AF2-299 Final System Impact Study (Retool 1) Report

v1.00 released 2025-12-08 18:20

Fields 34.5 kV

10.8 MW Capacity / 18.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Jarratt Energy Facility, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the TC1 projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.
Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of TC1 projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed a Solar generating facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Greensville County, Virginia. The installed facilities will have a total capability of 18.0 MW with 10.8 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AF2-299
Project Name:
Fields 34.5 kV
Project Developer Name:
Jarratt Energy Facility, LLC
State:
Virginia
County:
Greensville
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
18.0
MWE:
18.0
MWC:
10.8
Fuel Type:
Solar
Basecase Study Year:
2027

Physical Interconnection Facility Study

Not Required

A Physical Interconnection Facilities Study is not required for this project.

Point of Interconnection

AF2-299 will interconnect with the Dominion distribution system via a connection to the existing Fields 115/34.5 kV substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AF2-299 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AF2-299Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$515,000$0
Total$515,000$0

* Contributes to calculation for Security. See Security Section of this report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF2-299

Security has been calculated for the AF2-299 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF2-299
Project(s): AF2-299
Final Agreement Security (A): $0
Portion of Costs Already Paid (B): $0
Revised Net Security (C): A − B = $0
Security on Hand with PJM (D): $0
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

AF2-299 will interconnect with the Dominion distribution system. The POI is a direct connection to an existing Fields 34.5 kV substation in the Dominion area.

No TO Interconnection Facilities or Physical Network Upgrades are required for this project.

The costs associated with interconnecting AF2-299 to the Dominion distribution system will be documented in the two-party Interconnection Agreement between the Project Developer and the Transmission Owner. The Project Developer will need to coordinate with the Transmission Owner for scope, cost and schedule for this physical interconnection. This PJM report identifies the effects on the transmission system.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2027 load flow model and the results were verified by Dominion.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AF2-299 was evaluated as a 18.0 MW (10.8 MW Capacity) injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1CPLE/DVP
3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line
DVP_P7-1: LN 2058-2181_SRT-A
TowerAC119.41 %313.0B373.751.3
GD1DVP
6BUCKING-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC113.03 %571.52B645.990.94
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC110.49 %1204.0C1330.342.6
GD1DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC108.7 %1204.0C1308.782.6
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC142.63 %812.0C1158.141.51
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC133.85 %663.64B888.270.86
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 217_SRT-A
SingleAC109.77 %663.64B728.50.82
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P4-2: 246T247_SRT-A
BreakerAC112.58 %830.0C934.437.58
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P4-2: 24642_SRT-A
BreakerAC107.8 %830.0C894.717.54
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P4-2: 24662_SRT-A
BreakerAC107.79 %830.0C894.667.53
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC100.22 %678.68B680.184.4
GD1DVP
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2092_SRT-A
SingleAC118.32 %571.52B676.241.11
GD1DVP
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2131_SRT-A
SingleAC116.14 %571.52B663.741.11
GD1DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: H2T557_SRT-S
BreakerAC132.14 %1065.0C1407.282.09
GD1DVP
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S-1
BreakerAC117.22 %684.0C801.791.57
GD1DVP
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC114.05 %559.3B637.860.94
GD1DVP
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
DVP_P1-2: LN 2092_SRT-A
SingleAC113.42 %571.52B648.231.11
GD1DVP
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
DVP_P1-2: LN 2131_SRT-A
SingleAC111.23 %571.52B635.731.11
GD1DVP
6POE-6TYLER1 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC104.13 %541.0C563.341.45
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P4-2: 246T247_SRT-A
BreakerAC123.57 %830.0C1025.657.58
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC112.21 %678.68B761.574.4
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 246_SRT-A
SingleAC111.1 %678.68B753.984.52
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC106.16 %3940.0C4182.744.51
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC104.22 %3940.0C4106.124.31
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H1T567_SRT-A
BreakerAC103.44 %3940.0C4075.554.45
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
SingleAC100.39 %1058.16B1062.250.8
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC108.98 %3940.0C4293.984.79
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC104.85 %3940.0C4130.984.7
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S_SENS
BreakerAC102.96 %3940.0C4056.764.53
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S_SENS
SingleAC102.07 %3220.44B3287.012.65
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC102.59 %3144.0C3225.323.2
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC102.48 %3144.0C3221.973.43
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC102.48 %3144.0C3221.973.43
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC102.48 %3144.0C3221.813.43
GD1DVP
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
DVP_P4-2: 246T247_SRT-A
BreakerAC123.02 %830.0C1021.047.58
GD1DVP
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC109.42 %678.68B742.634.4
GD1DVP
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
DVP_P1-2: LN 246_SRT-A
SingleAC108.28 %678.68B734.844.52

Details for 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2058-2181_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.41 %
Rating:313.0 MVA
Rating Type:B
MVA to Mitigate:373.75
MW Contribution:1.3
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2058-2181_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.28 %
Rating:313.0 MVA
Rating Type:B
MVA to Mitigate:354.58
MW Contribution:1.33
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
962572AG1-106 E
50/50
0.7230.723
926214AC1-099 E
50/50
1.7261.726
932632AC2-084 E
50/50
4.6194.619
946282AF1-292 E
Adder
0.42941176470588230.365
957861AF2-080 C
50/50
5.4735.473
917512Z2-088 E OP1
50/50
4.2784.278
960082AF2-299 E
Adder
0.51882352941176470.441
946281AF1-292 C
Adder
0.64470588235294120.548
926071AC1-086 C
50/50
12.78312.783
316317KELFORD C
50/50
0.3020.302
927021AC1-189 C
50/50
6.0266.026
924152AB2-059 E OP
50/50
14.32214.322
933982AD1-022 E
Adder
1.62117647058823521.378
927146AC1-208 E
50/50
6.0296.029
316049AB1-081 C OP
50/50
3.8543.854
3145393UNCAMP
Adder
1.8752941176470591.594
933981AD1-022 C
Adder
2.97764705882352982.531
900672V4-068 E
Adder
0.168235294117647040.143
3151261ROARAP2
50/50
0.8440.844
3137643SOCKMAN
Adder
0.40.34
316212AC1-099 C
50/50
0.4520.452
919710AA2-057 E
50/50
8.3988.398
316319Z2-044 C
50/50
0.5230.523
934501AD1-074 C
Adder
10.6670588235294139.067
924517AB2-100 E2
Adder
1.24470588235294131.058
3151371ROSEMS1
50/50
0.860.86
961671AG1-007 C
50/50
0.9370.937
316359AB2-059 C OP
50/50
4.5434.543
920042AA2-088 E OP
Adder
4.582352941176473.895
934521AD1-076 C
Adder
3.8741176470588243.293
934511AD1-075 C
Adder
2.66705882352941172.267
3145723EMPORIA
Adder
0.189411764705882360.161
316011AB1-132 C OP
50/50
1.4191.419
923573AB1-173 E OP
Adder
1.65882352941176461.41
919692AA2-053 E OP
50/50
2.5162.516
925785AC1-054 E
Adder
1.18705882352941171.009
316263AC1-034 C
50/50
18.00818.008
961942AG1-037 E
Adder
0.174117647058823520.148
961941AG1-037 C
Adder
0.260.221
3151391GASTONA
50/50
1.8581.858
3151381ROSEMG2
50/50
0.650.65
934332AD1-057 E
50/50
1.9141.914
934331AD1-057 C
50/50
3.6763.676
934321AD1-056 C
50/50
6.596.59
934322AD1-056 E
50/50
3.5743.574
927022AC1-189 E
50/50
3.0023.002
925595AC1-034 E
50/50
13.58513.585
3145413WATKINS
Adder
0.240.204
960081AF2-299 C
Adder
0.77882352941176480.662
926072AC1-086 E
50/50
5.8185.818
957862AF2-080 E
50/50
2.4262.426
934522AD1-076 E
Adder
1.97411764705882351.678
943172AE2-346 E
Adder
0.31294117647058830.266
918492AA1-063AE OP
Adder
2.2223529411764711.889
962571AG1-106 C
50/50
1.6531.653
917332KELFORD E
50/50
1.3871.387
925122AB2-169 E
Adder
2.0305882352941181.726
932631AC2-084 C
50/50
1.4371.437
316274AC1-208 C
50/50
13.57713.577
917342Z2-044 E
50/50
1.4831.483
3151311EDGECMA
50/50
21.06121.061
934512AD1-075 E
Adder
1.35764705882352941.154
934502AD1-074 E
Adder
5.4305882352941184.616
924516AB2-100 E1
Adder
1.24470588235294131.058
918512AA1-065 E OP
Adder
2.24588235294117671.909
966621AG1-532 C
Adder
0.58470588235294120.497
918532AA1-067 E
Adder
0.28117647058823530.239
316141AB2-099 E
Adder
0.130588235294117640.111
316088AB2-174 E
Adder
3.11764705882352942.65
923994AB2-040_E
Adder
3.1117647058823532.645
3151361ROSEMG1
50/50
1.3891.389
961672AG1-007 E
50/50
0.5310.531
316210AC1-098 C
50/50
1.351.35
926206AC1-098 E
50/50
5.2255.225
316327AA2-057 C
50/50
2.7552.755
923263AB1-132 E OP
50/50
3.723.72
3151411GASTONB
50/50
1.8581.858
3156063AA2-053SOLA
50/50
0.8980.898
3151281ROARAP4
50/50
0.7990.799
3156011CONETOE2SOL
50/50
1.0931.093
966622AG1-532 E
Adder
0.38941176470588240.331
922923AB1-081 E OP
50/50
10.1110.11
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
2.4822.482
G-007ALTFEXP_G-007A->PJM
CMTX
0.3460.346
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.1150.115
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.3950.395
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.2431.243
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
2.5362.536
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.5711.571
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.8040.804
VTFLTFEXP_VFT->PJM
CMTX
0.9190.919
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.7690.769
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.2722.272
MDUPJM->LTFIMP_MDU
CLTF
0.0820.082

Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.03 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:645.99
MW Contribution:0.94
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.98 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:685.72
MW Contribution:0.91
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
Adder
-5.884705882352941-5.002
934611AD1-087 C
80/20
2.212.21
316049AB1-081 C OP
80/20
0.4770.477
3151611KERR 4
80/20
1.5611.561
3156073AA1-063SOLA
80/20
0.5840.584
3151371ROSEMS1
80/20
0.3840.384
934621AD1-088 C
80/20
18.88618.886
316359AB2-059 C OP
80/20
0.5620.562
946301AF1-294 C
80/20
9.6099.609
942461AE2-259 C
80/20
31.13331.133
316197AC1-042 C
80/20
0.1420.142
316087AB2-174 C
80/20
0.5880.588
313527AB2-043 C
80/20
0.9080.908
3151591KERR 2
80/20
1.5611.561
316283AC2-100 C
80/20
1.2351.235
3151391GASTONA
80/20
0.9230.923
3151381ROSEMG2
80/20
0.2910.291
934331AD1-057 C
80/20
1.1031.103
934321AD1-056 C
80/20
1.9781.978
958211AF2-115 C
80/20
5.8435.843
316129AC1-054 C
80/20
1.1891.189
316131AB2-060 C
80/20
2.662.66
3138533PONTONDP
80/20
1.7311.731
316118AC1-105 C
80/20
1.3691.369
316217AC1-145 C
80/20
0.1690.169
946281AF1-292 C
80/20
0.7790.779
926071AC1-086 C
80/20
6.3516.351
3151531CLOVER1
80/20
22.47222.472
964241AG1-285 C
80/20
25.13225.132
316034AC1-036 C
80/20
0.5340.534
962561AG1-105 C
80/20
14.16114.161
942671AE2-283 C
80/20
1.5211.521
962571AG1-106 C
80/20
0.8210.821
932631AC2-084 C
80/20
0.3610.361
316274AC1-208 C
80/20
3.5413.541
3151311EDGECMA
80/20
5.0375.037
3151601KERR 3
80/20
1.5611.561
3151581KERR 1
80/20
0.5570.557
3152661PLYWOOD A
80/20
1.751.75
941011AE2-092 C
Adder
-9.714117647058824-8.257
3151261ROARAP2
80/20
0.6810.681
3147043LAWRENC
80/20
0.2660.266
3151621KERR 5
80/20
1.5611.561
316222AC1-221 C
80/20
1.5791.579
3137643SOCKMAN
80/20
0.3520.352
316212AC1-099 C
80/20
0.1130.113
316319Z2-044 C
80/20
0.0740.074
937481AD2-202 C
80/20
0.6410.641
3151641KERR 7
80/20
1.5611.561
316123AC1-075 C
80/20
0.9530.953
316205AC1-080 C
80/20
0.3190.319
316011AB1-132 C OP
80/20
0.7050.705
316263AC1-034 C
80/20
2.2292.229
959311AF2-222 C
80/20
38.88338.883
942751AE2-291 C
80/20
8.1298.129
3151561HALLBR1
80/20
0.5580.558
960081AF2-299 C
80/20
0.9410.941
3151541CLOVER2
80/20
22.26222.262
3151631KERR 6
80/20
1.5611.561
936261AD2-033 C
80/20
27.64927.649
961791AG1-021 C
80/20
4.6754.675
3144293JTRSVLE
80/20
1.0761.076
316248AF1-058 C
80/20
0.450.45
936171AD2-023 C
80/20
2.1112.111
941801AE2-185 C
80/20
1.9561.956
966621AG1-532 C
80/20
0.7060.706
316003AC1-222 C
80/20
1.3481.348
936161AD2-022 C
80/20
3.6193.619
313506AB1-173 C OP
80/20
0.5620.562
3151361ROSEMG1
80/20
0.6210.621
957481AF2-042 C
80/20
97.99997.999
316210AC1-098 C
80/20
0.3390.339
316327AA2-057 C
80/20
0.4730.473
316239AB2-077 C O1
80/20
0.5670.567
935171AD1-152 C
80/20
2.1552.155
964791AG1-342 C
80/20
5.5355.535
3151411GASTONB
80/20
0.9230.923
316181AB2-040 GEN
80/20
0.6330.633
3156063AA2-053SOLA
80/20
0.6790.679
3151281ROARAP4
80/20
0.6440.644
316238AB2-078 C O1
80/20
0.5670.567
316237AB2-079 C O1
80/20
0.5670.567
938821AE1-108 C
Adder
-10.596470588235293-9.007
316322AB2-045 C
80/20
1.2941.294
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1162.116
CBM South 2LTFEXP_CBM-S2->PJM
CBM
35.17235.172
CPLELTFEXP_CPLE->PJM
CLTF
4.444.44
TVALTFEXP_TVA->PJM
CLTF
1.9591.959
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.0479.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.0847.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1891.189
LAGNLTFEXP_LAGN->PJM
CLTF
2.5082.508
NYPJM->LTFIMP_NY
CLTF
0.3750.375
LGEELTFEXP_LGEE->PJM
CLTF
0.3550.355
WECLTFEXP_WEC->PJM
CLTF
0.1880.188
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.49 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1330.34
MW Contribution:2.6
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.67 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1404.76
MW Contribution:2.54
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940541AE2-040 C
50/50
3.3223.322
940481AE2-033 C
50/50
18.24118.241
940482AE2-033 E
50/50
12.29712.297
923263AB1-132 E OP
50/50
4.64.6
3151411GASTONB
50/50
2.2972.297
923852AB2-025 E
50/50
1.3441.344
939412AE1-173 E
Adder
33.1823529411764728.205
961942AG1-037 E
Adder
0.167058823529411760.142
961941AG1-037 C
Adder
0.251764705882352950.214
3151391GASTONA
50/50
2.2972.297
3151381ROSEMG2
50/50
0.7050.705
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934332AD1-057 E
Adder
1.21529411764705891.033
934331AD1-057 C
Adder
2.33411764705882341.984
934321AD1-056 C
Adder
4.1835294117647063.556
316023AB2-100 C2
50/50
0.8890.889
960082AF2-299 E
50/50
1.0391.039
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
3151051BRUNSWICKS1
50/50
12.19612.196
963042AG1-153 E
50/50
5.9665.966
927021AC1-189 C
Adder
4.5788235294117653.892
964241AG1-285 C
Adder
7.502352941176476.377
924152AB2-059 E OP
Adder
3.18705882352941172.709
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
936172AD2-023 E
Adder
1.21058823529411751.029
316141AB2-099 E
Adder
0.125882352941176470.107
316088AB2-174 E
50/50
5.0815.081
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151361ROSEMG1
50/50
1.5051.505
957481AF2-042 C
50/50
34.00834.008
961672AG1-007 E
Adder
0.30352941176470590.258
924322AB2-079 E O1
Adder
0.7917647058823530.673
946302AF1-294 E
Adder
1.46000000000000021.241
943902AF1-058 E
Adder
0.71411764705882350.607
3145413WATKINS
Adder
0.265882352941176460.226
960081AF2-299 C
50/50
1.5581.558
926072AC1-086 E
50/50
7.1937.193
944011AF1-069 C
50/50
9.4749.474
963041AG1-153 C
50/50
3.9773.977
957862AF2-080 E
Adder
1.84352941176470591.567
936261AD2-033 C
Adder
7.0082352941176475.957
961791AG1-021 C
Adder
0.83882352941176460.713
962562AG1-105 E
Adder
3.39764705882352922.888
936171AD2-023 C
Adder
2.23058823529411751.896
316181AB2-040 GEN
50/50
0.9590.959
3151281ROARAP4
50/50
0.8680.868
3152441Z1-086 ST
50/50
13.14613.146
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
925612AC1-036 E
Adder
0.47058823529411770.4
924312AB2-078 E O1
Adder
0.7917647058823530.673
926274AC1-105 E
Adder
1.50823529411764711.282
3145393UNCAMP
Adder
2.10941176470588231.793
933981AD1-022 C
Adder
3.6082352941176473.067
900672V4-068 E
Adder
0.172941176470588240.147
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
924302AB2-077 E O1
Adder
0.7917647058823530.673
316087AB2-174 C
50/50
0.9180.918
962572AG1-106 E
50/50
0.8940.894
926214AC1-099 E
Adder
0.70941176470588230.603
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
920042AA2-088 E OP
Adder
4.9317647058823534.192
934322AD1-056 E
Adder
2.26941176470588251.929
927022AC1-189 E
Adder
2.28117647058823541.939
925595AC1-034 E
Adder
3.0235294117647062.57
936262AD2-033 E
Adder
4.6729411764705883.972
958211AF2-115 C
Adder
1.04823529411764720.891
934521AD1-076 C
Adder
4.7823529411764714.065
934511AD1-075 C
Adder
3.2917647058823532.798
3145723EMPORIA
50/50
0.3510.351
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
919692AA2-053 E OP
Adder
2.6788235294117652.277
925785AC1-054 E
Adder
2.1505882352941181.828
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
942001AE2-212 C
Adder
-3.7917647058823527-3.223
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
3151371ROSEMS1
50/50
0.9320.932
957482AF2-042 E
50/50
22.67222.672
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
946301AF1-294 C
Adder
1.7247058823529411.466
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
936162AD2-022 E
Adder
2.29411764705882341.95
920692AA2-178 E
Adder
1.43529411764705881.22
966622AG1-532 E
50/50
0.7790.779
922923AB1-081 E OP
Adder
2.24941176470588241.912
3147133PAMPLIN
Adder
0.454117647058823570.386
927264AC1-222 E
Adder
2.16588235294117661.841
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
933982AD1-022 E
Adder
1.9647058823529411.67
927146AC1-208 E
Adder
2.45294117647058842.085
934622AD1-088 E
Adder
2.72588235294117662.317
934612AD1-087 E
Adder
2.20941176470588241.878
927255AC1-221 E
Adder
2.0517647058823531.744
932632AC2-084 E
Adder
1.89764705882352951.613
964242AG1-285 E
Adder
5.0011764705882364.251
924162AB2-060 E OP
Adder
2.522.142
964792AG1-342 E
Adder
1.34588235294117631.144
932763AC2-100 E
Adder
1.3917647058823531.183
939411AE1-173 C
Adder
49.7729411764705942.307
3137643SOCKMAN
50/50
0.5020.502
3151031BRUNSWICKG2
50/50
5.8715.871
919710AA2-057 E
Adder
2.3988235294117652.039
316315AB2-025 C
50/50
0.4720.472
946282AF1-292 E
50/50
0.860.86
944012AF1-069 E
50/50
3.683.68
957861AF2-080 C
Adder
4.1588235294117653.535
917512Z2-088 E OP1
Adder
2.742.329
3138533PONTONDP
Adder
0.310588235294117660.264
940492AE2-034 E
Adder
1.07647058823529430.915
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
918492AA1-063AE OP
Adder
2.40470588235294122.044
962571AG1-106 C
50/50
2.0442.044
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
316274AC1-208 C
Adder
5.5235294117647074.695
917342Z2-044 E
Adder
0.36117647058823530.307
937482AD2-202 E
Adder
0.64705882352941180.55
3151311EDGECMA
Adder
9.4070588235294137.996
961792AG1-021 E
Adder
0.71411764705882350.607
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
924516AB2-100 E1
50/50
2.6782.678
918512AA1-065 E OP
Adder
2.60941176470588232.218
966621AG1-532 C
50/50
1.1691.169
918532AA1-067 E
Adder
0.367058823529411770.312
924022AB2-043 E O1
Adder
3.07764705882352942.616
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
926024AC1-080 E
Adder
0.454117647058823570.386
936161AD2-022 C
Adder
3.8235294117647063.25
3143316POE
Adder
0.51176470588235290.435
316365AB2-100 C1
50/50
0.8890.889
926206AC1-098 E
Adder
2.14705882352941171.825
3151041BRUNSWICKG3
50/50
5.8715.871
3151021BRUNSWICKG1
50/50
5.8715.871
942462AE2-259 E
Adder
2.62.21
964791AG1-342 C
Adder
2.0188235294117651.716
925997AC1-075 E
Adder
1.36941176470588231.164
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.7 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1308.78
MW Contribution:2.6
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.88 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1383.11
MW Contribution:2.54
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940492AE2-034 E
Adder
1.07647058823529430.915
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
918492AA1-063AE OP
Adder
2.40470588235294122.044
962571AG1-106 C
50/50
2.0442.044
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
316274AC1-208 C
Adder
5.5235294117647074.695
917342Z2-044 E
Adder
0.36117647058823530.307
937482AD2-202 E
Adder
0.64705882352941180.55
3151311EDGECMA
Adder
9.4070588235294137.996
961792AG1-021 E
Adder
0.71411764705882350.607
316023AB2-100 C2
50/50
0.8890.889
960082AF2-299 E
50/50
1.0391.039
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
3151051BRUNSWICKS1
50/50
12.19612.196
963042AG1-153 E
50/50
5.9665.966
927021AC1-189 C
Adder
4.5788235294117653.892
964241AG1-285 C
Adder
7.502352941176476.377
924152AB2-059 E OP
Adder
3.18705882352941172.709
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
936172AD2-023 E
Adder
1.21058823529411751.029
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
920042AA2-088 E OP
Adder
4.9317647058823534.192
934521AD1-076 C
Adder
4.7823529411764714.065
934511AD1-075 C
Adder
3.2917647058823532.798
3145723EMPORIA
50/50
0.3510.351
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
919692AA2-053 E OP
Adder
2.6788235294117652.277
925785AC1-054 E
Adder
2.1505882352941181.828
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
940541AE2-040 C
50/50
3.3223.322
940481AE2-033 C
50/50
18.24118.241
940482AE2-033 E
50/50
12.29712.297
923263AB1-132 E OP
50/50
4.64.6
3151411GASTONB
50/50
2.2972.297
316181AB2-040 GEN
50/50
0.9590.959
3151281ROARAP4
50/50
0.8680.868
3152441Z1-086 ST
50/50
13.14613.146
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
925612AC1-036 E
Adder
0.47058823529411770.4
924312AB2-078 E O1
Adder
0.7917647058823530.673
926274AC1-105 E
Adder
1.50823529411764711.282
942001AE2-212 C
Adder
-3.7917647058823527-3.223
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
3151371ROSEMS1
50/50
0.9320.932
957482AF2-042 E
50/50
22.67222.672
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
946301AF1-294 C
Adder
1.7247058823529411.466
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
936162AD2-022 E
Adder
2.29411764705882341.95
923852AB2-025 E
50/50
1.3441.344
939412AE1-173 E
Adder
33.1823529411764728.205
961942AG1-037 E
Adder
0.167058823529411760.142
961941AG1-037 C
Adder
0.251764705882352950.214
3151391GASTONA
50/50
2.2972.297
3151381ROSEMG2
50/50
0.7050.705
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934332AD1-057 E
Adder
1.21529411764705891.033
934331AD1-057 C
Adder
2.33411764705882341.984
934321AD1-056 C
Adder
4.1835294117647063.556
934322AD1-056 E
Adder
2.26941176470588251.929
927022AC1-189 E
Adder
2.28117647058823541.939
925595AC1-034 E
Adder
3.0235294117647062.57
936262AD2-033 E
Adder
4.6729411764705883.972
958211AF2-115 C
Adder
1.04823529411764720.891
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
924516AB2-100 E1
50/50
2.6782.678
918512AA1-065 E OP
Adder
2.60941176470588232.218
966621AG1-532 C
50/50
1.1691.169
918532AA1-067 E
Adder
0.367058823529411770.312
924022AB2-043 E O1
Adder
3.07764705882352942.616
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
926024AC1-080 E
Adder
0.454117647058823570.386
936161AD2-022 C
Adder
3.8235294117647063.25
316141AB2-099 E
Adder
0.125882352941176470.107
316088AB2-174 E
50/50
5.0815.081
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151361ROSEMG1
50/50
1.5051.505
957481AF2-042 C
50/50
34.00834.008
961672AG1-007 E
Adder
0.30352941176470590.258
924322AB2-079 E O1
Adder
0.7917647058823530.673
946302AF1-294 E
Adder
1.46000000000000021.241
943902AF1-058 E
Adder
0.71411764705882350.607
3145413WATKINS
Adder
0.265882352941176460.226
960081AF2-299 C
50/50
1.5581.558
926072AC1-086 E
50/50
7.1937.193
944011AF1-069 C
50/50
9.4749.474
963041AG1-153 C
50/50
3.9773.977
957862AF2-080 E
Adder
1.84352941176470591.567
936261AD2-033 C
Adder
7.0082352941176475.957
961791AG1-021 C
Adder
0.83882352941176460.713
962562AG1-105 E
Adder
3.39764705882352922.888
936171AD2-023 C
Adder
2.23058823529411751.896
3145393UNCAMP
Adder
2.10941176470588231.793
933981AD1-022 C
Adder
3.6082352941176473.067
900672V4-068 E
Adder
0.172941176470588240.147
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
924302AB2-077 E O1
Adder
0.7917647058823530.673
316087AB2-174 C
50/50
0.9180.918
962572AG1-106 E
50/50
0.8940.894
926214AC1-099 E
Adder
0.70941176470588230.603
932632AC2-084 E
Adder
1.89764705882352951.613
964242AG1-285 E
Adder
5.0011764705882364.251
924162AB2-060 E OP
Adder
2.522.142
964792AG1-342 E
Adder
1.34588235294117631.144
932763AC2-100 E
Adder
1.3917647058823531.183
920692AA2-178 E
Adder
1.43529411764705881.22
966622AG1-532 E
50/50
0.7790.779
922923AB1-081 E OP
Adder
2.24941176470588241.912
3147133PAMPLIN
Adder
0.454117647058823570.386
927264AC1-222 E
Adder
2.16588235294117661.841
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
933982AD1-022 E
Adder
1.9647058823529411.67
927146AC1-208 E
Adder
2.45294117647058842.085
934622AD1-088 E
Adder
2.72588235294117662.317
934612AD1-087 E
Adder
2.20941176470588241.878
927255AC1-221 E
Adder
2.0517647058823531.744
939411AE1-173 C
Adder
49.7729411764705942.307
3137643SOCKMAN
50/50
0.5020.502
3151031BRUNSWICKG2
50/50
5.8715.871
919710AA2-057 E
Adder
2.3988235294117652.039
316315AB2-025 C
50/50
0.4720.472
946282AF1-292 E
50/50
0.860.86
944012AF1-069 E
50/50
3.683.68
957861AF2-080 C
Adder
4.1588235294117653.535
917512Z2-088 E OP1
Adder
2.742.329
3138533PONTONDP
Adder
0.310588235294117660.264
3143316POE
Adder
0.51176470588235290.435
316365AB2-100 C1
50/50
0.8890.889
926206AC1-098 E
Adder
2.14705882352941171.825
3151041BRUNSWICKG3
50/50
5.8715.871
3151021BRUNSWICKG1
50/50
5.8715.871
942462AE2-259 E
Adder
2.62.21
964791AG1-342 C
Adder
2.0188235294117651.716
925997AC1-075 E
Adder
1.36941176470588231.164
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.63 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1158.14
MW Contribution:1.51
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.2 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1065.31
MW Contribution:1.48
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150731STONECA
50/50
4.7614.761
935161AD1-151 C
50/50
9.2889.288
932046AC2-012 E
Adder
4.1552941176470593.532
316084AB2-161 E
50/50
3.3973.397
3150651CHESTF6
50/50
25.13725.137
946262AF1-291 E
50/50
1.8721.872
940432AE2-027 E
Adder
3.68588235294117663.133
934012AD1-025 E
Adder
5.4482352941176474.631
942341AE2-247 C
Adder
0.69882352941176470.594
943462AF1-017 E
Adder
1.03058823529411760.876
3150801HOPHCF4
50/50
2.5532.553
316349AD2-085 C
Adder
1.61058823529411771.369
935112AD1-144 E
Adder
0.315294117647058840.268
944582AF1-123 E
Adder
31.66823529411764726.918
944592AF1-124 E
Adder
31.78352941176470427.016
961611AG1-000B C
Adder
7.286.188
940541AE2-040 C
50/50
1.7731.773
940481AE2-033 C
50/50
9.8069.806
940482AE2-033 E
50/50
6.6116.611
923263AB1-132 E OP
Adder
2.8364705882352942.411
924312AB2-078 E O1
Adder
0.448235294117647070.381
926274AC1-105 E
Adder
0.860.731
3150781HOPHCF2
50/50
1.6821.682
942001AE2-212 C
50/50
2.3882.388
939192AE1-149 E
50/50
5.125.12
939312AE1-162 E
Adder
0.54941176470588240.467
3150761HOPPOLC
50/50
1.0581.058
3150791HOPHCF3
50/50
1.6821.682
926662AC1-147 E
Adder
0.420.357
916192Z1-068 E
Adder
0.58588235294117650.498
957492AF2-043 E
Adder
0.4717647058823530.401
923852AB2-025 E
50/50
0.7170.717
939412AE1-173 E
Adder
23.37764705882352719.871
961942AG1-037 E
Adder
0.132941176470588230.113
961941AG1-037 C
Adder
0.198823529411764730.169
941032AE2-094 E
Adder
7.6070588235294126.466
941031AE2-094 C
Adder
16.9847058823529414.437
934332AD1-057 E
Adder
0.76705882352941180.652
934331AD1-057 C
Adder
1.47294117647058821.252
934321AD1-056 C
Adder
2.642.244
934322AD1-056 E
Adder
1.4317647058823531.217
927022AC1-189 E
Adder
1.59882352941176481.359
925595AC1-034 E
Adder
1.95294117647058821.66
923832AB2-022 E
Adder
0.397647058823529460.338
938772AE1-103 E
Adder
1.55882352941176471.325
916042Z1-036 E
Adder
9.7517647058823538.289
960082AF2-299 E
Adder
0.60352941176470590.513
946281AF1-292 C
Adder
0.74941176470588230.637
926071AC1-086 C
Adder
9.7470588235294138.285
963042AG1-153 E
Adder
3.4917647058823532.968
927021AC1-189 C
Adder
3.2094117647058832.728
964241AG1-285 C
Adder
4.1952941176470593.566
924152AB2-059 E OP
Adder
2.0588235294117651.75
962561AG1-105 C
Adder
2.89529411764705862.461
3150771HOPHCF1
50/50
1.6821.682
940431AE2-027 C
Adder
5.5282352941176474.699
942002AE2-212 E
50/50
1.5921.592
316132AB2-190 C
50/50
2.4992.499
944581AF1-123 C
Adder
13.82941176470588311.755
941101AE2-104 C
Adder
1.2482352941176471.061
316141AB2-099 E
Adder
0.098823529411764710.084
316088AB2-174 E
Adder
3.04352941176470632.587
923994AB2-040_E
Adder
2.8235294117647062.4
957481AF2-042 C
Adder
19.4705882352941216.55
961672AG1-007 E
Adder
0.204705882352941150.174
924322AB2-079 E O1
Adder
0.448235294117647070.381
925332AB2-190 E
50/50
4.8614.861
927226AC1-216 E
Adder
4.2082352941176473.577
936666AD2-085 E
Adder
2.62823529411764722.234
941591AE2-156 C
Adder
5.6635294117647064.814
944591AF1-124 C
Adder
13.87882352941176711.797
944601AF1-125 C
Adder
13.61647058823529511.574
938771AE1-103 C
Adder
1.1282352941176470.959
3145413WATKINS
Adder
0.271764705882352960.231
960081AF2-299 C
Adder
0.90588235294117650.77
926072AC1-086 E
Adder
4.4364705882352943.771
944011AF1-069 C
Adder
5.5494117647058824.717
963041AG1-153 C
Adder
2.32823529411764741.979
957862AF2-080 E
Adder
1.29176470588235311.098
962562AG1-105 E
Adder
1.93058823529411771.641
958161AF2-110 C
Adder
0.50941176470588230.433
938531AE1-072 C
Adder
5.49411764705882364.67
3145393UNCAMP
Adder
2.362.006
933981AD1-022 C
Adder
3.22705882352941182.743
900672V4-068 E
Adder
0.14235294117647060.121
924302AB2-077 E O1
Adder
0.448235294117647070.381
3145256KINGFORK
Adder
0.33882352941176470.288
925522AC1-027 E
Adder
0.380.323
941102AE2-104 E
Adder
1.98470588235294131.687
957872AF2-081 E
Adder
1.33058823529411761.131
962572AG1-106 E
Adder
0.55176470588235290.469
926214AC1-099 E
Adder
0.484705882352941150.412
932632AC2-084 E
Adder
1.2988235294117651.104
964242AG1-285 E
Adder
2.7964705882352942.377
924162AB2-060 E OP
Adder
1.41882352941176461.206
964792AG1-342 E
Adder
0.76588235294117660.651
944641AF1-129 C
50/50
138.059138.059
316240AF1-291 C
50/50
2.8082.808
924814AB2-134 E
Adder
6.8941176470588245.86
316381AD1-082 C
50/50
0.7750.775
942342AE2-247 E
Adder
0.96470588235294120.82
919152AA1-139 E1
Adder
1.27058823529411781.08
920042AA2-088 E OP
Adder
4.2552941176470593.617
934521AD1-076 C
Adder
4.443.774
934511AD1-075 C
Adder
3.0564705882352942.598
3145723EMPORIA
Adder
0.205882352941176460.175
923573AB1-173 E OP
Adder
1.50588235294117641.28
919692AA2-053 E OP
Adder
1.7835294117647061.516
925785AC1-054 E
Adder
1.32352941176470581.125
316263AC1-034 C
Adder
2.5882352941176472.2
934065AD1-033 E
Adder
1.53411764705882361.304
937226AE2-253 E
Adder
1.80588235294117651.535
934501AD1-074 C
Adder
12.22470588235294110.391
924517AB2-100 E2
Adder
1.5282352941176471.299
957482AF2-042 E
Adder
12.9811.033
961671AG1-007 C
Adder
0.36235294117647060.308
934621AD1-088 C
Adder
3.18117647058823572.704
935172AD1-152 E
Adder
1.86235294117647051.583
935162AD1-151 E
50/50
6.1926.192
943461AF1-017 C
Adder
0.6317647058823530.537
932596AC2-079 E
Adder
4.2658823529411763.626
316311AC2-079 C
Adder
2.61529411764705882.223
938532AE1-072 E
Adder
2.8635294117647062.434
3146326AYDLETT TAP
Adder
0.424705882352941160.361
917122Z2-027 E
Adder
0.435294117647058830.37
920692AA2-178 E
Adder
1.45294117647058841.235
966622AG1-532 E
Adder
0.452941176470588240.385
922923AB1-081 E OP
Adder
1.45294117647058841.235
316083AB2-161 C
50/50
0.340.34
3145946PLYMOUTH TP
Adder
0.116470588235294130.099
933982AD1-022 E
Adder
1.75647058823529421.493
927146AC1-208 E
Adder
1.62941176470588231.385
934622AD1-088 E
Adder
1.53176470588235311.302
934612AD1-087 E
Adder
1.26235294117647071.073
913392Y1-086 E
Adder
0.70470588235294120.599
939411AE1-173 C
Adder
35.0670588235294129.807
3137643SOCKMAN
Adder
0.315294117647058840.268
919710AA2-057 E
Adder
1.58117647058823541.344
316315AB2-025 C
50/50
0.2520.252
946282AF1-292 E
Adder
0.50.425
944012AF1-069 E
Adder
2.1552941176470591.832
957861AF2-080 C
Adder
2.9152941176470592.478
917512Z2-088 E OP1
Adder
1.88000000000000011.598
934576AD1-082 E
50/50
2.7072.707
944602AF1-125 E
Adder
31.17176470588235326.496
3145506HICKORY
Adder
0.6682352941176470.568
943612AF1-032 E
Adder
0.30705882352941180.261
957871AF2-081 C
Adder
3.10588235294117652.64
940492AE2-034 E
Adder
1.08941176470588250.926
934522AD1-076 E
Adder
2.2623529411764711.923
943172AE2-346 E
Adder
0.238823529411764740.203
918492AA1-063AE OP
Adder
1.7070588235294121.451
962571AG1-106 C
Adder
1.26117647058823531.072
917332KELFORD E
Adder
0.65058823529411770.553
925122AB2-169 E
Adder
2.1235294117647061.805
316274AC1-208 C
Adder
3.6705882352941183.12
917342Z2-044 E
Adder
0.235294117647058850.2
937482AD2-202 E
Adder
0.36941176470588240.314
3151311EDGECMA
Adder
6.0682352941176485.158
958162AF2-110 E
Adder
0.81058823529411760.689
919153AA1-139 E2
Adder
1.27058823529411781.08
934512AD1-075 E
Adder
1.5552941176470591.322
934502AD1-074 E
Adder
6.222352941176475.289
924516AB2-100 E1
Adder
1.5282352941176471.299
918512AA1-065 E OP
Adder
2.12470588235294141.806
966621AG1-532 C
Adder
0.67999999999999990.578
918532AA1-067 E
Adder
0.269411764705882350.229
924022AB2-043 E O1
Adder
1.73764705882352951.477
939191AE1-149 C
50/50
7.6817.681
3143316POE
50/50
1.2311.231
901082W1-029 E
Adder
10.5541176470588248.971
926206AC1-098 E
Adder
1.4682352941176471.248
964791AG1-342 C
Adder
1.1482352941176470.976
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.8981.898
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.93631.936
CPLELTFEXP_CPLE->PJM
CLTF
3.9843.984
TVALTFEXP_TVA->PJM
CLTF
1.811.81
O66PJM->LTFIMP_O-066
CMTX_NF
6.2766.276
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.0758.075
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.5166.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.081.08
LAGNLTFEXP_LAGN->PJM
CLTF
2.3232.323
NYPJM->LTFIMP_NY
CLTF
0.4640.464
LGEELTFEXP_LGEE->PJM
CLTF
0.3190.319
WECLTFEXP_WEC->PJM
CLTF
0.1690.169
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9850.985
SIGELTFEXP_SIGE->PJM
CLTF
0.0650.065

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.85 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:888.27
MW Contribution:0.86
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.9 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:921.81
MW Contribution:0.84
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150731STONECA
80/20
4.8074.807
935161AD1-151 C
80/20
9.5159.515
3151221GRAVEL6
80/20
1.141.14
3151201GRAVEL4
80/20
1.1421.142
958161AF2-110 C
80/20
0.5350.535
938531AE1-072 C
Adder
6.04588235294117655.139
933981AD1-022 C
Adder
3.26941176470588252.779
3151261ROARAP2
80/20
0.5670.567
3147043LAWRENC
80/20
0.1270.127
3152411Z1-086 GT1
80/20
3.8333.833
944641AF1-129 C
80/20
137.537137.537
316240AF1-291 C
80/20
2.7922.792
3151191GRAVEL3
80/20
1.1271.127
316381AD1-082 C
80/20
0.7760.776
934521AD1-076 C
Adder
4.5247058823529423.846
3150781HOPHCF2
80/20
1.6981.698
942001AE2-212 C
80/20
2.3582.358
3151161SURRY 1
80/20
11.09811.098
934501AD1-074 C
Adder
12.4576470588235310.589
3156073AA1-063SOLA
80/20
0.570.57
3151371ROSEMS1
80/20
0.5510.551
961671AG1-007 C
Adder
0.34588235294117650.294
316083AB2-161 C
80/20
0.340.34
940641AE2-051 C
80/20
6.3516.351
316336AC2-165 C
Adder
-2.925882352941177-2.487
3150761HOPPOLC
80/20
1.0681.068
933291AC2-141 C
Adder
9.0470588235294127.69
316087AB2-174 C
80/20
0.5210.521
939411AE1-173 C
80/20
32.73632.736
3137643SOCKMAN
80/20
0.30.3
3151031BRUNSWICKG2
80/20
2.9812.981
3150791HOPHCF3
80/20
1.6981.698
316369AC1-216 C
80/20
0.90.9
961941AG1-037 C
Adder
0.196470588235294150.167
3151391GASTONA
80/20
1.3541.354
3151381ROSEMG2
80/20
0.4160.416
941031AE2-094 C
80/20
14.70614.706
934331AD1-057 C
Adder
1.39882352941176481.189
934321AD1-056 C
Adder
2.50705882352941162.131
316315AB2-025 C
80/20
0.2380.238
957861AF2-080 C
Adder
2.8035294117647062.383
3150801HOPHCF4
80/20
2.5782.578
316349AD2-085 C
80/20
1.6511.651
316023AB2-100 C2
80/20
0.4810.481
946281AF1-292 C
80/20
0.7080.708
926071AC1-086 C
80/20
9.3179.317
3151051BRUNSWICKS1
80/20
6.1926.192
927021AC1-189 C
Adder
3.0858823529411772.623
3150651CHESTF6
80/20
25.04225.042
957871AF2-081 C
Adder
3.42823529411764752.914
3151151S HAMPT1
80/20
0.5930.593
962571AG1-106 C
80/20
1.2051.205
316274AC1-208 C
Adder
3.50823529411764762.982
3151311EDGECMA
Adder
5.7282352941176474.869
934511AD1-075 C
Adder
3.1141176470588232.647
316011AB1-132 C OP
80/20
1.0341.034
316263AC1-034 C
Adder
2.44235294117647062.076
941591AE2-156 C
Adder
6.2764705882352945.335
944591AF1-124 C
Adder
15.47294117647058813.152
944601AF1-125 C
Adder
15.18117647058823612.904
938771AE1-103 C
80/20
1.1561.156
960081AF2-299 C
80/20
0.8560.856
944011AF1-069 C
80/20
4.8054.805
963041AG1-153 C
Adder
2.0188235294117651.716
3151171GRAVELC
80/20
0.3880.388
942341AE2-247 C
80/20
0.7150.715
966621AG1-532 C
80/20
0.6420.642
3150771HOPHCF1
80/20
1.6981.698
940431AE2-027 C
80/20
5.4285.428
316132AB2-190 C
80/20
2.552.55
944581AF1-123 C
Adder
15.41882352941176613.106
941101AE2-104 C
80/20
1.3111.311
3156083AA2-088SOLA
80/20
0.4240.424
313506AB1-173 C OP
80/20
0.4910.491
3151361ROSEMG1
80/20
0.8890.889
957481AF2-042 C
Adder
16.9176470588235314.38
316033AB2-134 GEN
80/20
1.1791.179
934011AD1-025 C
80/20
1.4591.459
939191AE1-149 C
80/20
7.67.6
316365AB2-100 C1
80/20
0.4810.481
3151041BRUNSWICKG3
80/20
2.9812.981
3151021BRUNSWICKG1
80/20
2.9812.981
961611AG1-000B C
80/20
7.6267.626
316236AE1-162 C
80/20
0.1440.144
940541AE2-040 C
80/20
1.6761.676
940481AE2-033 C
80/20
9.2759.275
3151411GASTONB
80/20
1.3541.354
316181AB2-040 GEN
80/20
0.5530.553
3156063AA2-053SOLA
80/20
0.6110.611
3151281ROARAP4
80/20
0.5360.536
3152441Z1-086 ST
80/20
6.6736.673
3152431Z1-086 GT3
80/20
3.8323.832
3152421Z1-086 GT2
80/20
3.8323.832
3151211GRAVEL5
80/20
1.1271.127
943461AF1-017 C
80/20
0.6470.647
316311AC2-079 C
80/20
2.6862.686
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7131.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.64628.646
CPLELTFEXP_CPLE->PJM
CLTF
3.5953.595
TVALTFEXP_TVA->PJM
CLTF
1.6011.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.8996.899
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.7315.731
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.9380.938
LAGNLTFEXP_LAGN->PJM
CLTF
2.0572.057
NYPJM->LTFIMP_NY
CLTF
0.4310.431
LGEELTFEXP_LGEE->PJM
CLTF
0.2740.274
WECLTFEXP_WEC->PJM
CLTF
0.1450.145
SIGELTFEXP_SIGE->PJM
CLTF
0.0560.056

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.77 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:728.5
MW Contribution:0.82
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.54 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:707.05
MW Contribution:0.8
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316083AB2-161 C
80/20
0.3740.374
316072AD1-144 C
80/20
0.0920.092
3150761HOPPOLC
80/20
1.2891.289
316305AF2-043 C
80/20
0.1080.108
316087AB2-174 C
80/20
0.4920.492
316315AB2-025 C
80/20
0.2430.243
3150801HOPHCF4
80/20
3.1113.111
316349AD2-085 C
80/20
1.6711.671
316023AB2-100 C2
80/20
0.4730.473
946281AF1-292 C
80/20
0.6770.677
926071AC1-086 C
80/20
8.8218.821
316317KELFORD C
80/20
0.1250.125
3150651CHESTF6
80/20
31.16731.167
957871AF2-081 C
Adder
2.91294117647058842.476
3151151S HAMPT1
80/20
0.5450.545
962571AG1-106 C
80/20
1.1411.141
932631AC2-084 C
80/20
0.3490.349
316274AC1-208 C
80/20
3.1613.161
3150731STONECA
80/20
5.8035.803
935161AD1-151 C
80/20
10.99910.999
3151221GRAVEL6
80/20
1.2011.201
3151201GRAVEL4
80/20
1.2021.202
958161AF2-110 C
80/20
0.4930.493
938531AE1-072 C
Adder
5.1458823529411764.374
315614AA2-178 C
80/20
0.5030.503
933981AD1-022 C
80/20
2.92.9
3151261ROARAP2
80/20
0.5210.521
3147043LAWRENC
80/20
0.1170.117
316140AB2-099 C
80/20
0.0340.034
3137643SOCKMAN
80/20
0.2790.279
316212AC1-099 C
80/20
0.110.11
3150781HOPHCF2
80/20
2.052.05
942001AE2-212 C
80/20
2.8572.857
3151161SURRY 1
80/20
11.68311.683
940491AE2-034 C
80/20
0.370.37
934501AD1-074 C
80/20
11.00411.004
3156021HOLLOMANSOL
80/20
0.6320.632
3156073AA1-063SOLA
80/20
0.5230.523
3151371ROSEMS1
80/20
0.5190.519
944641AF1-129 C
80/20
171.179171.179
316240AF1-291 C
80/20
3.4573.457
3151191GRAVEL3
80/20
1.1871.187
316381AD1-082 C
80/20
0.8530.853
934521AD1-076 C
80/20
3.9963.996
934511AD1-075 C
80/20
2.7512.751
316011AB1-132 C OP
80/20
0.9790.979
3150791HOPHCF3
80/20
2.052.05
316369AC1-216 C
80/20
1.0251.025
943171AE2-346 C
80/20
0.0790.079
961941AG1-037 C
80/20
0.1780.178
3151391GASTONA
80/20
1.2821.282
3151381ROSEMG2
80/20
0.3920.392
934331AD1-057 C
80/20
1.2741.274
934321AD1-056 C
80/20
2.2852.285
941591AE2-156 C
Adder
5.457647058823534.639
944591AF1-124 C
Adder
13.0623529411764711.103
944601AF1-125 C
Adder
12.8152941176470610.893
938771AE1-103 C
80/20
1.0631.063
960081AF2-299 C
80/20
0.8180.818
3151171GRAVELC
80/20
0.4080.408
942341AE2-247 C
80/20
0.7240.724
316246AF1-032 C
80/20
0.0890.089
966621AG1-532 C
80/20
0.6130.613
3150771HOPHCF1
80/20
2.052.05
940431AE2-027 C
80/20
6.666.66
316132AB2-190 C
80/20
2.9822.982
944581AF1-123 C
Adder
13.0152941176470611.063
941101AE2-104 C
80/20
1.2091.209
3156083AA2-088SOLA
80/20
0.3880.388
313506AB1-173 C OP
80/20
0.4620.462
3151361ROSEMG1
80/20
0.8370.837
316033AB2-134 GEN
80/20
1.3431.343
934011AD1-025 C
80/20
1.6611.661
939191AE1-149 C
80/20
8.6748.674
316365AB2-100 C1
80/20
0.4730.473
316318V4-068 C
80/20
0.0290.029
316210AC1-098 C
80/20
0.3280.328
961611AG1-000B C
80/20
8.238.23
316236AE1-162 C
80/20
0.1430.143
316375AC2-012 C
80/20
0.4130.413
940541AE2-040 C
80/20
1.7111.711
940481AE2-033 C
80/20
9.4279.427
3151411GASTONB
80/20
1.2821.282
316181AB2-040 GEN
80/20
0.520.52
3156063AA2-053SOLA
80/20
0.560.56
3151281ROARAP4
80/20
0.4930.493
3151211GRAVEL5
80/20
1.1871.187
943461AF1-017 C
80/20
0.6550.655
316311AC2-079 C
80/20
2.6932.693
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3561.356
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.36622.366
CPLELTFEXP_CPLE->PJM
CLTF
2.8462.846
TVALTFEXP_TVA->PJM
CLTF
1.211.21
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.844.84
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.2794.279
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.6820.682
LAGNLTFEXP_LAGN->PJM
CLTF
1.5581.558
NYPJM->LTFIMP_NY
CLTF
0.3360.336
LGEELTFEXP_LGEE->PJM
CLTF
0.1940.194
WECLTFEXP_WEC->PJM
CLTF
0.1020.102
SIGELTFEXP_SIGE->PJM
CLTF
0.040.04

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 246T247_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.58 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:934.43
MW Contribution:7.58
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 246T247_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.26 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:989.84
MW Contribution:7.66
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
923263AB1-132 E OP
50/50
13.58313.583
3151411GASTONB
50/50
6.7836.783
316181AB2-040 GEN
50/50
2.6442.644
316174AB2-169_C
50/50
1.0821.082
3156063AA2-053SOLA
50/50
2.4332.433
3151281ROARAP4
50/50
2.1872.187
3156011CONETOE2SOL
50/50
1.4931.493
961942AG1-037 E
50/50
0.440.44
943171AE2-346 C
50/50
0.2930.293
961941AG1-037 C
50/50
0.660.66
3151391GASTONA
50/50
6.7836.783
3151381ROSEMG2
50/50
2.0322.032
934332AD1-057 E
50/50
3.0163.016
934331AD1-057 C
50/50
5.7925.792
934321AD1-056 C
50/50
10.38210.382
934322AD1-056 E
50/50
5.6325.632
927022AC1-189 E
50/50
4.9224.922
925595AC1-034 E
50/50
6.1616.161
916042Z1-036 E
Adder
15.8176470588235313.445
316023AB2-100 C2
50/50
2.92.9
960082AF2-299 E
50/50
3.0313.031
946281AF1-292 C
50/50
3.7633.763
926071AC1-086 C
50/50
46.67446.674
316317KELFORD C
50/50
0.4920.492
927021AC1-189 C
50/50
9.889.88
924152AB2-059 E OP
50/50
6.4956.495
3156083AA2-088SOLA
50/50
1.0541.054
316141AB2-099 E
50/50
0.330.33
316088AB2-174 E
50/50
14.27714.277
313506AB1-173 C OP
50/50
2.3482.348
923994AB2-040_E
50/50
12.80412.804
3151361ROSEMG1
50/50
4.3384.338
316005AA1-067 C
50/50
0.3090.309
961672AG1-007 E
50/50
0.6430.643
3145413WATKINS
Adder
0.46352941176470590.394
960081AF2-299 C
50/50
4.5464.546
926072AC1-086 E
50/50
21.24321.243
957862AF2-080 E
50/50
3.9783.978
315614AA2-178 C
50/50
1.2131.213
933981AD1-022 C
50/50
9.1829.182
900672V4-068 E
50/50
0.4080.408
3151261ROARAP2
50/50
2.3112.311
3147043LAWRENC
50/50
0.5750.575
316087AB2-174 C
50/50
2.5792.579
962572AG1-106 E
50/50
2.6412.641
926214AC1-099 E
50/50
1.6921.692
932632AC2-084 E
50/50
4.5274.527
920042AA2-088 E OP
50/50
10.51910.519
934521AD1-076 C
50/50
11.51711.517
934511AD1-075 C
50/50
7.9287.928
3145723EMPORIA
50/50
1.0091.009
316011AB1-132 C OP
50/50
5.1795.179
923573AB1-173 E OP
50/50
6.8296.829
919692AA2-053 E OP
50/50
6.826.82
925785AC1-054 E
50/50
3.6613.661
316263AC1-034 C
50/50
8.1678.167
940491AE2-034 C
50/50
0.8920.892
934501AD1-074 C
50/50
31.71231.712
924517AB2-100 E2
50/50
8.748.74
3156021HOLLOMANSOL
50/50
2.4892.489
3156073AA1-063SOLA
50/50
1.9971.997
3151371ROSEMS1
50/50
2.6872.687
961671AG1-007 C
50/50
1.1341.134
316359AB2-059 C OP
50/50
2.062.06
920692AA2-178 E
50/50
3.1813.181
966622AG1-532 E
50/50
2.2732.273
922923AB1-081 E OP
50/50
4.5854.585
3145946PLYMOUTH TP
50/50
0.2950.295
933982AD1-022 E
50/50
4.9994.999
927146AC1-208 E
50/50
5.7685.768
316049AB1-081 C OP
50/50
1.7481.748
3152921DOMTR78
50/50
1.3421.342
316140AB2-099 C
50/50
0.1260.126
3137643SOCKMAN
50/50
1.3241.324
316212AC1-099 C
50/50
0.4430.443
919710AA2-057 E
50/50
5.3045.304
316319Z2-044 C
50/50
0.2710.271
946282AF1-292 E
50/50
2.5092.509
316129AC1-054 C
50/50
1.2981.298
957861AF2-080 C
50/50
8.9748.974
917512Z2-088 E OP1
50/50
5.8425.842
940492AE2-034 E
50/50
2.3862.386
934522AD1-076 E
50/50
5.875.87
943172AE2-346 E
50/50
0.7920.792
918492AA1-063AE OP
50/50
5.7985.798
962571AG1-106 C
50/50
6.0376.037
917332KELFORD E
50/50
2.262.26
925122AB2-169 E
50/50
5.9415.941
932631AC2-084 C
50/50
1.4091.409
316274AC1-208 C
50/50
12.9912.99
917342Z2-044 E
50/50
0.7670.767
3151311EDGECMA
50/50
19.40219.402
934512AD1-075 E
50/50
4.0364.036
934502AD1-074 E
50/50
16.14316.143
924516AB2-100 E1
50/50
8.748.74
918512AA1-065 E OP
50/50
7.487.48
966621AG1-532 C
50/50
3.413.41
918532AA1-067 E
50/50
0.8120.812
316365AB2-100 C1
50/50
2.92.9
316318V4-068 C
50/50
0.0920.092
316210AC1-098 C
50/50
1.3231.323
926206AC1-098 E
50/50
5.1215.121
316327AA2-057 C
50/50
1.741.74
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5332.533
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.08239.082
CPLELTFEXP_CPLE->PJM
CLTF
5.3135.313
TVALTFEXP_TVA->PJM
CLTF
2.2652.265
O66PJM->LTFIMP_O-066
CMTX_NF
5.1955.195
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.32112.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4748.474
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5081.508
LAGNLTFEXP_LAGN->PJM
CLTF
2.9042.904
NYPJM->LTFIMP_NY
CLTF
0.3730.373
LGEELTFEXP_LGEE->PJM
CLTF
0.470.47
WECLTFEXP_WEC->PJM
CLTF
0.2520.252
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8170.817
SIGELTFEXP_SIGE->PJM
CLTF
0.0920.092

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 24642_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.8 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:894.71
MW Contribution:7.54
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
923263AB1-132 E OP
50/50
13.44913.449
3151411GASTONB
50/50
6.7166.716
316181AB2-040 GEN
50/50
2.6272.627
316174AB2-169_C
50/50
1.0031.003
3156063AA2-053SOLA
50/50
2.4022.402
3151281ROARAP4
50/50
2.1662.166
3156011CONETOE2SOL
50/50
1.451.45
934501AD1-074 C
50/50
28.2428.24
924517AB2-100 E2
50/50
8.7018.701
3156021HOLLOMANSOL
50/50
2.3922.392
3156073AA1-063SOLA
50/50
1.9871.987
3151371ROSEMS1
50/50
2.6592.659
961671AG1-007 C
50/50
1.1041.104
316359AB2-059 C OP
50/50
2.0212.021
961942AG1-037 E
50/50
0.4290.429
943171AE2-346 C
50/50
0.2860.286
961941AG1-037 C
50/50
0.6430.643
3151391GASTONA
50/50
6.7166.716
3151381ROSEMG2
50/50
2.012.01
934332AD1-057 E
50/50
2.9742.974
934331AD1-057 C
50/50
5.7115.711
934321AD1-056 C
50/50
10.23710.237
934322AD1-056 E
50/50
5.5535.553
927022AC1-189 E
50/50
4.7634.763
925595AC1-034 E
50/50
6.0436.043
316023AB2-100 C2
50/50
2.8872.887
960082AF2-299 E
50/50
3.0163.016
946281AF1-292 C
50/50
3.7453.745
926071AC1-086 C
50/50
46.21146.211
316317KELFORD C
50/50
0.4790.479
927021AC1-189 C
50/50
9.5629.562
924152AB2-059 E OP
50/50
6.3716.371
3156083AA2-088SOLA
50/50
1.0641.064
316141AB2-099 E
50/50
0.3220.322
316088AB2-174 E
50/50
14.1914.19
313506AB1-173 C OP
50/50
2.3322.332
923994AB2-040_E
50/50
12.71812.718
3151361ROSEMG1
50/50
4.2934.293
316005AA1-067 C
50/50
0.2970.297
961672AG1-007 E
50/50
0.6260.626
940492AE2-034 E
Adder
1.99411764705882361.695
934522AD1-076 E
50/50
5.2285.228
943172AE2-346 E
50/50
0.7720.772
918492AA1-063AE OP
50/50
5.7695.769
962571AG1-106 C
50/50
5.9775.977
3145393UNCAMP
Adder
3.4082352941176472.897
933981AD1-022 C
50/50
8.3948.394
900672V4-068 E
50/50
0.4050.405
3151261ROARAP2
50/50
2.2892.289
3147043LAWRENC
50/50
0.5720.572
316087AB2-174 C
50/50
2.5632.563
962572AG1-106 E
50/50
2.6152.615
926214AC1-099 E
50/50
1.6591.659
932632AC2-084 E
50/50
4.4394.439
3145413WATKINS
Adder
0.48352941176470590.411
960081AF2-299 C
50/50
4.5244.524
926072AC1-086 E
50/50
21.03221.032
957862AF2-080 E
50/50
3.853.85
920042AA2-088 E OP
50/50
10.62410.624
934521AD1-076 C
50/50
10.25610.256
934511AD1-075 C
50/50
7.067.06
3145723EMPORIA
50/50
1.0031.003
316011AB1-132 C OP
50/50
5.1285.128
923573AB1-173 E OP
50/50
6.7836.783
919692AA2-053 E OP
50/50
6.7336.733
925785AC1-054 E
50/50
3.6243.624
316263AC1-034 C
50/50
8.0118.011
920692AA2-178 E
Adder
2.65882352941176462.26
966622AG1-532 E
50/50
2.2622.262
922923AB1-081 E OP
50/50
4.4974.497
3145946PLYMOUTH TP
50/50
0.2610.261
933982AD1-022 E
50/50
4.574.57
927146AC1-208 E
50/50
5.6755.675
316049AB1-081 C OP
50/50
1.7151.715
3152921DOMTR78
50/50
1.2181.218
316140AB2-099 C
50/50
0.1230.123
3137643SOCKMAN
50/50
1.3131.313
316212AC1-099 C
50/50
0.4340.434
919710AA2-057 E
50/50
5.215.21
316319Z2-044 C
50/50
0.2660.266
946282AF1-292 E
50/50
2.4962.496
316129AC1-054 C
50/50
1.2851.285
957861AF2-080 C
50/50
8.6848.684
917512Z2-088 E OP1
50/50
5.6735.673
917332KELFORD E
50/50
2.22.2
925122AB2-169 E
50/50
5.5085.508
932631AC2-084 C
50/50
1.3821.382
316274AC1-208 C
50/50
12.78112.781
917342Z2-044 E
50/50
0.7530.753
3151311EDGECMA
50/50
19.02419.024
934512AD1-075 E
50/50
3.5943.594
934502AD1-074 E
50/50
14.37614.376
924516AB2-100 E1
50/50
8.7018.701
918512AA1-065 E OP
50/50
7.1897.189
966621AG1-532 C
50/50
3.3933.393
918532AA1-067 E
50/50
0.780.78
316365AB2-100 C1
50/50
2.8872.887
316318V4-068 C
50/50
0.0910.091
316210AC1-098 C
50/50
1.2971.297
926206AC1-098 E
50/50
5.0225.022
316327AA2-057 C
50/50
1.7091.709
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4672.467
CBM South 2LTFEXP_CBM-S2->PJM
CBM
38.0738.07
CPLELTFEXP_CPLE->PJM
CLTF
5.1745.174
TVALTFEXP_TVA->PJM
CLTF
2.2062.206
O66PJM->LTFIMP_O-066
CMTX_NF
5.085.08
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.98911.989
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.2518.251
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4681.468
LAGNLTFEXP_LAGN->PJM
CLTF
2.8282.828
NYPJM->LTFIMP_NY
CLTF
0.3650.365
LGEELTFEXP_LGEE->PJM
CLTF
0.4580.458
WECLTFEXP_WEC->PJM
CLTF
0.2450.245
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7990.799
SIGELTFEXP_SIGE->PJM
CLTF
0.090.09

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 24662_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 24662_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.79 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:894.66
MW Contribution:7.53
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 24662_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.89 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:945.25
MW Contribution:7.61
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316023AB2-100 C2
50/50
2.8852.885
960082AF2-299 E
50/50
3.0133.013
946281AF1-292 C
50/50
3.7413.741
926071AC1-086 C
50/50
46.14246.142
316317KELFORD C
50/50
0.480.48
927021AC1-189 C
50/50
9.5289.528
924152AB2-059 E OP
50/50
6.3586.358
3156083AA2-088SOLA
50/50
1.0481.048
316141AB2-099 E
50/50
0.3220.322
316088AB2-174 E
50/50
14.17214.172
313506AB1-173 C OP
50/50
2.3292.329
923994AB2-040_E
50/50
12.712.7
3151361ROSEMG1
50/50
4.2874.287
316005AA1-067 C
50/50
0.2960.296
961672AG1-007 E
50/50
0.6240.624
3145413WATKINS
Adder
0.46823529411764710.398
960081AF2-299 C
50/50
4.5194.519
926072AC1-086 E
50/50
21.00121.001
957862AF2-080 E
50/50
3.8363.836
923263AB1-132 E OP
50/50
13.42813.428
3151411GASTONB
50/50
6.7066.706
316181AB2-040 GEN
50/50
2.6232.623
316174AB2-169_C
50/50
0.9970.997
3156063AA2-053SOLA
50/50
2.3982.398
3151281ROARAP4
50/50
2.1612.161
3156011CONETOE2SOL
50/50
1.4451.445
3145393UNCAMP
Adder
3.25058823529411762.763
933981AD1-022 C
50/50
8.3318.331
961942AG1-037 E
50/50
0.4290.429
943171AE2-346 C
50/50
0.2860.286
961941AG1-037 C
50/50
0.6430.643
3151391GASTONA
50/50
6.7066.706
3151381ROSEMG2
50/50
2.0072.007
934332AD1-057 E
50/50
2.9682.968
934331AD1-057 C
50/50
5.75.7
934321AD1-056 C
50/50
10.21910.219
934322AD1-056 E
50/50
5.5435.543
927022AC1-189 E
50/50
4.7464.746
925595AC1-034 E
50/50
6.0316.031
900672V4-068 E
50/50
0.4020.402
3151261ROARAP2
50/50
2.2842.284
3147043LAWRENC
50/50
0.5710.571
920042AA2-088 E OP
50/50
10.46410.464
934521AD1-076 C
50/50
10.16810.168
934511AD1-075 C
50/50
6.9996.999
3145723EMPORIA
50/50
1.0021.002
316011AB1-132 C OP
50/50
5.125.12
923573AB1-173 E OP
50/50
6.7736.773
919692AA2-053 E OP
50/50
6.7216.721
925785AC1-054 E
50/50
3.6173.617
316263AC1-034 C
50/50
7.9947.994
934501AD1-074 C
50/50
27.99627.996
924517AB2-100 E2
50/50
8.6958.695
3156021HOLLOMANSOL
50/50
2.382.38
3156073AA1-063SOLA
50/50
1.9761.976
3151371ROSEMS1
50/50
2.6552.655
961671AG1-007 C
50/50
1.1011.101
316359AB2-059 C OP
50/50
2.0172.017
920692AA2-178 E
Adder
2.62823529411764722.234
966622AG1-532 E
50/50
2.262.26
922923AB1-081 E OP
50/50
4.4884.488
3145946PLYMOUTH TP
50/50
0.2580.258
933982AD1-022 E
50/50
4.5364.536
927146AC1-208 E
50/50
5.6665.666
316049AB1-081 C OP
50/50
1.7111.711
316087AB2-174 C
50/50
2.5592.559
962572AG1-106 E
50/50
2.6112.611
926214AC1-099 E
50/50
1.6581.658
932632AC2-084 E
50/50
4.4354.435
3152921DOMTR78
50/50
1.2091.209
316140AB2-099 C
50/50
0.1230.123
3137643SOCKMAN
50/50
1.311.31
316212AC1-099 C
50/50
0.4340.434
919710AA2-057 E
50/50
5.2015.201
316319Z2-044 C
50/50
0.2650.265
946282AF1-292 E
50/50
2.4942.494
316129AC1-054 C
50/50
1.2831.283
957861AF2-080 C
50/50
8.6538.653
917512Z2-088 E OP1
50/50
5.6555.655
940492AE2-034 E
Adder
1.97058823529411781.675
934522AD1-076 E
50/50
5.1825.182
943172AE2-346 E
50/50
0.7720.772
918492AA1-063AE OP
50/50
5.7385.738
962571AG1-106 C
50/50
5.9685.968
917332KELFORD E
50/50
2.2022.202
925122AB2-169 E
50/50
5.4735.473
932631AC2-084 C
50/50
1.381.38
316274AC1-208 C
50/50
12.76112.761
917342Z2-044 E
50/50
0.7520.752
3151311EDGECMA
50/50
18.98218.982
934512AD1-075 E
50/50
3.5633.563
934502AD1-074 E
50/50
14.25214.252
924516AB2-100 E1
50/50
8.6958.695
918512AA1-065 E OP
50/50
7.1527.152
966621AG1-532 C
50/50
3.393.39
918532AA1-067 E
50/50
0.7770.777
316365AB2-100 C1
50/50
2.8852.885
316318V4-068 C
50/50
0.090.09
316210AC1-098 C
50/50
1.2961.296
926206AC1-098 E
50/50
5.0185.018
316327AA2-057 C
50/50
1.7071.707
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4612.461
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3838
CPLELTFEXP_CPLE->PJM
CLTF
5.1645.164
TVALTFEXP_TVA->PJM
CLTF
2.2032.203
O66PJM->LTFIMP_O-066
CMTX_NF
5.0655.065
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.98111.981
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.2418.241
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4661.466
LAGNLTFEXP_LAGN->PJM
CLTF
2.8242.824
NYPJM->LTFIMP_NY
CLTF
0.3630.363
LGEELTFEXP_LGEE->PJM
CLTF
0.4570.457
WECLTFEXP_WEC->PJM
CLTF
0.2450.245
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7960.796
SIGELTFEXP_SIGE->PJM
CLTF
0.090.09

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.22 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:680.18
MW Contribution:4.4
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.36 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:701.52
MW Contribution:4.41
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316049AB1-081 C OP
80/20
1.4941.494
3151611KERR 4
80/20
0.8620.862
316087AB2-174 C
80/20
2.4642.464
313527AB2-043 C
80/20
0.3630.363
3151591KERR 2
80/20
0.8620.862
316129AC1-054 C
80/20
1.341.34
957861AF2-080 C
80/20
6.8566.856
316131AB2-060 C
80/20
1.0341.034
3138533PONTONDP
80/20
0.3360.336
316118AC1-105 C
80/20
0.4840.484
316023AB2-100 C2
80/20
2.7732.773
946281AF1-292 C
80/20
3.6413.641
926071AC1-086 C
80/20
42.49342.493
316317KELFORD C
80/20
0.370.37
927021AC1-189 C
80/20
7.5497.549
3151531CLOVER1
80/20
5.8195.819
964241AG1-285 C
80/20
7.2257.225
316034AC1-036 C
80/20
0.1240.124
962561AG1-105 C
80/20
5.2875.287
3151151S HAMPT1
80/20
0.9570.957
962571AG1-106 C
80/20
5.4965.496
932631AC2-084 C
80/20
1.171.17
316274AC1-208 C
80/20
11.22611.226
3151311EDGECMA
80/20
16.55516.555
3151601KERR 3
80/20
0.8620.862
3151581KERR 1
80/20
0.3080.308
933981AD1-022 C
80/20
5.6875.687
3151261ROARAP2
80/20
2.1232.123
3147043LAWRENC
80/20
0.5790.579
3151621KERR 5
80/20
0.8620.862
3152921DOMTR78
80/20
0.8540.854
316140AB2-099 C
80/20
0.0920.092
3137643SOCKMAN
80/20
1.2371.237
316212AC1-099 C
80/20
0.3680.368
316319Z2-044 C
80/20
0.2310.231
3151641KERR 7
80/20
0.8620.862
934501AD1-074 C
80/20
19.36119.361
3156021HOLLOMANSOL
80/20
1.5861.586
3156073AA1-063SOLA
80/20
1.8141.814
3151371ROSEMS1
80/20
2.4382.438
961671AG1-007 C
80/20
0.9120.912
934621AD1-088 C
80/20
4.4044.404
316359AB2-059 C OP
80/20
1.7611.761
946301AF1-294 C
80/20
1.8661.866
934521AD1-076 C
80/20
7.0327.032
934511AD1-075 C
80/20
4.844.84
316011AB1-132 C OP
80/20
4.7154.715
316263AC1-034 C
80/20
6.9816.981
959311AF2-222 C
80/20
8.6368.636
943171AE2-346 C
80/20
0.2140.214
961941AG1-037 C
80/20
0.4820.482
3151391GASTONA
80/20
6.1766.176
3151381ROSEMG2
80/20
1.8431.843
934331AD1-057 C
80/20
5.1335.133
934321AD1-056 C
80/20
9.2019.201
958211AF2-115 C
80/20
1.1351.135
960081AF2-299 C
80/20
4.3984.398
3151631KERR 6
80/20
0.8620.862
936261AD2-033 C
80/20
8.0298.029
961791AG1-021 C
80/20
0.9080.908
3144293JTRSVLE
80/20
0.2090.209
3152661PLYWOOD A
80/20
0.6390.639
966621AG1-532 C
80/20
3.2993.299
3156083AA2-088SOLA
80/20
0.9350.935
313506AB1-173 C OP
80/20
2.2292.229
3151361ROSEMG1
80/20
3.9363.936
316005AA1-067 C
80/20
0.2210.221
957481AF2-042 C
80/20
24.31224.312
316365AB2-100 C1
80/20
2.7732.773
316318V4-068 C
80/20
0.0750.075
316210AC1-098 C
80/20
1.0991.099
316327AA2-057 C
80/20
1.4891.489
316239AB2-077 C O1
80/20
0.2290.229
964791AG1-342 C
80/20
2.0352.035
3151411GASTONB
80/20
6.1766.176
316181AB2-040 GEN
80/20
2.5112.511
316174AB2-169_C
80/20
0.7190.719
3156063AA2-053SOLA
80/20
2.1582.158
3151281ROARAP4
80/20
2.0092.009
3156011CONETOE2SOL
80/20
1.1751.175
316238AB2-078 C O1
80/20
0.2290.229
316237AB2-079 C O1
80/20
0.2290.229
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1882.188
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.15434.154
CPLELTFEXP_CPLE->PJM
CLTF
4.5894.589
TVALTFEXP_TVA->PJM
CLTF
2.0182.018
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.20711.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.5767.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.3611.361
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
NYPJM->LTFIMP_NY
CLTF
0.3660.366
LGEELTFEXP_LGEE->PJM
CLTF
0.4310.431
WECLTFEXP_WEC->PJM
CLTF
0.2290.229
SIGELTFEXP_SIGE->PJM
CLTF
0.0840.084

Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.32 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:676.24
MW Contribution:1.11
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.4 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:716.68
MW Contribution:1.12
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
315614AA2-178 C
80/20
3.1813.181
933981AD1-022 C
80/20
18.40618.406
3151261ROARAP2
80/20
1.211.21
940491AE2-034 C
80/20
2.3412.341
934501AD1-074 C
80/20
69.11769.117
3156021HOLLOMANSOL
80/20
4.1274.127
3156073AA1-063SOLA
80/20
1.1081.108
3151371ROSEMS1
80/20
1.2321.232
961671AG1-007 C
80/20
1.1121.112
316359AB2-059 C OP
80/20
1.571.57
316049AB1-081 C OP
80/20
1.3321.332
316087AB2-174 C
80/20
0.8050.805
3156116Z1-036WIND
80/20
1.3161.316
943171AE2-346 C
80/20
0.3740.374
961941AG1-037 C
80/20
0.8430.843
3151391GASTONA
80/20
2.992.99
3151381ROSEMG2
80/20
0.9310.931
934331AD1-057 C
80/20
3.3453.345
934321AD1-056 C
80/20
5.9965.996
316129AC1-054 C
80/20
0.6740.674
957861AF2-080 C
80/20
10.44310.443
316023AB2-100 C2
80/20
0.5940.594
946281AF1-292 C
80/20
0.9210.921
926071AC1-086 C
80/20
20.57620.576
316317KELFORD C
80/20
0.5890.589
927021AC1-189 C
80/20
11.49811.498
3151151S HAMPT1
80/20
0.4350.435
962571AG1-106 C
80/20
2.6612.661
932631AC2-084 C
80/20
1.2271.227
316274AC1-208 C
80/20
9.5699.569
3151311EDGECMA
80/20
14.76714.767
3147043LAWRENC
80/20
0.1460.146
3152921DOMTR78
80/20
2.6612.661
316140AB2-099 C
80/20
0.1610.161
3137643SOCKMAN
80/20
0.5730.573
316212AC1-099 C
80/20
0.3860.386
316319Z2-044 C
80/20
0.2070.207
934521AD1-076 C
80/20
25.10225.102
934511AD1-075 C
80/20
17.27917.279
316011AB1-132 C OP
80/20
2.2832.283
316263AC1-034 C
80/20
6.2256.225
960081AF2-299 C
80/20
1.1131.113
966621AG1-532 C
80/20
0.8350.835
3156083AA2-088SOLA
80/20
0.6410.641
313506AB1-173 C OP
80/20
0.8160.816
3151361ROSEMG1
80/20
1.9891.989
316005AA1-067 C
80/20
0.4290.429
316365AB2-100 C1
80/20
0.5940.594
316318V4-068 C
80/20
0.0840.084
316210AC1-098 C
80/20
1.1521.152
316327AA2-057 C
80/20
1.3351.335
3151411GASTONB
80/20
2.992.99
316181AB2-040 GEN
80/20
0.9190.919
316174AB2-169_C
80/20
1.9111.911
3156063AA2-053SOLA
80/20
1.5851.585
3151281ROARAP4
80/20
1.1451.145
3156011CONETOE2SOL
80/20
1.5831.583
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4372.437
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.337.3
CPLELTFEXP_CPLE->PJM
CLTF
5.1125.112
TVALTFEXP_TVA->PJM
CLTF
2.2172.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.90912.909
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4168.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5351.535
LAGNLTFEXP_LAGN->PJM
CLTF
2.8432.843
NYPJM->LTFIMP_NY
CLTF
0.2690.269
LGEELTFEXP_LGEE->PJM
CLTF
0.4860.486
WECLTFEXP_WEC->PJM
CLTF
0.2620.262
SIGELTFEXP_SIGE->PJM
CLTF
0.0950.095

Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2131_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.14 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:663.74
MW Contribution:1.11
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2131_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.21 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:709.9
MW Contribution:1.12
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940491AE2-034 C
80/20
2.3422.342
934501AD1-074 C
80/20
69.12869.128
3156021HOLLOMANSOL
80/20
4.1284.128
3156073AA1-063SOLA
80/20
1.1081.108
3151371ROSEMS1
80/20
1.2321.232
961671AG1-007 C
80/20
1.1131.113
316359AB2-059 C OP
80/20
1.5711.571
316049AB1-081 C OP
80/20
1.3331.333
316087AB2-174 C
80/20
0.8060.806
943171AE2-346 C
80/20
0.3750.375
961941AG1-037 C
80/20
0.8430.843
3151391GASTONA
80/20
2.9912.991
3151381ROSEMG2
80/20
0.9320.932
934331AD1-057 C
80/20
3.3463.346
934321AD1-056 C
80/20
5.9985.998
316129AC1-054 C
80/20
0.6750.675
957861AF2-080 C
80/20
10.44510.445
316023AB2-100 C2
80/20
0.5940.594
946281AF1-292 C
80/20
0.9220.922
926071AC1-086 C
80/20
20.58320.583
316317KELFORD C
80/20
0.5890.589
927021AC1-189 C
80/20
11.50111.501
3151151S HAMPT1
80/20
0.4350.435
962571AG1-106 C
80/20
2.6622.662
932631AC2-084 C
80/20
1.2281.228
316274AC1-208 C
80/20
9.5729.572
3151311EDGECMA
80/20
14.77214.772
938531AE1-072 C
Adder
-6.952941176470588-5.91
315614AA2-178 C
80/20
3.1823.182
933981AD1-022 C
80/20
18.40918.409
3151261ROARAP2
80/20
1.211.21
3147043LAWRENC
80/20
0.1460.146
3152921DOMTR78
80/20
2.6612.661
316140AB2-099 C
80/20
0.1610.161
3137643SOCKMAN
80/20
0.5730.573
316212AC1-099 C
80/20
0.3860.386
316319Z2-044 C
80/20
0.2070.207
934521AD1-076 C
80/20
25.10625.106
934511AD1-075 C
80/20
17.28217.282
316011AB1-132 C OP
80/20
2.2842.284
316263AC1-034 C
80/20
6.2276.227
960081AF2-299 C
80/20
1.1141.114
966621AG1-532 C
80/20
0.8350.835
3156083AA2-088SOLA
80/20
0.6420.642
313506AB1-173 C OP
80/20
0.8170.817
3151361ROSEMG1
80/20
1.9891.989
316005AA1-067 C
80/20
0.4290.429
316365AB2-100 C1
80/20
0.5940.594
316318V4-068 C
80/20
0.0840.084
316210AC1-098 C
80/20
1.1531.153
316327AA2-057 C
80/20
1.3361.336
3151411GASTONB
80/20
2.9912.991
316181AB2-040 GEN
80/20
0.920.92
316174AB2-169_C
80/20
1.9121.912
3156063AA2-053SOLA
80/20
1.5851.585
3151281ROARAP4
80/20
1.1451.145
3156011CONETOE2SOL
80/20
1.5831.583
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.442.44
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.35737.357
CPLELTFEXP_CPLE->PJM
CLTF
5.1185.118
TVALTFEXP_TVA->PJM
CLTF
2.2252.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.00413.004
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4538.453
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5441.544
LAGNLTFEXP_LAGN->PJM
CLTF
2.8532.853
NYPJM->LTFIMP_NY
CLTF
0.2650.265
LGEELTFEXP_LGEE->PJM
CLTF
0.4890.489
WECLTFEXP_WEC->PJM
CLTF
0.2640.264
SIGELTFEXP_SIGE->PJM
CLTF
0.0950.095

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: H2T557_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.14 %
Rating:1065.0 MVA
Rating Type:C
MVA to Mitigate:1407.28
MW Contribution:2.09
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: H2T557_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.17 %
Rating:1065.0 MVA
Rating Type:C
MVA to Mitigate:1780.31
MW Contribution:2.44
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940431AE2-027 C
Adder
13.56705882352941311.532
316312AB1-027 C
50/50
0.7090.709
944631AF1-128 C
Adder
44.20941176470588437.578
938552AE1-074 E
Adder
1.21058823529411751.029
316160AE1-175 E
Adder
1.14588235294117660.974
3150921YORKTN3
Adder
107.5905882352941291.452
934782AD1-105 E
50/50
6.4256.425
3145256KINGFORK
Adder
0.83411764705882350.709
925522AC1-027 E
Adder
0.97294117647058820.827
933291AC2-141 C
Adder
23.7529411764705920.19
926755AC1-161 E
Adder
10.1388235294117658.618
941102AE2-104 E
Adder
4.2741176470588243.633
957872AF2-081 E
Adder
3.3717647058823532.866
936592AD2-074 E
Adder
8.7800000000000017.463
962572AG1-106 E
Adder
0.80235294117647070.682
315051AA1-145 CT1
50/50
6.5696.569
927041AC1-191 C
50/50
14.27914.279
3142366NRTHEST
50/50
0.2420.242
3138116ELKO L286
Adder
1.61294117647058831.371
961611AG1-000B C
Adder
14.80117647058823512.581
940541AE2-040 C
Adder
2.13058823529411741.811
940481AE2-033 C
Adder
11.9247058823529410.136
940482AE2-033 E
Adder
8.0388235294117656.833
3150481FOUR RIVERF
50/50
4.9634.963
927042AC1-191 E
50/50
7.1137.113
3150691DARBY 3
50/50
3.2743.274
935162AD1-151 E
Adder
10.7000000000000019.095
316233AE1-074 C
Adder
2.40235294117647062.042
940551AE2-041 C
Adder
7.1435294117647066.072
957832AF2-077 E
Adder
1.33764705882352941.137
943461AF1-017 C
Adder
1.13294117647058810.963
932596AC2-079 E
Adder
7.8070588235294126.636
316311AC2-079 C
Adder
4.7847058823529424.067
938532AE1-072 E
Adder
7.2011764705882366.121
3146326AYDLETT TAP
Adder
1.06588235294117650.906
917122Z2-027 E
Adder
1.04588235294117650.889
920692AA2-178 E
Adder
3.0352941176470592.58
966622AG1-532 E
Adder
0.62705882352941180.533
3150701DARBY 4
50/50
3.2783.278
3150731STONECA
Adder
7.29647058823529456.202
935161AD1-151 C
Adder
16.05058823529411813.643
932046AC2-012 E
Adder
10.5517647058823528.969
958161AF2-110 C
Adder
1.09647058823529430.932
938531AE1-072 C
Adder
13.81411764705882611.742
3145393UNCAMP
Adder
4.6082352941176473.917
933981AD1-022 C
Adder
6.2894117647058835.346
900672V4-068 E
Adder
0.25294117647058820.215
926785AC1-164_E
Adder
19.72000000000000216.762
943471AF1-018 C
Adder
7.1435294117647066.072
316084AB2-161 E
Adder
4.9517647058823524.209
3145946PLYMOUTH TP
Adder
0.234117647058823540.199
933982AD1-022 E
Adder
3.4235294117647062.91
940641AE2-051 C
Adder
10.9988235294117669.349
926472AC1-118 E
Adder
0.95294117647058830.81
3150441FOUR RIVERB
50/50
4.1244.124
3150651CHESTF6
Adder
20.39176470588235217.333
946262AF1-291 E
Adder
1.54705882352941181.315
3130536PAPERMILL
Adder
6.6941176470588245.69
939602AE1-190 E
Adder
1.41058823529411771.199
934576AD1-082 E
Adder
3.94470588235294173.353
933292AC2-141 E
Adder
10.1388235294117658.618
944602AF1-125 E
Adder
80.9447058823529368.803
3145506HICKORY
Adder
1.7235294117647061.465
943612AF1-032 E
Adder
0.73411764705882350.624
957871AF2-081 C
Adder
7.8682352941176476.688
936591AD2-074 C
Adder
5.3811764705882354.574
940492AE2-034 E
Adder
2.2764705882352941.935
934522AD1-076 E
Adder
4.5105882352941183.834
943172AE2-346 E
Adder
0.42235294117647060.359
966872AG1-558 E
50/50
1.7921.792
966871AG1-558 C
50/50
3.5563.556
316076AC2-137 E
Adder
1.54705882352941181.315
3150841SPRUNCB
Adder
10.1282352941176488.609
3150831SPRUNCA
Adder
10.1282352941176488.609
923842AB2-024 E
Adder
1.81529411764705871.543
316157AD2-030 E
Adder
1.1635294117647060.989
926662AC1-147 E
Adder
1.06705882352941180.907
916192Z1-068 E
Adder
1.50117647058823531.276
957492AF2-043 E
Adder
1.12941176470588230.96
923852AB2-025 E
Adder
0.86235294117647050.733
918492AA1-063AE OP
Adder
2.78000000000000022.363
962571AG1-106 C
Adder
1.83294117647058831.558
3150601CHESTF5
Adder
70.6552941176470660.057
925332AB2-190 E
Adder
8.1470588235294116.925
927226AC1-216 E
Adder
7.5517647058823536.419
962962AG1-145 E
Adder
1.38941176470588231.181
936666AD2-085 E
Adder
4.7117647058823534.005
941591AE2-156 C
Adder
14.40941176470588112.248
944591AF1-124 C
Adder
36.0430.634
944601AF1-125 C
Adder
35.35882352941176530.055
938771AE1-103 C
Adder
2.24235294117647041.906
3145413WATKINS
Adder
0.51529411764705880.438
964212AG1-282 E
Adder
1.30235294117647071.107
960081AF2-299 C
Adder
1.2552941176470591.067
3150461FOUR RIVERD
50/50
4.0644.064
939191AE1-149 C
Adder
10.0305882352941188.526
3143316POE
Adder
1.24941176470588241.062
934146AD1-041 E
Adder
3.52588235294117652.997
957601AF2-054 C
Adder
2.07411764705882361.763
901082W1-029 E
Adder
24.7470588235294121.035
958261AF2-120 C
Adder
6.0223529411764715.119
3150451FOUR RIVERC
50/50
5.0385.038
3150471FOUR RIVERE
50/50
4.0644.064
315052AA1-145 CT2
50/50
6.5666.566
3150671DARBY 1
50/50
3.2593.259
940432AE2-027 E
Adder
9.0447058823529417.688
934012AD1-025 E
Adder
9.777647058823538.311
939612AE1-191 E
Adder
5.6423529411764714.796
957602AF2-054 E
Adder
1.38235294117647081.175
913392Y1-086 E
Adder
1.71647058823529421.459
939411AE1-173 C
Adder
60.99529411764705651.846
958262AF2-120 E
Adder
4.0152941176470593.413
966661AG1-536 C
Adder
5.184.403
316078AC2-138 E
Adder
0.89294117647058820.759
944491AF1-114 C
Adder
4.88705882352941154.154
944641AF1-129 C
Adder
111.9952941176470695.196
316240AF1-291 C
Adder
2.32117647058823541.973
924814AB2-134 E
Adder
12.37058823529411810.515
942342AE2-247 E
Adder
1.7282352941176471.469
919152AA1-139 E1
Adder
3.21764705882352952.735
920042AA2-088 E OP
Adder
7.6305882352941186.486
934521AD1-076 C
Adder
8.8494117647058837.522
934511AD1-075 C
Adder
6.0917647058823535.178
939246AE1-155 E
Adder
8.3858823529411777.128
926412AC1-112 E
50/50
1.5121.512
3150681DARBY 2
50/50
3.2633.263
934781AD1-105 C
50/50
1.5491.549
942341AE2-247 C
Adder
1.25176470588235311.064
943462AF1-017 E
Adder
1.8482352941176471.571
958162AF2-110 E
Adder
1.74470588235294131.483
919153AA1-139 E2
Adder
3.21764705882352952.735
934512AD1-075 E
Adder
3.10117647058823562.636
934502AD1-074 E
Adder
12.40352941176470510.543
924516AB2-100 E1
Adder
2.0282352941176471.724
918512AA1-065 E OP
Adder
3.88823529411764753.305
940642AE2-051 E
Adder
7.3317647058823536.232
966621AG1-532 C
Adder
0.94117647058823540.8
963612AG1-210 E
Adder
0.95647058823529410.813
3150431FOUR RIVERA
50/50
4.1244.124
925865AC1-065 E
Adder
16.6414.144
961951AG1-038 C
Adder
3.1117647058823532.645
961952AG1-038 E
Adder
4.297647058823533.653
946282AF1-292 E
Adder
0.69294117647058820.589
936582AD2-073 E
Adder
0.99294117647058820.844
939262AE1-157 E
Adder
5.2788235294117654.487
930122AB1-027 E
50/50
1.8591.859
316169AC1-164 GEN
Adder
43.8917647058823537.308
316349AD2-085 C
Adder
2.8882352941176472.455
935112AD1-144 E
Adder
0.77529411764705890.659
944582AF1-123 E
Adder
82.2352941176470769.9
944592AF1-124 E
Adder
82.532941176470670.153
923832AB2-022 E
Adder
0.96823529411764710.823
938772AE1-103 E
Adder
3.09647058823529432.632
916042Z1-036 E
Adder
21.6647058823529418.415
960082AF2-299 E
Adder
0.83647058823529410.711
946281AF1-292 C
Adder
1.03882352941176470.883
926071AC1-086 C
Adder
14.17176470588235312.046
957971AF2-091 C
Adder
1.66117647058823531.412
939261AE1-157 C
Adder
9.7317647058823548.272
966882AG1-559 E
Adder
1.02588235294117650.872
3142296MT RD221
50/50
0.1860.186
316004AC1-112 C
50/50
0.4420.442
942001AE2-212 C
Adder
2.1905882352941181.862
3150501FOURRIVERG
50/50
6.2846.284
939192AE1-149 E
Adder
6.6870588235294125.684
939312AE1-162 E
Adder
1.24705882352941181.06
934065AD1-033 E
Adder
3.9752941176470593.379
937226AE2-253 E
Adder
4.6070588235294123.916
923263AB1-132 E OP
Adder
4.1247058823529413.506
963611AG1-210 C
Adder
0.63764705882352950.542
943741AF1-042 C
Adder
2.81529411764705852.393
934501AD1-074 C
Adder
24.36705882352941220.712
962861AG1-135 C
Adder
5.8517647058823544.974
924517AB2-100 E2
Adder
2.0282352941176471.724
3141813NORNECK
Adder
0.84941176470588230.722
939412AE1-173 E
Adder
40.66352941176470634.564
964211AG1-282 C
Adder
1.95411764705882351.661
961942AG1-037 E
Adder
0.235294117647058850.2
961941AG1-037 C
Adder
0.352941176470588260.3
941032AE2-094 E
Adder
10.4941176470588248.92
941031AE2-094 C
Adder
23.43176470588235519.917
942002AE2-212 E
Adder
1.46000000000000021.241
934392AD1-063 E
Adder
1.0717647058823530.911
944581AF1-123 C
Adder
35.91176470588235530.525
941101AE2-104 C
Adder
2.68823529411764732.285
943742AF1-042 E
Adder
4.5941176470588233.905
962862AG1-135 E
Adder
3.9011764705882353.316
966662AG1-536 E
Adder
6.9611764705882355.917
316141AB2-099 E
Adder
0.176470588235294130.15
316088AB2-174 E
Adder
4.3517647058823533.699
923994AB2-040_E
Adder
4.0952941176470593.481
944492AF1-114 E
Adder
6.7482352941176475.736
926072AC1-086 E
Adder
6.4505882352941175.483
944011AF1-069 C
Adder
4.4164705882352953.754
966881AG1-559 C
Adder
2.03647058823529431.731
3145723EMPORIA
Adder
0.289411764705882370.246
923573AB1-173 E OP
Adder
2.1847058823529411.857
957972AF2-091 E
Adder
2.29411764705882341.95
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.6452.645
CBM South 2LTFEXP_CBM-S2->PJM
CBM
41.47141.471
CPLELTFEXP_CPLE->PJM
CLTF
5.5585.558
TVALTFEXP_TVA->PJM
CLTF
1.5691.569
O66PJM->LTFIMP_O-066
CMTX_NF
10.11910.119
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.3964.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0520.052
MECLTFEXP_MEC->PJM
CLTF
0.2980.298
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.1280.128
LAGNLTFEXP_LAGN->PJM
CLTF
2.0762.076
NYPJM->LTFIMP_NY
CLTF
0.8060.806
G-007PJM->LTFIMP_G-007
CMTX_NF
1.5811.581
SIGELTFEXP_SIGE->PJM
CLTF
0.0090.009

Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.22 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:801.79
MW Contribution:1.57
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.59 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:831.68
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
937482AD2-202 E
Adder
1.86823529411764721.588
961792AG1-021 E
50/50
3.9843.984
941011AE2-092 C
Adder
-9.724705882352941-8.266
960081AF2-299 C
Adder
0.94000000000000010.799
936261AD2-033 C
50/50
27.67327.673
961791AG1-021 C
50/50
4.6774.677
3144293JTRSVLE
50/50
1.0761.076
962562AG1-105 E
Adder
9.4564705882352958.038
3145723EMPORIA
Adder
0.21647058823529410.184
925785AC1-054 E
Adder
3.35647058823529452.853
959311AF2-222 C
50/50
38.91438.914
942751AE2-291 C
Adder
8.1517647058823536.929
942462AE2-259 E
50/50
20.76320.763
964791AG1-342 C
Adder
5.5447058823529414.713
925997AC1-075 E
Adder
3.3141176470588242.817
966621AG1-532 C
Adder
0.70470588235294120.599
924022AB2-043 E O1
Adder
9.1247058823529417.756
960082AF2-299 E
Adder
0.62705882352941180.533
946281AF1-292 C
Adder
0.77764705882352950.661
3151531CLOVER1
50/50
22.50522.505
964241AG1-285 C
50/50
25.15925.159
316034AC1-036 C
50/50
0.5350.535
958212AF2-115 E
50/50
4.9814.981
962561AG1-105 C
Adder
14.18352941176470612.056
936262AD2-033 E
50/50
18.44918.449
958211AF2-115 C
50/50
5.8475.847
957482AF2-042 E
50/50
65.41765.417
934621AD1-088 C
50/50
18.90718.907
946301AF1-294 C
50/50
9.6159.615
942461AE2-259 C
50/50
31.14431.144
935172AD1-152 E
Adder
8.8823529411764717.55
925612AC1-036 E
50/50
1.961.96
924312AB2-078 E O1
Adder
2.3164705882352941.969
926274AC1-105 E
Adder
4.0141176470588233.412
938821AE1-108 C
Adder
-10.602352941176472-9.012
964242AG1-285 E
50/50
16.77316.773
924162AB2-060 E OP
Adder
7.6694117647058836.519
964792AG1-342 E
Adder
3.6964705882352943.142
932763AC2-100 E
Adder
2.7305882352941182.321
3147223TWITTYS
50/50
2.1732.173
959312AF2-222 E
50/50
26.07226.072
926024AC1-080 E
Adder
1.10.935
957481AF2-042 C
50/50
98.12598.125
924322AB2-079 E O1
Adder
2.3164705882352941.969
946302AF1-294 E
50/50
8.1428.142
943902AF1-058 E
Adder
1.841.564
924302AB2-077 E O1
Adder
2.3164705882352941.969
942752AE2-291 E
Adder
5.4352941176470594.62
966622AG1-532 E
Adder
0.47058823529411770.4
3147133PAMPLIN
50/50
2.7572.757
927264AC1-222 E
Adder
5.5211764705882354.693
316336AC2-165 C
Adder
-5.9023529411764715-5.017
934622AD1-088 E
50/50
9.1039.103
934612AD1-087 E
Adder
6.3847058823529415.427
927255AC1-221 E
Adder
4.1470588235294123.525
946282AF1-292 E
Adder
0.51882352941176470.441
3138533PONTONDP
50/50
1.7321.732
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1672.167
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.10836.108
CPLELTFEXP_CPLE->PJM
CLTF
4.5484.548
TVALTFEXP_TVA->PJM
CLTF
2.0222.022
O66PJM->LTFIMP_O-066
CMTX_NF
5.0935.093
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.4439.443
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.3277.327
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.2351.235
LAGNLTFEXP_LAGN->PJM
CLTF
2.5882.588
NYPJM->LTFIMP_NY
CLTF
0.3810.381
LGEELTFEXP_LGEE->PJM
CLTF
0.370.37
WECLTFEXP_WEC->PJM
CLTF
0.1960.196
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7990.799
SIGELTFEXP_SIGE->PJM
CLTF
0.0750.075

Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.05 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:637.86
MW Contribution:0.94
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.13 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:677.49
MW Contribution:0.91
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3156073AA1-063SOLA
80/20
0.5850.585
3151371ROSEMS1
80/20
0.3850.385
934621AD1-088 C
80/20
18.88918.889
316359AB2-059 C OP
80/20
0.5630.563
946301AF1-294 C
80/20
9.619.61
942461AE2-259 C
80/20
31.13731.137
316197AC1-042 C
80/20
0.1420.142
316336AC2-165 C
Adder
-5.881176470588235-4.999
934611AD1-087 C
80/20
2.212.21
316049AB1-081 C OP
80/20
0.4780.478
3151611KERR 4
80/20
1.5621.562
316087AB2-174 C
80/20
0.5890.589
313527AB2-043 C
80/20
0.9080.908
3151591KERR 2
80/20
1.5621.562
316283AC2-100 C
80/20
1.2351.235
3151391GASTONA
80/20
0.9240.924
3151381ROSEMG2
80/20
0.2910.291
934331AD1-057 C
80/20
1.1051.105
934321AD1-056 C
80/20
1.981.98
958211AF2-115 C
80/20
5.8445.844
316129AC1-054 C
80/20
1.1891.189
316131AB2-060 C
80/20
2.6612.661
3138533PONTONDP
80/20
1.7321.732
316118AC1-105 C
80/20
1.3691.369
316217AC1-145 C
80/20
0.1690.169
946281AF1-292 C
80/20
0.7790.779
926071AC1-086 C
80/20
6.3586.358
3151531CLOVER1
80/20
22.47722.477
964241AG1-285 C
80/20
25.13725.137
316034AC1-036 C
80/20
0.5340.534
962561AG1-105 C
80/20
14.16414.164
942671AE2-283 C
80/20
1.5231.523
962571AG1-106 C
80/20
0.8220.822
932631AC2-084 C
80/20
0.3610.361
316274AC1-208 C
80/20
3.5443.544
3151311EDGECMA
80/20
5.0435.043
3151601KERR 3
80/20
1.5621.562
3151581KERR 1
80/20
0.5580.558
3152661PLYWOOD A
80/20
1.751.75
941011AE2-092 C
Adder
-9.709411764705882-8.253
3151261ROARAP2
80/20
0.6820.682
3147043LAWRENC
80/20
0.2660.266
3151621KERR 5
80/20
1.5621.562
316222AC1-221 C
80/20
1.581.58
3137643SOCKMAN
80/20
0.3530.353
316212AC1-099 C
80/20
0.1140.114
316319Z2-044 C
80/20
0.0740.074
937481AD2-202 C
80/20
0.6410.641
3151641KERR 7
80/20
1.5621.562
316123AC1-075 C
80/20
0.9540.954
316205AC1-080 C
80/20
0.3190.319
316011AB1-132 C OP
80/20
0.7060.706
316263AC1-034 C
80/20
2.2322.232
959311AF2-222 C
80/20
38.88938.889
942751AE2-291 C
80/20
8.1328.132
3151561HALLBR1
80/20
0.5580.558
960081AF2-299 C
80/20
0.9420.942
3151541CLOVER2
80/20
22.26722.267
3151631KERR 6
80/20
1.5621.562
936261AD2-033 C
80/20
27.65427.654
961791AG1-021 C
80/20
4.6754.675
3144293JTRSVLE
80/20
1.0761.076
316248AF1-058 C
80/20
0.450.45
936171AD2-023 C
80/20
2.1132.113
941801AE2-185 C
80/20
1.9581.958
966621AG1-532 C
80/20
0.7060.706
316003AC1-222 C
80/20
1.3491.349
936161AD2-022 C
80/20
3.6223.622
313506AB1-173 C OP
80/20
0.5620.562
3151361ROSEMG1
80/20
0.6210.621
957481AF2-042 C
80/20
98.01698.016
316210AC1-098 C
80/20
0.3390.339
316327AA2-057 C
80/20
0.4730.473
316239AB2-077 C O1
80/20
0.5670.567
935171AD1-152 C
80/20
2.1562.156
964791AG1-342 C
80/20
5.5375.537
3151411GASTONB
80/20
0.9240.924
316181AB2-040 GEN
80/20
0.6330.633
3156063AA2-053SOLA
80/20
0.680.68
3151281ROARAP4
80/20
0.6450.645
316238AB2-078 C O1
80/20
0.5670.567
316237AB2-079 C O1
80/20
0.5670.567
938821AE1-108 C
Adder
-10.591764705882353-9.003
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1192.119
CBM South 2LTFEXP_CBM-S2->PJM
CBM
35.23335.233
CPLELTFEXP_CPLE->PJM
CLTF
4.4464.446
TVALTFEXP_TVA->PJM
CLTF
1.9681.968
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.1489.148
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.1237.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1991.199
LAGNLTFEXP_LAGN->PJM
CLTF
2.5182.518
NYPJM->LTFIMP_NY
CLTF
0.3720.372
LGEELTFEXP_LGEE->PJM
CLTF
0.3590.359
WECLTFEXP_WEC->PJM
CLTF
0.190.19
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072

Details for 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.42 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:648.23
MW Contribution:1.11
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.5 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:688.68
MW Contribution:1.12
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940491AE2-034 C
80/20
2.3412.341
934501AD1-074 C
80/20
69.11769.117
3156021HOLLOMANSOL
80/20
4.1274.127
316049AB1-081 C OP
80/20
1.3321.332
3156073AA1-063SOLA
80/20
1.1081.108
3151371ROSEMS1
80/20
1.2321.232
961671AG1-007 C
80/20
1.1121.112
316359AB2-059 C OP
80/20
1.571.57
316087AB2-174 C
80/20
0.8050.805
943171AE2-346 C
80/20
0.3740.374
961941AG1-037 C
80/20
0.8430.843
3151391GASTONA
80/20
2.992.99
3151381ROSEMG2
80/20
0.9310.931
934331AD1-057 C
80/20
3.3453.345
934321AD1-056 C
80/20
5.9965.996
316129AC1-054 C
80/20
0.6740.674
957861AF2-080 C
80/20
10.44310.443
316023AB2-100 C2
80/20
0.5940.594
946281AF1-292 C
80/20
0.9210.921
926071AC1-086 C
80/20
20.57620.576
316317KELFORD C
80/20
0.5890.589
927021AC1-189 C
80/20
11.49811.498
3151151S HAMPT1
80/20
0.4350.435
962571AG1-106 C
80/20
2.6612.661
932631AC2-084 C
80/20
1.2271.227
316274AC1-208 C
80/20
9.5699.569
3151311EDGECMA
80/20
14.76714.767
315614AA2-178 C
80/20
3.1813.181
933981AD1-022 C
80/20
18.40618.406
3151261ROARAP2
80/20
1.211.21
3147043LAWRENC
80/20
0.1460.146
3156116Z1-036WIND
80/20
1.3161.316
3152921DOMTR78
80/20
2.6612.661
316140AB2-099 C
80/20
0.1610.161
3137643SOCKMAN
80/20
0.5730.573
316212AC1-099 C
80/20
0.3860.386
316319Z2-044 C
80/20
0.2070.207
934521AD1-076 C
80/20
25.10225.102
934511AD1-075 C
80/20
17.27917.279
316011AB1-132 C OP
80/20
2.2832.283
316263AC1-034 C
80/20
6.2256.225
960081AF2-299 C
80/20
1.1131.113
966621AG1-532 C
80/20
0.8350.835
3156083AA2-088SOLA
80/20
0.6410.641
313506AB1-173 C OP
80/20
0.8160.816
3151361ROSEMG1
80/20
1.9891.989
316005AA1-067 C
80/20
0.4290.429
316365AB2-100 C1
80/20
0.5940.594
316318V4-068 C
80/20
0.0840.084
316210AC1-098 C
80/20
1.1521.152
316327AA2-057 C
80/20
1.3351.335
3151411GASTONB
80/20
2.992.99
316181AB2-040 GEN
80/20
0.9190.919
316174AB2-169_C
80/20
1.9111.911
3156063AA2-053SOLA
80/20
1.5851.585
3151281ROARAP4
80/20
1.1451.145
3156011CONETOE2SOL
80/20
1.5831.583
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4372.437
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.337.3
CPLELTFEXP_CPLE->PJM
CLTF
5.1125.112
TVALTFEXP_TVA->PJM
CLTF
2.2172.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.90912.909
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4168.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5351.535
LAGNLTFEXP_LAGN->PJM
CLTF
2.8432.843
NYPJM->LTFIMP_NY
CLTF
0.2690.269
LGEELTFEXP_LGEE->PJM
CLTF
0.4860.486
WECLTFEXP_WEC->PJM
CLTF
0.2620.262
SIGELTFEXP_SIGE->PJM
CLTF
0.0950.095

Details for 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2131_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.23 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:635.73
MW Contribution:1.11
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2131_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.31 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:681.91
MW Contribution:1.12
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316049AB1-081 C OP
80/20
1.3331.333
940491AE2-034 C
80/20
2.3422.342
934501AD1-074 C
80/20
69.12869.128
3156021HOLLOMANSOL
80/20
4.1284.128
3156073AA1-063SOLA
80/20
1.1081.108
3151371ROSEMS1
80/20
1.2321.232
961671AG1-007 C
80/20
1.1131.113
316359AB2-059 C OP
80/20
1.5711.571
316087AB2-174 C
80/20
0.8060.806
943171AE2-346 C
80/20
0.3750.375
961941AG1-037 C
80/20
0.8430.843
3151391GASTONA
80/20
2.9912.991
3151381ROSEMG2
80/20
0.9320.932
934331AD1-057 C
80/20
3.3463.346
934321AD1-056 C
80/20
5.9985.998
316129AC1-054 C
80/20
0.6750.675
957861AF2-080 C
80/20
10.44510.445
316023AB2-100 C2
80/20
0.5940.594
946281AF1-292 C
80/20
0.9220.922
926071AC1-086 C
80/20
20.58320.583
316317KELFORD C
80/20
0.5890.589
927021AC1-189 C
80/20
11.50111.501
3151151S HAMPT1
80/20
0.4350.435
962571AG1-106 C
80/20
2.6622.662
932631AC2-084 C
80/20
1.2281.228
316274AC1-208 C
80/20
9.5729.572
3151311EDGECMA
80/20
14.77214.772
938531AE1-072 C
Adder
-6.952941176470588-5.91
315614AA2-178 C
80/20
3.1823.182
933981AD1-022 C
80/20
18.40918.409
3151261ROARAP2
80/20
1.211.21
3147043LAWRENC
80/20
0.1460.146
3152921DOMTR78
80/20
2.6612.661
316140AB2-099 C
80/20
0.1610.161
3137643SOCKMAN
80/20
0.5730.573
316212AC1-099 C
80/20
0.3860.386
316319Z2-044 C
80/20
0.2070.207
934521AD1-076 C
80/20
25.10625.106
934511AD1-075 C
80/20
17.28217.282
316011AB1-132 C OP
80/20
2.2842.284
316263AC1-034 C
80/20
6.2276.227
960081AF2-299 C
80/20
1.1141.114
966621AG1-532 C
80/20
0.8350.835
3156083AA2-088SOLA
80/20
0.6420.642
313506AB1-173 C OP
80/20
0.8170.817
3151361ROSEMG1
80/20
1.9891.989
316005AA1-067 C
80/20
0.4290.429
316365AB2-100 C1
80/20
0.5940.594
316318V4-068 C
80/20
0.0840.084
316210AC1-098 C
80/20
1.1531.153
316327AA2-057 C
80/20
1.3361.336
3151411GASTONB
80/20
2.9912.991
316181AB2-040 GEN
80/20
0.920.92
316174AB2-169_C
80/20
1.9121.912
3156063AA2-053SOLA
80/20
1.5851.585
3151281ROARAP4
80/20
1.1451.145
3156011CONETOE2SOL
80/20
1.5831.583
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.442.44
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.35737.357
CPLELTFEXP_CPLE->PJM
CLTF
5.1185.118
TVALTFEXP_TVA->PJM
CLTF
2.2252.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.00413.004
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4538.453
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5441.544
LAGNLTFEXP_LAGN->PJM
CLTF
2.8532.853
NYPJM->LTFIMP_NY
CLTF
0.2650.265
LGEELTFEXP_LGEE->PJM
CLTF
0.4890.489
WECLTFEXP_WEC->PJM
CLTF
0.2640.264
SIGELTFEXP_SIGE->PJM
CLTF
0.0950.095

Details for 6POE-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6POE-6TYLER1 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.13 %
Rating:541.0 MVA
Rating Type:C
MVA to Mitigate:563.34
MW Contribution:1.45
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6POE-6TYLER1 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.84 %
Rating:541.0 MVA
Rating Type:C
MVA to Mitigate:588.85
MW Contribution:1.41
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316349AD2-085 C
Adder
1.69882352941176461.444
938772AE1-103 E
Adder
1.20117647058823531.021
960082AF2-299 E
Adder
0.57764705882352940.491
946281AF1-292 C
Adder
0.71764705882352940.61
926071AC1-086 C
Adder
8.9552941176470597.612
963042AG1-153 E
Adder
3.28588235294117672.793
927021AC1-189 C
Adder
2.7035294117647062.298
964241AG1-285 C
Adder
4.1470588235294123.525
924152AB2-059 E OP
Adder
1.83411764705882341.559
962561AG1-105 C
Adder
2.82588235294117672.402
936666AD2-085 E
Adder
2.77176470588235272.356
938771AE1-103 C
Adder
0.87058823529411770.74
3145413WATKINS
Adder
0.215294117647058830.183
960081AF2-299 C
Adder
0.86705882352941180.737
940541AE2-040 C
50/50
1.7881.788
940481AE2-033 C
50/50
9.8449.844
940482AE2-033 E
50/50
6.6366.636
923263AB1-132 E OP
Adder
2.60588235294117652.215
925612AC1-036 E
Adder
0.260.221
924312AB2-078 E O1
Adder
0.440.374
926072AC1-086 E
Adder
4.0752941176470593.464
944011AF1-069 C
Adder
5.2117647058823534.43
963041AG1-153 C
Adder
2.1905882352941181.862
957862AF2-080 E
Adder
1.08823529411764720.925
962562AG1-105 E
Adder
1.8835294117647061.601
923852AB2-025 E
50/50
0.7230.723
939412AE1-173 E
Adder
19.10941176470588216.243
961942AG1-037 E
Adder
0.105882352941176470.09
961941AG1-037 C
Adder
0.158823529411764720.135
941032AE2-094 E
Adder
7.1447058823529426.073
941031AE2-094 C
Adder
15.95176470588235213.559
934332AD1-057 E
Adder
0.69411764705882350.59
934331AD1-057 C
Adder
1.3317647058823531.132
934321AD1-056 C
Adder
2.3882352941176472.03
934322AD1-056 E
Adder
1.2952941176470591.101
927022AC1-189 E
Adder
1.34705882352941191.145
925595AC1-034 E
Adder
1.74000000000000021.479
3145393UNCAMP
Adder
1.841.564
900672V4-068 E
Adder
0.116470588235294130.099
924302AB2-077 E O1
Adder
0.440.374
944641AF1-129 C
Adder
-70.29176470588236-59.748
316240AF1-291 C
Adder
-2.144705882352941-1.823
316381AD1-082 C
50/50
1.0531.053
942342AE2-247 E
Adder
1.01647058823529420.864
920042AA2-088 E OP
Adder
3.4941176470588242.97
3145723EMPORIA
Adder
0.196470588235294150.167
923573AB1-173 E OP
Adder
1.40588235294117661.195
919692AA2-053 E OP
Adder
1.57764705882352941.341
925785AC1-054 E
Adder
1.22941176470588221.045
316263AC1-034 C
Adder
2.30588235294117631.96
939192AE1-149 E
50/50
7.667.66
924517AB2-100 E2
Adder
1.4764705882352941.255
957482AF2-042 E
Adder
12.50352941176470610.628
961671AG1-007 C
Adder
0.31294117647058830.266
934621AD1-088 C
Adder
3.12235294117647082.654
935172AD1-152 E
Adder
1.7964705882352941.527
943461AF1-017 C
Adder
0.66588235294117650.566
932596AC2-079 E
Adder
4.3541176470588243.701
316311AC2-079 C
Adder
2.6682352941176472.268
966622AG1-532 E
Adder
0.434117647058823550.369
922923AB1-081 E OP
Adder
1.2952941176470591.101
316084AB2-161 E
50/50
4.6154.615
316083AB2-161 C
50/50
0.4620.462
927146AC1-208 E
Adder
1.43647058823529421.221
934622AD1-088 E
Adder
1.5035294117647061.278
934612AD1-087 E
Adder
1.21882352941176491.036
962572AG1-106 E
Adder
0.50705882352941180.431
926214AC1-099 E
Adder
0.420.357
932632AC2-084 E
Adder
1.12235294117647060.954
964242AG1-285 E
Adder
2.76470588235294162.35
924162AB2-060 E OP
Adder
1.39764705882352951.188
964792AG1-342 E
Adder
0.74588235294117660.634
939411AE1-173 C
Adder
28.66352941176470624.364
3137643SOCKMAN
Adder
0.289411764705882370.246
919710AA2-057 E
Adder
1.39647058823529411.187
316315AB2-025 C
50/50
0.2540.254
946282AF1-292 E
Adder
0.47882352941176470.407
944012AF1-069 E
Adder
2.02470588235294141.721
957861AF2-080 C
Adder
2.4564705882352942.088
917512Z2-088 E OP1
Adder
1.60588235294117651.365
934576AD1-082 E
50/50
3.6773.677
943172AE2-346 E
Adder
0.191764705882352950.163
918492AA1-063AE OP
Adder
1.49058823529411751.267
962571AG1-106 C
Adder
1.15882352941176480.985
917332KELFORD E
Adder
0.53411764705882360.454
316274AC1-208 C
Adder
3.23411764705882382.749
917342Z2-044 E
Adder
0.209411764705882350.178
937482AD2-202 E
Adder
0.35647058823529410.303
3151311EDGECMA
Adder
5.4047058823529424.594
926274AC1-105 E
Adder
0.83529411764705890.71
942341AE2-247 C
Adder
0.73647058823529410.626
943462AF1-017 E
Adder
1.08705882352941190.924
924516AB2-100 E1
Adder
1.4764705882352941.255
966621AG1-532 C
Adder
0.65058823529411770.553
924022AB2-043 E O1
Adder
1.7070588235294121.451
3147223TWITTYS
Adder
0.288235294117647030.245
316141AB2-099 E
Adder
0.080.068
316088AB2-174 E
Adder
2.8647058823529412.435
923994AB2-040_E
Adder
2.63529411764705922.24
957481AF2-042 C
Adder
18.75411764705882315.941
961672AG1-007 E
Adder
0.17764705882352940.151
924322AB2-079 E O1
Adder
0.440.374
939191AE1-149 C
50/50
11.48911.489
3143316POE
50/50
2.8062.806
926206AC1-098 E
Adder
1.26941176470588221.079
964791AG1-342 C
Adder
1.11882352941176480.951
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7591.759
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.05430.054
CPLELTFEXP_CPLE->PJM
CLTF
3.6893.689
TVALTFEXP_TVA->PJM
CLTF
1.8151.815
O66PJM->LTFIMP_O-066
CMTX_NF
4.8534.853
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.5019.501
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7336.733
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1821.182
LAGNLTFEXP_LAGN->PJM
CLTF
2.3242.324
NYPJM->LTFIMP_NY
CLTF
0.3510.351
LGEELTFEXP_LGEE->PJM
CLTF
0.3660.366
WECLTFEXP_WEC->PJM
CLTF
0.1950.195
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7620.762
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 246T247_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.57 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1025.65
MW Contribution:7.58
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316023AB2-100 C2
50/50
2.8992.899
960082AF2-299 E
50/50
3.033.03
946281AF1-292 C
50/50
3.7633.763
926071AC1-086 C
50/50
46.66546.665
316317KELFORD C
50/50
0.4920.492
927021AC1-189 C
50/50
9.8769.876
924152AB2-059 E OP
50/50
6.4936.493
3145413WATKINS
Adder
0.46352941176470590.394
960081AF2-299 C
50/50
4.5464.546
926072AC1-086 E
50/50
21.23921.239
957862AF2-080 E
50/50
3.9763.976
923852AB2-025 E
50/50
4.8134.813
961942AG1-037 E
50/50
0.440.44
943171AE2-346 C
50/50
0.2930.293
961941AG1-037 C
50/50
0.660.66
3151391GASTONA
50/50
6.7826.782
3151381ROSEMG2
50/50
2.0312.031
934332AD1-057 E
50/50
3.0153.015
934331AD1-057 C
50/50
5.795.79
934321AD1-056 C
50/50
10.3810.38
934322AD1-056 E
50/50
5.635.63
927022AC1-189 E
50/50
4.924.92
925595AC1-034 E
50/50
6.1596.159
933981AD1-022 C
50/50
9.1789.178
900672V4-068 E
50/50
0.4080.408
3151261ROARAP2
50/50
2.3112.311
3147043LAWRENC
50/50
0.5750.575
920042AA2-088 E OP
50/50
10.51410.514
934521AD1-076 C
Adder
11.5117647058823539.785
934511AD1-075 C
Adder
7.9247058823529416.736
3145723EMPORIA
50/50
1.0091.009
316011AB1-132 C OP
50/50
5.1785.178
923573AB1-173 E OP
50/50
6.8286.828
919692AA2-053 E OP
50/50
6.8186.818
925785AC1-054 E
50/50
3.6593.659
316263AC1-034 C
50/50
8.1648.164
934501AD1-074 C
Adder
31.6976470588235326.943
924517AB2-100 E2
50/50
8.7398.739
3156021HOLLOMANSOL
50/50
2.4882.488
3156073AA1-063SOLA
50/50
1.9971.997
3151371ROSEMS1
50/50
2.6872.687
961671AG1-007 C
50/50
1.1341.134
316359AB2-059 C OP
50/50
2.062.06
920692AA2-178 E
Adder
3.17882352941176462.702
966622AG1-532 E
50/50
2.2732.273
922923AB1-081 E OP
50/50
4.5834.583
3145946PLYMOUTH TP
Adder
0.29529411764705880.251
933982AD1-022 E
50/50
4.9974.997
927146AC1-208 E
50/50
5.7665.766
316049AB1-081 C OP
50/50
1.7471.747
316087AB2-174 C
50/50
2.5782.578
962572AG1-106 E
50/50
2.6412.641
926214AC1-099 E
50/50
1.6911.691
932632AC2-084 E
50/50
4.5254.525
316140AB2-099 C
50/50
0.1260.126
3137643SOCKMAN
50/50
1.3231.323
316212AC1-099 C
50/50
0.4430.443
919710AA2-057 E
50/50
5.3025.302
316319Z2-044 C
50/50
0.2710.271
316315AB2-025 C
50/50
1.691.69
946282AF1-292 E
50/50
2.5082.508
316129AC1-054 C
50/50
1.2981.298
957861AF2-080 C
50/50
8.978.97
917512Z2-088 E OP1
50/50
5.845.84
940492AE2-034 E
Adder
2.38470588235294122.027
934522AD1-076 E
Adder
5.8670588235294124.987
943172AE2-346 E
50/50
0.7920.792
918492AA1-063AE OP
50/50
5.7965.796
962571AG1-106 C
50/50
6.0366.036
917332KELFORD E
50/50
2.262.26
925122AB2-169 E
50/50
5.9385.938
932631AC2-084 C
50/50
1.4081.408
316274AC1-208 C
50/50
12.98612.986
917342Z2-044 E
50/50
0.7670.767
3151311EDGECMA
50/50
19.39519.395
940541AE2-040 C
50/50
11.90111.901
934512AD1-075 E
Adder
4.0341176470588243.429
934502AD1-074 E
Adder
16.1352941176470613.715
924516AB2-100 E1
50/50
8.7398.739
918512AA1-065 E OP
50/50
7.4787.478
966621AG1-532 C
50/50
3.4093.409
918532AA1-067 E
50/50
0.8110.811
3156083AA2-088SOLA
50/50
1.0531.053
316141AB2-099 E
50/50
0.330.33
316088AB2-174 E
50/50
14.27414.274
313506AB1-173 C OP
50/50
2.3472.347
923994AB2-040_E
50/50
12.80212.802
3151361ROSEMG1
50/50
4.3384.338
316005AA1-067 C
50/50
0.3090.309
961672AG1-007 E
50/50
0.6420.642
316365AB2-100 C1
50/50
2.8992.899
316318V4-068 C
50/50
0.0920.092
316210AC1-098 C
50/50
1.3221.322
926206AC1-098 E
50/50
5.1195.119
316327AA2-057 C
50/50
1.741.74
940481AE2-033 C
50/50
64.71464.714
940482AE2-033 E
50/50
43.62743.627
923263AB1-132 E OP
50/50
13.58113.581
3151411GASTONB
50/50
6.7826.782
316181AB2-040 GEN
50/50
2.6442.644
316174AB2-169_C
50/50
1.0811.081
3156063AA2-053SOLA
50/50
2.4322.432
3151281ROARAP4
50/50
2.1862.186
3156011CONETOE2SOL
50/50
1.4931.493
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.532.53
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.00939.009
CPLELTFEXP_CPLE->PJM
CLTF
5.3075.307
TVALTFEXP_TVA->PJM
CLTF
2.2552.255
O66PJM->LTFIMP_O-066
CMTX_NF
5.2435.243
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.20112.201
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4278.427
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4961.496
LAGNLTFEXP_LAGN->PJM
CLTF
2.8922.892
NYPJM->LTFIMP_NY
CLTF
0.3770.377
LGEELTFEXP_LGEE->PJM
CLTF
0.4660.466
WECLTFEXP_WEC->PJM
CLTF
0.250.25
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8240.824
SIGELTFEXP_SIGE->PJM
CLTF
0.0920.092

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.21 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:761.57
MW Contribution:4.4
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.21 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:781.94
MW Contribution:4.41
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316049AB1-081 C OP
80/20
1.4931.493
3151611KERR 4
80/20
0.8610.861
316087AB2-174 C
80/20
2.4642.464
313527AB2-043 C
80/20
0.3630.363
3151591KERR 2
80/20
0.8610.861
943171AE2-346 C
80/20
0.2140.214
961941AG1-037 C
80/20
0.4820.482
3151391GASTONA
80/20
6.1746.174
3151381ROSEMG2
80/20
1.8431.843
934331AD1-057 C
80/20
5.1315.131
934321AD1-056 C
80/20
9.1989.198
958211AF2-115 C
80/20
1.1341.134
316315AB2-025 C
80/20
1.661.66
316129AC1-054 C
80/20
1.341.34
957861AF2-080 C
80/20
6.8536.853
316131AB2-060 C
80/20
1.0331.033
3138533PONTONDP
80/20
0.3360.336
316118AC1-105 C
80/20
0.4840.484
316023AB2-100 C2
80/20
2.7732.773
946281AF1-292 C
80/20
3.643.64
926071AC1-086 C
80/20
42.48542.485
316317KELFORD C
80/20
0.3690.369
927021AC1-189 C
80/20
7.5457.545
3151531CLOVER1
80/20
5.8145.814
964241AG1-285 C
80/20
7.2197.219
316034AC1-036 C
80/20
0.1230.123
962561AG1-105 C
80/20
5.2835.283
3151151S HAMPT1
80/20
0.9560.956
962571AG1-106 C
80/20
5.4955.495
932631AC2-084 C
80/20
1.171.17
316274AC1-208 C
80/20
11.22211.222
3151311EDGECMA
80/20
16.54816.548
3151601KERR 3
80/20
0.8610.861
3151581KERR 1
80/20
0.3070.307
3152661PLYWOOD A
80/20
0.6380.638
933981AD1-022 C
80/20
5.6845.684
3151261ROARAP2
80/20
2.1232.123
3147043LAWRENC
80/20
0.5790.579
3151621KERR 5
80/20
0.8610.861
3152921DOMTR78
80/20
0.8530.853
316140AB2-099 C
80/20
0.0920.092
3137643SOCKMAN
80/20
1.2371.237
316212AC1-099 C
80/20
0.3680.368
316319Z2-044 C
80/20
0.2310.231
3151641KERR 7
80/20
0.8610.861
934501AD1-074 C
80/20
19.34719.347
3156021HOLLOMANSOL
80/20
1.5851.585
3156073AA1-063SOLA
80/20
1.8141.814
3151371ROSEMS1
80/20
2.4382.438
961671AG1-007 C
80/20
0.9120.912
934621AD1-088 C
80/20
4.4014.401
316359AB2-059 C OP
80/20
1.761.76
946301AF1-294 C
80/20
1.8641.864
934521AD1-076 C
80/20
7.0267.026
934511AD1-075 C
80/20
4.8374.837
316011AB1-132 C OP
80/20
4.7154.715
316263AC1-034 C
80/20
6.9786.978
959311AF2-222 C
80/20
8.6298.629
960081AF2-299 C
80/20
4.3984.398
3151631KERR 6
80/20
0.8610.861
936261AD2-033 C
80/20
8.0238.023
961791AG1-021 C
80/20
0.9070.907
3144293JTRSVLE
80/20
0.2090.209
966621AG1-532 C
80/20
3.2983.298
3156083AA2-088SOLA
80/20
0.9350.935
313506AB1-173 C OP
80/20
2.2292.229
3151361ROSEMG1
80/20
3.9353.935
316005AA1-067 C
80/20
0.2210.221
957481AF2-042 C
80/20
24.2924.29
316365AB2-100 C1
80/20
2.7732.773
316318V4-068 C
80/20
0.0750.075
316210AC1-098 C
80/20
1.0991.099
316327AA2-057 C
80/20
1.4881.488
316239AB2-077 C O1
80/20
0.2290.229
964791AG1-342 C
80/20
2.0342.034
940541AE2-040 C
80/20
11.68811.688
940481AE2-033 C
80/20
63.40163.401
3151411GASTONB
80/20
6.1746.174
316181AB2-040 GEN
80/20
2.512.51
316174AB2-169_C
80/20
0.7190.719
3156063AA2-053SOLA
80/20
2.1572.157
3151281ROARAP4
80/20
2.0092.009
3156011CONETOE2SOL
80/20
1.1751.175
316238AB2-078 C O1
80/20
0.2290.229
316237AB2-079 C O1
80/20
0.2290.229
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1852.185
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.08134.081
CPLELTFEXP_CPLE->PJM
CLTF
4.5834.583
TVALTFEXP_TVA->PJM
CLTF
2.0082.008
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.08611.086
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.537.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.351.35
LAGNLTFEXP_LAGN->PJM
CLTF
2.5652.565
NYPJM->LTFIMP_NY
CLTF
0.370.37
LGEELTFEXP_LGEE->PJM
CLTF
0.4270.427
WECLTFEXP_WEC->PJM
CLTF
0.2270.227
SIGELTFEXP_SIGE->PJM
CLTF
0.0830.083

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.1 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:753.98
MW Contribution:4.52
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.29 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:816.35
MW Contribution:4.57
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316049AB1-081 C OP
80/20
1.711.71
3151611KERR 4
80/20
0.6570.657
940491AE2-034 C
80/20
0.7380.738
934501AD1-074 C
80/20
28.02128.021
3156021HOLLOMANSOL
80/20
2.3822.382
3156073AA1-063SOLA
80/20
1.9731.973
3151371ROSEMS1
80/20
2.6552.655
961671AG1-007 C
80/20
1.1011.101
316359AB2-059 C OP
80/20
2.0162.016
316087AB2-174 C
80/20
2.5582.558
313527AB2-043 C
80/20
0.2330.233
3151591KERR 2
80/20
0.6570.657
943171AE2-346 C
80/20
0.2840.284
961941AG1-037 C
80/20
0.6390.639
3151391GASTONA
80/20
6.7056.705
3151381ROSEMG2
80/20
2.0072.007
934331AD1-057 C
80/20
5.6995.699
934321AD1-056 C
80/20
10.21610.216
316315AB2-025 C
80/20
1.6881.688
316129AC1-054 C
80/20
1.2811.281
957861AF2-080 C
80/20
8.6558.655
316131AB2-060 C
80/20
0.6590.659
316023AB2-100 C2
80/20
2.8842.884
946281AF1-292 C
80/20
3.743.74
926071AC1-086 C
80/20
46.13446.134
316317KELFORD C
80/20
0.4770.477
927021AC1-189 C
80/20
9.5299.529
962561AG1-105 C
80/20
3.043.04
3151151S HAMPT1
80/20
1.0411.041
962571AG1-106 C
80/20
5.9675.967
932631AC2-084 C
80/20
1.3771.377
316274AC1-208 C
80/20
12.73812.738
3151311EDGECMA
80/20
18.97618.976
3151601KERR 3
80/20
0.6570.657
3151581KERR 1
80/20
0.2350.235
315614AA2-178 C
80/20
1.0031.003
933981AD1-022 C
80/20
8.3398.339
3151261ROARAP2
80/20
2.2812.281
3147043LAWRENC
80/20
0.5710.571
3151621KERR 5
80/20
0.6570.657
3156116Z1-036WIND
80/20
0.2550.255
3152921DOMTR78
80/20
1.211.21
316140AB2-099 C
80/20
0.1220.122
3137643SOCKMAN
80/20
1.3091.309
316212AC1-099 C
80/20
0.4330.433
316319Z2-044 C
80/20
0.2650.265
3151641KERR 7
80/20
0.6570.657
934521AD1-076 C
80/20
10.17610.176
934511AD1-075 C
80/20
7.0057.005
316011AB1-132 C OP
80/20
5.125.12
316263AC1-034 C
80/20
7.9897.989
938771AE1-103 C
80/20
1.2891.289
960081AF2-299 C
80/20
4.5184.518
3151631KERR 6
80/20
0.6570.657
936261AD2-033 C
80/20
4.7864.786
966621AG1-532 C
80/20
3.3883.388
3156083AA2-088SOLA
80/20
1.0451.045
313506AB1-173 C OP
80/20
2.3272.327
3151361ROSEMG1
80/20
4.2864.286
316005AA1-067 C
80/20
0.2960.296
316365AB2-100 C1
80/20
2.8842.884
316318V4-068 C
80/20
0.090.09
316210AC1-098 C
80/20
1.2931.293
316327AA2-057 C
80/20
1.7041.704
316239AB2-077 C O1
80/20
0.1480.148
964791AG1-342 C
80/20
1.1391.139
940541AE2-040 C
80/20
11.88611.886
940481AE2-033 C
80/20
64.6164.61
3151411GASTONB
80/20
6.7056.705
316181AB2-040 GEN
80/20
2.6212.621
316174AB2-169_C
80/20
0.9970.997
3156063AA2-053SOLA
80/20
2.3932.393
3151281ROARAP4
80/20
2.1582.158
3156011CONETOE2SOL
80/20
1.4451.445
316238AB2-078 C O1
80/20
0.1480.148
316237AB2-079 C O1
80/20
0.1480.148
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4592.459
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.93537.935
CPLELTFEXP_CPLE->PJM
CLTF
5.1585.158
TVALTFEXP_TVA->PJM
CLTF
2.1942.194
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.86411.864
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.1968.196
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4551.455
LAGNLTFEXP_LAGN->PJM
CLTF
2.8132.813
NYPJM->LTFIMP_NY
CLTF
0.3670.367
LGEELTFEXP_LGEE->PJM
CLTF
0.4530.453
WECLTFEXP_WEC->PJM
CLTF
0.2430.243
SIGELTFEXP_SIGE->PJM
CLTF
0.0890.089

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.16 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4182.74
MW Contribution:4.51
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.7 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4637.48
MW Contribution:4.5
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934576AD1-082 E
Adder
5.7482352941176484.886
916191Z1-068 C
50/50
0.0680.068
933292AC2-141 E
50/50
20.76320.763
316294AC1-161 C
50/50
7.9487.948
944602AF1-125 E
50/50
159.152159.152
3145506HICKORY
50/50
3.3883.388
943612AF1-032 E
Adder
1.40823529411764731.197
957871AF2-081 C
50/50
15.47915.479
940492AE2-034 E
Adder
4.6305882352941183.936
934522AD1-076 E
Adder
9.3011764705882357.906
943172AE2-346 E
Adder
0.88941176470588230.756
918492AA1-063AE OP
Adder
5.9423529411764715.051
962571AG1-106 C
Adder
3.9364705882352943.346
917332KELFORD E
Adder
2.39764705882352922.038
925122AB2-169 E
Adder
8.4305882352941197.166
316274AC1-208 C
Adder
12.93882352941176410.998
917342Z2-044 E
Adder
0.84705882352941180.72
937482AD2-202 E
Adder
1.57764705882352941.341
3151311EDGECMA
Adder
21.84705882352941218.57
942342AE2-247 E
Adder
2.92470588235294172.486
316036AC1-147 C
50/50
0.5640.564
919152AA1-139 E1
50/50
6.336.33
316018AA1-139 ULT2
50/50
1.6761.676
920042AA2-088 E OP
Adder
15.59882352941176513.259
934521AD1-076 C
Adder
18.24823529411764515.511
934511AD1-075 C
Adder
12.56117647058823510.677
3145723EMPORIA
Adder
0.62470588235294120.531
939191AE1-149 C
Adder
13.15411764705882411.181
316349AD2-085 C
Adder
4.8858823529411764.153
935112AD1-144 E
Adder
1.38117647058823521.174
3151091ELIZAR2
50/50
4.8274.827
944582AF1-123 E
50/50
161.69161.69
944592AF1-124 E
50/50
162.275162.275
923832AB2-022 E
50/50
1.9081.908
938772AE1-103 E
Adder
6.0023529411764715.102
916042Z1-036 E
Adder
43.3141176470588236.817
960082AF2-299 E
Adder
1.80588235294117651.535
946281AF1-292 C
Adder
2.24235294117647041.906
926071AC1-086 C
Adder
30.4329411764705925.868
3151051BRUNSWICKS1
50/50
30.03530.035
963042AG1-153 E
50/50
14.69214.692
927021AC1-189 C
Adder
12.02000000000000110.217
964241AG1-285 C
Adder
17.9658823529411815.271
924152AB2-059 E OP
Adder
7.4317647058823546.317
962561AG1-105 C
Adder
12.04705882352941210.24
926662AC1-147 E
50/50
2.0262.026
916192Z1-068 E
50/50
2.92.9
957492AF2-043 E
Adder
2.16705882352941171.842
923852AB2-025 E
50/50
1.7231.723
939412AE1-173 E
50/50
105.86105.86
961942AG1-037 E
Adder
0.494117647058823550.42
961941AG1-037 C
Adder
0.74117647058823530.63
941032AE2-094 E
50/50
32.01732.017
941031AE2-094 C
50/50
71.48571.485
934332AD1-057 E
Adder
2.5917647058823532.203
934331AD1-057 C
Adder
4.9764705882352954.23
934321AD1-056 C
Adder
8.927.582
934322AD1-056 E
Adder
4.8388235294117664.113
927022AC1-189 E
Adder
5.9882352941176475.09
923573AB1-173 E OP
Adder
4.7517647058823534.039
919692AA2-053 E OP
Adder
6.1282352941176475.209
925785AC1-054 E
Adder
4.8741176470588234.143
316263AC1-034 C
Adder
9.344705882352947.943
959311AF2-222 C
Adder
21.718.445
939192AE1-149 E
Adder
8.7694117647058827.454
939312AE1-162 E
Adder
1.95882352941176491.665
3150991CHESPKB
50/50
1.1051.105
934065AD1-033 E
50/50
7.7977.797
937226AE2-253 E
50/50
9.0629.062
934501AD1-074 C
Adder
50.2447058823529442.708
924517AB2-100 E2
Adder
4.23058823529411753.596
957482AF2-042 E
50/50
55.48555.485
961671AG1-007 C
Adder
1.33294117647058831.133
961611AG1-000B C
Adder
19.52941176470588416.6
316375AC2-012 C
50/50
2.0662.066
313526AB2-022 C
50/50
0.5790.579
940541AE2-040 C
Adder
4.263.621
940481AE2-033 C
Adder
23.97176470588235420.376
940482AE2-033 E
Adder
16.1613.736
923263AB1-132 E OP
Adder
8.8564705882352937.528
3152441Z1-086 ST
50/50
32.38732.387
3152431Z1-086 GT3
50/50
18.59718.597
3152421Z1-086 GT2
50/50
18.59718.597
925612AC1-036 E
Adder
1.13647058823529410.966
924312AB2-078 E O1
Adder
1.84705882352941191.57
926274AC1-105 E
Adder
3.63.06
934621AD1-088 C
Adder
13.82823529411764711.754
935172AD1-152 E
Adder
7.9105882352941186.724
925595AC1-034 E
Adder
7.0494117647058835.992
942341AE2-247 C
Adder
2.11764705882352941.8
943462AF1-017 E
Adder
3.12588235294117662.657
958162AF2-110 E
Adder
3.24941176470588242.762
316388AE2-253 GEN
50/50
3.0473.047
919153AA1-139 E2
50/50
6.336.33
934512AD1-075 E
Adder
6.3941176470588235.435
934502AD1-074 E
Adder
25.5776470588235321.741
924516AB2-100 E1
Adder
4.23058823529411753.596
918512AA1-065 E OP
Adder
8.1470588235294116.925
940642AE2-051 E
50/50
20.9220.92
966621AG1-532 C
Adder
2.0317647058823531.727
918532AA1-067 E
Adder
1.02823529411764710.874
924022AB2-043 E O1
Adder
7.1670588235294126.092
3147223TWITTYS
Adder
1.2588235294117651.07
959312AF2-222 E
Adder
2.9682352941176472.523
3150981CHESPKA
50/50
0.6670.667
316185AD1-033 C
50/50
1.9111.911
944581AF1-123 C
50/50
70.6170.61
941101AE2-104 C
Adder
5.00705882352941254.256
316320Y1-086 C
50/50
0.3390.339
316141AB2-099 E
Adder
0.370588235294117660.315
316088AB2-174 E
Adder
9.4435294117647068.027
923994AB2-040_E
Adder
8.9094117647058837.573
957481AF2-042 C
50/50
83.22783.227
961672AG1-007 E
Adder
0.75529411764705890.642
924322AB2-079 E O1
Adder
1.84705882352941191.57
936666AD2-085 E
Adder
7.9705882352941196.775
941591AE2-156 C
50/50
27.4127.41
3151081ELIZAR1
50/50
4.9124.912
316316AC1-027 C
50/50
0.4870.487
944591AF1-124 C
50/50
70.86170.861
944601AF1-125 C
50/50
69.52369.523
938771AE1-103 C
Adder
4.3470588235294113.695
3145413WATKINS
Adder
1.02235294117647070.869
960081AF2-299 C
Adder
2.70823529411764732.302
926072AC1-086 E
Adder
13.85058823529411711.773
944011AF1-069 C
50/50
23.35723.357
963041AG1-153 C
50/50
9.7959.795
957862AF2-080 E
Adder
4.844.114
962562AG1-105 E
Adder
8.0317647058823526.827
932046AC2-012 E
50/50
20.04320.043
958161AF2-110 C
Adder
2.04352941176470631.737
316017AA1-139 ULT1
50/50
1.6761.676
938531AE1-072 C
50/50
27.18327.183
3145393UNCAMP
Adder
9.0117647058823537.66
933981AD1-022 C
Adder
13.02235294117647211.069
900672V4-068 E
Adder
0.52352941176470590.445
3152411Z1-086 GT1
50/50
18.60518.605
924302AB2-077 E O1
Adder
1.84705882352941191.57
3150921YORKTN3
Adder
152.65647058823532129.758
3145256KINGFORK
Adder
1.48823529411764691.265
925522AC1-027 E
50/50
1.8771.877
933291AC2-141 C
50/50
48.6448.64
926755AC1-161 E
50/50
20.76320.763
941102AE2-104 E
Adder
7.966.766
957872AF2-081 E
50/50
6.6346.634
962572AG1-106 E
Adder
1.72235294117647061.464
926214AC1-099 E
Adder
1.73647058823529421.476
932632AC2-084 E
Adder
4.6458823529411763.949
964242AG1-285 E
Adder
11.97764705882352810.181
924162AB2-060 E OP
Adder
5.8752941176470594.994
964792AG1-342 E
Adder
3.1905882352941182.712
943461AF1-017 C
Adder
1.91529411764705881.628
932596AC2-079 E
Adder
13.36941176470588411.364
316311AC2-079 C
Adder
8.1941176470588236.965
938532AE1-072 E
50/50
14.1714.17
3146326AYDLETT TAP
50/50
2.0962.096
917122Z2-027 E
Adder
2.061.751
920692AA2-178 E
Adder
6.1741176470588245.248
966622AG1-532 E
Adder
1.35411764705882361.151
922923AB1-081 E OP
Adder
5.2458823529411764.459
316084AB2-161 E
Adder
7.2141176470588236.132
3145946PLYMOUTH TP
Adder
0.48235294117647060.41
933982AD1-022 E
Adder
7.0894117647058836.026
940641AE2-051 C
50/50
31.3831.38
927146AC1-208 E
Adder
5.74470588235294164.883
934622AD1-088 E
Adder
6.6576470588235295.659
934612AD1-087 E
Adder
5.3905882352941184.582
913392Y1-086 E
50/50
3.383.38
939411AE1-173 C
50/50
158.79158.79
3137643SOCKMAN
Adder
1.03058823529411760.876
3151031BRUNSWICKG2
50/50
14.45714.457
919710AA2-057 E
Adder
5.6458823529411774.799
3151101ELIZAR3
50/50
4.9744.974
316315AB2-025 C
50/50
0.6050.605
946282AF1-292 E
Adder
1.49529411764705871.271
944012AF1-069 E
50/50
9.0749.074
957861AF2-080 C
Adder
10.917647058823539.28
917512Z2-088 E OP1
Adder
6.9717647058823535.926
3143316POE
Adder
1.71764705882352931.46
901082W1-029 E
Adder
48.63529411764706441.34
926206AC1-098 E
Adder
5.25647058823529444.468
3151041BRUNSWICKG3
50/50
14.45714.457
3151021BRUNSWICKG1
50/50
14.45714.457
964791AG1-342 C
Adder
4.7858823529411764.068
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6337.633
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.923129.923
CPLELTFEXP_CPLE->PJM
CLTF
16.01716.017
TVALTFEXP_TVA->PJM
CLTF
7.5637.563
O66PJM->LTFIMP_O-066
CMTX_NF
29.52729.527
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.88834.888
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.38927.389
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.6044.604
LAGNLTFEXP_LAGN->PJM
CLTF
9.689.68
NYPJM->LTFIMP_NY
CLTF
2.172.17
LGEELTFEXP_LGEE->PJM
CLTF
1.3891.389
WECLTFEXP_WEC->PJM
CLTF
0.7290.729
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6364.636
SIGELTFEXP_SIGE->PJM
CLTF
0.2790.279

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.22 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4106.12
MW Contribution:4.31
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150921YORKTN3
Adder
46.1517647058823539.229
3145256KINGFORK
Adder
1.35529411764705881.152
925522AC1-027 E
50/50
1.7051.705
933291AC2-141 C
50/50
43.61643.616
926755AC1-161 E
50/50
18.61818.618
941102AE2-104 E
Adder
7.3058823529411766.21
957872AF2-081 E
50/50
6.0346.034
962572AG1-106 E
Adder
1.63529411764705881.39
926214AC1-099 E
Adder
1.64117647058823551.395
932632AC2-084 E
Adder
4.3905882352941183.732
964242AG1-285 E
Adder
11.549.809
924162AB2-060 E OP
Adder
5.6588235294117644.81
964792AG1-342 E
Adder
3.07411764705882362.613
3151101ELIZAR3
50/50
4.5194.519
316315AB2-025 C
50/50
0.5820.582
946282AF1-292 E
Adder
1.4270588235294121.213
944012AF1-069 E
50/50
8.6848.684
957861AF2-080 C
Adder
10.3094117647058838.763
917512Z2-088 E OP1
Adder
6.5941176470588245.605
316349AD2-085 C
Adder
4.5341176470588243.854
935112AD1-144 E
Adder
1.2588235294117651.07
3151091ELIZAR2
50/50
4.3864.386
944582AF1-123 E
50/50
146.831146.831
944592AF1-124 E
50/50
147.363147.363
923832AB2-022 E
Adder
1.74000000000000021.479
938772AE1-103 E
Adder
5.5529411764705884.72
916042Z1-036 E
Adder
39.78705882352941433.819
316084AB2-161 E
Adder
6.8258823529411765.802
3145946PLYMOUTH TP
Adder
0.44705882352941180.38
933982AD1-022 E
Adder
6.582352941176475.595
940641AE2-051 C
50/50
29.73129.731
927146AC1-208 E
Adder
5.44117647058823554.625
934622AD1-088 E
Adder
6.4094117647058835.448
934611AD1-087 C
50/50
1.7961.796
934612AD1-087 E
50/50
5.1825.182
932046AC2-012 E
50/50
18.21618.216
958161AF2-110 C
Adder
1.8752941176470591.594
316017AA1-139 ULT1
50/50
1.5241.524
938531AE1-072 C
50/50
24.73924.739
3145393UNCAMP
Adder
8.3505882352941197.098
933981AD1-022 C
Adder
12.09058823529411710.277
900672V4-068 E
Adder
0.490588235294117660.417
3152411Z1-086 GT1
50/50
17.81217.812
924302AB2-077 E O1
Adder
1.77764705882352941.511
913392Y1-086 E
Adder
3.08235294117647072.62
939411AE1-173 C
50/50
149.153149.153
3137643SOCKMAN
Adder
0.97882352941176460.832
3151031BRUNSWICKG2
50/50
13.84313.843
919710AA2-057 E
Adder
5.3541176470588244.551
937481AD2-202 C
50/50
0.5210.521
939192AE1-149 E
Adder
8.424705882352947.161
939312AE1-162 E
Adder
1.79058823529411781.522
934065AD1-033 E
50/50
7.0817.081
937226AE2-253 E
50/50
8.2398.239
934501AD1-074 C
Adder
46.5682352941176539.583
924517AB2-100 E2
Adder
4.042352941176473.436
957482AF2-042 E
50/50
53.29753.297
961671AG1-007 C
Adder
1.26235294117647071.073
934621AD1-088 C
Adder
13.31176470588235211.315
935172AD1-152 E
Adder
7.6094117647058826.468
942342AE2-247 E
Adder
2.71411764705882372.307
919152AA1-139 E1
50/50
5.7585.758
316018AA1-139 ULT2
50/50
1.5241.524
920042AA2-088 E OP
Adder
14.57411764705882412.388
934521AD1-076 C
Adder
16.9129411764705914.376
934511AD1-075 C
Adder
11.6423529411764739.896
3145723EMPORIA
Adder
0.59647058823529410.507
923573AB1-173 E OP
Adder
4.5223529411764713.844
919692AA2-053 E OP
Adder
5.797647058823534.928
925785AC1-054 E
Adder
4.65176470588235353.954
316263AC1-034 C
Adder
8.8847058823529417.552
959311AF2-222 C
Adder
20.9952941176470617.846
960082AF2-299 E
Adder
1.7247058823529411.466
946281AF1-292 C
Adder
2.14117647058823521.82
926071AC1-086 C
Adder
28.90117647058823624.566
3151051BRUNSWICKS1
50/50
28.75928.759
963042AG1-153 E
50/50
14.06814.068
927021AC1-189 C
Adder
11.3505882352941179.648
3151531CLOVER1
50/50
18.24618.246
964241AG1-285 C
Adder
17.3105882352941214.714
924152AB2-059 E OP
Adder
7.0658823529411776.006
962561AG1-105 C
Adder
11.6047058823529429.864
926662AC1-147 E
Adder
1.84117647058823521.565
916192Z1-068 E
50/50
2.6352.635
957492AF2-043 E
Adder
1.97647058823529421.68
923852AB2-025 E
50/50
1.6571.657
939412AE1-173 E
50/50
99.43599.435
961942AG1-037 E
Adder
0.462352941176470630.393
961941AG1-037 C
Adder
0.69294117647058820.589
941032AE2-094 E
50/50
30.64130.641
941031AE2-094 C
50/50
68.41468.414
934332AD1-057 E
Adder
2.46235294117647062.093
934331AD1-057 C
Adder
4.72941176470588154.02
934321AD1-056 C
Adder
8.477647058823537.206
934322AD1-056 E
Adder
4.59882352941176453.909
927022AC1-189 E
Adder
5.6541176470588244.806
925595AC1-034 E
Adder
6.702352941176475.697
936262AD2-033 E
Adder
10.6635294117647069.064
936666AD2-085 E
Adder
7.397647058823536.288
941591AE2-156 C
50/50
24.9124.91
3151081ELIZAR1
50/50
4.4634.463
316316AC1-027 C
50/50
0.4430.443
944591AF1-124 C
50/50
64.34964.349
944601AF1-125 C
50/50
63.13463.134
938771AE1-103 C
Adder
4.0211764705882363.418
3145413WATKINS
Adder
0.94941176470588240.807
960081AF2-299 C
Adder
2.58705882352941162.199
926072AC1-086 E
Adder
13.15411764705882411.181
944011AF1-069 C
50/50
22.35322.353
963041AG1-153 C
50/50
9.3799.379
957862AF2-080 E
Adder
4.5705882352941173.885
3151541CLOVER2
50/50
18.07618.076
936261AD2-033 C
Adder
15.9952941176470613.596
962562AG1-105 E
Adder
7.7364705882352946.576
934576AD1-082 E
Adder
5.4388235294117654.623
916191Z1-068 C
50/50
0.0610.061
933292AC2-141 E
50/50
18.61818.618
316294AC1-161 C
50/50
7.1277.127
944602AF1-125 E
50/50
144.526144.526
3145506HICKORY
50/50
3.0783.078
943612AF1-032 E
Adder
1.28470588235294141.092
957871AF2-081 C
50/50
14.0814.08
940492AE2-034 E
Adder
4.2752941176470593.634
934522AD1-076 E
Adder
8.6200000000000017.327
943172AE2-346 E
Adder
0.8317647058823530.707
918492AA1-063AE OP
Adder
5.6035294117647064.763
962571AG1-106 C
Adder
3.73764705882352953.177
917332KELFORD E
Adder
2.25058823529411761.913
925122AB2-169 E
Adder
7.8694117647058836.689
316274AC1-208 C
Adder
12.25411764705882510.416
917342Z2-044 E
Adder
0.80352941176470590.683
937482AD2-202 E
50/50
1.5171.517
3151311EDGECMA
Adder
20.7705882352941217.655
942341AE2-247 C
Adder
1.9647058823529411.67
943462AF1-017 E
Adder
2.90117647058823552.466
958162AF2-110 E
Adder
2.98235294117647072.535
316388AE2-253 GEN
50/50
2.7712.771
919153AA1-139 E2
50/50
5.7585.758
934512AD1-075 E
Adder
5.9258823529411765.037
934502AD1-074 E
Adder
23.70588235294117420.15
924516AB2-100 E1
Adder
4.042352941176473.436
918512AA1-065 E OP
Adder
7.6023529411764716.462
940642AE2-051 E
50/50
19.82119.821
966621AG1-532 C
Adder
1.94000000000000021.649
918532AA1-067 E
Adder
0.96823529411764710.823
924022AB2-043 E O1
Adder
6.95.865
3147223TWITTYS
Adder
1.21764705882352931.035
959312AF2-222 E
Adder
14.06705882352941311.957
316185AD1-033 C
50/50
1.7361.736
944581AF1-123 C
50/50
64.12164.121
941101AE2-104 C
Adder
4.5952941176470593.906
316141AB2-099 E
Adder
0.347058823529411750.295
316088AB2-174 E
Adder
8.997647058823537.648
923994AB2-040_E
Adder
8.487.208
957481AF2-042 C
50/50
79.94679.946
961672AG1-007 E
Adder
0.71529411764705890.608
924322AB2-079 E O1
Adder
1.77764705882352941.511
943902AF1-058 E
Adder
1.65647058823529411.408
939191AE1-149 C
Adder
12.63647058823529410.741
3143316POE
Adder
1.67647058823529421.425
901082W1-029 E
Adder
44.4776470588235337.806
926206AC1-098 E
Adder
4.9670588235294124.222
3151041BRUNSWICKG3
50/50
13.84313.843
3151021BRUNSWICKG1
50/50
13.84313.843
964791AG1-342 C
Adder
4.6105882352941173.919
961611AG1-000B C
Adder
18.02352941176470615.32
316375AC2-012 C
50/50
1.8781.878
940541AE2-040 C
50/50
4.0974.097
940481AE2-033 C
50/50
23.03323.033
940482AE2-033 E
50/50
15.52815.528
923263AB1-132 E OP
Adder
8.4105882352941177.149
3152441Z1-086 ST
50/50
31.00731.007
3152431Z1-086 GT3
50/50
17.80517.805
3152421Z1-086 GT2
50/50
17.80517.805
925612AC1-036 E
Adder
1.09882352941176480.934
924312AB2-078 E O1
Adder
1.77764705882352941.511
926274AC1-105 E
Adder
3.4682352941176472.948
943461AF1-017 C
Adder
1.77764705882352941.511
932596AC2-079 E
Adder
12.38941176470588310.531
316311AC2-079 C
Adder
7.5929411764705886.454
938532AE1-072 E
50/50
12.89612.896
3146326AYDLETT TAP
50/50
1.9081.908
917122Z2-027 E
Adder
1.88117647058823521.599
920692AA2-178 E
Adder
5.74.845
966622AG1-532 E
Adder
1.29294117647058831.099
922923AB1-081 E OP
Adder
4.9882352941176474.24
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.3487.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
126.03126.03
CPLELTFEXP_CPLE->PJM
CLTF
15.41515.415
TVALTFEXP_TVA->PJM
CLTF
7.567.56
O66PJM->LTFIMP_O-066
CMTX_NF
30.16830.168
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.99436.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.67827.678
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.7584.758
LAGNLTFEXP_LAGN->PJM
CLTF
9.6549.654
NYPJM->LTFIMP_NY
CLTF
2.22.2
LGEELTFEXP_LGEE->PJM
CLTF
1.4681.468
WECLTFEXP_WEC->PJM
CLTF
0.7690.769
G-007PJM->LTFIMP_G-007
CMTX_NF
4.7394.739
SIGELTFEXP_SIGE->PJM
CLTF
0.2910.291

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T567_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T567_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.44 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4075.55
MW Contribution:4.45
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961611AG1-000B C
Adder
5.04.25
3152331SURRY 2
50/50
39.09439.094
316375AC2-012 C
50/50
2.0942.094
940541AE2-040 C
Adder
4.16470588235294153.54
940481AE2-033 C
Adder
23.45176470588235419.934
940482AE2-033 E
Adder
15.81058823529411813.439
923263AB1-132 E OP
Adder
8.7635294117647067.449
3152441Z1-086 ST
50/50
32.43232.432
3152431Z1-086 GT3
50/50
18.62318.623
3152421Z1-086 GT2
50/50
18.62318.623
925612AC1-036 E
Adder
1.11882352941176480.951
939312AE1-162 E
Adder
1.93058823529411771.641
3150991CHESPKB
50/50
1.121.12
934065AD1-033 E
50/50
7.9347.934
937226AE2-253 E
50/50
9.2149.214
934501AD1-074 C
Adder
50.4623529411764742.893
924517AB2-100 E2
Adder
4.1635294117647063.539
957482AF2-042 E
Adder
55.2517647058823546.964
961671AG1-007 C
Adder
1.32588235294117651.127
934621AD1-088 C
Adder
13.7211.662
926662AC1-147 E
Adder
2.05411764705882361.746
916192Z1-068 E
50/50
2.9452.945
957492AF2-043 E
Adder
2.18823529411764731.86
923852AB2-025 E
Adder
1.6847058823529411.432
939412AE1-173 E
50/50
106.866106.866
961942AG1-037 E
Adder
0.49294117647058820.419
961941AG1-037 C
Adder
0.740.629
941032AE2-094 E
50/50
32.08232.082
941031AE2-094 C
50/50
71.63171.631
934332AD1-057 E
Adder
2.56941176470588272.184
934331AD1-057 C
Adder
4.9341176470588244.194
934321AD1-056 C
Adder
8.844705882352947.518
934322AD1-056 E
Adder
4.797647058823534.078
927022AC1-189 E
Adder
5.9647058823529415.07
925595AC1-034 E
Adder
7.0011764705882355.951
316349AD2-085 C
Adder
4.8305882352941174.106
935112AD1-144 E
Adder
1.3835294117647061.176
3151091ELIZAR2
50/50
4.8964.896
944582AF1-123 E
50/50
164.574164.574
944592AF1-124 E
50/50
165.171165.171
923832AB2-022 E
Adder
1.93411764705882351.644
938772AE1-103 E
Adder
6.0094117647058825.108
916042Z1-036 E
Adder
43.71058823529412537.154
960082AF2-299 E
Adder
1.78117647058823541.514
946281AF1-292 C
Adder
2.21058823529411751.879
926071AC1-086 C
Adder
30.1129411764705925.596
3151051BRUNSWICKS1
50/50
30.06830.068
963042AG1-153 E
50/50
14.70814.708
927021AC1-189 C
Adder
11.97411764705882410.178
964241AG1-285 C
Adder
17.77647058823529515.11
924152AB2-059 E OP
Adder
7.3811764705882366.274
962561AG1-105 C
Adder
11.92235294117647210.134
316185AD1-033 C
50/50
1.9451.945
944581AF1-123 C
50/50
71.8771.87
941101AE2-104 C
Adder
5.0270588235294114.273
316141AB2-099 E
Adder
0.36941176470588240.314
316088AB2-174 E
Adder
9.3282352941176477.929
923994AB2-040_E
Adder
8.8082352941176477.487
957481AF2-042 C
Adder
82.8776470588235370.446
961672AG1-007 E
Adder
0.7517647058823530.639
932046AC2-012 E
50/50
20.31420.314
958161AF2-110 C
Adder
2.0517647058823531.744
316017AA1-139 ULT1
50/50
1.7031.703
938531AE1-072 C
50/50
27.61527.615
3145393UNCAMP
Adder
9.017647058823537.665
3150921YORKTN3
Adder
148.4764705882353126.205
3145256KINGFORK
Adder
1.49058823529411751.267
925522AC1-027 E
50/50
1.9061.906
933291AC2-141 C
50/50
50.29350.293
926755AC1-161 E
50/50
21.46921.469
941102AE2-104 E
Adder
7.99294117647058756.794
957872AF2-081 E
50/50
6.7436.743
962572AG1-106 E
Adder
1.7035294117647061.448
926214AC1-099 E
Adder
1.72705882352941181.468
932632AC2-084 E
Adder
4.623.927
964242AG1-285 E
Adder
11.85176470588235310.074
924162AB2-060 E OP
Adder
5.8058823529411764.935
964792AG1-342 E
Adder
3.1588235294117652.685
936666AD2-085 E
Adder
7.8811764705882356.699
941591AE2-156 C
50/50
27.78727.787
3151081ELIZAR1
50/50
4.9824.982
316316AC1-027 C
50/50
0.4950.495
944591AF1-124 C
50/50
72.12672.126
944601AF1-125 C
50/50
70.76370.763
938771AE1-103 C
Adder
4.3517647058823533.699
3145413WATKINS
Adder
1.02235294117647070.869
960081AF2-299 C
Adder
2.6705882352941182.27
926072AC1-086 E
Adder
13.70588235294117811.65
944011AF1-069 C
50/50
23.40523.405
963041AG1-153 C
50/50
9.8059.805
957862AF2-080 E
Adder
4.8211764705882354.098
962562AG1-105 E
Adder
7.9482352941176486.756
933981AD1-022 C
Adder
13.06588235294117711.106
900672V4-068 E
Adder
0.52235294117647060.444
3152411Z1-086 GT1
50/50
18.63118.631
924302AB2-077 E O1
Adder
1.82588235294117651.552
942342AE2-247 E
Adder
2.89058823529411772.457
919152AA1-139 E1
50/50
6.4346.434
316018AA1-139 ULT2
50/50
1.7031.703
920042AA2-088 E OP
Adder
15.5623529411764713.228
934521AD1-076 C
Adder
18.32705882352941315.578
934511AD1-075 C
Adder
12.6152941176470610.723
3145723EMPORIA
Adder
0.61647058823529410.524
923573AB1-173 E OP
Adder
4.6976470588235293.993
919692AA2-053 E OP
Adder
6.08588235294117655.173
925785AC1-054 E
Adder
4.8317647058823534.107
316263AC1-034 C
Adder
9.287.888
959311AF2-222 C
Adder
21.34470588235294418.143
935172AD1-152 E
Adder
7.8611764705882366.682
943461AF1-017 C
Adder
1.89411764705882371.61
932596AC2-079 E
Adder
13.2447058823529411.258
316311AC2-079 C
Adder
8.117647058823536.9
938532AE1-072 E
50/50
14.39614.396
3146326AYDLETT TAP
50/50
2.1292.129
917122Z2-027 E
Adder
2.08705882352941161.774
920692AA2-178 E
Adder
6.2129411764705885.281
966622AG1-532 E
Adder
1.3352941176470591.135
922923AB1-081 E OP
Adder
5.2094117647058834.428
316084AB2-161 E
Adder
6.937647058823535.897
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
933982AD1-022 E
Adder
7.11294117647058856.046
940641AE2-051 C
50/50
31.61831.618
927146AC1-208 E
Adder
5.7070588235294124.851
934622AD1-088 E
Adder
6.6058823529411775.615
934612AD1-087 E
Adder
5.3611764705882364.557
913392Y1-086 E
Adder
3.42705882352941152.913
939411AE1-173 C
50/50
160.299160.299
3137643SOCKMAN
Adder
1.02117647058823540.868
3151031BRUNSWICKG2
50/50
14.47314.473
919710AA2-057 E
Adder
5.6082352941176474.767
3151101ELIZAR3
50/50
5.0455.045
946282AF1-292 E
Adder
1.47411764705882351.253
944012AF1-069 E
50/50
9.0929.092
957861AF2-080 C
Adder
10.8752941176470599.244
917512Z2-088 E OP1
Adder
6.9388235294117645.898
934576AD1-082 E
Adder
5.5282352941176474.699
916191Z1-068 C
50/50
0.0690.069
933292AC2-141 E
50/50
21.46921.469
316294AC1-161 C
50/50
8.2198.219
944602AF1-125 E
50/50
161.991161.991
3145506HICKORY
50/50
3.4483.448
943612AF1-032 E
Adder
1.42235294117647081.209
957871AF2-081 C
50/50
15.73315.733
940492AE2-034 E
Adder
4.663.961
934522AD1-076 E
Adder
9.3411764705882367.94
943172AE2-346 E
Adder
0.88823529411764710.755
918492AA1-063AE OP
Adder
5.9070588235294125.021
962571AG1-106 C
Adder
3.8952941176470593.311
917332KELFORD E
Adder
2.39058823529411772.032
925122AB2-169 E
Adder
8.4411764705882367.175
316274AC1-208 C
Adder
12.85294117647058910.925
917342Z2-044 E
Adder
0.84117647058823530.715
937482AD2-202 E
Adder
1.56941176470588251.334
3151311EDGECMA
Adder
21.6952941176470618.441
942341AE2-247 C
Adder
2.09411764705882361.78
943462AF1-017 E
Adder
3.09058823529411742.627
958162AF2-110 E
Adder
3.2635294117647062.774
316388AE2-253 GEN
50/50
3.0993.099
919153AA1-139 E2
50/50
6.4346.434
934512AD1-075 E
Adder
6.422352941176475.459
934502AD1-074 E
Adder
25.6882352941176521.835
924516AB2-100 E1
Adder
4.1635294117647063.539
918512AA1-065 E OP
Adder
8.1494117647058816.927
940642AE2-051 E
50/50
21.07921.079
966621AG1-532 C
Adder
2.00352941176470621.703
918532AA1-067 E
Adder
1.02588235294117650.872
924022AB2-043 E O1
Adder
7.0847058823529416.022
3147223TWITTYS
Adder
1.241.054
959312AF2-222 E
Adder
14.30117647058823712.156
924322AB2-079 E O1
Adder
1.82588235294117651.552
943902AF1-058 E
Adder
1.70235294117647061.447
3143316POE
Adder
1.61411764705882371.372
901082W1-029 E
Adder
49.1811764705882441.804
926206AC1-098 E
Adder
5.2270588235294114.443
3151041BRUNSWICKG3
50/50
14.47314.473
3151021BRUNSWICKG1
50/50
14.47314.473
964791AG1-342 C
Adder
4.737647058823534.027
924312AB2-078 E O1
Adder
1.82588235294117651.552
926274AC1-105 E
Adder
3.5647058823529413.03
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.5637.563
CBM South 2LTFEXP_CBM-S2->PJM
CBM
128.067128.067
CPLELTFEXP_CPLE->PJM
CLTF
15.87115.871
TVALTFEXP_TVA->PJM
CLTF
7.2977.297
O66PJM->LTFIMP_O-066
CMTX_NF
27.12727.127
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.34332.343
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.24226.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.3444.344
LAGNLTFEXP_LAGN->PJM
CLTF
9.3599.359
NYPJM->LTFIMP_NY
CLTF
2.0052.005
LGEELTFEXP_LGEE->PJM
CLTF
1.2871.287
WECLTFEXP_WEC->PJM
CLTF
0.6770.677
G-007PJM->LTFIMP_G-007
CMTX_NF
4.2584.258
SIGELTFEXP_SIGE->PJM
CLTF
0.2610.261

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.39 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1062.25
MW Contribution:0.8
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.68 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1086.53
MW Contribution:0.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
933291AC2-141 C
80/20
13.44213.442
316305AF2-043 C
80/20
0.1410.141
316087AB2-174 C
80/20
0.5050.505
3151591KERR 2
80/20
0.4940.494
3151101ELIZAR3
80/20
1.3121.312
316315AB2-025 C
80/20
0.1780.178
316129AC1-054 C
80/20
0.5240.524
957861AF2-080 C
Adder
3.3247058823529412.826
316349AD2-085 C
Adder
1.15882352941176480.985
3151091ELIZAR2
80/20
1.2731.273
316023AB2-100 C2
80/20
0.4150.415
946281AF1-292 C
80/20
0.6630.663
926071AC1-086 C
80/20
9.0389.038
316317KELFORD C
80/20
0.1530.153
3151051BRUNSWICKS1
80/20
11.26211.262
927021AC1-189 C
Adder
3.66117647058823573.112
3151531CLOVER1
80/20
6.3346.334
964241AG1-285 C
80/20
5.3655.365
962561AG1-105 C
Adder
3.70941176470588243.153
940641AE2-051 C
80/20
11.53811.538
316336AC2-165 C
Adder
-10.758823529411764-9.145
934611AD1-087 C
80/20
0.6230.623
3151611KERR 4
80/20
0.4940.494
958161AF2-110 C
Adder
0.53058823529411770.451
316017AA1-139 ULT1
80/20
0.4540.454
938531AE1-072 C
80/20
7.3717.371
315614AA2-178 C
80/20
0.6580.658
933981AD1-022 C
80/20
3.6993.699
3151261ROARAP2
80/20
0.5930.593
3147043LAWRENC
80/20
0.130.13
3152411Z1-086 GT1
80/20
7.0067.006
3151621KERR 5
80/20
0.4940.494
3156116Z1-036WIND
80/20
0.2750.275
939411AE1-173 C
80/20
55.12655.126
3152921DOMTR78
80/20
0.5790.579
316140AB2-099 C
80/20
0.0410.041
3137643SOCKMAN
80/20
0.3050.305
316212AC1-099 C
80/20
0.1360.136
3151031BRUNSWICKG2
80/20
5.4215.421
937481AD2-202 C
80/20
0.1810.181
3151641KERR 7
80/20
0.4940.494
3150991CHESPKB
80/20
0.290.29
316321Z2-027 C
80/20
0.1520.152
940491AE2-034 C
80/20
0.4850.485
934501AD1-074 C
80/20
14.21814.218
3156021HOLLOMANSOL
80/20
0.7790.779
3156073AA1-063SOLA
80/20
0.5950.595
3151371ROSEMS1
80/20
0.5440.544
961671AG1-007 C
Adder
0.410588235294117640.349
934621AD1-088 C
80/20
4.3624.362
316036AC1-147 C
80/20
0.1480.148
316018AA1-139 ULT2
80/20
0.4540.454
934521AD1-076 C
80/20
5.1645.164
934511AD1-075 C
80/20
3.5543.554
316011AB1-132 C OP
80/20
1.0031.003
316263AC1-034 C
Adder
2.91411764705882352.477
959311AF2-222 C
Adder
5.57411764705882454.738
943171AE2-346 C
80/20
0.0950.095
961941AG1-037 C
80/20
0.2130.213
3151391GASTONA
80/20
1.3141.314
3151381ROSEMG2
80/20
0.4110.411
941031AE2-094 C
80/20
27.16527.165
934331AD1-057 C
Adder
1.52117647058823541.293
934321AD1-056 C
Adder
2.72588235294117662.317
941591AE2-156 C
80/20
7.2027.202
3151081ELIZAR1
80/20
1.2951.295
316316AC1-027 C
80/20
0.130.13
944591AF1-124 C
80/20
19.18819.188
944601AF1-125 C
80/20
18.82618.826
938771AE1-103 C
Adder
1.16941176470588240.994
960081AF2-299 C
80/20
0.8010.801
944011AF1-069 C
80/20
8.8768.876
963041AG1-153 C
80/20
3.6733.673
3151541CLOVER2
80/20
6.2756.275
3151631KERR 6
80/20
0.4940.494
936261AD2-033 C
Adder
4.2364705882352943.601
936171AD2-023 C
Adder
1.80117647058823521.531
916191Z1-068 C
80/20
0.0180.018
316294AC1-161 C
80/20
2.1972.197
957871AF2-081 C
80/20
4.1964.196
962571AG1-106 C
80/20
1.1691.169
932631AC2-084 C
80/20
0.4330.433
316274AC1-208 C
80/20
3.8963.896
3151311EDGECMA
Adder
6.8129411764705895.791
3151601KERR 3
80/20
0.4940.494
3151581KERR 1
80/20
0.1760.176
941011AE2-092 C
Adder
-4.452941176470588-3.785
942341AE2-247 C
Adder
0.50235294117647060.427
316246AF1-032 C
80/20
0.1150.115
316388AE2-253 GEN
80/20
0.8260.826
966621AG1-532 C
80/20
0.6010.601
936161AD2-022 C
Adder
3.0882352941176472.625
3150981CHESPKA
80/20
0.1750.175
316185AD1-033 C
80/20
0.5160.516
944581AF1-123 C
80/20
19.1219.12
941101AE2-104 C
Adder
1.31.105
316320Y1-086 C
80/20
0.0920.092
3156083AA2-088SOLA
80/20
0.4390.439
313506AB1-173 C OP
80/20
0.4830.483
3151361ROSEMG1
80/20
0.8780.878
957481AF2-042 C
80/20
28.34128.341
316365AB2-100 C1
80/20
0.4150.415
316318V4-068 C
80/20
0.0340.034
316210AC1-098 C
80/20
0.4070.407
3151041BRUNSWICKG3
80/20
5.4215.421
3151021BRUNSWICKG1
80/20
5.4215.421
935171AD1-152 C
80/20
0.6380.638
964791AG1-342 C
Adder
1.48470588235294131.262
316375AC2-012 C
80/20
0.5420.542
313526AB2-022 C
80/20
0.1570.157
940541AE2-040 C
80/20
1.2541.254
940481AE2-033 C
80/20
7.0627.062
3151411GASTONB
80/20
1.3141.314
316181AB2-040 GEN
80/20
0.5450.545
316174AB2-169_C
80/20
0.4470.447
3156063AA2-053SOLA
80/20
0.6450.645
3151281ROARAP4
80/20
0.5610.561
3152441Z1-086 ST
80/20
12.19612.196
3152431Z1-086 GT3
80/20
7.0037.003
3152421Z1-086 GT2
80/20
7.0037.003
938821AE1-108 C
Adder
-4.716470588235294-4.009
943461AF1-017 C
Adder
0.454117647058823570.386
316311AC2-079 C
Adder
1.9682352941176471.673
3156056W1-029WIND
80/20
0.3220.322
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5712.571
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.69643.696
CPLELTFEXP_CPLE->PJM
CLTF
5.3965.396
TVALTFEXP_TVA->PJM
CLTF
2.4942.494
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.53211.532
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.0379.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5141.514
LAGNLTFEXP_LAGN->PJM
CLTF
3.2073.207
NYPJM->LTFIMP_NY
CLTF
0.5140.514
LGEELTFEXP_LGEE->PJM
CLTF
0.4480.448
WECLTFEXP_WEC->PJM
CLTF
0.2390.239
SIGELTFEXP_SIGE->PJM
CLTF
0.0910.091

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.98 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4293.98
MW Contribution:4.79
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938552AE1-074 E
50/50
2.1052.105
3150921YORKTN3
Adder
175.7670588235294149.402
3145256KINGFORK
Adder
1.5952941176470591.356
925522AC1-027 E
50/50
1.9431.943
933291AC2-141 C
50/50
48.63248.632
926755AC1-161 E
50/50
20.7620.76
941102AE2-104 E
Adder
8.4494117647058827.182
957872AF2-081 E
Adder
6.8282352941176485.804
938562AE1-075 E
Adder
1.64117647058823551.395
3151101ELIZAR3
50/50
5.1725.172
316315AB2-025 C
50/50
0.650.65
946282AF1-292 E
Adder
1.58588235294117651.348
944012AF1-069 E
50/50
8.3958.395
316349AD2-085 C
Adder
5.4458823529411764.629
935112AD1-144 E
Adder
1.48117647058823531.259
3151091ELIZAR2
50/50
5.0195.019
944582AF1-123 E
50/50
166.107166.107
944592AF1-124 E
50/50
166.709166.709
923832AB2-022 E
Adder
1.96941176470588241.674
938772AE1-103 E
Adder
6.3458823529411775.394
916042Z1-036 E
Adder
44.8811764705882438.149
960082AF2-299 E
Adder
1.91529411764705881.628
946281AF1-292 C
Adder
2.37764705882352922.021
926071AC1-086 C
Adder
31.96588235294117627.171
3151051BRUNSWICKS1
50/50
28.05828.058
963042AG1-153 E
50/50
13.72513.725
316084AB2-161 E
Adder
8.717647058823537.41
3145946PLYMOUTH TP
Adder
0.50.425
933982AD1-022 E
Adder
7.3576470588235296.254
940641AE2-051 C
50/50
29.19229.192
316336AC2-165 C
Adder
14.85411764705882312.626
934622AD1-088 E
Adder
6.9164705882352945.879
934612AD1-087 E
Adder
5.42823529411764754.614
3150731STONECA
Adder
10.1976470588235298.668
935161AD1-151 C
Adder
24.22470588235294320.591
932046AC2-012 E
50/50
20.89320.893
958161AF2-110 C
Adder
2.16823529411764731.843
938531AE1-072 C
Adder
27.99411764705882523.795
3145393UNCAMP
Adder
9.5200000000000018.092
933981AD1-022 C
Adder
13.5152941176470611.488
900672V4-068 E
Adder
0.54941176470588240.467
3152411Z1-086 GT1
50/50
17.32817.328
940432AE2-027 E
Adder
13.04588235294117711.089
934012AD1-025 E
Adder
15.07294117647058812.812
913392Y1-086 E
Adder
3.48941176470588272.966
939411AE1-173 C
50/50
151.032151.032
933502AC2-165 E
Adder
11.189.503
3151031BRUNSWICKG2
50/50
13.50613.506
942001AE2-212 C
Adder
3.34588235294117632.844
939192AE1-149 E
Adder
11.2529411764705879.565
939312AE1-162 E
Adder
2.22705882352941181.893
934065AD1-033 E
50/50
8.0198.019
937226AE2-253 E
Adder
9.322352941176477.924
934501AD1-074 C
Adder
52.1070588235294144.291
958502AF2-144 E
Adder
1.89058823529411771.607
924517AB2-100 E2
Adder
4.4917647058823533.818
957482AF2-042 E
Adder
55.1988235294117646.919
934621AD1-088 C
Adder
14.36470588235294312.21
944641AF1-129 C
Adder
153.60588235294117130.565
316240AF1-291 C
Adder
3.2635294117647062.774
924814AB2-134 E
Adder
19.07058823529411716.21
942342AE2-247 E
Adder
3.262.771
919152AA1-139 E1
Adder
6.5152941176470595.538
920042AA2-088 E OP
Adder
16.40941176470588313.948
934521AD1-076 C
Adder
18.92352941176470816.085
934511AD1-075 C
Adder
13.02705882352941211.073
3145723EMPORIA
Adder
0.66117647058823540.562
923573AB1-173 E OP
Adder
5.0141176470588234.262
3150841SPRUNCB
Adder
14.05529411764705811.947
3150831SPRUNCA
Adder
14.05529411764705811.947
926662AC1-147 E
Adder
2.1117647058823531.795
916192Z1-068 E
50/50
3.0013.001
957492AF2-043 E
Adder
2.25882352941176471.92
923852AB2-025 E
50/50
1.8511.851
939412AE1-173 E
50/50
100.688100.688
923862AB2-026 E
Adder
1.9247058823529411.636
941032AE2-094 E
50/50
29.62229.622
941031AE2-094 C
50/50
66.13866.138
925332AB2-190 E
Adder
12.07529411764705810.264
927226AC1-216 E
Adder
11.6423529411764739.896
936666AD2-085 E
Adder
8.8858823529411777.553
941591AE2-156 C
50/50
28.55328.553
3151081ELIZAR1
50/50
5.1085.108
316316AC1-027 C
50/50
0.5040.504
944591AF1-124 C
50/50
72.79772.797
944601AF1-125 C
50/50
71.42271.422
938771AE1-103 C
Adder
4.5952941176470593.906
3145413WATKINS
Adder
1.07882352941176470.917
960081AF2-299 C
Adder
2.87294117647058832.442
926072AC1-086 E
Adder
14.54823529411764812.366
944011AF1-069 C
50/50
21.6121.61
963041AG1-153 C
50/50
9.159.15
3150651CHESTF6
Adder
27.96823529411764823.773
946262AF1-291 E
Adder
2.17647058823529441.85
934576AD1-082 E
Adder
6.9458823529411775.904
916191Z1-068 C
50/50
0.070.07
933292AC2-141 E
50/50
20.7620.76
316294AC1-161 C
50/50
7.9477.947
944602AF1-125 E
50/50
163.5163.5
3145506HICKORY
50/50
3.4833.483
943612AF1-032 E
Adder
1.4682352941176471.248
957871AF2-081 C
Adder
15.93294117647058713.543
940492AE2-034 E
Adder
4.84.08
934522AD1-076 E
Adder
9.6458823529411778.199
918492AA1-063AE OP
Adder
6.2388235294117655.303
962571AG1-106 C
Adder
3.9470588235294123.355
937482AD2-202 E
Adder
1.58941176470588231.351
942341AE2-247 C
Adder
2.362.006
943462AF1-017 E
Adder
3.48470588235294132.962
958162AF2-110 E
Adder
3.4494117647058822.932
919153AA1-139 E2
Adder
6.5152941176470595.538
934512AD1-075 E
Adder
6.6317647058823535.637
934502AD1-074 E
Adder
26.5247058823529422.546
924516AB2-100 E1
Adder
4.4917647058823533.818
940642AE2-051 E
50/50
19.46119.461
966621AG1-532 C
Adder
2.15411764705882371.831
940431AE2-027 C
Adder
19.56823529411764516.633
942002AE2-212 E
Adder
2.23058823529411751.896
316185AD1-033 C
50/50
1.9651.965
944581AF1-123 C
50/50
72.53972.539
941101AE2-104 C
Adder
5.3141176470588244.517
316088AB2-174 E
Adder
9.988.483
923994AB2-040_E
Adder
9.4011764705882357.991
957481AF2-042 C
Adder
82.7976470588235370.378
939191AE1-149 C
Adder
16.88000000000000314.348
3143316POE
50/50
2.1752.175
901082W1-029 E
Adder
50.41764705882352642.855
3151041BRUNSWICKG3
50/50
13.50613.506
3151021BRUNSWICKG1
50/50
13.50613.506
961611AG1-000B C
Adder
24.2858823529411820.643
316375AC2-012 C
50/50
2.1542.154
940541AE2-040 C
50/50
4.5764.576
940481AE2-033 C
50/50
25.70925.709
940482AE2-033 E
50/50
17.33217.332
923263AB1-132 E OP
Adder
9.3023529411764717.907
3152441Z1-086 ST
50/50
30.16330.163
3152431Z1-086 GT3
50/50
17.32117.321
3152421Z1-086 GT2
50/50
17.32117.321
935162AD1-151 E
Adder
16.1505882352941213.728
316233AE1-074 C
50/50
4.1784.178
943461AF1-017 C
Adder
2.1352941176470591.815
932596AC2-079 E
Adder
14.80823529411764712.587
316311AC2-079 C
Adder
9.0764705882352947.715
938532AE1-072 E
Adder
14.59294117647058912.404
3146326AYDLETT TAP
Adder
2.161.836
917122Z2-027 E
Adder
2.12941176470588231.81
920692AA2-178 E
Adder
6.45.44
966622AG1-532 E
Adder
1.43647058823529421.221
316303AF2-085
50/50
6.8996.899
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6737.673
CBM South 2LTFEXP_CBM-S2->PJM
CBM
132.286132.286
CPLELTFEXP_CPLE->PJM
CLTF
16.09616.096
TVALTFEXP_TVA->PJM
CLTF
8.1488.148
O66PJM->LTFIMP_O-066
CMTX_NF
37.46537.465
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.00241.002
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.98729.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.2215.221
LAGNLTFEXP_LAGN->PJM
CLTF
10.36610.366
NYPJM->LTFIMP_NY
CLTF
2.7212.721
LGEELTFEXP_LGEE->PJM
CLTF
1.6421.642
WECLTFEXP_WEC->PJM
CLTF
0.8540.854
G-007PJM->LTFIMP_G-007
CMTX_NF
5.8875.887
SIGELTFEXP_SIGE->PJM
CLTF
0.3220.322

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.85 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4130.98
MW Contribution:4.7
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.17 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4734.56
MW Contribution:4.82
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
946262AF1-291 E
Adder
2.00235294117647071.702
934576AD1-082 E
Adder
6.7411764705882365.73
916191Z1-068 C
50/50
0.0710.071
933292AC2-141 E
50/50
21.18321.183
316294AC1-161 C
50/50
8.1098.109
944602AF1-125 E
50/50
165.126165.126
3145506HICKORY
50/50
3.5173.517
943612AF1-032 E
Adder
1.4764705882352941.255
957871AF2-081 C
Adder
16.07411764705882413.663
940492AE2-034 E
Adder
4.8023529411764714.082
934522AD1-076 E
Adder
9.6317647058823528.187
943172AE2-346 E
Adder
0.92117647058823540.783
918492AA1-063AE OP
Adder
6.1705882352941185.245
962571AG1-106 C
Adder
4.07176470588235253.461
917332KELFORD E
Adder
2.4741176470588242.103
925122AB2-169 E
Adder
8.6764705882352937.375
937482AD2-202 E
Adder
1.5682352941176471.333
925332AB2-190 E
Adder
11.5164705882352939.789
927226AC1-216 E
Adder
11.2188235294117659.536
962962AG1-145 E
Adder
2.0305882352941181.726
936666AD2-085 E
Adder
8.7835294117647067.466
941591AE2-156 C
50/50
28.7728.77
3151081ELIZAR1
50/50
5.1485.148
316316AC1-027 C
50/50
0.5090.509
940432AE2-027 E
Adder
12.12235294117647110.304
934012AD1-025 E
Adder
14.52470588235294212.346
913392Y1-086 E
Adder
3.51411764705882362.987
939411AE1-173 C
50/50
151.38151.38
3137643SOCKMAN
Adder
1.06823529411764720.908
944641AF1-129 C
Adder
128.6564705882353109.358
316240AF1-291 C
Adder
3.0047058823529412.554
924814AB2-134 E
Adder
18.37647058823529315.62
942342AE2-247 E
Adder
3.22235294117647042.739
919152AA1-139 E1
Adder
6.57294117647058855.587
920042AA2-088 E OP
Adder
16.29647058823529413.852
934521AD1-076 C
Adder
18.8976470588235316.063
934511AD1-075 C
Adder
13.00823529411764811.057
3145723EMPORIA
Adder
0.65058823529411770.553
923573AB1-173 E OP
Adder
4.9341176470588244.194
919692AA2-053 E OP
Adder
6.3423529411764715.391
939191AE1-149 C
Adder
16.1694117647058813.744
3143316POE
Adder
2.0705882352941181.76
901082W1-029 E
Adder
50.6800000000000143.078
3151041BRUNSWICKG3
50/50
13.42713.427
3151021BRUNSWICKG1
50/50
13.42713.427
316349AD2-085 C
Adder
5.3835294117647054.576
935112AD1-144 E
Adder
1.48470588235294131.262
3151091ELIZAR2
50/50
5.0595.059
944582AF1-123 E
50/50
167.759167.759
944592AF1-124 E
50/50
168.367168.367
923832AB2-022 E
Adder
1.98352941176470581.686
938772AE1-103 E
Adder
6.3270588235294125.378
916042Z1-036 E
Adder
45.0211764705882438.268
960082AF2-299 E
Adder
1.88000000000000011.598
946281AF1-292 C
Adder
2.33411764705882341.984
926071AC1-086 C
Adder
31.48235294117647226.76
3151051BRUNSWICKS1
50/50
27.89527.895
963042AG1-153 E
50/50
13.64513.645
964241AG1-285 C
Adder
18.8416.014
3150841SPRUNCB
Adder
12.67882352941176410.777
3150831SPRUNCA
Adder
12.67882352941176410.777
926662AC1-147 E
Adder
2.12823529411764721.809
916192Z1-068 E
50/50
3.0273.027
957492AF2-043 E
Adder
2.2717647058823531.931
923852AB2-025 E
Adder
1.80470588235294121.534
939412AE1-173 E
50/50
100.92100.92
923862AB2-026 E
Adder
1.7964705882352941.527
961942AG1-037 E
Adder
0.51176470588235290.435
961941AG1-037 C
Adder
0.76823529411764710.653
941032AE2-094 E
50/50
29.48329.483
941031AE2-094 C
50/50
65.82865.828
942001AE2-212 C
Adder
3.1211764705882352.653
939192AE1-149 E
Adder
10.7800000000000019.163
939312AE1-162 E
Adder
2.21058823529411751.879
934065AD1-033 E
50/50
8.0978.097
937226AE2-253 E
50/50
9.4079.407
934501AD1-074 C
Adder
52.03294117647059444.228
958502AF2-144 E
Adder
1.76470588235294111.5
924517AB2-100 E2
Adder
4.4035294117647063.743
957482AF2-042 E
Adder
54.5552941176470646.372
934621AD1-088 C
Adder
14.14588235294117512.024
961611AG1-000B C
Adder
23.7620.196
316375AC2-012 C
50/50
2.172.17
940541AE2-040 C
Adder
4.4623529411764713.793
940481AE2-033 C
Adder
25.0882352941176521.325
940482AE2-033 E
Adder
16.9129411764705914.376
923263AB1-132 E OP
Adder
9.162352941176477.788
3152441Z1-086 ST
50/50
29.99929.999
3152431Z1-086 GT3
50/50
17.22617.226
3152421Z1-086 GT2
50/50
17.22617.226
938552AE1-074 E
50/50
1.9361.936
316160AE1-175 E
Adder
1.67529411764705881.424
3150921YORKTN3
Adder
176.88117647058823150.349
3145256KINGFORK
Adder
1.61.36
942341AE2-247 C
Adder
2.33294117647058831.983
943462AF1-017 E
Adder
3.44470588235294132.928
958162AF2-110 E
Adder
3.45058823529411772.933
316388AE2-253 GEN
50/50
3.1643.164
919153AA1-139 E2
Adder
6.57294117647058855.587
934512AD1-075 E
Adder
6.622352941176475.629
934502AD1-074 E
Adder
26.48705882352941322.514
924516AB2-100 E1
Adder
4.4035294117647063.743
918512AA1-065 E OP
Adder
8.4305882352941197.166
940642AE2-051 E
50/50
19.46619.466
966621AG1-532 C
Adder
2.11529411764705881.798
940431AE2-027 C
Adder
18.18352941176470615.456
942002AE2-212 E
Adder
2.0811764705882351.769
316185AD1-033 C
50/50
1.9851.985
944581AF1-123 C
50/50
73.26173.261
941101AE2-104 C
Adder
5.3152941176470594.518
316141AB2-099 E
Adder
0.38352941176470590.326
316088AB2-174 E
Adder
9.8129411764705888.341
923994AB2-040_E
Adder
9.2505882352941197.863
957481AF2-042 C
Adder
81.8317647058823669.557
944591AF1-124 C
50/50
73.52173.521
944601AF1-125 C
50/50
72.13372.133
938771AE1-103 C
Adder
4.582352941176473.895
3145413WATKINS
Adder
1.07411764705882360.913
960081AF2-299 C
Adder
2.822.397
926072AC1-086 E
Adder
14.32823529411764712.179
944011AF1-069 C
50/50
21.50921.509
963041AG1-153 C
50/50
9.0979.097
3150731STONECA
Adder
9.5694117647058838.134
935161AD1-151 C
Adder
23.2152941176470619.733
932046AC2-012 E
50/50
21.04921.049
958161AF2-110 C
Adder
2.16941176470588241.844
938531AE1-072 C
Adder
28.2329411764705923.998
3145393UNCAMP
Adder
9.4858823529411778.063
933981AD1-022 C
Adder
13.48352941176470711.461
900672V4-068 E
Adder
0.54588235294117650.464
3152411Z1-086 GT1
50/50
17.23317.233
925522AC1-027 E
50/50
1.961.96
933291AC2-141 C
50/50
49.62549.625
926755AC1-161 E
50/50
21.18321.183
941102AE2-104 E
Adder
8.4505882352941187.183
957872AF2-081 E
Adder
6.88823529411764755.855
938562AE1-075 E
Adder
1.53176470588235311.302
962572AG1-106 E
Adder
1.78117647058823541.514
964242AG1-285 E
Adder
12.5610.676
935162AD1-151 E
Adder
15.4776470588235313.156
316233AE1-074 C
50/50
3.8433.843
943461AF1-017 C
Adder
2.1105882352941181.794
932596AC2-079 E
Adder
14.6612.461
316311AC2-079 C
Adder
8.9858823529411777.638
938532AE1-072 E
Adder
14.7176470588235312.51
3146326AYDLETT TAP
Adder
2.17764705882352951.851
917122Z2-027 E
Adder
2.1435294117647061.822
920692AA2-178 E
Adder
6.4035294117647065.443
966622AG1-532 E
Adder
1.41058823529411771.199
316084AB2-161 E
Adder
8.467.191
3145946PLYMOUTH TP
Adder
0.50.425
933982AD1-022 E
Adder
7.346.239
940641AE2-051 C
50/50
29.19929.199
934622AD1-088 E
Adder
6.8105882352941185.789
934612AD1-087 E
Adder
5.3588235294117644.555
3151031BRUNSWICKG2
50/50
13.42713.427
3151101ELIZAR3
50/50
5.2135.213
946282AF1-292 E
Adder
1.5564705882352941.323
944012AF1-069 E
50/50
8.3568.356
316303AF2-085
50/50
6.4766.476
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.547.54
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.173129.173
CPLELTFEXP_CPLE->PJM
CLTF
15.81915.819
TVALTFEXP_TVA->PJM
CLTF
7.767.76
O66PJM->LTFIMP_O-066
CMTX_NF
34.77734.777
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.34537.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.31928.319
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8474.847
LAGNLTFEXP_LAGN->PJM
CLTF
9.8929.892
NYPJM->LTFIMP_NY
CLTF
2.5392.539
LGEELTFEXP_LGEE->PJM
CLTF
1.4991.499
WECLTFEXP_WEC->PJM
CLTF
0.780.78
G-007PJM->LTFIMP_G-007
CMTX_NF
5.4635.463
SIGELTFEXP_SIGE->PJM
CLTF
0.2970.297

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.96 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4056.76
MW Contribution:4.53
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316349AD2-085 C
Adder
5.09882352941176454.334
935112AD1-144 E
Adder
1.3882352941176471.18
3151091ELIZAR2
50/50
4.7134.713
944582AF1-123 E
50/50
156.119156.119
944592AF1-124 E
50/50
156.684156.684
923832AB2-022 E
Adder
1.8517647058823531.574
938772AE1-103 E
Adder
5.9670588235294125.072
916042Z1-036 E
Adder
42.2247058823529435.891
960082AF2-299 E
Adder
1.81058823529411761.539
946281AF1-292 C
Adder
2.24823529411764731.911
926071AC1-086 C
Adder
30.19411764705882525.665
3151051BRUNSWICKS1
50/50
26.83226.832
963042AG1-153 E
50/50
13.12513.125
964241AG1-285 C
Adder
6.4458823529411775.479
938552AE1-074 E
50/50
1.9631.963
3150921YORKTN3
Adder
163.19176470588235138.713
3145256KINGFORK
Adder
1.49529411764705871.271
925522AC1-027 E
50/50
1.8261.826
933291AC2-141 C
50/50
45.72845.728
926755AC1-161 E
50/50
19.5219.52
941102AE2-104 E
Adder
7.9317647058823536.742
957872AF2-081 E
Adder
6.4188235294117665.456
925332AB2-190 E
Adder
11.1200000000000019.452
927226AC1-216 E
Adder
10.7541176470588239.141
936666AD2-085 E
Adder
8.327.072
941591AE2-156 C
50/50
26.80726.807
3151081ELIZAR1
50/50
4.7964.796
316316AC1-027 C
50/50
0.4740.474
944591AF1-124 C
50/50
68.4268.42
944601AF1-125 C
50/50
67.12767.127
938771AE1-103 C
Adder
4.3211764705882353.673
3145413WATKINS
Adder
1.0152941176470590.863
960081AF2-299 C
Adder
2.7152941176470592.308
926072AC1-086 E
Adder
13.7423529411764711.681
944011AF1-069 C
50/50
20.67620.676
963041AG1-153 C
50/50
8.758.75
3150841SPRUNCB
Adder
12.87647058823529510.945
3150831SPRUNCA
Adder
12.87647058823529510.945
926662AC1-147 E
Adder
1.98235294117647071.685
916192Z1-068 E
50/50
2.8192.819
957492AF2-043 E
Adder
2.12235294117647081.804
923852AB2-025 E
50/50
1.7471.747
939412AE1-173 E
50/50
95.76595.765
923862AB2-026 E
Adder
1.81882352941176471.546
941032AE2-094 E
50/50
28.34228.342
941031AE2-094 C
50/50
63.2863.28
935161AD1-151 C
Adder
22.3418.989
932046AC2-012 E
50/50
19.61519.615
958161AF2-110 C
Adder
2.03529411764705871.73
938531AE1-072 C
Adder
26.31411764705882622.367
3145393UNCAMP
Adder
8.9552941176470597.612
933981AD1-022 C
Adder
12.73411764705882410.824
900672V4-068 E
Adder
0.51764705882352950.44
3152411Z1-086 GT1
50/50
16.57316.573
944641AF1-129 C
Adder
140.53529411764706119.455
316240AF1-291 C
Adder
2.99294117647058842.544
924814AB2-134 E
Adder
17.61647058823529514.974
942342AE2-247 E
Adder
3.0517647058823532.594
919152AA1-139 E1
Adder
6.1235294117647065.205
920042AA2-088 E OP
Adder
15.46470588235294113.145
934521AD1-076 C
Adder
17.82705882352941315.153
934511AD1-075 C
Adder
12.27176470588235310.431
3145723EMPORIA
Adder
0.62588235294117660.532
923573AB1-173 E OP
Adder
4.744.029
942001AE2-212 C
Adder
3.08941176470588232.626
939192AE1-149 E
Adder
10.4635294117647078.894
939312AE1-162 E
Adder
2.07764705882352941.766
934065AD1-033 E
50/50
7.5367.536
937226AE2-253 E
Adder
8.7623529411764727.448
934501AD1-074 C
Adder
49.0858823529411841.723
958502AF2-144 E
Adder
1.78705882352941181.519
924517AB2-100 E2
Adder
4.2411764705882353.605
957482AF2-042 E
Adder
52.67882352941176544.777
934621AD1-088 C
Adder
13.69411764705882511.64
935162AD1-151 E
Adder
14.89411764705882412.66
316233AE1-074 C
50/50
3.8973.897
943461AF1-017 C
Adder
2.01.7
932596AC2-079 E
Adder
13.86941176470588211.789
316311AC2-079 C
Adder
8.5011764705882367.226
938532AE1-072 E
Adder
13.7176470588235311.66
3146326AYDLETT TAP
Adder
2.02941176470588271.725
917122Z2-027 E
Adder
2.00235294117647071.702
920692AA2-178 E
Adder
6.0258823529411775.122
966622AG1-532 E
Adder
1.35764705882352941.154
316084AB2-161 E
Adder
8.1282352941176486.909
3145946PLYMOUTH TP
Adder
0.47058823529411770.4
933982AD1-022 E
Adder
6.9329411764705885.893
940641AE2-051 C
50/50
27.86227.862
316336AC2-165 C
Adder
14.02588235294117811.922
934622AD1-088 E
Adder
6.5941176470588245.605
934612AD1-087 E
Adder
5.17764705882352954.401
938562AE1-075 E
Adder
1.55058823529411781.318
962572AG1-106 E
Adder
1.7082352941176471.452
940432AE2-027 E
Adder
11.99411764705882410.195
934012AD1-025 E
Adder
13.92352941176470811.835
913392Y1-086 E
Adder
3.282.788
939411AE1-173 C
50/50
143.648143.648
933502AC2-165 E
Adder
10.5564705882352968.973
3137643SOCKMAN
Adder
1.02470588235294110.871
3151031BRUNSWICKG2
50/50
12.91612.916
3151101ELIZAR3
50/50
4.8574.857
316315AB2-025 C
50/50
0.6130.613
946282AF1-292 E
Adder
1.49882352941176471.274
944012AF1-069 E
50/50
8.0328.032
3150651CHESTF6
Adder
25.5882352941176521.75
946262AF1-291 E
Adder
1.99529411764705891.696
934576AD1-082 E
Adder
6.4764705882352945.505
916191Z1-068 C
50/50
0.0660.066
933292AC2-141 E
50/50
19.5219.52
316294AC1-161 C
50/50
7.4737.473
944602AF1-125 E
50/50
153.669153.669
3145506HICKORY
50/50
3.2743.274
943612AF1-032 E
Adder
1.38000000000000011.173
957871AF2-081 C
Adder
14.97647058823529412.73
940492AE2-034 E
Adder
4.5188235294117653.841
934522AD1-076 E
Adder
9.0858823529411777.723
918492AA1-063AE OP
Adder
5.8905882352941185.007
962571AG1-106 C
Adder
3.90588235294117643.32
937482AD2-202 E
Adder
1.5152941176470591.288
942341AE2-247 C
Adder
2.21058823529411751.879
943462AF1-017 E
Adder
3.2623529411764712.773
958162AF2-110 E
Adder
3.2376470588235292.752
919153AA1-139 E2
Adder
6.1235294117647065.205
934512AD1-075 E
Adder
6.2470588235294125.31
934502AD1-074 E
Adder
24.98705882352941321.239
924516AB2-100 E1
Adder
4.2411764705882353.605
940642AE2-051 E
50/50
18.57518.575
966621AG1-532 C
Adder
2.03647058823529431.731
940431AE2-027 C
Adder
17.9905882352941215.292
942002AE2-212 E
Adder
2.0588235294117651.75
316185AD1-033 C
50/50
1.8471.847
944581AF1-123 C
50/50
68.17868.178
941101AE2-104 C
Adder
4.9894117647058824.241
316088AB2-174 E
Adder
9.4352941176470598.02
923994AB2-040_E
Adder
8.8870588235294117.554
957481AF2-042 C
Adder
79.0188235294117667.166
939191AE1-149 C
Adder
15.69529411764705913.341
3143316POE
50/50
2.0282.028
901082W1-029 E
Adder
47.440.29
3151041BRUNSWICKG3
50/50
12.91612.916
3151021BRUNSWICKG1
50/50
12.91612.916
961611AG1-000B C
Adder
22.53529411764706219.155
316375AC2-012 C
50/50
2.0222.022
940541AE2-040 C
50/50
4.3194.319
940481AE2-033 C
50/50
24.26824.268
940482AE2-033 E
50/50
16.3616.36
923263AB1-132 E OP
Adder
8.7870588235294127.469
3152441Z1-086 ST
50/50
28.8528.85
3152431Z1-086 GT3
50/50
16.56616.566
3152421Z1-086 GT2
50/50
16.56616.566
316303AF2-085
50/50
6.5326.532
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.2837.283
CBM South 2LTFEXP_CBM-S2->PJM
CBM
125.379125.379
CPLELTFEXP_CPLE->PJM
CLTF
15.2815.28
TVALTFEXP_TVA->PJM
CLTF
7.6637.663
O66PJM->LTFIMP_O-066
CMTX_NF
35.08335.083
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.98737.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.12228.122
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8684.868
LAGNLTFEXP_LAGN->PJM
CLTF
9.7559.755
NYPJM->LTFIMP_NY
CLTF
2.5532.553
LGEELTFEXP_LGEE->PJM
CLTF
1.5241.524
WECLTFEXP_WEC->PJM
CLTF
0.7920.792
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5125.512
SIGELTFEXP_SIGE->PJM
CLTF
0.30.3

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.07 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3287.01
MW Contribution:2.65
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944631AF1-128 C
Adder
48.040.8
3150921YORKTN3
Adder
157.0388235294118133.483
933291AC2-141 C
80/20
44.42644.426
316305AF2-043 C
80/20
0.5050.505
3151101ELIZAR3
80/20
4.7154.715
316315AB2-025 C
80/20
0.5980.598
961951AG1-038 C
Adder
3.3341176470588242.834
957861AF2-080 C
Adder
10.3623529411764718.808
3138533PONTONDP
Adder
0.87294117647058820.742
316169AC1-164 GEN
Adder
44.9588235294117738.215
316349AD2-085 C
80/20
4.9434.943
3151091ELIZAR2
80/20
4.5754.575
316258AE1-075 C
80/20
0.5030.503
316023AB2-100 C2
80/20
1.3721.372
946281AF1-292 C
Adder
2.19294117647058861.864
926071AC1-086 C
Adder
29.4425.024
3151051BRUNSWICKS1
80/20
26.33426.334
927021AC1-189 C
Adder
11.4094117647058839.698
3151531CLOVER1
80/20
17.87817.878
964241AG1-285 C
Adder
17.89058823529411815.207
962561AG1-105 C
Adder
11.8176470588235310.045
943471AF1-018 C
Adder
7.9588235294117656.765
316083AB2-161 C
80/20
0.7870.787
316072AD1-144 C
80/20
0.4020.402
940641AE2-051 C
80/20
27.30727.307
316336AC2-165 C
Adder
13.69411764705882511.64
934611AD1-087 C
80/20
1.761.76
3150731STONECA
Adder
8.9505882352941187.608
935161AD1-151 C
Adder
21.46588235294117618.246
3151221GRAVEL6
80/20
3.4833.483
3151201GRAVEL4
80/20
3.4873.487
958161AF2-110 C
80/20
1.9761.976
316017AA1-139 ULT1
80/20
1.5751.575
938531AE1-072 C
80/20
25.56125.561
933981AD1-022 C
Adder
12.39411764705882410.535
3152411Z1-086 GT1
80/20
16.26716.267
3150851SPRUNCC
80/20
0.2220.222
3156116Z1-036WIND
80/20
0.9440.944
939411AE1-173 C
80/20
140.502140.502
3137643SOCKMAN
Adder
1.00.85
3151031BRUNSWICKG2
80/20
12.67612.676
937481AD2-202 C
80/20
0.5110.511
942001AE2-212 C
80/20
2.9732.973
3151161SURRY 1
80/20
33.88933.889
3150991CHESPKB
80/20
1.051.05
316321Z2-027 C
80/20
0.5270.527
943741AF1-042 C
Adder
3.01647058823529422.564
934501AD1-074 C
Adder
47.763529411764740.599
961671AG1-007 C
Adder
1.26588235294117671.076
934621AD1-088 C
80/20
13.42613.426
946301AF1-294 C
Adder
4.8470588235294124.12
942461AE2-259 C
Adder
12.70588235294117810.8
944641AF1-129 C
Adder
134.59058823529412114.402
316240AF1-291 C
Adder
2.86941176470588262.439
316381AD1-082 C
80/20
1.7951.795
316036AC1-147 C
80/20
0.5360.536
316018AA1-139 ULT2
80/20
1.5751.575
934521AD1-076 C
Adder
17.34705882352941214.745
934511AD1-075 C
Adder
11.94117647058823610.15
316263AC1-034 C
Adder
8.8741176470588247.543
959311AF2-222 C
Adder
23.07176470588235519.611
3150841SPRUNCB
80/20
12.34712.347
3150831SPRUNCA
80/20
12.34712.347
961941AG1-037 C
Adder
0.71058823529411760.604
941031AE2-094 C
80/20
62.11762.117
934331AD1-057 C
Adder
4.7623529411764714.048
934321AD1-056 C
Adder
8.5376470588235297.257
958211AF2-115 C
Adder
2.94705882352941152.505
3150601CHESTF5
Adder
76.7117647058823665.205
941591AE2-156 C
80/20
26.02126.021
3151081ELIZAR1
80/20
4.6564.656
316316AC1-027 C
80/20
0.460.46
944591AF1-124 C
80/20
66.45566.455
944601AF1-125 C
80/20
65.265.2
938771AE1-103 C
80/20
4.24.2
960081AF2-299 C
Adder
2.64941176470588242.252
944011AF1-069 C
80/20
20.29620.296
963041AG1-153 C
80/20
8.5888.588
3151541CLOVER2
80/20
17.71117.711
936261AD2-033 C
Adder
17.57529411764705814.939
961791AG1-021 C
Adder
2.35764705882352972.004
3150651CHESTF6
Adder
24.50588235294117520.83
916191Z1-068 C
80/20
0.0640.064
316294AC1-161 C
80/20
7.267.26
957871AF2-081 C
80/20
14.54714.547
936591AD2-074 C
Adder
5.7647058823529424.9
3151151S HAMPT1
80/20
2.1352.135
316313AB2-026 C
80/20
0.5480.548
962571AG1-106 C
Adder
3.80823529411764743.237
316274AC1-208 C
Adder
12.4023529411764710.542
3151311EDGECMA
Adder
20.74352941176470817.632
942341AE2-247 C
80/20
2.1432.143
316246AF1-032 C
80/20
0.4130.413
316388AE2-253 GEN
80/20
2.8622.862
966621AG1-532 C
Adder
1.9870588235294121.689
3150861SPRUNCD
80/20
0.2220.222
940431AE2-027 C
Adder
17.26588235294117614.676
3150981CHESPKA
80/20
0.6340.634
316185AD1-033 C
80/20
1.7941.794
944581AF1-123 C
80/20
66.2266.22
941101AE2-104 C
80/20
4.8434.843
316320Y1-086 C
80/20
0.3190.319
316405AF2-144 C
80/20
0.4280.428
957481AF2-042 C
80/20
77.49977.499
939191AE1-149 C
80/20
15.16215.162
957601AF2-054 C
Adder
2.37764705882352922.021
316365AB2-100 C1
80/20
1.3721.372
3151041BRUNSWICKG3
80/20
12.67612.676
3151021BRUNSWICKG1
80/20
12.67612.676
964791AG1-342 C
Adder
4.6788235294117653.977
961611AG1-000B C
Adder
21.72352941176470518.465
316236AE1-162 C
80/20
0.4930.493
3152331SURRY 2
80/20
34.47834.478
316375AC2-012 C
80/20
1.9631.963
313526AB2-022 C
80/20
0.5460.546
940541AE2-040 C
80/20
4.2084.208
940481AE2-033 C
80/20
23.64823.648
3152441Z1-086 ST
80/20
28.31628.316
3152431Z1-086 GT3
80/20
16.2616.26
3152421Z1-086 GT2
80/20
16.2616.26
316233AE1-074 C
80/20
3.7763.776
940551AE2-041 C
Adder
7.9588235294117656.765
3151211GRAVEL5
80/20
3.4433.443
943461AF1-017 C
80/20
1.9381.938
316311AC2-079 C
80/20
8.2428.242
3156056W1-029WIND
80/20
1.1231.123
316303AF2-085
80/20
6.3826.382
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1347.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.889122.889
CPLELTFEXP_CPLE->PJM
CLTF
14.96614.966
TVALTFEXP_TVA->PJM
CLTF
7.5327.532
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.6437.64
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.68227.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8064.806
LAGNLTFEXP_LAGN->PJM
CLTF
9.5879.587
NYPJM->LTFIMP_NY
CLTF
2.4692.469
LGEELTFEXP_LGEE->PJM
CLTF
1.5071.507
WECLTFEXP_WEC->PJM
CLTF
0.7840.784
SIGELTFEXP_SIGE->PJM
CLTF
0.2960.296

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.59 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3225.32
MW Contribution:3.2
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.29 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3436.04
MW Contribution:3.14
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
924814AB2-134 E
Adder
11.1823529411764729.505
942342AE2-247 E
Adder
2.6752941176470592.274
316036AC1-147 C
50/50
0.60.6
919152AA1-139 E1
50/50
6.7236.723
316018AA1-139 ULT2
50/50
1.781.78
920042AA2-088 E OP
Adder
13.60117647058823611.561
934521AD1-076 C
Adder
16.99176470588235314.443
934511AD1-075 C
Adder
11.6964705882352959.942
3145723EMPORIA
Adder
0.44705882352941180.38
923573AB1-173 E OP
Adder
3.50352941176470622.978
919692AA2-053 E OP
Adder
4.8294117647058834.105
961611AG1-000B C
Adder
17.5717647058823514.936
316236AE1-162 C
50/50
0.4750.475
3152331SURRY 2
50/50
52.22852.228
316375AC2-012 C
50/50
2.1982.198
313526AB2-022 C
50/50
0.6030.603
940541AE2-040 C
Adder
2.6435294117647062.247
940481AE2-033 C
Adder
15.09058823529411912.827
940482AE2-033 E
Adder
10.1729411764705898.647
923263AB1-132 E OP
Adder
6.6282352941176485.634
925612AC1-036 E
Adder
0.80823529411764720.687
924312AB2-078 E O1
Adder
1.3164705882352941.119
926274AC1-105 E
Adder
2.5482352941176472.166
939192AE1-149 E
Adder
4.0364705882352953.431
939312AE1-162 E
50/50
1.9371.937
3150991CHESPKB
50/50
1.1761.176
934065AD1-033 E
50/50
8.3718.371
937226AE2-253 E
50/50
9.6579.657
316321Z2-027 C
50/50
0.5770.577
940491AE2-034 C
50/50
1.6591.659
934501AD1-074 C
Adder
46.7858823529411839.768
924517AB2-100 E2
Adder
2.92235294117647062.484
957482AF2-042 E
Adder
39.0611764705882433.202
961671AG1-007 C
Adder
1.05647058823529430.898
934621AD1-088 C
Adder
9.7717647058823538.306
935172AD1-152 E
Adder
5.5847058823529414.747
926662AC1-147 E
50/50
2.1552.155
916192Z1-068 E
50/50
3.0983.098
957492AF2-043 E
50/50
2.2332.233
923852AB2-025 E
Adder
1.06941176470588250.909
939412AE1-173 E
50/50
88.25188.251
961942AG1-037 E
Adder
0.427058823529411770.363
961941AG1-037 C
Adder
0.640.544
941032AE2-094 E
50/50
22.37122.371
941031AE2-094 C
50/50
49.94849.948
934332AD1-057 E
Adder
1.96588235294117661.671
934331AD1-057 C
Adder
3.7752941176470593.209
934321AD1-056 C
Adder
6.7670588235294115.752
934322AD1-056 E
Adder
3.6705882352941183.12
927022AC1-189 E
Adder
4.86235294117647054.133
925595AC1-034 E
Adder
5.4105882352941184.599
936262AD2-033 E
Adder
7.8811764705882356.699
3144216WINCHST
50/50
0.1770.177
316349AD2-085 C
Adder
4.4694117647058833.799
935112AD1-144 E
50/50
1.4091.409
3151091ELIZAR2
50/50
5.1465.146
944582AF1-123 E
50/50
173.752173.752
944592AF1-124 E
50/50
174.381174.381
923832AB2-022 E
50/50
1.9881.988
938772AE1-103 E
50/50
5.6365.636
916042Z1-036 E
50/50
42.96342.963
960082AF2-299 E
Adder
1.27882352941176471.087
946281AF1-292 C
Adder
1.58823529411764721.35
926071AC1-086 C
Adder
22.77647058823529519.36
942341AE2-247 C
Adder
1.93764705882352951.647
943462AF1-017 E
Adder
2.86000000000000032.431
958162AF2-110 E
50/50
3.2233.223
316246AF1-032 C
50/50
0.4470.447
316388AE2-253 GEN
50/50
3.2483.248
919153AA1-139 E2
50/50
6.7236.723
934512AD1-075 E
Adder
5.95411764705882355.061
934502AD1-074 E
Adder
23.81647058823529420.244
924516AB2-100 E1
Adder
2.92235294117647062.484
918512AA1-065 E OP
Adder
7.1905882352941186.112
940642AE2-051 E
50/50
16.13516.135
966621AG1-532 C
Adder
1.43882352941176481.223
918532AA1-067 E
Adder
0.85764705882352940.729
924022AB2-043 E O1
Adder
5.1070588235294124.341
3147223TWITTYS
Adder
0.89647058823529410.762
959312AF2-222 E
Adder
10.3552941176470598.802
963042AG1-153 E
Adder
10.2835294117647068.741
927021AC1-189 C
Adder
9.768.296
964241AG1-285 C
Adder
12.75176470588235310.839
924152AB2-059 E OP
Adder
5.70470588235294154.849
962561AG1-105 C
Adder
8.5494117647058847.267
3150981CHESPKA
50/50
0.7090.709
316185AD1-033 C
50/50
2.0522.052
944581AF1-123 C
50/50
75.87875.878
941101AE2-104 C
50/50
4.9664.966
316320Y1-086 C
50/50
0.3530.353
316141AB2-099 E
Adder
0.320.272
316088AB2-174 E
Adder
6.877647058823535.846
923994AB2-040_E
Adder
6.5694117647058825.584
957481AF2-042 C
Adder
58.59176470588235549.803
961672AG1-007 E
Adder
0.59882352941176480.509
924322AB2-079 E O1
Adder
1.3164705882352941.119
943902AF1-058 E
Adder
1.21411764705882351.032
934576AD1-082 E
Adder
4.4847058823529413.812
916191Z1-068 C
50/50
0.0720.072
933292AC2-141 E
50/50
24.4824.48
316294AC1-161 C
50/50
9.3719.371
944602AF1-125 E
50/50
171.025171.025
3145506HICKORY
50/50
3.633.63
943612AF1-032 E
50/50
1.4511.451
957871AF2-081 C
50/50
16.44116.441
940492AE2-034 E
50/50
4.4344.434
934522AD1-076 E
Adder
8.667.361
943172AE2-346 E
Adder
0.76823529411764710.653
918492AA1-063AE OP
Adder
4.80941176470588254.088
962571AG1-106 C
Adder
2.94588235294117642.504
917332KELFORD E
Adder
2.01647058823529421.714
925122AB2-169 E
Adder
7.4694117647058836.349
316274AC1-208 C
Adder
10.168.636
917342Z2-044 E
Adder
0.65529411764705890.557
937482AD2-202 E
Adder
1.1129411764705880.946
3151311EDGECMA
Adder
16.76352941176470814.249
927226AC1-216 E
Adder
6.8258823529411765.802
962962AG1-145 E
Adder
1.36235294117647051.158
936666AD2-085 E
Adder
7.2929411764705886.199
941591AE2-156 C
50/50
29.1829.18
3151081ELIZAR1
50/50
5.2375.237
316316AC1-027 C
50/50
0.520.52
944591AF1-124 C
50/50
76.14876.148
944601AF1-125 C
50/50
74.70974.709
938771AE1-103 C
50/50
4.0814.081
3145413WATKINS
Adder
0.93058823529411770.791
960081AF2-299 C
Adder
1.91882352941176481.631
926072AC1-086 E
Adder
10.3658823529411768.811
944011AF1-069 C
50/50
16.3216.32
963041AG1-153 C
Adder
6.8564705882352955.828
957862AF2-080 E
Adder
3.9294117647058823.34
936261AD2-033 C
Adder
11.82117647058823610.048
962562AG1-105 E
Adder
5.74.845
932046AC2-012 E
50/50
21.31821.318
958161AF2-110 C
50/50
2.0262.026
316017AA1-139 ULT1
50/50
1.781.78
938531AE1-072 C
50/50
28.76728.767
3145393UNCAMP
Adder
8.367.106
315614AA2-178 C
50/50
2.2542.254
933981AD1-022 C
Adder
11.96352941176470710.169
900672V4-068 E
Adder
0.452941176470588240.385
924302AB2-077 E O1
Adder
1.3164705882352941.119
316160AE1-175 E
Adder
1.12470588235294120.956
3150921YORKTN3
50/50
162.48162.48
3145256KINGFORK
50/50
1.5181.518
925522AC1-027 E
50/50
2.0032.003
933291AC2-141 C
50/50
57.34757.347
926755AC1-161 E
50/50
24.4824.48
941102AE2-104 E
50/50
7.8957.895
316305AF2-043 C
50/50
0.5470.547
957872AF2-081 E
50/50
7.0467.046
962572AG1-106 E
Adder
1.28941176470588251.096
926214AC1-099 E
Adder
1.38941176470588231.181
932632AC2-084 E
Adder
3.71882352941176463.161
964242AG1-285 E
Adder
8.5011764705882367.226
924162AB2-060 E OP
Adder
4.1870588235294123.559
964792AG1-342 E
Adder
2.2623529411764711.923
925785AC1-054 E
Adder
3.63176470588235353.087
316263AC1-034 C
Adder
7.1729411764705896.097
959311AF2-222 C
Adder
15.45647058823529513.138
957832AF2-077 E
Adder
1.38000000000000011.173
943461AF1-017 C
Adder
1.75294117647058821.49
932596AC2-079 E
Adder
12.36705882352941210.512
316311AC2-079 C
Adder
7.586.443
938532AE1-072 E
50/50
14.99614.996
3146326AYDLETT TAP
50/50
2.2162.216
917122Z2-027 E
50/50
2.1312.131
3156056W1-029WIND
50/50
1.211.21
920692AA2-178 E
50/50
5.9125.912
966622AG1-532 E
Adder
0.95882352941176460.815
922923AB1-081 E OP
Adder
4.0270588235294123.423
316084AB2-161 E
Adder
5.6282352941176474.784
316072AD1-144 C
50/50
0.4210.421
3145946PLYMOUTH TP
Adder
0.451764705882352960.384
933982AD1-022 E
Adder
6.5129411764705885.536
940641AE2-051 C
50/50
24.20324.203
927146AC1-208 E
Adder
4.5117647058823533.835
934622AD1-088 E
Adder
4.70470588235294153.999
934612AD1-087 E
Adder
3.80117647058823543.231
927255AC1-221 E
Adder
3.5270588235294122.998
934012AD1-025 E
Adder
8.837647058823537.512
913392Y1-086 E
50/50
3.5213.521
3156116Z1-036WIND
50/50
0.9890.989
939411AE1-173 C
50/50
132.376132.376
3137643SOCKMAN
Adder
0.77882352941176480.662
919710AA2-057 E
Adder
4.43.74
3151101ELIZAR3
50/50
5.3035.303
946282AF1-292 E
Adder
1.05882352941176470.9
944012AF1-069 E
50/50
6.346.34
957861AF2-080 C
Adder
8.8647058823529427.535
917512Z2-088 E OP1
Adder
5.58588235294117654.748
939191AE1-149 C
Adder
8.8411764705882367.515
901082W1-029 E
50/50
49.64949.649
926206AC1-098 E
Adder
4.2070588235294123.576
964791AG1-342 C
Adder
3.39411764705882352.885
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.515.51
CBM South 2LTFEXP_CBM-S2->PJM
CBM
91.70491.704
CPLELTFEXP_CPLE->PJM
CLTF
11.56611.566
TVALTFEXP_TVA->PJM
CLTF
4.9264.926
O66PJM->LTFIMP_O-066
CMTX_NF
19.32919.329
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.74418.744
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.28317.283
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.712.71
LAGNLTFEXP_LAGN->PJM
CLTF
6.3446.344
NYPJM->LTFIMP_NY
CLTF
1.4491.449
LGEELTFEXP_LGEE->PJM
CLTF
0.760.76
WECLTFEXP_WEC->PJM
CLTF
0.3980.398
G-007PJM->LTFIMP_G-007
CMTX_NF
3.0313.031
SIGELTFEXP_SIGE->PJM
CLTF
0.160.16

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3221.97
MW Contribution:3.43
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
3151091ELIZAR2
50/50
5.1875.187
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
3151081ELIZAR1
50/50
5.2795.279
316316AC1-027 C
50/50
0.5240.524
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961942AG1-037 E
Adder
0.43882352941176470.373
961941AG1-037 C
Adder
0.65882352941176480.56
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934332AD1-057 E
Adder
2.05294117647058851.745
934331AD1-057 C
Adder
3.94352941176470573.352
934321AD1-056 C
Adder
7.0682352941176476.008
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
919152AA1-139 E1
50/50
6.7746.774
316018AA1-139 ULT2
50/50
1.7931.793
920042AA2-088 E OP
Adder
14.01647058823529311.914
934521AD1-076 C
Adder
17.32941176470588514.73
934511AD1-075 C
Adder
11.92941176470588310.14
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
933291AC2-141 C
50/50
57.45157.451
926755AC1-161 E
50/50
24.52424.524
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
962572AG1-106 E
Adder
1.36823529411764721.163
926214AC1-099 E
Adder
1.43882352941176481.223
932632AC2-084 E
Adder
3.8494117647058823.272
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
934322AD1-056 E
Adder
3.83411764705882343.259
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
3151101ELIZAR3
50/50
5.3455.345
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
957861AF2-080 C
Adder
9.1035294117647067.738
917512Z2-088 E OP1
Adder
5.7423529411764714.881
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
962571AG1-106 C
Adder
3.1282352941176472.659
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
944591AF1-124 C
50/50
76.6476.64
944601AF1-125 C
50/50
75.19275.192
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
957862AF2-080 E
Adder
4.0352941176470593.43
936261AD2-033 C
Adder
10.6341176470588249.039
962562AG1-105 E
Adder
5.75647058823529444.893
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
3152331SURRY 2
50/50
52.46452.464
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940481AE2-033 C
Adder
17.1423529411764714.571
940482AE2-033 E
Adder
11.5564705882352949.823
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3221.97
MW Contribution:3.43
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
3151091ELIZAR2
50/50
5.1875.187
944582AF1-123 E
50/50
174.875174.875
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
919152AA1-139 E1
50/50
6.7746.774
316018AA1-139 ULT2
50/50
1.7931.793
920042AA2-088 E OP
Adder
14.01647058823529311.914
934521AD1-076 C
Adder
17.32941176470588514.73
934511AD1-075 C
Adder
11.92941176470588310.14
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
935162AD1-151 E
Adder
9.3141176470588247.917
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
933291AC2-141 C
50/50
57.45157.451
926755AC1-161 E
50/50
24.52424.524
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
962572AG1-106 E
Adder
1.36823529411764721.163
926214AC1-099 E
Adder
1.43882352941176481.223
932632AC2-084 E
Adder
3.8494117647058823.272
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961942AG1-037 E
Adder
0.43882352941176470.373
961941AG1-037 C
Adder
0.65882352941176480.56
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934332AD1-057 E
Adder
2.05294117647058851.745
934331AD1-057 C
Adder
3.94352941176470573.352
934321AD1-056 C
Adder
7.0682352941176476.008
934322AD1-056 E
Adder
3.83411764705882343.259
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
3151101ELIZAR3
50/50
5.3455.345
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
957861AF2-080 C
Adder
9.1035294117647067.738
917512Z2-088 E OP1
Adder
5.7423529411764714.881
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
962571AG1-106 C
Adder
3.1282352941176472.659
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
3151081ELIZAR1
50/50
5.2795.279
316316AC1-027 C
50/50
0.5240.524
944591AF1-124 C
50/50
76.6476.64
944601AF1-125 C
50/50
75.19275.192
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
957862AF2-080 E
Adder
4.0352941176470593.43
936261AD2-033 C
Adder
10.6341176470588249.039
962562AG1-105 E
Adder
5.75647058823529444.893
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
3152331SURRY 2
50/50
52.46452.464
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940481AE2-033 C
Adder
17.1423529411764714.571
940482AE2-033 E
Adder
11.5564705882352949.823
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
957832AF2-077 E
Adder
1.4235294117647061.21
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3221.81
MW Contribution:3.43
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.28 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3435.8
MW Contribution:3.4
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
3151091ELIZAR2
50/50
5.1875.187
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
3151081ELIZAR1
50/50
5.2795.279
316316AC1-027 C
50/50
0.5240.524
944591AF1-124 C
50/50
76.6476.64
944601AF1-125 C
50/50
75.19275.192
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
957862AF2-080 E
Adder
4.0352941176470593.43
936261AD2-033 C
Adder
10.6341176470588249.039
962562AG1-105 E
Adder
5.75647058823529444.893
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
3152331SURRY 2
50/50
52.46452.464
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940481AE2-033 C
Adder
17.1423529411764714.571
940482AE2-033 E
Adder
11.5564705882352949.823
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961942AG1-037 E
Adder
0.43882352941176470.373
961941AG1-037 C
Adder
0.65882352941176480.56
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934332AD1-057 E
Adder
2.05294117647058851.745
934331AD1-057 C
Adder
3.94352941176470573.352
934321AD1-056 C
Adder
7.0682352941176476.008
934322AD1-056 E
Adder
3.83411764705882343.259
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
919152AA1-139 E1
50/50
6.7746.774
316018AA1-139 ULT2
50/50
1.7931.793
920042AA2-088 E OP
Adder
14.01647058823529311.914
934521AD1-076 C
Adder
17.32941176470588514.73
934511AD1-075 C
Adder
11.92941176470588310.14
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
933291AC2-141 C
50/50
57.45157.451
926755AC1-161 E
50/50
24.52424.524
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
962572AG1-106 E
Adder
1.36823529411764721.163
926214AC1-099 E
Adder
1.43882352941176481.223
932632AC2-084 E
Adder
3.8494117647058823.272
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
3151101ELIZAR3
50/50
5.3455.345
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
957861AF2-080 C
Adder
9.1035294117647067.738
917512Z2-088 E OP1
Adder
5.7423529411764714.881
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
962571AG1-106 C
Adder
3.1282352941176472.659
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161

Details for AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 246T247_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.02 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1021.04
MW Contribution:7.58
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940481AE2-033 C
50/50
64.7264.72
940482AE2-033 E
50/50
43.63243.632
923263AB1-132 E OP
50/50
13.58313.583
3151411GASTONB
50/50
6.7836.783
316181AB2-040 GEN
50/50
2.6442.644
316174AB2-169_C
50/50
1.0821.082
3156063AA2-053SOLA
50/50
2.4332.433
3151281ROARAP4
50/50
2.1872.187
3156011CONETOE2SOL
50/50
1.4931.493
940491AE2-034 C
50/50
0.8920.892
934501AD1-074 C
50/50
31.71231.712
924517AB2-100 E2
50/50
8.748.74
3156021HOLLOMANSOL
50/50
2.4892.489
3156073AA1-063SOLA
50/50
1.9971.997
3151371ROSEMS1
50/50
2.6872.687
961671AG1-007 C
50/50
1.1341.134
316359AB2-059 C OP
50/50
2.062.06
961942AG1-037 E
50/50
0.440.44
943171AE2-346 C
50/50
0.2930.293
961941AG1-037 C
50/50
0.660.66
3151391GASTONA
50/50
6.7836.783
3151381ROSEMG2
50/50
2.0322.032
934332AD1-057 E
50/50
3.0163.016
934331AD1-057 C
50/50
5.7925.792
934321AD1-056 C
50/50
10.38210.382
934322AD1-056 E
50/50
5.6325.632
927022AC1-189 E
50/50
4.9224.922
925595AC1-034 E
50/50
6.1616.161
934512AD1-075 E
50/50
4.0364.036
934502AD1-074 E
50/50
16.14316.143
924516AB2-100 E1
50/50
8.748.74
316023AB2-100 C2
50/50
2.92.9
960082AF2-299 E
50/50
3.0313.031
946281AF1-292 C
50/50
3.7633.763
926071AC1-086 C
50/50
46.67446.674
316317KELFORD C
50/50
0.4920.492
927021AC1-189 C
50/50
9.889.88
924152AB2-059 E OP
50/50
6.4956.495
3156083AA2-088SOLA
50/50
1.0541.054
316141AB2-099 E
50/50
0.330.33
316088AB2-174 E
50/50
14.27714.277
313506AB1-173 C OP
50/50
2.3482.348
923994AB2-040_E
50/50
12.80412.804
3151361ROSEMG1
50/50
4.3384.338
316005AA1-067 C
50/50
0.3090.309
961672AG1-007 E
50/50
0.6430.643
940492AE2-034 E
50/50
2.3862.386
934522AD1-076 E
50/50
5.875.87
943172AE2-346 E
50/50
0.7920.792
918492AA1-063AE OP
50/50
5.7985.798
962571AG1-106 C
50/50
6.0376.037
917332KELFORD E
50/50
2.262.26
925122AB2-169 E
50/50
5.9415.941
932631AC2-084 C
50/50
1.4091.409
316274AC1-208 C
50/50
12.9912.99
917342Z2-044 E
50/50
0.7670.767
3151311EDGECMA
50/50
19.40219.402
3145413WATKINS
Adder
0.46352941176470590.394
960081AF2-299 C
50/50
4.5464.546
315614AA2-178 C
50/50
1.2131.213
933981AD1-022 C
50/50
9.1829.182
900672V4-068 E
50/50
0.4080.408
3151261ROARAP2
50/50
2.3112.311
3147043LAWRENC
50/50
0.5750.575
316087AB2-174 C
50/50
2.5792.579
962572AG1-106 E
50/50
2.6412.641
926214AC1-099 E
50/50
1.6921.692
932632AC2-084 E
50/50
4.5274.527
920042AA2-088 E OP
50/50
10.51910.519
934521AD1-076 C
50/50
11.51711.517
934511AD1-075 C
50/50
7.9287.928
926072AC1-086 E
50/50
21.24321.243
957862AF2-080 E
50/50
3.9783.978
3145723EMPORIA
50/50
1.0091.009
316011AB1-132 C OP
50/50
5.1795.179
923573AB1-173 E OP
50/50
6.8296.829
919692AA2-053 E OP
50/50
6.826.82
925785AC1-054 E
50/50
3.6613.661
316263AC1-034 C
50/50
8.1678.167
920692AA2-178 E
50/50
3.1813.181
966622AG1-532 E
50/50
2.2732.273
922923AB1-081 E OP
50/50
4.5854.585
3145946PLYMOUTH TP
50/50
0.2950.295
933982AD1-022 E
50/50
4.9994.999
927146AC1-208 E
50/50
5.7685.768
316049AB1-081 C OP
50/50
1.7481.748
3152921DOMTR78
50/50
1.3421.342
316140AB2-099 C
50/50
0.1260.126
3137643SOCKMAN
50/50
1.3241.324
316212AC1-099 C
50/50
0.4430.443
919710AA2-057 E
50/50
5.3045.304
316319Z2-044 C
50/50
0.2710.271
946282AF1-292 E
50/50
2.5092.509
316129AC1-054 C
50/50
1.2981.298
957861AF2-080 C
50/50
8.9748.974
917512Z2-088 E OP1
50/50
5.8425.842
918512AA1-065 E OP
50/50
7.487.48
966621AG1-532 C
50/50
3.413.41
918532AA1-067 E
50/50
0.8120.812
316365AB2-100 C1
50/50
2.92.9
316318V4-068 C
50/50
0.0920.092
316210AC1-098 C
50/50
1.3231.323
926206AC1-098 E
50/50
5.1215.121
316327AA2-057 C
50/50
1.741.74
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5332.533
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.08239.082
CPLELTFEXP_CPLE->PJM
CLTF
5.3135.313
TVALTFEXP_TVA->PJM
CLTF
2.2652.265
O66PJM->LTFIMP_O-066
CMTX_NF
5.1955.195
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.32112.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4748.474
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5081.508
LAGNLTFEXP_LAGN->PJM
CLTF
2.9042.904
NYPJM->LTFIMP_NY
CLTF
0.3730.373
LGEELTFEXP_LGEE->PJM
CLTF
0.470.47
WECLTFEXP_WEC->PJM
CLTF
0.2520.252
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8170.817
SIGELTFEXP_SIGE->PJM
CLTF
0.0920.092

Details for AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.42 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:742.63
MW Contribution:4.4
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.42 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:762.95
MW Contribution:4.41
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316049AB1-081 C OP
80/20
1.4941.494
3151611KERR 4
80/20
0.8620.862
316087AB2-174 C
80/20
2.4642.464
313527AB2-043 C
80/20
0.3630.363
3151591KERR 2
80/20
0.8620.862
316129AC1-054 C
80/20
1.341.34
957861AF2-080 C
80/20
6.8566.856
316131AB2-060 C
80/20
1.0341.034
3138533PONTONDP
80/20
0.3360.336
316118AC1-105 C
80/20
0.4840.484
316023AB2-100 C2
80/20
2.7732.773
946281AF1-292 C
80/20
3.6413.641
926071AC1-086 C
80/20
42.49342.493
316317KELFORD C
80/20
0.370.37
927021AC1-189 C
80/20
7.5497.549
3151531CLOVER1
80/20
5.8195.819
964241AG1-285 C
80/20
7.2257.225
316034AC1-036 C
80/20
0.1240.124
962561AG1-105 C
80/20
5.2875.287
3151151S HAMPT1
80/20
0.9570.957
962571AG1-106 C
80/20
5.4965.496
932631AC2-084 C
80/20
1.171.17
316274AC1-208 C
80/20
11.22611.226
3151311EDGECMA
80/20
16.55516.555
3151601KERR 3
80/20
0.8620.862
3151581KERR 1
80/20
0.3080.308
3152661PLYWOOD A
80/20
0.6390.639
933981AD1-022 C
80/20
5.6875.687
3151261ROARAP2
80/20
2.1232.123
3147043LAWRENC
80/20
0.5790.579
3151621KERR 5
80/20
0.8620.862
3152921DOMTR78
80/20
0.8540.854
316140AB2-099 C
80/20
0.0920.092
3137643SOCKMAN
80/20
1.2371.237
316212AC1-099 C
80/20
0.3680.368
316319Z2-044 C
80/20
0.2310.231
3151641KERR 7
80/20
0.8620.862
934501AD1-074 C
80/20
19.36119.361
3156021HOLLOMANSOL
80/20
1.5861.586
3156073AA1-063SOLA
80/20
1.8141.814
3151371ROSEMS1
80/20
2.4382.438
961671AG1-007 C
80/20
0.9120.912
934621AD1-088 C
80/20
4.4044.404
316359AB2-059 C OP
80/20
1.7611.761
946301AF1-294 C
80/20
1.8661.866
934521AD1-076 C
80/20
7.0327.032
934511AD1-075 C
80/20
4.844.84
316011AB1-132 C OP
80/20
4.7154.715
316263AC1-034 C
80/20
6.9816.981
959311AF2-222 C
80/20
8.6368.636
943171AE2-346 C
80/20
0.2140.214
961941AG1-037 C
80/20
0.4820.482
3151391GASTONA
80/20
6.1766.176
3151381ROSEMG2
80/20
1.8431.843
934331AD1-057 C
80/20
5.1335.133
934321AD1-056 C
80/20
9.2019.201
958211AF2-115 C
80/20
1.1351.135
960081AF2-299 C
80/20
4.3984.398
3151631KERR 6
80/20
0.8620.862
936261AD2-033 C
80/20
8.0298.029
961791AG1-021 C
80/20
0.9080.908
3144293JTRSVLE
80/20
0.2090.209
966621AG1-532 C
80/20
3.2993.299
3156083AA2-088SOLA
80/20
0.9350.935
313506AB1-173 C OP
80/20
2.2292.229
3151361ROSEMG1
80/20
3.9363.936
316005AA1-067 C
80/20
0.2210.221
957481AF2-042 C
80/20
24.31224.312
316365AB2-100 C1
80/20
2.7732.773
316318V4-068 C
80/20
0.0750.075
316210AC1-098 C
80/20
1.0991.099
316327AA2-057 C
80/20
1.4891.489
316239AB2-077 C O1
80/20
0.2290.229
964791AG1-342 C
80/20
2.0352.035
940481AE2-033 C
80/20
63.40763.407
3151411GASTONB
80/20
6.1766.176
316181AB2-040 GEN
80/20
2.5112.511
316174AB2-169_C
80/20
0.7190.719
3156063AA2-053SOLA
80/20
2.1582.158
3151281ROARAP4
80/20
2.0092.009
3156011CONETOE2SOL
80/20
1.1751.175
316238AB2-078 C O1
80/20
0.2290.229
316237AB2-079 C O1
80/20
0.2290.229
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1882.188
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.15434.154
CPLELTFEXP_CPLE->PJM
CLTF
4.5894.589
TVALTFEXP_TVA->PJM
CLTF
2.0182.018
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.20711.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.5767.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.3611.361
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
NYPJM->LTFIMP_NY
CLTF
0.3660.366
LGEELTFEXP_LGEE->PJM
CLTF
0.4310.431
WECLTFEXP_WEC->PJM
CLTF
0.2290.229
SIGELTFEXP_SIGE->PJM
CLTF
0.0840.084

Details for AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.28 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:734.84
MW Contribution:4.52
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.5 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:797.42
MW Contribution:4.57
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316049AB1-081 C OP
80/20
1.7111.711
3151611KERR 4
80/20
0.6570.657
940491AE2-034 C
80/20
0.7380.738
934501AD1-074 C
80/20
28.03528.035
3156021HOLLOMANSOL
80/20
2.3832.383
316087AB2-174 C
80/20
2.5592.559
313527AB2-043 C
80/20
0.2330.233
3151591KERR 2
80/20
0.6570.657
943171AE2-346 C
80/20
0.2840.284
961941AG1-037 C
80/20
0.6390.639
3151391GASTONA
80/20
6.7066.706
3151381ROSEMG2
80/20
2.0072.007
934331AD1-057 C
80/20
5.7015.701
934321AD1-056 C
80/20
10.21910.219
316129AC1-054 C
80/20
1.2821.282
957861AF2-080 C
80/20
8.6598.659
316131AB2-060 C
80/20
0.660.66
316023AB2-100 C2
80/20
2.8852.885
946281AF1-292 C
80/20
3.743.74
926071AC1-086 C
80/20
46.14346.143
316317KELFORD C
80/20
0.4770.477
927021AC1-189 C
80/20
9.5339.533
962561AG1-105 C
80/20
3.0443.044
3151151S HAMPT1
80/20
1.0421.042
962571AG1-106 C
80/20
5.9685.968
932631AC2-084 C
80/20
1.3771.377
316274AC1-208 C
80/20
12.74212.742
3151311EDGECMA
80/20
18.98318.983
3151601KERR 3
80/20
0.6570.657
3151581KERR 1
80/20
0.2350.235
315614AA2-178 C
80/20
1.0031.003
933981AD1-022 C
80/20
8.3438.343
3151261ROARAP2
80/20
2.2822.282
3147043LAWRENC
80/20
0.5710.571
3151621KERR 5
80/20
0.6570.657
3156116Z1-036WIND
80/20
0.2550.255
3152921DOMTR78
80/20
1.2111.211
316140AB2-099 C
80/20
0.1220.122
3137643SOCKMAN
80/20
1.311.31
316212AC1-099 C
80/20
0.4330.433
316319Z2-044 C
80/20
0.2650.265
3151641KERR 7
80/20
0.6570.657
3156073AA1-063SOLA
80/20
1.9741.974
3151371ROSEMS1
80/20
2.6552.655
961671AG1-007 C
80/20
1.1011.101
316359AB2-059 C OP
80/20
2.0162.016
934521AD1-076 C
80/20
10.18210.182
934511AD1-075 C
80/20
7.0097.009
316011AB1-132 C OP
80/20
5.125.12
316263AC1-034 C
80/20
7.9927.992
938771AE1-103 C
80/20
1.2911.291
960081AF2-299 C
80/20
4.5194.519
3151631KERR 6
80/20
0.6570.657
936261AD2-033 C
80/20
4.7924.792
966621AG1-532 C
80/20
3.3893.389
3156083AA2-088SOLA
80/20
1.0451.045
313506AB1-173 C OP
80/20
2.3282.328
3151361ROSEMG1
80/20
4.2874.287
316005AA1-067 C
80/20
0.2960.296
316365AB2-100 C1
80/20
2.8852.885
316318V4-068 C
80/20
0.090.09
316210AC1-098 C
80/20
1.2931.293
316327AA2-057 C
80/20
1.7051.705
316239AB2-077 C O1
80/20
0.1480.148
964791AG1-342 C
80/20
1.141.14
940481AE2-033 C
80/20
64.61764.617
3151411GASTONB
80/20
6.7066.706
316181AB2-040 GEN
80/20
2.6222.622
316174AB2-169_C
80/20
0.9980.998
3156063AA2-053SOLA
80/20
2.3942.394
3151281ROARAP4
80/20
2.1592.159
3156011CONETOE2SOL
80/20
1.4461.446
316238AB2-078 C O1
80/20
0.1480.148
316237AB2-079 C O1
80/20
0.1480.148
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4622.462
CBM South 2LTFEXP_CBM-S2->PJM
CBM
38.00838.008
CPLELTFEXP_CPLE->PJM
CLTF
5.1655.165
TVALTFEXP_TVA->PJM
CLTF
2.2042.204
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.98411.984
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.2438.243
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4671.467
LAGNLTFEXP_LAGN->PJM
CLTF
2.8252.825
NYPJM->LTFIMP_NY
CLTF
0.3630.363
LGEELTFEXP_LGEE->PJM
CLTF
0.4570.457
WECLTFEXP_WEC->PJM
CLTF
0.2450.245
SIGELTFEXP_SIGE->PJM
CLTF
0.090.09
CONTINGENCY 'DVP_P7-1: LN 2058-2181_SRT-A'
 OPEN BRANCH FROM BUS 304222 TO BUS 313845 CKT 1   /*6ROCKYMT230T 230.0 - 6HATHAWAY    230.0
 OPEN BRANCH FROM BUS 304226 TO BUS 314591 CKT 1   /*6PA-RMOUNT#4 230.0 - 6NASH        230.0
 OPEN BRANCH FROM BUS 313844 TO BUS 313845 CKT 2   /*3HATHAWAY    115.0 - 6HATHAWAY    230.0
 OPEN BRANCH FROM BUS 313845 TO BUS 314591 CKT 1   /*6HATHAWAY    230.0 - 6NASH        230.0
 OPEN BUS 304226                                   /*6PA-RMOUNT#4 230.0
 OPEN BUS 314591                                   /*6NASH        230.0
END
CONTINGENCY 'DVP_P1-2: LN 556_SRT-S-3'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 217_SRT-A'
 OPEN BRANCH FROM BUS 314225 TO BUS 314227 CKT 1   /*6CHARCTY     230.0 - 6LAKESIDE    230.0
 OPEN BRANCH FROM BUS 314225 TO BUS 314260 CKT 1   /*6CHARCTY     230.0 - 6VARINA      230.0
 OPEN BRANCH FROM BUS 314260 TO BUS 314287 CKT 1   /*6VARINA      230.0 - 6CHESTF B    230.0
 OPEN BUS 314225                                   /*6CHARCTY     230.0
 OPEN BUS 314260                                   /*6VARINA      230.0
END
CONTINGENCY 'DVP_P4-2: 246T247_SRT-A'
 OPEN BRANCH FROM BUS 313713 TO BUS 314648 CKT 1   /*6SWAMP       230.0 - 6SUNBURY     230.0
 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1   /*6SUFFOLK     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314537 TO BUS 314648 CKT 1   /*6SUFFOLK     230.0 - 6SUNBURY     230.0
 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1   /*6EARLEYS     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1   /*6NUCO TP     230.0 - 6NUCOR       230.0
 OPEN BUS 314575                                   /*6NUCO TP     230.0
 OPEN BUS 314590                                   /*6NUCOR       230.0
 OPEN BUS 314648                                   /*6SUNBURY     230.0
END
CONTINGENCY 'DVP_P4-2: 24642_SRT-A'
 OPEN BRANCH FROM BUS 314536 TO BUS 314537 CKT 3   /*3SUFFOLK     115.0 - 6SUFFOLK     230.0
 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1   /*6SUFFOLK     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314537 TO BUS 314928 CKT 2   /*6SUFFOLK     230.0 - 8SUFFOLK     500.0
 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1   /*6EARLEYS     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1   /*6NUCO TP     230.0 - 6NUCOR       230.0
 OPEN BUS 314575                                   /*6NUCO TP     230.0
 OPEN BUS 314590                                   /*6NUCOR       230.0
END
CONTINGENCY 'DVP_P4-2: 24662_SRT-A'
 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1   /*6SUFFOLK     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314568 TO BUS 314569 CKT 1   /*3EARLEYS     115.0 - 6EARLEYS     230.0
 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1   /*6EARLEYS     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1   /*6NUCO TP     230.0 - 6NUCOR       230.0
 OPEN BUS 314575                                   /*6NUCO TP     230.0
 OPEN BUS 314590                                   /*6NUCOR       230.0
END
CONTINGENCY 'DVP_P1-2: LN 2092_SRT-A'
 OPEN BRANCH FROM BUS 313714 TO BUS 313885 CKT 1   /*6PEMBROKE    230.0 - 6WALBMRL     230.0
 OPEN BRANCH FROM BUS 313885 TO BUS 314662 CKT 1   /*6WALBMRL     230.0 - 6S HERTFORD  230.0
 OPEN BRANCH FROM BUS 314651 TO BUS 314662 CKT 1   /*6WINFALL     230.0 - 6S HERTFORD  230.0
 OPEN BUS 313885                                   /*6WALBMRL     230.0
 OPEN BUS 314662                                   /*6S HERTFORD  230.0
END
CONTINGENCY 'DVP_P1-2: LN 2131_SRT-A'
 OPEN BRANCH FROM BUS 313015 TO BUS 313714 CKT 1   /*6CHOWAN      230.0 - 6PEMBROKE    230.0
 OPEN BRANCH FROM BUS 313015 TO BUS 314637 CKT 1   /*6CHOWAN      230.0 - 6EDENTON     230.0
 OPEN BRANCH FROM BUS 314203 TO BUS 314637 CKT 1   /*6MACKEYS     230.0 - 6EDENTON     230.0
 OPEN BUS 313015                                   /*6CHOWAN      230.0
 OPEN BUS 314637                                   /*6EDENTON     230.0
END
CONTINGENCY 'DVP_P4-2: H2T557_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 511T556_SRT-S-1'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 246_SRT-A'
 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1   /*6SUFFOLK     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1   /*6EARLEYS     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1   /*6NUCO TP     230.0 - 6NUCOR       230.0
 OPEN BUS 314575                                   /*6NUCO TP     230.0
 OPEN BUS 314590                                   /*6NUCOR       230.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A'
 OPEN BRANCH FROM BUS 314218 TO BUS 314196 CKT 1   /*6ELMONT      230.0 - 6LADYSMITH   230.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1   /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T567_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1   /*6CHCKAHM     230.0 - 8CHCKAHM     500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
314554 to 304223 ckt 1
314677 to 314747 ckt 1
314282 to 314285 ckt 1
314285 to 314316 ckt 1
314287 to 314276 ckt 1
314563 to 940480 ckt 1
314569 to 314575 ckt 1
314218 to 314908 ckt 1
314692 to 314677 ckt 1
314575 to 314537 ckt 1
314331 to 314263 ckt 1
314435 to 314282 ckt 1
314902 to 314914 ckt 1
314914 to 314322 ckt 1
314914 to 314918 ckt 1
314924 to 314903 ckt 1
940480 to 314435 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC100.89 %984.18B992.941.39
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 246_SRT-A
SingleAC108.46 %678.68B736.134.57
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A
SingleAC104.8 %678.68B711.274.31
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Base Case
SingleAC102.72 %678.68A697.114.35
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC113.38 %3940.0C4467.24.16
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.8 %3220.44B3342.682.48
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC104.31 %3637.0C3793.692.46
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC111.92 %4070.2B4555.562.9
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC111.48 %5011.0C5586.284.83
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC101.04 %4070.2B4112.52.42
GD1DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: 545T552_SRT-S
BreakerAC107.93 %3940.0C4252.572.6
GD1DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC100.32 %3220.44B3230.791.49
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC119.82 %3220.44B3858.592.75
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC117.79 %3940.0C4641.114.62
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC111.38 %3220.44B3586.781.46
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
SingleAC111.09 %3220.44B3577.611.53
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC110.41 %3940.0C4350.172.54
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H1T594_SRT-S
BreakerAC106.75 %3940.0C4205.812.43
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC116.97 %3220.44B3767.031.72
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC114.22 %3220.44B3678.491.95
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC111.99 %3940.0C4412.362.99
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC121.18 %3220.44B3902.621.67
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC120.07 %3220.44B3866.791.91
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC117.55 %3940.0C4631.322.94

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.89 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:992.94
MW Contribution:1.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943171AE2-346 C
80/20
0.1050.105
961941AG1-037 C
80/20
0.2370.237
3151391GASTONA
80/20
2.0712.071
934321AD1-056 C
80/20
3.7443.744
934331AD1-057 C
80/20
2.0892.089
958211AF2-115 C
Adder
0.80.68
316365AB2-100 C1
80/20
0.7990.799
3156083AA2-088SOLA
80/20
0.4670.467
316003AC1-222 C
80/20
0.4260.426
957481AF2-042 C
80/20
26.38726.387
934501AD1-074 C
80/20
13.23613.236
961671AG1-007 C
80/20
0.4820.482
940491AE2-034 C
80/20
0.4170.417
316359AB2-059 C OP
80/20
0.8920.892
316283AC2-100 C
80/20
0.510.51
946301AF1-294 C
Adder
1.3164705882352941.119
934621AD1-088 C
80/20
4.424.42
942001AE2-212 C
Adder
-3.9329411764705884-3.343
3151531CLOVER1
80/20
6.056.05
941031AE2-094 C
80/20
22.06822.068
316005AA1-067 C
80/20
0.1280.128
316210AC1-098 C
80/20
0.50.5
316318V4-068 C
80/20
0.0370.037
313506AB1-173 C OP
80/20
0.7570.757
966621AG1-532 C
80/20
1.041.04
3151601KERR 3
80/20
0.5540.554
3151581KERR 1
80/20
0.1980.198
935171AD1-152 C
80/20
0.620.62
3151021BRUNSWICKG1
80/20
4.4774.477
3151041BRUNSWICKG3
80/20
4.4774.477
316140AB2-099 C
80/20
0.0450.045
3152921DOMTR78
80/20
0.5570.557
316319Z2-044 C
80/20
0.1130.113
3151641KERR 7
80/20
0.5540.554
313527AB2-043 C
80/20
0.2380.238
927021AC1-189 C
80/20
4.1534.153
926071AC1-086 C
80/20
14.30114.301
946281AF1-292 C
80/20
1.1471.147
964241AG1-285 C
80/20
5.5515.551
962561AG1-105 C
80/20
4.0224.022
316034AC1-036 C
80/20
0.0950.095
316118AC1-105 C
80/20
0.4080.408
315614AA2-178 C
80/20
0.5670.567
3151411GASTONB
80/20
2.0712.071
316181AB2-040 GEN
80/20
0.8530.853
3147043LAWRENC
80/20
0.2030.203
940481AE2-033 C
80/20
16.46516.465
940541AE2-040 C
80/20
2.9992.999
3152441Z1-086 ST
80/20
10.00810.008
3151261ROARAP2
80/20
0.8190.819
3152411Z1-086 GT1
80/20
5.755.75
3152421Z1-086 GT2
80/20
5.7485.748
933981AD1-022 C
80/20
3.5783.578
316174AB2-169_C
80/20
0.4490.449
3156063AA2-053SOLA
80/20
0.860.86
3151281ROARAP4
80/20
0.7750.775
316049AB1-081 C OP
80/20
0.7570.757
316238AB2-078 C O1
80/20
0.1510.151
3156011CONETOE2SOL
80/20
0.6290.629
3151611KERR 4
80/20
0.5540.554
3151621KERR 5
80/20
0.5540.554
316237AB2-079 C O1
80/20
0.1510.151
316222AC1-221 C
80/20
0.6320.632
934611AD1-087 C
80/20
0.5960.596
3152431Z1-086 GT3
80/20
5.7485.748
940641AE2-051 C
80/20
9.0359.035
932631AC2-084 C
80/20
0.5330.533
316274AC1-208 C
80/20
4.9624.962
962571AG1-106 C
80/20
1.851.85
3151311EDGECMA
80/20
8.3398.339
3152661PLYWOOD A
80/20
0.5410.541
3151381ROSEMG2
80/20
0.6340.634
960081AF2-299 C
80/20
1.3861.386
936261AD2-033 C
80/20
5.4245.424
316248AF1-058 C
80/20
0.140.14
961791AG1-021 C
Adder
0.640.544
938771AE1-103 C
Adder
0.96705882352941170.822
963041AG1-153 C
80/20
3.0443.044
3151051BRUNSWICKS1
80/20
9.3029.302
944011AF1-069 C
80/20
7.217.21
3151361ROSEMG1
80/20
1.3551.355
316327AA2-057 C
80/20
0.7010.701
3151151S HAMPT1
80/20
0.570.57
316239AB2-077 C O1
80/20
0.1510.151
964791AG1-342 C
80/20
1.5971.597
316317KELFORD C
80/20
0.1760.176
957861AF2-080 C
80/20
3.7723.772
316023AB2-100 C2
80/20
0.7990.799
316129AC1-054 C
80/20
0.6480.648
3151631KERR 6
80/20
0.5540.554
316315AB2-025 C
80/20
0.4250.425
316131AB2-060 C
80/20
0.680.68
3138533PONTONDP
Adder
0.237647058823529430.202
3151541CLOVER2
80/20
5.9935.993
3156021HOLLOMANSOL
80/20
0.830.83
316011AB1-132 C OP
80/20
1.5811.581
3151371ROSEMS1
80/20
0.8390.839
3137643SOCKMAN
80/20
0.4490.449
939411AE1-173 C
80/20
41.75841.758
934521AD1-076 C
80/20
4.8074.807
934511AD1-075 C
80/20
3.3093.309
316212AC1-099 C
80/20
0.1680.168
316263AC1-034 C
80/20
3.5493.549
3156073AA1-063SOLA
80/20
0.7530.753
316087AB2-174 C
80/20
0.8150.815
3151591KERR 2
80/20
0.5540.554
959311AF2-222 C
80/20
6.6486.648
937481AD2-202 C
80/20
0.1730.173
3151031BRUNSWICKG2
80/20
4.4774.477
316240AF1-291 C
Adder
-1.6611764705882353-1.412
944641AF1-129 C
Adder
-92.12117647058824-78.303
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.6422.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.16446.164
CPLELTFEXP_CPLE->PJM
CLTF
5.5395.539
TVALTFEXP_TVA->PJM
CLTF
3.0473.047
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.95317.953
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.57311.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1342.134
LAGNLTFEXP_LAGN->PJM
CLTF
3.8673.867
NYPJM->LTFIMP_NY
CLTF
0.5840.584
LGEELTFEXP_LGEE->PJM
CLTF
0.6950.695
WECLTFEXP_WEC->PJM
CLTF
0.3670.367
SIGELTFEXP_SIGE->PJM
CLTF
0.1330.133

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:736.13
MW Contribution:4.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943171AE2-346 C
80/20
0.2840.284
961941AG1-037 C
80/20
0.6420.642
3151391GASTONA
80/20
6.76.7
934321AD1-056 C
80/20
10.25810.258
934331AD1-057 C
80/20
5.7225.722
958211AF2-115 C
80/20
0.790.79
316365AB2-100 C1
80/20
2.8782.878
3156083AA2-088SOLA
80/20
1.0451.045
934501AD1-074 C
80/20
28.03828.038
961671AG1-007 C
80/20
1.1061.106
940491AE2-034 C
80/20
0.7340.734
316359AB2-059 C OP
80/20
2.0212.021
3156116Z1-036WIND
80/20
0.2510.251
946301AF1-294 C
80/20
1.31.3
934521AD1-076 C
80/20
10.18310.183
934511AD1-075 C
80/20
7.017.01
316212AC1-099 C
80/20
0.4340.434
316263AC1-034 C
80/20
8.0388.038
3156073AA1-063SOLA
80/20
1.9821.982
316087AB2-174 C
80/20
2.5762.576
3151591KERR 2
80/20
0.7120.712
959311AF2-222 C
80/20
7.5547.554
3151381ROSEMG2
80/20
2.0062.006
960081AF2-299 C
80/20
4.5664.566
936261AD2-033 C
80/20
6.4546.454
961791AG1-021 C
80/20
0.6320.632
938771AE1-103 C
80/20
1.2731.273
927021AC1-189 C
80/20
9.5779.577
316005AA1-067 C
80/20
0.2960.296
316210AC1-098 C
80/20
1.2971.297
316318V4-068 C
80/20
0.090.09
313506AB1-173 C OP
80/20
2.3432.343
966621AG1-532 C
80/20
3.4243.424
3151601KERR 3
80/20
0.7120.712
3151581KERR 1
80/20
0.2540.254
932631AC2-084 C
80/20
1.3811.381
316274AC1-208 C
80/20
12.83612.836
962571AG1-106 C
80/20
5.9855.985
3151311EDGECMA
80/20
19.08119.081
3152661PLYWOOD A
80/20
0.3910.391
316140AB2-099 C
80/20
0.1220.122
3152921DOMTR78
80/20
1.2081.208
316319Z2-044 C
80/20
0.2660.266
3151641KERR 7
80/20
0.7120.712
313527AB2-043 C
80/20
0.3120.312
926071AC1-086 C
80/20
46.26846.268
946281AF1-292 C
80/20
3.783.78
964241AG1-285 C
80/20
7.0017.001
962561AG1-105 C
80/20
3.8843.884
316034AC1-036 C
80/20
0.110.11
316118AC1-105 C
80/20
0.3030.303
3144293JTRSVLE
80/20
0.1450.145
315614AA2-178 C
80/20
0.9970.997
3151411GASTONB
80/20
6.76.7
316181AB2-040 GEN
80/20
2.6392.639
3147043LAWRENC
80/20
0.5880.588
3151261ROARAP2
80/20
2.2952.295
933981AD1-022 C
80/20
8.3538.353
316174AB2-169_C
80/20
0.9970.997
3156063AA2-053SOLA
80/20
2.4062.406
3151281ROARAP4
80/20
2.1722.172
316049AB1-081 C OP
80/20
1.7151.715
316238AB2-078 C O1
80/20
0.1950.195
3156011CONETOE2SOL
80/20
1.4481.448
3151611KERR 4
80/20
0.7120.712
3151621KERR 5
80/20
0.7120.712
316237AB2-079 C O1
80/20
0.1950.195
3151361ROSEMG1
80/20
4.2844.284
316327AA2-057 C
80/20
1.711.71
3151151S HAMPT1
80/20
1.0351.035
316239AB2-077 C O1
80/20
0.1950.195
964791AG1-342 C
80/20
1.4341.434
316317KELFORD C
80/20
0.4780.478
957861AF2-080 C
80/20
8.6988.698
316023AB2-100 C2
80/20
2.8782.878
316129AC1-054 C
80/20
1.321.32
3151631KERR 6
80/20
0.7120.712
316131AB2-060 C
80/20
0.8840.884
3138533PONTONDP
80/20
0.2340.234
3156021HOLLOMANSOL
80/20
2.3822.382
316011AB1-132 C OP
80/20
5.1165.116
3151371ROSEMS1
80/20
2.6542.654
3137643SOCKMAN
80/20
1.3221.322
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5172.517
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.76439.764
CPLELTFEXP_CPLE->PJM
CLTF
5.2785.278
TVALTFEXP_TVA->PJM
CLTF
2.5052.505
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.04115.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.5619.561
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.7731.773
LAGNLTFEXP_LAGN->PJM
CLTF
3.1853.185
NYPJM->LTFIMP_NY
CLTF
0.4240.424
LGEELTFEXP_LGEE->PJM
CLTF
0.5780.578
WECLTFEXP_WEC->PJM
CLTF
0.3070.307
SIGELTFEXP_SIGE->PJM
CLTF
0.1110.111

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.8 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:711.27
MW Contribution:4.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316365AB2-100 C1
80/20
2.7382.738
3156083AA2-088SOLA
80/20
0.8980.898
934501AD1-074 C
80/20
19.28319.283
961671AG1-007 C
80/20
0.970.97
940491AE2-034 C
80/20
0.5050.505
316359AB2-059 C OP
80/20
1.8661.866
934521AD1-076 C
80/20
7.0037.003
934511AD1-075 C
80/20
4.8214.821
316212AC1-099 C
80/20
0.370.37
3151381ROSEMG2
80/20
1.8351.835
960081AF2-299 C
80/20
4.3064.306
936171AD2-023 C
80/20
2.0082.008
936261AD2-033 C
80/20
5.5815.581
938771AE1-103 C
80/20
1.1451.145
316005AA1-067 C
80/20
0.2330.233
316210AC1-098 C
80/20
1.1041.104
316318V4-068 C
80/20
0.0730.073
313506AB1-173 C OP
80/20
2.1692.169
966621AG1-532 C
80/20
3.233.23
3151601KERR 3
80/20
0.6330.633
3151581KERR 1
80/20
0.2260.226
936161AD2-022 C
80/20
3.4423.442
316263AC1-034 C
80/20
7.4217.421
3156073AA1-063SOLA
80/20
1.7541.754
316087AB2-174 C
80/20
2.42.4
3151591KERR 2
80/20
0.6330.633
959311AF2-222 C
80/20
6.4496.449
927021AC1-189 C
80/20
8.0138.013
926071AC1-086 C
80/20
42.342.3
946281AF1-292 C
80/20
3.5653.565
964241AG1-285 C
80/20
6.1446.144
962561AG1-105 C
80/20
3.4083.408
316034AC1-036 C
80/20
0.0940.094
943171AE2-346 C
80/20
0.2110.211
961941AG1-037 C
80/20
0.4770.477
3151391GASTONA
80/20
6.1266.126
934321AD1-056 C
80/20
9.4289.428
934331AD1-057 C
80/20
5.2595.259
316140AB2-099 C
80/20
0.0910.091
3152921DOMTR78
80/20
0.8630.863
316319Z2-044 C
80/20
0.2410.241
3151641KERR 7
80/20
0.6330.633
313527AB2-043 C
80/20
0.2770.277
315614AA2-178 C
80/20
0.6860.686
3151411GASTONB
80/20
6.1266.126
316181AB2-040 GEN
80/20
2.4442.444
3147043LAWRENC
80/20
0.5520.552
3151261ROARAP2
80/20
2.0572.057
933981AD1-022 C
80/20
5.6735.673
316174AB2-169_C
80/20
0.7390.739
3156063AA2-053SOLA
80/20
2.0962.096
3151281ROARAP4
80/20
1.9471.947
316049AB1-081 C OP
80/20
1.5831.583
316238AB2-078 C O1
80/20
0.1730.173
3156011CONETOE2SOL
80/20
1.2441.244
3151611KERR 4
80/20
0.6330.633
3151621KERR 5
80/20
0.6330.633
316237AB2-079 C O1
80/20
0.1730.173
932631AC2-084 C
80/20
1.1761.176
316274AC1-208 C
80/20
11.28911.289
962571AG1-106 C
80/20
5.4715.471
3151311EDGECMA
80/20
17.61917.619
3151361ROSEMG1
80/20
3.923.92
316327AA2-057 C
80/20
1.5281.528
3151151S HAMPT1
80/20
0.9030.903
316239AB2-077 C O1
80/20
0.1730.173
964791AG1-342 C
80/20
1.2551.255
316317KELFORD C
80/20
0.3680.368
957861AF2-080 C
80/20
7.2787.278
316023AB2-100 C2
80/20
2.7382.738
316129AC1-054 C
80/20
1.1791.179
3151631KERR 6
80/20
0.6330.633
316131AB2-060 C
80/20
0.7820.782
3156021HOLLOMANSOL
80/20
1.581.58
316011AB1-132 C OP
80/20
4.6784.678
3151371ROSEMS1
80/20
2.4282.428
3137643SOCKMAN
80/20
1.2051.205
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1753.175
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.41853.418
CPLELTFEXP_CPLE->PJM
CLTF
6.6566.656
TVALTFEXP_TVA->PJM
CLTF
3.5423.542
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.22922.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.65213.652
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.5732.573
LAGNLTFEXP_LAGN->PJM
CLTF
4.5044.504
NYPJM->LTFIMP_NY
CLTF
0.4770.477
LGEELTFEXP_LGEE->PJM
CLTF
0.8450.845
WECLTFEXP_WEC->PJM
CLTF
0.4510.451
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.72 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:697.11
MW Contribution:4.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943171AE2-346 C
80/20
0.2130.213
961941AG1-037 C
80/20
0.480.48
3151391GASTONA
80/20
6.1336.133
934321AD1-056 C
80/20
9.1359.135
934331AD1-057 C
80/20
5.0965.096
958211AF2-115 C
80/20
0.7340.734
316365AB2-100 C1
80/20
2.7652.765
3156083AA2-088SOLA
80/20
0.9250.925
934501AD1-074 C
80/20
19.85319.853
961671AG1-007 C
80/20
0.9040.904
940491AE2-034 C
80/20
0.5370.537
316359AB2-059 C OP
80/20
1.731.73
3156116Z1-036WIND
80/20
0.2010.201
946301AF1-294 C
80/20
1.2081.208
316005AA1-067 C
80/20
0.220.22
316210AC1-098 C
80/20
1.0791.079
316318V4-068 C
80/20
0.0740.074
313506AB1-173 C OP
80/20
2.1872.187
966621AG1-532 C
80/20
3.2633.263
3151601KERR 3
80/20
0.6440.644
3151581KERR 1
80/20
0.230.23
316140AB2-099 C
80/20
0.0910.091
3152921DOMTR78
80/20
0.8660.866
316319Z2-044 C
80/20
0.2270.227
3151641KERR 7
80/20
0.6440.644
313527AB2-043 C
80/20
0.290.29
927021AC1-189 C
80/20
7.5047.504
926071AC1-086 C
80/20
42.34842.348
946281AF1-292 C
80/20
3.6023.602
964241AG1-285 C
80/20
6.4946.494
962561AG1-105 C
80/20
3.5683.568
316034AC1-036 C
80/20
0.1020.102
3144293JTRSVLE
80/20
0.1350.135
315614AA2-178 C
80/20
0.7290.729
3151411GASTONB
80/20
6.1336.133
316181AB2-040 GEN
80/20
2.4632.463
3147043LAWRENC
80/20
0.5590.559
940481AE2-033 C
80/20
63.69463.694
940541AE2-040 C
80/20
11.74711.747
3151261ROARAP2
80/20
2.0652.065
933981AD1-022 C
80/20
5.7955.795
316174AB2-169_C
80/20
0.7240.724
3156063AA2-053SOLA
80/20
2.1042.104
3151281ROARAP4
80/20
1.9541.954
316049AB1-081 C OP
80/20
1.4681.468
316238AB2-078 C O1
80/20
0.1810.181
3156011CONETOE2SOL
80/20
1.1621.162
3151611KERR 4
80/20
0.6440.644
3151621KERR 5
80/20
0.6440.644
316237AB2-079 C O1
80/20
0.1810.181
932631AC2-084 C
80/20
1.1481.148
316274AC1-208 C
80/20
11.02211.022
962571AG1-106 C
80/20
5.4785.478
3151311EDGECMA
80/20
16.35316.353
3151381ROSEMG2
80/20
1.831.83
960081AF2-299 C
80/20
4.3514.351
936261AD2-033 C
80/20
5.9895.989
961791AG1-021 C
80/20
0.5880.588
938771AE1-103 C
80/20
1.2791.279
3151361ROSEMG1
80/20
3.9083.908
316327AA2-057 C
80/20
1.461.46
3151151S HAMPT1
80/20
0.9570.957
316239AB2-077 C O1
80/20
0.1810.181
964791AG1-342 C
80/20
1.3141.314
316317KELFORD C
80/20
0.3660.366
957861AF2-080 C
80/20
6.8156.815
316023AB2-100 C2
80/20
2.7652.765
316129AC1-054 C
80/20
1.1891.189
3151631KERR 6
80/20
0.6440.644
316315AB2-025 C
80/20
1.6631.663
316131AB2-060 C
80/20
0.820.82
3138533PONTONDP
80/20
0.2180.218
3156021HOLLOMANSOL
80/20
1.5911.591
316011AB1-132 C OP
80/20
4.6834.683
3151371ROSEMS1
80/20
2.422.42
3137643SOCKMAN
80/20
1.2121.212
934521AD1-076 C
80/20
7.217.21
934511AD1-075 C
80/20
4.9634.963
316212AC1-099 C
80/20
0.3610.361
316263AC1-034 C
80/20
6.8836.883
3156073AA1-063SOLA
80/20
1.7721.772
316087AB2-174 C
80/20
2.4212.421
3151591KERR 2
80/20
0.6440.644
959311AF2-222 C
80/20
7.0127.012
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.0622.062
CBM South 2LTFEXP_CBM-S2->PJM
CBM
32.61632.616
CPLELTFEXP_CPLE->PJM
CLTF
4.3234.323
TVALTFEXP_TVA->PJM
CLTF
2.0422.042
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.06512.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.7657.765
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4321.432
LAGNLTFEXP_LAGN->PJM
CLTF
2.5962.596
NYPJM->LTFIMP_NY
CLTF
0.370.37
LGEELTFEXP_LGEE->PJM
CLTF
0.4650.465
WECLTFEXP_WEC->PJM
CLTF
0.2460.246
SIGELTFEXP_SIGE->PJM
CLTF
0.0890.089

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.38 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4467.2
MW Contribution:4.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316141AB2-099 E
Adder
0.33882352941176470.288
961672AG1-007 E
Adder
0.71058823529411760.604
923994AB2-040_E
Adder
8.2247058823529416.991
316088AB2-174 E
Adder
8.7141176470588247.407
924322AB2-079 E O1
Adder
1.6447058823529411.398
934501AD1-074 C
Adder
45.3647058823529438.56
961671AG1-007 C
Adder
1.25411764705882361.066
924517AB2-100 E2
Adder
3.9282352941176473.339
937226AE2-253 E
50/50
7.9097.909
935172AD1-152 E
Adder
7.5717647058823536.436
957862AF2-080 E
Adder
4.53176470588235253.852
926072AC1-086 E
Adder
12.85176470588235310.924
943902AF1-058 E
Adder
1.65529411764705881.407
957481AF2-042 C
50/50
79.02379.023
316294AC1-161 C
50/50
6.8696.869
944581AF1-123 C
50/50
62.37662.376
316185AD1-033 C
50/50
1.6591.659
916191Z1-068 C
50/50
0.0590.059
941101AE2-104 C
Adder
4.4388235294117653.773
918512AA1-065 E OP
Adder
7.42823529411764756.314
918532AA1-067 E
Adder
0.95764705882352940.814
934502AD1-074 E
Adder
23.0929411764705919.629
934512AD1-075 E
Adder
5.7729411764705894.907
924516AB2-100 E1
Adder
3.9282352941176473.339
966621AG1-532 C
Adder
1.87411764705882341.593
919153AA1-139 E2
50/50
5.535.53
316388AE2-253 GEN
50/50
2.652.65
924022AB2-043 E O1
Adder
6.3552941176470595.402
3151021BRUNSWICKG1
50/50
13.49313.493
3151041BRUNSWICKG3
50/50
13.49313.493
940642AE2-051 E
50/50
19.2519.25
942341AE2-247 C
Adder
1.89411764705882371.61
943462AF1-017 E
Adder
2.7964705882352942.377
958162AF2-110 E
Adder
2.8811764705882352.449
934521AD1-076 C
Adder
16.4752941176470614.004
934511AD1-075 C
Adder
11.3411764705882369.64
919692AA2-053 E OP
Adder
5.65176470588235354.804
316263AC1-034 C
Adder
8.8505882352941177.523
923573AB1-173 E OP
Adder
4.3858823529411773.728
3145723EMPORIA
Adder
0.57647058823529410.49
920042AA2-088 E OP
Adder
14.1647058823529412.04
925785AC1-054 E
Adder
4.5188235294117653.841
919152AA1-139 E1
50/50
5.535.53
937481AD2-202 C
50/50
0.5150.515
3151031BRUNSWICKG2
50/50
13.49313.493
942342AE2-247 E
Adder
2.61647058823529432.224
927021AC1-189 C
Adder
11.2564705882352949.568
926071AC1-086 C
Adder
28.2376470588235324.002
924152AB2-059 E OP
Adder
7.0388235294117655.983
946281AF1-292 C
Adder
2.0682352941176471.758
960082AF2-299 E
Adder
1.66588235294117641.416
916042Z1-036 E
Adder
38.52941176470588432.75
923832AB2-022 E
Adder
1.67529411764705881.424
964241AG1-285 C
Adder
14.8776470588235312.646
962561AG1-105 C
Adder
11.1211764705882359.453
938772AE1-103 E
Adder
5.3788235294117654.572
963042AG1-153 E
50/50
13.7613.76
944592AF1-124 E
50/50
143.351143.351
944582AF1-123 E
50/50
142.834142.834
3151091ELIZAR2
50/50
4.2124.212
316349AD2-085 C
Adder
4.3705882352941173.715
935112AD1-144 E
Adder
1.21411764705882351.032
926214AC1-099 E
Adder
1.61294117647058831.371
932632AC2-084 E
Adder
4.3164705882352943.669
962572AG1-106 E
Adder
1.59764705882352961.358
957872AF2-081 E
50/50
5.7955.795
316018AA1-139 ULT2
50/50
1.4591.459
924162AB2-060 E OP
Adder
5.2141176470588244.432
964242AG1-285 E
Adder
9.9188235294117648.431
964792AG1-342 E
Adder
2.9682352941176472.523
932763AC2-100 E
Adder
3.2952941176470592.801
926755AC1-161 E
50/50
18.00718.007
933291AC2-141 C
50/50
42.18342.183
3150921YORKTN3
Adder
106.1988235294117790.269
925522AC1-027 E
50/50
1.641.64
941102AE2-104 E
Adder
7.0576470588235295.999
3145256KINGFORK
Adder
1.30823529411764721.112
923263AB1-132 E OP
Adder
8.217647058823536.985
940481AE2-033 C
50/50
22.31122.311
940482AE2-033 E
50/50
15.04115.041
940541AE2-040 C
50/50
3.9673.967
924312AB2-078 E O1
Adder
1.6447058823529411.398
926274AC1-105 E
Adder
3.4082352941176472.897
3152441Z1-086 ST
50/50
30.18730.187
316375AC2-012 C
50/50
1.8031.803
920692AA2-178 E
Adder
5.5388235294117654.708
922923AB1-081 E OP
Adder
4.9682352941176474.223
966622AG1-532 E
Adder
1.24941176470588241.062
917122Z2-027 E
Adder
1.81294117647058831.541
3146326AYDLETT TAP
50/50
1.8341.834
938532AE1-072 E
50/50
12.39212.392
927264AC1-222 E
Adder
5.0905882352941184.327
3152411Z1-086 GT1
50/50
17.34217.342
3152421Z1-086 GT2
50/50
17.33717.337
943461AF1-017 C
Adder
1.71411764705882371.457
316311AC2-079 C
Adder
7.3223529411764716.224
932596AC2-079 E
Adder
11.94588235294117610.154
933981AD1-022 C
Adder
11.78823529411764610.02
900672V4-068 E
Adder
0.47764705882352950.406
938531AE1-072 C
50/50
23.77123.771
924302AB2-077 E O1
Adder
1.6447058823529411.398
3145393UNCAMP
Adder
8.0941176470588236.88
932046AC2-012 E
50/50
17.5517.55
958161AF2-110 C
Adder
1.8117647058823531.54
933982AD1-022 E
Adder
6.417647058823535.455
3145946PLYMOUTH TP
Adder
0.435294117647058830.37
927146AC1-208 E
Adder
5.3517647058823544.549
316017AA1-139 ULT1
50/50
1.4591.459
927255AC1-221 E
Adder
4.84941176470588254.122
934612AD1-087 E
50/50
5.1365.136
934611AD1-087 C
50/50
1.7741.774
934622AD1-088 E
50/50
6.3856.385
3152431Z1-086 GT3
50/50
17.33717.337
940641AE2-051 C
50/50
28.87528.875
316084AB2-161 E
Adder
6.5576470588235295.574
943172AE2-346 E
Adder
0.81176470588235290.69
917332KELFORD E
Adder
2.2035294117647061.873
925122AB2-169 E
Adder
7.7223529411764716.564
934522AD1-076 E
Adder
8.397647058823537.138
940492AE2-034 E
Adder
4.1541176470588243.531
316274AC1-208 C
Adder
12.05058823529411810.243
962571AG1-106 C
Adder
3.6529411764705883.105
917342Z2-044 E
Adder
0.79764705882352950.678
3151311EDGECMA
Adder
20.6976470588235317.593
918492AA1-063AE OP
Adder
5.4552941176470594.637
957871AF2-081 C
50/50
13.52313.523
937482AD2-202 E
50/50
1.5031.503
3145506HICKORY
50/50
2.9532.953
933292AC2-141 E
50/50
18.00718.007
934576AD1-082 E
Adder
5.2247058823529414.441
944602AF1-125 E
50/50
140.592140.592
943612AF1-032 E
Adder
1.24117647058823531.055
961942AG1-037 E
Adder
0.451764705882352960.384
961941AG1-037 C
Adder
0.6764705882352940.575
927022AC1-189 E
Adder
5.6070588235294124.766
934322AD1-056 E
Adder
4.5447058823529413.863
934332AD1-057 E
Adder
2.43411764705882352.069
934321AD1-056 C
Adder
8.3788235294117657.122
934331AD1-057 C
Adder
4.6741176470588233.973
925595AC1-034 E
Adder
6.6764705882352945.675
923852AB2-025 E
50/50
1.6041.604
3151531CLOVER1
50/50
18.02218.022
941031AE2-094 C
50/50
66.68466.684
941032AE2-094 E
50/50
29.86629.866
939412AE1-173 E
50/50
96.49596.495
3151081ELIZAR1
50/50
4.2884.288
926662AC1-147 E
Adder
1.77411764705882361.508
916192Z1-068 E
50/50
2.5342.534
957492AF2-043 E
Adder
1.9105882352941181.624
960081AF2-299 C
Adder
2.4988235294117652.124
3145413WATKINS
Adder
0.92117647058823540.783
962562AG1-105 E
Adder
7.41411764705882356.302
938771AE1-103 C
Adder
3.8941176470588243.31
963041AG1-153 C
50/50
9.1739.173
3151051BRUNSWICKS1
50/50
28.03428.034
944011AF1-069 C
50/50
21.78821.788
944591AF1-124 C
50/50
62.59862.598
944601AF1-125 C
50/50
61.41561.415
3151101ELIZAR3
50/50
4.3424.342
941591AE2-156 C
50/50
24.00724.007
936666AD2-085 E
Adder
7.1317647058823546.062
926206AC1-098 E
Adder
4.8835294117647064.151
964791AG1-342 C
Adder
4.4517647058823523.784
901082W1-029 E
Adder
42.9564705882352936.513
3143316POE
Adder
1.6082352941176471.367
939191AE1-149 C
Adder
12.10588235294117610.29
919710AA2-057 E
Adder
5.2964705882352944.502
3137643SOCKMAN
Adder
0.95176470588235310.809
913392Y1-086 E
Adder
2.9682352941176472.523
939411AE1-173 C
50/50
144.742144.742
957861AF2-080 C
Adder
10.2235294117647058.69
917512Z2-088 E OP1
Adder
6.54705882352941255.565
946282AF1-292 E
Adder
1.37882352941176461.172
316315AB2-025 C
50/50
0.5620.562
3151541CLOVER2
50/50
17.85317.853
944012AF1-069 E
50/50
8.4648.464
316316AC1-027 C
50/50
0.4240.424
934621AD1-088 C
50/50
13.2613.26
957482AF2-042 E
50/50
52.68252.682
939192AE1-149 E
Adder
8.0705882352941176.86
939312AE1-162 E
Adder
1.72117647058823551.463
934065AD1-033 E
50/50
6.7926.792
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6257.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
136.078136.078
CPLELTFEXP_CPLE->PJM
CLTF
15.98515.985
TVALTFEXP_TVA->PJM
CLTF
9.3529.352
O66PJM->LTFIMP_O-066
CMTX_NF
36.00236.002
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.25255.252
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.53435.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.5866.586
LAGNLTFEXP_LAGN->PJM
CLTF
11.79711.797
NYPJM->LTFIMP_NY
CLTF
2.5842.584
LGEELTFEXP_LGEE->PJM
CLTF
2.1892.189
WECLTFEXP_WEC->PJM
CLTF
1.1371.137
G-007PJM->LTFIMP_G-007
CMTX_NF
5.665.66
SIGELTFEXP_SIGE->PJM
CLTF
0.4160.416

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.8 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3342.68
MW Contribution:2.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943171AE2-346 C
80/20
0.2980.298
961941AG1-037 C
80/20
0.6730.673
3151391GASTONA
80/20
4.0664.066
934321AD1-056 C
Adder
8.332941176470597.083
934331AD1-057 C
Adder
4.6482352941176473.951
958211AF2-115 C
Adder
2.28235294117647051.94
3151531CLOVER1
80/20
17.9517.95
941031AE2-094 C
80/20
66.45566.455
3151081ELIZAR1
80/20
4.2584.258
316365AB2-100 C1
80/20
1.2911.291
3156083AA2-088SOLA
80/20
1.4051.405
957481AF2-042 C
80/20
78.71578.715
940431AE2-027 C
Adder
11.395294117647069.686
316294AC1-161 C
80/20
6.8246.824
944581AF1-123 C
80/20
61.95761.957
316185AD1-033 C
80/20
1.6481.648
916191Z1-068 C
80/20
0.0580.058
941101AE2-104 C
80/20
4.4074.407
934501AD1-074 C
80/20
45.0845.08
961671AG1-007 C
Adder
1.2482352941176471.061
940491AE2-034 C
80/20
1.5381.538
3156116Z1-036WIND
80/20
0.8770.877
946301AF1-294 C
Adder
3.75411764705882333.191
934621AD1-088 C
80/20
13.20613.206
942001AE2-212 C
Adder
2.11411764705882371.797
934521AD1-076 C
80/20
16.37216.372
934511AD1-075 C
80/20
11.2711.27
316212AC1-099 C
80/20
0.4180.418
316263AC1-034 C
Adder
8.8035294117647057.483
3156073AA1-063SOLA
80/20
1.8611.861
316087AB2-174 C
80/20
1.561.56
316321Z2-027 C
80/20
0.4860.486
959311AF2-222 C
Adder
18.28823529411764815.545
937481AD2-202 C
80/20
0.5130.513
3151031BRUNSWICKG2
80/20
13.44613.446
316036AC1-147 C
80/20
0.4890.489
3151381ROSEMG2
80/20
1.271.27
960081AF2-299 C
80/20
2.4842.484
936171AD2-023 C
Adder
5.5152941176470584.688
936261AD2-033 C
Adder
14.72470588235294112.516
961791AG1-021 C
Adder
1.82588235294117651.552
938771AE1-103 C
80/20
3.8693.869
963041AG1-153 C
80/20
9.1419.141
3151051BRUNSWICKS1
80/20
27.93627.936
944011AF1-069 C
80/20
21.71321.713
944591AF1-124 C
80/20
62.17762.177
944601AF1-125 C
80/20
61.00261.002
3151101ELIZAR3
80/20
4.3114.311
941591AE2-156 C
80/20
23.83823.838
316210AC1-098 C
80/20
1.251.25
316318V4-068 C
80/20
0.1070.107
313506AB1-173 C OP
80/20
1.4941.494
966621AG1-532 C
80/20
1.8631.863
316320Y1-086 C
80/20
0.2940.294
316388AE2-253 GEN
80/20
2.6322.632
936161AD2-022 C
Adder
9.455294117647068.037
935171AD1-152 C
80/20
1.8271.827
3151021BRUNSWICKG1
80/20
13.44613.446
3151041BRUNSWICKG3
80/20
13.44613.446
942341AE2-247 C
80/20
1.881.88
316246AF1-032 C
80/20
0.3780.378
932631AC2-084 C
80/20
1.3311.331
316274AC1-208 C
80/20
11.98411.984
962571AG1-106 C
80/20
3.6323.632
3151311EDGECMA
Adder
20.58941176470588317.501
957871AF2-081 C
80/20
13.4313.43
316140AB2-099 C
80/20
0.1280.128
3152921DOMTR78
80/20
1.8181.818
316018AA1-139 ULT2
80/20
1.4491.449
933291AC2-141 C
80/20
41.90441.904
3150921YORKTN3
Adder
127.84235294117647108.666
927021AC1-189 C
Adder
11.1952941176470599.516
926071AC1-086 C
80/20
28.07728.077
946281AF1-292 C
80/20
2.0562.056
964241AG1-285 C
Adder
14.80352941176470712.583
962561AG1-105 C
Adder
11.0694117647058839.409
3151091ELIZAR2
80/20
4.1834.183
316349AD2-085 C
80/20
4.3374.337
315614AA2-178 C
80/20
2.0912.091
3151411GASTONB
80/20
4.0664.066
316181AB2-040 GEN
80/20
1.6831.683
3147043LAWRENC
80/20
0.3980.398
940481AE2-033 C
80/20
22.18122.181
940541AE2-040 C
80/20
3.9443.944
3152441Z1-086 ST
80/20
30.08130.081
961611AG1-000B C
Adder
17.0670588235294114.507
316375AC2-012 C
80/20
1.7911.791
316072AD1-144 C
80/20
0.3590.359
3151261ROARAP2
80/20
1.8341.834
3156056W1-029WIND
80/20
1.0361.036
3152411Z1-086 GT1
80/20
17.28117.281
3152421Z1-086 GT2
80/20
17.27717.277
943461AF1-017 C
80/20
1.7011.701
316311AC2-079 C
80/20
7.2667.266
933981AD1-022 C
80/20
11.71411.714
316174AB2-169_C
80/20
1.3931.393
3156063AA2-053SOLA
80/20
1.9981.998
3151281ROARAP4
80/20
1.7351.735
938531AE1-072 C
80/20
23.60823.608
935161AD1-151 C
Adder
15.27058823529411812.98
958161AF2-110 C
80/20
1.7981.798
313526AB2-022 C
80/20
0.5040.504
316017AA1-139 ULT1
80/20
1.4491.449
934611AD1-087 C
80/20
1.7671.767
3152431Z1-086 GT3
80/20
17.27717.277
940641AE2-051 C
80/20
28.76428.764
3152331SURRY 2
80/20
30.82730.827
3151361ROSEMG1
80/20
2.7122.712
3151151S HAMPT1
80/20
1.9741.974
964791AG1-342 C
Adder
4.4317647058823533.767
939191AE1-149 C
Adder
11.99058823529411710.192
3150981CHESPKA
80/20
0.5780.578
316317KELFORD C
80/20
0.4760.476
957861AF2-080 C
Adder
10.167058823529418.642
316023AB2-100 C2
80/20
1.2911.291
316129AC1-054 C
80/20
1.5891.589
316315AB2-025 C
80/20
0.5580.558
3138533PONTONDP
Adder
0.6764705882352940.575
3151541CLOVER2
80/20
17.78217.782
316316AC1-027 C
80/20
0.4210.421
3156021HOLLOMANSOL
80/20
2.4482.448
316011AB1-132 C OP
80/20
3.1053.105
3151371ROSEMS1
80/20
1.681.68
3137643SOCKMAN
80/20
0.9470.947
939411AE1-173 C
80/20
144.1144.1
3150991CHESPKB
80/20
0.9580.958
316305AF2-043 C
80/20
0.4630.463
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.597.59
CBM South 2LTFEXP_CBM-S2->PJM
CBM
135.46135.46
CPLELTFEXP_CPLE->PJM
CLTF
15.91315.913
TVALTFEXP_TVA->PJM
CLTF
9.319.31
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.0655.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.38335.383
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.566.56
LAGNLTFEXP_LAGN->PJM
CLTF
11.74411.744
NYPJM->LTFIMP_NY
CLTF
2.5592.559
LGEELTFEXP_LGEE->PJM
CLTF
2.182.18
WECLTFEXP_WEC->PJM
CLTF
1.1331.133
SIGELTFEXP_SIGE->PJM
CLTF
0.4150.415

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.31 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:3793.69
MW Contribution:2.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943172AE2-346 E
Adder
0.90941176470588240.773
917332KELFORD E
Adder
2.42.04
925122AB2-169 E
Adder
8.6941176470588237.39
934522AD1-076 E
Adder
9.9670588235294128.472
940492AE2-034 E
Adder
5.057647058823534.299
962571AG1-106 C
Adder
3.71294117647058863.156
918492AA1-063AE OP
Adder
5.82352941176470654.95
957871AF2-081 C
50/50
17.9717.97
3145506HICKORY
50/50
3.9493.949
936591AD2-074 C
Adder
8.3435294117647067.092
3130536PAPERMILL
Adder
10.4988235294117648.924
939602AE1-190 E
Adder
2.23058823529411751.896
933292AC2-141 E
50/50
25.37725.377
934576AD1-082 E
Adder
6.4070588235294125.446
944602AF1-125 E
50/50
188.725188.725
943612AF1-032 E
50/50
1.6391.639
926072AC1-086 E
Adder
13.06352941176470511.104
960081AF2-299 C
Adder
2.12235294117647081.804
3145413WATKINS
Adder
1.09647058823529430.932
938771AE1-103 C
Adder
4.7799999999999994.063
963041AG1-153 C
Adder
7.662352941176476.513
944011AF1-069 C
Adder
18.13647058823529415.416
3150601CHESTF5
Adder
80.1388235294117768.118
964212AG1-282 E
Adder
1.91529411764705881.628
925332AB2-190 E
Adder
11.1811764705882369.504
962962AG1-145 E
50/50
2.6032.603
927226AC1-216 E
Adder
11.3047058823529419.609
944591AF1-124 C
50/50
84.02984.029
944601AF1-125 C
50/50
82.44182.441
3151101ELIZAR3
50/50
5.8665.866
941591AE2-156 C
50/50
32.45632.456
936666AD2-085 E
Adder
9.0611764705882357.702
3137643SOCKMAN
Adder
0.96588235294117640.821
913392Y1-086 E
50/50
3.893.89
316078AC2-138 E
Adder
1.30588235294117671.11
958262AF2-120 E
Adder
6.1329411764705885.213
966661AG1-536 C
Adder
7.9129411764705886.726
939612AE1-191 E
Adder
8.9247058823529427.586
957602AF2-054 E
Adder
2.24117647058823531.905
939411AE1-173 C
50/50
144.69144.69
934012AD1-025 E
Adder
14.63647058823529612.441
3151161SURRY 1
50/50
40.01440.014
3150991CHESPKB
50/50
1.3041.304
934521AD1-076 C
Adder
19.5552941176470616.622
934511AD1-075 C
Adder
13.46117647058823511.442
919692AA2-053 E OP
Adder
5.8800000000000014.998
923573AB1-173 E OP
Adder
4.3988235294117643.739
3145723EMPORIA
Adder
0.57058823529411760.485
920042AA2-088 E OP
Adder
16.1705882352941213.745
316321Z2-027 C
50/50
0.6380.638
919152AA1-139 E1
50/50
7.3487.348
939246AE1-155 E
Adder
12.80941176470588310.888
924814AB2-134 E
Adder
18.51882352941176515.741
316036AC1-147 C
50/50
0.6650.665
942342AE2-247 E
Adder
3.3247058823529412.826
316305AF2-043 C
50/50
0.6160.616
901082W1-029 E
50/50
55.655.6
958261AF2-120 C
Adder
9.1988235294117657.819
939191AE1-149 C
Adder
14.42941176470588312.265
934146AD1-041 E
Adder
5.5776470588235294.741
957601AF2-054 C
Adder
3.36117647058823542.857
316382AG1-145 C
50/50
0.6360.636
3150981CHESPKA
50/50
0.7870.787
918512AA1-065 E OP
Adder
8.4494117647058827.182
934502AD1-074 E
Adder
27.4094117647058823.298
934512AD1-075 E
Adder
6.8529411764705895.825
924516AB2-100 E1
Adder
3.87764705882352923.296
316320Y1-086 C
50/50
0.3880.388
919153AA1-139 E2
50/50
7.3487.348
316388AE2-253 GEN
50/50
3.5313.531
940642AE2-051 E
50/50
17.58317.583
963612AG1-210 E
Adder
1.39882352941176481.189
316159AE1-175 C
50/50
0.7040.704
942341AE2-247 C
Adder
2.40705882352941152.046
943462AF1-017 E
Adder
3.55294117647058853.02
958162AF2-110 E
50/50
3.7353.735
316246AF1-032 C
50/50
0.5030.503
944012AF1-069 E
Adder
7.04588235294117655.989
961952AG1-038 E
Adder
6.66352941176470555.664
961951AG1-038 C
Adder
4.8258823529411774.102
925865AC1-065 E
Adder
25.8294117647058821.955
3144216WINCHST
50/50
0.2410.241
926071AC1-086 C
Adder
28.7023529411764724.397
916042Z1-036 E
50/50
48.46248.462
923832AB2-022 E
50/50
2.1962.196
938772AE1-103 E
Adder
6.6011764705882355.611
963042AG1-153 E
Adder
11.4941176470588249.77
316169AC1-164 GEN
50/50
65.01265.012
944592AF1-124 E
50/50
192.429192.429
944582AF1-123 E
50/50
191.735191.735
3151091ELIZAR2
50/50
5.6915.691
316349AD2-085 C
Adder
5.5541176470588244.721
935112AD1-144 E
50/50
1.661.66
961942AG1-037 E
Adder
0.50470588235294120.429
961941AG1-037 C
Adder
0.75764705882352950.644
923852AB2-025 E
Adder
1.53294117647058831.303
941031AE2-094 C
Adder
55.5058823529411847.18
941032AE2-094 E
Adder
24.8621.131
316076AC2-137 E
Adder
1.77294117647058821.507
964211AG1-282 C
Adder
2.87176470588235282.441
923842AB2-024 E
Adder
2.84000000000000032.414
316157AD2-030 E
Adder
1.88588235294117661.603
939412AE1-173 E
50/50
96.4696.46
3151081ELIZAR1
50/50
5.7935.793
926662AC1-147 E
50/50
2.3992.399
916192Z1-068 E
50/50
3.4083.408
957492AF2-043 E
50/50
2.5222.522
934501AD1-074 C
Adder
53.8447058823529445.768
924517AB2-100 E2
Adder
3.87764705882352923.296
3156116Z1-036WIND
50/50
1.1111.111
937226AE2-253 E
50/50
10.53510.535
3141813NORNECK
Adder
1.24235294117647071.056
962861AG1-135 C
Adder
8.9694117647058827.624
939192AE1-149 E
Adder
9.628.177
943741AF1-042 C
Adder
4.3658823529411773.711
939312AE1-162 E
50/50
2.4312.431
934065AD1-033 E
50/50
9.1079.107
923263AB1-132 E OP
Adder
8.3529411764705897.1
940481AE2-033 C
Adder
21.4117647058823518.2
940482AE2-033 E
Adder
14.43529411764705912.27
940541AE2-040 C
Adder
3.79058823529411763.222
3138116ELKO L286
Adder
1.84941176470588251.572
963611AG1-210 C
Adder
0.93294117647058830.793
957831AF2-077 C
50/50
0.570.57
961611AG1-000B C
Adder
25.22588235294117721.442
316375AC2-012 C
50/50
2.4382.438
316072AD1-144 C
50/50
0.4940.494
962572AG1-106 E
Adder
1.62470588235294121.381
957872AF2-081 E
50/50
7.7017.701
316018AA1-139 ULT2
50/50
1.9391.939
944631AF1-128 C
Adder
50.1435294117647142.622
936592AD2-074 E
Adder
13.61411764705882311.572
316160AE1-175 E
50/50
2.1482.148
926755AC1-161 E
50/50
25.37725.377
933291AC2-141 C
50/50
59.4559.45
3150921YORKTN3
50/50
222.183222.183
925522AC1-027 E
50/50
2.2062.206
941102AE2-104 E
50/50
9.159.15
3145256KINGFORK
50/50
1.7881.788
316141AB2-099 E
Adder
0.37882352941176470.322
923994AB2-040_E
Adder
8.2482352941176477.011
316088AB2-174 E
Adder
8.6929411764705897.389
966662AG1-536 E
Adder
10.6329411764705889.038
962862AG1-135 E
Adder
5.985.083
943742AF1-042 E
Adder
7.1235294117647056.055
934392AD1-063 E
Adder
1.69764705882352951.443
316294AC1-161 C
50/50
9.6819.681
944581AF1-123 C
50/50
83.73183.731
316185AD1-033 C
50/50
2.2242.224
916191Z1-068 C
50/50
0.0790.079
941101AE2-104 C
50/50
5.7555.755
933981AD1-022 C
Adder
13.8411.764
900672V4-068 E
Adder
0.53882352941176470.458
938531AE1-072 C
50/50
31.50731.507
3145393UNCAMP
Adder
9.815294117647068.343
935161AD1-151 C
Adder
22.94117647058823619.5
932046AC2-012 E
50/50
23.72823.728
958161AF2-110 C
50/50
2.3482.348
920692AA2-178 E
Adder
6.7435294117647065.732
917122Z2-027 E
50/50
2.3642.364
3146326AYDLETT TAP
50/50
2.4292.429
938532AE1-072 E
50/50
16.42416.424
3156056W1-029WIND
50/50
1.351.35
940551AE2-041 C
Adder
11.3211764705882359.623
935162AD1-151 E
Adder
15.29411764705882413
957832AF2-077 E
50/50
2.4692.469
943461AF1-017 C
Adder
2.17764705882352951.851
316311AC2-079 C
Adder
9.3282352941176477.929
932596AC2-079 E
Adder
15.21999999999999912.937
933982AD1-022 E
Adder
7.5341176470588246.404
3145946PLYMOUTH TP
Adder
0.51882352941176470.441
313526AB2-022 C
50/50
0.6650.665
316017AA1-139 ULT1
50/50
1.9391.939
940641AE2-051 C
50/50
26.37426.374
926785AC1-164_E
50/50
29.20829.208
943471AF1-018 C
Adder
11.3211764705882359.623
3152331SURRY 2
50/50
52.5452.54
316084AB2-161 E
Adder
8.0411764705882356.835
316236AE1-162 C
50/50
0.5940.594
316316AC1-027 C
50/50
0.5710.571
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.5566.556
CBM South 2LTFEXP_CBM-S2->PJM
CBM
111.34111.34
CPLELTFEXP_CPLE->PJM
CLTF
13.75813.758
TVALTFEXP_TVA->PJM
CLTF
6.4816.481
O66PJM->LTFIMP_O-066
CMTX_NF
27.4327.43
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.41628.416
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.24623.246
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.853.85
LAGNLTFEXP_LAGN->PJM
CLTF
8.2678.267
NYPJM->LTFIMP_NY
CLTF
2.0382.038
LGEELTFEXP_LGEE->PJM
CLTF
1.1621.162
WECLTFEXP_WEC->PJM
CLTF
0.5990.599
G-007PJM->LTFIMP_G-007
CMTX_NF
4.3044.304
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.92 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4555.56
MW Contribution:2.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.82117647058823530.698
934321AD1-056 C
Adder
9.6541176470588248.206
934331AD1-057 C
Adder
5.3847058823529414.577
941031AE2-094 C
Adder
59.24117647058823650.355
3150831SPRUNCA
Adder
15.78000000000000113.413
3150841SPRUNCB
Adder
15.78000000000000113.413
966871AG1-558 C
Adder
4.0835294117647063.471
316075AC2-137 C
80/20
0.6870.687
964211AG1-282 C
Adder
2.9811764705882352.534
3150801HOPHCF4
80/20
6.5586.558
316369AC1-216 C
80/20
2.8462.846
957481AF2-042 C
Adder
77.7682352941176466.103
940431AE2-027 C
Adder
22.58000000000000219.193
3150681DARBY 2
80/20
4.5764.576
316294AC1-161 C
80/20
8.8498.849
944581AF1-123 C
Adder
80.2141176470588368.182
941101AE2-104 C
Adder
5.8423529411764714.966
934501AD1-074 C
Adder
56.2176470588235347.785
961671AG1-007 C
Adder
1.44941176470588241.232
934621AD1-088 C
Adder
13.69294117647058911.639
942001AE2-212 C
Adder
3.73882352941176473.178
3150671DARBY 1
80/20
4.574.57
3150641CHESTS8
80/20
3.5113.511
962861AG1-135 C
Adder
9.3188235294117667.921
943741AF1-042 C
Adder
4.5552941176470593.872
934521AD1-076 C
Adder
20.41647058823529517.354
934511AD1-075 C
Adder
14.05411764705882411.946
316263AC1-034 C
Adder
10.102352941176478.587
316240AF1-291 C
Adder
3.78000000000000023.213
944641AF1-129 C
Adder
179.8423529411765152.866
3142296MT RD221
80/20
0.2170.217
316004AC1-112 C
80/20
0.5960.596
3150781HOPHCF2
80/20
4.324.32
3150761HOPPOLC
80/20
2.7172.717
960081AF2-299 C
Adder
2.92.465
936261AD2-033 C
Adder
18.25529411764705815.517
938771AE1-103 C
Adder
4.9788235294117654.232
963041AG1-153 C
Adder
8.3011764705882357.056
944011AF1-069 C
Adder
19.35647058823529316.453
3150621CHESTS7
80/20
3.1823.182
3150601CHESTF5
80/20
113.981113.981
944591AF1-124 C
Adder
80.4988235294117868.424
944601AF1-125 C
Adder
78.9788235294117767.132
941591AE2-156 C
Adder
31.64823529411764726.901
927021AC1-189 C
Adder
13.13058823529411811.161
926071AC1-086 C
Adder
32.9752941176470628.029
946281AF1-292 C
Adder
2.40117647058823552.041
964241AG1-285 C
Adder
17.71058823529411815.054
316169AC1-164 GEN
80/20
73.90473.904
316349AD2-085 C
Adder
5.9917647058823535.093
966621AG1-532 C
Adder
2.1752941176470591.849
3150771HOPHCF1
80/20
4.324.32
316159AE1-175 C
80/20
0.7120.712
942341AE2-247 C
Adder
2.5964705882352942.207
316274AC1-208 C
Adder
14.04588235294117711.939
962571AG1-106 C
Adder
4.2647058823529413.625
3151311EDGECMA
Adder
23.6270588235294120.083
957871AF2-081 C
Adder
17.51647058823529314.889
3150651CHESTF6
Adder
32.7447058823529427.833
936591AD2-074 C
Adder
8.7058823529411787.4
316033AB2-134 GEN
80/20
3.7293.729
934011AD1-025 C
80/20
4.6114.611
944631AF1-128 C
80/20
71.31971.319
933291AC2-141 C
80/20
54.34454.344
3150921YORKTN3
80/20
215.99215.99
3151191GRAVEL3
80/20
4.4484.448
3137643SOCKMAN
Adder
1.1117647058823530.945
316312AB1-027 C
80/20
0.9570.957
966661AG1-536 C
Adder
8.2105882352941186.979
939411AE1-173 C
Adder
145.74235294117648123.881
3151161SURRY 1
80/20
43.78743.787
940481AE2-033 C
Adder
25.6411764705882421.795
940541AE2-040 C
Adder
4.5529411764705883.87
927041AC1-191 C
Adder
16.39529411764705813.936
963611AG1-210 C
Adder
0.95764705882352940.814
961611AG1-000B C
80/20
28.34928.349
316233AE1-074 C
Adder
4.08588235294117653.473
3150691DARBY 3
80/20
4.5924.592
940551AE2-041 C
Adder
12.16117647058823610.337
943461AF1-017 C
Adder
2.34941176470588251.997
316311AC2-079 C
Adder
9.984705882352948.487
933981AD1-022 C
Adder
14.54588235294117712.364
938531AE1-072 C
Adder
30.76823529411764526.153
3142366NRTHEST
80/20
0.330.33
3150701DARBY 4
80/20
4.5974.597
3150731STONECA
80/20
12.27512.275
935161AD1-151 C
80/20
28.71928.719
958161AF2-110 C
Adder
2.38352941176470572.026
316336AC2-165 C
Adder
13.90823529411764711.822
940641AE2-051 C
Adder
26.97529411764705622.929
943471AF1-018 C
Adder
12.16117647058823610.337
3152331SURRY 2
80/20
45.81645.816
3151201GRAVEL4
80/20
4.5054.505
3151221GRAVEL6
80/20
4.54.5
3143096IRON208
80/20
0.7870.787
958261AF2-120 C
Adder
9.5447058823529418.113
939191AE1-149 C
Adder
18.60588235294117615.815
957601AF2-054 C
Adder
3.56235294117647073.028
316132AB2-190 C
80/20
7.3677.367
316382AG1-145 C
80/20
0.6420.642
957861AF2-080 C
Adder
11.92588235294117810.137
3150631CHESTG8
80/20
6.826.82
3150611CHESTG7
80/20
6.936.93
3150791HOPHCF3
80/20
4.324.32
961951AG1-038 C
Adder
5.035294117647064.28
3144216WINCHST
80/20
0.2370.237
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.4058.405
CBM South 2LTFEXP_CBM-S2->PJM
CBM
156.686156.686
CPLELTFEXP_CPLE->PJM
CLTF
17.60717.607
TVALTFEXP_TVA->PJM
CLTF
12.412.4
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.27284.272
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.64648.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
9.5619.561
LAGNLTFEXP_LAGN->PJM
CLTF
15.45715.457
NYPJM->LTFIMP_NY
CLTF
4.1344.134
LGEELTFEXP_LGEE->PJM
CLTF
3.3563.356
WECLTFEXP_WEC->PJM
CLTF
1.7261.726
SIGELTFEXP_SIGE->PJM
CLTF
0.620.62

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.48 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5586.28
MW Contribution:4.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316141AB2-099 E
Adder
0.410588235294117640.349
923994AB2-040_E
Adder
9.5835294117647068.146
316088AB2-174 E
Adder
10.1435294117647078.622
957481AF2-042 C
Adder
64.6541176470588354.956
942002AE2-212 E
Adder
2.49058823529411782.117
940431AE2-027 C
Adder
22.57058823529411719.185
3150681DARBY 2
50/50
4.5734.573
943742AF1-042 E
Adder
7.42705882352941156.313
934392AD1-063 E
Adder
1.8235294117647061.55
944581AF1-123 C
Adder
80.1835294117647168.156
941101AE2-104 C
Adder
5.8411764705882354.965
918512AA1-065 E OP
Adder
9.0517647058823547.694
934502AD1-074 E
Adder
28.60941176470588624.318
934512AD1-075 E
Adder
7.1529411764705896.08
924516AB2-100 E1
Adder
4.5505882352941183.868
966621AG1-532 C
Adder
2.1752941176470591.849
919153AA1-139 E2
Adder
7.166.086
940642AE2-051 E
Adder
17.97882352941176615.282
926412AC1-112 E
50/50
2.0462.046
316159AE1-175 C
50/50
0.7110.711
942341AE2-247 C
Adder
2.5964705882352942.207
943462AF1-017 E
Adder
3.8317647058823533.257
958162AF2-110 E
Adder
3.79058823529411763.222
934521AD1-076 C
Adder
20.41176470588235517.35
934511AD1-075 C
Adder
14.05058823529411811.943
919692AA2-053 E OP
Adder
6.6552941176470595.657
923573AB1-173 E OP
Adder
5.11176470588235254.345
3145723EMPORIA
Adder
0.66941176470588230.569
920042AA2-088 E OP
Adder
17.4414.824
919152AA1-139 E1
Adder
7.166.086
316240AF1-291 C
Adder
3.7788235294117653.212
944641AF1-129 C
Adder
179.7623529411765152.798
3142296MT RD221
50/50
0.2170.217
316004AC1-112 C
50/50
0.5960.596
926071AC1-086 C
Adder
32.9682352941176528.023
946281AF1-292 C
Adder
2.40117647058823552.041
960082AF2-299 E
Adder
1.93294117647058841.643
916042Z1-036 E
Adder
48.916470588235341.579
923832AB2-022 E
Adder
2.16117647058823531.837
938772AE1-103 E
Adder
6.8741176470588235.843
963042AG1-153 E
Adder
12.44941176470588410.582
930122AB1-027 E
50/50
2.5162.516
316169AC1-164 GEN
50/50
73.86273.862
944592AF1-124 E
Adder
184.2764705882353156.635
944582AF1-123 E
Adder
183.61176470588234156.07
316349AD2-085 C
Adder
5.9894117647058835.091
935112AD1-144 E
Adder
1.66000000000000011.411
962572AG1-106 E
Adder
1.86588235294117651.586
957872AF2-081 E
Adder
7.50470588235294046.379
938552AE1-074 E
Adder
2.05764705882352941.749
944631AF1-128 C
50/50
71.28371.283
936592AD2-074 E
Adder
14.19411764705882312.065
316160AE1-175 E
50/50
2.1682.168
926755AC1-161 E
Adder
23.1894117647058819.711
933291AC2-141 C
Adder
54.3223529411764746.174
3150921YORKTN3
Adder
215.8894117647059183.506
925522AC1-027 E
Adder
2.14588235294117661.824
941102AE2-104 E
Adder
9.2858823529411767.893
3145256KINGFORK
Adder
1.78823529411764711.52
923263AB1-132 E OP
Adder
9.595294117647068.156
940481AE2-033 C
Adder
25.63411764705882621.789
940482AE2-033 E
Adder
17.28117647058823514.689
940541AE2-040 C
Adder
4.5517647058823533.869
927041AC1-191 C
Adder
16.38352941176470513.926
3138116ELKO L286
50/50
2.5282.528
961611AG1-000B C
Adder
28.33647058823529424.086
920692AA2-178 E
Adder
6.9352941176470585.895
966622AG1-532 E
Adder
1.45058823529411771.233
917122Z2-027 E
Adder
2.3352941176470591.985
3146326AYDLETT TAP
Adder
2.3717647058823532.016
938532AE1-072 E
Adder
16.0329411764705913.628
316233AE1-074 C
Adder
4.08588235294117653.473
927042AC1-191 E
Adder
8.1611764705882366.937
3150691DARBY 3
50/50
4.5894.589
940551AE2-041 C
Adder
12.15411764705882410.331
935162AD1-151 E
Adder
19.1376470588235316.267
957832AF2-077 E
Adder
2.49294117647058842.119
943461AF1-017 C
Adder
2.34941176470588251.997
316311AC2-079 C
Adder
9.9811764705882358.484
932596AC2-079 E
Adder
16.2847058823529413.842
933981AD1-022 C
Adder
14.54117647058823512.36
900672V4-068 E
Adder
0.58235294117647060.495
938531AE1-072 C
Adder
30.75647058823529526.143
3145393UNCAMP
Adder
10.2788235294117658.737
3142366NRTHEST
50/50
0.330.33
3150701DARBY 4
50/50
4.5944.594
3150731STONECA
Adder
12.26941176470588210.429
935161AD1-151 C
Adder
28.70588235294117424.4
932046AC2-012 E
Adder
23.15176470588235319.679
958161AF2-110 C
Adder
2.38352941176470572.026
933982AD1-022 E
Adder
7.9164705882352956.729
3145946PLYMOUTH TP
Adder
0.540.459
940641AE2-051 C
Adder
26.96705882352941322.922
926785AC1-164_E
50/50
33.18433.184
943471AF1-018 C
Adder
12.15411764705882410.331
3152331SURRY 2
50/50
45.79645.796
316084AB2-161 E
Adder
9.597647058823538.158
943172AE2-346 E
Adder
0.98588235294117640.838
917332KELFORD E
Adder
2.63882352941176462.243
925122AB2-169 E
Adder
9.3470588235294127.945
934522AD1-076 E
Adder
10.4035294117647078.843
940492AE2-034 E
Adder
5.2011764705882364.421
962571AG1-106 C
Adder
4.2647058823529413.625
918492AA1-063AE OP
Adder
6.5082352941176485.532
957871AF2-081 C
Adder
17.5105882352941214.884
3145506HICKORY
Adder
3.83058823529411763.256
946262AF1-291 E
Adder
2.5188235294117652.141
3150651CHESTF6
Adder
32.7305882352941227.821
936591AD2-074 C
Adder
8.77.395
3130536PAPERMILL
Adder
11.342352941176479.641
939602AE1-190 E
Adder
2.40470588235294122.044
933292AC2-141 E
Adder
23.1894117647058819.711
934576AD1-082 E
Adder
7.6470588235294126.5
944602AF1-125 E
Adder
180.73058823529414153.621
943612AF1-032 E
Adder
1.61764705882352941.375
961942AG1-037 E
Adder
0.54705882352941180.465
961941AG1-037 C
Adder
0.82117647058823530.698
923852AB2-025 E
Adder
1.84117647058823521.565
941031AE2-094 C
Adder
59.2294117647058850.345
941032AE2-094 E
Adder
26.52705882352941222.548
3150831SPRUNCA
Adder
15.77411764705882313.408
3150841SPRUNCB
Adder
15.77411764705882313.408
966872AG1-558 E
Adder
2.0552941176470591.747
966871AG1-558 C
Adder
4.083.468
316076AC2-137 E
50/50
2.4242.424
316075AC2-137 C
50/50
0.6870.687
923842AB2-024 E
Adder
3.07294117647058852.612
316157AD2-030 E
Adder
1.99764705882352931.698
939412AE1-173 E
Adder
97.132941176470682.563
926662AC1-147 E
Adder
2.34000000000000031.989
916192Z1-068 E
Adder
3.3141176470588242.817
957492AF2-043 E
Adder
2.48941176470588272.116
926072AC1-086 E
Adder
15.0047058823529412.754
960081AF2-299 C
Adder
2.92.465
3145413WATKINS
Adder
1.15882352941176480.985
938771AE1-103 C
Adder
4.9776470588235294.231
963041AG1-153 C
Adder
8.37.055
944011AF1-069 C
Adder
19.35294117647058716.45
3150621CHESTS7
50/50
3.183.18
3150601CHESTF5
50/50
113.923113.923
925332AB2-190 E
Adder
14.35882352941176512.205
962962AG1-145 E
50/50
2.6282.628
927226AC1-216 E
Adder
13.74117647058823411.68
944591AF1-124 C
Adder
80.4682352941176568.398
944601AF1-125 C
Adder
78.9482352941176467.106
941591AE2-156 C
Adder
31.63647058823529426.891
936666AD2-085 E
Adder
9.7729411764705898.307
901082W1-029 E
Adder
55.2529411764705946.965
3143316POE
Adder
2.31058823529411761.964
939191AE1-149 C
Adder
18.59882352941176415.809
934146AD1-041 E
Adder
6.0129411764705885.111
957601AF2-054 C
Adder
3.56117647058823563.027
316382AG1-145 C
50/50
0.6420.642
3137643SOCKMAN
Adder
1.1117647058823530.945
913392Y1-086 E
Adder
3.8282352941176473.254
940432AE2-027 E
Adder
15.04705882352941212.79
316312AB1-027 C
50/50
0.9560.956
939612AE1-191 E
Adder
9.628.177
957602AF2-054 E
Adder
2.37411764705882342.018
939411AE1-173 C
Adder
145.69882352941175123.844
934012AD1-025 E
Adder
17.78941176470588215.121
924814AB2-134 E
Adder
22.5082352941176519.132
942342AE2-247 E
Adder
3.58470588235294143.047
946282AF1-292 E
Adder
1.61.36
944012AF1-069 E
Adder
7.5176470588235296.39
3150631CHESTG8
50/50
6.8166.816
3150611CHESTG7
50/50
6.9276.927
961952AG1-038 E
Adder
6.9482352941176475.906
961951AG1-038 C
Adder
5.0317647058823534.277
925865AC1-065 E
Adder
28.22117647058823723.988
934501AD1-074 C
Adder
56.2023529411764747.772
924517AB2-100 E2
Adder
4.5505882352941183.868
937226AE2-253 E
Adder
10.2482352941176478.711
942001AE2-212 C
Adder
3.73647058823529443.176
3150671DARBY 1
50/50
4.5674.567
3150641CHESTS8
50/50
3.5093.509
939192AE1-149 E
Adder
12.39882352941176410.539
943741AF1-042 C
Adder
4.5517647058823533.869
939312AE1-162 E
Adder
2.54117647058823562.16
934065AD1-033 E
Adder
8.8270588235294137.503
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.4068.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
156.721156.721
CPLELTFEXP_CPLE->PJM
CLTF
17.60917.609
TVALTFEXP_TVA->PJM
CLTF
12.40612.406
O66PJM->LTFIMP_O-066
CMTX_NF
58.60758.607
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.33484.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.67448.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
9.5679.567
LAGNLTFEXP_LAGN->PJM
CLTF
15.46415.464
NYPJM->LTFIMP_NY
CLTF
4.1384.138
LGEELTFEXP_LGEE->PJM
CLTF
3.3583.358
WECLTFEXP_WEC->PJM
CLTF
1.7271.727
G-007PJM->LTFIMP_G-007
CMTX_NF
9.2239.223
SIGELTFEXP_SIGE->PJM
CLTF
0.620.62

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.04 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4112.5
MW Contribution:2.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957481AF2-042 C
Adder
64.7188235294117655.011
3152191CUNINGD
80/20
17.70617.706
940431AE2-027 C
Adder
18.18117647058823715.454
316294AC1-161 C
80/20
7.7077.707
944581AF1-123 C
80/20
69.29269.292
316185AD1-033 C
80/20
1.8591.859
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
55
934501AD1-074 C
Adder
48.0341176470588340.829
961671AG1-007 C
Adder
1.22941176470588221.045
934621AD1-088 C
Adder
11.2658823529411789.576
942001AE2-212 C
Adder
3.01764705882352932.565
3150641CHESTS8
80/20
2.8432.843
962861AG1-135 C
Adder
7.9105882352941186.724
943741AF1-042 C
Adder
3.87058823529411773.29
960081AF2-299 C
Adder
2.4235294117647062.06
938771AE1-103 C
Adder
4.2458823529411773.609
963041AG1-153 C
Adder
7.0223529411764725.969
944011AF1-069 C
Adder
16.40117647058823613.941
3150621CHESTS7
80/20
2.5762.576
3150601CHESTF5
80/20
92.29692.296
944591AF1-124 C
80/20
69.53869.538
944601AF1-125 C
80/20
68.22568.225
3151101ELIZAR3
80/20
4.9194.919
941591AE2-156 C
80/20
27.25627.256
966621AG1-532 C
Adder
1.81764705882352941.545
316320Y1-086 C
80/20
0.3290.329
316388AE2-253 GEN
80/20
2.9612.961
316159AE1-175 C
80/20
0.6130.613
942341AE2-247 C
Adder
2.21.87
316246AF1-032 C
80/20
0.4270.427
934521AD1-076 C
Adder
17.4447058823529414.828
934511AD1-075 C
Adder
12.00823529411764810.207
316263AC1-034 C
Adder
8.5517647058823547.269
316321Z2-027 C
80/20
0.5420.542
316240AF1-291 C
Adder
3.02705882352941162.573
944641AF1-129 C
Adder
143.61529411764707122.073
3142296MT RD221
80/20
0.180.18
316004AC1-112 C
80/20
0.5060.506
316036AC1-147 C
80/20
0.5590.559
316305AF2-043 C
80/20
0.5230.523
927021AC1-189 C
Adder
11.1482352941176499.476
926071AC1-086 C
Adder
27.76352941176470823.599
946281AF1-292 C
Adder
2.00588235294117641.705
316169AC1-164 GEN
80/20
63.00863.008
3151091ELIZAR2
80/20
4.7734.773
316349AD2-085 C
Adder
5.0752941176470594.314
961941AG1-037 C
Adder
0.69764705882352940.593
934321AD1-056 C
Adder
8.1541176470588246.931
934331AD1-057 C
Adder
4.5482352941176483.866
941031AE2-094 C
Adder
50.196470588235342.667
3150831SPRUNCA
Adder
10.6141176470588259.022
3150841SPRUNCB
Adder
10.6141176470588259.022
966871AG1-558 C
Adder
3.3847058823529412.877
316075AC2-137 C
80/20
0.5730.573
964211AG1-282 C
Adder
2.5270588235294122.148
316369AC1-216 C
80/20
2.3642.364
3151081ELIZAR1
80/20
4.8584.858
316018AA1-139 ULT2
80/20
1.6281.628
3152181CUNINGC
80/20
7.9167.916
944631AF1-128 C
80/20
57.75157.751
933291AC2-141 C
80/20
47.32947.329
3150921YORKTN3
80/20
186.63186.63
3151191GRAVEL3
80/20
3.7583.758
940481AE2-033 C
Adder
21.37647058823529618.17
940541AE2-040 C
Adder
3.7941176470588243.225
927041AC1-191 C
Adder
13.58823529411764911.55
963611AG1-210 C
Adder
0.81058823529411760.689
957831AF2-077 C
80/20
0.4940.494
961611AG1-000B C
80/20
23.84623.846
316375AC2-012 C
80/20
2.0492.049
316072AD1-144 C
80/20
0.4250.425
940551AE2-041 C
Adder
10.3670588235294128.812
943461AF1-017 C
Adder
1.99058823529411751.692
316311AC2-079 C
Adder
8.4682352941176487.198
933981AD1-022 C
Adder
12.41647058823529510.554
938531AE1-072 C
80/20
26.50226.502
3150731STONECA
Adder
9.9858823529411778.488
935161AD1-151 C
80/20
23.75423.754
958161AF2-110 C
80/20
2.042.04
313526AB2-022 C
80/20
0.5630.563
316017AA1-139 ULT1
80/20
1.6281.628
940641AE2-051 C
Adder
23.00823529411764719.557
943471AF1-018 C
Adder
10.3670588235294128.812
3152331SURRY 2
80/20
40.26840.268
3151201GRAVEL4
80/20
3.8063.806
3151211GRAVEL5
80/20
3.7583.758
3151221GRAVEL6
80/20
3.8023.802
316236AE1-162 C
80/20
0.5280.528
316274AC1-208 C
Adder
11.86588235294117810.086
962571AG1-106 C
Adder
3.5905882352941183.052
3151311EDGECMA
Adder
20.00352941176470617.003
957871AF2-081 C
80/20
15.09215.092
3150651CHESTF6
Adder
26.14823529411764722.226
936591AD2-074 C
Adder
7.3964705882352946.287
316033AB2-134 GEN
80/20
3.0983.098
934011AD1-025 C
80/20
3.8313.831
958261AF2-120 C
Adder
8.16.885
939191AE1-149 C
Adder
15.33294117647058713.033
957601AF2-054 C
Adder
3.03647058823529432.581
316382AG1-145 C
80/20
0.5540.554
3151171GRAVELC
80/20
1.2921.292
3150981CHESPKA
80/20
0.6610.661
957861AF2-080 C
Adder
10.1247058823529418.606
3152161CUNINGA
80/20
7.9167.916
3152171CUNINGB
80/20
7.9167.916
3150631CHESTG8
80/20
5.5225.522
3150611CHESTG7
80/20
5.6125.612
961951AG1-038 C
Adder
4.277647058823533.636
3144216WINCHST
80/20
0.2040.204
316316AC1-027 C
80/20
0.4790.479
3137643SOCKMAN
Adder
0.93411764705882360.794
316312AB1-027 C
80/20
0.8120.812
966661AG1-536 C
Adder
6.96705882352941155.922
939411AE1-173 C
Adder
124.68470588235294105.982
3151161SURRY 1
80/20
36.99336.993
3150991CHESPKB
80/20
1.0961.096
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1467.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
133.887133.887
CPLELTFEXP_CPLE->PJM
CLTF
14.96914.969
TVALTFEXP_TVA->PJM
CLTF
10.74810.748
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.17274.172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.32542.325
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.3698.369
LAGNLTFEXP_LAGN->PJM
CLTF
13.38813.388
NYPJM->LTFIMP_NY
CLTF
3.5973.597
LGEELTFEXP_LGEE->PJM
CLTF
2.952.95
WECLTFEXP_WEC->PJM
CLTF
1.5171.517
SIGELTFEXP_SIGE->PJM
CLTF
0.5440.544

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.93 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4252.57
MW Contribution:2.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961942AG1-037 E
Adder
0.290588235294117650.247
961941AG1-037 C
Adder
0.435294117647058830.37
923852AB2-025 E
Adder
0.98705882352941180.839
923862AB2-026 E
Adder
1.02941176470588250.875
941031AE2-094 C
Adder
31.94588235294117627.154
941032AE2-094 E
Adder
14.3082352941176512.162
3150831SPRUNCA
Adder
8.5294117647058827.25
3150841SPRUNCB
Adder
8.5294117647058827.25
966872AG1-558 E
Adder
1.1317647058823530.962
966871AG1-558 C
Adder
2.24588235294117671.909
316076AC2-137 E
50/50
1.2591.259
316075AC2-137 C
50/50
0.3570.357
923842AB2-024 E
Adder
1.61176470588235321.37
316157AD2-030 E
Adder
1.05647058823529430.898
939412AE1-173 E
Adder
51.40235294117647443.692
926662AC1-147 E
Adder
1.2117647058823531.03
916192Z1-068 E
Adder
1.71529411764705891.458
957492AF2-043 E
Adder
1.29176470588235311.098
943172AE2-346 E
Adder
0.52235294117647060.444
934522AD1-076 E
Adder
5.4705882352941194.65
940492AE2-034 E
Adder
2.72588235294117662.317
918492AA1-063AE OP
Adder
3.47058823529411782.95
957871AF2-081 C
Adder
9.0741176470588247.713
3145506HICKORY
Adder
1.98352941176470581.686
946262AF1-291 E
Adder
1.34470588235294121.143
3150651CHESTF6
Adder
17.46352941176470714.844
3150461FOUR RIVERD
50/50
2.9592.959
3150441FOUR RIVERB
50/50
3.0033.003
936591AD2-074 C
Adder
4.7717647058823534.056
3130536PAPERMILL
Adder
5.95411764705882355.061
939602AE1-190 E
Adder
1.27058823529411781.08
933292AC2-141 E
Adder
11.89764705882352810.113
934576AD1-082 E
Adder
4.0317647058823533.427
944602AF1-125 E
Adder
93.4294117647058979.415
943612AF1-032 E
Adder
0.840.714
960081AF2-299 C
Adder
1.56117647058823541.327
3145413WATKINS
Adder
0.60941176470588240.518
938771AE1-103 C
Adder
2.60941176470588232.218
963041AG1-153 C
Adder
4.4858823529411773.813
944011AF1-069 C
Adder
10.437647058823538.872
966881AG1-559 C
50/50
2.2942.294
3150601CHESTF5
Adder
59.7211764705882350.763
925332AB2-190 E
Adder
7.537647058823536.407
962962AG1-145 E
Adder
1.34588235294117631.144
927226AC1-216 E
Adder
7.19176470588235356.113
944591AF1-124 C
Adder
41.5988235294117735.359
944601AF1-125 C
Adder
40.81294117647059534.691
941591AE2-156 C
Adder
16.3729411764705913.917
936666AD2-085 E
Adder
5.11411764705882454.347
913392Y1-086 E
Adder
1.9870588235294121.689
933502AC2-165 E
Adder
6.177647058823535.251
940432AE2-027 E
Adder
8.0188235294117656.816
316312AB1-027 C
50/50
0.5020.502
939612AE1-191 E
Adder
5.0823529411764714.32
957602AF2-054 E
Adder
1.2552941176470591.067
939411AE1-173 C
Adder
77.103529411764765.538
934012AD1-025 E
Adder
9.3117647058823547.915
934521AD1-076 C
Adder
10.7329411764705889.123
934511AD1-075 C
Adder
7.38823529411764756.28
3145723EMPORIA
Adder
0.360.306
920042AA2-088 E OP
Adder
9.2247058823529417.841
919152AA1-139 E1
Adder
3.71058823529411753.154
316240AF1-291 C
Adder
2.01647058823529421.714
944641AF1-129 C
Adder
95.9141176470588381.527
3150451FOUR RIVERC
50/50
3.6693.669
3142296MT RD221
50/50
0.1170.117
316004AC1-112 C
50/50
0.3130.313
924814AB2-134 E
Adder
11.78117647058823510.014
942342AE2-247 E
Adder
1.87647058823529411.595
901082W1-029 E
Adder
28.74235294117647424.431
3143316POE
Adder
1.23411764705882351.049
939191AE1-149 C
Adder
9.8564705882352958.378
934146AD1-041 E
Adder
3.17647058823529442.7
957601AF2-054 C
Adder
1.8835294117647061.601
918512AA1-065 E OP
Adder
4.7847058823529424.067
934502AD1-074 E
Adder
15.04470588235294112.788
934512AD1-075 E
Adder
3.76117647058823533.197
924516AB2-100 E1
Adder
2.4388235294117652.073
966621AG1-532 C
Adder
1.17058823529411770.995
919153AA1-139 E2
Adder
3.71058823529411753.154
226704AOCX4-046 E
Adder
-2.8423529411764705-2.416
3152261N ANNA2
50/50
28.62228.622
940642AE2-051 E
Adder
9.5882352941176498.15
926412AC1-112 E
50/50
1.0751.075
942341AE2-247 C
Adder
1.35882352941176481.155
943462AF1-017 E
Adder
2.00588235294117641.705
958162AF2-110 E
Adder
1.97411764705882351.678
946282AF1-292 E
Adder
0.86117647058823530.732
944012AF1-069 E
Adder
4.0552941176470593.447
939262AE1-157 E
Adder
7.2070588235294136.126
3150431FOUR RIVERA
50/50
3.0033.003
961952AG1-038 E
Adder
3.81058823529411763.239
961951AG1-038 C
Adder
2.7588235294117652.345
925865AC1-065 E
Adder
14.8929411764705912.659
946281AF1-292 C
Adder
1.29176470588235311.098
960082AF2-299 E
Adder
1.040.884
916042Z1-036 E
Adder
25.53647058823529321.706
923832AB2-022 E
Adder
1.12235294117647060.954
938772AE1-103 E
Adder
3.60352941176470633.063
963042AG1-153 E
Adder
6.7294117647058825.72
939261AE1-157 C
Adder
13.28588235294117611.293
966882AG1-559 E
50/50
1.1551.155
930122AB1-027 E
50/50
1.3221.322
316169AC1-164 GEN
Adder
37.8729411764705932.192
944592AF1-124 E
Adder
95.2635294117647180.974
944582AF1-123 E
Adder
94.9280.682
316349AD2-085 C
Adder
3.13411764705882372.664
935112AD1-144 E
Adder
0.86117647058823530.732
934501AD1-074 C
Adder
29.5529411764705925.12
924517AB2-100 E2
Adder
2.4388235294117652.073
937226AE2-253 E
Adder
5.30941176470588254.513
226896D-009
Adder
-1.4576470588235295-1.239
958502AF2-144 E
Adder
1.0117647058823530.86
942001AE2-212 C
Adder
1.99647058823529421.697
3150671DARBY 1
50/50
2.4232.423
962861AG1-135 C
Adder
5.1564705882352944.383
939192AE1-149 E
Adder
6.5717647058823535.586
943741AF1-042 C
Adder
2.4964705882352942.122
939312AE1-162 E
Adder
1.31882352941176471.121
934065AD1-033 E
Adder
4.5682352941176473.883
940481AE2-033 C
Adder
13.74117647058823411.68
940482AE2-033 E
Adder
9.2635294117647067.874
940541AE2-040 C
Adder
2.442.074
927041AC1-191 C
Adder
9.0164705882352937.664
3138116ELKO L286
50/50
1.3131.313
961611AG1-000B C
Adder
14.76705882352941212.552
957872AF2-081 E
Adder
3.88941176470588263.306
938562AE1-075 E
Adder
0.87764705882352940.746
3152251N ANNA1
50/50
28.6128.61
938552AE1-074 E
Adder
1.13294117647058810.963
3150471FOUR RIVERE
50/50
2.9592.959
315052AA1-145 CT2
50/50
4.7814.781
944631AF1-128 C
Adder
37.3682352941176531.763
936592AD2-074 E
Adder
7.7847058823529426.617
316160AE1-175 E
Adder
1.11058823529411770.944
926755AC1-161 E
Adder
11.89764705882352810.113
933291AC2-141 C
Adder
27.87176470588235223.691
3150921YORKTN3
Adder
110.8188235294117694.196
925522AC1-027 E
Adder
1.11058823529411770.944
941102AE2-104 E
Adder
4.8364705882352944.111
3145256KINGFORK
Adder
0.92823529411764720.789
316141AB2-099 E
Adder
0.217647058823529420.185
923994AB2-040_E
Adder
1.6270588235294121.383
316088AB2-174 E
Adder
5.4517647058823534.634
942002AE2-212 E
Adder
1.33058823529411761.131
940431AE2-027 C
Adder
12.02823529411764810.224
3150681DARBY 2
50/50
2.4262.426
962862AG1-135 E
Adder
3.43764705882352972.922
943742AF1-042 E
Adder
4.07294117647058853.462
934392AD1-063 E
Adder
0.960.816
944581AF1-123 C
Adder
41.45176470588235435.234
941101AE2-104 C
Adder
3.04235294117647072.586
933981AD1-022 C
Adder
7.6564705882352946.508
900672V4-068 E
Adder
0.308235294117647050.262
938531AE1-072 C
Adder
15.94470588235294213.553
3145393UNCAMP
Adder
5.3964705882352944.587
315051AA1-145 CT1
50/50
4.7834.783
3142366NRTHEST
50/50
0.1760.176
3150701DARBY 4
50/50
2.4382.438
3150731STONECA
Adder
6.46823529411764755.498
935161AD1-151 C
Adder
15.04823529411764812.791
932046AC2-012 E
Adder
11.9823529411764710.185
958161AF2-110 C
Adder
1.24117647058823531.055
920692AA2-178 E
Adder
3.6352941176470593.09
966622AG1-532 E
Adder
0.780.663
917122Z2-027 E
Adder
1.21294117647058821.031
3146326AYDLETT TAP
Adder
1.22941176470588221.045
938532AE1-072 E
Adder
8.3117647058823547.065
316233AE1-074 C
Adder
2.25058823529411761.913
927042AC1-191 E
Adder
4.4917647058823533.818
3150691DARBY 3
50/50
2.4352.435
940551AE2-041 C
Adder
6.3964705882352955.437
935162AD1-151 E
Adder
10.0317647058823528.527
957832AF2-077 E
Adder
1.29764705882352941.103
943461AF1-017 C
Adder
1.22941176470588221.045
316311AC2-079 C
Adder
5.2200000000000014.437
932596AC2-079 E
Adder
8.517647058823537.24
933982AD1-022 E
Adder
4.1682352941176483.543
3145946PLYMOUTH TP
Adder
0.283529411764705860.241
316336AC2-165 C
Adder
8.2082352941176486.977
3150481FOUR RIVERF
50/50
3.6143.614
940641AE2-051 C
Adder
14.38235294117647112.225
926785AC1-164_E
Adder
17.0152941176470614.463
943471AF1-018 C
Adder
6.3964705882352955.437
316084AB2-161 E
Adder
5.06000000000000054.301
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.6074.607
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.84786.847
CPLELTFEXP_CPLE->PJM
CLTF
9.659.65
TVALTFEXP_TVA->PJM
CLTF
7.1437.143
O66PJM->LTFIMP_O-066
CMTX_NF
44.79944.799
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.34851.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.44428.444
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.7125.712
LAGNLTFEXP_LAGN->PJM
CLTF
8.98.9
NYPJM->LTFIMP_NY
CLTF
3.113.11
LGEELTFEXP_LGEE->PJM
CLTF
2.0262.026
WECLTFEXP_WEC->PJM
CLTF
1.0481.048
G-007PJM->LTFIMP_G-007
CMTX_NF
7.0597.059
SIGELTFEXP_SIGE->PJM
CLTF
0.3720.372

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.32 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3230.79
MW Contribution:1.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
957481AF2-042 C
Adder
40.39647058823529634.337
3150401LDYSMT4
80/20
4.4254.425
940431AE2-027 C
Adder
11.5988235294117659.859
3150681DARBY 2
80/20
2.3542.354
944581AF1-123 C
Adder
39.80941176470588533.838
941101AE2-104 C
Adder
2.92000000000000042.482
934501AD1-074 C
Adder
28.28352941176470724.041
934621AD1-088 C
Adder
7.1611764705882356.087
942001AE2-212 C
Adder
1.92117647058823531.633
3150671DARBY 1
80/20
2.3512.351
3150641CHESTS8
80/20
1.7811.781
962861AG1-135 C
Adder
5.0788235294117654.317
943741AF1-042 C
Adder
2.45411764705882352.086
960081AF2-299 C
Adder
1.48823529411764691.265
938771AE1-103 C
Adder
2.5011764705882352.126
963041AG1-153 C
Adder
4.2658823529411763.626
944011AF1-069 C
Adder
9.9305882352941198.441
966881AG1-559 C
80/20
2.2882.288
3150621CHESTS7
80/20
1.6141.614
3150601CHESTF5
80/20
57.83757.837
944591AF1-124 C
Adder
39.9505882352941233.958
944601AF1-125 C
Adder
39.1964705882352933.317
941591AE2-156 C
Adder
15.7305882352941213.371
966621AG1-532 C
Adder
1.1164705882352940.949
3152261N ANNA2
80/20
26.0926.09
942341AE2-247 C
Adder
1.30470588235294121.109
934521AD1-076 C
Adder
10.2717647058823538.731
934511AD1-075 C
Adder
7.0705882352941176.01
3150411LDYSMT5
80/20
4.4394.439
316240AF1-291 C
Adder
1.94470588235294131.653
944641AF1-129 C
Adder
92.5282352941176578.649
3150451FOUR RIVERC
80/20
3.6073.607
3142296MT RD221
80/20
0.1140.114
316004AC1-112 C
80/20
0.3050.305
926071AC1-086 C
Adder
16.83294117647058714.308
946281AF1-292 C
Adder
1.23176470588235291.047
939261AE1-157 C
80/20
13.3213.32
316169AC1-164 GEN
80/20
36.80636.806
316349AD2-085 C
Adder
3.0105882352941182.559
961941AG1-037 C
Adder
0.41529411764705880.353
941031AE2-094 C
Adder
30.39411764705882425.835
3150391LDYSMT3
80/20
4.4174.417
3150831SPRUNCA
80/20
8.2198.219
3150841SPRUNCB
Adder
8.2188235294117656.986
966871AG1-558 C
80/20
2.1962.196
316075AC2-137 C
80/20
0.3470.347
964211AG1-282 C
Adder
1.65294117647058841.405
3152251N ANNA1
80/20
26.07926.079
3150471FOUR RIVERE
80/20
2.9092.909
315052AA1-145 CT2
80/20
4.74.7
3150851SPRUNCC
80/20
0.1470.147
944631AF1-128 C
80/20
36.1936.19
933291AC2-141 C
Adder
26.7822.763
3150921YORKTN3
Adder
107.0694117647058991.009
940481AE2-033 C
Adder
13.13529411764705811.165
940541AE2-040 C
Adder
2.33294117647058831.983
3150371LDYSMT1
80/20
4.2494.249
927041AC1-191 C
80/20
8.8178.817
963611AG1-210 C
Adder
0.53882352941176470.458
961611AG1-000B C
Adder
14.23176470588235412.097
3150381LDYSMT2
80/20
4.3034.303
316233AE1-074 C
Adder
2.1552941176470591.832
3150691DARBY 3
80/20
2.3622.362
940551AE2-041 C
Adder
6.2364705882352955.301
943461AF1-017 C
Adder
1.18117647058823531.004
316311AC2-079 C
Adder
5.0141176470588234.262
933981AD1-022 C
Adder
7.3258823529411776.227
938531AE1-072 C
Adder
15.30823529411764713.012
315051AA1-145 CT1
80/20
4.7034.703
3142366NRTHEST
80/20
0.1710.171
3150701DARBY 4
80/20
2.3652.365
3150731STONECA
Adder
6.2458823529411775.309
935161AD1-151 C
Adder
14.5176470588235312.34
958161AF2-110 C
Adder
1.19176470588235281.013
316336AC2-165 C
Adder
7.7411764705882356.58
3150481FOUR RIVERF
80/20
3.5533.553
940641AE2-051 C
Adder
13.71529411764705811.658
943471AF1-018 C
Adder
6.2364705882352955.301
962571AG1-106 C
Adder
2.17764705882352951.851
957871AF2-081 C
Adder
8.7129411764705887.406
3150651CHESTF6
Adder
16.84705882352941214.32
3150461FOUR RIVERD
80/20
2.9092.909
3150441FOUR RIVERB
80/20
2.9522.952
3150861SPRUNCD
80/20
0.1470.147
936591AD2-074 C
Adder
4.6894117647058823.986
3143096IRON208
80/20
0.4040.404
958261AF2-120 C
Adder
5.2200000000000014.437
939191AE1-149 C
Adder
9.4788235294117668.057
957601AF2-054 C
Adder
1.83764705882352961.562
3150431FOUR RIVERA
80/20
2.9522.952
3150631CHESTG8
80/20
3.4613.461
3150611CHESTG7
80/20
3.5173.517
3137643SOCKMAN
Adder
0.56941176470588240.484
316312AB1-027 C
80/20
0.4890.489
966661AG1-536 C
Adder
4.4905882352941183.817
939411AE1-173 C
Adder
73.6611764705882562.612
961951AG1-038 C
Adder
2.7117647058823532.305
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.3484.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.51781.517
CPLELTFEXP_CPLE->PJM
CLTF
9.1099.109
TVALTFEXP_TVA->PJM
CLTF
6.5746.574
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.86545.865
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.97725.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.1595.159
LAGNLTFEXP_LAGN->PJM
CLTF
8.1928.192
NYPJM->LTFIMP_NY
CLTF
2.8322.832
LGEELTFEXP_LGEE->PJM
CLTF
1.8211.821
WECLTFEXP_WEC->PJM
CLTF
0.9380.938
SIGELTFEXP_SIGE->PJM
CLTF
0.3350.335

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.82 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3858.59
MW Contribution:2.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.74470588235294120.633
934321AD1-056 C
Adder
9.0458823529411777.689
934331AD1-057 C
Adder
5.04588235294117654.289
958211AF2-115 C
Adder
3.0058823529411772.555
3151531CLOVER1
80/20
18.57418.574
316258AE1-075 C
80/20
0.5130.513
941031AE2-094 C
80/20
63.15563.155
3150831SPRUNCA
80/20
13.15813.158
3150841SPRUNCB
80/20
13.15813.158
3151081ELIZAR1
80/20
4.824.82
316365AB2-100 C1
80/20
1.4231.423
957481AF2-042 C
80/20
80.37380.373
940431AE2-027 C
Adder
18.39647058823529615.637
316294AC1-161 C
80/20
7.5057.505
944581AF1-123 C
80/20
68.97668.976
316185AD1-033 C
80/20
1.8511.851
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
5.0455.045
934501AD1-074 C
Adder
50.0317647058823542.527
961671AG1-007 C
Adder
1.34941176470588231.147
3156116Z1-036WIND
80/20
0.9810.981
946301AF1-294 C
Adder
4.9423529411764714.201
942461AE2-259 C
Adder
12.99058823529411711.042
934621AD1-088 C
80/20
14.01914.019
942001AE2-212 C
80/20
3.1513.151
934521AD1-076 C
Adder
18.1705882352941215.445
934511AD1-075 C
Adder
12.50823529411764710.632
316263AC1-034 C
Adder
9.488.058
316321Z2-027 C
80/20
0.5460.546
959311AF2-222 C
Adder
22.66470588235294419.265
3151031BRUNSWICKG2
80/20
12.91412.914
316240AF1-291 C
Adder
3.0682352941176472.608
944641AF1-129 C
Adder
144.29529411764705122.651
316036AC1-147 C
80/20
0.5540.554
316305AF2-043 C
80/20
0.5240.524
960081AF2-299 C
Adder
2.74941176470588242.337
936261AD2-033 C
Adder
17.81058823529411615.139
961791AG1-021 C
Adder
2.40470588235294122.044
938771AE1-103 C
80/20
4.3814.381
963041AG1-153 C
80/20
8.7798.779
3151051BRUNSWICKS1
80/20
26.8326.83
944011AF1-069 C
80/20
20.63520.635
3150601CHESTF5
Adder
83.0647058823529570.605
944591AF1-124 C
80/20
69.22169.221
944601AF1-125 C
80/20
67.91467.914
3151101ELIZAR3
80/20
4.8814.881
941591AE2-156 C
80/20
27.03327.033
927021AC1-189 C
Adder
12.14117647058823710.32
926071AC1-086 C
Adder
30.83882352941176626.213
946281AF1-292 C
Adder
2.2752941176470591.934
964241AG1-285 C
Adder
17.31176470588235414.715
962561AG1-105 C
Adder
12.25882352941176610.42
316169AC1-164 GEN
Adder
49.0282352941176541.674
3151091ELIZAR2
80/20
4.7354.735
316349AD2-085 C
80/20
5.1625.162
966621AG1-532 C
Adder
2.06235294117647071.753
316320Y1-086 C
80/20
0.330.33
316388AE2-253 GEN
80/20
2.9552.955
3151021BRUNSWICKG1
80/20
12.91412.914
3151041BRUNSWICKG3
80/20
12.91412.914
942341AE2-247 C
80/20
2.2382.238
316246AF1-032 C
80/20
0.4280.428
316274AC1-208 C
Adder
13.08588235294117711.123
962571AG1-106 C
Adder
3.98941176470588273.391
3151311EDGECMA
Adder
22.1658823529411818.841
957871AF2-081 C
80/20
15.07515.075
316405AF2-144 C
80/20
0.4360.436
3150651CHESTF6
Adder
26.27176470588235422.331
3150861SPRUNCD
80/20
0.2360.236
316018AA1-139 ULT2
80/20
1.6261.626
3150851SPRUNCC
80/20
0.2360.236
944631AF1-128 C
Adder
51.9752941176470644.179
933291AC2-141 C
80/20
46.08646.086
3150921YORKTN3
Adder
165.5670588235294140.732
3151191GRAVEL3
80/20
3.6113.611
3137643SOCKMAN
Adder
1.04352941176470580.887
939411AE1-173 C
80/20
143.49143.49
316381AD1-082 C
80/20
1.8751.875
3151161SURRY 1
80/20
35.54335.543
3150991CHESPKB
80/20
1.0871.087
940481AE2-033 C
80/20
24.49624.496
940541AE2-040 C
80/20
4.3564.356
3152441Z1-086 ST
80/20
28.79528.795
961611AG1-000B C
Adder
22.90588235294117719.47
316375AC2-012 C
80/20
2.0322.032
316072AD1-144 C
80/20
0.4180.418
3156056W1-029WIND
80/20
1.1641.164
3152411Z1-086 GT1
80/20
16.54216.542
3152421Z1-086 GT2
80/20
16.53816.538
316233AE1-074 C
80/20
3.9163.916
940551AE2-041 C
Adder
8.4917647058823537.218
943461AF1-017 C
80/20
2.0242.024
316311AC2-079 C
80/20
8.6058.605
933981AD1-022 C
Adder
12.98823529411764711.04
938531AE1-072 C
80/20
26.49826.498
3150731STONECA
Adder
9.5788235294117648.142
935161AD1-151 C
Adder
22.80117647058823519.381
316083AB2-161 C
80/20
0.8230.823
958161AF2-110 C
80/20
2.0582.058
313526AB2-022 C
80/20
0.5650.565
316017AA1-139 ULT1
80/20
1.6261.626
3152431Z1-086 GT3
80/20
16.53816.538
316336AC2-165 C
Adder
14.04941176470588411.942
940641AE2-051 C
80/20
27.74527.745
943471AF1-018 C
Adder
8.4917647058823537.218
3152331SURRY 2
80/20
35.95635.956
3151201GRAVEL4
80/20
3.6573.657
3151211GRAVEL5
80/20
3.6113.611
3151221GRAVEL6
80/20
3.6533.653
316236AE1-162 C
80/20
0.5140.514
964791AG1-342 C
Adder
4.884.148
316313AB2-026 C
80/20
0.5590.559
939191AE1-149 C
80/20
15.94215.942
957601AF2-054 C
Adder
2.53058823529411742.151
3150981CHESPKA
80/20
0.6560.656
957861AF2-080 C
Adder
11.0270588235294129.373
316023AB2-100 C2
80/20
1.4231.423
316315AB2-025 C
80/20
0.6170.617
3138533PONTONDP
Adder
0.89058823529411770.757
3151541CLOVER2
80/20
18.418.4
316316AC1-027 C
80/20
0.4760.476
316303AF2-085
80/20
6.4786.478
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.9747.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
144.491144.491
CPLELTFEXP_CPLE->PJM
CLTF
16.71416.714
TVALTFEXP_TVA->PJM
CLTF
10.46710.467
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.12565.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.22440.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6237.623
LAGNLTFEXP_LAGN->PJM
CLTF
13.13513.135
NYPJM->LTFIMP_NY
CLTF
3.1863.186
LGEELTFEXP_LGEE->PJM
CLTF
2.5932.593
WECLTFEXP_WEC->PJM
CLTF
1.3381.338
SIGELTFEXP_SIGE->PJM
CLTF
0.4870.487

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.79 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4641.11
MW Contribution:4.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316141AB2-099 E
Adder
0.37647058823529410.32
923994AB2-040_E
Adder
9.1117647058823537.745
316088AB2-174 E
Adder
9.6611764705882348.212
957481AF2-042 C
Adder
80.9247058823529468.786
942002AE2-212 E
Adder
2.13058823529411741.811
940431AE2-027 C
Adder
18.6823529411764715.88
316294AC1-161 C
50/50
7.5867.586
944581AF1-123 C
50/50
69.72769.727
316185AD1-033 C
50/50
1.8711.871
916191Z1-068 C
50/50
0.0670.067
941101AE2-104 C
Adder
5.1011764705882364.336
934501AD1-074 C
Adder
50.5435294117647142.962
924517AB2-100 E2
Adder
4.3447058823529413.693
937226AE2-253 E
Adder
8.9129411764705877.576
934621AD1-088 C
Adder
14.11647058823529511.999
957482AF2-042 E
Adder
53.94941176470588645.857
958502AF2-144 E
Adder
1.81.53
942001AE2-212 C
Adder
3.19647058823529442.717
939192AE1-149 E
Adder
10.7658823529411769.151
939312AE1-162 E
Adder
2.13058823529411741.811
934065AD1-033 E
50/50
7.6627.662
961942AG1-037 E
Adder
0.50117647058823530.426
961941AG1-037 C
Adder
0.7517647058823530.639
923852AB2-025 E
50/50
1.7791.779
923862AB2-026 E
Adder
1.8317647058823531.557
941031AE2-094 C
50/50
63.56663.566
941032AE2-094 E
50/50
28.4728.47
3150831SPRUNCA
Adder
13.36352941176470611.359
3150841SPRUNCB
Adder
13.36352941176470611.359
939412AE1-173 E
50/50
96.42796.427
3151081ELIZAR1
50/50
4.8744.874
926662AC1-147 E
Adder
2.02235294117647071.719
916192Z1-068 E
50/50
2.8712.871
957492AF2-043 E
Adder
2.16705882352941171.842
918512AA1-065 E OP
Adder
8.2458823529411777.009
962572AG1-106 E
Adder
1.76117647058823561.497
957872AF2-081 E
Adder
6.53176470588235255.552
938562AE1-075 E
Adder
1.56235294117647071.328
938552AE1-074 E
50/50
1.9951.995
926755AC1-161 E
50/50
19.88619.886
933291AC2-141 C
50/50
46.58646.586
3150921YORKTN3
Adder
168.0623529411765142.853
925522AC1-027 E
50/50
1.8591.859
923263AB1-132 E OP
Adder
9.0588235294117647.7
940481AE2-033 C
50/50
24.72924.729
940482AE2-033 E
50/50
16.67116.671
940541AE2-040 C
50/50
4.3984.398
3152441Z1-086 ST
50/50
28.98428.984
961611AG1-000B C
Adder
23.2270588235294119.743
316375AC2-012 C
50/50
2.0552.055
920692AA2-178 E
Adder
6.19058823529411755.262
966622AG1-532 E
Adder
1.3870588235294121.179
917122Z2-027 E
Adder
2.04352941176470631.737
3146326AYDLETT TAP
Adder
2.06705882352941161.757
938532AE1-072 E
Adder
13.96470588235294111.87
3152411Z1-086 GT1
50/50
16.65116.651
3152421Z1-086 GT2
50/50
16.64616.646
316233AE1-074 C
50/50
3.9613.961
935162AD1-151 E
Adder
15.43176470588235513.117
943461AF1-017 C
Adder
2.0482352941176471.741
316311AC2-079 C
Adder
8.7047058823529427.399
932596AC2-079 E
Adder
14.20352941176470712.073
933981AD1-022 C
Adder
13.12117647058823711.153
900672V4-068 E
Adder
0.53294117647058830.453
938531AE1-072 C
Adder
26.78823529411764822.77
3145393UNCAMP
Adder
9.1811764705882367.804
3150731STONECA
Adder
9.735294117647068.275
935161AD1-151 C
Adder
23.14823529411764719.676
932046AC2-012 E
50/50
20.00120.001
958161AF2-110 C
Adder
2.0811764705882351.769
933982AD1-022 E
Adder
7.1423529411764716.071
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
934612AD1-087 E
Adder
5.3305882352941174.531
934622AD1-088 E
Adder
6.79647058823529455.777
3152431Z1-086 GT3
50/50
16.64616.646
316336AC2-165 C
Adder
5.537647058823534.707
940641AE2-051 C
50/50
27.94427.944
316084AB2-161 E
Adder
8.3482352941176477.096
943172AE2-346 E
Adder
0.90235294117647060.767
934522AD1-076 E
Adder
9.3564705882352957.953
940492AE2-034 E
Adder
4.6423529411764713.946
962571AG1-106 C
Adder
4.0258823529411773.422
918492AA1-063AE OP
Adder
6.065.151
957871AF2-081 C
Adder
15.24000000000000212.954
937482AD2-202 E
Adder
1.561.326
3145506HICKORY
50/50
3.3283.328
946262AF1-291 E
Adder
2.07764705882352941.766
3150651CHESTF6
Adder
26.6976470588235322.693
933292AC2-141 E
50/50
19.88619.886
934576AD1-082 E
Adder
6.6517647058823535.654
944602AF1-125 E
50/50
157.162157.162
943612AF1-032 E
Adder
1.40941176470588241.198
926072AC1-086 E
Adder
14.16705882352941312.042
960081AF2-299 C
Adder
2.7741176470588242.358
3145413WATKINS
Adder
1.04117647058823540.885
938771AE1-103 C
Adder
4.4282352941176473.764
963041AG1-153 C
50/50
8.8378.837
3151051BRUNSWICKS1
50/50
27.00627.006
944011AF1-069 C
50/50
20.76920.769
925332AB2-190 E
Adder
11.5352941176470599.805
927226AC1-216 E
Adder
11.1270588235294129.458
944591AF1-124 C
50/50
69.97569.975
944601AF1-125 C
50/50
68.65368.653
3151101ELIZAR3
50/50
4.9354.935
941591AE2-156 C
50/50
27.33727.337
936666AD2-085 E
Adder
8.5211764705882367.243
901082W1-029 E
Adder
48.43294117647058541.168
3143316POE
50/50
2.082.08
939191AE1-149 C
Adder
16.1494117647058813.727
946282AF1-292 E
Adder
1.53058823529411761.301
316315AB2-025 C
50/50
0.6230.623
944012AF1-069 E
50/50
8.0688.068
3137643SOCKMAN
Adder
1.05294117647058830.895
913392Y1-086 E
Adder
3.3447058823529412.843
940432AE2-027 E
Adder
12.45529411764705910.587
939411AE1-173 C
50/50
144.64144.64
934012AD1-025 E
Adder
14.40588235294117712.245
934521AD1-076 C
Adder
18.35647058823529315.603
934511AD1-075 C
Adder
12.6352941176470610.74
919692AA2-053 E OP
Adder
6.2482352941176475.311
923573AB1-173 E OP
Adder
4.8588235294117644.13
3145723EMPORIA
Adder
0.640.544
920042AA2-088 E OP
Adder
15.88941176470588313.506
919152AA1-139 E1
Adder
6.2317647058823535.297
3151031BRUNSWICKG2
50/50
12.99912.999
316240AF1-291 C
Adder
3.11647058823529432.649
944641AF1-129 C
Adder
146.62823529411764124.634
924814AB2-134 E
Adder
18.2270588235294115.493
942342AE2-247 E
Adder
3.12588235294117662.657
934502AD1-074 E
Adder
25.72941176470588321.87
934512AD1-075 E
Adder
6.4317647058823535.467
924516AB2-100 E1
Adder
4.3447058823529413.693
966621AG1-532 C
Adder
2.0811764705882351.769
919153AA1-139 E2
Adder
6.2317647058823535.297
3151021BRUNSWICKG1
50/50
12.99912.999
3151041BRUNSWICKG3
50/50
12.99912.999
940642AE2-051 E
50/50
18.62918.629
942341AE2-247 C
Adder
2.2635294117647061.924
943462AF1-017 E
Adder
3.34117647058823542.84
958162AF2-110 E
Adder
3.31058823529411762.814
316316AC1-027 C
50/50
0.4810.481
926071AC1-086 C
Adder
31.12823529411764826.459
946281AF1-292 C
Adder
2.2964705882352941.952
960082AF2-299 E
Adder
1.84941176470588251.572
916042Z1-036 E
Adder
43.2517647058823636.764
923832AB2-022 E
Adder
1.8882352941176471.605
938772AE1-103 E
Adder
6.115294117647065.198
963042AG1-153 E
50/50
13.25613.256
944592AF1-124 E
50/50
160.246160.246
944582AF1-123 E
50/50
159.668159.668
3151091ELIZAR2
50/50
4.7894.789
316349AD2-085 C
Adder
5.2223529411764714.439
935112AD1-144 E
Adder
1.42000000000000021.207
941102AE2-104 E
Adder
8.1105882352941186.894
3145256KINGFORK
Adder
1.52941176470588251.3
316303AF2-085
50/50
6.5316.531
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.0368.036
CBM South 2LTFEXP_CBM-S2->PJM
CBM
145.599145.599
CPLELTFEXP_CPLE->PJM
CLTF
16.84316.843
TVALTFEXP_TVA->PJM
CLTF
10.54210.542
O66PJM->LTFIMP_O-066
CMTX_NF
45.24145.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.46965.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.49440.494
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6697.669
LAGNLTFEXP_LAGN->PJM
CLTF
13.22813.228
NYPJM->LTFIMP_NY
CLTF
3.2313.231
LGEELTFEXP_LGEE->PJM
CLTF
2.6092.609
WECLTFEXP_WEC->PJM
CLTF
1.3461.346
G-007PJM->LTFIMP_G-007
CMTX_NF
7.1157.115
SIGELTFEXP_SIGE->PJM
CLTF
0.490.49

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.38 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3586.78
MW Contribution:1.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.37294117647058830.317
934321AD1-056 C
Adder
4.7070588235294134.001
934331AD1-057 C
Adder
2.6258823529411772.232
958211AF2-115 C
80/20
1.7961.796
3151531CLOVER1
80/20
10.82910.829
208900BRIS G1
80/20
-2.405-2.405
3151761LOISA E
80/20
6.8276.827
3151771S ANNAG1
80/20
3.2623.262
3151791S ANNAG2
80/20
3.2623.262
3151781S ANNAS1
80/20
1.6761.676
316258AE1-075 C
80/20
0.320.32
941031AE2-094 C
80/20
37.11337.113
316365AB2-100 C1
80/20
0.7450.745
957481AF2-042 C
80/20
47.06247.062
3151801S ANNAS2
80/20
1.6761.676
944581AF1-123 C
Adder
32.0470588235294127.24
941101AE2-104 C
Adder
2.35411764705882342.001
934501AD1-074 C
Adder
24.38588235294117720.728
961671AG1-007 C
Adder
0.69647058823529410.592
946301AF1-294 C
80/20
2.9542.954
942461AE2-259 C
80/20
7.9867.986
934621AD1-088 C
80/20
8.2538.253
208901BRIS G2
80/20
-2.846-2.846
316192AB2-158 C
80/20
4.3254.325
942001AE2-212 C
Adder
1.40235294117647061.192
934521AD1-076 C
Adder
8.8564705882352937.528
934511AD1-075 C
Adder
6.0964705882352945.182
316087AB2-174 C
80/20
0.9080.908
959311AF2-222 C
80/20
13.30313.303
937481AD2-202 C
80/20
0.3090.309
3151031BRUNSWICKG2
80/20
7.5567.556
960081AF2-299 C
80/20
1.4551.455
936261AD2-033 C
80/20
10.37510.375
961791AG1-021 C
80/20
1.4371.437
938771AE1-103 C
Adder
2.10235294117647081.787
963041AG1-153 C
80/20
5.1375.137
3151051BRUNSWICKS1
80/20
15.69915.699
316170AC1-121 C
80/20
2.952.95
944011AF1-069 C
80/20
12.12612.126
316045AC1-158 C2
80/20
18.51718.517
944591AF1-124 C
Adder
32.1611764705882427.337
944601AF1-125 C
Adder
31.55411764705882826.821
941591AE2-156 C
Adder
12.43294117647058910.568
927021AC1-189 C
Adder
6.225.287
926071AC1-086 C
Adder
15.98823529411764713.59
946281AF1-292 C
80/20
1.2041.204
964241AG1-285 C
80/20
9.9749.974
962561AG1-105 C
Adder
6.9729411764705885.927
316034AC1-036 C
80/20
0.1860.186
3144293JTRSVLE
80/20
0.3290.329
316044AC1-158 C1
80/20
18.51718.517
316349AD2-085 C
Adder
2.3964705882352942.037
966621AG1-532 C
80/20
1.0911.091
935171AD1-152 C
80/20
1.0991.099
3151021BRUNSWICKG1
80/20
7.5567.556
3151041BRUNSWICKG3
80/20
7.5567.556
934861AD1-115 C
80/20
3.3063.306
3152261N ANNA2
80/20
103.964103.964
942341AE2-247 C
Adder
1.03882352941176470.883
316274AC1-208 C
Adder
6.785.763
962571AG1-106 C
Adder
2.0682352941176471.758
957871AF2-081 C
Adder
7.0094117647058835.958
316405AF2-144 C
80/20
0.2720.272
313527AB2-043 C
80/20
0.4090.409
3152251N ANNA1
80/20
103.92103.92
933291AC2-141 C
Adder
21.0423529411764717.886
3137643SOCKMAN
Adder
0.54588235294117650.464
3151741LOISA C
80/20
3.3493.349
3151721LOISA A
80/20
3.3313.331
939411AE1-173 C
80/20
78.11378.113
3147043LAWRENC
80/20
0.240.24
940481AE2-033 C
80/20
12.91312.913
940541AE2-040 C
80/20
2.2982.298
3152441Z1-086 ST
80/20
16.87216.872
966001AG1-469 C
80/20
2.3822.382
3152411Z1-086 GT1
80/20
9.6939.693
3152421Z1-086 GT2
80/20
9.699.69
316233AE1-074 C
80/20
2.0672.067
943461AF1-017 C
Adder
0.94000000000000010.799
316311AC2-079 C
Adder
3.99647058823529383.397
933981AD1-022 C
Adder
6.3599999999999995.406
938531AE1-072 C
Adder
12.33529411764705810.485
316238AB2-078 C O1
80/20
0.2590.259
958161AF2-110 C
Adder
0.96117647058823530.817
316237AB2-079 C O1
80/20
0.2590.259
934611AD1-087 C
80/20
1.0661.066
3152431Z1-086 GT3
80/20
9.699.69
316336AC2-165 C
80/20
8.8748.874
940641AE2-051 C
80/20
15.75815.758
316239AB2-077 C O1
80/20
0.2590.259
964791AG1-342 C
Adder
2.77294117647058872.357
3151731LOISA B
80/20
3.3493.349
3151751LOISA D
80/20
3.3493.349
316313AB2-026 C
80/20
0.3480.348
316164AC1-076_C
80/20
1.0891.089
939191AE1-149 C
Adder
7.2929411764705886.199
957861AF2-080 C
Adder
5.6494117647058824.802
316023AB2-100 C2
80/20
0.7450.745
316315AB2-025 C
80/20
0.3250.325
316131AB2-060 C
80/20
1.1781.178
3138533PONTONDP
80/20
0.5320.532
3151541CLOVER2
80/20
10.72710.727
316257AC1-043 C
80/20
6.6126.612
316254AC1-120 C
80/20
8.5918.591
316303AF2-085
80/20
3.8763.876
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2194.219
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.82173.821
CPLELTFEXP_CPLE->PJM
CLTF
8.8538.853
TVALTFEXP_TVA->PJM
CLTF
4.5224.522
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.20919.209
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.12316.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.6672.667
LAGNLTFEXP_LAGN->PJM
CLTF
5.7055.705
NYPJM->LTFIMP_NY
CLTF
2.292.29
LGEELTFEXP_LGEE->PJM
CLTF
0.8350.835
WECLTFEXP_WEC->PJM
CLTF
0.4130.413
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.09 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3577.61
MW Contribution:1.53
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.39411764705882360.335
934321AD1-056 C
Adder
4.9729411764705894.227
934331AD1-057 C
Adder
2.7741176470588242.358
958211AF2-115 C
80/20
1.8751.875
3151531CLOVER1
80/20
11.34911.349
208900BRIS G1
80/20
-2.414-2.414
3151761LOISA E
80/20
6.316.31
3151771S ANNAG1
80/20
3.0413.041
3151791S ANNAG2
80/20
3.0413.041
3151781S ANNAS1
80/20
1.5631.563
316258AE1-075 C
80/20
0.3330.333
941031AE2-094 C
80/20
38.91138.911
3150831SPRUNCA
Adder
6.1623529411764715.238
3150841SPRUNCB
Adder
6.1623529411764715.238
316365AB2-100 C1
80/20
0.7870.787
957481AF2-042 C
80/20
49.31549.315
3151801S ANNAS2
80/20
1.5631.563
940431AE2-027 C
Adder
8.3129411764705887.066
944581AF1-123 C
Adder
34.0988235294117728.984
941101AE2-104 C
Adder
2.50470588235294132.129
934501AD1-074 C
Adder
25.86823529411764621.988
961671AG1-007 C
Adder
0.73647058823529410.626
946301AF1-294 C
80/20
3.0833.083
942461AE2-259 C
Adder
8.3117647058823547.065
934621AD1-088 C
80/20
8.6418.641
208901BRIS G2
80/20
-2.857-2.857
316192AB2-158 C
80/20
4.2764.276
942001AE2-212 C
Adder
1.49882352941176471.274
934521AD1-076 C
Adder
9.3952941176470587.986
934511AD1-075 C
Adder
6.46705882352941155.497
316263AC1-034 C
Adder
5.2270588235294114.443
316087AB2-174 C
80/20
0.9580.958
959311AF2-222 C
80/20
13.90913.909
937481AD2-202 C
80/20
0.3240.324
3151031BRUNSWICKG2
80/20
7.9247.924
316240AF1-291 C
Adder
1.37882352941176461.172
944641AF1-129 C
Adder
63.6988235294117654.144
960081AF2-299 C
80/20
1.5351.535
936261AD2-033 C
80/20
10.85610.856
961791AG1-021 C
80/20
1.51.5
938771AE1-103 C
Adder
2.2329411764705881.898
963041AG1-153 C
80/20
5.3875.387
3151051BRUNSWICKS1
80/20
16.46316.463
944011AF1-069 C
80/20
12.71412.714
944591AF1-124 C
Adder
34.2229.087
944601AF1-125 C
Adder
33.5741176470588328.538
941591AE2-156 C
Adder
13.23882352941176611.253
927021AC1-189 C
Adder
6.5788235294117645.592
926071AC1-086 C
Adder
16.8929411764705914.359
946281AF1-292 C
80/20
1.2711.271
964241AG1-285 C
80/20
10.44910.449
962561AG1-105 C
Adder
7.3152941176470596.218
316034AC1-036 C
80/20
0.1950.195
3144293JTRSVLE
80/20
0.3440.344
316349AD2-085 C
Adder
2.5505882352941182.168
313506AB1-173 C OP
80/20
0.9150.915
966621AG1-532 C
80/20
1.1511.151
935171AD1-152 C
80/20
1.1531.153
3151021BRUNSWICKG1
80/20
7.9247.924
3151041BRUNSWICKG3
80/20
7.9247.924
3152261N ANNA2
80/20
106.999106.999
942341AE2-247 C
Adder
1.10588235294117650.94
316274AC1-208 C
Adder
7.1635294117647066.089
962571AG1-106 C
Adder
2.1847058823529411.857
3151311EDGECMA
Adder
12.21411764705882410.382
957871AF2-081 C
Adder
7.4588235294117656.34
316405AF2-144 C
80/20
0.2830.283
3150651CHESTF6
Adder
11.5976470588235319.858
313527AB2-043 C
80/20
0.4290.429
3152251N ANNA1
80/20
106.954106.954
933291AC2-141 C
Adder
22.41294117647058619.051
3137643SOCKMAN
Adder
0.57647058823529410.49
316181AB2-040 GEN
80/20
1.0311.031
3147043LAWRENC
80/20
0.2530.253
940481AE2-033 C
80/20
13.63113.631
940541AE2-040 C
80/20
2.4262.426
3152441Z1-086 ST
80/20
17.69217.692
966001AG1-469 C
80/20
1.9821.982
961611AG1-000B C
Adder
10.3129411764705888.766
3152411Z1-086 GT1
80/20
10.16410.164
3152421Z1-086 GT2
80/20
10.16110.161
316233AE1-074 C
80/20
2.1822.182
943461AF1-017 C
Adder
1.00.85
316311AC2-079 C
Adder
4.2541176470588233.616
933981AD1-022 C
Adder
6.7447058823529415.733
938531AE1-072 C
Adder
13.12352941176470511.155
316238AB2-078 C O1
80/20
0.2720.272
958161AF2-110 C
Adder
1.02235294117647070.869
316237AB2-079 C O1
80/20
0.2720.272
934611AD1-087 C
80/20
1.1171.117
3152431Z1-086 GT3
80/20
10.16110.161
316336AC2-165 C
80/20
9.2269.226
940641AE2-051 C
80/20
16.55416.554
316239AB2-077 C O1
80/20
0.2720.272
964791AG1-342 C
Adder
2.9105882352941182.474
3151731LOISA B
80/20
3.0953.095
3151751LOISA D
80/20
3.0953.095
316313AB2-026 C
80/20
0.3630.363
939191AE1-149 C
Adder
7.7752941176470596.609
957861AF2-080 C
Adder
5.9741176470588245.078
316023AB2-100 C2
80/20
0.7870.787
316315AB2-025 C
80/20
0.3440.344
316131AB2-060 C
80/20
1.2351.235
3138533PONTONDP
80/20
0.5550.555
3151541CLOVER2
80/20
11.24311.243
3151741LOISA C
80/20
3.0953.095
3151721LOISA A
80/20
3.0793.079
939411AE1-173 C
80/20
82.26382.263
316303AF2-085
80/20
4.064.06
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4574.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
78.26878.268
CPLELTFEXP_CPLE->PJM
CLTF
9.3529.352
TVALTFEXP_TVA->PJM
CLTF
4.8954.895
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.24822.248
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.65817.658
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.9882.988
LAGNLTFEXP_LAGN->PJM
CLTF
6.1746.174
NYPJM->LTFIMP_NY
CLTF
2.2912.291
LGEELTFEXP_LGEE->PJM
CLTF
0.9480.948
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
SIGELTFEXP_SIGE->PJM
CLTF
0.1860.186

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.41 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4350.17
MW Contribution:2.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316141AB2-099 E
Adder
0.195294117647058840.166
961672AG1-007 E
Adder
0.414117647058823530.352
934501AD1-074 C
Adder
25.6821.828
961671AG1-007 C
Adder
0.73058823529411760.621
961942AG1-037 E
Adder
0.26117647058823530.222
961941AG1-037 C
Adder
0.391764705882352960.333
927022AC1-189 E
Adder
3.25058823529411762.763
923263AB1-132 E OP
Adder
4.8811764705882354.149
933981AD1-022 C
Adder
6.6952941176470595.691
900672V4-068 E
Adder
0.276470588235294130.235
938531AE1-072 C
Adder
13.03294117647058811.078
924302AB2-077 E O1
Adder
1.10588235294117650.94
3145393UNCAMP
Adder
4.622352941176473.929
933982AD1-022 E
Adder
3.6447058823529413.098
3145946PLYMOUTH TP
Adder
0.245882352941176470.209
927146AC1-208 E
Adder
3.1564705882352942.683
927255AC1-221 E
Adder
2.9588235294117652.515
934612AD1-087 E
Adder
3.2152941176470592.733
934622AD1-088 E
Adder
4.1364705882352943.516
316336AC2-165 C
Adder
9.177647058823537.801
940641AE2-051 C
50/50
16.47216.472
934322AD1-056 E
Adder
2.6764705882352942.275
934332AD1-057 E
Adder
1.43411764705882371.219
934321AD1-056 C
Adder
4.9352941176470594.195
934331AD1-057 C
Adder
2.75294117647058822.34
925595AC1-034 E
Adder
3.91058823529411773.324
923852AB2-025 E
Adder
0.97529411764705880.829
936262AD2-033 E
Adder
7.1882352941176476.11
958211AF2-115 C
Adder
1.86235294117647051.583
208900BRIS G1
50/50
-2.489-2.489
3151761LOISA E
50/50
6.3326.332
3151771S ANNAG1
50/50
3.0513.051
3151791S ANNAG2
50/50
3.0513.051
3151781S ANNAS1
50/50
1.5681.568
923862AB2-026 E
Adder
1.17294117647058820.997
941031AE2-094 C
50/50
38.72138.721
941032AE2-094 E
50/50
17.34217.342
3150831SPRUNCA
Adder
6.117647058823535.2
3150841SPRUNCB
Adder
6.117647058823535.2
939412AE1-173 E
Adder
54.5505882352941246.368
926662AC1-147 E
Adder
0.97176470588235290.826
916192Z1-068 E
Adder
1.38588235294117631.178
957492AF2-043 E
Adder
1.05294117647058830.895
943172AE2-346 E
Adder
0.46941176470588240.399
917332KELFORD E
Adder
1.281.088
925122AB2-169 E
Adder
4.4105882352941183.749
934522AD1-076 E
Adder
4.7541176470588244.041
940492AE2-034 E
Adder
2.3364705882352941.986
316274AC1-208 C
Adder
7.1094117647058826.043
962571AG1-106 C
Adder
2.16941176470588241.844
917342Z2-044 E
Adder
0.46823529411764710.398
3151311EDGECMA
Adder
12.11411764705882510.297
918492AA1-063AE OP
Adder
3.22705882352941182.743
957871AF2-081 C
Adder
7.4070588235294126.296
961792AG1-021 E
Adder
1.26941176470588221.079
937482AD2-202 E
Adder
0.94117647058823540.8
3145506HICKORY
Adder
1.61411764705882371.372
933292AC2-141 E
Adder
9.502352941176478.077
934576AD1-082 E
Adder
3.19882352941176462.719
944602AF1-125 E
Adder
76.3341176470588364.884
943612AF1-032 E
Adder
0.68470588235294120.582
957862AF2-080 E
Adder
2.6270588235294122.233
926072AC1-086 E
Adder
7.6341176470588236.489
960081AF2-299 C
Adder
1.52470588235294141.296
3145413WATKINS
Adder
0.52941176470588240.45
936261AD2-033 C
Adder
10.782352941176479.165
962562AG1-105 E
Adder
4.842352941176474.116
961791AG1-021 C
Adder
1.48941176470588241.266
938771AE1-103 C
Adder
2.21764705882352951.885
924032AB2-045 E
Adder
1.08588235294117650.923
963041AG1-153 C
Adder
5.3588235294117644.555
944011AF1-069 C
50/50
12.65212.652
316045AC1-158 C2
50/50
19.56819.568
944591AF1-124 C
Adder
33.9870588235294128.889
944601AF1-125 C
Adder
33.3447058823529428.343
941591AE2-156 C
Adder
13.14823529411764711.176
936666AD2-085 E
Adder
4.1329411764705883.513
926206AC1-098 E
Adder
2.86705882352941142.437
919710AA2-057 E
Adder
3.1117647058823532.645
3137643SOCKMAN
Adder
0.57294117647058830.487
913392Y1-086 E
Adder
1.63411764705882371.389
933502AC2-165 E
Adder
6.9070588235294135.871
3151741LOISA C
50/50
3.1063.106
3151721LOISA A
50/50
3.093.09
939411AE1-173 C
Adder
81.8247058823529469.551
934521AD1-076 C
Adder
9.3258823529411777.927
934511AD1-075 C
Adder
6.425.457
919692AA2-053 E OP
Adder
3.36117647058823542.857
316263AC1-034 C
Adder
5.1835294117647064.406
923573AB1-173 E OP
Adder
2.6529411764705882.255
3145723EMPORIA
Adder
0.350588235294117640.298
920042AA2-088 E OP
Adder
8.226.987
925785AC1-054 E
Adder
2.79764705882352962.378
919152AA1-139 E1
Adder
3.02941176470588272.575
959311AF2-222 C
Adder
13.8152941176470611.743
942342AE2-247 E
Adder
1.5164705882352941.289
964791AG1-342 C
Adder
2.88941176470588262.456
901082W1-029 E
Adder
23.76705882352941420.202
942462AE2-259 E
Adder
5.5047058823529414.679
3151731LOISA B
50/50
3.1063.106
3151751LOISA D
50/50
3.1063.106
3143316POE
Adder
1.04235294117647070.886
939191AE1-149 C
Adder
7.7200000000000016.562
918512AA1-065 E OP
Adder
4.2588235294117653.62
918532AA1-067 E
Adder
0.55176470588235290.469
934502AD1-074 E
Adder
13.07176470588235311.111
934512AD1-075 E
Adder
3.26823529411764732.778
924516AB2-100 E1
Adder
2.36470588235294082.01
966621AG1-532 C
Adder
1.1435294117647060.972
919153AA1-139 E2
Adder
3.02941176470588272.575
924022AB2-043 E O1
Adder
4.2929411764705883.649
3147223TWITTYS
Adder
0.78941176470588240.671
959312AF2-222 E
Adder
9.2564705882352957.868
3152261N ANNA2
50/50
106.886106.886
940642AE2-051 E
50/50
10.98110.981
942341AE2-247 C
Adder
1.09764705882352940.933
943462AF1-017 E
Adder
1.621.377
958162AF2-110 E
Adder
1.61411764705882371.372
957861AF2-080 C
Adder
5.9270588235294125.038
917512Z2-088 E OP1
Adder
3.8047058823529413.234
946282AF1-292 E
Adder
0.84117647058823530.715
3138533PONTONDP
Adder
0.55176470588235290.469
944012AF1-069 E
50/50
4.9154.915
927021AC1-189 C
Adder
6.5247058823529425.546
926071AC1-086 C
Adder
16.77411764705882314.258
924152AB2-059 E OP
Adder
4.122352941176473.504
946281AF1-292 C
Adder
1.26235294117647071.073
960082AF2-299 E
Adder
1.01647058823529420.864
916042Z1-036 E
Adder
21.48117647058823518.259
923832AB2-022 E
Adder
0.92235294117647060.784
964241AG1-285 C
Adder
10.3776470588235298.821
962561AG1-105 C
Adder
7.2635294117647076.174
958212AF2-115 E
Adder
1.58588235294117651.348
938772AE1-103 E
Adder
3.0611764705882352.602
963042AG1-153 E
Adder
8.0388235294117656.833
925022AB2-158 E
50/50
11.37311.373
316044AC1-158 C1
50/50
19.56819.568
944592AF1-124 E
Adder
77.8317647058823566.157
944582AF1-123 E
Adder
77.5517647058823565.919
316349AD2-085 C
Adder
2.53294117647058852.153
935112AD1-144 E
Adder
0.67176470588235290.571
924517AB2-100 E2
Adder
2.36470588235294082.01
937226AE2-253 E
Adder
4.3282352941176473.679
946301AF1-294 C
Adder
3.06235294117647072.603
935172AD1-152 E
Adder
4.7270588235294114.018
942461AE2-259 C
Adder
8.257647058823537.019
934621AD1-088 C
Adder
8.5905882352941177.302
957482AF2-042 E
Adder
32.6894117647058927.786
208901BRIS G2
50/50
-2.946-2.946
958502AF2-144 E
Adder
1.15294117647058810.98
316192AB2-158 C
50/50
4.2784.278
942001AE2-212 C
Adder
1.48705882352941181.264
939192AE1-149 E
Adder
5.1470588235294124.375
939312AE1-162 E
Adder
0.97647058823529410.83
934065AD1-033 E
Adder
3.70941176470588243.153
316084AB2-161 E
Adder
4.0141176470588233.412
940481AE2-033 C
Adder
13.54823529411764811.516
940482AE2-033 E
Adder
9.1341176470588247.764
940541AE2-040 C
Adder
2.4117647058823532.05
924312AB2-078 E O1
Adder
1.10588235294117650.94
925612AC1-036 E
Adder
0.7117647058823530.605
926274AC1-105 E
Adder
2.1788235294117651.852
966001AG1-469 C
50/50
2.0062.006
926740AC1-158 E2
50/50
51.18251.182
926214AC1-099 E
Adder
0.94705882352941180.805
932632AC2-084 E
Adder
2.53411764705882362.154
962572AG1-106 E
Adder
0.94941176470588240.807
957872AF2-081 E
Adder
3.17411764705882372.698
924162AB2-060 E OP
Adder
3.54470588235294143.013
964242AG1-285 E
Adder
6.9188235294117655.881
964792AG1-342 E
Adder
1.92588235294117661.637
932763AC2-100 E
Adder
2.00588235294117641.705
938562AE1-075 E
Adder
1.00.85
3152251N ANNA1
50/50
106.841106.841
938552AE1-074 E
Adder
1.09294117647058830.929
926755AC1-161 E
Adder
9.502352941176478.077
933291AC2-141 C
Adder
22.2618.921
925522AC1-027 E
Adder
0.89764705882352950.763
941102AE2-104 E
Adder
3.9541176470588243.361
3145256KINGFORK
Adder
0.72352941176470590.615
923994AB2-040_E
Adder
4.9741176470588234.228
316088AB2-174 E
Adder
5.2858823529411774.493
924322AB2-079 E O1
Adder
1.10588235294117650.94
943902AF1-058 E
Adder
1.04352941176470580.887
946302AF1-294 E
Adder
2.59294117647058852.204
957481AF2-042 C
Adder
49.0341176470588341.679
3151801S ANNAS2
50/50
1.5681.568
942002AE2-212 E
Adder
0.99176470588235290.843
944581AF1-123 C
Adder
33.8670588235294128.787
941101AE2-104 C
Adder
2.48705882352941152.114
932046AC2-012 E
Adder
9.6164705882352938.174
958161AF2-110 C
Adder
1.0152941176470590.863
920692AA2-178 E
Adder
3.1141176470588232.647
922923AB1-081 E OP
Adder
2.9105882352941182.474
966622AG1-532 E
Adder
0.76235294117647070.648
917122Z2-027 E
Adder
1.00.85
3146326AYDLETT TAP
Adder
1.00588235294117640.855
938532AE1-072 E
Adder
6.7941176470588245.775
927264AC1-222 E
Adder
3.20470588235294152.724
3147133PAMPLIN
Adder
0.82352941176470580.7
966002AG1-469 E
50/50
1.0031.003
926739AC1-158 E1
50/50
51.18251.182
316233AE1-074 C
Adder
2.17058823529411751.845
943461AF1-017 C
Adder
0.99294117647058820.844
316311AC2-079 C
Adder
4.2247058823529413.591
932596AC2-079 E
Adder
6.8929411764705895.859
316303AF2-085
50/50
4.0434.043
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4084.408
CBM South 2LTFEXP_CBM-S2->PJM
CBM
77.11777.117
CPLELTFEXP_CPLE->PJM
CLTF
9.2519.251
TVALTFEXP_TVA->PJM
CLTF
4.7224.722
O66PJM->LTFIMP_O-066
CMTX_NF
32.20632.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.05120.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.83616.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7842.784
LAGNLTFEXP_LAGN->PJM
CLTF
5.9595.959
NYPJM->LTFIMP_NY
CLTF
2.3732.373
LGEELTFEXP_LGEE->PJM
CLTF
0.8720.872
WECLTFEXP_WEC->PJM
CLTF
0.4310.431
G-007PJM->LTFIMP_G-007
CMTX_NF
5.0575.057
SIGELTFEXP_SIGE->PJM
CLTF
0.1730.173

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.75 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4205.81
MW Contribution:2.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316141AB2-099 E
Adder
0.187058823529411780.159
923994AB2-040_E
Adder
4.7588235294117654.045
316088AB2-174 E
Adder
5.0564705882352944.298
924322AB2-079 E O1
Adder
1.06588235294117650.906
943902AF1-058 E
Adder
1.00470588235294110.854
946302AF1-294 E
Adder
2.51294117647058852.136
957481AF2-042 C
Adder
47.1905882352941240.112
3151801S ANNAS2
50/50
1.7251.725
942002AE2-212 E
Adder
0.93764705882352950.797
944581AF1-123 C
Adder
32.1329411764705927.313
941101AE2-104 C
Adder
2.362.006
918512AA1-065 E OP
Adder
4.06000000000000053.451
918532AA1-067 E
Adder
0.52705882352941180.448
934502AD1-074 E
Adder
12.44588235294117810.579
934512AD1-075 E
Adder
3.1117647058823532.645
924516AB2-100 E1
Adder
2.26000000000000021.921
966621AG1-532 C
Adder
1.09411764705882360.93
926214AC1-099 E
Adder
0.90470588235294120.769
932632AC2-084 E
Adder
2.4211764705882352.058
962572AG1-106 E
Adder
0.90705882352941180.771
957872AF2-081 E
Adder
3.0117647058823532.56
924162AB2-060 E OP
Adder
3.4164705882352942.904
964242AG1-285 E
Adder
6.6741176470588245.673
964792AG1-342 E
Adder
1.85529411764705881.577
932763AC2-100 E
Adder
1.9282352941176471.639
934862AD1-115 E
50/50
5.7435.743
938562AE1-075 E
Adder
0.96941176470588230.824
3152251N ANNA1
50/50
104.031104.031
938552AE1-074 E
Adder
1.04470588235294120.888
926755AC1-161 E
Adder
9.0070588235294127.656
933291AC2-141 C
Adder
21.09882352941176717.934
925522AC1-027 E
Adder
0.85058823529411760.723
941102AE2-104 E
Adder
3.75294117647058823.19
3145256KINGFORK
Adder
0.68588235294117650.583
923263AB1-132 E OP
Adder
4.66470588235294153.965
940481AE2-033 C
Adder
12.94470588235294211.003
940482AE2-033 E
Adder
8.7270588235294117.418
940541AE2-040 C
Adder
2.3035294117647061.958
924312AB2-078 E O1
Adder
1.06588235294117650.906
925612AC1-036 E
Adder
0.68823529411764710.585
926274AC1-105 E
Adder
2.09764705882352941.783
966001AG1-469 C
50/50
2.4612.461
925672AC1-043 E
50/50
11.48611.486
926740AC1-158 E2
50/50
48.49548.495
920692AA2-178 E
Adder
2.9635294117647062.519
966622AG1-532 E
Adder
0.72941176470588230.62
917122Z2-027 E
Adder
0.94941176470588240.807
3146326AYDLETT TAP
Adder
0.95411764705882360.811
938532AE1-072 E
Adder
6.4470588235294135.48
927264AC1-222 E
Adder
3.0847058823529412.622
3147133PAMPLIN
Adder
0.79882352941176480.679
966002AG1-469 E
50/50
1.231.23
926739AC1-158 E1
50/50
48.49548.495
316233AE1-074 C
Adder
2.07294117647058851.762
943461AF1-017 C
Adder
0.94235294117647060.801
316311AC2-079 C
Adder
4.00705882352941253.406
932596AC2-079 E
Adder
6.5388235294117655.558
933981AD1-022 C
Adder
6.3764705882352955.42
900672V4-068 E
Adder
0.26352941176470590.224
938531AE1-072 C
Adder
12.36823529411764810.513
924302AB2-077 E O1
Adder
1.06588235294117650.906
3145393UNCAMP
Adder
4.3976470588235293.738
926486AC1-120 E
50/50
4.6124.612
932046AC2-012 E
Adder
9.1176470588235297.75
958161AF2-110 C
Adder
0.96352941176470590.819
933982AD1-022 E
Adder
3.47058823529411782.95
3145946PLYMOUTH TP
Adder
0.234117647058823540.199
927146AC1-208 E
Adder
3.01882352941176452.566
927255AC1-221 E
Adder
2.84470588235294162.418
934612AD1-087 E
Adder
3.09529411764705882.631
934622AD1-088 E
Adder
3.98588235294117643.388
316336AC2-165 C
Adder
8.9188235294117667.581
926004AC1-076_E
50/50
6.3656.365
940641AE2-051 C
50/50
15.79315.793
316084AB2-161 E
Adder
3.8047058823529413.234
943172AE2-346 E
Adder
0.448235294117647070.381
917332KELFORD E
Adder
1.22235294117647041.039
925122AB2-169 E
Adder
4.2058823529411773.575
934522AD1-076 E
Adder
4.5258823529411773.847
940492AE2-034 E
Adder
2.2223529411764711.889
316274AC1-208 C
Adder
6.7976470588235295.778
962571AG1-106 C
Adder
2.07294117647058851.762
917342Z2-044 E
Adder
0.448235294117647070.381
918492AA1-063AE OP
Adder
3.08235294117647072.62
957871AF2-081 C
Adder
7.0282352941176475.974
961792AG1-021 E
Adder
1.22941176470588221.045
937482AD2-202 E
Adder
0.90588235294117650.77
3145506HICKORY
Adder
1.53058823529411761.301
933292AC2-141 E
Adder
9.0070588235294127.656
934576AD1-082 E
Adder
3.0317647058823532.577
944602AF1-125 E
Adder
72.4247058823529461.561
943612AF1-032 E
Adder
0.64941176470588250.552
961942AG1-037 E
Adder
0.249411764705882360.212
961941AG1-037 C
Adder
0.37294117647058830.317
927022AC1-189 E
Adder
3.10588235294117652.64
934322AD1-056 E
Adder
2.562.176
934332AD1-057 E
Adder
1.37058823529411771.165
934321AD1-056 C
Adder
4.7188235294117654.011
934331AD1-057 C
Adder
2.6329411764705882.238
923852AB2-025 E
Adder
0.9317647058823530.792
936262AD2-033 E
Adder
6.9435294117647075.902
958211AF2-115 C
Adder
1.80470588235294121.534
208900BRIS G1
50/50
-2.42-2.42
3151761LOISA E
50/50
7.047.04
3151771S ANNAG1
50/50
3.3573.357
3151791S ANNAG2
50/50
3.3573.357
3151781S ANNAS1
50/50
1.7251.725
923862AB2-026 E
Adder
1.13764705882352950.967
941031AE2-094 C
50/50
37.19337.193
941032AE2-094 E
50/50
16.65816.658
939412AE1-173 E
Adder
52.19411764705882544.365
926662AC1-147 E
Adder
0.92117647058823540.783
916192Z1-068 E
Adder
1.31411764705882361.117
957492AF2-043 E
Adder
0.99882352941176470.849
957862AF2-080 E
Adder
2.5105882352941182.134
926072AC1-086 E
Adder
7.29529411764705856.201
960081AF2-299 C
Adder
1.45882352941176461.24
3145413WATKINS
Adder
0.50352941176470590.428
936261AD2-033 C
Adder
10.415294117647068.853
962562AG1-105 E
Adder
4.6635294117647063.964
961791AG1-021 C
Adder
1.4435294117647061.227
938771AE1-103 C
Adder
2.1082352941176471.792
924032AB2-045 E
Adder
1.06588235294117650.906
963041AG1-153 C
Adder
5.1482352941176474.376
316170AC1-121 C
50/50
3.0753.075
944011AF1-069 C
50/50
12.15212.152
316045AC1-158 C2
50/50
18.54118.541
944591AF1-124 C
Adder
32.24705882352941427.41
944601AF1-125 C
Adder
31.6376470588235326.892
941591AE2-156 C
Adder
12.46588235294117710.596
936666AD2-085 E
Adder
3.923.332
926206AC1-098 E
Adder
2.742.329
964791AG1-342 C
Adder
2.7823529411764712.365
901082W1-029 E
Adder
22.56941176470588319.184
942462AE2-259 E
Adder
5.3529411764705884.55
3151731LOISA B
50/50
3.4533.453
3151751LOISA D
50/50
3.4533.453
3143316POE
Adder
0.99058823529411770.842
316164AC1-076_C
50/50
1.1111.111
939191AE1-149 C
Adder
7.3129411764705896.216
919710AA2-057 E
Adder
2.97647058823529382.53
3137643SOCKMAN
Adder
0.54705882352941180.465
913392Y1-086 E
Adder
1.5517647058823531.319
933502AC2-165 E
Adder
6.7129411764705895.706
3151741LOISA C
50/50
3.4533.453
3151721LOISA A
50/50
3.4353.435
939411AE1-173 C
Adder
78.2905882352941166.547
934521AD1-076 C
Adder
8.8788235294117657.547
934511AD1-075 C
Adder
6.1117647058823535.195
919692AA2-053 E OP
Adder
3.2129411764705882.731
923573AB1-173 E OP
Adder
2.53764705882352942.157
3145723EMPORIA
Adder
0.33529411764705880.285
920042AA2-088 E OP
Adder
7.8352941176470596.66
925785AC1-054 E
Adder
2.6835294117647062.281
919152AA1-139 E1
Adder
2.8741176470588242.443
959311AF2-222 C
Adder
13.3576470588235311.354
926502AC1-121 E
50/50
1.4471.447
942342AE2-247 E
Adder
1.43764705882352951.222
919153AA1-139 E2
Adder
2.8741176470588242.443
924022AB2-043 E O1
Adder
4.1364705882352943.516
3147223TWITTYS
Adder
0.76235294117647070.648
959312AF2-222 E
Adder
8.9494117647058827.607
934861AD1-115 C
50/50
3.523.52
3152261N ANNA2
50/50
104.075104.075
940642AE2-051 E
50/50
10.52910.529
942341AE2-247 C
Adder
1.04117647058823540.885
943462AF1-017 E
Adder
1.53764705882352941.307
958162AF2-110 E
Adder
1.53176470588235311.302
957861AF2-080 C
Adder
5.6635294117647064.814
946282AF1-292 E
Adder
0.80470588235294130.684
3138533PONTONDP
Adder
0.53411764705882360.454
316257AC1-043 C
50/50
7.047.04
316254AC1-120 C
50/50
8.9538.953
944012AF1-069 E
50/50
4.7214.721
927021AC1-189 C
Adder
6.2352941176470595.3
926071AC1-086 C
Adder
16.0282352941176513.624
946281AF1-292 C
Adder
1.2082352941176471.027
960082AF2-299 E
Adder
0.97294117647058820.827
916042Z1-036 E
Adder
20.41647058823529517.354
923832AB2-022 E
Adder
0.87529411764705890.744
964241AG1-285 C
Adder
10.0105882352941198.509
962561AG1-105 C
Adder
6.9952941176470595.946
958212AF2-115 E
Adder
1.53764705882352941.307
938772AE1-103 E
Adder
2.91176470588235332.475
963042AG1-153 E
Adder
7.7235294117647076.565
925022AB2-158 E
50/50
11.64111.641
316044AC1-158 C1
50/50
18.54118.541
944592AF1-124 E
Adder
73.8458823529411762.769
944582AF1-123 E
Adder
73.5862.543
316349AD2-085 C
Adder
2.40235294117647062.042
935112AD1-144 E
Adder
0.63647058823529420.541
934501AD1-074 C
Adder
24.44941176470588220.782
924517AB2-100 E2
Adder
2.26000000000000021.921
937226AE2-253 E
Adder
4.1070588235294123.491
946301AF1-294 C
Adder
2.96705882352941152.522
935172AD1-152 E
Adder
4.5494117647058833.867
942461AE2-259 C
Adder
8.0294117647058826.825
934621AD1-088 C
Adder
8.277647058823537.036
957482AF2-042 E
Adder
31.4626.741
208901BRIS G2
50/50
-2.864-2.864
958502AF2-144 E
Adder
1.11764705882352940.95
316192AB2-158 C
50/50
4.384.38
942001AE2-212 C
Adder
1.40588235294117661.195
939192AE1-149 E
Adder
4.87529411764705944.144
934065AD1-033 E
Adder
3.5188235294117652.991
316303AF2-085
50/50
3.8863.886
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2284.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.97573.975
CPLELTFEXP_CPLE->PJM
CLTF
8.8738.873
TVALTFEXP_TVA->PJM
CLTF
4.5234.523
O66PJM->LTFIMP_O-066
CMTX_NF
31.31531.315
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.05119.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.10316.103
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.6562.656
LAGNLTFEXP_LAGN->PJM
CLTF
5.7065.706
NYPJM->LTFIMP_NY
CLTF
2.3072.307
LGEELTFEXP_LGEE->PJM
CLTF
0.8310.831
WECLTFEXP_WEC->PJM
CLTF
0.410.41
G-007PJM->LTFIMP_G-007
CMTX_NF
4.9174.917
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.97 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3767.03
MW Contribution:1.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.454117647058823570.386
934321AD1-056 C
Adder
5.5882352941176484.75
934331AD1-057 C
Adder
3.11764705882352942.65
958211AF2-115 C
Adder
2.0152941176470591.713
3151531CLOVER1
80/20
12.09912.099
208900BRIS G1
80/20
-2.561-2.561
3151761LOISA E
80/20
4.8664.866
3151771S ANNAG1
80/20
2.372.37
3151791S ANNAG2
80/20
2.372.37
3151781S ANNAS1
80/20
1.2181.218
316258AE1-075 C
80/20
0.3530.353
941031AE2-094 C
80/20
41.10641.106
3150831SPRUNCA
Adder
7.7905882352941186.622
3150841SPRUNCB
Adder
7.7905882352941186.622
3151081ELIZAR1
80/20
2.8512.851
316365AB2-100 C1
80/20
0.8850.885
957481AF2-042 C
80/20
52.44752.447
3151801S ANNAS2
80/20
1.2181.218
940431AE2-027 C
Adder
10.6976470588235299.093
316294AC1-161 C
80/20
4.4154.415
944581AF1-123 C
80/20
40.90340.903
316185AD1-033 C
80/20
1.0971.097
916191Z1-068 C
80/20
0.0390.039
941101AE2-104 C
80/20
3.0013.001
934501AD1-074 C
Adder
30.18352941176470625.656
961671AG1-007 C
Adder
0.82941176470588230.705
946301AF1-294 C
Adder
3.3141176470588242.817
942461AE2-259 C
Adder
8.8929411764705887.559
934621AD1-088 C
80/20
9.29.2
208901BRIS G2
80/20
-3.03-3.03
316192AB2-158 C
80/20
3.5593.559
942001AE2-212 C
Adder
1.8635294117647061.584
934521AD1-076 C
Adder
10.9623529411764719.318
934511AD1-075 C
Adder
7.54588235294117656.414
316263AC1-034 C
Adder
5.8505882352941184.973
316087AB2-174 C
80/20
1.0751.075
316321Z2-027 C
80/20
0.3250.325
959311AF2-222 C
Adder
14.9976470588235312.748
937481AD2-202 C
80/20
0.3460.346
3151031BRUNSWICKG2
80/20
8.3898.389
316240AF1-291 C
Adder
1.78117647058823541.514
944641AF1-129 C
Adder
83.2882352941176570.795
316036AC1-147 C
80/20
0.3280.328
316305AF2-043 C
80/20
0.3110.311
960081AF2-299 C
80/20
1.7191.719
936261AD2-033 C
Adder
11.7211764705882359.963
961791AG1-021 C
Adder
1.61176470588235321.37
938771AE1-103 C
80/20
2.6332.633
963041AG1-153 C
80/20
5.7035.703
3151051BRUNSWICKS1
80/20
17.42917.429
944011AF1-069 C
80/20
13.43113.431
3150601CHESTF5
Adder
45.29058823529411638.497
944591AF1-124 C
80/20
41.04941.049
944601AF1-125 C
80/20
40.27340.273
3151101ELIZAR3
80/20
2.8872.887
941591AE2-156 C
80/20
15.98415.984
927021AC1-189 C
Adder
7.4435294117647066.327
926071AC1-086 C
Adder
19.07647058823529616.215
946281AF1-292 C
80/20
1.4231.423
964241AG1-285 C
Adder
11.3035294117647079.608
962561AG1-105 C
Adder
7.9117647058823526.725
3151091ELIZAR2
80/20
2.8012.801
316349AD2-085 C
80/20
3.0713.071
313506AB1-173 C OP
80/20
1.0281.028
966621AG1-532 C
80/20
1.2891.289
316320Y1-086 C
80/20
0.1960.196
316388AE2-253 GEN
80/20
1.7531.753
935171AD1-152 C
80/20
1.2331.233
3151021BRUNSWICKG1
80/20
8.3898.389
3151041BRUNSWICKG3
80/20
8.3898.389
3152261N ANNA2
80/20
92.75992.759
942341AE2-247 C
80/20
1.3311.331
316246AF1-032 C
80/20
0.2540.254
316274AC1-208 C
Adder
8.077647058823536.866
962571AG1-106 C
Adder
2.4670588235294122.097
3151311EDGECMA
Adder
13.67647058823529511.625
957871AF2-081 C
80/20
8.9458.945
316405AF2-144 C
80/20
0.30.3
3150651CHESTF6
Adder
15.16470588235294212.89
3150861SPRUNCD
80/20
0.140.14
316018AA1-139 ULT2
80/20
0.9650.965
3152251N ANNA1
80/20
92.7292.72
3150851SPRUNCC
80/20
0.140.14
944631AF1-128 C
Adder
28.33882352941176624.088
933291AC2-141 C
80/20
27.11427.114
3150921YORKTN3
Adder
92.4352941176470578.57
3137643SOCKMAN
Adder
0.64823529411764710.551
3151741LOISA C
80/20
2.3872.387
3151721LOISA A
80/20
2.3742.374
939411AE1-173 C
80/20
90.4790.47
316381AD1-082 C
80/20
1.1161.116
3150991CHESPKB
80/20
0.6430.643
316181AB2-040 GEN
80/20
1.1581.158
3147043LAWRENC
80/20
0.2810.281
940481AE2-033 C
80/20
15.30215.302
940541AE2-040 C
80/20
2.7232.723
3152441Z1-086 ST
80/20
18.71718.717
966001AG1-469 C
Adder
1.43764705882352951.222
961611AG1-000B C
Adder
13.19882352941176511.219
316375AC2-012 C
80/20
1.2021.202
316072AD1-144 C
80/20
0.2460.246
3156056W1-029WIND
80/20
0.6930.693
3152411Z1-086 GT1
80/20
10.75310.753
3152421Z1-086 GT2
80/20
10.7510.75
316233AE1-074 C
80/20
2.4792.479
943461AF1-017 C
80/20
1.2041.204
316311AC2-079 C
80/20
5.125.12
933981AD1-022 C
Adder
7.84941176470588256.672
938531AE1-072 C
80/20
15.7315.73
3150731STONECA
Adder
5.4352941176470594.62
935161AD1-151 C
Adder
13.03882352941176511.083
316083AB2-161 C
80/20
0.4890.489
958161AF2-110 C
80/20
1.2251.225
313526AB2-022 C
80/20
0.3360.336
316017AA1-139 ULT1
80/20
0.9650.965
934611AD1-087 C
80/20
1.1911.191
3152431Z1-086 GT3
80/20
10.7510.75
316336AC2-165 C
80/20
9.7879.787
940641AE2-051 C
80/20
17.817.8
964791AG1-342 C
Adder
3.14588235294117662.674
3151731LOISA B
80/20
2.3872.387
3151751LOISA D
80/20
2.3872.387
316313AB2-026 C
80/20
0.3850.385
939191AE1-149 C
80/20
9.4869.486
3150981CHESPKA
80/20
0.3880.388
957861AF2-080 C
Adder
6.7600000000000015.746
316023AB2-100 C2
80/20
0.8850.885
316315AB2-025 C
80/20
0.3860.386
3138533PONTONDP
Adder
0.59764705882352940.508
3151541CLOVER2
80/20
11.98611.986
316316AC1-027 C
80/20
0.2820.282
316303AF2-085
80/20
4.3034.303
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.8954.895
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.42786.427
CPLELTFEXP_CPLE->PJM
CLTF
10.2710.27
TVALTFEXP_TVA->PJM
CLTF
5.5015.501
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.18225.182
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.8619.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.3753.375
LAGNLTFEXP_LAGN->PJM
CLTF
6.9186.918
NYPJM->LTFIMP_NY
CLTF
2.4542.454
LGEELTFEXP_LGEE->PJM
CLTF
1.0841.084
WECLTFEXP_WEC->PJM
CLTF
0.5370.537
SIGELTFEXP_SIGE->PJM
CLTF
0.2110.211

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.22 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3678.49
MW Contribution:1.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.53764705882352950.457
934321AD1-056 C
Adder
6.3870588235294125.429
934331AD1-057 C
Adder
3.5635294117647063.029
958211AF2-115 C
Adder
2.14705882352941171.825
941031AE2-094 C
80/20
42.24742.247
3150831SPRUNCA
80/20
10.42510.425
3150841SPRUNCB
80/20
10.42510.425
966871AG1-558 C
Adder
2.56235294117647072.178
964211AG1-282 C
Adder
2.07882352941176451.767
3150801HOPHCF4
80/20
4.1494.149
3151081ELIZAR1
80/20
3.6013.601
957481AF2-042 C
Adder
54.6470588235294146.45
940431AE2-027 C
80/20
14.61614.616
316294AC1-161 C
80/20
5.5975.597
944581AF1-123 C
80/20
51.27751.277
941101AE2-104 C
Adder
3.75764705882352963.194
934501AD1-074 C
Adder
36.4552941176470630.987
961671AG1-007 C
Adder
0.95176470588235310.809
946301AF1-294 C
Adder
3.5305882352941183.001
942461AE2-259 C
Adder
9.4035294117647077.993
934621AD1-088 C
Adder
9.6105882352941188.169
942001AE2-212 C
80/20
2.4472.447
962861AG1-135 C
Adder
6.3647058823529425.41
943741AF1-042 C
Adder
3.06352941176470632.604
934521AD1-076 C
Adder
13.2411.254
934511AD1-075 C
Adder
9.1141176470588237.747
316263AC1-034 C
Adder
6.6529411764705895.655
959311AF2-222 C
Adder
16.0552941176470613.647
316240AF1-291 C
80/20
2.4442.444
944641AF1-129 C
80/20
115.84115.84
3150781HOPHCF2
80/20
2.7332.733
3150761HOPPOLC
80/20
1.7191.719
960081AF2-299 C
Adder
1.95294117647058821.66
936261AD2-033 C
Adder
12.57294117647058810.687
961791AG1-021 C
Adder
1.71764705882352931.46
938771AE1-103 C
Adder
3.22705882352941182.743
963041AG1-153 C
Adder
5.8858823529411765.003
944011AF1-069 C
80/20
13.80413.804
966881AG1-559 C
Adder
2.45176470588235332.084
3150601CHESTF5
Adder
70.4105882352941159.849
944591AF1-124 C
80/20
51.4651.46
944601AF1-125 C
80/20
50.48850.488
3151101ELIZAR3
80/20
3.6473.647
941591AE2-156 C
80/20
20.20920.209
927021AC1-189 C
Adder
8.6023529411764727.312
926071AC1-086 C
Adder
21.9611764705882418.667
946281AF1-292 C
Adder
1.61647058823529431.374
964241AG1-285 C
Adder
12.1610.336
962561AG1-105 C
Adder
8.5058823529411767.23
939261AE1-157 C
Adder
14.10235294117647211.987
316169AC1-164 GEN
Adder
43.66588235294117537.116
3151091ELIZAR2
80/20
3.5383.538
316349AD2-085 C
Adder
3.87058823529411773.29
966621AG1-532 C
Adder
1.46470588235294131.245
934861AD1-115 C
Adder
-3.06-2.601
3152261N ANNA2
80/20
56.72156.721
3150771HOPHCF1
80/20
2.7332.733
942341AE2-247 C
Adder
1.67764705882352931.426
316274AC1-208 C
Adder
9.2835294117647067.891
962571AG1-106 C
Adder
2.84117647058823542.415
3151311EDGECMA
Adder
15.55647058823529613.223
957871AF2-081 C
Adder
11.2117647058823529.53
3150651CHESTF6
80/20
21.09121.091
3150861SPRUNCD
80/20
0.1870.187
936591AD2-074 C
Adder
5.8552941176470594.977
3152251N ANNA1
80/20
56.69756.697
3150851SPRUNCC
80/20
0.1870.187
944631AF1-128 C
Adder
44.0564705882352937.448
933291AC2-141 C
80/20
34.37234.372
3150921YORKTN3
Adder
133.0105882352941113.059
3137643SOCKMAN
Adder
0.74235294117647070.631
966661AG1-536 C
Adder
5.6341176470588234.789
939411AE1-173 C
80/20
99.71499.714
3150991CHESPKB
80/20
0.8130.813
940481AE2-033 C
Adder
17.43882352941176714.823
940541AE2-040 C
Adder
3.10117647058823562.636
927041AC1-191 C
Adder
10.2870588235294128.744
963611AG1-210 C
Adder
0.68235294117647060.58
961611AG1-000B C
Adder
17.92352941176470415.235
316375AC2-012 C
80/20
1.521.52
316233AE1-074 C
80/20
2.8742.874
940551AE2-041 C
Adder
7.6152941176470596.473
943461AF1-017 C
Adder
1.51764705882352961.29
316311AC2-079 C
Adder
6.4458823529411775.479
933981AD1-022 C
Adder
9.4470588235294128.03
938531AE1-072 C
Adder
19.70000000000000316.745
3142366NRTHEST
80/20
0.2040.204
3150731STONECA
80/20
7.7657.765
935161AD1-151 C
Adder
18.16235294117647215.438
958161AF2-110 C
Adder
1.53294117647058831.303
316336AC2-165 C
Adder
10.1788235294117648.652
940641AE2-051 C
80/20
18.8818.88
943471AF1-018 C
Adder
7.6152941176470596.473
3152331SURRY 2
80/20
27.86527.865
964791AG1-342 C
Adder
3.38000000000000032.873
3143096IRON208
80/20
0.4940.494
958261AF2-120 C
Adder
6.5505882352941175.568
939191AE1-149 C
80/20
12.15312.153
957601AF2-054 C
Adder
2.26000000000000021.921
957861AF2-080 C
Adder
7.8129411764705896.641
3138533PONTONDP
Adder
0.63647058823529420.541
316257AC1-043 C
Adder
-6.121176470588236-5.203
316254AC1-120 C
Adder
-6.376470588235295-5.42
3150791HOPHCF3
80/20
2.7332.733
961951AG1-038 C
Adder
3.3858823529411772.878
316303AF2-085
80/20
4.4474.447
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.4135.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69496.694
CPLELTFEXP_CPLE->PJM
CLTF
11.35211.352
TVALTFEXP_TVA->PJM
CLTF
6.4156.415
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.72830.728
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.33523.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.0414.041
LAGNLTFEXP_LAGN->PJM
CLTF
8.0268.026
NYPJM->LTFIMP_NY
CLTF
2.72.7
LGEELTFEXP_LGEE->PJM
CLTF
1.331.33
WECLTFEXP_WEC->PJM
CLTF
0.6540.654
SIGELTFEXP_SIGE->PJM
CLTF
0.2560.256

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.99 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4412.36
MW Contribution:2.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316141AB2-099 E
Adder
0.237647058823529430.202
923994AB2-040_E
Adder
5.8811764705882354.999
316088AB2-174 E
Adder
6.242352941176475.306
924322AB2-079 E O1
Adder
1.25764705882352931.069
946302AF1-294 E
Adder
2.9258823529411772.487
957481AF2-042 C
Adder
54.4729411764705946.302
3151801S ANNAS2
50/50
1.2331.233
942002AE2-212 E
Adder
1.31294117647058851.116
940431AE2-027 C
Adder
11.3411764705882369.64
944581AF1-123 C
Adder
43.0529411764705936.595
941101AE2-104 C
Adder
3.1588235294117652.685
934501AD1-074 C
Adder
31.6952941176470626.941
924517AB2-100 E2
Adder
2.82.38
937226AE2-253 E
Adder
5.5047058823529414.679
946301AF1-294 C
Adder
3.45529411764705862.937
935172AD1-152 E
Adder
5.2941176470588234.5
942461AE2-259 C
Adder
9.2705882352941187.88
934621AD1-088 C
Adder
9.5599999999999998.126
957482AF2-042 E
Adder
36.31529411764705630.868
208901BRIS G2
50/50
-3.245-3.245
958502AF2-144 E
Adder
1.2764705882352941.085
316192AB2-158 C
50/50
3.5873.587
942001AE2-212 C
Adder
1.96941176470588241.674
939192AE1-149 E
Adder
6.6670588235294125.667
939312AE1-162 E
Adder
1.29647058823529431.102
934065AD1-033 E
Adder
4.7282352941176474.019
961942AG1-037 E
Adder
0.317647058823529450.27
961941AG1-037 C
Adder
0.476470588235294150.405
923852AB2-025 E
Adder
1.15058823529411770.978
936262AD2-033 E
Adder
8.1458823529411776.924
958211AF2-115 C
Adder
2.1011764705882351.786
3151761LOISA E
50/50
4.9314.931
3151771S ANNAG1
50/50
2.42.4
3151791S ANNAG2
50/50
2.42.4
3151781S ANNAS1
50/50
1.2331.233
923862AB2-026 E
Adder
1.31.105
941031AE2-094 C
50/50
42.60742.607
941032AE2-094 E
50/50
19.08319.083
3150831SPRUNCA
Adder
8.2435294117647067.007
3150841SPRUNCB
Adder
8.2435294117647067.007
939412AE1-173 E
50/50
62.82462.824
926662AC1-147 E
Adder
1.24470588235294131.058
916192Z1-068 E
Adder
1.77058823529411761.505
957492AF2-043 E
Adder
1.341.139
923263AB1-132 E OP
Adder
5.80941176470588254.938
940481AE2-033 C
Adder
15.98588235294117513.588
940482AE2-033 E
Adder
10.777647058823539.161
940541AE2-040 C
Adder
2.84470588235294162.418
924312AB2-078 E O1
Adder
1.25764705882352931.069
925612AC1-036 E
Adder
0.80588235294117660.685
3152441Z1-086 ST
50/50
19.40819.408
966001AG1-469 C
Adder
1.46235294117647091.243
961611AG1-000B C
Adder
13.98823529411764911.89
920692AA2-178 E
Adder
3.86941176470588263.289
966622AG1-532 E
Adder
0.89882352941176480.764
917122Z2-027 E
Adder
1.26588235294117671.076
3146326AYDLETT TAP
Adder
1.27764705882352961.086
938532AE1-072 E
Adder
8.6305882352941187.336
3147133PAMPLIN
Adder
0.92823529411764720.789
3152411Z1-086 GT1
50/50
11.14911.149
3152421Z1-086 GT2
50/50
11.14611.146
966002AG1-469 E
Adder
0.73058823529411760.621
316233AE1-074 C
50/50
2.5912.591
935162AD1-151 E
Adder
0.93764705882352950.797
943461AF1-017 C
Adder
1.26823529411764711.078
316311AC2-079 C
Adder
5.3905882352941184.582
932596AC2-079 E
Adder
8.7952941176470587.476
933981AD1-022 C
Adder
8.247.004
900672V4-068 E
Adder
0.33764705882352940.287
938531AE1-072 C
Adder
16.55647058823529614.073
924302AB2-077 E O1
Adder
1.25764705882352931.069
3145393UNCAMP
Adder
5.7482352941176484.886
935161AD1-151 C
Adder
13.84941176470588311.772
932046AC2-012 E
Adder
12.31647058823529410.469
958161AF2-110 C
Adder
1.28941176470588251.096
933982AD1-022 E
Adder
4.4858823529411773.813
3145946PLYMOUTH TP
Adder
0.30352941176470590.258
934612AD1-087 E
Adder
3.5835294117647063.046
934622AD1-088 E
Adder
4.6035294117647063.913
3152431Z1-086 GT3
50/50
11.14611.146
316336AC2-165 C
Adder
10.1788235294117648.652
940641AE2-051 C
50/50
18.48718.487
316084AB2-161 E
Adder
5.1694117647058834.394
943172AE2-346 E
Adder
0.5717647058823530.486
917332KELFORD E
Adder
1.54588235294117651.314
934522AD1-076 E
Adder
5.8670588235294124.987
940492AE2-034 E
Adder
2.90235294117647062.467
962571AG1-106 C
Adder
2.58235294117647032.195
918492AA1-063AE OP
Adder
3.87294117647058833.292
957871AF2-081 C
Adder
9.4164705882352948.004
961792AG1-021 E
Adder
1.4317647058823531.217
937482AD2-202 E
Adder
1.04941176470588250.892
3145506HICKORY
Adder
2.05411764705882361.746
946262AF1-291 E
Adder
1.261.071
3150651CHESTF6
Adder
16.10470588235294213.689
933292AC2-141 E
Adder
12.19411764705882510.365
934576AD1-082 E
Adder
4.1188235294117653.501
944602AF1-125 E
Adder
97.0388235294117782.483
943612AF1-032 E
Adder
0.87058823529411770.74
926072AC1-086 E
Adder
9.0847058823529427.722
960081AF2-299 C
Adder
1.7964705882352941.527
3145413WATKINS
Adder
0.65411764705882360.556
936261AD2-033 C
Adder
12.2210.387
961791AG1-021 C
Adder
1.68117647058823551.429
938771AE1-103 C
Adder
2.7670588235294122.352
963041AG1-153 C
50/50
5.9155.915
3151051BRUNSWICKS1
50/50
18.07518.075
944011AF1-069 C
50/50
13.92113.921
927226AC1-216 E
Adder
6.6694117647058825.669
944591AF1-124 C
Adder
43.2058823529411836.725
944601AF1-125 C
Adder
42.3894117647058836.031
941591AE2-156 C
Adder
16.83647058823529414.311
936666AD2-085 E
Adder
5.2764705882352954.485
901082W1-029 E
Adder
30.02588235294117425.522
942462AE2-259 E
Adder
6.1800000000000015.253
3151731LOISA B
50/50
2.4192.419
3151751LOISA D
50/50
2.4192.419
3143316POE
Adder
1.30941176470588231.113
939191AE1-149 C
Adder
10.0011764705882348.501
3137643SOCKMAN
Adder
0.67882352941176470.577
913392Y1-086 E
Adder
2.0705882352941181.76
933502AC2-165 E
Adder
7.6611764705882356.512
940432AE2-027 E
Adder
7.5611764705882356.427
939411AE1-173 C
50/50
94.23794.237
934012AD1-025 E
Adder
8.6341176470588247.339
934521AD1-076 C
Adder
11.5105882352941199.784
934511AD1-075 C
Adder
7.9235294117647066.735
919692AA2-053 E OP
Adder
4.00705882352941253.406
923573AB1-173 E OP
Adder
3.1364705882352942.666
3145723EMPORIA
Adder
0.414117647058823530.352
920042AA2-088 E OP
Adder
10.0447058823529418.538
925785AC1-054 E
Adder
3.24941176470588242.762
919152AA1-139 E1
Adder
3.8505882352941183.273
959311AF2-222 C
Adder
15.63529411764705813.29
3151031BRUNSWICKG2
50/50
8.78.7
316240AF1-291 C
Adder
1.88941176470588261.606
944641AF1-129 C
Adder
88.4505882352941375.183
924814AB2-134 E
Adder
10.9235294117647069.285
942342AE2-247 E
Adder
1.93529411764705881.645
918512AA1-065 E OP
Adder
5.2011764705882364.421
934502AD1-074 E
Adder
16.13411764705882613.714
934512AD1-075 E
Adder
4.0341176470588243.429
924516AB2-100 E1
Adder
2.82.38
966621AG1-532 C
Adder
1.34705882352941191.145
919153AA1-139 E2
Adder
3.8505882352941183.273
924022AB2-043 E O1
Adder
4.8811764705882354.149
3147223TWITTYS
Adder
0.89294117647058820.759
959312AF2-222 E
Adder
10.4764705882352948.905
3151021BRUNSWICKG1
50/50
8.78.7
3151041BRUNSWICKG3
50/50
8.78.7
3152261N ANNA2
50/50
93.22693.226
940642AE2-051 E
50/50
12.32512.325
942341AE2-247 C
Adder
1.40235294117647061.192
943462AF1-017 E
Adder
2.06941176470588231.759
958162AF2-110 E
Adder
2.0505882352941181.743
946282AF1-292 E
Adder
0.99176470588235290.843
3138533PONTONDP
Adder
0.62235294117647070.529
944012AF1-069 E
50/50
5.4085.408
926071AC1-086 C
Adder
19.96117647058823516.967
946281AF1-292 C
Adder
1.48705882352941181.264
960082AF2-299 E
Adder
1.19764705882352951.018
916042Z1-036 E
Adder
26.91882352941176422.881
923832AB2-022 E
Adder
1.1682352941176470.993
964241AG1-285 C
Adder
11.78352941176470610.016
958212AF2-115 E
Adder
1.78941176470588231.521
938772AE1-103 E
Adder
3.8211764705882363.248
963042AG1-153 E
50/50
8.8728.872
925022AB2-158 E
50/50
9.5359.535
944592AF1-124 E
Adder
98.9435294117647184.102
944582AF1-123 E
Adder
98.5858823529411883.798
316349AD2-085 C
Adder
3.23411764705882382.749
935112AD1-144 E
Adder
0.8717647058823530.741
962572AG1-106 E
Adder
1.12941176470588230.96
957872AF2-081 E
Adder
4.0352941176470593.43
924162AB2-060 E OP
Adder
4.0294117647058823.425
964242AG1-285 E
Adder
7.8564705882352946.678
938562AE1-075 E
Adder
1.1082352941176470.942
3152251N ANNA1
50/50
93.18793.187
938552AE1-074 E
50/50
1.3051.305
926755AC1-161 E
Adder
12.19411764705882510.365
933291AC2-141 C
Adder
28.56588235294117724.281
925522AC1-027 E
Adder
1.14588235294117660.974
941102AE2-104 E
Adder
5.0223529411764714.269
3145256KINGFORK
Adder
0.93882352941176480.798
316303AF2-085
50/50
4.464.46
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.1255.125
CBM South 2LTFEXP_CBM-S2->PJM
CBM
90.8190.81
CPLELTFEXP_CPLE->PJM
CLTF
10.7510.75
TVALTFEXP_TVA->PJM
CLTF
5.8785.878
O66PJM->LTFIMP_O-066
CMTX_NF
35.46935.469
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.02528.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.37921.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.6863.686
LAGNLTFEXP_LAGN->PJM
CLTF
7.3867.386
NYPJM->LTFIMP_NY
CLTF
2.6122.612
LGEELTFEXP_LGEE->PJM
CLTF
1.1951.195
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5685.568
SIGELTFEXP_SIGE->PJM
CLTF
0.2320.232

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.18 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3902.62
MW Contribution:1.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.44235294117647060.376
934321AD1-056 C
Adder
5.4329411764705894.618
934331AD1-057 C
Adder
3.0305882352941182.576
958211AF2-115 C
Adder
1.97411764705882351.678
3151531CLOVER1
80/20
11.76811.768
208900BRIS G1
80/20
-2.628-2.628
3151761LOISA E
80/20
5.5225.522
3151771S ANNAG1
80/20
2.6512.651
3151791S ANNAG2
80/20
2.6512.651
3151781S ANNAS1
80/20
1.3621.362
316258AE1-075 C
80/20
0.3460.346
941031AE2-094 C
80/20
39.89839.898
3150831SPRUNCA
Adder
7.6235294117647066.48
3150841SPRUNCB
Adder
7.6235294117647066.48
3151081ELIZAR1
80/20
2.7822.782
316365AB2-100 C1
80/20
0.8620.862
957481AF2-042 C
80/20
51.00351.003
3151801S ANNAS2
80/20
1.3621.362
940431AE2-027 C
Adder
10.4682352941176488.898
316294AC1-161 C
80/20
4.314.31
944581AF1-123 C
80/20
39.90939.909
316185AD1-033 C
80/20
1.071.07
916191Z1-068 C
80/20
0.0380.038
941101AE2-104 C
80/20
2.9282.928
934501AD1-074 C
Adder
29.40470588235294324.994
961671AG1-007 C
Adder
0.80588235294117660.685
946301AF1-294 C
Adder
3.2458823529411762.759
942461AE2-259 C
Adder
8.7329411764705887.423
934621AD1-088 C
80/20
8.9588.958
208901BRIS G2
80/20
-3.11-3.11
316192AB2-158 C
80/20
3.6253.625
942001AE2-212 C
Adder
1.82117647058823541.548
934521AD1-076 C
Adder
10.6788235294117659.077
934511AD1-075 C
Adder
7.3517647058823536.249
316263AC1-034 C
Adder
5.6858823529411774.833
316087AB2-174 C
80/20
1.0461.046
316321Z2-027 C
80/20
0.3170.317
959311AF2-222 C
Adder
14.6623529411764712.463
937481AD2-202 C
80/20
0.3360.336
3151031BRUNSWICKG2
80/20
8.1438.143
316240AF1-291 C
Adder
1.7435294117647061.482
944641AF1-129 C
Adder
81.5517647058823669.319
316036AC1-147 C
80/20
0.320.32
316305AF2-043 C
80/20
0.3030.303
960081AF2-299 C
80/20
1.6731.673
936261AD2-033 C
Adder
11.4505882352941189.733
961791AG1-021 C
Adder
1.57882352941176471.342
938771AE1-103 C
80/20
2.5672.567
963041AG1-153 C
80/20
5.5365.536
3151051BRUNSWICKS1
80/20
16.91816.918
316170AC1-121 C
80/20
2.7242.724
944011AF1-069 C
80/20
13.03613.036
316045AC1-158 C2
80/20
19.41919.419
944591AF1-124 C
80/20
40.05140.051
944601AF1-125 C
80/20
39.29539.295
3151101ELIZAR3
80/20
2.8172.817
941591AE2-156 C
80/20
15.615.6
927021AC1-189 C
Adder
7.2364705882352946.151
926071AC1-086 C
Adder
18.5623529411764715.778
946281AF1-292 C
80/20
1.3851.385
964241AG1-285 C
Adder
11.0294117647058829.375
962561AG1-105 C
Adder
7.70470588235294156.549
316044AC1-158 C1
80/20
19.41919.419
3151091ELIZAR2
80/20
2.7332.733
316349AD2-085 C
80/20
2.9972.997
966621AG1-532 C
80/20
1.2551.255
316320Y1-086 C
80/20
0.1920.192
316388AE2-253 GEN
80/20
1.711.71
935171AD1-152 C
80/20
1.1991.199
3151021BRUNSWICKG1
80/20
8.1438.143
3151041BRUNSWICKG3
80/20
8.1438.143
934861AD1-115 C
Adder
2.8482352941176472.421
3152261N ANNA2
80/20
89.07389.073
942341AE2-247 C
80/20
1.2991.299
316246AF1-032 C
80/20
0.2480.248
316274AC1-208 C
Adder
7.857647058823536.679
962571AG1-106 C
Adder
2.40117647058823552.041
3151311EDGECMA
Adder
13.28823529411764811.295
957871AF2-081 C
80/20
8.7288.728
316405AF2-144 C
80/20
0.2940.294
3150651CHESTF6
Adder
14.84823529411764812.621
3150861SPRUNCD
80/20
0.1370.137
316018AA1-139 ULT2
80/20
0.9420.942
3152251N ANNA1
80/20
89.03589.035
3150851SPRUNCC
80/20
0.1370.137
933291AC2-141 C
80/20
26.46526.465
3150921YORKTN3
Adder
90.5694117647058876.984
3137643SOCKMAN
Adder
0.6317647058823530.537
3151741LOISA C
80/20
2.7082.708
3151721LOISA A
80/20
2.6942.694
939411AE1-173 C
80/20
87.96287.962
316381AD1-082 C
80/20
1.0891.089
3150991CHESPKB
80/20
0.6270.627
3147043LAWRENC
80/20
0.2730.273
940481AE2-033 C
80/20
14.89114.891
940541AE2-040 C
80/20
2.652.65
3152441Z1-086 ST
80/20
18.16818.168
966001AG1-469 C
80/20
1.9591.959
961611AG1-000B C
Adder
12.91058823529411910.974
316375AC2-012 C
80/20
1.1731.173
3156056W1-029WIND
80/20
0.6760.676
3152411Z1-086 GT1
80/20
10.43710.437
3152421Z1-086 GT2
80/20
10.43410.434
316233AE1-074 C
80/20
2.4172.417
943461AF1-017 C
80/20
1.1751.175
316311AC2-079 C
80/20
4.9964.996
933981AD1-022 C
Adder
7.6458823529411766.499
938531AE1-072 C
80/20
15.34615.346
3150731STONECA
Adder
5.3258823529411774.527
935161AD1-151 C
Adder
12.7647058823529410.85
316083AB2-161 C
80/20
0.4780.478
958161AF2-110 C
80/20
1.1951.195
313526AB2-022 C
80/20
0.3280.328
316017AA1-139 ULT1
80/20
0.9420.942
934611AD1-087 C
80/20
1.1591.159
3152431Z1-086 GT3
80/20
10.43410.434
316336AC2-165 C
80/20
9.6099.609
940641AE2-051 C
80/20
17.2917.29
964791AG1-342 C
Adder
3.06352941176470632.604
3151731LOISA B
80/20
2.7082.708
3151751LOISA D
80/20
2.7082.708
316313AB2-026 C
80/20
0.3770.377
316164AC1-076_C
80/20
1.1141.114
939191AE1-149 C
80/20
9.2629.262
3150981CHESPKA
80/20
0.3780.378
957861AF2-080 C
Adder
6.57294117647058855.587
316023AB2-100 C2
80/20
0.8620.862
316315AB2-025 C
80/20
0.3750.375
3138533PONTONDP
Adder
0.58470588235294120.497
3151541CLOVER2
80/20
11.65811.658
316257AC1-043 C
Adder
5.697647058823534.843
316254AC1-120 C
80/20
7.9327.932
316316AC1-027 C
80/20
0.2750.275
316303AF2-085
80/20
4.1844.184
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.744.74
CBM South 2LTFEXP_CBM-S2->PJM
CBM
83.40383.403
CPLELTFEXP_CPLE->PJM
CLTF
9.9459.945
TVALTFEXP_TVA->PJM
CLTF
5.1955.195
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.96121.961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.49718.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.0623.062
LAGNLTFEXP_LAGN->PJM
CLTF
6.5316.531
NYPJM->LTFIMP_NY
CLTF
2.5322.532
LGEELTFEXP_LGEE->PJM
CLTF
0.9710.971
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
SIGELTFEXP_SIGE->PJM
CLTF
0.1910.191

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.07 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3866.79
MW Contribution:1.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.52705882352941180.448
934321AD1-056 C
Adder
6.2529411764705895.315
934331AD1-057 C
Adder
3.4882352941176472.965
958211AF2-115 C
Adder
2.12470588235294141.806
941031AE2-094 C
80/20
41.37341.373
3150831SPRUNCA
80/20
10.21910.219
3150841SPRUNCB
80/20
10.21910.219
966871AG1-558 C
Adder
2.50941176470588222.133
964211AG1-282 C
Adder
2.0317647058823531.727
3150801HOPHCF4
80/20
4.0644.064
3151081ELIZAR1
80/20
3.5273.527
957481AF2-042 C
Adder
53.64117647058823545.595
940431AE2-027 C
80/20
14.31814.318
316294AC1-161 C
80/20
5.4825.482
944581AF1-123 C
80/20
50.22150.221
941101AE2-104 C
Adder
3.683.128
934501AD1-074 C
Adder
35.6976470588235330.343
961671AG1-007 C
Adder
0.9317647058823530.792
946301AF1-294 C
Adder
3.4941176470588242.97
942461AE2-259 C
Adder
9.347.939
934621AD1-088 C
Adder
9.4482352941176488.031
316192AB2-158 C
80/20
2.1182.118
942001AE2-212 C
80/20
2.3972.397
962861AG1-135 C
Adder
6.222352941176475.289
943741AF1-042 C
Adder
2.9964705882352942.547
934521AD1-076 C
Adder
12.96470588235294111.02
934511AD1-075 C
Adder
8.9247058823529427.586
316263AC1-034 C
Adder
6.5105882352941185.534
959311AF2-222 C
Adder
15.85294117647058913.475
316240AF1-291 C
80/20
2.3942.394
944641AF1-129 C
80/20
113.49113.49
3150781HOPHCF2
80/20
2.6772.677
3150761HOPPOLC
80/20
1.6841.684
960081AF2-299 C
Adder
1.91411764705882351.627
936261AD2-033 C
Adder
12.4023529411764710.542
961791AG1-021 C
Adder
1.70000000000000021.445
938771AE1-103 C
Adder
3.162.686
963041AG1-153 C
Adder
5.7647058823529424.9
944011AF1-069 C
80/20
13.51813.518
316045AC1-158 C2
80/20
14.96214.962
966881AG1-559 C
Adder
2.3964705882352942.037
3150601CHESTF5
Adder
68.9811764705882458.634
944591AF1-124 C
80/20
50.39950.399
944601AF1-125 C
80/20
49.44749.447
3151101ELIZAR3
80/20
3.5723.572
941591AE2-156 C
80/20
19.79319.793
927021AC1-189 C
Adder
8.4188235294117647.156
926071AC1-086 C
Adder
21.50823529411764718.282
946281AF1-292 C
Adder
1.58470588235294121.347
964241AG1-285 C
Adder
11.97764705882352810.181
962561AG1-105 C
Adder
8.3588235294117657.105
316044AC1-158 C1
80/20
14.96214.962
939261AE1-157 C
Adder
13.77647058823529511.71
316169AC1-164 GEN
Adder
42.77176470588235436.356
3151091ELIZAR2
80/20
3.4653.465
316349AD2-085 C
Adder
3.79058823529411763.222
966621AG1-532 C
Adder
1.43529411764705881.22
3152261N ANNA2
80/20
55.34655.346
3150771HOPHCF1
80/20
2.6772.677
942341AE2-247 C
Adder
1.64235294117647061.396
316274AC1-208 C
Adder
9.0917647058823537.728
962571AG1-106 C
Adder
2.7823529411764712.365
3151311EDGECMA
Adder
15.22352941176470512.94
957871AF2-081 C
Adder
10.989.333
3150651CHESTF6
80/20
20.66420.664
3150861SPRUNCD
80/20
0.1830.183
936591AD2-074 C
Adder
5.7258823529411764.867
3152251N ANNA1
80/20
55.32355.323
3150851SPRUNCC
80/20
0.1830.183
944631AF1-128 C
Adder
43.1623529411764736.688
933291AC2-141 C
80/20
33.66433.664
3150921YORKTN3
Adder
130.26705882352942110.727
3137643SOCKMAN
Adder
0.72705882352941180.618
966661AG1-536 C
Adder
5.5082352941176484.682
939411AE1-173 C
80/20
97.64897.648
3150991CHESPKB
80/20
0.7960.796
940481AE2-033 C
Adder
17.08117647058823614.519
940541AE2-040 C
Adder
3.03764705882352942.582
927041AC1-191 C
Adder
10.0729411764705888.562
963611AG1-210 C
Adder
0.66705882352941170.567
961611AG1-000B C
Adder
17.55647058823529614.923
316375AC2-012 C
80/20
1.4881.488
316233AE1-074 C
80/20
2.8192.819
940551AE2-041 C
Adder
7.4541176470588246.336
943461AF1-017 C
Adder
1.48588235294117641.263
316311AC2-079 C
Adder
6.3129411764705885.366
933981AD1-022 C
Adder
9.2505882352941197.863
938531AE1-072 C
Adder
19.2929411764705916.399
3142366NRTHEST
80/20
0.20.2
3150731STONECA
80/20
7.6067.606
935161AD1-151 C
Adder
17.79176470588235415.123
958161AF2-110 C
Adder
1.50117647058823531.276
316336AC2-165 C
Adder
10.1094117647058828.593
940641AE2-051 C
80/20
18.48818.488
943471AF1-018 C
Adder
7.4541176470588246.336
3152331SURRY 2
80/20
27.29427.294
964791AG1-342 C
Adder
3.32117647058823542.823
316164AC1-076_C
80/20
0.9930.993
3143096IRON208
80/20
0.4840.484
958261AF2-120 C
Adder
6.4035294117647065.443
939191AE1-149 C
80/20
11.90511.905
957601AF2-054 C
Adder
2.2117647058823531.88
957861AF2-080 C
Adder
7.6458823529411766.499
3138533PONTONDP
Adder
0.62941176470588240.535
3150791HOPHCF3
80/20
2.6772.677
961951AG1-038 C
Adder
3.3117647058823532.815
316303AF2-085
80/20
4.3634.363
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.2865.286
CBM South 2LTFEXP_CBM-S2->PJM
CBM
94.17394.173
CPLELTFEXP_CPLE->PJM
CLTF
11.08811.088
TVALTFEXP_TVA->PJM
CLTF
6.1396.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.65727.657
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.08222.082
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.7473.747
LAGNLTFEXP_LAGN->PJM
CLTF
7.6777.677
NYPJM->LTFIMP_NY
CLTF
2.8062.806
LGEELTFEXP_LGEE->PJM
CLTF
1.2221.222
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
SIGELTFEXP_SIGE->PJM
CLTF
0.2370.237

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.55 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4631.32
MW Contribution:2.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316141AB2-099 E
Adder
0.234117647058823540.199
923994AB2-040_E
Adder
5.76941176470588254.904
316088AB2-174 E
Adder
6.1235294117647065.205
924322AB2-079 E O1
Adder
1.23529411764705891.05
946302AF1-294 E
Adder
2.88470588235294122.452
957481AF2-042 C
Adder
53.3270588235294245.328
3151801S ANNAS2
50/50
1.381.38
942002AE2-212 E
Adder
1.2952941176470591.101
940431AE2-027 C
Adder
11.2058823529411789.525
944581AF1-123 C
Adder
42.37411764705882436.018
941101AE2-104 C
Adder
3.10941176470588232.643
934501AD1-074 C
Adder
31.13882352941176626.468
924517AB2-100 E2
Adder
2.74588235294117672.334
937226AE2-253 E
Adder
5.4188235294117654.606
946301AF1-294 C
Adder
3.4070588235294122.896
935172AD1-152 E
Adder
5.1847058823529414.407
942461AE2-259 C
Adder
9.1658823529411777.791
934621AD1-088 C
Adder
9.3717647058823547.966
957482AF2-042 E
Adder
35.55176470588235630.219
208901BRIS G2
50/50
-3.356-3.356
958502AF2-144 E
Adder
1.2588235294117651.07
316192AB2-158 C
50/50
3.6573.657
942001AE2-212 C
Adder
1.94235294117647061.651
939192AE1-149 E
Adder
6.5694117647058825.584
939312AE1-162 E
Adder
1.27764705882352961.086
934065AD1-033 E
Adder
4.6541176470588243.956
926072AC1-086 E
Adder
8.9094117647058837.573
960081AF2-299 C
Adder
1.76235294117647071.498
3145413WATKINS
Adder
0.64235294117647070.546
936261AD2-033 C
Adder
12.02117647058823610.218
962562AG1-105 E
Adder
5.3929411764705884.584
961791AG1-021 C
Adder
1.65764705882352951.409
938771AE1-103 C
Adder
2.72117647058823582.313
963041AG1-153 C
Adder
5.7788235294117654.912
316170AC1-121 C
50/50
2.7692.769
944011AF1-069 C
50/50
13.59813.598
316045AC1-158 C2
50/50
19.48619.486
925332AB2-190 E
Adder
6.8164705882352945.794
927226AC1-216 E
Adder
6.5917647058823535.603
944591AF1-124 C
Adder
42.5247058823529436.146
944601AF1-125 C
Adder
41.7211764705882435.463
941591AE2-156 C
Adder
16.57647058823529614.09
936666AD2-085 E
Adder
5.195294117647064.416
918512AA1-065 E OP
Adder
5.1070588235294124.341
934502AD1-074 E
Adder
15.85176470588235313.474
934512AD1-075 E
Adder
3.96235294117647063.368
924516AB2-100 E1
Adder
2.74588235294117672.334
966621AG1-532 C
Adder
1.32117647058823541.123
919153AA1-139 E2
Adder
3.78941176470588253.221
924022AB2-043 E O1
Adder
4.7941176470588244.075
3147223TWITTYS
Adder
0.87882352941176480.747
959312AF2-222 E
Adder
10.3129411764705888.766
934861AD1-115 C
Adder
2.92.465
3152261N ANNA2
50/50
89.60989.609
940642AE2-051 E
50/50
12.05212.052
942341AE2-247 C
Adder
1.38000000000000011.173
943462AF1-017 E
Adder
2.03764705882352941.732
958162AF2-110 E
Adder
2.01764705882352931.715
934521AD1-076 C
Adder
11.3094117647058829.613
934511AD1-075 C
Adder
7.7847058823529426.617
919692AA2-053 E OP
Adder
3.93176470588235333.342
923573AB1-173 E OP
Adder
3.07647058823529432.615
3145723EMPORIA
Adder
0.405882352941176470.345
920042AA2-088 E OP
Adder
9.8670588235294128.387
925785AC1-054 E
Adder
3.18705882352941172.709
919152AA1-139 E1
Adder
3.78941176470588253.221
959311AF2-222 C
Adder
15.39294117647058813.084
926502AC1-121 E
50/50
1.3031.303
316240AF1-291 C
Adder
1.86705882352941191.587
944641AF1-129 C
Adder
87.4717647058823574.351
924814AB2-134 E
Adder
10.7988235294117659.179
942342AE2-247 E
Adder
1.90588235294117661.62
926071AC1-086 C
Adder
19.57647058823529616.64
946281AF1-292 C
Adder
1.45882352941176461.24
960082AF2-299 E
Adder
1.17529411764705880.999
916042Z1-036 E
Adder
26.4694117647058822.499
923832AB2-022 E
Adder
1.14941176470588240.977
964241AG1-285 C
Adder
11.5811764705882349.844
962561AG1-105 C
Adder
8.0894117647058836.876
958212AF2-115 E
Adder
1.76470588235294111.5
938772AE1-103 E
Adder
3.75764705882352963.194
963042AG1-153 E
Adder
8.6682352941176477.368
925022AB2-158 E
50/50
9.7219.721
316044AC1-158 C1
50/50
19.48619.486
944592AF1-124 E
Adder
97.3823529411764882.775
944582AF1-123 E
Adder
97.0317647058823782.477
316349AD2-085 C
Adder
3.1835294117647062.706
935112AD1-144 E
Adder
0.85764705882352940.729
961942AG1-037 E
Adder
0.311764705882352940.265
961941AG1-037 C
Adder
0.46705882352941180.397
923852AB2-025 E
Adder
1.1282352941176470.959
936262AD2-033 E
Adder
8.0141176470588256.812
958211AF2-115 C
Adder
2.0717647058823531.761
208900BRIS G1
50/50
-2.836-2.836
926214AC1-099 E
Adder
1.1082352941176470.942
932632AC2-084 E
Adder
2.96705882352941152.522
962572AG1-106 E
Adder
1.1082352941176470.942
957872AF2-081 E
Adder
3.9717647058823533.376
924162AB2-060 E OP
Adder
3.95764705882352933.364
964242AG1-285 E
Adder
7.7211764705882356.563
934862AD1-115 E
Adder
4.73176470588235354.022
938562AE1-075 E
Adder
1.0917647058823530.928
3152251N ANNA1
50/50
89.57189.571
938552AE1-074 E
Adder
1.28235294117647071.09
926755AC1-161 E
Adder
12.0070588235294110.206
933291AC2-141 C
Adder
28.12941176470588223.91
925522AC1-027 E
Adder
1.1282352941176470.959
941102AE2-104 E
Adder
4.9423529411764714.201
3145256KINGFORK
Adder
0.92470588235294130.786
923263AB1-132 E OP
Adder
5.697647058823534.843
940481AE2-033 C
Adder
15.6752941176470613.324
940482AE2-033 E
Adder
10.5670588235294118.982
940541AE2-040 C
Adder
2.78823529411764742.37
924312AB2-078 E O1
Adder
1.23529411764705891.05
925612AC1-036 E
Adder
0.79294117647058830.674
966001AG1-469 C
50/50
1.9871.987
925672AC1-043 E
Adder
9.4635294117647078.044
926740AC1-158 E2
50/50
50.96750.967
961611AG1-000B C
Adder
13.8152941176470611.743
920692AA2-178 E
Adder
3.8023529411764713.232
966622AG1-532 E
Adder
0.88117647058823530.749
917122Z2-027 E
Adder
1.24470588235294131.058
3146326AYDLETT TAP
Adder
1.25764705882352931.069
938532AE1-072 E
Adder
8.4941176470588247.22
3147133PAMPLIN
Adder
0.91529411764705890.778
966002AG1-469 E
50/50
0.9930.993
926739AC1-158 E1
50/50
50.96750.967
316233AE1-074 C
Adder
2.5458823529411772.164
935162AD1-151 E
Adder
9.1294117647058827.76
943461AF1-017 C
Adder
1.2482352941176471.061
316311AC2-079 C
Adder
5.3070588235294124.511
932596AC2-079 E
Adder
8.6588235294117667.36
933981AD1-022 C
Adder
8.0941176470588236.88
900672V4-068 E
Adder
0.33058823529411770.281
938531AE1-072 C
Adder
16.29411764705882213.85
924302AB2-077 E O1
Adder
1.23529411764705891.05
3145393UNCAMP
Adder
5.65176470588235354.804
926486AC1-120 E
50/50
4.1534.153
935161AD1-151 C
Adder
13.69411764705882511.64
932046AC2-012 E
Adder
12.12705882352941210.308
958161AF2-110 C
Adder
1.26823529411764711.078
933982AD1-022 E
Adder
4.4070588235294123.746
3145946PLYMOUTH TP
Adder
0.29882352941176470.254
927146AC1-208 E
Adder
1.16941176470588240.994
934612AD1-087 E
Adder
3.50941176470588272.983
934622AD1-088 E
Adder
4.5117647058823533.835
316336AC2-165 C
Adder
10.0588235294117668.55
926004AC1-076_E
50/50
6.486.48
940641AE2-051 C
50/50
18.07818.078
316084AB2-161 E
Adder
5.0917647058823544.328
943172AE2-346 E
Adder
0.56117647058823530.477
917332KELFORD E
Adder
1.51764705882352961.29
925122AB2-169 E
Adder
5.2764705882352954.485
934522AD1-076 E
Adder
5.7635294117647064.899
940492AE2-034 E
Adder
2.85176470588235282.424
316274AC1-208 C
Adder
8.2905882352941187.047
962571AG1-106 C
Adder
2.53176470588235342.152
918492AA1-063AE OP
Adder
3.80117647058823543.231
957871AF2-081 C
Adder
9.2670588235294127.877
961792AG1-021 E
Adder
1.4117647058823531.2
937482AD2-202 E
Adder
1.02705882352941180.873
3145506HICKORY
Adder
2.02235294117647071.719
946262AF1-291 E
Adder
1.24470588235294131.058
3150651CHESTF6
Adder
15.92588235294117813.537
933292AC2-141 E
Adder
12.0070588235294110.206
934576AD1-082 E
Adder
4.0564705882352943.448
944602AF1-125 E
Adder
95.5082352941176581.182
943612AF1-032 E
Adder
0.85764705882352940.729
3151761LOISA E
50/50
5.5965.596
3151771S ANNAG1
50/50
2.6852.685
3151791S ANNAG2
50/50
2.6852.685
3151781S ANNAS1
50/50
1.381.38
923862AB2-026 E
Adder
1.28117647058823541.089
941031AE2-094 C
50/50
41.61841.618
941032AE2-094 E
50/50
18.6418.64
3150831SPRUNCA
Adder
8.1435294117647056.922
3150841SPRUNCB
Adder
8.1435294117647056.922
939412AE1-173 E
Adder
61.5211764705882452.293
926662AC1-147 E
Adder
1.22588235294117661.042
916192Z1-068 E
Adder
1.74235294117647071.481
957492AF2-043 E
Adder
1.31882352941176471.121
926206AC1-098 E
Adder
3.35647058823529452.853
901082W1-029 E
Adder
29.54000000000000325.109
942462AE2-259 E
Adder
6.1105882352941175.194
3151731LOISA B
50/50
2.7452.745
3151751LOISA D
50/50
2.7452.745
3143316POE
Adder
1.28823529411764711.095
316164AC1-076_C
50/50
1.1311.131
939191AE1-149 C
Adder
9.8529411764705898.375
3137643SOCKMAN
Adder
0.66588235294117650.566
913392Y1-086 E
Adder
2.03647058823529431.731
933502AC2-165 E
Adder
7.5705882352941176.435
3151741LOISA C
50/50
2.7452.745
3151721LOISA A
50/50
2.7312.731
940432AE2-027 E
Adder
7.4705882352941186.35
939411AE1-173 C
Adder
92.2811764705882478.439
934012AD1-025 E
Adder
8.5352941176470597.255
946282AF1-292 E
Adder
0.97294117647058820.827
3138533PONTONDP
Adder
0.61411764705882350.522
316257AC1-043 C
Adder
5.84.93
316254AC1-120 C
50/50
8.0618.061
944012AF1-069 E
50/50
5.2835.283
316303AF2-085
50/50
4.3644.364
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.0035.003
CBM South 2LTFEXP_CBM-S2->PJM
CBM
88.42988.429
CPLELTFEXP_CPLE->PJM
CLTF
10.49610.496
TVALTFEXP_TVA->PJM
CLTF
5.6275.627
O66PJM->LTFIMP_O-066
CMTX_NF
36.7236.72
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.22125.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.23820.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.4183.418
LAGNLTFEXP_LAGN->PJM
CLTF
7.0687.068
NYPJM->LTFIMP_NY
CLTF
2.7142.714
LGEELTFEXP_LGEE->PJM
CLTF
1.0981.098
WECLTFEXP_WEC->PJM
CLTF
0.5410.541
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7645.764
SIGELTFEXP_SIGE->PJM
CLTF
0.2140.214
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 246_SRT-A'
 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1   /*6SUFFOLK     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1   /*6EARLEYS     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1   /*6NUCO TP     230.0 - 6NUCOR       230.0
 OPEN BUS 314575                                   /*6NUCO TP     230.0
 OPEN BUS 314590                                   /*6NUCOR       230.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A'
 OPEN BRANCH FROM BUS 304183 TO BUS 314935 CKT 1   /*8WAKE 500 TT 500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: 545T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314916 CKT 1                /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314063 TO BUS 314916 CKT 1                /*6MORRSVL     230.0 - 8MORRSVL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BUS 314897                                                /*8MORRS_1     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 568T575_SRT-A'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1   /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1   /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
314282 to 314285 ckt 1
314563 to 940480 ckt 1
314435 to 314282 ckt 1
314902 to 314914 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314911 to 314922 ckt 1
314914 to 314918 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314934 to 314916 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC101.12 %678.68B686.281.36
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC100.08 %678.68B679.211.36
GD1DVP
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
OPAC107.58 %571.52B614.820.97
GD1DVP
6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC100.11 %984.18B985.291.36
GD1DVP
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC103.74 %984.18B1020.961.36
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Base Case
OPAC109.02 %678.68A739.927.18
GD1DVP
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2092_SRT-A
OPAC166.69 %571.52B952.641.85
GD1DVP
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Base Case
OPAC111.43 %571.52A636.851.54
GD1DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
DVP_P1-2: LN 557_SRT-S
OPAC108.08 %879.84B950.941.41
GD1CPLE/DVP
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
RKYMT-WILS230_&_RKYMT-SHARPB115_SRT-S
OPAC106.07 %478.0B507.021.31
GD1DVP
6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
OPAC108.24 %571.52B618.610.97
GD1DVP
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
OPAC117.46 %678.68B797.161.15
GD1DVP
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
DVP_P1-2: LN 2092_SRT-A
OPAC161.64 %571.52B923.831.85
GD1DVP
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Base Case
OPAC106.53 %571.52A608.851.54
GD1DVP
6PEMBROKE-6WALBMRL 230.0 kV Ckt 1 line
DVP_P1-2: LN 238_SRT-A-1
OPAC106.27 %733.2B779.151.55
GD1DVP
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
OPAC107.58 %571.52B614.810.97
GD1DVP
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line
DVP_P1-2: LN 238_SRT-A-1
OPAC104.54 %733.2B766.491.55
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Base Case
OPAC127.47 %678.68A865.087.18
GD1DVP
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC103.68 %984.18B1020.421.36
GD1DVP
6WALBMRL-6S HERTFORD 230.0 kV Ckt 1 line
DVP_P1-2: LN 238_SRT-A-1
OPAC104.95 %733.2B769.481.55
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Base Case
OPAC104.12 %3220.44A3352.993.62
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC136.21 %2442.12B3326.43.84
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC115.81 %4070.2B4713.594.46
GD1DVP
8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
OPAC113.6 %3220.44B3658.562.85
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
OPAC126.88 %1058.16B1342.551.33
GD1DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC106.42 %2442.12B2598.932.57
GD1DVP
AD1-056 TP-6HATHAWAY 230.0 kV Ckt 1 line
DVP_P1-2: LN 238_SRT-A-1
OPAC105.88 %441.8B467.794.55
GD1DVP
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Base Case
OPAC124.4 %678.68A844.267.18

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:101.12 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:686.28
MW Contribution:1.36
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:107.88 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:732.13
MW Contribution:1.43
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
Adder
6.297647058823535.353
316336AC2-165 C
50/50
15.41215.412
934622AD1-088 E
50/50
3.2433.243
934612AD1-087 E
Adder
2.13647058823529431.816
927255AC1-221 E
Adder
1.72235294117647061.464
938552AE1-074 E
Adder
0.60823529411764710.517
938562AE1-075 E
50/50
1.3971.397
964242AG1-285 E
50/50
6.4876.487
3151911BEARGRDN G1
50/50
13.38913.389
924162AB2-060 E OP
50/50
3.163.16
313527AB2-043 C
50/50
0.3720.372
964792AG1-342 E
Adder
1.45411764705882351.236
932763AC2-100 E
Adder
1.15411764705882350.981
3145723EMPORIA
Adder
0.187058823529411780.159
923573AB1-173 E OP
Adder
1.4035294117647061.193
919692AA2-053 E OP
Adder
1.73294117647058841.473
959311AF2-222 C
50/50
16.21416.214
925785AC1-054 E
Adder
1.7588235294117651.495
940451AE2-029 C
Adder
-2.1529411764705886-1.83
316313AB2-026 C
50/50
0.5060.506
918492AA1-063AE OP
Adder
1.64941176470588241.402
937482AD2-202 E
Adder
0.62470588235294120.531
961792AG1-021 E
50/50
1.7981.798
3151921BEARGRDN G2
50/50
13.38913.389
942462AE2-259 E
50/50
9.6239.623
316239AB2-077 C O1
50/50
0.2330.233
964791AG1-342 C
Adder
2.18117647058823531.854
3150841SPRUNCB
Adder
3.52.975
3150831SPRUNCA
Adder
3.52.975
939412AE1-173 E
Adder
21.52705882352941218.298
923862AB2-026 E
50/50
1.6391.639
941032AE2-094 E
Adder
6.83647058823529455.811
941031AE2-094 C
Adder
15.26470588235294212.975
923852AB2-025 E
Adder
0.428235294117647050.364
958211AF2-115 C
50/50
2.6382.638
939411AE1-173 C
Adder
32.29058823529411627.447
933502AC2-165 E
50/50
11.611.6
3137643SOCKMAN
Adder
0.30117647058823530.256
958502AF2-144 E
50/50
1.611.61
924517AB2-100 E2
Adder
1.11058823529411770.944
957482AF2-042 E
Adder
20.7517647058823517.639
934621AD1-088 C
50/50
6.7356.735
942461AE2-259 C
50/50
14.43514.435
946301AF1-294 C
50/50
4.3394.339
935172AD1-152 E
Adder
3.09058823529411742.627
938822AE1-108 E
Adder
3.71882352941176463.161
940642AE2-051 E
Adder
4.1988235294117653.569
924516AB2-100 E1
Adder
1.11058823529411770.944
966621AG1-532 C
Adder
0.61058823529411770.519
3147223TWITTYS
50/50
0.8960.896
959312AF2-222 E
50/50
10.86410.864
924022AB2-043 E O1
50/50
3.7383.738
316405AF2-144 C
50/50
0.3950.395
957481AF2-042 C
Adder
31.1270588235294126.458
316088AB2-174 E
Adder
2.8035294117647062.383
923994AB2-040_E
Adder
2.6317647058823532.237
946302AF1-294 E
50/50
3.6743.674
924322AB2-079 E O1
50/50
0.9490.949
943902AF1-058 E
Adder
0.69647058823529410.592
944012AF1-069 E
Adder
1.93764705882352951.647
946282AF1-292 E
Adder
0.44941176470588240.382
3138533PONTONDP
50/50
0.7820.782
316131AB2-060 C
50/50
1.0971.097
944011AF1-069 C
Adder
4.9870588235294124.239
963041AG1-153 C
Adder
2.2447058823529411.908
960081AF2-299 C
Adder
0.81294117647058820.691
924032AB2-045 E
50/50
2.9052.905
3144293JTRSVLE
50/50
0.4860.486
961791AG1-021 C
50/50
2.1112.111
936261AD2-033 C
50/50
11.9511.95
962562AG1-105 E
Adder
3.74705882352941183.185
316258AE1-075 C
50/50
0.4640.464
963042AG1-153 E
Adder
3.3670588235294122.862
960082AF2-299 E
Adder
0.54235294117647060.461
946281AF1-292 C
Adder
0.67294117647058820.572
964241AG1-285 C
50/50
9.7319.731
316034AC1-036 C
50/50
0.2210.221
958212AF2-115 E
50/50
2.2482.248
962561AG1-105 C
Adder
5.6211764705882354.778
936262AD2-033 E
50/50
7.9677.967
316233AE1-074 C
Adder
1.20705882352941171.026
966622AG1-532 E
Adder
0.407058823529411750.346
3147133PAMPLIN
50/50
1.231.23
316322AB2-045 C
50/50
0.6480.648
3151931BEARGRDN S1
50/50
17.32117.321
927264AC1-222 E
Adder
2.09764705882352941.783
924302AB2-077 E O1
50/50
0.9490.949
940541AE2-040 C
Adder
1.05764705882352940.899
940481AE2-033 C
Adder
6.05.1
940482AE2-033 E
Adder
4.0447058823529413.438
925612AC1-036 E
50/50
0.8090.809
316238AB2-078 C O1
50/50
0.2330.233
924312AB2-078 E O1
50/50
0.9490.949
316237AB2-079 C O1
50/50
0.2330.233
926274AC1-105 E
Adder
1.55058823529411781.318
938821AE1-108 C
Adder
7.7941176470588236.625
316303AF2-085
50/50
2.1712.171
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9041.904
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.16230.162
CPLELTFEXP_CPLE->PJM
CLTF
4.0014.001
TVALTFEXP_TVA->PJM
CLTF
1.171.17
O66PJM->LTFIMP_O-066
CMTX_NF
5.2725.272
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8220.822
SIGELTFEXP_SIGE->PJM
CLTF
0.010.01
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.3713.371
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0190.019
MECLTFEXP_MEC->PJM
CLTF
0.2690.269
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0350.035
LAGNLTFEXP_LAGN->PJM
CLTF
1.5461.546
NYPJM->LTFIMP_NY
CLTF
0.4340.434

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.08 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:679.21
MW Contribution:1.36
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.82 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:724.99
MW Contribution:1.43
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
Adder
6.297647058823535.353
316336AC2-165 C
50/50
15.41215.412
934622AD1-088 E
50/50
3.2433.243
934612AD1-087 E
Adder
2.13647058823529431.816
927255AC1-221 E
Adder
1.72235294117647061.464
938552AE1-074 E
Adder
0.60823529411764710.517
938562AE1-075 E
50/50
1.3971.397
964242AG1-285 E
50/50
6.4876.487
3151911BEARGRDN G1
50/50
13.38913.389
924162AB2-060 E OP
50/50
3.163.16
313527AB2-043 C
50/50
0.3720.372
964792AG1-342 E
Adder
1.45411764705882351.236
932763AC2-100 E
Adder
1.15411764705882350.981
3145723EMPORIA
Adder
0.187058823529411780.159
923573AB1-173 E OP
Adder
1.4035294117647061.193
919692AA2-053 E OP
Adder
1.73294117647058841.473
959311AF2-222 C
50/50
16.21416.214
925785AC1-054 E
Adder
1.7588235294117651.495
940451AE2-029 C
Adder
-2.1529411764705886-1.83
316313AB2-026 C
50/50
0.5060.506
918492AA1-063AE OP
Adder
1.64941176470588241.402
937482AD2-202 E
Adder
0.62470588235294120.531
961792AG1-021 E
50/50
1.7981.798
3151921BEARGRDN G2
50/50
13.38913.389
942462AE2-259 E
50/50
9.6239.623
316239AB2-077 C O1
50/50
0.2330.233
964791AG1-342 C
Adder
2.18117647058823531.854
939411AE1-173 C
Adder
32.29058823529411627.447
933502AC2-165 E
50/50
11.611.6
3137643SOCKMAN
Adder
0.30117647058823530.256
958502AF2-144 E
50/50
1.611.61
924517AB2-100 E2
Adder
1.11058823529411770.944
957482AF2-042 E
Adder
20.7517647058823517.639
934621AD1-088 C
50/50
6.7356.735
942461AE2-259 C
50/50
14.43514.435
946301AF1-294 C
50/50
4.3394.339
935172AD1-152 E
Adder
3.09058823529411742.627
938822AE1-108 E
Adder
3.71882352941176463.161
940642AE2-051 E
Adder
4.1988235294117653.569
924516AB2-100 E1
Adder
1.11058823529411770.944
966621AG1-532 C
Adder
0.61058823529411770.519
3147223TWITTYS
50/50
0.8960.896
959312AF2-222 E
50/50
10.86410.864
924022AB2-043 E O1
50/50
3.7383.738
316405AF2-144 C
50/50
0.3950.395
957481AF2-042 C
Adder
31.1270588235294126.458
316088AB2-174 E
Adder
2.8035294117647062.383
923994AB2-040_E
Adder
2.6317647058823532.237
946302AF1-294 E
50/50
3.6743.674
924322AB2-079 E O1
50/50
0.9490.949
943902AF1-058 E
Adder
0.69647058823529410.592
944012AF1-069 E
Adder
1.93764705882352951.647
946282AF1-292 E
Adder
0.44941176470588240.382
3138533PONTONDP
50/50
0.7820.782
316131AB2-060 C
50/50
1.0971.097
944011AF1-069 C
Adder
4.9870588235294124.239
963041AG1-153 C
Adder
2.2447058823529411.908
960081AF2-299 C
Adder
0.81294117647058820.691
924032AB2-045 E
50/50
2.9052.905
3144293JTRSVLE
50/50
0.4860.486
961791AG1-021 C
50/50
2.1112.111
936261AD2-033 C
50/50
11.9511.95
962562AG1-105 E
Adder
3.74705882352941183.185
316258AE1-075 C
50/50
0.4640.464
963042AG1-153 E
Adder
3.3670588235294122.862
960082AF2-299 E
Adder
0.54235294117647060.461
946281AF1-292 C
Adder
0.67294117647058820.572
964241AG1-285 C
50/50
9.7319.731
316034AC1-036 C
50/50
0.2210.221
958212AF2-115 E
50/50
2.2482.248
962561AG1-105 C
Adder
5.6211764705882354.778
3150841SPRUNCB
Adder
3.52.975
3150831SPRUNCA
Adder
3.52.975
939412AE1-173 E
Adder
21.52705882352941218.298
923862AB2-026 E
50/50
1.6391.639
941032AE2-094 E
Adder
6.83647058823529455.811
941031AE2-094 C
Adder
15.26470588235294212.975
923852AB2-025 E
Adder
0.428235294117647050.364
958211AF2-115 C
50/50
2.6382.638
936262AD2-033 E
50/50
7.9677.967
316233AE1-074 C
Adder
1.20705882352941171.026
966622AG1-532 E
Adder
0.407058823529411750.346
3147133PAMPLIN
50/50
1.231.23
316322AB2-045 C
50/50
0.6480.648
3151931BEARGRDN S1
50/50
17.32117.321
927264AC1-222 E
Adder
2.09764705882352941.783
924302AB2-077 E O1
50/50
0.9490.949
940541AE2-040 C
Adder
1.05764705882352940.899
940481AE2-033 C
Adder
6.05.1
940482AE2-033 E
Adder
4.0447058823529413.438
925612AC1-036 E
50/50
0.8090.809
316238AB2-078 C O1
50/50
0.2330.233
924312AB2-078 E O1
50/50
0.9490.949
316237AB2-079 C O1
50/50
0.2330.233
926274AC1-105 E
Adder
1.55058823529411781.318
938821AE1-108 C
Adder
7.7941176470588236.625
316303AF2-085
50/50
2.1712.171
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9041.904
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.16230.162
CPLELTFEXP_CPLE->PJM
CLTF
4.0014.001
TVALTFEXP_TVA->PJM
CLTF
1.171.17
O66PJM->LTFIMP_O-066
CMTX_NF
5.2725.272
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8220.822
SIGELTFEXP_SIGE->PJM
CLTF
0.010.01
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.3713.371
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0190.019
MECLTFEXP_MEC->PJM
CLTF
0.2690.269
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0350.035
LAGNLTFEXP_LAGN->PJM
CLTF
1.5461.546
NYPJM->LTFIMP_NY
CLTF
0.4340.434

Details for 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:107.58 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:614.82
MW Contribution:0.97
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.99 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:645.76
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
937482AD2-202 E
50/50
1.621.62
3151581KERR 1
50/50
0.3970.397
3151601KERR 3
50/50
1.1131.113
3152661PLYWOOD A
50/50
1.3061.306
941011AE2-092 C
Adder
-7.384705882352941-6.277
3137643SOCKMAN
Adder
0.236470588235294130.201
937481AD2-202 C
50/50
0.5570.557
3151641KERR 7
50/50
1.1131.113
316205AC1-080 C
50/50
0.2470.247
316123AC1-075 C
50/50
0.740.74
924302AB2-077 E O1
50/50
1.321.32
3151621KERR 5
50/50
1.1131.113
316222AC1-221 C
50/50
1.3041.304
942752AE2-291 E
50/50
4.2094.209
925612AC1-036 E
50/50
0.6080.608
316238AB2-078 C O1
50/50
0.3240.324
924312AB2-078 E O1
50/50
1.321.32
316237AB2-079 C O1
50/50
0.3240.324
926274AC1-105 E
50/50
2.892.89
938821AE1-108 C
Adder
-8.042352941176471-6.836
316336AC2-165 C
Adder
-4.488235294117647-3.815
934622AD1-088 E
50/50
8.0788.078
934611AD1-087 C
50/50
1.9191.919
934612AD1-087 E
50/50
5.5365.536
3151611KERR 4
50/50
1.1131.113
927255AC1-221 E
50/50
3.413.41
964242AG1-285 E
50/50
10.84610.846
924162AB2-060 E OP
50/50
3.9993.999
313527AB2-043 C
50/50
0.5090.509
3151591KERR 2
50/50
1.1131.113
964792AG1-342 E
50/50
2.4822.482
316283AC2-100 C
50/50
1.0191.019
932763AC2-100 E
50/50
2.2422.242
3145723EMPORIA
Adder
0.136470588235294120.116
923573AB1-173 E OP
Adder
1.06470588235294120.905
919692AA2-053 E OP
Adder
1.31411764705882361.117
959311AF2-222 C
Adder
9.9482352941176468.456
925785AC1-054 E
50/50
2.3712.371
942751AE2-291 C
50/50
6.3136.313
316239AB2-077 C O1
50/50
0.3240.324
935171AD1-152 C
50/50
1.8391.839
964791AG1-342 C
50/50
3.7243.724
925997AC1-075 E
50/50
2.5662.566
936262AD2-033 E
Adder
3.5152941176470592.988
957482AF2-042 E
50/50
57.29557.295
934621AD1-088 C
50/50
16.77816.778
942461AE2-259 C
Adder
-11.085882352941177-9.423
935172AD1-152 E
50/50
7.5637.563
966621AG1-532 C
Adder
0.437647058823529440.372
3147223TWITTYS
50/50
0.6740.674
959312AF2-222 E
Adder
6.66588235294117755.666
924022AB2-043 E O1
50/50
5.1075.107
316003AC1-222 C
50/50
1.0461.046
926024AC1-080 E
50/50
0.8510.851
957481AF2-042 C
50/50
85.94285.942
316088AB2-174 E
Adder
2.0917647058823531.778
923994AB2-040_E
Adder
1.99764705882352931.698
924322AB2-079 E O1
50/50
1.321.32
943902AF1-058 E
50/50
1.4231.423
946282AF1-292 E
Adder
0.32235294117647060.274
3151541CLOVER2
50/50
19.33819.338
316131AB2-060 C
50/50
1.3891.389
316129AC1-054 C
50/50
0.8410.841
316118AC1-105 C
50/50
0.9880.988
960081AF2-299 C
Adder
0.58352941176470590.496
936261AD2-033 C
Adder
5.2729411764705894.482
3151631KERR 6
50/50
1.1131.113
962562AG1-105 E
50/50
6.1616.161
316248AF1-058 C
50/50
0.3490.349
960082AF2-299 E
Adder
0.38941176470588240.331
946281AF1-292 C
Adder
0.48352941176470590.411
3151531CLOVER1
50/50
19.51919.519
964241AG1-285 C
50/50
16.2716.27
316034AC1-036 C
50/50
0.1660.166
962561AG1-105 C
50/50
9.2429.242
966622AG1-532 E
Adder
0.29176470588235290.248
927264AC1-222 E
50/50
4.2714.271
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6471.647
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.50427.504
CPLELTFEXP_CPLE->PJM
CLTF
3.4573.457
TVALTFEXP_TVA->PJM
CLTF
1.5461.546
O66PJM->LTFIMP_O-066
CMTX_NF
3.8923.892
G-007PJM->LTFIMP_G-007
CMTX_NF
0.610.61
SIGELTFEXP_SIGE->PJM
CLTF
0.0570.057
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.2877.287
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.6115.611
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.9490.949
LAGNLTFEXP_LAGN->PJM
CLTF
1.9781.978
NYPJM->LTFIMP_NY
CLTF
0.2910.291
LGEELTFEXP_LGEE->PJM
CLTF
0.2860.286
WECLTFEXP_WEC->PJM
CLTF
0.1510.151

Details for 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.11 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:985.29
MW Contribution:1.36
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:96.98 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:954.41
MW Contribution:1.3
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316084AB2-161 E
50/50
3.213.21
316083AB2-161 C
50/50
0.3210.321
940641AE2-051 C
Adder
6.0952941176470595.181
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
933982AD1-022 E
Adder
1.721.462
934622AD1-088 E
Adder
1.38117647058823521.174
934612AD1-087 E
Adder
1.1117647058823530.945
927146AC1-208 E
Adder
1.51.275
3150761HOPPOLC
50/50
1.0021.002
926755AC1-161 E
Adder
3.78588235294117673.218
933291AC2-141 C
Adder
8.8694117647058827.539
925522AC1-027 E
Adder
0.410588235294117640.349
3145256KINGFORK
Adder
0.357647058823529430.304
957872AF2-081 E
Adder
1.4317647058823531.217
941102AE2-104 E
Adder
2.0188235294117651.716
962572AG1-106 E
Adder
0.50117647058823530.426
964242AG1-285 E
Adder
2.5717647058823532.186
924162AB2-060 E OP
Adder
1.3117647058823531.115
932632AC2-084 E
Adder
1.20235294117647061.022
926214AC1-099 E
Adder
0.44941176470588240.382
944641AF1-129 C
50/50
120.262120.262
316240AF1-291 C
50/50
2.4482.448
3150651CHESTF6
50/50
21.89721.897
946262AF1-291 E
50/50
1.6321.632
933292AC2-141 E
Adder
3.78588235294117673.218
934576AD1-082 E
50/50
2.5582.558
944602AF1-125 E
Adder
33.8847058823529428.802
3145506HICKORY
Adder
0.72352941176470590.615
957871AF2-081 C
Adder
3.34117647058823542.84
943612AF1-032 E
Adder
0.320.272
940492AE2-034 E
Adder
1.09058823529411760.927
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
918492AA1-063AE OP
Adder
1.59411764705882361.355
962571AG1-106 C
Adder
1.14705882352941170.975
937482AD2-202 E
Adder
0.32588235294117650.277
917332KELFORD E
Adder
0.61411764705882350.522
925122AB2-169 E
Adder
2.04352941176470631.737
316274AC1-208 C
Adder
3.3788235294117652.872
917342Z2-044 E
Adder
0.215294117647058830.183
3151311EDGECMA
Adder
5.5117647058823534.685
3143316POE
50/50
1.0861.086
939191AE1-149 C
50/50
7.1377.137
901082W1-029 E
Adder
10.9870588235294139.339
926206AC1-098 E
Adder
1.35999999999999991.156
924814AB2-134 E
Adder
6.7529411764705885.74
316381AD1-082 C
50/50
0.7330.733
942342AE2-247 E
Adder
0.94470588235294130.803
919152AA1-139 E1
Adder
1.36588235294117651.161
920042AA2-088 E OP
Adder
4.0811764705882353.469
934521AD1-076 C
Adder
4.377647058823533.721
934511AD1-075 C
Adder
3.01411764705882362.562
3145723EMPORIA
Adder
0.185882352941176470.158
923573AB1-173 E OP
Adder
1.36823529411764721.163
919692AA2-053 E OP
Adder
1.64941176470588241.402
925785AC1-054 E
Adder
1.2082352941176471.027
316263AC1-034 C
Adder
2.3517647058823531.999
940432AE2-027 E
Adder
4.6964705882352943.992
934012AD1-025 E
Adder
5.3364705882352944.536
939411AE1-173 C
Adder
31.5352941176470626.805
913392Y1-086 E
Adder
0.74470588235294120.633
3137643SOCKMAN
Adder
0.288235294117647030.245
919710AA2-057 E
Adder
1.44823529411764731.231
3150781HOPHCF2
50/50
1.5941.594
942001AE2-212 C
50/50
2.1112.111
939192AE1-149 E
50/50
4.7584.758
939312AE1-162 E
Adder
0.5717647058823530.486
934065AD1-033 E
Adder
1.6670588235294121.417
937226AE2-253 E
Adder
1.9482352941176471.656
924517AB2-100 E2
Adder
1.36823529411764721.163
934501AD1-074 C
Adder
12.05529411764705810.247
957482AF2-042 E
Adder
11.3435294117647069.642
934621AD1-088 C
Adder
2.86941176470588262.439
935172AD1-152 E
Adder
1.6435294117647061.397
961671AG1-007 C
Adder
0.332941176470588240.283
316132AB2-190 C
50/50
2.4122.412
940642AE2-051 E
Adder
4.0635294117647063.454
942341AE2-247 C
Adder
0.68470588235294120.582
943462AF1-017 E
Adder
1.00941176470588250.858
919153AA1-139 E2
Adder
1.36588235294117651.161
958162AF2-110 E
Adder
0.82470588235294120.701
924516AB2-100 E1
Adder
1.36823529411764721.163
934512AD1-075 E
Adder
1.53411764705882361.304
934502AD1-074 E
Adder
6.1364705882352945.216
966621AG1-532 C
Adder
0.61294117647058830.521
918512AA1-065 E OP
Adder
2.04235294117647071.736
924022AB2-043 E O1
Adder
1.60117647058823541.361
918532AA1-067 E
Adder
0.251764705882352950.214
3150771HOPHCF1
50/50
1.5941.594
940431AE2-027 C
Adder
7.0447058823529425.988
942002AE2-212 E
50/50
1.4081.408
944581AF1-123 C
Adder
15.03411764705882412.779
941101AE2-104 C
Adder
1.26941176470588221.079
957481AF2-042 C
Adder
17.0152941176470614.463
316088AB2-174 E
Adder
2.7588235294117652.345
316141AB2-099 E
Adder
0.095294117647058830.081
923994AB2-040_E
Adder
2.56588235294117652.181
924322AB2-079 E O1
Adder
0.41176470588235290.35
961672AG1-007 E
Adder
0.188235294117647060.16
944012AF1-069 E
Adder
1.7917647058823531.523
946282AF1-292 E
Adder
0.45058823529411770.383
957861AF2-080 C
Adder
2.7023529411764712.297
917512Z2-088 E OP1
Adder
1.73411764705882351.474
925332AB2-190 E
50/50
4.6914.691
927226AC1-216 E
Adder
4.122352941176473.504
941591AE2-156 C
Adder
6.1141176470588245.197
944601AF1-125 C
Adder
14.80235294117647312.582
944591AF1-124 C
Adder
15.08705882352941312.824
936666AD2-085 E
Adder
2.5752941176470592.189
944011AF1-069 C
Adder
4.6141176470588243.922
938771AE1-103 C
Adder
1.11764705882352940.95
3145413WATKINS
Adder
0.26470588235294120.225
963041AG1-153 C
Adder
1.9482352941176471.656
960081AF2-299 C
Adder
0.81647058823529410.694
926072AC1-086 E
Adder
4.0352941176470593.43
957862AF2-080 E
Adder
1.19764705882352951.018
944582AF1-123 E
Adder
34.4258823529411829.262
944592AF1-124 E
Adder
34.55058823529411429.368
935112AD1-144 E
Adder
0.33176470588235290.282
316349AD2-085 C
Adder
1.57882352941176471.342
923832AB2-022 E
Adder
0.421176470588235260.358
938772AE1-103 E
Adder
1.5435294117647061.312
916042Z1-036 E
Adder
9.9682352941176488.473
963042AG1-153 E
Adder
2.92235294117647062.484
960082AF2-299 E
Adder
0.54470588235294130.463
946281AF1-292 C
Adder
0.67529411764705880.574
926071AC1-086 C
Adder
8.8647058823529427.535
964241AG1-285 C
Adder
3.85882352941176483.28
927021AC1-189 C
Adder
2.97529411764705862.529
924152AB2-059 E OP
Adder
1.87058823529411791.59
3150841SPRUNCB
Adder
2.6776470588235292.276
3150831SPRUNCA
Adder
2.6776470588235292.276
3150791HOPHCF3
50/50
1.5941.594
3150801HOPHCF4
50/50
2.4192.419
926662AC1-147 E
Adder
0.452941176470588240.385
916192Z1-068 E
Adder
0.63294117647058830.538
939412AE1-173 E
Adder
21.0235294117647117.87
957492AF2-043 E
Adder
0.49294117647058820.419
941032AE2-094 E
Adder
6.3247058823529425.376
941031AE2-094 C
Adder
14.12000000000000112.002
923852AB2-025 E
Adder
0.6317647058823530.537
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
934332AD1-057 E
Adder
0.69647058823529410.592
934321AD1-056 C
Adder
2.3988235294117652.039
934322AD1-056 E
Adder
1.30117647058823541.106
934331AD1-057 C
Adder
1.33882352941176451.138
927022AC1-189 E
Adder
1.48235294117647071.26
925595AC1-034 E
Adder
1.77411764705882361.508
935162AD1-151 E
50/50
6.0156.015
943461AF1-017 C
Adder
0.61882352941176480.526
932596AC2-079 E
Adder
4.1964705882352953.567
316311AC2-079 C
Adder
2.5717647058823532.186
938532AE1-072 E
Adder
3.07058823529411742.61
3146326AYDLETT TAP
Adder
0.455294117647058850.387
917122Z2-027 E
Adder
0.457647058823529460.389
920692AA2-178 E
Adder
1.4552941176470591.237
966622AG1-532 E
Adder
0.408235294117647030.347
922923AB1-081 E OP
Adder
1.321.122
3150731STONECA
50/50
4.5124.512
935161AD1-151 C
50/50
9.0229.022
932046AC2-012 E
Adder
4.4823529411764713.81
938531AE1-072 C
Adder
5.8905882352941185.007
958161AF2-110 C
Adder
0.51764705882352950.44
3145393UNCAMP
Adder
2.3247058823529411.976
933981AD1-022 C
Adder
3.162.686
900672V4-068 E
Adder
0.136470588235294120.116
924302AB2-077 E O1
Adder
0.41176470588235290.35
961611AG1-000B C
Adder
7.342352941176476.241
940541AE2-040 C
Adder
1.56117647058823541.327
940481AE2-033 C
Adder
8.6517647058823537.354
940482AE2-033 E
Adder
5.8329411764705884.958
923263AB1-132 E OP
Adder
2.582.193
924312AB2-078 E O1
Adder
0.41176470588235290.35
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
TVALTFEXP_TVA->PJM
CLTF
1.561.56
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
NYPJM->LTFIMP_NY
CLTF
0.4360.436
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
WECLTFEXP_WEC->PJM
CLTF
0.140.14

Details for 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.74 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1020.96
MW Contribution:1.36
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.61 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:990.18
MW Contribution:1.3
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150841SPRUNCB
Adder
2.6776470588235292.276
3150831SPRUNCA
Adder
2.6776470588235292.276
3150791HOPHCF3
50/50
1.5941.594
3150801HOPHCF4
50/50
2.4192.419
926662AC1-147 E
Adder
0.452941176470588240.385
916192Z1-068 E
Adder
0.63294117647058830.538
939412AE1-173 E
Adder
21.0235294117647117.87
957492AF2-043 E
Adder
0.49294117647058820.419
941032AE2-094 E
Adder
6.3247058823529425.376
941031AE2-094 C
Adder
14.12000000000000112.002
923852AB2-025 E
Adder
0.6317647058823530.537
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
934332AD1-057 E
Adder
0.69647058823529410.592
934321AD1-056 C
Adder
2.3988235294117652.039
934322AD1-056 E
Adder
1.30117647058823541.106
934331AD1-057 C
Adder
1.33882352941176451.138
927022AC1-189 E
Adder
1.48235294117647071.26
925595AC1-034 E
Adder
1.77411764705882361.508
944641AF1-129 C
50/50
120.262120.262
316240AF1-291 C
50/50
2.4482.448
924814AB2-134 E
Adder
6.7529411764705885.74
316381AD1-082 C
50/50
0.7330.733
942342AE2-247 E
Adder
0.94470588235294130.803
919152AA1-139 E1
Adder
1.36588235294117651.161
920042AA2-088 E OP
Adder
4.0811764705882353.469
934521AD1-076 C
Adder
4.377647058823533.721
934511AD1-075 C
Adder
3.01411764705882362.562
3145723EMPORIA
Adder
0.185882352941176470.158
923573AB1-173 E OP
Adder
1.36823529411764721.163
919692AA2-053 E OP
Adder
1.64941176470588241.402
925785AC1-054 E
Adder
1.2082352941176471.027
316263AC1-034 C
Adder
2.3517647058823531.999
3150761HOPPOLC
50/50
1.0021.002
3150651CHESTF6
50/50
21.89721.897
946262AF1-291 E
50/50
1.6321.632
933292AC2-141 E
Adder
3.78588235294117673.218
934576AD1-082 E
50/50
2.5582.558
944602AF1-125 E
Adder
33.8847058823529428.802
3145506HICKORY
Adder
0.72352941176470590.615
957871AF2-081 C
Adder
3.34117647058823542.84
943612AF1-032 E
Adder
0.320.272
940492AE2-034 E
Adder
1.09058823529411760.927
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
918492AA1-063AE OP
Adder
1.59411764705882361.355
962571AG1-106 C
Adder
1.14705882352941170.975
937482AD2-202 E
Adder
0.32588235294117650.277
917332KELFORD E
Adder
0.61411764705882350.522
925122AB2-169 E
Adder
2.04352941176470631.737
316274AC1-208 C
Adder
3.3788235294117652.872
917342Z2-044 E
Adder
0.215294117647058830.183
3151311EDGECMA
Adder
5.5117647058823534.685
925332AB2-190 E
50/50
4.6914.691
927226AC1-216 E
Adder
4.122352941176473.504
941591AE2-156 C
Adder
6.1141176470588245.197
944601AF1-125 C
Adder
14.80235294117647312.582
944591AF1-124 C
Adder
15.08705882352941312.824
936666AD2-085 E
Adder
2.5752941176470592.189
944011AF1-069 C
Adder
4.6141176470588243.922
938771AE1-103 C
Adder
1.11764705882352940.95
3145413WATKINS
Adder
0.26470588235294120.225
963041AG1-153 C
Adder
1.9482352941176471.656
960081AF2-299 C
Adder
0.81647058823529410.694
926072AC1-086 E
Adder
4.0352941176470593.43
957862AF2-080 E
Adder
1.19764705882352951.018
944582AF1-123 E
Adder
34.4258823529411829.262
944592AF1-124 E
Adder
34.55058823529411429.368
935112AD1-144 E
Adder
0.33176470588235290.282
316349AD2-085 C
Adder
1.57882352941176471.342
923832AB2-022 E
Adder
0.421176470588235260.358
938772AE1-103 E
Adder
1.5435294117647061.312
916042Z1-036 E
Adder
9.9682352941176488.473
963042AG1-153 E
Adder
2.92235294117647062.484
960082AF2-299 E
Adder
0.54470588235294130.463
946281AF1-292 C
Adder
0.67529411764705880.574
926071AC1-086 C
Adder
8.8647058823529427.535
964241AG1-285 C
Adder
3.85882352941176483.28
927021AC1-189 C
Adder
2.97529411764705862.529
924152AB2-059 E OP
Adder
1.87058823529411791.59
926755AC1-161 E
Adder
3.78588235294117673.218
933291AC2-141 C
Adder
8.8694117647058827.539
925522AC1-027 E
Adder
0.410588235294117640.349
3145256KINGFORK
Adder
0.357647058823529430.304
957872AF2-081 E
Adder
1.4317647058823531.217
941102AE2-104 E
Adder
2.0188235294117651.716
962572AG1-106 E
Adder
0.50117647058823530.426
964242AG1-285 E
Adder
2.5717647058823532.186
924162AB2-060 E OP
Adder
1.3117647058823531.115
932632AC2-084 E
Adder
1.20235294117647061.022
926214AC1-099 E
Adder
0.44941176470588240.382
940432AE2-027 E
Adder
4.6964705882352943.992
934012AD1-025 E
Adder
5.3364705882352944.536
939411AE1-173 C
Adder
31.5352941176470626.805
913392Y1-086 E
Adder
0.74470588235294120.633
3137643SOCKMAN
Adder
0.288235294117647030.245
919710AA2-057 E
Adder
1.44823529411764731.231
3150731STONECA
50/50
4.5124.512
935161AD1-151 C
50/50
9.0229.022
932046AC2-012 E
Adder
4.4823529411764713.81
938531AE1-072 C
Adder
5.8905882352941185.007
958161AF2-110 C
Adder
0.51764705882352950.44
3145393UNCAMP
Adder
2.3247058823529411.976
933981AD1-022 C
Adder
3.162.686
900672V4-068 E
Adder
0.136470588235294120.116
924302AB2-077 E O1
Adder
0.41176470588235290.35
961611AG1-000B C
Adder
7.342352941176476.241
940541AE2-040 C
Adder
1.56117647058823541.327
940481AE2-033 C
Adder
8.6517647058823537.354
940482AE2-033 E
Adder
5.8329411764705884.958
923263AB1-132 E OP
Adder
2.582.193
924312AB2-078 E O1
Adder
0.41176470588235290.35
316132AB2-190 C
50/50
2.4122.412
940642AE2-051 E
Adder
4.0635294117647063.454
942341AE2-247 C
Adder
0.68470588235294120.582
943462AF1-017 E
Adder
1.00941176470588250.858
919153AA1-139 E2
Adder
1.36588235294117651.161
958162AF2-110 E
Adder
0.82470588235294120.701
924516AB2-100 E1
Adder
1.36823529411764721.163
934512AD1-075 E
Adder
1.53411764705882361.304
934502AD1-074 E
Adder
6.1364705882352945.216
966621AG1-532 C
Adder
0.61294117647058830.521
918512AA1-065 E OP
Adder
2.04235294117647071.736
924022AB2-043 E O1
Adder
1.60117647058823541.361
918532AA1-067 E
Adder
0.251764705882352950.214
316084AB2-161 E
50/50
3.213.21
316083AB2-161 C
50/50
0.3210.321
940641AE2-051 C
Adder
6.0952941176470595.181
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
933982AD1-022 E
Adder
1.721.462
934622AD1-088 E
Adder
1.38117647058823521.174
934612AD1-087 E
Adder
1.1117647058823530.945
927146AC1-208 E
Adder
1.51.275
3150781HOPHCF2
50/50
1.5941.594
942001AE2-212 C
50/50
2.1112.111
939192AE1-149 E
50/50
4.7584.758
939312AE1-162 E
Adder
0.5717647058823530.486
934065AD1-033 E
Adder
1.6670588235294121.417
937226AE2-253 E
Adder
1.9482352941176471.656
924517AB2-100 E2
Adder
1.36823529411764721.163
934501AD1-074 C
Adder
12.05529411764705810.247
957482AF2-042 E
Adder
11.3435294117647069.642
934621AD1-088 C
Adder
2.86941176470588262.439
935172AD1-152 E
Adder
1.6435294117647061.397
961671AG1-007 C
Adder
0.332941176470588240.283
3150771HOPHCF1
50/50
1.5941.594
940431AE2-027 C
Adder
7.0447058823529425.988
942002AE2-212 E
50/50
1.4081.408
944581AF1-123 C
Adder
15.03411764705882412.779
941101AE2-104 C
Adder
1.26941176470588221.079
957481AF2-042 C
Adder
17.0152941176470614.463
316088AB2-174 E
Adder
2.7588235294117652.345
316141AB2-099 E
Adder
0.095294117647058830.081
923994AB2-040_E
Adder
2.56588235294117652.181
924322AB2-079 E O1
Adder
0.41176470588235290.35
961672AG1-007 E
Adder
0.188235294117647060.16
3143316POE
50/50
1.0861.086
939191AE1-149 C
50/50
7.1377.137
901082W1-029 E
Adder
10.9870588235294139.339
926206AC1-098 E
Adder
1.35999999999999991.156
935162AD1-151 E
50/50
6.0156.015
943461AF1-017 C
Adder
0.61882352941176480.526
932596AC2-079 E
Adder
4.1964705882352953.567
316311AC2-079 C
Adder
2.5717647058823532.186
938532AE1-072 E
Adder
3.07058823529411742.61
3146326AYDLETT TAP
Adder
0.455294117647058850.387
917122Z2-027 E
Adder
0.457647058823529460.389
920692AA2-178 E
Adder
1.4552941176470591.237
966622AG1-532 E
Adder
0.408235294117647030.347
922923AB1-081 E OP
Adder
1.321.122
944012AF1-069 E
Adder
1.7917647058823531.523
946282AF1-292 E
Adder
0.45058823529411770.383
957861AF2-080 C
Adder
2.7023529411764712.297
917512Z2-088 E OP1
Adder
1.73411764705882351.474
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
TVALTFEXP_TVA->PJM
CLTF
1.561.56
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
NYPJM->LTFIMP_NY
CLTF
0.4360.436
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
WECLTFEXP_WEC->PJM
CLTF
0.140.14

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.02 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:739.92
MW Contribution:7.18
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:116.6 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:791.36
MW Contribution:7.25
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
920042AA2-088 E OP
50/50
9.2489.248
934521AD1-076 C
Adder
7.246.154
934511AD1-075 C
Adder
4.9835294117647064.236
3151151S HAMPT1
50/50
0.9640.964
934522AD1-076 E
Adder
3.6905882352941183.137
943172AE2-346 E
50/50
0.5760.576
918492AA1-063AE OP
50/50
5.1285.128
962571AG1-106 C
50/50
5.4685.468
917332KELFORD E
50/50
1.6811.681
925122AB2-169 E
50/50
3.9953.995
932631AC2-084 C
50/50
1.1471.147
316274AC1-208 C
50/50
10.95810.958
917342Z2-044 E
50/50
0.6430.643
3151311EDGECMA
50/50
16.316.3
316087AB2-174 C
50/50
2.4072.407
962572AG1-106 E
50/50
2.3922.392
932632AC2-084 E
50/50
3.6863.686
926214AC1-099 E
50/50
1.3781.378
316140AB2-099 C
50/50
0.0910.091
3137643SOCKMAN
50/50
1.2021.202
316212AC1-099 C
50/50
0.3610.361
919710AA2-057 E
50/50
4.4424.442
316319Z2-044 C
50/50
0.2270.227
3145393UNCAMP
Adder
3.1317647058823532.662
933981AD1-022 C
50/50
5.8155.815
900672V4-068 E
50/50
0.330.33
3147043LAWRENC
50/50
0.5440.544
3151411GASTONB
50/50
6.1446.144
3151261ROARAP2
50/50
2.0552.055
924516AB2-100 E1
50/50
8.3588.358
934512AD1-075 E
Adder
2.53764705882352942.157
934502AD1-074 E
Adder
10.1482352941176478.626
966621AG1-532 C
50/50
3.2323.232
918512AA1-065 E OP
50/50
4.8064.806
918532AA1-067 E
50/50
0.5790.579
316181AB2-040 GEN
50/50
2.4492.449
923263AB1-132 E OP
50/50
12.30412.304
3156063AA2-053SOLA
50/50
2.0952.095
3151281ROARAP4
50/50
1.9441.944
316174AB2-169_C
50/50
0.7280.728
3156011CONETOE2SOL
50/50
1.1641.164
3145946PLYMOUTH TP
Adder
0.18470588235294120.157
933982AD1-022 E
50/50
3.1653.165
927146AC1-208 E
50/50
4.8664.866
316049AB1-081 C OP
50/50
1.4681.468
924517AB2-100 E2
50/50
8.3588.358
934501AD1-074 C
Adder
19.93647058823529516.946
3156021HOLLOMANSOL
50/50
1.5991.599
3156073AA1-063SOLA
50/50
1.7661.766
3151371ROSEMS1
50/50
2.4252.425
961671AG1-007 C
50/50
0.9020.902
316359AB2-059 C OP
50/50
1.731.73
3145723EMPORIA
50/50
0.9510.951
923573AB1-173 E OP
50/50
6.3246.324
316011AB1-132 C OP
50/50
4.6924.692
919692AA2-053 E OP
50/50
5.8745.874
925785AC1-054 E
50/50
3.2573.257
316263AC1-034 C
50/50
6.8576.857
3156083AA2-088SOLA
50/50
0.9260.926
316088AB2-174 E
50/50
13.32913.329
316141AB2-099 E
50/50
0.240.24
923994AB2-040_E
50/50
11.85811.858
313506AB1-173 C OP
50/50
2.1742.174
3151361ROSEMG1
50/50
3.9143.914
316005AA1-067 C
50/50
0.2210.221
961672AG1-007 E
50/50
0.5110.511
316365AB2-100 C1
50/50
2.7732.773
316318V4-068 C
50/50
0.0740.074
926206AC1-098 E
50/50
4.1714.171
316210AC1-098 C
50/50
1.0771.077
316327AA2-057 C
50/50
1.4581.458
961941AG1-037 C
50/50
0.480.48
961942AG1-037 E
50/50
0.320.32
943171AE2-346 C
50/50
0.2130.213
3151381ROSEMG2
50/50
1.8331.833
934332AD1-057 E
50/50
2.6472.647
934321AD1-056 C
50/50
9.1149.114
934322AD1-056 E
50/50
4.9434.943
934331AD1-057 C
50/50
5.0845.084
927022AC1-189 E
50/50
3.7313.731
925595AC1-034 E
50/50
5.1725.172
966622AG1-532 E
50/50
2.1552.155
922923AB1-081 E OP
50/50
3.8493.849
946282AF1-292 E
50/50
2.3782.378
316129AC1-054 C
50/50
1.1551.155
957861AF2-080 C
50/50
6.8036.803
917512Z2-088 E OP1
50/50
4.5534.553
3145413WATKINS
50/50
0.4340.434
960081AF2-299 C
50/50
4.3094.309
3151391GASTONA
50/50
6.1446.144
926072AC1-086 E
50/50
19.24219.242
957862AF2-080 E
50/50
3.0163.016
316023AB2-100 C2
50/50
2.7732.773
960082AF2-299 E
50/50
2.8732.873
946281AF1-292 C
50/50
3.5673.567
926071AC1-086 C
50/50
42.27842.278
316317KELFORD C
50/50
0.3660.366
927021AC1-189 C
50/50
7.497.49
924152AB2-059 E OP
50/50
5.4535.453
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.0232.023
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.27631.276
CPLELTFEXP_CPLE->PJM
CLTF
4.2444.244
TVALTFEXP_TVA->PJM
CLTF
1.8021.802
O66PJM->LTFIMP_O-066
CMTX_NF
4.3814.381
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6890.689
SIGELTFEXP_SIGE->PJM
CLTF
0.0730.073
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.6319.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7166.716
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1871.187
LAGNLTFEXP_LAGN->PJM
CLTF
2.312.31
NYPJM->LTFIMP_NY
CLTF
0.3160.316
LGEELTFEXP_LGEE->PJM
CLTF
0.3690.369
WECLTFEXP_WEC->PJM
CLTF
0.1970.197

Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:166.69 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:952.64
MW Contribution:1.85
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:173.55 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:991.87
MW Contribution:1.87
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
50/50
0.8430.843
961942AG1-037 E
50/50
0.5620.562
943171AE2-346 C
50/50
0.3740.374
3151381ROSEMG2
50/50
0.9310.931
934332AD1-057 E
50/50
1.7421.742
934321AD1-056 C
50/50
5.9965.996
934322AD1-056 E
50/50
3.2523.252
934331AD1-057 C
50/50
3.3453.345
927022AC1-189 E
50/50
5.7275.727
925595AC1-034 E
50/50
4.6964.696
920042AA2-088 E OP
50/50
6.4046.404
934521AD1-076 C
50/50
25.10225.102
934511AD1-075 C
50/50
17.27917.279
3145723EMPORIA
50/50
0.2710.271
923573AB1-173 E OP
50/50
2.3742.374
316011AB1-132 C OP
50/50
2.2832.283
919692AA2-053 E OP
50/50
4.4424.442
925785AC1-054 E
Adder
1.90117647058823551.616
316263AC1-034 C
50/50
6.2256.225
316087AB2-174 C
50/50
0.8050.805
962572AG1-106 E
50/50
1.1641.164
932632AC2-084 E
50/50
3.9433.943
926214AC1-099 E
50/50
1.4741.474
940492AE2-034 E
50/50
6.2586.258
934522AD1-076 E
50/50
12.79412.794
943172AE2-346 E
50/50
1.0111.011
918492AA1-063AE OP
50/50
3.2163.216
962571AG1-106 C
50/50
2.6612.661
917332KELFORD E
50/50
2.7032.703
925122AB2-169 E
50/50
10.49610.496
932631AC2-084 C
50/50
1.2271.227
316274AC1-208 C
50/50
9.5699.569
917342Z2-044 E
50/50
0.5880.588
3151311EDGECMA
50/50
14.76714.767
924516AB2-100 E1
50/50
1.791.79
934512AD1-075 E
50/50
8.7968.796
934502AD1-074 E
50/50
35.18435.184
966621AG1-532 C
50/50
0.8350.835
918512AA1-065 E OP
50/50
12.40212.402
918532AA1-067 E
50/50
1.1251.125
960081AF2-299 C
50/50
1.1131.113
3151391GASTONA
50/50
2.992.99
926072AC1-086 E
50/50
9.3659.365
957862AF2-080 E
50/50
4.6294.629
916042Z1-036 E
50/50
57.18957.189
316023AB2-100 C2
50/50
0.5940.594
960082AF2-299 E
50/50
0.7420.742
946281AF1-292 C
50/50
0.9210.921
926071AC1-086 C
50/50
20.57620.576
316317KELFORD C
50/50
0.5890.589
927021AC1-189 C
50/50
11.49811.498
924152AB2-059 E OP
50/50
4.954.95
3156116Z1-036WIND
50/50
1.3161.316
316140AB2-099 C
50/50
0.1610.161
3152921DOMTR78
50/50
2.6612.661
3137643SOCKMAN
50/50
0.5730.573
316212AC1-099 C
50/50
0.3860.386
919710AA2-057 E
50/50
4.074.07
316319Z2-044 C
50/50
0.2070.207
315614AA2-178 C
50/50
3.1813.181
933981AD1-022 C
50/50
18.40618.406
900672V4-068 E
50/50
0.3710.371
3151411GASTONB
50/50
2.992.99
3151261ROARAP2
50/50
1.211.21
316181AB2-040 GEN
50/50
0.9190.919
923263AB1-132 E OP
50/50
5.9885.988
3156063AA2-053SOLA
50/50
1.5851.585
3151281ROARAP4
50/50
1.1451.145
316174AB2-169_C
50/50
1.9111.911
3156011CONETOE2SOL
50/50
1.5831.583
3145946PLYMOUTH TP
50/50
0.6620.662
933982AD1-022 E
50/50
10.0210.02
927146AC1-208 E
50/50
4.2494.249
316049AB1-081 C OP
50/50
1.3321.332
940491AE2-034 C
50/50
2.3412.341
924517AB2-100 E2
50/50
1.791.79
934501AD1-074 C
50/50
69.11769.117
3156021HOLLOMANSOL
50/50
4.1274.127
3156073AA1-063SOLA
50/50
1.1081.108
3151371ROSEMS1
50/50
1.2321.232
961671AG1-007 C
50/50
1.1121.112
316359AB2-059 C OP
50/50
1.571.57
3156083AA2-088SOLA
50/50
0.6410.641
316088AB2-174 E
50/50
4.4594.459
316141AB2-099 E
50/50
0.4210.421
923994AB2-040_E
50/50
4.4524.452
313506AB1-173 C OP
50/50
0.8160.816
3151361ROSEMG1
50/50
1.9891.989
316005AA1-067 C
50/50
0.4290.429
961672AG1-007 E
50/50
0.630.63
316365AB2-100 C1
50/50
0.5940.594
316318V4-068 C
50/50
0.0840.084
926206AC1-098 E
50/50
4.4614.461
316210AC1-098 C
50/50
1.1521.152
316327AA2-057 C
50/50
1.3351.335
920692AA2-178 E
50/50
8.3448.344
966622AG1-532 E
50/50
0.5560.556
922923AB1-081 E OP
50/50
3.4943.494
946282AF1-292 E
50/50
0.6140.614
957861AF2-080 C
50/50
10.44310.443
917512Z2-088 E OP1
50/50
6.1936.193
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4372.437
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.337.3
CPLELTFEXP_CPLE->PJM
CLTF
5.1125.112
TVALTFEXP_TVA->PJM
CLTF
2.2172.217
O66PJM->LTFIMP_O-066
CMTX_NF
3.8433.843
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6050.605
SIGELTFEXP_SIGE->PJM
CLTF
0.0950.095
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.90912.909
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4168.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5351.535
LAGNLTFEXP_LAGN->PJM
CLTF
2.8432.843
NYPJM->LTFIMP_NY
CLTF
0.2690.269
LGEELTFEXP_LGEE->PJM
CLTF
0.4860.486
WECLTFEXP_WEC->PJM
CLTF
0.2620.262

Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.43 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:636.85
MW Contribution:1.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.25 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:670.11
MW Contribution:1.55
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
920042AA2-088 E OP
Adder
5.2376470588235294.452
934521AD1-076 C
50/50
12.94512.945
934511AD1-075 C
50/50
8.9118.911
3145723EMPORIA
Adder
0.22470588235294120.191
923573AB1-173 E OP
50/50
1.9641.964
316011AB1-132 C OP
50/50
1.8881.888
919692AA2-053 E OP
50/50
3.6823.682
925785AC1-054 E
Adder
1.57058823529411761.335
316263AC1-034 C
50/50
4.9994.999
940492AE2-034 E
50/50
2.3072.307
934522AD1-076 E
50/50
6.5986.598
943172AE2-346 E
50/50
0.8430.843
918492AA1-063AE OP
50/50
2.6512.651
962571AG1-106 C
50/50
2.22.2
917332KELFORD E
50/50
2.2482.248
925122AB2-169 E
50/50
6.5316.531
932631AC2-084 C
50/50
1.0111.011
316274AC1-208 C
50/50
7.8537.853
917342Z2-044 E
50/50
0.4760.476
3151311EDGECMA
50/50
11.80811.808
960081AF2-299 C
Adder
0.92117647058823540.783
3151391GASTONA
50/50
2.4722.472
926072AC1-086 E
50/50
7.7427.742
962572AG1-106 E
50/50
0.9630.963
932632AC2-084 E
50/50
3.2493.249
926214AC1-099 E
50/50
1.2141.214
316140AB2-099 C
50/50
0.1340.134
3152921DOMTR78
50/50
1.4921.492
3137643SOCKMAN
50/50
0.4740.474
316212AC1-099 C
50/50
0.3180.318
919710AA2-057 E
50/50
3.3143.314
316319Z2-044 C
50/50
0.1680.168
315614AA2-178 C
50/50
1.1731.173
933981AD1-022 C
50/50
11.12811.128
900672V4-068 E
50/50
0.3070.307
3151411GASTONB
50/50
2.4722.472
3151261ROARAP2
50/50
11
924516AB2-100 E1
Adder
1.48352941176470581.261
934512AD1-075 E
50/50
4.5364.536
934502AD1-074 E
50/50
18.14418.144
966621AG1-532 C
Adder
0.6917647058823530.588
918512AA1-065 E OP
50/50
10.3710.37
918532AA1-067 E
50/50
0.8740.874
316181AB2-040 GEN
50/50
0.7610.761
923263AB1-132 E OP
50/50
4.954.95
3156063AA2-053SOLA
50/50
1.3141.314
3151281ROARAP4
50/50
0.9460.946
316174AB2-169_C
50/50
1.1891.189
3156011CONETOE2SOL
50/50
1.2431.243
3145946PLYMOUTH TP
50/50
0.3260.326
933982AD1-022 E
50/50
6.0586.058
927146AC1-208 E
50/50
3.4873.487
316049AB1-081 C OP
50/50
1.071.07
940491AE2-034 C
50/50
0.8630.863
924517AB2-100 E2
Adder
1.48352941176470581.261
934501AD1-074 C
50/50
35.64335.643
3156021HOLLOMANSOL
50/50
3.4513.451
3156073AA1-063SOLA
50/50
0.9130.913
3151371ROSEMS1
50/50
1.0151.015
961671AG1-007 C
50/50
0.8770.877
316359AB2-059 C OP
50/50
1.2611.261
316088AB2-174 E
Adder
3.68941176470588243.136
316141AB2-099 E
50/50
0.3510.351
923994AB2-040_E
50/50
3.6833.683
313506AB1-173 C OP
50/50
0.6750.675
3151361ROSEMG1
50/50
1.6391.639
316005AA1-067 C
50/50
0.3330.333
961672AG1-007 E
50/50
0.4970.497
316318V4-068 C
50/50
0.0690.069
926206AC1-098 E
50/50
3.6753.675
316210AC1-098 C
50/50
0.9490.949
316327AA2-057 C
50/50
1.0871.087
961941AG1-037 C
50/50
0.7020.702
961942AG1-037 E
50/50
0.4680.468
943171AE2-346 C
50/50
0.3120.312
3151381ROSEMG2
50/50
0.7680.768
934332AD1-057 E
50/50
1.4131.413
934321AD1-056 C
50/50
4.8664.866
934322AD1-056 E
50/50
2.6392.639
934331AD1-057 C
50/50
2.7142.714
927022AC1-189 E
50/50
4.4794.479
925595AC1-034 E
50/50
3.7713.771
920692AA2-178 E
50/50
3.0763.076
966622AG1-532 E
Adder
0.46117647058823530.392
922923AB1-081 E OP
50/50
2.8072.807
946282AF1-292 E
Adder
0.50823529411764710.432
957861AF2-080 C
50/50
8.1668.166
917512Z2-088 E OP1
50/50
4.8634.863
957862AF2-080 E
50/50
3.623.62
916042Z1-036 E
Adder
9.7517647058823538.289
960082AF2-299 E
Adder
0.61411764705882350.522
946281AF1-292 C
Adder
0.76235294117647070.648
926071AC1-086 C
50/50
17.00917.009
316317KELFORD C
50/50
0.4890.489
927021AC1-189 C
50/50
8.9918.991
924152AB2-059 E OP
50/50
3.9763.976
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9321.932
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.62929.629
CPLELTFEXP_CPLE->PJM
CLTF
4.0524.052
TVALTFEXP_TVA->PJM
CLTF
1.7681.768
O66PJM->LTFIMP_O-066
CMTX_NF
3.0083.008
G-007PJM->LTFIMP_G-007
CMTX_NF
0.4730.473
SIGELTFEXP_SIGE->PJM
CLTF
0.0760.076
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.35910.359
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7216.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.2291.229
LAGNLTFEXP_LAGN->PJM
CLTF
2.2672.267
NYPJM->LTFIMP_NY
CLTF
0.210.21
LGEELTFEXP_LGEE->PJM
CLTF
0.3890.389
WECLTFEXP_WEC->PJM
CLTF
0.210.21

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.08 %
Rating:879.84 MVA
Rating Type:B
MVA to Mitigate:950.94
MW Contribution:1.41
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:132.71 %
Rating:879.84 MVA
Rating Type:B
MVA to Mitigate:1167.6
MW Contribution:1.6
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
939246AE1-155 E
Adder
5.6705882352941184.82
957972AF2-091 E
Adder
1.5517647058823531.319
944641AF1-129 C
Adder
75.7352941176470664.375
316240AF1-291 C
Adder
1.56941176470588251.334
924814AB2-134 E
Adder
8.3647058823529427.11
942342AE2-247 E
Adder
1.16941176470588240.994
919152AA1-139 E1
Adder
2.1752941176470591.849
920042AA2-088 E OP
Adder
5.164.386
934521AD1-076 C
Adder
5.9847058823529415.087
934511AD1-075 C
Adder
4.1188235294117653.501
3145723EMPORIA
Adder
0.195294117647058840.166
923573AB1-173 E OP
Adder
1.4764705882352941.255
3150441FOUR RIVERB
50/50
2.7882.788
3130536PAPERMILL
Adder
4.5270588235294123.848
939602AE1-190 E
Adder
0.95411764705882360.811
936591AD2-074 C
Adder
3.63882352941176463.093
3150651CHESTF6
Adder
13.78941176470588211.721
946262AF1-291 E
Adder
1.04588235294117650.889
933292AC2-141 E
Adder
6.8564705882352955.828
934576AD1-082 E
Adder
2.6682352941176472.268
944602AF1-125 E
Adder
54.7376470588235346.527
3145506HICKORY
Adder
1.16588235294117660.991
957871AF2-081 C
Adder
5.3211764705882354.523
943612AF1-032 E
Adder
0.49647058823529410.422
940492AE2-034 E
Adder
1.53882352941176471.308
934522AD1-076 E
Adder
3.0505882352941182.593
943172AE2-346 E
Adder
0.28588235294117650.243
918492AA1-063AE OP
Adder
1.88000000000000011.598
962571AG1-106 C
Adder
1.241.054
966871AG1-558 C
50/50
2.4052.405
966872AG1-558 E
50/50
1.2121.212
3150841SPRUNCB
Adder
6.84941176470588255.822
3150831SPRUNCA
Adder
6.84941176470588255.822
316076AC2-137 E
Adder
1.04588235294117650.889
923842AB2-024 E
Adder
1.2282352941176471.044
964211AG1-282 C
Adder
1.32117647058823541.123
316157AD2-030 E
Adder
0.78705882352941180.669
926662AC1-147 E
Adder
0.72117647058823530.613
916192Z1-068 E
Adder
1.0152941176470590.863
939412AE1-173 E
Adder
27.4976470588235323.373
957492AF2-043 E
Adder
0.76352941176470590.649
941032AE2-094 E
Adder
7.0964705882352946.032
941031AE2-094 C
Adder
15.84470588235294213.468
923852AB2-025 E
Adder
0.58235294117647060.495
961941AG1-037 C
Adder
0.238823529411764740.203
961942AG1-037 E
Adder
0.158823529411764720.135
966881AG1-559 C
Adder
1.37764705882352941.171
3150601CHESTF5
Adder
47.7840.613
964212AG1-282 E
Adder
0.88117647058823530.749
962962AG1-145 E
Adder
0.94000000000000010.799
925332AB2-190 E
Adder
5.5094117647058834.683
927226AC1-216 E
Adder
5.1070588235294124.341
941591AE2-156 C
Adder
9.744705882352948.283
944601AF1-125 C
Adder
23.9117647058823520.325
944591AF1-124 C
Adder
24.37176470588235620.716
936666AD2-085 E
Adder
3.18705882352941172.709
944011AF1-069 C
Adder
2.9870588235294122.539
938771AE1-103 C
Adder
1.5164705882352941.289
3145413WATKINS
Adder
0.348235294117647030.296
960081AF2-299 C
Adder
0.84823529411764710.721
926072AC1-086 E
Adder
4.36235294117647053.708
939261AE1-157 C
Adder
6.5811764705882365.594
966882AG1-559 E
Adder
0.69411764705882350.59
930122AB1-027 E
50/50
1.2571.257
316169AC1-164 GEN
Adder
29.68117647058823425.229
957971AF2-091 C
Adder
1.12352941176470590.955
944582AF1-123 E
Adder
55.6105882352941247.269
944592AF1-124 E
Adder
55.81176470588235447.44
935112AD1-144 E
Adder
0.52352941176470590.445
316349AD2-085 C
Adder
1.95294117647058821.66
923832AB2-022 E
Adder
0.65529411764705890.557
938772AE1-103 E
Adder
2.09411764705882361.78
916042Z1-036 E
Adder
14.65058823529411712.453
960082AF2-299 E
Adder
0.56588235294117650.481
946281AF1-292 C
Adder
0.70235294117647060.597
926071AC1-086 C
Adder
9.5835294117647068.146
316312AB1-027 C
50/50
0.4790.479
938552AE1-074 E
Adder
0.81882352941176460.696
934782AD1-105 E
50/50
4.3454.345
944631AF1-128 C
Adder
29.89647058823529225.412
936592AD2-074 E
Adder
5.9376470588235295.047
316160AE1-175 E
Adder
0.77529411764705890.659
3150921YORKTN3
Adder
72.7576470588235461.844
926755AC1-161 E
Adder
6.8564705882352955.828
933291AC2-141 C
Adder
16.0623529411764713.653
925522AC1-027 E
Adder
0.65764705882352950.559
3145256KINGFORK
Adder
0.56470588235294120.48
957872AF2-081 E
Adder
2.281.938
941102AE2-104 E
Adder
2.89058823529411772.457
962572AG1-106 E
Adder
0.54235294117647060.461
3150451FOUR RIVERC
50/50
3.4073.407
3150671DARBY 1
50/50
2.2042.204
316078AC2-138 E
Adder
0.60352941176470590.513
958262AF2-120 E
Adder
2.7152941176470592.308
966661AG1-536 C
Adder
3.50352941176470622.978
939612AE1-191 E
Adder
3.8152941176470593.243
957602AF2-054 E
Adder
0.93529411764705890.795
944491AF1-114 C
Adder
3.30470588235294162.809
940432AE2-027 E
Adder
6.1164705882352945.199
934012AD1-025 E
Adder
6.6117647058823535.62
939411AE1-173 C
Adder
41.24705882352941435.06
913392Y1-086 E
Adder
1.160.986
3150701DARBY 4
50/50
2.2172.217
3150731STONECA
Adder
4.9341176470588244.194
935161AD1-151 C
Adder
10.8541176470588259.226
932046AC2-012 E
Adder
7.1352941176470596.065
938531AE1-072 C
Adder
9.3411764705882367.94
958161AF2-110 C
Adder
0.74235294117647070.631
3145393UNCAMP
Adder
3.11647058823529432.649
933981AD1-022 C
Adder
4.2529411764705883.615
900672V4-068 E
Adder
0.170588235294117650.145
927041AC1-191 C
50/50
9.6569.656
3142366NRTHEST
50/50
0.1640.164
3138116ELKO L286
Adder
1.09058823529411760.927
963611AG1-210 C
Adder
0.431764705882352940.367
961611AG1-000B C
Adder
10.0094117647058818.508
940541AE2-040 C
Adder
1.44117647058823551.225
940481AE2-033 C
Adder
8.0647058823529436.855
940482AE2-033 E
Adder
5.4364705882352954.621
923263AB1-132 E OP
Adder
2.78941176470588252.371
926412AC1-112 E
50/50
1.0221.022
934781AD1-105 C
50/50
1.0481.048
3150681DARBY 2
50/50
2.2072.207
963612AG1-210 E
Adder
0.64705882352941180.55
940642AE2-051 E
Adder
4.9588235294117654.215
942341AE2-247 C
Adder
0.84705882352941180.72
943462AF1-017 E
Adder
1.24941176470588241.062
919153AA1-139 E2
Adder
2.1752941176470591.849
958162AF2-110 E
Adder
1.181.003
924516AB2-100 E1
Adder
1.3717647058823531.166
934512AD1-075 E
Adder
2.09647058823529431.782
934502AD1-074 E
Adder
8.3882352941176477.13
966621AG1-532 C
Adder
0.63647058823529420.541
918512AA1-065 E OP
Adder
2.62941176470588232.235
926785AC1-164_E
Adder
13.3352941176470611.335
943471AF1-018 C
Adder
4.8305882352941174.106
926472AC1-118 E
Adder
0.64470588235294120.548
316084AB2-161 E
Adder
3.34823529411764742.846
940641AE2-051 C
Adder
7.4376470588235296.322
3145946PLYMOUTH TP
Adder
0.158823529411764720.135
933982AD1-022 E
Adder
2.3152941176470591.968
3150471FOUR RIVERE
50/50
2.7482.748
315052AA1-145 CT2
50/50
4.444.44
3142296MT RD221
50/50
0.1260.126
316004AC1-112 C
50/50
0.2990.299
3150501FOURRIVERG
50/50
4.254.25
3141813NORNECK
Adder
0.57411764705882350.488
962861AG1-135 C
Adder
3.9564705882352943.363
943741AF1-042 C
Adder
1.90352941176470611.618
942001AE2-212 C
Adder
1.48117647058823531.259
939192AE1-149 E
Adder
4.5223529411764713.844
939312AE1-162 E
Adder
0.84352941176470590.717
934065AD1-033 E
Adder
2.68823529411764732.285
937226AE2-253 E
Adder
3.1152941176470592.648
924517AB2-100 E2
Adder
1.3717647058823531.166
934501AD1-074 C
Adder
16.4776470588235314.006
3150461FOUR RIVERD
50/50
2.7482.748
934392AD1-063 E
Adder
0.72470588235294120.616
966662AG1-536 E
Adder
4.7070588235294134.001
962862AG1-135 E
Adder
2.63764705882352952.242
943742AF1-042 E
Adder
3.10705882352941172.641
944492AF1-114 E
Adder
4.5635294117647063.879
940431AE2-027 C
Adder
9.175294117647067.799
942002AE2-212 E
Adder
0.98705882352941180.839
944581AF1-123 C
Adder
24.2847058823529420.642
941101AE2-104 C
Adder
1.81764705882352941.545
316088AB2-174 E
Adder
2.94235294117647062.501
316141AB2-099 E
Adder
0.118823529411764720.101
923994AB2-040_E
Adder
2.76941176470588252.354
958261AF2-120 C
Adder
4.07294117647058853.462
934146AD1-041 E
Adder
2.38470588235294122.027
957601AF2-054 C
Adder
1.40235294117647061.192
3143316POE
Adder
0.84470588235294120.718
939191AE1-149 C
Adder
6.78235294117647055.765
901082W1-029 E
Adder
16.73529411764705814.225
315051AA1-145 CT1
50/50
4.4424.442
3150481FOUR RIVERF
50/50
3.3563.356
927042AC1-191 E
50/50
4.814.81
316233AE1-074 C
Adder
1.62470588235294121.381
3150691DARBY 3
50/50
2.2142.214
940551AE2-041 C
Adder
4.8305882352941174.106
957832AF2-077 E
Adder
0.90470588235294120.769
935162AD1-151 E
Adder
7.235294117647066.15
943461AF1-017 C
Adder
0.76588235294117660.651
932596AC2-079 E
Adder
5.284.488
316311AC2-079 C
Adder
3.2352941176470592.75
938532AE1-072 E
Adder
4.8694117647058834.139
3146326AYDLETT TAP
Adder
0.720.612
917122Z2-027 E
Adder
0.70705882352941170.601
920692AA2-178 E
Adder
2.05294117647058851.745
966622AG1-532 E
Adder
0.424705882352941160.361
939262AE1-157 E
Adder
3.56941176470588233.034
3150431FOUR RIVERA
50/50
2.7882.788
925865AC1-065 E
Adder
11.2529411764705879.565
936582AD2-073 E
Adder
0.67176470588235290.571
961952AG1-038 E
Adder
2.9058823529411772.47
961951AG1-038 C
Adder
2.1047058823529411.789
946282AF1-292 E
Adder
0.46823529411764710.398
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7881.788
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.04428.044
CPLELTFEXP_CPLE->PJM
CLTF
3.7593.759
TVALTFEXP_TVA->PJM
CLTF
1.0611.061
O66PJM->LTFIMP_O-066
CMTX_NF
6.8436.843
G-007PJM->LTFIMP_G-007
CMTX_NF
1.0691.069
SIGELTFEXP_SIGE->PJM
CLTF
0.0060.006
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.9732.973
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0350.035
MECLTFEXP_MEC->PJM
CLTF
0.2010.201
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0870.087
LAGNLTFEXP_LAGN->PJM
CLTF
1.4041.404
NYPJM->LTFIMP_NY
CLTF
0.5450.545

Details for 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o RKYMT-WILS230_&_RKYMT-SHARPB115_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
Contingency Name:
RKYMT-WILS230_&_RKYMT-SHARPB115_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.07 %
Rating:478.0 MVA
Rating Type:B
MVA to Mitigate:507.02
MW Contribution:1.31
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
Contingency Name:
RKYMT-WILS230_&_RKYMT-SHARPB115_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.18 %
Rating:478.0 MVA
Rating Type:B
MVA to Mitigate:478.87
MW Contribution:1.35
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3145946PLYMOUTH TP
50/50
0.2960.296
933982AD1-022 E
50/50
4.5544.554
927146AC1-208 E
50/50
2.8172.817
316049AB1-081 C OP
50/50
1.1391.139
957872AF2-081 E
Adder
1.24470588235294131.058
941102AE2-104 E
Adder
1.69176470588235281.438
962572AG1-106 E
50/50
0.7430.743
932632AC2-084 E
50/50
2.432.43
926214AC1-099 E
50/50
0.9080.908
919152AA1-139 E1
Adder
1.18705882352941171.009
920042AA2-088 E OP
Adder
5.7423529411764714.881
934521AD1-076 C
50/50
11.47511.475
934511AD1-075 C
50/50
7.8997.899
3145723EMPORIA
Adder
0.188235294117647060.16
923573AB1-173 E OP
Adder
1.57882352941176471.342
316011AB1-132 C OP
50/50
1.4581.458
919692AA2-053 E OP
50/50
2.5922.592
925785AC1-054 E
Adder
1.1082352941176470.942
316263AC1-034 C
50/50
5.3235.323
957871AF2-081 C
Adder
2.9035294117647062.468
943612AF1-032 E
Adder
0.28588235294117650.243
940492AE2-034 E
50/50
2.4562.456
934522AD1-076 E
50/50
5.8495.849
943172AE2-346 E
50/50
0.5080.508
918492AA1-063AE OP
Adder
2.2552941176470591.917
962571AG1-106 C
50/50
1.6991.699
917332KELFORD E
50/50
1.3911.391
925122AB2-169 E
50/50
8.5338.533
932631AC2-084 C
50/50
0.7560.756
316274AC1-208 C
50/50
6.3436.343
917342Z2-044 E
50/50
0.4590.459
3151311EDGECMA
50/50
13.61713.617
901082W1-029 E
Adder
14.01882352941176511.916
316318V4-068 C
50/50
0.0530.053
926206AC1-098 E
50/50
2.752.75
316210AC1-098 C
50/50
0.710.71
316327AA2-057 C
50/50
0.9750.975
913392Y1-086 E
Adder
0.81411764705882350.692
3156116Z1-036WIND
50/50
0.4010.401
316140AB2-099 C
50/50
0.0810.081
3152921DOMTR78
50/50
1.6181.618
3137643SOCKMAN
Adder
0.370588235294117660.315
316212AC1-099 C
50/50
0.2380.238
919710AA2-057 E
50/50
2.9712.971
316319Z2-044 C
50/50
0.1620.162
940491AE2-034 C
50/50
0.9190.919
924517AB2-100 E2
Adder
1.31294117647058851.116
934501AD1-074 C
50/50
31.59531.595
3156021HOLLOMANSOL
50/50
1.8471.847
3151371ROSEMS1
50/50
0.8170.817
961671AG1-007 C
50/50
1.251.25
316359AB2-059 C OP
50/50
1.3431.343
919153AA1-139 E2
Adder
1.18705882352941171.009
958162AF2-110 E
Adder
0.69058823529411760.587
924516AB2-100 E1
Adder
1.31294117647058851.116
934512AD1-075 E
50/50
4.0214.021
934502AD1-074 E
50/50
16.08316.083
966621AG1-532 C
Adder
0.58941176470588240.501
918512AA1-065 E OP
50/50
5.5525.552
918532AA1-067 E
50/50
1.4951.495
941101AE2-104 C
Adder
1.06352941176470580.904
316088AB2-174 E
Adder
3.0152941176470592.563
316141AB2-099 E
50/50
0.2120.212
923994AB2-040_E
Adder
2.9611764705882352.517
3151361ROSEMG1
50/50
1.321.32
316005AA1-067 C
50/50
0.570.57
961672AG1-007 E
50/50
0.7090.709
946282AF1-292 E
Adder
0.434117647058823550.369
957861AF2-080 C
50/50
12.88512.885
917512Z2-088 E OP1
50/50
7.2857.285
938771AE1-103 C
Adder
1.22235294117647041.039
3145413WATKINS
Adder
0.32588235294117650.277
960081AF2-299 C
Adder
0.78588235294117660.668
3151391GASTONA
50/50
1.9091.909
926072AC1-086 E
50/50
5.9785.978
957862AF2-080 E
50/50
5.7125.712
923832AB2-022 E
Adder
0.460.391
938772AE1-103 E
Adder
1.68705882352941171.434
916042Z1-036 E
50/50
17.44917.449
960082AF2-299 E
Adder
0.52352941176470590.445
946281AF1-292 C
Adder
0.65058823529411770.553
926071AC1-086 C
50/50
13.13513.135
316317KELFORD C
50/50
0.3030.303
927021AC1-189 C
50/50
14.18714.187
924152AB2-059 E OP
50/50
4.2334.233
957492AF2-043 E
Adder
0.440.374
961941AG1-037 C
50/50
0.4240.424
961942AG1-037 E
50/50
0.2820.282
943171AE2-346 C
50/50
0.1880.188
3151381ROSEMG2
50/50
0.6180.618
934332AD1-057 E
50/50
1.3841.384
934321AD1-056 C
50/50
4.7644.764
934322AD1-056 E
50/50
2.5842.584
934331AD1-057 C
50/50
2.6572.657
927022AC1-189 E
50/50
7.0677.067
925595AC1-034 E
50/50
4.0154.015
932596AC2-079 E
Adder
2.69411764705882372.29
316311AC2-079 C
Adder
1.65058823529411771.403
938532AE1-072 E
Adder
2.82.38
3146326AYDLETT TAP
Adder
0.42235294117647060.359
917122Z2-027 E
Adder
0.53882352941176470.458
920692AA2-178 E
50/50
3.2743.274
966622AG1-532 E
Adder
0.39294117647058830.334
922923AB1-081 E OP
50/50
2.9882.988
938531AE1-072 C
Adder
5.3705882352941184.565
958161AF2-110 C
Adder
0.434117647058823550.369
3145393UNCAMP
Adder
2.66588235294117662.266
315614AA2-178 C
50/50
1.2481.248
933981AD1-022 C
50/50
8.3658.365
900672V4-068 E
50/50
0.2360.236
3151411GASTONB
50/50
1.9091.909
940481AE2-033 C
Adder
4.7576470588235294.044
940482AE2-033 E
Adder
3.2082352941176472.727
923263AB1-132 E OP
50/50
3.8233.823
3156063AA2-053SOLA
50/50
0.9250.925
316174AB2-169_C
50/50
1.5541.554
3156011CONETOE2SOL
50/50
1.8621.862
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
5.8875.887
G-007ALTFEXP_G-007A->PJM
CMTX
0.8590.859
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
1.3941.394
VTFLTFEXP_VFT->PJM
CMTX
2.2892.289
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.4161.416
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.0014.001
MDUPJM->LTFIMP_MDU
CLTF
0.1430.143
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.3390.339
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6630.663
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0942.094
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
4.6924.692
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.2223.222

Details for 6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.24 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:618.61
MW Contribution:0.97
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.66 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:649.58
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
937482AD2-202 E
50/50
1.621.62
3151581KERR 1
50/50
0.3970.397
3151601KERR 3
50/50
1.1131.113
3152661PLYWOOD A
50/50
1.3061.306
941011AE2-092 C
Adder
-7.384705882352941-6.277
964242AG1-285 E
50/50
10.84610.846
924162AB2-060 E OP
50/50
3.9993.999
313527AB2-043 C
50/50
0.5090.509
3151591KERR 2
50/50
1.1131.113
964792AG1-342 E
50/50
2.4822.482
316283AC2-100 C
50/50
1.0191.019
932763AC2-100 E
50/50
2.2422.242
3137643SOCKMAN
Adder
0.236470588235294130.201
937481AD2-202 C
50/50
0.5570.557
3151641KERR 7
50/50
1.1131.113
316205AC1-080 C
50/50
0.2470.247
316123AC1-075 C
50/50
0.740.74
924302AB2-077 E O1
50/50
1.321.32
3151621KERR 5
50/50
1.1131.113
316222AC1-221 C
50/50
1.3041.304
942752AE2-291 E
50/50
4.2094.209
925612AC1-036 E
50/50
0.6080.608
316238AB2-078 C O1
50/50
0.3240.324
924312AB2-078 E O1
50/50
1.321.32
316237AB2-079 C O1
50/50
0.3240.324
926274AC1-105 E
50/50
2.892.89
938821AE1-108 C
Adder
-8.042352941176471-6.836
316336AC2-165 C
Adder
-4.488235294117647-3.815
934622AD1-088 E
50/50
8.0788.078
934611AD1-087 C
50/50
1.9191.919
934612AD1-087 E
50/50
5.5365.536
3151611KERR 4
50/50
1.1131.113
927255AC1-221 E
50/50
3.413.41
957482AF2-042 E
50/50
57.29557.295
934621AD1-088 C
50/50
16.77816.778
942461AE2-259 C
Adder
-11.085882352941177-9.423
935172AD1-152 E
50/50
7.5637.563
3145723EMPORIA
Adder
0.136470588235294120.116
923573AB1-173 E OP
Adder
1.06470588235294120.905
919692AA2-053 E OP
Adder
1.31411764705882361.117
959311AF2-222 C
Adder
9.9482352941176468.456
925785AC1-054 E
50/50
2.3712.371
942751AE2-291 C
50/50
6.3136.313
957481AF2-042 C
50/50
85.94285.942
316088AB2-174 E
Adder
2.0917647058823531.778
923994AB2-040_E
Adder
1.99764705882352931.698
924322AB2-079 E O1
50/50
1.321.32
943902AF1-058 E
50/50
1.4231.423
316239AB2-077 C O1
50/50
0.3240.324
935171AD1-152 C
50/50
1.8391.839
964791AG1-342 C
50/50
3.7243.724
925997AC1-075 E
50/50
2.5662.566
936262AD2-033 E
Adder
3.5152941176470592.988
966621AG1-532 C
Adder
0.437647058823529440.372
3147223TWITTYS
50/50
0.6740.674
959312AF2-222 E
Adder
6.66588235294117755.666
924022AB2-043 E O1
50/50
5.1075.107
316003AC1-222 C
50/50
1.0461.046
926024AC1-080 E
50/50
0.8510.851
946282AF1-292 E
Adder
0.32235294117647060.274
3151541CLOVER2
50/50
19.33819.338
316131AB2-060 C
50/50
1.3891.389
316129AC1-054 C
50/50
0.8410.841
316118AC1-105 C
50/50
0.9880.988
960081AF2-299 C
Adder
0.58352941176470590.496
936261AD2-033 C
Adder
5.2729411764705894.482
3151631KERR 6
50/50
1.1131.113
962562AG1-105 E
50/50
6.1616.161
316248AF1-058 C
50/50
0.3490.349
960082AF2-299 E
Adder
0.38941176470588240.331
946281AF1-292 C
Adder
0.48352941176470590.411
3151531CLOVER1
50/50
19.51919.519
964241AG1-285 C
50/50
16.2716.27
316034AC1-036 C
50/50
0.1660.166
962561AG1-105 C
50/50
9.2429.242
966622AG1-532 E
Adder
0.29176470588235290.248
927264AC1-222 E
50/50
4.2714.271
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6471.647
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.50427.504
CPLELTFEXP_CPLE->PJM
CLTF
3.4573.457
TVALTFEXP_TVA->PJM
CLTF
1.5461.546
O66PJM->LTFIMP_O-066
CMTX_NF
3.8923.892
G-007PJM->LTFIMP_G-007
CMTX_NF
0.610.61
SIGELTFEXP_SIGE->PJM
CLTF
0.0570.057
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.2877.287
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.6115.611
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.9490.949
LAGNLTFEXP_LAGN->PJM
CLTF
1.9781.978
NYPJM->LTFIMP_NY
CLTF
0.2910.291
LGEELTFEXP_LGEE->PJM
CLTF
0.2860.286
WECLTFEXP_WEC->PJM
CLTF
0.1510.151

Details for 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.46 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:797.16
MW Contribution:1.15
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.99 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:766.86
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3130536PAPERMILL
Adder
3.7670588235294123.202
939602AE1-190 E
Adder
0.79058823529411770.672
936591AD2-074 C
Adder
2.8741176470588242.443
3150651CHESTF6
Adder
11.472941176470599.752
946262AF1-291 E
Adder
0.86941176470588230.739
933292AC2-141 E
Adder
5.5482352941176484.716
934576AD1-082 E
Adder
2.16941176470588241.844
944602AF1-125 E
Adder
44.11647058823529537.499
3145506HICKORY
Adder
0.93882352941176480.798
957871AF2-081 C
Adder
4.2894117647058823.646
943612AF1-032 E
Adder
0.40.34
940492AE2-034 E
Adder
1.24588235294117641.059
934522AD1-076 E
Adder
2.47058823529411782.1
943172AE2-346 E
Adder
0.231764705882352960.197
944631AF1-128 C
Adder
21.0152941176470617.863
936592AD2-074 E
Adder
4.6894117647058823.986
316160AE1-175 E
Adder
0.64705882352941180.55
3150671DARBY 1
50/50
5.1375.137
3150851SPRUNCC
50/50
0.1930.193
316078AC2-138 E
Adder
0.46470588235294120.395
958262AF2-120 E
Adder
2.1164705882352941.799
966661AG1-536 C
Adder
2.7305882352941182.321
939612AE1-191 E
Adder
3.16117647058823532.687
957602AF2-054 E
Adder
0.76823529411764710.653
940432AE2-027 E
Adder
5.3800000000000014.573
934012AD1-025 E
Adder
5.1988235294117644.419
939411AE1-173 C
Adder
32.84941176470588427.922
913392Y1-086 E
Adder
0.93647058823529420.796
3150701DARBY 4
50/50
5.1675.167
3150731STONECA
Adder
3.82941176470588253.255
935161AD1-151 C
Adder
8.5094117647058837.233
932046AC2-012 E
Adder
5.74352941176470564.882
938531AE1-072 C
Adder
7.5329411764705886.403
958161AF2-110 C
Adder
0.59882352941176480.509
3145393UNCAMP
Adder
2.522.142
933981AD1-022 C
Adder
3.44588235294117642.929
900672V4-068 E
Adder
0.13882352941176470.118
3142366NRTHEST
50/50
0.4150.415
3138116ELKO L286
50/50
1.6051.605
963611AG1-210 C
Adder
0.33176470588235290.282
961611AG1-000B C
Adder
7.94235294117647156.751
940541AE2-040 C
Adder
1.1717647058823530.996
940481AE2-033 C
Adder
6.5541176470588235.571
940482AE2-033 E
Adder
4.4188235294117653.756
926785AC1-164_E
50/50
11.42911.429
943471AF1-018 C
Adder
4.0035294117647063.403
926472AC1-118 E
Adder
0.448235294117647070.381
316084AB2-161 E
Adder
2.7223529411764712.314
940641AE2-051 C
Adder
5.8941176470588235.01
3145946PLYMOUTH TP
Adder
0.128235294117647060.109
933982AD1-022 E
Adder
1.87647058823529411.595
3141813NORNECK
Adder
0.44235294117647060.376
3150921YORKTN3
Adder
59.65411764705882550.706
926755AC1-161 E
Adder
5.5482352941176484.716
933291AC2-141 C
Adder
12.9976470588235311.048
925522AC1-027 E
Adder
0.52941176470588240.45
3145256KINGFORK
Adder
0.455294117647058850.387
957872AF2-081 E
Adder
1.83882352941176471.563
941102AE2-104 E
Adder
2.33411764705882341.984
939246AE1-155 E
Adder
4.423.757
944641AF1-129 C
Adder
63.01529411764706653.563
316240AF1-291 C
Adder
1.30470588235294121.109
924814AB2-134 E
Adder
6.5788235294117645.592
942342AE2-247 E
Adder
0.94705882352941180.805
919152AA1-139 E1
Adder
1.75411764705882381.491
920042AA2-088 E OP
Adder
4.1788235294117653.552
934521AD1-076 C
Adder
4.8470588235294124.12
934511AD1-075 C
Adder
3.3364705882352942.836
3150861SPRUNCD
50/50
0.1930.193
934392AD1-063 E
Adder
0.60.51
966662AG1-536 E
Adder
3.6694117647058833.119
958261AF2-120 C
Adder
3.17411764705882372.698
934146AD1-041 E
Adder
1.97529411764705891.679
957601AF2-054 C
Adder
1.15294117647058810.98
3143316POE
Adder
0.69294117647058820.589
939191AE1-149 C
Adder
5.5294117647058834.7
901082W1-029 E
Adder
13.50705882352941211.481
3150841SPRUNCB
50/50
10.71910.719
3150831SPRUNCA
50/50
10.71910.719
316076AC2-137 E
50/50
1.5391.539
923842AB2-024 E
Adder
1.02235294117647070.869
964211AG1-282 C
Adder
1.02941176470588250.875
316157AD2-030 E
Adder
0.64705882352941180.55
926662AC1-147 E
Adder
0.580.493
916192Z1-068 E
Adder
0.81764705882352940.695
939412AE1-173 E
Adder
21.918.615
957492AF2-043 E
Adder
0.61647058823529410.524
923852AB2-025 E
Adder
0.47411764705882360.403
961941AG1-037 C
Adder
0.192941176470588250.164
961942AG1-037 E
Adder
0.129411764705882370.11
962861AG1-135 C
Adder
3.09411764705882362.63
943741AF1-042 C
Adder
1.5035294117647061.278
942001AE2-212 C
Adder
1.23176470588235291.047
939192AE1-149 E
Adder
3.68588235294117663.133
939312AE1-162 E
Adder
0.67411764705882350.573
934065AD1-033 E
Adder
2.16705882352941171.842
937226AE2-253 E
Adder
2.5117647058823532.135
924517AB2-100 E2
Adder
1.11411764705882340.947
934501AD1-074 C
Adder
13.34588235294117611.344
3150681DARBY 2
50/50
5.1435.143
963612AG1-210 E
Adder
0.49764705882352940.423
940642AE2-051 E
Adder
3.9294117647058823.34
942341AE2-247 C
Adder
0.68588235294117650.583
943462AF1-017 E
Adder
1.0117647058823530.86
919153AA1-139 E2
Adder
1.75411764705882381.491
958162AF2-110 E
Adder
0.95294117647058830.81
924516AB2-100 E1
Adder
1.11411764705882340.947
934512AD1-075 E
Adder
1.69882352941176461.444
934502AD1-074 E
Adder
6.7941176470588245.775
966621AG1-532 C
Adder
0.51647058823529410.439
918512AA1-065 E OP
Adder
2.1329411764705881.813
962862AG1-135 E
Adder
2.06235294117647071.753
943742AF1-042 E
Adder
2.45411764705882352.086
940431AE2-027 C
Adder
8.0694117647058836.859
942002AE2-212 E
Adder
0.82117647058823530.698
944581AF1-123 C
Adder
19.5729411764705916.637
941101AE2-104 C
Adder
1.4682352941176471.248
316141AB2-099 E
Adder
0.096470588235294130.082
316075AC2-137 C
50/50
0.4380.438
925865AC1-065 E
Adder
9.377647058823537.971
936582AD2-073 E
Adder
0.494117647058823550.42
961952AG1-038 E
Adder
2.2952941176470591.951
961951AG1-038 C
Adder
1.66235294117647061.413
946282AF1-292 E
Adder
0.380.323
3150601CHESTF5
Adder
33.5858823529411828.548
964212AG1-282 E
Adder
0.68588235294117650.583
962962AG1-145 E
Adder
0.78470588235294130.667
925332AB2-190 E
Adder
4.3082352941176473.662
927226AC1-216 E
Adder
4.0164705882352943.414
941591AE2-156 C
Adder
7.8423529411764716.666
944601AF1-125 C
Adder
19.27176470588235416.381
944591AF1-124 C
Adder
19.64235294117647316.696
936666AD2-085 E
Adder
2.5811764705882352.194
938771AE1-103 C
Adder
1.22588235294117661.042
3145413WATKINS
Adder
0.28235294117647060.24
960081AF2-299 C
Adder
0.68823529411764710.585
316169AC1-164 GEN
50/50
25.43925.439
944582AF1-123 E
Adder
44.8238.097
944592AF1-124 E
Adder
44.9823529411764738.235
935112AD1-144 E
Adder
0.42235294117647060.359
316349AD2-085 C
Adder
1.58235294117647051.345
923832AB2-022 E
Adder
0.52823529411764710.449
938772AE1-103 E
Adder
1.69294117647058841.439
916042Z1-036 E
Adder
11.8376470588235310.062
960082AF2-299 E
Adder
0.458823529411764740.39
946281AF1-292 C
Adder
0.56941176470588240.484
3150691DARBY 3
50/50
5.1615.161
940551AE2-041 C
Adder
4.0035294117647063.403
957832AF2-077 E
Adder
0.74235294117647070.631
935162AD1-151 E
Adder
5.6729411764705884.822
943461AF1-017 C
Adder
0.620.527
932596AC2-079 E
Adder
4.2752941176470593.634
316311AC2-079 C
Adder
2.622.227
938532AE1-072 E
Adder
3.9270588235294123.338
3146326AYDLETT TAP
Adder
0.58117647058823530.494
917122Z2-027 E
Adder
0.57058823529411760.485
920692AA2-178 E
Adder
1.66000000000000011.411
966622AG1-532 E
Adder
0.343529411764705860.292
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.5041.504
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.58824.588
CPLELTFEXP_CPLE->PJM
CLTF
3.1573.157
TVALTFEXP_TVA->PJM
CLTF
1.2281.228
O66PJM->LTFIMP_O-066
CMTX_NF
6.1076.107
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9570.957
SIGELTFEXP_SIGE->PJM
CLTF
0.0340.034
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.4653.465
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.1394.139
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.590.59
LAGNLTFEXP_LAGN->PJM
CLTF
1.5871.587
NYPJM->LTFIMP_NY
CLTF
0.4630.463
LGEELTFEXP_LGEE->PJM
CLTF
0.150.15
WECLTFEXP_WEC->PJM
CLTF
0.0770.077

Details for 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:161.64 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:923.83
MW Contribution:1.85
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:168.52 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:963.14
MW Contribution:1.87
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
50/50
0.8430.843
961942AG1-037 E
50/50
0.5620.562
943171AE2-346 C
50/50
0.3740.374
3151381ROSEMG2
50/50
0.9310.931
934332AD1-057 E
50/50
1.7421.742
934321AD1-056 C
50/50
5.9965.996
934322AD1-056 E
50/50
3.2523.252
934331AD1-057 C
50/50
3.3453.345
927022AC1-189 E
50/50
5.7275.727
925595AC1-034 E
50/50
4.6964.696
920042AA2-088 E OP
50/50
6.4046.404
934521AD1-076 C
50/50
25.10225.102
934511AD1-075 C
50/50
17.27917.279
3145723EMPORIA
50/50
0.2710.271
923573AB1-173 E OP
50/50
2.3742.374
316011AB1-132 C OP
50/50
2.2832.283
919692AA2-053 E OP
50/50
4.4424.442
925785AC1-054 E
Adder
1.90117647058823551.616
316263AC1-034 C
50/50
6.2256.225
316087AB2-174 C
50/50
0.8050.805
962572AG1-106 E
50/50
1.1641.164
932632AC2-084 E
50/50
3.9433.943
926214AC1-099 E
50/50
1.4741.474
940492AE2-034 E
50/50
6.2586.258
934522AD1-076 E
50/50
12.79412.794
943172AE2-346 E
50/50
1.0111.011
918492AA1-063AE OP
50/50
3.2163.216
962571AG1-106 C
50/50
2.6612.661
917332KELFORD E
50/50
2.7032.703
925122AB2-169 E
50/50
10.49610.496
932631AC2-084 C
50/50
1.2271.227
316274AC1-208 C
50/50
9.5699.569
917342Z2-044 E
50/50
0.5880.588
3151311EDGECMA
50/50
14.76714.767
924516AB2-100 E1
50/50
1.791.79
934512AD1-075 E
50/50
8.7968.796
934502AD1-074 E
50/50
35.18435.184
966621AG1-532 C
50/50
0.8350.835
918512AA1-065 E OP
50/50
12.40212.402
918532AA1-067 E
50/50
1.1251.125
960081AF2-299 C
50/50
1.1131.113
3151391GASTONA
50/50
2.992.99
926072AC1-086 E
50/50
9.3659.365
957862AF2-080 E
50/50
4.6294.629
916042Z1-036 E
50/50
57.18957.189
316023AB2-100 C2
50/50
0.5940.594
960082AF2-299 E
50/50
0.7420.742
946281AF1-292 C
50/50
0.9210.921
926071AC1-086 C
50/50
20.57620.576
316317KELFORD C
50/50
0.5890.589
927021AC1-189 C
50/50
11.49811.498
924152AB2-059 E OP
50/50
4.954.95
3156116Z1-036WIND
50/50
1.3161.316
316140AB2-099 C
50/50
0.1610.161
3152921DOMTR78
50/50
2.6612.661
3137643SOCKMAN
50/50
0.5730.573
316212AC1-099 C
50/50
0.3860.386
919710AA2-057 E
50/50
4.074.07
316319Z2-044 C
50/50
0.2070.207
315614AA2-178 C
50/50
3.1813.181
933981AD1-022 C
50/50
18.40618.406
900672V4-068 E
50/50
0.3710.371
3151411GASTONB
50/50
2.992.99
3151261ROARAP2
50/50
1.211.21
316181AB2-040 GEN
50/50
0.9190.919
923263AB1-132 E OP
50/50
5.9885.988
3156063AA2-053SOLA
50/50
1.5851.585
3151281ROARAP4
50/50
1.1451.145
316174AB2-169_C
50/50
1.9111.911
3156011CONETOE2SOL
50/50
1.5831.583
3145946PLYMOUTH TP
50/50
0.6620.662
933982AD1-022 E
50/50
10.0210.02
927146AC1-208 E
50/50
4.2494.249
316049AB1-081 C OP
50/50
1.3321.332
940491AE2-034 C
50/50
2.3412.341
924517AB2-100 E2
50/50
1.791.79
934501AD1-074 C
50/50
69.11769.117
3156021HOLLOMANSOL
50/50
4.1274.127
3156073AA1-063SOLA
50/50
1.1081.108
3151371ROSEMS1
50/50
1.2321.232
961671AG1-007 C
50/50
1.1121.112
316359AB2-059 C OP
50/50
1.571.57
3156083AA2-088SOLA
50/50
0.6410.641
316088AB2-174 E
50/50
4.4594.459
316141AB2-099 E
50/50
0.4210.421
923994AB2-040_E
50/50
4.4524.452
313506AB1-173 C OP
50/50
0.8160.816
3151361ROSEMG1
50/50
1.9891.989
316005AA1-067 C
50/50
0.4290.429
961672AG1-007 E
50/50
0.630.63
316365AB2-100 C1
50/50
0.5940.594
316318V4-068 C
50/50
0.0840.084
926206AC1-098 E
50/50
4.4614.461
316210AC1-098 C
50/50
1.1521.152
316327AA2-057 C
50/50
1.3351.335
920692AA2-178 E
50/50
8.3448.344
966622AG1-532 E
50/50
0.5560.556
922923AB1-081 E OP
50/50
3.4943.494
946282AF1-292 E
50/50
0.6140.614
957861AF2-080 C
50/50
10.44310.443
917512Z2-088 E OP1
50/50
6.1936.193
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4372.437
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.337.3
CPLELTFEXP_CPLE->PJM
CLTF
5.1125.112
TVALTFEXP_TVA->PJM
CLTF
2.2172.217
O66PJM->LTFIMP_O-066
CMTX_NF
3.8433.843
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6050.605
SIGELTFEXP_SIGE->PJM
CLTF
0.0950.095
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.90912.909
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4168.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5351.535
LAGNLTFEXP_LAGN->PJM
CLTF
2.8432.843
NYPJM->LTFIMP_NY
CLTF
0.2690.269
LGEELTFEXP_LGEE->PJM
CLTF
0.4860.486
WECLTFEXP_WEC->PJM
CLTF
0.2620.262

Details for 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.53 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:608.85
MW Contribution:1.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.35 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:642.1
MW Contribution:1.55
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940492AE2-034 E
50/50
2.3072.307
934522AD1-076 E
50/50
6.5986.598
943172AE2-346 E
50/50
0.8430.843
918492AA1-063AE OP
50/50
2.6512.651
962571AG1-106 C
50/50
2.22.2
917332KELFORD E
50/50
2.2482.248
925122AB2-169 E
50/50
6.5316.531
932631AC2-084 C
50/50
1.0111.011
316274AC1-208 C
50/50
7.8537.853
917342Z2-044 E
50/50
0.4760.476
3151311EDGECMA
50/50
11.80811.808
316140AB2-099 C
50/50
0.1340.134
3152921DOMTR78
50/50
1.4921.492
3137643SOCKMAN
50/50
0.4740.474
316212AC1-099 C
50/50
0.3180.318
919710AA2-057 E
50/50
3.3143.314
316319Z2-044 C
50/50
0.1680.168
315614AA2-178 C
50/50
1.1731.173
933981AD1-022 C
50/50
11.12811.128
900672V4-068 E
50/50
0.3070.307
3151411GASTONB
50/50
2.4722.472
3151261ROARAP2
50/50
11
3145946PLYMOUTH TP
50/50
0.3260.326
933982AD1-022 E
50/50
6.0586.058
927146AC1-208 E
50/50
3.4873.487
316049AB1-081 C OP
50/50
1.071.07
962572AG1-106 E
50/50
0.9630.963
932632AC2-084 E
50/50
3.2493.249
926214AC1-099 E
50/50
1.2141.214
920042AA2-088 E OP
Adder
5.2376470588235294.452
934521AD1-076 C
50/50
12.94512.945
934511AD1-075 C
50/50
8.9118.911
3145723EMPORIA
Adder
0.22470588235294120.191
923573AB1-173 E OP
50/50
1.9641.964
316011AB1-132 C OP
50/50
1.8881.888
919692AA2-053 E OP
50/50
3.6823.682
925785AC1-054 E
Adder
1.57058823529411761.335
316263AC1-034 C
50/50
4.9994.999
316318V4-068 C
50/50
0.0690.069
926206AC1-098 E
50/50
3.6753.675
316210AC1-098 C
50/50
0.9490.949
316327AA2-057 C
50/50
1.0871.087
961941AG1-037 C
50/50
0.7020.702
961942AG1-037 E
50/50
0.4680.468
943171AE2-346 C
50/50
0.3120.312
3151381ROSEMG2
50/50
0.7680.768
934332AD1-057 E
50/50
1.4131.413
934321AD1-056 C
50/50
4.8664.866
934322AD1-056 E
50/50
2.6392.639
934331AD1-057 C
50/50
2.7142.714
927022AC1-189 E
50/50
4.4794.479
925595AC1-034 E
50/50
3.7713.771
940491AE2-034 C
50/50
0.8630.863
924517AB2-100 E2
Adder
1.48352941176470581.261
934501AD1-074 C
50/50
35.64335.643
3156021HOLLOMANSOL
50/50
3.4513.451
3156073AA1-063SOLA
50/50
0.9130.913
3151371ROSEMS1
50/50
1.0151.015
961671AG1-007 C
50/50
0.8770.877
316359AB2-059 C OP
50/50
1.2611.261
924516AB2-100 E1
Adder
1.48352941176470581.261
934512AD1-075 E
50/50
4.5364.536
934502AD1-074 E
50/50
18.14418.144
966621AG1-532 C
Adder
0.6917647058823530.588
918512AA1-065 E OP
50/50
10.3710.37
918532AA1-067 E
50/50
0.8740.874
316088AB2-174 E
Adder
3.68941176470588243.136
316141AB2-099 E
50/50
0.3510.351
923994AB2-040_E
50/50
3.6833.683
313506AB1-173 C OP
50/50
0.6750.675
3151361ROSEMG1
50/50
1.6391.639
316005AA1-067 C
50/50
0.3330.333
961672AG1-007 E
50/50
0.4970.497
946282AF1-292 E
Adder
0.50823529411764710.432
957861AF2-080 C
50/50
8.1668.166
917512Z2-088 E OP1
50/50
4.8634.863
960081AF2-299 C
Adder
0.92117647058823540.783
3151391GASTONA
50/50
2.4722.472
926072AC1-086 E
50/50
7.7427.742
957862AF2-080 E
50/50
3.623.62
916042Z1-036 E
Adder
9.7517647058823538.289
960082AF2-299 E
Adder
0.61411764705882350.522
946281AF1-292 C
Adder
0.76235294117647070.648
926071AC1-086 C
50/50
17.00917.009
316317KELFORD C
50/50
0.4890.489
927021AC1-189 C
50/50
8.9918.991
924152AB2-059 E OP
50/50
3.9763.976
920692AA2-178 E
50/50
3.0763.076
966622AG1-532 E
Adder
0.46117647058823530.392
922923AB1-081 E OP
50/50
2.8072.807
316181AB2-040 GEN
50/50
0.7610.761
923263AB1-132 E OP
50/50
4.954.95
3156063AA2-053SOLA
50/50
1.3141.314
3151281ROARAP4
50/50
0.9460.946
316174AB2-169_C
50/50
1.1891.189
3156011CONETOE2SOL
50/50
1.2431.243
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9321.932
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.62929.629
CPLELTFEXP_CPLE->PJM
CLTF
4.0524.052
TVALTFEXP_TVA->PJM
CLTF
1.7681.768
O66PJM->LTFIMP_O-066
CMTX_NF
3.0083.008
G-007PJM->LTFIMP_G-007
CMTX_NF
0.4730.473
SIGELTFEXP_SIGE->PJM
CLTF
0.0760.076
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.35910.359
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7216.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.2291.229
LAGNLTFEXP_LAGN->PJM
CLTF
2.2672.267
NYPJM->LTFIMP_NY
CLTF
0.210.21
LGEELTFEXP_LGEE->PJM
CLTF
0.3890.389
WECLTFEXP_WEC->PJM
CLTF
0.210.21

Details for 6PEMBROKE-6WALBMRL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6PEMBROKE-6WALBMRL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 238_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.27 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:779.15
MW Contribution:1.55
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6PEMBROKE-6WALBMRL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 238_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:110.32 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:808.85
MW Contribution:1.57
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940492AE2-034 E
50/50
9.2879.287
934522AD1-076 E
50/50
14.72614.726
943172AE2-346 E
50/50
0.4540.454
918492AA1-063AE OP
Adder
1.88588235294117661.603
962571AG1-106 C
50/50
1.6841.684
917332KELFORD E
50/50
1.2411.241
925122AB2-169 E
50/50
9.6079.607
932631AC2-084 C
50/50
0.6290.629
316274AC1-208 C
Adder
5.202352941176474.422
917342Z2-044 E
Adder
0.33176470588235290.282
3151311EDGECMA
Adder
8.677647058823537.376
3156116Z1-036WIND
50/50
2.5432.543
316140AB2-099 C
50/50
0.0720.072
3152921DOMTR78
50/50
2.7962.796
3137643SOCKMAN
Adder
0.36588235294117650.311
316212AC1-099 C
50/50
0.1980.198
919710AA2-057 E
Adder
2.24941176470588241.912
938531AE1-072 C
Adder
-8.872941176470588-7.542
315614AA2-178 C
50/50
4.7214.721
933981AD1-022 C
50/50
17.46517.465
900672V4-068 E
Adder
0.18470588235294120.157
3151411GASTONB
50/50
1.8921.892
3145946PLYMOUTH TP
50/50
0.7970.797
933982AD1-022 E
50/50
9.5089.508
927146AC1-208 E
Adder
2.31058823529411761.964
962572AG1-106 E
50/50
0.7370.737
932632AC2-084 E
50/50
2.0212.021
926214AC1-099 E
50/50
0.7550.755
934521AD1-076 C
50/50
28.89228.892
934511AD1-075 C
50/50
19.88819.888
3145723EMPORIA
Adder
0.215294117647058830.183
923573AB1-173 E OP
Adder
1.6635294117647061.414
316011AB1-132 C OP
50/50
1.4451.445
919692AA2-053 E OP
Adder
2.4188235294117652.056
316263AC1-034 C
Adder
3.60470588235294143.064
316365AB2-100 C1
50/50
0.5490.549
926206AC1-098 E
50/50
2.2862.286
316210AC1-098 C
50/50
0.5910.591
961941AG1-037 C
50/50
0.3780.378
961942AG1-037 E
50/50
0.2520.252
943171AE2-346 C
50/50
0.1680.168
3151381ROSEMG2
50/50
0.5850.585
934332AD1-057 E
Adder
1.05764705882352940.899
934321AD1-056 C
Adder
3.64117647058823573.095
934322AD1-056 E
Adder
1.97529411764705891.679
934331AD1-057 C
Adder
2.0305882352941181.726
927022AC1-189 E
50/50
3.3063.306
925595AC1-034 E
Adder
2.71999999999999982.312
940491AE2-034 C
50/50
3.4743.474
924517AB2-100 E2
50/50
1.6551.655
934501AD1-074 C
50/50
79.55379.553
3156021HOLLOMANSOL
50/50
1.7431.743
3151371ROSEMS1
50/50
0.7740.774
961671AG1-007 C
50/50
0.6460.646
924516AB2-100 E1
50/50
1.6551.655
934512AD1-075 E
50/50
10.12410.124
934502AD1-074 E
50/50
40.49740.497
966621AG1-532 C
Adder
0.69764705882352940.593
918512AA1-065 E OP
50/50
5.2385.238
918532AA1-067 E
50/50
0.6460.646
316088AB2-174 E
Adder
3.28588235294117672.793
316141AB2-099 E
50/50
0.1890.189
923994AB2-040_E
Adder
3.11882352941176462.651
3151361ROSEMG1
50/50
1.251.25
316005AA1-067 C
50/50
0.2460.246
961672AG1-007 E
50/50
0.3660.366
946282AF1-292 E
Adder
0.51294117647058820.436
957861AF2-080 C
50/50
6.0276.027
917512Z2-088 E OP1
50/50
3.5873.587
960081AF2-299 C
Adder
0.92941176470588240.79
3151391GASTONA
50/50
1.8921.892
926072AC1-086 E
50/50
5.9275.927
957862AF2-080 E
50/50
2.6722.672
916042Z1-036 E
50/50
110.543110.543
316023AB2-100 C2
50/50
0.5490.549
960082AF2-299 E
Adder
0.620.527
946281AF1-292 C
Adder
0.76941176470588240.654
926071AC1-086 C
50/50
13.02213.022
316317KELFORD C
50/50
0.270.27
927021AC1-189 C
50/50
6.6366.636
924152AB2-059 E OP
Adder
2.86705882352941142.437
920692AA2-178 E
50/50
12.38212.382
966622AG1-532 E
Adder
0.46470588235294120.395
922923AB1-081 E OP
Adder
2.0235294117647061.72
940481AE2-033 C
Adder
8.8694117647058827.539
940482AE2-033 E
Adder
5.985.083
923263AB1-132 E OP
50/50
3.793.79
316174AB2-169_C
50/50
1.751.75
3156011CONETOE2SOL
50/50
0.9170.917
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3961.396
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.25321.253
CPLELTFEXP_CPLE->PJM
CLTF
2.9282.928
TVALTFEXP_TVA->PJM
CLTF
1.241.24
O66PJM->LTFIMP_O-066
CMTX_NF
2.4252.425
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3810.381
SIGELTFEXP_SIGE->PJM
CLTF
0.0520.052
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.9766.976
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.6744.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.8410.841
LAGNLTFEXP_LAGN->PJM
CLTF
1.5921.592
NYPJM->LTFIMP_NY
CLTF
0.1720.172
LGEELTFEXP_LGEE->PJM
CLTF
0.2640.264
WECLTFEXP_WEC->PJM
CLTF
0.1420.142

Details for 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:107.58 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:614.81
MW Contribution:0.97
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.99 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:645.76
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
937482AD2-202 E
50/50
1.621.62
3151581KERR 1
50/50
0.3970.397
3151601KERR 3
50/50
1.1131.113
3152661PLYWOOD A
50/50
1.3061.306
941011AE2-092 C
Adder
-7.384705882352941-6.277
3137643SOCKMAN
Adder
0.236470588235294130.201
937481AD2-202 C
50/50
0.5570.557
3151641KERR 7
50/50
1.1131.113
316205AC1-080 C
50/50
0.2470.247
316123AC1-075 C
50/50
0.740.74
924302AB2-077 E O1
50/50
1.321.32
3151621KERR 5
50/50
1.1131.113
316222AC1-221 C
50/50
1.3041.304
942752AE2-291 E
50/50
4.2094.209
925612AC1-036 E
50/50
0.6080.608
316238AB2-078 C O1
50/50
0.3240.324
924312AB2-078 E O1
50/50
1.321.32
316237AB2-079 C O1
50/50
0.3240.324
926274AC1-105 E
50/50
2.892.89
316336AC2-165 C
Adder
-4.488235294117647-3.815
934622AD1-088 E
50/50
8.0788.078
934611AD1-087 C
50/50
1.9191.919
934612AD1-087 E
50/50
5.5365.536
3151611KERR 4
50/50
1.1131.113
927255AC1-221 E
50/50
3.413.41
964242AG1-285 E
50/50
10.84610.846
924162AB2-060 E OP
50/50
3.9993.999
313527AB2-043 C
50/50
0.5090.509
3151591KERR 2
50/50
1.1131.113
964792AG1-342 E
50/50
2.4822.482
316283AC2-100 C
50/50
1.0191.019
932763AC2-100 E
50/50
2.2422.242
3145723EMPORIA
Adder
0.136470588235294120.116
923573AB1-173 E OP
Adder
1.06470588235294120.905
919692AA2-053 E OP
Adder
1.31411764705882361.117
959311AF2-222 C
Adder
9.9482352941176468.456
925785AC1-054 E
50/50
2.3712.371
942751AE2-291 C
50/50
6.3136.313
316239AB2-077 C O1
50/50
0.3240.324
935171AD1-152 C
50/50
1.8391.839
964791AG1-342 C
50/50
3.7243.724
925997AC1-075 E
50/50
2.5662.566
936262AD2-033 E
Adder
3.5152941176470592.988
957482AF2-042 E
50/50
57.29557.295
934621AD1-088 C
50/50
16.77816.778
942461AE2-259 C
Adder
-11.085882352941177-9.423
935172AD1-152 E
50/50
7.5637.563
966621AG1-532 C
Adder
0.437647058823529440.372
3147223TWITTYS
50/50
0.6740.674
959312AF2-222 E
Adder
6.66588235294117755.666
924022AB2-043 E O1
50/50
5.1075.107
316003AC1-222 C
50/50
1.0461.046
926024AC1-080 E
50/50
0.8510.851
957481AF2-042 C
50/50
85.94285.942
316088AB2-174 E
Adder
2.0917647058823531.778
923994AB2-040_E
Adder
1.99764705882352931.698
924322AB2-079 E O1
50/50
1.321.32
943902AF1-058 E
50/50
1.4231.423
946282AF1-292 E
Adder
0.32235294117647060.274
3151541CLOVER2
50/50
19.33819.338
316131AB2-060 C
50/50
1.3891.389
316129AC1-054 C
50/50
0.8410.841
316118AC1-105 C
50/50
0.9880.988
960081AF2-299 C
Adder
0.58352941176470590.496
936261AD2-033 C
Adder
5.2729411764705894.482
3151631KERR 6
50/50
1.1131.113
962562AG1-105 E
50/50
6.1616.161
316248AF1-058 C
50/50
0.3490.349
960082AF2-299 E
Adder
0.38941176470588240.331
946281AF1-292 C
Adder
0.48352941176470590.411
3151531CLOVER1
50/50
19.51919.519
964241AG1-285 C
50/50
16.2716.27
316034AC1-036 C
50/50
0.1660.166
962561AG1-105 C
50/50
9.2429.242
966622AG1-532 E
Adder
0.29176470588235290.248
927264AC1-222 E
50/50
4.2714.271
938821AE1-108 C
Adder
-8.042352941176471-6.836
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6471.647
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.50427.504
CPLELTFEXP_CPLE->PJM
CLTF
3.4573.457
TVALTFEXP_TVA->PJM
CLTF
1.5461.546
O66PJM->LTFIMP_O-066
CMTX_NF
3.8923.892
G-007PJM->LTFIMP_G-007
CMTX_NF
0.610.61
SIGELTFEXP_SIGE->PJM
CLTF
0.0570.057
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.2877.287
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.6115.611
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.9490.949
LAGNLTFEXP_LAGN->PJM
CLTF
1.9781.978
NYPJM->LTFIMP_NY
CLTF
0.2910.291
LGEELTFEXP_LGEE->PJM
CLTF
0.2860.286
WECLTFEXP_WEC->PJM
CLTF
0.1510.151

Details for 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 238_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.54 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:766.49
MW Contribution:1.55
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 238_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.59 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:796.19
MW Contribution:1.57
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940492AE2-034 E
50/50
9.2879.287
934522AD1-076 E
50/50
14.72614.726
943172AE2-346 E
50/50
0.4540.454
918492AA1-063AE OP
Adder
1.88588235294117661.603
962571AG1-106 C
50/50
1.6841.684
917332KELFORD E
50/50
1.2411.241
925122AB2-169 E
50/50
9.6079.607
932631AC2-084 C
50/50
0.6290.629
316274AC1-208 C
Adder
5.202352941176474.422
917342Z2-044 E
Adder
0.33176470588235290.282
3151311EDGECMA
Adder
8.677647058823537.376
938531AE1-072 C
Adder
-8.872941176470588-7.542
315614AA2-178 C
50/50
4.7214.721
933981AD1-022 C
50/50
17.46517.465
900672V4-068 E
Adder
0.18470588235294120.157
3151411GASTONB
50/50
1.8921.892
3145946PLYMOUTH TP
50/50
0.7970.797
933982AD1-022 E
50/50
9.5089.508
927146AC1-208 E
Adder
2.31058823529411761.964
962572AG1-106 E
50/50
0.7370.737
932632AC2-084 E
50/50
2.0212.021
926214AC1-099 E
50/50
0.7550.755
934521AD1-076 C
50/50
28.89228.892
934511AD1-075 C
50/50
19.88819.888
3145723EMPORIA
Adder
0.215294117647058830.183
923573AB1-173 E OP
Adder
1.6635294117647061.414
316011AB1-132 C OP
50/50
1.4451.445
919692AA2-053 E OP
Adder
2.4188235294117652.056
316263AC1-034 C
Adder
3.60470588235294143.064
316365AB2-100 C1
50/50
0.5490.549
926206AC1-098 E
50/50
2.2862.286
316210AC1-098 C
50/50
0.5910.591
961941AG1-037 C
50/50
0.3780.378
961942AG1-037 E
50/50
0.2520.252
943171AE2-346 C
50/50
0.1680.168
3151381ROSEMG2
50/50
0.5850.585
934332AD1-057 E
Adder
1.05764705882352940.899
934321AD1-056 C
Adder
3.64117647058823573.095
934322AD1-056 E
Adder
1.97529411764705891.679
934331AD1-057 C
Adder
2.0305882352941181.726
927022AC1-189 E
50/50
3.3063.306
925595AC1-034 E
Adder
2.71999999999999982.312
3156116Z1-036WIND
50/50
2.5432.543
316140AB2-099 C
50/50
0.0720.072
3152921DOMTR78
50/50
2.7962.796
3137643SOCKMAN
Adder
0.36588235294117650.311
316212AC1-099 C
50/50
0.1980.198
919710AA2-057 E
Adder
2.24941176470588241.912
940491AE2-034 C
50/50
3.4743.474
924517AB2-100 E2
50/50
1.6551.655
934501AD1-074 C
50/50
79.55379.553
3156021HOLLOMANSOL
50/50
1.7431.743
3151371ROSEMS1
50/50
0.7740.774
961671AG1-007 C
50/50
0.6460.646
924516AB2-100 E1
50/50
1.6551.655
934512AD1-075 E
50/50
10.12410.124
934502AD1-074 E
50/50
40.49740.497
966621AG1-532 C
Adder
0.69764705882352940.593
918512AA1-065 E OP
50/50
5.2385.238
918532AA1-067 E
50/50
0.6460.646
316088AB2-174 E
Adder
3.28588235294117672.793
316141AB2-099 E
50/50
0.1890.189
923994AB2-040_E
Adder
3.11882352941176462.651
3151361ROSEMG1
50/50
1.251.25
316005AA1-067 C
50/50
0.2460.246
961672AG1-007 E
50/50
0.3660.366
946282AF1-292 E
Adder
0.51294117647058820.436
957861AF2-080 C
50/50
6.0276.027
917512Z2-088 E OP1
50/50
3.5873.587
960081AF2-299 C
Adder
0.92941176470588240.79
3151391GASTONA
50/50
1.8921.892
926072AC1-086 E
50/50
5.9275.927
957862AF2-080 E
50/50
2.6722.672
916042Z1-036 E
50/50
110.543110.543
316023AB2-100 C2
50/50
0.5490.549
960082AF2-299 E
Adder
0.620.527
946281AF1-292 C
Adder
0.76941176470588240.654
926071AC1-086 C
50/50
13.02213.022
316317KELFORD C
50/50
0.270.27
927021AC1-189 C
50/50
6.6366.636
924152AB2-059 E OP
Adder
2.86705882352941142.437
920692AA2-178 E
50/50
12.38212.382
966622AG1-532 E
Adder
0.46470588235294120.395
922923AB1-081 E OP
Adder
2.0235294117647061.72
940481AE2-033 C
Adder
8.8694117647058827.539
940482AE2-033 E
Adder
5.985.083
923263AB1-132 E OP
50/50
3.793.79
316174AB2-169_C
50/50
1.751.75
3156011CONETOE2SOL
50/50
0.9170.917
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3961.396
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.25321.253
CPLELTFEXP_CPLE->PJM
CLTF
2.9282.928
TVALTFEXP_TVA->PJM
CLTF
1.241.24
O66PJM->LTFIMP_O-066
CMTX_NF
2.4252.425
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3810.381
SIGELTFEXP_SIGE->PJM
CLTF
0.0520.052
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.9766.976
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.6744.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.8410.841
LAGNLTFEXP_LAGN->PJM
CLTF
1.5921.592
NYPJM->LTFIMP_NY
CLTF
0.1720.172
LGEELTFEXP_LGEE->PJM
CLTF
0.2640.264
WECLTFEXP_WEC->PJM
CLTF
0.1420.142

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:127.47 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:865.08
MW Contribution:7.18
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:132.38 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:898.41
MW Contribution:7.25
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
920042AA2-088 E OP
50/50
9.2439.243
934521AD1-076 C
Adder
7.235294117647066.15
934511AD1-075 C
Adder
4.97999999999999954.233
3145723EMPORIA
50/50
0.9510.951
923573AB1-173 E OP
50/50
6.3236.323
316011AB1-132 C OP
50/50
4.6914.691
919692AA2-053 E OP
50/50
5.8725.872
925785AC1-054 E
50/50
3.2563.256
316263AC1-034 C
50/50
6.8536.853
3151151S HAMPT1
50/50
0.9630.963
934522AD1-076 E
Adder
3.6882352941176473.135
943172AE2-346 E
50/50
0.5750.575
918492AA1-063AE OP
50/50
5.1265.126
962571AG1-106 C
50/50
5.4675.467
917332KELFORD E
50/50
1.681.68
925122AB2-169 E
50/50
3.9923.992
932631AC2-084 C
50/50
1.1471.147
316274AC1-208 C
50/50
10.95410.954
917342Z2-044 E
50/50
0.6430.643
3151311EDGECMA
50/50
16.29316.293
923852AB2-025 E
50/50
4.7594.759
3145413WATKINS
50/50
0.4340.434
960081AF2-299 C
50/50
4.3084.308
3151391GASTONA
50/50
6.1436.143
926072AC1-086 E
50/50
19.23819.238
957862AF2-080 E
50/50
3.0143.014
316023AB2-100 C2
50/50
2.7722.772
960082AF2-299 E
50/50
2.8722.872
946281AF1-292 C
50/50
3.5663.566
926071AC1-086 C
50/50
42.26942.269
316317KELFORD C
50/50
0.3660.366
927021AC1-189 C
50/50
7.4877.487
924152AB2-059 E OP
50/50
5.4515.451
961941AG1-037 C
50/50
0.480.48
961942AG1-037 E
50/50
0.320.32
943171AE2-346 C
50/50
0.2130.213
3151381ROSEMG2
50/50
1.8331.833
934332AD1-057 E
50/50
2.6472.647
934321AD1-056 C
50/50
9.1119.111
934322AD1-056 E
50/50
4.9424.942
934331AD1-057 C
50/50
5.0825.082
927022AC1-189 E
50/50
3.7293.729
925595AC1-034 E
50/50
5.175.17
316087AB2-174 C
50/50
2.4072.407
962572AG1-106 E
50/50
2.3922.392
932632AC2-084 E
50/50
3.6853.685
926214AC1-099 E
50/50
1.3771.377
316140AB2-099 C
50/50
0.0910.091
3137643SOCKMAN
50/50
1.2021.202
316212AC1-099 C
50/50
0.3610.361
919710AA2-057 E
50/50
4.4414.441
316319Z2-044 C
50/50
0.2270.227
933981AD1-022 C
50/50
5.8115.811
900672V4-068 E
50/50
0.330.33
3147043LAWRENC
50/50
0.5440.544
3151411GASTONB
50/50
6.1436.143
3151261ROARAP2
50/50
2.0542.054
940541AE2-040 C
50/50
11.76711.767
940481AE2-033 C
50/50
63.78563.785
924516AB2-100 E1
50/50
8.3568.356
934512AD1-075 E
Adder
2.53529411764705872.155
934502AD1-074 E
Adder
10.1411764705882358.62
966621AG1-532 C
50/50
3.2313.231
918512AA1-065 E OP
50/50
4.8034.803
918532AA1-067 E
50/50
0.5780.578
940482AE2-033 E
50/50
43.00143.001
316181AB2-040 GEN
50/50
2.4482.448
923263AB1-132 E OP
50/50
12.30112.301
3156063AA2-053SOLA
50/50
2.0952.095
3151281ROARAP4
50/50
1.9431.943
316174AB2-169_C
50/50
0.7270.727
3156011CONETOE2SOL
50/50
1.1631.163
933982AD1-022 E
50/50
3.1633.163
927146AC1-208 E
50/50
4.8644.864
316049AB1-081 C OP
50/50
1.4671.467
924517AB2-100 E2
50/50
8.3568.356
934501AD1-074 C
Adder
19.92235294117647416.934
3156021HOLLOMANSOL
50/50
1.5981.598
3156073AA1-063SOLA
50/50
1.7661.766
3151371ROSEMS1
50/50
2.4242.424
961671AG1-007 C
50/50
0.9020.902
316359AB2-059 C OP
50/50
1.7291.729
3156083AA2-088SOLA
50/50
0.9260.926
316088AB2-174 E
50/50
13.32613.326
316141AB2-099 E
50/50
0.240.24
923994AB2-040_E
50/50
11.85511.855
313506AB1-173 C OP
50/50
2.1742.174
3151361ROSEMG1
50/50
3.9133.913
316005AA1-067 C
50/50
0.220.22
961672AG1-007 E
50/50
0.5110.511
316365AB2-100 C1
50/50
2.7722.772
316318V4-068 C
50/50
0.0740.074
926206AC1-098 E
50/50
4.1694.169
316210AC1-098 C
50/50
1.0771.077
316327AA2-057 C
50/50
1.4571.457
966622AG1-532 E
50/50
2.1542.154
922923AB1-081 E OP
50/50
3.8483.848
316315AB2-025 C
50/50
1.6711.671
946282AF1-292 E
50/50
2.3782.378
316129AC1-054 C
50/50
1.1551.155
957861AF2-080 C
50/50
6.86.8
917512Z2-088 E OP1
50/50
4.554.55
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.022.02
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.20331.203
CPLELTFEXP_CPLE->PJM
CLTF
4.2374.237
TVALTFEXP_TVA->PJM
CLTF
1.7921.792
O66PJM->LTFIMP_O-066
CMTX_NF
4.4294.429
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6960.696
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.519.51
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.6696.669
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1761.176
LAGNLTFEXP_LAGN->PJM
CLTF
2.2982.298
NYPJM->LTFIMP_NY
CLTF
0.320.32
LGEELTFEXP_LGEE->PJM
CLTF
0.3650.365
WECLTFEXP_WEC->PJM
CLTF
0.1950.195

Details for 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.68 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1020.42
MW Contribution:1.36
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.56 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:989.69
MW Contribution:1.3
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316084AB2-161 E
50/50
3.213.21
316083AB2-161 C
50/50
0.3210.321
940641AE2-051 C
Adder
6.0952941176470595.181
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
933982AD1-022 E
Adder
1.721.462
934622AD1-088 E
Adder
1.38117647058823521.174
934612AD1-087 E
Adder
1.1117647058823530.945
927146AC1-208 E
Adder
1.51.275
3150761HOPPOLC
50/50
1.0021.002
926755AC1-161 E
Adder
3.78588235294117673.218
933291AC2-141 C
Adder
8.8694117647058827.539
925522AC1-027 E
Adder
0.410588235294117640.349
3145256KINGFORK
Adder
0.357647058823529430.304
957872AF2-081 E
Adder
1.4317647058823531.217
941102AE2-104 E
Adder
2.0188235294117651.716
962572AG1-106 E
Adder
0.50117647058823530.426
964242AG1-285 E
Adder
2.5717647058823532.186
924162AB2-060 E OP
Adder
1.3117647058823531.115
932632AC2-084 E
Adder
1.20235294117647061.022
926214AC1-099 E
Adder
0.44941176470588240.382
944641AF1-129 C
50/50
120.262120.262
316240AF1-291 C
50/50
2.4482.448
924814AB2-134 E
Adder
6.7529411764705885.74
316381AD1-082 C
50/50
0.7330.733
942342AE2-247 E
Adder
0.94470588235294130.803
919152AA1-139 E1
Adder
1.36588235294117651.161
920042AA2-088 E OP
Adder
4.0811764705882353.469
934521AD1-076 C
Adder
4.377647058823533.721
934511AD1-075 C
Adder
3.01411764705882362.562
3145723EMPORIA
Adder
0.185882352941176470.158
923573AB1-173 E OP
Adder
1.36823529411764721.163
919692AA2-053 E OP
Adder
1.64941176470588241.402
925785AC1-054 E
Adder
1.2082352941176471.027
316263AC1-034 C
Adder
2.3517647058823531.999
3150651CHESTF6
50/50
21.89721.897
946262AF1-291 E
50/50
1.6321.632
933292AC2-141 E
Adder
3.78588235294117673.218
934576AD1-082 E
50/50
2.5582.558
944602AF1-125 E
Adder
33.8847058823529428.802
3145506HICKORY
Adder
0.72352941176470590.615
957871AF2-081 C
Adder
3.34117647058823542.84
943612AF1-032 E
Adder
0.320.272
940492AE2-034 E
Adder
1.09058823529411760.927
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
918492AA1-063AE OP
Adder
1.59411764705882361.355
962571AG1-106 C
Adder
1.14705882352941170.975
937482AD2-202 E
Adder
0.32588235294117650.277
917332KELFORD E
Adder
0.61411764705882350.522
925122AB2-169 E
Adder
2.04352941176470631.737
316274AC1-208 C
Adder
3.3788235294117652.872
917342Z2-044 E
Adder
0.215294117647058830.183
3151311EDGECMA
Adder
5.5117647058823534.685
3143316POE
50/50
1.0861.086
939191AE1-149 C
50/50
7.1377.137
901082W1-029 E
Adder
10.9870588235294139.339
926206AC1-098 E
Adder
1.35999999999999991.156
940432AE2-027 E
Adder
4.6964705882352943.992
934012AD1-025 E
Adder
5.3364705882352944.536
939411AE1-173 C
Adder
31.5352941176470626.805
913392Y1-086 E
Adder
0.74470588235294120.633
3137643SOCKMAN
Adder
0.288235294117647030.245
919710AA2-057 E
Adder
1.44823529411764731.231
3150781HOPHCF2
50/50
1.5941.594
942001AE2-212 C
50/50
2.1112.111
939192AE1-149 E
50/50
4.7584.758
939312AE1-162 E
Adder
0.5717647058823530.486
934065AD1-033 E
Adder
1.6670588235294121.417
937226AE2-253 E
Adder
1.9482352941176471.656
924517AB2-100 E2
Adder
1.36823529411764721.163
934501AD1-074 C
Adder
12.05529411764705810.247
957482AF2-042 E
Adder
11.3435294117647069.642
934621AD1-088 C
Adder
2.86941176470588262.439
935172AD1-152 E
Adder
1.6435294117647061.397
961671AG1-007 C
Adder
0.332941176470588240.283
316132AB2-190 C
50/50
2.4122.412
940642AE2-051 E
Adder
4.0635294117647063.454
942341AE2-247 C
Adder
0.68470588235294120.582
943462AF1-017 E
Adder
1.00941176470588250.858
919153AA1-139 E2
Adder
1.36588235294117651.161
958162AF2-110 E
Adder
0.82470588235294120.701
924516AB2-100 E1
Adder
1.36823529411764721.163
934512AD1-075 E
Adder
1.53411764705882361.304
934502AD1-074 E
Adder
6.1364705882352945.216
966621AG1-532 C
Adder
0.61294117647058830.521
918512AA1-065 E OP
Adder
2.04235294117647071.736
924022AB2-043 E O1
Adder
1.60117647058823541.361
918532AA1-067 E
Adder
0.251764705882352950.214
3150771HOPHCF1
50/50
1.5941.594
940431AE2-027 C
Adder
7.0447058823529425.988
942002AE2-212 E
50/50
1.4081.408
944581AF1-123 C
Adder
15.03411764705882412.779
941101AE2-104 C
Adder
1.26941176470588221.079
957481AF2-042 C
Adder
17.0152941176470614.463
316088AB2-174 E
Adder
2.7588235294117652.345
316141AB2-099 E
Adder
0.095294117647058830.081
923994AB2-040_E
Adder
2.56588235294117652.181
924322AB2-079 E O1
Adder
0.41176470588235290.35
961672AG1-007 E
Adder
0.188235294117647060.16
944012AF1-069 E
Adder
1.7917647058823531.523
946282AF1-292 E
Adder
0.45058823529411770.383
957861AF2-080 C
Adder
2.7023529411764712.297
917512Z2-088 E OP1
Adder
1.73411764705882351.474
925332AB2-190 E
50/50
4.6914.691
927226AC1-216 E
Adder
4.122352941176473.504
941591AE2-156 C
Adder
6.1141176470588245.197
944601AF1-125 C
Adder
14.80235294117647312.582
944591AF1-124 C
Adder
15.08705882352941312.824
936666AD2-085 E
Adder
2.5752941176470592.189
944011AF1-069 C
Adder
4.6141176470588243.922
938771AE1-103 C
Adder
1.11764705882352940.95
3145413WATKINS
Adder
0.26470588235294120.225
963041AG1-153 C
Adder
1.9482352941176471.656
960081AF2-299 C
Adder
0.81647058823529410.694
926072AC1-086 E
Adder
4.0352941176470593.43
957862AF2-080 E
Adder
1.19764705882352951.018
944582AF1-123 E
Adder
34.4258823529411829.262
944592AF1-124 E
Adder
34.55058823529411429.368
935112AD1-144 E
Adder
0.33176470588235290.282
316349AD2-085 C
Adder
1.57882352941176471.342
923832AB2-022 E
Adder
0.421176470588235260.358
938772AE1-103 E
Adder
1.5435294117647061.312
916042Z1-036 E
Adder
9.9682352941176488.473
963042AG1-153 E
Adder
2.92235294117647062.484
960082AF2-299 E
Adder
0.54470588235294130.463
946281AF1-292 C
Adder
0.67529411764705880.574
926071AC1-086 C
Adder
8.8647058823529427.535
964241AG1-285 C
Adder
3.85882352941176483.28
927021AC1-189 C
Adder
2.97529411764705862.529
924152AB2-059 E OP
Adder
1.87058823529411791.59
3150841SPRUNCB
Adder
2.6776470588235292.276
3150831SPRUNCA
Adder
2.6776470588235292.276
3150791HOPHCF3
50/50
1.5941.594
3150801HOPHCF4
50/50
2.4192.419
926662AC1-147 E
Adder
0.452941176470588240.385
916192Z1-068 E
Adder
0.63294117647058830.538
939412AE1-173 E
Adder
21.0235294117647117.87
957492AF2-043 E
Adder
0.49294117647058820.419
941032AE2-094 E
Adder
6.3247058823529425.376
941031AE2-094 C
Adder
14.12000000000000112.002
923852AB2-025 E
Adder
0.6317647058823530.537
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
934332AD1-057 E
Adder
0.69647058823529410.592
934321AD1-056 C
Adder
2.3988235294117652.039
934322AD1-056 E
Adder
1.30117647058823541.106
934331AD1-057 C
Adder
1.33882352941176451.138
927022AC1-189 E
Adder
1.48235294117647071.26
925595AC1-034 E
Adder
1.77411764705882361.508
935162AD1-151 E
50/50
6.0156.015
943461AF1-017 C
Adder
0.61882352941176480.526
932596AC2-079 E
Adder
4.1964705882352953.567
316311AC2-079 C
Adder
2.5717647058823532.186
938532AE1-072 E
Adder
3.07058823529411742.61
3146326AYDLETT TAP
Adder
0.455294117647058850.387
917122Z2-027 E
Adder
0.457647058823529460.389
920692AA2-178 E
Adder
1.4552941176470591.237
966622AG1-532 E
Adder
0.408235294117647030.347
922923AB1-081 E OP
Adder
1.321.122
3150731STONECA
50/50
4.5124.512
935161AD1-151 C
50/50
9.0229.022
932046AC2-012 E
Adder
4.4823529411764713.81
938531AE1-072 C
Adder
5.8905882352941185.007
958161AF2-110 C
Adder
0.51764705882352950.44
3145393UNCAMP
Adder
2.3247058823529411.976
933981AD1-022 C
Adder
3.162.686
900672V4-068 E
Adder
0.136470588235294120.116
924302AB2-077 E O1
Adder
0.41176470588235290.35
961611AG1-000B C
Adder
7.342352941176476.241
940541AE2-040 C
Adder
1.56117647058823541.327
940481AE2-033 C
Adder
8.6517647058823537.354
940482AE2-033 E
Adder
5.8329411764705884.958
923263AB1-132 E OP
Adder
2.582.193
924312AB2-078 E O1
Adder
0.41176470588235290.35
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
TVALTFEXP_TVA->PJM
CLTF
1.561.56
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
NYPJM->LTFIMP_NY
CLTF
0.4360.436
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
WECLTFEXP_WEC->PJM
CLTF
0.140.14

Details for 6WALBMRL-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6WALBMRL-6S HERTFORD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 238_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.95 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:769.48
MW Contribution:1.55
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6WALBMRL-6S HERTFORD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 238_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.0 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:799.15
MW Contribution:1.57
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940492AE2-034 E
50/50
9.2879.287
934522AD1-076 E
50/50
14.72614.726
943172AE2-346 E
50/50
0.4540.454
918492AA1-063AE OP
Adder
1.88588235294117661.603
962571AG1-106 C
50/50
1.6841.684
917332KELFORD E
50/50
1.2411.241
925122AB2-169 E
50/50
9.6079.607
932631AC2-084 C
50/50
0.6290.629
316274AC1-208 C
Adder
5.202352941176474.422
917342Z2-044 E
Adder
0.33176470588235290.282
3151311EDGECMA
Adder
8.677647058823537.376
3156116Z1-036WIND
50/50
2.5432.543
316140AB2-099 C
50/50
0.0720.072
938531AE1-072 C
Adder
-8.872941176470588-7.542
315614AA2-178 C
50/50
4.7214.721
933981AD1-022 C
50/50
17.46517.465
900672V4-068 E
Adder
0.18470588235294120.157
3151411GASTONB
50/50
1.8921.892
3145946PLYMOUTH TP
50/50
0.7970.797
933982AD1-022 E
50/50
9.5089.508
927146AC1-208 E
Adder
2.31058823529411761.964
962572AG1-106 E
50/50
0.7370.737
932632AC2-084 E
50/50
2.0212.021
926214AC1-099 E
50/50
0.7550.755
934521AD1-076 C
50/50
28.89228.892
934511AD1-075 C
50/50
19.88819.888
3145723EMPORIA
Adder
0.215294117647058830.183
923573AB1-173 E OP
Adder
1.6635294117647061.414
316011AB1-132 C OP
50/50
1.4451.445
919692AA2-053 E OP
Adder
2.4188235294117652.056
316263AC1-034 C
Adder
3.60470588235294143.064
316365AB2-100 C1
50/50
0.5490.549
926206AC1-098 E
50/50
2.2862.286
316210AC1-098 C
50/50
0.5910.591
961941AG1-037 C
50/50
0.3780.378
961942AG1-037 E
50/50
0.2520.252
943171AE2-346 C
50/50
0.1680.168
3151381ROSEMG2
50/50
0.5850.585
934332AD1-057 E
Adder
1.05764705882352940.899
934321AD1-056 C
Adder
3.64117647058823573.095
934322AD1-056 E
Adder
1.97529411764705891.679
934331AD1-057 C
Adder
2.0305882352941181.726
927022AC1-189 E
50/50
3.3063.306
925595AC1-034 E
Adder
2.71999999999999982.312
3152921DOMTR78
50/50
2.7962.796
3137643SOCKMAN
Adder
0.36588235294117650.311
316212AC1-099 C
50/50
0.1980.198
919710AA2-057 E
Adder
2.24941176470588241.912
940491AE2-034 C
50/50
3.4743.474
924517AB2-100 E2
50/50
1.6551.655
934501AD1-074 C
50/50
79.55379.553
3156021HOLLOMANSOL
50/50
1.7431.743
3151371ROSEMS1
50/50
0.7740.774
961671AG1-007 C
50/50
0.6460.646
924516AB2-100 E1
50/50
1.6551.655
934512AD1-075 E
50/50
10.12410.124
934502AD1-074 E
50/50
40.49740.497
966621AG1-532 C
Adder
0.69764705882352940.593
918512AA1-065 E OP
50/50
5.2385.238
918532AA1-067 E
50/50
0.6460.646
316088AB2-174 E
Adder
3.28588235294117672.793
316141AB2-099 E
50/50
0.1890.189
923994AB2-040_E
Adder
3.11882352941176462.651
3151361ROSEMG1
50/50
1.251.25
316005AA1-067 C
50/50
0.2460.246
961672AG1-007 E
50/50
0.3660.366
946282AF1-292 E
Adder
0.51294117647058820.436
957861AF2-080 C
50/50
6.0276.027
917512Z2-088 E OP1
50/50
3.5873.587
960081AF2-299 C
Adder
0.92941176470588240.79
3151391GASTONA
50/50
1.8921.892
926072AC1-086 E
50/50
5.9275.927
957862AF2-080 E
50/50
2.6722.672
916042Z1-036 E
50/50
110.543110.543
316023AB2-100 C2
50/50
0.5490.549
960082AF2-299 E
Adder
0.620.527
946281AF1-292 C
Adder
0.76941176470588240.654
926071AC1-086 C
50/50
13.02213.022
316317KELFORD C
50/50
0.270.27
927021AC1-189 C
50/50
6.6366.636
924152AB2-059 E OP
Adder
2.86705882352941142.437
920692AA2-178 E
50/50
12.38212.382
966622AG1-532 E
Adder
0.46470588235294120.395
922923AB1-081 E OP
Adder
2.0235294117647061.72
940481AE2-033 C
Adder
8.8694117647058827.539
940482AE2-033 E
Adder
5.985.083
923263AB1-132 E OP
50/50
3.793.79
316174AB2-169_C
50/50
1.751.75
3156011CONETOE2SOL
50/50
0.9170.917
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3961.396
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.25321.253
CPLELTFEXP_CPLE->PJM
CLTF
2.9282.928
TVALTFEXP_TVA->PJM
CLTF
1.241.24
O66PJM->LTFIMP_O-066
CMTX_NF
2.4252.425
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3810.381
SIGELTFEXP_SIGE->PJM
CLTF
0.0520.052
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.9766.976
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.6744.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.8410.841
LAGNLTFEXP_LAGN->PJM
CLTF
1.5921.592
NYPJM->LTFIMP_NY
CLTF
0.1720.172
LGEELTFEXP_LGEE->PJM
CLTF
0.2640.264
WECLTFEXP_WEC->PJM
CLTF
0.1420.142

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.12 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3352.99
MW Contribution:3.62
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3492.91
MW Contribution:3.48
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
933292AC2-141 E
50/50
14.89414.894
316294AC1-161 C
50/50
5.7015.701
934576AD1-082 E
Adder
4.1988235294117653.569
916191Z1-068 C
50/50
0.0490.049
944602AF1-125 E
50/50
115.795115.795
3145506HICKORY
50/50
2.4672.467
957871AF2-081 C
50/50
11.29311.293
943612AF1-032 E
Adder
1.02823529411764710.874
940492AE2-034 E
Adder
3.4764705882352942.955
934522AD1-076 E
Adder
7.045.984
943172AE2-346 E
Adder
0.68588235294117650.583
918492AA1-063AE OP
Adder
4.65058823529411753.953
316084AB2-161 E
Adder
5.26941176470588254.479
940641AE2-051 C
50/50
26.11526.115
3145946PLYMOUTH TP
Adder
0.364705882352941160.31
933982AD1-022 E
Adder
5.3847058823529414.577
934622AD1-088 E
50/50
5.5555.555
934611AD1-087 C
50/50
1.5661.566
934612AD1-087 E
50/50
4.5174.517
927146AC1-208 E
Adder
4.5541176470588243.871
927255AC1-221 E
Adder
4.1411764705882363.52
926755AC1-161 E
50/50
14.89414.894
933291AC2-141 C
50/50
34.8934.89
925522AC1-027 E
50/50
1.3621.362
3145256KINGFORK
Adder
1.06588235294117650.906
957872AF2-081 E
50/50
4.844.84
941102AE2-104 E
Adder
5.8305882352941184.956
316087AB2-174 C
50/50
1.3621.362
962572AG1-106 E
Adder
1.36588235294117651.161
964242AG1-285 E
50/50
9.9189.918
924162AB2-060 E OP
Adder
4.8364705882352944.111
932632AC2-084 E
Adder
3.66588235294117663.116
926214AC1-099 E
Adder
1.36941176470588231.164
964792AG1-342 E
Adder
2.6435294117647062.247
932763AC2-100 E
Adder
2.80941176470588252.388
942342AE2-247 E
Adder
2.141.819
316018AA1-139 ULT2
50/50
1.2231.223
919152AA1-139 E1
50/50
4.6184.618
920042AA2-088 E OP
Adder
11.94941176470588210.157
934521AD1-076 C
Adder
13.81176470588235411.74
934511AD1-075 C
Adder
9.507058823529418.081
3145723EMPORIA
50/50
0.50.5
923573AB1-173 E OP
Adder
3.78941176470588253.221
919692AA2-053 E OP
Adder
4.8352941176470594.11
959311AF2-222 C
Adder
17.79058823529411615.122
925785AC1-054 E
Adder
3.94000000000000043.349
316263AC1-034 C
Adder
7.4894117647058826.366
962571AG1-106 C
Adder
3.1235294117647062.655
937482AD2-202 E
50/50
1.3221.322
917332KELFORD E
Adder
1.8635294117647061.584
961792AG1-021 E
Adder
1.38941176470588231.181
925122AB2-169 E
Adder
6.4858823529411775.513
316274AC1-208 C
Adder
10.255294117647068.717
917342Z2-044 E
Adder
0.6764705882352940.575
3151311EDGECMA
Adder
17.50705882352941214.881
3143316POE
Adder
1.30823529411764721.112
939191AE1-149 C
Adder
9.5941176470588238.155
901082W1-029 E
Adder
35.7705882352941230.405
3151021BRUNSWICKG1
50/50
12.28212.282
3151041BRUNSWICKG3
50/50
12.28212.282
316365AB2-100 C1
50/50
1.1231.123
935171AD1-152 C
50/50
1.6091.609
926206AC1-098 E
Adder
4.1470588235294123.525
964791AG1-342 C
Adder
3.96470588235294133.37
926662AC1-147 E
Adder
1.46588235294117641.246
916192Z1-068 E
50/50
2.1052.105
939412AE1-173 E
50/50
85.77785.777
957492AF2-043 E
Adder
1.58117647058823541.344
941032AE2-094 E
50/50
27.25927.259
941031AE2-094 C
50/50
60.86460.864
923852AB2-025 E
50/50
1.3891.389
3151051BRUNSWICKS1
50/50
25.51625.516
961941AG1-037 C
Adder
0.5717647058823530.486
961942AG1-037 E
Adder
0.381176470588235340.324
958211AF2-115 C
Adder
2.03764705882352941.732
936262AD2-033 E
Adder
9.0082352941176477.657
934332AD1-057 E
Adder
2.0682352941176471.758
934321AD1-056 C
Adder
7.126.052
934322AD1-056 E
Adder
3.86117647058823543.282
934331AD1-057 C
Adder
3.9717647058823533.376
927022AC1-189 E
Adder
4.7282352941176474.019
925595AC1-034 E
Adder
5.65058823529411754.803
939411AE1-173 C
50/50
128.665128.665
913392Y1-086 E
50/50
2.4762.476
3151031BRUNSWICKG2
50/50
12.28212.282
3137643SOCKMAN
Adder
0.81882352941176460.696
937481AD2-202 C
50/50
0.4540.454
919710AA2-057 E
Adder
4.49411764705882363.82
939192AE1-149 E
Adder
6.3964705882352955.437
939312AE1-162 E
Adder
1.37058823529411771.165
934065AD1-033 E
50/50
5.6715.671
937226AE2-253 E
50/50
6.6066.606
316321Z2-027 C
50/50
0.410.41
924517AB2-100 E2
50/50
3.3843.384
934501AD1-074 C
Adder
38.0305882352941232.326
957482AF2-042 E
50/50
46.62746.627
934621AD1-088 C
50/50
11.53711.537
946301AF1-294 C
Adder
3.3517647058823532.849
935172AD1-152 E
50/50
6.6176.617
961671AG1-007 C
Adder
1.05882352941176470.9
940642AE2-051 E
50/50
17.4117.41
316388AE2-253 GEN
50/50
2.2212.221
942341AE2-247 C
Adder
1.54941176470588231.317
943462AF1-017 E
Adder
2.2870588235294121.944
919153AA1-139 E2
50/50
4.6184.618
958162AF2-110 E
Adder
2.38000000000000032.023
924516AB2-100 E1
50/50
3.3843.384
934512AD1-075 E
Adder
4.844.114
934502AD1-074 E
Adder
19.3616.456
966621AG1-532 C
50/50
1.6281.628
918512AA1-065 E OP
Adder
6.2505882352941175.313
3147223TWITTYS
Adder
1.03411764705882360.879
959312AF2-222 E
Adder
11.9210.132
924022AB2-043 E O1
Adder
5.9035294117647065.018
918532AA1-067 E
Adder
0.80588235294117660.685
316185AD1-033 C
50/50
1.391.39
944581AF1-123 C
50/50
51.37451.374
941101AE2-104 C
Adder
3.66705882352941173.117
316320Y1-086 C
50/50
0.2480.248
957481AF2-042 C
50/50
69.9469.94
316088AB2-174 E
50/50
7.5427.542
316141AB2-099 E
Adder
0.28588235294117650.243
923994AB2-040_E
Adder
7.1047058823529416.039
946302AF1-294 E
Adder
2.83882352941176472.413
924322AB2-079 E O1
Adder
1.52117647058823541.293
943902AF1-058 E
Adder
1.42941176470588241.215
961672AG1-007 E
Adder
0.60.51
3151101ELIZAR3
50/50
3.6013.601
944012AF1-069 E
50/50
7.7257.725
316315AB2-025 C
50/50
0.4880.488
946282AF1-292 E
50/50
1.1981.198
3151541CLOVER2
50/50
15.75715.757
3138533PONTONDP
Adder
0.60352941176470590.513
957861AF2-080 C
Adder
8.6200000000000017.327
917512Z2-088 E OP1
Adder
5.5247058823529414.696
941591AE2-156 C
50/50
19.83519.835
3151081ELIZAR1
50/50
3.5563.556
3151091ELIZAR2
50/50
3.4953.495
316316AC1-027 C
50/50
0.3530.353
944601AF1-125 C
50/50
50.58350.583
944591AF1-124 C
50/50
51.55751.557
936666AD2-085 E
Adder
5.8329411764705884.958
944011AF1-069 C
50/50
19.88619.886
938771AE1-103 C
Adder
3.24823529411764732.761
3145413WATKINS
Adder
0.7717647058823530.656
963041AG1-153 C
50/50
8.3218.321
960081AF2-299 C
50/50
2.1712.171
926072AC1-086 E
Adder
10.9894117647058819.341
961791AG1-021 C
Adder
1.63058823529411771.386
936261AD2-033 C
Adder
13.51176470588235311.485
962562AG1-105 E
Adder
6.6470588235294125.65
957862AF2-080 E
Adder
3.8211764705882363.248
944582AF1-123 E
50/50
117.641117.641
944592AF1-124 E
50/50
118.067118.067
935112AD1-144 E
Adder
0.98941176470588230.841
316349AD2-085 C
Adder
3.5752941176470593.039
923832AB2-022 E
50/50
1.3981.398
938772AE1-103 E
Adder
4.4858823529411773.813
916042Z1-036 E
Adder
32.1705882352941227.345
963042AG1-153 E
50/50
12.48112.481
316023AB2-100 C2
50/50
1.1231.123
960082AF2-299 E
50/50
1.4471.447
946281AF1-292 C
50/50
1.7971.797
926071AC1-086 C
Adder
24.1447058823529420.523
3151531CLOVER1
50/50
15.90515.905
964241AG1-285 C
50/50
14.87614.876
958212AF2-115 E
Adder
1.73647058823529421.476
962561AG1-105 C
Adder
9.9705882352941188.475
927021AC1-189 C
Adder
9.4905882352941178.067
924152AB2-059 E OP
Adder
5.9564705882352945.063
943461AF1-017 C
Adder
1.40235294117647061.192
932596AC2-079 E
Adder
9.7835294117647078.316
316311AC2-079 C
Adder
5.9964705882352955.097
938532AE1-072 E
50/50
10.34610.346
3146326AYDLETT TAP
50/50
1.5311.531
917122Z2-027 E
50/50
1.5121.512
920692AA2-178 E
Adder
4.6352941176470593.94
966622AG1-532 E
50/50
1.0851.085
3147133PAMPLIN
Adder
0.89882352941176480.764
927264AC1-222 E
Adder
4.3282352941176473.679
922923AB1-081 E OP
Adder
4.20470588235294153.574
932046AC2-012 E
50/50
14.50114.501
316017AA1-139 ULT1
50/50
1.2231.223
938531AE1-072 C
50/50
19.84719.847
958161AF2-110 C
Adder
1.49647058823529421.272
3145393UNCAMP
Adder
6.7635294117647065.749
3152411Z1-086 GT1
50/50
15.81615.816
933981AD1-022 C
Adder
9.8917647058823528.408
900672V4-068 E
Adder
0.402352941176470640.342
924302AB2-077 E O1
Adder
1.52117647058823541.293
961611AG1-000B C
Adder
5.824.947
316375AC2-012 C
50/50
1.4951.495
313526AB2-022 C
50/50
0.4240.424
940541AE2-040 C
50/50
3.4343.434
940481AE2-033 C
50/50
19.30519.305
940482AE2-033 E
50/50
13.01513.015
3152441Z1-086 ST
50/50
27.53327.533
3152431Z1-086 GT3
50/50
15.81115.811
3152421Z1-086 GT2
50/50
15.81115.811
923263AB1-132 E OP
Adder
7.0270588235294125.973
925612AC1-036 E
Adder
0.93294117647058830.793
924312AB2-078 E O1
Adder
1.52117647058823541.293
926274AC1-105 E
Adder
2.9882352941176472.54
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.3016.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
107.493107.493
CPLELTFEXP_CPLE->PJM
CLTF
13.22113.221
TVALTFEXP_TVA->PJM
CLTF
6.2796.279
O66PJM->LTFIMP_O-066
CMTX_NF
22.61622.616
G-007PJM->LTFIMP_G-007
CMTX_NF
3.5513.551
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.47229.472
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.8122.81
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.8563.856
LAGNLTFEXP_LAGN->PJM
CLTF
8.048.04
NYPJM->LTFIMP_NY
CLTF
1.6611.661
LGEELTFEXP_LGEE->PJM
CLTF
1.1651.165
WECLTFEXP_WEC->PJM
CLTF
0.6140.614

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:136.21 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3326.4
MW Contribution:3.84
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:145.97 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3564.84
MW Contribution:3.83
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316076AC2-137 E
Adder
1.64117647058823551.395
923842AB2-024 E
Adder
2.7035294117647062.298
964211AG1-282 C
Adder
2.76588235294117672.351
316157AD2-030 E
Adder
1.7917647058823531.523
926662AC1-147 E
50/50
2.2972.297
916192Z1-068 E
50/50
3.2743.274
939412AE1-173 E
50/50
91.51291.512
957492AF2-043 E
50/50
2.4072.407
941032AE2-094 E
Adder
23.3529411764705919.85
941031AE2-094 C
Adder
52.14117647058823544.32
923852AB2-025 E
Adder
1.42470588235294131.211
961941AG1-037 C
Adder
0.71294117647058820.606
961942AG1-037 E
Adder
0.475294117647058870.404
939246AE1-155 E
Adder
12.06941176470588310.259
924814AB2-134 E
Adder
17.2517647058823514.664
316036AC1-147 C
50/50
0.6390.639
942342AE2-247 E
Adder
3.142.669
316018AA1-139 ULT2
50/50
1.8731.873
919152AA1-139 E1
50/50
7.0757.075
920042AA2-088 E OP
Adder
15.25058823529411712.963
934521AD1-076 C
Adder
18.52705882352941215.748
934511AD1-075 C
Adder
12.75411764705882310.841
3145723EMPORIA
Adder
0.53411764705882360.454
923573AB1-173 E OP
Adder
4.1152941176470593.498
919692AA2-053 E OP
Adder
5.50588235294117644.68
944631AF1-128 C
Adder
26.26705882352941422.327
936592AD2-074 E
Adder
12.85529411764705910.927
316160AE1-175 E
50/50
2.0532.053
3150921YORKTN3
50/50
212.818212.818
3151161SURRY 1
50/50
37.92137.921
926755AC1-161 E
50/50
24.37824.378
933291AC2-141 C
50/50
57.10857.108
925522AC1-027 E
50/50
2.1192.119
3145256KINGFORK
50/50
1.7041.704
957872AF2-081 E
50/50
7.4157.415
316305AF2-043 C
50/50
0.590.59
941102AE2-104 E
50/50
8.7058.705
962572AG1-106 E
Adder
1.5164705882352941.289
932632AC2-084 E
Adder
4.183.553
926214AC1-099 E
Adder
1.56235294117647071.328
3130536PAPERMILL
Adder
9.9929411764705888.494
939602AE1-190 E
Adder
2.1164705882352941.799
936591AD2-074 C
Adder
7.8788235294117656.697
933292AC2-141 E
50/50
24.37824.378
316294AC1-161 C
50/50
9.3329.332
934576AD1-082 E
Adder
5.9741176470588245.078
916191Z1-068 C
50/50
0.0760.076
944602AF1-125 E
50/50
179.158179.158
3145506HICKORY
50/50
3.8083.808
957871AF2-081 C
50/50
17.30217.302
943612AF1-032 E
50/50
1.5651.565
940492AE2-034 E
Adder
4.8058823529411764.085
934522AD1-076 E
Adder
9.4435294117647068.027
943172AE2-346 E
Adder
0.85647058823529410.728
918492AA1-063AE OP
Adder
5.464705882352944.645
962571AG1-106 C
Adder
3.4647058823529412.945
917332KELFORD E
Adder
2.25294117647058821.915
925122AB2-169 E
Adder
8.1847058823529426.957
963612AG1-210 E
Adder
1.35529411764705881.152
316382AG1-145 C
50/50
0.610.61
940642AE2-051 E
50/50
16.6416.64
3150601CHESTF5
Adder
72.936470588235361.996
964212AG1-282 E
Adder
1.84352941176470591.567
962962AG1-145 E
50/50
2.4882.488
925332AB2-190 E
Adder
10.335294117647068.785
927226AC1-216 E
Adder
10.5317647058823528.952
941591AE2-156 C
50/50
31.07431.074
3151081ELIZAR1
50/50
5.5655.565
3151091ELIZAR2
50/50
5.4685.468
316316AC1-027 C
50/50
0.550.55
944601AF1-125 C
50/50
78.26278.262
944591AF1-124 C
50/50
79.76979.769
936666AD2-085 E
Adder
8.5588235294117647.275
944011AF1-069 C
Adder
17.03647058823529314.481
938771AE1-103 C
Adder
4.5305882352941173.851
3145413WATKINS
Adder
1.03764705882352940.882
963041AG1-153 C
Adder
7.1717647058823536.096
960081AF2-299 C
Adder
2.3023529411764711.957
926072AC1-086 E
Adder
12.19176470588235310.363
316169AC1-164 GEN
50/50
61.5761.57
3144216WINCHST
50/50
0.2310.231
944582AF1-123 E
50/50
182.015182.015
944592AF1-124 E
50/50
182.674182.674
935112AD1-144 E
50/50
1.5821.582
316349AD2-085 C
Adder
5.2458823529411764.459
923832AB2-022 E
50/50
2.1082.108
938772AE1-103 E
Adder
6.257647058823535.319
916042Z1-036 E
50/50
46.21946.219
963042AG1-153 E
Adder
10.757647058823539.144
960082AF2-299 E
Adder
1.53529411764705871.305
946281AF1-292 C
Adder
1.90588235294117661.62
926071AC1-086 C
Adder
26.78823529411764822.77
316078AC2-138 E
Adder
1.26470588235294111.075
958262AF2-120 E
Adder
5.7788235294117654.912
966661AG1-536 C
Adder
7.4564705882352956.338
939612AE1-191 E
Adder
8.4670588235294127.197
957602AF2-054 E
Adder
2.12823529411764721.809
934012AD1-025 E
Adder
13.63529411764705811.59
939411AE1-173 C
50/50
137.269137.269
913392Y1-086 E
50/50
3.7343.734
3156116Z1-036WIND
50/50
1.0631.063
3137643SOCKMAN
Adder
0.90352941176470590.768
935161AD1-151 C
Adder
21.28588235294117618.093
932046AC2-012 E
50/50
22.72422.724
316017AA1-139 ULT1
50/50
1.8731.873
938531AE1-072 C
50/50
30.31830.318
958161AF2-110 C
50/50
2.2342.234
3145393UNCAMP
Adder
9.2964705882352947.902
933981AD1-022 C
Adder
13.0952941176470611.131
900672V4-068 E
Adder
0.50705882352941180.431
3138116ELKO L286
Adder
1.71058823529411771.454
963611AG1-210 C
Adder
0.90352941176470590.768
957831AF2-077 C
50/50
0.5460.546
961611AG1-000B C
Adder
23.74470588235294220.183
316236AE1-162 C
50/50
0.5660.566
316375AC2-012 C
50/50
2.3432.343
313526AB2-022 C
50/50
0.640.64
940541AE2-040 C
Adder
3.5223529411764712.994
940481AE2-033 C
Adder
19.89882352941176816.914
940482AE2-033 E
Adder
13.4152941176470611.403
923263AB1-132 E OP
Adder
7.79647058823529456.627
316388AE2-253 GEN
50/50
3.4133.413
942341AE2-247 C
Adder
2.2741176470588241.933
943462AF1-017 E
Adder
3.35647058823529452.853
919153AA1-139 E2
50/50
7.0757.075
316246AF1-032 C
50/50
0.4820.482
958162AF2-110 E
50/50
3.5543.554
924516AB2-100 E1
Adder
3.61411764705882373.072
934512AD1-075 E
Adder
6.4917647058823525.518
934502AD1-074 E
Adder
25.96941176470588522.074
966621AG1-532 C
Adder
1.72705882352941181.468
918512AA1-065 E OP
Adder
7.9635294117647066.769
918532AA1-067 E
Adder
0.94588235294117650.804
926785AC1-164_E
50/50
27.66227.662
943471AF1-018 C
Adder
10.7682352941176489.153
316084AB2-161 E
Adder
7.497647058823536.373
316072AD1-144 C
50/50
0.4730.473
940641AE2-051 C
50/50
24.9624.96
3145946PLYMOUTH TP
Adder
0.491764705882352940.418
933982AD1-022 E
Adder
7.1294117647058826.06
3141813NORNECK
Adder
1.20352941176470571.023
962861AG1-135 C
Adder
8.4564705882352957.188
943741AF1-042 C
Adder
4.122352941176473.504
939192AE1-149 E
Adder
8.8705882352941187.54
939312AE1-162 E
50/50
2.3092.309
3150991CHESPKB
50/50
1.2531.253
934065AD1-033 E
50/50
8.788.78
937226AE2-253 E
50/50
10.1510.15
316321Z2-027 C
50/50
0.6140.614
924517AB2-100 E2
Adder
3.61411764705882373.072
934501AD1-074 C
Adder
51.01411764705882543.362
934392AD1-063 E
Adder
1.61529411764705881.373
966662AG1-536 E
Adder
10.0188235294117658.516
962862AG1-135 E
Adder
5.63764705882352954.792
943742AF1-042 E
Adder
6.7258823529411765.717
3150981CHESPKA
50/50
0.7560.756
316185AD1-033 C
50/50
2.1522.152
944581AF1-123 C
50/50
79.48679.486
941101AE2-104 C
50/50
5.4755.475
316320Y1-086 C
50/50
0.3740.374
316088AB2-174 E
Adder
8.1305882352941186.911
316141AB2-099 E
Adder
0.35647058823529410.303
923994AB2-040_E
Adder
7.7152941176470586.558
958261AF2-120 C
Adder
8.6682352941176477.368
934146AD1-041 E
Adder
5.2917647058823534.498
957601AF2-054 C
Adder
3.1929411764705882.714
316159AE1-175 C
50/50
0.6760.676
939191AE1-149 C
Adder
13.30705882352941111.311
901082W1-029 E
50/50
53.16253.162
926206AC1-098 E
Adder
4.72941176470588154.02
940551AE2-041 C
Adder
10.7682352941176489.153
957832AF2-077 E
50/50
2.3562.356
935162AD1-151 E
Adder
14.19058823529411712.062
3152331SURRY 2
50/50
50.93450.934
943461AF1-017 C
Adder
2.05764705882352941.749
932596AC2-079 E
Adder
14.39058823529411812.232
316311AC2-079 C
Adder
8.827.497
938532AE1-072 E
50/50
15.80515.805
3146326AYDLETT TAP
50/50
2.3362.336
917122Z2-027 E
50/50
2.2672.267
3156056W1-029WIND
50/50
1.2961.296
920692AA2-178 E
Adder
6.4070588235294125.446
966622AG1-532 E
Adder
1.1517647058823530.979
925865AC1-065 E
Adder
24.48470588235294420.812
961952AG1-038 E
Adder
6.2929411764705885.349
961951AG1-038 C
Adder
4.5564705882352943.873
3151101ELIZAR3
50/50
5.6365.636
944012AF1-069 E
Adder
6.6188235294117655.626
946282AF1-292 E
Adder
1.27058823529411781.08
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.8765.876
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69696.696
CPLELTFEXP_CPLE->PJM
CLTF
12.33712.337
TVALTFEXP_TVA->PJM
CLTF
4.9324.932
O66PJM->LTFIMP_O-066
CMTX_NF
21.46821.468
G-007PJM->LTFIMP_G-007
CMTX_NF
3.3653.365
SIGELTFEXP_SIGE->PJM
CLTF
0.1430.143
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.55415.554
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.85316.853
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.4842.484
LAGNLTFEXP_LAGN->PJM
CLTF
6.3726.372
NYPJM->LTFIMP_NY
CLTF
1.6271.627
LGEELTFEXP_LGEE->PJM
CLTF
0.6520.652
WECLTFEXP_WEC->PJM
CLTF
0.3380.338

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.81 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4713.59
MW Contribution:4.46
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:137.17 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5582.91
MW Contribution:4.83
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966871AG1-558 C
Adder
3.73647058823529443.176
966872AG1-558 E
Adder
1.88235294117647081.6
3150841SPRUNCB
Adder
14.5823529411764712.395
3150831SPRUNCA
Adder
14.5823529411764712.395
316076AC2-137 E
50/50
2.32.3
3150641CHESTS8
50/50
3.3243.324
939246AE1-155 E
Adder
13.111.135
944641AF1-129 C
Adder
166.98352941176472141.936
316240AF1-291 C
Adder
3.5117647058823532.985
924814AB2-134 E
Adder
21.28941176470588218.096
942342AE2-247 E
Adder
3.39176470588235322.883
919152AA1-139 E1
Adder
6.8435294117647065.817
920042AA2-088 E OP
Adder
16.25647058823529513.818
934521AD1-076 C
Adder
19.0647058823529416.205
934511AD1-075 C
Adder
13.12352941176470511.155
3145723EMPORIA
Adder
0.61764705882352940.525
923573AB1-173 E OP
Adder
4.7082352941176474.002
316312AB1-027 C
50/50
0.8920.892
938552AE1-074 E
Adder
1.90000000000000011.615
944631AF1-128 C
50/50
67.28467.284
936592AD2-074 E
Adder
13.95176470588235211.859
316160AE1-175 E
50/50
2.0922.092
3150921YORKTN3
50/50
208.205208.205
926755AC1-161 E
50/50
22.27722.277
933291AC2-141 C
50/50
52.18752.187
925522AC1-027 E
Adder
2.05294117647058851.745
3145256KINGFORK
Adder
1.70470588235294131.449
957872AF2-081 E
Adder
7.1717647058823536.096
941102AE2-104 E
Adder
8.815294117647067.493
3130536PAPERMILL
Adder
11.0400000000000019.384
939602AE1-190 E
Adder
2.33764705882352961.987
936591AD2-074 C
Adder
8.5505882352941187.268
3150651CHESTF6
Adder
30.4035294117647125.843
946262AF1-291 E
Adder
2.34117647058823541.99
933292AC2-141 E
50/50
22.27722.277
316294AC1-161 C
50/50
8.5288.528
934576AD1-082 E
Adder
7.1941176470588246.115
944602AF1-125 E
Adder
172.25764705882355146.419
3145506HICKORY
Adder
3.66705882352941173.117
957871AF2-081 C
Adder
16.73529411764705814.225
943612AF1-032 E
Adder
1.54117647058823541.31
940492AE2-034 E
Adder
4.8823529411764714.15
934522AD1-076 E
Adder
9.7164705882352948.259
943172AE2-346 E
Adder
0.91294117647058830.776
918492AA1-063AE OP
Adder
6.0129411764705885.111
917332KELFORD E
Adder
2.43058823529411772.066
925122AB2-169 E
Adder
8.6200000000000017.327
923842AB2-024 E
Adder
2.99058823529411732.542
964211AG1-282 C
Adder
3.02000000000000052.567
316157AD2-030 E
Adder
1.94470588235294131.653
926662AC1-147 E
Adder
2.2364705882352941.901
916192Z1-068 E
Adder
3.16941176470588242.694
939412AE1-173 E
Adder
91.772941176470678.007
957492AF2-043 E
Adder
2.37058823529411772.015
941032AE2-094 E
Adder
24.70588235294117821
941031AE2-094 C
Adder
55.1635294117647146.889
923852AB2-025 E
Adder
1.7117647058823531.455
961941AG1-037 C
Adder
0.76117647058823530.647
961942AG1-037 E
Adder
0.50705882352941180.431
3150611CHESTG7
50/50
6.5626.562
3150601CHESTF5
50/50
107.532107.532
964212AG1-282 E
Adder
2.01294117647058851.711
962962AG1-145 E
50/50
2.5352.535
925332AB2-190 E
Adder
13.54588235294117611.514
927226AC1-216 E
Adder
12.9976470588235311.048
941591AE2-156 C
Adder
30.2317647058823525.697
944601AF1-125 C
Adder
75.2470588235294163.96
944591AF1-124 C
Adder
76.6964705882352965.192
936666AD2-085 E
Adder
9.244705882352947.858
944011AF1-069 C
Adder
18.02352941176470615.32
938771AE1-103 C
Adder
4.6882352941176473.985
3145413WATKINS
Adder
1.08705882352941190.924
963041AG1-153 C
Adder
7.67882352941176556.527
960081AF2-299 C
Adder
2.6764705882352942.275
930122AB1-027 E
50/50
2.342.34
316169AC1-164 GEN
50/50
71.02671.026
3150631CHESTG8
50/50
6.4576.457
3144216WINCHST
50/50
0.2290.229
944582AF1-123 E
Adder
175.0035294117647148.753
944592AF1-124 E
Adder
175.63764705882355149.292
935112AD1-144 E
Adder
1.58235294117647051.345
316349AD2-085 C
Adder
5.6658823529411774.816
923832AB2-022 E
Adder
2.0588235294117651.75
938772AE1-103 E
Adder
6.4741176470588245.503
916042Z1-036 E
Adder
46.2035294117647139.273
963042AG1-153 E
Adder
11.517647058823539.79
960082AF2-299 E
Adder
1.78470588235294111.517
946281AF1-292 C
Adder
2.2152941176470591.883
926071AC1-086 C
Adder
8.492941176470597.219
316078AC2-138 E
Adder
1.37294117647058831.167
958262AF2-120 E
Adder
6.2717647058823545.331
966661AG1-536 C
Adder
8.0929411764705876.879
939612AE1-191 E
Adder
9.3494117647058837.947
957602AF2-054 E
Adder
2.31058823529411761.964
940432AE2-027 E
Adder
14.03647058823529311.931
934012AD1-025 E
Adder
16.82705882352941314.303
939411AE1-173 C
Adder
137.65882352941176117.01
913392Y1-086 E
Adder
3.6470588235294123.1
3150701DARBY 4
50/50
4.2774.277
3150731STONECA
Adder
11.5258823529411789.797
935161AD1-151 C
Adder
27.11411764705882623.047
932046AC2-012 E
Adder
22.12352941176470718.805
938531AE1-072 C
Adder
29.3776470588235324.971
958161AF2-110 C
Adder
2.2623529411764711.923
3145393UNCAMP
Adder
9.664705882352948.215
933981AD1-022 C
Adder
13.55882352941176611.525
900672V4-068 E
Adder
0.54235294117647060.461
927041AC1-191 C
Adder
15.00352941176470612.753
3138116ELKO L286
50/50
2.3992.399
963611AG1-210 C
Adder
0.980.833
961611AG1-000B C
Adder
26.9129411764705922.876
940541AE2-040 C
Adder
4.2317647058823533.597
940481AE2-033 C
Adder
23.8117647058823520.24
940482AE2-033 E
Adder
16.0529411764705913.645
926412AC1-112 E
50/50
1.9031.903
3150681DARBY 2
50/50
4.2574.257
963612AG1-210 E
Adder
1.47058823529411781.25
316382AG1-145 C
50/50
0.6220.622
940642AE2-051 E
Adder
16.92588235294117614.387
942341AE2-247 C
Adder
2.4552941176470592.087
943462AF1-017 E
Adder
3.62470588235294143.081
919153AA1-139 E2
Adder
6.8435294117647065.817
958162AF2-110 E
Adder
3.5988235294117653.059
924516AB2-100 E1
Adder
4.20352941176470553.573
934512AD1-075 E
Adder
6.685.678
934502AD1-074 E
Adder
26.72117647058823722.713
966621AG1-532 C
Adder
2.00705882352941161.706
918512AA1-065 E OP
Adder
8.397647058823537.138
926785AC1-164_E
50/50
31.9131.91
943471AF1-018 C
Adder
11.82823529411764710.054
316084AB2-161 E
Adder
9.0294117647058827.675
940641AE2-051 C
Adder
25.38941176470588321.581
3145946PLYMOUTH TP
Adder
0.50470588235294120.429
933982AD1-022 E
Adder
7.3811764705882366.274
316004AC1-112 C
50/50
0.5560.556
3141813NORNECK
Adder
1.30588235294117671.11
962861AG1-135 C
Adder
9.177647058823537.801
943741AF1-042 C
Adder
4.4741176470588243.803
942001AE2-212 C
Adder
3.4764705882352942.955
939192AE1-149 E
Adder
11.6211764705882359.878
939312AE1-162 E
Adder
2.4211764705882352.058
934065AD1-033 E
Adder
8.4505882352941187.183
937226AE2-253 E
Adder
9.88.33
924517AB2-100 E2
Adder
4.20352941176470553.573
934501AD1-074 C
Adder
52.4929411764705944.619
934392AD1-063 E
Adder
1.77411764705882361.508
966662AG1-536 E
Adder
10.8741176470588249.243
962862AG1-135 E
Adder
6.1188235294117645.201
943742AF1-042 E
Adder
7.3000000000000016.205
940431AE2-027 C
Adder
21.05411764705882417.896
942002AE2-212 E
Adder
2.31764705882352961.97
944581AF1-123 C
Adder
76.4247058823529464.961
941101AE2-104 C
Adder
5.5447058823529414.713
316088AB2-174 E
Adder
9.3494117647058837.947
316141AB2-099 E
Adder
0.380.323
923994AB2-040_E
Adder
8.8282352941176477.504
958261AF2-120 C
Adder
9.4070588235294137.996
934146AD1-041 E
Adder
5.8435294117647054.967
957601AF2-054 C
Adder
3.4647058823529412.945
316159AE1-175 C
50/50
0.6890.689
3143316POE
Adder
2.15411764705882371.831
939191AE1-149 C
Adder
17.43176470588235514.817
901082W1-029 E
Adder
52.4682352941176544.598
927042AC1-191 E
Adder
7.4741176470588236.353
316233AE1-074 C
Adder
3.7705882352941183.205
3150691DARBY 3
50/50
4.2724.272
940551AE2-041 C
Adder
11.82823529411764710.054
957832AF2-077 E
Adder
2.41411764705882352.052
935162AD1-151 E
Adder
18.0752941176470615.364
3152331SURRY 2
50/50
44.51344.513
943461AF1-017 C
Adder
2.2223529411764711.889
932596AC2-079 E
Adder
15.41176470588235313.1
316311AC2-079 C
Adder
9.4458823529411768.029
938532AE1-072 E
Adder
15.31411764705882413.017
3146326AYDLETT TAP
Adder
2.26588235294117621.926
917122Z2-027 E
Adder
2.22117647058823531.888
920692AA2-178 E
Adder
6.5094117647058835.533
966622AG1-532 E
Adder
1.33882352941176451.138
316075AC2-137 C
50/50
0.6540.654
3150621CHESTS7
50/50
3.0123.012
925865AC1-065 E
Adder
27.3976470588235323.288
961952AG1-038 E
Adder
6.8294117647058825.805
961951AG1-038 C
Adder
4.9458823529411764.204
944012AF1-069 E
Adder
7.0023529411764715.952
946282AF1-292 E
Adder
1.47764705882352951.256
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.017.01
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.912122.912
CPLELTFEXP_CPLE->PJM
CLTF
14.714.7
TVALTFEXP_TVA->PJM
CLTF
8.1358.135
O66PJM->LTFIMP_O-066
CMTX_NF
43.443.4
G-007PJM->LTFIMP_G-007
CMTX_NF
6.8256.825
SIGELTFEXP_SIGE->PJM
CLTF
0.3490.349
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.3345.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.55730.557
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.5435.543
LAGNLTFEXP_LAGN->PJM
CLTF
10.28110.281
NYPJM->LTFIMP_NY
CLTF
3.1153.115
LGEELTFEXP_LGEE->PJM
CLTF
1.8191.819
WECLTFEXP_WEC->PJM
CLTF
0.9390.939

Details for 8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.6 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3658.56
MW Contribution:2.85
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926785AC1-164_E
Adder
22.7847058823529419.367
943471AF1-018 C
Adder
8.5917647058823537.303
926472AC1-118 E
Adder
1.221.037
316084AB2-161 E
Adder
6.0470588235294125.14
3150411LDYSMT5
50/50
7.2677.267
316312AB1-027 C
50/50
0.6940.694
938552AE1-074 E
Adder
1.32352941176470581.125
934782AD1-105 E
Adder
6.1211764705882365.203
944631AF1-128 C
Adder
48.5670588235294141.282
936592AD2-074 E
Adder
10.7858823529411769.168
316160AE1-175 E
Adder
1.4270588235294121.213
3150921YORKTN3
Adder
139.0764705882353118.215
926755AC1-161 E
Adder
14.11411764705882511.997
933291AC2-141 C
Adder
33.06352941176470528.104
925522AC1-027 E
Adder
1.3152941176470591.118
3145256KINGFORK
Adder
1.10588235294117650.94
957872AF2-081 E
Adder
4.58588235294117653.898
941102AE2-104 E
Adder
5.69058823529411754.837
938562AE1-075 E
Adder
0.92941176470588240.79
3150401LDYSMT4
50/50
7.2447.244
3150441FOUR RIVERB
50/50
4.4254.425
3130536PAPERMILL
Adder
8.0105882352941196.809
939602AE1-190 E
Adder
1.70117647058823531.446
936591AD2-074 C
Adder
6.6105882352941175.619
3150651CHESTF6
Adder
21.86235294117646818.583
946262AF1-291 E
Adder
1.67294117647058821.422
933292AC2-141 E
Adder
14.11411764705882511.997
934576AD1-082 E
Adder
4.8176470588235294.095
944602AF1-125 E
Adder
110.112941176470693.596
3145506HICKORY
Adder
2.3435294117647061.992
957871AF2-081 C
Adder
10.7011764705882359.096
943612AF1-032 E
Adder
0.98941176470588230.841
940492AE2-034 E
Adder
3.11882352941176462.651
934522AD1-076 E
Adder
6.2011764705882355.271
943172AE2-346 E
Adder
0.58235294117647060.495
918492AA1-063AE OP
Adder
3.83529411764705853.26
925122AB2-169 E
Adder
5.48117647058823554.659
958261AF2-120 C
Adder
7.4223529411764716.309
934146AD1-041 E
Adder
4.2517647058823533.614
940641AE2-051 C
Adder
15.55529411764705813.222
3145946PLYMOUTH TP
Adder
0.32235294117647060.274
933982AD1-022 E
Adder
4.7105882352941174.004
939246AE1-155 E
Adder
10.3364705882352948.786
957972AF2-091 E
Adder
3.1105882352941182.644
944641AF1-129 C
Adder
120.07411764705883102.063
316240AF1-291 C
Adder
2.5105882352941182.134
924814AB2-134 E
Adder
14.62588235294117712.432
942342AE2-247 E
Adder
2.22117647058823531.888
919152AA1-139 E1
Adder
4.3764705882352953.72
920042AA2-088 E OP
Adder
10.4070588235294138.846
934521AD1-076 C
Adder
12.16705882352941310.342
934511AD1-075 C
Adder
8.3752941176470597.119
3145723EMPORIA
Adder
0.39411764705882360.335
923573AB1-173 E OP
Adder
3.00235294117647072.552
3150451FOUR RIVERC
50/50
5.4065.406
316078AC2-138 E
Adder
1.10352941176470590.938
958262AF2-120 E
Adder
4.9482352941176484.206
966661AG1-536 C
Adder
6.3847058823529415.427
939612AE1-191 E
Adder
6.8023529411764715.782
957602AF2-054 E
Adder
1.68117647058823551.429
944491AF1-114 C
Adder
6.6258823529411775.632
940432AE2-027 E
Adder
9.9623529411764718.468
934012AD1-025 E
Adder
11.569.826
939411AE1-173 C
Adder
85.3176470588235272.52
913392Y1-086 E
Adder
2.33294117647058831.983
3150471FOUR RIVERE
50/50
4.3614.361
315052AA1-145 CT2
50/50
7.0467.046
3142296MT RD221
50/50
0.1630.163
316004AC1-112 C
50/50
0.4320.432
3141813NORNECK
Adder
1.05058823529411760.893
962861AG1-135 C
Adder
7.2058823529411776.125
943741AF1-042 C
Adder
3.4588235294117652.94
942001AE2-212 C
Adder
2.4364705882352942.071
939192AE1-149 E
Adder
7.9023529411764716.717
939312AE1-162 E
Adder
1.5964705882352941.357
934065AD1-033 E
Adder
5.4035294117647064.593
937226AE2-253 E
Adder
6.2658823529411765.326
958502AF2-144 E
Adder
1.0717647058823530.911
924517AB2-100 E2
Adder
2.69764705882352952.293
934501AD1-074 C
Adder
33.50117647058823428.476
957601AF2-054 C
Adder
2.5211764705882352.143
3143316POE
Adder
1.46235294117647091.243
939191AE1-149 C
Adder
11.85294117647058710.075
901082W1-029 E
Adder
33.6023529411764728.562
926412AC1-112 E
50/50
1.481.48
963612AG1-210 E
Adder
1.18235294117647041.005
940642AE2-051 E
Adder
10.3694117647058828.814
942341AE2-247 C
Adder
1.6082352941176471.367
943462AF1-017 E
Adder
2.37411764705882342.018
919153AA1-139 E2
Adder
4.3764705882352953.72
958162AF2-110 E
Adder
2.3235294117647061.975
924516AB2-100 E1
Adder
2.69764705882352952.293
934512AD1-075 E
Adder
4.2635294117647063.624
934502AD1-074 E
Adder
17.05411764705882414.496
966621AG1-532 C
Adder
1.28235294117647071.09
918512AA1-065 E OP
Adder
5.3564705882352944.553
3150461FOUR RIVERD
50/50
4.3614.361
934392AD1-063 E
Adder
1.28823529411764711.095
966662AG1-536 E
Adder
8.587.293
962862AG1-135 E
Adder
4.8047058823529414.084
943742AF1-042 E
Adder
5.6435294117647064.797
944492AF1-114 E
Adder
9.1505882352941177.778
940431AE2-027 C
Adder
14.94470588235294212.703
942002AE2-212 E
Adder
1.62470588235294121.381
944581AF1-123 C
Adder
48.8541176470588341.526
941101AE2-104 C
Adder
3.57882352941176453.042
316088AB2-174 E
Adder
5.9647058823529415.07
316141AB2-099 E
Adder
0.242352941176470580.206
923994AB2-040_E
Adder
5.6294117647058834.785
3150391LDYSMT3
50/50
7.2317.231
939262AE1-157 E
50/50
11.49311.493
3150431FOUR RIVERA
50/50
4.4254.425
925865AC1-065 E
Adder
19.93176470588235516.942
936582AD2-073 E
Adder
1.24588235294117641.059
961952AG1-038 E
Adder
5.2788235294117654.487
961951AG1-038 C
Adder
3.8235294117647063.25
944012AF1-069 E
Adder
4.2588235294117653.62
946282AF1-292 E
Adder
0.9435294117647060.802
966881AG1-559 C
50/50
3.5873.587
3150601CHESTF5
Adder
77.6188235294117765.976
964212AG1-282 E
Adder
1.59882352941176481.359
962962AG1-145 E
Adder
1.73058823529411781.471
925332AB2-190 E
Adder
9.4164705882352948.004
927226AC1-216 E
Adder
8.9282352941176487.589
941591AE2-156 C
Adder
19.41529411764705816.503
944601AF1-125 C
Adder
48.1011764705882440.886
944591AF1-124 C
Adder
49.02705882352941641.673
936666AD2-085 E
Adder
6.0552941176470595.147
944011AF1-069 C
Adder
10.9635294117647079.319
938771AE1-103 C
Adder
3.0152941176470592.563
3145413WATKINS
Adder
0.69764705882352940.593
960081AF2-299 C
Adder
1.71058823529411771.454
939261AE1-157 C
50/50
21.18921.189
966882AG1-559 E
50/50
1.8071.807
930122AB1-027 E
50/50
1.821.82
316169AC1-164 GEN
Adder
50.7141176470588243.107
957971AF2-091 C
Adder
2.25294117647058821.915
944582AF1-123 E
Adder
111.8694117647058995.089
944592AF1-124 E
Adder
112.2741176470588395.433
935112AD1-144 E
Adder
1.02705882352941180.873
316349AD2-085 C
Adder
3.71176470588235263.155
923832AB2-022 E
Adder
1.31764705882352961.12
938772AE1-103 E
Adder
4.16470588235294153.54
916042Z1-036 E
Adder
29.55058823529411825.118
960082AF2-299 E
Adder
1.140.969
946281AF1-292 C
Adder
1.4152941176470591.203
926071AC1-086 C
Adder
1.16117647058823530.987
966871AG1-558 C
50/50
3.1913.191
966872AG1-558 E
50/50
1.6071.607
3150841SPRUNCB
Adder
10.5929411764705879.004
3150831SPRUNCA
Adder
10.5929411764705879.004
316076AC2-137 E
Adder
1.6835294117647061.431
923842AB2-024 E
Adder
2.16941176470588241.844
964211AG1-282 C
Adder
2.3988235294117652.039
316157AD2-030 E
Adder
1.4152941176470591.203
926662AC1-147 E
Adder
1.43647058823529421.221
916192Z1-068 E
Adder
2.0305882352941181.726
939412AE1-173 E
Adder
56.8788235294117748.347
957492AF2-043 E
Adder
1.52235294117647071.294
923862AB2-026 E
Adder
1.09058823529411760.927
941032AE2-094 E
Adder
15.02823529411764612.774
941031AE2-094 C
Adder
33.5552941176470628.522
923852AB2-025 E
Adder
1.10705882352941170.941
961941AG1-037 C
Adder
0.485882352941176430.413
961942AG1-037 E
Adder
0.32352941176470590.275
3150381LDYSMT2
50/50
7.0467.046
315051AA1-145 CT1
50/50
7.0497.049
3150481FOUR RIVERF
50/50
5.3255.325
927042AC1-191 E
50/50
6.3816.381
316233AE1-074 C
Adder
2.6270588235294122.233
3150691DARBY 3
50/50
3.2613.261
940551AE2-041 C
Adder
8.5917647058823537.303
957832AF2-077 E
Adder
1.67882352941176481.427
935162AD1-151 E
Adder
12.49647058823529410.622
943461AF1-017 C
Adder
1.4552941176470591.237
932596AC2-079 E
Adder
10.0764705882352948.565
316311AC2-079 C
Adder
6.1752941176470585.249
938532AE1-072 E
Adder
9.7941176470588228.325
3146326AYDLETT TAP
Adder
1.44941176470588241.232
917122Z2-027 E
Adder
1.42117647058823531.208
920692AA2-178 E
Adder
4.1576470588235293.534
966622AG1-532 E
Adder
0.85529411764705890.727
3150701DARBY 4
50/50
3.2653.265
3150731STONECA
Adder
8.157647058823536.934
935161AD1-151 C
Adder
18.74470588235294215.933
932046AC2-012 E
Adder
14.21176470588235412.08
938531AE1-072 C
Adder
18.7870588235294115.969
958161AF2-110 C
Adder
1.46000000000000021.241
3145393UNCAMP
Adder
6.2117647058823535.28
933981AD1-022 C
Adder
8.6517647058823537.354
900672V4-068 E
Adder
0.34588235294117650.294
3150371LDYSMT1
50/50
6.9556.955
927041AC1-191 C
50/50
12.81112.811
3142366NRTHEST
50/50
0.2360.236
3138116ELKO L286
Adder
1.75647058823529421.493
963611AG1-210 C
Adder
0.78823529411764710.67
961611AG1-000B C
Adder
18.15411764705882215.431
940541AE2-040 C
Adder
2.73647058823529442.326
940481AE2-033 C
Adder
15.38117647058823513.074
940482AE2-033 E
Adder
10.3694117647058828.814
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.3184.318
CBM South 2LTFEXP_CBM-S2->PJM
CBM
75.17775.177
CPLELTFEXP_CPLE->PJM
CLTF
9.069.06
TVALTFEXP_TVA->PJM
CLTF
4.8114.811
O66PJM->LTFIMP_O-066
CMTX_NF
33.64633.646
G-007PJM->LTFIMP_G-007
CMTX_NF
5.2915.291
SIGELTFEXP_SIGE->PJM
CLTF
0.1960.196
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.54824.548
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.76217.762
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.1253.125
LAGNLTFEXP_LAGN->PJM
CLTF
6.0826.082
NYPJM->LTFIMP_NY
CLTF
2.4212.421
LGEELTFEXP_LGEE->PJM
CLTF
1.011.01
WECLTFEXP_WEC->PJM
CLTF
0.5150.515

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.88 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1342.55
MW Contribution:1.33
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:127.67 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1350.99
MW Contribution:1.25
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
942342AE2-247 E
Adder
0.69411764705882350.59
919152AA1-139 E1
Adder
1.71529411764705891.458
920042AA2-088 E OP
Adder
4.3847058823529413.727
934521AD1-076 C
Adder
5.1635294117647064.389
934511AD1-075 C
Adder
3.55411764705882363.021
3145723EMPORIA
Adder
0.18470588235294120.157
923573AB1-173 E OP
Adder
1.40588235294117661.195
919692AA2-053 E OP
Adder
1.80705882352941181.536
959311AF2-222 C
Adder
5.57411764705882454.738
925785AC1-054 E
Adder
1.47764705882352951.256
316263AC1-034 C
Adder
2.91411764705882352.477
933292AC2-141 E
Adder
5.7376470588235294.877
944602AF1-125 E
Adder
43.0952941176470636.631
3145506HICKORY
Adder
0.91764705882352950.78
957871AF2-081 C
Adder
4.1964705882352953.567
943612AF1-032 E
Adder
0.374117647058823550.318
940492AE2-034 E
Adder
1.2952941176470591.101
934522AD1-076 E
Adder
2.6317647058823532.237
943172AE2-346 E
Adder
0.255294117647058840.217
918492AA1-063AE OP
Adder
1.72705882352941181.468
962571AG1-106 C
Adder
1.16941176470588240.994
937482AD2-202 E
Adder
0.52588235294117650.447
917332KELFORD E
Adder
0.70117647058823530.596
925122AB2-169 E
Adder
2.4564705882352942.088
316274AC1-208 C
Adder
3.8952941176470593.311
917342Z2-044 E
Adder
0.26117647058823530.222
3151311EDGECMA
Adder
6.8129411764705895.791
941011AE2-092 C
Adder
-4.452941176470588-3.785
941591AE2-156 C
Adder
7.202352941176476.122
944601AF1-125 C
Adder
18.82588235294117516.002
944591AF1-124 C
Adder
19.18823529411764616.31
936666AD2-085 E
Adder
1.89058823529411771.607
944011AF1-069 C
50/50
8.8768.876
938771AE1-103 C
Adder
1.16941176470588240.994
3145413WATKINS
Adder
0.279999999999999970.238
963041AG1-153 C
50/50
3.6733.673
960081AF2-299 C
Adder
0.80117647058823540.681
926072AC1-086 E
Adder
4.11294117647058853.496
936261AD2-033 C
Adder
4.2364705882352943.601
962562AG1-105 E
Adder
2.4729411764705882.102
957862AF2-080 E
Adder
1.47411764705882351.253
936171AD2-023 C
Adder
1.80117647058823521.531
944582AF1-123 E
Adder
43.7823529411764837.215
944592AF1-124 E
Adder
43.9411764705882437.35
935112AD1-144 E
Adder
0.339999999999999970.289
316349AD2-085 C
Adder
1.15882352941176480.985
923832AB2-022 E
Adder
0.51764705882352950.44
938772AE1-103 E
Adder
1.61529411764705881.373
916042Z1-036 E
Adder
11.93411764705882510.144
963042AG1-153 E
50/50
5.5095.509
960082AF2-299 E
Adder
0.53411764705882360.454
926662AC1-147 E
Adder
0.53176470588235290.452
916192Z1-068 E
Adder
0.77294117647058820.657
939412AE1-173 E
50/50
36.75136.751
957492AF2-043 E
Adder
0.57529411764705880.489
941032AE2-094 E
50/50
12.16712.167
941031AE2-094 C
50/50
27.16527.165
923852AB2-025 E
Adder
0.50705882352941180.431
3151051BRUNSWICKS1
50/50
11.26311.263
961941AG1-037 C
Adder
0.212941176470588240.181
961942AG1-037 E
Adder
0.14235294117647060.121
936262AD2-033 E
Adder
2.8247058823529412.401
934332AD1-057 E
Adder
0.7917647058823530.673
934321AD1-056 C
Adder
2.72588235294117662.317
934322AD1-056 E
Adder
1.47882352941176461.257
934331AD1-057 C
Adder
1.52117647058823541.293
927022AC1-189 E
Adder
1.8235294117647061.55
926755AC1-161 E
Adder
5.7376470588235294.877
933291AC2-141 C
Adder
13.44235294117647211.426
925522AC1-027 E
Adder
0.50.425
3145256KINGFORK
Adder
0.367058823529411770.312
957872AF2-081 E
Adder
1.79882352941176471.529
941102AE2-104 E
Adder
2.06588235294117651.756
962572AG1-106 E
Adder
0.51176470588235290.435
964242AG1-285 E
Adder
3.57647058823529433.04
924162AB2-060 E OP
Adder
1.71764705882352931.46
932632AC2-084 E
Adder
1.3917647058823531.183
926214AC1-099 E
Adder
0.520.442
964792AG1-342 E
Adder
0.99058823529411770.842
932763AC2-100 E
Adder
1.12117647058823520.953
939411AE1-173 C
50/50
55.12655.126
913392Y1-086 E
Adder
0.91764705882352950.78
3151031BRUNSWICKG2
50/50
5.4215.421
3137643SOCKMAN
Adder
0.30470588235294120.259
919710AA2-057 E
Adder
1.72588235294117661.467
932046AC2-012 E
Adder
5.2588235294117654.47
938531AE1-072 C
Adder
7.3705882352941176.265
958161AF2-110 C
Adder
0.53058823529411770.451
3145393UNCAMP
Adder
2.44352941176470572.077
3152411Z1-086 GT1
50/50
7.0067.006
933981AD1-022 C
Adder
3.73.145
900672V4-068 E
Adder
0.149411764705882360.127
924302AB2-077 E O1
Adder
0.54823529411764720.466
940642AE2-051 E
50/50
7.6927.692
942341AE2-247 C
Adder
0.50235294117647060.427
943462AF1-017 E
Adder
0.74117647058823530.63
919153AA1-139 E2
Adder
1.71529411764705891.458
958162AF2-110 E
Adder
0.84352941176470590.717
924516AB2-100 E1
Adder
1.25176470588235311.064
934512AD1-075 E
Adder
1.80941176470588251.538
934502AD1-074 E
Adder
7.237647058823536.152
966621AG1-532 C
Adder
0.60117647058823530.511
918512AA1-065 E OP
Adder
2.34000000000000031.989
3147223TWITTYS
Adder
0.332941176470588240.283
959312AF2-222 E
Adder
3.73411764705882383.174
924022AB2-043 E O1
Adder
2.11764705882352941.8
918532AA1-067 E
Adder
0.30941176470588240.263
936161AD2-022 C
Adder
3.0882352941176472.625
940541AE2-040 C
Adder
1.25411764705882361.066
940481AE2-033 C
Adder
7.0611764705882366.002
940482AE2-033 E
Adder
4.7611764705882354.047
3152441Z1-086 ST
50/50
12.19612.196
3152431Z1-086 GT3
50/50
7.0037.003
3152421Z1-086 GT2
50/50
7.0037.003
923263AB1-132 E OP
Adder
2.6305882352941182.236
925612AC1-036 E
Adder
0.30.255
924312AB2-078 E O1
Adder
0.54823529411764720.466
926274AC1-105 E
Adder
1.13764705882352950.967
938821AE1-108 C
Adder
-4.716470588235294-4.009
940641AE2-051 C
50/50
11.53811.538
316336AC2-165 C
Adder
-10.758823529411764-9.145
3145946PLYMOUTH TP
Adder
0.136470588235294120.116
933982AD1-022 E
Adder
2.01411764705882361.712
934622AD1-088 E
Adder
2.11.785
934612AD1-087 E
Adder
1.79882352941176471.529
927146AC1-208 E
Adder
1.72941176470588241.47
927255AC1-221 E
Adder
1.65176470588235281.404
939312AE1-162 E
Adder
0.41294117647058820.351
934065AD1-033 E
Adder
2.10705882352941171.791
937226AE2-253 E
Adder
2.4552941176470592.087
924517AB2-100 E2
Adder
1.25176470588235311.064
934501AD1-074 C
Adder
14.2176470588235312.085
957482AF2-042 E
Adder
18.89411764705882416.06
934621AD1-088 C
Adder
4.3611764705882353.707
935172AD1-152 E
Adder
2.6258823529411772.232
961671AG1-007 C
Adder
0.410588235294117640.349
936162AD2-022 E
Adder
1.85294117647058831.575
944581AF1-123 C
Adder
19.11999999999999716.252
941101AE2-104 C
Adder
1.31.105
957481AF2-042 C
Adder
28.3424.089
316088AB2-174 E
Adder
2.7941176470588242.375
316141AB2-099 E
Adder
0.107058823529411760.091
923994AB2-040_E
Adder
2.63647058823529432.241
924322AB2-079 E O1
Adder
0.54823529411764720.466
943902AF1-058 E
Adder
0.55294117647058830.47
961672AG1-007 E
Adder
0.232941176470588260.198
901082W1-029 E
Adder
13.19764705882352911.218
3151021BRUNSWICKG1
50/50
5.4215.421
3151041BRUNSWICKG3
50/50
5.4215.421
926206AC1-098 E
Adder
1.57411764705882361.338
964791AG1-342 C
Adder
1.48470588235294131.262
925595AC1-034 E
Adder
2.19764705882352951.868
943461AF1-017 C
Adder
0.454117647058823570.386
932596AC2-079 E
Adder
3.2117647058823532.73
316311AC2-079 C
Adder
1.9682352941176471.673
938532AE1-072 E
Adder
3.84235294117647053.266
3146326AYDLETT TAP
Adder
0.56823529411764710.483
917122Z2-027 E
Adder
0.55999999999999990.476
920692AA2-178 E
Adder
1.72705882352941181.468
966622AG1-532 E
Adder
0.40.34
927264AC1-222 E
Adder
1.66470588235294131.415
922923AB1-081 E OP
Adder
1.63529411764705881.39
944012AF1-069 E
50/50
3.4483.448
946282AF1-292 E
Adder
0.44235294117647060.376
957861AF2-080 C
Adder
3.3247058823529412.826
917512Z2-088 E OP1
Adder
2.1352941176470591.815
946281AF1-292 C
Adder
0.66352941176470580.564
926071AC1-086 C
Adder
9.037647058823537.682
964241AG1-285 C
Adder
5.3647058823529414.56
962561AG1-105 C
Adder
3.70941176470588243.153
927021AC1-189 C
Adder
3.66117647058823573.112
924152AB2-059 E OP
Adder
2.31764705882352961.97
936172AD2-023 E
Adder
0.97764705882352940.831
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5712.571
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.69643.696
CPLELTFEXP_CPLE->PJM
CLTF
5.3965.396
TVALTFEXP_TVA->PJM
CLTF
2.4942.494
O66PJM->LTFIMP_O-066
CMTX_NF
6.9576.957
G-007PJM->LTFIMP_G-007
CMTX_NF
1.0921.092
SIGELTFEXP_SIGE->PJM
CLTF
0.0910.091
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.53211.532
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.0379.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5141.514
LAGNLTFEXP_LAGN->PJM
CLTF
3.2073.207
NYPJM->LTFIMP_NY
CLTF
0.5140.514
LGEELTFEXP_LGEE->PJM
CLTF
0.4480.448
WECLTFEXP_WEC->PJM
CLTF
0.2390.239

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.42 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2598.93
MW Contribution:2.57
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.96 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2758.53
MW Contribution:2.49
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
933292AC2-141 E
50/50
37.13537.135
316294AC1-161 C
50/50
14.21614.216
916191Z1-068 C
50/50
0.0420.042
944602AF1-125 E
50/50
102.879102.879
3145506HICKORY
50/50
2.1612.161
957871AF2-081 C
50/50
9.4939.493
940492AE2-034 E
Adder
2.3152941176470591.968
934522AD1-076 E
Adder
4.6470588235294123.95
943172AE2-346 E
Adder
0.440.374
918492AA1-063AE OP
Adder
3.0882352941176472.625
962571AG1-106 C
Adder
2.1564705882352941.833
937482AD2-202 E
50/50
1.0431.043
917332KELFORD E
Adder
1.2282352941176471.044
961792AG1-021 E
Adder
1.13294117647058810.963
925122AB2-169 E
Adder
4.3388235294117653.688
316274AC1-208 C
Adder
7.0835294117647066.021
917342Z2-044 E
Adder
0.475294117647058870.404
3151311EDGECMA
Adder
12.4152941176470610.553
939411AE1-173 C
50/50
86.92186.921
913392Y1-086 E
Adder
1.8917647058823531.608
3151031BRUNSWICKG2
50/50
9.6689.668
3137643SOCKMAN
Adder
0.56941176470588240.484
937481AD2-202 C
50/50
0.3590.359
919710AA2-057 E
Adder
3.1364705882352942.666
932046AC2-012 E
50/50
12.1712.17
316017AA1-139 ULT1
50/50
1.0281.028
938531AE1-072 C
50/50
16.39816.398
3145393UNCAMP
Adder
3.8517647058823533.274
3152411Z1-086 GT1
50/50
12.45512.455
933981AD1-022 C
Adder
6.4741176470588245.503
900672V4-068 E
Adder
0.254117647058823560.216
924302AB2-077 E O1
Adder
1.18705882352941171.009
940641AE2-051 C
50/50
26.4726.47
3145946PLYMOUTH TP
Adder
0.24117647058823530.205
933982AD1-022 E
Adder
3.52470588235294142.996
934622AD1-088 E
50/50
4.4114.411
934611AD1-087 C
50/50
1.2361.236
934612AD1-087 E
50/50
3.5653.565
927146AC1-208 E
Adder
3.14470588235294152.673
927255AC1-221 E
Adder
3.2152941176470592.733
926755AC1-161 E
50/50
37.13537.135
933291AC2-141 C
50/50
86.99486.994
925522AC1-027 E
50/50
1.1581.158
957872AF2-081 E
50/50
4.0684.068
962572AG1-106 E
Adder
0.9435294117647060.802
964242AG1-285 E
Adder
7.846.664
924162AB2-060 E OP
Adder
3.78117647058823543.214
932632AC2-084 E
Adder
2.50352941176470622.128
926214AC1-099 E
Adder
0.93529411764705890.795
964792AG1-342 E
Adder
2.06588235294117651.756
932763AC2-100 E
Adder
2.1788235294117651.852
316018AA1-139 ULT2
50/50
1.0281.028
919152AA1-139 E1
50/50
3.8823.882
920042AA2-088 E OP
Adder
7.3835294117647066.276
934521AD1-076 C
Adder
9.1176470588235297.75
934511AD1-075 C
Adder
6.2764705882352945.335
3145723EMPORIA
Adder
0.352941176470588260.3
923573AB1-173 E OP
Adder
2.65411764705882322.256
919692AA2-053 E OP
Adder
3.30000000000000032.805
959311AF2-222 C
Adder
14.27882352941176512.137
925785AC1-054 E
Adder
2.882.448
316263AC1-034 C
Adder
5.31058823529411854.514
957601AF2-054 C
Adder
-1.2505882352941176-1.063
3143316POE
Adder
0.80823529411764720.687
901082W1-029 E
Adder
23.54352941176470520.012
3151021BRUNSWICKG1
50/50
9.6689.668
3151041BRUNSWICKG3
50/50
9.6689.668
942462AE2-259 E
Adder
4.3564705882352943.703
926206AC1-098 E
Adder
2.8317647058823532.407
964791AG1-342 C
Adder
3.09882352941176452.634
926662AC1-147 E
Adder
1.23058823529411781.046
916192Z1-068 E
50/50
1.7941.794
939412AE1-173 E
50/50
57.94757.947
941032AE2-094 E
50/50
21.48321.483
941031AE2-094 C
50/50
47.96747.967
923852AB2-025 E
Adder
0.98588235294117640.838
3151051BRUNSWICKS1
50/50
20.08620.086
961941AG1-037 C
Adder
0.367058823529411770.312
961942AG1-037 E
Adder
0.244705882352941160.208
958211AF2-115 C
Adder
1.6635294117647061.414
936262AD2-033 E
Adder
7.1529411764705896.08
934332AD1-057 E
Adder
1.45058823529411771.233
934321AD1-056 C
Adder
4.99411764705882364.245
934322AD1-056 E
Adder
2.70941176470588242.303
934331AD1-057 C
Adder
2.78588235294117632.368
927022AC1-189 E
Adder
3.25764705882352962.769
925595AC1-034 E
Adder
4.00588235294117643.405
934065AD1-033 E
50/50
5.0045.004
937226AE2-253 E
50/50
5.6435.643
924517AB2-100 E2
Adder
2.3717647058823532.016
934501AD1-074 C
Adder
25.10470588235294221.339
957482AF2-042 E
50/50
36.84236.842
934621AD1-088 C
50/50
9.1619.161
942461AE2-259 C
Adder
6.5341176470588245.554
946301AF1-294 C
Adder
2.73529411764705932.325
935172AD1-152 E
Adder
5.2058823529411774.425
961671AG1-007 C
Adder
0.73882352941176480.628
940642AE2-051 E
50/50
17.64717.647
316388AE2-253 GEN
50/50
1.8981.898
919153AA1-139 E2
50/50
3.8823.882
924516AB2-100 E1
Adder
2.3717647058823532.016
934512AD1-075 E
Adder
3.19529411764705932.716
934502AD1-074 E
Adder
12.7810.863
966621AG1-532 C
Adder
1.15411764705882350.981
918512AA1-065 E OP
Adder
3.98941176470588273.391
3147223TWITTYS
Adder
0.82823529411764710.704
959312AF2-222 E
Adder
9.5670588235294118.132
924022AB2-043 E O1
Adder
4.6082352941176473.917
918532AA1-067 E
Adder
0.54705882352941180.465
316185AD1-033 C
50/50
1.2261.226
944581AF1-123 C
50/50
45.64445.644
957481AF2-042 C
50/50
55.26355.263
316088AB2-174 E
Adder
5.3035294117647064.508
316141AB2-099 E
Adder
0.183529411764705890.156
923994AB2-040_E
Adder
4.9776470588235294.231
946302AF1-294 E
Adder
2.3164705882352941.969
924322AB2-079 E O1
Adder
1.18705882352941171.009
943902AF1-058 E
Adder
1.11882352941176480.951
961672AG1-007 E
Adder
0.41882352941176470.356
3151101ELIZAR3
50/50
3.0693.069
944012AF1-069 E
50/50
6.0886.088
946282AF1-292 E
Adder
0.84941176470588230.722
3151541CLOVER2
50/50
12.43612.436
3138533PONTONDP
Adder
0.49294117647058820.419
957861AF2-080 C
Adder
5.9388235294117655.048
917512Z2-088 E OP1
Adder
3.83294117647058833.258
941591AE2-156 C
50/50
16.7516.75
3151081ELIZAR1
50/50
3.033.03
3151091ELIZAR2
50/50
2.9782.978
316316AC1-027 C
50/50
0.3010.301
944601AF1-125 C
50/50
44.94144.941
944591AF1-124 C
50/50
45.80645.806
944011AF1-069 C
50/50
15.67315.673
938771AE1-103 C
Adder
1.81647058823529431.544
3145413WATKINS
Adder
0.451764705882352960.384
963041AG1-153 C
50/50
6.556.55
960081AF2-299 C
Adder
1.541.309
926072AC1-086 E
Adder
7.5870588235294126.449
961791AG1-021 C
Adder
1.33058823529411761.131
936261AD2-033 C
Adder
10.7294117647058829.12
962562AG1-105 E
Adder
5.1941176470588244.415
957862AF2-080 E
Adder
2.6329411764705882.238
944582AF1-123 E
50/50
104.52104.52
944592AF1-124 E
50/50
104.898104.898
923832AB2-022 E
Adder
1.06823529411764720.908
938772AE1-103 E
Adder
2.50941176470588222.133
916042Z1-036 E
Adder
21.67647058823529718.425
963042AG1-153 E
50/50
9.8259.825
960082AF2-299 E
Adder
1.02588235294117650.872
946281AF1-292 C
Adder
1.27411764705882361.083
926071AC1-086 C
Adder
16.6705882352941214.17
3151531CLOVER1
50/50
12.55212.552
964241AG1-285 C
Adder
11.7588235294117649.995
958212AF2-115 E
Adder
1.41647058823529411.204
962561AG1-105 C
Adder
7.7917647058823536.623
927021AC1-189 C
Adder
6.5388235294117655.558
924152AB2-059 E OP
Adder
4.2235294117647063.59
938532AE1-072 E
50/50
8.5488.548
3146326AYDLETT TAP
Adder
1.25647058823529421.068
917122Z2-027 E
Adder
1.1117647058823530.945
920692AA2-178 E
Adder
3.0870588235294122.624
966622AG1-532 E
Adder
0.76941176470588240.654
3147133PAMPLIN
Adder
0.740.629
927264AC1-222 E
Adder
3.3870588235294122.879
922923AB1-081 E OP
Adder
2.9811764705882352.534
316375AC2-012 C
50/50
1.2551.255
940541AE2-040 C
Adder
2.4364705882352942.071
940481AE2-033 C
Adder
13.6776470588235311.626
940482AE2-033 E
Adder
9.2211764705882357.838
3152441Z1-086 ST
50/50
21.68121.681
3152431Z1-086 GT3
50/50
12.4512.45
3152421Z1-086 GT2
50/50
12.4512.45
923263AB1-132 E OP
Adder
4.8517647058823534.124
925612AC1-036 E
Adder
0.74705882352941180.635
924312AB2-078 E O1
Adder
1.18705882352941171.009
926274AC1-105 E
Adder
2.3364705882352941.986
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.7574.757
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.65881.658
CPLELTFEXP_CPLE->PJM
CLTF
9.989.98
TVALTFEXP_TVA->PJM
CLTF
4.8674.867
O66PJM->LTFIMP_O-066
CMTX_NF
13.52713.527
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1242.124
SIGELTFEXP_SIGE->PJM
CLTF
0.1890.189
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.52724.527
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.91517.915
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.1033.103
LAGNLTFEXP_LAGN->PJM
CLTF
6.2356.235
NYPJM->LTFIMP_NY
CLTF
0.9860.986
LGEELTFEXP_LGEE->PJM
CLTF
0.950.95
WECLTFEXP_WEC->PJM
CLTF
0.5060.506

Details for AD1-056 TP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AD1-056 TP-6HATHAWAY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 238_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.88 %
Rating:441.8 MVA
Rating Type:B
MVA to Mitigate:467.79
MW Contribution:4.55
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
AD1-056 TP-6HATHAWAY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 238_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.07 %
Rating:441.8 MVA
Rating Type:B
MVA to Mitigate:450.95
MW Contribution:4.62
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316087AB2-174 C
50/50
1.61.6
962572AG1-106 E
50/50
2.4312.431
920042AA2-088 E OP
50/50
7.227.22
3145723EMPORIA
50/50
0.6130.613
923573AB1-173 E OP
50/50
4.3114.311
316011AB1-132 C OP
50/50
4.7674.767
919692AA2-053 E OP
50/50
4.4044.404
925785AC1-054 E
50/50
2.3732.373
943172AE2-346 E
50/50
0.3630.363
918492AA1-063AE OP
50/50
3.9553.955
962571AG1-106 C
50/50
5.5565.556
316365AB2-100 C1
50/50
1.7671.767
316318V4-068 C
50/50
0.0530.053
316140AB2-099 C
50/50
0.0580.058
3137643SOCKMAN
50/50
0.870.87
924517AB2-100 E2
50/50
5.3255.325
3156073AA1-063SOLA
50/50
1.3621.362
3151371ROSEMS1
50/50
2.9592.959
924516AB2-100 E1
50/50
5.3255.325
966621AG1-532 C
50/50
2.0462.046
918512AA1-065 E OP
Adder
3.00117647058823562.551
3156083AA2-088SOLA
50/50
0.7230.723
316088AB2-174 E
50/50
8.8598.859
316141AB2-099 E
50/50
0.1510.151
923994AB2-040_E
50/50
8.0838.083
313506AB1-173 C OP
50/50
1.4821.482
3151361ROSEMG1
50/50
4.7774.777
946282AF1-292 E
50/50
1.5051.505
316129AC1-054 C
50/50
0.8420.842
3145413WATKINS
Adder
0.364705882352941160.31
960081AF2-299 C
50/50
2.7282.728
3151391GASTONA
50/50
6.2436.243
926072AC1-086 E
50/50
19.55119.551
316023AB2-100 C2
50/50
1.7671.767
960082AF2-299 E
50/50
1.8191.819
946281AF1-292 C
50/50
2.2582.258
926071AC1-086 C
50/50
42.95742.957
927021AC1-189 C
Adder
-4.234117647058824-3.599
961941AG1-037 C
50/50
0.3030.303
961942AG1-037 E
50/50
0.2020.202
943171AE2-346 C
50/50
0.1340.134
3151381ROSEMG2
50/50
2.2372.237
934332AD1-057 E
50/50
7.0257.025
934321AD1-056 C
50/50
24.18524.185
934322AD1-056 E
50/50
13.11813.118
934331AD1-057 C
50/50
13.49113.491
966622AG1-532 E
50/50
1.3641.364
3145393UNCAMP
Adder
2.7764705882352942.36
900672V4-068 E
50/50
0.2370.237
3147043LAWRENC
50/50
0.3450.345
3151411GASTONB
50/50
6.2436.243
3151261ROARAP2
50/50
1.5821.582
940481AE2-033 C
50/50
28.45328.453
940482AE2-033 E
50/50
19.18219.182
316181AB2-040 GEN
50/50
1.6691.669
923263AB1-132 E OP
50/50
12.50212.502
3156063AA2-053SOLA
50/50
1.5711.571
3151281ROARAP4
50/50
1.4971.497
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
2.5592.559
G-007ALTFEXP_G-007A->PJM
CMTX
0.2050.205
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.8110.811
VTFLTFEXP_VFT->PJM
CMTX
0.5390.539
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.7580.758
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.2862.286
MDUPJM->LTFIMP_MDU
CLTF
0.0830.083
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.0440.044
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.3990.399
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.2551.255
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
2.542.54
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.5731.573

Details for AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:124.4 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:844.26
MW Contribution:7.18
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:129.93 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:881.78
MW Contribution:7.25
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
920042AA2-088 E OP
50/50
9.2489.248
934521AD1-076 C
Adder
7.246.154
934511AD1-075 C
Adder
4.9835294117647064.236
3145723EMPORIA
50/50
0.9510.951
923573AB1-173 E OP
50/50
6.3246.324
316011AB1-132 C OP
50/50
4.6924.692
919692AA2-053 E OP
50/50
5.8745.874
925785AC1-054 E
50/50
3.2573.257
316263AC1-034 C
50/50
6.8576.857
3151151S HAMPT1
50/50
0.9640.964
934522AD1-076 E
Adder
3.6905882352941183.137
943172AE2-346 E
50/50
0.5760.576
918492AA1-063AE OP
50/50
5.1285.128
962571AG1-106 C
50/50
5.4685.468
917332KELFORD E
50/50
1.6811.681
925122AB2-169 E
50/50
3.9953.995
932631AC2-084 C
50/50
1.1471.147
316274AC1-208 C
50/50
10.95810.958
917342Z2-044 E
50/50
0.6430.643
3151311EDGECMA
50/50
16.316.3
3145413WATKINS
50/50
0.4340.434
960081AF2-299 C
50/50
4.3094.309
3151391GASTONA
50/50
6.1446.144
926072AC1-086 E
50/50
19.24219.242
957862AF2-080 E
50/50
3.0163.016
316023AB2-100 C2
50/50
2.7732.773
960082AF2-299 E
50/50
2.8732.873
946281AF1-292 C
50/50
3.5673.567
926071AC1-086 C
50/50
42.27842.278
316317KELFORD C
50/50
0.3660.366
927021AC1-189 C
50/50
7.497.49
924152AB2-059 E OP
50/50
5.4535.453
961941AG1-037 C
50/50
0.480.48
961942AG1-037 E
50/50
0.320.32
943171AE2-346 C
50/50
0.2130.213
3151381ROSEMG2
50/50
1.8331.833
934332AD1-057 E
50/50
2.6472.647
934321AD1-056 C
50/50
9.1149.114
934322AD1-056 E
50/50
4.9434.943
934331AD1-057 C
50/50
5.0845.084
927022AC1-189 E
50/50
3.7313.731
925595AC1-034 E
50/50
5.1725.172
316087AB2-174 C
50/50
2.4072.407
962572AG1-106 E
50/50
2.3922.392
932632AC2-084 E
50/50
3.6863.686
926214AC1-099 E
50/50
1.3781.378
316140AB2-099 C
50/50
0.0910.091
3137643SOCKMAN
50/50
1.2021.202
316212AC1-099 C
50/50
0.3610.361
919710AA2-057 E
50/50
4.4424.442
316319Z2-044 C
50/50
0.2270.227
3145393UNCAMP
Adder
3.1317647058823532.662
933981AD1-022 C
50/50
5.8155.815
900672V4-068 E
50/50
0.330.33
3147043LAWRENC
50/50
0.5440.544
3151411GASTONB
50/50
6.1446.144
3151261ROARAP2
50/50
2.0552.055
924516AB2-100 E1
50/50
8.3588.358
934512AD1-075 E
Adder
2.53764705882352942.157
934502AD1-074 E
Adder
10.1482352941176478.626
966621AG1-532 C
50/50
3.2323.232
918512AA1-065 E OP
50/50
4.8064.806
918532AA1-067 E
50/50
0.5790.579
940481AE2-033 C
50/50
63.79163.791
940482AE2-033 E
50/50
43.00543.005
316181AB2-040 GEN
50/50
2.4492.449
923263AB1-132 E OP
50/50
12.30412.304
3156063AA2-053SOLA
50/50
2.0952.095
3151281ROARAP4
50/50
1.9441.944
316174AB2-169_C
50/50
0.7280.728
3156011CONETOE2SOL
50/50
1.1641.164
3145946PLYMOUTH TP
Adder
0.18470588235294120.157
933982AD1-022 E
50/50
3.1653.165
927146AC1-208 E
50/50
4.8664.866
316049AB1-081 C OP
50/50
1.4681.468
924517AB2-100 E2
50/50
8.3588.358
934501AD1-074 C
Adder
19.93647058823529516.946
3156021HOLLOMANSOL
50/50
1.5991.599
3156073AA1-063SOLA
50/50
1.7661.766
3151371ROSEMS1
50/50
2.4252.425
961671AG1-007 C
50/50
0.9020.902
316359AB2-059 C OP
50/50
1.731.73
3156083AA2-088SOLA
50/50
0.9260.926
316088AB2-174 E
50/50
13.32913.329
316141AB2-099 E
50/50
0.240.24
923994AB2-040_E
50/50
11.85811.858
313506AB1-173 C OP
50/50
2.1742.174
3151361ROSEMG1
50/50
3.9143.914
316005AA1-067 C
50/50
0.2210.221
961672AG1-007 E
50/50
0.5110.511
316365AB2-100 C1
50/50
2.7732.773
316318V4-068 C
50/50
0.0740.074
926206AC1-098 E
50/50
4.1714.171
316210AC1-098 C
50/50
1.0771.077
316327AA2-057 C
50/50
1.4581.458
966622AG1-532 E
50/50
2.1552.155
922923AB1-081 E OP
50/50
3.8493.849
946282AF1-292 E
50/50
2.3782.378
316129AC1-054 C
50/50
1.1551.155
957861AF2-080 C
50/50
6.8036.803
917512Z2-088 E OP1
50/50
4.5534.553
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.0232.023
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.27631.276
CPLELTFEXP_CPLE->PJM
CLTF
4.2444.244
TVALTFEXP_TVA->PJM
CLTF
1.8021.802
O66PJM->LTFIMP_O-066
CMTX_NF
4.3814.381
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6890.689
SIGELTFEXP_SIGE->PJM
CLTF
0.0730.073
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.6319.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7166.716
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1871.187
LAGNLTFEXP_LAGN->PJM
CLTF
2.312.31
NYPJM->LTFIMP_NY
CLTF
0.3160.316
LGEELTFEXP_LGEE->PJM
CLTF
0.3690.369
WECLTFEXP_WEC->PJM
CLTF
0.1970.197
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 556_SRT-S-3'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 2092_SRT-A'
 OPEN BRANCH FROM BUS 313714 TO BUS 313885 CKT 1   /*6PEMBROKE    230.0 - 6WALBMRL     230.0
 OPEN BRANCH FROM BUS 313885 TO BUS 314662 CKT 1   /*6WALBMRL     230.0 - 6S HERTFORD  230.0
 OPEN BRANCH FROM BUS 314651 TO BUS 314662 CKT 1   /*6WINFALL     230.0 - 6S HERTFORD  230.0
 OPEN BUS 313885                                   /*6WALBMRL     230.0
 OPEN BUS 314662                                   /*6S HERTFORD  230.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'RKYMT-WILS230_&_RKYMT-SHARPB115_SRT-S'
 OPEN BRANCH FROM BUS 304219 TO BUS 304223 CKT 1   /*3W-SHARPB    115.0 - 3ROCKYMT115T 115.0
 OPEN BRANCH FROM BUS 304222 TO BUS 304228 CKT 1   /*6ROCKYMT230T 230.0 - 6WILSON230 T 230.0
END
CONTINGENCY 'DVP_P1-2: LN 238_SRT-A-1'
 OPEN BRANCH FROM BUS 314282 TO BUS 314435 CKT 1   /*6CARSON      230.0 - 6SAPONY      230.0
 OPEN BRANCH FROM BUS 314435 TO BUS 940480 CKT 1   /*6SAPONY      230.0 - AE2-033 TP   230.0
 OPEN BUS 314435                                   /*6SAPONY      230.0
 OPEN BUS 316315                                   /*AB2-025 C    230.0
 OPEN BUS 923852                                   /*AB2-025 E    230.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314268 to 313802 ckt 1
314225 to 314227 ckt 1
314287 to 314260 ckt 1
314563 to 940480 ckt 1
314569 to 314575 ckt 1
314218 to 314908 ckt 2
314574 to 304451 ckt 1
313996 to 314268 ckt 1
314236 to 314218 ckt 1
314575 to 314537 ckt 1
313714 to 313885 ckt 1
313802 to 314692 ckt 1
314662 to 314651 ckt 1
314435 to 314282 ckt 1
314260 to 314225 ckt 1
313885 to 314662 ckt 1
314902 to 314914 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314911 to 313483 ckt 1
314914 to 314322 ckt 1
314923 to 314924 ckt 1
934320 to 313845 ckt 1
940480 to 314435 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 2201_SRT-A
OPAC112.45 %252.86B284.359.77
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC106.19 %661.76B702.741.34
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC108.87 %661.76B720.451.34
GD1DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S-1
OPAC111.78 %1058.16B1182.781.42
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC102.58 %661.76B678.861.34
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Base Case
OPAC104.11 %2442.12A2542.462.83

Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 2201_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.45 %
Rating:252.86 MVA
Rating Type:B
MVA to Mitigate:284.35
MW Contribution:9.77
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
958211AF2-115 C
Adder
0.840.714
936262AD2-033 E
Adder
4.4164705882352953.754
959311AF2-222 C
Adder
7.8188235294117656.646
925785AC1-054 E
50/50
2.0962.096
3145723EMPORIA
50/50
1.2311.231
316087AB2-174 C
50/50
2.8212.821
923573AB1-173 E OP
50/50
6.8126.812
919692AA2-053 E OP
50/50
3.1533.153
3156073AA1-063SOLA
50/50
0.9590.959
920042AA2-088 E OP
Adder
4.6305882352941183.936
964242AG1-285 E
Adder
4.7470588235294124.035
964792AG1-342 E
Adder
0.90352941176470590.768
924162AB2-060 E OP
50/50
2.5852.585
313527AB2-043 C
50/50
0.3160.316
962572AG1-106 E
Adder
0.52588235294117650.447
932632AC2-084 E
Adder
1.5435294117647061.312
926214AC1-099 E
Adder
0.57647058823529410.49
961792AG1-021 E
Adder
0.5717647058823530.486
962571AG1-106 C
Adder
1.20117647058823531.021
316274AC1-208 C
Adder
4.9105882352941184.174
918492AA1-063AE OP
50/50
2.7952.795
917332KELFORD E
Adder
0.63764705882352950.542
959312AF2-222 E
Adder
5.2388235294117654.453
3147223TWITTYS
Adder
0.46117647058823530.392
924022AB2-043 E O1
50/50
3.1813.181
924516AB2-100 E1
Adder
1.23882352941176471.053
966621AG1-532 C
50/50
4.3954.395
313506AB1-173 C OP
50/50
2.3342.334
961791AG1-021 C
Adder
0.67176470588235290.571
936261AD2-033 C
Adder
6.6258823529411775.632
962562AG1-105 E
Adder
2.48588235294117642.113
960081AF2-299 C
50/50
5.865.86
926072AC1-086 E
Adder
4.2270588235294123.593
958212AF2-115 E
Adder
0.71529411764705890.608
964241AG1-285 C
Adder
7.126.052
962561AG1-105 C
Adder
3.72941176470588243.17
960082AF2-299 E
50/50
3.9073.907
946281AF1-292 C
50/50
4.8514.851
926071AC1-086 C
Adder
9.2870588235294127.894
919710AA2-057 E
Adder
1.7070588235294121.451
3137643SOCKMAN
50/50
1.0011.001
946301AF1-294 C
Adder
1.38117647058823521.174
924517AB2-100 E2
Adder
1.23882352941176471.053
924302AB2-077 E O1
Adder
0.79529411764705890.676
3151281ROARAP4
50/50
1.091.09
3156063AA2-053SOLA
50/50
1.1211.121
900672V4-068 E
Adder
0.149411764705882360.127
925612AC1-036 E
Adder
0.41647058823529410.354
924312AB2-078 E O1
Adder
0.79529411764705890.676
3147043LAWRENC
50/50
0.740.74
316181AB2-040 GEN
50/50
2.6292.629
923263AB1-132 E OP
Adder
2.7023529411764712.297
946302AF1-294 E
Adder
1.16941176470588240.994
924322AB2-079 E O1
Adder
0.79529411764705890.676
316088AB2-174 E
50/50
15.67415.674
923994AB2-040_E
50/50
12.77312.773
927146AC1-208 E
Adder
2.18117647058823531.854
964791AG1-342 C
Adder
1.3564705882352941.153
926206AC1-098 E
Adder
1.7470588235294121.485
3138533PONTONDP
Adder
0.248235294117647050.211
316131AB2-060 C
50/50
0.8950.895
316129AC1-054 C
50/50
0.7410.741
946282AF1-292 E
50/50
3.2343.234
966622AG1-532 E
50/50
2.932.93
3151261ROARAP2
50/50
1.1521.152
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.7010.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.39311.393
CPLELTFEXP_CPLE->PJM
CLTF
1.471.47
TVALTFEXP_TVA->PJM
CLTF
0.7390.739
O66PJM->LTFIMP_O-066
CMTX_NF
2.1672.167
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3410.341
SIGELTFEXP_SIGE->PJM
CLTF
0.0330.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.4494.449
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.8192.819
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.5250.525
LAGNLTFEXP_LAGN->PJM
CLTF
0.9350.935
NYPJM->LTFIMP_NY
CLTF
0.1550.155
LGEELTFEXP_LGEE->PJM
CLTF
0.1740.174
WECLTFEXP_WEC->PJM
CLTF
0.0910.091

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.19 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:702.74
MW Contribution:1.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150831SPRUNCA
Adder
3.4141176470588242.902
3150841SPRUNCB
Adder
3.4141176470588242.902
316258AE1-075 C
50/50
0.4360.436
923862AB2-026 E
50/50
1.5431.543
941012AE2-092 E
50/50
11.34711.347
958211AF2-115 C
50/50
2.5362.536
936262AD2-033 E
50/50
7.7937.793
923852AB2-025 E
Adder
0.41764705882352940.355
941031AE2-094 C
Adder
14.76941176470588212.554
941032AE2-094 E
Adder
6.615294117647065.623
939412AE1-173 E
Adder
20.8635294117647117.734
940451AE2-029 C
Adder
-2.101176470588235-1.786
959311AF2-222 C
50/50
16.12516.125
925785AC1-054 E
Adder
1.72941176470588241.47
3145723EMPORIA
Adder
0.183529411764705890.156
923573AB1-173 E OP
Adder
1.38235294117647081.175
919692AA2-053 E OP
Adder
1.70470588235294131.449
938552AE1-074 E
Adder
0.58705882352941170.499
938562AE1-075 E
50/50
1.3151.315
932763AC2-100 E
Adder
1.14117647058823520.97
964242AG1-285 E
50/50
6.6676.667
964792AG1-342 E
50/50
1.4521.452
924162AB2-060 E OP
50/50
3.1523.152
313527AB2-043 C
50/50
0.3710.371
316405AF2-144 C
50/50
0.370.37
941011AE2-092 C
50/50
17.02117.021
961792AG1-021 E
50/50
1.7281.728
937482AD2-202 E
Adder
0.59882352941176480.509
918492AA1-063AE OP
Adder
1.62117647058823521.378
959312AF2-222 E
50/50
10.80310.803
3147223TWITTYS
50/50
0.8950.895
924022AB2-043 E O1
50/50
3.7383.738
924516AB2-100 E1
Adder
1.08941176470588250.926
966621AG1-532 C
Adder
0.60117647058823530.511
940642AE2-051 E
Adder
4.0647058823529413.455
924032AB2-045 E
50/50
2.7232.723
961791AG1-021 C
50/50
2.0282.028
936261AD2-033 C
50/50
11.6911.69
962562AG1-105 E
50/50
3.7423.742
963041AG1-153 C
Adder
2.1717647058823531.846
960081AF2-299 C
Adder
0.80117647058823540.681
944011AF1-069 C
Adder
4.8258823529411774.102
3144293JTRSVLE
50/50
0.4650.465
958212AF2-115 E
50/50
2.162.16
316034AC1-036 C
50/50
0.220.22
964241AG1-285 C
50/50
1010
962561AG1-105 C
50/50
5.6135.613
963042AG1-153 E
Adder
3.25764705882352962.769
960082AF2-299 E
Adder
0.53411764705882360.454
946281AF1-292 C
Adder
0.66352941176470580.564
933502AC2-165 E
50/50
10.89810.898
3151911BEARGRDN G1
50/50
12.47412.474
3137643SOCKMAN
Adder
0.296470588235294150.252
939411AE1-173 C
Adder
31.29411764705882626.6
958502AF2-144 E
50/50
1.5161.516
938822AE1-108 E
50/50
11.96911.969
942461AE2-259 C
50/50
13.72813.728
946301AF1-294 C
50/50
4.174.17
935172AD1-152 E
Adder
2.9870588235294122.539
934621AD1-088 C
50/50
6.3766.376
957482AF2-042 E
Adder
19.8305882352941216.856
924517AB2-100 E2
Adder
1.08941176470588250.926
958131AF2-107 C
50/50
3.6383.638
316322AB2-045 C
50/50
0.6050.605
316238AB2-078 C O1
50/50
0.2320.232
924302AB2-077 E O1
50/50
0.9480.948
938821AE1-108 C
50/50
25.08525.085
925612AC1-036 E
50/50
0.8080.808
926274AC1-105 E
Adder
1.54705882352941181.315
924312AB2-078 E O1
50/50
0.9480.948
940541AE2-040 C
Adder
1.03294117647058830.878
940481AE2-033 C
Adder
5.8647058823529424.985
940482AE2-033 E
Adder
3.9541176470588243.361
946302AF1-294 E
50/50
3.5313.531
943902AF1-058 E
Adder
0.69411764705882350.59
924322AB2-079 E O1
50/50
0.9480.948
957481AF2-042 C
Adder
29.74705882352941425.285
316088AB2-174 E
Adder
2.76235294117647052.348
923994AB2-040_E
Adder
2.5917647058823532.203
316336AC2-165 C
50/50
14.4814.48
3151931BEARGRDN S1
50/50
16.13716.137
927255AC1-221 E
Adder
1.70000000000000021.445
316237AB2-079 C O1
50/50
0.2320.232
934622AD1-088 E
50/50
3.073.07
934612AD1-087 E
Adder
2.04705882352941161.74
940641AE2-051 C
Adder
6.0976470588235295.183
316313AB2-026 C
50/50
0.4750.475
3151921BEARGRDN G2
50/50
12.47412.474
942462AE2-259 E
50/50
9.1529.152
964791AG1-342 C
50/50
2.1782.178
316239AB2-077 C O1
50/50
0.2320.232
316233AE1-074 C
Adder
1.16470588235294130.99
958132AF2-107 E
50/50
1.9941.994
3147133PAMPLIN
50/50
1.1881.188
927264AC1-222 E
Adder
2.12235294117647081.804
966622AG1-532 E
Adder
0.401176470588235360.341
3138533PONTONDP
50/50
0.7510.751
316131AB2-060 C
50/50
1.0911.091
946282AF1-292 E
Adder
0.44235294117647060.376
944012AF1-069 E
Adder
1.87411764705882341.593
316303AF2-085
50/50
2.082.08
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9351.935
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.59331.593
CPLELTFEXP_CPLE->PJM
CLTF
4.0634.063
TVALTFEXP_TVA->PJM
CLTF
1.461.46
O66PJM->LTFIMP_O-066
CMTX_NF
6.1316.131
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9570.957
SIGELTFEXP_SIGE->PJM
CLTF
0.030.03
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.2992.299
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.6554.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.5720.572
LAGNLTFEXP_LAGN->PJM
CLTF
1.8911.891
NYPJM->LTFIMP_NY
CLTF
0.4910.491
LGEELTFEXP_LGEE->PJM
CLTF
0.1180.118
WECLTFEXP_WEC->PJM
CLTF
0.0570.057

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.87 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:720.45
MW Contribution:1.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150831SPRUNCA
Adder
3.4141176470588242.902
3150841SPRUNCB
Adder
3.4141176470588242.902
316258AE1-075 C
50/50
0.4360.436
923862AB2-026 E
50/50
1.5431.543
941012AE2-092 E
50/50
11.34711.347
958211AF2-115 C
50/50
2.5362.536
936262AD2-033 E
50/50
7.7937.793
923852AB2-025 E
Adder
0.41764705882352940.355
941031AE2-094 C
Adder
14.76941176470588212.554
941032AE2-094 E
Adder
6.615294117647065.623
939412AE1-173 E
Adder
20.8635294117647117.734
940451AE2-029 C
Adder
-2.101176470588235-1.786
959311AF2-222 C
50/50
16.12516.125
925785AC1-054 E
Adder
1.72941176470588241.47
3145723EMPORIA
Adder
0.183529411764705890.156
923573AB1-173 E OP
Adder
1.38235294117647081.175
919692AA2-053 E OP
Adder
1.70470588235294131.449
938552AE1-074 E
Adder
0.58705882352941170.499
938562AE1-075 E
50/50
1.3151.315
932763AC2-100 E
Adder
1.14117647058823520.97
964242AG1-285 E
50/50
6.6676.667
964792AG1-342 E
50/50
1.4521.452
924162AB2-060 E OP
50/50
3.1523.152
313527AB2-043 C
50/50
0.3710.371
316405AF2-144 C
50/50
0.370.37
941011AE2-092 C
50/50
17.02117.021
961792AG1-021 E
50/50
1.7281.728
937482AD2-202 E
Adder
0.59882352941176480.509
918492AA1-063AE OP
Adder
1.62117647058823521.378
959312AF2-222 E
50/50
10.80310.803
3147223TWITTYS
50/50
0.8950.895
924022AB2-043 E O1
50/50
3.7383.738
924516AB2-100 E1
Adder
1.08941176470588250.926
966621AG1-532 C
Adder
0.60117647058823530.511
940642AE2-051 E
Adder
4.0647058823529413.455
924032AB2-045 E
50/50
2.7232.723
961791AG1-021 C
50/50
2.0282.028
936261AD2-033 C
50/50
11.6911.69
962562AG1-105 E
50/50
3.7423.742
963041AG1-153 C
Adder
2.1717647058823531.846
960081AF2-299 C
Adder
0.80117647058823540.681
944011AF1-069 C
Adder
4.8258823529411774.102
3144293JTRSVLE
50/50
0.4650.465
958212AF2-115 E
50/50
2.162.16
316034AC1-036 C
50/50
0.220.22
964241AG1-285 C
50/50
1010
962561AG1-105 C
50/50
5.6135.613
963042AG1-153 E
Adder
3.25764705882352962.769
960082AF2-299 E
Adder
0.53411764705882360.454
946281AF1-292 C
Adder
0.66352941176470580.564
933502AC2-165 E
50/50
10.89810.898
3151911BEARGRDN G1
50/50
12.47412.474
3137643SOCKMAN
Adder
0.296470588235294150.252
939411AE1-173 C
Adder
31.29411764705882626.6
958502AF2-144 E
50/50
1.5161.516
938822AE1-108 E
50/50
11.96911.969
942461AE2-259 C
50/50
13.72813.728
946301AF1-294 C
50/50
4.174.17
935172AD1-152 E
Adder
2.9870588235294122.539
934621AD1-088 C
50/50
6.3766.376
957482AF2-042 E
Adder
19.8305882352941216.856
924517AB2-100 E2
Adder
1.08941176470588250.926
958131AF2-107 C
50/50
3.6383.638
316322AB2-045 C
50/50
0.6050.605
316238AB2-078 C O1
50/50
0.2320.232
924302AB2-077 E O1
50/50
0.9480.948
938821AE1-108 C
50/50
25.08525.085
925612AC1-036 E
50/50
0.8080.808
926274AC1-105 E
Adder
1.54705882352941181.315
924312AB2-078 E O1
50/50
0.9480.948
940541AE2-040 C
Adder
1.03294117647058830.878
940481AE2-033 C
Adder
5.8647058823529424.985
940482AE2-033 E
Adder
3.9541176470588243.361
946302AF1-294 E
50/50
3.5313.531
943902AF1-058 E
Adder
0.69411764705882350.59
924322AB2-079 E O1
50/50
0.9480.948
957481AF2-042 C
Adder
29.74705882352941425.285
316088AB2-174 E
Adder
2.76235294117647052.348
923994AB2-040_E
Adder
2.5917647058823532.203
316336AC2-165 C
50/50
14.4814.48
3151931BEARGRDN S1
50/50
16.13716.137
927255AC1-221 E
Adder
1.70000000000000021.445
316237AB2-079 C O1
50/50
0.2320.232
934622AD1-088 E
50/50
3.073.07
934612AD1-087 E
Adder
2.04705882352941161.74
940641AE2-051 C
Adder
6.0976470588235295.183
316313AB2-026 C
50/50
0.4750.475
3151921BEARGRDN G2
50/50
12.47412.474
942462AE2-259 E
50/50
9.1529.152
964791AG1-342 C
50/50
2.1782.178
316239AB2-077 C O1
50/50
0.2320.232
316233AE1-074 C
Adder
1.16470588235294130.99
958132AF2-107 E
50/50
1.9941.994
3147133PAMPLIN
50/50
1.1881.188
927264AC1-222 E
Adder
2.12235294117647081.804
966622AG1-532 E
Adder
0.401176470588235360.341
3138533PONTONDP
50/50
0.7510.751
316131AB2-060 C
50/50
1.0911.091
946282AF1-292 E
Adder
0.44235294117647060.376
944012AF1-069 E
Adder
1.87411764705882341.593
316303AF2-085
50/50
2.082.08
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9351.935
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.59331.593
CPLELTFEXP_CPLE->PJM
CLTF
4.0634.063
TVALTFEXP_TVA->PJM
CLTF
1.461.46
O66PJM->LTFIMP_O-066
CMTX_NF
6.1316.131
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9570.957
SIGELTFEXP_SIGE->PJM
CLTF
0.030.03
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.2992.299
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.6554.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.5720.572
LAGNLTFEXP_LAGN->PJM
CLTF
1.8911.891
NYPJM->LTFIMP_NY
CLTF
0.4910.491
LGEELTFEXP_LGEE->PJM
CLTF
0.1180.118
WECLTFEXP_WEC->PJM
CLTF
0.0570.057

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.78 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1182.78
MW Contribution:1.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316076AC2-137 E
Adder
0.73529411764705890.625
966871AG1-558 C
Adder
1.27764705882352961.086
966872AG1-558 E
Adder
0.64352941176470590.547
3150831SPRUNCA
50/50
9.4469.446
3150841SPRUNCB
50/50
9.4469.446
316258AE1-075 C
50/50
0.5110.511
923862AB2-026 E
50/50
1.8081.808
941012AE2-092 E
Adder
4.6305882352941183.936
958211AF2-115 C
Adder
1.21529411764705891.033
936262AD2-033 E
Adder
4.3329411764705883.683
923852AB2-025 E
Adder
0.54941176470588240.467
941031AE2-094 C
Adder
15.98588235294117513.588
941032AE2-094 E
Adder
7.166.086
939412AE1-173 E
Adder
24.89294117647058621.159
916192Z1-068 E
Adder
0.820.697
926662AC1-147 E
Adder
0.58117647058823530.494
957492AF2-043 E
Adder
0.62470588235294120.531
923842AB2-024 E
Adder
0.82235294117647050.699
316157AD2-030 E
Adder
0.53411764705882360.454
944641AF1-129 C
Adder
65.7211764705882355.863
316240AF1-291 C
Adder
1.36588235294117651.161
959311AF2-222 C
Adder
8.5341176470588237.254
3145723EMPORIA
Adder
0.196470588235294150.167
923573AB1-173 E OP
Adder
1.47764705882352951.256
919692AA2-053 E OP
Adder
1.86823529411764721.588
924814AB2-134 E
Adder
6.8847058823529425.852
920042AA2-088 E OP
Adder
4.724.012
942342AE2-247 E
Adder
0.98470588235294120.837
919152AA1-139 E1
Adder
1.7717647058823531.506
944631AF1-128 C
Adder
24.6823529411764720.98
3150851SPRUNCC
50/50
0.1690.169
938552AE1-074 E
50/50
1.8811.881
938562AE1-075 E
50/50
1.5421.542
964242AG1-285 E
Adder
4.0211764705882363.418
924162AB2-060 E OP
Adder
2.0117647058823531.71
962572AG1-106 E
Adder
0.52705882352941180.448
316160AE1-175 E
Adder
0.54117647058823540.46
933291AC2-141 C
Adder
12.51176470588235310.635
926755AC1-161 E
Adder
0.59529411764705890.506
957872AF2-081 E
Adder
1.85647058823529431.578
925522AC1-027 E
Adder
0.53176470588235290.452
941102AE2-104 E
Adder
2.39764705882352922.038
3145256KINGFORK
Adder
0.455294117647058850.387
3150921YORKTN3
Adder
52.8152941176470644.893
3150861SPRUNCD
50/50
0.1690.169
316405AF2-144 C
50/50
0.4340.434
3150651CHESTF6
Adder
11.96588235294117610.171
946262AF1-291 E
Adder
0.91058823529411770.774
941011AE2-092 C
Adder
6.9470588235294125.905
961792AG1-021 E
Adder
0.82823529411764710.704
937482AD2-202 E
Adder
0.456470588235294130.388
962571AG1-106 C
Adder
1.20352941176470571.023
934576AD1-082 E
Adder
2.2917647058823531.948
918492AA1-063AE OP
Adder
1.8117647058823531.54
940492AE2-034 E
Adder
1.33882352941176451.138
944602AF1-125 E
Adder
43.9588235294117737.365
957871AF2-081 C
Adder
4.3329411764705883.683
3145506HICKORY
Adder
0.94470588235294130.803
943612AF1-032 E
Adder
0.405882352941176470.345
3130536PAPERMILL
Adder
3.0341176470588242.579
939602AE1-190 E
Adder
0.6517647058823530.554
926412AC1-112 E
Adder
0.56470588235294120.48
959312AF2-222 E
Adder
5.71764705882352954.86
3147223TWITTYS
Adder
0.48235294117647060.41
924022AB2-043 E O1
Adder
2.4235294117647062.06
924516AB2-100 E1
Adder
1.32117647058823541.123
966621AG1-532 C
Adder
0.63882352941176480.543
940642AE2-051 E
Adder
4.67764705882352953.976
943462AF1-017 E
Adder
1.0517647058823530.894
942341AE2-247 C
Adder
0.71294117647058820.606
919153AA1-139 E2
Adder
1.7717647058823531.506
958162AF2-110 E
Adder
0.97882352941176460.832
3150601CHESTF5
Adder
39.4470588235294233.53
924032AB2-045 E
Adder
0.94941176470588240.807
961791AG1-021 C
Adder
0.97294117647058820.827
936261AD2-033 C
Adder
6.5000000000000015.525
925332AB2-190 E
Adder
4.5752941176470593.889
963041AG1-153 C
Adder
2.2623529411764711.923
960081AF2-299 C
Adder
0.8517647058823530.724
944011AF1-069 C
Adder
5.2235294117647074.44
926072AC1-086 E
Adder
4.2364705882352943.601
927226AC1-216 E
Adder
4.20352941176470553.573
3145413WATKINS
Adder
0.30941176470588240.263
936666AD2-085 E
Adder
2.6835294117647062.281
962962AG1-145 E
Adder
0.65529411764705890.557
938771AE1-103 C
Adder
1.3117647058823531.115
944601AF1-125 C
Adder
19.2023529411764716.322
944591AF1-124 C
Adder
19.5717647058823516.636
941591AE2-156 C
Adder
7.8529411764705886.675
316169AC1-164 GEN
Adder
19.79647058823529816.827
930122AB1-027 E
Adder
0.69529411764705880.591
958212AF2-115 E
Adder
1.0352941176470590.88
964241AG1-285 C
Adder
6.0305882352941185.126
963042AG1-153 E
Adder
3.39411764705882352.885
960082AF2-299 E
Adder
0.56823529411764710.483
946281AF1-292 C
Adder
0.70588235294117650.6
926071AC1-086 C
Adder
9.3082352941176477.912
316349AD2-085 C
Adder
1.6447058823529411.398
938772AE1-103 E
Adder
1.8117647058823531.54
916042Z1-036 E
Adder
12.43647058823529310.571
944582AF1-123 E
Adder
44.6637.961
944592AF1-124 E
Adder
44.82117647058823538.098
923832AB2-022 E
Adder
0.53882352941176470.458
935112AD1-144 E
Adder
0.42235294117647060.359
933502AC2-165 E
50/50
10.19910.199
940432AE2-027 E
Adder
5.3129411764705894.516
3137643SOCKMAN
Adder
0.317647058823529450.27
939411AE1-173 C
Adder
37.3388235294117631.738
934012AD1-025 E
Adder
5.44117647058823554.625
913392Y1-086 E
Adder
0.9552941176470590.812
939612AE1-191 E
Adder
2.6082352941176472.217
957602AF2-054 E
Adder
0.63529411764705890.54
958502AF2-144 E
50/50
1.7771.777
938822AE1-108 E
Adder
4.0211764705882363.418
942001AE2-212 C
Adder
1.3035294117647061.108
942461AE2-259 C
Adder
5.83647058823529454.961
946301AF1-294 C
Adder
1.99882352941176491.699
939192AE1-149 E
Adder
3.93176470588235333.342
934621AD1-088 C
Adder
4.3294117647058833.68
957482AF2-042 E
Adder
15.4776470588235313.156
924517AB2-100 E2
Adder
1.32117647058823541.123
937226AE2-253 E
Adder
2.53176470588235342.152
934065AD1-033 E
Adder
2.1752941176470591.849
939312AE1-162 E
Adder
0.67999999999999990.578
3150731STONECA
Adder
4.1494117647058823.527
924302AB2-077 E O1
Adder
0.62117647058823530.528
935161AD1-151 C
Adder
8.9764705882352947.63
900672V4-068 E
Adder
0.157647058823529420.134
3145393UNCAMP
Adder
2.72117647058823582.313
938531AE1-072 C
Adder
7.6223529411764716.479
932046AC2-012 E
Adder
5.7529411764705884.89
958161AF2-110 C
Adder
0.61529411764705890.523
3138116ELKO L286
Adder
0.76588235294117660.651
927041AC1-191 C
Adder
5.1282352941176474.359
938821AE1-108 C
Adder
8.4270588235294127.163
925612AC1-036 E
Adder
0.435294117647058830.37
924312AB2-078 E O1
Adder
0.62117647058823530.528
940541AE2-040 C
Adder
1.35764705882352941.154
940481AE2-033 C
Adder
7.6223529411764716.479
940482AE2-033 E
Adder
5.13882352941176554.368
923263AB1-132 E OP
Adder
2.70941176470588242.303
961611AG1-000B C
Adder
8.1152941176470596.898
942002AE2-212 E
Adder
0.86941176470588230.739
946302AF1-294 E
Adder
1.69294117647058841.439
940431AE2-027 C
Adder
7.9682352941176476.773
924322AB2-079 E O1
Adder
0.62117647058823530.528
957481AF2-042 C
Adder
23.21647058823529619.734
316088AB2-174 E
Adder
2.94705882352941152.505
923994AB2-040_E
Adder
2.76941176470588252.354
944581AF1-123 C
Adder
19.50352941176470616.578
941101AE2-104 C
Adder
1.50823529411764711.282
934392AD1-063 E
Adder
0.487058823529411770.414
926785AC1-164_E
Adder
8.8941176470588247.56
316336AC2-165 C
50/50
13.55213.552
934622AD1-088 E
Adder
2.08470588235294141.772
934612AD1-087 E
Adder
1.55882352941176471.325
316084AB2-161 E
Adder
2.8764705882352942.445
940641AE2-051 C
Adder
7.0152941176470595.963
943471AF1-018 C
Adder
3.25058823529411762.763
3143096IRON208
50/50
0.330.33
316313AB2-026 C
50/50
0.5570.557
3143316POE
Adder
0.75647058823529410.643
942462AE2-259 E
Adder
3.8917647058823533.308
939191AE1-149 C
Adder
5.8976470588235295.013
901082W1-029 E
Adder
13.8976470588235311.813
934146AD1-041 E
Adder
1.63058823529411771.386
957601AF2-054 C
Adder
0.95294117647058830.81
3138533PONTONDP
Adder
0.360.306
946282AF1-292 E
Adder
0.47058823529411770.4
927042AC1-191 E
Adder
2.55411764705882362.171
316233AE1-074 C
50/50
3.7333.733
3147133PAMPLIN
Adder
0.54941176470588240.467
966622AG1-532 E
Adder
0.42588235294117650.362
935162AD1-151 E
Adder
5.9847058823529415.087
943461AF1-017 C
Adder
0.64470588235294120.548
932596AC2-079 E
Adder
4.4376470588235293.772
316311AC2-079 C
Adder
2.71999999999999982.312
920692AA2-178 E
Adder
1.78588235294117651.518
917122Z2-027 E
Adder
0.58470588235294120.497
3146326AYDLETT TAP
Adder
0.58823529411764710.5
938532AE1-072 E
Adder
3.9729411764705883.377
940551AE2-041 C
Adder
3.25058823529411762.763
957832AF2-077 E
Adder
0.63529411764705890.54
944012AF1-069 E
Adder
2.02941176470588271.725
925865AC1-065 E
Adder
7.73058823529411756.571
316303AF2-085
50/50
7.0277.027
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.2422.242
CBM South 2LTFEXP_CBM-S2->PJM
CBM
40.62940.629
CPLELTFEXP_CPLE->PJM
CLTF
4.6984.698
TVALTFEXP_TVA->PJM
CLTF
2.952.95
O66PJM->LTFIMP_O-066
CMTX_NF
13.41813.418
G-007PJM->LTFIMP_G-007
CMTX_NF
2.112.11
SIGELTFEXP_SIGE->PJM
CLTF
0.1370.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.08118.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.29711.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1322.132
LAGNLTFEXP_LAGN->PJM
CLTF
3.6953.695
NYPJM->LTFIMP_NY
CLTF
0.9630.963
LGEELTFEXP_LGEE->PJM
CLTF
0.7270.727
WECLTFEXP_WEC->PJM
CLTF
0.3730.373

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.58 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:678.86
MW Contribution:1.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150831SPRUNCA
Adder
3.4141176470588242.902
3150841SPRUNCB
Adder
3.4141176470588242.902
316258AE1-075 C
50/50
0.4360.436
923862AB2-026 E
50/50
1.5431.543
941012AE2-092 E
50/50
11.34711.347
958211AF2-115 C
50/50
2.5362.536
936262AD2-033 E
50/50
7.7937.793
923852AB2-025 E
Adder
0.41764705882352940.355
941031AE2-094 C
Adder
14.76941176470588212.554
941032AE2-094 E
Adder
6.615294117647065.623
939412AE1-173 E
Adder
20.8635294117647117.734
940451AE2-029 C
Adder
-2.101176470588235-1.786
959311AF2-222 C
50/50
16.12516.125
925785AC1-054 E
Adder
1.72941176470588241.47
3145723EMPORIA
Adder
0.183529411764705890.156
923573AB1-173 E OP
Adder
1.38235294117647081.175
919692AA2-053 E OP
Adder
1.70470588235294131.449
938552AE1-074 E
Adder
0.58705882352941170.499
938562AE1-075 E
50/50
1.3151.315
932763AC2-100 E
Adder
1.14117647058823520.97
964242AG1-285 E
50/50
6.6676.667
964792AG1-342 E
50/50
1.4521.452
924162AB2-060 E OP
50/50
3.1523.152
313527AB2-043 C
50/50
0.3710.371
316405AF2-144 C
50/50
0.370.37
941011AE2-092 C
50/50
17.02117.021
961792AG1-021 E
50/50
1.7281.728
937482AD2-202 E
Adder
0.59882352941176480.509
918492AA1-063AE OP
Adder
1.62117647058823521.378
959312AF2-222 E
50/50
10.80310.803
3147223TWITTYS
50/50
0.8950.895
924022AB2-043 E O1
50/50
3.7383.738
924516AB2-100 E1
Adder
1.08941176470588250.926
966621AG1-532 C
Adder
0.60117647058823530.511
940642AE2-051 E
Adder
4.0647058823529413.455
924032AB2-045 E
50/50
2.7232.723
961791AG1-021 C
50/50
2.0282.028
936261AD2-033 C
50/50
11.6911.69
962562AG1-105 E
50/50
3.7423.742
963041AG1-153 C
Adder
2.1717647058823531.846
960081AF2-299 C
Adder
0.80117647058823540.681
944011AF1-069 C
Adder
4.8258823529411774.102
3144293JTRSVLE
50/50
0.4650.465
958212AF2-115 E
50/50
2.162.16
316034AC1-036 C
50/50
0.220.22
964241AG1-285 C
50/50
1010
962561AG1-105 C
50/50
5.6135.613
963042AG1-153 E
Adder
3.25764705882352962.769
960082AF2-299 E
Adder
0.53411764705882360.454
946281AF1-292 C
Adder
0.66352941176470580.564
933502AC2-165 E
50/50
10.89810.898
3151911BEARGRDN G1
50/50
12.47412.474
3137643SOCKMAN
Adder
0.296470588235294150.252
939411AE1-173 C
Adder
31.29411764705882626.6
958131AF2-107 C
50/50
3.6383.638
316322AB2-045 C
50/50
0.6050.605
316238AB2-078 C O1
50/50
0.2320.232
924302AB2-077 E O1
50/50
0.9480.948
938821AE1-108 C
50/50
25.08525.085
925612AC1-036 E
50/50
0.8080.808
926274AC1-105 E
Adder
1.54705882352941181.315
924312AB2-078 E O1
50/50
0.9480.948
940541AE2-040 C
Adder
1.03294117647058830.878
940481AE2-033 C
Adder
5.8647058823529424.985
940482AE2-033 E
Adder
3.9541176470588243.361
316336AC2-165 C
50/50
14.4814.48
3151931BEARGRDN S1
50/50
16.13716.137
927255AC1-221 E
Adder
1.70000000000000021.445
316237AB2-079 C O1
50/50
0.2320.232
934622AD1-088 E
50/50
3.073.07
934612AD1-087 E
Adder
2.04705882352941161.74
940641AE2-051 C
Adder
6.0976470588235295.183
958502AF2-144 E
50/50
1.5161.516
938822AE1-108 E
50/50
11.96911.969
942461AE2-259 C
50/50
13.72813.728
946301AF1-294 C
50/50
4.174.17
935172AD1-152 E
Adder
2.9870588235294122.539
934621AD1-088 C
50/50
6.3766.376
957482AF2-042 E
Adder
19.8305882352941216.856
924517AB2-100 E2
Adder
1.08941176470588250.926
946302AF1-294 E
50/50
3.5313.531
943902AF1-058 E
Adder
0.69411764705882350.59
924322AB2-079 E O1
50/50
0.9480.948
957481AF2-042 C
Adder
29.74705882352941425.285
316088AB2-174 E
Adder
2.76235294117647052.348
923994AB2-040_E
Adder
2.5917647058823532.203
316313AB2-026 C
50/50
0.4750.475
3151921BEARGRDN G2
50/50
12.47412.474
942462AE2-259 E
50/50
9.1529.152
964791AG1-342 C
50/50
2.1782.178
316239AB2-077 C O1
50/50
0.2320.232
316233AE1-074 C
Adder
1.16470588235294130.99
958132AF2-107 E
50/50
1.9941.994
3147133PAMPLIN
50/50
1.1881.188
927264AC1-222 E
Adder
2.12235294117647081.804
966622AG1-532 E
Adder
0.401176470588235360.341
3138533PONTONDP
50/50
0.7510.751
316131AB2-060 C
50/50
1.0911.091
946282AF1-292 E
Adder
0.44235294117647060.376
944012AF1-069 E
Adder
1.87411764705882341.593
316303AF2-085
50/50
2.082.08
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9351.935
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.59331.593
CPLELTFEXP_CPLE->PJM
CLTF
4.0634.063
TVALTFEXP_TVA->PJM
CLTF
1.461.46
O66PJM->LTFIMP_O-066
CMTX_NF
6.1316.131
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9570.957
SIGELTFEXP_SIGE->PJM
CLTF
0.030.03
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.2992.299
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.6554.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.5720.572
LAGNLTFEXP_LAGN->PJM
CLTF
1.8911.891
NYPJM->LTFIMP_NY
CLTF
0.4910.491
LGEELTFEXP_LGEE->PJM
CLTF
0.1180.118
WECLTFEXP_WEC->PJM
CLTF
0.0570.057

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.11 %
Rating:2442.12 MVA
Rating Type:A
MVA to Mitigate:2542.46
MW Contribution:2.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
964211AG1-282 C
Adder
2.5270588235294122.148
316076AC2-137 E
Adder
1.53647058823529431.306
923852AB2-025 E
Adder
1.040.884
941031AE2-094 C
Adder
35.2988235294117730.004
941032AE2-094 E
Adder
15.80941176470588313.438
927022AC1-189 E
Adder
4.1023529411764713.487
939412AE1-173 E
Adder
67.656470588235357.508
961942AG1-037 E
Adder
0.370588235294117660.315
961941AG1-037 C
Adder
0.55529411764705880.472
916192Z1-068 E
50/50
2.672.67
3151081ELIZAR1
50/50
4.5444.544
926662AC1-147 E
50/50
1.8821.882
957492AF2-043 E
Adder
1.9635294117647061.669
923842AB2-024 E
50/50
2.4762.476
316157AD2-030 E
Adder
1.6270588235294121.383
939246AE1-155 E
Adder
11.1941176470588259.515
3145723EMPORIA
Adder
0.39411764705882360.335
923573AB1-173 E OP
Adder
3.06235294117647072.603
919692AA2-053 E OP
Adder
4.1705882352941183.545
924814AB2-134 E
Adder
14.67647058823529312.475
920042AA2-088 E OP
Adder
11.93294117647058910.143
934511AD1-075 C
Adder
10.102352941176478.587
934521AD1-076 C
Adder
14.67647058823529312.475
942342AE2-247 E
Adder
2.54235294117647072.161
919152AA1-139 E1
50/50
5.7365.736
316036AC1-147 C
50/50
0.5220.522
936592AD2-074 E
Adder
11.85764705882353110.079
944631AF1-128 C
Adder
41.73529411764706535.475
962572AG1-106 E
Adder
1.140.969
932632AC2-084 E
Adder
3.17764705882352952.701
926214AC1-099 E
Adder
1.18705882352941171.009
316160AE1-175 E
50/50
1.8321.832
933291AC2-141 C
50/50
47.35447.354
926755AC1-161 E
50/50
20.21420.214
957872AF2-081 E
50/50
6.0126.012
316018AA1-139 ULT2
50/50
1.5131.513
925522AC1-027 E
50/50
1.7291.729
941102AE2-104 E
Adder
7.0717647058823536.011
3145256KINGFORK
50/50
1.4051.405
3150921YORKTN3
50/50
185.501185.501
936591AD2-074 C
Adder
7.2670588235294116.177
962571AG1-106 C
Adder
2.60588235294117652.215
316274AC1-208 C
Adder
8.6647058823529427.365
934576AD1-082 E
Adder
4.80941176470588254.088
918492AA1-063AE OP
Adder
4.17764705882352953.551
917332KELFORD E
Adder
1.74000000000000021.479
925122AB2-169 E
Adder
6.3976470588235295.438
943172AE2-346 E
Adder
0.66705882352941170.567
934522AD1-076 E
Adder
7.48117647058823556.359
933292AC2-141 E
50/50
20.21420.214
940492AE2-034 E
Adder
3.8317647058823533.257
944602AF1-125 E
50/50
147.882147.882
957871AF2-081 C
50/50
14.02714.027
3145506HICKORY
50/50
3.0893.089
943612AF1-032 E
Adder
1.2764705882352941.085
3130536PAPERMILL
50/50
9.1469.146
939602AE1-190 E
Adder
1.9247058823529411.636
963612AG1-210 E
Adder
1.23058823529411781.046
924516AB2-100 E1
Adder
2.6788235294117652.277
966621AG1-532 C
Adder
1.27294117647058851.082
940642AE2-051 E
Adder
11.79999999999999910.03
918532AA1-067 E
Adder
0.72588235294117650.617
918512AA1-065 E OP
Adder
6.2364705882352955.301
934502AD1-074 E
Adder
20.57176470588235517.486
934512AD1-075 E
Adder
5.1435294117647064.372
943462AF1-017 E
Adder
2.71882352941176462.311
942341AE2-247 C
Adder
1.84117647058823521.565
316159AE1-175 C
50/50
0.6010.601
919153AA1-139 E2
50/50
5.7365.736
316388AE2-253 GEN
50/50
2.7582.758
958162AF2-110 E
Adder
2.8870588235294122.454
964212AG1-282 E
Adder
1.6847058823529411.432
3150601CHESTF5
Adder
66.756.695
925332AB2-190 E
Adder
8.8411764705882367.515
963041AG1-153 C
Adder
4.884.148
960081AF2-299 C
Adder
1.69647058823529421.442
944011AF1-069 C
Adder
11.532941176470599.803
926072AC1-086 E
Adder
9.1682352941176477.793
957862AF2-080 E
Adder
3.3152941176470592.818
927226AC1-216 E
Adder
8.9599999999999997.616
3145413WATKINS
Adder
0.82235294117647050.699
936666AD2-085 E
Adder
6.9317647058823545.892
962962AG1-145 E
50/50
2.2212.221
938771AE1-103 C
Adder
3.62470588235294143.081
944601AF1-125 C
50/50
64.664.6
944591AF1-124 C
50/50
65.84465.844
3151101ELIZAR3
50/50
4.6014.601
941591AE2-156 C
50/50
25.46125.461
316169AC1-164 GEN
50/50
57.50657.506
963042AG1-153 E
Adder
7.3188235294117656.221
960082AF2-299 E
Adder
1.13058823529411770.961
946281AF1-292 C
Adder
1.40470588235294121.194
926071AC1-086 C
Adder
20.14470588235294517.123
927021AC1-189 C
Adder
8.235294117647067
316349AD2-085 C
Adder
4.2482352941176483.611
938772AE1-103 E
Adder
5.00588235294117644.255
916042Z1-036 E
Adder
37.13529411764706431.565
944582AF1-123 E
50/50
150.24150.24
944592AF1-124 E
50/50
150.785150.785
923832AB2-022 E
Adder
1.7070588235294121.451
3151091ELIZAR2
50/50
4.4644.464
935112AD1-144 E
50/50
1.3041.304
316314AB2-024 C
50/50
0.4030.403
966661AG1-536 C
Adder
6.91529411764705955.878
958262AF2-120 E
Adder
5.3588235294117644.555
316078AC2-138 E
Adder
1.1482352941176470.976
940432AE2-027 E
Adder
3.88235294117647063.3
3137643SOCKMAN
Adder
0.6764705882352940.575
939411AE1-173 C
Adder
101.4858823529411986.263
934012AD1-025 E
Adder
11.69.86
913392Y1-086 E
Adder
3.0235294117647062.57
3150991CHESPKB
50/50
1.0231.023
939612AE1-191 E
Adder
7.76.545
957602AF2-054 E
Adder
1.93294117647058841.643
943741AF1-042 C
Adder
3.8023529411764713.232
962861AG1-135 C
Adder
7.8329411764705896.658
3141813NORNECK
Adder
1.09294117647058830.929
3150731STONECA
Adder
6.8694117647058835.839
935161AD1-151 C
Adder
18.1615.436
900672V4-068 E
Adder
0.395294117647058850.336
933981AD1-022 C
Adder
10.3435294117647068.792
3145393UNCAMP
Adder
7.4105882352941186.299
938531AE1-072 C
50/50
24.57324.573
932046AC2-012 E
50/50
18.61318.613
958161AF2-110 C
Adder
1.81529411764705871.543
963611AG1-210 C
Adder
0.820.697
3138116ELKO L286
Adder
1.60117647058823541.361
940541AE2-040 C
Adder
2.5717647058823532.186
940481AE2-033 C
Adder
14.5623529411764712.378
940482AE2-033 E
Adder
9.817647058823538.345
923263AB1-132 E OP
Adder
5.86235294117647054.983
316375AC2-012 C
50/50
1.9131.913
961611AG1-000B C
Adder
20.0529411764705917.045
316072AD1-144 C
50/50
0.3890.389
316059AD1-063 C
50/50
0.360.36
957831AF2-077 C
50/50
0.4830.483
943742AF1-042 E
Adder
6.20470588235294155.274
962862AG1-135 E
Adder
5.2211764705882354.438
966662AG1-536 E
Adder
9.2917647058823527.898
940431AE2-027 C
Adder
10.9364705882352939.296
316088AB2-174 E
Adder
6.03294117647058855.128
923994AB2-040_E
Adder
5.7423529411764714.881
316141AB2-099 E
Adder
0.27764705882352940.236
926472AC1-118 E
Adder
1.13411764705882350.964
926785AC1-164_E
50/50
25.83625.836
927146AC1-208 E
Adder
3.8470588235294123.27
316084AB2-161 E
Adder
6.0352941176470595.13
940641AE2-051 C
Adder
17.715.045
933982AD1-022 E
Adder
5.6317647058823534.787
3145946PLYMOUTH TP
Adder
0.38941176470588240.331
316017AA1-139 ULT1
50/50
1.5131.513
943471AF1-018 C
Adder
9.8305882352941178.356
939192AE1-149 E
Adder
7.1047058823529416.039
924517AB2-100 E2
Adder
2.6788235294117652.277
934501AD1-074 C
Adder
40.41176470588235534.35
937226AE2-253 E
50/50
8.238.23
934065AD1-033 E
50/50
7.137.13
939312AE1-162 E
Adder
1.9235294117647061.635
316294AC1-161 C
50/50
7.7117.711
944581AF1-123 C
50/50
65.6165.61
316185AD1-033 C
50/50
1.7411.741
916191Z1-068 C
50/50
0.0620.062
941101AE2-104 C
Adder
4.4482352941176473.781
934392AD1-063 E
50/50
1.4751.475
958261AF2-120 C
Adder
8.0388235294117656.833
3143316POE
Adder
1.19294117647058821.014
939191AE1-149 C
Adder
10.6576470588235289.059
926206AC1-098 E
Adder
3.5952941176470593.056
316382AG1-145 C
50/50
0.5420.542
901082W1-029 E
Adder
43.0176470588235336.565
3150981CHESPKA
50/50
0.6170.617
934146AD1-041 E
Adder
4.8129411764705894.091
957601AF2-054 C
Adder
2.92.465
966622AG1-532 E
Adder
0.84823529411764710.721
935162AD1-151 E
Adder
12.10588235294117610.29
943461AF1-017 C
Adder
1.66588235294117641.416
932596AC2-079 E
Adder
11.6588235294117669.91
316311AC2-079 C
Adder
7.1458823529411766.074
920692AA2-178 E
Adder
5.1082352941176474.342
3152331SURRY 2
50/50
43.89143.891
917122Z2-027 E
Adder
1.83411764705882341.559
3146326AYDLETT TAP
50/50
1.8931.893
938532AE1-072 E
50/50
12.8112.81
940551AE2-041 C
Adder
9.8305882352941178.356
957832AF2-077 E
50/50
2.0912.091
961951AG1-038 C
Adder
4.20352941176470553.573
961952AG1-038 E
Adder
5.8035294117647064.933
936582AD2-073 E
Adder
1.23176470588235291.047
946282AF1-292 E
Adder
0.93647058823529420.796
944012AF1-069 E
Adder
4.47999999999999953.808
957861AF2-080 C
Adder
7.47999999999999956.358
316316AC1-027 C
50/50
0.4470.447
3144216WINCHST
50/50
0.20.2
925865AC1-065 E
Adder
22.29058823529411618.947
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.274.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
70.8670.86
CPLELTFEXP_CPLE->PJM
CLTF
8.9638.963
TVALTFEXP_TVA->PJM
CLTF
3.7783.778
O66PJM->LTFIMP_O-066
CMTX_NF
17.37617.376
G-007PJM->LTFIMP_G-007
CMTX_NF
2.7242.724
SIGELTFEXP_SIGE->PJM
CLTF
0.1170.117
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.05913.059
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.06213.062
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.9921.992
LAGNLTFEXP_LAGN->PJM
CLTF
4.854.85
NYPJM->LTFIMP_NY
CLTF
1.3121.312
LGEELTFEXP_LGEE->PJM
CLTF
0.5530.553
WECLTFEXP_WEC->PJM
CLTF
0.2830.283
CONTINGENCY 'DVP_P1-2: LN 2201_SRT-A'
 OPEN BRANCH FROM BUS 313725 TO BUS 314563 CKT 1   /*6DRY BREAD   230.0 - 6CLUBHSE     230.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
314562 to 314563 ckt 1
313373 to 314765 ckt 1
313707 to 313373 ckt 1
314322 to 314914 ckt 1
314765 to 314749 ckt 1
314903 to 314908 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AF2-299 was evaluated as a 18.0 MW injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

(No impacts were found for this analysis)

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

(No impacts were found for this analysis)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Not Required

Stability Analysis is Not Required

Reactive Power Analysis

Reactive Power Analysis was not performed. This project is responsible for meeting all applicable power factor requirements.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-065Earleys 230kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA1-145Four Rivers 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-088Boykins-Handsome 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB1-173Brink-Trego 115kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-100Clubhouse-Lakeview 230kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-065Harmony Village-Shackleford 115kVUnder Construction
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-080Perth-Hickory Grove 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-112Old Church 34.5kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-216Hopewell-Surry 230kVIn Service
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-084Dawson-South Justice 115kVPartially in Service - Under Construction
AC2-100Halifax-Person 230kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVPartially in Service - Under Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-103Holland-Union Camp 115 kVSuspended
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-149Disputanta-Poe 115 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-247Myrtle-Windsor 115 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-153Heritage 500 kVActive
AG1-210Northern Neck 34.5 kVWithdrawn
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-536Garner-Northern Neck 115 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
V4-068Murphy's 34.5kVIn Service
W1-029Winfall 230kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z1-068Birdneck 34.5kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-088Tarboro-Everetts 230kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 312.A.1.b and as outlined in PJM Manual 14H, Section 13, in Phase III of the Cycle, PJM coordinates with the Affected System Operators to conduct any studies required to determine the impact of the New Service Request on any Affected System and will include the Affected System Study results in Phase III System Impact Study, if available from the Affected System Operator.

If your project required an Affected System Study, the results are shown below from the Affected System Operator.

For more details, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM will list any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE) Identified Impacts
Note: Please communicate with the Affected System Operator regarding the status of the Affected System Study for your project.
Impacted FacilityTransmission OwnerReinforcementCostCost Allocated to AF2-299Scenarios
  • Rocky Mount 230.0 - Nash 230.0 CKT 1
  • Rocky Mount 230.0 - Hathaway 230.0 CKT 1
CPLE Reconductor 4.73 miles with bundled 795 ACSS and replace substation components to get 3000A (City of Rocky Mount – Nash 230 kV)
Reconductor 4.73 miles with bundled 795 ACSS and
replace substation components to get 3000A (City
of Rocky Mount – Nash 230 kV)
$14,033,000$491,000
  • Rocky Mount 230.0 - Rocky Mount 115.0 CKT 1
CPLE Replace transformer protection panel, uprate CT ratios, and revise relay settings
Replace transformer protection panel, uprate CT
ratios, and revise relay settings
$619,000$24,000
  • Greenville 230.0 - Everetts 230.0 CKT 1
CPLE Reconductor one side of Everetts to Greenville 230 kV Line. Upgrade the terminal equipment.
Reconductor one side of Everetts to Greenville 230
kV Line. Upgrade the terminal equipment.
$150,000$0
  • Contingent
  • Greenville 230.0 - Everetts 230.0 CKT 1
CPLE Rebuild aging double circuit 230kV towers of Everetts to Greenville Line
Rebuild aging double circuit 230kV towers of
Everetts to Greenville Line
$19,000,000$0
  • Contingent
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Final System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
Dominion facility ratings: 379/390/449 MVA Winter | 372/384/441 MVA LL | 342/352/405 MVA Summer.
Description
Dominion facility ratings: 379/390/449 MVA Winter | 372/384/441 MVA LL | 342/352/405 MVA Summer.
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
3ROCKYMT115T-3BTLEBRO 115.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA342.0 MVA
SUMB352.0 MVA
SUMC405.0 MVA

System Reinforcement: n9112.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9112.0 / TC1-PH2-DOM-063
Title
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Description
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Total Cost ($USD)
$87,030,447
Discounted Total Cost ($USD)
$87,030,447
Allocated Cost ($USD)
$0
Time Estimate
46 to 47 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A797.0 MVA
(All)B797.0 MVA
(All)C1115.0 MVA

System Reinforcement: n9265.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9265.0 / TC1-PH2-DOM-064
Title
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Description
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Total Cost ($USD)
$396,021
Discounted Total Cost ($USD)
$396,021
Allocated Cost ($USD)
$0
Time Estimate
14 to 15 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A876.0 MVA
(All)B956.0 MVA
(All)C1163.0 MVA

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Discounted Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

FacilityContingency
6BUCKING-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A796.0 MVA
(All)B796.0 MVA
(All)C964.0 MVA

System Reinforcement: n9217.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9217.0 / TC1-PH2-DOM-028
Title
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$40,414,822
Discounted Total Cost ($USD)
$40,414,822
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

FacilityContingency
6BUCKING-6FARMVIL 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A797.0 MVA
(All)B797.0 MVA
(All)C1116.0 MVA

System Reinforcement: n9681.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9681.0
Title
Upgrade 1.04 Miles of 230kV transmission line 249 from 249/86 to 249/93
Description
Reconductor 1.04 miles of 2*636 ACSR 24/7 MOT 150 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" MOT 250 on 230 kV line 249 between Carson and Chaparral
Total Cost ($USD)
$3,042,004
Discounted Total Cost ($USD)
$3,042,004
Allocated Cost ($USD)
$0
Time Estimate
20 to 21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1442.0 MVA
LLB1540.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1493.0 MVA
WINB1587.0 MVA
WINC1631.0 MVA

System Reinforcement: b3694.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3694.8
Title
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA.
Description
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA. Upgrade terminal equipment at Carson and Locks to not limit the new conductor rating.
Cost Information
Time Estimate
May 03 2025

Not Contingent

Note: AF2-299 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-299 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1047.0 MVA
(All)B1047.0 MVA
(All)C1204.0 MVA
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA

System Reinforcement: n9200.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9200.0 / TC1-PH2-DOM-005
Title
Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" conductors.
Description
Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$38,691,326
Discounted Total Cost ($USD)
$38,691,326
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA797.0 MVA
SUMB797.0 MVA
SUMC1115.0 MVA

System Reinforcement: n9201.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9201.0 / TC1-PH2-DOM-006
Title
Replace wave trap at Carson 230 kV (Carson - Sapony).
Description
Replace wave trap at Carson 230 kV (Carson - Sapony).
Total Cost ($USD)
$521,941
Discounted Total Cost ($USD)
$521,941
Allocated Cost ($USD)
$0
Time Estimate
14 to 15 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA876.0 MVA
SUMB956.0 MVA
SUMC1163.0 MVA

System Reinforcement: n6872
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6872 / dom-047
Title
Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C.
Description
Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C
Total Cost ($USD)
$59,572,939
Discounted Total Cost ($USD)
$59,572,939
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

FacilityContingency
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1168.0 MVA
(All)B1195.0 MVA
(All)C1348.0 MVA

System Reinforcement: s3222.1
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3222.1
Title
Rebuild approximately 44.3 miles of 230kV Line #246 between Earleys and Suffolk to current 230kV standards. The normal rating of the line conductor will be 1573 MVA.
Description
Rebuild approximately 44.3 miles of 230kV Line #246 between Earleys and Suffolk to current 230kV standards. The normal rating of the line conductor will be 1573 MVA.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AF2-299 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AF2-299 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1809.0 MVA
6SUFFOLK-6NUCO TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1195.0 MVA
(All)B1195.0 MVA
(All)C1673.0 MVA

System Reinforcement: n9207.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9207.0 / TC1-PH2-DOM-018
Title
Replace 6ELMONT 230 kV to 8ELMONT 500 kV circuit 1 with larger transformer (3-480 MVA single phase transformer).
Description
Replace 6ELMONT 230 KV to 8ELMONT 500 kV ckt 1 with Larger XFRM. (3-480 MVA Single Phase XFRM).
Total Cost ($USD)
$38,254,469
Discounted Total Cost ($USD)
$38,254,469
Allocated Cost ($USD)
$0
Time Estimate
59 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

FacilityContingency
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA

System Reinforcement: n9379.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9379.0 / TC1-PH3-DOM-011
Title
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.
Description
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase 500/230 kV transformers.
Total Cost ($USD)
$37,836,293
Discounted Total Cost ($USD)
$37,836,293
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

FacilityContingency
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA

System Reinforcement: n9204.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9204.0 / TC1-PH2-DOM-014
Title
Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C
Total Cost ($USD)
$6,764,273
Discounted Total Cost ($USD)
$6,764,273
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

FacilityContingency
6SAPONY-AE2-033 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA876.0 MVA
SUMB956.0 MVA
SUMC1163.0 MVA

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AF2-299 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-299 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-299 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-299 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-299 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-299 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-299 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-299 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-299 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-299 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AF2-299 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-299 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AF2-299 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-299 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-299 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-299 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-299 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-299 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not ContingentTopology Changing

Note 1: AF2-299 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-299 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not ContingentTopology Changing

Note 1: AF2-299 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-299 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.315
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.315
Title
Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.
Description
Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Apr 22 2030

Not Contingent

Note: AF2-299 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-299 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TYLER1-6POE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA

System Reinforcement: n9139.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9139.0 / TC1-PH1-DOM-073
Title
Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.
Description
Wreck and rebuild 37.41 miles of 500kV transmission line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA. Remove wave traps.
Total Cost ($USD)
$245,455,768
Discounted Total Cost ($USD)
$245,455,768
Allocated Cost ($USD)
$0
Time Estimate
69 to 70 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.

System Reinforcement: b3692
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3692
Title
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.
Description
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy with current 500 kV standards construction practices to achieve a summer rating of 4330 MVA. Projected ISD: 06/01/2026
Cost Information
Time Estimate
Jun 01 2026

Not Contingent

Note: AF2-299 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-299 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4330.0 MVA
(All)B4330.0 MVA
(All)C5011.0 MVA

System Reinforcement: n9264.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9264.0 / TC1-PH1-DOM-080
Title
Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1.
Description
Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1.
Total Cost ($USD)
$582,006
Discounted Total Cost ($USD)
$582,006
Allocated Cost ($USD)
$0
Time Estimate
12 to 13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2650.0 MVA
(All)B2831.0 MVA
(All)C3663.0 MVA

System Reinforcement: n9191.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9191.0 / TC1-PH1-DOM-090
Title
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.
Description
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$256,706,175
Discounted Total Cost ($USD)
$256,706,175
Allocated Cost ($USD)
$0
Time Estimate
74 to 75 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-040
Title
ELIM TC1: Wreck and rebuild 18.75 miles of Line 594 btwn Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) Dipper at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 18.75 miles of Line 594 between Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$128,018,212
Discounted Total Cost ($USD)
$128,018,212
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9247.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9247.0 / TC1-PH2-DOM-041
Title
ELIM TC1: Wreck and rebuild 14.02 miles of Line 573 btwn Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 14.02 miles of Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA
Total Cost ($USD)
$99,636,684
Discounted Total Cost ($USD)
$99,636,684
Allocated Cost ($USD)
$0
Time Estimate
48 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-299 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-299 could receive cost allocation. Although AF2-299 may not presently have cost responsibility for this upgrade, AF2-299 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n8492.2

AF2-299 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.2
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.2
Title
Expand Yadkin Substation to accommodate the new 500 kV line.
Description
Expansion of yadkins 500 kV switchyard to accommodate the new 500 kV line which includes addition of 5000 amp GIS breakers and relocation of the existing suffolk -yadkin 500 kV line#565
Total Cost ($USD)
$16,207,123
Allocated Cost ($USD)
$0
Time Estimate
15 to 16 Months
Cost Alloc Type
Non-Contingent

System Reinforcement: n9259.0

AF2-299 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9259.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9259.0
Title
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Description
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Total Cost ($USD)
$25,304,902
Allocated Cost ($USD)
$0
Time Estimate
38 to 39 Months
Cost Alloc Type
Non-Contingent

System Reinforcement: n9267.0

AF2-299 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9267.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9267.0 / TC1-PH2-DOM-067
Title
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.
Description
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner substations with single (1) 768.2 ACSS/TW “Maumee” at 250 degrees C. This new line will be on separate transmission towers from the existing Northern Neck and Moon Corner line 1059. Station expansion is required at Northern Neck and Moon Corner to accommodate the new line.
Total Cost ($USD)
$45,730,074
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months
Cost Alloc Type
Non-Contingent

System Reinforcement: n9630.0

AF2-299 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.325

AF2-299 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: s3047.2

AF2-299 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: s3047.2
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3047.2
Title
Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.
Description
Install (2) 1400 MVA 500-230 kV transformers and associated 500 kV and 230 kV equipment (breakers, switches, leads) at Vint Hill Substation to supply the area with a 500 kV source Cut and loop 500 kV line #535 Loudoun – Meadowbrook and #569 Loudoun - Morrisville as the 500 kV sources into the proposed 500 kV ring bus Vint Hill Substation will be expanded to the north of the existing site to accommodate the 500 kV ring required for the addition of the new transformers Existing terminations for 230 kV line #2174 Wheeler – Vint Hill, line #2101 Bristers – Vint Hill, and line #2163 Liberty – Vint Hill will be rearranged to terminate into the expanded Vint Hill Substation 230 kV line #2114 Remington CT – Rollins Ford will also be cut and looped into the expanded Vint Hill Substation due to spatial constraints along the existing right-of-way.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.312

AF2-299 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.312
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.312
Title
Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.
Description
Rebuild 500kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. New conductor to have a summer rating of 4357 MVA.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.313

AF2-299 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.313
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.313
Title
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Description
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.356

AF2-299 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.356
Title
Build a new 500 kV line from Vint Hill to Wishing Star.
Description
Build a new 500kV line from Vint Hill to Wishing Star. The line will be supported on single circuit monopoles. New conductor to have a summer rating of 4357 MVA. Line length is approximately 16.59 miles
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.357

AF2-299 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.357
Title
Build a new 500 kV line from Morrisville to Vint Hill.
Description
Build a new 500kV line from Morrisville to Vint Hill. New conductor to have a summer rating of 4357 MVA. Line length is approximately 19.71 miles.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.354

AF2-299 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.354
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.354
Title
Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.
Description
Install terminal equipment at Wishing Star substation to support a 5000A line to Vint Hill. Update relay settings for 500kV Lines #546 and #590.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: n8492

AF2-299 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492
Title
Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.
Description
Wreck and rebuild one (1) overhead 500kV transmission line that will start at the existing Fentress 500 kV Substation and terminate at the existing Yadkin 500 kV Substation, located approximately 13.5 miles away.
Total Cost ($USD)
$80,172,278
Allocated Cost ($USD)
$0
Time Estimate
26 to 27 Months
Cost Alloc Type
Non-Contingent

System Reinforcement: n8492.1

AF2-299 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.1
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.1
Title
Two Breaker Additions at Fentress Substation.
Description
Install Two 5000 amp GIS Breakers at Fentress Substation to connect the new 500 kV line 5005.
Total Cost ($USD)
$19,945,879
Allocated Cost ($USD)
$0
Time Estimate
30 to 36 Months
Cost Alloc Type
Non-Contingent

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AF2-299


AF2-299 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AF2-299 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Non-Contingent$0
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Non-Contingent$0
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Non-Contingent$0
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Non-Contingent$0
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Non-Contingent$0
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.Non-Contingent$0
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.Non-Contingent$0
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.Non-Contingent$0
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.Non-Contingent$0
Dominionb4000.348Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Non-Contingent$0
Dominionb4000.346Cut-in 500kV line from Kraken substation into Yeat substationNon-Contingent$0
Dominionb4000.345Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Non-Contingent$0
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.Non-Contingent$0
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Non-Contingent$0
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Non-Contingent$0
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Non-Contingent$0
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Non-Contingent$0
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Non-Contingent$0
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Non-Contingent$0
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Non-Contingent$0
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Non-Contingent$0
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Non-Contingent$0
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Non-Contingent$0
Dominionn8492.1Two Breaker Additions at Fentress Substation.Non-Contingent$0
Region Topology Upgrade Total:$0

Attachments

AF2-299 One Line Diagram

AF2-299 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.