AF2-404 Final System Impact Study (Retool 1) Report

v1.00 released 2025-12-08 18:19

Gladys DP-Stonemill 69 kV

0.0 MW Capacity / 0.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Pigeon Run Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the TC1 projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.
Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of TC1 projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Campbell County, Virginia. This project is an increase to the developer’s AE2-185 project(s), which will share the same Point of Interconnection. The AF2-404 project is a 0.0 MW uprate (0.0 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 60.0 MW with 36.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AF2-404
Project Name:
Gladys DP-Stonemill 69 kV
Project Developer Name:
Pigeon Run Solar, LLC
State:
Virginia
County:
Campbell
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
60.0
MWE:
0.0
MWC:
0.0
Battery Storage Specification:
80.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2027

Physical Interconnection Facility Study

Reviewed

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AF2-404 will interconnect with the Dominion transmission system tapping the Gladys DP to Stonemill Switching Station 69 kV line, sharing interconnection facilities with AE2-185.

 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AF2-404 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AF2-404Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$939,177$939,177
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$724,989$724,989
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$1,664,166$1,664,166

* Contributes to calculation for Security. See Security Section of this report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AE2-185/AF2-404

Security has been calculated for the AE2-185/AF2-404 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AE2-185/AF2-404
Project(s): AE2-185/AF2-404
Final Agreement Security (A): $3,328,332
Portion of Costs Already Paid (B): $0
Revised Net Security (C): A − B = $3,328,332
Security on Hand with PJM (D): $5,782,235
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

The New Service Request Project will interconnect with the Dominion transmission system by tapping the Gladys DP-Stonemill Switching Station 69 kV Line 35. The required work for the interconnection of the New Service Request Project to the Dominion Transmission System is detailed in the following tables.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n9323.0

Remote Relay at Stone Mill Substation.

$144,634$99,161$27,348$17,487$288,630$96,210 (See Note 1)
Developer Scope

Project Developer has elected the option Option to Build where they will assume responsibility for the design, procurement and construction of the Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades identified in this SIS report.

The Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n9324.0

Transmission Line Tie-in for new single breaker tap switching station for AE2-185 and AF2-404.

$754,578$366,424$113,779$22,777$1,257,558$628,779 (See Note 1)
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Transmission Owner Interconnection Facilities (Oversight) Transmission Owner will review the Project Developer’s Option to Build design documents and drawings, provide construction oversight for Option to Build designated facilities and perform a protection and control equipment checkout and end-to-end testing.

$106,788$0$22,352$0$129,140$64,570 (See Note 1)
(Pending)

New interconnection substation (Oversight) Transmission Owner will review the Project Developer’s Option to Build design documents and drawings, provide construction oversight for Option to Build designated facilities and perform a protection and control equipment checkout and end-to-end testing.

$1,135,834$326,193$257,752$29,435$1,749,214$874,607 (See Note 1)

Based on the scope of work for the Interconnection Facilities, it is expected to take 42 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

 

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2027 load flow model and the results were verified by Dominion.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AF2-404 was evaluated as a 0.0 MW (0.0 MW Capacity) injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AF2-404 was evaluated as a 20.0 MW injection and 20.0 MW withdrawal in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary for Dynamic Stability Analysis Using PSSE

New Service Requests (projects) in PJM Transition Cycle 1 Cluster 35 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 35 projects.

 

Table 1: Transition Cycle 1 Cluster 35 Projects

Cluster

Project

Fuel Type

Transmission Owner

MFO (MW)

MWE (MW)

MWC (MW)

Point of Interconnection

35

AE2-185

Solar

Dominion

60

60

36

Gladys DP – Stonemill 69 kV

AF2-404

Battery

Dominion

0

0

AE2-283

Solar

Dominion

53

53

28

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 35 projects will meet the dynamics requirements of the NERC, Dominion Energy, and PJM reliability standards.

 

The load flow case finalized for Phase 2 was used as a starting point and was updated based on latest Cluster 35 data, Dominion Energy recommended transmission changes and withdrawn generation. Projects in vicinity of Cluster 35 have been dispatched online at maximum power output with near unity power factor measured at the high-side of the main substation transformer. The dynamic models for Cluster 35 projects were updated based on the latest DP2 data and include any tuning adjustments recommended during Phase 2.

 

For Cluster 35 the dispatch of the study units was based on two scenarios.

  • Scenario 1: MFO met with solar generation and energy storage offline (solar output = 61.9 MW and storage is offline)
  • Scenario 3: MFO met with the solar generation and energy storage dispatched proportionally to their power capability (solar output = 47.44 MW and storage output = 14.56 MW)

 

Cluster 35 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. 75 contingencies were studied, each with a 30 second simulation time period. The studied contingencies included:

 

  • Steady-state operation
  • Three-phase faults with normal clearing time
  • Single-phase bus faults with normal clearing time
  • Single-phase faults with stuck breaker
  • Single-phase faults with delayed clearing at remote end
  • Three-phase faults with loss of multiple-circuit tower line.

 

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

For all of the fault contingencies tested on the RTEP 2027 summer peak case:

 

  • Cluster 35 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  • The system with Cluster 35 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.
  • Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus) and the final voltages are within the steady-state voltage ranges below per Dominion Energy and AEP’s transmission planning criteria.
    • Dominion Energy:
      • P1 Category Contingencies:
        • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
        • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
        • 1.01 to 1.096 p.u. for 500 kV facilities
      • P2, P4, P5, and P7 Category Contingencies:
        • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
        • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
        • 1.00 to 1.096 p.u. for 500 kV facilities
    • AEP:
      • 0.92 p.u. to 1.05 p.u. for all voltage levels for each NERC Category Contingency
  • No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

The results of the analysis indicated all evaluation criteria were met. The following observations were made.

 

The initial results showed that Cluster 35 generators units exhibited slow reactive power recovery for several contingencies, Power Plant Controller (PPC) freezing, divergence and low frequency controller oscillations. These issues did not cause instability, and the generating units were tuned to achieve a faster recovery with better response.

The following adjustments were required for the respective queue projects based on the analysis results:

 

  • For AE2-187 the following adjustments were made:
    • The REECA1 Vup (p.u.) (CON J+1) parameter was set to 1.15 p.u to mitigate PPC freezing
    • Generator tripped for overvoltage protection model for voltage above 1.21 p.u and the time delay setting was updated from 0.16 to 0.3 seconds to allow generator to ride through the fault

 

  • For AE2-283 the following adjustments were made:
    • The REGCA1 Accel (CON J+13) parameter was set to 0.5 to improve PSS/E network solution calculations

 

  • For AC1-122 the following adjustments were made:
    • The REPCA Ki (CON J+2) parameter was changed from 0 to 10 to improve reactive power recovery

 

During phase 3 analysis all generations near Cluster 35 (AC1-042, AC1-145, AE2-185, AE2-187, and AF2-404) have their REGCA1 Accel set to 0.7. This was implemented as part of a phase 2 observation.  It should be noted that this parameter does not affect the performance or recovery of the renewable model, but is used to smooth the voltage and angle calculations within PSS/E.

 

Voltages above 1.05 p.u. were observed at Altavista 69 kV. This is due to Altavista 138-69 kV load tap changer operating at 1.10 p.u. to maintain the Altavista 69 kV scheduled voltage. A significant voltage drop was observed between Altavista, Gladys Tap, Altavista DP, and Mt Airy Tap due to the amount of generation served within the Altavista 69 kV system. To ensure that the post contingency voltage is below 1.05 p.u., the Altavista 138/69 kV load tap changing transformer would need to operate at 1.0375 p.u. tap and under System Normal (P0) conditions, would produce a 0.968 p.u. voltage on the Altavista 69 kV bus, which is within Dominion Energy’s P0 voltage levels. A voltage coordination study is recommended in the future to determine an acceptable voltage schedule for the Altavista 138/69 kV load tap changing transformer to coordinate with the generations served in the Altavista 69 kV system.

 

AE2-185, AF2-404, AE2-283, AC1-042 and AE2-187 were observed to have controller oscillations for a few faults such as P415. This is not a concern, and IC can tune their model to eliminate this behavior.

 

AD1-131, and AF2-107’s reactive power was observed to not settle within the 30 second simulation window for various faults. This issue did not cause instability in the system and the models can be tuned to achieve a faster reactive power output settlement.

 

Low-frequency oscillations were observed for AE1-250 that were positively damped and settled in less than 15 seconds.  This issue did not cause instability in the system.

 

The AE2-185 queue project met the 0.95 lagging and leading power factor measured at the high side of main transformer.

 

The AE2-185 and AF2-404 BESS queue projects combined met the 0.95 lagging and leading power factor measured at the high side of main transformer.

 

The AE2-283 queue project met the 0.95 lagging and leading power factor measured at the high side of main transformer.

 

A voltage coordination study and Electromagnetic Transients (EMT) study around Altavista is recommended due to the findings of this analysis.  Additionally, any future projects connecting near Altavista should provide EMT models for their facility.

 

No mitigations were found to be required

 

Executive Summary for Dynamic Stability Analysis Using  PSCAD/EMT

 

Model Quality Testing Report

 

PSCAD model for Queue project AE2-185/AF2-404 and AE2-283 was developed and tested individually to ensure the model was in compliance with the PJM requirements. Test summary and result of test been summarized below in table 2. it is confirmed that PSCAD model was set up properly and satisfied the PJM requirement.

 

Table 2. MQT Result for each project

Test

Status

Flat Start Test 

Pass 

Voltage Step-Down 

Pass 

Voltage Step-Up 

Pass 

Frequency Step-Down, No Headroom

Pass 

Frequency Step-Down, Headroom

Pass 

Frequency Step-Up, Headroom 

Pass 

HVRT Leading

Pass 

HVRT Lagging

Pass 

LVRT Leading

Pass 

LVRT Lagging

Pass 

System Strength Test 

Pass 

Voltage Ride Through

Pass 

Phase Angle Step-Down 

Pass 

Phase Angle Step-Up 

Pass 

Weak Grid Assessment

 

This Weak Grid Assessment evaluates three projects from PJM Transition Cycle 1 (TC1) Cluster 35 for risk of voltage instability due to weak grid conditions in an EMT simulation environment.  The three projects, AE2-185, AF2-404, and AE2-283, were identified in the Cluster Study as having potential risk of weak grid instability during contingency conditions after dynamic simulation analysis in PSS/E. System reinforcement was found to not be required, although evaluation using detailed models in an EMT simulation was recommended.

 

This assessment, completed by INS Engineering, aims to evaluate the risk of weak grid instability due to low short circuit ratio as identified in the Cluster Study, using detailed models in an EMT simulation.  A summary description of each project can be found below:

Table 3. Summary Description of TC1 Cluster 35 Projects

Project Name

Project Type

Project Size (MW)

POI

POI Bus Number

AE2-185 / AF2-404 Pigeon Run Solar and BESS

PV + BESS

60

Gladys DP – Stonemill 69 kV

941800

AE2-283 Gladys Solar

PV

53

Gladys DP – Stonemill 69 kV

942670

 

Individual project PSCAD models were evaluated for data consistency and model performance as part of the standard Model Quality Test process,  model updates being made where needed.  INS confirmed that the PSCAD models were set up properly and satisfied the requirements of PJM. After satisfactory configuration and performance of the individual projects were obtained, the models were integrated into a translated reduced network in PSCAD to create an overall detailed system model. 

 

Two representative contingency cases from the Cluster Study, considered effectively the worst case in terms of risk for weak grid instability, were then simulated in the PSCAD detailed system model. For Cluster 35, the following contingency cases were chosen (all projects operating at rated power pre-fault).

 

  • Fault ID: P1.01: Fault at Stone Mill 69 kV on Gladys DP 69 kV and loss of circuit line #35
  • Fault ID: P1.18: Fault at Altavista 138 kV on New London (APCO) 138 kV and loss of circuit line #13

 

Simulation results in PSCAD are summarized below.  It can be observed that in case P1.01 the islanded condition results in the projects tripping, similar to the Cluster Study.  Overall system recovery as observed from the remaining 138kV network is stable.  In P1.18, stable recovery is observed in PSCAD and is consistent with the results of the Cluster Study. 

 

Table 4. Summary of cases tested in PSCAD system study

Fault ID

Fault Description

Cluster Study Result

PSCAD Study Result

P1.01

Fault at Stone Mill 69 kV on Gladys DP 69 kV and loss of circuit line #35. Islanded condition in the 69 kV subnetwork. Cluster projects expected to trip.

System Stable,
Projects on 69kV trip

System Stable,
Projects on 69kV trip

P1.18

Fault at Altavista 138 kV on New London (APCO) 138 kV and loss of circuit line #13

Stable

Stable

 

The results of this weak grid assessment using PSCAD show overall stable system recovery in the two worst-case contingencies and supports the conclusion from the Cluster Study that mitigation's are not required.

Reactive Power Analysis

The reactive power capability of AF2-404 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

(No dependencies were identified)

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 312.A.1.b and as outlined in PJM Manual 14H, Section 13, in Phase III of the Cycle, PJM coordinates with the Affected System Operators to conduct any studies required to determine the impact of the New Service Request on any Affected System and will include the Affected System Study results in Phase III System Impact Study, if available from the Affected System Operator.

If your project required an Affected System Study, the results are shown below from the Affected System Operator.

For more details, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM will list any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Final System Impact Study load flow analysis.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AF2-404


AF2-404 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AF2-404 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AF2-404 One Line Diagram

AF2-404 One Line Diagram.png
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.