AF2-350 Final System Impact Study (Retool 2) Report

v2.00 released 2026-05-14 11:52

Kensington 138 kV

60.0 MW Capacity / 100.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Deriva Energy Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Commonwealth Edison Company.

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.

The AF2-350 Final System Impact Study (Retool 1) Report is available for download here.

Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed a Solar generating facility located in the Commonwealth Edison Company zone — Kankakee County, Illinois. The installed facilities will have a total capability of 100.0 MW with 60.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AF2-350
Project Name:
Kensington 138 kV
Project Developer Name:
Deriva Energy Solar, LLC
State:
Illinois
County:
Kankakee
Transmission Owner:
Commonwealth Edison Company
MFO:
100.0
MWE:
100.0
MWC:
60.0
Fuel Type:
Solar
Basecase Study Year:
2027

Physical Interconnection Facility Study

Received

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AF2-350 will interconnect on the ComEd transmission system via a direct connection into the TSS 199 Kensington Road 138 kV substation.

 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AF2-350 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AF2-350Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$793,922$793,922
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$29,405,140$29,405,140
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0
AFS - Non-PJM Violations$428,064 **$0 **
Total$30,627,126$30,199,062

* Contributes to calculation for Security. See Security Requirement Section of this report for additional detail.

** This value reflects the results at the time of the report posting and it is subject to change. AFS – Non-PJM Violations are not subject to Security. For latest AFS – Non-PJM Violations, please refer to the latest Affected System Study Report for your project.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF2-350

Security has been calculated for the AF2-350 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF2-350
Project(s): AF2-350
Final Agreement Security (A): $30,199,062
Portion of Costs Already Paid (B): $0
Revised Net Security (C): A − B = $30,199,062
Security on Hand with PJM (D): $30,199,062
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

As shown in the one line diagram, this Interconnection Request is sharing the Point of Interconnection (POI) with one or more other Interconnection Requests. Should other requests withdraw from the Interconnection Queue, the cost allocation for Transmission Owner Interconnection Facilities, Stand Alone Network Upgrades, and applicable Network Upgrades identified in the study report will be updated for the remaining project(s). Refer to the one line for other Interconnection Requests at this POI.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n9363.0

Construct substation upgrades at TSS199 Kensington Road including relocating/upgrading L19901 and L19902 lines

$13,681,424$4,837,500$3,192,984$287,511$21,999,419$21,999,419
n9362.0

Relocate/upgrade L19906 138 kV line with approximately 0.15 new circuit miles to TSS 199 Kensington Road.

$2,348,391$954,960$548,070$56,757$3,908,178$3,908,178
n9361.0

Relocate/upgrade L19907 138 kV line with approximately 0.04 new circuit miles to TSS 199 Kensington Road.

$1,150,152$449,266$268,423$26,702$1,894,543$1,894,543
n9360.0

Perform Relaying Upgrades at ESS K323 CSL

$208,385$6,112$48,633$363$263,493$263,493
n9359.0

Perform Relaying Upgrades at TSS70 Bradley

$208,385$6,112$48,633$363$263,493$263,493
n9358.0

Perform Relaying Upgrades at TSS86 Davis Creek

$208,385$6,112$48,633$363$263,493$263,493
n9357.0

Perform Relaying Upgrades at STA4 Quad Cities

$208,385$6,112$48,633$363$263,493$263,493
n9356.0

Relocate fiber optic cables for L19901 to TSS938 Pilot Hill and L19902 to TSS949 Kelly Creek

$287,638$183,363$67,129$10,898$549,028$549,028
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Construct Transmission Owner Interconnection Facilities from the Point of Change in Ownership to the TSS199 Kensington Road Substation

$220,655$492,499$51,497$29,271$793,922$793,922

Based on the scope of work for the Interconnection Facilities, it is expected to take 36 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Notes on Cost Estimate:

  1. These estimates are Order-of-Magnitude estimates of the costs that ComEd would bill to the Project Developer for this interconnection. These estimates are based on a one-line electrical diagram of the project and the information provided by the Project Developer.
  2. There were no site visits performed for these estimates. There may be costs related to specific site related issues that are not identified in these estimates. The site reviews will be performed during the Facilities Study or during detailed engineering.
  3. These estimates are not a guarantee of the maximum amount payable by the Project Developer and the actual costs of ComEd's work may differ significantly from these estimates. The Project Developer will be responsible for paying actual costs of ComEd's work in accordance with the PJM Open Access Transmission Tariff.
  4. The Project Developer is responsible for all engineering, procurement, testing and construction of all equipment on the Project Developer’s side of the Point of Change in Ownership.

These cost estimates do not include cost of acquiring right-of-way for the transmission line and purchasing any additional land, if needed, for the line terminations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. ComEd interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AF2-350 was evaluated as a 100.0 MW (60.0 MW Capacity) injection in the ComEd area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP
05DUMONT-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC111.58 %4142.0B4621.4923.61
GD1AEP
05DUMONT-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC100.3 %4142.0B4154.5421.4
GD1AEP
05SORENS-05MARYSV 765.0 kV Ckt 1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC102.72 %4142.0B4254.7124.67

Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.58 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4621.49
MW Contribution:23.61
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.09 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4642.69
MW Contribution:23.69
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966092AG1-478 E
Adder
0.93411764705882360.794
962692AG1-118 E
Adder
27.37176470588235223.266
962691AG1-118 C
Adder
41.05764705882353434.899
272363ESS H440 ; R
Adder
4.9294117647058834.19
959091AF2-200 C
Adder
26.65176470588235322.654
274682WAUKEGAN ;7U
Adder
75.2058823529411763.925
938851AE1-113 C
Adder
14.73882352941176612.528
942652AE2-281 E
Adder
9.6188235294117658.176
942651AE2-281 C
Adder
1.56588235294117651.331
274708KENDALL ;3C
50/50
7.1797.179
274789SE CHICAG;6U
Adder
8.7305882352941187.421
274790SE CHICAG;7U
Adder
8.7305882352941187.421
274791SE CHICAG;8U
Adder
8.7305882352941187.421
941551AE2-152 C
50/50
21.32121.321
274891CAYUG;2U E
Adder
26.69411764705882522.69
957332AF2-027 E
Adder
6.8388235294117655.813
274709KENDALL ;3S
50/50
4.7494.749
958481AF2-142 C
Adder
20.41411764705882317.352
274676JOLIET 29;8U
Adder
129.0705882352941109.71
960681AF2-359 C
Adder
17.43176470588235514.817
933411AC2-154 C
Adder
4.4858823529411773.813
958011AF2-095 C
Adder
20.3976470588235317.338
966091AG1-478 C
Adder
3.71294117647058863.156
966441AG1-513 C
Adder
0.93411764705882360.794
274711KENDALL ;4S
50/50
4.7494.749
274687WILL CNTY;4U
Adder
119.63882352941177101.693
274788SE CHICAG;5U
Adder
8.7305882352941187.421
934722AD1-100 E
50/50
165.829165.829
274660LASCO STA;1U
50/50
44.08744.087
960591AF2-350 C
Adder
14.1647058823529412.04
275149KELLYCK ;1E
Adder
33.05176470588235628.094
960592AF2-350 E
Adder
9.4435294117647068.027
960751AF2-366 C
Adder
12.94823529411764811.006
960582AF2-349 E
Adder
67.176470588235357.1
942422AE2-255 E
Adder
16.7482352941176514.236
957371AF2-031 C
Adder
1.8882352941176471.605
965791AG1-447 C
Adder
12.78352941176470610.866
965682AG1-436 E
Adder
11.6211764705882359.878
270101AB1-080 CT2
50/50
9.0469.046
270100AB1-080 CT1
50/50
9.0469.046
939351AE1-166 C
50/50
18.47818.478
293519PILOT HIL;1E
Adder
33.05176470588235628.094
293061N-015 E
Adder
28.1705882352941223.945
274674JOLIET 9 ;6U
Adder
65.8517647058823555.974
943121AE2-341 C
Adder
23.57411764705882420.038
295111SUBLETTE E
Adder
5.1047058823529424.339
939321AE1-163 C
Adder
10.9611764705882359.317
274675JOLIET 29;7U
Adder
129.0741176470588109.713
961501AF2-441 C
Adder
18.91647058823529516.079
274777LINCOLN ;8U
50/50
3.1483.148
939352AE1-166 E
50/50
17.05717.057
294392P-010 E
Adder
35.776470588235330.41
290108LEEDK;1U E
Adder
44.7835294117647138.066
916221Z1-073 E
Adder
13.82117647058823511.748
934101AD2-000 1
Adder
10.767058823529419.152
959092AF2-200 E
Adder
1.71529411764705891.458
957472AF2-041 E
Adder
19.98823529411764716.99
942421AE2-255 C
Adder
5.5823529411764714.745
958492AF2-143 E
Adder
13.42117647058823411.408
959352AF2-226 E
Adder
6.8141176470588245.792
910542X3-005 E
Adder
1.32588235294117651.127
24344105CKG2
50/50
60.20560.205
958012AF2-095 E
Adder
13.59882352941176411.559
290051GSG-6; E
Adder
19.6129411764705916.671
966442AG1-513 E
Adder
1.40117647058823551.191
274683WAUKEGAN ;8U
Adder
81.1376470588235368.967
934111AD2-000 2
Adder
10.7964705882352949.177
936512AD2-066 E
Adder
10.422352941176478.859
936511AD2-066 C
Adder
15.63294117647058813.288
295109WESTBROOK E
Adder
10.5011764705882368.926
957331AF2-027 C
Adder
4.55882352941176453.875
274661LASCO STA;2U
50/50
44.22744.227
943122AE2-341 E
Adder
11.5764705882352949.84
933912AD1-013 E
Adder
5.5141176470588244.687
958491AF2-143 C
Adder
20.1317647058823517.112
959351AF2-226 C
Adder
4.5435294117647063.862
934721AD1-100 C
50/50
5.4595.459
943591AF1-030 C
Adder
15.67647058823529313.325
943592AF1-030 E
Adder
7.75647058823529446.593
937002AD2-134 E
Adder
18.96352941176470716.119
290021O50 E
Adder
35.73058823529411430.371
936292AD2-038 E
Adder
27.6482352941176523.501
274770LINCOLN ;1U
50/50
3.1483.148
274772LINCOLN ;3U
50/50
3.1483.148
274771LINCOLN ;2U
50/50
3.1483.148
960752AF2-366 E
Adder
8.6317647058823527.337
957471AF2-041 C
Adder
39.97764705882353633.981
293644O22 E1
Adder
26.09999999999999822.185
960281AF2-319 C
Adder
4.5435294117647063.862
957372AF2-031 E
Adder
2.83294117647058832.408
270102AB1-080 ST
50/50
9.7879.787
274774LINCOLN ;5U
50/50
3.1483.148
941552AE2-152 E
50/50
14.21414.214
274890CAYUG;1U E
Adder
26.69411764705882522.69
938852AE1-113 E
Adder
52.2552941176470644.417
274710KENDALL ;4C
50/50
7.1017.101
958482AF2-142 E
Adder
13.60941176470588211.568
274792SE CHICAG;9U
Adder
8.722352941176477.414
960682AF2-359 E
Adder
11.6211764705882359.878
918052AA1-018 E OP
Adder
29.625.16
293645O22 E2
Adder
29.89294117647058625.409
960282AF2-319 E
Adder
6.8141176470588245.792
965681AG1-436 C
Adder
17.43176470588235514.817
274773LINCOLN ;4U
50/50
3.1483.148
939322AE1-163 E
Adder
67.3294117647058857.23
961502AF2-441 E
Adder
28.3752941176470624.119
936372AD2-047 E
Adder
39.1894117647058833.311
962781AG1-127 C
Adder
12.98470588235294311.037
933911AD1-013 C
Adder
3.45176470588235332.934
276591L-013 2
Adder
6.7270588235294125.718
274795SE CHICAG;2U
Adder
8.722352941176477.414
274793SE CHICAG;0U
Adder
8.722352941176477.414
24796705OLIV SLR E
Adder
0.56117647058823530.477
274776LINCOLN ;7U
50/50
3.1483.148
933412AC2-154 E
Adder
7.3188235294117656.221
936371AD2-047 C
Adder
8.0270588235294126.823
936461AD2-060 C
Adder
4.7211764705882354.013
962782AG1-127 E
Adder
8.6411764705882357.345
946671AF1-331 C
Adder
4.4823529411764713.81
274794SE CHICAG;1U
Adder
8.722352941176477.414
274775LINCOLN ;6U
50/50
3.1483.148
920272AA2-123 E
Adder
5.30941176470588254.513
276170Z1-108 E
Adder
5.3764705882352954.57
276675AE2-062 E
Adder
0.275294117647058860.234
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
2.162.16
TVALTFEXP_TVA->PJM
CLTF
5.7885.788
O66PJM->LTFIMP_O-066
CMTX_NF
37.87737.877
NYPJM->LTFIMP_NY
CLTF
3.0993.099
LGEELTFEXP_LGEE->PJM
CLTF
1.2131.213
WECLTFEXP_WEC->PJM
CLTF
7.2467.246
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.4271.427
CBM West 1LTFEXP_CBM-W1->PJM
CBM
268.722268.722
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.75157.751
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
27.4427.44
LAGNLTFEXP_LAGN->PJM
CLTF
10.83410.834
G-007PJM->LTFIMP_G-007
CMTX_NF
5.9085.908
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.7140.714
SIGELTFEXP_SIGE->PJM
CLTF
0.7480.748

Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.3 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4154.54
MW Contribution:21.4
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.95 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4181.2
MW Contribution:21.49
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966092AG1-478 E
Adder
0.84705882352941180.72
962692AG1-118 E
Adder
24.8329411764705921.108
962691AG1-118 C
Adder
37.2494117647058831.662
272363ESS H440 ; R
Adder
4.4705882352941183.8
959091AF2-200 C
Adder
24.1647058823529420.54
274682WAUKEGAN ;7U
Adder
68.2257.987
938851AE1-113 C
Adder
13.33647058823529511.336
942652AE2-281 E
Adder
8.7023529411764717.397
942651AE2-281 C
Adder
1.41647058823529411.204
274708KENDALL ;3C
50/50
6.5186.518
274789SE CHICAG;6U
Adder
7.9058823529411776.72
274790SE CHICAG;7U
Adder
7.9058823529411776.72
274791SE CHICAG;8U
Adder
7.9058823529411776.72
941551AE2-152 C
50/50
19.33119.331
957332AF2-027 E
Adder
6.20352941176470555.273
274709KENDALL ;3S
50/50
4.3114.311
958481AF2-142 C
Adder
18.47882352941176615.707
274676JOLIET 29;8U
Adder
117.0517647058823699.494
960681AF2-359 C
Adder
15.73176470588235413.372
933411AC2-154 C
Adder
4.0658823529411773.456
958011AF2-095 C
Adder
18.48823529411764715.715
966091AG1-478 C
Adder
3.3647058823529412.86
966441AG1-513 C
Adder
0.84705882352941180.72
959081AF2-199 C
Adder
12.0823529411764710.27
274711KENDALL ;4S
50/50
4.3114.311
274687WILL CNTY;4U
Adder
108.4752941176470592.204
274788SE CHICAG;5U
Adder
7.9058823529411776.72
934722AD1-100 E
50/50
150.352150.352
274660LASCO STA;1U
50/50
40.01840.018
960591AF2-350 C
Adder
12.83882352941176610.913
275149KELLYCK ;1E
Adder
29.9576470588235325.464
960592AF2-350 E
Adder
8.5588235294117647.275
960751AF2-366 C
Adder
11.747058823529419.985
960582AF2-349 E
Adder
60.9223529411764751.784
942422AE2-255 E
Adder
15.1552941176470612.882
957371AF2-031 C
Adder
1.71058823529411771.454
965791AG1-447 C
Adder
11.5364705882352939.806
965682AG1-436 E
Adder
10.4870588235294118.914
270101AB1-080 CT2
50/50
8.1638.163
270100AB1-080 CT1
50/50
8.1638.163
939351AE1-166 C
50/50
16.75316.753
293519PILOT HIL;1E
Adder
29.9576470588235325.464
293061N-015 E
Adder
25.55058823529411821.718
274674JOLIET 9 ;6U
Adder
59.7105882352941250.754
943121AE2-341 C
Adder
21.4047058823529418.194
295111SUBLETTE E
Adder
4.6294117647058833.935
939321AE1-163 C
Adder
9.9164705882352958.429
274675JOLIET 29;7U
Adder
117.0552941176470799.497
961501AF2-441 C
Adder
17.1376470588235314.567
274777LINCOLN ;8U
50/50
2.8662.866
939352AE1-166 E
50/50
15.46515.465
294392P-010 E
Adder
32.44823529411764427.581
290108LEEDK;1U E
Adder
40.62588235294117634.532
916221Z1-073 E
Adder
12.53411764705882410.654
934101AD2-000 1
Adder
9.7588235294117668.295
959092AF2-200 E
Adder
16.1105882352941213.694
957472AF2-041 E
Adder
18.12352941176470715.405
942421AE2-255 C
Adder
5.0517647058823534.294
958492AF2-143 E
Adder
12.1423529411764710.321
959352AF2-226 E
Adder
6.1694117647058825.244
910542X3-005 E
Adder
1.20117647058823531.021
24344105CKG2
50/50
55.59555.595
958012AF2-095 E
Adder
12.32588235294117710.477
290051GSG-6; E
Adder
17.78705882352941415.119
966442AG1-513 E
Adder
1.27058823529411781.08
959082AF2-199 E
Adder
5.44117647058823554.625
274683WAUKEGAN ;8U
Adder
73.6000000000000162.56
934111AD2-000 2
Adder
9.7858823529411768.318
936512AD2-066 E
Adder
9.4294117647058838.015
936511AD2-066 C
Adder
14.14470588235294112.023
295109WESTBROOK E
Adder
9.522352941176478.094
957331AF2-027 C
Adder
4.1352941176470593.515
933912AD1-013 E
Adder
5.04.25
958491AF2-143 C
Adder
18.21411764705882415.482
959351AF2-226 C
Adder
4.11294117647058853.496
934721AD1-100 C
50/50
4.9494.949
943591AF1-030 C
Adder
14.23411764705882412.099
943592AF1-030 E
Adder
7.042352941176475.986
937002AD2-134 E
Adder
17.1976470588235314.618
290021O50 E
Adder
32.3317647058823527.482
936292AD2-038 E
Adder
25.01411764705882521.262
274770LINCOLN ;1U
50/50
2.8662.866
274772LINCOLN ;3U
50/50
2.8662.866
274771LINCOLN ;2U
50/50
2.8662.866
960752AF2-366 E
Adder
7.8305882352941176.656
957471AF2-041 C
Adder
36.2482352941176530.811
293644O22 E1
Adder
23.6270588235294120.083
960281AF2-319 C
Adder
4.11294117647058853.496
957372AF2-031 E
Adder
2.56470588235294142.18
270102AB1-080 ST
50/50
8.8338.833
274774LINCOLN ;5U
50/50
2.8662.866
941552AE2-152 E
50/50
12.88712.887
938852AE1-113 E
Adder
47.2858823529411740.193
274710KENDALL ;4C
50/50
6.4476.447
958482AF2-142 E
Adder
12.31882352941176410.471
274792SE CHICAG;9U
Adder
7.8964705882352946.712
960682AF2-359 E
Adder
10.4870588235294118.914
918052AA1-018 E OP
Adder
26.79411764705882222.775
293645O22 E2
Adder
27.06117647058823323.002
960282AF2-319 E
Adder
6.1694117647058825.244
965681AG1-436 C
Adder
15.73176470588235413.372
274773LINCOLN ;4U
50/50
2.8662.866
274661LASCO STA;2U
50/50
40.14440.144
943122AE2-341 E
Adder
10.5105882352941178.934
939322AE1-163 E
Adder
60.916470588235351.779
961502AF2-441 E
Adder
25.7070588235294121.851
936372AD2-047 E
Adder
35.5211764705882430.193
962781AG1-127 C
Adder
11.7810.013
933911AD1-013 C
Adder
3.1305882352941182.661
276591L-013 2
Adder
6.1047058823529415.189
274795SE CHICAG;2U
Adder
7.8964705882352946.712
274793SE CHICAG;0U
Adder
7.8964705882352946.712
24796705OLIV SLR E
Adder
0.50470588235294120.429
274776LINCOLN ;7U
50/50
2.8662.866
933412AC2-154 E
Adder
6.6329411764705885.638
936371AD2-047 C
Adder
7.2752941176470596.184
936461AD2-060 C
Adder
4.283.638
962782AG1-127 E
Adder
7.8388235294117666.663
946671AF1-331 C
Adder
4.0647058823529413.455
274794SE CHICAG;1U
Adder
7.8964705882352946.712
274775LINCOLN ;6U
50/50
2.8662.866
920272AA2-123 E
Adder
4.8164705882352954.094
276675AE2-062 E
Adder
0.249411764705882360.212
276170Z1-108 E
Adder
4.877647058823534.146
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
1.8261.826
TVALTFEXP_TVA->PJM
CLTF
5.8945.894
O66PJM->LTFIMP_O-066
CMTX_NF
35.23735.237
NYPJM->LTFIMP_NY
CLTF
2.8932.893
LGEELTFEXP_LGEE->PJM
CLTF
3.0323.032
WECLTFEXP_WEC->PJM
CLTF
6.5716.571
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.1751.175
CBM West 1LTFEXP_CBM-W1->PJM
CBM
243.013243.013
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.43653.436
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
24.86724.867
LAGNLTFEXP_LAGN->PJM
CLTF
10.36210.362
G-007PJM->LTFIMP_G-007
CMTX_NF
5.4955.495
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.5610.561
SIGELTFEXP_SIGE->PJM
CLTF
0.7770.777

Details for 05SORENS-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SORENS-05MARYSV 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.72 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4254.71
MW Contribution:24.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05MARYSV 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.53 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4288.42
MW Contribution:24.74
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966092AG1-478 E
Adder
0.97647058823529410.83
962691AG1-118 C
Adder
17.81058823529411615.139
274682WAUKEGAN ;7U
Adder
78.4505882352941366.683
274789SE CHICAG;6U
Adder
9.2541176470588237.866
274790SE CHICAG;7U
Adder
9.2541176470588237.866
274791SE CHICAG;8U
Adder
9.2541176470588237.866
958392AF2-133 E
Adder
29.59529411764705725.156
944242AF1-092 E
Adder
8.822352941176477.499
24647605NILES
50/50
0.0550.055
962601AG1-109 C
50/50
6.3426.342
939391AE1-170 C
50/50
16.1416.14
941551AE2-152 C
Adder
22.1447058823529418.823
957332AF2-027 E
Adder
7.1400000000000016.069
958481AF2-142 C
Adder
21.49882352941176618.274
274676JOLIET 29;8U
Adder
134.5764705882353114.39
945421AF1-207 C
Adder
8.1811764705882366.954
960681AF2-359 C
Adder
18.9305882352941216.091
944241AF1-092 C
Adder
28.98705882352941324.639
933411AC2-154 C
Adder
4.6870588235294123.984
958011AF2-095 C
Adder
21.31529411764705618.118
966091AG1-478 C
Adder
3.88000000000000033.298
966441AG1-513 C
Adder
0.96823529411764710.823
274687WILL CNTY;4U
Adder
124.97176470588235106.226
274788SE CHICAG;5U
Adder
9.2541176470588237.866
964861AG1-349 C
Adder
38.6632.861
958382AF2-132 E
Adder
29.80235294117647325.332
943002AE2-323 E
Adder
8.097647058823536.883
24647705NILES
50/50
0.0550.055
270142AA2-116_CT1
50/50
15.92315.923
934722AD1-100 E
Adder
172.2376470588235146.402
960591AF2-350 C
Adder
14.80235294117647312.582
275149KELLYCK ;1E
Adder
34.53882352941176529.358
960592AF2-350 E
Adder
9.8682352941176488.388
957371AF2-031 C
Adder
2.01.7
959142AF2-205 E
Adder
19.65764705882352816.709
945502AF1-215 E
Adder
30.13647058823529425.616
965791AG1-447 C
Adder
13.88235294117647111.8
965682AG1-436 E
Adder
12.62117647058823510.728
943001AE2-323 C
Adder
16.5152941176470614.038
24441505OLIV SLR C
50/50
0.1060.106
944931AF1-158 C
50/50
3.7133.713
270101AB1-080 CT2
50/50
9.9719.971
270100AB1-080 CT1
50/50
9.9719.971
24643105BUCHANAN
50/50
0.0840.084
24307105BERRINSP G
50/50
0.1370.137
944161AF1-084 C
Adder
13.66941176470588311.619
939351AE1-166 C
Adder
19.19176470588235316.313
293519PILOT HIL;1E
Adder
34.53882352941176529.358
293061N-015 E
Adder
29.2470588235294124.86
274674JOLIET 9 ;6U
Adder
68.6729411764705958.372
943121AE2-341 C
Adder
24.38470588235294320.727
274675JOLIET 29;7U
Adder
134.57764705882354114.391
961501AF2-441 C
Adder
19.95058823529411616.958
940582AE2-045 E
Adder
28.28352941176470724.041
24344005CKG1
50/50
43.40443.404
274777LINCOLN ;8U
50/50
3.1893.189
939352AE1-166 E
Adder
17.7152941176470615.058
294392P-010 E
Adder
37.143529411764731.572
934101AD2-000 1
Adder
11.2117647058823529.53
959352AF2-226 E
Adder
7.17647058823529356.1
942241AE2-236 C
Adder
9.7541176470588238.291
910542X3-005 E
Adder
1.39411764705882371.185
945112AF1-176 E
50/50
36.6236.62
936141AD2-020 C
50/50
15.70315.703
270144AA2-116_ST
50/50
14.10214.102
24344105CKG2
50/50
55.84955.849
958012AF2-095 E
Adder
14.21058823529411812.079
966442AG1-513 E
Adder
1.45294117647058841.235
274683WAUKEGAN ;8U
Adder
84.6588235294117671.96
934111AD2-000 2
Adder
11.2741176470588259.583
964862AG1-349 E
Adder
25.7729411764705921.907
958381AF2-132 C
Adder
44.7047058823529537.999
270216AD2-079_C O1
50/50
0.5020.502
270143AA2-116_CT2
50/50
15.92315.923
957331AF2-027 C
Adder
4.7600000000000014.046
957842AF2-078 E
Adder
19.25058823529411716.363
957841AF2-078 C
Adder
28.8752941176470624.544
24335205NTRDAM
50/50
2.4332.433
24641605TWIN BRNCH
50/50
0.0710.071
247643Z2-116 C
50/50
0.0550.055
959351AF2-226 C
Adder
4.7847058823529424.067
959141AF2-205 C
Adder
29.48588235294117525.063
942242AE2-236 E
Adder
4.183.553
944932AF1-158 E
50/50
15.54815.548
945111AF1-176 C
50/50
39.50439.504
957892AF2-083 E
50/50
12.77812.778
24796605WTRV SLR E
Adder
0.57647058823529410.49
943591AF1-030 C
Adder
16.21647058823529613.784
943592AF1-030 E
Adder
8.0235294117647066.82
964401AG1-302 C
Adder
44.7047058823529537.999
964402AG1-302 E
Adder
29.80235294117647325.332
24642205MAYFLWER
50/50
0.2440.244
944961AF1-161 C
50/50
6.3426.342
274770LINCOLN ;1U
50/50
3.1893.189
274772LINCOLN ;3U
50/50
3.1893.189
274771LINCOLN ;2U
50/50
3.1893.189
293644O22 E1
Adder
27.48823529411764723.365
960281AF2-319 C
Adder
4.7847058823529424.067
957372AF2-031 E
Adder
3.02.55
270102AB1-080 ST
50/50
10.78910.789
944162AF1-084 E
Adder
7.80823529411764656.637
936142AD2-020 E
50/50
9.6669.666
274774LINCOLN ;5U
50/50
3.1893.189
941552AE2-152 E
Adder
14.76352941176470612.549
958482AF2-142 E
Adder
14.3329411764705912.183
274792SE CHICAG;9U
Adder
9.2541176470588237.866
958402AF2-134 E
Adder
10.0458823529411768.539
960682AF2-359 E
Adder
12.62117647058823510.728
247969Z2-116 E
50/50
0.3340.334
957891AF2-083 C
50/50
25.55625.556
961051AF2-396 C
50/50
50.74150.741
939392AE1-170 E
50/50
22.28822.288
918052AA1-018 E OP
Adder
31.17294117647058726.497
293645O22 E2
Adder
31.48352941176470726.761
960282AF2-319 E
Adder
7.17647058823529356.1
965681AG1-436 C
Adder
18.9305882352941216.091
936632AD2-079 E O1
50/50
2.0472.047
274773LINCOLN ;4U
50/50
3.1893.189
943122AE2-341 E
Adder
11.97411764705882410.178
961502AF2-441 E
Adder
29.9258823529411825.437
940581AE2-045 C
Adder
20.59882352941176717.509
24335305OLIVE
50/50
0.2120.212
936372AD2-047 E
Adder
40.95294117647059634.81
276591L-013 2
Adder
6.9894117647058825.941
274795SE CHICAG;2U
Adder
9.2541176470588237.866
274793SE CHICAG;0U
Adder
9.2541176470588237.866
24796705OLIV SLR E
50/50
0.6480.648
274776LINCOLN ;7U
50/50
3.1893.189
933412AC2-154 E
Adder
7.6482352941176476.501
936371AD2-047 C
Adder
8.3882352941176477.13
936461AD2-060 C
Adder
4.9341176470588244.194
274794SE CHICAG;1U
Adder
9.2541176470588237.866
945422AF1-207 E
Adder
35.13176470588235429.862
958391AF2-133 C
Adder
44.3929411764705937.734
276675AE2-062 E
Adder
0.287058823529411760.244
276170Z1-108 E
Adder
5.6058823529411764.765
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
2.3872.387
TVALTFEXP_TVA->PJM
CLTF
8.198.19
O66PJM->LTFIMP_O-066
CMTX_NF
44.79244.792
NYPJM->LTFIMP_NY
CLTF
3.633.63
LGEELTFEXP_LGEE->PJM
CLTF
3.8433.843
WECLTFEXP_WEC->PJM
CLTF
7.6087.608
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.531.53
CBM West 1LTFEXP_CBM-W1->PJM
CBM
319.618319.618
CBM West 2LTFEXP_CBM-W2->PJM
CBM
75.36775.367
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
30.0930.09
LAGNLTFEXP_LAGN->PJM
CLTF
13.77113.771
G-007PJM->LTFIMP_G-007
CMTX_NF
6.9886.988
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.7280.728
SIGELTFEXP_SIGE->PJM
CLTF
1.2341.234
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT Z1   /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1    /*05HANG R     765.0 - 05JEFRSO     765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1   /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1   /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1   /*05HANG R     765.0 - 05JEFRSO     765.0
 REMOVE UNIT 1A FROM BUS 247245                    /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                    /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                    /*05HRKG1S      18.0
 REMOVE UNIT 2 FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2A FROM BUS 247248                    /*05HRKG2A      18.0
 REMOVE UNIT 2S FROM BUS 247250                    /*05HRKG2S      18.0
END
243206 to 246999 ckt 1
246999 to 242928 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP
05DUMONT-05SORENS 765.0 kV Ckt 1 line
AEP_P7-1_#11046___SRT-A
TowerAC100.51 %4142.0B4163.0621.35
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC143.99 %1075.0B1547.919.44
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC143.99 %1075.0B1547.879.44
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Base Case
SingleAC108.83 %1075.0A1169.936.0
GD1ATSI/ITCT
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-025T_SRT-A-1
TowerAC114.15 %1660.0B1894.947.02
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC146.62 %971.0B1423.7211.06
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC146.52 %971.0B1422.6911.16
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC146.52 %971.0B1422.6911.16
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC126.45 %1399.0B1768.9711.84
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC126.44 %1399.0B1768.911.84
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC126.42 %1399.0B1768.6711.78
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC100.5 %1399.0B1405.957.11
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC100.5 %1399.0B1405.937.11
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC110.61 %1399.0B1547.4111.94
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC110.58 %1399.0B1546.9812.0
GD1CE
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC110.57 %1399.0B1546.9212.0
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC126.43 %970.0STE1226.411.16
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC126.43 %970.0STE1226.411.16
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC126.41 %970.0STE1226.1511.06
GD1CE
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
COMED_P4_112-65-BT5-6___SRT-A
BreakerAC115.85 %1469.0STE1701.8714.92
GD1CE
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
COMED_P4_112-65-BT2-3___SRT-A
BreakerAC118.88 %1469.0STE1746.3315.31
GD1CE
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_112-65-BT5-6___SRT-A
BreakerAC116.01 %1469.0STE1704.1214.92
GD1CE
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_112-65-BT2-3___SRT-A
BreakerAC119.03 %1469.0STE1748.5215.31

Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P7-1_#11046___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11046___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.51 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4163.06
MW Contribution:21.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
958012AF2-095 E
Adder
12.29882352941176610.454
934111AD2-000 2
Adder
9.7294117647058828.27
966442AG1-513 E
Adder
1.26235294117647071.073
274683WAUKEGAN ;8U
Adder
73.0517647058823662.094
290051GSG-6; E
Adder
17.55176470588235614.919
959082AF2-199 E
Adder
5.9694117647058835.074
274790SE CHICAG;7U
Adder
7.93999999999999956.749
274791SE CHICAG;8U
Adder
7.93999999999999956.749
274789SE CHICAG;6U
Adder
7.93999999999999956.749
966092AG1-478 E
Adder
0.84235294117647050.716
274682WAUKEGAN ;7U
Adder
67.7223529411764757.564
942651AE2-281 C
Adder
1.40235294117647061.192
942652AE2-281 E
Adder
8.6164705882352957.324
962691AG1-118 C
Adder
36.9352941176470631.395
962692AG1-118 E
Adder
24.62352941176470720.93
938851AE1-113 C
Adder
13.18235294117647211.205
272363ESS H440 ; R
Adder
4.4117647058823533.75
959091AF2-200 C
Adder
23.87882352941176520.297
274788SE CHICAG;5U
Adder
7.93999999999999956.749
958011AF2-095 C
Adder
18.44823529411764815.681
933411AC2-154 C
Adder
4.0564705882352943.448
274687WILL CNTY;4U
Adder
108.1341176470588391.914
966091AG1-478 C
Adder
3.35058823529411762.848
966441AG1-513 C
Adder
0.84235294117647050.716
959081AF2-199 C
Adder
11.9410.149
24344005CKG1
50/50
36.32436.324
961501AF2-441 C
Adder
17.18352941176470614.606
293519PILOT HIL;1E
Adder
29.89176470588235525.408
939351AE1-166 C
Adder
16.6614.161
274675JOLIET 29;7U
Adder
116.6376470588235399.142
274674JOLIET 9 ;6U
Adder
59.4611764705882450.542
293061N-015 E
Adder
25.37882352941176521.572
943121AE2-341 C
Adder
21.2623529411764718.073
939321AE1-163 C
Adder
9.8188235294117648.346
295111SUBLETTE E
Adder
4.5682352941176473.883
274660LASCO STA;1U
50/50
39.69139.691
943592AF1-030 E
Adder
6.9952941176470595.946
943591AF1-030 C
Adder
14.1412.019
936292AD2-038 E
Adder
24.7670588235294121.052
290021O50 E
Adder
31.95647058823529527.163
937002AD2-134 E
Adder
16.9705882352941214.425
270100AB1-080 CT1
50/50
8.4898.489
270101AB1-080 CT2
50/50
8.4898.489
965791AG1-447 C
50/50
12.24212.242
965682AG1-436 E
50/50
11.12911.129
957371AF2-031 C
Adder
1.71647058823529421.459
274770LINCOLN ;1U
50/50
2.8472.847
274773LINCOLN ;4U
50/50
2.8472.847
274772LINCOLN ;3U
50/50
2.8472.847
274771LINCOLN ;2U
50/50
2.8472.847
960591AF2-350 C
Adder
12.81058823529411810.889
960592AF2-350 E
Adder
8.5411764705882357.26
275149KELLYCK ;1E
Adder
29.89176470588235525.408
934722AD1-100 E
Adder
149.50823529411764127.082
960751AF2-366 C
Adder
11.6435294117647079.897
942422AE2-255 E
Adder
14.97882352941176412.732
960582AF2-349 E
Adder
60.28705882352941451.244
957331AF2-027 C
Adder
4.1035294117647063.488
936511AD2-066 C
Adder
13.97882352941176411.882
936512AD2-066 E
Adder
9.3188235294117667.921
295109WESTBROOK E
Adder
9.3964705882352947.987
960681AF2-359 C
50/50
16.69316.693
941551AE2-152 C
Adder
19.2223529411764716.339
274676JOLIET 29;8U
Adder
116.6341176470588299.139
958481AF2-142 C
Adder
18.34588235294117515.594
957332AF2-027 E
Adder
6.1552941176470595.232
960682AF2-359 E
50/50
11.12911.129
274792SE CHICAG;9U
Adder
7.9305882352941186.741
941552AE2-152 E
Adder
12.8152941176470610.893
957372AF2-031 E
Adder
2.5752941176470592.189
274774LINCOLN ;5U
50/50
2.8472.847
293644O22 E1
Adder
23.4329411764705919.918
960281AF2-319 C
Adder
4.0788235294117653.467
960752AF2-366 E
Adder
7.7623529411764716.598
957471AF2-041 C
Adder
35.81882352941176630.446
958482AF2-142 E
Adder
12.2305882352941210.396
938852AE1-113 E
Adder
46.73529411764706539.725
274890CAYUG;1U E
Adder
15.40235294117647213.092
270102AB1-080 ST
50/50
9.1849.184
965681AG1-436 C
50/50
16.69316.693
293645O22 E2
Adder
26.8376470588235322.812
960282AF2-319 E
Adder
6.117647058823535.2
918052AA1-018 E OP
Adder
26.60117647058823622.611
961502AF2-441 E
Adder
25.77529411764705721.909
274661LASCO STA;2U
50/50
39.8239.82
943122AE2-341 E
Adder
10.4411764705882368.875
939322AE1-163 E
Adder
60.3141176470588351.267
24796705OLIV SLR E
Adder
0.52823529411764710.449
24344105CKG2
50/50
55.71355.713
274793SE CHICAG;0U
Adder
7.9305882352941186.741
274795SE CHICAG;2U
Adder
7.9305882352941186.741
274776LINCOLN ;7U
50/50
2.8472.847
936372AD2-047 E
Adder
35.4435294117647130.127
276591L-013 2
Adder
6.0611764705882365.152
962781AG1-127 C
Adder
11.6764705882352959.925
933911AD1-013 C
Adder
3.08941176470588232.626
910542X3-005 E
Adder
1.20352941176470571.023
939352AE1-166 E
Adder
15.37764705882352913.071
294392P-010 E
Adder
32.2305882352941227.396
959352AF2-226 E
Adder
6.117647058823535.2
934101AD2-000 1
Adder
9.6658823529411778.216
958492AF2-143 E
Adder
12.0223529411764710.219
942421AE2-255 C
Adder
4.9929411764705884.244
290108LEEDK;1U E
Adder
40.1234.102
916221Z1-073 E
Adder
12.36823529411764810.513
957472AF2-041 E
Adder
17.90941176470588315.223
959092AF2-200 E
Adder
15.91882352941176613.531
944932AF1-158 E
Adder
12.53176470588235210.652
959351AF2-226 C
Adder
4.0788235294117653.467
958491AF2-143 C
Adder
18.03411764705882415.329
933912AD1-013 E
Adder
4.9341176470588244.194
274794SE CHICAG;1U
Adder
7.9305882352941186.741
274775LINCOLN ;6U
50/50
2.8472.847
274777LINCOLN ;8U
50/50
2.8472.847
936371AD2-047 C
Adder
7.2600000000000016.171
936461AD2-060 C
Adder
4.2705882352941183.63
933412AC2-154 E
Adder
6.6188235294117655.626
962782AG1-127 E
Adder
7.77058823529411856.605
946671AF1-331 C
Adder
4.0117647058823533.41
276675AE2-062 E
Adder
0.249411764705882360.212
920272AA2-123 E
Adder
4.76941176470588254.054
276170Z1-108 E
Adder
4.837647058823534.112
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
1.4661.466
TVALTFEXP_TVA->PJM
CLTF
5.1695.169
O66PJM->LTFIMP_O-066
CMTX_NF
33.48333.483
NYPJM->LTFIMP_NY
CLTF
2.7622.762
LGEELTFEXP_LGEE->PJM
CLTF
1.661.66
WECLTFEXP_WEC->PJM
CLTF
6.4986.498
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.9160.916
CBM West 1LTFEXP_CBM-W1->PJM
CBM
235.985235.985
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.62846.628
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
23.96923.969
LAGNLTFEXP_LAGN->PJM
CLTF
9.4439.443
G-007PJM->LTFIMP_G-007
CMTX_NF
5.225.22
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.4090.409
SIGELTFEXP_SIGE->PJM
CLTF
0.560.56

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.99 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1547.91
MW Contribution:9.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274790SE CHICAG;7U
80/20
7.2327.232
274791SE CHICAG;8U
80/20
7.2327.232
274789SE CHICAG;6U
80/20
7.2327.232
274682WAUKEGAN ;7U
Adder
46.7423529411764739.731
942651AE2-281 C
Adder
0.96470588235294120.82
962691AG1-118 C
Adder
25.1023529411764721.337
938851AE1-113 C
Adder
9.0329411764705887.678
959091AF2-200 C
Adder
16.12823529411764813.709
959341AF2-225 C
Adder
7.0364705882352945.981
965091AG1-374 C
Adder
19.1976470588235316.318
274800UNIV PARK;3U
80/20
1.3961.396
941551AE2-152 C
Adder
13.39529411764705811.386
274676JOLIET 29;8U
Adder
82.4152941176470670.053
958481AF2-142 C
Adder
12.7223529411764710.814
274788SE CHICAG;5U
80/20
7.2327.232
274798UNIV PARK;1U
80/20
1.4061.406
958011AF2-095 C
80/20
13.59713.597
933411AC2-154 C
80/20
2.992.99
274687WILL CNTY;4U
Adder
78.0176470588235366.315
966091AG1-478 C
Adder
2.38941176470588262.031
966441AG1-513 C
Adder
0.57647058823529410.49
959081AF2-199 C
Adder
8.0647058823529436.855
942111AE2-223 C
Adder
2.17764705882352951.851
939741AE1-205 C
Adder
9.3811764705882357.974
957371AF2-031 C
80/20
1.5531.553
960591AF2-350 C
80/20
9.4429.442
960751AF2-366 C
Adder
7.9070588235294126.721
961501AF2-441 C
80/20
14.87514.875
274826FISK ;BP
80/20
2.6552.655
939351AE1-166 C
Adder
11.6094117647058829.868
274675JOLIET 29;7U
Adder
82.4117647058823570.05
274674JOLIET 9 ;6U
Adder
42.3282352941176535.979
943121AE2-341 C
Adder
14.46117647058823512.292
939321AE1-163 C
Adder
6.7517647058823535.739
934101AD2-000 1
Adder
6.542352941176475.561
942421AE2-255 C
Adder
3.42117647058823552.908
926821AC1-168 C
Adder
1.28941176470588251.096
959611AF2-252 C
Adder
2.1329411764705881.813
274754CRETE EC ;4U
80/20
1.941.94
274887PILOT HIL;1U
80/20
0.8970.897
934111AD2-000 2
Adder
6.8035294117647065.783
274683WAUKEGAN ;8U
Adder
50.3941176470588342.835
276164X3-005 C
80/20
0.0990.099
274827FISK ;RP
80/20
1.8821.882
957331AF2-027 C
Adder
2.82588235294117672.402
936511AD2-066 C
Adder
9.5376470588235298.107
939061AE1-134 2
Adder
1.54823529411764721.316
959351AF2-226 C
Adder
2.89058823529411772.457
958491AF2-143 C
Adder
12.40117647058823610.541
965931AG1-462 C
Adder
18.16117647058823415.437
274888KELLY CRK;1U
80/20
0.8970.897
943591AF1-030 C
Adder
9.6164705882352938.174
274751CRETE EC ;1U
80/20
1.941.94
274723RIVER EC ;12
80/20
5.1225.122
274724RIVER EC ;11
80/20
5.1235.123
960281AF2-319 C
Adder
2.89058823529411772.457
957471AF2-041 C
Adder
24.1929411764705920.564
938861AE1-114 C
Adder
4.4423529411764713.776
274792SE CHICAG;9U
80/20
7.1437.143
274799UNIV PARK;2U
80/20
1.3961.396
274801UNIV PARK;4U
80/20
1.3961.396
946321AF1-296 C
Adder
4.0305882352941183.426
274753CRETE EC ;3U
80/20
1.941.94
274793SE CHICAG;0U
80/20
7.1437.143
274795SE CHICAG;2U
80/20
7.1437.143
962781AG1-127 C
Adder
7.92823529411764756.739
933911AD1-013 C
Adder
2.08705882352941161.774
274752CRETE EC ;2U
80/20
1.941.94
274794SE CHICAG;1U
80/20
7.1437.143
936371AD2-047 C
80/20
5.355.35
936461AD2-060 C
80/20
3.1473.147
946671AF1-331 C
Adder
2.71058823529411752.304
960611AF2-352 C
Adder
2.1329411764705881.813
991247J1684 G
External Queue
33.61624908447265633.616249084472656
990647J1355
External Queue
42.268421173095742.2684211730957
955742J1058 G
External Queue
35.2828559875488335.28285598754883
990552J1334 G
External Queue
40.5239410400390640.52394104003906
990557J1335 G
External Queue
40.5239410400390640.52394104003906
990562J1336 G
External Queue
40.5239410400390640.52394104003906
990577J1339
External Queue
26.57409286499023426.574092864990234
991332J1785
External Queue
13.53217792510986313.532177925109863
990762J1386
External Queue
12.93081378936767612.930813789367676
990547J1333 G
External Queue
40.5239410400390640.52394104003906
990582J1340
External Queue
26.57409286499023426.574092864990234
990662J1358
External Queue
14.93047237396240214.930472373962402
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8260.826
TVALTFEXP_TVA->PJM
CLTF
1.7951.795
NYPJM->LTFIMP_NY
CLTF
1.271.27
WECLTFEXP_WEC->PJM
CLTF
4.4234.423
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5520.552
CBM West 1LTFEXP_CBM-W1->PJM
CBM
118.129118.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.88718.887
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.510.51
MECLTFEXP_MEC->PJM
CLTF
14.93414.934
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.4171.417
LAGNLTFEXP_LAGN->PJM
CLTF
4.3274.327
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2810.281
SIGELTFEXP_SIGE->PJM
CLTF
0.060.06

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.99 %
Rating:1075.0 MVA
Rating Type:B
MVA to Mitigate:1547.87
MW Contribution:9.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274790SE CHICAG;7U
80/20
7.2327.232
274791SE CHICAG;8U
80/20
7.2327.232
274789SE CHICAG;6U
80/20
7.2327.232
274682WAUKEGAN ;7U
Adder
46.7423529411764739.731
942651AE2-281 C
Adder
0.96470588235294120.82
962691AG1-118 C
Adder
25.1023529411764721.337
938851AE1-113 C
Adder
9.0329411764705887.678
959091AF2-200 C
Adder
16.12823529411764813.709
959341AF2-225 C
Adder
7.0364705882352945.981
965091AG1-374 C
Adder
19.1976470588235316.318
274800UNIV PARK;3U
80/20
1.3961.396
941551AE2-152 C
Adder
13.39529411764705811.386
274676JOLIET 29;8U
Adder
82.4152941176470670.053
958481AF2-142 C
Adder
12.7223529411764710.814
274788SE CHICAG;5U
80/20
7.2327.232
274798UNIV PARK;1U
80/20
1.4061.406
958011AF2-095 C
80/20
13.59713.597
933411AC2-154 C
80/20
2.992.99
274687WILL CNTY;4U
Adder
78.0176470588235366.315
966091AG1-478 C
Adder
2.38941176470588262.031
966441AG1-513 C
Adder
0.57647058823529410.49
959081AF2-199 C
Adder
8.0647058823529436.855
942111AE2-223 C
Adder
2.17764705882352951.851
939741AE1-205 C
Adder
9.3811764705882357.974
957371AF2-031 C
80/20
1.5531.553
960591AF2-350 C
80/20
9.4429.442
960751AF2-366 C
Adder
7.9070588235294126.721
961501AF2-441 C
80/20
14.87514.875
274826FISK ;BP
80/20
2.6552.655
939351AE1-166 C
Adder
11.6094117647058829.868
274675JOLIET 29;7U
Adder
82.4117647058823570.05
274674JOLIET 9 ;6U
Adder
42.3282352941176535.979
943121AE2-341 C
Adder
14.46117647058823512.292
939321AE1-163 C
Adder
6.7517647058823535.739
934101AD2-000 1
Adder
6.542352941176475.561
942421AE2-255 C
Adder
3.42117647058823552.908
926821AC1-168 C
Adder
1.28941176470588251.096
959611AF2-252 C
Adder
2.1329411764705881.813
274754CRETE EC ;4U
80/20
1.941.94
274887PILOT HIL;1U
80/20
0.8970.897
934111AD2-000 2
Adder
6.8035294117647065.783
274683WAUKEGAN ;8U
Adder
50.3941176470588342.835
276164X3-005 C
80/20
0.0990.099
274827FISK ;RP
80/20
1.8821.882
957331AF2-027 C
Adder
2.82588235294117672.402
936511AD2-066 C
Adder
9.5376470588235298.107
939061AE1-134 2
Adder
1.54823529411764721.316
959351AF2-226 C
Adder
2.89058823529411772.457
958491AF2-143 C
Adder
12.40117647058823610.541
965931AG1-462 C
Adder
18.16117647058823415.437
274888KELLY CRK;1U
80/20
0.8970.897
943591AF1-030 C
Adder
9.6164705882352938.174
274751CRETE EC ;1U
80/20
1.941.94
274723RIVER EC ;12
80/20
5.1225.122
274724RIVER EC ;11
80/20
5.1235.123
960281AF2-319 C
Adder
2.89058823529411772.457
957471AF2-041 C
Adder
24.1929411764705920.564
938861AE1-114 C
Adder
4.4423529411764713.776
274792SE CHICAG;9U
80/20
7.1437.143
274799UNIV PARK;2U
80/20
1.3961.396
274801UNIV PARK;4U
80/20
1.3961.396
946321AF1-296 C
Adder
4.0305882352941183.426
274753CRETE EC ;3U
80/20
1.941.94
274793SE CHICAG;0U
80/20
7.1437.143
274795SE CHICAG;2U
80/20
7.1437.143
962781AG1-127 C
Adder
7.92823529411764756.739
933911AD1-013 C
Adder
2.08705882352941161.774
274752CRETE EC ;2U
80/20
1.941.94
274794SE CHICAG;1U
80/20
7.1437.143
936371AD2-047 C
80/20
5.355.35
936461AD2-060 C
80/20
3.1473.147
946671AF1-331 C
Adder
2.71058823529411752.304
960611AF2-352 C
Adder
2.1329411764705881.813
991247J1684 G
External Queue
33.61624908447265633.616249084472656
990647J1355
External Queue
42.268421173095742.2684211730957
955742J1058 G
External Queue
35.2828559875488335.28285598754883
990552J1334 G
External Queue
40.5239410400390640.52394104003906
990557J1335 G
External Queue
40.5239410400390640.52394104003906
990562J1336 G
External Queue
40.5239410400390640.52394104003906
990577J1339
External Queue
26.57409286499023426.574092864990234
991332J1785
External Queue
13.53217792510986313.532177925109863
990762J1386
External Queue
12.93081378936767612.930813789367676
990547J1333 G
External Queue
40.5239410400390640.52394104003906
990582J1340
External Queue
26.57409286499023426.574092864990234
990662J1358
External Queue
14.93047237396240214.930472373962402
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8260.826
TVALTFEXP_TVA->PJM
CLTF
1.7951.795
NYPJM->LTFIMP_NY
CLTF
1.271.27
WECLTFEXP_WEC->PJM
CLTF
4.4234.423
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5520.552
CBM West 1LTFEXP_CBM-W1->PJM
CBM
118.129118.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.88718.887
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.510.51
MECLTFEXP_MEC->PJM
CLTF
14.93414.934
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.4171.417
LAGNLTFEXP_LAGN->PJM
CLTF
4.3274.327
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2810.281
SIGELTFEXP_SIGE->PJM
CLTF
0.060.06

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.83 %
Rating:1075.0 MVA
Rating Type:A
MVA to Mitigate:1169.93
MW Contribution:6.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274790SE CHICAG;7U
80/20
5.5385.538
274791SE CHICAG;8U
80/20
5.5385.538
274789SE CHICAG;6U
80/20
5.5385.538
274682WAUKEGAN ;7U
Adder
27.29294117647059223.199
942651AE2-281 C
Adder
0.58941176470588240.501
962691AG1-118 C
Adder
14.20823529411764812.077
938851AE1-113 C
Adder
5.4270588235294124.613
959091AF2-200 C
Adder
9.2294117647058827.845
959341AF2-225 C
Adder
4.1082352941176473.492
965091AG1-374 C
Adder
11.249.554
274800UNIV PARK;3U
80/20
0.9170.917
941551AE2-152 C
Adder
7.8141176470588246.642
274676JOLIET 29;8U
Adder
49.9529411764705942.46
958481AF2-142 C
Adder
7.8258823529411776.652
274788SE CHICAG;5U
80/20
5.5385.538
274798UNIV PARK;1U
80/20
0.9230.923
958011AF2-095 C
80/20
8.6418.641
933411AC2-154 C
80/20
1.91.9
274687WILL CNTY;4U
Adder
48.5929411764705941.304
966091AG1-478 C
Adder
1.46941176470588241.249
966441AG1-513 C
Adder
0.32705882352941180.278
959081AF2-199 C
Adder
4.6141176470588243.922
942111AE2-223 C
Adder
1.2717647058823531.081
939741AE1-205 C
Adder
5.4776470588235294.656
957371AF2-031 C
80/20
1.1831.183
960591AF2-350 C
80/20
66
960751AF2-366 C
Adder
4.4776470588235293.806
961501AF2-441 C
80/20
10.91610.916
274826FISK ;BP
80/20
1.7681.768
939351AE1-166 C
Adder
6.7717647058823545.756
274675JOLIET 29;7U
Adder
49.9447058823529542.453
274674JOLIET 9 ;6U
Adder
25.73058823529411821.871
943121AE2-341 C
Adder
7.99529411764705966.796
939321AE1-163 C
Adder
4.1294117647058823.51
934101AD2-000 1
Adder
3.68941176470588243.136
942421AE2-255 C
Adder
2.0552941176470591.747
926821AC1-168 C
Adder
0.75294117647058820.64
959611AF2-252 C
Adder
1.24941176470588241.062
274754CRETE EC ;4U
80/20
1.4551.455
274887PILOT HIL;1U
80/20
0.570.57
934111AD2-000 2
Adder
4.077647058823533.466
274683WAUKEGAN ;8U
Adder
29.42352941176470825.01
276164X3-005 C
80/20
0.070.07
274827FISK ;RP
80/20
1.2531.253
957331AF2-027 C
Adder
1.64941176470588241.402
936511AD2-066 C
Adder
5.6788235294117654.827
939061AE1-134 2
Adder
0.89294117647058820.759
959351AF2-226 C
Adder
1.80588235294117651.535
958491AF2-143 C
Adder
7.5847058823529416.447
965931AG1-462 C
Adder
10.5505882352941188.968
274888KELLY CRK;1U
80/20
0.570.57
943591AF1-030 C
Adder
5.3176470588235294.52
274751CRETE EC ;1U
80/20
1.4551.455
274723RIVER EC ;12
80/20
3.8963.896
274724RIVER EC ;11
80/20
3.9023.902
960281AF2-319 C
Adder
1.80588235294117651.535
957471AF2-041 C
Adder
13.84352941176470611.767
938861AE1-114 C
Adder
2.562.176
274792SE CHICAG;9U
80/20
5.4655.465
274799UNIV PARK;2U
80/20
0.9170.917
274801UNIV PARK;4U
80/20
0.9170.917
946321AF1-296 C
Adder
2.34000000000000031.989
274753CRETE EC ;3U
80/20
1.4551.455
274793SE CHICAG;0U
80/20
5.4655.465
274795SE CHICAG;2U
80/20
5.4655.465
962781AG1-127 C
Adder
4.4894117647058823.816
933911AD1-013 C
Adder
1.18705882352941171.009
274752CRETE EC ;2U
80/20
1.4551.455
274794SE CHICAG;1U
80/20
5.4655.465
936371AD2-047 C
80/20
3.43.4
936461AD2-060 C
80/20
22
946671AF1-331 C
Adder
1.54235294117647051.311
960611AF2-352 C
Adder
1.24941176470588241.062
991247J1684 G
External Queue
33.68902206420898433.689022064208984
990647J1355
External Queue
45.41125869750976645.411258697509766
955742J1058 G
External Queue
34.2569389343261734.25693893432617
990552J1334 G
External Queue
40.5459747314453140.54597473144531
990557J1335 G
External Queue
40.5459747314453140.54597473144531
990562J1336 G
External Queue
40.5459747314453140.54597473144531
990577J1339
External Queue
26.6973209381103526.69732093811035
991332J1785
External Queue
15.41609477996826215.416094779968262
991337J1802
External Queue
11.39966201782226611.399662017822266
990762J1386
External Queue
12.26621055603027312.266210556030273
990547J1333 G
External Queue
40.5459747314453140.54597473144531
990582J1340
External Queue
26.6973209381103526.69732093811035
990662J1358
External Queue
15.6888904571533215.68889045715332
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.4540.454
TVALTFEXP_TVA->PJM
CLTF
1.1741.174
NYPJM->LTFIMP_NY
CLTF
0.7460.746
WECLTFEXP_WEC->PJM
CLTF
2.5782.578
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2990.299
CBM West 1LTFEXP_CBM-W1->PJM
CBM
75.73675.736
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.85611.856
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.2290.229
MECLTFEXP_MEC->PJM
CLTF
8.7698.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.6110.611
LAGNLTFEXP_LAGN->PJM
CLTF
2.6762.676
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1480.148
SIGELTFEXP_SIGE->PJM
CLTF
0.0530.053

Details for 19MON12-02LALLENDORF 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-025T_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI/ITCT
Facility Description:
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-025T_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:114.15 %
Rating:1660.0 MVA
Rating Type:B
MVA to Mitigate:1894.94
MW Contribution:7.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
24752805COVRT1
50/50
4.6664.666
958381AF2-132 C
Adder
13.51647058823529511.489
964862AG1-349 E
Adder
7.7788235294117656.612
24791305MDL-4G E
Adder
6.117647058823535.2
958012AF2-095 E
Adder
4.042352941176473.436
939391AE1-170 C
Adder
6.1764705882352945.25
962601AG1-109 C
50/50
2.5432.543
958392AF2-133 E
Adder
8.8964705882352947.562
274790SE CHICAG;7U
Adder
2.69176470588235262.288
274791SE CHICAG;8U
Adder
2.69176470588235262.288
274789SE CHICAG;6U
Adder
2.69176470588235262.288
966092AG1-478 E
Adder
0.27764705882352940.236
943002AE2-323 E
Adder
2.54117647058823562.16
958382AF2-132 E
Adder
9.0105882352941177.659
964861AG1-349 C
Adder
11.6682352941176479.918
274788SE CHICAG;5U
Adder
2.69176470588235262.288
24791205MDL-3G E
Adder
5.8752941176470594.994
958011AF2-095 C
Adder
6.0635294117647065.154
933411AC2-154 C
Adder
1.33294117647058831.133
274687WILL CNTY;4U
Adder
35.5494117647058830.217
966091AG1-478 C
Adder
1.10117647058823540.936
940582AE2-045 E
Adder
8.4388235294117657.173
961501AF2-441 C
Adder
5.7635294117647064.899
293519PILOT HIL;1E
Adder
9.8247058823529438.351
939351AE1-166 C
Adder
5.4070588235294124.596
274675JOLIET 29;7U
Adder
38.1870588235294232.459
274674JOLIET 9 ;6U
Adder
19.46705882352941316.547
941781AE2-181 C
Adder
-2.6894117647058824-2.286
944961AF1-161 C
50/50
2.5432.543
24307105BERRINSP G
50/50
0.0540.054
964402AG1-302 E
Adder
9.0105882352941177.659
964401AG1-302 C
Adder
13.51647058823529511.489
943001AE2-323 C
Adder
5.1835294117647064.406
944161AF1-084 C
50/50
5.6125.612
24441205WTRV SLR C
50/50
0.0410.041
965791AG1-447 C
Adder
4.497647058823533.823
965682AG1-436 E
Adder
4.0882352941176483.475
945502AF1-215 E
Adder
9.1941176470588257.815
959142AF2-205 E
Adder
5.8917647058823535.008
957371AF2-031 C
Adder
0.58117647058823530.494
24790705MDL-2G E
Adder
5.8823529411764715
960591AF2-350 C
Adder
4.2105882352941183.579
960592AF2-350 E
Adder
2.8070588235294122.386
275149KELLYCK ;1E
Adder
9.8247058823529438.351
934722AD1-100 E
Adder
48.5211764705882441.243
945641AF1-229 C
Adder
-7.210588235294117-6.129
24753305COVRT6
50/50
2.2822.282
24753105COVRT4
50/50
2.8062.806
957841AF2-078 C
Adder
8.5011764705882367.226
957842AF2-078 E
Adder
5.6670588235294124.817
943961AF1-064 C
Adder
-3.6247058823529414-3.081
960681AF2-359 C
Adder
6.1329411764705885.213
24753205COVRT5
50/50
2.7852.785
945421AF1-207 C
Adder
2.40823529411764752.047
941551AE2-152 C
Adder
6.2388235294117655.303
274676JOLIET 29;8U
Adder
38.1870588235294232.459
247969Z2-116 E
Adder
0.118823529411764720.101
957891AF2-083 C
Adder
9.7458823529411778.284
961051AF2-396 C
50/50
20.11920.119
939392AE1-170 E
Adder
8.5294117647058827.25
960682AF2-359 E
Adder
4.0882352941176483.475
958402AF2-134 E
Adder
3.06470588235294142.605
274792SE CHICAG;9U
Adder
2.6952941176470592.291
941552AE2-152 E
Adder
4.1588235294117653.535
936142AD2-020 E
50/50
3.8753.875
944162AF1-084 E
50/50
3.2053.205
957372AF2-031 E
Adder
0.8717647058823530.741
24790605MDL-1G E
Adder
12.21529411764705810.383
936632AD2-079 E O1
Adder
0.73411764705882350.624
965681AG1-436 C
Adder
6.1329411764705885.213
940581AE2-045 C
Adder
6.1458823529411775.224
961502AF2-441 E
Adder
8.6447058823529417.348
939161AE1-146 C
Adder
-6.9141176470588235-5.877
24796705OLIV SLR E
Adder
0.217647058823529420.185
274793SE CHICAG;0U
Adder
2.6952941176470592.291
274795SE CHICAG;2U
Adder
2.6952941176470592.291
946581AF1-322 C
Adder
5.8270588235294124.953
936372AD2-047 E
Adder
11.6494117647058819.902
945112AF1-176 E
Adder
14.24588235294117712.109
936141AD2-020 C
50/50
6.2956.295
24752905COVRT2
50/50
4.6664.666
910542X3-005 E
Adder
0.401176470588235360.341
939352AE1-166 E
Adder
4.9905882352941174.242
960841AF2-375 C
Adder
-7.203529411764706-6.123
945111AF1-176 C
Adder
15.36823529411764813.063
957892AF2-083 E
Adder
4.8729411764705884.142
944932AF1-158 E
Adder
5.25529411764705844.467
24796605WTRV SLR E
50/50
0.250.25
24753005COVRT3
50/50
4.6664.666
959141AF2-205 C
Adder
8.8364705882352947.511
930041AB1-006 E1
Adder
10.5611764705882368.977
247604X1-042
50/50
0.0690.069
958391AF2-133 C
Adder
13.34588235294117611.344
274794SE CHICAG;1U
Adder
2.6952941176470592.291
945422AF1-207 E
Adder
10.3435294117647068.792
930042AB1-006 E2
Adder
1.50823529411764711.282
946582AF1-322 E
Adder
8.0458823529411776.839
247943T-127 E
Adder
5.5352941176470594.705
936371AD2-047 C
Adder
2.38588235294117632.028
936461AD2-060 C
Adder
1.4035294117647061.193
933412AC2-154 E
Adder
2.1752941176470591.849
276675AE2-062 E
Adder
0.081176470588235310.069
990527J1329 G
External Queue
4.0417356491088874.041735649108887
990142J1224 G
External Queue
34.1838302612304734.18383026123047
991182J1586 G
External Queue
48.1941452026367248.19414520263672
955782J1062 G
External Queue
38.120239257812538.1202392578125
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.2310.231
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.3369.336
CPLELTFEXP_CPLE->PJM
CLTF
0.4660.466
TVALTFEXP_TVA->PJM
CLTF
3.7743.774
O66PJM->LTFIMP_O-066
CMTX_NF
13.49813.498
NYPJM->LTFIMP_NY
CLTF
1.2751.275
LGEELTFEXP_LGEE->PJM
CLTF
1.7551.755
WECLTFEXP_WEC->PJM
CLTF
2.1642.164
CBM West 1LTFEXP_CBM-W1->PJM
CBM
219.895219.895
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.93824.938
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.8318.831
LAGNLTFEXP_LAGN->PJM
CLTF
5.4355.435
G-007PJM->LTFIMP_G-007
CMTX_NF
2.0942.094
SIGELTFEXP_SIGE->PJM
CLTF
0.3980.398

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.62 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1423.72
MW Contribution:11.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966092AG1-478 E
Adder
0.44117647058823530.375
274682WAUKEGAN ;7U
Adder
34.8235294117647129.6
942651AE2-281 C
Adder
0.75764705882352950.644
942652AE2-281 E
Adder
4.6529411764705893.955
962691AG1-118 C
Adder
18.6752941176470615.874
962692AG1-118 E
Adder
12.45058823529411810.583
938851AE1-113 C
Adder
6.75.695
272363ESS H440 ; R
Adder
2.21411764705882331.882
959091AF2-200 C
Adder
11.97176470588235410.176
940502AE2-035 E
Adder
2.84588235294117682.419
960681AF2-359 C
50/50
63.75263.752
274813UNIV PK N;9U
50/50
1.8991.899
274811UNIV PK N;7U
50/50
1.9151.915
941551AE2-152 C
Adder
9.7929411764705888.324
274676JOLIET 29;8U
Adder
61.7682352941176552.503
958481AF2-142 C
Adder
10.2035294117647068.673
957332AF2-027 E
Adder
3.15764705882352952.684
274891CAYUG;2U E
Adder
11.395294117647069.686
926822AC1-168 E
Adder
6.4258823529411765.462
274814UNIV PK N;0U
50/50
1.8911.891
274807UNIV PK N;3U
50/50
1.9151.915
274816UNIV PK N;YU
50/50
1.9151.915
958011AF2-095 C
Adder
9.557647058823538.124
933411AC2-154 C
Adder
2.10235294117647081.787
274687WILL CNTY;4U
Adder
55.58000000000000547.243
966091AG1-478 C
Adder
1.7552941176470591.492
966441AG1-513 C
Adder
0.430588235294117660.366
959081AF2-199 C
Adder
5.9858823529411775.088
965791AG1-447 C
50/50
46.75146.751
965682AG1-436 E
50/50
42.50142.501
960591AF2-350 C
Adder
6.637647058823535.642
960592AF2-350 E
Adder
4.4247058823529413.761
275149KELLYCK ;1E
Adder
15.48823529411764713.165
934722AD1-100 E
Adder
76.1647058823529364.74
960751AF2-366 C
Adder
5.8811764705882354.999
942422AE2-255 E
Adder
7.61411764705882456.472
960582AF2-349 E
Adder
30.4847058823529425.912
937312AD2-172 E
Adder
2.84588235294117682.419
274859EASYR;U1 E
Adder
10.0658823529411758.556
293519PILOT HIL;1E
Adder
15.48823529411764713.165
939351AE1-166 C
Adder
8.4870588235294137.214
274675JOLIET 29;7U
Adder
61.79058823529411652.522
274674JOLIET 9 ;6U
Adder
31.0329411764705926.378
293061N-015 E
Adder
13.10117647058823411.136
943121AE2-341 C
Adder
10.7729411764705899.157
939321AE1-163 C
Adder
5.302352941176474.507
295111SUBLETTE E
Adder
2.29294117647058831.949
274860EASYR;U2 E
Adder
10.0658823529411758.556
910542X3-005 E
Adder
0.53058823529411770.451
939352AE1-166 E
Adder
7.8341176470588236.659
294392P-010 E
Adder
16.63882352941176614.143
959352AF2-226 E
Adder
3.01647058823529422.564
934101AD2-000 1
Adder
4.8788235294117654.147
958492AF2-143 E
Adder
6.4929411764705885.519
942421AE2-255 C
Adder
2.53764705882352942.157
290108LEEDK;1U E
Adder
20.2152941176470617.183
916221Z1-073 E
Adder
6.2070588235294125.276
957472AF2-041 E
Adder
8.9788235294117647.632
959092AF2-200 E
Adder
7.98117647058823556.784
926821AC1-168 C
Adder
0.95764705882352940.814
938862AE1-114 E
Adder
11.244705882352949.558
274815UNIV PK N;XU
50/50
1.9031.903
958012AF2-095 E
Adder
6.3717647058823535.416
934111AD2-000 2
Adder
5.0470588235294124.29
966442AG1-513 E
Adder
0.64470588235294120.548
274683WAUKEGAN ;8U
Adder
37.5458823529411831.914
290051GSG-6; E
Adder
8.8082352941176477.487
959082AF2-199 E
Adder
2.99294117647058842.544
958912AF2-182 E
Adder
28.6258823529411824.332
957331AF2-027 C
Adder
2.1047058823529411.789
936511AD2-066 C
Adder
7.1305882352941186.061
936512AD2-066 E
Adder
4.7541176470588244.041
295109WESTBROOK E
Adder
4.7152941176470594.008
939061AE1-134 2
Adder
1.14705882352941170.975
274808UNIV PK N;4U
50/50
1.9071.907
959351AF2-226 C
Adder
2.0105882352941181.709
958491AF2-143 C
Adder
9.748.279
933912AD1-013 E
Adder
2.47764705882352932.106
946152AF1-280 E
Adder
19.08352941176470816.221
293716O-029 E
Adder
4.46823529411764753.798
274805UNIV PK N;1U
50/50
1.9031.903
943592AF1-030 E
Adder
3.54470588235294143.013
943591AF1-030 C
Adder
7.1635294117647066.089
936292AD2-038 E
Adder
13.37529411764705911.369
290021O50 E
Adder
16.24352941176470813.807
937002AD2-134 E
Adder
8.5164705882352937.239
293644O22 E1
Adder
11.5517647058823549.819
960281AF2-319 C
Adder
2.0105882352941181.709
960752AF2-366 E
Adder
3.92117647058823553.333
957471AF2-041 C
Adder
17.9576470588235315.264
294763P-046 E
Adder
7.9094117647058826.723
938861AE1-114 C
Adder
3.2964705882352942.802
960682AF2-359 E
50/50
42.50142.501
274810UNIV PK N;6U
50/50
1.9071.907
274812UNIV PK N;8U
50/50
1.8991.899
941552AE2-152 E
Adder
6.5282352941176485.549
958482AF2-142 E
Adder
6.8023529411764715.782
938852AE1-113 E
Adder
23.75647058823529520.193
274890CAYUG;1U E
Adder
11.395294117647069.686
962012AG1-044 E
Adder
0.0529411764705882350.045
965681AG1-436 C
50/50
63.75263.752
293645O22 E2
Adder
13.2305882352941211.246
960282AF2-319 E
Adder
3.01647058823529422.564
918052AA1-018 E OP
Adder
14.7952941176470612.576
293715O-029 E
Adder
8.1494117647058816.927
943122AE2-341 E
Adder
5.2905882352941184.497
939322AE1-163 E
Adder
32.5729411764705927.687
293516O-009 E
Adder
15.7576470588235313.394
293717O-029 E
Adder
4.1070588235294123.491
936372AD2-047 E
Adder
18.36705882352941215.612
276591L-013 2
Adder
3.09411764705882362.63
962781AG1-127 C
Adder
5.8976470588235295.013
933911AD1-013 C
Adder
1.55058823529411781.318
936371AD2-047 C
Adder
3.76235294117647053.198
936461AD2-060 C
Adder
2.2129411764705881.881
933412AC2-154 E
Adder
3.42941176470588262.915
962782AG1-127 E
Adder
3.92470588235294133.336
946671AF1-331 C
Adder
2.01411764705882361.712
276170Z1-108 E
Adder
2.4670588235294122.097
920272AA2-123 E
Adder
2.4188235294117652.056
276675AE2-062 E
Adder
0.134117647058823540.114
276626AG1-044 E
Adder
0.061176470588235290.052
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6070.607
TVALTFEXP_TVA->PJM
CLTF
1.1671.167
O66PJM->LTFIMP_O-066
CMTX_NF
11.09411.094
NYPJM->LTFIMP_NY
CLTF
0.9310.931
WECLTFEXP_WEC->PJM
CLTF
3.2883.288
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4090.409
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.23368.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.47412.474
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.4090.409
MECLTFEXP_MEC->PJM
CLTF
10.92410.924
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.1721.172
LAGNLTFEXP_LAGN->PJM
CLTF
2.992.99
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7291.729
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.210.21
SIGELTFEXP_SIGE->PJM
CLTF
0.0150.015

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.52 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1422.69
MW Contribution:11.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966092AG1-478 E
Adder
0.44470588235294120.378
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
938851AE1-113 C
Adder
6.7458823529411775.734
272363ESS H440 ; R
Adder
2.22941176470588241.895
959091AF2-200 C
Adder
12.05294117647058810.245
940502AE2-035 E
Adder
2.8647058823529412.435
960681AF2-359 C
50/50
63.94963.949
274813UNIV PK N;9U
50/50
1.9091.909
274811UNIV PK N;7U
50/50
1.9251.925
941551AE2-152 C
Adder
9.8717647058823528.391
274676JOLIET 29;8U
Adder
62.29647058823529452.952
958481AF2-142 C
Adder
10.2776470588235318.736
957332AF2-027 E
Adder
3.1823529411764712.705
274891CAYUG;2U E
Adder
11.4552941176470599.737
926822AC1-168 E
Adder
6.4588235294117655.49
274814UNIV PK N;0U
50/50
1.9011.901
274807UNIV PK N;3U
50/50
1.9251.925
274816UNIV PK N;YU
50/50
1.9251.925
958011AF2-095 C
Adder
9.6458823529411778.199
933411AC2-154 C
Adder
2.1211764705882351.803
274687WILL CNTY;4U
Adder
56.08235294117647447.67
966091AG1-478 C
Adder
1.76941176470588251.504
966441AG1-513 C
Adder
0.434117647058823550.369
959081AF2-199 C
Adder
6.0258823529411775.122
965791AG1-447 C
50/50
46.89646.896
965682AG1-436 E
50/50
42.63342.633
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
275149KELLYCK ;1E
Adder
15.63058823529411813.286
934722AD1-100 E
Adder
76.7823529411764765.265
960751AF2-366 C
Adder
5.9247058823529415.036
942422AE2-255 E
Adder
7.6658823529411776.516
960582AF2-349 E
Adder
30.726.095
937312AD2-172 E
Adder
2.8647058823529412.435
274859EASYR;U1 E
Adder
10.1270588235294138.608
293519PILOT HIL;1E
Adder
15.63058823529411813.286
939351AE1-166 C
Adder
8.555294117647067.272
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
293061N-015 E
Adder
13.20352941176470711.223
943121AE2-341 C
Adder
10.8588235294117659.23
939321AE1-163 C
Adder
5.3388235294117654.538
295111SUBLETTE E
Adder
2.3082352941176471.962
274860EASYR;U2 E
Adder
10.1270588235294138.608
910542X3-005 E
Adder
0.53764705882352950.457
939352AE1-166 E
Adder
7.897647058823536.713
294392P-010 E
Adder
16.76941176470588214.254
959352AF2-226 E
Adder
3.0411764705882352.585
934101AD2-000 1
Adder
4.91411764705882354.177
958492AF2-143 E
Adder
6.537647058823535.557
942421AE2-255 C
Adder
2.5552941176470592.172
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
957472AF2-041 E
Adder
9.0400000000000017.684
959092AF2-200 E
Adder
8.0352941176470596.83
926821AC1-168 C
Adder
0.96235294117647050.818
938862AE1-114 E
Adder
11.315294117647069.618
274815UNIV PK N;XU
50/50
1.9131.913
958012AF2-095 E
Adder
6.4305882352941185.466
934111AD2-000 2
Adder
5.0882352941176484.325
966442AG1-513 E
Adder
0.65058823529411770.553
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
290051GSG-6; E
Adder
8.8682352941176487.538
959082AF2-199 E
Adder
3.01294117647058852.561
958912AF2-182 E
Adder
28.79647058823529424.477
957331AF2-027 C
Adder
2.1211764705882351.803
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
295109WESTBROOK E
Adder
4.7482352941176474.036
939061AE1-134 2
Adder
1.15294117647058810.98
274808UNIV PK N;4U
50/50
1.9171.917
959351AF2-226 C
Adder
2.0270588235294121.723
958491AF2-143 C
Adder
9.8058823529411778.335
933912AD1-013 E
Adder
2.49411764705882362.12
946152AF1-280 E
Adder
19.1976470588235316.318
293716O-029 E
Adder
4.4917647058823533.818
274805UNIV PK N;1U
50/50
1.9131.913
943592AF1-030 E
Adder
3.5729411764705883.037
943591AF1-030 C
Adder
7.2211764705882366.138
936292AD2-038 E
Adder
13.46705882352941211.447
290021O50 E
Adder
16.3552941176470613.902
937002AD2-134 E
Adder
8.5752941176470587.289
293644O22 E1
Adder
11.6458823529411759.899
960281AF2-319 C
Adder
2.0270588235294121.723
960752AF2-366 E
Adder
3.94941176470588263.357
957471AF2-041 C
Adder
18.07882352941176815.367
294763P-046 E
Adder
7.9611764705882366.767
938861AE1-114 C
Adder
3.3164705882352942.819
960682AF2-359 E
50/50
42.63342.633
274810UNIV PK N;6U
50/50
1.9171.917
274812UNIV PK N;8U
50/50
1.9091.909
941552AE2-152 E
Adder
6.5811764705882365.594
958482AF2-142 E
Adder
6.8517647058823535.824
938852AE1-113 E
Adder
23.91882352941176420.331
274890CAYUG;1U E
Adder
11.4552941176470599.737
962012AG1-044 E
Adder
0.0529411764705882350.045
965681AG1-436 C
50/50
63.94963.949
293645O22 E2
Adder
13.33882352941176411.338
960282AF2-319 E
Adder
3.0411764705882352.585
918052AA1-018 E OP
Adder
14.9023529411764712.667
293715O-029 E
Adder
8.1929411764705896.964
943122AE2-341 E
Adder
5.3317647058823534.532
939322AE1-163 E
Adder
32.7952941176470627.876
293516O-009 E
Adder
15.8423529411764713.466
293717O-029 E
Adder
4.1282352941176473.509
936372AD2-047 E
Adder
18.53411764705882415.754
276591L-013 2
Adder
3.11882352941176462.651
962781AG1-127 C
Adder
5.94117647058823555.05
933911AD1-013 C
Adder
1.56117647058823541.327
936371AD2-047 C
Adder
3.7964705882352943.227
936461AD2-060 C
Adder
2.2329411764705881.898
933412AC2-154 E
Adder
3.46117647058823552.942
962782AG1-127 E
Adder
3.9541176470588243.361
946671AF1-331 C
Adder
2.0282352941176471.724
276170Z1-108 E
Adder
2.48588235294117642.113
920272AA2-123 E
Adder
2.4364705882352942.071
276675AE2-062 E
Adder
0.135294117647058840.115
276626AG1-044 E
Adder
0.062352941176470590.053
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142
NYPJM->LTFIMP_NY
CLTF
0.9330.933
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.52 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1422.69
MW Contribution:11.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966092AG1-478 E
Adder
0.44470588235294120.378
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
938851AE1-113 C
Adder
6.7458823529411775.734
272363ESS H440 ; R
Adder
2.22941176470588241.895
959091AF2-200 C
Adder
12.05294117647058810.245
940502AE2-035 E
Adder
2.8647058823529412.435
960681AF2-359 C
50/50
63.94963.949
274813UNIV PK N;9U
50/50
1.9091.909
274811UNIV PK N;7U
50/50
1.9251.925
941551AE2-152 C
Adder
9.8717647058823528.391
274676JOLIET 29;8U
Adder
62.29647058823529452.952
958481AF2-142 C
Adder
10.2776470588235318.736
957332AF2-027 E
Adder
3.1823529411764712.705
274891CAYUG;2U E
Adder
11.4552941176470599.737
926822AC1-168 E
Adder
6.4588235294117655.49
274814UNIV PK N;0U
50/50
1.9011.901
274807UNIV PK N;3U
50/50
1.9251.925
274816UNIV PK N;YU
50/50
1.9251.925
958011AF2-095 C
Adder
9.6458823529411778.199
933411AC2-154 C
Adder
2.1211764705882351.803
274687WILL CNTY;4U
Adder
56.08235294117647447.67
966091AG1-478 C
Adder
1.76941176470588251.504
966441AG1-513 C
Adder
0.434117647058823550.369
959081AF2-199 C
Adder
6.0258823529411775.122
965791AG1-447 C
50/50
46.89646.896
965682AG1-436 E
50/50
42.63342.633
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
275149KELLYCK ;1E
Adder
15.63058823529411813.286
934722AD1-100 E
Adder
76.7823529411764765.265
960751AF2-366 C
Adder
5.9247058823529415.036
942422AE2-255 E
Adder
7.6658823529411776.516
960582AF2-349 E
Adder
30.726.095
937312AD2-172 E
Adder
2.8647058823529412.435
274859EASYR;U1 E
Adder
10.1270588235294138.608
293519PILOT HIL;1E
Adder
15.63058823529411813.286
939351AE1-166 C
Adder
8.555294117647067.272
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
293061N-015 E
Adder
13.20352941176470711.223
943121AE2-341 C
Adder
10.8588235294117659.23
939321AE1-163 C
Adder
5.3388235294117654.538
295111SUBLETTE E
Adder
2.3082352941176471.962
274860EASYR;U2 E
Adder
10.1270588235294138.608
910542X3-005 E
Adder
0.53764705882352950.457
939352AE1-166 E
Adder
7.897647058823536.713
294392P-010 E
Adder
16.76941176470588214.254
959352AF2-226 E
Adder
3.0411764705882352.585
934101AD2-000 1
Adder
4.91411764705882354.177
958492AF2-143 E
Adder
6.537647058823535.557
942421AE2-255 C
Adder
2.5552941176470592.172
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
957472AF2-041 E
Adder
9.0400000000000017.684
959092AF2-200 E
Adder
8.0352941176470596.83
274815UNIV PK N;XU
50/50
1.9131.913
958012AF2-095 E
Adder
6.4305882352941185.466
934111AD2-000 2
Adder
5.0882352941176484.325
966442AG1-513 E
Adder
0.65058823529411770.553
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
290051GSG-6; E
Adder
8.8682352941176487.538
959082AF2-199 E
Adder
3.01294117647058852.561
958912AF2-182 E
Adder
28.79647058823529424.477
957331AF2-027 C
Adder
2.1211764705882351.803
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
295109WESTBROOK E
Adder
4.7482352941176474.036
939061AE1-134 2
Adder
1.15294117647058810.98
926821AC1-168 C
Adder
0.96235294117647050.818
938862AE1-114 E
Adder
11.315294117647069.618
274808UNIV PK N;4U
50/50
1.9171.917
959351AF2-226 C
Adder
2.0270588235294121.723
958491AF2-143 C
Adder
9.8058823529411778.335
933912AD1-013 E
Adder
2.49411764705882362.12
946152AF1-280 E
Adder
19.1976470588235316.318
293716O-029 E
Adder
4.4917647058823533.818
274805UNIV PK N;1U
50/50
1.9131.913
943592AF1-030 E
Adder
3.5729411764705883.037
943591AF1-030 C
Adder
7.2211764705882366.138
936292AD2-038 E
Adder
13.46705882352941211.447
290021O50 E
Adder
16.3552941176470613.902
937002AD2-134 E
Adder
8.5752941176470587.289
293644O22 E1
Adder
11.6458823529411759.899
960281AF2-319 C
Adder
2.0270588235294121.723
960752AF2-366 E
Adder
3.94941176470588263.357
957471AF2-041 C
Adder
18.07882352941176815.367
294763P-046 E
Adder
7.9611764705882366.767
938861AE1-114 C
Adder
3.3164705882352942.819
960682AF2-359 E
50/50
42.63342.633
274810UNIV PK N;6U
50/50
1.9171.917
274812UNIV PK N;8U
50/50
1.9091.909
941552AE2-152 E
Adder
6.5811764705882365.594
958482AF2-142 E
Adder
6.8517647058823535.824
938852AE1-113 E
Adder
23.91882352941176420.331
274890CAYUG;1U E
Adder
11.4552941176470599.737
962012AG1-044 E
Adder
0.0529411764705882350.045
965681AG1-436 C
50/50
63.94963.949
293645O22 E2
Adder
13.33882352941176411.338
960282AF2-319 E
Adder
3.0411764705882352.585
918052AA1-018 E OP
Adder
14.9023529411764712.667
293715O-029 E
Adder
8.1929411764705896.964
943122AE2-341 E
Adder
5.3317647058823534.532
939322AE1-163 E
Adder
32.7952941176470627.876
293516O-009 E
Adder
15.8423529411764713.466
293717O-029 E
Adder
4.1282352941176473.509
936372AD2-047 E
Adder
18.53411764705882415.754
276591L-013 2
Adder
3.11882352941176462.651
962781AG1-127 C
Adder
5.94117647058823555.05
933911AD1-013 C
Adder
1.56117647058823541.327
936371AD2-047 C
Adder
3.7964705882352943.227
936461AD2-060 C
Adder
2.2329411764705881.898
933412AC2-154 E
Adder
3.46117647058823552.942
962782AG1-127 E
Adder
3.9541176470588243.361
946671AF1-331 C
Adder
2.0282352941176471.724
276170Z1-108 E
Adder
2.48588235294117642.113
920272AA2-123 E
Adder
2.4364705882352942.071
276675AE2-062 E
Adder
0.135294117647058840.115
276626AG1-044 E
Adder
0.062352941176470590.053
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142
NYPJM->LTFIMP_NY
CLTF
0.9330.933
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.45 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1768.97
MW Contribution:11.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966092AG1-478 E
Adder
0.50588235294117640.43
274682WAUKEGAN ;7U
Adder
42.623529411764736.23
942651AE2-281 C
Adder
0.840.714
942652AE2-281 E
Adder
5.1611764705882354.387
962691AG1-118 C
Adder
22.70941176470588419.303
962692AG1-118 E
Adder
15.1412.869
938851AE1-113 C
Adder
8.3164705882352947.069
272363ESS H440 ; R
Adder
2.69411764705882372.29
959091AF2-200 C
Adder
14.62470588235294112.431
940502AE2-035 E
Adder
3.4682352941176472.948
941551AE2-152 C
Adder
11.78941176470588410.021
958011AF2-095 C
Adder
10.2317647058823528.697
933411AC2-154 C
Adder
2.25058823529411761.913
274687WILL CNTY;4U
50/50
71.93671.936
966091AG1-478 C
Adder
2.00941176470588221.708
966441AG1-513 C
Adder
0.52235294117647060.444
959081AF2-199 C
Adder
7.3129411764705896.216
960591AF2-350 C
Adder
7.1058823529411776.04
293519PILOT HIL;1E
Adder
16.58000000000000214.093
939351AE1-166 C
Adder
10.217647058823538.685
274675JOLIET 29;7U
Adder
76.2117647058823664.78
274674JOLIET 9 ;6U
Adder
35.323529411764730.025
293061N-015 E
Adder
16.04470588235294313.638
943121AE2-341 C
Adder
13.05176470588235211.094
274862TOP CROP ;2U
50/50
0.8420.842
939321AE1-163 C
Adder
5.8811764705882354.999
295111SUBLETTE E
Adder
2.78941176470588252.371
274860EASYR;U2 E
Adder
12.26705882352941210.427
274754CRETE EC ;4U
50/50
6.1116.111
958012AF2-095 E
Adder
6.8211764705882355.798
934111AD2-000 2
Adder
6.3129411764705885.366
966442AG1-513 E
Adder
0.78235294117647070.665
274683WAUKEGAN ;8U
Adder
45.9439.049
290051GSG-6; E
Adder
10.715294117647069.108
959082AF2-199 E
Adder
3.65647058823529443.108
958912AF2-182 E
Adder
34.8823529411764729.65
274676JOLIET 29;8U
50/50
76.25576.255
274704KENDALL ;1C
50/50
4.144.14
274706KENDALL ;2C
50/50
4.144.14
274705KENDALL ;1S
50/50
2.7692.769
958481AF2-142 C
Adder
10.8694117647058849.239
957332AF2-027 E
Adder
3.86117647058823543.282
274891CAYUG;2U E
Adder
13.66000000000000211.611
926822AC1-168 E
Adder
7.797647058823536.628
939352AE1-166 E
Adder
9.4317647058823538.017
294392P-010 E
Adder
20.3776470588235317.321
959352AF2-226 E
50/50
4.424.42
934101AD2-000 1
Adder
5.8964705882352945.012
958492AF2-143 E
Adder
7.2011764705882366.121
942421AE2-255 C
Adder
3.15058823529411752.678
290108LEEDK;1U E
Adder
24.58352941176470820.896
916221Z1-073 E
Adder
7.5505882352941186.418
957472AF2-041 E
Adder
10.9682352941176489.323
959092AF2-200 E
Adder
9.7494117647058838.287
926821AC1-168 C
Adder
1.16235294117647060.988
938862AE1-114 E
Adder
13.70117647058823711.646
274655BRAIDWOOD;2U
50/50
26.87526.875
959351AF2-226 C
50/50
2.9472.947
958491AF2-143 C
Adder
10.8023529411764719.182
933912AD1-013 E
Adder
3.01294117647058852.561
946152AF1-280 E
Adder
23.25529411764705819.767
960592AF2-350 E
Adder
4.737647058823534.027
275149KELLYCK ;1E
Adder
16.58000000000000214.093
934722AD1-100 E
Adder
91.6917647058823677.938
960751AF2-366 C
Adder
7.1517647058823536.079
942422AE2-255 E
Adder
9.4505882352941168.033
960582AF2-349 E
Adder
37.19058823529411531.612
937312AD2-172 E
Adder
3.4682352941176472.948
274859EASYR;U1 E
Adder
12.26705882352941210.427
943592AF1-030 E
Adder
4.2941176470588233.65
943591AF1-030 C
Adder
8.687.378
936292AD2-038 E
Adder
14.8352941176470612.61
290021O50 E
Adder
20.16117647058823817.137
937002AD2-134 E
Adder
10.368.806
274751CRETE EC ;1U
50/50
6.1116.111
293644O22 E1
50/50
16.92816.928
960281AF2-319 C
50/50
2.9472.947
960752AF2-366 E
Adder
4.7682352941176474.053
957471AF2-041 C
Adder
21.9376470588235318.647
294763P-046 E
Adder
9.6411764705882378.195
938861AE1-114 C
Adder
4.0152941176470593.413
274707KENDALL ;2S
50/50
2.7692.769
957331AF2-027 C
Adder
2.57411764705882362.188
936511AD2-066 C
Adder
8.5164705882352937.239
936512AD2-066 E
Adder
5.67764705882352954.826
295109WESTBROOK E
Adder
5.7364705882352954.876
939061AE1-134 2
Adder
1.39764705882352951.188
941552AE2-152 E
Adder
7.8588235294117646.68
958482AF2-142 E
Adder
7.2458823529411776.159
938852AE1-113 E
Adder
29.48470588235294425.062
274890CAYUG;1U E
Adder
13.66000000000000211.611
962012AG1-044 E
Adder
0.063529411764705890.054
293645O22 E2
50/50
19.38819.388
960282AF2-319 E
50/50
4.424.42
918052AA1-018 E OP
Adder
15.76000000000000213.396
943122AE2-341 E
Adder
6.4094117647058835.448
939322AE1-163 E
Adder
36.1270588235294130.708
293516O-009 E
Adder
8.2905882352941187.047
274753CRETE EC ;3U
50/50
6.1116.111
936372AD2-047 E
Adder
19.6616.711
274654BRAIDWOOD;1U
50/50
27.62127.621
274861TOP CROP ;1U
50/50
0.4420.442
276591L-013 2
Adder
3.7670588235294123.202
962781AG1-127 C
Adder
7.1717647058823536.096
933911AD1-013 C
Adder
1.88588235294117661.603
274752CRETE EC ;2U
50/50
6.1116.111
936371AD2-047 C
Adder
4.0270588235294123.423
936461AD2-060 C
Adder
2.3682352941176472.013
933412AC2-154 E
Adder
3.6717647058823533.121
962782AG1-127 E
Adder
4.7729411764705894.057
946671AF1-331 C
Adder
2.4494117647058822.082
276626AG1-044 E
Adder
0.075294117647058830.064
276675AE2-062 E
Adder
0.152941176470588250.13
920272AA2-123 E
Adder
2.9517647058823532.509
276170Z1-108 E
Adder
3.01294117647058852.561
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
O66PJM->LTFIMP_O-066
CMTX_NF
13.7513.75
NYPJM->LTFIMP_NY
CLTF
1.1511.151
WECLTFEXP_WEC->PJM
CLTF
4.0154.015
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5770.577
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.30480.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.41313.413
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7060.706
MECLTFEXP_MEC->PJM
CLTF
13.16213.162
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0692.069
LAGNLTFEXP_LAGN->PJM
CLTF
3.2773.277
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1432.143
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.44 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1768.9
MW Contribution:11.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
966092AG1-478 E
Adder
0.50588235294117640.43
274682WAUKEGAN ;7U
Adder
42.6236.227
942651AE2-281 C
Adder
0.840.714
958011AF2-095 C
Adder
10.232941176470598.698
933411AC2-154 C
Adder
2.25058823529411761.913
274687WILL CNTY;4U
50/50
71.93571.935
293519PILOT HIL;1E
Adder
16.58117647058823614.094
939351AE1-166 C
Adder
10.217647058823538.685
274675JOLIET 29;7U
Adder
76.2094117647058964.778
966091AG1-478 C
Adder
2.00941176470588221.708
966441AG1-513 C
Adder
0.52235294117647060.444
959081AF2-199 C
Adder
7.3117647058823536.215
274674JOLIET 9 ;6U
Adder
35.32235294117647630.024
293061N-015 E
Adder
16.04470588235294313.638
943121AE2-341 C
Adder
13.05058823529411811.093
274862TOP CROP ;2U
50/50
0.8420.842
939321AE1-163 C
Adder
5.8811764705882354.999
295111SUBLETTE E
Adder
2.78823529411764742.37
274860EASYR;U2 E
Adder
12.26588235294117610.426
274754CRETE EC ;4U
50/50
6.1116.111
958012AF2-095 E
Adder
6.8211764705882355.798
934111AD2-000 2
Adder
6.3117647058823545.365
966442AG1-513 E
Adder
0.78235294117647070.665
274683WAUKEGAN ;8U
Adder
45.93647058823529539.046
290051GSG-6; E
Adder
10.7141176470588229.107
959082AF2-199 E
Adder
3.65529411764705923.107
941551AE2-152 C
Adder
11.78941176470588410.021
274676JOLIET 29;8U
50/50
76.25276.252
274704KENDALL ;1C
50/50
4.144.14
274706KENDALL ;2C
50/50
4.144.14
274705KENDALL ;1S
50/50
2.7692.769
958481AF2-142 C
Adder
10.8694117647058849.239
957332AF2-027 E
Adder
3.86117647058823543.282
274891CAYUG;2U E
Adder
13.66000000000000211.611
926822AC1-168 E
Adder
7.79647058823529456.627
942652AE2-281 E
Adder
5.1611764705882354.387
962691AG1-118 C
Adder
22.7070588235294119.301
962692AG1-118 E
Adder
15.13882352941176612.868
938851AE1-113 C
Adder
8.3164705882352947.069
272363ESS H440 ; R
Adder
2.69411764705882372.29
959091AF2-200 C
Adder
14.62352941176470512.43
940502AE2-035 E
Adder
3.4682352941176472.948
958912AF2-182 E
Adder
34.8788235294117629.647
939352AE1-166 E
Adder
9.4317647058823538.017
294392P-010 E
Adder
20.37647058823529617.32
959352AF2-226 E
50/50
4.424.42
934101AD2-000 1
Adder
5.8952941176470595.011
958492AF2-143 E
Adder
7.2011764705882366.121
942421AE2-255 C
Adder
3.14941176470588242.677
290108LEEDK;1U E
Adder
24.58117647058823320.894
916221Z1-073 E
Adder
7.5494117647058836.417
957472AF2-041 E
Adder
10.9670588235294129.322
959092AF2-200 E
Adder
9.7494117647058838.287
926821AC1-168 C
Adder
1.16235294117647060.988
938862AE1-114 E
Adder
13.711.645
274655BRAIDWOOD;2U
50/50
26.87526.875
959351AF2-226 C
50/50
2.9462.946
958491AF2-143 C
Adder
10.8023529411764719.182
933912AD1-013 E
Adder
3.01294117647058852.561
946152AF1-280 E
Adder
23.2529411764705919.765
960591AF2-350 C
Adder
7.1058823529411776.04
960592AF2-350 E
Adder
4.737647058823534.027
275149KELLYCK ;1E
Adder
16.58117647058823614.094
934722AD1-100 E
Adder
91.6988235294117777.944
960751AF2-366 C
Adder
7.1517647058823536.079
942422AE2-255 E
Adder
9.4494117647058828.032
960582AF2-349 E
Adder
37.1870588235294131.609
937312AD2-172 E
Adder
3.4682352941176472.948
274859EASYR;U1 E
Adder
12.26588235294117610.426
943592AF1-030 E
Adder
4.2941176470588233.65
943591AF1-030 C
Adder
8.6788235294117657.377
936292AD2-038 E
Adder
14.83411764705882312.609
290021O50 E
Adder
20.1617.136
937002AD2-134 E
Adder
10.3588235294117658.805
274751CRETE EC ;1U
50/50
6.1116.111
293644O22 E1
50/50
16.92816.928
960281AF2-319 C
50/50
2.9462.946
274707KENDALL ;2S
50/50
2.7692.769
957331AF2-027 C
Adder
2.57411764705882362.188
936511AD2-066 C
Adder
8.5164705882352937.239
936512AD2-066 E
Adder
5.67764705882352954.826
295109WESTBROOK E
Adder
5.7364705882352954.876
939061AE1-134 2
Adder
1.39764705882352951.188
941552AE2-152 E
Adder
7.866.681
958482AF2-142 E
Adder
7.2458823529411776.159
938852AE1-113 E
Adder
29.48352941176470725.061
274890CAYUG;1U E
Adder
13.66000000000000211.611
962012AG1-044 E
Adder
0.063529411764705890.054
960752AF2-366 E
Adder
4.7670588235294114.052
957471AF2-041 C
Adder
21.93529411764705718.645
294763P-046 E
Adder
9.648.194
938861AE1-114 C
Adder
4.0152941176470593.413
293645O22 E2
50/50
19.38819.388
960282AF2-319 E
50/50
4.424.42
918052AA1-018 E OP
Adder
15.76000000000000213.396
943122AE2-341 E
Adder
6.4082352941176475.447
939322AE1-163 E
Adder
36.12588235294117630.707
293516O-009 E
Adder
8.2905882352941187.047
274753CRETE EC ;3U
50/50
6.1116.111
936372AD2-047 E
Adder
19.66117647058823416.712
274654BRAIDWOOD;1U
50/50
27.62127.621
274861TOP CROP ;1U
50/50
0.4420.442
276591L-013 2
Adder
3.7670588235294123.202
962781AG1-127 C
Adder
7.1717647058823536.096
933911AD1-013 C
Adder
1.88588235294117661.603
274752CRETE EC ;2U
50/50
6.1116.111
936371AD2-047 C
Adder
4.0270588235294123.423
936461AD2-060 C
Adder
2.3682352941176472.013
933412AC2-154 E
Adder
3.6717647058823533.121
962782AG1-127 E
Adder
4.7729411764705894.057
946671AF1-331 C
Adder
2.4494117647058822.082
276626AG1-044 E
Adder
0.075294117647058830.064
276675AE2-062 E
Adder
0.152941176470588250.13
920272AA2-123 E
Adder
2.9517647058823532.509
276170Z1-108 E
Adder
3.0117647058823532.56
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
O66PJM->LTFIMP_O-066
CMTX_NF
13.7513.75
NYPJM->LTFIMP_NY
CLTF
1.1511.151
WECLTFEXP_WEC->PJM
CLTF
4.0154.015
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5760.576
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.29780.297
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.41213.412
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7060.706
MECLTFEXP_MEC->PJM
CLTF
13.16113.161
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0692.069
LAGNLTFEXP_LAGN->PJM
CLTF
3.2773.277
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1432.143
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.42 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1768.67
MW Contribution:11.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
958011AF2-095 C
Adder
10.1811764705882368.654
933411AC2-154 C
Adder
2.23882352941176471.903
274687WILL CNTY;4U
50/50
71.61971.619
966091AG1-478 C
Adder
2.01.7
966441AG1-513 C
Adder
0.520.442
959081AF2-199 C
Adder
7.2835294117647066.191
293519PILOT HIL;1E
Adder
16.49764705882352814.023
939351AE1-166 C
Adder
10.1800000000000018.653
274675JOLIET 29;7U
Adder
75.8694117647058964.489
274674JOLIET 9 ;6U
Adder
35.15058823529411629.878
293061N-015 E
Adder
15.9752941176470613.579
943121AE2-341 C
Adder
12.98823529411764711.04
274862TOP CROP ;2U
50/50
0.8390.839
939321AE1-163 C
Adder
5.8588235294117654.98
295111SUBLETTE E
Adder
2.77764705882352962.361
274860EASYR;U2 E
Adder
12.2223529411764710.389
941551AE2-152 C
Adder
11.7458823529411779.984
274676JOLIET 29;8U
50/50
75.91275.912
274704KENDALL ;1C
50/50
4.1234.123
274706KENDALL ;2C
50/50
4.1234.123
274705KENDALL ;1S
50/50
2.7572.757
958481AF2-142 C
Adder
10.8235294117647059.2
957332AF2-027 E
Adder
3.8447058823529413.268
274891CAYUG;2U E
Adder
13.62588235294117711.582
926822AC1-168 E
Adder
7.7741176470588236.608
966092AG1-478 E
Adder
0.50352941176470590.428
274682WAUKEGAN ;7U
Adder
42.43647058823529536.071
942651AE2-281 C
Adder
0.83647058823529410.711
942652AE2-281 E
Adder
5.1411764705882364.37
962691AG1-118 C
Adder
22.60941176470588219.218
962692AG1-118 E
Adder
15.07294117647058812.812
938851AE1-113 C
Adder
8.2858823529411787.043
272363ESS H440 ; R
Adder
2.68235294117647042.28
959091AF2-200 C
Adder
14.56588235294117712.381
940502AE2-035 E
Adder
3.45529411764705862.937
274754CRETE EC ;4U
50/50
6.1016.101
958012AF2-095 E
Adder
6.7870588235294125.769
934111AD2-000 2
Adder
6.2858823529411775.343
966442AG1-513 E
Adder
0.77882352941176480.662
274683WAUKEGAN ;8U
Adder
45.7388235294117738.878
290051GSG-6; E
Adder
10.6705882352941199.07
959082AF2-199 E
Adder
3.64117647058823573.095
958912AF2-182 E
Adder
34.7576470588235329.544
939352AE1-166 E
Adder
9.397647058823537.988
294392P-010 E
Adder
20.28941176470588217.246
959352AF2-226 E
50/50
4.4044.404
934101AD2-000 1
Adder
5.8705882352941184.99
958492AF2-143 E
Adder
7.1729411764705896.097
942421AE2-255 C
Adder
3.1388235294117652.668
290108LEEDK;1U E
Adder
24.47764705882353220.806
916221Z1-073 E
Adder
7.52000000000000056.392
957472AF2-041 E
Adder
10.924705882352949.286
959092AF2-200 E
Adder
9.7105882352941188.254
926821AC1-168 C
Adder
1.15882352941176480.985
938862AE1-114 E
Adder
13.65058823529411711.603
274655BRAIDWOOD;2U
50/50
26.76926.769
959351AF2-226 C
50/50
2.9362.936
958491AF2-143 C
Adder
10.7600000000000029.146
933912AD1-013 E
Adder
3.00117647058823562.551
946152AF1-280 E
Adder
23.17176470588235719.696
960591AF2-350 C
Adder
7.0705882352941176.01
960592AF2-350 E
Adder
4.7141176470588234.007
275149KELLYCK ;1E
Adder
16.49764705882352814.023
934722AD1-100 E
Adder
91.3611764705882377.657
960751AF2-366 C
Adder
7.1211764705882356.053
942422AE2-255 E
Adder
9.415294117647068.003
960582AF2-349 E
Adder
37.0376470588235331.482
937312AD2-172 E
Adder
3.45529411764705862.937
274859EASYR;U1 E
Adder
12.2223529411764710.389
943592AF1-030 E
Adder
4.2741176470588243.633
943591AF1-030 C
Adder
8.6376470588235297.342
936292AD2-038 E
Adder
14.7776470588235312.561
290021O50 E
Adder
20.08705882352941417.074
937002AD2-134 E
Adder
10.317647058823538.77
274707KENDALL ;2S
50/50
2.7572.757
957331AF2-027 C
Adder
2.5635294117647062.179
936511AD2-066 C
Adder
8.484705882352947.212
936512AD2-066 E
Adder
5.6564705882352944.808
295109WESTBROOK E
Adder
5.7129411764705884.856
939061AE1-134 2
Adder
1.39294117647058811.184
941552AE2-152 E
Adder
7.8305882352941176.656
958482AF2-142 E
Adder
7.2152941176470596.133
938852AE1-113 E
Adder
29.3776470588235324.971
274890CAYUG;1U E
Adder
13.62588235294117711.582
962012AG1-044 E
Adder
0.063529411764705890.054
274751CRETE EC ;1U
50/50
6.1016.101
293644O22 E1
50/50
16.86916.869
960281AF2-319 C
50/50
2.9362.936
960752AF2-366 E
Adder
4.7470588235294124.035
957471AF2-041 C
Adder
21.8494117647058818.572
294763P-046 E
Adder
9.6035294117647068.163
938861AE1-114 C
Adder
4.0011764705882353.401
293645O22 E2
50/50
19.32119.321
960282AF2-319 E
50/50
4.4044.404
918052AA1-018 E OP
Adder
15.69411764705882513.34
943122AE2-341 E
Adder
6.377647058823535.421
939322AE1-163 E
Adder
35.98588235294117530.588
293516O-009 E
Adder
8.2647058823529427.025
274753CRETE EC ;3U
50/50
6.1016.101
936372AD2-047 E
Adder
19.5623529411764716.628
274654BRAIDWOOD;1U
50/50
27.51327.513
274861TOP CROP ;1U
50/50
0.440.44
276591L-013 2
Adder
3.7505882352941183.188
962781AG1-127 C
Adder
7.1411764705882366.07
933911AD1-013 C
Adder
1.87882352941176481.597
274752CRETE EC ;2U
50/50
6.1016.101
936371AD2-047 C
Adder
4.00705882352941253.406
936461AD2-060 C
Adder
2.3564705882352942.003
933412AC2-154 E
Adder
3.6529411764705883.105
962782AG1-127 E
Adder
4.7517647058823534.039
946671AF1-331 C
Adder
2.442.074
276626AG1-044 E
Adder
0.075294117647058830.064
276675AE2-062 E
Adder
0.152941176470588250.13
920272AA2-123 E
Adder
2.9388235294117652.498
276170Z1-108 E
Adder
2.9988235294117652.549
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8080.808
TVALTFEXP_TVA->PJM
CLTF
1.191.19
O66PJM->LTFIMP_O-066
CMTX_NF
13.71713.717
NYPJM->LTFIMP_NY
CLTF
1.151.15
WECLTFEXP_WEC->PJM
CLTF
3.9993.999
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5540.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.46579.465
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.83113.831
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6340.634
MECLTFEXP_MEC->PJM
CLTF
13.15813.158
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.8531.853
LAGNLTFEXP_LAGN->PJM
CLTF
3.3653.365
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1382.138
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2920.292

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.5 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1405.95
MW Contribution:7.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274708KENDALL ;3C
80/20
3.9223.922
274734ELWOOD EC;8P
80/20
3.3643.364
274736ELWOOD EC;9P
80/20
3.3643.364
274735ELWOOD EC;4P
80/20
3.3583.358
274682WAUKEGAN ;7U
Adder
42.636.21
942651AE2-281 C
Adder
0.840.714
962691AG1-118 C
Adder
22.6929411764705919.289
938851AE1-113 C
Adder
8.3141176470588247.067
959091AF2-200 C
Adder
14.61529411764705912.423
959341AF2-225 C
Adder
6.0400000000000015.134
965091AG1-374 C
Adder
16.39058823529411813.932
941551AE2-152 C
80/20
11.79611.796
274676JOLIET 29;8U
80/20
76.23476.234
937401AD2-194 1
80/20
1.3081.308
274704KENDALL ;1C
80/20
4.1394.139
274706KENDALL ;2C
80/20
4.1394.139
274705KENDALL ;1S
80/20
2.7682.768
274847GR RIDGE ;BU
80/20
0.5960.596
958481AF2-142 C
Adder
10.8682352941176469.238
958011AF2-095 C
Adder
10.2352941176470588.7
933411AC2-154 C
Adder
2.25058823529411761.913
274687WILL CNTY;4U
80/20
71.92771.927
966091AG1-478 C
Adder
2.00941176470588221.708
274733ELWOOD EC;3P
80/20
3.3583.358
966441AG1-513 C
Adder
0.52117647058823540.443
959081AF2-199 C
Adder
7.3070588235294126.211
942111AE2-223 C
Adder
1.86941176470588231.589
939741AE1-205 C
Adder
8.0529411764705886.845
960591AF2-350 C
Adder
7.1082352941176476.042
934721AD1-100 C
80/20
3.0093.009
274728ELWOOD EC;5P
80/20
3.3643.364
274745AURORA EC;9P
80/20
1.0831.083
960751AF2-366 C
Adder
7.1470588235294126.075
961501AF2-441 C
Adder
6.6670588235294125.667
939351AE1-166 C
80/20
10.22310.223
274675JOLIET 29;7U
80/20
76.19176.191
274674JOLIET 9 ;6U
Adder
35.31176470588235430.015
943121AE2-341 C
Adder
13.0411.084
274862TOP CROP ;2U
80/20
0.8420.842
939321AE1-163 C
Adder
5.8800000000000014.998
274711KENDALL ;4S
80/20
2.5942.594
934101AD2-000 1
80/20
5.8925.892
942421AE2-255 C
Adder
3.14941176470588242.677
926821AC1-168 C
Adder
1.16117647058823530.987
959611AF2-252 C
Adder
1.82117647058823541.548
274754CRETE EC ;4U
80/20
6.1116.111
934111AD2-000 2
80/20
6.316.31
274683WAUKEGAN ;8U
Adder
45.9152941176470639.028
274710KENDALL ;4C
80/20
3.8793.879
274709KENDALL ;3S
80/20
2.5942.594
276642AC1-204 GEN2
80/20
12.51212.512
274707KENDALL ;2S
80/20
2.7682.768
274871GR RIDGE ;2U
80/20
0.2220.222
957331AF2-027 C
Adder
2.5729411764705882.187
936511AD2-066 C
Adder
8.5141176470588237.237
939061AE1-134 2
Adder
1.39647058823529411.187
274655BRAIDWOOD;2U
80/20
26.8826.88
276640AC1-204 GEN1
80/20
12.4912.49
959351AF2-226 C
80/20
2.9462.946
958491AF2-143 C
Adder
10.89.18
965931AG1-462 C
Adder
16.29411764705882213.85
274660LASCO STA;1U
80/20
25.49425.494
943591AF1-030 C
Adder
8.6717647058823537.371
274751CRETE EC ;1U
80/20
6.1116.111
274729ELWOOD EC;1P
80/20
3.3583.358
960281AF2-319 C
80/20
2.9462.946
957471AF2-041 C
Adder
21.9223529411764718.634
938861AE1-114 C
Adder
4.0129411764705883.411
937411AD2-194 2
80/20
1.3111.311
274737AURORA EC;1P
80/20
3.5563.556
274658DRESDEN ;2U
80/20
19.99619.996
274661LASCO STA;2U
80/20
25.57725.577
276658AB1-122 CT1
80/20
11.86311.863
946321AF1-296 C
Adder
3.6188235294117653.076
274753CRETE EC ;3U
80/20
6.1116.111
274654BRAIDWOOD;1U
80/20
27.62627.626
274731ELWOOD EC;2P
80/20
3.3583.358
274861TOP CROP ;1U
80/20
0.4420.442
962781AG1-127 C
Adder
7.1670588235294126.092
933911AD1-013 C
Adder
1.88470588235294121.602
274752CRETE EC ;2U
80/20
6.1116.111
936371AD2-047 C
Adder
4.0282352941176473.424
936461AD2-060 C
Adder
2.3694117647058822.014
274732ELWOOD EC;7P
80/20
3.3643.364
274730ELWOOD EC;6P
80/20
3.3643.364
276660AB1-122 CT2
80/20
12.70612.706
274739AURORA EC;2P
80/20
3.5563.556
946671AF1-331 C
Adder
2.4482352941176472.081
960611AF2-352 C
Adder
1.82117647058823541.548
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
NYPJM->LTFIMP_NY
CLTF
1.1511.151
WECLTFEXP_WEC->PJM
CLTF
4.0134.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5760.576
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.25680.256
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.40713.407
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7050.705
MECLTFEXP_MEC->PJM
CLTF
13.15513.155
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0682.068
LAGNLTFEXP_LAGN->PJM
CLTF
3.2763.276
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.5 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1405.93
MW Contribution:7.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274708KENDALL ;3C
80/20
3.9223.922
274734ELWOOD EC;8P
80/20
3.3643.364
274736ELWOOD EC;9P
80/20
3.3643.364
274735ELWOOD EC;4P
80/20
3.3583.358
274682WAUKEGAN ;7U
Adder
42.636.21
942651AE2-281 C
Adder
0.840.714
962691AG1-118 C
Adder
22.6929411764705919.289
938851AE1-113 C
Adder
8.3141176470588247.067
959091AF2-200 C
Adder
14.61529411764705912.423
959341AF2-225 C
Adder
6.0400000000000015.134
965091AG1-374 C
Adder
16.39058823529411813.932
941551AE2-152 C
80/20
11.79611.796
274676JOLIET 29;8U
80/20
76.23476.234
937401AD2-194 1
80/20
1.3081.308
274704KENDALL ;1C
80/20
4.1394.139
274706KENDALL ;2C
80/20
4.1394.139
274705KENDALL ;1S
80/20
2.7682.768
274847GR RIDGE ;BU
80/20
0.5960.596
958481AF2-142 C
Adder
10.8682352941176469.238
958011AF2-095 C
Adder
10.2352941176470588.7
933411AC2-154 C
Adder
2.25058823529411761.913
274687WILL CNTY;4U
80/20
71.92771.927
966091AG1-478 C
Adder
2.00941176470588221.708
274733ELWOOD EC;3P
80/20
3.3583.358
966441AG1-513 C
Adder
0.52117647058823540.443
959081AF2-199 C
Adder
7.3070588235294126.211
942111AE2-223 C
Adder
1.86941176470588231.589
939741AE1-205 C
Adder
8.0529411764705886.845
960591AF2-350 C
Adder
7.1082352941176476.042
934721AD1-100 C
80/20
3.0093.009
274728ELWOOD EC;5P
80/20
3.3643.364
274745AURORA EC;9P
80/20
1.0831.083
960751AF2-366 C
Adder
7.1470588235294126.075
961501AF2-441 C
Adder
6.6670588235294125.667
939351AE1-166 C
80/20
10.22310.223
274675JOLIET 29;7U
80/20
76.19176.191
274674JOLIET 9 ;6U
Adder
35.31176470588235430.015
943121AE2-341 C
Adder
13.0411.084
274862TOP CROP ;2U
80/20
0.8420.842
939321AE1-163 C
Adder
5.8800000000000014.998
274711KENDALL ;4S
80/20
2.5942.594
934101AD2-000 1
80/20
5.8925.892
942421AE2-255 C
Adder
3.14941176470588242.677
926821AC1-168 C
Adder
1.16117647058823530.987
959611AF2-252 C
Adder
1.82117647058823541.548
274754CRETE EC ;4U
80/20
6.1116.111
934111AD2-000 2
80/20
6.316.31
274683WAUKEGAN ;8U
Adder
45.9152941176470639.028
274710KENDALL ;4C
80/20
3.8793.879
274709KENDALL ;3S
80/20
2.5942.594
276642AC1-204 GEN2
80/20
12.51212.512
274707KENDALL ;2S
80/20
2.7682.768
274871GR RIDGE ;2U
80/20
0.2220.222
957331AF2-027 C
Adder
2.5729411764705882.187
936511AD2-066 C
Adder
8.5141176470588237.237
939061AE1-134 2
Adder
1.39647058823529411.187
274655BRAIDWOOD;2U
80/20
26.8826.88
276640AC1-204 GEN1
80/20
12.4912.49
959351AF2-226 C
80/20
2.9462.946
958491AF2-143 C
Adder
10.89.18
965931AG1-462 C
Adder
16.29411764705882213.85
274660LASCO STA;1U
80/20
25.49425.494
943591AF1-030 C
Adder
8.6717647058823537.371
274751CRETE EC ;1U
80/20
6.1116.111
274729ELWOOD EC;1P
80/20
3.3583.358
960281AF2-319 C
80/20
2.9462.946
957471AF2-041 C
Adder
21.9223529411764718.634
938861AE1-114 C
Adder
4.0129411764705883.411
937411AD2-194 2
80/20
1.3111.311
274737AURORA EC;1P
80/20
3.5563.556
274658DRESDEN ;2U
80/20
19.99619.996
274661LASCO STA;2U
80/20
25.57725.577
276658AB1-122 CT1
80/20
11.86311.863
946321AF1-296 C
Adder
3.6188235294117653.076
274753CRETE EC ;3U
80/20
6.1116.111
274654BRAIDWOOD;1U
80/20
27.62627.626
274731ELWOOD EC;2P
80/20
3.3583.358
274861TOP CROP ;1U
80/20
0.4420.442
962781AG1-127 C
Adder
7.1670588235294126.092
933911AD1-013 C
Adder
1.88470588235294121.602
274752CRETE EC ;2U
80/20
6.1116.111
936371AD2-047 C
Adder
4.0282352941176473.424
936461AD2-060 C
Adder
2.3694117647058822.014
274732ELWOOD EC;7P
80/20
3.3643.364
274730ELWOOD EC;6P
80/20
3.3643.364
276660AB1-122 CT2
80/20
12.70612.706
274739AURORA EC;2P
80/20
3.5563.556
946671AF1-331 C
Adder
2.4482352941176472.081
960611AF2-352 C
Adder
1.82117647058823541.548
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8350.835
TVALTFEXP_TVA->PJM
CLTF
1.1071.107
NYPJM->LTFIMP_NY
CLTF
1.1511.151
WECLTFEXP_WEC->PJM
CLTF
4.0134.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5760.576
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.25680.256
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.40713.407
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.7050.705
MECLTFEXP_MEC->PJM
CLTF
13.15513.155
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0682.068
LAGNLTFEXP_LAGN->PJM
CLTF
3.2763.276
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3070.307

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.61 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1547.41
MW Contribution:11.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
941551AE2-152 C
Adder
11.88823529411764710.105
274676JOLIET 29;8U
50/50
76.77576.775
958012AF2-095 E
Adder
6.877647058823535.846
934111AD2-000 2
Adder
6.3588235294117655.405
966442AG1-513 E
Adder
0.78823529411764710.67
274683WAUKEGAN ;8U
Adder
46.2952941176470639.351
290051GSG-6; E
Adder
10.8082352941176479.187
959082AF2-199 E
Adder
3.6882352941176473.135
293519PILOT HIL;1E
Adder
16.7176470588235314.21
939351AE1-166 C
Adder
10.3023529411764718.757
274675JOLIET 29;7U
50/50
76.73276.732
274674JOLIET 9 ;6U
Adder
35.59176470588235530.253
293061N-015 E
Adder
16.1647058823529413.74
943121AE2-341 C
Adder
13.14705882352941311.175
274862TOP CROP ;2U
50/50
0.8480.848
966092AG1-478 E
Adder
0.50941176470588230.433
274734ELWOOD EC;8P
50/50
3.3883.388
274682WAUKEGAN ;7U
Adder
42.9505882352941236.508
942651AE2-281 C
Adder
0.84823529411764710.721
942652AE2-281 E
Adder
5.2082352941176474.427
962691AG1-118 C
Adder
22.89176470588235219.458
962692AG1-118 E
Adder
15.26117647058823612.972
938851AE1-113 C
Adder
8.3894117647058837.131
272363ESS H440 ; R
Adder
2.71764705882352952.31
959091AF2-200 C
Adder
14.75411764705882512.541
940502AE2-035 E
Adder
3.50117647058823562.976
958011AF2-095 C
Adder
10.3164705882352948.769
933411AC2-154 C
Adder
2.26941176470588251.929
274687WILL CNTY;4U
50/50
72.4272.42
966091AG1-478 C
Adder
2.02470588235294141.721
966441AG1-513 C
Adder
0.52588235294117650.447
959081AF2-199 C
Adder
7.377647058823536.271
939321AE1-163 C
Adder
5.9352941176470595.045
295111SUBLETTE E
Adder
2.81294117647058832.391
274860EASYR;U2 E
Adder
2.5435294117647062.162
274660LASCO STA;1U
50/50
25.67925.679
943592AF1-030 E
Adder
4.3258823529411773.677
943591AF1-030 C
Adder
8.742352941176477.431
936292AD2-038 E
Adder
14.97058823529411812.725
290021O50 E
Adder
20.33764705882352817.287
937002AD2-134 E
Adder
10.4505882352941168.883
960591AF2-350 C
Adder
7.16470588235294156.09
960592AF2-350 E
Adder
4.7764705882352944.06
275149KELLYCK ;1E
Adder
16.7176470588235314.21
934722AD1-100 E
Adder
92.4678.591
960751AF2-366 C
Adder
7.2105882352941176.129
942422AE2-255 E
Adder
9.5329411764705888.103
960582AF2-349 E
Adder
37.5082352941176531.882
937312AD2-172 E
Adder
3.50117647058823562.976
274859EASYR;U1 E
Adder
12.38705882352941110.529
276642AC1-204 GEN2
50/50
12.60312.603
274707KENDALL ;2S
50/50
2.7882.788
957331AF2-027 C
Adder
2.59529411764705882.206
936511AD2-066 C
Adder
8.5941176470588237.305
936512AD2-066 E
Adder
5.7294117647058824.87
295109WESTBROOK E
Adder
5.7870588235294124.919
274704KENDALL ;1C
50/50
4.1694.169
274706KENDALL ;2C
50/50
4.1694.169
274705KENDALL ;1S
50/50
2.7882.788
958481AF2-142 C
Adder
10.9647058823529419.32
957332AF2-027 E
Adder
3.8917647058823533.308
941552AE2-152 E
Adder
7.9247058823529416.736
958482AF2-142 E
Adder
7.30941176470588256.213
938852AE1-113 E
Adder
29.74470588235294225.283
293644O22 E1
50/50
17.04917.049
960281AF2-319 C
50/50
2.9682.968
960752AF2-366 E
Adder
4.8070588235294124.086
957471AF2-041 C
Adder
22.13176470588235418.812
294763P-046 E
Adder
9.730588235294128.271
938861AE1-114 C
Adder
4.0541176470588243.446
293645O22 E2
50/50
19.52719.527
960282AF2-319 E
50/50
4.4524.452
918052AA1-018 E OP
Adder
15.89882352941176413.514
274661LASCO STA;2U
50/50
25.76325.763
943122AE2-341 E
Adder
6.45529411764705955.487
939322AE1-163 E
Adder
36.4588235294117730.99
936372AD2-047 E
Adder
19.82352941176470716.85
274654BRAIDWOOD;1U
50/50
27.81527.815
274861TOP CROP ;1U
50/50
0.4450.445
276591L-013 2
Adder
3.7952941176470593.226
962781AG1-127 C
Adder
7.23058823529411756.146
933911AD1-013 C
Adder
1.90235294117647061.617
939352AE1-166 E
Adder
9.5105882352941178.084
294392P-010 E
Adder
20.5282352941176517.449
959352AF2-226 E
50/50
4.4524.452
934101AD2-000 1
Adder
5.9435294117647065.052
958492AF2-143 E
Adder
7.2670588235294116.177
942421AE2-255 C
Adder
3.17764705882352952.701
290108LEEDK;1U E
Adder
24.78823529411764821.07
916221Z1-073 E
Adder
7.6164705882352956.474
957472AF2-041 E
Adder
11.0658823529411779.406
959092AF2-200 E
Adder
9.8364705882352958.361
938862AE1-114 E
Adder
13.83176470588235311.757
274655BRAIDWOOD;2U
50/50
27.06427.064
276640AC1-204 GEN1
50/50
12.58212.582
959351AF2-226 C
50/50
2.9682.968
958491AF2-143 C
Adder
10.9011764705882369.266
933912AD1-013 E
Adder
3.042.584
936371AD2-047 C
Adder
4.06000000000000053.451
936461AD2-060 C
Adder
2.3882352941176472.03
933412AC2-154 E
Adder
3.70235294117647043.147
274732ELWOOD EC;7P
50/50
3.3883.388
274730ELWOOD EC;6P
50/50
3.3883.388
962782AG1-127 E
Adder
4.8117647058823534.09
946671AF1-331 C
Adder
2.47058823529411782.1
276170Z1-108 E
Adder
3.03647058823529432.581
920272AA2-123 E
Adder
2.97647058823529382.53
276675AE2-062 E
Adder
0.154117647058823530.131
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.690.69
TVALTFEXP_TVA->PJM
CLTF
1.4091.409
O66PJM->LTFIMP_O-066
CMTX_NF
12.66112.661
NYPJM->LTFIMP_NY
CLTF
1.0631.063
WECLTFEXP_WEC->PJM
CLTF
4.0514.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4630.463
CBM West 1LTFEXP_CBM-W1->PJM
CBM
82.12382.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.85714.857
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5470.547
MECLTFEXP_MEC->PJM
CLTF
13.40713.407
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5811.581
LAGNLTFEXP_LAGN->PJM
CLTF
3.643.64
G-007PJM->LTFIMP_G-007
CMTX_NF
1.9731.973
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2370.237
SIGELTFEXP_SIGE->PJM
CLTF
0.0050.005

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.58 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1546.98
MW Contribution:12.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
958012AF2-095 E
Adder
6.9117647058823535.875
934111AD2-000 2
Adder
6.3858823529411765.428
966442AG1-513 E
Adder
0.7917647058823530.673
274683WAUKEGAN ;8U
Adder
46.4964705882352939.522
290051GSG-6; E
Adder
10.8529411764705899.225
959082AF2-199 E
Adder
3.7035294117647063.148
966092AG1-478 E
Adder
0.51176470588235290.435
274734ELWOOD EC;8P
50/50
3.4033.403
274736ELWOOD EC;9P
50/50
3.4033.403
274682WAUKEGAN ;7U
Adder
43.13882352941176636.668
942651AE2-281 C
Adder
0.85058823529411760.723
942652AE2-281 E
Adder
5.2282352941176474.444
962691AG1-118 C
Adder
22.9929411764705919.544
962692AG1-118 E
Adder
15.32823529411764713.029
938851AE1-113 C
Adder
8.427.157
272363ESS H440 ; R
Adder
2.7282352941176472.319
959091AF2-200 C
Adder
14.81294117647058812.591
940502AE2-035 E
Adder
3.51411764705882362.987
958011AF2-095 C
Adder
10.3682352941176488.813
933411AC2-154 C
Adder
2.281.938
274687WILL CNTY;4U
50/50
72.73772.737
966091AG1-478 C
Adder
2.03411764705882361.729
966441AG1-513 C
Adder
0.52823529411764710.449
959081AF2-199 C
Adder
7.4070588235294126.296
293519PILOT HIL;1E
Adder
16.814.28
939351AE1-166 C
Adder
10.348.789
274675JOLIET 29;7U
50/50
77.07577.075
274674JOLIET 9 ;6U
Adder
35.7647058823529430.4
293061N-015 E
Adder
16.2329411764705913.798
943121AE2-341 C
Adder
13.20941176470588211.228
274862TOP CROP ;2U
50/50
0.8510.851
939321AE1-163 C
Adder
5.957647058823535.064
295111SUBLETTE E
Adder
2.8247058823529412.401
274860EASYR;U2 E
Adder
2.5529411764705882.17
274660LASCO STA;1U
50/50
25.79425.794
943592AF1-030 E
Adder
4.3458823529411763.694
943591AF1-030 C
Adder
8.7847058823529427.467
936292AD2-038 E
Adder
15.02941176470588412.775
290021O50 E
Adder
20.41176470588235517.35
937002AD2-134 E
Adder
10.492941176470598.919
960591AF2-350 C
Adder
7.26.12
960592AF2-350 E
Adder
4.84.08
275149KELLYCK ;1E
Adder
16.814.28
934722AD1-100 E
Adder
92.7905882352941278.872
274728ELWOOD EC;5P
50/50
3.4033.403
960751AF2-366 C
Adder
7.2411764705882366.155
942422AE2-255 E
Adder
9.5682352941176458.133
960582AF2-349 E
Adder
37.6611764705882432.012
937312AD2-172 E
Adder
3.51411764705882362.987
274859EASYR;U1 E
Adder
12.43176470588235310.567
276642AC1-204 GEN2
50/50
12.65812.658
274707KENDALL ;2S
50/50
2.82.8
957331AF2-027 C
Adder
2.60588235294117652.215
936511AD2-066 C
Adder
8.6258823529411767.332
936512AD2-066 E
Adder
5.7505882352941184.888
295109WESTBROOK E
Adder
5.8105882352941184.939
941551AE2-152 C
Adder
11.93058823529411910.141
274676JOLIET 29;8U
50/50
77.11877.118
274704KENDALL ;1C
50/50
4.1874.187
274706KENDALL ;2C
50/50
4.1874.187
274705KENDALL ;1S
50/50
2.82.8
958481AF2-142 C
Adder
11.0105882352941199.359
957332AF2-027 E
Adder
3.90941176470588263.323
941552AE2-152 E
Adder
7.9529411764705886.76
958482AF2-142 E
Adder
7.346.239
938852AE1-113 E
Adder
29.8529411764705925.375
293644O22 E1
50/50
17.10817.108
960281AF2-319 C
50/50
2.9782.978
960752AF2-366 E
Adder
4.8282352941176474.104
957471AF2-041 C
Adder
22.22000000000000218.887
294763P-046 E
Adder
9.7670588235294128.302
938861AE1-114 C
Adder
4.0694117647058823.459
293645O22 E2
50/50
19.59519.595
960282AF2-319 E
50/50
4.4674.467
918052AA1-018 E OP
Adder
15.96470588235294113.57
274661LASCO STA;2U
50/50
25.87825.878
943122AE2-341 E
Adder
6.4870588235294125.514
939322AE1-163 E
Adder
36.631.11
936372AD2-047 E
Adder
19.92117647058823616.933
274654BRAIDWOOD;1U
50/50
27.92327.923
274861TOP CROP ;1U
50/50
0.4460.446
276591L-013 2
Adder
3.81294117647058833.241
962781AG1-127 C
Adder
7.2623529411764716.173
933911AD1-013 C
Adder
1.9105882352941181.624
939352AE1-166 E
Adder
9.5447058823529418.113
294392P-010 E
Adder
20.61647058823529517.524
959352AF2-226 E
50/50
4.4674.467
934101AD2-000 1
Adder
5.9694117647058835.074
958492AF2-143 E
Adder
7.29529411764705856.201
942421AE2-255 C
Adder
3.18941176470588242.711
290108LEEDK;1U E
Adder
24.89294117647058621.159
916221Z1-073 E
Adder
7.6470588235294126.5
957472AF2-041 E
Adder
11.1094117647058829.443
959092AF2-200 E
Adder
9.8752941176470598.394
938862AE1-114 E
Adder
13.88352941176470711.801
274655BRAIDWOOD;2U
50/50
27.1727.17
276640AC1-204 GEN1
50/50
12.63712.637
959351AF2-226 C
50/50
2.9782.978
958491AF2-143 C
Adder
10.9435294117647069.302
933912AD1-013 E
Adder
3.0517647058823532.594
936371AD2-047 C
Adder
4.083.468
936461AD2-060 C
Adder
2.42.04
933412AC2-154 E
Adder
3.723.162
962782AG1-127 E
Adder
4.8329411764705884.108
946671AF1-331 C
Adder
2.48117647058823552.109
920272AA2-123 E
Adder
2.9882352941176472.54
276170Z1-108 E
Adder
3.04941176470588272.592
276675AE2-062 E
Adder
0.155294117647058830.132
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.7170.717
TVALTFEXP_TVA->PJM
CLTF
1.3271.327
O66PJM->LTFIMP_O-066
CMTX_NF
12.69412.694
NYPJM->LTFIMP_NY
CLTF
1.0641.064
WECLTFEXP_WEC->PJM
CLTF
4.0674.067
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4860.486
CBM West 1LTFEXP_CBM-W1->PJM
CBM
82.96182.961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.43914.439
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6180.618
MECLTFEXP_MEC->PJM
CLTF
13.41113.411
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.7971.797
LAGNLTFEXP_LAGN->PJM
CLTF
3.5523.552
G-007PJM->LTFIMP_G-007
CMTX_NF
1.9781.978
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2520.252

Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.57 %
Rating:1399.0 MVA
Rating Type:B
MVA to Mitigate:1546.92
MW Contribution:12.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
958012AF2-095 E
Adder
6.9117647058823535.875
934111AD2-000 2
Adder
6.3847058823529415.427
966442AG1-513 E
Adder
0.7917647058823530.673
274683WAUKEGAN ;8U
Adder
46.4929411764705939.519
290051GSG-6; E
Adder
10.8517647058823539.224
959082AF2-199 E
Adder
3.7035294117647063.148
966092AG1-478 E
Adder
0.51176470588235290.435
274736ELWOOD EC;9P
50/50
3.4033.403
274682WAUKEGAN ;7U
Adder
43.1352941176470636.665
942651AE2-281 C
Adder
0.85058823529411760.723
942652AE2-281 E
Adder
5.2282352941176474.444
962691AG1-118 C
Adder
22.9905882352941219.542
962692AG1-118 E
Adder
15.32705882352941313.028
938851AE1-113 C
Adder
8.427.157
272363ESS H440 ; R
Adder
2.7282352941176472.319
959091AF2-200 C
Adder
14.81176470588235412.59
940502AE2-035 E
Adder
3.51411764705882362.987
958011AF2-095 C
Adder
10.3682352941176488.813
933411AC2-154 C
Adder
2.281.938
274687WILL CNTY;4U
50/50
72.73672.736
966091AG1-478 C
Adder
2.03411764705882361.729
966441AG1-513 C
Adder
0.52823529411764710.449
959081AF2-199 C
Adder
7.4058823529411776.295
293519PILOT HIL;1E
Adder
16.80117647058823514.281
939351AE1-166 C
Adder
10.348.789
274675JOLIET 29;7U
50/50
77.07277.072
274674JOLIET 9 ;6U
Adder
35.7635294117647130.399
293061N-015 E
Adder
16.2329411764705913.798
943121AE2-341 C
Adder
13.20823529411764811.227
274862TOP CROP ;2U
50/50
0.8510.851
939321AE1-163 C
Adder
5.957647058823535.064
295111SUBLETTE E
Adder
2.8247058823529412.401
274860EASYR;U2 E
Adder
12.43058823529411910.566
274660LASCO STA;1U
50/50
25.79225.792
943592AF1-030 E
Adder
4.3458823529411763.694
943591AF1-030 C
Adder
8.7835294117647067.466
936292AD2-038 E
Adder
15.02823529411764612.774
290021O50 E
Adder
20.41058823529411717.349
937002AD2-134 E
Adder
10.4917647058823528.918
960591AF2-350 C
Adder
7.26.12
960592AF2-350 E
Adder
4.84.08
275149KELLYCK ;1E
Adder
16.80117647058823514.281
934722AD1-100 E
Adder
92.7976470588235378.878
274728ELWOOD EC;5P
50/50
3.4033.403
960751AF2-366 C
Adder
7.2411764705882366.155
942422AE2-255 E
Adder
9.5682352941176458.133
960582AF2-349 E
Adder
37.6588235294117632.01
937312AD2-172 E
Adder
3.51411764705882362.987
274859EASYR;U1 E
Adder
2.5529411764705882.17
276642AC1-204 GEN2
50/50
12.65712.657
274707KENDALL ;2S
50/50
2.82.8
957331AF2-027 C
Adder
2.60588235294117652.215
936511AD2-066 C
Adder
8.6258823529411767.332
936512AD2-066 E
Adder
5.7505882352941184.888
295109WESTBROOK E
Adder
5.80941176470588254.938
941551AE2-152 C
Adder
11.93058823529411910.141
274676JOLIET 29;8U
50/50
77.11677.116
274704KENDALL ;1C
50/50
4.1874.187
274706KENDALL ;2C
50/50
4.1874.187
274705KENDALL ;1S
50/50
2.82.8
958481AF2-142 C
Adder
11.0105882352941199.359
957332AF2-027 E
Adder
3.9082352941176473.322
941552AE2-152 E
Adder
7.95411764705882356.761
958482AF2-142 E
Adder
7.346.239
938852AE1-113 E
Adder
29.85176470588235325.374
293644O22 E1
50/50
17.10817.108
960281AF2-319 C
50/50
2.9782.978
960752AF2-366 E
Adder
4.8270588235294124.103
957471AF2-041 C
Adder
22.2176470588235318.885
294763P-046 E
Adder
9.7670588235294128.302
938861AE1-114 C
Adder
4.0694117647058823.459
293645O22 E2
50/50
19.59519.595
960282AF2-319 E
50/50
4.4674.467
918052AA1-018 E OP
Adder
15.96470588235294113.57
274661LASCO STA;2U
50/50
25.87625.876
943122AE2-341 E
Adder
6.4858823529411775.513
939322AE1-163 E
Adder
36.5988235294117731.109
936372AD2-047 E
Adder
19.92117647058823616.933
274654BRAIDWOOD;1U
50/50
27.92427.924
274861TOP CROP ;1U
50/50
0.4460.446
276591L-013 2
Adder
3.81294117647058833.241
962781AG1-127 C
Adder
7.2611764705882356.172
933911AD1-013 C
Adder
1.9105882352941181.624
939352AE1-166 E
Adder
9.5447058823529418.113
294392P-010 E
Adder
20.6152941176470617.523
959352AF2-226 E
50/50
4.4674.467
934101AD2-000 1
Adder
5.96823529411764755.073
958492AF2-143 E
Adder
7.29529411764705856.201
942421AE2-255 C
Adder
3.18941176470588242.711
290108LEEDK;1U E
Adder
24.89058823529411821.157
916221Z1-073 E
Adder
7.6470588235294126.5
957472AF2-041 E
Adder
11.1094117647058829.443
959092AF2-200 E
Adder
9.8741176470588248.393
938862AE1-114 E
Adder
13.88235294117647111.8
274655BRAIDWOOD;2U
50/50
27.1727.17
276640AC1-204 GEN1
50/50
12.63612.636
959351AF2-226 C
50/50
2.9782.978
958491AF2-143 C
Adder
10.9435294117647069.302
933912AD1-013 E
Adder
3.0517647058823532.594
936371AD2-047 C
Adder
4.083.468
936461AD2-060 C
Adder
2.42.04
933412AC2-154 E
Adder
3.723.162
274732ELWOOD EC;7P
50/50
3.4033.403
962782AG1-127 E
Adder
4.8317647058823534.107
946671AF1-331 C
Adder
2.48117647058823552.109
276675AE2-062 E
Adder
0.155294117647058830.132
920272AA2-123 E
Adder
2.9882352941176472.54
276170Z1-108 E
Adder
3.04941176470588272.592
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.7170.717
TVALTFEXP_TVA->PJM
CLTF
1.3271.327
O66PJM->LTFIMP_O-066
CMTX_NF
12.69312.693
NYPJM->LTFIMP_NY
CLTF
1.0641.064
WECLTFEXP_WEC->PJM
CLTF
4.0664.066
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4860.486
CBM West 1LTFEXP_CBM-W1->PJM
CBM
82.95582.955
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.43814.438
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6180.618
MECLTFEXP_MEC->PJM
CLTF
13.4113.41
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.7971.797
LAGNLTFEXP_LAGN->PJM
CLTF
3.5523.552
G-007PJM->LTFIMP_G-007
CMTX_NF
1.9781.978
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2520.252

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.43 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1226.4
MW Contribution:11.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274814UNIV PK N;0U
50/50
1.9011.901
274807UNIV PK N;3U
50/50
1.9251.925
274816UNIV PK N;YU
50/50
1.9251.925
958011AF2-095 C
Adder
9.6458823529411778.199
933411AC2-154 C
Adder
2.1211764705882351.803
274687WILL CNTY;4U
Adder
56.08235294117647447.67
966091AG1-478 C
Adder
1.76941176470588251.504
966441AG1-513 C
Adder
0.434117647058823550.369
959081AF2-199 C
Adder
6.0258823529411775.122
916212CRESCENT ;1U
Adder
4.0658823529411773.456
294410BSHIL;2U E
Adder
7.2082352941176476.127
961501AF2-441 C
Adder
7.2070588235294136.126
293519PILOT HIL;1E
Adder
15.63058823529411813.286
939351AE1-166 C
Adder
8.555294117647067.272
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
293061N-015 E
Adder
13.20352941176470711.223
943121AE2-341 C
Adder
10.8588235294117659.23
939321AE1-163 C
Adder
5.3388235294117654.538
295111SUBLETTE E
Adder
2.3082352941176471.962
274860EASYR;U2 E
Adder
10.1270588235294138.608
927209AC1-214 E2
Adder
2.7435294117647062.332
946322AF1-296 E
Adder
5.1964705882352944.417
274813UNIV PK N;9U
50/50
1.9091.909
274811UNIV PK N;7U
50/50
1.9251.925
941551AE2-152 C
Adder
9.8717647058823528.391
274676JOLIET 29;8U
Adder
62.29647058823529452.952
958481AF2-142 C
Adder
10.2776470588235318.736
957332AF2-027 E
Adder
3.1823529411764712.705
274891CAYUG;2U E
Adder
11.4552941176470599.737
926822AC1-168 E
Adder
6.4588235294117655.49
966092AG1-478 E
Adder
0.44470588235294120.378
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
938851AE1-113 C
Adder
6.7458823529411775.734
272363ESS H440 ; R
Adder
2.22941176470588241.895
959091AF2-200 C
Adder
12.05294117647058810.245
940502AE2-035 E
Adder
2.8647058823529412.435
274815UNIV PK N;XU
50/50
1.9131.913
958012AF2-095 E
Adder
6.4305882352941185.466
934111AD2-000 2
Adder
5.0882352941176484.325
966442AG1-513 E
Adder
0.65058823529411770.553
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
290051GSG-6; E
Adder
8.8682352941176487.538
959082AF2-199 E
Adder
3.01294117647058852.561
958912AF2-182 E
Adder
28.79647058823529424.477
294401BSHIL;1U E
Adder
7.2082352941176476.127
910542X3-005 E
Adder
0.53764705882352950.457
939352AE1-166 E
Adder
7.897647058823536.713
294392P-010 E
Adder
16.76941176470588214.254
274808UNIV PK N;4U
50/50
1.9171.917
959351AF2-226 C
Adder
2.0270588235294121.723
958491AF2-143 C
Adder
9.8058823529411778.335
933912AD1-013 E
Adder
2.49411764705882362.12
946152AF1-280 E
Adder
19.1976470588235316.318
293771O-035 E
Adder
5.7870588235294124.919
293716O-029 E
Adder
4.4917647058823533.818
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
275149KELLYCK ;1E
Adder
15.63058823529411813.286
934722AD1-100 E
Adder
76.7823529411764765.265
960751AF2-366 C
Adder
5.9247058823529415.036
942422AE2-255 E
Adder
7.6658823529411776.516
274805UNIV PK N;1U
50/50
1.9131.913
943592AF1-030 E
Adder
3.5729411764705883.037
943591AF1-030 C
Adder
7.2211764705882366.138
936292AD2-038 E
Adder
13.46705882352941211.447
290021O50 E
Adder
16.3552941176470613.902
937002AD2-134 E
Adder
8.5752941176470587.289
960582AF2-349 E
Adder
30.726.095
937312AD2-172 E
Adder
2.8647058823529412.435
274859EASYR;U1 E
Adder
10.1270588235294138.608
957331AF2-027 C
Adder
2.1211764705882351.803
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
295109WESTBROOK E
Adder
4.7482352941176474.036
939061AE1-134 2
Adder
1.15294117647058810.98
274810UNIV PK N;6U
50/50
1.9171.917
274812UNIV PK N;8U
50/50
1.9091.909
941552AE2-152 E
Adder
6.5811764705882365.594
958482AF2-142 E
Adder
6.8517647058823535.824
938852AE1-113 E
Adder
23.91882352941176420.331
274890CAYUG;1U E
Adder
11.4552941176470599.737
962012AG1-044 E
Adder
0.0529411764705882350.045
925582AC1-033 E
Adder
7.9023529411764716.717
293644O22 E1
Adder
11.6458823529411759.899
960281AF2-319 C
Adder
2.0270588235294121.723
960752AF2-366 E
Adder
3.94941176470588263.357
957471AF2-041 C
Adder
18.07882352941176815.367
294763P-046 E
Adder
7.9611764705882366.767
938861AE1-114 C
Adder
3.3164705882352942.819
293645O22 E2
Adder
13.33882352941176411.338
960282AF2-319 E
Adder
3.0411764705882352.585
918052AA1-018 E OP
Adder
14.9023529411764712.667
293715O-029 E
Adder
8.1929411764705896.964
961502AF2-441 E
Adder
10.8105882352941189.189
943122AE2-341 E
Adder
5.3317647058823534.532
939322AE1-163 E
Adder
32.7952941176470627.876
927208AC1-214 E1
Adder
2.7435294117647062.332
293516O-009 E
Adder
15.8423529411764713.466
293717O-029 E
Adder
4.1282352941176473.509
936372AD2-047 E
Adder
18.53411764705882415.754
276591L-013 2
Adder
3.11882352941176462.651
962781AG1-127 C
Adder
5.94117647058823555.05
933911AD1-013 C
Adder
1.56117647058823541.327
959352AF2-226 E
Adder
3.0411764705882352.585
934101AD2-000 1
Adder
4.91411764705882354.177
958492AF2-143 E
Adder
6.537647058823535.557
942421AE2-255 C
Adder
2.5552941176470592.172
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
957472AF2-041 E
Adder
9.0400000000000017.684
959092AF2-200 E
Adder
8.0352941176470596.83
926821AC1-168 C
Adder
0.96235294117647050.818
938862AE1-114 E
Adder
11.315294117647069.618
936371AD2-047 C
Adder
3.7964705882352943.227
936461AD2-060 C
Adder
2.2329411764705881.898
933412AC2-154 E
Adder
3.46117647058823552.942
962782AG1-127 E
Adder
3.9541176470588243.361
946671AF1-331 C
Adder
2.0282352941176471.724
276626AG1-044 E
Adder
0.062352941176470590.053
276675AE2-062 E
Adder
0.135294117647058840.115
920272AA2-123 E
Adder
2.4364705882352942.071
276170Z1-108 E
Adder
2.48588235294117642.113
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142
NYPJM->LTFIMP_NY
CLTF
0.9330.933
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.43 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1226.4
MW Contribution:11.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274814UNIV PK N;0U
50/50
1.9011.901
274807UNIV PK N;3U
50/50
1.9251.925
274816UNIV PK N;YU
50/50
1.9251.925
958011AF2-095 C
Adder
9.6458823529411778.199
933411AC2-154 C
Adder
2.1211764705882351.803
274687WILL CNTY;4U
Adder
56.08235294117647447.67
966091AG1-478 C
Adder
1.76941176470588251.504
966441AG1-513 C
Adder
0.434117647058823550.369
959081AF2-199 C
Adder
6.0258823529411775.122
916212CRESCENT ;1U
Adder
4.0658823529411773.456
294410BSHIL;2U E
Adder
7.2082352941176476.127
961501AF2-441 C
Adder
7.2070588235294136.126
293519PILOT HIL;1E
Adder
15.63058823529411813.286
939351AE1-166 C
Adder
8.555294117647067.272
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274813UNIV PK N;9U
50/50
1.9091.909
274811UNIV PK N;7U
50/50
1.9251.925
941551AE2-152 C
Adder
9.8717647058823528.391
274676JOLIET 29;8U
Adder
62.29647058823529452.952
958481AF2-142 C
Adder
10.2776470588235318.736
957332AF2-027 E
Adder
3.1823529411764712.705
274891CAYUG;2U E
Adder
11.4552941176470599.737
926822AC1-168 E
Adder
6.4588235294117655.49
966092AG1-478 E
Adder
0.44470588235294120.378
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
938851AE1-113 C
Adder
6.7458823529411775.734
272363ESS H440 ; R
Adder
2.22941176470588241.895
959091AF2-200 C
Adder
12.05294117647058810.245
940502AE2-035 E
Adder
2.8647058823529412.435
274815UNIV PK N;XU
50/50
1.9131.913
958012AF2-095 E
Adder
6.4305882352941185.466
934111AD2-000 2
Adder
5.0882352941176484.325
966442AG1-513 E
Adder
0.65058823529411770.553
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
290051GSG-6; E
Adder
8.8682352941176487.538
959082AF2-199 E
Adder
3.01294117647058852.561
958912AF2-182 E
Adder
28.79647058823529424.477
294401BSHIL;1U E
Adder
7.2082352941176476.127
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
293061N-015 E
Adder
13.20352941176470711.223
943121AE2-341 C
Adder
10.8588235294117659.23
939321AE1-163 C
Adder
5.3388235294117654.538
295111SUBLETTE E
Adder
2.3082352941176471.962
274860EASYR;U2 E
Adder
10.1270588235294138.608
927209AC1-214 E2
Adder
2.7435294117647062.332
946322AF1-296 E
Adder
5.1964705882352944.417
274808UNIV PK N;4U
50/50
1.9171.917
959351AF2-226 C
Adder
2.0270588235294121.723
958491AF2-143 C
Adder
9.8058823529411778.335
933912AD1-013 E
Adder
2.49411764705882362.12
274805UNIV PK N;1U
50/50
1.9131.913
943592AF1-030 E
Adder
3.5729411764705883.037
943591AF1-030 C
Adder
7.2211764705882366.138
936292AD2-038 E
Adder
13.46705882352941211.447
290021O50 E
Adder
16.3552941176470613.902
937002AD2-134 E
Adder
8.5752941176470587.289
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
275149KELLYCK ;1E
Adder
15.63058823529411813.286
934722AD1-100 E
Adder
76.7823529411764765.265
960751AF2-366 C
Adder
5.9247058823529415.036
942422AE2-255 E
Adder
7.6658823529411776.516
960582AF2-349 E
Adder
30.726.095
937312AD2-172 E
Adder
2.8647058823529412.435
274859EASYR;U1 E
Adder
10.1270588235294138.608
957331AF2-027 C
Adder
2.1211764705882351.803
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
295109WESTBROOK E
Adder
4.7482352941176474.036
939061AE1-134 2
Adder
1.15294117647058810.98
274810UNIV PK N;6U
50/50
1.9171.917
274812UNIV PK N;8U
50/50
1.9091.909
941552AE2-152 E
Adder
6.5811764705882365.594
958482AF2-142 E
Adder
6.8517647058823535.824
938852AE1-113 E
Adder
23.91882352941176420.331
274890CAYUG;1U E
Adder
11.4552941176470599.737
962012AG1-044 E
Adder
0.0529411764705882350.045
925582AC1-033 E
Adder
7.9023529411764716.717
293644O22 E1
Adder
11.6458823529411759.899
960281AF2-319 C
Adder
2.0270588235294121.723
960752AF2-366 E
Adder
3.94941176470588263.357
957471AF2-041 C
Adder
18.07882352941176815.367
294763P-046 E
Adder
7.9611764705882366.767
938861AE1-114 C
Adder
3.3164705882352942.819
293645O22 E2
Adder
13.33882352941176411.338
960282AF2-319 E
Adder
3.0411764705882352.585
918052AA1-018 E OP
Adder
14.9023529411764712.667
293715O-029 E
Adder
8.1929411764705896.964
961502AF2-441 E
Adder
10.8105882352941189.189
943122AE2-341 E
Adder
5.3317647058823534.532
939322AE1-163 E
Adder
32.7952941176470627.876
927208AC1-214 E1
Adder
2.7435294117647062.332
293516O-009 E
Adder
15.8423529411764713.466
293717O-029 E
Adder
4.1282352941176473.509
936372AD2-047 E
Adder
18.53411764705882415.754
276591L-013 2
Adder
3.11882352941176462.651
962781AG1-127 C
Adder
5.94117647058823555.05
933911AD1-013 C
Adder
1.56117647058823541.327
910542X3-005 E
Adder
0.53764705882352950.457
939352AE1-166 E
Adder
7.897647058823536.713
294392P-010 E
Adder
16.76941176470588214.254
959352AF2-226 E
Adder
3.0411764705882352.585
934101AD2-000 1
Adder
4.91411764705882354.177
958492AF2-143 E
Adder
6.537647058823535.557
942421AE2-255 C
Adder
2.5552941176470592.172
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
957472AF2-041 E
Adder
9.0400000000000017.684
959092AF2-200 E
Adder
8.0352941176470596.83
926821AC1-168 C
Adder
0.96235294117647050.818
938862AE1-114 E
Adder
11.315294117647069.618
946152AF1-280 E
Adder
19.1976470588235316.318
293771O-035 E
Adder
5.7870588235294124.919
293716O-029 E
Adder
4.4917647058823533.818
936371AD2-047 C
Adder
3.7964705882352943.227
936461AD2-060 C
Adder
2.2329411764705881.898
933412AC2-154 E
Adder
3.46117647058823552.942
962782AG1-127 E
Adder
3.9541176470588243.361
946671AF1-331 C
Adder
2.0282352941176471.724
276626AG1-044 E
Adder
0.062352941176470590.053
276675AE2-062 E
Adder
0.135294117647058840.115
920272AA2-123 E
Adder
2.4364705882352942.071
276170Z1-108 E
Adder
2.48588235294117642.113
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142
NYPJM->LTFIMP_NY
CLTF
0.9330.933
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.41 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1226.15
MW Contribution:11.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274814UNIV PK N;0U
50/50
1.8911.891
274813UNIV PK N;9U
50/50
1.8991.899
274811UNIV PK N;7U
50/50
1.9151.915
941551AE2-152 C
Adder
9.7929411764705888.324
274676JOLIET 29;8U
Adder
61.7682352941176552.503
958481AF2-142 C
Adder
10.2035294117647068.673
957332AF2-027 E
Adder
3.15764705882352952.684
274891CAYUG;2U E
Adder
11.395294117647069.686
926822AC1-168 E
Adder
6.4258823529411765.462
966092AG1-478 E
Adder
0.44117647058823530.375
274682WAUKEGAN ;7U
Adder
34.8235294117647129.6
942651AE2-281 C
Adder
0.75764705882352950.644
942652AE2-281 E
Adder
4.6529411764705893.955
962691AG1-118 C
Adder
18.6752941176470615.874
962692AG1-118 E
Adder
12.45058823529411810.583
938851AE1-113 C
Adder
6.75.695
272363ESS H440 ; R
Adder
2.21411764705882331.882
959091AF2-200 C
Adder
11.97176470588235410.176
940502AE2-035 E
Adder
2.84588235294117682.419
274815UNIV PK N;XU
50/50
1.9031.903
958012AF2-095 E
Adder
6.3717647058823535.416
934111AD2-000 2
Adder
5.0470588235294124.29
966442AG1-513 E
Adder
0.64470588235294120.548
274683WAUKEGAN ;8U
Adder
37.5458823529411831.914
290051GSG-6; E
Adder
8.8082352941176477.487
959082AF2-199 E
Adder
2.99294117647058842.544
958912AF2-182 E
Adder
28.6258823529411824.332
294401BSHIL;1U E
Adder
7.17647058823529356.1
961501AF2-441 C
Adder
7.1070588235294126.041
293519PILOT HIL;1E
Adder
15.48823529411764713.165
939351AE1-166 C
Adder
8.4870588235294137.214
274675JOLIET 29;7U
Adder
61.79058823529411652.522
274674JOLIET 9 ;6U
Adder
31.0329411764705926.378
293061N-015 E
Adder
13.10117647058823411.136
943121AE2-341 C
Adder
10.7729411764705899.157
939321AE1-163 C
Adder
5.302352941176474.507
295111SUBLETTE E
Adder
2.29294117647058831.949
274860EASYR;U2 E
Adder
10.0658823529411758.556
927209AC1-214 E2
Adder
2.7317647058823532.322
946322AF1-296 E
Adder
5.1729411764705894.397
274807UNIV PK N;3U
50/50
1.9151.915
274816UNIV PK N;YU
50/50
1.9151.915
958011AF2-095 C
Adder
9.557647058823538.124
933411AC2-154 C
Adder
2.10235294117647081.787
274687WILL CNTY;4U
Adder
55.58000000000000547.243
966091AG1-478 C
Adder
1.7552941176470591.492
966441AG1-513 C
Adder
0.430588235294117660.366
959081AF2-199 C
Adder
5.9858823529411775.088
916212CRESCENT ;1U
Adder
4.0470588235294123.44
294410BSHIL;2U E
Adder
7.17647058823529356.1
274805UNIV PK N;1U
50/50
1.9031.903
943592AF1-030 E
Adder
3.54470588235294143.013
943591AF1-030 C
Adder
7.1635294117647066.089
936292AD2-038 E
Adder
13.37529411764705911.369
290021O50 E
Adder
16.24352941176470813.807
937002AD2-134 E
Adder
8.5164705882352937.239
960591AF2-350 C
Adder
6.637647058823535.642
960592AF2-350 E
Adder
4.4247058823529413.761
275149KELLYCK ;1E
Adder
15.48823529411764713.165
934722AD1-100 E
Adder
76.1647058823529364.74
960751AF2-366 C
Adder
5.8811764705882354.999
942422AE2-255 E
Adder
7.61411764705882456.472
960582AF2-349 E
Adder
30.4847058823529425.912
937312AD2-172 E
Adder
2.84588235294117682.419
274859EASYR;U1 E
Adder
10.0658823529411758.556
957331AF2-027 C
Adder
2.1047058823529411.789
936511AD2-066 C
Adder
7.1305882352941186.061
936512AD2-066 E
Adder
4.7541176470588244.041
295109WESTBROOK E
Adder
4.7152941176470594.008
939061AE1-134 2
Adder
1.14705882352941170.975
274810UNIV PK N;6U
50/50
1.9071.907
274812UNIV PK N;8U
50/50
1.8991.899
941552AE2-152 E
Adder
6.5282352941176485.549
958482AF2-142 E
Adder
6.8023529411764715.782
938852AE1-113 E
Adder
23.75647058823529520.193
274890CAYUG;1U E
Adder
11.395294117647069.686
962012AG1-044 E
Adder
0.0529411764705882350.045
925582AC1-033 E
Adder
7.8670588235294126.687
293644O22 E1
Adder
11.5517647058823549.819
960281AF2-319 C
Adder
2.0105882352941181.709
960752AF2-366 E
Adder
3.92117647058823553.333
957471AF2-041 C
Adder
17.9576470588235315.264
294763P-046 E
Adder
7.9094117647058826.723
938861AE1-114 C
Adder
3.2964705882352942.802
293645O22 E2
Adder
13.2305882352941211.246
960282AF2-319 E
Adder
3.01647058823529422.564
918052AA1-018 E OP
Adder
14.7952941176470612.576
293715O-029 E
Adder
8.1494117647058816.927
961502AF2-441 E
Adder
10.6611764705882349.062
943122AE2-341 E
Adder
5.2905882352941184.497
939322AE1-163 E
Adder
32.5729411764705927.687
927208AC1-214 E1
Adder
2.7317647058823532.322
293516O-009 E
Adder
15.7576470588235313.394
293717O-029 E
Adder
4.1070588235294123.491
936372AD2-047 E
Adder
18.36705882352941215.612
276591L-013 2
Adder
3.09411764705882362.63
962781AG1-127 C
Adder
5.8976470588235295.013
933911AD1-013 C
Adder
1.55058823529411781.318
910542X3-005 E
Adder
0.53058823529411770.451
939352AE1-166 E
Adder
7.8341176470588236.659
294392P-010 E
Adder
16.63882352941176614.143
959352AF2-226 E
Adder
3.01647058823529422.564
934101AD2-000 1
Adder
4.8788235294117654.147
958492AF2-143 E
Adder
6.4929411764705885.519
942421AE2-255 C
Adder
2.53764705882352942.157
290108LEEDK;1U E
Adder
20.2152941176470617.183
916221Z1-073 E
Adder
6.2070588235294125.276
957472AF2-041 E
Adder
8.9788235294117647.632
959092AF2-200 E
Adder
7.98117647058823556.784
926821AC1-168 C
Adder
0.95764705882352940.814
938862AE1-114 E
Adder
11.244705882352949.558
274808UNIV PK N;4U
50/50
1.9071.907
959351AF2-226 C
Adder
2.0105882352941181.709
958491AF2-143 C
Adder
9.748.279
933912AD1-013 E
Adder
2.47764705882352932.106
946152AF1-280 E
Adder
19.08352941176470816.221
293771O-035 E
Adder
5.7611764705882364.897
293716O-029 E
Adder
4.46823529411764753.798
936371AD2-047 C
Adder
3.76235294117647053.198
936461AD2-060 C
Adder
2.2129411764705881.881
933412AC2-154 E
Adder
3.42941176470588262.915
962782AG1-127 E
Adder
3.92470588235294133.336
946671AF1-331 C
Adder
2.01411764705882361.712
276626AG1-044 E
Adder
0.061176470588235290.052
276675AE2-062 E
Adder
0.134117647058823540.114
920272AA2-123 E
Adder
2.4188235294117652.056
276170Z1-108 E
Adder
2.4670588235294122.097
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6070.607
TVALTFEXP_TVA->PJM
CLTF
1.1671.167
O66PJM->LTFIMP_O-066
CMTX_NF
11.09411.094
NYPJM->LTFIMP_NY
CLTF
0.9310.931
WECLTFEXP_WEC->PJM
CLTF
3.2883.288
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4090.409
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.23368.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.47412.474
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.4090.409
MECLTFEXP_MEC->PJM
CLTF
10.92410.924
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.1721.172
LAGNLTFEXP_LAGN->PJM
CLTF
2.992.99
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7291.729
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.210.21
SIGELTFEXP_SIGE->PJM
CLTF
0.0150.015

Details for WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT5-6___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.85 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1701.87
MW Contribution:14.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274800UNIV PARK;3U
50/50
1.2031.203
941551AE2-152 C
50/50
15.22915.229
274676JOLIET 29;8U
Adder
76.0835294117647264.671
274847GR RIDGE ;BU
50/50
0.6370.637
958481AF2-142 C
Adder
11.90941176470588110.123
957332AF2-027 E
Adder
3.94352941176470573.352
274891CAYUG;2U E
50/50
16.86716.867
958012AF2-095 E
50/50
8.5938.593
274887PILOT HIL;1U
50/50
0.850.85
934111AD2-000 2
Adder
6.317647058823535.37
966442AG1-513 E
Adder
0.80941176470588230.688
274683WAUKEGAN ;8U
Adder
46.8729411764705939.842
290051GSG-6; E
Adder
11.102352941176479.437
959082AF2-199 E
Adder
3.77294117647058823.207
961501AF2-441 C
Adder
10.5505882352941188.968
293519PILOT HIL;1E
50/50
20.88720.887
939351AE1-166 C
50/50
13.19813.198
274675JOLIET 29;7U
Adder
76.0835294117647264.671
274674JOLIET 9 ;6U
Adder
38.7023529411764732.897
293061N-015 E
50/50
17.13617.136
943121AE2-341 C
Adder
13.58823529411764911.55
939321AE1-163 C
Adder
6.3164705882352945.369
295111SUBLETTE E
Adder
2.88941176470588262.456
274790SE CHICAG;7U
Adder
1.68941176470588241.436
966092AG1-478 E
50/50
0.5630.563
274682WAUKEGAN ;7U
Adder
43.47411764705882636.953
942651AE2-281 C
Adder
0.90235294117647060.767
942652AE2-281 E
Adder
5.5435294117647054.712
962691AG1-118 C
Adder
23.50941176470588419.983
962692AG1-118 E
Adder
15.67294117647058713.322
938851AE1-113 C
Adder
8.4129411764705877.151
272363ESS H440 ; R
Adder
2.7917647058823532.373
959091AF2-200 C
Adder
15.08941176470588312.826
940502AE2-035 E
Adder
3.58235294117647073.045
274788SE CHICAG;5U
Adder
4.5223529411764713.844
274798UNIV PARK;1U
50/50
1.2121.212
958011AF2-095 C
50/50
12.8912.89
933411AC2-154 C
50/50
2.8352.835
274687WILL CNTY;4U
Adder
70.7847058823529460.167
966091AG1-478 C
50/50
2.242.24
966441AG1-513 C
Adder
0.540.459
959081AF2-199 C
Adder
7.5447058823529416.413
274888KELLY CRK;1U
50/50
0.850.85
274660LASCO STA;1U
50/50
27.28127.281
943592AF1-030 E
Adder
4.4705882352941183.8
943591AF1-030 C
Adder
9.0364705882352957.681
936292AD2-038 E
Adder
15.93411764705882513.544
290021O50 E
Adder
20.39647058823529617.337
937002AD2-134 E
Adder
10.7341176470588249.124
957371AF2-031 C
Adder
0.98823529411764710.84
274770LINCOLN ;1U
50/50
3.0623.062
274773LINCOLN ;4U
50/50
3.0623.062
274772LINCOLN ;3U
50/50
3.0623.062
274771LINCOLN ;2U
50/50
3.0623.062
960591AF2-350 C
50/50
8.9528.952
960592AF2-350 E
50/50
5.9685.968
275149KELLYCK ;1E
50/50
20.88720.887
934722AD1-100 E
50/50
118.444118.444
934721AD1-100 C
50/50
3.8843.884
960751AF2-366 C
Adder
7.4047058823529416.294
942422AE2-255 E
Adder
9.5611764705882368.127
960582AF2-349 E
Adder
38.2764705882352932.535
937312AD2-172 E
Adder
3.58235294117647073.045
274871GR RIDGE ;2U
50/50
0.2370.237
957331AF2-027 C
Adder
2.62941176470588232.235
936511AD2-066 C
Adder
8.977647058823537.631
936512AD2-066 E
Adder
5.9847058823529415.087
274864CAYUGA RI;2U
50/50
0.5150.515
295109WESTBROOK E
Adder
5.9435294117647065.052
941552AE2-152 E
50/50
10.15210.152
958482AF2-142 E
Adder
7.93999999999999956.749
938852AE1-113 E
Adder
29.82941176470588525.355
274890CAYUG;1U E
50/50
16.86716.867
957372AF2-031 E
Adder
1.48235294117647071.26
274774LINCOLN ;5U
50/50
3.0623.062
293644O22 E1
Adder
15.21999999999999912.937
960281AF2-319 C
Adder
2.64941176470588242.252
960752AF2-366 E
Adder
4.9364705882352944.196
957471AF2-041 C
Adder
22.63411764705882619.239
294763P-046 E
Adder
9.9564705882352938.463
293645O22 E2
Adder
17.43176470588235514.817
960282AF2-319 E
Adder
3.9741176470588243.378
918052AA1-018 E OP
Adder
17.26941176470588214.679
961502AF2-441 E
Adder
15.82588235294117713.452
274661LASCO STA;2U
50/50
27.3727.37
943122AE2-341 E
Adder
6.6729411764705885.672
939322AE1-163 E
Adder
38.803529411764732.983
274863CAYUGA RI;1U
50/50
0.5150.515
274776LINCOLN ;7U
50/50
3.0623.062
936372AD2-047 E
50/50
24.76624.766
274654BRAIDWOOD;1U
50/50
29.85229.852
276591L-013 2
Adder
3.8835294117647063.301
962781AG1-127 C
Adder
7.4258823529411776.312
933911AD1-013 C
Adder
1.95411764705882351.661
910542X3-005 E
Adder
0.76941176470588240.654
939352AE1-166 E
50/50
12.18312.183
294392P-010 E
50/50
21.76221.762
959352AF2-226 E
Adder
3.9741176470588243.378
934101AD2-000 1
Adder
6.1705882352941185.245
958492AF2-143 E
Adder
7.7352941176470596.575
942421AE2-255 C
Adder
3.18705882352941172.709
290108LEEDK;1U E
Adder
25.4658823529411821.646
916221Z1-073 E
Adder
7.82352941176470656.65
957472AF2-041 E
Adder
11.3176470588235289.62
959092AF2-200 E
Adder
10.068.551
274655BRAIDWOOD;2U
50/50
29.08529.085
959351AF2-226 C
Adder
2.64941176470588242.252
958491AF2-143 C
Adder
11.6023529411764729.862
933912AD1-013 E
Adder
3.12235294117647082.654
274775LINCOLN ;6U
50/50
3.0623.062
274777LINCOLN ;8U
50/50
3.0623.062
936371AD2-047 C
50/50
5.0735.073
936461AD2-060 C
50/50
2.9842.984
933412AC2-154 E
50/50
4.6254.625
962782AG1-127 E
Adder
4.94117647058823554.2
946671AF1-331 C
Adder
2.53882352941176452.158
276675AE2-062 E
Adder
0.162352941176470620.138
276170Z1-108 E
Adder
3.0917647058823532.628
920272AA2-123 E
Adder
3.0352941176470592.58
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8740.874
TVALTFEXP_TVA->PJM
CLTF
1.4271.427
O66PJM->LTFIMP_O-066
CMTX_NF
14.71114.711
NYPJM->LTFIMP_NY
CLTF
1.2271.227
WECLTFEXP_WEC->PJM
CLTF
4.1174.117
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5980.598
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.2195.21
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.37116.371
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6470.647
MECLTFEXP_MEC->PJM
CLTF
13.89713.897
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.8521.852
LAGNLTFEXP_LAGN->PJM
CLTF
3.7743.774
G-007PJM->LTFIMP_G-007
CMTX_NF
2.2932.293
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3140.314
SIGELTFEXP_SIGE->PJM
CLTF
0.0210.021

Details for WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.88 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1746.33
MW Contribution:15.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274790SE CHICAG;7U
Adder
1.73411764705882351.474
274791SE CHICAG;8U
Adder
4.6423529411764713.946
966092AG1-478 E
50/50
0.5780.578
274682WAUKEGAN ;7U
Adder
44.62823529411764437.934
942651AE2-281 C
Adder
0.92705882352941180.788
942652AE2-281 E
Adder
5.6929411764705894.839
962691AG1-118 C
Adder
24.13176470588235420.512
962692AG1-118 E
Adder
16.0882352941176513.675
938851AE1-113 C
Adder
8.6364705882352947.341
272363ESS H440 ; R
Adder
2.8647058823529412.435
959091AF2-200 C
Adder
15.48823529411764713.165
940502AE2-035 E
Adder
3.67764705882352953.126
274800UNIV PARK;3U
50/50
1.2351.235
941551AE2-152 C
50/50
15.61115.611
274676JOLIET 29;8U
Adder
78.1152941176470566.398
274847GR RIDGE ;BU
50/50
0.6540.654
958481AF2-142 C
Adder
12.23176470588235410.397
957332AF2-027 E
Adder
4.0482352941176473.441
274891CAYUG;2U E
50/50
17.29517.295
274798UNIV PARK;1U
50/50
1.2441.244
958011AF2-095 C
50/50
13.22413.224
933411AC2-154 C
50/50
2.9082.908
274687WILL CNTY;4U
Adder
72.6647058823529561.765
966091AG1-478 C
50/50
2.2992.299
966441AG1-513 C
Adder
0.55411764705882350.471
959081AF2-199 C
Adder
7.74470588235294166.583
957371AF2-031 C
Adder
1.01411764705882360.862
274770LINCOLN ;1U
50/50
3.1623.162
274773LINCOLN ;4U
50/50
3.1623.162
274772LINCOLN ;3U
50/50
3.1623.162
274771LINCOLN ;2U
50/50
3.1623.162
960591AF2-350 C
50/50
9.1849.184
960592AF2-350 E
50/50
6.1226.122
275149KELLYCK ;1E
50/50
21.42821.428
934722AD1-100 E
50/50
121.416121.416
934721AD1-100 C
50/50
3.9823.982
960751AF2-366 C
Adder
7.6011764705882366.461
942422AE2-255 E
Adder
9.8141176470588248.342
960582AF2-349 E
Adder
39.29058823529411633.397
937312AD2-172 E
Adder
3.67764705882352953.126
961501AF2-441 C
Adder
10.8282352941176499.204
293519PILOT HIL;1E
50/50
21.42821.428
939351AE1-166 C
50/50
13.52913.529
274675JOLIET 29;7U
Adder
78.1152941176470566.398
274674JOLIET 9 ;6U
Adder
39.72588235294118433.767
293061N-015 E
50/50
17.5817.58
943121AE2-341 C
Adder
13.94823529411764811.856
939321AE1-163 C
Adder
6.4870588235294125.514
295111SUBLETTE E
Adder
2.96588235294117642.521
958012AF2-095 E
50/50
8.8168.816
274887PILOT HIL;1U
50/50
0.8720.872
934111AD2-000 2
Adder
6.4847058823529415.512
966442AG1-513 E
Adder
0.8317647058823530.707
274683WAUKEGAN ;8U
Adder
48.1176470588235340.9
290051GSG-6; E
Adder
11.395294117647069.686
959082AF2-199 E
Adder
3.87176470588235283.291
910542X3-005 E
Adder
0.79058823529411770.672
939352AE1-166 E
50/50
12.48912.489
294392P-010 E
50/50
22.32722.327
959352AF2-226 E
Adder
4.0788235294117653.467
934101AD2-000 1
Adder
6.3329411764705885.383
958492AF2-143 E
Adder
7.9435294117647066.752
942421AE2-255 C
Adder
3.2717647058823532.781
290108LEEDK;1U E
Adder
26.1422.219
916221Z1-073 E
Adder
8.0305882352941186.826
957472AF2-041 E
Adder
11.6164705882352959.874
959092AF2-200 E
Adder
10.3258823529411778.777
274655BRAIDWOOD;2U
50/50
29.82929.829
959351AF2-226 C
Adder
2.71882352941176462.311
958491AF2-143 C
Adder
11.91411764705882510.127
933912AD1-013 E
Adder
3.20470588235294152.724
274888KELLY CRK;1U
50/50
0.8720.872
274660LASCO STA;1U
50/50
27.98627.986
943592AF1-030 E
Adder
4.5894117647058823.901
943591AF1-030 C
Adder
9.2752941176470597.884
936292AD2-038 E
Adder
16.3623529411764713.908
290021O50 E
Adder
20.9376470588235317.797
937002AD2-134 E
Adder
11.0188235294117659.366
957372AF2-031 E
Adder
1.52117647058823541.293
274774LINCOLN ;5U
50/50
3.1623.162
293644O22 E1
Adder
15.62117647058823713.278
960281AF2-319 C
Adder
2.71882352941176462.311
960752AF2-366 E
Adder
5.0670588235294124.307
957471AF2-041 C
Adder
23.2329411764705919.748
294763P-046 E
Adder
10.2199999999999998.687
274871GR RIDGE ;2U
50/50
0.2430.243
957331AF2-027 C
Adder
2.69882352941176462.294
936511AD2-066 C
Adder
9.2141176470588247.832
936512AD2-066 E
Adder
6.1435294117647075.222
274864CAYUGA RI;2U
50/50
0.5280.528
295109WESTBROOK E
Adder
6.1011764705882365.186
941552AE2-152 E
50/50
10.40710.407
958482AF2-142 E
Adder
8.1541176470588246.931
938852AE1-113 E
Adder
30.62117647058823526.028
274890CAYUG;1U E
50/50
17.29517.295
293645O22 E2
Adder
17.89176470588235215.208
960282AF2-319 E
Adder
4.0788235294117653.467
918052AA1-018 E OP
Adder
17.73647058823529615.076
961502AF2-441 E
Adder
16.2423529411764713.806
274661LASCO STA;2U
50/50
28.07728.077
943122AE2-341 E
Adder
6.84941176470588255.822
939322AE1-163 E
Adder
39.8482352941176533.871
274863CAYUGA RI;1U
50/50
0.5280.528
274776LINCOLN ;7U
50/50
3.1623.162
936372AD2-047 E
50/50
25.40825.408
274654BRAIDWOOD;1U
50/50
30.61530.615
276591L-013 2
Adder
3.98705882352941153.389
962781AG1-127 C
Adder
7.6223529411764716.479
933911AD1-013 C
Adder
2.00588235294117641.705
274775LINCOLN ;6U
50/50
3.1623.162
274777LINCOLN ;8U
50/50
3.1623.162
936371AD2-047 C
50/50
5.2045.204
936461AD2-060 C
50/50
3.0613.061
933412AC2-154 E
50/50
4.7454.745
962782AG1-127 E
Adder
5.07294117647058854.312
946671AF1-331 C
Adder
2.60588235294117652.215
920272AA2-123 E
Adder
3.11647058823529432.649
276170Z1-108 E
Adder
3.17411764705882372.698
276675AE2-062 E
Adder
0.167058823529411760.142
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8980.898
TVALTFEXP_TVA->PJM
CLTF
1.4641.464
O66PJM->LTFIMP_O-066
CMTX_NF
15.10215.102
NYPJM->LTFIMP_NY
CLTF
1.2591.259
WECLTFEXP_WEC->PJM
CLTF
4.2274.227
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.6140.614
CBM West 1LTFEXP_CBM-W1->PJM
CBM
97.73297.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.79716.797
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6640.664
MECLTFEXP_MEC->PJM
CLTF
14.26314.263
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.9021.902
LAGNLTFEXP_LAGN->PJM
CLTF
3.8723.872
G-007PJM->LTFIMP_G-007
CMTX_NF
2.3542.354
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3230.323
SIGELTFEXP_SIGE->PJM
CLTF
0.0220.022

Details for WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_112-65-BT5-6___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.01 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1704.12
MW Contribution:14.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274800UNIV PARK;3U
50/50
1.2031.203
941551AE2-152 C
50/50
15.22915.229
274676JOLIET 29;8U
Adder
76.0835294117647264.671
274847GR RIDGE ;BU
50/50
0.6370.637
958481AF2-142 C
Adder
11.90941176470588110.123
957332AF2-027 E
Adder
3.94352941176470573.352
274891CAYUG;2U E
50/50
16.86716.867
274790SE CHICAG;7U
Adder
1.68941176470588241.436
966092AG1-478 E
50/50
0.5630.563
274682WAUKEGAN ;7U
Adder
43.47411764705882636.953
942651AE2-281 C
Adder
0.90235294117647060.767
942652AE2-281 E
Adder
5.5435294117647054.712
962691AG1-118 C
Adder
23.50941176470588419.983
962692AG1-118 E
Adder
15.67294117647058713.322
938851AE1-113 C
Adder
8.4129411764705877.151
272363ESS H440 ; R
Adder
2.7917647058823532.373
959091AF2-200 C
Adder
15.08941176470588312.826
940502AE2-035 E
Adder
3.58235294117647073.045
958012AF2-095 E
50/50
8.5938.593
274887PILOT HIL;1U
50/50
0.850.85
934111AD2-000 2
Adder
6.317647058823535.37
966442AG1-513 E
Adder
0.80941176470588230.688
274683WAUKEGAN ;8U
Adder
46.8729411764705939.842
290051GSG-6; E
Adder
11.102352941176479.437
959082AF2-199 E
Adder
3.77294117647058823.207
961501AF2-441 C
Adder
10.5505882352941188.968
293519PILOT HIL;1E
50/50
20.88720.887
939351AE1-166 C
50/50
13.19813.198
274675JOLIET 29;7U
Adder
76.0835294117647264.671
274674JOLIET 9 ;6U
Adder
38.7023529411764732.897
293061N-015 E
50/50
17.13617.136
943121AE2-341 C
Adder
13.58823529411764911.55
939321AE1-163 C
Adder
6.3164705882352945.369
295111SUBLETTE E
Adder
2.88941176470588262.456
274788SE CHICAG;5U
Adder
4.5223529411764713.844
274798UNIV PARK;1U
50/50
1.2121.212
958011AF2-095 C
50/50
12.8912.89
933411AC2-154 C
50/50
2.8352.835
274687WILL CNTY;4U
Adder
70.7847058823529460.167
966091AG1-478 C
50/50
2.242.24
966441AG1-513 C
Adder
0.540.459
959081AF2-199 C
Adder
7.5447058823529416.413
274888KELLY CRK;1U
50/50
0.850.85
274660LASCO STA;1U
50/50
27.28127.281
943592AF1-030 E
Adder
4.4705882352941183.8
943591AF1-030 C
Adder
9.0364705882352957.681
936292AD2-038 E
Adder
15.93411764705882513.544
290021O50 E
Adder
20.39647058823529617.337
937002AD2-134 E
Adder
10.7341176470588249.124
957371AF2-031 C
Adder
0.98823529411764710.84
274770LINCOLN ;1U
50/50
3.0623.062
274773LINCOLN ;4U
50/50
3.0623.062
274772LINCOLN ;3U
50/50
3.0623.062
274771LINCOLN ;2U
50/50
3.0623.062
960591AF2-350 C
50/50
8.9528.952
960592AF2-350 E
50/50
5.9685.968
275149KELLYCK ;1E
50/50
20.88720.887
934722AD1-100 E
50/50
118.444118.444
934721AD1-100 C
50/50
3.8843.884
960751AF2-366 C
Adder
7.4047058823529416.294
942422AE2-255 E
Adder
9.5611764705882368.127
960582AF2-349 E
Adder
38.2764705882352932.535
937312AD2-172 E
Adder
3.58235294117647073.045
274871GR RIDGE ;2U
50/50
0.2370.237
957331AF2-027 C
Adder
2.62941176470588232.235
936511AD2-066 C
Adder
8.977647058823537.631
936512AD2-066 E
Adder
5.9847058823529415.087
274864CAYUGA RI;2U
50/50
0.5150.515
295109WESTBROOK E
Adder
5.9435294117647065.052
941552AE2-152 E
50/50
10.15210.152
958482AF2-142 E
Adder
7.93999999999999956.749
938852AE1-113 E
Adder
29.82941176470588525.355
274890CAYUG;1U E
50/50
16.86716.867
957372AF2-031 E
Adder
1.48235294117647071.26
274774LINCOLN ;5U
50/50
3.0623.062
293644O22 E1
Adder
15.21999999999999912.937
960281AF2-319 C
Adder
2.64941176470588242.252
960752AF2-366 E
Adder
4.9364705882352944.196
957471AF2-041 C
Adder
22.63411764705882619.239
294763P-046 E
Adder
9.9564705882352938.463
293645O22 E2
Adder
17.43176470588235514.817
960282AF2-319 E
Adder
3.9741176470588243.378
918052AA1-018 E OP
Adder
17.26941176470588214.679
961502AF2-441 E
Adder
15.82588235294117713.452
274661LASCO STA;2U
50/50
27.3727.37
943122AE2-341 E
Adder
6.6729411764705885.672
939322AE1-163 E
Adder
38.803529411764732.983
274863CAYUGA RI;1U
50/50
0.5150.515
274776LINCOLN ;7U
50/50
3.0623.062
936372AD2-047 E
50/50
24.76624.766
274654BRAIDWOOD;1U
50/50
29.85229.852
276591L-013 2
Adder
3.8835294117647063.301
962781AG1-127 C
Adder
7.4258823529411776.312
933911AD1-013 C
Adder
1.95411764705882351.661
910542X3-005 E
Adder
0.76941176470588240.654
939352AE1-166 E
50/50
12.18312.183
294392P-010 E
50/50
21.76221.762
959352AF2-226 E
Adder
3.9741176470588243.378
934101AD2-000 1
Adder
6.1705882352941185.245
958492AF2-143 E
Adder
7.7352941176470596.575
942421AE2-255 C
Adder
3.18705882352941172.709
290108LEEDK;1U E
Adder
25.4658823529411821.646
916221Z1-073 E
Adder
7.82352941176470656.65
957472AF2-041 E
Adder
11.3176470588235289.62
959092AF2-200 E
Adder
10.068.551
274655BRAIDWOOD;2U
50/50
29.08529.085
959351AF2-226 C
Adder
2.64941176470588242.252
958491AF2-143 C
Adder
11.6023529411764729.862
933912AD1-013 E
Adder
3.12235294117647082.654
274775LINCOLN ;6U
50/50
3.0623.062
274777LINCOLN ;8U
50/50
3.0623.062
936371AD2-047 C
50/50
5.0735.073
936461AD2-060 C
50/50
2.9842.984
933412AC2-154 E
50/50
4.6254.625
962782AG1-127 E
Adder
4.94117647058823554.2
946671AF1-331 C
Adder
2.53882352941176452.158
276675AE2-062 E
Adder
0.162352941176470620.138
920272AA2-123 E
Adder
3.0352941176470592.58
276170Z1-108 E
Adder
3.0917647058823532.628
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8740.874
TVALTFEXP_TVA->PJM
CLTF
1.4271.427
O66PJM->LTFIMP_O-066
CMTX_NF
14.71114.711
NYPJM->LTFIMP_NY
CLTF
1.2271.227
WECLTFEXP_WEC->PJM
CLTF
4.1174.117
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.5980.598
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.2195.21
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.37116.371
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6470.647
MECLTFEXP_MEC->PJM
CLTF
13.89713.897
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.8521.852
LAGNLTFEXP_LAGN->PJM
CLTF
3.7743.774
G-007PJM->LTFIMP_G-007
CMTX_NF
2.2932.293
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3140.314
SIGELTFEXP_SIGE->PJM
CLTF
0.0210.021

Details for WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_112-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.03 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1748.52
MW Contribution:15.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274790SE CHICAG;7U
Adder
1.73411764705882351.474
274791SE CHICAG;8U
Adder
4.6423529411764713.946
966092AG1-478 E
50/50
0.5780.578
274682WAUKEGAN ;7U
Adder
44.62823529411764437.934
942651AE2-281 C
Adder
0.92705882352941180.788
942652AE2-281 E
Adder
5.6929411764705894.839
962691AG1-118 C
Adder
24.13176470588235420.512
962692AG1-118 E
Adder
16.0882352941176513.675
938851AE1-113 C
Adder
8.6364705882352947.341
272363ESS H440 ; R
Adder
2.8647058823529412.435
959091AF2-200 C
Adder
15.48823529411764713.165
940502AE2-035 E
Adder
3.67764705882352953.126
274800UNIV PARK;3U
50/50
1.2351.235
941551AE2-152 C
50/50
15.61115.611
274676JOLIET 29;8U
Adder
78.1152941176470566.398
274847GR RIDGE ;BU
50/50
0.6540.654
958481AF2-142 C
Adder
12.23176470588235410.397
957332AF2-027 E
Adder
4.0482352941176473.441
274891CAYUG;2U E
50/50
17.29517.295
274798UNIV PARK;1U
50/50
1.2441.244
958011AF2-095 C
50/50
13.22413.224
933411AC2-154 C
50/50
2.9082.908
274687WILL CNTY;4U
Adder
72.6647058823529561.765
966091AG1-478 C
50/50
2.2992.299
966441AG1-513 C
Adder
0.55411764705882350.471
959081AF2-199 C
Adder
7.74470588235294166.583
957371AF2-031 C
Adder
1.01411764705882360.862
274770LINCOLN ;1U
50/50
3.1623.162
274773LINCOLN ;4U
50/50
3.1623.162
274772LINCOLN ;3U
50/50
3.1623.162
274771LINCOLN ;2U
50/50
3.1623.162
960591AF2-350 C
50/50
9.1849.184
960592AF2-350 E
50/50
6.1226.122
275149KELLYCK ;1E
50/50
21.42821.428
934722AD1-100 E
50/50
121.416121.416
934721AD1-100 C
50/50
3.9823.982
960751AF2-366 C
Adder
7.6011764705882366.461
942422AE2-255 E
Adder
9.8141176470588248.342
960582AF2-349 E
Adder
39.29058823529411633.397
937312AD2-172 E
Adder
3.67764705882352953.126
961501AF2-441 C
Adder
10.8282352941176499.204
293519PILOT HIL;1E
50/50
21.42821.428
939351AE1-166 C
50/50
13.52913.529
274675JOLIET 29;7U
Adder
78.1152941176470566.398
274674JOLIET 9 ;6U
Adder
39.72588235294118433.767
293061N-015 E
50/50
17.5817.58
943121AE2-341 C
Adder
13.94823529411764811.856
939321AE1-163 C
Adder
6.4870588235294125.514
295111SUBLETTE E
Adder
2.96588235294117642.521
958012AF2-095 E
50/50
8.8168.816
274887PILOT HIL;1U
50/50
0.8720.872
934111AD2-000 2
Adder
6.4847058823529415.512
966442AG1-513 E
Adder
0.8317647058823530.707
274683WAUKEGAN ;8U
Adder
48.1176470588235340.9
290051GSG-6; E
Adder
11.395294117647069.686
959082AF2-199 E
Adder
3.87176470588235283.291
910542X3-005 E
Adder
0.79058823529411770.672
939352AE1-166 E
50/50
12.48912.489
294392P-010 E
50/50
22.32722.327
959352AF2-226 E
Adder
4.0788235294117653.467
934101AD2-000 1
Adder
6.3329411764705885.383
958492AF2-143 E
Adder
7.9435294117647066.752
942421AE2-255 C
Adder
3.2717647058823532.781
290108LEEDK;1U E
Adder
26.1422.219
916221Z1-073 E
Adder
8.0305882352941186.826
957472AF2-041 E
Adder
11.6164705882352959.874
959092AF2-200 E
Adder
10.3258823529411778.777
274655BRAIDWOOD;2U
50/50
29.82929.829
959351AF2-226 C
Adder
2.71882352941176462.311
958491AF2-143 C
Adder
11.91411764705882510.127
933912AD1-013 E
Adder
3.20470588235294152.724
274888KELLY CRK;1U
50/50
0.8720.872
274660LASCO STA;1U
50/50
27.98627.986
943592AF1-030 E
Adder
4.5894117647058823.901
943591AF1-030 C
Adder
9.2752941176470597.884
936292AD2-038 E
Adder
16.3623529411764713.908
290021O50 E
Adder
20.9376470588235317.797
937002AD2-134 E
Adder
11.0188235294117659.366
957372AF2-031 E
Adder
1.52117647058823541.293
274774LINCOLN ;5U
50/50
3.1623.162
293644O22 E1
Adder
15.62117647058823713.278
960281AF2-319 C
Adder
2.71882352941176462.311
960752AF2-366 E
Adder
5.0670588235294124.307
957471AF2-041 C
Adder
23.2329411764705919.748
294763P-046 E
Adder
10.2199999999999998.687
274871GR RIDGE ;2U
50/50
0.2430.243
957331AF2-027 C
Adder
2.69882352941176462.294
936511AD2-066 C
Adder
9.2141176470588247.832
936512AD2-066 E
Adder
6.1435294117647075.222
274864CAYUGA RI;2U
50/50
0.5280.528
295109WESTBROOK E
Adder
6.1011764705882365.186
941552AE2-152 E
50/50
10.40710.407
958482AF2-142 E
Adder
8.1541176470588246.931
938852AE1-113 E
Adder
30.62117647058823526.028
274890CAYUG;1U E
50/50
17.29517.295
293645O22 E2
Adder
17.89176470588235215.208
960282AF2-319 E
Adder
4.0788235294117653.467
918052AA1-018 E OP
Adder
17.73647058823529615.076
961502AF2-441 E
Adder
16.2423529411764713.806
274661LASCO STA;2U
50/50
28.07728.077
943122AE2-341 E
Adder
6.84941176470588255.822
939322AE1-163 E
Adder
39.8482352941176533.871
274863CAYUGA RI;1U
50/50
0.5280.528
274776LINCOLN ;7U
50/50
3.1623.162
936372AD2-047 E
50/50
25.40825.408
274654BRAIDWOOD;1U
50/50
30.61530.615
276591L-013 2
Adder
3.98705882352941153.389
962781AG1-127 C
Adder
7.6223529411764716.479
933911AD1-013 C
Adder
2.00588235294117641.705
274775LINCOLN ;6U
50/50
3.1623.162
274777LINCOLN ;8U
50/50
3.1623.162
936371AD2-047 C
50/50
5.2045.204
936461AD2-060 C
50/50
3.0613.061
933412AC2-154 E
50/50
4.7454.745
962782AG1-127 E
Adder
5.07294117647058854.312
946671AF1-331 C
Adder
2.60588235294117652.215
276170Z1-108 E
Adder
3.17411764705882372.698
920272AA2-123 E
Adder
3.11647058823529432.649
276675AE2-062 E
Adder
0.167058823529411760.142
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.8980.898
TVALTFEXP_TVA->PJM
CLTF
1.4641.464
O66PJM->LTFIMP_O-066
CMTX_NF
15.10215.102
NYPJM->LTFIMP_NY
CLTF
1.2591.259
WECLTFEXP_WEC->PJM
CLTF
4.2274.227
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.6140.614
CBM West 1LTFEXP_CBM-W1->PJM
CBM
97.73297.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.79716.797
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6640.664
MECLTFEXP_MEC->PJM
CLTF
14.26314.263
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.9021.902
LAGNLTFEXP_LAGN->PJM
CLTF
3.8723.872
G-007PJM->LTFIMP_G-007
CMTX_NF
2.3542.354
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3230.323
SIGELTFEXP_SIGE->PJM
CLTF
0.0220.022
CONTINGENCY 'AEP_P7-1_#11046___SRT-A'
 OPEN BRANCH FROM BUS 243219 TO BUS 246955 CKT 1   /*05DUMONT     345.0 - 05OLIVE_BP   345.0
 OPEN BRANCH FROM BUS 243228 TO BUS 243234 CKT 1   /*05MERIDN     345.0 - 05TWIN B     345.0
 OPEN BRANCH FROM BUS 243232 TO BUS 246955 CKT 1   /*05SORENS     345.0 - 05OLIVE_BP   345.0
END
CONTINGENCY '765-L11215__-S_SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
END
CONTINGENCY 'AEP_P1-2_#695_1681_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-025T_SRT-A-1'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 955780 CKT 1   /*02LEMOYN     345.0 - J1062 POI    345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 256583 CKT 1   /*19LULU       345.0 - 18MOROCCO    345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 264613 CKT 1   /*19LULU       345.0 - 19MON34      345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 264839 CKT 1   /*19LULU       345.0 - 19MILAN      345.0
END
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243207 CKT 1   /*05DUMONT     765.0 - 05GRNTWN     765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'COMED_P4_112-65-BT3-4___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT4-5___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT5-6___SRT-A'
 TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1   /*WILTON   ;   765.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT2-3___SRT-A'
 TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1   /*WILTON   ;   765.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
243206 to 246999 ckt 1
255113 to 243219 ckt 1
264612 to 241901 ckt 1
960680 to 243229 ckt 1
274750 to 255112 ckt 1
270728 to 274750 ckt 1
274804 to 960680 ckt 1
270926 to 275232 ckt 1
270927 to 275233 ckt 1
275232 to 270644 ckt 1
275233 to 270644 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1CE
AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line
765-L11216__-S_SRT-A
OPAC136.42 %1528.0B2084.515.81
GD1CE
AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line
Base Case
OPAC118.44 %1364.0A1615.5413.47

Details for AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o 765-L11216__-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line
Contingency Name:
765-L11216__-S_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:136.42 %
Rating:1528.0 MVA
Rating Type:B
MVA to Mitigate:2084.5
MW Contribution:15.81
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line
Contingency Name:
765-L11216__-S_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:138.03 %
Rating:1528.0 MVA
Rating Type:B
MVA to Mitigate:2109.1
MW Contribution:15.93
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.52705882352941181.298
962012AG1-044 E
Adder
0.0364705882352941160.031
962781AG1-127 C
Adder
4.0341176470588243.429
962782AG1-127 E
Adder
2.68470588235294152.282
965091AG1-374 C
50/50
23.9423.94
965092AG1-374 E
50/50
15.9615.96
965911AG1-460 C
Adder
0.90823529411764710.772
965912AG1-460 E
Adder
1.36235294117647051.158
966091AG1-478 C
50/50
1.5961.596
966092AG1-478 E
50/50
0.4020.402
966441AG1-513 C
Adder
0.28470588235294120.242
966442AG1-513 E
Adder
0.427058823529411770.363
290051GSG-6; E
Adder
6.07294117647058855.162
290261S-027 E
50/50
21.70521.705
290265S-028 E
50/50
21.57221.572
295109WESTBROOK E
Adder
3.25176470588235272.764
295111SUBLETTE E
Adder
1.58117647058823541.344
933911AD1-013 C
Adder
1.06941176470588250.909
933912AD1-013 E
Adder
1.7082352941176471.452
934721AD1-100 C
50/50
7.0137.013
934722AD1-100 E
50/50
213.036213.036
936771AD2-100 C
Adder
9.2247058823529417.841
936772AD2-100 E
Adder
6.1494117647058835.227
936971AD2-131 C
Adder
0.60823529411764710.517
936972AD2-131 E
Adder
3.05294117647058852.595
937002AD2-134 E
Adder
5.8717647058823524.991
937312AD2-172 E
Adder
1.8635294117647061.584
942111AE2-223 C
50/50
2.7622.762
942112AE2-223 E
50/50
18.48618.486
942481AE2-261 C
Adder
13.5729411764705911.537
942482AE2-261 E
Adder
9.0482352941176487.691
958912AF2-182 E
Adder
6.0364705882352955.131
959081AF2-199 C
Adder
4.00705882352941253.406
959082AF2-199 E
Adder
2.00352941176470621.703
959341AF2-225 C
50/50
8.9248.924
959342AF2-225 E
50/50
12.32412.324
959611AF2-252 C
50/50
2.662.66
959612AF2-252 E
50/50
3.993.99
960611AF2-352 C
50/50
2.662.66
960612AF2-352 E
50/50
3.993.99
960751AF2-366 C
Adder
4.0235294117647063.42
960752AF2-366 E
Adder
2.68235294117647042.28
274654BRAIDWOOD;1U
50/50
40.69940.699
274655BRAIDWOOD;2U
50/50
39.44139.441
274660LASCO STA;1U
50/50
30.56730.567
274661LASCO STA;2U
50/50
30.67130.671
274847GR RIDGE ;BU
50/50
0.6440.644
274853TWINGROVE;U1
50/50
0.7560.756
274854TWINGROVE;U2
50/50
0.7780.778
274859EASYR;U1 E
Adder
6.7258823529411765.717
274860EASYR;U2 E
Adder
6.7258823529411765.717
274863CAYUGA RI;1U
50/50
0.7780.778
274864CAYUGA RI;2U
50/50
0.7780.778
274871GR RIDGE ;2U
50/50
0.240.24
274887PILOT HIL;1U
50/50
0.9040.904
274888KELLY CRK;1U
50/50
0.9040.904
276173Z2-081
50/50
0.1940.194
276591L-013 2
Adder
2.00705882352941161.706
276615W2-048 GEN
Adder
4.7835294117647064.066
276621X2-022 GEN
Adder
16.37176470588235213.916
293061N-015 E
50/50
17.26517.265
293715O-029 E
Adder
5.8564705882352944.978
293716O-029 E
Adder
3.2117647058823532.73
293717O-029 E
Adder
2.9517647058823532.509
293771O-035 E
Adder
4.8764705882352944.145
294392P-010 E
50/50
21.92721.927
294401BSHIL;1U E
Adder
5.824.947
294410BSHIL;2U E
Adder
5.824.947
294763P-046 E
Adder
5.1811764705882364.404
917502Z2-087 E
50/50
24.64724.647
925582AC1-033 E
Adder
6.385.423
933411AC2-154 C
50/50
3.0043.004
933412AC2-154 E
50/50
4.9014.901
940502AE2-035 E
Adder
1.8635294117647061.584
957381AF2-032 C
Adder
1.04117647058823540.885
957382AF2-032 E
Adder
0.48941176470588230.416
957471AF2-041 C
Adder
12.02000000000000110.217
957472AF2-041 E
Adder
6.0094117647058825.108
274674JOLIET 9 ;6U
Adder
21.01647058823529717.864
274890CAYUG;1U E
50/50
25.40125.401
274891CAYUG;2U E
50/50
25.40125.401
925772AC1-053 E
Adder
16.27882352941176313.837
934101AD2-000 1
Adder
3.4423529411764712.926
270681BRIGHTSTK; R
50/50
0.6020.602
275149KELLYCK ;1E
50/50
22.13322.133
276174W4-005 E
Adder
25.75411764705882321.891
276655AB2-047 C1
50/50
0.3760.376
276656AB2-047 C2
50/50
0.3760.376
293516O-009 E
Adder
11.324705882352949.626
293519PILOT HIL;1E
50/50
22.13322.133
916212CRESCENT ;1U
Adder
3.42588235294117642.912
924048AB2-047 E1
50/50
15.28415.284
924049AB2-047 E2
50/50
15.52515.525
927208AC1-214 E1
Adder
2.3117647058823531.965
927209AC1-214 E2
Adder
2.3117647058823531.965
990901L-005 E
Adder
8.6541176470588247.356
290108LEEDK;1U E
Adder
13.96705882352941211.872
916221Z1-073 E
Adder
4.283.638
924266AB2-070 E
Adder
15.10823529411764812.842
926821AC1-168 C
Adder
0.91529411764705890.778
926822AC1-168 E
Adder
6.1435294117647075.222
936371AD2-047 C
50/50
5.3765.376
936372AD2-047 E
50/50
26.24526.245
936461AD2-060 C
50/50
3.1623.162
936511AD2-066 C
Adder
5.4588235294117654.64
936512AD2-066 E
Adder
3.63882352941176463.093
943121AE2-341 C
Adder
7.9658823529411766.771
943122AE2-341 E
Adder
3.91176470588235333.325
943591AF1-030 C
Adder
5.297647058823534.503
943592AF1-030 E
Adder
2.62117647058823572.228
959091AF2-200 C
Adder
8.0129411764705896.811
959092AF2-200 E
Adder
5.3423529411764714.541
960141AF2-305_AG1-
Adder
0.88235294117647060.75
960591AF2-350 C
50/50
9.4869.486
960592AF2-350 E
50/50
6.3246.324
938861AE1-114 C
Adder
2.21.87
938862AE1-114 E
Adder
7.50470588235294046.379
939351AE1-166 C
50/50
23.73823.738
939352AE1-166 E
50/50
21.91221.912
939741AE1-205 C
50/50
11.89911.899
939742AE1-205 E
50/50
16.43216.432
946671AF1-331 C
Adder
1.3882352941176471.18
962691AG1-118 C
Adder
12.77176470588235310.856
962692AG1-118 E
Adder
8.515294117647067.238
941551AE2-152 C
50/50
27.3927.39
941552AE2-152 E
50/50
18.2618.26
944221AF1-090 C
Adder
2.32588235294117671.977
944222AF1-090 E
Adder
10.8870588235294119.254
958011AF2-095 C
50/50
13.65913.659
958012AF2-095 E
50/50
9.1069.106
920272AA2-123 E
Adder
1.5152941176470591.288
276170Z1-108 E
Adder
1.51058823529411781.284
276626AG1-044 E
Adder
0.043529411764705880.037
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.09146.091
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.15914.159
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3311.331
NYPJM->LTFIMP_NY
CLTF
0.7180.718
WECLTFEXP_WEC->PJM
CLTF
1.9381.938
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2610.261
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1240.124
TVALTFEXP_TVA->PJM
CLTF
1.4341.434
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.2330.233
MECLTFEXP_MEC->PJM
CLTF
8.128.12
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.6030.603
LAGNLTFEXP_LAGN->PJM
CLTF
2.9712.971
SIGELTFEXP_SIGE->PJM
CLTF
0.0690.069
O66PJM->LTFIMP_O-066
CMTX_NF
8.5428.542
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.4090.409

Details for AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:118.44 %
Rating:1364.0 MVA
Rating Type:A
MVA to Mitigate:1615.54
MW Contribution:13.47
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:119.45 %
Rating:1364.0 MVA
Rating Type:A
MVA to Mitigate:1629.34
MW Contribution:13.56
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
965091AG1-374 C
50/50
19.95319.953
965092AG1-374 E
50/50
13.30213.302
965911AG1-460 C
Adder
0.71058823529411760.604
965912AG1-460 E
Adder
1.06470588235294120.905
966091AG1-478 C
Adder
1.12235294117647060.954
966092AG1-478 E
Adder
0.28235294117647060.24
290261S-027 E
50/50
18.09118.091
290265S-028 E
50/50
17.9817.98
934721AD1-100 C
50/50
6.5466.546
934722AD1-100 E
50/50
198.856198.856
936771AD2-100 C
Adder
7.2094117647058836.128
936772AD2-100 E
Adder
4.8070588235294124.086
936971AD2-131 C
Adder
0.475294117647058870.404
936972AD2-131 E
Adder
2.38588235294117632.028
942111AE2-223 C
50/50
2.312.31
942112AE2-223 E
50/50
15.45815.458
942481AE2-261 C
Adder
10.6152941176470599.023
942482AE2-261 E
Adder
7.0764705882352946.015
959341AF2-225 C
50/50
7.4627.462
959342AF2-225 E
50/50
10.30510.305
959611AF2-252 C
50/50
2.2172.217
959612AF2-252 E
50/50
3.3253.325
960611AF2-352 C
50/50
2.2172.217
960612AF2-352 E
50/50
3.3253.325
274654BRAIDWOOD;1U
50/50
35.7235.72
274655BRAIDWOOD;2U
50/50
34.57234.572
274660LASCO STA;1U
50/50
23.3723.37
274661LASCO STA;2U
50/50
23.4523.45
274847GR RIDGE ;BU
50/50
0.4750.475
274853TWINGROVE;U1
50/50
0.630.63
274854TWINGROVE;U2
50/50
0.6480.648
274863CAYUGA RI;1U
50/50
0.6930.693
274864CAYUGA RI;2U
50/50
0.6930.693
274871GR RIDGE ;2U
50/50
0.1770.177
274887PILOT HIL;1U
50/50
0.7710.771
274888KELLY CRK;1U
50/50
0.7710.771
276615W2-048 GEN
Adder
3.81058823529411763.239
276621X2-022 GEN
Adder
13.04117647058823711.085
293061N-015 E
50/50
12.72212.722
294392P-010 E
50/50
16.15716.157
917502Z2-087 E
50/50
20.6120.61
933411AC2-154 C
50/50
2.562.56
933412AC2-154 E
50/50
4.1774.177
957381AF2-032 C
Adder
0.81411764705882350.692
957382AF2-032 E
Adder
0.38352941176470590.326
274890CAYUG;1U E
50/50
22.61422.614
274891CAYUG;2U E
50/50
22.61422.614
925772AC1-053 E
Adder
13.06941176470588311.109
270681BRIGHTSTK; R
50/50
0.5030.503
275149KELLYCK ;1E
50/50
18.86218.862
276174W4-005 E
Adder
20.91647058823529517.779
276655AB2-047 C1
50/50
0.3150.315
276656AB2-047 C2
50/50
0.3150.315
293519PILOT HIL;1E
50/50
18.86218.862
924048AB2-047 E1
50/50
12.78112.781
924049AB2-047 E2
50/50
12.98212.982
924266AB2-070 E
Adder
12.17058823529411910.345
926821AC1-168 C
Adder
0.59529411764705890.506
926822AC1-168 E
Adder
3.99529411764705873.396
936371AD2-047 C
50/50
4.5814.581
936372AD2-047 E
50/50
22.36722.367
936461AD2-060 C
50/50
2.6952.695
960141AF2-305_AG1-
Adder
0.71058823529411760.604
960591AF2-350 C
50/50
8.0848.084
960592AF2-350 E
50/50
5.3895.389
939351AE1-166 C
50/50
22.15822.158
939352AE1-166 E
50/50
20.45420.454
939741AE1-205 C
50/50
9.959.95
939742AE1-205 E
50/50
13.7413.74
941551AE2-152 C
50/50
25.56725.567
941552AE2-152 E
50/50
17.04517.045
944221AF1-090 C
Adder
1.81294117647058831.541
944222AF1-090 E
Adder
8.4882352941176477.215
958011AF2-095 C
50/50
11.6411.64
958012AF2-095 E
50/50
7.767.76
956282J1115 C
External Queue
1.80338597297668461.8033859729766846
956283J1115 E
External Queue
9.7567806243896489.756780624389648
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.23219.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.09110.091
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7730.773
NYPJM->LTFIMP_NY
CLTF
0.4180.418
WECLTFEXP_WEC->PJM
CLTF
0.7530.753
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1160.116
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0480.048
TVALTFEXP_TVA->PJM
CLTF
1.0661.066
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0640.064
MECLTFEXP_MEC->PJM
CLTF
4.254.25
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.1150.115
LAGNLTFEXP_LAGN->PJM
CLTF
1.9731.973
SIGELTFEXP_SIGE->PJM
CLTF
0.0670.067
O66PJM->LTFIMP_O-066
CMTX_NF
4.964.96
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.1960.196
CONTINGENCY '765-L11216__-S_SRT-A'
 TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1   /*WILTON   ;   765.0 - COLLINS  ;   765.0
END
934720 to 270926 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Base Case
OPAC112.52 %1075.0A1209.6110.0
GD1CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Base Case
OPAC114.84 %1091.0A1252.957.73

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.52 %
Rating:1075.0 MVA
Rating Type:A
MVA to Mitigate:1209.61
MW Contribution:10.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.69647058823529421.442
962012AG1-044 E
Adder
0.04117647058823530.035
962781AG1-127 C
Adder
4.4894117647058823.816
962782AG1-127 E
Adder
2.9882352941176472.54
966091AG1-478 C
Adder
1.46941176470588241.249
966092AG1-478 E
Adder
0.36941176470588240.314
966441AG1-513 C
Adder
0.32705882352941180.278
966442AG1-513 E
Adder
0.48941176470588230.416
290021O50 E
Adder
13.1552941176470611.182
290051GSG-6; E
Adder
6.7482352941176475.736
295109WESTBROOK E
Adder
3.61294117647058853.071
295111SUBLETTE E
Adder
1.75647058823529421.493
910542X3-005 E
Adder
0.71294117647058820.606
918052AA1-018 E OP
Adder
11.3482352941176489.646
933911AD1-013 C
Adder
1.18705882352941171.009
933912AD1-013 E
Adder
1.89647058823529441.612
934722AD1-100 E
Adder
60.7764705882352951.66
937002AD2-134 E
Adder
6.5247058823529425.546
937312AD2-172 E
Adder
2.20823529411764731.877
958481AF2-142 C
Adder
7.8258823529411776.652
958482AF2-142 E
Adder
5.21764705882352954.435
958491AF2-143 C
Adder
7.5847058823529416.447
958492AF2-143 E
Adder
5.0564705882352944.298
958912AF2-182 E
Adder
22.26470588235294218.925
959081AF2-199 C
Adder
4.6141176470588243.922
959082AF2-199 E
Adder
2.3070588235294121.961
959351AF2-226 C
Adder
1.80588235294117651.535
959352AF2-226 E
Adder
2.70941176470588242.303
960281AF2-319 C
Adder
1.80588235294117651.535
960282AF2-319 E
Adder
2.70941176470588242.303
960582AF2-349 E
Adder
23.60470588235294220.064
960751AF2-366 C
Adder
4.4776470588235293.806
960752AF2-366 E
Adder
2.98470588235294132.537
274675JOLIET 29;7U
Adder
49.9447058823529542.453
274676JOLIET 29;8U
Adder
49.9529411764705942.46
274682WAUKEGAN ;7U
Adder
27.29294117647059223.199
274683WAUKEGAN ;8U
Adder
29.42352941176470825.01
274687WILL CNTY;4U
Adder
48.5929411764705941.304
274724RIVER EC ;11
50/50
3.9023.902
274788SE CHICAG;5U
50/50
5.5385.538
274789SE CHICAG;6U
50/50
5.5385.538
274790SE CHICAG;7U
50/50
5.5385.538
274791SE CHICAG;8U
50/50
5.5385.538
274792SE CHICAG;9U
50/50
5.4655.465
274793SE CHICAG;0U
Adder
5.464705882352944.645
274794SE CHICAG;1U
50/50
5.4655.465
274795SE CHICAG;2U
Adder
5.464705882352944.645
274859EASYR;U1 E
Adder
7.82352941176470656.65
274860EASYR;U2 E
Adder
7.82352941176470656.65
276591L-013 2
Adder
2.36235294117647052.008
293061N-015 E
Adder
9.8294117647058838.355
293644O22 E1
Adder
10.3776470588235298.821
293645O22 E2
Adder
11.88588235294117710.103
293715O-029 E
Adder
6.3811764705882365.424
293716O-029 E
Adder
3.4988235294117652.974
293717O-029 E
Adder
3.2152941176470592.733
293771O-035 E
Adder
4.5764705882352953.89
294392P-010 E
Adder
12.48352941176470710.611
294763P-046 E
Adder
6.13764705882352955.217
925582AC1-033 E
Adder
2.2152941176470591.883
933411AC2-154 C
Adder
1.90000000000000011.615
933412AC2-154 E
Adder
3.09999999999999962.635
939061AE1-134 2
Adder
0.89294117647058820.759
940502AE2-035 E
Adder
2.20823529411764731.877
957331AF2-027 C
Adder
1.64941176470588241.402
957332AF2-027 E
Adder
2.4741176470588242.103
957471AF2-041 C
Adder
13.84352941176470611.767
957472AF2-041 E
Adder
6.9211764705882355.883
274674JOLIET 9 ;6U
Adder
25.73058823529411821.871
274890CAYUG;1U E
Adder
9.1035294117647067.738
274891CAYUG;2U E
Adder
9.1035294117647067.738
938851AE1-113 C
Adder
5.4270588235294124.613
938852AE1-113 E
Adder
19.2416.354
934101AD2-000 1
Adder
3.68941176470588243.136
934111AD2-000 2
Adder
4.077647058823533.466
275149KELLYCK ;1E
Adder
14.00117647058823611.901
293516O-009 E
Adder
12.33882352941176410.488
293519PILOT HIL;1E
Adder
14.00117647058823611.901
916212CRESCENT ;1U
Adder
3.2152941176470592.733
927208AC1-214 E1
Adder
2.16941176470588241.844
927209AC1-214 E2
Adder
2.16941176470588241.844
290108LEEDK;1U E
Adder
15.41176470588235313.1
916221Z1-073 E
Adder
4.75529411764705844.042
926821AC1-168 C
Adder
0.75294117647058820.64
926822AC1-168 E
Adder
5.0564705882352944.298
936292AD2-038 E
Adder
10.4164705882352948.854
936371AD2-047 C
Adder
3.40000000000000042.89
936372AD2-047 E
Adder
16.614.11
936461AD2-060 C
Adder
2.01.7
936511AD2-066 C
Adder
5.6788235294117654.827
936512AD2-066 E
Adder
3.78588235294117673.218
942421AE2-255 C
Adder
2.0552941176470591.747
942422AE2-255 E
Adder
6.1670588235294125.242
942651AE2-281 C
Adder
0.58941176470588240.501
942652AE2-281 E
Adder
3.6235294117647063.08
943121AE2-341 C
Adder
7.99529411764705966.796
943122AE2-341 E
Adder
3.9258823529411773.337
943591AF1-030 C
Adder
5.3176470588235294.52
943592AF1-030 E
Adder
2.6305882352941182.236
959091AF2-200 C
Adder
9.2294117647058827.845
959092AF2-200 E
Adder
6.1529411764705895.23
960591AF2-350 C
Adder
6.05.1
960592AF2-350 E
Adder
4.03.4
961501AF2-441 C
Adder
10.915294117647069.278
961502AF2-441 E
Adder
16.37411764705882413.918
938861AE1-114 C
Adder
2.562.176
938862AE1-114 E
Adder
8.7329411764705887.423
939321AE1-163 C
Adder
4.1294117647058823.51
939322AE1-163 E
Adder
25.36588235294117821.561
939351AE1-166 C
Adder
6.7717647058823545.756
939352AE1-166 E
Adder
6.2517647058823535.314
946152AF1-280 E
Adder
14.84352941176470812.617
946671AF1-331 C
Adder
1.54235294117647051.311
962691AG1-118 C
Adder
14.20823529411764812.077
962692AG1-118 E
Adder
9.4717647058823548.051
941551AE2-152 C
Adder
7.8141176470588246.642
941552AE2-152 E
Adder
5.2094117647058834.428
957371AF2-031 C
50/50
1.1831.183
957372AF2-031 E
50/50
1.7751.775
958011AF2-095 C
Adder
8.6411764705882357.345
958012AF2-095 E
Adder
5.764.896
920272AA2-123 E
Adder
1.87058823529411791.59
276170Z1-108 E
Adder
1.9070588235294121.621
276626AG1-044 E
Adder
0.0482352941176470640.041
276675AE2-062 E
Adder
0.107058823529411760.091
CBM West 1LTFEXP_CBM-W1->PJM
CBM
75.73675.736
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.85611.856
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3871.387
NYPJM->LTFIMP_NY
CLTF
0.7460.746
WECLTFEXP_WEC->PJM
CLTF
2.5782.578
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.2990.299
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1480.148
TVALTFEXP_TVA->PJM
CLTF
1.1741.174
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.2290.229
MECLTFEXP_MEC->PJM
CLTF
8.7698.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.6110.611
LAGNLTFEXP_LAGN->PJM
CLTF
2.6762.676
SIGELTFEXP_SIGE->PJM
CLTF
0.0530.053
O66PJM->LTFIMP_O-066
CMTX_NF
8.8988.898
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.4540.454

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:114.84 %
Rating:1091.0 MVA
Rating Type:A
MVA to Mitigate:1252.95
MW Contribution:7.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
1.76941176470588251.504
962012AG1-044 E
Adder
0.0423529411764705860.036
962781AG1-127 C
Adder
4.6976470588235293.993
962782AG1-127 E
Adder
3.12588235294117662.657
966091AG1-478 C
Adder
1.3482352941176471.146
966092AG1-478 E
Adder
0.33882352941176470.288
966441AG1-513 C
Adder
0.34235294117647060.291
966442AG1-513 E
Adder
0.51294117647058820.436
290021O50 E
Adder
13.8752941176470611.794
290051GSG-6; E
Adder
7.045.984
295109WESTBROOK E
Adder
3.76941176470588253.204
295111SUBLETTE E
Adder
1.8317647058823531.557
918052AA1-018 E OP
Adder
10.6611764705882349.062
933911AD1-013 C
Adder
1.23882352941176471.053
933912AD1-013 E
Adder
1.97882352941176461.682
934722AD1-100 E
Adder
60.5729411764705951.487
937002AD2-134 E
Adder
6.8070588235294115.786
937312AD2-172 E
Adder
2.30000000000000031.955
958481AF2-142 C
Adder
7.3529411764705896.25
958482AF2-142 E
Adder
4.90117647058823554.166
958491AF2-143 C
Adder
7.3411764705882366.24
958492AF2-143 E
Adder
4.8941176470588244.16
958912AF2-182 E
Adder
23.1219.652
959081AF2-199 C
Adder
4.8305882352941174.106
959082AF2-199 E
Adder
2.41529411764705862.053
959351AF2-226 C
50/50
2.1682.168
959352AF2-226 E
50/50
3.2523.252
960281AF2-319 C
50/50
2.1682.168
960282AF2-319 E
50/50
3.2523.252
960582AF2-349 E
Adder
24.68117647058823420.979
960751AF2-366 C
Adder
4.6847058823529423.982
960752AF2-366 E
Adder
3.12235294117647082.654
274654BRAIDWOOD;1U
50/50
19.28319.283
274675JOLIET 29;7U
Adder
52.87529411764706644.944
274676JOLIET 29;8U
Adder
52.9223529411764844.984
274682WAUKEGAN ;7U
Adder
28.6329411764705924.338
274683WAUKEGAN ;8U
Adder
30.8552941176470626.227
274687WILL CNTY;4U
Adder
50.79647058823529443.177
274752CRETE EC ;2U
50/50
5.7635.763
274753CRETE EC ;3U
50/50
5.7635.763
274754CRETE EC ;4U
50/50
5.7635.763
274859EASYR;U1 E
Adder
8.1305882352941186.911
274860EASYR;U2 E
Adder
8.1305882352941186.911
274861TOP CROP ;1U
50/50
0.3250.325
274862TOP CROP ;2U
50/50
0.620.62
276591L-013 2
Adder
2.4788235294117652.107
293061N-015 E
Adder
10.669.061
293644O22 E1
50/50
12.45512.455
293645O22 E2
50/50
14.26614.266
293715O-029 E
Adder
6.58705882352941255.599
293716O-029 E
Adder
3.6117647058823533.07
293717O-029 E
Adder
3.32000000000000032.822
293771O-035 E
Adder
4.6694117647058823.969
294392P-010 E
Adder
13.53764705882352911.507
294401BSHIL;1U E
Adder
5.8247058823529414.951
294410BSHIL;2U E
Adder
1.40235294117647061.192
294763P-046 E
Adder
6.3917647058823535.433
925582AC1-033 E
Adder
6.3858823529411765.428
933411AC2-154 C
Adder
1.4682352941176471.248
933412AC2-154 E
Adder
2.3952941176470592.036
939061AE1-134 2
Adder
0.92588235294117650.787
940502AE2-035 E
Adder
2.30000000000000031.955
957331AF2-027 C
Adder
1.7282352941176471.469
957332AF2-027 E
Adder
2.5917647058823532.203
957471AF2-041 C
Adder
14.49058823529411912.317
957472AF2-041 E
Adder
7.24470588235294166.158
274674JOLIET 9 ;6U
Adder
23.3929411764705919.884
274890CAYUG;1U E
Adder
8.9564705882352957.613
274891CAYUG;2U E
Adder
8.9564705882352957.613
938851AE1-113 C
Adder
5.7235294117647064.865
938852AE1-113 E
Adder
20.2929411764705917.249
934101AD2-000 1
Adder
3.8435294117647063.267
934111AD2-000 2
Adder
4.3529411764705893.7
275149KELLYCK ;1E
Adder
10.8188235294117649.196
293516O-009 E
Adder
12.7376470588235310.827
293519PILOT HIL;1E
Adder
10.8188235294117649.196
916212CRESCENT ;1U
Adder
3.282.788
927208AC1-214 E1
Adder
2.21411764705882331.882
927209AC1-214 E2
Adder
2.21411764705882331.882
290108LEEDK;1U E
Adder
16.10823529411764813.692
916221Z1-073 E
Adder
4.9611764705882354.217
926821AC1-168 C
Adder
0.77647058823529410.66
926822AC1-168 E
Adder
5.2117647058823534.43
936292AD2-038 E
Adder
10.0823529411764728.57
936371AD2-047 C
Adder
2.6270588235294122.233
936372AD2-047 E
Adder
12.82823529411764710.904
936461AD2-060 C
Adder
1.54588235294117651.314
936511AD2-066 C
Adder
5.7423529411764714.881
936512AD2-066 E
Adder
3.8282352941176473.254
942421AE2-255 C
Adder
2.16823529411764731.843
942422AE2-255 E
Adder
6.5047058823529415.529
942651AE2-281 C
Adder
0.57058823529411760.485
942652AE2-281 E
Adder
3.50705882352941162.981
943121AE2-341 C
Adder
8.397647058823537.138
943122AE2-341 E
Adder
4.1235294117647053.505
943591AF1-030 C
Adder
5.5847058823529414.747
943592AF1-030 E
Adder
2.7635294117647062.349
959091AF2-200 C
Adder
9.668.211
959092AF2-200 E
Adder
6.445.474
960591AF2-350 C
Adder
4.6364705882352943.941
960592AF2-350 E
Adder
3.09058823529411742.627
938861AE1-114 C
Adder
2.66117647058823532.262
938862AE1-114 E
Adder
9.087.718
939321AE1-163 C
Adder
3.99647058823529383.397
939322AE1-163 E
Adder
24.55176470588235220.869
939351AE1-166 C
Adder
6.7494117647058835.737
939352AE1-166 E
Adder
6.2305882352941185.296
946152AF1-280 E
Adder
15.4129411764705913.101
946671AF1-331 C
Adder
1.60941176470588251.368
962691AG1-118 C
Adder
14.86823529411764812.638
962692AG1-118 E
Adder
9.912941176470598.426
941551AE2-152 C
Adder
7.7882352941176486.62
941552AE2-152 E
Adder
5.19176470588235354.413
958011AF2-095 C
Adder
6.6764705882352945.675
958012AF2-095 E
Adder
4.4505882352941173.783
274751CRETE EC ;1U
50/50
5.7635.763
920272AA2-123 E
Adder
1.95882352941176491.665
276170Z1-108 E
Adder
2.00117647058823561.701
276626AG1-044 E
Adder
0.0494117647058823560.042
276675AE2-062 E
Adder
0.103529411764705880.088
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.81249.812
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.3588.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.4391.439
NYPJM->LTFIMP_NY
CLTF
0.7740.774
WECLTFEXP_WEC->PJM
CLTF
2.6882.688
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.3940.394
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2110.211
TVALTFEXP_TVA->PJM
CLTF
0.660.66
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5040.504
MECLTFEXP_MEC->PJM
CLTF
8.7288.728
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.491.49
LAGNLTFEXP_LAGN->PJM
CLTF
2.092.09
O66PJM->LTFIMP_O-066
CMTX_NF
9.239.23
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.5680.568
255113 to 243219 ckt 1
274750 to 255112 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AF2-350 was evaluated as a 100.0 MW injection in the ComEd area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 1, Cluster 3 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 3 projects.

This analysis is effectively a screening study to determine whether the addition of the Cluster 3 projects will meet the dynamics requirements of the NERC, ComEd and PJM reliability standards.

The load flow scenario for the analysis was based on the RTEP 2027 summer peak load case, modified to include applicable projects. Cluster 3 projects have been dispatched online at maximum power output and the voltage schedule set to achieve near unity power factor at the high side of the main transformer.

Cluster 3 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 166 contingencies were studied, each with a 20 second simulation time period. Studied faults included:

  1. Steady-state operation (20 second run);
  2. Three-phase faults with normal clearing time;
  3. Three-phase bus faults with normal clearing time;
  4. Three-phase to ground faults with three-phase delayed clearing due to a stuck breaker (GO breakers);
  5. Three-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure;
  6. Three-phase faults with loss of multiple-circuit tower line.

No relevant high speed reclosing (HSR) contingencies were identified for this study.

For all simulations, the Cluster 3 projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

For all of the fault contingencies tested on the 2027 peak load case:

  1. Cluster 3 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  2. The system with Cluster 3 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3%.
  3. Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).
  4. No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

AF2-350 meets the 0.95 leading and lagging PF requirement.

The IPCMD and IQCMD states in the REGCA1 model of AF2-350 GEN showed erratic behavior for some contingencies in which these generators have been disconnected as part of the contingency event. Since the machine is disconnected and no active or reactive power is injected into the system these plots are ignored.

 

No mitigations were found to be required.

Table 1: TC1 Cluster 3 Projects

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

3

AF2-350

Solar

ComEd

100

100

60

Kensington 138 kV

 

Reactive Power Analysis

The reactive power capability of AF2-350 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA2-116Cook-East Elkhart 345kVIn Service
AA2-123Marengo 34kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-080Dumont-Olive 345kVIn Service
AB1-087Sullivan 345kV #1Under Construction
AB1-088Sullivan 345kV #2Engineering & Procurement
AC1-033Kewanee 138 kVIn Service
AC1-168Kewanee-StreatorSuspended
AC1-214Crescent RidgeIn Service
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD2-020Valley 138 kVEngineering & Procurement
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-079Capitol Ave 34.5kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-172Lena 138kVIn Service
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-134Nelson 345 kVIn Service
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-205McLean 345 kVEngineering & Procurement
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-062Romeoville 12 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-181Snyder 69kVIn Service
AE2-223McLean 345 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVUnder Construction
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-276Sullivan 345kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVPartially in Service - Under Construction
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-064Weston 69 kVUnder Construction
AF1-084Hartford-Almena 69 kVUnder Construction
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVEngineering & Procurement
AF1-176Corey 138 kVEngineering & Procurement
AF1-204Eugene 345 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-229Galion-South Berwick 345 kVUnder Construction
AF1-280Nelson-Lee CountyEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-027Zion Energy Center 345 kVEngineering & Procurement
AF2-031CalumetEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-182Nelson-Lee County 345 kV IIEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-226Katydid Road 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-319Katydid Road 345 kVEngineering & Procurement
AF2-349SILVER LAKE- CHERRY VALLEY 345 KVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-366Crego Rd 138 kVEngineering & Procurement
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-396Stinger 138 kVEngineering & Procurement
AF2-441Burnham 138kVEngineering & Procurement
AG1-044Whiteside CountyIn Service
AG1-109Valley 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-513Aurora 138 kVSuspended
AG1-555Dequine 345 kVEngineering & Procurement
X1-042WatervlietIn Service
X3-005Wildwood 12kVIn Service
Y1-054Rochelle 138kVIn Service
Z1-073Mendota HillsIn Service
Z1-108McHenry 34kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)Identified Impacts
AF2-350 System Reinforcements:
TOTrans Owner IDTitleCategoryAllocated Cost ($USD)
ITCTITCT_TC1_13866MTEP #25223/#25224 - Lulu Sub. Construct the Lulu switching station. Cut in the Lemoyne-Maple and Milan-Monroe-Morocco lines into the new station (Projected ISD 6/11/2027)Informational$0
Grand Total:$0

System Reinforcement
Type
Load Flow
TO
ITCT
RTEP ID / TO ID
(Pending) / ITCT_TC1_13866
Title
MTEP #25223/#25224 - Lulu Sub. Construct the Lulu switching station. Cut in the Lemoyne-Maple and Milan-Monroe-Morocco lines into the new station (Projected ISD 6/11/2027)
Description
Construct the Lulu switching station. Cut in the Lemoyne-Maple and Milan-Monroe-Morocco lines into the new station. This project is a DPP 2020 Network Upgrade associated with the J1516, J1525, J1526, J1527, J1550, J1553, J1557, J1571, J1586, J1587, J1603, J1614, J1635, J1658, J1659, J1663, and J1664 projects. Projected In-Service 6/1/2027
Total Cost ($USD)
$29,916,928
Allocated Cost ($USD)
$0
Time Estimate
TBD

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AF2-350 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-350 could receive cost allocation. Although AF2-350 may not presently have cost responsibility for this upgrade, AF2-350 is a potential Aggregate Pool Contributor.

FacilityContingency
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In coordination with other Affected System Operators, PJM has determined that the Affected System Operator for this project that requires an Affected System Study. For the latest Affected System Study results pertaining this project, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM lists any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO) Identified Impacts
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AF2-350 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
ComEdb3775.1Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV lineContingent$0N/A
AEPb3775.10Perform sag study mitigation work on Olive – University ParkContingent$0N/A
ComEdn5145Reconfigure Wilton 765kV busContingent$0N/A
Grand Total:$0

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: s3442.26
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s3442.26
Title
Dumont 765 kV: Replace 3000 A circuit breaker at Dumont
Description
Dumont 765 kV: Replace 3000 A circuit breaker at Dumont to address a generation deliverability violation on the Dumont – Sorenson 765 kV branch related to the new customer interconnections in the area. Projected in service date 3/5/2027
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AF2-350 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AF2-350 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05DUMONT-05SORENS 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4558.0 MVA
(All)B5001.0 MVA

System Reinforcement: b3775.6
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.6
Title
Perform sag study mitigation work on the Dumont-Stillwell 345 kV line
Description
Perform sag study mitigation work on the Dumont-Stillwell 345 kV line (remove a center-pivot irrigation system from under the line, allowing for the normal and emergency ratings of the line to increase, replace two structures and modify a third structure).
Cost Information
Time Estimate
Nov 20 2026

Not Contingent

Note: AF2-350 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-350 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1409.0 MVA
(All)B1718.0 MVA

System Reinforcement: b3775.11
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.11 / b3775.7a
Title
Upgrade the wavetrap at Dumont substation to increase the rating of the Stillwell-Dumont 345 kV line to match conductor rating.
Description
Upgrade the wavetrap at Dumont substation to increase the rating of the Stillwell-Dumont 345 kV line to match conductor rating.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AF2-350 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-350 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1409.0 MVA
(All)B1737.0 MVA

System Reinforcement: b3775.7
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.7 / b3775.7b
Title
Upgrade breakers at Dumont substation on the Stillwell-Dumont 345 kV line.
Description
Upgrade the limiting element at Dumont substation to increase the rating of the Stillwell-Dumont 345 kV line to match conductor rating. This includes replacement of breakers F and F1.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AF2-350 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-350 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1408.0 MVA
(All)B1887.0 MVA

System Reinforcement: n3985
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n3985 / AEPO0036a
Title
Upgrade three Marysville Wavetraps ( 3000A)
Description
Replace 3 Marysville 765 kV wave traps. Costs updated to $705,368 from Facility Study
Total Cost ($USD)
$900,000
Discounted Total Cost ($USD)
$900,000
Allocated Cost ($USD)
$0
Time Estimate
Jul 16 2026

Not Contingent

Note: AF2-350 contributes to the loading of an overloaded facility that is being mitigated by a network upgrade that was securitized by a prior Queue/Cycle. AF2-350 is not contingent on this network upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARYSV-05SORENS 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5075.0 MVA
(All)B5075.0 MVA

System Reinforcement: b3775.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.1
Title
Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line
Description
Outside of the Green Acres substation, swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line to the University Park N-Olive 345 kV line to create a University Park N-Green Acres-Olive and St. John-Olive 345 kV lines.
Cost Information
Time Estimate
Mar 30 2027

Contingent

Note: Although AF2-350 may not presently have cost responsibility for this upgrade, AF2-350 may need this upgrade in-service to be deliverable to the PJM system. If AF2-350 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)ALDR9999.0 MVA
(All)STE9999.0 MVA
05OLIVE-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A9999.0 MVA
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A9999.0 MVA

System Reinforcement: b3775.10
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.10
Title
Perform sag study mitigation work on Olive – University Park
Description
Perform a sag study on the Olive – University Park 345kV line to increase the operating temperature to 225 F. Remediation work includes two tower replacements on the line.
Cost Information
Time Estimate
Dec 01 2026

Contingent

Note: Although AF2-350 may not presently have cost responsibility for this upgrade, AF2-350 may need this upgrade in-service to be deliverable to the PJM system. If AF2-350 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA

System Reinforcement: b3775.2
Type
Load Flow
TO
NextEra
RTEP ID / TO ID
b3775.2
Title
Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles).
Description
Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles).
Cost Information
Time Estimate
May 09 2023

Not Contingent

Note: AF2-350 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-350 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA
(All)C2280.0 MVA
(All)STE2107.0 MVA

System Reinforcement: b3775.3
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.3
Title
Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete
Description
Part of b3775 baseline. Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete (5 miles) with twin bundled 1277 ACAR conductor.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AF2-350 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-350 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA
(All)C2280.0 MVA
(All)STE2107.0 MVA

System Reinforcement: b3775.5
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.5
Title
Replace E. Frankfort 345 kV circuit breaker “9-14” with 3150A SF6 circuit breaker.
Description
Part of b3775 baseline. Replace E. Frankfort 345 kV circuit breaker “9-14” with 3150A SF6 circuit breaker.
Cost Information
Time Estimate
Oct 06 2025

Not Contingent

Note: AF2-350 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-350 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1826.0 MVA
(All)B2070.0 MVA
(All)C2390.0 MVA
SUMSTE2385.0 MVA

System Reinforcement: b3775.4
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.4 / CE_B3775.4
Title
Rebuild 345 kV double circuit extending from Crete to E. Frankfort.
Description
Part of b3775 baseline. Rebuild 12.7 miles of 345 kV double circuit extending from Crete to E. Frankfort with twin bundled 1277 ACAR conductor.
Cost Information
Time Estimate
Jun 01 2026

Not Contingent

Note: AF2-350 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-350 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
(Any)765-L11215__-S_SRT-A
No new ratings for this Flowgate.
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA
(All)C2280.0 MVA
(All)STE2017.0 MVA

System Reinforcement: n5145
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n5145
Title
Reconfigure Wilton 765kV bus
Description
Reconfigure Wilton 765kV bus thereby allowing for 765kV L11216 (currently on Bus 6) to be relocated to Bus 8. Along with this line relocation, installation of 2-765kV BT CBs (6-8 & 8-2). Cost increased from $12M to $55M. This will eliminate the stuck breaker contingencies '112-65-BT4-5__' and '112-65-BT5-6__'. No other contingency updates needed.
Total Cost ($USD)
$55,229,373
Discounted Total Cost ($USD)
$55,229,373
Allocated Cost ($USD)
$0
Time Estimate
Jun 30 2026

Contingent

Note: Based on PJM cost allocation criteria, AF2-350 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AF2-350 may not have cost responsibility for this upgrade, AF2-350 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AF2-350 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
(Any)COMED_P4_112-65-BT4-5___SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4_112-65-BT5-6___SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4_112-65-BT2-3___SRT-A
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AF2-350


AF2-350 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AF2-350 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AF2-350 One Line Diagram

AF2-350 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.