AF2-319 Final System Impact Study (Retool 1) Report

v1.00 released 2025-12-08 18:19

Katydid Road 345 kV

20.0 MW Capacity / 50.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Blackstone Wind Farm, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Commonwealth Edison Company.

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the TC1 projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.
Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of TC1 projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed an uprate to a planned/existing Storage facility located in the Commonwealth Edison Company zone — Lasalle County, Illinois. This project is an increase to the developer’s AF2-226 project(s), which will share the same Point of Interconnection. The AF2-319 project is a 50.0 MW uprate (20.0 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 400.0 MW with 40.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AF2-319
Project Name:
Katydid Road 345 kV
Project Developer Name:
Blackstone Wind Farm, LLC
State:
Illinois
County:
Lasalle
Transmission Owner:
Commonwealth Edison Company
MFO:
400.0
MWE:
50.0
MWC:
20.0
Battery Storage Specification:
200.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2027

Physical Interconnection Facility Study

Reviewed

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AF2-319 will interconnect on the ComEd transmission system via a connection to the TSS 196 Katydid 345 kV substation and will share interconnection facilities with O22 (Top Crop I and Top Crop II) and AF2-226.

 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AF2-319 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AF2-319Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$256,082$256,082
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$627,185$627,185
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$204,661$0
Total$1,087,928$883,267

* Contributes to calculation for Security. See Security Section of this report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF2-226/AF2-319

Security has been calculated for the AF2-226/AF2-319 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF2-226/AF2-319
Project(s): AF2-226/AF2-319
Final Agreement Security (A): $1,766,534
Portion of Costs Already Paid (B): $0
Revised Net Security (C): A − B = $1,766,534
Security on Hand with PJM (D): $1,766,535
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Oversight and SCADA, Communication and metering settings changes to accommodate the new energy storage.

$153,870$0$102,212$0$256,082$256,082

Based on the scope of work for the Interconnection Facilities, it is expected to take 18 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Notes on Cost Estimate:

  1. These estimates are Order-of-Magnitude estimates of the costs that ComEd would bill to the Project Developer for this interconnection. These estimates are based on a one-line electrical diagram of the project and the information provided by the Project Developer.
  2. There were no site visits performed for these estimates. There may be costs related to specific site related issues that are not identified in these estimates. The site reviews will be performed during the Facilities Study or during detailed engineering.
  3. These estimates are not a guarantee of the maximum amount payable by the Project Developer and the actual costs of ComEd's work may differ significantly from these estimates. The Project Developer will be responsible for paying actual costs of ComEd's work in accordance with the PJM Open Access Transmission Tariff.
  4. The Project Developer is responsible for all engineering, procurement, testing and construction of all equipment on the Project Developer’s side of the Point of Change in Ownership.

These cost estimates do not include cost of acquiring right-of-way for the transmission line and purchasing any additional land, if needed, for the line terminations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. ComEd interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AF2-319 was evaluated as a 50.0 MW (20.0 MW Capacity) injection in the ComEd area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP
05DUMONT-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC111.6 %4142.0B4622.3211.36
GD1AEP
05DUMONT-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC100.33 %4142.0B4155.8110.28
GD1AEP
05SORENS-05MARYSV 765.0 kV Ckt 1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC102.72 %4142.0B4254.8511.96
GD1AMIL/CE
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A
TowerAC156.1 %1489.0B2324.3336.98
GD1AMIL/CE
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
COMED_P4_012-45-BT4-5___SRT-A
BreakerAC125.61 %1489.0B1870.2914.56

Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.6 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4622.32
MW Contribution:11.36
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.12 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4643.96
MW Contribution:11.39
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
4.9294117647058834.19
962781AG1-127 C
Adder
12.98470588235294311.037
962782AG1-127 E
Adder
8.6411764705882357.345
965681AG1-436 C
Adder
17.43176470588235514.817
965682AG1-436 E
Adder
11.6211764705882359.878
966091AG1-478 C
Adder
3.71294117647058863.156
966092AG1-478 E
Adder
0.93411764705882360.794
966441AG1-513 C
Adder
0.93411764705882360.794
966442AG1-513 E
Adder
1.40117647058823551.191
24796705OLIV SLR E
Adder
0.56117647058823530.477
290021O50 E
Adder
35.73058823529411430.371
290051GSG-6; E
Adder
19.6129411764705916.671
295109WESTBROOK E
Adder
10.5011764705882368.926
295111SUBLETTE E
Adder
5.1047058823529424.339
910542X3-005 E
Adder
1.32588235294117651.127
918052AA1-018 E OP
Adder
29.625.16
933911AD1-013 C
Adder
3.45176470588235332.934
933912AD1-013 E
Adder
5.5141176470588244.687
934721AD1-100 C
50/50
5.4585.458
934722AD1-100 E
50/50
165.829165.829
937002AD2-134 E
Adder
18.96352941176470716.119
958481AF2-142 C
Adder
20.41411764705882317.352
958482AF2-142 E
Adder
13.60941176470588211.568
958491AF2-143 C
Adder
20.1317647058823517.112
958492AF2-143 E
Adder
13.42117647058823411.408
959351AF2-226 C
Adder
4.5435294117647063.862
959352AF2-226 E
Adder
6.8141176470588245.792
960281AF2-319 C
Adder
4.5435294117647063.862
960282AF2-319 E
Adder
6.8141176470588245.792
960582AF2-349 E
Adder
67.176470588235357.1
960681AF2-359 C
Adder
17.43176470588235514.817
960682AF2-359 E
Adder
11.6211764705882359.878
960751AF2-366 C
Adder
12.94823529411764811.006
960752AF2-366 E
Adder
8.6317647058823527.337
24344105CKG2
50/50
60.20560.205
274660LASCO STA;1U
50/50
44.08644.086
274661LASCO STA;2U
50/50
44.22744.227
274675JOLIET 29;7U
Adder
129.0741176470588109.713
274676JOLIET 29;8U
Adder
129.0705882352941109.71
274682WAUKEGAN ;7U
Adder
75.2058823529411763.925
274683WAUKEGAN ;8U
Adder
81.1376470588235368.967
274687WILL CNTY;4U
Adder
119.63882352941177101.693
274771LINCOLN ;2U
50/50
3.1483.148
274772LINCOLN ;3U
50/50
3.1483.148
274773LINCOLN ;4U
50/50
3.1483.148
274774LINCOLN ;5U
50/50
3.1483.148
274775LINCOLN ;6U
50/50
3.1483.148
274776LINCOLN ;7U
50/50
3.1483.148
274777LINCOLN ;8U
50/50
3.1483.148
274788SE CHICAG;5U
Adder
8.7305882352941187.421
274789SE CHICAG;6U
Adder
8.7305882352941187.421
274790SE CHICAG;7U
Adder
8.7305882352941187.421
274791SE CHICAG;8U
Adder
8.7305882352941187.421
274792SE CHICAG;9U
Adder
8.722352941176477.414
274793SE CHICAG;0U
Adder
8.722352941176477.414
274794SE CHICAG;1U
Adder
8.722352941176477.414
274795SE CHICAG;2U
Adder
8.722352941176477.414
276591L-013 2
Adder
6.7270588235294125.718
293061N-015 E
Adder
28.1705882352941223.945
293644O22 E1
Adder
26.09999999999999822.185
293645O22 E2
Adder
29.89294117647058625.409
294392P-010 E
Adder
35.776470588235330.41
933411AC2-154 C
Adder
4.4858823529411773.813
933412AC2-154 E
Adder
7.3188235294117656.221
957331AF2-027 C
Adder
4.55882352941176453.875
957332AF2-027 E
Adder
6.8388235294117655.813
957471AF2-041 C
Adder
31.69882352941176526.944
274674JOLIET 9 ;6U
Adder
65.8517647058823555.974
274890CAYUG;1U E
Adder
26.69411764705882522.69
274891CAYUG;2U E
Adder
26.69411764705882522.69
938851AE1-113 C
Adder
14.73882352941176612.528
938852AE1-113 E
Adder
52.2552941176470644.417
934101AD2-000 1
Adder
10.767058823529419.152
934111AD2-000 2
Adder
10.7964705882352949.177
270100AB1-080 CT1
50/50
9.0469.046
270101AB1-080 CT2
50/50
9.0469.046
270102AB1-080 ST
50/50
9.7879.787
274708KENDALL ;3C
50/50
7.1797.179
274709KENDALL ;3S
50/50
4.7494.749
274710KENDALL ;4C
50/50
7.1017.101
274711KENDALL ;4S
50/50
4.7494.749
275149KELLYCK ;1E
Adder
33.05176470588235628.094
293519PILOT HIL;1E
Adder
33.05176470588235628.094
290108LEEDK;1U E
Adder
44.7835294117647138.066
916221Z1-073 E
Adder
13.82117647058823511.748
936292AD2-038 E
Adder
27.6482352941176523.501
936371AD2-047 C
Adder
8.0270588235294126.823
936372AD2-047 E
Adder
39.1894117647058833.311
936461AD2-060 C
Adder
4.7211764705882354.013
936511AD2-066 C
Adder
15.63294117647058813.288
936512AD2-066 E
Adder
10.422352941176478.859
942421AE2-255 C
Adder
5.5823529411764714.745
942422AE2-255 E
Adder
16.7482352941176514.236
942651AE2-281 C
Adder
1.56588235294117651.331
942652AE2-281 E
Adder
9.6188235294117658.176
943121AE2-341 C
Adder
23.57411764705882420.038
943122AE2-341 E
Adder
11.5764705882352949.84
943591AF1-030 C
Adder
15.67647058823529313.325
943592AF1-030 E
Adder
7.75647058823529446.593
960591AF2-350 C
Adder
14.1647058823529412.04
960592AF2-350 E
Adder
9.4435294117647068.027
961501AF2-441 C
Adder
18.91647058823529516.079
961502AF2-441 E
Adder
28.3752941176470624.119
939321AE1-163 C
Adder
10.9611764705882359.317
939322AE1-163 E
Adder
67.3294117647058857.23
939351AE1-166 C
50/50
18.47818.478
939352AE1-166 E
50/50
17.05717.057
939401AE1-172 C
Adder
10.182352941176478.655
939402AE1-172 E
Adder
47.6717647058823540.521
946671AF1-331 C
Adder
4.4823529411764713.81
962691AG1-118 C
Adder
41.05764705882353434.899
962692AG1-118 E
Adder
27.37176470588235223.266
941551AE2-152 C
50/50
21.32121.321
941552AE2-152 E
50/50
14.21414.214
957371AF2-031 C
Adder
1.8882352941176471.605
957372AF2-031 E
Adder
2.83294117647058832.408
958011AF2-095 C
Adder
20.3976470588235317.338
958012AF2-095 E
Adder
13.59882352941176411.559
965791AG1-447 C
Adder
12.78352941176470610.866
274770LINCOLN ;1U
50/50
3.1483.148
920272AA2-123 E
Adder
5.30941176470588254.513
276170Z1-108 E
Adder
5.3764705882352954.57
276675AE2-062 E
Adder
0.275294117647058860.234
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
2.162.16
CBM West 1LTFEXP_CBM-W1->PJM
CBM
268.722268.722
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.75157.751
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
5.9085.908
NYPJM->LTFIMP_NY
CLTF
3.0993.099
LGEELTFEXP_LGEE->PJM
CLTF
1.2131.213
WECLTFEXP_WEC->PJM
CLTF
7.2467.246
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.4271.427
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.7140.714
TVALTFEXP_TVA->PJM
CLTF
5.7885.788
MECLTFEXP_MEC->PJM
CLTF
27.4427.44
LAGNLTFEXP_LAGN->PJM
CLTF
10.83410.834
SIGELTFEXP_SIGE->PJM
CLTF
0.7480.748
O66PJM->LTFIMP_O-066
CMTX_NF
37.87737.877

Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.33 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4155.81
MW Contribution:10.28
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.97 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4182.04
MW Contribution:10.32
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
4.4705882352941183.8
962781AG1-127 C
Adder
11.7810.013
962782AG1-127 E
Adder
7.8388235294117666.663
965681AG1-436 C
Adder
15.73176470588235413.372
965682AG1-436 E
Adder
10.4870588235294118.914
966091AG1-478 C
Adder
3.3647058823529412.86
966092AG1-478 E
Adder
0.84705882352941180.72
966441AG1-513 C
Adder
0.84705882352941180.72
966442AG1-513 E
Adder
1.27058823529411781.08
24796705OLIV SLR E
Adder
0.50470588235294120.429
290021O50 E
Adder
32.3317647058823527.482
290051GSG-6; E
Adder
17.78705882352941415.119
295109WESTBROOK E
Adder
9.522352941176478.094
295111SUBLETTE E
Adder
4.6294117647058833.935
910542X3-005 E
Adder
1.20117647058823531.021
918052AA1-018 E OP
Adder
26.79411764705882222.775
933911AD1-013 C
Adder
3.1305882352941182.661
933912AD1-013 E
Adder
5.04.25
934721AD1-100 C
50/50
4.9494.949
934722AD1-100 E
50/50
150.352150.352
937002AD2-134 E
Adder
17.1976470588235314.618
958481AF2-142 C
Adder
18.47882352941176615.707
958482AF2-142 E
Adder
12.31882352941176410.471
958491AF2-143 C
Adder
18.21411764705882415.482
958492AF2-143 E
Adder
12.1423529411764710.321
959351AF2-226 C
Adder
4.11294117647058853.496
959352AF2-226 E
Adder
6.1694117647058825.244
960281AF2-319 C
Adder
4.11294117647058853.496
960282AF2-319 E
Adder
6.1694117647058825.244
960582AF2-349 E
Adder
60.9223529411764751.784
960681AF2-359 C
Adder
15.73176470588235413.372
960682AF2-359 E
Adder
10.4870588235294118.914
960751AF2-366 C
Adder
11.747058823529419.985
960752AF2-366 E
Adder
7.8305882352941176.656
24344105CKG2
50/50
55.59555.595
274660LASCO STA;1U
50/50
40.01740.017
274661LASCO STA;2U
50/50
40.14440.144
274675JOLIET 29;7U
Adder
117.0552941176470799.497
274676JOLIET 29;8U
Adder
117.0517647058823699.494
274682WAUKEGAN ;7U
Adder
68.2257.987
274683WAUKEGAN ;8U
Adder
73.6000000000000162.56
274687WILL CNTY;4U
Adder
108.4752941176470592.204
274771LINCOLN ;2U
50/50
2.8662.866
274772LINCOLN ;3U
50/50
2.8662.866
274773LINCOLN ;4U
50/50
2.8662.866
274774LINCOLN ;5U
50/50
2.8662.866
274775LINCOLN ;6U
50/50
2.8662.866
274776LINCOLN ;7U
50/50
2.8662.866
274777LINCOLN ;8U
50/50
2.8662.866
274788SE CHICAG;5U
Adder
7.9058823529411776.72
274789SE CHICAG;6U
Adder
7.9058823529411776.72
274790SE CHICAG;7U
Adder
7.9058823529411776.72
274791SE CHICAG;8U
Adder
7.9058823529411776.72
274792SE CHICAG;9U
Adder
7.8964705882352946.712
274793SE CHICAG;0U
Adder
7.8964705882352946.712
274794SE CHICAG;1U
Adder
7.8964705882352946.712
274795SE CHICAG;2U
Adder
7.8964705882352946.712
276591L-013 2
Adder
6.1047058823529415.189
293061N-015 E
Adder
25.55058823529411821.718
293644O22 E1
Adder
23.6270588235294120.083
293645O22 E2
Adder
27.06117647058823323.002
294392P-010 E
Adder
32.44823529411764427.581
933411AC2-154 C
Adder
4.0658823529411773.456
933412AC2-154 E
Adder
6.6329411764705885.638
957331AF2-027 C
Adder
4.1352941176470593.515
957332AF2-027 E
Adder
6.20352941176470555.273
957471AF2-041 C
Adder
36.2482352941176530.811
957472AF2-041 E
Adder
0.407058823529411750.346
274674JOLIET 9 ;6U
Adder
59.7105882352941250.754
938851AE1-113 C
Adder
13.33647058823529511.336
938852AE1-113 E
Adder
47.2858823529411740.193
934101AD2-000 1
Adder
9.7588235294117668.295
934111AD2-000 2
Adder
9.7858823529411768.318
270100AB1-080 CT1
50/50
8.1638.163
270101AB1-080 CT2
50/50
8.1638.163
270102AB1-080 ST
50/50
8.8338.833
274708KENDALL ;3C
50/50
6.5186.518
274709KENDALL ;3S
50/50
4.3114.311
274710KENDALL ;4C
50/50
6.4476.447
274711KENDALL ;4S
50/50
4.3114.311
275149KELLYCK ;1E
Adder
29.9576470588235325.464
293519PILOT HIL;1E
Adder
29.9576470588235325.464
290108LEEDK;1U E
Adder
40.62588235294117634.532
916221Z1-073 E
Adder
12.53411764705882410.654
936292AD2-038 E
Adder
25.01411764705882521.262
936371AD2-047 C
Adder
7.2752941176470596.184
936372AD2-047 E
Adder
35.5211764705882430.193
936461AD2-060 C
Adder
4.283.638
936511AD2-066 C
Adder
14.14470588235294112.023
936512AD2-066 E
Adder
9.4294117647058838.015
942421AE2-255 C
Adder
5.0517647058823534.294
942422AE2-255 E
Adder
15.1552941176470612.882
942651AE2-281 C
Adder
1.41647058823529411.204
942652AE2-281 E
Adder
8.7023529411764717.397
943121AE2-341 C
Adder
21.4047058823529418.194
943122AE2-341 E
Adder
10.5105882352941178.934
943591AF1-030 C
Adder
14.23411764705882412.099
943592AF1-030 E
Adder
7.042352941176475.986
959091AF2-200 C
Adder
24.1647058823529420.54
960591AF2-350 C
Adder
12.83882352941176610.913
960592AF2-350 E
Adder
8.5588235294117647.275
961501AF2-441 C
Adder
17.1376470588235314.567
961502AF2-441 E
Adder
25.7070588235294121.851
939321AE1-163 C
Adder
9.9164705882352958.429
939322AE1-163 E
Adder
60.916470588235351.779
939351AE1-166 C
50/50
16.75316.753
939352AE1-166 E
50/50
15.46515.465
939401AE1-172 C
Adder
9.2000000000000017.82
939402AE1-172 E
Adder
43.0741176470588336.613
946671AF1-331 C
Adder
4.0647058823529413.455
962691AG1-118 C
Adder
37.2494117647058831.662
962692AG1-118 E
Adder
24.8329411764705921.108
941551AE2-152 C
50/50
19.33119.331
941552AE2-152 E
50/50
12.88712.887
957371AF2-031 C
Adder
1.71058823529411771.454
957372AF2-031 E
Adder
2.56470588235294142.18
958011AF2-095 C
Adder
18.48823529411764715.715
958012AF2-095 E
Adder
12.32588235294117710.477
965791AG1-447 C
Adder
11.5364705882352939.806
274770LINCOLN ;1U
50/50
2.8662.866
920272AA2-123 E
Adder
4.8164705882352954.094
276170Z1-108 E
Adder
4.877647058823534.146
276675AE2-062 E
Adder
0.249411764705882360.212
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
1.8261.826
CBM West 1LTFEXP_CBM-W1->PJM
CBM
243.013243.013
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.43653.436
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
5.4955.495
NYPJM->LTFIMP_NY
CLTF
2.8932.893
LGEELTFEXP_LGEE->PJM
CLTF
3.0323.032
WECLTFEXP_WEC->PJM
CLTF
6.5716.571
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.1751.175
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.5610.561
TVALTFEXP_TVA->PJM
CLTF
5.8945.894
MECLTFEXP_MEC->PJM
CLTF
24.86724.867
LAGNLTFEXP_LAGN->PJM
CLTF
10.36210.362
SIGELTFEXP_SIGE->PJM
CLTF
0.7770.777
O66PJM->LTFIMP_O-066
CMTX_NF
35.23735.237

Details for 05SORENS-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SORENS-05MARYSV 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.72 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4254.85
MW Contribution:11.96
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05MARYSV 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.54 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4288.77
MW Contribution:11.99
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
24335305OLIVE
50/50
0.2120.212
965681AG1-436 C
Adder
18.9305882352941216.091
965682AG1-436 E
Adder
12.62117647058823510.728
966091AG1-478 C
Adder
3.88000000000000033.298
966092AG1-478 E
Adder
0.97647058823529410.83
966441AG1-513 C
Adder
0.96823529411764710.823
966442AG1-513 E
Adder
1.45294117647058841.235
24642205MAYFLWER
50/50
0.2440.244
24643105BUCHANAN
50/50
0.0840.084
247643Z2-116 C
50/50
0.0550.055
24796605WTRV SLR E
Adder
0.57647058823529410.49
24796705OLIV SLR E
50/50
0.6480.648
247969Z2-116 E
50/50
0.3340.334
910542X3-005 E
Adder
1.39411764705882371.185
918052AA1-018 E OP
Adder
31.17294117647058726.497
934722AD1-100 E
Adder
172.2376470588235146.402
943001AE2-323 C
Adder
16.5152941176470614.038
943002AE2-323 E
Adder
8.097647058823536.883
943021AE2-325 C
50/50
7.9467.946
943022AE2-325 E
50/50
5.2975.297
944161AF1-084 C
Adder
13.66941176470588311.619
944162AF1-084 E
Adder
7.80823529411764656.637
944961AF1-161 C
50/50
6.3426.342
958481AF2-142 C
Adder
21.49882352941176618.274
958482AF2-142 E
Adder
14.3329411764705912.183
959351AF2-226 C
Adder
4.7847058823529424.067
959352AF2-226 E
Adder
7.17647058823529356.1
960281AF2-319 C
Adder
4.7847058823529424.067
960282AF2-319 E
Adder
7.17647058823529356.1
960681AF2-359 C
Adder
18.9305882352941216.091
960682AF2-359 E
Adder
12.62117647058823510.728
24307105BERRINSP G
50/50
0.1370.137
24344005CKG1
50/50
43.40443.404
24344105CKG2
50/50
55.8555.85
24441505OLIV SLR C
50/50
0.1060.106
270142AA2-116_CT1
50/50
15.92315.923
270143AA2-116_CT2
50/50
15.92315.923
270144AA2-116_ST
50/50
14.10214.102
274675JOLIET 29;7U
Adder
134.57764705882354114.391
274676JOLIET 29;8U
Adder
134.5764705882353114.39
274682WAUKEGAN ;7U
Adder
78.4505882352941366.683
274683WAUKEGAN ;8U
Adder
84.6588235294117671.96
274687WILL CNTY;4U
Adder
124.97176470588235106.226
274771LINCOLN ;2U
50/50
3.1893.189
274772LINCOLN ;3U
50/50
3.1893.189
274773LINCOLN ;4U
50/50
3.1893.189
274776LINCOLN ;7U
50/50
3.1893.189
274777LINCOLN ;8U
50/50
3.1893.189
274788SE CHICAG;5U
Adder
9.2541176470588237.866
274789SE CHICAG;6U
Adder
9.2541176470588237.866
274790SE CHICAG;7U
Adder
9.2541176470588237.866
274791SE CHICAG;8U
Adder
9.2541176470588237.866
274792SE CHICAG;9U
Adder
9.2541176470588237.866
274793SE CHICAG;0U
Adder
9.2541176470588237.866
274794SE CHICAG;1U
Adder
9.2541176470588237.866
274795SE CHICAG;2U
Adder
9.2541176470588237.866
276591L-013 2
Adder
6.9894117647058825.941
293061N-015 E
Adder
29.2470588235294124.86
293644O22 E1
Adder
27.48823529411764723.365
293645O22 E2
Adder
31.48352941176470726.761
294392P-010 E
Adder
37.143529411764731.572
933411AC2-154 C
Adder
4.6870588235294123.984
933412AC2-154 E
Adder
7.6482352941176476.501
274674JOLIET 9 ;6U
Adder
68.6729411764705958.372
934101AD2-000 1
Adder
11.2117647058823529.53
934111AD2-000 2
Adder
11.2741176470588259.583
24335205NTRDAM
50/50
2.4332.433
24641605TWIN BRNCH
50/50
0.0710.071
24647605NILES
50/50
0.0550.055
24647705NILES
50/50
0.0550.055
270100AB1-080 CT1
50/50
9.9719.971
270101AB1-080 CT2
50/50
9.9719.971
270102AB1-080 ST
50/50
10.78910.789
270216AD2-079_C O1
50/50
0.5020.502
275149KELLYCK ;1E
Adder
34.53882352941176529.358
293519PILOT HIL;1E
Adder
34.53882352941176529.358
936632AD2-079 E O1
50/50
2.0472.047
936141AD2-020 C
50/50
15.70315.703
936371AD2-047 C
Adder
8.3882352941176477.13
936372AD2-047 E
Adder
40.95294117647059634.81
936461AD2-060 C
Adder
4.9341176470588244.194
942241AE2-236 C
Adder
9.7541176470588238.291
942242AE2-236 E
Adder
4.183.553
943121AE2-341 C
Adder
24.38470588235294320.727
943122AE2-341 E
Adder
11.97411764705882410.178
943591AF1-030 C
Adder
16.21647058823529613.784
943592AF1-030 E
Adder
8.0235294117647066.82
944241AF1-092 C
Adder
28.98705882352941324.639
944242AF1-092 E
Adder
8.822352941176477.499
944931AF1-158 C
50/50
3.7133.713
944932AF1-158 E
50/50
15.54815.548
945111AF1-176 C
50/50
39.50439.504
945112AF1-176 E
50/50
36.6236.62
945421AF1-207 C
Adder
8.1811764705882366.954
945422AF1-207 E
Adder
35.13176470588235429.862
945502AF1-215 E
Adder
30.13647058823529425.616
959141AF2-205 C
Adder
29.48588235294117525.063
959142AF2-205 E
Adder
19.65764705882352816.709
960591AF2-350 C
Adder
14.80235294117647312.582
960592AF2-350 E
Adder
9.8682352941176488.388
961051AF2-396 C
50/50
50.74150.741
961501AF2-441 C
Adder
19.95058823529411616.958
961502AF2-441 E
Adder
29.9258823529411825.437
939351AE1-166 C
Adder
19.19176470588235316.313
939352AE1-166 E
Adder
17.7152941176470615.058
939391AE1-170 C
50/50
16.1416.14
939392AE1-170 E
50/50
22.28822.288
939402AE1-172 E
Adder
25.43999999999999821.624
940581AE2-045 C
Adder
20.59882352941176717.509
940582AE2-045 E
Adder
28.28352941176470724.041
962601AG1-109 C
50/50
6.3426.342
964401AG1-302 C
Adder
44.7047058823529537.999
964402AG1-302 E
Adder
29.80235294117647325.332
936142AD2-020 E
50/50
9.6669.666
941551AE2-152 C
Adder
22.1447058823529418.823
941552AE2-152 E
Adder
14.76352941176470612.549
957371AF2-031 C
Adder
2.01.7
957372AF2-031 E
Adder
3.02.55
957841AF2-078 C
Adder
28.8752941176470624.544
957842AF2-078 E
Adder
19.25058823529411716.363
957891AF2-083 C
50/50
25.55625.556
957892AF2-083 E
50/50
12.77812.778
958011AF2-095 C
Adder
21.31529411764705618.118
958012AF2-095 E
Adder
14.21058823529411812.079
958381AF2-132 C
Adder
44.7047058823529537.999
958382AF2-132 E
Adder
29.80235294117647325.332
958391AF2-133 C
Adder
44.3929411764705937.734
958392AF2-133 E
Adder
29.59529411764705725.156
958402AF2-134 E
Adder
10.0458823529411768.539
964861AG1-349 C
Adder
38.6632.861
964862AG1-349 E
Adder
25.7729411764705921.907
965791AG1-447 C
Adder
13.88235294117647111.8
274770LINCOLN ;1U
50/50
3.1893.189
276675AE2-062 E
Adder
0.287058823529411760.244
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
2.3872.387
CBM West 1LTFEXP_CBM-W1->PJM
CBM
319.618319.618
CBM West 2LTFEXP_CBM-W2->PJM
CBM
75.36775.367
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
6.9886.988
NYPJM->LTFIMP_NY
CLTF
3.633.63
LGEELTFEXP_LGEE->PJM
CLTF
3.8433.843
WECLTFEXP_WEC->PJM
CLTF
7.6087.608
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.531.53
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.7280.728
TVALTFEXP_TVA->PJM
CLTF
8.198.19
MECLTFEXP_MEC->PJM
CLTF
30.0930.09
LAGNLTFEXP_LAGN->PJM
CLTF
13.77113.771
SIGELTFEXP_SIGE->PJM
CLTF
1.2341.234
O66PJM->LTFIMP_O-066
CMTX_NF
44.79244.792

Details for POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AMIL/CE
Facility Description:
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:156.1 %
Rating:1489.0 MVA
Rating Type:B
MVA to Mitigate:2324.33
MW Contribution:36.98
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
290021O50 E
50/50
71.52471.524
918052AA1-018 E OP
50/50
96.52396.523
958481AF2-142 C
50/50
66.56766.567
958482AF2-142 E
50/50
44.37844.378
958491AF2-143 C
50/50
66.56566.565
958492AF2-143 E
50/50
44.37644.376
959351AF2-226 C
50/50
14.79314.793
959352AF2-226 E
50/50
22.18922.189
960281AF2-319 C
50/50
14.79314.793
960282AF2-319 E
50/50
22.18922.189
274677POWERTON ;5U
50/50
92.92192.921
274678POWERTON ;6U
50/50
92.92192.921
274861TOP CROP ;1U
50/50
2.2242.224
274862TOP CROP ;2U
50/50
4.2434.243
274879MINONK ;1U
50/50
2.9212.921
293644O22 E1
50/50
84.98584.985
293645O22 E2
50/50
97.33797.337
938851AE1-113 C
50/50
29.50429.504
938852AE1-113 E
50/50
104.604104.604
270839OTTER CRK; R
50/50
2.3562.356
936291AD2-038 C
50/50
2.9812.981
936292AD2-038 E
50/50
91.41591.415
942421AE2-255 C
50/50
11.17611.176
942422AE2-255 E
50/50
33.52733.527
942651AE2-281 C
50/50
5.1775.177
942652AE2-281 E
50/50
31.80331.803
939321AE1-163 C
50/50
36.24136.241
939322AE1-163 E
50/50
222.621222.621
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
4.1374.137
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.9150.915
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9030.903
NYPJM->LTFIMP_NY
CLTF
0.4660.466
WECLTFEXP_WEC->PJM
CLTF
0.0510.051
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
5.0885.088
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.7310.731
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.460.46
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
8.1518.151
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6460.646
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0622.062
O66PJM->LTFIMP_O-066
CMTX_NF
5.7815.781
MDUPJM->LTFIMP_MDU
CLTF
0.3110.311

Details for POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT4-5___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AMIL/CE
Facility Description:
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_012-45-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.61 %
Rating:1489.0 MVA
Rating Type:B
MVA to Mitigate:1870.29
MW Contribution:14.56
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AMIL/CE
Facility Description:
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_012-45-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.57 %
Rating:1489.0 MVA
Rating Type:B
MVA to Mitigate:1869.8
MW Contribution:14.57
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
290021O50 E
50/50
99.6699.66
918052AA1-018 E OP
50/50
39.64339.643
958481AF2-142 C
50/50
27.3427.34
958482AF2-142 E
50/50
18.22618.226
958491AF2-143 C
50/50
35.77235.772
958492AF2-143 E
50/50
23.84823.848
959351AF2-226 C
50/50
5.8245.824
959352AF2-226 E
50/50
8.7358.735
960281AF2-319 C
50/50
5.8245.824
960282AF2-319 E
50/50
8.7358.735
274677POWERTON ;5U
50/50
77.94277.942
274678POWERTON ;6U
50/50
78.26778.267
274861TOP CROP ;1U
50/50
0.8760.876
274862TOP CROP ;2U
50/50
1.671.67
274879MINONK ;1U
50/50
4.074.07
293644O22 E1
50/50
33.45733.457
293645O22 E2
50/50
38.31938.319
938851AE1-113 C
50/50
41.1141.11
938852AE1-113 E
50/50
145.752145.752
934101AD2-000 1
50/50
-1.5-1.5
934111AD2-000 2
50/50
28.96228.962
270839OTTER CRK; R
50/50
0.9680.968
276658AB1-122 CT1
50/50
-3.03-3.03
276660AB1-122 CT2
50/50
58.51858.518
936291AD2-038 C
50/50
1.6021.602
936292AD2-038 E
50/50
49.12849.128
942421AE2-255 C
50/50
15.57215.572
942422AE2-255 E
50/50
46.71646.716
942651AE2-281 C
50/50
2.7822.782
942652AE2-281 E
50/50
17.09117.091
939321AE1-163 C
50/50
19.47619.476
939322AE1-163 E
50/50
119.639119.639
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
5.9655.965
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
1.061.06
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8680.868
NYPJM->LTFIMP_NY
CLTF
0.4420.442
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
7.1267.126
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.8590.859
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.5480.548
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
11.65611.656
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7280.728
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.352.35
O66PJM->LTFIMP_O-066
CMTX_NF
5.5525.552
MDUPJM->LTFIMP_MDU
CLTF
0.5030.503
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT Z1   /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1    /*05HANG R     765.0 - 05JEFRSO     765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1   /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1   /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1   /*05HANG R     765.0 - 05JEFRSO     765.0
 REMOVE UNIT 1A FROM BUS 247245                    /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                    /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                    /*05HRKG1S      18.0
 REMOVE UNIT 2 FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2A FROM BUS 247248                    /*05HRKG2A      18.0
 REMOVE UNIT 2S FROM BUS 247250                    /*05HRKG2S      18.0
END
CONTINGENCY 'COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A'
 TRIP BRANCH FROM BUS 270790 TO BUS 270770 CKT 1   /*KATYDID  ; B 345.0 - GOODINGS ; B 345.0
 TRIP BRANCH FROM BUS 270827 TO BUS 270769 CKT 1   /*NEVADA   ; R 345.0 - GOODINGS ; R 345.0
END
CONTINGENCY 'COMED_P4_012-45-BT4-5___SRT-A'
 TRIP BRANCH FROM BUS 270716 TO BUS 270736 CKT 1    /*DRESDEN  ; B 345.0 - ELWOOD   ; B 345.0
 TRIP BRANCH FROM BUS 270716 TO BUS 276659 CKT 1    /*DRESDEN  ; B 345.0 - AB1-122 TAP2 345.0
 TRIP BRANCH FROM BUS 270736 TO BUS 270737 CKT Z1   /*ELWOOD   ; B 345.0 - ELWOOD   ; R 345.0
END
243206 to 246999 ckt 1
246999 to 242928 ckt 1
270855 to 349662 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP
05DUMONT-05SORENS 765.0 kV Ckt 1 line
AEP_P7-1_#11046___SRT-A
TowerAC100.52 %4142.0B4163.6410.2
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC144.48 %1075.0B1553.152.89
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC144.47 %1075.0B1553.12.89
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Base Case
SingleAC109.11 %1075.0A1172.981.81
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC148.85 %971.0B1445.355.03
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC148.76 %971.0B1444.445.07
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC148.76 %971.0B1444.445.07
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC126.52 %1399.0B1770.057.37
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC126.52 %1399.0B1769.987.37
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC126.5 %1399.0B1769.757.34
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC100.85 %1399.0B1410.832.95
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC100.84 %1399.0B1410.812.95
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC110.64 %1399.0B1547.797.42
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC110.6 %1399.0B1547.347.45
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC110.6 %1399.0B1547.287.45
GD1CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4-6_116-345-R______SRT-A
BreakerAC107.57 %2297.0STE2470.9914.57
GD1CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4_116-45-L11614__SRT-A
BreakerAC103.27 %2297.0STE2372.114.9
GD1CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4_112-45-BT4-5___SRT-A
BreakerAC100.41 %2297.0STE2306.4617.84
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC126.65 %970.0STE1228.525.07
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC126.65 %970.0STE1228.525.07
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC126.64 %970.0STE1228.45.03
GD1CE
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
COMED_P4_112-65-BT5-6___SRT-A
BreakerAC116.26 %1469.0STE1707.816.62
GD1CE
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
COMED_P4_112-65-BT2-3___SRT-A
BreakerAC119.29 %1469.0STE1752.46.8
GD1CE
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_112-65-BT5-6___SRT-A
BreakerAC116.43 %1469.0STE1710.316.62
GD1CE
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_112-65-BT2-3___SRT-A
BreakerAC119.46 %1469.0STE1754.836.8

Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P7-1_#11046___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11046___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.52 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4163.64
MW Contribution:10.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
4.4117647058823533.75
962781AG1-127 C
Adder
11.6764705882352959.925
962782AG1-127 E
Adder
7.77058823529411856.605
965681AG1-436 C
50/50
16.69316.693
965682AG1-436 E
50/50
11.12911.129
966091AG1-478 C
Adder
3.35058823529411762.848
966092AG1-478 E
Adder
0.84235294117647050.716
966441AG1-513 C
Adder
0.84235294117647050.716
966442AG1-513 E
Adder
1.26235294117647071.073
24796705OLIV SLR E
Adder
0.52823529411764710.449
290021O50 E
Adder
31.95647058823529527.163
290051GSG-6; E
Adder
17.55176470588235614.919
295109WESTBROOK E
Adder
9.3964705882352947.987
295111SUBLETTE E
Adder
4.5682352941176473.883
910542X3-005 E
Adder
1.20352941176470571.023
918052AA1-018 E OP
Adder
26.60117647058823622.611
933911AD1-013 C
Adder
3.08941176470588232.626
933912AD1-013 E
Adder
4.9341176470588244.194
934722AD1-100 E
Adder
149.50823529411764127.082
937002AD2-134 E
Adder
16.9705882352941214.425
958481AF2-142 C
Adder
18.34588235294117515.594
958482AF2-142 E
Adder
12.2305882352941210.396
958491AF2-143 C
Adder
18.03411764705882415.329
958492AF2-143 E
Adder
12.0223529411764710.219
959351AF2-226 C
Adder
4.0788235294117653.467
959352AF2-226 E
Adder
6.117647058823535.2
960281AF2-319 C
Adder
4.0788235294117653.467
960282AF2-319 E
Adder
6.117647058823535.2
960582AF2-349 E
Adder
60.28705882352941451.244
960681AF2-359 C
50/50
16.69316.693
960682AF2-359 E
50/50
11.12911.129
960751AF2-366 C
Adder
11.6435294117647079.897
960752AF2-366 E
Adder
7.7623529411764716.598
24344005CKG1
50/50
36.32536.325
24344105CKG2
50/50
55.71455.714
274660LASCO STA;1U
50/50
39.69139.691
274661LASCO STA;2U
50/50
39.8239.82
274675JOLIET 29;7U
Adder
116.6376470588235399.142
274676JOLIET 29;8U
Adder
116.6341176470588299.139
274682WAUKEGAN ;7U
Adder
67.7223529411764757.564
274683WAUKEGAN ;8U
Adder
73.0517647058823662.094
274687WILL CNTY;4U
Adder
108.1341176470588391.914
274771LINCOLN ;2U
50/50
2.8472.847
274772LINCOLN ;3U
50/50
2.8472.847
274773LINCOLN ;4U
50/50
2.8472.847
274774LINCOLN ;5U
50/50
2.8472.847
274775LINCOLN ;6U
50/50
2.8472.847
274776LINCOLN ;7U
50/50
2.8472.847
274777LINCOLN ;8U
50/50
2.8472.847
274788SE CHICAG;5U
Adder
7.93999999999999956.749
274789SE CHICAG;6U
Adder
7.93999999999999956.749
274790SE CHICAG;7U
Adder
7.93999999999999956.749
274791SE CHICAG;8U
Adder
7.93999999999999956.749
274792SE CHICAG;9U
Adder
7.9305882352941186.741
274793SE CHICAG;0U
Adder
7.9305882352941186.741
274794SE CHICAG;1U
Adder
7.9305882352941186.741
274795SE CHICAG;2U
Adder
7.9305882352941186.741
276591L-013 2
Adder
6.0611764705882365.152
293061N-015 E
Adder
25.37882352941176521.572
293644O22 E1
Adder
23.4329411764705919.918
293645O22 E2
Adder
26.8376470588235322.812
294392P-010 E
Adder
32.2305882352941227.396
933411AC2-154 C
Adder
4.0564705882352943.448
933412AC2-154 E
Adder
6.6188235294117655.626
957331AF2-027 C
Adder
4.1035294117647063.488
957332AF2-027 E
Adder
6.1552941176470595.232
957471AF2-041 C
Adder
35.81882352941176630.446
957472AF2-041 E
Adder
16.55176470588235614.069
274674JOLIET 9 ;6U
Adder
59.4611764705882450.542
938851AE1-113 C
Adder
13.18235294117647211.205
938852AE1-113 E
Adder
46.73529411764706539.725
934101AD2-000 1
Adder
9.6658823529411778.216
934111AD2-000 2
Adder
9.7294117647058828.27
270100AB1-080 CT1
50/50
8.4898.489
270101AB1-080 CT2
50/50
8.4898.489
270102AB1-080 ST
50/50
9.1849.184
275149KELLYCK ;1E
Adder
29.89176470588235525.408
293519PILOT HIL;1E
Adder
29.89176470588235525.408
290108LEEDK;1U E
Adder
40.1234.102
916221Z1-073 E
Adder
12.36823529411764810.513
936292AD2-038 E
Adder
24.7670588235294121.052
936371AD2-047 C
Adder
7.2600000000000016.171
936372AD2-047 E
Adder
35.4435294117647130.127
936461AD2-060 C
Adder
4.2705882352941183.63
936511AD2-066 C
Adder
13.97882352941176411.882
936512AD2-066 E
Adder
9.3188235294117667.921
942421AE2-255 C
Adder
4.9929411764705884.244
942422AE2-255 E
Adder
14.97882352941176412.732
942651AE2-281 C
Adder
1.40235294117647061.192
942652AE2-281 E
Adder
8.6164705882352957.324
943121AE2-341 C
Adder
21.2623529411764718.073
943122AE2-341 E
Adder
10.4411764705882368.875
943591AF1-030 C
Adder
14.1412.019
943592AF1-030 E
Adder
6.9952941176470595.946
944932AF1-158 E
Adder
12.53176470588235210.652
959091AF2-200 C
Adder
23.87882352941176520.297
960591AF2-350 C
Adder
12.81058823529411810.889
960592AF2-350 E
Adder
8.5411764705882357.26
961501AF2-441 C
Adder
17.18352941176470614.606
961502AF2-441 E
Adder
25.77529411764705721.909
939321AE1-163 C
Adder
9.8188235294117648.346
939322AE1-163 E
Adder
60.3141176470588351.267
939351AE1-166 C
Adder
16.6614.161
939352AE1-166 E
Adder
15.37764705882352913.071
939401AE1-172 C
Adder
9.0694117647058817.709
939402AE1-172 E
Adder
42.46235294117647636.093
946671AF1-331 C
Adder
4.0117647058823533.41
962691AG1-118 C
Adder
36.9352941176470631.395
962692AG1-118 E
Adder
24.62352941176470720.93
941551AE2-152 C
Adder
19.2223529411764716.339
941552AE2-152 E
Adder
12.8152941176470610.893
957371AF2-031 C
Adder
1.71647058823529421.459
957372AF2-031 E
Adder
2.5752941176470592.189
958011AF2-095 C
Adder
18.44823529411764815.681
958012AF2-095 E
Adder
12.29882352941176610.454
965791AG1-447 C
50/50
12.24212.242
274770LINCOLN ;1U
50/50
2.8472.847
920272AA2-123 E
Adder
4.76941176470588254.054
276170Z1-108 E
Adder
4.837647058823534.112
276675AE2-062 E
Adder
0.249411764705882360.212
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
1.4661.466
CBM West 1LTFEXP_CBM-W1->PJM
CBM
235.985235.985
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.62846.628
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
5.225.22
NYPJM->LTFIMP_NY
CLTF
2.7622.762
LGEELTFEXP_LGEE->PJM
CLTF
1.661.66
WECLTFEXP_WEC->PJM
CLTF
6.4986.498
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.9160.916
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.4090.409
TVALTFEXP_TVA->PJM
CLTF
5.1695.169
MECLTFEXP_MEC->PJM
CLTF
23.96923.969
LAGNLTFEXP_LAGN->PJM
CLTF
9.4439.443
SIGELTFEXP_SIGE->PJM
CLTF
0.560.56
O66PJM->LTFIMP_O-066
CMTX_NF
33.48333.483

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:144.48 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1553.15
MW Contribution:2.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
962781AG1-127 C
Adder
7.92823529411764756.739
965091AG1-374 C
Adder
19.1976470588235316.318
966091AG1-478 C
Adder
2.38941176470588262.031
966441AG1-513 C
Adder
0.57647058823529410.49
933911AD1-013 C
Adder
2.08705882352941161.774
942111AE2-223 C
Adder
2.17764705882352951.851
958481AF2-142 C
Adder
12.7223529411764710.814
958491AF2-143 C
Adder
12.40117647058823610.541
959081AF2-199 C
Adder
8.0647058823529436.855
959341AF2-225 C
Adder
7.0364705882352945.981
959351AF2-226 C
Adder
2.89058823529411772.457
959611AF2-252 C
Adder
2.1329411764705881.813
960281AF2-319 C
Adder
2.89058823529411772.457
960611AF2-352 C
Adder
2.1329411764705881.813
960751AF2-366 C
Adder
7.9070588235294126.721
274675JOLIET 29;7U
Adder
82.4117647058823570.05
274676JOLIET 29;8U
Adder
82.4152941176470670.053
274682WAUKEGAN ;7U
Adder
46.7423529411764739.731
274683WAUKEGAN ;8U
Adder
50.3941176470588342.835
274687WILL CNTY;4U
Adder
78.0176470588235366.315
274723RIVER EC ;12
80/20
5.1225.122
274724RIVER EC ;11
80/20
5.1235.123
274752CRETE EC ;2U
80/20
1.941.94
274753CRETE EC ;3U
80/20
1.941.94
274754CRETE EC ;4U
80/20
1.941.94
274788SE CHICAG;5U
80/20
7.2327.232
274789SE CHICAG;6U
80/20
7.2327.232
274790SE CHICAG;7U
80/20
7.2327.232
274791SE CHICAG;8U
80/20
7.2327.232
274792SE CHICAG;9U
80/20
7.1437.143
274793SE CHICAG;0U
80/20
7.1437.143
274794SE CHICAG;1U
80/20
7.1437.143
274795SE CHICAG;2U
80/20
7.1437.143
274799UNIV PARK;2U
80/20
1.3961.396
274800UNIV PARK;3U
80/20
1.3961.396
274801UNIV PARK;4U
80/20
1.3961.396
274826FISK ;BP
80/20
2.6552.655
274827FISK ;RP
80/20
1.8821.882
274887PILOT HIL;1U
80/20
0.8970.897
274888KELLY CRK;1U
80/20
0.8970.897
276164X3-005 C
80/20
0.0990.099
933411AC2-154 C
80/20
2.992.99
939061AE1-134 2
Adder
1.54823529411764721.316
957331AF2-027 C
Adder
2.82588235294117672.402
957471AF2-041 C
Adder
24.1929411764705920.564
274674JOLIET 9 ;6U
Adder
42.3282352941176535.979
938851AE1-113 C
Adder
9.0329411764705887.678
934101AD2-000 1
Adder
6.542352941176475.561
934111AD2-000 2
Adder
6.8035294117647065.783
926821AC1-168 C
Adder
1.28941176470588251.096
936371AD2-047 C
80/20
5.355.35
936461AD2-060 C
80/20
3.1473.147
936511AD2-066 C
Adder
9.5376470588235298.107
942421AE2-255 C
Adder
3.42117647058823552.908
942651AE2-281 C
Adder
0.96470588235294120.82
943121AE2-341 C
Adder
14.46117647058823512.292
943591AF1-030 C
Adder
9.6164705882352938.174
959091AF2-200 C
Adder
16.12823529411764813.709
960591AF2-350 C
80/20
9.4429.442
961501AF2-441 C
80/20
14.87514.875
938861AE1-114 C
Adder
4.4423529411764713.776
939321AE1-163 C
Adder
6.7517647058823535.739
939351AE1-166 C
Adder
11.6094117647058829.868
939401AE1-172 C
Adder
6.1070588235294125.191
939741AE1-205 C
Adder
9.3811764705882357.974
946321AF1-296 C
Adder
4.0305882352941183.426
946671AF1-331 C
Adder
2.71058823529411752.304
962691AG1-118 C
Adder
25.1023529411764721.337
941551AE2-152 C
Adder
13.39529411764705811.386
957371AF2-031 C
80/20
1.5531.553
958011AF2-095 C
80/20
13.59713.597
965931AG1-462 C
Adder
18.16117647058823415.437
274798UNIV PARK;1U
80/20
1.4061.406
274751CRETE EC ;1U
80/20
1.941.94
990547J1333 G
External Queue
40.523937225341840.5239372253418
990552J1334 G
External Queue
40.523937225341840.5239372253418
990557J1335 G
External Queue
40.523937225341840.5239372253418
990562J1336 G
External Queue
40.523937225341840.5239372253418
990577J1339
External Queue
26.574090957641626.5740909576416
990582J1340
External Queue
26.574090957641626.5740909576416
990647J1355
External Queue
42.2684173583984442.26841735839844
990662J1358
External Queue
14.93047142028808614.930471420288086
955742J1058 G
External Queue
35.282848358154335.2828483581543
990762J1386
External Queue
12.93081378936767612.930813789367676
991247J1684 G
External Queue
33.6162452697753933.61624526977539
991332J1785
External Queue
13.53217697143554713.532176971435547
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8260.826
CBM West 1LTFEXP_CBM-W1->PJM
CBM
118.129118.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.88718.887
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
NYPJM->LTFIMP_NY
CLTF
1.271.27
WECLTFEXP_WEC->PJM
CLTF
4.4234.423
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5520.552
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2810.281
TVALTFEXP_TVA->PJM
CLTF
1.7951.795
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.510.51
MECLTFEXP_MEC->PJM
CLTF
14.93414.934
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.4171.417
LAGNLTFEXP_LAGN->PJM
CLTF
4.3274.327
SIGELTFEXP_SIGE->PJM
CLTF
0.060.06

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:144.47 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1553.1
MW Contribution:2.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
962781AG1-127 C
Adder
7.92823529411764756.739
965091AG1-374 C
Adder
19.1976470588235316.318
966091AG1-478 C
Adder
2.38941176470588262.031
966441AG1-513 C
Adder
0.57647058823529410.49
933911AD1-013 C
Adder
2.08705882352941161.774
942111AE2-223 C
Adder
2.17764705882352951.851
958481AF2-142 C
Adder
12.7223529411764710.814
958491AF2-143 C
Adder
12.40117647058823610.541
959081AF2-199 C
Adder
8.0647058823529436.855
959341AF2-225 C
Adder
7.0364705882352945.981
959351AF2-226 C
Adder
2.89058823529411772.457
959611AF2-252 C
Adder
2.1329411764705881.813
960281AF2-319 C
Adder
2.89058823529411772.457
960611AF2-352 C
Adder
2.1329411764705881.813
960751AF2-366 C
Adder
7.9070588235294126.721
274675JOLIET 29;7U
Adder
82.4117647058823570.05
274676JOLIET 29;8U
Adder
82.4152941176470670.053
274682WAUKEGAN ;7U
Adder
46.7423529411764739.731
274683WAUKEGAN ;8U
Adder
50.3941176470588342.835
274687WILL CNTY;4U
Adder
78.0176470588235366.315
274723RIVER EC ;12
80/20
5.1225.122
274724RIVER EC ;11
80/20
5.1235.123
274752CRETE EC ;2U
80/20
1.941.94
274753CRETE EC ;3U
80/20
1.941.94
274754CRETE EC ;4U
80/20
1.941.94
274788SE CHICAG;5U
80/20
7.2327.232
274789SE CHICAG;6U
80/20
7.2327.232
274790SE CHICAG;7U
80/20
7.2327.232
274791SE CHICAG;8U
80/20
7.2327.232
274792SE CHICAG;9U
80/20
7.1437.143
274793SE CHICAG;0U
80/20
7.1437.143
274794SE CHICAG;1U
80/20
7.1437.143
274795SE CHICAG;2U
80/20
7.1437.143
274799UNIV PARK;2U
80/20
1.3961.396
274800UNIV PARK;3U
80/20
1.3961.396
274801UNIV PARK;4U
80/20
1.3961.396
274826FISK ;BP
80/20
2.6552.655
274827FISK ;RP
80/20
1.8821.882
274887PILOT HIL;1U
80/20
0.8970.897
274888KELLY CRK;1U
80/20
0.8970.897
276164X3-005 C
80/20
0.0990.099
933411AC2-154 C
80/20
2.992.99
939061AE1-134 2
Adder
1.54823529411764721.316
957331AF2-027 C
Adder
2.82588235294117672.402
957471AF2-041 C
Adder
24.1929411764705920.564
274674JOLIET 9 ;6U
Adder
42.3282352941176535.979
938851AE1-113 C
Adder
9.0329411764705887.678
934101AD2-000 1
Adder
6.542352941176475.561
934111AD2-000 2
Adder
6.8035294117647065.783
926821AC1-168 C
Adder
1.28941176470588251.096
936371AD2-047 C
80/20
5.355.35
936461AD2-060 C
80/20
3.1473.147
936511AD2-066 C
Adder
9.5376470588235298.107
942421AE2-255 C
Adder
3.42117647058823552.908
942651AE2-281 C
Adder
0.96470588235294120.82
943121AE2-341 C
Adder
14.46117647058823512.292
943591AF1-030 C
Adder
9.6164705882352938.174
959091AF2-200 C
Adder
16.12823529411764813.709
960591AF2-350 C
80/20
9.4429.442
961501AF2-441 C
80/20
14.87514.875
938861AE1-114 C
Adder
4.4423529411764713.776
939321AE1-163 C
Adder
6.7517647058823535.739
939351AE1-166 C
Adder
11.6094117647058829.868
939401AE1-172 C
Adder
6.1070588235294125.191
939741AE1-205 C
Adder
9.3811764705882357.974
946321AF1-296 C
Adder
4.0305882352941183.426
946671AF1-331 C
Adder
2.71058823529411752.304
962691AG1-118 C
Adder
25.1023529411764721.337
941551AE2-152 C
Adder
13.39529411764705811.386
957371AF2-031 C
80/20
1.5531.553
958011AF2-095 C
80/20
13.59713.597
965931AG1-462 C
Adder
18.16117647058823415.437
274798UNIV PARK;1U
80/20
1.4061.406
274751CRETE EC ;1U
80/20
1.941.94
990547J1333 G
External Queue
40.523937225341840.5239372253418
990552J1334 G
External Queue
40.523937225341840.5239372253418
990557J1335 G
External Queue
40.523937225341840.5239372253418
990562J1336 G
External Queue
40.523937225341840.5239372253418
990577J1339
External Queue
26.574090957641626.5740909576416
990582J1340
External Queue
26.574090957641626.5740909576416
990647J1355
External Queue
42.2684173583984442.26841735839844
990662J1358
External Queue
14.93047142028808614.930471420288086
955742J1058 G
External Queue
35.282848358154335.2828483581543
990762J1386
External Queue
12.93081378936767612.930813789367676
991247J1684 G
External Queue
33.6162452697753933.61624526977539
991332J1785
External Queue
13.53217697143554713.532176971435547
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8260.826
CBM West 1LTFEXP_CBM-W1->PJM
CBM
118.129118.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.88718.887
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
NYPJM->LTFIMP_NY
CLTF
1.271.27
WECLTFEXP_WEC->PJM
CLTF
4.4234.423
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5520.552
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2810.281
TVALTFEXP_TVA->PJM
CLTF
1.7951.795
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.510.51
MECLTFEXP_MEC->PJM
CLTF
14.93414.934
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.4171.417
LAGNLTFEXP_LAGN->PJM
CLTF
4.3274.327
SIGELTFEXP_SIGE->PJM
CLTF
0.060.06

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.11 %
Rating:1075.0 MVA
Rating Type:A
MVA to Mitigate:1172.98
MW Contribution:1.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
962781AG1-127 C
Adder
4.4894117647058823.816
965091AG1-374 C
Adder
11.249.554
966091AG1-478 C
Adder
1.46941176470588241.249
966441AG1-513 C
Adder
0.32705882352941180.278
933911AD1-013 C
Adder
1.18705882352941171.009
942111AE2-223 C
Adder
1.2717647058823531.081
958481AF2-142 C
Adder
7.8258823529411776.652
958491AF2-143 C
Adder
7.5847058823529416.447
959081AF2-199 C
Adder
4.6141176470588243.922
959341AF2-225 C
Adder
4.1082352941176473.492
959351AF2-226 C
Adder
1.80588235294117651.535
959611AF2-252 C
Adder
1.24941176470588241.062
960281AF2-319 C
Adder
1.80588235294117651.535
960611AF2-352 C
Adder
1.24941176470588241.062
960751AF2-366 C
Adder
4.4776470588235293.806
274675JOLIET 29;7U
Adder
49.9447058823529542.453
274676JOLIET 29;8U
Adder
49.9529411764705942.46
274682WAUKEGAN ;7U
Adder
27.29294117647059223.199
274683WAUKEGAN ;8U
Adder
29.42352941176470825.01
274687WILL CNTY;4U
Adder
48.5929411764705941.304
274723RIVER EC ;12
80/20
3.8963.896
274724RIVER EC ;11
80/20
3.9023.902
274752CRETE EC ;2U
80/20
1.4551.455
274753CRETE EC ;3U
80/20
1.4551.455
274754CRETE EC ;4U
80/20
1.4551.455
274788SE CHICAG;5U
80/20
5.5385.538
274789SE CHICAG;6U
80/20
5.5385.538
274790SE CHICAG;7U
80/20
5.5385.538
274791SE CHICAG;8U
80/20
5.5385.538
274792SE CHICAG;9U
80/20
5.4655.465
274793SE CHICAG;0U
80/20
5.4655.465
274794SE CHICAG;1U
80/20
5.4655.465
274795SE CHICAG;2U
80/20
5.4655.465
274799UNIV PARK;2U
80/20
0.9170.917
274800UNIV PARK;3U
80/20
0.9170.917
274801UNIV PARK;4U
80/20
0.9170.917
274826FISK ;BP
80/20
1.7681.768
274827FISK ;RP
80/20
1.2531.253
274887PILOT HIL;1U
80/20
0.570.57
274888KELLY CRK;1U
80/20
0.570.57
276164X3-005 C
80/20
0.070.07
933411AC2-154 C
80/20
1.91.9
939061AE1-134 2
Adder
0.89294117647058820.759
957331AF2-027 C
Adder
1.64941176470588241.402
957471AF2-041 C
Adder
13.84352941176470611.767
274674JOLIET 9 ;6U
Adder
25.73058823529411821.871
938851AE1-113 C
Adder
5.4270588235294124.613
934101AD2-000 1
Adder
3.68941176470588243.136
934111AD2-000 2
Adder
4.077647058823533.466
926821AC1-168 C
Adder
0.75294117647058820.64
936371AD2-047 C
80/20
3.43.4
936461AD2-060 C
80/20
22
936511AD2-066 C
Adder
5.6788235294117654.827
942421AE2-255 C
Adder
2.0552941176470591.747
942651AE2-281 C
Adder
0.58941176470588240.501
943121AE2-341 C
Adder
7.99529411764705966.796
943591AF1-030 C
Adder
5.3176470588235294.52
959091AF2-200 C
Adder
9.2294117647058827.845
960591AF2-350 C
80/20
66
961501AF2-441 C
80/20
10.91610.916
938861AE1-114 C
Adder
2.562.176
939321AE1-163 C
Adder
4.1294117647058823.51
939351AE1-166 C
Adder
6.7717647058823545.756
939401AE1-172 C
Adder
3.55294117647058853.02
939741AE1-205 C
Adder
5.4776470588235294.656
946321AF1-296 C
Adder
2.34000000000000031.989
946671AF1-331 C
Adder
1.54235294117647051.311
962691AG1-118 C
Adder
14.20823529411764812.077
941551AE2-152 C
Adder
7.8141176470588246.642
957371AF2-031 C
80/20
1.1831.183
958011AF2-095 C
80/20
8.6418.641
965931AG1-462 C
Adder
10.5505882352941188.968
274798UNIV PARK;1U
80/20
0.9230.923
274751CRETE EC ;1U
80/20
1.4551.455
990547J1333 G
External Queue
40.5459747314453140.54597473144531
990552J1334 G
External Queue
40.5459747314453140.54597473144531
990557J1335 G
External Queue
40.5459747314453140.54597473144531
990562J1336 G
External Queue
40.5459747314453140.54597473144531
990577J1339
External Queue
26.69731712341308626.697317123413086
990582J1340
External Queue
26.69731712341308626.697317123413086
990647J1355
External Queue
45.41125869750976645.411258697509766
990662J1358
External Queue
15.68888854980468815.688888549804688
955742J1058 G
External Queue
34.25693511962890634.256935119628906
990762J1386
External Queue
12.26621055603027312.266210556030273
991247J1684 G
External Queue
33.68902206420898433.689022064208984
991332J1785
External Queue
15.41609573364257815.416095733642578
991337J1802
External Queue
11.3996610641479511.39966106414795
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.4540.454
CBM West 1LTFEXP_CBM-W1->PJM
CBM
75.73675.736
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.85611.856
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
NYPJM->LTFIMP_NY
CLTF
0.7460.746
WECLTFEXP_WEC->PJM
CLTF
2.5782.578
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2990.299
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1480.148
TVALTFEXP_TVA->PJM
CLTF
1.1741.174
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.2290.229
MECLTFEXP_MEC->PJM
CLTF
8.7698.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.6110.611
LAGNLTFEXP_LAGN->PJM
CLTF
2.6762.676
SIGELTFEXP_SIGE->PJM
CLTF
0.0530.053

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.85 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1445.35
MW Contribution:5.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.21411764705882331.882
962012AG1-044 E
Adder
0.0529411764705882350.045
962781AG1-127 C
Adder
5.8976470588235295.013
962782AG1-127 E
Adder
3.92470588235294133.336
965681AG1-436 C
50/50
63.75263.752
965682AG1-436 E
50/50
42.50142.501
966091AG1-478 C
Adder
1.7552941176470591.492
966092AG1-478 E
Adder
0.44117647058823530.375
966441AG1-513 C
Adder
0.430588235294117660.366
966442AG1-513 E
Adder
0.64470588235294120.548
290021O50 E
Adder
16.24352941176470813.807
290051GSG-6; E
Adder
8.8082352941176477.487
295109WESTBROOK E
Adder
4.7152941176470594.008
295111SUBLETTE E
Adder
2.29294117647058831.949
910542X3-005 E
Adder
0.53058823529411770.451
918052AA1-018 E OP
Adder
14.7952941176470612.576
933911AD1-013 C
Adder
1.55058823529411781.318
933912AD1-013 E
Adder
2.47764705882352932.106
934722AD1-100 E
Adder
76.1635294117647164.739
937002AD2-134 E
Adder
8.5164705882352937.239
937312AD2-172 E
Adder
2.84588235294117682.419
958481AF2-142 C
Adder
10.2035294117647068.673
958482AF2-142 E
Adder
6.8023529411764715.782
958491AF2-143 C
Adder
9.748.279
958492AF2-143 E
Adder
6.4929411764705885.519
958912AF2-182 E
Adder
28.6258823529411824.332
959081AF2-199 C
Adder
5.9858823529411775.088
959082AF2-199 E
Adder
2.99294117647058842.544
959351AF2-226 C
Adder
2.0105882352941181.709
959352AF2-226 E
Adder
3.01647058823529422.564
960281AF2-319 C
Adder
2.0105882352941181.709
960282AF2-319 E
Adder
3.01647058823529422.564
960582AF2-349 E
Adder
30.4847058823529425.912
960681AF2-359 C
50/50
63.75263.752
960682AF2-359 E
50/50
42.50142.501
960751AF2-366 C
Adder
5.8811764705882354.999
960752AF2-366 E
Adder
3.92117647058823553.333
274675JOLIET 29;7U
Adder
61.79058823529411652.522
274676JOLIET 29;8U
Adder
61.7682352941176552.503
274682WAUKEGAN ;7U
Adder
34.8235294117647129.6
274683WAUKEGAN ;8U
Adder
37.5458823529411831.914
274687WILL CNTY;4U
Adder
55.58000000000000547.243
274859EASYR;U1 E
Adder
10.0658823529411758.556
274860EASYR;U2 E
Adder
10.0658823529411758.556
276591L-013 2
Adder
3.09411764705882362.63
293061N-015 E
Adder
13.10117647058823411.136
293644O22 E1
Adder
11.5517647058823549.819
293645O22 E2
Adder
13.2305882352941211.246
293715O-029 E
Adder
8.1494117647058816.927
293716O-029 E
Adder
4.46823529411764753.798
293717O-029 E
Adder
4.1070588235294123.491
294392P-010 E
Adder
16.63882352941176614.143
294763P-046 E
Adder
7.9094117647058826.723
933411AC2-154 C
Adder
2.10235294117647081.787
933412AC2-154 E
Adder
3.42941176470588262.915
939061AE1-134 2
Adder
1.14705882352941170.975
940502AE2-035 E
Adder
2.84588235294117682.419
957331AF2-027 C
Adder
2.1047058823529411.789
957332AF2-027 E
Adder
3.15764705882352952.684
957471AF2-041 C
Adder
17.9576470588235315.264
957472AF2-041 E
Adder
8.9788235294117647.632
274674JOLIET 9 ;6U
Adder
31.0329411764705926.378
274890CAYUG;1U E
Adder
11.395294117647069.686
274891CAYUG;2U E
Adder
11.395294117647069.686
938851AE1-113 C
Adder
6.75.695
938852AE1-113 E
Adder
23.75647058823529520.193
934101AD2-000 1
Adder
4.8788235294117654.147
934111AD2-000 2
Adder
5.0470588235294124.29
275149KELLYCK ;1E
Adder
15.48823529411764713.165
293516O-009 E
Adder
15.7576470588235313.394
293519PILOT HIL;1E
Adder
15.48823529411764713.165
290108LEEDK;1U E
Adder
20.2152941176470617.183
916221Z1-073 E
Adder
6.2070588235294125.276
274805UNIV PK N;1U
50/50
1.9031.903
274807UNIV PK N;3U
50/50
1.9151.915
274808UNIV PK N;4U
50/50
1.9071.907
926821AC1-168 C
Adder
0.95764705882352940.814
926822AC1-168 E
Adder
6.4258823529411765.462
936292AD2-038 E
Adder
13.37529411764705911.369
936371AD2-047 C
Adder
3.76235294117647053.198
936372AD2-047 E
Adder
18.36705882352941215.612
936461AD2-060 C
Adder
2.2129411764705881.881
936511AD2-066 C
Adder
7.1305882352941186.061
936512AD2-066 E
Adder
4.7541176470588244.041
942421AE2-255 C
Adder
2.53764705882352942.157
942422AE2-255 E
Adder
7.61411764705882456.472
942651AE2-281 C
Adder
0.75764705882352950.644
942652AE2-281 E
Adder
4.6529411764705893.955
943121AE2-341 C
Adder
10.7729411764705899.157
943122AE2-341 E
Adder
5.2905882352941184.497
943591AF1-030 C
Adder
7.1635294117647066.089
943592AF1-030 E
Adder
3.54470588235294143.013
959091AF2-200 C
Adder
11.97176470588235410.176
959092AF2-200 E
Adder
7.98117647058823556.784
960591AF2-350 C
Adder
6.637647058823535.642
960592AF2-350 E
Adder
4.4247058823529413.761
938861AE1-114 C
Adder
3.2964705882352942.802
938862AE1-114 E
Adder
11.244705882352949.558
939321AE1-163 C
Adder
5.302352941176474.507
939322AE1-163 E
Adder
32.5729411764705927.687
939351AE1-166 C
Adder
8.4870588235294137.214
939352AE1-166 E
Adder
7.8341176470588236.659
939401AE1-172 C
Adder
4.4505882352941173.783
939402AE1-172 E
Adder
20.8352941176470617.71
946152AF1-280 E
Adder
19.08352941176470816.221
946671AF1-331 C
Adder
2.01411764705882361.712
962691AG1-118 C
Adder
18.6752941176470615.874
962692AG1-118 E
Adder
12.45058823529411810.583
941551AE2-152 C
Adder
9.7929411764705888.324
941552AE2-152 E
Adder
6.5282352941176485.549
958011AF2-095 C
Adder
9.557647058823538.124
958012AF2-095 E
Adder
6.3717647058823535.416
965791AG1-447 C
50/50
46.75146.751
274810UNIV PK N;6U
50/50
1.9071.907
274811UNIV PK N;7U
50/50
1.9151.915
274812UNIV PK N;8U
50/50
1.8991.899
274813UNIV PK N;9U
50/50
1.8991.899
274814UNIV PK N;0U
50/50
1.8911.891
274815UNIV PK N;XU
50/50
1.9031.903
274816UNIV PK N;YU
50/50
1.9151.915
920272AA2-123 E
Adder
2.4188235294117652.056
276170Z1-108 E
Adder
2.4670588235294122.097
276626AG1-044 E
Adder
0.061176470588235290.052
276675AE2-062 E
Adder
0.134117647058823540.114
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6070.607
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.23368.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.47412.474
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7291.729
NYPJM->LTFIMP_NY
CLTF
0.9310.931
WECLTFEXP_WEC->PJM
CLTF
3.2883.288
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4090.409
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.210.21
TVALTFEXP_TVA->PJM
CLTF
1.1671.167
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.4090.409
MECLTFEXP_MEC->PJM
CLTF
10.92410.924
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.1721.172
LAGNLTFEXP_LAGN->PJM
CLTF
2.992.99
SIGELTFEXP_SIGE->PJM
CLTF
0.0150.015
O66PJM->LTFIMP_O-066
CMTX_NF
11.09411.094

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.76 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1444.44
MW Contribution:5.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.22941176470588241.895
962012AG1-044 E
Adder
0.0529411764705882350.045
962781AG1-127 C
Adder
5.94117647058823555.05
962782AG1-127 E
Adder
3.9541176470588243.361
965681AG1-436 C
50/50
63.94963.949
965682AG1-436 E
50/50
42.63342.633
966091AG1-478 C
Adder
1.76941176470588251.504
966092AG1-478 E
Adder
0.44470588235294120.378
966441AG1-513 C
Adder
0.434117647058823550.369
966442AG1-513 E
Adder
0.65058823529411770.553
290021O50 E
Adder
16.3552941176470613.902
290051GSG-6; E
Adder
8.8682352941176487.538
295109WESTBROOK E
Adder
4.7482352941176474.036
295111SUBLETTE E
Adder
2.3082352941176471.962
910542X3-005 E
Adder
0.53764705882352950.457
918052AA1-018 E OP
Adder
14.9023529411764712.667
933911AD1-013 C
Adder
1.56117647058823541.327
933912AD1-013 E
Adder
2.49411764705882362.12
934722AD1-100 E
Adder
76.7823529411764765.265
937002AD2-134 E
Adder
8.5752941176470587.289
937312AD2-172 E
Adder
2.8647058823529412.435
958481AF2-142 C
Adder
10.2776470588235318.736
958482AF2-142 E
Adder
6.8517647058823535.824
958491AF2-143 C
Adder
9.8058823529411778.335
958492AF2-143 E
Adder
6.537647058823535.557
958912AF2-182 E
Adder
28.79647058823529424.477
959081AF2-199 C
Adder
6.0258823529411775.122
959082AF2-199 E
Adder
3.01294117647058852.561
959351AF2-226 C
Adder
2.0270588235294121.723
959352AF2-226 E
Adder
3.0411764705882352.585
960281AF2-319 C
Adder
2.0270588235294121.723
960282AF2-319 E
Adder
3.0411764705882352.585
960582AF2-349 E
Adder
30.726.095
960681AF2-359 C
50/50
63.94963.949
960682AF2-359 E
50/50
42.63342.633
960751AF2-366 C
Adder
5.9247058823529415.036
960752AF2-366 E
Adder
3.94941176470588263.357
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274676JOLIET 29;8U
Adder
62.29647058823529452.952
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
274687WILL CNTY;4U
Adder
56.08235294117647447.67
274859EASYR;U1 E
Adder
10.1270588235294138.608
274860EASYR;U2 E
Adder
10.1270588235294138.608
276591L-013 2
Adder
3.11882352941176462.651
293061N-015 E
Adder
13.20352941176470711.223
293644O22 E1
Adder
11.6458823529411759.899
293645O22 E2
Adder
13.33882352941176411.338
293715O-029 E
Adder
8.1929411764705896.964
293716O-029 E
Adder
4.4917647058823533.818
293717O-029 E
Adder
4.1282352941176473.509
294392P-010 E
Adder
16.76941176470588214.254
294763P-046 E
Adder
7.9611764705882366.767
933411AC2-154 C
Adder
2.1211764705882351.803
933412AC2-154 E
Adder
3.46117647058823552.942
939061AE1-134 2
Adder
1.15294117647058810.98
940502AE2-035 E
Adder
2.8647058823529412.435
957331AF2-027 C
Adder
2.1211764705882351.803
957332AF2-027 E
Adder
3.1823529411764712.705
957471AF2-041 C
Adder
18.07882352941176815.367
957472AF2-041 E
Adder
9.0400000000000017.684
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
274890CAYUG;1U E
Adder
11.4552941176470599.737
274891CAYUG;2U E
Adder
11.4552941176470599.737
938851AE1-113 C
Adder
6.7458823529411775.734
938852AE1-113 E
Adder
23.91882352941176420.331
934101AD2-000 1
Adder
4.91411764705882354.177
934111AD2-000 2
Adder
5.0882352941176484.325
275149KELLYCK ;1E
Adder
15.63058823529411813.286
293516O-009 E
Adder
15.8423529411764713.466
293519PILOT HIL;1E
Adder
15.63058823529411813.286
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
274805UNIV PK N;1U
50/50
1.9131.913
274807UNIV PK N;3U
50/50
1.9251.925
274808UNIV PK N;4U
50/50
1.9171.917
926821AC1-168 C
Adder
0.96235294117647050.818
926822AC1-168 E
Adder
6.4588235294117655.49
936292AD2-038 E
Adder
13.46705882352941211.447
936371AD2-047 C
Adder
3.7964705882352943.227
936372AD2-047 E
Adder
18.53411764705882415.754
936461AD2-060 C
Adder
2.2329411764705881.898
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
942421AE2-255 C
Adder
2.5552941176470592.172
942422AE2-255 E
Adder
7.6658823529411776.516
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
943121AE2-341 C
Adder
10.8588235294117659.23
943122AE2-341 E
Adder
5.3317647058823534.532
943591AF1-030 C
Adder
7.2211764705882366.138
943592AF1-030 E
Adder
3.5729411764705883.037
959091AF2-200 C
Adder
12.05294117647058810.245
959092AF2-200 E
Adder
8.0352941176470596.83
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
938861AE1-114 C
Adder
3.3164705882352942.819
938862AE1-114 E
Adder
11.315294117647069.618
939321AE1-163 C
Adder
5.3388235294117654.538
939322AE1-163 E
Adder
32.7952941176470627.876
939351AE1-166 C
Adder
8.555294117647067.272
939352AE1-166 E
Adder
7.897647058823536.713
939401AE1-172 C
Adder
4.4776470588235293.806
939402AE1-172 E
Adder
20.9647058823529417.82
946152AF1-280 E
Adder
19.1976470588235316.318
946671AF1-331 C
Adder
2.0282352941176471.724
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
941551AE2-152 C
Adder
9.8717647058823528.391
941552AE2-152 E
Adder
6.5811764705882365.594
958011AF2-095 C
Adder
9.6458823529411778.199
958012AF2-095 E
Adder
6.4305882352941185.466
965791AG1-447 C
50/50
46.89646.896
274810UNIV PK N;6U
50/50
1.9171.917
274811UNIV PK N;7U
50/50
1.9251.925
274812UNIV PK N;8U
50/50
1.9091.909
274813UNIV PK N;9U
50/50
1.9091.909
274814UNIV PK N;0U
50/50
1.9011.901
274815UNIV PK N;XU
50/50
1.9131.913
274816UNIV PK N;YU
50/50
1.9251.925
920272AA2-123 E
Adder
2.4364705882352942.071
276170Z1-108 E
Adder
2.48588235294117642.113
276626AG1-044 E
Adder
0.062352941176470590.053
276675AE2-062 E
Adder
0.135294117647058840.115
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
NYPJM->LTFIMP_NY
CLTF
0.9330.933
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.76 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1444.44
MW Contribution:5.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.22941176470588241.895
962012AG1-044 E
Adder
0.0529411764705882350.045
962781AG1-127 C
Adder
5.94117647058823555.05
962782AG1-127 E
Adder
3.9541176470588243.361
965681AG1-436 C
50/50
63.94963.949
965682AG1-436 E
50/50
42.63342.633
966091AG1-478 C
Adder
1.76941176470588251.504
966092AG1-478 E
Adder
0.44470588235294120.378
966441AG1-513 C
Adder
0.434117647058823550.369
966442AG1-513 E
Adder
0.65058823529411770.553
290021O50 E
Adder
16.3552941176470613.902
290051GSG-6; E
Adder
8.8682352941176487.538
295109WESTBROOK E
Adder
4.7482352941176474.036
295111SUBLETTE E
Adder
2.3082352941176471.962
910542X3-005 E
Adder
0.53764705882352950.457
918052AA1-018 E OP
Adder
14.9023529411764712.667
933911AD1-013 C
Adder
1.56117647058823541.327
933912AD1-013 E
Adder
2.49411764705882362.12
934722AD1-100 E
Adder
76.7823529411764765.265
937002AD2-134 E
Adder
8.5752941176470587.289
937312AD2-172 E
Adder
2.8647058823529412.435
958481AF2-142 C
Adder
10.2776470588235318.736
958482AF2-142 E
Adder
6.8517647058823535.824
958491AF2-143 C
Adder
9.8058823529411778.335
958492AF2-143 E
Adder
6.537647058823535.557
958912AF2-182 E
Adder
28.79647058823529424.477
959081AF2-199 C
Adder
6.0258823529411775.122
959082AF2-199 E
Adder
3.01294117647058852.561
959351AF2-226 C
Adder
2.0270588235294121.723
959352AF2-226 E
Adder
3.0411764705882352.585
960281AF2-319 C
Adder
2.0270588235294121.723
960282AF2-319 E
Adder
3.0411764705882352.585
960582AF2-349 E
Adder
30.726.095
960681AF2-359 C
50/50
63.94963.949
960682AF2-359 E
50/50
42.63342.633
960751AF2-366 C
Adder
5.9247058823529415.036
960752AF2-366 E
Adder
3.94941176470588263.357
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274676JOLIET 29;8U
Adder
62.29647058823529452.952
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
274687WILL CNTY;4U
Adder
56.08235294117647447.67
274859EASYR;U1 E
Adder
10.1270588235294138.608
274860EASYR;U2 E
Adder
10.1270588235294138.608
276591L-013 2
Adder
3.11882352941176462.651
293061N-015 E
Adder
13.20352941176470711.223
293644O22 E1
Adder
11.6458823529411759.899
293645O22 E2
Adder
13.33882352941176411.338
293715O-029 E
Adder
8.1929411764705896.964
293716O-029 E
Adder
4.4917647058823533.818
293717O-029 E
Adder
4.1282352941176473.509
294392P-010 E
Adder
16.76941176470588214.254
294763P-046 E
Adder
7.9611764705882366.767
933411AC2-154 C
Adder
2.1211764705882351.803
933412AC2-154 E
Adder
3.46117647058823552.942
939061AE1-134 2
Adder
1.15294117647058810.98
940502AE2-035 E
Adder
2.8647058823529412.435
957331AF2-027 C
Adder
2.1211764705882351.803
957332AF2-027 E
Adder
3.1823529411764712.705
957471AF2-041 C
Adder
18.07882352941176815.367
957472AF2-041 E
Adder
9.0400000000000017.684
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
274890CAYUG;1U E
Adder
11.4552941176470599.737
274891CAYUG;2U E
Adder
11.4552941176470599.737
938851AE1-113 C
Adder
6.7458823529411775.734
938852AE1-113 E
Adder
23.91882352941176420.331
934101AD2-000 1
Adder
4.91411764705882354.177
934111AD2-000 2
Adder
5.0882352941176484.325
275149KELLYCK ;1E
Adder
15.63058823529411813.286
293516O-009 E
Adder
15.8423529411764713.466
293519PILOT HIL;1E
Adder
15.63058823529411813.286
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
274805UNIV PK N;1U
50/50
1.9131.913
274807UNIV PK N;3U
50/50
1.9251.925
274808UNIV PK N;4U
50/50
1.9171.917
926821AC1-168 C
Adder
0.96235294117647050.818
926822AC1-168 E
Adder
6.4588235294117655.49
936292AD2-038 E
Adder
13.46705882352941211.447
936371AD2-047 C
Adder
3.7964705882352943.227
936372AD2-047 E
Adder
18.53411764705882415.754
936461AD2-060 C
Adder
2.2329411764705881.898
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
942421AE2-255 C
Adder
2.5552941176470592.172
942422AE2-255 E
Adder
7.6658823529411776.516
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
943121AE2-341 C
Adder
10.8588235294117659.23
943122AE2-341 E
Adder
5.3317647058823534.532
943591AF1-030 C
Adder
7.2211764705882366.138
943592AF1-030 E
Adder
3.5729411764705883.037
959091AF2-200 C
Adder
12.05294117647058810.245
959092AF2-200 E
Adder
8.0352941176470596.83
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
938861AE1-114 C
Adder
3.3164705882352942.819
938862AE1-114 E
Adder
11.315294117647069.618
939321AE1-163 C
Adder
5.3388235294117654.538
939322AE1-163 E
Adder
32.7952941176470627.876
939351AE1-166 C
Adder
8.555294117647067.272
939352AE1-166 E
Adder
7.897647058823536.713
939401AE1-172 C
Adder
4.4776470588235293.806
939402AE1-172 E
Adder
20.9658823529411817.821
946152AF1-280 E
Adder
19.1976470588235316.318
946671AF1-331 C
Adder
2.0282352941176471.724
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
941551AE2-152 C
Adder
9.8717647058823528.391
941552AE2-152 E
Adder
6.5811764705882365.594
958011AF2-095 C
Adder
9.6458823529411778.199
958012AF2-095 E
Adder
6.4305882352941185.466
965791AG1-447 C
50/50
46.89646.896
274810UNIV PK N;6U
50/50
1.9171.917
274811UNIV PK N;7U
50/50
1.9251.925
274812UNIV PK N;8U
50/50
1.9091.909
274813UNIV PK N;9U
50/50
1.9091.909
274814UNIV PK N;0U
50/50
1.9011.901
274815UNIV PK N;XU
50/50
1.9131.913
274816UNIV PK N;YU
50/50
1.9251.925
920272AA2-123 E
Adder
2.4364705882352942.071
276170Z1-108 E
Adder
2.48588235294117642.113
276626AG1-044 E
Adder
0.062352941176470590.053
276675AE2-062 E
Adder
0.135294117647058840.115
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
NYPJM->LTFIMP_NY
CLTF
0.9330.933
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.52 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1770.05
MW Contribution:7.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.69411764705882372.29
962012AG1-044 E
Adder
0.063529411764705890.054
962781AG1-127 C
Adder
7.1717647058823536.096
962782AG1-127 E
Adder
4.7729411764705894.057
966091AG1-478 C
Adder
2.00941176470588221.708
966092AG1-478 E
Adder
0.50588235294117640.43
966441AG1-513 C
Adder
0.52235294117647060.444
966442AG1-513 E
Adder
0.78235294117647070.665
290021O50 E
Adder
20.16117647058823817.137
290051GSG-6; E
Adder
10.715294117647069.108
295109WESTBROOK E
Adder
5.7364705882352954.876
295111SUBLETTE E
Adder
2.78941176470588252.371
918052AA1-018 E OP
Adder
15.76000000000000213.396
933911AD1-013 C
Adder
1.88588235294117661.603
933912AD1-013 E
Adder
3.01294117647058852.561
934722AD1-100 E
Adder
91.6917647058823677.938
937002AD2-134 E
Adder
10.368.806
937312AD2-172 E
Adder
3.4682352941176472.948
958481AF2-142 C
Adder
10.8694117647058849.239
958482AF2-142 E
Adder
7.2458823529411776.159
958491AF2-143 C
Adder
10.8023529411764719.182
958492AF2-143 E
Adder
7.2011764705882366.121
958912AF2-182 E
Adder
34.8823529411764729.65
959081AF2-199 C
Adder
7.3129411764705896.216
959082AF2-199 E
Adder
3.65647058823529443.108
959351AF2-226 C
50/50
2.9472.947
959352AF2-226 E
50/50
4.424.42
960281AF2-319 C
50/50
2.9472.947
960282AF2-319 E
50/50
4.424.42
960582AF2-349 E
Adder
37.19058823529411531.612
960751AF2-366 C
Adder
7.1517647058823536.079
960752AF2-366 E
Adder
4.7682352941176474.053
274654BRAIDWOOD;1U
50/50
27.62127.621
274655BRAIDWOOD;2U
50/50
26.87526.875
274675JOLIET 29;7U
Adder
76.2117647058823664.78
274676JOLIET 29;8U
50/50
76.25576.255
274682WAUKEGAN ;7U
Adder
42.623529411764736.23
274683WAUKEGAN ;8U
Adder
45.9439.049
274687WILL CNTY;4U
50/50
71.93671.936
274752CRETE EC ;2U
50/50
6.1116.111
274753CRETE EC ;3U
50/50
6.1116.111
274754CRETE EC ;4U
50/50
6.1116.111
274859EASYR;U1 E
Adder
12.26705882352941210.427
274860EASYR;U2 E
Adder
12.26705882352941210.427
274861TOP CROP ;1U
50/50
0.4420.442
274862TOP CROP ;2U
50/50
0.8420.842
276591L-013 2
Adder
3.7670588235294123.202
293061N-015 E
Adder
16.04470588235294313.638
293644O22 E1
50/50
16.92816.928
293645O22 E2
50/50
19.38819.388
294392P-010 E
Adder
20.3776470588235317.321
294763P-046 E
Adder
9.6411764705882378.195
933411AC2-154 C
Adder
2.25058823529411761.913
933412AC2-154 E
Adder
3.6717647058823533.121
939061AE1-134 2
Adder
1.39764705882352951.188
940502AE2-035 E
Adder
3.4682352941176472.948
957331AF2-027 C
Adder
2.57411764705882362.188
957332AF2-027 E
Adder
3.86117647058823543.282
957471AF2-041 C
Adder
21.9376470588235318.647
957472AF2-041 E
Adder
10.9682352941176489.323
274674JOLIET 9 ;6U
Adder
35.323529411764730.025
274891CAYUG;2U E
Adder
6.6400000000000015.644
938851AE1-113 C
Adder
8.3164705882352947.069
938852AE1-113 E
Adder
29.48470588235294425.062
934101AD2-000 1
Adder
5.8964705882352945.012
934111AD2-000 2
Adder
6.3129411764705885.366
274704KENDALL ;1C
50/50
4.144.14
274705KENDALL ;1S
50/50
2.7692.769
274706KENDALL ;2C
50/50
4.144.14
274707KENDALL ;2S
50/50
2.7692.769
275149KELLYCK ;1E
Adder
16.58000000000000214.093
293519PILOT HIL;1E
Adder
16.58000000000000214.093
290108LEEDK;1U E
Adder
24.58352941176470820.896
916221Z1-073 E
Adder
7.5505882352941186.418
926821AC1-168 C
Adder
1.16235294117647060.988
926822AC1-168 E
Adder
7.797647058823536.628
936292AD2-038 E
Adder
14.8352941176470612.61
936371AD2-047 C
Adder
4.0270588235294123.423
936372AD2-047 E
Adder
19.6616.711
936461AD2-060 C
Adder
2.3682352941176472.013
936511AD2-066 C
Adder
8.5164705882352937.239
936512AD2-066 E
Adder
5.67764705882352954.826
942421AE2-255 C
Adder
3.15058823529411752.678
942422AE2-255 E
Adder
9.4505882352941168.033
942651AE2-281 C
Adder
0.840.714
942652AE2-281 E
Adder
5.1611764705882354.387
943121AE2-341 C
Adder
13.05176470588235211.094
943122AE2-341 E
Adder
6.4094117647058835.448
943591AF1-030 C
Adder
8.687.378
943592AF1-030 E
Adder
4.2941176470588233.65
959091AF2-200 C
Adder
14.62470588235294112.431
959092AF2-200 E
Adder
9.7494117647058838.287
960591AF2-350 C
Adder
7.1058823529411776.04
960592AF2-350 E
Adder
4.737647058823534.027
938861AE1-114 C
Adder
4.0152941176470593.413
938862AE1-114 E
Adder
13.70117647058823711.646
939321AE1-163 C
Adder
5.8811764705882354.999
939322AE1-163 E
Adder
36.1270588235294130.708
939351AE1-166 C
Adder
10.217647058823538.685
939352AE1-166 E
Adder
9.4317647058823538.017
939401AE1-172 C
Adder
5.3423529411764714.541
939402AE1-172 E
Adder
25.0094117647058821.258
946152AF1-280 E
Adder
23.25529411764705819.767
946671AF1-331 C
Adder
2.4494117647058822.082
962691AG1-118 C
Adder
22.70941176470588419.303
962692AG1-118 E
Adder
15.1412.869
941551AE2-152 C
Adder
11.78941176470588410.021
941552AE2-152 E
Adder
7.8588235294117646.68
958011AF2-095 C
Adder
10.2317647058823528.697
958012AF2-095 E
Adder
6.8211764705882355.798
274751CRETE EC ;1U
50/50
6.1116.111
920272AA2-123 E
Adder
2.9517647058823532.509
276170Z1-108 E
Adder
3.01294117647058852.561
276626AG1-044 E
Adder
0.075294117647058830.064
276675AE2-062 E
Adder
0.152941176470588250.13
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.30480.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.41313.413
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1432.143
NYPJM->LTFIMP_NY
CLTF
1.1511.151
WECLTFEXP_WEC->PJM
CLTF
4.0154.015
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5770.577
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7060.706
MECLTFEXP_MEC->PJM
CLTF
13.16213.162
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0692.069
LAGNLTFEXP_LAGN->PJM
CLTF
3.2773.277
O66PJM->LTFIMP_O-066
CMTX_NF
13.7513.75

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.52 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1769.98
MW Contribution:7.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.69411764705882372.29
962012AG1-044 E
Adder
0.063529411764705890.054
962781AG1-127 C
Adder
7.1717647058823536.096
962782AG1-127 E
Adder
4.7729411764705894.057
966091AG1-478 C
Adder
2.00941176470588221.708
966092AG1-478 E
Adder
0.50588235294117640.43
966441AG1-513 C
Adder
0.52235294117647060.444
966442AG1-513 E
Adder
0.78235294117647070.665
290021O50 E
Adder
20.1617.136
290051GSG-6; E
Adder
10.7141176470588229.107
295109WESTBROOK E
Adder
5.7364705882352954.876
295111SUBLETTE E
Adder
2.78823529411764742.37
918052AA1-018 E OP
Adder
15.76000000000000213.396
933911AD1-013 C
Adder
1.88588235294117661.603
933912AD1-013 E
Adder
3.01294117647058852.561
934722AD1-100 E
Adder
91.6988235294117777.944
937002AD2-134 E
Adder
10.3588235294117658.805
937312AD2-172 E
Adder
3.4682352941176472.948
958481AF2-142 C
Adder
10.8694117647058849.239
958482AF2-142 E
Adder
7.2458823529411776.159
958491AF2-143 C
Adder
10.8023529411764719.182
958492AF2-143 E
Adder
7.2011764705882366.121
958912AF2-182 E
Adder
34.8788235294117629.647
959081AF2-199 C
Adder
7.3117647058823536.215
959082AF2-199 E
Adder
3.65529411764705923.107
959351AF2-226 C
50/50
2.9462.946
959352AF2-226 E
50/50
4.424.42
960281AF2-319 C
50/50
2.9462.946
960282AF2-319 E
50/50
4.424.42
960582AF2-349 E
Adder
37.1870588235294131.609
960751AF2-366 C
Adder
7.1517647058823536.079
960752AF2-366 E
Adder
4.7670588235294114.052
274654BRAIDWOOD;1U
50/50
27.62127.621
274655BRAIDWOOD;2U
50/50
26.87526.875
274675JOLIET 29;7U
Adder
76.2094117647058964.778
274676JOLIET 29;8U
50/50
76.25276.252
274682WAUKEGAN ;7U
Adder
42.6236.227
274683WAUKEGAN ;8U
Adder
45.93647058823529539.046
274687WILL CNTY;4U
50/50
71.93571.935
274752CRETE EC ;2U
50/50
6.1116.111
274753CRETE EC ;3U
50/50
6.1116.111
274754CRETE EC ;4U
50/50
6.1116.111
274859EASYR;U1 E
Adder
12.26588235294117610.426
274860EASYR;U2 E
Adder
12.26588235294117610.426
274861TOP CROP ;1U
50/50
0.4420.442
274862TOP CROP ;2U
50/50
0.8420.842
276591L-013 2
Adder
3.7670588235294123.202
293061N-015 E
Adder
16.04470588235294313.638
293644O22 E1
50/50
16.92816.928
293645O22 E2
50/50
19.38819.388
294392P-010 E
Adder
20.37647058823529617.32
294763P-046 E
Adder
9.648.194
933411AC2-154 C
Adder
2.25058823529411761.913
933412AC2-154 E
Adder
3.6717647058823533.121
939061AE1-134 2
Adder
1.39764705882352951.188
940502AE2-035 E
Adder
3.4682352941176472.948
957331AF2-027 C
Adder
2.57411764705882362.188
957332AF2-027 E
Adder
3.86117647058823543.282
957471AF2-041 C
Adder
21.93529411764705718.645
957472AF2-041 E
Adder
10.9670588235294129.322
274674JOLIET 9 ;6U
Adder
35.32235294117647630.024
274891CAYUG;2U E
Adder
6.6400000000000015.644
938851AE1-113 C
Adder
8.3164705882352947.069
938852AE1-113 E
Adder
29.48352941176470725.061
934101AD2-000 1
Adder
5.8952941176470595.011
934111AD2-000 2
Adder
6.3117647058823545.365
274704KENDALL ;1C
50/50
4.144.14
274705KENDALL ;1S
50/50
2.7692.769
274706KENDALL ;2C
50/50
4.144.14
274707KENDALL ;2S
50/50
2.7692.769
275149KELLYCK ;1E
Adder
16.58117647058823614.094
293519PILOT HIL;1E
Adder
16.58117647058823614.094
290108LEEDK;1U E
Adder
24.58117647058823320.894
916221Z1-073 E
Adder
7.5494117647058836.417
926821AC1-168 C
Adder
1.16235294117647060.988
926822AC1-168 E
Adder
7.79647058823529456.627
936292AD2-038 E
Adder
14.83411764705882312.609
936371AD2-047 C
Adder
4.0270588235294123.423
936372AD2-047 E
Adder
19.66117647058823416.712
936461AD2-060 C
Adder
2.3682352941176472.013
936511AD2-066 C
Adder
8.5164705882352937.239
936512AD2-066 E
Adder
5.67764705882352954.826
942421AE2-255 C
Adder
3.14941176470588242.677
942422AE2-255 E
Adder
9.4494117647058828.032
942651AE2-281 C
Adder
0.840.714
942652AE2-281 E
Adder
5.1611764705882354.387
943121AE2-341 C
Adder
13.05058823529411811.093
943122AE2-341 E
Adder
6.4082352941176475.447
943591AF1-030 C
Adder
8.6788235294117657.377
943592AF1-030 E
Adder
4.2941176470588233.65
959091AF2-200 C
Adder
14.62352941176470512.43
959092AF2-200 E
Adder
9.7494117647058838.287
960591AF2-350 C
Adder
7.1058823529411776.04
960592AF2-350 E
Adder
4.737647058823534.027
938861AE1-114 C
Adder
4.0152941176470593.413
938862AE1-114 E
Adder
13.711.645
939321AE1-163 C
Adder
5.8811764705882354.999
939322AE1-163 E
Adder
36.12588235294117630.707
939351AE1-166 C
Adder
10.217647058823538.685
939352AE1-166 E
Adder
9.4317647058823538.017
939401AE1-172 C
Adder
5.3423529411764714.541
939402AE1-172 E
Adder
25.0105882352941221.259
946152AF1-280 E
Adder
23.2529411764705919.765
946671AF1-331 C
Adder
2.4494117647058822.082
962691AG1-118 C
Adder
22.7070588235294119.301
962692AG1-118 E
Adder
15.13882352941176612.868
941551AE2-152 C
Adder
11.78941176470588410.021
941552AE2-152 E
Adder
7.866.681
958011AF2-095 C
Adder
10.232941176470598.698
958012AF2-095 E
Adder
6.8211764705882355.798
274751CRETE EC ;1U
50/50
6.1116.111
920272AA2-123 E
Adder
2.9517647058823532.509
276170Z1-108 E
Adder
3.0117647058823532.56
276626AG1-044 E
Adder
0.075294117647058830.064
276675AE2-062 E
Adder
0.152941176470588250.13
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.29780.297
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.41213.412
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1432.143
NYPJM->LTFIMP_NY
CLTF
1.1511.151
WECLTFEXP_WEC->PJM
CLTF
4.0154.015
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5760.576
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7060.706
MECLTFEXP_MEC->PJM
CLTF
13.16113.161
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0692.069
LAGNLTFEXP_LAGN->PJM
CLTF
3.2773.277
O66PJM->LTFIMP_O-066
CMTX_NF
13.7513.75

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.5 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1769.75
MW Contribution:7.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.68235294117647042.28
962012AG1-044 E
Adder
0.063529411764705890.054
962781AG1-127 C
Adder
7.1411764705882366.07
962782AG1-127 E
Adder
4.7517647058823534.039
966091AG1-478 C
Adder
2.01.7
966092AG1-478 E
Adder
0.50352941176470590.428
966441AG1-513 C
Adder
0.520.442
966442AG1-513 E
Adder
0.77882352941176480.662
290021O50 E
Adder
20.08705882352941417.074
290051GSG-6; E
Adder
10.6705882352941199.07
295109WESTBROOK E
Adder
5.7129411764705884.856
295111SUBLETTE E
Adder
2.77764705882352962.361
918052AA1-018 E OP
Adder
15.69411764705882513.34
933911AD1-013 C
Adder
1.87882352941176481.597
933912AD1-013 E
Adder
3.00117647058823562.551
934722AD1-100 E
Adder
91.3611764705882377.657
937002AD2-134 E
Adder
10.317647058823538.77
937312AD2-172 E
Adder
3.45529411764705862.937
958481AF2-142 C
Adder
10.8235294117647059.2
958482AF2-142 E
Adder
7.2152941176470596.133
958491AF2-143 C
Adder
10.7600000000000029.146
958492AF2-143 E
Adder
7.1729411764705896.097
958912AF2-182 E
Adder
34.7576470588235329.544
959081AF2-199 C
Adder
7.2835294117647066.191
959082AF2-199 E
Adder
3.64117647058823573.095
959351AF2-226 C
50/50
2.9362.936
959352AF2-226 E
50/50
4.4044.404
960281AF2-319 C
50/50
2.9362.936
960282AF2-319 E
50/50
4.4044.404
960582AF2-349 E
Adder
37.0376470588235331.482
960751AF2-366 C
Adder
7.1211764705882356.053
960752AF2-366 E
Adder
4.7470588235294124.035
274654BRAIDWOOD;1U
50/50
27.51327.513
274655BRAIDWOOD;2U
50/50
26.76926.769
274675JOLIET 29;7U
Adder
75.8694117647058964.489
274676JOLIET 29;8U
50/50
75.91275.912
274682WAUKEGAN ;7U
Adder
42.43647058823529536.071
274683WAUKEGAN ;8U
Adder
45.7388235294117738.878
274687WILL CNTY;4U
50/50
71.61971.619
274752CRETE EC ;2U
50/50
6.1016.101
274753CRETE EC ;3U
50/50
6.1016.101
274754CRETE EC ;4U
50/50
6.1016.101
274859EASYR;U1 E
Adder
12.2223529411764710.389
274860EASYR;U2 E
Adder
12.2223529411764710.389
274861TOP CROP ;1U
50/50
0.440.44
274862TOP CROP ;2U
50/50
0.8390.839
276591L-013 2
Adder
3.7505882352941183.188
293061N-015 E
Adder
15.9752941176470613.579
293644O22 E1
50/50
16.86916.869
293645O22 E2
50/50
19.32119.321
294392P-010 E
Adder
20.28941176470588217.246
294763P-046 E
Adder
9.6035294117647068.163
933411AC2-154 C
Adder
2.23882352941176471.903
933412AC2-154 E
Adder
3.6529411764705883.105
939061AE1-134 2
Adder
1.39294117647058811.184
940502AE2-035 E
Adder
3.45529411764705862.937
957331AF2-027 C
Adder
2.5635294117647062.179
957332AF2-027 E
Adder
3.8447058823529413.268
957471AF2-041 C
Adder
21.8494117647058818.572
957472AF2-041 E
Adder
10.924705882352949.286
274674JOLIET 9 ;6U
Adder
35.15058823529411629.878
274890CAYUG;1U E
Adder
6.6235294117647065.63
938851AE1-113 C
Adder
8.2858823529411787.043
938852AE1-113 E
Adder
29.3776470588235324.971
934101AD2-000 1
Adder
5.8705882352941184.99
934111AD2-000 2
Adder
6.2858823529411775.343
274704KENDALL ;1C
50/50
4.1234.123
274705KENDALL ;1S
50/50
2.7572.757
274706KENDALL ;2C
50/50
4.1234.123
274707KENDALL ;2S
50/50
2.7572.757
275149KELLYCK ;1E
Adder
16.49764705882352814.023
293519PILOT HIL;1E
Adder
16.49764705882352814.023
290108LEEDK;1U E
Adder
24.47764705882353220.806
916221Z1-073 E
Adder
7.52000000000000056.392
926821AC1-168 C
Adder
1.15882352941176480.985
926822AC1-168 E
Adder
7.7741176470588236.608
936292AD2-038 E
Adder
14.7776470588235312.561
936371AD2-047 C
Adder
4.00705882352941253.406
936372AD2-047 E
Adder
19.5623529411764716.628
936461AD2-060 C
Adder
2.3564705882352942.003
936511AD2-066 C
Adder
8.484705882352947.212
936512AD2-066 E
Adder
5.6564705882352944.808
942421AE2-255 C
Adder
3.1388235294117652.668
942422AE2-255 E
Adder
9.415294117647068.003
942651AE2-281 C
Adder
0.83647058823529410.711
942652AE2-281 E
Adder
5.1411764705882364.37
943121AE2-341 C
Adder
12.98823529411764711.04
943122AE2-341 E
Adder
6.377647058823535.421
943591AF1-030 C
Adder
8.6376470588235297.342
943592AF1-030 E
Adder
4.2741176470588243.633
959091AF2-200 C
Adder
14.56588235294117712.381
959092AF2-200 E
Adder
9.7105882352941188.254
960591AF2-350 C
Adder
7.0705882352941176.01
960592AF2-350 E
Adder
4.7141176470588234.007
938861AE1-114 C
Adder
4.0011764705882353.401
938862AE1-114 E
Adder
13.65058823529411711.603
939321AE1-163 C
Adder
5.8588235294117654.98
939322AE1-163 E
Adder
35.98588235294117530.588
939351AE1-166 C
Adder
10.1800000000000018.653
939352AE1-166 E
Adder
9.397647058823537.988
939401AE1-172 C
Adder
5.3270588235294124.528
939402AE1-172 E
Adder
24.9376470588235321.197
946152AF1-280 E
Adder
23.17176470588235719.696
946671AF1-331 C
Adder
2.442.074
962691AG1-118 C
Adder
22.60941176470588219.218
962692AG1-118 E
Adder
15.07294117647058812.812
941551AE2-152 C
Adder
11.7458823529411779.984
941552AE2-152 E
Adder
7.8305882352941176.656
958011AF2-095 C
Adder
10.1811764705882368.654
958012AF2-095 E
Adder
6.7870588235294125.769
274751CRETE EC ;1U
50/50
6.1016.101
920272AA2-123 E
Adder
2.9388235294117652.498
276170Z1-108 E
Adder
2.9988235294117652.549
276626AG1-044 E
Adder
0.075294117647058830.064
276675AE2-062 E
Adder
0.152941176470588250.13
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8080.808
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.46579.465
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.83113.831
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1382.138
NYPJM->LTFIMP_NY
CLTF
1.151.15
WECLTFEXP_WEC->PJM
CLTF
3.9993.999
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5540.554
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2920.292
TVALTFEXP_TVA->PJM
CLTF
1.191.19
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6340.634
MECLTFEXP_MEC->PJM
CLTF
13.15813.158
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.8531.853
LAGNLTFEXP_LAGN->PJM
CLTF
3.3653.365
O66PJM->LTFIMP_O-066
CMTX_NF
13.71713.717

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.85 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1410.83
MW Contribution:2.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
962781AG1-127 C
Adder
7.1670588235294126.092
965091AG1-374 C
Adder
16.39058823529411813.932
966091AG1-478 C
Adder
2.00941176470588221.708
966441AG1-513 C
Adder
0.52117647058823540.443
933911AD1-013 C
Adder
1.88470588235294121.602
934721AD1-100 C
80/20
3.0093.009
937401AD2-194 1
80/20
1.3081.308
937411AD2-194 2
80/20
1.3111.311
942111AE2-223 C
Adder
1.86941176470588231.589
958481AF2-142 C
Adder
10.8682352941176469.238
958491AF2-143 C
Adder
10.89.18
959081AF2-199 C
Adder
7.3070588235294126.211
959341AF2-225 C
Adder
6.0400000000000015.134
959351AF2-226 C
80/20
2.9462.946
959611AF2-252 C
Adder
1.82117647058823541.548
960281AF2-319 C
80/20
2.9462.946
960611AF2-352 C
Adder
1.82117647058823541.548
960751AF2-366 C
Adder
7.1470588235294126.075
274654BRAIDWOOD;1U
80/20
27.62627.626
274655BRAIDWOOD;2U
80/20
26.8826.88
274658DRESDEN ;2U
80/20
19.99619.996
274660LASCO STA;1U
80/20
25.49325.493
274661LASCO STA;2U
80/20
25.57725.577
274675JOLIET 29;7U
80/20
76.19176.191
274676JOLIET 29;8U
80/20
76.23476.234
274682WAUKEGAN ;7U
Adder
42.636.21
274683WAUKEGAN ;8U
Adder
45.9152941176470639.028
274687WILL CNTY;4U
80/20
71.92671.926
274728ELWOOD EC;5P
80/20
3.3643.364
274729ELWOOD EC;1P
80/20
3.3583.358
274730ELWOOD EC;6P
80/20
3.3643.364
274731ELWOOD EC;2P
80/20
3.3583.358
274732ELWOOD EC;7P
80/20
3.3643.364
274733ELWOOD EC;3P
80/20
3.3583.358
274734ELWOOD EC;8P
80/20
3.3643.364
274735ELWOOD EC;4P
80/20
3.3583.358
274736ELWOOD EC;9P
80/20
3.3643.364
274737AURORA EC;1P
80/20
3.5563.556
274739AURORA EC;2P
80/20
3.5563.556
274744AURORA EC;8P
80/20
1.0831.083
274752CRETE EC ;2U
80/20
6.1116.111
274753CRETE EC ;3U
80/20
6.1116.111
274754CRETE EC ;4U
80/20
6.1116.111
274847GR RIDGE ;BU
80/20
0.5960.596
274861TOP CROP ;1U
80/20
0.4420.442
274862TOP CROP ;2U
80/20
0.8420.842
274871GR RIDGE ;2U
80/20
0.2220.222
933411AC2-154 C
Adder
2.25058823529411761.913
939061AE1-134 2
Adder
1.39647058823529411.187
957331AF2-027 C
Adder
2.5729411764705882.187
957471AF2-041 C
Adder
21.9223529411764718.634
274674JOLIET 9 ;6U
Adder
35.31176470588235430.015
938851AE1-113 C
Adder
8.3141176470588247.067
934101AD2-000 1
80/20
5.8925.892
934111AD2-000 2
80/20
6.316.31
274704KENDALL ;1C
80/20
4.1394.139
274705KENDALL ;1S
80/20
2.7682.768
274706KENDALL ;2C
80/20
4.1394.139
274707KENDALL ;2S
80/20
2.7682.768
274708KENDALL ;3C
80/20
3.9223.922
274709KENDALL ;3S
80/20
2.5942.594
274710KENDALL ;4C
80/20
3.8793.879
274711KENDALL ;4S
80/20
2.5942.594
276640AC1-204 GEN1
80/20
12.4912.49
276642AC1-204 GEN2
80/20
12.51212.512
276658AB1-122 CT1
80/20
11.86311.863
276660AB1-122 CT2
80/20
12.70612.706
926821AC1-168 C
Adder
1.16117647058823530.987
936371AD2-047 C
Adder
4.0282352941176473.424
936461AD2-060 C
Adder
2.3694117647058822.014
936511AD2-066 C
Adder
8.5141176470588237.237
942421AE2-255 C
Adder
3.14941176470588242.677
942651AE2-281 C
Adder
0.840.714
943121AE2-341 C
Adder
13.0411.084
943591AF1-030 C
Adder
8.6717647058823537.371
959091AF2-200 C
Adder
14.61529411764705912.423
960591AF2-350 C
Adder
7.1082352941176476.042
961501AF2-441 C
Adder
6.6670588235294125.667
938861AE1-114 C
Adder
4.0129411764705883.411
939321AE1-163 C
Adder
5.8800000000000014.998
939351AE1-166 C
80/20
10.22310.223
939401AE1-172 C
Adder
5.3435294117647064.542
939741AE1-205 C
Adder
8.0529411764705886.845
946321AF1-296 C
Adder
3.6188235294117653.076
946671AF1-331 C
Adder
2.4482352941176472.081
962691AG1-118 C
Adder
22.6929411764705919.289
941551AE2-152 C
80/20
11.79611.796
958011AF2-095 C
Adder
10.2352941176470588.7
965931AG1-462 C
Adder
16.29411764705882213.85
274751CRETE EC ;1U
80/20
6.1116.111
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.25680.256
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.40713.407
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
NYPJM->LTFIMP_NY
CLTF
1.1511.151
WECLTFEXP_WEC->PJM
CLTF
4.0134.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5760.576
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7050.705
MECLTFEXP_MEC->PJM
CLTF
13.15513.155
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0682.068
LAGNLTFEXP_LAGN->PJM
CLTF
3.2763.276

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.84 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1410.81
MW Contribution:2.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
962781AG1-127 C
Adder
7.1670588235294126.092
965091AG1-374 C
Adder
16.39058823529411813.932
966091AG1-478 C
Adder
2.00941176470588221.708
966441AG1-513 C
Adder
0.52117647058823540.443
933911AD1-013 C
Adder
1.88470588235294121.602
934721AD1-100 C
80/20
3.0093.009
937401AD2-194 1
80/20
1.3081.308
937411AD2-194 2
80/20
1.3111.311
942111AE2-223 C
Adder
1.86941176470588231.589
958481AF2-142 C
Adder
10.8682352941176469.238
958491AF2-143 C
Adder
10.89.18
959081AF2-199 C
Adder
7.3070588235294126.211
959341AF2-225 C
Adder
6.0400000000000015.134
959351AF2-226 C
80/20
2.9462.946
959611AF2-252 C
Adder
1.82117647058823541.548
960281AF2-319 C
80/20
2.9462.946
960611AF2-352 C
Adder
1.82117647058823541.548
960751AF2-366 C
Adder
7.1470588235294126.075
274654BRAIDWOOD;1U
80/20
27.62627.626
274655BRAIDWOOD;2U
80/20
26.8826.88
274658DRESDEN ;2U
80/20
19.99619.996
274660LASCO STA;1U
80/20
25.49325.493
274661LASCO STA;2U
80/20
25.57725.577
274675JOLIET 29;7U
80/20
76.19176.191
274676JOLIET 29;8U
80/20
76.23476.234
274682WAUKEGAN ;7U
Adder
42.636.21
274683WAUKEGAN ;8U
Adder
45.9152941176470639.028
274687WILL CNTY;4U
80/20
71.92671.926
274728ELWOOD EC;5P
80/20
3.3643.364
274729ELWOOD EC;1P
80/20
3.3583.358
274730ELWOOD EC;6P
80/20
3.3643.364
274731ELWOOD EC;2P
80/20
3.3583.358
274732ELWOOD EC;7P
80/20
3.3643.364
274733ELWOOD EC;3P
80/20
3.3583.358
274734ELWOOD EC;8P
80/20
3.3643.364
274735ELWOOD EC;4P
80/20
3.3583.358
274736ELWOOD EC;9P
80/20
3.3643.364
274737AURORA EC;1P
80/20
3.5563.556
274739AURORA EC;2P
80/20
3.5563.556
274744AURORA EC;8P
80/20
1.0831.083
274752CRETE EC ;2U
80/20
6.1116.111
274753CRETE EC ;3U
80/20
6.1116.111
274754CRETE EC ;4U
80/20
6.1116.111
274847GR RIDGE ;BU
80/20
0.5960.596
274861TOP CROP ;1U
80/20
0.4420.442
274862TOP CROP ;2U
80/20
0.8420.842
274871GR RIDGE ;2U
80/20
0.2220.222
933411AC2-154 C
Adder
2.25058823529411761.913
939061AE1-134 2
Adder
1.39647058823529411.187
957331AF2-027 C
Adder
2.5729411764705882.187
957471AF2-041 C
Adder
21.9223529411764718.634
274674JOLIET 9 ;6U
Adder
35.31176470588235430.015
938851AE1-113 C
Adder
8.3141176470588247.067
934101AD2-000 1
80/20
5.8925.892
934111AD2-000 2
80/20
6.316.31
274704KENDALL ;1C
80/20
4.1394.139
274705KENDALL ;1S
80/20
2.7682.768
274706KENDALL ;2C
80/20
4.1394.139
274707KENDALL ;2S
80/20
2.7682.768
274708KENDALL ;3C
80/20
3.9223.922
274709KENDALL ;3S
80/20
2.5942.594
274710KENDALL ;4C
80/20
3.8793.879
274711KENDALL ;4S
80/20
2.5942.594
276640AC1-204 GEN1
80/20
12.4912.49
276642AC1-204 GEN2
80/20
12.51212.512
276658AB1-122 CT1
80/20
11.86311.863
276660AB1-122 CT2
80/20
12.70612.706
926821AC1-168 C
Adder
1.16117647058823530.987
936371AD2-047 C
Adder
4.0282352941176473.424
936461AD2-060 C
Adder
2.3694117647058822.014
936511AD2-066 C
Adder
8.5141176470588237.237
942421AE2-255 C
Adder
3.14941176470588242.677
942651AE2-281 C
Adder
0.840.714
943121AE2-341 C
Adder
13.0411.084
943591AF1-030 C
Adder
8.6717647058823537.371
959091AF2-200 C
Adder
14.61529411764705912.423
960591AF2-350 C
Adder
7.1082352941176476.042
961501AF2-441 C
Adder
6.6670588235294125.667
938861AE1-114 C
Adder
4.0129411764705883.411
939321AE1-163 C
Adder
5.8800000000000014.998
939351AE1-166 C
80/20
10.22310.223
939401AE1-172 C
Adder
5.3435294117647064.542
939741AE1-205 C
Adder
8.0529411764705886.845
946321AF1-296 C
Adder
3.6188235294117653.076
946671AF1-331 C
Adder
2.4482352941176472.081
962691AG1-118 C
Adder
22.6929411764705919.289
941551AE2-152 C
80/20
11.79611.796
958011AF2-095 C
Adder
10.2352941176470588.7
965931AG1-462 C
Adder
16.29411764705882213.85
274751CRETE EC ;1U
80/20
6.1116.111
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.25680.256
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.40713.407
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
NYPJM->LTFIMP_NY
CLTF
1.1511.151
WECLTFEXP_WEC->PJM
CLTF
4.0134.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5760.576
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7050.705
MECLTFEXP_MEC->PJM
CLTF
13.15513.155
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0682.068
LAGNLTFEXP_LAGN->PJM
CLTF
3.2763.276

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.64 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1547.79
MW Contribution:7.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.71764705882352952.31
962781AG1-127 C
Adder
7.23058823529411756.146
962782AG1-127 E
Adder
4.8117647058823534.09
966091AG1-478 C
Adder
2.02470588235294141.721
966092AG1-478 E
Adder
0.50941176470588230.433
966441AG1-513 C
Adder
0.52588235294117650.447
966442AG1-513 E
Adder
0.78823529411764710.67
290021O50 E
Adder
20.33764705882352817.287
290051GSG-6; E
Adder
10.8082352941176479.187
295109WESTBROOK E
Adder
5.7870588235294124.919
295111SUBLETTE E
Adder
2.81294117647058832.391
918052AA1-018 E OP
Adder
15.89882352941176413.514
933911AD1-013 C
Adder
1.90235294117647061.617
933912AD1-013 E
Adder
3.042.584
934722AD1-100 E
Adder
92.4678.591
937002AD2-134 E
Adder
10.4505882352941168.883
937312AD2-172 E
Adder
3.50117647058823562.976
958481AF2-142 C
Adder
10.9647058823529419.32
958482AF2-142 E
Adder
7.30941176470588256.213
958491AF2-143 C
Adder
10.9011764705882369.266
958492AF2-143 E
Adder
7.2670588235294116.177
959081AF2-199 C
Adder
7.377647058823536.271
959082AF2-199 E
Adder
3.6882352941176473.135
959351AF2-226 C
50/50
2.9682.968
959352AF2-226 E
50/50
4.4524.452
960281AF2-319 C
50/50
2.9682.968
960282AF2-319 E
50/50
4.4524.452
960582AF2-349 E
Adder
37.5082352941176531.882
960751AF2-366 C
Adder
7.2105882352941176.129
960752AF2-366 E
Adder
4.8070588235294124.086
274654BRAIDWOOD;1U
50/50
27.81527.815
274655BRAIDWOOD;2U
50/50
27.06427.064
274660LASCO STA;1U
50/50
25.67925.679
274661LASCO STA;2U
50/50
25.76325.763
274675JOLIET 29;7U
50/50
76.73276.732
274676JOLIET 29;8U
50/50
76.77576.775
274682WAUKEGAN ;7U
Adder
42.9505882352941236.508
274683WAUKEGAN ;8U
Adder
46.2952941176470639.351
274687WILL CNTY;4U
50/50
72.4272.42
274728ELWOOD EC;5P
50/50
3.3883.388
274730ELWOOD EC;6P
50/50
3.3883.388
274736ELWOOD EC;9P
50/50
3.3883.388
274861TOP CROP ;1U
50/50
0.4450.445
274862TOP CROP ;2U
50/50
0.8480.848
276591L-013 2
Adder
3.7952941176470593.226
293061N-015 E
Adder
16.1647058823529413.74
293644O22 E1
50/50
17.04917.049
293645O22 E2
50/50
19.52719.527
294392P-010 E
Adder
20.5282352941176517.449
294763P-046 E
Adder
9.730588235294128.271
933411AC2-154 C
Adder
2.26941176470588251.929
933412AC2-154 E
Adder
3.70235294117647043.147
940502AE2-035 E
Adder
3.50117647058823562.976
957331AF2-027 C
Adder
2.59529411764705882.206
957332AF2-027 E
Adder
3.8917647058823533.308
957471AF2-041 C
Adder
22.13176470588235418.812
957472AF2-041 E
Adder
11.0658823529411779.406
274674JOLIET 9 ;6U
Adder
35.59176470588235530.253
938851AE1-113 C
Adder
8.3894117647058837.131
938852AE1-113 E
Adder
29.74470588235294225.283
934101AD2-000 1
Adder
5.9435294117647065.052
934111AD2-000 2
Adder
6.3588235294117655.405
274704KENDALL ;1C
50/50
4.1694.169
274705KENDALL ;1S
50/50
2.7882.788
274706KENDALL ;2C
50/50
4.1694.169
274707KENDALL ;2S
50/50
2.7882.788
275149KELLYCK ;1E
Adder
16.7176470588235314.21
276640AC1-204 GEN1
50/50
12.58212.582
276642AC1-204 GEN2
50/50
12.60312.603
293519PILOT HIL;1E
Adder
16.7176470588235314.21
290108LEEDK;1U E
Adder
24.78823529411764821.07
916221Z1-073 E
Adder
7.6164705882352956.474
936292AD2-038 E
Adder
14.97058823529411812.725
936371AD2-047 C
Adder
4.06000000000000053.451
936372AD2-047 E
Adder
19.82352941176470716.85
936461AD2-060 C
Adder
2.3882352941176472.03
936511AD2-066 C
Adder
8.5941176470588237.305
936512AD2-066 E
Adder
5.7294117647058824.87
942421AE2-255 C
Adder
3.17764705882352952.701
942422AE2-255 E
Adder
9.5329411764705888.103
942651AE2-281 C
Adder
0.84823529411764710.721
942652AE2-281 E
Adder
5.2082352941176474.427
943121AE2-341 C
Adder
13.14705882352941311.175
943122AE2-341 E
Adder
6.45529411764705955.487
943591AF1-030 C
Adder
8.742352941176477.431
943592AF1-030 E
Adder
4.3258823529411773.677
959091AF2-200 C
Adder
14.75411764705882512.541
959092AF2-200 E
Adder
9.8364705882352958.361
960591AF2-350 C
Adder
7.16470588235294156.09
960592AF2-350 E
Adder
4.7764705882352944.06
938862AE1-114 E
Adder
2.5435294117647062.162
939321AE1-163 C
Adder
5.9352941176470595.045
939322AE1-163 E
Adder
36.4588235294117730.99
939351AE1-166 C
Adder
10.3023529411764718.757
939352AE1-166 E
Adder
9.5105882352941178.084
939401AE1-172 C
Adder
5.3964705882352944.587
939402AE1-172 E
Adder
25.26705882352941421.477
946671AF1-331 C
Adder
2.47058823529411782.1
962691AG1-118 C
Adder
22.89176470588235219.458
962692AG1-118 E
Adder
15.26117647058823612.972
941551AE2-152 C
Adder
11.88823529411764710.105
941552AE2-152 E
Adder
7.9247058823529416.736
958011AF2-095 C
Adder
10.3164705882352948.769
958012AF2-095 E
Adder
6.877647058823535.846
920272AA2-123 E
Adder
2.97647058823529382.53
276170Z1-108 E
Adder
3.03647058823529432.581
276675AE2-062 E
Adder
0.154117647058823530.131
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.690.69
CBM West 1LTFEXP_CBM-W1->PJM
CBM
82.12382.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.85714.857
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.9731.973
NYPJM->LTFIMP_NY
CLTF
1.0631.063
WECLTFEXP_WEC->PJM
CLTF
4.0514.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4630.463
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2370.237
TVALTFEXP_TVA->PJM
CLTF
1.4091.409
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5470.547
MECLTFEXP_MEC->PJM
CLTF
13.40713.407
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5811.581
LAGNLTFEXP_LAGN->PJM
CLTF
3.643.64
SIGELTFEXP_SIGE->PJM
CLTF
0.0050.005
O66PJM->LTFIMP_O-066
CMTX_NF
12.66112.661

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.6 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1547.34
MW Contribution:7.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.7282352941176472.319
962781AG1-127 C
Adder
7.2623529411764716.173
962782AG1-127 E
Adder
4.8329411764705884.108
966091AG1-478 C
Adder
2.03411764705882361.729
966092AG1-478 E
Adder
0.51176470588235290.435
966441AG1-513 C
Adder
0.52823529411764710.449
966442AG1-513 E
Adder
0.7917647058823530.673
290021O50 E
Adder
20.41176470588235517.35
290051GSG-6; E
Adder
10.8529411764705899.225
295109WESTBROOK E
Adder
5.8105882352941184.939
295111SUBLETTE E
Adder
2.8247058823529412.401
918052AA1-018 E OP
Adder
15.96470588235294113.57
933911AD1-013 C
Adder
1.9105882352941181.624
933912AD1-013 E
Adder
3.0517647058823532.594
934722AD1-100 E
Adder
92.7905882352941278.872
937002AD2-134 E
Adder
10.492941176470598.919
937312AD2-172 E
Adder
3.51411764705882362.987
958481AF2-142 C
Adder
11.0105882352941199.359
958482AF2-142 E
Adder
7.346.239
958491AF2-143 C
Adder
10.9435294117647069.302
958492AF2-143 E
Adder
7.29529411764705856.201
959081AF2-199 C
Adder
7.4070588235294126.296
959082AF2-199 E
Adder
3.7035294117647063.148
959351AF2-226 C
50/50
2.9782.978
959352AF2-226 E
50/50
4.4674.467
960281AF2-319 C
50/50
2.9782.978
960282AF2-319 E
50/50
4.4674.467
960582AF2-349 E
Adder
37.6611764705882432.012
960751AF2-366 C
Adder
7.2411764705882366.155
960752AF2-366 E
Adder
4.8282352941176474.104
274654BRAIDWOOD;1U
50/50
27.92327.923
274655BRAIDWOOD;2U
50/50
27.1727.17
274660LASCO STA;1U
50/50
25.79325.793
274661LASCO STA;2U
50/50
25.87825.878
274675JOLIET 29;7U
50/50
77.07577.075
274676JOLIET 29;8U
50/50
77.11877.118
274682WAUKEGAN ;7U
Adder
43.13882352941176636.668
274683WAUKEGAN ;8U
Adder
46.4964705882352939.522
274687WILL CNTY;4U
50/50
72.73772.737
274728ELWOOD EC;5P
50/50
3.4033.403
274730ELWOOD EC;6P
50/50
3.4033.403
274734ELWOOD EC;8P
50/50
3.4033.403
274861TOP CROP ;1U
50/50
0.4460.446
274862TOP CROP ;2U
50/50
0.8510.851
276591L-013 2
Adder
3.81294117647058833.241
293061N-015 E
Adder
16.2329411764705913.798
293644O22 E1
50/50
17.10817.108
293645O22 E2
50/50
19.59519.595
294392P-010 E
Adder
20.61647058823529517.524
294763P-046 E
Adder
9.7670588235294128.302
933411AC2-154 C
Adder
2.281.938
933412AC2-154 E
Adder
3.723.162
940502AE2-035 E
Adder
3.51411764705882362.987
957331AF2-027 C
Adder
2.60588235294117652.215
957332AF2-027 E
Adder
3.90941176470588263.323
957471AF2-041 C
Adder
22.22000000000000218.887
957472AF2-041 E
Adder
11.1094117647058829.443
274674JOLIET 9 ;6U
Adder
35.7647058823529430.4
938851AE1-113 C
Adder
8.427.157
938852AE1-113 E
Adder
29.8529411764705925.375
934101AD2-000 1
Adder
5.9694117647058835.074
934111AD2-000 2
Adder
6.3858823529411765.428
274704KENDALL ;1C
50/50
4.1874.187
274705KENDALL ;1S
50/50
2.82.8
274706KENDALL ;2C
50/50
4.1874.187
274707KENDALL ;2S
50/50
2.82.8
275149KELLYCK ;1E
Adder
16.814.28
276640AC1-204 GEN1
50/50
12.63612.636
276642AC1-204 GEN2
50/50
12.65812.658
293519PILOT HIL;1E
Adder
16.814.28
290108LEEDK;1U E
Adder
24.89294117647058621.159
916221Z1-073 E
Adder
7.6470588235294126.5
936292AD2-038 E
Adder
15.02941176470588412.775
936371AD2-047 C
Adder
4.083.468
936372AD2-047 E
Adder
19.92117647058823616.933
936461AD2-060 C
Adder
2.42.04
936511AD2-066 C
Adder
8.6258823529411767.332
936512AD2-066 E
Adder
5.7505882352941184.888
942421AE2-255 C
Adder
3.18941176470588242.711
942422AE2-255 E
Adder
9.5682352941176458.133
942651AE2-281 C
Adder
0.85058823529411760.723
942652AE2-281 E
Adder
5.2282352941176474.444
943121AE2-341 C
Adder
13.20941176470588211.228
943122AE2-341 E
Adder
6.4870588235294125.514
943591AF1-030 C
Adder
8.7847058823529427.467
943592AF1-030 E
Adder
4.3458823529411763.694
959091AF2-200 C
Adder
14.81294117647058812.591
959092AF2-200 E
Adder
9.8752941176470598.394
960591AF2-350 C
Adder
7.26.12
960592AF2-350 E
Adder
4.84.08
938862AE1-114 E
Adder
2.5529411764705882.17
939321AE1-163 C
Adder
5.957647058823535.064
939322AE1-163 E
Adder
36.631.11
939351AE1-166 C
Adder
10.348.789
939352AE1-166 E
Adder
9.5447058823529418.113
939401AE1-172 C
Adder
5.4117647058823524.6
939402AE1-172 E
Adder
25.33882352941176621.538
946671AF1-331 C
Adder
2.48117647058823552.109
962691AG1-118 C
Adder
22.9929411764705919.544
962692AG1-118 E
Adder
15.32823529411764713.029
941551AE2-152 C
Adder
11.93058823529411910.141
941552AE2-152 E
Adder
7.9529411764705886.76
958011AF2-095 C
Adder
10.3682352941176488.813
958012AF2-095 E
Adder
6.9117647058823535.875
920272AA2-123 E
Adder
2.9882352941176472.54
276170Z1-108 E
Adder
3.04941176470588272.592
276675AE2-062 E
Adder
0.155294117647058830.132
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.7170.717
CBM West 1LTFEXP_CBM-W1->PJM
CBM
82.96182.961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.43914.439
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.9781.978
NYPJM->LTFIMP_NY
CLTF
1.0641.064
WECLTFEXP_WEC->PJM
CLTF
4.0674.067
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4860.486
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2520.252
TVALTFEXP_TVA->PJM
CLTF
1.3271.327
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6180.618
MECLTFEXP_MEC->PJM
CLTF
13.41113.411
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.7971.797
LAGNLTFEXP_LAGN->PJM
CLTF
3.5523.552
O66PJM->LTFIMP_O-066
CMTX_NF
12.69412.694

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.6 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1547.28
MW Contribution:7.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.7282352941176472.319
962781AG1-127 C
Adder
7.2611764705882356.172
962782AG1-127 E
Adder
4.8317647058823534.107
966091AG1-478 C
Adder
2.03411764705882361.729
966092AG1-478 E
Adder
0.51176470588235290.435
966441AG1-513 C
Adder
0.52823529411764710.449
966442AG1-513 E
Adder
0.7917647058823530.673
290021O50 E
Adder
20.41058823529411717.349
290051GSG-6; E
Adder
10.8517647058823539.224
295109WESTBROOK E
Adder
5.80941176470588254.938
295111SUBLETTE E
Adder
2.8247058823529412.401
918052AA1-018 E OP
Adder
15.96470588235294113.57
933911AD1-013 C
Adder
1.9105882352941181.624
933912AD1-013 E
Adder
3.0517647058823532.594
934722AD1-100 E
Adder
92.7976470588235378.878
937002AD2-134 E
Adder
10.4917647058823528.918
937312AD2-172 E
Adder
3.51411764705882362.987
958481AF2-142 C
Adder
11.0105882352941199.359
958482AF2-142 E
Adder
7.346.239
958491AF2-143 C
Adder
10.9435294117647069.302
958492AF2-143 E
Adder
7.29529411764705856.201
959081AF2-199 C
Adder
7.4058823529411776.295
959082AF2-199 E
Adder
3.70235294117647043.147
959351AF2-226 C
50/50
2.9782.978
959352AF2-226 E
50/50
4.4674.467
960281AF2-319 C
50/50
2.9782.978
960282AF2-319 E
50/50
4.4674.467
960582AF2-349 E
Adder
37.6588235294117632.01
960751AF2-366 C
Adder
7.2411764705882366.155
960752AF2-366 E
Adder
4.8270588235294124.103
274654BRAIDWOOD;1U
50/50
27.92427.924
274655BRAIDWOOD;2U
50/50
27.1727.17
274660LASCO STA;1U
50/50
25.79225.792
274661LASCO STA;2U
50/50
25.87625.876
274675JOLIET 29;7U
50/50
77.07277.072
274676JOLIET 29;8U
50/50
77.11677.116
274682WAUKEGAN ;7U
Adder
43.1352941176470636.665
274683WAUKEGAN ;8U
Adder
46.4929411764705939.519
274687WILL CNTY;4U
50/50
72.73672.736
274728ELWOOD EC;5P
50/50
3.4033.403
274730ELWOOD EC;6P
50/50
3.4033.403
274734ELWOOD EC;8P
50/50
3.4033.403
274861TOP CROP ;1U
50/50
0.4460.446
274862TOP CROP ;2U
50/50
0.8510.851
276591L-013 2
Adder
3.81294117647058833.241
293061N-015 E
Adder
16.2329411764705913.798
293644O22 E1
50/50
17.10817.108
293645O22 E2
50/50
19.59519.595
294392P-010 E
Adder
20.6152941176470617.523
294763P-046 E
Adder
9.7670588235294128.302
933411AC2-154 C
Adder
2.281.938
933412AC2-154 E
Adder
3.723.162
940502AE2-035 E
Adder
3.51411764705882362.987
957331AF2-027 C
Adder
2.60588235294117652.215
957332AF2-027 E
Adder
3.9082352941176473.322
957471AF2-041 C
Adder
22.2176470588235318.885
957472AF2-041 E
Adder
11.1094117647058829.443
274674JOLIET 9 ;6U
Adder
35.7635294117647130.399
938851AE1-113 C
Adder
8.427.157
938852AE1-113 E
Adder
29.85176470588235325.374
934101AD2-000 1
Adder
5.96823529411764755.073
934111AD2-000 2
Adder
6.3847058823529415.427
274704KENDALL ;1C
50/50
4.1874.187
274705KENDALL ;1S
50/50
2.82.8
274706KENDALL ;2C
50/50
4.1874.187
274707KENDALL ;2S
50/50
2.82.8
275149KELLYCK ;1E
Adder
16.80117647058823514.281
276640AC1-204 GEN1
50/50
12.63612.636
276642AC1-204 GEN2
50/50
12.65712.657
293519PILOT HIL;1E
Adder
16.80117647058823514.281
290108LEEDK;1U E
Adder
24.89058823529411821.157
916221Z1-073 E
Adder
7.6470588235294126.5
936292AD2-038 E
Adder
15.02823529411764612.774
936371AD2-047 C
Adder
4.083.468
936372AD2-047 E
Adder
19.92117647058823616.933
936461AD2-060 C
Adder
2.42.04
936511AD2-066 C
Adder
8.6258823529411767.332
936512AD2-066 E
Adder
5.7505882352941184.888
942421AE2-255 C
Adder
3.18941176470588242.711
942422AE2-255 E
Adder
9.5682352941176458.133
942651AE2-281 C
Adder
0.85058823529411760.723
942652AE2-281 E
Adder
5.2282352941176474.444
943121AE2-341 C
Adder
13.20823529411764811.227
943122AE2-341 E
Adder
6.4858823529411775.513
943591AF1-030 C
Adder
8.7835294117647067.466
943592AF1-030 E
Adder
4.3458823529411763.694
959091AF2-200 C
Adder
14.81176470588235412.59
959092AF2-200 E
Adder
9.8741176470588248.393
960591AF2-350 C
Adder
7.26.12
960592AF2-350 E
Adder
4.84.08
938862AE1-114 E
Adder
2.5517647058823532.169
939321AE1-163 C
Adder
5.957647058823535.064
939322AE1-163 E
Adder
36.5988235294117731.109
939351AE1-166 C
Adder
10.348.789
939352AE1-166 E
Adder
9.5447058823529418.113
939401AE1-172 C
Adder
5.4129411764705884.601
939402AE1-172 E
Adder
25.34000000000000321.539
946671AF1-331 C
Adder
2.48117647058823552.109
962691AG1-118 C
Adder
22.9905882352941219.542
962692AG1-118 E
Adder
15.32705882352941313.028
941551AE2-152 C
Adder
11.93058823529411910.141
941552AE2-152 E
Adder
7.95411764705882356.761
958011AF2-095 C
Adder
10.3682352941176488.813
958012AF2-095 E
Adder
6.9117647058823535.875
920272AA2-123 E
Adder
2.9882352941176472.54
276170Z1-108 E
Adder
3.04941176470588272.592
276675AE2-062 E
Adder
0.155294117647058830.132
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.7170.717
CBM West 1LTFEXP_CBM-W1->PJM
CBM
82.95582.955
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.43814.438
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.9781.978
NYPJM->LTFIMP_NY
CLTF
1.0641.064
WECLTFEXP_WEC->PJM
CLTF
4.0664.066
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4860.486
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2520.252
TVALTFEXP_TVA->PJM
CLTF
1.3271.327
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6180.618
MECLTFEXP_MEC->PJM
CLTF
13.4113.41
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.7971.797
LAGNLTFEXP_LAGN->PJM
CLTF
3.5523.552
O66PJM->LTFIMP_O-066
CMTX_NF
12.69312.693

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4-6_116-345-R______SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_116-345-R______SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.57 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2470.99
MW Contribution:14.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.96705882352941171.672
962012AG1-044 E
Adder
0.051764705882352940.044
962781AG1-127 C
Adder
5.0494117647058834.292
962782AG1-127 E
Adder
3.362.856
966091AG1-478 C
Adder
1.16588235294117660.991
966092AG1-478 E
Adder
0.292941176470588260.249
966441AG1-513 C
Adder
0.364705882352941160.31
966442AG1-513 E
Adder
0.54705882352941180.465
290021O50 E
Adder
25.58117647058823621.744
290051GSG-6; E
Adder
7.846.664
295109WESTBROOK E
Adder
4.197647058823533.568
295111SUBLETTE E
Adder
2.041.734
918052AA1-018 E OP
Adder
19.13411764705882216.264
933911AD1-013 C
Adder
1.37647058823529411.17
933912AD1-013 E
Adder
2.19882352941176461.869
937002AD2-134 E
Adder
7.586.443
937312AD2-172 E
Adder
2.74941176470588242.337
937401AD2-194 1
50/50
1.9831.983
937411AD2-194 2
50/50
1.9931.993
958481AF2-142 C
Adder
13.19647058823529511.217
958482AF2-142 E
Adder
8.7976470588235297.478
958491AF2-143 C
Adder
13.35058823529411911.348
958492AF2-143 E
Adder
8.9011764705882357.566
958912AF2-182 E
Adder
28.10235294117647323.887
959081AF2-199 C
Adder
5.7458823529411774.884
959082AF2-199 E
Adder
2.87294117647058832.442
959351AF2-226 C
50/50
5.8285.828
959352AF2-226 E
50/50
8.7428.742
960281AF2-319 C
50/50
5.8285.828
960282AF2-319 E
50/50
8.7428.742
960582AF2-349 E
Adder
29.2670588235294124.877
960751AF2-366 C
Adder
5.035294117647064.28
960752AF2-366 E
Adder
3.35647058823529452.853
274675JOLIET 29;7U
Adder
83.9305882352941171.341
274676JOLIET 29;8U
Adder
84.2188235294117671.586
274682WAUKEGAN ;7U
Adder
34.8294117647058829.605
274683WAUKEGAN ;8U
Adder
37.50470588235294431.879
274728ELWOOD EC;5P
50/50
5.1145.114
274729ELWOOD EC;1P
50/50
5.0895.089
274730ELWOOD EC;6P
50/50
5.1145.114
274731ELWOOD EC;2P
50/50
5.0895.089
274732ELWOOD EC;7P
50/50
5.1145.114
274734ELWOOD EC;8P
50/50
5.1145.114
274735ELWOOD EC;4P
50/50
5.0895.089
274736ELWOOD EC;9P
50/50
5.1145.114
274859EASYR;U1 E
Adder
9.8505882352941178.373
274860EASYR;U2 E
Adder
9.8505882352941178.373
274861TOP CROP ;1U
50/50
0.8730.873
274862TOP CROP ;2U
50/50
1.6661.666
276591L-013 2
Adder
2.7541176470588242.341
293644O22 E1
50/50
33.48133.481
293645O22 E2
50/50
38.34738.347
293715O-029 E
Adder
8.1270588235294126.908
293716O-029 E
Adder
4.4564705882352943.788
293717O-029 E
Adder
4.0952941176470593.481
293771O-035 E
Adder
5.6823529411764714.83
294401BSHIL;1U E
Adder
7.4129411764705886.301
294410BSHIL;2U E
Adder
7.4129411764705886.301
294763P-046 E
Adder
7.6411764705882366.495
925582AC1-033 E
Adder
8.1270588235294126.908
939061AE1-134 2
Adder
1.13411764705882350.964
940502AE2-035 E
Adder
2.74941176470588242.337
957331AF2-027 C
Adder
2.0988235294117651.784
957332AF2-027 E
Adder
3.14705882352941172.675
957471AF2-041 C
Adder
17.23882352941176414.653
957472AF2-041 E
Adder
8.6188235294117657.326
938851AE1-113 C
Adder
10.552941176470598.97
938852AE1-113 E
Adder
37.4129411764705931.801
934101AD2-000 1
Adder
5.88705882352941155.004
934111AD2-000 2
Adder
7.8929411764705886.709
276640AC1-204 GEN1
50/50
18.92818.928
276642AC1-204 GEN2
50/50
19.02419.024
293516O-009 E
Adder
15.7152941176470613.358
916212CRESCENT ;1U
Adder
3.9917647058823533.393
927208AC1-214 E1
Adder
2.69411764705882372.29
927209AC1-214 E2
Adder
2.69411764705882372.29
990901L-005 E
Adder
11.329.622
290108LEEDK;1U E
Adder
17.4505882352941214.833
916221Z1-073 E
Adder
5.5247058823529414.696
926821AC1-168 C
Adder
0.77294117647058820.657
926822AC1-168 E
Adder
5.1858823529411774.408
936292AD2-038 E
Adder
18.3352941176470615.585
936511AD2-066 C
Adder
7.0129411764705895.961
936512AD2-066 E
Adder
4.6752941176470593.974
942421AE2-255 C
Adder
3.99764705882352983.398
942422AE2-255 E
Adder
11.99176470588235310.193
942651AE2-281 C
Adder
1.03882352941176470.883
942652AE2-281 E
Adder
6.3788235294117655.422
943121AE2-341 C
Adder
7.6458823529411766.499
943122AE2-341 E
Adder
3.75411764705882333.191
943591AF1-030 C
Adder
5.0847058823529414.322
943592AF1-030 E
Adder
2.51529411764705872.138
959091AF2-200 C
Adder
11.4917647058823539.768
959092AF2-200 E
Adder
7.6611764705882356.512
966822AG1-553 E
Adder
23.40705882352941519.896
938861AE1-114 C
Adder
3.19411764705882332.715
938862AE1-114 E
Adder
10.8952941176470589.261
939321AE1-163 C
Adder
7.26941176470588256.179
939322AE1-163 E
Adder
44.6517647058823637.954
946152AF1-280 E
Adder
18.7352941176470615.925
946321AF1-296 C
Adder
3.02705882352941162.573
946322AF1-296 E
Adder
14.17411764705882312.048
946671AF1-331 C
Adder
1.78823529411764711.52
962691AG1-118 C
Adder
15.91411764705882313.527
962692AG1-118 E
Adder
10.6094117647058849.018
965931AG1-462 C
Adder
13.77411764705882511.708
965932AG1-462 E
Adder
9.1835294117647067.806
920272AA2-123 E
Adder
2.3082352941176471.962
276170Z1-108 E
Adder
2.35294117647058832
276626AG1-044 E
Adder
0.061176470588235290.052
990547J1333 G
External Queue
-23.770288467407227-23.770288467407227
990552J1334 G
External Queue
-23.770288467407227-23.770288467407227
990557J1335 G
External Queue
-23.770288467407227-23.770288467407227
990562J1336 G
External Queue
-23.770288467407227-23.770288467407227
990577J1339
External Queue
-28.12350082397461-28.12350082397461
990582J1340
External Queue
-28.12350082397461-28.12350082397461
990647J1355
External Queue
-10.19384765625-10.19384765625
990662J1358
External Queue
-12.060293197631836-12.060293197631836
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.3820.382
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.268.2
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.94111.941
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.2681.268
NYPJM->LTFIMP_NY
CLTF
0.6860.686
WECLTFEXP_WEC->PJM
CLTF
3.283.28
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2450.245
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1170.117
TVALTFEXP_TVA->PJM
CLTF
1.2761.276
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.3970.397
MECLTFEXP_MEC->PJM
CLTF
11.3111.31
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.1491.149
LAGNLTFEXP_LAGN->PJM
CLTF
3.1343.134
O66PJM->LTFIMP_O-066
CMTX_NF
8.148.14

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614__SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_116-45-L11614__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.27 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2372.1
MW Contribution:14.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.69529411764705881.441
962012AG1-044 E
Adder
0.045882352941176470.039
962781AG1-127 C
Adder
4.32235294117647053.674
962782AG1-127 E
Adder
2.8764705882352942.445
966091AG1-478 C
Adder
1.06705882352941180.907
966092AG1-478 E
Adder
0.268235294117647070.228
966441AG1-513 C
Adder
0.30705882352941180.261
966442AG1-513 E
Adder
0.46117647058823530.392
290021O50 E
Adder
24.68705882352941620.984
290051GSG-6; E
Adder
6.7552941176470595.742
295109WESTBROOK E
Adder
3.6164705882352943.074
295111SUBLETTE E
Adder
1.7588235294117651.495
918052AA1-018 E OP
Adder
18.79411764705882215.975
933911AD1-013 C
Adder
1.18588235294117661.008
933912AD1-013 E
Adder
1.89411764705882371.61
937002AD2-134 E
Adder
6.53176470588235255.552
937312AD2-172 E
Adder
2.3423529411764711.991
937401AD2-194 1
50/50
1.951.95
937411AD2-194 2
50/50
1.9611.961
958481AF2-142 C
Adder
12.96117647058823511.017
958482AF2-142 E
Adder
8.6411764705882357.345
958491AF2-143 C
Adder
13.09882352941176511.134
958492AF2-143 E
Adder
8.7329411764705887.423
958912AF2-182 E
Adder
24.30352941176470720.658
959081AF2-199 C
Adder
4.9752941176470594.229
959082AF2-199 E
Adder
2.48705882352941152.114
959351AF2-226 C
50/50
5.9595.959
959352AF2-226 E
50/50
8.9388.938
960281AF2-319 C
50/50
5.9595.959
960282AF2-319 E
50/50
8.9388.938
960582AF2-349 E
Adder
24.51176470588235320.835
960751AF2-366 C
Adder
4.3105882352941183.664
960752AF2-366 E
Adder
2.87294117647058832.442
274675JOLIET 29;7U
Adder
63.4341176470588253.919
274676JOLIET 29;8U
Adder
63.8752941176470654.294
274682WAUKEGAN ;7U
Adder
28.12352941176470723.905
274683WAUKEGAN ;8U
Adder
30.27176470588235425.731
274728ELWOOD EC;5P
50/50
5.0335.033
274729ELWOOD EC;1P
50/50
5.0055.005
274730ELWOOD EC;6P
50/50
5.0335.033
274731ELWOOD EC;2P
50/50
5.0055.005
274732ELWOOD EC;7P
50/50
5.0335.033
274733ELWOOD EC;3P
50/50
5.0055.005
274734ELWOOD EC;8P
50/50
5.0335.033
274736ELWOOD EC;9P
50/50
5.0335.033
274859EASYR;U1 E
Adder
8.4917647058823537.218
274860EASYR;U2 E
Adder
8.4917647058823537.218
274861TOP CROP ;1U
50/50
0.8930.893
274862TOP CROP ;2U
50/50
1.7031.703
276591L-013 2
Adder
2.32235294117647051.974
293644O22 E1
50/50
34.23434.234
293645O22 E2
50/50
39.2139.21
293715O-029 E
Adder
7.2105882352941176.129
293716O-029 E
Adder
3.95294117647058843.36
293717O-029 E
Adder
3.63411764705882373.089
293771O-035 E
Adder
5.2858823529411774.493
294401BSHIL;1U E
Adder
6.8764705882352945.845
294410BSHIL;2U E
Adder
6.8764705882352945.845
294763P-046 E
Adder
6.5117647058823535.535
925582AC1-033 E
Adder
7.5388235294117656.408
939061AE1-134 2
Adder
0.98823529411764710.84
940502AE2-035 E
Adder
2.3423529411764711.991
957331AF2-027 C
Adder
1.69529411764705881.441
957332AF2-027 E
Adder
2.54235294117647072.161
957471AF2-041 C
Adder
14.92470588235294212.686
957472AF2-041 E
Adder
7.4623529411764716.343
938851AE1-113 C
Adder
10.1835294117647088.656
938852AE1-113 E
Adder
36.10470588235294530.689
934101AD2-000 1
Adder
5.4164705882352954.604
934111AD2-000 2
Adder
7.502352941176476.377
276640AC1-204 GEN1
50/50
18.61818.618
276642AC1-204 GEN2
50/50
18.72218.722
293516O-009 E
Adder
13.94235294117647211.851
916212CRESCENT ;1U
Adder
3.71294117647058863.156
927208AC1-214 E1
Adder
2.50588235294117642.13
927209AC1-214 E2
Adder
2.50588235294117642.13
990901L-005 E
Adder
10.5717647058823538.986
290108LEEDK;1U E
Adder
14.98705882352941312.739
916221Z1-073 E
Adder
4.7611764705882354.047
926821AC1-168 C
Adder
0.72352941176470590.615
926822AC1-168 E
Adder
4.8552941176470594.127
936292AD2-038 E
Adder
17.98823529411764715.29
936511AD2-066 C
Adder
6.53294117647058855.553
936512AD2-066 E
Adder
4.3552941176470593.702
942421AE2-255 C
Adder
3.8576470588235293.279
942422AE2-255 E
Adder
11.5717647058823539.836
942651AE2-281 C
Adder
1.01882352941176470.866
942652AE2-281 E
Adder
6.2588235294117665.32
943121AE2-341 C
Adder
6.5717647058823535.586
943122AE2-341 E
Adder
3.22705882352941182.743
943591AF1-030 C
Adder
4.3694117647058823.714
943592AF1-030 E
Adder
2.1623529411764711.838
959091AF2-200 C
Adder
9.9494117647058848.457
959092AF2-200 E
Adder
6.6329411764705885.638
966822AG1-553 E
Adder
20.70352941176470617.598
938861AE1-114 C
Adder
2.74470588235294162.333
938862AE1-114 E
Adder
9.3635294117647067.959
939321AE1-163 C
Adder
7.1317647058823546.062
939322AE1-163 E
Adder
43.8082352941176537.237
946152AF1-280 E
Adder
16.2023529411764713.772
946321AF1-296 C
Adder
2.6705882352941182.27
946322AF1-296 E
Adder
12.50235294117647210.627
946671AF1-331 C
Adder
1.541.309
962691AG1-118 C
Adder
13.63294117647058811.588
962692AG1-118 E
Adder
9.0882352941176477.725
965931AG1-462 C
Adder
12.18352941176470610.356
965932AG1-462 E
Adder
8.1223529411764716.904
920272AA2-123 E
Adder
1.92705882352941171.638
276170Z1-108 E
Adder
1.94588235294117641.654
276626AG1-044 E
Adder
0.054117647058823530.046
990547J1333 G
External Queue
-22.909948348999023-22.909948348999023
990552J1334 G
External Queue
-22.909948348999023-22.909948348999023
990557J1335 G
External Queue
-22.909948348999023-22.909948348999023
990562J1336 G
External Queue
-22.909948348999023-22.909948348999023
990577J1339
External Queue
-27.099613189697266-27.099613189697266
990582J1340
External Queue
-27.099613189697266-27.099613189697266
990647J1355
External Queue
-9.393624305725098-9.393624305725098
990662J1358
External Queue
-11.463171005249023-11.463171005249023
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.3520.352
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.86656.866
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.99810.998
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.1661.166
NYPJM->LTFIMP_NY
CLTF
0.630.63
WECLTFEXP_WEC->PJM
CLTF
2.6952.695
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2250.225
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1080.108
TVALTFEXP_TVA->PJM
CLTF
1.1651.165
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.3610.361
MECLTFEXP_MEC->PJM
CLTF
10.03810.038
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.0441.044
LAGNLTFEXP_LAGN->PJM
CLTF
2.8362.836
SIGELTFEXP_SIGE->PJM
CLTF
00
O66PJM->LTFIMP_O-066
CMTX_NF
7.4827.482

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-45-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.41 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2306.46
MW Contribution:17.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.1517647058823531.829
962012AG1-044 E
Adder
0.056470588235294120.048
962781AG1-127 C
Adder
5.5211764705882354.693
962782AG1-127 E
Adder
3.67411764705882373.123
965091AG1-374 C
Adder
13.80470588235294111.734
965092AG1-374 E
Adder
9.2023529411764717.822
966441AG1-513 C
Adder
0.396470588235294130.337
966442AG1-513 E
Adder
0.59411764705882350.505
290021O50 E
Adder
26.14235294117647322.221
290051GSG-6; E
Adder
8.5729411764705887.287
290261S-027 E
Adder
12.5152941176470610.638
290265S-028 E
Adder
12.43882352941176510.573
295109WESTBROOK E
Adder
4.5905882352941183.902
295111SUBLETTE E
Adder
2.2317647058823531.897
933911AD1-013 C
Adder
1.50588235294117641.28
933912AD1-013 E
Adder
2.40470588235294122.044
937002AD2-134 E
Adder
8.2894117647058827.046
937312AD2-172 E
Adder
3.01647058823529422.564
937401AD2-194 1
50/50
1.8111.811
937411AD2-194 2
50/50
1.8341.834
942111AE2-223 C
Adder
1.55294117647058831.32
942112AE2-223 E
Adder
10.3941176470588268.835
958491AF2-143 C
Adder
8.4411764705882367.175
958492AF2-143 E
Adder
5.6270588235294134.783
958912AF2-182 E
Adder
30.77764705882353326.161
959081AF2-199 C
Adder
6.2741176470588245.333
959082AF2-199 E
Adder
3.13764705882352952.667
959341AF2-225 C
Adder
5.0176470588235294.265
959342AF2-225 E
Adder
6.9294117647058825.89
959351AF2-226 C
50/50
7.1367.136
959352AF2-226 E
50/50
10.70410.704
959611AF2-252 C
Adder
1.53411764705882361.304
959612AF2-252 E
Adder
2.30117647058823541.956
960281AF2-319 C
50/50
7.1367.136
960282AF2-319 E
50/50
10.70410.704
960582AF2-349 E
Adder
32.12588235294117627.307
960611AF2-352 C
Adder
1.53411764705882361.304
960612AF2-352 E
Adder
2.30117647058823541.956
960751AF2-366 C
Adder
5.50588235294117644.68
960752AF2-366 E
Adder
3.6705882352941183.12
274675JOLIET 29;7U
Adder
91.0294117647058877.375
274676JOLIET 29;8U
Adder
91.5117647058823677.785
274682WAUKEGAN ;7U
Adder
38.8423529411764733.016
274683WAUKEGAN ;8U
Adder
41.79647058823529435.527
274728ELWOOD EC;5P
50/50
4.7054.705
274729ELWOOD EC;1P
50/50
4.6474.647
274730ELWOOD EC;6P
50/50
4.7054.705
274731ELWOOD EC;2P
50/50
4.6474.647
274732ELWOOD EC;7P
50/50
4.7054.705
274733ELWOOD EC;3P
50/50
4.6474.647
274734ELWOOD EC;8P
50/50
4.7054.705
274736ELWOOD EC;9P
50/50
4.7054.705
274859EASYR;U1 E
Adder
10.7905882352941189.172
274860EASYR;U2 E
Adder
10.7905882352941189.172
274861TOP CROP ;1U
50/50
1.0691.069
274862TOP CROP ;2U
50/50
2.0392.039
276591L-013 2
Adder
3.00235294117647072.552
293644O22 E1
50/50
40.99540.995
293645O22 E2
50/50
46.95446.954
293715O-029 E
Adder
8.8741176470588247.543
293716O-029 E
Adder
4.8658823529411774.136
293717O-029 E
Adder
4.4717647058823533.801
293771O-035 E
Adder
6.177647058823535.251
294401BSHIL;1U E
Adder
8.0376470588235296.832
294410BSHIL;2U E
Adder
8.0376470588235296.832
294763P-046 E
Adder
8.3823529411764717.125
917502Z2-087 E
Adder
13.85882352941176311.78
925582AC1-033 E
Adder
8.8105882352941187.489
939061AE1-134 2
Adder
1.24117647058823531.055
940502AE2-035 E
Adder
3.01647058823529422.564
957331AF2-027 C
Adder
2.3352941176470591.985
957332AF2-027 E
Adder
3.50235294117647072.977
957471AF2-041 C
Adder
18.82352941176470716
957472AF2-041 E
Adder
9.4117647058823538
938851AE1-113 C
Adder
10.7835294117647079.166
938852AE1-113 E
Adder
38.2329411764705932.498
934101AD2-000 1
Adder
5.8152941176470594.943
934111AD2-000 2
Adder
8.1694117647058836.944
274704KENDALL ;1C
50/50
5.9235.923
274705KENDALL ;1S
50/50
3.9613.961
274706KENDALL ;2C
50/50
5.9235.923
274707KENDALL ;2S
50/50
3.9613.961
276640AC1-204 GEN1
50/50
17.28517.285
276642AC1-204 GEN2
50/50
17.50217.502
293516O-009 E
Adder
17.15882352941176614.585
916212CRESCENT ;1U
Adder
4.343.689
924048AB2-047 E1
Adder
8.5941176470588237.305
924049AB2-047 E2
Adder
8.7294117647058837.42
927208AC1-214 E1
Adder
2.92941176470588262.49
927209AC1-214 E2
Adder
2.92941176470588262.49
990901L-005 E
Adder
12.28823529411764810.445
290108LEEDK;1U E
Adder
19.07882352941176416.217
916221Z1-073 E
Adder
6.0411764705882355.135
926821AC1-168 C
Adder
0.8317647058823530.707
926822AC1-168 E
Adder
5.5847058823529414.747
936292AD2-038 E
Adder
11.5917647058823539.853
936511AD2-066 C
Adder
7.3411764705882366.24
936512AD2-066 E
Adder
4.8941176470588244.16
942421AE2-255 C
Adder
4.0847058823529413.472
942422AE2-255 E
Adder
12.25411764705882510.416
942651AE2-281 C
Adder
0.65647058823529430.558
942652AE2-281 E
Adder
4.03294117647058853.428
943121AE2-341 C
Adder
8.3105882352941187.064
943122AE2-341 E
Adder
4.0811764705882353.469
943591AF1-030 C
Adder
5.5270588235294124.698
943592AF1-030 E
Adder
2.73411764705882332.324
959091AF2-200 C
Adder
12.54823529411764810.666
959092AF2-200 E
Adder
8.3658823529411767.111
966822AG1-553 E
Adder
25.66705882352941321.817
938861AE1-114 C
Adder
3.52.975
938862AE1-114 E
Adder
11.94117647058823610.15
939321AE1-163 C
Adder
4.5952941176470593.906
939322AE1-163 E
Adder
28.22941176470588323.995
939741AE1-205 C
Adder
6.6905882352941185.687
939742AE1-205 E
Adder
9.247.854
946152AF1-280 E
Adder
20.51882352941176517.441
946321AF1-296 C
Adder
3.32000000000000032.822
946322AF1-296 E
Adder
15.54588235294117713.214
946671AF1-331 C
Adder
1.95529411764705881.662
962691AG1-118 C
Adder
17.414.79
962692AG1-118 E
Adder
11.69.86
965931AG1-462 C
Adder
15.10352941176470612.838
965932AG1-462 E
Adder
10.0694117647058818.559
920272AA2-123 E
Adder
2.53411764705882362.154
276170Z1-108 E
Adder
2.58588235294117652.198
276626AG1-044 E
Adder
0.067058823529411770.057
990497J1323
External Queue
-1.8008151054382324-1.8008151054382324
990547J1333 G
External Queue
-25.955141067504883-25.955141067504883
990552J1334 G
External Queue
-25.955141067504883-25.955141067504883
990557J1335 G
External Queue
-25.955141067504883-25.955141067504883
990562J1336 G
External Queue
-25.955141067504883-25.955141067504883
990577J1339
External Queue
-28.660625457763672-28.660625457763672
990582J1340
External Queue
-28.660625457763672-28.660625457763672
990647J1355
External Queue
-11.565272331237793-11.565272331237793
990662J1358
External Queue
-13.962589263916016-13.962589263916016
991182J1586 G
External Queue
-35.323299407958984-35.323299407958984
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.2990.299
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.48876.488
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.95815.958
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.2971.297
NYPJM->LTFIMP_NY
CLTF
0.7040.704
WECLTFEXP_WEC->PJM
CLTF
3.6463.646
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1710.171
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0650.065
TVALTFEXP_TVA->PJM
CLTF
1.831.83
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.3060.306
MECLTFEXP_MEC->PJM
CLTF
12.68312.683
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.8420.842
LAGNLTFEXP_LAGN->PJM
CLTF
3.9933.993
SIGELTFEXP_SIGE->PJM
CLTF
0.0390.039
O66PJM->LTFIMP_O-066
CMTX_NF
8.3278.327

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.65 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1228.52
MW Contribution:5.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.22941176470588241.895
962012AG1-044 E
Adder
0.0529411764705882350.045
962781AG1-127 C
Adder
5.94117647058823555.05
962782AG1-127 E
Adder
3.9541176470588243.361
966091AG1-478 C
Adder
1.76941176470588251.504
966092AG1-478 E
Adder
0.44470588235294120.378
966441AG1-513 C
Adder
0.434117647058823550.369
966442AG1-513 E
Adder
0.65058823529411770.553
290021O50 E
Adder
16.3552941176470613.902
290051GSG-6; E
Adder
8.8682352941176487.538
295109WESTBROOK E
Adder
4.7482352941176474.036
295111SUBLETTE E
Adder
2.3082352941176471.962
910542X3-005 E
Adder
0.53764705882352950.457
918052AA1-018 E OP
Adder
14.9023529411764712.667
933911AD1-013 C
Adder
1.56117647058823541.327
933912AD1-013 E
Adder
2.49411764705882362.12
934722AD1-100 E
Adder
76.7823529411764765.265
937002AD2-134 E
Adder
8.5752941176470587.289
937312AD2-172 E
Adder
2.8647058823529412.435
958481AF2-142 C
Adder
10.2776470588235318.736
958482AF2-142 E
Adder
6.8517647058823535.824
958491AF2-143 C
Adder
9.8058823529411778.335
958492AF2-143 E
Adder
6.537647058823535.557
958912AF2-182 E
Adder
28.79647058823529424.477
959081AF2-199 C
Adder
6.0258823529411775.122
959082AF2-199 E
Adder
3.01294117647058852.561
959351AF2-226 C
Adder
2.0270588235294121.723
959352AF2-226 E
Adder
3.0411764705882352.585
960281AF2-319 C
Adder
2.0270588235294121.723
960282AF2-319 E
Adder
3.0411764705882352.585
960582AF2-349 E
Adder
30.726.095
960751AF2-366 C
Adder
5.9247058823529415.036
960752AF2-366 E
Adder
3.94941176470588263.357
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274676JOLIET 29;8U
Adder
62.29647058823529452.952
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
274687WILL CNTY;4U
Adder
56.08235294117647447.67
274859EASYR;U1 E
Adder
10.1270588235294138.608
274860EASYR;U2 E
Adder
10.1270588235294138.608
276591L-013 2
Adder
3.11882352941176462.651
293061N-015 E
Adder
13.20352941176470711.223
293644O22 E1
Adder
11.6458823529411759.899
293645O22 E2
Adder
13.33882352941176411.338
293715O-029 E
Adder
8.1929411764705896.964
293716O-029 E
Adder
4.4917647058823533.818
293717O-029 E
Adder
4.1282352941176473.509
293771O-035 E
Adder
5.7870588235294124.919
294392P-010 E
Adder
16.76941176470588214.254
294401BSHIL;1U E
Adder
3.9070588235294123.321
294763P-046 E
Adder
7.9611764705882366.767
925582AC1-033 E
Adder
7.9023529411764716.717
933411AC2-154 C
Adder
2.1211764705882351.803
933412AC2-154 E
Adder
3.46117647058823552.942
939061AE1-134 2
Adder
1.15294117647058810.98
940502AE2-035 E
Adder
2.8647058823529412.435
957331AF2-027 C
Adder
2.1211764705882351.803
957332AF2-027 E
Adder
3.1823529411764712.705
957471AF2-041 C
Adder
18.07882352941176815.367
957472AF2-041 E
Adder
9.0400000000000017.684
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
274890CAYUG;1U E
Adder
11.4552941176470599.737
274891CAYUG;2U E
Adder
11.4552941176470599.737
938851AE1-113 C
Adder
6.7458823529411775.734
938852AE1-113 E
Adder
23.91882352941176420.331
934101AD2-000 1
Adder
4.91411764705882354.177
934111AD2-000 2
Adder
5.0882352941176484.325
275149KELLYCK ;1E
Adder
15.63058823529411813.286
293516O-009 E
Adder
15.8423529411764713.466
293519PILOT HIL;1E
Adder
15.63058823529411813.286
916212CRESCENT ;1U
Adder
4.0658823529411773.456
927208AC1-214 E1
Adder
2.7435294117647062.332
927209AC1-214 E2
Adder
2.7435294117647062.332
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
274805UNIV PK N;1U
50/50
1.9131.913
274807UNIV PK N;3U
50/50
1.9251.925
274808UNIV PK N;4U
50/50
1.9171.917
926821AC1-168 C
Adder
0.96235294117647050.818
926822AC1-168 E
Adder
6.4588235294117655.49
936292AD2-038 E
Adder
13.46705882352941211.447
936371AD2-047 C
Adder
3.7964705882352943.227
936372AD2-047 E
Adder
18.53411764705882415.754
936461AD2-060 C
Adder
2.2329411764705881.898
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
942421AE2-255 C
Adder
2.5552941176470592.172
942422AE2-255 E
Adder
7.6658823529411776.516
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
943121AE2-341 C
Adder
10.8588235294117659.23
943122AE2-341 E
Adder
5.3317647058823534.532
943591AF1-030 C
Adder
7.2211764705882366.138
943592AF1-030 E
Adder
3.5729411764705883.037
959091AF2-200 C
Adder
12.05294117647058810.245
959092AF2-200 E
Adder
8.0352941176470596.83
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
961502AF2-441 E
Adder
10.8105882352941189.189
938861AE1-114 C
Adder
3.3164705882352942.819
938862AE1-114 E
Adder
11.315294117647069.618
939321AE1-163 C
Adder
5.3388235294117654.538
939322AE1-163 E
Adder
32.7952941176470627.876
939351AE1-166 C
Adder
8.555294117647067.272
939352AE1-166 E
Adder
7.897647058823536.713
939401AE1-172 C
Adder
4.4776470588235293.806
939402AE1-172 E
Adder
20.9658823529411817.821
946152AF1-280 E
Adder
19.1976470588235316.318
946671AF1-331 C
Adder
2.0282352941176471.724
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
941551AE2-152 C
Adder
9.8717647058823528.391
941552AE2-152 E
Adder
6.5811764705882365.594
958011AF2-095 C
Adder
9.6458823529411778.199
958012AF2-095 E
Adder
6.4305882352941185.466
274810UNIV PK N;6U
50/50
1.9171.917
274811UNIV PK N;7U
50/50
1.9251.925
274812UNIV PK N;8U
50/50
1.9091.909
274813UNIV PK N;9U
50/50
1.9091.909
274814UNIV PK N;0U
50/50
1.9011.901
274815UNIV PK N;XU
50/50
1.9131.913
274816UNIV PK N;YU
50/50
1.9251.925
920272AA2-123 E
Adder
2.4364705882352942.071
276170Z1-108 E
Adder
2.48588235294117642.113
276626AG1-044 E
Adder
0.062352941176470590.053
276675AE2-062 E
Adder
0.135294117647058840.115
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
NYPJM->LTFIMP_NY
CLTF
0.9330.933
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.65 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1228.52
MW Contribution:5.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.22941176470588241.895
962012AG1-044 E
Adder
0.0529411764705882350.045
962781AG1-127 C
Adder
5.94117647058823555.05
962782AG1-127 E
Adder
3.9541176470588243.361
966091AG1-478 C
Adder
1.76941176470588251.504
966092AG1-478 E
Adder
0.44470588235294120.378
966441AG1-513 C
Adder
0.434117647058823550.369
966442AG1-513 E
Adder
0.65058823529411770.553
290021O50 E
Adder
16.3552941176470613.902
290051GSG-6; E
Adder
8.8682352941176487.538
295109WESTBROOK E
Adder
4.7482352941176474.036
295111SUBLETTE E
Adder
2.3082352941176471.962
910542X3-005 E
Adder
0.53764705882352950.457
918052AA1-018 E OP
Adder
14.9023529411764712.667
933911AD1-013 C
Adder
1.56117647058823541.327
933912AD1-013 E
Adder
2.49411764705882362.12
934722AD1-100 E
Adder
76.7823529411764765.265
937002AD2-134 E
Adder
8.5752941176470587.289
937312AD2-172 E
Adder
2.8647058823529412.435
958481AF2-142 C
Adder
10.2776470588235318.736
958482AF2-142 E
Adder
6.8517647058823535.824
958491AF2-143 C
Adder
9.8058823529411778.335
958492AF2-143 E
Adder
6.537647058823535.557
958912AF2-182 E
Adder
28.79647058823529424.477
959081AF2-199 C
Adder
6.0258823529411775.122
959082AF2-199 E
Adder
3.01294117647058852.561
959351AF2-226 C
Adder
2.0270588235294121.723
959352AF2-226 E
Adder
3.0411764705882352.585
960281AF2-319 C
Adder
2.0270588235294121.723
960282AF2-319 E
Adder
3.0411764705882352.585
960582AF2-349 E
Adder
30.726.095
960751AF2-366 C
Adder
5.9247058823529415.036
960752AF2-366 E
Adder
3.94941176470588263.357
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274676JOLIET 29;8U
Adder
62.29647058823529452.952
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
274687WILL CNTY;4U
Adder
56.08235294117647447.67
274859EASYR;U1 E
Adder
10.1270588235294138.608
274860EASYR;U2 E
Adder
10.1270588235294138.608
276591L-013 2
Adder
3.11882352941176462.651
293061N-015 E
Adder
13.20352941176470711.223
293644O22 E1
Adder
11.6458823529411759.899
293645O22 E2
Adder
13.33882352941176411.338
293715O-029 E
Adder
8.1929411764705896.964
293716O-029 E
Adder
4.4917647058823533.818
293717O-029 E
Adder
4.1282352941176473.509
293771O-035 E
Adder
5.7870588235294124.919
294392P-010 E
Adder
16.76941176470588214.254
294401BSHIL;1U E
Adder
3.9070588235294123.321
294763P-046 E
Adder
7.9611764705882366.767
925582AC1-033 E
Adder
7.9023529411764716.717
933411AC2-154 C
Adder
2.1211764705882351.803
933412AC2-154 E
Adder
3.46117647058823552.942
939061AE1-134 2
Adder
1.15294117647058810.98
940502AE2-035 E
Adder
2.8647058823529412.435
957331AF2-027 C
Adder
2.1211764705882351.803
957332AF2-027 E
Adder
3.1823529411764712.705
957471AF2-041 C
Adder
18.07882352941176815.367
957472AF2-041 E
Adder
9.0400000000000017.684
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
274890CAYUG;1U E
Adder
11.4552941176470599.737
274891CAYUG;2U E
Adder
11.4552941176470599.737
938851AE1-113 C
Adder
6.7458823529411775.734
938852AE1-113 E
Adder
23.91882352941176420.331
934101AD2-000 1
Adder
4.91411764705882354.177
934111AD2-000 2
Adder
5.0882352941176484.325
275149KELLYCK ;1E
Adder
15.63058823529411813.286
293516O-009 E
Adder
15.8423529411764713.466
293519PILOT HIL;1E
Adder
15.63058823529411813.286
916212CRESCENT ;1U
Adder
4.0658823529411773.456
927208AC1-214 E1
Adder
2.7435294117647062.332
927209AC1-214 E2
Adder
2.7435294117647062.332
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
274805UNIV PK N;1U
50/50
1.9131.913
274807UNIV PK N;3U
50/50
1.9251.925
274808UNIV PK N;4U
50/50
1.9171.917
926821AC1-168 C
Adder
0.96235294117647050.818
926822AC1-168 E
Adder
6.4588235294117655.49
936292AD2-038 E
Adder
13.46705882352941211.447
936371AD2-047 C
Adder
3.7964705882352943.227
936372AD2-047 E
Adder
18.53411764705882415.754
936461AD2-060 C
Adder
2.2329411764705881.898
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
942421AE2-255 C
Adder
2.5552941176470592.172
942422AE2-255 E
Adder
7.6658823529411776.516
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
943121AE2-341 C
Adder
10.8588235294117659.23
943122AE2-341 E
Adder
5.3317647058823534.532
943591AF1-030 C
Adder
7.2211764705882366.138
943592AF1-030 E
Adder
3.5729411764705883.037
959091AF2-200 C
Adder
12.05294117647058810.245
959092AF2-200 E
Adder
8.0352941176470596.83
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
961502AF2-441 E
Adder
10.8105882352941189.189
938861AE1-114 C
Adder
3.3164705882352942.819
938862AE1-114 E
Adder
11.315294117647069.618
939321AE1-163 C
Adder
5.3388235294117654.538
939322AE1-163 E
Adder
32.7952941176470627.876
939351AE1-166 C
Adder
8.555294117647067.272
939352AE1-166 E
Adder
7.897647058823536.713
939401AE1-172 C
Adder
4.4776470588235293.806
939402AE1-172 E
Adder
20.9647058823529417.82
946152AF1-280 E
Adder
19.1976470588235316.318
946671AF1-331 C
Adder
2.0282352941176471.724
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
941551AE2-152 C
Adder
9.8717647058823528.391
941552AE2-152 E
Adder
6.5811764705882365.594
958011AF2-095 C
Adder
9.6458823529411778.199
958012AF2-095 E
Adder
6.4305882352941185.466
274810UNIV PK N;6U
50/50
1.9171.917
274811UNIV PK N;7U
50/50
1.9251.925
274812UNIV PK N;8U
50/50
1.9091.909
274813UNIV PK N;9U
50/50
1.9091.909
274814UNIV PK N;0U
50/50
1.9011.901
274815UNIV PK N;XU
50/50
1.9131.913
274816UNIV PK N;YU
50/50
1.9251.925
920272AA2-123 E
Adder
2.4364705882352942.071
276170Z1-108 E
Adder
2.48588235294117642.113
276626AG1-044 E
Adder
0.062352941176470590.053
276675AE2-062 E
Adder
0.135294117647058840.115
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
NYPJM->LTFIMP_NY
CLTF
0.9330.933
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.64 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1228.4
MW Contribution:5.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.21411764705882331.882
962012AG1-044 E
Adder
0.0529411764705882350.045
962781AG1-127 C
Adder
5.8976470588235295.013
962782AG1-127 E
Adder
3.92470588235294133.336
966091AG1-478 C
Adder
1.7552941176470591.492
966092AG1-478 E
Adder
0.44117647058823530.375
966441AG1-513 C
Adder
0.430588235294117660.366
966442AG1-513 E
Adder
0.64470588235294120.548
290021O50 E
Adder
16.24352941176470813.807
290051GSG-6; E
Adder
8.8082352941176477.487
295109WESTBROOK E
Adder
4.7152941176470594.008
295111SUBLETTE E
Adder
2.29294117647058831.949
910542X3-005 E
Adder
0.53058823529411770.451
918052AA1-018 E OP
Adder
14.7952941176470612.576
933911AD1-013 C
Adder
1.55058823529411781.318
933912AD1-013 E
Adder
2.47764705882352932.106
934722AD1-100 E
Adder
76.1635294117647164.739
937002AD2-134 E
Adder
8.5164705882352937.239
937312AD2-172 E
Adder
2.84588235294117682.419
958481AF2-142 C
Adder
10.2035294117647068.673
958482AF2-142 E
Adder
6.8023529411764715.782
958491AF2-143 C
Adder
9.748.279
958492AF2-143 E
Adder
6.4929411764705885.519
958912AF2-182 E
Adder
28.6258823529411824.332
959081AF2-199 C
Adder
5.9858823529411775.088
959082AF2-199 E
Adder
2.99294117647058842.544
959351AF2-226 C
Adder
2.0105882352941181.709
959352AF2-226 E
Adder
3.01647058823529422.564
960281AF2-319 C
Adder
2.0105882352941181.709
960282AF2-319 E
Adder
3.01647058823529422.564
960582AF2-349 E
Adder
30.4847058823529425.912
960751AF2-366 C
Adder
5.8811764705882354.999
960752AF2-366 E
Adder
3.92117647058823553.333
274675JOLIET 29;7U
Adder
61.79058823529411652.522
274676JOLIET 29;8U
Adder
61.7682352941176552.503
274682WAUKEGAN ;7U
Adder
34.8235294117647129.6
274683WAUKEGAN ;8U
Adder
37.5458823529411831.914
274687WILL CNTY;4U
Adder
55.58000000000000547.243
274859EASYR;U1 E
Adder
10.0658823529411758.556
274860EASYR;U2 E
Adder
10.0658823529411758.556
276591L-013 2
Adder
3.09411764705882362.63
293061N-015 E
Adder
13.10117647058823411.136
293644O22 E1
Adder
11.5517647058823549.819
293645O22 E2
Adder
13.2305882352941211.246
293715O-029 E
Adder
8.1494117647058816.927
293716O-029 E
Adder
4.46823529411764753.798
293717O-029 E
Adder
4.1070588235294123.491
293771O-035 E
Adder
5.7611764705882364.897
294392P-010 E
Adder
16.63882352941176614.143
294401BSHIL;1U E
Adder
7.17647058823529356.1
294410BSHIL;2U E
Adder
7.17647058823529356.1
294763P-046 E
Adder
7.9094117647058826.723
925582AC1-033 E
Adder
7.8670588235294126.687
933411AC2-154 C
Adder
2.10235294117647081.787
933412AC2-154 E
Adder
3.42941176470588262.915
939061AE1-134 2
Adder
1.14705882352941170.975
940502AE2-035 E
Adder
2.84588235294117682.419
957331AF2-027 C
Adder
2.1047058823529411.789
957332AF2-027 E
Adder
3.15764705882352952.684
957471AF2-041 C
Adder
17.9576470588235315.264
957472AF2-041 E
Adder
8.9788235294117647.632
274674JOLIET 9 ;6U
Adder
31.0329411764705926.378
274890CAYUG;1U E
Adder
11.395294117647069.686
274891CAYUG;2U E
Adder
11.395294117647069.686
938851AE1-113 C
Adder
6.75.695
938852AE1-113 E
Adder
23.75647058823529520.193
934101AD2-000 1
Adder
4.8788235294117654.147
934111AD2-000 2
Adder
5.0470588235294124.29
275149KELLYCK ;1E
Adder
15.48823529411764713.165
293516O-009 E
Adder
15.7576470588235313.394
293519PILOT HIL;1E
Adder
15.48823529411764713.165
916212CRESCENT ;1U
Adder
4.0470588235294123.44
927208AC1-214 E1
Adder
2.7317647058823532.322
927209AC1-214 E2
Adder
2.7317647058823532.322
290108LEEDK;1U E
Adder
20.2152941176470617.183
916221Z1-073 E
Adder
6.2070588235294125.276
274805UNIV PK N;1U
50/50
1.9031.903
274807UNIV PK N;3U
50/50
1.9151.915
274808UNIV PK N;4U
50/50
1.9071.907
926821AC1-168 C
Adder
0.95764705882352940.814
926822AC1-168 E
Adder
6.4258823529411765.462
936292AD2-038 E
Adder
13.37529411764705911.369
936371AD2-047 C
Adder
3.76235294117647053.198
936372AD2-047 E
Adder
18.36705882352941215.612
936461AD2-060 C
Adder
2.2129411764705881.881
936511AD2-066 C
Adder
7.1305882352941186.061
936512AD2-066 E
Adder
4.7541176470588244.041
942421AE2-255 C
Adder
2.53764705882352942.157
942422AE2-255 E
Adder
7.61411764705882456.472
942651AE2-281 C
Adder
0.75764705882352950.644
942652AE2-281 E
Adder
4.6529411764705893.955
943121AE2-341 C
Adder
10.7729411764705899.157
943122AE2-341 E
Adder
5.2905882352941184.497
943591AF1-030 C
Adder
7.1635294117647066.089
943592AF1-030 E
Adder
3.54470588235294143.013
959091AF2-200 C
Adder
11.97176470588235410.176
959092AF2-200 E
Adder
7.98117647058823556.784
960591AF2-350 C
Adder
6.637647058823535.642
960592AF2-350 E
Adder
4.4247058823529413.761
961502AF2-441 E
Adder
0.29882352941176470.254
938861AE1-114 C
Adder
3.2964705882352942.802
938862AE1-114 E
Adder
11.244705882352949.558
939321AE1-163 C
Adder
5.302352941176474.507
939322AE1-163 E
Adder
32.5729411764705927.687
939351AE1-166 C
Adder
8.4870588235294137.214
939352AE1-166 E
Adder
7.8341176470588236.659
939401AE1-172 C
Adder
4.4505882352941173.783
939402AE1-172 E
Adder
20.8352941176470617.71
946152AF1-280 E
Adder
19.08352941176470816.221
946671AF1-331 C
Adder
2.01411764705882361.712
962691AG1-118 C
Adder
18.6752941176470615.874
962692AG1-118 E
Adder
12.45058823529411810.583
941551AE2-152 C
Adder
9.7929411764705888.324
941552AE2-152 E
Adder
6.5282352941176485.549
958011AF2-095 C
Adder
9.557647058823538.124
958012AF2-095 E
Adder
6.3717647058823535.416
274810UNIV PK N;6U
50/50
1.9071.907
274811UNIV PK N;7U
50/50
1.9151.915
274812UNIV PK N;8U
50/50
1.8991.899
274813UNIV PK N;9U
50/50
1.8991.899
274814UNIV PK N;0U
50/50
1.8911.891
274815UNIV PK N;XU
50/50
1.9031.903
274816UNIV PK N;YU
50/50
1.9151.915
920272AA2-123 E
Adder
2.4188235294117652.056
276170Z1-108 E
Adder
2.4670588235294122.097
276626AG1-044 E
Adder
0.061176470588235290.052
276675AE2-062 E
Adder
0.134117647058823540.114
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6070.607
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.23368.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.47412.474
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7291.729
NYPJM->LTFIMP_NY
CLTF
0.9310.931
WECLTFEXP_WEC->PJM
CLTF
3.2883.288
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4090.409
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.210.21
TVALTFEXP_TVA->PJM
CLTF
1.1671.167
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.4090.409
MECLTFEXP_MEC->PJM
CLTF
10.92410.924
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.1721.172
LAGNLTFEXP_LAGN->PJM
CLTF
2.992.99
SIGELTFEXP_SIGE->PJM
CLTF
0.0150.015
O66PJM->LTFIMP_O-066
CMTX_NF
11.09411.094

Details for WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT5-6___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.26 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1707.81
MW Contribution:6.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.7917647058823532.373
962781AG1-127 C
Adder
7.4258823529411776.312
962782AG1-127 E
Adder
4.94117647058823554.2
966091AG1-478 C
50/50
2.242.24
966092AG1-478 E
50/50
0.5630.563
966441AG1-513 C
Adder
0.540.459
966442AG1-513 E
Adder
0.80941176470588230.688
290021O50 E
Adder
20.39647058823529617.337
290051GSG-6; E
Adder
11.102352941176479.437
295109WESTBROOK E
Adder
5.9435294117647065.052
295111SUBLETTE E
Adder
2.88941176470588262.456
910542X3-005 E
Adder
0.76941176470588240.654
918052AA1-018 E OP
Adder
17.26941176470588214.679
933911AD1-013 C
Adder
1.95411764705882351.661
933912AD1-013 E
Adder
3.12235294117647082.654
934721AD1-100 C
50/50
3.8843.884
934722AD1-100 E
50/50
118.444118.444
937002AD2-134 E
Adder
10.7341176470588249.124
958481AF2-142 C
Adder
11.90941176470588110.123
958482AF2-142 E
Adder
7.93999999999999956.749
958491AF2-143 C
Adder
11.6023529411764729.862
958492AF2-143 E
Adder
7.7352941176470596.575
959351AF2-226 C
Adder
2.64941176470588242.252
959352AF2-226 E
Adder
3.9741176470588243.378
960281AF2-319 C
Adder
2.64941176470588242.252
960282AF2-319 E
Adder
3.9741176470588243.378
960582AF2-349 E
Adder
38.2764705882352932.535
960751AF2-366 C
Adder
7.4047058823529416.294
960752AF2-366 E
Adder
4.9364705882352944.196
274654BRAIDWOOD;1U
50/50
29.85229.852
274655BRAIDWOOD;2U
50/50
29.08529.085
274660LASCO STA;1U
50/50
27.28127.281
274661LASCO STA;2U
50/50
27.3727.37
274675JOLIET 29;7U
Adder
76.0835294117647264.671
274676JOLIET 29;8U
Adder
76.0835294117647264.671
274682WAUKEGAN ;7U
Adder
43.47411764705882636.953
274683WAUKEGAN ;8U
Adder
46.8729411764705939.842
274687WILL CNTY;4U
Adder
70.7847058823529460.167
274771LINCOLN ;2U
50/50
3.0623.062
274772LINCOLN ;3U
50/50
3.0623.062
274773LINCOLN ;4U
50/50
3.0623.062
274774LINCOLN ;5U
50/50
3.0623.062
274775LINCOLN ;6U
50/50
3.0623.062
274776LINCOLN ;7U
50/50
3.0623.062
274777LINCOLN ;8U
50/50
3.0623.062
274800UNIV PARK;3U
50/50
1.2031.203
274847GR RIDGE ;BU
50/50
0.6370.637
274863CAYUGA RI;1U
50/50
0.5150.515
274864CAYUGA RI;2U
50/50
0.5150.515
274871GR RIDGE ;2U
50/50
0.2370.237
274887PILOT HIL;1U
50/50
0.850.85
274888KELLY CRK;1U
50/50
0.850.85
276591L-013 2
Adder
3.8835294117647063.301
293061N-015 E
50/50
17.13617.136
293644O22 E1
Adder
15.21999999999999912.937
293645O22 E2
Adder
17.43176470588235514.817
294392P-010 E
50/50
21.76221.762
933411AC2-154 C
50/50
2.8352.835
933412AC2-154 E
50/50
4.6254.625
957331AF2-027 C
Adder
2.62941176470588232.235
957332AF2-027 E
Adder
3.94352941176470573.352
957471AF2-041 C
Adder
22.63411764705882619.239
957472AF2-041 E
Adder
11.3176470588235289.62
274674JOLIET 9 ;6U
Adder
38.7023529411764732.897
274890CAYUG;1U E
50/50
16.86716.867
274891CAYUG;2U E
50/50
16.86716.867
938851AE1-113 C
Adder
8.4129411764705877.151
938852AE1-113 E
Adder
29.82941176470588525.355
934101AD2-000 1
Adder
6.1705882352941185.245
934111AD2-000 2
Adder
6.317647058823535.37
275149KELLYCK ;1E
50/50
20.88720.887
293519PILOT HIL;1E
50/50
20.88720.887
290108LEEDK;1U E
Adder
25.4658823529411821.646
916221Z1-073 E
Adder
7.82352941176470656.65
936292AD2-038 E
Adder
15.93411764705882513.544
936371AD2-047 C
50/50
5.0735.073
936372AD2-047 E
50/50
24.76624.766
936461AD2-060 C
50/50
2.9842.984
936511AD2-066 C
Adder
8.977647058823537.631
936512AD2-066 E
Adder
5.9847058823529415.087
942421AE2-255 C
Adder
3.18705882352941172.709
942422AE2-255 E
Adder
9.5611764705882368.127
942651AE2-281 C
Adder
0.90235294117647060.767
942652AE2-281 E
Adder
5.5435294117647054.712
943121AE2-341 C
Adder
13.58823529411764911.55
943122AE2-341 E
Adder
6.6729411764705885.672
943591AF1-030 C
Adder
9.0364705882352957.681
943592AF1-030 E
Adder
4.4705882352941183.8
959091AF2-200 C
Adder
15.08941176470588312.826
959092AF2-200 E
Adder
9.9870588235294138.489
960591AF2-350 C
50/50
8.9528.952
960592AF2-350 E
50/50
5.9685.968
961501AF2-441 C
Adder
10.5505882352941188.968
961502AF2-441 E
Adder
15.82588235294117713.452
939321AE1-163 C
Adder
6.3164705882352945.369
939322AE1-163 E
Adder
38.803529411764732.983
939351AE1-166 C
50/50
13.19813.198
939352AE1-166 E
50/50
12.18312.183
939401AE1-172 C
50/50
6.716.71
939402AE1-172 E
50/50
31.41531.415
946671AF1-331 C
Adder
2.53882352941176452.158
962691AG1-118 C
Adder
23.50941176470588419.983
962692AG1-118 E
Adder
15.67294117647058713.322
941551AE2-152 C
50/50
15.22915.229
941552AE2-152 E
50/50
10.15210.152
958011AF2-095 C
50/50
12.8912.89
958012AF2-095 E
50/50
8.5938.593
274798UNIV PARK;1U
50/50
1.2121.212
274770LINCOLN ;1U
50/50
3.0623.062
920272AA2-123 E
Adder
3.0352941176470592.58
276170Z1-108 E
Adder
3.0917647058823532.628
276675AE2-062 E
Adder
0.162352941176470620.138
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8740.874
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.2195.21
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.37116.371
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
2.2932.293
NYPJM->LTFIMP_NY
CLTF
1.2271.227
WECLTFEXP_WEC->PJM
CLTF
4.1174.117
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5980.598
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3140.314
TVALTFEXP_TVA->PJM
CLTF
1.4271.427
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6470.647
MECLTFEXP_MEC->PJM
CLTF
13.89713.897
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.8521.852
LAGNLTFEXP_LAGN->PJM
CLTF
3.7743.774
SIGELTFEXP_SIGE->PJM
CLTF
0.0210.021
O66PJM->LTFIMP_O-066
CMTX_NF
14.71114.711

Details for WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.29 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1752.4
MW Contribution:6.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.8647058823529412.435
962781AG1-127 C
Adder
7.6223529411764716.479
962782AG1-127 E
Adder
5.07294117647058854.312
966091AG1-478 C
50/50
2.2992.299
966092AG1-478 E
50/50
0.5780.578
966441AG1-513 C
Adder
0.55411764705882350.471
966442AG1-513 E
Adder
0.8317647058823530.707
290021O50 E
Adder
20.9376470588235317.797
290051GSG-6; E
Adder
11.395294117647069.686
295109WESTBROOK E
Adder
6.1011764705882365.186
295111SUBLETTE E
Adder
2.96588235294117642.521
910542X3-005 E
Adder
0.79058823529411770.672
918052AA1-018 E OP
Adder
17.73647058823529615.076
933911AD1-013 C
Adder
2.00588235294117641.705
933912AD1-013 E
Adder
3.20470588235294152.724
934721AD1-100 C
50/50
3.9823.982
934722AD1-100 E
50/50
121.416121.416
937002AD2-134 E
Adder
11.0188235294117659.366
958481AF2-142 C
Adder
12.23176470588235410.397
958482AF2-142 E
Adder
8.1541176470588246.931
958491AF2-143 C
Adder
11.91411764705882510.127
958492AF2-143 E
Adder
7.9435294117647066.752
959351AF2-226 C
Adder
2.71882352941176462.311
959352AF2-226 E
Adder
4.0788235294117653.467
960281AF2-319 C
Adder
2.71882352941176462.311
960282AF2-319 E
Adder
4.0788235294117653.467
960582AF2-349 E
Adder
39.29058823529411633.397
960751AF2-366 C
Adder
7.6011764705882366.461
960752AF2-366 E
Adder
5.0670588235294124.307
274654BRAIDWOOD;1U
50/50
30.61530.615
274655BRAIDWOOD;2U
50/50
29.82929.829
274660LASCO STA;1U
50/50
27.98527.985
274661LASCO STA;2U
50/50
28.07728.077
274675JOLIET 29;7U
Adder
78.1152941176470566.398
274676JOLIET 29;8U
Adder
78.1152941176470566.398
274682WAUKEGAN ;7U
Adder
44.62823529411764437.934
274683WAUKEGAN ;8U
Adder
48.1176470588235340.9
274687WILL CNTY;4U
Adder
72.6647058823529561.765
274771LINCOLN ;2U
50/50
3.1623.162
274772LINCOLN ;3U
50/50
3.1623.162
274773LINCOLN ;4U
50/50
3.1623.162
274774LINCOLN ;5U
50/50
3.1623.162
274775LINCOLN ;6U
50/50
3.1623.162
274776LINCOLN ;7U
50/50
3.1623.162
274777LINCOLN ;8U
50/50
3.1623.162
274800UNIV PARK;3U
50/50
1.2351.235
274847GR RIDGE ;BU
50/50
0.6540.654
274863CAYUGA RI;1U
50/50
0.5280.528
274864CAYUGA RI;2U
50/50
0.5280.528
274871GR RIDGE ;2U
50/50
0.2430.243
274887PILOT HIL;1U
50/50
0.8720.872
274888KELLY CRK;1U
50/50
0.8720.872
276591L-013 2
Adder
3.98705882352941153.389
293061N-015 E
50/50
17.5817.58
293644O22 E1
Adder
15.62117647058823713.278
293645O22 E2
Adder
17.89176470588235215.208
294392P-010 E
50/50
22.32722.327
933411AC2-154 C
50/50
2.9082.908
933412AC2-154 E
50/50
4.7454.745
957331AF2-027 C
Adder
2.69882352941176462.294
957332AF2-027 E
Adder
4.0482352941176473.441
957471AF2-041 C
Adder
23.2329411764705919.748
957472AF2-041 E
Adder
11.6164705882352959.874
274674JOLIET 9 ;6U
Adder
39.72588235294118433.767
274890CAYUG;1U E
50/50
17.29517.295
274891CAYUG;2U E
50/50
17.29517.295
938851AE1-113 C
Adder
8.6364705882352947.341
938852AE1-113 E
Adder
30.62117647058823526.028
934101AD2-000 1
Adder
6.3329411764705885.383
934111AD2-000 2
Adder
6.4847058823529415.512
275149KELLYCK ;1E
50/50
21.42821.428
293519PILOT HIL;1E
50/50
21.42821.428
290108LEEDK;1U E
Adder
26.1422.219
916221Z1-073 E
Adder
8.0305882352941186.826
936292AD2-038 E
Adder
16.3623529411764713.908
936371AD2-047 C
50/50
5.2045.204
936372AD2-047 E
50/50
25.40825.408
936461AD2-060 C
50/50
3.0613.061
936511AD2-066 C
Adder
9.2141176470588247.832
936512AD2-066 E
Adder
6.1435294117647075.222
942421AE2-255 C
Adder
3.2717647058823532.781
942422AE2-255 E
Adder
9.8141176470588248.342
942651AE2-281 C
Adder
0.92705882352941180.788
942652AE2-281 E
Adder
5.6929411764705894.839
943121AE2-341 C
Adder
13.94823529411764811.856
943122AE2-341 E
Adder
6.84941176470588255.822
943591AF1-030 C
Adder
9.2752941176470597.884
943592AF1-030 E
Adder
4.5894117647058823.901
959091AF2-200 C
Adder
15.48823529411764713.165
959092AF2-200 E
Adder
10.2505882352941178.713
960591AF2-350 C
50/50
9.1849.184
960592AF2-350 E
50/50
6.1226.122
961501AF2-441 C
Adder
10.8282352941176499.204
961502AF2-441 E
Adder
16.2423529411764713.806
939321AE1-163 C
Adder
6.4870588235294125.514
939322AE1-163 E
Adder
39.8482352941176533.871
939351AE1-166 C
50/50
13.52913.529
939352AE1-166 E
50/50
12.48812.488
939401AE1-172 C
50/50
6.886.88
939402AE1-172 E
50/50
32.20932.209
946671AF1-331 C
Adder
2.60588235294117652.215
962691AG1-118 C
Adder
24.13176470588235420.512
962692AG1-118 E
Adder
16.0882352941176513.675
941551AE2-152 C
50/50
15.61115.611
941552AE2-152 E
50/50
10.40710.407
958011AF2-095 C
50/50
13.22413.224
958012AF2-095 E
50/50
8.8168.816
274798UNIV PARK;1U
50/50
1.2441.244
274770LINCOLN ;1U
50/50
3.1623.162
920272AA2-123 E
Adder
3.11647058823529432.649
276170Z1-108 E
Adder
3.17411764705882372.698
276675AE2-062 E
Adder
0.167058823529411760.142
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8980.898
CBM West 1LTFEXP_CBM-W1->PJM
CBM
97.73297.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.79716.797
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
2.3542.354
NYPJM->LTFIMP_NY
CLTF
1.2591.259
WECLTFEXP_WEC->PJM
CLTF
4.2274.227
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.6140.614
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3230.323
TVALTFEXP_TVA->PJM
CLTF
1.4641.464
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6640.664
MECLTFEXP_MEC->PJM
CLTF
14.26314.263
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.9021.902
LAGNLTFEXP_LAGN->PJM
CLTF
3.8723.872
SIGELTFEXP_SIGE->PJM
CLTF
0.0220.022
O66PJM->LTFIMP_O-066
CMTX_NF
15.10215.102

Details for WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_112-65-BT5-6___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.43 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1710.31
MW Contribution:6.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.7917647058823532.373
962781AG1-127 C
Adder
7.4258823529411776.312
962782AG1-127 E
Adder
4.94117647058823554.2
966091AG1-478 C
50/50
2.242.24
966092AG1-478 E
50/50
0.5630.563
966441AG1-513 C
Adder
0.540.459
966442AG1-513 E
Adder
0.80941176470588230.688
290021O50 E
Adder
20.39647058823529617.337
290051GSG-6; E
Adder
11.102352941176479.437
295109WESTBROOK E
Adder
5.9435294117647065.052
295111SUBLETTE E
Adder
2.88941176470588262.456
910542X3-005 E
Adder
0.76941176470588240.654
918052AA1-018 E OP
Adder
17.26941176470588214.679
933911AD1-013 C
Adder
1.95411764705882351.661
933912AD1-013 E
Adder
3.12235294117647082.654
934721AD1-100 C
50/50
3.8843.884
934722AD1-100 E
50/50
118.444118.444
937002AD2-134 E
Adder
10.7341176470588249.124
958481AF2-142 C
Adder
11.90941176470588110.123
958482AF2-142 E
Adder
7.93999999999999956.749
958491AF2-143 C
Adder
11.6023529411764729.862
958492AF2-143 E
Adder
7.7352941176470596.575
959351AF2-226 C
Adder
2.64941176470588242.252
959352AF2-226 E
Adder
3.9741176470588243.378
960281AF2-319 C
Adder
2.64941176470588242.252
960282AF2-319 E
Adder
3.9741176470588243.378
960582AF2-349 E
Adder
38.2764705882352932.535
960751AF2-366 C
Adder
7.4047058823529416.294
960752AF2-366 E
Adder
4.9364705882352944.196
274654BRAIDWOOD;1U
50/50
29.85229.852
274655BRAIDWOOD;2U
50/50
29.08529.085
274660LASCO STA;1U
50/50
27.28127.281
274661LASCO STA;2U
50/50
27.3727.37
274675JOLIET 29;7U
Adder
76.0835294117647264.671
274676JOLIET 29;8U
Adder
76.0835294117647264.671
274682WAUKEGAN ;7U
Adder
43.47411764705882636.953
274683WAUKEGAN ;8U
Adder
46.8729411764705939.842
274687WILL CNTY;4U
Adder
70.7847058823529460.167
274771LINCOLN ;2U
50/50
3.0623.062
274772LINCOLN ;3U
50/50
3.0623.062
274773LINCOLN ;4U
50/50
3.0623.062
274774LINCOLN ;5U
50/50
3.0623.062
274775LINCOLN ;6U
50/50
3.0623.062
274776LINCOLN ;7U
50/50
3.0623.062
274777LINCOLN ;8U
50/50
3.0623.062
274800UNIV PARK;3U
50/50
1.2031.203
274847GR RIDGE ;BU
50/50
0.6370.637
274863CAYUGA RI;1U
50/50
0.5150.515
274864CAYUGA RI;2U
50/50
0.5150.515
274871GR RIDGE ;2U
50/50
0.2370.237
274887PILOT HIL;1U
50/50
0.850.85
274888KELLY CRK;1U
50/50
0.850.85
276591L-013 2
Adder
3.8835294117647063.301
293061N-015 E
50/50
17.13617.136
293644O22 E1
Adder
15.21999999999999912.937
293645O22 E2
Adder
17.43176470588235514.817
294392P-010 E
50/50
21.76221.762
933411AC2-154 C
50/50
2.8352.835
933412AC2-154 E
50/50
4.6254.625
957331AF2-027 C
Adder
2.62941176470588232.235
957332AF2-027 E
Adder
3.94352941176470573.352
957471AF2-041 C
Adder
22.63411764705882619.239
957472AF2-041 E
Adder
11.3176470588235289.62
274674JOLIET 9 ;6U
Adder
38.7023529411764732.897
274890CAYUG;1U E
50/50
16.86716.867
274891CAYUG;2U E
50/50
16.86716.867
938851AE1-113 C
Adder
8.4129411764705877.151
938852AE1-113 E
Adder
29.82941176470588525.355
934101AD2-000 1
Adder
6.1705882352941185.245
934111AD2-000 2
Adder
6.317647058823535.37
275149KELLYCK ;1E
50/50
20.88720.887
293519PILOT HIL;1E
50/50
20.88720.887
290108LEEDK;1U E
Adder
25.4658823529411821.646
916221Z1-073 E
Adder
7.82352941176470656.65
936292AD2-038 E
Adder
15.93411764705882513.544
936371AD2-047 C
50/50
5.0735.073
936372AD2-047 E
50/50
24.76624.766
936461AD2-060 C
50/50
2.9842.984
936511AD2-066 C
Adder
8.977647058823537.631
936512AD2-066 E
Adder
5.9847058823529415.087
942421AE2-255 C
Adder
3.18705882352941172.709
942422AE2-255 E
Adder
9.5611764705882368.127
942651AE2-281 C
Adder
0.90235294117647060.767
942652AE2-281 E
Adder
5.5435294117647054.712
943121AE2-341 C
Adder
13.58823529411764911.55
943122AE2-341 E
Adder
6.6729411764705885.672
943591AF1-030 C
Adder
9.0364705882352957.681
943592AF1-030 E
Adder
4.4705882352941183.8
959091AF2-200 C
Adder
15.08941176470588312.826
959092AF2-200 E
Adder
9.9870588235294138.489
960591AF2-350 C
50/50
8.9528.952
960592AF2-350 E
50/50
5.9685.968
961501AF2-441 C
Adder
10.5505882352941188.968
961502AF2-441 E
Adder
15.82588235294117713.452
939321AE1-163 C
Adder
6.3164705882352945.369
939322AE1-163 E
Adder
38.803529411764732.983
939351AE1-166 C
50/50
13.19813.198
939352AE1-166 E
50/50
12.18312.183
939401AE1-172 C
50/50
6.716.71
939402AE1-172 E
50/50
31.41531.415
946671AF1-331 C
Adder
2.53882352941176452.158
962691AG1-118 C
Adder
23.50941176470588419.983
962692AG1-118 E
Adder
15.67294117647058713.322
941551AE2-152 C
50/50
15.22915.229
941552AE2-152 E
50/50
10.15210.152
958011AF2-095 C
50/50
12.8912.89
958012AF2-095 E
50/50
8.5938.593
274798UNIV PARK;1U
50/50
1.2121.212
274770LINCOLN ;1U
50/50
3.0623.062
920272AA2-123 E
Adder
3.0352941176470592.58
276170Z1-108 E
Adder
3.0917647058823532.628
276675AE2-062 E
Adder
0.162352941176470620.138
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8740.874
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.2195.21
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.37116.371
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
2.2932.293
NYPJM->LTFIMP_NY
CLTF
1.2271.227
WECLTFEXP_WEC->PJM
CLTF
4.1174.117
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5980.598
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3140.314
TVALTFEXP_TVA->PJM
CLTF
1.4271.427
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6470.647
MECLTFEXP_MEC->PJM
CLTF
13.89713.897
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.8521.852
LAGNLTFEXP_LAGN->PJM
CLTF
3.7743.774
SIGELTFEXP_SIGE->PJM
CLTF
0.0210.021
O66PJM->LTFIMP_O-066
CMTX_NF
14.71114.711

Details for WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_112-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.46 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1754.83
MW Contribution:6.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.8647058823529412.435
962781AG1-127 C
Adder
7.6223529411764716.479
962782AG1-127 E
Adder
5.07294117647058854.312
966091AG1-478 C
50/50
2.2992.299
966092AG1-478 E
50/50
0.5780.578
966441AG1-513 C
Adder
0.55411764705882350.471
966442AG1-513 E
Adder
0.8317647058823530.707
290021O50 E
Adder
20.9376470588235317.797
290051GSG-6; E
Adder
11.395294117647069.686
295109WESTBROOK E
Adder
6.1011764705882365.186
295111SUBLETTE E
Adder
2.96588235294117642.521
910542X3-005 E
Adder
0.79058823529411770.672
918052AA1-018 E OP
Adder
17.73647058823529615.076
933911AD1-013 C
Adder
2.00588235294117641.705
933912AD1-013 E
Adder
3.20470588235294152.724
934721AD1-100 C
50/50
3.9823.982
934722AD1-100 E
50/50
121.416121.416
937002AD2-134 E
Adder
11.0188235294117659.366
958481AF2-142 C
Adder
12.23176470588235410.397
958482AF2-142 E
Adder
8.1541176470588246.931
958491AF2-143 C
Adder
11.91411764705882510.127
958492AF2-143 E
Adder
7.9435294117647066.752
959351AF2-226 C
Adder
2.71882352941176462.311
959352AF2-226 E
Adder
4.0788235294117653.467
960281AF2-319 C
Adder
2.71882352941176462.311
960282AF2-319 E
Adder
4.0788235294117653.467
960582AF2-349 E
Adder
39.29058823529411633.397
960751AF2-366 C
Adder
7.6011764705882366.461
960752AF2-366 E
Adder
5.0670588235294124.307
274654BRAIDWOOD;1U
50/50
30.61530.615
274655BRAIDWOOD;2U
50/50
29.82929.829
274660LASCO STA;1U
50/50
27.98527.985
274661LASCO STA;2U
50/50
28.07728.077
274675JOLIET 29;7U
Adder
78.1152941176470566.398
274676JOLIET 29;8U
Adder
78.1152941176470566.398
274682WAUKEGAN ;7U
Adder
44.62823529411764437.934
274683WAUKEGAN ;8U
Adder
48.1176470588235340.9
274687WILL CNTY;4U
Adder
72.6647058823529561.765
274771LINCOLN ;2U
50/50
3.1623.162
274772LINCOLN ;3U
50/50
3.1623.162
274773LINCOLN ;4U
50/50
3.1623.162
274774LINCOLN ;5U
50/50
3.1623.162
274775LINCOLN ;6U
50/50
3.1623.162
274776LINCOLN ;7U
50/50
3.1623.162
274777LINCOLN ;8U
50/50
3.1623.162
274800UNIV PARK;3U
50/50
1.2351.235
274847GR RIDGE ;BU
50/50
0.6540.654
274863CAYUGA RI;1U
50/50
0.5280.528
274864CAYUGA RI;2U
50/50
0.5280.528
274871GR RIDGE ;2U
50/50
0.2430.243
274887PILOT HIL;1U
50/50
0.8720.872
274888KELLY CRK;1U
50/50
0.8720.872
276591L-013 2
Adder
3.98705882352941153.389
293061N-015 E
50/50
17.5817.58
293644O22 E1
Adder
15.62117647058823713.278
293645O22 E2
Adder
17.89176470588235215.208
294392P-010 E
50/50
22.32722.327
933411AC2-154 C
50/50
2.9082.908
933412AC2-154 E
50/50
4.7454.745
957331AF2-027 C
Adder
2.69882352941176462.294
957332AF2-027 E
Adder
4.0482352941176473.441
957471AF2-041 C
Adder
23.2329411764705919.748
957472AF2-041 E
Adder
11.6164705882352959.874
274674JOLIET 9 ;6U
Adder
39.72588235294118433.767
274890CAYUG;1U E
50/50
17.29517.295
274891CAYUG;2U E
50/50
17.29517.295
938851AE1-113 C
Adder
8.6364705882352947.341
938852AE1-113 E
Adder
30.62117647058823526.028
934101AD2-000 1
Adder
6.3329411764705885.383
934111AD2-000 2
Adder
6.4847058823529415.512
275149KELLYCK ;1E
50/50
21.42821.428
293519PILOT HIL;1E
50/50
21.42821.428
290108LEEDK;1U E
Adder
26.1422.219
916221Z1-073 E
Adder
8.0305882352941186.826
936292AD2-038 E
Adder
16.3623529411764713.908
936371AD2-047 C
50/50
5.2045.204
936372AD2-047 E
50/50
25.40825.408
936461AD2-060 C
50/50
3.0613.061
936511AD2-066 C
Adder
9.2141176470588247.832
936512AD2-066 E
Adder
6.1435294117647075.222
942421AE2-255 C
Adder
3.2717647058823532.781
942422AE2-255 E
Adder
9.8141176470588248.342
942651AE2-281 C
Adder
0.92705882352941180.788
942652AE2-281 E
Adder
5.6929411764705894.839
943121AE2-341 C
Adder
13.94823529411764811.856
943122AE2-341 E
Adder
6.84941176470588255.822
943591AF1-030 C
Adder
9.2752941176470597.884
943592AF1-030 E
Adder
4.5894117647058823.901
959091AF2-200 C
Adder
15.48823529411764713.165
959092AF2-200 E
Adder
10.2505882352941178.713
960591AF2-350 C
50/50
9.1849.184
960592AF2-350 E
50/50
6.1226.122
961501AF2-441 C
Adder
10.8282352941176499.204
961502AF2-441 E
Adder
16.2423529411764713.806
939321AE1-163 C
Adder
6.4870588235294125.514
939322AE1-163 E
Adder
39.8482352941176533.871
939351AE1-166 C
50/50
13.52913.529
939352AE1-166 E
50/50
12.48812.488
939401AE1-172 C
50/50
6.886.88
939402AE1-172 E
50/50
32.20932.209
946671AF1-331 C
Adder
2.60588235294117652.215
962691AG1-118 C
Adder
24.13176470588235420.512
962692AG1-118 E
Adder
16.0882352941176513.675
941551AE2-152 C
50/50
15.61115.611
941552AE2-152 E
50/50
10.40710.407
958011AF2-095 C
50/50
13.22413.224
958012AF2-095 E
50/50
8.8168.816
274798UNIV PARK;1U
50/50
1.2441.244
274770LINCOLN ;1U
50/50
3.1623.162
920272AA2-123 E
Adder
3.11647058823529432.649
276170Z1-108 E
Adder
3.17411764705882372.698
276675AE2-062 E
Adder
0.167058823529411760.142
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8980.898
CBM West 1LTFEXP_CBM-W1->PJM
CBM
97.73297.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.79716.797
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
2.3542.354
NYPJM->LTFIMP_NY
CLTF
1.2591.259
WECLTFEXP_WEC->PJM
CLTF
4.2274.227
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.6140.614
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3230.323
TVALTFEXP_TVA->PJM
CLTF
1.4641.464
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6640.664
MECLTFEXP_MEC->PJM
CLTF
14.26314.263
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.9021.902
LAGNLTFEXP_LAGN->PJM
CLTF
3.8723.872
SIGELTFEXP_SIGE->PJM
CLTF
0.0220.022
O66PJM->LTFIMP_O-066
CMTX_NF
15.10215.102
CONTINGENCY 'AEP_P7-1_#11046___SRT-A'
 OPEN BRANCH FROM BUS 243219 TO BUS 246955 CKT 1   /*05DUMONT     345.0 - 05OLIVE_BP   345.0
 OPEN BRANCH FROM BUS 243228 TO BUS 243234 CKT 1   /*05MERIDN     345.0 - 05TWIN B     345.0
 OPEN BRANCH FROM BUS 243232 TO BUS 246955 CKT 1   /*05SORENS     345.0 - 05OLIVE_BP   345.0
END
CONTINGENCY '765-L11215__-S_SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
END
CONTINGENCY 'AEP_P1-2_#695_1681_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243207 CKT 1   /*05DUMONT     765.0 - 05GRNTWN     765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'COMED_P4_112-65-BT3-4___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT4-5___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'COMED_P4-6_116-345-R______SRT-A'
 DISCONNECT BUS 270767                                          /*GOODINGS ;1R 345.0
 DISCONNECT BUS 270769                                          /*GOODINGS ;2R 345.0
 DISCONNECT BUS 275240                                          /*GOODINGS ;1M 138.0
 TRIP BRANCH FROM BUS 270729 TO BUS 271385 TO BUS 275351 CKT 1  /*E FRANKFO; R 345.0 - E FRANKFO; R 138.0 - E FRANKFO;3C  34.5
END
CONTINGENCY 'COMED_P4_116-45-L11614__SRT-A'
 DISCONNECT BUS 270769                             /*GOODINGS ;2R 345.0
 TRIP BRANCH FROM BUS 270667 TO BUS 270665 CKT 1   /*BLUE ISL ;RT 345.0 - BLUE ISL ; R 345.0
 TRIP BRANCH FROM BUS 270667 TO BUS 270927 CKT 1   /*BLUE ISL ;RT 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 270769 TO BUS 270667 CKT 1   /*GOODINGS ;2R 345.0 - BLUE ISL ;RT 345.0
END
CONTINGENCY 'COMED_P4_112-45-BT4-5___SRT-A'
 TRIP BRANCH FROM BUS 270666 TO BUS 270664 CKT 1   /*BLUE ISL ;BT 345.0 - BLUE ISL ; B 345.0
 TRIP BRANCH FROM BUS 270666 TO BUS 270926 CKT 1   /*BLUE ISL ;BT 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 270770 TO BUS 270666 CKT 1   /*GOODINGS ;4B 345.0 - BLUE ISL ;BT 345.0
 TRIP BRANCH FROM BUS 270852 TO BUS 270704 CKT 1   /*PONTIAC  ; B 345.0 - LORETTO  ; B 345.0
END
CONTINGENCY 'COMED_P4_112-65-BT5-6___SRT-A'
 TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1   /*WILTON   ;   765.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT2-3___SRT-A'
 TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1   /*WILTON   ;   765.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
243206 to 246999 ckt 1
255113 to 243219 ckt 1
960680 to 243229 ckt 1
274750 to 255112 ckt 1
270728 to 274750 ckt 1
270770 to 270766 ckt 1
274804 to 960680 ckt 1
270926 to 275232 ckt 1
270927 to 275233 ckt 1
275232 to 270644 ckt 1
275233 to 270644 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1CE
AB1-122 TAP2-DRESDEN ; B 345.0 kV Ckt 1 line
COMED_P1-2_345-L0304__R-S_SRT-A
OPAC113.07 %1479.0B1672.377.59
GD1CE
NEVADA ; R-GOODINGS ; R 345.0 kV Ckt 1 line
COMED_P1-2_345-L0304__R-S_SRT-A
OPAC102.5 %1290.0B1322.226.82

Details for AB1-122 TAP2-DRESDEN ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0304__R-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AB1-122 TAP2-DRESDEN ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0304__R-S_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.07 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1672.37
MW Contribution:7.59
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
AB1-122 TAP2-DRESDEN ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0304__R-S_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.1 %
Rating:1479.0 MVA
Rating Type:B
MVA to Mitigate:1672.77
MW Contribution:7.59
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
290021O50 E
50/50
98.40298.402
918052AA1-018 E OP
50/50
21.23221.232
958481AF2-142 C
50/50
14.64314.643
958482AF2-142 E
50/50
9.7629.762
958491AF2-143 C
50/50
19.81919.819
958492AF2-143 E
50/50
13.21313.213
959351AF2-226 C
50/50
3.0353.035
959352AF2-226 E
50/50
4.5534.553
960281AF2-319 C
50/50
3.0353.035
960282AF2-319 E
50/50
4.5534.553
274677POWERTON ;5U
50/50
44.85744.857
274678POWERTON ;6U
50/50
45.05845.058
274861TOP CROP ;1U
50/50
0.4560.456
274862TOP CROP ;2U
50/50
0.8710.871
274879MINONK ;1U
50/50
4.0194.019
293644O22 E1
50/50
17.43817.438
293645O22 E2
50/50
19.97319.973
938851AE1-113 C
50/50
40.59140.591
938852AE1-113 E
50/50
143.912143.912
934101AD2-000 1
50/50
-0.6-0.6
934111AD2-000 2
50/50
43.34743.347
270839OTTER CRK; R
50/50
0.5180.518
276658AB1-122 CT1
50/50
-1.212-1.212
276660AB1-122 CT2
50/50
87.58387.583
936291AD2-038 C
50/50
0.8880.888
936292AD2-038 E
50/50
27.21827.218
942421AE2-255 C
50/50
15.37515.375
942422AE2-255 E
50/50
46.12646.126
942651AE2-281 C
50/50
1.5411.541
942652AE2-281 E
50/50
9.4699.469
939321AE1-163 C
50/50
10.7910.79
939322AE1-163 E
50/50
66.28466.284
G-007PJM->LTFIMP_G-007
CMTX_NF
0.5180.518
NYPJM->LTFIMP_NY
CLTF
0.2720.272
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
1.4471.447
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.3120.312
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1910.191
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.8811.881
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.2910.291
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.9110.911
O66PJM->LTFIMP_O-066
CMTX_NF
3.3183.318
MDUPJM->LTFIMP_MDU
CLTF
0.1090.109
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.7550.755
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.4010.401

Details for NEVADA ; R-GOODINGS ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0304__R-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
NEVADA ; R-GOODINGS ; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0304__R-S_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.5 %
Rating:1290.0 MVA
Rating Type:B
MVA to Mitigate:1322.22
MW Contribution:6.82
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
290021O50 E
50/50
29.90829.908
918052AA1-018 E OP
50/50
88.84788.847
958481AF2-142 C
50/50
61.27461.274
958482AF2-142 E
50/50
40.84940.849
958491AF2-143 C
50/50
51.53251.532
958492AF2-143 E
50/50
34.35534.355
959351AF2-226 C
50/50
2.7262.726
959352AF2-226 E
50/50
4.0894.089
960281AF2-319 C
50/50
2.7262.726
960282AF2-319 E
50/50
4.0894.089
274677POWERTON ;5U
50/50
39.639.6
274678POWERTON ;6U
50/50
39.539.5
274861TOP CROP ;1U
50/50
0.410.41
274862TOP CROP ;2U
50/50
0.7820.782
274879MINONK ;1U
50/50
1.2221.222
293644O22 E1
50/50
15.66215.662
293645O22 E2
50/50
17.93917.939
938851AE1-113 C
50/50
12.33712.337
938852AE1-113 E
50/50
43.7443.74
270839OTTER CRK; R
50/50
2.1692.169
936291AD2-038 C
50/50
2.3082.308
936292AD2-038 E
50/50
70.77170.771
942421AE2-255 C
50/50
4.6734.673
942422AE2-255 E
50/50
14.01914.019
942651AE2-281 C
50/50
4.0084.008
942652AE2-281 E
50/50
24.62124.621
939321AE1-163 C
50/50
28.05728.057
939322AE1-163 E
50/50
172.347172.347
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3560.356
NYPJM->LTFIMP_NY
CLTF
0.1880.188
WECLTFEXP_WEC->PJM
CLTF
0.0110.011
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.5020.502
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1820.182
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1090.109
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.5680.568
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1810.181
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.560.56
O66PJM->LTFIMP_O-066
CMTX_NF
2.2852.285
MDUPJM->LTFIMP_MDU
CLTF
0.0040.004
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.2080.208
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.2390.239
CONTINGENCY 'COMED_P1-2_345-L0304__R-S_SRT-A'
 TRIP BRANCH FROM BUS 270855 TO BUS 349662 CKT 1   /*POWERTON ; R 345.0 - 7TAZEWELL    345.0
END
276659 to 270716 ckt 1
270827 to 270769 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Base Case
OPAC112.67 %1075.0A1211.174.52
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Base Case
OPAC114.94 %1091.0A1254.035.42
GD1CE
NEVADA ; R-GOODINGS ;2R 345.0 kV Ckt 1 line
COMED_P1-2_345-L0304__R-S_SRT-A
OPAC102.29 %1290.0B1319.66.81

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.67 %
Rating:1075.0 MVA
Rating Type:A
MVA to Mitigate:1211.17
MW Contribution:4.52
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.69647058823529421.442
962012AG1-044 E
Adder
0.04117647058823530.035
962781AG1-127 C
Adder
4.4894117647058823.816
962782AG1-127 E
Adder
2.9882352941176472.54
966091AG1-478 C
Adder
1.46941176470588241.249
966092AG1-478 E
Adder
0.36941176470588240.314
966441AG1-513 C
Adder
0.32705882352941180.278
966442AG1-513 E
Adder
0.48941176470588230.416
290021O50 E
Adder
13.1552941176470611.182
290051GSG-6; E
Adder
6.7482352941176475.736
295109WESTBROOK E
Adder
3.61294117647058853.071
295111SUBLETTE E
Adder
1.75647058823529421.493
910542X3-005 E
Adder
0.71294117647058820.606
918052AA1-018 E OP
Adder
11.3482352941176489.646
933911AD1-013 C
Adder
1.18705882352941171.009
933912AD1-013 E
Adder
1.89647058823529441.612
934722AD1-100 E
Adder
60.7764705882352951.66
937002AD2-134 E
Adder
6.5247058823529425.546
937312AD2-172 E
Adder
2.20823529411764731.877
958481AF2-142 C
Adder
7.8258823529411776.652
958482AF2-142 E
Adder
5.21764705882352954.435
958491AF2-143 C
Adder
7.5847058823529416.447
958492AF2-143 E
Adder
5.0564705882352944.298
958912AF2-182 E
Adder
22.26470588235294218.925
959081AF2-199 C
Adder
4.6141176470588243.922
959082AF2-199 E
Adder
2.3070588235294121.961
959351AF2-226 C
Adder
1.80588235294117651.535
959352AF2-226 E
Adder
2.70941176470588242.303
960281AF2-319 C
Adder
1.80588235294117651.535
960282AF2-319 E
Adder
2.70941176470588242.303
960582AF2-349 E
Adder
23.60470588235294220.064
960751AF2-366 C
Adder
4.4776470588235293.806
960752AF2-366 E
Adder
2.98470588235294132.537
274675JOLIET 29;7U
Adder
49.9447058823529542.453
274676JOLIET 29;8U
Adder
49.9529411764705942.46
274682WAUKEGAN ;7U
Adder
27.29294117647059223.199
274683WAUKEGAN ;8U
Adder
29.42352941176470825.01
274687WILL CNTY;4U
Adder
48.5929411764705941.304
274724RIVER EC ;11
50/50
3.9023.902
274788SE CHICAG;5U
50/50
5.5385.538
274789SE CHICAG;6U
50/50
5.5385.538
274790SE CHICAG;7U
50/50
5.5385.538
274791SE CHICAG;8U
50/50
5.5385.538
274792SE CHICAG;9U
50/50
5.4655.465
274793SE CHICAG;0U
50/50
5.4655.465
274794SE CHICAG;1U
Adder
5.464705882352944.645
274795SE CHICAG;2U
Adder
5.464705882352944.645
274859EASYR;U1 E
Adder
7.82352941176470656.65
274860EASYR;U2 E
Adder
7.82352941176470656.65
276591L-013 2
Adder
2.36235294117647052.008
293061N-015 E
Adder
9.8294117647058838.355
293644O22 E1
Adder
10.3776470588235298.821
293645O22 E2
Adder
11.88588235294117710.103
293715O-029 E
Adder
6.3811764705882365.424
293716O-029 E
Adder
2.70823529411764732.302
294392P-010 E
Adder
12.48352941176470710.611
294763P-046 E
Adder
6.13764705882352955.217
933411AC2-154 C
Adder
1.90000000000000011.615
933412AC2-154 E
Adder
3.09999999999999962.635
939061AE1-134 2
Adder
0.89294117647058820.759
940502AE2-035 E
Adder
2.20823529411764731.877
957331AF2-027 C
Adder
1.64941176470588241.402
957332AF2-027 E
Adder
2.4741176470588242.103
957471AF2-041 C
Adder
13.84352941176470611.767
957472AF2-041 E
Adder
6.9211764705882355.883
274674JOLIET 9 ;6U
Adder
25.73058823529411821.871
274890CAYUG;1U E
Adder
9.1035294117647067.738
274891CAYUG;2U E
Adder
9.1035294117647067.738
938851AE1-113 C
Adder
5.4270588235294124.613
938852AE1-113 E
Adder
19.2416.354
934101AD2-000 1
Adder
3.68941176470588243.136
934111AD2-000 2
Adder
4.077647058823533.466
275149KELLYCK ;1E
Adder
14.00117647058823611.901
293516O-009 E
Adder
12.33882352941176410.488
293519PILOT HIL;1E
Adder
14.00117647058823611.901
290108LEEDK;1U E
Adder
15.41176470588235313.1
916221Z1-073 E
Adder
4.75529411764705844.042
926821AC1-168 C
Adder
0.75294117647058820.64
926822AC1-168 E
Adder
5.0564705882352944.298
936292AD2-038 E
Adder
10.4164705882352948.854
936371AD2-047 C
Adder
3.40000000000000042.89
936372AD2-047 E
Adder
16.614.11
936461AD2-060 C
Adder
2.01.7
936511AD2-066 C
Adder
5.6788235294117654.827
936512AD2-066 E
Adder
3.78588235294117673.218
942421AE2-255 C
Adder
2.0552941176470591.747
942422AE2-255 E
Adder
6.1670588235294125.242
942651AE2-281 C
Adder
0.58941176470588240.501
942652AE2-281 E
Adder
3.6235294117647063.08
943121AE2-341 C
Adder
7.99529411764705966.796
943122AE2-341 E
Adder
3.9258823529411773.337
943591AF1-030 C
Adder
5.3176470588235294.52
943592AF1-030 E
Adder
2.6305882352941182.236
959091AF2-200 C
Adder
9.2294117647058827.845
959092AF2-200 E
Adder
6.1529411764705895.23
960591AF2-350 C
Adder
6.05.1
960592AF2-350 E
Adder
4.03.4
961501AF2-441 C
Adder
10.915294117647069.278
961502AF2-441 E
Adder
16.37411764705882413.918
938861AE1-114 C
Adder
2.562.176
938862AE1-114 E
Adder
8.7329411764705887.423
939321AE1-163 C
Adder
4.1294117647058823.51
939322AE1-163 E
Adder
25.36588235294117821.561
939351AE1-166 C
Adder
6.7717647058823545.756
939352AE1-166 E
Adder
6.2517647058823535.314
939401AE1-172 C
Adder
3.55294117647058853.02
939402AE1-172 E
Adder
16.63411764705882214.139
946152AF1-280 E
Adder
14.84352941176470812.617
946671AF1-331 C
Adder
1.54235294117647051.311
962691AG1-118 C
Adder
14.20823529411764812.077
962692AG1-118 E
Adder
9.4717647058823548.051
941551AE2-152 C
Adder
7.8141176470588246.642
941552AE2-152 E
Adder
5.2094117647058834.428
957371AF2-031 C
50/50
1.1831.183
957372AF2-031 E
50/50
1.7751.775
958011AF2-095 C
Adder
8.6411764705882357.345
958012AF2-095 E
Adder
5.764.896
920272AA2-123 E
Adder
1.87058823529411791.59
276170Z1-108 E
Adder
1.9070588235294121.621
276626AG1-044 E
Adder
0.0482352941176470640.041
276675AE2-062 E
Adder
0.107058823529411760.091
CBM West 1LTFEXP_CBM-W1->PJM
CBM
75.73675.736
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.85611.856
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3871.387
NYPJM->LTFIMP_NY
CLTF
0.7460.746
WECLTFEXP_WEC->PJM
CLTF
2.5782.578
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2990.299
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1480.148
TVALTFEXP_TVA->PJM
CLTF
1.1741.174
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.2290.229
MECLTFEXP_MEC->PJM
CLTF
8.7698.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.6110.611
LAGNLTFEXP_LAGN->PJM
CLTF
2.6762.676
SIGELTFEXP_SIGE->PJM
CLTF
0.0530.053
O66PJM->LTFIMP_O-066
CMTX_NF
8.8988.898
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.4540.454

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:114.94 %
Rating:1091.0 MVA
Rating Type:A
MVA to Mitigate:1254.03
MW Contribution:5.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.76941176470588251.504
962012AG1-044 E
Adder
0.0423529411764705860.036
962781AG1-127 C
Adder
4.6976470588235293.993
962782AG1-127 E
Adder
3.12588235294117662.657
966091AG1-478 C
Adder
1.3482352941176471.146
966092AG1-478 E
Adder
0.33882352941176470.288
966441AG1-513 C
Adder
0.34235294117647060.291
966442AG1-513 E
Adder
0.51294117647058820.436
290021O50 E
Adder
13.8752941176470611.794
290051GSG-6; E
Adder
7.045.984
295109WESTBROOK E
Adder
3.76941176470588253.204
295111SUBLETTE E
Adder
1.8317647058823531.557
918052AA1-018 E OP
Adder
10.6611764705882349.062
933911AD1-013 C
Adder
1.23882352941176471.053
933912AD1-013 E
Adder
1.97882352941176461.682
934722AD1-100 E
Adder
60.5729411764705951.487
937002AD2-134 E
Adder
6.8070588235294115.786
937312AD2-172 E
Adder
2.30000000000000031.955
958481AF2-142 C
Adder
7.3529411764705896.25
958482AF2-142 E
Adder
4.90117647058823554.166
958491AF2-143 C
Adder
7.3411764705882366.24
958492AF2-143 E
Adder
4.8941176470588244.16
958912AF2-182 E
Adder
23.1219.652
959081AF2-199 C
Adder
4.8305882352941174.106
959082AF2-199 E
Adder
2.41529411764705862.053
959351AF2-226 C
50/50
2.1682.168
959352AF2-226 E
50/50
3.2523.252
960281AF2-319 C
50/50
2.1682.168
960282AF2-319 E
50/50
3.2523.252
960582AF2-349 E
Adder
24.68117647058823420.979
960751AF2-366 C
Adder
4.6847058823529423.982
960752AF2-366 E
Adder
3.12235294117647082.654
274654BRAIDWOOD;1U
50/50
19.28319.283
274675JOLIET 29;7U
Adder
52.87529411764706644.944
274676JOLIET 29;8U
Adder
52.9223529411764844.984
274682WAUKEGAN ;7U
Adder
28.6329411764705924.338
274683WAUKEGAN ;8U
Adder
30.8552941176470626.227
274687WILL CNTY;4U
Adder
50.79647058823529443.177
274752CRETE EC ;2U
50/50
5.7635.763
274753CRETE EC ;3U
50/50
5.7635.763
274754CRETE EC ;4U
50/50
5.7635.763
274859EASYR;U1 E
Adder
8.1305882352941186.911
274860EASYR;U2 E
Adder
8.1305882352941186.911
274861TOP CROP ;1U
50/50
0.3250.325
274862TOP CROP ;2U
50/50
0.620.62
276591L-013 2
Adder
2.4788235294117652.107
293061N-015 E
Adder
10.669.061
293644O22 E1
50/50
12.45512.455
293645O22 E2
50/50
14.26614.266
293715O-029 E
Adder
6.58705882352941255.599
293716O-029 E
Adder
3.6117647058823533.07
293717O-029 E
Adder
3.32000000000000032.822
293771O-035 E
Adder
4.6694117647058823.969
294392P-010 E
Adder
13.53764705882352911.507
294763P-046 E
Adder
6.3917647058823535.433
933411AC2-154 C
Adder
1.4682352941176471.248
933412AC2-154 E
Adder
2.3952941176470592.036
939061AE1-134 2
Adder
0.92588235294117650.787
940502AE2-035 E
Adder
2.30000000000000031.955
957331AF2-027 C
Adder
1.7282352941176471.469
957332AF2-027 E
Adder
2.5917647058823532.203
957471AF2-041 C
Adder
14.49058823529411912.317
957472AF2-041 E
Adder
7.24470588235294166.158
274674JOLIET 9 ;6U
Adder
23.3929411764705919.884
274890CAYUG;1U E
Adder
8.9564705882352957.613
274891CAYUG;2U E
Adder
8.9564705882352957.613
938851AE1-113 C
Adder
5.7235294117647064.865
938852AE1-113 E
Adder
20.2929411764705917.249
934101AD2-000 1
Adder
3.8435294117647063.267
934111AD2-000 2
Adder
4.3529411764705893.7
275149KELLYCK ;1E
Adder
10.8188235294117649.196
293516O-009 E
Adder
12.7376470588235310.827
293519PILOT HIL;1E
Adder
10.8188235294117649.196
916212CRESCENT ;1U
Adder
2.71999999999999982.312
290108LEEDK;1U E
Adder
16.10823529411764813.692
916221Z1-073 E
Adder
4.9611764705882354.217
926821AC1-168 C
Adder
0.77647058823529410.66
926822AC1-168 E
Adder
5.2117647058823534.43
936292AD2-038 E
Adder
10.0823529411764728.57
936371AD2-047 C
Adder
2.6270588235294122.233
936372AD2-047 E
Adder
12.82823529411764710.904
936461AD2-060 C
Adder
1.54588235294117651.314
936511AD2-066 C
Adder
5.7423529411764714.881
936512AD2-066 E
Adder
3.8282352941176473.254
942421AE2-255 C
Adder
2.16823529411764731.843
942422AE2-255 E
Adder
6.5047058823529415.529
942651AE2-281 C
Adder
0.57058823529411760.485
942652AE2-281 E
Adder
3.50705882352941162.981
943121AE2-341 C
Adder
8.397647058823537.138
943122AE2-341 E
Adder
4.1235294117647053.505
943591AF1-030 C
Adder
5.5847058823529414.747
943592AF1-030 E
Adder
2.7635294117647062.349
959091AF2-200 C
Adder
9.668.211
959092AF2-200 E
Adder
6.445.474
960591AF2-350 C
Adder
4.6364705882352943.941
960592AF2-350 E
Adder
3.09058823529411742.627
938861AE1-114 C
Adder
2.66117647058823532.262
938862AE1-114 E
Adder
9.087.718
939321AE1-163 C
Adder
3.99647058823529383.397
939322AE1-163 E
Adder
24.55176470588235220.869
939351AE1-166 C
Adder
6.7494117647058835.737
939352AE1-166 E
Adder
6.2305882352941185.296
939401AE1-172 C
Adder
3.50941176470588272.983
939402AE1-172 E
Adder
16.43058823529411713.966
946152AF1-280 E
Adder
15.4129411764705913.101
946671AF1-331 C
Adder
1.60941176470588251.368
962691AG1-118 C
Adder
14.86823529411764812.638
962692AG1-118 E
Adder
9.912941176470598.426
941551AE2-152 C
Adder
7.7882352941176486.62
941552AE2-152 E
Adder
5.19176470588235354.413
958011AF2-095 C
Adder
6.6764705882352945.675
958012AF2-095 E
Adder
4.4505882352941173.783
274751CRETE EC ;1U
50/50
5.7635.763
920272AA2-123 E
Adder
1.95882352941176491.665
276170Z1-108 E
Adder
2.00117647058823561.701
276626AG1-044 E
Adder
0.0494117647058823560.042
276675AE2-062 E
Adder
0.103529411764705880.088
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.81249.812
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.3588.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.4391.439
NYPJM->LTFIMP_NY
CLTF
0.7740.774
WECLTFEXP_WEC->PJM
CLTF
2.6882.688
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.3940.394
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2110.211
TVALTFEXP_TVA->PJM
CLTF
0.660.66
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5040.504
MECLTFEXP_MEC->PJM
CLTF
8.7288.728
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.491.49
LAGNLTFEXP_LAGN->PJM
CLTF
2.092.09
O66PJM->LTFIMP_O-066
CMTX_NF
9.239.23
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.5680.568

Details for NEVADA ; R-GOODINGS ;2R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0304__R-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
NEVADA ; R-GOODINGS ;2R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0304__R-S_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.29 %
Rating:1290.0 MVA
Rating Type:B
MVA to Mitigate:1319.6
MW Contribution:6.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
290021O50 E
50/50
29.87529.875
918052AA1-018 E OP
50/50
88.77888.778
958481AF2-142 C
50/50
61.22761.227
958482AF2-142 E
50/50
40.81840.818
958491AF2-143 C
50/50
51.49251.492
958492AF2-143 E
50/50
34.32834.328
959351AF2-226 C
50/50
2.7252.725
959352AF2-226 E
50/50
4.0884.088
960281AF2-319 C
50/50
2.7252.725
960282AF2-319 E
50/50
4.0884.088
274677POWERTON ;5U
50/50
39.43239.432
274678POWERTON ;6U
50/50
39.33339.333
274861TOP CROP ;1U
50/50
0.4080.408
274862TOP CROP ;2U
50/50
0.7790.779
274879MINONK ;1U
50/50
1.2161.216
293644O22 E1
50/50
15.65715.657
293645O22 E2
50/50
17.93217.932
938851AE1-113 C
50/50
12.32312.323
938852AE1-113 E
50/50
43.69243.692
270839OTTER CRK; R
50/50
2.162.16
936291AD2-038 C
50/50
2.2982.298
936292AD2-038 E
50/50
70.71670.716
942421AE2-255 C
50/50
4.6684.668
942422AE2-255 E
50/50
14.00414.004
942651AE2-281 C
50/50
4.0054.005
942652AE2-281 E
50/50
24.60224.602
939321AE1-163 C
50/50
28.03528.035
939322AE1-163 E
50/50
172.214172.214
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3540.354
NYPJM->LTFIMP_NY
CLTF
0.1870.187
WECLTFEXP_WEC->PJM
CLTF
0.0080.008
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.5030.503
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1810.181
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1090.109
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.5720.572
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1790.179
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.5540.554
O66PJM->LTFIMP_O-066
CMTX_NF
2.2672.267
MDUPJM->LTFIMP_MDU
CLTF
0.0040.004
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.2110.211
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.2370.237
CONTINGENCY 'COMED_P1-2_345-L0304__R-S_SRT-A'
 TRIP BRANCH FROM BUS 270855 TO BUS 349662 CKT 1   /*POWERTON ; R 345.0 - 7TAZEWELL    345.0
END
255113 to 243219 ckt 1
274750 to 255112 ckt 1
270827 to 270769 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AF2-319 was evaluated as a 50.0 MW injection and 50.0 MW withdrawal in the ComEd area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AMIL/CE
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A
TowerAC101.66 %1489.0B1513.7336.34

Details for POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AMIL/CE
Facility Description:
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.66 %
Rating:1489.0 MVA
Rating Type:B
MVA to Mitigate:1513.73
MW Contribution:36.34
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274861TOP CROP ;1U
50/50
3.3433.343
274862TOP CROP ;2U
50/50
6.3786.378
274879MINONK ;1U
50/50
4.3594.359
290021O50 E
50/50
17.43717.437
293644O22 E1
50/50
20.87820.878
293645O22 E2
50/50
23.91223.912
918052AA1-018 E OP
50/50
23.71223.712
959351AF2-226 C
50/50
14.53614.536
959352AF2-226 E
50/50
21.80421.804
960281AF2-319 C
50/50
14.53614.536
960282AF2-319 E
50/50
21.80421.804
938851AE1-113 C
50/50
23.01723.017
938852AE1-113 E
50/50
81.60481.604
942651AE2-281 C
50/50
4.074.07
942652AE2-281 E
50/50
25.00125.001
270839OTTER CRK; R
50/50
3.5433.543
939321AE1-163 C
50/50
28.48928.489
939322AE1-163 E
50/50
175.006175.006
942421AE2-255 C
50/50
8.7188.718
942422AE2-255 E
50/50
26.15526.155
CONTINGENCY 'COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S_SRT-A'
 TRIP BRANCH FROM BUS 270790 TO BUS 270770 CKT 1   /*KATYDID  ; B 345.0 - GOODINGS ; B 345.0
 TRIP BRANCH FROM BUS 270827 TO BUS 270769 CKT 1   /*NEVADA   ; R 345.0 - GOODINGS ; R 345.0
END
270855 to 349662 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleDC101.06 %1204.0B1216.722.67
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC126.34 %1075.0B1358.127.05
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleDC121.52 %1075.0B1306.397.05
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC119.42 %1075.0B1283.786.85
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC124.77 %971.0B1211.564.91
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC124.6 %971.0B1209.94.91
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC110.59 %971.0B1073.814.91
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC110.59 %971.0B1073.84.91
GD1CE/NIPS
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC100.96 %1441.0B1454.815.46
GD1CE/NIPS
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC100.81 %1441.0B1452.615.46
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC116.58 %1399.0B1630.97.13
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC116.39 %1399.0B1628.287.13
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC105.23 %1399.0B1472.147.1
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC104.33 %1399.0B1459.577.13
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Base Case
SingleAC102.15 %1091.0A1114.475.26
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC116.61 %1399.0B1631.337.13
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC116.42 %1399.0B1628.717.13
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC105.23 %1399.0B1472.217.1
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC104.33 %1399.0B1459.637.13
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Base Case
SingleAC102.15 %1091.0A1114.435.26
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC121.46 %970.0STE1178.144.91
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC121.2 %970.0STE1175.664.91
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC107.66 %970.0STE1044.284.91
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC107.66 %970.0STE1044.264.91

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:DC
Final Cycle Loading:101.06 %
Rating:1204.0 MVA
Rating Type:B
MVA to Mitigate:1216.72
MW Contribution:2.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
24725505WLD G2 C
80/20
0.2270.227
24385905FR-11G C
80/20
0.3740.374
24386205FR-12G C
80/20
0.1820.182
24386405FR-21G C
80/20
0.1890.189
24386605FR-22G C
80/20
0.1890.189
24387005FR-3G C
80/20
0.1820.182
24387305FR-4G C
80/20
0.4240.424
24790105FR-12G E
80/20
1.2271.227
24790205FR-21G E
80/20
1.3041.304
24790405FR-3G E
80/20
2.432.43
24790505FR-4G E
80/20
1.9261.926
24790605MDL-1G E
80/20
2.5232.523
24790705MDL-2G E
80/20
1.2151.215
24791205MDL-3G E
80/20
1.2141.214
24791305MDL-4G E
80/20
1.2641.264
24795805WLD G2 E
80/20
3.0893.089
274847GR RIDGE ;BU
80/20
0.3660.366
274848CAMPGROVE;RU
80/20
0.1730.173
274849CRESCENT ;1U
80/20
0.1290.129
274851PROVIDENC;RU
80/20
0.1370.137
274853TWINGROVE;U1
80/20
0.4790.479
274854TWINGROVE;U2
80/20
0.4920.492
274861TOP CROP ;1U
80/20
0.2450.245
274862TOP CROP ;2U
80/20
0.4680.468
274863CAYUGA RI;1U
80/20
0.3050.305
274864CAYUGA RI;2U
80/20
0.3050.305
274871GR RIDGE ;2U
80/20
0.1360.136
274877BISHOP HL;1U
80/20
0.2660.266
274878BISHOP HL;2U
80/20
0.2660.266
274879MINONK ;1U
80/20
0.5330.533
274880RADFORD R;1U
80/20
0.6340.634
274887PILOT HIL;1U
80/20
0.4670.467
274888KELLY CRK;1U
80/20
0.4670.467
276615W2-048 GEN
80/20
0.9020.902
276621X2-022 GEN
80/20
2.5692.569
290021O50 E
80/20
2.1322.132
290261S-027 E
80/20
2.2452.245
290265S-028 E
80/20
2.2322.232
293061N-015 E
80/20
1.6031.603
293644O22 E1
80/20
1.5311.531
293645O22 E2
80/20
1.7541.754
293771O-035 E
80/20
0.8490.849
294392P-010 E
80/20
2.0362.036
294401BSHIL;1U E
80/20
1.0641.064
294410BSHIL;2U E
80/20
1.0641.064
917502Z2-087 E
80/20
2.3892.389
918052AA1-018 E OP
80/20
1.7391.739
925581AC1-033 C
80/20
0.2790.279
925582AC1-033 E
80/20
1.8681.868
934721AD1-100 C
80/20
1.9291.929
934722AD1-100 E
80/20
30.0130.01
942111AE2-223 C
80/20
0.8570.857
942112AE2-223 E
80/20
5.7335.733
959351AF2-226 C
80/20
1.0661.066
959352AF2-226 E
80/20
1.5991.599
959611AF2-252 C
80/20
1.1011.101
959612AF2-252 E
80/20
1.6511.651
960281AF2-319 C
80/20
1.0661.066
960282AF2-319 E
80/20
1.5991.599
960611AF2-352 C
80/20
1.1011.101
960612AF2-352 E
80/20
1.6511.651
960971AF2-388 C
80/20
1.8951.895
960972AF2-388 E
80/20
8.8738.873
965651AG1-433 C
80/20
0.9480.948
965652AG1-433 E
80/20
4.4364.436
966091AG1-478 C
80/20
0.2130.213
966092AG1-478 E
80/20
0.320.32
966842AG1-555 E
80/20
5.1515.151
24344305RKG2
80/20
49.81949.819
24379505HDWTR1G C
80/20
0.5180.518
24699105WLD G1 C
80/20
0.2340.234
24753605BLUFF P WF
80/20
0.4330.433
247543V3-007 C
80/20
0.5180.518
247929S-071 E
80/20
1.7341.734
247935V3-007 E
80/20
3.4643.464
24796305HDWTR1G E
80/20
3.4643.464
274674JOLIET 9 ;6U
80/20
6.7426.742
274675JOLIET 29;7U
80/20
17.57617.576
274676JOLIET 29;8U
80/20
17.57617.576
274687WILL CNTY;4U
80/20
16.29816.298
943771AF1-045 C
80/20
3.7493.749
943772AF1-045 E
80/20
2.5032.503
945382AF1-203 E
80/20
1.0781.078
961761AG1-017 C
80/20
0.1560.156
961762AG1-017 E
80/20
0.7170.717
24690905MDL-1G C
80/20
0.3710.371
24691005MDL-2G C
80/20
0.2180.218
24697605MDL-3G C
80/20
0.2190.219
24697905MDL-4G C
80/20
0.1690.169
274890CAYUG;1U E
80/20
1.6261.626
274891CAYUG;2U E
80/20
1.6261.626
925771AC1-053 C
80/20
0.5780.578
925772AC1-053 E
80/20
3.8683.868
938851AE1-113 C
80/20
2.8142.814
938852AE1-113 E
80/20
9.9789.978
24790005FR-11G E
80/20
1.2461.246
24790305FR-22G E
80/20
1.2531.253
939401AE1-172 C
80/20
1.941.94
939402AE1-172 E
80/20
9.0819.081
942651AE2-281 C
80/20
0.2980.298
942652AE2-281 E
80/20
1.8341.834
939781AE1-209 C
80/20
0.7710.771
939782AE1-209 E
80/20
5.1615.161
957382AF2-032 E
80/20
0.1110.111
964782AG1-341 E
80/20
5.6895.689
24755605MDL-5G
80/20
0.2890.289
247943T-127 E
80/20
1.1431.143
251828CLNTESP1
80/20
1.0531.053
25196808ZIMRHP
80/20
48.79548.795
270180AB1-006 W1
80/20
0.3260.326
270181AB1-006 W2
80/20
0.0470.047
270681BRIGHTSTK; R
80/20
0.3570.357
270839OTTER CRK; R
80/20
0.260.26
275149KELLYCK ;1E
80/20
1.8691.869
276174W4-005 E
80/20
3.6233.623
276645AC1-214 C1
80/20
0.1130.113
276646AC1-214 C2
80/20
0.1130.113
276655AB2-047 C1
80/20
0.2230.223
276656AB2-047 C2
80/20
0.2230.223
276668AB2-070 C
80/20
0.3610.361
276675AE2-062 E
80/20
0.0530.053
293519PILOT HIL;1E
80/20
1.8691.869
916212CRESCENT ;1U
80/20
0.5970.597
924048AB2-047 E1
80/20
1.4811.481
924049AB2-047 E2
80/20
1.5041.504
924266AB2-070 E
80/20
2.1882.188
926821AC1-168 C
80/20
0.4360.436
926822AC1-168 E
80/20
2.9272.927
927208AC1-214 E1
80/20
0.4030.403
927209AC1-214 E2
80/20
0.4030.403
930041AB1-006 E1
80/20
2.1822.182
930042AB1-006 E2
80/20
0.3120.312
935141AD1-148 C
80/20
0.8070.807
936371AD2-047 C
80/20
1.4531.453
936372AD2-047 E
80/20
7.0937.093
939321AE1-163 C
80/20
2.092.09
939322AE1-163 E
80/20
12.83712.837
939791AE1-210 C
80/20
0.7710.771
939792AE1-210 E
80/20
5.1615.161
941721AE2-172 C
80/20
2.7562.756
942421AE2-255 C
80/20
1.0661.066
942422AE2-255 E
80/20
3.1983.198
942601AE2-276 C
80/20
3.1363.136
944221AF1-090 C
80/20
1.5711.571
944222AF1-090 E
80/20
7.3577.357
944242AF1-092 E
80/20
6.476.47
944532AF1-118 E
80/20
22.09922.099
944542AF1-119 E
80/20
13.12313.123
945371AF1-202 C
80/20
1.871.87
945372AF1-202 E
80/20
9.1319.131
945391AF1-204 C
80/20
3.1723.172
945392AF1-204 E
80/20
9.5179.517
957372AF2-031 E
80/20
0.6380.638
957842AF2-078 E
80/20
1.1371.137
958861AF2-177 C
80/20
1.4161.416
958862AF2-177 E
80/20
9.4749.474
960261AF2-317 C
80/20
0.3490.349
961161AF2-407 C
80/20
22.20322.203
961171AF2-408 C
80/20
5.9915.991
961501AF2-441 C
80/20
4.2584.258
961502AF2-441 E
80/20
6.3886.388
963581AG1-207 C
80/20
6.7246.724
963841AG1-237 C
80/20
1.2281.228
963842AG1-237 E
80/20
8.2188.218
964611AG1-324 C
80/20
0.3140.314
964612AG1-324 E
80/20
0.4710.471
965331AG1-398 C
80/20
0.1630.163
965462AG1-414 E
80/20
1.6981.698
990901L-005 E
80/20
1.5991.599
270201AC2-176 GEN
80/20
0.2920.292
933596AC2-176 E
80/20
1.9521.952
25016408BKJDB1
80/20
0.2670.267
251827WILLYESP
80/20
0.6880.688
965913AG1-460 BT
80/20
0.0060.006

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.34 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1358.12
MW Contribution:7.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.9610.961
274848CAMPGROVE;RU
80/20
0.3760.376
274849CRESCENT ;1U
80/20
0.2860.286
274850MENDOTA H;RU
80/20
0.4720.472
274851PROVIDENC;RU
80/20
0.3040.304
274853TWINGROVE;U1
80/20
0.8810.881
274854TWINGROVE;U2
80/20
0.9070.907
274855GSG-6 ;RU
80/20
0.7180.718
274856ECOGROVE ;U1
80/20
0.620.62
274857BIG SKY ;U1
80/20
0.4760.476
274858BIG SKY ;U2
80/20
0.4760.476
274859EASYR;U1 E
80/20
3.283.28
274860EASYR;U2 E
80/20
3.283.28
274861TOP CROP ;1U
80/20
0.6480.648
274862TOP CROP ;2U
80/20
1.2361.236
274863CAYUGA RI;1U
80/20
0.7080.708
274864CAYUGA RI;2U
80/20
0.7080.708
274871GR RIDGE ;2U
80/20
0.3580.358
274872LEE DEKAL;1U
80/20
1.3351.335
274877BISHOP HL;1U
80/20
0.5860.586
274878BISHOP HL;2U
80/20
0.5860.586
274879MINONK ;1U
80/20
1.3331.333
274880RADFORD R;1U
80/20
0.9440.944
274887PILOT HIL;1U
80/20
1.3431.343
274888KELLY CRK;1U
80/20
1.3431.343
276156O-029 C
80/20
0.3360.336
276157O-029 C
80/20
0.6060.606
276158O-029 C
80/20
0.6060.606
276615W2-048 GEN
80/20
1.2811.281
276621X2-022 GEN
80/20
3.6453.645
290021O50 E
80/20
5.335.33
290051GSG-6; E
80/20
2.8722.872
290108LEEDK;1U E
80/20
6.5926.592
290261S-027 E
80/20
4.1334.133
290265S-028 E
80/20
4.1084.108
293061N-015 E
80/20
4.214.21
293644O22 E1
80/20
4.0484.048
293645O22 E2
80/20
4.6364.636
293715O-029 E
80/20
2.6572.657
293716O-029 E
80/20
1.4571.457
293717O-029 E
80/20
1.3391.339
293771O-035 E
80/20
1.8811.881
294392P-010 E
80/20
5.3475.347
294401BSHIL;1U E
80/20
2.3442.344
294410BSHIL;2U E
80/20
2.3442.344
294763P-046 E
80/20
2.5772.577
295109WESTBROOK E
80/20
1.5381.538
295111SUBLETTE E
80/20
0.7470.747
917502Z2-087 E
80/20
4.6344.634
918052AA1-018 E OP
80/20
4.4934.493
925581AC1-033 C
80/20
0.6150.615
925582AC1-033 E
80/20
4.1154.115
934721AD1-100 C
80/20
5.2135.213
934722AD1-100 E
80/20
81.09481.094
937001AD2-134 C
80/20
1.1131.113
937002AD2-134 E
80/20
4.4474.447
942111AE2-223 C
80/20
1.6621.662
942112AE2-223 E
80/20
11.12111.121
957331AF2-027 C
80/20
2.7442.744
957332AF2-027 E
80/20
4.1174.117
959351AF2-226 C
80/20
2.8182.818
959352AF2-226 E
80/20
4.2274.227
959611AF2-252 C
80/20
2.0262.026
959612AF2-252 E
80/20
3.0393.039
960281AF2-319 C
80/20
2.8182.818
960282AF2-319 E
80/20
4.2274.227
960611AF2-352 C
80/20
2.0262.026
960612AF2-352 E
80/20
3.0393.039
962012AG1-044 E
80/20
0.0610.061
966091AG1-478 C
80/20
0.5860.586
966092AG1-478 E
80/20
0.8780.878
966441AG1-513 C
80/20
0.5610.561
966442AG1-513 E
80/20
0.8410.841
274674JOLIET 9 ;6U
80/20
18.55318.553
274675JOLIET 29;7U
80/20
48.1748.17
274676JOLIET 29;8U
80/20
48.17348.173
274682WAUKEGAN ;7U
80/20
20.43720.437
274683WAUKEGAN ;8U
80/20
22.03122.031
274687WILL CNTY;4U
80/20
45.63745.637
274890CAYUG;1U E
80/20
3.7773.777
274891CAYUG;2U E
80/20
3.7773.777
925771AC1-053 C
80/20
0.8460.846
925772AC1-053 E
80/20
5.6625.662
938851AE1-113 C
80/20
7.0367.036
938852AE1-113 E
80/20
24.94624.946
939401AE1-172 C
80/20
4.7284.728
939402AE1-172 E
80/20
22.13322.133
942651AE2-281 C
80/20
0.7520.752
942652AE2-281 E
80/20
4.6174.617
957382AF2-032 E
80/20
0.1430.143
270681BRIGHTSTK; R
80/20
0.6920.692
270839OTTER CRK; R
80/20
0.6710.671
274881WALNUT RG;1U
80/20
1.2841.284
275149KELLYCK ;1E
80/20
5.3725.372
276174W4-005 E
80/20
5.3895.389
276602WESTBROOK C
80/20
0.2330.233
276603SUBLETTE C
80/20
0.1050.105
276626AG1-044 E
80/20
0.0680.068
276627AG1-044 BAT
80/20
0.0120.012
276645AC1-214 C1
80/20
0.2510.251
276646AC1-214 C2
80/20
0.2510.251
276655AB2-047 C1
80/20
0.4330.433
276656AB2-047 C2
80/20
0.4330.433
276668AB2-070 C
80/20
0.5370.537
276675AE2-062 E
80/20
0.1460.146
293516O-009 E
80/20
5.1385.138
293519PILOT HIL;1E
80/20
5.3725.372
916212CRESCENT ;1U
80/20
1.3211.321
916221Z1-073 E
80/20
2.0242.024
924048AB2-047 E1
80/20
2.8732.873
924049AB2-047 E2
80/20
2.9192.919
924266AB2-070 E
80/20
3.253.25
926821AC1-168 C
80/20
0.9980.998
926822AC1-168 E
80/20
6.6946.694
927208AC1-214 E1
80/20
0.8920.892
927209AC1-214 E2
80/20
0.8920.892
935141AD1-148 C
80/20
1.1451.145
936371AD2-047 C
80/20
4.1754.175
936372AD2-047 E
80/20
20.38420.384
938861AE1-114 C
80/20
3.4363.436
938862AE1-114 E
80/20
11.72411.724
939321AE1-163 C
80/20
5.2615.261
939322AE1-163 E
80/20
32.3232.32
942421AE2-255 C
80/20
2.6652.665
942422AE2-255 E
80/20
7.9967.996
944221AF1-090 C
80/20
1.7541.754
944222AF1-090 E
80/20
8.2118.211
946321AF1-296 C
80/20
3.1023.102
946322AF1-296 E
80/20
14.52214.522
957371AF2-031 C
80/20
1.5261.526
957372AF2-031 E
80/20
2.2882.288
960261AF2-317 C
80/20
0.4950.495
961501AF2-441 C
80/20
14.5914.59
961502AF2-441 E
80/20
21.88421.884
965331AG1-398 C
80/20
0.2420.242
990901L-005 E
80/20
3.4733.473
276170Z1-108 E
80/20
2.7352.735
920272AA2-123 E
80/20
2.682.68
965913AG1-460 BT
80/20
0.0070.007
990547J1333 G
External Queue
1.95611.9561
990552J1334 G
External Queue
1.95611.9561
990557J1335 G
External Queue
1.95611.9561
990562J1336 G
External Queue
1.95611.9561
990647J1355
External Queue
42.973342.9733

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:DC
Final Cycle Loading:121.52 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1306.39
MW Contribution:7.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.9610.961
274848CAMPGROVE;RU
80/20
0.3760.376
274849CRESCENT ;1U
80/20
0.2860.286
274850MENDOTA H;RU
80/20
0.4720.472
274851PROVIDENC;RU
80/20
0.3040.304
274853TWINGROVE;U1
80/20
0.8810.881
274854TWINGROVE;U2
80/20
0.9070.907
274855GSG-6 ;RU
80/20
0.7180.718
274856ECOGROVE ;U1
80/20
0.620.62
274857BIG SKY ;U1
80/20
0.4760.476
274858BIG SKY ;U2
80/20
0.4760.476
274859EASYR;U1 E
80/20
3.283.28
274860EASYR;U2 E
80/20
3.283.28
274861TOP CROP ;1U
80/20
0.6480.648
274862TOP CROP ;2U
80/20
1.2361.236
274863CAYUGA RI;1U
80/20
0.7080.708
274864CAYUGA RI;2U
80/20
0.7080.708
274871GR RIDGE ;2U
80/20
0.3580.358
274872LEE DEKAL;1U
80/20
1.3351.335
274877BISHOP HL;1U
80/20
0.5860.586
274878BISHOP HL;2U
80/20
0.5860.586
274879MINONK ;1U
80/20
1.3331.333
274880RADFORD R;1U
80/20
0.9440.944
274887PILOT HIL;1U
80/20
1.3431.343
274888KELLY CRK;1U
80/20
1.3431.343
276156O-029 C
80/20
0.3360.336
276157O-029 C
80/20
0.6060.606
276158O-029 C
80/20
0.6060.606
276615W2-048 GEN
80/20
1.2811.281
276621X2-022 GEN
80/20
3.6453.645
290021O50 E
80/20
5.335.33
290051GSG-6; E
80/20
2.8722.872
290108LEEDK;1U E
80/20
6.5926.592
290261S-027 E
80/20
4.1334.133
290265S-028 E
80/20
4.1084.108
293061N-015 E
80/20
4.214.21
293644O22 E1
80/20
4.0484.048
293645O22 E2
80/20
4.6364.636
293715O-029 E
80/20
2.6572.657
293716O-029 E
80/20
1.4571.457
293717O-029 E
80/20
1.3391.339
293771O-035 E
80/20
1.8811.881
294392P-010 E
80/20
5.3475.347
294401BSHIL;1U E
80/20
2.3442.344
294410BSHIL;2U E
80/20
2.3442.344
294763P-046 E
80/20
2.5772.577
295109WESTBROOK E
80/20
1.5381.538
295111SUBLETTE E
80/20
0.7470.747
917502Z2-087 E
80/20
4.6344.634
918052AA1-018 E OP
80/20
4.4934.493
925581AC1-033 C
80/20
0.6150.615
925582AC1-033 E
80/20
4.1154.115
934721AD1-100 C
80/20
5.2135.213
934722AD1-100 E
80/20
81.09481.094
937001AD2-134 C
80/20
1.1131.113
937002AD2-134 E
80/20
4.4474.447
942111AE2-223 C
80/20
1.6621.662
942112AE2-223 E
80/20
11.12111.121
957331AF2-027 C
80/20
2.7442.744
957332AF2-027 E
80/20
4.1174.117
959351AF2-226 C
80/20
2.8182.818
959352AF2-226 E
80/20
4.2274.227
959611AF2-252 C
80/20
2.0262.026
959612AF2-252 E
80/20
3.0393.039
960281AF2-319 C
80/20
2.8182.818
960282AF2-319 E
80/20
4.2274.227
960611AF2-352 C
80/20
2.0262.026
960612AF2-352 E
80/20
3.0393.039
962012AG1-044 E
80/20
0.0610.061
966091AG1-478 C
80/20
0.5860.586
966092AG1-478 E
80/20
0.8780.878
966441AG1-513 C
80/20
0.5610.561
966442AG1-513 E
80/20
0.8410.841
274674JOLIET 9 ;6U
80/20
18.55318.553
274675JOLIET 29;7U
80/20
48.1748.17
274676JOLIET 29;8U
80/20
48.17348.173
274682WAUKEGAN ;7U
80/20
20.43720.437
274683WAUKEGAN ;8U
80/20
22.03122.031
274687WILL CNTY;4U
80/20
45.63745.637
274890CAYUG;1U E
80/20
3.7773.777
274891CAYUG;2U E
80/20
3.7773.777
925771AC1-053 C
80/20
0.8460.846
925772AC1-053 E
80/20
5.6625.662
938851AE1-113 C
80/20
7.0367.036
938852AE1-113 E
80/20
24.94624.946
939401AE1-172 C
80/20
4.7284.728
939402AE1-172 E
80/20
22.13322.133
942651AE2-281 C
80/20
0.7520.752
942652AE2-281 E
80/20
4.6174.617
957382AF2-032 E
80/20
0.1430.143
270681BRIGHTSTK; R
80/20
0.6920.692
270839OTTER CRK; R
80/20
0.6710.671
274881WALNUT RG;1U
80/20
1.2841.284
275149KELLYCK ;1E
80/20
5.3725.372
276174W4-005 E
80/20
5.3895.389
276602WESTBROOK C
80/20
0.2330.233
276603SUBLETTE C
80/20
0.1050.105
276626AG1-044 E
80/20
0.0680.068
276627AG1-044 BAT
80/20
0.0120.012
276645AC1-214 C1
80/20
0.2510.251
276646AC1-214 C2
80/20
0.2510.251
276655AB2-047 C1
80/20
0.4330.433
276656AB2-047 C2
80/20
0.4330.433
276668AB2-070 C
80/20
0.5370.537
276675AE2-062 E
80/20
0.1460.146
293516O-009 E
80/20
5.1385.138
293519PILOT HIL;1E
80/20
5.3725.372
916212CRESCENT ;1U
80/20
1.3211.321
916221Z1-073 E
80/20
2.0242.024
924048AB2-047 E1
80/20
2.8732.873
924049AB2-047 E2
80/20
2.9192.919
924266AB2-070 E
80/20
3.253.25
926821AC1-168 C
80/20
0.9980.998
926822AC1-168 E
80/20
6.6946.694
927208AC1-214 E1
80/20
0.8920.892
927209AC1-214 E2
80/20
0.8920.892
935141AD1-148 C
80/20
1.1451.145
936371AD2-047 C
80/20
4.1754.175
936372AD2-047 E
80/20
20.38420.384
938861AE1-114 C
80/20
3.4363.436
938862AE1-114 E
80/20
11.72411.724
939321AE1-163 C
80/20
5.2615.261
939322AE1-163 E
80/20
32.3232.32
942421AE2-255 C
80/20
2.6652.665
942422AE2-255 E
80/20
7.9967.996
944221AF1-090 C
80/20
1.7541.754
944222AF1-090 E
80/20
8.2118.211
946321AF1-296 C
80/20
3.1023.102
946322AF1-296 E
80/20
14.52214.522
957371AF2-031 C
80/20
1.5261.526
957372AF2-031 E
80/20
2.2882.288
960261AF2-317 C
80/20
0.4950.495
961501AF2-441 C
80/20
14.5914.59
961502AF2-441 E
80/20
21.88421.884
965331AG1-398 C
80/20
0.2420.242
990901L-005 E
80/20
3.4733.473
276170Z1-108 E
80/20
2.7352.735
920272AA2-123 E
80/20
2.682.68
965913AG1-460 BT
80/20
0.0070.007
990547J1333 G
External Queue
1.95611.9561
990552J1334 G
External Queue
1.95611.9561
990557J1335 G
External Queue
1.95611.9561
990562J1336 G
External Queue
1.95611.9561
990647J1355
External Queue
42.973342.9733

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.42 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1283.78
MW Contribution:6.85
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
50/50
0.9340.934
274861TOP CROP ;1U
50/50
0.630.63
274862TOP CROP ;2U
50/50
1.2021.202
274871GR RIDGE ;2U
50/50
0.3480.348
274887PILOT HIL;1U
50/50
1.3011.301
274888KELLY CRK;1U
50/50
1.3011.301
293061N-015 E
50/50
4.094.09
293644O22 E1
50/50
3.9353.935
293645O22 E2
50/50
4.5074.507
294392P-010 E
50/50
5.1945.194
934721AD1-100 C
50/50
5.0615.061
934722AD1-100 E
50/50
78.72578.725
942111AE2-223 C
Adder
1.65411764705882351.406
942112AE2-223 E
Adder
11.0670588235294139.407
957331AF2-027 C
Adder
2.66941176470588242.269
957332AF2-027 E
Adder
4.0035294117647063.403
959351AF2-226 C
50/50
2.742.74
959352AF2-226 E
50/50
4.114.11
959611AF2-252 C
Adder
2.02588235294117651.722
959612AF2-252 E
Adder
3.03764705882352942.582
960281AF2-319 C
50/50
2.742.74
960282AF2-319 E
50/50
4.114.11
960611AF2-352 C
Adder
2.02588235294117651.722
960612AF2-352 E
Adder
3.03764705882352942.582
962012AG1-044 E
Adder
0.060.051
966091AG1-478 C
50/50
0.5680.568
966092AG1-478 E
50/50
0.8520.852
966441AG1-513 C
50/50
0.5450.545
966442AG1-513 E
50/50
0.8170.817
274674JOLIET 9 ;6U
50/50
17.99517.995
274675JOLIET 29;7U
50/50
46.68246.682
274676JOLIET 29;8U
50/50
46.68546.685
274682WAUKEGAN ;7U
50/50
19.86719.867
274683WAUKEGAN ;8U
Adder
21.4218.207
274687WILL CNTY;4U
50/50
44.2244.22
938851AE1-113 C
Adder
6.865.831
938852AE1-113 E
Adder
24.32235294117647220.674
939401AE1-172 C
Adder
4.6211764705882353.928
939402AE1-172 E
Adder
21.6352941176470618.39
942651AE2-281 C
Adder
0.7317647058823530.622
942652AE2-281 E
Adder
4.49529411764705963.821
957382AF2-032 E
Adder
0.148235294117647080.126
275149KELLYCK ;1E
50/50
5.2055.205
276626AG1-044 E
Adder
0.067058823529411770.057
276627AG1-044 BAT
Adder
0.0117647058823529410.01
276675AE2-062 E
50/50
0.1410.141
293519PILOT HIL;1E
50/50
5.2055.205
926821AC1-168 C
Adder
0.97882352941176460.832
926822AC1-168 E
Adder
6.5682352941176475.583
936371AD2-047 C
50/50
4.0454.045
936372AD2-047 E
50/50
19.74719.747
938861AE1-114 C
Adder
3.35882352941176482.855
938862AE1-114 E
Adder
11.4611764705882379.742
939321AE1-163 C
Adder
5.1235294117647064.355
939322AE1-163 E
Adder
31.4705882352941226.75
942421AE2-255 C
Adder
2.5988235294117652.209
942422AE2-255 E
Adder
7.7952941176470596.626
944221AF1-090 C
Adder
1.85529411764705881.577
944222AF1-090 E
Adder
8.684705882352947.382
946321AF1-296 C
Adder
3.0505882352941182.593
946322AF1-296 E
Adder
14.27882352941176512.137
957371AF2-031 C
50/50
1.4761.476
957372AF2-031 E
50/50
2.2132.213
961501AF2-441 C
50/50
14.11814.118
961502AF2-441 E
50/50
21.17621.176
276170Z1-108 E
Adder
3.1294117647058832.66
920272AA2-123 E
Adder
3.07176470588235342.611
965913AG1-460 BT
Adder
0.0070588235294117650.006
990052J1200
External Queue
0.42270.4227
990512J1326 G
External Queue
5.28785.2878
990547J1333 G
External Queue
8.86958.8695
990552J1334 G
External Queue
8.86958.8695
990557J1335 G
External Queue
8.86958.8695
990562J1336 G
External Queue
8.86958.8695
990577J1339
External Queue
5.89225.8922
990582J1340
External Queue
5.89225.8922
990647J1355
External Queue
41.608541.6085
990662J1358
External Queue
14.341514.3415
990947J1432 G
External Queue
14.957514.9575
991092J1477
External Queue
2.81562.8156
991302J1755
External Queue
9.68289.6828

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.77 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1211.56
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.730.73
274848CAMPGROVE;RU
80/20
0.2780.278
274849CRESCENT ;1U
80/20
0.2120.212
274850MENDOTA H;RU
80/20
0.3520.352
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274856ECOGROVE ;U1
80/20
0.4620.462
274857BIG SKY ;U1
80/20
0.3530.353
274858BIG SKY ;U2
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274860EASYR;U2 E
80/20
2.4372.437
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
274864CAYUGA RI;2U
80/20
0.5160.516
274871GR RIDGE ;2U
80/20
0.2720.272
274872LEE DEKAL;1U
80/20
0.9950.995
274877BISHOP HL;1U
80/20
0.4330.433
274878BISHOP HL;2U
80/20
0.4330.433
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274887PILOT HIL;1U
80/20
0.9460.946
274888KELLY CRK;1U
80/20
0.9460.946
276156O-029 C
80/20
0.2490.249
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
276615W2-048 GEN
80/20
0.8910.891
276621X2-022 GEN
80/20
2.5362.536
290021O50 E
80/20
3.9653.965
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
293061N-015 E
80/20
3.1963.196
293644O22 E1
80/20
2.822.82
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293716O-029 E
80/20
1.081.08
293717O-029 E
80/20
0.9930.993
293771O-035 E
80/20
1.3921.392
294392P-010 E
80/20
4.0594.059
294401BSHIL;1U E
80/20
1.7331.733
294410BSHIL;2U E
80/20
1.7331.733
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
295111SUBLETTE E
80/20
0.5570.557
917502Z2-087 E
80/20
3.3333.333
918052AA1-018 E OP
80/20
3.6223.622
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
934721AD1-100 C
80/20
3.8223.822
934722AD1-100 E
80/20
59.4559.45
937001AD2-134 C
80/20
0.8290.829
937002AD2-134 E
80/20
3.3123.312
942111AE2-223 C
80/20
1.1951.195
942112AE2-223 E
80/20
7.9997.999
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959351AF2-226 C
80/20
1.9641.964
959352AF2-226 E
80/20
2.9452.945
959611AF2-252 C
80/20
1.4511.451
959612AF2-252 E
80/20
2.1762.176
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
962012AG1-044 E
80/20
0.0450.045
966091AG1-478 C
80/20
0.4310.431
966092AG1-478 E
80/20
0.6470.647
966441AG1-513 C
80/20
0.4190.419
966442AG1-513 E
80/20
0.6290.629
274674JOLIET 9 ;6U
80/20
13.64413.644
274675JOLIET 29;7U
80/20
36.25136.251
274676JOLIET 29;8U
80/20
36.23736.237
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274687WILL CNTY;4U
80/20
32.59232.592
274890CAYUG;1U E
80/20
2.7522.752
274891CAYUG;2U E
80/20
2.7522.752
925771AC1-053 C
80/20
0.590.59
925772AC1-053 E
80/20
3.953.95
938851AE1-113 C
80/20
5.2345.234
938852AE1-113 E
80/20
18.55518.555
939401AE1-172 C
80/20
3.453.45
939402AE1-172 E
80/20
16.15416.154
942651AE2-281 C
80/20
0.5930.593
942652AE2-281 E
80/20
3.6423.642
270681BRIGHTSTK; R
80/20
0.4980.498
270839OTTER CRK; R
80/20
0.5410.541
274881WALNUT RG;1U
80/20
0.9520.952
275149KELLYCK ;1E
80/20
3.7863.786
276174W4-005 E
80/20
3.7663.766
276602WESTBROOK C
80/20
0.1730.173
276603SUBLETTE C
80/20
0.0780.078
276626AG1-044 E
80/20
0.0510.051
276627AG1-044 BAT
80/20
0.0090.009
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
276655AB2-047 C1
80/20
0.3110.311
276656AB2-047 C2
80/20
0.3110.311
276668AB2-070 C
80/20
0.3750.375
276675AE2-062 E
80/20
0.1120.112
293516O-009 E
80/20
3.8093.809
293519PILOT HIL;1E
80/20
3.7863.786
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
924048AB2-047 E1
80/20
2.0672.067
924049AB2-047 E2
80/20
2.0992.099
924266AB2-070 E
80/20
2.272.27
926821AC1-168 C
80/20
0.7420.742
926822AC1-168 E
80/20
4.9814.981
927208AC1-214 E1
80/20
0.660.66
927209AC1-214 E2
80/20
0.660.66
935141AD1-148 C
80/20
0.7970.797
936371AD2-047 C
80/20
2.9422.942
936372AD2-047 E
80/20
14.36514.365
938861AE1-114 C
80/20
2.5552.555
938862AE1-114 E
80/20
8.7168.716
939321AE1-163 C
80/20
4.1514.151
939322AE1-163 E
80/20
25.49625.496
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
946321AF1-296 C
80/20
2.2942.294
946322AF1-296 E
80/20
10.73910.739
957371AF2-031 C
80/20
0.6360.636
957372AF2-031 E
80/20
0.9540.954
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
961502AF2-441 E
80/20
10.40210.402
965331AG1-398 C
80/20
0.1690.169
965791AG1-447 C
80/20
46.67646.676
990901L-005 E
80/20
2.5642.564
276170Z1-108 E
80/20
2.0422.042
920272AA2-123 E
80/20
22
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.6 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1209.9
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.730.73
274848CAMPGROVE;RU
80/20
0.2780.278
274849CRESCENT ;1U
80/20
0.2120.212
274850MENDOTA H;RU
80/20
0.3520.352
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274856ECOGROVE ;U1
80/20
0.4620.462
274857BIG SKY ;U1
80/20
0.3530.353
274858BIG SKY ;U2
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274860EASYR;U2 E
80/20
2.4372.437
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
274864CAYUGA RI;2U
80/20
0.5160.516
274871GR RIDGE ;2U
80/20
0.2720.272
274872LEE DEKAL;1U
80/20
0.9950.995
274877BISHOP HL;1U
80/20
0.4330.433
274878BISHOP HL;2U
80/20
0.4330.433
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274887PILOT HIL;1U
80/20
0.9460.946
274888KELLY CRK;1U
80/20
0.9460.946
276156O-029 C
80/20
0.2490.249
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
276615W2-048 GEN
80/20
0.8910.891
276621X2-022 GEN
80/20
2.5362.536
290021O50 E
80/20
3.9653.965
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
293061N-015 E
80/20
3.1963.196
293644O22 E1
80/20
2.822.82
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293716O-029 E
80/20
1.081.08
293717O-029 E
80/20
0.9930.993
293771O-035 E
80/20
1.3921.392
294392P-010 E
80/20
4.0594.059
294401BSHIL;1U E
80/20
1.7331.733
294410BSHIL;2U E
80/20
1.7331.733
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
295111SUBLETTE E
80/20
0.5570.557
917502Z2-087 E
80/20
3.3333.333
918052AA1-018 E OP
80/20
3.6223.622
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
934721AD1-100 C
80/20
3.8223.822
934722AD1-100 E
80/20
59.4559.45
937001AD2-134 C
80/20
0.8290.829
937002AD2-134 E
80/20
3.3123.312
942111AE2-223 C
80/20
1.1951.195
942112AE2-223 E
80/20
7.9997.999
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959351AF2-226 C
80/20
1.9641.964
959352AF2-226 E
80/20
2.9452.945
959611AF2-252 C
80/20
1.4511.451
959612AF2-252 E
80/20
2.1762.176
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
962012AG1-044 E
80/20
0.0450.045
966091AG1-478 C
80/20
0.4310.431
966092AG1-478 E
80/20
0.6470.647
966441AG1-513 C
80/20
0.4190.419
966442AG1-513 E
80/20
0.6290.629
274674JOLIET 9 ;6U
80/20
13.64413.644
274675JOLIET 29;7U
80/20
36.25136.251
274676JOLIET 29;8U
80/20
36.23736.237
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274687WILL CNTY;4U
80/20
32.59232.592
274890CAYUG;1U E
80/20
2.7522.752
274891CAYUG;2U E
80/20
2.7522.752
925771AC1-053 C
80/20
0.590.59
925772AC1-053 E
80/20
3.953.95
938851AE1-113 C
80/20
5.2345.234
938852AE1-113 E
80/20
18.55518.555
939401AE1-172 C
80/20
3.453.45
939402AE1-172 E
80/20
16.15416.154
942651AE2-281 C
80/20
0.5930.593
942652AE2-281 E
80/20
3.6423.642
270681BRIGHTSTK; R
80/20
0.4980.498
270839OTTER CRK; R
80/20
0.5410.541
274881WALNUT RG;1U
80/20
0.9520.952
275149KELLYCK ;1E
80/20
3.7863.786
276174W4-005 E
80/20
3.7663.766
276602WESTBROOK C
80/20
0.1730.173
276603SUBLETTE C
80/20
0.0780.078
276626AG1-044 E
80/20
0.0510.051
276627AG1-044 BAT
80/20
0.0090.009
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
276655AB2-047 C1
80/20
0.3110.311
276656AB2-047 C2
80/20
0.3110.311
276668AB2-070 C
80/20
0.3750.375
276675AE2-062 E
80/20
0.1120.112
293516O-009 E
80/20
3.8093.809
293519PILOT HIL;1E
80/20
3.7863.786
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
924048AB2-047 E1
80/20
2.0672.067
924049AB2-047 E2
80/20
2.0992.099
924266AB2-070 E
80/20
2.272.27
926821AC1-168 C
80/20
0.7420.742
926822AC1-168 E
80/20
4.9814.981
927208AC1-214 E1
80/20
0.660.66
927209AC1-214 E2
80/20
0.660.66
935141AD1-148 C
80/20
0.7970.797
936371AD2-047 C
80/20
2.9422.942
936372AD2-047 E
80/20
14.36514.365
938861AE1-114 C
80/20
2.5552.555
938862AE1-114 E
80/20
8.7168.716
939321AE1-163 C
80/20
4.1514.151
939322AE1-163 E
80/20
25.49625.496
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
946321AF1-296 C
80/20
2.2942.294
946322AF1-296 E
80/20
10.73910.739
957371AF2-031 C
80/20
0.6360.636
957372AF2-031 E
80/20
0.9540.954
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
961502AF2-441 E
80/20
10.40210.402
965331AG1-398 C
80/20
0.1690.169
965791AG1-447 C
80/20
46.67646.676
990901L-005 E
80/20
2.5642.564
276170Z1-108 E
80/20
2.0422.042
920272AA2-123 E
80/20
22
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.59 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1073.81
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
50/50
0.730.73
274871GR RIDGE ;2U
50/50
0.2720.272
274887PILOT HIL;1U
50/50
0.9460.946
274888KELLY CRK;1U
50/50
0.9460.946
293061N-015 E
50/50
3.1963.196
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
934721AD1-100 C
50/50
3.8213.821
934722AD1-100 E
50/50
59.44459.444
942111AE2-223 C
Adder
1.19529411764705881.016
942112AE2-223 E
Adder
7.9988235294117666.799
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959351AF2-226 C
Adder
1.9635294117647061.669
959352AF2-226 E
Adder
2.94588235294117642.504
959611AF2-252 C
Adder
1.45058823529411771.233
959612AF2-252 E
Adder
2.17647058823529441.85
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
962012AG1-044 E
Adder
0.044705882352941180.038
966091AG1-478 C
50/50
0.4310.431
966092AG1-478 E
50/50
0.6470.647
966441AG1-513 C
50/50
0.420.42
966442AG1-513 E
50/50
0.6290.629
274674JOLIET 9 ;6U
50/50
13.64513.645
274675JOLIET 29;7U
50/50
36.25136.251
274676JOLIET 29;8U
50/50
36.23736.237
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
274687WILL CNTY;4U
50/50
32.59532.595
938851AE1-113 C
Adder
5.2341176470588244.449
938852AE1-113 E
Adder
18.5576470588235315.774
939401AE1-172 C
Adder
3.45058823529411772.933
939402AE1-172 E
Adder
16.15411764705882513.731
942651AE2-281 C
50/50
0.5930.593
942652AE2-281 E
50/50
3.6423.642
270839OTTER CRK; R
50/50
0.5410.541
275149KELLYCK ;1E
50/50
3.7853.785
276626AG1-044 E
Adder
0.050588235294117640.043
276627AG1-044 BAT
Adder
0.0094117647058823540.008
276675AE2-062 E
50/50
0.1120.112
293519PILOT HIL;1E
50/50
3.7853.785
926821AC1-168 C
Adder
0.74235294117647070.631
926822AC1-168 E
Adder
4.98117647058823554.234
936371AD2-047 C
50/50
2.9422.942
936372AD2-047 E
50/50
14.36514.365
938861AE1-114 C
Adder
2.5552941176470592.172
938862AE1-114 E
Adder
8.717647058823537.41
939321AE1-163 C
50/50
4.1514.151
939322AE1-163 E
50/50
25.49625.496
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
946321AF1-296 C
Adder
2.29411764705882341.95
946322AF1-296 E
Adder
10.749.129
957371AF2-031 C
Adder
0.63647058823529420.541
957372AF2-031 E
Adder
0.95411764705882360.811
961501AF2-441 C
Adder
6.9341176470588245.894
961502AF2-441 E
Adder
10.48.84
965791AG1-447 C
50/50
46.67546.675
276170Z1-108 E
50/50
2.0432.043
920272AA2-123 E
Adder
2.35294117647058832
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
990947J1432 G
External Queue
12.502512.5025
991302J1755
External Queue
8.07698.0769

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.59 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1073.8
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
50/50
0.730.73
274871GR RIDGE ;2U
50/50
0.2720.272
274887PILOT HIL;1U
50/50
0.9460.946
274888KELLY CRK;1U
50/50
0.9460.946
293061N-015 E
50/50
3.1963.196
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
934721AD1-100 C
50/50
3.8213.821
934722AD1-100 E
50/50
59.44459.444
942111AE2-223 C
Adder
1.19529411764705881.016
942112AE2-223 E
Adder
7.9988235294117666.799
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959351AF2-226 C
Adder
1.9635294117647061.669
959352AF2-226 E
Adder
2.94588235294117642.504
959611AF2-252 C
Adder
1.45058823529411771.233
959612AF2-252 E
Adder
2.17647058823529441.85
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
962012AG1-044 E
Adder
0.044705882352941180.038
966091AG1-478 C
50/50
0.4310.431
966092AG1-478 E
50/50
0.6470.647
966441AG1-513 C
50/50
0.420.42
966442AG1-513 E
50/50
0.6290.629
274674JOLIET 9 ;6U
50/50
13.64513.645
274675JOLIET 29;7U
50/50
36.25136.251
274676JOLIET 29;8U
50/50
36.23736.237
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
274687WILL CNTY;4U
50/50
32.59532.595
938851AE1-113 C
Adder
5.2341176470588244.449
938852AE1-113 E
Adder
18.5576470588235315.774
939401AE1-172 C
Adder
3.45058823529411772.933
939402AE1-172 E
Adder
16.15411764705882513.731
942651AE2-281 C
50/50
0.5930.593
942652AE2-281 E
50/50
3.6423.642
270839OTTER CRK; R
50/50
0.5410.541
275149KELLYCK ;1E
50/50
3.7853.785
276626AG1-044 E
Adder
0.050588235294117640.043
276627AG1-044 BAT
Adder
0.0094117647058823540.008
276675AE2-062 E
50/50
0.1120.112
293519PILOT HIL;1E
50/50
3.7853.785
926821AC1-168 C
Adder
0.74235294117647070.631
926822AC1-168 E
Adder
4.98117647058823554.234
936371AD2-047 C
50/50
2.9422.942
936372AD2-047 E
50/50
14.36514.365
938861AE1-114 C
Adder
2.5552941176470592.172
938862AE1-114 E
Adder
8.717647058823537.41
939321AE1-163 C
50/50
4.1514.151
939322AE1-163 E
50/50
25.49625.496
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
946321AF1-296 C
Adder
2.29411764705882341.95
946322AF1-296 E
Adder
10.749.129
957371AF2-031 C
Adder
0.63647058823529420.541
957372AF2-031 E
Adder
0.95411764705882360.811
961501AF2-441 C
Adder
6.9341176470588245.894
961502AF2-441 E
Adder
10.48.84
965791AG1-447 C
50/50
46.67546.675
276170Z1-108 E
50/50
2.0432.043
920272AA2-123 E
Adder
2.35294117647058832
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
990947J1432 G
External Queue
12.502512.5025
991302J1755
External Queue
8.07698.0769

Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.96 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1454.81
MW Contribution:5.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.8150.815
274848CAMPGROVE;RU
80/20
0.3150.315
274849CRESCENT ;1U
80/20
0.240.24
274850MENDOTA H;RU
80/20
0.40.4
274851PROVIDENC;RU
80/20
0.2550.255
274853TWINGROVE;U1
80/20
0.7350.735
274854TWINGROVE;U2
80/20
0.7560.756
274855GSG-6 ;RU
80/20
0.6080.608
274856ECOGROVE ;U1
80/20
0.5240.524
274857BIG SKY ;U1
80/20
0.4010.401
274858BIG SKY ;U2
80/20
0.4010.401
274859EASYR;U1 E
80/20
2.7672.767
274860EASYR;U2 E
80/20
2.7672.767
274861TOP CROP ;1U
80/20
0.5020.502
274862TOP CROP ;2U
80/20
0.9590.959
274863CAYUGA RI;1U
80/20
0.6080.608
274864CAYUGA RI;2U
80/20
0.6080.608
274871GR RIDGE ;2U
80/20
0.3030.303
274872LEE DEKAL;1U
80/20
1.1321.132
274877BISHOP HL;1U
80/20
0.4910.491
274878BISHOP HL;2U
80/20
0.4910.491
274879MINONK ;1U
80/20
1.1161.116
274880RADFORD R;1U
80/20
0.7660.766
274887PILOT HIL;1U
80/20
1.2441.244
274888KELLY CRK;1U
80/20
1.2441.244
276156O-029 C
80/20
0.2830.283
276157O-029 C
80/20
0.510.51
276158O-029 C
80/20
0.510.51
276615W2-048 GEN
80/20
1.0321.032
276621X2-022 GEN
80/20
2.9362.936
290021O50 E
80/20
4.4654.465
290051GSG-6; E
80/20
2.4322.432
290108LEEDK;1U E
80/20
5.5895.589
290261S-027 E
80/20
3.4493.449
290265S-028 E
80/20
3.4283.428
293061N-015 E
80/20
3.5693.569
293644O22 E1
80/20
3.1383.138
293645O22 E2
80/20
3.5943.594
293715O-029 E
80/20
2.2352.235
293716O-029 E
80/20
1.2261.226
293717O-029 E
80/20
1.1261.126
293771O-035 E
80/20
1.5761.576
294392P-010 E
80/20
4.5334.533
294401BSHIL;1U E
80/20
1.9641.964
294410BSHIL;2U E
80/20
1.9641.964
294763P-046 E
80/20
2.1772.177
295109WESTBROOK E
80/20
1.3021.302
295111SUBLETTE E
80/20
0.6330.633
917502Z2-087 E
80/20
3.8853.885
918052AA1-018 E OP
80/20
4.0454.045
925581AC1-033 C
80/20
0.5150.515
925582AC1-033 E
80/20
3.4483.448
934721AD1-100 C
80/20
4.5624.562
934722AD1-100 E
80/20
70.95870.958
937001AD2-134 C
80/20
0.9430.943
937002AD2-134 E
80/20
3.7653.765
942111AE2-223 C
80/20
1.3931.393
942112AE2-223 E
80/20
9.3259.325
957331AF2-027 C
80/20
2.3262.326
957332AF2-027 E
80/20
3.4893.489
959351AF2-226 C
80/20
2.1852.185
959352AF2-226 E
80/20
3.2773.277
959611AF2-252 C
80/20
1.6911.691
959612AF2-252 E
80/20
2.5362.536
960281AF2-319 C
80/20
2.1852.185
960282AF2-319 E
80/20
3.2773.277
960611AF2-352 C
80/20
1.6911.691
960612AF2-352 E
80/20
2.5362.536
962012AG1-044 E
80/20
0.0510.051
966091AG1-478 C
80/20
0.5150.515
966092AG1-478 E
80/20
0.7720.772
966441AG1-513 C
80/20
0.4770.477
966442AG1-513 E
80/20
0.7160.716
274674JOLIET 9 ;6U
80/20
15.7815.78
274675JOLIET 29;7U
80/20
40.76540.765
274676JOLIET 29;8U
80/20
40.75240.752
274682WAUKEGAN ;7U
80/20
17.32117.321
274683WAUKEGAN ;8U
80/20
18.67418.674
274687WILL CNTY;4U
80/20
37.42737.427
274890CAYUG;1U E
80/20
3.2433.243
274891CAYUG;2U E
80/20
3.2433.243
925771AC1-053 C
80/20
0.6840.684
925772AC1-053 E
80/20
4.5784.578
938851AE1-113 C
80/20
5.8945.894
938852AE1-113 E
80/20
20.89520.895
939401AE1-172 C
80/20
4.0864.086
939402AE1-172 E
80/20
19.12919.129
942651AE2-281 C
80/20
0.6630.663
942652AE2-281 E
80/20
4.0764.076
957382AF2-032 E
80/20
0.1140.114
270681BRIGHTSTK; R
80/20
0.5810.581
270839OTTER CRK; R
80/20
0.6040.604
274881WALNUT RG;1U
80/20
1.0811.081
275149KELLYCK ;1E
80/20
4.9764.976
276174W4-005 E
80/20
4.3724.372
276602WESTBROOK C
80/20
0.1970.197
276603SUBLETTE C
80/20
0.0890.089
276626AG1-044 E
80/20
0.0580.058
276627AG1-044 BAT
80/20
0.010.01
276645AC1-214 C1
80/20
0.210.21
276646AC1-214 C2
80/20
0.210.21
276655AB2-047 C1
80/20
0.3630.363
276656AB2-047 C2
80/20
0.3630.363
276668AB2-070 C
80/20
0.4340.434
276675AE2-062 E
80/20
0.1280.128
293516O-009 E
80/20
4.3224.322
293519PILOT HIL;1E
80/20
4.9764.976
916212CRESCENT ;1U
80/20
1.1071.107
916221Z1-073 E
80/20
1.7141.714
924048AB2-047 E1
80/20
2.4092.409
924049AB2-047 E2
80/20
2.4472.447
924266AB2-070 E
80/20
2.6322.632
926821AC1-168 C
80/20
0.8380.838
926822AC1-168 E
80/20
5.6235.623
927208AC1-214 E1
80/20
0.7470.747
927209AC1-214 E2
80/20
0.7470.747
935141AD1-148 C
80/20
0.9230.923
936371AD2-047 C
80/20
3.8673.867
936372AD2-047 E
80/20
18.8818.88
938861AE1-114 C
80/20
2.9012.901
938862AE1-114 E
80/20
9.8979.897
939321AE1-163 C
80/20
4.6444.644
939322AE1-163 E
80/20
28.5328.53
942421AE2-255 C
80/20
2.2322.232
942422AE2-255 E
80/20
6.6976.697
946321AF1-296 C
80/20
2.6042.604
946322AF1-296 E
80/20
12.19312.193
957371AF2-031 C
80/20
0.5430.543
957372AF2-031 E
80/20
0.8150.815
960261AF2-317 C
80/20
0.3990.399
961501AF2-441 C
80/20
7.147.14
961502AF2-441 E
80/20
10.7110.71
965331AG1-398 C
80/20
0.1960.196
990901L-005 E
80/20
2.9052.905
276170Z1-108 E
80/20
2.3192.319
920272AA2-123 E
80/20
2.2712.271
965913AG1-460 BT
80/20
0.0060.006
990052J1200
External Queue
0.40350.4035
990512J1326 G
External Queue
5.09935.0993
990947J1432 G
External Queue
5.75495.7549
991302J1755
External Queue
9.24129.2412

Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.81 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1452.61
MW Contribution:5.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.8150.815
274848CAMPGROVE;RU
80/20
0.3150.315
274849CRESCENT ;1U
80/20
0.240.24
274850MENDOTA H;RU
80/20
0.40.4
274851PROVIDENC;RU
80/20
0.2550.255
274853TWINGROVE;U1
80/20
0.7350.735
274854TWINGROVE;U2
80/20
0.7560.756
274855GSG-6 ;RU
80/20
0.6080.608
274856ECOGROVE ;U1
80/20
0.5240.524
274857BIG SKY ;U1
80/20
0.4010.401
274858BIG SKY ;U2
80/20
0.4010.401
274859EASYR;U1 E
80/20
2.7672.767
274860EASYR;U2 E
80/20
2.7672.767
274861TOP CROP ;1U
80/20
0.5020.502
274862TOP CROP ;2U
80/20
0.9590.959
274863CAYUGA RI;1U
80/20
0.6080.608
274864CAYUGA RI;2U
80/20
0.6080.608
274871GR RIDGE ;2U
80/20
0.3030.303
274872LEE DEKAL;1U
80/20
1.1321.132
274877BISHOP HL;1U
80/20
0.4910.491
274878BISHOP HL;2U
80/20
0.4910.491
274879MINONK ;1U
80/20
1.1161.116
274880RADFORD R;1U
80/20
0.7660.766
274887PILOT HIL;1U
80/20
1.2441.244
274888KELLY CRK;1U
80/20
1.2441.244
276156O-029 C
80/20
0.2830.283
276157O-029 C
80/20
0.510.51
276158O-029 C
80/20
0.510.51
276615W2-048 GEN
80/20
1.0321.032
276621X2-022 GEN
80/20
2.9362.936
290021O50 E
80/20
4.4654.465
290051GSG-6; E
80/20
2.4322.432
290108LEEDK;1U E
80/20
5.5895.589
290261S-027 E
80/20
3.4493.449
290265S-028 E
80/20
3.4283.428
293061N-015 E
80/20
3.5693.569
293644O22 E1
80/20
3.1383.138
293645O22 E2
80/20
3.5943.594
293715O-029 E
80/20
2.2352.235
293716O-029 E
80/20
1.2261.226
293717O-029 E
80/20
1.1261.126
293771O-035 E
80/20
1.5761.576
294392P-010 E
80/20
4.5334.533
294401BSHIL;1U E
80/20
1.9641.964
294410BSHIL;2U E
80/20
1.9641.964
294763P-046 E
80/20
2.1772.177
295109WESTBROOK E
80/20
1.3021.302
295111SUBLETTE E
80/20
0.6330.633
917502Z2-087 E
80/20
3.8853.885
918052AA1-018 E OP
80/20
4.0454.045
925581AC1-033 C
80/20
0.5150.515
925582AC1-033 E
80/20
3.4483.448
934721AD1-100 C
80/20
4.5624.562
934722AD1-100 E
80/20
70.95870.958
937001AD2-134 C
80/20
0.9430.943
937002AD2-134 E
80/20
3.7653.765
942111AE2-223 C
80/20
1.3931.393
942112AE2-223 E
80/20
9.3259.325
957331AF2-027 C
80/20
2.3262.326
957332AF2-027 E
80/20
3.4893.489
959351AF2-226 C
80/20
2.1852.185
959352AF2-226 E
80/20
3.2773.277
959611AF2-252 C
80/20
1.6911.691
959612AF2-252 E
80/20
2.5362.536
960281AF2-319 C
80/20
2.1852.185
960282AF2-319 E
80/20
3.2773.277
960611AF2-352 C
80/20
1.6911.691
960612AF2-352 E
80/20
2.5362.536
962012AG1-044 E
80/20
0.0510.051
966091AG1-478 C
80/20
0.5150.515
966092AG1-478 E
80/20
0.7720.772
966441AG1-513 C
80/20
0.4770.477
966442AG1-513 E
80/20
0.7160.716
274674JOLIET 9 ;6U
80/20
15.7815.78
274675JOLIET 29;7U
80/20
40.76540.765
274676JOLIET 29;8U
80/20
40.75240.752
274682WAUKEGAN ;7U
80/20
17.32117.321
274683WAUKEGAN ;8U
80/20
18.67418.674
274687WILL CNTY;4U
80/20
37.42737.427
274890CAYUG;1U E
80/20
3.2433.243
274891CAYUG;2U E
80/20
3.2433.243
925771AC1-053 C
80/20
0.6840.684
925772AC1-053 E
80/20
4.5784.578
938851AE1-113 C
80/20
5.8945.894
938852AE1-113 E
80/20
20.89520.895
939401AE1-172 C
80/20
4.0864.086
939402AE1-172 E
80/20
19.12919.129
942651AE2-281 C
80/20
0.6630.663
942652AE2-281 E
80/20
4.0764.076
957382AF2-032 E
80/20
0.1140.114
270681BRIGHTSTK; R
80/20
0.5810.581
270839OTTER CRK; R
80/20
0.6040.604
274881WALNUT RG;1U
80/20
1.0811.081
275149KELLYCK ;1E
80/20
4.9764.976
276174W4-005 E
80/20
4.3724.372
276602WESTBROOK C
80/20
0.1970.197
276603SUBLETTE C
80/20
0.0890.089
276626AG1-044 E
80/20
0.0580.058
276627AG1-044 BAT
80/20
0.010.01
276645AC1-214 C1
80/20
0.210.21
276646AC1-214 C2
80/20
0.210.21
276655AB2-047 C1
80/20
0.3630.363
276656AB2-047 C2
80/20
0.3630.363
276668AB2-070 C
80/20
0.4340.434
276675AE2-062 E
80/20
0.1280.128
293516O-009 E
80/20
4.3224.322
293519PILOT HIL;1E
80/20
4.9764.976
916212CRESCENT ;1U
80/20
1.1071.107
916221Z1-073 E
80/20
1.7141.714
924048AB2-047 E1
80/20
2.4092.409
924049AB2-047 E2
80/20
2.4472.447
924266AB2-070 E
80/20
2.6322.632
926821AC1-168 C
80/20
0.8380.838
926822AC1-168 E
80/20
5.6235.623
927208AC1-214 E1
80/20
0.7470.747
927209AC1-214 E2
80/20
0.7470.747
935141AD1-148 C
80/20
0.9230.923
936371AD2-047 C
80/20
3.8673.867
936372AD2-047 E
80/20
18.8818.88
938861AE1-114 C
80/20
2.9012.901
938862AE1-114 E
80/20
9.8979.897
939321AE1-163 C
80/20
4.6444.644
939322AE1-163 E
80/20
28.5328.53
942421AE2-255 C
80/20
2.2322.232
942422AE2-255 E
80/20
6.6976.697
946321AF1-296 C
80/20
2.6042.604
946322AF1-296 E
80/20
12.19312.193
957371AF2-031 C
80/20
0.5430.543
957372AF2-031 E
80/20
0.8150.815
960261AF2-317 C
80/20
0.3990.399
961501AF2-441 C
80/20
7.147.14
961502AF2-441 E
80/20
10.7110.71
965331AG1-398 C
80/20
0.1960.196
990901L-005 E
80/20
2.9052.905
276170Z1-108 E
80/20
2.3192.319
920272AA2-123 E
80/20
2.2712.271
965913AG1-460 BT
80/20
0.0060.006
990052J1200
External Queue
0.40350.4035
990512J1326 G
External Queue
5.09935.0993
990947J1432 G
External Queue
5.75495.7549
991302J1755
External Queue
9.24129.2412

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.58 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1630.9
MW Contribution:7.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.8810.881
274848CAMPGROVE;RU
80/20
0.3340.334
274849CRESCENT ;1U
80/20
0.2550.255
274850MENDOTA H;RU
80/20
0.4220.422
274851PROVIDENC;RU
80/20
0.270.27
274853TWINGROVE;U1
80/20
0.7480.748
274854TWINGROVE;U2
80/20
0.770.77
274855GSG-6 ;RU
80/20
0.6420.642
274856ECOGROVE ;U1
80/20
0.5550.555
274857BIG SKY ;U1
80/20
0.4250.425
274858BIG SKY ;U2
80/20
0.4250.425
274859EASYR;U1 E
80/20
2.9342.934
274860EASYR;U2 E
80/20
2.9342.934
274861TOP CROP ;1U
80/20
0.6560.656
274862TOP CROP ;2U
80/20
1.2521.252
274863CAYUGA RI;1U
80/20
0.6120.612
274864CAYUGA RI;2U
80/20
0.6120.612
274871GR RIDGE ;2U
80/20
0.3280.328
274872LEE DEKAL;1U
80/20
1.1941.194
274877BISHOP HL;1U
80/20
0.5210.521
274878BISHOP HL;2U
80/20
0.5210.521
274879MINONK ;1U
80/20
1.2161.216
274880RADFORD R;1U
80/20
0.7810.781
274887PILOT HIL;1U
80/20
0.9910.991
274888KELLY CRK;1U
80/20
0.9910.991
276156O-029 C
80/20
0.30.3
276157O-029 C
80/20
0.5410.541
276158O-029 C
80/20
0.5410.541
276615W2-048 GEN
80/20
1.0561.056
276621X2-022 GEN
80/20
3.0063.006
290021O50 E
80/20
4.8624.862
290051GSG-6; E
80/20
2.5672.567
290108LEEDK;1U E
80/20
5.8935.893
290261S-027 E
80/20
3.5093.509
290265S-028 E
80/20
3.4883.488
293061N-015 E
80/20
3.8593.859
293644O22 E1
80/20
4.0984.098
293645O22 E2
80/20
4.6944.694
293715O-029 E
80/20
2.3712.371
293716O-029 E
80/20
1.31.3
293717O-029 E
80/20
1.1951.195
293771O-035 E
80/20
1.6711.671
294392P-010 E
80/20
4.9014.901
294401BSHIL;1U E
80/20
2.0852.085
294410BSHIL;2U E
80/20
2.0852.085
294763P-046 E
80/20
2.3082.308
295109WESTBROOK E
80/20
1.3751.375
295111SUBLETTE E
80/20
0.6680.668
917502Z2-087 E
80/20
3.9533.953
918052AA1-018 E OP
80/20
3.793.79
925581AC1-033 C
80/20
0.5470.547
925582AC1-033 E
80/20
3.6613.661
934721AD1-100 C
80/20
4.5344.534
934722AD1-100 E
80/20
70.52170.521
937001AD2-134 C
80/20
0.9950.995
937002AD2-134 E
80/20
3.9763.976
942111AE2-223 C
80/20
1.4181.418
942112AE2-223 E
80/20
9.4879.487
957331AF2-027 C
80/20
2.4722.472
957332AF2-027 E
80/20
3.7083.708
959351AF2-226 C
80/20
2.8532.853
959352AF2-226 E
80/20
4.284.28
959611AF2-252 C
80/20
1.721.72
959612AF2-252 E
80/20
2.582.58
960281AF2-319 C
80/20
2.8532.853
960282AF2-319 E
80/20
4.284.28
960611AF2-352 C
80/20
1.721.72
960612AF2-352 E
80/20
2.582.58
962012AG1-044 E
80/20
0.0540.054
966091AG1-478 C
80/20
0.4850.485
966092AG1-478 E
80/20
0.7280.728
966441AG1-513 C
80/20
0.5010.501
966442AG1-513 E
80/20
0.7520.752
274674JOLIET 9 ;6U
80/20
15.24915.249
274675JOLIET 29;7U
80/20
44.03844.038
274676JOLIET 29;8U
80/20
44.06544.065
274682WAUKEGAN ;7U
80/20
18.42518.425
274683WAUKEGAN ;8U
80/20
19.85719.857
274687WILL CNTY;4U
80/20
41.59241.592
274890CAYUG;1U E
80/20
3.2643.264
274891CAYUG;2U E
80/20
3.2643.264
925771AC1-053 C
80/20
0.70.7
925772AC1-053 E
80/20
4.6814.681
938851AE1-113 C
80/20
6.4186.418
938852AE1-113 E
80/20
22.75422.754
939401AE1-172 C
80/20
4.0924.092
939402AE1-172 E
80/20
19.1619.16
942651AE2-281 C
80/20
0.6470.647
942652AE2-281 E
80/20
3.9763.976
957382AF2-032 E
80/20
0.1170.117
270681BRIGHTSTK; R
80/20
0.5910.591
270839OTTER CRK; R
80/20
0.5660.566
274881WALNUT RG;1U
80/20
1.1461.146
275149KELLYCK ;1E
80/20
3.9663.966
276174W4-005 E
80/20
4.4614.461
276602WESTBROOK C
80/20
0.2080.208
276603SUBLETTE C
80/20
0.0940.094
276626AG1-044 E
80/20
0.0610.061
276627AG1-044 BAT
80/20
0.0110.011
276645AC1-214 C1
80/20
0.2230.223
276646AC1-214 C2
80/20
0.2230.223
276655AB2-047 C1
80/20
0.3690.369
276656AB2-047 C2
80/20
0.3690.369
276668AB2-070 C
80/20
0.4440.444
276675AE2-062 E
80/20
0.1250.125
293516O-009 E
80/20
4.5854.585
293519PILOT HIL;1E
80/20
3.9663.966
916212CRESCENT ;1U
80/20
1.1741.174
916221Z1-073 E
80/20
1.8091.809
924048AB2-047 E1
80/20
2.4512.451
924049AB2-047 E2
80/20
2.492.49
924266AB2-070 E
80/20
2.692.69
926821AC1-168 C
80/20
0.8910.891
926822AC1-168 E
80/20
5.9825.982
927208AC1-214 E1
80/20
0.7920.792
927209AC1-214 E2
80/20
0.7920.792
935141AD1-148 C
80/20
0.9450.945
936371AD2-047 C
80/20
3.0823.082
936372AD2-047 E
80/20
15.04615.046
938861AE1-114 C
80/20
3.0753.075
938862AE1-114 E
80/20
10.49110.491
939321AE1-163 C
80/20
4.5314.531
939322AE1-163 E
80/20
27.83427.834
942421AE2-255 C
80/20
2.4312.431
942422AE2-255 E
80/20
7.2937.293
946321AF1-296 C
80/20
2.7622.762
946322AF1-296 E
80/20
12.93112.931
957371AF2-031 C
80/20
0.470.47
957372AF2-031 E
80/20
0.7050.705
960261AF2-317 C
80/20
0.4080.408
961501AF2-441 C
80/20
6.2416.241
961502AF2-441 E
80/20
9.3619.361
965331AG1-398 C
80/20
0.2010.201
990901L-005 E
80/20
3.0863.086
276170Z1-108 E
80/20
2.4582.458
920272AA2-123 E
80/20
2.4072.407
965913AG1-460 BT
80/20
0.0060.006
990052J1200
External Queue
0.43040.4304
990512J1326 G
External Queue
5.43125.4312
990947J1432 G
External Queue
6.13376.1337
991302J1755
External Queue
9.86249.8624

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.39 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1628.28
MW Contribution:7.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.8810.881
274848CAMPGROVE;RU
80/20
0.3340.334
274849CRESCENT ;1U
80/20
0.2550.255
274850MENDOTA H;RU
80/20
0.4220.422
274851PROVIDENC;RU
80/20
0.270.27
274853TWINGROVE;U1
80/20
0.7480.748
274854TWINGROVE;U2
80/20
0.770.77
274855GSG-6 ;RU
80/20
0.6420.642
274856ECOGROVE ;U1
80/20
0.5550.555
274857BIG SKY ;U1
80/20
0.4250.425
274858BIG SKY ;U2
80/20
0.4250.425
274859EASYR;U1 E
80/20
2.9342.934
274860EASYR;U2 E
80/20
2.9342.934
274861TOP CROP ;1U
80/20
0.6560.656
274862TOP CROP ;2U
80/20
1.2521.252
274863CAYUGA RI;1U
80/20
0.6120.612
274864CAYUGA RI;2U
80/20
0.6120.612
274871GR RIDGE ;2U
80/20
0.3280.328
274872LEE DEKAL;1U
80/20
1.1941.194
274877BISHOP HL;1U
80/20
0.5210.521
274878BISHOP HL;2U
80/20
0.5210.521
274879MINONK ;1U
80/20
1.2161.216
274880RADFORD R;1U
80/20
0.7810.781
274887PILOT HIL;1U
80/20
0.9910.991
274888KELLY CRK;1U
80/20
0.9910.991
276156O-029 C
80/20
0.30.3
276157O-029 C
80/20
0.5410.541
276158O-029 C
80/20
0.5410.541
276615W2-048 GEN
80/20
1.0561.056
276621X2-022 GEN
80/20
3.0063.006
290021O50 E
80/20
4.8624.862
290051GSG-6; E
80/20
2.5672.567
290108LEEDK;1U E
80/20
5.8935.893
290261S-027 E
80/20
3.5093.509
290265S-028 E
80/20
3.4883.488
293061N-015 E
80/20
3.8593.859
293644O22 E1
80/20
4.0984.098
293645O22 E2
80/20
4.6944.694
293715O-029 E
80/20
2.3712.371
293716O-029 E
80/20
1.31.3
293717O-029 E
80/20
1.1951.195
293771O-035 E
80/20
1.6711.671
294392P-010 E
80/20
4.9014.901
294401BSHIL;1U E
80/20
2.0852.085
294410BSHIL;2U E
80/20
2.0852.085
294763P-046 E
80/20
2.3082.308
295109WESTBROOK E
80/20
1.3751.375
295111SUBLETTE E
80/20
0.6680.668
917502Z2-087 E
80/20
3.9533.953
918052AA1-018 E OP
80/20
3.793.79
925581AC1-033 C
80/20
0.5470.547
925582AC1-033 E
80/20
3.6613.661
934721AD1-100 C
80/20
4.5344.534
934722AD1-100 E
80/20
70.52170.521
937001AD2-134 C
80/20
0.9950.995
937002AD2-134 E
80/20
3.9763.976
942111AE2-223 C
80/20
1.4181.418
942112AE2-223 E
80/20
9.4879.487
957331AF2-027 C
80/20
2.4722.472
957332AF2-027 E
80/20
3.7083.708
959351AF2-226 C
80/20
2.8532.853
959352AF2-226 E
80/20
4.284.28
959611AF2-252 C
80/20
1.721.72
959612AF2-252 E
80/20
2.582.58
960281AF2-319 C
80/20
2.8532.853
960282AF2-319 E
80/20
4.284.28
960611AF2-352 C
80/20
1.721.72
960612AF2-352 E
80/20
2.582.58
962012AG1-044 E
80/20
0.0540.054
966091AG1-478 C
80/20
0.4850.485
966092AG1-478 E
80/20
0.7280.728
966441AG1-513 C
80/20
0.5010.501
966442AG1-513 E
80/20
0.7520.752
274674JOLIET 9 ;6U
80/20
15.24915.249
274675JOLIET 29;7U
80/20
44.03844.038
274676JOLIET 29;8U
80/20
44.06544.065
274682WAUKEGAN ;7U
80/20
18.42518.425
274683WAUKEGAN ;8U
80/20
19.85719.857
274687WILL CNTY;4U
80/20
41.59241.592
274890CAYUG;1U E
80/20
3.2643.264
274891CAYUG;2U E
80/20
3.2643.264
925771AC1-053 C
80/20
0.70.7
925772AC1-053 E
80/20
4.6814.681
938851AE1-113 C
80/20
6.4186.418
938852AE1-113 E
80/20
22.75422.754
939401AE1-172 C
80/20
4.0924.092
939402AE1-172 E
80/20
19.1619.16
942651AE2-281 C
80/20
0.6470.647
942652AE2-281 E
80/20
3.9763.976
957382AF2-032 E
80/20
0.1170.117
270681BRIGHTSTK; R
80/20
0.5910.591
270839OTTER CRK; R
80/20
0.5660.566
274881WALNUT RG;1U
80/20
1.1461.146
275149KELLYCK ;1E
80/20
3.9663.966
276174W4-005 E
80/20
4.4614.461
276602WESTBROOK C
80/20
0.2080.208
276603SUBLETTE C
80/20
0.0940.094
276626AG1-044 E
80/20
0.0610.061
276627AG1-044 BAT
80/20
0.0110.011
276645AC1-214 C1
80/20
0.2230.223
276646AC1-214 C2
80/20
0.2230.223
276655AB2-047 C1
80/20
0.3690.369
276656AB2-047 C2
80/20
0.3690.369
276668AB2-070 C
80/20
0.4440.444
276675AE2-062 E
80/20
0.1250.125
293516O-009 E
80/20
4.5854.585
293519PILOT HIL;1E
80/20
3.9663.966
916212CRESCENT ;1U
80/20
1.1741.174
916221Z1-073 E
80/20
1.8091.809
924048AB2-047 E1
80/20
2.4512.451
924049AB2-047 E2
80/20
2.492.49
924266AB2-070 E
80/20
2.692.69
926821AC1-168 C
80/20
0.8910.891
926822AC1-168 E
80/20
5.9825.982
927208AC1-214 E1
80/20
0.7920.792
927209AC1-214 E2
80/20
0.7920.792
935141AD1-148 C
80/20
0.9450.945
936371AD2-047 C
80/20
3.0823.082
936372AD2-047 E
80/20
15.04615.046
938861AE1-114 C
80/20
3.0753.075
938862AE1-114 E
80/20
10.49110.491
939321AE1-163 C
80/20
4.5314.531
939322AE1-163 E
80/20
27.83427.834
942421AE2-255 C
80/20
2.4312.431
942422AE2-255 E
80/20
7.2937.293
946321AF1-296 C
80/20
2.7622.762
946322AF1-296 E
80/20
12.93112.931
957371AF2-031 C
80/20
0.470.47
957372AF2-031 E
80/20
0.7050.705
960261AF2-317 C
80/20
0.4080.408
961501AF2-441 C
80/20
6.2416.241
961502AF2-441 E
80/20
9.3619.361
965331AG1-398 C
80/20
0.2010.201
990901L-005 E
80/20
3.0863.086
276170Z1-108 E
80/20
2.4582.458
920272AA2-123 E
80/20
2.4072.407
965913AG1-460 BT
80/20
0.0060.006
990052J1200
External Queue
0.43040.4304
990512J1326 G
External Queue
5.43125.4312
990947J1432 G
External Queue
6.13376.1337
991302J1755
External Queue
9.86249.8624

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.23 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1472.14
MW Contribution:7.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
50/50
0.8770.877
274861TOP CROP ;1U
50/50
0.6530.653
274862TOP CROP ;2U
50/50
1.2461.246
274871GR RIDGE ;2U
50/50
0.3260.326
274879MINONK ;1U
50/50
1.211.21
290021O50 E
50/50
4.844.84
293061N-015 E
50/50
3.8393.839
293644O22 E1
50/50
4.084.08
293645O22 E2
50/50
4.6734.673
294392P-010 E
50/50
4.8764.876
934721AD1-100 C
50/50
4.5094.509
934722AD1-100 E
50/50
70.13470.134
942111AE2-223 C
Adder
1.41647058823529411.204
942112AE2-223 E
Adder
9.4776470588235288.056
957331AF2-027 C
50/50
2.462.46
957332AF2-027 E
50/50
3.693.69
959351AF2-226 C
50/50
2.8412.841
959352AF2-226 E
50/50
4.2614.261
959611AF2-252 C
Adder
1.721.462
959612AF2-252 E
Adder
2.582.193
960281AF2-319 C
50/50
2.8412.841
960282AF2-319 E
50/50
4.2614.261
960611AF2-352 C
Adder
1.721.462
960612AF2-352 E
Adder
2.582.193
962012AG1-044 E
Adder
0.054117647058823530.046
966091AG1-478 C
50/50
0.4820.482
966092AG1-478 E
50/50
0.7240.724
966441AG1-513 C
50/50
0.4990.499
966442AG1-513 E
50/50
0.7480.748
274674JOLIET 9 ;6U
Adder
15.1576470588235312.884
274675JOLIET 29;7U
50/50
43.79843.798
274676JOLIET 29;8U
50/50
43.82443.824
274682WAUKEGAN ;7U
50/50
18.33318.333
274683WAUKEGAN ;8U
50/50
19.75819.758
274687WILL CNTY;4U
50/50
41.36241.362
938851AE1-113 C
50/50
6.3896.389
938852AE1-113 E
50/50
22.65322.653
939401AE1-172 C
Adder
4.0752941176470593.464
939402AE1-172 E
Adder
19.07882352941176416.217
942651AE2-281 C
Adder
0.64352941176470590.547
942652AE2-281 E
Adder
3.9564705882352943.363
957382AF2-032 E
Adder
0.117647058823529420.1
276626AG1-044 E
Adder
0.061176470588235290.052
276627AG1-044 BAT
Adder
0.0105882352941176470.009
276675AE2-062 E
50/50
0.1240.124
926821AC1-168 C
Adder
0.88823529411764710.755
926822AC1-168 E
Adder
5.9611764705882365.067
936371AD2-047 C
Adder
3.0611764705882352.602
936372AD2-047 E
Adder
14.94235294117647212.701
938861AE1-114 C
Adder
3.06235294117647072.603
938862AE1-114 E
Adder
10.4482352941176488.881
939321AE1-163 C
Adder
4.5094117647058833.833
939322AE1-163 E
Adder
27.69647058823529723.542
942421AE2-255 C
50/50
2.422.42
942422AE2-255 E
50/50
7.2617.261
944221AF1-090 C
Adder
1.41647058823529411.204
944222AF1-090 E
Adder
6.6294117647058825.635
946321AF1-296 C
Adder
2.7541176470588242.341
946322AF1-296 E
Adder
12.8905882352941210.957
957371AF2-031 C
Adder
0.462352941176470630.393
957372AF2-031 E
Adder
0.69294117647058820.589
961501AF2-441 C
Adder
6.16352941176470555.239
961502AF2-441 E
Adder
9.2458823529411777.859
276170Z1-108 E
50/50
2.4462.446
920272AA2-123 E
Adder
2.81764705882352962.395
965913AG1-460 BT
Adder
0.00588235294117647050.005
990052J1200
External Queue
0.42840.4284
990512J1326 G
External Queue
5.40125.4012
990947J1432 G
External Queue
15.277515.2775
991092J1477
External Queue
2.87522.8752
991302J1755
External Queue
9.81979.8197

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.33 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1459.57
MW Contribution:7.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
50/50
0.8810.881
274861TOP CROP ;1U
50/50
0.6560.656
274862TOP CROP ;2U
50/50
1.2521.252
274871GR RIDGE ;2U
50/50
0.3280.328
274879MINONK ;1U
50/50
1.2161.216
290021O50 E
50/50
4.8644.864
293061N-015 E
50/50
3.863.86
293644O22 E1
50/50
4.0984.098
293645O22 E2
50/50
4.6944.694
294392P-010 E
50/50
4.9034.903
934721AD1-100 C
50/50
4.5314.531
934722AD1-100 E
50/50
70.47670.476
942111AE2-223 C
Adder
1.41764705882352951.205
942112AE2-223 E
Adder
9.4870588235294138.064
957331AF2-027 C
50/50
2.4742.474
957332AF2-027 E
50/50
3.713.71
959351AF2-226 C
50/50
2.8532.853
959352AF2-226 E
50/50
4.284.28
959611AF2-252 C
Adder
1.721.462
959612AF2-252 E
Adder
2.582.193
960281AF2-319 C
50/50
2.8532.853
960282AF2-319 E
50/50
4.284.28
960611AF2-352 C
Adder
1.721.462
960612AF2-352 E
Adder
2.582.193
962012AG1-044 E
Adder
0.054117647058823530.046
966091AG1-478 C
50/50
0.4850.485
966092AG1-478 E
50/50
0.7280.728
966441AG1-513 C
50/50
0.5020.502
966442AG1-513 E
50/50
0.7530.753
274674JOLIET 9 ;6U
Adder
15.25411764705882312.966
274675JOLIET 29;7U
50/50
44.05244.052
274676JOLIET 29;8U
50/50
44.07844.078
274682WAUKEGAN ;7U
50/50
18.43518.435
274683WAUKEGAN ;8U
50/50
19.86819.868
274687WILL CNTY;4U
50/50
41.59841.598
938851AE1-113 C
50/50
6.426.42
938852AE1-113 E
50/50
22.76222.762
939401AE1-172 C
Adder
4.0905882352941183.477
939402AE1-172 E
Adder
19.15176470588235316.279
942651AE2-281 C
Adder
0.64705882352941180.55
942652AE2-281 E
Adder
3.9764705882352943.38
957382AF2-032 E
Adder
0.117647058823529420.1
276626AG1-044 E
Adder
0.061176470588235290.052
276627AG1-044 BAT
Adder
0.0105882352941176470.009
276675AE2-062 E
50/50
0.1250.125
926821AC1-168 C
Adder
0.8917647058823530.758
926822AC1-168 E
Adder
5.9847058823529415.087
936371AD2-047 C
Adder
3.08117647058823562.619
936372AD2-047 E
Adder
15.04117647058823512.785
938861AE1-114 C
Adder
3.07647058823529432.615
938862AE1-114 E
Adder
10.497647058823538.923
939321AE1-163 C
Adder
4.53176470588235253.852
939322AE1-163 E
Adder
27.83882352941176623.663
942421AE2-255 C
50/50
2.4322.432
942422AE2-255 E
50/50
7.2957.295
946321AF1-296 C
Adder
2.7635294117647062.349
946322AF1-296 E
Adder
12.93882352941176410.998
957371AF2-031 C
Adder
0.46941176470588240.399
957372AF2-031 E
Adder
0.70470588235294120.599
961501AF2-441 C
Adder
6.2364705882352955.301
961502AF2-441 E
Adder
9.3552941176470597.952
276170Z1-108 E
50/50
2.462.46
920272AA2-123 E
Adder
2.83294117647058832.408
965913AG1-460 BT
Adder
0.00588235294117647050.005
990052J1200
External Queue
0.43050.4305
990512J1326 G
External Queue
5.4355.435
990947J1432 G
External Queue
15.3515.35
991092J1477
External Queue
2.88632.8863
991302J1755
External Queue
9.86539.8653

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.15 %
Rating:1091.0 MVA
Rating Type:A
MVA to Mitigate:1114.47
MW Contribution:5.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.5850.585
274848CAMPGROVE;RU
80/20
0.2240.224
274849CRESCENT ;1U
80/20
0.170.17
274850MENDOTA H;RU
80/20
0.2770.277
274851PROVIDENC;RU
80/20
0.1810.181
274853TWINGROVE;U1
80/20
0.4870.487
274854TWINGROVE;U2
80/20
0.5010.501
274855GSG-6 ;RU
80/20
0.4210.421
274856ECOGROVE ;U1
80/20
0.3680.368
274857BIG SKY ;U1
80/20
0.2820.282
274858BIG SKY ;U2
80/20
0.2820.282
274859EASYR;U1 E
80/20
1.9441.944
274860EASYR;U2 E
80/20
1.9441.944
274861TOP CROP ;1U
80/20
0.4840.484
274862TOP CROP ;2U
80/20
0.9230.923
274863CAYUGA RI;1U
80/20
0.4010.401
274864CAYUGA RI;2U
80/20
0.4010.401
274871GR RIDGE ;2U
80/20
0.2180.218
274872LEE DEKAL;1U
80/20
0.7810.781
274877BISHOP HL;1U
80/20
0.3490.349
274878BISHOP HL;2U
80/20
0.3490.349
274879MINONK ;1U
80/20
0.8370.837
274887PILOT HIL;1U
80/20
0.6450.645
274888KELLY CRK;1U
80/20
0.6450.645
276156O-029 C
80/20
0.1990.199
276157O-029 C
80/20
0.3590.359
276158O-029 C
80/20
0.3590.359
290021O50 E
80/20
3.3493.349
290051GSG-6; E
80/20
1.6851.685
290108LEEDK;1U E
80/20
3.8583.858
290261S-027 E
80/20
2.2852.285
290265S-028 E
80/20
2.2712.271
293061N-015 E
80/20
2.5612.561
293644O22 E1
80/20
3.0223.022
293645O22 E2
80/20
3.4613.461
293715O-029 E
80/20
1.5751.575
293716O-029 E
80/20
0.8640.864
293717O-029 E
80/20
0.7940.794
293771O-035 E
80/20
1.1181.118
294392P-010 E
80/20
3.2533.253
294401BSHIL;1U E
80/20
1.3951.395
294410BSHIL;2U E
80/20
1.3951.395
294763P-046 E
80/20
1.5291.529
295109WESTBROOK E
80/20
0.9020.902
295111SUBLETTE E
80/20
0.4390.439
917502Z2-087 E
80/20
2.5752.575
918052AA1-018 E OP
80/20
2.5632.563
925581AC1-033 C
80/20
0.3660.366
925582AC1-033 E
80/20
2.4492.449
934721AD1-100 C
80/20
2.9882.988
934722AD1-100 E
80/20
46.47446.474
937001AD2-134 C
80/20
0.6530.653
937002AD2-134 E
80/20
2.612.61
942111AE2-223 C
80/20
0.9230.923
942112AE2-223 E
80/20
6.1816.181
957331AF2-027 C
80/20
1.6591.659
957332AF2-027 E
80/20
2.4882.488
959351AF2-226 C
80/20
2.1042.104
959352AF2-226 E
80/20
3.1563.156
959611AF2-252 C
80/20
1.121.12
959612AF2-252 E
80/20
1.681.68
960281AF2-319 C
80/20
2.1042.104
960282AF2-319 E
80/20
3.1563.156
960611AF2-352 C
80/20
1.121.12
960612AF2-352 E
80/20
1.681.68
962012AG1-044 E
80/20
0.0360.036
966091AG1-478 C
80/20
0.3250.325
966092AG1-478 E
80/20
0.4880.488
966441AG1-513 C
80/20
0.3280.328
966442AG1-513 E
80/20
0.4920.492
274674JOLIET 9 ;6U
80/20
10.08310.083
274675JOLIET 29;7U
80/20
30.56830.568
274676JOLIET 29;8U
80/20
30.59430.594
274682WAUKEGAN ;7U
80/20
12.37312.373
274683WAUKEGAN ;8U
80/20
13.33213.332
274687WILL CNTY;4U
80/20
29.39129.391
274890CAYUG;1U E
80/20
2.1372.137
274891CAYUG;2U E
80/20
2.1372.137
938851AE1-113 C
80/20
4.424.42
938852AE1-113 E
80/20
15.67215.672
939401AE1-172 C
80/20
2.6832.683
939402AE1-172 E
80/20
12.56312.563
942651AE2-281 C
80/20
0.440.44
942652AE2-281 E
80/20
2.7032.703
270681BRIGHTSTK; R
80/20
0.3850.385
270839OTTER CRK; R
80/20
0.3830.383
274881WALNUT RG;1U
80/20
0.7610.761
275149KELLYCK ;1E
80/20
2.5792.579
276602WESTBROOK C
80/20
0.1370.137
276603SUBLETTE C
80/20
0.0620.062
276626AG1-044 E
80/20
0.0410.041
276627AG1-044 BAT
80/20
0.0070.007
276645AC1-214 C1
80/20
0.1490.149
276646AC1-214 C2
80/20
0.1490.149
276655AB2-047 C1
80/20
0.240.24
276656AB2-047 C2
80/20
0.240.24
276675AE2-062 E
80/20
0.0850.085
293516O-009 E
80/20
3.0453.045
293519PILOT HIL;1E
80/20
2.5792.579
916212CRESCENT ;1U
80/20
0.7850.785
916221Z1-073 E
80/20
1.1881.188
924048AB2-047 E1
80/20
1.5971.597
924049AB2-047 E2
80/20
1.6221.622
926821AC1-168 C
80/20
0.5960.596
926822AC1-168 E
80/20
44
927208AC1-214 E1
80/20
0.530.53
927209AC1-214 E2
80/20
0.530.53
936371AD2-047 C
80/20
2.0042.004
936372AD2-047 E
80/20
9.7859.785
938861AE1-114 C
80/20
2.0372.037
938862AE1-114 E
80/20
6.9496.949
939321AE1-163 C
80/20
3.083.08
939322AE1-163 E
80/20
18.9218.92
942421AE2-255 C
80/20
1.6741.674
942422AE2-255 E
80/20
5.0235.023
946321AF1-296 C
80/20
1.8341.834
946322AF1-296 E
80/20
8.5868.586
990901L-005 E
80/20
2.0672.067
276170Z1-108 E
80/20
1.6321.632
920272AA2-123 E
80/20
1.5961.596

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.61 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1631.33
MW Contribution:7.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.8810.881
274848CAMPGROVE;RU
80/20
0.3340.334
274849CRESCENT ;1U
80/20
0.2550.255
274850MENDOTA H;RU
80/20
0.4220.422
274851PROVIDENC;RU
80/20
0.270.27
274853TWINGROVE;U1
80/20
0.7480.748
274854TWINGROVE;U2
80/20
0.770.77
274855GSG-6 ;RU
80/20
0.6420.642
274856ECOGROVE ;U1
80/20
0.5550.555
274857BIG SKY ;U1
80/20
0.4250.425
274858BIG SKY ;U2
80/20
0.4250.425
274859EASYR;U1 E
80/20
2.9342.934
274860EASYR;U2 E
80/20
2.9342.934
274861TOP CROP ;1U
80/20
0.6560.656
274862TOP CROP ;2U
80/20
1.2521.252
274863CAYUGA RI;1U
80/20
0.6120.612
274864CAYUGA RI;2U
80/20
0.6120.612
274871GR RIDGE ;2U
80/20
0.3280.328
274872LEE DEKAL;1U
80/20
1.1941.194
274877BISHOP HL;1U
80/20
0.5210.521
274878BISHOP HL;2U
80/20
0.5210.521
274879MINONK ;1U
80/20
1.2161.216
274880RADFORD R;1U
80/20
0.7810.781
274887PILOT HIL;1U
80/20
0.9910.991
274888KELLY CRK;1U
80/20
0.9910.991
276156O-029 C
80/20
0.30.3
276157O-029 C
80/20
0.5410.541
276158O-029 C
80/20
0.5410.541
276615W2-048 GEN
80/20
1.0561.056
276621X2-022 GEN
80/20
3.0063.006
290021O50 E
80/20
4.8624.862
290051GSG-6; E
80/20
2.5672.567
290108LEEDK;1U E
80/20
5.8935.893
290261S-027 E
80/20
3.5093.509
290265S-028 E
80/20
3.4883.488
293061N-015 E
80/20
3.8593.859
293644O22 E1
80/20
4.0984.098
293645O22 E2
80/20
4.6944.694
293715O-029 E
80/20
2.3712.371
293716O-029 E
80/20
1.31.3
293717O-029 E
80/20
1.1951.195
293771O-035 E
80/20
1.6711.671
294392P-010 E
80/20
4.9014.901
294401BSHIL;1U E
80/20
2.0852.085
294410BSHIL;2U E
80/20
2.0852.085
294763P-046 E
80/20
2.3082.308
295109WESTBROOK E
80/20
1.3751.375
295111SUBLETTE E
80/20
0.6680.668
917502Z2-087 E
80/20
3.9533.953
918052AA1-018 E OP
80/20
3.793.79
925581AC1-033 C
80/20
0.5470.547
925582AC1-033 E
80/20
3.6613.661
934721AD1-100 C
80/20
4.5344.534
934722AD1-100 E
80/20
70.52170.521
937001AD2-134 C
80/20
0.9950.995
937002AD2-134 E
80/20
3.9763.976
942111AE2-223 C
80/20
1.4181.418
942112AE2-223 E
80/20
9.4879.487
957331AF2-027 C
80/20
2.4722.472
957332AF2-027 E
80/20
3.7083.708
959351AF2-226 C
80/20
2.8532.853
959352AF2-226 E
80/20
4.284.28
959611AF2-252 C
80/20
1.721.72
959612AF2-252 E
80/20
2.582.58
960281AF2-319 C
80/20
2.8532.853
960282AF2-319 E
80/20
4.284.28
960611AF2-352 C
80/20
1.721.72
960612AF2-352 E
80/20
2.582.58
962012AG1-044 E
80/20
0.0540.054
966091AG1-478 C
80/20
0.4850.485
966092AG1-478 E
80/20
0.7280.728
966441AG1-513 C
80/20
0.5010.501
966442AG1-513 E
80/20
0.7520.752
274674JOLIET 9 ;6U
80/20
15.24915.249
274675JOLIET 29;7U
80/20
44.03844.038
274676JOLIET 29;8U
80/20
44.06544.065
274682WAUKEGAN ;7U
80/20
18.42518.425
274683WAUKEGAN ;8U
80/20
19.85719.857
274687WILL CNTY;4U
80/20
41.59241.592
274890CAYUG;1U E
80/20
3.2643.264
274891CAYUG;2U E
80/20
3.2643.264
925771AC1-053 C
80/20
0.70.7
925772AC1-053 E
80/20
4.6814.681
938851AE1-113 C
80/20
6.4186.418
938852AE1-113 E
80/20
22.75422.754
939401AE1-172 C
80/20
4.0924.092
939402AE1-172 E
80/20
19.1619.16
942651AE2-281 C
80/20
0.6470.647
942652AE2-281 E
80/20
3.9763.976
957382AF2-032 E
80/20
0.1170.117
270681BRIGHTSTK; R
80/20
0.5910.591
270839OTTER CRK; R
80/20
0.5660.566
274881WALNUT RG;1U
80/20
1.1461.146
275149KELLYCK ;1E
80/20
3.9663.966
276174W4-005 E
80/20
4.4614.461
276602WESTBROOK C
80/20
0.2080.208
276603SUBLETTE C
80/20
0.0940.094
276626AG1-044 E
80/20
0.0610.061
276627AG1-044 BAT
80/20
0.0110.011
276645AC1-214 C1
80/20
0.2230.223
276646AC1-214 C2
80/20
0.2230.223
276655AB2-047 C1
80/20
0.3690.369
276656AB2-047 C2
80/20
0.3690.369
276668AB2-070 C
80/20
0.4440.444
276675AE2-062 E
80/20
0.1250.125
293516O-009 E
80/20
4.5854.585
293519PILOT HIL;1E
80/20
3.9663.966
916212CRESCENT ;1U
80/20
1.1741.174
916221Z1-073 E
80/20
1.8091.809
924048AB2-047 E1
80/20
2.4512.451
924049AB2-047 E2
80/20
2.492.49
924266AB2-070 E
80/20
2.692.69
926821AC1-168 C
80/20
0.8910.891
926822AC1-168 E
80/20
5.9825.982
927208AC1-214 E1
80/20
0.7920.792
927209AC1-214 E2
80/20
0.7920.792
935141AD1-148 C
80/20
0.9450.945
936371AD2-047 C
80/20
3.0823.082
936372AD2-047 E
80/20
15.04615.046
938861AE1-114 C
80/20
3.0753.075
938862AE1-114 E
80/20
10.49110.491
939321AE1-163 C
80/20
4.5314.531
939322AE1-163 E
80/20
27.83427.834
942421AE2-255 C
80/20
2.4312.431
942422AE2-255 E
80/20
7.2937.293
946321AF1-296 C
80/20
2.7622.762
946322AF1-296 E
80/20
12.93112.931
957371AF2-031 C
80/20
0.470.47
957372AF2-031 E
80/20
0.7050.705
960261AF2-317 C
80/20
0.4080.408
961501AF2-441 C
80/20
6.2416.241
961502AF2-441 E
80/20
9.3619.361
965331AG1-398 C
80/20
0.2010.201
990901L-005 E
80/20
3.0863.086
276170Z1-108 E
80/20
2.4582.458
920272AA2-123 E
80/20
2.4072.407
965913AG1-460 BT
80/20
0.0060.006
990052J1200
External Queue
0.43040.4304
990512J1326 G
External Queue
5.43125.4312
990947J1432 G
External Queue
6.13376.1337
991302J1755
External Queue
9.86249.8624

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.42 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1628.71
MW Contribution:7.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.8810.881
274848CAMPGROVE;RU
80/20
0.3340.334
274849CRESCENT ;1U
80/20
0.2550.255
274850MENDOTA H;RU
80/20
0.4220.422
274851PROVIDENC;RU
80/20
0.270.27
274853TWINGROVE;U1
80/20
0.7480.748
274854TWINGROVE;U2
80/20
0.770.77
274855GSG-6 ;RU
80/20
0.6420.642
274856ECOGROVE ;U1
80/20
0.5550.555
274857BIG SKY ;U1
80/20
0.4250.425
274858BIG SKY ;U2
80/20
0.4250.425
274859EASYR;U1 E
80/20
2.9342.934
274860EASYR;U2 E
80/20
2.9342.934
274861TOP CROP ;1U
80/20
0.6560.656
274862TOP CROP ;2U
80/20
1.2521.252
274863CAYUGA RI;1U
80/20
0.6120.612
274864CAYUGA RI;2U
80/20
0.6120.612
274871GR RIDGE ;2U
80/20
0.3280.328
274872LEE DEKAL;1U
80/20
1.1941.194
274877BISHOP HL;1U
80/20
0.5210.521
274878BISHOP HL;2U
80/20
0.5210.521
274879MINONK ;1U
80/20
1.2161.216
274880RADFORD R;1U
80/20
0.7810.781
274887PILOT HIL;1U
80/20
0.9910.991
274888KELLY CRK;1U
80/20
0.9910.991
276156O-029 C
80/20
0.30.3
276157O-029 C
80/20
0.5410.541
276158O-029 C
80/20
0.5410.541
276615W2-048 GEN
80/20
1.0561.056
276621X2-022 GEN
80/20
3.0063.006
290021O50 E
80/20
4.8624.862
290051GSG-6; E
80/20
2.5672.567
290108LEEDK;1U E
80/20
5.8935.893
290261S-027 E
80/20
3.5093.509
290265S-028 E
80/20
3.4883.488
293061N-015 E
80/20
3.8593.859
293644O22 E1
80/20
4.0984.098
293645O22 E2
80/20
4.6944.694
293715O-029 E
80/20
2.3712.371
293716O-029 E
80/20
1.31.3
293717O-029 E
80/20
1.1951.195
293771O-035 E
80/20
1.6711.671
294392P-010 E
80/20
4.9014.901
294401BSHIL;1U E
80/20
2.0852.085
294410BSHIL;2U E
80/20
2.0852.085
294763P-046 E
80/20
2.3082.308
295109WESTBROOK E
80/20
1.3751.375
295111SUBLETTE E
80/20
0.6680.668
917502Z2-087 E
80/20
3.9533.953
918052AA1-018 E OP
80/20
3.793.79
925581AC1-033 C
80/20
0.5470.547
925582AC1-033 E
80/20
3.6613.661
934721AD1-100 C
80/20
4.5344.534
934722AD1-100 E
80/20
70.52170.521
937001AD2-134 C
80/20
0.9950.995
937002AD2-134 E
80/20
3.9763.976
942111AE2-223 C
80/20
1.4181.418
942112AE2-223 E
80/20
9.4879.487
957331AF2-027 C
80/20
2.4722.472
957332AF2-027 E
80/20
3.7083.708
959351AF2-226 C
80/20
2.8532.853
959352AF2-226 E
80/20
4.284.28
959611AF2-252 C
80/20
1.721.72
959612AF2-252 E
80/20
2.582.58
960281AF2-319 C
80/20
2.8532.853
960282AF2-319 E
80/20
4.284.28
960611AF2-352 C
80/20
1.721.72
960612AF2-352 E
80/20
2.582.58
962012AG1-044 E
80/20
0.0540.054
966091AG1-478 C
80/20
0.4850.485
966092AG1-478 E
80/20
0.7280.728
966441AG1-513 C
80/20
0.5010.501
966442AG1-513 E
80/20
0.7520.752
274674JOLIET 9 ;6U
80/20
15.24915.249
274675JOLIET 29;7U
80/20
44.03844.038
274676JOLIET 29;8U
80/20
44.06544.065
274682WAUKEGAN ;7U
80/20
18.42518.425
274683WAUKEGAN ;8U
80/20
19.85719.857
274687WILL CNTY;4U
80/20
41.59241.592
274890CAYUG;1U E
80/20
3.2643.264
274891CAYUG;2U E
80/20
3.2643.264
925771AC1-053 C
80/20
0.70.7
925772AC1-053 E
80/20
4.6814.681
938851AE1-113 C
80/20
6.4186.418
938852AE1-113 E
80/20
22.75422.754
939401AE1-172 C
80/20
4.0924.092
939402AE1-172 E
80/20
19.1619.16
942651AE2-281 C
80/20
0.6470.647
942652AE2-281 E
80/20
3.9763.976
957382AF2-032 E
80/20
0.1170.117
270681BRIGHTSTK; R
80/20
0.5910.591
270839OTTER CRK; R
80/20
0.5660.566
274881WALNUT RG;1U
80/20
1.1461.146
275149KELLYCK ;1E
80/20
3.9663.966
276174W4-005 E
80/20
4.4614.461
276602WESTBROOK C
80/20
0.2080.208
276603SUBLETTE C
80/20
0.0940.094
276626AG1-044 E
80/20
0.0610.061
276627AG1-044 BAT
80/20
0.0110.011
276645AC1-214 C1
80/20
0.2230.223
276646AC1-214 C2
80/20
0.2230.223
276655AB2-047 C1
80/20
0.3690.369
276656AB2-047 C2
80/20
0.3690.369
276668AB2-070 C
80/20
0.4440.444
276675AE2-062 E
80/20
0.1250.125
293516O-009 E
80/20
4.5854.585
293519PILOT HIL;1E
80/20
3.9663.966
916212CRESCENT ;1U
80/20
1.1741.174
916221Z1-073 E
80/20
1.8091.809
924048AB2-047 E1
80/20
2.4512.451
924049AB2-047 E2
80/20
2.492.49
924266AB2-070 E
80/20
2.692.69
926821AC1-168 C
80/20
0.8910.891
926822AC1-168 E
80/20
5.9825.982
927208AC1-214 E1
80/20
0.7920.792
927209AC1-214 E2
80/20
0.7920.792
935141AD1-148 C
80/20
0.9450.945
936371AD2-047 C
80/20
3.0823.082
936372AD2-047 E
80/20
15.04615.046
938861AE1-114 C
80/20
3.0753.075
938862AE1-114 E
80/20
10.49110.491
939321AE1-163 C
80/20
4.5314.531
939322AE1-163 E
80/20
27.83427.834
942421AE2-255 C
80/20
2.4312.431
942422AE2-255 E
80/20
7.2937.293
946321AF1-296 C
80/20
2.7622.762
946322AF1-296 E
80/20
12.93112.931
957371AF2-031 C
80/20
0.470.47
957372AF2-031 E
80/20
0.7050.705
960261AF2-317 C
80/20
0.4080.408
961501AF2-441 C
80/20
6.2416.241
961502AF2-441 E
80/20
9.3619.361
965331AG1-398 C
80/20
0.2010.201
990901L-005 E
80/20
3.0863.086
276170Z1-108 E
80/20
2.4582.458
920272AA2-123 E
80/20
2.4072.407
965913AG1-460 BT
80/20
0.0060.006
990052J1200
External Queue
0.43040.4304
990512J1326 G
External Queue
5.43125.4312
990947J1432 G
External Queue
6.13376.1337
991302J1755
External Queue
9.86249.8624

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.23 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1472.21
MW Contribution:7.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
50/50
0.8770.877
274861TOP CROP ;1U
50/50
0.6530.653
274862TOP CROP ;2U
50/50
1.2461.246
274871GR RIDGE ;2U
50/50
0.3260.326
274879MINONK ;1U
50/50
1.211.21
290021O50 E
50/50
4.844.84
293061N-015 E
50/50
3.8393.839
293644O22 E1
50/50
4.084.08
293645O22 E2
50/50
4.6734.673
294392P-010 E
50/50
4.8764.876
934721AD1-100 C
50/50
4.5094.509
934722AD1-100 E
50/50
70.13470.134
942111AE2-223 C
Adder
1.41647058823529411.204
942112AE2-223 E
Adder
9.4776470588235288.056
957331AF2-027 C
50/50
2.462.46
957332AF2-027 E
50/50
3.693.69
959351AF2-226 C
50/50
2.8412.841
959352AF2-226 E
50/50
4.2614.261
959611AF2-252 C
Adder
1.721.462
959612AF2-252 E
Adder
2.582.193
960281AF2-319 C
50/50
2.8412.841
960282AF2-319 E
50/50
4.2614.261
960611AF2-352 C
Adder
1.721.462
960612AF2-352 E
Adder
2.582.193
962012AG1-044 E
Adder
0.054117647058823530.046
966091AG1-478 C
50/50
0.4820.482
966092AG1-478 E
50/50
0.7240.724
966441AG1-513 C
50/50
0.4990.499
966442AG1-513 E
50/50
0.7480.748
274674JOLIET 9 ;6U
Adder
15.1576470588235312.884
274675JOLIET 29;7U
50/50
43.79843.798
274676JOLIET 29;8U
50/50
43.82443.824
274682WAUKEGAN ;7U
50/50
18.33318.333
274683WAUKEGAN ;8U
50/50
19.75819.758
274687WILL CNTY;4U
50/50
41.36241.362
938851AE1-113 C
50/50
6.3896.389
938852AE1-113 E
50/50
22.65322.653
939401AE1-172 C
Adder
4.0752941176470593.464
939402AE1-172 E
Adder
19.07882352941176416.217
942651AE2-281 C
Adder
0.64352941176470590.547
942652AE2-281 E
Adder
3.9564705882352943.363
957382AF2-032 E
Adder
0.117647058823529420.1
276626AG1-044 E
Adder
0.061176470588235290.052
276627AG1-044 BAT
Adder
0.0105882352941176470.009
276675AE2-062 E
50/50
0.1240.124
926821AC1-168 C
Adder
0.88823529411764710.755
926822AC1-168 E
Adder
5.9611764705882365.067
936371AD2-047 C
Adder
3.0611764705882352.602
936372AD2-047 E
Adder
14.94235294117647212.701
938861AE1-114 C
Adder
3.06235294117647072.603
938862AE1-114 E
Adder
10.4482352941176488.881
939321AE1-163 C
Adder
4.5094117647058833.833
939322AE1-163 E
Adder
27.69647058823529723.542
942421AE2-255 C
50/50
2.422.42
942422AE2-255 E
50/50
7.2617.261
944221AF1-090 C
Adder
1.41647058823529411.204
944222AF1-090 E
Adder
6.6294117647058825.635
946321AF1-296 C
Adder
2.7541176470588242.341
946322AF1-296 E
Adder
12.8905882352941210.957
957371AF2-031 C
Adder
0.462352941176470630.393
957372AF2-031 E
Adder
0.69294117647058820.589
961501AF2-441 C
Adder
6.16352941176470555.239
961502AF2-441 E
Adder
9.2458823529411777.859
276170Z1-108 E
50/50
2.4462.446
920272AA2-123 E
Adder
2.81764705882352962.395
965913AG1-460 BT
Adder
0.00588235294117647050.005
990052J1200
External Queue
0.42840.4284
990512J1326 G
External Queue
5.40125.4012
990947J1432 G
External Queue
15.277515.2775
991092J1477
External Queue
2.87522.8752
991302J1755
External Queue
9.81979.8197

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.33 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1459.63
MW Contribution:7.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
50/50
0.8810.881
274861TOP CROP ;1U
50/50
0.6560.656
274862TOP CROP ;2U
50/50
1.2521.252
274871GR RIDGE ;2U
50/50
0.3280.328
274879MINONK ;1U
50/50
1.2161.216
290021O50 E
50/50
4.8644.864
293061N-015 E
50/50
3.863.86
293644O22 E1
50/50
4.0984.098
293645O22 E2
50/50
4.6944.694
294392P-010 E
50/50
4.9034.903
934721AD1-100 C
50/50
4.5314.531
934722AD1-100 E
50/50
70.47670.476
942111AE2-223 C
Adder
1.41764705882352951.205
942112AE2-223 E
Adder
9.4870588235294138.064
957331AF2-027 C
50/50
2.4742.474
957332AF2-027 E
50/50
3.713.71
959351AF2-226 C
50/50
2.8532.853
959352AF2-226 E
50/50
4.284.28
959611AF2-252 C
Adder
1.721.462
959612AF2-252 E
Adder
2.582.193
960281AF2-319 C
50/50
2.8532.853
960282AF2-319 E
50/50
4.284.28
960611AF2-352 C
Adder
1.721.462
960612AF2-352 E
Adder
2.582.193
962012AG1-044 E
Adder
0.054117647058823530.046
966091AG1-478 C
50/50
0.4850.485
966092AG1-478 E
50/50
0.7280.728
966441AG1-513 C
50/50
0.5020.502
966442AG1-513 E
50/50
0.7530.753
274674JOLIET 9 ;6U
Adder
15.25411764705882312.966
274675JOLIET 29;7U
50/50
44.05244.052
274676JOLIET 29;8U
50/50
44.07844.078
274682WAUKEGAN ;7U
50/50
18.43518.435
274683WAUKEGAN ;8U
50/50
19.86819.868
274687WILL CNTY;4U
50/50
41.59841.598
938851AE1-113 C
50/50
6.426.42
938852AE1-113 E
50/50
22.76222.762
939401AE1-172 C
Adder
4.0905882352941183.477
939402AE1-172 E
Adder
19.15176470588235316.279
942651AE2-281 C
Adder
0.64705882352941180.55
942652AE2-281 E
Adder
3.9764705882352943.38
957382AF2-032 E
Adder
0.117647058823529420.1
276626AG1-044 E
Adder
0.061176470588235290.052
276627AG1-044 BAT
Adder
0.0105882352941176470.009
276675AE2-062 E
50/50
0.1250.125
926821AC1-168 C
Adder
0.8917647058823530.758
926822AC1-168 E
Adder
5.9847058823529415.087
936371AD2-047 C
Adder
3.08117647058823562.619
936372AD2-047 E
Adder
15.04117647058823512.785
938861AE1-114 C
Adder
3.07647058823529432.615
938862AE1-114 E
Adder
10.497647058823538.923
939321AE1-163 C
Adder
4.53176470588235253.852
939322AE1-163 E
Adder
27.83882352941176623.663
942421AE2-255 C
50/50
2.4322.432
942422AE2-255 E
50/50
7.2957.295
946321AF1-296 C
Adder
2.7635294117647062.349
946322AF1-296 E
Adder
12.93882352941176410.998
957371AF2-031 C
Adder
0.46941176470588240.399
957372AF2-031 E
Adder
0.70470588235294120.599
961501AF2-441 C
Adder
6.2364705882352955.301
961502AF2-441 E
Adder
9.3552941176470597.952
276170Z1-108 E
50/50
2.462.46
920272AA2-123 E
Adder
2.83294117647058832.408
965913AG1-460 BT
Adder
0.00588235294117647050.005
990052J1200
External Queue
0.43050.4305
990512J1326 G
External Queue
5.4355.435
990947J1432 G
External Queue
15.3515.35
991092J1477
External Queue
2.88632.8863
991302J1755
External Queue
9.86539.8653

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.15 %
Rating:1091.0 MVA
Rating Type:A
MVA to Mitigate:1114.43
MW Contribution:5.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.5850.585
274848CAMPGROVE;RU
80/20
0.2240.224
274849CRESCENT ;1U
80/20
0.170.17
274850MENDOTA H;RU
80/20
0.2770.277
274851PROVIDENC;RU
80/20
0.1810.181
274853TWINGROVE;U1
80/20
0.4870.487
274854TWINGROVE;U2
80/20
0.5010.501
274855GSG-6 ;RU
80/20
0.4210.421
274856ECOGROVE ;U1
80/20
0.3680.368
274857BIG SKY ;U1
80/20
0.2820.282
274858BIG SKY ;U2
80/20
0.2820.282
274859EASYR;U1 E
80/20
1.9441.944
274860EASYR;U2 E
80/20
1.9441.944
274861TOP CROP ;1U
80/20
0.4840.484
274862TOP CROP ;2U
80/20
0.9230.923
274863CAYUGA RI;1U
80/20
0.4010.401
274864CAYUGA RI;2U
80/20
0.4010.401
274871GR RIDGE ;2U
80/20
0.2180.218
274872LEE DEKAL;1U
80/20
0.7810.781
274877BISHOP HL;1U
80/20
0.3490.349
274878BISHOP HL;2U
80/20
0.3490.349
274879MINONK ;1U
80/20
0.8370.837
274887PILOT HIL;1U
80/20
0.6450.645
274888KELLY CRK;1U
80/20
0.6450.645
276156O-029 C
80/20
0.1990.199
276157O-029 C
80/20
0.3590.359
276158O-029 C
80/20
0.3590.359
290021O50 E
80/20
3.3493.349
290051GSG-6; E
80/20
1.6851.685
290108LEEDK;1U E
80/20
3.8583.858
290261S-027 E
80/20
2.2852.285
290265S-028 E
80/20
2.2712.271
293061N-015 E
80/20
2.5612.561
293644O22 E1
80/20
3.0223.022
293645O22 E2
80/20
3.4613.461
293715O-029 E
80/20
1.5751.575
293716O-029 E
80/20
0.8640.864
293717O-029 E
80/20
0.7940.794
293771O-035 E
80/20
1.1181.118
294392P-010 E
80/20
3.2533.253
294401BSHIL;1U E
80/20
1.3951.395
294410BSHIL;2U E
80/20
1.3951.395
294763P-046 E
80/20
1.5291.529
295109WESTBROOK E
80/20
0.9020.902
295111SUBLETTE E
80/20
0.4390.439
917502Z2-087 E
80/20
2.5752.575
918052AA1-018 E OP
80/20
2.5632.563
925581AC1-033 C
80/20
0.3660.366
925582AC1-033 E
80/20
2.4492.449
934721AD1-100 C
80/20
2.9882.988
934722AD1-100 E
80/20
46.47446.474
937001AD2-134 C
80/20
0.6530.653
937002AD2-134 E
80/20
2.612.61
942111AE2-223 C
80/20
0.9230.923
942112AE2-223 E
80/20
6.1816.181
957331AF2-027 C
80/20
1.6591.659
957332AF2-027 E
80/20
2.4882.488
959351AF2-226 C
80/20
2.1042.104
959352AF2-226 E
80/20
3.1563.156
959611AF2-252 C
80/20
1.121.12
959612AF2-252 E
80/20
1.681.68
960281AF2-319 C
80/20
2.1042.104
960282AF2-319 E
80/20
3.1563.156
960611AF2-352 C
80/20
1.121.12
960612AF2-352 E
80/20
1.681.68
962012AG1-044 E
80/20
0.0360.036
966091AG1-478 C
80/20
0.3250.325
966092AG1-478 E
80/20
0.4880.488
966441AG1-513 C
80/20
0.3280.328
966442AG1-513 E
80/20
0.4920.492
274674JOLIET 9 ;6U
80/20
10.08310.083
274675JOLIET 29;7U
80/20
30.56830.568
274676JOLIET 29;8U
80/20
30.59430.594
274682WAUKEGAN ;7U
80/20
12.37312.373
274683WAUKEGAN ;8U
80/20
13.33213.332
274687WILL CNTY;4U
80/20
29.39129.391
274890CAYUG;1U E
80/20
2.1372.137
274891CAYUG;2U E
80/20
2.1372.137
938851AE1-113 C
80/20
4.424.42
938852AE1-113 E
80/20
15.67215.672
939401AE1-172 C
80/20
2.6832.683
939402AE1-172 E
80/20
12.56312.563
942651AE2-281 C
80/20
0.440.44
942652AE2-281 E
80/20
2.7032.703
270681BRIGHTSTK; R
80/20
0.3850.385
270839OTTER CRK; R
80/20
0.3830.383
274881WALNUT RG;1U
80/20
0.7610.761
275149KELLYCK ;1E
80/20
2.5792.579
276602WESTBROOK C
80/20
0.1370.137
276603SUBLETTE C
80/20
0.0620.062
276626AG1-044 E
80/20
0.0410.041
276627AG1-044 BAT
80/20
0.0070.007
276645AC1-214 C1
80/20
0.1490.149
276646AC1-214 C2
80/20
0.1490.149
276655AB2-047 C1
80/20
0.240.24
276656AB2-047 C2
80/20
0.240.24
276675AE2-062 E
80/20
0.0850.085
293516O-009 E
80/20
3.0453.045
293519PILOT HIL;1E
80/20
2.5792.579
916212CRESCENT ;1U
80/20
0.7850.785
916221Z1-073 E
80/20
1.1881.188
924048AB2-047 E1
80/20
1.5971.597
924049AB2-047 E2
80/20
1.6221.622
926821AC1-168 C
80/20
0.5960.596
926822AC1-168 E
80/20
44
927208AC1-214 E1
80/20
0.530.53
927209AC1-214 E2
80/20
0.530.53
936371AD2-047 C
80/20
2.0042.004
936372AD2-047 E
80/20
9.7859.785
938861AE1-114 C
80/20
2.0372.037
938862AE1-114 E
80/20
6.9496.949
939321AE1-163 C
80/20
3.083.08
939322AE1-163 E
80/20
18.9218.92
942421AE2-255 C
80/20
1.6741.674
942422AE2-255 E
80/20
5.0235.023
946321AF1-296 C
80/20
1.8341.834
946322AF1-296 E
80/20
8.5868.586
990901L-005 E
80/20
2.0672.067
276170Z1-108 E
80/20
1.6321.632
920272AA2-123 E
80/20
1.5961.596

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.46 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1178.14
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.730.73
274848CAMPGROVE;RU
80/20
0.2780.278
274849CRESCENT ;1U
80/20
0.2120.212
274850MENDOTA H;RU
80/20
0.3520.352
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274856ECOGROVE ;U1
80/20
0.4620.462
274857BIG SKY ;U1
80/20
0.3530.353
274858BIG SKY ;U2
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274860EASYR;U2 E
80/20
2.4372.437
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
274864CAYUGA RI;2U
80/20
0.5160.516
274871GR RIDGE ;2U
80/20
0.2720.272
274872LEE DEKAL;1U
80/20
0.9950.995
274877BISHOP HL;1U
80/20
0.4330.433
274878BISHOP HL;2U
80/20
0.4330.433
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274887PILOT HIL;1U
80/20
0.9460.946
274888KELLY CRK;1U
80/20
0.9460.946
276156O-029 C
80/20
0.2490.249
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
276615W2-048 GEN
80/20
0.8910.891
276621X2-022 GEN
80/20
2.5362.536
290021O50 E
80/20
3.9653.965
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
293061N-015 E
80/20
3.1963.196
293644O22 E1
80/20
2.822.82
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293716O-029 E
80/20
1.081.08
293717O-029 E
80/20
0.9930.993
293771O-035 E
80/20
1.3921.392
294392P-010 E
80/20
4.0594.059
294401BSHIL;1U E
80/20
1.7331.733
294410BSHIL;2U E
80/20
1.7331.733
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
295111SUBLETTE E
80/20
0.5570.557
917502Z2-087 E
80/20
3.3333.333
918052AA1-018 E OP
80/20
3.6223.622
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
934721AD1-100 C
80/20
3.8223.822
934722AD1-100 E
80/20
59.4559.45
937001AD2-134 C
80/20
0.8290.829
937002AD2-134 E
80/20
3.3123.312
942111AE2-223 C
80/20
1.1951.195
942112AE2-223 E
80/20
7.9997.999
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959351AF2-226 C
80/20
1.9641.964
959352AF2-226 E
80/20
2.9452.945
959611AF2-252 C
80/20
1.4511.451
959612AF2-252 E
80/20
2.1762.176
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
962012AG1-044 E
80/20
0.0450.045
966091AG1-478 C
80/20
0.4310.431
966092AG1-478 E
80/20
0.6470.647
966441AG1-513 C
80/20
0.4190.419
966442AG1-513 E
80/20
0.6290.629
274674JOLIET 9 ;6U
80/20
13.64413.644
274675JOLIET 29;7U
80/20
36.25136.251
274676JOLIET 29;8U
80/20
36.23736.237
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274687WILL CNTY;4U
80/20
32.59232.592
274890CAYUG;1U E
80/20
2.7522.752
274891CAYUG;2U E
80/20
2.7522.752
925771AC1-053 C
80/20
0.590.59
925772AC1-053 E
80/20
3.953.95
938851AE1-113 C
80/20
5.2345.234
938852AE1-113 E
80/20
18.55518.555
939401AE1-172 C
80/20
3.453.45
939402AE1-172 E
80/20
16.15416.154
942651AE2-281 C
80/20
0.5930.593
942652AE2-281 E
80/20
3.6423.642
270681BRIGHTSTK; R
80/20
0.4980.498
270839OTTER CRK; R
80/20
0.5410.541
274881WALNUT RG;1U
80/20
0.9520.952
275149KELLYCK ;1E
80/20
3.7863.786
276174W4-005 E
80/20
3.7663.766
276602WESTBROOK C
80/20
0.1730.173
276603SUBLETTE C
80/20
0.0780.078
276626AG1-044 E
80/20
0.0510.051
276627AG1-044 BAT
80/20
0.0090.009
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
276655AB2-047 C1
80/20
0.3110.311
276656AB2-047 C2
80/20
0.3110.311
276668AB2-070 C
80/20
0.3750.375
276675AE2-062 E
80/20
0.1120.112
293516O-009 E
80/20
3.8093.809
293519PILOT HIL;1E
80/20
3.7863.786
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
924048AB2-047 E1
80/20
2.0672.067
924049AB2-047 E2
80/20
2.0992.099
924266AB2-070 E
80/20
2.272.27
926821AC1-168 C
80/20
0.7420.742
926822AC1-168 E
80/20
4.9814.981
927208AC1-214 E1
80/20
0.660.66
927209AC1-214 E2
80/20
0.660.66
935141AD1-148 C
80/20
0.7970.797
936371AD2-047 C
80/20
2.9422.942
936372AD2-047 E
80/20
14.36514.365
938861AE1-114 C
80/20
2.5552.555
938862AE1-114 E
80/20
8.7168.716
939321AE1-163 C
80/20
4.1514.151
939322AE1-163 E
80/20
25.49625.496
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
946321AF1-296 C
80/20
2.2942.294
946322AF1-296 E
80/20
10.73910.739
957371AF2-031 C
80/20
0.6360.636
957372AF2-031 E
80/20
0.9540.954
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
961502AF2-441 E
80/20
10.40210.402
965331AG1-398 C
80/20
0.1690.169
990901L-005 E
80/20
2.5642.564
276170Z1-108 E
80/20
2.0422.042
920272AA2-123 E
80/20
22
965793AG1-447 BT
80/20
8.3248.324
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.2 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1175.66
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.730.73
274848CAMPGROVE;RU
80/20
0.2780.278
274849CRESCENT ;1U
80/20
0.2120.212
274850MENDOTA H;RU
80/20
0.3520.352
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274856ECOGROVE ;U1
80/20
0.4620.462
274857BIG SKY ;U1
80/20
0.3530.353
274858BIG SKY ;U2
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274860EASYR;U2 E
80/20
2.4372.437
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
274864CAYUGA RI;2U
80/20
0.5160.516
274871GR RIDGE ;2U
80/20
0.2720.272
274872LEE DEKAL;1U
80/20
0.9950.995
274877BISHOP HL;1U
80/20
0.4330.433
274878BISHOP HL;2U
80/20
0.4330.433
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274887PILOT HIL;1U
80/20
0.9460.946
274888KELLY CRK;1U
80/20
0.9460.946
276156O-029 C
80/20
0.2490.249
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
276615W2-048 GEN
80/20
0.8910.891
276621X2-022 GEN
80/20
2.5362.536
290021O50 E
80/20
3.9653.965
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
293061N-015 E
80/20
3.1963.196
293644O22 E1
80/20
2.822.82
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293716O-029 E
80/20
1.081.08
293717O-029 E
80/20
0.9930.993
293771O-035 E
80/20
1.3921.392
294392P-010 E
80/20
4.0594.059
294401BSHIL;1U E
80/20
1.7331.733
294410BSHIL;2U E
80/20
1.7331.733
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
295111SUBLETTE E
80/20
0.5570.557
917502Z2-087 E
80/20
3.3333.333
918052AA1-018 E OP
80/20
3.6223.622
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
934721AD1-100 C
80/20
3.8223.822
934722AD1-100 E
80/20
59.4559.45
937001AD2-134 C
80/20
0.8290.829
937002AD2-134 E
80/20
3.3123.312
942111AE2-223 C
80/20
1.1951.195
942112AE2-223 E
80/20
7.9997.999
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959351AF2-226 C
80/20
1.9641.964
959352AF2-226 E
80/20
2.9452.945
959611AF2-252 C
80/20
1.4511.451
959612AF2-252 E
80/20
2.1762.176
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
962012AG1-044 E
80/20
0.0450.045
966091AG1-478 C
80/20
0.4310.431
966092AG1-478 E
80/20
0.6470.647
966441AG1-513 C
80/20
0.4190.419
966442AG1-513 E
80/20
0.6290.629
274674JOLIET 9 ;6U
80/20
13.64413.644
274675JOLIET 29;7U
80/20
36.25136.251
274676JOLIET 29;8U
80/20
36.23736.237
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274687WILL CNTY;4U
80/20
32.59232.592
274890CAYUG;1U E
80/20
2.7522.752
274891CAYUG;2U E
80/20
2.7522.752
925771AC1-053 C
80/20
0.590.59
925772AC1-053 E
80/20
3.953.95
938851AE1-113 C
80/20
5.2345.234
938852AE1-113 E
80/20
18.55518.555
939401AE1-172 C
80/20
3.453.45
939402AE1-172 E
80/20
16.15416.154
942651AE2-281 C
80/20
0.5930.593
942652AE2-281 E
80/20
3.6423.642
270681BRIGHTSTK; R
80/20
0.4980.498
270839OTTER CRK; R
80/20
0.5410.541
274881WALNUT RG;1U
80/20
0.9520.952
275149KELLYCK ;1E
80/20
3.7863.786
276174W4-005 E
80/20
3.7663.766
276602WESTBROOK C
80/20
0.1730.173
276603SUBLETTE C
80/20
0.0780.078
276626AG1-044 E
80/20
0.0510.051
276627AG1-044 BAT
80/20
0.0090.009
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
276655AB2-047 C1
80/20
0.3110.311
276656AB2-047 C2
80/20
0.3110.311
276668AB2-070 C
80/20
0.3750.375
276675AE2-062 E
80/20
0.1120.112
293516O-009 E
80/20
3.8093.809
293519PILOT HIL;1E
80/20
3.7863.786
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
924048AB2-047 E1
80/20
2.0672.067
924049AB2-047 E2
80/20
2.0992.099
924266AB2-070 E
80/20
2.272.27
926821AC1-168 C
80/20
0.7420.742
926822AC1-168 E
80/20
4.9814.981
927208AC1-214 E1
80/20
0.660.66
927209AC1-214 E2
80/20
0.660.66
935141AD1-148 C
80/20
0.7970.797
936371AD2-047 C
80/20
2.9422.942
936372AD2-047 E
80/20
14.36514.365
938861AE1-114 C
80/20
2.5552.555
938862AE1-114 E
80/20
8.7168.716
939321AE1-163 C
80/20
4.1514.151
939322AE1-163 E
80/20
25.49625.496
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
946321AF1-296 C
80/20
2.2942.294
946322AF1-296 E
80/20
10.73910.739
957371AF2-031 C
80/20
0.6360.636
957372AF2-031 E
80/20
0.9540.954
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
961502AF2-441 E
80/20
10.40210.402
965331AG1-398 C
80/20
0.1690.169
990901L-005 E
80/20
2.5642.564
276170Z1-108 E
80/20
2.0422.042
920272AA2-123 E
80/20
22
965793AG1-447 BT
80/20
8.3248.324
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.66 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1044.28
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
50/50
0.730.73
274871GR RIDGE ;2U
50/50
0.2720.272
274887PILOT HIL;1U
50/50
0.9460.946
274888KELLY CRK;1U
50/50
0.9460.946
293061N-015 E
50/50
3.1963.196
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
934721AD1-100 C
50/50
3.8213.821
934722AD1-100 E
50/50
59.44459.444
942111AE2-223 C
Adder
1.19529411764705881.016
942112AE2-223 E
Adder
7.9988235294117666.799
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959351AF2-226 C
Adder
1.9635294117647061.669
959352AF2-226 E
Adder
2.94588235294117642.504
959611AF2-252 C
Adder
1.45058823529411771.233
959612AF2-252 E
Adder
2.17647058823529441.85
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
962012AG1-044 E
Adder
0.044705882352941180.038
966091AG1-478 C
50/50
0.4310.431
966092AG1-478 E
50/50
0.6470.647
966441AG1-513 C
50/50
0.420.42
966442AG1-513 E
50/50
0.6290.629
274674JOLIET 9 ;6U
50/50
13.64513.645
274675JOLIET 29;7U
50/50
36.25136.251
274676JOLIET 29;8U
50/50
36.23736.237
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
274687WILL CNTY;4U
50/50
32.59532.595
938851AE1-113 C
Adder
5.2341176470588244.449
938852AE1-113 E
Adder
18.5576470588235315.774
939401AE1-172 C
Adder
3.45058823529411772.933
939402AE1-172 E
Adder
16.15411764705882513.731
942651AE2-281 C
50/50
0.5930.593
942652AE2-281 E
50/50
3.6423.642
270839OTTER CRK; R
50/50
0.5410.541
275149KELLYCK ;1E
50/50
3.7853.785
276626AG1-044 E
Adder
0.050588235294117640.043
276627AG1-044 BAT
Adder
0.0094117647058823540.008
276675AE2-062 E
50/50
0.1120.112
293519PILOT HIL;1E
50/50
3.7853.785
926821AC1-168 C
Adder
0.74235294117647070.631
926822AC1-168 E
Adder
4.98117647058823554.234
936371AD2-047 C
50/50
2.9422.942
936372AD2-047 E
50/50
14.36514.365
938861AE1-114 C
Adder
2.5552941176470592.172
938862AE1-114 E
Adder
8.717647058823537.41
939321AE1-163 C
50/50
4.1514.151
939322AE1-163 E
50/50
25.49625.496
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
946321AF1-296 C
Adder
2.29411764705882341.95
946322AF1-296 E
Adder
10.749.129
957371AF2-031 C
Adder
0.63647058823529420.541
957372AF2-031 E
Adder
0.95411764705882360.811
961501AF2-441 C
Adder
6.9341176470588245.894
961502AF2-441 E
Adder
10.48.84
276170Z1-108 E
50/50
2.0432.043
920272AA2-123 E
50/50
22
965793AG1-447 BT
50/50
8.3258.325
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
990947J1432 G
External Queue
12.502512.5025
991302J1755
External Queue
8.07698.0769

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.66 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1044.26
MW Contribution:4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
50/50
0.730.73
274871GR RIDGE ;2U
50/50
0.2720.272
274887PILOT HIL;1U
50/50
0.9460.946
274888KELLY CRK;1U
50/50
0.9460.946
293061N-015 E
50/50
3.1963.196
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
934721AD1-100 C
50/50
3.8213.821
934722AD1-100 E
50/50
59.44459.444
942111AE2-223 C
Adder
1.19529411764705881.016
942112AE2-223 E
Adder
7.9988235294117666.799
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959351AF2-226 C
Adder
1.9635294117647061.669
959352AF2-226 E
Adder
2.94588235294117642.504
959611AF2-252 C
Adder
1.45058823529411771.233
959612AF2-252 E
Adder
2.17647058823529441.85
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
962012AG1-044 E
Adder
0.044705882352941180.038
966091AG1-478 C
50/50
0.4310.431
966092AG1-478 E
50/50
0.6470.647
966441AG1-513 C
50/50
0.420.42
966442AG1-513 E
50/50
0.6290.629
274674JOLIET 9 ;6U
50/50
13.64513.645
274675JOLIET 29;7U
50/50
36.25136.251
274676JOLIET 29;8U
50/50
36.23736.237
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
274687WILL CNTY;4U
50/50
32.59532.595
938851AE1-113 C
Adder
5.2341176470588244.449
938852AE1-113 E
Adder
18.5576470588235315.774
939401AE1-172 C
Adder
3.45058823529411772.933
939402AE1-172 E
Adder
16.15411764705882513.731
942651AE2-281 C
50/50
0.5930.593
942652AE2-281 E
50/50
3.6423.642
270839OTTER CRK; R
50/50
0.5410.541
275149KELLYCK ;1E
50/50
3.7853.785
276626AG1-044 E
Adder
0.050588235294117640.043
276627AG1-044 BAT
Adder
0.0094117647058823540.008
276675AE2-062 E
50/50
0.1120.112
293519PILOT HIL;1E
50/50
3.7853.785
926821AC1-168 C
Adder
0.74235294117647070.631
926822AC1-168 E
Adder
4.98117647058823554.234
936371AD2-047 C
50/50
2.9422.942
936372AD2-047 E
50/50
14.36514.365
938861AE1-114 C
Adder
2.5552941176470592.172
938862AE1-114 E
Adder
8.717647058823537.41
939321AE1-163 C
50/50
4.1514.151
939322AE1-163 E
50/50
25.49625.496
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
946321AF1-296 C
Adder
2.29411764705882341.95
946322AF1-296 E
Adder
10.749.129
957371AF2-031 C
Adder
0.63647058823529420.541
957372AF2-031 E
Adder
0.95411764705882360.811
961501AF2-441 C
Adder
6.9341176470588245.894
961502AF2-441 E
Adder
10.48.84
276170Z1-108 E
50/50
2.0432.043
920272AA2-123 E
50/50
22
965793AG1-447 BT
50/50
8.3258.325
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
990947J1432 G
External Queue
12.502512.5025
991302J1755
External Queue
8.07698.0769
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 246999 CKT 1   /*05MARYSV     765.0 - 05SORENS     765.0
END
CONTINGENCY '765-L11215__-S_SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
END
CONTINGENCY 'AEP_P1-2_#695_1681_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243207 CKT 1   /*05DUMONT     765.0 - 05GRNTWN     765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'COMED_P4_112-65-BT4-5___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT3-4___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
248005 to 242528 ckt 1
255113 to 243219 ckt 1
960680 to 243229 ckt 1
270677 to 255109 ckt 1
274750 to 255112 ckt 1
270728 to 274750 ckt 1
274804 to 960680 ckt 1

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 1, Cluster 5 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 5 projects.

This analysis is effectively a screening study to determine whether the addition of the Cluster 5 projects will meet the dynamics requirements of the NERC, ComEd and PJM reliability standards.

The load flow scenario for the analysis was based on the RTEP 2027 summer peak load case, modified to include applicable projects. Cluster 5 projects have been dispatched online at maximum power output and the voltage schedule set to achieve near unity power factor at the high side of the main transformer.

Cluster 5 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 107 contingencies were studied, each with a 20 second simulation time period. Studied faults included:

  1. Steady-state operation (20 second run);
  2. Three-phase faults with normal clearing time;
  3. Three-phase bus faults with normal clearing time;
  4. Three-phase to ground faults with three-phase delayed clearing due to a stuck breaker (GO breakers);
  5. Three-phase to ground faults with single-phase delayed clearing due to a stuck breaker (IPO breakers)
  6. Three-phase faults with loss of multiple-circuit tower line.

No relevant high speed reclosing (HSR) contingencies were identified for this study.

For all simulations, the Cluster 5 projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

For all of the fault contingencies tested on the 2027 peak load case:

  1. Cluster 5 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  2. The system with Cluster 5 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3%.
  3. Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).
  4. No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

AF2-226 and AF2-319 meet the 0.95 leading and lagging PF requirement.

The IPCMD and IQCMD states in the REGCA1 models of AF2-226 GEN and AF2-319 GEN showed erratic behavior for some contingencies in which this generator has been disconnected as part of the contingency event. Since the machine is disconnected and no active or reactive power is injected into the system, these plots are ignored.

Initial simulations showed AF2-226 and AF2-319 exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. The reactive power settling time was decreased by adjusting the PPC Q/V controller PI gains for both projects (Kp = 1 from 0, Ki = 5 from 0.5). The developer confirmed that the updated controller parameters are acceptable.

Simulations showed AF2-142, AF2-143, and AE1-163 getting stuck in high voltage ride through (HVRT) mode for extended periods after fault clearance for several contingencies. This resulted in a 345 kV POI voltage of about 1.1 pu for more than 5 seconds. For AF2-142 and AF2-143, this was resolved by adjusting the HVRT threshold and deadband to 1.15 pu (from 1.1 pu) and 0.15 pu (from 0.1 pu), respectively. These parameter adjustments were confirmed by the respective project developers. For AE1-163, the dynamic model was updated to the Vestas UDM which was submitted for the AE1-163/AE2-281 necessary study as per the developer’s request.

Initial simulations showed poorly damped oscillations in AC1-111 power. The AC1-111 dynamic model was updated to the most recent (revision 1) model which uses the AC7B exciter model instead of the ESAC1A model. Revision 1 of the AC1-111 dynamic model was used in the last iteration of the AC1-111 dynamic analysis, therefore it is assumed that the AC7B model is accurate relative to what is in the field. The updated dynamic model eliminated these oscillations.

No mitigations were found to be required.

 

Table 1: TC1 Cluster 5 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

5

AF2-226

Storage

ComEd

50

50

20

Katydid Road 345 kV

AF2-319

Storage

ComEd

50

50

20

Katydid Road 345 kV

 

Reactive Power Analysis

The reactive power capability of AF2-319 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA2-116Cook-East Elkhart 345kVIn Service
AA2-123Marengo 34kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-080Dumont-Olive 345kVIn Service
AB1-087Sullivan 345kV #1Under Construction
AB1-088Sullivan 345kV #2Engineering & Procurement
AB1-122Kendall-Tazewell & Dresden-Mole CreekIn Service
AC1-168Kewanee-StreatorSuspended
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-157Sullivan 345 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD2-020Valley 138 kVEngineering & Procurement
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-079Capitol Ave 34.5kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-172Lena 138kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-134Nelson 345 kVIn Service
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-205McLean 345 kVEngineering & Procurement
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-062Romeoville 12 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-223McLean 345 kVActive
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-276Sullivan 345kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-323Twin Branch-Guardian 138 kVPartially in Service - Under Construction
AE2-325Valley 138 kVActive
AE2-341Sandwich-Plano 138 kVActive
AF1-030Sandwich-Plano 138 kVActive
AF1-084Hartford-Almena 69 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVActive
AF1-176Corey 138 kVActive
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-280Nelson-Lee CountyActive
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-027Zion Energy Center 345 kVEngineering & Procurement
AF2-031CalumetEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-095Davis Creek 138 kVActive
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-182Nelson-Lee County 345 kV IIActive
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-226Katydid Road 345 kVActive
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-349SILVER LAKE- CHERRY VALLEY 345 KVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-366Crego Rd 138 kVEngineering & Procurement
AF2-396Stinger 138 kVActive
AF2-441Burnham 138kVActive
AG1-044Whiteside CountyIn Service
AG1-109Valley 138 kVActive
AG1-118Sugar Grove-Waterman 138kVActive
AG1-127Crego Rd 138 kVActive
AG1-226Dequine-Eugene 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-513Aurora 138 kVSuspended
AG1-555Dequine 345 kVEngineering & Procurement
X3-005Wildwood 12kVIn Service
Z1-073Mendota HillsIn Service
Z1-108McHenry 34kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)Identified Impacts
AF2-319 System Reinforcements:
TOTrans Owner IDTitleCategoryAllocated Cost ($USD)
NIPSb3775.8Upgrade existing terminal equipment at St. John on the existing Crete to St. John 345 kV lineInformational$0
AMILAMIL_TC1_13300Ameren - Powerton - Tazewell 345 kV Line Reconductoring & Upgrade Station EquipmentContingent$0
Grand Total:$0

System Reinforcement: b3775.8
Type
Load Flow
TO
NIPS
RTEP ID / TO ID
b3775.8
Title
Upgrade existing terminal equipment at St. John on the existing Crete to St. John 345 kV line
Description
Part of b3375 Baseline project. Upgrade the existing terminal equipment (substation conductor) at St. John on the existing Crete to St. John 345 kV line with bundled 2x1590 ACSR Lapwing
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
Mar 30 2027

Not Contingent

Note: AF2-319 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-319 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1961.0 MVA
(All)B2390.0 MVA
(All)C2390.0 MVA
(All)STE2390.0 MVA

System Reinforcement
Type
Load Flow
TO
AMIL
RTEP ID / TO ID
(Pending) / AMIL_TC1_13300
Title
Ameren - Powerton - Tazewell 345 kV Line Reconductoring & Upgrade Station Equipment
Description
AMIL limit is 1512 MVA 0.64 miles. (PWRT-TAZW-0304). Need to rebuild to be 4000 A/2390 MVA SE, upgrade the Powerton-Tazewell 345 kV circuit 1 terminal equipment and breaker and a half leg at Tazewell from 3000A to 4000A. Rebuild 0.6 miles of the Powerton-Tazewell 345 kV transmission line to increase the ampacity to 4000A
Total Cost ($USD)
$2,760,000
Allocated Cost ($USD)
$0
Time Estimate
24 Months

Contingent

Note: Based on PJM cost allocation criteria, AF2-319 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-319 could receive cost allocation. Although AF2-319 may not presently have cost responsibility for this upgrade, AF2-319 may need this upgrade in-service to be deliverable to the PJM system. If AF2-319 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B2390.0 MVA

New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 312.A.1.b and as outlined in PJM Manual 14H, Section 13, in Phase III of the Cycle, PJM coordinates with the Affected System Operators to conduct any studies required to determine the impact of the New Service Request on any Affected System and will include the Affected System Study results in Phase III System Impact Study, if available from the Affected System Operator.

If your project required an Affected System Study, the results are shown below from the Affected System Operator.

For more details, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM will list any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO) Identified Impacts
Note: Please communicate with the Affected System Operator regarding the status of the Affected System Study for your project.
Impacted FacilityTransmission OwnerReinforcementCostCost Allocated to AF2-319Scenarios
  • Wvrich 69.0 - Rochester TP 69.0 CKT 1
DEI DEI: Rebuild 1 mile of Wvrich - Rochester TP 69 kV
DEI: Rebuild 1 mile of 69kV with 477ACSR/VR2 @
100/120C the ratings assume that NIPSCO terminal
upgrades would not limit our T-Line rating. $1.5M
NIPSCO: Rebuild line, NIPSCO owns 0.037 miles of
0.9 mile line. NIPSCO portion included in Argos to
Rochester tap mitigation/cost.
$1,500,000$13,347
  • NIPSCO LPC
  • Wvrich 69.0 - Rochester TP 69.0 CKT 1
NIPS NIPSCO: Rebuild line (.3miles)Wvrich - Rochester TP 69 kV
DEI: Rebuild 1 mile of 69kV with 477ACSR/VR2 @
100/120C the ratings assume that NIPSCO terminal
upgrades would not limit our T-Line rating. $1.5M
NIPSCO: Rebuild line, NIPSCO owns 0.037 miles of
0.9 mile line. NIPSCO portion included in Argos to
Rochester tap mitigation/cost.
$0$0
  • NIPSCO LPC
  • Argos 69.0 - Plymouth 69.0 CKT 1
NIPS Rebuild Argos - Plymouth 69 kV line
Rebuild line, approx 10 miles
$12,654,948$108,928
  • NIPSCO LPC
  • Argos 69.0 - Rochester TP 69.0 CKT 1
NIPS Rebuild Argos - Rochester TP 69 kV
Rebuild line, approx 3.2 miles
$4,049,583$36,034
  • NIPSCO LPC
  • CAP BANK 230.0 - Gallagher 230.0 CKT 0
DEI Install 144 MVAR cap bank at Gallagher sub.
Install 144 MVAR cap bank at Gallagher sub.
$3,000,000$16,713
  • MISO Voltage
  • CAP BANK 138.0 - Shoals 138.0 CKT 0
DEI Install 28.8 MVAR cap bank at Shoals sub
Install 28.8 MVAR cap bank at Shoals sub
$3,000,000$12,658
  • MISO Voltage
  • CAP BANK 138.0 - Avon East 138.0 CKT 0
DEI Install 28.8 MVAR cap bank at Avon East sub
Install 28.8 MVAR cap bank at Avon East sub
$3,000,000$16,981
  • MISO Voltage
  • Morrison Ditch 345.0 - Reynolds 345.0 CKT 1
NIPS LRTP-16: Morrison Ditch – Reynolds – Burr Oak
Install single circuit 345kV transmission line
from the existing Morrison Ditch
Substation, to the existing Reynolds Substation,
to the existing Burr Oak
Substation, to the existing Leesburg Substation,
to the existing Hiple Substation.
$0$0
  • Contingent
  • Greentown 765.0 - Sorenson 765.0 CKT 1
ITCT LRTP-33: Greentown - Sorenson - Lulu
Install single circuit 765kV transmission line
from the existing Greentown
Substation to the existing Sorenson Substation, to
the existing Lulu Substation.
$0$0
  • Contingent
  • Burr Oak 345.0 - Schahfer 345.0 CKT 1
NIPS LRTP-42: Burr Oak - Schahfer
Install single circuit 345kV transmission line
from the existing Burr Oak Substation to the
existing Schahfer Substation.
$0$0
  • Contingent
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AF2-319 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
ComEdn9682.0Perform sag mitigation on the Powerton - Tazewell 345 kV Line and replace disconnect switches at Powerton substation.Cost Allocated$627,185
ComEdn6280Mitigate the sag on the ComEd Powerton - Tazewell L0304 345 kV line.Contingent$0N/A
Grand Total:$627,185

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9682.0
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n9682.0 / CE_NUN_0304.1
Title
Perform sag mitigation on the Powerton - Tazewell 345 kV Line and replace disconnect switches at Powerton substation.
Description
• Upgrade the existing substation Station 3 Powerton by replacing two sets of disconnect switches with ones capable of interrupting 3000 Amps of charging current. • Perform sag mitigation on 9 miles of 345kV transmission line L0304 from Station 3 Powerton to Tazewell (Ameren). 0.9 miles will need to be retensioned to accommodate the sag mitigation.
Total Cost ($USD)
$5,017,397
Discounted Total Cost ($USD)
$5,017,397
Allocated Cost ($USD)
$627,185
Time Estimate
1 to 36 Months

Contributor

FacilityContingency
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1576.0 MVA
(All)ALDR2340.0 MVA
(All)B1862.0 MVA
(All)C2035.0 MVA
(All)STE1900.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-142110.9 MW37.5%$1,881,556
AF2-143110.9 MW37.5%$1,881,471
AF2-226 ⧉ Katydid Road 345kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-226, AF2-319
37.0 MW12.5%$627,185
AF2-319 ⧉ Katydid Road 345kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-226, AF2-319
37.0 MW12.5%$627,185

System Reinforcement: s3442.26
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s3442.26
Title
Dumont 765 kV: Replace 3000 A circuit breaker at Dumont
Description
Dumont 765 kV: Replace 3000 A circuit breaker at Dumont to address a generation deliverability violation on the Dumont – Sorenson 765 kV branch related to the new customer interconnections in the area. Projected in service date 3/5/2027
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AF2-319 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AF2-319 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05DUMONT-05SORENS 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4558.0 MVA
(All)B5001.0 MVA

System Reinforcement: b3775.6
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.6
Title
Perform sag study mitigation work on the Dumont-Stillwell 345 kV line
Description
Perform sag study mitigation work on the Dumont-Stillwell 345 kV line (remove a center-pivot irrigation system from under the line, allowing for the normal and emergency ratings of the line to increase, replace two structures and modify a third structure).
Cost Information
Time Estimate
Nov 20 2026

Not Contingent

Note: AF2-319 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-319 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1409.0 MVA
(All)B1718.0 MVA

System Reinforcement: b3775.11
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.11 / b3775.7a
Title
Upgrade the wavetrap at Dumont substation to increase the rating of the Stillwell-Dumont 345 kV line to match conductor rating.
Description
Upgrade the wavetrap at Dumont substation to increase the rating of the Stillwell-Dumont 345 kV line to match conductor rating.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AF2-319 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-319 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1409.0 MVA
(All)B1737.0 MVA

System Reinforcement: b3775.7
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.7 / b3775.7b
Title
Upgrade breakers at Dumont substation on the Stillwell-Dumont 345 kV line.
Description
Upgrade the limiting element at Dumont substation to increase the rating of the Stillwell-Dumont 345 kV line to match conductor rating. This includes replacement of breakers F and F1.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AF2-319 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-319 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1408.0 MVA
(All)B1887.0 MVA

System Reinforcement: n3985
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n3985 / AEPO0036a
Title
Upgrade three Marysville Wavetraps ( 3000A)
Description
Replace 3 Marysville 765 kV wave traps. Costs updated to $705,368 from Facility Study
Total Cost ($USD)
$900,000
Discounted Total Cost ($USD)
$900,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 24 Months

Not Contingent

Note: AF2-319 contributes to the loading of an overloaded facility that is being mitigated by a network upgrade that was securitized by a prior Queue/Cycle. AF2-319 is not contingent on this network upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARYSV-05SORENS 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5075.0 MVA
(All)B5075.0 MVA

System Reinforcement: b3775.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.1
Title
Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line
Description
Outside of the Green Acres substation, swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line to the University Park N-Olive 345 kV line to create a University Park N-Green Acres-Olive and St. John-Olive 345 kV lines.
Cost Information
Time Estimate
Mar 30 2027

Not Contingent

Note: AF2-319 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-319 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)ALDR9999.0 MVA
(All)STE9999.0 MVA
05OLIVE-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A9999.0 MVA
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A9999.0 MVA

System Reinforcement: b3775.10
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.10
Title
Perform sag study mitigation work on Olive – University Park
Description
Perform a sag study on the Olive – University Park 345kV line to increase the operating temperature to 225 F. Remediation work includes two tower replacements on the line.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AF2-319 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-319 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA

System Reinforcement: b3775.2
Type
Load Flow
TO
NextEra
RTEP ID / TO ID
b3775.2
Title
Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles).
Description
Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles).
Cost Information
Time Estimate
May 09 2023

Not Contingent

Note: AF2-319 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-319 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA
(All)C2280.0 MVA
(All)STE2107.0 MVA

System Reinforcement: b3775.3
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.3
Title
Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete
Description
Part of b3775 baseline. Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete (5 miles) with twin bundled 1277 ACAR conductor.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AF2-319 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-319 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA
(All)C2280.0 MVA
(All)STE2107.0 MVA

System Reinforcement: b3775.5
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.5
Title
Replace E. Frankfort 345 kV circuit breaker “9-14” with 3150A SF6 circuit breaker.
Description
Part of b3775 baseline. Replace E. Frankfort 345 kV circuit breaker “9-14” with 3150A SF6 circuit breaker.
Cost Information
Time Estimate
TBD

Not Contingent

Note: AF2-319 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-319 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1826.0 MVA
(All)B2070.0 MVA
(All)C2390.0 MVA
SUMSTE2385.0 MVA

System Reinforcement: n6280
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n6280 / ce-005
Title
Mitigate the sag on the ComEd Powerton - Tazewell L0304 345 kV line.
Description
ComEd 345kV L0304 ratings ,SSTE: 1512 MVA and ALDR: 1739 MVA. The post contingency flow for this event exceeds the rating therefore an upgrade is required. The upgarde will be to mitigate the sag on the line. A preliminary estimate for this work is $9.1M with a estimated construction timeline of 30 months. Upon completion of this upgrade the new ratings will be 1461/1656/1909/1912/2198 MVA (SN/SLTE/SSTE/SLD/ALDR).
Total Cost ($USD)
$2,470,000
Discounted Total Cost ($USD)
$2,470,000
Allocated Cost ($USD)
$0
Time Estimate
Nov 01 2026

Contingent

Note: Based on PJM cost allocation criteria, AF2-319 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AF2-319 may not have cost responsibility for this upgrade, AF2-319 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AF2-319 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
POWERTON ; R-7TAZEWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1461.0 MVA
(All)ALDR2198.0 MVA
(All)B1656.0 MVA
(All)C1912.0 MVA
(All)STE1909.0 MVA

System Reinforcement: s3011
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
s3011 / CE_S3011
Title
Replace 345kV straight bus at TSS 116 Goodings Grove with a gas insulated switchgear ("GIS") breaker and a half configuration.
Description
Replace 345 kV open air straight bus with GIS in a breaker and half configuration (34 Circuit Breakers) at Goodings Grove with 80kA capability.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AF2-319 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AF2-319 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
(Any)COMED_P4_116-45-L11614__SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4-6_116-345-R______SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4_112-45-BT4-5___SRT-A
No new ratings for this Flowgate.

System Reinforcement: b3775.4
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.4 / CE_B3775.4
Title
Rebuild 345 kV double circuit extending from Crete to E. Frankfort.
Description
Part of b3775 baseline. Rebuild 12.7 miles of 345 kV double circuit extending from Crete to E. Frankfort with twin bundled 1277 ACAR conductor.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AF2-319 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-319 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
(Any)765-L11215__-S_SRT-A
No new ratings for this Flowgate.
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA
(All)C2280.0 MVA
(All)STE2017.0 MVA

System Reinforcement: n5145
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n5145
Title
Reconfigure Wilton 765kV bus
Description
Reconfigure Wilton 765kV bus thereby allowing for 765kV L11216 (currently on Bus 6) to be relocated to Bus 8. Along with this line relocation, installation of 2-765kV BT CBs (6-8 & 8-2). Cost increased from $12M to $55M. This will eliminate the stuck breaker contingencies '112-65-BT4-5__' and '112-65-BT5-6__'. No other contingency updates needed.
Total Cost ($USD)
$55,229,373
Discounted Total Cost ($USD)
$55,229,373
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2025

Not Contingent

Note: AF2-319 contributes to the loading of an overloaded facility that is being mitigated by a network upgrade that was securitized by a prior Queue/Cycle. AF2-319 is not contingent on this network upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
(Any)COMED_P4_112-65-BT4-5___SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4_112-65-BT5-6___SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4_112-65-BT2-3___SRT-A
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AF2-319


AF2-319 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AF2-319 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AF2-319 One Line Diagram

AF2-319 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.