Adder
13.39529411764705811.386
274676JOLIET 29;8U
Adder
82.4152941176470670.053
958481AF2-142 C
Adder
12.7223529411764710.814
274751CRETE EC ;1U
80/20
1.941.94
274723RIVER EC ;12
80/20
5.1225.122
274724RIVER EC ;11
80/20
5.1235.123
960281AF2-319 C
Adder
2.89058823529411772.457
957471AF2-041 C
Adder
24.1929411764705920.564
938861AE1-114 C
Adder
4.4423529411764713.776
276164X3-005 C
80/20
0.0990.099
274827FISK ;RP
80/20
1.8821.882
957331AF2-027 C
Adder
2.82588235294117672.402
936511AD2-066 C
Adder
9.5376470588235298.107
939061AE1-134 2
Adder
1.54823529411764721.316
274753CRETE EC ;3U
80/20
1.941.94
274793SE CHICAG;0U
80/20
7.1437.143
274795SE CHICAG;2U
80/20
7.1437.143
962781AG1-127 C
Adder
7.92823529411764756.739
933911AD1-013 C
Adder
2.08705882352941161.774
274888KELLY CRK;1U
80/20
0.8970.897
943591AF1-030 C
Adder
9.6164705882352938.174
274752CRETE EC ;2U
80/20
1.941.94
274794SE CHICAG;1U
80/20
7.1437.143
936371AD2-047 C
80/20
5.355.35
936461AD2-060 C
80/20
3.1473.147
946671AF1-331 C
Adder
2.71058823529411752.304
960611AF2-352 C
Adder
2.1329411764705881.813
946321AF1-296 C
Adder
4.0305882352941183.426
274792SE CHICAG;9U
80/20
7.1437.143
274799UNIV PARK;2U
80/20
1.3961.396
274801UNIV PARK;4U
80/20
1.3961.396
959351AF2-226 C
Adder
2.89058823529411772.457
958491AF2-143 C
Adder
12.40117647058823610.541
965931AG1-462 C
Adder
18.16117647058823415.437
991332J1785
External Queue
13.53217792510986313.532177925109863
990552J1334 G
External Queue
40.5239410400390640.52394104003906
990557J1335 G
External Queue
40.5239410400390640.52394104003906
990562J1336 G
External Queue
40.5239410400390640.52394104003906
990577J1339
External Queue
26.57409286499023426.574092864990234
990547J1333 G
External Queue
40.5239410400390640.52394104003906
990762J1386
External Queue
12.93081378936767612.930813789367676
990582J1340
External Queue
26.57409286499023426.574092864990234
990662J1358
External Queue
14.93047237396240214.930472373962402
991247J1684 G
External Queue
33.61624908447265633.616249084472656
955742J1058 G
External Queue
35.2828559875488335.28285598754883
990647J1355
External Queue
42.268421173095742.2684211730957
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8260.826
TVALTFEXP_TVA->PJM
CLTF
1.7951.795
CBM West 1LTFEXP_CBM-W1->PJM
CBM
118.129118.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.88718.887
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.510.51
MECLTFEXP_MEC->PJM
CLTF
14.93414.934
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.4171.417
LAGNLTFEXP_LAGN->PJM
CLTF
4.3274.327
NYPJM->LTFIMP_NY
CLTF
1.271.27
WECLTFEXP_WEC->PJM
CLTF
4.4234.423
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5520.552
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2810.281
SIGELTFEXP_SIGE->PJM
CLTF
0.060.06

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.99 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1547.87
MW Contribution:2.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274788SE CHICAG;5U
80/20
7.2327.232
274798UNIV PARK;1U
80/20
1.4061.406
958011AF2-095 C
80/20
13.59713.597
933411AC2-154 C
80/20
2.992.99
274687WILL CNTY;4U
Adder
78.0176470588235366.315
966091AG1-478 C
Adder
2.38941176470588262.031
966441AG1-513 C
Adder
0.57647058823529410.49
959081AF2-199 C
Adder
8.0647058823529436.855
942111AE2-223 C
Adder
2.17764705882352951.851
939741AE1-205 C
Adder
9.3811764705882357.974
934101AD2-000 1
Adder
6.542352941176475.561
942421AE2-255 C
Adder
3.42117647058823552.908
926821AC1-168 C
Adder
1.28941176470588251.096
959611AF2-252 C
Adder
2.1329411764705881.813
274790SE CHICAG;7U
80/20
7.2327.232
274791SE CHICAG;8U
80/20
7.2327.232
274789SE CHICAG;6U
80/20
7.2327.232
274682WAUKEGAN ;7U
Adder
46.7423529411764739.731
942651AE2-281 C
Adder
0.96470588235294120.82
962691AG1-118 C
Adder
25.1023529411764721.337
938851AE1-113 C
Adder
9.0329411764705887.678
959091AF2-200 C
Adder
16.12823529411764813.709
959341AF2-225 C
Adder
7.0364705882352945.981
965091AG1-374 C
Adder
19.1976470588235316.318
961501AF2-441 C
80/20
14.87514.875
274826FISK ;BP
80/20
2.6552.655
939351AE1-166 C
Adder
11.6094117647058829.868
274675JOLIET 29;7U
Adder
82.4117647058823570.05
274674JOLIET 9 ;6U
Adder
42.3282352941176535.979
943121AE2-341 C
Adder
14.46117647058823512.292
939321AE1-163 C
Adder
6.7517647058823535.739
957371AF2-031 C
80/20
1.5531.553
960591AF2-350 C
80/20
9.4429.442
960751AF2-366 C
Adder
7.9070588235294126.721
274754CRETE EC ;4U
80/20
1.941.94
274887PILOT HIL;1U
80/20
0.8970.897
934111AD2-000 2
Adder
6.8035294117647065.783
274683WAUKEGAN ;8U
Adder
50.3941176470588342.835
274800UNIV PARK;3U
80/20
1.3961.396
941551AE2-152 C
Adder
13.39529411764705811.386
274676JOLIET 29;8U
Adder
82.4152941176470670.053
958481AF2-142 C
Adder
12.7223529411764710.814
274751CRETE EC ;1U
80/20
1.941.94
274723RIVER EC ;12
80/20
5.1225.122
274724RIVER EC ;11
80/20
5.1235.123
960281AF2-319 C
Adder
2.89058823529411772.457
957471AF2-041 C
Adder
24.1929411764705920.564
938861AE1-114 C
Adder
4.4423529411764713.776
276164X3-005 C
80/20
0.0990.099
274827FISK ;RP
80/20
1.8821.882
957331AF2-027 C
Adder
2.82588235294117672.402
936511AD2-066 C
Adder
9.5376470588235298.107
939061AE1-134 2
Adder
1.54823529411764721.316
274753CRETE EC ;3U
80/20
1.941.94
274793SE CHICAG;0U
80/20
7.1437.143
274795SE CHICAG;2U
80/20
7.1437.143
962781AG1-127 C
Adder
7.92823529411764756.739
933911AD1-013 C
Adder
2.08705882352941161.774
274888KELLY CRK;1U
80/20
0.8970.897
943591AF1-030 C
Adder
9.6164705882352938.174
274752CRETE EC ;2U
80/20
1.941.94
274794SE CHICAG;1U
80/20
7.1437.143
936371AD2-047 C
80/20
5.355.35
936461AD2-060 C
80/20
3.1473.147
946671AF1-331 C
Adder
2.71058823529411752.304
960611AF2-352 C
Adder
2.1329411764705881.813
946321AF1-296 C
Adder
4.0305882352941183.426
274792SE CHICAG;9U
80/20
7.1437.143
274799UNIV PARK;2U
80/20
1.3961.396
274801UNIV PARK;4U
80/20
1.3961.396
959351AF2-226 C
Adder
2.89058823529411772.457
958491AF2-143 C
Adder
12.40117647058823610.541
965931AG1-462 C
Adder
18.16117647058823415.437
991332J1785
External Queue
13.53217792510986313.532177925109863
990552J1334 G
External Queue
40.5239410400390640.52394104003906
990557J1335 G
External Queue
40.5239410400390640.52394104003906
990562J1336 G
External Queue
40.5239410400390640.52394104003906
990577J1339
External Queue
26.57409286499023426.574092864990234
990547J1333 G
External Queue
40.5239410400390640.52394104003906
990762J1386
External Queue
12.93081378936767612.930813789367676
990582J1340
External Queue
26.57409286499023426.574092864990234
990662J1358
External Queue
14.93047237396240214.930472373962402
991247J1684 G
External Queue
33.61624908447265633.616249084472656
955742J1058 G
External Queue
35.2828559875488335.28285598754883
990647J1355
External Queue
42.268421173095742.2684211730957
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8260.826
TVALTFEXP_TVA->PJM
CLTF
1.7951.795
CBM West 1LTFEXP_CBM-W1->PJM
CBM
118.129118.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.88718.887
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.510.51
MECLTFEXP_MEC->PJM
CLTF
14.93414.934
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.4171.417
LAGNLTFEXP_LAGN->PJM
CLTF
4.3274.327
NYPJM->LTFIMP_NY
CLTF
1.271.27
WECLTFEXP_WEC->PJM
CLTF
4.4234.423
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5520.552
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2810.281
SIGELTFEXP_SIGE->PJM
CLTF
0.060.06

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.83 %
Rating:1075.0 MVA
Rating Type:A
MVA to Mitigate:1169.93
MW Contribution:1.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274788SE CHICAG;5U
80/20
5.5385.538
274798UNIV PARK;1U
80/20
0.9230.923
958011AF2-095 C
80/20
8.6418.641
933411AC2-154 C
80/20
1.91.9
274687WILL CNTY;4U
Adder
48.5929411764705941.304
966091AG1-478 C
Adder
1.46941176470588241.249
966441AG1-513 C
Adder
0.32705882352941180.278
959081AF2-199 C
Adder
4.6141176470588243.922
942111AE2-223 C
Adder
1.2717647058823531.081
939741AE1-205 C
Adder
5.4776470588235294.656
934101AD2-000 1
Adder
3.68941176470588243.136
942421AE2-255 C
Adder
2.0552941176470591.747
926821AC1-168 C
Adder
0.75294117647058820.64
959611AF2-252 C
Adder
1.24941176470588241.062
274790SE CHICAG;7U
80/20
5.5385.538
274791SE CHICAG;8U
80/20
5.5385.538
274789SE CHICAG;6U
80/20
5.5385.538
274682WAUKEGAN ;7U
Adder
27.29294117647059223.199
942651AE2-281 C
Adder
0.58941176470588240.501
962691AG1-118 C
Adder
14.20823529411764812.077
938851AE1-113 C
Adder
5.4270588235294124.613
959091AF2-200 C
Adder
9.2294117647058827.845
959341AF2-225 C
Adder
4.1082352941176473.492
965091AG1-374 C
Adder
11.249.554
961501AF2-441 C
80/20
10.91610.916
274826FISK ;BP
80/20
1.7681.768
939351AE1-166 C
Adder
6.7717647058823545.756
274675JOLIET 29;7U
Adder
49.9447058823529542.453
274674JOLIET 9 ;6U
Adder
25.73058823529411821.871
943121AE2-341 C
Adder
7.99529411764705966.796
939321AE1-163 C
Adder
4.1294117647058823.51
957371AF2-031 C
80/20
1.1831.183
960591AF2-350 C
80/20
66
960751AF2-366 C
Adder
4.4776470588235293.806
274754CRETE EC ;4U
80/20
1.4551.455
274887PILOT HIL;1U
80/20
0.570.57
934111AD2-000 2
Adder
4.077647058823533.466
274683WAUKEGAN ;8U
Adder
29.42352941176470825.01
274800UNIV PARK;3U
80/20
0.9170.917
941551AE2-152 C
Adder
7.8141176470588246.642
274676JOLIET 29;8U
Adder
49.9529411764705942.46
958481AF2-142 C
Adder
7.8258823529411776.652
274751CRETE EC ;1U
80/20
1.4551.455
274723RIVER EC ;12
80/20
3.8963.896
274724RIVER EC ;11
80/20
3.9023.902
960281AF2-319 C
Adder
1.80588235294117651.535
957471AF2-041 C
Adder
13.84352941176470611.767
938861AE1-114 C
Adder
2.562.176
276164X3-005 C
80/20
0.070.07
274827FISK ;RP
80/20
1.2531.253
957331AF2-027 C
Adder
1.64941176470588241.402
936511AD2-066 C
Adder
5.6788235294117654.827
939061AE1-134 2
Adder
0.89294117647058820.759
274753CRETE EC ;3U
80/20
1.4551.455
274793SE CHICAG;0U
80/20
5.4655.465
274795SE CHICAG;2U
80/20
5.4655.465
962781AG1-127 C
Adder
4.4894117647058823.816
933911AD1-013 C
Adder
1.18705882352941171.009
274888KELLY CRK;1U
80/20
0.570.57
943591AF1-030 C
Adder
5.3176470588235294.52
274752CRETE EC ;2U
80/20
1.4551.455
274794SE CHICAG;1U
80/20
5.4655.465
936371AD2-047 C
80/20
3.43.4
936461AD2-060 C
80/20
22
946671AF1-331 C
Adder
1.54235294117647051.311
960611AF2-352 C
Adder
1.24941176470588241.062
946321AF1-296 C
Adder
2.34000000000000031.989
274792SE CHICAG;9U
80/20
5.4655.465
274799UNIV PARK;2U
80/20
0.9170.917
274801UNIV PARK;4U
80/20
0.9170.917
959351AF2-226 C
Adder
1.80588235294117651.535
958491AF2-143 C
Adder
7.5847058823529416.447
965931AG1-462 C
Adder
10.5505882352941188.968
991332J1785
External Queue
15.41609477996826215.416094779968262
991337J1802
External Queue
11.39966201782226611.399662017822266
990552J1334 G
External Queue
40.5459747314453140.54597473144531
990557J1335 G
External Queue
40.5459747314453140.54597473144531
990562J1336 G
External Queue
40.5459747314453140.54597473144531
990577J1339
External Queue
26.6973209381103526.69732093811035
990547J1333 G
External Queue
40.5459747314453140.54597473144531
990762J1386
External Queue
12.26621055603027312.266210556030273
990582J1340
External Queue
26.6973209381103526.69732093811035
990662J1358
External Queue
15.6888904571533215.68889045715332
991247J1684 G
External Queue
33.68902206420898433.689022064208984
955742J1058 G
External Queue
34.2569389343261734.25693893432617
990647J1355
External Queue
45.41125869750976645.411258697509766
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.4540.454
TVALTFEXP_TVA->PJM
CLTF
1.1741.174
CBM West 1LTFEXP_CBM-W1->PJM
CBM
75.73675.736
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.85611.856
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.2290.229
MECLTFEXP_MEC->PJM
CLTF
8.7698.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.6110.611
LAGNLTFEXP_LAGN->PJM
CLTF
2.6762.676
NYPJM->LTFIMP_NY
CLTF
0.7460.746
WECLTFEXP_WEC->PJM
CLTF
2.5782.578
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2990.299
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1480.148
SIGELTFEXP_SIGE->PJM
CLTF
0.0530.053

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.62 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1423.72
MW Contribution:5.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274814UNIV PK N;0U
50/50
1.8911.891
274807UNIV PK N;3U
50/50
1.9151.915
274816UNIV PK N;YU
50/50
1.9151.915
958011AF2-095 C
Adder
9.557647058823538.124
933411AC2-154 C
Adder
2.10235294117647081.787
274687WILL CNTY;4U
Adder
55.58000000000000547.243
966091AG1-478 C
Adder
1.7552941176470591.492
966441AG1-513 C
Adder
0.430588235294117660.366
959081AF2-199 C
Adder
5.9858823529411775.088
910542X3-005 E
Adder
0.53058823529411770.451
939352AE1-166 E
Adder
7.8341176470588236.659
294392P-010 E
Adder
16.63882352941176614.143
959352AF2-226 E
Adder
3.01647058823529422.564
934101AD2-000 1
Adder
4.8788235294117654.147
958492AF2-143 E
Adder
6.4929411764705885.519
942421AE2-255 C
Adder
2.53764705882352942.157
290108LEEDK;1U E
Adder
20.2152941176470617.183
916221Z1-073 E
Adder
6.2070588235294125.276
957472AF2-041 E
Adder
8.9788235294117647.632
959092AF2-200 E
Adder
7.98117647058823556.784
926821AC1-168 C
Adder
0.95764705882352940.814
938862AE1-114 E
Adder
11.244705882352949.558
966092AG1-478 E
Adder
0.44117647058823530.375
274682WAUKEGAN ;7U
Adder
34.8235294117647129.6
942651AE2-281 C
Adder
0.75764705882352950.644
942652AE2-281 E
Adder
4.6529411764705893.955
962691AG1-118 C
Adder
18.6752941176470615.874
962692AG1-118 E
Adder
12.45058823529411810.583
938851AE1-113 C
Adder
6.75.695
272363ESS H440 ; R
Adder
2.21411764705882331.882
959091AF2-200 C
Adder
11.97176470588235410.176
940502AE2-035 E
Adder
2.84588235294117682.419
293519PILOT HIL;1E
Adder
15.48823529411764713.165
939351AE1-166 C
Adder
8.4870588235294137.214
274675JOLIET 29;7U
Adder
61.79058823529411652.522
274674JOLIET 9 ;6U
Adder
31.0329411764705926.378
293061N-015 E
Adder
13.10117647058823411.136
943121AE2-341 C
Adder
10.7729411764705899.157
939321AE1-163 C
Adder
5.302352941176474.507
295111SUBLETTE E
Adder
2.29294117647058831.949
274860EASYR;U2 E
Adder
10.0658823529411758.556
965791AG1-447 C
50/50
46.75146.751
965682AG1-436 E
50/50
42.50142.501
960591AF2-350 C
Adder
6.637647058823535.642
960592AF2-350 E
Adder
4.4247058823529413.761
275149KELLYCK ;1E
Adder
15.48823529411764713.165
934722AD1-100 E
Adder
76.1647058823529364.74
960751AF2-366 C
Adder
5.8811764705882354.999
942422AE2-255 E
Adder
7.61411764705882456.472
960582AF2-349 E
Adder
30.4847058823529425.912
937312AD2-172 E
Adder
2.84588235294117682.419
274859EASYR;U1 E
Adder
10.0658823529411758.556
274815UNIV PK N;XU
50/50
1.9031.903
958012AF2-095 E
Adder
6.3717647058823535.416
934111AD2-000 2
Adder
5.0470588235294124.29
966442AG1-513 E
Adder
0.64470588235294120.548
274683WAUKEGAN ;8U
Adder
37.5458823529411831.914
290051GSG-6; E
Adder
8.8082352941176477.487
959082AF2-199 E
Adder
2.99294117647058842.544
958912AF2-182 E
Adder
28.6258823529411824.332
960681AF2-359 C
50/50
63.75263.752
274813UNIV PK N;9U
50/50
1.8991.899
274811UNIV PK N;7U
50/50
1.9151.915
941551AE2-152 C
Adder
9.7929411764705888.324
274676JOLIET 29;8U
Adder
61.7682352941176552.503
958481AF2-142 C
Adder
10.2035294117647068.673
957332AF2-027 E
Adder
3.15764705882352952.684
274891CAYUG;2U E
Adder
11.395294117647069.686
926822AC1-168 E
Adder
6.4258823529411765.462
293644O22 E1
Adder
11.5517647058823549.819
960281AF2-319 C
Adder
2.0105882352941181.709
960752AF2-366 E
Adder
3.92117647058823553.333
957471AF2-041 C
Adder
17.9576470588235315.264
294763P-046 E
Adder
7.9094117647058826.723
938861AE1-114 C
Adder
3.2964705882352942.802
957331AF2-027 C
Adder
2.1047058823529411.789
936511AD2-066 C
Adder
7.1305882352941186.061
936512AD2-066 E
Adder
4.7541176470588244.041
295109WESTBROOK E
Adder
4.7152941176470594.008
939061AE1-134 2
Adder
1.14705882352941170.975
936372AD2-047 E
Adder
18.36705882352941215.612
276591L-013 2
Adder
3.09411764705882362.63
962781AG1-127 C
Adder
5.8976470588235295.013
933911AD1-013 C
Adder
1.55058823529411781.318
274805UNIV PK N;1U
50/50
1.9031.903
943592AF1-030 E
Adder
3.54470588235294143.013
943591AF1-030 C
Adder
7.1635294117647066.089
936292AD2-038 E
Adder
13.37529411764705911.369
290021O50 E
Adder
16.24352941176470813.807
937002AD2-134 E
Adder
8.5164705882352937.239
936371AD2-047 C
Adder
3.76235294117647053.198
936461AD2-060 C
Adder
2.2129411764705881.881
933412AC2-154 E
Adder
3.42941176470588262.915
962782AG1-127 E
Adder
3.92470588235294133.336
946671AF1-331 C
Adder
2.01411764705882361.712
943122AE2-341 E
Adder
5.2905882352941184.497
939322AE1-163 E
Adder
32.5729411764705927.687
293516O-009 E
Adder
15.7576470588235313.394
293717O-029 E
Adder
4.1070588235294123.491
960682AF2-359 E
50/50
42.50142.501
274810UNIV PK N;6U
50/50
1.9071.907
274812UNIV PK N;8U
50/50
1.8991.899
941552AE2-152 E
Adder
6.5282352941176485.549
958482AF2-142 E
Adder
6.8023529411764715.782
938852AE1-113 E
Adder
23.75647058823529520.193
274890CAYUG;1U E
Adder
11.395294117647069.686
962012AG1-044 E
Adder
0.0529411764705882350.045
965681AG1-436 C
50/50
63.75263.752
293645O22 E2
Adder
13.2305882352941211.246
960282AF2-319 E
Adder
3.01647058823529422.564
918052AA1-018 E OP
Adder
14.7952941176470612.576
293715O-029 E
Adder
8.1494117647058816.927
274808UNIV PK N;4U
50/50
1.9071.907
959351AF2-226 C
Adder
2.0105882352941181.709
958491AF2-143 C
Adder
9.748.279
933912AD1-013 E
Adder
2.47764705882352932.106
946152AF1-280 E
Adder
19.08352941176470816.221
293716O-029 E
Adder
4.46823529411764753.798
276675AE2-062 E
Adder
0.134117647058823540.114
276170Z1-108 E
Adder
2.4670588235294122.097
920272AA2-123 E
Adder
2.4188235294117652.056
276626AG1-044 E
Adder
0.061176470588235290.052
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6070.607
TVALTFEXP_TVA->PJM
CLTF
1.1671.167
O66PJM->LTFIMP_O-066
CMTX_NF
11.09411.094
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.23368.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.47412.474
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.4090.409
MECLTFEXP_MEC->PJM
CLTF
10.92410.924
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.1721.172
LAGNLTFEXP_LAGN->PJM
CLTF
2.992.99
NYPJM->LTFIMP_NY
CLTF
0.9310.931
WECLTFEXP_WEC->PJM
CLTF
3.2883.288
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4090.409
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7291.729
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.210.21
SIGELTFEXP_SIGE->PJM
CLTF
0.0150.015

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.52 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1422.69
MW Contribution:5.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274814UNIV PK N;0U
50/50
1.9011.901
274807UNIV PK N;3U
50/50
1.9251.925
274816UNIV PK N;YU
50/50
1.9251.925
958011AF2-095 C
Adder
9.6458823529411778.199
933411AC2-154 C
Adder
2.1211764705882351.803
274687WILL CNTY;4U
Adder
56.08235294117647447.67
966091AG1-478 C
Adder
1.76941176470588251.504
966441AG1-513 C
Adder
0.434117647058823550.369
959081AF2-199 C
Adder
6.0258823529411775.122
910542X3-005 E
Adder
0.53764705882352950.457
939352AE1-166 E
Adder
7.897647058823536.713
294392P-010 E
Adder
16.76941176470588214.254
959352AF2-226 E
Adder
3.0411764705882352.585
934101AD2-000 1
Adder
4.91411764705882354.177
958492AF2-143 E
Adder
6.537647058823535.557
942421AE2-255 C
Adder
2.5552941176470592.172
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
957472AF2-041 E
Adder
9.0400000000000017.684
959092AF2-200 E
Adder
8.0352941176470596.83
926821AC1-168 C
Adder
0.96235294117647050.818
938862AE1-114 E
Adder
11.315294117647069.618
966092AG1-478 E
Adder
0.44470588235294120.378
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
938851AE1-113 C
Adder
6.7458823529411775.734
272363ESS H440 ; R
Adder
2.22941176470588241.895
959091AF2-200 C
Adder
12.05294117647058810.245
940502AE2-035 E
Adder
2.8647058823529412.435
293519PILOT HIL;1E
Adder
15.63058823529411813.286
939351AE1-166 C
Adder
8.555294117647067.272
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
293061N-015 E
Adder
13.20352941176470711.223
943121AE2-341 C
Adder
10.8588235294117659.23
939321AE1-163 C
Adder
5.3388235294117654.538
295111SUBLETTE E
Adder
2.3082352941176471.962
274860EASYR;U2 E
Adder
10.1270588235294138.608
965791AG1-447 C
50/50
46.89646.896
965682AG1-436 E
50/50
42.63342.633
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
275149KELLYCK ;1E
Adder
15.63058823529411813.286
934722AD1-100 E
Adder
76.7823529411764765.265
960751AF2-366 C
Adder
5.9247058823529415.036
942422AE2-255 E
Adder
7.6658823529411776.516
960582AF2-349 E
Adder
30.726.095
937312AD2-172 E
Adder
2.8647058823529412.435
274859EASYR;U1 E
Adder
10.1270588235294138.608
274815UNIV PK N;XU
50/50
1.9131.913
958012AF2-095 E
Adder
6.4305882352941185.466
934111AD2-000 2
Adder
5.0882352941176484.325
966442AG1-513 E
Adder
0.65058823529411770.553
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
290051GSG-6; E
Adder
8.8682352941176487.538
959082AF2-199 E
Adder
3.01294117647058852.561
958912AF2-182 E
Adder
28.79647058823529424.477
960681AF2-359 C
50/50
63.94963.949
274813UNIV PK N;9U
50/50
1.9091.909
274811UNIV PK N;7U
50/50
1.9251.925
941551AE2-152 C
Adder
9.8717647058823528.391
274676JOLIET 29;8U
Adder
62.29647058823529452.952
958481AF2-142 C
Adder
10.2776470588235318.736
957332AF2-027 E
Adder
3.1823529411764712.705
274891CAYUG;2U E
Adder
11.4552941176470599.737
926822AC1-168 E
Adder
6.4588235294117655.49
293644O22 E1
Adder
11.6458823529411759.899
960281AF2-319 C
Adder
2.0270588235294121.723
960752AF2-366 E
Adder
3.94941176470588263.357
957471AF2-041 C
Adder
18.07882352941176815.367
294763P-046 E
Adder
7.9611764705882366.767
938861AE1-114 C
Adder
3.3164705882352942.819
957331AF2-027 C
Adder
2.1211764705882351.803
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
295109WESTBROOK E
Adder
4.7482352941176474.036
939061AE1-134 2
Adder
1.15294117647058810.98
936372AD2-047 E
Adder
18.53411764705882415.754
276591L-013 2
Adder
3.11882352941176462.651
962781AG1-127 C
Adder
5.94117647058823555.05
933911AD1-013 C
Adder
1.56117647058823541.327
274805UNIV PK N;1U
50/50
1.9131.913
943592AF1-030 E
Adder
3.5729411764705883.037
943591AF1-030 C
Adder
7.2211764705882366.138
936292AD2-038 E
Adder
13.46705882352941211.447
290021O50 E
Adder
16.3552941176470613.902
937002AD2-134 E
Adder
8.5752941176470587.289
936371AD2-047 C
Adder
3.7964705882352943.227
936461AD2-060 C
Adder
2.2329411764705881.898
933412AC2-154 E
Adder
3.46117647058823552.942
962782AG1-127 E
Adder
3.9541176470588243.361
946671AF1-331 C
Adder
2.0282352941176471.724
943122AE2-341 E
Adder
5.3317647058823534.532
939322AE1-163 E
Adder
32.7952941176470627.876
293516O-009 E
Adder
15.8423529411764713.466
293717O-029 E
Adder
4.1282352941176473.509
960682AF2-359 E
50/50
42.63342.633
274810UNIV PK N;6U
50/50
1.9171.917
274812UNIV PK N;8U
50/50
1.9091.909
941552AE2-152 E
Adder
6.5811764705882365.594
958482AF2-142 E
Adder
6.8517647058823535.824
938852AE1-113 E
Adder
23.91882352941176420.331
274890CAYUG;1U E
Adder
11.4552941176470599.737
962012AG1-044 E
Adder
0.0529411764705882350.045
965681AG1-436 C
50/50
63.94963.949
293645O22 E2
Adder
13.33882352941176411.338
960282AF2-319 E
Adder
3.0411764705882352.585
918052AA1-018 E OP
Adder
14.9023529411764712.667
293715O-029 E
Adder
8.1929411764705896.964
274808UNIV PK N;4U
50/50
1.9171.917
959351AF2-226 C
Adder
2.0270588235294121.723
958491AF2-143 C
Adder
9.8058823529411778.335
933912AD1-013 E
Adder
2.49411764705882362.12
946152AF1-280 E
Adder
19.1976470588235316.318
293716O-029 E
Adder
4.4917647058823533.818
276675AE2-062 E
Adder
0.135294117647058840.115
276170Z1-108 E
Adder
2.48588235294117642.113
920272AA2-123 E
Adder
2.4364705882352942.071
276626AG1-044 E
Adder
0.062352941176470590.053
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
NYPJM->LTFIMP_NY
CLTF
0.9330.933
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.52 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1422.69
MW Contribution:5.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274814UNIV PK N;0U
50/50
1.9011.901
274807UNIV PK N;3U
50/50
1.9251.925
274816UNIV PK N;YU
50/50
1.9251.925
958011AF2-095 C
Adder
9.6458823529411778.199
933411AC2-154 C
Adder
2.1211764705882351.803
274687WILL CNTY;4U
Adder
56.08235294117647447.67
966091AG1-478 C
Adder
1.76941176470588251.504
966441AG1-513 C
Adder
0.434117647058823550.369
959081AF2-199 C
Adder
6.0258823529411775.122
910542X3-005 E
Adder
0.53764705882352950.457
939352AE1-166 E
Adder
7.897647058823536.713
294392P-010 E
Adder
16.76941176470588214.254
959352AF2-226 E
Adder
3.0411764705882352.585
934101AD2-000 1
Adder
4.91411764705882354.177
958492AF2-143 E
Adder
6.537647058823535.557
942421AE2-255 C
Adder
2.5552941176470592.172
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
957472AF2-041 E
Adder
9.0400000000000017.684
959092AF2-200 E
Adder
8.0352941176470596.83
926821AC1-168 C
Adder
0.96235294117647050.818
938862AE1-114 E
Adder
11.315294117647069.618
966092AG1-478 E
Adder
0.44470588235294120.378
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
938851AE1-113 C
Adder
6.7458823529411775.734
272363ESS H440 ; R
Adder
2.22941176470588241.895
959091AF2-200 C
Adder
12.05294117647058810.245
940502AE2-035 E
Adder
2.8647058823529412.435
293519PILOT HIL;1E
Adder
15.63058823529411813.286
939351AE1-166 C
Adder
8.555294117647067.272
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
293061N-015 E
Adder
13.20352941176470711.223
943121AE2-341 C
Adder
10.8588235294117659.23
939321AE1-163 C
Adder
5.3388235294117654.538
295111SUBLETTE E
Adder
2.3082352941176471.962
274860EASYR;U2 E
Adder
10.1270588235294138.608
965791AG1-447 C
50/50
46.89646.896
965682AG1-436 E
50/50
42.63342.633
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
275149KELLYCK ;1E
Adder
15.63058823529411813.286
934722AD1-100 E
Adder
76.7823529411764765.265
960751AF2-366 C
Adder
5.9247058823529415.036
942422AE2-255 E
Adder
7.6658823529411776.516
960582AF2-349 E
Adder
30.726.095
937312AD2-172 E
Adder
2.8647058823529412.435
274859EASYR;U1 E
Adder
10.1270588235294138.608
274815UNIV PK N;XU
50/50
1.9131.913
958012AF2-095 E
Adder
6.4305882352941185.466
934111AD2-000 2
Adder
5.0882352941176484.325
966442AG1-513 E
Adder
0.65058823529411770.553
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
290051GSG-6; E
Adder
8.8682352941176487.538
959082AF2-199 E
Adder
3.01294117647058852.561
958912AF2-182 E
Adder
28.79647058823529424.477
960681AF2-359 C
50/50
63.94963.949
274813UNIV PK N;9U
50/50
1.9091.909
274811UNIV PK N;7U
50/50
1.9251.925
941551AE2-152 C
Adder
9.8717647058823528.391
274676JOLIET 29;8U
Adder
62.29647058823529452.952
958481AF2-142 C
Adder
10.2776470588235318.736
957332AF2-027 E
Adder
3.1823529411764712.705
274891CAYUG;2U E
Adder
11.4552941176470599.737
926822AC1-168 E
Adder
6.4588235294117655.49
293644O22 E1
Adder
11.6458823529411759.899
960281AF2-319 C
Adder
2.0270588235294121.723
960752AF2-366 E
Adder
3.94941176470588263.357
957471AF2-041 C
Adder
18.07882352941176815.367
294763P-046 E
Adder
7.9611764705882366.767
938861AE1-114 C
Adder
3.3164705882352942.819
957331AF2-027 C
Adder
2.1211764705882351.803
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
295109WESTBROOK E
Adder
4.7482352941176474.036
939061AE1-134 2
Adder
1.15294117647058810.98
936372AD2-047 E
Adder
18.53411764705882415.754
276591L-013 2
Adder
3.11882352941176462.651
962781AG1-127 C
Adder
5.94117647058823555.05
933911AD1-013 C
Adder
1.56117647058823541.327
274805UNIV PK N;1U
50/50
1.9131.913
943592AF1-030 E
Adder
3.5729411764705883.037
943591AF1-030 C
Adder
7.2211764705882366.138
936292AD2-038 E
Adder
13.46705882352941211.447
290021O50 E
Adder
16.3552941176470613.902
937002AD2-134 E
Adder
8.5752941176470587.289
936371AD2-047 C
Adder
3.7964705882352943.227
936461AD2-060 C
Adder
2.2329411764705881.898
933412AC2-154 E
Adder
3.46117647058823552.942
962782AG1-127 E
Adder
3.9541176470588243.361
946671AF1-331 C
Adder
2.0282352941176471.724
943122AE2-341 E
Adder
5.3317647058823534.532
939322AE1-163 E
Adder
32.7952941176470627.876
293516O-009 E
Adder
15.8423529411764713.466
293717O-029 E
Adder
4.1282352941176473.509
960682AF2-359 E
50/50
42.63342.633
274810UNIV PK N;6U
50/50
1.9171.917
274812UNIV PK N;8U
50/50
1.9091.909
941552AE2-152 E
Adder
6.5811764705882365.594
958482AF2-142 E
Adder
6.8517647058823535.824
938852AE1-113 E
Adder
23.91882352941176420.331
274890CAYUG;1U E
Adder
11.4552941176470599.737
962012AG1-044 E
Adder
0.0529411764705882350.045
965681AG1-436 C
50/50
63.94963.949
274808UNIV PK N;4U
50/50
1.9171.917
959351AF2-226 C
Adder
2.0270588235294121.723
958491AF2-143 C
Adder
9.8058823529411778.335
933912AD1-013 E
Adder
2.49411764705882362.12
946152AF1-280 E
Adder
19.1976470588235316.318
293716O-029 E
Adder
4.4917647058823533.818
293645O22 E2
Adder
13.33882352941176411.338
960282AF2-319 E
Adder
3.0411764705882352.585
918052AA1-018 E OP
Adder
14.9023529411764712.667
293715O-029 E
Adder
8.1929411764705896.964
276675AE2-062 E
Adder
0.135294117647058840.115
276170Z1-108 E
Adder
2.48588235294117642.113
920272AA2-123 E
Adder
2.4364705882352942.071
276626AG1-044 E
Adder
0.062352941176470590.053
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
NYPJM->LTFIMP_NY
CLTF
0.9330.933
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.45 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1768.97
MW Contribution:7.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
958011AF2-095 C
Adder
10.2317647058823528.697
933411AC2-154 C
Adder
2.25058823529411761.913
274687WILL CNTY;4U
50/50
71.93671.936
966091AG1-478 C
Adder
2.00941176470588221.708
966441AG1-513 C
Adder
0.52235294117647060.444
959081AF2-199 C
Adder
7.3129411764705896.216
939352AE1-166 E
Adder
9.4317647058823538.017
294392P-010 E
Adder
20.3776470588235317.321
959352AF2-226 E
50/50
4.424.42
934101AD2-000 1
Adder
5.8964705882352945.012
958492AF2-143 E
Adder
7.2011764705882366.121
942421AE2-255 C
Adder
3.15058823529411752.678
290108LEEDK;1U E
Adder
24.58352941176470820.896
916221Z1-073 E
Adder
7.5505882352941186.418
957472AF2-041 E
Adder
10.9682352941176489.323
959092AF2-200 E
Adder
9.7494117647058838.287
966092AG1-478 E
Adder
0.50588235294117640.43
274682WAUKEGAN ;7U
Adder
42.623529411764736.23
942651AE2-281 C
Adder
0.840.714
942652AE2-281 E
Adder
5.1611764705882354.387
962691AG1-118 C
Adder
22.70941176470588419.303
962692AG1-118 E
Adder
15.1412.869
938851AE1-113 C
Adder
8.3164705882352947.069
272363ESS H440 ; R
Adder
2.69411764705882372.29
959091AF2-200 C
Adder
14.62470588235294112.431
940502AE2-035 E
Adder
3.4682352941176472.948
293519PILOT HIL;1E
Adder
16.58000000000000214.093
939351AE1-166 C
Adder
10.217647058823538.685
274675JOLIET 29;7U
Adder
76.2117647058823664.78
274674JOLIET 9 ;6U
Adder
35.323529411764730.025
293061N-015 E
Adder
16.04470588235294313.638
943121AE2-341 C
Adder
13.05176470588235211.094
274862TOP CROP ;2U
50/50
0.8420.842
939321AE1-163 C
Adder
5.8811764705882354.999
295111SUBLETTE E
Adder
2.78941176470588252.371
274860EASYR;U2 E
Adder
12.26705882352941210.427
960591AF2-350 C
Adder
7.1058823529411776.04
960592AF2-350 E
Adder
4.737647058823534.027
275149KELLYCK ;1E
Adder
16.58000000000000214.093
934722AD1-100 E
Adder
91.6917647058823677.938
960751AF2-366 C
Adder
7.1517647058823536.079
942422AE2-255 E
Adder
9.4505882352941168.033
960582AF2-349 E
Adder
37.19058823529411531.612
937312AD2-172 E
Adder
3.4682352941176472.948
274859EASYR;U1 E
Adder
12.26705882352941210.427
274754CRETE EC ;4U
50/50
6.1116.111
958012AF2-095 E
Adder
6.8211764705882355.798
934111AD2-000 2
Adder
6.3129411764705885.366
966442AG1-513 E
Adder
0.78235294117647070.665
274683WAUKEGAN ;8U
Adder
45.9439.049
290051GSG-6; E
Adder
10.715294117647069.108
959082AF2-199 E
Adder
3.65647058823529443.108
958912AF2-182 E
Adder
34.8823529411764729.65
941551AE2-152 C
Adder
11.78941176470588410.021
274676JOLIET 29;8U
50/50
76.25576.255
274704KENDALL ;1C
50/50
4.144.14
274706KENDALL ;2C
50/50
4.144.14
274705KENDALL ;1S
50/50
2.7692.769
958481AF2-142 C
Adder
10.8694117647058849.239
957332AF2-027 E
Adder
3.86117647058823543.282
274891CAYUG;2U E
Adder
13.66000000000000211.611
926822AC1-168 E
Adder
7.797647058823536.628
274751CRETE EC ;1U
50/50
6.1116.111
293644O22 E1
50/50
16.92816.928
960281AF2-319 C
50/50
2.9472.947
960752AF2-366 E
Adder
4.7682352941176474.053
957471AF2-041 C
Adder
21.9376470588235318.647
294763P-046 E
Adder
9.6411764705882378.195
938861AE1-114 C
Adder
4.0152941176470593.413
926821AC1-168 C
Adder
1.16235294117647060.988
938862AE1-114 E
Adder
13.70117647058823711.646
274753CRETE EC ;3U
50/50
6.1116.111
936372AD2-047 E
Adder
19.6616.711
274654BRAIDWOOD;1U
50/50
27.62127.621
274861TOP CROP ;1U
50/50
0.4420.442
276591L-013 2
Adder
3.7670588235294123.202
962781AG1-127 C
Adder
7.1717647058823536.096
933911AD1-013 C
Adder
1.88588235294117661.603
943592AF1-030 E
Adder
4.2941176470588233.65
943591AF1-030 C
Adder
8.687.378
936292AD2-038 E
Adder
14.8352941176470612.61
290021O50 E
Adder
20.16117647058823817.137
937002AD2-134 E
Adder
10.368.806
274707KENDALL ;2S
50/50
2.7692.769
957331AF2-027 C
Adder
2.57411764705882362.188
936511AD2-066 C
Adder
8.5164705882352937.239
936512AD2-066 E
Adder
5.67764705882352954.826
295109WESTBROOK E
Adder
5.7364705882352954.876
939061AE1-134 2
Adder
1.39764705882352951.188
941552AE2-152 E
Adder
7.8588235294117646.68
958482AF2-142 E
Adder
7.2458823529411776.159
938852AE1-113 E
Adder
29.48470588235294425.062
274890CAYUG;1U E
Adder
13.66000000000000211.611
962012AG1-044 E
Adder
0.063529411764705890.054
943122AE2-341 E
Adder
6.4094117647058835.448
939322AE1-163 E
Adder
36.1270588235294130.708
293516O-009 E
Adder
8.2905882352941187.047
274752CRETE EC ;2U
50/50
6.1116.111
936371AD2-047 C
Adder
4.0270588235294123.423
936461AD2-060 C
Adder
2.3682352941176472.013
933412AC2-154 E
Adder
3.6717647058823533.121
962782AG1-127 E
Adder
4.7729411764705894.057
946671AF1-331 C
Adder
2.4494117647058822.082
274655BRAIDWOOD;2U
50/50
26.87526.875
959351AF2-226 C
50/50
2.9472.947
958491AF2-143 C
Adder
10.8023529411764719.182
933912AD1-013 E
Adder
3.01294117647058852.561
946152AF1-280 E
Adder
23.25529411764705819.767
293645O22 E2
50/50
19.38819.388
960282AF2-319 E
50/50
4.424.42
918052AA1-018 E OP
Adder
15.76000000000000213.396
920272AA2-123 E
Adder
2.9517647058823532.509
276626AG1-044 E
Adder
0.075294117647058830.064
276675AE2-062 E
Adder
0.152941176470588250.13
276170Z1-108 E
Adder
3.01294117647058852.561
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
O66PJM->LTFIMP_O-066
CMTX_NF
13.7513.75
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.30480.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.41313.413
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7060.706
MECLTFEXP_MEC->PJM
CLTF
13.16213.162
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0692.069
LAGNLTFEXP_LAGN->PJM
CLTF
3.2773.277
NYPJM->LTFIMP_NY
CLTF
1.1511.151
WECLTFEXP_WEC->PJM
CLTF
4.0154.015
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5770.577
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1432.143
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.44 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1768.9
MW Contribution:7.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
958011AF2-095 C
Adder
10.232941176470598.698
933411AC2-154 C
Adder
2.25058823529411761.913
274687WILL CNTY;4U
50/50
71.93571.935
966091AG1-478 C
Adder
2.00941176470588221.708
966441AG1-513 C
Adder
0.52235294117647060.444
959081AF2-199 C
Adder
7.3117647058823536.215
966092AG1-478 E
Adder
0.50588235294117640.43
274682WAUKEGAN ;7U
Adder
42.6236.227
942651AE2-281 C
Adder
0.840.714
942652AE2-281 E
Adder
5.1611764705882354.387
962691AG1-118 C
Adder
22.7070588235294119.301
962692AG1-118 E
Adder
15.13882352941176612.868
938851AE1-113 C
Adder
8.3164705882352947.069
272363ESS H440 ; R
Adder
2.69411764705882372.29
293519PILOT HIL;1E
Adder
16.58117647058823614.094
939351AE1-166 C
Adder
10.217647058823538.685
274675JOLIET 29;7U
Adder
76.2094117647058964.778
274674JOLIET 9 ;6U
Adder
35.32235294117647630.024
293061N-015 E
Adder
16.04470588235294313.638
943121AE2-341 C
Adder
13.05058823529411811.093
274862TOP CROP ;2U
50/50
0.8420.842
939321AE1-163 C
Adder
5.8811764705882354.999
295111SUBLETTE E
Adder
2.78823529411764742.37
274860EASYR;U2 E
Adder
12.26588235294117610.426
960591AF2-350 C
Adder
7.1058823529411776.04
960592AF2-350 E
Adder
4.737647058823534.027
275149KELLYCK ;1E
Adder
16.58117647058823614.094
934722AD1-100 E
Adder
91.6988235294117777.944
960751AF2-366 C
Adder
7.1517647058823536.079
942422AE2-255 E
Adder
9.4494117647058828.032
960582AF2-349 E
Adder
37.1870588235294131.609
937312AD2-172 E
Adder
3.4682352941176472.948
274859EASYR;U1 E
Adder
12.26588235294117610.426
274754CRETE EC ;4U
50/50
6.1116.111
958012AF2-095 E
Adder
6.8211764705882355.798
934111AD2-000 2
Adder
6.3117647058823545.365
966442AG1-513 E
Adder
0.78235294117647070.665
274683WAUKEGAN ;8U
Adder
45.93647058823529539.046
290051GSG-6; E
Adder
10.7141176470588229.107
959082AF2-199 E
Adder
3.65529411764705923.107
958912AF2-182 E
Adder
34.8788235294117629.647
959091AF2-200 C
Adder
14.62352941176470512.43
940502AE2-035 E
Adder
3.4682352941176472.948
941551AE2-152 C
Adder
11.78941176470588410.021
274676JOLIET 29;8U
50/50
76.25276.252
274704KENDALL ;1C
50/50
4.144.14
274706KENDALL ;2C
50/50
4.144.14
274705KENDALL ;1S
50/50
2.7692.769
958481AF2-142 C
Adder
10.8694117647058849.239
957332AF2-027 E
Adder
3.86117647058823543.282
274891CAYUG;2U E
Adder
13.66000000000000211.611
926822AC1-168 E
Adder
7.79647058823529456.627
274751CRETE EC ;1U
50/50
6.1116.111
293644O22 E1
50/50
16.92816.928
960281AF2-319 C
50/50
2.9462.946
960752AF2-366 E
Adder
4.7670588235294114.052
957471AF2-041 C
Adder
21.93529411764705718.645
294763P-046 E
Adder
9.648.194
938861AE1-114 C
Adder
4.0152941176470593.413
939352AE1-166 E
Adder
9.4317647058823538.017
294392P-010 E
Adder
20.37647058823529617.32
959352AF2-226 E
50/50
4.424.42
934101AD2-000 1
Adder
5.8952941176470595.011
958492AF2-143 E
Adder
7.2011764705882366.121
942421AE2-255 C
Adder
3.14941176470588242.677
290108LEEDK;1U E
Adder
24.58117647058823320.894
916221Z1-073 E
Adder
7.5494117647058836.417
957472AF2-041 E
Adder
10.9670588235294129.322
959092AF2-200 E
Adder
9.7494117647058838.287
926821AC1-168 C
Adder
1.16235294117647060.988
938862AE1-114 E
Adder
13.711.645
274753CRETE EC ;3U
50/50
6.1116.111
936372AD2-047 E
Adder
19.66117647058823416.712
274654BRAIDWOOD;1U
50/50
27.62127.621
943592AF1-030 E
Adder
4.2941176470588233.65
943591AF1-030 C
Adder
8.6788235294117657.377
936292AD2-038 E
Adder
14.83411764705882312.609
290021O50 E
Adder
20.1617.136
937002AD2-134 E
Adder
10.3588235294117658.805
274707KENDALL ;2S
50/50
2.7692.769
957331AF2-027 C
Adder
2.57411764705882362.188
936511AD2-066 C
Adder
8.5164705882352937.239
936512AD2-066 E
Adder
5.67764705882352954.826
295109WESTBROOK E
Adder
5.7364705882352954.876
939061AE1-134 2
Adder
1.39764705882352951.188
274861TOP CROP ;1U
50/50
0.4420.442
276591L-013 2
Adder
3.7670588235294123.202
962781AG1-127 C
Adder
7.1717647058823536.096
933911AD1-013 C
Adder
1.88588235294117661.603
941552AE2-152 E
Adder
7.866.681
958482AF2-142 E
Adder
7.2458823529411776.159
938852AE1-113 E
Adder
29.48352941176470725.061
274890CAYUG;1U E
Adder
13.66000000000000211.611
962012AG1-044 E
Adder
0.063529411764705890.054
943122AE2-341 E
Adder
6.4082352941176475.447
939322AE1-163 E
Adder
36.12588235294117630.707
293516O-009 E
Adder
8.2905882352941187.047
274752CRETE EC ;2U
50/50
6.1116.111
936371AD2-047 C
Adder
4.0270588235294123.423
936461AD2-060 C
Adder
2.3682352941176472.013
933412AC2-154 E
Adder
3.6717647058823533.121
962782AG1-127 E
Adder
4.7729411764705894.057
946671AF1-331 C
Adder
2.4494117647058822.082
274655BRAIDWOOD;2U
50/50
26.87526.875
959351AF2-226 C
50/50
2.9462.946
958491AF2-143 C
Adder
10.8023529411764719.182
933912AD1-013 E
Adder
3.01294117647058852.561
946152AF1-280 E
Adder
23.2529411764705919.765
293645O22 E2
50/50
19.38819.388
960282AF2-319 E
50/50
4.424.42
918052AA1-018 E OP
Adder
15.76000000000000213.396
920272AA2-123 E
Adder
2.9517647058823532.509
276626AG1-044 E
Adder
0.075294117647058830.064
276675AE2-062 E
Adder
0.152941176470588250.13
276170Z1-108 E
Adder
3.0117647058823532.56
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
O66PJM->LTFIMP_O-066
CMTX_NF
13.7513.75
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.29780.297
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.41213.412
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7060.706
MECLTFEXP_MEC->PJM
CLTF
13.16113.161
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0692.069
LAGNLTFEXP_LAGN->PJM
CLTF
3.2773.277
NYPJM->LTFIMP_NY
CLTF
1.1511.151
WECLTFEXP_WEC->PJM
CLTF
4.0154.015
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5760.576
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1432.143
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.42 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1768.67
MW Contribution:7.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
958011AF2-095 C
Adder
10.1811764705882368.654
933411AC2-154 C
Adder
2.23882352941176471.903
274687WILL CNTY;4U
50/50
71.61971.619
966091AG1-478 C
Adder
2.01.7
966441AG1-513 C
Adder
0.520.442
959081AF2-199 C
Adder
7.2835294117647066.191
293519PILOT HIL;1E
Adder
16.49764705882352814.023
939351AE1-166 C
Adder
10.1800000000000018.653
274675JOLIET 29;7U
Adder
75.8694117647058964.489
274674JOLIET 9 ;6U
Adder
35.15058823529411629.878
293061N-015 E
Adder
15.9752941176470613.579
943121AE2-341 C
Adder
12.98823529411764711.04
274862TOP CROP ;2U
50/50
0.8390.839
939321AE1-163 C
Adder
5.8588235294117654.98
295111SUBLETTE E
Adder
2.77764705882352962.361
274860EASYR;U2 E
Adder
12.2223529411764710.389
960591AF2-350 C
Adder
7.0705882352941176.01
960592AF2-350 E
Adder
4.7141176470588234.007
275149KELLYCK ;1E
Adder
16.49764705882352814.023
934722AD1-100 E
Adder
91.3611764705882377.657
960751AF2-366 C
Adder
7.1211764705882356.053
942422AE2-255 E
Adder
9.415294117647068.003
960582AF2-349 E
Adder
37.0376470588235331.482
937312AD2-172 E
Adder
3.45529411764705862.937
274859EASYR;U1 E
Adder
12.2223529411764710.389
274754CRETE EC ;4U
50/50
6.1016.101
958012AF2-095 E
Adder
6.7870588235294125.769
934111AD2-000 2
Adder
6.2858823529411775.343
966442AG1-513 E
Adder
0.77882352941176480.662
274683WAUKEGAN ;8U
Adder
45.7388235294117738.878
290051GSG-6; E
Adder
10.6705882352941199.07
959082AF2-199 E
Adder
3.64117647058823573.095
958912AF2-182 E
Adder
34.7576470588235329.544
966092AG1-478 E
Adder
0.50352941176470590.428
274682WAUKEGAN ;7U
Adder
42.43647058823529536.071
942651AE2-281 C
Adder
0.83647058823529410.711
942652AE2-281 E
Adder
5.1411764705882364.37
962691AG1-118 C
Adder
22.60941176470588219.218
962692AG1-118 E
Adder
15.07294117647058812.812
938851AE1-113 C
Adder
8.2858823529411787.043
272363ESS H440 ; R
Adder
2.68235294117647042.28
959091AF2-200 C
Adder
14.56588235294117712.381
940502AE2-035 E
Adder
3.45529411764705862.937
941551AE2-152 C
Adder
11.7458823529411779.984
274676JOLIET 29;8U
50/50
75.91275.912
274704KENDALL ;1C
50/50
4.1234.123
274706KENDALL ;2C
50/50
4.1234.123
274751CRETE EC ;1U
50/50
6.1016.101
293644O22 E1
50/50
16.86916.869
960281AF2-319 C
50/50
2.9362.936
960752AF2-366 E
Adder
4.7470588235294124.035
957471AF2-041 C
Adder
21.8494117647058818.572
294763P-046 E
Adder
9.6035294117647068.163
938861AE1-114 C
Adder
4.0011764705882353.401
274705KENDALL ;1S
50/50
2.7572.757
958481AF2-142 C
Adder
10.8235294117647059.2
957332AF2-027 E
Adder
3.8447058823529413.268
274891CAYUG;2U E
Adder
13.62588235294117711.582
926822AC1-168 E
Adder
7.7741176470588236.608
939352AE1-166 E
Adder
9.397647058823537.988
294392P-010 E
Adder
20.28941176470588217.246
959352AF2-226 E
50/50
4.4044.404
934101AD2-000 1
Adder
5.8705882352941184.99
958492AF2-143 E
Adder
7.1729411764705896.097
942421AE2-255 C
Adder
3.1388235294117652.668
290108LEEDK;1U E
Adder
24.47764705882353220.806
916221Z1-073 E
Adder
7.52000000000000056.392
957472AF2-041 E
Adder
10.924705882352949.286
959092AF2-200 E
Adder
9.7105882352941188.254
926821AC1-168 C
Adder
1.15882352941176480.985
938862AE1-114 E
Adder
13.65058823529411711.603
943592AF1-030 E
Adder
4.2741176470588243.633
943591AF1-030 C
Adder
8.6376470588235297.342
936292AD2-038 E
Adder
14.7776470588235312.561
290021O50 E
Adder
20.08705882352941417.074
937002AD2-134 E
Adder
10.317647058823538.77
274707KENDALL ;2S
50/50
2.7572.757
957331AF2-027 C
Adder
2.5635294117647062.179
936511AD2-066 C
Adder
8.484705882352947.212
936512AD2-066 E
Adder
5.6564705882352944.808
295109WESTBROOK E
Adder
5.7129411764705884.856
939061AE1-134 2
Adder
1.39294117647058811.184
274753CRETE EC ;3U
50/50
6.1016.101
936372AD2-047 E
Adder
19.5623529411764716.628
274654BRAIDWOOD;1U
50/50
27.51327.513
274861TOP CROP ;1U
50/50
0.440.44
276591L-013 2
Adder
3.7505882352941183.188
962781AG1-127 C
Adder
7.1411764705882366.07
933911AD1-013 C
Adder
1.87882352941176481.597
941552AE2-152 E
Adder
7.8305882352941176.656
958482AF2-142 E
Adder
7.2152941176470596.133
938852AE1-113 E
Adder
29.3776470588235324.971
274890CAYUG;1U E
Adder
13.62588235294117711.582
962012AG1-044 E
Adder
0.063529411764705890.054
943122AE2-341 E
Adder
6.377647058823535.421
939322AE1-163 E
Adder
35.98588235294117530.588
293516O-009 E
Adder
8.2647058823529427.025
274752CRETE EC ;2U
50/50
6.1016.101
936371AD2-047 C
Adder
4.00705882352941253.406
936461AD2-060 C
Adder
2.3564705882352942.003
933412AC2-154 E
Adder
3.6529411764705883.105
962782AG1-127 E
Adder
4.7517647058823534.039
946671AF1-331 C
Adder
2.442.074
274655BRAIDWOOD;2U
50/50
26.76926.769
959351AF2-226 C
50/50
2.9362.936
958491AF2-143 C
Adder
10.7600000000000029.146
933912AD1-013 E
Adder
3.00117647058823562.551
946152AF1-280 E
Adder
23.17176470588235719.696
293645O22 E2
50/50
19.32119.321
960282AF2-319 E
50/50
4.4044.404
918052AA1-018 E OP
Adder
15.69411764705882513.34
920272AA2-123 E
Adder
2.9388235294117652.498
276626AG1-044 E
Adder
0.075294117647058830.064
276675AE2-062 E
Adder
0.152941176470588250.13
276170Z1-108 E
Adder
2.9988235294117652.549
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8080.808
TVALTFEXP_TVA->PJM
CLTF
1.191.19
O66PJM->LTFIMP_O-066
CMTX_NF
13.71713.717
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.46579.465
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.83113.831
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6340.634
MECLTFEXP_MEC->PJM
CLTF
13.15813.158
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.8531.853
LAGNLTFEXP_LAGN->PJM
CLTF
3.3653.365
NYPJM->LTFIMP_NY
CLTF
1.151.15
WECLTFEXP_WEC->PJM
CLTF
3.9993.999
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5540.554
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1382.138
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2920.292

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.5 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1405.95
MW Contribution:2.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
958011AF2-095 C
Adder
10.2352941176470588.7
933411AC2-154 C
Adder
2.25058823529411761.913
274687WILL CNTY;4U
80/20
71.92771.927
966091AG1-478 C
Adder
2.00941176470588221.708
274733ELWOOD EC;3P
80/20
3.3583.358
966441AG1-513 C
Adder
0.52117647058823540.443
959081AF2-199 C
Adder
7.3070588235294126.211
942111AE2-223 C
Adder
1.86941176470588231.589
939741AE1-205 C
Adder
8.0529411764705886.845
274711KENDALL ;4S
80/20
2.5942.594
934101AD2-000 1
80/20
5.8925.892
942421AE2-255 C
Adder
3.14941176470588242.677
926821AC1-168 C
Adder
1.16117647058823530.987
959611AF2-252 C
Adder
1.82117647058823541.548
274708KENDALL ;3C
80/20
3.9223.922
274734ELWOOD EC;8P
80/20
3.3643.364
274736ELWOOD EC;9P
80/20
3.3643.364
274735ELWOOD EC;4P
80/20
3.3583.358
274682WAUKEGAN ;7U
Adder
42.636.21
942651AE2-281 C
Adder
0.840.714
962691AG1-118 C
Adder
22.6929411764705919.289
938851AE1-113 C
Adder
8.3141176470588247.067
959091AF2-200 C
Adder
14.61529411764705912.423
959341AF2-225 C
Adder
6.0400000000000015.134
965091AG1-374 C
Adder
16.39058823529411813.932
961501AF2-441 C
Adder
6.6670588235294125.667
939351AE1-166 C
80/20
10.22310.223
274675JOLIET 29;7U
80/20
76.19176.191
274674JOLIET 9 ;6U
Adder
35.31176470588235430.015
943121AE2-341 C
Adder
13.0411.084
274862TOP CROP ;2U
80/20
0.8420.842
939321AE1-163 C
Adder
5.8800000000000014.998
960591AF2-350 C
Adder
7.1082352941176476.042
934721AD1-100 C
80/20
3.0093.009
274728ELWOOD EC;5P
80/20
3.3643.364
274745AURORA EC;9P
80/20
1.0831.083
960751AF2-366 C
Adder
7.1470588235294126.075
274754CRETE EC ;4U
80/20
6.1116.111
934111AD2-000 2
80/20
6.316.31
274683WAUKEGAN ;8U
Adder
45.9152941176470639.028
941551AE2-152 C
80/20
11.79611.796
274676JOLIET 29;8U
80/20
76.23476.234
937401AD2-194 1
80/20
1.3081.308
274704KENDALL ;1C
80/20
4.1394.139
274706KENDALL ;2C
80/20
4.1394.139
274705KENDALL ;1S
80/20
2.7682.768
274847GR RIDGE ;BU
80/20
0.5960.596
958481AF2-142 C
Adder
10.8682352941176469.238
274751CRETE EC ;1U
80/20
6.1116.111
274729ELWOOD EC;1P
80/20
3.3583.358
960281AF2-319 C
80/20
2.9462.946
957471AF2-041 C
Adder
21.9223529411764718.634
938861AE1-114 C
Adder
4.0129411764705883.411
274710KENDALL ;4C
80/20
3.8793.879
274709KENDALL ;3S
80/20
2.5942.594
276642AC1-204 GEN2
80/20
12.51212.512
274707KENDALL ;2S
80/20
2.7682.768
274871GR RIDGE ;2U
80/20
0.2220.222
957331AF2-027 C
Adder
2.5729411764705882.187
936511AD2-066 C
Adder
8.5141176470588237.237
939061AE1-134 2
Adder
1.39647058823529411.187
274753CRETE EC ;3U
80/20
6.1116.111
274654BRAIDWOOD;1U
80/20
27.62627.626
274731ELWOOD EC;2P
80/20
3.3583.358
274861TOP CROP ;1U
80/20
0.4420.442
962781AG1-127 C
Adder
7.1670588235294126.092
933911AD1-013 C
Adder
1.88470588235294121.602
274660LASCO STA;1U
80/20
25.49425.494
943591AF1-030 C
Adder
8.6717647058823537.371
274752CRETE EC ;2U
80/20
6.1116.111
936371AD2-047 C
Adder
4.0282352941176473.424
936461AD2-060 C
Adder
2.3694117647058822.014
274732ELWOOD EC;7P
80/20
3.3643.364
274730ELWOOD EC;6P
80/20
3.3643.364
276660AB1-122 CT2
80/20
12.70612.706
274739AURORA EC;2P
80/20
3.5563.556
946671AF1-331 C
Adder
2.4482352941176472.081
960611AF2-352 C
Adder
1.82117647058823541.548
274661LASCO STA;2U
80/20
25.57725.577
276658AB1-122 CT1
80/20
11.86311.863
946321AF1-296 C
Adder
3.6188235294117653.076
937411AD2-194 2
80/20
1.3111.311
274737AURORA EC;1P
80/20
3.5563.556
274658DRESDEN ;2U
80/20
19.99619.996
274655BRAIDWOOD;2U
80/20
26.8826.88
276640AC1-204 GEN1
80/20
12.4912.49
959351AF2-226 C
80/20
2.9462.946
958491AF2-143 C
Adder
10.89.18
965931AG1-462 C
Adder
16.29411764705882213.85
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.25680.256
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.40713.407
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7050.705
MECLTFEXP_MEC->PJM
CLTF
13.15513.155
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0682.068
LAGNLTFEXP_LAGN->PJM
CLTF
3.2763.276
NYPJM->LTFIMP_NY
CLTF
1.1511.151
WECLTFEXP_WEC->PJM
CLTF
4.0134.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5760.576
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.5 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1405.93
MW Contribution:2.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
958011AF2-095 C
Adder
10.2352941176470588.7
933411AC2-154 C
Adder
2.25058823529411761.913
274687WILL CNTY;4U
80/20
71.92771.927
966091AG1-478 C
Adder
2.00941176470588221.708
274733ELWOOD EC;3P
80/20
3.3583.358
966441AG1-513 C
Adder
0.52117647058823540.443
959081AF2-199 C
Adder
7.3070588235294126.211
942111AE2-223 C
Adder
1.86941176470588231.589
939741AE1-205 C
Adder
8.0529411764705886.845
274711KENDALL ;4S
80/20
2.5942.594
934101AD2-000 1
80/20
5.8925.892
942421AE2-255 C
Adder
3.14941176470588242.677
926821AC1-168 C
Adder
1.16117647058823530.987
959611AF2-252 C
Adder
1.82117647058823541.548
274708KENDALL ;3C
80/20
3.9223.922
274734ELWOOD EC;8P
80/20
3.3643.364
274736ELWOOD EC;9P
80/20
3.3643.364
274735ELWOOD EC;4P
80/20
3.3583.358
274682WAUKEGAN ;7U
Adder
42.636.21
942651AE2-281 C
Adder
0.840.714
962691AG1-118 C
Adder
22.6929411764705919.289
938851AE1-113 C
Adder
8.3141176470588247.067
959091AF2-200 C
Adder
14.61529411764705912.423
959341AF2-225 C
Adder
6.0400000000000015.134
965091AG1-374 C
Adder
16.39058823529411813.932
961501AF2-441 C
Adder
6.6670588235294125.667
939351AE1-166 C
80/20
10.22310.223
274675JOLIET 29;7U
80/20
76.19176.191
274674JOLIET 9 ;6U
Adder
35.31176470588235430.015
943121AE2-341 C
Adder
13.0411.084
274862TOP CROP ;2U
80/20
0.8420.842
939321AE1-163 C
Adder
5.8800000000000014.998
960591AF2-350 C
Adder
7.1082352941176476.042
934721AD1-100 C
80/20
3.0093.009
274728ELWOOD EC;5P
80/20
3.3643.364
274745AURORA EC;9P
80/20
1.0831.083
960751AF2-366 C
Adder
7.1470588235294126.075
274754CRETE EC ;4U
80/20
6.1116.111
934111AD2-000 2
80/20
6.316.31
274683WAUKEGAN ;8U
Adder
45.9152941176470639.028
941551AE2-152 C
80/20
11.79611.796
274676JOLIET 29;8U
80/20
76.23476.234
937401AD2-194 1
80/20
1.3081.308
274704KENDALL ;1C
80/20
4.1394.139
274706KENDALL ;2C
80/20
4.1394.139
274705KENDALL ;1S
80/20
2.7682.768
274847GR RIDGE ;BU
80/20
0.5960.596
958481AF2-142 C
Adder
10.8682352941176469.238
274751CRETE EC ;1U
80/20
6.1116.111
274729ELWOOD EC;1P
80/20
3.3583.358
960281AF2-319 C
80/20
2.9462.946
957471AF2-041 C
Adder
21.9223529411764718.634
938861AE1-114 C
Adder
4.0129411764705883.411
274710KENDALL ;4C
80/20
3.8793.879
274709KENDALL ;3S
80/20
2.5942.594
276642AC1-204 GEN2
80/20
12.51212.512
274707KENDALL ;2S
80/20
2.7682.768
274871GR RIDGE ;2U
80/20
0.2220.222
957331AF2-027 C
Adder
2.5729411764705882.187
936511AD2-066 C
Adder
8.5141176470588237.237
939061AE1-134 2
Adder
1.39647058823529411.187
274753CRETE EC ;3U
80/20
6.1116.111
274654BRAIDWOOD;1U
80/20
27.62627.626
274731ELWOOD EC;2P
80/20
3.3583.358
274861TOP CROP ;1U
80/20
0.4420.442
962781AG1-127 C
Adder
7.1670588235294126.092
933911AD1-013 C
Adder
1.88470588235294121.602
274660LASCO STA;1U
80/20
25.49425.494
943591AF1-030 C
Adder
8.6717647058823537.371
274752CRETE EC ;2U
80/20
6.1116.111
936371AD2-047 C
Adder
4.0282352941176473.424
936461AD2-060 C
Adder
2.3694117647058822.014
274732ELWOOD EC;7P
80/20
3.3643.364
274730ELWOOD EC;6P
80/20
3.3643.364
276660AB1-122 CT2
80/20
12.70612.706
274739AURORA EC;2P
80/20
3.5563.556
946671AF1-331 C
Adder
2.4482352941176472.081
960611AF2-352 C
Adder
1.82117647058823541.548
274661LASCO STA;2U
80/20
25.57725.577
276658AB1-122 CT1
80/20
11.86311.863
946321AF1-296 C
Adder
3.6188235294117653.076
937411AD2-194 2
80/20
1.3111.311
274737AURORA EC;1P
80/20
3.5563.556
274658DRESDEN ;2U
80/20
19.99619.996
274655BRAIDWOOD;2U
80/20
26.8826.88
276640AC1-204 GEN1
80/20
12.4912.49
959351AF2-226 C
80/20
2.9462.946
958491AF2-143 C
Adder
10.89.18
965931AG1-462 C
Adder
16.29411764705882213.85
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.25680.256
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.40713.407
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7050.705
MECLTFEXP_MEC->PJM
CLTF
13.15513.155
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0682.068
LAGNLTFEXP_LAGN->PJM
CLTF
3.2763.276
NYPJM->LTFIMP_NY
CLTF
1.1511.151
WECLTFEXP_WEC->PJM
CLTF
4.0134.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5760.576
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.61 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1547.41
MW Contribution:7.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
941551AE2-152 C
Adder
11.88823529411764710.105
274676JOLIET 29;8U
50/50
76.77576.775
274704KENDALL ;1C
50/50
4.1694.169
274706KENDALL ;2C
50/50
4.1694.169
274705KENDALL ;1S
50/50
2.7882.788
293644O22 E1
50/50
17.04917.049
960281AF2-319 C
50/50
2.9682.968
960752AF2-366 E
Adder
4.8070588235294124.086
957471AF2-041 C
Adder
22.13176470588235418.812
294763P-046 E
Adder
9.730588235294128.271
938861AE1-114 C
Adder
4.0541176470588243.446
276642AC1-204 GEN2
50/50
12.60312.603
274707KENDALL ;2S
50/50
2.7882.788
957331AF2-027 C
Adder
2.59529411764705882.206
936511AD2-066 C
Adder
8.5941176470588237.305
936512AD2-066 E
Adder
5.7294117647058824.87
295109WESTBROOK E
Adder
5.7870588235294124.919
966092AG1-478 E
Adder
0.50941176470588230.433
274734ELWOOD EC;8P
50/50
3.3883.388
274682WAUKEGAN ;7U
Adder
42.9505882352941236.508
942651AE2-281 C
Adder
0.84823529411764710.721
942652AE2-281 E
Adder
5.2082352941176474.427
962691AG1-118 C
Adder
22.89176470588235219.458
962692AG1-118 E
Adder
15.26117647058823612.972
938851AE1-113 C
Adder
8.3894117647058837.131
272363ESS H440 ; R
Adder
2.71764705882352952.31
959091AF2-200 C
Adder
14.75411764705882512.541
940502AE2-035 E
Adder
3.50117647058823562.976
958012AF2-095 E
Adder
6.877647058823535.846
934111AD2-000 2
Adder
6.3588235294117655.405
966442AG1-513 E
Adder
0.78823529411764710.67
274683WAUKEGAN ;8U
Adder
46.2952941176470639.351
290051GSG-6; E
Adder
10.8082352941176479.187
959082AF2-199 E
Adder
3.6882352941176473.135
936372AD2-047 E
Adder
19.82352941176470716.85
274654BRAIDWOOD;1U
50/50
27.81527.815
274861TOP CROP ;1U
50/50
0.4450.445
276591L-013 2
Adder
3.7952941176470593.226
962781AG1-127 C
Adder
7.23058823529411756.146
933911AD1-013 C
Adder
1.90235294117647061.617
274660LASCO STA;1U
50/50
25.67925.679
943592AF1-030 E
Adder
4.3258823529411773.677
943591AF1-030 C
Adder
8.742352941176477.431
936292AD2-038 E
Adder
14.97058823529411812.725
290021O50 E
Adder
20.33764705882352817.287
937002AD2-134 E
Adder
10.4505882352941168.883
960591AF2-350 C
Adder
7.16470588235294156.09
960592AF2-350 E
Adder
4.7764705882352944.06
275149KELLYCK ;1E
Adder
16.7176470588235314.21
934722AD1-100 E
Adder
92.4678.591
960751AF2-366 C
Adder
7.2105882352941176.129
942422AE2-255 E
Adder
9.5329411764705888.103
960582AF2-349 E
Adder
37.5082352941176531.882
937312AD2-172 E
Adder
3.50117647058823562.976
274859EASYR;U1 E
Adder
12.38705882352941110.529
958481AF2-142 C
Adder
10.9647058823529419.32
957332AF2-027 E
Adder
3.8917647058823533.308
274661LASCO STA;2U
50/50
25.76325.763
943122AE2-341 E
Adder
6.45529411764705955.487
939322AE1-163 E
Adder
36.4588235294117730.99
936371AD2-047 C
Adder
4.06000000000000053.451
936461AD2-060 C
Adder
2.3882352941176472.03
933412AC2-154 E
Adder
3.70235294117647043.147
274732ELWOOD EC;7P
50/50
3.3883.388
274730ELWOOD EC;6P
50/50
3.3883.388
962782AG1-127 E
Adder
4.8117647058823534.09
946671AF1-331 C
Adder
2.47058823529411782.1
293519PILOT HIL;1E
Adder
16.7176470588235314.21
939351AE1-166 C
Adder
10.3023529411764718.757
274675JOLIET 29;7U
50/50
76.73276.732
274674JOLIET 9 ;6U
Adder
35.59176470588235530.253
293061N-015 E
Adder
16.1647058823529413.74
943121AE2-341 C
Adder
13.14705882352941311.175
274862TOP CROP ;2U
50/50
0.8480.848
939321AE1-163 C
Adder
5.9352941176470595.045
295111SUBLETTE E
Adder
2.81294117647058832.391
274860EASYR;U2 E
Adder
2.5435294117647062.162
274655BRAIDWOOD;2U
50/50
27.06427.064
276640AC1-204 GEN1
50/50
12.58212.582
959351AF2-226 C
50/50
2.9682.968
958491AF2-143 C
Adder
10.9011764705882369.266
933912AD1-013 E
Adder
3.042.584
939352AE1-166 E
Adder
9.5105882352941178.084
294392P-010 E
Adder
20.5282352941176517.449
959352AF2-226 E
50/50
4.4524.452
934101AD2-000 1
Adder
5.9435294117647065.052
958492AF2-143 E
Adder
7.2670588235294116.177
942421AE2-255 C
Adder
3.17764705882352952.701
290108LEEDK;1U E
Adder
24.78823529411764821.07
916221Z1-073 E
Adder
7.6164705882352956.474
957472AF2-041 E
Adder
11.0658823529411779.406
959092AF2-200 E
Adder
9.8364705882352958.361
938862AE1-114 E
Adder
13.83176470588235311.757
941552AE2-152 E
Adder
7.9247058823529416.736
958482AF2-142 E
Adder
7.30941176470588256.213
938852AE1-113 E
Adder
29.74470588235294225.283
958011AF2-095 C
Adder
10.3164705882352948.769
933411AC2-154 C
Adder
2.26941176470588251.929
274687WILL CNTY;4U
50/50
72.4272.42
966091AG1-478 C
Adder
2.02470588235294141.721
966441AG1-513 C
Adder
0.52588235294117650.447
959081AF2-199 C
Adder
7.377647058823536.271
293645O22 E2
50/50
19.52719.527
960282AF2-319 E
50/50
4.4524.452
918052AA1-018 E OP
Adder
15.89882352941176413.514
276675AE2-062 E
Adder
0.154117647058823530.131
276170Z1-108 E
Adder
3.03647058823529432.581
920272AA2-123 E
Adder
2.97647058823529382.53
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.690.69
TVALTFEXP_TVA->PJM
CLTF
1.4091.409
O66PJM->LTFIMP_O-066
CMTX_NF
12.66112.661
CBM West 1LTFEXP_CBM-W1->PJM
CBM
82.12382.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.85714.857
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5470.547
MECLTFEXP_MEC->PJM
CLTF
13.40713.407
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5811.581
LAGNLTFEXP_LAGN->PJM
CLTF
3.643.64
NYPJM->LTFIMP_NY
CLTF
1.0631.063
WECLTFEXP_WEC->PJM
CLTF
4.0514.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4630.463
G-007PJM->LTFIMP_G-007
CMTX_NF
1.9731.973
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2370.237
SIGELTFEXP_SIGE->PJM
CLTF
0.0050.005

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.58 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1546.98
MW Contribution:7.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
293644O22 E1
50/50
17.10817.108
960281AF2-319 C
50/50
2.9782.978
960752AF2-366 E
Adder
4.8282352941176474.104
957471AF2-041 C
Adder
22.22000000000000218.887
294763P-046 E
Adder
9.7670588235294128.302
938861AE1-114 C
Adder
4.0694117647058823.459
276642AC1-204 GEN2
50/50
12.65812.658
274707KENDALL ;2S
50/50
2.82.8
957331AF2-027 C
Adder
2.60588235294117652.215
936511AD2-066 C
Adder
8.6258823529411767.332
936512AD2-066 E
Adder
5.7505882352941184.888
295109WESTBROOK E
Adder
5.8105882352941184.939
966092AG1-478 E
Adder
0.51176470588235290.435
274734ELWOOD EC;8P
50/50
3.4033.403
274736ELWOOD EC;9P
50/50
3.4033.403
274682WAUKEGAN ;7U
Adder
43.13882352941176636.668
942651AE2-281 C
Adder
0.85058823529411760.723
942652AE2-281 E
Adder
5.2282352941176474.444
962691AG1-118 C
Adder
22.9929411764705919.544
962692AG1-118 E
Adder
15.32823529411764713.029
938851AE1-113 C
Adder
8.427.157
272363ESS H440 ; R
Adder
2.7282352941176472.319
959091AF2-200 C
Adder
14.81294117647058812.591
940502AE2-035 E
Adder
3.51411764705882362.987
958012AF2-095 E
Adder
6.9117647058823535.875
934111AD2-000 2
Adder
6.3858823529411765.428
966442AG1-513 E
Adder
0.7917647058823530.673
274683WAUKEGAN ;8U
Adder
46.4964705882352939.522
290051GSG-6; E
Adder
10.8529411764705899.225
959082AF2-199 E
Adder
3.7035294117647063.148
936372AD2-047 E
Adder
19.92117647058823616.933
274654BRAIDWOOD;1U
50/50
27.92327.923
274861TOP CROP ;1U
50/50
0.4460.446
276591L-013 2
Adder
3.81294117647058833.241
962781AG1-127 C
Adder
7.2623529411764716.173
933911AD1-013 C
Adder
1.9105882352941181.624
274660LASCO STA;1U
50/50
25.79425.794
943592AF1-030 E
Adder
4.3458823529411763.694
943591AF1-030 C
Adder
8.7847058823529427.467
936292AD2-038 E
Adder
15.02941176470588412.775
290021O50 E
Adder
20.41176470588235517.35
937002AD2-134 E
Adder
10.492941176470598.919
960591AF2-350 C
Adder
7.26.12
941551AE2-152 C
Adder
11.93058823529411910.141
274676JOLIET 29;8U
50/50
77.11877.118
274704KENDALL ;1C
50/50
4.1874.187
274706KENDALL ;2C
50/50
4.1874.187
274705KENDALL ;1S
50/50
2.82.8
958481AF2-142 C
Adder
11.0105882352941199.359
957332AF2-027 E
Adder
3.90941176470588263.323
274661LASCO STA;2U
50/50
25.87825.878
943122AE2-341 E
Adder
6.4870588235294125.514
939322AE1-163 E
Adder
36.631.11
960592AF2-350 E
Adder
4.84.08
275149KELLYCK ;1E
Adder
16.814.28
934722AD1-100 E
Adder
92.7905882352941278.872
274728ELWOOD EC;5P
50/50
3.4033.403
960751AF2-366 C
Adder
7.2411764705882366.155
942422AE2-255 E
Adder
9.5682352941176458.133
960582AF2-349 E
Adder
37.6611764705882432.012
937312AD2-172 E
Adder
3.51411764705882362.987
274859EASYR;U1 E
Adder
12.43176470588235310.567
936371AD2-047 C
Adder
4.083.468
936461AD2-060 C
Adder
2.42.04
933412AC2-154 E
Adder
3.723.162
962782AG1-127 E
Adder
4.8329411764705884.108
946671AF1-331 C
Adder
2.48117647058823552.109
293519PILOT HIL;1E
Adder
16.814.28
939351AE1-166 C
Adder
10.348.789
274675JOLIET 29;7U
50/50
77.07577.075
274674JOLIET 9 ;6U
Adder
35.7647058823529430.4
293061N-015 E
Adder
16.2329411764705913.798
943121AE2-341 C
Adder
13.20941176470588211.228
274862TOP CROP ;2U
50/50
0.8510.851
939321AE1-163 C
Adder
5.957647058823535.064
295111SUBLETTE E
Adder
2.8247058823529412.401
274860EASYR;U2 E
Adder
2.5529411764705882.17
274655BRAIDWOOD;2U
50/50
27.1727.17
276640AC1-204 GEN1
50/50
12.63712.637
959351AF2-226 C
50/50
2.9782.978
958491AF2-143 C
Adder
10.9435294117647069.302
933912AD1-013 E
Adder
3.0517647058823532.594
939352AE1-166 E
Adder
9.5447058823529418.113
294392P-010 E
Adder
20.61647058823529517.524
959352AF2-226 E
50/50
4.4674.467
934101AD2-000 1
Adder
5.9694117647058835.074
958492AF2-143 E
Adder
7.29529411764705856.201
942421AE2-255 C
Adder
3.18941176470588242.711
290108LEEDK;1U E
Adder
24.89294117647058621.159
916221Z1-073 E
Adder
7.6470588235294126.5
957472AF2-041 E
Adder
11.1094117647058829.443
959092AF2-200 E
Adder
9.8752941176470598.394
938862AE1-114 E
Adder
13.88352941176470711.801
941552AE2-152 E
Adder
7.9529411764705886.76
958482AF2-142 E
Adder
7.346.239
938852AE1-113 E
Adder
29.8529411764705925.375
958011AF2-095 C
Adder
10.3682352941176488.813
933411AC2-154 C
Adder
2.281.938
274687WILL CNTY;4U
50/50
72.73772.737
966091AG1-478 C
Adder
2.03411764705882361.729
966441AG1-513 C
Adder
0.52823529411764710.449
959081AF2-199 C
Adder
7.4070588235294126.296
293645O22 E2
50/50
19.59519.595
960282AF2-319 E
50/50
4.4674.467
918052AA1-018 E OP
Adder
15.96470588235294113.57
276675AE2-062 E
Adder
0.155294117647058830.132
276170Z1-108 E
Adder
3.04941176470588272.592
920272AA2-123 E
Adder
2.9882352941176472.54
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.7170.717
TVALTFEXP_TVA->PJM
CLTF
1.3271.327
O66PJM->LTFIMP_O-066
CMTX_NF
12.69412.694
CBM West 1LTFEXP_CBM-W1->PJM
CBM
82.96182.961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.43914.439
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6180.618
MECLTFEXP_MEC->PJM
CLTF
13.41113.411
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.7971.797
LAGNLTFEXP_LAGN->PJM
CLTF
3.5523.552
NYPJM->LTFIMP_NY
CLTF
1.0641.064
WECLTFEXP_WEC->PJM
CLTF
4.0674.067
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4860.486
G-007PJM->LTFIMP_G-007
CMTX_NF
1.9781.978
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2520.252

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.57 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1546.92
MW Contribution:7.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
293644O22 E1
50/50
17.10817.108
960281AF2-319 C
50/50
2.9782.978
960752AF2-366 E
Adder
4.8270588235294124.103
957471AF2-041 C
Adder
22.2176470588235318.885
294763P-046 E
Adder
9.7670588235294128.302
938861AE1-114 C
Adder
4.0694117647058823.459
276642AC1-204 GEN2
50/50
12.65712.657
274707KENDALL ;2S
50/50
2.82.8
957331AF2-027 C
Adder
2.60588235294117652.215
936511AD2-066 C
Adder
8.6258823529411767.332
936512AD2-066 E
Adder
5.7505882352941184.888
295109WESTBROOK E
Adder
5.80941176470588254.938
966092AG1-478 E
Adder
0.51176470588235290.435
274736ELWOOD EC;9P
50/50
3.4033.403
274682WAUKEGAN ;7U
Adder
43.1352941176470636.665
942651AE2-281 C
Adder
0.85058823529411760.723
942652AE2-281 E
Adder
5.2282352941176474.444
962691AG1-118 C
Adder
22.9905882352941219.542
962692AG1-118 E
Adder
15.32705882352941313.028
938851AE1-113 C
Adder
8.427.157
272363ESS H440 ; R
Adder
2.7282352941176472.319
959091AF2-200 C
Adder
14.81176470588235412.59
940502AE2-035 E
Adder
3.51411764705882362.987
936372AD2-047 E
Adder
19.92117647058823616.933
274654BRAIDWOOD;1U
50/50
27.92427.924
274861TOP CROP ;1U
50/50
0.4460.446
276591L-013 2
Adder
3.81294117647058833.241
962781AG1-127 C
Adder
7.2611764705882356.172
933911AD1-013 C
Adder
1.9105882352941181.624
274660LASCO STA;1U
50/50
25.79225.792
943592AF1-030 E
Adder
4.3458823529411763.694
943591AF1-030 C
Adder
8.7835294117647067.466
936292AD2-038 E
Adder
15.02823529411764612.774
290021O50 E
Adder
20.41058823529411717.349
937002AD2-134 E
Adder
10.4917647058823528.918
941551AE2-152 C
Adder
11.93058823529411910.141
274676JOLIET 29;8U
50/50
77.11677.116
274704KENDALL ;1C
50/50
4.1874.187
274706KENDALL ;2C
50/50
4.1874.187
274705KENDALL ;1S
50/50
2.82.8
958481AF2-142 C
Adder
11.0105882352941199.359
957332AF2-027 E
Adder
3.9082352941176473.322
274661LASCO STA;2U
50/50
25.87625.876
943122AE2-341 E
Adder
6.4858823529411775.513
939322AE1-163 E
Adder
36.5988235294117731.109
960591AF2-350 C
Adder
7.26.12
960592AF2-350 E
Adder
4.84.08
275149KELLYCK ;1E
Adder
16.80117647058823514.281
934722AD1-100 E
Adder
92.7976470588235378.878
274728ELWOOD EC;5P
50/50
3.4033.403
960751AF2-366 C
Adder
7.2411764705882366.155
942422AE2-255 E
Adder
9.5682352941176458.133
960582AF2-349 E
Adder
37.6588235294117632.01
937312AD2-172 E
Adder
3.51411764705882362.987
274859EASYR;U1 E
Adder
2.5529411764705882.17
936371AD2-047 C
Adder
4.083.468
936461AD2-060 C
Adder
2.42.04
933412AC2-154 E
Adder
3.723.162
274732ELWOOD EC;7P
50/50
3.4033.403
962782AG1-127 E
Adder
4.8317647058823534.107
946671AF1-331 C
Adder
2.48117647058823552.109
293519PILOT HIL;1E
Adder
16.80117647058823514.281
939351AE1-166 C
Adder
10.348.789
274675JOLIET 29;7U
50/50
77.07277.072
274674JOLIET 9 ;6U
Adder
35.7635294117647130.399
293061N-015 E
Adder
16.2329411764705913.798
943121AE2-341 C
Adder
13.20823529411764811.227
274862TOP CROP ;2U
50/50
0.8510.851
939321AE1-163 C
Adder
5.957647058823535.064
295111SUBLETTE E
Adder
2.8247058823529412.401
274860EASYR;U2 E
Adder
12.43058823529411910.566
274655BRAIDWOOD;2U
50/50
27.1727.17
276640AC1-204 GEN1
50/50
12.63612.636
959351AF2-226 C
50/50
2.9782.978
958491AF2-143 C
Adder
10.9435294117647069.302
933912AD1-013 E
Adder
3.0517647058823532.594
939352AE1-166 E
Adder
9.5447058823529418.113
294392P-010 E
Adder
20.6152941176470617.523
959352AF2-226 E
50/50
4.4674.467
934101AD2-000 1
Adder
5.96823529411764755.073
958492AF2-143 E
Adder
7.29529411764705856.201
942421AE2-255 C
Adder
3.18941176470588242.711
290108LEEDK;1U E
Adder
24.89058823529411821.157
916221Z1-073 E
Adder
7.6470588235294126.5
957472AF2-041 E
Adder
11.1094117647058829.443
959092AF2-200 E
Adder
9.8741176470588248.393
938862AE1-114 E
Adder
13.88235294117647111.8
941552AE2-152 E
Adder
7.95411764705882356.761
958482AF2-142 E
Adder
7.346.239
938852AE1-113 E
Adder
29.85176470588235325.374
958011AF2-095 C
Adder
10.3682352941176488.813
933411AC2-154 C
Adder
2.281.938
274687WILL CNTY;4U
50/50
72.73672.736
966091AG1-478 C
Adder
2.03411764705882361.729
966441AG1-513 C
Adder
0.52823529411764710.449
959081AF2-199 C
Adder
7.4058823529411776.295
293645O22 E2
50/50
19.59519.595
960282AF2-319 E
50/50
4.4674.467
918052AA1-018 E OP
Adder
15.96470588235294113.57
958012AF2-095 E
Adder
6.9117647058823535.875
934111AD2-000 2
Adder
6.3847058823529415.427
966442AG1-513 E
Adder
0.7917647058823530.673
274683WAUKEGAN ;8U
Adder
46.4929411764705939.519
290051GSG-6; E
Adder
10.8517647058823539.224
959082AF2-199 E
Adder
3.7035294117647063.148
276170Z1-108 E
Adder
3.04941176470588272.592
920272AA2-123 E
Adder
2.9882352941176472.54
276675AE2-062 E
Adder
0.155294117647058830.132
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.7170.717
TVALTFEXP_TVA->PJM
CLTF
1.3271.327
O66PJM->LTFIMP_O-066
CMTX_NF
12.69312.693
CBM West 1LTFEXP_CBM-W1->PJM
CBM
82.95582.955
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.43814.438
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6180.618
MECLTFEXP_MEC->PJM
CLTF
13.4113.41
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.7971.797
LAGNLTFEXP_LAGN->PJM
CLTF
3.5523.552
NYPJM->LTFIMP_NY
CLTF
1.0641.064
WECLTFEXP_WEC->PJM
CLTF
4.0664.066
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4860.486
G-007PJM->LTFIMP_G-007
CMTX_NF
1.9781.978
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2520.252

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4-6_116-345-R______SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_116-345-R______SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.57 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2471.0
MW Contribution:14.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274676JOLIET 29;8U
Adder
84.2188235294117671.586
937401AD2-194 1
50/50
1.9831.983
958481AF2-142 C
Adder
13.19647058823529511.217
957332AF2-027 E
Adder
3.14705882352941172.675
926822AC1-168 E
Adder
5.1858823529411774.408
274729ELWOOD EC;1P
50/50
5.0895.089
293644O22 E1
50/50
33.48133.481
960281AF2-319 C
50/50
5.8285.828
960752AF2-366 E
Adder
3.35647058823529452.853
957471AF2-041 C
Adder
17.23882352941176414.653
294763P-046 E
Adder
7.6411764705882366.495
938861AE1-114 C
Adder
3.19411764705882332.715
276642AC1-204 GEN2
50/50
19.02419.024
957331AF2-027 C
Adder
2.0988235294117651.784
936511AD2-066 C
Adder
7.0129411764705895.961
936512AD2-066 E
Adder
4.6752941176470593.974
295109WESTBROOK E
Adder
4.197647058823533.568
939061AE1-134 2
Adder
1.13411764705882350.964
990901L-005 E
Adder
11.329.622
966092AG1-478 E
Adder
0.292941176470588260.249
274734ELWOOD EC;8P
50/50
5.1145.114
274736ELWOOD EC;9P
50/50
5.1145.114
274735ELWOOD EC;4P
50/50
5.0895.089
274682WAUKEGAN ;7U
Adder
34.8294117647058829.605
942651AE2-281 C
Adder
1.03882352941176470.883
942652AE2-281 E
Adder
6.3788235294117655.422
962691AG1-118 C
Adder
15.91411764705882313.527
962692AG1-118 E
Adder
10.6094117647058849.018
938851AE1-113 C
Adder
10.552941176470598.97
272363ESS H440 ; R
Adder
1.96705882352941171.672
959091AF2-200 C
Adder
11.4917647058823539.768
940502AE2-035 E
Adder
2.74941176470588242.337
965932AG1-462 E
Adder
9.1835294117647067.806
934111AD2-000 2
Adder
7.8929411764705886.709
966442AG1-513 E
Adder
0.54705882352941180.465
274683WAUKEGAN ;8U
Adder
37.50470588235294431.879
290051GSG-6; E
Adder
7.846.664
959082AF2-199 E
Adder
2.87294117647058832.442
958912AF2-182 E
Adder
28.10235294117647323.887
294401BSHIL;1U E
Adder
7.4129411764705886.301
274861TOP CROP ;1U
50/50
0.8730.873
276591L-013 2
Adder
2.7541176470588242.341
962781AG1-127 C
Adder
5.0494117647058834.292
933911AD1-013 C
Adder
1.37647058823529411.17
943592AF1-030 E
Adder
2.51529411764705872.138
943591AF1-030 C
Adder
5.0847058823529414.322
936292AD2-038 E
Adder
18.3352941176470615.585
290021O50 E
Adder
25.58117647058823621.744
937002AD2-134 E
Adder
7.586.443
274728ELWOOD EC;5P
50/50
5.1145.114
960751AF2-366 C
Adder
5.035294117647064.28
942422AE2-255 E
Adder
11.99176470588235310.193
960582AF2-349 E
Adder
29.2670588235294124.877
937312AD2-172 E
Adder
2.74941176470588242.337
274859EASYR;U1 E
Adder
9.8505882352941178.373
943122AE2-341 E
Adder
3.75411764705882333.191
939322AE1-163 E
Adder
44.6517647058823637.954
927208AC1-214 E1
Adder
2.69411764705882372.29
293516O-009 E
Adder
15.7152941176470613.358
293717O-029 E
Adder
4.0952941176470593.481
946321AF1-296 C
Adder
3.02705882352941162.573
959352AF2-226 E
50/50
8.7428.742
934101AD2-000 1
Adder
5.88705882352941155.004
958492AF2-143 E
Adder
8.9011764705882357.566
942421AE2-255 C
Adder
3.99764705882352983.398
290108LEEDK;1U E
Adder
17.4505882352941214.833
916221Z1-073 E
Adder
5.5247058823529414.696
957472AF2-041 E
Adder
8.6188235294117657.326
959092AF2-200 E
Adder
7.6611764705882356.512
926821AC1-168 C
Adder
0.77294117647058820.657
938862AE1-114 E
Adder
10.8952941176470589.261
274732ELWOOD EC;7P
50/50
5.1145.114
274730ELWOOD EC;6P
50/50
5.1145.114
962782AG1-127 E
Adder
3.362.856
946671AF1-331 C
Adder
1.78823529411764711.52
274675JOLIET 29;7U
Adder
83.9305882352941171.341
943121AE2-341 C
Adder
7.6458823529411766.499
274862TOP CROP ;2U
50/50
1.6661.666
939321AE1-163 C
Adder
7.26941176470588256.179
295111SUBLETTE E
Adder
2.041.734
274860EASYR;U2 E
Adder
9.8505882352941178.373
927209AC1-214 E2
Adder
2.69411764705882372.29
946322AF1-296 E
Adder
14.17411764705882312.048
276640AC1-204 GEN1
50/50
18.92818.928
959351AF2-226 C
50/50
5.8285.828
958491AF2-143 C
Adder
13.35058823529411911.348
933912AD1-013 E
Adder
2.19882352941176461.869
946152AF1-280 E
Adder
18.7352941176470615.925
293771O-035 E
Adder
5.6823529411764714.83
293716O-029 E
Adder
4.4564705882352943.788
965931AG1-462 C
Adder
13.77411764705882511.708
966091AG1-478 C
Adder
1.16588235294117660.991
274733ELWOOD EC;3P
50/50
5.0895.089
966441AG1-513 C
Adder
0.364705882352941160.31
959081AF2-199 C
Adder
5.7458823529411774.884
916212CRESCENT ;1U
Adder
3.9917647058823533.393
294410BSHIL;2U E
Adder
7.4129411764705886.301
966822AG1-553 E
Adder
23.40705882352941519.896
937411AD2-194 2
50/50
1.9931.993
958482AF2-142 E
Adder
8.7976470588235297.478
938852AE1-113 E
Adder
37.4129411764705931.801
962012AG1-044 E
Adder
0.051764705882352940.044
925582AC1-033 E
Adder
8.1270588235294126.908
293645O22 E2
50/50
38.34738.347
960282AF2-319 E
50/50
8.7428.742
918052AA1-018 E OP
Adder
19.13411764705882216.264
293715O-029 E
Adder
8.1270588235294126.908
276170Z1-108 E
Adder
2.35294117647058832
920272AA2-123 E
Adder
2.3082352941176471.962
276626AG1-044 E
Adder
0.061176470588235290.052
990552J1334 G
External Queue
-23.77029800415039-23.77029800415039
990557J1335 G
External Queue
-23.77029800415039-23.77029800415039
990562J1336 G
External Queue
-23.77029800415039-23.77029800415039
990577J1339
External Queue
-28.123506546020508-28.123506546020508
990547J1333 G
External Queue
-23.77029800415039-23.77029800415039
990582J1340
External Queue
-28.123506546020508-28.123506546020508
990662J1358
External Queue
-12.060297966003418-12.060297966003418
990647J1355
External Queue
-10.193851470947266-10.193851470947266
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.3820.382
TVALTFEXP_TVA->PJM
CLTF
1.2761.276
O66PJM->LTFIMP_O-066
CMTX_NF
8.148.14
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.268.2
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.94111.941
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.3970.397
MECLTFEXP_MEC->PJM
CLTF
11.3111.31
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.1491.149
LAGNLTFEXP_LAGN->PJM
CLTF
3.1343.134
NYPJM->LTFIMP_NY
CLTF
0.6860.686
WECLTFEXP_WEC->PJM
CLTF
3.283.28
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2450.245
G-007PJM->LTFIMP_G-007
CMTX_NF
1.2681.268
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1170.117

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614__SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_116-45-L11614__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.27 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2372.1
MW Contribution:14.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274676JOLIET 29;8U
Adder
63.8752941176470654.294
937401AD2-194 1
50/50
1.951.95
958481AF2-142 C
Adder
12.96117647058823511.017
957332AF2-027 E
Adder
2.54235294117647072.161
926822AC1-168 E
Adder
4.8552941176470594.127
274729ELWOOD EC;1P
50/50
5.0055.005
293644O22 E1
50/50
34.23434.234
960281AF2-319 C
50/50
5.9595.959
960752AF2-366 E
Adder
2.87294117647058832.442
957471AF2-041 C
Adder
14.92470588235294212.686
294763P-046 E
Adder
6.5117647058823535.535
938861AE1-114 C
Adder
2.74470588235294162.333
276642AC1-204 GEN2
50/50
18.72218.722
957331AF2-027 C
Adder
1.69529411764705881.441
936511AD2-066 C
Adder
6.53294117647058855.553
936512AD2-066 E
Adder
4.3552941176470593.702
295109WESTBROOK E
Adder
3.6164705882352943.074
939061AE1-134 2
Adder
0.98823529411764710.84
990901L-005 E
Adder
10.5717647058823538.986
966092AG1-478 E
Adder
0.268235294117647070.228
274734ELWOOD EC;8P
50/50
5.0335.033
274736ELWOOD EC;9P
50/50
5.0335.033
274682WAUKEGAN ;7U
Adder
28.12352941176470723.905
942651AE2-281 C
Adder
1.01882352941176470.866
942652AE2-281 E
Adder
6.2588235294117665.32
962691AG1-118 C
Adder
13.63294117647058811.588
962692AG1-118 E
Adder
9.0882352941176477.725
938851AE1-113 C
Adder
10.1835294117647088.656
272363ESS H440 ; R
Adder
1.69529411764705881.441
959091AF2-200 C
Adder
9.9494117647058848.457
940502AE2-035 E
Adder
2.3423529411764711.991
965932AG1-462 E
Adder
8.1223529411764716.904
934111AD2-000 2
Adder
7.502352941176476.377
966442AG1-513 E
Adder
0.46117647058823530.392
274683WAUKEGAN ;8U
Adder
30.27176470588235425.731
290051GSG-6; E
Adder
6.7552941176470595.742
959082AF2-199 E
Adder
2.48705882352941152.114
958912AF2-182 E
Adder
24.30352941176470720.658
294401BSHIL;1U E
Adder
6.8764705882352945.845
274731ELWOOD EC;2P
50/50
5.0055.005
274861TOP CROP ;1U
50/50
0.8930.893
276591L-013 2
Adder
2.32235294117647051.974
962781AG1-127 C
Adder
4.32235294117647053.674
933911AD1-013 C
Adder
1.18588235294117661.008
943592AF1-030 E
Adder
2.1623529411764711.838
943591AF1-030 C
Adder
4.3694117647058823.714
936292AD2-038 E
Adder
17.98823529411764715.29
290021O50 E
Adder
24.68705882352941620.984
937002AD2-134 E
Adder
6.53176470588235255.552
274728ELWOOD EC;5P
50/50
5.0335.033
960751AF2-366 C
Adder
4.3105882352941183.664
942422AE2-255 E
Adder
11.5717647058823539.836
960582AF2-349 E
Adder
24.51176470588235320.835
937312AD2-172 E
Adder
2.3423529411764711.991
274859EASYR;U1 E
Adder
8.4917647058823537.218
943122AE2-341 E
Adder
3.22705882352941182.743
939322AE1-163 E
Adder
43.8082352941176537.237
927208AC1-214 E1
Adder
2.50588235294117642.13
293516O-009 E
Adder
13.94235294117647211.851
293717O-029 E
Adder
3.63411764705882373.089
946321AF1-296 C
Adder
2.6705882352941182.27
959352AF2-226 E
50/50
8.9388.938
274732ELWOOD EC;7P
50/50
5.0335.033
274730ELWOOD EC;6P
50/50
5.0335.033
962782AG1-127 E
Adder
2.8764705882352942.445
946671AF1-331 C
Adder
1.541.309
274675JOLIET 29;7U
Adder
63.4341176470588253.919
943121AE2-341 C
Adder
6.5717647058823535.586
274862TOP CROP ;2U
50/50
1.7031.703
939321AE1-163 C
Adder
7.1317647058823546.062
295111SUBLETTE E
Adder
1.7588235294117651.495
274860EASYR;U2 E
Adder
8.4917647058823537.218
927209AC1-214 E2
Adder
2.50588235294117642.13
946322AF1-296 E
Adder
12.50235294117647210.627
276640AC1-204 GEN1
50/50
18.61918.619
959351AF2-226 C
50/50
5.9595.959
958491AF2-143 C
Adder
13.09882352941176511.134
933912AD1-013 E
Adder
1.89411764705882371.61
946152AF1-280 E
Adder
16.2023529411764713.772
293771O-035 E
Adder
5.2858823529411774.493
293716O-029 E
Adder
3.95294117647058843.36
965931AG1-462 C
Adder
12.18352941176470610.356
934101AD2-000 1
Adder
5.4164705882352954.604
958492AF2-143 E
Adder
8.7329411764705887.423
942421AE2-255 C
Adder
3.8576470588235293.279
290108LEEDK;1U E
Adder
14.98705882352941312.739
916221Z1-073 E
Adder
4.7611764705882354.047
957472AF2-041 E
Adder
7.4623529411764716.343
959092AF2-200 E
Adder
6.6329411764705885.638
926821AC1-168 C
Adder
0.72352941176470590.615
938862AE1-114 E
Adder
9.3635294117647067.959
966091AG1-478 C
Adder
1.06705882352941180.907
274733ELWOOD EC;3P
50/50
5.0055.005
966441AG1-513 C
Adder
0.30705882352941180.261
959081AF2-199 C
Adder
4.9752941176470594.229
916212CRESCENT ;1U
Adder
3.71294117647058863.156
294410BSHIL;2U E
Adder
6.8764705882352945.845
966822AG1-553 E
Adder
20.70352941176470617.598
937411AD2-194 2
50/50
1.9611.961
958482AF2-142 E
Adder
8.6411764705882357.345
938852AE1-113 E
Adder
36.10470588235294530.689
962012AG1-044 E
Adder
0.045882352941176470.039
925582AC1-033 E
Adder
7.5388235294117656.408
293645O22 E2
50/50
39.2139.21
960282AF2-319 E
50/50
8.9388.938
918052AA1-018 E OP
Adder
18.79411764705882215.975
293715O-029 E
Adder
7.2105882352941176.129
920272AA2-123 E
Adder
1.92705882352941171.638
276626AG1-044 E
Adder
0.054117647058823530.046
276170Z1-108 E
Adder
1.94588235294117641.654
990552J1334 G
External Queue
-22.909955978393555-22.909955978393555
990557J1335 G
External Queue
-22.909955978393555-22.909955978393555
990562J1336 G
External Queue
-22.909955978393555-22.909955978393555
990577J1339
External Queue
-27.099620819091797-27.099620819091797
990547J1333 G
External Queue
-22.909955978393555-22.909955978393555
990582J1340
External Queue
-27.099620819091797-27.099620819091797
990662J1358
External Queue
-11.463173866271973-11.463173866271973
990647J1355
External Queue
-9.393627166748047-9.393627166748047
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.3520.352
TVALTFEXP_TVA->PJM
CLTF
1.1651.165
O66PJM->LTFIMP_O-066
CMTX_NF
7.4827.482
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.86656.866
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.99810.998
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.3610.361
MECLTFEXP_MEC->PJM
CLTF
10.03810.038
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.0441.044
LAGNLTFEXP_LAGN->PJM
CLTF
2.8362.836
NYPJM->LTFIMP_NY
CLTF
0.630.63
WECLTFEXP_WEC->PJM
CLTF
2.6952.695
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2250.225
G-007PJM->LTFIMP_G-007
CMTX_NF
1.1661.166
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1080.108
SIGELTFEXP_SIGE->PJM
CLTF
00

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-45-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.41 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2306.47
MW Contribution:17.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274676JOLIET 29;8U
Adder
91.5117647058823677.785
937401AD2-194 1
50/50
1.8111.811
274704KENDALL ;1C
50/50
5.9235.923
274706KENDALL ;2C
50/50
5.9235.923
274705KENDALL ;1S
50/50
3.9613.961
957332AF2-027 E
Adder
3.50235294117647072.977
926822AC1-168 E
Adder
5.5847058823529414.747
274729ELWOOD EC;1P
50/50
4.6474.647
293644O22 E1
50/50
40.99540.995
960281AF2-319 C
50/50
7.1367.136
960752AF2-366 E
Adder
3.6705882352941183.12
957471AF2-041 C
Adder
18.82352941176470716
294763P-046 E
Adder
8.3823529411764717.125
938861AE1-114 C
Adder
3.52.975
276642AC1-204 GEN2
50/50
17.50217.502
274707KENDALL ;2S
50/50
3.9613.961
957331AF2-027 C
Adder
2.3352941176470591.985
936511AD2-066 C
Adder
7.3411764705882366.24
936512AD2-066 E
Adder
4.8941176470588244.16
295109WESTBROOK E
Adder
4.5905882352941183.902
939061AE1-134 2
Adder
1.24117647058823531.055
990901L-005 E
Adder
12.28823529411764810.445
290261S-027 E
Adder
12.5152941176470610.638
290265S-028 E
Adder
12.43882352941176510.573
274734ELWOOD EC;8P
50/50
4.7054.705
274736ELWOOD EC;9P
50/50
4.7054.705
274735ELWOOD EC;4P
50/50
4.6474.647
274682WAUKEGAN ;7U
Adder
38.8423529411764733.016
942651AE2-281 C
Adder
0.65647058823529430.558
942652AE2-281 E
Adder
4.03294117647058853.428
962691AG1-118 C
Adder
17.414.79
962692AG1-118 E
Adder
11.69.86
938851AE1-113 C
Adder
10.7835294117647079.166
272363ESS H440 ; R
Adder
2.1517647058823531.829
959091AF2-200 C
Adder
12.54823529411764810.666
940502AE2-035 E
Adder
3.01647058823529422.564
924048AB2-047 E1
Adder
8.5941176470588237.305
959341AF2-225 C
Adder
5.0176470588235294.265
965092AG1-374 E
Adder
9.2023529411764717.822
965091AG1-374 C
Adder
13.80470588235294111.734
965932AG1-462 E
Adder
10.0694117647058818.559
934111AD2-000 2
Adder
8.1694117647058836.944
966442AG1-513 E
Adder
0.59411764705882350.505
274683WAUKEGAN ;8U
Adder
41.79647058823529435.527
290051GSG-6; E
Adder
8.5729411764705887.287
959082AF2-199 E
Adder
3.13764705882352952.667
958912AF2-182 E
Adder
30.77764705882353326.161
294401BSHIL;1U E
Adder
8.0376470588235296.832
942112AE2-223 E
Adder
10.3941176470588268.835
959612AF2-252 E
Adder
2.30117647058823541.956
274731ELWOOD EC;2P
50/50
4.6474.647
274861TOP CROP ;1U
50/50
1.0691.069
276591L-013 2
Adder
3.00235294117647072.552
962781AG1-127 C
Adder
5.5211764705882354.693
933911AD1-013 C
Adder
1.50588235294117641.28
943592AF1-030 E
Adder
2.73411764705882332.324
943591AF1-030 C
Adder
5.5270588235294124.698
936292AD2-038 E
Adder
11.5917647058823539.853
290021O50 E
Adder
26.14235294117647322.221
937002AD2-134 E
Adder
8.2894117647058827.046
274728ELWOOD EC;5P
50/50
4.7054.705
960751AF2-366 C
Adder
5.50588235294117644.68
942422AE2-255 E
Adder
12.25411764705882510.416
960582AF2-349 E
Adder
32.12588235294117627.307
937312AD2-172 E
Adder
3.01647058823529422.564
274859EASYR;U1 E
Adder
10.7905882352941189.172
943122AE2-341 E
Adder
4.0811764705882353.469
939322AE1-163 E
Adder
28.22941176470588323.995
927208AC1-214 E1
Adder
2.92941176470588262.49
293516O-009 E
Adder
17.15882352941176614.585
293717O-029 E
Adder
4.4717647058823533.801
946321AF1-296 C
Adder
3.32000000000000032.822
274732ELWOOD EC;7P
50/50
4.7054.705
274730ELWOOD EC;6P
50/50
4.7054.705
962782AG1-127 E
Adder
3.67411764705882373.123
946671AF1-331 C
Adder
1.95529411764705881.662
960611AF2-352 C
Adder
1.53411764705882361.304
274675JOLIET 29;7U
Adder
91.0294117647058877.375
943121AE2-341 C
Adder
8.3105882352941187.064
274862TOP CROP ;2U
50/50
2.0392.039
939321AE1-163 C
Adder
4.5952941176470593.906
295111SUBLETTE E
Adder
2.2317647058823531.897
274860EASYR;U2 E
Adder
10.7905882352941189.172
927209AC1-214 E2
Adder
2.92941176470588262.49
946322AF1-296 E
Adder
15.54588235294117713.214
276640AC1-204 GEN1
50/50
17.28517.285
959351AF2-226 C
50/50
7.1367.136
958491AF2-143 C
Adder
8.4411764705882367.175
933912AD1-013 E
Adder
2.40470588235294122.044
946152AF1-280 E
Adder
20.51882352941176517.441
293771O-035 E
Adder
6.177647058823535.251
293716O-029 E
Adder
4.8658823529411774.136
939742AE1-205 E
Adder
9.247.854
965931AG1-462 C
Adder
15.10352941176470612.838
959352AF2-226 E
50/50
10.70410.704
934101AD2-000 1
Adder
5.8152941176470594.943
958492AF2-143 E
Adder
5.6270588235294134.783
942421AE2-255 C
Adder
4.0847058823529413.472
290108LEEDK;1U E
Adder
19.07882352941176416.217
916221Z1-073 E
Adder
6.0411764705882355.135
957472AF2-041 E
Adder
9.4117647058823538
959092AF2-200 E
Adder
8.3658823529411767.111
926821AC1-168 C
Adder
0.8317647058823530.707
938862AE1-114 E
Adder
11.94117647058823610.15
959611AF2-252 C
Adder
1.53411764705882361.304
966441AG1-513 C
Adder
0.396470588235294130.337
959081AF2-199 C
Adder
6.2741176470588245.333
937411AD2-194 2
50/50
1.8341.834
938852AE1-113 E
Adder
38.2329411764705932.498
962012AG1-044 E
Adder
0.056470588235294120.048
925582AC1-033 E
Adder
8.8105882352941187.489
924049AB2-047 E2
Adder
8.7294117647058837.42
959342AF2-225 E
Adder
6.9294117647058825.89
916212CRESCENT ;1U
Adder
4.343.689
294410BSHIL;2U E
Adder
8.0376470588235296.832
917502Z2-087 E
Adder
13.85882352941176311.78
942111AE2-223 C
Adder
1.55294117647058831.32
939741AE1-205 C
Adder
6.6905882352941185.687
960612AF2-352 E
Adder
2.30117647058823541.956
966822AG1-553 E
Adder
25.66705882352941321.817
293645O22 E2
50/50
46.95446.954
960282AF2-319 E
50/50
10.70410.704
293715O-029 E
Adder
8.8741176470588247.543
276626AG1-044 E
Adder
0.067058823529411770.057
276170Z1-108 E
Adder
2.58588235294117652.198
920272AA2-123 E
Adder
2.53411764705882362.154
991182J1586 G
External Queue
-35.323299407958984-35.323299407958984
990552J1334 G
External Queue
-25.95514488220215-25.95514488220215
990557J1335 G
External Queue
-25.95514488220215-25.95514488220215
990562J1336 G
External Queue
-25.95514488220215-25.95514488220215
990577J1339
External Queue
-28.660625457763672-28.660625457763672
990497J1323
External Queue
-1.8008151054382324-1.8008151054382324
990547J1333 G
External Queue
-25.95514488220215-25.95514488220215
990582J1340
External Queue
-28.660625457763672-28.660625457763672
990662J1358
External Queue
-13.962589263916016-13.962589263916016
990647J1355
External Queue
-11.565272331237793-11.565272331237793
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.2990.299
TVALTFEXP_TVA->PJM
CLTF
1.831.83
O66PJM->LTFIMP_O-066
CMTX_NF
8.3278.327
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.48876.488
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.95815.958
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.3060.306
MECLTFEXP_MEC->PJM
CLTF
12.68312.683
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.8420.842
LAGNLTFEXP_LAGN->PJM
CLTF
3.9933.993
NYPJM->LTFIMP_NY
CLTF
0.7040.704
WECLTFEXP_WEC->PJM
CLTF
3.6463.646
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1710.171
G-007PJM->LTFIMP_G-007
CMTX_NF
1.2971.297
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0650.065
SIGELTFEXP_SIGE->PJM
CLTF
0.0390.039

Details for POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AMIL/CE
Facility Description:
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:156.02 %
Rating:1489.0 MVA
Rating Type:B
MVA to Mitigate:2323.19
MW Contribution:36.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
293644O22 E1
50/50
84.98884.988
960281AF2-319 C
50/50
14.79314.793
942651AE2-281 C
50/50
5.1775.177
942652AE2-281 E
50/50
31.80431.804
938851AE1-113 C
50/50
29.50729.507
274677POWERTON ;5U
50/50
92.60792.607
274678POWERTON ;6U
50/50
92.60792.607
274861TOP CROP ;1U
50/50
2.2172.217
936292AD2-038 E
50/50
91.41991.419
290021O50 E
50/50
71.53371.533
958481AF2-142 C
50/50
66.5766.57
939322AE1-163 E
50/50
222.631222.631
942422AE2-255 E
50/50
33.53133.531
274879MINONK ;1U
50/50
2.9122.912
274862TOP CROP ;2U
50/50
4.2284.228
939321AE1-163 C
50/50
36.24236.242
959351AF2-226 C
50/50
14.79314.793
958491AF2-143 C
50/50
66.56766.567
959352AF2-226 E
50/50
22.1922.19
958492AF2-143 E
50/50
44.37844.378
942421AE2-255 C
50/50
11.17711.177
958482AF2-142 E
50/50
44.3844.38
270839OTTER CRK; R
50/50
2.3482.348
938852AE1-113 E
50/50
104.617104.617
293645O22 E2
50/50
97.3497.34
960282AF2-319 E
50/50
22.1922.19
918052AA1-018 E OP
50/50
96.52796.527
936291AD2-038 C
50/50
2.972.97
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.9210.921
O66PJM->LTFIMP_O-066
CMTX_NF
5.7525.752
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.650.65
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0762.076
NYPJM->LTFIMP_NY
CLTF
0.4640.464
WECLTFEXP_WEC->PJM
CLTF
0.0530.053
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
5.1025.102
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.7360.736
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
4.1414.141
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8980.898
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.4630.463
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
8.1648.164
MDUPJM->LTFIMP_MDU
CLTF
0.3110.311

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.43 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1226.4
MW Contribution:5.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274814UNIV PK N;0U
50/50
1.9011.901
274807UNIV PK N;3U
50/50
1.9251.925
274816UNIV PK N;YU
50/50
1.9251.925
958011AF2-095 C
Adder
9.6458823529411778.199
933411AC2-154 C
Adder
2.1211764705882351.803
274687WILL CNTY;4U
Adder
56.08235294117647447.67
966091AG1-478 C
Adder
1.76941176470588251.504
966441AG1-513 C
Adder
0.434117647058823550.369
959081AF2-199 C
Adder
6.0258823529411775.122
916212CRESCENT ;1U
Adder
4.0658823529411773.456
294410BSHIL;2U E
Adder
7.2082352941176476.127
961501AF2-441 C
Adder
7.2070588235294136.126
293519PILOT HIL;1E
Adder
15.63058823529411813.286
939351AE1-166 C
Adder
8.555294117647067.272
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
293061N-015 E
Adder
13.20352941176470711.223
943121AE2-341 C
Adder
10.8588235294117659.23
939321AE1-163 C
Adder
5.3388235294117654.538
295111SUBLETTE E
Adder
2.3082352941176471.962
274860EASYR;U2 E
Adder
10.1270588235294138.608
927209AC1-214 E2
Adder
2.7435294117647062.332
946322AF1-296 E
Adder
5.1964705882352944.417
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
275149KELLYCK ;1E
Adder
15.63058823529411813.286
934722AD1-100 E
Adder
76.7823529411764765.265
960751AF2-366 C
Adder
5.9247058823529415.036
942422AE2-255 E
Adder
7.6658823529411776.516
960582AF2-349 E
Adder
30.726.095
937312AD2-172 E
Adder
2.8647058823529412.435
274859EASYR;U1 E
Adder
10.1270588235294138.608
274815UNIV PK N;XU
50/50
1.9131.913
958012AF2-095 E
Adder
6.4305882352941185.466
934111AD2-000 2
Adder
5.0882352941176484.325
966442AG1-513 E
Adder
0.65058823529411770.553
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
290051GSG-6; E
Adder
8.8682352941176487.538
959082AF2-199 E
Adder
3.01294117647058852.561
958912AF2-182 E
Adder
28.79647058823529424.477
294401BSHIL;1U E
Adder
7.2082352941176476.127
966092AG1-478 E
Adder
0.44470588235294120.378
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
938851AE1-113 C
Adder
6.7458823529411775.734
272363ESS H440 ; R
Adder
2.22941176470588241.895
959091AF2-200 C
Adder
12.05294117647058810.245
940502AE2-035 E
Adder
2.8647058823529412.435
293644O22 E1
Adder
11.6458823529411759.899
960281AF2-319 C
Adder
2.0270588235294121.723
960752AF2-366 E
Adder
3.94941176470588263.357
957471AF2-041 C
Adder
18.07882352941176815.367
294763P-046 E
Adder
7.9611764705882366.767
938861AE1-114 C
Adder
3.3164705882352942.819
274813UNIV PK N;9U
50/50
1.9091.909
274811UNIV PK N;7U
50/50
1.9251.925
941551AE2-152 C
Adder
9.8717647058823528.391
274676JOLIET 29;8U
Adder
62.29647058823529452.952
958481AF2-142 C
Adder
10.2776470588235318.736
957332AF2-027 E
Adder
3.1823529411764712.705
274891CAYUG;2U E
Adder
11.4552941176470599.737
926822AC1-168 E
Adder
6.4588235294117655.49
910542X3-005 E
Adder
0.53764705882352950.457
939352AE1-166 E
Adder
7.897647058823536.713
294392P-010 E
Adder
16.76941176470588214.254
959352AF2-226 E
Adder
3.0411764705882352.585
934101AD2-000 1
Adder
4.91411764705882354.177
958492AF2-143 E
Adder
6.537647058823535.557
942421AE2-255 C
Adder
2.5552941176470592.172
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
957472AF2-041 E
Adder
9.0400000000000017.684
959092AF2-200 E
Adder
8.0352941176470596.83
926821AC1-168 C
Adder
0.96235294117647050.818
938862AE1-114 E
Adder
11.315294117647069.618
274805UNIV PK N;1U
50/50
1.9131.913
943592AF1-030 E
Adder
3.5729411764705883.037
943591AF1-030 C
Adder
7.2211764705882366.138
936292AD2-038 E
Adder
13.46705882352941211.447
290021O50 E
Adder
16.3552941176470613.902
937002AD2-134 E
Adder
8.5752941176470587.289
957331AF2-027 C
Adder
2.1211764705882351.803
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
295109WESTBROOK E
Adder
4.7482352941176474.036
939061AE1-134 2
Adder
1.15294117647058810.98
936372AD2-047 E
Adder
18.53411764705882415.754
276591L-013 2
Adder
3.11882352941176462.651
962781AG1-127 C
Adder
5.94117647058823555.05
933911AD1-013 C
Adder
1.56117647058823541.327
274810UNIV PK N;6U
50/50
1.9171.917
274812UNIV PK N;8U
50/50
1.9091.909
961502AF2-441 E
Adder
10.8105882352941189.189
943122AE2-341 E
Adder
5.3317647058823534.532
939322AE1-163 E
Adder
32.7952941176470627.876
927208AC1-214 E1
Adder
2.7435294117647062.332
293516O-009 E
Adder
15.8423529411764713.466
293717O-029 E
Adder
4.1282352941176473.509
936371AD2-047 C
Adder
3.7964705882352943.227
936461AD2-060 C
Adder
2.2329411764705881.898
933412AC2-154 E
Adder
3.46117647058823552.942
962782AG1-127 E
Adder
3.9541176470588243.361
946671AF1-331 C
Adder
2.0282352941176471.724
274808UNIV PK N;4U
50/50
1.9171.917
959351AF2-226 C
Adder
2.0270588235294121.723
958491AF2-143 C
Adder
9.8058823529411778.335
933912AD1-013 E
Adder
2.49411764705882362.12
946152AF1-280 E
Adder
19.1976470588235316.318
293771O-035 E
Adder
5.7870588235294124.919
293716O-029 E
Adder
4.4917647058823533.818
941552AE2-152 E
Adder
6.5811764705882365.594
958482AF2-142 E
Adder
6.8517647058823535.824
938852AE1-113 E
Adder
23.91882352941176420.331
274890CAYUG;1U E
Adder
11.4552941176470599.737
962012AG1-044 E
Adder
0.0529411764705882350.045
925582AC1-033 E
Adder
7.9023529411764716.717
293645O22 E2
Adder
13.33882352941176411.338
960282AF2-319 E
Adder
3.0411764705882352.585
918052AA1-018 E OP
Adder
14.9023529411764712.667
293715O-029 E
Adder
8.1929411764705896.964
920272AA2-123 E
Adder
2.4364705882352942.071
276626AG1-044 E
Adder
0.062352941176470590.053
276675AE2-062 E
Adder
0.135294117647058840.115
276170Z1-108 E
Adder
2.48588235294117642.113
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
NYPJM->LTFIMP_NY
CLTF
0.9330.933
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.43 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1226.4
MW Contribution:5.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274814UNIV PK N;0U
50/50
1.9011.901
274807UNIV PK N;3U
50/50
1.9251.925
274816UNIV PK N;YU
50/50
1.9251.925
958011AF2-095 C
Adder
9.6458823529411778.199
933411AC2-154 C
Adder
2.1211764705882351.803
274687WILL CNTY;4U
Adder
56.08235294117647447.67
966091AG1-478 C
Adder
1.76941176470588251.504
966441AG1-513 C
Adder
0.434117647058823550.369
959081AF2-199 C
Adder
6.0258823529411775.122
916212CRESCENT ;1U
Adder
4.0658823529411773.456
294410BSHIL;2U E
Adder
7.2082352941176476.127
961501AF2-441 C
Adder
7.2070588235294136.126
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
275149KELLYCK ;1E
Adder
15.63058823529411813.286
934722AD1-100 E
Adder
76.7823529411764765.265
960751AF2-366 C
Adder
5.9247058823529415.036
942422AE2-255 E
Adder
7.6658823529411776.516
960582AF2-349 E
Adder
30.726.095
937312AD2-172 E
Adder
2.8647058823529412.435
274859EASYR;U1 E
Adder
10.1270588235294138.608
293519PILOT HIL;1E
Adder
15.63058823529411813.286
939351AE1-166 C
Adder
8.555294117647067.272
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
293061N-015 E
Adder
13.20352941176470711.223
943121AE2-341 C
Adder
10.8588235294117659.23
939321AE1-163 C
Adder
5.3388235294117654.538
295111SUBLETTE E
Adder
2.3082352941176471.962
274860EASYR;U2 E
Adder
10.1270588235294138.608
927209AC1-214 E2
Adder
2.7435294117647062.332
946322AF1-296 E
Adder
5.1964705882352944.417
274815UNIV PK N;XU
50/50
1.9131.913
958012AF2-095 E
Adder
6.4305882352941185.466
966092AG1-478 E
Adder
0.44470588235294120.378
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
938851AE1-113 C
Adder
6.7458823529411775.734
272363ESS H440 ; R
Adder
2.22941176470588241.895
959091AF2-200 C
Adder
12.05294117647058810.245
940502AE2-035 E
Adder
2.8647058823529412.435
293644O22 E1
Adder
11.6458823529411759.899
960281AF2-319 C
Adder
2.0270588235294121.723
960752AF2-366 E
Adder
3.94941176470588263.357
957471AF2-041 C
Adder
18.07882352941176815.367
294763P-046 E
Adder
7.9611764705882366.767
938861AE1-114 C
Adder
3.3164705882352942.819
274813UNIV PK N;9U
50/50
1.9091.909
274811UNIV PK N;7U
50/50
1.9251.925
941551AE2-152 C
Adder
9.8717647058823528.391
274676JOLIET 29;8U
Adder
62.29647058823529452.952
958481AF2-142 C
Adder
10.2776470588235318.736
957332AF2-027 E
Adder
3.1823529411764712.705
274891CAYUG;2U E
Adder
11.4552941176470599.737
926822AC1-168 E
Adder
6.4588235294117655.49
910542X3-005 E
Adder
0.53764705882352950.457
939352AE1-166 E
Adder
7.897647058823536.713
294392P-010 E
Adder
16.76941176470588214.254
959352AF2-226 E
Adder
3.0411764705882352.585
934101AD2-000 1
Adder
4.91411764705882354.177
958492AF2-143 E
Adder
6.537647058823535.557
942421AE2-255 C
Adder
2.5552941176470592.172
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
957472AF2-041 E
Adder
9.0400000000000017.684
959092AF2-200 E
Adder
8.0352941176470596.83
926821AC1-168 C
Adder
0.96235294117647050.818
938862AE1-114 E
Adder
11.315294117647069.618
274805UNIV PK N;1U
50/50
1.9131.913
957331AF2-027 C
Adder
2.1211764705882351.803
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
295109WESTBROOK E
Adder
4.7482352941176474.036
939061AE1-134 2
Adder
1.15294117647058810.98
934111AD2-000 2
Adder
5.0882352941176484.325
966442AG1-513 E
Adder
0.65058823529411770.553
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
290051GSG-6; E
Adder
8.8682352941176487.538
959082AF2-199 E
Adder
3.01294117647058852.561
958912AF2-182 E
Adder
28.79647058823529424.477
294401BSHIL;1U E
Adder
7.2082352941176476.127
936372AD2-047 E
Adder
18.53411764705882415.754
276591L-013 2
Adder
3.11882352941176462.651
962781AG1-127 C
Adder
5.94117647058823555.05
933911AD1-013 C
Adder
1.56117647058823541.327
943592AF1-030 E
Adder
3.5729411764705883.037
943591AF1-030 C
Adder
7.2211764705882366.138
936292AD2-038 E
Adder
13.46705882352941211.447
290021O50 E
Adder
16.3552941176470613.902
937002AD2-134 E
Adder
8.5752941176470587.289
961502AF2-441 E
Adder
10.8105882352941189.189
943122AE2-341 E
Adder
5.3317647058823534.532
939322AE1-163 E
Adder
32.7952941176470627.876
927208AC1-214 E1
Adder
2.7435294117647062.332
293516O-009 E
Adder
15.8423529411764713.466
293717O-029 E
Adder
4.1282352941176473.509
936371AD2-047 C
Adder
3.7964705882352943.227
936461AD2-060 C
Adder
2.2329411764705881.898
933412AC2-154 E
Adder
3.46117647058823552.942
962782AG1-127 E
Adder
3.9541176470588243.361
946671AF1-331 C
Adder
2.0282352941176471.724
274808UNIV PK N;4U
50/50
1.9171.917
959351AF2-226 C
Adder
2.0270588235294121.723
958491AF2-143 C
Adder
9.8058823529411778.335
933912AD1-013 E
Adder
2.49411764705882362.12
946152AF1-280 E
Adder
19.1976470588235316.318
293771O-035 E
Adder
5.7870588235294124.919
293716O-029 E
Adder
4.4917647058823533.818
274810UNIV PK N;6U
50/50
1.9171.917
274812UNIV PK N;8U
50/50
1.9091.909
941552AE2-152 E
Adder
6.5811764705882365.594
958482AF2-142 E
Adder
6.8517647058823535.824
938852AE1-113 E
Adder
23.91882352941176420.331
274890CAYUG;1U E
Adder
11.4552941176470599.737
962012AG1-044 E
Adder
0.0529411764705882350.045
925582AC1-033 E
Adder
7.9023529411764716.717
293645O22 E2
Adder
13.33882352941176411.338
960282AF2-319 E
Adder
3.0411764705882352.585
918052AA1-018 E OP
Adder
14.9023529411764712.667
293715O-029 E
Adder
8.1929411764705896.964
920272AA2-123 E
Adder
2.4364705882352942.071
276626AG1-044 E
Adder
0.062352941176470590.053
276675AE2-062 E
Adder
0.135294117647058840.115
276170Z1-108 E
Adder
2.48588235294117642.113
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
NYPJM->LTFIMP_NY
CLTF
0.9330.933
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.41 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1226.15
MW Contribution:5.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274814UNIV PK N;0U
50/50
1.8911.891
274807UNIV PK N;3U
50/50
1.9151.915
274816UNIV PK N;YU
50/50
1.9151.915
958011AF2-095 C
Adder
9.557647058823538.124
933411AC2-154 C
Adder
2.10235294117647081.787
274687WILL CNTY;4U
Adder
55.58000000000000547.243
966091AG1-478 C
Adder
1.7552941176470591.492
966441AG1-513 C
Adder
0.430588235294117660.366
959081AF2-199 C
Adder
5.9858823529411775.088
916212CRESCENT ;1U
Adder
4.0470588235294123.44
294410BSHIL;2U E
Adder
7.17647058823529356.1
961501AF2-441 C
Adder
7.1070588235294126.041
293519PILOT HIL;1E
Adder
15.48823529411764713.165
939351AE1-166 C
Adder
8.4870588235294137.214
274675JOLIET 29;7U
Adder
61.79058823529411652.522
274674JOLIET 9 ;6U
Adder
31.0329411764705926.378
293061N-015 E
Adder
13.10117647058823411.136
943121AE2-341 C
Adder
10.7729411764705899.157
939321AE1-163 C
Adder
5.302352941176474.507
295111SUBLETTE E
Adder
2.29294117647058831.949
274860EASYR;U2 E
Adder
10.0658823529411758.556
927209AC1-214 E2
Adder
2.7317647058823532.322
946322AF1-296 E
Adder
5.1729411764705894.397
960591AF2-350 C
Adder
6.637647058823535.642
960592AF2-350 E
Adder
4.4247058823529413.761
275149KELLYCK ;1E
Adder
15.48823529411764713.165
934722AD1-100 E
Adder
76.1647058823529364.74
960751AF2-366 C
Adder
5.8811764705882354.999
942422AE2-255 E
Adder
7.61411764705882456.472
960582AF2-349 E
Adder
30.4847058823529425.912
937312AD2-172 E
Adder
2.84588235294117682.419
274859EASYR;U1 E
Adder
10.0658823529411758.556
293644O22 E1
Adder
11.5517647058823549.819
274813UNIV PK N;9U
50/50
1.8991.899
274811UNIV PK N;7U
50/50
1.9151.915
941551AE2-152 C
Adder
9.7929411764705888.324
274676JOLIET 29;8U
Adder
61.7682352941176552.503
958481AF2-142 C
Adder
10.2035294117647068.673
957332AF2-027 E
Adder
3.15764705882352952.684
274891CAYUG;2U E
Adder
11.395294117647069.686
926822AC1-168 E
Adder
6.4258823529411765.462
910542X3-005 E
Adder
0.53058823529411770.451
939352AE1-166 E
Adder
7.8341176470588236.659
294392P-010 E
Adder
16.63882352941176614.143
959352AF2-226 E
Adder
3.01647058823529422.564
934101AD2-000 1
Adder
4.8788235294117654.147
958492AF2-143 E
Adder
6.4929411764705885.519
942421AE2-255 C
Adder
2.53764705882352942.157
290108LEEDK;1U E
Adder
20.2152941176470617.183
916221Z1-073 E
Adder
6.2070588235294125.276
957472AF2-041 E
Adder
8.9788235294117647.632
959092AF2-200 E
Adder
7.98117647058823556.784
960281AF2-319 C
Adder
2.0105882352941181.709
960752AF2-366 E
Adder
3.92117647058823553.333
957471AF2-041 C
Adder
17.9576470588235315.264
294763P-046 E
Adder
7.9094117647058826.723
938861AE1-114 C
Adder
3.2964705882352942.802
957331AF2-027 C
Adder
2.1047058823529411.789
936511AD2-066 C
Adder
7.1305882352941186.061
936512AD2-066 E
Adder
4.7541176470588244.041
295109WESTBROOK E
Adder
4.7152941176470594.008
939061AE1-134 2
Adder
1.14705882352941170.975
966092AG1-478 E
Adder
0.44117647058823530.375
274682WAUKEGAN ;7U
Adder
34.8235294117647129.6
942651AE2-281 C
Adder
0.75764705882352950.644
942652AE2-281 E
Adder
4.6529411764705893.955
962691AG1-118 C
Adder
18.6752941176470615.874
962692AG1-118 E
Adder
12.45058823529411810.583
938851AE1-113 C
Adder
6.75.695
272363ESS H440 ; R
Adder
2.21411764705882331.882
959091AF2-200 C
Adder
11.97176470588235410.176
940502AE2-035 E
Adder
2.84588235294117682.419
274815UNIV PK N;XU
50/50
1.9031.903
958012AF2-095 E
Adder
6.3717647058823535.416
934111AD2-000 2
Adder
5.0470588235294124.29
966442AG1-513 E
Adder
0.64470588235294120.548
274683WAUKEGAN ;8U
Adder
37.5458823529411831.914
290051GSG-6; E
Adder
8.8082352941176477.487
959082AF2-199 E
Adder
2.99294117647058842.544
958912AF2-182 E
Adder
28.6258823529411824.332
294401BSHIL;1U E
Adder
7.17647058823529356.1
936372AD2-047 E
Adder
18.36705882352941215.612
276591L-013 2
Adder
3.09411764705882362.63
962781AG1-127 C
Adder
5.8976470588235295.013
933911AD1-013 C
Adder
1.55058823529411781.318
274805UNIV PK N;1U
50/50
1.9031.903
943592AF1-030 E
Adder
3.54470588235294143.013
943591AF1-030 C
Adder
7.1635294117647066.089
936292AD2-038 E
Adder
13.37529411764705911.369
290021O50 E
Adder
16.24352941176470813.807
937002AD2-134 E
Adder
8.5164705882352937.239
961502AF2-441 E
Adder
10.6611764705882349.062
943122AE2-341 E
Adder
5.2905882352941184.497
939322AE1-163 E
Adder
32.5729411764705927.687
927208AC1-214 E1
Adder
2.7317647058823532.322
293516O-009 E
Adder
15.7576470588235313.394
293717O-029 E
Adder
4.1070588235294123.491
926821AC1-168 C
Adder
0.95764705882352940.814
938862AE1-114 E
Adder
11.244705882352949.558
936371AD2-047 C
Adder
3.76235294117647053.198
936461AD2-060 C
Adder
2.2129411764705881.881
933412AC2-154 E
Adder
3.42941176470588262.915
962782AG1-127 E
Adder
3.92470588235294133.336
946671AF1-331 C
Adder
2.01411764705882361.712
274808UNIV PK N;4U
50/50
1.9071.907
959351AF2-226 C
Adder
2.0105882352941181.709
958491AF2-143 C
Adder
9.748.279
933912AD1-013 E
Adder
2.47764705882352932.106
946152AF1-280 E
Adder
19.08352941176470816.221
293771O-035 E
Adder
5.7611764705882364.897
293716O-029 E
Adder
4.46823529411764753.798
274810UNIV PK N;6U
50/50
1.9071.907
274812UNIV PK N;8U
50/50
1.8991.899
941552AE2-152 E
Adder
6.5282352941176485.549
958482AF2-142 E
Adder
6.8023529411764715.782
938852AE1-113 E
Adder
23.75647058823529520.193
274890CAYUG;1U E
Adder
11.395294117647069.686
962012AG1-044 E
Adder
0.0529411764705882350.045
925582AC1-033 E
Adder
7.8670588235294126.687
293645O22 E2
Adder
13.2305882352941211.246
960282AF2-319 E
Adder
3.01647058823529422.564
918052AA1-018 E OP
Adder
14.7952941176470612.576
293715O-029 E
Adder
8.1494117647058816.927
920272AA2-123 E
Adder
2.4188235294117652.056
276626AG1-044 E
Adder
0.061176470588235290.052
276675AE2-062 E
Adder
0.134117647058823540.114
276170Z1-108 E
Adder
2.4670588235294122.097
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6070.607
TVALTFEXP_TVA->PJM
CLTF
1.1671.167
O66PJM->LTFIMP_O-066
CMTX_NF
11.09411.094
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.23368.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.47412.474
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.4090.409
MECLTFEXP_MEC->PJM
CLTF
10.92410.924
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.1721.172
LAGNLTFEXP_LAGN->PJM
CLTF
2.992.99
NYPJM->LTFIMP_NY
CLTF
0.9310.931
WECLTFEXP_WEC->PJM
CLTF
3.2883.288
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4090.409
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7291.729
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.210.21
SIGELTFEXP_SIGE->PJM
CLTF
0.0150.015

Details for WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT5-6___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.85 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1701.87
MW Contribution:6.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274788SE CHICAG;5U
Adder
4.5223529411764713.844
274798UNIV PARK;1U
50/50
1.2121.212
958011AF2-095 C
50/50
12.8912.89
933411AC2-154 C
50/50
2.8352.835
274687WILL CNTY;4U
Adder
70.7847058823529460.167
966091AG1-478 C
50/50
2.242.24
966441AG1-513 C
Adder
0.540.459
959081AF2-199 C
Adder
7.5447058823529416.413
961501AF2-441 C
Adder
10.5505882352941188.968
957371AF2-031 C
Adder
0.98823529411764710.84
274770LINCOLN ;1U
50/50
3.0623.062
274773LINCOLN ;4U
50/50
3.0623.062
274772LINCOLN ;3U
50/50
3.0623.062
274771LINCOLN ;2U
50/50
3.0623.062
960591AF2-350 C
50/50
8.9528.952
960592AF2-350 E
50/50
5.9685.968
275149KELLYCK ;1E
50/50
20.88720.887
274800UNIV PARK;3U
50/50
1.2031.203
941551AE2-152 C
50/50
15.22915.229
274676JOLIET 29;8U
Adder
76.0835294117647264.671
274847GR RIDGE ;BU
50/50
0.6370.637
958481AF2-142 C
Adder
11.90941176470588110.123
957332AF2-027 E
Adder
3.94352941176470573.352
274891CAYUG;2U E
50/50
16.86716.867
957372AF2-031 E
Adder
1.48235294117647071.26
274774LINCOLN ;5U
50/50
3.0623.062
293644O22 E1
Adder
15.21999999999999912.937
960281AF2-319 C
Adder
2.64941176470588242.252
960752AF2-366 E
Adder
4.9364705882352944.196
957471AF2-041 C
Adder
22.63411764705882619.239
294763P-046 E
Adder
9.9564705882352938.463
274871GR RIDGE ;2U
50/50
0.2370.237
957331AF2-027 C
Adder
2.62941176470588232.235
936511AD2-066 C
Adder
8.977647058823537.631
936512AD2-066 E
Adder
5.9847058823529415.087
274864CAYUGA RI;2U
50/50
0.5150.515
295109WESTBROOK E
Adder
5.9435294117647065.052
274790SE CHICAG;7U
Adder
1.68941176470588241.436
966092AG1-478 E
50/50
0.5630.563
274682WAUKEGAN ;7U
Adder
43.47411764705882636.953
942651AE2-281 C
Adder
0.90235294117647060.767
942652AE2-281 E
Adder
5.5435294117647054.712
962691AG1-118 C
Adder
23.50941176470588419.983
962692AG1-118 E
Adder
15.67294117647058713.322
938851AE1-113 C
Adder
8.4129411764705877.151
272363ESS H440 ; R
Adder
2.7917647058823532.373
959091AF2-200 C
Adder
15.08941176470588312.826
940502AE2-035 E
Adder
3.58235294117647073.045
958012AF2-095 E
50/50
8.5938.593
274887PILOT HIL;1U
50/50
0.850.85
934111AD2-000 2
Adder
6.317647058823535.37
966442AG1-513 E
Adder
0.80941176470588230.688
274683WAUKEGAN ;8U
Adder
46.8729411764705939.842
290051GSG-6; E
Adder
11.102352941176479.437
959082AF2-199 E
Adder
3.77294117647058823.207
274776LINCOLN ;7U
50/50
3.0623.062
936372AD2-047 E
50/50
24.76624.766
274654BRAIDWOOD;1U
50/50
29.85229.852
276591L-013 2
Adder
3.8835294117647063.301
962781AG1-127 C
Adder
7.4258823529411776.312
933911AD1-013 C
Adder
1.95411764705882351.661
274888KELLY CRK;1U
50/50
0.850.85
274660LASCO STA;1U
50/50
27.28127.281
943592AF1-030 E
Adder
4.4705882352941183.8
943591AF1-030 C
Adder
9.0364705882352957.681
936292AD2-038 E
Adder
15.93411764705882513.544
290021O50 E
Adder
20.39647058823529617.337
937002AD2-134 E
Adder
10.7341176470588249.124
934722AD1-100 E
50/50
118.444118.444
934721AD1-100 C
50/50
3.8843.884
960751AF2-366 C
Adder
7.4047058823529416.294
942422AE2-255 E
Adder
9.5611764705882368.127
960582AF2-349 E
Adder
38.2764705882352932.535
937312AD2-172 E
Adder
3.58235294117647073.045
961502AF2-441 E
Adder
15.82588235294117713.452
274661LASCO STA;2U
50/50
27.3727.37
943122AE2-341 E
Adder
6.6729411764705885.672
939322AE1-163 E
Adder
38.803529411764732.983
274863CAYUGA RI;1U
50/50
0.5150.515
910542X3-005 E
Adder
0.76941176470588240.654
939352AE1-166 E
50/50
12.18312.183
294392P-010 E
50/50
21.76221.762
959352AF2-226 E
Adder
3.9741176470588243.378
934101AD2-000 1
Adder
6.1705882352941185.245
958492AF2-143 E
Adder
7.7352941176470596.575
942421AE2-255 C
Adder
3.18705882352941172.709
290108LEEDK;1U E
Adder
25.4658823529411821.646
916221Z1-073 E
Adder
7.82352941176470656.65
957472AF2-041 E
Adder
11.3176470588235289.62
959092AF2-200 E
Adder
10.068.551
274775LINCOLN ;6U
50/50
3.0623.062
274777LINCOLN ;8U
50/50
3.0623.062
936371AD2-047 C
50/50
5.0735.073
936461AD2-060 C
50/50
2.9842.984
933412AC2-154 E
50/50
4.6254.625
962782AG1-127 E
Adder
4.94117647058823554.2
946671AF1-331 C
Adder
2.53882352941176452.158
293519PILOT HIL;1E
50/50
20.88720.887
939351AE1-166 C
50/50
13.19813.198
274675JOLIET 29;7U
Adder
76.0835294117647264.671
274674JOLIET 9 ;6U
Adder
38.7023529411764732.897
293061N-015 E
50/50
17.13617.136
943121AE2-341 C
Adder
13.58823529411764911.55
939321AE1-163 C
Adder
6.3164705882352945.369
295111SUBLETTE E
Adder
2.88941176470588262.456
274655BRAIDWOOD;2U
50/50
29.08529.085
959351AF2-226 C
Adder
2.64941176470588242.252
958491AF2-143 C
Adder
11.6023529411764729.862
933912AD1-013 E
Adder
3.12235294117647082.654
941552AE2-152 E
50/50
10.15210.152
958482AF2-142 E
Adder
7.93999999999999956.749
938852AE1-113 E
Adder
29.82941176470588525.355
274890CAYUG;1U E
50/50
16.86716.867
293645O22 E2
Adder
17.43176470588235514.817
960282AF2-319 E
Adder
3.9741176470588243.378
918052AA1-018 E OP
Adder
17.26941176470588214.679
276675AE2-062 E
Adder
0.162352941176470620.138
276170Z1-108 E
Adder
3.0917647058823532.628
920272AA2-123 E
Adder
3.0352941176470592.58
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8740.874
TVALTFEXP_TVA->PJM
CLTF
1.4271.427
O66PJM->LTFIMP_O-066
CMTX_NF
14.71114.711
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.2195.21
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.37116.371
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6470.647
MECLTFEXP_MEC->PJM
CLTF
13.89713.897
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.8521.852
LAGNLTFEXP_LAGN->PJM
CLTF
3.7743.774
NYPJM->LTFIMP_NY
CLTF
1.2271.227
WECLTFEXP_WEC->PJM
CLTF
4.1174.117
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5980.598
G-007PJM->LTFIMP_G-007
CMTX_NF
2.2932.293
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3140.314
SIGELTFEXP_SIGE->PJM
CLTF
0.0210.021

Details for WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.88 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1746.33
MW Contribution:6.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274798UNIV PARK;1U
50/50
1.2441.244
958011AF2-095 C
50/50
13.22413.224
933411AC2-154 C
50/50
2.9082.908
274687WILL CNTY;4U
Adder
72.6647058823529561.765
966091AG1-478 C
50/50
2.2992.299
966441AG1-513 C
Adder
0.55411764705882350.471
959081AF2-199 C
Adder
7.74470588235294166.583
910542X3-005 E
Adder
0.79058823529411770.672
939352AE1-166 E
50/50
12.48912.489
294392P-010 E
50/50
22.32722.327
959352AF2-226 E
Adder
4.0788235294117653.467
934101AD2-000 1
Adder
6.3329411764705885.383
958492AF2-143 E
Adder
7.9435294117647066.752
942421AE2-255 C
Adder
3.2717647058823532.781
290108LEEDK;1U E
Adder
26.1422.219
916221Z1-073 E
Adder
8.0305882352941186.826
957472AF2-041 E
Adder
11.6164705882352959.874
959092AF2-200 E
Adder
10.3258823529411778.777
274790SE CHICAG;7U
Adder
1.73411764705882351.474
274791SE CHICAG;8U
Adder
4.6423529411764713.946
966092AG1-478 E
50/50
0.5780.578
274682WAUKEGAN ;7U
Adder
44.62823529411764437.934
942651AE2-281 C
Adder
0.92705882352941180.788
942652AE2-281 E
Adder
5.6929411764705894.839
962691AG1-118 C
Adder
24.13176470588235420.512
962692AG1-118 E
Adder
16.0882352941176513.675
938851AE1-113 C
Adder
8.6364705882352947.341
272363ESS H440 ; R
Adder
2.8647058823529412.435
959091AF2-200 C
Adder
15.48823529411764713.165
940502AE2-035 E
Adder
3.67764705882352953.126
961501AF2-441 C
Adder
10.8282352941176499.204
293519PILOT HIL;1E
50/50
21.42821.428
939351AE1-166 C
50/50
13.52913.529
274675JOLIET 29;7U
Adder
78.1152941176470566.398
274674JOLIET 9 ;6U
Adder
39.72588235294118433.767
293061N-015 E
50/50
17.5817.58
943121AE2-341 C
Adder
13.94823529411764811.856
939321AE1-163 C
Adder
6.4870588235294125.514
295111SUBLETTE E
Adder
2.96588235294117642.521
957371AF2-031 C
Adder
1.01411764705882360.862
274770LINCOLN ;1U
50/50
3.1623.162
274773LINCOLN ;4U
50/50
3.1623.162
274772LINCOLN ;3U
50/50
3.1623.162
274771LINCOLN ;2U
50/50
3.1623.162
960591AF2-350 C
50/50
9.1849.184
960592AF2-350 E
50/50
6.1226.122
275149KELLYCK ;1E
50/50
21.42821.428
934722AD1-100 E
50/50
121.416121.416
934721AD1-100 C
50/50
3.9823.982
960751AF2-366 C
Adder
7.6011764705882366.461
942422AE2-255 E
Adder
9.8141176470588248.342
960582AF2-349 E
Adder
39.29058823529411633.397
937312AD2-172 E
Adder
3.67764705882352953.126
958012AF2-095 E
50/50
8.8168.816
274887PILOT HIL;1U
50/50
0.8720.872
934111AD2-000 2
Adder
6.4847058823529415.512
966442AG1-513 E
Adder
0.8317647058823530.707
274683WAUKEGAN ;8U
Adder
48.1176470588235340.9
290051GSG-6; E
Adder
11.395294117647069.686
959082AF2-199 E
Adder
3.87176470588235283.291
274800UNIV PARK;3U
50/50
1.2351.235
941551AE2-152 C
50/50
15.61115.611
274676JOLIET 29;8U
Adder
78.1152941176470566.398
274847GR RIDGE ;BU
50/50
0.6540.654
958481AF2-142 C
Adder
12.23176470588235410.397
957332AF2-027 E
Adder
4.0482352941176473.441
274891CAYUG;2U E
50/50
17.29517.295
957372AF2-031 E
Adder
1.52117647058823541.293
274774LINCOLN ;5U
50/50
3.1623.162
293644O22 E1
Adder
15.62117647058823713.278
960281AF2-319 C
Adder
2.71882352941176462.311
960752AF2-366 E
Adder
5.0670588235294124.307
957471AF2-041 C
Adder
23.2329411764705919.748
294763P-046 E
Adder
10.2199999999999998.687
274871GR RIDGE ;2U
50/50
0.2430.243
957331AF2-027 C
Adder
2.69882352941176462.294
936511AD2-066 C
Adder
9.2141176470588247.832
936512AD2-066 E
Adder
6.1435294117647075.222
274864CAYUGA RI;2U
50/50
0.5280.528
295109WESTBROOK E
Adder
6.1011764705882365.186
274776LINCOLN ;7U
50/50
3.1623.162
936372AD2-047 E
50/50
25.40825.408
274654BRAIDWOOD;1U
50/50
30.61530.615
276591L-013 2
Adder
3.98705882352941153.389
962781AG1-127 C
Adder
7.6223529411764716.479
933911AD1-013 C
Adder
2.00588235294117641.705
274888KELLY CRK;1U
50/50
0.8720.872
274660LASCO STA;1U
50/50
27.98627.986
943592AF1-030 E
Adder
4.5894117647058823.901
943591AF1-030 C
Adder
9.2752941176470597.884
936292AD2-038 E
Adder
16.3623529411764713.908
290021O50 E
Adder
20.9376470588235317.797
937002AD2-134 E
Adder
11.0188235294117659.366
274775LINCOLN ;6U
50/50
3.1623.162
961502AF2-441 E
Adder
16.2423529411764713.806
274661LASCO STA;2U
50/50
28.07728.077
943122AE2-341 E
Adder
6.84941176470588255.822
941552AE2-152 E
50/50
10.40710.407
958482AF2-142 E
Adder
8.1541176470588246.931
938852AE1-113 E
Adder
30.62117647058823526.028
274890CAYUG;1U E
50/50
17.29517.295
939322AE1-163 E
Adder
39.8482352941176533.871
274863CAYUGA RI;1U
50/50
0.5280.528
274777LINCOLN ;8U
50/50
3.1623.162
936371AD2-047 C
50/50
5.2045.204
936461AD2-060 C
50/50
3.0613.061
933412AC2-154 E
50/50
4.7454.745
962782AG1-127 E
Adder
5.07294117647058854.312
946671AF1-331 C
Adder
2.60588235294117652.215
274655BRAIDWOOD;2U
50/50
29.82929.829
959351AF2-226 C
Adder
2.71882352941176462.311
958491AF2-143 C
Adder
11.91411764705882510.127
933912AD1-013 E
Adder
3.20470588235294152.724
293645O22 E2
Adder
17.89176470588235215.208
960282AF2-319 E
Adder
4.0788235294117653.467
918052AA1-018 E OP
Adder
17.73647058823529615.076
276170Z1-108 E
Adder
3.17411764705882372.698
920272AA2-123 E
Adder
3.11647058823529432.649
276675AE2-062 E
Adder
0.167058823529411760.142
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8980.898
TVALTFEXP_TVA->PJM
CLTF
1.4641.464
O66PJM->LTFIMP_O-066
CMTX_NF
15.10215.102
CBM West 1LTFEXP_CBM-W1->PJM
CBM
97.73297.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.79716.797
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6640.664
MECLTFEXP_MEC->PJM
CLTF
14.26314.263
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.9021.902
LAGNLTFEXP_LAGN->PJM
CLTF
3.8723.872
NYPJM->LTFIMP_NY
CLTF
1.2591.259
WECLTFEXP_WEC->PJM
CLTF
4.2274.227
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.6140.614
G-007PJM->LTFIMP_G-007
CMTX_NF
2.3542.354
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3230.323
SIGELTFEXP_SIGE->PJM
CLTF
0.0220.022

Details for WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_112-65-BT5-6___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.01 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1704.12
MW Contribution:6.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274788SE CHICAG;5U
Adder
4.5223529411764713.844
274798UNIV PARK;1U
50/50
1.2121.212
958011AF2-095 C
50/50
12.8912.89
933411AC2-154 C
50/50
2.8352.835
274687WILL CNTY;4U
Adder
70.7847058823529460.167
966091AG1-478 C
50/50
2.242.24
966441AG1-513 C
Adder
0.540.459
959081AF2-199 C
Adder
7.5447058823529416.413
961501AF2-441 C
Adder
10.5505882352941188.968
293519PILOT HIL;1E
50/50
20.88720.887
939351AE1-166 C
50/50
13.19813.198
274675JOLIET 29;7U
Adder
76.0835294117647264.671
274674JOLIET 9 ;6U
Adder
38.7023529411764732.897
293061N-015 E
50/50
17.13617.136
943121AE2-341 C
Adder
13.58823529411764911.55
939321AE1-163 C
Adder
6.3164705882352945.369
295111SUBLETTE E
Adder
2.88941176470588262.456
957371AF2-031 C
Adder
0.98823529411764710.84
274770LINCOLN ;1U
50/50
3.0623.062
274773LINCOLN ;4U
50/50
3.0623.062
274772LINCOLN ;3U
50/50
3.0623.062
274771LINCOLN ;2U
50/50
3.0623.062
960591AF2-350 C
50/50
8.9528.952
960592AF2-350 E
50/50
5.9685.968
275149KELLYCK ;1E
50/50
20.88720.887
934722AD1-100 E
50/50
118.444118.444
934721AD1-100 C
50/50
3.8843.884
960751AF2-366 C
Adder
7.4047058823529416.294
942422AE2-255 E
Adder
9.5611764705882368.127
960582AF2-349 E
Adder
38.2764705882352932.535
937312AD2-172 E
Adder
3.58235294117647073.045
274800UNIV PARK;3U
50/50
1.2031.203
941551AE2-152 C
50/50
15.22915.229
274676JOLIET 29;8U
Adder
76.0835294117647264.671
274847GR RIDGE ;BU
50/50
0.6370.637
958481AF2-142 C
Adder
11.90941176470588110.123
957332AF2-027 E
Adder
3.94352941176470573.352
274891CAYUG;2U E
50/50
16.86716.867
957372AF2-031 E
Adder
1.48235294117647071.26
274774LINCOLN ;5U
50/50
3.0623.062
293644O22 E1
Adder
15.21999999999999912.937
960281AF2-319 C
Adder
2.64941176470588242.252
960752AF2-366 E
Adder
4.9364705882352944.196
957471AF2-041 C
Adder
22.63411764705882619.239
294763P-046 E
Adder
9.9564705882352938.463
274871GR RIDGE ;2U
50/50
0.2370.237
957331AF2-027 C
Adder
2.62941176470588232.235
936511AD2-066 C
Adder
8.977647058823537.631
936512AD2-066 E
Adder
5.9847058823529415.087
274864CAYUGA RI;2U
50/50
0.5150.515
295109WESTBROOK E
Adder
5.9435294117647065.052
274790SE CHICAG;7U
Adder
1.68941176470588241.436
966092AG1-478 E
50/50
0.5630.563
274682WAUKEGAN ;7U
Adder
43.47411764705882636.953
942651AE2-281 C
Adder
0.90235294117647060.767
942652AE2-281 E
Adder
5.5435294117647054.712
962691AG1-118 C
Adder
23.50941176470588419.983
962692AG1-118 E
Adder
15.67294117647058713.322
938851AE1-113 C
Adder
8.4129411764705877.151
272363ESS H440 ; R
Adder
2.7917647058823532.373
959091AF2-200 C
Adder
15.08941176470588312.826
940502AE2-035 E
Adder
3.58235294117647073.045
958012AF2-095 E
50/50
8.5938.593
274887PILOT HIL;1U
50/50
0.850.85
934111AD2-000 2
Adder
6.317647058823535.37
966442AG1-513 E
Adder
0.80941176470588230.688
274683WAUKEGAN ;8U
Adder
46.8729411764705939.842
290051GSG-6; E
Adder
11.102352941176479.437
959082AF2-199 E
Adder
3.77294117647058823.207
274776LINCOLN ;7U
50/50
3.0623.062
936372AD2-047 E
50/50
24.76624.766
274654BRAIDWOOD;1U
50/50
29.85229.852
276591L-013 2
Adder
3.8835294117647063.301
962781AG1-127 C
Adder
7.4258823529411776.312
933911AD1-013 C
Adder
1.95411764705882351.661
274888KELLY CRK;1U
50/50
0.850.85
274660LASCO STA;1U
50/50
27.28127.281
943592AF1-030 E
Adder
4.4705882352941183.8
943591AF1-030 C
Adder
9.0364705882352957.681
936292AD2-038 E
Adder
15.93411764705882513.544
290021O50 E
Adder
20.39647058823529617.337
937002AD2-134 E
Adder
10.7341176470588249.124
961502AF2-441 E
Adder
15.82588235294117713.452
274661LASCO STA;2U
50/50
27.3727.37
943122AE2-341 E
Adder
6.6729411764705885.672
939322AE1-163 E
Adder
38.803529411764732.983
274863CAYUGA RI;1U
50/50
0.5150.515
910542X3-005 E
Adder
0.76941176470588240.654
939352AE1-166 E
50/50
12.18312.183
294392P-010 E
50/50
21.76221.762
959352AF2-226 E
Adder
3.9741176470588243.378
934101AD2-000 1
Adder
6.1705882352941185.245
958492AF2-143 E
Adder
7.7352941176470596.575
942421AE2-255 C
Adder
3.18705882352941172.709
290108LEEDK;1U E
Adder
25.4658823529411821.646
916221Z1-073 E
Adder
7.82352941176470656.65
957472AF2-041 E
Adder
11.3176470588235289.62
959092AF2-200 E
Adder
10.068.551
274775LINCOLN ;6U
50/50
3.0623.062
274777LINCOLN ;8U
50/50
3.0623.062
936371AD2-047 C
50/50
5.0735.073
936461AD2-060 C
50/50
2.9842.984
933412AC2-154 E
50/50
4.6254.625
962782AG1-127 E
Adder
4.94117647058823554.2
946671AF1-331 C
Adder
2.53882352941176452.158
274655BRAIDWOOD;2U
50/50
29.08529.085
959351AF2-226 C
Adder
2.64941176470588242.252
958491AF2-143 C
Adder
11.6023529411764729.862
933912AD1-013 E
Adder
3.12235294117647082.654
941552AE2-152 E
50/50
10.15210.152
958482AF2-142 E
Adder
7.93999999999999956.749
938852AE1-113 E
Adder
29.82941176470588525.355
274890CAYUG;1U E
50/50
16.86716.867
293645O22 E2
Adder
17.43176470588235514.817
960282AF2-319 E
Adder
3.9741176470588243.378
918052AA1-018 E OP
Adder
17.26941176470588214.679
920272AA2-123 E
Adder
3.0352941176470592.58
276675AE2-062 E
Adder
0.162352941176470620.138
276170Z1-108 E
Adder
3.0917647058823532.628
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8740.874
TVALTFEXP_TVA->PJM
CLTF
1.4271.427
O66PJM->LTFIMP_O-066
CMTX_NF
14.71114.711
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.2195.21
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.37116.371
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6470.647
MECLTFEXP_MEC->PJM
CLTF
13.89713.897
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.8521.852
LAGNLTFEXP_LAGN->PJM
CLTF
3.7743.774
NYPJM->LTFIMP_NY
CLTF
1.2271.227
WECLTFEXP_WEC->PJM
CLTF
4.1174.117
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5980.598
G-007PJM->LTFIMP_G-007
CMTX_NF
2.2932.293
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3140.314
SIGELTFEXP_SIGE->PJM
CLTF
0.0210.021

Details for WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_112-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.03 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1748.52
MW Contribution:6.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274798UNIV PARK;1U
50/50
1.2441.244
958011AF2-095 C
50/50
13.22413.224
933411AC2-154 C
50/50
2.9082.908
274687WILL CNTY;4U
Adder
72.6647058823529561.765
966091AG1-478 C
50/50
2.2992.299
966441AG1-513 C
Adder
0.55411764705882350.471
959081AF2-199 C
Adder
7.74470588235294166.583
910542X3-005 E
Adder
0.79058823529411770.672
939352AE1-166 E
50/50
12.48912.489
294392P-010 E
50/50
22.32722.327
959352AF2-226 E
Adder
4.0788235294117653.467
934101AD2-000 1
Adder
6.3329411764705885.383
958492AF2-143 E
Adder
7.9435294117647066.752
942421AE2-255 C
Adder
3.2717647058823532.781
290108LEEDK;1U E
Adder
26.1422.219
916221Z1-073 E
Adder
8.0305882352941186.826
957472AF2-041 E
Adder
11.6164705882352959.874
959092AF2-200 E
Adder
10.3258823529411778.777
274790SE CHICAG;7U
Adder
1.73411764705882351.474
274791SE CHICAG;8U
Adder
4.6423529411764713.946
966092AG1-478 E
50/50
0.5780.578
274682WAUKEGAN ;7U
Adder
44.62823529411764437.934
942651AE2-281 C
Adder
0.92705882352941180.788
942652AE2-281 E
Adder
5.6929411764705894.839
962691AG1-118 C
Adder
24.13176470588235420.512
962692AG1-118 E
Adder
16.0882352941176513.675
938851AE1-113 C
Adder
8.6364705882352947.341
272363ESS H440 ; R
Adder
2.8647058823529412.435
959091AF2-200 C
Adder
15.48823529411764713.165
940502AE2-035 E
Adder
3.67764705882352953.126
961501AF2-441 C
Adder
10.8282352941176499.204
293519PILOT HIL;1E
50/50
21.42821.428
939351AE1-166 C
50/50
13.52913.529
274675JOLIET 29;7U
Adder
78.1152941176470566.398
274674JOLIET 9 ;6U
Adder
39.72588235294118433.767
293061N-015 E
50/50
17.5817.58
943121AE2-341 C
Adder
13.94823529411764811.856
939321AE1-163 C
Adder
6.4870588235294125.514
295111SUBLETTE E
Adder
2.96588235294117642.521
957371AF2-031 C
Adder
1.01411764705882360.862
274770LINCOLN ;1U
50/50
3.1623.162
274773LINCOLN ;4U
50/50
3.1623.162
274772LINCOLN ;3U
50/50
3.1623.162
274771LINCOLN ;2U
50/50
3.1623.162
960591AF2-350 C
50/50
9.1849.184
960592AF2-350 E
50/50
6.1226.122
275149KELLYCK ;1E
50/50
21.42821.428
934722AD1-100 E
50/50
121.416121.416
934721AD1-100 C
50/50
3.9823.982
960751AF2-366 C
Adder
7.6011764705882366.461
942422AE2-255 E
Adder
9.8141176470588248.342
960582AF2-349 E
Adder
39.29058823529411633.397
937312AD2-172 E
Adder
3.67764705882352953.126
958012AF2-095 E
50/50
8.8168.816
274887PILOT HIL;1U
50/50
0.8720.872
934111AD2-000 2
Adder
6.4847058823529415.512
966442AG1-513 E
Adder
0.8317647058823530.707
274683WAUKEGAN ;8U
Adder
48.1176470588235340.9
290051GSG-6; E
Adder
11.395294117647069.686
959082AF2-199 E
Adder
3.87176470588235283.291
274800UNIV PARK;3U
50/50
1.2351.235
941551AE2-152 C
50/50
15.61115.611
274676JOLIET 29;8U
Adder
78.1152941176470566.398
274847GR RIDGE ;BU
50/50
0.6540.654
958481AF2-142 C
Adder
12.23176470588235410.397
957332AF2-027 E
Adder
4.0482352941176473.441
274891CAYUG;2U E
50/50
17.29517.295
957372AF2-031 E
Adder
1.52117647058823541.293
274774LINCOLN ;5U
50/50
3.1623.162
293644O22 E1
Adder
15.62117647058823713.278
960281AF2-319 C
Adder
2.71882352941176462.311
960752AF2-366 E
Adder
5.0670588235294124.307
957471AF2-041 C
Adder
23.2329411764705919.748
294763P-046 E
Adder
10.2199999999999998.687
274871GR RIDGE ;2U
50/50
0.2430.243
957331AF2-027 C
Adder
2.69882352941176462.294
936511AD2-066 C
Adder
9.2141176470588247.832
936512AD2-066 E
Adder
6.1435294117647075.222
274864CAYUGA RI;2U
50/50
0.5280.528
295109WESTBROOK E
Adder
6.1011764705882365.186
274776LINCOLN ;7U
50/50
3.1623.162
936372AD2-047 E
50/50
25.40825.408
274654BRAIDWOOD;1U
50/50
30.61530.615
276591L-013 2
Adder
3.98705882352941153.389
962781AG1-127 C
Adder
7.6223529411764716.479
933911AD1-013 C
Adder
2.00588235294117641.705
274888KELLY CRK;1U
50/50
0.8720.872
274660LASCO STA;1U
50/50
27.98627.986
943592AF1-030 E
Adder
4.5894117647058823.901
943591AF1-030 C
Adder
9.2752941176470597.884
936292AD2-038 E
Adder
16.3623529411764713.908
290021O50 E
Adder
20.9376470588235317.797
937002AD2-134 E
Adder
11.0188235294117659.366
274775LINCOLN ;6U
50/50
3.1623.162
274777LINCOLN ;8U
50/50
3.1623.162
936371AD2-047 C
50/50
5.2045.204
936461AD2-060 C
50/50
3.0613.061
933412AC2-154 E
50/50
4.7454.745
962782AG1-127 E
Adder
5.07294117647058854.312
946671AF1-331 C
Adder
2.60588235294117652.215
961502AF2-441 E
Adder
16.2423529411764713.806
274661LASCO STA;2U
50/50
28.07728.077
943122AE2-341 E
Adder
6.84941176470588255.822
939322AE1-163 E
Adder
39.8482352941176533.871
274863CAYUGA RI;1U
50/50
0.5280.528
941552AE2-152 E
50/50
10.40710.407
958482AF2-142 E
Adder
8.1541176470588246.931
938852AE1-113 E
Adder
30.62117647058823526.028
274890CAYUG;1U E
50/50
17.29517.295
274655BRAIDWOOD;2U
50/50
29.82929.829
959351AF2-226 C
Adder
2.71882352941176462.311
958491AF2-143 C
Adder
11.91411764705882510.127
933912AD1-013 E
Adder
3.20470588235294152.724
293645O22 E2
Adder
17.89176470588235215.208
960282AF2-319 E
Adder
4.0788235294117653.467
918052AA1-018 E OP
Adder
17.73647058823529615.076
276675AE2-062 E
Adder
0.167058823529411760.142
276170Z1-108 E
Adder
3.17411764705882372.698
920272AA2-123 E
Adder
3.11647058823529432.649
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8980.898
TVALTFEXP_TVA->PJM
CLTF
1.4641.464
O66PJM->LTFIMP_O-066
CMTX_NF
15.10215.102
CBM West 1LTFEXP_CBM-W1->PJM
CBM
97.73297.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.79716.797
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6640.664
MECLTFEXP_MEC->PJM
CLTF
14.26314.263
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.9021.902
LAGNLTFEXP_LAGN->PJM
CLTF
3.8723.872
NYPJM->LTFIMP_NY
CLTF
1.2591.259
WECLTFEXP_WEC->PJM
CLTF
4.2274.227
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.6140.614
G-007PJM->LTFIMP_G-007
CMTX_NF
2.3542.354
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3230.323
SIGELTFEXP_SIGE->PJM
CLTF
0.0220.022
CONTINGENCY 'AEP_P7-1_#11046___SRT-A'
 OPEN BRANCH FROM BUS 243219 TO BUS 246955 CKT 1   /*05DUMONT     345.0 - 05OLIVE_BP   345.0
 OPEN BRANCH FROM BUS 243228 TO BUS 243234 CKT 1   /*05MERIDN     345.0 - 05TWIN B     345.0
 OPEN BRANCH FROM BUS 243232 TO BUS 246955 CKT 1   /*05SORENS     345.0 - 05OLIVE_BP   345.0
END
CONTINGENCY '765-L11215__-S_SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
END
CONTINGENCY 'AEP_P1-2_#695_1681_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243207 CKT 1   /*05DUMONT     765.0 - 05GRNTWN     765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'COMED_P4_112-65-BT3-4___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT4-5___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'COMED_P4-6_116-345-R______SRT-A'
 DISCONNECT BUS 270767                                          /*GOODINGS ;1R 345.0
 DISCONNECT BUS 270769                                          /*GOODINGS ;2R 345.0
 DISCONNECT BUS 275240                                          /*GOODINGS ;1M 138.0
 TRIP BRANCH FROM BUS 270729 TO BUS 271385 TO BUS 275351 CKT 1  /*E FRANKFO; R 345.0 - E FRANKFO; R 138.0 - E FRANKFO;3C  34.5
END
CONTINGENCY 'COMED_P4_116-45-L11614__SRT-A'
 DISCONNECT BUS 270769                             /*GOODINGS ;2R 345.0
 TRIP BRANCH FROM BUS 270667 TO BUS 270665 CKT 1   /*BLUE ISL ;RT 345.0 - BLUE ISL ; R 345.0
 TRIP BRANCH FROM BUS 270667 TO BUS 270927 CKT 1   /*BLUE ISL ;RT 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 270769 TO BUS 270667 CKT 1   /*GOODINGS ;2R 345.0 - BLUE ISL ;RT 345.0
END
CONTINGENCY 'COMED_P4_112-45-BT4-5___SRT-A'
 TRIP BRANCH FROM BUS 270666 TO BUS 270664 CKT 1   /*BLUE ISL ;BT 345.0 - BLUE ISL ; B 345.0
 TRIP BRANCH FROM BUS 270666 TO BUS 270926 CKT 1   /*BLUE ISL ;BT 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 270770 TO BUS 270666 CKT 1   /*GOODINGS ;4B 345.0 - BLUE ISL ;BT 345.0
 TRIP BRANCH FROM BUS 270852 TO BUS 270704 CKT 1   /*PONTIAC  ; B 345.0 - LORETTO  ; B 345.0
END
CONTINGENCY 'COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A'
 TRIP BRANCH FROM BUS 270790 TO BUS 270770 CKT 1   /*KATYDID  ; B 345.0 - GOODINGS ;4B 345.0
 TRIP BRANCH FROM BUS 270827 TO BUS 270769 CKT 1   /*NEVADA   ; R 345.0 - GOODINGS ;2R 345.0
END
CONTINGENCY 'COMED_P4_112-65-BT5-6___SRT-A'
 TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1   /*WILTON   ;   765.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT2-3___SRT-A'
 TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1   /*WILTON   ;   765.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
243206 to 246999 ckt 1
255113 to 243219 ckt 1
960680 to 243229 ckt 1
274750 to 255112 ckt 1
270728 to 274750 ckt 1
270770 to 270766 ckt 1
270855 to 349662 ckt 1
274804 to 960680 ckt 1
270926 to 275232 ckt 1
270927 to 275233 ckt 1
275232 to 270644 ckt 1
275233 to 270644 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1CE
AB1-122 TAP2-DRESDEN ; B 345.0 kV Ckt 1 line
COMED_P1-2_345-L0304__R-S_SRT-A
OPAC113.07 %1479.0B1672.367.59
GD1CE
NEVADA ; R-GOODINGS ; R 345.0 kV Ckt 1 line
COMED_P1-2_345-L0304__R-S_SRT-A
OPAC102.5 %1290.0B1322.226.82

Details for AB1-122 TAP2-DRESDEN ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0304__R-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AB1-122 TAP2-DRESDEN ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0304__R-S_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.07 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1672.36
MW Contribution:7.59
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
AB1-122 TAP2-DRESDEN ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0304__R-S_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.1 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1672.76
MW Contribution:7.59
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
290021O50 E
50/50
98.40298.402
918052AA1-018 E OP
50/50
21.23221.232
958481AF2-142 C
50/50
14.64314.643
958482AF2-142 E
50/50
9.7629.762
958491AF2-143 C
50/50
19.81919.819
958492AF2-143 E
50/50
13.21313.213
959351AF2-226 C
50/50
3.0353.035
959352AF2-226 E
50/50
4.5534.553
960281AF2-319 C
50/50
3.0353.035
960282AF2-319 E
50/50
4.5534.553
274677POWERTON ;5U
50/50
44.85744.857
274678POWERTON ;6U
50/50
45.05845.058
274861TOP CROP ;1U
50/50
0.4560.456
274862TOP CROP ;2U
50/50
0.8710.871
274879MINONK ;1U
50/50
4.0194.019
293644O22 E1
50/50
17.43817.438
293645O22 E2
50/50
19.97319.973
938851AE1-113 C
50/50
40.59140.591
938852AE1-113 E
50/50
143.912143.912
934101AD2-000 1
50/50
-0.6-0.6
934111AD2-000 2
50/50
43.34743.347
270839OTTER CRK; R
50/50
0.5180.518
276658AB1-122 CT1
50/50
-1.212-1.212
276660AB1-122 CT2
50/50
87.58387.583
936291AD2-038 C
50/50
0.8880.888
936292AD2-038 E
50/50
27.21827.218
942421AE2-255 C
50/50
15.37515.375
942422AE2-255 E
50/50
46.12646.126
942651AE2-281 C
50/50
1.5411.541
942652AE2-281 E
50/50
9.4699.469
939321AE1-163 C
50/50
10.7910.79
939322AE1-163 E
50/50
66.28466.284
G-007PJM->LTFIMP_G-007
CMTX_NF
0.5180.518
NYPJM->LTFIMP_NY
CLTF
0.2720.272
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
1.4471.447
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.3120.312
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1910.191
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.8811.881
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.2910.291
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.9110.911
O66PJM->LTFIMP_O-066
CMTX_NF
3.3183.318
MDUPJM->LTFIMP_MDU
CLTF
0.1090.109
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.7550.755
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.4010.401

Details for NEVADA ; R-GOODINGS ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0304__R-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
NEVADA ; R-GOODINGS ; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0304__R-S_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.5 %
Rating:1290.0 MVA
Rating Type:B
MVA to Mitigate:1322.22
MW Contribution:6.82
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
290021O50 E
50/50
29.90829.908
918052AA1-018 E OP
50/50
88.84788.847
958481AF2-142 C
50/50
61.27461.274
958482AF2-142 E
50/50
40.84940.849
958491AF2-143 C
50/50
51.53251.532
958492AF2-143 E
50/50
34.35534.355
959351AF2-226 C
50/50
2.7262.726
959352AF2-226 E
50/50
4.0894.089
960281AF2-319 C
50/50
2.7262.726
960282AF2-319 E
50/50
4.0894.089
274677POWERTON ;5U
50/50
39.639.6
274678POWERTON ;6U
50/50
39.539.5
274861TOP CROP ;1U
50/50
0.410.41
274862TOP CROP ;2U
50/50
0.7820.782
274879MINONK ;1U
50/50
1.2221.222
293644O22 E1
50/50
15.66215.662
293645O22 E2
50/50
17.93917.939
938851AE1-113 C
50/50
12.33712.337
938852AE1-113 E
50/50
43.7443.74
270839OTTER CRK; R
50/50
2.1692.169
936291AD2-038 C
50/50
2.3082.308
936292AD2-038 E
50/50
70.77170.771
942421AE2-255 C
50/50
4.6734.673
942422AE2-255 E
50/50
14.01914.019
942651AE2-281 C
50/50
4.0084.008
942652AE2-281 E
50/50
24.62124.621
939321AE1-163 C
50/50
28.05728.057
939322AE1-163 E
50/50
172.347172.347
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3560.356
NYPJM->LTFIMP_NY
CLTF
0.1880.188
WECLTFEXP_WEC->PJM
CLTF
0.0110.011
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.5020.502
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1820.182
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1090.109
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.5680.568
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1810.181
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.560.56
O66PJM->LTFIMP_O-066
CMTX_NF
2.2852.285
MDUPJM->LTFIMP_MDU
CLTF
0.0040.004
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.2080.208
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.2390.239
CONTINGENCY 'COMED_P1-2_345-L0304__R-S_SRT-A'
 TRIP BRANCH FROM BUS 270855 TO BUS 349662 CKT 1   /*POWERTON ; R 345.0 - 7TAZEWELL    345.0
END
276659 to 270716 ckt 1
270827 to 270769 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Base Case
OPAC112.52 %1075.0A1209.614.52
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Base Case
OPAC114.84 %1091.0A1252.955.42
GD1CE
NEVADA ; R-GOODINGS ;2R 345.0 kV Ckt 1 line
COMED_P1-2_345-L0304__R-S_SRT-A
OPAC102.29 %1290.0B1319.66.81

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.52 %
Rating:1075.0 MVA
Rating Type:A
MVA to Mitigate:1209.61
MW Contribution:4.52
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.69647058823529421.442
962012AG1-044 E
Adder
0.04117647058823530.035
962781AG1-127 C
Adder
4.4894117647058823.816
962782AG1-127 E
Adder
2.9882352941176472.54
966091AG1-478 C
Adder
1.46941176470588241.249
966092AG1-478 E
Adder
0.36941176470588240.314
966441AG1-513 C
Adder
0.32705882352941180.278
966442AG1-513 E
Adder
0.48941176470588230.416
290021O50 E
Adder
13.1552941176470611.182
290051GSG-6; E
Adder
6.7482352941176475.736
295109WESTBROOK E
Adder
3.61294117647058853.071
295111SUBLETTE E
Adder
1.75647058823529421.493
910542X3-005 E
Adder
0.71294117647058820.606
918052AA1-018 E OP
Adder
11.3482352941176489.646
933911AD1-013 C
Adder
1.18705882352941171.009
933912AD1-013 E
Adder
1.89647058823529441.612
934722AD1-100 E
Adder
60.7764705882352951.66
937002AD2-134 E
Adder
6.5247058823529425.546
937312AD2-172 E
Adder
2.20823529411764731.877
958481AF2-142 C
Adder
7.8258823529411776.652
958482AF2-142 E
Adder
5.21764705882352954.435
958491AF2-143 C
Adder
7.5847058823529416.447
958492AF2-143 E
Adder
5.0564705882352944.298
958912AF2-182 E
Adder
22.26470588235294218.925
959081AF2-199 C
Adder
4.6141176470588243.922
959082AF2-199 E
Adder
2.3070588235294121.961
959351AF2-226 C
Adder
1.80588235294117651.535
959352AF2-226 E
Adder
2.70941176470588242.303
960281AF2-319 C
Adder
1.80588235294117651.535
960282AF2-319 E
Adder
2.70941176470588242.303
960582AF2-349 E
Adder
23.60470588235294220.064
960751AF2-366 C
Adder
4.4776470588235293.806
960752AF2-366 E
Adder
2.98470588235294132.537
274675JOLIET 29;7U
Adder
49.9447058823529542.453
274676JOLIET 29;8U
Adder
49.9529411764705942.46
274682WAUKEGAN ;7U
Adder
27.29294117647059223.199
274683WAUKEGAN ;8U
Adder
29.42352941176470825.01
274687WILL CNTY;4U
Adder
48.5929411764705941.304
274724RIVER EC ;11
50/50
3.9023.902
274788SE CHICAG;5U
50/50
5.5385.538
274789SE CHICAG;6U
50/50
5.5385.538
274790SE CHICAG;7U
50/50
5.5385.538
274791SE CHICAG;8U
50/50
5.5385.538
274792SE CHICAG;9U
50/50
5.4655.465
274793SE CHICAG;0U
Adder
5.464705882352944.645
274794SE CHICAG;1U
50/50
5.4655.465
274795SE CHICAG;2U
Adder
5.464705882352944.645
274859EASYR;U1 E
Adder
7.82352941176470656.65
274860EASYR;U2 E
Adder
7.82352941176470656.65
276591L-013 2
Adder
2.36235294117647052.008
293061N-015 E
Adder
9.8294117647058838.355
293644O22 E1
Adder
10.3776470588235298.821
293645O22 E2
Adder
11.88588235294117710.103
293715O-029 E
Adder
6.3811764705882365.424
293716O-029 E
Adder
3.4988235294117652.974
293717O-029 E
Adder
3.2152941176470592.733
293771O-035 E
Adder
4.5764705882352953.89
294392P-010 E
Adder
12.48352941176470710.611
294763P-046 E
Adder
6.13764705882352955.217
925582AC1-033 E
Adder
2.2152941176470591.883
933411AC2-154 C
Adder
1.90000000000000011.615
933412AC2-154 E
Adder
3.09999999999999962.635
939061AE1-134 2
Adder
0.89294117647058820.759
940502AE2-035 E
Adder
2.20823529411764731.877
957331AF2-027 C
Adder
1.64941176470588241.402
957332AF2-027 E
Adder
2.4741176470588242.103
957471AF2-041 C
Adder
13.84352941176470611.767
957472AF2-041 E
Adder
6.9211764705882355.883
274674JOLIET 9 ;6U
Adder
25.73058823529411821.871
274890CAYUG;1U E
Adder
9.1035294117647067.738
274891CAYUG;2U E
Adder
9.1035294117647067.738
938851AE1-113 C
Adder
5.4270588235294124.613
938852AE1-113 E
Adder
19.2416.354
934101AD2-000 1
Adder
3.68941176470588243.136
934111AD2-000 2
Adder
4.077647058823533.466
275149KELLYCK ;1E
Adder
14.00117647058823611.901
293516O-009 E
Adder
12.33882352941176410.488
293519PILOT HIL;1E
Adder
14.00117647058823611.901
916212CRESCENT ;1U
Adder
3.2152941176470592.733
927208AC1-214 E1
Adder
2.16941176470588241.844
927209AC1-214 E2
Adder
2.16941176470588241.844
290108LEEDK;1U E
Adder
15.41176470588235313.1
916221Z1-073 E
Adder
4.75529411764705844.042
926821AC1-168 C
Adder
0.75294117647058820.64
926822AC1-168 E
Adder
5.0564705882352944.298
936292AD2-038 E
Adder
10.4164705882352948.854
936371AD2-047 C
Adder
3.40000000000000042.89
936372AD2-047 E
Adder
16.614.11
936461AD2-060 C
Adder
2.01.7
936511AD2-066 C
Adder
5.6788235294117654.827
936512AD2-066 E
Adder
3.78588235294117673.218
942421AE2-255 C
Adder
2.0552941176470591.747
942422AE2-255 E
Adder
6.1670588235294125.242
942651AE2-281 C
Adder
0.58941176470588240.501
942652AE2-281 E
Adder
3.6235294117647063.08
943121AE2-341 C
Adder
7.99529411764705966.796
943122AE2-341 E
Adder
3.9258823529411773.337
943591AF1-030 C
Adder
5.3176470588235294.52
943592AF1-030 E
Adder
2.6305882352941182.236
959091AF2-200 C
Adder
9.2294117647058827.845
959092AF2-200 E
Adder
6.1529411764705895.23
960591AF2-350 C
Adder
6.05.1
960592AF2-350 E
Adder
4.03.4
961501AF2-441 C
Adder
10.915294117647069.278
961502AF2-441 E
Adder
16.37411764705882413.918
938861AE1-114 C
Adder
2.562.176
938862AE1-114 E
Adder
8.7329411764705887.423
939321AE1-163 C
Adder
4.1294117647058823.51
939322AE1-163 E
Adder
25.36588235294117821.561
939351AE1-166 C
Adder
6.7717647058823545.756
939352AE1-166 E
Adder
6.2517647058823535.314
946152AF1-280 E
Adder
14.84352941176470812.617
946671AF1-331 C
Adder
1.54235294117647051.311
962691AG1-118 C
Adder
14.20823529411764812.077
962692AG1-118 E
Adder
9.4717647058823548.051
941551AE2-152 C
Adder
7.8141176470588246.642
941552AE2-152 E
Adder
5.2094117647058834.428
957371AF2-031 C
50/50
1.1831.183
957372AF2-031 E
50/50
1.7751.775
958011AF2-095 C
Adder
8.6411764705882357.345
958012AF2-095 E
Adder
5.764.896
920272AA2-123 E
Adder
1.87058823529411791.59
276170Z1-108 E
Adder
1.9070588235294121.621
276626AG1-044 E
Adder
0.0482352941176470640.041
276675AE2-062 E
Adder
0.107058823529411760.091
CBM West 1LTFEXP_CBM-W1->PJM
CBM
75.73675.736
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.85611.856
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3871.387
NYPJM->LTFIMP_NY
CLTF
0.7460.746
WECLTFEXP_WEC->PJM
CLTF
2.5782.578
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2990.299
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1480.148
TVALTFEXP_TVA->PJM
CLTF
1.1741.174
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.2290.229
MECLTFEXP_MEC->PJM
CLTF
8.7698.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.6110.611
LAGNLTFEXP_LAGN->PJM
CLTF
2.6762.676
SIGELTFEXP_SIGE->PJM
CLTF
0.0530.053
O66PJM->LTFIMP_O-066
CMTX_NF
8.8988.898
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.4540.454

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:114.84 %
Rating:1091.0 MVA
Rating Type:A
MVA to Mitigate:1252.95
MW Contribution:5.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.76941176470588251.504
962012AG1-044 E
Adder
0.0423529411764705860.036
962781AG1-127 C
Adder
4.6976470588235293.993
962782AG1-127 E
Adder
3.12588235294117662.657
966091AG1-478 C
Adder
1.3482352941176471.146
966092AG1-478 E
Adder
0.33882352941176470.288
966441AG1-513 C
Adder
0.34235294117647060.291
966442AG1-513 E
Adder
0.51294117647058820.436
290021O50 E
Adder
13.8752941176470611.794
290051GSG-6; E
Adder
7.045.984
295109WESTBROOK E
Adder
3.76941176470588253.204
295111SUBLETTE E
Adder
1.8317647058823531.557
918052AA1-018 E OP
Adder
10.6611764705882349.062
933911AD1-013 C
Adder
1.23882352941176471.053
933912AD1-013 E
Adder
1.97882352941176461.682
934722AD1-100 E
Adder
60.5729411764705951.487
937002AD2-134 E
Adder
6.8070588235294115.786
937312AD2-172 E
Adder
2.30000000000000031.955
958481AF2-142 C
Adder
7.3529411764705896.25
958482AF2-142 E
Adder
4.90117647058823554.166
958491AF2-143 C
Adder
7.3411764705882366.24
958492AF2-143 E
Adder
4.8941176470588244.16
958912AF2-182 E
Adder
23.1219.652
959081AF2-199 C
Adder
4.8305882352941174.106
959082AF2-199 E
Adder
2.41529411764705862.053
959351AF2-226 C
50/50
2.1682.168
959352AF2-226 E
50/50
3.2523.252
960281AF2-319 C
50/50
2.1682.168
960282AF2-319 E
50/50
3.2523.252
960582AF2-349 E
Adder
24.68117647058823420.979
960751AF2-366 C
Adder
4.6847058823529423.982
960752AF2-366 E
Adder
3.12235294117647082.654
274654BRAIDWOOD;1U
50/50
19.28319.283
274675JOLIET 29;7U
Adder
52.87529411764706644.944
274676JOLIET 29;8U
Adder
52.9223529411764844.984
274682WAUKEGAN ;7U
Adder
28.6329411764705924.338
274683WAUKEGAN ;8U
Adder
30.8552941176470626.227
274687WILL CNTY;4U
Adder
50.79647058823529443.177
274752CRETE EC ;2U
50/50
5.7635.763
274753CRETE EC ;3U
50/50
5.7635.763
274754CRETE EC ;4U
50/50
5.7635.763
274859EASYR;U1 E
Adder
8.1305882352941186.911
274860EASYR;U2 E
Adder
8.1305882352941186.911
274861TOP CROP ;1U
50/50
0.3250.325
274862TOP CROP ;2U
50/50
0.620.62
276591L-013 2
Adder
2.4788235294117652.107
293061N-015 E
Adder
10.669.061
293644O22 E1
50/50
12.45512.455
293645O22 E2
50/50
14.26614.266
293715O-029 E
Adder
6.58705882352941255.599
293716O-029 E
Adder
3.6117647058823533.07
293717O-029 E
Adder
3.32000000000000032.822
293771O-035 E
Adder
4.6694117647058823.969
294392P-010 E
Adder
13.53764705882352911.507
294401BSHIL;1U E
Adder
5.8247058823529414.951
294410BSHIL;2U E
Adder
1.40235294117647061.192
294763P-046 E
Adder
6.3917647058823535.433
925582AC1-033 E
Adder
6.3858823529411765.428
933411AC2-154 C
Adder
1.4682352941176471.248
933412AC2-154 E
Adder
2.3952941176470592.036
939061AE1-134 2
Adder
0.92588235294117650.787
940502AE2-035 E
Adder
2.30000000000000031.955
957331AF2-027 C
Adder
1.7282352941176471.469
957332AF2-027 E
Adder
2.5917647058823532.203
957471AF2-041 C
Adder
14.49058823529411912.317
957472AF2-041 E
Adder
7.24470588235294166.158
274674JOLIET 9 ;6U
Adder
23.3929411764705919.884
274890CAYUG;1U E
Adder
8.9564705882352957.613
274891CAYUG;2U E
Adder
8.9564705882352957.613
938851AE1-113 C
Adder
5.7235294117647064.865
938852AE1-113 E
Adder
20.2929411764705917.249
934101AD2-000 1
Adder
3.8435294117647063.267
934111AD2-000 2
Adder
4.3529411764705893.7
275149KELLYCK ;1E
Adder
10.8188235294117649.196
293516O-009 E
Adder
12.7376470588235310.827
293519PILOT HIL;1E
Adder
10.8188235294117649.196
916212CRESCENT ;1U
Adder
3.282.788
927208AC1-214 E1
Adder
2.21411764705882331.882
927209AC1-214 E2
Adder
2.21411764705882331.882
290108LEEDK;1U E
Adder
16.10823529411764813.692
916221Z1-073 E
Adder
4.9611764705882354.217
926821AC1-168 C
Adder
0.77647058823529410.66
926822AC1-168 E
Adder
5.2117647058823534.43
936292AD2-038 E
Adder
10.0823529411764728.57
936371AD2-047 C
Adder
2.6270588235294122.233
936372AD2-047 E
Adder
12.82823529411764710.904
936461AD2-060 C
Adder
1.54588235294117651.314
936511AD2-066 C
Adder
5.7423529411764714.881
936512AD2-066 E
Adder
3.8282352941176473.254
942421AE2-255 C
Adder
2.16823529411764731.843
942422AE2-255 E
Adder
6.5047058823529415.529
942651AE2-281 C
Adder
0.57058823529411760.485
942652AE2-281 E
Adder
3.50705882352941162.981
943121AE2-341 C
Adder
8.397647058823537.138
943122AE2-341 E
Adder
4.1235294117647053.505
943591AF1-030 C
Adder
5.5847058823529414.747
943592AF1-030 E
Adder
2.7635294117647062.349
959091AF2-200 C
Adder
9.668.211
959092AF2-200 E
Adder
6.445.474
960591AF2-350 C
Adder
4.6364705882352943.941
960592AF2-350 E
Adder
3.09058823529411742.627
938861AE1-114 C
Adder
2.66117647058823532.262
938862AE1-114 E
Adder
9.087.718
939321AE1-163 C
Adder
3.99647058823529383.397
939322AE1-163 E
Adder
24.55176470588235220.869
939351AE1-166 C
Adder
6.7494117647058835.737
939352AE1-166 E
Adder
6.2305882352941185.296
946152AF1-280 E
Adder
15.4129411764705913.101
946671AF1-331 C
Adder
1.60941176470588251.368
962691AG1-118 C
Adder
14.86823529411764812.638
962692AG1-118 E
Adder
9.912941176470598.426
941551AE2-152 C
Adder
7.7882352941176486.62
941552AE2-152 E
Adder
5.19176470588235354.413
958011AF2-095 C
Adder
6.6764705882352945.675
958012AF2-095 E
Adder
4.4505882352941173.783
274751CRETE EC ;1U
50/50
5.7635.763
920272AA2-123 E
Adder
1.95882352941176491.665
276170Z1-108 E
Adder
2.00117647058823561.701
276626AG1-044 E
Adder
0.0494117647058823560.042
276675AE2-062 E
Adder
0.103529411764705880.088
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.81249.812
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.3588.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.4391.439
NYPJM->LTFIMP_NY
CLTF
0.7740.774
WECLTFEXP_WEC->PJM
CLTF
2.6882.688
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.3940.394
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2110.211
TVALTFEXP_TVA->PJM
CLTF
0.660.66
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5040.504
MECLTFEXP_MEC->PJM
CLTF
8.7288.728
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.491.49
LAGNLTFEXP_LAGN->PJM
CLTF
2.092.09
O66PJM->LTFIMP_O-066
CMTX_NF
9.239.23
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.5680.568

Details for NEVADA ; R-GOODINGS ;2R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0304__R-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
NEVADA ; R-GOODINGS ;2R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0304__R-S_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.29 %
Rating:1290.0 MVA
Rating Type:B
MVA to Mitigate:1319.6
MW Contribution:6.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
290021O50 E
50/50
29.87529.875
918052AA1-018 E OP
50/50
88.77888.778
958481AF2-142 C
50/50
61.22761.227
958482AF2-142 E
50/50
40.81840.818
958491AF2-143 C
50/50
51.49251.492
958492AF2-143 E
50/50
34.32834.328
959351AF2-226 C
50/50
2.7252.725
959352AF2-226 E
50/50
4.0884.088
960281AF2-319 C
50/50
2.7252.725
960282AF2-319 E
50/50
4.0884.088
274677POWERTON ;5U
50/50
39.43239.432
274678POWERTON ;6U
50/50
39.33339.333
274861TOP CROP ;1U
50/50
0.4080.408
274862TOP CROP ;2U
50/50
0.7790.779
274879MINONK ;1U
50/50
1.2161.216
293644O22 E1
50/50
15.65715.657
293645O22 E2
50/50
17.93217.932
938851AE1-113 C
50/50
12.32312.323
938852AE1-113 E
50/50
43.69243.692
270839OTTER CRK; R
50/50
2.162.16
936291AD2-038 C
50/50
2.2982.298
936292AD2-038 E
50/50
70.71670.716
942421AE2-255 C
50/50
4.6684.668
942422AE2-255 E
50/50
14.00414.004
942651AE2-281 C
50/50
4.0054.005
942652AE2-281 E
50/50
24.60224.602
939321AE1-163 C
50/50
28.03528.035
939322AE1-163 E
50/50
172.214172.214
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3540.354
NYPJM->LTFIMP_NY
CLTF
0.1870.187
WECLTFEXP_WEC->PJM
CLTF
0.0080.008
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.5030.503
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1810.181
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1090.109
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.5720.572
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1790.179
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.5540.554
O66PJM->LTFIMP_O-066
CMTX_NF
2.2672.267
MDUPJM->LTFIMP_MDU
CLTF
0.0040.004
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.2110.211
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.2370.237
CONTINGENCY 'COMED_P1-2_345-L0304__R-S_SRT-A'
 TRIP BRANCH FROM BUS 270855 TO BUS 349662 CKT 1   /*POWERTON ; R 345.0 - 7TAZEWELL    345.0
END
255113 to 243219 ckt 1
274750 to 255112 ckt 1
270827 to 270769 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AF2-226 was evaluated as a 50.0 MW injection and 50.0 MW withdrawal in the ComEd area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AMIL/CE
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A
TowerAC101.66 %1489.0B1513.7336.34

Details for POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AMIL/CE
Facility Description:
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.66 %
Rating:1489.0 MVA
Rating Type:B
MVA to Mitigate:1513.73
MW Contribution:36.34
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274861TOP CROP ;1U
50/50
3.3433.343
274862TOP CROP ;2U
50/50
6.3786.378
942421AE2-255 C
50/50
8.7188.718
942422AE2-255 E
50/50
26.15526.155
938851AE1-113 C
50/50
23.01723.017
270839OTTER CRK; R
50/50
3.5433.543
938852AE1-113 E
50/50
81.60481.604
274879MINONK ;1U
50/50
4.3594.359
293645O22 E2
50/50
23.91223.912
959352AF2-226 E
50/50
21.80421.804
960281AF2-319 C
50/50
14.53614.536
960282AF2-319 E
50/50
21.80421.804
918052AA1-018 E OP
50/50
23.71223.712
942651AE2-281 C
50/50
4.074.07
939322AE1-163 E
50/50
175.006175.006
959351AF2-226 C
50/50
14.53614.536
290021O50 E
50/50
17.43717.437
293644O22 E1
50/50
20.87820.878
939321AE1-163 C
50/50
28.48928.489
942652AE2-281 E
50/50
25.00125.001
CONTINGENCY 'COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A'
 TRIP BRANCH FROM BUS 270790 TO BUS 270770 CKT 1   /*KATYDID  ; B 345.0 - GOODINGS ; B 345.0
 TRIP BRANCH FROM BUS 270827 TO BUS 270769 CKT 1   /*NEVADA   ; R 345.0 - GOODINGS ; R 345.0
END
270855 to 349662 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC127.96 %1075.0B1375.597.05
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC127.94 %1075.0B1375.377.05
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC117.34 %1075.0B1261.436.85
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC122.26 %971.0B1187.124.91
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC122.21 %971.0B1186.74.91
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC108.87 %971.0B1057.124.91
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC108.87 %971.0B1057.114.91
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC115.73 %1399.0B1619.017.13
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC115.64 %1399.0B1617.847.13
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC103.82 %1399.0B1452.467.1
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC102.92 %1399.0B1439.817.13
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Base Case
SingleAC100.53 %1091.0A1096.795.26
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC115.75 %1399.0B1619.47.13
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC115.67 %1399.0B1618.227.13
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC103.83 %1399.0B1452.537.1
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC102.92 %1399.0B1439.867.13
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Base Case
SingleAC100.52 %1091.0A1096.725.26
GD1AMIL/CE
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A
TowerAC101.67 %1489.0B1513.8836.34
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC119.44 %970.0STE1158.614.91
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC119.42 %970.0STE1158.424.91
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC105.94 %970.0STE1027.64.91
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC105.94 %970.0STE1027.594.91

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.96 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1375.59
MW Contribution:7.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
5.3895.389
290051GSG-6; E
80/20
2.8722.872
290108LEEDK;1U E
80/20
6.5926.592
290261S-027 E
80/20
4.1334.133
290265S-028 E
80/20
4.1084.108
295111SUBLETTE E
80/20
0.7470.747
925581AC1-033 C
80/20
0.6150.615
925582AC1-033 E
80/20
4.1154.115
938861AE1-114 C
80/20
3.4363.436
957371AF2-031 C
80/20
1.5261.526
960261AF2-317 C
80/20
0.4950.495
961501AF2-441 C
80/20
14.5914.59
270681BRIGHTSTK; R
80/20
0.6920.692
274887PILOT HIL;1U
80/20
1.3431.343
275149KELLYCK ;1E
80/20
5.3725.372
293771O-035 E
80/20
1.8811.881
924048AB2-047 E1
80/20
2.8732.873
937001AD2-134 C
80/20
1.1131.113
944221AF1-090 C
80/20
1.7541.754
274682WAUKEGAN ;7U
80/20
20.43720.437
274683WAUKEGAN ;8U
80/20
22.03122.031
274861TOP CROP ;1U
80/20
0.6480.648
274862TOP CROP ;2U
80/20
1.2361.236
274863CAYUGA RI;1U
80/20
0.7080.708
276157O-029 C
80/20
0.6060.606
276158O-029 C
80/20
0.6060.606
934721AD1-100 C
80/20
5.2135.213
942421AE2-255 C
80/20
2.6652.665
942422AE2-255 E
80/20
7.9967.996
959611AF2-252 C
80/20
2.0262.026
960611AF2-352 C
80/20
2.0262.026
960612AF2-352 E
80/20
3.0393.039
990901L-005 E
80/20
3.4733.473
274687WILL CNTY;4U
80/20
45.63745.637
276656AB2-047 C2
80/20
0.4330.433
294401BSHIL;1U E
80/20
2.3442.344
925772AC1-053 E
80/20
5.6625.662
926821AC1-168 C
80/20
0.9980.998
927208AC1-214 E1
80/20
0.8920.892
959612AF2-252 E
80/20
3.0393.039
274864CAYUGA RI;2U
80/20
0.7080.708
274847GR RIDGE ;BU
80/20
0.9610.961
274849CRESCENT ;1U
80/20
0.2860.286
274857BIG SKY ;U1
80/20
0.4760.476
274859EASYR;U1 E
80/20
3.283.28
274872LEE DEKAL;1U
80/20
1.3351.335
276621X2-022 GEN
80/20
3.6453.645
293061N-015 E
80/20
4.214.21
293519PILOT HIL;1E
80/20
5.3725.372
924049AB2-047 E2
80/20
2.9192.919
934722AD1-100 E
80/20
81.09481.094
939322AE1-163 E
80/20
32.3232.32
944222AF1-090 E
80/20
8.2118.211
946322AF1-296 E
80/20
14.52214.522
959351AF2-226 C
80/20
2.8182.818
966092AG1-478 E
80/20
0.8780.878
274676JOLIET 29;8U
80/20
48.17348.173
294763P-046 E
80/20
2.5772.577
295109WESTBROOK E
80/20
1.5381.538
936371AD2-047 C
80/20
4.1754.175
938851AE1-113 C
80/20
7.0367.036
957372AF2-031 E
80/20
2.2882.288
965331AG1-398 C
80/20
0.2420.242
966442AG1-513 E
80/20
0.8410.841
274674JOLIET 9 ;6U
80/20
18.55318.553
274890CAYUG;1U E
80/20
3.7773.777
276602WESTBROOK C
80/20
0.2330.233
276675AE2-062 E
80/20
0.1460.146
942651AE2-281 C
80/20
0.7520.752
270839OTTER CRK; R
80/20
0.6710.671
274888KELLY CRK;1U
80/20
1.3431.343
293716O-029 E
80/20
1.4571.457
937002AD2-134 E
80/20
4.4474.447
938852AE1-113 E
80/20
24.94624.946
938862AE1-114 E
80/20
11.72411.724
274851PROVIDENC;RU
80/20
0.3040.304
274853TWINGROVE;U1
80/20
0.8810.881
274854TWINGROVE;U2
80/20
0.9070.907
274855GSG-6 ;RU
80/20
0.7180.718
274879MINONK ;1U
80/20
1.3331.333
274880RADFORD R;1U
80/20
0.9440.944
274881WALNUT RG;1U
80/20
1.2841.284
293645O22 E2
80/20
4.6364.636
293715O-029 E
80/20
2.6572.657
293717O-029 E
80/20
1.3391.339
916212CRESCENT ;1U
80/20
1.3211.321
916221Z1-073 E
80/20
2.0242.024
957331AF2-027 C
80/20
2.7442.744
957332AF2-027 E
80/20
4.1174.117
959352AF2-226 E
80/20
4.2274.227
960281AF2-319 C
80/20
2.8182.818
960282AF2-319 E
80/20
4.2274.227
276655AB2-047 C1
80/20
0.4330.433
294392P-010 E
80/20
5.3475.347
294410BSHIL;2U E
80/20
2.3442.344
918052AA1-018 E OP
80/20
4.4934.493
926822AC1-168 E
80/20
6.6946.694
927209AC1-214 E2
80/20
0.8920.892
276645AC1-214 C1
80/20
0.2510.251
276646AC1-214 C2
80/20
0.2510.251
925771AC1-053 C
80/20
0.8460.846
962012AG1-044 E
80/20
0.0610.061
274878BISHOP HL;2U
80/20
0.5860.586
276626AG1-044 E
80/20
0.0680.068
917502Z2-087 E
80/20
4.6344.634
942112AE2-223 E
80/20
11.12111.121
274848CAMPGROVE;RU
80/20
0.3760.376
274850MENDOTA H;RU
80/20
0.4720.472
274856ECOGROVE ;U1
80/20
0.620.62
274858BIG SKY ;U2
80/20
0.4760.476
274871GR RIDGE ;2U
80/20
0.3580.358
274877BISHOP HL;1U
80/20
0.5860.586
276615W2-048 GEN
80/20
1.2811.281
293516O-009 E
80/20
5.1385.138
293644O22 E1
80/20
4.0484.048
924266AB2-070 E
80/20
3.253.25
936372AD2-047 E
80/20
20.38420.384
939321AE1-163 C
80/20
5.2615.261
942111AE2-223 C
80/20
1.6621.662
942652AE2-281 E
80/20
4.6174.617
946321AF1-296 C
80/20
3.1023.102
966441AG1-513 C
80/20
0.5610.561
274675JOLIET 29;7U
80/20
48.1748.17
274860EASYR;U2 E
80/20
3.283.28
276156O-029 C
80/20
0.3360.336
290021O50 E
80/20
5.335.33
961502AF2-441 E
80/20
21.88421.884
966091AG1-478 C
80/20
0.5860.586
274891CAYUG;2U E
80/20
3.7773.777
276603SUBLETTE C
80/20
0.1050.105
276668AB2-070 C
80/20
0.5370.537
276627AG1-044 BAT
80/20
0.0120.012
935141AD1-148 C
80/20
1.1451.145
957382AF2-032 E
80/20
0.1430.143
276170Z1-108 E
80/20
2.7352.735
965913AG1-460 BT
80/20
0.0070.007
920272AA2-123 E
80/20
2.682.68
990547J1333 G
External Queue
9.21919.2191
990582J1340
External Queue
6.17656.1765
990647J1355
External Queue
42.973342.9733
990552J1334 G
External Queue
9.21919.2191
990557J1335 G
External Queue
9.21919.2191
990562J1336 G
External Queue
9.21919.2191
990577J1339
External Queue
2.90532.9053

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.94 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1375.37
MW Contribution:7.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
5.3895.389
290051GSG-6; E
80/20
2.8722.872
290108LEEDK;1U E
80/20
6.5926.592
290261S-027 E
80/20
4.1334.133
290265S-028 E
80/20
4.1084.108
295111SUBLETTE E
80/20
0.7470.747
925581AC1-033 C
80/20
0.6150.615
925582AC1-033 E
80/20
4.1154.115
938861AE1-114 C
80/20
3.4363.436
957371AF2-031 C
80/20
1.5261.526
960261AF2-317 C
80/20
0.4950.495
961501AF2-441 C
80/20
14.5914.59
270681BRIGHTSTK; R
80/20
0.6920.692
274887PILOT HIL;1U
80/20
1.3431.343
275149KELLYCK ;1E
80/20
5.3725.372
293771O-035 E
80/20
1.8811.881
924048AB2-047 E1
80/20
2.8732.873
937001AD2-134 C
80/20
1.1131.113
944221AF1-090 C
80/20
1.7541.754
274682WAUKEGAN ;7U
80/20
20.43720.437
274683WAUKEGAN ;8U
80/20
22.03122.031
274861TOP CROP ;1U
80/20
0.6480.648
274862TOP CROP ;2U
80/20
1.2361.236
274863CAYUGA RI;1U
80/20
0.7080.708
276157O-029 C
80/20
0.6060.606
276158O-029 C
80/20
0.6060.606
934721AD1-100 C
80/20
5.2135.213
942421AE2-255 C
80/20
2.6652.665
942422AE2-255 E
80/20
7.9967.996
959611AF2-252 C
80/20
2.0262.026
960611AF2-352 C
80/20
2.0262.026
960612AF2-352 E
80/20
3.0393.039
990901L-005 E
80/20
3.4733.473
274687WILL CNTY;4U
80/20
45.63745.637
276656AB2-047 C2
80/20
0.4330.433
294401BSHIL;1U E
80/20
2.3442.344
925772AC1-053 E
80/20
5.6625.662
926821AC1-168 C
80/20
0.9980.998
927208AC1-214 E1
80/20
0.8920.892
959612AF2-252 E
80/20
3.0393.039
274864CAYUGA RI;2U
80/20
0.7080.708
274847GR RIDGE ;BU
80/20
0.9610.961
274849CRESCENT ;1U
80/20
0.2860.286
274857BIG SKY ;U1
80/20
0.4760.476
274859EASYR;U1 E
80/20
3.283.28
274872LEE DEKAL;1U
80/20
1.3351.335
276621X2-022 GEN
80/20
3.6453.645
293061N-015 E
80/20
4.214.21
293519PILOT HIL;1E
80/20
5.3725.372
924049AB2-047 E2
80/20
2.9192.919
934722AD1-100 E
80/20
81.09481.094
939322AE1-163 E
80/20
32.3232.32
944222AF1-090 E
80/20
8.2118.211
946322AF1-296 E
80/20
14.52214.522
959351AF2-226 C
80/20
2.8182.818
966092AG1-478 E
80/20
0.8780.878
274676JOLIET 29;8U
80/20
48.17348.173
294763P-046 E
80/20
2.5772.577
295109WESTBROOK E
80/20
1.5381.538
936371AD2-047 C
80/20
4.1754.175
938851AE1-113 C
80/20
7.0367.036
957372AF2-031 E
80/20
2.2882.288
965331AG1-398 C
80/20
0.2420.242
966442AG1-513 E
80/20
0.8410.841
274674JOLIET 9 ;6U
80/20
18.55318.553
274890CAYUG;1U E
80/20
3.7773.777
276602WESTBROOK C
80/20
0.2330.233
276675AE2-062 E
80/20
0.1460.146
942651AE2-281 C
80/20
0.7520.752
270839OTTER CRK; R
80/20
0.6710.671
274888KELLY CRK;1U
80/20
1.3431.343
293716O-029 E
80/20
1.4571.457
937002AD2-134 E
80/20
4.4474.447
938852AE1-113 E
80/20
24.94624.946
938862AE1-114 E
80/20
11.72411.724
274851PROVIDENC;RU
80/20
0.3040.304
274853TWINGROVE;U1
80/20
0.8810.881
274854TWINGROVE;U2
80/20
0.9070.907
274855GSG-6 ;RU
80/20
0.7180.718
274879MINONK ;1U
80/20
1.3331.333
274880RADFORD R;1U
80/20
0.9440.944
274881WALNUT RG;1U
80/20
1.2841.284
293645O22 E2
80/20
4.6364.636
293715O-029 E
80/20
2.6572.657
293717O-029 E
80/20
1.3391.339
916212CRESCENT ;1U
80/20
1.3211.321
916221Z1-073 E
80/20
2.0242.024
957331AF2-027 C
80/20
2.7442.744
957332AF2-027 E
80/20
4.1174.117
959352AF2-226 E
80/20
4.2274.227
960281AF2-319 C
80/20
2.8182.818
960282AF2-319 E
80/20
4.2274.227
276655AB2-047 C1
80/20
0.4330.433
294392P-010 E
80/20
5.3475.347
294410BSHIL;2U E
80/20
2.3442.344
918052AA1-018 E OP
80/20
4.4934.493
926822AC1-168 E
80/20
6.6946.694
927209AC1-214 E2
80/20
0.8920.892
276645AC1-214 C1
80/20
0.2510.251
276646AC1-214 C2
80/20
0.2510.251
925771AC1-053 C
80/20
0.8460.846
962012AG1-044 E
80/20
0.0610.061
274878BISHOP HL;2U
80/20
0.5860.586
276626AG1-044 E
80/20
0.0680.068
917502Z2-087 E
80/20
4.6344.634
942112AE2-223 E
80/20
11.12111.121
274848CAMPGROVE;RU
80/20
0.3760.376
274850MENDOTA H;RU
80/20
0.4720.472
274856ECOGROVE ;U1
80/20
0.620.62
274858BIG SKY ;U2
80/20
0.4760.476
274871GR RIDGE ;2U
80/20
0.3580.358
274877BISHOP HL;1U
80/20
0.5860.586
276615W2-048 GEN
80/20
1.2811.281
293516O-009 E
80/20
5.1385.138
293644O22 E1
80/20
4.0484.048
924266AB2-070 E
80/20
3.253.25
936372AD2-047 E
80/20
20.38420.384
939321AE1-163 C
80/20
5.2615.261
942111AE2-223 C
80/20
1.6621.662
942652AE2-281 E
80/20
4.6174.617
946321AF1-296 C
80/20
3.1023.102
966441AG1-513 C
80/20
0.5610.561
274675JOLIET 29;7U
80/20
48.1748.17
274860EASYR;U2 E
80/20
3.283.28
276156O-029 C
80/20
0.3360.336
290021O50 E
80/20
5.335.33
961502AF2-441 E
80/20
21.88421.884
966091AG1-478 C
80/20
0.5860.586
274891CAYUG;2U E
80/20
3.7773.777
276603SUBLETTE C
80/20
0.1050.105
276668AB2-070 C
80/20
0.5370.537
276627AG1-044 BAT
80/20
0.0120.012
935141AD1-148 C
80/20
1.1451.145
957382AF2-032 E
80/20
0.1430.143
276170Z1-108 E
80/20
2.7352.735
920272AA2-123 E
80/20
2.682.68
965913AG1-460 BT
80/20
0.0070.007
990547J1333 G
External Queue
9.21919.2191
990582J1340
External Queue
6.17656.1765
990647J1355
External Queue
42.973342.9733
990552J1334 G
External Queue
9.21919.2191
990557J1335 G
External Queue
9.21919.2191
990562J1336 G
External Queue
9.21919.2191
990577J1339
External Queue
2.90532.9053

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.34 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1261.43
MW Contribution:6.85
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
3.35882352941176482.855
957371AF2-031 C
50/50
1.4761.476
961501AF2-441 C
50/50
14.11814.118
274887PILOT HIL;1U
50/50
1.3011.301
275149KELLYCK ;1E
50/50
5.2055.205
944221AF1-090 C
Adder
1.85529411764705881.577
274682WAUKEGAN ;7U
50/50
19.86719.867
274683WAUKEGAN ;8U
Adder
21.4218.207
274861TOP CROP ;1U
50/50
0.630.63
274862TOP CROP ;2U
50/50
1.2021.202
934721AD1-100 C
50/50
5.0615.061
942421AE2-255 C
Adder
2.5988235294117652.209
942422AE2-255 E
Adder
7.7952941176470596.626
959611AF2-252 C
Adder
2.02588235294117651.722
960611AF2-352 C
Adder
2.02588235294117651.722
960612AF2-352 E
Adder
3.03764705882352942.582
274687WILL CNTY;4U
50/50
44.2244.22
926821AC1-168 C
Adder
0.97882352941176460.832
959612AF2-252 E
Adder
3.03764705882352942.582
274847GR RIDGE ;BU
50/50
0.9340.934
274676JOLIET 29;8U
50/50
46.68546.685
936371AD2-047 C
50/50
4.0454.045
938851AE1-113 C
Adder
6.865.831
957372AF2-031 E
50/50
2.2132.213
966442AG1-513 E
50/50
0.8170.817
274674JOLIET 9 ;6U
50/50
17.99517.995
276675AE2-062 E
50/50
0.1410.141
274888KELLY CRK;1U
50/50
1.3011.301
938852AE1-113 E
Adder
24.32235294117647220.674
938862AE1-114 E
Adder
11.4611764705882379.742
293645O22 E2
50/50
4.5074.507
957331AF2-027 C
Adder
2.66941176470588242.269
957332AF2-027 E
Adder
4.0035294117647063.403
959352AF2-226 E
50/50
4.114.11
960281AF2-319 C
50/50
2.742.74
960282AF2-319 E
50/50
4.114.11
294392P-010 E
50/50
5.1945.194
926822AC1-168 E
Adder
6.5682352941176475.583
962012AG1-044 E
Adder
0.060.051
942651AE2-281 C
Adder
0.7317647058823530.622
293061N-015 E
50/50
4.094.09
293519PILOT HIL;1E
50/50
5.2055.205
934722AD1-100 E
50/50
78.72578.725
939322AE1-163 E
Adder
31.4705882352941226.75
944222AF1-090 E
Adder
8.684705882352947.382
946322AF1-296 E
Adder
14.27882352941176512.137
959351AF2-226 C
50/50
2.742.74
966092AG1-478 E
50/50
0.8520.852
276626AG1-044 E
Adder
0.067058823529411770.057
942112AE2-223 E
Adder
11.0670588235294139.407
274675JOLIET 29;7U
50/50
46.68246.682
961502AF2-441 E
50/50
21.17621.176
966091AG1-478 C
50/50
0.5680.568
274871GR RIDGE ;2U
50/50
0.3480.348
293644O22 E1
50/50
3.9353.935
936372AD2-047 E
50/50
19.74719.747
939321AE1-163 C
Adder
5.1235294117647064.355
942111AE2-223 C
Adder
1.65411764705882351.406
942652AE2-281 E
Adder
4.49529411764705963.821
946321AF1-296 C
Adder
3.0505882352941182.593
966441AG1-513 C
50/50
0.5450.545
276627AG1-044 BAT
Adder
0.0117647058823529410.01
957382AF2-032 E
Adder
0.148235294117647080.126
276170Z1-108 E
Adder
3.1294117647058832.66
965913AG1-460 BT
Adder
0.0070588235294117650.006
920272AA2-123 E
Adder
3.07176470588235342.611
990547J1333 G
External Queue
8.86958.8695
991302J1755
External Queue
9.68289.6828
990582J1340
External Queue
5.89225.8922
990662J1358
External Queue
14.341514.3415
990947J1432 G
External Queue
14.957514.9575
991092J1477
External Queue
2.81562.8156
990052J1200
External Queue
0.42270.4227
990512J1326 G
External Queue
5.28785.2878
990647J1355
External Queue
41.608541.6085
990552J1334 G
External Queue
8.86958.8695
990557J1335 G
External Queue
8.86958.8695
990562J1336 G
External Queue
8.86958.8695
990577J1339
External Queue
5.89225.8922

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.26 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1187.12
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
3.7663.766
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
295111SUBLETTE E
80/20
0.5570.557
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
938861AE1-114 C
80/20
2.5552.555
957371AF2-031 C
80/20
0.6360.636
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
270681BRIGHTSTK; R
80/20
0.4980.498
274887PILOT HIL;1U
80/20
0.9460.946
275149KELLYCK ;1E
80/20
3.7863.786
293771O-035 E
80/20
1.3921.392
924048AB2-047 E1
80/20
2.0672.067
937001AD2-134 C
80/20
0.8290.829
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
934721AD1-100 C
80/20
3.8223.822
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
959611AF2-252 C
80/20
1.4511.451
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
990901L-005 E
80/20
2.5642.564
274687WILL CNTY;4U
80/20
32.59232.592
276656AB2-047 C2
80/20
0.3110.311
294401BSHIL;1U E
80/20
1.7331.733
925772AC1-053 E
80/20
3.953.95
926821AC1-168 C
80/20
0.7420.742
927208AC1-214 E1
80/20
0.660.66
959612AF2-252 E
80/20
2.1762.176
274864CAYUGA RI;2U
80/20
0.5160.516
274847GR RIDGE ;BU
80/20
0.730.73
274849CRESCENT ;1U
80/20
0.2120.212
274857BIG SKY ;U1
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274872LEE DEKAL;1U
80/20
0.9950.995
276621X2-022 GEN
80/20
2.5362.536
293061N-015 E
80/20
3.1963.196
293519PILOT HIL;1E
80/20
3.7863.786
924049AB2-047 E2
80/20
2.0992.099
934722AD1-100 E
80/20
59.4559.45
939322AE1-163 E
80/20
25.49625.496
946322AF1-296 E
80/20
10.73910.739
959351AF2-226 C
80/20
1.9641.964
966092AG1-478 E
80/20
0.6470.647
274676JOLIET 29;8U
80/20
36.23736.237
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
936371AD2-047 C
80/20
2.9422.942
938851AE1-113 C
80/20
5.2345.234
957372AF2-031 E
80/20
0.9540.954
965331AG1-398 C
80/20
0.1690.169
966442AG1-513 E
80/20
0.6290.629
274674JOLIET 9 ;6U
80/20
13.64413.644
274890CAYUG;1U E
80/20
2.7522.752
276602WESTBROOK C
80/20
0.1730.173
276675AE2-062 E
80/20
0.1120.112
942651AE2-281 C
80/20
0.5930.593
270839OTTER CRK; R
80/20
0.5410.541
274888KELLY CRK;1U
80/20
0.9460.946
293716O-029 E
80/20
1.081.08
937002AD2-134 E
80/20
3.3123.312
938852AE1-113 E
80/20
18.55518.555
938862AE1-114 E
80/20
8.7168.716
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274881WALNUT RG;1U
80/20
0.9520.952
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293717O-029 E
80/20
0.9930.993
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959352AF2-226 E
80/20
2.9452.945
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
276655AB2-047 C1
80/20
0.3110.311
294392P-010 E
80/20
4.0594.059
294410BSHIL;2U E
80/20
1.7331.733
918052AA1-018 E OP
80/20
3.6223.622
926822AC1-168 E
80/20
4.9814.981
927209AC1-214 E2
80/20
0.660.66
965791AG1-447 C
80/20
46.67646.676
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
925771AC1-053 C
80/20
0.590.59
962012AG1-044 E
80/20
0.0450.045
274878BISHOP HL;2U
80/20
0.4330.433
276626AG1-044 E
80/20
0.0510.051
917502Z2-087 E
80/20
3.3333.333
942112AE2-223 E
80/20
7.9997.999
274848CAMPGROVE;RU
80/20
0.2780.278
274850MENDOTA H;RU
80/20
0.3520.352
274856ECOGROVE ;U1
80/20
0.4620.462
274858BIG SKY ;U2
80/20
0.3530.353
274871GR RIDGE ;2U
80/20
0.2720.272
274877BISHOP HL;1U
80/20
0.4330.433
276615W2-048 GEN
80/20
0.8910.891
293516O-009 E
80/20
3.8093.809
293644O22 E1
80/20
2.822.82
924266AB2-070 E
80/20
2.272.27
936372AD2-047 E
80/20
14.36514.365
939321AE1-163 C
80/20
4.1514.151
942111AE2-223 C
80/20
1.1951.195
942652AE2-281 E
80/20
3.6423.642
946321AF1-296 C
80/20
2.2942.294
966441AG1-513 C
80/20
0.4190.419
274675JOLIET 29;7U
80/20
36.25136.251
274860EASYR;U2 E
80/20
2.4372.437
276156O-029 C
80/20
0.2490.249
290021O50 E
80/20
3.9653.965
961502AF2-441 E
80/20
10.40210.402
966091AG1-478 C
80/20
0.4310.431
274891CAYUG;2U E
80/20
2.7522.752
276603SUBLETTE C
80/20
0.0780.078
276668AB2-070 C
80/20
0.3750.375
276627AG1-044 BAT
80/20
0.0090.009
935141AD1-148 C
80/20
0.7970.797
920272AA2-123 E
80/20
22
276170Z1-108 E
80/20
2.0422.042
991302J1755
External Queue
8.07698.0769
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.21 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1186.7
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
3.7663.766
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
295111SUBLETTE E
80/20
0.5570.557
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
938861AE1-114 C
80/20
2.5552.555
957371AF2-031 C
80/20
0.6360.636
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
270681BRIGHTSTK; R
80/20
0.4980.498
274887PILOT HIL;1U
80/20
0.9460.946
275149KELLYCK ;1E
80/20
3.7863.786
293771O-035 E
80/20
1.3921.392
924048AB2-047 E1
80/20
2.0672.067
937001AD2-134 C
80/20
0.8290.829
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
934721AD1-100 C
80/20
3.8223.822
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
959611AF2-252 C
80/20
1.4511.451
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
990901L-005 E
80/20
2.5642.564
274687WILL CNTY;4U
80/20
32.59232.592
276656AB2-047 C2
80/20
0.3110.311
294401BSHIL;1U E
80/20
1.7331.733
925772AC1-053 E
80/20
3.953.95
926821AC1-168 C
80/20
0.7420.742
927208AC1-214 E1
80/20
0.660.66
959612AF2-252 E
80/20
2.1762.176
274847GR RIDGE ;BU
80/20
0.730.73
274849CRESCENT ;1U
80/20
0.2120.212
274857BIG SKY ;U1
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274872LEE DEKAL;1U
80/20
0.9950.995
276621X2-022 GEN
80/20
2.5362.536
293061N-015 E
80/20
3.1963.196
293519PILOT HIL;1E
80/20
3.7863.786
924049AB2-047 E2
80/20
2.0992.099
934722AD1-100 E
80/20
59.4559.45
939322AE1-163 E
80/20
25.49625.496
946322AF1-296 E
80/20
10.73910.739
959351AF2-226 C
80/20
1.9641.964
966092AG1-478 E
80/20
0.6470.647
274676JOLIET 29;8U
80/20
36.23736.237
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
936371AD2-047 C
80/20
2.9422.942
938851AE1-113 C
80/20
5.2345.234
957372AF2-031 E
80/20
0.9540.954
965331AG1-398 C
80/20
0.1690.169
966442AG1-513 E
80/20
0.6290.629
274674JOLIET 9 ;6U
80/20
13.64413.644
274890CAYUG;1U E
80/20
2.7522.752
276602WESTBROOK C
80/20
0.1730.173
276675AE2-062 E
80/20
0.1120.112
942651AE2-281 C
80/20
0.5930.593
270839OTTER CRK; R
80/20
0.5410.541
274888KELLY CRK;1U
80/20
0.9460.946
293716O-029 E
80/20
1.081.08
937002AD2-134 E
80/20
3.3123.312
938852AE1-113 E
80/20
18.55518.555
938862AE1-114 E
80/20
8.7168.716
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274881WALNUT RG;1U
80/20
0.9520.952
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293717O-029 E
80/20
0.9930.993
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959352AF2-226 E
80/20
2.9452.945
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
274864CAYUGA RI;2U
80/20
0.5160.516
276655AB2-047 C1
80/20
0.3110.311
294392P-010 E
80/20
4.0594.059
294410BSHIL;2U E
80/20
1.7331.733
918052AA1-018 E OP
80/20
3.6223.622
926822AC1-168 E
80/20
4.9814.981
927209AC1-214 E2
80/20
0.660.66
965791AG1-447 C
80/20
46.67646.676
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
925771AC1-053 C
80/20
0.590.59
962012AG1-044 E
80/20
0.0450.045
274878BISHOP HL;2U
80/20
0.4330.433
276626AG1-044 E
80/20
0.0510.051
917502Z2-087 E
80/20
3.3333.333
942112AE2-223 E
80/20
7.9997.999
274848CAMPGROVE;RU
80/20
0.2780.278
274850MENDOTA H;RU
80/20
0.3520.352
274856ECOGROVE ;U1
80/20
0.4620.462
274858BIG SKY ;U2
80/20
0.3530.353
274871GR RIDGE ;2U
80/20
0.2720.272
274877BISHOP HL;1U
80/20
0.4330.433
276615W2-048 GEN
80/20
0.8910.891
293516O-009 E
80/20
3.8093.809
293644O22 E1
80/20
2.822.82
924266AB2-070 E
80/20
2.272.27
936372AD2-047 E
80/20
14.36514.365
939321AE1-163 C
80/20
4.1514.151
942111AE2-223 C
80/20
1.1951.195
942652AE2-281 E
80/20
3.6423.642
946321AF1-296 C
80/20
2.2942.294
966441AG1-513 C
80/20
0.4190.419
274675JOLIET 29;7U
80/20
36.25136.251
274860EASYR;U2 E
80/20
2.4372.437
276156O-029 C
80/20
0.2490.249
290021O50 E
80/20
3.9653.965
961502AF2-441 E
80/20
10.40210.402
966091AG1-478 C
80/20
0.4310.431
274891CAYUG;2U E
80/20
2.7522.752
276603SUBLETTE C
80/20
0.0780.078
276668AB2-070 C
80/20
0.3750.375
276627AG1-044 BAT
80/20
0.0090.009
935141AD1-148 C
80/20
0.7970.797
276170Z1-108 E
80/20
2.0422.042
920272AA2-123 E
80/20
22
991302J1755
External Queue
8.07698.0769
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.87 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1057.12
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
2.5552941176470592.172
957371AF2-031 C
Adder
0.63647058823529420.541
961501AF2-441 C
Adder
6.9341176470588245.894
274887PILOT HIL;1U
50/50
0.9460.946
275149KELLYCK ;1E
50/50
3.7853.785
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
934721AD1-100 C
50/50
3.8213.821
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
959611AF2-252 C
Adder
1.45058823529411771.233
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
274687WILL CNTY;4U
50/50
32.59532.595
926821AC1-168 C
Adder
0.74235294117647070.631
959612AF2-252 E
Adder
2.17647058823529441.85
274847GR RIDGE ;BU
50/50
0.730.73
274676JOLIET 29;8U
50/50
36.23736.237
936371AD2-047 C
50/50
2.9422.942
938851AE1-113 C
Adder
5.2341176470588244.449
957372AF2-031 E
Adder
0.95411764705882360.811
966442AG1-513 E
50/50
0.6290.629
274674JOLIET 9 ;6U
50/50
13.64513.645
276675AE2-062 E
50/50
0.1120.112
270839OTTER CRK; R
50/50
0.5410.541
274888KELLY CRK;1U
50/50
0.9460.946
938852AE1-113 E
Adder
18.5576470588235315.774
938862AE1-114 E
Adder
8.717647058823537.41
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959352AF2-226 E
Adder
2.94588235294117642.504
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
926822AC1-168 E
Adder
4.98117647058823554.234
965791AG1-447 C
50/50
46.67546.675
962012AG1-044 E
Adder
0.044705882352941180.038
942651AE2-281 C
50/50
0.5930.593
293061N-015 E
50/50
3.1963.196
293519PILOT HIL;1E
50/50
3.7853.785
934722AD1-100 E
50/50
59.44459.444
939322AE1-163 E
50/50
25.49625.496
946322AF1-296 E
Adder
10.749.129
959351AF2-226 C
Adder
1.9635294117647061.669
966092AG1-478 E
50/50
0.6470.647
276626AG1-044 E
Adder
0.050588235294117640.043
942112AE2-223 E
Adder
7.9988235294117666.799
274675JOLIET 29;7U
50/50
36.25136.251
961502AF2-441 E
Adder
10.48.84
966091AG1-478 C
50/50
0.4310.431
274871GR RIDGE ;2U
50/50
0.2720.272
936372AD2-047 E
50/50
14.36514.365
939321AE1-163 C
50/50
4.1514.151
942111AE2-223 C
Adder
1.19529411764705881.016
942652AE2-281 E
50/50
3.6423.642
946321AF1-296 C
Adder
2.29411764705882341.95
966441AG1-513 C
50/50
0.420.42
276627AG1-044 BAT
Adder
0.0094117647058823540.008
276170Z1-108 E
50/50
2.0432.043
920272AA2-123 E
Adder
2.35294117647058832
991302J1755
External Queue
8.07698.0769
990947J1432 G
External Queue
12.502512.5025
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.87 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1057.11
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
2.5552941176470592.172
957371AF2-031 C
Adder
0.63647058823529420.541
961501AF2-441 C
Adder
6.9341176470588245.894
274887PILOT HIL;1U
50/50
0.9460.946
275149KELLYCK ;1E
50/50
3.7853.785
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
934721AD1-100 C
50/50
3.8213.821
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
959611AF2-252 C
Adder
1.45058823529411771.233
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
274687WILL CNTY;4U
50/50
32.59532.595
926821AC1-168 C
Adder
0.74235294117647070.631
959612AF2-252 E
Adder
2.17647058823529441.85
274847GR RIDGE ;BU
50/50
0.730.73
274676JOLIET 29;8U
50/50
36.23736.237
936371AD2-047 C
50/50
2.9422.942
938851AE1-113 C
Adder
5.2341176470588244.449
957372AF2-031 E
Adder
0.95411764705882360.811
966442AG1-513 E
50/50
0.6290.629
274674JOLIET 9 ;6U
50/50
13.64513.645
276675AE2-062 E
50/50
0.1120.112
270839OTTER CRK; R
50/50
0.5410.541
274888KELLY CRK;1U
50/50
0.9460.946
938852AE1-113 E
Adder
18.5576470588235315.774
938862AE1-114 E
Adder
8.717647058823537.41
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959352AF2-226 E
Adder
2.94588235294117642.504
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
926822AC1-168 E
Adder
4.98117647058823554.234
965791AG1-447 C
50/50
46.67546.675
962012AG1-044 E
Adder
0.044705882352941180.038
942651AE2-281 C
50/50
0.5930.593
293061N-015 E
50/50
3.1963.196
293519PILOT HIL;1E
50/50
3.7853.785
934722AD1-100 E
50/50
59.44459.444
939322AE1-163 E
50/50
25.49625.496
946322AF1-296 E
Adder
10.749.129
959351AF2-226 C
Adder
1.9635294117647061.669
966092AG1-478 E
50/50
0.6470.647
276626AG1-044 E
Adder
0.050588235294117640.043
942112AE2-223 E
Adder
7.9988235294117666.799
274675JOLIET 29;7U
50/50
36.25136.251
961502AF2-441 E
Adder
10.48.84
966091AG1-478 C
50/50
0.4310.431
274871GR RIDGE ;2U
50/50
0.2720.272
936372AD2-047 E
50/50
14.36514.365
939321AE1-163 C
50/50
4.1514.151
942111AE2-223 C
Adder
1.19529411764705881.016
942652AE2-281 E
50/50
3.6423.642
946321AF1-296 C
Adder
2.29411764705882341.95
966441AG1-513 C
50/50
0.420.42
276627AG1-044 BAT
Adder
0.0094117647058823540.008
920272AA2-123 E
Adder
2.35294117647058832
276170Z1-108 E
50/50
2.0432.043
991302J1755
External Queue
8.07698.0769
990947J1432 G
External Queue
12.502512.5025
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.73 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1619.01
MW Contribution:7.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
4.4614.461
290051GSG-6; E
80/20
2.5672.567
290108LEEDK;1U E
80/20
5.8935.893
290261S-027 E
80/20
3.5093.509
290265S-028 E
80/20
3.4883.488
295111SUBLETTE E
80/20
0.6680.668
925581AC1-033 C
80/20
0.5470.547
925582AC1-033 E
80/20
3.6613.661
938861AE1-114 C
80/20
3.0753.075
957371AF2-031 C
80/20
0.470.47
960261AF2-317 C
80/20
0.4080.408
961501AF2-441 C
80/20
6.2416.241
270681BRIGHTSTK; R
80/20
0.5910.591
274887PILOT HIL;1U
80/20
0.9910.991
275149KELLYCK ;1E
80/20
3.9663.966
293771O-035 E
80/20
1.6711.671
924048AB2-047 E1
80/20
2.4512.451
937001AD2-134 C
80/20
0.9950.995
274682WAUKEGAN ;7U
80/20
18.42518.425
274683WAUKEGAN ;8U
80/20
19.85719.857
274861TOP CROP ;1U
80/20
0.6560.656
274862TOP CROP ;2U
80/20
1.2521.252
274863CAYUGA RI;1U
80/20
0.6120.612
276157O-029 C
80/20
0.5410.541
276158O-029 C
80/20
0.5410.541
934721AD1-100 C
80/20
4.5344.534
942421AE2-255 C
80/20
2.4312.431
942422AE2-255 E
80/20
7.2937.293
959611AF2-252 C
80/20
1.721.72
960611AF2-352 C
80/20
1.721.72
960612AF2-352 E
80/20
2.582.58
990901L-005 E
80/20
3.0863.086
274687WILL CNTY;4U
80/20
41.59241.592
276656AB2-047 C2
80/20
0.3690.369
294401BSHIL;1U E
80/20
2.0852.085
925772AC1-053 E
80/20
4.6814.681
926821AC1-168 C
80/20
0.8910.891
927208AC1-214 E1
80/20
0.7920.792
959612AF2-252 E
80/20
2.582.58
274847GR RIDGE ;BU
80/20
0.8810.881
274849CRESCENT ;1U
80/20
0.2550.255
274857BIG SKY ;U1
80/20
0.4250.425
274859EASYR;U1 E
80/20
2.9342.934
274872LEE DEKAL;1U
80/20
1.1941.194
276621X2-022 GEN
80/20
3.0063.006
293061N-015 E
80/20
3.8593.859
293519PILOT HIL;1E
80/20
3.9663.966
924049AB2-047 E2
80/20
2.492.49
934722AD1-100 E
80/20
70.52170.521
939322AE1-163 E
80/20
27.83427.834
946322AF1-296 E
80/20
12.93112.931
959351AF2-226 C
80/20
2.8532.853
966092AG1-478 E
80/20
0.7280.728
274676JOLIET 29;8U
80/20
44.06544.065
294763P-046 E
80/20
2.3082.308
295109WESTBROOK E
80/20
1.3751.375
936371AD2-047 C
80/20
3.0823.082
938851AE1-113 C
80/20
6.4186.418
957372AF2-031 E
80/20
0.7050.705
965331AG1-398 C
80/20
0.2010.201
966442AG1-513 E
80/20
0.7520.752
274674JOLIET 9 ;6U
80/20
15.24915.249
274890CAYUG;1U E
80/20
3.2643.264
276602WESTBROOK C
80/20
0.2080.208
276675AE2-062 E
80/20
0.1250.125
942651AE2-281 C
80/20
0.6470.647
270839OTTER CRK; R
80/20
0.5660.566
274888KELLY CRK;1U
80/20
0.9910.991
293716O-029 E
80/20
1.31.3
937002AD2-134 E
80/20
3.9763.976
938852AE1-113 E
80/20
22.75422.754
938862AE1-114 E
80/20
10.49110.491
274851PROVIDENC;RU
80/20
0.270.27
274853TWINGROVE;U1
80/20
0.7480.748
274854TWINGROVE;U2
80/20
0.770.77
274855GSG-6 ;RU
80/20
0.6420.642
274879MINONK ;1U
80/20
1.2161.216
274880RADFORD R;1U
80/20
0.7810.781
274881WALNUT RG;1U
80/20
1.1461.146
293645O22 E2
80/20
4.6944.694
293715O-029 E
80/20
2.3712.371
293717O-029 E
80/20
1.1951.195
916212CRESCENT ;1U
80/20
1.1741.174
916221Z1-073 E
80/20
1.8091.809
957331AF2-027 C
80/20
2.4722.472
957332AF2-027 E
80/20
3.7083.708
959352AF2-226 E
80/20
4.284.28
960281AF2-319 C
80/20
2.8532.853
960282AF2-319 E
80/20
4.284.28
274864CAYUGA RI;2U
80/20
0.6120.612
276655AB2-047 C1
80/20
0.3690.369
294392P-010 E
80/20
4.9014.901
294410BSHIL;2U E
80/20
2.0852.085
918052AA1-018 E OP
80/20
3.793.79
926822AC1-168 E
80/20
5.9825.982
927209AC1-214 E2
80/20
0.7920.792
276645AC1-214 C1
80/20
0.2230.223
276646AC1-214 C2
80/20
0.2230.223
925771AC1-053 C
80/20
0.70.7
962012AG1-044 E
80/20
0.0540.054
274878BISHOP HL;2U
80/20
0.5210.521
276626AG1-044 E
80/20
0.0610.061
917502Z2-087 E
80/20
3.9533.953
942112AE2-223 E
80/20
9.4879.487
274848CAMPGROVE;RU
80/20
0.3340.334
274850MENDOTA H;RU
80/20
0.4220.422
274856ECOGROVE ;U1
80/20
0.5550.555
274858BIG SKY ;U2
80/20
0.4250.425
274871GR RIDGE ;2U
80/20
0.3280.328
274877BISHOP HL;1U
80/20
0.5210.521
276615W2-048 GEN
80/20
1.0561.056
293516O-009 E
80/20
4.5854.585
293644O22 E1
80/20
4.0984.098
924266AB2-070 E
80/20
2.692.69
936372AD2-047 E
80/20
15.04615.046
939321AE1-163 C
80/20
4.5314.531
274675JOLIET 29;7U
80/20
44.03844.038
274860EASYR;U2 E
80/20
2.9342.934
276156O-029 C
80/20
0.30.3
290021O50 E
80/20
4.8624.862
961502AF2-441 E
80/20
9.3619.361
966091AG1-478 C
80/20
0.4850.485
942111AE2-223 C
80/20
1.4181.418
942652AE2-281 E
80/20
3.9763.976
946321AF1-296 C
80/20
2.7622.762
966441AG1-513 C
80/20
0.5010.501
274891CAYUG;2U E
80/20
3.2643.264
276603SUBLETTE C
80/20
0.0940.094
276668AB2-070 C
80/20
0.4440.444
276627AG1-044 BAT
80/20
0.0110.011
935141AD1-148 C
80/20
0.9450.945
957382AF2-032 E
80/20
0.1170.117
276170Z1-108 E
80/20
2.4582.458
965913AG1-460 BT
80/20
0.0060.006
920272AA2-123 E
80/20
2.4072.407
991302J1755
External Queue
9.86249.8624
990947J1432 G
External Queue
15.3415.34
991092J1477
External Queue
2.88432.8843
990052J1200
External Queue
0.43040.4304
990512J1326 G
External Queue
5.43125.4312

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.64 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1617.84
MW Contribution:7.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
4.4614.461
290051GSG-6; E
80/20
2.5672.567
290108LEEDK;1U E
80/20
5.8935.893
290261S-027 E
80/20
3.5093.509
290265S-028 E
80/20
3.4883.488
295111SUBLETTE E
80/20
0.6680.668
925581AC1-033 C
80/20
0.5470.547
925582AC1-033 E
80/20
3.6613.661
938861AE1-114 C
80/20
3.0753.075
957371AF2-031 C
80/20
0.470.47
960261AF2-317 C
80/20
0.4080.408
961501AF2-441 C
80/20
6.2416.241
270681BRIGHTSTK; R
80/20
0.5910.591
274887PILOT HIL;1U
80/20
0.9910.991
275149KELLYCK ;1E
80/20
3.9663.966
293771O-035 E
80/20
1.6711.671
924048AB2-047 E1
80/20
2.4512.451
937001AD2-134 C
80/20
0.9950.995
274682WAUKEGAN ;7U
80/20
18.42518.425
274683WAUKEGAN ;8U
80/20
19.85719.857
274861TOP CROP ;1U
80/20
0.6560.656
274862TOP CROP ;2U
80/20
1.2521.252
274863CAYUGA RI;1U
80/20
0.6120.612
276157O-029 C
80/20
0.5410.541
276158O-029 C
80/20
0.5410.541
934721AD1-100 C
80/20
4.5344.534
942421AE2-255 C
80/20
2.4312.431
942422AE2-255 E
80/20
7.2937.293
959611AF2-252 C
80/20
1.721.72
960611AF2-352 C
80/20
1.721.72
960612AF2-352 E
80/20
2.582.58
990901L-005 E
80/20
3.0863.086
274687WILL CNTY;4U
80/20
41.59241.592
276656AB2-047 C2
80/20
0.3690.369
294401BSHIL;1U E
80/20
2.0852.085
925772AC1-053 E
80/20
4.6814.681
926821AC1-168 C
80/20
0.8910.891
927208AC1-214 E1
80/20
0.7920.792
959612AF2-252 E
80/20
2.582.58
274847GR RIDGE ;BU
80/20
0.8810.881
274849CRESCENT ;1U
80/20
0.2550.255
274857BIG SKY ;U1
80/20
0.4250.425
274859EASYR;U1 E
80/20
2.9342.934
274676JOLIET 29;8U
80/20
44.06544.065
294763P-046 E
80/20
2.3082.308
295109WESTBROOK E
80/20
1.3751.375
936371AD2-047 C
80/20
3.0823.082
938851AE1-113 C
80/20
6.4186.418
957372AF2-031 E
80/20
0.7050.705
965331AG1-398 C
80/20
0.2010.201
966442AG1-513 E
80/20
0.7520.752
274674JOLIET 9 ;6U
80/20
15.24915.249
274890CAYUG;1U E
80/20
3.2643.264
276602WESTBROOK C
80/20
0.2080.208
276675AE2-062 E
80/20
0.1250.125
942651AE2-281 C
80/20
0.6470.647
270839OTTER CRK; R
80/20
0.5660.566
274888KELLY CRK;1U
80/20
0.9910.991
293716O-029 E
80/20
1.31.3
937002AD2-134 E
80/20
3.9763.976
938852AE1-113 E
80/20
22.75422.754
938862AE1-114 E
80/20
10.49110.491
274851PROVIDENC;RU
80/20
0.270.27
274853TWINGROVE;U1
80/20
0.7480.748
274854TWINGROVE;U2
80/20
0.770.77
274855GSG-6 ;RU
80/20
0.6420.642
274879MINONK ;1U
80/20
1.2161.216
274880RADFORD R;1U
80/20
0.7810.781
274881WALNUT RG;1U
80/20
1.1461.146
293645O22 E2
80/20
4.6944.694
293715O-029 E
80/20
2.3712.371
293717O-029 E
80/20
1.1951.195
916212CRESCENT ;1U
80/20
1.1741.174
916221Z1-073 E
80/20
1.8091.809
957331AF2-027 C
80/20
2.4722.472
957332AF2-027 E
80/20
3.7083.708
959352AF2-226 E
80/20
4.284.28
960281AF2-319 C
80/20
2.8532.853
960282AF2-319 E
80/20
4.284.28
274864CAYUGA RI;2U
80/20
0.6120.612
276655AB2-047 C1
80/20
0.3690.369
294392P-010 E
80/20
4.9014.901
294410BSHIL;2U E
80/20
2.0852.085
918052AA1-018 E OP
80/20
3.793.79
926822AC1-168 E
80/20
5.9825.982
927209AC1-214 E2
80/20
0.7920.792
276645AC1-214 C1
80/20
0.2230.223
276646AC1-214 C2
80/20
0.2230.223
925771AC1-053 C
80/20
0.70.7
962012AG1-044 E
80/20
0.0540.054
274872LEE DEKAL;1U
80/20
1.1941.194
276621X2-022 GEN
80/20
3.0063.006
293061N-015 E
80/20
3.8593.859
293519PILOT HIL;1E
80/20
3.9663.966
924049AB2-047 E2
80/20
2.492.49
934722AD1-100 E
80/20
70.52170.521
939322AE1-163 E
80/20
27.83427.834
946322AF1-296 E
80/20
12.93112.931
959351AF2-226 C
80/20
2.8532.853
966092AG1-478 E
80/20
0.7280.728
274878BISHOP HL;2U
80/20
0.5210.521
276626AG1-044 E
80/20
0.0610.061
917502Z2-087 E
80/20
3.9533.953
942112AE2-223 E
80/20
9.4879.487
274848CAMPGROVE;RU
80/20
0.3340.334
274850MENDOTA H;RU
80/20
0.4220.422
274856ECOGROVE ;U1
80/20
0.5550.555
274858BIG SKY ;U2
80/20
0.4250.425
274871GR RIDGE ;2U
80/20
0.3280.328
274877BISHOP HL;1U
80/20
0.5210.521
276615W2-048 GEN
80/20
1.0561.056
293516O-009 E
80/20
4.5854.585
274675JOLIET 29;7U
80/20
44.03844.038
274860EASYR;U2 E
80/20
2.9342.934
276156O-029 C
80/20
0.30.3
290021O50 E
80/20
4.8624.862
961502AF2-441 E
80/20
9.3619.361
966091AG1-478 C
80/20
0.4850.485
293644O22 E1
80/20
4.0984.098
924266AB2-070 E
80/20
2.692.69
936372AD2-047 E
80/20
15.04615.046
939321AE1-163 C
80/20
4.5314.531
942111AE2-223 C
80/20
1.4181.418
942652AE2-281 E
80/20
3.9763.976
946321AF1-296 C
80/20
2.7622.762
966441AG1-513 C
80/20
0.5010.501
274891CAYUG;2U E
80/20
3.2643.264
276603SUBLETTE C
80/20
0.0940.094
276668AB2-070 C
80/20
0.4440.444
276627AG1-044 BAT
80/20
0.0110.011
935141AD1-148 C
80/20
0.9450.945
957382AF2-032 E
80/20
0.1170.117
276170Z1-108 E
80/20
2.4582.458
920272AA2-123 E
80/20
2.4072.407
965913AG1-460 BT
80/20
0.0060.006
991302J1755
External Queue
9.86249.8624
990947J1432 G
External Queue
15.3415.34
991092J1477
External Queue
2.88432.8843
990052J1200
External Queue
0.43040.4304
990512J1326 G
External Queue
5.43125.4312

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.82 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1452.46
MW Contribution:7.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
3.06235294117647072.603
957371AF2-031 C
Adder
0.462352941176470630.393
961501AF2-441 C
Adder
6.16352941176470555.239
274682WAUKEGAN ;7U
50/50
18.33318.333
274683WAUKEGAN ;8U
50/50
19.75819.758
274861TOP CROP ;1U
50/50
0.6530.653
274862TOP CROP ;2U
50/50
1.2461.246
934721AD1-100 C
50/50
4.5094.509
942421AE2-255 C
50/50
2.422.42
942422AE2-255 E
50/50
7.2617.261
959611AF2-252 C
Adder
1.721.462
960611AF2-352 C
Adder
1.721.462
960612AF2-352 E
Adder
2.582.193
274687WILL CNTY;4U
50/50
41.36241.362
926821AC1-168 C
Adder
0.88823529411764710.755
959612AF2-252 E
Adder
2.582.193
274847GR RIDGE ;BU
50/50
0.8770.877
274676JOLIET 29;8U
50/50
43.82443.824
936371AD2-047 C
Adder
3.0611764705882352.602
938851AE1-113 C
50/50
6.3896.389
957372AF2-031 E
Adder
0.69294117647058820.589
966442AG1-513 E
50/50
0.7480.748
274674JOLIET 9 ;6U
Adder
15.1576470588235312.884
944221AF1-090 C
Adder
1.41647058823529411.204
938852AE1-113 E
50/50
22.65322.653
938862AE1-114 E
Adder
10.4482352941176488.881
274879MINONK ;1U
50/50
1.211.21
293645O22 E2
50/50
4.6734.673
957331AF2-027 C
50/50
2.462.46
957332AF2-027 E
50/50
3.693.69
959352AF2-226 E
50/50
4.2614.261
960281AF2-319 C
50/50
2.8412.841
960282AF2-319 E
50/50
4.2614.261
294392P-010 E
50/50
4.8764.876
926822AC1-168 E
Adder
5.9611764705882365.067
962012AG1-044 E
Adder
0.054117647058823530.046
276675AE2-062 E
50/50
0.1240.124
942651AE2-281 C
Adder
0.64352941176470590.547
293061N-015 E
50/50
3.8393.839
934722AD1-100 E
50/50
70.13470.134
939322AE1-163 E
Adder
27.69647058823529723.542
944222AF1-090 E
Adder
6.6294117647058825.635
946322AF1-296 E
Adder
12.8905882352941210.957
959351AF2-226 C
50/50
2.8412.841
966092AG1-478 E
50/50
0.7240.724
276626AG1-044 E
Adder
0.061176470588235290.052
942112AE2-223 E
Adder
9.4776470588235288.056
274675JOLIET 29;7U
50/50
43.79843.798
290021O50 E
50/50
4.844.84
961502AF2-441 E
Adder
9.2458823529411777.859
966091AG1-478 C
50/50
0.4820.482
274871GR RIDGE ;2U
50/50
0.3260.326
293644O22 E1
50/50
4.084.08
936372AD2-047 E
Adder
14.94235294117647212.701
939321AE1-163 C
Adder
4.5094117647058833.833
942111AE2-223 C
Adder
1.41647058823529411.204
942652AE2-281 E
Adder
3.9564705882352943.363
946321AF1-296 C
Adder
2.7541176470588242.341
966441AG1-513 C
50/50
0.4990.499
276627AG1-044 BAT
Adder
0.0105882352941176470.009
957382AF2-032 E
Adder
0.117647058823529420.1
276170Z1-108 E
50/50
2.4462.446
920272AA2-123 E
Adder
2.81764705882352962.395
965913AG1-460 BT
Adder
0.00588235294117647050.005
991302J1755
External Queue
9.81979.8197
990947J1432 G
External Queue
15.277515.2775
991092J1477
External Queue
2.87522.8752
990052J1200
External Queue
0.42840.4284
990512J1326 G
External Queue
5.40125.4012

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.92 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1439.81
MW Contribution:7.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
3.07647058823529432.615
957371AF2-031 C
Adder
0.46941176470588240.399
961501AF2-441 C
Adder
6.2364705882352955.301
274682WAUKEGAN ;7U
50/50
18.43518.435
274683WAUKEGAN ;8U
50/50
19.86819.868
274861TOP CROP ;1U
50/50
0.6560.656
274862TOP CROP ;2U
50/50
1.2521.252
934721AD1-100 C
50/50
4.5314.531
942421AE2-255 C
50/50
2.4322.432
942422AE2-255 E
50/50
7.2957.295
959611AF2-252 C
Adder
1.721.462
960611AF2-352 C
Adder
1.721.462
960612AF2-352 E
Adder
2.582.193
274687WILL CNTY;4U
50/50
41.59841.598
926821AC1-168 C
Adder
0.8917647058823530.758
959612AF2-252 E
Adder
2.582.193
274676JOLIET 29;8U
50/50
44.07844.078
936371AD2-047 C
Adder
3.08117647058823562.619
938851AE1-113 C
50/50
6.426.42
957372AF2-031 E
Adder
0.70470588235294120.599
966442AG1-513 E
50/50
0.7530.753
274674JOLIET 9 ;6U
Adder
15.25411764705882312.966
938852AE1-113 E
50/50
22.76222.762
938862AE1-114 E
Adder
10.497647058823538.923
274879MINONK ;1U
50/50
1.2161.216
293645O22 E2
50/50
4.6944.694
957331AF2-027 C
50/50
2.4742.474
957332AF2-027 E
50/50
3.713.71
959352AF2-226 E
50/50
4.284.28
960281AF2-319 C
50/50
2.8532.853
960282AF2-319 E
50/50
4.284.28
294392P-010 E
50/50
4.9034.903
926822AC1-168 E
Adder
5.9847058823529415.087
962012AG1-044 E
Adder
0.054117647058823530.046
276675AE2-062 E
50/50
0.1250.125
942651AE2-281 C
Adder
0.64705882352941180.55
274847GR RIDGE ;BU
50/50
0.8810.881
293061N-015 E
50/50
3.863.86
934722AD1-100 E
50/50
70.47670.476
939322AE1-163 E
Adder
27.83882352941176623.663
946322AF1-296 E
Adder
12.93882352941176410.998
959351AF2-226 C
50/50
2.8532.853
966092AG1-478 E
50/50
0.7280.728
276626AG1-044 E
Adder
0.061176470588235290.052
942112AE2-223 E
Adder
9.4870588235294138.064
274675JOLIET 29;7U
50/50
44.05244.052
290021O50 E
50/50
4.8644.864
961502AF2-441 E
Adder
9.3552941176470597.952
966091AG1-478 C
50/50
0.4850.485
274871GR RIDGE ;2U
50/50
0.3280.328
293644O22 E1
50/50
4.0984.098
936372AD2-047 E
Adder
15.04117647058823512.785
939321AE1-163 C
Adder
4.53176470588235253.852
942111AE2-223 C
Adder
1.41764705882352951.205
942652AE2-281 E
Adder
3.9764705882352943.38
946321AF1-296 C
Adder
2.7635294117647062.349
966441AG1-513 C
50/50
0.5020.502
276627AG1-044 BAT
Adder
0.0105882352941176470.009
957382AF2-032 E
Adder
0.117647058823529420.1
920272AA2-123 E
Adder
2.83294117647058832.408
965913AG1-460 BT
Adder
0.00588235294117647050.005
276170Z1-108 E
50/50
2.462.46
991302J1755
External Queue
9.86539.8653
990947J1432 G
External Queue
15.3515.35
991092J1477
External Queue
2.88632.8863
990052J1200
External Queue
0.43050.4305
990512J1326 G
External Queue
5.4355.435

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.53 %
Rating:1091.0 MVA
Rating Type:A
MVA to Mitigate:1096.79
MW Contribution:5.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
290051GSG-6; E
80/20
1.6851.685
290108LEEDK;1U E
80/20
3.8583.858
290261S-027 E
80/20
2.2852.285
290265S-028 E
80/20
2.2712.271
295111SUBLETTE E
80/20
0.4390.439
925581AC1-033 C
80/20
0.3660.366
925582AC1-033 E
80/20
2.4492.449
938861AE1-114 C
80/20
2.0372.037
270681BRIGHTSTK; R
80/20
0.3850.385
274887PILOT HIL;1U
80/20
0.6450.645
275149KELLYCK ;1E
80/20
2.5792.579
293771O-035 E
80/20
1.1181.118
924048AB2-047 E1
80/20
1.5971.597
937001AD2-134 C
80/20
0.6530.653
274682WAUKEGAN ;7U
80/20
12.37312.373
274683WAUKEGAN ;8U
80/20
13.33213.332
274861TOP CROP ;1U
80/20
0.4840.484
274862TOP CROP ;2U
80/20
0.9230.923
274863CAYUGA RI;1U
80/20
0.4010.401
276157O-029 C
80/20
0.3590.359
276158O-029 C
80/20
0.3590.359
934721AD1-100 C
80/20
2.9882.988
942421AE2-255 C
80/20
1.6741.674
942422AE2-255 E
80/20
5.0235.023
959611AF2-252 C
80/20
1.121.12
960611AF2-352 C
80/20
1.121.12
960612AF2-352 E
80/20
1.681.68
990901L-005 E
80/20
2.0672.067
274687WILL CNTY;4U
80/20
29.39129.391
276656AB2-047 C2
80/20
0.240.24
294401BSHIL;1U E
80/20
1.3951.395
926821AC1-168 C
80/20
0.5960.596
927208AC1-214 E1
80/20
0.530.53
959612AF2-252 E
80/20
1.681.68
274847GR RIDGE ;BU
80/20
0.5850.585
274849CRESCENT ;1U
80/20
0.170.17
274857BIG SKY ;U1
80/20
0.2820.282
274859EASYR;U1 E
80/20
1.9441.944
274872LEE DEKAL;1U
80/20
0.7810.781
293061N-015 E
80/20
2.5612.561
293519PILOT HIL;1E
80/20
2.5792.579
924049AB2-047 E2
80/20
1.6221.622
934722AD1-100 E
80/20
46.47446.474
939322AE1-163 E
80/20
18.9218.92
946322AF1-296 E
80/20
8.5868.586
959351AF2-226 C
80/20
2.1042.104
966092AG1-478 E
80/20
0.4880.488
274676JOLIET 29;8U
80/20
30.59430.594
294763P-046 E
80/20
1.5291.529
295109WESTBROOK E
80/20
0.9020.902
936371AD2-047 C
80/20
2.0042.004
938851AE1-113 C
80/20
4.424.42
966442AG1-513 E
80/20
0.4920.492
274674JOLIET 9 ;6U
80/20
10.08310.083
274890CAYUG;1U E
80/20
2.1372.137
276602WESTBROOK C
80/20
0.1370.137
276675AE2-062 E
80/20
0.0850.085
942651AE2-281 C
80/20
0.440.44
270839OTTER CRK; R
80/20
0.3830.383
274888KELLY CRK;1U
80/20
0.6450.645
293716O-029 E
80/20
0.8630.863
937002AD2-134 E
80/20
2.612.61
938852AE1-113 E
80/20
15.67215.672
938862AE1-114 E
80/20
6.9496.949
274851PROVIDENC;RU
80/20
0.1810.181
274853TWINGROVE;U1
80/20
0.4870.487
274854TWINGROVE;U2
80/20
0.5010.501
274855GSG-6 ;RU
80/20
0.4210.421
274879MINONK ;1U
80/20
0.8370.837
274881WALNUT RG;1U
80/20
0.7610.761
293645O22 E2
80/20
3.4613.461
293715O-029 E
80/20
1.5751.575
293717O-029 E
80/20
0.7940.794
916212CRESCENT ;1U
80/20
0.7850.785
916221Z1-073 E
80/20
1.1881.188
957331AF2-027 C
80/20
1.6591.659
957332AF2-027 E
80/20
2.4882.488
959352AF2-226 E
80/20
3.1563.156
960281AF2-319 C
80/20
2.1042.104
960282AF2-319 E
80/20
3.1563.156
274864CAYUGA RI;2U
80/20
0.4010.401
276655AB2-047 C1
80/20
0.240.24
294392P-010 E
80/20
3.2533.253
294410BSHIL;2U E
80/20
1.3951.395
918052AA1-018 E OP
80/20
2.5632.563
926822AC1-168 E
80/20
44
927209AC1-214 E2
80/20
0.530.53
276645AC1-214 C1
80/20
0.1490.149
276646AC1-214 C2
80/20
0.1490.149
962012AG1-044 E
80/20
0.0360.036
274878BISHOP HL;2U
80/20
0.3490.349
276626AG1-044 E
80/20
0.0410.041
917502Z2-087 E
80/20
2.5752.575
942112AE2-223 E
80/20
6.1816.181
274848CAMPGROVE;RU
80/20
0.2240.224
274850MENDOTA H;RU
80/20
0.2770.277
274856ECOGROVE ;U1
80/20
0.3680.368
274858BIG SKY ;U2
80/20
0.2820.282
274871GR RIDGE ;2U
80/20
0.2180.218
274877BISHOP HL;1U
80/20
0.3490.349
293516O-009 E
80/20
3.0453.045
293644O22 E1
80/20
3.0223.022
936372AD2-047 E
80/20
9.7859.785
939321AE1-163 C
80/20
3.083.08
274675JOLIET 29;7U
80/20
30.56830.568
274860EASYR;U2 E
80/20
1.9441.944
276156O-029 C
80/20
0.1990.199
290021O50 E
80/20
3.3493.349
966091AG1-478 C
80/20
0.3250.325
942111AE2-223 C
80/20
0.9230.923
942652AE2-281 E
80/20
2.7032.703
946321AF1-296 C
80/20
1.8341.834
966441AG1-513 C
80/20
0.3280.328
274891CAYUG;2U E
80/20
2.1372.137
276603SUBLETTE C
80/20
0.0620.062
276627AG1-044 BAT
80/20
0.0070.007
920272AA2-123 E
80/20
1.5961.596
276170Z1-108 E
80/20
1.6321.632

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.75 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1619.4
MW Contribution:7.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
4.4614.461
290051GSG-6; E
80/20
2.5672.567
290108LEEDK;1U E
80/20
5.8935.893
290261S-027 E
80/20
3.5093.509
290265S-028 E
80/20
3.4883.488
295111SUBLETTE E
80/20
0.6680.668
925581AC1-033 C
80/20
0.5470.547
925582AC1-033 E
80/20
3.6613.661
938861AE1-114 C
80/20
3.0753.075
957371AF2-031 C
80/20
0.470.47
960261AF2-317 C
80/20
0.4080.408
961501AF2-441 C
80/20
6.2416.241
270681BRIGHTSTK; R
80/20
0.5910.591
274887PILOT HIL;1U
80/20
0.9910.991
275149KELLYCK ;1E
80/20
3.9663.966
293771O-035 E
80/20
1.6711.671
924048AB2-047 E1
80/20
2.4512.451
937001AD2-134 C
80/20
0.9950.995
274682WAUKEGAN ;7U
80/20
18.42518.425
274683WAUKEGAN ;8U
80/20
19.85719.857
274861TOP CROP ;1U
80/20
0.6560.656
274862TOP CROP ;2U
80/20
1.2521.252
274863CAYUGA RI;1U
80/20
0.6120.612
276157O-029 C
80/20
0.5410.541
276158O-029 C
80/20
0.5410.541
934721AD1-100 C
80/20
4.5344.534
942421AE2-255 C
80/20
2.4312.431
942422AE2-255 E
80/20
7.2937.293
959611AF2-252 C
80/20
1.721.72
960611AF2-352 C
80/20
1.721.72
960612AF2-352 E
80/20
2.582.58
990901L-005 E
80/20
3.0863.086
274687WILL CNTY;4U
80/20
41.59241.592
276656AB2-047 C2
80/20
0.3690.369
294401BSHIL;1U E
80/20
2.0852.085
925772AC1-053 E
80/20
4.6814.681
926821AC1-168 C
80/20
0.8910.891
927208AC1-214 E1
80/20
0.7920.792
959612AF2-252 E
80/20
2.582.58
274847GR RIDGE ;BU
80/20
0.8810.881
274849CRESCENT ;1U
80/20
0.2550.255
274857BIG SKY ;U1
80/20
0.4250.425
274859EASYR;U1 E
80/20
2.9342.934
274872LEE DEKAL;1U
80/20
1.1941.194
276621X2-022 GEN
80/20
3.0063.006
293061N-015 E
80/20
3.8593.859
293519PILOT HIL;1E
80/20
3.9663.966
924049AB2-047 E2
80/20
2.492.49
934722AD1-100 E
80/20
70.52170.521
939322AE1-163 E
80/20
27.83427.834
946322AF1-296 E
80/20
12.93112.931
959351AF2-226 C
80/20
2.8532.853
966092AG1-478 E
80/20
0.7280.728
274676JOLIET 29;8U
80/20
44.06544.065
294763P-046 E
80/20
2.3082.308
295109WESTBROOK E
80/20
1.3751.375
936371AD2-047 C
80/20
3.0823.082
938851AE1-113 C
80/20
6.4186.418
957372AF2-031 E
80/20
0.7050.705
965331AG1-398 C
80/20
0.2010.201
966442AG1-513 E
80/20
0.7520.752
274674JOLIET 9 ;6U
80/20
15.24915.249
274890CAYUG;1U E
80/20
3.2643.264
276602WESTBROOK C
80/20
0.2080.208
276675AE2-062 E
80/20
0.1250.125
942651AE2-281 C
80/20
0.6470.647
270839OTTER CRK; R
80/20
0.5660.566
274888KELLY CRK;1U
80/20
0.9910.991
293716O-029 E
80/20
1.31.3
937002AD2-134 E
80/20
3.9763.976
938852AE1-113 E
80/20
22.75422.754
938862AE1-114 E
80/20
10.49110.491
274851PROVIDENC;RU
80/20
0.270.27
274853TWINGROVE;U1
80/20
0.7480.748
274854TWINGROVE;U2
80/20
0.770.77
274855GSG-6 ;RU
80/20
0.6420.642
274879MINONK ;1U
80/20
1.2161.216
274880RADFORD R;1U
80/20
0.7810.781
274881WALNUT RG;1U
80/20
1.1461.146
293645O22 E2
80/20
4.6944.694
293715O-029 E
80/20
2.3712.371
293717O-029 E
80/20
1.1951.195
916212CRESCENT ;1U
80/20
1.1741.174
916221Z1-073 E
80/20
1.8091.809
957331AF2-027 C
80/20
2.4722.472
957332AF2-027 E
80/20
3.7083.708
959352AF2-226 E
80/20
4.284.28
960281AF2-319 C
80/20
2.8532.853
960282AF2-319 E
80/20
4.284.28
274864CAYUGA RI;2U
80/20
0.6120.612
276655AB2-047 C1
80/20
0.3690.369
294392P-010 E
80/20
4.9014.901
294410BSHIL;2U E
80/20
2.0852.085
918052AA1-018 E OP
80/20
3.793.79
926822AC1-168 E
80/20
5.9825.982
927209AC1-214 E2
80/20
0.7920.792
276645AC1-214 C1
80/20
0.2230.223
276646AC1-214 C2
80/20
0.2230.223
925771AC1-053 C
80/20
0.70.7
962012AG1-044 E
80/20
0.0540.054
274878BISHOP HL;2U
80/20
0.5210.521
276626AG1-044 E
80/20
0.0610.061
917502Z2-087 E
80/20
3.9533.953
942112AE2-223 E
80/20
9.4879.487
274848CAMPGROVE;RU
80/20
0.3340.334
274850MENDOTA H;RU
80/20
0.4220.422
274856ECOGROVE ;U1
80/20
0.5550.555
274858BIG SKY ;U2
80/20
0.4250.425
274871GR RIDGE ;2U
80/20
0.3280.328
274877BISHOP HL;1U
80/20
0.5210.521
276615W2-048 GEN
80/20
1.0561.056
293516O-009 E
80/20
4.5854.585
293644O22 E1
80/20
4.0984.098
924266AB2-070 E
80/20
2.692.69
936372AD2-047 E
80/20
15.04615.046
939321AE1-163 C
80/20
4.5314.531
274675JOLIET 29;7U
80/20
44.03844.038
274860EASYR;U2 E
80/20
2.9342.934
276156O-029 C
80/20
0.30.3
290021O50 E
80/20
4.8624.862
961502AF2-441 E
80/20
9.3619.361
966091AG1-478 C
80/20
0.4850.485
942111AE2-223 C
80/20
1.4181.418
942652AE2-281 E
80/20
3.9763.976
946321AF1-296 C
80/20
2.7622.762
966441AG1-513 C
80/20
0.5010.501
274891CAYUG;2U E
80/20
3.2643.264
276603SUBLETTE C
80/20
0.0940.094
276668AB2-070 C
80/20
0.4440.444
276627AG1-044 BAT
80/20
0.0110.011
935141AD1-148 C
80/20
0.9450.945
957382AF2-032 E
80/20
0.1170.117
276170Z1-108 E
80/20
2.4582.458
965913AG1-460 BT
80/20
0.0060.006
920272AA2-123 E
80/20
2.4072.407
991302J1755
External Queue
9.86249.8624
990947J1432 G
External Queue
15.3415.34
991092J1477
External Queue
2.88432.8843
990052J1200
External Queue
0.43040.4304
990512J1326 G
External Queue
5.43125.4312

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1618.22
MW Contribution:7.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
4.4614.461
290051GSG-6; E
80/20
2.5672.567
290108LEEDK;1U E
80/20
5.8935.893
290261S-027 E
80/20
3.5093.509
290265S-028 E
80/20
3.4883.488
295111SUBLETTE E
80/20
0.6680.668
925581AC1-033 C
80/20
0.5470.547
925582AC1-033 E
80/20
3.6613.661
938861AE1-114 C
80/20
3.0753.075
957371AF2-031 C
80/20
0.470.47
960261AF2-317 C
80/20
0.4080.408
961501AF2-441 C
80/20
6.2416.241
270681BRIGHTSTK; R
80/20
0.5910.591
274887PILOT HIL;1U
80/20
0.9910.991
275149KELLYCK ;1E
80/20
3.9663.966
293771O-035 E
80/20
1.6711.671
924048AB2-047 E1
80/20
2.4512.451
937001AD2-134 C
80/20
0.9950.995
274682WAUKEGAN ;7U
80/20
18.42518.425
274683WAUKEGAN ;8U
80/20
19.85719.857
274861TOP CROP ;1U
80/20
0.6560.656
274862TOP CROP ;2U
80/20
1.2521.252
274863CAYUGA RI;1U
80/20
0.6120.612
276157O-029 C
80/20
0.5410.541
276158O-029 C
80/20
0.5410.541
934721AD1-100 C
80/20
4.5344.534
942421AE2-255 C
80/20
2.4312.431
942422AE2-255 E
80/20
7.2937.293
959611AF2-252 C
80/20
1.721.72
960611AF2-352 C
80/20
1.721.72
960612AF2-352 E
80/20
2.582.58
990901L-005 E
80/20
3.0863.086
274687WILL CNTY;4U
80/20
41.59241.592
276656AB2-047 C2
80/20
0.3690.369
294401BSHIL;1U E
80/20
2.0852.085
925772AC1-053 E
80/20
4.6814.681
926821AC1-168 C
80/20
0.8910.891
927208AC1-214 E1
80/20
0.7920.792
959612AF2-252 E
80/20
2.582.58
274847GR RIDGE ;BU
80/20
0.8810.881
274849CRESCENT ;1U
80/20
0.2550.255
274857BIG SKY ;U1
80/20
0.4250.425
274859EASYR;U1 E
80/20
2.9342.934
274676JOLIET 29;8U
80/20
44.06544.065
294763P-046 E
80/20
2.3082.308
295109WESTBROOK E
80/20
1.3751.375
936371AD2-047 C
80/20
3.0823.082
938851AE1-113 C
80/20
6.4186.418
957372AF2-031 E
80/20
0.7050.705
965331AG1-398 C
80/20
0.2010.201
966442AG1-513 E
80/20
0.7520.752
274674JOLIET 9 ;6U
80/20
15.24915.249
274890CAYUG;1U E
80/20
3.2643.264
276602WESTBROOK C
80/20
0.2080.208
276675AE2-062 E
80/20
0.1250.125
942651AE2-281 C
80/20
0.6470.647
270839OTTER CRK; R
80/20
0.5660.566
274888KELLY CRK;1U
80/20
0.9910.991
293716O-029 E
80/20
1.31.3
937002AD2-134 E
80/20
3.9763.976
938852AE1-113 E
80/20
22.75422.754
938862AE1-114 E
80/20
10.49110.491
274851PROVIDENC;RU
80/20
0.270.27
274853TWINGROVE;U1
80/20
0.7480.748
274854TWINGROVE;U2
80/20
0.770.77
274855GSG-6 ;RU
80/20
0.6420.642
274879MINONK ;1U
80/20
1.2161.216
274880RADFORD R;1U
80/20
0.7810.781
274881WALNUT RG;1U
80/20
1.1461.146
293645O22 E2
80/20
4.6944.694
293715O-029 E
80/20
2.3712.371
293717O-029 E
80/20
1.1951.195
916212CRESCENT ;1U
80/20
1.1741.174
916221Z1-073 E
80/20
1.8091.809
957331AF2-027 C
80/20
2.4722.472
957332AF2-027 E
80/20
3.7083.708
959352AF2-226 E
80/20
4.284.28
960281AF2-319 C
80/20
2.8532.853
960282AF2-319 E
80/20
4.284.28
274864CAYUGA RI;2U
80/20
0.6120.612
276655AB2-047 C1
80/20
0.3690.369
294392P-010 E
80/20
4.9014.901
294410BSHIL;2U E
80/20
2.0852.085
918052AA1-018 E OP
80/20
3.793.79
926822AC1-168 E
80/20
5.9825.982
927209AC1-214 E2
80/20
0.7920.792
276645AC1-214 C1
80/20
0.2230.223
276646AC1-214 C2
80/20
0.2230.223
925771AC1-053 C
80/20
0.70.7
962012AG1-044 E
80/20
0.0540.054
274872LEE DEKAL;1U
80/20
1.1941.194
276621X2-022 GEN
80/20
3.0063.006
293061N-015 E
80/20
3.8593.859
293519PILOT HIL;1E
80/20
3.9663.966
924049AB2-047 E2
80/20
2.492.49
934722AD1-100 E
80/20
70.52170.521
939322AE1-163 E
80/20
27.83427.834
946322AF1-296 E
80/20
12.93112.931
959351AF2-226 C
80/20
2.8532.853
966092AG1-478 E
80/20
0.7280.728
274878BISHOP HL;2U
80/20
0.5210.521
276626AG1-044 E
80/20
0.0610.061
917502Z2-087 E
80/20
3.9533.953
942112AE2-223 E
80/20
9.4879.487
274848CAMPGROVE;RU
80/20
0.3340.334
274850MENDOTA H;RU
80/20
0.4220.422
274856ECOGROVE ;U1
80/20
0.5550.555
274858BIG SKY ;U2
80/20
0.4250.425
274871GR RIDGE ;2U
80/20
0.3280.328
274877BISHOP HL;1U
80/20
0.5210.521
276615W2-048 GEN
80/20
1.0561.056
293516O-009 E
80/20
4.5854.585
274675JOLIET 29;7U
80/20
44.03844.038
274860EASYR;U2 E
80/20
2.9342.934
276156O-029 C
80/20
0.30.3
290021O50 E
80/20
4.8624.862
961502AF2-441 E
80/20
9.3619.361
966091AG1-478 C
80/20
0.4850.485
293644O22 E1
80/20
4.0984.098
924266AB2-070 E
80/20
2.692.69
936372AD2-047 E
80/20
15.04615.046
939321AE1-163 C
80/20
4.5314.531
942111AE2-223 C
80/20
1.4181.418
942652AE2-281 E
80/20
3.9763.976
946321AF1-296 C
80/20
2.7622.762
966441AG1-513 C
80/20
0.5010.501
274891CAYUG;2U E
80/20
3.2643.264
276603SUBLETTE C
80/20
0.0940.094
276668AB2-070 C
80/20
0.4440.444
276627AG1-044 BAT
80/20
0.0110.011
935141AD1-148 C
80/20
0.9450.945
957382AF2-032 E
80/20
0.1170.117
276170Z1-108 E
80/20
2.4582.458
920272AA2-123 E
80/20
2.4072.407
965913AG1-460 BT
80/20
0.0060.006
991302J1755
External Queue
9.86249.8624
990947J1432 G
External Queue
15.3415.34
991092J1477
External Queue
2.88432.8843
990052J1200
External Queue
0.43040.4304
990512J1326 G
External Queue
5.43125.4312

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.83 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1452.53
MW Contribution:7.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
3.06235294117647072.603
957371AF2-031 C
Adder
0.462352941176470630.393
961501AF2-441 C
Adder
6.16352941176470555.239
944221AF1-090 C
Adder
1.41647058823529411.204
274682WAUKEGAN ;7U
50/50
18.33318.333
274683WAUKEGAN ;8U
50/50
19.75819.758
274861TOP CROP ;1U
50/50
0.6530.653
274862TOP CROP ;2U
50/50
1.2461.246
934721AD1-100 C
50/50
4.5094.509
942421AE2-255 C
50/50
2.422.42
942422AE2-255 E
50/50
7.2617.261
959611AF2-252 C
Adder
1.721.462
960611AF2-352 C
Adder
1.721.462
960612AF2-352 E
Adder
2.582.193
274687WILL CNTY;4U
50/50
41.36241.362
926821AC1-168 C
Adder
0.88823529411764710.755
959612AF2-252 E
Adder
2.582.193
274847GR RIDGE ;BU
50/50
0.8770.877
274676JOLIET 29;8U
50/50
43.82443.824
936371AD2-047 C
Adder
3.0611764705882352.602
938851AE1-113 C
50/50
6.3896.389
957372AF2-031 E
Adder
0.69294117647058820.589
966442AG1-513 E
50/50
0.7480.748
274674JOLIET 9 ;6U
Adder
15.1576470588235312.884
938852AE1-113 E
50/50
22.65322.653
938862AE1-114 E
Adder
10.4482352941176488.881
274879MINONK ;1U
50/50
1.211.21
293645O22 E2
50/50
4.6734.673
957331AF2-027 C
50/50
2.462.46
957332AF2-027 E
50/50
3.693.69
959352AF2-226 E
50/50
4.2614.261
960281AF2-319 C
50/50
2.8412.841
960282AF2-319 E
50/50
4.2614.261
294392P-010 E
50/50
4.8764.876
926822AC1-168 E
Adder
5.9611764705882365.067
962012AG1-044 E
Adder
0.054117647058823530.046
276675AE2-062 E
50/50
0.1240.124
942651AE2-281 C
Adder
0.64352941176470590.547
293061N-015 E
50/50
3.8393.839
934722AD1-100 E
50/50
70.13470.134
939322AE1-163 E
Adder
27.69647058823529723.542
944222AF1-090 E
Adder
6.6294117647058825.635
946322AF1-296 E
Adder
12.8905882352941210.957
959351AF2-226 C
50/50
2.8412.841
966092AG1-478 E
50/50
0.7240.724
276626AG1-044 E
Adder
0.061176470588235290.052
942112AE2-223 E
Adder
9.4776470588235288.056
274675JOLIET 29;7U
50/50
43.79843.798
290021O50 E
50/50
4.844.84
961502AF2-441 E
Adder
9.2458823529411777.859
966091AG1-478 C
50/50
0.4820.482
274871GR RIDGE ;2U
50/50
0.3260.326
293644O22 E1
50/50
4.084.08
936372AD2-047 E
Adder
14.94235294117647212.701
939321AE1-163 C
Adder
4.5094117647058833.833
942111AE2-223 C
Adder
1.41647058823529411.204
942652AE2-281 E
Adder
3.9564705882352943.363
946321AF1-296 C
Adder
2.7541176470588242.341
966441AG1-513 C
50/50
0.4990.499
276627AG1-044 BAT
Adder
0.0105882352941176470.009
957382AF2-032 E
Adder
0.117647058823529420.1
965913AG1-460 BT
Adder
0.00588235294117647050.005
920272AA2-123 E
Adder
2.81764705882352962.395
276170Z1-108 E
50/50
2.4462.446
991302J1755
External Queue
9.81979.8197
990947J1432 G
External Queue
15.277515.2775
991092J1477
External Queue
2.87522.8752
990052J1200
External Queue
0.42840.4284
990512J1326 G
External Queue
5.40125.4012

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.92 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1439.86
MW Contribution:7.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
3.07647058823529432.615
957371AF2-031 C
Adder
0.46941176470588240.399
961501AF2-441 C
Adder
6.2364705882352955.301
274682WAUKEGAN ;7U
50/50
18.43518.435
274683WAUKEGAN ;8U
50/50
19.86819.868
274861TOP CROP ;1U
50/50
0.6560.656
274862TOP CROP ;2U
50/50
1.2521.252
934721AD1-100 C
50/50
4.5314.531
942421AE2-255 C
50/50
2.4322.432
942422AE2-255 E
50/50
7.2957.295
959611AF2-252 C
Adder
1.721.462
960611AF2-352 C
Adder
1.721.462
960612AF2-352 E
Adder
2.582.193
274687WILL CNTY;4U
50/50
41.59841.598
926821AC1-168 C
Adder
0.8917647058823530.758
959612AF2-252 E
Adder
2.582.193
274847GR RIDGE ;BU
50/50
0.8810.881
274676JOLIET 29;8U
50/50
44.07844.078
936371AD2-047 C
Adder
3.08117647058823562.619
938851AE1-113 C
50/50
6.426.42
957372AF2-031 E
Adder
0.70470588235294120.599
966442AG1-513 E
50/50
0.7530.753
274674JOLIET 9 ;6U
Adder
15.25411764705882312.966
938852AE1-113 E
50/50
22.76222.762
938862AE1-114 E
Adder
10.497647058823538.923
274879MINONK ;1U
50/50
1.2161.216
293645O22 E2
50/50
4.6944.694
957331AF2-027 C
50/50
2.4742.474
957332AF2-027 E
50/50
3.713.71
959352AF2-226 E
50/50
4.284.28
960281AF2-319 C
50/50
2.8532.853
960282AF2-319 E
50/50
4.284.28
294392P-010 E
50/50
4.9034.903
926822AC1-168 E
Adder
5.9847058823529415.087
962012AG1-044 E
Adder
0.054117647058823530.046
276675AE2-062 E
50/50
0.1250.125
942651AE2-281 C
Adder
0.64705882352941180.55
293061N-015 E
50/50
3.863.86
934722AD1-100 E
50/50
70.47670.476
939322AE1-163 E
Adder
27.83882352941176623.663
946322AF1-296 E
Adder
12.93882352941176410.998
959351AF2-226 C
50/50
2.8532.853
966092AG1-478 E
50/50
0.7280.728
276626AG1-044 E
Adder
0.061176470588235290.052
942112AE2-223 E
Adder
9.4870588235294138.064
274675JOLIET 29;7U
50/50
44.05244.052
290021O50 E
50/50
4.8644.864
961502AF2-441 E
Adder
9.3552941176470597.952
966091AG1-478 C
50/50
0.4850.485
274871GR RIDGE ;2U
50/50
0.3280.328
293644O22 E1
50/50
4.0984.098
936372AD2-047 E
Adder
15.04117647058823512.785
939321AE1-163 C
Adder
4.53176470588235253.852
942111AE2-223 C
Adder
1.41764705882352951.205
942652AE2-281 E
Adder
3.9764705882352943.38
946321AF1-296 C
Adder
2.7635294117647062.349
966441AG1-513 C
50/50
0.5020.502
276627AG1-044 BAT
Adder
0.0105882352941176470.009
957382AF2-032 E
Adder
0.117647058823529420.1
276170Z1-108 E
50/50
2.462.46
965913AG1-460 BT
Adder
0.00588235294117647050.005
920272AA2-123 E
Adder
2.83294117647058832.408
991302J1755
External Queue
9.86539.8653
990947J1432 G
External Queue
15.3515.35
991092J1477
External Queue
2.88632.8863
990052J1200
External Queue
0.43050.4305
990512J1326 G
External Queue
5.4355.435

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.52 %
Rating:1091.0 MVA
Rating Type:A
MVA to Mitigate:1096.72
MW Contribution:5.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
290051GSG-6; E
80/20
1.6851.685
290108LEEDK;1U E
80/20
3.8583.858
290261S-027 E
80/20
2.2852.285
290265S-028 E
80/20
2.2712.271
295111SUBLETTE E
80/20
0.4390.439
925581AC1-033 C
80/20
0.3660.366
925582AC1-033 E
80/20
2.4492.449
938861AE1-114 C
80/20
2.0372.037
270681BRIGHTSTK; R
80/20
0.3850.385
274887PILOT HIL;1U
80/20
0.6450.645
275149KELLYCK ;1E
80/20
2.5792.579
293771O-035 E
80/20
1.1181.118
924048AB2-047 E1
80/20
1.5971.597
937001AD2-134 C
80/20
0.6530.653
274682WAUKEGAN ;7U
80/20
12.37312.373
274683WAUKEGAN ;8U
80/20
13.33213.332
274861TOP CROP ;1U
80/20
0.4840.484
274862TOP CROP ;2U
80/20
0.9230.923
274863CAYUGA RI;1U
80/20
0.4010.401
276157O-029 C
80/20
0.3590.359
276158O-029 C
80/20
0.3590.359
934721AD1-100 C
80/20
2.9882.988
942421AE2-255 C
80/20
1.6741.674
942422AE2-255 E
80/20
5.0235.023
959611AF2-252 C
80/20
1.121.12
960611AF2-352 C
80/20
1.121.12
960612AF2-352 E
80/20
1.681.68
990901L-005 E
80/20
2.0672.067
274687WILL CNTY;4U
80/20
29.39129.391
276656AB2-047 C2
80/20
0.240.24
294401BSHIL;1U E
80/20
1.3951.395
926821AC1-168 C
80/20
0.5960.596
927208AC1-214 E1
80/20
0.530.53
959612AF2-252 E
80/20
1.681.68
274847GR RIDGE ;BU
80/20
0.5850.585
274849CRESCENT ;1U
80/20
0.170.17
274857BIG SKY ;U1
80/20
0.2820.282
274859EASYR;U1 E
80/20
1.9441.944
274872LEE DEKAL;1U
80/20
0.7810.781
293061N-015 E
80/20
2.5612.561
293519PILOT HIL;1E
80/20
2.5792.579
924049AB2-047 E2
80/20
1.6221.622
934722AD1-100 E
80/20
46.47446.474
939322AE1-163 E
80/20
18.9218.92
946322AF1-296 E
80/20
8.5868.586
959351AF2-226 C
80/20
2.1042.104
966092AG1-478 E
80/20
0.4880.488
274676JOLIET 29;8U
80/20
30.59430.594
294763P-046 E
80/20
1.5291.529
295109WESTBROOK E
80/20
0.9020.902
936371AD2-047 C
80/20
2.0042.004
938851AE1-113 C
80/20
4.424.42
966442AG1-513 E
80/20
0.4920.492
274674JOLIET 9 ;6U
80/20
10.08310.083
274890CAYUG;1U E
80/20
2.1372.137
276602WESTBROOK C
80/20
0.1370.137
276675AE2-062 E
80/20
0.0850.085
942651AE2-281 C
80/20
0.440.44
270839OTTER CRK; R
80/20
0.3830.383
274888KELLY CRK;1U
80/20
0.6450.645
293716O-029 E
80/20
0.8630.863
937002AD2-134 E
80/20
2.612.61
938852AE1-113 E
80/20
15.67215.672
938862AE1-114 E
80/20
6.9496.949
274851PROVIDENC;RU
80/20
0.1810.181
274853TWINGROVE;U1
80/20
0.4870.487
274854TWINGROVE;U2
80/20
0.5010.501
274855GSG-6 ;RU
80/20
0.4210.421
274879MINONK ;1U
80/20
0.8370.837
274881WALNUT RG;1U
80/20
0.7610.761
293645O22 E2
80/20
3.4613.461
293715O-029 E
80/20
1.5751.575
293717O-029 E
80/20
0.7940.794
916212CRESCENT ;1U
80/20
0.7850.785
916221Z1-073 E
80/20
1.1881.188
957331AF2-027 C
80/20
1.6591.659
957332AF2-027 E
80/20
2.4882.488
959352AF2-226 E
80/20
3.1563.156
960281AF2-319 C
80/20
2.1042.104
960282AF2-319 E
80/20
3.1563.156
274864CAYUGA RI;2U
80/20
0.4010.401
276655AB2-047 C1
80/20
0.240.24
294392P-010 E
80/20
3.2533.253
294410BSHIL;2U E
80/20
1.3951.395
918052AA1-018 E OP
80/20
2.5632.563
926822AC1-168 E
80/20
44
927209AC1-214 E2
80/20
0.530.53
276645AC1-214 C1
80/20
0.1490.149
276646AC1-214 C2
80/20
0.1490.149
962012AG1-044 E
80/20
0.0360.036
274878BISHOP HL;2U
80/20
0.3490.349
276626AG1-044 E
80/20
0.0410.041
917502Z2-087 E
80/20
2.5752.575
942112AE2-223 E
80/20
6.1816.181
274848CAMPGROVE;RU
80/20
0.2240.224
274850MENDOTA H;RU
80/20
0.2770.277
274856ECOGROVE ;U1
80/20
0.3680.368
274858BIG SKY ;U2
80/20
0.2820.282
274871GR RIDGE ;2U
80/20
0.2180.218
274877BISHOP HL;1U
80/20
0.3490.349
293516O-009 E
80/20
3.0453.045
293644O22 E1
80/20
3.0223.022
936372AD2-047 E
80/20
9.7859.785
939321AE1-163 C
80/20
3.083.08
274675JOLIET 29;7U
80/20
30.56830.568
274860EASYR;U2 E
80/20
1.9441.944
276156O-029 C
80/20
0.1990.199
290021O50 E
80/20
3.3493.349
966091AG1-478 C
80/20
0.3250.325
942111AE2-223 C
80/20
0.9230.923
942652AE2-281 E
80/20
2.7032.703
946321AF1-296 C
80/20
1.8341.834
966441AG1-513 C
80/20
0.3280.328
274891CAYUG;2U E
80/20
2.1372.137
276603SUBLETTE C
80/20
0.0620.062
276627AG1-044 BAT
80/20
0.0070.007
920272AA2-123 E
80/20
1.5961.596
276170Z1-108 E
80/20
1.6321.632

Details for POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AMIL/CE
Facility Description:
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.67 %
Rating:1489.0 MVA
Rating Type:B
MVA to Mitigate:1513.88
MW Contribution:36.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274861TOP CROP ;1U
50/50
3.3433.343
274862TOP CROP ;2U
50/50
6.3786.378
942421AE2-255 C
50/50
8.7198.719
942422AE2-255 E
50/50
26.15826.158
938851AE1-113 C
50/50
23.01923.019
942651AE2-281 C
50/50
4.074.07
270839OTTER CRK; R
50/50
3.5433.543
938852AE1-113 E
50/50
81.61281.612
274879MINONK ;1U
50/50
4.364.36
293645O22 E2
50/50
23.91323.913
959352AF2-226 E
50/50
21.80521.805
960281AF2-319 C
50/50
14.53714.537
960282AF2-319 E
50/50
21.80521.805
918052AA1-018 E OP
50/50
23.71323.713
939322AE1-163 E
50/50
175.013175.013
959351AF2-226 C
50/50
14.53714.537
290021O50 E
50/50
17.43817.438
293644O22 E1
50/50
20.87820.878
939321AE1-163 C
50/50
28.49128.491
942652AE2-281 E
50/50
25.00225.002

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.44 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1158.61
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
3.7663.766
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
295111SUBLETTE E
80/20
0.5570.557
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
938861AE1-114 C
80/20
2.5552.555
957371AF2-031 C
80/20
0.6360.636
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
270681BRIGHTSTK; R
80/20
0.4980.498
274887PILOT HIL;1U
80/20
0.9460.946
275149KELLYCK ;1E
80/20
3.7863.786
293771O-035 E
80/20
1.3921.392
924048AB2-047 E1
80/20
2.0672.067
937001AD2-134 C
80/20
0.8290.829
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
934721AD1-100 C
80/20
3.8223.822
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
959611AF2-252 C
80/20
1.4511.451
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
990901L-005 E
80/20
2.5642.564
274687WILL CNTY;4U
80/20
32.59232.592
276656AB2-047 C2
80/20
0.3110.311
294401BSHIL;1U E
80/20
1.7331.733
925772AC1-053 E
80/20
3.953.95
926821AC1-168 C
80/20
0.7420.742
927208AC1-214 E1
80/20
0.660.66
959612AF2-252 E
80/20
2.1762.176
274847GR RIDGE ;BU
80/20
0.730.73
274849CRESCENT ;1U
80/20
0.2120.212
274857BIG SKY ;U1
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274872LEE DEKAL;1U
80/20
0.9950.995
276621X2-022 GEN
80/20
2.5362.536
293061N-015 E
80/20
3.1963.196
293519PILOT HIL;1E
80/20
3.7863.786
924049AB2-047 E2
80/20
2.0992.099
934722AD1-100 E
80/20
59.4559.45
939322AE1-163 E
80/20
25.49625.496
946322AF1-296 E
80/20
10.73910.739
959351AF2-226 C
80/20
1.9641.964
966092AG1-478 E
80/20
0.6470.647
274676JOLIET 29;8U
80/20
36.23736.237
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
936371AD2-047 C
80/20
2.9422.942
938851AE1-113 C
80/20
5.2345.234
957372AF2-031 E
80/20
0.9540.954
965331AG1-398 C
80/20
0.1690.169
966442AG1-513 E
80/20
0.6290.629
274674JOLIET 9 ;6U
80/20
13.64413.644
274890CAYUG;1U E
80/20
2.7522.752
276602WESTBROOK C
80/20
0.1730.173
276675AE2-062 E
80/20
0.1120.112
942651AE2-281 C
80/20
0.5930.593
270839OTTER CRK; R
80/20
0.5410.541
274888KELLY CRK;1U
80/20
0.9460.946
293716O-029 E
80/20
1.081.08
937002AD2-134 E
80/20
3.3123.312
938852AE1-113 E
80/20
18.55518.555
938862AE1-114 E
80/20
8.7168.716
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274881WALNUT RG;1U
80/20
0.9520.952
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293717O-029 E
80/20
0.9930.993
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959352AF2-226 E
80/20
2.9452.945
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
274864CAYUGA RI;2U
80/20
0.5160.516
276655AB2-047 C1
80/20
0.3110.311
294392P-010 E
80/20
4.0594.059
294410BSHIL;2U E
80/20
1.7331.733
918052AA1-018 E OP
80/20
3.6223.622
926822AC1-168 E
80/20
4.9814.981
927209AC1-214 E2
80/20
0.660.66
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
925771AC1-053 C
80/20
0.590.59
962012AG1-044 E
80/20
0.0450.045
274878BISHOP HL;2U
80/20
0.4330.433
276626AG1-044 E
80/20
0.0510.051
917502Z2-087 E
80/20
3.3333.333
942112AE2-223 E
80/20
7.9997.999
274848CAMPGROVE;RU
80/20
0.2780.278
274850MENDOTA H;RU
80/20
0.3520.352
274856ECOGROVE ;U1
80/20
0.4620.462
274858BIG SKY ;U2
80/20
0.3530.353
274871GR RIDGE ;2U
80/20
0.2720.272
274877BISHOP HL;1U
80/20
0.4330.433
276615W2-048 GEN
80/20
0.8910.891
293516O-009 E
80/20
3.8093.809
293644O22 E1
80/20
2.822.82
924266AB2-070 E
80/20
2.272.27
936372AD2-047 E
80/20
14.36514.365
939321AE1-163 C
80/20
4.1514.151
942111AE2-223 C
80/20
1.1951.195
942652AE2-281 E
80/20
3.6423.642
946321AF1-296 C
80/20
2.2942.294
966441AG1-513 C
80/20
0.4190.419
274675JOLIET 29;7U
80/20
36.25136.251
274860EASYR;U2 E
80/20
2.4372.437
276156O-029 C
80/20
0.2490.249
290021O50 E
80/20
3.9653.965
961502AF2-441 E
80/20
10.40210.402
966091AG1-478 C
80/20
0.4310.431
274891CAYUG;2U E
80/20
2.7522.752
276603SUBLETTE C
80/20
0.0780.078
276668AB2-070 C
80/20
0.3750.375
276627AG1-044 BAT
80/20
0.0090.009
935141AD1-148 C
80/20
0.7970.797
920272AA2-123 E
80/20
22
965793AG1-447 BT
80/20
8.3248.324
276170Z1-108 E
80/20
2.0422.042
991302J1755
External Queue
8.07698.0769
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.42 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1158.42
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
276174W4-005 E
80/20
3.7663.766
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
295111SUBLETTE E
80/20
0.5570.557
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
938861AE1-114 C
80/20
2.5552.555
957371AF2-031 C
80/20
0.6360.636
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
270681BRIGHTSTK; R
80/20
0.4980.498
274887PILOT HIL;1U
80/20
0.9460.946
275149KELLYCK ;1E
80/20
3.7863.786
293771O-035 E
80/20
1.3921.392
924048AB2-047 E1
80/20
2.0672.067
937001AD2-134 C
80/20
0.8290.829
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
934721AD1-100 C
80/20
3.8223.822
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
959611AF2-252 C
80/20
1.4511.451
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
990901L-005 E
80/20
2.5642.564
274687WILL CNTY;4U
80/20
32.59232.592
276656AB2-047 C2
80/20
0.3110.311
294401BSHIL;1U E
80/20
1.7331.733
925772AC1-053 E
80/20
3.953.95
926821AC1-168 C
80/20
0.7420.742
927208AC1-214 E1
80/20
0.660.66
959612AF2-252 E
80/20
2.1762.176
274847GR RIDGE ;BU
80/20
0.730.73
274849CRESCENT ;1U
80/20
0.2120.212
274857BIG SKY ;U1
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274872LEE DEKAL;1U
80/20
0.9950.995
276621X2-022 GEN
80/20
2.5362.536
293061N-015 E
80/20
3.1963.196
293519PILOT HIL;1E
80/20
3.7863.786
924049AB2-047 E2
80/20
2.0992.099
934722AD1-100 E
80/20
59.4559.45
939322AE1-163 E
80/20
25.49625.496
946322AF1-296 E
80/20
10.73910.739
959351AF2-226 C
80/20
1.9641.964
966092AG1-478 E
80/20
0.6470.647
274676JOLIET 29;8U
80/20
36.23736.237
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
936371AD2-047 C
80/20
2.9422.942
938851AE1-113 C
80/20
5.2345.234
957372AF2-031 E
80/20
0.9540.954
965331AG1-398 C
80/20
0.1690.169
966442AG1-513 E
80/20
0.6290.629
274674JOLIET 9 ;6U
80/20
13.64413.644
274890CAYUG;1U E
80/20
2.7522.752
276602WESTBROOK C
80/20
0.1730.173
276675AE2-062 E
80/20
0.1120.112
942651AE2-281 C
80/20
0.5930.593
270839OTTER CRK; R
80/20
0.5410.541
274888KELLY CRK;1U
80/20
0.9460.946
293716O-029 E
80/20
1.081.08
937002AD2-134 E
80/20
3.3123.312
938852AE1-113 E
80/20
18.55518.555
938862AE1-114 E
80/20
8.7168.716
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274881WALNUT RG;1U
80/20
0.9520.952
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293717O-029 E
80/20
0.9930.993
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959352AF2-226 E
80/20
2.9452.945
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
274864CAYUGA RI;2U
80/20
0.5160.516
276655AB2-047 C1
80/20
0.3110.311
294392P-010 E
80/20
4.0594.059
294410BSHIL;2U E
80/20
1.7331.733
918052AA1-018 E OP
80/20
3.6223.622
926822AC1-168 E
80/20
4.9814.981
927209AC1-214 E2
80/20
0.660.66
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
925771AC1-053 C
80/20
0.590.59
962012AG1-044 E
80/20
0.0450.045
274878BISHOP HL;2U
80/20
0.4330.433
276626AG1-044 E
80/20
0.0510.051
917502Z2-087 E
80/20
3.3333.333
942112AE2-223 E
80/20
7.9997.999
274848CAMPGROVE;RU
80/20
0.2780.278
274850MENDOTA H;RU
80/20
0.3520.352
274856ECOGROVE ;U1
80/20
0.4620.462
274858BIG SKY ;U2
80/20
0.3530.353
274871GR RIDGE ;2U
80/20
0.2720.272
274877BISHOP HL;1U
80/20
0.4330.433
276615W2-048 GEN
80/20
0.8910.891
293516O-009 E
80/20
3.8093.809
293644O22 E1
80/20
2.822.82
924266AB2-070 E
80/20
2.272.27
936372AD2-047 E
80/20
14.36514.365
939321AE1-163 C
80/20
4.1514.151
942111AE2-223 C
80/20
1.1951.195
942652AE2-281 E
80/20
3.6423.642
946321AF1-296 C
80/20
2.2942.294
966441AG1-513 C
80/20
0.4190.419
274675JOLIET 29;7U
80/20
36.25136.251
274860EASYR;U2 E
80/20
2.4372.437
276156O-029 C
80/20
0.2490.249
290021O50 E
80/20
3.9653.965
961502AF2-441 E
80/20
10.40210.402
966091AG1-478 C
80/20
0.4310.431
274891CAYUG;2U E
80/20
2.7522.752
276603SUBLETTE C
80/20
0.0780.078
276668AB2-070 C
80/20
0.3750.375
276627AG1-044 BAT
80/20
0.0090.009
935141AD1-148 C
80/20
0.7970.797
965793AG1-447 BT
80/20
8.3248.324
920272AA2-123 E
80/20
22
276170Z1-108 E
80/20
2.0422.042
991302J1755
External Queue
8.07698.0769
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.94 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1027.6
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
2.5552941176470592.172
957371AF2-031 C
Adder
0.63647058823529420.541
961501AF2-441 C
Adder
6.9341176470588245.894
274887PILOT HIL;1U
50/50
0.9460.946
275149KELLYCK ;1E
50/50
3.7853.785
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
934721AD1-100 C
50/50
3.8213.821
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
959611AF2-252 C
Adder
1.45058823529411771.233
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
274687WILL CNTY;4U
50/50
32.59532.595
926821AC1-168 C
Adder
0.74235294117647070.631
959612AF2-252 E
Adder
2.17647058823529441.85
274847GR RIDGE ;BU
50/50
0.730.73
274676JOLIET 29;8U
50/50
36.23736.237
936371AD2-047 C
50/50
2.9422.942
938851AE1-113 C
Adder
5.2341176470588244.449
957372AF2-031 E
Adder
0.95411764705882360.811
966442AG1-513 E
50/50
0.6290.629
274674JOLIET 9 ;6U
50/50
13.64513.645
276675AE2-062 E
50/50
0.1120.112
270839OTTER CRK; R
50/50
0.5410.541
274888KELLY CRK;1U
50/50
0.9460.946
938852AE1-113 E
Adder
18.5576470588235315.774
938862AE1-114 E
Adder
8.717647058823537.41
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959352AF2-226 E
Adder
2.94588235294117642.504
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
926822AC1-168 E
Adder
4.98117647058823554.234
962012AG1-044 E
Adder
0.044705882352941180.038
942651AE2-281 C
50/50
0.5930.593
293061N-015 E
50/50
3.1963.196
293519PILOT HIL;1E
50/50
3.7853.785
934722AD1-100 E
50/50
59.44459.444
939322AE1-163 E
50/50
25.49625.496
946322AF1-296 E
Adder
10.749.129
959351AF2-226 C
Adder
1.9635294117647061.669
966092AG1-478 E
50/50
0.6470.647
276626AG1-044 E
Adder
0.050588235294117640.043
942112AE2-223 E
Adder
7.9988235294117666.799
274675JOLIET 29;7U
50/50
36.25136.251
961502AF2-441 E
Adder
10.48.84
966091AG1-478 C
50/50
0.4310.431
274871GR RIDGE ;2U
50/50
0.2720.272
936372AD2-047 E
50/50
14.36514.365
939321AE1-163 C
50/50
4.1514.151
942111AE2-223 C
Adder
1.19529411764705881.016
942652AE2-281 E
50/50
3.6423.642
946321AF1-296 C
Adder
2.29411764705882341.95
966441AG1-513 C
50/50
0.420.42
276627AG1-044 BAT
Adder
0.0094117647058823540.008
276170Z1-108 E
50/50
2.0432.043
920272AA2-123 E
50/50
22
965793AG1-447 BT
50/50
8.3258.325
991302J1755
External Queue
8.07698.0769
990947J1432 G
External Queue
12.502512.5025
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.94 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1027.59
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938861AE1-114 C
Adder
2.5552941176470592.172
957371AF2-031 C
Adder
0.63647058823529420.541
961501AF2-441 C
Adder
6.9341176470588245.894
274887PILOT HIL;1U
50/50
0.9460.946
275149KELLYCK ;1E
50/50
3.7853.785
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
934721AD1-100 C
50/50
3.8213.821
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
959611AF2-252 C
Adder
1.45058823529411771.233
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
274687WILL CNTY;4U
50/50
32.59532.595
926821AC1-168 C
Adder
0.74235294117647070.631
959612AF2-252 E
Adder
2.17647058823529441.85
274847GR RIDGE ;BU
50/50
0.730.73
274676JOLIET 29;8U
50/50
36.23736.237
936371AD2-047 C
50/50
2.9422.942
938851AE1-113 C
Adder
5.2341176470588244.449
957372AF2-031 E
Adder
0.95411764705882360.811
966442AG1-513 E
50/50
0.6290.629
274674JOLIET 9 ;6U
50/50
13.64513.645
276675AE2-062 E
50/50
0.1120.112
270839OTTER CRK; R
50/50
0.5410.541
274888KELLY CRK;1U
50/50
0.9460.946
938852AE1-113 E
Adder
18.5576470588235315.774
938862AE1-114 E
Adder
8.717647058823537.41
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959352AF2-226 E
Adder
2.94588235294117642.504
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
926822AC1-168 E
Adder
4.98117647058823554.234
962012AG1-044 E
Adder
0.044705882352941180.038
942651AE2-281 C
50/50
0.5930.593
293061N-015 E
50/50
3.1963.196
293519PILOT HIL;1E
50/50
3.7853.785
934722AD1-100 E
50/50
59.44459.444
939322AE1-163 E
50/50
25.49625.496
946322AF1-296 E
Adder
10.749.129
959351AF2-226 C
Adder
1.9635294117647061.669
966092AG1-478 E
50/50
0.6470.647
276626AG1-044 E
Adder
0.050588235294117640.043
942112AE2-223 E
Adder
7.9988235294117666.799
274675JOLIET 29;7U
50/50
36.25136.251
961502AF2-441 E
Adder
10.48.84
966091AG1-478 C
50/50
0.4310.431
274871GR RIDGE ;2U
50/50
0.2720.272
936372AD2-047 E
50/50
14.36514.365
939321AE1-163 C
50/50
4.1514.151
942111AE2-223 C
Adder
1.19529411764705881.016
942652AE2-281 E
50/50
3.6423.642
946321AF1-296 C
Adder
2.29411764705882341.95
966441AG1-513 C
50/50
0.420.42
276627AG1-044 BAT
Adder
0.0094117647058823540.008
920272AA2-123 E
50/50
22
965793AG1-447 BT
50/50
8.3258.325
276170Z1-108 E
50/50
2.0432.043
991302J1755
External Queue
8.07698.0769
990947J1432 G
External Queue
12.502512.5025
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
CONTINGENCY '765-L11215__-S_SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
END
CONTINGENCY 'AEP_P1-2_#695_1681_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243207 CKT 1   /*05DUMONT     765.0 - 05GRNTWN     765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'COMED_P4_112-65-BT4-5___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT3-4___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
CONTINGENCY 'COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A'
 TRIP BRANCH FROM BUS 270790 TO BUS 270770 CKT 1   /*KATYDID  ; B 345.0 - GOODINGS ;4B 345.0
 TRIP BRANCH FROM BUS 270827 TO BUS 270769 CKT 1   /*NEVADA   ; R 345.0 - GOODINGS ;2R 345.0
END
255113 to 243219 ckt 1
960680 to 243229 ckt 1
274750 to 255112 ckt 1
270728 to 274750 ckt 1
270855 to 349662 ckt 1
274804 to 960680 ckt 1

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 1, Cluster 5 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 5 projects.

This analysis is effectively a screening study to determine whether the addition of the Cluster 5 projects will meet the dynamics requirements of the NERC, ComEd and PJM reliability standards.

The load flow scenario for the analysis was based on the RTEP 2027 summer peak load case, modified to include applicable projects. Cluster 5 projects have been dispatched online at maximum power output and the voltage schedule set to achieve near unity power factor at the high side of the main transformer.

Cluster 5 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 107 contingencies were studied, each with a 20 second simulation time period. Studied faults included:

  1. Steady-state operation (20 second run);
  2. Three-phase faults with normal clearing time;
  3. Three-phase bus faults with normal clearing time;
  4. Three-phase to ground faults with three-phase delayed clearing due to a stuck breaker (GO breakers);
  5. Three-phase to ground faults with single-phase delayed clearing due to a stuck breaker (IPO breakers)
  6. Three-phase faults with loss of multiple-circuit tower line.

No relevant high speed reclosing (HSR) contingencies were identified for this study.

For all simulations, the Cluster 5 projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

For all of the fault contingencies tested on the 2027 peak load case:

  1. Cluster 5 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  2. The system with Cluster 5 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3%.
  3. Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).
  4. No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

AF2-226 and AF2-319 meet the 0.95 leading and lagging PF requirement.

The IPCMD and IQCMD states in the REGCA1 models of AF2-226 GEN and AF2-319 GEN showed erratic behavior for some contingencies in which this generator has been disconnected as part of the contingency event. Since the machine is disconnected and no active or reactive power is injected into the system, these plots are ignored.

Initial simulations showed AF2-226 and AF2-319 exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. The reactive power settling time was decreased by adjusting the PPC Q/V controller PI gains for both projects (Kp = 1 from 0, Ki = 5 from 0.5). The developer confirmed that the updated controller parameters are acceptable.

Simulations showed AF2-142, AF2-143, and AE1-163 getting stuck in high voltage ride through (HVRT) mode for extended periods after fault clearance for several contingencies. This resulted in a 345 kV POI voltage of about 1.1 pu for more than 5 seconds. For AF2-142 and AF2-143, this was resolved by adjusting the HVRT threshold and deadband to 1.15 pu (from 1.1 pu) and 0.15 pu (from 0.1 pu), respectively. These parameter adjustments were confirmed by the respective project developers. For AE1-163, the dynamic model was updated to the Vestas UDM which was submitted for the AE1-163/AE2-281 necessary study as per the developer’s request.

Initial simulations showed poorly damped oscillations in AC1-111 power. The AC1-111 dynamic model was updated to the most recent (revision 1) model which uses the AC7B exciter model instead of the ESAC1A model. Revision 1 of the AC1-111 dynamic model was used in the last iteration of the AC1-111 dynamic analysis, therefore it is assumed that the AC7B model is accurate relative to what is in the field. The updated dynamic model eliminated these oscillations.

No mitigations were found to be required.

 

Table 1: TC1 Cluster 5 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

5

AF2-226

Storage

ComEd

50

50

20

Katydid Road 345 kV

AF2-319

Storage

ComEd

50

50

20

Katydid Road 345 kV

 

Reactive Power Analysis

The reactive power capability of AF2-226 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA2-116Cook-East Elkhart 345kVIn Service
AA2-123Marengo 34kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-080Dumont-Olive 345kVIn Service
AB1-087Sullivan 345kV #1Under Construction
AB1-088Sullivan 345kV #2Engineering & Procurement
AB1-122Kendall-Tazewell & Dresden-Mole CreekIn Service
AC1-033Kewanee 138 kVIn Service
AC1-168Kewanee-StreatorSuspended
AC1-214Crescent RidgeIn Service
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD2-020Valley 138 kVEngineering & Procurement
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-079Capitol Ave 34.5kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-172Lena 138kVIn Service
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-134Nelson 345 kVIn Service
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-205McLean 345 kVEngineering & Procurement
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-062Romeoville 12 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-223McLean 345 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVUnder Construction
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-276Sullivan 345kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVPartially in Service - Under Construction
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-084Hartford-Almena 69 kVUnder Construction
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVEngineering & Procurement
AF1-176Corey 138 kVEngineering & Procurement
AF1-204Eugene 345 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-280Nelson-Lee CountyEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-027Zion Energy Center 345 kVEngineering & Procurement
AF2-031CalumetEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-182Nelson-Lee County 345 kV IIEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-319Katydid Road 345 kVEngineering & Procurement
AF2-349SILVER LAKE- CHERRY VALLEY 345 KVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-366Crego Rd 138 kVEngineering & Procurement
AF2-396Stinger 138 kVEngineering & Procurement
AF2-441Burnham 138kVEngineering & Procurement
AG1-044Whiteside CountyIn Service
AG1-109Valley 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-513Aurora 138 kVSuspended
AG1-555Dequine 345 kVEngineering & Procurement
X3-005Wildwood 12kVIn Service
Z1-073Mendota HillsIn Service
Z1-108McHenry 34kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)Identified Impacts
AF2-226 System Reinforcements:
TOTrans Owner IDTitleCategoryAllocated Cost ($USD)
AMILAMIL_TC1_13300Ameren - Powerton - Tazewell 345 kV Line Reconductoring & Upgrade Station EquipmentContingent$0
Grand Total:$0

System Reinforcement
Type
Load Flow
TO
AMIL
RTEP ID / TO ID
(Pending) / AMIL_TC1_13300
Title
Ameren - Powerton - Tazewell 345 kV Line Reconductoring & Upgrade Station Equipment
Description
AMIL limit is 1512 MVA 0.64 miles. (PWRT-TAZW-0304). Need to rebuild to be 4000 A/2390 MVA SE, upgrade the Powerton-Tazewell 345 kV circuit 1 terminal equipment and breaker and a half leg at Tazewell from 3000A to 4000A. Rebuild 0.6 miles of the Powerton-Tazewell 345 kV transmission line to increase the ampacity to 4000A
Total Cost ($USD)
$2,760,000
Allocated Cost ($USD)
$0
Time Estimate
24 Months

Contingent

Note: Based on PJM cost allocation criteria, AF2-226 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-226 could receive cost allocation. Although AF2-226 may not presently have cost responsibility for this upgrade, AF2-226 may need this upgrade in-service to be deliverable to the PJM system. If AF2-226 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B2390.0 MVA

New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In coordination with other Affected System Operators, PJM has determined that the Affected System Operator for this project that requires an Affected System Study. For the latest Affected System Study results pertaining this project, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM lists any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO) Identified Impacts
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AF2-226 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
ComEdn9682.0Perform sag mitigation on the Powerton - Tazewell 345 kV Line and replace disconnect switches at Powerton substation.Cost Allocated$627,185
ComEdn6280Mitigate the sag on the ComEd Powerton - Tazewell L0304 345 kV line.Contingent$0N/A
Grand Total:$627,185

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9682.0
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n9682.0 / CE_NUN_0304.1
Title
Perform sag mitigation on the Powerton - Tazewell 345 kV Line and replace disconnect switches at Powerton substation.
Description
• Upgrade the existing substation Station 3 Powerton by replacing two sets of disconnect switches with ones capable of interrupting 3000 Amps of charging current. • Perform sag mitigation on 9 miles of 345kV transmission line L0304 from Station 3 Powerton to Tazewell (Ameren). 0.9 miles will need to be retensioned to accommodate the sag mitigation.
Total Cost ($USD)
$5,017,397
Discounted Total Cost ($USD)
$5,017,397
Allocated Cost ($USD)
$627,185
Time Estimate
Mar 13 2029

Contributor

FacilityContingency
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1576.0 MVA
(All)ALDR2340.0 MVA
(All)B1862.0 MVA
(All)C2035.0 MVA
(All)STE1900.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-142110.9 MW37.5%$1,881,556
AF2-143110.9 MW37.5%$1,881,471
AF2-226 ⧉ Katydid Road 345kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-226, AF2-319
37.0 MW12.5%$627,185
AF2-319 ⧉ Katydid Road 345kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-226, AF2-319
37.0 MW12.5%$627,185

System Reinforcement: s3442.26
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s3442.26
Title
Dumont 765 kV: Replace 3000 A circuit breaker at Dumont
Description
Dumont 765 kV: Replace 3000 A circuit breaker at Dumont to address a generation deliverability violation on the Dumont – Sorenson 765 kV branch related to the new customer interconnections in the area. Projected in service date 3/5/2027
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AF2-226 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AF2-226 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05DUMONT-05SORENS 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4558.0 MVA
(All)B5001.0 MVA

System Reinforcement: b3775.6
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.6
Title
Perform sag study mitigation work on the Dumont-Stillwell 345 kV line
Description
Perform sag study mitigation work on the Dumont-Stillwell 345 kV line (remove a center-pivot irrigation system from under the line, allowing for the normal and emergency ratings of the line to increase, replace two structures and modify a third structure).
Cost Information
Time Estimate
Nov 20 2026

Not Contingent

Note: AF2-226 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-226 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1409.0 MVA
(All)B1718.0 MVA

System Reinforcement: b3775.11
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.11 / b3775.7a
Title
Upgrade the wavetrap at Dumont substation to increase the rating of the Stillwell-Dumont 345 kV line to match conductor rating.
Description
Upgrade the wavetrap at Dumont substation to increase the rating of the Stillwell-Dumont 345 kV line to match conductor rating.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AF2-226 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-226 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1409.0 MVA
(All)B1737.0 MVA

System Reinforcement: b3775.7
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.7 / b3775.7b
Title
Upgrade breakers at Dumont substation on the Stillwell-Dumont 345 kV line.
Description
Upgrade the limiting element at Dumont substation to increase the rating of the Stillwell-Dumont 345 kV line to match conductor rating. This includes replacement of breakers F and F1.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AF2-226 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-226 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1408.0 MVA
(All)B1887.0 MVA

System Reinforcement: n3985
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n3985 / AEPO0036a
Title
Upgrade three Marysville Wavetraps ( 3000A)
Description
Replace 3 Marysville 765 kV wave traps. Costs updated to $705,368 from Facility Study
Total Cost ($USD)
$900,000
Discounted Total Cost ($USD)
$900,000
Allocated Cost ($USD)
$0
Time Estimate
Jul 16 2026

Not Contingent

Note: AF2-226 contributes to the loading of an overloaded facility that is being mitigated by a network upgrade that was securitized by a prior Queue/Cycle. AF2-226 is not contingent on this network upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARYSV-05SORENS 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5075.0 MVA
(All)B5075.0 MVA

System Reinforcement: b3775.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.1
Title
Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line
Description
Outside of the Green Acres substation, swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line to the University Park N-Olive 345 kV line to create a University Park N-Green Acres-Olive and St. John-Olive 345 kV lines.
Cost Information
Time Estimate
Mar 30 2027

Not Contingent

Note: AF2-226 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-226 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)ALDR9999.0 MVA
(All)STE9999.0 MVA
05OLIVE-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A9999.0 MVA
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A9999.0 MVA

System Reinforcement: b3775.10
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.10
Title
Perform sag study mitigation work on Olive – University Park
Description
Perform a sag study on the Olive – University Park 345kV line to increase the operating temperature to 225 F. Remediation work includes two tower replacements on the line.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AF2-226 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-226 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA

System Reinforcement: b3775.2
Type
Load Flow
TO
NextEra
RTEP ID / TO ID
b3775.2
Title
Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles).
Description
Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles).
Cost Information
Time Estimate
May 09 2023

Not Contingent

Note: AF2-226 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-226 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA
(All)C2280.0 MVA
(All)STE2107.0 MVA

System Reinforcement: b3775.3
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.3
Title
Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete
Description
Part of b3775 baseline. Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete (5 miles) with twin bundled 1277 ACAR conductor.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AF2-226 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-226 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA
(All)C2280.0 MVA
(All)STE2107.0 MVA

System Reinforcement: b3775.5
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.5
Title
Replace E. Frankfort 345 kV circuit breaker “9-14” with 3150A SF6 circuit breaker.
Description
Part of b3775 baseline. Replace E. Frankfort 345 kV circuit breaker “9-14” with 3150A SF6 circuit breaker.
Cost Information
Time Estimate
Oct 06 2025

Not Contingent

Note: AF2-226 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-226 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1826.0 MVA
(All)B2070.0 MVA
(All)C2390.0 MVA
SUMSTE2385.0 MVA

System Reinforcement: n6280
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n6280 / ce-005
Title
Mitigate the sag on the ComEd Powerton - Tazewell L0304 345 kV line.
Description
ComEd 345kV L0304 ratings ,SSTE: 1512 MVA and ALDR: 1739 MVA. The post contingency flow for this event exceeds the rating therefore an upgrade is required. The upgarde will be to mitigate the sag on the line. A preliminary estimate for this work is $9.1M with a estimated construction timeline of 30 months. Upon completion of this upgrade the new ratings will be 1461/1656/1909/1912/2198 MVA (SN/SLTE/SSTE/SLD/ALDR).
Total Cost ($USD)
$2,625,686
Discounted Total Cost ($USD)
$2,625,686
Allocated Cost ($USD)
$0
Time Estimate
Nov 01 2026

Contingent

Note: Based on PJM cost allocation criteria, AF2-226 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AF2-226 may not have cost responsibility for this upgrade, AF2-226 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AF2-226 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1461.0 MVA
(All)ALDR2198.0 MVA
(All)B1656.0 MVA
(All)C1912.0 MVA
(All)STE1909.0 MVA

System Reinforcement: s3011
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
s3011 / CE_S3011
Title
Replace 345kV straight bus at TSS 116 Goodings Grove with a gas insulated switchgear ("GIS") breaker and a half configuration.
Description
Replace 345 kV open air straight bus with GIS in a breaker and half configuration (34 Circuit Breakers) at Goodings Grove with 80kA capability.
Cost Information
Time Estimate
Dec 31 2029

Not Contingent

Note: AF2-226 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AF2-226 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
(Any)COMED_P4_116-45-L11614__SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4-6_116-345-R______SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4_112-45-BT4-5___SRT-A
No new ratings for this Flowgate.

System Reinforcement: b3775.4
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.4 / CE_B3775.4
Title
Rebuild 345 kV double circuit extending from Crete to E. Frankfort.
Description
Part of b3775 baseline. Rebuild 12.7 miles of 345 kV double circuit extending from Crete to E. Frankfort with twin bundled 1277 ACAR conductor.
Cost Information
Time Estimate
Jun 01 2026

Not Contingent

Note: AF2-226 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-226 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
(Any)765-L11215__-S_SRT-A
No new ratings for this Flowgate.
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA
(All)C2280.0 MVA
(All)STE2017.0 MVA

System Reinforcement: n5145
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n5145
Title
Reconfigure Wilton 765kV bus
Description
Reconfigure Wilton 765kV bus thereby allowing for 765kV L11216 (currently on Bus 6) to be relocated to Bus 8. Along with this line relocation, installation of 2-765kV BT CBs (6-8 & 8-2). Cost increased from $12M to $55M. This will eliminate the stuck breaker contingencies '112-65-BT4-5__' and '112-65-BT5-6__'. No other contingency updates needed.
Total Cost ($USD)
$55,229,373
Discounted Total Cost ($USD)
$55,229,373
Allocated Cost ($USD)
$0
Time Estimate
Jun 30 2026

Not Contingent

Note: AF2-226 contributes to the loading of an overloaded facility that is being mitigated by a network upgrade that was securitized by a prior Queue/Cycle. AF2-226 is not contingent on this network upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
(Any)COMED_P4_112-65-BT4-5___SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4_112-65-BT5-6___SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4_112-65-BT2-3___SRT-A
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AF2-226


AF2-226 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AF2-226 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AF2-226 One Line Diagram

AF2-226 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.