AG1-021 Final System Impact Study (Retool 1) Report

v1.00 released 2025-12-08 18:20

Jetersville-Ponton 115 kV

10.8 MW Capacity / 20.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Amelia Energy Facility, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the TC1 projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.
Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of TC1 projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Amelia County, Virginia. This project is an increase to the developer’s AF1-294/AF2-115 project(s), which will share the same Point of Interconnection. The AG1-021 project is a 20.0 MW uprate (10.8 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 86.0 MW with 46.5 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG1-021
Project Name:
Jetersville-Ponton 115 kV
Project Developer Name:
Amelia Energy Facility, LLC
State:
Virginia
County:
Amelia
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
86.0
MWE:
20.0
MWC:
10.8
Fuel Type:
Solar
Basecase Study Year:
2027

Physical Interconnection Facility Study

Received

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG1-021 will interconnect with the Dominion transmission system tapping the Jetersville to Ponton 115 kV line, sharing interconnection facilities with AF1-294 and AF2-115.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AG1-021 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AG1-021Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$956,979$956,979
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$1,370,721$1,370,721
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$2,075,992$2,075,992
Transient Stability$389,779$389,779
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$4,793,471$4,793,471

* Contributes to calculation for Security. See Security Section of this report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF1-294/AF2-115/AG1-021

Security has been calculated for the AF1-294/AF2-115/AG1-021 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF1-294/AF2-115/AG1-021
Project(s): AF1-294/AF2-115/AG1-021
Final Agreement Security (A): $17,585,673
Portion of Costs Already Paid (B): $0
Revised Net Security (C): A − B = $17,585,673
Security on Hand with PJM (D): $18,757,552
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

The New Service Request Project will interconnect with the Dominion transmission system via a new three breaker ring bus switching station that connects on the Jetersville-Ponton 115 kV Line 1007.   The required work for the interconnection of the New Service Request Project to the Dominion Transmission System is detailed in the following tables.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

(No Transmission Owner Scope for this project.)

Developer Scope

Project Developer has elected the option Option to Build where they will assume responsibility for the design, procurement and construction of the Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades identified in this SIS report.

The Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n9415.0

Re-arrange Line #1007 to loop into and out of the new three-breaker AF1-294/AF2-115/AG1-021 115 kV switching station (including fiber).

$2,217,373$1,201,242$212,962$150,008$3,781,585$1,260,528 (See Note 1)
n9414.0

Remote Relay at Dennisville Road Substation.

$121,050$0$23,111$0$144,161$48,054 (See Note 1)
n9413.0

Remote Relay at Lone Pine Substation.

$128,143$28,809$24,385$5,080$186,417$62,139 (See Note 1)
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Transmission Owner Interconnection Facilities (oversight) Transmission Owner will review the Project Developer’s Option to Build design documents and drawings, provide construction oversight for Option to Build designated facilities and perform a protection and control equipment checkout and end-to-end testing.

$106,788$0$22,352$0$129,140$43,047 (See Note 1)
(Pending)

New interconnection substation (oversight) Transmission Owner will review the Project Developer’s Option to Build design documents and drawings, provide construction oversight for Option to Build designated facilities and perform a protection and control equipment checkout and end-to-end testing.

$1,918,075$387,747$400,710$35,266$2,741,798$913,933 (See Note 1)

Based on the scope of work for the Interconnection Facilities, it is expected to take 39 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

As shown in the oneline diagram, this Interconnection Request is sharing the Point of Interconnection and Interconnection Facilities with one or more other Interconnection Requests. Should other requests withdraw from Transition Cycle 1, the cost allocation for Transmission Owner Interconnection Facilities, Stand Alone Network Upgrades, and applicable Network Upgrades identified in the study report will be updated for the remaining project(s).

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2027 load flow model and the results were verified by Dominion.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG1-021 was evaluated as a 20.0 MW (10.8 MW Capacity) injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BUCKING-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S-1
BreakerAC116.16 %699.0C811.978.66
GD1DVP
6BUCKING-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC113.03 %571.52B645.994.67
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC110.49 %1204.0C1330.341.55
GD1DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC108.7 %1204.0C1308.781.55
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC100.22 %678.68B680.180.91
GD1DVP
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S-1
BreakerAC117.22 %684.0C801.798.66
GD1DVP
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC114.05 %559.3B637.864.67
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC112.21 %678.68B761.570.91
GD1DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 56372_SRT-S
BreakerAC113.54 %1056.8C1199.861.09
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S_SENS
SingleAC102.07 %3220.44B3287.012.36
GD1DVP
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC109.42 %678.68B742.630.91

Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.16 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:811.97
MW Contribution:8.66
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.96 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:845.48
MW Contribution:8.54
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
4.6774.677
961792AG1-021 E
50/50
3.9843.984
964791AG1-342 C
Adder
5.5435294117647054.712
964792AG1-342 E
Adder
3.6952941176470593.141
3138533PONTONDP
50/50
1.7321.732
3144293JTRSVLE
50/50
1.0761.076
3147133PAMPLIN
50/50
2.7572.757
3151531CLOVER1
50/50
22.522.5
925785AC1-054 E
Adder
3.35529411764705852.852
926274AC1-105 E
Adder
4.0129411764705883.411
942751AE2-291 C
Adder
8.1482352941176476.926
942752AE2-291 E
Adder
5.4329411764705894.618
943902AF1-058 E
Adder
1.841.564
959311AF2-222 C
50/50
38.90838.908
959312AF2-222 E
50/50
26.06826.068
924162AB2-060 E OP
Adder
7.6670588235294136.517
924302AB2-077 E O1
Adder
2.3152941176470591.968
924312AB2-078 E O1
Adder
2.3152941176470591.968
924322AB2-079 E O1
Adder
2.3152941176470591.968
925612AC1-036 E
50/50
1.961.96
941011AE2-092 C
Adder
-9.729411764705882-8.27
946301AF1-294 C
50/50
9.6139.613
946302AF1-294 E
50/50
8.1418.141
957481AF2-042 C
50/50
98.10798.107
957482AF2-042 E
50/50
65.40565.405
958211AF2-115 C
50/50
5.8465.846
958212AF2-115 E
50/50
4.984.98
924032AB2-045 E
50/50
5.85.8
3147223TWITTYS
50/50
2.1732.173
936261AD2-033 C
50/50
27.66927.669
936262AD2-033 E
50/50
18.44618.446
934621AD1-088 C
50/50
18.90418.904
934622AD1-088 E
50/50
9.1029.102
316034AC1-036 C
50/50
0.5350.535
316322AB2-045 C
50/50
1.2941.294
316336AC2-165 C
Adder
-5.905882352941176-5.02
927255AC1-221 E
Adder
4.1458823529411773.524
927264AC1-222 E
Adder
5.52000000000000054.692
932763AC2-100 E
Adder
2.72941176470588242.32
924022AB2-043 E O1
Adder
9.122352941176477.754
925997AC1-075 E
Adder
3.31294117647058832.816
926024AC1-080 E
Adder
1.09882352941176480.934
962561AG1-105 C
Adder
14.18117647058823612.054
962562AG1-105 E
Adder
9.4541176470588238.036
964241AG1-285 C
50/50
25.15525.155
964242AG1-285 E
50/50
16.7716.77
934612AD1-087 E
Adder
6.3835294117647065.426
935172AD1-152 E
Adder
8.887.548
937482AD2-202 E
Adder
1.86823529411764721.588
938821AE1-108 C
Adder
-10.607058823529412-9.016
942461AE2-259 C
50/50
31.1431.14
942462AE2-259 E
50/50
20.7620.76
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1652.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.3429.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.2887.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.04736.047
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8050.805
NYPJM->LTFIMP_NY
CLTF
0.3840.384
LGEELTFEXP_LGEE->PJM
CLTF
0.3670.367
WECLTFEXP_WEC->PJM
CLTF
0.1940.194
CPLELTFEXP_CPLE->PJM
CLTF
4.5424.542
TVALTFEXP_TVA->PJM
CLTF
2.0142.014
MECLTFEXP_MEC->PJM
CLTF
1.2261.226
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
SIGELTFEXP_SIGE->PJM
CLTF
0.0740.074
O66PJM->LTFIMP_O-066
CMTX_NF
5.1335.133

Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.03 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:645.99
MW Contribution:4.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.98 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:685.72
MW Contribution:4.61
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
80/20
4.6754.675
964791AG1-342 C
80/20
5.5355.535
966621AG1-532 C
80/20
0.7060.706
313506AB1-173 C OP
80/20
0.5620.562
3138533PONTONDP
80/20
1.7311.731
3144293JTRSVLE
80/20
1.0761.076
3147043LAWRENC
80/20
0.2660.266
3151261ROARAP2
80/20
0.6810.681
3151281ROARAP4
80/20
0.6440.644
3151311EDGECMA
80/20
5.0375.037
3151361ROSEMG1
80/20
0.6210.621
3151371ROSEMS1
80/20
0.3840.384
3151381ROSEMG2
80/20
0.2910.291
3151391GASTONA
80/20
0.9230.923
3151531CLOVER1
80/20
22.47222.472
3151541CLOVER2
80/20
22.26222.262
3151561HALLBR1
80/20
0.5580.558
3151581KERR 1
80/20
0.5570.557
3151591KERR 2
80/20
1.5611.561
3151601KERR 3
80/20
1.5611.561
3151611KERR 4
80/20
1.5611.561
3151621KERR 5
80/20
1.5611.561
942671AE2-283 C
80/20
1.5211.521
942751AE2-291 C
80/20
8.1298.129
959311AF2-222 C
80/20
38.88338.883
960081AF2-299 C
80/20
0.9410.941
3151631KERR 6
80/20
1.5611.561
3151641KERR 7
80/20
1.5611.561
3152661PLYWOOD A
80/20
1.751.75
3156063AA2-053SOLA
80/20
0.6790.679
316118AC1-105 C
80/20
1.3691.369
316129AC1-054 C
80/20
1.1891.189
316131AB2-060 C
80/20
2.662.66
941011AE2-092 C
Adder
-9.714117647058824-8.257
941801AE2-185 C
80/20
1.9561.956
946281AF1-292 C
80/20
0.7790.779
946301AF1-294 C
80/20
9.6099.609
957481AF2-042 C
80/20
97.99997.999
958211AF2-115 C
80/20
5.8435.843
3151411GASTONB
80/20
0.9230.923
3156073AA1-063SOLA
80/20
0.5840.584
926071AC1-086 C
80/20
6.3516.351
936261AD2-033 C
80/20
27.64927.649
934621AD1-088 C
80/20
18.88618.886
962571AG1-106 C
80/20
0.8210.821
316003AC1-222 C
80/20
1.3481.348
316011AB1-132 C OP
80/20
0.7050.705
316034AC1-036 C
80/20
0.5340.534
316049AB1-081 C OP
80/20
0.4770.477
316210AC1-098 C
80/20
0.3390.339
316212AC1-099 C
80/20
0.1130.113
316222AC1-221 C
80/20
1.5791.579
316237AB2-079 C O1
80/20
0.5670.567
316238AB2-078 C O1
80/20
0.5670.567
316239AB2-077 C O1
80/20
0.5670.567
316248AF1-058 C
80/20
0.450.45
316263AC1-034 C
80/20
2.2292.229
316274AC1-208 C
80/20
3.5413.541
316283AC2-100 C
80/20
1.2351.235
316319Z2-044 C
80/20
0.0740.074
316322AB2-045 C
80/20
1.2941.294
316336AC2-165 C
Adder
-5.884705882352941-5.002
316217AC1-145 C
80/20
0.1690.169
316327AA2-057 C
80/20
0.4730.473
316181AB2-040 GEN
80/20
0.6330.633
313527AB2-043 C
80/20
0.9080.908
316359AB2-059 C OP
80/20
0.5620.562
316087AB2-174 C
80/20
0.5880.588
316197AC1-042 C
80/20
0.1420.142
316123AC1-075 C
80/20
0.9530.953
316205AC1-080 C
80/20
0.3190.319
962561AG1-105 C
80/20
14.16114.161
964241AG1-285 C
80/20
25.13225.132
3137643SOCKMAN
80/20
0.3520.352
932631AC2-084 C
80/20
0.3610.361
934321AD1-056 C
80/20
1.9781.978
934331AD1-057 C
80/20
1.1031.103
934611AD1-087 C
80/20
2.212.21
935171AD1-152 C
80/20
2.1552.155
936161AD2-022 C
80/20
3.6193.619
936171AD2-023 C
80/20
2.1112.111
937481AD2-202 C
80/20
0.6410.641
938821AE1-108 C
Adder
-10.596470588235293-9.007
942461AE2-259 C
80/20
31.13331.133
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1162.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.0479.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.0847.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
35.17235.172
NYPJM->LTFIMP_NY
CLTF
0.3750.375
LGEELTFEXP_LGEE->PJM
CLTF
0.3550.355
WECLTFEXP_WEC->PJM
CLTF
0.1880.188
CPLELTFEXP_CPLE->PJM
CLTF
4.444.44
TVALTFEXP_TVA->PJM
CLTF
1.9591.959
MECLTFEXP_MEC->PJM
CLTF
1.1891.189
LAGNLTFEXP_LAGN->PJM
CLTF
2.5082.508
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.49 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1330.34
MW Contribution:1.55
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.67 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1404.76
MW Contribution:1.47
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.53647058823529410.456
961672AG1-007 E
Adder
0.30352941176470590.258
961791AG1-021 C
Adder
0.83882352941176460.713
961792AG1-021 E
Adder
0.71411764705882350.607
961941AG1-037 C
Adder
0.251764705882352950.214
961942AG1-037 E
Adder
0.167058823529411760.142
963041AG1-153 C
50/50
3.9773.977
963042AG1-153 E
50/50
5.9665.966
964791AG1-342 C
Adder
2.0188235294117651.716
964792AG1-342 E
Adder
1.34588235294117631.144
966621AG1-532 C
50/50
1.1691.169
966622AG1-532 E
50/50
0.7790.779
313506AB1-173 C OP
50/50
0.8520.852
3138533PONTONDP
Adder
0.310588235294117660.264
3145413WATKINS
Adder
0.265882352941176460.226
3145723EMPORIA
50/50
0.3510.351
3147043LAWRENC
50/50
0.2360.236
3147133PAMPLIN
Adder
0.454117647058823570.386
3151261ROARAP2
50/50
0.9170.917
3151281ROARAP4
50/50
0.8680.868
3151311EDGECMA
Adder
9.4070588235294137.996
3151361ROSEMG1
50/50
1.5051.505
3151371ROSEMS1
50/50
0.9320.932
3151381ROSEMG2
50/50
0.7050.705
3151391GASTONA
50/50
2.2972.297
918492AA1-063AE OP
Adder
2.40470588235294122.044
918532AA1-067 E
Adder
0.367058823529411770.312
919692AA2-053 E OP
Adder
2.6788235294117652.277
920042AA2-088 E OP
Adder
4.9317647058823534.192
925785AC1-054 E
Adder
2.1505882352941181.828
926274AC1-105 E
Adder
1.50823529411764711.282
927146AC1-208 E
Adder
2.45294117647058842.085
934521AD1-076 C
Adder
4.7823529411764714.065
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
943902AF1-058 E
Adder
0.71411764705882350.607
944011AF1-069 C
50/50
9.4749.474
944012AF1-069 E
50/50
3.683.68
959311AF2-222 C
Adder
8.9788235294117647.632
959312AF2-222 E
Adder
6.0152941176470595.113
960081AF2-299 C
50/50
1.5581.558
960082AF2-299 E
50/50
1.0391.039
316141AB2-099 E
Adder
0.125882352941176470.107
900672V4-068 E
Adder
0.172941176470588240.147
917342Z2-044 E
Adder
0.36117647058823530.307
922923AB1-081 E OP
Adder
2.24941176470588241.912
923263AB1-132 E OP
50/50
4.64.6
923573AB1-173 E OP
50/50
2.4772.477
924162AB2-060 E OP
Adder
2.522.142
924302AB2-077 E O1
Adder
0.7917647058823530.673
924312AB2-078 E O1
Adder
0.7917647058823530.673
924322AB2-079 E O1
Adder
0.7917647058823530.673
925612AC1-036 E
Adder
0.47058823529411770.4
940492AE2-034 E
Adder
1.07647058823529430.915
941031AE2-094 C
50/50
28.99528.995
941032AE2-094 E
50/50
12.98612.986
946281AF1-292 C
50/50
1.291.29
946282AF1-292 E
50/50
0.860.86
946301AF1-294 C
Adder
1.7247058823529411.466
946302AF1-294 E
Adder
1.46000000000000021.241
957481AF2-042 C
50/50
34.00834.008
957482AF2-042 E
50/50
22.67222.672
957861AF2-080 C
Adder
4.1588235294117653.535
957862AF2-080 E
Adder
1.84352941176470591.567
958211AF2-115 C
Adder
1.04823529411764720.891
958212AF2-115 E
Adder
0.89294117647058820.759
3145393UNCAMP
Adder
2.10941176470588231.793
3143316POE
Adder
0.51176470588235290.435
3151021BRUNSWICKG1
50/50
5.8715.871
3151031BRUNSWICKG2
50/50
5.8715.871
3151041BRUNSWICKG3
50/50
5.8715.871
3151051BRUNSWICKS1
50/50
12.19612.196
3151411GASTONB
50/50
2.2972.297
3152411Z1-086 GT1
50/50
7.5527.552
3152421Z1-086 GT2
50/50
7.5497.549
3152431Z1-086 GT3
50/50
7.5497.549
3152441Z1-086 ST
50/50
13.14613.146
923852AB2-025 E
50/50
1.3441.344
942001AE2-212 C
Adder
-3.7917647058823527-3.223
3147223TWITTYS
Adder
0.52235294117647060.444
917512Z2-088 E OP1
Adder
2.742.329
926071AC1-086 C
50/50
15.80515.805
926072AC1-086 E
50/50
7.1937.193
927021AC1-189 C
Adder
4.5788235294117653.892
927022AC1-189 E
Adder
2.28117647058823541.939
936261AD2-033 C
Adder
7.0082352941176475.957
936262AD2-033 E
Adder
4.6729411764705883.972
934621AD1-088 C
Adder
5.6611764705882364.812
934622AD1-088 E
Adder
2.72588235294117662.317
939411AE1-173 C
Adder
49.7729411764705942.307
939412AE1-173 E
Adder
33.1823529411764728.205
933981AD1-022 C
Adder
3.6082352941176473.067
933982AD1-022 E
Adder
1.9647058823529411.67
962572AG1-106 E
50/50
0.8940.894
962571AG1-106 C
50/50
2.0442.044
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
316011AB1-132 C OP
50/50
1.7541.754
316023AB2-100 C2
50/50
0.8890.889
316240AF1-291 C
Adder
-1.56-1.326
316263AC1-034 C
Adder
4.00705882352941253.406
316274AC1-208 C
Adder
5.5235294117647074.695
316315AB2-025 C
50/50
0.4720.472
316365AB2-100 C1
50/50
0.8890.889
917332KELFORD E
Adder
0.87529411764705890.744
924516AB2-100 E1
50/50
2.6782.678
924517AB2-100 E2
50/50
2.6782.678
925595AC1-034 E
Adder
3.0235294117647062.57
926206AC1-098 E
Adder
2.14705882352941171.825
926214AC1-099 E
Adder
0.70941176470588230.603
927255AC1-221 E
Adder
2.0517647058823531.744
927264AC1-222 E
Adder
2.16588235294117661.841
932763AC2-100 E
Adder
1.3917647058823531.183
918512AA1-065 E OP
Adder
2.60941176470588232.218
919710AA2-057 E
Adder
2.3988235294117652.039
920692AA2-178 E
Adder
1.43529411764705881.22
316181AB2-040 GEN
50/50
0.9590.959
923994AB2-040_E
50/50
4.6454.645
924022AB2-043 E O1
Adder
3.07764705882352942.616
924152AB2-059 E OP
Adder
3.18705882352941172.709
925122AB2-169 E
Adder
2.5788235294117652.192
316087AB2-174 C
50/50
0.9180.918
316088AB2-174 E
50/50
5.0815.081
925997AC1-075 E
Adder
1.36941176470588231.164
926024AC1-080 E
Adder
0.454117647058823570.386
962561AG1-105 C
Adder
5.0952941176470594.331
962562AG1-105 E
Adder
3.39764705882352922.888
964241AG1-285 C
Adder
7.502352941176476.377
964242AG1-285 E
Adder
5.0011764705882364.251
3137643SOCKMAN
50/50
0.5020.502
932632AC2-084 E
Adder
1.89764705882352951.613
934321AD1-056 C
Adder
4.1835294117647063.556
934322AD1-056 E
Adder
2.26941176470588251.929
934331AD1-057 C
Adder
2.33411764705882341.984
934332AD1-057 E
Adder
1.21529411764705891.033
934501AD1-074 C
Adder
13.16823529411764711.193
934502AD1-074 E
Adder
6.7035294117647065.698
934511AD1-075 C
Adder
3.2917647058823532.798
934512AD1-075 E
Adder
1.67647058823529421.425
934612AD1-087 E
Adder
2.20941176470588241.878
935172AD1-152 E
Adder
3.25058823529411762.763
936161AD2-022 C
Adder
3.8235294117647063.25
936162AD2-022 E
Adder
2.29411764705882341.95
936171AD2-023 C
Adder
2.23058823529411751.896
936172AD2-023 E
Adder
1.21058823529411751.029
937482AD2-202 E
Adder
0.64705882352941180.55
940481AE2-033 C
50/50
18.24118.241
940482AE2-033 E
50/50
12.29712.297
940541AE2-040 C
50/50
3.3223.322
942461AE2-259 C
Adder
3.8988235294117653.314
942462AE2-259 E
Adder
2.62.21
944641AF1-129 C
Adder
-87.83529411764705-74.66
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.7 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1308.78
MW Contribution:1.55
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.88 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1383.11
MW Contribution:1.47
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.53647058823529410.456
961672AG1-007 E
Adder
0.30352941176470590.258
961791AG1-021 C
Adder
0.83882352941176460.713
961792AG1-021 E
Adder
0.71411764705882350.607
961941AG1-037 C
Adder
0.251764705882352950.214
961942AG1-037 E
Adder
0.167058823529411760.142
963041AG1-153 C
50/50
3.9773.977
963042AG1-153 E
50/50
5.9665.966
964791AG1-342 C
Adder
2.0188235294117651.716
964792AG1-342 E
Adder
1.34588235294117631.144
966621AG1-532 C
50/50
1.1691.169
966622AG1-532 E
50/50
0.7790.779
313506AB1-173 C OP
50/50
0.8520.852
3138533PONTONDP
Adder
0.310588235294117660.264
3145413WATKINS
Adder
0.265882352941176460.226
3145723EMPORIA
50/50
0.3510.351
3147043LAWRENC
50/50
0.2360.236
3147133PAMPLIN
Adder
0.454117647058823570.386
3151261ROARAP2
50/50
0.9170.917
3151281ROARAP4
50/50
0.8680.868
3151311EDGECMA
Adder
9.4070588235294137.996
3151361ROSEMG1
50/50
1.5051.505
3151371ROSEMS1
50/50
0.9320.932
3151381ROSEMG2
50/50
0.7050.705
3151391GASTONA
50/50
2.2972.297
918492AA1-063AE OP
Adder
2.40470588235294122.044
918532AA1-067 E
Adder
0.367058823529411770.312
919692AA2-053 E OP
Adder
2.6788235294117652.277
920042AA2-088 E OP
Adder
4.9317647058823534.192
925785AC1-054 E
Adder
2.1505882352941181.828
926274AC1-105 E
Adder
1.50823529411764711.282
927146AC1-208 E
Adder
2.45294117647058842.085
934521AD1-076 C
Adder
4.7823529411764714.065
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
943902AF1-058 E
Adder
0.71411764705882350.607
944011AF1-069 C
50/50
9.4749.474
944012AF1-069 E
50/50
3.683.68
959311AF2-222 C
Adder
8.9788235294117647.632
959312AF2-222 E
Adder
6.0152941176470595.113
960081AF2-299 C
50/50
1.5581.558
960082AF2-299 E
50/50
1.0391.039
316141AB2-099 E
Adder
0.125882352941176470.107
900672V4-068 E
Adder
0.172941176470588240.147
917342Z2-044 E
Adder
0.36117647058823530.307
922923AB1-081 E OP
Adder
2.24941176470588241.912
923263AB1-132 E OP
50/50
4.64.6
923573AB1-173 E OP
50/50
2.4772.477
924162AB2-060 E OP
Adder
2.522.142
924302AB2-077 E O1
Adder
0.7917647058823530.673
924312AB2-078 E O1
Adder
0.7917647058823530.673
924322AB2-079 E O1
Adder
0.7917647058823530.673
925612AC1-036 E
Adder
0.47058823529411770.4
940492AE2-034 E
Adder
1.07647058823529430.915
941031AE2-094 C
50/50
28.99528.995
941032AE2-094 E
50/50
12.98612.986
946281AF1-292 C
50/50
1.291.29
946282AF1-292 E
50/50
0.860.86
946301AF1-294 C
Adder
1.7247058823529411.466
946302AF1-294 E
Adder
1.46000000000000021.241
957481AF2-042 C
50/50
34.00834.008
957482AF2-042 E
50/50
22.67222.672
957861AF2-080 C
Adder
4.1588235294117653.535
957862AF2-080 E
Adder
1.84352941176470591.567
958211AF2-115 C
Adder
1.04823529411764720.891
958212AF2-115 E
Adder
0.89294117647058820.759
3145393UNCAMP
Adder
2.10941176470588231.793
3143316POE
Adder
0.51176470588235290.435
3151021BRUNSWICKG1
50/50
5.8715.871
3151031BRUNSWICKG2
50/50
5.8715.871
3151041BRUNSWICKG3
50/50
5.8715.871
3151051BRUNSWICKS1
50/50
12.19612.196
3151411GASTONB
50/50
2.2972.297
3152411Z1-086 GT1
50/50
7.5527.552
3152421Z1-086 GT2
50/50
7.5497.549
3152431Z1-086 GT3
50/50
7.5497.549
3152441Z1-086 ST
50/50
13.14613.146
923852AB2-025 E
50/50
1.3441.344
942001AE2-212 C
Adder
-3.7917647058823527-3.223
3147223TWITTYS
Adder
0.52235294117647060.444
917512Z2-088 E OP1
Adder
2.742.329
926071AC1-086 C
50/50
15.80515.805
926072AC1-086 E
50/50
7.1937.193
927021AC1-189 C
Adder
4.5788235294117653.892
927022AC1-189 E
Adder
2.28117647058823541.939
936261AD2-033 C
Adder
7.0082352941176475.957
936262AD2-033 E
Adder
4.6729411764705883.972
934621AD1-088 C
Adder
5.6611764705882364.812
934622AD1-088 E
Adder
2.72588235294117662.317
939411AE1-173 C
Adder
49.7729411764705942.307
939412AE1-173 E
Adder
33.1823529411764728.205
933981AD1-022 C
Adder
3.6082352941176473.067
933982AD1-022 E
Adder
1.9647058823529411.67
962572AG1-106 E
50/50
0.8940.894
962571AG1-106 C
50/50
2.0442.044
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
316011AB1-132 C OP
50/50
1.7541.754
316023AB2-100 C2
50/50
0.8890.889
316240AF1-291 C
Adder
-1.56-1.326
316263AC1-034 C
Adder
4.00705882352941253.406
316274AC1-208 C
Adder
5.5235294117647074.695
316315AB2-025 C
50/50
0.4720.472
316365AB2-100 C1
50/50
0.8890.889
917332KELFORD E
Adder
0.87529411764705890.744
924516AB2-100 E1
50/50
2.6782.678
924517AB2-100 E2
50/50
2.6782.678
925595AC1-034 E
Adder
3.0235294117647062.57
926206AC1-098 E
Adder
2.14705882352941171.825
926214AC1-099 E
Adder
0.70941176470588230.603
927255AC1-221 E
Adder
2.0517647058823531.744
927264AC1-222 E
Adder
2.16588235294117661.841
932763AC2-100 E
Adder
1.3917647058823531.183
918512AA1-065 E OP
Adder
2.60941176470588232.218
919710AA2-057 E
Adder
2.3988235294117652.039
920692AA2-178 E
Adder
1.43529411764705881.22
316181AB2-040 GEN
50/50
0.9590.959
923994AB2-040_E
50/50
4.6454.645
924022AB2-043 E O1
Adder
3.07764705882352942.616
924152AB2-059 E OP
Adder
3.18705882352941172.709
925122AB2-169 E
Adder
2.5788235294117652.192
316087AB2-174 C
50/50
0.9180.918
316088AB2-174 E
50/50
5.0815.081
925997AC1-075 E
Adder
1.36941176470588231.164
926024AC1-080 E
Adder
0.454117647058823570.386
962561AG1-105 C
Adder
5.0952941176470594.331
962562AG1-105 E
Adder
3.39764705882352922.888
964241AG1-285 C
Adder
7.502352941176476.377
964242AG1-285 E
Adder
5.0011764705882364.251
3137643SOCKMAN
50/50
0.5020.502
932632AC2-084 E
Adder
1.89764705882352951.613
934321AD1-056 C
Adder
4.1835294117647063.556
934322AD1-056 E
Adder
2.26941176470588251.929
934331AD1-057 C
Adder
2.33411764705882341.984
934332AD1-057 E
Adder
1.21529411764705891.033
934501AD1-074 C
Adder
13.16823529411764711.193
934502AD1-074 E
Adder
6.7035294117647065.698
934511AD1-075 C
Adder
3.2917647058823532.798
934512AD1-075 E
Adder
1.67647058823529421.425
934612AD1-087 E
Adder
2.20941176470588241.878
935172AD1-152 E
Adder
3.25058823529411762.763
936161AD2-022 C
Adder
3.8235294117647063.25
936162AD2-022 E
Adder
2.29411764705882341.95
936171AD2-023 C
Adder
2.23058823529411751.896
936172AD2-023 E
Adder
1.21058823529411751.029
937482AD2-202 E
Adder
0.64705882352941180.55
940481AE2-033 C
50/50
18.24118.241
940482AE2-033 E
50/50
12.29712.297
940541AE2-040 C
50/50
3.3223.322
942461AE2-259 C
Adder
3.8988235294117653.314
942462AE2-259 E
Adder
2.62.21
944641AF1-129 C
Adder
-87.83529411764705-74.66
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.22 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:680.18
MW Contribution:0.91
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.36 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:701.52
MW Contribution:0.98
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
80/20
0.9120.912
961791AG1-021 C
80/20
0.9080.908
961941AG1-037 C
80/20
0.4820.482
964791AG1-342 C
80/20
2.0352.035
966621AG1-532 C
80/20
3.2993.299
313506AB1-173 C OP
80/20
2.2292.229
3138533PONTONDP
80/20
0.3360.336
3144293JTRSVLE
80/20
0.2090.209
3147043LAWRENC
80/20
0.5790.579
3151261ROARAP2
80/20
2.1232.123
3151281ROARAP4
80/20
2.0092.009
3151311EDGECMA
80/20
16.55516.555
3151361ROSEMG1
80/20
3.9363.936
3151371ROSEMS1
80/20
2.4382.438
3151381ROSEMG2
80/20
1.8431.843
3151391GASTONA
80/20
6.1766.176
3151531CLOVER1
80/20
5.8195.819
3151581KERR 1
80/20
0.3080.308
3151591KERR 2
80/20
0.8620.862
3151601KERR 3
80/20
0.8620.862
3151611KERR 4
80/20
0.8620.862
3151621KERR 5
80/20
0.8620.862
934521AD1-076 C
80/20
7.0327.032
943171AE2-346 C
80/20
0.2140.214
959311AF2-222 C
80/20
8.6368.636
960081AF2-299 C
80/20
4.3984.398
3151631KERR 6
80/20
0.8620.862
3151641KERR 7
80/20
0.8620.862
3152661PLYWOOD A
80/20
0.6390.639
3156011CONETOE2SOL
80/20
1.1751.175
3156063AA2-053SOLA
80/20
2.1582.158
316118AC1-105 C
80/20
0.4840.484
316129AC1-054 C
80/20
1.341.34
316131AB2-060 C
80/20
1.0341.034
316140AB2-099 C
80/20
0.0920.092
946281AF1-292 C
80/20
3.6413.641
946301AF1-294 C
80/20
1.8661.866
957481AF2-042 C
80/20
24.31224.312
957861AF2-080 C
80/20
6.8566.856
958211AF2-115 C
80/20
1.1351.135
3151151S HAMPT1
80/20
0.9570.957
3151411GASTONB
80/20
6.1766.176
3152921DOMTR78
80/20
0.8540.854
3156073AA1-063SOLA
80/20
1.8141.814
3156083AA2-088SOLA
80/20
0.9350.935
926071AC1-086 C
80/20
42.49342.493
927021AC1-189 C
80/20
7.5497.549
936261AD2-033 C
80/20
8.0298.029
934621AD1-088 C
80/20
4.4044.404
933981AD1-022 C
80/20
5.6875.687
962571AG1-106 C
80/20
5.4965.496
316005AA1-067 C
80/20
0.2210.221
316011AB1-132 C OP
80/20
4.7154.715
316023AB2-100 C2
80/20
2.7732.773
316034AC1-036 C
80/20
0.1240.124
316049AB1-081 C OP
80/20
1.4941.494
316210AC1-098 C
80/20
1.0991.099
316212AC1-099 C
80/20
0.3680.368
316237AB2-079 C O1
80/20
0.2290.229
316238AB2-078 C O1
80/20
0.2290.229
316239AB2-077 C O1
80/20
0.2290.229
316263AC1-034 C
80/20
6.9816.981
316274AC1-208 C
80/20
11.22611.226
316317KELFORD C
80/20
0.370.37
316318V4-068 C
80/20
0.0750.075
316319Z2-044 C
80/20
0.2310.231
316365AB2-100 C1
80/20
2.7732.773
3156021HOLLOMANSOL
80/20
1.5861.586
316327AA2-057 C
80/20
1.4891.489
316181AB2-040 GEN
80/20
2.5112.511
313527AB2-043 C
80/20
0.3630.363
316359AB2-059 C OP
80/20
1.7611.761
316174AB2-169_C
80/20
0.7190.719
316087AB2-174 C
80/20
2.4642.464
962561AG1-105 C
80/20
5.2875.287
964241AG1-285 C
80/20
7.2257.225
3137643SOCKMAN
80/20
1.2371.237
932631AC2-084 C
80/20
1.171.17
934321AD1-056 C
80/20
9.2019.201
934331AD1-057 C
80/20
5.1335.133
934501AD1-074 C
80/20
19.36119.361
934511AD1-075 C
80/20
4.844.84
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1882.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.20711.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.5767.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.15434.154
NYPJM->LTFIMP_NY
CLTF
0.3660.366
LGEELTFEXP_LGEE->PJM
CLTF
0.4310.431
WECLTFEXP_WEC->PJM
CLTF
0.2290.229
CPLELTFEXP_CPLE->PJM
CLTF
4.5894.589
TVALTFEXP_TVA->PJM
CLTF
2.0182.018
MECLTFEXP_MEC->PJM
CLTF
1.3611.361
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
SIGELTFEXP_SIGE->PJM
CLTF
0.0840.084

Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.22 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:801.79
MW Contribution:8.66
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.59 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:831.68
MW Contribution:8.54
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
4.6774.677
961792AG1-021 E
50/50
3.9843.984
964791AG1-342 C
Adder
5.5447058823529414.713
964792AG1-342 E
Adder
3.6964705882352943.142
966621AG1-532 C
Adder
0.70470588235294120.599
966622AG1-532 E
Adder
0.47058823529411770.4
3138533PONTONDP
50/50
1.7321.732
3144293JTRSVLE
50/50
1.0761.076
3145723EMPORIA
Adder
0.21647058823529410.184
3147133PAMPLIN
50/50
2.7572.757
3151531CLOVER1
50/50
22.50522.505
925785AC1-054 E
Adder
3.35647058823529452.853
926274AC1-105 E
Adder
4.0141176470588233.412
942751AE2-291 C
Adder
8.1517647058823536.929
942752AE2-291 E
Adder
5.4352941176470594.62
943902AF1-058 E
Adder
1.841.564
959311AF2-222 C
50/50
38.91438.914
959312AF2-222 E
50/50
26.07226.072
960081AF2-299 C
Adder
0.94000000000000010.799
960082AF2-299 E
Adder
0.62705882352941180.533
924162AB2-060 E OP
Adder
7.6694117647058836.519
924302AB2-077 E O1
Adder
2.3164705882352941.969
924312AB2-078 E O1
Adder
2.3164705882352941.969
924322AB2-079 E O1
Adder
2.3164705882352941.969
925612AC1-036 E
50/50
1.961.96
941011AE2-092 C
Adder
-9.724705882352941-8.266
946281AF1-292 C
Adder
0.77764705882352950.661
946282AF1-292 E
Adder
0.51882352941176470.441
946301AF1-294 C
50/50
9.6159.615
946302AF1-294 E
50/50
8.1428.142
957481AF2-042 C
50/50
98.12598.125
957482AF2-042 E
50/50
65.41765.417
958211AF2-115 C
50/50
5.8475.847
958212AF2-115 E
50/50
4.9814.981
3147223TWITTYS
50/50
2.1732.173
936261AD2-033 C
50/50
27.67327.673
936262AD2-033 E
50/50
18.44918.449
934621AD1-088 C
50/50
18.90718.907
934622AD1-088 E
50/50
9.1039.103
316034AC1-036 C
50/50
0.5350.535
316336AC2-165 C
Adder
-5.9023529411764715-5.017
927255AC1-221 E
Adder
4.1470588235294123.525
927264AC1-222 E
Adder
5.5211764705882354.693
932763AC2-100 E
Adder
2.7305882352941182.321
924022AB2-043 E O1
Adder
9.1247058823529417.756
925997AC1-075 E
Adder
3.3141176470588242.817
926024AC1-080 E
Adder
1.10.935
962561AG1-105 C
Adder
14.18352941176470612.056
962562AG1-105 E
Adder
9.4564705882352958.038
964241AG1-285 C
50/50
25.15925.159
964242AG1-285 E
50/50
16.77316.773
934612AD1-087 E
Adder
6.3847058823529415.427
935172AD1-152 E
Adder
8.8823529411764717.55
937482AD2-202 E
Adder
1.86823529411764721.588
938821AE1-108 C
Adder
-10.602352941176472-9.012
942461AE2-259 C
50/50
31.14431.144
942462AE2-259 E
50/50
20.76320.763
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1672.167
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.4439.443
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.3277.327
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.10836.108
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7990.799
NYPJM->LTFIMP_NY
CLTF
0.3810.381
LGEELTFEXP_LGEE->PJM
CLTF
0.370.37
WECLTFEXP_WEC->PJM
CLTF
0.1960.196
CPLELTFEXP_CPLE->PJM
CLTF
4.5484.548
TVALTFEXP_TVA->PJM
CLTF
2.0222.022
MECLTFEXP_MEC->PJM
CLTF
1.2351.235
LAGNLTFEXP_LAGN->PJM
CLTF
2.5882.588
SIGELTFEXP_SIGE->PJM
CLTF
0.0750.075
O66PJM->LTFIMP_O-066
CMTX_NF
5.0935.093

Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.05 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:637.86
MW Contribution:4.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.13 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:677.49
MW Contribution:4.61
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
80/20
4.6754.675
964791AG1-342 C
80/20
5.5375.537
966621AG1-532 C
80/20
0.7060.706
313506AB1-173 C OP
80/20
0.5620.562
3138533PONTONDP
80/20
1.7321.732
3144293JTRSVLE
80/20
1.0761.076
3147043LAWRENC
80/20
0.2660.266
3151261ROARAP2
80/20
0.6820.682
3151281ROARAP4
80/20
0.6450.645
3151311EDGECMA
80/20
5.0435.043
3151361ROSEMG1
80/20
0.6210.621
3151371ROSEMS1
80/20
0.3850.385
3151381ROSEMG2
80/20
0.2910.291
3151391GASTONA
80/20
0.9240.924
3151531CLOVER1
80/20
22.47722.477
3151541CLOVER2
80/20
22.26722.267
3151561HALLBR1
80/20
0.5580.558
3151581KERR 1
80/20
0.5580.558
3151591KERR 2
80/20
1.5621.562
3151601KERR 3
80/20
1.5621.562
3151611KERR 4
80/20
1.5621.562
3151621KERR 5
80/20
1.5621.562
942671AE2-283 C
80/20
1.5231.523
942751AE2-291 C
80/20
8.1328.132
959311AF2-222 C
80/20
38.88938.889
960081AF2-299 C
80/20
0.9420.942
3151631KERR 6
80/20
1.5621.562
3151641KERR 7
80/20
1.5621.562
3152661PLYWOOD A
80/20
1.751.75
3156063AA2-053SOLA
80/20
0.680.68
316118AC1-105 C
80/20
1.3691.369
316129AC1-054 C
80/20
1.1891.189
316131AB2-060 C
80/20
2.6612.661
941011AE2-092 C
Adder
-9.709411764705882-8.253
941801AE2-185 C
80/20
1.9581.958
946281AF1-292 C
80/20
0.7790.779
946301AF1-294 C
80/20
9.619.61
957481AF2-042 C
80/20
98.01698.016
958211AF2-115 C
80/20
5.8445.844
3151411GASTONB
80/20
0.9240.924
3156073AA1-063SOLA
80/20
0.5850.585
926071AC1-086 C
80/20
6.3586.358
936261AD2-033 C
80/20
27.65427.654
934621AD1-088 C
80/20
18.88918.889
962571AG1-106 C
80/20
0.8220.822
316003AC1-222 C
80/20
1.3491.349
316011AB1-132 C OP
80/20
0.7060.706
316034AC1-036 C
80/20
0.5340.534
316049AB1-081 C OP
80/20
0.4780.478
316210AC1-098 C
80/20
0.3390.339
316212AC1-099 C
80/20
0.1140.114
316222AC1-221 C
80/20
1.581.58
316237AB2-079 C O1
80/20
0.5670.567
316238AB2-078 C O1
80/20
0.5670.567
316239AB2-077 C O1
80/20
0.5670.567
316248AF1-058 C
80/20
0.450.45
316263AC1-034 C
80/20
2.2322.232
316274AC1-208 C
80/20
3.5443.544
316283AC2-100 C
80/20
1.2351.235
316319Z2-044 C
80/20
0.0740.074
316336AC2-165 C
Adder
-5.881176470588235-4.999
316217AC1-145 C
80/20
0.1690.169
316327AA2-057 C
80/20
0.4730.473
316181AB2-040 GEN
80/20
0.6330.633
313527AB2-043 C
80/20
0.9080.908
316359AB2-059 C OP
80/20
0.5630.563
316087AB2-174 C
80/20
0.5890.589
316197AC1-042 C
80/20
0.1420.142
316123AC1-075 C
80/20
0.9540.954
316205AC1-080 C
80/20
0.3190.319
962561AG1-105 C
80/20
14.16414.164
964241AG1-285 C
80/20
25.13725.137
3137643SOCKMAN
80/20
0.3530.353
932631AC2-084 C
80/20
0.3610.361
934321AD1-056 C
80/20
1.981.98
934331AD1-057 C
80/20
1.1051.105
934611AD1-087 C
80/20
2.212.21
935171AD1-152 C
80/20
2.1562.156
936161AD2-022 C
80/20
3.6223.622
936171AD2-023 C
80/20
2.1132.113
937481AD2-202 C
80/20
0.6410.641
938821AE1-108 C
Adder
-10.591764705882353-9.003
942461AE2-259 C
80/20
31.13731.137
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1192.119
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.1489.148
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.1237.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
35.23335.233
NYPJM->LTFIMP_NY
CLTF
0.3720.372
LGEELTFEXP_LGEE->PJM
CLTF
0.3590.359
WECLTFEXP_WEC->PJM
CLTF
0.190.19
CPLELTFEXP_CPLE->PJM
CLTF
4.4464.446
TVALTFEXP_TVA->PJM
CLTF
1.9681.968
MECLTFEXP_MEC->PJM
CLTF
1.1991.199
LAGNLTFEXP_LAGN->PJM
CLTF
2.5182.518
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.21 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:761.57
MW Contribution:0.91
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.21 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:781.94
MW Contribution:0.98
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
80/20
0.9120.912
961791AG1-021 C
80/20
0.9070.907
961941AG1-037 C
80/20
0.4820.482
964791AG1-342 C
80/20
2.0342.034
966621AG1-532 C
80/20
3.2983.298
313506AB1-173 C OP
80/20
2.2292.229
3138533PONTONDP
80/20
0.3360.336
3144293JTRSVLE
80/20
0.2090.209
3147043LAWRENC
80/20
0.5790.579
3151261ROARAP2
80/20
2.1232.123
3151281ROARAP4
80/20
2.0092.009
3151311EDGECMA
80/20
16.54816.548
3151361ROSEMG1
80/20
3.9353.935
3151371ROSEMS1
80/20
2.4382.438
3151381ROSEMG2
80/20
1.8431.843
3151391GASTONA
80/20
6.1746.174
3151531CLOVER1
80/20
5.8145.814
3151581KERR 1
80/20
0.3070.307
3151591KERR 2
80/20
0.8610.861
3151601KERR 3
80/20
0.8610.861
3151611KERR 4
80/20
0.8610.861
3151621KERR 5
80/20
0.8610.861
934521AD1-076 C
80/20
7.0267.026
943171AE2-346 C
80/20
0.2140.214
959311AF2-222 C
80/20
8.6298.629
960081AF2-299 C
80/20
4.3984.398
3151631KERR 6
80/20
0.8610.861
3151641KERR 7
80/20
0.8610.861
3152661PLYWOOD A
80/20
0.6380.638
3156011CONETOE2SOL
80/20
1.1751.175
3156063AA2-053SOLA
80/20
2.1572.157
316118AC1-105 C
80/20
0.4840.484
316129AC1-054 C
80/20
1.341.34
316131AB2-060 C
80/20
1.0331.033
316140AB2-099 C
80/20
0.0920.092
946281AF1-292 C
80/20
3.643.64
946301AF1-294 C
80/20
1.8641.864
957481AF2-042 C
80/20
24.2924.29
957861AF2-080 C
80/20
6.8536.853
958211AF2-115 C
80/20
1.1341.134
3151151S HAMPT1
80/20
0.9560.956
3151411GASTONB
80/20
6.1746.174
3152921DOMTR78
80/20
0.8530.853
3156073AA1-063SOLA
80/20
1.8141.814
3156083AA2-088SOLA
80/20
0.9350.935
926071AC1-086 C
80/20
42.48542.485
927021AC1-189 C
80/20
7.5457.545
936261AD2-033 C
80/20
8.0238.023
934621AD1-088 C
80/20
4.4014.401
933981AD1-022 C
80/20
5.6845.684
962571AG1-106 C
80/20
5.4955.495
316005AA1-067 C
80/20
0.2210.221
316011AB1-132 C OP
80/20
4.7154.715
316023AB2-100 C2
80/20
2.7732.773
316034AC1-036 C
80/20
0.1230.123
316049AB1-081 C OP
80/20
1.4931.493
316210AC1-098 C
80/20
1.0991.099
316212AC1-099 C
80/20
0.3680.368
316237AB2-079 C O1
80/20
0.2290.229
316238AB2-078 C O1
80/20
0.2290.229
316239AB2-077 C O1
80/20
0.2290.229
316263AC1-034 C
80/20
6.9786.978
316274AC1-208 C
80/20
11.22211.222
316315AB2-025 C
80/20
1.661.66
316317KELFORD C
80/20
0.3690.369
316318V4-068 C
80/20
0.0750.075
316319Z2-044 C
80/20
0.2310.231
316365AB2-100 C1
80/20
2.7732.773
3156021HOLLOMANSOL
80/20
1.5851.585
316327AA2-057 C
80/20
1.4881.488
316181AB2-040 GEN
80/20
2.512.51
313527AB2-043 C
80/20
0.3630.363
316359AB2-059 C OP
80/20
1.761.76
316174AB2-169_C
80/20
0.7190.719
316087AB2-174 C
80/20
2.4642.464
962561AG1-105 C
80/20
5.2835.283
964241AG1-285 C
80/20
7.2197.219
3137643SOCKMAN
80/20
1.2371.237
932631AC2-084 C
80/20
1.171.17
934321AD1-056 C
80/20
9.1989.198
934331AD1-057 C
80/20
5.1315.131
934501AD1-074 C
80/20
19.34719.347
934511AD1-075 C
80/20
4.8374.837
940481AE2-033 C
80/20
63.40163.401
940541AE2-040 C
80/20
11.68811.688
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1852.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.08611.086
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.537.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.08134.081
NYPJM->LTFIMP_NY
CLTF
0.370.37
LGEELTFEXP_LGEE->PJM
CLTF
0.4270.427
WECLTFEXP_WEC->PJM
CLTF
0.2270.227
CPLELTFEXP_CPLE->PJM
CLTF
4.5834.583
TVALTFEXP_TVA->PJM
CLTF
2.0082.008
MECLTFEXP_MEC->PJM
CLTF
1.351.35
LAGNLTFEXP_LAGN->PJM
CLTF
2.5652.565
SIGELTFEXP_SIGE->PJM
CLTF
0.0830.083

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.54 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1199.86
MW Contribution:1.09
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.15 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1216.94
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
0.58823529411764710.5
961792AG1-021 E
Adder
0.50117647058823530.426
963041AG1-153 C
50/50
4.6824.682
963042AG1-153 E
50/50
7.0227.022
964791AG1-342 C
Adder
1.43529411764705881.22
964792AG1-342 E
Adder
0.95647058823529410.813
966621AG1-532 C
Adder
-1.14-0.969
3138533PONTONDP
Adder
0.217647058823529420.185
3145723EMPORIA
Adder
-0.3270588235294118-0.278
3147133PAMPLIN
Adder
0.377647058823529450.321
3151531CLOVER1
50/50
7.797.79
3151541CLOVER2
50/50
7.7177.717
926274AC1-105 E
Adder
1.15529411764705880.982
943902AF1-058 E
Adder
0.58823529411764710.5
944011AF1-069 C
50/50
11.48911.489
944012AF1-069 E
50/50
4.4634.463
959311AF2-222 C
Adder
7.2776470588235296.186
959312AF2-222 E
Adder
4.8764705882352944.145
924162AB2-060 E OP
Adder
1.4435294117647061.227
924302AB2-077 E O1
Adder
0.45058823529411770.383
924312AB2-078 E O1
Adder
0.45058823529411770.383
924322AB2-079 E O1
Adder
0.45058823529411770.383
925612AC1-036 E
Adder
0.381176470588235340.324
941031AE2-094 C
50/50
35.16335.163
941032AE2-094 E
50/50
15.74915.749
946281AF1-292 C
Adder
-1.2576470588235293-1.069
946301AF1-294 C
Adder
1.2082352941176471.027
946302AF1-294 E
Adder
1.02352941176470580.87
957481AF2-042 C
50/50
35.70935.709
957482AF2-042 E
50/50
23.80623.806
958211AF2-115 C
Adder
0.73529411764705890.625
958212AF2-115 E
Adder
0.62588235294117660.532
3145506HICKORY
Adder
0.80470588235294130.684
926662AC1-147 E
Adder
0.448235294117647070.381
926755AC1-161 E
Adder
6.3529411764705895.4
3151021BRUNSWICKG1
50/50
6.916.91
3151031BRUNSWICKG2
50/50
6.916.91
3151041BRUNSWICKG3
50/50
6.916.91
3151051BRUNSWICKS1
50/50
14.35614.356
3152411Z1-086 GT1
50/50
8.9758.975
3152421Z1-086 GT2
50/50
8.9718.971
3152431Z1-086 GT3
50/50
8.9718.971
3152441Z1-086 ST
50/50
15.62315.623
913392Y1-086 E
Adder
0.66235294117647060.563
916192Z1-068 E
Adder
0.6682352941176470.568
923832AB2-022 E
Adder
0.374117647058823550.318
925522AC1-027 E
Adder
0.430588235294117660.366
942001AE2-212 C
Adder
-2.8705882352941177-2.44
957871AF2-081 C
Adder
3.47411764705882352.953
957872AF2-081 E
Adder
1.48941176470588241.266
3147223TWITTYS
Adder
0.42235294117647060.359
936261AD2-033 C
Adder
4.3352941176470593.685
936262AD2-033 E
Adder
2.89058823529411772.457
933291AC2-141 C
Adder
14.88235294117647112.65
933292AC2-141 E
Adder
6.3529411764705895.4
934621AD1-088 C
50/50
5.5965.596
934622AD1-088 E
50/50
2.6942.694
939411AE1-173 C
50/50
67.01167.011
939412AE1-173 E
50/50
44.67444.674
3146326AYDLETT TAP
Adder
0.455294117647058850.387
316240AF1-291 C
Adder
-2.2705882352941176-1.93
927255AC1-221 E
Adder
1.70117647058823531.446
927264AC1-222 E
Adder
1.781.513
932763AC2-100 E
Adder
1.14235294117647060.971
934065AD1-033 E
Adder
1.87294117647058831.592
937226AE2-253 E
Adder
2.081.768
919153AA1-139 E2
Adder
1.42117647058823531.208
919152AA1-139 E1
Adder
1.42117647058823531.208
924022AB2-043 E O1
Adder
1.75058823529411781.488
932046AC2-012 E
Adder
4.4317647058823533.767
941591AE2-156 C
Adder
6.1035294117647065.188
944581AF1-123 C
Adder
17.0976470588235314.533
944582AF1-123 E
Adder
39.15058823529411633.278
944591AF1-124 C
Adder
17.15764705882352814.584
944592AF1-124 E
Adder
39.2929411764705933.399
944601AF1-125 C
Adder
16.8341176470588214.309
944602AF1-125 E
Adder
38.536470588235332.756
962561AG1-105 C
Adder
3.50352941176470622.978
962562AG1-105 E
Adder
2.3352941176470591.985
964241AG1-285 C
Adder
5.9952941176470595.096
964242AG1-285 E
Adder
3.99647058823529383.397
3137643SOCKMAN
Adder
-0.34352941176470586-0.292
934321AD1-056 C
Adder
-2.142352941176471-1.821
934331AD1-057 C
Adder
-1.1952941176470588-1.016
934611AD1-087 C
50/50
0.7660.766
934612AD1-087 E
50/50
2.212.21
935172AD1-152 E
Adder
3.1047058823529412.639
937481AD2-202 C
50/50
0.2220.222
937482AD2-202 E
50/50
0.6470.647
938531AE1-072 C
Adder
5.95529411764705955.062
938532AE1-072 E
Adder
3.1047058823529412.639
940641AE2-051 C
50/50
14.85114.851
940642AE2-051 E
50/50
9.9019.901
942461AE2-259 C
Adder
3.32588235294117632.827
942462AE2-259 E
Adder
2.21764705882352951.885
944641AF1-129 C
Adder
-99.89764705882352-84.913
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9681.968
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.10812.108
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4868.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.24536.245
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9710.971
NYPJM->LTFIMP_NY
CLTF
0.4470.447
LGEELTFEXP_LGEE->PJM
CLTF
0.4670.467
WECLTFEXP_WEC->PJM
CLTF
0.2490.249
CPLELTFEXP_CPLE->PJM
CLTF
4.1284.128
TVALTFEXP_TVA->PJM
CLTF
2.2832.283
MECLTFEXP_MEC->PJM
CLTF
1.4991.499
LAGNLTFEXP_LAGN->PJM
CLTF
2.9182.918
SIGELTFEXP_SIGE->PJM
CLTF
0.0920.092
O66PJM->LTFIMP_O-066
CMTX_NF
6.1826.182

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.07 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3287.01
MW Contribution:2.36
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
1.26588235294117671.076
961791AG1-021 C
Adder
2.35764705882352972.004
961941AG1-037 C
Adder
0.71058823529411760.604
963041AG1-153 C
80/20
8.5888.588
964791AG1-342 C
Adder
4.6788235294117653.977
966621AG1-532 C
Adder
1.9870588235294121.689
3138533PONTONDP
Adder
0.87294117647058820.742
3151311EDGECMA
Adder
20.74352941176470817.632
3151531CLOVER1
80/20
17.87817.878
3151541CLOVER2
80/20
17.71117.711
934521AD1-076 C
Adder
17.34705882352941214.745
944011AF1-069 C
80/20
20.29620.296
959311AF2-222 C
Adder
23.07176470588235519.611
960081AF2-299 C
Adder
2.64941176470588242.252
941031AE2-094 C
80/20
62.11762.117
946281AF1-292 C
Adder
2.19294117647058861.864
946301AF1-294 C
Adder
4.8470588235294124.12
957481AF2-042 C
80/20
77.49977.499
957861AF2-080 C
Adder
10.3623529411764718.808
958211AF2-115 C
Adder
2.94705882352941152.505
938771AE1-103 C
80/20
4.24.2
313526AB2-022 C
80/20
0.5460.546
3150601CHESTF5
Adder
76.7117647058823665.205
3150651CHESTF6
Adder
24.50588235294117520.83
3150731STONECA
Adder
8.9505882352941187.608
3150831SPRUNCA
80/20
12.34712.347
3150841SPRUNCB
80/20
12.34712.347
3150921YORKTN3
Adder
157.0388235294118133.483
936591AD2-074 C
Adder
5.7647058823529424.9
942341AE2-247 C
80/20
2.1432.143
943461AF1-017 C
80/20
1.9381.938
943741AF1-042 C
Adder
3.01647058823529422.564
961951AG1-038 C
Adder
3.3341176470588242.834
3150981CHESPKA
80/20
0.6340.634
3150991CHESPKB
80/20
1.051.05
3151021BRUNSWICKG1
80/20
12.67612.676
3151031BRUNSWICKG2
80/20
12.67612.676
3151041BRUNSWICKG3
80/20
12.67612.676
3151051BRUNSWICKS1
80/20
26.33426.334
3151081ELIZAR1
80/20
4.6564.656
3151091ELIZAR2
80/20
4.5754.575
3151101ELIZAR3
80/20
4.7154.715
3151151S HAMPT1
80/20
2.1352.135
3151161SURRY 1
80/20
33.88933.889
3151201GRAVEL4
80/20
3.4873.487
3151211GRAVEL5
80/20
3.4433.443
3151221GRAVEL6
80/20
3.4833.483
3152331SURRY 2
80/20
34.47834.478
3152411Z1-086 GT1
80/20
16.26716.267
3152421Z1-086 GT2
80/20
16.2616.26
3152431Z1-086 GT3
80/20
16.2616.26
3152441Z1-086 ST
80/20
28.31628.316
3156056W1-029WIND
80/20
1.1231.123
3156116Z1-036WIND
80/20
0.9440.944
957601AF2-054 C
Adder
2.37764705882352922.021
942001AE2-212 C
80/20
2.9732.973
957871AF2-081 C
80/20
14.54714.547
958161AF2-110 C
80/20
1.9761.976
926071AC1-086 C
Adder
29.4425.024
927021AC1-189 C
Adder
11.4094117647058839.698
936261AD2-033 C
Adder
17.57529411764705814.939
933291AC2-141 C
80/20
44.42644.426
934621AD1-088 C
80/20
13.42613.426
939411AE1-173 C
80/20
140.502140.502
916191Z1-068 C
80/20
0.0640.064
933981AD1-022 C
Adder
12.39411764705882410.535
962571AG1-106 C
Adder
3.80823529411764743.237
316023AB2-100 C2
80/20
1.3721.372
316036AC1-147 C
80/20
0.5360.536
316072AD1-144 C
80/20
0.4020.402
316169AC1-164 GEN
Adder
44.9588235294117738.215
316185AD1-033 C
80/20
1.7941.794
316233AE1-074 C
80/20
3.7763.776
316236AE1-162 C
80/20
0.4930.493
316240AF1-291 C
Adder
2.86941176470588262.439
316246AF1-032 C
80/20
0.4130.413
316258AE1-075 C
80/20
0.5030.503
316263AC1-034 C
Adder
8.8741176470588247.543
316274AC1-208 C
Adder
12.4023529411764710.542
316294AC1-161 C
80/20
7.267.26
316305AF2-043 C
80/20
0.5050.505
316313AB2-026 C
80/20
0.5480.548
316315AB2-025 C
80/20
0.5980.598
316316AC1-027 C
80/20
0.460.46
316320Y1-086 C
80/20
0.3190.319
316321Z2-027 C
80/20
0.5270.527
316336AC2-165 C
Adder
13.69411764705882511.64
316365AB2-100 C1
80/20
1.3721.372
316405AF2-144 C
80/20
0.4280.428
316017AA1-139 ULT1
80/20
1.5751.575
316018AA1-139 ULT2
80/20
1.5751.575
316083AB2-161 C
80/20
0.7870.787
316375AC2-012 C
80/20
1.9631.963
316311AC2-079 C
80/20
8.2428.242
316381AD1-082 C
80/20
1.7951.795
316349AD2-085 C
80/20
4.9434.943
316388AE2-253 GEN
80/20
2.8622.862
961611AG1-000B C
Adder
21.72352941176470518.465
941591AE2-156 C
80/20
26.02126.021
944581AF1-123 C
80/20
66.2266.22
944591AF1-124 C
80/20
66.45566.455
944601AF1-125 C
80/20
65.265.2
944631AF1-128 C
Adder
48.040.8
962561AG1-105 C
Adder
11.8176470588235310.045
964241AG1-285 C
Adder
17.89058823529411815.207
3137643SOCKMAN
Adder
1.00.85
934321AD1-056 C
Adder
8.5376470588235297.257
934331AD1-057 C
Adder
4.7623529411764714.048
934501AD1-074 C
Adder
47.763529411764740.599
934511AD1-075 C
Adder
11.94117647058823610.15
934611AD1-087 C
80/20
1.761.76
935161AD1-151 C
Adder
21.46588235294117618.246
937481AD2-202 C
80/20
0.5110.511
938531AE1-072 C
80/20
25.56125.561
939191AE1-149 C
80/20
15.16215.162
940431AE2-027 C
Adder
17.26588235294117614.676
940481AE2-033 C
80/20
23.64823.648
940541AE2-040 C
80/20
4.2084.208
940551AE2-041 C
Adder
7.9588235294117656.765
940641AE2-051 C
80/20
27.30727.307
941101AE2-104 C
80/20
4.8434.843
942461AE2-259 C
Adder
12.70588235294117810.8
943471AF1-018 C
Adder
7.9588235294117656.765
944641AF1-129 C
Adder
134.59058823529412114.402
3150851SPRUNCC
80/20
0.2220.222
3150861SPRUNCD
80/20
0.2220.222
316303AF2-085
80/20
6.3826.382
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1347.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.6437.64
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.68227.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.889122.889
NYPJM->LTFIMP_NY
CLTF
2.4692.469
LGEELTFEXP_LGEE->PJM
CLTF
1.5071.507
WECLTFEXP_WEC->PJM
CLTF
0.7840.784
CPLELTFEXP_CPLE->PJM
CLTF
14.96614.966
TVALTFEXP_TVA->PJM
CLTF
7.5327.532
MECLTFEXP_MEC->PJM
CLTF
4.8064.806
LAGNLTFEXP_LAGN->PJM
CLTF
9.5879.587
SIGELTFEXP_SIGE->PJM
CLTF
0.2960.296

Details for AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.42 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:742.63
MW Contribution:0.91
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.42 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:762.95
MW Contribution:0.98
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
80/20
0.9120.912
961791AG1-021 C
80/20
0.9080.908
961941AG1-037 C
80/20
0.4820.482
964791AG1-342 C
80/20
2.0352.035
966621AG1-532 C
80/20
3.2993.299
313506AB1-173 C OP
80/20
2.2292.229
3138533PONTONDP
80/20
0.3360.336
3144293JTRSVLE
80/20
0.2090.209
3147043LAWRENC
80/20
0.5790.579
3151261ROARAP2
80/20
2.1232.123
3151281ROARAP4
80/20
2.0092.009
3151311EDGECMA
80/20
16.55516.555
3151361ROSEMG1
80/20
3.9363.936
3151371ROSEMS1
80/20
2.4382.438
3151381ROSEMG2
80/20
1.8431.843
3151391GASTONA
80/20
6.1766.176
3151531CLOVER1
80/20
5.8195.819
3151581KERR 1
80/20
0.3080.308
3151591KERR 2
80/20
0.8620.862
3151601KERR 3
80/20
0.8620.862
3151611KERR 4
80/20
0.8620.862
3151621KERR 5
80/20
0.8620.862
934521AD1-076 C
80/20
7.0327.032
943171AE2-346 C
80/20
0.2140.214
959311AF2-222 C
80/20
8.6368.636
960081AF2-299 C
80/20
4.3984.398
3151631KERR 6
80/20
0.8620.862
3151641KERR 7
80/20
0.8620.862
3152661PLYWOOD A
80/20
0.6390.639
3156011CONETOE2SOL
80/20
1.1751.175
3156063AA2-053SOLA
80/20
2.1582.158
316118AC1-105 C
80/20
0.4840.484
316129AC1-054 C
80/20
1.341.34
316131AB2-060 C
80/20
1.0341.034
316140AB2-099 C
80/20
0.0920.092
946281AF1-292 C
80/20
3.6413.641
946301AF1-294 C
80/20
1.8661.866
957481AF2-042 C
80/20
24.31224.312
957861AF2-080 C
80/20
6.8566.856
958211AF2-115 C
80/20
1.1351.135
3151151S HAMPT1
80/20
0.9570.957
3151411GASTONB
80/20
6.1766.176
3152921DOMTR78
80/20
0.8540.854
3156073AA1-063SOLA
80/20
1.8141.814
3156083AA2-088SOLA
80/20
0.9350.935
926071AC1-086 C
80/20
42.49342.493
927021AC1-189 C
80/20
7.5497.549
936261AD2-033 C
80/20
8.0298.029
934621AD1-088 C
80/20
4.4044.404
933981AD1-022 C
80/20
5.6875.687
962571AG1-106 C
80/20
5.4965.496
316005AA1-067 C
80/20
0.2210.221
316011AB1-132 C OP
80/20
4.7154.715
316023AB2-100 C2
80/20
2.7732.773
316034AC1-036 C
80/20
0.1240.124
316049AB1-081 C OP
80/20
1.4941.494
316210AC1-098 C
80/20
1.0991.099
316212AC1-099 C
80/20
0.3680.368
316237AB2-079 C O1
80/20
0.2290.229
316238AB2-078 C O1
80/20
0.2290.229
316239AB2-077 C O1
80/20
0.2290.229
316263AC1-034 C
80/20
6.9816.981
316274AC1-208 C
80/20
11.22611.226
316317KELFORD C
80/20
0.370.37
316318V4-068 C
80/20
0.0750.075
316319Z2-044 C
80/20
0.2310.231
316365AB2-100 C1
80/20
2.7732.773
3156021HOLLOMANSOL
80/20
1.5861.586
316327AA2-057 C
80/20
1.4891.489
316181AB2-040 GEN
80/20
2.5112.511
313527AB2-043 C
80/20
0.3630.363
316359AB2-059 C OP
80/20
1.7611.761
316174AB2-169_C
80/20
0.7190.719
316087AB2-174 C
80/20
2.4642.464
962561AG1-105 C
80/20
5.2875.287
964241AG1-285 C
80/20
7.2257.225
3137643SOCKMAN
80/20
1.2371.237
932631AC2-084 C
80/20
1.171.17
934321AD1-056 C
80/20
9.2019.201
934331AD1-057 C
80/20
5.1335.133
934501AD1-074 C
80/20
19.36119.361
934511AD1-075 C
80/20
4.844.84
940481AE2-033 C
80/20
63.40763.407
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1882.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.20711.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.5767.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.15434.154
NYPJM->LTFIMP_NY
CLTF
0.3660.366
LGEELTFEXP_LGEE->PJM
CLTF
0.4310.431
WECLTFEXP_WEC->PJM
CLTF
0.2290.229
CPLELTFEXP_CPLE->PJM
CLTF
4.5894.589
TVALTFEXP_TVA->PJM
CLTF
2.0182.018
MECLTFEXP_MEC->PJM
CLTF
1.3611.361
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
SIGELTFEXP_SIGE->PJM
CLTF
0.0840.084
CONTINGENCY 'DVP_P4-2: 511T556_SRT-S-1'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 556_SRT-S-3'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
END
314677 to 314747 ckt 1
314282 to 314285 ckt 1
314285 to 314316 ckt 1
314563 to 940480 ckt 1
314692 to 314677 ckt 1
314435 to 314282 ckt 1
314902 to 314282 ckt 2
314914 to 314918 ckt 1
940480 to 314435 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
DVP_P4-6: CHASE C T342_SRT-A
BreakerAC126.04 %221.4C279.058.92
GD1DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P4-6: CHASE C T342_SRT-A
BreakerAC165.99 %208.7C346.4111.07
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC100.89 %984.18B992.940.64
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 246_SRT-A
SingleAC108.46 %678.68B736.130.63
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Base Case
SingleAC102.72 %678.68A697.110.59
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.8 %3220.44B3342.681.83
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC119.82 %3220.44B3858.592.4
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC111.38 %3220.44B3586.781.44
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
SingleAC111.09 %3220.44B3577.611.5
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC110.41 %3940.0C4350.172.76
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H1T594_SRT-S
BreakerAC106.75 %3940.0C4205.812.67
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC116.97 %3220.44B3767.031.61
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC114.22 %3220.44B3678.491.72
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC111.99 %3940.0C4412.363.11
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC106.7 %4070.2B4342.972.64
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC102.59 %4070.2B4175.622.64
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC121.18 %3220.44B3902.621.58
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC120.07 %3220.44B3866.791.7
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC117.55 %3940.0C4631.323.07
GD1DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC104.04 %4070.2B4234.72.31

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-6: CHASE C T342_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.04 %
Rating:221.4 MVA
Rating Type:C
MVA to Mitigate:279.05
MW Contribution:8.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
4.8164.816
961792AG1-021 E
50/50
4.1034.103
3138533PONTONDP
50/50
1.7841.784
3144293JTRSVLE
50/50
1.1041.104
3147133PAMPLIN
50/50
2.6642.664
959311AF2-222 C
50/50
44.59344.593
959312AF2-222 E
50/50
29.87729.877
316131AB2-060 C
50/50
3.953.95
924162AB2-060 E OP
50/50
11.41611.416
925612AC1-036 E
50/50
2.2972.297
946301AF1-294 C
50/50
9.99.9
946302AF1-294 E
50/50
8.3838.383
958211AF2-115 C
50/50
6.026.02
958212AF2-115 E
50/50
5.1285.128
3147223TWITTYS
50/50
2.5462.546
936261AD2-033 C
50/50
34.78234.782
936262AD2-033 E
50/50
23.18823.188
316034AC1-036 C
50/50
0.6250.625
964241AG1-285 C
50/50
33.44533.445
964242AG1-285 E
50/50
22.29622.296
942461AE2-259 C
50/50
26.75626.756
942462AE2-259 E
50/50
17.83717.837
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0180.018
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0140.014
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0190.019
NYPJM->LTFIMP_NY
CLTF
0.010.01
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0380.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0110.011
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0060.006
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0470.047
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.010.01
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0320.032
O66PJM->LTFIMP_O-066
CMTX_NF
0.1230.123
MDUPJM->LTFIMP_MDU
CLTF
0.0020.002

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-6: CHASE C T342_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.99 %
Rating:208.7 MVA
Rating Type:C
MVA to Mitigate:346.41
MW Contribution:11.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
5.985.98
961792AG1-021 E
50/50
5.0945.094
3138533PONTONDP
50/50
2.2152.215
3144293JTRSVLE
50/50
1.371.37
3147133PAMPLIN
50/50
3.3083.308
959311AF2-222 C
50/50
55.36655.366
959312AF2-222 E
50/50
37.09537.095
316131AB2-060 C
50/50
4.9054.905
924162AB2-060 E OP
50/50
14.17414.174
925612AC1-036 E
50/50
2.8512.851
946301AF1-294 C
50/50
12.29112.291
946302AF1-294 E
50/50
10.40910.409
958211AF2-115 C
50/50
7.4747.474
958212AF2-115 E
50/50
6.3676.367
3147223TWITTYS
50/50
3.1613.161
936261AD2-033 C
50/50
43.18643.186
936262AD2-033 E
50/50
28.7928.79
316034AC1-036 C
50/50
0.7760.776
964241AG1-285 C
50/50
41.52541.525
964242AG1-285 E
50/50
27.68327.683
942461AE2-259 C
50/50
33.2233.22
942462AE2-259 E
50/50
22.14722.147
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0230.023
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0170.017
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0240.024
NYPJM->LTFIMP_NY
CLTF
0.0120.012
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0470.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0130.013
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0080.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0580.058
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0130.013
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0390.039
O66PJM->LTFIMP_O-066
CMTX_NF
0.1520.152
MDUPJM->LTFIMP_MDU
CLTF
0.0020.002

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.89 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:992.94
MW Contribution:0.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
80/20
0.4820.482
961791AG1-021 C
Adder
0.640.544
961941AG1-037 C
80/20
0.2370.237
963041AG1-153 C
80/20
3.0443.044
964791AG1-342 C
80/20
1.5971.597
966621AG1-532 C
80/20
1.041.04
313506AB1-173 C OP
80/20
0.7570.757
3138533PONTONDP
Adder
0.237647058823529430.202
3147043LAWRENC
80/20
0.2030.203
3151261ROARAP2
80/20
0.8190.819
3151281ROARAP4
80/20
0.7750.775
3151311EDGECMA
80/20
8.3398.339
3151361ROSEMG1
80/20
1.3551.355
3151371ROSEMS1
80/20
0.8390.839
3151381ROSEMG2
80/20
0.6340.634
3151391GASTONA
80/20
2.0712.071
3151531CLOVER1
80/20
6.056.05
3151541CLOVER2
80/20
5.9935.993
3151581KERR 1
80/20
0.1980.198
3151591KERR 2
80/20
0.5540.554
3151601KERR 3
80/20
0.5540.554
3151611KERR 4
80/20
0.5540.554
3151621KERR 5
80/20
0.5540.554
934521AD1-076 C
80/20
4.8074.807
943171AE2-346 C
80/20
0.1050.105
944011AF1-069 C
80/20
7.217.21
959311AF2-222 C
80/20
6.6486.648
960081AF2-299 C
80/20
1.3861.386
3151631KERR 6
80/20
0.5540.554
3151641KERR 7
80/20
0.5540.554
3152661PLYWOOD A
80/20
0.5410.541
3156011CONETOE2SOL
80/20
0.6290.629
3156063AA2-053SOLA
80/20
0.860.86
316118AC1-105 C
80/20
0.4080.408
316129AC1-054 C
80/20
0.6480.648
316131AB2-060 C
80/20
0.680.68
316140AB2-099 C
80/20
0.0450.045
940491AE2-034 C
80/20
0.4170.417
941031AE2-094 C
80/20
22.06822.068
946281AF1-292 C
80/20
1.1471.147
946301AF1-294 C
Adder
1.3164705882352941.119
957481AF2-042 C
80/20
26.38726.387
957861AF2-080 C
80/20
3.7723.772
958211AF2-115 C
Adder
0.80.68
938771AE1-103 C
Adder
0.96705882352941170.822
3151021BRUNSWICKG1
80/20
4.4774.477
3151031BRUNSWICKG2
80/20
4.4774.477
3151041BRUNSWICKG3
80/20
4.4774.477
3151051BRUNSWICKS1
80/20
9.3029.302
3151151S HAMPT1
80/20
0.570.57
3151411GASTONB
80/20
2.0712.071
3152411Z1-086 GT1
80/20
5.755.75
3152421Z1-086 GT2
80/20
5.7485.748
3152431Z1-086 GT3
80/20
5.7485.748
3152441Z1-086 ST
80/20
10.00810.008
3152921DOMTR78
80/20
0.5570.557
3156073AA1-063SOLA
80/20
0.7530.753
3156083AA2-088SOLA
80/20
0.4670.467
942001AE2-212 C
Adder
-3.9329411764705884-3.343
926071AC1-086 C
80/20
14.30114.301
927021AC1-189 C
80/20
4.1534.153
936261AD2-033 C
80/20
5.4245.424
934621AD1-088 C
80/20
4.424.42
939411AE1-173 C
80/20
41.75841.758
933981AD1-022 C
80/20
3.5783.578
962571AG1-106 C
80/20
1.851.85
316003AC1-222 C
80/20
0.4260.426
316005AA1-067 C
80/20
0.1280.128
316011AB1-132 C OP
80/20
1.5811.581
316023AB2-100 C2
80/20
0.7990.799
316034AC1-036 C
80/20
0.0950.095
316049AB1-081 C OP
80/20
0.7570.757
316210AC1-098 C
80/20
0.50.5
316212AC1-099 C
80/20
0.1680.168
316222AC1-221 C
80/20
0.6320.632
316237AB2-079 C O1
80/20
0.1510.151
316238AB2-078 C O1
80/20
0.1510.151
316239AB2-077 C O1
80/20
0.1510.151
316240AF1-291 C
Adder
-1.6611764705882353-1.412
316248AF1-058 C
80/20
0.140.14
316263AC1-034 C
80/20
3.5493.549
316274AC1-208 C
80/20
4.9624.962
316283AC2-100 C
80/20
0.510.51
316315AB2-025 C
80/20
0.4250.425
316317KELFORD C
80/20
0.1760.176
316318V4-068 C
80/20
0.0370.037
316319Z2-044 C
80/20
0.1130.113
316365AB2-100 C1
80/20
0.7990.799
3156021HOLLOMANSOL
80/20
0.830.83
316327AA2-057 C
80/20
0.7010.701
315614AA2-178 C
80/20
0.5670.567
316181AB2-040 GEN
80/20
0.8530.853
313527AB2-043 C
80/20
0.2380.238
316359AB2-059 C OP
80/20
0.8920.892
316174AB2-169_C
80/20
0.4490.449
316087AB2-174 C
80/20
0.8150.815
962561AG1-105 C
80/20
4.0224.022
964241AG1-285 C
80/20
5.5515.551
3137643SOCKMAN
80/20
0.4490.449
932631AC2-084 C
80/20
0.5330.533
934321AD1-056 C
80/20
3.7443.744
934331AD1-057 C
80/20
2.0892.089
934501AD1-074 C
80/20
13.23613.236
934511AD1-075 C
80/20
3.3093.309
934611AD1-087 C
80/20
0.5960.596
935171AD1-152 C
80/20
0.620.62
937481AD2-202 C
80/20
0.1730.173
940481AE2-033 C
80/20
16.46516.465
940541AE2-040 C
80/20
2.9992.999
940641AE2-051 C
80/20
9.0359.035
944641AF1-129 C
Adder
-92.12117647058824-78.303
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.6422.642
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.95317.953
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.57311.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.16446.164
NYPJM->LTFIMP_NY
CLTF
0.5840.584
LGEELTFEXP_LGEE->PJM
CLTF
0.6950.695
WECLTFEXP_WEC->PJM
CLTF
0.3670.367
CPLELTFEXP_CPLE->PJM
CLTF
5.5395.539
TVALTFEXP_TVA->PJM
CLTF
3.0473.047
MECLTFEXP_MEC->PJM
CLTF
2.1342.134
LAGNLTFEXP_LAGN->PJM
CLTF
3.8673.867
SIGELTFEXP_SIGE->PJM
CLTF
0.1330.133

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:736.13
MW Contribution:0.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
80/20
1.1061.106
961791AG1-021 C
80/20
0.6320.632
961941AG1-037 C
80/20
0.6420.642
964791AG1-342 C
80/20
1.4341.434
966621AG1-532 C
80/20
3.4243.424
313506AB1-173 C OP
80/20
2.3432.343
3138533PONTONDP
80/20
0.2340.234
3144293JTRSVLE
80/20
0.1450.145
3147043LAWRENC
80/20
0.5880.588
3151261ROARAP2
80/20
2.2952.295
3151281ROARAP4
80/20
2.1722.172
3151311EDGECMA
80/20
19.08119.081
3151361ROSEMG1
80/20
4.2844.284
3151371ROSEMS1
80/20
2.6542.654
3151381ROSEMG2
80/20
2.0062.006
3151391GASTONA
80/20
6.76.7
3151581KERR 1
80/20
0.2540.254
3151591KERR 2
80/20
0.7120.712
3151601KERR 3
80/20
0.7120.712
3151611KERR 4
80/20
0.7120.712
3151621KERR 5
80/20
0.7120.712
934521AD1-076 C
80/20
10.18310.183
943171AE2-346 C
80/20
0.2840.284
959311AF2-222 C
80/20
7.5547.554
960081AF2-299 C
80/20
4.5664.566
3151631KERR 6
80/20
0.7120.712
3151641KERR 7
80/20
0.7120.712
3152661PLYWOOD A
80/20
0.3910.391
3156011CONETOE2SOL
80/20
1.4481.448
3156063AA2-053SOLA
80/20
2.4062.406
316118AC1-105 C
80/20
0.3030.303
316129AC1-054 C
80/20
1.321.32
316131AB2-060 C
80/20
0.8840.884
316140AB2-099 C
80/20
0.1220.122
940491AE2-034 C
80/20
0.7340.734
946281AF1-292 C
80/20
3.783.78
946301AF1-294 C
80/20
1.31.3
957861AF2-080 C
80/20
8.6988.698
958211AF2-115 C
80/20
0.790.79
938771AE1-103 C
80/20
1.2731.273
3151151S HAMPT1
80/20
1.0351.035
3151411GASTONB
80/20
6.76.7
3152921DOMTR78
80/20
1.2081.208
3156073AA1-063SOLA
80/20
1.9821.982
3156083AA2-088SOLA
80/20
1.0451.045
3156116Z1-036WIND
80/20
0.2510.251
926071AC1-086 C
80/20
46.26846.268
927021AC1-189 C
80/20
9.5779.577
936261AD2-033 C
80/20
6.4546.454
933981AD1-022 C
80/20
8.3538.353
962571AG1-106 C
80/20
5.9855.985
316005AA1-067 C
80/20
0.2960.296
316011AB1-132 C OP
80/20
5.1165.116
316023AB2-100 C2
80/20
2.8782.878
316034AC1-036 C
80/20
0.110.11
316049AB1-081 C OP
80/20
1.7151.715
316210AC1-098 C
80/20
1.2971.297
316212AC1-099 C
80/20
0.4340.434
316237AB2-079 C O1
80/20
0.1950.195
316238AB2-078 C O1
80/20
0.1950.195
316239AB2-077 C O1
80/20
0.1950.195
316263AC1-034 C
80/20
8.0388.038
316274AC1-208 C
80/20
12.83612.836
316317KELFORD C
80/20
0.4780.478
316318V4-068 C
80/20
0.090.09
316319Z2-044 C
80/20
0.2660.266
316365AB2-100 C1
80/20
2.8782.878
3156021HOLLOMANSOL
80/20
2.3822.382
316327AA2-057 C
80/20
1.711.71
315614AA2-178 C
80/20
0.9970.997
316181AB2-040 GEN
80/20
2.6392.639
313527AB2-043 C
80/20
0.3120.312
316359AB2-059 C OP
80/20
2.0212.021
316174AB2-169_C
80/20
0.9970.997
316087AB2-174 C
80/20
2.5762.576
962561AG1-105 C
80/20
3.8843.884
964241AG1-285 C
80/20
7.0017.001
3137643SOCKMAN
80/20
1.3221.322
932631AC2-084 C
80/20
1.3811.381
934321AD1-056 C
80/20
10.25810.258
934331AD1-057 C
80/20
5.7225.722
934501AD1-074 C
80/20
28.03828.038
934511AD1-075 C
80/20
7.017.01
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5172.517
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.04115.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.5619.561
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.76439.764
NYPJM->LTFIMP_NY
CLTF
0.4240.424
LGEELTFEXP_LGEE->PJM
CLTF
0.5780.578
WECLTFEXP_WEC->PJM
CLTF
0.3070.307
CPLELTFEXP_CPLE->PJM
CLTF
5.2785.278
TVALTFEXP_TVA->PJM
CLTF
2.5052.505
MECLTFEXP_MEC->PJM
CLTF
1.7731.773
LAGNLTFEXP_LAGN->PJM
CLTF
3.1853.185
SIGELTFEXP_SIGE->PJM
CLTF
0.1110.111

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.72 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:697.11
MW Contribution:0.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
80/20
0.9040.904
961791AG1-021 C
80/20
0.5880.588
961941AG1-037 C
80/20
0.480.48
964791AG1-342 C
80/20
1.3141.314
966621AG1-532 C
80/20
3.2633.263
313506AB1-173 C OP
80/20
2.1872.187
3138533PONTONDP
80/20
0.2180.218
3144293JTRSVLE
80/20
0.1350.135
3147043LAWRENC
80/20
0.5590.559
3151261ROARAP2
80/20
2.0652.065
3151281ROARAP4
80/20
1.9541.954
3151311EDGECMA
80/20
16.35316.353
3151361ROSEMG1
80/20
3.9083.908
3151371ROSEMS1
80/20
2.422.42
3151381ROSEMG2
80/20
1.831.83
3151391GASTONA
80/20
6.1336.133
3151581KERR 1
80/20
0.230.23
3151591KERR 2
80/20
0.6440.644
3151601KERR 3
80/20
0.6440.644
3151611KERR 4
80/20
0.6440.644
3151621KERR 5
80/20
0.6440.644
934521AD1-076 C
80/20
7.217.21
943171AE2-346 C
80/20
0.2130.213
959311AF2-222 C
80/20
7.0127.012
960081AF2-299 C
80/20
4.3514.351
3151631KERR 6
80/20
0.6440.644
3151641KERR 7
80/20
0.6440.644
3156011CONETOE2SOL
80/20
1.1621.162
3156063AA2-053SOLA
80/20
2.1042.104
316129AC1-054 C
80/20
1.1891.189
316131AB2-060 C
80/20
0.820.82
316140AB2-099 C
80/20
0.0910.091
940491AE2-034 C
80/20
0.5370.537
946281AF1-292 C
80/20
3.6023.602
946301AF1-294 C
80/20
1.2081.208
957861AF2-080 C
80/20
6.8156.815
958211AF2-115 C
80/20
0.7340.734
938771AE1-103 C
80/20
1.2791.279
3151151S HAMPT1
80/20
0.9570.957
3151411GASTONB
80/20
6.1336.133
3152921DOMTR78
80/20
0.8660.866
3156073AA1-063SOLA
80/20
1.7721.772
3156083AA2-088SOLA
80/20
0.9250.925
3156116Z1-036WIND
80/20
0.2010.201
926071AC1-086 C
80/20
42.34842.348
927021AC1-189 C
80/20
7.5047.504
936261AD2-033 C
80/20
5.9895.989
933981AD1-022 C
80/20
5.7955.795
962571AG1-106 C
80/20
5.4785.478
316005AA1-067 C
80/20
0.220.22
316011AB1-132 C OP
80/20
4.6834.683
316023AB2-100 C2
80/20
2.7652.765
316034AC1-036 C
80/20
0.1020.102
316049AB1-081 C OP
80/20
1.4681.468
316210AC1-098 C
80/20
1.0791.079
316212AC1-099 C
80/20
0.3610.361
316237AB2-079 C O1
80/20
0.1810.181
316238AB2-078 C O1
80/20
0.1810.181
316239AB2-077 C O1
80/20
0.1810.181
316263AC1-034 C
80/20
6.8836.883
316274AC1-208 C
80/20
11.02211.022
316315AB2-025 C
80/20
1.6631.663
316317KELFORD C
80/20
0.3660.366
316318V4-068 C
80/20
0.0740.074
316319Z2-044 C
80/20
0.2270.227
316365AB2-100 C1
80/20
2.7652.765
3156021HOLLOMANSOL
80/20
1.5911.591
316327AA2-057 C
80/20
1.461.46
315614AA2-178 C
80/20
0.7290.729
316181AB2-040 GEN
80/20
2.4632.463
313527AB2-043 C
80/20
0.290.29
316359AB2-059 C OP
80/20
1.731.73
316174AB2-169_C
80/20
0.7240.724
316087AB2-174 C
80/20
2.4212.421
962561AG1-105 C
80/20
3.5683.568
964241AG1-285 C
80/20
6.4946.494
3137643SOCKMAN
80/20
1.2121.212
932631AC2-084 C
80/20
1.1481.148
934321AD1-056 C
80/20
9.1359.135
934331AD1-057 C
80/20
5.0965.096
934501AD1-074 C
80/20
19.85319.853
934511AD1-075 C
80/20
4.9634.963
940481AE2-033 C
80/20
63.69463.694
940541AE2-040 C
80/20
11.74711.747
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.0622.062
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.06512.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.7657.765
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
32.61632.616
NYPJM->LTFIMP_NY
CLTF
0.370.37
LGEELTFEXP_LGEE->PJM
CLTF
0.4650.465
WECLTFEXP_WEC->PJM
CLTF
0.2460.246
CPLELTFEXP_CPLE->PJM
CLTF
4.3234.323
TVALTFEXP_TVA->PJM
CLTF
2.0422.042
MECLTFEXP_MEC->PJM
CLTF
1.4321.432
LAGNLTFEXP_LAGN->PJM
CLTF
2.5962.596
SIGELTFEXP_SIGE->PJM
CLTF
0.0890.089

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.8 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3342.68
MW Contribution:1.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
1.2482352941176471.061
961791AG1-021 C
Adder
1.82588235294117651.552
961941AG1-037 C
80/20
0.6730.673
963041AG1-153 C
80/20
9.1419.141
964791AG1-342 C
Adder
4.4317647058823533.767
966621AG1-532 C
80/20
1.8631.863
313506AB1-173 C OP
80/20
1.4941.494
3138533PONTONDP
Adder
0.6764705882352940.575
3147043LAWRENC
80/20
0.3980.398
3151261ROARAP2
80/20
1.8341.834
3151281ROARAP4
80/20
1.7351.735
3151311EDGECMA
Adder
20.58941176470588317.501
3151361ROSEMG1
80/20
2.7122.712
3151371ROSEMS1
80/20
1.681.68
3151381ROSEMG2
80/20
1.271.27
3151391GASTONA
80/20
4.0664.066
3151531CLOVER1
80/20
17.9517.95
3151541CLOVER2
80/20
17.78217.782
934521AD1-076 C
80/20
16.37216.372
943171AE2-346 C
80/20
0.2980.298
944011AF1-069 C
80/20
21.71321.713
959311AF2-222 C
Adder
18.28823529411764815.545
960081AF2-299 C
80/20
2.4842.484
3156063AA2-053SOLA
80/20
1.9981.998
316129AC1-054 C
80/20
1.5891.589
316140AB2-099 C
80/20
0.1280.128
940491AE2-034 C
80/20
1.5381.538
941031AE2-094 C
80/20
66.45566.455
946281AF1-292 C
80/20
2.0562.056
946301AF1-294 C
Adder
3.75411764705882333.191
957481AF2-042 C
80/20
78.71578.715
957861AF2-080 C
Adder
10.167058823529418.642
958211AF2-115 C
Adder
2.28235294117647051.94
938771AE1-103 C
80/20
3.8693.869
313526AB2-022 C
80/20
0.5040.504
3150921YORKTN3
Adder
127.84235294117647108.666
942341AE2-247 C
80/20
1.881.88
943461AF1-017 C
80/20
1.7011.701
3150981CHESPKA
80/20
0.5780.578
3150991CHESPKB
80/20
0.9580.958
3151021BRUNSWICKG1
80/20
13.44613.446
3151031BRUNSWICKG2
80/20
13.44613.446
3151041BRUNSWICKG3
80/20
13.44613.446
3151051BRUNSWICKS1
80/20
27.93627.936
3151081ELIZAR1
80/20
4.2584.258
3151091ELIZAR2
80/20
4.1834.183
3151101ELIZAR3
80/20
4.3114.311
3151151S HAMPT1
80/20
1.9741.974
3151411GASTONB
80/20
4.0664.066
3152331SURRY 2
80/20
30.82730.827
3152411Z1-086 GT1
80/20
17.28117.281
3152421Z1-086 GT2
80/20
17.27717.277
3152431Z1-086 GT3
80/20
17.27717.277
3152441Z1-086 ST
80/20
30.08130.081
3152921DOMTR78
80/20
1.8181.818
3156056W1-029WIND
80/20
1.0361.036
3156073AA1-063SOLA
80/20
1.8611.861
3156083AA2-088SOLA
80/20
1.4051.405
3156116Z1-036WIND
80/20
0.8770.877
942001AE2-212 C
Adder
2.11411764705882371.797
957871AF2-081 C
80/20
13.4313.43
958161AF2-110 C
80/20
1.7981.798
926071AC1-086 C
80/20
28.07728.077
927021AC1-189 C
Adder
11.1952941176470599.516
936261AD2-033 C
Adder
14.72470588235294112.516
933291AC2-141 C
80/20
41.90441.904
934621AD1-088 C
80/20
13.20613.206
939411AE1-173 C
80/20
144.1144.1
916191Z1-068 C
80/20
0.0580.058
933981AD1-022 C
80/20
11.71411.714
962571AG1-106 C
80/20
3.6323.632
316011AB1-132 C OP
80/20
3.1053.105
316023AB2-100 C2
80/20
1.2911.291
316036AC1-147 C
80/20
0.4890.489
316072AD1-144 C
80/20
0.3590.359
316185AD1-033 C
80/20
1.6481.648
316210AC1-098 C
80/20
1.251.25
316212AC1-099 C
80/20
0.4180.418
316246AF1-032 C
80/20
0.3780.378
316263AC1-034 C
Adder
8.8035294117647057.483
316274AC1-208 C
80/20
11.98411.984
316294AC1-161 C
80/20
6.8246.824
316305AF2-043 C
80/20
0.4630.463
316315AB2-025 C
80/20
0.5580.558
316316AC1-027 C
80/20
0.4210.421
316317KELFORD C
80/20
0.4760.476
316318V4-068 C
80/20
0.1070.107
316320Y1-086 C
80/20
0.2940.294
316321Z2-027 C
80/20
0.4860.486
316365AB2-100 C1
80/20
1.2911.291
3156021HOLLOMANSOL
80/20
2.4482.448
316017AA1-139 ULT1
80/20
1.4491.449
316018AA1-139 ULT2
80/20
1.4491.449
315614AA2-178 C
80/20
2.0912.091
316181AB2-040 GEN
80/20
1.6831.683
316174AB2-169_C
80/20
1.3931.393
316087AB2-174 C
80/20
1.561.56
316375AC2-012 C
80/20
1.7911.791
316311AC2-079 C
80/20
7.2667.266
316349AD2-085 C
80/20
4.3374.337
316388AE2-253 GEN
80/20
2.6322.632
961611AG1-000B C
Adder
17.0670588235294114.507
941591AE2-156 C
80/20
23.83823.838
944581AF1-123 C
80/20
61.95761.957
944591AF1-124 C
80/20
62.17762.177
944601AF1-125 C
80/20
61.00261.002
962561AG1-105 C
Adder
11.0694117647058839.409
964241AG1-285 C
Adder
14.80352941176470712.583
3137643SOCKMAN
80/20
0.9470.947
932631AC2-084 C
80/20
1.3311.331
934321AD1-056 C
Adder
8.332941176470597.083
934331AD1-057 C
Adder
4.6482352941176473.951
934501AD1-074 C
80/20
45.0845.08
934511AD1-075 C
80/20
11.2711.27
934611AD1-087 C
80/20
1.7671.767
935161AD1-151 C
Adder
15.27058823529411812.98
935171AD1-152 C
80/20
1.8271.827
936161AD2-022 C
Adder
9.455294117647068.037
936171AD2-023 C
Adder
5.5152941176470584.688
937481AD2-202 C
80/20
0.5130.513
938531AE1-072 C
80/20
23.60823.608
939191AE1-149 C
Adder
11.99058823529411710.192
940431AE2-027 C
Adder
11.395294117647069.686
940481AE2-033 C
80/20
22.18122.181
940541AE2-040 C
80/20
3.9443.944
940641AE2-051 C
80/20
28.76428.764
941101AE2-104 C
80/20
4.4074.407
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.597.59
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.0655.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.38335.383
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
135.46135.46
NYPJM->LTFIMP_NY
CLTF
2.5592.559
LGEELTFEXP_LGEE->PJM
CLTF
2.182.18
WECLTFEXP_WEC->PJM
CLTF
1.1331.133
CPLELTFEXP_CPLE->PJM
CLTF
15.91315.913
TVALTFEXP_TVA->PJM
CLTF
9.319.31
MECLTFEXP_MEC->PJM
CLTF
6.566.56
LAGNLTFEXP_LAGN->PJM
CLTF
11.74411.744
SIGELTFEXP_SIGE->PJM
CLTF
0.4150.415

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.82 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3858.59
MW Contribution:2.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
1.34941176470588231.147
961791AG1-021 C
Adder
2.40470588235294122.044
961941AG1-037 C
Adder
0.74470588235294120.633
963041AG1-153 C
80/20
8.7798.779
964791AG1-342 C
Adder
4.884.148
966621AG1-532 C
Adder
2.06235294117647071.753
3138533PONTONDP
Adder
0.89058823529411770.757
3151311EDGECMA
Adder
22.1658823529411818.841
3151531CLOVER1
80/20
18.57418.574
3151541CLOVER2
80/20
18.418.4
934521AD1-076 C
Adder
18.1705882352941215.445
944011AF1-069 C
80/20
20.63520.635
959311AF2-222 C
Adder
22.66470588235294419.265
960081AF2-299 C
Adder
2.74941176470588242.337
941031AE2-094 C
80/20
63.15563.155
946281AF1-292 C
Adder
2.2752941176470591.934
946301AF1-294 C
Adder
4.9423529411764714.201
957481AF2-042 C
80/20
80.37380.373
957861AF2-080 C
Adder
11.0270588235294129.373
958211AF2-115 C
Adder
3.0058823529411772.555
938771AE1-103 C
80/20
4.3814.381
313526AB2-022 C
80/20
0.5650.565
3150601CHESTF5
Adder
83.0647058823529570.605
3150651CHESTF6
Adder
26.27176470588235422.331
3150731STONECA
Adder
9.5788235294117648.142
3150831SPRUNCA
80/20
13.15813.158
3150841SPRUNCB
80/20
13.15813.158
3150921YORKTN3
Adder
165.5670588235294140.732
942341AE2-247 C
80/20
2.2382.238
943461AF1-017 C
80/20
2.0242.024
3150981CHESPKA
80/20
0.6560.656
3150991CHESPKB
80/20
1.0871.087
3151021BRUNSWICKG1
80/20
12.91412.914
3151031BRUNSWICKG2
80/20
12.91412.914
3151041BRUNSWICKG3
80/20
12.91412.914
3151051BRUNSWICKS1
80/20
26.8326.83
3151081ELIZAR1
80/20
4.824.82
3151091ELIZAR2
80/20
4.7354.735
3151101ELIZAR3
80/20
4.8814.881
3151161SURRY 1
80/20
35.54335.543
3151191GRAVEL3
80/20
3.6113.611
3151201GRAVEL4
80/20
3.6573.657
3151211GRAVEL5
80/20
3.6113.611
3151221GRAVEL6
80/20
3.6533.653
3152331SURRY 2
80/20
35.95635.956
3152411Z1-086 GT1
80/20
16.54216.542
3152421Z1-086 GT2
80/20
16.53816.538
3152431Z1-086 GT3
80/20
16.53816.538
3152441Z1-086 ST
80/20
28.79528.795
3156056W1-029WIND
80/20
1.1641.164
3156116Z1-036WIND
80/20
0.9810.981
957601AF2-054 C
Adder
2.53058823529411742.151
942001AE2-212 C
80/20
3.1513.151
957871AF2-081 C
80/20
15.07515.075
958161AF2-110 C
80/20
2.0582.058
926071AC1-086 C
Adder
30.83882352941176626.213
927021AC1-189 C
Adder
12.14117647058823710.32
936261AD2-033 C
Adder
17.81058823529411615.139
933291AC2-141 C
80/20
46.08646.086
934621AD1-088 C
80/20
14.01914.019
939411AE1-173 C
80/20
143.49143.49
916191Z1-068 C
80/20
0.0660.066
933981AD1-022 C
Adder
12.98823529411764711.04
962571AG1-106 C
Adder
3.98941176470588273.391
316023AB2-100 C2
80/20
1.4231.423
316036AC1-147 C
80/20
0.5540.554
316072AD1-144 C
80/20
0.4180.418
316169AC1-164 GEN
Adder
49.0282352941176541.674
316185AD1-033 C
80/20
1.8511.851
316233AE1-074 C
80/20
3.9163.916
316236AE1-162 C
80/20
0.5140.514
316240AF1-291 C
Adder
3.0682352941176472.608
316246AF1-032 C
80/20
0.4280.428
316258AE1-075 C
80/20
0.5130.513
316263AC1-034 C
Adder
9.488.058
316274AC1-208 C
Adder
13.08588235294117711.123
316294AC1-161 C
80/20
7.5057.505
316305AF2-043 C
80/20
0.5240.524
316313AB2-026 C
80/20
0.5590.559
316315AB2-025 C
80/20
0.6170.617
316316AC1-027 C
80/20
0.4760.476
316320Y1-086 C
80/20
0.330.33
316321Z2-027 C
80/20
0.5460.546
316336AC2-165 C
Adder
14.04941176470588411.942
316365AB2-100 C1
80/20
1.4231.423
316405AF2-144 C
80/20
0.4360.436
316017AA1-139 ULT1
80/20
1.6261.626
316018AA1-139 ULT2
80/20
1.6261.626
316083AB2-161 C
80/20
0.8230.823
316375AC2-012 C
80/20
2.0322.032
316311AC2-079 C
80/20
8.6058.605
316381AD1-082 C
80/20
1.8751.875
316349AD2-085 C
80/20
5.1625.162
316388AE2-253 GEN
80/20
2.9552.955
961611AG1-000B C
Adder
22.90588235294117719.47
941591AE2-156 C
80/20
27.03327.033
944581AF1-123 C
80/20
68.97668.976
944591AF1-124 C
80/20
69.22169.221
944601AF1-125 C
80/20
67.91467.914
944631AF1-128 C
Adder
51.9752941176470644.179
962561AG1-105 C
Adder
12.25882352941176610.42
964241AG1-285 C
Adder
17.31176470588235414.715
3137643SOCKMAN
Adder
1.04352941176470580.887
934321AD1-056 C
Adder
9.0458823529411777.689
934331AD1-057 C
Adder
5.04588235294117654.289
934501AD1-074 C
Adder
50.0317647058823542.527
934511AD1-075 C
Adder
12.50823529411764710.632
935161AD1-151 C
Adder
22.80117647058823519.381
938531AE1-072 C
80/20
26.49826.498
939191AE1-149 C
80/20
15.94215.942
940431AE2-027 C
Adder
18.39647058823529615.637
940481AE2-033 C
80/20
24.49624.496
940541AE2-040 C
80/20
4.3564.356
940551AE2-041 C
Adder
8.4917647058823537.218
940641AE2-051 C
80/20
27.74527.745
941101AE2-104 C
80/20
5.0455.045
942461AE2-259 C
Adder
12.99058823529411711.042
943471AF1-018 C
Adder
8.4917647058823537.218
944641AF1-129 C
Adder
144.29529411764705122.651
3150851SPRUNCC
80/20
0.2360.236
3150861SPRUNCD
80/20
0.2360.236
316303AF2-085
80/20
6.4786.478
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.9747.974
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.12565.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.22440.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
144.491144.491
NYPJM->LTFIMP_NY
CLTF
3.1863.186
LGEELTFEXP_LGEE->PJM
CLTF
2.5932.593
WECLTFEXP_WEC->PJM
CLTF
1.3381.338
CPLELTFEXP_CPLE->PJM
CLTF
16.71416.714
TVALTFEXP_TVA->PJM
CLTF
10.46710.467
MECLTFEXP_MEC->PJM
CLTF
7.6237.623
LAGNLTFEXP_LAGN->PJM
CLTF
13.13513.135
SIGELTFEXP_SIGE->PJM
CLTF
0.4870.487

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.38 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3586.78
MW Contribution:1.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.69647058823529410.592
961791AG1-021 C
80/20
1.4371.437
961941AG1-037 C
Adder
0.37294117647058830.317
963041AG1-153 C
80/20
5.1375.137
964791AG1-342 C
Adder
2.77294117647058872.357
966621AG1-532 C
80/20
1.0911.091
3138533PONTONDP
80/20
0.5320.532
3144293JTRSVLE
80/20
0.3290.329
3147043LAWRENC
80/20
0.240.24
3151531CLOVER1
80/20
10.82910.829
3151541CLOVER2
80/20
10.72710.727
934521AD1-076 C
Adder
8.8564705882352937.528
944011AF1-069 C
80/20
12.12612.126
959311AF2-222 C
80/20
13.30313.303
960081AF2-299 C
80/20
1.4551.455
316131AB2-060 C
80/20
1.1781.178
941031AE2-094 C
80/20
37.11337.113
946281AF1-292 C
80/20
1.2041.204
946301AF1-294 C
80/20
2.9542.954
957481AF2-042 C
80/20
47.06247.062
957861AF2-080 C
Adder
5.6494117647058824.802
958211AF2-115 C
80/20
1.7961.796
938771AE1-103 C
Adder
2.10235294117647081.787
934861AD1-115 C
80/20
3.3063.306
942341AE2-247 C
Adder
1.03882352941176470.883
943461AF1-017 C
Adder
0.94000000000000010.799
3151021BRUNSWICKG1
80/20
7.5567.556
3151031BRUNSWICKG2
80/20
7.5567.556
3151041BRUNSWICKG3
80/20
7.5567.556
3151051BRUNSWICKS1
80/20
15.69915.699
3151721LOISA A
80/20
3.3313.331
3151731LOISA B
80/20
3.3493.349
3151741LOISA C
80/20
3.3493.349
3151751LOISA D
80/20
3.3493.349
3151761LOISA E
80/20
6.8276.827
3151771S ANNAG1
80/20
3.2623.262
3151781S ANNAS1
80/20
1.6761.676
3151791S ANNAG2
80/20
3.2623.262
3151801S ANNAS2
80/20
1.6761.676
3152251N ANNA1
80/20
103.92103.92
3152261N ANNA2
80/20
103.964103.964
3152411Z1-086 GT1
80/20
9.6939.693
3152421Z1-086 GT2
80/20
9.699.69
3152431Z1-086 GT3
80/20
9.699.69
3152441Z1-086 ST
80/20
16.87216.872
966001AG1-469 C
80/20
2.3822.382
942001AE2-212 C
Adder
1.40235294117647061.192
957871AF2-081 C
Adder
7.0094117647058835.958
958161AF2-110 C
Adder
0.96117647058823530.817
926071AC1-086 C
Adder
15.98823529411764713.59
927021AC1-189 C
Adder
6.225.287
936261AD2-033 C
80/20
10.37510.375
933291AC2-141 C
Adder
21.0423529411764717.886
934621AD1-088 C
80/20
8.2538.253
939411AE1-173 C
80/20
78.11378.113
933981AD1-022 C
Adder
6.3599999999999995.406
962571AG1-106 C
Adder
2.0682352941176471.758
208900BRIS G1
80/20
-2.405-2.405
208901BRIS G2
80/20
-2.846-2.846
316023AB2-100 C2
80/20
0.7450.745
316034AC1-036 C
80/20
0.1860.186
316164AC1-076_C
80/20
1.0891.089
316170AC1-121 C
80/20
2.952.95
316192AB2-158 C
80/20
4.3254.325
316233AE1-074 C
80/20
2.0672.067
316237AB2-079 C O1
80/20
0.2590.259
316238AB2-078 C O1
80/20
0.2590.259
316239AB2-077 C O1
80/20
0.2590.259
316254AC1-120 C
80/20
8.5918.591
316257AC1-043 C
80/20
6.6126.612
316258AE1-075 C
80/20
0.320.32
316274AC1-208 C
Adder
6.785.763
316313AB2-026 C
80/20
0.3480.348
316315AB2-025 C
80/20
0.3250.325
316336AC2-165 C
80/20
8.8748.874
316365AB2-100 C1
80/20
0.7450.745
316405AF2-144 C
80/20
0.2720.272
313527AB2-043 C
80/20
0.4090.409
316087AB2-174 C
80/20
0.9080.908
316044AC1-158 C1
80/20
18.51718.517
316045AC1-158 C2
80/20
18.51718.517
316311AC2-079 C
Adder
3.99647058823529383.397
316349AD2-085 C
Adder
2.3964705882352942.037
941591AE2-156 C
Adder
12.43294117647058910.568
944581AF1-123 C
Adder
32.0470588235294127.24
944591AF1-124 C
Adder
32.1611764705882427.337
944601AF1-125 C
Adder
31.55411764705882826.821
962561AG1-105 C
Adder
6.9729411764705885.927
964241AG1-285 C
80/20
9.9749.974
3137643SOCKMAN
Adder
0.54588235294117650.464
934321AD1-056 C
Adder
4.7070588235294134.001
934331AD1-057 C
Adder
2.6258823529411772.232
934501AD1-074 C
Adder
24.38588235294117720.728
934511AD1-075 C
Adder
6.0964705882352945.182
934611AD1-087 C
80/20
1.0661.066
935171AD1-152 C
80/20
1.0991.099
937481AD2-202 C
80/20
0.3090.309
938531AE1-072 C
Adder
12.33529411764705810.485
939191AE1-149 C
Adder
7.2929411764705886.199
940481AE2-033 C
80/20
12.91312.913
940541AE2-040 C
80/20
2.2982.298
940641AE2-051 C
80/20
15.75815.758
941101AE2-104 C
Adder
2.35411764705882342.001
942461AE2-259 C
80/20
7.9867.986
316303AF2-085
80/20
3.8763.876
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2194.219
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.20919.209
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.12316.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.82173.821
NYPJM->LTFIMP_NY
CLTF
2.292.29
LGEELTFEXP_LGEE->PJM
CLTF
0.8350.835
WECLTFEXP_WEC->PJM
CLTF
0.4130.413
CPLELTFEXP_CPLE->PJM
CLTF
8.8538.853
TVALTFEXP_TVA->PJM
CLTF
4.5224.522
MECLTFEXP_MEC->PJM
CLTF
2.6672.667
LAGNLTFEXP_LAGN->PJM
CLTF
5.7055.705
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.09 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3577.61
MW Contribution:1.5
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.73647058823529410.626
961791AG1-021 C
80/20
1.51.5
961941AG1-037 C
Adder
0.39411764705882360.335
963041AG1-153 C
80/20
5.3875.387
964791AG1-342 C
Adder
2.9105882352941182.474
966621AG1-532 C
80/20
1.1511.151
313506AB1-173 C OP
80/20
0.9150.915
3138533PONTONDP
80/20
0.5550.555
3144293JTRSVLE
80/20
0.3440.344
3147043LAWRENC
80/20
0.2530.253
3151311EDGECMA
Adder
12.21411764705882410.382
3151531CLOVER1
80/20
11.34911.349
3151541CLOVER2
80/20
11.24311.243
934521AD1-076 C
Adder
9.3952941176470587.986
944011AF1-069 C
80/20
12.71412.714
959311AF2-222 C
80/20
13.90913.909
960081AF2-299 C
80/20
1.5351.535
316131AB2-060 C
80/20
1.2351.235
941031AE2-094 C
80/20
38.91138.911
946281AF1-292 C
80/20
1.2711.271
946301AF1-294 C
80/20
3.0833.083
957481AF2-042 C
80/20
49.31549.315
957861AF2-080 C
Adder
5.9741176470588245.078
958211AF2-115 C
80/20
1.8751.875
938771AE1-103 C
Adder
2.2329411764705881.898
3150651CHESTF6
Adder
11.5976470588235319.858
3150831SPRUNCA
Adder
6.1623529411764715.238
3150841SPRUNCB
Adder
6.1623529411764715.238
942341AE2-247 C
Adder
1.10588235294117650.94
943461AF1-017 C
Adder
1.00.85
3151021BRUNSWICKG1
80/20
7.9247.924
3151031BRUNSWICKG2
80/20
7.9247.924
3151041BRUNSWICKG3
80/20
7.9247.924
3151051BRUNSWICKS1
80/20
16.46316.463
3151721LOISA A
80/20
3.0793.079
3151731LOISA B
80/20
3.0953.095
3151741LOISA C
80/20
3.0953.095
3151751LOISA D
80/20
3.0953.095
3151761LOISA E
80/20
6.316.31
3151771S ANNAG1
80/20
3.0413.041
3151781S ANNAS1
80/20
1.5631.563
3151791S ANNAG2
80/20
3.0413.041
3151801S ANNAS2
80/20
1.5631.563
3152251N ANNA1
80/20
106.954106.954
3152261N ANNA2
80/20
106.999106.999
3152411Z1-086 GT1
80/20
10.16410.164
3152421Z1-086 GT2
80/20
10.16110.161
3152431Z1-086 GT3
80/20
10.16110.161
3152441Z1-086 ST
80/20
17.69217.692
966001AG1-469 C
80/20
1.9821.982
942001AE2-212 C
Adder
1.49882352941176471.274
957871AF2-081 C
Adder
7.4588235294117656.34
958161AF2-110 C
Adder
1.02235294117647070.869
926071AC1-086 C
Adder
16.8929411764705914.359
927021AC1-189 C
Adder
6.5788235294117645.592
936261AD2-033 C
80/20
10.85610.856
933291AC2-141 C
Adder
22.41294117647058619.051
934621AD1-088 C
80/20
8.6418.641
939411AE1-173 C
80/20
82.26382.263
933981AD1-022 C
Adder
6.7447058823529415.733
962571AG1-106 C
Adder
2.1847058823529411.857
208900BRIS G1
80/20
-2.414-2.414
208901BRIS G2
80/20
-2.857-2.857
316023AB2-100 C2
80/20
0.7870.787
316034AC1-036 C
80/20
0.1950.195
316192AB2-158 C
80/20
4.2764.276
316233AE1-074 C
80/20
2.1822.182
316237AB2-079 C O1
80/20
0.2720.272
316238AB2-078 C O1
80/20
0.2720.272
316239AB2-077 C O1
80/20
0.2720.272
316240AF1-291 C
Adder
1.37882352941176461.172
316258AE1-075 C
80/20
0.3330.333
316263AC1-034 C
Adder
5.2270588235294114.443
316274AC1-208 C
Adder
7.1635294117647066.089
316313AB2-026 C
80/20
0.3630.363
316315AB2-025 C
80/20
0.3440.344
316336AC2-165 C
80/20
9.2269.226
316365AB2-100 C1
80/20
0.7870.787
316405AF2-144 C
80/20
0.2830.283
316181AB2-040 GEN
80/20
1.0311.031
313527AB2-043 C
80/20
0.4290.429
316087AB2-174 C
80/20
0.9580.958
316311AC2-079 C
Adder
4.2541176470588233.616
316349AD2-085 C
Adder
2.5505882352941182.168
961611AG1-000B C
Adder
10.3129411764705888.766
941591AE2-156 C
Adder
13.23882352941176611.253
944581AF1-123 C
Adder
34.0988235294117728.984
944591AF1-124 C
Adder
34.2229.087
944601AF1-125 C
Adder
33.5741176470588328.538
962561AG1-105 C
Adder
7.3152941176470596.218
964241AG1-285 C
80/20
10.44910.449
3137643SOCKMAN
Adder
0.57647058823529410.49
934321AD1-056 C
Adder
4.9729411764705894.227
934331AD1-057 C
Adder
2.7741176470588242.358
934501AD1-074 C
Adder
25.86823529411764621.988
934511AD1-075 C
Adder
6.46705882352941155.497
934611AD1-087 C
80/20
1.1171.117
935171AD1-152 C
80/20
1.1531.153
937481AD2-202 C
80/20
0.3240.324
938531AE1-072 C
Adder
13.12352941176470511.155
939191AE1-149 C
Adder
7.7752941176470596.609
940431AE2-027 C
Adder
8.3129411764705887.066
940481AE2-033 C
80/20
13.63113.631
940541AE2-040 C
80/20
2.4262.426
940641AE2-051 C
80/20
16.55416.554
941101AE2-104 C
Adder
2.50470588235294132.129
942461AE2-259 C
Adder
8.3117647058823547.065
944641AF1-129 C
Adder
63.6988235294117654.144
316303AF2-085
80/20
4.064.06
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4574.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.24822.248
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.65817.658
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
78.26878.268
NYPJM->LTFIMP_NY
CLTF
2.2912.291
LGEELTFEXP_LGEE->PJM
CLTF
0.9480.948
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
CPLELTFEXP_CPLE->PJM
CLTF
9.3529.352
TVALTFEXP_TVA->PJM
CLTF
4.8954.895
MECLTFEXP_MEC->PJM
CLTF
2.9882.988
LAGNLTFEXP_LAGN->PJM
CLTF
6.1746.174
SIGELTFEXP_SIGE->PJM
CLTF
0.1860.186

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.41 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4350.17
MW Contribution:2.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.73058823529411760.621
961672AG1-007 E
Adder
0.414117647058823530.352
961791AG1-021 C
Adder
1.48941176470588241.266
961792AG1-021 E
Adder
1.26941176470588221.079
961941AG1-037 C
Adder
0.391764705882352960.333
961942AG1-037 E
Adder
0.26117647058823530.222
963041AG1-153 C
Adder
5.3588235294117644.555
963042AG1-153 E
Adder
8.0388235294117656.833
964791AG1-342 C
Adder
2.88941176470588262.456
964792AG1-342 E
Adder
1.92588235294117661.637
966621AG1-532 C
Adder
1.1435294117647060.972
966622AG1-532 E
Adder
0.76235294117647070.648
3138533PONTONDP
Adder
0.55176470588235290.469
3145413WATKINS
Adder
0.52941176470588240.45
3145723EMPORIA
Adder
0.350588235294117640.298
3147133PAMPLIN
Adder
0.82352941176470580.7
3151311EDGECMA
Adder
12.11411764705882510.297
918492AA1-063AE OP
Adder
3.22705882352941182.743
918532AA1-067 E
Adder
0.55176470588235290.469
919692AA2-053 E OP
Adder
3.36117647058823542.857
920042AA2-088 E OP
Adder
8.226.987
925785AC1-054 E
Adder
2.79764705882352962.378
926274AC1-105 E
Adder
2.1788235294117651.852
927146AC1-208 E
Adder
3.1564705882352942.683
934521AD1-076 C
Adder
9.3258823529411777.927
934522AD1-076 E
Adder
4.7541176470588244.041
943172AE2-346 E
Adder
0.46941176470588240.399
943902AF1-058 E
Adder
1.04352941176470580.887
944011AF1-069 C
50/50
12.65212.652
944012AF1-069 E
50/50
4.9154.915
959311AF2-222 C
Adder
13.8152941176470611.743
959312AF2-222 E
Adder
9.2564705882352957.868
960081AF2-299 C
Adder
1.52470588235294141.296
960082AF2-299 E
Adder
1.01647058823529420.864
316141AB2-099 E
Adder
0.195294117647058840.166
900672V4-068 E
Adder
0.276470588235294130.235
917342Z2-044 E
Adder
0.46823529411764710.398
922923AB1-081 E OP
Adder
2.9105882352941182.474
923263AB1-132 E OP
Adder
4.8811764705882354.149
923573AB1-173 E OP
Adder
2.6529411764705882.255
924162AB2-060 E OP
Adder
3.54470588235294143.013
924302AB2-077 E O1
Adder
1.10588235294117650.94
924312AB2-078 E O1
Adder
1.10588235294117650.94
924322AB2-079 E O1
Adder
1.10588235294117650.94
925612AC1-036 E
Adder
0.7117647058823530.605
940492AE2-034 E
Adder
2.3364705882352941.986
941031AE2-094 C
50/50
38.72138.721
941032AE2-094 E
50/50
17.34217.342
946281AF1-292 C
Adder
1.26235294117647071.073
946282AF1-292 E
Adder
0.84117647058823530.715
946301AF1-294 C
Adder
3.06235294117647072.603
946302AF1-294 E
Adder
2.59294117647058852.204
957481AF2-042 C
Adder
49.0341176470588341.679
957482AF2-042 E
Adder
32.6894117647058927.786
957861AF2-080 C
Adder
5.9270588235294125.038
957862AF2-080 E
Adder
2.6270588235294122.233
958211AF2-115 C
Adder
1.86235294117647051.583
958212AF2-115 E
Adder
1.58588235294117651.348
3145393UNCAMP
Adder
4.622352941176473.929
916042Z1-036 E
Adder
21.48117647058823518.259
938771AE1-103 C
Adder
2.21764705882352951.885
938772AE1-103 E
Adder
3.0611764705882352.602
924032AB2-045 E
Adder
1.08588235294117650.923
933502AC2-165 E
Adder
6.9070588235294135.871
3143316POE
Adder
1.04235294117647070.886
3145256KINGFORK
Adder
0.72352941176470590.615
3145506HICKORY
Adder
1.61411764705882371.372
3150831SPRUNCA
Adder
6.117647058823535.2
3150841SPRUNCB
Adder
6.117647058823535.2
926662AC1-147 E
Adder
0.97176470588235290.826
926755AC1-161 E
Adder
9.502352941176478.077
935112AD1-144 E
Adder
0.67176470588235290.571
942341AE2-247 C
Adder
1.09764705882352940.933
942342AE2-247 E
Adder
1.5164705882352941.289
943461AF1-017 C
Adder
0.99294117647058820.844
943462AF1-017 E
Adder
1.621.377
943612AF1-032 E
Adder
0.68470588235294120.582
958502AF2-144 E
Adder
1.15294117647058810.98
3151721LOISA A
50/50
3.093.09
3151731LOISA B
50/50
3.1063.106
3151741LOISA C
50/50
3.1063.106
3151751LOISA D
50/50
3.1063.106
3151761LOISA E
50/50
6.3326.332
3151771S ANNAG1
50/50
3.0513.051
3151781S ANNAS1
50/50
1.5681.568
3151791S ANNAG2
50/50
3.0513.051
3151801S ANNAS2
50/50
1.5681.568
3152251N ANNA1
50/50
106.841106.841
3152261N ANNA2
50/50
106.886106.886
913392Y1-086 E
Adder
1.63411764705882371.389
916192Z1-068 E
Adder
1.38588235294117631.178
923832AB2-022 E
Adder
0.92235294117647060.784
923852AB2-025 E
Adder
0.97529411764705880.829
923862AB2-026 E
Adder
1.17294117647058820.997
925022AB2-158 E
50/50
11.37311.373
938552AE1-074 E
Adder
1.09294117647058830.929
938562AE1-075 E
Adder
1.00.85
939312AE1-162 E
Adder
0.97647058823529410.83
957492AF2-043 E
Adder
1.05294117647058830.895
966001AG1-469 C
50/50
2.0062.006
966002AG1-469 E
50/50
1.0031.003
901082W1-029 E
Adder
23.76705882352941420.202
917122Z2-027 E
Adder
1.00.85
925522AC1-027 E
Adder
0.89764705882352950.763
942001AE2-212 C
Adder
1.48705882352941181.264
942002AE2-212 E
Adder
0.99176470588235290.843
957871AF2-081 C
Adder
7.4070588235294126.296
957872AF2-081 E
Adder
3.17411764705882372.698
958161AF2-110 C
Adder
1.0152941176470590.863
958162AF2-110 E
Adder
1.61411764705882371.372
3147223TWITTYS
Adder
0.78941176470588240.671
917512Z2-088 E OP1
Adder
3.8047058823529413.234
926071AC1-086 C
Adder
16.77411764705882314.258
926072AC1-086 E
Adder
7.6341176470588236.489
927021AC1-189 C
Adder
6.5247058823529425.546
927022AC1-189 E
Adder
3.25058823529411762.763
936261AD2-033 C
Adder
10.782352941176479.165
936262AD2-033 E
Adder
7.1882352941176476.11
933291AC2-141 C
Adder
22.2618.921
933292AC2-141 E
Adder
9.502352941176478.077
934621AD1-088 C
Adder
8.5905882352941177.302
934622AD1-088 E
Adder
4.1364705882352943.516
939411AE1-173 C
Adder
81.8247058823529469.551
939412AE1-173 E
Adder
54.5505882352941246.368
933981AD1-022 C
Adder
6.6952941176470595.691
933982AD1-022 E
Adder
3.6447058823529413.098
962572AG1-106 E
Adder
0.94941176470588240.807
962571AG1-106 C
Adder
2.16941176470588241.844
208900BRIS G1
50/50
-2.489-2.489
208901BRIS G2
50/50
-2.946-2.946
3145946PLYMOUTH TP
Adder
0.245882352941176470.209
3146326AYDLETT TAP
Adder
1.00588235294117640.855
316192AB2-158 C
50/50
4.2784.278
316233AE1-074 C
Adder
2.17058823529411751.845
316263AC1-034 C
Adder
5.1835294117647064.406
316274AC1-208 C
Adder
7.1094117647058826.043
316336AC2-165 C
Adder
9.177647058823537.801
917332KELFORD E
Adder
1.281.088
924516AB2-100 E1
Adder
2.36470588235294082.01
924517AB2-100 E2
Adder
2.36470588235294082.01
925595AC1-034 E
Adder
3.91058823529411773.324
926206AC1-098 E
Adder
2.86705882352941142.437
926214AC1-099 E
Adder
0.94705882352941180.805
927255AC1-221 E
Adder
2.9588235294117652.515
927264AC1-222 E
Adder
3.20470588235294152.724
932763AC2-100 E
Adder
2.00588235294117641.705
934065AD1-033 E
Adder
3.70941176470588243.153
937226AE2-253 E
Adder
4.3282352941176473.679
918512AA1-065 E OP
Adder
4.2588235294117653.62
919153AA1-139 E2
Adder
3.02941176470588272.575
919152AA1-139 E1
Adder
3.02941176470588272.575
919710AA2-057 E
Adder
3.1117647058823532.645
920692AA2-178 E
Adder
3.1141176470588232.647
923994AB2-040_E
Adder
4.9741176470588234.228
924022AB2-043 E O1
Adder
4.2929411764705883.649
924152AB2-059 E OP
Adder
4.122352941176473.504
316084AB2-161 E
Adder
4.0141176470588233.412
925122AB2-169 E
Adder
4.4105882352941183.749
316088AB2-174 E
Adder
5.2858823529411774.493
316044AC1-158 C1
50/50
19.56819.568
316045AC1-158 C2
50/50
19.56819.568
926739AC1-158 E1
50/50
51.18251.182
926740AC1-158 E2
50/50
51.18251.182
932046AC2-012 E
Adder
9.6164705882352938.174
316311AC2-079 C
Adder
4.2247058823529413.591
932596AC2-079 E
Adder
6.8929411764705895.859
934576AD1-082 E
Adder
3.19882352941176462.719
316349AD2-085 C
Adder
2.53294117647058852.153
936666AD2-085 E
Adder
4.1329411764705883.513
941591AE2-156 C
Adder
13.14823529411764711.176
944581AF1-123 C
Adder
33.8670588235294128.787
944582AF1-123 E
Adder
77.5517647058823565.919
944591AF1-124 C
Adder
33.9870588235294128.889
944592AF1-124 E
Adder
77.8317647058823566.157
944601AF1-125 C
Adder
33.3447058823529428.343
944602AF1-125 E
Adder
76.3341176470588364.884
962561AG1-105 C
Adder
7.2635294117647076.174
962562AG1-105 E
Adder
4.842352941176474.116
964241AG1-285 C
Adder
10.3776470588235298.821
964242AG1-285 E
Adder
6.9188235294117655.881
3137643SOCKMAN
Adder
0.57294117647058830.487
932632AC2-084 E
Adder
2.53411764705882362.154
934321AD1-056 C
Adder
4.9352941176470594.195
934322AD1-056 E
Adder
2.6764705882352942.275
934331AD1-057 C
Adder
2.75294117647058822.34
934332AD1-057 E
Adder
1.43411764705882371.219
934501AD1-074 C
Adder
25.6821.828
934502AD1-074 E
Adder
13.07176470588235311.111
934511AD1-075 C
Adder
6.425.457
934512AD1-075 E
Adder
3.26823529411764732.778
934612AD1-087 E
Adder
3.2152941176470592.733
935172AD1-152 E
Adder
4.7270588235294114.018
937482AD2-202 E
Adder
0.94117647058823540.8
938531AE1-072 C
Adder
13.03294117647058811.078
938532AE1-072 E
Adder
6.7941176470588245.775
939191AE1-149 C
Adder
7.7200000000000016.562
939192AE1-149 E
Adder
5.1470588235294124.375
940481AE2-033 C
Adder
13.54823529411764811.516
940482AE2-033 E
Adder
9.1341176470588247.764
940541AE2-040 C
Adder
2.4117647058823532.05
940641AE2-051 C
50/50
16.47216.472
940642AE2-051 E
50/50
10.98110.981
941101AE2-104 C
Adder
2.48705882352941152.114
941102AE2-104 E
Adder
3.9541176470588243.361
942461AE2-259 C
Adder
8.257647058823537.019
942462AE2-259 E
Adder
5.5047058823529414.679
316303AF2-085
50/50
4.0434.043
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4084.408
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.05120.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.83616.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
77.11777.117
G-007PJM->LTFIMP_G-007
CMTX_NF
5.0575.057
NYPJM->LTFIMP_NY
CLTF
2.3732.373
LGEELTFEXP_LGEE->PJM
CLTF
0.8720.872
WECLTFEXP_WEC->PJM
CLTF
0.4310.431
CPLELTFEXP_CPLE->PJM
CLTF
9.2519.251
TVALTFEXP_TVA->PJM
CLTF
4.7224.722
MECLTFEXP_MEC->PJM
CLTF
2.7842.784
LAGNLTFEXP_LAGN->PJM
CLTF
5.9595.959
SIGELTFEXP_SIGE->PJM
CLTF
0.1730.173
O66PJM->LTFIMP_O-066
CMTX_NF
32.20632.206

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.75 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4205.81
MW Contribution:2.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
1.4435294117647061.227
961792AG1-021 E
Adder
1.22941176470588221.045
961941AG1-037 C
Adder
0.37294117647058830.317
961942AG1-037 E
Adder
0.249411764705882360.212
963041AG1-153 C
Adder
5.1482352941176474.376
963042AG1-153 E
Adder
7.7235294117647076.565
964791AG1-342 C
Adder
2.7823529411764712.365
964792AG1-342 E
Adder
1.85529411764705881.577
966621AG1-532 C
Adder
1.09411764705882360.93
966622AG1-532 E
Adder
0.72941176470588230.62
3138533PONTONDP
Adder
0.53411764705882360.454
3145413WATKINS
Adder
0.50352941176470590.428
3145723EMPORIA
Adder
0.33529411764705880.285
3147133PAMPLIN
Adder
0.79882352941176480.679
918492AA1-063AE OP
Adder
3.08235294117647072.62
918532AA1-067 E
Adder
0.52705882352941180.448
919692AA2-053 E OP
Adder
3.2129411764705882.731
920042AA2-088 E OP
Adder
7.8352941176470596.66
925785AC1-054 E
Adder
2.6835294117647062.281
926274AC1-105 E
Adder
2.09764705882352941.783
927146AC1-208 E
Adder
3.01882352941176452.566
934521AD1-076 C
Adder
8.8788235294117657.547
934522AD1-076 E
Adder
4.5258823529411773.847
943172AE2-346 E
Adder
0.448235294117647070.381
943902AF1-058 E
Adder
1.00470588235294110.854
944011AF1-069 C
50/50
12.15212.152
944012AF1-069 E
50/50
4.7214.721
959311AF2-222 C
Adder
13.3576470588235311.354
959312AF2-222 E
Adder
8.9494117647058827.607
960081AF2-299 C
Adder
1.45882352941176461.24
960082AF2-299 E
Adder
0.97294117647058820.827
316141AB2-099 E
Adder
0.187058823529411780.159
900672V4-068 E
Adder
0.26352941176470590.224
917342Z2-044 E
Adder
0.448235294117647070.381
923263AB1-132 E OP
Adder
4.66470588235294153.965
923573AB1-173 E OP
Adder
2.53764705882352942.157
924162AB2-060 E OP
Adder
3.4164705882352942.904
924302AB2-077 E O1
Adder
1.06588235294117650.906
924312AB2-078 E O1
Adder
1.06588235294117650.906
924322AB2-079 E O1
Adder
1.06588235294117650.906
925612AC1-036 E
Adder
0.68823529411764710.585
940492AE2-034 E
Adder
2.2223529411764711.889
941031AE2-094 C
50/50
37.19337.193
941032AE2-094 E
50/50
16.65816.658
946281AF1-292 C
Adder
1.2082352941176471.027
946282AF1-292 E
Adder
0.80470588235294130.684
946301AF1-294 C
Adder
2.96705882352941152.522
946302AF1-294 E
Adder
2.51294117647058852.136
957481AF2-042 C
Adder
47.1905882352941240.112
957482AF2-042 E
Adder
31.4626.741
957861AF2-080 C
Adder
5.6635294117647064.814
957862AF2-080 E
Adder
2.5105882352941182.134
958211AF2-115 C
Adder
1.80470588235294121.534
958212AF2-115 E
Adder
1.53764705882352941.307
3145393UNCAMP
Adder
4.3976470588235293.738
916042Z1-036 E
Adder
20.41647058823529517.354
938771AE1-103 C
Adder
2.1082352941176471.792
938772AE1-103 E
Adder
2.91176470588235332.475
924032AB2-045 E
Adder
1.06588235294117650.906
933502AC2-165 E
Adder
6.7129411764705895.706
3143316POE
Adder
0.99058823529411770.842
3145256KINGFORK
Adder
0.68588235294117650.583
3145506HICKORY
Adder
1.53058823529411761.301
926662AC1-147 E
Adder
0.92117647058823540.783
926755AC1-161 E
Adder
9.0070588235294127.656
934861AD1-115 C
50/50
3.523.52
934862AD1-115 E
50/50
5.7435.743
935112AD1-144 E
Adder
0.63647058823529420.541
942341AE2-247 C
Adder
1.04117647058823540.885
942342AE2-247 E
Adder
1.43764705882352951.222
943461AF1-017 C
Adder
0.94235294117647060.801
943462AF1-017 E
Adder
1.53764705882352941.307
943612AF1-032 E
Adder
0.64941176470588250.552
958502AF2-144 E
Adder
1.11764705882352940.95
3151721LOISA A
50/50
3.4353.435
3151731LOISA B
50/50
3.4533.453
3151741LOISA C
50/50
3.4533.453
3151751LOISA D
50/50
3.4533.453
3151761LOISA E
50/50
7.047.04
3151771S ANNAG1
50/50
3.3573.357
3151781S ANNAS1
50/50
1.7251.725
3151791S ANNAG2
50/50
3.3573.357
3151801S ANNAS2
50/50
1.7251.725
3152251N ANNA1
50/50
104.031104.031
3152261N ANNA2
50/50
104.075104.075
913392Y1-086 E
Adder
1.5517647058823531.319
916192Z1-068 E
Adder
1.31411764705882361.117
923832AB2-022 E
Adder
0.87529411764705890.744
923852AB2-025 E
Adder
0.9317647058823530.792
923862AB2-026 E
Adder
1.13764705882352950.967
925022AB2-158 E
50/50
11.64111.641
938552AE1-074 E
Adder
1.04470588235294120.888
938562AE1-075 E
Adder
0.96941176470588230.824
957492AF2-043 E
Adder
0.99882352941176470.849
966001AG1-469 C
50/50
2.4612.461
966002AG1-469 E
50/50
1.231.23
901082W1-029 E
Adder
22.56941176470588319.184
917122Z2-027 E
Adder
0.94941176470588240.807
925522AC1-027 E
Adder
0.85058823529411760.723
925672AC1-043 E
50/50
11.48611.486
942001AE2-212 C
Adder
1.40588235294117661.195
942002AE2-212 E
Adder
0.93764705882352950.797
957871AF2-081 C
Adder
7.0282352941176475.974
957872AF2-081 E
Adder
3.0117647058823532.56
958161AF2-110 C
Adder
0.96352941176470590.819
958162AF2-110 E
Adder
1.53176470588235311.302
3147223TWITTYS
Adder
0.76235294117647070.648
926071AC1-086 C
Adder
16.0282352941176513.624
926072AC1-086 E
Adder
7.29529411764705856.201
927021AC1-189 C
Adder
6.2352941176470595.3
927022AC1-189 E
Adder
3.10588235294117652.64
936261AD2-033 C
Adder
10.415294117647068.853
936262AD2-033 E
Adder
6.9435294117647075.902
933291AC2-141 C
Adder
21.09882352941176717.934
933292AC2-141 E
Adder
9.0070588235294127.656
934621AD1-088 C
Adder
8.277647058823537.036
934622AD1-088 E
Adder
3.98588235294117643.388
939411AE1-173 C
Adder
78.2905882352941166.547
939412AE1-173 E
Adder
52.19411764705882544.365
933981AD1-022 C
Adder
6.3764705882352955.42
933982AD1-022 E
Adder
3.47058823529411782.95
962572AG1-106 E
Adder
0.90705882352941180.771
962571AG1-106 C
Adder
2.07294117647058851.762
208900BRIS G1
50/50
-2.42-2.42
208901BRIS G2
50/50
-2.864-2.864
3145946PLYMOUTH TP
Adder
0.234117647058823540.199
3146326AYDLETT TAP
Adder
0.95411764705882360.811
316164AC1-076_C
50/50
1.1111.111
316170AC1-121 C
50/50
3.0753.075
316192AB2-158 C
50/50
4.384.38
316233AE1-074 C
Adder
2.07294117647058851.762
316254AC1-120 C
50/50
8.9538.953
316257AC1-043 C
50/50
7.047.04
316274AC1-208 C
Adder
6.7976470588235295.778
316336AC2-165 C
Adder
8.9188235294117667.581
917332KELFORD E
Adder
1.22235294117647041.039
924516AB2-100 E1
Adder
2.26000000000000021.921
924517AB2-100 E2
Adder
2.26000000000000021.921
926206AC1-098 E
Adder
2.742.329
926214AC1-099 E
Adder
0.90470588235294120.769
927255AC1-221 E
Adder
2.84470588235294162.418
927264AC1-222 E
Adder
3.0847058823529412.622
932763AC2-100 E
Adder
1.9282352941176471.639
934065AD1-033 E
Adder
3.5188235294117652.991
937226AE2-253 E
Adder
4.1070588235294123.491
926004AC1-076_E
50/50
6.3656.365
926486AC1-120 E
50/50
4.6124.612
926502AC1-121 E
50/50
1.4471.447
918512AA1-065 E OP
Adder
4.06000000000000053.451
919153AA1-139 E2
Adder
2.8741176470588242.443
919152AA1-139 E1
Adder
2.8741176470588242.443
919710AA2-057 E
Adder
2.97647058823529382.53
920692AA2-178 E
Adder
2.9635294117647062.519
923994AB2-040_E
Adder
4.7588235294117654.045
924022AB2-043 E O1
Adder
4.1364705882352943.516
316084AB2-161 E
Adder
3.8047058823529413.234
925122AB2-169 E
Adder
4.2058823529411773.575
316088AB2-174 E
Adder
5.0564705882352944.298
316044AC1-158 C1
50/50
18.54118.541
316045AC1-158 C2
50/50
18.54118.541
926739AC1-158 E1
50/50
48.49548.495
926740AC1-158 E2
50/50
48.49548.495
932046AC2-012 E
Adder
9.1176470588235297.75
316311AC2-079 C
Adder
4.00705882352941253.406
932596AC2-079 E
Adder
6.5388235294117655.558
934576AD1-082 E
Adder
3.0317647058823532.577
316349AD2-085 C
Adder
2.40235294117647062.042
936666AD2-085 E
Adder
3.923.332
941591AE2-156 C
Adder
12.46588235294117710.596
944581AF1-123 C
Adder
32.1329411764705927.313
944582AF1-123 E
Adder
73.5862.543
944591AF1-124 C
Adder
32.24705882352941427.41
944592AF1-124 E
Adder
73.8458823529411762.769
944601AF1-125 C
Adder
31.6376470588235326.892
944602AF1-125 E
Adder
72.4247058823529461.561
962561AG1-105 C
Adder
6.9952941176470595.946
962562AG1-105 E
Adder
4.6635294117647063.964
964241AG1-285 C
Adder
10.0105882352941198.509
964242AG1-285 E
Adder
6.6741176470588245.673
3137643SOCKMAN
Adder
0.54705882352941180.465
932632AC2-084 E
Adder
2.4211764705882352.058
934321AD1-056 C
Adder
4.7188235294117654.011
934322AD1-056 E
Adder
2.562.176
934331AD1-057 C
Adder
2.6329411764705882.238
934332AD1-057 E
Adder
1.37058823529411771.165
934501AD1-074 C
Adder
24.44941176470588220.782
934502AD1-074 E
Adder
12.44588235294117810.579
934511AD1-075 C
Adder
6.1117647058823535.195
934512AD1-075 E
Adder
3.1117647058823532.645
934612AD1-087 E
Adder
3.09529411764705882.631
935172AD1-152 E
Adder
4.5494117647058833.867
937482AD2-202 E
Adder
0.90588235294117650.77
938531AE1-072 C
Adder
12.36823529411764810.513
938532AE1-072 E
Adder
6.4470588235294135.48
939191AE1-149 C
Adder
7.3129411764705896.216
939192AE1-149 E
Adder
4.87529411764705944.144
940481AE2-033 C
Adder
12.94470588235294211.003
940482AE2-033 E
Adder
8.7270588235294117.418
940541AE2-040 C
Adder
2.3035294117647061.958
940641AE2-051 C
50/50
15.79315.793
940642AE2-051 E
50/50
10.52910.529
941101AE2-104 C
Adder
2.362.006
941102AE2-104 E
Adder
3.75294117647058823.19
942461AE2-259 C
Adder
8.0294117647058826.825
942462AE2-259 E
Adder
5.3529411764705884.55
316303AF2-085
50/50
3.8863.886
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2284.228
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.05119.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.10316.103
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.97573.975
G-007PJM->LTFIMP_G-007
CMTX_NF
4.9174.917
NYPJM->LTFIMP_NY
CLTF
2.3072.307
LGEELTFEXP_LGEE->PJM
CLTF
0.8310.831
WECLTFEXP_WEC->PJM
CLTF
0.410.41
CPLELTFEXP_CPLE->PJM
CLTF
8.8738.873
TVALTFEXP_TVA->PJM
CLTF
4.5234.523
MECLTFEXP_MEC->PJM
CLTF
2.6562.656
LAGNLTFEXP_LAGN->PJM
CLTF
5.7065.706
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165
O66PJM->LTFIMP_O-066
CMTX_NF
31.31531.315

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.97 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3767.03
MW Contribution:1.61
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.82941176470588230.705
961791AG1-021 C
Adder
1.61176470588235321.37
961941AG1-037 C
Adder
0.454117647058823570.386
963041AG1-153 C
80/20
5.7035.703
964791AG1-342 C
Adder
3.14588235294117662.674
966621AG1-532 C
80/20
1.2891.289
313506AB1-173 C OP
80/20
1.0281.028
3138533PONTONDP
Adder
0.59764705882352940.508
3147043LAWRENC
80/20
0.2810.281
3151311EDGECMA
Adder
13.67647058823529511.625
3151531CLOVER1
80/20
12.09912.099
3151541CLOVER2
80/20
11.98611.986
934521AD1-076 C
Adder
10.9623529411764719.318
944011AF1-069 C
80/20
13.43113.431
959311AF2-222 C
Adder
14.9976470588235312.748
960081AF2-299 C
80/20
1.7191.719
941031AE2-094 C
80/20
41.10641.106
946281AF1-292 C
80/20
1.4231.423
946301AF1-294 C
Adder
3.3141176470588242.817
957481AF2-042 C
80/20
52.44752.447
957861AF2-080 C
Adder
6.7600000000000015.746
958211AF2-115 C
Adder
2.0152941176470591.713
938771AE1-103 C
80/20
2.6332.633
313526AB2-022 C
80/20
0.3360.336
3150601CHESTF5
Adder
45.29058823529411638.497
3150651CHESTF6
Adder
15.16470588235294212.89
3150731STONECA
Adder
5.4352941176470594.62
3150831SPRUNCA
Adder
7.7905882352941186.622
3150841SPRUNCB
Adder
7.7905882352941186.622
3150921YORKTN3
Adder
92.4352941176470578.57
942341AE2-247 C
80/20
1.3311.331
943461AF1-017 C
80/20
1.2041.204
3150981CHESPKA
80/20
0.3880.388
3150991CHESPKB
80/20
0.6430.643
3151021BRUNSWICKG1
80/20
8.3898.389
3151031BRUNSWICKG2
80/20
8.3898.389
3151041BRUNSWICKG3
80/20
8.3898.389
3151051BRUNSWICKS1
80/20
17.42917.429
3151081ELIZAR1
80/20
2.8512.851
3151091ELIZAR2
80/20
2.8012.801
3151101ELIZAR3
80/20
2.8872.887
3151721LOISA A
80/20
2.3742.374
3151731LOISA B
80/20
2.3872.387
3151741LOISA C
80/20
2.3872.387
3151751LOISA D
80/20
2.3872.387
3151761LOISA E
80/20
4.8664.866
3151771S ANNAG1
80/20
2.372.37
3151781S ANNAS1
80/20
1.2181.218
3151791S ANNAG2
80/20
2.372.37
3151801S ANNAS2
80/20
1.2181.218
3152251N ANNA1
80/20
92.7292.72
3152261N ANNA2
80/20
92.75992.759
3152411Z1-086 GT1
80/20
10.75310.753
3152421Z1-086 GT2
80/20
10.7510.75
3152431Z1-086 GT3
80/20
10.7510.75
3152441Z1-086 ST
80/20
18.71718.717
3156056W1-029WIND
80/20
0.6930.693
966001AG1-469 C
Adder
1.43764705882352951.222
942001AE2-212 C
Adder
1.8635294117647061.584
957871AF2-081 C
80/20
8.9458.945
958161AF2-110 C
80/20
1.2251.225
926071AC1-086 C
Adder
19.07647058823529616.215
927021AC1-189 C
Adder
7.4435294117647066.327
936261AD2-033 C
Adder
11.7211764705882359.963
933291AC2-141 C
80/20
27.11427.114
934621AD1-088 C
80/20
9.29.2
939411AE1-173 C
80/20
90.4790.47
916191Z1-068 C
80/20
0.0390.039
933981AD1-022 C
Adder
7.84941176470588256.672
962571AG1-106 C
Adder
2.4670588235294122.097
208900BRIS G1
80/20
-2.561-2.561
208901BRIS G2
80/20
-3.03-3.03
316023AB2-100 C2
80/20
0.8850.885
316036AC1-147 C
80/20
0.3280.328
316072AD1-144 C
80/20
0.2460.246
316185AD1-033 C
80/20
1.0971.097
316192AB2-158 C
80/20
3.5593.559
316233AE1-074 C
80/20
2.4792.479
316240AF1-291 C
Adder
1.78117647058823541.514
316246AF1-032 C
80/20
0.2540.254
316258AE1-075 C
80/20
0.3530.353
316263AC1-034 C
Adder
5.8505882352941184.973
316274AC1-208 C
Adder
8.077647058823536.866
316294AC1-161 C
80/20
4.4154.415
316305AF2-043 C
80/20
0.3110.311
316313AB2-026 C
80/20
0.3850.385
316315AB2-025 C
80/20
0.3860.386
316316AC1-027 C
80/20
0.2820.282
316320Y1-086 C
80/20
0.1960.196
316321Z2-027 C
80/20
0.3250.325
316336AC2-165 C
80/20
9.7879.787
316365AB2-100 C1
80/20
0.8850.885
316405AF2-144 C
80/20
0.30.3
316017AA1-139 ULT1
80/20
0.9650.965
316018AA1-139 ULT2
80/20
0.9650.965
316181AB2-040 GEN
80/20
1.1581.158
316083AB2-161 C
80/20
0.4890.489
316087AB2-174 C
80/20
1.0751.075
316375AC2-012 C
80/20
1.2021.202
316311AC2-079 C
80/20
5.125.12
316381AD1-082 C
80/20
1.1161.116
316349AD2-085 C
80/20
3.0713.071
316388AE2-253 GEN
80/20
1.7531.753
961611AG1-000B C
Adder
13.19882352941176511.219
941591AE2-156 C
80/20
15.98415.984
944581AF1-123 C
80/20
40.90340.903
944591AF1-124 C
80/20
41.04941.049
944601AF1-125 C
80/20
40.27340.273
944631AF1-128 C
Adder
28.33882352941176624.088
962561AG1-105 C
Adder
7.9117647058823526.725
964241AG1-285 C
Adder
11.3035294117647079.608
3137643SOCKMAN
Adder
0.64823529411764710.551
934321AD1-056 C
Adder
5.5882352941176484.75
934331AD1-057 C
Adder
3.11764705882352942.65
934501AD1-074 C
Adder
30.18352941176470625.656
934511AD1-075 C
Adder
7.54588235294117656.414
934611AD1-087 C
80/20
1.1911.191
935161AD1-151 C
Adder
13.03882352941176511.083
935171AD1-152 C
80/20
1.2331.233
937481AD2-202 C
80/20
0.3460.346
938531AE1-072 C
80/20
15.7315.73
939191AE1-149 C
80/20
9.4869.486
940431AE2-027 C
Adder
10.6976470588235299.093
940481AE2-033 C
80/20
15.30215.302
940541AE2-040 C
80/20
2.7232.723
940641AE2-051 C
80/20
17.817.8
941101AE2-104 C
80/20
3.0013.001
942461AE2-259 C
Adder
8.8929411764705887.559
944641AF1-129 C
Adder
83.2882352941176570.795
3150851SPRUNCC
80/20
0.140.14
3150861SPRUNCD
80/20
0.140.14
316303AF2-085
80/20
4.3034.303
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.8954.895
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.18225.182
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.8619.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.42786.427
NYPJM->LTFIMP_NY
CLTF
2.4542.454
LGEELTFEXP_LGEE->PJM
CLTF
1.0841.084
WECLTFEXP_WEC->PJM
CLTF
0.5370.537
CPLELTFEXP_CPLE->PJM
CLTF
10.2710.27
TVALTFEXP_TVA->PJM
CLTF
5.5015.501
MECLTFEXP_MEC->PJM
CLTF
3.3753.375
LAGNLTFEXP_LAGN->PJM
CLTF
6.9186.918
SIGELTFEXP_SIGE->PJM
CLTF
0.2110.211

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.22 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3678.49
MW Contribution:1.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.95176470588235310.809
961791AG1-021 C
Adder
1.71764705882352931.46
961941AG1-037 C
Adder
0.53764705882352950.457
963041AG1-153 C
Adder
5.8858823529411765.003
964791AG1-342 C
Adder
3.38000000000000032.873
966621AG1-532 C
Adder
1.46470588235294131.245
3138533PONTONDP
Adder
0.63647058823529420.541
3151311EDGECMA
Adder
15.55647058823529613.223
934521AD1-076 C
Adder
13.2411.254
944011AF1-069 C
80/20
13.80413.804
959311AF2-222 C
Adder
16.0552941176470613.647
960081AF2-299 C
Adder
1.95294117647058821.66
941031AE2-094 C
80/20
42.24742.247
946281AF1-292 C
Adder
1.61647058823529431.374
946301AF1-294 C
Adder
3.5305882352941183.001
957481AF2-042 C
Adder
54.6470588235294146.45
957861AF2-080 C
Adder
7.8129411764705896.641
958211AF2-115 C
Adder
2.14705882352941171.825
938771AE1-103 C
Adder
3.22705882352941182.743
3142366NRTHEST
80/20
0.2040.204
3143096IRON208
80/20
0.4940.494
3150601CHESTF5
Adder
70.4105882352941159.849
3150651CHESTF6
80/20
21.09121.091
3150731STONECA
80/20
7.7657.765
3150761HOPPOLC
80/20
1.7191.719
3150771HOPHCF1
80/20
2.7332.733
3150781HOPHCF2
80/20
2.7332.733
3150791HOPHCF3
80/20
2.7332.733
3150801HOPHCF4
80/20
4.1494.149
3150831SPRUNCA
80/20
10.42510.425
3150841SPRUNCB
80/20
10.42510.425
3150921YORKTN3
Adder
133.0105882352941113.059
934861AD1-115 C
Adder
-3.06-2.601
936591AD2-074 C
Adder
5.8552941176470594.977
942341AE2-247 C
Adder
1.67764705882352931.426
943461AF1-017 C
Adder
1.51764705882352961.29
943741AF1-042 C
Adder
3.06352941176470632.604
961951AG1-038 C
Adder
3.3858823529411772.878
966661AG1-536 C
Adder
5.6341176470588234.789
966871AG1-558 C
Adder
2.56235294117647072.178
966881AG1-559 C
Adder
2.45176470588235332.084
3150991CHESPKB
80/20
0.8130.813
3151081ELIZAR1
80/20
3.6013.601
3151091ELIZAR2
80/20
3.5383.538
3151101ELIZAR3
80/20
3.6473.647
3152251N ANNA1
80/20
56.69756.697
3152261N ANNA2
80/20
56.72156.721
3152331SURRY 2
80/20
27.86527.865
957601AF2-054 C
Adder
2.26000000000000021.921
962861AG1-135 C
Adder
6.3647058823529425.41
963611AG1-210 C
Adder
0.68235294117647060.58
964211AG1-282 C
Adder
2.07882352941176451.767
942001AE2-212 C
80/20
2.4472.447
957871AF2-081 C
Adder
11.2117647058823529.53
958161AF2-110 C
Adder
1.53294117647058831.303
926071AC1-086 C
Adder
21.9611764705882418.667
927021AC1-189 C
Adder
8.6023529411764727.312
936261AD2-033 C
Adder
12.57294117647058810.687
933291AC2-141 C
80/20
34.37234.372
934621AD1-088 C
Adder
9.6105882352941188.169
939411AE1-173 C
80/20
99.71499.714
927041AC1-191 C
Adder
10.2870588235294128.744
933981AD1-022 C
Adder
9.4470588235294128.03
962571AG1-106 C
Adder
2.84117647058823542.415
316169AC1-164 GEN
Adder
43.66588235294117537.116
316233AE1-074 C
80/20
2.8742.874
316240AF1-291 C
80/20
2.4442.444
316254AC1-120 C
Adder
-6.376470588235295-5.42
316257AC1-043 C
Adder
-6.121176470588236-5.203
316263AC1-034 C
Adder
6.6529411764705895.655
316274AC1-208 C
Adder
9.2835294117647067.891
316294AC1-161 C
80/20
5.5975.597
316336AC2-165 C
Adder
10.1788235294117648.652
316375AC2-012 C
80/20
1.521.52
316311AC2-079 C
Adder
6.4458823529411775.479
316349AD2-085 C
Adder
3.87058823529411773.29
961611AG1-000B C
Adder
17.92352941176470415.235
941591AE2-156 C
80/20
20.20920.209
944581AF1-123 C
80/20
51.27751.277
944591AF1-124 C
80/20
51.4651.46
944601AF1-125 C
80/20
50.48850.488
944631AF1-128 C
Adder
44.0564705882352937.448
958261AF2-120 C
Adder
6.5505882352941175.568
962561AG1-105 C
Adder
8.5058823529411767.23
964241AG1-285 C
Adder
12.1610.336
3137643SOCKMAN
Adder
0.74235294117647070.631
934321AD1-056 C
Adder
6.3870588235294125.429
934331AD1-057 C
Adder
3.5635294117647063.029
934501AD1-074 C
Adder
36.4552941176470630.987
934511AD1-075 C
Adder
9.1141176470588237.747
935161AD1-151 C
Adder
18.16235294117647215.438
938531AE1-072 C
Adder
19.70000000000000316.745
939191AE1-149 C
80/20
12.15312.153
939261AE1-157 C
Adder
14.10235294117647211.987
940431AE2-027 C
80/20
14.61614.616
940481AE2-033 C
Adder
17.43882352941176714.823
940541AE2-040 C
Adder
3.10117647058823562.636
940551AE2-041 C
Adder
7.6152941176470596.473
940641AE2-051 C
80/20
18.8818.88
941101AE2-104 C
Adder
3.75764705882352963.194
942461AE2-259 C
Adder
9.4035294117647077.993
943471AF1-018 C
Adder
7.6152941176470596.473
944641AF1-129 C
80/20
115.84115.84
3150851SPRUNCC
80/20
0.1870.187
3150861SPRUNCD
80/20
0.1870.187
316303AF2-085
80/20
4.4474.447
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.4135.413
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.72830.728
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.33523.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69496.694
NYPJM->LTFIMP_NY
CLTF
2.72.7
LGEELTFEXP_LGEE->PJM
CLTF
1.331.33
WECLTFEXP_WEC->PJM
CLTF
0.6540.654
CPLELTFEXP_CPLE->PJM
CLTF
11.35211.352
TVALTFEXP_TVA->PJM
CLTF
6.4156.415
MECLTFEXP_MEC->PJM
CLTF
4.0414.041
LAGNLTFEXP_LAGN->PJM
CLTF
8.0268.026
SIGELTFEXP_SIGE->PJM
CLTF
0.2560.256

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.99 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4412.36
MW Contribution:3.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
1.68117647058823551.429
961792AG1-021 E
Adder
1.4317647058823531.217
961941AG1-037 C
Adder
0.476470588235294150.405
961942AG1-037 E
Adder
0.317647058823529450.27
963041AG1-153 C
50/50
5.9155.915
963042AG1-153 E
50/50
8.8728.872
966621AG1-532 C
Adder
1.34705882352941191.145
966622AG1-532 E
Adder
0.89882352941176480.764
3138533PONTONDP
Adder
0.62235294117647070.529
3145413WATKINS
Adder
0.65411764705882360.556
3145723EMPORIA
Adder
0.414117647058823530.352
3147133PAMPLIN
Adder
0.92823529411764720.789
918492AA1-063AE OP
Adder
3.87294117647058833.292
919692AA2-053 E OP
Adder
4.00705882352941253.406
920042AA2-088 E OP
Adder
10.0447058823529418.538
925785AC1-054 E
Adder
3.24941176470588242.762
934521AD1-076 C
Adder
11.5105882352941199.784
934522AD1-076 E
Adder
5.8670588235294124.987
943172AE2-346 E
Adder
0.5717647058823530.486
944011AF1-069 C
50/50
13.92113.921
944012AF1-069 E
50/50
5.4085.408
959311AF2-222 C
Adder
15.63529411764705813.29
959312AF2-222 E
Adder
10.4764705882352948.905
960081AF2-299 C
Adder
1.7964705882352941.527
960082AF2-299 E
Adder
1.19764705882352951.018
316141AB2-099 E
Adder
0.237647058823529430.202
900672V4-068 E
Adder
0.33764705882352940.287
923263AB1-132 E OP
Adder
5.80941176470588254.938
923573AB1-173 E OP
Adder
3.1364705882352942.666
924162AB2-060 E OP
Adder
4.0294117647058823.425
924302AB2-077 E O1
Adder
1.25764705882352931.069
924312AB2-078 E O1
Adder
1.25764705882352931.069
924322AB2-079 E O1
Adder
1.25764705882352931.069
925612AC1-036 E
Adder
0.80588235294117660.685
940492AE2-034 E
Adder
2.90235294117647062.467
941031AE2-094 C
50/50
42.60742.607
941032AE2-094 E
50/50
19.08319.083
946281AF1-292 C
Adder
1.48705882352941181.264
946282AF1-292 E
Adder
0.99176470588235290.843
946301AF1-294 C
Adder
3.45529411764705862.937
946302AF1-294 E
Adder
2.9258823529411772.487
957481AF2-042 C
Adder
54.4729411764705946.302
957482AF2-042 E
Adder
36.31529411764705630.868
958211AF2-115 C
Adder
2.1011764705882351.786
958212AF2-115 E
Adder
1.78941176470588231.521
3145393UNCAMP
Adder
5.7482352941176484.886
916042Z1-036 E
Adder
26.91882352941176422.881
938771AE1-103 C
Adder
2.7670588235294122.352
938772AE1-103 E
Adder
3.8211764705882363.248
933502AC2-165 E
Adder
7.6611764705882356.512
3143316POE
Adder
1.30941176470588231.113
3145256KINGFORK
Adder
0.93882352941176480.798
3145506HICKORY
Adder
2.05411764705882361.746
3150651CHESTF6
Adder
16.10470588235294213.689
3150831SPRUNCA
Adder
8.2435294117647067.007
3150841SPRUNCB
Adder
8.2435294117647067.007
926662AC1-147 E
Adder
1.24470588235294131.058
926755AC1-161 E
Adder
12.19411764705882510.365
927226AC1-216 E
Adder
6.6694117647058825.669
935112AD1-144 E
Adder
0.8717647058823530.741
942341AE2-247 C
Adder
1.40235294117647061.192
942342AE2-247 E
Adder
1.93529411764705881.645
943461AF1-017 C
Adder
1.26823529411764711.078
943462AF1-017 E
Adder
2.06941176470588231.759
943612AF1-032 E
Adder
0.87058823529411770.74
958502AF2-144 E
Adder
1.2764705882352941.085
3151021BRUNSWICKG1
50/50
8.78.7
3151031BRUNSWICKG2
50/50
8.78.7
3151041BRUNSWICKG3
50/50
8.78.7
3151051BRUNSWICKS1
50/50
18.07518.075
3151731LOISA B
50/50
2.4192.419
3151751LOISA D
50/50
2.4192.419
3151761LOISA E
50/50
4.9314.931
3151771S ANNAG1
50/50
2.42.4
3151781S ANNAS1
50/50
1.2331.233
3151791S ANNAG2
50/50
2.42.4
3151801S ANNAS2
50/50
1.2331.233
3152251N ANNA1
50/50
93.18793.187
3152261N ANNA2
50/50
93.22693.226
3152411Z1-086 GT1
50/50
11.14911.149
3152421Z1-086 GT2
50/50
11.14611.146
3152431Z1-086 GT3
50/50
11.14611.146
3152441Z1-086 ST
50/50
19.40819.408
913392Y1-086 E
Adder
2.0705882352941181.76
916192Z1-068 E
Adder
1.77058823529411761.505
923832AB2-022 E
Adder
1.1682352941176470.993
923852AB2-025 E
Adder
1.15058823529411770.978
923862AB2-026 E
Adder
1.31.105
925022AB2-158 E
50/50
9.5359.535
938552AE1-074 E
50/50
1.3051.305
938562AE1-075 E
Adder
1.1082352941176470.942
939312AE1-162 E
Adder
1.29647058823529431.102
946262AF1-291 E
Adder
1.261.071
957492AF2-043 E
Adder
1.341.139
966001AG1-469 C
Adder
1.46235294117647091.243
966002AG1-469 E
Adder
0.73058823529411760.621
901082W1-029 E
Adder
30.02588235294117425.522
917122Z2-027 E
Adder
1.26588235294117671.076
925522AC1-027 E
Adder
1.14588235294117660.974
942001AE2-212 C
Adder
1.96941176470588241.674
942002AE2-212 E
Adder
1.31294117647058851.116
957871AF2-081 C
Adder
9.4164705882352948.004
957872AF2-081 E
Adder
4.0352941176470593.43
958161AF2-110 C
Adder
1.28941176470588251.096
958162AF2-110 E
Adder
2.0505882352941181.743
3147223TWITTYS
Adder
0.89294117647058820.759
926071AC1-086 C
Adder
19.96117647058823516.967
926072AC1-086 E
Adder
9.0847058823529427.722
936261AD2-033 C
Adder
12.2210.387
936262AD2-033 E
Adder
8.1458823529411776.924
933291AC2-141 C
Adder
28.56588235294117724.281
933292AC2-141 E
Adder
12.19411764705882510.365
934621AD1-088 C
Adder
9.5599999999999998.126
934622AD1-088 E
Adder
4.6035294117647063.913
939411AE1-173 C
50/50
94.23794.237
939412AE1-173 E
50/50
62.82462.824
934012AD1-025 E
Adder
8.6341176470588247.339
933981AD1-022 C
Adder
8.247.004
933982AD1-022 E
Adder
4.4858823529411773.813
962572AG1-106 E
Adder
1.12941176470588230.96
962571AG1-106 C
Adder
2.58235294117647032.195
208901BRIS G2
50/50
-3.245-3.245
3145946PLYMOUTH TP
Adder
0.30352941176470590.258
3146326AYDLETT TAP
Adder
1.27764705882352961.086
316192AB2-158 C
50/50
3.5873.587
316233AE1-074 C
50/50
2.5912.591
316240AF1-291 C
Adder
1.88941176470588261.606
316336AC2-165 C
Adder
10.1788235294117648.652
917332KELFORD E
Adder
1.54588235294117651.314
924516AB2-100 E1
Adder
2.82.38
924517AB2-100 E2
Adder
2.82.38
934065AD1-033 E
Adder
4.7282352941176474.019
937226AE2-253 E
Adder
5.5047058823529414.679
918512AA1-065 E OP
Adder
5.2011764705882364.421
919153AA1-139 E2
Adder
3.8505882352941183.273
919152AA1-139 E1
Adder
3.8505882352941183.273
920692AA2-178 E
Adder
3.86941176470588263.289
923994AB2-040_E
Adder
5.8811764705882354.999
924022AB2-043 E O1
Adder
4.8811764705882354.149
924814AB2-134 E
Adder
10.9235294117647069.285
316084AB2-161 E
Adder
5.1694117647058834.394
316088AB2-174 E
Adder
6.242352941176475.306
932046AC2-012 E
Adder
12.31647058823529410.469
316311AC2-079 C
Adder
5.3905882352941184.582
932596AC2-079 E
Adder
8.7952941176470587.476
934576AD1-082 E
Adder
4.1188235294117653.501
316349AD2-085 C
Adder
3.23411764705882382.749
936666AD2-085 E
Adder
5.2764705882352954.485
961611AG1-000B C
Adder
13.98823529411764911.89
941591AE2-156 C
Adder
16.83647058823529414.311
944581AF1-123 C
Adder
43.0529411764705936.595
944582AF1-123 E
Adder
98.5858823529411883.798
944591AF1-124 C
Adder
43.2058823529411836.725
944592AF1-124 E
Adder
98.9435294117647184.102
944601AF1-125 C
Adder
42.3894117647058836.031
944602AF1-125 E
Adder
97.0388235294117782.483
964241AG1-285 C
Adder
11.78352941176470610.016
964242AG1-285 E
Adder
7.8564705882352946.678
3137643SOCKMAN
Adder
0.67882352941176470.577
934501AD1-074 C
Adder
31.6952941176470626.941
934502AD1-074 E
Adder
16.13411764705882613.714
934511AD1-075 C
Adder
7.9235294117647066.735
934512AD1-075 E
Adder
4.0341176470588243.429
934612AD1-087 E
Adder
3.5835294117647063.046
935161AD1-151 C
Adder
13.84941176470588311.772
935162AD1-151 E
Adder
0.93764705882352950.797
935172AD1-152 E
Adder
5.2941176470588234.5
937482AD2-202 E
Adder
1.04941176470588250.892
938531AE1-072 C
Adder
16.55647058823529614.073
938532AE1-072 E
Adder
8.6305882352941187.336
939191AE1-149 C
Adder
10.0011764705882348.501
939192AE1-149 E
Adder
6.6670588235294125.667
940431AE2-027 C
Adder
11.3411764705882369.64
940432AE2-027 E
Adder
7.5611764705882356.427
940481AE2-033 C
Adder
15.98588235294117513.588
940482AE2-033 E
Adder
10.777647058823539.161
940541AE2-040 C
Adder
2.84470588235294162.418
940641AE2-051 C
50/50
18.48718.487
940642AE2-051 E
50/50
12.32512.325
941101AE2-104 C
Adder
3.1588235294117652.685
941102AE2-104 E
Adder
5.0223529411764714.269
942461AE2-259 C
Adder
9.2705882352941187.88
942462AE2-259 E
Adder
6.1800000000000015.253
944641AF1-129 C
Adder
88.4505882352941375.183
316303AF2-085
50/50
4.464.46
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.1255.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.02528.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.37921.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
90.8190.81
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5685.568
NYPJM->LTFIMP_NY
CLTF
2.6122.612
LGEELTFEXP_LGEE->PJM
CLTF
1.1951.195
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
CPLELTFEXP_CPLE->PJM
CLTF
10.7510.75
TVALTFEXP_TVA->PJM
CLTF
5.8785.878
MECLTFEXP_MEC->PJM
CLTF
3.6863.686
LAGNLTFEXP_LAGN->PJM
CLTF
7.3867.386
SIGELTFEXP_SIGE->PJM
CLTF
0.2320.232
O66PJM->LTFIMP_O-066
CMTX_NF
35.46935.469

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.7 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4342.97
MW Contribution:2.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
80/20
2.642.64
963041AG1-153 C
80/20
17.24617.246
964791AG1-342 C
80/20
6.5026.502
24728405LEESVG
80/20
0.9740.974
3138533PONTONDP
80/20
0.9780.978
3144293JTRSVLE
80/20
0.6050.605
3151311EDGECMA
80/20
10.35810.358
3151531CLOVER1
80/20
32.84832.848
3151541CLOVER2
80/20
32.5432.54
3151561HALLBR1
80/20
1.2391.239
3151581KERR 1
80/20
0.650.65
3151591KERR 2
80/20
1.8191.819
3151601KERR 3
80/20
1.8191.819
3151611KERR 4
80/20
1.8191.819
3151621KERR 5
80/20
1.8191.819
942671AE2-283 C
80/20
3.7323.732
942751AE2-291 C
80/20
13.51213.512
943811AF1-049 C
80/20
9.4269.426
944011AF1-069 C
80/20
38.91238.912
959311AF2-222 C
80/20
25.13225.132
3151631KERR 6
80/20
1.8191.819
3151641KERR 7
80/20
1.8191.819
3152661PLYWOOD A
80/20
2.3542.354
316118AC1-105 C
80/20
1.7691.769
316129AC1-054 C
80/20
1.1861.186
316131AB2-060 C
80/20
2.3152.315
940081AE1-250 C
80/20
13.65313.653
941031AE2-094 C
80/20
119.094119.094
941801AE2-185 C
80/20
4.7984.798
946301AF1-294 C
80/20
5.4265.426
957481AF2-042 C
80/20
148.174148.174
958211AF2-115 C
80/20
3.33.3
3151021BRUNSWICKG1
80/20
25.36825.368
3151031BRUNSWICKG2
80/20
25.36825.368
3151041BRUNSWICKG3
80/20
25.36825.368
3151051BRUNSWICKS1
80/20
52.70552.705
3152411Z1-086 GT1
80/20
32.08832.088
3152421Z1-086 GT2
80/20
32.07932.079
3152431Z1-086 GT3
80/20
32.07932.079
3152441Z1-086 ST
80/20
55.85455.854
957601AF2-054 C
Adder
-1.8941176470588237-1.61
964211AG1-282 C
Adder
-1.7882352941176471-1.52
942001AE2-212 C
Adder
-2.1176470588235294-1.8
936261AD2-033 C
80/20
19.83719.837
941671AE2-166 C
80/20
5.7085.708
933291AC2-141 C
Adder
-33.98823529411765-28.89
934621AD1-088 C
80/20
24.38424.384
24684305SMG1
80/20
1.1751.175
24684405SMG2
80/20
3.2353.235
24684505SMG3
80/20
1.9881.988
24684605SMG4
80/20
3.2353.235
24684705SMG5
80/20
1.2291.229
316003AC1-222 C
80/20
1.9581.958
316034AC1-036 C
80/20
0.3540.354
316049AB1-081 C OP
80/20
0.9630.963
316222AC1-221 C
80/20
2.9052.905
316237AB2-079 C O1
80/20
0.5160.516
316238AB2-078 C O1
80/20
0.5160.516
316239AB2-077 C O1
80/20
0.5160.516
316240AF1-291 C
Adder
-2.031764705882353-1.727
316248AF1-058 C
80/20
0.6420.642
316263AC1-034 C
80/20
4.5164.516
316283AC2-100 C
80/20
2.3262.326
316322AB2-045 C
80/20
0.2670.267
316217AC1-145 C
80/20
0.4120.412
270197AC1-083 C
80/20
0.9970.997
313527AB2-043 C
80/20
0.8060.806
316359AB2-059 C OP
80/20
1.1351.135
316197AC1-042 C
80/20
0.3460.346
316123AC1-075 C
80/20
1.5121.512
316205AC1-080 C
80/20
0.5050.505
962561AG1-105 C
80/20
15.92115.921
964241AG1-285 C
80/20
19.39519.395
934611AD1-087 C
80/20
3.2323.232
935171AD1-152 C
80/20
3.2243.224
936161AD2-022 C
80/20
12.80112.801
936171AD2-023 C
80/20
7.4677.467
937481AD2-202 C
80/20
0.9380.938
938531AE1-072 C
Adder
-16.896470588235296-14.362
940641AE2-051 C
Adder
-22.240000000000002-18.904
941431AE2-140 C
80/20
14.14314.143
942461AE2-259 C
80/20
14.02314.023
944641AF1-129 C
Adder
-95.19529411764705-80.916
938741AE1-100 C
80/20
0.7290.729
940601AE2-047 C
80/20
4.254.25
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.6199.619
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.77474.774
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.81246.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
177.277177.277
NYPJM->LTFIMP_NY
CLTF
2.1882.188
LGEELTFEXP_LGEE->PJM
CLTF
2.8852.885
WECLTFEXP_WEC->PJM
CLTF
1.5251.525
CPLELTFEXP_CPLE->PJM
CLTF
20.16220.162
TVALTFEXP_TVA->PJM
CLTF
12.22612.226
MECLTFEXP_MEC->PJM
CLTF
8.7578.757
LAGNLTFEXP_LAGN->PJM
CLTF
15.4915.49
SIGELTFEXP_SIGE->PJM
CLTF
0.550.55

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.59 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4175.62
MW Contribution:2.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
80/20
2.642.64
963041AG1-153 C
80/20
17.24617.246
964791AG1-342 C
80/20
6.5026.502
24728405LEESVG
80/20
0.9740.974
3138533PONTONDP
80/20
0.9780.978
3144293JTRSVLE
80/20
0.6050.605
3151311EDGECMA
80/20
10.35810.358
3151531CLOVER1
80/20
32.84832.848
3151541CLOVER2
80/20
32.5432.54
3151561HALLBR1
80/20
1.2391.239
3151581KERR 1
80/20
0.650.65
3151591KERR 2
80/20
1.8191.819
3151601KERR 3
80/20
1.8191.819
3151611KERR 4
80/20
1.8191.819
3151621KERR 5
80/20
1.8191.819
942671AE2-283 C
80/20
3.7323.732
942751AE2-291 C
80/20
13.51213.512
943811AF1-049 C
80/20
9.4269.426
959311AF2-222 C
80/20
25.13225.132
3151631KERR 6
80/20
1.8191.819
3151641KERR 7
80/20
1.8191.819
3152661PLYWOOD A
80/20
2.3542.354
316118AC1-105 C
80/20
1.7691.769
316129AC1-054 C
80/20
1.1861.186
316131AB2-060 C
80/20
2.3152.315
940081AE1-250 C
80/20
13.65313.653
941801AE2-185 C
80/20
4.7984.798
946301AF1-294 C
80/20
5.4265.426
957481AF2-042 C
80/20
148.174148.174
958211AF2-115 C
80/20
3.33.3
3151021BRUNSWICKG1
80/20
25.36825.368
3151031BRUNSWICKG2
80/20
25.36825.368
3151041BRUNSWICKG3
80/20
25.36825.368
3151051BRUNSWICKS1
80/20
52.70552.705
3152411Z1-086 GT1
80/20
32.08832.088
3152421Z1-086 GT2
80/20
32.07932.079
3152431Z1-086 GT3
80/20
32.07932.079
3152441Z1-086 ST
80/20
55.85455.854
957601AF2-054 C
Adder
-1.8941176470588237-1.61
964211AG1-282 C
Adder
-1.7882352941176471-1.52
942001AE2-212 C
Adder
-2.1176470588235294-1.8
936261AD2-033 C
80/20
19.83719.837
941671AE2-166 C
80/20
5.7085.708
933291AC2-141 C
Adder
-33.98823529411765-28.89
934621AD1-088 C
80/20
24.38424.384
24684305SMG1
80/20
1.1751.175
24684405SMG2
80/20
3.2353.235
24684505SMG3
80/20
1.9881.988
24684605SMG4
80/20
3.2353.235
24684705SMG5
80/20
1.2291.229
316003AC1-222 C
80/20
1.9581.958
316034AC1-036 C
80/20
0.3540.354
316049AB1-081 C OP
80/20
0.9630.963
316222AC1-221 C
80/20
2.9052.905
316237AB2-079 C O1
80/20
0.5160.516
316238AB2-078 C O1
80/20
0.5160.516
316239AB2-077 C O1
80/20
0.5160.516
316240AF1-291 C
Adder
-2.031764705882353-1.727
316248AF1-058 C
80/20
0.6420.642
316263AC1-034 C
80/20
4.5164.516
316283AC2-100 C
80/20
2.3262.326
316322AB2-045 C
80/20
0.2670.267
316217AC1-145 C
80/20
0.4120.412
270197AC1-083 C
80/20
0.9970.997
313527AB2-043 C
80/20
0.8060.806
316359AB2-059 C OP
80/20
1.1351.135
316197AC1-042 C
80/20
0.3460.346
316123AC1-075 C
80/20
1.5121.512
316205AC1-080 C
80/20
0.5050.505
962561AG1-105 C
80/20
15.92115.921
964241AG1-285 C
80/20
19.39519.395
934611AD1-087 C
80/20
3.2323.232
935171AD1-152 C
80/20
3.2243.224
936161AD2-022 C
80/20
12.80112.801
936171AD2-023 C
80/20
7.4677.467
937481AD2-202 C
80/20
0.9380.938
938531AE1-072 C
Adder
-16.896470588235296-14.362
940641AE2-051 C
Adder
-22.240000000000002-18.904
941431AE2-140 C
80/20
14.14314.143
942461AE2-259 C
80/20
14.02314.023
944641AF1-129 C
Adder
-95.19529411764705-80.916
938741AE1-100 C
80/20
0.7290.729
940601AE2-047 C
80/20
4.254.25
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.6199.619
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.77474.774
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.81246.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
177.277177.277
NYPJM->LTFIMP_NY
CLTF
2.1882.188
LGEELTFEXP_LGEE->PJM
CLTF
2.8852.885
WECLTFEXP_WEC->PJM
CLTF
1.5251.525
CPLELTFEXP_CPLE->PJM
CLTF
20.16220.162
TVALTFEXP_TVA->PJM
CLTF
12.22612.226
MECLTFEXP_MEC->PJM
CLTF
8.7578.757
LAGNLTFEXP_LAGN->PJM
CLTF
15.4915.49
SIGELTFEXP_SIGE->PJM
CLTF
0.550.55

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.18 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3902.62
MW Contribution:1.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.80588235294117660.685
961791AG1-021 C
Adder
1.57882352941176471.342
961941AG1-037 C
Adder
0.44235294117647060.376
963041AG1-153 C
80/20
5.5365.536
964791AG1-342 C
Adder
3.06352941176470632.604
966621AG1-532 C
80/20
1.2551.255
3138533PONTONDP
Adder
0.58470588235294120.497
3147043LAWRENC
80/20
0.2730.273
3151311EDGECMA
Adder
13.28823529411764811.295
3151531CLOVER1
80/20
11.76811.768
3151541CLOVER2
80/20
11.65811.658
934521AD1-076 C
Adder
10.6788235294117659.077
944011AF1-069 C
80/20
13.03613.036
959311AF2-222 C
Adder
14.6623529411764712.463
960081AF2-299 C
80/20
1.6731.673
941031AE2-094 C
80/20
39.89839.898
946281AF1-292 C
80/20
1.3851.385
946301AF1-294 C
Adder
3.2458823529411762.759
957481AF2-042 C
80/20
51.00351.003
957861AF2-080 C
Adder
6.57294117647058855.587
958211AF2-115 C
Adder
1.97411764705882351.678
938771AE1-103 C
80/20
2.5672.567
313526AB2-022 C
80/20
0.3280.328
3150651CHESTF6
Adder
14.84823529411764812.621
3150731STONECA
Adder
5.3258823529411774.527
3150831SPRUNCA
Adder
7.6235294117647066.48
3150841SPRUNCB
Adder
7.6235294117647066.48
3150921YORKTN3
Adder
90.5694117647058876.984
934861AD1-115 C
Adder
2.8482352941176472.421
942341AE2-247 C
80/20
1.2991.299
943461AF1-017 C
80/20
1.1751.175
3150981CHESPKA
80/20
0.3780.378
3150991CHESPKB
80/20
0.6270.627
3151021BRUNSWICKG1
80/20
8.1438.143
3151031BRUNSWICKG2
80/20
8.1438.143
3151041BRUNSWICKG3
80/20
8.1438.143
3151051BRUNSWICKS1
80/20
16.91816.918
3151081ELIZAR1
80/20
2.7822.782
3151091ELIZAR2
80/20
2.7332.733
3151101ELIZAR3
80/20
2.8172.817
3151721LOISA A
80/20
2.6942.694
3151731LOISA B
80/20
2.7082.708
3151741LOISA C
80/20
2.7082.708
3151751LOISA D
80/20
2.7082.708
3151761LOISA E
80/20
5.5225.522
3151771S ANNAG1
80/20
2.6512.651
3151781S ANNAS1
80/20
1.3621.362
3151791S ANNAG2
80/20
2.6512.651
3151801S ANNAS2
80/20
1.3621.362
3152251N ANNA1
80/20
89.03589.035
3152261N ANNA2
80/20
89.07389.073
3152411Z1-086 GT1
80/20
10.43710.437
3152421Z1-086 GT2
80/20
10.43410.434
3152431Z1-086 GT3
80/20
10.43410.434
3152441Z1-086 ST
80/20
18.16818.168
3156056W1-029WIND
80/20
0.6760.676
966001AG1-469 C
80/20
1.9591.959
942001AE2-212 C
Adder
1.82117647058823541.548
957871AF2-081 C
80/20
8.7288.728
958161AF2-110 C
80/20
1.1951.195
926071AC1-086 C
Adder
18.5623529411764715.778
927021AC1-189 C
Adder
7.2364705882352946.151
936261AD2-033 C
Adder
11.4505882352941189.733
933291AC2-141 C
80/20
26.46526.465
934621AD1-088 C
80/20
8.9588.958
939411AE1-173 C
80/20
87.96287.962
916191Z1-068 C
80/20
0.0380.038
933981AD1-022 C
Adder
7.6458823529411766.499
962571AG1-106 C
Adder
2.40117647058823552.041
208900BRIS G1
80/20
-2.628-2.628
208901BRIS G2
80/20
-3.11-3.11
316023AB2-100 C2
80/20
0.8620.862
316036AC1-147 C
80/20
0.320.32
316164AC1-076_C
80/20
1.1141.114
316170AC1-121 C
80/20
2.7242.724
316185AD1-033 C
80/20
1.071.07
316192AB2-158 C
80/20
3.6253.625
316233AE1-074 C
80/20
2.4172.417
316240AF1-291 C
Adder
1.7435294117647061.482
316246AF1-032 C
80/20
0.2480.248
316254AC1-120 C
80/20
7.9327.932
316257AC1-043 C
Adder
5.697647058823534.843
316258AE1-075 C
80/20
0.3460.346
316263AC1-034 C
Adder
5.6858823529411774.833
316274AC1-208 C
Adder
7.857647058823536.679
316294AC1-161 C
80/20
4.314.31
316305AF2-043 C
80/20
0.3030.303
316313AB2-026 C
80/20
0.3770.377
316315AB2-025 C
80/20
0.3750.375
316316AC1-027 C
80/20
0.2750.275
316320Y1-086 C
80/20
0.1920.192
316321Z2-027 C
80/20
0.3170.317
316336AC2-165 C
80/20
9.6099.609
316365AB2-100 C1
80/20
0.8620.862
316405AF2-144 C
80/20
0.2940.294
316017AA1-139 ULT1
80/20
0.9420.942
316018AA1-139 ULT2
80/20
0.9420.942
316083AB2-161 C
80/20
0.4780.478
316087AB2-174 C
80/20
1.0461.046
316044AC1-158 C1
80/20
19.41919.419
316045AC1-158 C2
80/20
19.41919.419
316375AC2-012 C
80/20
1.1731.173
316311AC2-079 C
80/20
4.9964.996
316381AD1-082 C
80/20
1.0891.089
316349AD2-085 C
80/20
2.9972.997
316388AE2-253 GEN
80/20
1.711.71
961611AG1-000B C
Adder
12.91058823529411910.974
941591AE2-156 C
80/20
15.615.6
944581AF1-123 C
80/20
39.90939.909
944591AF1-124 C
80/20
40.05140.051
944601AF1-125 C
80/20
39.29539.295
962561AG1-105 C
Adder
7.70470588235294156.549
964241AG1-285 C
Adder
11.0294117647058829.375
3137643SOCKMAN
Adder
0.6317647058823530.537
934321AD1-056 C
Adder
5.4329411764705894.618
934331AD1-057 C
Adder
3.0305882352941182.576
934501AD1-074 C
Adder
29.40470588235294324.994
934511AD1-075 C
Adder
7.3517647058823536.249
934611AD1-087 C
80/20
1.1591.159
935161AD1-151 C
Adder
12.7647058823529410.85
935171AD1-152 C
80/20
1.1991.199
937481AD2-202 C
80/20
0.3360.336
938531AE1-072 C
80/20
15.34615.346
939191AE1-149 C
80/20
9.2629.262
940431AE2-027 C
Adder
10.4682352941176488.898
940481AE2-033 C
80/20
14.89114.891
940541AE2-040 C
80/20
2.652.65
940641AE2-051 C
80/20
17.2917.29
941101AE2-104 C
80/20
2.9282.928
942461AE2-259 C
Adder
8.7329411764705887.423
944641AF1-129 C
Adder
81.5517647058823669.319
3150851SPRUNCC
80/20
0.1370.137
3150861SPRUNCD
80/20
0.1370.137
316303AF2-085
80/20
4.1844.184
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.744.74
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.96121.961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.49718.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
83.40383.403
NYPJM->LTFIMP_NY
CLTF
2.5322.532
LGEELTFEXP_LGEE->PJM
CLTF
0.9710.971
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
CPLELTFEXP_CPLE->PJM
CLTF
9.9459.945
TVALTFEXP_TVA->PJM
CLTF
5.1955.195
MECLTFEXP_MEC->PJM
CLTF
3.0623.062
LAGNLTFEXP_LAGN->PJM
CLTF
6.5316.531
SIGELTFEXP_SIGE->PJM
CLTF
0.1910.191

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.07 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3866.79
MW Contribution:1.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.9317647058823530.792
961791AG1-021 C
Adder
1.70000000000000021.445
961941AG1-037 C
Adder
0.52705882352941180.448
963041AG1-153 C
Adder
5.7647058823529424.9
964791AG1-342 C
Adder
3.32117647058823542.823
966621AG1-532 C
Adder
1.43529411764705881.22
3138533PONTONDP
Adder
0.62941176470588240.535
3151311EDGECMA
Adder
15.22352941176470512.94
934521AD1-076 C
Adder
12.96470588235294111.02
944011AF1-069 C
80/20
13.51813.518
959311AF2-222 C
Adder
15.85294117647058913.475
960081AF2-299 C
Adder
1.91411764705882351.627
941031AE2-094 C
80/20
41.37341.373
946281AF1-292 C
Adder
1.58470588235294121.347
946301AF1-294 C
Adder
3.4941176470588242.97
957481AF2-042 C
Adder
53.64117647058823545.595
957861AF2-080 C
Adder
7.6458823529411766.499
958211AF2-115 C
Adder
2.12470588235294141.806
938771AE1-103 C
Adder
3.162.686
3142366NRTHEST
80/20
0.20.2
3143096IRON208
80/20
0.4840.484
3150601CHESTF5
Adder
68.9811764705882458.634
3150651CHESTF6
80/20
20.66420.664
3150731STONECA
80/20
7.6067.606
3150761HOPPOLC
80/20
1.6841.684
3150771HOPHCF1
80/20
2.6772.677
3150781HOPHCF2
80/20
2.6772.677
3150791HOPHCF3
80/20
2.6772.677
3150801HOPHCF4
80/20
4.0644.064
3150831SPRUNCA
80/20
10.21910.219
3150841SPRUNCB
80/20
10.21910.219
3150921YORKTN3
Adder
130.26705882352942110.727
936591AD2-074 C
Adder
5.7258823529411764.867
942341AE2-247 C
Adder
1.64235294117647061.396
943461AF1-017 C
Adder
1.48588235294117641.263
943741AF1-042 C
Adder
2.9964705882352942.547
961951AG1-038 C
Adder
3.3117647058823532.815
966661AG1-536 C
Adder
5.5082352941176484.682
966871AG1-558 C
Adder
2.50941176470588222.133
966881AG1-559 C
Adder
2.3964705882352942.037
3150991CHESPKB
80/20
0.7960.796
3151081ELIZAR1
80/20
3.5273.527
3151091ELIZAR2
80/20
3.4653.465
3151101ELIZAR3
80/20
3.5723.572
3152251N ANNA1
80/20
55.32355.323
3152261N ANNA2
80/20
55.34655.346
3152331SURRY 2
80/20
27.29427.294
957601AF2-054 C
Adder
2.2117647058823531.88
962861AG1-135 C
Adder
6.222352941176475.289
963611AG1-210 C
Adder
0.66705882352941170.567
964211AG1-282 C
Adder
2.0317647058823531.727
942001AE2-212 C
80/20
2.3972.397
957871AF2-081 C
Adder
10.989.333
958161AF2-110 C
Adder
1.50117647058823531.276
926071AC1-086 C
Adder
21.50823529411764718.282
927021AC1-189 C
Adder
8.4188235294117647.156
936261AD2-033 C
Adder
12.4023529411764710.542
933291AC2-141 C
80/20
33.66433.664
934621AD1-088 C
Adder
9.4482352941176488.031
939411AE1-173 C
80/20
97.64897.648
927041AC1-191 C
Adder
10.0729411764705888.562
933981AD1-022 C
Adder
9.2505882352941197.863
962571AG1-106 C
Adder
2.7823529411764712.365
316164AC1-076_C
80/20
0.9930.993
316169AC1-164 GEN
Adder
42.77176470588235436.356
316192AB2-158 C
80/20
2.1182.118
316233AE1-074 C
80/20
2.8192.819
316240AF1-291 C
80/20
2.3942.394
316263AC1-034 C
Adder
6.5105882352941185.534
316274AC1-208 C
Adder
9.0917647058823537.728
316294AC1-161 C
80/20
5.4825.482
316336AC2-165 C
Adder
10.1094117647058828.593
316044AC1-158 C1
80/20
14.96214.962
316045AC1-158 C2
80/20
14.96214.962
316375AC2-012 C
80/20
1.4881.488
316311AC2-079 C
Adder
6.3129411764705885.366
316349AD2-085 C
Adder
3.79058823529411763.222
961611AG1-000B C
Adder
17.55647058823529614.923
941591AE2-156 C
80/20
19.79319.793
944581AF1-123 C
80/20
50.22150.221
944591AF1-124 C
80/20
50.39950.399
944601AF1-125 C
80/20
49.44749.447
944631AF1-128 C
Adder
43.1623529411764736.688
958261AF2-120 C
Adder
6.4035294117647065.443
962561AG1-105 C
Adder
8.3588235294117657.105
964241AG1-285 C
Adder
11.97764705882352810.181
3137643SOCKMAN
Adder
0.72705882352941180.618
934321AD1-056 C
Adder
6.2529411764705895.315
934331AD1-057 C
Adder
3.4882352941176472.965
934501AD1-074 C
Adder
35.6976470588235330.343
934511AD1-075 C
Adder
8.9247058823529427.586
935161AD1-151 C
Adder
17.79176470588235415.123
938531AE1-072 C
Adder
19.2929411764705916.399
939191AE1-149 C
80/20
11.90511.905
939261AE1-157 C
Adder
13.77647058823529511.71
940431AE2-027 C
80/20
14.31814.318
940481AE2-033 C
Adder
17.08117647058823614.519
940541AE2-040 C
Adder
3.03764705882352942.582
940551AE2-041 C
Adder
7.4541176470588246.336
940641AE2-051 C
80/20
18.48818.488
941101AE2-104 C
Adder
3.683.128
942461AE2-259 C
Adder
9.347.939
943471AF1-018 C
Adder
7.4541176470588246.336
944641AF1-129 C
80/20
113.49113.49
3150851SPRUNCC
80/20
0.1830.183
3150861SPRUNCD
80/20
0.1830.183
316303AF2-085
80/20
4.3634.363
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.2865.286
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.65727.657
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.08222.082
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
94.17394.173
NYPJM->LTFIMP_NY
CLTF
2.8062.806
LGEELTFEXP_LGEE->PJM
CLTF
1.2221.222
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
CPLELTFEXP_CPLE->PJM
CLTF
11.08811.088
TVALTFEXP_TVA->PJM
CLTF
6.1396.139
MECLTFEXP_MEC->PJM
CLTF
3.7473.747
LAGNLTFEXP_LAGN->PJM
CLTF
7.6777.677
SIGELTFEXP_SIGE->PJM
CLTF
0.2370.237

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.55 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4631.32
MW Contribution:3.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
1.65764705882352951.409
961792AG1-021 E
Adder
1.4117647058823531.2
961941AG1-037 C
Adder
0.46705882352941180.397
961942AG1-037 E
Adder
0.311764705882352940.265
963041AG1-153 C
Adder
5.7788235294117654.912
963042AG1-153 E
Adder
8.6682352941176477.368
966621AG1-532 C
Adder
1.32117647058823541.123
966622AG1-532 E
Adder
0.88117647058823530.749
3138533PONTONDP
Adder
0.61411764705882350.522
3145413WATKINS
Adder
0.64235294117647070.546
3145723EMPORIA
Adder
0.405882352941176470.345
3147133PAMPLIN
Adder
0.91529411764705890.778
918492AA1-063AE OP
Adder
3.80117647058823543.231
919692AA2-053 E OP
Adder
3.93176470588235333.342
920042AA2-088 E OP
Adder
9.8670588235294128.387
925785AC1-054 E
Adder
3.18705882352941172.709
927146AC1-208 E
Adder
1.16941176470588240.994
934521AD1-076 C
Adder
11.3094117647058829.613
934522AD1-076 E
Adder
5.7635294117647064.899
943172AE2-346 E
Adder
0.56117647058823530.477
944011AF1-069 C
50/50
13.59813.598
944012AF1-069 E
50/50
5.2835.283
959311AF2-222 C
Adder
15.39294117647058813.084
959312AF2-222 E
Adder
10.3129411764705888.766
960081AF2-299 C
Adder
1.76235294117647071.498
960082AF2-299 E
Adder
1.17529411764705880.999
316141AB2-099 E
Adder
0.234117647058823540.199
900672V4-068 E
Adder
0.33058823529411770.281
923263AB1-132 E OP
Adder
5.697647058823534.843
923573AB1-173 E OP
Adder
3.07647058823529432.615
924162AB2-060 E OP
Adder
3.95764705882352933.364
924302AB2-077 E O1
Adder
1.23529411764705891.05
924312AB2-078 E O1
Adder
1.23529411764705891.05
924322AB2-079 E O1
Adder
1.23529411764705891.05
925612AC1-036 E
Adder
0.79294117647058830.674
940492AE2-034 E
Adder
2.85176470588235282.424
941031AE2-094 C
50/50
41.61841.618
941032AE2-094 E
50/50
18.6418.64
946281AF1-292 C
Adder
1.45882352941176461.24
946282AF1-292 E
Adder
0.97294117647058820.827
946301AF1-294 C
Adder
3.4070588235294122.896
946302AF1-294 E
Adder
2.88470588235294122.452
957481AF2-042 C
Adder
53.3270588235294245.328
957482AF2-042 E
Adder
35.55176470588235630.219
958211AF2-115 C
Adder
2.0717647058823531.761
958212AF2-115 E
Adder
1.76470588235294111.5
3145393UNCAMP
Adder
5.65176470588235354.804
916042Z1-036 E
Adder
26.4694117647058822.499
938771AE1-103 C
Adder
2.72117647058823582.313
938772AE1-103 E
Adder
3.75764705882352963.194
933502AC2-165 E
Adder
7.5705882352941176.435
3143316POE
Adder
1.28823529411764711.095
3145256KINGFORK
Adder
0.92470588235294130.786
3145506HICKORY
Adder
2.02235294117647071.719
3150651CHESTF6
Adder
15.92588235294117813.537
3150831SPRUNCA
Adder
8.1435294117647056.922
3150841SPRUNCB
Adder
8.1435294117647056.922
926662AC1-147 E
Adder
1.22588235294117661.042
926755AC1-161 E
Adder
12.0070588235294110.206
927226AC1-216 E
Adder
6.5917647058823535.603
934861AD1-115 C
Adder
2.92.465
934862AD1-115 E
Adder
4.73176470588235354.022
935112AD1-144 E
Adder
0.85764705882352940.729
942341AE2-247 C
Adder
1.38000000000000011.173
942342AE2-247 E
Adder
1.90588235294117661.62
943461AF1-017 C
Adder
1.2482352941176471.061
943462AF1-017 E
Adder
2.03764705882352941.732
943612AF1-032 E
Adder
0.85764705882352940.729
958502AF2-144 E
Adder
1.2588235294117651.07
3151721LOISA A
50/50
2.7312.731
3151731LOISA B
50/50
2.7452.745
3151741LOISA C
50/50
2.7452.745
3151751LOISA D
50/50
2.7452.745
3151761LOISA E
50/50
5.5965.596
3151771S ANNAG1
50/50
2.6852.685
3151781S ANNAS1
50/50
1.381.38
3151791S ANNAG2
50/50
2.6852.685
3151801S ANNAS2
50/50
1.381.38
3152251N ANNA1
50/50
89.57189.571
3152261N ANNA2
50/50
89.60989.609
913392Y1-086 E
Adder
2.03647058823529431.731
916192Z1-068 E
Adder
1.74235294117647071.481
923832AB2-022 E
Adder
1.14941176470588240.977
923852AB2-025 E
Adder
1.1282352941176470.959
923862AB2-026 E
Adder
1.28117647058823541.089
925022AB2-158 E
50/50
9.7219.721
938552AE1-074 E
Adder
1.28235294117647071.09
938562AE1-075 E
Adder
1.0917647058823530.928
939312AE1-162 E
Adder
1.27764705882352961.086
946262AF1-291 E
Adder
1.24470588235294131.058
957492AF2-043 E
Adder
1.31882352941176471.121
966001AG1-469 C
50/50
1.9871.987
966002AG1-469 E
50/50
0.9930.993
901082W1-029 E
Adder
29.54000000000000325.109
917122Z2-027 E
Adder
1.24470588235294131.058
925332AB2-190 E
Adder
6.8164705882352945.794
925522AC1-027 E
Adder
1.1282352941176470.959
925672AC1-043 E
Adder
9.4635294117647078.044
942001AE2-212 C
Adder
1.94235294117647061.651
942002AE2-212 E
Adder
1.2952941176470591.101
957871AF2-081 C
Adder
9.2670588235294127.877
957872AF2-081 E
Adder
3.9717647058823533.376
958161AF2-110 C
Adder
1.26823529411764711.078
958162AF2-110 E
Adder
2.01764705882352931.715
3147223TWITTYS
Adder
0.87882352941176480.747
926071AC1-086 C
Adder
19.57647058823529616.64
926072AC1-086 E
Adder
8.9094117647058837.573
936261AD2-033 C
Adder
12.02117647058823610.218
936262AD2-033 E
Adder
8.0141176470588256.812
933291AC2-141 C
Adder
28.12941176470588223.91
933292AC2-141 E
Adder
12.0070588235294110.206
934621AD1-088 C
Adder
9.3717647058823547.966
934622AD1-088 E
Adder
4.5117647058823533.835
939411AE1-173 C
Adder
92.2811764705882478.439
939412AE1-173 E
Adder
61.5211764705882452.293
934012AD1-025 E
Adder
8.5352941176470597.255
933981AD1-022 C
Adder
8.0941176470588236.88
933982AD1-022 E
Adder
4.4070588235294123.746
962572AG1-106 E
Adder
1.1082352941176470.942
962571AG1-106 C
Adder
2.53176470588235342.152
208900BRIS G1
50/50
-2.836-2.836
208901BRIS G2
50/50
-3.356-3.356
3145946PLYMOUTH TP
Adder
0.29882352941176470.254
3146326AYDLETT TAP
Adder
1.25764705882352931.069
316164AC1-076_C
50/50
1.1311.131
316170AC1-121 C
50/50
2.7692.769
316192AB2-158 C
50/50
3.6573.657
316233AE1-074 C
Adder
2.5458823529411772.164
316240AF1-291 C
Adder
1.86705882352941191.587
316254AC1-120 C
50/50
8.0618.061
316257AC1-043 C
Adder
5.84.93
316274AC1-208 C
Adder
8.2905882352941187.047
316336AC2-165 C
Adder
10.0588235294117668.55
917332KELFORD E
Adder
1.51764705882352961.29
924516AB2-100 E1
Adder
2.74588235294117672.334
924517AB2-100 E2
Adder
2.74588235294117672.334
926206AC1-098 E
Adder
3.35647058823529452.853
926214AC1-099 E
Adder
1.1082352941176470.942
934065AD1-033 E
Adder
4.6541176470588243.956
937226AE2-253 E
Adder
5.4188235294117654.606
926004AC1-076_E
50/50
6.486.48
926486AC1-120 E
50/50
4.1534.153
926502AC1-121 E
50/50
1.3031.303
918512AA1-065 E OP
Adder
5.1070588235294124.341
919153AA1-139 E2
Adder
3.78941176470588253.221
919152AA1-139 E1
Adder
3.78941176470588253.221
920692AA2-178 E
Adder
3.8023529411764713.232
923994AB2-040_E
Adder
5.76941176470588254.904
924022AB2-043 E O1
Adder
4.7941176470588244.075
924814AB2-134 E
Adder
10.7988235294117659.179
316084AB2-161 E
Adder
5.0917647058823544.328
925122AB2-169 E
Adder
5.2764705882352954.485
316088AB2-174 E
Adder
6.1235294117647065.205
316044AC1-158 C1
50/50
19.48619.486
316045AC1-158 C2
50/50
19.48619.486
926739AC1-158 E1
50/50
50.96750.967
926740AC1-158 E2
50/50
50.96750.967
932046AC2-012 E
Adder
12.12705882352941210.308
316311AC2-079 C
Adder
5.3070588235294124.511
932596AC2-079 E
Adder
8.6588235294117667.36
934576AD1-082 E
Adder
4.0564705882352943.448
316349AD2-085 C
Adder
3.1835294117647062.706
936666AD2-085 E
Adder
5.195294117647064.416
961611AG1-000B C
Adder
13.8152941176470611.743
941591AE2-156 C
Adder
16.57647058823529614.09
944581AF1-123 C
Adder
42.37411764705882436.018
944582AF1-123 E
Adder
97.0317647058823782.477
944591AF1-124 C
Adder
42.5247058823529436.146
944592AF1-124 E
Adder
97.3823529411764882.775
944601AF1-125 C
Adder
41.7211764705882435.463
944602AF1-125 E
Adder
95.5082352941176581.182
962561AG1-105 C
Adder
8.0894117647058836.876
962562AG1-105 E
Adder
5.3929411764705884.584
964241AG1-285 C
Adder
11.5811764705882349.844
964242AG1-285 E
Adder
7.7211764705882356.563
3137643SOCKMAN
Adder
0.66588235294117650.566
932632AC2-084 E
Adder
2.96705882352941152.522
934501AD1-074 C
Adder
31.13882352941176626.468
934502AD1-074 E
Adder
15.85176470588235313.474
934511AD1-075 C
Adder
7.7847058823529426.617
934512AD1-075 E
Adder
3.96235294117647063.368
934612AD1-087 E
Adder
3.50941176470588272.983
935161AD1-151 C
Adder
13.69411764705882511.64
935162AD1-151 E
Adder
9.1294117647058827.76
935172AD1-152 E
Adder
5.1847058823529414.407
937482AD2-202 E
Adder
1.02705882352941180.873
938531AE1-072 C
Adder
16.29411764705882213.85
938532AE1-072 E
Adder
8.4941176470588247.22
939191AE1-149 C
Adder
9.8529411764705898.375
939192AE1-149 E
Adder
6.5694117647058825.584
940431AE2-027 C
Adder
11.2058823529411789.525
940432AE2-027 E
Adder
7.4705882352941186.35
940481AE2-033 C
Adder
15.6752941176470613.324
940482AE2-033 E
Adder
10.5670588235294118.982
940541AE2-040 C
Adder
2.78823529411764742.37
940641AE2-051 C
50/50
18.07818.078
940642AE2-051 E
50/50
12.05212.052
941101AE2-104 C
Adder
3.10941176470588232.643
941102AE2-104 E
Adder
4.9423529411764714.201
942461AE2-259 C
Adder
9.1658823529411777.791
942462AE2-259 E
Adder
6.1105882352941175.194
944641AF1-129 C
Adder
87.4717647058823574.351
316303AF2-085
50/50
4.3644.364
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.0035.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.22125.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.23820.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
88.42988.429
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7645.764
NYPJM->LTFIMP_NY
CLTF
2.7142.714
LGEELTFEXP_LGEE->PJM
CLTF
1.0981.098
WECLTFEXP_WEC->PJM
CLTF
0.5410.541
CPLELTFEXP_CPLE->PJM
CLTF
10.49610.496
TVALTFEXP_TVA->PJM
CLTF
5.6275.627
MECLTFEXP_MEC->PJM
CLTF
3.4183.418
LAGNLTFEXP_LAGN->PJM
CLTF
7.0687.068
SIGELTFEXP_SIGE->PJM
CLTF
0.2140.214
O66PJM->LTFIMP_O-066
CMTX_NF
36.7236.72

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4234.7
MW Contribution:2.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
80/20
2.3092.309
963041AG1-153 C
80/20
17.10317.103
964791AG1-342 C
80/20
5.7665.766
24728405LEESVG
80/20
0.8940.894
3138533PONTONDP
80/20
0.8550.855
3144293JTRSVLE
80/20
0.5290.529
3151531CLOVER1
80/20
28.86928.869
3151541CLOVER2
80/20
28.59828.598
3151561HALLBR1
80/20
1.1241.124
3151581KERR 1
80/20
0.5770.577
3151591KERR 2
80/20
1.6151.615
3151601KERR 3
80/20
1.6151.615
3151611KERR 4
80/20
1.6151.615
3151621KERR 5
80/20
1.6151.615
942671AE2-283 C
80/20
3.3963.396
942751AE2-291 C
80/20
12.11212.112
943811AF1-049 C
80/20
8.9298.929
944011AF1-069 C
80/20
45.1645.16
959311AF2-222 C
80/20
22.05622.056
3151631KERR 6
80/20
1.6151.615
3151641KERR 7
80/20
1.6151.615
3152661PLYWOOD A
80/20
2.0932.093
316118AC1-105 C
80/20
1.5721.572
316129AC1-054 C
80/20
1.0481.048
316131AB2-060 C
80/20
2.042.04
940081AE1-250 C
80/20
12.86112.861
941031AE2-094 C
80/20
138.215138.215
941801AE2-185 C
80/20
4.3664.366
946301AF1-294 C
80/20
4.7464.746
957481AF2-042 C
80/20
129.887129.887
958211AF2-115 C
80/20
2.8862.886
3151021BRUNSWICKG1
80/20
25.15625.156
3151031BRUNSWICKG2
80/20
25.15625.156
3151041BRUNSWICKG3
80/20
25.15625.156
3151051BRUNSWICKS1
80/20
52.26552.265
3152411Z1-086 GT1
80/20
33.47333.473
3152421Z1-086 GT2
80/20
33.46433.464
3152431Z1-086 GT3
80/20
33.46433.464
3152441Z1-086 ST
80/20
58.26658.266
957601AF2-054 C
Adder
-1.8-1.53
964211AG1-282 C
Adder
-1.7011764705882353-1.446
942001AE2-212 C
Adder
-2.010588235294118-1.709
936261AD2-033 C
80/20
17.43217.432
941671AE2-166 C
80/20
5.45.4
933291AC2-141 C
Adder
-32.203529411764706-27.373
934621AD1-088 C
80/20
21.36821.368
24684305SMG1
80/20
1.0911.091
24684405SMG2
80/20
3.0033.003
24684505SMG3
80/20
1.8451.845
24684605SMG4
80/20
3.0033.003
24684705SMG5
80/20
1.1411.141
316003AC1-222 C
80/20
1.7441.744
316034AC1-036 C
80/20
0.3110.311
316049AB1-081 C OP
80/20
0.9230.923
316222AC1-221 C
80/20
2.6372.637
316237AB2-079 C O1
80/20
0.4550.455
316238AB2-078 C O1
80/20
0.4550.455
316239AB2-077 C O1
80/20
0.4550.455
316240AF1-291 C
Adder
-1.9317647058823528-1.642
316248AF1-058 C
80/20
0.5710.571
316263AC1-034 C
80/20
4.3284.328
316283AC2-100 C
80/20
2.1162.116
316322AB2-045 C
80/20
0.2270.227
316217AC1-145 C
80/20
0.3750.375
270197AC1-083 C
80/20
0.9340.934
313527AB2-043 C
80/20
0.7110.711
316359AB2-059 C OP
80/20
1.0881.088
316197AC1-042 C
80/20
0.3150.315
316123AC1-075 C
80/20
1.3531.353
316205AC1-080 C
80/20
0.4520.452
962561AG1-105 C
80/20
14.10814.108
964241AG1-285 C
80/20
17.07617.076
934611AD1-087 C
80/20
2.842.84
935171AD1-152 C
80/20
2.8492.849
936161AD2-022 C
80/20
12.15912.159
936171AD2-023 C
80/20
7.0937.093
937481AD2-202 C
80/20
0.8240.824
938531AE1-072 C
Adder
-16.01294117647059-13.611
940641AE2-051 C
Adder
-21.040000000000003-17.884
941431AE2-140 C
80/20
13.39313.393
942461AE2-259 C
80/20
12.19912.199
944641AF1-129 C
Adder
-90.49176470588236-76.918
938741AE1-100 C
80/20
0.690.69
940601AE2-047 C
80/20
4.0274.027
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.2639.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.06671.066
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.76444.764
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
170.641170.641
NYPJM->LTFIMP_NY
CLTF
2.1082.108
LGEELTFEXP_LGEE->PJM
CLTF
2.7422.742
WECLTFEXP_WEC->PJM
CLTF
1.451.45
CPLELTFEXP_CPLE->PJM
CLTF
19.41719.417
TVALTFEXP_TVA->PJM
CLTF
11.71211.712
MECLTFEXP_MEC->PJM
CLTF
8.3488.348
LAGNLTFEXP_LAGN->PJM
CLTF
14.84614.846
SIGELTFEXP_SIGE->PJM
CLTF
0.5240.524
CONTINGENCY 'DVP_P4-6: CHASE C T342_SRT-A'
 OPEN BUS 313527   /*AB2-043 C      0.6
 OPEN BUS 313528   /*AB2-043 COL   34.5
 OPEN BUS 313529   /*3BLUESTONE   115.0
 OPEN BUS 314267   /*3CHASCTY2    115.0
 OPEN BUS 314518   /*3CHASC_1     115.0
 OPEN BUS 314681   /*3CHASCTY     115.0
 OPEN BUS 924022   /*AB2-043 E O1   0.6
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 246_SRT-A'
 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1   /*6SUFFOLK     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1   /*6EARLEYS     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1   /*6NUCO TP     230.0 - 6NUCOR       230.0
 OPEN BUS 314575                                   /*6NUCO TP     230.0
 OPEN BUS 314590                                   /*6NUCOR       230.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314063 TO BUS 314916 CKT 1                /*6MORRSVL     230.0 - 8MORRSVL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BUS 314897                                                /*8MORRS_1     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 568T575_SRT-A'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1   /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1   /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 314940 TO BUS 941030 CKT 1   /*8ROGERS RD   500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314691 to 314692 ckt 1
314691 to 314692 ckt 2
314282 to 314285 ckt 1
314563 to 940480 ckt 1
314435 to 314282 ckt 1
314902 to 314914 ckt 1
314914 to 314918 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314936 to 314902 ckt 1
314934 to 314916 ckt 1
941030 to 314902 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P1-2: LN 235_SRT-A
OPAC121.52 %182.64B221.957.85
GD1DVP
3FLAT CREEK-3MORAN 115.0 kV Ckt 1 line
DVP_P1-2: LN 1045_SRT-A
OPAC119.98 %203.98B244.7419.99
GD1DVP
3LONEPN-3FLAT CREEK 115.0 kV Ckt 1 line
DVP_P1-2: LN 1045_SRT-A
OPAC120.01 %203.98B244.7919.99
GD1DVP
3MORAN-3FARMVIL 115.0 kV Ckt 1 line
DVP_P1-2: LN 1045_SRT-A
OPAC117.13 %203.98B238.9319.99
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC109.21 %678.68B741.184.59
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC108.15 %678.68B734.034.59
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC105.97 %661.76B701.294.28
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC108.64 %661.76B718.914.28
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-2
OPAC102.38 %661.76B677.524.28
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 578_SRT-S-1
OPAC111.77 %3220.44B3599.453.26
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Base Case
OPAC104.12 %3220.44A3352.993.02
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
AEP_P1-2_242515_248184_SRT-A
OPAC101.34 %3220.44B3263.623.62
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
OPAC108.69 %4070.2B4423.725.72
GD1DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC106.42 %2442.12B2598.932.46
GD1DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
OPAC105.93 %4070.2B4311.714.98

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 235_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:121.52 %
Rating:182.64 MVA
Rating Type:B
MVA to Mitigate:221.95
MW Contribution:7.85
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 235_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:149.01 %
Rating:182.64 MVA
Rating Type:B
MVA to Mitigate:272.15
MW Contribution:8.8
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
4.2384.238
961792AG1-021 E
50/50
3.613.61
964791AG1-342 C
Adder
1.70117647058823531.446
964792AG1-342 E
Adder
1.13411764705882350.964
3138533PONTONDP
50/50
1.571.57
3144293JTRSVLE
50/50
0.9750.975
3147133PAMPLIN
50/50
2.4852.485
926274AC1-105 E
Adder
1.0752941176470590.914
943902AF1-058 E
Adder
0.414117647058823530.352
959311AF2-222 C
50/50
24.13324.133
959312AF2-222 E
50/50
16.16916.169
316131AB2-060 C
50/50
1.1311.131
924162AB2-060 E OP
50/50
3.2583.258
924302AB2-077 E O1
50/50
0.9010.901
924312AB2-078 E O1
50/50
0.9010.901
924322AB2-079 E O1
50/50
0.9010.901
925612AC1-036 E
50/50
1.1371.137
941011AE2-092 C
Adder
-4.856470588235294-4.128
946301AF1-294 C
50/50
8.7128.712
946302AF1-294 E
50/50
7.3787.378
958211AF2-115 C
50/50
5.2985.298
958212AF2-115 E
50/50
4.5134.513
3147223TWITTYS
50/50
1.261.26
936261AD2-033 C
50/50
18.4818.48
936262AD2-033 E
50/50
12.3212.32
934621AD1-088 C
Adder
2.9611764705882352.517
934622AD1-088 E
Adder
1.42588235294117641.212
316034AC1-036 C
50/50
0.310.31
316237AB2-079 C O1
50/50
0.2210.221
316238AB2-078 C O1
50/50
0.2210.221
316239AB2-077 C O1
50/50
0.2210.221
313527AB2-043 C
50/50
0.3610.361
924022AB2-043 E O1
50/50
3.623.62
962561AG1-105 C
Adder
4.583.893
962562AG1-105 E
Adder
3.05294117647058852.595
964241AG1-285 C
50/50
8.3818.381
964242AG1-285 E
50/50
5.5885.588
938821AE1-108 C
Adder
-5.455294117647059-4.637
942461AE2-259 C
50/50
33.29833.298
942462AE2-259 E
50/50
22.19822.198
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.7150.715
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.1372.137
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.0592.059
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.68211.682
G-007PJM->LTFIMP_G-007
CMTX_NF
0.2090.209
NYPJM->LTFIMP_NY
CLTF
0.1040.104
LGEELTFEXP_LGEE->PJM
CLTF
0.0840.084
WECLTFEXP_WEC->PJM
CLTF
0.0450.045
CPLELTFEXP_CPLE->PJM
CLTF
1.51.5
TVALTFEXP_TVA->PJM
CLTF
0.5920.592
MECLTFEXP_MEC->PJM
CLTF
0.3150.315
LAGNLTFEXP_LAGN->PJM
CLTF
0.7670.767
SIGELTFEXP_SIGE->PJM
CLTF
0.0180.018
O66PJM->LTFIMP_O-066
CMTX_NF
1.3381.338

Details for 3FLAT CREEK-3MORAN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1045_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
3FLAT CREEK-3MORAN 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1045_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:119.98 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:244.74
MW Contribution:19.99
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
3FLAT CREEK-3MORAN 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1045_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:119.95 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:244.68
MW Contribution:19.99
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
10.79610.796
961792AG1-021 E
50/50
9.1979.197
3138533PONTONDP
50/50
3.9993.999
3144293JTRSVLE
50/50
2.4842.484
316131AB2-060 C
50/50
8.8878.887
924162AB2-060 E OP
50/50
25.59125.591
946301AF1-294 C
50/50
22.19222.192
946302AF1-294 E
50/50
18.79318.793
958211AF2-115 C
50/50
13.49513.495
958212AF2-115 E
50/50
11.49611.496
936261AD2-033 C
50/50
77.97277.972
936262AD2-033 E
50/50
51.98151.981
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0360.036
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0270.027
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0380.038
NYPJM->LTFIMP_NY
CLTF
0.020.02
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0760.076
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0210.021
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0130.013
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0940.094
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.020.02
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0630.063
O66PJM->LTFIMP_O-066
CMTX_NF
0.2440.244
MDUPJM->LTFIMP_MDU
CLTF
0.0040.004

Details for 3LONEPN-3FLAT CREEK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1045_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
3LONEPN-3FLAT CREEK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1045_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:120.01 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:244.79
MW Contribution:19.99
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
3LONEPN-3FLAT CREEK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1045_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:119.98 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:244.73
MW Contribution:19.99
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
10.79610.796
961792AG1-021 E
50/50
9.1979.197
3138533PONTONDP
50/50
3.9993.999
3144293JTRSVLE
50/50
2.4842.484
316131AB2-060 C
50/50
8.8878.887
924162AB2-060 E OP
50/50
25.59125.591
946301AF1-294 C
50/50
22.19222.192
946302AF1-294 E
50/50
18.79318.793
958211AF2-115 C
50/50
13.49513.495
958212AF2-115 E
50/50
11.49611.496
936261AD2-033 C
50/50
77.97277.972
936262AD2-033 E
50/50
51.98151.981
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0360.036
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0270.027
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0380.038
NYPJM->LTFIMP_NY
CLTF
0.020.02
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0760.076
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0210.021
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0130.013
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0940.094
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.020.02
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0630.063
O66PJM->LTFIMP_O-066
CMTX_NF
0.2440.244
MDUPJM->LTFIMP_MDU
CLTF
0.0040.004

Details for 3MORAN-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1045_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
3MORAN-3FARMVIL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1045_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.13 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:238.93
MW Contribution:19.99
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
3MORAN-3FARMVIL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1045_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.1 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:238.85
MW Contribution:19.99
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
10.79610.796
961792AG1-021 E
50/50
9.1979.197
3138533PONTONDP
50/50
3.9993.999
3144293JTRSVLE
50/50
2.4842.484
316131AB2-060 C
50/50
8.8878.887
924162AB2-060 E OP
50/50
25.59125.591
946301AF1-294 C
50/50
22.19222.192
946302AF1-294 E
50/50
18.79318.793
958211AF2-115 C
50/50
13.49513.495
958212AF2-115 E
50/50
11.49611.496
936261AD2-033 C
50/50
77.97277.972
936262AD2-033 E
50/50
51.98151.981
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.0360.036
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.0270.027
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0380.038
NYPJM->LTFIMP_NY
CLTF
0.020.02
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.0760.076
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0210.021
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0130.013
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.0940.094
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.020.02
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0630.063
O66PJM->LTFIMP_O-066
CMTX_NF
0.2440.244
MDUPJM->LTFIMP_MDU
CLTF
0.0040.004

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.21 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:741.18
MW Contribution:4.59
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.95 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:773.37
MW Contribution:4.73
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
2.4812.481
961792AG1-021 E
50/50
2.1132.113
964791AG1-342 C
Adder
2.1235294117647061.805
964792AG1-342 E
Adder
1.41647058823529411.204
3138533PONTONDP
50/50
0.9190.919
3144293JTRSVLE
50/50
0.5710.571
3147133PAMPLIN
50/50
1.4571.457
925785AC1-054 E
Adder
1.48235294117647071.26
926274AC1-105 E
Adder
1.48352941176470581.261
943902AF1-058 E
Adder
0.65294117647058840.555
959311AF2-222 C
50/50
18.01818.018
959312AF2-222 E
50/50
12.07212.072
316131AB2-060 C
50/50
1.121.12
924162AB2-060 E OP
50/50
3.2253.225
924302AB2-077 E O1
50/50
0.9550.955
924312AB2-078 E O1
50/50
0.9550.955
924322AB2-079 E O1
50/50
0.9550.955
925612AC1-036 E
50/50
0.8890.889
941011AE2-092 C
Adder
8.222352941176476.989
941012AE2-092 E
Adder
5.48117647058823554.659
946301AF1-294 C
50/50
5.15.1
946302AF1-294 E
50/50
4.3194.319
957481AF2-042 C
Adder
27.58352941176470823.446
957482AF2-042 E
Adder
18.38941176470588315.631
958131AF2-107 C
Adder
2.38941176470588262.031
958132AF2-107 E
Adder
1.30941176470588231.113
958211AF2-115 C
50/50
3.1013.101
958212AF2-115 E
50/50
2.6422.642
924032AB2-045 E
50/50
3.7663.766
933502AC2-165 E
50/50
24.49824.498
3151911BEARGRDN G1
50/50
17.79517.795
3151921BEARGRDN G2
50/50
17.79517.795
3147223TWITTYS
50/50
0.9860.986
936261AD2-033 C
50/50
13.17213.172
936262AD2-033 E
50/50
8.7818.781
934621AD1-088 C
50/50
6.6736.673
934622AD1-088 E
50/50
3.2133.213
3151931BEARGRDN S1
50/50
23.02123.021
316034AC1-036 C
50/50
0.2430.243
316237AB2-079 C O1
50/50
0.2340.234
316238AB2-078 C O1
50/50
0.2340.234
316239AB2-077 C O1
50/50
0.2340.234
316322AB2-045 C
50/50
0.840.84
316336AC2-165 C
50/50
32.5532.55
927264AC1-222 E
Adder
1.98117647058823531.684
313527AB2-043 C
50/50
0.3760.376
924022AB2-043 E O1
50/50
3.7783.778
962561AG1-105 C
50/50
5.5115.511
962562AG1-105 E
50/50
3.6743.674
964241AG1-285 C
50/50
9.9699.969
964242AG1-285 E
50/50
6.6466.646
934612AD1-087 E
Adder
1.95058823529411751.658
935172AD1-152 E
Adder
2.81529411764705852.393
937482AD2-202 E
Adder
0.57058823529411760.485
938821AE1-108 C
50/50
16.62316.623
938822AE1-108 E
50/50
7.9317.931
942461AE2-259 C
50/50
17.67317.673
942462AE2-259 E
50/50
11.78211.782
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3441.344
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.0390.039
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.6382.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.54721.547
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6760.676
NYPJM->LTFIMP_NY
CLTF
0.3510.351
LGEELTFEXP_LGEE->PJM
CLTF
0.0240.024
WECLTFEXP_WEC->PJM
CLTF
0.0090.009
CPLELTFEXP_CPLE->PJM
CLTF
2.8232.823
TVALTFEXP_TVA->PJM
CLTF
0.8870.887
MECLTFEXP_MEC->PJM
CLTF
0.2490.249
LAGNLTFEXP_LAGN->PJM
CLTF
1.161.16
SIGELTFEXP_SIGE->PJM
CLTF
0.0110.011
O66PJM->LTFIMP_O-066
CMTX_NF
4.3344.334

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.15 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:734.03
MW Contribution:4.59
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.89 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:766.15
MW Contribution:4.73
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
2.4812.481
961792AG1-021 E
50/50
2.1132.113
964791AG1-342 C
Adder
2.1235294117647061.805
964792AG1-342 E
Adder
1.41647058823529411.204
3138533PONTONDP
50/50
0.9190.919
3144293JTRSVLE
50/50
0.5710.571
3147133PAMPLIN
50/50
1.4571.457
925785AC1-054 E
Adder
1.48235294117647071.26
926274AC1-105 E
Adder
1.48352941176470581.261
943902AF1-058 E
Adder
0.65294117647058840.555
959311AF2-222 C
50/50
18.01818.018
959312AF2-222 E
50/50
12.07212.072
316131AB2-060 C
50/50
1.121.12
924162AB2-060 E OP
50/50
3.2253.225
924302AB2-077 E O1
50/50
0.9550.955
924312AB2-078 E O1
50/50
0.9550.955
924322AB2-079 E O1
50/50
0.9550.955
925612AC1-036 E
50/50
0.8890.889
941011AE2-092 C
Adder
8.222352941176476.989
941012AE2-092 E
Adder
5.48117647058823554.659
946301AF1-294 C
50/50
5.15.1
946302AF1-294 E
50/50
4.3194.319
957481AF2-042 C
Adder
27.58352941176470823.446
957482AF2-042 E
Adder
18.38941176470588315.631
958131AF2-107 C
Adder
2.38941176470588262.031
958132AF2-107 E
Adder
1.30941176470588231.113
958211AF2-115 C
50/50
3.1013.101
958212AF2-115 E
50/50
2.6422.642
924032AB2-045 E
50/50
3.7663.766
933502AC2-165 E
50/50
24.49824.498
3151911BEARGRDN G1
50/50
17.79517.795
3151921BEARGRDN G2
50/50
17.79517.795
3147223TWITTYS
50/50
0.9860.986
936261AD2-033 C
50/50
13.17213.172
936262AD2-033 E
50/50
8.7818.781
934621AD1-088 C
50/50
6.6736.673
934622AD1-088 E
50/50
3.2133.213
3151931BEARGRDN S1
50/50
23.02123.021
316034AC1-036 C
50/50
0.2430.243
316237AB2-079 C O1
50/50
0.2340.234
316238AB2-078 C O1
50/50
0.2340.234
316239AB2-077 C O1
50/50
0.2340.234
316322AB2-045 C
50/50
0.840.84
316336AC2-165 C
50/50
32.5532.55
927264AC1-222 E
Adder
1.98117647058823531.684
313527AB2-043 C
50/50
0.3760.376
924022AB2-043 E O1
50/50
3.7783.778
962561AG1-105 C
50/50
5.5115.511
962562AG1-105 E
50/50
3.6743.674
964241AG1-285 C
50/50
9.9699.969
964242AG1-285 E
50/50
6.6466.646
934612AD1-087 E
Adder
1.95058823529411751.658
935172AD1-152 E
Adder
2.81529411764705852.393
937482AD2-202 E
Adder
0.57058823529411760.485
938821AE1-108 C
50/50
16.62316.623
938822AE1-108 E
50/50
7.9317.931
942461AE2-259 C
50/50
17.67317.673
942462AE2-259 E
50/50
11.78211.782
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3441.344
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.0390.039
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.6382.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.54721.547
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6760.676
NYPJM->LTFIMP_NY
CLTF
0.3510.351
LGEELTFEXP_LGEE->PJM
CLTF
0.0240.024
WECLTFEXP_WEC->PJM
CLTF
0.0090.009
CPLELTFEXP_CPLE->PJM
CLTF
2.8232.823
TVALTFEXP_TVA->PJM
CLTF
0.8870.887
MECLTFEXP_MEC->PJM
CLTF
0.2490.249
LAGNLTFEXP_LAGN->PJM
CLTF
1.161.16
SIGELTFEXP_SIGE->PJM
CLTF
0.0110.011
O66PJM->LTFIMP_O-066
CMTX_NF
4.3344.334

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.97 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:701.29
MW Contribution:4.28
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.14 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:748.75
MW Contribution:4.41
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
2.3122.312
961792AG1-021 E
50/50
1.971.97
964791AG1-342 C
Adder
2.00705882352941161.706
964792AG1-342 E
Adder
1.33764705882352941.137
3138533PONTONDP
50/50
0.8560.856
3144293JTRSVLE
50/50
0.5320.532
3147133PAMPLIN
50/50
1.3571.357
925785AC1-054 E
Adder
1.3870588235294121.179
926274AC1-105 E
Adder
1.40941176470588241.198
943902AF1-058 E
Adder
0.62352941176470590.53
959311AF2-222 C
50/50
16.79916.799
959312AF2-222 E
50/50
11.25511.255
316131AB2-060 C
50/50
1.0471.047
924162AB2-060 E OP
50/50
3.0163.016
924302AB2-077 E O1
50/50
0.8940.894
924312AB2-078 E O1
50/50
0.8940.894
924322AB2-079 E O1
50/50
0.8940.894
925612AC1-036 E
50/50
0.8290.829
941011AE2-092 C
50/50
23.99423.994
941012AE2-092 E
50/50
15.99615.996
946301AF1-294 C
50/50
4.7534.753
946302AF1-294 E
50/50
4.0254.025
957481AF2-042 C
Adder
25.7317647058823521.872
957482AF2-042 E
Adder
17.15411764705882214.581
958131AF2-107 C
50/50
4.7314.731
958132AF2-107 E
50/50
2.5922.592
958211AF2-115 C
50/50
2.892.89
958212AF2-115 E
50/50
2.4622.462
924032AB2-045 E
50/50
3.5043.504
933502AC2-165 E
50/50
22.78922.789
3151911BEARGRDN G1
50/50
16.55416.554
3151921BEARGRDN G2
50/50
16.55416.554
3147223TWITTYS
50/50
0.9190.919
936261AD2-033 C
50/50
12.29412.294
936262AD2-033 E
50/50
8.1968.196
934621AD1-088 C
50/50
6.2236.223
934622AD1-088 E
50/50
2.9962.996
3151931BEARGRDN S1
50/50
21.41521.415
316034AC1-036 C
50/50
0.2260.226
316237AB2-079 C O1
50/50
0.2190.219
316238AB2-078 C O1
50/50
0.2190.219
316239AB2-077 C O1
50/50
0.2190.219
316322AB2-045 C
50/50
0.7820.782
316336AC2-165 C
50/50
30.2830.28
927264AC1-222 E
Adder
1.91647058823529411.629
313527AB2-043 C
50/50
0.3520.352
924022AB2-043 E O1
50/50
3.5343.534
962561AG1-105 C
Adder
5.197647058823534.418
962562AG1-105 E
Adder
3.4647058823529412.945
964241AG1-285 C
50/50
9.3069.306
964242AG1-285 E
50/50
6.2046.204
934612AD1-087 E
Adder
1.8235294117647061.55
935172AD1-152 E
Adder
2.64470588235294152.248
937482AD2-202 E
Adder
0.53411764705882360.454
938821AE1-108 C
50/50
33.08633.086
938822AE1-108 E
50/50
15.78715.787
942461AE2-259 C
50/50
16.45516.455
942462AE2-259 E
50/50
10.9710.97
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.2941.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4071.407
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.0933.093
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.18821.188
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6880.688
NYPJM->LTFIMP_NY
CLTF
0.3520.352
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
WECLTFEXP_WEC->PJM
CLTF
0.0360.036
CPLELTFEXP_CPLE->PJM
CLTF
2.7182.718
TVALTFEXP_TVA->PJM
CLTF
0.9770.977
MECLTFEXP_MEC->PJM
CLTF
0.3740.374
LAGNLTFEXP_LAGN->PJM
CLTF
1.2621.262
SIGELTFEXP_SIGE->PJM
CLTF
0.020.02
O66PJM->LTFIMP_O-066
CMTX_NF
4.4054.405

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.64 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:718.91
MW Contribution:4.28
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.82 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:766.43
MW Contribution:4.41
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
2.3122.312
961792AG1-021 E
50/50
1.971.97
964791AG1-342 C
Adder
2.00705882352941161.706
964792AG1-342 E
Adder
1.33764705882352941.137
3138533PONTONDP
50/50
0.8560.856
3144293JTRSVLE
50/50
0.5320.532
3147133PAMPLIN
50/50
1.3571.357
925785AC1-054 E
Adder
1.3870588235294121.179
926274AC1-105 E
Adder
1.40941176470588241.198
943902AF1-058 E
Adder
0.62352941176470590.53
959311AF2-222 C
50/50
16.79916.799
959312AF2-222 E
50/50
11.25511.255
316131AB2-060 C
50/50
1.0471.047
924162AB2-060 E OP
50/50
3.0163.016
924302AB2-077 E O1
50/50
0.8940.894
924312AB2-078 E O1
50/50
0.8940.894
924322AB2-079 E O1
50/50
0.8940.894
925612AC1-036 E
50/50
0.8290.829
941011AE2-092 C
50/50
23.99423.994
941012AE2-092 E
50/50
15.99615.996
946301AF1-294 C
50/50
4.7534.753
946302AF1-294 E
50/50
4.0254.025
957481AF2-042 C
Adder
25.7317647058823521.872
957482AF2-042 E
Adder
17.15411764705882214.581
958131AF2-107 C
50/50
4.7314.731
958132AF2-107 E
50/50
2.5922.592
958211AF2-115 C
50/50
2.892.89
958212AF2-115 E
50/50
2.4622.462
924032AB2-045 E
50/50
3.5043.504
933502AC2-165 E
50/50
22.78922.789
3151911BEARGRDN G1
50/50
16.55416.554
3151921BEARGRDN G2
50/50
16.55416.554
3147223TWITTYS
50/50
0.9190.919
936261AD2-033 C
50/50
12.29412.294
936262AD2-033 E
50/50
8.1968.196
934621AD1-088 C
50/50
6.2236.223
934622AD1-088 E
50/50
2.9962.996
3151931BEARGRDN S1
50/50
21.41521.415
316034AC1-036 C
50/50
0.2260.226
316237AB2-079 C O1
50/50
0.2190.219
316238AB2-078 C O1
50/50
0.2190.219
316239AB2-077 C O1
50/50
0.2190.219
316322AB2-045 C
50/50
0.7820.782
316336AC2-165 C
50/50
30.2830.28
927264AC1-222 E
Adder
1.91647058823529411.629
313527AB2-043 C
50/50
0.3520.352
924022AB2-043 E O1
50/50
3.5343.534
962561AG1-105 C
Adder
5.197647058823534.418
962562AG1-105 E
Adder
3.4647058823529412.945
964241AG1-285 C
50/50
9.3069.306
964242AG1-285 E
50/50
6.2046.204
934612AD1-087 E
Adder
1.8235294117647061.55
935172AD1-152 E
Adder
2.64470588235294152.248
937482AD2-202 E
Adder
0.53411764705882360.454
938821AE1-108 C
50/50
33.08633.086
938822AE1-108 E
50/50
15.78715.787
942461AE2-259 C
50/50
16.45516.455
942462AE2-259 E
50/50
10.9710.97
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.2941.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4071.407
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.0933.093
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.18821.188
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6880.688
NYPJM->LTFIMP_NY
CLTF
0.3520.352
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
WECLTFEXP_WEC->PJM
CLTF
0.0360.036
CPLELTFEXP_CPLE->PJM
CLTF
2.7182.718
TVALTFEXP_TVA->PJM
CLTF
0.9770.977
MECLTFEXP_MEC->PJM
CLTF
0.3740.374
LAGNLTFEXP_LAGN->PJM
CLTF
1.2621.262
SIGELTFEXP_SIGE->PJM
CLTF
0.020.02
O66PJM->LTFIMP_O-066
CMTX_NF
4.4054.405

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.38 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:677.52
MW Contribution:4.28
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-2
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.53 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:724.84
MW Contribution:4.41
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
2.3122.312
961792AG1-021 E
50/50
1.971.97
964791AG1-342 C
Adder
2.00705882352941161.706
964792AG1-342 E
Adder
1.33764705882352941.137
3138533PONTONDP
50/50
0.8560.856
3144293JTRSVLE
50/50
0.5320.532
3147133PAMPLIN
50/50
1.3571.357
925785AC1-054 E
Adder
1.3870588235294121.179
926274AC1-105 E
Adder
1.40941176470588241.198
943902AF1-058 E
Adder
0.62352941176470590.53
959311AF2-222 C
50/50
16.79916.799
959312AF2-222 E
50/50
11.25511.255
316131AB2-060 C
50/50
1.0471.047
924162AB2-060 E OP
50/50
3.0163.016
924302AB2-077 E O1
50/50
0.8940.894
924312AB2-078 E O1
50/50
0.8940.894
924322AB2-079 E O1
50/50
0.8940.894
925612AC1-036 E
50/50
0.8290.829
941011AE2-092 C
50/50
23.99423.994
941012AE2-092 E
50/50
15.99615.996
946301AF1-294 C
50/50
4.7534.753
946302AF1-294 E
50/50
4.0254.025
957481AF2-042 C
Adder
25.7317647058823521.872
957482AF2-042 E
Adder
17.15411764705882214.581
958131AF2-107 C
50/50
4.7314.731
958132AF2-107 E
50/50
2.5922.592
958211AF2-115 C
50/50
2.892.89
958212AF2-115 E
50/50
2.4622.462
924032AB2-045 E
50/50
3.5043.504
933502AC2-165 E
50/50
22.78922.789
3151911BEARGRDN G1
50/50
16.55416.554
3151921BEARGRDN G2
50/50
16.55416.554
3147223TWITTYS
50/50
0.9190.919
936261AD2-033 C
50/50
12.29412.294
936262AD2-033 E
50/50
8.1968.196
934621AD1-088 C
50/50
6.2236.223
934622AD1-088 E
50/50
2.9962.996
3151931BEARGRDN S1
50/50
21.41521.415
316034AC1-036 C
50/50
0.2260.226
316237AB2-079 C O1
50/50
0.2190.219
316238AB2-078 C O1
50/50
0.2190.219
316239AB2-077 C O1
50/50
0.2190.219
316322AB2-045 C
50/50
0.7820.782
316336AC2-165 C
50/50
30.2830.28
927264AC1-222 E
Adder
1.91647058823529411.629
313527AB2-043 C
50/50
0.3520.352
924022AB2-043 E O1
50/50
3.5343.534
962561AG1-105 C
Adder
5.197647058823534.418
962562AG1-105 E
Adder
3.4647058823529412.945
964241AG1-285 C
50/50
9.3069.306
964242AG1-285 E
50/50
6.2046.204
934612AD1-087 E
Adder
1.8235294117647061.55
935172AD1-152 E
Adder
2.64470588235294152.248
937482AD2-202 E
Adder
0.53411764705882360.454
938821AE1-108 C
50/50
33.08633.086
938822AE1-108 E
50/50
15.78715.787
942461AE2-259 C
50/50
16.45516.455
942462AE2-259 E
50/50
10.9710.97
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.2941.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4071.407
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.0933.093
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.18821.188
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6880.688
NYPJM->LTFIMP_NY
CLTF
0.3520.352
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
WECLTFEXP_WEC->PJM
CLTF
0.0360.036
CPLELTFEXP_CPLE->PJM
CLTF
2.7182.718
TVALTFEXP_TVA->PJM
CLTF
0.9770.977
MECLTFEXP_MEC->PJM
CLTF
0.3740.374
LAGNLTFEXP_LAGN->PJM
CLTF
1.2621.262
SIGELTFEXP_SIGE->PJM
CLTF
0.020.02
O66PJM->LTFIMP_O-066
CMTX_NF
4.4054.405

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 578_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 578_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.77 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3599.45
MW Contribution:3.26
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 578_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:116.45 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3750.16
MW Contribution:3.0
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
1.12470588235294120.956
961672AG1-007 E
Adder
0.63764705882352950.542
961791AG1-021 C
Adder
1.761.496
961792AG1-021 E
Adder
1.49882352941176471.274
961941AG1-037 C
Adder
0.60235294117647060.512
961942AG1-037 E
Adder
0.401176470588235360.341
963041AG1-153 C
50/50
8.9478.947
963042AG1-153 E
50/50
13.4213.42
964791AG1-342 C
Adder
4.263.621
964792AG1-342 E
Adder
2.84000000000000032.414
966621AG1-532 C
Adder
1.73176470588235291.472
966622AG1-532 E
Adder
1.15411764705882350.981
3138533PONTONDP
Adder
0.6517647058823530.554
3145413WATKINS
Adder
0.80705882352941180.686
3145723EMPORIA
Adder
0.53176470588235290.452
3147133PAMPLIN
Adder
0.97058823529411760.825
3151311EDGECMA
Adder
18.62235294117647315.829
3151531CLOVER1
50/50
17.10517.105
3151541CLOVER2
50/50
16.94716.947
918492AA1-063AE OP
Adder
4.9164705882352954.179
918532AA1-067 E
Adder
0.85411764705882350.726
919692AA2-053 E OP
Adder
5.1235294117647064.355
920042AA2-088 E OP
Adder
12.54941176470588210.667
925785AC1-054 E
Adder
4.20352941176470553.573
926274AC1-105 E
Adder
3.2105882352941182.729
927146AC1-208 E
Adder
4.8317647058823534.107
934521AD1-076 C
Adder
14.59176470588235512.403
934522AD1-076 E
Adder
7.4376470588235296.322
943172AE2-346 E
Adder
0.72235294117647060.614
943902AF1-058 E
Adder
1.53647058823529431.306
944011AF1-069 C
50/50
21.38521.385
944012AF1-069 E
50/50
8.3078.307
959311AF2-222 C
Adder
19.16941176470588516.294
959312AF2-222 E
Adder
12.84352941176470610.917
960081AF2-299 C
Adder
2.30941176470588251.963
960082AF2-299 E
Adder
1.53882352941176471.308
316141AB2-099 E
Adder
0.30117647058823530.256
900672V4-068 E
Adder
0.42352941176470590.36
917342Z2-044 E
Adder
0.71882352941176480.611
922923AB1-081 E OP
Adder
4.4729411764705883.802
923263AB1-132 E OP
Adder
7.4552941176470596.337
923573AB1-173 E OP
Adder
4.0258823529411773.422
924162AB2-060 E OP
Adder
5.1964705882352944.417
924302AB2-077 E O1
Adder
1.63411764705882371.389
924312AB2-078 E O1
Adder
1.63411764705882371.389
924322AB2-079 E O1
Adder
1.63411764705882371.389
925612AC1-036 E
Adder
1.00470588235294110.854
940492AE2-034 E
Adder
3.67529411764705933.124
941031AE2-094 C
50/50
65.44965.449
941032AE2-094 E
50/50
29.31329.313
946281AF1-292 C
Adder
1.9117647058823531.625
946282AF1-292 E
Adder
1.27411764705882361.083
946301AF1-294 C
Adder
3.617647058823533.075
946302AF1-294 E
Adder
3.06352941176470632.604
957481AF2-042 C
50/50
75.2375.23
957482AF2-042 E
50/50
50.15450.154
957861AF2-080 C
Adder
9.1435294117647077.772
957862AF2-080 E
Adder
4.0529411764705883.445
958211AF2-115 C
Adder
2.21.87
958212AF2-115 E
Adder
1.87411764705882341.593
3145393UNCAMP
Adder
7.0541176470588245.996
916042Z1-036 E
Adder
34.05176470588235628.944
938771AE1-103 C
Adder
3.38352941176470572.876
938772AE1-103 E
Adder
4.6717647058823533.971
3143316POE
Adder
1.37411764705882341.168
3145256KINGFORK
Adder
1.08117647058823540.919
3145506HICKORY
50/50
2.6852.685
926662AC1-147 E
Adder
1.58705882352941191.349
926755AC1-161 E
50/50
19.76119.761
935112AD1-144 E
Adder
1.00470588235294110.854
942341AE2-247 C
Adder
1.60352941176470591.363
942342AE2-247 E
Adder
2.21411764705882331.882
943461AF1-017 C
Adder
1.45058823529411771.233
943462AF1-017 E
Adder
2.3670588235294122.012
943612AF1-032 E
Adder
1.06117647058823540.902
3151021BRUNSWICKG1
50/50
13.20613.206
3151031BRUNSWICKG2
50/50
13.20613.206
3151041BRUNSWICKG3
50/50
13.20613.206
3151051BRUNSWICKS1
50/50
27.43527.435
3151081ELIZAR1
50/50
3.8583.858
3151091ELIZAR2
50/50
3.7913.791
3151101ELIZAR3
50/50
3.9073.907
3152411Z1-086 GT1
50/50
17.00617.006
3152421Z1-086 GT2
50/50
1717
3152431Z1-086 GT3
50/50
1717
3152441Z1-086 ST
50/50
29.60429.604
913392Y1-086 E
Adder
2.65411764705882322.256
916192Z1-068 E
50/50
2.2832.283
923832AB2-022 E
Adder
1.49882352941176471.274
923852AB2-025 E
50/50
1.4781.478
939312AE1-162 E
Adder
1.42235294117647081.209
957492AF2-043 E
Adder
1.63294117647058811.388
901082W1-029 E
Adder
37.7832.113
917122Z2-027 E
Adder
1.61411764705882371.372
925522AC1-027 E
50/50
1.4771.477
942001AE2-212 C
Adder
1.59764705882352961.358
957871AF2-081 C
50/50
12.23112.231
957872AF2-081 E
50/50
5.2425.242
958161AF2-110 C
Adder
1.54823529411764721.316
958162AF2-110 E
Adder
2.46235294117647062.093
3147223TWITTYS
Adder
1.11411764705882340.947
917512Z2-088 E OP1
Adder
5.8647058823529424.985
926071AC1-086 C
Adder
25.61647058823529521.774
926072AC1-086 E
Adder
11.6588235294117669.91
927021AC1-189 C
Adder
10.0670588235294138.557
927022AC1-189 E
Adder
5.0152941176470594.263
936261AD2-033 C
Adder
14.54117647058823512.36
936262AD2-033 E
Adder
9.6941176470588258.24
933291AC2-141 C
50/50
46.29246.292
933292AC2-141 E
50/50
19.76119.761
934621AD1-088 C
50/50
12.41612.416
934622AD1-088 E
50/50
5.9785.978
939411AE1-173 C
50/50
136.223136.223
939412AE1-173 E
50/50
90.81590.815
916191Z1-068 C
50/50
0.0530.053
933981AD1-022 C
Adder
10.4411764705882368.875
933982AD1-022 E
Adder
5.6847058823529414.832
962572AG1-106 E
Adder
1.44941176470588241.232
962571AG1-106 C
Adder
3.31294117647058832.816
3145946PLYMOUTH TP
Adder
0.38470588235294120.327
3146326AYDLETT TAP
50/50
1.6541.654
316023AB2-100 C2
50/50
1.1931.193
316185AD1-033 C
50/50
1.5141.514
316263AC1-034 C
Adder
7.9670588235294126.772
316274AC1-208 C
Adder
10.8799999999999999.248
316294AC1-161 C
50/50
7.5657.565
316315AB2-025 C
50/50
0.5190.519
316316AC1-027 C
50/50
0.3830.383
316365AB2-100 C1
50/50
1.1931.193
917332KELFORD E
Adder
1.96941176470588241.674
924516AB2-100 E1
50/50
3.5953.595
924517AB2-100 E2
50/50
3.5953.595
925595AC1-034 E
Adder
6.0094117647058825.108
926206AC1-098 E
Adder
4.3952941176470593.736
926214AC1-099 E
Adder
1.4517647058823531.234
927255AC1-221 E
Adder
4.4470588235294123.78
927264AC1-222 E
Adder
4.65176470588235353.954
932763AC2-100 E
Adder
3.01647058823529422.564
934065AD1-033 E
50/50
6.1776.177
937226AE2-253 E
50/50
7.1687.168
918512AA1-065 E OP
Adder
6.582352941176475.595
316017AA1-139 ULT1
50/50
1.3241.324
316018AA1-139 ULT2
50/50
1.3241.324
919153AA1-139 E2
50/50
5.0025.002
919152AA1-139 E1
50/50
5.0025.002
919710AA2-057 E
Adder
4.7729411764705894.057
920692AA2-178 E
Adder
4.94.165
923994AB2-040_E
Adder
7.5482352941176486.416
924022AB2-043 E O1
Adder
6.3423529411764715.391
924152AB2-059 E OP
Adder
6.33647058823529455.386
316084AB2-161 E
Adder
5.457647058823534.639
925122AB2-169 E
Adder
6.8611764705882355.832
316088AB2-174 E
Adder
8.015294117647066.813
316375AC2-012 C
50/50
1.6191.619
932046AC2-012 E
50/50
15.70315.703
316311AC2-079 C
Adder
6.2058823529411775.275
932596AC2-079 E
Adder
10.1247058823529418.606
934576AD1-082 E
Adder
4.3482352941176473.696
316349AD2-085 C
Adder
3.73.145
936666AD2-085 E
Adder
6.0364705882352955.131
316388AE2-253 GEN
50/50
2.4112.411
961611AG1-000B C
Adder
13.20352941176470711.223
941591AE2-156 C
50/50
21.49421.494
944581AF1-123 C
50/50
56.00556.005
944582AF1-123 E
50/50
128.245128.245
944591AF1-124 C
50/50
56.20456.204
944592AF1-124 E
50/50
128.709128.709
944601AF1-125 C
50/50
55.14255.142
944602AF1-125 E
50/50
126.232126.232
962561AG1-105 C
Adder
10.7117647058823549.105
962562AG1-105 E
Adder
7.1411764705882366.07
964241AG1-285 C
Adder
16.00235294117647213.602
964242AG1-285 E
Adder
10.6682352941176479.068
3137643SOCKMAN
Adder
0.86941176470588230.739
932632AC2-084 E
Adder
3.88470588235294123.302
934321AD1-056 C
Adder
7.5647058823529416.43
934322AD1-056 E
Adder
4.1035294117647063.488
934331AD1-057 C
Adder
4.2200000000000013.587
934332AD1-057 E
Adder
2.19764705882352951.868
934501AD1-074 C
Adder
40.1776470588235334.151
934502AD1-074 E
Adder
20.45294117647059217.385
934511AD1-075 C
Adder
10.0447058823529418.538
934512AD1-075 E
Adder
5.11294117647058854.346
934611AD1-087 C
50/50
1.6841.684
934612AD1-087 E
50/50
4.8584.858
935171AD1-152 C
50/50
1.7291.729
935172AD1-152 E
50/50
7.1147.114
937481AD2-202 C
50/50
0.4890.489
937482AD2-202 E
50/50
1.4221.422
938531AE1-072 C
50/50
21.45421.454
938532AE1-072 E
50/50
11.18411.184
939191AE1-149 C
Adder
9.9423529411764728.451
939192AE1-149 E
Adder
6.6282352941176485.634
940481AE2-033 C
50/50
20.53320.533
940482AE2-033 E
50/50
13.84313.843
940541AE2-040 C
50/50
3.6533.653
940641AE2-051 C
50/50
28.95128.951
940642AE2-051 E
50/50
19.30119.301
941101AE2-104 C
Adder
3.7941176470588243.225
941102AE2-104 E
Adder
6.03176470588235255.127
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.7456.745
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.88431.884
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.51924.519
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
115.14115.14
G-007PJM->LTFIMP_G-007
CMTX_NF
3.7193.719
NYPJM->LTFIMP_NY
CLTF
1.7391.739
LGEELTFEXP_LGEE->PJM
CLTF
1.2571.257
WECLTFEXP_WEC->PJM
CLTF
0.6630.663
CPLELTFEXP_CPLE->PJM
CLTF
14.15314.153
TVALTFEXP_TVA->PJM
CLTF
6.746.74
MECLTFEXP_MEC->PJM
CLTF
4.1564.156
LAGNLTFEXP_LAGN->PJM
CLTF
8.6318.631
SIGELTFEXP_SIGE->PJM
CLTF
0.2520.252
O66PJM->LTFIMP_O-066
CMTX_NF
23.68623.686

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.12 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3352.99
MW Contribution:3.02
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3492.91
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
1.05882352941176470.9
961672AG1-007 E
Adder
0.60.51
961791AG1-021 C
Adder
1.63058823529411771.386
961792AG1-021 E
Adder
1.38941176470588231.181
961941AG1-037 C
Adder
0.5717647058823530.486
961942AG1-037 E
Adder
0.381176470588235340.324
963041AG1-153 C
50/50
8.3218.321
963042AG1-153 E
50/50
12.48112.481
964791AG1-342 C
Adder
3.96470588235294133.37
964792AG1-342 E
Adder
2.6435294117647062.247
966621AG1-532 C
50/50
1.6281.628
966622AG1-532 E
50/50
1.0851.085
3138533PONTONDP
Adder
0.60352941176470590.513
3145413WATKINS
Adder
0.7717647058823530.656
3145723EMPORIA
50/50
0.50.5
3147133PAMPLIN
Adder
0.89882352941176480.764
3151311EDGECMA
Adder
17.50705882352941214.881
3151531CLOVER1
50/50
15.90515.905
3151541CLOVER2
50/50
15.75715.757
918492AA1-063AE OP
Adder
4.65058823529411753.953
918532AA1-067 E
Adder
0.80588235294117660.685
919692AA2-053 E OP
Adder
4.8352941176470594.11
920042AA2-088 E OP
Adder
11.94941176470588210.157
925785AC1-054 E
Adder
3.94000000000000043.349
926274AC1-105 E
Adder
2.9882352941176472.54
927146AC1-208 E
Adder
4.5541176470588243.871
934521AD1-076 C
Adder
13.81176470588235411.74
934522AD1-076 E
Adder
7.045.984
943172AE2-346 E
Adder
0.68588235294117650.583
943902AF1-058 E
Adder
1.42941176470588241.215
944011AF1-069 C
50/50
19.88619.886
944012AF1-069 E
50/50
7.7257.725
959311AF2-222 C
Adder
17.79058823529411615.122
959312AF2-222 E
Adder
11.9210.132
960081AF2-299 C
50/50
2.1712.171
960082AF2-299 E
50/50
1.4471.447
316141AB2-099 E
Adder
0.28588235294117650.243
900672V4-068 E
Adder
0.402352941176470640.342
917342Z2-044 E
Adder
0.6764705882352940.575
922923AB1-081 E OP
Adder
4.20470588235294153.574
923263AB1-132 E OP
Adder
7.0270588235294125.973
923573AB1-173 E OP
Adder
3.78941176470588253.221
924162AB2-060 E OP
Adder
4.8364705882352944.111
924302AB2-077 E O1
Adder
1.52117647058823541.293
924312AB2-078 E O1
Adder
1.52117647058823541.293
924322AB2-079 E O1
Adder
1.52117647058823541.293
925612AC1-036 E
Adder
0.93294117647058830.793
940492AE2-034 E
Adder
3.4764705882352942.955
941031AE2-094 C
50/50
60.86460.864
941032AE2-094 E
50/50
27.25927.259
946281AF1-292 C
50/50
1.7971.797
946282AF1-292 E
50/50
1.1981.198
946301AF1-294 C
Adder
3.3517647058823532.849
946302AF1-294 E
Adder
2.83882352941176472.413
957481AF2-042 C
50/50
69.9469.94
957482AF2-042 E
50/50
46.62746.627
957861AF2-080 C
Adder
8.6200000000000017.327
957862AF2-080 E
Adder
3.8211764705882363.248
958211AF2-115 C
Adder
2.03764705882352941.732
958212AF2-115 E
Adder
1.73647058823529421.476
3145393UNCAMP
Adder
6.7635294117647065.749
916042Z1-036 E
Adder
32.1705882352941227.345
938771AE1-103 C
Adder
3.24823529411764732.761
938772AE1-103 E
Adder
4.4858823529411773.813
313526AB2-022 C
50/50
0.4240.424
3143316POE
Adder
1.30823529411764721.112
3145256KINGFORK
Adder
1.06588235294117650.906
3145506HICKORY
50/50
2.4672.467
926662AC1-147 E
Adder
1.46588235294117641.246
926755AC1-161 E
50/50
14.89414.894
935112AD1-144 E
Adder
0.98941176470588230.841
942341AE2-247 C
Adder
1.54941176470588231.317
942342AE2-247 E
Adder
2.141.819
943461AF1-017 C
Adder
1.40235294117647061.192
943462AF1-017 E
Adder
2.2870588235294121.944
943612AF1-032 E
Adder
1.02823529411764710.874
3151021BRUNSWICKG1
50/50
12.28212.282
3151031BRUNSWICKG2
50/50
12.28212.282
3151041BRUNSWICKG3
50/50
12.28212.282
3151051BRUNSWICKS1
50/50
25.51625.516
3151081ELIZAR1
50/50
3.5563.556
3151091ELIZAR2
50/50
3.4953.495
3151101ELIZAR3
50/50
3.6013.601
3152411Z1-086 GT1
50/50
15.81615.816
3152421Z1-086 GT2
50/50
15.81115.811
3152431Z1-086 GT3
50/50
15.81115.811
3152441Z1-086 ST
50/50
27.53327.533
913392Y1-086 E
50/50
2.4762.476
916192Z1-068 E
50/50
2.1052.105
923832AB2-022 E
50/50
1.3981.398
923852AB2-025 E
50/50
1.3891.389
939312AE1-162 E
Adder
1.37058823529411771.165
957492AF2-043 E
Adder
1.58117647058823541.344
901082W1-029 E
Adder
35.7705882352941230.405
917122Z2-027 E
50/50
1.5121.512
925522AC1-027 E
50/50
1.3621.362
957871AF2-081 C
50/50
11.29311.293
957872AF2-081 E
50/50
4.844.84
958161AF2-110 C
Adder
1.49647058823529421.272
958162AF2-110 E
Adder
2.38000000000000032.023
3147223TWITTYS
Adder
1.03411764705882360.879
917512Z2-088 E OP1
Adder
5.5247058823529414.696
926071AC1-086 C
Adder
24.1447058823529420.523
926072AC1-086 E
Adder
10.9894117647058819.341
927021AC1-189 C
Adder
9.4905882352941178.067
927022AC1-189 E
Adder
4.7282352941176474.019
936261AD2-033 C
Adder
13.51176470588235311.485
936262AD2-033 E
Adder
9.0082352941176477.657
933291AC2-141 C
50/50
34.8934.89
933292AC2-141 E
50/50
14.89414.894
934621AD1-088 C
50/50
11.53711.537
934622AD1-088 E
50/50
5.5555.555
939411AE1-173 C
50/50
128.665128.665
939412AE1-173 E
50/50
85.77785.777
916191Z1-068 C
50/50
0.0490.049
933981AD1-022 C
Adder
9.8917647058823528.408
933982AD1-022 E
Adder
5.3847058823529414.577
962572AG1-106 E
Adder
1.36588235294117651.161
962571AG1-106 C
Adder
3.1235294117647062.655
3145946PLYMOUTH TP
Adder
0.364705882352941160.31
3146326AYDLETT TAP
50/50
1.5311.531
316023AB2-100 C2
50/50
1.1231.123
316185AD1-033 C
50/50
1.391.39
316263AC1-034 C
Adder
7.4894117647058826.366
316274AC1-208 C
Adder
10.255294117647068.717
316294AC1-161 C
50/50
5.7015.701
316315AB2-025 C
50/50
0.4880.488
316316AC1-027 C
50/50
0.3530.353
316320Y1-086 C
50/50
0.2480.248
316321Z2-027 C
50/50
0.410.41
316365AB2-100 C1
50/50
1.1231.123
917332KELFORD E
Adder
1.8635294117647061.584
924516AB2-100 E1
50/50
3.3843.384
924517AB2-100 E2
50/50
3.3843.384
925595AC1-034 E
Adder
5.65058823529411754.803
926206AC1-098 E
Adder
4.1470588235294123.525
926214AC1-099 E
Adder
1.36941176470588231.164
927255AC1-221 E
Adder
4.1411764705882363.52
927264AC1-222 E
Adder
4.3282352941176473.679
932763AC2-100 E
Adder
2.80941176470588252.388
934065AD1-033 E
50/50
5.6715.671
937226AE2-253 E
50/50
6.6066.606
918512AA1-065 E OP
Adder
6.2505882352941175.313
316017AA1-139 ULT1
50/50
1.2231.223
316018AA1-139 ULT2
50/50
1.2231.223
919153AA1-139 E2
50/50
4.6184.618
919152AA1-139 E1
50/50
4.6184.618
919710AA2-057 E
Adder
4.49411764705882363.82
920692AA2-178 E
Adder
4.6352941176470593.94
923994AB2-040_E
Adder
7.1047058823529416.039
924022AB2-043 E O1
Adder
5.9035294117647065.018
924152AB2-059 E OP
Adder
5.9564705882352945.063
316084AB2-161 E
Adder
5.26941176470588254.479
925122AB2-169 E
Adder
6.4858823529411775.513
316087AB2-174 C
50/50
1.3621.362
316088AB2-174 E
50/50
7.5427.542
316375AC2-012 C
50/50
1.4951.495
932046AC2-012 E
50/50
14.50114.501
316311AC2-079 C
Adder
5.9964705882352955.097
932596AC2-079 E
Adder
9.7835294117647078.316
934576AD1-082 E
Adder
4.1988235294117653.569
316349AD2-085 C
Adder
3.5752941176470593.039
936666AD2-085 E
Adder
5.8329411764705884.958
316388AE2-253 GEN
50/50
2.2212.221
961611AG1-000B C
Adder
5.824.947
941591AE2-156 C
50/50
19.83519.835
944581AF1-123 C
50/50
51.37451.374
944582AF1-123 E
50/50
117.641117.641
944591AF1-124 C
50/50
51.55751.557
944592AF1-124 E
50/50
118.067118.067
944601AF1-125 C
50/50
50.58350.583
944602AF1-125 E
50/50
115.795115.795
962561AG1-105 C
Adder
9.9705882352941188.475
962562AG1-105 E
Adder
6.6470588235294125.65
964241AG1-285 C
50/50
14.87614.876
964242AG1-285 E
50/50
9.9189.918
3137643SOCKMAN
Adder
0.81882352941176460.696
932632AC2-084 E
Adder
3.66588235294117663.116
934321AD1-056 C
Adder
7.126.052
934322AD1-056 E
Adder
3.86117647058823543.282
934331AD1-057 C
Adder
3.9717647058823533.376
934332AD1-057 E
Adder
2.0682352941176471.758
934501AD1-074 C
Adder
38.0305882352941232.326
934502AD1-074 E
Adder
19.3616.456
934511AD1-075 C
Adder
9.507058823529418.081
934512AD1-075 E
Adder
4.844.114
934611AD1-087 C
50/50
1.5661.566
934612AD1-087 E
50/50
4.5174.517
935171AD1-152 C
50/50
1.6091.609
935172AD1-152 E
50/50
6.6176.617
937481AD2-202 C
50/50
0.4540.454
937482AD2-202 E
50/50
1.3221.322
938531AE1-072 C
50/50
19.84719.847
938532AE1-072 E
50/50
10.34610.346
939191AE1-149 C
Adder
9.5941176470588238.155
939192AE1-149 E
Adder
6.3964705882352955.437
940481AE2-033 C
50/50
19.30519.305
940482AE2-033 E
50/50
13.01513.015
940541AE2-040 C
50/50
3.4343.434
940641AE2-051 C
50/50
26.11526.115
940642AE2-051 E
50/50
17.4117.41
941101AE2-104 C
Adder
3.66705882352941173.117
941102AE2-104 E
Adder
5.8305882352941184.956
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.3016.301
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.47229.472
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.8122.81
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
107.493107.493
G-007PJM->LTFIMP_G-007
CMTX_NF
3.5513.551
NYPJM->LTFIMP_NY
CLTF
1.6611.661
LGEELTFEXP_LGEE->PJM
CLTF
1.1651.165
WECLTFEXP_WEC->PJM
CLTF
0.6140.614
CPLELTFEXP_CPLE->PJM
CLTF
13.22113.221
TVALTFEXP_TVA->PJM
CLTF
6.2796.279
MECLTFEXP_MEC->PJM
CLTF
3.8563.856
LAGNLTFEXP_LAGN->PJM
CLTF
8.048.04
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234
O66PJM->LTFIMP_O-066
CMTX_NF
22.61622.616

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o AEP_P1-2_242515_248184_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_242515_248184_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:101.34 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3263.62
MW Contribution:3.62
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
1.95529411764705881.662
961792AG1-021 E
Adder
1.66588235294117641.416
961941AG1-037 C
Adder
0.55999999999999990.476
961942AG1-037 E
Adder
0.37294117647058830.317
963041AG1-153 C
50/50
7.2587.258
963042AG1-153 E
50/50
10.88710.887
964791AG1-342 C
Adder
3.9741176470588243.378
964792AG1-342 E
Adder
2.64941176470588242.252
966621AG1-532 C
50/50
1.6081.608
966622AG1-532 E
50/50
1.0721.072
313506AB1-173 C OP
50/50
1.2841.284
3138533PONTONDP
Adder
0.72470588235294120.616
3145413WATKINS
Adder
0.76352941176470590.649
3145723EMPORIA
50/50
0.4940.494
3147043LAWRENC
50/50
0.3540.354
3147133PAMPLIN
Adder
1.09058823529411760.927
3151531CLOVER1
50/50
15.09415.094
3151541CLOVER2
50/50
14.95414.954
918492AA1-063AE OP
Adder
4.5788235294117653.892
918532AA1-067 E
Adder
0.78588235294117660.668
919692AA2-053 E OP
Adder
4.7517647058823534.039
920042AA2-088 E OP
Adder
11.78823529411764610.02
925785AC1-054 E
Adder
3.88823529411764753.305
926274AC1-105 E
Adder
2.9811764705882352.534
927146AC1-208 E
Adder
4.463.791
934521AD1-076 C
Adder
13.47647058823529411.455
934522AD1-076 E
Adder
6.8694117647058835.839
943172AE2-346 E
Adder
0.67176470588235290.571
943902AF1-058 E
Adder
1.41882352941176461.206
944011AF1-069 C
50/50
17.13917.139
944012AF1-069 E
50/50
6.6586.658
959311AF2-222 C
Adder
19.2552941176470616.367
959312AF2-222 E
Adder
12.90117647058823510.966
960081AF2-299 C
50/50
2.1442.144
960082AF2-299 E
50/50
1.4291.429
316141AB2-099 E
Adder
0.279999999999999970.238
900672V4-068 E
Adder
0.396470588235294130.337
917342Z2-044 E
Adder
0.660.561
923263AB1-132 E OP
Adder
6.8941176470588245.86
923573AB1-173 E OP
50/50
3.7353.735
924162AB2-060 E OP
Adder
4.9352941176470594.195
924302AB2-077 E O1
Adder
1.54117647058823541.31
924312AB2-078 E O1
Adder
1.54117647058823541.31
924322AB2-079 E O1
Adder
1.54117647058823541.31
925612AC1-036 E
Adder
0.99764705882352940.848
940492AE2-034 E
Adder
3.3894117647058822.881
941031AE2-094 C
50/50
52.45552.455
941032AE2-094 E
50/50
23.49323.493
946281AF1-292 C
50/50
1.7741.774
946282AF1-292 E
50/50
1.1831.183
946301AF1-294 C
Adder
4.023.417
946302AF1-294 E
Adder
3.40470588235294122.894
957481AF2-042 C
50/50
65.35965.359
957482AF2-042 E
50/50
43.57343.573
957861AF2-080 C
Adder
2.9552941176470592.512
958211AF2-115 C
Adder
2.4447058823529412.078
958212AF2-115 E
Adder
2.08235294117647071.77
3145393UNCAMP
Adder
6.6964705882352955.692
916042Z1-036 E
Adder
31.33529411764706326.635
938771AE1-103 C
Adder
3.2188235294117652.736
938772AE1-103 E
Adder
4.4447058823529423.778
933502AC2-165 E
50/50
8.4968.496
3143316POE
50/50
1.5031.503
3145256KINGFORK
Adder
1.07411764705882360.913
3145506HICKORY
50/50
2.3832.383
3150831SPRUNCA
Adder
9.0235294117647067.67
3150841SPRUNCB
Adder
9.0235294117647067.67
926662AC1-147 E
Adder
1.43529411764705881.22
926755AC1-161 E
50/50
14.05414.054
935112AD1-144 E
Adder
0.99764705882352940.848
942341AE2-247 C
Adder
1.61058823529411771.369
942342AE2-247 E
Adder
2.2235294117647061.89
943461AF1-017 C
Adder
1.45647058823529421.238
943462AF1-017 E
Adder
2.37764705882352922.021
943612AF1-032 E
Adder
1.00588235294117640.855
958502AF2-144 E
50/50
1.4471.447
3151021BRUNSWICKG1
50/50
10.71310.713
3151031BRUNSWICKG2
50/50
10.71310.713
3151041BRUNSWICKG3
50/50
10.71310.713
3151051BRUNSWICKS1
50/50
22.25722.257
3151081ELIZAR1
50/50
3.4743.474
3151101ELIZAR3
50/50
3.5183.518
3152411Z1-086 GT1
50/50
13.74313.743
3152421Z1-086 GT2
50/50
13.73913.739
3152431Z1-086 GT3
50/50
13.73913.739
3152441Z1-086 ST
50/50
23.92523.925
913392Y1-086 E
Adder
2.40235294117647062.042
916192Z1-068 E
50/50
2.0462.046
923832AB2-022 E
Adder
1.3564705882352941.153
923852AB2-025 E
50/50
1.3671.367
923862AB2-026 E
50/50
1.4721.472
938552AE1-074 E
50/50
1.5121.512
938562AE1-075 E
50/50
1.2551.255
939312AE1-162 E
Adder
1.46588235294117641.246
957492AF2-043 E
Adder
1.54705882352941181.315
901082W1-029 E
Adder
34.83647058823529429.611
917122Z2-027 E
Adder
1.4682352941176471.248
925522AC1-027 E
50/50
1.3251.325
942001AE2-212 C
Adder
2.19764705882352951.868
942002AE2-212 E
Adder
1.46470588235294131.245
957871AF2-081 C
50/50
10.92110.921
957872AF2-081 E
50/50
4.6814.681
958161AF2-110 C
Adder
1.48823529411764691.265
958162AF2-110 E
Adder
2.3670588235294122.012
3147223TWITTYS
Adder
1.10588235294117650.94
926071AC1-086 C
Adder
23.6894117647058820.136
926072AC1-086 E
Adder
10.782352941176479.165
927021AC1-189 C
Adder
9.2541176470588237.866
936261AD2-033 C
Adder
14.6612.461
936262AD2-033 E
Adder
9.7729411764705898.307
933291AC2-141 C
50/50
32.92332.923
933292AC2-141 E
50/50
14.05414.054
934621AD1-088 C
50/50
11.28411.284
934622AD1-088 E
50/50
5.4335.433
939411AE1-173 C
50/50
113.794113.794
939412AE1-173 E
50/50
75.86375.863
916191Z1-068 C
50/50
0.0480.048
933981AD1-022 C
Adder
9.657647058823538.209
933982AD1-022 E
Adder
5.257647058823534.469
962572AG1-106 E
Adder
1.341.139
962571AG1-106 C
Adder
3.06470588235294142.605
3145946PLYMOUTH TP
Adder
0.35529411764705880.302
3146326AYDLETT TAP
50/50
1.4821.482
316023AB2-100 C2
50/50
1.1041.104
316185AD1-033 C
50/50
1.3431.343
316233AE1-074 C
50/50
3.0023.002
316258AE1-075 C
50/50
0.4170.417
316274AC1-208 C
Adder
10.0447058823529418.538
316294AC1-161 C
50/50
5.385.38
316313AB2-026 C
50/50
0.4550.455
316315AB2-025 C
50/50
0.480.48
316316AC1-027 C
50/50
0.3440.344
316336AC2-165 C
50/50
11.28911.289
316365AB2-100 C1
50/50
1.1041.104
316405AF2-144 C
50/50
0.3540.354
917332KELFORD E
Adder
1.82470588235294121.551
924516AB2-100 E1
50/50
3.3273.327
924517AB2-100 E2
50/50
3.3273.327
926206AC1-098 E
Adder
4.06000000000000053.451
926214AC1-099 E
Adder
1.34117647058823521.14
934065AD1-033 E
50/50
5.485.48
937226AE2-253 E
50/50
6.3856.385
918512AA1-065 E OP
Adder
6.1129411764705885.196
316017AA1-139 ULT1
50/50
1.1821.182
316018AA1-139 ULT2
50/50
1.1821.182
919153AA1-139 E2
50/50
4.4664.466
919152AA1-139 E1
50/50
4.4664.466
919710AA2-057 E
Adder
4.3929411764705883.734
920692AA2-178 E
Adder
4.5188235294117653.841
316181AB2-040 GEN
50/50
1.4461.446
923994AB2-040_E
50/50
7.0037.003
924022AB2-043 E O1
Adder
5.9905882352941175.092
316084AB2-161 E
Adder
5.8929411764705895.009
925122AB2-169 E
Adder
6.3270588235294125.378
316087AB2-174 C
50/50
1.3431.343
316088AB2-174 E
50/50
7.4387.438
932046AC2-012 E
Adder
14.19882352941176712.069
316311AC2-079 C
Adder
6.1964705882352955.267
932596AC2-079 E
Adder
10.1105882352941178.594
934576AD1-082 E
Adder
4.6952941176470593.991
316349AD2-085 C
Adder
3.7152941176470593.158
936666AD2-085 E
Adder
6.062352941176475.153
316388AE2-253 GEN
50/50
2.1472.147
961611AG1-000B C
Adder
15.56000000000000213.226
941591AE2-156 C
Adder
19.4082352941176516.497
944581AF1-123 C
50/50
49.58949.589
944582AF1-123 E
50/50
113.553113.553
944591AF1-124 C
50/50
49.76549.765
944592AF1-124 E
50/50
113.964113.964
944601AF1-125 C
50/50
48.82548.825
944602AF1-125 E
50/50
111.771111.771
962561AG1-105 C
Adder
10.0129411764705878.511
962562AG1-105 E
Adder
6.6752941176470595.674
964241AG1-285 C
50/50
14.99914.999
964242AG1-285 E
50/50
1010
3137643SOCKMAN
Adder
0.80705882352941180.686
932632AC2-084 E
Adder
3.58823529411764673.05
934321AD1-056 C
Adder
6.9588235294117655.915
934322AD1-056 E
Adder
3.7752941176470593.209
934331AD1-057 C
Adder
3.88235294117647063.3
934332AD1-057 E
Adder
2.0211764705882351.718
934501AD1-074 C
Adder
37.1082352941176531.542
934502AD1-074 E
Adder
18.89058823529411816.057
934511AD1-075 C
Adder
9.2764705882352957.885
934512AD1-075 E
Adder
4.7223529411764714.014
934611AD1-087 C
50/50
1.4861.486
934612AD1-087 E
50/50
4.2874.287
935171AD1-152 C
50/50
1.5411.541
935172AD1-152 E
50/50
6.3396.339
937481AD2-202 C
50/50
0.4310.431
937482AD2-202 E
50/50
1.2551.255
938531AE1-072 C
50/50
19.20519.205
938532AE1-072 E
50/50
10.01210.012
939191AE1-149 C
Adder
11.3364705882352949.636
939192AE1-149 E
Adder
7.557647058823536.424
940481AE2-033 C
50/50
1919
940482AE2-033 E
50/50
12.80912.809
940541AE2-040 C
50/50
3.383.38
940641AE2-051 C
50/50
22.59322.593
940642AE2-051 E
50/50
15.06215.062
941101AE2-104 C
Adder
3.6470588235294123.1
941102AE2-104 E
Adder
5.7988235294117664.929
942461AE2-259 C
Adder
10.4729411764705888.902
942462AE2-259 E
Adder
6.9823529411764715.935
316303AF2-085
50/50
5.3815.381
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.1846.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.40542.405
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.02428.024
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
109.89109.89
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6484.648
NYPJM->LTFIMP_NY
CLTF
2.1382.138
LGEELTFEXP_LGEE->PJM
CLTF
1.6941.694
WECLTFEXP_WEC->PJM
CLTF
0.8760.876
CPLELTFEXP_CPLE->PJM
CLTF
12.96712.967
TVALTFEXP_TVA->PJM
CLTF
7.4317.431
MECLTFEXP_MEC->PJM
CLTF
5.1295.129
LAGNLTFEXP_LAGN->PJM
CLTF
9.3749.374
SIGELTFEXP_SIGE->PJM
CLTF
0.3240.324
O66PJM->LTFIMP_O-066
CMTX_NF
29.57929.579

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.69 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4423.72
MW Contribution:5.72
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:114.82 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4673.36
MW Contribution:4.89
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
3.08941176470588232.626
961792AG1-021 E
Adder
2.6317647058823532.237
963041AG1-153 C
50/50
17.36617.366
963042AG1-153 E
50/50
26.04926.049
964791AG1-342 C
50/50
7.2097.209
964792AG1-342 E
50/50
4.8064.806
3138533PONTONDP
Adder
1.14470588235294120.973
3147133PAMPLIN
50/50
1.8091.809
3151531CLOVER1
50/50
32.82932.829
3151541CLOVER2
50/50
32.52432.524
3151581KERR 1
50/50
0.7110.711
3151591KERR 2
50/50
1.991.99
3151601KERR 3
50/50
1.991.99
3151611KERR 4
50/50
1.991.99
3151621KERR 5
50/50
1.991.99
925785AC1-054 E
Adder
3.75647058823529443.193
926274AC1-105 E
50/50
5.5465.546
942751AE2-291 C
Adder
13.03294117647058811.078
942752AE2-291 E
Adder
8.6882352941176467.385
943902AF1-058 E
50/50
2.7082.708
944011AF1-069 C
50/50
39.18539.185
944012AF1-069 E
50/50
15.22215.222
959311AF2-222 C
50/50
34.76234.762
959312AF2-222 E
50/50
23.29123.291
24401205PINNACLE
Adder
1.62588235294117631.382
3151631KERR 6
50/50
1.991.99
3151641KERR 7
50/50
1.991.99
3152661PLYWOOD A
50/50
2.4812.481
316118AC1-105 C
50/50
1.8951.895
316131AB2-060 C
50/50
2.8942.894
924162AB2-060 E OP
50/50
8.3338.333
924302AB2-077 E O1
50/50
2.6052.605
924312AB2-078 E O1
50/50
2.6052.605
924322AB2-079 E O1
50/50
2.6052.605
925612AC1-036 E
50/50
1.8171.817
941031AE2-094 C
50/50
119.928119.928
941032AE2-094 E
50/50
53.71353.713
946301AF1-294 C
Adder
6.3505882352941185.398
946302AF1-294 E
Adder
5.377647058823534.571
957481AF2-042 C
50/50
147.496147.496
957482AF2-042 E
50/50
98.33198.331
958211AF2-115 C
Adder
3.86117647058823543.282
958212AF2-115 E
Adder
3.2894117647058822.796
924032AB2-045 E
Adder
1.26941176470588221.079
3151021BRUNSWICKG1
50/50
25.63425.634
3151031BRUNSWICKG2
50/50
25.63425.634
3151041BRUNSWICKG3
50/50
25.63425.634
3151051BRUNSWICKS1
50/50
53.25453.254
3152411Z1-086 GT1
50/50
32.42432.424
3152421Z1-086 GT2
50/50
32.41332.413
3152431Z1-086 GT3
50/50
32.41332.413
3152441Z1-086 ST
50/50
56.44456.444
957601AF2-054 C
Adder
-1.72-1.462
942001AE2-212 C
Adder
-1.9541176470588235-1.661
3147223TWITTYS
50/50
2.0152.015
936261AD2-033 C
50/50
24.11624.116
936262AD2-033 E
50/50
16.07816.078
933291AC2-141 C
Adder
-31.96117647058824-27.167
934621AD1-088 C
50/50
23.87723.877
934622AD1-088 E
50/50
11.49611.496
316003AC1-222 C
50/50
2.0082.008
316034AC1-036 C
50/50
0.4960.496
316222AC1-221 C
50/50
2.9122.912
316237AB2-079 C O1
50/50
0.6390.639
316238AB2-078 C O1
50/50
0.6390.639
316239AB2-077 C O1
50/50
0.6390.639
316240AF1-291 C
Adder
-1.863529411764706-1.584
316248AF1-058 C
50/50
0.6640.664
316283AC2-100 C
50/50
2.3312.331
927255AC1-221 E
50/50
7.6147.614
927264AC1-222 E
50/50
8.2018.201
932763AC2-100 E
50/50
5.1295.129
313527AB2-043 C
50/50
1.011.01
924022AB2-043 E O1
50/50
10.1410.14
925997AC1-075 E
Adder
5.1705882352941174.395
926024AC1-080 E
Adder
1.71529411764705891.458
962561AG1-105 C
50/50
17.96517.965
962562AG1-105 E
50/50
11.97711.977
964241AG1-285 C
50/50
28.57228.572
964242AG1-285 E
50/50
19.04819.048
934611AD1-087 C
50/50
3.233.23
934612AD1-087 E
50/50
9.3199.319
935171AD1-152 C
50/50
3.2363.236
935172AD1-152 E
50/50
13.31413.314
936161AD2-022 C
Adder
12.41176470588235310.55
936162AD2-022 E
Adder
7.4470588235294126.33
936171AD2-023 C
Adder
7.246.154
936172AD2-023 E
Adder
3.9305882352941183.341
937481AD2-202 C
50/50
0.9370.937
937482AD2-202 E
50/50
2.7272.727
938531AE1-072 C
Adder
-16.06705882352941-13.657
940641AE2-051 C
Adder
-21.288235294117648-18.095
942461AE2-259 C
Adder
16.0152941176470613.613
942462AE2-259 E
Adder
10.6764705882352939.075
944641AF1-129 C
Adder
-87.13882352941177-74.068
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.4399.439
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.04159.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.12440.124
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
169.426169.426
G-007PJM->LTFIMP_G-007
CMTX_NF
4.1284.128
NYPJM->LTFIMP_NY
CLTF
1.8831.883
LGEELTFEXP_LGEE->PJM
CLTF
2.2642.264
WECLTFEXP_WEC->PJM
CLTF
1.2081.208
CPLELTFEXP_CPLE->PJM
CLTF
19.79519.795
TVALTFEXP_TVA->PJM
CLTF
10.7110.71
MECLTFEXP_MEC->PJM
CLTF
7.1897.189
LAGNLTFEXP_LAGN->PJM
CLTF
13.6813.68
SIGELTFEXP_SIGE->PJM
CLTF
0.4430.443
O66PJM->LTFIMP_O-066
CMTX_NF
26.2626.26

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.42 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2598.93
MW Contribution:2.46
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.96 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2758.53
MW Contribution:2.3
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.73882352941176480.628
961672AG1-007 E
Adder
0.41882352941176470.356
961791AG1-021 C
Adder
1.33058823529411761.131
961792AG1-021 E
Adder
1.13294117647058810.963
961941AG1-037 C
Adder
0.367058823529411770.312
961942AG1-037 E
Adder
0.244705882352941160.208
963041AG1-153 C
50/50
6.556.55
963042AG1-153 E
50/50
9.8259.825
964791AG1-342 C
Adder
3.09882352941176452.634
964792AG1-342 E
Adder
2.06588235294117651.756
966621AG1-532 C
Adder
1.15411764705882350.981
966622AG1-532 E
Adder
0.76941176470588240.654
3138533PONTONDP
Adder
0.49294117647058820.419
3145413WATKINS
Adder
0.451764705882352960.384
3145723EMPORIA
Adder
0.352941176470588260.3
3147133PAMPLIN
Adder
0.740.629
3151311EDGECMA
Adder
12.4152941176470610.553
3151531CLOVER1
50/50
12.55212.552
3151541CLOVER2
50/50
12.43612.436
918492AA1-063AE OP
Adder
3.0882352941176472.625
918532AA1-067 E
Adder
0.54705882352941180.465
919692AA2-053 E OP
Adder
3.30000000000000032.805
920042AA2-088 E OP
Adder
7.3835294117647066.276
925785AC1-054 E
Adder
2.882.448
926274AC1-105 E
Adder
2.3364705882352941.986
927146AC1-208 E
Adder
3.14470588235294152.673
934521AD1-076 C
Adder
9.1176470588235297.75
934522AD1-076 E
Adder
4.6470588235294123.95
943172AE2-346 E
Adder
0.440.374
943902AF1-058 E
Adder
1.11882352941176480.951
944011AF1-069 C
50/50
15.67315.673
944012AF1-069 E
50/50
6.0886.088
959311AF2-222 C
Adder
14.27882352941176512.137
959312AF2-222 E
Adder
9.5670588235294118.132
960081AF2-299 C
Adder
1.541.309
960082AF2-299 E
Adder
1.02588235294117650.872
316141AB2-099 E
Adder
0.183529411764705890.156
900672V4-068 E
Adder
0.254117647058823560.216
917342Z2-044 E
Adder
0.475294117647058870.404
922923AB1-081 E OP
Adder
2.9811764705882352.534
923263AB1-132 E OP
Adder
4.8517647058823534.124
923573AB1-173 E OP
Adder
2.65411764705882322.256
924162AB2-060 E OP
Adder
3.78117647058823543.214
924302AB2-077 E O1
Adder
1.18705882352941171.009
924312AB2-078 E O1
Adder
1.18705882352941171.009
924322AB2-079 E O1
Adder
1.18705882352941171.009
925612AC1-036 E
Adder
0.74705882352941180.635
940492AE2-034 E
Adder
2.3152941176470591.968
941031AE2-094 C
50/50
47.96747.967
941032AE2-094 E
50/50
21.48321.483
946281AF1-292 C
Adder
1.27411764705882361.083
946282AF1-292 E
Adder
0.84941176470588230.722
946301AF1-294 C
Adder
2.73529411764705932.325
946302AF1-294 E
Adder
2.3164705882352941.969
957481AF2-042 C
50/50
55.26355.263
957482AF2-042 E
50/50
36.84236.842
957861AF2-080 C
Adder
5.9388235294117655.048
957862AF2-080 E
Adder
2.6329411764705882.238
958211AF2-115 C
Adder
1.6635294117647061.414
958212AF2-115 E
Adder
1.41647058823529411.204
3145393UNCAMP
Adder
3.8517647058823533.274
916042Z1-036 E
Adder
21.67647058823529718.425
938771AE1-103 C
Adder
1.81647058823529431.544
938772AE1-103 E
Adder
2.50941176470588222.133
3143316POE
Adder
0.80823529411764720.687
3145506HICKORY
50/50
2.1612.161
926662AC1-147 E
Adder
1.23058823529411781.046
926755AC1-161 E
50/50
37.13537.135
3151021BRUNSWICKG1
50/50
9.6689.668
3151031BRUNSWICKG2
50/50
9.6689.668
3151041BRUNSWICKG3
50/50
9.6689.668
3151051BRUNSWICKS1
50/50
20.08620.086
3151081ELIZAR1
50/50
3.033.03
3151091ELIZAR2
50/50
2.9782.978
3151101ELIZAR3
50/50
3.0693.069
3152411Z1-086 GT1
50/50
12.45512.455
3152421Z1-086 GT2
50/50
12.4512.45
3152431Z1-086 GT3
50/50
12.4512.45
3152441Z1-086 ST
50/50
21.68121.681
913392Y1-086 E
Adder
1.8917647058823531.608
916192Z1-068 E
50/50
1.7941.794
923832AB2-022 E
Adder
1.06823529411764720.908
923852AB2-025 E
Adder
0.98588235294117640.838
957601AF2-054 C
Adder
-1.2505882352941176-1.063
901082W1-029 E
Adder
23.54352941176470520.012
917122Z2-027 E
Adder
1.1117647058823530.945
925522AC1-027 E
50/50
1.1581.158
957871AF2-081 C
50/50
9.4939.493
957872AF2-081 E
50/50
4.0684.068
3147223TWITTYS
Adder
0.82823529411764710.704
917512Z2-088 E OP1
Adder
3.83294117647058833.258
926071AC1-086 C
Adder
16.6705882352941214.17
926072AC1-086 E
Adder
7.5870588235294126.449
927021AC1-189 C
Adder
6.5388235294117655.558
927022AC1-189 E
Adder
3.25764705882352962.769
936261AD2-033 C
Adder
10.7294117647058829.12
936262AD2-033 E
Adder
7.1529411764705896.08
933291AC2-141 C
50/50
86.99486.994
933292AC2-141 E
50/50
37.13537.135
934621AD1-088 C
50/50
9.1619.161
934622AD1-088 E
50/50
4.4114.411
939411AE1-173 C
50/50
86.92186.921
939412AE1-173 E
50/50
57.94757.947
916191Z1-068 C
50/50
0.0420.042
933981AD1-022 C
Adder
6.4741176470588245.503
933982AD1-022 E
Adder
3.52470588235294142.996
962572AG1-106 E
Adder
0.9435294117647060.802
962571AG1-106 C
Adder
2.1564705882352941.833
3145946PLYMOUTH TP
Adder
0.24117647058823530.205
3146326AYDLETT TAP
Adder
1.25647058823529421.068
316185AD1-033 C
50/50
1.2261.226
316263AC1-034 C
Adder
5.31058823529411854.514
316274AC1-208 C
Adder
7.0835294117647066.021
316294AC1-161 C
50/50
14.21614.216
316316AC1-027 C
50/50
0.3010.301
917332KELFORD E
Adder
1.2282352941176471.044
924516AB2-100 E1
Adder
2.3717647058823532.016
924517AB2-100 E2
Adder
2.3717647058823532.016
925595AC1-034 E
Adder
4.00588235294117643.405
926206AC1-098 E
Adder
2.8317647058823532.407
926214AC1-099 E
Adder
0.93529411764705890.795
927255AC1-221 E
Adder
3.2152941176470592.733
927264AC1-222 E
Adder
3.3870588235294122.879
932763AC2-100 E
Adder
2.1788235294117651.852
934065AD1-033 E
50/50
5.0045.004
937226AE2-253 E
50/50
5.6435.643
918512AA1-065 E OP
Adder
3.98941176470588273.391
316017AA1-139 ULT1
50/50
1.0281.028
316018AA1-139 ULT2
50/50
1.0281.028
919153AA1-139 E2
50/50
3.8823.882
919152AA1-139 E1
50/50
3.8823.882
919710AA2-057 E
Adder
3.1364705882352942.666
920692AA2-178 E
Adder
3.0870588235294122.624
923994AB2-040_E
Adder
4.9776470588235294.231
924022AB2-043 E O1
Adder
4.6082352941176473.917
924152AB2-059 E OP
Adder
4.2235294117647063.59
925122AB2-169 E
Adder
4.3388235294117653.688
316088AB2-174 E
Adder
5.3035294117647064.508
316375AC2-012 C
50/50
1.2551.255
932046AC2-012 E
50/50
12.1712.17
316388AE2-253 GEN
50/50
1.8981.898
941591AE2-156 C
50/50
16.7516.75
944581AF1-123 C
50/50
45.64445.644
944582AF1-123 E
50/50
104.52104.52
944591AF1-124 C
50/50
45.80645.806
944592AF1-124 E
50/50
104.898104.898
944601AF1-125 C
50/50
44.94144.941
944602AF1-125 E
50/50
102.879102.879
962561AG1-105 C
Adder
7.7917647058823536.623
962562AG1-105 E
Adder
5.1941176470588244.415
964241AG1-285 C
Adder
11.7588235294117649.995
964242AG1-285 E
Adder
7.846.664
3137643SOCKMAN
Adder
0.56941176470588240.484
932632AC2-084 E
Adder
2.50352941176470622.128
934321AD1-056 C
Adder
4.99411764705882364.245
934322AD1-056 E
Adder
2.70941176470588242.303
934331AD1-057 C
Adder
2.78588235294117632.368
934332AD1-057 E
Adder
1.45058823529411771.233
934501AD1-074 C
Adder
25.10470588235294221.339
934502AD1-074 E
Adder
12.7810.863
934511AD1-075 C
Adder
6.2764705882352945.335
934512AD1-075 E
Adder
3.19529411764705932.716
934611AD1-087 C
50/50
1.2361.236
934612AD1-087 E
50/50
3.5653.565
935172AD1-152 E
Adder
5.2058823529411774.425
937481AD2-202 C
50/50
0.3590.359
937482AD2-202 E
50/50
1.0431.043
938531AE1-072 C
50/50
16.39816.398
938532AE1-072 E
50/50
8.5488.548
940481AE2-033 C
Adder
13.6776470588235311.626
940482AE2-033 E
Adder
9.2211764705882357.838
940541AE2-040 C
Adder
2.4364705882352942.071
940641AE2-051 C
50/50
26.4726.47
940642AE2-051 E
50/50
17.64717.647
942461AE2-259 C
Adder
6.5341176470588245.554
942462AE2-259 E
Adder
4.3564705882352943.703
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.7574.757
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.52724.527
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.91517.915
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.65881.658
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1242.124
NYPJM->LTFIMP_NY
CLTF
0.9860.986
LGEELTFEXP_LGEE->PJM
CLTF
0.950.95
WECLTFEXP_WEC->PJM
CLTF
0.5060.506
CPLELTFEXP_CPLE->PJM
CLTF
9.989.98
TVALTFEXP_TVA->PJM
CLTF
4.8674.867
MECLTFEXP_MEC->PJM
CLTF
3.1033.103
LAGNLTFEXP_LAGN->PJM
CLTF
6.2356.235
SIGELTFEXP_SIGE->PJM
CLTF
0.1890.189
O66PJM->LTFIMP_O-066
CMTX_NF
13.52713.527

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.93 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4311.71
MW Contribution:4.98
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.26 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4569.37
MW Contribution:4.28
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
2.68823529411764732.285
961792AG1-021 E
Adder
2.28941176470588251.946
963041AG1-153 C
50/50
17.20617.206
963042AG1-153 E
50/50
25.80825.808
964791AG1-342 C
50/50
6.3476.347
964792AG1-342 E
50/50
4.2324.232
3138533PONTONDP
Adder
0.99529411764705880.846
3147133PAMPLIN
50/50
1.5711.571
3151531CLOVER1
50/50
28.70828.708
3151541CLOVER2
50/50
28.44128.441
3151581KERR 1
50/50
0.6270.627
3151591KERR 2
50/50
1.7561.756
3151601KERR 3
50/50
1.7561.756
3151611KERR 4
50/50
1.7561.756
3151621KERR 5
50/50
1.7561.756
925785AC1-054 E
Adder
3.30235294117647052.807
926274AC1-105 E
50/50
4.8944.894
942751AE2-291 C
Adder
11.5670588235294139.832
942752AE2-291 E
Adder
7.7105882352941186.554
943902AF1-058 E
50/50
2.3942.394
944011AF1-069 C
50/50
45.64245.642
944012AF1-069 E
50/50
17.73117.731
959311AF2-222 C
50/50
30.29330.293
959312AF2-222 E
50/50
20.29620.296
24401205PINNACLE
Adder
1.53647058823529431.306
3151631KERR 6
50/50
1.7561.756
3151641KERR 7
50/50
1.7561.756
3152661PLYWOOD A
50/50
2.1912.191
316118AC1-105 C
50/50
1.6721.672
316131AB2-060 C
50/50
2.5322.532
924162AB2-060 E OP
50/50
7.2927.292
924302AB2-077 E O1
50/50
2.2822.282
924312AB2-078 E O1
50/50
2.2822.282
924322AB2-079 E O1
50/50
2.2822.282
925612AC1-036 E
50/50
1.5841.584
941031AE2-094 C
50/50
139.691139.691
941032AE2-094 E
50/50
62.56462.564
946301AF1-294 C
Adder
5.5247058823529414.696
946302AF1-294 E
Adder
4.6788235294117653.977
957481AF2-042 C
50/50
128.648128.648
957482AF2-042 E
50/50
85.76685.766
958211AF2-115 C
Adder
3.362.856
958212AF2-115 E
Adder
2.86235294117647052.433
3151021BRUNSWICKG1
50/50
25.39725.397
3151031BRUNSWICKG2
50/50
25.39725.397
3151041BRUNSWICKG3
50/50
25.39725.397
3151051BRUNSWICKS1
50/50
52.76252.762
3152411Z1-086 GT1
50/50
33.84633.846
3152421Z1-086 GT2
50/50
33.83433.834
3152431Z1-086 GT3
50/50
33.83433.834
3152441Z1-086 ST
50/50
58.91958.919
957601AF2-054 C
Adder
-1.6305882352941177-1.386
942001AE2-212 C
Adder
-1.851764705882353-1.574
3147223TWITTYS
50/50
1.7561.756
936261AD2-033 C
50/50
21.05721.057
936262AD2-033 E
50/50
14.03814.038
933291AC2-141 C
Adder
-30.18235294117647-25.655
934621AD1-088 C
50/50
20.82320.823
934622AD1-088 E
50/50
10.02610.026
316003AC1-222 C
50/50
1.7761.776
316034AC1-036 C
50/50
0.4320.432
316222AC1-221 C
50/50
2.632.63
316237AB2-079 C O1
50/50
0.5590.559
316238AB2-078 C O1
50/50
0.5590.559
316239AB2-077 C O1
50/50
0.5590.559
316240AF1-291 C
Adder
-1.7670588235294118-1.502
316248AF1-058 C
50/50
0.5870.587
316283AC2-100 C
50/50
2.112.11
927255AC1-221 E
50/50
6.8776.877
927264AC1-222 E
50/50
7.2547.254
932763AC2-100 E
50/50
4.6444.644
313527AB2-043 C
50/50
0.8840.884
924022AB2-043 E O1
50/50
8.8758.875
925997AC1-075 E
Adder
4.5835294117647063.896
926024AC1-080 E
Adder
1.52117647058823541.293
962561AG1-105 C
50/50
15.80415.804
962562AG1-105 E
50/50
10.53610.536
964241AG1-285 C
50/50
24.94424.944
964242AG1-285 E
50/50
16.62916.629
934611AD1-087 C
50/50
2.8252.825
934612AD1-087 E
50/50
8.158.15
935171AD1-152 C
50/50
2.8452.845
935172AD1-152 E
50/50
11.70511.705
936161AD2-022 C
Adder
11.7541176470588239.991
936162AD2-022 E
Adder
7.0529411764705895.995
936171AD2-023 C
Adder
6.8564705882352955.828
936172AD2-023 E
Adder
3.7223529411764713.164
937481AD2-202 C
50/50
0.820.82
937482AD2-202 E
50/50
2.3852.385
938531AE1-072 C
Adder
-15.17764705882353-12.901
940641AE2-051 C
Adder
-20.06823529411765-17.058
942461AE2-259 C
Adder
13.86823529411764811.788
942462AE2-259 E
Adder
9.2458823529411777.859
944641AF1-129 C
Adder
-82.61058823529412-70.219
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.0719.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5656
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.3338.33
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
162.815162.815
G-007PJM->LTFIMP_G-007
CMTX_NF
3.9723.972
NYPJM->LTFIMP_NY
CLTF
1.8141.814
LGEELTFEXP_LGEE->PJM
CLTF
2.1482.148
WECLTFEXP_WEC->PJM
CLTF
1.1471.147
CPLELTFEXP_CPLE->PJM
CLTF
19.02319.023
TVALTFEXP_TVA->PJM
CLTF
10.24910.249
MECLTFEXP_MEC->PJM
CLTF
6.8436.843
LAGNLTFEXP_LAGN->PJM
CLTF
13.09813.098
SIGELTFEXP_SIGE->PJM
CLTF
0.4210.421
O66PJM->LTFIMP_O-066
CMTX_NF
25.2725.27
CONTINGENCY 'DVP_P1-2: LN 235_SRT-A'
 OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1   /*6PRINCE EDW  230.0 - 6BRIERY      230.0
 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1   /*6PRINCE EDW  230.0 - 6FARMVIL     230.0
 OPEN BRANCH FROM BUS 313996 TO BUS 314268 CKT 1   /*6FINNEYWOOD  230.0 - 6BRIERY      230.0
 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1   /*3FARMVIL     115.0 - 6FARMVIL     230.0
 OPEN BUS 313802                                   /*6PRINCE EDW  230.0
 OPEN BUS 314268                                   /*6BRIERY      230.0
END
CONTINGENCY 'DVP_P1-2: LN 1045_SRT-A'
 OPEN BRANCH FROM BUS 313898 TO BUS 314267 CKT 1   /*3BUTCHER CRK 115.0 - 3CHASCTY2    115.0
END
CONTINGENCY 'DVP_P1-2: LN 2027_SRT-A-2'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026 C    230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
 OPEN BUS 923862                                   /*AB2-026 E    230.0
 OPEN BUS 938562                                   /*AE1-075 E    230.0
 OPEN BUS 958502                                   /*AF2-144 E    230.0
END
CONTINGENCY 'DVP_P1-2: LN 578_SRT-S-1'
 OPEN BRANCH FROM BUS 314923 TO BUS 314924 CKT 1                /*8SEPTA       500.0 - 8SURRY       500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 940640 TO BUS 314902 CKT 1 /*AE2-051 TP   500.0 - 8CARSON      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 940640 TO BUS 314923 CKT 1 /*AE2-051 TP   500.0 - 8SEPTA       500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 940640 TO BUS 314902 CKT 1 /*AE2-051 TP   500.0 - 8CARSON      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 940640 TO BUS 314923 CKT 1 /*AE2-051 TP   500.0 - 8SEPTA       500.0
END
CONTINGENCY 'AEP_P1-2_242515_248184_SRT-A'
 OPEN BRANCH FROM BUS 242515 TO BUS 248184 CKT 1   /*05JOSHUA     765.0 - 05YEAT7      765.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314691 to 314692 ckt 2
313755 to 314707 ckt 1
314701 to 313755 ckt 1
314707 to 314691 ckt 1
314747 to 313867 ckt 1
313867 to 313707 ckt 1
313373 to 314765 ckt 1
313707 to 313373 ckt 1
314765 to 314749 ckt 1
314902 to 314914 ckt 1
314914 to 314918 ckt 1
314936 to 314902 ckt 1
314923 to 314924 ckt 1
941030 to 314902 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 2201_SRT-A
OPAC112.45 %252.86B284.351.24
GD1DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S-1
OPAC111.78 %1058.16B1182.781.8
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 550_SRT-S
OPAC105.93 %3220.44B3411.453.69
GD1DVP
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
OPAC105.31 %4070.2B4286.264.28

Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 2201_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.45 %
Rating:252.86 MVA
Rating Type:B
MVA to Mitigate:284.35
MW Contribution:1.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
0.67176470588235290.571
961792AG1-021 E
Adder
0.5717647058823530.486
964791AG1-342 C
Adder
1.3564705882352941.153
964792AG1-342 E
Adder
0.90352941176470590.768
966621AG1-532 C
50/50
4.3954.395
966622AG1-532 E
50/50
2.932.93
313506AB1-173 C OP
50/50
2.3342.334
3138533PONTONDP
Adder
0.248235294117647050.211
3145723EMPORIA
50/50
1.2311.231
3147043LAWRENC
50/50
0.740.74
3151261ROARAP2
50/50
1.1521.152
3151281ROARAP4
50/50
1.091.09
918492AA1-063AE OP
50/50
2.7952.795
919692AA2-053 E OP
50/50
3.1533.153
920042AA2-088 E OP
Adder
4.6305882352941183.936
925785AC1-054 E
50/50
2.0962.096
927146AC1-208 E
Adder
2.18117647058823531.854
959311AF2-222 C
Adder
7.8188235294117656.646
959312AF2-222 E
Adder
5.2388235294117654.453
960081AF2-299 C
50/50
5.865.86
960082AF2-299 E
50/50
3.9073.907
3156063AA2-053SOLA
50/50
1.1211.121
316129AC1-054 C
50/50
0.7410.741
316131AB2-060 C
50/50
0.8950.895
900672V4-068 E
Adder
0.149411764705882360.127
923263AB1-132 E OP
Adder
2.7023529411764712.297
923573AB1-173 E OP
50/50
6.8126.812
924162AB2-060 E OP
50/50
2.5852.585
924302AB2-077 E O1
Adder
0.79529411764705890.676
924312AB2-078 E O1
Adder
0.79529411764705890.676
924322AB2-079 E O1
Adder
0.79529411764705890.676
925612AC1-036 E
Adder
0.41647058823529410.354
946281AF1-292 C
50/50
4.8514.851
946282AF1-292 E
50/50
3.2343.234
946301AF1-294 C
Adder
1.38117647058823521.174
946302AF1-294 E
Adder
1.16941176470588240.994
958211AF2-115 C
Adder
0.840.714
958212AF2-115 E
Adder
0.71529411764705890.608
3156073AA1-063SOLA
50/50
0.9590.959
3147223TWITTYS
Adder
0.46117647058823530.392
926071AC1-086 C
Adder
9.2870588235294127.894
926072AC1-086 E
Adder
4.2270588235294123.593
936261AD2-033 C
Adder
6.6258823529411775.632
936262AD2-033 E
Adder
4.4164705882352953.754
962572AG1-106 E
Adder
0.52588235294117650.447
962571AG1-106 C
Adder
1.20117647058823531.021
316274AC1-208 C
Adder
4.9105882352941184.174
917332KELFORD E
Adder
0.63764705882352950.542
924516AB2-100 E1
Adder
1.23882352941176471.053
924517AB2-100 E2
Adder
1.23882352941176471.053
926206AC1-098 E
Adder
1.7470588235294121.485
926214AC1-099 E
Adder
0.57647058823529410.49
919710AA2-057 E
Adder
1.7070588235294121.451
316181AB2-040 GEN
50/50
2.6292.629
923994AB2-040_E
50/50
12.77312.773
313527AB2-043 C
50/50
0.3160.316
924022AB2-043 E O1
50/50
3.1813.181
316087AB2-174 C
50/50
2.8212.821
316088AB2-174 E
50/50
15.67415.674
962561AG1-105 C
Adder
3.72941176470588243.17
962562AG1-105 E
Adder
2.48588235294117642.113
964241AG1-285 C
Adder
7.126.052
964242AG1-285 E
Adder
4.7470588235294124.035
3137643SOCKMAN
50/50
1.0011.001
932632AC2-084 E
Adder
1.5435294117647061.312
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.7010.701
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.4494.449
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.8192.819
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.39311.393
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3410.341
NYPJM->LTFIMP_NY
CLTF
0.1550.155
LGEELTFEXP_LGEE->PJM
CLTF
0.1740.174
WECLTFEXP_WEC->PJM
CLTF
0.0910.091
CPLELTFEXP_CPLE->PJM
CLTF
1.471.47
TVALTFEXP_TVA->PJM
CLTF
0.7390.739
MECLTFEXP_MEC->PJM
CLTF
0.5250.525
LAGNLTFEXP_LAGN->PJM
CLTF
0.9350.935
SIGELTFEXP_SIGE->PJM
CLTF
0.0330.033
O66PJM->LTFIMP_O-066
CMTX_NF
2.1672.167

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.78 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1182.78
MW Contribution:1.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
0.97294117647058820.827
961792AG1-021 E
Adder
0.82823529411764710.704
963041AG1-153 C
Adder
2.2623529411764711.923
963042AG1-153 E
Adder
3.39411764705882352.885
966621AG1-532 C
Adder
0.63882352941176480.543
966622AG1-532 E
Adder
0.42588235294117650.362
3138533PONTONDP
Adder
0.360.306
3145413WATKINS
Adder
0.30941176470588240.263
3145723EMPORIA
Adder
0.196470588235294150.167
3147133PAMPLIN
Adder
0.54941176470588240.467
918492AA1-063AE OP
Adder
1.8117647058823531.54
919692AA2-053 E OP
Adder
1.86823529411764721.588
920042AA2-088 E OP
Adder
4.724.012
944011AF1-069 C
Adder
5.2235294117647074.44
944012AF1-069 E
Adder
2.02941176470588271.725
959311AF2-222 C
Adder
8.5341176470588237.254
959312AF2-222 E
Adder
5.71764705882352954.86
960081AF2-299 C
Adder
0.8517647058823530.724
960082AF2-299 E
Adder
0.56823529411764710.483
900672V4-068 E
Adder
0.157647058823529420.134
923263AB1-132 E OP
Adder
2.70941176470588242.303
923573AB1-173 E OP
Adder
1.47764705882352951.256
924162AB2-060 E OP
Adder
2.0117647058823531.71
924302AB2-077 E O1
Adder
0.62117647058823530.528
924312AB2-078 E O1
Adder
0.62117647058823530.528
924322AB2-079 E O1
Adder
0.62117647058823530.528
925612AC1-036 E
Adder
0.435294117647058830.37
940492AE2-034 E
Adder
1.33882352941176451.138
941011AE2-092 C
Adder
6.9470588235294125.905
941012AE2-092 E
Adder
4.6305882352941183.936
941031AE2-094 C
Adder
15.98588235294117513.588
941032AE2-094 E
Adder
7.166.086
946281AF1-292 C
Adder
0.70588235294117650.6
946282AF1-292 E
Adder
0.47058823529411770.4
946301AF1-294 C
Adder
1.99882352941176491.699
946302AF1-294 E
Adder
1.69294117647058841.439
957481AF2-042 C
Adder
23.21647058823529619.734
957482AF2-042 E
Adder
15.4776470588235313.156
958211AF2-115 C
Adder
1.21529411764705891.033
958212AF2-115 E
Adder
1.0352941176470590.88
3145393UNCAMP
Adder
2.72117647058823582.313
916042Z1-036 E
Adder
12.43647058823529310.571
938771AE1-103 C
Adder
1.3117647058823531.115
938772AE1-103 E
Adder
1.8117647058823531.54
924032AB2-045 E
Adder
0.94941176470588240.807
933502AC2-165 E
50/50
10.19910.199
3143096IRON208
50/50
0.330.33
3143316POE
Adder
0.75647058823529410.643
3145256KINGFORK
Adder
0.455294117647058850.387
3145506HICKORY
Adder
0.94470588235294130.803
3150601CHESTF5
Adder
39.4470588235294233.53
3150651CHESTF6
Adder
11.96588235294117610.171
3150731STONECA
Adder
4.1494117647058823.527
3150831SPRUNCA
50/50
9.4469.446
3150841SPRUNCB
50/50
9.4469.446
3150921YORKTN3
Adder
52.8152941176470644.893
925865AC1-065 E
Adder
7.73058823529411756.571
926412AC1-112 E
Adder
0.56470588235294120.48
926662AC1-147 E
Adder
0.58117647058823530.494
926755AC1-161 E
Adder
0.59529411764705890.506
927226AC1-216 E
Adder
4.20352941176470553.573
934392AD1-063 E
Adder
0.487058823529411770.414
935112AD1-144 E
Adder
0.42235294117647060.359
942341AE2-247 C
Adder
0.71294117647058820.606
942342AE2-247 E
Adder
0.98470588235294120.837
943461AF1-017 C
Adder
0.64470588235294120.548
943462AF1-017 E
Adder
1.0517647058823530.894
943612AF1-032 E
Adder
0.405882352941176470.345
958502AF2-144 E
50/50
1.7771.777
966871AG1-558 C
Adder
1.27764705882352961.086
966872AG1-558 E
Adder
0.64352941176470590.547
316076AC2-137 E
Adder
0.73529411764705890.625
316157AD2-030 E
Adder
0.53411764705882360.454
913392Y1-086 E
Adder
0.9552941176470590.812
916192Z1-068 E
Adder
0.820.697
923832AB2-022 E
Adder
0.53882352941176470.458
923842AB2-024 E
Adder
0.82235294117647050.699
923852AB2-025 E
Adder
0.54941176470588240.467
923862AB2-026 E
50/50
1.8081.808
930122AB1-027 E
Adder
0.69529411764705880.591
938552AE1-074 E
50/50
1.8811.881
938562AE1-075 E
50/50
1.5421.542
939312AE1-162 E
Adder
0.67999999999999990.578
946262AF1-291 E
Adder
0.91058823529411770.774
957492AF2-043 E
Adder
0.62470588235294120.531
957601AF2-054 C
Adder
0.95294117647058830.81
957602AF2-054 E
Adder
0.63529411764705890.54
962962AG1-145 E
Adder
0.65529411764705890.557
901082W1-029 E
Adder
13.8976470588235311.813
917122Z2-027 E
Adder
0.58470588235294120.497
925332AB2-190 E
Adder
4.5752941176470593.889
925522AC1-027 E
Adder
0.53176470588235290.452
942001AE2-212 C
Adder
1.3035294117647061.108
942002AE2-212 E
Adder
0.86941176470588230.739
957832AF2-077 E
Adder
0.63529411764705890.54
957871AF2-081 C
Adder
4.3329411764705883.683
957872AF2-081 E
Adder
1.85647058823529431.578
958161AF2-110 C
Adder
0.61529411764705890.523
958162AF2-110 E
Adder
0.97882352941176460.832
3138116ELKO L286
Adder
0.76588235294117660.651
3147223TWITTYS
Adder
0.48235294117647060.41
926071AC1-086 C
Adder
9.3082352941176477.912
926072AC1-086 E
Adder
4.2364705882352943.601
936261AD2-033 C
Adder
6.5000000000000015.525
936262AD2-033 E
Adder
4.3329411764705883.683
933291AC2-141 C
Adder
12.51176470588235310.635
934621AD1-088 C
Adder
4.3294117647058833.68
934622AD1-088 E
Adder
2.08470588235294141.772
939411AE1-173 C
Adder
37.3388235294117631.738
939412AE1-173 E
Adder
24.89294117647058621.159
934012AD1-025 E
Adder
5.44117647058823554.625
927041AC1-191 C
Adder
5.1282352941176474.359
927042AC1-191 E
Adder
2.55411764705882362.171
962572AG1-106 E
Adder
0.52705882352941180.448
962571AG1-106 C
Adder
1.20352941176470571.023
3130536PAPERMILL
Adder
3.0341176470588242.579
3146326AYDLETT TAP
Adder
0.58823529411764710.5
316160AE1-175 E
Adder
0.54117647058823540.46
316169AC1-164 GEN
Adder
19.79647058823529816.827
316233AE1-074 C
50/50
3.7333.733
316240AF1-291 C
Adder
1.36588235294117651.161
316258AE1-075 C
50/50
0.5110.511
316313AB2-026 C
50/50
0.5570.557
316336AC2-165 C
50/50
13.55213.552
316405AF2-144 C
50/50
0.4340.434
924516AB2-100 E1
Adder
1.32117647058823541.123
924517AB2-100 E2
Adder
1.32117647058823541.123
926785AC1-164_E
Adder
8.8941176470588247.56
934065AD1-033 E
Adder
2.1752941176470591.849
937226AE2-253 E
Adder
2.53176470588235342.152
939612AE1-191 E
Adder
2.6082352941176472.217
919153AA1-139 E2
Adder
1.7717647058823531.506
919152AA1-139 E1
Adder
1.7717647058823531.506
920692AA2-178 E
Adder
1.78588235294117651.518
923994AB2-040_E
Adder
2.76941176470588252.354
924022AB2-043 E O1
Adder
2.4235294117647062.06
924814AB2-134 E
Adder
6.8847058823529425.852
316084AB2-161 E
Adder
2.8764705882352942.445
316088AB2-174 E
Adder
2.94705882352941152.505
932046AC2-012 E
Adder
5.7529411764705884.89
316311AC2-079 C
Adder
2.71999999999999982.312
932596AC2-079 E
Adder
4.4376470588235293.772
934146AD1-041 E
Adder
1.63058823529411771.386
934576AD1-082 E
Adder
2.2917647058823531.948
316349AD2-085 C
Adder
1.6447058823529411.398
936666AD2-085 E
Adder
2.6835294117647062.281
961611AG1-000B C
Adder
8.1152941176470596.898
941591AE2-156 C
Adder
7.8529411764705886.675
944581AF1-123 C
Adder
19.50352941176470616.578
944582AF1-123 E
Adder
44.6637.961
944591AF1-124 C
Adder
19.5717647058823516.636
944592AF1-124 E
Adder
44.82117647058823538.098
944601AF1-125 C
Adder
19.2023529411764716.322
944602AF1-125 E
Adder
43.9588235294117737.365
944631AF1-128 C
Adder
24.6823529411764720.98
964241AG1-285 C
Adder
6.0305882352941185.126
964242AG1-285 E
Adder
4.0211764705882363.418
3137643SOCKMAN
Adder
0.317647058823529450.27
934612AD1-087 E
Adder
1.55882352941176471.325
935161AD1-151 C
Adder
8.9764705882352947.63
935162AD1-151 E
Adder
5.9847058823529415.087
937482AD2-202 E
Adder
0.456470588235294130.388
938531AE1-072 C
Adder
7.6223529411764716.479
938532AE1-072 E
Adder
3.9729411764705883.377
938821AE1-108 C
Adder
8.4270588235294127.163
938822AE1-108 E
Adder
4.0211764705882363.418
939191AE1-149 C
Adder
5.8976470588235295.013
939192AE1-149 E
Adder
3.93176470588235333.342
939602AE1-190 E
Adder
0.6517647058823530.554
940431AE2-027 C
Adder
7.9682352941176476.773
940432AE2-027 E
Adder
5.3129411764705894.516
940481AE2-033 C
Adder
7.6223529411764716.479
940482AE2-033 E
Adder
5.13882352941176554.368
940541AE2-040 C
Adder
1.35764705882352941.154
940551AE2-041 C
Adder
3.25058823529411762.763
940641AE2-051 C
Adder
7.0152941176470595.963
940642AE2-051 E
Adder
4.67764705882352953.976
941101AE2-104 C
Adder
1.50823529411764711.282
941102AE2-104 E
Adder
2.39764705882352922.038
942461AE2-259 C
Adder
5.83647058823529454.961
942462AE2-259 E
Adder
3.8917647058823533.308
943471AF1-018 C
Adder
3.25058823529411762.763
944641AF1-129 C
Adder
65.7211764705882355.863
3150851SPRUNCC
50/50
0.1690.169
3150861SPRUNCD
50/50
0.1690.169
316303AF2-085
50/50
7.0277.027
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.2422.242
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.08118.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.29711.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
40.62940.629
G-007PJM->LTFIMP_G-007
CMTX_NF
2.112.11
NYPJM->LTFIMP_NY
CLTF
0.9630.963
LGEELTFEXP_LGEE->PJM
CLTF
0.7270.727
WECLTFEXP_WEC->PJM
CLTF
0.3730.373
CPLELTFEXP_CPLE->PJM
CLTF
4.6984.698
TVALTFEXP_TVA->PJM
CLTF
2.952.95
MECLTFEXP_MEC->PJM
CLTF
2.1322.132
LAGNLTFEXP_LAGN->PJM
CLTF
3.6953.695
SIGELTFEXP_SIGE->PJM
CLTF
0.1370.137
O66PJM->LTFIMP_O-066
CMTX_NF
13.41813.418

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 550_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.93 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3411.45
MW Contribution:3.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
1.99411764705882361.695
961792AG1-021 E
Adder
1.69882352941176461.444
961941AG1-037 C
Adder
0.580.493
961942AG1-037 E
Adder
0.38705882352941180.329
963041AG1-153 C
50/50
7.4237.423
963042AG1-153 E
50/50
11.13411.134
964791AG1-342 C
Adder
4.037647058823533.432
964792AG1-342 E
Adder
2.69176470588235262.288
966621AG1-532 C
50/50
1.6521.652
966622AG1-532 E
50/50
1.1011.101
3138533PONTONDP
Adder
0.73882352941176480.628
3145413WATKINS
Adder
0.7917647058823530.673
3145723EMPORIA
50/50
0.5070.507
3147133PAMPLIN
Adder
1.09647058823529430.932
3151531CLOVER1
50/50
15.58115.581
3151541CLOVER2
50/50
15.43615.436
918492AA1-063AE OP
Adder
4.7329411764705884.023
918532AA1-067 E
Adder
0.81647058823529410.694
919692AA2-053 E OP
Adder
4.9082352941176474.172
920042AA2-088 E OP
Adder
12.21058823529411810.379
925785AC1-054 E
Adder
3.9917647058823533.393
926274AC1-105 E
Adder
3.05411764705882362.596
927146AC1-208 E
Adder
4.6176470588235293.925
934521AD1-076 C
Adder
13.97999999999999911.883
934522AD1-076 E
Adder
7.12588235294117746.057
943172AE2-346 E
Adder
0.69647058823529410.592
943902AF1-058 E
Adder
1.4670588235294121.247
944011AF1-069 C
50/50
17.48817.488
944012AF1-069 E
50/50
6.7946.794
959311AF2-222 C
Adder
18.7552941176470615.942
959312AF2-222 E
Adder
12.56588235294117510.681
960081AF2-299 C
50/50
2.2032.203
960082AF2-299 E
50/50
1.4691.469
316141AB2-099 E
Adder
0.290588235294117650.247
900672V4-068 E
Adder
0.410588235294117640.349
923263AB1-132 E OP
Adder
7.1317647058823546.062
923573AB1-173 E OP
Adder
3.84588235294117683.269
924162AB2-060 E OP
Adder
4.9070588235294124.171
924302AB2-077 E O1
Adder
1.53411764705882361.304
924312AB2-078 E O1
Adder
1.53411764705882361.304
924322AB2-079 E O1
Adder
1.53411764705882361.304
925612AC1-036 E
Adder
0.96823529411764710.823
940492AE2-034 E
Adder
3.5152941176470592.988
941031AE2-094 C
50/50
53.52353.523
941032AE2-094 E
50/50
23.97223.972
946281AF1-292 C
50/50
1.8231.823
946282AF1-292 E
50/50
1.2161.216
946301AF1-294 C
Adder
4.09882352941176453.484
946302AF1-294 E
Adder
3.47176470588235332.951
957481AF2-042 C
50/50
67.59667.596
957482AF2-042 E
50/50
45.06445.064
958211AF2-115 C
Adder
2.49294117647058842.119
958212AF2-115 E
Adder
2.1235294117647061.805
3145393UNCAMP
Adder
6.9494117647058825.907
916042Z1-036 E
Adder
32.496470588235327.622
938771AE1-103 C
Adder
3.34117647058823542.84
938772AE1-103 E
Adder
4.6141176470588243.922
933502AC2-165 E
50/50
8.9548.954
3143316POE
50/50
1.5751.575
3145256KINGFORK
Adder
1.11999999999999990.952
3145506HICKORY
50/50
2.4652.465
3150831SPRUNCA
Adder
9.668.211
3150841SPRUNCB
Adder
9.668.211
926662AC1-147 E
Adder
1.49058823529411751.267
926755AC1-161 E
50/50
14.58914.589
935112AD1-144 E
Adder
1.040.884
942341AE2-247 C
Adder
1.681.428
942342AE2-247 E
Adder
2.321.972
943461AF1-017 C
Adder
1.521.292
943462AF1-017 E
Adder
2.482.108
943612AF1-032 E
Adder
1.04470588235294120.888
958502AF2-144 E
50/50
1.5151.515
3151021BRUNSWICKG1
50/50
10.91910.919
3151031BRUNSWICKG2
50/50
10.91910.919
3151041BRUNSWICKG3
50/50
10.91910.919
3151051BRUNSWICKS1
50/50
22.68422.684
3151081ELIZAR1
50/50
3.5963.596
3151101ELIZAR3
50/50
3.6413.641
3152411Z1-086 GT1
50/50
13.99713.997
3152421Z1-086 GT2
50/50
13.99313.993
3152431Z1-086 GT3
50/50
13.99313.993
3152441Z1-086 ST
50/50
24.36424.364
913392Y1-086 E
Adder
2.48823529411764752.115
916192Z1-068 E
50/50
2.1212.121
923832AB2-022 E
Adder
1.40470588235294121.194
923852AB2-025 E
50/50
1.4131.413
923862AB2-026 E
50/50
1.5421.542
938552AE1-074 E
50/50
1.5821.582
938562AE1-075 E
50/50
1.3151.315
939312AE1-162 E
Adder
1.53529411764705871.305
946262AF1-291 E
Adder
1.47176470588235291.251
957492AF2-043 E
Adder
1.6082352941176471.367
901082W1-029 E
Adder
36.1329411764705930.713
917122Z2-027 E
Adder
1.52235294117647071.294
925522AC1-027 E
50/50
1.3731.373
942001AE2-212 C
Adder
2.33058823529411761.981
942002AE2-212 E
Adder
1.55411764705882361.321
957871AF2-081 C
50/50
11.30311.303
957872AF2-081 E
50/50
4.8444.844
958161AF2-110 C
Adder
1.54823529411764721.316
958162AF2-110 E
Adder
2.46235294117647062.093
3147223TWITTYS
Adder
1.07294117647058830.912
926071AC1-086 C
Adder
24.50588235294117520.83
926072AC1-086 E
Adder
11.152941176470599.48
936261AD2-033 C
Adder
14.72588235294117712.517
936262AD2-033 E
Adder
9.8164705882352948.344
933291AC2-141 C
50/50
34.17534.175
933292AC2-141 E
50/50
14.58914.589
934621AD1-088 C
50/50
11.7711.77
934622AD1-088 E
50/50
5.6675.667
939411AE1-173 C
50/50
116.624116.624
939412AE1-173 E
50/50
77.7577.75
916191Z1-068 C
50/50
0.0490.049
933981AD1-022 C
Adder
10.0176470588235318.515
933982AD1-022 E
Adder
5.4529411764705884.635
962572AG1-106 E
Adder
1.3870588235294121.179
962571AG1-106 C
Adder
3.16941176470588242.694
3145946PLYMOUTH TP
Adder
0.36941176470588240.314
3146326AYDLETT TAP
Adder
1.53411764705882361.304
316023AB2-100 C2
50/50
1.1361.136
316185AD1-033 C
50/50
1.3851.385
316233AE1-074 C
50/50
3.143.14
316240AF1-291 C
Adder
2.20823529411764731.877
316258AE1-075 C
50/50
0.4350.435
316274AC1-208 C
Adder
10.48.84
316294AC1-161 C
50/50
5.5655.565
316313AB2-026 C
50/50
0.4750.475
316315AB2-025 C
50/50
0.4950.495
316316AC1-027 C
50/50
0.3550.355
316336AC2-165 C
50/50
11.89711.897
316365AB2-100 C1
50/50
1.1361.136
316405AF2-144 C
50/50
0.370.37
917332KELFORD E
Adder
1.8917647058823531.608
924516AB2-100 E1
50/50
3.4373.437
924517AB2-100 E2
50/50
3.4373.437
926206AC1-098 E
Adder
4.2058823529411773.575
926214AC1-099 E
Adder
1.38941176470588231.181
934065AD1-033 E
50/50
5.675.67
937226AE2-253 E
50/50
6.6076.607
918512AA1-065 E OP
Adder
6.3400000000000015.389
316017AA1-139 ULT1
50/50
1.221.22
316018AA1-139 ULT2
50/50
1.221.22
919153AA1-139 E2
50/50
4.6224.622
919152AA1-139 E1
50/50
4.6224.622
919710AA2-057 E
Adder
4.5541176470588243.871
920692AA2-178 E
Adder
4.6870588235294123.984
923994AB2-040_E
Adder
7.2105882352941176.129
924022AB2-043 E O1
Adder
5.9517647058823535.059
316084AB2-161 E
Adder
6.1764705882352945.25
925122AB2-169 E
Adder
6.5670588235294125.582
316088AB2-174 E
Adder
7.6541176470588246.506
932046AC2-012 E
Adder
14.74823529411764712.536
316311AC2-079 C
Adder
6.4611764705882355.492
932596AC2-079 E
Adder
10.5423529411764718.961
934576AD1-082 E
Adder
4.9211764705882354.183
316349AD2-085 C
Adder
3.8752941176470593.294
936666AD2-085 E
Adder
6.3235294117647065.375
316388AE2-253 GEN
50/50
2.2142.214
961611AG1-000B C
Adder
16.4223529411764713.959
941591AE2-156 C
Adder
20.1617.136
944581AF1-123 C
50/50
51.66651.666
944582AF1-123 E
50/50
118.31118.31
944591AF1-124 C
50/50
51.8551.85
944592AF1-124 E
50/50
118.738118.738
944601AF1-125 C
50/50
50.8750.87
944602AF1-125 E
50/50
116.453116.453
962561AG1-105 C
Adder
10.137647058823538.617
962562AG1-105 E
Adder
6.7588235294117655.745
964241AG1-285 C
Adder
14.29529411764705812.151
964242AG1-285 E
Adder
9.5294117647058828.1
3137643SOCKMAN
Adder
0.8317647058823530.707
932632AC2-084 E
Adder
3.71764705882352953.16
934321AD1-056 C
Adder
7.2164705882352946.134
934322AD1-056 E
Adder
3.91411764705882353.327
934331AD1-057 C
Adder
4.0258823529411773.422
934332AD1-057 E
Adder
2.09647058823529431.782
934501AD1-074 C
Adder
38.4929411764705932.719
934502AD1-074 E
Adder
19.59411764705882716.655
934511AD1-075 C
Adder
9.6235294117647058.18
934512AD1-075 E
Adder
4.8988235294117644.164
934611AD1-087 C
50/50
1.5341.534
934612AD1-087 E
50/50
4.4414.441
935171AD1-152 C
50/50
1.5911.591
935172AD1-152 E
50/50
6.5696.569
937481AD2-202 C
50/50
0.4450.445
937482AD2-202 E
50/50
1.31.3
938531AE1-072 C
Adder
19.8816.898
938532AE1-072 E
Adder
10.3635294117647068.809
939191AE1-149 C
Adder
11.92235294117647210.134
939192AE1-149 E
Adder
7.9482352941176486.756
940431AE2-027 C
Adder
13.27647058823529511.285
940432AE2-027 E
Adder
8.8517647058823537.524
940481AE2-033 C
50/50
19.63119.631
940482AE2-033 E
50/50
13.23413.234
940541AE2-040 C
50/50
3.4933.493
940641AE2-051 C
50/50
23.07223.072
940642AE2-051 E
50/50
15.38115.381
941101AE2-104 C
Adder
3.79294117647058873.224
941102AE2-104 E
Adder
6.0305882352941185.126
944641AF1-129 C
Adder
25.10705882352941421.341
316303AF2-085
50/50
5.5375.537
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.4826.482
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.12546.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.44630.446
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
116.495116.495
G-007PJM->LTFIMP_G-007
CMTX_NF
4.9764.976
NYPJM->LTFIMP_NY
CLTF
2.3122.312
LGEELTFEXP_LGEE->PJM
CLTF
1.8681.868
WECLTFEXP_WEC->PJM
CLTF
0.9550.955
CPLELTFEXP_CPLE->PJM
CLTF
13.58913.589
TVALTFEXP_TVA->PJM
CLTF
8.0788.078
MECLTFEXP_MEC->PJM
CLTF
5.5885.588
LAGNLTFEXP_LAGN->PJM
CLTF
10.14710.147
SIGELTFEXP_SIGE->PJM
CLTF
0.3550.355
O66PJM->LTFIMP_O-066
CMTX_NF
31.68131.681

Details for 8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.31 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4286.26
MW Contribution:4.28
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
2.30941176470588251.963
961792AG1-021 E
Adder
1.96705882352941171.672
963041AG1-153 C
50/50
17.10317.103
963042AG1-153 E
50/50
25.65425.654
964791AG1-342 C
50/50
5.7665.766
964792AG1-342 E
50/50
3.8443.844
3138533PONTONDP
Adder
0.85529411764705890.727
3147133PAMPLIN
Adder
1.261.071
3151531CLOVER1
50/50
28.86828.868
3151541CLOVER2
50/50
28.59928.599
3151581KERR 1
50/50
0.5770.577
3151591KERR 2
50/50
1.6151.615
3151601KERR 3
50/50
1.6151.615
3151611KERR 4
50/50
1.6151.615
3151621KERR 5
50/50
1.6151.615
925785AC1-054 E
Adder
2.96470588235294132.52
926274AC1-105 E
50/50
4.6164.616
942751AE2-291 C
Adder
12.11176470588235310.295
942752AE2-291 E
Adder
8.0741176470588246.863
943902AF1-058 E
50/50
2.342.34
959311AF2-222 C
50/50
22.05622.056
959312AF2-222 E
50/50
14.77814.778
24401205PINNACLE
Adder
1.6670588235294121.417
3151631KERR 6
50/50
1.6151.615
3151641KERR 7
50/50
1.6151.615
3152661PLYWOOD A
50/50
2.0932.093
316118AC1-105 C
50/50
1.5721.572
316131AB2-060 C
50/50
2.042.04
924162AB2-060 E OP
50/50
5.8965.896
924302AB2-077 E O1
50/50
1.8631.863
924312AB2-078 E O1
50/50
1.8631.863
924322AB2-079 E O1
50/50
1.8631.863
925612AC1-036 E
50/50
1.1421.142
940081AE1-250 C
Adder
12.86117647058823510.932
940082AE1-250 E
Adder
8.5741176470588247.288
946301AF1-294 C
Adder
4.7458823529411774.034
946302AF1-294 E
Adder
4.01882352941176453.416
957481AF2-042 C
50/50
129.887129.887
957482AF2-042 E
50/50
86.59186.591
958211AF2-115 C
Adder
2.88588235294117632.453
958212AF2-115 E
Adder
2.45882352941176442.09
3151021BRUNSWICKG1
50/50
25.15825.158
3151031BRUNSWICKG2
50/50
25.15825.158
3151041BRUNSWICKG3
50/50
25.15825.158
3151051BRUNSWICKS1
50/50
52.26552.265
3152411Z1-086 GT1
50/50
33.47433.474
3152421Z1-086 GT2
50/50
33.46533.465
3152431Z1-086 GT3
50/50
33.46533.465
3152441Z1-086 ST
50/50
58.26658.266
957601AF2-054 C
Adder
-1.8-1.53
964211AG1-282 C
Adder
-1.7011764705882353-1.446
942001AE2-212 C
Adder
-2.010588235294118-1.709
3147223TWITTYS
50/50
1.2661.266
936261AD2-033 C
50/50
17.43217.432
936262AD2-033 E
50/50
11.62211.622
933291AC2-141 C
Adder
-32.203529411764706-27.373
934621AD1-088 C
50/50
21.36821.368
934622AD1-088 E
50/50
10.28810.288
316003AC1-222 C
50/50
1.7441.744
316034AC1-036 C
50/50
0.3110.311
316222AC1-221 C
50/50
2.6372.637
316237AB2-079 C O1
50/50
0.4550.455
316238AB2-078 C O1
50/50
0.4550.455
316239AB2-077 C O1
50/50
0.4550.455
316240AF1-291 C
Adder
-1.9317647058823528-1.642
316248AF1-058 C
50/50
0.5710.571
316283AC2-100 C
50/50
2.1162.116
927255AC1-221 E
50/50
6.9166.916
927264AC1-222 E
50/50
7.1497.149
932763AC2-100 E
50/50
4.6734.673
313527AB2-043 C
50/50
0.7110.711
924022AB2-043 E O1
50/50
7.1597.159
316123AC1-075 C
50/50
1.3531.353
925997AC1-075 E
50/50
4.7084.708
316205AC1-080 C
50/50
0.4520.452
926024AC1-080 E
50/50
1.5621.562
962561AG1-105 C
50/50
14.10814.108
962562AG1-105 E
50/50
9.4059.405
964241AG1-285 C
50/50
17.07617.076
964242AG1-285 E
50/50
11.38411.384
934611AD1-087 C
50/50
2.842.84
934612AD1-087 E
50/50
8.2238.223
935171AD1-152 C
50/50
2.8492.849
935172AD1-152 E
50/50
11.76211.762
936161AD2-022 C
Adder
12.15882352941176610.335
936162AD2-022 E
Adder
7.29529411764705856.201
936171AD2-023 C
Adder
7.0929411764705886.029
936172AD2-023 E
Adder
3.8505882352941183.273
937481AD2-202 C
50/50
0.8240.824
937482AD2-202 E
50/50
2.4072.407
938531AE1-072 C
Adder
-16.01294117647059-13.611
940641AE2-051 C
Adder
-21.040000000000003-17.884
942461AE2-259 C
Adder
12.19882352941176510.369
942462AE2-259 E
Adder
8.1329411764705886.913
944641AF1-129 C
Adder
-90.49176470588236-76.918
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.2639.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.06671.066
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.76444.764
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
170.641170.641
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6814.681
NYPJM->LTFIMP_NY
CLTF
2.1082.108
LGEELTFEXP_LGEE->PJM
CLTF
2.7422.742
WECLTFEXP_WEC->PJM
CLTF
1.451.45
CPLELTFEXP_CPLE->PJM
CLTF
19.41719.417
TVALTFEXP_TVA->PJM
CLTF
11.71211.712
MECLTFEXP_MEC->PJM
CLTF
8.3488.348
LAGNLTFEXP_LAGN->PJM
CLTF
14.84614.846
SIGELTFEXP_SIGE->PJM
CLTF
0.5240.524
O66PJM->LTFIMP_O-066
CMTX_NF
29.75629.756
CONTINGENCY 'DVP_P1-2: LN 2201_SRT-A'
 OPEN BRANCH FROM BUS 313725 TO BUS 314563 CKT 1   /*6DRY BREAD   230.0 - 6CLUBHSE     230.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 550_SRT-S'
 OPEN BRANCH FROM BUS 314917 TO BUS 314926 CKT 1                /*8MT STM      500.0 - 8VALLEY      500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314562 to 314563 ckt 1
314322 to 314914 ckt 1
314914 to 314918 ckt 1
314940 to 941030 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AG1-021 was evaluated as a 20.0 MW injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

(No impacts were found for this analysis)

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

(No impacts were found for this analysis)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 1 Cluster 30 for Phase 3 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 30 projects.

 

Table 1: Transition Cycle 1 Cluster 30 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

30

AF1-294

Solar

Dominion

41

41

22.2

Jetersville - Ponton 115 kV

AF2-115

Solar

Dominion

25

25

13.5

AG1-021

Solar

Dominion

20

20

10.8

AG1-166

Solar

Dominion

20

20

6

Lone Pine 115 kV

AG1-167

Solar

Dominion

15

15

4.5

AG1-168

Solar

Dominion

15

15

4.5

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 30 projects will meet the dynamics requirements of the NERC, Dominion Energy, and PJM reliability standards.

 

The load flow case for Phase 2 was used as a starting point and was updated based on latest Cluster 30 data, recommended transmission changes incorporated based on Dominion Energy Phase 2 feedback, and withdrawn generation removed. Cluster 30 projects have been dispatched online at maximum power output with near unity power factor measured at the high-side of the main substation transformer. The dynamic models for Cluster 30 projects were updated based on the latest DP2 data and include any tuning adjustments recommended during Phase 2.

 

Cluster 30 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. During the Phase 2 analysis contingencies were examined around the POIs and no violations were observed as a result of Cluster 30 projects interconnecting.  Due to this the Phase 3 analysis for Cluster 30 focused on the contingencies at Chase City that resulted in instability caused by Cluster 31 and Cluster 40 during Phase 2.  The Phase 3 analysis examined, 8 initial contingencies and 24 sensitivity contingencies were studied, each with a 30 second simulation time period. The studied contingencies included:

 

  • Three-phase faults with normal clearing time.
  • Single-phase bus faults with normal clearing time.
  • Single-phase faults with stuck breaker.

 

Instability was observed for contingencies when the Chase City to AG1-285 Tap 115 kV circuit was tripped. This outage resulted in instability due to insufficient export paths for the generation along the Farmville to Chase City 115 kV path through the radial connection.  Additionally, the Farmville to Chase City 115 kV path is prone to controller instability due to weak grid conditions determined by the composite short circuit ratio assessment.  The instability was caused by the Cluster 31 queue projects. 

 

To following mitigation was tested and all maintain stability:

  1. Adding a new 115 kV line from AG1-285 to Butcher’s Creek.
  2. Moving AF2-222 and AG1-285 to a new 230 kV line from Farmville to Finneywood.
  3. Upgrade the new AG1-285 substation to a breaker and a half scheme to accommodate 2 x 230/115 kV transformers and a 230 kV line from AG1-285 to Finneywood .

 

The Transmission Owner has elected to upgrade the new AG1-285 substation to a breaker and a half scheme to accommodate 2 x 230/115 kV transformers and a 230 kV line from AG1-285 to Finneywood as the mitigation to the instability. This mitigation is required due to the interconnection of the Cluster 31 queue projects. Cluster 30 queue projects did not cause the instability. The mitigation was further tested for all Phase 2 contingencies and no violations were observed.

 

Nearby projects were found to trip based on their protection settings. The protection trip times were increased during Phase 2 analysis and maintained during the Phase 3 analysis:

 

  • AE1-056 tripped for frequencies below 55 hz for more than 0.001 seconds and the relay pick-up time was increased to 0.034 seconds
  • AE1-056 tripped for frequencies above 65 hz for more than 0.001 seconds and the relay pick-up time was increased to 0.020834 seconds
  • AF2-222 tripped for voltages above 1.3 p.u. for more than 0.001 seconds and the relay pick-up time was increased to 0.012501 seconds

 

With the mitigation identified above, the results of the contingencies tested on the RTEP 2027 summer peak case found:

 

  • Cluster 30 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  • The system with Cluster 30 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for inter area modes and 4% for local modes.
  • Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus) and the final voltages are within the steady-state voltage ranges below per Dominion Energy’s transmission planning criteria.
    • P1 Category Contingencies:
      • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.01 to 1.096 p.u. for 500 kV facilities
    • P2, P4, P5, and P7 Category Contingencies:
      • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.00 to 1.096 p.u. for 500 kV facilities
  • No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

No mitigation was needed to connect the Cluster 30 queue projects.

Reactive Power Analysis

The reactive power capability of AG1-021 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-065Earleys 230kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-088Boykins-Handsome 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB1-173Brink-Trego 115kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-100Clubhouse-Lakeview 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-080Perth-Hickory Grove 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-084Dawson-South Justice 115kVPartially in Service - Under Construction
AC2-100Halifax-Person 230kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-033Fentress-Landstown 230 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-103Holland-Union Camp 115 kVSuspended
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-149Disputanta-Poe 115 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-247Myrtle-Windsor 115 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-299Fields 34.5 kVActive
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-153Heritage 500 kVActive
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-532Fields 34.5 kVEngineering & Procurement
V4-068Murphy's 34.5kVIn Service
Y1-086Morgans CornerIn Service
Z1-068Birdneck 34.5kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-088Tarboro-Everetts 230kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 312.A.1.b and as outlined in PJM Manual 14H, Section 13, in Phase III of the Cycle, PJM coordinates with the Affected System Operators to conduct any studies required to determine the impact of the New Service Request on any Affected System and will include the Affected System Study results in Phase III System Impact Study, if available from the Affected System Operator.

If your project required an Affected System Study, the results are shown below from the Affected System Operator.

For more details, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM will list any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG1-021 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionn9220.0Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.Cost Allocated$1,087,573
Dominionn9217.0Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.Cost Allocated$988,419
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$120,627
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$107,877
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$68,806
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$38,074
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$30,011
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$24,385
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Kraken substation into Yeat substationContingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0N/A
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0N/A
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0N/A
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0N/A
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0N/A
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0N/A
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0N/A
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0N/A
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0N/A
Grand Total:$2,465,772

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Discounted Total Cost ($USD)
$18,752,679
Allocated Cost ($USD)
$389,779
Time Estimate
Dec 31 2029

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

FacilityContingency
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-294 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
41.0 MW4.3%$799,036
AF2-115 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
25.0 MW2.6%$487,224
AF2-222500.9 MW52.1%$9,766,518
AG1-021 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
20.0 MW2.1%$389,779
AG1-285374.9 MW39.0%$7,310,120
System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Allocated Cost ($USD)
$107,877
Time Estimate
Dec 31 2029
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$10,680,188
AF1-12414.9488 %$10,717,979
AF1-12514.6652 %$10,514,642
AF1-2940.3084 %$221,144
AF2-04229.0898 %$20,856,758
AF2-1150.1881 %$134,846
AF2-1205.5338 %$3,967,580
AF2-2223.7926 %$2,719,216
AG1-0210.1505 %$107,877
AG1-1243.0179 %$2,163,751
AG1-1355.3024 %$3,801,724
AG1-2852.8388 %$2,035,325
AG1-5365.2677 %$3,776,802

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Discounted Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$1,087,573
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
6BUCKING-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A796.0 MVA
(All)B796.0 MVA
(All)C964.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE2-29113.6 MW3.8%$1,705,384
AF1-294 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
17.8 MW5.0%$2,229,393
AF2-042163.5 MW46.2%$20,532,412
AF2-115 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
10.8 MW3.1%$1,359,435
AF2-22265.0 MW18.3%$8,159,120
AG1-021 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
8.7 MW2.4%$1,087,573
AG1-10523.6 MW6.7%$2,967,877
AG1-28541.9 MW11.8%$5,264,576
AG1-3429.2 MW2.6%$1,160,153

System Reinforcement: n9217.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9217.0 / TC1-PH2-DOM-028
Title
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$40,414,822
Discounted Total Cost ($USD)
$40,414,822
Allocated Cost ($USD)
$988,419
Time Estimate
45 to 46 Months

Contributor

FacilityContingency
6BUCKING-6FARMVIL 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A797.0 MVA
(All)B797.0 MVA
(All)C1116.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AE2-29113.6 MW3.8%$1,550,409
AF1-294 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
17.8 MW5.0%$2,026,247
AF2-042163.5 MW46.2%$18,661,737
AF2-115 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
10.8 MW3.1%$1,235,466
AF2-22265.0 MW18.3%$7,415,536
AG1-021 ⧉ AF1-294 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-294, AF2-115, AG1-021
8.7 MW2.4%$988,419
AG1-10523.6 MW6.7%$2,697,555
AG1-28541.9 MW11.8%$4,784,850
AG1-3429.2 MW2.6%$1,054,602

System Reinforcement: n9681.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9681.0
Title
Upgrade 1.04 Miles of 230kV transmission line 249 from 249/86 to 249/93
Description
Reconductor 1.04 miles of 2*636 ACSR 24/7 MOT 150 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" MOT 250 on 230 kV line 249 between Carson and Chaparral
Total Cost ($USD)
$3,042,004
Discounted Total Cost ($USD)
$3,042,004
Allocated Cost ($USD)
$0
Time Estimate
20 to 21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-021 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-021 could receive cost allocation. Although AG1-021 may not presently have cost responsibility for this upgrade, AG1-021 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1442.0 MVA
LLB1540.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1493.0 MVA
WINB1587.0 MVA
WINC1631.0 MVA

System Reinforcement: b3694.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3694.8
Title
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA.
Description
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA. Upgrade terminal equipment at Carson and Locks to not limit the new conductor rating.
Cost Information
Time Estimate
May 03 2025

Not Contingent

Note: AG1-021 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-021 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1047.0 MVA
(All)B1047.0 MVA
(All)C1204.0 MVA
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA

System Reinforcement: n9200.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9200.0 / TC1-PH2-DOM-005
Title
Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" conductors.
Description
Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$38,691,326
Discounted Total Cost ($USD)
$38,691,326
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-021 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-021 could receive cost allocation. Although AG1-021 may not presently have cost responsibility for this upgrade, AG1-021 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA797.0 MVA
SUMB797.0 MVA
SUMC1115.0 MVA

System Reinforcement: n9201.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9201.0 / TC1-PH2-DOM-006
Title
Replace wave trap at Carson 230 kV (Carson - Sapony).
Description
Replace wave trap at Carson 230 kV (Carson - Sapony).
Total Cost ($USD)
$521,941
Discounted Total Cost ($USD)
$521,941
Allocated Cost ($USD)
$0
Time Estimate
14 to 15 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-021 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-021 could receive cost allocation. Although AG1-021 may not presently have cost responsibility for this upgrade, AG1-021 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA876.0 MVA
SUMB956.0 MVA
SUMC1163.0 MVA

System Reinforcement: n9378.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9378.0 / TC1-PH3-DOM-010
Title
Replace existing 230/500 kV Carson transformer 2 with (4)-480 MVA single phase transformers.
Description
Replace Existing 230/500 kV Carson transformer 2 with (4)-480 MVA Single Phase transformers.
Total Cost ($USD)
$37,801,301
Discounted Total Cost ($USD)
$37,801,301
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-021 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-021 could receive cost allocation. Although AG1-021 may not presently have cost responsibility for this upgrade, AG1-021 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer(Any)
Rating SetRating TypeRating Value
LLA2016.0 MVA
LLB2083.0 MVA
LLC2239.0 MVA
SUMA1707.0 MVA
SUMB1758.0 MVA
SUMC1873.0 MVA
WINA2196.0 MVA
WINB2228.0 MVA
WINC2308.0 MVA

System Reinforcement: n6872
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6872 / dom-047
Title
Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C.
Description
Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C
Total Cost ($USD)
$59,572,939
Discounted Total Cost ($USD)
$59,572,939
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-021 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-021 could receive cost allocation. Although AG1-021 may not presently have cost responsibility for this upgrade, AG1-021 is a potential Aggregate Pool Contributor.

FacilityContingency
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1168.0 MVA
(All)B1195.0 MVA
(All)C1348.0 MVA

System Reinforcement: n9204.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9204.0 / TC1-PH2-DOM-014
Title
Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C
Total Cost ($USD)
$6,764,273
Discounted Total Cost ($USD)
$6,764,273
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-021 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-021 could receive cost allocation. Although AG1-021 may not presently have cost responsibility for this upgrade, AG1-021 is a potential Aggregate Pool Contributor.

FacilityContingency
6SAPONY-AE2-033 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA876.0 MVA
SUMB956.0 MVA
SUMC1163.0 MVA

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG1-021 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-021 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-021 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-021 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-021 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-021 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-021 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-021 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-021 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-021 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG1-021 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-021 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG1-021 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-021 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-021 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-021 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-021 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-021 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: n9139.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9139.0 / TC1-PH1-DOM-073
Title
Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.
Description
Wreck and rebuild 37.41 miles of 500kV transmission line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA. Remove wave traps.
Total Cost ($USD)
$245,455,768
Discounted Total Cost ($USD)
$245,455,768
Allocated Cost ($USD)
$0
Time Estimate
69 to 70 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-021 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-021 could receive cost allocation. Although AG1-021 may not presently have cost responsibility for this upgrade, AG1-021 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9191.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9191.0 / TC1-PH1-DOM-090
Title
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.
Description
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$256,706,175
Discounted Total Cost ($USD)
$256,706,175
Allocated Cost ($USD)
$0
Time Estimate
74 to 75 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-021 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-021 could receive cost allocation. Although AG1-021 may not presently have cost responsibility for this upgrade, AG1-021 is a potential Aggregate Pool Contributor.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9138.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9138.0 / TC1-PH1-DOM-070
Title
ELIM TC1: Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.
Description
Wreck and rebuild 22.59 miles of Line 511 between Carson and Rawlings with three (3) 1351 ACSS/TW and associated substation work.
Total Cost ($USD)
$111,130,292
Discounted Total Cost ($USD)
$111,130,292
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-021 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-021 could receive cost allocation. Although AG1-021 may not presently have cost responsibility for this upgrade, AG1-021 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.

System Reinforcement: n9250.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9250.0 / TC1-PH2-DOM-044
Title
ELIM TC1: Construct a new 22.59 mile line between Carson and Rawlings Substations.
Description
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Total Cost ($USD)
$108,728,086
Discounted Total Cost ($USD)
$108,728,086
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-021 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-021 could receive cost allocation. Although AG1-021 may not presently have cost responsibility for this upgrade, AG1-021 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-040
Title
ELIM TC1: Wreck and rebuild 18.75 miles of Line 594 btwn Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) Dipper at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 18.75 miles of Line 594 between Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$128,018,212
Discounted Total Cost ($USD)
$128,018,212
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-021 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-021 could receive cost allocation. Although AG1-021 may not presently have cost responsibility for this upgrade, AG1-021 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9247.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9247.0 / TC1-PH2-DOM-041
Title
ELIM TC1: Wreck and rebuild 14.02 miles of Line 573 btwn Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 14.02 miles of Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA
Total Cost ($USD)
$99,636,684
Discounted Total Cost ($USD)
$99,636,684
Allocated Cost ($USD)
$0
Time Estimate
48 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-021 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-021 could receive cost allocation. Although AG1-021 may not presently have cost responsibility for this upgrade, AG1-021 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n8492

AG1-021 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492
Title
Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.
Description
Wreck and rebuild one (1) overhead 500kV transmission line that will start at the existing Fentress 500 kV Substation and terminate at the existing Yadkin 500 kV Substation, located approximately 13.5 miles away.
Total Cost ($USD)
$80,172,278
Allocated Cost ($USD)
$120,627
Time Estimate
26 to 27 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$11,942,543
AF1-12414.9488 %$11,984,793
AF1-12514.6652 %$11,757,425
AF1-2940.3084 %$247,251
AF2-04229.0898 %$23,321,955
AF2-1150.1881 %$150,804
AF2-1205.5338 %$4,436,574
AF2-2223.7926 %$3,040,614
AG1-0210.1505 %$120,659
AG1-1243.0179 %$2,419,519
AG1-1355.3024 %$4,251,055
AG1-2852.8388 %$2,275,931
AG1-5365.2677 %$4,223,235

System Reinforcement: n9267.0

AG1-021 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9267.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9267.0 / TC1-PH2-DOM-067
Title
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.
Description
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner substations with single (1) 768.2 ACSS/TW “Maumee” at 250 degrees C. This new line will be on separate transmission towers from the existing Northern Neck and Moon Corner line 1059. Station expansion is required at Northern Neck and Moon Corner to accommodate the new line.
Total Cost ($USD)
$45,730,074
Allocated Cost ($USD)
$68,806
Time Estimate
45 to 46 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$6,811,998
AF1-12414.9488 %$6,836,097
AF1-12514.6652 %$6,706,407
AF1-2940.3084 %$141,032
AF2-04229.0898 %$13,302,787
AF2-1150.1881 %$86,018
AF2-1205.5338 %$2,530,611
AF2-2223.7926 %$1,734,359
AG1-0210.1505 %$68,824
AG1-1243.0179 %$1,380,088
AG1-1355.3024 %$2,424,791
AG1-2852.8388 %$1,298,185
AG1-5365.2677 %$2,408,923

System Reinforcement: n9259.0

AG1-021 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9259.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9259.0
Title
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Description
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Total Cost ($USD)
$25,304,902
Allocated Cost ($USD)
$38,074
Time Estimate
38 to 39 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$3,769,444
AF1-12414.9488 %$3,782,779
AF1-12514.6652 %$3,711,014
AF1-2940.3084 %$78,040
AF2-04229.0898 %$7,361,145
AF2-1150.1881 %$47,599
AF2-1205.5338 %$1,400,323
AF2-2223.7926 %$959,714
AG1-0210.1505 %$38,084
AG1-1243.0179 %$763,677
AG1-1355.3024 %$1,341,767
AG1-2852.8388 %$718,356
AG1-5365.2677 %$1,332,986

System Reinforcement: n8492.1

AG1-021 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.1
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.1
Title
Two Breaker Additions at Fentress Substation.
Description
Install Two 5000 amp GIS Breakers at Fentress Substation to connect the new 500 kV line 5005.
Total Cost ($USD)
$19,945,879
Allocated Cost ($USD)
$30,011
Time Estimate
30 to 36 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$2,971,158
AF1-12414.9488 %$2,981,670
AF1-12514.6652 %$2,925,103
AF1-2940.3084 %$61,513
AF2-04229.0898 %$5,802,216
AF2-1150.1881 %$37,518
AF2-1205.5338 %$1,103,765
AF2-2223.7926 %$756,467
AG1-0210.1505 %$30,019
AG1-1243.0179 %$601,947
AG1-1355.3024 %$1,057,610
AG1-2852.8388 %$566,224
AG1-5365.2677 %$1,050,689

System Reinforcement: n8492.2

AG1-021 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.2
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.2
Title
Expand Yadkin Substation to accommodate the new 500 kV line.
Description
Expansion of yadkins 500 kV switchyard to accommodate the new 500 kV line which includes addition of 5000 amp GIS breakers and relocation of the existing suffolk -yadkin 500 kV line#565
Total Cost ($USD)
$16,207,123
Allocated Cost ($USD)
$24,385
Time Estimate
15 to 16 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$2,414,229
AF1-12414.9488 %$2,422,770
AF1-12514.6652 %$2,376,807
AF1-2940.3084 %$49,983
AF2-04229.0898 %$4,714,620
AF2-1150.1881 %$30,486
AF2-1205.5338 %$896,870
AF2-2223.7926 %$614,671
AG1-0210.1505 %$24,392
AG1-1243.0179 %$489,115
AG1-1355.3024 %$859,366
AG1-2852.8388 %$460,088
AG1-5365.2677 %$853,743

System Reinforcement: b4000.325

AG1-021 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.326

AG1-021 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.327

AG1-021 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: s3047.2

AG1-021 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: s3047.2
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3047.2
Title
Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.
Description
Install (2) 1400 MVA 500-230 kV transformers and associated 500 kV and 230 kV equipment (breakers, switches, leads) at Vint Hill Substation to supply the area with a 500 kV source Cut and loop 500 kV line #535 Loudoun – Meadowbrook and #569 Loudoun - Morrisville as the 500 kV sources into the proposed 500 kV ring bus Vint Hill Substation will be expanded to the north of the existing site to accommodate the 500 kV ring required for the addition of the new transformers Existing terminations for 230 kV line #2174 Wheeler – Vint Hill, line #2101 Bristers – Vint Hill, and line #2163 Liberty – Vint Hill will be rearranged to terminate into the expanded Vint Hill Substation 230 kV line #2114 Remington CT – Rollins Ford will also be cut and looped into the expanded Vint Hill Substation due to spatial constraints along the existing right-of-way.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.312

AG1-021 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.312
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.312
Title
Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.
Description
Rebuild 500kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. New conductor to have a summer rating of 4357 MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.313

AG1-021 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.313
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.313
Title
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Description
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.356

AG1-021 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.356
Title
Build a new 500 kV line from Vint Hill to Wishing Star.
Description
Build a new 500kV line from Vint Hill to Wishing Star. The line will be supported on single circuit monopoles. New conductor to have a summer rating of 4357 MVA. Line length is approximately 16.59 miles
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.357

AG1-021 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.357
Title
Build a new 500 kV line from Morrisville to Vint Hill.
Description
Build a new 500kV line from Morrisville to Vint Hill. New conductor to have a summer rating of 4357 MVA. Line length is approximately 19.71 miles.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.354

AG1-021 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.354
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.354
Title
Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.
Description
Install terminal equipment at Wishing Star substation to support a 5000A line to Vint Hill. Update relay settings for 500kV Lines #546 and #590.
Cost Information
Cost Alloc Type
Contingent

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG1-021


AG1-021 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
StabilityDominionn9630.0 / TC1-PH3-DOM-013Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Topology20.0 MW2.1%Cost Allocated$389,779
Contributions into Topology or Eliminated Reinforcement Total:$389,779
AG1-021 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$120,627
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$107,877
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$68,806
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$38,074
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$30,011
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$24,385
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.Contingent$0
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.Contingent$0
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.Contingent$0
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.Contingent$0
Dominionb4000.348Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0
Dominionb4000.346Cut-in 500kV line from Kraken substation into Yeat substationContingent$0
Dominionb4000.345Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0
Region Topology Upgrade Total:$389,780

Attachments

AG1-021 One Line Diagram

AG1-021 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.